 Passive Radon Control System for New Construction
                    Architectural Drawings
                              of:
          1) Passive radon control system
          2) Crawlspace radon control system
          3) Additional fan for active system

          for one and two -family dwellings
            These architectural drawings are intended for use by
          architects, home builders, designers, radon mitigators and
          others interested in the installation of passive radon control
             systems in one and two -family dwellings. For more
          information on radon and radon-resistant new construction
              call 1-800-55RADON or see the EPA web page:
                	www.epa.gov/iaq	   	

-------
 PASSIVE SUB-SLAB DEPRESSURIZATION  RADON
 CONTROL SYSTEM FOR NEW  CONSTRUCTION

 NOTES:
 1. ALL CONCRETE SLABS THAT  COME IN CONTACT  WITH  THE  GROUND SHALL
   BE LAID OVER A  GAS PERMEABLE MATERIAL MADE UP  OF EITHER A MINIMUM
   4" THICK UNIFORM LAYER OF CLEAN  AGGREGATE, OR A MINIMUM 4" THICK
   UNIFORM LAYER OF SAND, OVERLAIN BY A LAYER OR  STRIPS OF MANUFACTURED
   MATTING DESIGNED TO ALLOW THE LATERAL FLOW  OF SOIL  GASES.

2. ALL CONCRETE FLOOR SLABS SHALL  BE DESIGNED AND CONSTRUCTED
   IN ACCORDANCE WITH LOCAL  BUILDING CODES. ADDITIONAL  REFS-'
   AMERICAN CONCRETE INSTITUTE  PUBLICATIONS, "ACI302.1R"  &
   "ACI332R", OR  THE POST  TENSIONING INSTITUTE  MANUAL, "DESIGN
   AND CONSTRUCTION OF POST-TENSIONED SLABS ON GROUND".

3. ALL OPENINGS, GAPS  AND  JOINTS IN FLOOR AND WALL ASSEMBLIES IN
   CONTACT SOIL OR GAPS  AROUND PIPES, TOILETS, BATHTUBS OR
   DRAINS PENETRATING THESE ASSEMBLIES  SHALL  BE  FILLED OR CLOSED
   WITH MATERIALS THAT PROVIDE  A PERMANENT AIR-TIGHT SEAL.  SEAL
   LARGE  OPENINGS  WITH NON-SHRINK MORTAR, GROUTS OR EXPANDING
   FOAM MATERIALS  AND SMALLER  GAPS WITH AN ELASTOMERIC JOINT
   SEALANT, AS DEFINED IN  ASTM C920-87.

4. VENT PIPES  SHALL BE INSTALLED SO THAT ANY RAINWATER  OR
   CONDENSATION DRAINS DOWNWARD INTO  THE GROUND  BENEATH  THE
   SLAB OR SOIL-GAS-RETARDER MEMBRANE.

5. CIRCUITS SHOULD BE A MINIMUM 15 AMP, 115  VOLT.
                                              EXHAUST (10' FROM OPENINGS INTO
                                                      CONDITIONED SPACES OF BUILDING)
                                                    12" MIN. ABOVE ROOF
                             JOIST
LIVING AREA


       INTERIOR PARTITION

   FLOORING —i
                             JOIST
     GRADE
     LEVEL
   CAP  BLOCK OR OTHER SEAL
   ON HOLLOW BLOCK WALLS

   WATERPROOF SEALANT APPLIED
   TO EXTERIOR WALLS

   SOIL-GAS-RETARDER MEMBRANE (MIN.
   6-MIL POLYETHYLENE SHEETING OR
   EQUIVALENT); OVERLAP SEAMS 12" MIN.

   -SEAL OPENINGS IN SLAB AND
   AROUND PENETRATIONS; NOTE 3
                                                                                          ELECTRICAL JUNCTION BOX
                                                                                          FOR FUTURE INSTALLATION
                                                                                          OF VENT FAN: NOTE  5.

                                                                                      ELECTRICAL JUNCTION BOX
                                                                                      FOR FUTURE INSTALLATION
                                                                                      OF WARNING DEVICE: NOTE 5.
                                                                                      3"-4" DIA. VENT PIPE
                                                                                      (PVC OR EQUIVALENT)
SLAB; NOTE 2

MIN. 4" THICK LAYER
OF GAS PERMEABLE
MATERIAL; NOTE 1
                                                                                     PVC T-FITTING (OR  EQUIVALENT)
                                                                                     TO  SUPPORT  VENT  PIPE

-------
ADDITIONAL COMPONENTS  REQUIRED FOR ACTIVATION
OF PASSIVE SUB-SLAB  DEPRESSURIZATION  OR
CRAWLSPACE RADON CONTROL SYSTEM

NOTES:
1.  NSTALL  THE VENT FAN IN THE VERTICAL RUN OF THE VENT PIPE.
   THE SIZE AND  AIR MOVEMENT CAPACITY OF THE  VENT FAN SHALL
   BE SUFFICIENT TO CREATE AND MAJNTAN A PRESSURE FIELD
   BENEATH  THE SLAB OR CRAWLSPACE MEMBRANE  THAT IS LOWER
   THAN THE PRESSURE ABOVE THE SLAB OR MEMBRANE.

2.  ALL POSITIVELY PRESSURED PORTIONS  OF THE VENT PPE AND
   FAN SHALL BE LOCATED OUTSIDE THE  HABITABLE SPACE
   THE BUILDING.

3.  PROVIDE A VISIBLE OR AUDIBLE WARNING  SYSTEM TO
   ALERT THE BUILDING OCCUPANT IF THERE IS A LOSS
   OF PRESSURE OR AIR FLOW IN THE  VENT PIPE.
EXHAUST (1C1 FROM OPENWGS WTO
        CONDITIONED SPACES' OF BUILDING)
      12" MIN. ABOVE  ROOF
            FAN COUPLING TO PPE

                    ROOF BRACE
                                                  FAN; NOTE 1
                                                  & NOTE 2
                                                                                      ELECTRICAL
                                                                                      JUNCTION BOX
                                 LIVING AREA
                                                                                SYSTEM FAILURE
                                                                                DEVICE: NOTE 3.
                               INTERIOR  PARTITION

                           FLOORING

-------
PASSIVE RADON CONTROL SYSTEM IN
CRAWL  SPACE  FOR  NEW  CONSTRUCTION

NOTES
1. (STALL A LENGTH OF 3" OR 4" DIAMETER  PERFORATED DRAIN
  TLE HORIZONTALLY BENEATH THE  SHEETWG AND CONNECT
  TO THE "T" FITTWG WITH THE VERTICAL STANOPPE THROUGH
  THE SOL-GAS-RETAROER MEMBRANE.  THE HORIZONTAL PPE
  SHOULD NORMALLY BE PLACED PARALLEL TO THE LONG
  DIMENSION OF THE HOUSE AND SHOULD EXTEND NO CLOSER
  THAN 6 FEET TO THE FOUNDATION WALL.

2. VENTILATE CRAWLSPACES IN CONFORMANCE  WITH
  LOCAL COOES; VENTS SHALL BE OPEN TO THE
  EXTERIOR AND BE OF NONCLOSEABLE DESIGN.
3. CIRCUITS SHOULD BE  A MNMUM  15 AMP. 115 VOLT.
                                         EXHAUST (W FROM OPEMNGS WTO
                                             ,    CONDITIONED SPACES OF BUB.DNG)
                                               12" MM. ABOVE ROOF
                              WTERIOR PARTITION

                          LIVING  AREA
                              SEAL AROUND
                              FLOOR PENETRATIONS
                                                                               SUPPORT
                                                                               STRAPPING
   3"-4" DIA. VENT
   (PVC  OR EQUIVALENT)
                          CAP BLOCK OR OTHER SEAL
                          ON HOLLOW  BLOCK WALLS
                          CRAWL SPACE
                          NOTE 2
                                                         ELECTRICAL JUNCTION BOX
                                                         FOR FUTURE NSTALLATWN
                                                         OF VENT FAN; NOTE 3.

                                                     ELECTRICAL JUNCTION BOX
                                                     FOR FUTURE INSTALLATION
                                                     OF WARMNG DEVICE: NOTE 3.
 GRADE
 LEVEL
                      r
SOL-GAS-RETAROER MEMBRANE SEALED AGAINST
WALL AND AROUND PENETRATIONS (MN. 6-ML
POLYETHYLENE SHEETING OR EQUIVALENT)

PERFORATED DRAW
TIE; NOTE 1
  -SEAL MEMBRANE AROUND
   PPE PENETRATION

ADJOtiNC  SHEETS OF
MEMBRANE OVERLAPPED
AND SEALED —,
                                                                             PVC T-FUTING (OR EQUIVALENT)
                                                                             TO SUPPORT  VENT PPE

-------