„                                               510-B-94-008
      '\       UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
       °                  WASHINGTON, D.C. 20460
                                                  I

                           JAN  I 7 1995
   ;                                                        OFFICE OF
                                                      SOLID WASTE AND EMERGENCY
                                                           RESPONSE
MEMORANDUM

TO:       All  Interested Parties

FROM:     Lisf'c.  Lund,  Acting
          Office of Underground Storage' Tanks

RE:       Leak Detection Equipment/Procedures Evaluations:
          Draft List

Please find attached a draft list of underground storage tank
(UST) system leak  detection third-party evaluations.  The
attached draft list is being provided for your reiview prior to
publication of the first edition.  In general, the draft includes
leak detection system evaluations performed by an independent
third party in accordance with EPA standard test procedures (or
equivalent procedures),  with leak rates blind to the tester.
This list was  compiled based on reviews by a work group
consisting of  state and EPA regulators.  This document is
provided for review for accuracy and completeness and is not
intended to be used for any other purpose.  This draft list in no
way implies that listed or unlisted leak detection equipment  or
procedures do  or do not meet the criteria for which evaluations
are reviewed.

The list is divided into three parts, a Summary section, a
Specification  section,  and an Under Review section.  The Summary
section categorizes leak detection systems by the. standard test
procedures, or "protocol," used in the evaluations.  The
Specification  section lists each system evaluation in
alphabetical order by the name of the system vendor, and contains
the system name, model number,  and specifications, and also
contains the name  of the evaluator and date of the evaluation.
The Under Review section lists systems about which the work group
has received some  information,  and is either in the process of
reviewing the  third-party evaluation, or has requested additional
information which  is needed to clarify the evaluation.  Listing
of systems as  "under review" in no way implies that the systems
do or do not meet  the criteria by which the evaluations are
reviewed.  The "under review" category will help vendors
reviewing this draft list determine if the work group has
received a copy of their third-party evaluation.
Please note that multiple evaluations may exist for one system,
and therefore  there may be multiple listings for that system.


                                                     Recycled/Recyclable
                                                     Printed with Soy/Canola Ink on paper that
                                                     contains at least 50% recycled fiber

-------
                                                                     ~
For those who are not familiar with the work group, please refer
to the StlcLd August 4,  1994 memorandum . from Curt Johnson,  the
work group's chair,  providing background information.
Neither EPA nor the work group approve or will aPPro™ i®**f
detection equipment or procedures.  Approval or acceptance of
leak defection equipment and procedures is the ^ponsibility of
tSeimDlementing agency, which in most cases is the state
eSvironmS?ara|ency.  Please contact the implementing agency UST
program manager to determine what systems are approved or
acceptable for use in your area.

We Dlan to distribute the first  edition of this list in the
lumme? of 1995?  While the ctirrent  draft list only includes a
SSSd number of evaluations that  followed non-EPA Protocols,
every effort will be made to review the majority of such
evaluations for inclusion in the first edition list.  The "««•
edition aSo will be made available in electronic format on EPA's
"CLU-IN" electronic bulletin board  at no charge, and may be

                        -pie** Sisssspit ^ssas.ar
month dSSSvSlSTaS new evaluations and  information are reviewed.
EPA Region 10 has' been publishing    .
detection systems for several years, but has indicated that
will no longer update its list.

We believe that the first edition  list can be of great benefit to
the entirl UST community.  While it will be beneficial, please
                            t limitations   It will be based on
 remer  hat i has  inherent limitations
 evaluations  which are  one-time events, often conducted in a lab
 SStiSg   ?t SeSf ore  cannot determine that a particular system
 will work or comply with regulations at a particular site -- or
 It in^ site.  Fo?  ?his  and other reasons  any edition of this^
 lisFis not intended  to be — and cannot be -- the final word,
 decision-makers must  make up their own minds based on all
 available sources  of  information.
 Your comments are important in making the first edi^jon l^jL*?
 useful as possible.   Please do not hesitate to provide feedback.
 All comments ~r»*Hng this draft list should be made to the
 appropriate team leader for that type of evaluation, /or MM
 SSinStions onlv. please send three copies to Harold Scott of EPA
 Region 10?  When the first edition is published this summer, it
 will list a new contact, who will take over Mr. Scott's
 responsibilities as recipient and distributor of new evaluations.
 The team leaders' and Mr. Scott's addresses are fo md in the
 first attachment.  In order to be considered for the first
 edition list, all comments and new evaluations should be
 submitted by March l. 1995.

-------
Attachments:
* August 4, 1994, Johnson memo, with attachments
* Disclaimer
* Draft list

cc:  State UST Program Managers
     UST/LUST Regional Program Managers
     David Lloyd, OGC
     Recipients of EPA Region 10 Leak Detection Methods  Document
     Vendors appearing on Draft list

cc (cover only):
     Frank Ciaviattieri, Region I
     Stanley Siegel, Region II
     Robert Greaves, Region III
     Mary Kay Lynch, Region IV
     Norman Niedergang, Region V
     Guanita Reiter, Region VI
     Lynn Harrington, Region VII
     Robert Duprey, Region VIII
     Laura Yoshii, Region IX
     Ken Feigner, Region X
     OUST Management Team

\LD_Eval.U51

-------

-------
                                                                     ,
                                 [Attachment 1 to Jan. 17, 1995 memo]
                               HHBBaBBHMBBB^MnimHBBH^BBHMIMB^
                                           ALABAMA
                  DEPARTMENT OF ENVIRONMENTAL MANAGEMENT
James W. Warr, Director
                                                                   Jim Folsom
                                                                    Governor
Mailing Address:

PO BOX 301463
MONTGOMERY AL

36130-1463


Physical Address:

1751 Cong.W.L.

Dickinson Drive
(Montgomery, AL

36109-2608


(205)271-7700
FAX 270-5612
Field Offices:


110 Vulcan Road
Birmingham, AL
35209-4702
(205)942-6168
FAX 941-1603


400 Well Street
P.O. Box 953
Decatur, AL

35602-0953
(205)353-1713
FAX 340-9359


2204 Perimeter Road
Mobile, AL
36615-1131
(205)450-3400
FAX 479-2593
August  4,  1994

MEMORANDUM

TO:     Vendors of Leak Detection Equipment/Procedures
        for Underground Storage Tanks

FROM:   Curt D. Johnson
        Chairperson

RE:     Notice of Formation of Work Group for  Review of
        Underground Storage Tank Leak Detection  Equipment/Procedures
        Evaluations

By now,  most of you have heard of our work group,  which was put
together for the purpose of reviewing leak detection
equipment/procedures evaluations.  However, we  have come to realize
that you need to know more about the work group so you can better
understand why we are requesting information  concerning the
evaluations you have performed on your leak detection
equipment/procedures and what we intend to do with the information you
send us.

Let me  begin by providing some history behind the  formation of the
work group.   Soon after leak detection equipment/procedures were
required to be evaluated to prove its capability to meet EPA leak
detection  performance requirements, some states began to take a hard
look at  how the evaluations were performed instead of accepting the
results  at face value.   The states reviewing  these evaluations found
most to  be well  done, but a few that were not properly tested in
accordance with EPA Standard Test Procedures.   Many other states
expressed  interest in these findings, but did not  have the resources
and/or expertise to review the evaluations themselves.   At this point
an effort  was  made to consolidate state and EPA expertise and
resources  in a work group for the purpose of  reviewing leak detection
equipment/procedures evaluations.

The resulting  work group consists of 7 states,  2 EPA regions, and
EPA's Office of Underground Storage Tanks (see  attached member list).
It is divided  up into teams (see attached team  list)  which perform a
detailed review of leak detection evaluation  results,  test data,
calculations,  test protocols, operating procedures,  etc.  in order to
accomplish the following mission as established by the members of the
work group.

    The  mission  of the  work group is to review release detection
    equipment/procedures evaluations to determine  if each evaluation
    was  performed in accordance with an acceptable  protocol,  to ensure
    that the equipment/procedures meet EPA performance standards.

    EPA  and  member states will  share the results of  such  reviews with
    interested parties.
                                                                                   Printed on Recycled Paper

-------
                                   -2-

 As discussed In the "Forward" to all  EPA Standard Test Procedures,
 both state agencies and tank owners  prefer that evaluations  be carried
 out by an Independent third-party.   In  response to this,  work group
 members agreed that it was appropriate  to review only Independent
 third-party evaluations performed in  accordance with an acceptable
 protocol  where leak rates  are blind  to  the vendor.

 If an EPA standard test procedure is  not available  for use to evaluate
 a certain type of equipment/procedure,  the work group has agreed  to
 review the test protocol.   To avoid problems  with evaluations
 performed using new protocols,  the work group 1s offering to review
 them prior to the vendor proceeding with the  third-party  evaluation.

 Prior to member states and EPA  preparing a list or  incorporating  work
 group Information into their existing equipment/procedures lists, a
 draft of the work group information pertaining to your leak  detection
 equipment/procedures will  be distributed by work group team  leaders to
 allow for any necessary revisions to  be made.  In some cases,  the
 Information will  Include an "under review" category for
 equipment/procedures where the  review could not be  completed  prior to
 the deadline.

 It 1s expected that information gathered by the work group will be
 available for member states and EPA to  establish or revise
 equipment/procedures lists prior to the end of FY 1994.   Member states
 and EPA lists  are expected to be finalized and made available  to other
 states  and any other interested parties shortly thereafter.   It is
 anticipated that  member states  and EPA  equipment/procedures  lists may
 be used by others as follows:
     1.    by owners  and operators in the selection of appropriate
          release  detection equipment/procedures  for their specific
          underground storage  tank needs,
     2.    by vendors  of release  detection equipment/procedures  for
          comparison  with other  vendor equipment/procedures as  well as
          documents  to be presented to other state,  county and  local
          regulatory  agencies  to gain acceptance  in  the  respective
          jurisdiction,
     3.    by other state  and  local governments  to the  desired extent as
          a  basis  for  determining whether or not  the  equipment  meets
          their  requirements,  as  a reference for  comparison (for states
          who have their own review process  or  have  more stringent
          requirements), or  as a  reference  during field  inspections to
          ensure that  the leak detection  equipment/procedures are being
          used properly  1n  the field.

THE WORK GROUP DOES NOT HAVE THE AUTHORITY  TO DETERMINE IF THE
EQUIPMENT/PROCEDURES MEET STATE, OR LOCAL LEAK DETECTION
REQUIREMENTS.   Please  contact the appropriate  local  authority  to
determine 1f your leak detection  equipment/procedures meets their
requirements.

-------
                                   -3-

Work group teams are currently being forwarded third-party evaluations
and protocols through Region 10 EPA.  If you have any existing or new
evaluations that you want to send in to be reviewed,, please send three
copies of them to Harold Scott, USEPA Region 10.  Mr. Scott's address
1s on the attached 11st of work group members.  The information that
is necessary to allow the work group to review an evaluation is
included in the attached document list.  The work group intends to
meet approximately every 6 months to finalize the review of any new or
existing evaluations and protocols received by Mr. Scott.

We believe the member states and EPA equipment/procedures lists will
be beneficial to vendors as well as states, local government, and
underground storage tanks owners and operators.  However, we need your
help and cooperation to make our effort a success.  We strongly
encourage you to work with us 1n this effort by contacting any of the
work group members to discuss any questions or problems that may
arise.  A list of member phone numbers and addresses is attached.

CDJ/rlb                                             ;

Enclosures - Member List
             Team List
             Leak Detection Equipment Review - Document List

-------
                                       LIST OF MEMBERS
  Member
Address
Phone/Fax
  Curt D. Johnson
Alabama Department of Environmental Management
P.O. Box 301463
Montgomery, AL 36130-1463
(334) 271-7986

FAX (334) 270-5612
  MikeKadri
Michigan Department of Natural Resources
UST Division
P.O. Box 30157
Lansing, MI 48909-7657
(517) 335-7204

FAX (517) 335-2245
  Beth DeHaas
Maine Department of Environmental Protection
Statehouse Station No. 17
Augusta, ME 04333
(207) 287-2651

FAX (207) 287-7826
  Russ Brauksieck
New York State Department of Environmental Conservation
50 Wolf Road, Room 340
Albany, NY 12233-3750
(518) 457-4351

FAX (518) 457-4332
  David Wiley
U.S. EPA
401 M Street Southwest
5402W
Washington, DC 20460
(703) 308-8877

FAX (703) 308-8505
  Lamar Bradley
Tennessee Department of Environment & Conservation
UST Division, 4th Floor L & C Tower
401 Church Street
Nashville, TN 37243-1541
(615) 532-0952
     532-0945

FAX (615) 532-0938
  Randy Nelson
U.S. EPA Region 7
RCRA/STPG Branch
726 Minnesota Avenue
Kansas City, KS 66101
(913) 551-7220

FAX (913) 551-7947
  Thomas Springer
Oklahoma Corporation Commission
Fuel Division
P.O. Box 52000-2000
Oklahoma City, OK 73152-2000
(405) 521-3107

FAX (405) 521-6576
  Ellen Van Duzee
U.S. EPA Idaho Operations
422 West Washington Street
Boise, ID 83702
(208) 334-9507

FAX (208) 334-1231
  Harold Scott
U.S. EPA Region 10
1200 Sixth Avenue
Mailcode: WD133
Seattle, WA 98101
                                                                               FAX (206) 553-0165
  Shahla Farahnak
California State Water Resource Control Board
Division of Clean Water Program
P.O. Box 944212
Sacramento, CA 94244-2120
(916) 227-4350

FAX (916) 227-4349
 meaben
Updated as of January 17, 1995.

-------
                            Team   List
Team
Volumetric
, Non- Volumetric
ATG
SIR
! Vapor/Liquid
Pipeline
Other
Leader
DeHaas
Farahnak
Van Duzee
Bradley
Wiley
Kadri
Nelson
Members
Brauksieck
Springer
Brauksieck*
Brauksieck
DeHaas
Kadri
Van Duzee
Farahnak
Springer
Kadri
Wiley
Farahnak
* phasing out of this group
Updated as of January 17, 1995.

-------
                      Leak Detection Equipment Review - Document List

This enclosure lists the  documentation required for review of third-party evaluation of underground
storaae tank and line leak detection equipment or test-methods.
          1.      A complete third-party evaluation report, including:

                 a.      Details of the evaluation procedure if the EPA standard procedure was not used
                        for the evaluation.  If the EPA evaluation procedure was used, list any deviations
                        or modifications to the procedure.

                 b.      Complete set of all the EPA required  attachment sheets.

                 c.      Individual test logs and/or field notes.

                 d.      Statistical calculations and any applicable graphs or charts generated during the
                        evaluation.

                 e.      A statement from the evaluator confirming that all equipment at the test site was
                        properly maintained and calibrated to the level of accuracy necessary fora valid
                         evaluation.
          2.      An outline of the manufacturer's operating procedures for the equipment/method.  The
                 summary procedure must be dated and include a revision number, if applicable.  A copy
                 of the summary procedure must be provided to the third-party evaluator for enclosure in
                 the report. Also required is a statement'from the manufacturer confirming the use of the
                 submitted procedure  during  the evaluation.

-------
_ —   3.      Complete installation/operations manual for the equipment/method.




_   4.      A sample of the test report (including field work-sheets) which will be submitted to the
  :             owner/local  implementing  agency.                                 *uuw/«ea ra me




_j__   5.      Outline of the test procedures in high ground water areas. These procedures should be
        6.      Outline  of the test procedures for manifolded tanks.   These procedures should be
                                                    evaluator and a statement
        7.      An*™™* from the manufacturer confirming that there are no mutual financial interests
               between the equipment manufacturer and the third-party evaluator.
        a                               //fcawe formal trainin9 and
__   9.      Equipment  calibration  procedures  and  manufacturer recommended  schedule of
               calibration.




__   10.     The name,  address, and phone number of the technical ' personnel  serving as the
__   1 1.     Correspondence  letters from state agencies who have reviewed the equipment/method.

-------
 12.
 Following documentation for alt permanently-installed leak detection equipment:

                                       "* manufactu™ <° install the leak detection
        b.
        c.
        d.
       e.
        A list of service personnel authorized by the manufacturer to conduct the annual
        functional test (required for all leak detection equipment).


        An outline of the maintenance procedure (including a list of the parts or functions
        of the  system  to be checked,  calibrated,  or programmed)  for the annual
        functional test by authorized service personnel.

        An outline (1 - 2 pages) "Equipment Check Guidelines for Inspectors" prepared
        by the manufacturer.  Tft/s summary should  guide local agency inspectors on
        proper  field procedures  to follow  when inspecting  equipment for proper
        operation, for attempting to access the stored history (for alarms or failed tests)
        to determine compliance with state requirements.

        A sample of the  reports generated and/or printed by the equipment (for all
        equipment models), and an  explanation  of the items in the report  if not self-
        explanatory.                                                   '

        Information on how the control  panel modules connected to the various probes
        are labeled.  The information on the panel should be directly comparable to the
        equipment name,  model/part/probe  number which will be included in  the
13.
Following  documentation for the methods using tracer analysis:

a.      Name and certification of the laboratory analyzing vapor samples.

       Quality Assurance Manual of the laboratory.

       Method and amount of tracer injection.

       Vapor sample collection  method and chain of custody records.
       b.

       c.

       d.

       e.
       Third party certification for capability of the test method to detect leaks from the
       ullage portion of the tank.

-------
                  [Attachment 2 to Jan. 17, 1995 memo]


                            DISCLAIMER

     This draft list is being circulated for discussion purposes
only, and its general release is not yet authorized.  The purpose
of the circulation is to allow representatives from state
governments, leak detection system vendors, third-party
evaluators, and EPA to review the document and provide comments
thereon.  THIS DOCUMENT MAY NOT BE USED OR RELIED UPON BY ANY
PERSON OR ENTITY FOR ANY OTHER PURPOSE AS THE CONTENTS HEREIN ARE
SUBJECT TO REVISION.

This draft list is limited to evaluations of leak detection
equipment and procedures that the Work Group has completed review
of, and that were conducted by an independent third-party
evaluator with leak rates blind to the vendor.  This draft list
includes evaluations conducted in accordance with EPA Standard
Test Procedures for Evaluating Leak Detection Methods
(EPA/530/UST-90/OOX) and as many evaluations conducted in
accordance with other acceptable protocols as possible.  The
draft list includes an Under Review category of
equipment/procedures evaluations, for which the Work Group review
could not be finalized prior to publication.

THE LISTING OP EQUIPMENT/PROCEDURES EVALUATIONS AS "UNDER REVIEW"
IN NO WAY IMPLIES THAT THE EQUIPMENT/PROCEDURES DO OR DO NOT MEET
THE CRITERIA FOR WHICH EVALUATIONS ARE REVIEWED,,

-------

-------
                                Jtt
     LIST OF LEAK DETECTION EVALUATIONS

FOR UNDERGROUND STORAGE TANK (UST) SYSTEMS
                                            s
m
3
n-

GJ
                  January 17, 1995
                                           Ul

                                           3

-------

-------
             SUMMARY SECTION
         IN ORDER OF TYPE OF. EVALUATION:

    VOLUMETRIC TANK TIGHTNESS TEST METHODS
  NON-VOLUMETRIC TANK TIGHTNESS TEST METHODS
        AUTOMATIC TANK GAUGING SYSTEMS
   LIQUID PHASE OUT-OF-TANK PRODUCT DETECTORS
       LIQUID PHASE INTERSTITIAL DETECTORS
   VAPOR PHASE OUT-OF-TANK PRODUCT DETECTORS
      DOUBLE WALLED TANK TIGHTNESS TESTS
LINE LEAK DETECTORS / LINE TIGHTNESS TEST METHODS
STATISTICAL INVENTORY RECONCILIATION (SIR) METHODS

  AND ALPHABETICAL BY MODEL WITHIN EACH TYPE
                   January 17, 1995

-------

-------
                                                                               s^
           VOLUMETRIC TANK TIGHTNESS TEST METHODS
3E«»t Method

ABB Systesi II
(Overfilled
Te»t)
AEs Systesi II
(Overfilled
Tait-Large Tanks)
Alnrt Model 1000
Automated Precision
Tank Testing  Systea
(APXT Systaa)
R-2 Overfilled Xest

Computerised
VPLT Underfilled lank
Tightness Testing
Sygtea

Homer Bsy-Chek I
(manual)
Horner Bsy-Chek  II
(computerised)
Horner Bsy-Chek  II
Ib» Precision
T.it Systea
Leak Computer Tank
TMt Systesi
Evaluation Kesults

Threshold: 0.05 gph
Overfilled Test
Tanks to 15,000 gai-
100% full tank

Threshold: 0.05 gph
Overfilled Test
Tanks to 75,000 gal
100% full tank

Threshold: 0.05 gph
Underfilled Test
Tanks to 30,000 gal
20-95% full tank

Threshold: O.OS gph
Overfilled Test
Tanks to 15,000 gal
100% full tank

Threshold: 0.05 gph
Underfilled Test
Tanks to 18,000 gal
At least 24" of product

Threshold: 0.05 gph
Overfilled Test
Tanks to 12,000 gal
100% full tank

Threshold: 0.05 gph
Overfilled Test
Tanks to 12,000 gal
100% full tank

Threshold: O.OS gph
Underfilled Test
Tanks to 12,000 gal
98-100% full tank

Threshold: 0.05 gph
Overfilled Test
Tanks to 18,000 gal
92% to 100% full tank

Threshold: 0.05 gph
Overfilled Test
Tanks to 12,000 gal
100% full tank
                                                                                                           VOLUMETRIC TANK TIGHTNESS TEST METHODS
                                                    Associated Environmental Systems
                                                    Associated Environmental Systems
                                                    Alert Technologies
                                                    Tank Automation
                                                    NDE Environmental
                                                    Horner Creative Products
                                                    Horner Creative  Products
                                                    Horner Creative Products
                                                    Ibex Industries
                                                    Hasstech
                                                                                                 Test Method

                                                                                                 Petro Coap




                                                                                                 Petro Xite II
                                                                                                 Ooiltest Ainlay Tank
                                                                                                 •Xegrity Tester, 8-3
                                                                                                 Sure Test -
                                                                                                 Assured Tight SysteB,
                                                                                                 Series  IV
                                                                                                 Tank Auditor,
                                                                                                 Version KID V.2.16
                                                                                                 Xel-A-Leak  1
                                                                                                X.B.I. Systaa 40OO
                                                                                                Version 1.00
                                                                                                 USX 2000/f
                                                                                                USX JOOO/LL
evaluation Results

Threshold: 0.05 gph
Overfilled Test
Tanks to 15,000 gal
100% full tank

Threshold: 0.05 gph
Overfilled Test
Tanks to 15,000 gal
100% full tank

Threshold: 0.05 gph
Overfilled Test
Tanks to 15,000 gal
100% full tank

Threshold: 0.05 gph
Underfilled Test
Tanks to 18,000 gal
11-95% full tank

Threshold: 0.05 gph
Overfilled Test
Tanks to 15,000 gal
100% full tank

Threshold: 0.05 gph
Overfilled Test
Tanks to 15,000 gal
100% full tank

Threshold: 0.05 gph
underfilled Test
Tanks to 15,000 gal
50-100% full tank

Threshold: O.OS gph
Underfilled Test
Tanks to 45,000 gal
At least 78.6% full tank

Threshold:  0.05 gph
Underfilled Test
Tanks to 15,000 gallons
At least 15% full,  & between
20 to 60 in. of product
Manufacturer

Heath Consultants
                                                                                                                                                     Heath consultants
                                                                                                                                                     soilteat
                                                                                                                                                     NDE Environmental
                                                                                                                                                     Leak Detection Systems
                                                                                                                                                     Schuster Instruments
                                                                                                                                                     Triangle Environmental
                                                                                                                                                     USTest
                                                                                                                                                     USTest
last Systea
                       ThfSSiiolui G.G5 gph  r
                       Underfilled Test
                       Tanks to 15,000 gal
                       At least 90% full tank

-------
NON-VOLUMETRIC TANK TIGHTNESS TEST METHODS
Tot K»tbPd

Alert Ullage Syste
Hodel 1050
Ullage Test


Alert Ullage Syste
Model 10SO Z
Ullage lest
(Underfilled Xest)
XBI System 500O
Ver. 1.0
XEI Ullage
Xeit Ver. 1.0
Tracer light
USX Ullage Teet -
Veraion ProBco U2
USI 2000/U
Ullage Teat
UT8-4T
Ullage Xeat
U3 Ullage Teat
 (Vacuum or Pressure)
 VacuTect Oil Tank
 Sy.tea
Evaluation Results            K»a»jfset
-------
AUTOMATIC TANK GAUGING SYSTEMS
Teat Method

BBCO Systeai TLH
Monthly Test
BECO Systeat TLM
Quick Precision
BJSCO Syateai TIM
Quick Test
Encompass Nil XPAM
(lUgnetostrictive
Probe)
Encompass WSF IPAM
(Ultrasonic Probe)
Oaaboy IMS 500
Image IX
Red Jacket KM lyatam,
Var. ELM 5000,
5001, 9000
Sonic Technology
140O-180O Serial
Tank Monitoring System
ATO Monitor/LLM Series
/FM> Monitor
SN 3, 3, 2.1,  3.1
Environmental
Management Console
PA02380OOZSZZ  Froba
      Evaluation Kesults

      0.2 gph teat
      Threshold!  0.10 gph
      -50-95* full tank
      Tanka to 15,000 gal

      0.1 gph test
      Threshold:  0.05 gph
      50-95* full tank
      Tanks to 15,000 gal

      0.1 gph test
      Thresholds  0.05 gph
      50-95% full tank
      Tanks to 15,000 gal

      0.2 gph Tostt
      Threshold! 0.1 gph
      At least 50t full tank
      Tanks to 15,000 gal

      0.2 gph Test!
      Threshold: 0.1 gph
      At least 50% full tank
      Tanks to 15,000 gal

      0.2 gph Testt
      Thresholdt 0.10 gph
      Tanks to 15,000 gal
      50-95% full tank

      0.2 gph Test!
      Threshold: 0.1 gph
      Tanks to 15,000 gal
      90% full tank

      0.2 gph Test:
      Thrashold: 0.1 gph
      Tanks to 15,000
      50-95% full tank

      0.1 gph Tost:
      Threshold: 0.05 gph
      Tanks to 18,000 gal
      95% full tank

      0.2 gph Test:
      Thrashold: 0.1 gph
      Tanks to 18,000 gal
      50-95% full tank

      0.2 gph Taot:
      Threshold: 0.10 gph
      Tanks to 15,000 gal
      50-95% full tank
Manufacturer

Emco Wheaton
                                                     Emco Wheaton
                                                     Emco Hheaton
                                                     Arizona Instrument
                                                    Arizona Instrument
                                                    Gaaboy International
Engineered Systems
                                                                                                        AUTOMATIC TANK GAUGING SYSTEMS
Harley Pump
Harlay Pump
                                                                                       last Method
Gilbarcp Environmental Producta
                                  TM 2.1, TM 3.1
                                  Environmental
                                  MBnageoant Consols
                                  Digital Sensing Probe
                                  PA0264XZZOOOO
                                  Capacitance Probe
                                  IN 2.1, TM 3.1
                                  Environmental Manage-
                                  ment Console Digital
                                  Sensing Probe
                                  PA0265ZZZOOOO
                                  Series Probe
                                  (lUgnetostrictive)
                                                                                       TICS-1000
Tidel EMS
Ver. BM8 2000, 3000,
3500; Probe /401-0009,
1401-0010

Tidel EMS 2000/3000/
3500; Probe #401-0021,
#401-0022
                                                                                       IS  1000
                                                                                       Magnetostrictive Probe
                                  IS 2000
                                  Magnetostrictive Probe
Veeder-Root
TLS-250/300/350
UST ATOS with 7842
Digital Sensing
Capacitance Probe
Evaluation Results

0.2 gph Test:
Threshold: 0.126 gph
50-95% full tank

0.1 gph Test:
Threshold: 0.071 gph
At least 95% full tank
Tanks to 15,000 gal

0.2 gph Test:
Threshold: 0.093 gph
50-95% full tank
Tanks to 15,000

0.1 gph Test!
Threshold: 0.069 gph
At least 95% full tank
Tanks to 15,000 gal

0.2 gph Test:
Threshold: 0.1 gph
z 90% full tank
Tanks to 15,000 gal

0.2 gph Test:
Threshold: 0.05 gph
Tanka to 15,000 gal
At least 15" product

0.2 gph Test:
Threshold: 0.1 gph
At least 15" product
0.2 gph Test:
Threshold: 0.05 gph
Tanks to 15,000 gal
50-95% full tank

0.2 gph Test:
Threshold: 0.058 gph
Tanks to 15,000 gal
50-95% full tank

0.2 gph Test:
Thrashold: 0.1 gph
Tanks to 15.000 aal
50-95% full"tank"
                                                     Manufacturer

                                                     Gllbarco Environmental Products
                                                                                                                                            Gilbarco Environmental Producta
                                                                                                                                            Universal Sensors & Devices
                                                                                                                                            Tidal Engineering
                                                                                                                                            Tidel Engineering
                                                                                                                                            Incon Environmental
                                                                                       Incon Environmental
                                                                                                                                            Veeder-Root

-------
                 AUTOMATIC TANK GAUGING SYSTEMS
Teat Kethod
Veeder-*oot
3L3-250/250i/300/330
UST AXOI with 1472
Digital «ea«ims
Capacitance Probe
Veeder-Boot
TLS-200/200i/2SO/250i/
300/350/400 UST AM*
with 8473 Digital
Beaaing Probe
(Kagaetoatrictiva)
Veeder-Koot 3000
Tank Laval Modula-
TLP2; Kormal/Rapid
Teat Moda (Formerly
CBI 3000 TLP2)
JC-76 RM t, Z-7C
ETH-4X
7021 Digital Tank
Oauga
traluitloa »«»alt«

0.2 gph T«iti
Thraiholdi 0.126 gph
50-95% full tank
Tanka to 15,000 gal

0.1 gph Teati
Threshold: 0.071 gph
50-95% full tank
Tanka to 15,000 gal

0.2 gph Teati
Thraaholdt 0.093 gph
50-95% full tank
Tanka to 15,000 gal

0.1 gph Taat:
Thraaholdt 0.069 gph
95% full tank
Tanka to 15,000 gal

0.2 gph Taatt
Thraaholdi 0.10 gph
50-95% full tank
Tanka to 15,000 gal

0.1 gph Taati
Thraaholdi 0.05 gph
& 95% full tank
Tanka to 15,000 gal

0.2 gph Taat:
Thraaholdi 0.1 gph
10-95% full tank
Tanks to 15,000 gal

0.1 gph Taati
Thraaholdt O.OS gph
10-95% full tank
Tanka to 15,000 gal

0.2 gph Taati
Thraaholdt 0.1 gph
10-95% full tank
Tanka to 15,000 gal

0.1 gph Test:
Threshold: 0.05 gph
10-95% full tank
'Tanks to 15,000 gal
Manufacturer

Ve*der-Jtoot
                                                                       LIQUID PHASE OUT-OF-TANK PRODUCT DETECTORS
                                                    Vender-Root
                                                    Veeder-Root
API/Ronan
                                                    Patriot Sanaora  & Controla
                                                                                      T«lt
rci Xavirooaeatal
Analog Hydrocarbon
Proba AXr-100

FCI rnrironaental
Digital Hydrocarbon
Proba DMP-100

Oeaw Saartwell HPX-535
with Oroundwatar
Proba HP-S3S

oilbarco
Environmental
Management Conaola
with Oroundwater
aenaor, PA02700ZZOOO1

Leak Detection Bystaas
KH-140 / KM-240
Konitora with
Type 1 Senaor

Leak Detection Cyatau
KH-140 /'KH-240
Monitors with
Type 2 Senaor

Leak Edge
Models 100-3001,
100-4001

Laak Tracer Dye
LTD Systems, Inc.

LEAKHISE Oroundwatar
Monitor, ID-220
 Series Hydrocarbon
on water Detector

PeraAlert  PAL-AX
Models AX20C,  AX50C,
AX40KI AOM Senaor
 Cabin

 PerariUart  PAL-AX
 Models AX20C,  AT50C,
 AX40KI PHFH
 Hydrocarbon Probe
 and Type  1 Censor

 PeraAlart  PAL-AX
 Models AX20C,  AXSOC,
 AT40K!  PHFH
 Hydrocarbon Probe
 and Type  2 Censor
                                                         ribar optic chaatical aancor
Kanafafetarer

FCI Environmental
                                                         Fiber optic chenlcal aanior   FCI Enviroiutantal
                                                                                                             Conductiva Folyoar
                                                         Elactrical conductivity
                                                                                                             Product Solubility
                                                         Product Solubility
                                                                                                             Product Permeability
                                                                                                             Product Solubility-
                                                                                                             Color Development

                                                                                                             RF Attenuation
                                                          Capacitanca Change
                                                                                                              Product Solubility
                                                                                                              Product Solubility
IHO Induatriaa



Gilbarco Environmental Producta





In-situ




In-Situ




One Plua



Advanced Tank Technology


Agar




 PermAlert




 PermAlert





 ParmAlert

-------
          LIQUID PHASE OUT-OF-TANK PRODUCT DETECTORS
 Test Method

 PermAlert PAL-XT
 Models XX20C,  ATSOC,
 AT40Ki IFB Hydrocarbon
 Sensor Cable

 Pollulert Probe*
 MD221O/X,
 MD2210/XRA

 Pollulert Probes
 MD241R,MD241RRA,
 MD241O,MD2410RA

 Petro Vend
 SiteSentineli
 30-3206,  -3207, -3210
 Sensors

 TracaTek  Alarm and
 Locator Modules
 TT502 Fuel Sensing
 Cable

 Xidel EMS-3500
 with Monitoring Hell
 Probes Part 301-0641

 Xidel EMS-3500
 with Sheen Probes
 Probes Part 301-0687

 Tidel EMS-3500
 Detector  301-0762
 Xidel  Detectors
 301-0324-001,
 301-0325-001

 Xidel  Detectors
 301-0326-001,
 301-0326-002

 Veeder-Root
 ILS-350, TLS-350,
 XLS-350RI Oroundwater
 Sensor (794380-621,
.-622,  -624)
Detector Principle

Capacitance Change




Electrical Conductivity



Electrical Conductivity



Product Permeability




Electrical Conductivity
Conductivity via Resistor
Ladder Network
Electrical Conductivity/
Hydrocarbon Sensitive
Polymer

Electrical Conductivity/
Hydrocarbon Sensitive
Polymer

Electrical Conductivity
Electrical  Conductivity
Electrical  Conductivity
Manufacturer

PermAlert




Kallory Controls



Hallory Controls



Petro Vend




Raychem




Tidel Engineering



Tidel Engineering



Tidel Engineering



Tidel Engineering



Tidel Engineering



Veeder-Root
                                                                              LIQUID PHASE INTERSTITIAL DETECTORS
                                                               lest Method
Ariiona Instrument
Soil Sentry
Liquid 330,
17-330-A/17-330-B,
Probes 17-141A,
17-142A, 17-143A,
17-144A

Arisona Instrument
XLM-830
Probes 17-141A,
17-142A, 17-143A
17-144A

Oilbarco
PA02590XZXOOO

Oilbarco
PA02591144000

Oilbarco
PA02592000000

LDB 700, LDB 740,
LDB 9000t Sensor
Probe Models 9-901,
9-902, and 9-903

PermAlert PAL-AI
Models AX20C, AX50C,
AX40KI PBL
Hydrocarbon Sensor

PenAlert XankHatch
PEM10, PHMSi
Combination
Hydrocarbon/Water
Probe

PermAlert XankWatch
PBM10, PBMSi
Hydrocarbon Probe

Petro Vend
Petrosentry IV,
Petrosentry VIII,
SiteSentineli
Liqplid Sensor

Petro Vend
Petrosentry IV,
Petrosentry VIII,
SiteSentinelt
Universal Reservoir
Sensor
                        Detector Princiol«
                        Refraction
                                                     Manufacturer

                                                     Arizona Instrument
Refraction





Float Switch


Float Switch


Float Switch


Capacitance




Electrical Conductivity




Electrical Conductivity





Electrical Conductivity



Thermal Conductivity





Float Switch
Arizona Instrument





Gilbarco Environmental Products


Gilbarco Environmental Products


Gilbarco Environmental Products


Pneumercator Company




PermAlert




PermAlert





PermAlert



Petro Vend





Petro Vend
                                                                                                                              10

-------
               LIQUID PHASE INTERSTITIAL DETECTORS
                                                                                           LIQUID PHASE INTERSTITIAL DETECTORS
Tait H»tbod
Petro V«ad
Patroseatry IV,
Patroseatrr VIZI,
SitaBantinali
Universal limp
Sensor

Tidel BU-3500
Containment Samp
Probes Part 301-0642

Sidel Bt>-3500
Liquid Discriminatory
Probes 301-OS35

Tidal KM8-3500
Detector 301-0752-001

Universal
Leak Mart Svstea
Kodali LAL-100, IA-01,
IJl-02, 1A-04,  LA-I4,
LA-08, CATLASI
Liquid Sanior  LALS-1
TL3-350
Diccriminating
Int«r»titi«l Liquid
Svnsor

Va«d«r-Roofc
TLS-350
Di«p«n>ar Pan S«n»or»,
CoataiuMnt Sump
Saucora

Ve«dor-Root
TL3-350
Dual and Singla Stag*
Bydroatatic Sanaora

Vaadar-Rooi;
TL3-250i, XLS 2SOi
Plua, ILS 250,
ILS 350, TLS-350
Interatitial Liquid
Senior for Fibarglaaa
Tanka (0794390-401)

Va ada r-Root
XLS-250, XLS 250i
Plus, ILS 250,
ILS 350, TLS-350
Intaratitial Liquid
Sanaor for Staal
Tanks (0794390-420)
                       Patactor Prlnelola
                       Float Switch
Hagnatic Switch /
Float and Hydrocarbon
Sensitive Polyraar

Electrical Conductivity /
Hydrocarbon Sanaitiva
Polycar

Float Switch
Thormal Conductivity
                       Capacitanca Change/
                       Ultrasonic
Electrical Conductivity/
Ultrasonic
Float Switch
Float Switch
Float Switch
                                                   Hinafacturar
                                                    Petro V«nd
Tidal Bnglnsarlng



Tidal Knginaaring



Tidel Engineering


Universal Sensors and Devices
                                                    Vaedar-Root
                             Veader-Root
                             Veeder-Root
                             Veeder-Root
                                                                                                    Ittt K>thod
                                                                                                                           Pataetor
Vaadar-Koot
TU-2501,  XL* 2501
Plua, X£* 250,
ILS 350, TLC-350
Liquid San«or for
IUMJ)« (0794390-20$)

Vaadar-Xoot
SL*-350| Eolid-Btata
Pan/Kuap Banior
(794380-321, -351),
Piping Snap Censor
(794380-208), Micro
Bansor (794380-340)
                                                                                                                           Float Switch
Product Perneability/
Ultrasonic/
Float Switch
                                                                                                                                                       Veeder-Root
                                                                                                                                Veeder-Root
                             Veeder-Root
                                        11
                                                                                                                                            12

-------
         VAPOR PHASE OUT-OF-TANK PRODUCT DETECTORS
                                                                                            DOUBLE WALLED TANK TIGHTNESS TEST
test Method

Arisona Inatnuaent
Soil Sentry
Twelve-!

FCI Environmental
Analog Hydrocarbon
Probe AHP-100

FCI Kaviroountal
Digital Hydrocarbon
Probe DBP-100

Fuel Pindar
Version IV

Oilbarco
PA02CCOOOOOOO

MSA
Xankgard

MSA
Tankgard VIII

Petro Vand
Petrosentry TLD III

Patro Vand
SitaSantinal
(hurt Module and
Vapor Sensor

Pollulert Probaa
M0221V, MD221VRA,
MD210V,MD210VRA

Tidal EMS-3000
301-0328-001,
301-0330-001

Tidal EMS-3500
301-0*34

Univaraal
Laak Alart Syitam
Modala 1AL-100, LA-01,
LA-02, LA-04, LA-I4,
LA-08, CATLASl
LflVS-1 MOS Vapor Senior

Vaadar-Rool:
IL8 350, TLS-350
Adciator Vapor Probe*

Harrick
Modal S700 Matar
PVP-2 Senior
                       Datactor Principle
Metal Oxida
Semiconductor
                            Manufacturer

                            Arizona Instrument
                                                                                                    Teat Method
Fiber optic chemical aanaor  FCI Bnvironroantal
Fiber optic chemical sensor   FCI Environmental
                                                 o/c
                                                 Hydroatatic
                                                 Precision lank
                                                 Teat for DHT-Type
                                                 II Tank*

                                                 Xerxei Trucheck
                                                 •ydrostatic
                                                 Monitoring
                                                 Sya
Byaluatiop Kesults

Threshold! O.OS gph
without dispensing  -
0.07 gph w/dispenaing
Tanks to 13,000 gallons
0-100* Full Tank

Threshold: 0.05 gph
Tanks to 30,000 gph
0-100% full
                                                                                                    Manufacturer

                                                                                                    O/C Tanks
                                                                                                                                 Xerxes
Adsorption Sampling


Adsistor
Hatal Oxida
Semiconductor
Metal Oxide
Semiconductor
Metal Oxide
Semiconductor
Metal Oxide
Semiconductor
Adaistor
Adaistor
Adsistor
Metal Oxide
Semiconductor
Adsistor
Adsistor
Environmental Fuel Systems


Gilbarco Environmental Product*


Mine Safety Appliances


Mine Safety Appliances


Petro Vend


Petro Vend




Mallory Controls



Tidel Engineering



Tidel Engineering


Universal  Sensors and Devices






Veeder-Root



Warrick Controls
                                       13
                                                                                                                                            14

-------
    LINE LEAK DETECTORS / LINE TIGHTNESS TEST METHODS
                                                                        LINE LEAK DETECTORS / LINE TIGHTNESS TEST METHODS
T.lt U»thod

AeuKite


KBCO Bjstea LLD
Knvironaeatal
Hanageawnt Coacole
with Lin* Leak
Detector
PX02MOOOOS01
Horner EIY-Chek
Manual Line
Leak Detector

Homer EIY-Chek II
Autoutic Line
Leak Detector

LineXite Pipeline
Leak Monitor
LLP1
LLP2
LS300, LS300 M/C,
LS300-120,
L8300-120 ZLC,
LS300-120 PLOT,
LS300-120 FIKJS A/8

Petro. Tit*
Line Xeeter

PLT-100R
Proline Teat
seriea III, Ver.
                 1.0
Lin* Tightneaa Teat
Xhreaholdt  0.01 gph

Autostktlc Electronic
Line I*«k Detector
Thraiholdi
2.0 gph (3  gph teit)
0.1293 gph  (0.2 gph teet)
0.0793 gph  (0.1 gph te«t)

Electronic
Line Leak Detector
Thresholdi
1.5 gph (3  gph teet)
0.079 gph (0.1 gph teet)
0.1 gph (0.2 gph te«t)

Line Tightneie Teat
Threaholdt  0.05
Line Tightness  Teit
Threshold:  0.05
Automatic Electronic
Line Leak Detector
Thresholdi
2.00 gph (3.0 gph tamt)
0.062 gph (0.1 gph teet)

Automatic Electronic
Line Leak Detector
Threshold: 1.88 gph
(3 gph teat)

Automatic Electronic
Line Leak Detector
Threshold:
1.88 gph (3 gph teet)
0.05 gph (0.1 gph teat)

Automatic Electronic
Line Leak Detector;
Threeholdx
2.36 gph (3 gph teet)
Line Tightneee Teat
Threahold:  0.01 gph

Line Tightneaa Teet
Threahold:  0.05 gph

Line Tightneaa Teat
Threaholdi  0.05 gph
Kjinufacturer

Hteatech


Eoco Hheaton
Cilbarco Environmental Products






Horner Creative  Product*



Hornar Creative  Products



Haoatech





Control Engineera




Control Engineere





Campo/Hlller





Heath Conaultants


Associated Environmental Systems


NDE Environmental
                                                                    Tot K»thod
rxx-st
                                                                                           Ked Jacket
                                                                                           PPM 4000,  KM 9000,
                                                                                           X£M 10000, »T 1401,
                                                                                           ST 14011,,  «T 1101,
                                                                                           ax 18011,

                                                                                           Red Jacket
                                                                                           OLD and XLD
                                                                                           Xed Jacket
                                                                                           PZ1/FX2
                                                                    Red Jacket
                                                                    PX1/FZ2  Flexline
Red Jacket
PZ1/FZ2-D (Bigflow)
                                                                                           Red Jacket XLP
                                                                                           Ronaa Z-76 Automatic
                                                                                           Line Leak Detector
                                                                                           BTP-MLD Pipeline
                                                                                           Leak Detector
8TP-MLD-D Pipeline
Leak Detector (Dieael)
 STP-MLD-E Line
 (Flexline)
 Leak Detector

 X.B.I.
 Model LT-3, Ver. 1.0
Line Tightneaa Teat
Thresholds  0.05 gph

Automatic Electronic
Line Leak Detector
Threahold:
3 gph teat  (3 gph teat)
0.047 gph teat  (0.1 gph teat)

Mechanical  Line
Leak Detector
Threaholdi  2.0 gph
(3 gph teat)

Hechanical  Line
Leak Detector
Thresholdi  2.0 gph
(3 gph teat)

Mechanical  Line
Leak Detector
Threaholdi  2.0 gph
(3 gph teat)

Hechanical  Line
Leak Detector
Threahold:  2.0 gph
•(3 gph teat)

Hechanical  Line
Leak Detector
(rigid and  flex  line)
Threahold:  2.0 gph
(3 gph teat)

Automatic Electronic
Line Leak Detector
Thresholdi
0.831 gph (3 gph teat)
0.066 gph (0.1 gph teat)

Mechanical  Line
Leak Detector
Threahold:  2.0  gph

Mechanical  Hourly Line
Leak Detector
Threshold:  2.0  gph

Mechanical  Hourly Line
Leak Detector
Threahold:  2.0  gph

Line Tightness  Test
Threshold:  0.05  gph
(0.1 gph teat)
HOB Environmental


Harley Pimp





Harley Pump




Harley Pump




Marley Pump




Harley Pump




Harley Pump





API/Ronan





FE Petro



FE Petro



FE Petro



Triangle Environmental
                                        15
                                                                                                                                   16

-------
    LINE LEAK DETECTORS / LINE TIGHTNESS TEST METHODS
last Method

TLD-1
Zokheim Pressure
Monitor, Model•
PM 101 and 585A-PM

Tracer Tight Line
Teat
Vaporless LD  2000
Vaporless LD  2000E
Vaporla•» LD  20001
Vaporless LD  3000 t
LD 30008
Veieder-Root
TLS Lisa Laak
Detection Series 8475
Veeder-Root
TLS Lin* Leak
Detection Series 8484
Evaluation Reiults

Lin* Tightness Test
Threshold: O.OS gph
(0.1 gph test)

Mechanical Line
Laak Detector
Thraahold: 2.25 gph

Lina Tightness Test
Thraahold: Dataction
of tracar chamical

Machanical Lina
Laak Datactor
Thraahold i 1.7 gph
(3 gph taat)

Hachanical Lina
Laak Datactor
Thraahold: 2.0 gph
(3 gph test)

Mechanical Line
Leak Detector
Thraahold! 2.5 gph
(3 gph teat)

Mechanical Lina
Leak Detector
Threahold: 2.0 gph
(3 gph teat)

Automatic Electronic
Line Leak Detector
Threshold!
1.5 gph (3 gph teat)
0.1 gph (0.2 gph teat)
0.079 gph (0.1 gph teat)

Automatic Electronic
Line Leak Detector
Thresholdi
1.88 gph (3 gph test)
O.OS gph (0.1 gph teat)
Manufacturer

Tanknology



Tokheim



Tracer Reoearch



Vaporleaa Manufacturing




Vaporleea Manufacturing




Vaporless Manufacturing




Vaporleaa Manufacturing




Veeder-Root






Veeder-Root
                                       17
                                                                       STATISTICAL INVENTORY RECONCHJATION (SIR) METHODS

                                                                    Teat Method
Bnviro Tita SIR
(a k a SIRAS 99.6)
Mitchell'« SIR
Program V.2.6
12-13-91

Precision Tank
Inventor; Control
Syatem, Rev.  90
(Quantitative)
Precision Tank
Inventory Control
System, Version 90
(Qualitative)

SIR 5.7
                                                                                           SIR MONITOR
SIR PRO 1
Version 1.0
                                                                                           SIR PRO 1
                                                                                           Version 2.0
                                                                                           SIRAS Software
                                                                                           System Version  2.0
                                       SIRAS Software
                                       System
                                       Version 2.8.3

                                       SIRTBCH
                                                                                           Store Vision
                                                                                           Version E.2
                                                                                           USTMAM SIR 1.91
•valuation Results

Threshold: 0.05 gph
quantitative method
Tanks to 18,000 gal

Threshold: 0.05 gph
quantitative method
Tanks to 18,000 gal

Threshold: 0.05 gph
quantitative  Method
Single Tank to 21,000 gal
Manifolded ayatema to 60,000
gal

Threshold: 0.04 gph
qualitative method
Tanks to 30,000 gal
Threshold:  0.05 gph
quantitative method
Tanks to 18,000 gal

Threshold:  0.05 gph
quantltive  method
Tanks to 18,000 gal

Threahold:  0.1 gph
qualitative method
Tanks to 18,000 gal

Threshold:  O.OS gph
qualitative method
Tanks to 18,000 gal

Threshold:  0.05 gph
Quantitative Method
Tanks to 30,000 gal

Threshold:  0.10 gph
Quantitative Method
Tanks to 30,000 gallons

Threahold:  O.OSgph
quantitative method
Tanks to 18,000 gal

Threahold:  0.0834 gph
Qualitative Method
Tanks to 12,000 gallons

Threshold:  0.1 gph
quantitative method
Tanks to 18,000 gal
                                                    Vendor

                                                    EnviroQuest Technologies
                                                                                                                                               S.I.R. International
Entropy
                                                                                                                                               Entropy
                                                                                                                                               Simmons Sirvey Group
                                                                                                                                               Sir Phoenix
                                                                                                                                               Horner Creative Products
                                                                                                                                               Horner Creative  Products
                                                    EnviroQueot Technologies
                                                                                                                                               EnviroQuest Technologies
                                                                                                                                               Environmental Management
                                                                                                                                               Technologies
                                                                                                                        Syacorp
                                                                                                                                               USTMAN industries
                                                                                                                                   18

-------
t  m
I  'Sc,
      s
   x-9 •   >ff»   xs> •

   "?*   "£§•   *£-f
   ft ft O   ft pi o   rt rt O
   0ȣ  OrtJi   O*H>
     IT o.    i-o   ,  it a
    >B o
    »£"•
          i"'o

          §!M
,'?
>• o
      I
       o
       a

-------
i>   >y
    SPECIFICATION SECTION
     ALPHABETICAL BY COMPANY,
    THEN BY TYPE OF EVALUATION,
          THEN BY MODEL,
   THEN BY LEAK RATE: 3, 0.2, 0.1 GPH
             January 17, 1995

-------

-------
                              Advanced Tank Technology, Inc.

                                   Leak Tracer Dye (LTD)
                                     LTD Systems, Inc.
                     LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
    Output type:          qualitative
    Sampling frequency:   continuous
    Operating principle:    Product solubility - color development
Tejt Results:
    Accuracy(%)
    Detection time(min:sec)
    Fall Time (min:sec)
    Lower detection limit(cm)

Specificity Results:
Commercial
Gasoline
100 (above 8 ppm)
<00:01
Not App.
<0.32
Synthetic
Gasoline
100 (above 23 ppm)
<00:01
Not App.
<0.32
    Activated:    commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, JP-4 jet fuel,
                 synthetic gasoline, xylene(s).

Manufacturer's Specifications:

    LTD develops color in alcohols, ketones, solvents, and PCBs as well as petroleum products.

Comments:

    EPA and many states require detection of 1/8 inch of product, which is 0.32 cm. The
    detector is not reusable, and must be replaced after contact with hydrocarbons.
Advancad Tank Technology, Inc.
820 N. Sylvania
Fort Worth, TX 78111
T«l: (817) 831-3248
             Evaluator: Glann B. White, Scientific Information Services


             Data of evaluation: 02-02-93
                                                                                                                                                                                         DRAFT
                                                                                                                        Agar Corporation
                                                                                                                 LEAKWISE Groundwatar Monitor
                                                                                                       ID-220 Series Hydrocarbon on Water Detector System

                                                                                                       LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                                                    Detector:
                                                                                      Output type:          qualitative
                                                                                      Sampling frequency:   continuous
                                                                                      Operating principle:    radio frequency (RF) attenuation

                                                                                  Teat Results:

-------
                                  Alirt Tt/chnofojlii, Inc.

                            AJtrt Mod*) 1000 tUrtdtriBttd Ttttl
                                                                            DRAFT
                      VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with P0-98.2% & P,A-1.8% for 2 hr test
                     and P0-99.8% & P,A-0.2% for 4 hr test.

L«ak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Appllcabiity:          Gasoline, diesel, aviation fuel, fuel oil *4, fuel oil #6, solvent, waste oil and
                     other compatible products.

Capacity:             The maximum tank capacity is 30,000 gallons.
                     This equipment is capable of testing a tank at product levels from 20 to
                     95% full.

Waiting time:         Minimum waiting time between delivery and the beginning of the test data
                     collection must be at least 1 hour.
                     There must be no product delivery during the test waiting time.

Test Period:          The minimum data collection time must be 4 hours to achieve PD of 99.8%
                     and P,A of 0.2% and 2 hours to achieve PD of 98.2% and PFA of 1.8%.
                     The test data must be acquired and recorded by a computer.
                     Leak rate is calculated from  the data determined to be valid by statistical
                     analysis.
                     There must be no dispensing or product delivery during the test.

Ground Water:        Depth to the water table present in the backfill must be determined, and if
                     it is above the bottom of the tank, product level must be adjusted to
                     provide minimum of 2 psi net pressure on the  bottom of the tank.

Calibration:           The load cell must be calibrated before each test.

Comments:           This system was not evaluated using manifolded tanks.
                     This system tests only the portion of the tank containing product.
                     As the product level is lowered the leak rate in a leaking tank decreases
                     (due to lower head pressure).
 Atort T«chnologiM, Inc.
 3350 W. Silt CiMk LWM, Suit* 109
 Artington, IL 60OOS
 Ttl: (800) 322-7845
Ev«iu«tor: Km Wilcox Associate


D«1« ol Ev.ki.tion: 04-26-91
                                                                                                    AIirtTichnotoflJts, (nc.

                                                                                      Attrt Uttigi Systtm - Mod*l 1050 (1.5 p«l aod -1.0 pin
                                                                                                                                           DRAFT
                                                                                   NON-VOLUMETRIC ULLAGE TANK TIGHTNESS TEST METHOD

                                                                  Certification:     Leak raw of 0.1 gallon per hour with P0 -100% & P,A- 0%.

                                                                  Usk Threshold:   Ultrasonic signal when the tank it under pressure or vacuum is compared to
                                                                                   background signal (prior to pressurization). A leak is declared if the ratio
                                                                                   exceeds 1.5 for either 12 kHz or 25 kHz frequency band.

                                                                  Applicability:     Gasoline, diesel, aviation fuel, heavy fuel oils (#2 through #6), solvents, and
                                                                                   waste oil.

                                                                  Capacity:        The maximum ullage volume is 6,000 gallons.

                                                                  Waiting time:     There is no waiting time after product delivery if the test is conducted after an
                                                                                   underfilled tank tightness test.

                                                                  Test Period:     The minimum data collection time is 5 minutes.
                                                                                   The test data is be acquired and recorded by a computer.

                                                                   Test Pressure:   A net pressure of 1.5 psi (or -1.0 psi) in the ullage portion of the tank is
                                                                                   maintained.  Tank system must be able to maintain pressure or vacuum with a
                                                                                   loss of less than 0.4 psig.

                                                                   Ground Water:   Depth to water table must be determined. If water table is present outside the
                                                                                   ullage portion of the tank vacuum-ullage test must not be used; Pressure-ullage
                                                                                   tast must bs dons under a net outward pressure  of 1.5 psi.

                                                                   Calibration:       Equipment is calibrated before each test.

                                                                   Comments:     This test method only tests the ullage portion of the tank, the product-filled
                                                                                    portion of the tank must be tested with an underfilled test method.
                                                                                    Vibration due to nearby equipment and dripping condensation can interfere with
                                                                                    this test method.
                                                                                    When testing with vacuum, this test method may not be effective in some
                                                                                    backfill because some backfill (such as clay) may plug a hole in the tank.
                                                                                    Manifolded tanks are isolated prior to the test.
                                                                                    During the third-party evaluation unleaded gasoline was used.
                                                                                    During the third-party evaluation microphone was located 25 feet away from the
                                                                                    leak simulator.
Alert TKhnologni, Inc.
3350 W. Salt Cr««te L*n*. Suit* 109
Arlington Height., !L. 60005
T«t: (800) 322-7845
                                                                                                                                                        Evikiitor: K«n Wiloox A.toci.t.t
DM* of Evaluation: 03-15-92

-------
                                  Alert Technologies. Inc.

                        Alert Ullage System - Model 1050 X (-1.6 ptl)
                                 DRAFT
                NON-VOLUMETRIC ULLAGE TANK TIGHTNESS TEST METHOD

Certification:      Leak rate of 0.1 gallon per hour with PD=100% & PfA=0%.

L»ak Threshold:   Ultrasonic signal when the tank is under vacuum is compared to background
                 signal (prior to vacuum).  A leak is declared if the ratio exceeds 1.5 for either 12
                 kHz or 25 kHz frequency band.

Applicability:      Gasoline, diesel, aviation fuel, heavy fuel oils (#2 through #6), solvents, and
                 waste oil.

Capacity:         The maximum ullage volume is 24,000 gallons.

Waiting time:     There is no waiting time after product delivery if the test is conducted after an
                 underfilled tank tightness test.

T«$t Period:       The data collection time is 5 minutes.
                 The test data is acquired and recorded by a computer.

Ttst Pressure:    A net pressure of 1.5 psi (or -1.0 psi) in the ullage  portion of the tank is
                 maintained.  Tank system must be able to maintain pressure or vacuum with a
                 loss of less than 0.4 psig.
                 Zero pressure (background) must produce a flat line response.

Ground Water:    Depth to water table must be determined. If water table is present outside the
                 ullage portion of the tank vacuum-ullage test must not be used; Pressure-ullage
                 test must be done under a net outward pressure of 1.5 psi.

Calibration:       Equipment is calibrated before each test.

Comments:       - This test method only tests the ullage portion of the tank, the product-filled
                 portion of  the tank must be tested with an underfilled test method.
                 - Vibration due to nearby equipment and dripping condensation can interfere
                 with this test method.
                 - When testing with vacuum, this test method may not be effective  in some
                 backfill because some backfill (such as clay) may plug a hole in the tank.
                 - Manifolded tanks are isolated prior to the test.
                 - During the third-party evaluation *4 fuel oil was used.
                 - During the third-party evaluation microphone was located 25 feet away from
                 the leak simulator.
Alert Tochnotagioi, Inc.
3350 W. Salt Creak lane, SulM 109
Arlington Heighta, IL. 60005
Tel: (BOO) 322-7845
Evatuator: Ken WHcox Aaaooiatea


Date of Evaluation: 02-28-94
                                   Alert Technologies, Inc.

                  Alert Model 2000 bi-Tank Mass Measurement Probe System
DRAFT
                                                                                                  AUTOMATIC TANK GAUGING SYSTEM*

                                                                        Certification:      Leak rate of 0.2 gallon per hour with PD=95.4% & PFA=4.6% (calculated based
                                                                                         on a one-hour test).

                                                                        Leak Threshold:   0.10 gallon per hour (a leak is declared if the output of the measurement system
                                                                                         exceeds this threshold).

                                                                        Applicability:      Gasoline, diesel, aviation fuel, fuel oil, waste oil, and solvents.

                                                                        Capacity:         The maximum tank capacity must be 15,000 gallons.
                                                                                         The tank must be between 50 and 95% full.

                                                                        Waiting Time:     Minimum waiting time between product delivery to the tank and test data collection
                                                                                         must be 15 hours.

                                                                        Test Period:       The minimum  data collection time must be 2 hours.
                                                                                         Test data must be acquired and recorded by computer.
                                                                                         Leak rate is calculated from data determined to be valid by statistical analysis.
                                                                                         There must be no dispensing or product delivery during the test.

                                                                        Water Sensor:     A water sensor must be used to detect  water incursion.
                                                                                         Minimum water level detectable in the tank is 0.175 inches (0.27 inches for waste
                                                                                         oil).
                                                                                         Minimum change in water level that can  be detected is 0.088 inches (0.031 inches
                                                                                         for waste oil).

                                                                        Calibration:        Mass measurement probe and water  sensor must be checked  and calibrated
                                                                                         annually.

                                                                         This is a banery operated system and does not automatically generate a hard copy of the leak test
                                                                        result. However, a hard copy of  the results can  be obtained by transfer of data to another unit (see
                                                                        manufacturer's instructions for further details). This system is not equipped with any alarms (e.g. high
                                                                        water alarm,  or failed leak test alarm.

                                                                        Comments:        This equipment was not evaluated using manifolded tanks.
                                                                                         This equipment only tests the portion of the tank that contains product.
                                                                                         As the product level is lowered the leak rate in a leaking tank decreases (due to
                                                                                         lower head pressure).
                                                                                         2000-X model which was certified for use on tanks up to 30,000 gal capacity and
                                                                                         2000-XB model which was certified for use on tanks up 72,948 gallons are still
                                                                                         under review.
Atert Tachnolooiee, Inc.
3350 W. Salt Crook Une, Suits 109
Arlington Heighte, IL 60O05
Tot: (800) 322-7845
                                                   Evaluator: MMwaat Ramroh liMtitute
                                                                                                                                                                 Date of Evaluation: 3-11-91

-------
                                                                         DRAFT
                               Anttovtr Control* Corporation

                                     Arvdovw Infinity
                             CX3000, CX9200, and CMX240

                          AUTOMATIC TANK GAUGING SYSTEM

Certification:          Usk rat* of 0.1 gslton P*r hour with PD-97.6% & P,A-2.4%.

Leak Threshold:       0.05 gallon per hour (a teak is declared if the output of the meaniremtnt
                     system exceeds tills threshold).

AppNcabBity:          Gasoline, dlesel, aviation fuel, fuel oil #4, fuel oil *6, solvents,  and other
                     compatible products with known coefficients of expansion and density.

Capacity:             The maximum tank capacity is 15,000 gallons.
                     The tank must be between 50 and 95% full.

Waiting Thru:         Minimum waiting  time between delivery to the tank and test data collection
                     must be 6 hours.

Test Period:           The minimum  data collection time must be 6 hours.
                     Test data is acquired and recorded by a computer.
                     Leak rate is calculated as the average of subsets of all data collected.
                     There must be no dispensing or product delivery during the test.

Temperature:          A minimum of 3 Resistance Temperature Detectors must be used to determine
                     the average temperature of the stored product.

Wotsr Sensor:         A water sensor must be used to detect water incursion.
                     Minimum water level detectable in the tank is 0.35 inches.
                     Minimum detectable change in water level is 0.003 inches.

Calibration:           Temperature sensors and probe must be checked and calibrated in accordance
                     with manufacturer's instructions.

Comments:           This equipment was not evaluated using manifolded tanks.
                     This equipment only tests the portion of the tank that contains product.
                     As the product level is lowered the leak rate in a leaking tank decreases (due
                     to tower head pressure).
Andovw Control! Corporation
3OO IriekttoM Squaw
Andovw. MA 01810
T«fc (SOS) 470-O55S
                                                  Ev«tu«
-------
                                      API/Ronan

                               X-76 ETM & X-76 ETM-4X
                                                                         DRAFT
                         AUTOMATIC TANK GAUGING SYSTEM

                    Laak rate of 0.2 gallon per hour with PD = 99.96% & PM
                                                                          0.044%.
Certification:

Uak Threshold:       0.1 gallon per hour (• leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel. aviation fuel, fuel oil #4, solvents, waste oil, and other
                     substances with specific gravity > 0.60 and viscosity < 1500 cp.

Capacity:             The maximum tank capacity is 15,000 gallons.
                     The tank must be between 10 and 95% full.

Waiting Time:         Minimum waiting time between product delivery and test data collection
                     must be 2 hours.
                     There must be no dispensing or product delivery during the test waiting
                     time.

Test Period:          The minimum data collection time must be 4 hours.
                     Test data must be acquired and recorded by a computer.
                     Leak rate calculated from data determined to be statistically valid.

Temperature:         Minimum of 1 resistance temperature detector must be used to determine
                     the average temperature of the stored substance.

Water Sensor:        A water sensor must be used to detect water incursion.
                     Minimum water level detectable in the tank is 0.947 inches.
                     Minimum detectable  water level change is 0.0254 inches.

Calibration:           Temperature sensors and probes  must be checked and calibrated annually in
                     accordance with manufacturer's instructions.

Comments:           This equipment was  not evaluated using  manifolded tanks.
                     This equipment tests only that portion of the tank which contains product.
                     As the product level  is lowered the leak rate in a leaking tank decreases
                     (due to lower head pressure).
                     Change in product volume is measured using magnetostrictive probe.
                     This system is identical to Patriot Sensor's 7021 Digital Tank Gauge.
                     X76ETM-4X console has different housing which allows it to be mounted
                     outside.
API/Rerun
230O E. Artotia Blvd.
Lona Baach. CA  90805-4113
|310) 984-5380
                                          Evaluator:  Km Wiloox Aaaoolataa
                                          Data of Evaluation: 02-07-91
                                                                                                                                                    API/Ronan

                                                                                                                                             X-76 ETM & X-76 ETM-4X
                                                                                                                                                                                     DRAFT
                           AUTOMATIC TANK GAUGING SYSTEM  _  .      _	    „

 Certification:          Leak rate of 0.1 gallon per hour with P0 = 95.34% & PfA  - 4.66%.

 Leak Threshold:        0.05 gallon per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

 Applicability:          Gasoline, diesel, aviation fuel, fuel oil #4, solvents, waste  oil, and other
                      substances with specific gravity > 0.60 and viscosity  < 1500 cp.

 Capacity:             The maximum tank capacity is 15,000 gallons.
                      The tank must be between 10 and 95% full.

 Waiting Time:         Minimum waiting time between product delivery and test data collection
                      must be 8 hours.
                      There must be no dispensing or product delivery during the test waiting
                      time.

 Test-Period:           The minimum data collection time must be 4 hours.
                      Test data must be acquired and recorded by a computer.
                      Leak rate calculated from data determined to be statistically valid.

 Temperature:          Minimum of 1 resistance temperature detector must be used to determine
                      the average temperature of the stored substance.

 Water Sensor:         A water sensor must be used to detect water incursion.
                      Minimum water level detectable in the tank is 0.947 inches.
                      Minimum detectable water level change is 0.0254 inches.

 Calibration:            Temperature sensors and probes must be checked and calibrated annually in
                      accordance with manufacturer's instructions.

 Comments:            This equipment was not evaluated using manifolded tanks.
                      This equipment tests only that portion of the tank which contains product.
                      As the product level is lowered the teak rate in a leaking tank decreases
                      (due to lower head pressure).
                      Change in product volume is measured using magnetostrictive probe.
                     This system is identical to Patriot Sensor's 7021 Digital Tank Gauge.
                      X76ETM-4X console has different housing which allows it to be mounted
                     outside.
AFI/Ronan
2300 E. Arteaia Blvd.
Long Baach, CA  90805-4113
(310) 984-5380
                                                                                                                                                              Evaluator:  Kan Wiloox Aaaooiataa
                                                                                                                                                              Data of Evaluation: 11-21-91
                                                                                                                                                       10

-------
                                                                               DRAFT
                                        APWRonan

                          Ronin X-78 Automate Une U*k Detector
                vir. X-78 DM-4 Microprocessor and JT-H2 Urx Pressure S«ntor

                      AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification:          Leak rate of 3.0 gallon ptr hour with P0-100% & P,A-0%.

Leak Thr«tlio)d:       0.831 gallon per hour (i leak it declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil *4 & #6, solvent, and waste oil.

Specification:         System is installed on pressurized fiberglass and steel pipelines.
                     The piping system volume must not exceed 45 gallons.
                     Tests are conducted at the line operating pressure.
                     The mechanical line leak detector must be removed from the pipeline
                     system.

Waiting Time:         No waiting time between last delivery of the product to the tank and the
                     start of data collection.
                     No waiting time between last dispensing of product through the pipeline
                     and the start of data collection for the test.

Test Period:          The minimum data collection time (response time) for the test must be 20
                     seconds.
                     Test data  must be acquired and recorded by a permanently installed
                     microprocessor.
                     Calculations are automatically done by the microprocessor.

System Features:      This system is permanently installed on the pipeline and automatically tests
                     the line;
                     uses a preset threshold and a single test to determine whether the pipeline
                     is leaking.
                     If a leak is declared, this system displays a message, triggers an alarm, and
                     shuts down the dispensing system.

Calibration:           Sensor must be checked and calibrated annually in accordance with
                     manufacturer's instructions.
                                                                                                                                             DRAF1
                                                                                                            APWRoosn

                                                                                              Ronan X-76 Automatic Una U*k Detector
                                                                                    VST. X-78 DM-4 Mfcrop«>c«stor and JT-H2 Lin* Pressure Sector

                                                                                          AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

                                                                    CerthTcatJon:          Leak rate of 0.1 gallon per hourwith P0-100% and P,A-0%.

                                                                    Leak Threshold:       0.066 galton per hour (a leak I* declared If the output of the measurement
                                                                                         system exceeds this threshold).

                                                                    Applicability:          Gasoline, diesel, aviation fuel, fuel oil #4 & *6, solvent, and waste oil.

                                                                    Specification:         System is installed on pressurized fiberglass and steel pipelines.
                                                                                         The piping system volume must not exceed 45 gallons.
                                                                                         Tests are conducted at the  line operating pressure.
                                                                                         The mechanical line leak detector must be removed from the pipeline
                                                                                         system.

                                                                    Waiting Time:         No waiting time between last delivery of the product to the tank and the
                                                                                         start of data collection.
                                                                                         Waiting time between last dispensing of product through the pipeline and
                                                                                         the start of  data collection for the test must be 2 hours.

                                                                    Test Period:           Minimum data collection time (response time) for the test must be 20
                                                                                         minutes.
                                                                                         Test data must be acquired  and recorded by a permanently installed
                                                                                         microprocessor.
                                                                                         Calculations are automatically done by the microprocessor.

                                                                    System Features:      This system is permanently  installed on the pipeline and automatically tests
                                                                                         the line.
                                                                                         Uses a preset threshold and a single test to determine whether the pipeline
                                                                                         is leaking.
                                                                                         If a leak is declared, this system displays a message, triggers an alarm, and
                                                                                         shuts down the dispensing system.

                                                                    Calibration:           Sensor must be checked and calibrated annually in accordance with
                                                                                         manufacturer's instructions.
API/Ronan
23OO Ext Art.ti. Blvd.
LongBuch, CA 91355
Tel: (8OO) 834-0085
Evaluator: Mdwaat Retearch Inatituta



Data of Evaluation: 10/4/91
'API/Ronan
 2300 Eait Artoiio Blvd.
 Long Baach. CA 91355
 Tel: (800) 634-OO8S
Evaluator: Mklwaat Reaaarch Inatituta


Data of Evaluation: 1O-04-91
                                            11
                                                                                                                                                          12

-------
                                                                        DRAFT
                               Arizona Instrument Corporation

                                  Encompass MTS IPAM
                                  (Magnetostrictlva Probe)

                           AUTOMATIC TANK GAUGING SYSTEM

Certification:      Leak rate of 0.2 gallon per hour PD = 97.80% & PFA = 2.20%.

Leak Threshold:   0.10 gallon per hour (a leak is declared if the output of the measurement system
                                  exceeds this threshold).

Applicability:      Gasoline, Diesel, Aviation Fuel, Fuel Oil #4, Fuel Oil #6, Solvents, Waste Oil, and
                                  other products which are compatible with the probe.

Capacity:         The maximum tank capacity is 15,000 gallons.
                 The tank must be at least 50% full.

Waiting Tim*:     The minimum waiting  period between delivery to the tank and test data
                 collection must be 3 hours.

Test Period:      The minimum data collection time must be 6 hours.
                 Test data must be acquired and recorded by a computer.
                 Leak rate is calculated from data determined to be valid by statistical analysis.
                 There must be no dispensing or product delivery during the test.

Temperature:     A minimum of 5 Resistance Temperature Detectors must be used to determine
                 the average temperature of the stored substance.

Water Senior:     A water sensor must be used to detect water incursion.
                 Minimum water level detectable in the tank is 1.29 inches.
                 Minimum change in water level that can be detected is 0.0034 inches.

Calibration:       Temperature  sensors and probe must be annually checked and calibrated in
                 accordance with manufacturer's instructions.

Comments:       This equipment was not evaluated using manifolded tanks.
                 This equipment only tests that portion of the tank which  contains product.
                 As the product level is lowered, the leak rate in a leaking tank decreases (due to
                 lower head pressure).
                 Encompass software provides for remote access capabilities.
Arizona Inatrumant Corp.
4114EaatWoodStraat
Phoanix, Arizona 85040
Tel: (800)528-7411
                                          Evaluator: Kan Wilcox Aacociatoa
                                          Data of Evaluation: 08/22/94
                                           13
                                                                         DRAFT
               1                Arizona Instrument Corporation

                                   Encompass USF IPAM
                                     (Ultrasonic Probe)

                           AUTOMATIC TANK GAUGING SYSTEM

Certification:      Leak rate of 0.2 gallon per hour with P0 = 99.94% & PFA = 2.06%.

Leak Threshold:   0.10 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:      Gasoline, Diesel, Aviation Fuel, Fuel Oil #4, Fuel Oil #6, Solvents, Waste Oil, and
                 other products which are compatibla with the probe.

Capacity:         The maximum tank capacity is 15,000 gallons.
                 The tank must be at least 50% full.

Waiting Time:     The minimum waiting period between delivery to the tank and test data
                 collection must be 3 hours.

Test Period:      The minimum data collection time must be 6 hours.
                 Test data must be acquired and recorded by a computer.
                 Leak rate is calculated from data determined to  be valid by statistical analysis.
                 There must be no dispensing or product delivery during the test.

Temperature:     A single non-circulating sensor measures change in ultrasonic wave velocity to
                 determine the average temperature of the stored substance.

Water Sensor:     A water sensor must be used to detect water incursion.
                 Minimum water level detectable in the tank is 1.86 inches.
                 Minimum change in water level that can be detected  is 0.012 inches.

Calibration:       Temperature sensors and probes must be checked and calibrated annually in
                 accordance with manufacturer's instructions.

Comments:       This equipment was not evaluated using manifolded tanks.
                 This equipment only tests that portion of the tank which contains product.
                 As the product level is lowered the leak rate in a leaking tank decreases (due to
                 lower head  pressure).
                 Encompass software provides for  remote access capabilities.
Arizona tnatrumont Corp.
4114 Ea»t Wood Street
Phoonix, AZ 8B040
Tel: (800) 528-7411
Evduotor: Kan Wilcox A«oc!ita>


Data of Evaluation: 08/22/04
                                                                                                                                                   14

-------
                              Arfroni fcwtnimtnt C
-------
                               Arizona Instrument Corporation

                                   Sol Sentry Twehre-X
                                                  DRAFT
                                                          Arizona Instrument Corporation

                                                               Sol Sentry Twelve-X
                                                                         DRAFT
                     VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
Output type:          quantitative
Sampling frequency:   continuous
Operating principle:    metal oxide semiconductor
                                                                                                  VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                                       Detector:
                                                                              Output type:          quantitative
                                                                              Sampling frequency:   continuous
                                                                              Operating principle:    metal oxide semiconductor
Teat Results:
Accuracy' (%):
Bias* (%):
Precision* l%):
Detection Time (min:sec):
Fall Time' (min:sec):
Lower Detection Limit
    (ppm):
Commercial
Gasoline
170
60
6.3
12:20
11:53
Synthetic
Gasoline
120
8.0
7.7
12:27
11:53

JJM
120
1.8
18
12:33
11:55
150
                 140
                                 60
JP-S
Notdet.
Notdet.
Notdet.
Not det.
Not det.

92"
* For tests conducted with 1000 ppm of test gas.
•* Testing was done using a JP-5 concentration on 90 ppm in humidified air.

Specificity Results (%):

    Commercial gasoline   170
    n-Hexane             110
    JP-4 jet fuel           90
    Synthetic gasoline     110
    Toluene              43
    Xylene(s)             22

Manufacturer's Specifications:
Comments:  The test procedures used were those in Radian Corporation's draft report
            •Development of Procedures to Assess the Performance of External Leak Detection
            Devices: Vapor-Phase ASTM-Formatted Methods,* June 29, 1990.  Please note there
            is another specification sheet for this system, regarding a separate evaluation.
Arizona Inatrumant Corporation
4114 E«t Wood St.
Phoanix, AZ 86040-1941
(602)470-1414
                Evaluator: Radian Corporation

                Data of Evaluation: 12-28-90
                Date of Evaluation. JP-5 only: 04-17-91
                                                                              Test Results:

                                                                              Accuracy (%):
                                                                              Bia's:
                                                                              Precision:
                                                                              Detection Time (mini:
                                                                              Fall Time (min):
                                                                              Lower Detection Limit:
                              Diesel Fuel
                              Not determined
                              -20 ppm 0 50 ppm
                              12 ppm
                              15
                              15
                              10 ppm
JM
Not determined
Not determined
Not determined
15
15
<0.01 gal/hr
 Specificity Results*:

     Activated:    Diesel Fuel, JP-8

 • A limited number of tests were conducted to determine the response of the system to Diesel and
 JP-8.

' Manufacturer's Specifications:


 Comments:  The test procedures used were modified from EPA's 'Standard Test Procedures for
             Evaluation Leak Detection Methods: Vapor-Phase Out-of-Tank Product Detectors,*
             March 1990, and Radian Corporation's draft report 'Development of Procedures to
             Assess the Performance of External Leak Detection Devices: Vapor-Phase ASTM-
             Formatted Methods,* June 6, 1990. Please note there is another specification sheet
             for this system, regarding a separate evaluation.
                                                                                                        Arizona Inatnnrant Corporation
                                                                                                        4114EaatWoodSt.
                                                                                                        Pnoanix. AZ 85040-1941
                                                                                                        (602)470-1414
                                                                                                                            Evaluator: Kan Wilcox Aaaociataa


                                                                                                                            Dst« of Evaluation: 02-18-92
                                           17
                                                                                                                                                   18

-------
                          A»«oclrt*d EnvVcxim*nUl Syttimi, inc.

                              AES Systtm II (OvirflB»d T»»t)
                                                                             DRAFT
                          As*oc!at»d EnvfconroeotaJ Syttwra. Inc.

                        AES Sy*1»m It (Ov*ff*«d Tt«t - two* T«nta)
                                                                       DRAFT
                      VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 flillon per hour with P0-97.7% & PM-2.3%.

L«ak Threshold:       0.05 galton per hour (a teak is declared if the output of the measurement
                     lyitam exceed* this threshold).

Applicability:          Gasoline, diewl, aviation fuel, fuel oil, waste oil, and solvent*.

Capacity:             Maximum tank capacity is 15,000 gallons.
                     The tank must be at least 100% full.

Waiting time:         Waiting period between delivery and the beginning of the test included in
                     waiting period after "topping off".
                     Waiting time between "topping off" and beginning the test is computer-
                     dictated by real-time analysis of level and temperature data.
                     Waiting time is generally 4 to  12 hours.
                     There must be no dispensing or product delivery during the test waiting
                     time.

Test Period:          The minimum data collection time is 2 hours (two  one-hour tests).
                     Test data must be acquired and recorded by a computer.
                     Leak rate is calculated from the data of last 1.5 hours of test period.
                     There must be no dispensing or product delivery during the test.

Temperature:         A minimum of 5 temperature sensors must be used to determine the
                     average temperature of the stored hazardous substance.

Ground Water:        Depth to the water  table present in the backfill must be determined, and if
                     it is above the bottom of the tank, product level must be adjusted to
                     provide minimum of 2 psi net pressure on the bottom of the  tank during the
                     test.

Calibration:           Level sensors must  be calibrated before each test in accordance with
                     manufacturer's instructions.
                     Temperature sensor must be calibrated annually in accordance with
                     manufacturer's instructions.

Comments:           This equipment was not evaluated using manifolded tanks.
                       VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with P0-98.9% & P,A-1.1%.

U»lc Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil, waste oil, and solvents.

Capacity:             The maximum tank capacity is 75,000 gallons.
                     The tank must be 100% full.

Waiting Time:         Minimum waiting time after adding any substantial amount of product to
                     the tank is 24 hours.
                     Waiting time between "topping off" and beginning the test is computer-
                     dictated by real-time analysis of level and temperature data and must be at
                     least 1 hour.
                     There must be no dispensing or product delivery during the test waiting
                     time.

Test Period:          The minimum data collection time must be 4 hours.
                     Test data must be acquired and recorded by a computer.
                     Leak rate is calculated from the data of 3 hours of test period.
                     There must be no dispensing or product delivery during the test.

Temperature:         A minimum of 12 thermistors must be used to determine the average
                     temperature of the stored hazardous substance.

Ground Water:        Depth to the water table present in the backfill must be determined, and if
                     it is above the bottom of the tank, product level must be adjusted to
                     provide minimum of 2 psi net pressure on the bottom of the tank during the
                     test.

Calibration:           Level sensors must be calibrated before each test in accordance with
                     manufacturer's instructions.
                     Temperature sensors must be calibrated annually in accordance with
                     manufacturer's instructions.

Comments:           This equipment was not evaluated using  manifolded tanks.
Asiccinted Environmental Syetema, Inc.
3101 N. SHIeot, Suit. 105
Bakerafield. CA 93308
Tel: (805) 326-1073
                                                           Evaluator: Villa Research
                                                           Evaluation Completed: 12-20-SO
Auociated Environmental, Inc.
3101 N. Sillect, Suite 105
Bakerafield, CA 93308
Tel: (805) 328-0173
Evaluator: Ken Wilcox Aaaooiatae


DIM of Evaluation: 02-28-92
                                            19
                                                                                                                                                    20

-------
                           Associated Environmental Systems. Inc.

                                     Modal PLT-100R
                                                                              DRAFT
                                       Campo/MHIar

                                    LS300 & LS300 NIC
                                                                        DRAFT
                              LINE TIGHTNESS TEST METHOD                            .

Certification:          Leak rate of 0.1 gallon per hour with P0 = 100% & PFA=0%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil,  waste oil, and solvents.

Capacity:             System tests fiberglass and steel piping.
                     The piping system volume must  not exceed 80 gallons.
                     Tests are conducted at 150% of the line operating pressure.
                     Mechanical line leak detector must be  removed from the piping system
                     being tested.

Waiting Tim*:         There is no waiting period between delivery and testing.
                     Minimum waiting time between last dispensing and testing is 1 hour.

Test Period:          The minimum data collection time must be 30 minutes.
                     Test data must be acquired and recorded manually.
                     Two tests with zero time  between the tests are required before a leak can
                     be declared.

Calibration:           Equipment must be calibrated annually in accordance with manufacturer's
                     instructions.
                       AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification:          Leak rate of 3 gallons per hour with P0 = 96.2% & PFA = 0%.

Laak Threshold:       2.36 gallons per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuels #4 & #6, waste oil,  kerosene, and solvents.

Specifications:        System is installed on pressurized fiberglass and/or steel piping.
                     The piping system must not exceed 35.36 gallons.
                     Tests are conducted at the line operating pressure.

Waiting Time:         There is no waiting time between product delivery and testing.
                     There is no waiting time between last dispensing and testing.

Test Period:          Minimum data collection time is 10 seconds.
                     Test data  is acquired and recorded by the microprocessor.

Calibration:           Manufacturer recommends a weekly self check, activated by the operator,
                     and a full functional test every 30 days, estimated to take 5 minutes to
                     perform.

System Features:      This system is permanently installed on the piping and automatically tests
                     the line.
                     It uses a preset threshold and a single test to determine whether the
                     pipeline is leaking.
                     If a leak is declared, this system will energize an indicator light, trigger an
                     audible alarm, and shut down the dispensing system.
Associated Environmental Syetem, Ino.
301 ON. Sfflect, Suite 106
BakerafieM. CA 93308
Tel: (805) 328-0173
                                                           Evaluator: Vista Reeearch
                                                           Data of Evaluation: 11/21/90
                                                                                                         Cempo/Miller, Ino.
                                                                                                         P. O. Box 1809
                                                                                                         Portorvillo. CA 93258
                                                                                                         (209)781-8862
                                                       Evaluator:  Jetronix Engineering Laboratorjee
                                                       Evaluation Data: 08-O1-91
                                                       Reviewed by: Ken Wilcox Atiocintoi
                                                       R.vi.« D.t«;
                                            21
                                                                                                                                                     22

-------
                                       Campo/Mffitr

                               LS300-120 & LS300-120 XLC
                    DRAFT
                                                                                                                                                                                 DRAFT
                                                                                                                                   LS300-120 PLUS 4 LS300-120 PLUS A/S
                      AUTOMATIC ELECTRONIC UNE LEAK DETECTOR

Certification:          L««k rat* of 3 gallon* ptr hour with P0 - 96.2% & P,A - 0%.

L««k Threshold:       2.36 o>Jton» par hour {• leak i> declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, dfetel, aviation fuels *4 & *6, waste oil, kerosene, and solvent!.

Specifications:        System is installed on pressurized fiberglass and/or steel pipino,
                     The piping system must not exceed 35.36 gallons.
                     Tests are conducted at the line operating pressure.

Waiting Time:         There Is no waiting time between product delivery and testing.
                     There is no waiting time between last dispensing and testing.

Test Period:          Minimum data collection time is 10 seconds, but can be adjusted between
                     10 and 150 seconds depending on the bulk modulus of the piping system.
                     Test data is acquired and recorded  by the microprocessor.

Calibration:           Manufacturer recommends a weekly self check,  activated by the operator,
                     and a full functional test every 30 days, estimated to take 5 minutes to
                     perform.

System Features:     This system is permanently installed on the  piping and automatically tests
                     the line.
                     It uses a preset threshold and a single test to determine whether the
                     pipeline is leaking.
                     If a leak is declared, this system will energize an indicator light, trigger an
                     audible alarm,  and shut down the dispensing system.
                                                                        AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

                                                  Certification:          Leak rate* of 3 gallons par hour with PD - 96.2% & PFA - 0%.

                                                  Leak Threshold:       2,38 gallons per hour (a leak f» declared if the output of the measurement
                                                                       system exceeds this threshold).

                                                  Applicability:          Gasoline, dlesel, aviation fuels 14 & 06, waste oil, kerosene, and solvents.

                                                  Specifications:        System is Installed on pressurized fiberglass and/or steel piping.
                                                                       The piping system must not exceed 35.36 gallons.
                                                                       Tests are conducted at the line operating pressure.

                                                  Waiting Time:         There is no waiting time between product delivery and testing.
                                                                       There is no waiting time between last dispensing and testing.

                                                  Test Period:          Minimum data collection time is 10 seconds, but can be adjusted between
                                                                       10 and 150 seconds depending on  the bulk modulus of the piping system.
                                                                       Test data is acquired and recorded  by the microprocessor.

                                                  Calibration:           System must be calibrated annually in accordance with manufacturer's
                                                                       instructions.

                                                  System Features:      This system is permanently installed on the piping and automatically tests
                                                                       the line.
                                                                       It uses a prasst threshold and a singls tost to determine whether ths
                                                                       pipeline is leaking.
                                                                       If a leak is declared, this system will energize an indicator light, trigger an
                                                                       audible alarm, and shut down the dispensing system.
Campo/MiMftr, Inc.
P. 0.80x1809
PortorviNe. CA 932S8
(209) 781-6882
                                                                                                          • The LS300-120 PLUS 6 LS300-120 PLUS A/S have additional leak detection capabilities, which
                                                                                                          are under review.
Evaluator: Jatronix Engineering Laboratoriet
Evaluation Oato: O6-O1-91
Reviewed by: Kan Wiloox Associates
Review Date: 09-09-94
Campo/Miller, Inc.
P.O. Box 1809
Portervilla, CA 93258
(209) 781-6862
Evaluator: Jatronix Engineering Laboratories
Evaluation Oato: Oe-OI-91
Reviowad by: Ken WiJcox Associates
Review Date: 09-09-94
                                            23
                                                                                                                                                     24

-------
                                     Control Engine*™

                                    Una Leak Detector
                                        Model LLP1
                                                                           DRAFT
                                                                                                                              DRAFT
                      AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification:          Leak rate of 3.0 gallons per hour with P0 = 100% & PFA = 0%.

Leak Threshold:       1.88 gallons per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diasel, and aviation fuel.

Specification:         System is installed on pressurized fiberglass and steel piping.
                     The piping system volume must not exceed 89 gallons.
                     Tests are conducted at the line operating pressure.

Waiting Time:        No waiting period between product delivery and testing.
                     No waiting period between last dispensing and testing.

Test Period:          Data collection time (response time) is about 10 seconds.
                     Test data must be acquired and recorded by permanently installed
                     microprocessor.
                     Calculations are automatically done by the microprocessor.

System Features:     This system is permanently installed on the piping and automatically tests
                     the tine.
                      It uses a preset threshold and a single test to determine whether the piping
                      is leaking.
                      If a leak is declared, this system  displays a message, triggers an alarm, and
                      shuts down the dispensing system.

 Calibration:           Sensor must be checked  and calibrated annually in accordance with
                      manufacturer's instructions.

 Comments:           This equipment is no longer produced by Control Engineers.
                                                                                          Control Engineers

                                                                                         Line Leak Detector
                                                                                            Model LLP2

                                                                           AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

                                                     Certification:          Leak rate of 3.0 gallons per hour with P0 = 100% & PFA = 0%.

                                                     Leak Threshold:       1.88 gallons per hour (a leak is declared if the output of the measurement
                                                                          system exceeds this threshold).

                                                     Applicability:          Gasoline, dieset, and aviation fuel.

                                                     Specification:         System is installed on pressurized fiberglass and steel piping.
                                                                          The piping system volume must not exceed 89 gallons.
                                                                          Tests are conducted at the line operating pressure.

                                                     Waiting Time:         No waiting  period between product delivery and testing.
                                                                          No waiting  period between last dispensing and testing.

                                                     Test Period:          Data collection time (response time) is about 10 seconds.
                                                                          Test data must be acquired and recorded by permanently installed
                                                                          microprocessor.
                                                                          Calculations are automatically  done by the microprocessor.

                                                     System Features:      This system is permanently installed on the piping and automatically tests
                                                                          the line.
                                                                          It uses a preset threshold and  a single test to determine whether the piping
                                                                          is  leaking.
                                                                          If a leak is declared, this system displays a message, triggers an  alarm, and
                                                                          shuts down the dispensing system.

                                                     Calibration:           Sensor must be checked and calibrated annually in accordance with
                                                                          manufacturer's  instructions.

                                                     Comments:           This equipment is no longer produced by Control Engineers.
 Control Engineers
 P. O. Box 9037
 114MensrdRo»d
 Hourn*. LA 70381
 Tel: (504) 872-4541
                                                    Evsiustor: Midwest Research Institute
Date of Evaluation:  08/07/91
                                                     Control Engineers
                                                     P. 0. Box 9037
                                                     114Monord Rood
                                                     Houme, LA  70361
                                                     Tel: (504) 872-4541
                                                                                                                                                             Evduator: Midweat Research Institute
Date of Evaluation: 08/07/91
                                             25
                                                                                                                                                     26

-------
                                                                             DRAFT
Ctrtrflcatkxi:

Leak Threshold:


AppKobUfty:

Specification:



Waiting Tlm»:



Test Period:





System Features:
Calibration:


Comments:
                Control &igirtMn

               Urn Utk D»t*ctor
                   Modtl LLP2

 AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Leak rite of 0.1 gallon per hour with P0-100% & P,A-0%.

0.05 gallon per hour (i Isik is declared if the output of the measurement
system exceeds this threshold).

Gasoline, diets!, and aviation fuel.

System is installed on pressurized fiberglass and steel piping.
The piping system volume must not exceed 89 gallons.
Tests are conducted at the line operating pressure.

There is no waiting period between product delivery and testing.
Minimum waiting period between dispensing of product through the piping
and testing is 15 minutes.

Minimum data collection time is 30 minutes.
Test data must be acquired and recorded by permanently-installed
microprocessor.
Calculations are automatically done by the microprocessor.

This system is permanently installed on the piping and automatically tests
the line.
It uses a preset threshold and a single test to determine whether the piping
is leaking.
If a leak is declared, this system  displays a message, triggers an alarm, and
shuts down the dispensing system.

Sensor must be checked and calibrated annually in accordance with
manufacturer's instructions.

This equipment is no longer produced by Control Engineers.
Cortfficntton:

Leak Thrtshotd:


Applicability:


Capacity:


Waiting Time:



Test Period:




Temperature:


Water Sensor:



Calibration:


Comments:
Control Engineer*
P. O. Box 9037
114 Msnard Road
Houma, LA 70381
Tel: 1504) 872-4541
                                                   Evaluator: Midwest Research Institute
                                                   Date of Evaluation: 08/07/91
                                                                                    EBW, INC.
                                                                                    2814 McCrakan Avenue
                                                                                    Muskegon. Ml 49443
                                                                                    Tel: (800) 475-5151
                   EBW. Inc.

        EBW Auto-Stik H and Atrto-Sttk Jr.


      AUTOMATIC TANK GAUGING SYSTEM

Leak rate of 0.2 gph with PD-99.9% & PM-0.1%.

0.10 gallons per hour (a leak is declared if the output of the measurement
system exceeds this threshold).

Gasoline, Diesel, Aviation Fuel, Fuel Oil #4, Fuel Oil #6, Solvents, and other
compatible products with known coefficients of expansion and densities.

The maximum tank capacity Is 15,000 gallons.
The tank must be at least 50% full.

The minimum waiting period between delivery and testing is 6 hours.
The minimum waiting period between dispensing and testing is 6 hours.
There must be no product delivery during the test waiting time.

The minimum data  collection time must be 4 hours.
The test data must be acquired and recorded by a computer.
Leak rate is calculated from average of subsets of all data collected.
There must be no dispensing or product delivery during the test.

Minimum of 5 Thermistors  must be used to determine the average
temperature of the  stored regulated substance.

A water sensor must be used to detect water incursion.
Minimum water level detectable in the tank is 0.49 inches.
Minimum detectable water level change is 0.0052 inches.

Temperature sensor and probe must be checked and calibrated in
accordance with manufacturer's instructions.

This equipment was not evaluated using manifolded tanks.
This equipment only tests the portion of the tank that contains product.
As the product level is lowered the leak rate in a leaking tank decreases
(due to lower head  pressure).
Auto Stik Jr.  is used with up to 4 magnetostrictive probes and can handle
up to 8 input sensors.
Auto Stik II is used with up to 16 magnetostrictive probes and can handle
up to 64 input sensors.

                                  Evaluator: Kan Wilcox Associate*
                                                                                                                                           Date of Evaluation: 08-20-93
                                            27
                                                                                                                                                     28

-------
                                        EBW, Inc.

                             EBW Auto-Stik II and Auto-Stile Jr.
                                                                         DRAFT
                           AUTOMATIC TANK GAUGING SYSTEM                   "'

Certification:          Leak rate of 0.1 gallon per hour with PD = 98.3% & Pw = 1.7%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil #4, fuel oil #6, solvents, and other
                     compatible products with known coefficients of expansion and densities.

Capacity:             The maximum tank capacity is 15,000 gallons.
                     The tank must be between 50 and 95% full.

Waiting Time:         Minimum waiting time between delivery to the tank and test data collection
                     must be 6 hours.

Test Period:          The minimum data collection time must be 4 hours.
                     The test data must be acquired and recorded by a  computer.
                     Leak rate is calculated from average of subsets of  all data collected.
                     There must be no dispensing or product delivery during the test.

Temperature:         Minimum of 5 thermistors must be used to determine the average
                     temperature of the stored product.

Water Sensor:        A water sensor must be used to detect water incursion.
                     Minimum water level detectable in the tank is 0.49 inches.
                     Minimum detectable water level change is 0.0052 inches.

Calibration:           Temperature sensor and probe must be checked and calibrated in
                     accordance with manufacturer's instructions.

Comments:           This equipment was not evaluated using manifolded  tanks.
                     This equipment only tests the portion of the tank that contains product.
                     As the product level is lowered the leak rate in a leaking tank decreases
                     (due to lower head pressure).
                     Auto Stik Jr. is used with up to 4 magnetostrictive probes and can handle
                     up to 8 input sensors.
                     Auto Stik II is used with up to 16 magnetostrictive probes and can handle
                     up to 64 input sensors.
 EBW, INC.
 2814 McCrokon Avenue
 Muskegon, Ml 49443
 Tel: (800) 475-5151
                                                        Evsiuetor: Ken WUoos Associate:
Date of Evaluation: 08-20-93
                                            29
                                                                                      Egem'n Naamloze Vennootschap

                                                                                                 E'SPI III
                                                                                   AUTOMATIC TANK GAUGING SYSTEM

                                                       Certification:          Leak rate of 0.2 gallon per hour with P0 = 97.9% &PFA=1.1%.

                                                       Leak Threshold:        0.075 gallon per hour (a leak is declared if the output of the measurement
                                                                             system exceeds this threshold).

                                                       Applicability:          Gasoline, diesel, aviation fuel, and solvents.

                                                       Capacity:             The maximum tank capacity is 15,000 gallons.
                                                                             The tank must be between 50 and 95% full.
                                                                                                                          ij
                                                       Waiting Time:         Minimum waiting time between delivery to the tank and test data collection
                                                                             must be 7 hours.

                                                       Test Period:           Minimum data collection time must be 5.5 hours.
                                                                             The test data must be acquired and recorded by a computer.
                                                                             Leak rate is calculated from average of subsets of all collected data.
                                                                             There  must be no dispensing or product delivery during the test.

                                                       Temperature:          A single moving quartz crystal temperature sensor must be used to
                                                                             determine the average temperature of the stored hazardous substance.

                                                       Water Sensor:         A water sensor must be used to detect water incursion.
                                                                             Minimum water level detectable in the tank is 0.253 inches.
                                                                             Minimum change in water level that can be detected is 0.029 inches.

                                                       Calibration:           Temperature sensor and probe must be checked and calibrated annually in
                                                                             accordance with manufacturer's instructions.

                                                       Comments:           This equipment was not evaluated using manifolded tanks.
                                                                             This equipment only tests the portion of the tank that contains product.
                                                                             As the product level is lowered the leak rate in a leaking tank decreases
                                                                             (due to lower head pressure).
                                                        Egemin Naamloze Vennootschap
                                                        Bredabaan 1201 -2900
                                                        Schoten, Belgium
                                                        Tel: O11-32-3-O3/845 27 90
                                                                                                                                                                       Evaluator: Midwoit Raiearch Institute
                                                                                                               Data of Evaluation: 12/21/90
                                                                                                                                                            30

-------
                              Efftmln N*tmtoze Vtnnootschtp

                                         esniv
                                                                         DRAFT
                           AUTOMATIC TANK GAUGING SYSTEM

 Certification:         Leak rate of 0.2 gallon per hour with P0-97.2% & P,A-0.3%.

 Uak Threshold:       0.1 gallon per hour (a leak is declared if the output of the measurement
                     systam exceeds this threshold).

 Applicability:         Gasoline, diesel, aviation fuel, fuel oil, and solvents.

 Capacity:            The maximum tank capacity i* 15,000 gallons.
                     The tank must be between 50 and 95% full.

 Waiting Time:        Minimum waiting time between product delivery to the tank and test data
                     collection must be 6 hours.

 Test Time:           The minimum data collection time must be 2 hours and 15 minutes.
                     Test data must be acquired and recorded by a computer.
                     Leak rate is calculated from average of subsets of all collected data.
                     There must be no dispensing or product delivery during the test.

 Temperature:     "   A minimum of 5 temperature sensors must be used to determine the
                     average temperature of the stored hazardous substance.

 Water Senior:        A water sensor must be used to detect water incursion.
                     Minimum water level detectable In the tank is 0.253 Inches.
                     Minimum change in water level that can be detected is 0.029 inches.

 Calibration:           Temperature sensor and probe must be checked and calibrated annually in
                     accordance with manufacturer's instructions.

 Comments:           This equipment was not evaluated using manifolded tanks.
                     This equipment only tests the  portion of the tank that contains product.
                     As the product level is lowered the leak rate in a leaking tank decreases
                     (due to lower head pressure).
Egomln Naamloza Vannootiohap
Bndabaan 1201 -2900
Schotan, Bdgium
Tol: 011-32-3-03/645 2790
Ev«lu«tor: Midwnt Raaaaroh Inatituta


Data of Evaluation: 12/21/90
                                           31
                                                                                                                              DRAFT
                                                                                          Emeo Whsrtoo, toe.

                                                                                          EECO System Setfc*
                                                                                        (0.1 ophPrtciilonTttO

                                                                                 AUTOMATIC TANK GAUGING SYSTEM

                                                       Certification:     Leak rate of 0.1 gatlon p»r hour with P0 - 99% & P,A - 1 %.

                                                       Leak Threshold:  0.05 gallon per hour (a teak Is declared if the output of the measurement system
                                                                       exceeds this threshold).

                                                       Applicability:     Gasoline, diesel, aviation fuel, fuel oil #4,  solvents, waste oil, and other
                                                                       substances determined to be  compatible with probe.

                                                       Capacity:        Tha maximum tank capacity Is 15,000 gallons.
                                                                       The certification tests were done on a tank which was 50% & 95% full.

                                                       Watting Time:    Minimum waiting time between delivery to the tank and test data collection
                                                                       must be 6 hours.

                                                       Test Period:      Minimum data collection time must be 3.75  hours
                                                                       The data is acquired and recorded by a microprocessor.
                                                                       Microprocessor automatically determines test time based on tank size and
                                                                       product level.
                                                                       Leak rate is calculated from data determined to be valid by statistical analysis.
                                                                       There must be no dispensing  or product delivery during the test.

                                                       Temperature:     A minimum of 5 Resistance Temperature Detectors must be used to determine
                                                                       tha average temperature of the stored substance.

                                                       Water Sensor:    A water sensor must be used to detect water incursion.
                                                                       Minimum water level detectable in the tank  is 0.66 inches.
                                                                       Minimum detectable change in water level is 0.039 inches.

                                                       Calibration:      Temperature sensors and probe must be checked and calibrated annually in
                                                                       accordance with manufacturer's instructions.

                                                       Comment*:      This equipment was not evaluated using manifolded tanks.
                                                                       This equipment tests that portion of the tank which contains product.
                                                                       As the product level is lowered, the leak rate in a leaking tank decreases (due to
                                                                       lower head pressure).
                                                                       A magnetostrictive probe is used to measure changes in product volume.
Emco Whaaton, Inc.
114 MacKanan Drive
Caiy, NC  27511
Ttl: (800)342-6125
Evakiator: Midwaat Raaaarch Inatituta


Data of Evaluation:  02-08-94
                                                                                                                                                        32

-------
                                                                             DRAFT
                                   Emco WhMton, Inc.

                                   EECO System Series
                                   (0.1 gph Quick Tot)

                          AUTOMATIC TANK GAUGING SYSTEM

CortHication:     Leak rate of 0.1 gallon per hour with PD = 96% & PFA = 4%.

Leak Threshold:  0.05 gallon per hour (a leak is declared if the output of the measurement system
                exceeds this threshold).

Applicability:     Gasoline, diesel, aviation fuel, fuel oil #4, solvents, waste oil, and other
                substances determined to be compatible with probe.

Capacity:        The maximum tank capacity is 15,000 gallons.
                The certification tests were conducted on a tank which was 50% and 95% full.

Waiting Time:    Minimum waiting time between delivery to the tank and test  data collection
                must be 6 hours.

Test Period:      The minimum data collection time is 1.7 hours.
                The data is acquired and recorded by a microprocessor.
                Microprocessor automatically determines test time based on tank size and
                product level.
                Leak rate is calculated from data determined to be valid by statistical analysis.
                There must be no dispensing or product delivery during the test.

T«mparature:     A minimum of 5 Resistance Temperature Detectors must be used to determine
                the average temperature of the stored substance.

Water Sensor:    A water sensor must be used to detect water incursion.
                Minimum water level detectable in the tank is 0.66 inches.
                Minimum detectable change in water level is 0.039 inches.

Calibration:      Temperature sensors and probes must be checked and calibrated annually in
                accordance with manufacturer's instructions.

Comments:      This equipment was not evaluated using manifolded tanks.
                This equipment tests only that portion of the tank which contains product.
                As the product level is lowered, the leak rate in a leaking tank decreases (due to
                lower head pressure).
                A magnetostrictive probe is used to measure changes in product volume.
Emoo Whaaton, Inc.
114 MacKanan Drive
Ciry, NC  27511
Tel: (800)342-6125
                                                      Evatuator: Midwaat Reaaarch Infltituta
                                                      Data of Evaluation: 02-15-94
                                           33
                                                                         DRAFT
                                    Emco Wheaton, Inc

                                    EECO System Safes
                                  (0.2 gph Precision Test)

                           AUTOMATIC TANK GAUGING SYSTEM

Certification:      Leak rite of 0.2 gallon per hour with P0 - 99.1 % & PFA = 0.9%.

Le*k Threshold:   0.10 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:      Gasoline, diesel,  aviation  fuel, fuel oil #4 & #6, solvents, waste oil, and other
                 substances determined to be compatible with probe.

Capacity:         The maximum tank capacity is 15,000 gallons.
                 The tank must be at least 50% full.
     
-------
                                                                          DRAFT
                                    Emco WhMton, Inc

                                   EECO Syium S»rtt*
                                   (0.2 gph Quick Ttit)

                           AUTOMATIC TANK GAUGING SYSTEM

Certification:      Leak rate of 0.2 gallon per hour with P0 - 95.4% & P,A - 4.6%.

Leak Threshold:   0.10 galton p«r hour (a teak li declared if the output of tha measurement system
                 exceeds this threshold).

Applicability:      Gasoline, diasel, aviation fual, fuel oil *4 & 6, solvents, waste oil, and other
                 substances determined to be compatible with probe.

Capacity:         The maximum tank capacity is  15,000 oallons.
                 The tank must be at least 50% full.

Wailing Time:     Minimum waiting time between delivery to the tank and test  data collection must
                 be at least 1 hour and can range up to 6 hours depending upon tank conditions.

Test Period:       Minimum data collection time must be at least 53 minutes.
                 Test data is acquired and recorded by a microprocessor.
                 Microprocessor automatically determines test time based on tank size and product
                 level.
                 Leak rate is calculated from data determined to be valid by statistical analysis.
                 There  must be no dispensing or product delivery during the test.

Temperature:      A minimum of 5 Resistance Temperature Detectors must be used to determine the
                 average temperature  of the stored hazardous substance.

Water Sensor:     A water sensor must be used to detect water incursion.
                 Minimum water level detectable in the tank is 0.66 inches.
                 Minimum detectable change in  water level that can be detected is 0.039 inches.
Calibration:       Temperature sensors  and probe must  be  annually checked  and calibrated in
                 accordance with manufacturer's instructions.

Comments:       This equipment was not evaluated using manifolded tanks.
                 This equipment only tests the portion of the tank that contains  product.
                 As the product level is lowered the leak rate in a leaking tank  decreases (due to
                 lower head pressure).
                 A magnetostrictive probe measures changes in product volume.

                                                      Evsluator: Ksn WHcox Associates
Emeo Wheston, Inc
114 MaoKenan Drive
CarY, NC 27511
(800)342-8125
                                                      Date of Evaluation: 12-23-93
                                           35
                                   Emco Whutoo, Inc.

                              EECO System TLM MomhJy T«»t
DRAFT
                           AUTOMATIC TANK GAUGING SYSTEM

Certfflctflon:      Leak rate of 0.2 gallon per hour with P0 - 99.1 % & P,A « 0.9%.

Uak Threshold:   0.10 gallon per hour (a leak Is declared if the output of the measurement system
                 exceed* this threshold).

AppHcabl'rty:      Gasoline, diesel, aviation  fuel, fuel oil #4, solvents and waste  oil.   Contact
                 manufacturer for other applications.

Capacity:         The maximum tank capacity Is  16,000 gallons.
                 The certification tests were conducted on a tank which was 50% and 95% full.

Waiting Time:     Minimum waiting time between delivery to the tank and test data collection must
                 be 6 hours.

Tast Period:      The minimum data collection time is 1.9 hours.
                 The data is acquired and recorded by a microprocessor.
                 Microprocessor automatically determines test time based on tank size and product
                 level.
                 Leak rate is calculated from data determined to be valid by statistical analysis.
                 There must be no dispensing or product delivery during the test.

Temperature:      A minimum of 5 Resistance Temperature Detectors must be used to  determine the
                 average temperature  of the stored substance.

Water Sensor:     A water sensor must be used to detect water incursion.
                 Minimum water level detectable in the tank is 0.66 inches.
                 Minimum detectable change in water level is 0.039 inches.

Calibration:       Temperature sensors and probes must be checked and calibrated annually in
                 accordance with manufacturer's instructions.

Comments:       This equipment was not evaluated using manifolded tanks.
                 This equipment tests only that portion of the tank which contains product.
                 As the product level is lowered, the leak rate in a leaking tank decreases (due to
                 lower head pressure).
Emco Wheaton, Inc.
114 MacKonan Drive
C«ry. NC  27511
Tel: (800)342-6125
                                                                                                                                                                   Eveluetor: Ken Wilcox Associates
                                                                                                                                                                   Date of Evaluation:  12-23-93
                                                                                                                                                        36

-------
                                    Emco Wheaton. Inc.

                           EECO System TLM Monthly Quick Te»t
                                                                             DRAFT
                           AUTOMATIC TANK GAUGING SYSTEM

Certification:      Leak rate of 0.2 gallon per hour with PD = 95.4% & PFA = 4.6%.

Leak Threshold:   0.10 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:      Gasoline, diesel, aviation fuel, fuel oil #4, solvents and waste oil.  Contact
                 manufacturer for other applications.

Capacity:         The maximum tank capacity is 15,000 gallons.
                 The certification tests were conducted on a  tank which was 50% and 95% full.

Waiting Time:     Minimum waiting time between delivery to the tank  and test data collection is
                 variable and ranges between 1 and 6 hours.

Test Period:      The minimum data collection time is 53 minutes.
                 The data is acquired and recorded by a microprocessor.
                 Microprocessor automatically determines test time based on tank size and product
                 level.
                 Leak rate is calculated from data determined to be valid by statistical analysis.
                 There must be no dispensing or product delivery during the test.

Temperature:     A minimum of 5 Resistance Temperature Detectors must be used to determine the
                 average temperature of the stored substance.

Watar Sensor:    A water sensor must be used to detect water incursion.
                 Minimum water level detectable in the tank  is 0.66  inches.
                 Minimum detectable change in water level is 0.039  inches.

Calibration:       Temperature sensors and probes must be checked and calibrated annually in
                 accordance with manufacturer's instructions.

Comments:       This equipment was not evaluated  using manifolded tanks.
                 This equipment tests only that portion of the tank which contains product.
                 As the product level is lowered, the leak rate in a leaking tank decreases (due to
                 lower head pressure).
 Emco Wtoaton. Inc.
 114 MacKanan Drive
 Catv, NC  27511
 Tel: <800> 342-6125
                                                        Evaluator:  Kan Wilcox Aeaociatea
Data of Evaluation:  12-23-S3
                                            37
                                                                                        Emco Wheaton, Inc.

                                                                                  EECO System TLM Quick Precision
                                                                                                                             DRAFT
                                                                               AUTOMATIC TANK GAUGING SYSTEM

                                                     Certification:      Leak rate of 0.1 gallon per hour with PD = 96% & PFA =  1 %.

                                                     Leak Threshold:   0.05 gallon  per hour (a leak is declared if the output of the measurement system
                                                                      exceeds this threshold).

                                                     Applicability:      Gasoline,  diesel,  aviation fuel,  fuel oil  #4,  solvents and waste  oil. Contact
                                                                      manufacturer for other applications.

                                                     Capacity:         The maximum tank capacity it 15,000 gallons.
                                                                      The certification tests were conducted on a tank which was 50% and 95% full.

                                                     Waiting Time:     Minimum waiting  time between delivery to the tank and test data collection must
                                                                      be 6 hours.

                                                     Test Period:      The minimum data collection time is 3.75 hours.
                                                                      The data is acquired and recorded by a microprocessor.
                                                                      Microprocessor automatically determines test time based on tank size and product
                                                                      level.
                                                                      Leak rate is calculated from data determined to be valid by statistical analysis.
                                                                      There must be no dispensing or product delivery during the test.

                                                     Temperature:     A minimum of 5 Resistance Temperature Detectors must be used to determine the
                                                                      average temperature of the stored substance.

                                                     Water Senior:    A water sensor must be used to detect water incursion.
                                                                      Minimum water level detectable in the tank is 0.66  inches.
                                                                      Minimum detectable change in water level is 0.039 inches.

                                                     Calibration:       Temperature sensors and probes must be checked and calibrated annually in
                                                                      accordance with manufacturer's instructions.

                                                     Comments:       This equipment was not evaluated using manifolded tanks.
                                                                      This equipment tests only that portion of the tank which  contains product.
                                                                      As the product level is lowered, the leak rate in a leaking tank decreases (due to
                                                                      lower head  pressure).
                                                                                                             Emco Wheaton, Inc.
                                                                                                             114 MacKanan Drive
                                                                                                             Cory, NC  27511
                                                                                                             Tel: (800)342-8125
                                                                                                        Evaluator: Midweat Reaaarch Inttitule


                                                                                                        Due of Evaluation: 02-08-94
                                                                                                                                                        38

-------
                                    Emco Wheaton, Inc

                               EECO Sytttm TUM Quick Tot
                                                                          DRAFT
                           AUTOMATIC TANK GAUGING SYSTEM

Certification:      Leak rate of 0.1 gallon per hour with P0 = 96% & PFA = 4%.

Leak Threshold:   0.05 gallon per hour (a leak is declared if the output of the measurement system
                 exceed* this threshold).

App!iceb3rty:      Gasoline,  diesel,  aviation fuel,  fuel  oil #4,  solvents, waste  oil.   Contact
                 manufacturer for other applications.

Capacity:         The maximum tank capacity is  15,000 gallons.
                 The tests were conducted at on a tank which was 50% and 95% full.

Waiting Time:     Minimum waiting time between delivery to the tank and test data collection must
                 be 6 hours.

Test Period:      The minimum data collection time is 1.7 hours.
                 The data is acquired and recorded by a microprocessor.
                 Microprocessor automatically determines test time based on tank size and product
                 level.
                 Leak rate is calculated from data determined to be valid by statistical analysis.
                 There must be no dispensing or product delivery during the test.

Temperature:      A minimum of 5 Resistance Temperature Detectors must be used to determine the
                 average temperature  of the stored substance.

Water Sensor:     A water sensor must be used to detect water incursion.
                 Minimum water level detectable in the tank is 0.66 inches.
                 MiriirRurn dstoctsbls change in  water levs! is 0.03S inches.

Calibration:       Temperature sensors and probes must be checked and calibrated annually in
                 accordance with manufacturer's instructions.

Comments:       This equipment was not evaluated qsing manifolded tanks.
                 This equipment tests only that  portion of the tank which contains product
                 As the product level is lowered, the leak rate in a leaking tank decreases (due to
                 lower head pressure).
Emco WhMton, loo.
114MocK«nanDrivi
CMV, NC  27S11
T4: (000)3-42-6125
Eviluitor: Midwiit RiiMrch Inititult


Dili of Ev.lu.tion: 02-15-94
                                           39
                                                                                          Emco WhMton, Inc

                                                                                EECO System LLD - Hourly Monitoring Test
                                                                                                                              DRAFT
                                                                            AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

                                                       Certification:          Leak rate of 3.0 gallon per hour with P0 = 100% & PfA = 0%.

                                                       Leak Threshold:       2.0  gallon  per hour (a leak is declared if the  output of the measurement
                                                                            system exceeds this threshold).

                                                       Apollcsbiiitv:          Gasoline, diesel, aviation fuel, and fuel oil #4.  Contact manufacturer for other
                                                                            applications.

                                                       Specification:          System is installed on pressurized fiberglass and steel piping.
                                                                            The  piping system volume must not exceed 67.4 gallons.
                                                                            Tests are conducted at 10 psi pressure.

                                                                            System may be installed on flexible pipeline systems.
                                                                            The  Flex line system volume must not exceed 49.6 gallons.
                                                                            Tests  are conducted at an average pressure of  10 psi.

                                                       Test Period:           Data collection time for the test is at least 2 hours.
                                                                            Test data acquired and recorded by microprocessor.
                                                                            Calculations are automatically done with the microprocessor.

                                                       System Features:      This system is permanently installed on the piping and automatically tests the
                                                                            line.
                                                                            It uses a preset threshold and a single test to determine whether the piping is
                                                                            leaking.
                                                                            If a leak is declared the system shuts down the dispensing system, displays
                                                                            and  prints a message, and triggers an alarm.

                                                       Calibration:           Equipment  must  be checked and calibrated annually  in accordance with
                                                                            manufacturer's instructions.
Emco Whuton, Ino
114 MicK«n.n Dtiv>
Ciry.NC 27511
(8001 342-8125
Evaluator: Kan WHcox AtiodaUi
                                                                                                                                                                   Oiti of Evaluation: 7/11/84

-------
                                                                             DRAFT
                                     Emco Whuton, Inc

                         EECO System UO - Monthly Monitoring Test


                       AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

 Certification:          Leak rate of 0.2 gallon per hour with P0- 100% & P« - 0%.

 Leak Threshold:       0.1293 gallon per hour  (a leak is declared if the output of the measurement
                      system exceeds this threshold).

 Applicablity:          Gasoline, diesel, aviation fuel, and fuel oil #4.  Contact manufacturer for other
                      applications.

 Specification:         System is installed on pressurized fiberglass and steel piping.
                      The piping system volume must not exceed 67.4 gallons.
                      Tests are conducted at 10 psi pressure.

                      System may be insiniiod on fioxibie pipeline systems.  The Hex line system
                      volume must not exceed 49.6 gallons. Tests are conducted at an average
                      pressure of 10 psi.

 Test Period:           Data collection time for the  test is at least 9 minutes.
                      Test data acquired and recorded by microprocessor.
                      Calculations are automatically done with the microprocessor.

 System Features:      This system is permanently installed on the piping and automatically tests the
                      line.
                      It uses a preset threshold and a single test to determine whether the piping is
                      leaking.
                      If a leak is declared the system shuts down the dispensing system, displays
                      and prints a message,  and triggers an alarm.

 Calibration:            Equipment  must be checked  and calibrated annually in accordance with
                      manufacturer's instructions.
                                                     Certification:

                                                     Leak Threshold:


                                                     Applicability:


                                                     Specification:
                                                     T«st Period:
                                                     System Features:
                                                                                                                           DRAFT
                                      Emco Whaaton. Inc

                             EECO System LLD - Line Tightness Test


                       AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

                       Leak rate of 0.1 gallon per hour with P0 - 100% & Pw - 0%

                       0.0793 gallon per hour (a leak is declared if the output of the measurement
                       system exceeds this threshold).


                                                               C°ntaCt manufa«ur«f for o«h^
                                                                          System is installed on pressurized fiberglass and steel piping.
                                                                          The piping system volume must not exceed 67.4 gallons.
                                                                          Tests are conducted at 10 psi pressure.

                                                                          Systems may be installed on flexible pipeline systems. The flex line system

                                                                                                                                 at an av«rafl«
                                                    Calibration:
                      Data collection time for the test is at least 31 minutes.
                      Test data acquired and recorded by microprocessor.
                      Calculations are automatically done with the microprocessor.

                      This system is permanently installed on the piping and automatically tests the
                      iino>
                      Ituses a preset threshold and a single test to determine whether the piping is

                      If a leak is declared the system shuts down the dispensing system, displays
                      and prmts a message, and triggers an alarm.

                      Equipment must be checked and calibrated annually in accordance with
                      manufacturer's instructions.
Emco WhMton, Inc
114 M«K«n«n Drive
Gary, NC27B11
(800) 342-8126
Evakiator: Kan Wiloox Anoci*t«, Inc.


DIM of Evaluation: 7/18/84
Emco Whaaton, Ino
114M*cKananDriva
Cary, NC 27511
(BOO) 342-6125
                                                                                                                                                                 Evakiator: Kan Wiloox Anooiataa


                                                                                                                                                                 Data of Evaluation: 7/18/94
                                           41
                                                                                                                                                     42

-------

                                 Engineered System*. Inc.

                                         Imaged
                                                                            DRAFT
                           AUTOMATIC TANK GAUGING SYSTEM

Certification:          Leak rate of 0.2 gallon per hour with PD = 96.6% & PM = 3.4%.

Leak Threshold:       0.1 gallon per hour (a teak is declared  if the  output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, and solvents.

Capacity:             The maximum tank capacity is 15,000 gallons.
                     The tank must be at least 90% full.

Waiting Time:        Minimum waiting time between  product delivery to the tank and test data
                     collection must be 8 hours.

Test Period:          The  minimum data  collection time must be 6 hours.
                     Test data must be acquired and recorded by a computer.
                     Leak rate is calculated from average of subsets of all collected data.
                     There must be no dispensing or product delivery during the test.

Temperature:         Minimum of 5 Resistance Temperature Detectors must be used to determine
                     the average temperature of the stored hazardous product.

Water Sensor:        A water sensor must be used to monitor changes in water level in tank during
                     test.
                     Minimum water level detectable  in the tank is 0.83 inches.
                     Minimum detectable water level  change is 0.0116 inches.

 Caiibratkni:          Temperature sensors and probe must be checked and calibrated annually in
                     accordance with manufacturer's instructions.

 Comments:          This equipment was not evaluated using manifolded tanks.
                      This equipment only tests the portion of the tank that contains product.
                      As the product level is lowered the leak rate in a leaking tank decreases (due
                      to lower head pressure).
                      This system  is identical to Universal Sensor's TICS-1000 ATGS.
                                                  Certification:


                                                  Uak Threshold:

                                                  Applicability:

                                                  Tank Capacity:

                                                  Data Requirement:

                                                  Comments:
                    Entropy Limited

   Precision Tank Inventory Control System. Version 90
                     (qualitative)

STATISTICAL INVENTORY RECONCILIATION TEST METHOD

   Method is certified to detect a 0.10 gph  leak rate with a PD=97.9% and
   PFA=0%.

   A leak is declared when teak rate exceeds 0.04 gallons per hour.

   Gasoline, diesel, aviation fuel, fuel oil #4.

   Maximum tank capacity may not exceed 30,000 gallons.

   Minimum 64 days of product level and flowthrough data.

   Of 120 data sets submitted for analysis, 13 were not evaluated and 16 were
   inconclusive.

    The median throughput for tanks used in this evaluation was 42,835 gallons
    per month.

    This evaluation did not include data from manifolded tanks.

    Data sets used in this evaluation were supplied  by the evaluator.
  Engitwtitd Svttwni Inc.
  2001 Wait CmfU* Drivi
  Tompg. AZ 15282
  Til: (502) 431-1362
Ev«lu»tor:  Ken Wilcox Aitod«tei, Inc.


Dili at EvJuilion: 00-20-83
                                                                                                            Entropy Limited
                                                                                                            South Gra»t Rd.
                                                                                                            Lincoln, MA 01773
                                                                                                            Tel: (S17) 25S-89O1
                                                                                                  Ev«kiitor: Mdwut Re»iroh InttftuM


                                                                                                  DM* of Eviluitfon: 04/02/91
                                             43
                                                                                                                                                       44


-------
                                                                         DRAFT
                                      Entropy Limited

                       Precision Tank Inventory Control System Rev. 90
                                       (quantitative)

                  STATISTICAL INVENTORY RECONCILIATION TEST METHOD

Certification:          Method is certified to  detect a 0.1  gph leak rate  with  PD = 99.5% and
                     P,A-<0.5%.

Liak Threshold:       A leak is declared when leak rate exceeds 0.05 gallon per hour.

Applicability:          Gasoline, diesel, aviation fuel, fuel oil *4.

Tank Capacity:        Maximum single tank capacity shall not exceed 21,000 gallons.  Maximum
                     total capacity  for tanks in a manifolded system shall not exceed  60,000
                     gallons.

Data Requirement:     Minimum of  30 days of product level and flow through data.

Comments:           32% of the  data  sets used in this evaluation were from manifolded tanks.
                     89% of the manifolded tanks had manually stuck data.

                     A maximum  of three tanks were included in the manifolded systems used in
                     this evaluation. The largest single tank capacity was 20,000 gallons.

                     Of the 56 data sets presented for evaluation, 6 were not analyzed due to
                     unusable data.  There were no inconclusives.

                     The median  monthly throughput of tanks used in this evaluation was 52,207
                     gallons.

                     Leak rates ranging from 0.0497 to 0.2003 were used in the evaluation.

                     Data sets used in this evaluation were supplied by the evaluator.
                                                                                          Environment and Safety

                                                                                              EASI Level-Tru
                                                                                                                              DRAFT
                                                        Certification:

                                                        Leak Threshold:


                                                        Applicability:


                                                        Capacity:


                                                        Waiting Time:


                                                        Test Period:





                                                        Temperature:


                                                        Water Sensor:



                                                        Calibration:


                                                        Comments:
                            AUTOMATIC TANK GAUGING SYSTEM

                      Leak rate of 0.2 gallon per hour with P0-95.4% & PFA=4.6%.

                      0.1  gallon  per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

                      Gasoline, diesel, aviation fuel, fuel oil #4, antifreeze, brake fluid, transmission
                      fluid, and solvents.

                      The maximum tank capacity is 15,000 gallons.
                      The tank must be at least 50% full.

                      Minimum waiting  time between  product delivery to the tank and test data
                      collection must be 4.1  hours.

                      The minimum data collection time must be 3.6 hours.
                      Test data must be acquired and recorded by a computer.
                      Leak rate is calculated from data collected over the entire range of the test
                      period.
                      There must be no  dispensing or product delivery during the test.

                      A minimum of 5 resistance temperature detectors must be used to determine
                      the average temperature  of the stored substance.

                      A water sensor must be used to detect water incursion.
                      Minimum water level detectable in the tank is 0.896 inches.
                      Minimum detectable change in  water level is 0.023 inches.

                      Temperature sensors and probe must be checked and calibrated annually in
                      accordance with manufacturer's instructions.

                      This equipment was not evaluated using manifolded tanks.
                     This equipment only tests the portion of the tank that contains product.
                      As the product level is lowered the leak rate in a leaking tank decreases (due
                     to lower head pressure).
                      System is currently undergoing 3rd party certification for 0.1 gph leak rate.
Entropy limitad
South Great Rd.
Lincoln. MA 01773
Tel: (617) 256-8901
Evakiator: Simpaon, Gumpartz & Hagar, Inc.


Date of Evaluation:  11/30/83
Environment and Safety, Ino.
2075 OToola Avenue
SanJoia. CA95131
Tel: (408) 954-9081
Evaluator: Midwott Research IrntituU
                                                                                                                                                            Data of Evaluation: 04-11-91
                                            45
                                                                                                                                                 46

-------
                                                                         nra A r-r
                              ErsvironrrMT.t-! Fas! Systems. Ins.

                                        Futl Finder
                                        Version IV

                     VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
Output type:          quantitative
Sampling frequency:   intermittent
Operating principle:    adsorption sampling
Test Results:

Accuracy (%) [Avg. Reading]:
Bias (%)
Precision (%)
Detection Time (min:sec):
Fall Time (min:sec):
Lower Detection Limit (ppm):
Specificity Results:

    Benzene
    n-Butane
    n-Hexane
    Isobutane
    2-Methylpentane
    Toluene
_2L_
147.7
90.7
55.7
51.1
143.7
66.5
Manufacturer's Specifications:
Comments:
         Benzene          2-Methvlbutane
         106.8 11647 ppm]     122.7 11380 ppm]
         64.5                 38.2
         22.3                 53.2
         Not App.              Not App.
         Not App.              Not App.
         77                   116
                                       Msnsgtmsfit Tschr.cJojiss

                                  SIRTECH (quantitative)


                 STATISTICAL INVENTORY RECONCILIATION TEST METHOD

Certification:          Method is certified to detect a 0.1 gph leak rate with a PD=99% and
                     P,A-1%.

Leak Threshold:       A leak is declared when leak rate exceeds 0.05 gph.

AppllcabiKy:          Gasoline, dieset, aviation fuel, and fuel oil #4.

Tank Capacity:        Maximum tank capacity shall not exceed 18,000 gallons.

Data Requirement:     Minimum 30 days of usable product level and flow through data are
                     required.

Comments:           Of the 41 data sets presented for evaluation, 5 were inconclusive.

                     The median monthly throughput for tanks used in this evaluation was
                     14,600 gallons.

                     Leak rates of 0.05, 0.1, and 0.2 gph were used in this evaluation.

                     Data Sets used in this evaluation were supplied by the vendor.

                     This evaluation did not include data from manifolded tanks.
                                                                                                            Envtroramntil Mwuocnwnt TnhnologiH
                                                                                                            20001 Gl«n Echo Rd.
                                                                                                            N«thviH«.TN 37215
                                                                                                            (SIB) 386-5503
                                                                                                                                     Evdtutor: Nithm Adtcra. MWdli TO Strtt Univ.


                                                                                                                                     Out of Eviluidon: 11-OE-»2
Environment*! Fuel System*, Inc.
P.O. Box 1*1*
B«nd«l«, TX 71003
Til: (100) 376-7747
                                  EvWuitor: C*n»fl!> KMon RnMrch Inidtutt


                                  D«t« of EvAntlon: 04-20-S3
                                            47
                                                                                                                                                       48

-------
                              EnviroQuest Technologiei Limited

                   Envko THe SIR (also known as SIRAS 99.6) (quantitative)
                                                                          DRAFT
                                                                             EnviroQuest Technologies Limited

                                                                     SIRAS Software System, Version 2.0 (quantitative)
                                                                                                                       DRAFT
                 STATISTICAL INVENTORY RECONCILIATION TEST METHOD

Certification:          Method  is certified to detect a 0.1 gph  leak rate with a PD = 99.6% and
                     PM=0.4%.

Leak Threshold:       A leak is declared when leak rate exceeds 0.05 gph.

Applicability:          Gasoline, diesel, aviation fuel, and fuel oil  #4.

Tank Capacity:        Maximum UST capacity shall not exceed 18,000 gallons.

Data Requirement:     Minimum of 31 days to make an SIR evaluation with at least 95% confidence
                     at the rate of 0.1  gph,  and vendor recommends 45 to 60 days for greater
                     confidence.

Comments:           Of the 41  data sets presented for evaluation, 5 were not analyzed due to
                     unusable data.

                     The median monthly throughput for tanks used in this evaluation was 16,700
                     gallons.

                     Leak rates ranging from 0.0500 to 0.2043 were used in the evaluation.

                     Data Sets used in this evaluation were supplied by the evaluator.

                     This evaluation did not include data from manifolded tanks.
                                                                 STATISTICAL INVENTORY RECONCILIATION TEST METHOD

                                                Certification:         Version 2.0 is designed to meet annual tests requirements.  Method certified
                                                                    to detect a 0.1 gph leak rate with a PD = 99.3% and PFA = 0.7%

                                                Leak Threshold:       A leak is declared when the calculated leak rate exceed the threshold of 0.05
                                                                    gph.

                                                Applicability:         Gasoline, diesel, aviation fuel, and fuel oil #4.

                                                Tank Capacity:        Maximum single tank capacity shall not 30,000 gallons.  Maximum total
                                                                    capacity  for tanks in a manifolded system shall not exceed 60,000 gallons.
                                                 *
                                                Data Requirement:    Minimum 30 days of usable product level and flowthrough data are required.

                                                Comments:           27% of the data sets  used in this  evaluation were from manifolded tanks.

                                                                    A maximum of 4 tanks were included in the manifolded systems used in the
                                                                    evaluation. The largest individual tank in this evaluation was 30,000 gallons.
                                                                    Of the 56 data sets presented for evaluation 6 were not analyzed due to
                                                                    unusable  data.
                                                                    The median monthly throughput for tanks used in this evaluation was 73,518
                                                                    gallons.
                                                                    Leak rates ranging from 0.0458 to 0.2500 gph were used in the evaluation.
                                                                    Data sets used in this evaluation were supplied by the evaluator.
                                                                    Over 50% of the data from large manifolded tanks was collected by automatic
                                                                    tank gauges.
                                                                                                      EnviroQudBt T.chnolooi«s Umit«d
                                                                                                      4501 Madiaon
                                                                                                      Kaniaa City, MO 84111
                                                                                                      Tel: (816) 758-0774
                                                                                                                                                            Evaluator: Midwaat Raaaarch Inatituta
                                                                                                                                                            Date of Evaluation: 08-23-93
EnviroQuMt Tachnologiaa limited
4501 M«di«on
Kaniaa City, MO 84111
Tel: (800) 75B-O774
Evaluator: Midwaat Raaaarch ln«titut«


Data of Evaluation: 04-O3-92
                                           49
                                                                                                                                                50

-------
                             EnviroGuest Tschnoios-ss Limited

                    SIRAS Software System. Version 2.8.3 (quantitative)
                                                                         PRAFl
                 STATISTICAL INVENTORY RECONCILIATION TEST METHOD

Certification:          Version 2.8.3 is designed to meet monthly monitoring requirements.
                     Method certified to detect a 0.2 gph leak rate with a PD = 99.999% and
                     PFA = 0.01 %.

Leak Threshold:       A leak is declared when the calculated leak rate exceeds the threshold of
                     0.10 gph.

AppiicabSrty:          GsscKns, diosGl, aviation fuel, and fuel ci! #4.

Tank Capacity:        Maximum single tank capacity shall not exceed 30,000 gallons.  Maximum
                     total capacity for tanks in a manifolded system shall not exceed 60,000
                     gallons.

Data Requirement:     Minimum 30 days of usable product level and flowthrough data are
                     required.

Comments:           27% of the data sets used in this evaluation were from manifolded tanks.

                     A maximum of 4 tanks were included in the manifolded systems used in the
                     evaluation.  The largest individual tank in this evaluation was 30,000
                     gallons.
                     Of the 56 data sets presented for evaluation 6 were not analyzed due to
                     unusable data.
                     The median monthly throughput for tanks used in this evaluation was
                     73,518 gallons.
                     Leak rates ranging from 0.0458 to 0.2500 gph were used in the evaluation.
                     Data sets used in this evaluation were supplied by the evaluator.
                     Over 50% of the data from large manifolded tanks was collected by
                     automatic tank gauges.
 EnviroQuest Techndofltei Limited
 45O1 Madieon
 Kensal City. MO 84111
 Tel: (818) 758-0774
                                                       Evaluator:  Midwest Reiaarch Institute
Data of Evaluation: 08-23-93
                                            51
                                                                                   FC! EnvircnmSRts!, Inc.

                                                                             Analog Hydrocarbon Probe AHP-100
                                                                                                                      UKAFT
                                                                      LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                  Detector:
                                                      Output type:
                                                      Sampling frequency:
                                                      Operating principle:

                                                 Test Results:
                                                     Accuracy (%)
                                                     Detection time (min)
                                                     Fall Time (min)
                                                     Lower detection limit (cm)

                                                 Specificity Results:
qualitative
continuous
fiber optic chemical sensor
    Commercial
    Gasoline
    100
    <8
    <5
    <0.01
Synthetic
Gasoline
100
<8
<5
<0.01
                                                     Activated:    commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, synthetic
                                                                  gasoline, xylene(s).

                                                 Manufacturer's Specifications:


                                                 Comments:

                                                     EPA and many states require detection of 1/8 inch of product which is 0.32 cm. The
                                                     detector is reusable.
                                                                                                        FCI Environmental, Inc.
                                                                                                        1181 Grior Drive, Bldg. B
                                                                                                        L«i Vegut, NV89119
                                                                                                        Tel: (800) 510-3827
                                                                                                       Evaluator: Ken Wilcox Associates


                                                                                                       Data of Evaluation: 01-15-94
                                                                                                                                                  52

-------
                                   FCI Environmental, Inc.

                             Digital Hydrocarbon Probe DHP-100


                     LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
Output type: qualitative
Sampling frequency: continuous
Operating principle: fiber optic chemical sensor
:, Results:
Accuracy(%)
Detection time (min)
Fall Time (min)
Lower detection limit (cm)
Commercial
Gasoline
100
<8
<5
<0.01
Synthetic
Gasoline
100
<8
<5
<0.01
Specificity Results:

    Activated:    commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, synthetic
                 gasoline, xylene(s).

Manufacturer's Specifications:
Comments:

    EPA and many states require detection of 1 /8 inch of product, which is 0.32 cm. The
    detector is reusable.
FCI Environmental, Inc.
1181 Grier Drive, Hdg. B
La> Veoae, NV89119
Tel: (800) 510-3627
Evaluator: Kan Wilcox Aaaociatea


Date of Evaluation: 01-15-94
                                            53
                                   FCI Environmental, Inc.

                             Analog Hydrocarbon Probe AHP-100
                                                                                                                                                                                    DRAFT
                                                                                                                                VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                                           Detector:
                                                                                                           Output type:           quantitative
                                                                                                           Sampling frequency:    continuous
                                                                                                           Operating principle:     fiber optic
                                                                                                                                        EPA March 1990 protocol
                                                                                                                                                                       Radian June 1990 protocol
Test Results:

Gasoline
Relative Accuracy* (%):
Bias (%):
Precision (%):
Detection Time (min):
Fall Time (mini:
Lower Detect. Limit (ppm):  84

• Relative accuracy ia a function of eyatematio error, or biaa, and random arror, or preciaion. Smaller veluaa indicate better
accuracy.
• • No Reaponaa

Specificity Results (%)  (corrected for sensitivity differences):
Xvlene
2
1.
1
<1
<1
84
Benzene
35
-23
11
<1
<1
519
2-Methvlbutana
NR"
NR
NR
NR
NR
NR
Unl. Gasoline
12
-7
4
<1
<1
137
Svnth.
22
-2
15
<•)
,-1
220
                                                                                                           EPA March 1990 protocol
                                                                                                                                             Radian June 1990 protocol
Benzene
Toluene
p-Xylene
Synthetic Gasoline
Trimethylbenzene
Methane
Butane
2-Methylbutane
Pentane
76
96
101
100
107
NR
NR
NR
NR
Unleaded Gasoline
Synthetic Gasoline
JP-4 Jet Fuel
n-Hexane
Xylene




93
98
105
NR
103




Manufacturer's Specifications:

Comments:

The test procedures used were taken from EPA's "Standard Test Procedures for Evaluation Leak
Detection Methods: Vapor-Phase Out-of-Tank Product Detectors/ March 1990, and Radian
Corporation's draft report "Development of Procedures to Assess the Performance of External Leak
Detection Devices: Vapor-Phase ASTM-Formatted Methods," June 6, 1990.
                                                                                                           FCI Environmental, Inc.
                                                                                                           1181 Grier Drive, Hdg. B
                                                                                                           LaaVagaa, NV89119
                                                                                                           Tal: (800) 510-3827
                                                       Evaluator: Ken Wilcox Aaaociatea
                                                                                                                                                                  Data of Evaluation: 03-07-94
                                                                                                                                                      54

-------
QR ACT
FC! E.-.vkKirRsr.i-!. few.
Digital Hydrocarbon Probe DHP-100
VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
Output type: quantitative
Sampling frequency: continuous
Operating principle: fiber optic

Tot ft-Tin- PPA Marrh 1 990 protocol Rsdisn June 1 990 protocol
Xvlena Benzene 2-Methvlbutane U, nl. Gasoline SyntHi
Gasoline .. „ ,„
Relative Accuracy' (%): 0 17 NR 18 29
Bias(%): 0 -9 NR 1 -•*
Precision (%): 0 11 NR 9 10
Detection Time (min): <1 <1 NR <1 
-------
                                       FE Petro. Inc.

                              STP-MLD-D Pipeline Leak Detector
                                                                          DRAFT
                            MECHANICAL UNE LEAK DETECTOR

Certification:      Leak rate of 3.0 gallons per hour with PD = 100% & PFA = 0%;

L«ak Threshold:   2.0 gallons per hour (a leak is declared if the output of the measurement system
                 exceods this threshold).

Applicability:      Diesel.

Specification:     System is installed on steel and fiberglass (rigid) lines.
                 The piping system (rigid) volume must not exceed 341 gallons.
                 Tests are conducted at the line operating pressure.

Waiting Time:     No waiting time between last delivery of the product to the tank and the start of
                 uSia CGnSCtiGii.
                 No waiting time between last dispensing of product through the pipeline and the
                 start of data collection for the test.

Test Period:      Average data collection time is 1 minute.

System Features:  This system is permanently installed on the piping and automatically tests the
                 line.
                 It uses a preset threshold and a single test to determine whether the piping is
                 leaking.
                 If a leak is detected, this system restricts fuel flow to dispenser.
Calibration:
                 Equipment must be checked annually for capability of detecting a leak of 3.0
                 gallons per hour.
FE P«tro. Inc.
P.O. Box 138
McFwlMld, Wl 63SS8
Tel: (MS) S3S-S7S6
Evakutor: Km Wttoox Anociit*


DM* of Evriuition: 04-30-94
                                            57
                                                                                                               FE Petro, Inc.

                                                                                                   STP-MLD-E Line (Flexible) Leak Detector
                                                                                                                                                DRAFT
                                                                        Certification:

                                                                        Leak Threshold:


                                                                        Applicability:

                                                                        Specification:



                                                                        Waiting Time:




                                                                        Test Period:

                                                                        System Features:
                                                                        Calibration:


                                                                        Comments:
           MECHANICAL LINE LEAK DETECTOR

 Leak rate of 3.0 gallons per hour with PD = 100% & PfA = 0%;

 2.0 gallons per hour (a leak is declared if the output of the measurement system
 exceeds this threshold).

 Gasoline, diesel, aviation fuel, and some solvents.

 System is installed on flexible line.
 The  piping system volume must not exceed 49.6 gallons.
 Tests are conducted at the line operating pressure.

 No waiting time between  last delivery of the product to the tank and the start of
 data collection.
 No waiting time between  last dispensing of product through the pipeline and the
 start of data collection for the test.

 Average data collection time is 3 minutes.

 This  system is permanently instalted on the piping and automatically tests the
 line.
 It uses a preset threshold  and a single test to determine whether the piping is
 leaking.
 If a leak is detected, this system restricts fuel flow to dispenser.

 Equipment must be checked annually for capability of detecting a leak of 3.0
gallons per hour.

Enviroflex line with a bulk modulus of 1,280 was used during the third-party
evaluation.
                                                                                                          FE Patro, Inc.
                                                                                                          P.O. Box 139
                                                                                                          McFart.nd, Wl 53SS8
                                                                                                          Tel: (608) 838-8786
                                                                                                         Evifaitor: K*n WUcox Anoditt


                                                                                                         D«t« of Evduition: 03-24-94
                                                                                                                                                     58

-------
                                    Qssbsy internstivRsi

                                     GasboyTMSBOO
                           AUTOMATIC TANK GAUGING SYSTEM

Certification:          Leak rate of 0.2 gallon per hour with PD = 99.91 % & PfA  = 0.09%.

Leak Threshold:       0.1 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, and solvents.

Capacity:             The maximum tank capacity is 15,000 gallons.
                     The tank must be between 50 and 95% full.

Waiting Time:        Minimum waiting time between product delivery to the tank and test data
                     collection must be 6 hours.

Test Period:          The minimum data collection time must be 3 hours.
                     Test data must be acquired and recorded  by a computer.
                     There must be no dispensing or product delivery during the test.

Temperature:         A minimum of five temperature sensors must be used to determine the
                     average temperature of the stored substance.

Water Sensor:        A water sensor must  be used to detect water incursion.
                      Minimum water level  detectable in the tank is 1.04 inches.
                      Minimum change in water level that can be detected is 0.011 inches.

Calibration:          Temperature sensors  and probes must be checked and calibrated annually in
                                            accordance with manufacturer's instructions.

Comments:          This equipment was net evaluated using manifolded tanks.
                      This equipment only tests that portion of the tank which contains product.
                      As the product level is lowered, the leak rate in a leaking tank decreases
                      (due to lower head pressure).
                      This system is no longer being manufactured although product support is
                      still available.
                      Gasboy International  was formerly called William M. Wilson's Sons.
 Gatboy International
 P.O. Box 308
 Unidale, PA 19448
 Tel: (215)855-4831
Evaluator: Kan Wilcox Aeeoclate*


Data of Evaluation: 05-10-91
                                             59
                                                                                                                                                                                   HDAPT
                                                                                                                                                                                       '
                                                                                 GSbnrco Environmental Products

                                                               EMC Environmental Management Console, EMC Basic Monitoring System
                                                               Tank Monitor 2. 3. 2.1, and 3.1, PA0238000XXXX Capacitance Probe

                                                                              AUTOMATIC TANK GAUGING SYSTEM

                                                  Certification:          Leak rate of 0.2 gallon per hour with P0=99% & PfA=1%.

                                                  Leak Threshold:       0.1 gallon per hour (a leak is declared if the output of the measurement
                                                                        system exceeds this threshold).

                                                  Applicability:          Gasoline, diesel, aviation fuel, and solvents.

                                                  Capacity:             The maximum tank capacity is 15,000 gallons.
                                                                        The tank must be between 50 and 95% full.

                                                  Waiting Time:         Minimum waiting time between delivery to the tank and test data collection
                                                                        must be 8.3 hours.

                                                  Test Period:           The minimum data  collection time must be 5 hours.
                                                                        Test data must be acquired and recorded by a microprocessor  within the
                                                                        monitoring console.
                                                                        Leak rate is calculated from converting the level signals from the probe
                                                                        during the test period to temperature-compensated volume change.
                                                                        There must be no dispensing or product delivery during the test.

                                                  Temperature:         A temperature averaging probe (thermistor) must be used to determine the
                                                                        average temperature of the stored hazardous substance.

                                                  Water Sensor:         A water sensor must be used to detect water incursion.
                                                                        Minimum water level detectable in the  tank is 1.40 inches.
                                                                        Minimum detectable water level change is 0.040 inches.

                                                  Calibration:           The in-tank probe with temperature and water sensor is self-calibrating but
                                                                        occasional system checks may be required in accordance with
                                                                        manufacturer's instructions.

                                                  Comments:           This equipment was not evaluated using manifolded tanks.
                                                                        This equipment only tests the portion of the tank that contains product.
                                                                        As the product level is lowered the  leak rate in a leaking  tank  decreases
                                                                        (due to lower head pressure).
                                                                                                            Gil'barco Environmental Product*
                                                                                                            7300 W. Friindly Avenue
                                                                                                            Groemboro, NC 27420
                                                                                                            Tal: (910) 547-5000
                                                                                                                                                                   Evaluator: Midwaet Riinrch Initituta
                                                                                                                                                                   DiU of Evaluation: 05-14-93
                                                                                                                                                        60

-------
                               Gilbarco Environmental Product*
                                                                             DRAFT
             EMC Environmental Management Console, EMC Basic Monitoring System
                  Tank Monitor 2.1. 3.1. PA0264XXXOOOO Capacitance Probe

                            AUTOMATIC TANK GAUGING SYSTEM

 Certification:          Leak rate of 0.2 gallon per hour with P0 = 99% & PFA=0.2%.

 Leak Threshold:       0.126 gallon per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

 Applicability:          Gasoline, diesel, aviation fuel, and solvents.

 Capacity:             The maximum tank capacity is 15,000 gallons.
                      The tank must be between 50 and 95% full.

 Waiting Time:         Minimum waiting time between delivery to the tank and test data collection
                      must bs 8,3 hours.          	                                   	

 Test Period:           The minimum data collection time must be 2 hours.
                      Test data must be acquired and recorded by a microprocessor within the
                      monitoring console.
                      Leak rate is calculated from converting the level signals from the probe
                      during the test period to temperature-compensated volume change.  '
                      There must be no dispensing or product delivery during the test.

 Temperature:          A minimum of 5 thermistors must be used to determine the average
                      temperature of the stored hazardous substance.

 Water Sensor:         A water sensor must be used to detect water incursion.
                      Minimum water level detectable in the tank is 1.52 inches.
                      Minimum change in water level that can be detected is 0.027 inches.

 Calibration:            The in-tank probe with temperature and water sensors is  self-calibrating but
                      occasional checks may be required in accordance with manufacturer's
                      instructions.

 Comments:            This equipment was not evaluated using manifolded tanks.
                      This equipment only tests the  portion of the tank that contains product.
                      As the product level is lowered the leak rate in a leaking tank decreases
                      (due to lower head pressure).
Gilbarco Environmental Products
730O W. Friendly Avenue
Greensboro, NC  27420
Tel: (910) S47-5OOO
Evaluator: Midwest Research Institute
                                                       Date of Evaluation: 05-14-93
                                            61
                                                                                                                               DRAFT
                                                                                                                                           Gilbarco Environmental Products
                                                                  EMC Environmental Management Console, EMC Basic Monitoring System
                                                                       Tank Monitor 2.1, 3.1, PA0264XXXOOOO Capacitance Probe

                                                                                AUTOMATIC TANK GAUGING SYSTEM

                                                      Certification:          Leak rate of 0.1 gallon per hour with P0 = 99% & PFA=0.1 %.

                                                      Leak Threshold:       0.071 gallon per hour (a leak is declared if the output of the measurement
                                                                           system exceeds this threshold).

                                                      Applicability:          Gasoline, diesel, aviation fuel, and solvents.

                                                      Capacity:             The maximum tank capacity is 15,000 gallons.
                                                                           The tank must be at least 95% full.

                                                      Waiting Time:         Minimum waiting time between delivery to the tank and test data collection
                                                                           must be 8.25 hours.

                                                      Test Period:           The minimum data collection time must be 3 hours.
                                                                           Test data must be acquired and recorded by a microprocessor within the
                                                                           monitoring console.
                                                                           Leak rate is calculated from converting the level signals from the probe
                                                                           during the test period to temperature-compensated volume change.
                                                                           There must be no dispensing or product delivery during the test.

                                                      Temperature:          A minimum of 5 thermistors must be used to determine the average
                                                                           temperature of the stored substance.

                                                      Water Sensor:         A water sensor must be used to detect water incursion.
                                                                           Minimum water level detectable in the tank is 1.52 inches.
                                                                           Minimum detectable water level change is 0.027 inches.

                                                      Calibration:           The in-tank probe with temperature and water sensor is self-calibrating but
                                                                           occasional checks may be required in accordance with manufacturer's
                                                                           instructions.

                                                      Comments:           This equipment was not evaluated using manifolded tanks.
                                                                           This equipment only tests the  portion of the tank that contains product.
                                                                           As the product level is lowered the leak rate in a leaking tank decreases
                                                                           (due to lower head pressure).
                                                                                                             Gilbarco Environmantal Product*
                                                                                                             7300 W. Friendly Avenue
                                                                                                             Greeneboro, NC 27420
                                                                                                             Tel: (910) 547-5OOO
                                                                                                        Evafuator:     Midwest Research Institute


                                                                                                        Data of Evaluation: 05-14-93
                                                                                                                                                        62

-------
Certification:

Leak Threshold:


Applicability:

Capacity:


Waiting Time:


Test Period:
                              GBbarco Environmental Products

            EMC Environmental Management Console. EMC Baste Monitoring System
               Tank Monitor 2.1. 3.1, PA0265XXXOOOO Magnetostrictlve Probe

                           AUTOMATIC TANK GAUGING SYSTEM

                     Leak rate of 0.2 gallon per hour with P0=99% & PFA=0-1 *•
 Temperature:


 Water Sensor.



 Calibration:



 Comments:
0.093 gallon per hour (a leak is declared if the output of the measurement
system exceeds this threshold).

Gasoline, diesel, aviation fuel, and solvents.

The maximum tank capacity is 15.000 gallons.
The tank must be between 50 and 95% full.

Minimum waiting time between delivery to the tank and test data collection
must be 8.3 hours.

The minimum data collection time must be 2 hours.
Test data must be acquired and recorded by a microprocessor within the
monitoring console.
Leak rate is calculated from converting the level signals from the probe
during the test period to temperature-compensated volume change.
There must be no dispensing or product delivery during the test.

A minimum of 5 thermistors are used to determine the average temperature
of the stored hazardous substance.

A water sensor must be used to detect water incursion.
 Minimum water level detectable in the tank is 0.544 inches.
 Minimum change in water level that can be detected is 0.027 inches.

 The in-tank probe with temperature and water sensor is self-calibrating but
 occasional checks may be required in accordance with  manufacturer's
 instructions.

 This equipment was not evaluated using manifolded tanks.
 This equipment only tests the portion of the tank that contains product.
 As the product level is lowered the leak rate in a leaking tank decreases
 (due to lower head pressure).
  Gilbmco Environmental Produota
  7300 W. Friendly Av*nu»
  Greeneboto. NC 27420
  T*l: I»10) 647-SOOO
                                    Evakiaton Mdwait Reeearoh Inatitute


                                    Data of Evaluation: 05-14-93
                                              63
                              GSbsrcs Environments! Products

            EMC Environmental Management Console. EMC Baste Monitoring System
               Tank Monitor 2.1.3.1. PAO265XXXOOOO Magnetostrtetive Probe

                           AUTOMATIC TANK GAUGING SYSTEM

Certification:          Leakrate of 0.1 gallon per hour with P0=> 99% &PFA-1%.

Leak Threshold:       0.069 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:  .        Gasoline, diesel, aviation fuel, and solvents.

Capacity:             The maximum tank capacity is  15,000 gallons.
                     The tank must be at least 95% full.

Waiting Time:        Minimum waiting time between product delivery to the tank and test data
                     collection must be 8.25 hours.

Test Period:          The minimum data collection time must  be 3 hours.
                     Test data must be acquired and recorded by a microprocessor within the
                     monitoring console.
                     Leak rate is calculated from converting the level signals from the probe
                     during the test period to temperature-compensated volume change.
                     There must be no dispensing or product delivery during the test.

Temperature:         A minimum of 5 thermistors are used to determine the average temperature
                     of the stored substance.

Water Sensor:        A water sensor must be used to detect water incursion.
                      Minimum water level detectable in the tank is 0.544 inches.
                      Minimum change in water level that can be detected is 0.027 inches.

Calibration:          The in-tank probe with temperature and water sensor is self-calibrating but
                      occasional checks may be required in accordance with manufacturer's
                      instructions.

 Comments:           This equipment was not evaluated using manifolded tanks.
                      This equipment only tests the portion of the tank that contains product.
                      As the product level is lowered the leak rate in a leaking tank decreases
                      (due to lower head pressure).
                                                                                                              GUbaroo Envfronmantal Product!
                                                                                                              7300 W. Friendly Avanua
                                                                                                              Gre»n»boro, NC  27420
                                                                                                              Tel: (910) 547-5000
                                                                                                                                                             E valuator:
                                                                                                                                                                         Midwut Reaaarch Inititme
                                                                                                                                       0>t> of Evaluation: 05-14-93
                                                                                                                                                          64

-------
                               GHbarco Environmental Product*

                          Environmental Management Console (EMC)
                         Groundwater Senior, aeries PA02700XX0001

                      LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                             DRAFT
 Detector:
     Output type:          qualitative
     Sampling frequency:    continuous
     Operating principle:    electrical conductivity
Test RaiuKs:
                          Commercial
                          Gasoline
    Accuracy(%)              100
    Detection time(min:sec)     08:55
    Fall Time (min:sec)         54:50
    Lower detection
    limit(cm)                  0.02
Specificity Results:
Synthetic
 Gasoline
   100
   06:18
   26:02

   0.02
    Activated:    commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, synthetic
                 gasoline, xylene(s).
Calibration:       Sensor must be checked annually for operability or in accordance with
                 manufacturer's instructions and calibrated/replaced if necessary.

Comments:       EPA and many states require detection of 1/8 inch of product, which is 0.32
                 cm. This detector is reusable.
                                                                                                                                                                                      DRAFT
                                                            Detector:

                                                                Output type:
                                                                Sampling frequency:
                                                                Operating principle:

                                                           Test Results*:
Accuracy (%)
Response time (min)

Product activation
    height (cm)
                                                                                         GHbarco Environmental Products


                                                                                               PA02590XXXOOO

                                                                                     LIQUID-PHASE INTERSTITIAL DETECTOR
                              qualitative
                              continuous
                              float switch
                                                                                                                                        Commercial  Commercial
                             100
                             3.66
                              1.28
                                           100
                                           3.45
                                          1.27
                                          1.65
    Lower Detection Limit (cm) 1.84

    * at a flow rate of 0.19 gal/hr in 7.6 cm diameter test chamber

Specificity Results:

    Activated:   diesel fuel, synthetic fuel, home heating oil #2, water

Manufacturer's Specifications:
                                                           Comments:   Evaluation performed on equivalent Veeder-Root detector. EPA and many states
                                                                       require detection of 1/8 inch of product, which is 0.32 cm, for ground water
                                                                       monitoring  The test procedures used were those in Carnegie Mellon Research
                                                                       SSL?   f* P™edures for ""^ Partv Evaluation of Leak Detection Methods:
                                                                       Point Sensor Uqu.d Contact Leak Detection Systems': Final Report - November 11
I
Gilbireo Environnwntal Product!
7300 W. Friendly Ave.,
Greonaboro. NO 27420
(910) 547-5000
       Ev«lu«tor: Carnegie Motion Reaoarch Inatituta


       DIM of Evaluation: 11-2O-91
                                                                                                          *• evaluated for Veeder-Root TLS-250, TLS 250i Plus, ILS 250
                                                                                                            * evaluated for Veeder-Root ILS 350, TLS-350
Gilbirco Environmental Product*
7300 W. Friandly Ava.
Grooniboro, NC 27420
Tel: (910) 547-5000
                                                     Evaluator: Carnagia Mallcn Raaaarch Inetitute


                                                     Data of Evaluation: 07-17-92
                                           65
                                                                                                                                                    66

-------
                               Gibtrco Environments! Products
Detector:

    Output type:
    Sampling frequency:
    Operating principle:

Test Results:
     Accuracy (%)
     Response time (min)
     Recovery time (min)
     Product activation
         height (cm)
                                     PA02691144000

                           LIQUID-PHASE INTERSTITIAL DETECTOR
qualitative
continuous
float switch
                              Commercial  Commercial
                              Gasoline*    Gasoline."
                              100
6.00
 3.67
             100
             6.51
     Lower Detection Limit (cm)  4.05
3.62
4.17
 Specificity Results:

     Activated:    diesel fuel, synthetic fuel, home heating oil #2, water

 Manufacturer's Specifications:
 Comments:   Evaluation psrformsd on equivalent Veeder-Root detector.  EPA and many states
              require detection of 1/8 inch of product, which is 0.32 cm, for ground water
              monitoring.  The test procedures used were those in Carnegie Mellon Research
              Institute's 'Test Procedures for Third Party Evaluation of Leak Detection Methods:
              Point Sensor Liquid Contact Leak Detection Systems': Final Report - November 11,
              1991.

  •   evaluated for Veeder-Root TLS-250, TLS 250i Plus, ILS 250, at a flow rate of 0.13 gal/hr in

  ••  tvalSanted'foratVe^er-Root'lLSr 350, TLS-350, at a flow rate of 0.12 gal/hr in 4.8 cm diameter
      test chamber
  Gilborco Envtronmentel Product!
  7300 W. Friendly Ave.
  Greeneboro, NO 27420
  T«l: 1810) S47-SCOO
                            Evaluitor: Carnerfe Mellon Research Intdtuu


                            Date of Evaluation: 07-17-92
                                               67
                                                                                                                                              Gifaarco Environment: Products
                                                                    Detector:

                                                                        Output type:
                                                                        Sampling frequency:
                                                                        Operating principle:

                                                                    Test Results:
                                                                        Accuracy (%)
                                                                        Response time (min)
                                                                        Recovery time (min)
                                                                        Product activation
                                                                             height (cm)
                                                                                                                      PA02592000000

                                                                                                           LIQUID-PHASE INTERSTITIAL DETECTOR
qualitative
continuous
float switch
                                                                                                               Commercial  Commercial
                                                                                                               Gasoline'     Gasoline"
                                                                                                                            100
100
8.19
                                                                                                               4.12
                                                                                                                    Lower Detection Limit (cm)  4.67
             8.49
             3.95
             4.36
                                                                                  Specificity Results:

                                                                                      Activated:    diesel fuel, synthetic fuel, home heating oil #2, water

                                                                                  Manufacturer's Specifications:
                                                                                  Comments:   Evaluation performed on equivalent Veeder-Root detector. EPA and many states
                                                                                               require detection of 1/8 inch of product, which is 0.32 cm, for ground watsr
                                                                                               monitoring. The test procedures used were those in Carnegie Mellon Research
                                                                                               Institute's "Test Procedures for Third Party Evaluation of Leak Detection Methods:
                                                                                               Point Sensor Liquid Contact Leak Detection Systems": Final Report - November 11,
                                                                                               1991.

                                                                                  •   evaluated for Veeder-Root TLS-250, TLS 250i Plus, ILS 250, at a flow rate of 0.15 gal/hr in
                                                                                      5.8 cm diameter test chamber
                                                                                  •• evaluated for Veeder-Root ILS 350, TLS-350, at a flow rate of 0.14 gal/hr in 5.8 cm diameter
                                                                                      test chamber
                                                                                   Gilbitco Environment*! Product!
                                                                                   7300 W. Friendly Ave.
                                                                                   GnenabofO, NC 27420
                                                                                   Tel: (910) 547-5000
                                                                                                                             Evaluitor: Carmgie Mellon Research Inidtute


                                                                                                                             Date of Evaluation: 07-17-92
                                                                                                                                                             68

-------
                               GHbtrco Environment*! Products
                                                                           DRAFT
Detector:
                                     PA02660000000

                     VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
Output type:          qualitative
Sampling frequency:   continuous
Operating principle:    adsistor
Test Results:
Accuracy (%):
Detection Time (min:sec):
Fail Time (min:sec):
Lower Detection  Limit
    (ppm):
Commercial
Gasoline
100
7:46
2:38
Synthetic
Gasoline
0
Not App.
NotApp.
JP4
100
17:01
3:05
500
                 >1000
                                  500
Specificity Results (%):

    Activated:    Commercial gasoline, JP-4 jet fuel
    No response: n-Hexane, Synthetic gasoline. Toluene, Xylene(s)

Manufacturer's Specifications:
Comments:   Evaluation performed on equivalent Veeder-Root detector. The test procedures used
             were those in Radian Corporation's draft report "Development of Procedures to
             Assess the Performance of External Leak Detection Devices: Vapor-Phase ASTM-
             Formatted Methods,' June 29, 1990.
Gilbarco Environmental Producte
7300 W. Friendly Ava.
Greenaboro. NC 27420
Tel: (910) 547-5OOO
                             Evaluator: Carnegie Mellon Reaearch Inatituta
                                                       Date of Evaluation: 07-24-92
                                            69
                                                                                                                                                        DRAFT
                              Gilbarco Environmental Products

                          Environmental Management Console (EMC)
                       with Line Leak Detector. Series PA02630000501

                             ELECTRONIC LINE LEAK DETECTOR

Certification:      Leak rate of 3.0 gallon per hour with P0 = 100% & PFA=0%.

Leak Threshold:   1.5 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:      Gasoline, diesel, aviation fuel, and solvent.

Specification:     System is installed on pressurized fiberglass and steel piping.
                 The piping system volume must not exceed 41 gallons.
                 Tests are conducted at the line operating pressure.

                 System is installed on pressurized flexible piping. The piping yojume must not
                 exceed 158.4 gallons. Tests are  conducted at the line pressure.  The
                 mechanical line leak detector must be removed from the pipeline.

Waiting Time:     There is no waiting time between product delivery of the product to the tank
                 and the start of data collection.
                 Minimum waiting  period between last dispensing and testing depends on volume
                 of product and temperature gradient which is determined by the system's
                 computer.

Test Period:      The minimum data collection time (response time) for  the test must be 12
                 minutes.
                 Test data must ba acquired and recorded by a microprocessor.
                 Calculations are automatically done by the microprocessor.

Calibration:       Sensor must be checked and calibrated annually in accordance with
                 manufacturer's instructions.

System Features:  This system is permanently installed on the piping and automatically tests the
                 line.
                 It uses a preset threshold and a single test to determine whether the piping is
                 leaking.
                 If a leak is declared, this system displays a message, triggers an alarm, and
                 shuts down the dispensing system.
                                                                                    GHbarco Environmental Products
                                                                                    7300 W. Friendly Ava.,
                                                                                    Greenaboro, NC 27420
                                                                                    (910) B47-5OOO
                                                  Evaluator: Kon Wilcox Aaaocista*, Inc.


                                                  Date of Evaluation: 4/12/93
                                                                                                                                                         70

-------
Certification:
                               Gibareo Environment* rrooucts

                          Environmental Management Console (EMC)
                        with Line Leak Detector. Series PA02630000501

                             ELECTRONIC LINE LEAK DETECTOR

                 Leak rate of 0.2 gallon per hour with P0=100% & PFA=0%.
Leak Threshold:   0.10 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:     Gasoline,  diesel, aviation fuel, and solvent.

Specification:     System is installed on pressurized fiberglass and steel piping.
                 The piping system volume must not exceed 41 gallons.
                 Tests are conducted at the line operating pressure.

                 System is installed on pressurized flexible piping.  The piping volume must not
                 exceed 158.4 gallons. Tests are conducted at the line pressure. The
                 mechanical line leak detector must be removed from the pipeline.

Waiting Time:    There is no waiting time between product delivery of the product to the tank
                 and the start of data collection.
                  Minimum waiting period between last dispensing and testing depends on volume
                 of product and temperature gradient which is determined by the system's
                  computer.

Test Period:     The minimum data collection time (response time) for the test must be 0.75 to
                  8.85 hours.
                  Test data must be acquired and recorded by a microprocessor.
                  Calculations are automatically done by the microprocessor.

 Calibration:       Sensor must be  checked and calibrated annually in accordance with
                  manufacturer's instructions.

 System Features: This system is permanently-installed on the piping and automatically tests the
                  line.
                  It uses a preset  threshold and a single test to determine whether the piping is
                  leaking.
                  If a leak  is declared, this system displays a message, triggers an alarm, and
                  shuts down the dispensing system.
 GilbKco Env»ronrr»nt«l Product!
 7300 W. Fritndly Av..,
 G»«uboro, NC 27420
 (910) 647-5000
                                                     Ev«lu«tor: K«n Wilcox AnocltMi, Inn.
Dili of Evaluation: 4/1243
                                              71
                                                                                        G8bsrce Er.vi.-cnrr.sr.ts! Products

                                                                                   Environmental Management Console (EMC)
                                                                                with Line Leak Detector. Series PA02630000501

                                                                                AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

                                                         Certification:      Leak rate of 0.1 gallon per hour with P0 = 100.0% & PFA=0%.

                                                         Leak Threshold:   0.079 gallon per hour (a leak is declared  if the output of the measurement
                                                                          system exceeds this threshold).

                                                         Applicability:      Gasoline, diesel, aviation fuel, and solvent.

                                                         Specification:     System is installed on pressurized fiberglass and steel piping.
                                                                          The piping system volume must not exceed 41 gallons.
                                                                          Tests are conducted at the line operating pressure.
                                                                          System is installed on pressurized flexible piping. The piping volume must not
                                                                          exceed 158.4 gallons.  Tests are conducted at the line  pressure. The
                                                                          mechanical line leak detector must be removed from the pipeline.

                                                         Waiting Time:     There is no waiting time between product delivery and testing.
                                                                          Minimum waiting  period between last dispensing and testing depends on volume
                                                                          of product and temperature gradient which is determined by the system's
                                                                          computer.

                                                         Test Period:      Minimum data collection time must be 1.2 to 12.9 hours.
                                                                          Test data must be acquired and recorded by a microprocessor.
                                                                          Calculations are automatically done by the microprocessor.

                                                         Calibration:       Sensor must be checked and calibrated annually in accordance with
                                                                          manufacturer's instructions.

                                                         System Features: This system is permanently installed on the piping and automatically tests the
                                                                          line.
                                                                          It uses a preset threshold and a single test to determine whether the piping is
                                                                          leaking.
                                                                          If a leak is  declared, this system displays a message, triggers an alarm, and
                                                                          shuts down the dispensing system.
                                                                                                               Gllbarco Environmental Product*
                                                                                                               7300 W. Friindly Ave.
                                                                                                               Greoniboro, NC 27420
                                                                                                               (910) 547-5000
                                                                                                                                                                       Eviluitor: K«n Wilcox Anocl«t««, Inc.
                                                                                                                                                                       D«t« of Evaluation: 08-04-83
                                                                                                                                                           72

-------
                                         Hasstech

                       Leak Computer Tank Test System (Overfilled Tost)
                                                                             DRAFT
                                                                                                      Hantech

                                                                                   Leak Computer Tank Test System (Underfilled Test)
                                                                                                                                       DRAFT
           VOLUMETRIC TANK TIGHTNESS TEST METHOD (EDISON LAB PROTOCOL)

Certification:      Leak rate of 0.1 gallon per hour with PD=95% & PFA = 5.0%.

Leak Threshold:   0.05 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:      Gasoline, diesel, aviation fuel, fuel oil #4, fuel oil #6, solvents, waste oil, and
                 other liquids compatible with the probes.

Capacity:        The maximum tank capacity is 12,000 gallons.
                 The tank must be at least 100% full.

Waiting Time:     The test data must be acquired and recorded by a computer that calculates a
                 leak rate every minute, and determines waiting time for satisfactory data (the
                 test is finished when the standard deviation  of 30 sequential leak rates is less
                 than half of the last leak rate determined).
                 There must be no dispensing or product delivery during the test  waiting time.

Test Period:      The minimum data collection time must be 70 minutes.
                 Leak rate is calculated from data determined to be valid by statistical analysis.

Temperature:     A minimum of 7 temperature sensors (thermistors) must be used to determine
                 the average temperature of the stored product.

Ground Water:    If the groundwater level is not determined, the tank must pass a two level test
                 with at least a 3 foot difference in product level. If the groundwater level can
                 be determined, a single level test can be conducted provided a net pressure
                 difference of at least 1 psi exists between the groundwater and  product at the
                 bottom of the tank.

Calibration:       Level sensor must be calibrated before each test.
                 Temperature sensors must be calibrated annually.

Comments:       This  equipment was evaluated at the EPA Edison Risk Reduction Engineering
                 Laboratory prior to the standard protocols being written.
                 This equipment was not evaluated using manifolded tanks.
  Certification:

  Leak Threshold:


  Applicability:


  Capacity:


  Waiting Time:





 Test Period:


 Temperature:


 Ground Water:



 Calibration:


 Comments:
                                                                                    VOLUMETRIC TANK TIGHTNESS TEST METHOD

                                                                              Leak rate of 0.1 gallon per hour with P0>99% &PfA
-------
                                         Hasstech

                                          AcuRlte
Certification:

Leak Threshold:


Applicability:

Specification:
 Wahkig Time:


 Test Period:



 Calibration:
             LINE TIGHTNESS TEST METHOD

Leak rate of 0.1 gallon per hour with P0=100% & PfA=0*>-

0.01 gallon per hour (a leak is declared if the output of the measurement system
exceeds this threshold).

Gasoline, diessl, aviation fuel, and fuel oil#4.

System tests fiberglass and steel piping.
The piping system volume must not exceed 75 gallons.
Tests are conducted at 150% of the line operating pressure.
The mechanical line leak detector must be removed from the piping system
being tested.

Minimum waiting period between product delivery and testing is 6 hours.
Minimum waiting period between last dispensing and testing is 30 minutes.

The minimum data collection time must be 30 minutes.
Test data must be acquired and recorded manually.
 Manual calculations are performed by the tester on site.

 Equipment must be checked annually and calibrated if necessary in accordance
 with manufacturer's instructions.
  HMlUCh
  698S Flindtrl Or.
  S.nDi.go, CA  92121
  T«I:"«I19) 457-SB80
                                         Evsluitor: Lamir Unlvorjity


                                         Diu of Eviluition: 03/25/91
                                               75
                                                                                                                                      Kassteeh

                                                                                                                             UnsThs Pipeline Leek Monitor
                                                                                                                                                                                        PKAFT
                                                                                                              Certification:
                      AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

                 Leak rate of 3.0 gallon per hour with PD = 100% & PFA=0%.
Leak Threshold:   2.00 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:     Gasoline, diesel, and aviation fuel.

Specification:     System can be installed on pressurized fiberglass, steel, and flexible piping.
                 The rigid piping system volume must not exceed 341 gallons.
                 The flexible piping system volume must not exceed 49.6 gallons.
                 Tests are conducted at the line operating pressure.

Waiting Time:     There is no waiting period between product delivery and testing.
                 There is no waiting period between last dispensing and testing.

Test Period:      Minimum data collection time (response time) is 1 minute.
                 Minimum data collection time is 1 minute; this is a single test consisting of
                 multiple cycles of data acquisition with 1-24 minutes waiting time between each
                 cycle.
                 Test data must be acquired and recorded by a permanently installed
                 microprocessor.
                 Calculations are automatically done by tha microprocessor.

System Features: This system is permanently installed on the pipeline and automatically tests the
                 line.
                 Uses a  preset threshold and a single test to determine whether the pipeline is
                 leaking.
                 If a leak is declared, this system displays a message, triggers an alarm, and
                 shuts down the dispensing system.
                                                                                                              Calibration:
                                                                                                              Equipment must be checked annually and calibrated if necessary in accordance
                                                                                                              with manufacturer's instructions.
Htnuch
09S5 Randtri Drive
SwDilflo, CA 92121
Tri: (819) 457-5880
Evduitor: K»n Wiloox Atioditii


D«t« of Evaluation: 10-15-91 & 04-10-94
                                                                                                                                                           76

-------
                                         Hasstech

                                LineTrt. Pipeline Leak Monitor
                                                                         DRAFT
                                     Heath Consultants

                                Petro Comp (Overfilled Test)
                                                                            DRAFT
                      AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification:      Leak rate of 0.1 gallon per hour with PD-100% & PFA-0%.

Leak Threshold:   0.062 gallon per hour (a leak is declared if the output of the measurement
                 system exceeds this threshold).

Applicability:      Gasoline, diesel, and aviation fuel.

Specification:     System is installed on pressurized fiberglass, steel, and flexible pipelines.
                 The rigid piping system volume must not exceed 341 gallons.
                 The flexible piping system volume must not exceed 49.6 gallons.
                 Tests are conducted at the line operating pressure.

Waiting Time:     There is no waiting time between product  delivery and testing.          _
                 There is no waiting time between last dispensing and testing.

Test Period:      Minimum data collection time (response time) is 50 minutes.
                 This is a single test consisting of multiple cycles of data acquisition with 30
                 minutes waiting time between each cycle.
                 Test data is acquired and recorded by a permanently installed microprocessor;
                 calculations automatically done by the microprocessor.

Syitem Features: This system is permanently installed on the pipeline and automatically tests the
                 line.
                 Uses a preset threshold and a single test to determine whether the pipeline is
                 leaking.
                 If a leak is declared, this system displays a message, triggers an alarm, and
                 shuts down the dispensing system.

Calibration:       Equipment must be checked  annually and calibrated  if necessary in accordance
                 with manufacturer's instructions.
                       VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD = 99% & PfA=0.98%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, solvents, alcohols and water.

Capacity:             The maximum tank capacity is 15,000 gallons.
                     The'tank must be 100% full.
                     An automatic product leveler must be used to maintain a constant product
                     level during the test.

Waiting Time:.        There is no minimum waiting time between product delivery and test data
                     collection.
                     The product must be mixed continuously throughout the test.

Test Period:          The minimum data collection time must be 2 hours after the completion of
                     the high level circulation.
                     The test data must be acquired and recorded by a computer after the
                     completion of the high level circulation.
                     There must be no dispensing or product delivery during the test.

Temperature:         A single sensor is used to determine the temperature of the stored product.

Ground Water:        Depth to the water table present in the backfill must be determined, and if
                     it is above the bottom of the tank, product level must be adjusted to
                     provide net pressure of 4 psi on the bottom of the tank.

Calibration:           Temperature sensor is self calibrating.
                     Level sensor must be checked annually and calibrated if necessary in
                     accordance with manufacturer's instructions.
                                                                                                    Comments:
                     This equipment was not evaluated using manifolded tanks.
 Hasatech
 6985 Randara Dr.
 San Diego, CA 92121
 Tel: (819) 457-5880
                                   (valuator: Kan Wilcox Aaaodataa
                                   Data of Evaluation: 10-16-81 li 04-10-94
Haath Consultants Ino.
9030 Monroe Road
Houiton. TX 77061
(713)947-9292
Evaluator: Ken Wilcox Aaaociataa


Data of Evaluation: 12-15-90
                                            77
                                                                                                                                               78

-------
                                                                               DRAFT
                                     HMth Consultants

                                Petro Tit* II (Overttltd Test)
                                                                                      HMth Consultants

                                                                                    Petro THe Lin* Tester
                       VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with P0 = 99% &PFA=1%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil *4.

Capacity:             The maximum tank capacity is 15,000 gallon*.
                     The tank must be 100% full.
                     An automatic product leveler must be used to maintain a constant product
                     level during the test.

Waiting Tbna:         There is no minimum waiting time between product delivery and test data
                     collection.
                     The product must be mixed continuously throughout the test.
                     There must be no dispensing or product delivery during the test waiting
                     time.

Test Period:          The minimum data collection time must be 2 hours; test data is acquired
                     and recorded manually.
                     Leak rate calculated based on cumulative volume change during low level
                     test (generally based on one-hour average volume change).
                     There must be no dispensing or product delivery during the test.

Temperature:         A single DTS-2000 digital sensor is used to determine the temperature of
                     the stored product.

Ground Water:        Depth to the water table present in the backfill must be determined, and if
                     it is above the bottom of the tank, product level must be adjusted to
                     provide net pressure of 4 psi on the bottom of the tank.

Calibration:           Sensors calibration must be checked at each  use and the DTS-2000
                     recertified a  minimum of once every 3 years.

Comments:           This equipment was not evaluated using manifolded tanks.
                                                 Certification:

                                                 Leak Threshold:


                                                 Applicability:

                                                 Specification:
                                                 Waiting Time:


                                                 Test Period:




                                                 Calibration:
                               LINE TIGHTNESS TEST METHOD

                  Leak rate of 0.1 gallon per hour with PD-99.99% & PFA=0.37%.

                  0.01 gallon per hour (a leak is declared if the output of the measurement system
                  exceeds this threshold).

                  Gasoline, diesel, aviation fuel, fuel oil.

                  System tests fiberglass and steel piping.
                  The piping  system volume must not exceed 129 gallons.
                  Tests are conducted at 150% of the line operating pressure.
                  The mechanical line leak detector must be removed from the pipeline system
                  being tested.

                  There is no minimum waiting period between product delivery and testing.
                  There is no minimum waiting period between last dispensing and testing.

                  Minimum data collection time must be 1 hour; a bleedback must be performed
                  and the volume change must be within the allowable bleedback time calculated.

                 Test data is acquired and recorded manually.

                  Equipment  must be calibrated annually in accordance with manufacturer's
                 instructions.
Htath Coiuuhanu Inc.
9030 Monro* Ro«d
Houston, TX770SI
Tri: (713) «47-9292
Evaluttor: Ktn Wilcox Aiiod«t««


D«t« of EvWuitfon: 11-O1-9O
Heath Coniultanti, Inc.
9030 Monies Ro«d
Houiton, Toxai 77081
(713)9479292
Evduitor: Kin Wilcox Atioditu


D«to of Evaluation: 3/11/91
                                            79
                                                                                                                                                   80

-------
                                 Homer Creative Products, hie.

                              Homer EZY-Chek I (Overfilled Test)
                        VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD = 99% & PFA = 1%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil #4, solvents and waste oil,

Capacity:             The maximum tank capacity is 12,000 gallons.
                      The tank must be 100% full.

Waiting Time:         Minimum waiting time between product delivery and test data collection
                      must be 6 hours.
                      Minimum waiting time between "topping off" and test data collection must
                      be 3 hours.
                      Total minimum waiting time is 6 hours.
                      There must be no product delivery during the test waiting time.

Test Period:           Minimum data collection time must be 1.5 hours (30 minute monitor period,
                      60 minute test period); data collection must continue until data meets
                      manufacturer's stop test criteria.
                      Test data must be acquired and recorded by a strip chart recorder.  Leak
                      rate calculated from data of last 1  hour of the test period.
                      There must be no dispensing or product delivery during the test.

Ground Water:         Depth to the water table present in the backfill must be determined, and if
                      it is above the bottom of the tank, product level must ba adjusted to
                      provide 2-4 psi net pressure on the bottom of the tank during the test.
                      Ground water level must be stable prior to and during the test.

Calibration:            Level sensors must be calibrated before each test.
                      Temperature sensor must be calibrated annually.

Comments:            This equipment was not evaluated using manifolded tanks.
Homer Craativa Product!
212 Morton Straat
Bay City. Ml 487O6
Tol: (517) 893-3380
Evaluator: W. A. Kibba i Aaiooiataa


Data of Evaluation: 10-O3-90
                                             81
                                                   Certification:

                                                   Leak Threshold:


                                                   Applicability:

                                                   Capacity:


                                                   Waiting Time:
                                                   Test Period:
                                                   Ground Water:




                                                   Calibration:

                                                   Comments:
                                Homer Creative Products, Inc.

                              Homer EZY-Chek II (Overfilled Test)


                        VOLUMETRIC TANK TIGHTNESS TEST METHOD

                      Leak rate of 0.1 gallon per hour with PD=99.95% & PfA=0.05%.

                      0.05 gallon per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

                      Gasoline, diesel, aviation fuel, fuel oil #4, solvents and waste oil.

                      The maximum tank capacity is 12,000 gallons.
                      The tank must be 100% full.

                      Minimum waiting time between product delivery and test data collection
                      must be 6 hours;  minimum waiting time between "topping off* and test  -
                      data collection must be 3 hours.
                      Total minimum waiting time is 6 hours.
                      There must be no product delivery during the test waiting time.

                      The minimum data collection time must be one hour and forty minutes (33
                      minutes monitor mode and 67 minutes test mode).
                      Leak rate is calculated from data of last 67 minutes of test period.
                      At'the conclusion of the test mode, data must be checked for the
                      manufacturer's stop test criteria, if data does not meet the criteria data
                      collection must continue.
                      Test data must be acquired and recorded by a computer.
                      There must be no dispensing or product delivery during the test.

                      Depth to tha  water tsble present in the backfill must be determined and if it
                      is above the bottom of the tank, product level must be adjusted to  provide
                      2-4 psi  net pressure on the bottom of the tank during the test. Ground
                      water level must be stable prior to and during the test.

                      Load cell must be calibrated  before each use.

                      This equipment was not evaluated using manifolded tanks.
Horner Croativa Producta
212 Morton Street
Bay City. Ml 48706
(517) 893-3380
                                                                                                                                                                   Evaluator: W. A. Kibba & Aiioci.te.
                                                        Evaluation Computed: 09-18-90
                                                                                                                                                       82

-------
                               Homer Creative Product*, inc.

                             Homer EZY-Chek II (Underfiltd Test)
                                                                             UK An
                                                                                                                    Homer Creative Products, inc.

                                                                                                                      EZY 3 (Underfilled Test)
                                                                                                                                                             DRA"
                                                                                   r i
Certification:

Leak Threshold:


Applicability:

Capacity:


WaHing Time:



Test Period:
 Ground Water:
 Calibration:

 Comments:
  VOLUMETRIC TANK TIGHTNESS TEST METHOD

Leak rate of 0.1 gallon per hour with PD=95.79% & PfA=4.21 %.

0.05 gallon per hour (a leak is declared if the output of the measurement
system exceeds this threshold).

Gasoline, diesel, aviation fuel, fuel oil #4, waste oil and solvents.

The maximum tank capacity is 12,000 gallons.
The tank must be between 98 to 100% full.

Minimum waiting time between product delivery and test data collection
must be 8 hours.
There must be no product delivery during the test waiting time.

Minimum data collection time must be one hour and forty minutes (33
minutes monitor mode and 67 minutes test mode).
The test data must be acquired and recorded by a computer.
Leak rate calculated from data of last 67 minutes of test period.
There must be no dispensing or product delivery during the test.
At the conclusion of the test mode, data must be checked for the
manufacturer's stop test criteria. If data does not meet the criteria data
collection must continue.

 Depth to the water table present in the backfill must be determined and if it
is above the  bottom of the tank, product level must be adjusted to provide
 at least 1 psi net pressure on the bottom of the tank during the test.  If this
 can not be accomplished, then the tank can not be tested using this
 method.

 Load cell must be calibrated before each use.

 This equipment was not evaluated using manifolded tanks.
                    NON-VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with P0 = 100% & PfA=0%.

Leak Threshold:       A leak is declared if the pressure decay is greater than 1 inch water column
                     pressure for non-volatile products and 10% of the lower determined
                     pressure for volatile products. A leak is also declared if water incursion is
                     detected.

Applicability:          Gasoline, diesel, aviation fuel, fuel oil #4, fuel oil #6, solvents and waste
                     oil.

Capacity:             The Maximum tank capacity is 12,000 gallons if ground water is not
                     present. Larger tanks may be tested if groundwater is present and a
                     negative pressure of 1.0 to 1.7 psi can be maintained at bottom of tank.
                     The ullage volume must be between 500 and 2500 gallons.

Test Period:          The minimum data collection time must be 2 and 112 hours for gasoline and
                     1 and 1/4 hours for diesel. This data collection time includes the time
                     required to apply vacuum and to saturate the ullage with vapors.
                     Test data is acquired manually and recorded by computer.

Water Sensor:        A water sensor must be used to detect water incursion and must be
                     calibrated for every test. In accordance with manufacturer's procedures,
                     this calibration  may determine the length of the test in presence of
                     groundwater.

Ground Water:        Depth to the water table present in the backfill must be determined, and if
                     it is above the bottom of the tank, test time must be extended to allow
                     sufficient time to detect 0.1 gph incursion of water into the tank.

Vacuum:             The minimum vacuum at the bottom of the tank must be at 0.1 to 1.7 psi
                     below the atmospheric pressure.
 Hoinir Crmtivo Product!
 212 Morton Strut
 Bay City, Ml 48706
 Tel: (617) 893-3380
                                                         Evaluator: W. A. Kibbo & Auoclaui
                                    Date of Evaluation: 08-26-90
                                                                                                           Hornar Creative Producte, Inc.
                                                                                                           212 Morton Street
                                                                                                           Bay City, Michigan 48706
                                                                                                           (517) 893-3300
                                                                                                                                        Evaluator: Ken Wilcox Atioolatee


                                                                                                                                        Date of Evaluation: 08-23-94
                                              83
                                                                                                                                                       84

-------
                                  Homar Creative Products

                             EZY-Chek Manual Line Leak Detector
                                                                            DRAFT
                                                                                    Homer Creative Products

                                                                             EZY-Chek II Automatic Una Leak Detector
                                                                                                                          DRAFT
                              LINE TIGHTNESS TEST METHOD

Certification:      Leak rate of 0.1 gallon per hour with PD = 98.0% & PFA = 1 %.

Leak Threshold:   0.05 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:      Gasoline, diesel, aviation fuel, fuel oil #4, solvents and waste oil.

Specification:     System tests fiberglass and steel piping.
                 The piping system volume must not exceed 129 gallons.
                 Tests are conducted at 150% of the line operation pressure.

Waiting Time:     No waiting time between last delivery of the product to the tank and the start cf
                 data collection.
                 Waiting time between  last dispensing of product through the pipeline system
                 and the start of data collection is zero hours.

Test Period:      The minimum data collection time for the test must be one and half hours.
                 Data must be collected every 15 minutes.
                 Data collection period consists of a monitor mode and  test mode.
                 Data must be collected in the monitor mode until two consecutive records are
                 within 0.01 gallon of each other.
                 Four data points must  be taken in the test mode for a final gallon per hour result.
                 Test data is acquired and recorded manually.
                 Manual calculations performed by the operator on site.

Calibration:       No temperature sensors used.  No calibration required.  Equipment  must be
                 checked annually in accordance with manufacturer's instructions.
                                                  Certification:

                                                  Leak Threshold:


                                                  Applicability:

                                                  Specification:



                                                  Waiting Time:




                                                  Test Period:
                                                                                                         Calibration:
                               LINE TIGHTNESS TEST METHOD

                  Leak rate of 0.1 gallon per hour with P0 = 99.0% & Pw = 1 %.

                  0.05 gallon per hour (a leak is declared if the output of the measurement system
                  exceeds this threshold).

                  Gasoline, diesel, aviation fuel, fuel oil #4, solvents and waste oil.

                  System tests fiberglass and steel piping.
                  The piping system volume must not exceed 129 gallons.
                  Tests are conducted at 150% of the line operating pressure.

                  No waiting time between last delivery of the product to the tank and the start of
                  data collection.
                  Waiting time between last dispensing of product through the pipeline system
                  and the start of data collection is zero hours.

                  The minimum data collection time for the test must be 2 hours.
                  Data  must be collected every 30 seconds.
                  Data collection period consists of a  monitor mode and test mode.
                  Data must be collected in the monitor mode until two consecutive 15-minute
                  records are within 0.01 gallon of each other; An additional 15-minute in the
                  monitor mode is required before start of the test mode.
                  Data must be collected in the test mode for 67 minutes for a final gallon per
                  hour result.
                  Test data is acquired and recorded by a microprocessor.
                  Calculations are automatically done  with a microprocessor.

                  Sensors are calibrated before each test.
Horner Creative Product*
212 Morton Street
Bay City. Ml  48708
Til: (517) 833-3380
Evaluator:  Kan Wilcox Aagociatoa


Data of Evaluation: 07-O9-92
Hornor Creative Producta
212 Morton Straat
Bay City, Ml 48706
Tal: (517) 893-3380
Evaluator: Kan Wilcox Aigoclatea


Data of Ev»lustion:07-13-92
                                            85
                                                                                                                                                    86

-------
                                                                        HP ACT
                                                                        •—•»*—as  B

                                 Homer Creative Product*

                             SIR PRO 1 Version 1.0 (qualitative)


                 STATISTICAL INVENTORY RECONCILIATION TEST METHOD

Certification:          Version 1.0 is designed to meet monthly monitoring requirements.  Method
                     is certified to detect a 0.2 gph leak rate with a P0 = 100% & PFA-=0%.

Leak Threshold:       A teak is declared when leak rate exceeds 0.10 gallons per hour.

ApplicsbBrty:          Gasoline, diesel, aviation fuel, and fuel oil  #4.

Tank Capacity:        Maximum tank capacity may not exceed 18,000 gallons.

Data Requirement:    A minimum of 30 days of product level and flow through data.

Comments:           Of the 120 data sets presented for evaluation, 10 were inconclusive.

                     The median monthly throughput for tanks used in this evaluation was
                     13,640 gallons.

                     This evaluation did not include data from  manifolded tanks.

                     Data sets used in this  evaluation were supplied by the evaluator.

                     A single leak rate of 0.2 gph was used in this evaluation.
 Homar Craativ* Product!
 212MortonStr«t
 Bay City, Michigan 48706
 (517) 893-3390
Ev»luitoi: Pitro Works


Data of Evaluation: 04-07-93
                                             87
                                                                                                                             DRA
                                                                                     rii
                                                    Certification:
                                 Komar Creative Products

                             SIR PRO 1 Version 2.0 (qualitative)


                 STATISTICAL INVENTORY RECONCILIATION TEST METHOD

                     Version 2.0 is designed to meet annual test requirements. Method is
                     certified to detect a 0.1 gph leak rate with a PD = 100% & PFA=0%.
                                                    Leak Threshold:      A leak is declared when the leak rate exceeds 0.05 gph.

                                                    Product Applicability:  Gasoline, diesel, aviation fuel, and fuel oil #4.

                                                    Tank Capacity:       Maximum tank capacity may not exceed 18,000 gallons.

                                                    Data Requirement:    A minimum of 30 days of product level and flow through data.

                                                    Comments:          Of the 120 data sets presented for evaluation, 9 were inconclusive.

                                                                        The median monthly throughput for tanks used in this evaluation was
                                                                        11,828 gallons.

                                                                        This evaluation did not include data from manifolded tanks.

                                                                        Data sets used in this evaluation were supplied by the evaluator.

                                                                        A single leak rate of 0.1 gph was used in this evaluation.
Homar Craativa Product!
212MortonStr.lt
Bay City, Mohlgan 49708
(617) S93-330O
Evaluator: P.tro Woriti


Data of Evaluation: 09-10-83
                                                                                                                                                      88

-------
                                                                            DRAFT
                                      Ibex Industrie*

                            Ibax Precision Tect System (Overfilled)
                       VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with P0=99.5% & PFA=0.5%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil #4, and solvent.

Capacity:             The maximum tank capacity is 18,000 gallons.
                     The tank must be 92% to  100% full.

Waiting Time:         Minimum waiting time between product delivery and test data collection
                     must be 12 hours.
                     Minimum waiting time between "topping off* and test data collection must
                     be 3 hours.
                     There must be no product  delivery during the waiting time.

Test Period:          Test data must be acquired and recorded by a computer.
                     Leak rate calculated from data determined valid by statistical analysis.
                     There must be no dispensing or product delivery during the test.

Temperature:         A minimum of 6 temperature sensors must be used to determine the
                     average temperature of the stored product.

Ground Water:        Depth  to the  water table present in the backfill must be determined, and if
                     it is above the bottom of the tank, product level must be adjusted to
                     provide 2-4 psi net pressure on the bottom of the tank.

Calibration:           Level sensors must  be calibrated before each test.

Comments:           The equipment was not evaluated using manifolded  tanks.
                                                                               IMO Industrie* Inc., Gems Sensors Division

                                                                           Gems Smartwell Portable Monitor model WPM-535
                                                                               with Groundwater Probe model WP-535

                                                                          LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                     Detector:
                                                         Output type:
                                                         Sampling frequency:
                                                         Operating principle:

                                                     Test Results:
                                                        * Accuracy(%)
                                                         Detection time(min:sec)
                                                         Fall Time (min:sec)
                                                         Lower detection limit(cm)
                             qualitative
                             intermittent*
                             conductive polymer
                                  Commercial
                                  Gasoline
                                  100
                                  09:31
                                  55:42
                                  0.04
                                                                                                        Synthetic
100
07:05
17:04
0.08
                                                                      commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, synthetic
                                                                      gasoline, xylene(s).
Specificity Results:

    Activated:


Manufacturer's Specifications:


Comments:

    * Although the sensor is a polymer strip which is mounted in the monitoring well, the monitor
    is a hand held unit which is typically connected to the sensor periodically - hence the
    'intermittent" designation.

    EPA and many states require detection of 1/8 inch of product, which is 0.32 cm. This
    detector is reusable.
tbax Industrial
2014 S. Union Avo., Suits 103
Bakoraffeld, CA 93307
Tel: (805) 836-8910
                                                        Evituator: AppUtd Rtnarch Centor
DM* of Evaluation: 01-18-91
IMO InduitriH Inc.
G«nt Santera Divinon
Cowloa Road
Pl*nvill«, CT 08062-1198
Tal: (203) 747-3000
                                                                                                   Evaluator: Carnagia Mallon Research Inatituta
                                                                                                                                                           Data of (valuation: 04-22-93
                                            89
                                                                                                                                                        90

-------
                                     kiCSR Environments!

                               TS 1000 Magnatostricthre Probe
                            AUTOMATIC TANK GAUGING SYSTEM

 Certification:          Leak rate of 0.2 gallon per hour with P0-99.99% & PM=0.8%.

 Leak Threshold:       0.05 gallon par hour (a leak is declared if the measured slope by the system
                      exceeds this threshold).

 Applicability:          Gasoline, diesel, aviation fuel, and solvents with known coefficients of
                      expansion.

 Capacity:             The maximum tank capacity is 15,000 gallons.
                      The tank must be between 50 and 95% full.

 Waiting Time:         Minimum waiting time between product delivery to the tank and test data
                      collection must be 6 hours.
                      Minimum waiting time between last dispensing and test data collection
                      must be 2 hours.

 Test Period:          The minimum data collection time must be 4 hours.
                      Test data must be acquired and recorded by a computer.
                      Leak rate is calculated from data determined to be valid by statistical
                      analysis.
                      There must be no dispensing or product during the test.

 Temperature:         A minimum of 5 Resistance Temperature Detectors must be used to
                      determine the average temperature of the stored hazardous substance.

 Water Sensor:        A water sensor must be used to detect water incursion.
                      Minimum water level detectable in the tank is 1.04 inches.
                      Minimum detectable water level change is 0.024 inches.

 Calibration:          Temperature sensors and probe must be checked and calibrated annually in
                      accordance with manufacturer's instructions.

' Comments:          This equipment was not evaluated using manifolded tanks.
                      This equipment only tests the portion of the tank that contains product.
                      As the product level is lowered the leak rate in a leaking tank decreases
                      (due to lower head pressure).
                      3rd party certification for 0.1 gph on this equipment is still under review.
  Incon Environmental
  P. 0. Box 838
  SKO. ME 04O72
  T.I: 1100) 872-3455
                                                         Eveluator: K«n Wilcox Aeaooiatee
Out of Evaluation: 8/5/92
                                              91
                                                                                                                                                                               no
                                                                                     Incon Environmental

                                                                               TS 2000 Magnetoitrictiva Probe
                                                                            AUTOMATIC TANK GAUGING SYSTEM

                                                 Certification:          Leak rate of 0.2 gallon per hour with PD-99.9% & PM-0.5%.

                                                 Leak Threshold:       0.058 gallon per hour (a leak is declared if the measured slope by the
                                                                      system exceeds this threshold).

                                                 Applicability:          Gasoline, diesel, aviation fuel, and solvents with known coefficients of
                                                                      expansion.

                                                 Capacity:             The maximum tank capacity is 15,000 gallons.
                                                                      The tank must be between 50 and 95% full.

                                                 Waiting Time:         Minimum waiting time between product delivery to the tank and test data
                                                                      collection must be 6 hours.
                                                                      Minimum waiting time between last dispensing and test data collection
                                                                      must be 2 hours.

                                                 Test Period:           The minimum data collection time must be 6 hours.
                                                                      Test data must be acquired and recorded by a computer.
                                                                      Leak rate is calculated from data determined to be valid by statistical
                                                                      analysis.
                                                                      There must be no dispensing or product delivery during the test.

                                                 Temperature:          A minimum of 5 temperature sensors must be used to determine the
                                                                      average temperature of the hazardous substance.

                                                 Water Sensor:         A water sensor must be used to detect water incursion.
                                                                      Minimum water level detectable in the tank is 1.04 inches.
                                                                      Minimum detectable water level change  is  0.024 inches.

                                                 Calibration:           Temperature sensors and probe must be checked and calibrated annually in
                                                                      accordance with manufacturer's instructions.

                                                 Comments:           This equipment was not evaluated using manifolded tanks.
                                                                      This equipment only tests the portion of the tank that contains product.
                                                                      As the product level is lowered the leak  rate in a leaking tank decreases
                                                                      (due to lower head pressure).
                                                                      3rd party certification for 0.1 gph on this equipment is still under review.
(noon Environmental
P. O. Box 838
Saco, ME 04072
Tel: (800) 872-3455
Evaluitor: Ken Wiloox A»oolitee


Data of Evaluation: 5/10/91
                                                                                                                                                      92

-------
                                       tn-SHu, Inc.

                                 Leak Detection Systems,
                       KW-140 / KW-240 Monitors with Type 1 Sensor

                     LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                        DRAFT
Detector:

Output type:          qualitative
Sampling frequency:   continuous
Operating principle:    product soluble

Test Results:
Accuracy (%)
r\..».»»:_» •¥•:_.> !«:...«A«.l
uroKwllun  I imw \iuix.om,
Fall Time (minisec)
Lower Detection Limit (cm)

Specificrty Results:

Activated:    commercial gasoline, n-Hexane, diesel fuel, Jet-A Jet fuel, toluene, synthetic gasoline,
             xylene(s).

Manufacturer's specifrcetton:
             Type 1  sensor is recommended by manufacturer for detecting liquid and vapor
             gasoline, alcohol-blend fuels, and JP4 in wet or dry monitor wells.


Comments:  EPA and many states require detection 1/8 inch of product, which is 0.32 cm. This
           •  detector is not reusable, and must be replaced after contact with hydrocarbons.
Commercial
Gasoline
100
00:24
Not App.
0.01
Synthetic
Gasoline
100
00:09
Not App.
0.01
 ItvSttu, Inc.
 210 South Third Strati
 Laramia, WY 82070-0920
 Tot: (307) 742-8213
Evaluator: Carnegie Mellon Reaaarch Inatitute


Date of Evaluation: 07-29-91
                                            93
                                                                                           In-Situ, Inc.

                                                                                     Leak Detection Systems,
                                                                          KW-140 / KW-240 Monitors with Type 2 Sensor

                                                                        LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                                                          DRAFT
                                                    Detector:

                                                    Output type:         qualitative
                                                    Sampling frequency:   continuous
                                                    Operating Principle:   product soluble

                                                    Test Results:
                                                                             Commercial      Synthetic
                                                                             Gasoline         Gasoline
                                                    Accuracy (%)                 100             100
                                                    Detection TimA trnirrfiag)        14;39           08:45                - -  -
                                                    Fall Time (min:sec)             Not App.         Not App.
                                                    Lower Detection Limit (cm)      0.01            0.01

                                                    Specificity Results:

                                                    Activated:  .  commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, synthetic gasoline,
                                                                xylene(s).

                                                    Manufacturer's Specifications:
                                                                Type 2 sensor is recommended by manufacturer-for detecting diesel, heating oil (No.
                                                                1 & 2), A2M, JP4, JP5, gasoline, and alcohol blend fuels in wet  monitoring wells
                                                                only.

                                                    Comments:   EPA and many states require detection of 1/6 inch of product, which is 0.32 cm.
                                                                This detector  is not reusable, and must be replaced after contact with hydrocarbons.
In-SItu, Inc.
210 South Third Street
Laramie, WY 82070-0920
Tel: (307) 742-8213
Evatuator: Carnegie Motion Reaearch Institute


Date of evaluation: 07-29-91
                                                                                                                                                     94

-------
                                Leak Detection Systems, inc.

                      Tank Auditor, Version RTD V.2.16 (Overfilled Test)
                                                                                      .
                                                                             UK AS-i
                       VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD=99.98% & PfA=0.02%.

Leak Threshold:       0.05 gallon per hour if groundwater presence is determined (a leak is
                     declared if the output of the measurement system exceeds this threshold).
                     If using 2 level testing, the level is changed by 3 feet between the two
                     tests and if the net change between the two tests is greater than 0.02 gph,
                     a teak is dsclarsd.

Applicability:          Gasoline, diesel, aviation fuel, fuel oil *4, solvents, waste oil and other
                     liquids that flow under ambient conditions.

Capacity:             The maximum tank capacity is 15,000 gallons.
                     The tank must be 100% full.

Waiting Time:         Minimum waiting time between product delivery and test data  collection is
                     variable dependent on site conditions but must not be less than 6 hours.
                     Minimum waiting time between "topping off" and test data collection must
                     be 1 hour.
                     There must be no dispensing or product delivery during the test waiting
                     time.

Test Period:          The minimum data collection time must be 1 hour.
                     Test data must bs acquired and recorded by a computer.
                     Leak rate calculated from data determined to be valid by statistical analysis.

Ground Water:        If depth to the water table is determined and it is above the bottom  of the
                     tank, the product level must be adjusted to provide height differential of 3
                     fast between tha product and water in the backfill.  If depth to the vvstsr
                     table is not determined, 2 tests must be performed with a level change of
                     at least 3 feet between tests.

Calibration:           The level sensors must be calibrated before each test.

Comments:           This equipment was not evaluated using manifolded tanks.
                     The evaluation of this equipment  did not include a field evaluation of the
                     ground water compensation by two level testing.
 Leak Detection Syatema, Inc.
 152 ting Street
 Coho.nl, MA 02025
 Tel: (817) 383-2305
Evakiator: K«n WHcox Aeeodatae


Date of Evaluation: 11-29-91
                                            95
                                                                                           Maiiory Controls

                                                                               Pollulert Probes MD221G/T. MD221G/TRA
                                                                                                                              UK AS-1
                                                      Detector:

                                                      Output type:
                                                      Sampling frequency:
                                                      Operating principle:
                                                                           LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
qualitative
continuous
electrical conductivity
                                                     Test Results:
                                                                      Commercial      Synthetic         Jet Fuel
                                                                       Gasoline.          Gasoline          (JP-4)
                                                     Accuracy(%)          100             100             100
                                                     Detection time(sec)     472
                                                     Fall time (sec)         344
                                                     tower detection
                                                     limit(cm)         0.08-0.32        0.08-0.32        0.08-0.32
                                                     Specificity Results:

                                                     Activated:    commercial gasoline, toluene, n-Hexane, diesel fuel, jet-A fuel, JP-4 jet fuel, synthetic
                                                                  gasoline, xylene(s).

                                                     Manufacturer's Specifications:
                                                     Comments:
                                                                  EPA and many states require detection of 1/8 inch of product, which is 0.32 cm.
                                                                  Evaluation was conducted on probe FD221G/TRA, which has identical performance
                                                                  to probes listed, according to manufacturer.  Probes beginning with "MD" have
                                                                  identical performance as older probes beginning with "FD," according to
                                                                  manufacturer. The test procedures used were those in Radian Corporation's draft
                                                                  report "Development of Procedures to Assess the Performance of External Leak
                                                                  Detection Devices: Liquid-Phase ASTM-Formatted Methods," June 29, 1990.
                                                                                                             Mallory Conuott
                                                                                                             2831 Waterfront Hcwy. E. Or.
                                                                                                             Indianapolie, IN 48214
                                                                                                             Tel: (000) 343-2128
                                                                                                            Evaluator: Radian Corporation
                                                                                                                                                                   Data of Evaluation: 07-08-91
                                                                                                                                                        98

-------
                                      Mallory Control*

                  PoHutort ProbM MD241R. MD241RRA. MD241G, MD241GRA
                                                                             DRAFT
                                                                                                                          Mallory Control*

                                                                                                      Pollulert Probe* MD221V, MD221VRA, MD210V.-MD210VRA
                                                                                                                                                           DRAFT
 Detector:

 Output type:
 Sampling frequency:
 Operating principle:
                      LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
qualitative
continuous
electrical conductivity
                                                                                     Detector:
                                                                                                                               VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
 Output type:          qualitative
 Sampling frequency:   continuous
 Operating principle:    adsistor
 Test Roiultt:

Accuracy(%)
Detection time(sec)
Fa!i Tims (sec)
Lower detection
limit
-------
                                     mariey rump Co.
                                                                            IJKAS-1
    Sonic Technology 1ST) 1400-1800 Series Tank Monitoring System (Ultrasonic Transducer)
             ATG Automatic Tank Gauging Monitor. LLM Series Liquid Level Monitor
                               FMS Fuel Management Monitor

                           AUTOMATIC TANK GAUGING SYSTEM

Certification:          Leak rate of 0.2 gallon per hour with P0 = 100% & PFA=0%.

Leak Threshold:       0.1 gallon per hour (a leak is declared if the output of the system exceeds
                     this threshold).

Applicability:          Gasoline, diesel, aviation fuel, and solvents.

Capacity:             The maximum tank capacity is 18,000 gallons.
                     The tank must be between 50 and 95% full.

Waiting Time:        Minimum waiting time between product delivery to the tank and test data
                     collection must be 10 hours.

Test Period:          The minimum data collection time must be 2.35 hours.
                     Test data must be acquired and recorded by a computer.
                     Leak rate is calculated from all data collected.
                     There must be no dispensing or product delivery during the test.

Temperature:         A minimum of 5 temperature sensors are used to determine the average
                     temperature of the stored product.

Water Sensor:        A water sensor must be used to detect water incursion.
                     Minimum water level detectable in the tank is 0.112 inches.
                     Minimum detectable water leval change is 0.011 inches.

Calibration:          Temperature sensors and probe must be checked and calibrated annually in
                     accordance with manufacturer's instructions.

Comments:          The equipment was not evaluated using manifolded tanks.
                     This equipment only tests the portion of the tank that contains product.
                      As the product level is lowered the leak rate in a leaking tank decreases
                      (due to lower head pressure).
                      This system  was previously known as the LT1 Automatic Product Level
                      Monitor and  was manufactured by Level Tech, Inc. (purchased by Marley
                      9/91).
 MatUy Pump Co.
 S8OO Foxrida* Drive
 Miilon, KS 86202
 Tel: (913) 831-5700
                                                    Evaluator: ADA Tochnotogiea
Data of Evaluation: 09-30-92
                                             99
                                                                                               mariey rump Co.

                                                              Sonic Technology 1ST) 1400-1800 Series Tank Monitoring System (Ultrasonic Transducer)
                                                                      ATG Automatic Tank Gauging Monitor, LLM Series Liquid Level Monitor,
                                                                                        FMS Fuel Management Monitor
                                                          Certification:

                                                          Leak Threshold:


                                                          Applicability:

                                                          Capacity:


                                                          Waiting Time:


                                                          Test Period:




                                                          Temperature:


                                                          Water Senior:



                                                          Calibration:


                                                          Comments:
                                                           Mariay Pump Co.
                                                           5800 Foxridgd Driva
                                                           Minion, KS B6202
                                                           Tol: (913) 831-5700
     AUTOMATIC TANK GAUGING SYSTEM

Leak rate of 0.1 gallon per hour with PD = 99.9% & PFA=0.01%.

0.05 gallon per hour (a leak is declared if the output of the system exceeds
this threshold).

Gasoline, diessl, aviation fuel, fuel oil #4, fuel oil #6, and some solvents.

The maximum tank capacity is 18,000 gallons.
The tank must be 95% full.

Minimum waiting time between product delivery to the tank and test data
collection must be 12 hours.

The minimum data collection time must be 2.35 hours.
Test data must be acquired and recorded by a computer.
Leak rate is calculated from all data collected.
There must be no dispensing or product  delivery during the test.

A minimum of 5 temperature sensors are used to determine the average
temperature  of the stored product.

A water sensor must be used to detect water incursion.
Minimum water level detectable in the tank is 0.112 inches.
Minimum detectable water level change is 0.011 inches.

Temperature sensors and probe must be checked and calibrated annually in
accordance with manufacturer's instructions.

The equipment was  not evaluated using  manifolded tanks.
This equipment only tests the portion of the tank that contains product.
As the product level is lowered, the teak rate in a leaking tank decreases
(due to lower head pressure).
This system was previously known as the LT1  Automatic Product Level
Monitor and was manufactured by Level Tech, Inc. (purchased by Marley
9/91).

                              EvnlUitor:  ADA Tochnologioi, Inc.


                              Dit« of Evaluation: 09-25-92
                                                                                                                                                         100

-------
                                                                         DRAFT
                                     Marley Pump Co.

                                 Red Jacket ATM System,
                              Ver. RLM 5000, 5001, and 9000

                           AUTOMATIC TANK GAUGING SYSTEM

Certification:          Leak rate of 0.2 gallon per hour with PD = 100% & PFA=0%.

Leak Threshold:       0.1  gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, and solvent.

Capacity:             The maximum tank capacity is 15,000 gallons.
                     The tank must be between 50 and 95% full.

Waiting Time:         Minimum waiting time between product delivery to the tank and test data
                     collection must be 6 hours.

Test Pariod:          The minimum data collection time must be 3 hours.
                     Test data must be acquired  and recorded by a computer.
                     There must be no dispensing or product delivery during the test.

Temperature:          A minimum of 5 temperature sensors must be used to determine the
                     average temperature of the  stored hazardous substance.

Water Senior:         A water sensor must be used to detect water incursion.
                     Minimum water level detectable in the tank is 1.04 inches.
                     Minimum detectable water level change is 0.011  inches.

Calibration:           Temperature sensors and probe must be checked and calibrated annually in
                     accordance with manufacturer's instructions.

Comments:           The equipment was not evaluated using manifolded tanks.
                     This equipment only tests the portion of the tank that contains product.
                     As the product level is lowered the leak rate in a leaking tank decreases
                     (due to lower head pressure).
Marlev Pump Co.
5800 Faxridge Drive
Mission, KS 66202
Tel: 1913) 831-5700
                                                      Evotuator: Ken Wricox Associates
                                                      DM of Evaluation: 04/02/91
                                           101
                                     Marley Pump Co.
                                                                          DRAFT
   Red Jacket PPM 4000, RLM 9000, RLM 10000, ST 1401, ST 1401 L, ST 1801, and ST1801L


                      AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification:          Leak rate of 3 gallons per hour with PD = 100% & Pu=0%.

Leak Threshold:       3 gallons per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel and solvent.

Specification:         System is installed on pressurized fiberglass and steel piping.
                     The piping system volume must not exceed 56 gallons.
                     Tests are conducted at 5-10 psi.

Waiting Time:         There is no waiting  period between product delivery and testing.
                     There is no waiting  period between last dispensing and testin".

Test Period:          The minimum data collection time (response time) for the test is 1 second.
                     Test data must be acquired and recorded by a microprocessor.
                     Calculations are automatically  done by the microprocessor.

System Features:      This system is permanently installed on the pipeline and automatically tests
                     the line.
                     Uses a preset threshold and a  single test to determine whether the pipeline
                     is leaking.
                     This system records and displays day, date, time of positive test.
                     If a leak is declared, this system displays a message, triggers an alarm, and
                     shuts down the dispensing system.

Calibration:           Sansor must bs checked and calibrated annually in accordance with
                     manufacturer's instructions.
Mariev Pump Co.
5800 Foxrido* Drive
Minion, KS 86202
Tel: (913)813-5700
Evaluator: Kon Wilcox Associates


Data of Evaluation: 3/11/91
                                                                                                                                                      102

-------
                                                                            no  ACT
                                                                            Ui^f^r I
                                      Msri*y Pump Co.

   Red Jacket PPM 4000. RLM 9000. RLM 10000. ST 1401. ST 1401L, ST 1801. and ST1801L
                AUTOMATIC ELECTRONIC LINE LEAK DETECTOR (annual test)

Certification:          Leak rate of 0.1 gallon per hour with PD-100% & PM-0%.

Leak Threshold:       0.047 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel and solvent.

Spsoificstic,-.:         System is installed on pressurized fiberglass and stesl piping.
                     The piping system volume must not exceed 56 gallons.
                     Tests are conducted at 10 psi.

Waiting Time:        There is no waiting period between product delivery and testing.
                     There is no waiting period between last dispensing and testing.

Test Period:          The minimum data collection time must be 2.5 hours.
                     Test data must be acquired and recorded by a microprocessor.
                     Calculations are automatically done by the microprocessor.

System Features:     This system is permanently installed on the pipeline and automatically tests
                     the line.
                      Uses a preset threshold and a single test to determine whether the pipeline
                     is leaking.
                     This system records and displays day, date, time of positive test.
                      If a leak is declared, this system displays a message, triggers an alarm, and
                      shuts down the dispensing system.

Calibration:           Sensor must be checked and calibrated annually in accordance with
                      manufacturer's instructions.
 M«r1«y Pump Co.
 5800 Foxridg* Drive
 Migrion, KS 89202
 Tel: (913) 813-5700
Evaluator: Kin Wilcox AtiooUtu


Data of Evaluation: 3/11/91
                                             103
                                                                                            Msrfcy Pump Cs.

                                                                                        Red Jacket OLD and XLD
                                                                                                                              D
                                                                                   MECHANICAL LINE LEAK DETECTOR

                                                       Certification:          Leak rate of 3.0 gallon per hour with PD = 100% & PFA=0%.

                                                       Leak Threshold:       2.0 gallon per hour (a leak is declared if the output of the measurement
                                                                            system exceeds this threshold).

                                                       Applicability:          Gasoline, diesel, aviation fuel and solvent.

                                                       Specification:         System is installed on pressurized fiberglass and steel piping.
                                                                            The piping system volume must not exceed  129 gallons.
                                                                            Tests are conducted  at 8-12 psi.

                                                       Waiting Time:         There is no waiting period between product delivery and testing.
                                                                            There is no waiting period between last dispensing and testing.

                                                       Test Period:          The minimum test time (response time) is 6 seconds.

                                                       System Features:     This system is permanently installed on the piping and automatically tests
                                                                            the line. It uses a preset threshold and a single test to determine whether
                                                                            the piping is leaking.
                                                                            If a leak is detected,  this system restricts fuel flow to dispenser.

                                                       Calibration:           Equipment must be checked annually in accordance with manufacturer's
                                                                            instructions.
Mariay Pump Co
5800 Foxridoa Driva
MMon, KS 88202
T«l: (913) 813-5700
Evaluator: Kin Wilcox Anoclataa


Data of Evaluation: 12/21/90
                                                                                                                                                            104

-------
                                      Mariey Pump Co.

                                     Red Jacket FX1/FX2
                             MECHANICAL LINE LEAK DETECTOR

Certification:           Leak rate of 3.0 gallons per hour with P0 = 100% & PFA=0%.

Leak Thrtshold:        2.0 gallons per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

Applicability:           Gasoline, diesel, aviation fuel, and some solvents.

Specification:          System is installed on pressurized fiberglass or steel.  The piping system
                      volume must not exceed 257 gallons. Tests are conducted at 8-12 psi.

Waiting Time:          There is no waiting period between delivery and testing.
                      There is no waiting period between last dispensing and testing. Stabilization
                      time up to 45 minutes after dispensing may be required when temperature
                      extremes are present.

T«*t Period:           The test time  (response time) is less than 5 minutes.

System Features:      This system is permanently installed on the piping and automatically tests
                      the line. It uses a preset threshold and a single test to determine whether
                      the piping is leaking. If a leak is detected, this system restricts flow to the
                      dispenser.

Calibration:            Equipment must be checked annually for capability of detecting a leak of
                      3.0 gallons per hour in accordance with manufacturer's instructions.
Morlay Pump Co.
5800 RoxrWga Drive
Minion. KS a«202
T«l: 013)813-5700
Evaluates: Kan Wilcox A»»oc!»t««


Data of Evaluation: 3/14/84
                                            105
                                                                                                                                                                                            DRAFT
                                                                                                         Mariey Pump Co.

                                                                                                    Red Jacket FX1/FX2 Rexline
                                                                   Certification:

                                                                   Leak Threshold:


                                                                   Applicability:

                                                                   Specification:


                                                                   Wailing Time:


                                                                   Test Period:

                                                                   System Features:
                                                                   Calibration:
                             MECHANICAL LINE LEAK DETECTOR

                      Leak rate of 3.0 gallons per hour with P0 = 100% & PfA=0%.

                      2.0 gallons per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

                      Gasoline, diesel, aviation fuel, and some solvents.

                      System is installed on flexible pipeline.The piping system volume must not
                      exceed 49.6 gallons.

                      There is no waiting period between delivery and testing.
                      There is no waiting period between last dispensing  and testing.

                      The test time (response time) is less than 3 minutes.

                      This system is permanently installed on the piping and automatically tests
                      the line. It uses a preset threshold and a single test to determine whether
                      the piping is leaking. If a leak is detected, this system restricts flow to the
                      dispenser.

                      Equipment must be checked annually for capability of detecting a leak of
                      3.0 gallons per hour in accordance with manufacturer's instructions.
                                                                                                              Comments:           Enviroflex pipeline was used during this evaluation which had a bulk
                                                                                                                                   modulus of 1,280 psi.
                                                                                                                                   In order for the leak detector to have adequate test, time delays must be
                                                                                                                                   integrated into the electronic dispensing equipment or retrofitted in the
                                                                                                                                   junction box. Without this delay, the nozzles cannot be guaranteed being
                                                                                                                                   closed for sufficient time to allow the leak detector to compile its line test
                                                                                                                                   and provide uninterrupted service.
Martay Pump Co.
6800 Fexridfla Driva
Million, KS 4S2O2
Tel: (913) 813-5700
Evaluator: Kan Wiloox Anooiataa


Data of Evaluation: 3/22/94
                                                                                                                                                         106

-------
                                      Msrisy Pump Cc.

                               Red Jacket FX2/FX2-O (Bigflow)
                                                                          no ACT
                                                                                        i
                            MECHANICAL LINE LEAK DETECTOR

Certification:          Leak rate of 3.0 gallons per hour with PD = 100% & PFA=0%.

Leak Threshold:       2.0 gallons per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diasel.

Specification:         System is installed on pressurized fiberglass or steel.  The piping system
                     volume must not exceed 362 gallons. Tests are conducted at 8-12 psi.

Waiting Time:         There is  no waiting period between delivery and testing.
                     There is  no waiting period between last dispensing and testing.
                     Stabilization time up to 45 minutes after dispensing may be required when
                     temperature extremes are present.

Test Period:          The minimum test time (response time) is 3 minutes.

System Features:     This system is permanently installed on the piping system and automatically
                     tests the line. It uses a preset threshold and a single test to determine
                     whether the piping is leaking. If a leak is detected, this system restricts
                     flow to the dispenser.

Calibration:          Equipment must be checked annually for capability of detecting a leak of
                     3.0 gallons per hour in accordance with manufacturer's instructions.
 Marlty Pump Co.
 5800 Foxiidg* Driv«
 Million, KS 08202
 Tel: (913) 813-5700
Evihiitor: K»n Wilcox AMOC!«M


Dun of Evaluation: 3/16/94 & 8/1/94
                                             107
                                                                                                       Marley Pump Co.

                                                                                                        Red Jacket XLP
                                                                                              MECHANICAL LINE LEAK DETECTOR

                                                                  Certification:          Leak rate of 3.0 gallon per hour with PD = 100% & PFA=0%.

                                                                  Leak Threshold:       2.0 gallon per hour (a teak is declared if the output of the measurement
                                                                                       system exceeds this threshold).

                                                                  Applicablity:          Gasoline, diesel, aviation fuel and solvent.

                                                                  Spac'nicattofl:         System is installed on pressurized fiberglass and steal piping.
                                                                                       Ths  piping system volume must not exceed 129 gallons.
                                                                                       Tests are conducted at 15-22 psi.

                                                                  Waiting Time:         There is no waiting period between delivery and testing.
                                                                                       There is no waiting period between last dispensing and testing.

                                                                  Test Period:          The  minimum test time (response time) is 6 seconds.

                                                                  System Features:     This system is permanently installed on the piping and automatically tests
                                                                                       the line.  It uses a preset threshold and a single test to determine whether
                                                                                       the piping is leaking.
                                                                                       If a leak is detected, this system restricts fuel flow to dispenser.

                                                                  Calibration:           Equipment must be checked annually in accordance with manufacturer's
                                                                                       instructions.
M*rity Pump Co.
5800 Foxridot Drivo
Mliion, KS 66202
T*l: 1*13) 813-5700
Ev«lu*tor: Ktn Wilcox Anooiiiei


D«tl ol Evthlitton: 12/21/90
                                                                                                                                                         108

-------
 Certification:

 Uak Threshold:


 Applicability:

 Specification:



 Waiting Time:


 Teit Period:

 System Features:




 Calibration:
                 Marley Pump Co.

                 Red Jacket XLP


       MECHANICAL LINE LEAK DETECTOR

Leak rate of 3.0 gallon per hour with P0= 100% & PFA=0%.

2.0 gallon per hour (a leak is declared if the output of the measurement
system exceeds this threshold).

Gasoline, diesel, aviation fuel and solvent..

System is installed on pressurized flexible piping.
The piping system volume must not exceed 48.9 gallons.
Tests are conducted at operating pressure.

There is no waiting period between delivery and testing.
There is no waiting period between last dispensing and testing.

The minimum test time (response time) is less than 3 minutes.

This system is permanently installed on the piping and automatically tests
the line.  It uses a preset threshold and a single test to determine whether
the piping is leaking.
If a leak is detected, this system restricts fuel flow to dispenser.

Equipment must be checked annually in accordance with manufacturer's
instruction*.
                                                                                                                                                    Mine Safety Appliances

                                                                                                                                                          Tankgard
                                                                                                                                               Version: P/N 481532 S/N 03095

                                                                                                                                      VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:

Output type:           quantitative
Sampling frequency:    continuous
Operating principle:    metal oxide semiconductor
Test Results:
                              Banzens         2-Methvlbutane
Accuracy (%):                 100                  100
Dstsction Tims (ssc):           5                     16
Fall Time (min:sec):            04:12                04:42
Lower Detection Limit(ppm):    12.5                  12.5

Specificity Results:

Activated (100%):     Benzene, n-Butane, n-Hexane, 2-Methylpentane, Toluene, Isobutane
Manufacturer's Specifications:
                                                                                                                 Maximum Wire Distance:
                                                                                                                 Response Time:
                                                                                                                 Recover Time:
                                                                                                                 Sensor Life:
                                                                                                                     500 ft using 18 AWG
                                                                                                                     30 seconds
                                                                                                                     1 minute maximum
                                                                                                                     2 year warranty
Marlav Pump Co.
68OO Foxridee Drive
Mission, KS 68202
Tot: (9131 813-5700
                                   Evaluator: Kan Wilcox Associates


                                   Date of Evaluation: 04/19/93
                                                                                                                 Mine Safety Appliances
                                                                                                                 P. O. Box 427
                                                                                                                 Pittsburgh, PA 15230
                                                                                                                 Tel: (412) 776-8600
                                                                                                                                                                Evaluaton Carnegia Mellon Research Institution
                                                                                                                                                                Date of Evaluation: 3/26/91
                                            109
                                                                                                                                                             110

-------
                                  mint Safety Appliances

                                       Tankgard VIII
                              Version: P/N 488803 S/N 00389

                     VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:

Output type:          quantitative
Sampling frequency:   continuous
Operating principle:    metal oxide semiconductor
Test Results:
                              Benzene          2-Methvlbutane
Accuracy (%):                 100                  100
Detection Time (sec):           5                     16
Fall Time (min:sec):            04:12                 04:42
Lower Detection Limit (ppm):    12.5                  12.5

Specificity Results:

Activated(100%): benzene, n-Butane, n-Hexane, isobutane, 2-methylpentane, toluene
Manufacturer's Specifications:
Maximum Wire Distance:
Response Time:
Recover Time:
Sensor Life:
SOOftusinglSAWG
30 seconds
1 minute maximum
2 year warranty
 Mm Safety Appliances
 P. 0. Box 427
 Pittsburgh, PA 15230
 Tel: (412) 778-8600
                          Evahiator: Carnegie MeHon Research Institution


                          Dst. of Evaluation: 3/28/91
                                            111
                                                                                                                     NDE Environments!

                                                                                                 Computerized VPLT Underfilled Tank Tightness Testing System
                       VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with P0-99.9% & PFA-0.1%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applfcaba'rty:          Gasoline, diesel, aviation fuel, fuel oil #4, fuel oil #6, solvents, waste oil
                     and other products.

Capacity:             The maximum tank capacity is 18,000 gallons.
                     The tank must contain at least 24 inches of product.

Waiting Time:         The waiting time between product delivery to tank and test data collection
                     must be long enough to ensure a temperature change of less than 0.09
                     •F/hr, typically at least 2 hours.

Test Period:          The minimum data collection time must be 2 hours.
                     Test data must be acquired and recorded by a computer.
                     Leak rate is calculated from average over data window.
                     There must be no dispensing or product delivery during the test.

Temperature:         Typically 5 thermistors are used to determine the average temperature of
                     the stored product. A minimum of one is required.

Ground Water:        Depth to the  water table present in the backfill must be determined, and if
                     it is above the bottom of the tank, the product level in the tank is adjusted
                     to provide minimum of 1 psi pressure differential, positive or negative, on
                     the bottom of the tank during the test.

Calibration:           Sensors must be checked and calibrated annually.

Comments:       1.  The equipment was not evaluated using manifolded tanks.
                 2.  This equipment only tests the portion of the tank that contains product.
                 3.  As the product level is lowered the leak rate  in a leaking tank decreases
                     (due to lower head pressure).
NOE Environmental
8908 Wa« Street, Suit. 306
Austin, TX 78764
Tel: (800) 800-4633
Evatuator: Ken Wilcox Aesoo.


Date of Evaluation: 02-15-93
                                                                                                                                                      112

-------
                                  NDE Environmental

               Sura TMt - Assured Tight System, Series IV (Underfilled Test)
                                                                         DRAFT
                                                                                                                                         NDE Environment^

                                                                                                                                 UST Ullage Test • Version ProEco U2
                                                                                                                                                                             DRAFT
Certification:

Leak Threshold:


Applicability:

Capacity:


Waiting Thne:


Test Period:




Temperature:


Ground Water:




 Calibration:


 Comments-
                     VOLUMETRIC TANK TIGHTNESS TEST METHOD

                   Leak rate of 0.1 gallon per hour with PD=99.99%  & PFA=0.005%.

                   0.05 gallon per hour (a teak is declared if the output of the measurement
                   system exceeds this threshold).

                   Gasoline, diesel, aviation fuel, fuel oil, solvents, and waste oil.

                   The maximum tank capacity is 18,000 gallons.
                   The tank being tested must be between 1 1 % and  95% full.

                    Minimum waiting time between product delivery to the tank and test data
                    collection must be 6 hours.

                    The minimum data collection time must be 3 hours.
                    Test data must be acquired and recorded by a computer.
                    Leak rate is calculated from average of subsets of all collected data.
                    There must be no dispensing or product delivery during the test.

                    A minimum of 24 inches of product must be present for the temperature
                    probes to operate properly.

                    Depth to the water table present in the backfill must be determined, and if
                    it is above the bottom of the tank, the product level in the tank is adjusted
                    to provide minimum of 1 psi net pressure on the bottom of the tank during
                    the test.

                    Temperature probes and floats must be checked for proper operation prior
                    to each test.

                 1 .  The equipment was not evaluated using manifolded tanks.
                 2  This equipment only tests the portion of the tank that contains product.
                 3.  As the product level is lowered the  leak rate in a  leaking tank decreases
                    (due to lower head pressure).
                NON-VOLUMETRIC ULLAGE TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with P0 = 95.24% & PFA=0%.

Leak Threshold:       Pressure decay trend not to exceed  ±  0.016 psi/hr.

Applicability:          Gasoline, diesel, aviation fuel, heavy fuel oils (#2 through #6), and solvents.


Capacity:             Maximum ullage volume is 10,260 gallons.

Waiting Time:         At least 2 hours between the end of adding the product and the start of
                     data collection.

Test Period:           Minimum data collection time must be 30 minutes (after data trend has
                     been established).

Test Pressure:         During the test, a total of 4.0 psi pressure at the bottom of the tank Is
                     applied.

Temperature:         Temperature of ullage portion of the tank is monitored during the test.  A
                     correction factor is applied to account for temperature changes. The
                     correction factor is not applicable for ullage temperature changes greater
                     than 5°F.

Groundwatar:         Depth to the water table present in the backfill must be determined. If it is
                     above the product level, the ullage test pressure is maintained at a minimum
                     of 1.0 psi higher than the pressure exerted by water table.

Comments:           - The product filled portion of the tank must be tested using a volumetric
                     underfilled test.
                     - This test method was third-party certified using #2 diesel fuel as  the test
                     product.
                     - This test method was not third-party certified with manifolded tanks.
NDE Environmental Corp.
89oa w«ii street, suit* sot
Austin, TX 78754
Tel: (800) 80O-4633
                                                       Evaluetor: ADA Technologiee
                                                        Data of Evaluation: 09-08-92
                                                                                                    NDE Environmental Corp.
                                                                                                    8908 Wall Straat. Sulta 306
                                                                                                    Auatin, TX 787S4
                                                                                                    Tal: (800) 80O-4633
                                                                                                                                               Evatuator: ADA Teohnologiea, Inc.


                                                                                                                                               Data of Evaluation: 04-10-92
                                           113
                                                                                                                                               114

-------
                                    NDE Environmental

                                    UTS-4T Ullage Test
                                                                        DRAFT
                NON-VOLUMETRIC ULLAGE TANK TIGHTNESS TEST METHOD

Certification:      Leak rate of 0.1 gallon per hour with P0~95.2%; PFA=0%.

Leak Threshold:   Make-up gas flow rate into ullage exceeding 0.275 cubic feet/hour.

Applicability:      Gasoline, diesel, aviation fuel, heavy fuel oils #4, and solvents.

Capacity:         Maximum ullage volume is 7,500 gallons.

Waiting time:     At least 2 hours between the end of adding the product and the start of data
                 collection.

Test Period:      Data collection time is at least 30 minutes. Test data is acquired and recorded
                 manually.

Test Pressure:    The pressure in the ullage portion of the tank is increased such that the net
                 pressure at the bottom of the tank (sum of ullage pressure and product head)
                 does not exceed 5.0 psi.  It is maintained for a minimum of 5 minutes per 1,000
                 gallons of ullage.  At the conclusion of this stabilization period, the ullage
                 pressure is reduced by 0.5 psi for the  remainder of the test.

Temperature:     Temperature of the ullage must be monitored, and the rate of change of ullage
                 temperature must not exceed manufacturer's tabulated values.

Groundwater:    Depth to the water table present in the backfill must be determined, and if it is
                 above the product level, the net outward  pressure must exceed 1  psi throughout
                 the ullage.

Comments:      - The product portion of the tank must be tested using a volumetric underfilled
                 test.
                 - This test method was third-party certified using #2 diesel fuels as the test
                 product.
                 - This test method was third-party certified using manifolded tanks.
 NOC Environment
 8908 W>» SUM!, Suit! 306
 Aunt*!. TX 7B76*
 T.I (800) SOO-4B33
Evaluator: Midwaat Raaaaroh Institute


Data of Evaluation: 12-O4-92
                                            115
                                                                                                       NDE Environmental

                                                                                               U3 Ullage Test (Vacuum or Pressure)
                                                                                                                                          DRAFT
                                                                   Certification:
                 NON-VOLUMETRIC ULLAGE TANK TIGHTNESS TEST METHOD

                 Leak rate of 0.1 gallon per hour with PD = 100% & PM=0%.
                                                                   Leak Threshold:   A leak is declared if the noise signal detected is different from the baseline.
                                                                                    (Baseline is the noise signal before pressure or vacuum is applied to the tank.)

                                                                   Applicability:      Gasoline, diesel, aviation fuel, fuel oil #4 and #6,  solvent and waste oil. Since
                                                                                    this is an ullage test, it is applicable to virtually any fluid.

                                                                   Capacity:         Maximum ullage volume is 16,500 gallons.

                                                                   Waiting Time:     There is no waiting time required after product delivery to the tank.

                                                                   Test Period:       The data collection time (determination of background noise and a leak) is a few
                                                                                    minutes. After the desired pressure has been reached, the tank should be
                                                                                    allowed to settle for ten minutes. Test period also depends on background noise
                                                                                    at the site  and on the size of the leak.

                                                                   Test Pressure:     A vacuum  blower to produce a vacuum of 1  psi in the ullage portion is used.  Or,
                                                                                    a nitrogen pressure of 4 psi at the tank bottom is applied.

                                                                   Temperature:      Acoustical signal is independent of product temperature.

                                                                   Groundwater:     Depth to the water table present in the backfill must be determined. If it is
                                                                                    above the product level, a vacuum test should not be used. The pressure test
                                                                                    may only be used if the ullage test pressure is maintained at a minimum of 1.0
                                                                                    psi higher than the pressure exerted by the water table.  If this requires more
                                                                                    than 5 psi at tank bottom, then the ullage test should not be used.

                                                                   Comments:       - This test method was third-party certified using #2 diesel fuel as the test
                                                                                    product.
                                                                                    - During the third-party testing, the microphone was 25 feet away from the leak
                                                                                    source.
                                                                                    - Excess background noise can  be a factor in the test result. If background
                                                                                    noise is too high, the test is inconclusive.
                                                                                    - Noise signals are tape recorded (not digitally recorded).
                                                                                    - This test method was not third-party certified with manifolded tanks.
                                                                                    - When testing with vacuum, this test method may not be effective in some
                                                                                    backfill, because some particles (such as clay) may plug a hole in the tank.
                                                                                    - If the soil is saturated with product, this test will not detect air or water
                                                                                    Ingress.
NDE Environmental Corp.
8908 Wall Sweat
Austin, TX 787S4
Te); (BOO) 800-4633
Evaluator: K«n Wilcox Aiiooiitoi
                                                                                                                                                        Dale of Evaluation: 1/15/93
                                                                                                                                                     116

-------
                                      NDE Environmental

                               Prdine Tost Series III. Version 1.0
Certification:

Leak Threshold:


Applicability:

Specification:
Waiting Time:
Test Period:
Calibration:
         LINE TIGHTNESS TEST METHOD

Leak rate of 0.1  gallon per hour with P0=-99.0% & PFA=0.1%.

0.05 gallon per hour (a leak is declared if the output of the measurement
system exceeds this threshold).

Gasoline, diesel, aviation fuel, fuel oil #4 & #6, solvents, and waste oil.

System tests fiberglass and steel piping.
The piping system volume must not exceed 41  gallons.
Tests are conducted at 150% of the line operating pressure.
Mechanical line leak detector must be removed from the pipeline system
being tested.

No waiting time between last delivery of the product to the tank and the
start of data collection.
Minimum waiting time between last dispensing and testing is one hour.

The minimum data collection time for the test must be one hour.
Pipe deflection, vapor pockets, and large temperature  differences may
produce inconsistent readings, testing to continue until stable conditions are
present.
Test data  must be acquired and recorded manually.
Manual calculations are performed by the operator on  site.

Sensors must bo calibrated before each test.
NDE Environmental Corp.
8906 Wall Street. Suite 306
Austin, TX 787S4
Tel: 1800) 800-4633
                                    Evakiator: Midwest Research Institute


                                    Date of Evaluation: 08-30-91
                                             117
                                                                                                                            NDE Environmental

                                                                                                                                 PTK-88
                               LINE TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD = 99.8% & PPA = 1.3%.

Leak Threshold:        0.05 gallon per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil, solvent, and waste oil.

Specification:          System tests fiberglass and steel piping.
                      The piping system volume must not exceed 40 gal.
                      Tests are conducted at 150% of the line operating pressure.
                      The mechanical line leak detector must be removed from the pipeline
                      system being tested.

Waiting Time:         There is no minimum waiting period between product delivery and testing.
                      Minimum waiting  period between last dispensing and testing is one  hour.

Test Period:           The minimum data collection time must be 10 minutes per cycle.
                      Test data is acquired and recorded manually.
                      Manual calculations are performed by the operator on site.

Calibration:            Sensors must be calibrated before each test.
                                                                                                             NOE Environmental Corp.
                                                                                                             8906 Wall Street, Suite 306
                                                                                                             Auitin, TX 78754
                                                                                                             Tel: (800) 800-4633
                                                                                                                                                Evahiator: Mklwoet Re>earch Inithute


                                                                                                                                                Data of Evaluation: 2/14/91
                                                                                                                                                         118

-------
                                  O/C Tanks Corporation

              0/C TANKS Hydrostatic Precision Tank Twt for DWT-Type II Tanks
Certification:


Leak Threshold:



Applicability:

Capacity:



Waiting Time:
Test Period:
 Other Limitations:
    DOUBLE WALLED TANK TIGHTNESS TEST

Leak rate of 0.1 gallon per hour with per hour with PD-99.9% &
PfA»= 1.2% without dispensing and with PD=95% & PFA=5.0%.

0.05 gallon per hour without dispensing and 0.07 gallon per hour with
dispensing (a leak is  declared if the output of the measurement system
exceeds this threshold).

Gasoline, diesel, aviation fuel, and fuel oii #4.

The maximum  tank capacity is 13,000 gallons.
The tank may be tested from zero to 100% full.
The maximum  tank diameter must be 10 feet.

Minimum waiting time between product delivery and test data collection
must be 24 hours.
Minimum waiting time bstwssn "topping off" the annular space with liquid
and test data collection must be 3 hours.
There must be no dispensing or product delivery during the test waiting
time.

The minimum data collection time must be 4 hours.
The maximum amount of liquid allowed to withdraw from the tank during
the test must be 150 gallons per hour.
A leak is not declared unless the threshold is exceeded in two tests,
separated by at toast 8 hours which are performed without dispensing and
without changes in the water table.

Volume of trapped vapor not to exceed 20 gallons.  The change in
barometric pressure must be less than 0.04 psia over the 4-hour test
 period. The annular space is at least 100% full with either water or
 antifreeze.  If the ground water is above the bottom of the tank, and no
 product is being dispensed during a test, the total change in ground water
 elevation during a test must be less than 1.5 inches per hour. If the ground
 water is below the bottom of the tank or not changing during a test, the
 total change in product level during a test must be less than 0.75 inches
 per hour.
 QIC Tanki Corporation
 FitmrglMl Towir
 Td«do, OH 438*9
 T«t: (419) 24S-S475
                                               EvikiMor:
                          D>M of «v»luition: 06-16-tl
                                            119
                                                                                                                                                                           DRAFT
                                       Leak Edge
                               Models 100-3001. 100-4001

                    LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                                       Detector:
    Output type:
    Sampling frequency:
    Operating principle:

Test Results:
qualitative
continuous
product permeable
    Accuracy(%)
    100
    Detection time(hr:m!n:sec)
    Fall Time (hr:min:sec)
    Lower detection limit(cm)

Specificity Results:
    Commercial
    Gasoline
    100

    00:05:41
    00:30:39
    0.02
                                                  Synthetic
                                                  Gasoline
00:05:14
00:18:36
0.02
     Activated:    commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, synthetic
                 gasoline, xylene(s).

 Manufacturer's Specifications:
                 Operating temperatures: Sensor is -40°C to +74°C; Monitor Module is -20°C to
                 49°C.

 Comments:

     EPA and many states require detection of 1 /8 inch of product, which is 0.32 cm.  This
     detector is reusable.
                                                                                   On* Piui Corporation
                                                                                   1955 Srxmw Rd., Sulto 100
                                                                                   Northbrook, IL 80082
                                                                                   Til: (708) 49B-08B5
                                               Evduitor:  Undirwrittra Uboritorin Inc.


                                               Dili of iviluition: 12-17411
                                                                                                                                                  120

-------
                               Patriot Senior* & Controls Corp.

                                  7021 Digital Tank Gauge
                           AUTOMATIC TANK GAUGING SYSTEM

Certification:          Leak rate of 0.2 gallon per hour with P0  = 99.96% & PFA = 0.044%.

L«ak Threshold:        0.1 gallon per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, and solvents.

Capacity:              The maximum tank capacity is 15,000 gallons.
                      The tank must b« 10% to 95% full.

Waiting Time:         Minimum waiting time between product delivery and test data collection
                      must be 2 hours.
                      There must be no dispensing or product delivery during the test waiting
                      time.

Test Period:           The minimum data collection time must be 4 hours.
                      Test data must be acquired and recorded by the 7021 controller.
                      Leak rate calculated from data determined to be statistically valid.

Temperature:          Minimum of 1 resistance temperature detector must be used to determine
                      the average temperature of the stored product.

Water Sensor:         A water sensor must be used to detect water incursion.
                      Minimum water level detectable in the tank is 0.947 inches.
                      Minimum detectable  water level change is 0.0254 inches.

Calibration:            Temperature sensors and probe must be checked and calibrated annually in
                      accordance with manufacturer's instructions.

Comments:            This equipment was not evaluated using  manifolded tanks.
                      This equipment tests only that portion of the tank which contains product.
                      As the product level is lowered, the leak  rate in a leaking  tank decreases
                      (due to lower head pressure).
                      This equipment was originally manufactured by MagneTek (Patriot's
                      predecessor).
                      This'system is identical to API Ronan's X-76 ETM ATGS.
Patriot Sarwora & Controls Corp.
1080 N. Crook* Ro«d
Ctawton. Ml  48017-1097
Tal: (810)436-0700
Evatoator: Kan Wricox Assoeiatas


Data of Evaluation: 02-O7-91
                                            121
                                                                                Patriot Sensors & Controls Corp.

                                                                                   7021 Digital Tank Gauge
                                                                                                                                                                              DRAFT
                                                                            AUTOMATIC TANK GAUGING SYSTEM

                                                  Certification:          Uak rate of 0.1 gallon per hour with PD = 95.34% and Pw = 4.66%.

                                                  Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                                                                       system exceeds this threshold).

                                                  Applicability:          Gasoline, diesel, aviation fuel, and solvents.

                                                  Capacity:             The maximum tank capacity is 1 5,000 gallons.
                                                                       The tank must be 10% to 95% full.

                                                  Waiting Time:         Minimum waiting time between product delivery and test data collection
Test Period:



Temperature:


Water Sensor:



Calibration:


Comments:
                                                                      iii    i/ o lwu.
                                                                      There must be no dispensing or product delivery during the test waiting
                                                                      time.

                                                                      The minimum data collection time must be 4 hours.
                                                                      Test data must be acquired and recorded by the 7021 controller.
                                                                      Leak rate calculated from data determined to be statistically valid.

                                                                      Minimum of 1 resistance temperature detector must be used to determine
                                                                      the average temperature of the stored substance.

                                                                      A water sensor must be used to detect water incursion.
                                                                      Minimum water level detectable in the tank is 0.947 inches.
                                                                      Minimum detectable water level change is 0.0254 inches.

                                                                      Temperature sensors and probes must be checked and calibrated annually in
                                                                      accordance with manufacturer's instructions.

                                                                      This equipment was not evaluated using manifolded tanks.
                                                                      This equipment only tests that portion of the tank which contains product.
                                                                      As the product level is lowered, the leak rate in a leaking tank decreases
                                                                      (due to lower head pressure).
                                                                      This equipment was originally manufactured by MagneTek (Patriot's
                                                                      predecessor).
                                                                      This system is identical to API Ronan's X-76  ETM ATGS.
Patriot Saiuora & Controls Corp.
1080 N. Crooka Road
Clawaon, Ml  48017-10*7
Tal: (BIO) 43S-0700
Evakiator: Kan Wilcox Aeioclataa


Data of Evaluation:  0247-91
                                                                                                                                                    122

-------
                                     -   PermAiert

                           PAL-AT Models AT20C. ATSOC. AT4OK
                                    AGW Sensor Cable

                     LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:

    Output type:

    Sampling frequency:
    Operating principle:

Test Results':
qualitative for presence of product
quantitative for location
continuous
capacitance change


            Commercial Gasoline
1/3 MER"
1348ft.
100
9.92
1.0
2.03
116.3
Not det.
Not det.
2/3 MER
2644 ft.
100
6.25
1.0
1.13
64.8
Not det.
Not det.
MER
3982 ft.
100
21.28
1.0
5.00
286.1
5.1
295.6
    Accuracy (%)
    Response time (min)
    Recovery time (min)
    Product activation height (cm)
    Detection length (cm)
    Lower Detection Limits:
         Product act. height (cm)
         Detection length (cm)

    •   at a flow rate of 0.14 gal/hr in test chamber
    • •  MER is Maximum Effective Range, the longest length of sensor cables and/or Jumper
         cables that can be connected to form a leak detection network.

 Specif (city Resorts:

    Activated:        dtesel fuel, synthetic fuel, home heating oil #2, water

 Manufacturer'* Specifications:
 Comments:   EPA and many states require detection of 1 /8 inch of product, which is 0.32 cm, for
              ground water monitoring. The test procedures used were those in Carnegie Mellon
              Research Institute's 'Test Procedures for Third Party Evaluation of Leak Detection
              Methods: Cable Sensor Liquid Contact Leak Detection Systems': Final Report -
              November  11,1991.  Evaluation also covered quantitative leak location.
 f>
-------
                                         PermAlert

                           PAL-AT Model* AT20C. AT50C. AT40K
                      with PHFW Hydrocarbon Probe and Type 2 Senior

                     LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
    Output type:
    Sampling frequency:
    Operating principle:

Tost Results:
    Accurscy(%)
    Detection time(min:sec)
    Call Timg fmin;S££l
    Lower detection limit(cm)
qualitative
continuous
product soluble
    Commercial
    Gasoline
    100
    14:39
    Ui* AMI
    .-»• *-.ff>
    0.01
                                                   Synthetic
100
08:45
U*t* A«
*•••<*+ r-iff
0.01
Specificity Results:
    Activated:
                 commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, synthetic
                 gasoline, xylene(s).         	                            .
Manufacturer'* Specification*:

    Operating temperature range is 0°F to 90°F.

Comments:

    EPA and many states require detection of 1/8 inch of product, which is 0.32 cm. This
    detector is not reusable.
PcrmAlert
7720 North Lehiflh Avanua
Mitel, IL 80714-3491
Tel: (708) 980-2190
             Evaluator: Carnagia Mallon Raaaarch Institute


             Date of Evaluation: 9-15-82
                                            125
                                                                                                                       PermAlert

                                                                                                          PAL-AT Models AT20C. AT50C. AT40K
                                                                                                              TFH Hydrocarbon Sensor Cable

                                                                                                    LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                                                                                                                   DRAFT
                                                                                                             Detector:
                                                              Output type:

                                                              Sampling frequency:
                                                              Operating principle:

                                                          Test Results':
                         qualitative for presence of product
                         quantitative for location
                         continuous
                         capacitance change
                                                                                                                                                      Commercial Gasoline
1/3 MER"
1368ft.
100
3.40
>60
0.65
27.7
Not det.
Not det.
2/3 MER
2685 ft.
100
7.48
>60
1.33
56.8
Not det.
Not det.
MER
4046ft.
100
16.21
>60
3.53
150.4
3.6
152.9 .:
Accuracy (%)
Response lime (mini
Recovery time (min)
Product activation height (cm)
Detection length (cm)
Lower Detection Limits:
    Product act. height (cm)
    Detection length (cm)

*   at a flow rate of 0.16 gal/hr in test chamber
*•  MER is Maximum-Effective Range, the longest length of sensor cables and/or jumper
    cables that can be connected to form a teak detection network.
                                                                               Specificity Results:

                                                                                   Activated:
                                                                                   •Not activated:
                                                                               diesel fuel, synthetic fuel, home heating oil #2
                                                                               water-
                                                                                                             Manufacturer's Specifications:
                                                                                                             Comments:   EPA and many states require detection of 1/8 inch of product, which is 0.32 cm, for
                                                                                                                          ground water monitoring. The test procedures used were those in Carnegie Mellon
                                                                                                                          Research Institute's 'Test Procedures for Third Party Evaluation of Leak Detection
                                                                                                                          Methods: Cable Sensor Liquid Contact Leak Detection Systems': Final Report -
                                                                                                                          November 11, 1991. Evaluation also covered quantitative teak location.
                                                          ParmAlart
                                                          7720 North Lehigh Avenue
                                                          Nilea. IL 60714-3491
                                                          Tel: (708) 986-2190
                                      Evaluator: Carmgia Mallon Raaaarch Institute


                                      Data of evaluation: February 11, 1992
                                                                                                                                                        126

-------
                                       FermAieri

                          PAL-AT Modela AT20C. AT60C. AT40K
                                 PHL Hydrocarbon Sanaor

                          LIQUID-PHASE INTERSTITIAL DETECTOR
                                                                         UK API
Detector:
    Output type:
    Sampling frequency:
    Operating principle:
       qualitative
       continuous
       electrical conductivity
Test Results*:
                                  Cemmsrcie!
                                  Gasoline
    Accuracy (%)                  100
    Response time (min)            1.13
    Recovery time (min)            8.83
     Product activation height (cm)   0.53
     Lower Detection Limit (cm)      0.38

     •   at a flow rate of 0.13 gal/hr in a 4.8 cm diameter test chamber
 Specificity Result*:

     Activated:
     Not Activated:
diesel fuel, synthetic fuel, home heating oil #2
water
 Manufacturer's Specifications:
 Comments-   The test procedures used were those in Carnegie Mellon Research Institute's "Test
 Comrr-nts.   T^WKjn^ ^ ^ ^^ ^ ^ ^^^ Mothod8. pojnt SensQr L,qu,d

              Contact Leak Detection Systems": Final Report - November 1 1 , 1 SSI .
  PermAUrt
  772O North Uhlgh Avtnut
  Mai, It 6071+-34»1
  fell (70S) 908-2190
                          EvikJtton Cwntol* Mtllon R«»«wch Iratitut*


                          DIM of «v«lu«tfon: Ftbrutiy E, 1982
                                             127
Detector:

    Output type:
    Sampling frequency:
    Operating principle:

Test Results*:
                                                                                                                              ParmAlert

                                                                                                                   TankWatch Models PHM10, PHMS
                                                                                                                  Combination Hydrocarbon/Water Probe

                                                                                                                LIQUID-PHASE INTERSTITIAL DETECTOR
                                                                                                                                         qualitative
                                                                                                                                         continuous
                                                                                                                                         electrical conductivity
                                                                                                                 Accuracy (%)
                                                                                                                 Response time (min)
                                                                                                                 Recovery time (min)
                                                                                                                 Product activation height (cm)
                                                                                                                 Lower Detection Limit (cm)
                                                                                                                        Commercial
                                                                                                                        Gasoline
                                                                                                                        100
                                                                                                                        0.30
                                                                                                                        1.97
                                                                                                                        0.18
                                                                                                                        0.56
                                                  Water
                                                  100
                                                  1.68
                                                  <1
                                                  0.80
                                                  1.93
     •   at a flow rate of 0.13 gal/hr in a 4.8 cm diameter test chamber

 Specificity Results:

     Activated:        diesel fuel, synthetic fuel, home heating oil #2

 Manufacturer's Specifications:


 Comments:   The test procedures used were those in Carnegie Mellon Research Institute's "Test
             Procedures for Third Party Evaluation of Leak Detection Methods: Point Sensor Liquid
             Contact Leak Detection Systems": final Report - November 11,1991.
 PtrmAlirt
 7720 North Uhlgh Avinut
 NilM. IL 60714-3491
 T«l: (701) 808-2190
                                                                                                                                                            Ev«lu«tor: C«n*0i« Mtttort RMuroh Inititutt


                                                                                                                                                            DIM of «v«luitlon: JUM 16,19*2
                                                                                                                                                         128

-------
Detector:

    Output type:
    Sampling frequency:
    Operating principle:

Test Results':
                                          P«rmAlert

                              TankWatch Model* PHM10, PHMS
                                     Hydrocarbon Probe

                           LIQUID-PHASE INTERSTITIAL DETECTOR
         qualitative
         continuous
         electrical conductivity
Accuracy (%)
Response time (min)
Recovery time (min)
DMJJ..M* «»*!>.A»I«« U«I_I.* J_«~t

Lower Detection Limit (cm)
                                   Commercial
                                   Gasoline
                                   100
                                   0.25
                                   2.33
                                   0.17
                                   0.38
     *    at a flow rate of 0.14 gal/hr in a 4.8 cm diameter test chamber

Specificity Result*:
    Activated:
    Not Activated:
diesel fuel, synthetic fuel, home heating oil #2
water
Manufacturer'* Specifications:
Comment*:   The test procedures used were those in Carnegie Mellon Research Institute's "Test
             Procedures for Third Party Evaluation of Leak Detection Methods: Point Sensor Liquid
             Contact Leak Detection System**: Rnal Report - November 11, 1991.
                                                                                                                                Petro Vend. Inc.

                                                                                                                              SrteSentinel System
                                                                                                                         30-3206, -3207. -3210 Sensor*

                                                                                                               LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                          Detector:
     Output type:
     Sampling frequency:
     Operating principle:

 Test Result*:
                                                                                              Accuracy(%)
                                                                                              Detection time(hr:min:sec)
                                                                                              Fail rime (hr:min:sec)
                                                                                              Lower detection limit(cm)

                                                                                         Specificity Result*:

                                                                                              Activated:
qualitative
continuous
product permeable
                                   Commercial
                                   Gasolina
                                   100
                                   00:01:41
                                   07:28:44
                                   0.02
                                                                                                                                             Synthetic
                     100
                     00:05:14
                     00:18:36
                     0.02
                 commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, synthetic
                 gasoline, xylene(s).

Manufacturer's Specifications:

    Conductive polymer.

Comments:

    EPA and many states require detection of 1/8 inch of product, which is 0.32 cm. This
    detector is reusable. The third party evaluators identified these sensors as identical to One
    SvS±fTtl°n ? M.°del8 ^f01 8nd 1°°-4001 L8ak Edoe Hydrocarbon Leak Monitor
    System. The evaluation was abbreviated and used some data from the One Plus system
    evaluation.
PormAlert
7720 North L«h!(}h Awnu*
Nilgs. 1160714-3481
T.I: (708) 988-2190
                          Ev.lu.tor: Cmwgi* M»tlon Research Inititut*


                          D.t. of «v«kjitlon: JUIM 16, 1882
                                                                                                              P«tro V»nd, Inc.
                                                                                                              6900 Sinti Ft Drive
                                                                                                              Hodgkiiu, IL 60525
                                                                                                              Td: (708) 485-4200
                                                                                                                                   Ev.lu.tor: Underwriter. Ubontoriu, Inc.


                                                                                                                                   DIM of Evduition: 12-10-82
                                            129
                                                                                                                                                         130

-------
Detector:

    Output type:
    Sampling frequency:
    Operating principle:

Test Results":
                                      Retro Vend, inc.

                         Petrosentry IV. Potrosentry VIII. SHeSentinel
                                       Liquid Sensor

                          LIQUID-PHASE INTERSTITIAL DETECTOR
qualitative
continuous
thermal conductivity
                                  Commercial
                                  Gasoline
                                  100
                                  0.51
    Accuracy (%)
    Response time (min)
    Recovery time (min)            < 1
    Product activation height (cm)   0.35
    Lower Detection Limit (cm)      0.76

    •   at a flow rate of 0.14 gal/hr in  a 4.8 cm diameter test chamber

Specificity Results:

    Activated:        diesel fuel, synthetic fuel, home heating oil #2, water

Manufacturer's Specifications:


Comments:   The test procedures used  were those in Carnegie Mellon Research Institute's "Test
             Procedures for Third Party Evaluation of Leak Detection Methods: Point Sensor Liquid
             Contact Leak Detection Systems": Final Report - November 11, 1991.
 Petro Vend. Inc.
 flSOO Sinu Fa Dr.
 Hodgklna, IL 60525-8909
 Tel: 1700) 485-4200
                      Evaluitor:  Carnegie Mellon Reiearch Inititute


                      Date of Evaluation: 10-16-92
                                             131
                                                                                                                     Petro Vend. Inc.

                                                                                                         Petrosentry IV, Petrosentry VIII, StteSantlne
                                                                                                                 Universal Reservoir Sensor

                                                                                                          LIQUID-PHASE INTERSTITIAL DETECTOR
                                                                     DRAFT
                                                                                                              Detector:
Output type:
Sampling frequency:
Operating principle:
Test RstuhV:
Accuracy (%)
Response time (min)
Recovery time (min)
Product activation
height (cm)
qualitative
continuous
float switch
50 wt% Ethylens fllyeo!
in water
Up Down
100 100
19.62 16.86
<1 <1
20.9 5.90
                                                                                                                                   30 wt% Calcium chloride
                                                                                                                                   in water	.
                                                                                                                                   llfi
                                                                                                                                   100
                                                                                                                                   17.77
                                                          Down
                                                          100
                                                          15.91
                                                                                                                                                                 20.5    5.95

                                                                                                                   • at a flow rate of 0.21 gal/hr in test chamber

                                                                                                               Specificity Results:

                                                                                                                   Not applicable

                                                                                                               Manufacturer's Specifications:


                                                                                                               Comments:

                                                                                                                   This point sensor is intended to monitor the level or either ethylene glycol or calcium chloride
                                                                                                                   solutions in the interstitial or annular space of a double-walled tank, by triggering an alarm if
                                                                                                                   any significant gain or loss of solution occurs.  Evaluation was performed using procedures
                                                                                                                   from Carnegie Mellon Research Institute's "Test Procedures for Third Party Evaluation of Leak
                                                                                                                   Detection Methods: Point Sensor Liquid Contact Leak Detection Systems": Final Report -
                                                                                                                   November 11, 1991, modified to accommodate the intended purpose.
P»tro Vend, Inc.
0900 Santa Fa Dr.
Hodokint, IL60535-9M9
Tel: (708) 485-4200
                                                                                                                                                                  Evahiator: Carnegie M«Hon Retearch Irutitute


                                                                                                                                                                  Cat« of Evaluation: 10-15-92
                                                                                                                                                           132

-------
 Detector:

     Output type:
     Sampling frequency:
     Operating principle:

 Test Results*:
                                       Petro Vend, Inc.

                          Petrosentry IV, Petrasentry VIII, SfteSentinel
                                    Universal Sump Sensor

                           LIQUID-PHASE INTERSTITIAL DETECTOR
qualitative
continuous
float switch
V*
     Accuracy (%)
     Response time (min)
     Recovery time (min)
     Product activation height (cm)
     Lower Detection Limit (cm)
    Commercial
    Gasoline
    100
    8.32
    <1
    3.37
    3.97
     *   at a flow rate of 0.20 gal/hr in a 7.8 cm diameter test chamber

Specificity Results:

     Activated:        diesel fuel, synthetic fuel, home heating oil *2, water

Manufacturer's Specifications:


Comments:  The test procedures used were those in Carnegie Mellon Research Institute's "Test
             Procedures for Third Party Evaluation of Leak Detection Methods: Point Sensor Liquid
             Contact Leak Detection Systems': Final Report - November 11, 1991.
                                                                                                                    Petro Vend, Inc.

                                                                                                                   Petrosentry TLD III


                                                                                                   VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                                                                                                                     D
                                                                              Detector:
Output type:          qualitative
Sampling frequency:    continuous
Operating principle:    metal oxide semiconductor
                                                                                                             Test Result*:
Accuracy (%):                 100
Detection Time (min:sec):       00:05
Fall Time (mirvsec):            04:12
Lower Detection Limit (ppm):    12.5
                                                                                2-Methvlbutane
                                                                                    100
                                                                                    00:16
                                                                                    00:42
                                                                                    12.5
                                                                              Specificity Results:

                                                                                  Activated:    Benzene, n-Butane, n-Hexane, Isobutane, 2-Methylpentane, Toluene

                                                                              Manufacturer's Specifications:

                                                                                  Maximum Wire Distance:   500 ft using 18 AWG

                                                                              Comments:
                                                                                                                                          Sii\
€                                                                                                                                            f\
                                                                                                                                         ..J> *
Potro V»nd, Inc.
89OO Santa ft Dr.
Hodgkirn, IL 90525-9909
Tol: (708) 485-4200
                     Evduitor: C«n«gi« Mellon R«»rch Institute


                     D
-------
                                                                                 ACT
Detector:

Output type:
Sampling frequency:
Operating principle:

Test Results:
                                     Feiro Vend, 'me.

                                       StteScntinel
                              Smart Module and Vapor Sensor

                    VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
    qualitative
    continuous
    metal oxide semiconductor
Accuracy* (%):
Detection Time* (min:sec):
Fall Time* (min:sec):
Lower Detection Limit (ppm):
• for tests conducted with 1000 ppm of test gas
Commercial Synthetic
Gasoline Gasoline
100 100
00:05 00:07
06:30 03:35
10 10
JM
100
00:10
04:26
10
Specificity Results:

    Activated:
Commercial gasoline. Synthetic gasoline, JP-4 Jet Fuel, n-Hexane, Toluene,
Xylene(s)
Manufacturer's Specifications:
 Comment*:

     The t«st procedures used were those in Radian Corporation's draft report "Development of
     Procedures to Assess the Performance of External Leak Detection Devices: Vapor-Phase
     ASTM-Formatted Methods," June 29, 1990.
 Potto V«nd, Inc.
 6900 S«nt« Fa Dr.
 Hodgklra, It 80525-S809
 Til: (708) 485-4200
                                  Ev«lu«tor: Camtgfo M«Hon Rolufch Inititute


                                  Dcto of Evaluction: 04-16-92
                                            135
                                                                                                                        PRSumsrcstor Company, ine.

                                                                                                                        LDE 700, IDE 740. LDE 9000
                                                                                                                  Sensor Probe Models 9-901,9-902,9-903

                                                                                                                  LIQUID-PHASE INTERSTITIAL DETECTOR
                                                                                                                                                                               ip^h. m*m.  
-------
                                     Raychem Corporation

                              TraceTek Alarm and Locator Modules
                                  TT502 Fuel Sensing Cable

                      LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
 Detector:
     Output type:

     Sampling frequency:
     Operating principle:

 Test Results':
         qualitative for presence of product
         quantitative for location
         continuous
         electrical conductivity
                                           Commercial Gasoline
1/3 MER"
334m
100
22,11
Not app.
1.53
61
Not det.
Not det.
2/3 MER
665m
100
17,13
Not app.
1.53
61
Not det.
Not det.
MER
995 m
100
19.42
Not app.
1.53
61
0.77
10
     Accuracy (%)
     Response time (mini
     Recovery time (min)
     Product activation height (cm)
     Detection length (cm)
     Lower Detection Limits:
         Product act. height  (cm)
         Detection length (cm)

     •   at a flow rate of 0.17 gal/hr in test chamber
     **  MER is Maximum Effective Range, the longest length of sensor cables and/or jumper
         cables that can be connected to form a leak detection network.
Specificity Results:

     Activated:
     Not activated:
diesel fuel, synthetic fuel, home heating oil #2
water
Manufacturer's Specifications:


Comments:  EPA and many states require detection of 1/8 inch of product, which is 0.32 cm, for
             ground water monitoring.  The test procedures used were those in Carnegie Mellon
             Research Institute's "Test Procedures for Third Party Evaluation of Leak Detection
             Methods: Cable Sensor Liquid Contact Leak Detection Systems": Final Report -
             November 11; 1991.  Evaluation also covered quantitative leak location.
Rsychmn Corporation
300 Constitution Dr.
Menlo Park, CA 94025-1184
T«l: (415) 381-3333
                              Evaluator: Carnegie Motion Research Institute


                              Date of evaluation: May 15.1992
                                            137
                                                                                                                               Schuster Instruments

                                                                                                                           Tel-A-Leak 1 (Overfilled Test)
                       VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD=99.86% & PFA=0.14%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil #4, solvents and waste oil.

Capacity:             The maximum tank capacity is 15,000 gallons.
                      The tank must be 100% full.

Welting Tims:         Minimum waiting time between product delivery to the tank and test data
                      collection must be 6 hours.
           	      Minimum wsiiirig tims tstwsen "tupping off" and test data eoiieoiiufi must
                      be  1 hour.

Test Period:           The minimum data collection time must be 1 hour.
                      Test data is acquired and recorded manually and by a  computer.
                      Leak rate calculated from average of the last 10 consecutive 6 minute
                      readings.
                      There must be no dispensing or product delivery during the test.

Temperature:          A minimum of 10 temperature sensors must be used to determine the
                      average temperature of the stored product.

Ground Water:         Depth to the  water table present in the backfill must be determined, and if
                      it is above the bottom of the tank, product level must be adjusted to
                      provide 2-4 psi net pressure on the bottom of the tank during the test.

Calibration:            Sensors must be checked and calibrated annually.

Comments:            This system was not evaluated for use in manifolded tanks.
                                                                                                                Schuster Instrument*
                                                                                                                211 East Grove Street
                                                                                                                Kowkowlin, Ml 48831
                                                                                                                Tel: (517) 084-8638
                                                                                                                                                  Ev«tuetor: W. A. Klbbe & Associates


                                                                                                                                                  Date of Evaluation: 11-2S-9O
                                                                                                                                                            138

-------
                                Simmon* Sirv«y Corporation

                                   SIR 5.7 (quantitative)


                 STATISTICAL INVENTORY RECONCILIATION TEST METHOD

Certification:          Method is certified to detect a 0.1 gph leak rate with PD=99.0% and
                     PFA=1.0%.

Leak Threshold:       A teak is declared when leak rate exceeds 0.05 gallon oar hour.

Applicability:          Motor vehicle fuels.

Tank Capacity:       Maximum tsnk capacity shall not exceed 18,000 gallons.

Data Requirement:    Minimum of 30 days of product level and flow through data.

Comments:           All 41 data sets were analyzed with conclusive  results.

                     The median monthly throughput for tanks used  in the evaluation was 7,000
                     gallons.

                     Leak rates ranging from 0.05 to 0.2 gph were used in the evaluation.

                     This evaluation did not include data from manifolded tanks.

                      Data sets used in this evaluation were supplied by the evaluator.
  Simmons Sirvay Corporation
  9550 Forcil Lam, St«. 720
  Dallal, TX 75243-5934
  Tol: 1800) 848-8378
Evthiitor: S.S.G. Aaiociataa


Data of Evaluation: 12-15-92
                                             139
                                                                                                                                                                                        DR;:
                                                                                       S.I.R. SfltemstkHia!, inc.

                                                                          MricheH'a Sin Program v.2.6 12-13-91 (Quantitative)


                                                                      STATISTICAL INVENTORY RECONCILIATION TEST METHOD

                                                     Certification:          Method is certified to detect a 0.1 gph leak rate with PD-98% and
                                                                          PFA-2%.

                                                     Leak Threshold:       A leak is declared when leak rate exceeds 0.05 gallon per hour.

                                                     Applicability:          Gasoline, diasa!, aviation fuel, and fuel oil #4.

                                                     Tank Capacity:        Maximum UST capacity shall not exceed 18,000 gallons.

                                                     Data Requirement:     Minimum of 32 days of  product level and flow through data.

                                                     Comments:           Of the 41 data sets presented for evaluation, only 24 "best* analyses were
                                                                          returned. 17 data sets were not analyzed.

                                                                          The median monthly throughput for tanks used in this evaluation was 6313
                                                                          gallons.

                                                                          Leak rates of 0.049 to 0.21  gph were used in the evaluation.

                                                                          Data sets used in this evaluation were supplied by the evaluator.

                                                                          This evaluation did not include data from manifolded tanks.
S.I.R. Intarnational, Ino.
2505 N. Moora Avo.
Moora, OK 73ISO
(800)793-1900
Evaluator: Kan WHoox Anoclataa


Data of Evaluation 01-27-92
                                                                                                                                                         140

-------
                                                                           DRAFT
                                      Sir Phoenix. Inc.

                                 SIR MONITOR (quantitative)


                  STATISTICAL INVENTORY RECONCILIATION TEST METHOD

Certification: •          Method is certified to detect a 0.1 gph leak rate with P0 = 99.0% and
                      P,A>1%.

Leak Threshold:        A leak is declared when leak rate exceeds 0.05 gallon per hour.

Applicability:          Gasoline, diesel, aviation fuel, and fuel oil *4.

Tank Capacity:        Maximum tank capacity shall not exceed 18,000 gallons.

Data Requirement:     Vendor requires 90 days of product level and flow through data before
                      making the first evaluation;

Comment*:            Of trie 41 data 8618 pioamiimi fwf evaluation, 5 W6f6 inconclusive.

                      The median monthly throughput for tanks used in the evaluation was
                      14,600 gallons.

                      Leak rates of 0.05, 0.1, and 0.2 gph were used in this evaluation.

                      Data sets used in this evaluation were supplied by the vendor.

                      This evaluation did not include data from manifolded tanks.
 Sir Phoenix, Inc.
 P.O. Box 588
 Lawroncebuffl, TN 38464
 (615)762-3300
Evahlitor: Nlthwi Adams. Mddlg TN SUM Univ.


Data of Evaluation 11-05-92
                                            141
                                                                                                           Softest, Inc

                                                                                        Solicit AMay Tank Tegrity Tester, S-3 (Overfilled Test)
                                                                                           VOLUMETRIC TANK TIGHTNESS TEST METHOD

                                                                    Certification:          Leak rate of 0.1 gallon per hour with P0 = 99% and P,A = 1%.

                                                                    Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                                                                                         system exceeds this threshold).

                                                                    Applicability:          Gasoline, diesel.

                                                                    Capacity:             The maximum tank capacity is 15,000 gallons.
                                                                                         The tank must be 100% full.

                                                                    Wafting Tims:         Minimum waiting time between product delivery to ths tank:and test data
                                                                                         collection must be 10 hours.
                                                                          __ _ .  _         Minimum v*joi»!r»n *ima t\A*MuraAn H*nnn!nn nff*-«n*4 *A0* *4«t*a *»nlla***inn nia»*>
                                                                                         be 2 hours.

                                                                    Test Period:           The minimum data collection time must be 1.5 hours.
                                                                                         Test data is acquired and recorded manually and by a strip chart recorder.
                                                                                         Leak rate is calculated from data of last 1.5 hours of test period.
                                                                                         There must be no dispensing or product delivery during the test.

                                                                    Temperature:          A minimum of 3 thermistors must be used to determine the average
                                                                                         temperature of the stored hazardous substance.

                                                                    Ground Water:        Depth to the water table present in the backfill must be determined, and if
                                                                                         it is above the bottom of the tank, product level  must be  adjusted to
                                                                                         provide 2-4 psi net pressure on the bottom of the tank during the test.

                                                                    Calibration:           Level sensors must be calibrated before each test.
                                                                                         Temperature sensor must be calibrated annually.

                                                                    Comments:       1.   This equipment was not evaluated using manifolded tanks.
SoilUit, Inc.
86 Albracht Drivo
P. 0. Box 8004
lak« Bluff, IL 60044-8004
Tel: (800) 323-1242
                                                                                                                                                              Evaluator: Law EnginMring Induttrial Saivicaa
                                                                                                                                                              OHM of Evaluation: 11-28-90
                                                                                                                                                      142

-------
                                            p. few.

                            Store Vision Version E.2 (qualitative)
                                                                       DRAFT
                                                                                                                                          uRAF
                 STATISTICAL INVENTORY RECONCIUATION TEST METHOD

Certification:          Method is certified to detect a 0.2 gph leak with a P0-95.7% and
                     PFA-O*.

Leak Threshold:       A leak is declared when leak rate exceeds 0.0834 gallons per hour.

Applicability:          Gasoline, diesal, aviation fuel, and fuel oil *4.

Tank Capacity:        Maximum tank capacity may not exceed 12,000 gallons.

Data Requirement:     Minimum of 29 days of product level and flow through data are required.

Comments:           Of the 120 data sets presented for evaluation, 32 were inconclusive.

                     The median monthly throughput for tanks used in this evaluation was 8,097
                     gallons.

                     A single leak rate of 0.2 gph was used in this evaluation.

                     This evaluation did not include data from manifolded tanks.

                     Data sets used in this evaluation were supplied by the evaluator.
                                                                                                     i ank Automation, Inc.

                                                                                     Automated Precision Tank Testing System (APTT System)
                                                                                                      R-2 OverfiHed Test

                                                                                         VOLUMETRIC TANK TIGHTNESS TEST METHOD

                                                                   Certification:         Leak rate of 0.1 gallon per hour with P0-99% & PFA-1%.

                                                                   Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                                                                                       system exceeds this threshold).

                                                                   Applicability:         Gasoline, diesel, aviation fuel, fuel oil #4, fuel oil #6, solvents, waste oil,
                                                                                       and other compatible products.

                                                                   Capacity:            The maximum tank  capacity is 15,000 gallons.
                                                                                       The tank must be 100% full.

                                                                   Waiting Time:        Minimum waiting time between product delivery and test data collection
                                                                                       must be 10.5 hours.
                                                                                       Minimum waiting time between "topping off" and test data collection must
                                                                                       be 2.5 hours.
                                                                                       There must ba  no dispensing or product delivery during the test waiting
                                                                                       time.

                                                                   Test Period:          The minimum data collection time must be 1 hour.
                                                                                       Test data must be acquired and recorded manually for level measurement
                                                                                       and by computer for temperature measurement.
                                                                                       Leak rate is calculated from the 1  hour test period.

                                                                   Temperature:         A total of 10 thermistors is used to determine the average temperature of
                                                                                       the stored product.

                                                                   Ground Water:        Groundwater presence is checked to a depth of 5 feet and test is performed
                                                                                       at product level of 66 inches above grade to ensure a minimum  1 psi
                                                                                       pressure at bottom of tank.

                                                                   Calibration:           Temperature and level sensors are calibrated annually.

                                                                   Comments:           This system was not evaluated using manifolded tanks.
 Sytcorp, Inc.
 1513 Huffman Road, Suit* 202
 aiminflham, AL3521S
 (205) 853-0004
Evaluator: Mdwnt Riaaaroh Inatituta


Data of Evaluation: 09-30-93
Tank Automation, Inc.
P.O. Box 1395
Wall, NJ 07719
Tal: (MI) 280-2233
Evaluator: WiWwood EngtiMaring


Data of Evaluation: 11-14-SO
                                           143
                                                                                                                                              144

-------
                             Tanknology Corporation International

                                         VacuTect
                                                                           DRAFT
Certification:
   NON-VOLUMETRIC TANK TIGHTNESS TEST METHOD

Leak rate of 0.1 gallon per hour with PD = 100% & PFA=0%.
Latk Threshold:   Air or water incursion (a leak is declared if any air or water incursion is
                 detected).

Applicability:      Gasoline, diesel, aviation fuel, fuel oil #4, and waste oil.

Capacity:         The maximum tank capacity is 75,000 gallons.
                 The tank must be more than 60% full.

Test Parted:      The minimum data collection time must be 2 hours if no water is detected prior
                 to or at the conclusion of the test.
                 »* wstsr tS wStsciGu prjo? tc or si m« conclusion Oi tus tsst, tho  riiinirfiuiTi ut&t
                 time is 4 hours. The actual test time must be calculated based on the tank size,
                 amount of water present in the  tank prior to the test, tank tilt, type of the water
                 sensor and its location.
                 Test data must be acquired and recorded by computer and audio cassette tape.
                 An inclinometer must be used to determine and record tank tilt.

Water Sensor:    A water sensor (at the lowest point of the tank) must be used to detect water
                 incursion. The type of water sensor, the minimum detectable water level, and
                 minimum detectable water level change for the sensor must be documented.

Ground Water:    Depth to the water table present in the backfill must be determined, and if it is
                 above the bottom of the tank, test time must be extended to allow sufficient
                 time to detect 0.1 gph incursion of water into the tank.

Vacuum:         The minimum vacuum at the bottom of the tank must be - 0.5 psi.

Comment:        - This test method may not be effective in some backfill because some backfill
                 (such  as clay) may plug a hole in the tank.
                 - This test method was not third-party certified using manifolded tanks.
                 - If the soil is saturated with product this test method may not detect air or
                 water incursion.  A well point in the backfill  may help identify presence of this
                 condition.
                 - During the third-party certification JP-4 was used.
Tanknologv Corporation
S25S HoHiMw
Hoiuton. TX 77O40
Tel: (800) 888-8683
                                          Evatuator: K*n WMoox Aeaodatae
                                          DM* of Evaluation: 09-08-92
                                           145
                                                                                                                      Tanknology Corporation International

                                                                                                                          VacuTect 01 Tank System
                                                                                                                                                                   DRAFT
                                                                                          Certification:

                                                                                          Leak Threshold:


                                                                                          Applicability:

                                                                                          Capacity:


                                                                                          Test Period:
                                                                                         Water Sensor:
                                                                                         Ground Water:
    NON-VOLUMETRIC TANK TIGHTNESS TEST METHOD

 Leak rate of 0.1 gallon per hour with P0=97.6% & P,A=0%.

 Air or water incursion (a leak is declared if any air or water incursion is
 detected).

 Waste oil.

 The maximum tank capacity is 1,500 gallons.
 The tank must be more than 5% full.

 The minimum data collection time must be 2 hours if no water is detected prior
 to or at the conclusion of the test.
 If water is detected prior to or at the conclusion of a test, the minimum test time
 is 4 hours.  The actual test time must be determined based on the tank size,
 amount of water present in the tank, tank tilt, type of the water sensor and its
 location.
 Test data must be acquired and recorded by computer and audio cassette tape.
 An inclinometer must be used to determine and record tank tilt.

 A water sensor (at the lowest point of the tank) must be used to detect water
 incursion. The type of water sensor, the minimum detectable water level, and
 minimum detectable water level change for the sensor must be recorded in the
test report.

 Depth to the water table present in the backfill must be  determined,  and if it is
above the bottom of the tank, test tims must be extended to allow sufficient
time to detect 0.1  gph incursion of water into the tank.
                                                                                         Vacuum:
                                                                                                          The minimum vacuum at the bottom of the tank must be at 0.5 psi below the
                                                                                                          atmospheric pressure.
                                                                                         Comment:
                                                                                                          - This test method may not be effective in some backfill because some backfill
                                                                                                          (such as clay) may plug a hoto in the tank.
                                                                                                          - This test method was not third-party certified using manifolded tanks.
                                                                                                          - If the soil is saturated with product this test method may not detect air or
                                                                                                          water incursion. A well point in the backfill may help identify presence of this
                                                                                                          condition.
                                                                                                          - During the third-party certification Fuel oil #4 was used.
                                                                                                          Tanknology Corporation
                                                                                                          5255 Hollieter
                                                                                                          Houaton, TX 7704O
                                                                                                          Tel: (800) 888-8563
                                                                                                                          Evduitor: Ken WHcox An ociatoi
                                                                                                                                           DM* of Evaluation: 10-28-91
                                                                                                                                                    146

-------
                            Tanknology Corporation International

                                         TUJ-1
                                                                             DRAFT
                              LINE TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD=99.5% and PFA=0.5%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, and aviation fuel.

Specification:         System tests fiberglass and steel piping.
                     The piping system volume must not exceed 50 gallons.
                     Tests are conducted at 150% of the line operating pressure.
                     Mechanical line leak detector must be removed from the pipeline system
                     being tested.

Waiting Time:         Testing may begin immediately after the test equipment is installed in the
                     line. Test may not be ended until the pass/fail criteria set by the
                     manufacturer  has been met.

Tait Ptriod:          The data collection time for the test is 30 minutes to 6 hours.
                     Pipe deflection, vapor pockets, and large temperature differences may
                     produce inconsistent readings, testing to continue until stable conditions are
                     present.
                     Test data is acquired and recorded manually.
                                                                                    Tide! Engineering. Inc.
                                                                                                                        DRAFT
                                                             Tidal Environmental Monitoring System,  EMS 2000. 3000. & 3500 Series
                                                                               ProbM #401-0009 & #401-0010

                                                                             AUTOMATIC TANK GAUGING SYSTEM

                                                  Certification:          Leak rate of 0.2 gallon per hour with P0=96.2% & PFA=3%.

                                                  Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                                                                       system exceeds this threshold).

                                                  Applicability:          Gasoline, diesel, aviation fuel, fuel oil, and solvents.

                                                  Capacity:             The maximum tank capacity is 15,000 gallons.
                                                                       The tank must contain at least 15 inches of product.

                                                  Waiting Time:         Minimum waiting time between product delivery to the tank and test data
                                                                       collection must be 2 hours.

                                                  Test Period:           The minimum data collection time must be 6 hours.
                                                                       Test data is acquired and recorded by the microprocessor contained within
                                                                       the EMS console.
                                                                       There must be no dispensing or product delivery during the test.

                                                  Temperature:          A minimum of five temperature sensors must be used to determine the
                                                                       average temperature of the stored substance.

                                                  Water Sensor:         A water sensor must be used to detect water incursion.
                                                                       Minimum water level detectable in the tank is  1.48 inches.
                                                                       Minimum detectable water level change is 0.035 inches.

                                                  Calibration:           Temperature  sensors and ultrasonic probe must be checked and calibrated
                                                                       annually in accordance with manufacturer's instructions.

                                                  Comments:           This equipment was not evaluated using manifolded tanks.
                                                                       This equipment only tests the portion of the tank that contains product.
                                                                       As the product level is lowered the leak rate in a leaking tank decreases
                                                                       (due to lower head pressure).
                                                                       EMS 2000 and 3000 Series are no longer manufactured by Tidal.
 TenknoloflY Corporation
 S2S5 HoNiiter
 Hourton. TX  77040
 Tel: 1-80O.888-8583
Evaluetor: Kin Wilcox Aaaooietee


Dtt« of Evaluation: 12/29/81
Tidal Engineering
2S15EwtB«ldlr»Ro«d
Carrotlton, TX 75OOB
Tal: (214) 416-8222
                                                                                                                                                                   Evaluitor: Kan Wilcox Aiioc!*te>
                                                      Data of Evaluation: 06-07-93
                                           147
                                                                                                                                                   148

-------
                                                                          DRAFT
                                 Tidal Engineering, Inc.
           Tidal Environmental Monitoring Systam. EMS 2000, 3000, & 3500 Series
                             Probe* #401 -0021 & #401 -0022

                          AUTOMATIC TANK GAUGING SYSTEM

Certification:         Laak rate of 0.2 gallon per hour with PD  = 99.91 % and Pw = 0.09%.

Leak Threshold:       0.1 gallon per hour (a leak is declared if the output of the measurement
                    system exceeds this threshold).

Applicability:         Gasoline, diesel, aviation fuel, fuel oil, and solvents.

Capacity:            The maximum tank capacity is 15,000 gallons.
                    The tank must be at least 15 inches full.

Waiting Time:        Minimum waiting time between product delivery to the tank and test data
                    nnHartinn must b* 2 hour*.                            	

Tut Period:          The minimum data collection time must be 6 hours.
                    Test data is acquired and recorded by the microprocessor contained within
                    the EMS console.
                    There must be no dispensing or product delivery during the test.

Temperature:         A minimum of 5 temperature sensors must be used to determine the
                    average temperature of the  stored substance.

Water Sensor:        A water sensor is used to detect  water incursion.
                    Minimum water level detectable in the tank is 1.48 inches.
                    Minimum detectable water level change is 0.03S inches.

Calibration:          Temperature sensors and ultrasonic probe must to checked and calibrated
                    annually in accordance with manufacturer's instructions.

Comment*:          This equipment was not evaluated using manifolded tanks.
                    This equipment only tests that portion of the tank that contains product.
                    As the product level is lowered, the leak rate in a leaking tank decreases
                    (due to lower head pressure).
                    EMS 2000 & 3000 Series are no longer manufactured by Tidel.
                                                                                                                                   [This page intentionally left blank.]
                                                                                                                                                                           DRAFT
 Tidel Engiixwing, Inc.
 2615E«tMtUluRo«d
 OrroHUn. TX  76O06
 T(H: (214)418-8222
                                             Evihiitor: Kon WHoox A>iod>t«
D
-------
                                        EMS-3500
                         With Monitoring W«N Probes Part 301-0641

                     LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                               Tidei Engineering

                                                                                                  EMS-3500
                                                                                       With Sheen Probe* Part 301-0687

                                                                               LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                                                                                                                              TT
                                                                                                                                                                                              Ff
Detector:
    Output type:           qualitative
    Sampling frequency:   continuous
    Operating principle:    Conductivity via resistor ladder network
                                                                                                             Detector:
                                                              Output type:
                                                              Sampling frequency:
                                                              Operating principle:
                                                                                                                                      qualitative
                                                                                                                                      continuous
                                                                                                                                      electrical conductivity/hydrocarbon sensitive polymer
Test Results:
                              Commercial
                              Gasoline
                              100
                              00:04
                              <01:00

                              0.32
Synthetic
Gasoline
100
00:07
<01:00

0.32
    Accuracy (%)
    Detection time(min:sec)
    Fall time(min:sec)
    Lower detection
      limit (cm)

Specificity Results:

    Activated(100%): commercial gasoline, n-hexane, diesel fuel, Jet-A fuel, toluene, JP-4 jet
                     fuel, toluene, synthetic gasoline, xylene(s).

Manufacturer's Specifications:
 Comments:

     EPA and many states require detection of 1/8 inch of product, which is 0.32 cm.
Test Results:
                              Commercial
                              Gasoline
    Accuracy (%)              100
    Detection time(m!n:sec)     07:45
    Fall time(min:sec)          18:01
    Lower detection limit (cm)  0.02

Specificity Results:
Synthetic
Gasoline
100
03:35
16:57
0.04
                                                              Activated(100%): commercial gasoline, n-hexane, diesel fuel, Jet-A fuel, toluene, JP-4 jet
                                                                               fuel, synthetic gasoline, xylene(s).

                                                          Manufacturer's Specifications:


                                                          Comments:

                                                              EPA and many states require detection of 1/8 inch of product, which is 0.32 cm.
 Tidel Engineering
 2615 Enl BeltUne Ro«d
 CatroHton, TX 75006
 Tel: (800) 878-7577
     Eveluetor: Cemegle Mellon Reeeerch Initltute


     O.!e of Evduetlon: 02-01-33
                                                                                                             Tidel Engineering
                                                                                                             2815 Eiit BeltUne Road
                                                                                                             Cerrollton, TX 75008
                                                                                                             Tel: (800) 878-7577
                                                                                                             Eveluetor: Cernegie Mellon Reieirch Inititute


                                                                                                             One of Evaluation: 01-31-93
                                             151
                                                                                                                                                        152


-------
                                      Tide! Engineering

                                         EMS-3500
                                TWel Detector No. 301-0762

                     LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
Output type: qualitative
Sampling frequency: continuous
Operating principle: electrical conductivity / hydrocarb
Ten Results:
Accuracy (%)
Detection time (min:sec)
Fall Time (min:sec)
Lower detection limit(cm)
Specificity Results:
Commercial
Gasoline
100
9:31
55:42
0.04

Activated: commercial gasoline, n-Hexane,
Synthetic
Gasoline
100
7:05
17:04
0.08

diesel fuel, Jet-j
                 gasoline, xylene(s).

Manufacturer's Specifications:

    Ground water probe used to detect free floating hydrocarbons in monitoring wells.
Comments:
EPA and many states require detection of 1/8 inch of product, which is 0.32
cm.
Tido! EnQinnrins
2815 Ent B»h Uiw Roid
CwfoHton, TX 75006
T«l: (800) 878-7877
                                   Evduuor: C«m«oi« Mttlon Riiurch tmtituM


                                   D«to of Ev.hj.tion: 03-18-93
                                            153
                                                                                                                                   Tide) Engineering

                                                                                                                   Tide! Detector No. 301-0324-001 and 301-0325-001


                                                                                                                   LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                              Detector:
Output type:
Sampling frequency:
Operating principle:
Test Results:


Accuracy(%)
Detection time(sec)
Fall Time (sec)
Lower detection
limit(cm)
qualitative
continuous
electrical

Commercial
Gasoline
100
2
1

0.16-0.32
conductivity

Synthetic
Gasoline
100
2
2

0.16-0.32


Jet Fuel
(JP-41
100
1
2

0.16-0.32
Specificity Results:

     Activated:   commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, JP-4 jet fuel,
                 synthetic gasoline, xylene(s).

Manufacturer's Specifications:

     Detector No. 301-0324-001
         Application:       Liquid sensor, water, used in 4* monitoring well
         Sensor:          Magnetism and conductivity pins
         Detection Range:  1 /8" floating product on ground water or 1.5" free product

     Detector No. 301-0325-001
         Application:       Liquid sensor, water or hydrocarbon used in reservoir, sump or piping
                          trench
         Sensor:          Magnetism and conductivity pins
         Detection Range:  1/8" floating product on ground water or 1.5" free product

Comments:       EPA and many states require detection of 118 inch of product, which is 0.32
                 cm.  Evaluation performed on equivalent Pollulert detectors.
TMri EngmMring
2S15E»tMtUiMRo«d
CirroHton. TX 76OOB
Td: (800) 878-7577
                                                                                                                                                                      Evaluitor: R«di«n Corporation
                                                        DM* of Evaluation: 07/08/91
                                                                                                                                                          154

-------
                                     Tids! Enssissrir.;

                     TMol Detector No. 301-O326-O01 and 301 -0326-002    i
                     LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
    Output type:          qualitative
    Sampling frequency:    continuous
    Operating principle:    electrical conductivity
Tait R>iuK>:


Accuracy(%)
Detection time(sec)
Fall time (sec)
Lower detection
limit(cm)
Commercial
Gasoline
100
4
3

0.08-0.32
                                           Synthetic
                                            Gasoline
                                           100
                                           7
                                           4

                                           0.08-0.32
     Jet Fuel
     (JP-41
    100
    2
    4

    0.08-0.32
Specificity R«sult«:

     Activated:   commercial gasoline, toluene, n-hexane, diesel fuel, jet-A fuel, JP-4 jet fuel,
                 synthetic gasoline, xylene(s).

Manufacturer's Specifications:

     Detector No. 301-0326-001
         Application:      Liquid sensor, water, used in 2* monitoring well
         Sensor:          Magnetism and conductivity pins
         Detection  Range: 1/8" floating product on ground water or 2.5" free product

     Detector No. 301-0326-002
         Application:      Liquid sensor, water, used in annulus of double wall steel tanks
         Sensor:          Magnetism and conductivity pins
         Detection  Range: 1/8' floating product on ground water or 2.5" free product

 Comments:       EPA and many states require detection of 1/8 inch of product, which  is 0.32
                  cm.  Evaluation performed on equivalent Pollulert detectors.
 TWol Enginwing
 2615Ea«tBaltUnaRoad
 C.troHlon, TX 75006
 Tel: (BOO) 871-7577
    Evaluator: Radian Corporation


Data of Evaluation: 07/03/31
                                             155
                                                                                         Tide! Ets!nssr!ns

                                                                                            EMS-3500
                                                                            Containment Sump Probes Part No. 301-0642

                                                                              LIQUID-PHASE INTERSTITIAL DETECTOR
                                                                                                                                                                                  UK AS-1
                                                                                                             Detector:
                                                        Output type:
                                                        Sampling frequency:
                                                        Operating principle:

                                                    Test Results*:
                              qualitative
                              continuous
                              magnetic switch / float & hydrocarbon sensitive polymer
    Accuracy (%)
    Response time (min)
    Recovery time (min)
    Product activation height (cm)
    Lower Detection Limit (cm)
Commercial
Gasoline
100
6.39
>60
2.27
2.32
                                                                                                                                                                     Water
Low
100
4.76
<1
4.31
4.31
Hioh
100
4.12"
<1
19.22
Not App.
    • at a flow rate of 0.89 gal/hr in test chamber of diameter 12.6 cm.
    ** larger test chamber and flow rate of 1.51 gal/hr.

Specificity Results:

    Activated at 2.27 cm height:
         diesel fuel, synthetic fuel, home heating oil #2.

Manufacturer's Specifications:


Comments:   The test procedures used were those in Carnegie Mellon Research Institute's 'Test
             Procedures for Third Party Evaluation of Leak Detection Methods: Point Sensor Liquid
             Contact Leak Detection Systems": Final Report - November 11, 1991.  In addition,
             the probe was tested to determine its capability of detection hydrocarbons floating
             on water. A Lower Detection Limit thickness of 0.04 cm was detected on average in
             16 min 41 sec, with the recovery time averaging 12 min 55 sec.
                                                                                                            Tidal Enginwring
                                                                                                            2816 EMt BdtUn* Rod
                                                                                                            Cirrollton, TX 7SOOB
                                                                                                            TO: (800) 878-7677
                                                   Evahiatof: C«m«g!« M*Hon Raaaaroh Irntitute


                                                   Data of Evaluation: 02-17-93
                                                                                                                                                       156

-------
                                      Tide) Engineering

                                         EMS-3500
                          Liquid Discriminatory Probe* Part 301-0635

                           LIQUID-PHASE INTERSTITIAL DETECTOR
Detector:
Output type:
Sampling frequency:
Operating principle:
Test Results':


Accuracy (%)
Response time (min)
Recovery time (min)
Product aetivatiofi
height (cm)
Lower detection limit
qualitative
continuous
electrical conductivity / h<

Commercial
Gasoline Water
100 100
3.59 0.96
13.18 <1
- -- -
1.76 0.49
4.19 1.52
     * at a flow rate of 0.04 gal/hr in a 2.54 cm diameter test chamber

Specificity Results:
    Activated:
                 diesel fuel (at liquid height of 1.78 cm), synthetic fuel (at 2.30 cm), home
                 heating oil #2 (at 2.30 cm).
Manufacturer's Specifications:
Comments:   The test procedures used were those in Carnegie Mellon Research Institute's "Test
             Procedures for Third Party Evaluation of Leak Detection Methods: Point Sensor Liquid
             Contact Leak Detection Systems": Final Report - November 11, 1991.
Tidel Engineering
2615 East Belt Una Road
CarroKton, TX 75O06
Tol: (SOO) 878-7577
                                                    Evaluator: Carnegie Mellon Research Institute
                                                    Date of Evaluation: 01-29-93
                                            157
                                      Tidel Engineering

                                         EMS-3500
                              Tidel Detector No. 301-0752-001

                           LIQUID-PHASE INTERSTITIAL DETECTOR
                                                                                                                                                                                  DRAFT
                                                                                                                Detector:
Output type:
Sampling frequency:
Operating principle:
Test Results':
Accuracy (%)
Response time (min)
Recovery time (min)
Product activation
height (cm)
qualitative
continuous
float switch
50 wt% Ethylene glycol
in water
iiU Down
100 100
21.91 30.10
<1 <1
28.92 2.75
30 wt% Calcium chloride
in water
Up Down
100 100
22.27 31.08
<1 <1
28.82 2.48
     • at a flow rate of 0.26 gal/hr in test chamber

Specificity Results:

     Not applicable

Manufacturer's Specifications:


Comments:

     This point sensor is intended to monitor the level or either ethylene glycol or calcium chloride
     solutions in the interstitial or annular space of a double-walled tank, by triggering an alarm if
     any significant gain or loss of solution occurs.  Evaluation was performed using procedures
     from Carnegie Mellon Research Institute's "Test Procedures for Third Party Evaluation of Leak
     Detection Methods: Point Sensor Liquid Contact Leak Detection Systems": Final Report -
     November 11, 1991, modified to accommodate the intended purpose.
Tidel Engineering
2615 Ea»t Belt Line Road
Carrollton, TX 75006
Tel: (800) 878-7577
Evaluator: Carnegie Mellon Research Institute


Date of Evaluation: 04-20-93
                                                                                                                                                          158

-------
                                        EMS-3000
                               301-0328-001, 301-O330-001

                     VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
Output type:          qualitative
Sampling frequency:   continuous
Operating principle:    adsistor
Teat RMuits:
Accuracy CM:
Detection Time (sec):
Fall Time (min:sec):
Lower Detection Limit
    (ppm):

Specificity Rosuhs:
                         Commercial  Synthetic
                         Gasoline     Gasoline
100
 91
5:39
100
 65
4:23
10 to 100    10 to 500
100
 86
9:38

10 to 50
Activated:    commercial gasoline, JP-4 jet fuel, synthetic gasoline, toluene, xylene(s)
Not activated:    n-Hexane

Manufacturer's Specifications:


Comments:   The test procedures used were those in Radian Corporation's draft report
             •Development of Procedures to Assess the Performance of External Leak Detection
             Devices: Vapor-Phase ASTM-Formatted Methods," June 29, 1990.
 Tidtl EnginMring
 CairoHlon, TX 75006
 T«l: (800) 870-7S77
                          Evolution Cwixgit M«llon R«««rch Imtitut*


                          D«t« of Evaluation: 03-18-93
                                            159
                                                                                                           Detector:
                                                                                                                      Tide! Engineering

                                                                                                                         EMS-3500
                                                                                                             Vapor Sensor Probe Part No. 301-0634

                                                                                                      VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                  Output type:          qualitative
                                                                                  Sampling frequency:   continuous
                                                                                  Operating principle:    adsistor
Test Results:
                         Commercial   Synthetic
                         Gasoline     Gasoline
Accuracy'(%):                100         100          100
Detection Time' (m!n:sec):       2:46        1:41         1:50
Fall Time* (hr:min:sec):         > 1:00:00"  > 1:00:00"   > 1:00:00"
Lower Detection Limit
    (ppm):                   100         500          100

* For tests conducted with 1000 ppm of test gas.
" The vapor sensor probe was recalibrated when it did not recover after 1 hour, from exposure to
test vapors.

Specificity Results:

Activated:    commercial gasoline, JP-4 jet fuel, synthetic gasoline, n-hexane, toluene, xylena(s)

Manufacturer's Specifications:

    Vapor sensor probe for use in normally dry monitoring wells to detect hydrocarbon vapors.
    Can be used in monitoring weiis up to 20 feet deep. The probe will alarm if it comes in
    contact with water and must be removed immediately to prevent damage to the probe.

Comments:   Evaluation performed on equivalent Pollulert detectors. The test procedures used
             were those in Radian Corporation's draft report "Development of Procedures to
             Assess the Performance of External Leak Detection Devices: Vapor-Phase ASTM-
             Formatted Methods," June 29, 1990.
                                                                                                           TkM Engiiwwlng
                                                                                                           2B15EMtB«ltUn*RoKf
                                                                                                           CtrroHton, TX 75008
                                                                                                           T«h (800) 678-7577
                                                                                                                                    Evtkutor: C«n*gl< M*Mon R«M*rch liMtitutt


                                                                                                                                    Oil. of Ewkwtien: 03-18-93
                                                                                                                                                      160

-------
                                                                          DRAFT
                                    Tokhaim Corporation

                   Tokhabn Praiture Monitor, Models PM 101 and 585A-PM
                      AUTOMATIC MECHANICAL LINE LEAK DETECTOR

Certification:          Leak rate of 3.0 gallons per hour with P0 = 100% & PFA=0%.

Leak Threshold:       2.25 gallons per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, and alcohols.

Specification:         System is installed on pressurized fiberglass and steel piping.
                     The piping system volume must not exceed 78 gallons.
                     Tests are conducted at 150% of the line operating pressure.

Waiting Time:         There is no waiting period between product delivery and testing.    	
                     There is no waiting period between last dispensing and testing.

Test Period:          Minimum test time (response time) must be 4 seconds.

System Features:      This system is permanently  installed  on the piping and automatically tests
                     the line.
                     It uses a preset threshold and a single test to determine whether the piping
                     is leaking.
                     If a leak is detected, this system restricts fuel flow to dispenser.

Calibration:           The equipment must be checked and calibrated semi-snnually in accordance
                     with manufacturer's instructions.
Comments:
                     Tokheim Corporation no longer manufactures this system.
Tokhaim Corporation
10501 Corporate Driva
FortWayrw. IN 48BO1-O3SO
Tel: (219) 423-2552
Evaluator: Viata Raaaarch


Data of Evaluation: 11/2/90
                                           161
                                                                                                                           DRAFT
                                                                                   Tracer Research Corporation

                                                                                          Tracer Tight
 Certification:

 Leak Threshold:

 Applicability:


 Capacity:


 Waiting Time:


 Tracer Dosage:


 Permeability:


 Probe:


 Groundwater:

 Comments:
                                                                       NON-VOLUMETRIC TANK TIGHTNESS TEST METHOD

                                                                        Leak rate of 0.1  gallon per hour with P0 = 100% & PfA=0%.

                                                                        Detection of tracer chemical.

                                                                        All fluid petroleum products and any other fluid with which the tracer is
                                                                        compatible.

                                                                        This test method is not limited by tank capacity, however only portions of
                                                                        the tank system  which within 10 feet of sample collection point are tested.

                                                                        Waiting period after injection of the tracer into the tank is 7 to 30 days
                                                                        nAnaralji/ t^un uuaobc\  .  _
                                                                        Dosage of tracer is a factor of tank size and the frequency of tank refills
                                                                        according to manufacturer's recommendations.

                                                                        Soil permeability must be greater than 1 Darcy. Soil permeability must be
                                                                        sufficient for transport of tracer through the backfill.

                                                                        Radius of influence of each probe is 1 0 feet; probes must be placed such
                                                                        that all possible locations and orientations are within the circle of influence.

                                                                        Depth to the water table present in the backfill must be determined.

                                                                        - Presence of frozen, saturated soil above the bottom of the tank may
                                                                        reduce the effectiveness of this test method.
                                                                        - Presence of groundwater above the bottom of the tank may also reduce
                                                                        the effectiveness of this test method (e.g. when applied to tanks containing
                                                                        water-miscible products or products whose specific gravity is greater than
                                                                        one).
Traoar Munch Corporation
3855 N. Builraaa Center Dr.
Tucion, AZ 8S705
Tel: (800) 989-9929
Evaluatora: K«n Wilcox Anociitei (1991)
     Control Stratagiea Enginearino, (1992)

DaUa of Evaluation*: 10/04/91 & 5/92
                                                                                                                                                    162

-------
                           r\&  ACT
                                 Treeer Research Corporation

                                    Tracer Tight Line Test
                               LINE TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD = 100% & PM=0.0%.

Leak Threshold:        Detection of tracer chemical.

Applicability:          All fluid petroleum products and any other fluid with which the tracer is
                      compatible.

Waiting Time:         Waiting period after injection of the tracer into the tank is on average 2
                      weeks, but must be no less than 1 week, and no  more than  4 weeks.  For
                      very large systems, several  days or weeks may be required to circulate
                      tracer labeled fuel through all parts of the system. Under these
                      circumstances the  1 week waiting period begins after the tracer reaches the
                      pipeline being tested.

Tracer Dosage:        Dosage of tracer is a factor of tank size and the frequency of tank refills
                      according to manufacturer's recommendations. Tracer labelled product
                      should be circulated through the piping before the test period begins.
                      Pressurized piping must be brought up to operating pressure or caused to
                      operate on a daily basis.

Permeability:          Soil permeability must be greater than 1  Darcy.  During probe sampling
                      vacuum must  not exceed 15 inches of mercury.  Soil permeability must be
                      sufficient for transport of tracer through the backfill.

Probe:                Radius of influence of each probe is 10 feet. Locating the pipelines should
                      be done according to the manufacturer operating procedures for pipeline
                      test results to be valid.

Comments:           Presence of frozen, saturated soil (frozen ground water) surrounding the
                      piping may reduce the reduce the effectiveness of this test  method.
                      Presence of ground water surrounding the piping may also reduce the
                      effectiveness  of this test method when applied to piping containing water
                      miscible products or products whose specific gravity is greater than one.
 Tracir Raaiarch Corporation
 3655 N. Bu.irmi Center Dr.
 Tuc.on, AZ 85705
 Tel: (800) 989-9929
Evaluator: Control Strangle! Engineering


Data of Evaluation: OS-??-92
                                              163
                                                                                                                                                                                        HP APT
                                                                                                                                                                                                —
                                                                                                 Triangle Environmental

                                                                                     T.E.I. System 4000. Ver. 1.00 (Underfilled Test)
                                                                                     VOLUMETRIC TANK TIGHTNESS TEST METHOD

                                                             Certification:          Leak rate of 0.1 gallon per hour with PD=99% and PfA=4.8%.

                                                             Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                                                                                   system exceeds this threshold).

                                                             Applicability:          Gasoline, diesel, aviation fuel, fuel oil, waste oil and solvents.

                                                             Capacity:             The maximum tank capacity must be 15,000 gallons.
                                                                                   The tank must be between 50 and 100% full.

                                                             Waiting Time:         Minimum waiting time between product delivery to the tank and test data
                                                                                   collection must be 6 hours.

                                                             Test Period:          The minimum data collection time is determined by computer.  The average
                                                                                   data collection time during the evaluation was four hours.
                                                                                   Leak rate is calculated from data of last 2 hours of test period.

                                                             Temperature:         A minimum of 3 thermistors must be used to determine the average
                                                                                   temperature of the stored hazardous substance.

                                                             Ground Water:        Depth to the  water table present in the backfill must be determined, and if
                                                                                   it is above the bottom of the tank, product level is raised to  provide
                                                                                   minimum of 1 psi net pressure on the bottom of the tank.

                                                             Calibration:           Sensors must be calibrated before each test.

                                                             Comments:       1.  This equipment was not evaluated using manifolded tanks.
                                                                               2.  This equipment only tests the portion of the tank that contains  product.
                                                                               3.  As the product level is lowered the leak rate in a leaking tank decreases
                                                                                   (due to lower head pressure).
                                                                                                               Triangle Environmental
                                                                                                               172W»etVerdugo Ave.
                                                                                                               Burbank, CA 91502-2132
                                                                                                               Tel: (818) 840-7020
Evaluator: United SlalM Tailing Co., Inc.


Evaluation Completed: 0442-91
                                                                                                                                                           164

-------
                                 Triangle Environmental, Ink..

                                 TEI System 5000. Ver. 1.0
                                                                            DRAFT
                     NON-VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD = 100% & PfA=0%.

Laak Thrathold:       A leak is declared if the acoustical noise level of the tank under vacuum is
                     greater than the calibrated noise level (which is taken without vacuum).

Applicability:          Gasoline, diesel, aviation fuel, fuel oil #4, solvents and light liquids.

Capacity:             The maximum tank capacity is 20,000 gallons. The tank must be at least
                     14% full. The microphone should be located within 24 feet of all points on
                     the tank.

Waiting Time:         There is  no waiting time after product delivery to the tank.

Tast Period:          The data collection time is 1 minute.

Test Pressure:        Vacuumed 1  psi is maintained at the bottom of the tank. If the vacuum
                     cannot be maintained, see manufacturer's instructions.

Calibration:           The sensor must be calibrated before each test.

Temperature:         Acoustical signal is independent of product temperature.

Groundwater:         Depth of the groundwater table in the backfill must be determined.
                     This method cannot be used if the groundwater is above the bottom of the
                     tank.

Comments:           - This test method was third-party certified using unleaded  gasoline as the
                     test product.
                     - During the third-party testing, the microphone was  24 feet away from the
                     leak source.
                     - Headphones are used during the test to listen for the signal of air ingress.
                     - Noise signals are tape recorded (not digitally recorded).
                     - Manifolded tanks are identified and isolated prior to the test.
                     - This test method cannot be used if the backfill material is not porous.
                     - This test method may not be effective in some backfill, because some
                     particles (such as clay) may plug a hole in the tank.
                     - If the soil is saturated with product, this test will not detect air or water
                     ingress.
 Triangle Environmantal, Inc.
 172 W. Vardugo Avanua
 Burbank, CA91S02
 Tel: (818) 840-7020
Evaluator: United Statn Totting Co. Inc.


Data of Evaluation: 02-O4-93


 165
                                                                                                 Triangle Environmental, Inc.

                                                                                                  TEI Ullage Test, Ver. 1.0
                                                                                                                                           DRAFT
                                                                                 NON-VOLUMETRIC ULLAGE TANK TIGHTNESS TEST METHOD

                                                                 Certification:          Leak rate of 0.1 gallon per hour with PD = 100% & PFA=«0%.

                                                                 Leak Threshold:       An increase in the acoustical noise level of the tank under vacuum due to
                                                                                      air or water ingress indicates a leak.

                                                                 Applicability:          Gasoline, diesel, aviation fuel, fuel oil #4, solvents and light liquids.

                                                                 Capacity:             The maximum ullage volume is 15,000 gallons.  The microphone should be
                                                                                      located within 24 feet of all points of the ullage portion of the tank.

                                                                 Waiting Time:         There is no waiting time if the test is conducted after the underfilled tank
                                                                                      test.

                                                                 Test Period:           The data collection time is 1  minute.

                                                                 Test Pressure:         Vacuumed 1 psi is maintained in the ullage portion of the tank.  If the
                                                                                      vacuum cannot be maintained, see manufacturer's instructions.

                                                                 Calibration:            The sensor must be calibrated before each test.

                                                                 Temperature:          Acoustical signal is independent of product temperature.

                                                                 Groundwater:         Depth of the groundwater table in the backfill must be determined, and if it
                                                                                      is above the product level, vacuum pressure must be adequate to detect an
                                                                                      ingress of water.

                                                                 Comments:            - This test method was third-party certified using unleaded gasoline as the
                                                                                      test product.
                                                                                      - Manifolded tanks are identified and isolated prior to the test.
                                                                                      - During the third-party testing, the microphone was 24 feet away from the
                                                                                      leak source.
                                                                                      - Headphones are used during the test to listen for the signal of air ingress.
                                                                                      - Noise signals are tape recorded.
                                                                                      - This test method may not be effective in some backfill, because some
                                                                                      particles (such as clay) may plug a hole in the tank.
                                                                                      - If the soil is saturated with product,  this test will  not detect air or water
                                                                                      ingress.
Triangla Environmental, Inc.
172W. Vardugo Avonue
Burbank. CA91502
Tel: (818) 840-7020
Evaluator: Unitad Stataa Taating Co. Inc.


Data of Evaluation: 05-05-93


     166

-------
                                                                           DRAFT
                               T.E.I. MocM LT-3. Version 1.0
                              LINE TIGHTNESS TEST METHOD

Certification:      Leak rate of 0.1 gallon per hour with P0=100.0% and PfA=0%.

Leak Threshold:   0.05 gallon per hour (a teak it declared if the output of the measurement system
                 exceeds this threshold).

Applicability:      Gasoline, diesel, aviation fuel, fuel oil #4 & *6, solvents and waste oil.

SpscHtcation:     System tests fiberglass and/or steel piping.
                 The piping system volume must not exceed 80 gallons.
                 Tests are conducted at 150% of the line operating pressure.

Waiting Time:     There is no minimum waiting time between delivery of product to the tank and
                 the start of data collection.
                 Minimum waiting time between last dispensing of product through the pipeline
                 system and the start of data collection is 15 minutes.

Temperature:     Product temperature change per hour should be less than 4 'F.

Test Period:      The minimum data collection time must be 15 minutes
                 Test data is acquired and recorded manually.
                 Manual calculations are performed by the operator on site.

Calibration:       Sensors must be checked and calibrated ssmi-annually in accordance with
                 manufacturer's instructions.
Triangla Envfoonmantal
172 Wait VardtigoAva.
Burbank,CA 91502-2132
Tal:fS18) 840-7020
Evatuator: Unitad Statta Tatting Company


Data of Evaluation: 3/3/82
                                            167
                                                                                    Univereai Sensors & Devices

                                                                                            TICS-1000
                                                                                   AUTOMATIC TANK GAUGING

                                                    Certification:         Leak rate of 0.2 gallon per hour with P0 = 96.6% & PfA = 3.4%.

                                                    Leak Threshold:       0.1 gallon per hour (a leak is declared if the output of the measurement
                                                                         system exceeds this threshold).

                                                    Applicability:         Gasoline, diesel, aviation fuel, and solvents.

                                                    Capacity:             Tne maximum tank capacity is  15,000  gallons.
                                                                         The tank must be at least 90% full.

                                                    Waiting Time:         Minimum waiting time between product delivery to the tank and test data
                                                                         collection must be 8 hours.

                                                    Test Period:          The minimum data collection time must be 6 hours.
                                                                         Test data must be acquired and recorded by a microprocessor.
                                                                         Leak rate is calculated from average of  subsets of all collected data.
                                                                         There must be no dispensing or product delivery during the test.

                                                    Temperature:         Minimum of 5 resistance temperature detectors must be used to determine
                                                                         the average temperature of the stored substance.

                                                    Water Sensor:         A water sensor must be used to monitor changes in water level in the tank
                                                                         during the test.
                                                                         Minimum water level detectable in the tank is 0.83 inches.
                                                                         Minimum detectable water level change is 0.0116 inches.

                                                    Calibration:           Temperature sensors and probes must be checked and calibrated annually in
                                                                         accordance with manufacturer's instructions.

                                                    Comments:           This equipment was not evaluated using manifolded tanks.
                                                                         This equipment only tests that portion of the tank which contains product.
                                                                         As the product level is lowered, the leak rate in a leaking tank decreases
                                                                         (due to lower head pressure).
                                                                         This system  is identical to Engineered System's Image II ATGS.
Unfraraal Sanaora & Davicaa, Inc.
9205 Alabama Avanua, Unit C
Chatawonh, CA  91311
T.I: (818)898-7121
Evaluator: Kan Wilcox Aaaociatn
                                                                                                                                                                   Data of Evaluation: 08-20-93
                                                                                                                                                       168

-------
                              Universal Sensors and Devices
                                                                       DRAFT
       Leak Alert System Models LAL-100, LA-01. LA-02. LA-04, LA-X4, LA-08. CATLAS
                                  Liquid Sensor LALS-1
Detector:

    Output type:
    Sampling frequency:
    Operating principle:

Test Results':
                         LIQUID-PHASE INTERSTITIAL DETECTOR
qualitative
continuous
thermal conductivity
                                 Commercial
                                 Gasoline
                                 100
                                 1.24
    Accuracy (%)
    Response time (min)
    Recovery time (min)            < 1
    Product activation height (cm)   6.61
    Lower Detection Limit (cm)      0.76

    • at a flow rate of 0.04 gal/hr in a 2.6 cm diameter test chamber

Specificity Results:

    Activated:   diesel fuel, synthetic fuel, home heating oil *2, water

Manufacturer's Specifications:
Comments:  EPA and many states require detection of 1/8 inch of product, which is 0.32 cm.
            The test procedures used were those in Carnegie Mellon Research Institute's "Test
            Procedures for Third Party Evaluation of Leak Detection Methods: Point Sensor Liquid
            Contact Leak Detection Systems': Final Report - November 11, 1991.
Univ«nal Sonaora and Davioaa, Inc.
9205 Alabama Aw.. Unit C
Chatawonh.CA 91311
T»l: (818)998-7121
                     Evaluator: Camogia Mellon Roaatrch Inatituta


                     Date of Evthution: 08-01-94
                                          169
                                                                                                                                       Universal Sensors and Devices
                                                                                                                                                  DRAFT
                                                                                    Leak Alert System Models LAL-100, LA-01, LA-02, LA-04, LA-X4, LA-08, CATLAS
                                                                                                            LAVS-1 MOS Vapor Sensor
                                                                                                         Detector:

                                                                                                         Output type:
                                                                                                         Sampling frequency:
                                                                                                         Operating principle:
                                                                                                                             VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
qualitative
continuous
metal oxide semiconductor
                                                                             Test Results:
                                                                                                          Accuracy (%):
                                                                                                          Detection Time (mimsec):
                                                                                                          Fall Time (min:sec):
                                                                                                          Lower Detection Limit (ppm):    100
Commercial
Gasoline
100
00:31
4:43
100
Synthetic
Gasoline
100
00:40
4:25
Not det.
JM
100
00:42
4:30
Not det.
                                                                                                          Specificity Results (%):

                                                                                                              Activated:
                                                                                             Commercial gasoline. Synthetic gasoline, JP-4 jet fuel, n-Hexane, Toluene,
                                                                                             Xylene(s)
                                                                                                          Manufacturer's Specifications:
                                                                             Comments:  The test procedures used were those in Radian Corporation's draft report
                                                                                         'Development of Procedures to Assess the Performance of External Leak Detection
                                                                                         Devices: Vapor-Phase ASTM-Formatted Methods,' June 29, 1990.
                                                                                                          Univwaal Soraora mi Davioaa, Inc.
                                                                                                          9205 Alabama Av«., Unit C
                                                                                                          Chitiworth, CA91311
                                                                                                          Tel: (818) 998-7121
                             Evaluator: Camagia Motion R«a««roh Institute


                             Data of Evaluation: 08-01-94
                                                                                                                                                    170

-------
                                          USTast

                               UST 2000/LL (Undarfaied Tt»t)
                       VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD = 98.12% and PFA=1.88%.

Leak Threshold:       0.05 gallon per hour (• leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, snd aviation fuel.  Water, kerosene, and other liquids may
                     be tested in consultation with manufacturer.

Capacity:             The maximum tank capacity is 15,000 gallons.  The tank must be at least
                     15% full.  There must be at least 20 inches and not more than 60 inches of
                     product in the tank.

Waiting Time:         Minimum waiting period  between product delivery and test data collection
                     is usually between 3 to 12 hours. Testing may begin when the rate of
                     product temperature change does not exceed 0.1 degrees F per hour.

Test Period:          The minimum data collection time must be 2 hours. Test data is acquired
                     and recorded by a computer, which does a regression analysis to determine
                     the leak rate.  An ultrasonic device is used to measure changes in product
                     level.

Temperature:         Change in temperature is determined via a measurement of the change in
                     the speed of  sound:

Ground Water:        Depth to the  water table present in the backfill must be determined, and if
                     it is above the bottom of the tank, product level must be adjusted to
                     provide a net pressure of at least + /-1.0 psi on the bottom of the tank.

Comments:          This equipment was not evaluated using manifolded tanks.
                     This system tests only the portion of the tank containing product.
                     As the product level is lowered the leak rate in a leaking tank decreases
                     (due to lower head pressure).
 USTeit
 P.O. Box 63835
 Lafayatta, LA 70SO5
 7.1:1318)981-9421
Evaluator: Kan Wilcox Aaaoclataa


Data of evaluation: 08-09-94
                                            171
                                                                                             USTest

                                                                                   UST 2000/P (Underfilled Test)
                                                                                                                                                                                  DRAFT
                       VOLUMETRIC TANK TIGHTNESS TEST METHOD

Certification:          Leak rate of 0.1 gallon per hour with PD=99.9% and PFA=0.1 % for tanks
                     up to 15,000 gallons.
                     Leak rate of 0.1 gph with PD = 99.7% and PFA=0.3% for tanks up to
                     45,000 gallons.

Leek Threshold:       0.05 gallon per hour (a leak is declared if tha cutout of tha measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, and aviation fuel.  Water and kerosene and other liquids
                     may be tested in consultation with manufacturer.

Capacity:             The maximum tank capacity is 45,000 gallons.
                     The tank must be at least 78.6% full.

Waiting Time:         Minimum waiting* period for tanks up to 45,000 gallons must be determined
                     from the manufacturer's chart of Wait Time versus Tank Volume, and this
                     chart must be included in the tank test report.

Test Period:          The minimum data collection time for tanks between 10,000 and 45,000
                     gallons is determined from the manufacturer's chart of Differential Volume
                     versus Test Duration. The line labelled PD - 99.9% must be used. This
                     chart must be included in the tank test report.
                     Test data is acquired and recorded by a computer, which does a regression
                     analysis to determine the leak rate.

Temperature:         Change in temperature is determined via a  measurement of the change in
                     the speed of sound.

Ground Water:        Depth to the water table present in the backfill must be determined, and if
                     it is above the bottom of the tank, product level  must be adjusted to
                     provide a net pressure of at least 0.5 psi on the bottom of the tank.

Comments:           This equipment was not evaluated using manifolded tanks.
                     This system tests only the portion of the tank containing product.
                     As the product level is lowered the leak rate in a leaking tank decreases
                     (due to lower head  pressure).
                                                                                                            UST.it
                                                                                                            P.O. Box S3835
                                                                                                            Latayatta, LA 70EOE
                                                                                                            Ttl: (318) 981-9421
                                                                                          Evaluator: Mdwaat Raaaarch Iratituta, 1000 - 10,000 «•), 12-05-90
                                                                                                  K«n Wilcox AnooI.Ut, 10,000<- 45.000 gal, 08-O4-92
                                                                                                                                                       172

-------
                                         USTett

                             UST 2000/U (2.0 psi and -1.0 psi)
                                                                          DRAFT
                NON-VOLUMETRIC ULLAGE TANK TIGHTNESS TEST METHOD

Certification:      Leak rate of 0.1 gallon per hour with PD= 100% and PFA=0%.

L«ak Threshold:   A substantial increase in the noise signal (under vacuum or pressure) over the
                 background signal (no pressure or vacuum applied) in the frequency interval of
                 10 kHz to 20 kHz, is declared as a leak.

Applicability:      Gasoline, diesel, aviation fuel, heavy fuel oils (#2 through #6), solvents, waste
                 oil.  Equipment is not in contact with the product.

Capacity:         Ullage volume of 7,550 gallons or less for +2.0 psig and 5,250 gallons or less
                 for-1.0 psio test.

Waiting time:     There is no waiting time if the test is conducted after an underfilled tank
                 tightness test.

Test Period:      Minimum data collection time is 15 minutes.

Test Pressure:    Tests are done at a net of + 2.0 psi (pressure) or -1.0 psi (vacuum) in the ullage
                 portion of the tank.

Ground Water:    Depth to the water table present in the backfill must be determined.  If it is
                 above the product level, the test under vacuum must not be conducted.  Net
                 outward pressure throughout the ullage must exceed 2.0 psi.

Calibration:       Test equipment is checked by the tester before each test.

Comments:       This is an ullage test only, the portion  of the tank that contains product must be
                 tested with an  underfilled test method.
                 During the third-party certification unleaded gasoline was the test product.
                 During the third-party certification microphone was less than 8.5 feet from the
                 leak source.
                 Surrounding acoustical noise can interfere with the test result. If the
                 background noise is above a certain threshold, test is inconclusive.
                 Vibration due to nearby equipment or dripping condensation can interfere with
                 this test.
                 This equipment is not third-party certified using manifolded  tanks.
 USToit
 P.O. Box 53835
 Lifayatte, LA 70505
 Tri: (318) 981-9421
                                      Evaluator: Kan Wiloox Aaioeiataa
Oat* of Evaluation: 03-24-92
                                           173
                                                                                                    USTMAN Industries, Inc.

                                                                                                 USTMAN SIR 1.91 (quantitative)
                                                                                                                                         DRAFT
                                                                                    STATISTICAL INVENTORY RECONCILIATION TEST METHOD

                                                                   Certification:          Method is certified to detect a 0.1 oph leak rate with P0=98.4% &
                                                                                        PfA = 1.6%.

                                                                   Leak Threshold:       A leak is  declared when a continuous loss exceeding 0.1 gallon per hour at
                                                                                        the 5% level of significance is detected.

                                                                   Applicability:          Gasoline, diesel, aviation fuel, and fuel oil #4.

                                                                   Tank Capacity:        Maximum tank capacity may not exceed 18,000 gallons.

                                                                   Data Requirement:    Minimum of 42 days of product level and flow through data is required.

                                                                   Comments:           Of the 41 data sets submitted for analysis, four data sets were not
                                                                                        analyzed, 7 were inconclusive.

                                                                                        This evaluation did not include data sets from manifolded tanks.

                                                                                        The median monthly throughput for tanks used in this evaluation was
                                                                                         10,978 gallons.

                                                                                         Leak rates  ranging from 0.048 to 0.201  gph were used in the evaluation.

                                                                                         Data sets used in this evaluation were supplied by the evaluator.
                                                                    USTMAN Industrie Inc.
                                                                    12265 Wo»t Bayaud Avenus, Suits 110
                                                                    LokowocK*. CO 80228
                                                                    T«l: (303) 988-8011
                                                                                                                               Evaluator: Ken Wilcox Aooclataa
DaM of Evaluation: 10-31-91
                                                                                                                                                      174

-------
                                  USTMAN Industries, k>e,

                           USTMAN SIR Version 94.1 (quantitative)


                 STATISTICAL INVENTORY RECONCILIATION TEST METHOD

Certification:          Method it certified to detect a 0.10 gph leak rate with P0 = >99% and
                     PFA-<1.6%.

Lack Threshold:       A leak is declared when leak rate exceeds 0.05 gallons per hour.

Applicability:          Gasoline, diesel, aviation fuel, and fuel oil #4.

Tank Capacity:        Maximum tank capacity shall not exceed 30,000 gallons.

Data Requirement:    Minimum of 30 days of product level and flow through data.

Comments:           All 53 data sets presented for evaluation were evaluated with conclusive
                     results.

                     The median monthly throughput of tanks used in this evaluation was
                     25,408 gallons.

                     Leak rates of 0.05, 0.1, and 0.2 cph ware used in the evaluation.

                     Data sets used in this evaluation were supplied by the evaluator and some
                     data sets used an USTMAN SIR 1.91  (0.1  gph) analysis as documentation
                     that tanks in this evaluation were tight.

                     This evaluation included some data from manifolded tanks.
 USTMAN IndtntriM Inc.
 12265 W«t B*vwd Avtnue, Suit* 110
 Ukawood, CO 80228
 T.l: (303) »88-SOU
                                                            Evtluator: K«n WHeox AModitx
DIM of Evrtutfon: 03-31-94
                                            175
                                               Certification:
                                               Leak Threshold:
                USTMAN industries, inc.

                YES SIR 90 (qualitative)


STATISTICAL INVENTORY RECONCILIATION TEST METHOD

    Method is certified to detect a 0.2 gph leak rate with PD-96.3% &
    PFA=3.9%.

    A leak is declared when a consistent loss exceeding 0.1 gallon per hour that
    is statistically significant from zero at the 5% confidence level.
                                               Product Applicability:  Gasoline, diesel. aviation fuel, and fuel oil #4.

                                               Tank Capacity:        Maximum tank capacity may not exceed 15,000 gallons.

                                               Data Requirement:     Minimum of 35 days of product level and flow through data.

                                               Comments:           Of the 120 data sets evaluated by the method, 15 were inconclusive.

                                                                    This evaluation did not include data from manifolded tanks.

                                                                    The median monthly throughput for tanks used in this evaluation was
                                                                    15,867 gallons.

                                                                    Data set used in this evaluation were supplied by the evaluator.
                                                                                                      USTMAN InduitriM Inc.
                                                                                                      12285 Wnt BayMid Avtnut, Sulli 110
                                                                                                      Ltkewood, CO 80228
                                                                                                      Td: (303) 908-8011
                                                                                                          Evduttor: MHwnt Rimroh Iratitutt


                                                                                                     D«tt of Evaluation: 12-17-90
                                                                                                                                                 176

-------
                                  Vaporiess Manufacturing

                                     Vaporiess LD 2000


                      AUTOMATIC MECHANICAL LINE LEAK DETECTOR

Certification:      Leak rate of 3.0 gallon per hour with PD-=100% & PfA«=0%.

Leak Threshold:   1.7 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:      Gasoline, diesel, aviation fuel and  solvent.

Specification:     System is installed on pressurized flexible piping.
                 The piping system volume must not exceed 129 gallons.
                 Tests are conducted at the line operating pressure.

Waiting Time:    There is no waiting  period between last dispensing and testing.
                 There is no waiting  period between product delivery and tesiinfl.

Test Period:      The minimum test time (response time) is 5 seconds.

System Features: This system is permanently installed on the piping and automatically tests the
                 line
                 It uses a preset threshold and a single test to determine whether the piping is
                 leaking.
                 If a leak is detected, this system restricts fuel flow to dispenser.

Calibration:       Equipment must be checked annually in accordance with manufacturer's
                 instructions.
 Vooorioee Manufacturing
 9234 Eut Valley Rd., Suit. C
 Pfiucott VaHey. AZ 86314
 Tel: (902)775-6191
Evahiator: Ken Wrlcox Aeeooietea


Date of Evaluation: 11-19-90
                                              177
                                                                                      Vaporiess Manufacturing

                                                                                        Vaporiess LD 2000E
                                                                                                                                                                                     DRAFT
                                                                    AUTOMATIC MECHANICAL LINE LEAK DETECTOR (Hourly Test)

                                                    Certification:      Leak rate of 3.0 gallon per hour with PD = 100% & PFA=0%.

                                                    Leak Threshold:   2.0 gallons per hour (a leak is declared if the output of the measurement system
                                                                     exceeds this threshold).

                                                    Applicability:      Gasoline, diesel, aviation fuel and solvent.

                                                    Specification:     System is installed on flexible piping.
                                                                     The piping system volume must not exceed 59.6 gallons.
                                                                     Tests are conducted at the line operating pressure.

                                                    Waiting Time:     There is no waiting period between last dispensing and testing.
                                                                     There is no waiting period between product delivery and testing.

                                                    Test Period:      The minimum test time (response time) is 30 seconds.

                                                    System Features: This system is permanently installed on the piping and automatically tests the
                                                                     line.
                                                                     It uses a preset threshold and a single test to determine whether the piping is
                                                                     leaking. '
                                                                     If a leak is detected, this system restricts fuel flow to dispenser.

                                                    Calibration:      Equipment must be checked annually for capability of detecting a leak of 3.0
                                                                     gallons per hour.

                                                    Comments:      Enviroflex piping with a bulk modulus of 1,352 was used during the third-party
                                                                     evaluation.
                                                                                                              VapoHan Manufacturing
                                                                                                              9234 Eait Valley Rd., Suite C
                                                                                                              Preecott Valley, AZ 86314
                                                                                                              Tel: (602) 778-5191
                                                                                                                                                     Eviuator: Ken Wiloox Aatodatea
                                                                                           Date of Evaluation: 12-11-92
                                                                                                                                                          178

-------
                                  VaporltM Manufacturing

                                    Vapories* LO 2000T
                                                                           DRAFT
                      AUTOMATIC MECHANICAL LINE LEAK DETECTOR

Certification:     Leak rate of 3.0 gallon per hour with P0-100% & PFA-0%.

Leak Threshold:   2.5 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:     Gasoline, diesel, aviation fuel and solvent.

Specification:     System is installed on pressurized fiberglass and steel piping.
                 The piping system volume must not exceed 129 gallons.
                 Tests are conducted at the line operating pressure.

Waiting Time:     There is no waiting period between last dispensing and testing.
                 There is no waiting period between product delivery and testing.

Test Period:      The minimum test time (response time) is 1 minute.

System Features: This system is permanently installed on the piping and automatically tests the
                 line.
                 It uses a preset threshold and a single test to determine whether the piping is
                 leaking.
                 If a leak is detected, this system restricts fuel flow to dispenser.

Calibration:      Equipment must be checked annually in accordance with manufacturer's
                 instructions.
 Vaporiaia Manufacturing
 9234 East Valley Rd., Suit. C
 Pioscott VaHav, AZ SS314
 Tal: (802) 775-5191
Evaluator: Kin Wilcox Aaaociatat


Datt of Evaluation: July 13, 1993
                                             179
                                                                                        Vaporless Manufacturing

                                                                                     Vaporless LD 3000 & LO 3000S
                                                                            AUTOMATIC MECHANICAL LINE LEAK DETECTOR

                                                      Certification:           Leak rate of 3.0 gallon per hour with P0 = 100% & PFA=0%.

                                                      Leak Threshold:        2.0 gallon per hour (a leak is declared if the output of the measurement
                                                                            system exceeds this threshold).

                                                      Applicability:           Gasoline, diesel, aviation fuel.

                                                      Spscificattcn:          System is installed on pressurized steel and fiberglass piping.
                                                                            Piping system vcluma must not excesd 320 gallons.
                                                                            Tests are conducted at the line operating  pressure.

                                                      Waiting Time:          There is no waiting times between last dispensing and testing.

                                                      Test Period:           The minimum test time (response time) is 9 seconds.

                                                      Calibration:            Equipment must be checked annually in accordance with manufacturer's
                                                                            instructions.
                                                                                                               Vaporiaia Manufacturing
                                                                                                               9234 Eait Vallay Rd., Sulta C
                                                                                                               Praicott Vallay, AZ 88314
                                                                                                               Tal: (602) 775-5191
                                                                                                              Evaluates Kin Wilcox Aiioclatoi


                                                                                                              Data of Evaluation: 08-20-83
                                                                                                                                                           180

-------
                                       Veador-Root

                               TLS-250/300/350 UST ATGS
                         with 7842 Digital Sensing Capacitance Probe

                           AUTOMATIC TANK GAUGING SYSTEM

Certification:          Leak rate of 0.2 gallon per hour with P0 = 99% & Pu = 1%.

Leak Threshold:       0.10 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, and solvents.

Capacity:             The maximum tank capacity is 15,000 gallons.
                     The tank must be between 50 and 95% full.

Waiting Time:         Minimum waiting time between product delivery to the tank and test data
                     collection must be 8.3 hours.

Test Period:          The minimum data collection time must be 5 hours.
                     Test data must be acquired  and recorded by a computer.
                     There must be no dispensing or product delivery during the test.

Temperature:         A temperature-average probe must be used to determine the average
                     temperature of the stored hazardous substance.

Water Sensor:        A water sensor must be used to detect water incursion.
                     Minimum water level detectable in the tank is 1.40 inches.
                     Minimum change in water level that can be detected is 0.040 inches.

Calibration:           Temperature sensors and probe must be checked and calibrated annually in
                     accordance with manufacturer's instructions.

Comments:           This equipment was not evaluated using manifolded tanks.
                     This equipment only tests the portion of the tank that contains product.
                     As the product level is lowered the leak rate in a leaking  tank decreases
                     (due to lower head pressure).
Veeder-Root
125 Powdar Foraat Drive
Simsbury, CT 06070-2003
Tel: (203) 851-2700
                                                            Evaluator: Midwaat Reiaarch Iratituta
Data of Evaluation: 01/18/91
                                            181
                                                                                                                                                                               DRAFT
                                                                                    Veeder-Root

                                                                            TLS-250/250i/350 UST ATGS
                                                                      with 8472 Digital Sensing Capacitance Probe

                                                                        AUTOMATIC TANK GAUGING SYSTEM

                                             Certification:          Leak rate of 0.2 gallon per hour with PD=99% & Pw=0.2%.

                                             Leak Threshold:       0.126 gallon per hour (a leak is declared if the output of the measurement
                                                                  system exceeds this threshold).

                                             Applicability:          Gasoline, diesel, aviation fuel, and solvents.

                                             Capacity:             The maximum tank capacity is 15,000 gallons.
                                                                  The tank must be between SO and 95% full.

                                             Waiting Time:         Minimum waiting timo between product delivery to the tank and test data
                                                                  collection must be 8.3 hours.

                                             Test Period:          The minimum data collection time must be 2 hours.
                                                                  Test data must be acquired and recorded by a computer.
                                                                  Leak rate is calculated from converting the level signals from the probe
                                                                  during the test period to change in temperature-compensated volume.
                                                                  There must be no dispensing or product delivery during the test.

                                             Temperature:         A minimum of 5 thermistors must be used to determine the average
                                                                  temperature of the stored hazardous substance.

                                             Water Sensor:        A water sensor must be used to detect water incursion.
                                                                  Minimum water level detectable in the tank is 1.52 inches.
                                                                  Minimum change in  water level that can be detected is 0.027 inches.

                                             Calibration:          Temperature sensors and probe must be checked and calibrated annually in
                                                                  accordance with manufacturer's instructions.

                                             Comments:          This equipment was not evaluated using manifolded tanks.
                                                                  This equipment only tests the portion of the tank that contains product.
                                                                  As the product level is lowered the leak rate in a leaking tank decreases
                                                                  (due to lower head pressure).
                                              Vendor-Root
                                              125 Powder Foreit Drive
                                              Sinwburv. CT 06070-2003
                                              Tal! (203) 851-2700
                                                                                                                                                                     Evatuator: Mtdwaat Raeaarch Inatituta
Data of Evaluation: 4/25/91
                                                                                                                                                     182

-------
                                                                                                                                                                                    Pk  A
                                       yssdsr-Roat

                               TLS-250/300/350 UST ATGS
                         with 8472 Digital Sensing Capacitance Probe

                  AUTOMATIC TANK GAUGING SYSTEM (0.1 gph test mode)

Certification:          Leak rate of 0.1 gallon per hour with PD»99% & PPA=0.1 %.

Leak Threshold:       0.071  gallon per hour (a teak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, aviation fuel, and solvents.

Capacity:            The maximum tank capacity is 15,000 gallons.
                     The tank must be between 50% and 95% full.

Waiting Time:        Minimum waiting time between product delivery to the tank and test data
                     collection must be 8.25 hours.

Test Period:          The minimum data collection time must be 2 hours.
                     Test data must be acquired and recorded by a computer.
                     Leak rate is calculated from the difference between first and last data
                     collected.
                     There must be no dispensing or product delivery during the test.

Temperature:         A minimum of 5 thermistors must be used to determine the average
                      temperature of the stored product.

Water Sensor:        A water sensor must be used to detect water incursion.
                      Minimum water level detectable in the tank is 1.52 inches.
                      Minimum change in water level that can bo detected is 0.027 inches.

 Calibration:           Temperature sensors and probe must be checked and calibrated annually in
                      accordance with manufacturer's instructions.

 Comments:           This equipment was not evaluated using manifolded tanks.
                      This equipment only tests the portion of the tank that contains product.
                      As the product level is lowered, the leak rate in a leaking tank decreases
                      (due to lower head pressure).
                                                                                                                                                Vesdar-Koot

                                                                                                                               TLS-200/200i/250/250W300/350/400 UST ATGS
                                                                                                                               with 8473 Digital Sensing Magnetoitrictive Probe

                                                                                                                                   AUTOMATIC TANK GAUGING SYSTEM

                                                                                                         Certification:          Leak rate of 0.2 gallon per hour with P0-99% & PFA~0.1%.

                                                                                                         Leak Threshold:       0.093 gallon per hour (a leak is declared if the output of the measurement
                                                                                                                              system exceeds this threshold).

                                                                                                         Applicability:          Gasoline, diesel, aviation fuel, and solvents.

                                                                                                         Capacity:             The maximum tank capacity is 1 5,000 gallons.
                                                                                                                              The tank must be between 50 and 95% full.

                                                                                                         Waiting Time:         Minimum waiting time between product delivery to the tank and test data
                                                                                                                              collection must be 8.3 hours.

                                                                                                         Test Period:           The minimum data collection time must be 2 hours.
                                                                                                                              Test data must be acquired and recorded by a computer.
                                                                                                                              Leak rate is calculated from converting the level signals from the probe
                                                                                                                              during the test period to change in temperature-compensated volume.
                                                                                                                              There must be no dispensing or product delivery during the test.

                                                                                                         Temperature:          A minimum of 5 thermistors must be used to determine the average
                                                                                                                              temperature of the stored hazardous substance.

                                                                                                         Water Sensor:         A water sensor must be used  to detect water incursion.
                                                                                                                              Minimum water  level detectable in the tank is 1 .32 inches.
                                                                                                                              Minimum change in water level that  can be detected is 0.024 inches.

                                                                                                         Calibration:           Temperature sensors and probe must be checked and calibrated annually in
                                                                                                                              accordance with manufacturer's instructions.

                                                                                                         Comments:           This equipment was not evaluated using manifolded tanks.
                                                                                                                              This equipment only tests the portion of the tank that contains product.
                                                                                                                              As the product level is lowered the leak rate in a leaking tank decreases
                                                                                                                              (due to lower head pressure).
Veeder-Root
125 Powder Foreit Drive
Simtbury, CT 08070-2003
Til: (203) 851-2700
                                                            Eveluator: Mdweit Reieerch Inttituta
                                                             D«t« of Eveluetion: 04-25-91
Veed«r-Root
12S Powdtr Forest Drive
Simebury, CT 08070-2003
Tel: (203) 051-2700
Evaluttor: Midweet Reieerch Inititute


Dete of Eveluetion: 4/28/81
                                            183
                                                                                                                                                    184


-------
Certification:

Leak Threshold:


Applicability:

Capacity:


Waiting Time:


Test Period:
Temperature:


Water Sensor:



Calibration:


Comment*:
                                       Veedar-Boot

                      TLS-200/200i/250/250i/300/360/400 UST ATGS
                      wHh 8473 Digital Sensing Magrotostrictiva Probe

                           AUTOMATIC TANK GAUGING SYSTEM

                     Leak rate of 0.1 gallon per hour with PD= 99% &PfA=1%.

                     0.069 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

                     Gasoline, diesel, aviation fuel, and solvents.

                     The maximum tank capacity is 1 5,000 gallons.
                     The tank must be at least 96% full.

                     Minimum waiting time between product delivery to the tank and test data
                              must b« 8.25 hours.          .  .
                     The minimum data collection time must be 3 hours.
                     Test data must be acquired and recorded by computer.
                     Leak rate is calculated from the difference between first and last data
                     collected.
                     There must be no dispensing or product deliver during the test.

                     A minimum of 5 thermistors must be used to determine the average
                     temperature of the stored product.

                     A water sensor must be used to detect water incursion.
                     Minimum water level detectable in the tank is 1 .32 inches.
                     Minimum change in water level that can be detected is 0.024 inches.

                     Temperature sensors and probe must be checked and calibrated annually in
                     accordance with manufacturer's instructions.

                     This equipment was not evaluated using manifolded tanks.
                     This equipment only tests the portion of the tank that contains product.
                     As the product level is lowered, the leak rate in a leaking tank decreases
                     (due to lower head pressure).
Voodar-Root
125 Powdar Fornt Driva
Slmtbury. CT OB07O-2003
Tel: (203) 851-2700
                                                            Evaluator:  Mdwaat Re»e«rch Institute
                                                             Data of Evaluation: O4-28-91
                                            185
                                       Veeder-Root

                     Vaedar-Root 3000 Tank Level Module - version TLP2
                       Normal/Rapid Test Mode - Magnetostrictive Probe

                           AUTOMATIC TANK GAUGING SYSTEM

Certification:          Leak rate of 0.2 gallon per hour with PD = 95.0% & PFA = 0.1 % in normal
                     test mode and PD = 95.0% & PFA - 5.0% in  rapid test mode.

Leak Threshold:       0.10 gallon per hour (a  leak is declared if the output of the measurement
                     system exceeds this threshold).

Applicability:          Gasoline, diesel, and aviation fuel.

Capacity:             The maximum tank capacity Is 15,000 gallons.
                     The tank must be between 50% and 95% full.

Waiting Time:         Minimum waiting time between product delivery to the tank and test data
                     collection must be 6 hours and 40 minutes.

Test Period:          The minimum data collection time must be 4 hours for normal test mode
                     and 1.2 hours for rapid test mode.
                     Test data must be acquired  and recorded by a microprocessor.
                     Leak rate is calculated from data determined to be valid by statistical
                     analysis.
                     There must be no dispensing or product delivery during the test.

Temperature:         A minimum of 5  resistance temperature detectors must be used to
                     determine the average temperature of the stored substance.

Water Sensor:        A water sensor must be used to detect water incursion.
                     Minimum water level detectable in the tank is 0.49 inches.
                     Minimum detectable change in water level is 0.05 inches.

Calibration:           Temperature sensors and probes must be checked and calibrated annually in
                     accordance with manufacturer's instructions.

Comments:           This equipment was not evaluated using manifolded tanks.
                     This equipment only tests that portion of the tank which contains product.
                     As the product level is lowered, the leak rate  in a leaking tank decreases
                     (due to lower head pressure).
                     This system was formerly called CEI 3000 and was manufactured  by
                     Control Engineers.
                                                                                                           Vaadar-Root
                                                                                                           lUMonordRosd
                                                                                                           Houma, LA 70383
                                                                                                           Tal: (504)872-4541
                                                                                                                                                                  Evatuator: Midwaat Raaaarch Inatituta
                                                                                                                                                                   Data of Evaluation: 05-27-92
                                                                                                                                                      186

-------
 Certification:


 Leak Threshold:
Applicability:
Capacity:
Waiting Tim*:


Test Period:





Temperature:


Water Senior:



Calibration:


Comments:
                   Veeder-Hoot

Veeder-floot 3000 Tank Level Module - version TLP2
  Normal/Rapid Test Mode • Magnatostrictiva Probe

      AUTOMATIC TANK GAUGING SYSTEM

Leak rate of 0.1 gallon per hour with PD = 99.2% & PFA = 0.08% in
normal test mode and PD  = 95.0% & PfA =  5.0% in rapid test mode.

0.05 gallon per hour (a leak is declared if the output of the measurement
system exceeds this threshold).

Gasoline, diesel, and aviation fuel
The maximum tank capacity is 15,000 gallons.
The tank must be at least 95% full.

Minimum waiting time between product delivery to the tank and test data
collection must be 6 hours and 40 minutes.

The minimum data collection time  must be 6.38 hours for normal test mode
and 2.67 hours for rapid test mode.
Test data must be acquired and recorded by a microprocessor.
Leak rate is calculated from data determined to be valid by statistical
analysis.

A minimum of 5 resistance temperature detectors must be used to
determine the average temperature of the stored substance.

A water sensor must be used to detect water incursion.
Minimum water level detectable in the tank is 0.49 inches.
Minimum detectable change in water level is 0.05 inches.

Temperature sensors and  probes must be checked and calibrated annually in
accordance with manufacturer's instructions.

This equipment was not evaluated  on manifolded tanks.
This equipment only tests that portion of the tank which contains product.
As the product level is lowered, the leak rate in a leaking tank decreases
(due to lower head pressure).
This system was formerly celled CEI 3000 and was manufactured by
Control Engineers.
                                                                                                                                                   Vssdsr-Hoot

                                                                                                                       350 Series UST Monitoring Systems: Models ILS-350, TLS-350, TLS-350R
                                                                                                                                   Groundwater Sensor (794380-621, -622, -624)

                                                                                                                                 LIQUID-PHASE OUT-OF-TANK PRODUCT DETECTOR
Detector:
                                                                                                                Output type:          qualitative
                                                                                                                Sampling frequency:   continuous
                                                                                                                Operating principle:    electrical conductivity
Test Results:
                          Commercial            Synthetic
                          Gasoline               Gasoline
    Accuracy(%)              100                  100
    Detection time(min:sec)    08:55                06:18
    Fall Time (min:sec)         54:50                26:02
    Lower detection
    limit(cm)                  0.02                 0.02
Specificity Results:

    Activated:    commercial gasoline, n-Hexane, diesel fuel, Jet-A fuel, toluene, synthetic
                 gasoline, xylene(s).

Manufacturer's Specifications:
Comments:

     EPA snd nwny states require detection of 1/8 inch of product, which is 0.32 cm.  This
     detector is reusable.
V«d«r«Root
Hourru, LA  70383
Tel: (504)872-4589
                                  Evrfuitor: Midwut Remrch Imtitut*


                                  DtU of Evaluation: 06/21/92
 V«0dir-Root
 12E Powder Forait Drive
 Slm.burv, CT 08070-2003
 Tel: (203) 851-2700
Evahutor: Cuixgi* M«Hon RiiMrch Inttituu


Dit. of Ev«lu«1ion: 11-2O-91 (TLS-350) tnd 07-28-S;
                                            187
                                                                                                                                   188


-------
                                                                         DRAFT
Detector:

     Output type:
     Sampling frequency:
     Operating principle:

Test Results':
Accuracy (%)
Rasnnrjfta time
Recovery time (min)
Product activation
    height (cm)
                                       Veeder-Root

                                         TLS-350
                            Discriminating Interstitial Liquid Sensor

                          LIQUID-PHASE INTERSTITIAL DETECTOR
qualitative
continuous
capacitance change / ultrasonic
                              Commercial
                              Gasoline
                              100
                              0.46
                              <1
                 Watqr
                 100
                 t.36
                 <1
                             0.23            0.69

     * at a flow rate of 0.94 gal/hr in 14.4 cm diameter test chamber

Specificity Results:

     Activated:    diesel fuel (at liquid height of 0.37 cm), synthetic fuel (at 0.35 cm), home
                 heating oil *2 (at 0.43 cm).

Manufacturer's Specifications:
Comments:   EPA and many states require detection of 1/8 inch of product, which is 0.32 cm, for
             ground water monitoring. The detectors are listed as interstitial due to intended use.
             The test procedures used were those in Carnegie Mellon Research Institute's "Test
             Procedures for Third Party Evaluation of Leak Detection Methods: Point Sensor Liquid
             Contact Leak Detection Systems': Final Report - November 11,  1991.
Ve»der-Root
125 Powder Forest Dr.
Simebury, CT OS07O-2OO3
Tel: (203) 851-2700
                                              Evaluator: Carnegie Mellon Research Inititute



                                              Date of Evaluation: 08-30-93
                                           189
                                                                                                                                                                                  DRAFT
                                                                                                                                              Veeder-Root

                                                                                                                                               TLS-350
                                                                                                                           Dispenser Pan Sensors and Containment Sump Sensors

                                                                                                                                 LIQUID-PHASE INTERSTITIAL DETECTOR
                                                                                                            Detector:
                                                                                                                Output type:
                                                                                                                Sampling frequency:
                                                                                                                Operating principle:

                                                                                                            Test Results':
                                                                                                                                    qualitative
                                                                                                                                    continuous
                                                                                                                                    electrical conductivity / ultrasonic
Commercial
Gaso|ina
100
c ca
                                                                                                                                                             Water
                                                                                                                                                          Low
                                                                                                                                                          100
                                                                                                                                                          A C/\
Hiah
100
    Accuracy (%)

                             17.17            <1          <1

                             3.40             2.45        20.3

    * at a flow rate of 0.17 gal/hr in a 6.0 cm diameter test Chamber.

Specificity Results:
                                                                                                                Recovery time (min)
                                                                                                                Product activation
                                                                                                                    height (cm)
                                                                                                                Activated:
                                                                                                                            diesel fuel (at liquid height of 4.75 cm), synthetic fuel (at 2.58 cm), home
                                                                                                                            heating oil #2 (at 4.67 cm).
                                                                                                            Manufacturer's Specifications:
                                                                                                       Comments:   EPA and many states require detection of 1/8 inch of product, which is 0.32 cm, for
                                                                                                                    ground water monitoring. The test procedures used were those in Carnegie Mellon
                                                                                                                    Research Institute's "Test Procedures for Third Party Evaluation of Leak Detection
                                                                                                                    Methods: Point Sensor Liquid Contact Leak Detection Systems": Final Report -   •
                                                                                                                    November 11, 1991.
                                                                                                           Veeder-Root
                                                                                                           125 Powder Forest Dr.
                                                                                                           Slmibury, CT 08070-2003
                                                                                                           Tel: (203) 851-2700
                                                                                                                                Evaluator: Carnegie Meflon Research Institute


                                                                                                                                Date of Evaluation: 05-28-93
                                                                                                                                                      190

-------
Detector:

    Output type:
    Sampling frequency:
    Operating principle:

Test Results':
                                        Vntmir-nooi

                                         TLS-350
                          Dud and Single Stage Hydrostatic Sensor*

                           LIQUID-PHASE INTERSTITIAL DETECTOR
qualitative
continuous
float switch
                                                                          i^fe t**aw  •»  ^^"w~
                                                                          UK AS-1
                          50 wt% Ethylena Qlycol
                          in water

Accuracy (%)
Response time (min)
Recovery time (min)
Product activation
height (cm)
ilc
100
22.52
<1

33.1
Down
100
35.75
<1

3.9
                      30 wt% Calcium chloride
                      in water	
                                                    ilB
                                                    100
                                                    20.46
                              Down
                              100
                              37.07
                                                    32.2    4.0

     • at a flow rate of 0.33 gal/hr in a test chamber of 7.8 cm diameter.

Specificity Results:

     Not applicable

Manufacturer's Specifications:


Comment*:

     This point sensor is intended to monitor the ievei or either ethyiene giycoi or caicium chloride
     solutions in the interstitial or annular space of a double-walled tank, by triggering an alarm if
     any significant gain or loss of solution occurs.  Evaluation was performed using procedures
     from Carnegie Mellon Research  Institute's "Test Procedures for Third Party Evaluation of Leak
     Detection Methods: Point Sensor Liquid Contact Leak Detection Systems": Final Report -
     November 11, 1991, modified to accommodate the intended purpose.
 Vesder-Root
 125 Powdsr Forest Dr.
 Sinubury, CT 06O70-2003
 Tel: (203) 851-2700
                      Evafuator: Carnegie Mellon Research Institute


                      Dili of Evaluation; 12-O7-92
                                            191
                                                                                                                       V««!er-S0o!

                                                                                                     TLS-250), TLS 250i Plus. ILS 250, ILS 350, TLS-350
                                                                                                 Interstitial Liquid Sensor for Fiberglass Tanks (0794390-401)

                                                                                                          LIQUID-PHASE INTERSTITIAL DETECTOR
                                                                                                                                                         •->» Mi  *  V* 'V
                                                                                                                                                         UK A,  i
                                                                                                              Detector:
     Output type:
     Sampling frequency:
     Operating principle:

 Test Results':
     Accuracy {%)
     Response time (min)
     Recovery time (min)
     Product activation
         height (cm)
qualitative
continuous
float switch
Ccmmsrc::!   Commercial
Gasoline"    Gasoline'"
100         100
3.66         3.45
                                                                                                                                            1.28
                                                                                    Lower Detection Limit (cm)  1.84
                                           1.27
                                           1.65
                                                                                    * at a flow rate of 0.19 gal/hr in 7.6 cm diameter test chamber

                                                                                Specificity Result*:

                                                                                    Activated:   diesel fuel, synthetic fuel, home heating oil #2, water

                                                                                Manufacturer's Specifications:
                                                                               Comments:  EPA and many states require detection of 1/8 inch of product, which is 0.32 cm, for
                                                                                            ground water monitoring. The test procedures used were those in Carnegie Mellon
                                                                                            Research Institute's "Test Procedures for Third Party Evaluation of Leak Detection
                                                                                            Methods: Point Sensor Liquid Contact Leak Detection Systems": Final Report -
                                                                                            November 11, 1991.
                                                                                                              •• TLS-250, TLS 250i Plus, ILS 250
                                                                                                              ••• ILS 350, TLS-350
Vndir-Root
125 Powder Form Dr.
SImtbury, CT 06070-2003
Tel: (203) 851-2700
                     Evaluator: Ctrmgia Matlon Ratearch Institute


                     Date of Evaluation: 07-17-92
                                                                                                                                                        192

-------
                                        Veedtr-Root

                      TLS-250. TLS 2501 Plus, ILS 250, ILS 350. TLS-350
                    Interstitial Liquid Sensor for StMl Tanks (0794390420)

                           LIQUID-PHASE INTERSTITIAL DETECTOR
Dsttctor:
    Output type:
    Sampling frequency:
    Operating principle:

Test Results:
    Accuracy (%)
    Response time (min)
qualitative
continuous
float switch
Commercial   Commercial
Gasoline'     Gasoline"
100         100
6.00         6.51
Product activation
    height (cm)            3.67         3.62
Lower Detection Limit (cm)  4.05         4.17
SpacHicity Results:

     Activated:   diesel fuel, synthetic fuel, home heating oil #2, water

Manufacturer's Specifications:
Comments:  EPA and many states require detection of 1/8 inch of product, which is 0.32 cm, for
             ground water monitoring. The test procedures used were those in Carnegie Mellon
             Research Institute's "Test Procedures for Third Party Evaluation of Leak Detection
             Methods: Point Sensor Liquid Contact Leak Detection Systems": Final Report -
             November 11, 1991.
 * TLS-250, TLS 250i Plus, ILS 250, at a flow rate of 0.13 gal/hr in 4.8 cm diameter test chamber
 **  ILS 350, TLS-350, at a flow rate of 0.12 gal/hr in 4.8 cm diameter test chamber
Veedar-Root
125 Powder Forest Dr.
Simaburv. CT 0607O-2O03
Tel: (203) 851-270O
                                                    Evaluator: Carnegie Mellon Research Institute
                      D«to of Evaluation: 07-17-92
                                            193
                                                                                                                       Veeder-Root

                                                                                                     TLS-250i, TLS 250i Plus, ILS 250, ILS 350, TLS-350
                                                                                                          Liquid Sensor for Sumps (0794390-206)

                                                                                                          LIQUID-PHASE INTERSTITIAL DETECTOR
                                                                                                              Detector:
Output type:               qualitative
Sampling frequency:        continuous
Operating principle:         float switch
                                                                                Test Results:
                                                                                    Accuracy (%)
                                                                                   * Response time (min)
                                                                                    RflnnuAru timo fn^in\
                                                                                    Product activation
                                                                                        height (cm)
                          Commercial
                          Gasoline'
                          100
                          8.19
                                                                                                                                            4.12
                                                                                                                  Lower Detection Limit (cm)  4.67
                                                                                                                                                    Commercial
                                                                                                                                                    Gasoline"
                                                                                                                                                    100
                                                                                                                                                    8.49
                                      3.95
                                      4.36
                                                                                Specificity Results:

                                                                                    Activated:    diesel fuel, synthetic fuel, home heating oil #2, water

                                                                                Manufacturer's Specifications:
                                                                                Comments:  EPA and many states require detection of 1/8 inch of product, which is 0.32 cm, for
                                                                                            ground water monitoring. The test procedures used were those in Carnegie Mellon
                                                                                            Research Institute's "Test Procedures for Third Party Evaluation of Leak Detection
                                                                                            Methods: Point Sensor Liquid Contact Leak Detection Systems":  Final Report -
                                                                                            November 11, 1991.
                                                                                * TLS-250, TLS 250i Plus, ILS 250, at a flow rate of 0.15 gal/hr in 5.8 cm diameter test chamber
                                                                                ••  ILS 350, TLS-350, at a flow rate of 0.14 gal/hr in 5.8 cm diameter test chamber
                                                                               Veeder-Root
                                                                               125 Powder Forest Dr.
                                                                               Simsbury, CT 06O7O-2003
                                                                               Tel: (203) 851-2700
                                                                                                                                                                 Evaluator: Carnegie Mellon Research Institute
                                                                                                                                   Date of Evaluation: 07-17-92
                                                                                                                                                         194

-------
                                       Veeder-Root
                                                                               DRAFT
                                        TLS-360
   Solid-State Pan/Sump Sensor (794380-321. -3S1). Piping Sump Sensor (794380-208), Micro
                                   Swisor (794380-340)
Detector:

    Output type:
    Sampling frequency:
    Operating principle:

Test Results:
                          LIQUID-PHASE INTERSTITIAL DETECTOR
qualitative
continuous
product permeable / ultrasonic / float switch
Piping Sumo Sensor (794380-208)
    Win. Product Level (cm)
    Precision
    Detection Time (sec)
                                          Gasoline     Diesel
             3.51
             0.011
Solid-State Pan/Sumo Sensor (794380-321. -351)
    Min. Product Thickness (cm)             2.60
    Precision                              0.010
    Detection Time (sec)                    < 1
Micro Sensor 1794380-3401
    Min. Product Thickness (cm)
    Precision
    Detection Time (sec)
Specificity Results i%i:

    Commercial gasoline    100
    Diesel Fuel            100
    Water                 100

Manufacturer's Specifications:
             0.51
             0.011
3.40
0.011
                         2.50
                         0.010
0.46
0.007
Water

3.03
0.011
             2.60
             0.010
0.48
0.007
                                                                                                                   Veeder-Root

                                                                                                                 ILS 350. TLS-360
                                                                                                               Adsistor Vapor Probes

                                                                                                 VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                                                          Detector:
                                                    Output type:         qualitative
                                                    Sampling frequency:   continuous
                                                    Operating principle:   edsistor
Test Results:
                         Commercial       Synthetic
                         Gasoline          Gasoline         JP-4
Accuracy (%):                 100              0           100
Detection Time (min:sec):        7:46        NotApp.        17:01
Fall Time (min:sec):            2:38         Not App.        3:05
Lower Detection Limit (ppm):    500         >1000          500
Specificity Results <%):

    Activated:    Commercial gasoline, JP-4 jet fuel
    No response: n-Hexane, Synthetic gasoline. Toluene, Xylene(s)

Manufacturer's Specifications:
                                                                             Comments:  The test procedures used were those in Radian Corporation's draft report
                                                                                         "Development of Procedures to Assess the Performance of External Leak Detection
                                                                                         Devices: Vapor-Phase ASTM-Forrnatted Methods," Juns 2S, 1SSO.
 Comments:   EPA and many states require detection of 118 inch of product, which is 0.32 cm, for
             ground water monitoring. The test procedures used were modified by the evaluator
             from those in EPA's "Standard Test Procedures for Evaluation Leak Detection
             Methods: Liquid-Phase Out-of-Tank Product Detectors," March 1990.
 Veeder-Root
 125 Powd«r Form Dr.
 Sfm«burv, CT 08070-2003
 Tel: (203) 051-2700
                                                       Evahietor: Ken Wilcox Anoclatei
                          D«U of Evaluation: 10-20-94
                                                                             Veeder-Root
                                                                             125 Powder Forest Dr.
                                                                             Simibury, CT 06070-2003
                                                                             Tel: (203)851-2700
                                                                                                      Evaluitor: Cernegle Mellon Reieerch Institute


                                                                                                      Due of EviluMlon: 07-24-92
                                           195
                                                                                                                                                     196

-------
                                        Vaeder-Root

                           TLS-350 Line Leak Detector, Series 8475
                                                                            DRAFT
                      AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification:           Leak rate of 3.0 gallons per hour with PD = 100% & PFA=0%.

Leak Threshold:        1.5 gallons per hour (a leak is declared if the output of the measurement
                      system exceeds this threshold).

Applicability:           Gasoline, diesel, aviation fuel, and solvent.

Specification:          System is installed on pressurized fiberglass and steel piping.
                      The piping system volume  must not exceed 41 gallons.
                      Tests are conducted at the line operating pressure.
                      The mechanical line leak detector must be removed from the pipeline
          .            ftyftt6rn:            	

                      System is installed on pressurized flexible piping.  The piping volume must
                      not exceed 158.4 gallons.  Tests are  conducted at the line  operating
                      pressure. The mechanical  line leak detector must be. removed from the
                      pipeline.

Waiting Time:         There is no waiting period  between product delivery and testing.
                      Minimum waiting period between last dispensing and testing depends on
                      volume of product and temperature gradient which is determined by the
                      system's computer.

Tast Period:           The minimum data collection time (response tims) is 12 minutes.
                      Test data must be acquired and recorded by a microprocessor.
                      Calculations are automatically done by the microprocessor.

Systim Features:      This system is permanently installed on the pipeline and automatically tests
                      the line.
                      Uses a preset threshold and a single test to determine whether the pipeline
                      is leaking.
                     ' If a leak is declared, this system displays a message and triggers an alarm.

Calibration:           Equipment must be checked and calibrated annually in accordance with
                      manufacturer's instructions.
 Vood.r-Root
 12.5 Powder Fonit Driva
 Simsbury, CT 08070-2003
 T»l: (203) 851-2700
Evaluetor: Ken Wilcox AuociatM, Inc.


Date of Evaluation: 08/04/93
                                             197
                                                                                            Veeder-Root

                                                                               TLS-350 Line Leak Detector, Series 8475
                                                                           AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

                                                    Certification:          Leak rate of 0.20 gallon per hour with P0 = 100.0% &PFA=0%.

                                                    Leak Threshold:        0.10 gallon per hour (a leak is declared if the output of the measurement
                                                                          system exceeds this threshold).

                                                    Applicability:          Gasoline, diesel, aviation fuel, and solvent.

                                                    Specification:          System is installed on pressurized fiberglass and steel piping.
                                                                          The piping system volume must not exceed 41 gallons.
                                                                          Tests are conducted at the line operating pressure.
                                                                          The mechanical  line leak detector must be removed from the pipeline
                                                                          system.

                                                                          System is installed on pressurized flexible piping. The piping volume must
                                                                          not exceed 158.4 gallons.  Tests are conducted at the line operating
                                                                          pressure. The mechanical line leak detector must be removed from the
                                                                          pipeline.

                                                    Waiting Time:         There is no waiting period between product delivery and testing.
                                                                          Minimum waiting period between last dispensing and testing depends on
                                                                          volume of product and temperature gradient which is determined by the
                                                                          system's computer.

                                                    Test Period:           Minimum data collection time must be 0.75 to 8.85 hours.
                                                                          Test data must be acquired and recorded by a microprocessor.
                                                                          Calculations are automatically done by the microprocessor.

                                                    System Features:      This system is permanently installed on the pipeline and automatically tests
                                                                          the line.
                                                                          Uses a preset threshold and a single test to determine whether the pipeline
                                                                          is leaking.
                                                                          If a leak is declared, this system  displays a message, triggers an alarm, and
                                                                          shuts down the  dispensing system.

                                                    Calibration:            Equipment must be checked annually and calibrated in accordance with
                                                                          manufacturer's instructions.
Veeder-Root
125 Powder Forest Driva
Sirmbury, CT 08070-2003
Tel: (203) 851-2700
Evaluator: Kan Wilcox Aitociatai


Data of Evaluation: 08/04/93
                                                                                                                                                         198

-------
                                       Veader-Root

                          TLS-350 Una Laak Detector. Serbs 8475
                                                                      DRAFT
                      AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification:          Leak rate of 0.1 nation per hour with P0 = 100.0% & PFA-0%.

Leak Threshold:       0.079 gallon per hour (a leak is declared if the output of the measurement
                     system exceeds this threshold).

App!tea«3fty:          Gasoline, diassl, aviation fuel, and solvent.

Specification:         System is installed on pressurized fiberglass and steel piping.
                     The piping system volume must not exceed 41 gallons.
                     Tests are conducted at the line operating pressure.
                     The mechanical line leak detector must be removed from the pipeline
                     system.

                     System is installed on pressurized flexible piping. The piping volume must
                     not exceed 158.4 gallons.  Tests are conducted at the line operating
                     pressure.  The mechanical line leak detector must be removed from the
                     pipeline.

Waiting Time:        There is no waiting period between  product delivery and testing.
                     Minimum waiting period between last dispensing and testing depends on
                     volume of product and temperature  gradient which  is determined by the
                     system's computer.

Test Period:          Minimum data collection time must  be 1.2 to 12.9 hours.
                     Test data must be acquired and recorded by a microprocessor.
                     Calculations are automatically done by the microprocessor.

System Features:     This system is permanently installed on the pipeline and automatically tests
                     the line.
                     Uses a preset threshold and a single test to determine whether the pipeline
                     is leaking.
                      If a leak is declared, this system displays a message, triggers an alarm, and
                     shuts down the dispensing system.

Calibration:           Equipment must be checked annually and calibrated in accordance with
                      manufacturer's instructions.
 125 Powd.f Forwt Driv.
 Simtbory, CT 06070-2003
 TW: (203) 651-2700
Evduitor: Km Wrioox Atiodxii


Dttt of Evjiuition: OBW4/93
                                            199
                                                       Certification:

                                                       Leak Threshold:


                                                       Applicability:

                                                       Specification:
                                                       Waiting Time:


                                                       Test Period:



                                                       System Features:
                                                      Calibration:
                   Veeder-Root

        TLS Line Leak Detector. Series 8484


  AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

 Leak rate of 3.0 gallon per hour with PD=100.0% & P,A=0%.

 1.88 gallon per hour (a leak is declared if the output of the measurement
 system exceeds this threshold).

 Gasoline, diesel, aviation fuel, and solvent.

 System is installed on pressurized fiberglass and steel piping.
 The piping system volume must not exceed 89 gallons.
 Tests are conducted at the line operating  pressure.
 The mechanical line leak detector must be removed from the pipeline
 system.

 There is no waiting period between product delivery and testing
 Minimum waiting period between last dispensing and testing is 0.27 hours.

 The minimum data collection time (response time) is 0.008 hours
 Test data  must be acquired and recorded by a microprocessor
 Calculations are automatically done by the microprocessor.

            is permanently installed on the pipeline and automatically tests
                                                                           is leaking.
 hrt     *' *'* 8V*tem di8plav* a meMaSe'
shuts down the dispensing system.
                                                                                                                                         . and
                                                                           Equipment must be checked annually and calibrated in accordance with
                                                                           manufacturer's instructions.
                                                                                                              VMder-Root
                                                                                                              126 Powdsr Form Driv«
                                                                                                              Slrmbury, CT 06070-2003
                                                                                                              T4: (203) 051-2700
                                                                                                            Evaluttor: Mdwnt Rnurch Imtituu


                                                                                                            Dtti of Eviluitlon: 08/07/91
                                                                                                                                                        200

-------
                                       Veeder-Root

                            TLS Line Leak Detector, Series 8484
                                                                           DRAFT
                      AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification:      Leak rate of 0.10 oallon per hour with P0 = 100.0% & PFA=0%.

Leak Threshold:   0.05 gallon per hour (a leak is declared if the output of the measurement system
                 exceeds this threshold).

Applicability:      Gasoline, diesel, aviation fuel, and solvent.

Specification:     System is installed on pressurized fiberglass and steel piping.
                 The piping system volume must not exceed 89 gallons.
                 Tests are conducted at the line operating pressure.
                 The mechanical line leak detector must be removed from the pipeline system.

Waiting Time:     There is no waiting period between product delivery and testing.
                 Minimum waiting period between last dispensing and testing is 2.5 hours.

Test Period:      The minimum data collection (response time) is 0.3 hours
                 Test data must be acquired and recorded by a microprocessor.
                 Calculations are automatically done by the microprocessor.

System Features:  This system is permanently installed  on the pipeline and automatically tests the
                 line.
                 Uses a preset threshold and a single  teat to determine whether the pipeline is
                 leaking.
                 If a leak is declared, this system displays a message, triggers an alarm, and
                 shuts down the dispensing system.

Calibration:       Equipment must be checked annually and calibrated in accordance with
                 manufacturer's instructions.
 V««Jw-Root
 125 Powdtt Forwl Driv*
 Sbmburv, CT 08070-2003
 Tel: (203) 851-2700
Evahutor: Mdw«t RwMreh IratituM


Dltt Qf Evaklrton: 08/07/81
                                           201
                                                                                                                            DRAFT
                                                      Certification:


                                                      Leak Threshold:

                                                      Applicability:

                                                      Tank Capacity:

                                                      Data Requirement:
             Warren Rogers Associates, Inc.

WRA Statistical Inventory Analysis, Version 5.1 (quantitative)


STATISTICAL INVENTORY RECONCILIATION TEST METHOD

    Method is certified to detect a 0.1 gph leak rate with PD = 99.98% &
    PFA=0.02%.

    A leak is declared when leak rate exceeds 0.05 gallons per hour.

    Gasoline, diesel, aviation fuel,  and fuel oil #4.

    Maximum tank capacity may not exceed 18,000 gallons.

    Minimum 30 days of product level and flow through data.

    AJJ 41 data sats wara analyzed with conclusive results.  	         	

    The median monthly throughput for tanks used in the evaluation was 1000
    gallons.

    Leak rates of 0.05, 0.10, and 0.20 gph were used in this evaluation.

    A portion of the data used in the evaluation was supplied by the vendor.

    This evaluation did not include data from manifolded tanks.
                                                                                                              Wwrm Room AuociitM, (no.
                                                                                                              747 AquMnwk Avwwi
                                                                                                              MMdMown, HI 02840
                                                                                                              Til: (401) 846-4747
                                                                                                             Evriiutor: Km Wilcox AnoeiitM


                                                                                                             DIM of Evaluation: 12-18-90
                                                                                                 202

-------
                                  Warrick Cwitrois, few.

                                   Mode! 5700 Meter
                                     PVP-2 Sensor

                    VAPOR PHASE OUT-OF-TANK PRODUCT DETECTOR
                                                                     DRAFT
Detector:

Output type:
Sampling frequency:
Operating principle:
quantitative
continuous
adsistor
Test Results:
Accuracy* (%):
Bias* (%):
Precision* (%):
Detection Time* (mini:
Fall Time* (min):
Lower Detection Limit (ppm):
Commercial
Gasoline
25.4
14.4
7.6
>60
38
1353.3
Synthetic
Gasoline
-100.0
-100.0
Not det.
Not app.
Not app.
Not det.

JP-4
157.1
108.3
20.4
>60
>60
Not det.
Specificity Results (%):

    Not activated:     Commercial gasoline. Synthetic gasoline, JP-4 jet fuel, n-Hexane, Toluene,
                     Xylene(s)

Manufacturer's Specifications:


Comments:   The test procedures used were those in Radian Corporation's draft report.
             "Development of Procedures to Assess the Performance of External Leak Detection
             Devices: Vapor-Phase ASTM-Formatted Methods," June 29, 1990.
 Werriclt Control!, Inc.
 4737 Normandy Court
 Royel Otk, Ml 44073
 Tel: (313) 545-2512
                                  Ev«luilor: Carnegie Mellon Retieroh Imitate


                                  Dtte of Evetuation: 08-10-91
                                           203
                                                                                                                     Xerxes Corporation

                                                                                                        Xerxes Trucheck Hydrostatic Monitoring System
                                                                                                                                                   DRAFT
                        DOUBLE WALLED TANK TIGHTNESS TEST

Certification:         Leak rate of 0.1 gallon per hour with PD = 99% & PFA=1%.

Leak Threshold:       0.05 gallon per hour (a leak is declared if the output of the measurement
                    system exceeds this threshold).

ApplicablHy:         Gasoline, diesel, aviation fuel, and fuel oil *4.

Capacity:            The maximum tank capacity must be 30,000 gallons.
                    The tank may be tested from 0 to 100% full.

Waiting Time:        There is no waiting time between product delivery and test data collection.

Test Period:          The minimum data collection time must be 10 hours.

Ground Water:        Ground water depth must be determined before and after the test. When
                    ground water level is above the bottom of the tank but below the top, the
                    test should be repeated if the ground water level increases by more than 7
                    inches during the test. When ground water is above the tank, the test
                    should be repeated if the ground water level increases by more than 5
                    inches.
XtncM Corporation
7901 XMXM Av«.
MmneepoUt, MN 55431
Tel: (612) 817-1880
Eveluotor: Robert Plunkttt, Ph.D.


DIM of Ewlueilon: 01/07/13
                                                                                                                                                204

-------
                        "
UNDER REVIEW SECTION
 ALPHABETICAL BY COMPANY
        January 17, 1995

-------

-------
Manufacturer
                              UNDER REVffiW
                       System;
                       Test Type
                                Kraluator;
                                Date of Evaluation
                                                                                            Manufacturer
                                                                                                    UNDER REVIEW
                                                            system;
                                                            Test Tvoe
                                                      •valuator;
                                                      Data of Evaluation
Alert Technologies



Andovar Control*




Armstrong Monitoring



Armstrong Monitoring


Caldwell Systems



Cuopo/Millar




Campo/Millar



Computerizing




Environment G Safety




Gora 6 Associates


Heath Consultants




HHU
2000-X 6 2000-XB;
Automatic Tank Gauging System
(0.1 and 0.2 gph)


Andovar Infinity CX9000,
CX9200, and CKX240;
Automatic Tank Gauging System
(0.2 gph)


Alertmaater 5100i AMC-5007;
Liquid-Phase Product Datactor


Alartmaater 5100: AMC F4000;
Vapor-Phaaa Product Datactor


TM-700, ATG-100;
Automatic Tank Gauging Syaten
(0.1 and 0.2 gph)


LS300-120. PLUS,
LS300-120 PLUS A/Sf
Lina Leak Detector  (0.2 gph)


PL400;
Lina Tightness Teat
Computank V. 3.0;
Statistical Inventory
Racbnciliation
 EASI Level-Tru;
 Automatic Tank Gauging Syetem
 (0.1 gph)

 Leak Learn  Modal 1000;
 Liquid-Pha«e Product Datactor


 Quick  Chack 2000;
 Volumetric  Tank Tightness
 Test  (Overfilled)


 .DL-101,  10.2 aV Probe,
 HW-101,  11.7 aV Probe,
 ISPI-101,  10.2 ev Probe,
 PI-101,  11.7 aV Probe;
 Vapor-Phase Product Datactor
Ken Hilcox AoaociataB;
02-28-94 £ 06-22-94
Kan Hilcox ABBOciataa;
05-24-93
Environment Canada;
12-03-92


Environment Canada;
12-03-92


Hyla Labs; HWGA
01-20-89; 07-17-89
Jetronix Radio
Engineering;
05-16-91


Jetronix Radio
Engineering;
05-16-91

Ken Hilcox Associates;
09-17-92
                                Midweat  Reaearch Institute
 Carnegie Mellon Research
 Institute

 Midwest Research
 Institute;
 03-12-90

 Carnegie Mellon Research
 Institute
                                                                                            Incon Environmental
                                      Incon Environmental
                                      Kaekor Environmental
                                      Products
Mallory Controls
                                      Marley Pump
Mine Safety
Appliance
                                                                      NDE Environmental
                                                                      Petro Vend
                                      Petro Vend
Practical Tank
Management
Southeastern Liquid
Analyzers
                                                                                             Tanknology
TS 1000;
Automatic Tank Gauging System
(0.1 gph)

TS 2000;
Automatic Tank Gauging. System
(0.1 gph)

TankTite Leak Detection
Kernal Version 1.0;
Automatic Tank Gauging System
(0.2 gph)

Pollulert Probes MD210,
HD210RA, MD221TJ, MD221TJRA;
ST 1400-1800, ATG, FMS,  6
LLM;
Continuous Leak Detect.
System
(ATGS)

Tank-Check;
Vapor-Phase Product Detector
Computerized VPLT;
Volumetric Tank Tightness
Test  (overfilled)


Petrosonic III, Version
4.04C;
Automatic Tank Gauging System

SiteSentinel;
Automatic Tank Gauging System


Tank  Management System 10;
Statistical Inventory
Reconciliation (Quantitative)


Tank  Chek 4.0;
Statistical Inventory
Reconciliation (Qualitative)


VacuTact;
Nonvolumetric Tank Tightness
Test  (Low Level Large Tank)
                                                      Ken Hilcox Associates;
                                                      08-05-92
                                                      Ken Rilcox Associates;
                                                      05-10-91
                                                      Arizona State Univ.;
                                                      10-25-94
Radian Corporation;
07-08-91
                                                      ADA Technologies;
                                                      10-12-92
Carnegie Mellon Research
Institute;
05-31-91

Vista Research;
06-17-91
                                                                                            Underwriters Laboratories;
                                                                                            11-94
Underwriters Laboratories;
11-94

Ken Hilcox Associates;
12-02-91
Petro Horks;
06-03-93
                                                                                                                                                   Kan Hilcox Associates;

-------
                              UNDER REVIEW
Hanufactnrar



Tidal Engineering



Tidal Engineering



Tracer Research



USTest
•vstea;
Best from
ENS 2000, 3000,  3500;
Automatic Tank Oauging System
(0.1 gph test)


BMS-3000: 301-0327-001, 301-
0329-001;
Liquid-Phase Product Detector


Tracer Sight;
Vapor-Phase Product Detector
                       DST 2000/P;
                       Volumetric Tank Tightness
                       Test  (Large Tanks G Low Level
                       Testing)
(valuator;
Date of Evaluation
Ken Wilcox Associates;
02-10-93
Radian Corporation;
07-08-91
Control Strategies
engineering;
05-77-92
                               Kan Wilcox Associates;
                               08-04-92

-------
                    *»   <*
GLOSSARY
  January 17, 1995

-------

-------
                            GLOSSARY     J

Aoenitacy:  The degree to which the measured leak rate agrees with
the induced leak rate on the average.   If a method is accurate,
it has a very small or zero bias.

Le»k threshold:  This is the measured leak rate at which the test
method declares the tank to be leaking.  This leak rate will
always be less than or equal to the leak rate requirement for the
various release detection (RD) methods given in 40 CFR S 280
Subpart D-Release Detection.  (Please note that some states and
other regulatory authorities may have different requirements).
The Minimum threshold for declaring a leak is experimentally
determined from the results of the evaluation of the RD method.

Specificity:  Specificity applies to vapor and liquid sensors and
lists products or components of products that these sensors can
detect.  Specificity for quantitative sensors is the ratio of
sensor output, or measured concentration, to the actual
concentration of hydrocarbon test gas expressed as a percentage.
Specificity for qualitative sensors is reported as activated if
the sensor responds within 24 hours.  Otherwise, specificity is
reported as inactivated.

Ullage Teat:  An ullage test tests the un-wetted portion of the
tank, or that portion of the tank that is not in contact with
product.  These tests can use a variety of physical phenomena'
including acoustical signals and pressure gain or loss in the
ullage space of a sealed system.

Resolution:  The resolution of a measurement system is the
smallest change in the quantity being measured which the system
is capable of detecting.

Precision:  The degree of agreement of repeated measurements of
the same parameter.  Precision estimates reflect random error and
are not  affected by bias.

Probe:   A component of a detection system that must come into
contact  with product before product can be detected or measured.

Qualitative Responses:  The type of detector response that
indicates only the presence or absence of product without
determining the specific product concentration or thickness.

Quantitative Response:  A type of detector response that
quantifies the concentration  or thickness of product present.
 False Alarm:
 tight.
Declaring a tank to be leaking when in fact it is
Probability of raise Alarm, P(TA):  The probability of declaring
a tank to be leaking when it  is tight.  It is usually expressed
as a percentage.

Probability of Detection,  P(D):  The probability of detecting a
leak of a given size and is usually expressed as a percentage.

Activated:  Refers to the state of a qualitative detector's
response when indicating the  presence of product.

Continuous Detector:  Detectors that operate continuously and are
always present and are never  turned off.

Intermittent Detector:  Detectors that monitor on a regular
basis.  An intermittent detector may be a hand held device that
is portable or a permanently  installed device that is used to
periodically test for the presence of product.

Response Time:  A general term that refers to the more specific
terms of lag time, rise time, and fall time.

Rise Time:  The elapsed time  from a detector's first detectable
signal in response to the presence of product to an output that
is 95% of full scale for a quantitative detector or activated for
a qualitative detector.

Lag Time:  The elapsed time from the detector's first contact
with test product to the first detectable signal.

Detection Time:  The sum of rise time and lag time.

Vail Time:  The elapsed time  after a detector has responded to a
test hydrocarbon and is removed and has recovered to 95% of its
original baseline level or there is no detectable signal output.

Manifolded Tanks:  Manifolded tanks are those tanks that are
connected by piping that allows the tank system to function as a
single tank.  A typical manifolded tank system usually consists
of two tanks connected by a syphon tube that permits the product
in the tanks to be at the same level while product is being
pumped out of only one tank.

Hominal Leak Rate:  The set or target leak rate to be achieved as
closely as possible during the evaluation of a leak detection
method.  It is a positive number expressed in gallons per hour
(gal/h).

Induced Leak Rate:  The actual leak rate, in gal/h, used during
the evaluation against which  the results from a given test device
will be compared.
                                                                                                                           DRAFT

-------
Measured Leak Sat*:  A positive number, in gal/h, measured by the
test device that indicates the amount of product leaking out of
the tank.  A negative number would indicate that something was
being added to the tank.  The performance of a method is based on
how well the measured leak rate compares to the actual induced
leak rate.