EPA 510-B-94-004
            UNITED STATES ENVIRONMENTAL PROTECTION AGiENCY
                            REGION 10
                          1200SixthAvenue
Attn of:  WD-133        Seatde,Washington98101
                      February  11,  1994


RE:  SEVENTH EDITION OF LEAK DETECTION METHODS     /

Dear Interested Party:

     The U.S. Environmental Protection Agency (EPA),  Region 10,
Underground Storage Tank (UST)  program,  acting at the request of
EPA Headquarters and the other  EPA  Regions, has compiled the
following list of leak detection methods that appear  to have met
or exceeded the accuracy requirements  stated  in the federal UST
regulations (40 CFR 280) .  Manufacturers listed have  provided
this office with certifications that their product (s)  meet
performance standards described in  the Standard Test  Procedures
for Evaluating Leak Detection Methods  (EPA/530/UST-90/xxx) .

     The list is divided into seven sections  based on method:
Volumetric .Tank Tightness Testing,  Nonvolumetric Tank Tightness
Testing, Automatic Tank Gauging Systems,  Statistical  Inventory
Reconciliation Method, Vapor-phase  Out-of-tank Product Detectors,
Liquid-phase Out-of-tank Product Detectors, Pipeline  Leak
Detection Systems, and Other Methods (Those for which no
established EPA Procedures are  available. ) .

     Each section includes 1) the manufacturer's name,  address
and phone; 2) the product name  and  model; 3)  accuracy and
applicable comments on the product  as  stated  by the evaluating
party, including probability of false  alarm (Pfa) ,  probability of
detection (Pd) , and operational limitations and requirements such
as tank size and product level; and 4)  the name of the evaluator
and evaluation date.

     The changes from the SIXTH EDITION are highlighted in PP§.
EPA has not evaluated these certifications, and inclusion ontfiis
list in no way states or implies that  EPA approves or certifies
any of these products.  Users are also advised to contact their
state UST program because several states maintain a more
restrictive list of leak detection  methodologies.

     Contact Harold Scott at (206)  553-1587 for any additions,
corrections, or comments.

                              Sincerely,
                              Joan Cabreza,  Chief
                              Underground Storage Tank  Section
                                                        f 'Printed on Recycled Paper

-------

-------
                                        SEVENTH EDITION
  LEAK DETECTION LIST OF METHODOLOGIES USED




                     FOR                  ~



           UNDERGROUND STORAGE TANKS






U.S. Environmental Protection Agency,  Region 10




               February  11,  1994

-------

-------
                        TABLE OP CONTENTS





                                                             PAGE






Disclaimer Notification.	-	n



Volumetric Tank Tightness Methods..........•••••••«	l



Nonvolumetric Tank Tightness Methods	8



Automatic Tank Gauging systems	• - •	io



Statistical Inventory Reconciliation Methods	16



Vapor-phase Out-of-tank Product Detectors	«	18



Liquid-phase Out-of-tank Product Detectors	20



Pipeline Leak Detection Systems	23



Other  Methods		-	•		• •	28

-------

-------
                          .  DISCLAIMER

          The U.S. Environmental  Protection Agency  (EPA),  Region
10, Underground Storage Tank  (UST)  program, acting  at  the  request
of EPA Headquarters and the other EPA Regions, has  compiled the
following list of leak detection  methods  that appear to have met
or exceeded the accuracy requirements stated in  the federal UST
regulations (40 CPR 280).  Manufacturers  listed  have provided
this office with certifications that  their product(s)  meet
performance standards described in  the Standard  Test Procedures
for Evaluating Leak Detection-Methods-(EPA/530-/Ct6V-90/xxx).

     EPA has not evaluated these  certifications, and inclusion on
this list in no way states or implies that EPA approves or
certifies any of these products.  Users are also advised to
contact their state UST program because several  states maintain a
more restrictive list of. leak .defection methodologies;.
         .' •  .     .         .    -- •••' .*?         - '-. - •• -f. -aT  " --. •
                                ii

-------

-------
                               VOLUMETRIC TANK TIGHTNESS TB8TINO METHOD  99% 6 0.10 gph
Tanks 0-100% full
Tanks to 15,000 gal
Evaluator/Date

Law Engineering
12/15/90
Gillbarco
7300 W. Friendly Avenue
P.O. Box 22087
Greensboro, NC 27420
(919) 547-5000
Alert 1000
Andover Controls Corporation
300 Brickstone Square
Andover, HA 01910
(508) 470-0555
                                          Alert 4000
AC8+ and 256+
Pfa-4.5% 6 0.05 gph
Pd«>95.5% @ 0.10 gph
Tanks >60% full
Tanks to 30,000 gal
Pfa-3.7% e 0.05 gph
Pda96.3% 9 0.10 gph
TaqkP 20-95% full
Xanjks to 15,000 gal

Pfa«3.5% @ 0.05 gph
Pd-96.5% e 0.10 gph
Tanks 50%-90% fulj.
Tanks to 15,000 gal
HRZ
3/17/92
                                                            Ken Vilcox Associate*
                                                            5/20/92
Ken Wilcox Associates)
2/3/92
Associated Environmental Systems
3651 Pegasus Dr. Suite 102
Bakerefield, CA 93308
(80S) 393-2212
ACS B
(Version 1-overfill)
rts-a..a.» e u.ua gpn
Pd-98.9% 6 0.10 gph
Oyerfill required
      to 75,000 gal
                                                            Ken HilcoX Avsocifttl
2/28/92
                                          AES System II
                                          (Version 2-underfill)
                              Pfa«3% @ 0.05 gph
                              Pd-99% @ 0.10 gph
                              Tank > 50% full
                              Tanks to 30,00 gal
                              Vista Research
                              7/8/91
                                                            1  VTT

-------
Control Engineers,
107 Henard Road
Houma, LA 70361
(504) 872-4541
Ino,
CEI 3000 Tank Models TLP2
(Rapid and Normal Test Mode)
Pfa«5% 9 0.05 gph-
Pd-95% 8 0.1 gph
Pfa-0.08% i 0.05 gph
Pd-99.2% f 0.1 gph
Tanki at least 95% full
Tanks to 15,000 gal
MRZ
6/26/92
EHCO Hheaton
114 MacKenan Dr.
Gary, NC 27511
(800) 342-6125
                       EBCO system Model Q2001
                              Pfa-5% 6 0.05 gph
                              Pd-95% 8 0.10 gph
                              Tank" >95% full
                              Tanjcs to 15,000 gal
                              MRI
                              9/25/91
Oilbarco
7300 H. Friendly Ave.
P.O. Box 22087
Greensboro, NC 27420
(919) 547-5000
                       TM-2/TM-3/EMC*
                       PA 0264XXXOOOO Probe
                                          TM-2/TM-3/EMC*
                                          PA 0265XXXOOOO Probe
                                          Oilbarco Precision
                                          Teat System
Pfa»<0.10% @ 0.071 gph
Pd-99% 6 0.10 gph
Tank >95% full
Tanks to 15,000 gal

Pfa-1.0% 6 0.069 gph
Pd«99% 8 0.10 gph
Tank >95% full
Tanjica to 15,000 gal

Pfa-0.04% 3 0.05 gph
Pd»99.9% 6 0.10 gph
Tank >95% full
Taints to 12,500 gal
                                                            MRI
                                                            8/28/91
                                                                                   MRI
                                                                                   8/28/91
                                                                                   MRI
                                                                                   1/16/91
Hasstech, Inc.
5360-E Eastgate Mall
San Diego, CA 92121
(619)457-5880
                       Leak Computer
Pfa-5% 6 0.05 gph
Pd«95% @ 0.10 gph
Overfill required
Tanjtp to 12,000 gal
Manufacturer claims 20,000 gal
limit based on statistical
interpretation of test data
and results
                                                            Risk Reduction
                                                            Engineering Lab
                                                            9/12/90
                                                       2 VTT Continued

-------
                                                                       P£a-99% 6 0.10 gph
                                                                       Tanks 0-100% full
                                                                       Tanks to 15,000 gal
                                                            Law Engineering
                                                            4/17/91
Heath consultants Inc.
9030 Monroe Road
Houston,  TX 77061
Quick Check 2000
Pfa-3.1% 6 O.OS gph
Pd-96.9% @ 0.10 gph
Overfill required
Tanks to 10,000 gal
MRI
3/22/90
                                          Petro Tite XI
                              Pfa-4.8% e 0.07 gph
                              Pd«9S.2% 8 0.10 gph
                              Overfill required
                              Tanks to 30,000 gal
                              Ken ffilcox Associate!
                              1/11/93
                                          Petro Comp
                              Pfa«0.98% i 0.05 gph
                              Pd-99+% 9 0.10 gph
                              Overfill required
                              Tanks to 15,000 gal
                              Ken Wilcox Associate*
                              12/15/91
Horner Creative Products
212 Morton Street
Bay City, MI 48706
(800) 443-0711
Horner Ezy Chek I
(manual)
                                          Horner Ezy Chek II
                                          (volumetric)
Pfa-1% e 0.05 gph
Pd-99% @ 0.10 gph
Overfill required
Tanks to 12,000 gal
                              Pfa-0.05% e 0.05 gph
                              Pd-99.95% 8 0.10 gph
                              Overfill required
                              Tanks to 12,000 gal
                                                                        Pfa*4?21% e 0.05 gph
                                                                        Pd-95.79% @ 0.10 gph
                                                                        Underfill @ 98% full
                                                                        Tanks to 12,000 gal
W. A. Kibbe 6
Associates
10/3/90
                              W. A. Kibbe
                              Associates
                              9/18/90
                                                            w. A. Kibbe  6
                                                            Associates
                                                            6/25/90
                                                       3 VTT Continued

-------
Ibex Industries
Canter
2014 S. Union Avenue, Suite 103
Bakersfield, CA 93307
(805) 835-8910

Incon Environmental
P.O. Box 638
Saco, HE 04072
(800) 872-3455
                 Ibex Precision Test System    Pfa»0.5% S 0.05 gph

                                               Pd-99.5% t 0.10 gph
                                               Tank mitt be >90% full
                                               Tanki to 18,000 gal
                 TS 2000
                                          TS 1000
                              Pfa«0.05%  @  0.058 gph
                              Pd-99.5% e 0.10 gph
                              Tank must  be >50% full
                              Tanks  to 15,000 gal
                               • no
                              Pfa-0.8% at  0.05 gph
                              Pd-99.2% at  0.10 gph
                              Tank must  be >50% full
                              Tanks  to 15,000 gal
                                                           Applied Research

                                                           12/12/90
                              Ken Hilcox Associates
                              5/10/91     t
                                                                             Ken Hilcox Associates
                                                                             8/5/92
Keekor Environmental Products
14806 North 74th St.
Scottsdale, AZ 85260
(602) 443-0001
                  FBO-800/801  Fuel  Inventory
                  and Environmental Monitor
                              Pfa-5.0% 8 0.1 gph
                              Pd-95.0% e 0.1 gph
                              Tanks 90-95% full
                              Tanks to 15,465 gal
                              Keekor Bnv.  Products
                              11/5/91
 Leak Detection Systems,
 152  King Street
 Cohasaet, MA 02025
 (617)  383-2305
Inc.
 Marley Pump Company
 5800 Foxridge Drive
 Mission,  KS 66202
Tank Auditor
RTD V.2.16
                  Sonic Technology (ST)
                  1400-1800 Series Tank
                  Monitoring System
Pfa«0.02 6 0.05 gph
Pd-99.98% e 0.10 gph
Overfill required
Tanks to 15,000 gal
A statistical evaluation of
this method by Ken Hilcox fi Assoc.
have shown this method can meet
the P£a<5% and Pd>95% for tanks to
50,000 gal.
Ken Hilcox Associates
12/11/90
                              Pfa-3.1% e O.OSgph
                              Pd-96.9% 6 O.lgph
                              Tanks must be >25% full
                              Tanks to 18,000 gal
                              ADA Technologies
                              10/12/92
 NDB Environmental Corporation
 2902 Oregon Court, Suite Bl
 Torranee,  CA 90503
 (213) 542-4342
                  Computerized VPLT Tank Leak
                  System, Model A


                               4 VTT Continued
                              Pfa*5% 6 o.OS gph
                              Pd-99% « 0.10 gph
                              Overfill required
                              Tanks to 75,000 gal
                              Vista Research
                              3/4/91

-------
                                                                       Pfa»0.3% 6 0.05 gph
                                                                       Pd-99.7% t 0.10 gph
                                                                       Underfill method
                                                                       Tanka to 12,000 gal
                                                                                                     Viata Research
                                                                                                     11/7/90
3/C Tanks Corporation
Fiberglass Tower
Toledor  OH 43699
(419)  248-5475
                                         * O/C Tanks Hydrostatic
                                         Tank Test for DW Tanks
                             Pfa-1.3%  6  0.05 gph
                             Pd-99.9%  @  0.10 gph
                             Tanks  0-100%  full
                             Tanks  to  30,000 gal
                              Vista Research
                              5/15/91
OTEC Inc.  (formerly ARCO HTC)
United Detection Systems Inc.
3466 Hwy 41
De Pere, WI 54155
(800) 448-1278
                                         HTC  (2nd and 3rd Generation)
                              Pfa-0.5%  6 0.05 gph
                              Pd-  99.4% 8 0.10 gph
                              Tank > 60%  full
                              Tanks to  15,000 gal
                                                                                                     Ken Wilcox Associate*
                                                                                                     1/23/91
Pncumercator Company
120 Finn Court
Farmingdale, NY 11735
(516) 293-8450
ProBco
7439 E. Hillsborough Ave,
Tampa, FL 33610
(800) 981-9421
                                          Pneumercator Precision
                                          Precision Tank Leak Detector
                                          Sure Test "
                                                                       Pfa-0.005% £  0.05 gph
                                                                       Pd-97.2%  6 0.05 gph
                                                                       Tank must be  >50% full
                                                                       Tanks to  18,000 gal
                                                            Ken Wilcox Associate*
                                                            9/26/91
                                                            ADA Technologies
                                                            8/19/91
Purpora Engineering,
2016 H. Bender Road
                     Inc.
  .
 (414) 228-7631

 Red Jacket Electronics
 5800 Foxridge Drive
 Mission, KS 66202
 (913) 831-5700
Purpora 706 Process
                                          RLH 5000,  RLM 5001
                                          and RLM 9000
Pfa-1.8% 6 0.05 gph
Pd-99.9% @ 0.10 gph
Overfill reouired
Tanks to 15/000 gal

Pfa*0.5% 6 0.05 gph
Pd-99.5% @ 0.10 gph
Tank must be >50% full
Tanks to 15,000 gal
Ken Wilcox Associate*
6/11/91
                                                            Ken Wilcox Associate*.
                                                            6/11/91
                                                       5 VTT Continued

-------
                                          ATO Automatic Tank
                                          Gauging System
                                            Pfa«<0.011 @ 0.05 gph
                                            Pd->99.99999% 8 0.10 gph
                                            Tanks to  15,000 gal
                                            Tanks 15" to 95% full
                                                            Campbell  Scientific,
                                                            Inc.
                                                            12/1/90
Integrated Product Systems,
Texas
506 Sandau Road, Suit* 200
San Antonio, TX 78216
(210) 525-1333
Inc.
Remote Tank Management

System RTH-I
Pfa-1% 8 0.10 gph

Pd-99.5% e 0.10 gph
Threshold leak
detection 8 0.05 gph
System detects tank and
and line leaks
The University of
           \
at San Antonio
3/21/91
                                                                         :t|
Ronan Engineering
21200 Oxnard St.
Woodland Hills, CA 91367
(818) 883-5211
              X-76 ETH Electronic Tank
              Monitor System
                              Pfa-4.66% 6 0.05 gph
                              Pd-95.34% e 0.10 gph
                              Tanks to 15,00 gal
                              Tanks must be >10% full
                              Ken Hilcox Associate*
                              11/21/91
Schuster Instruments, Inc.
211 Grover St.
Kawkawlin, MI 48631
(517) 684-6638
                                          Tel-a-Leak I
                                            Pfa-0.14% e 0.05 gph
                                            Pd«99.86% 6 0.10 gph
                                            Overfill required
                                            Tanks to 15,250 gal
                                                            W. A. Kibbe 6
                                                            Associates
                                                            11/26/90
Soil Test
86 Albrecht Drive
Lake Bluff, IL 60044
(800) 323-1242
Tank Automation, Inc.
701 Brazos, Suite 500
Austin, TX 78701
 (512)  320-9092
              Ainlay Tank 'Tegrity Tester
              S-3
              APTT System
              R-2
                              Pfa-1% Q 0.05 gph
                              Pd-99% e 0.10 gph
                             "Tank must be 100% full
                              Tanks to 15,000 gal
                              Pfa-1% 8 0.05 gph
                              Pd-99% 6 0.10 gph
                              Overfill required
                              Tanks to 15,000 qal
                              Law Engineering
                              11/28/90
                              Wildwood Engineering
                              11/14/90
 Triangle Manufacturing
 172  West Verdugo Avenue
 Burbank, CA 91502-2132
 (818)  840-7020
              T.S.I. System 4000
                              Pfa=4.8% @ 0.05 gph
                              Pd»99.6% @ 0.10 gph
                              Tank must be >50% full
                              Tanks to 15,000 gal
                              United  States
                              Testing,  Ine.
                              4/2/91
                                                       6 VTT Continued

-------
uSTest
P.O. Box 53835
Lafayette, LA 70505
(318) 981-9421
   UST 2000/P
Pfa <1% 8 0.05 gph
Pd >99% 6 0.10 gph
Tank must be >95% full
Tanks to 45,000 gal
Ken Wilcox
7/6/92
                                                                                                                 Associate*
Veeder-Root
125 Powder Forest Drive
Simsbury, CT 06070-2003
(203) 651-2700
   TLS-250,  TLS-2SOi,TLS-350
   8472 Digital Sensing  Probe
   (Capacitance)
Pfa*<0.1t 6 0.071 gph
Pd«99% £ 0.10 gph
Tank must be >50% full
Tanks to 15,000 gal
MRI
4/25/91
                                          TLS-250, TLS-250i,TLS-350
                                          8473 Digital Sensing Probe
                                          (Magnetostrictive
                                 Pfa-1.0* 6 0.069 gph
                                 Pd«9$% @ 0.10 gph
                                 Tank'must be >50% full
                                 Tanks to 15,000 gal
                              MRI
                              4/26/91
William M. Wilson's Sons, Znc,
P.O. Box 309
Lansdale, PA 19446
(215) 855-4631
   Gaaboy ATOS-Leak Detection
   Model TMS 500
Pfa-1.8% @ 0.05 gph
Pd-98.2% 6 0.10 gph
Tank must be >50% full
Tanks to 15,000 gal
Ken Wilcox Associates
5/10/91
Xerxes Corporation
7901 Xerxes Ave. South
Minneapolis, MN 55431
(612) 887-1890
*  Truchek / DWT IX
Pfa»2.5% 6 0.05 gph
Pd-97.5% 6 0.10 gph
Tanks 0-100%  full
Tanks to 18,000 gal
R. Plunket
6/7/91
        motnoui
                                          if 4-K.
                                                       7 VTT Continued

-------
                             ftOMVOLUHCTRIC gAWK glCBMBSg ggSTIHO METHOD	(EP*/??0/imT-*0/QQ?,l
Manufacturer

Gilbarco
7300 H. Friendly Ave.
P.O. Box 22087
Greensboro, NC 27420
(919) 547-5000
Test Method Name/Model

Alert 1050 Ullage System
Cofrvnentq

This IB a ullage
(<8/000 gal) test
This IB a nonic teBt
Tanka to 15,000 gal
Bvaluator/Date


Ken Hilcos Associates
3/15/92
Horner Creative Products
212 Morton Street
Bay City, MX 48706
(517) 893-3360
Lab One Analytical; Inc.
12329 B. 60th Street
Tulsa, OK 74146
Horner Ezy 3
Search 1.00 Tracer
Negative pressure test
Tanks to 50,000 gal
with tank 70-90% full
                                                                        Tanks 0-100% full
William A. Kibbe
Associates
4/6/92
                              University of Tulsa
                              11/2/92
NDE Environmental Corp.
2000 Mariner Ave.
Suite  500
Torrance, CA 90503
 (213)  542-4342
NDE Ullage Precision
Tank Test
                                          UTS-4T
                                          U-l
                                          U-2
This is a Ullage test
Tanks to 12,000 gal
                              Ullage test to 7,500 gal
                              Ullage test to 4,500 gal

                              Ullage test to 10,260 gal
MRI
7/11/91
                              MRI 7/11/91
                              ADA Technologies
                              3/25/92
                              4/10/92
 NLPA
 P.O. Box 1643
 Boise,  Idaho 83701
 (208) 389-2074
                                          NLPA PHD 3-15
                              Applicable to  internally
                              lined tanks and uses an
                              audible alarm.
                               Ken Hilocx Associates
                               1/17/92
                                                            8 NVT

-------
'riangle Environmental,  Inc.
72 West Verdugo Avenue
turbank, CA 91502-2132
;818) 840-7020

ranknology Corporation Znt.

5225 HolliBter  Street
iouston, TX 77040
(713) 690-8265
TEI System 5000
VacuTect
This is a sonic teat
Tanks to 20,000 gal
Tanks to 75,000 gal

with tank 60-90% full

Tanks to 30,000
with tank 5-95% full
United State TestJ
2/4/93
Ken Wilcox Associate*

5/10/91
Tracer Research Corporation
3855 North Business Center Dr.
Tucson, AZ 85705
(602) 888-9400
USTBST, Inc.
2727 Kaliste Saloora Road
Lafayette, LA 70508
Tracer Tight
                                          Tracer Tight
                                          Ullage Test
                                          UST 2000U
                                                                        Tanks 0-100% full
                              This  is a Ullage Test
                              No tank sice limitation
                                .•*:-<•&{,

                              This  is a sonic test
                              Tanks to 10,000 gal
                               Ken Wilcox Associates
                               10/4/91
                               control strategies
                               Engineering
                               12/30/91

                               Ken Wilcox Associates]
                               3/24/92
                                                       9 NVT Continued

-------
Manufacturer

Alert Technologies,  Inc.
3350 West Salt Creek Lane
suite 109
Arlington Hti., IL 60005
(708) 392-0060
AUTOMATIC TANK OAUOINQ 8Y8CTHS tATO81	fBpA/53Q/UST-?Q/QP$)

          Teat  Method Name/Model'        Accuracy/comments
          Alert Model 2000  '
Pfa«4.6% e 0.10 gph
Pd*95.4% @ 0.20 gph
Tanks to 15,000 gal
Data collection for above
performance at least 1 hr.
Evaluator/Date

MJRI
3/11/91
Andover Controls Corporation
300 Brickstone Square
Andover, MA 01910
(508) 470-0555
                                          Alert Model 3000
          Andover Controls  Tank
          System
Pfa-3.6% 6 0.05 gph
Pd- 96.4% S 0.10 gph
TankB 20-95% full
Tanka to 15,000 gal

Pfa»<0.5% @ 0.10 gph
Pd»99.5% 6 0.20 gph
Tanks must be >50% full
Tanka to 15,000 gal
                                                                     Ken Wilcox Associates
                                                                     2/29/92
Ken Hilcox Associates
2/3/92
 Control Engineers, Inc.
 107 Menard Road
 Houma, LA 70361
 (504) 872-4541
          CBX 3,000 Module TLP2
          (Rapid and Normal Test Mode)
Pfa-5% @ 0.05 gph
Pd-95% @ 0.1 gph
Pfa-0.9% 6  0.05 gph
Pd-99.1% @  0.1 gph
Pfa«5% @ 0.1 gph
Pd«9.5% 8 0.2 gph
Pfa*0.1% @  0.1 gph
Pd-99.9% @  0.2 gph
Tanks at least 50% full
Tanks to 15,000 gal
                                                               •SWJV"
                                                             i'S^rv
MRI
4/23/92
5/21/92
5/27/92
                                                                    »n
                                                                    ^*"tt/93
                                                            10 ATG

-------
:gemin Naamloze Vennotachap
!120 Schoten(B)
iredabaan  1202, Belgium
J2/3/645-2790
                 E'SPI III
Pfa-1.1% 6 0.075 gph
Pd-97.9% 6 0.20 gph
Tanks to 15,000 gal
Requires at least 20"
of product to function
Data collection for above
performance at least 5.4 hrs,
HRI
12/21/90
                                          E'SPI  IV
Emco Wheaton
114 MacKenan De.
Gary, NO 27511
(919) 460-6000
                                          BBCOsytem-TLH
                                               Pfa-0.3% e 0.10 gph           HRI
                                               Pd-97.2% 6 0.20 gph           12/21/90
                                               Tanks to 15,000 gal
                                               Requires at least 20"
                                               of product to function
                                               Data collection for above
                                               performance at least 2.15 hrs.

                                               Pfa-0.9% @ 0.10 gph           HRI
                                               Pd»99.1« 6 0.20 gph           3/25/91
                                               Tanks must >50% full
                                               Tanks to 15,000 gal
                                               Data collection for above
                                               performance at least 3.25 hrs.
Engineered Systems Inc.
2001 West Campus Drive
Tempo, AZ 85282
(602) 438-1362
                                          Tank Hinder ATGS1
                                               Pfa-2.9%  6  0.10  gph
                                               Pd-97.1%  6  0.20  gph
                                               Tanks must  be >90% full
                                               Tanks to  15,000  gal
                                               Data collection  fpr above
                                               performance at least 6 hrs.
                               Ken Hilcox Associates
                               6/4/91
Environment and Safety,
721 Charcot Ave.
S-n Joss.- CA 95131
(408) 954-9081
Inc.
                                          BASI Level-Tru
 Pfa«4.6% 8 0.1 gph
 P4_Q5_4% a 0=2 «ph
 Tanks must be >50ft full
 Tanks co 15,000 gal
 Data1 collection for above
 performance at least 3.6 hrs.
 HRI
 3/26/91
                                                       11 ATO Continued

-------
Gilbarco
7300 W. Friendly Ava.
P.O. Box 22087
Greensboro, NC 27420
(919) 547-5000
TH-2/TM-3/EMC*
PA 0238000XXX Probe
Pfa-1% § 0.10 gph
Pd-99% § 0.20 gph
Tanks must be >50% full
Tanks to 15,000 gal
Data collection for above
performance at leant 5 hr>.
HRI
8/28/91
                                          TM-2/TM-3/BMC*
                                          PA 0264XXXOOOO Probe
                                          TM-2/TM-3/EMC*
                                          PA 0265XXXOOOO Probe
                              Pfa-0.2% @ 0.126              HRI
                              Pd-99% 6 0.20 gph             8/28/91
                              Tanka must be >50% full
                              Tank! to 15,000 gal
                              Data collection for above
                              performance at leant 2 hre.

                              Pfa-<0.1 @ 0.093 gph          MRI
                              Pd-99% 6 0.20 gph             8/28/91
                              Tanka must be >50% full
                              Tank* to 15,000 gal
                              Data collection for above
                              performance at least 2 hre.
Ineon Environmental
P.O. Box 638
Saco, HE 04072
(800) 872-3455
TS 2000
Pfa-0.5% 8 0.058 gph
Pd->99.9% e 0.2 gph
Tanke must be >50% full
Tanka to 15,000 gal
Data collection fpr above
performance at least 3 hrs.
Ken Hilcox Aaaociatee
5/10/91
                                          TS 1000
                              Pfa-0.8% 6 0.05 gph
                              Pd-99.99% @ 0.02 gph
                              Tank muet be > 50% full
                              Tanks to 15,000 gal
                              Ken Hilcox Associate*
                              8/5/92
LfiJ Environmental Systems
4612 H. 137th St.
Crestwood, IL 60445
(708) 396-1878
MCG 1100 and HCO 8100
Pfa-1.4% @ 0.10 gph
Pd-98.6% @ 0.20 gph
Tanks 50-95% full
Tanks to 15,000 gal
Data collection for above
performance at least 4 hrs.
Ken Hilcox Associates
10/15/91
                                                      12 ATO Continued

-------
Keekor Environmental Product*
Scottsdale Airpark
14806 North 74th St.
Scottsdale, AZ 85260
(602) 443-0001
MagneTek
1080 N. Crooks Road
Claweon, HI 48017
(313) 435-0700
FBO-800/801 Fuel Inventory
and Environmental Monitor
7021 Digital
Tank Gauge
Pfa-2.4% @ 0.1 gph
Pd-97.6% e 0.2 gph
Tanks to 15,500 gal
Data collection for above
performance at least 24 hrs.
(Not tested for measuring
water in tanks)

Pfa-4.66% @ 0.05 gph
Pd-95.34% @ 0.10 gph
Pfa«0.044% @ 0.20 gph
Pd-99.96% 6 0.20 gph
Tanks must be > 10% full
Tanks to 15,000 gal
Data collection for above
performance at least 4 hrs.
Arizona State
University
10/5/92
Ken Wilcox Associate*
2/7/91
Marley Pump Company
5600 Foxridge Drive
Mission, KS 66202
Sonic Technology (ST)
1400-1800 Series Tank
Monitoring System
Pfa«0.05% @ O.lgph
Pd«99.95% @ 0.2gph
Tanks must be  > 25%  full
Tanks to be 18,000 gal
ADA Technologies,
10/12/92
                                                                                                                        Ine*
 PetroVend,  Inc.
 6900  Santa  Fe  Dr.
 Hodgkins, IL 60525-9909
 (708)  485-4200
                                          Petrosonie III
 Pfa«0.5%  6 0.1 gph
 Pd-99.5%  6 0.2 gph
 Tanks  must be >58% full
 Tanks  to  14,600 gal
 Data collection for above
 performance at least 4 hrs.
                                                            Underwriters
                                                            Laboratories
                                                            2/27/91
 Red Jacket Electronics
 5800 Foxridge Drive
 Mission,  KS 66202
 (913) 831-5700
 RLM 9000,  RLM 5000
 and RLM 5001
                                                       13 ATO continued
 Pfa-0.5% 8 0.058 gph
 Pd->99.9% 6 0.20 gph
 Tanks must be >SO% full
 Tanks to 15,000 gal
 Data collection for above
 performance at least 3 hrs.
 Ken Wilcox Associates
 6/11/91

-------
Integrated Product Syitems,
Texas
506 Sandau Road, Suite 200
San Antonio, TX 78216
(210) 525-1333
Ronan Engineering Co.
21200 Oxnard St.
Woodland Hills, CA 91367
(818) 883-5211

Tidel Engineering, Inc.
2615 E. Beltlina Rd.
Carrolton, TX 75006
(214) 416-8222

Veeder-Root
125 Powder Forest Drive
Simsbury, CT 06070-2003
(203) 651-2700
Inc.
                                          MO Automatic Tank
                                          Gauging System
Remote Tank Management

System RTM-I
              Ronan X-76.ETM Electronic
              Tank Monitor
              EMS-2000 & EMS-3000
              TLS-250/TLS-250i
              and TLS-350 with
              8473 Probe
              (Magnetoatrict ive)
                                          TLS-250/TLS-250i
                                          and TLS-350
                                          8472 Probe
                                          (Capacitance)
                                           TLS-25G/TLS-2501
                                           and TLS-350
                                           7842 Probe
                                           (Capacitance)
Pfa-0. 00001% @ 0.1 gph
Pd»99. 99999% @ 0.20 gph
Tanks roust be 50% - 90% full
Tanks to 18,000 gal

Pfa-1* 9 0.20 gph
   **
Pd-99.9% 6 0.20 gph
Tanks to 18,000 gal
System detects tank and
line leaks.

Pfa«0.044% 8 0.10 gph
Pd-99.96% @ 0.20 gph
Tanks to 15,000 gal
Tanks >10% full

Pfa-3.00% 8 0.05 gph
Pd-96.20% 8 0.20 gph
Tanks to 15,000 gal
Tanks >50% full

Pfar<0.1% @ 0.093 gph
Pd*99% 6 0.20 gph
PfaT<0.1% @ 0.071 gph
Pd-99% @ 0.10 gph
Tanks must be >50%  full
Tanks to 15,000 gal
Data, collection for above
performance at least 2 hrs.

Pfa»0.2% 8 0.126 gph
Pd-99% @ 0.20 gph
Pfa-1.0% 8 0.069 gph
Pd-99% 9 0.10 gph
Tanks must be >50%  full
Tanks to  15,000 gal
Data collection  for above
performance  at  least  2 hrs.
                                                    @ 0.10 gph
                                             Pd-99%  @ 0.20 gph
                                             Tanks must  be >50%  full
                                             Tanks to 15,000 gal
                                             Data collection for above
                                             performance at  least 5 hrs.
                                                                         ADA Technologies*
                                                                         11/19/90
The University of

at San Antonio
3/21/91
                                                            Ken Hilcox Associates
                                                            2/7/91
                                                            Ken Hilcox Associates
                                                            2/14/91
                                                            MRI
                                                            1/18/91
                                                            MRI
                                                            4/26/91
                                                                          MRI
                                                                          1/18/91
                                                                          MRI
                                                                          4/25/91
                                                             MRI
                                                             1/18/91
                                                       14 AT6 Continued

-------
William H.  Wilson's Sons,  Inc.
P.O.  Box 309
Lansdale,  PA 19446
(215) 855-4631
Gasboy TMS 500
Pfa-0.09% f 0.10 gph
Pd-99.91% • 0.20 gph
Tank! must b« >SO% full
Tanks to 15,000 gal
Data collection for above
performance at least 2.9 hrs.
Ken Wilcox AssociatMr
5/10/91
                                                      15 ATO Continued

-------
Manufacturer
Computerising, Inc.
P.O. Box 99
Scottsboro, AL 35768
INVENTORY
                                                                  HBTHOD - 0?Pftf53Q/VgT-9Q/pQ71,
                                               Hethofl flame /Model
 Computank 3.0
fte^tiraev/Connmntt


Pd-99.5% € 0.2 gph
Pfa-2%
Tanks to 18,000 gal-
                             fivaluator/Pat9


                             Ken Wilcox Associates
                             9/17/92
Entropy Limited
South Great Road
Lincoln, MA 01773
 (617) 259-8901
                                           PTIC Rev. 90
 BnviroQueet Technologies Limited
 4501 Madison Avenue
 Kaneas City, HO 64111
 (816) 756-0774
                                           SIRAS 99.6
 8XRAS 2.0
                                           8XRA3 2.8.3
Pd-99.6% 9 0.1 gph
pfa-0.4%
Tanks to 18,000 gal

Pd-99.3% 6 0.1 gph
pfa-0.7%
Tanks (includes manifolded)
to 60,000 gal

Pd-99.99% 6 0.2 gph
Pfa-0.01%
Tanks (includes Manifolded)
to 60,000 gal.
                               HRI
                               4/23/92


                               MRI
                               8/23/93
                                                             MRI
                                                             8/23/93
 Horner Creative Products, Inc.
 212 Morton Street
 Bay City, Michigan 48706
 (800) 443-0711
  SIR PRO 1
  (J & J Technologies)
 Pd-100%  8  0.20 gph
 Pfa - 0%
 Tanks to 18,000 gal
                               Petreworks
                               4/7/93
                                                             16 SIR

-------
Simmons SIR-VEY Group
9550 Forest Lane #720
Dallas, TX 75243
(800) 848-8378
SIR Monitor, Inc.
P.O. Box 2791
Nashville, TN 37133
(615) 895-2872
SIR 2.6
                                          SIR 5.7
SIR Monitor
Pd-98% e 0.10 gph
Pfa-2%
Tanks to 18,000

Pd-99% @ 0.1 gph
Pfa-1%
Tanks to 18,000 gal

Pd-99.9% @ 0.1 gph
Pfa»l%
Tanks to 18,000
Ken Hilcox Associat*
1/27/92
                                                            SSG Associates
                                                            12/15/92
Middle Tennessee State
University
11/5/92
Southeastern Liquid Analyzers, Inc.
P.O. Box 754
300 H. Liberty Street
York, S.C. 29745
(800) 888-7352
Tank Chek 4.0
Pd-100% £ 0.1 gph
Pfa-0%
Tanks to 18,000 gal
Petroworks
6/3/93
USTMAN Industries
12265 H. Bayaud Ave.
Lakewood, CO 80228
(303) 986-8011
USTMAN SIR
YESSIR
                                          USTMAN SIR 1.91
Pd-96.3% 6 0.20 gph
Pfa-3.9%
Tanks to 15,000 gal

Pd-98.4 i 0.10 gph
Pfa-1.6%
Tanks to 18,000 gal
MRI
12/17/90
                                                            Ken Hilcox Associatsts
                                                            10/28/91
Warren Rogers Associates, Inc.
747 Aquidneck Ave.
Middletown, RI 02840
(401) 846-4747
HRA Statistical Inventory
Analysis, 5.1
Pd-99.98% 0 0.10 gph
Tanks to 18,000 gal
Ken Hilcox Associate)*
12/28/90
                                                       17 SIR Continued

-------
                               VAPOR-PHASE OUT-OP-TAH1C PRODUCT DETECTORS 

Metal Oxide
Detector
Combustible Gas
Detector
Evaluator/Data

Radian Corporation
12/28/90
Radian Corporation
1/28/91
HNU Systems, Inc.
160 Charlemont St.
Newton Highland*, MA 02161
(617) 964-6690
 Xeekor Environmental Products
 scottsdale Airpark
 1406 North 74th St.
 Scottsdale, AZ 85260
 (602) 443-0001

 In-Situ Inc.
 210 South Third Street
 P.O. Box I
 Laramie, WY 82070
 (307) 742-8213
Portable Photoionizer
with Datalogging

Model DL-101 w/10.2 BV Probe
Photoionization
Detector
Model HW-101 w/11.7 EV Probe


Model ISPI-101 w/10.2 EV Probe


Model PI-101 w/11.7 EV Probe


KeeProba VLM
 Product Permeable
 Detector
 KW-140/KW-240 w/Type 1 Sensor Product Soluble
                               Detector
                                uid  i
                                 •nn
Carnegie Mellon  Research
11/28/91

Carnegie Mellon  Research
2/5/92

Carnegie Mellon  Research
3/5/92

Carnegie Mellon  Research
2/5/92

Keekor  Envir.  Product
11/5/91
                         Carnegie Mellon Research
                         4/20/92 & 5/20/92
                                                             18 VP

-------
 Mailory Controls
 3029  E. Washington St.
 Indianapolis,  IN  46206-0706
 (800)  343-2126
 Pollulert Probe PD221V
 Control Unit FD102N
 Adslstor
 Radian Corporation
 7/8/91
Mine  Safety Appliances  Company
P.O.  Box  427
Pittsburgh, PA 15230
(416)  776-8600
PetroVend, Inc.
6900 Santa Fe Dr.
Hodgklns, IL 60525-9909
(708) 485-4200
Tldel Engineering
2615 E. Beltllne Rd.
carrolton, TX 75006
(214) 416-8222
 Tankgard


 Tankgard VIII


 Tank-Check Leak Detection  Kit  Detector Tube
Metal  Oxide
Semiconductor

Metal  Oxide
Semiconductor
 PetroVend Model  - TLD  III
 P/N 486914   S/N  00431
Tldel t  301-0328-001
Metal Oxide
Semiconductor
Adslstor
Carnegie Mellon Research
3/26/91

Carnegie Mellon Research
3/28/91

Carnegie Mellon Research
5/31/91

Carnegie Mellon Research
3/26/91
                                                       Radian Corporation
                                                       7/8/91
Universal Sensors and Devices, Inc.
9205 Alabama Ave., Unit C
chatsworth, CA 91311
(818) 998-7121
Vaeder-Root
125 Pau> »<•»»•••«• n*».
Leak Alert
Simsbury, CT 06070-2003
(203) 651-270G
Warrlck Controls, Inc.
4237 Normandy Ct.
Royal Oak, MI 40873
(313) 545-2512
TLS-350/ILS-350
                              Metal Oxide
                              Semiconductor
  , .'&/

Adslstor
             19 VP Continued
Vapor Safe "Portable"         Adslstor
Hydrocarbon Vapor Detector
                        Carnegie Mellon Research
                        9/18/91
Carnegie Mellon Research
7/24/92
                        Carnegie Mellon Research
                        9/10/91
                                                       19 VP Continued

-------
                              MOOID-PHASB OUT-OF-TAMC PRODUCT DETECTORS   fEPA/530/U8T-90/OQ9>
Manufacturer
Agar Corporation
1600 Townhurst
Houston, TX 77043
(713) 464-4451
Armstrong Monitoring Corporation
215 Colonnade Road South
Nepean, Ontario - Canada K2B 7K3
1-800-465-5777
Emco Electronics
114-300 Mackenan Dr.
Cary, HC  27511
(919) 460-6000


Horner Creative Products
Associates
212 Morton  St.
Bay City, Ml 48706
 (517) 893-3360


 IHO Industries, Inc.
Cowles Road
 Plainville, CT  06062-1198
 (203)  747-3000
 In-Situ Inc.
 210 South Third Street P.O. Bos 1
 Lsramie, m 82070
 (307) 742-8213
                                          Test Method Name/Model
Leakwise Oroundwater
Monitor
Alertmaster 5100
(OPW-Dover)
                                          Leak Sensor Jr.
 Horner  Bzy Skimmer

 Size *2
 €ems Smartwell
 Model NPM-535
 with 53A sensor
 Leak Detection Systems
 KW-140/KW-240 Monitors
 with Type 1 Sensor

 Leak Detection Systems
 KW-140/KW-240 Monitors
 with Type 2 Sensor
Detector Principle


RF attenuation
                                                                        Electrical Conductivity
                                                                        Thermal Conductivity
 Separation
 Electrical Conductivity
                                                                         Product Soluble
 Product Soluble
                                                                                                      Evaluator/Date
Ken Wilcox Associates
11/15/91   '•
                              Environment Canada
                              12/3/92
                                                            Ken Wilcox Associates
                                                            9/26/91
 W.A.  Kibbe  fi

 2/8/91
 Carnegie Mellon
 Research
 4/22/93
 Carnegie Mellon
 Research
 7/29/91

 Carnegie Mellon
 Research
 7/29/91
                                                             20 LP

-------
LTD Systems
820 North Sylvania
Fort Worth, TX 76111
(817) 834-4474
Leak Tracer Dye
external detection system
Color Development
      Scientific Xriformatl
      Services
      2/2/93
Mailory Controls
3029 B. Washington St.
Indianapolis, IN 46206
(800) 343-2126
One Plus Corporation
1955 Shermer Road, Suite 100
Northbrook, IL 60062
(708) 498-0955
Pollulert Probe FD2210/TRA
Control Unit FD103

Pollulert Probe FD241R
Control Unit CD 101N

Leak Edge Models
100-3001, 100-4001
Electrical Conductivity


Electrical Conductivity
Product Permeable
Detector
      Radian Corporation
      7/8/91

      Radian Corporation
      7/8/91

Underwriters
Laboratories, Inc.
12/18/91
PsrmAlert ESP
7720 N. Lehigh Ave.
Niles, IL 60648
(708) 966-2190
PAL-AT
Models AT20C, AT50C, AT40K

Tankwatch
Models PHMS, PHM10
Impedance Change
Electrical Conductivity

Conductance Probe
      Carnegie Mellon
      Research
      2/11/92
      Carnegie Mellon
      Research
      6/16/92
Pneumercator Company
120 Finn Court
Farmingdale, NY 11735
(516) 293-8450
Probe Models 9-901, 9-902
and 9-903
Capacitance Probe
For annual and
monthly monitoring
      Ken Wilcox Associates
      9/26/91
                                                                        (uomoination System!
                                                                        Inventory, overfill
                                                                        interstitial, piping and sump.)
Tidel Engineering
2615 E. Beltline Road
Carrolton, TX 75006
(214) 416-8222
Tidel #301-0324-001
Electrical Conductivity
      Radian Corporation
      7/8/91
                                                       21 LP Continued

-------
Veeder-Root
125 Powder Foreit Dr.
SimBbury, CT 06070-2003
(203) 651-2700
H.L. Gore and
4747 B. Beautiful Lane
P.O. Box 50899
Pheonix, AZ 85075-0699
(802) 431-0077
Ground Hater senior
TLS-350/ILS-350
                                          Gore-Leaklearn 1000
Conductive Elaetoner .
                              Capacitance
Carnegie Mellon
Research
11/20/91
                              Carnegie Mellon
                              Research   '•
                              9/10/91
                                                        22 LP Continued

-------
                         PIPELINE LEAK DETECTION SYSTEMS 99%
 Bvaluator/Data

 Ken Hilcox Associates
 6/9/92     x
Associated Environmental
Systems
3651 Pegasus Or.
Bakerafield, CA 93308
(805) 393-2212
 PLT-100R
 Line Tightness Test
 Pfa-0% e 0.1 gph
 Pd-100% «. 0.1 gph
                                                             Vista Research
                                                             11/20/90
Campo/Miller
11395 Highway 65
Porterville, CA 93257
(209) 761-6862
LS300 N/C


LS300-120
 Hourly Test
 Pfa-Ot 6 3 gph
 Pd-96.2% 6 3 gph

 Pfa-0% @ 0.2 gph
 Pd-96.4%
Jetronix Radio
Engineering
3/1/91

Jetronix Radio
Laboratories
4/7/92
                                          PL400
                                                                        Line Tightness Test
                                                                        Pfa-0% @ 0.1 gph
                                                                        Pd-96.2% @ 0.1 gph
                                                             Engineering
                                                             5/16/91
Control Engineers
« 1 A U^h«h«**.*B *t.J
XA-W noitajLU x\u*
P.O. Box 9037
Houma, LA 70360
(504) 872-4541
EMCO Wheaton
114 MacKenan Dr.
cary, NC  27511
Model LLP2
EECO system Line Leak
Detector
Hourly Test
Pfa-0% 6 3 gph
Pd-10Q%

Line Tightness Test
Pfa-0% e 0.1 gph
Pd-100%

Hourly Test
Pfa-<0.1% @ 3 gph
Pd-99.9%
                                                            MRI
                                                            8/7/91
                                                                                                      MRI
                                                                                                      8/7/91
MRI
12/10/91
                                                         23  PIPELINE

-------
                                                                       Monthly Monitor
                                                                       Pfa«<0.1% 6 0.2 gph
                                                                       Pd-99.9%

                                                                       Lin* Tightness Teat
                                                                       Pfa-<0.1% @ 0.1 gph
                                                                       Pd-99.9%
                                                            HRI
                                                            12/20/91
                                                            HRI
                                                            12/29/91
Oilbarco
7300 H. Friendly Ave.
P.O. Box 22087
Greensboro, NC 27420
(919) 547-5000
Oilbarco Precision
Line Teat
Line Tightness Teat
Pfa-0% e 0.1 gph
Pd-100% 6 0.1 gph
Lamar University
3/25/91
Hasstech, Inc.
5360-B Baetgate Mall
San Diego, CA 92121
(619) 457-5880
AcuRite Pipeline Teeter
Single and Multiple Line
                                          LineTite Pipeline Monitor
Line Tightness Test
    }  Pfa-0% 6 0.1 gph
Pd-lpO% 6 0.1 gph

Linof. Tightness Test
Pfa-0% @ 0.062 gph
Pd-100%
Pfa-0% 8 3 gph
Pd-100%
Lamar University
3/25/91
                                                            Ken Wilcox Associates
                                                            10/15/91
Heath Consultants Inc.
100 Tosca Drive
P.O Box CS-200
Stoughton, MA 02072
(617) 344-1400
Petro Tite Line Tester
Line Tightness Test
Pfa-6.37% 9 0.10 gph
Pd-99.99%
Ken Hilccr. Associates
3/11/91
Horner Creative Products
212 Morton Street
Bay City, MI 48706
(800) 443-0711
Horner Ezy Chek II/Line
                                          Horner Ezy Chek/ Line
Line Tightness Test
Pfa-0+%  @  0.10 gph
Pd-100-%

Line Tightness Test
Pfa-0+%  i  0.10 gph
pd-100%
W.A. Kibbe & Assoc.
12/17/90
                                                            W.A. Kibbe & Assoc.
                                                            12/18/90
                                                    24 PIPELINE Continued

-------
Intergrated Product Systerna, Inc.
506 Sandau Road, Suite 200
San Antonio, TX 78216
(210) 525-1333
Hallory Controls
2831 Waterfront Parkway
Indianapolis, IN 46214
(800) 343-2126
Remote TAnk Management
System RTM-1
Pollulert FD 200 PSRA
Continous Line Tightness Test University of Texas?
Pfa-1% 8 0.1 gph              3/21/91
Pd-99.5% a. 0.1 gph
Threshold leak detection
9 0.05 gph
Hourly Test
Pfa-99%
Ken Hilcox'Associates
6/24/91
NDE Environmental Corp.
2000 Mariner Ave.
Suite 500
Torrance, CA 90503
(213) 542-4342
PTK-88
Line Tightness Test
Pfa-1.35 0 0.10 gph
Pd-99.8%
                                                            MRI
                                                            2/14/91
Perm Alert ESP
Research Research
7720 N. Lehigh Avenue
Niles, IL 60648
(708) 966-2190
Model PAL-AT

Model AT20C, AT50C, AT40K
Pd-100%

Pfa-0% @ 0.16 gph
Liquid Leak detection,
TFH direct buried
Carnegie Mellon

2/11/92
ProEco, Inc.
7439 B. Hillsborogh Ave.
Tampa, PL 33610
(813) 623-5003
ProLine Test Series III
Line Tightness Test
Pfa-0.1% 6 0.1 gph
Pd-99%
                                                            MRI
                                                            8/30/91
Bed Jacket Electronics
5800 Foxridge Drive
nLamLon, K5 66202
(913) 831-5700
Red Jacket Diaphragm
Leak Detector
                                          Red Jacket XLP
                                          PPM 4000 and RLM 9000
Hourly Teat
Pfa-0% % 3.0 gph
Pd-100%
                              Hourly Test
                              Pfa-0% 9 3.0 gph
                              Pd-100%

                              Hourly Test
                              Pfa-0% e 3.0 gph
                              Pd-100%
Ken Hilcox Associates
12/21/90
                                                                                                      Ken Hilcox Associates
                                                                                                      12/21/90
                                                                                                     Ken Hilcox Associates
                                                                                                     9/16/91
                                                   25 PIPELINE Continued

-------
                                                                        Monthly Monitoring Test
                                                                        Pfa-0% § 0.2 gph
                                                                        Pd-100%
                                                            Ken Hilcox Associatea
                                                            9/16/91
                                                                        Line Tightness Taat
                                                                        Pfa-0% e 0.1 gph
                                                                        Pd-100%
                                                            Ken Hilcox Aaaociataa
                                                            9/16/91
Ronan Engineering
21200 Oxnard Blvd.
Woodland Hills, CA 91367
(818) 883-5211
Schuatar Instrumenta, Inc.
Associates
211 Grover St.
Kawkawlin, MI 48631
(517) 684-6638


Tanknology Corp. Int.
5225 Hollister St.
Houston, TX 77040
(713) 690-8265
 Tidal Engineering
 2831 Waterfront  Parkway
 Indianapolia,  IH 46214
 (800) 343-2126


 Tokheim Corporation
 10501 Coreoration Dr.
 Port Wayne,  IN 46801
 (219) 423-2552
X76 DM-4 with JT-H2
Line Pressure Sensor
                                          Tal-A-Leak Version 1
                                          Tanknology Line Tester
                                          Manual TLD-1
Pipeline Leak Detector
 Tokheim Pressure Monitor
 Model  S8SA-PM
Hourly Test
Pfa-0% 6 3.0 gph
Pd-100%

Line Tightness Test
Pfa-3.7% 8 0.1 gph
Pd-100%

Lint Tightness Teat

Pfai-0+% e 0.1 gph
Pd-100-%
Line Tightness Test
Pfa-3% e 0.1 gph
Pd-99%
    <
 ' /*v!

H^yfely Teat
Pfa-99%
        Test
 Pfa»0% §3=0 gph
 Pd-100%
                                                                                                      MRI
                                                                                                      10/4/91
                                                                                                      MRI
                                                                                                      10/4/91
                                                            W.A. Kibbe G

                                                            3/13/91
                                                            Ken Wilcox Associates
                                                            7/22/91
                               Ken Wilcox Asaoeiatea
                               6/24/91
                                                                                                      Vista Research
                                                                                                      11/2/90
                                                     26  PIPELINE Continued

-------
Tracer Research Corp.
3855 N. Buainese Center Dr.
Tucson, A2 85705
Tracer Tight Line Teat System Tracer detection  System
                              Pfa*>2.9%
                              Pd-97.1%
                              Ken Wilcox  Associate^
                              9/30/91
Triangle Environmental, Inc.
172 West Verdugo Avenue
Burbank, CA 91502-2132
Vaporless Manufacturing
9234 East Valley Road
Suite C
Prescott Valley, Az 86314
(602) 775-5191
Vaeder-Root
125 Powder Forest Dr.
P.O. Box 2003
Simsbury, CT 06070-2003
(203) 651-2700
TEI Model LT-3
Vaporless LD 2000
TLS Line Leak Detector
Series 8475
30 Minute Test
Pfa*0% 9 0.1 gph
Pd*100%
Hourly Test
Pfa«0%
Pd-100%
 : > :* !•
 '.  A i
 >:>•'. *..',

Hourly Test
P£a«0% e 3 gph
Pd-100%

Monthly Monitoring Test
Pfa-0% e 0.2 gph
Pd-100%
                                                                        Llnla Tightness Test
                                                                        P*aM>%  e  0.1  gph
                                                                        Pd-100%
United States Testing
Company, Inc.
3/3/92
Ken Hilcox Associateis
11/19/90
MRI
9/20/91
                                                             MRI
                                                             9/20/91
                                                             MRI
                                                             9/20/91
William M Wilson's Sons,
P.O Box 309
Lansdale, PA 19446
(215) 855-4631
Model PM 101
Hdurly Test
PT»>0% 0 3 gph
Pd-100%
Vista Research
11/2/90
                                                                         -rli!. J t

                                                                          ..ti t

                                                                          '.it
                                                    27 PIPELINE Continued

-------
Manufacturer
                                        OCTBR HBiaOM tNO ESEMLISHBD BPA PROCBPUEgSV

                                                      *

                                          Test H»thod Name/Model        Comment!
Arizona Instrument Corp.
411 E. Hood Street
Phoenix, AZ 85040-1941
(800) 229-2930
Liquid 330
Model 17-330-A/17-330-B
                                          TLM-830
                             Liquid-phase detector
                             Operating principle! Refraction
                             Evaluated by Ken Wilcox Assoc. 7/2/91

                             Liquid-Phase interstitial product detector.
                             Operating principle! Refraction
Mallory Controls
3029 E. Washington St.
Indianapolis, IN  46206
(800) 343-2126

conductivity.
Omega Environmental, Inc.
P.O. Box 3005
Bothell, HA 98041-3005
overfill
 (206) 486-4800
 Preferred-Rimeor Instruments
 11 South St.
 P.O. Box 1280
 Danbury, CT 06801
 (203) 743-6741
Pollulert Probe FD200HLM
Control Unit CD 101N

Pollulert Probe M0210RA
Control Unit FD103
Model TC 110 System for
Petroleum Products
                             Liquid-phase in-tank overfill product detector.
                             Operating principle! pressure differential

                             Liquid-phase interstitial product detector.
                             Operating principle! thermal/electrical
                              Leak Prevention System for double walled tanks and
                              piping systems.  Provides pneumatic  leak prevention,
                              pump shutdown interlocks, inventory  control,

                              protection and remote monitoring.
                                                                          u M "
TG-EL-D3-ARF/HD-A1
                               System is  a  "three-in-one" product!
                               tank gauging, tank overfill alarm
                               and tank/sump/piping  interstitial  leak
                               monitor.   Solely for  double walled
                               tanks  and  double walled piping.
                                                           28 OTHER

-------
Steel Tank Institute
5*70 Oakwood Road
Lake Zurich, IL 60047
(708) 438-Tank

Tidel Engineering, Inc.
2615 E. Beltline Rd.
Charrolton, TX 75006
(214) 416-8222

conductivity.

Veeder-Root
125 Powder Forest Dr.
Simsbury, CT 06070-2003
(203) 651-2700
Permatank Installation
Test for Interstitial
Monitoring
Tidel #301-0330-001
Tidel #301-0329-001
Double-wall steel
interstitial:
TLS-2501, ILS-250, TLS-350,
and ILS-350
Quantitative and continuously monitors
loss of vacuum for tanks
Liquid-phase in-tank overfill product detector.
Operating principles pressure differential

Liquid-phase interstitial product detector.
Operating principles thermal/electrical
Liquid-phase detector
Operating principles Float Evaluations
Carnegie Mellon Research Inst.
7/17/92
                                          Double-wall fiberglass        Liquid-phase detector
                                          interstitials TLS-250i,        Operating principles Float Evaluations
                                          ILS-250, TLS-350, and ILS-350 Carnegie Mellon Research Inst.
                                                                        7/17/92
                                          Hydrostatic-Single & Dual
                                          Floats for Interstital
                                          Monitorings
                                          TLS-250, ILS-250 and TLS-3SO
                              Liquid-phase detector
                              Operating principles Float Evaluations
                              Carnegie Mellon Research Inst.
                              12/8/92
                                           ump
                                          TLS-250if ILS-250, TLS-350
                                          and ILS-350
                                                                        T I JMM.i «l_
                              Operating principles Float Evaluations
                              Carnegie Mellon Research  Znst.
                              7/17/92
                                                                        Liquid-phase hydrocarbon
                                                                        Liquid detectors.
                                                                        Operating principles Ultrasonic* and
                                                                        conductive elastomer
                                                                        Evaluations Carnegie Mellon Research Inst.
                                                      29 OTHER Continued 1/15/93
Discriminating Dispenser
Pan/Sump Sensors
TLS-350

-------
                                          Continuous Statistical
                                          Leak Detect
                                          TLS Series 300/400 with
                                          8472 or 8473 profess
                            Pf•"<.!% ff 0.16gph
                            Pd-99% • 0.20gph
                            Tanks 5-99% full
                            Tanks to 45,000 gal.
                           Statistical analysis
                           combined with ATO
                           Midwest Research Inst.
                           9/4/92
World Enviro Systems, Inc.
P.O. Drawer 789
Shawnee, OK 74802
(405) 275-3900
Vacuum Monitor Method
for Single Wall Tanks
This system uses a flexible membrane
liner, "bladder"/vacuum monitor system
                                                          30 OTHER

-------