EPA
         United States
         Environmental Protection
         Agency	
         Office of Water fWH-550)
             EPA 570/9-91-003
             May 1991
Manual of
Small Public
Water Supply
Systems

-------

-------
                                  PREFACE
     Healthful, comfortable living requires the availability of an adequate supply of high
quality water for drinking and domestic purposes.
     Whenever feasible, a community should consider obtaining water  from a public
water system hi order to enjoy the advantages of qualified supervision under the control
of a responsible public agency.  A public water system usually provides the best way to
assure an uninterrupted supply of safe water.
     This manual is primarily directed to the individual or institution faced with managing
or operating a small public water system.  This manual is an update to the EPA Manual
of Individual Water Supply  Systems which was published in 1982.  EPA is issuing this
revision of the manual to present current concepts and practices  to the public water
system owner.   This is in  response  to the  greater public awareness of health and
environmental issues, and advances in water treatment practices.
     EPA and others have noted a tremendous need for information and assistance to
very small systems.  These needs include  engineering solutions, such as appropriate
equipment to treat water and operations improvements. Non-engineering issues also have
become a primary focus of concern which will require  more attention in water supply
improvement efforts.  Among these concerns are proper financing and management of
water supply improvements, community involvement in water supply, institutional support,
and development of human resources for improved operations and management of water
supplies.
     The solutions offered in  this manual are the result  of the work  of many U.S.
agencies, individuals, and international organizations dedicated to the upkeep of safe and
reliable water supply. In fact, many of the problems and solutions identified have been
studied worldwide.  Through this manual, EPA will be able to offer practical assistance
to the many very small public water suppliers in the U.S., as well as those with similar
operating conditions elsewhere, through such programs as the U.S. Peace Corps. This
manual should be useful to other Federal agencies concerned with the development of
small water supplies, and to State and local health departments, well drillers, contractors,
as well as to owners and operators of any system which  supplies drinking water.
     As with the previous manual for individual and small water supplies, I hope that this
manual will be a practical tool to many thousands of rural water systems in their enduring
effort to supply safe and reliable drinking water.

                                                                  James R. Elder

-------
                          ACKNOWLEDGMENT
     This manual follows the general format of its predecessors:  U.S. Public Health
Service Publication No. 24, prepared by the Joint Committee on Rural Sanitation, and the
U.S. EPA Manual of Individual Water Supply Systems, which was prepared under the
direction of Mr. W. J. Whifsell.
     Overall planning and management for the preparation of this manual was provided
by Mr. Marc J. Parrotta, Environmental Engineer, U.S. EPA Office of Drinking Water.
The support by those who prepared this manual which is technologically updated and
more responsive to emerging environmental concerns is highly regarded.
     Further, EPA acknowledges the valuable contributions  of others who wrote and
reviewed parts of this manual. EPA is especially indebted to the following who deserve
particular acknowledgement for then: contributions to this manual: Mark A. Thompson
and Glenn M. Tillman of Malcolm Pirnie, Inc.; Frank Bell, Jr., Paul S. Berger, Walt Feige,
Benjamin P. Smith, James E. Smith, Jr., and James J. Westrick of U.S. EPA; T. David
Chinn of the American Water Works Association; Meg Harvey of ECOS, Inc.; and John
Trax of the National Rural Water Association.

-------
                                 CONTENTS

Preface  	  i

Introduction
      Overview of Small Public Water Systems	  1
      SDWA Requirements	  1
      General Requirements	2
      Institutional Concerns  	2
      Operations	3

Part I - Selection and Management of a Water Source
      Introduction	7
      Rights to  the Use of Water  	7
      Sources of Water Supply	  7
      Quality of Water  	  10
      Safe Drinking Water Act (SDWA)	  17
      Water Testing and Labs	  21
      Contaminant Sources	  21
      Quantity of Water	  22
      Water Conservation	  24
      Fire Protection	  25
      Sanitary Survey  	  27

Part II - Ground Water
      Rock Formations	  33
      Ground Water Basins	  33
      Sanitary Quality	  34
      Chemical  and Physical Quality . .	  34
      Distance to Sources of Contamination	  35
      Evaluating Contamination Threats	  36
      Development of Ground Water	  38
      Construction of Wells	  44
      Sanitary Construction of Wells	  58
      Abandonment of Wells	  63
      Reconstruction of Existing Dug Wells	  63
      Special Considerations in Constructing Artesian Wells	  64
      Springs  and Infiltration Galleries  	  64

Part III - Surface Water for Rural Use
      Introduction	  65
      Sources of Surface Water	  66
      Development of Springs  	  74
      Infiltration Galleries	  76
                                                                             111

-------
Part TV - Water Treatment
     Need and Purpose	  79
     Water Treatment	  80
     Disinfection	  83
     Disinfection with Ultraviolet Light  	  89
     Disinfection with Ozone	  90
     Membrane Technologies  	  90
     Aeration	  91
     Other Treatment	  91
     Package Plants	  98
     Household Water Treatment  	  100
     Treatment Waste Disposal	  103
                            «
Part V-Pumping Distribution and Storage
     Types of Well Pumps	  105
     Selection of Pumping Equipment	  113
     Sanitary Protection of Pumping Facilities  	  120
     Installation of Pumping Equipment	  121
     Alternate Energy Sources and Pumps	  123
     Pumphousing and Appurtenances	  126
     Cross-Connections	  136
     Pipe and Fittings	  138
     Pipe Capacity and Head Loss	  139
     Protection of Distribution Systems  	  142
     Disinfection of Distribution System	  142
     Determination of Storage Volume  	  143
     Protection of Storage Facilities	  144

Part VI - Information, Assistance and Community Support
     Introduction	  149
     Information Resources	:	  149
     Community Involvement	  150
     Technical Assistance and Training	  151
     Financial Assistance	  153
     Water Rates	  155
     Personal Computers	  157
     Institutional Alternatives	  157

Bibliography	  161
IV

-------
Appendices:

     A. Health Effects, Source of Contamination, and Treatment  	  167
     B. Collection and Analysis of Bacteriological Samples	  175
     C. Identification by Human Senses	  177
     D. Recommended Procedure for Cement Grouting of Wells for
       Sanitary Protection	  189
     E. Emergency Disinfection	  191
     F. State Drinking Water Agencies	  195
     G. EPA Drinking Water Offices	  199
     H. National Organizations  	  201
     I. Farmers Home Administration Offices  	  203

Index	  207
                               LIST OF TABLES

Table                                                                  Page

1.    Maximum Contaminant Levels (MCLs)  .....'	  18
2.    Secondary Maximum Contaminant Levels (SMCLs)   	  19
3.    Planning guide for water use	  23
4.    Average household water use activities	  24
5.    Suitability of well construction methods to different geological
     conditions	  43
6.    Steel pipe and casing, standard and standard line pipe	  53
7.    Quantities of calcium hypochlorite and liquid calcium hypochlorite
     required for water well disinfection	  61
8.    Recommended mechanical analysis of slow sand filter media	  82
9.    Information on pumps	116,117
10.   Allowance in equivalent length of pipe for friction loss in
     valves and threaded fittings	 141
11.   Seven-minute peak demand period usage  	 143
12.   Tank selection chart-gallons	 144

-------
                           LIST OF ILLUSTRATIONS
Figure
Page
1.   The hydrologic cycle	8
2.   Pumping effects on aquifers	 40
3.   Dug well with two-pipe jet pump installation	 45
4.   Different kinds of drive-well points	 46
5.   Well-point driving methods	 47
6.   Hand-bored well with driven-well point and "shallow well" jet
     pump	 49
7.   Drilled well with submersible pump  	 51
8.   Well seal for jet pump installation  	 56
9.   Well seal for submersible pump installation	 57
10.  Yield of impervious catchment area  	 67
11.  Cistern	 70
12.  Pond	 72
13.  Schematic diagram of pond water-treatment system	 73
14.  Spring protection	 75
15.  Slow sand filtration diagram	 81
16.  Package Plant Diagram 	 99
17.  Exploded view of submersible pump	  107
18.  "Over-the-weU" jet  pump installation	  108
19.  Typical solar pump systems	  109
20.  Typical wind powered pumps	  110
21.  Typical hand pumps	  112
22.  Typical air lift pump	  113
23.  Typical hydraulic ram	  114
24.  Determining recommended pump capacity 	  118
25.  Components of total operating head in well pump installations  	  119
26.  Vertical (line shaft) turbine pump mounted on well casing	  122
27.  Pumphouse	  127
28.  Clamp-on pitless adapter for submersible pump installation	  129
29.  Pitless unit with concentric external piping for jet pump
     installation	  130
30.  Weld-on pitless adapter with concentric external piping for
     "shallow well" pump installation  	  131
31.  Pitless adapter with submersible pump installation for
     basement storage	  132
32.  Pitless adapter and unit testing equipment	  135
33.  Head loss versus pipe size 	  140
34.  Typical concrete reservoir	  146
35.  Typical valve and box, manhole covers, and piping installations  ......  147
36.  Sources of Information and Assistance  	  152
 VI

-------
                          Introduction
 OVERVIEW  OF  SMALL  PUBLIC  WATER SYSTEMS
      Public demands for safe and dependable drinking water have a major effect on those
 who own or manage water supplies. Among the thousands of small public water systems
 in the U.S., many do not have the technical and information resources to meet the public's
 demands.
      A public water system is one that serves at least 15 connections or at least 25
 individuals.  EPA regulations apply to public water systems,  and should be followed
 because  of the importance of water  quality and  the  health  risks  associated with
 contaminants.
      Water systems must provide high quality drinking water at a low cost. Essential to
 this task are:  developing information sources, monitoring water quality, providing good
 system operation, and establishing preventive maintenance programs.  Many owners of
 small water systems do not have the resources that they need to perform this task.
 However, some assistance is available from federal, state and municipal agencies as well
 as service organizations. Many of these organizations and the assistance they can provide
 are discussed in this manual as  a practical source of information for the small public water
 system owner.
      Information and public involvement are very important to successful water system
 operation.   Technical and financial information from  governmental and  professional
 organizations can allow even the smallest water system to  enjoy many of the benefits of
 larger systems, without the high cost.  Starting  an information-sharing network with the
 active support of water system managers and users can help provide an efficient, cost
 effective  water supply system.

 SDWA REQUIREMENTS
     Passage of the federal Safe Drinking Water Act (SDWA) in 1974 allowed the federal
 government to establish national drinking water regulations, or rules, to protect  public
 health.
     Under  the SDWA, the federal government  develops  national  drinking  water
regulations to  protect public health and welfare. Individual states are expected to carry
 out and enforce these regulations for public water systems.  Public water systems must
provide water  treatment, as required, ensure drinking water quality through monitoring,
and provide public notice of violations or possible contamination.

-------
     Congress expanded and strengthened the SDWA in 1986.  The 1986 amendments
require EPA to regulate more contaminants, define maximum  contaminant levels, set
compliance deadlines, regulate surface water treatment, remove lead, require disinfection
and wellhead protection, and strengthen enforcement.

GENERAL  REQUIREMENTS
     Small public water system owners are responsible for the quality and availability of
drinking water from the raw water source to the consumer. The public must be able to
depend on the water system's management to provide a safe, reliable supply of drinking
water at a reasonable cost. This responsibility requires owners to successfully manage all
aspects of their water system and properly address the many problems faced by small
water systems.
     Another important requirement is training of water systems operators. Training may
include proper maintenance procedures, chemical treatment and safety procedures.  Such
training is usually provided by states, consultants, or other organizations.

INSTITUTIONAL CONCERNS
      Common problems faced by small water systems often involve difficulties obtaining
information, funding, training and community support for  operational needs and capital
improvements.
Information Sources
      State,  county or local health departments are the best contacts for information on
water quality, regulations, or  other specific concerns. Other sources  are also available,
such as the EPA Safe Drinking Water Hotline (1-800-426-4791) to answer questions about
requirements under  the SDWA.  National organizations  such as the American Water
Works Association,  National Rural Water  Association  and National Water Supply
Improvement Association can also provide technical assistance with specific problems, and
contacts with water equipment vendors.
      Pamphlets, journals, seminar notes and other written information on various topics
are available from the organizations listed above. Contacts within these organizations may
help solve particular problems. Information-sharing networks are an important part of
transferring technical knowledge within the water supply industry.  Small public water
system owners can benefit  from organizing  an active  information-sharing network.
Information sources are discussed in greater  detail in Part VI of this manual.
Financial Options
      Many small water systems often cannot afford the interest costs of standard loans,
or cannot afford other upgrades and changes that  some loan or grant programs require.
This is ^specially true for small water systems that have only a few customers. Loans and
grants intended especially for these systems are available from several sources including:
the  Farmers Home Administration;  U.S.  Department   of  Housing  and Urban
Development; U.S. Small Business Administration;  and  several other government and
private programs.  These are discussed further in Part VI of this manual.
 Public Relations/Community Support
      A public relations program conducted by a water system not  only  educates and
 involves the public, but encourages trust and support. People are interested in things that
 affect them, and clean drinking water plays an important role in providing a high quality

-------
 of life. A community needs to know about drinking water issues, and a water system
 owner may help increase the public's awareness and understanding.  This encourages a
 broad-based, informed and supportive group within the community that may assist in
 obtaining the improvements needed to provide a safe, reliable water supply.

 OPERATIONS
 Treatment
      Without treatment, water from natural sources may not be suitable for drinking.
 The type of water treatment needed depends on the chemical, physical  and biological
 makeup of the water.   When studying a potential  treatment system, operation and
 maintenance costs must be considered, as well as the capital (or initial equipment) cost.
-Operation and  maintenance costs may  vary greatly between different water systems
 providing the same-type of treatment. This may have an impact on the cost to the water
 user.
 Preventive Maintenance
      One of the most neglected aspects of water supply systems is proper maintenance.
 Crisis maintenance, or correcting system failures when they are discovered, is a common
 practice.  However, this creates higher costs in the long term and less protection for the
 drinking water supply.   Proper maintenance includes a good preventive maintenance
 program that can help prevent costly system failures.  This is always true, from the single
 home owner to the largest water supply system.
 Case Studies
      The  following  case studies are  provided to  show  how  communication and
 cooperation between owners of small public  water systems and regulatory agencies,
 professional organizations, and  water customers can solve some basic water concerns.
Case Study 1
Problem:
Discussion:
Solution:
The concentration of fluoride in a small public water'system exceeds the
maximum contaminant level of 4.0 mg/L.

The system owner contacts the state agency in charge of water quality
about possible treatment methods and cost of fluoride reduction. The
treatment  choices discussed include reverse osmosis,  electrodialysis
reversal and activated alumina. In addition, they looked for other water
supply sources with lower levels of fluoride.

During their research, the owner discovered that the county is planning
to extend its water distribution system  to within  1,200 feet of their
community. Comparing the cost of fluoride removal treatment to the
cost of  connecting  to the  neighboring  water system   shows that
connection to the county supply would be less costly.

The water  supply containing high levels of fluoride is abandoned, and
the users are connected to the new extension of the county supply.

-------
Case Study 2

Problem:


Discussion:
Solution:




Case Study 3

Problem:


Discussion:
               A water system that supplies a trailer park finds that its shallow well
               system usually delivers cloudy water after a heavy rainfall.
               The State Health Department studies the
               water supply is influenced by surface water.
               harmful microorganisms to the people who
               the water should be filtered. Homeowners,
               trailer park manager meet to  discuss  these
               treat the water.   A small package water
               filters is discussed as a low-cost answer.
problem and finds that the
Surface water may transmit
drink the water.  Therefore,
local health officers and the
findings and decide how to
treatment plant  using  sand
                Vendors  for supplying a small package plant are found and cost  is
                discussed. The package filtration plant is installed and regular visits by
                a contract operations and maintenance engineer are set up to keep the
                treatment system working properly.
                A small public water system regularly exceeds the standards for coliform
                bacteria in water.

                System owners have been unable to solve the problem, and agree that
                outside help is needed.  The water system manager asks the county
                health department and a local professional engineer for help. After a
                review of various alternatives to provide disinfection, several reliable and
                low-cost methods of simple chlorination are suggested.

Solution:        The system buys and installs a simple  solution-feed chlorinator.
 Case Study 4

 Problem:


 Discussion:


 Solution:
                Several households connected to a public water system have been tested
                and found to contain high lead levels at their tap.

                After a careful inspection, it is found that the source of lead is the lead
                solder used in their household plumbing.

                To increase awareness and understanding of  this problem,  the water
                system owner sends a notice providing information on lead in water and
                a copy of an EPA pamphlet to all of the customers.  Homeowners are
                also  advised that flushing their  water lines  every morning or  after
                extended periods of non-use will keep lead levels in the water as low as
                possible.

-------
The system owner explores several ways to reduce the water's tondoacy
to dissolve the lead in pipes and solder, including chemical corrosion
inhibitors.

A system is installed at the treatment plant to add a chemical that
controls the water's corrosivity and lessens leaching of lead from the
household plumbing.

-------

-------
                 Parti
                           Selection  and  Management
                           of  a  Water   Source
 INTRODUCTION
      Planning a water supply system requires that the quality of the water and available
 sources be evaluated. In addition, a basic knowledge of water rights and the hydrological,
 geological, chemical, biological, and possible radiological factors: affecting the water is
 helpful.  These factors are usually interrelated because water or water vapor continually
 circulates from the oceans to the air, over the surface of the land and underground, and
 back to the oceans.  This circulation is called the hydrologic cycle (see Figure 1).

 RIGHTS TO  THE  USE OF  WATER
      The rights of an individual to use water for household, irrigation, or other purposes
 varies in different states. Some water rights come from owning the land bordering on or
 overlying the source, while others are acquired by meeting certain legal requirements.
 There are three basic types of water rights.
      Riparian
      These are rights acquired with the title to the land bordering on or overlying the
 source of water. Whether or not a riparian right exists depends on the laws of each state.
      Appropriative
      These are rights  acquired for the use  of  water  by following  a specific legal
 procedure.
      Prescriptive
      These are rights acquired by diverting and putting to use, for a period specified by
 statute, water to which other parties may or may not have prior claims.  The procedure
 necessary to obtain prescriptive rights must conform with the water-rights laws of each
 individual state.
      A property owner should consult the appropriate state legal authority and clearly
 estabh'sh his rights to the use of water.

 SOURCES  OF WATER SUPPLY
      At  some  tune in  its history,  the oceans  contained all water.  By evaporation,
moisture is transferred from the ocean surface to the atmosphere, where winds carry the
moisture-laden  air over  land.   Under certain conditions, this water vapor condenses to
form  clouds, which release their moisture in the form of rain, hail, sleet, or snow.

-------
oo
           Lj\  PRECIPITATION
                                                FIGURE 1. - The hydrologic cycle.

-------
      When rain falls, part of it may evaporate and return immediately to the atmosphere.
Moisture in excess of the amount that wets a surface or evaporates is available as a
potential source of water supply.
Ground Water
      Some of the precipitation  may  seep into  the  soil (see Figure 1).  This  water
replenishes the soil moisture or is used by growing plants and returned to  the atmosphere
by transpiration (water vapor released to the air by plants).  Water that moves downward
(percolates) below the root zone reaches a level at which all of the openings or voids in
the ground are filled with water.  This zone is known as the "saturation zone."  Water in
the saturation zone is referred to as "ground water." The upper surface of the saturation
zone, if not restricted by an impermeable (watertight) layer, is called the "water table."
When the ground formation over the saturation zone keeps the ground water at a pressure
greater than atmospheric pressure, the ground water is under "artesian pressure."
      The name "artesian" comes from the ancient province of Artesium in France, where,
in the days of the Romans, water flowed to the surface of the ground from a well. Not
all water from artesian wells flows above the surface of the land. An artesian well is one
in which the water rises  above the  top of the aquifer.  An aquifer, or ground  water
reservoir, is an underground layer of permeable rock or soil that permits the passage of
water.
      The porous material just above the water table may contain "capillary" water in the
smaller void spaces.  This zone is referred to as  the "capillary fringe."  It is not a true
source of supply, however, since the water held  here will not drain freely.
      Because of the irregularities in  underground formations and  in surface topography
(hills and valleys), the water table occasionally  meets the surface of the ground.  As a
result, ground water moves to these locations and  seeps out of the  aquifer into a stream,
spring, lake or ocean. Ground water is continually  moving within the aquifer, even though
the movement may be very slow.  The direction of  the ground water flow,  especially when
affected by well pumping, does not necessarily follow the surface slopes. The water table,
or artesian pressure surface, slopes downward from areas of recharge (water inflow) to
lower areas of discharge (water outflow).  The differences in these slopes  causes the
ground water to flow within the aquifer. Seasonal  variations in the  supply of water to the
aquifer, such as snowmelt, can cause considerable changes hi the elevation and slope of
the water table and the artesian pressure level.
Wells
     A well that penetrates the water table can be used to extract water from an aquifer.
As water is pumped from the well, the water table near the well is lowered. If pumping
continues at a faster rate than the recharge of the water table, the "sustained yield" of the
well is exceeded. If the sustained yield is exceeded for a long period of time, the aquifer
may become depleted or other undesired results may occur. In that case, the "safe yield"
of the aquifer has been exceeded.  For example, salt-water may enter the aquifer where
wells are near the  seashore or other saline waters.
Springs
     An opening in the ground from which ground water flows is  a spring. Water may
flow by force of gravity (from water-table aquifers), or be forced out by artesian pressure.
The flow from a spring may vary considerably with changes hi the water-table or artesian
pressure. For further discussion, see Part II.

-------
Surface Water
     Surface  water collects mainly  as a result  of direct runoff from precipitation.
Precipitation that does not seep into the ground or evaporate, flows over the ground
surface and is called direct runoff.  Direct runoff flows over surfaces such as stream
channels and other natural or artificial runoff channels.
     In some areas, a source of water is the rainfall collected on the roof surfaces of
homes, barns, and other buildings. Water from those surfaces can be collected and stored
in tanks called cisterns. In some instances, natural ground surfaces can be conditioned to
make them impermeable.  This conditioning will increase runoff to cisterns or large
artificial storage reservoirs, thereby reducing loss by seepage into the ground.
     Runoff from the ground may be collected in either natural or artificial reservoirs.
A portion of the water stored in surface reservoirs evaporates  and seeps into the ground
water table through the pond bottom.  Transpiration from vegetation in and adjacent to
ponds  constitutes another means of water loss.
Ground and Surface Water
     Ground water may become surface water  at springs or at intersections of a water
body and a water table.  During extended dry  periods, stream flows consist largely of
water from the ground water reservoir.  As the ground water reservoir is drained by the
stream, the flow will  reach  a minimum or  may  cease altogether.   It is  important in
evaluating stream and spring supph'es to consider seasonal changes in flow that may occur
due to snow or dry periods.
Snow
     Much of the snow  falling  on a watershed  remains on the ground surface until
temperatures rise above freezing and it melts. In  the mountainous areas of the western
United States, snow storage is an important source of water supply through much of the
irrigation season. Water supply systems in these areas are usually helped by actions which
increase the snowpack and reduce melting.
Alternate Sources
     Another possible source of water supply  is an  existing water  system which may
service a nearby community.  This may be an attractive, low-cost solution, especially
considering the costs of developing and operating  a new water supply.

QUALITY OF  WATER
     Precipitation in the  form of rain,  snow, hail, or sleet contains very few impurities.
It may contain tiny amounts of minerals, gases, and other substances as it forms and falls
through the earth's atmosphere.  However, it has virtually no bacterial content.
     Once precipitation reaches the earth's surface, however, there are many chances for
mineral  and  organic  substances, micro-organisms, and  other  forms  of pollution
(contamination)1 to enter the water.   When water runs over or through the ground
surface, it may pick up particles of soil.  This is noticeable in the water as cloudiness, or
"turbidity".  It also picks up particles of organic matter and bacteria.  As surface water
      Pollution as used in this manual means the presence in water of any foreign substances (organic,
      inorganic, radiological, or biological) which tend to lower its quality to a point that it constitutes a health
      hazard or impairs the usefulness of the water. Contamination, where used in this manual, has essentially
      the same meaning.
10

-------
 seeps through the ground to the water table, most of the suspended particles (even, some
 bacteria) are filtered out.  However, the water may pick up additional contaminants or
 particles when it comes in contact with underground mineral deposits.
      The widespread  use of man-made  chemicals, including pesticides, herbicides,
 insecticides,  and industrial and medical chemicals, has caused a renewed interest in the
 quality of water.  Many of these materials are known to be toxic and/or  carcinogenic
 (cancer-causing) to humans and may have other  undesirable characteristics.  Water
 pollution has also been traced to sewage or waste water sources containing synthetic (man-
 made) detergents.  Chemical and bacteriological analyses to determine water quality may
 be performed by a state or local health department  or by a commercial laboratory.
      Characteristics that describe water as it moves over or below the ground may be
 classified under  four major headings:   physical,  chemical, biological and  radiological.
 Analytical methods for these  parameters  are discussed  below and can be  found in
 Standard Methods for the Examination of Water and  Wastewater2.
 Physical Characteristics
     Physical characteristics relate to the appearance of water, its color or turbidity, taste
 and odor, temperature and foamability. The water, as used, should look, taste and smell
 clean.
     Color.  Dissolved organic material from decaying vegetation and certain inorganic
 matter  causes water to appear colored.  Occasionally, algae blooms or  the growth of
 aquatic micro-organisms may also give color.  Iron  and manganese can cause a red or
 black color in water and may stain bathroom fixtures. While color itself does not usually
 mean that the water is not safe,  its  presence is unpleasant and suggests that the water
 needs treatment. Typically, treated water will have a  measurement of less than five "color
 units."  Color may also indicate mine  drainage or the presence of decaying organic matter,
 which may form harmful trihalomethanes during disinfection with chlorine.
     Foamability. Foam in water is usually caused by concentrations of detergents greater
 than 1 mg/L. The user should understand that  if enough detergent is in  the water supply
 to cause a noticeable froth to appear on a glass of water, hazardous materials from sewage
 or other pollution may also be present.  Foaming is also undesirable in drinking water
because it looks unclean.
     Taste and Odor.  Taste and odor in water can be caused by foreign matter such as
 organic compounds, inorganic salts, or other dissolved minerals or gases.  These materials
may come from household, industrial, agricultural, or natural sources.  Drinking water
should not have any unpleasant taste or odor.
     Tastes and  odors in water are usually tested for both strength and type. A sample
is collected in glass containers and tested as soon as possible. The test can be delayed for
a few hours if refrigeration is available.
     A simple test consisting of taking a sample and observing it for clarity and smelling
it for possible odors can be an early sign of pollution.  If there  is a detectible smell or
taste, the "threshold odor test" can then be performed at a laboratory to determine the
     American Public Health Association, American Water Works Association, and Water Pollution Control
     Federation, Standard Methods for the Examination of Water and Waste Water, 17th edition, Amer. Pub.
     Hlth. Assn., Washington, D.C. (1989)
                                                                                11

-------
severity of the problem. If pollution is suspected, other tests should be done and advice
from local county and state agencies obtained.
     Temperature.  The most desirable drinking waters are consistently cool and do not
have temperature changes of more than a few degrees.  Ground water and surface water
from mountainous areas generally meet this standard.  Most individuals find that water
having a temperature between 50°F (10°C) and 60°F (16°C) is most palatable.  Tempera-
ture may also increase sensory response to tastes  and odors.
     Turbidity.  The presence of suspended material such as clay, silt, finely divided
organic material, plankton, and other inorganic material in water is known as turbidity.
Turbidity in excess of five units can be  easily seen  in a glass of water, and is usually
undesirable because it causes the water  to look unclean. Treated water normally has
turbidity levels of less than 0.5 NTU3.
     Clay or other inert suspended particles in drinking water may not adversely affect
health, but water containing such particles may require treatment to make it suitable for
use and to increase disinfection effectiveness.  Turbidity's major danger in drinking water
is that it can harbor bacteria, require the use of more chlorine during disinfection, or react
with chlorine to form harmful by-products. Surface water supplies are generally more
turbid than ground water, which is normally less than 1 NTU.  Variations hi the ground
water turbidity following a rainfall may be considered a sign of surface water infiltration
or other pollution since ground water turbidity does not usually change.
Chemical Characteristics
     The materials that form the earth's crust affect not only the quantity of water  that
may be taken from a well, but also its chemical characteristics. As surface water seeps
downward to the water table, it dissolves portions of the minerals contained in soils and
rocks.  Ground water, therefore, usually contains more dissolved minerals than surface
water.
     The chemical characteristics of water in a particular  place  can sometimes be
predicted from analyses of nearby water sources, unless  a local  source of pollution is
present. Chemical and other water quality data are often available hi published reports
of the  U.S. Geological Survey or from Federal, State,  and local health, geological,  and
water agencies.  If information is not available, a chemical analysis of the water source
should be made. Some state health and geological departments, as well as state colleges,
and many commercial laboratories may provide this service. Portable water test kits are
also available. Knowing about the chemical quality of a water supply source is important
in order to determine what treatment, if  any, is required.
     Some substances, when present in water,  may corrode, or wear away parts  of the
water system or stain fixtures and clothing. Chemical analysis can detect those substances.
Proper sample size and the sample collection methods are important; the testing facilities
instructions should be followed.
     The following is a discussion of some of the chemical characteristics of water.
     Alkalinity.  Alkalinity results from bicarbonate, carbonate, or hydroxide compounds
in the  water.  The presence of  alkalinity is determined by standard methods involving
titration with various indicator solutions.  Knowledge of the compounds causing alkalinity
      NTU - Nephelometric Turbidity Unit, a standard unit of measurement for turbidity

12

-------
is useful in selecting chemical clarification, softening, and corrosion control procedures for
water supplies.
     Aluminum. Aluminum may, even at low levels (0.05 mg/L), cause precipitation and
increased turbidity in water as it passes through a distribution system.  The World Health
Organization recommends that levels of aluminum in water not exceed 0.2 mg/L because
of the increased potential for water discoloration. EPA has recommended that States set
aesthetic standards of 0.05 to 0.2 mg/L to prevent aluminum precipitation or discoloration
of drinking water.  The level chosen by a  State is determined by water quality and
treatment considerations.
     Chloride.  Most waters contain some  chloride in  solution.  Sources include the
leaching of marine sediments, intrusion of sea water, and  industrial and domestic wastes.
Chloride concentrations in excess of 250 mg/L usually  produce a noticeable taste in
drinking water. In areas where the chloride content is higher than 250 mg/L and all other
criteria are met, however, it may be necessary to use a water source that exceeds this limit.
     A sudden increase in the chloride content of a water may indicate pollution from
sewage sources, particularly if the normal chloride content is known to be low.
     Copper.  Copper is found in some natural waters, particularly in areas where copper
ore deposits have been mined.
     Corrosive water passing through copper pipes may also pick up excessive amounts
of copper.  Copper in small  amounts is not  considered unhealthy, but produces an
unpleasant taste.  A larger toxic dose of copper causes nausea, and prolonged ingestion
may result in liver damage.  For  this reason, the recommended limit for copper is 1.0
mg/L.
     Hardness.  Hard water and soft water are relative terms. Hard water retards the
cleaning action of soaps and detergents, causing additional expense in the form of extra
work and cleaning agents. Furthermore, when hard water is heated it will deposit a hard
scale (as in a kettle, heating coils, or cooking utensils) which damages hot water pipes and
requires additional heating fuel or energy expenditures.
     Calcium and magnesium salts, which are the major cause of  hardness in water
supplies, are divided into two general classifications: carbonate, or temporary hardness,
and noncarbonate, or permanent hardness.
     Carbonate, or temporary hardness is so called because  heating the water results in
its removal.  When water is heated, bicarbonates break down into solid particles that stick
to a heated surface and the inside of pipes.
     Noncarbonated, or permanent, hardness is so called because it is not removed when
water is heated. Noncarbonated hardness is due largely  to the presence of the sulfates
and  chlorides of calcium and magnesium in  the water.  Water  with total hardness
concentrations from 0 to 75 mg/L is considered soft, 75 to  150 mg/L is considered
moderately hard,  150 to 300 mg/L is considered hard, and over 300 mg/L is considered
very hard.
     Fluorides.  In some areas, water sources contain natural  fluorides.  Where the
concentrations approach optimum levels  (0.7 to  1.2 mg/L)  health benefits have  been
                                                                              13

-------
observed. In such areas, the incidence of dental cavities has been found to be below the
rate in areas without natural fluorides."
 Excessive fluoride (greater than 4 mg/L) in drinking water supplies may cause fluorosis
(mottling) or discoloration of teeth, which increases as the fluoride level rises.  When
fluoride concentrations exceed 4.0 mg/L,  the risk of skeletal fluorosis or other adverse
health effects is increased.
     Iron.  Small amounts of iron are often found in water because of the large amount
of iron present in the soil,  and because corrosive water will pick up iron from pipes.
Clothing washed in water containing excessive iron may become stained a brownish color.
Iron also affects the taste of beverages such as tea and coffee. The recommended  limit
for iron is 0.3 mg/L.
     Lead. Lead accumulations in the body and prolonged exposures to even very small
amounts, particularly among young children and pregnant women, can result in serious
health effects. The effects include delays in normal physical and mental development and
impairment in learning and behavior. In 1991, EPA issued a regulation for public water
supplies  which includes an "action level" of  0.015  mg/L for lead in drinking water
measured at household water  taps. A public supply would have  to take several steps to
minimize lead in drinking water if 10 percent or more of the homes served by the supply
exceed the lead "action level".
     Excessive lead is occasionally found in source water, but the usual cause of excessive
lead in tap water is lead in household plumbing. Solder and fixtures containing lead can
leach lead into  drinking water. In 1986, the U.S. Congress banned the use of lead solder
containing greater than 0.2 percent lead and restricted the lead content of faucets, pipes
and other plumbing materials  to 8.0 percent. Nevertheless, materials containing lead are
present in water distribution systems and in millions  of homes.
     Manganese. Manganese produces a-brownish color in laundered clothing, produces
black particles  on fixtures, and affects the taste of beverages, including coffee and tea.
The recommended limit for manganese is 0.05 mg/L.
     Nitrates.  Nitrate can cause the blood disorder methemoglobinemia (infant cyanosis
or "blue baby disease") in infants who have been given water or fed formulas prepared
with water having high nitrates.  A household water supply should  not contain nitrate
concentrations  in excess of 45 mg/L (10  mg/L expressed as nitrogen).  Excess nitrate
levels in water  may be caused by contamination from livestock manure  or from nitrogen
fertilizer applied to farmland.  Wells may also be contaminated by lawn fertilizers used by
homeowners.
      In some polluted wells, nitrite is also present in water and is even more hazardous,
especially to infants.  When a high nitrite concentration (i.e., at  levels greater than 1
mg/L) is found, the water must not be used for feeding infants. The nitrite concentration
should be determined, and if too high, advice obtained from health authorities about the
safety of the water for drinking.
      The addition of about 1 mg/L of fluoride to water supplies has been found to help prevent tooth decay
      in children.  Some natural water supplies already contain amounts of fluoride that exceed the
      recommended optimum concentrations.
 14

-------
     Pesticides.  Careless use or improper storage of pesticides can contaminate water
sources and make the water unsafe for drinking. Numerous cases have been reported of
well contamination resulting from termite-control treatment. Pesticides must not be used
near wells.
      Other synthetic (man-made) organic chemicals, some of which are used by industries
for many purposes, are also of concern in the protection of drinking water. These organic
chemicals can be hazardous to human health or cause taste and odor problems in drinking
water.
     pH.  pH is a measure of the hydrogen ion concentration in water.  It is also a
measure of the acid or alkaline content.  The pH scale ranges from 0 to 14.  Seven
represents neutrality, while values less than 7 indicate increasing acidity and values greater
than 7 indicate increasing alkalinity.  The pH of water in its natural state is generally in
the range of pH 5.5 to 9.0. Determination of the pH  value assists in the control of
corrosion,  the determination of proper chemical dosages,  and adequate control of
disinfection.
     Silver. Silver in water at levels in excess of 0.1 mg/L can cause a permanent gray
discoloration of the skin, eyes, and mucous membranes known as argyria or argyrosis.
     Sodium.  When it is necessary to know the precise amount of sodium present hi a
water supply, a laboratory analysis should be made.  Ion-exchange water softeners will
increase the amount of sodium in drinking water.  For this reason, water that has been
softened should be analyzed for sodium whenever a person needs to keep a precise record
of thek  sodium intake.  For a healthy person, the sodium content of water is not a
concern because the intake from table salt in the ordinary diet is so much greater, but for
those on a low-sodium diet, sodium in water must be considered. The usual low-sodium
diets allow for 20 mg/L sodium hi the drinking water.  When this limit is exceeded, a
physician's advice should be sought.
     Sulfates. Waters  containing high concentrations of sulfate (greater than 250 mg/L)
caused by the leaching  of natural deposits of magnesium sulfate (Epsom salts) or sodium
sulfate (Glauber's salt) may be undesirable because of their laxative effects.
     Total Dissolved Solids  (TDS). TDS refers to the presence of ions such as sodium,
chloride, sulfate, and calcium in water. Some of these dissolved solids may cause taste and
odor problems, deteriorate  plumbing  and appliances, or cause mineral precipitation.
Because water with high TDS  levels tastes bad, a maximum level of 500  mg/L is
recommended in drinking water supplies.
     Zinc.  Zinc is found in some natural waters, particularly in areas  where zinc ore
deposits have been mined. Zinc is not considered detrimental to health, but it will impart
an unpleasant taste to drinking water.  For this reason, the recommended limit for zinc
is 5.0 mg/L.
     Serious surface and ground water pollution problems have developed from existing
and abandoned mining operations.  Among the worst are those associated with coal mine
operations, where heavy concentrations of iron, manganese,  sulfates, and acids have
resulted from the weathering and leaching of minerals.  •
Biological Characteristics
     The presence of biological organisms hi water are very important to public health
considerations and can significantly change the  physical and chemical characteristics of
                                                                               15

-------
water.  Water for drinking and  cooking must be made free from disease-producing
organisms.
      Total Coliform as  Pollution Indicator.   Organisms which  are known to cause
waterborne disease include bacteria, protozoa and viruses.  Some algae and helminths
(worms) may also be capable of producing disease. Symptoms of waterborne disease may
include diarrhea, cramps, nausea and possibly jaundice.
      Unfortunately, specific disease-producing organisms present hi water are not easily
identified. It would be very difficult, expensive and time-consuming to monitor for each
of these organisms. For this reason, it is necessary to select an easily measured "indicator
organism," whose presence indicates that disease-producing organisms may be present.
A group of closely related bacteria, the total coliform, have been selected as an indicator
of harmful organisms in drinking water.
      Total conforms are common in the water environment.  One of them, Escherichia
coli (E. colt) often referred to as fecal coliform) only grows in the intestine of warm
blooded animals. Total  coliform bacteria are generally not harmful.  Water treatment
should  remove any total conforms  from water entering the distribution system.  The
presence of these bacteria hi drinking water generally is a result of a problem with water
treatment or the pipes which distribute the water,  and indicates that the water  may be
contaminated with harmful organisms.  Total conforms are not only a useful indicator of
potential sewage contamination, but are also a useful screen for the actual presence of E.
coli.  The presence of E. coli is strong evidence that fresh sewage is present.
      Total conform are not a perfect indicator of the  actual or potential presence of
harmful organisms, because some disease-producing organisms, especially protozoa such
as Giardia and cryptosporidium,  are able to withstand treatment which remove total
conforms. These two protoza are often found in surface waters which are contaminated
by human sewage or wildlife, which are principle carriers of these organisms.
      Other Biological Factors. Certain forms of aquatic plants and microscopic animal life
in natural water may be  either stimulated  or  retarded in then: growth by physical,
chemical, or biological factors. For example, the growth of algae, minute green plants
usually found floating in surface water,  is stimulated by light,  heat, nutrients  such as
nitrogen and phosphorus, and the presence of carbon dioxide as a product of organic
decomposition. Their growth may, in turn, be retarded by changes  in pH (measure of
acidity), the presence of inorganic impurities,  excessive cloudiness or darkness, low
temperature, and the presence of certain bacteria.
      Continuous cycles  of growth and decay  of algae in  water  may result hi the
production of undesirable by-products that may adversely affect water quality. The same
is true of certain non-harmful bacteria or other microorganisms that live in natural waters.
      A water source should be as free of biological activity as possible.  Select water
sources that do not normally support much plant or animal life, and protect these sources
from contamination by biological and fertilizing agents.  Stored water should not be
exposed to excessive light  or temperature. Disinfection may be  necessary to properly
control biological activity.
Radiological Characteristics
      Radiological factors must be considered in areas where there is a possibility that the
water may have come hi contact with radioactive substances.
 16

-------
      Radioactive material is found in nature, and as a result of the development and use
 of atomic energy as a power source, and the mining of radioactive and other materials.
 It has become necessary to set upper limits for the intake of radioactive substances into
 the body, including intake from drinking water.
      The effects of human exposure to radiation or radioactive materials are harmful and
 any unnecessary exposure should be avoided. The levels of radioactive materials specified
 in the current drinking water regulations (see Table 1) are intended to limit the human
 intake of these substances so that the radiation exposure of any individual will not exceed
 the amount defined by current radiation protection guidelines. People have always been
 exposed to natural radiation from water, food, and air. The total amount of radiation to
 which a person is exposed varies with the amount of this background,  or  natural,
 radioactivity as well as other factors, including exposure to man-made sources of radiation.
      Natural Radiation.  Natural radiation occurs primarily in ground water and includes
 radon, radium, and uranium. Radon is the most common radiological threat. The health
 risk  from these  contaminants  comes mainly from the deposit of radium and uranium
 within the bones and, inhalation of air which has  been contaminated by water or soil gas
 containing radon. Radon is known to cause lung cancer. Samples of source water should
 be sent to a qualified laboratory for analysis if natural radioactivity is suspected.
      Man-Made Radiation.  The health risks associated with man-made radiation are
 similar to the health risks associated with natural sources of radiation. Of the radioactive
 substances  that increase  the risk of cancer,  tritium, strontium, cesium and others have
 been found in drinking waters  sources.
      Radiological data indicating radioactive substances in an area's drinking water may
 be available in publications of the U.S. Environmental Protection Agency, U.S. Public
 Health Service, U.S. Geological Survey, or from Federal, State, or local agencies.  For
 information or recommendations on specific problems, the appropriate agency should be
 contacted.

 SAFE DRINKING WATER  ACT (SDWA)
 Background
      As mentioned in the Introduction, in 1974 the SDWA gave the federal government
 the responsibility to establish national drinking water regulations to protect public health.
 This act  was further strengthened and expanded in 1986 by Congress, requiring EPA to
 regulate  additional  contaminants,   define  maximum   contaminant  levels, establish
 compliance deadlines and filtration guidelines, require disinfection and wellhead protection
 and strengthen enforcement.
      Chemical, physical, radiological and bacteriological substances in drinking water
 which pose  a health risk to the public are regulated by the Environmental Protection
Agency under the  SDWA. EPA  establishes maximum contaminant levels (MCLs) for
 drinking  water contaminants.  If analysis of a water supply shows that any of the MCLs
listed in Table 1 are exceeded, the water should not be used without treatment to remove
 the contaminant(s).
      Not all substances are regulated because of their health risks.  Secondary maximum
 contaminant levels (SMCLs) are established by EPA to assure an aesthetically acceptable
water supply (see Table  2).  Exceeding SMCLs  may create  taste, odor or appearance
problems, and cause people to question the  safety of their drinking water even though
                                                                              17

-------
there is no direct health risk. As a result, people might use a water supply that looks,
smells or tastes better, but poses a health risk.

                 TABLE 1. -Maximum Contaminant Levels (MCLs)1

                              Inorganic Contaminants
PARAMETER
Arsenic
Asbestos (fibers/L)
Barium
Cadmium
Chtonuwtt
Copper
Fluoride
MCL
0,05
7 million
I
0.005
0,1
1.32
4.0
PARAMETER
HuoridS
Lead
Merciny
Nitrate (as N)
Ntttste t Nitrite (as N)
Selenium
V, H ^ -,, ,
MCL
4,0
0.0152
0.002
10
1
0.01

                                Organic Contaminants
PARAMETER
AJachlor
Atrazine
Benzene
Carbofuran
Carfpon Tetrachlorjde
Chlordane
2,44>fcnloro£henoxyacetie
Dibromochlorqpropane
o-Dichtorobenzene
para-Dichlorobenzene
l,2-t>ichloioethane
1,1-Dichloroethylene
cis4,2-Pichtoroethylene
trans-l,2-Dichloroethylene
1,2-DIcRIoropropane
Endrin
Eihylbenzene
MCL
0.002
0.003
0,005
0.04
0.005
0.002
0,07
0.0002
0.6
0.075
0,005
0.007
0.07"
0.1
0,005
0.0002
0.7
PARAMETER
Bthylene dibromide
Heptachlor
Heptachlor epOxi.dc
Lindane
Methoxychtor
Monochlorobenzene
PoIyeWorinated biphenyts
Styrene
Tetrachloroefhyleite
Toluene
Toxaphenft
Total Trihalomethanes
2,4J5*TP (Silvex)
Trichloroethane ^
14,1-TdehlQrOetnane
Vinyl Chloride
Xvtenes
MCL
0.00005
0.0004
0,0002 ,
0.0002
0.04
0.1
0,0005
0.1
0.005
1
0,003
0.10
0.05
0.005
0,20
0.002
10
                             Radiological Contaminants
PARAMETER
Total radium (:radhun-22jj * iadwm-228) (pCi/L)
Gross alpha activity (pCi/L)
Beta1 parties! and photon activity fmillii'em/yeat>
MCL
5
15
4
           Units in mg/L unless otherwise noted.
           USEPA has set "action levels" for copper and lead in public drinking water.
      Appendix A is a list of drinking water contaminants with associated health effects,
 sources of contamination, and best treatment methods also presented.
 18

-------
           TABLE 2. - Secondary Maximum Contaminant Levels (SMCLs)1
PARAMETER
Alunttttunj
Chloride
Color (PtCo units)
Copper
Coffosivity
Fluoride
Teaming Agents
Iron
SMCL
0,05 to 0,2
250
15
1.0
Nbn-eortosjve
2.0
0.5
0.3
PARAMETER
Majjgangse :
Odor (TON)
pH
Silver
Sulfete
Total dissolved solids
Zinc

•MCL
0,05
3
6,5 to 83
0.1
350
500
5.0

           Units in mg/L unless otherwise noted.

Maximum Contaminant Levels
      The Safe Drinking Water Act requires EPA to set numerical standards, referred to
as Maximum  Contaminant Levels (MCLs), or define treatment  requirements  for  83
contaminants that pose potential health risks in drinking water.  The 1986 amendments
established a strict schedule for EPA to  set MCLs or treatment requirements for many
additional  contaminants.  Every three years, an additional 25 contaminants  must be
regulated.  In addition  to the MCLs and treatment  techniques,  secondary maximum
contaminant levels (SMCLs) which effect the aesthetic quality of drinking water (but do
not represent significant health hazards)  have also been developed by EPA.
Monitoring
      The  EPA  issues  regulations  that  require  regulated   and some  unregulated
contaminants to be monitored. The unregulated contaminants that must be monitored
depends on the number of people served, the water supply source, and contaminants likely
to be found. Proper monitoring of biological, physical and chemical substances in water
is necessary to insure a consistent, high quality supply of drinking water.
Filtration
      Under the Safe Drinking Water Act, the EPA has set requirements for filtering
surface water  or  water  from sources that are exposed  to surface water.  It  has  also
developed procedures for states to use in determining which systems have to filter then-
water.
Disinfection
      The EPA must develop rules that require all public water  supplies to disinfect then-
water. EPA rules will apply to water systems which use surface water sources and those
which use groundwater.
Lead Levels
      Solder or flux containing more than 0.2 percent lead, or pipes and pipe fittings
containing more than 8 percent lead, cannot be used in new public water supply systems.
Each public water system  must identify 'and provide notice to  persons whose  drinking
water may be contaminated due to lead in construction materials of the public water
supply system, or where the corrosivity of the water may cause leaching of lead (from
household plumbing or the distribution system) into the drinking water.
                                                                              19

-------
Wellhead Protection
     The 1986 Safe Drinking Water Act amendments require all states to  develop
protection programs for the areas surrounding wells.  These programs are designed to
protect public water supplies from contamination.
Total Coliform Rule
     EPA issued new regulations regarding total coliform occurrence in June 1988 that
became effective December 31, 1990. The regulations establish limits and monitoring
guidelines for total conforms in public water systems to reduce the risk of water-borne
disease caused by microorganisms.  In addition, systems may be allowed to test for the
bacterium Escherichia coli (E.coli)  instead of fecal conforms, and must follow special
procedures to reduce the interference of heterotrophic bacteria (bacteria which get then-
energy from organic material) with the total conform analysis. To comply with the new
regulations, no more than 5.0 percent of the samples collected during a month can contain
total conforms. There is an exception for systems that collect fewer than 40 samples per
month: they may have one total coliform-positive sample per month.
     How often monitoring must take place is based on the number of people the system
serves. The larger the system, the more samples must be collected. If a system collects
fewer than five samples per month, it must also have a sanitary survey (described in this
section) every five years  (or every ten years for non-community water systems  that use
only protected and disinfected ground water).   The reason for. the  sanitary survey
requirement is that total coliforms are not found evenly distributed hi the system.  EPA
does not believe that a system owner will be able to ensure that its water is safe based on
fewer than five samples per month.
     Under the coliform rule, if a sample is total coliform-positive, the system owner must
collect three to four more samples to determine the extent of the contamination.  Systems
that collect fewer than five samples per month must (with some exceptions) collect at least
five samples during the next month it serves the water to the public.  This way, the system
owner will collect at least ten samples over a two-month period, a number that EPA
believes is necessary to find out whether the system is contaminated.
     A state, however, cannot disregard a total coliform-positive sample just because all
repeat samples are total coliform-negative.  Again, this is because coliforms are distributed
unevenly in the distribution pipes. These negative results do not prove that the system is
free of contamination.
      The total coliform rule also requires public water systems to test  total coliform-
positive samples for either fecal coliforms or E. coli to find out if the water is contaminat-
ed with fresh sewage. The presence of conforms may mean recent sewage contamination,
and the presence of a serious health concern. (Fecal conforms are a category of total
coHforms which includes E. coli and strains of several other bacteria.)  If a sample
contains fecal conforms or E. coli, the system may be in violation of the total  conform
rule. Variances to the total conform rule may be available where positive conform results
can be shown to be caused by non-fecal microorganisms.
Surface Water Treatment Requirements
      EPA Surface Water Treatment Rule (SWTR) requires all public water systems that
use any surface water, or ground water under the direct influence of surface water (as
determined by the  State), to disinfect drinking water.  All such systems must also filter
then- water, unless the State decides that filtration is not needed. More information about
 20

-------
 the total coliform rule and surface water treatment requirements for public water supplies
 can. be found by asking the State or local agency responsible for water supply.
 Control of Lead
      EPA regulations include an "action level" for lead in household water, at 0.015 mg/L.
 Water systems that have lead levels above this action level in 10 percent or more of
 monitored homes would have to take several steps to minimise, the exposure of people to
 lead in drinking water.  These steps may include: installation or improvement of corrosion
 control; monitoring and possible treatment of source water supplies; delivery of a public
 education program to tell consumers ways that they can avoid high lead levels; and, in
 cases where corrosion control  is  not sufficient,  gradual replacement of lead service
 connections that contribute more  than 0.015 mg/L of lead to drinking water. Water
 systems are encouraged to help insure that plumbers in their locality comply with the 1986
 Congressional ban on the use  of  solder containing greater than 0.2 percent lead and
 restrictions that limit to 8.0 percent the lead content of faucets, pipes and other plumbing
 materials.                                     '                     ;   •            '

 WATER TESTING AND LABS
      Many tests and  analyses  can be made  on water to determine  quality, so it is
 important to carefully select those most needed.  County and state health departments
 may help in selecting tests and locating testing laboratories. Water treatment equipment
 dealers may also help determine appropriate tests, and may perform some analysis. Some
 states certify laboratories that are qualified to test water, while some states provide water
 testing services themselves.
      Test kits are also available  for analysis at the water source or supply (field analysis)
 of many chemical and bacteriological characteristics. Field test kits are available (from
 several suppliers) for alkalinity, bacteria (iron and sulfur bacteria, slime organisms and
 coliform), fluoride, hardness, iron, lead, manganese, chlorine, nitrate, pH, and zinc. Test
 kits are a useful indicator, but can not always be relied on to prove the presence or
 absence of a contaminant. If a drinking water contaminant is identified during a field test,
 it may be desired that a more detailed analysis be performed by a qualified laboratory.
      Collection  of Samples.  Water samples must be collected carefully to prevent
 accidental contamination by the collector.  Samples collected to satisfy drinking water
 regulations must be analyzed in a laboratory certified by the State  or EPA.  More
 information about sample collection and analysis for microorganisms in water is found in
Appendix B.

 CONTAMINANT  SOURCES
     There are many ways a water source could become contaminated. An accurate
identification of the source of contamination is vital to determining the safety of a drinking
water.  If  the  source  of contamination  can be  located, it may then be  eliminated.
Unfortunately, if the contamination cannot be eliminated, the water supply may still have
to be used  (with appropriate treatment) if no other water source is available.
Physical
     Physical contamination can result from  surface runoff during periods of heavy
rainfall, urban runoff of oils, dirts and highway salts from roadways and parking lots, or
from the growth of taste- and odor-causing algae in stored water.
                                                                              21

-------
Chemical
     Chemical contamination may result from mine drainage, landfill leachate (leakage),
storage tank leaks, accidental spills of chemicals in transport, agricultural fertilizer runoff,
or salt water intrusion.  Excessive hardness may also be present from the slow trickle
(percolation) of water through natural mineral deposits.
Biological
     Biological  contamination  comes from municipal,  agricultural, industrial  and
individual wastewater systems. Treatment plant discharges, septic tank leaks, cess pools,
and applying undisinfected wastewater sludge to farmland all contribute bacteria and
viruses to source water.  Other biological contamination can come from landfill leachate,
deer and other wildlife in the watershed, and farm animal feedlots and manure lagoons.
Radiological
     Radiological contamination comes from natural geologic formations and soils, and
by leaks from radioactive storage sites, industrial sites, medical wastes and nuclear test
sites.  Natural radiation may also leak into drinking water  sources from active or
abandoned uranium mines.
     Appendix C contains a useful key to identify many of the contaminants  in water
discussed above by using the senses of feeling, smell, taste, sight and hearing.

QUANTITY  OF WATER
     With quality water supplies becoming  more difficult to find and water demands
increasing,  this limited resource must be conserved.  In order to select a suitable water
supply source, the demand that will be placed on it must be known.  The elements of
water demand include the average daily water use and the peak rate of demand. In the
process, the ability of the  water source to meet demands  during critical periods (when
surface flows and ground water tables are low) must be determined.  Stored water, that
would meet demand during these critical periods; must also be taken into consideration.
     The "peak demand" rates must be estimated in order to determine plumbing and
pipe sizing, pressure losses, and storage requirements necessary to supply enough water
during periods of peak water demand.
     State or local agency requirements may  dictate water supply (and component)
capacities.  Where such agency requirements do not  exist, the following discussion of
average and peak demands can be used to project water needs.
Average Daily Water Use
     Many factors influence water use. For example, the fact that water under pressure
is available encourages people to water lawns and gardens, wash automobiles, and perform
many other activities at home and on the farm.   Modern household appliances such as
food waste disposers and automatic dishwashers contribute to a higher total water use and
tend to increase peak demands.  Since water requirements will influence all features of a
water supply under development or improvement, they are very important in planning.
Table 3 presents a summary of average water use as a guide in preparing estimates. Local
adaptations must be made where necessary,  such as  in cases where limitations in water
supply require active water conservation measures.
22

-------
                         TABLE 3. - Planning guide for water use.
           Types of Establishments
                                                                               Gallons per day
  Airports (per passenger):
  Apartments, multiple family (per resident)
  Bath houses (per bather)
  Camps:  Construction, semipermanant (per worker)
           Day with no meals served (per camper)
           Luxury (per camper)
           Resorts, day and night, with limited plumbmglper camper)
           Tourist with central bath and toilet facilities (per person)
  Cottages with seasonal occupancy (per resident)
  Courts, tourist with individual bath units (per person)
  Clubs:  " Country (per resident member}
           Country (per non-resident member)
  Dwellings:  Boardinghouse (per boarder)
           Luxury (per person)
           Multiple-family apartments (per resident)
           Rooming houses  (per resident)
          Single family (pet resident)
  Estates (per resident)
  Factories (gallons per shift)
  Highway rest area (per person)
  flat els wife private baths (2 persons per room)
  Hotels without private baths (per person)
  Institutions Bther than hospitals (per person)
          Hospitals (per bed)
  Laundries, self-serviced (gallons per washing, Le,?per customer)
  Livestock (per animal):
          Cattle^ horse, mute, steer (drinking)
          Dairy (drinking and servicing)
          Goat, sheep (drinMng)
          Hog (drinking)
  Motels with bath, toilet, and! kitchen facilities (per bed; space)
          With bed and toilet (per bed space)
  Parks;   Overnight with flush toilets (per camper)
          Trailers with individual bath units, no sewer connections (per trailer)
          Trailers with individual baths, connected to sewer (per person)
  Picnic:  With bathhouses, showers, and flush toilets (per picnicker)
          With toilet facilities only (gallons per picnicker)
  Poultry: Chickens (per 100)
          Turkeys (per 100)
  Resturants with toilet facilities (per patron)
          Without toilet facilities (per patron)
          With bars and cocktail lounge (additional quantity per patron)
 Schools: Boarding (per pupil)
          Day with cafeteria, gymnasiums, and showers (per pupil)
          Day with cafeteria but no gymnasium or showers (per pupil)
          Day without cafeteria, gymnasiums, or showers (per pupil)
 Service stations (per vehicle)
 Stores (per toilet room)
 Swimming pools (per swimmer)
 Theaters (per seat)
 Workers: Construction (per person per shift)
	Day (school or offices per person per shift)     	
   3-5
   60
   to
   50
   15
 100-150
   50
   35
   50
   50
   100
   25
   50
 100-150
   40
   60
 50-75
 100-150
 15-3D
   5
   60
   50
 75-125
250-400
   50
  35
   2
   4
  50
  40
  25
  25
  50
  20
  10
 5-10
 10-18
 7-10
  2
75-100
  25
  20
  15
  10
 400
  10
  5
  50
  15
                                                                                              23

-------
WATER CONSERVATION
     Enormous amounts of treated water are wasted in the U.S. every day. Careless user
attitudes, leakage, and bad habits cost thousands of gallons each day in even the smallest
public water supply system. The cost of losing water after expensive, complex treatment
is a serious concern. To reduce this problem, a water system may need to estabh'sh an
active conservation strategy beginning at the treatment plant and extending out to even the
smallest end user.  If water saving conservation efforts are not made to preserve and
protect water supplies, legal restrictions and water rationing may someday be forced upon
water systems and users.
     The average U.S. family of four uses an estimated 300 gallons of water every day.
This is water that has been pumped, treated, and distributed or stored for consumption
or use.  About 95 percent of this water, or 285 gallons, ends up as sewage:  As much as
120 gallons is flushed down toilets, with the remainder going down household drains.
     Depending  on the type of plumbing fixtures and personal  use habits,  average
household water use is similar to the ranges described in Table 4:

                  Table 4.-Average Household Water Use Activities

                          Per Person Per Day (Indoor Use Only)
Use
Toilet (per flush)
Faucets (per minute use)
" ^th'/ShOwer (pet ittirtute v&$
Daily laundry (per load)
Coofcing/Drinldttg"
Gallons
15-5
3
5
25
3
Gallons
per day
25
15
15
10
$ -"
% Daily
37
21
22
15
5
                                                     TOTAL       100%
 Conservation Methods
      Water conservation can be achieved by structural means, economic methods, usage
 restrictions or legal means. The following sections summarize how each of these may help
 a small public water supply system conserve.
      Structural Means. Water saving devices, accurate metering and leak detection are
 physical methods of reducing water usage and thereby conserving water.
      Water saving devices include household retrofit devices (new equipment installed in
 existing plumbing) and originally installed fixtures such as low-flow showers, faucets and
 toilets.  Retrofit devices, such as toilet tank inserts, faucet aerators, and shower flow
 restrictors can be installed in existing home plumbing. Both originally installed low-flow
 equipment and retrofit devices can significantly reduce home water use.
      A  system can also reduce water demand by measuring (metering) customer water
 use and charging water rates that discourage excessive use.  This may also serve to help
 customers identify the existence of leaks.  If all water  in a home is turned off and the
 meter continues to register, a leak exists that can be traced and repaired.
      With meters, actual use is determined and the  customer billed  accordingly.  If
 significant reductions in demand are required, a price increase can heighten a consumer's
 awareness of the  need to conserve water.  The largest user also pays the higher bill.
 Customers of a flat rate system, however, cannot be billed according to use since quantity
 used is not measured.
 24

-------
      Another effective way to conserve water is to detect and repair leaks in the water
 system. This controls loss of water that a small system has already paid to acquire, treat,
 and pressurize.  When this water leaks from the system before it reaches the consumer,
 the system loses money and gains unnecessary expenses.
      A water audit compares the total quantity of water produced with metered water
 consumption.  If the total metered water usage is less than 85 percent of the total metered
 water production, a system-wide leak detection survey should be conducted and follow-up
 repair work performed, if necessary.
      Economic Methods.  A price strategy based on metered water use can significantly
 reduce the demand for water. Flat rate systems, however, can only depend on restrictions
 and public appeals to reduce water usage.  During a drought, or other cause for
 conservation, a metered system can also charge an increased amount for increased water
 usage to discourage waste.
      Usage Restrictions.   Water use restrictions can be adopted by either metered or
 unmetered small systems.  Overall  reduction of water use may be necessary  due to
 insufficient treatment plant production capacity, limited availability of supply, or  for the
 purpose of reducing peak water demand periods and thereby maintaining pressure in the
 distribution system.  Restrictions often reduce overall water use by restricting outside
 water use to certain days or certain hours during a day.
      Legal Means.  Legal means of restricting water use by state or local agencies may
 include building code modifications and regulations designed to reduce water demand.
 Public ordinances banning car washing and lawn sprinkling have also been enforced to
 save water.
 Public Awareness
      Regardless which approach is taken to conserve water, a small system must also
 educate and involve water users about why such conservation measures are being imposed.
 Customers may react negatively  to conservation measures unless a good explanation is
 provided.  Water customers deserve an explanation of why the measures are required, how
 to conserve water and save money by using water saving devices, and how to inspect for
 leaks.  Such knowledge develops  good water saving habits.

 FIRE  PROTECTION
      Small public water supply systems should also  provide sufficient water for fire
 protection.  An adequate .water system for fire protection also results in lower fire
 insurance rates. Although potable water production is the main system responsibility, fire
 protection requirements have an important influence on the design and operation of most
 distribution systems. Fire protection consists of both public protection, available directly
 from hydrants  supplied by the public  distribution system, and private protection, such as
 building sprinkler systems.
 Fire Flow Requirements
     This is the rate of flow needed for fire fighting purposes to successfully fight a fire
 and confine the fire to a small area.  Determination of this flow depends on the size,
 construction, occupancy of the building and its proximity to other buildings. This flow is
 calculated for different areas of a locality served. A water system will also have household
water demands while fires occur; therefore, an  adequate system must be able  to deliver
the required fire flow for a specified duration with system demand at the maximum daily
                                                                              25

-------
rate.  The maximum daily consumption is defined by insurance underwriters as the
greatest total amount of water used during any 24-hour period in the past three years.
     An estimated fire flow requirement for a given fire area can be calculated with the
following formula from National Fke Codes:
           where:
                     F  = 18 C (A)05

                     F  = fire flow requirement in gpm

                     C  =  building construction coefficient: 1.5 for wood frame, 1.0
                           for ordinary construction, 0.8 for noncombustible, and 0.6
                           for fire resistant construction

                     A  =  the total floor area of all floors in square feet excluding
                           basement

     Regardless of the calculated value, fire flow requirements should not be less than
500 gpm or more than 12,000 gpm. In residential districts the required flow ranges from
a minimum of 500 gpm to a maximum of 2,500 gpm.
     The period of time necessary to deliver the required fire flow is an important factor
in water supply design because it directly influences the size of the storage facilities
needed. Required fire flow duration is summarized in the table below adapted from the
AWWA manual on Water Utility Management:
                Required Fire Flow - gpm
                     10,000 and greater
                      9,000 - 10,000
                      8,000-  9,000
                      7,000-  8,000
                      6,000-  7,000
                      5,000-  6,000
                      4,000-  5,000
                      3,000-  4,000
                      2,500 and less
                                          Required Duration - Hour
                                                    10
                                                     9
                                                     8
                                                     7
                                                     6
                                                     5
                                                     4
                                                     3
                                                     2
      A suggested minimum, storage capacity would be the maximum day usage plus fire
 requirements, less the daily capacity of the water plant and system for the fire flow period.
 Required Pressure
      If the small system supplies water to pumpers to fight fires, 20 psi is a minimum
 required  pressure to provide a positive  pressure at the pumper suction  inlet  while
 minimizing the chance of a negative pressure developing in the distribution system. In
 small systems that do not use pumpers, actual pressure in the distribution system is used
 to fight fires. A pressure of at least 60 psi is needed for small towns, and at least 50 psi
 in areas where no building exceeds two stories.
 26

-------
Distribution System
      Supply mains and secondary feeders should be of sufficient size to deliver fire flow
and maximum consumption demands to all areas. They should be properly spaced and
looped so that no single area is totally dependent on one main.
      A small system distribution grid should not contain mains smaller than 6 inches in
diameter with no single interlock section longer than 600 feet.  If street arrangement or
topography does not allow this arrangement, then 8-inch diameter minimum mains should
be used.
Valves
      Valves should be arranged in shutoff lengths of 500 to 800  feet and arranged so
repairs or breaks do not require shutdown of a main artery.
Hydrants
      All water for public fire protection must be delivered through hydrants; therefore,
there must be a sufficient number of them strategically placed throughout a small system.
      Hydrant spacing is dictated by the required fire flow since the capacity of a single
hydrant is limited.  A single hose stream is considered to be 250  gpm. The minimum
building area served by a single hydrant is commonly accepted as 40,000 square feet with
a maximum area served of 100,000 square feet.  Thus minimum hydrant spacing should
be 200 feet, and in no case to exceed 500 feet apart.  Ordinarily, hydrants are located at
street intersections where streams can be pointed in any direction.
      The ability to satisfy these fire protection requirements,  whether through source
development or careful control by means of conservation measures, ultimately determines
the adequacy of a selected water supply source.

SANITARY  SURVEY
      A sanitary survey of water sources is very important. For a new supply, the sanitary
survey should be  made  along with the collection  of initial hydrogeologic and other
information regarding the source and its ability to meet existing and future needs. The
sanitary survey should include the detection of all existing and potential health hazards and
the assessment of their present and future importance. Experts trained and competent in
public health engineering and the epidemiology of waterborne diseases should conduct the
sanitary survey.   In the  case of existing surface water supplies, a sanitary survey is
recommended every three to five years to control health hazards and maintain high water
quality.  A periodic sanitary survey is required for some public systems under the total
conform regulations.
      The sanitary survey involves three phases: planning the survey, conducting the survey,
and compiling the final report. Those phases are presented in the following sections.
Planning the  Survey
      Before conducting or scheduling a sanitary survey, past sanitary survey reports, water
system plans, any  and  all sampling results, operating reports and engineering studies
should be found and closely studied.  This pre-survey review provides an opportunity to
see how and where samples are  collected and how field measurements are made.  The
results of the pre-survey review should include a list of items to check while in the field,
a list of questions about the system, and the format of the survey.
                                                                              27

-------
Conducting the Survey
     This is  the most important part of the survey. It involves interviewing those in
charge of managing the system, reviewing major parts of the system from the source to
distribution, and investigating any problems that are identified.  Water sampling, and
testing of equipment and facilities, are all part of the survey.  Records of any field tests
or water quality monitoring should also be checked to make sure proper maintenance is
being performed.
     Source Evaluation.  Based on field  observations and discussions, source evaluation
should include a description of the area, stream flow, land usage, degree of public access,
soil and ground cover.  Next, sources of  contamination, both man-made and  natural,
should be identified by visiting the area and asking others about the watershed.  Surface
intakes, infiltration galleries, springs and .catchment/cistern systems should be evaluated
in terms of their construction and their ability to protect the water supply. The source
should be evaluated for its quantity, quality, protection from contamination, protection
from  damage, and  ease of testing.  All pumps,  pump  houses and controls should be
checked for operation, maintenance, good  condition and safety hazards.  In addition, all
check valves, blow off valves, water  meters and other parts should be checked to  make
sure they operate and are being properly maintained.   Finally,  the identification and
control of any contaminant sources must be determined hi relation to the impacts on
water quality.
      Treatment Evaluation.  Depending on the source water quality,  one or more of
several water treatment processes may be in use. These processes may include oxidation,
coagulation,  sedimentation,  filtration  and disinfectiqn.  In  addition, more advanced
processes such as granular activated carbon (GAC) adsorption and membrane separation
may be part of the treatment system.                             *-
      Disinfection is one treatment method which is common to many water supplies for
insuring that  drinking water is free of bacterial contamination.  Disinfection feed, dosage
and  contact  time should be  evaluated.   Critical  spare  parts,  including a  back-up
disinfection unit in case of failure, may be required to be on hand.  Proper storage
procedures for the disinfectants and other safety precautions should also be followed to
insure a safe, properly maintained system.
      In all cases, treatment evaluation should include investigation of  all  treatment
processes, availability of materials and spare parts, monitoring of process  effectiveness,
record keeping, competence of personnel who operate and maintain the system, and other
key factors.
     Distribution System Evaluation. Water quality during storage and distribution must
also  be  maintained.  The distribution  system should  have  a scheduled  program for
removing any sediments that accumulate.  The distribution system should also be inspected
regularly for any possible sources of contamination. All distribution system overflow lines,
vents, drahuuies or cleanout pipes should be turned downward and screened.  Capacity
should be determined, and should be high enough to ensure sufficient pressure and flow.
The reservoir should also be able to be isolated from the system.
      Cross connections should be identified within  the system.  Each cross connection
should be controlled and, preferably, eliminated.  Annual testing of backflow prevention
devices is advisable to assure that proper pressures and flows are maintained. In addition,
a maintenance program should be developed to check leakage, pressure, corrosion control,
28

-------
working valves and hydrants.  More information on detection and prevention of cross
connections is provided in Part V.
     Management/Operation.  The overall operation of a system should be evaluated for
its ability to deliver high quality drinking water. User fees should be charged to customers
and collected regularly. There should be enough personnel to operate and manage the
system. Operation and maintenance records should be kept readily available.  Facilities
should be free from safety defects.  Emergency plans should be developed and usable, and
include enough tools, supplies and maintenance parts.
     The  information furnished  by a complete  sanitary survey is  essential for the
interpretation of bacteriological and chemical water quality data. This information should
always accompany  the laboratory findings.  The following outline covers the essential
factors that should be investigated or considered in a sanitary survey. Not all of the items
apply to any one system and, in some cases, items not in the list might be more important
to a particular water supply.

     Ground Water Supplies
     a.    Character of local geology; slope of ground surface.
     b.    Nature of soil and underlying porous material; whether clay, sand, gravel, rock
           (especially porous limestone); coarseness  of sand  or gravel;  thickness  of
           water-bearing  layer, depth to water table; location, log  (the underground
           features found by drilling a well), and construction details of local wells, both
           in use and abandoned.
     c.    Slope of water table, preferably as determined from observational wells or as
           indicated by the slope  of ground surface (which is an inexact way estimating
           water-table slope).
     d.    Size of drainage area likely to contribute water to the supply.
     e.    Nature, distance, and direction of local sources of pollution (individual septic
           tanks [density per square mile] and soil percolation rate).
     f.    Possibility of surface or drainage water entering the supply and wells becoming
           flooded; methods of protection.
     g.    Methods used for protecting the supply  against  pollution  by wastewater
           collection and treatment facilities and industrial waste disposal sites.
     h.    Well construction:
           1.    Total depth of well.
           2.    Casing: diameter, wall thickness, material, and length from surface.
           3.    Screen or perforations: diameter, material,  construction, locations, and
                 lengths.
           4.    Formation seal: material (cement, sand, bentonite, etc.), depth intervals,
                 annular  thickness, and method of placement.
      i.    Protection of well at top: presence of sanitary well seal, casing height above
           ground, floor, or flood level, protection of well vent, protection of well from
           erosion and animals.
     j.    Pumphouse construction (floors, drains, etc.), capacity of pumps, and whether
           water goes to  storage or distribution system.
      k.    Drawdown when pumps are in operation; recovery rate when off.
                                                                                 29

-------
     1.    Availability of alternate  (although, unsafe) water source that would require
          treatment.
     m.   Disinfection: equipment, back-up disinfection, supervision, test kits, or other
          types of laboratory control.
     n.    Availability of back-up power source (e.g., diesel generator) to protect supply
          during power outages.
     o.    Adequacy of supply to meet system demands (safe yield).
     p.    Adequacy of treatment to provide reliable, high quality drinking water.

     Surface-Water Supplies
     a.    Nature of surface geology: character of soils and rocks.
     b.    Character of vegetation, forests, cultivated and irrigated land, including salinity,
          effect on irrigation water, etc.
     c.    Population and sewered  population per square mile of watershed area.
     d.    Methods of sewage disposal, whether by diversion  from watershed or by
          treatment.
     e.    Character and efficiency of sewage-treatment works on watershed.
     f.    Proximity of sources of fecal pollution to intake of water  supply.
     g.    Proximity, sources, and  character of industrial wastes, oil  field brine, acid
          mine waters, etc.
     h.    Adequacy of quantity of supply (safe yield).
     i.    For lake or reservoir supplies:  wind direction and velocity data, drift of
          pollution, sunshine data, algal blooms, stratified lake  or impoundment.
     j.    Character and quality of raw water:  concentration  of conform organisms,
          algae, turbidity, color, objectionable mineral constituents.
     k.    Nominal period of detention in reservoir or storage basin.
     1.    Probable minimnm tune required for water to flow from sources of pollution
          to reservoir and through reservoir intake.
     m.   Shape of reservoir, with reference to possible  currents of water, induced by
          wind or reservoir discharge, from inlet to water-supply intake that may cause
          short-circuiting (uneven  flow) to  occur.
     n.    Measures to protect the watershed from controlled fishing, boating, landing of
          airplanes, swimming., wading, ice cutting, animals on marginal shore areas and
          in or upon the water.
     o.    Watershed control through ownership or zoning for restricted uses.
     p.    Efficiency and constancy of maintaining a controlled  watershed.
     q.    Treatment of water: kind and adequacy of equipment; duplication of parts;
          effectiveness of treatment;  adequacy of supervision, operation, and testing;
          contact period after disinfection; free chlorine  residuals.
     r.    Pumping facilities: pumphouse, pump capacity and  standby units, storage
          facilities.
     s.    Presence of an unsafe alternative source that may need treatment or have
          cross-connections that are a danger to public health.
30

-------
Reporting the Survey
     A final report of the survey should be completed as soon as possible after conducting
the survey. The report can be used by the water system owner for daily operation and
long term planning.  It should include the date of the survey, who was present during the
survey, the findings of the survey, the recommended improvements to problems found, and
the dates set to complete improvements.  The state agency responsible for water supply
may also require a copy of the sanitary survey reports.
                                                                            31

-------

-------
               Part II
                          Ground  Water
ROCK  FORMATIONS
      The rocks that form the crust of the earth are divided into three classes:

      1.     Igneous. Rocks that are derived from the hot magma deep in the earth are
             igneous.  They include granite and other coarse crystalline rocks, dense
             igneous rocks (found in dikes and sills), basalt and other lava rocks, cinders,
             tuff, and other loose volcanic materials.
      2.     Sedimentary.  Rocks that consist of chemical particles and rock fragments
             deposited by water, ice, or wind are sedimentary. They include deposits of
             gravel, sand, silt, clay, and the hardened equivalents of these—conglomerate,
             sandstone, siltstone, shale, limestone, and deposits of gypsum and salt.
      3.     Metamorphic.  Rocks that are made up of both igneous and   sedimentary
           ,  rocks   and  are formed  at great  depths  by  heat and  pressure  are
             metamorphic.  They include gneiss, schist, quartzite, slate, and marble.

      The pores, joints, and crevices of the rocks in the  saturation zone  are generally
filled with water. Although the openings in these rocks are usually small, the total amount
of water that can be stored in subsurface reservoirs of rock formations is large.  Those
subsurface reservoirs are known as aquifers. The aquifers that contain the most water are
deposits of clean, coarse sand and gravel; coarse, porous sandstones; cavernous limestones;
and  broken lava rock.  Some dense limestones, as well as most  of the igneous and
metamorphic rocks do not hold much water. Silts and clays are among the most dense
formations.   The openings  in these materials are  too small to hold water, and  the
formations  cannot maintain large openings under pressure. Dense materials near  the
surface, with crevice-like openings and cracks, may yield small  amounts of water.

GROUND  WATER  BASINS
      In an undeveloped ground water basin, movement of water to lower basins, seepage
from and to surface-water sources, and transpiration depend on how much water is already
in the basin and the rate of recharge.  During periods of heavy rainfall, recharge may
exceed discharge. If so, the excess rainfall increases the amount of water in the ground
water basin. As the water table or artesian pressure increases, the water pressure at the
points of discharge becomes higher and outflows increase.  Extended dry periods will
cause water-table levels and artesian pressures to decline.  In most undeveloped basins,
                                                                              33

-------
 the major fluctuations in storage are seasonal, with the mean annual elevation of water
 levels changing little between years. Thus, the average annual inflow to storage equals the
 average annual outflow—a quantity of water referred to as "the basin yield".
        Proper development of a ground water source requires careful consideration of the
 hydrological and geological conditions in the area.  In order to take full advantage of a
 water source for domestic use, the assistance of a qualified ground water engineer, ground
 water geologist, hydrologist, or contractor familiar with the construction of wells in the
 area  should be sought. Information on the geology and hydrology of an area should be
 available  in publications of the U.S. Geological Survey or from other federal and state
 agencies.  The National Water Well Association1 also offers assistance.

 SANITARY  QUALITY
        When  water seeps  through overlying material to the water table, particles in
 suspension, including micro-organisms, may be removed. How much is removed depends
 on the thickness and character of the overlying material.  Clay, or "hardpan", provides the
 most effective natural  filter for ground water.  Silt and sand also provide good filtration
 if fine enough and in  thick enough layers.  The bacterial quality of the water improves
 during  storage in the  aquifer because conditions  are usually unfavorable for bacteria.
 Clarity alone  does not guarantee that ground water is safe  to drink; this can  only be
 determined by laboratory testing.
        Ground water  found in unconsolidated formations (sand, clay, and gravel)  are
 protected from sources of pollution by these same types  of materials and is likely to be
 safer than water coming from consolidated formations (limestone, fractured rock, lava,
 etc.).
        Where overlying materials provide limited filtration, better and more sanitary water
 can sometimes be obtained by drilling deeper. It should be recognized, however, that
 there are areas where it is  not possible, because of the geology, to find water at greater
 depths. Much unnecessary drilling has been done in the mistaken belief that more and
 better quality water can  always be obtained by drilling deeper.
        In areas without central sewerage systems, human excreta are usually deposited in
 septic tanks,  cesspools,  or pit privies.  Bacteria  in the  liquid discharge  from such
 installations may enter shallow aquifers.  Sewage discharges have been known to find their
 way  directly into water-bearing  formations  from abandoned wells or soil-absorption
 systems.  In such areas, the threat of  contamination may be  reduced by proper well
 construction and/or by  locating wells  farther from sources of contamination.  It is
 advisable  to  locate wells  so  that  the normal  movement  of ground  water carries
 contaminants away from the well.

 CHEMICAL  AND  PHYSICAL  QUALITY
        The mineral content of ground water reflects its movement through the minerals
 which make up the earth's  crust. Generally, ground water in arid regions  is harder and
 more mineralized than water in regions with high annual rainfall. Also, deeper aquifers
 are more  likely to contain higher concentrations of minerals in solution because the water
1 National Water Well Association, 6375 Riverside Drive, Dublin, Ohio  43017. Phone:  (614)761-1711.

 34

-------
 has had more time-perhaps millions of years-to dissolve the mineral rocks. For any
 ground water region, tkere is a depth below which salty water, or brine, is almost certain
 to be found.  This depth varies from one region to another.
        Some substances found naturally in ground water, while not necessarily harmful,
 may impart a disagreeable taste or undesirable property to the water.  Magnesium sulfate
 (Epsom salt), sodium sulfate (Glauber's salt), and sodium chloride (common table salt)
 are a few of these.   Iron and manganese are commonly found in ground water.
 Interestingly, regular users of waters containing so-called "excessive" amounts of these
 common minerals become accustomed to the water and consider it tasty.
        Concentrations of chlorides and nitrates that are high for a particular region may
 be indicators of sewage pollution or contamination from agricultural fertilizers. This is
 another reason why a chemical analysis of the water should be made regularly and these
 results interpreted by someone familiar with the area.
 Temperature
        The temperature of ground water remains nearly constant throughout the year
 Water from very shallow sources (less than about 50 feet or  15 meters deep) may vary
 somewhat from one season to  another, but water from deeper zones remains quite
 constant-its temperature being close to that of the average annual temperature at the
 surface. This is why water from a well may seem relatively warm in winter or cool in
 summer.
        Contrary to popular belief, colder water is not obtained by drilling deeper. Beyond
 about 100 feet of depth, the temperature of ground water increases steadily at the rate of
 about 1°F for each 75 to 150  feet of depth.  In volcanic regions this rate of increase may
 be much greater.

 DISTANCES  TO  SOURCES  OF  CONTAMINATION
       All ground  water sources should be located a safe  distance from sources of
 contamination.  In cases where sources are severely limited,  however,  a ground water
 aquifer that might  become  contaminated  may be considered for a water  supply if
 treatment is provided.  After  a decision has been made to use  a water source in an area,
 it is necessary to determine the direction of water movement and the distance the source
 should be from the origin  of contamination. It should be noted that the direction of -
 ground water flow does not always follow the slope  of the land surface. A determination
 of a safe distance is based on specific local factors  described in the section on "Sanitary
 Survey" in Part I of this manual.
       Because many factors determine the  "safe"  distance  between ground water and
 sources of pollution, it is impractical to set fixed distances.  The table on the following
 page offers guidance on determining safe distances for wells. Where sufficient information
 is  unavailable, the distance should be the maximum that economics, land ownership,
 geology, and topography permit.  Each installation should be inspected by a person with
 sufficient training and experience to evaluate all of the factors  involved.
       Since safety of a ground water source depends primarily  on considerations of good
well construction and geology, these should be the primary factors in determining safe
distances for different locations.  The following criteria apply only to properly constructed
wells as described in this manual.  There is no "safe" distance for a poorly constructed
well!
                                                                              35

-------
      When a properly constructed well penetrates an unconsolidated formation (sand,
clay, gravel) with, good filtering properties, and when the aquifer itself is separated from
sources of contamination by similar materials, experience has demonstrated that 50 feet
(or 15 meters) between the well and the source of the potential contamination is adequate.
Shorter distances should be accepted only after qualified state or local health agency
officials have conducted a comprehensive sanitary survey proving that shorter distances are
safe.
      When wells must be constructed in consolidated formations (limestone, fractured
rock, lava formations, etc.), extra care should always be taken when locating the well and
when setting "safe" distances, since pollutants have been known to travel great distances
hi such formations. The owner should request assistance from the State or local health
agency.
       If individuals propose to  install a properly constructed well  in formations  of
unknown character, the State or  U.S. Geological Survey and the State or local health
agency should be consulted.
       The following table is offered as a  guide in determining safe distances for wells:
Formations
Favorable (uneonsolidated)
Unknown
Poor (consolidated)
Minimum acceptable distance from
well to source of contamination
$Q feet. Lesser distances only cm jjealth department
approval following Comprehensive sanitary Survey 
-------
       Lead. Use of brass and other lead-containing materials in operating wells should
be avoided.  Corrosive well water can corrode plumbing in lead service lines and lead
solders contribute to lead in drinking water. Ingestion of large amounts of lead may cause
impaired blood formation, brain damage, increased blood pressure, premature birth, low
birth weight and nervous system disorders. Lead contamination especially poses serious
health threats to young children.
       Radionuclides.  Radionuclides include naturally occurring  substances that emit
radiation as they decay, primarily hi systems using ground water. Radionuclides such as
radium and uranium in drinking water may be ingested into the body and cause cancer of
the bone and kidney.  Radon gas, which is dissolved in some ground waters, can be easily
released in household ah", causing a greater risk of lung cancer.
       Bacteria and Viruses and Other Pathogens. Microbiological contaminants may enter
ground water and  eventually drinking water systems and result  hi highly contagious
diseases. Symptoms of these diseases include nausea, vomiting, diarrhea and abdominal
discomfort.
       Organic Compounds. Other man-made organic materials may migrate from active
or abandoned industrial waste sites.  Many of these organic compounds migrate through
ground water and can cause serious health risks.
Underground Disposal
       Cesspools, septic systems, dry wells, disposal and injection wells of non-hazardous
waste and hazardous waste, landfills, agricultural drainage, dumps and leaching pits that
are in direct contact with the aquifer also increase the likelihood of contamination.  This
can be directly, by a contaminant leaching into the aquifer and into a drinking water well,
or indirectly by reducing the amount of soil filtering the contaminants and allowing them
to travel faster and  further distances through  the ground. In areas where direct  disposal
of wastes  into sink holes or cavities (limestone terrains) has occurred, the risk of
contamination is also increased.
Limited Filtration
       When materials surrounding the well and overlying the aquifer are too coarse
(limestone with solution cavities, gravel, etc.) or too thin (less than two feet) to provide
effective filtration, the risk of contamination  is increased. Lack of a fine grain surface
layer permits faster infiltration of storm water and the contaminants dissolved in it.
Aquifer
       When the aquifer materials  are too coarse to  provide good filtration (dissolved
limestone, fractured rock,  etc.), contaminants  entering aquifer may travel great distances
very rapidly.   Often the exact destination of contaminants may be difficult to predict
without the use of tracers.  In such cases it is  important to know the direction of ground
water flow, and the locations of possible  contamination sources in order to locate wells
"upstream" of the contamination or  outside the contaminated flow path.
Flow Changes
       If large volumes of liquid, waste are being discharged or ponded and are reaching
the aquifer, the slope of the water table and direction of ground water movement can be
altered. Water withdrawal will also change the direction and increase the speed of ground
water movement. Increased withdrawal of water from wells directly increases the speed
of ground water  flow and may, therefore, increase the likelihood of contamination.  -
                                                                               37

-------
Multiple Threats
      More than one source of contamination (e.g., domestic sewage and industrial
wastes)  in an area increases the total pollution load in the aquifer system and increases
the risk of contamination. Also, interactions from different contaminants may in some
instances produce hazardous compounds that were not originally present, increasing the
risk to public health.
Wellhead Protection Areas
      A wellhead protection area provides a protective barrier for the area surrounding
a. well or well field supplying a water system.  Ensuring protection of the well or wells
from possible contamination requires considerable investigation of the surface and ground
water flows around the wells and locating  sources  of potential  contamination.   A
protection area around a well should be a minimum of 50 feet between the well and any
form of potential contamination, and can help ensure a safe supply of drinking water.
Properly sealing the well to prevent any pollutants or rain water from entering the well
and or selecting an aquifer which has no contamination sources "upstream" of the well are
also effective.
      As stated previously, if one plans to install  a properly constructed well in  a
formation of unknown character, the State, U.S. Geological Survey, or local health agency
should be consulted. These agencies can also provide advice on local groundwater flows
and areas which should be avoided due to the potential for contamination.

DEVELOPMENT OF GROUND WATER
       Ground water development depends on the geological formations and hydrological
characteristics of the water-bearing formation. The development of ground water falls into
two main categories:

       1.     Development by wells
             a.    Nonartesian or water table
             b.    Artesian
       2.     Development from springs
             a.    Gravity
             b.    Artesian

Nonartesian Wells
       Nonartesian wells are those  that penetrate formations in which ground water  is
found under water-table conditions. Pumping the well lowers the water  table near it,
creating a pressure difference and causing water to flow toward the well.
Artesian Wells
       Artesian wells are those in which the ground water is under pressure because it is
confined beneath an impermeable layer of material below the recharge area of the aquifer.
Intake or recharge areas are commonly at high-level surface outcrops of the formations.
Ground water flow occurs from high-level outcrop areas to low-level outcrop areas-which
are areas of natural discharge. It also flows toward areas where water levels are lowered
artificially by pumping from wells. When the well water level is higher than the top of the
aquifer, the well is said to be artesian. A well that yields water by artesian pressure at the
ground surface is a "flowing" artesian well.
38

-------
 Gravity Springs
       Gravity springs occur in places where water percolating through permeable material
 that overlays an impermeable stratum comes to the surface. They also occur where the
 land surface intersects the water table.  This type of spring is particularly sensitive to
 seasonal changes in ground water storage and frequently dwindles or disappears during
 dry periods.  Gravity springs are characteristically low-volume sources, but when properly
 developed, they make satisfactory individual water supply systems.
 Artesian Springs
       Artesian springs discharge from artesian aquifers.  They may occur where the
 confining impermeable formation is ruptured by a fault or where the aquifer discharges
 to a lower area.   The flow from  these springs  depends on differences  in recharge,
 discharge elevations and on the size of the openings transmitting the water.  Artesian
 springs are usually more dependable than gravity springs, but the former are particularly
 sensitive to other wells being developed in the same aquifer. As a consequence, artesian
 springs may be dried by pumping.
 Seepage  Springs
       Seepage springs are those in which the water flows (or seeps) out of sand, gravel,
 or other material containing many small openings.  This includes many large and small
 springs. Some large springs have extensive seepage areas and are usually marked by plant
 growth. The water of small seepage springs may be colored or carry an oily scum because
 of decomposition of organic matter or the presence of iron.  Seepage springs may emerge
 along the top of an impermeable bed, but they occur more commonly where valleys are
 cut into the zone of saturation of water-bearing areas. These springs are generally free
 from harmful bacteria, but they are susceptible to contamination by surface runoff which
 collects in valleys or depressions.
 Tubular Springs
       Tubular springs issue from relatively large channels, such as the solution channels
 from caverns of limestone, soluble rocks or smaller channels that occur in glacial drift.
When  the water reaches the channels by percolation through sand or other fine-grained
material, it is usually free from contamination. When the channels receive surface water
 directly or  receive the indirect effluent  of cesspools, privies, or septic tanks, the water is
usually unsafe for consumption.
Fissure Springs
       Fissure  springs issue  along bedding, joint, cleavage,  or fault planes.  Their
 distinguishing feature is a break in the rocks along which the water passes.  Some of these
springs discharge uncontaminated water from deep  sources.  Many thermal springs are of
this type.  Fissure  springs, however, may discharge water which is contaminated by
drainage close to the  surface.
Pumping Effects
       When a well is pumped, the water level near the well is lowered (see Figure 2a).
This lowering  or  "drawdown"  causes  the water  table or artesian pressure surface,
depending on the type of aquifer, to take the shape of an inverted cone called a "cone of
depression".  This inverted cone, with the well at the lowest point, is measured in terms
of the  difference between the static water level  and the pumping level.  At increasing
distances from the well, the water level increases until it meets the static water table.  The
distance from the well at which this occurs is called "the radius of influence".  The radius
                                                                               39

-------
                                EFFECT OF PUMPING ON CONE OF DEPRESSION
                                                           -Discharge
                Ground Surface
                  fgrie o* Depression for
                                                  Cone of Depression for
                                   Craw-Down       tesser Pumping Rate
               .5	?—, Ridiusof Influence
                             EFFECT OF AQUIFER MATERIAL ON CONE OF DEPRESSION
                                                                         raw-Down
                                                                                  t
                                                                               Cone of Depress on
        - .,  Cone of Depression;;
Draw-Down    •             ,   ,,,    	,,
                    Radius of I nftuence
                                                               Radius of Influence
                           EFFECT OF OVERLAPPING FIELD OF INFLUENCE PUMPED WELLS

                           A                                             R
                           	-
                                                                                 Discharge
                            FIGURE 2. - Pumping effects on aquifers.
40

-------
of influence is not constant but tends to expand continuously with pumping. At a given
pumping rate, the shape of the cone of depression depends on the characteristics of the
water-bearing formation. Shallow and wide cones will form in highly permeable aquifers
composed of  coarse sands or gravel.  Steeper and narrower cones will form in  less
permeable aquifers.   As  the  pumping  rate  increases,  the  drawdown  increases;
consequently, the slope of the cone gets deeper and more narrow.
       The character of the aquifer—artesian or water table~and its physical characteristics
that affect the cone's shape include thickness, lateral extent, and the size and grading of
sands or gravels.  In a material of low permeability, such as fine sand or sandy clay, the
drawdown will be greater and the radius of influence less  than from very coarse gravel
(see Figure 2b).  For example, when other conditions are equal for two wells, expect that
pumping costs for the same pumping rate to be higher for the well surrounded by material
of lower permeability because of the greater drawdown.
       When the cones of depression of the two or more wells overlap, the local water
table will be  lowered (see Figure 2c).  This requires additional pumping lifts  to obtain
water from the interior portion of the group of wells.  A wider distribution of the wells
over the ground water basin will reduce the cost of pumping and will allow greater yield.
Yield of Wells
       The amount of water that can be pumped from any well depends on the character
of the  aquifer and the construction of the well.  Contrary to popular belief,  doubling the
diameter of a well increases its yield only about 10 percent; conversely, it decreases the
drawdown only about 10 percent for the same pumping rate. The casing diameter should
be chosen to provide space for proper installation of the pump.  Individual wells seldom
require casings larger than 6 inches, 4-inch wells are common.
       A more effective way of increasing well capacity is by drilling  deeper into the
aquifer—provided that the aquifer is deep enough.  Also, the inlet portion of the  well
(screen, perforations, slots) is important in determining the yield of a well in a sand or
gravel formation.   The amount of  "open area" in the screened or perforated portion
exposed to the aquifer is critical. Wells completed in consolidated formations are usually
of open-hole construction; there is no casing in the aquifer.
       It is sometimes difficult to accurately predict a well's yield before its completion.
Studying the  geology of the area and interpreting the results obtained from nearby wells
gives some indication. This information will be helpful in selecting the location and  type
of well most likely to be successful. The information can also provide an indication of the
yield to expect from a well.
       A.common  way to describe  a well's yield is to  express its discharge capacity hi
relation to its drawdown.  This relationship is called "the specific capacity" of the well and
is expressed in "gallons toer minute (gpm) per foot of drawdown." The specific capacity
may range from less than 1 gpm per foot of drawdown for a poorly developed well--
especially one in a "tight" aquifer—to more than 100 gpm per foot of drawdown for a
properly developed well in a highly permeable aquifer.
       Dug wells can be sunk only a few feet below the  water table. This seriously limits
drawdown during pumping, which in turn limits the yield of the well. A dug well that taps
a highly permeable formation, like gravel, may yield 10 to 30 gpm or more with only 2 or
3 feet  of drawdown. If the formation is primarily fine sand, the yield may be on the order
of 2 to 10 gpm.  These results refer to dug wells of common size.
                                                                               41

-------
       Like dug wells, bored wells can also be sunk only a limited depth below the static
 water level-probably 5 to 10 feet  into the water-bearing formation.  If the well is
 nonartesian, the drawdown should not be more than 2 or 3 feet.  If the well  taps an
 artesian aquifer, however, the static water level will rise to some point above the  aquifer.
 The available drawdown and the well's yield will then be increased. A bored well that taps
 a highly permeable aquifer and provides several feet of available drawdown may  yield 20
 gpm or more. If the aquifer has a low permeability or the water is shallow, the yield may
 be much lower.
       Driven wells can be sunk  to as much as 30 feet or more below the static water
 level.  A well at this depth provides 20 feet or more of drawdown.  The  well's  small
 diameter limits the type of pump that can be employed, so that under favorable conditions,
 the yield is limited to about 30 gpm. In fine sand or sandy clay formations of limited
 thickness, the yield may be less than 5 gpm.
       Drilled and jetted wells can usually be sunk to such depths that the depth of the
 well's standing water and the available drawdown will vary from less than 10  to hundreds
 of feet.  In productive formations of  considerable thickness, yields of 300 gpm  and more
 are readily attained. Drilled wells can be constructed in all instances where  driven wells
 are used and in many  areas where  dug and bored wells are  constructed.  The larger
 diameter of a drilled well-compared with that of a driven well-permits the use of larger
 pumping equipment which can develop the aquifer's  full capacity.  Again, a well's yield
 varies greatly  depending on the permeability  and thickness of the formation, the
 construction of the well, and the available drawdown.
       Table 5 provides details about penetrating various types of geologic formations by
 the methods indicated.
42

-------
TABLJE  5. - Suitability of well construction methods to different geological conditions.
Characteristics
Range Of practical 4eptte>
Diameter
Type of geologic formation:
Clay
Silt
Sand
Gravel
Cemented Gravel
Boulders


Sandstone
Limestone

Dense igneous rock
Dug
0-50 feet
3-20 feet

Ye*
Yes
Yes
Yes
Yes
Yes


Yes, if soft
and/or
fractured
No
Bored
0-100 feet
2-30 inches

Yes
Yes
Yes
Yes
No
Yes, if less
than well
diameter
,Yes, Jf .sofj
and/or
fractured
No
Driven
0-50 feel
• 1.25-2 inches

Y<*
Yes
Yes
Fine
No
No


TWn laye«
No

No
Jetted
0-100 feet
2-12 inches

Y§fi
Yes
Yes
1/4" pea gravel
No
No


No
No

No
Characteristics
Range iSf practical: depths :
Diameter
Type of geologic formation:
Clay
Silt
•Sand ,
Gravel
Cemented Gravel :
Boulders
.Sandstone: \
Limestone
Dense igneous rock
Drilled
Percussion
0-1,000 fetf
4-18 inches
Yes
Yes
Yes
Yes
Yes :
Yes, when in
firm bedding
Yes
Yes
Yes
Rotarv
Hydraulic
0-1,000 feet
4-24 inches
,Yes
Yes
Yes
Yes
Yes
(Difficult)
Yes
Yes
Yes
Air
0-750 feet
4-10 inches
No
No .
No
No
No
No
Yes
Yes
Yes
              Flow pressure is the pressure in the supply near the faucet or water outlet while the faucet
              or water outlet is wide open and flowing.
                                                                                         43

-------
Preparation of Ground Surface at Well Site
      A properly constructed well should exclude surface water from a ground water
source to the same degree as the natural undisturbed geologic formation. The top of the
well must be constructed so that no foreign matter or surface water enters. The well site
should be  properly  drained and adequately protected against erosion,  flooding,  and
damage or contamination from animals.  Surface drainage should be diverted from the
well.

CONSTRUCTION OF WELLS
Dug Wells
      Constructed by hand, the dug well is usually shallow. It is more difficult to protect
from contamination, although, if finished properly, may provide a satisfactory water supply.
Because of advantages offered by other types of wells, dug wells should not be considered
if it is possible to construct one of the other wells described later in this section.
      Dug wells are usually excavated with pick and shovel.  Workers  can lift the
excavated material to the surface with a bucket attached to a windlass or hoist. A
power-operated clam shell or orange peel bucket may be used in holes greater than 3 feet
in diameter where the material is principally gravel or sand.  In dense clays or cemented
materials, pneumatic hand tools are effective means of  excavation.
      To prevent the native material from caving, place  "a crib" or lining in the excavation
and move  it downward as  the pit deepens.  The  space between the lining  and the
undisturbed embankment should be backfilled with  clean material.   In the region of
water-bearing formations, the backfilled material should be sand or gravel. Place cement
grout to a depth of 10 feet below the ground surface to prevent entrance of surface water
along the well lining.
      Depending on the availability of materials and labor cost, dug wells may be lined
with brick,  stone or concrete.  Pre-cast concrete pipe, available in a wide range of sizes,
provides an excellent lining.  This lining can be used as  a crib as the pit deepens. When
using the lining as a crib, a concrete pipe with tongue-and-groove joints and smooth
exterior surface is preferred (see Figure 3).
      Bell and spigot pipe may be used for a lining where it can be placed inside the crib
or in an unsupported pit.  This type of pipe requires careful backfilling to guarantee a
tight well near the surface.  The primary factor in preventing contaminated water from
entering a  dug well  is the sealing of the well lining and preventing seepage of surface
water at and near the well.
      Most dug wells do not penetrate far below the water table because of the difficulty
of manual excavation including handling cribs and linings.  The depth  of excavation can
be increased by using pumps to lower the water level during construction.  Because of
their shallow penetration  into the zone of saturation,  many dug wells fail  in  tunes of
drought when the water level recedes or when large quantities of water are pumped from
the wells.
Bored Wells
      Bored wells are commonly constructed with earth augers turned either by hand or
by power equipment. Constructing such wells is feasible at depths  of less than 100  feet
provided the water  requirement  is low and the overlying material has  non-caving
properties and contains few large boulders. In suitable material, holes from 2  to 30 inches
44

-------
Note:
  Pump screen to be
  placed below point
  of maximum draw-down
                          Pump Unit
            Sanitary Well Seal

     Cobble Drain
Reinforced Concrete
Cover Slab Sloped
Away From Pump
        FIGURE 3. - Dug well with two-pipe jet pump installation.
                                                                                           45

-------
                           Galvanized
                           Steel Alloy,or
                           Stainless Steel
                           Construction
                           Throughout
                 Continuous
                 Slot Type
Brass Jacket
Type
Brass Tube
Type
                     FIGURE 4. * Different lands of drive-wettpoints.

in diameter can be bored to about 100 feet without caving in.  In general, bored wells have
the same  characteristics as dug wells, but they  may be extended deeper into the
water-bearing formation.
       Bored wells may be cased with vitrified tile, concrete pipe, standard wrought iron
pipe, steel casing, or other suitable material capable of sustaining imposed loads. The well
may be completed by installing well screens or perforated casing in the water-bearing sand
and graveL Provide proper protection from surface drainage by sealing the casing with
cement grout to the depth necessary to protect the well from contamination (see Appendix
C).
Driven Wells
       The simplest and least expensive of all wells is the driven well. It is constructed
by driving a drive-well point into the ground which is fitted to the end of a series of pipe
sections (see Figures 4 and 5) made of forged or cast steel.  Drive points are usually 1 1/4
46

-------
Wfj
             -Cold Rolled Shafting
              Weight 20 to 25 Ibs.

              • Welded Joint

             -Vent'Hole

             - Pipe -
               Weight 25 to 30 Ibs.


             -Drive Cap
              -Riser Pipe
 -Riser Pipe


-Driving Bar



-Coupling




-Sand Screen
                                                                  Driving Point
                                                                                                                        Supporting Cable
Falling Weight
 40 to 50 Ibs.
                                    FIGURE 5. - Well-point driving methods.

-------
or 2 inches in diameter.  The well is driven with the aid of a maul,  or a special drive
weight (see Figure 5).  For deeper wells,  the well points are  sometimes  driven into
water-bearing strata from the bottom of a bored or dug well (see Figure 6).  The yield of
driven wells is usually small to moderate.   If they can be driven an  appreciable depth
below the water table, they are no more likely than bored wells  to be seriously affected
by water-table fluctuations.  The most suitable locations for  driven wells are areas
containing alluvial deposits of high permeability. The presence of coarse gravels, cobbles,
or boulders interferes with sinking the well point and may damage the wire mesh jacket.
       Well-drive points come in a variety of designs and materials (see Figure 6).  In
general,  the efficiency and serviceability of each is related to  its basic design.  The
continuous-slot, wire-wound type is more resistant to corrosion and can usually be treated
with chemicals to  correct problems of encrustation.  It is more efficient because of its
greater open area, and is easier to develop because its design  permits easy access for
cleanup. Another type has a metal gauze wrapped around a perforated steel pipe base
and covered by a perforated jacket. If it contains dissimilar metals, electrolytic corrosion
is likely to shorten its life--especially in corrosive waters.
       Wherever maximum capacity is required, well-drive points  of good design are a
worthwhile investment. The manufacturers should be  consulted for their recommendation
of the metal alloy  best suited to each situation.
       Good drive-well points are available with different size openings, or slot sizes, for
use in sands of different gram sizes. If too large a slot size is used, it may never be
possible to develop the well properly, and the well  is  likely to  be a "sand pumper," or
gradually to fill in with sand, cutting off the flow of water from the aquifer. On the other
hand, if the slot size chosen is too small, it may be difficult to improve the well capacity
by development, and the yield may be too low. When the nature of aquifer sand is not
known, a medium-sized slot~0.015 inch or 0.020 inch-can be tried. If sand and sediments
continue to pass through the slots during development, a smaller  slot size should be used.
If, however, the Water clears very quickly  with  little  sand and sediment having  been
removed during development (less than one-third of  the volume  of the drive point) then
a larger slot size could have been selected, which would have resulted in more complete
development and greater well yield.
       When driving a well, prepare a pilot hole that extends to the maximum practical
depth. This can be done with a hand auger sightly larger  than the well point. After the
pilot hole has  been  prepared, lower  the  assembled point  and pipe into the  hole.
Depending on the resistance of the formation, driving is  accomplished in several ways.
The pipe is driven by directly striking the drive cap,  which is snugly threaded to the top
of the protruding section of the pipe. A maul, a sledge, or a "special driver" may be used
to hand-drive the pipe. The special driver may consist of a weight and sleeve arrangement
that slides over  the drive cap as the weight is lifted  and dropped in the driving process
(see Figure 5).
Jetted Wells
       A rapid and efficient method of sinking well points is jetting or washing-in.  This
method requires a source of water and a pressure pump. Water  is forced under pressure
downjthe riser pipe and comes out from a special washing point.  The well point and pipe
is lowered as material is loosened by the jetting action of the water.
48

-------
     Single Pipe (shallow well)
     Jet Pump
Sheet Plastic Separator


     Cobble Drain
Reinforced Concrete
,Cover Slab Sloped
Away From Pump
          FIGURE 6. -   Hand-bored well with driven-well point
                          . and "shallowwell"jet pump.
                                                                                    49

-------
       Often, the riser pipe of a jetted well is used as the suction pipe for the pump. In
such instances, surface water may be drawn into the well if the pipe develops holes. An
outside protective casing may be installed to the depth necessary to provide protection
against the possible entry of contaminated surface water.  The space  between the two
casings should then be filled with cement grout.  It is best to install the protective casing
in an auger hole and to drive the drive point inside it.
Drilled Wells
       Construction of a drilled well (see Figure 7) is ordinarily accomplished by one of
two techniques: percussion or rotary hydraulic drilling. Selection of the method depends
primarily on the site's geology and the availability of equipment.
       Percussion (Cable-Tool) Method.  Drilling by the cable-tool or percussion method
is done by raising and dropping a heavy drill bit and stem. The impact of the bit crushes
and dislodges pieces of the formation.  The reciprocating motion of the drill tools mixes
the drill cuttings with water into a slurry at the bottom of the hole.  This is periodically
brought to the surface with a bailer, a 10- to 20-foot-long pipe equipped with a valve at
the lower end.   Caving is prevented as drilling progresses by driving or sinking a casing
sightly larger in diameter than the bit.  When wells are drilled in hard rock, casing  is
usually necessary only when drilling through layers of unconsolidated material. A casing
may sometimes be necessary in hard rock formations to prevent caving of softer material.
       When good drilling practices are followed, water-bearing beds are readily detected
in cable-tool holes, because  the slurry does not  tend  to seal off the  water-bearing
formation.  A  rise or fall in the water  level in  the hole  during drilling, or increased
recovery water  during bailing, indicates that the well has entered a  permeable bed.
Crevices or  soft streaks in hard formations are often  water bearing.  Sand, gravel,
limestone, and sandstone are generally permeable and yield the most water.
       Hydraulic Rotary Drilling Method.  The hydraulic  rotary drilling method may be
used in most  formations.  The essential parts of the drilling assembly include a derrick and
hoist, a revolving table through which the drill pipe passes, a series of drill-pipe sections,
a cutting bit at the lower  end of the drill pipe, a pump for circulation of  drilling fluid, and
a power source to drive the drill.
       In the drilling operation, the bit breaks up the material as it rotates and advances.
The drilling fluid (called mud) pumped down the drill pipe picks up the drill cuttings and
carries them  up the space between the rotating pipe and the wall of the hole. The mixture
of mud and cuttings is discharged to a settling pit where the cuttings drop to the bottom
and mud is recirculated to the drill pipe.
       When the hole is completed, the drill pipe is withdrawn and the casing placed. The
drilling mud is usually left in place and pumped out after the casing and screen are
positioned. The space between the hole wall and the casing is generally filled with cement
grout in non-water-bearing sections, but may be enlarged and filled with gravel at the level
of water-bearing strata.
       When little is known about the geology of the area,  the search for water-bearing
formations must be  careful and deliberate—locating and  testing all possible formations.
Water-bearing formations may be difficult to recognize by the rotary method or may be
plugged by the pressure of the mud.
50

-------
Ground Surface Sloped
to Drain Away from Well
                              Plug

                        Air Vent
Discharge
              FIGURE 7. - Drilled well with submersible pump.
                                                                           51

-------
      Air Rotary Drilling Method. The air rotary method is similar to the rotary hydraulic
method in that the same type of drilling machine and tools may be used.  The principal
difference is that air is used rather than mud or water.  In place of the conventional mud
pump used to circulate the fluids, air compressors are employed.
      The air rotary method is well  adapted to rapid penetration  of consolidated
formations, and is especially popular in regions where limestone is the principal source of
water.  It is not generally suited to unconsolidated formations where careful sampling of
rock materials is required for well-screen installation.  Small quantities  of water can be
detected readily during drilling, and the yield estimated. Larger sources of water may slow
progress.
      The air rotary method requires that air be supplied at pressures from  100 to 250
pounds per square inch.  To remove the cuttings, upward air velocities of at  least 3,000
feet per minute are necessary. Penetration rates of 20 to 30 feet per hour in very hard
rock are common with air rotary methods. Conventional mud drilling is  sometimes used
to drill through soft formations that overlie bedrock.  Casing may have to be installed
through those formations before continuing with the air rotary method.
      Down-the-Hole Air Hammer.  The down-hole pneumatic hammer combines the
hammering effect of cable-tool drilling and the circular movement of rotary drilling. The
tool bit is equipped with tungsten-carbide inserts at the cutting surfaces. Tungsten-carbide
is very resistant to abrasion.
Water Well Casing and Pipe
      Several kinds of steel pipe are suitable for casing drilled wells.  The following are
the most commonly used:

             Standard Pipe
             Line Pipe
             Drive Pipe
             Reamed and Drifted (R&D) Pipe
             Water Well Casing

      For these there are different sizes, wall thicknesses, types of threaded connections
available and methods of manufacture. The important thing for the owner to check is that
they meet generally accepted specifications for quality of the steel and thickness of the
wall.   Both  are  important because  they  determine  resistance to  corrosion, and
consequently the useful life of the well.  Strength of the casing may also  be important in
determining whether certain well construction procedures may be successfully carried out.
This is  particularly unportant hi cable-tool drilling where hard driving the casing is
sometimes necessary.
      The most commonly  accepted  specifications for water well casing  are those
prepared by the following:

             American Society for Testing and Materials (ASTM)
             American Petroleum Institute (API)
             American Iron and Steel Institute (AISI)
             Federal Government
52

-------
       Each source lists several specifications that might be used, but those most likely to
be called for are ASTM A-120 and A-53, API 5-L, AISI Standard for R&D pipe, and
Federal  specification WW-P-406B.   States may require certain  well  designs  and/or
materials, so the reader is advised to check with the appropriate agencies to determine the
requirements.
       Table 6 lists "standard weight" wall thicknesses for standard pipe and line pipe
through the sizes ordinarily used hi well construction. Thinner pipe should not be used.
If conditions hi the area are known to be highly corrosive, the "extra strong" and heavier
weights should be used.
Setting Screens  or Slotted Casings
       Screens or slotted casings are installed hi wells to permit sand-free water to flow
into the well and to prevent unstable formations from caving in.  The size of the slot for
the screen or  perforated pipe should be based on a sieve analysis of carefully selected
samples  of the water-bearing formation.  The analysis is usually made by the screen
manufacturer. If the slot size is too large, the well may pump sand. If the slots are too
small,  they may become plugged with fine material and reduce its yield.  With a drilled
well, the screens are normally placed after the casing has  been installed. But hi a driven
well, the screen is a part of the drive assembly and is sunk to its final position as the well
is driven.

           TABLE 6. - Steel pipe and casing, standard and standard line pipe.
Nominal
size
finches')
1-1/4
1-1/2
2-
3
4
5
6
8
8
10-
Id'
10
12
12
Diameters
Outside
1,660
1.900
2375
3.500
4,500
5.563
6.625
8.625
8.625
10.750
10,750
10.750
12,750
12.750
Inside
J380
1.610
2,067
3.068
4,026
5.047
&06S
8.071
7.981.
10.192
10.136
10.020
12.090
12.000
Wall
thickness
finches')
.140
.145
.154
.216
237
.258
.280
.277
.322
.279
.307
.365
330
.375
Approximate weight fib. /ft.)
Plain ends
227
2.72
3,65
7.58
10.79
14.62
18.97
24.70
28.55
31.20
3424
40.48
43,77
49.56
Threaded
coupled
230
2.75
3.75
7.70
11.00
15.00
19.45
25.55
29.35
32.75
35.75
41.85
45,45
51.10
       Consider the relationship between the open area of the screen and the velocity of
water through the  openings if maximum  hydraulic efficiency is desired.  Keep loss of
energy through friction to a minimum by holding velocities to 0.1 foot per second or less.
Since the slot size  is  determined by the grain-size distribution in the aquifer sand, the
required open area must be obtained by varying the diameter—or, if aquifer thickness
permits—the  length of the screen.  Manufacturers of well screens provide tables of
capacities  and other information to aid  hi  selecting the  most economical screen
                                                                                53

-------
dimensions.  Note that a screen is seldom required in wells tapping bedrock or tightly
cemented sediments such as sandstone or limestone.
       Methods for installing screens in drilled wells include (1) the pullback method, (2)
the open-hole method, and (3) the baildown method.  The pullback method of installation
is one in which the casing is drawn back to expose a well screen placed inside the casing
at the bottom of the well. In the open-hole installation, the screen attached to the casing
is inserted in the un-cased bottom part of the hole when the aquifer portion of the hole
remains  open.  When the  baildown method is employed, the screen is placed at the
bottom of the cased hole and advanced  into the water-bearing formation by bailing the
sand out from below the screen.
       The "pullback" method is suited to bored or drilled wells, as long as the casing can
be moved, while the "open-hole" method is used in most instances with rotary drilling.
The "baildown" method may be used in wells drilled by any method where water-bearing
formations consist of sand.  It is not well adapted  to gravel formations.
       A fourth method, used primarily in rotary drilled holes, is the wash-down method.
This procedure involves the circulation of water through a self-closing bottom, upward
around the screen and through the space between the wash-pipe and the permanent casing
to the surface. This is accomplished with the help of a mud pump. As material is washed
by jet action from below it, the well screen settles  to its desired position.
       If the screen is placed after positioning the  casing, it must be firmly sealed to the
casing. This is done by spreading out a packer attached to the top of the screen. When
the pullback method of installation is employed, a closed bail bottom usually provides the
bottom closure. When the pullback method is used, a self-closing bottom serves this
purpose.  But when the baildown method is used, a special plug is placed in the bottom.
A small bag of dry cement  may be dumped into the bottom of the screen to seal it.
Development of Wells
       Before a well is operational, it is necessary  to remove all of the silt and fine sand
next to the well screen by one of several processes known as "development". Development
unplugs the formation and produces a natural filter of coarser and more uniform particles
of high permeability surrounding the well screen. After the development is completed, a
well-graded, stabilized layer of coarse material will entirely surround the well screen and
facilitate the flow of water into the well.
       The simplest method of well development is that of surging.  In this process, the
silt  and sand grains are agitated by a series of rapid reversals in the direction of flow of
water and are drawn toward the screen through larger pore openings.  A well may be
surged by moving a plunger up and down in it. This  action moves the water alternately
into and  out of the formation.  When water containing fine granular material flows into
the well,  the particles settle to  the bottom of the screen. They then can be removed by
pumping or bailing.
       One  of  the most   effective  methods  of development is  the  high-velocity
hydraulic-jetting method. Water under pressure is  ejected through the slot openings and
violently  agitates aquifer material. Sand  grains finer than the slot size move through the
screen and either settle to the bottom  of the well (from which they are removed by
bailing) or are washed out at the top. Conventional centrifugal, piston pumps, or the mud
pump of  the rotary hydraulic drill can easily accomplish this.  Pressures of at least 100 psi
should be used, with pressure greater than 150 psi preferred.   This method has the
54

-------
additional advantage of permitting development of those portions of the screen most in
need. For screens having continuous horizontal slot design, high-velocity jetting is most
beneficial. It has also proven effective in washing out drilling mud and crevice cuttings in
hard-rock wells.  But it is less useful in slotted or perforated pipe.
      Other methods of development include "interrupted pumping" and, explosives—used
only in consolidated material  and  then  only  by experts.   To  insure  proper well
development, match the method of development to the aquifer and the type of well.
Testing Well for Yield and Drawdown
      To select the most suitable pumping equipment, a pumping test should be made
after the well has been developed to determine its yield and drawdown.
The pumping test for yield and drawdown should include the following:

             A determination of the volume of water pumped per minute or hour.
             The depth to the pumping level as determined over a period of tune at one
             or more constant rates  of pumping.
             The recovery of the water level after pumping is stopped.
             The  length  of time the well  is pumped at each rate  during  the test
             procedure.

      When the completed well is tested for yield and drawdown, it is essential that it be
done accurately by using approved measuring devices and accepted methods. Additional
information regarding the testing of wells for yield and drawdown may be obtained from
the U.S. Geological Survey (USGS), the state or local  health department,  and  the
manufacturers of well screens and pumping equipment.
      Water-table wells are more affected than artesian wells by seasonal fluctuations in
ground water levels.  When testing a water-table well for yield and drawdown, it is best,
but not always possible, to test it near the end of the dry season. When this cannot be
done, it is important to estimate the additional seasonal decline in water level from other
wells tapping the same formations.  This additional decline should then be  added to the
drawdown determined by the pumping test in order to arrive at the maximum pumping
water level. Seasonal declines of several feet in water-table wells are not unusual, and can
seriously reduce the capacity of such wells in the dry season.
      Individual wells should be test  pumped at a constant pumping rate that is not less
than that planned for the final pump installation.  The well should be pumped at this rate
for not less than 4 hours, and the maximum drawdown recorded. Measurements of the
water levels after pumping can then be made.  Failure to recover completely to  the
original static water level within 24 hours is sufficient reason to question the dependability
of the aquifer.
Well Failure
      Over a period of time, wells may fail to produce for any of these causes:

      1.     Failure or wear of the pump.
      2.     Declining water levels.
      3.     Plugged or corroded screens.
      4.    Accumulation of sand or sediments in the well.
                                                                              55

-------
                 "Pumped
                  Water"
                  Pipe
Drive Water"
Pipe
                                                            Access
                                                            Plug
                  FIGURE 8. - Well seal for jet puny installation.

Proper analysis of the cause requires measuring the water level before, during, and after
pumping. To facilitate measuring the water level, provide for the entrance of a tape or
an electrical measuring device into the well in the space between the well casing and the
pump column (Figures 7 and 8).
      Use an "air line"  with  a water-depth indicating gauge  (available from  pump
suppliers). On some larger wells, the air line and gauge are left so that periodic readings
can be taken and a record kept of well and pump performance. While not as accurate as
the tape or electrode method, this installation is popular for use in a well that is being
pumped, because it is unaffected by water that may be falling from above.
      Unless the well is the pitless adapter or pitless unit type, gain access for water-level
measurements through a threaded hole in the sanitary well seal (Figures 8 and 9). This
is possible for submersible and jet pump installations,  as well as for some others. If it is
not possible to gain access through the top of the well, do so by means of a pipe welded
to the side of the casing.
      If the well is completed as a pitless adapter installation,  it is usually possible to
slide the measuring device past the adapter assembly inside the casing and on to the water
56

-------
                                            Pipe Plug
                         Drop Pipe from
                         Submersible
                         Pump
Submersible
Pump Cable
             FIGURE 9. - Well seed for submersible puny installation.
below.  If it is a pitless unit, particularly the "spool" type, it will probably not be possible
to reach the water level.  In the latter case, the well can only be tested by removing the
spool and pump and reinstalling that pump, or another one, without the spool.
       Any work performed within the well-including insertion of a measuring line-is
likely to contaminate the water with coliform bacteria and other organisms. Before
returning the well to service, it should be disinfected.  Tightly plug or cover all access
holes following the work.
                                                                                  57

-------
SANITARY CONSTRUCTION OF  WELLS
       The penetration of a water-bearing formation by a well provides a direct route for
possible contamination of the drinking water source.  Although there are different types
of wells and well construction, basic sanitary guidelines must be followed (state well codes
may be more specific than the following):

       1.     Fill the open space outside the casing with  a watertight  cement grout or
             puddled clay from a point just below the frost line, or  deepest level of
             excavation near the well (see "Pitless Units and Adapters," Page 128), to as
             deep as is necessary to prevent entry of surface water.  See Appendix D for
             grouting recommendations.
       2.     For  artesian aquifers,  seal the casing into the overlying impermeable
             formations to retain the artesian pressure.
       3.     When  a water-bearing  formation  containing  poor-quality water  is
             penetrated,  seal off the formation to prevent the infiltration of water into
             the well and aquifer.
       4.     Install a sanitary well seal with an approved vent at the top  of the well
             casing to prevent the entrance of contaminated water or other objectionable
             material.

       For large-diameter wells, such as dug wells, it is difficult to provide a sanitary well
seal.  In such cases, install a reinforced concrete slab, overlapping the casing and sealed
to it with a flexible sealant or rubber gasket.  The space outside the casing should first be
filled with a suitable grouting or sealing material.
Well Covers and Seals
       Every well should be fitted with an overlapping, tight-fitting cover at the top of the
casing or pipe sleeve to prevent contaminated water or other material from entering the
well.
       The sanitary well  seal in a well exposed  to  possible  flooding should be either
watertight or elevated at  least 2 feet above the highest known flood level.  When it is
expected that a well seal may be flooded, it should be watertight and equipped with a vent
line whose opening to the air is at least 2 feet above the highest known flood level.
       The seal in a well not exposed to possible flooding should be either watertight (with
an approved vent line) or  self-draining with an overlapping and downward flange. If the
seal is of the self-draining (non-watertight) type, all openings in the cover should be either
watertight or flanged upward and provided with overlapping, downward- flanged covers.
       Some pump and power units have closed bases that effectively seal the upper end
of the well casing.  When the unit is the open  type, or when it is located  at the side
(including some jet and suction-pump type installations), it is especially important that a
sanitary well seal be used.   There  are several acceptable designs  consisting of  an
expandable neoprene gasket compressed between two steel plates (see Figures 8 and  9).
They are easily installed and  removed  for well servicing.   Pump  and well  suppliers
normally stock sanitary well seals.
       If the pump is not installed immediately after well  drilling and placement of the
casing, the top of the casing should be closed with a metal cap screwed or tack-welded
into place,  or covered with a sanitary well seal.
58

-------
       A well slab alone is not an effective sanitary defense, since it can be undermined
by burrowing animals and insects, cracked from settlement or frost heave, or broken by
vehicles and vibrating machinery. The cement grout formation seal is far more effective.
Note, however, that some situations call for a concrete slab or floor around the well casing
to facilitate cleaning and improve appearance. When such a floor is necessary, it should
be placed only after the formation seal and the pitless installation have been inspected.
       WelLcovers and pump platforms should be elevated above  the adjacent finished
ground level.   Construct pump  room floors of reinforced,  watertight  concrete, that is
carefully leveled or sloped away from the well so that surface and waste water will not
stand near the well. The minimum thickness of such a slab or floor should be 4 inches.
Concrete  slabs or floors should be poured separately from the cement-formation seal.
When there is the threat of freezing, insulate them from the well casing with a plastic or
mastic coating or sleeve to prevent bonding of the concrete to either.
       All water wells should be readily accessible at the top for inspection, servicing, and
testing. This requires that any structure over the well be easy to remove, providing full,
unobstructed access for well-servicing equipment.  The so-called "buried seal," with the
well cover buried under several feet  of earth, is unacceptable because (1) it  discourages
periodic inspection and preventive maintenance, (2) it makes severe  contamination during
pump  servicing and well repair more likely, (3) well servicing is  more costly, and (4)
excavation to  expose the top of the well increases the risk of  damage to the well, the
cover,  the vent and the electrical connections.
Disinfection of Wells
       All newly constructed wells should be disinfected to neutralize any contamination
from  equipment,  material,  or surface  drainage  introduced  during  construction.
Disinfection should be done promptly after construction or repair. State requirements
may apply for disinfection of wells and need to be considered.
       An effective and economical method of disinfecting wells and well equipment is the
use  of a  calcium  hypochlorite solution containing approximately  70 percent available
chlorine.  This chemical can be purchased in granular  or tablet form at hardware stores,
swimming pool equipment supply outlets, or chemical supply houses. When disinfecting
wells, add calcium hypochlorite in sufficient amounts to provide a dosage of approximately
100 mg/L of available chlorine in the well water. This concentration is roughly equivalent
to a mixture of 2 ounces of dry chemical per 100 gallons  of water to be disinfected.
       Practical disinfection requires the use of a stock solution.  The stock solution may
be prepared by mixing 2 ounces of high-test hypochlorite with 2 quarts of water.  The
solution should be prepared in a thoroughly clean utensil, avoiding metal containers if
possible  because  strong chlorine solutions  will corrode  them.  Crockery, glass,  or
rubber-lined containers are recommended.  First  add a small  amount of water to the
granular calcium hypochlorite and mix it to a smooth, watery lump-free paste. Then mix
it with the remaining quantity of water.  This stock solution should be mixed thoroughly
for 10 to  15 minutes before allowing the inert ingredients to settle.  The  clearer liquid
which  contains the chlorine should be used and the sediment discarded.  Each 2 quarts
of stock solution provides a concentration of approximately 100 mg/L when added to 100
gallons of water.
                                                                                59

-------
       When only small quantities of disinfectant are required and a scale is unavailable,
measure dry  chemicals with a spoon. A heaping  tablespoonful  of granular calcium
hypochlorite weighs approximately 1/2 ounce.
       When calcium hypochlorite is unavailable, other sources of available chlorine, such
as sodium hypochlorite (12 to 15 percent of volume) can be used. Dilute an approved
sodium hypochloride solution, available commercially with 5.25 available chlorine, with one
part of water to produce a stock solution.  Use two quarts of this solution for disinfecting
100 gallons of water.
       Unless properly stored, stock solutions of chlorine in any form will deteriorate
rapidly.  Store in dark glass or plastic bottles with airtight caps.  Keep bottles of the
solution in a cool place and away from direct sunlight.  If proper storage facilities are
unavailable, always prepare fresh solution  immediately before use.  Because of its
convenience and consistency of concentration and strength, commercial bleach is preferred
as a stock solution for disinfecting individual water supplies.
       Table 7 shows quantities of disinfectants required for treating wells of different
diameters and water depths.  For sizes or depths not shown, the next larger figure should
be used.

       Dug Wells. The disinfection procedure for dug wells is as follows:

       1.     After completing the casing or lining, follow the procedure outlined below
             before placing the cover platform over the well.
             a.     Remove all equipment and materials, including
                    tools, forms, platforms,  etc., that will not be a
                    permanent part of the completed structure.
             b.     Using a stiff broom or brush, wash the ulterior
                    wall of the  casing  or  lining with a strong
                    solution (100 mg/L of chlorine)  to insure
                    thorough cleaning.
       2.     Place the cover over the  well  and pour the  required amount of chlorine
             solution as described  above into the well through  the manhole or pipe
             sleeve opening just before  inserting  the  pump cylinder  and  drop-pipe
             assembly.  Distribute the chlorine solution over as much surface area as
             possible to get the best distribution of the chemical in the water. Running
             the solution into the well through the water hose or pipeline while the line
             is being raised and lowered will insure better distribution.
       3.     Wash the exterior surface of the pump cylinder and drop pipe with the
             chlorine solution as the assembly is being lowered into the well.
       4.     After the pump is positioned, pump water from the well until a strong odor
             of chlorine is noted.
       5.     Allow the chlorine solution  to remain in the well at least 24 hours.
       6.     After 24 hours or more have elapsed, flush the well to remove all traces of
             chlorine.
60

-------
                     TABLET. - Quantities'of calcium hypochlorite, 70percent (rows A) and liquid calcium
                                  hypochlorite, 5.25percent (rows B)  requiredfor water well disinfection.
  Depth of
  water in
  well (ft.)
                                                    Well diameter (in.)
                                         10
                                             12
                                                16
                                         20
                         24
                                                                                  28
                32
36
                                                                                                      42
48
             Hf
      IT
      1C
      ti-
      le-
                       IT
                                         60"
                                         4G
                                                               30$,
                                                               ,JUJ
   10
             43'
      IT
                        1C
             JT
             1C
               IT
               IE
                                 4C-
                Sf
                2C
                •4- 02*
                                        u&.
                       ,...8(3....
                        mm.
                m
   15
 IT
 JtC
                  1C
      I?
      is
       IT
       1C
                                                     5t
                                                        12 px^
1C
4C
40
   20
IT
1C
                  10
      IT
      1C
       IT
       1C
iC
   30
      JW
      1C
      fcT
      1C
                                                                     Soa.
   40
             It
      IT
      1C
w
 1C
"W
 25.
   60
it
.&.
                                        8W
   80
                       4'}.'
                  1C
                                 2Q..
                                            fQ
  100
            1C
      •2C
      3C
                                                              m
                     254Q
  150
3T
2C
                        8T
                              •2Q
Quantities are indicated as: T = tablespoons; oz. = ounces (by weight); C = cups; Ib. = pounds; Q = quarts; G = gallons.
NOTE: Figures corresponding to rows A are amounts of solid calcium hypochlorite required; those corresponding to rows B are amounts of liquid household
bleach. For cases lying in green-shaded area, add 5 gallons of chlorinated water, as final step, to force solution into formation. For those in blue-shaded area,
add 10 gallons of chlorinated water. (See "Disinfection of Wells," pp. 50 ff.)

-------
      Drilled, Driven, and Bored Wells.  The procedure for disinfection of drilled, driven
and bored wells are as follows:

      1.     When testing the well for yield, operate the test pump until the well water
             is as clear and as free from turbidity as possible.
      2.     After removing the testing equipment, slowly pour the required amount of
             chlorine solution into the well just before installing the permanent pumping
             equipment.  Achieve best distribution of the solution with the well water by
             following Item 2 guidelines above, under "Dug Wells."
      3.     Add 5 or 10 gallons of clean, chlorinated water (see Table 7) to the well to
             force the solution out into the formation.  One-half teaspoon of calcium
             hypochlorite or one-half cup of liquid sodium hypochlorite in 5 gallons of
             water is enough for this.
      4.     Wash the exterior surface of the pump cylinder and drop pipe as they are
             lowered into the well.
      5.     After positioning the pump, operate the pump until detecting a distinct odor
             of chlorine in  the water.
      6.     Allow the chlorine solution to remain in the well for at least 24 hours.
      7.     After disinfection, pump the well until the odor of chlorine is gone.

      In the case of deep wells having a high water level, it may be necessary to  resort
to special methods of introducing the disinfecting agent into the well to insure the best
distribution of chlorine  throughout the well.
      Place the granulated calcium hypochlorite in a short section of pipe capped at both
ends. Drill a few small holes through each cap or into the sides of the pipe. Fit one of
the caps with an eye for attaching a suitable cable.  The disinfecting agent is distributed
when the pipe section is lowered or raised throughout the depth of the water.
      Flowing Artesian Wells.  The water from flowing artesian wells is generally free
from contamination as soon as the well is completed or after it has been allowed to flow
a short time.  It is not generally necessary to disinfect flowing wells.  If, however, analyses
show persistent contamination, the well should be thoroughly disinfected according to the
following guidelines.
      Use a device such as the pipe described in the preceding section (or any other
appropriate device) to distribute a  generous supply of disinfectant at or near the bottom
of the well. Pass the cable supporting the device through a stuffing box at the top  of the
well.  After placing the disinfectant, throttle down the flow enough to get an adequate
concentration. When water showing an adequate disinfectant concentration appears at the
surface, close the valve  completely and keep it closed for at least 24 hours.
Bacteriological Tests Following Disinfection
      If bacteriological tests after disinfection indicates that the water is not safe for use,
repeat disinfection until tests show that water samples from that portion of the system are
satisfactory. Samples collected immediately after disinfection may not be representative
of the normal water quality.  Hence, if bacteriological samples are collected immediately
after disinfection, it is necessary to  re-sample several days later to check on the delivered
water under normal conditions of operation and use. The water from the system should
not be used for domestic purposes (such as drinking, cooking, brushing teeth, etc.) until
62

-------
tie reports of the tests indicate that the water is safe for such uses.  If after repeated
disinfection the water is unsatisfactory, treatment of the supply is necessary to provide
water which consistently meets USEPA drinking water  requirements.  Under  these
conditions, the supply should not be used for domestic purposes until adequate treatment
has been provided.

ABANDONMENT  OF WELLS
      Unsealed, abandoned wells constitute a potential hazard to public health and safety.
Certain problems with sealing an abandoned well may be due to the well's construction
and the geological and hydrological conditions of the area.  To seal a well properly,  these
main factors should be considered: elimination of any physical hazard, prevention of any
contamination of  the ground water,  conservation and  maintenance  of the yield and
hydrostatic pressure of the aquifer, and the  prevention of  any possible contact between
acceptable and unacceptable waters.
      The objective of properly sealing any  abandoned well is to restore the controlling
geological conditions existing before the well was drilled or constructed.
      When a well is to be permanently abandoned, the lower portion of it is best
protected by filling it with concrete, cement grout, neat cement,  or clays having sealing
properties similar to those of cement.  When filling dug or bored wells, remove as much
of the lining as possible, so that surface water will not  reach the water-bearing layers
through a porous lining or one containing cracks or fissures. When any question arises,
follow the regulations and recommendations of the state or local health department.
      Abandoned wells should never be used for the disposal of sewage or other wastes.

RECONSTRUCTION  OF  EXISTING  DUG  WELLS
      Existing wells used for domestic water supplies and subject to contamination should
be reconstructed to insure safe water.  When reconstruction is not practicable, the water
supply should be treated or  a new well constructed.
      Dug wells with stone or brick  casings can often be rebuilt by enclosing existing
casings with concrete or by installing a buried concrete slab.
Safety
      Care must be exercised when entering wells because, until properly ventilated, they
may contain dangerous gases or lack oxygen.
      Hydrogen sulfide gas is found in certain ground waters and, being heavier than air,
it tends to accumulate in excavations. It is explosive, and nearly as poisonous as cyanide.
Also, a person's sense of smell tires quickly in its presence, making one unaware of the
danger.  Concentrations may become dangerous quickly without further warning.
      Methane gas is also found in some ground water or in underground formations.
It is the product of the decomposition of organic matter.   It is not toxic, but is highly
explosive.
      Gasoline, carbide lanterns or candles may not be reliable indicators  of safe well
atmospheres because many of these devices  will continue to burn at oxygen levels well
below those safe for humans. Also,  any open flame carries the additional risk of an
explosion from accumulated combustible gases.      r
      The flame safety lamp used by miners, construction companies, and utilities service
departments, is a much better device for determining safe atmospheres.  It is  readily
                                                                               63

-------
obtainable from mine safety equipment suppliers. The lamp should be lowered on a rope
to the well bottom to test the atmosphere.  Even after the well has passed this test, the
first person to enter the well should carry a safety rope tied around his waist, with  two
persons standing by, above ground, to rescue him at the first sign of dizziness or other
distress.  Whenever possible, a self-contained air  pack should be used by the person
entering the well.
      Improvements should be planned so that the reconstructed well will conform as
nearly as possible to the principles set forth in this manual.  If there is any doubt as to
what should be done, advice should be obtained from the state or local health department.

SPECIAL CONSIDERATIONS  IN  CONSTRUCTING ARTESIAN  WELLS
      To conserve water and improve the productivity of an artesian well, it is essential
that the casing be sealed into the confining stratum. Otherwise, a loss of water may occur
by leakage into lower pressure permeable strata at higher elevations. A flowing artesian
well should be designed so that the movement of water from the aquifer can be controlled.
Equipping such a well with a valve or shutoff device conserves waters. When the recharge
area and aquifer are large and the number of wells which penetrate the aquifer are small,
the flowing artesian well produces a fairly steady flow of water throughout the year.

SPRINGS  AND  INFILTRATION  GALLERIES
      Springs and infiltration galleries on headwaters of a fresh water stream can be used
to provide a safe, dependable source of drinking water. However, researchers have found
disease-causing bacteria and protozoa in many of these water sources which would classify
them as surface water sources, which are discussed in Part III of this manual.
 64

-------
                Part HI
                          Surface   Water
                          Source
 INTRODUCTION
      The  selection and use  of  surface  water as  a water-supply source requires
 consideration of additional factors not usually related to ground water sources. For small
 public water supply systems, ground water or connection to a large central water system
 is generally preferred, and should be used whenever possible.  When small streams, open
 ponds, lakes, or open reservoirs must be used, the danger of biological contamination and
 of the spread of diseases such as typhoid fever and dysentery increases. As a rule, surface
 water should only be used when ground water sources are not available  or are inadequate.
      Because surface water is open to physical  and biological contamination,  it is
 necessary to regard  it as unsafe for household use unless reliable treatment, including
 filtration and disinfection, is provided.
      EPA has set treatment requirements to control microbiological contaminants in
 public water systems using surface water sources (and ground water sources under the
 direct influence  of surface water).  These requirements, as part of the Surface Water
 Treatment Rule (SWTR), include the following:

           Treatment must remove or inactivate at least 99.9 percent of Giardia lamblia
           cysts and 99.99 percent of viruses.
           All systems must disinfect, and may also be required to filter if certain source
           water quality criteria and site-specific conditions are not met.
           The regulations set standards for determining if treatment, including turbidity
           removal and disinfection, is adequate for filtered systems.
           All systems must be operated by qualified, licensed operators as determined
           by the individual states.
           Systems  using  surface water  must file  reports  with  the  state to  show
           compliance with treatment and monitoring requirements.

      Detailed guidance on surface water treatment requirements is provided in EPA's,
 Guidance Manual for Compliance With the Filtration  and Disinfection Requirements for
Public Water Systems Using Surface Water Sources.
                                                                              65

-------
     Treatment of surface water to insure a consistent,  safe supply requires regular
attention to operation and maintenance of the treatment system by the owner.  Public
water systems must sample and monitor at a greater number of sampling sites.  This
includes regular monitoring of filter turbidities, disinfection residuals, and coliforms.
     When ground water sources are limited, consideration should be given to reserving
its use to household purposes such as drinking and cooking.  Surface water can then be
used for stock and poultry  watering,  gardening, firefighting, and similar  purposes.
Treatment  of surface water for livestock is not generally considered essential.  There is,
however, a  trend toward providing drinking water for stock and poultry which is free from
bacterial contamination and certain chemicals.

SOURCES OF SURFACE WATER
     Sources of surface water include rainwater catchments, ponds or lakes, and surface
streams. The water in them comes from direct precipitation over the drainage area.
     Because of the complexities  of the hydrological,  geological, and meteorological
factors affecting surface water sources, it is recommended that engineering  advice be
obtained when developing a natural catchment area of more than a few acres.
     To estimate the yield  of the source,  it  is necessary to consider  the following
information for the drainage area:

           Total annual precipitation
           Seasonal differences of precipitation
           Annual or monthly variations of rainfall from normal levels
           Annual and monthly evaporation and transpiration rates
           Soil moisture requirements and infiltration rates
           Runoff gauge information
           Size of drainage area
           All available local experience records

     Much of the required  data, particularly  that concerning  precipitation,  can "be
obtained from U.S. Weather Bureau publications. Essential data such as soil moisture and
evaporation requirements may be obtained from local soil conservation and agricultural
agencies or from field tests conducted by. hydrologists.
Controlled Catchments
     Historically,  in many parts of the world, rainwater catchment has  been used for
water  supply since ancient times.   In areas where ground water is inaccessible  or too
highly mineralized for domestic use, controlled catchments and cisterns may be necessary.
A properly located and constructed controlled catchment and cistern, with a good filtration
unit and adequate disinfection facilities, will provide a safe drinking water.
     A  controlled catchment is a defined surface area from which rainfall runoff is
collected.   It may be  a roof (roof catchment) or a  paved ground surface (surface
catchment). The collected water is stored in a constructed covered tank called a cistern
or reservoir. Surface catchments should be fenced off to prevent unauthorized entrance
by people or animals.  There should be no possibility of undesired surface drainage mixing
with the controlled runoff. An intercepting drainage ditch around the upper edge of the
 66

-------
                Runoff =0.75 Total Preciptation
                              2.OOO            4.OOO              6.0OO
                     Horizontal Area of Catchment, (In Square Feet)

                   FIGURE 10. - Yield of impervious catchment area.
catchment  area  and a raised curb around the surface will prevent the entry of any
undesired surface drainage.
     For these controlled catchments, simple guidelines to determine water yield from
rainfall totals can be established.  When the controlled catchment area has a smooth
surface (or is paved) and the runoff collected in a cistern, water loss due to evaporation,
replacement of soil moisture  deficit, and infiltration is small.  As a general rule, losses
from smooth concrete or asphalt-covered ground catchments are less than 10 percent,
shingled roofs or tar and gravel surfaces lose less than 15 percent, and sheet metal roofs
lose almost no water.
     A conservative design can be based on the assumption that the amount of water that
can be recovered for use is three-fourths of the total annual rainfall. (See Figure 10)
     Location.  A controlled catchment may be located on a hillside near the edge of a
natural bench.   The catchment area can be  placed on a moderate  slope above the
receiving cistern.
                                                                               67

-------
     The location of the cistern should.be governed by both convenience and quality
protection.  A cistern should be as close to the point of ultimate use as practical.  A
cistern should not be placed  closer than 50 feet from any part of a sewage-disposal
installation, and should be on higher ground.
     Cisterns collecting water from roof surfaces should be located adjacent to  the
building, but not in basements subject to flooding.  They may be placed below the surface
of the ground for protection against  freezing in cold  climates and  to keep water
temperatures  low in warm climates, but should be situated  on the highest ground
practicable, with the surrounding area graded to provide good drainage.
     Size.  The size of cistern needed will depend on the size of the family and the length
of time between periods of heavy rainfall. Daily water requirements can be estimated
from Table 3, following page 22. The size of the  catchment or roof surface needed will
depend on the amount of rainfall and the character of the surface.  It is a good idea to
allow a safety margin for years with lower-than-normal rainfall.  Designing  for three-
fourths of the mean annual rainfall will usually result in a  large enough catchment area.
     The following  example illustrates the procedure for determining  the size of  the
cistern and required catchment area.

     Step  1 - Calculate Volume of Cistern
           Assume that the minimum drinking and cooking needs of a family of four are
           100 gallons per day1 (4 persons x 25 gallons per day = 100 gallons) and that
           the effective period2 between rainy periods is 150 days.  The minimum volume
           of the cistern required will be 15,000 gallons (100 x 150).  This volume could
           be held by a cistern 10 feet deep and 15 feet square.

     Step 2 - Calculate Required Catchment Area
           If  the mean annual rainfall is 50 inches, then  the total design rainfall is 33
           inches (50 x 2/3).   In Figure 10, the catchment area required to produce
           36,500 gallons (365 days x 100 gallons  per day), the total year's requirement,
           is 2,400 square feet.

     Construction. Cisterns should be water tight with smooth interior surfaces. Manhole
or other covers should be sealed tight and vents screened to prevent the entrance of light,
dust, surface water, insects, and animals.
     Manhole openings should have a watertight curb with edges projecting a minimum
of 4 inches above the level of the surrounding surface. The edges of the manhole cover
should overlap the curb and project downward a minimum of 2 inches. The covers should
be locked to minimise, the danger of contamination and accidents.
     Twenty-five gallons per person per day, assuming that other uses are supplied by water of poorer quality.

     Effective period is the number of days between periods of rainfall during which there is negligible
     precipitation.
68

-------
      Provision can be made for diverting initial runoff, or "first flush", from paved
 surfaces or roof tops before allowing water to enter the cistern.  Dirt, leaves,  or bird
 droppings that accumulate on the roof or catchment area during dry periods should be
 washed down by the first flush of rain and collected in the roof washer.  The drain at the
 lower end of the cistern is for cleaning, which may periodically be needed, because some
 contaminants may reach the cistern if the diversion of the first flush is not complete. (See
 Figure 11.)
      Inlet, outlet, and waste pipes should be well-screened.  Cistern drains and waste or
 sewer lines should not be connected.
      Underground cisterns can be built  of brick or stone, although reinforced concrete
 is preferred.  If used, brick or stone must be low in permeability and laid with full
 Portland cement mortar joints.   Brick should  be wet before laying.   High-quality
 workmanship is required, and the use of unskilled labor for laying brick or stone is not
 advised.  Two 1/2-inch plaster coats of 1:3 portland cement mortar on the interior surface
 will help to  provide waterproofing.   A  hard, non-absorbing surface can be  made  by
 troweling the final coat before it is fully hardened.
      Figure 11 shows  a suggested design for a cistern of reinforced concrete.  A dense
 concrete should be used to obtain water-tightness and should be vibrated frequently during
 construction to eliminate "honeycomb."  All masonry cisterns should be allowed  to wet-
 cure properly before being used.
      The procedures outlined in Part IV of this manual should be followed in disinfecting
 the cistern with chlorine solutions. Initial and regular water samples should be taken to
 determine the bacteriological quality of the water supply. Chlorination  may be required
 on a continuing  basis if  the  bacteriological results  show that the  water  quality is
unsatisfactory.  Roofs,  gutters and other surfaces  that collect and transport water for a
 cistern should be cleaned regularly. Roof gutters should be maintained at an even slope
to prevent pooling of water. Roofs collecting rainwater should not be painted, nor should
asbestos cement sheeting be placed so that it ever comes into contact with water. Tiles,
slate, and galvanized iron are suitable for collection surfaces.
Ponds or Lakes
      A pond or lake should be considered as a source of water supply only if ground
water sources and controlled catchment  systems are inadequate or unacceptable.  The
development of a pond as a supply source depends on several factors:

          A watershed that allows only  water of the highest quality to enter the pond.
          Use of the best-quality water  from the pond.
          Filtering the water to remove turbidity and reduce bacteria.
          Disinfection of filtered water.
          Proper storage of the  treated water.
          Proper maintenance of the entire water system. Local authorities may be able
          to furnish advice on pond development.
                                                                               69

-------
2" Win.
                                                                                                 Sand Filter (May be used
                                                                                               in place of roof washer)
                                             flGURE 11. - Cistern.

-------
      The value of using a pond or lake as a water supply is its ability to store water
 during wet periods for use during dry periods. A pond should be capable of storing at
 least one year's supply of water. It must be big enough to meet water supply demand
 during periods of low rainfall, with an additional allowance for seepage and evaporation
 losses. The drainage area (watershed) should be large enough to fill the pond or lake
 during wet seasons of the year.
      Careful consideration of the location of the watershed and pond site reduces the
 possibility of chance contamination.
      The watershed  should be:
           Clean, preferably grassed
           Free from barns, septic tanks, privies, and soil-absorption fields
           Effectively protected against erosion and drainage from livestock areas
           Fenced to keep out livestock

      The pond should be:
           Not less than 8 feet deep at its deepest point.
           Designed  to have the maximum possible water storage area that is over 3 feet
           in depth
           Large enough to store at least one year's supply
           Fenced to keep out livestock
           Kept free  of weeds, algae, and floating debris

      In many instances, pond development requires the construction of an embankment
with an overflow or spillway.  Help in designing a storage pond may be available from
Federal, State, or local health agencies and in publications  from the State  or county
agricultural,  geological,  or soil conservation departments.  For specific conditions,
professional engineering or geological advice may be needed as pond development entails
potential liability that may be considerable.
     Intake.  A pond intake must be properly located so that it draws water of the highest
possible quality. When the intake is placed too close to the pond bottom, it may draw
cloudy water or water containing decayed organic material.  When placed too near the
pond surface, the intake system may draw floating debris, algae, and aquatic plants. The
depth at which it operates best will vary, depending upon the season of the year  and the
layout of  the pond.   The most desirable water is usually obtained when the intake is
located between 12 and 18 niches below the water surface.  An intake located at the
deepest point in the pond makes maximum use of stored water.
     Pond intakes should be of the type illustrated in Figure 12, known as "floating
intakes."  The intake consists of a flexible pipe attached to a rigid pipe that passes through
the pond embankment.
     Gate valves should be installed on the main line below the dam and on any branch
line to make  it possible to control of the rate of discharge.
     Treatment. The pond water-treatment facility consists of four basic parts.  These are
coagulation and settling for large particle removal, filtration for smaller particle removal,
a clear water storage tank, and continuous disinfection (see Figure 13).  A more detailed
explanation of these treatment techniques is  found in Part IV, under "Surface Water
Treatment."
                                                                               71

-------
A. PLAN (Overall)    "--^  .,•...„..;,*;>



           Maximum Flood Water Level
 B. SECTION A-A
                                        FIGURE 12. - Pond.

-------
                                       Pressure Tank	
                                       Automatic Chlorinator-
                                       Automatic Jet Pump-
                                       Pumphouse •
       Hand
       Valve
Reinforced Concrete Top rReinforced Concrete Top
  Hand Valve
                                      Reinforced
                                      V Concrete Cover
                                                         Purified Water to House
                                                         (Below Frost Line)
           Washed River Sand
           Screened Through 1/8" Sieve
            FjLTER
To Water coagulation &
Source  sedimentation Chamber
                               Concentric Piping with Outer
                               Pipe under System Pressure
           FIGURE 13. - Schematic diagram of pond •water-treatment system.

     Protection From Freezing.  Protection from freezing must be provided unless the
plant is not operated or drained during freezing weather. In general, the filter and pump
room should be located in a building that can be heated. With the right topography, the
need for heating can be eliminated by placing the pump room and filter underground on
a hillside.  Gravity drainage from  the pump room must be possible to prevent flooding.
No matter what arrangement is used, the filter and pump room must be easy to get to for
maintenance and operation.
     Tastes and Odors. Surface water frequently develops musty or unpleasant tastes and
odors. These are generally caused by the presence of microscopic plants called algae.
There are many kinds of algae. Some occur in long thread-like filaments that are visible
as large green masses of scum; others may be separately free floating and entirely invisible
to the unaided eye.  Some varieties grow in the  early spring, others in summer, and still
others in the fall.  Tastes and odors  generally result from the decay of dead algae.  This
decay occurs naturally as plants pass through their life cycle.  For discussion of algae
control, see Nuisance Organisms in Part IV.
Streams
     In some cases, streams receiving runoff from large, uncontrolled watersheds may be
the only source of water supply.  The physical and bacteriological quality of surface water
varies and may impose very high burdens on the treatment facilities.
     Stream intakes should be located upstream of sewer outlets or other sources of
contamination. The water should be pumped when the amount of silt in the stream is low.
Low water levels in the stream usually means that the temperature of the water is higher
than normal and the water is of poor chemical quality. However, maximum silt loads
occur during maximum runoff. High-water stages, shortly after storms and the silt has
                                                                                 73

-------
settled,  are usually the best times for diverting or pumping water to storage.  These
conditions vary and should be determined for each individual stream.  The following
chapter discusses techniques for treatment of surface waters for potable use.

DEVELOPMENT  OF SPRINGS
     There are two basic requirements for developing a spring as a source of domestic
water: (1) selection of a spring with enough capacity to provide the required quantity and
quality of water throughout the year, (2) protection of the sanitary quality of the spring.
Each spring must be developed according to its geological conditions and  sources. State
standards for spring development may apply and should be considered.
     The features of a spring encasement are as follows:

     1.   An open-bottom,  watertight basin intercepting the source which extends to
          bedrock or a system of collection pipes and a storage tank.
     2.   A cover keeps the entrance of surface drainage and debris from getting into
          the storage tank.
     3.   Provision for cleaning out and emptying of the tank contents.
     4.   Provision for overflow.
     5.   A connection to the distribution system or backup supply (see Figure 14).

     Tanks are usually made of reinforced concrete, large enough to capture or intercept
as much of the spring as possible.  When a spring is located on a hillside, the downhill
wall and sides should go down to bedrock, or to a depth that will insure an adequate water
level in the tank at all times. "Cutoff walls" of concrete or impermeable clay extending out
from the sides of the tank may be  used to control the water table around the tank.
Construct the bottom part of the tank's uphill wall of stone, brick, or other material that
will allow water to move freely into the tank from the aquifer. Backfill of graded gravel
and sand will help keep that material in place.
     A tank cover should be cast in place to insure a good fit. Forms should be designed
to allow for shrinkage of concrete and expansion of lumber.  The cover should be extend
down over the top edge of the tank at least 2 inches.  The  tank cover should be heavy
enough (so that it cannot be dislodged by children)  and should be equipped for locking.
     A drain pipe with an exterior valve should be installed close to the wall of the tank
near the bottom. The pipe should extend horizontally, clearing the normal ground level
at the point of discharge by at least 6 inches.  The  discharge end of the pipe should be
screened to keep out rodents and insects.
     The overflow pipe is usually placed slightly below the maximum water-level line and
screened. A layer of rock (a "drain apron") should be laid around the point of overflow
discharge to prevent erosion.
     The spring's outlet should  be located about 6 inches above the drain outlet and
screened. Care should be taken in fitting pipes through the tank's walls to insure a good
bond with the concrete and freedom from "honeycomb" around the pipes.
74

-------
                                    ;ci	d.c—ivi'v
                                    l-.S^r^ <^~ * V* ^-^-Parfora
-'^"feanout Drain"   ,.:, rV-* ;1.1' :''. '^;-/.'V/- /• v'-: ->-'  '-",- -'\.'< '* ;, I1 ^'','' -''/• ,"s' •'
 '-.----*-... -"T-  "•."  •--": ••-'        '''* '~N '"   '"  % '  -*•'  '"  v
                     MGUKE 14. - Spring Protection.
                                                                                    75

-------
Sanitary Protection of Springs
     Springs usually become contaminated when barnyards, pasture lands, sewers, septic
tanks, cesspools, or other sources of pollution are located on higher land next to them.
La limestone formations, however, contaminated material frequently enters through sink
holes or other large openings and may be  carried along with ground water for  long
distances.  Similarly, if contamination enters the water in glacial drift, this water may
remain contaminated for long periods of time and over long distances.
     Following these measures  will help to insure a spring water of consistent  high
quality:

     1.    Remove surface drainage from the site.  Dig a surface drainage ditch uphill
           from the source, to intercept surface-water runoff and carry it away from the
           source. Use care and judgement when locating the ditch and the outlet points
           where water is discharged from the system. Criteria used should include the
           local topography, the subsurface geology, land  ownership, and land use.
     2.    Build a fence to keep livestock out. Take into account the criteria mentioned
           in Item 1.  The fence should keep livestock  away from the surface-water
           drainage system at all points uphill from the source.
     3.    Provide access to the tank for maintenance, but prevent removal of the cover
           by installing locks.
     4.    Monitor  the  quality  of  the spring  water  regularly by checking  for
           contamination. A noticeable increase in turbidity or flow after a rainstorm is
           a good indication that surface runoff is reaching  the spring and possibly
           contaminating it.

Disinfection of Springs
     Disinfect the spring encasement using a procedure similar to the  one used for dug
wells.  If there is  not enough water pressure to raise  the  water to the  top  of the
encasement, it may be possible to shut off the flow, thus keeping the disinfectant in the
encasement for 24 hours.  If the flow cannot  be  shut off entirely, the disinfectant should
be added continuously for as long as is practical.

INFILTRATION GALLERIES
     Many recreational or other developments in the mountains have water supplies that
are near the headwaters of  mountain streams, where  the watersheds  are forested and
uninhabited. Even under these conditions, researchers have found disease-causing bacteria
and protozoa in the water. Although the water may appear safe to drink, some form of
treatment must be used to remove these contaminants. States may have specific treatment
requirements such as the use of an infiltration gallery. These requirements need to be
considered.
     Debris and turbidity at the water intake after spring thaws and  periods of heavy
rainfall can cause problems in operating and mainlining these supplies. If possible, this
material should be removed before it reaches the intake. Experience has shown that
debris and  turbidity can be removed successfully, especially when small volumes of water
are involved, by installing an infiltration gallery at or near the intake.
76

-------
     Where the soil next to a stream will allow water to pass through it, the water can.
be intercepted by an infiltration gallery located a reasonable distance from the high-water
level and a safe distance below the ground surface. Install infiltration galleries so that they
will intercept the flow from the stream after it flows through the soil formations.
     A typical infiltration gallery installation generally involves the construction of an
underdrained, sand-filter trench parallel to the stream bed and about 10 feet away from
the high-water mark.  The trench should have a minimum width of 30 inches and a depth
of about 10 feet. At the bottom of the trench, perforated or open-joint tile should be laid
in a bed of gravel about 12 inches thick with about 4 inches of graded gravel over the top
to support the sand.  Then, the gravel should be covered with clean, coarse sand to a
minimum depth of 24 inches, and the rest of the trench backfilled with fairly nonporous
material.  The collection tile ends in a watertight, concrete basin where it is chlorinated
and diverted or pumped to the distribution system.
     Where soil formations adjoining a stream will not allow water to flow through them,
the debris and turbidity that are occasionally encountered in a mountain stream should be
removed using a modified infiltration gallery/slow-sand filter combination in the  stream
bed. Typical installation involves building a dam across the stream to form a natural pool,
or digging a pool behind the dam. The filter should be installed in the pool behind the
dam by laying perforated pipe in a bed of graded gravel that is covered by at least 24
inches  of clean, coarse sand.  About 24 niches of space should be allowed between the
surface of the sand and the dam. spillway. The collection lines should end hi a watertight,
concrete basin, next to the, upstream side of the dam, where  the water is  diverted for
chlorination.
                                                                               77

-------

-------
                Part IV
                          Water   Treatment
NEED AND PURPOSE
      Raw waters from natural sources  may require treatment prior to  use.  Water
supplies may contain pathogenic (disease-producing) organisms, suspended particles, or
dissolved chemical substances.  Except in limestone areas, ground water is less likely to
have  pathogenic organisms than surface water, but may contain unpleasant tastes and
odors or mineral impurities.  Some of these objectionable characteristics may be tolerated
temporarily, but the quality of the water should be raised to the highest possible level by
treatment.  Even when nearly-ideal water can be found elsewhere, it is still a good idea
to provide for treatment of the less-desirable source in order to have a backup supply of
safe water.
    ^  The quality of water constantly  changes.  Natural processes which affect water
quality  are the dissolving of minerals,  sedimentation, filtration, aeration, sunlight, and
biochemical decomposition.  Natural processes may either contaminate or  purify water,
but the natural processes of purification are neither consistent nor reliable.
      Bacteria are numerous in waters at or near the earth's surface. Their numbers may
be reduced by seeping into the ground, lack of oxygen, or from being underground for
long periods under unfavorable conditions for bacterial growth. When water flows through
underground fissures or channels,  however, it  may remain contaminated  over  long
distances and time periods.                         ^
      The belief that flowing water purifies itself after traveling various distances has led
to feelings  of  false security about its safety.  Under certain conditions, the number of
microorganisms in flowing water may actually rise instead of fall.
      Water treatment incorporates, changes, or adds  to  certain natural purification
processes. Water treatment may condition or reduce to acceptable levels chemicals and
impurities which may be present in the water.
      Treatment may take place at a treatment facility with treated water pumped to the
distribution system or to storage, or may consist of household  point-of-use (POU) or
point-of-entry  (POE) treatment units.
                                                                               79

-------
WATER TREATMENT
     Some of the natural treatment processes and manmade changes to those processes
are discussed in the following section.
Coagulation-Flocculation
     Coagulation is the process  of forming particles in a liquid by the addition of a
chemical such as alum to  the water.  Iron salts, such  as ferric chloride, and organic
coagulant polymers can also be used.  The chemical is mixed with the cloudy, turbid water
and then gently stirred by mechanical or hydraulic means to allow flocculation to take
place.  During this flocculation stage, the suspended particles will combine physically and
form a mass of particles. The larger particles will be able to settle out by gravity. This
settling may be done in a separate (sedimentation) tank or in the same tank after the
mixing period.  Adjustment of pH  may be needed after  this process, because some
coagulant chemicals lower pH.   Some colors can also  be removed from water using
coagulation.  Competent engineering advice, however, should be obtained on specific
coagulation problems.
Sedimentation
     Sedimentation is a process  of heavy suspended material in water settling out and
collecting on the bottom. Sedimentation usually follows  coagulation-flocculation.
     This settling action can be done in a still pond or properly constructed tank or basin.
It takes a few hours  to get a significant reduction in suspended matter. The inlet of the
tank should be set up so that the incoming water is spread evenly across the entire width
of the tank as the water flows to the outlet at the opposite end.  Baffles are usually
constructed to even out the flow of water through the tank.  Cleaning  and repairing the
installation can be made easier if the tank is designed with two separate sections, so that
one can be used alone while the other is cleaned and/or repaired.
     When a water source contains a large  amount of turbidity,  much of it can be
removed by sedimentation.  A protected pond with gentle grassy slopes  often results in
reasonably clear raw water.
Filtration
     Filtration is the process of removing suspended matter from water as it  passes
through beds of porous material.  The degree of removal depends on the type and size of
the filter media, the thickness  of the media bed, and the size and quantity  of the
suspended matter.  Since bacterias can travel long distances through filters, filters alone
should not be relied upon to produce bacteriologically safe water.  Filtered water must
also be disinfected.  Types  of filtration that may be used include:
     Slow Sand Filters. Water passes slowly through beds of fine sand  at rates averaging
0.05 gallon per minute per square foot of filter area.  Properly constructed slow sand
filters  do not require much maintenance and can be easily adapted to individual water
systems (See Figure 15). The frequency of cleaning will vary depending on the turbidity
of the water and other factors. It is necessary to clean  the filter regularly by removing
about  one  inch of sand from the surface of the filter and either disposing of it or saving
it for washing and reuse. This removal will make it necessary to add new or washed sand.
     Sand for slow sand filters should consist of hard, durable grains free from clay, loam,
dirt, and organic matter. It should have a "sieve analysis" that falls  within the range of
values shown in Table 8, adapted from the AWWA manual Water Treatment Plant Design.
 80

-------
                                                          EflluintFlow
                                                        Control Structure   v»nt
 8>nd Filter Bid

 Support Qnvtl

Perforated Drain Plot
                      Typical unhoused slow sand filter Installation
                      Stow S«nd Filter
 EHIutntFlow
Control Struclura
                       Typical housed slow sand filter Installation


                     FIGURE 15. - Slow sand filtration diagram.


                 From "Technologiew for Upgrading Existing or Designing New
                            Drinking Water Facilities", EPA (1990)
                                                                                           81

-------
       TABLE 8. - Recommended mechanical analysis of slow sand filter media
Material passing sieve
(percent)
99
90-97
75-90
60-80
U.S. sieve
no.
4
12
16
20
Material passing sieve
(percent)
17-35
4-10
1
U.S. sieve
no.
30
40
60
100
     Sands with an "effective size" of 0.20 to 0.40 millimeters work well. The effective
size is determined from the dimensions of that sieve or mesh which allows 10 percent of
the sample to pass through and retains the remaining 90 percent.  This means 10 percent
of the grains ar smaller and 90 percent larger.  The "uniformity coefficient" should be
between 2.0 and 3.0.  The coefficient is the ratio of the diameter of a sand grain that is
too large to pass through a sieve that allows 60 percent of the material (by weight) to pass
through, to the diameter of a grain that is too large to pass through a sieve that allows 10
percent of the material (by weight) to pass through.
     For best  results, the rate of filtration for a slow sand filter should be 60 to 180
gallons per day per square foot of filter bed surface.  The amount of water that flows
through the filter bed can be adjusted by a valve placed on the outflow line.  Between 27
and 36 inches  of sand, with an additional 6 to 12 inches that can  be removed during
cleaning, is usually enough. The depth removed is replaced with clean sand,  Six to eight
inches  of gravel will  support the sand and keep it out of the underdrain system.  A
114-inch  plastic pipe  drilled with 3/4-inch holes  facing  down makes a convenient
underdrain system. One to two feet of freeboard on the top of the filter is usually enough.
     Slow sand filtration has proven to provide a large reduction in bacteria, cloudiness
and  organic levels,  and thereby reduce  the need for  disinfection and presence  of
disinfection by-products in the finished water.  Slow sand filters remove Giardia cysts,
which makes application especially valuable to small water supply systems that use surface
waters.  However, high levels of cloudiness require slower filtration rates  and therefore,
more frequent  filter cleaning.  For that reason, slow sand filters should not be  used on
waters that routinely exceed 10 NTU.
     Rapid Sand Filters. In a rapid sand filter, water is applied at a rate at or  above 2
gallons  per minute  per square foot of filter area,  with  an allowance for  frequent
backwashing.
     Rapid or "high rate" filters usually follow coagulation and  sedimentation  for very
cloudy source water.  Rapid sand filtration is not usually good for very  small water
supplies because of the necessary controls and additional attention it requires. However,
package plants have the necessary filtration processes and automatic controls  to meet
small system needs.
     Rapid sand filters may use a top layer  of quartz sand or anthracite coal.  Ordinary
bank sand cannot be  used without screening, washing  to  remove  organic matter and
grading to produce the correct size.  In addition, it should be free  from carbonate
hardness.
82

-------
      If the sand is too fine, it will not allow water to pass through it freely, and it will
reqyure frequent cleaning.  If it is too coarse, it will not effectively remove suspended
matter (turbidity).
      The sand usually used for rapid sand filters has an effective size of 0.4 to 0.5 mm
and a uniformity coefficient between 1.3 and 1.75.  Anthracite coal, crushed to  slightly
larger sizes, is also used instead of sand or to supplement it as a surface layer of lower
specific gravity.
      Rapid sand filters do not remove bacteria and viruses as well as slow sand filters
unless chemical pretreatment (coagulation,  flocculation, sedimentation)  is optimized.
Further treatment, such as disinfection, is required for filters treating surface water.
      Pressure Sand Filters.  In pressure sand filters, water is filtered at 2  gallons per
minute or higher per square foot of filter area. Chemical pretreatment is required and
equipment must be provided to allow frequent backwashing of the filter.
      Diatomaceous Earth Filters.   In diatomaceous earth  filters, suspended solids are
removed by passing the water through a diatomaceous filt*er supported by a rigid base
support at about the same rates as pressure sand filters.
      Diatomaceous earth filters, which require regular attention, are of two types-vacuum
and pressure.  The filter has several elements, usually small tubes  or hollow plates, which
are coated with a layer of diatomaceous earth. The  water passes through this earth layer,
into the tube  or plate, and out. A mixture of earth is fed  during the filtering run, and
when the filter is clogged up enough with suspended matter to slow down the filtering
rate, the coating is removed with a backwash. When properly operated and maintained,
these filters are effective at removing bacteria and cysts.
      Cartridge Filters.  Cartridge filters with porous  ceramic or glass fiber filter elements,
with pore sizes as small as 0.2 /tm, may be  able to produce drinkable water from raw
surface water  supplies containing low levels of cloudiness, algae,  protozoa and bacteria.
Cartridge filters must be used in combination with disinfection.  The advantage of  a small
system is (with the exception of chlorination) that no other chemicals are required. The
process is one of physical removal of small particles by straining as water passes through
the porous filter. Other than occasional cleaning or filter replacement, they are simple
to operate and do not  require any special skills or knowledge.
      Proper disinfection of water before drinking  or cooking is  necessary to assure  its
safety (see "Disinfection" section which follows).

DISINFECTION
      Water systems using surface water or water under the direct influence of surface
water must disinfect their water supply.  In addition, a filtering system is also required,
unless otherwise approved by  the state  agency  responsible for water  supply since
disinfection alone may not protect against some contaminants (such as Giardia lamblia).
These water treatment guidelines are part of the surface water treatment requirements
enacted  by EPA  to protect  drinking water  from   bacteriological  contamination.
Disinfection and filtration are both necessary to destroy all harmful bacteria and other
organisms. To assure that  all harmful organisms are removed, the  water to which the
disinfectant is  added must be low in turbidity.  Water with high  levels of turbidity may
shield microorganisms  from the action of disinfectants.  After disinfection, water must be
stored in suitable tanks or other facilities designed to prevent recontamination.
                                                                                83

-------
     Emergency disinfection procedures are included in Appendix E.
Chemical Disinfection
     The most important features of a chemical disinfectant are: powerful, stable, soluble,
non-toxic to man or animals, economic, dependable, lacking residual effects, easy and safe
to use and measure, and readily available.
     Disinfection must be carefully controlled. Enough disinfectant should be added to
water to destroy microorganisms.  Too much disinfectant,  however, can combine with
other compound in water  to form harmful chemical disinfection by-products.
     Chlorine compounds have some of the best properties of a chemical disinfectant.
As a result, chlorine is the most commonly used water disinfectant.
Disinfectant Terminology: Glossary
     Chlorine concentration. This is expressed in milligrams  per liter (mg/L).  One mg/L
is equivalent to 1 milligram  of chlorine in 1 liter of water. For water, the units of parts
per million (ppm)  and mg/L are basically the same.
     Chlorine feed or dosage.  The actual amount in mg/L fed into the water system by
the feeder or automatic dosing device is the chlorine feed or dosage.
     Chlorine demand. The chlorine fed into the water that combines with impurities,
and, therefore, is  no longer available for  disinfectant action, is commonly called  the
chlorine demand of the water. Examples of impurities that cause higher chlorine demand
are organic materials and certain "reducing" materials such as hydrogen sulfide, ferrous
iron, nitrites, etc.
     Free and combined chlorine. Chlorine can also combine with ammonia nitrogen, if
any is present in the water, to form chlorine compounds that have some ability to disinfect.
These  chlorine  compounds are called combined chlorine  residual.   However, if  no
ammonia is present in the water, the chlorine that remains hi the water once the chlorine
demand has been satisfied is called  "free chlorine residual".
     Chlorine contact time.  The chlorine contact time is the period of tune between the
addition of chlorine and the use of the water. Chlorine needs a certain amount of contact
time in order for it to act as a disinfectant.
     Contact time  ("T")  and chlorine residual  concentration  ("C")  affect  how well
disinfection will work.  For example, surface waters  that are  not filtered  (i.e., only
disinfected) require long contact tunes to assure inactivation of Giardia cysts: after  120
minutes of contact, the chlorine residual in a tank should be at least one mg/L.  However,
the "C" and "T" needed for treating ground water and filtered surface water are different
than for  unfiltered surface water,  and depend on water temperature, pH and other
conditions.
Chlorine  Disinfection
     In general, the primary factors that determine the  disinfectant efficiency of chlorine
are as follows:
     Chlorine concentration. Higher concentrations of chlorine results in effective  and
faster disinfection.   However, there is  a point of limited return as higher and higher
dosages are used.  For that reason, chlorine concentrations should not be more than 5
mg/L in drinking water.
     Type of chlorine residual. Free chlorine is a much better disinfectant than combined
chlorine.
84

-------
      Temperature of the water in which contact is made. The higher the temperature, the
better tke disinfection.
      The pH of the water in which contact is made.  The lower the pH, the more effective
the disinfection.
      Contact time between the water and chlorine.  To ensure proper  disinfection, the
disinfectant must be in contact with the target microorganisms for a sufficient amount of
time. Contact  time (CT) values describe  the extent of disinfection as a product of the
disinfectant residual concentration, C, (in mg/L) and the contact time  T, (in minutes).
EPA's Guidance Manual for Compliance With the Filtration and Disinfection Requirements
for Public Water Systems Using Surface Water Sources provides CT values for achieving
various  levels of Giardia and virus  inactivation.   Sufficient  CT is a state  regulated
requirement  of the Surface Water Treatment Rule.
      Generally speaking, the longer the contact time, the better the disinfection.  As a
basic guideline, chlorine  residuals and time  can be changed  to  provide  acceptable
disinfection for water at 10°C and 7.0 pH, if the following CT values are provided:

           C x T > 120   for an Unfiltered Surface Water
           C x T >  20   for a Filtered Surface Water
           C x T >   6  for Groundwater

           Where C is the chlorine residual in mg/L, and
           T is the contact time in minutes. Either variable, residual  or time, can be
           manipulated to obtain the above  products.

   Note:   These CT recommendations are provided here  as  a. general guideline only.
           They may not be sufficient for your water.  The guidance manual referred to
           above should be consulted for the exact CT values required.

      Chlorine Compounds and Solutions.  Compounds of chlorine, such as  sodium or
calcium hypochlorite, have excellent disinfecting properties. In small water systems, these
chlorine compounds are usually added to the water after being dissolved in a solution
form, but may also be used in tablet, powder or pellet form.
      One of the most commonly used forms of chlorine is calcium hypochlorite.  It is
available in soluble powder and tablets. These compounds are "high-test" hypochlorite and
contain 65 to 75 percent available chlorine by weight.  Packed in cans  or drums, these
compounds are stable and will not break down if properly stored and handled.
      Prepared sodium hypochlorite solution is available commercially with a strength of
approximately 5 percent available chlorine by weight. Other sodium hypochlorite solutions
vary in  strength from 3 to 15 percent available chlorine by weight, and are reasonably
stable when stored in a cool, dark place. These solutions are diluted with drinkable water
to obtain the desired solution strength to be  fed into the system.
      When hypochlorite powders are used, fresh solutions should be prepared frequently
because chlorine solutions will get weaker over time.  The container or vessel used for
preparation,  storage,  and distribution of  the chlorine solution should be resistant to
corrosion and shield  the  solution from light.   (Light causes  a reaction that weakens
                                                                               85

-------
chlorine solutions.)  Good materials include glass, plastic, crockery, or rubber-lined metal
containers.
     Hypochlorite solutions can be used either at full strength or diluted to a strength
suited to the feeding equipment and the rate of water flow. In preparing these solutions,
one must take into account the chlorine content of the concentrated (stock) solution. For
example, if 5 gallons of 2 percent solution are to be prepared with a high-test calcium
hypochlorite powder or tablet containing 70 percent available chlorine, 1.2 pounds of high-
test hypochlorite would be needed.
     Pounds of compound required:

           % strength      gallons of solution
     =    of solution   X	needed      X    8.3 Ibs./gal of water
                      %  available chlorine in compound

           2 X 5 X 8.3
             70

     =    1.2 pounds

     Similarly, the following formula can be used to  determine the pounds of chlorine
required per  day to disinfect at a particular dose:

     Chlorine, Ibs/day =  (Dosage, mg/L)(8.3 Ibs/gal of water) (Flow or quantity, mgd1)

     For example, how many pounds of chlorine would be required to feed a dose of 2.0
mg/L to 50,000 gallons of water?

     Chlorine, Ibs/day = (2.0 mg/L)(8.3 lbs/gal)(.05 mgd)

     Chlorine, Ibs/day = 2

     Now, if we used  calcium hypochlorite that was 65 percent available chlorine, how
many pounds of this compound would be required to  satisfy the previous condition?
      Calcium hypochlorite, Ibs/day  =
Chlorine. Ibs/day
Percent Available
                                       2        2
      Calcium hypochlorite, Ibs/day  =  rrr, or  -—
      Calcium hypochlorite, Ibs/day  =   3 pounds
     mgd = million gallons per day

86

-------
      For a hypochlorite solution,  how many gallons of 2 percent sodium hypochlorite
 solution, would be required to feed a 2.0 mg/L dosage to our 50,000 gallons of water?

                   solution, (gal/day)   -
      Hypochlorite solution, (gal/day)   =

=   12
                                          16.6
      Determination of Chlorine Residual.  Residual chlorine can exist in water as a free
 or  combined chlorine residual.  When present as a combined chlorine residual, it  is
 combined with either organic material or ammonia. The sum of combined and free
 chlorine is called total chlorine residual.  Sufficient  chlorine is the  amount needed to
 produce a desired residual after a definite contact period whether the chlorine residual is
 combined, free, or total.
      The amount of remaining chlorine  (chlorine residual) in the water is  normally
 measured using a simple test called the DPD calorimetric test (short for the chemical
 name N,N-dimethyl-p-phenylene-diamine). The test can be done outside of a laboratory
 using special pills that are placed in a test tube.  The  free or total chlorine  residuals
 produce a violet color that can be compared with a color chart to determine the quantity
 of chlorine hi the water.  The kits come with all necessary test tubes, chemicals, color
 chart and instructions.   Firms  that specialize hi the  manufacture of water  testing
 equipment and materials can supply them.
      A  combination DPD and pH kit is  also available at a modesO price. State and
 county water supply agencies can provide names of water test kit suppliers.
      Wherever chlorination is needed for disinfection, testing for chlorine residual should
 be done at least daily, and a daily record of results kept.
      For  more information  on the DPD test and other water testing  procedures,
 descriptions  are included hi Standard Methods for the Examination  of Water and
 Wastewater.2
 Chlorination Equipment
     Hypochlorinators.  Hypochlorinators  pump or inject a chlorine solution into the
water. When they are properly maintained, hypochlorinators are a reliable way to apply
chlorine to disinfect water. However, protection against over-feeding or siphoning should
be included.
      Types of hypochlorinators include positive displacement feeders, aspirator feeders,
suction feeders, tablet hypochlorinators  and dry pellet chlorinators.
     Positive Displacement Feeders. A common type of positive displacement hypochlor-
inator is one that uses a piston or diaphragm pump to  inject the solution.  It is adjustable
during operation, and can be  designed  to give reliable and accurate feed rates.  When
           Obtainable from the American Waterworks Association, 6666 West Quincy Avenue, Denver,
           Colorado 80235, Phone:  (303) 794-7711.
                                                                                87

-------
electricity is available, the stopping and starting of the hypochlorinator can be timed with
the water supply pumping unit. This kind of hypochlorinator can be used with any water
system, but it is especially useful in systems where water pressure is low and changeable.
     Aspirator Feeders.  The aspirator feeder uses a vacuum created when water flows
either through a venturi tube or perpendicular to a nozzle, to draw chlorine solution from
a container into the chlorinator unit, where it is mixed with water.  The mixed solution is
then injected into the water system. In most cases, the water inlet line to the chlorinator
is  connected to the discharge side of the water pump, with the chlorine solution being
pumped back into the suction side of the same pump.  The chlorinator operates only when
the pump is operating.  Chlorine solution flow rate is controlled by a valve, but pressure
changes may cause changes in the feed rate.
     Suction Feeders.  One type of suction feeder consists of a single line that runs from
the chlorine solution container through the chlorinator unit, and connects to the suction
side of the water pump. The chlorine solution is pulled from the container by suction
created by the water pump.
     Another type of suction feeder works on the  siphon principle, with  the  chlorine
solution being added directly into the well.  This type also consists of a single line, but the
line ends in the well, below the water surface, instead of at the suction side of the water
pump. When the pump is running, the chlorinator is turned on, so that a valve is opened
and the chlorine solution flows into the well
     In each of these units, the chlorine solution flow rate is regulated by a control valve,
and the chlorinator runs only when the pump is running.  The pump circuit should be
connected to a liquid  level control so that the water supply pump shuts off when the
chlorine  solution is gone.
     Tablet Hypochlorinators. The tablet ("erosion type") hypochlorinating unit consists
of a special pot feeder containing calcium hypochlorite tablets.  Accurately controlled by
an inlet baffle or flowmeter, small jets of feed water flow through the lower portion of the
tablet bed. The tablets slowly dissolve, providing a continuous source of fresh hypochlorite
solution.  Since this unit produces fairly high dose rates, a by-pass may be needed so that
only part of the total flow is treated. This type of chlorinator is used when electricity is
not available, but it needs good maintenance for efficient operation.  It can also operate
where the water pressure is low.
     Drop Pellet Chlorinators. Drop-feed pellet chlorinators consist of a motorized feeder
that drops a controlled number of dry calcium hypochlorite pellets into well water over
a  period of time. The device can be timed to drop pellets more or less often, depending
on the volume of water being treated. This unit runs only when the well pump is running.
      Gaseous Feed Chlorinators.  In situations in which large quantities of water are
treated, chlorine gas in pressure cylinders may be used as the disinfectant. Its use in very
small water supply systems may be limited because of its higher cost and the greater safety
precautions necessary to guard against accidents.  Gaseous chlorine  is an extremely
hazardous substance.
     Solution Supply Monitor.  Sensing units can be placed in solution containers to sound
a warning alarm when the solution goes below a predetermined level. This equipment can
also be connected to the pump so that when the chlorine is about to run out, the pump
will automatically shut and activate a warning bell. On that signal, the operator will have
to refill the solution container and take necessary steps to ensure proper disinfection.
 88

-------
      Chlorine Contact Tanks. Enough time for the chlorine to properly disinfect water
for drinking can be provided using a chlorine contact tank.   Although mixing is not
required, special measures should be taken to ensure that, at maximum flow, 90 percent
of the water discharged from the contact tank has been in the tank for the required tune
period. More information on disinfectant dosages and required contact time can be found
in the previous section on "Chlorine Disinfection".
      It is important to note that contact time is not simply the required time multiplied
by the flow rate.  Short-circuiting may occur, in which some water flows straight through
the tank, while other water becomes trapped in stagnant zones, remaining in the tank for
a long time. This can be corrected by using a properly designed tank, possibly with baffles
to direct the water flow.
Chlorination Control
      Several factors have a direct bearing on the effectiveness of chlorine. Because of
these factors, it is not possible to suggest rigid standards that will work in all water supply
systems.  It is possible, however,  to offer  some general  guidelines  for water supply
operation and maintenance.
      Simple Chlorination.   Unless bacteriological or other tests indicate the  need to
maintain higher minimum concentrations of free residual chlorine, at  least 0.2 mg/L of
free residual chlorine should be in contact with treated ground water (at 10 °C) for at least
30 minutes before the water reaches the first user from the point of where the chlorine
is added. As noted above, surface water supplies, and different water temperatures, would
require different disinfectant concentrations and contact time.  It is a good idea to
maintain a detectable free chlorine residual at  the end of the distribution system when
using simple Chlorination.   Refer  to the  section on "Chlorine Disinfection"  for  more
information on establishing the right chlorine dosages.
      A method known  as supercUorination-dechlorination can be used to  solve the
problem of insufficient contact time in a- water system.  By this method, chlorine is added
to the water in increased amounts  (superchlorination) to  provide a minimum chlorine
residual of 3.0 mg/L for a minimum contact period of 5 minutes. Removal of the excess
chlorine (dechlorination) is then used to get rid of unpleasant chlorine taste.
      Records. Proper control of water quality also depends on keeping accurate operating
records of Chlorination.  Those records can indicate chlorination is being done properly,
and as a guide for improving operations. The record should show the amount of water
treated, amount of chlorine used, setting of the chlorination equipment, tune and location
of chlorine tests, and results of chlorine tests.  This information should be kept current
and posted near the chlorination equipment.

DISINFECTION WITH ULTRAVIOLET LIGHT
      Ultraviolet (UV) light produced from UV lamps has been shown to be an effective
disinfectant. In disinfecting water, the amount of UV radiation needed depends on factors
such as turbidity, color, and dissolved iron salts, which prevent ultraviolet energy from
entering the water. For that reason, UV light would not work for disinfecting turbid water
and is normally used only hi treating groundwater.
      Cylindrical UV units with standard plumbing fittings have been designed for use in
water lines.  They should be checked often for light intensity and cleaned of any material
that would block radiation from reaching the water. An advantage of disinfection with UV
                                                                               89

-------
light is that the equipment is readily available and easy to operate and maintain.  A
disadvantage of UV light is that it does not provide a residual disinfectant in the water (as
does chlorine). Thus, there is no protection against recontamination in UV-disinfected
water and another disinfectant may be needed (such as chlorine) to maintain a bacteria
controlling residual in the distribution system. Another disadvantage of UV is that it is
not effective against some microorganisms, such as Giardia lamblia cysts. Where Giardia
lamblia are a potential problem, such as with surface water sources, disinfection by UV
is not recommended.

DISINFECTION WITH OZONE
     Ozone is the strongest oxidizing agent available for water treatment.  It is a very
strong disinfectant, and can oxidize the following types of compounds:  taste and odor
compounds, certain organics,  iron and  manganese, and sulfides.  However,  like UV
disinfection, ozone does not provide a residual to protect against recontamination.
     Either air or oxygen may be used to generate ozone. A typical ozone system using
air as the feed source would consist of the following units: air filter, air compressor, air
cooling and drying system, the ozone generator where ozone is created from oxygen in the
air as it passes through a high voltage electric current, a contact  chamber where the ozone
mixes through the water, and a destruction device for  the off-gases from the contactor.
If oxygen from tanks is used, the air compressor and drying system are not needed.
     The contactor for a small water treatment plant is usually a tall chamber or tall
fiberglass columns.  Contactors are normally designed for a contact time of ten minutes.
     Ozone gas leaks in and around a generator and  contactor are very dangerous.
Ozone is a toxic  gas  and  requires  operator protection similar to that  for  gas  feed
chlorination systems.

MEMBRANE TECHNOLOGIES
     Reverse Osmosis (R.O.) and electrodialysis reversal (EDR) are two commonly used
membrane processes for the  physical separation  and  removal of  unwanted water
contaminants.  Membranes act as molecular filters to remove most dissolved minerals,
biological organisms and suspended matter from water.  Before  installing an R.O. or EDR
system, care must be taken so that the liquid waste streams can be disposed of properly
and that  state and local permits are obtained.
Reverse Osmosis
     Reverse osmosis  (R.O.) is a membrane process that is  sometimes  referred to as
hyperfiltration, the highest form of filtration possible.  It uses  a special, semi-permeable
membrane which, under pressure, permits pure water  to pass  through it while acting as
a barrier to dissolved salts and other impurities.
     A basic  R.O. system consists of a high pressure pump, control system to  regulate
flows and pressure, and the R.O. module. Normally, some form of pretreatment is used.
This can be anything from a simple filter to  the combined use of coagulation, sedimenta-
tion and filtration followed by pH adjustment  when  treating very dirty water.  Post-
treatment methods can include pH adjustment, aeration and chlorination for disinfection.
90

-------
Electrodialysis Reversal
     The  electrodialysis  reversal  (EDR)  process  is  based on another  membrane
technology, electrodialysis.  Using alternately placed positively and negatively charged
membranes allows the passage of ions.  Separate areas of ion-rich and ion-poor water are
created.  The membranes are arranged in stacks, and the desired salt or other contami-
nant reduction is achieved by passing  the water through the proper number of stacks.
With EDR, the DC current is reversed periodically, typically two  to four times per hour.
This causes ion movement to reverse direction, and flushes the scale-forming ions from
membrane  surfaces.   This lengthens  membrane life and reduces maintenance and
replacement costs.

AERATION
     Aeration is the process of bringing air into contact with a liquid such as water.
Many methods can be used for effective  aeration, including spraying water into the air,
allowing water to fall over a spillway in a turbulent stream,  or  letting water trickle in
multiple streams or droplets through a series of perforated plates or through a packed
tower. Although aeration may be performed in an open system, care should be taken to
prevent possible external contamination of the water.  Whenever possible, a totally
enclosed system should be used.
     Aeration may be used to oxidize iron or manganese and remove odors from water,
such as those caused by hydrogen sulfide and algae. Aeration also efficiently removes
radon gas and volatile organic compounds (VOC's)  from water.  It is also effective in
increasing the oxygen content of water that is too low in dissolved oxygen. The flat taste
of cistern water and distilled water may be improved by adding oxygen. Carbon dioxide
and other gases, that increase the  corrosiveness  of  water, can be largely removed by
aeration. However, aeration increases the level of oxygen, increasing corrosion, which may
partially offset the advantage of decreasing the carbon dioxide levels.
     Aeration partially oxidizes dissolved iron and  manganese,  changing iron into its
insoluble form. Sometimes a short period of storage permits the insoluble particles to
settle out; at other times, the particles of iron and manganese must be filtered out.
     A simple cascade device or a coke tray (wire-bottom  trays filled with activated
carbon) aerator can be added to  a water supply system.  In addition to aerating, the coke
tray will reduce tastes and odors.
     Insects such  as the  chironomus fly may lay eggs in the stagnant portion of the
aerator tray. Covering the aerator prevents flies from getting into  the aerator. Screening
will also provide protection from windblown debris.

OTHER TREATMENT
Iron and/or Manganese Removal
     Iron and/or manganese in water creates a problem common to many individual
water supply systems.  When both are  present beyond recommended levels,  special
attention should be paid to the problem.  The removal of iron and manganese depends
on  the type and quantity, and this helps determine  the best procedure and (possibly)
equipment  to use.
     Well  water is usually clear and colorless when it comes out of the faucet or tap.
When water containing colorless, dissolved iron is allowed to stand in a cooking container
                                                                               91

-------
or comes in contact with a sink or bathtub, the iron combines with oxygen from the air
to form reddish-brown particles (commonly called rust). Manganese forms brownish-black
particles.
     These impurities can give a metallic taste to water or to food. Deposits of iron and,
manganese produce rusty or brown stains on plumbing fixtures, fabrics, dishes,  and
utensils.  Soaps or detergents will not remove these stains, and bleaches and alkaline
builders (often sodium phosphate) can make it worse. After a long period, iron deposits
can build up in pressure tanks, water heaters, and pipelines, reducing the quantity and
pressure of the water supply.
     Iron and manganese can be removed through chlorination and filtration.   The
chlorine chemically oxidizes the iron or manganese (forming a particle), kills iron bacteria,
and kills any disease bacteria that may be present. The filter then removes the iron or
manganese particles.  Other techniques, such as aeration followed by  filtration, ion
exchange with greensand, or  treatment with potassium  permanganate followed by
filtration, will also remove these materials.
     Insoluble iron or manganese and iron bacteria will clog up the mineral bed and the
valving of a water softener.  It is best, therefore,  to remove iron and manganese before
the water reaches the softener.
     When a backwash filter medium is used, an adequate quantity of water at a high
enough pressure must be provided for removing the iron particles.
     Potassium permanganate can be used in place of chlorine. The dose, however, must
be carefully  controlled.   Too  little permanganate will not oxidize all  the iron  and
manganese, and too much will allow permanganate to enter the distribution system and
cause a pink color.
     Iron can also be oxidized, by simple aeration, to removable ferric hydroxide by
exposing water to air in sprays or by cascading (water falls) over steps or trays. The ferric
hydroxide is then filtered out.  The main advantage of this method is that it requires no
chemicals.
     If the water contains less than 1.0 mg/L iron and  less than 0.3 mg/L manganese,
using polyphosphates followed by chlorination can be effective and inexpensive. Below
these concentrations, the polyphosphates combine with the iron and manganese preventing
them  from  being  oxidized.    Any of the three  polyphosphates   (pyrophosphate,
tripolyphosphate, or metaphosphate) can be used.
     To determine the best polyphosphate to use and the right dosage, prepare a series
of samples at different concentrations.  Add chlorine,  and observe  the  samples  daily
against a white background. The right polyphosphate dose  is the lowest dose that does
not noticeably discolor the water samples for four days.
Iron Bacteria Removal
     Under certain conditions,  the removal of iron compounds from a water supply may
be more difficult due to the presence of iron bacteria. When dissolved iron and oxygen
are present in the water, these bacteria get energy from the oxidation of the iron. These
bacteria  collect within a  gelatinous  mass which coats underwater surfaces.  A slimy,
rust-colored mass on the inside surface of flush tanks or water closets is caused by iron
bacteria.
     Iron bacteria can reduce the flow within water pipes by increasing friction. They
may give an unpleasant  taste  and odor to the water, discolor  and  spot fabrics  and
92

-------
plumbing fixtures, and clog pumps. A slime also builds up on any surface that the water
containing these organisms touches. Iron bacteria may be concentrated in a specific area
and may periodically break loose and appear at the faucet in visible amounts of rust.
Lines may need to be regularly flushed through hydrants or other valves when such red,
rusty water is found.
     Iron-removal filters or water softeners can remove iron bacteria; however, they often
become clogged by the slime.  A disinfecting solution should be injected into the water to
control the growth of iron bacteria.  This  causes iron particles to form.  These particles
can then be removed with a suitable fine filter.
Water Softening
     Water softening  is  a  process for removing minerals (primarily calcium  and
magnesium) that cause hardness.  It can also remove small quantities of kon and
manganese.
     It should be noted that the two softening processes discussed in this section will also
remove radium. Where radium is removed, care must be taken to safely dispose  the
treatment wastes.
     Softening of hard water is desirable  if:

           Large amounts of soap are needed to produce a lather.
           Hard scale is formed on cooking utensils or laundry basins.
           Hard, chalk-like formations coat the interiors of piping or water tanks.
           Heat-transfer efficiency through the walls of the heating element or exchange
           unit of the water tank is reduced.

     The buildup of scale will reduce the amount of water and pressure a pipe can carry.
Excessive scale from hard water is also unpleasant to look at. Experience  shows that
hardness values much higher than 200 mg/L (12 grains per gallon) may cause some
household problems.
     Water may be softened by either the ion-exchange or the lime-soda ash process, but
both processes increase the sodium content of the water and may make it unfit for people
on a low-sodium diet.
     Ion Exchange. The ion-exchange process replaces calcium or magnesium ions with
sodium ions. The process takes place when hard water containing calcium or magnesium
compounds comes in contact with an exchange medium.  The materials used in  the
process of ion exchange are insoluble, granular materials that can perform ion exchange.
Ion-exchange material may be classed as follows: glauconite (or greensand); precipitated
synthetic, organic (carbonaceous), and synthetic resins, or gel zeolites. The last two are
the most commonly used for centralized treatment of drinking water.
     The type of ion-exchange material to use depends on the type of water treatment
needed.  For example, when a sodium zeolite is used to  soften water by  exchanging
sodium ions for calcium and magnesium ions in the hard water, there will eventually be
too few sodium zeolite ions to complete the exchange. The hardness of the water entering
the unit and the water leaving should be checked regularly. After a certain period of time
(determined by the exchange rate), the sodium zeolite must be recharged. The sodium
ions are restored to the zeolite by passing a salt (NaCl) or brine solution through the ion-
exchange media (bed).  The salt solution used must contain the same type of ions
                                                                              93

-------
(sodium) that were replaced by the calcium and magnesium. The salt solution reverses
the ion-exchange process, restoring the sodium zeolite to its original condition.
     The type of recharge material or solution that must be used depends upon the type
of exchange material in the system.
     The ion-exchange method of softening water is fairly simple and  can be used easily
by a small or individual water supply system.  Only part of the hard water needs to be
passed through the softening process because it can produce water of zero hardness which
could be more corrosive to the metals  in the piping and household plumbing.  The
processed water can then be mixed back in with hard water to produce a final water with
a hardness  of 50 to 80 mg/L (3 to 5 grains per gallon). Water with a turbidity of more
than 5 NTUs (a measure of the cloudiness of water) should first be properly treated for
removal of particles to increase the effectiveness and the efficiency of  the later softening
process.
     If the bed turns an  orange or rusty color, iron fouling is becoming a problem.
Increasing the  tune  of the recharge stage may  help.  A chemical  cleanser (sodium
bisulfite) can also be used to remove heavy iron coatings from the media. The cleaner can
be added to the regenerating material or mixed in solution form and poured into the
softener when the unit is out of service.   The softener should be rinsed before using it
again after this cleaning.
     Ion-exchange softeners are commercially available for individual water systems.
Thek capacities range from about 85,000 to 550,000 milligrams of hardness removed for
each cubic  foot of ion-exchange material.  Water softeners should only be installed by
qualified persons following the manufacturer's instructions and applicable codes.  The
materials and workmanship should be guaranteed for a specified period of tune.  First
consideration should be given  to companies that provide  responsible servicing dealers
permanently located as  close as possible to the water supply system.  Note:  Zeolite
softening is not recommended if any of the water consumers are on a restricted sodium
diet for medical reasons.
     Lime-Soda Ash Process.  The use of the Lime-soda ash process  or the addition of
other chemicals may not be practical for a small water supply system. However, they may
be able to  obtain package plants that soften water.  Water used for laundry may be
softened at the time of use by adding certain  chemicals such as  borax, washing soda,
trisodiumphosphate, or ammonia. Commercial softening or water conditioning compounds
of unknown composition should not be used in water intended for drinking or cooking
without the advice of the state  or local health department.
Fluoride Removal
     Although fluoride is an accepted and useful preventive treatment for reducing tooth
decay, excessive levels of fluoride may cause pitting and staining  of children's teeth or
contribute to the development of crippling skeletal fluorosis when consumed over a long
period of time.  If a water source contains fluoride above 4 mg/L, a fluoride removal
treatment should be used.
     Two  common methods  of fluoride removal  are reverse osmosis and activated
alumina. Reverse osmosis removes the fluoride from the water by using a semi-permeable
membrane (see Reverse Osmosis, Page 90). Activated alumina is a commercially available
adsorption/ion exchange media which can remove up to 90 percent of fluoride from water.
However, it requires an extended contact time and increases the pH to a level that may
94

-------
be unacceptable.  Either method may be employed as a reliable means  of removing
ftuoride.
Tastes and Odor Control
      Tastes and odors in an individual water supply system fall into two general classes-
natural and man-made.  Some natural causes may be traced to algae, sulfate-reducing
bacteria, leaves, grass, decaying vegetation, dissolved gases, and slime-forming organisms.
Some of the man-made causes of taste and odor may be due to chemicals and sewage.
      Water having a "rotten egg" odor indicates the presence of hydrogen sulfide and is
commonly called sulfur water. In addition to its unpleasant ofor, sulfur water may cause
a black stain on plumbing fixtures. Hydrogen sulfide is corrosive to common metals and
will react with iron, copper, or silver to form the sulfides of these metals.
      Depending on the cause, taste and odor can be removed or reduced by aeration or
by treatment with activated carbon, copper sulfate, or an oxidizing agent such as chlorine,
ozone, or potassium permanganate.   It should  be noted that chlorine may actually
increase, rather than reduce, tastes and odors.
      Aeration.  Aeration for control of tastes, odors and other substances is  described in
the section above, entitled "Aeration." Hydrogen sulfide can be removed by a  combination
oxidization-filtration process. A simple iron-removal filter will also do a good job if there
are only small amounts of hydrogen sulfide.
      Activated Carbon.   Activated carbon treatment involves passing the  water to be
treated through granular carbon, or adding powdered activated carbon to the water.
Activated carbon adsorbs (attracts to itself) large quantities of dissolved gases, soluble
organics, and finely divided solids. It controls taste and odor well. Activated carbon can
be used in carbon filters available from manufacturers or producers of water-conditioning
or  treatment equipment.  The recommendations included with  the filter should be
followed.
      Copper Sulfate. The most frequent source of taste and odors in an individual water
supply system is algae, whose biological byproducts cause taste and odor problems. These
tastes and odors may increase when chlorine is added to the water. When algae is present
in a water supply, its growth  can be controlled by adding copper sulfate to  the water
source, as described in the section entitled "Nuisance Organisms".
      Because algae and other chlorophyll-containing plants need sunlight to live, the
storage of water in covered reservoirs inhibits their growth.
      Chlorine.   Chlorine may be effective in reducing some tastes and odors in water.
The process is the same as that described in  the section dealing with "Superchlorination-
Dechlorination".
      Hydrogen sulfide odors in water may be caused by bacterial activity in distribution
lines or in water heaters.  A maintained chlorine residual hi the water distribution system,
and periodic disinfection followed by flushing of water heater tanks, may  solve the
problem.
Corrosion Control
      The control of corrosion is important to continuous and efficient operation of the
individual water system and to delivery of properly-conditioned water that has not picked
up  traces of metals, such as  lead (from solder and plumbing fixtures), that may be
hazardous to health. Whenever corrosion is lessened, maintenance and replacement costs
of water pipes, water heaters, or other metal parts of the system are reduced.
                                                                               95

-------
      Corrosion is commonly defined as an electrochemical reaction in which metal wears
away or is destroyed by contact with elements such as air, water, or soil.  The important
characteristics of water that may affect its corrosiveness to metals include the following:
     Acidity.  A measure of the water's ability to neutralize alkaline materials. Water
with acidity or low alkalinity tends to be  corrosive.
      Conductivity. A measure of the amount of dissolved mineral salts.  An increase in
conductivity promotes the flow of electrical current and increases the rate of corrosion.
      Oxygen Content.  Oxygen dissolved in water promotes corrosion by destroying the
thin protective hydrogen f|kn that is present on the surface of metals in water.
      Carbon Dioxide.  Carbon dioxide forms carbonic acid, which tends to attack metal
surfaces.
      Water Temperatures.  The corrosion rate increases with water temperature.
Corrosion and Scale Relationship
      Corrosion and scale often occur together, but they should not be confused.  The
effect of corrosion is to destroy metal; scale, on the other hand, clogs open sections and
line surfaces with deposits.  The products of corrosion often add to scale formation, thus
making the  problem of treating corrosion more difficult.
Prevention of Corrosion
      When corrosion is caused by acidity,  it can be controlled by an  acid neutralizer.
Another way to control corrosion is to feed a small amount of commercially  available
film-forming material into the system.  Other methods of controlling corrosion are the
installation of dielectric or insulating unions, reduction of water velocities and pressures,
removal of oxygen  or acid, chemical treatment to  decrease acidity, or the use of
nonmetallic piping and equipment.
      Physical Control. Physical control of corrosion includes proper grounding and system
flushing.  Pipe surfaces may be attacked by electrolysis, biological growth, or general
chemical reactions.   Electrolysis  is the result of  the effects of  grounded  electrical
equipment in the area, and normally corrodes the outside of a water pipe faster than the
inside.  Electrical equipment should not be grounded to plumbing, since this can greatly
increase corrosion. Proper grounding, however, reduces this kind of corrosion.  Flushing
removes bacteria from the  system that can stimulate corrosion.  Lead-free or low-lead
solder prevents corrosive water from leaching lead into the  system.
      Chemical Control. The pH of water can be increased with a neutralizing solution,
so that it  no longer attacks parts of the water  system or contributes to electrolytic
corrosion.  Neutralizing solutions may be prepared by mixing soda ash  (58 percent light
grade) with water - 3 pounds soda ash to 4 gallons of water.  This solution can be fed into
the water supply with feeders as described under "Chlorination," and can be mixed with
chlorine solutions to both correct  pH and disinfect. Soda ash is available at  chemical
supply houses.
      A dosage of lime, soda ash,  or caustic soda can be used to adjust the pH of the
treated water and deposit a thin film of calcium carbonate on pipe surfaces.   This thin
coating prevents corrosion of the metal pipe.  The right pH for this Icind of protection is
usually in the range of eight to nine.
      The right dosage of film-forming materials is most  often determined from past
experience  with  similar water.  A dosage of several milligrams per liter is  normally
required.
 96

-------
      Another  method  of chemical control  is the use  of a limestone contactor, or
neutralizing tank.  The limestone contactor looks like a water softener tank, except that
it contains limestone or marble chips. Acidic water reacts with these materials and slowly
dissolves  them until they need to be replaced.  This slow dissolving of the limestone
neutralizes the water and makes it less corrosive.
      The flow rate through a limestone contactor needs to be slow, to allow time for the
limestone to neutralize  the water. If it becomes necessary to use two contactors,  they
should be connected in parallel to provide the most neutralizing capacity.
      Maintenance of a contactor requires backwashing, sometimes as often as every other
day, to loosen and clean the limestone.  Because the limestone is heavy, high backwash
flows may be necessary.  The limestone should be inspected annually and stone added to
replace the dissolved stone.
      Corrosion control chemicals are the last to be added during water treatment. This
is mainly  because the pH for successful coagulation and chlorination is much lower than
the pH for noncorrosive water. As another example, a calcium carbonate film can form
on the filter media and would  interfere with proper filtration.
Nuisance  Organisms
      Organisms that are known to  cause problems in water supplies include several
species  of algae, protozoa, and diatoms that produce tastes and odors and clog filters.
Iron bacteria plug water well  intakes and clog pipes in distribution systems (see Iron
Bacteria Removal, Page 92).   Other nuisance organisms are copepoda, whose eggs can
pass through filters; midge larvae  or bloodworms; and snails and mollusca.  These
organisms vary in complexity and size.  They are uncommon or absent in ground water,
but are common in surface water.
      Presence  of nuisance organisms may not be dangerous to health. Interference with
water treatment processes, and unpleasant taste, odor and  appearance are the chief
complaints against them.  The following suggested treatment process can control these
organisms, but may also cause harmful conditions if not done properly. Also, before
adding chemicals  to a surface water, remember to check with local  water protection
officials and secure any necessary permits.
      Control of Algae.  Algae can be controlled by treating the water with copper sulfate
(blue stone or blue vitriol) or, when possible, by covering the water storage unit  to block
sunlight.  Maintenance of an adequate chlorine residual will control the growth of algae
and other  organisms as long as the storage unit is covered and protected from contamina-
tion.  The particular control method, or combination of methods, should be  chosen by
studying each case to assess the probability of success and the cost involved.
      Copper sulfate has been successfully used for the control of algae since 1900.
Temperature, pH  and alkalinity all affect the solubility of copper in water, so  that the
dosage needed  depends on the chemistry of the water treated and how effective copper
is against  the particular nuisance organism. Dosage rates of 1 ounce of copper sulfate
(CuSO4'5H2O) for  each 25,000  gallons of water have worked where the total alkalinity of
the water  does not exceed 40 mg/L (40 ppm).  For more alkaline waters, the dosage can
be increased to 5.5 pounds of copper sulfate per acre of surface water treated regardless
of depth.   Caution should be taken when adding copper sulfate to water since high
concentrations  (in  excess of those suggested to control algae) can kill fish or  even be
unsafe for human consumption. The copper level should not exceed 1.3 mg/L.
                                                                               97

-------
     Frequency of treatment depends on temperature, amount of sunlight, and nutrients
in the water.  Applying the correct amount of chemical regularly over the entire surface
area will keep serious algal blooms from coming back. Several treatments per season are
generally required, with treatments as frequent as twice a month during the growing
season.
     The most practical method of application for small ponds is by spraying it on the
surface. Or, a burlap bag of copper sulfate can be dragged through the water. Rapid and
even spreading of the chemical is important.
     It should be noted that the sudden death of heavy growths of algae may be followed
by decomposition on a scale that uses up the oxygen in the water. , If the removal of
oxygen is too great, a fish  kill may result.
     Any chemical applied to control a problem with nuisance organisms must be used
with caution.  The concentrations recommended above will affect only a portion of the life
system.  Large amounts  of chemicals may be a danger to other life forms in the
environment. If there is any doubt about the effects that treatment might have on other
life systems, one should ask the responsible environmental agencies.
     Tastes and odors in water can usually be removed by passing the previously filtered
and chlorinated surface water through an activated carbon filter.  These filters  may be
helpful in improving the taste of small quantities  of previously treated  water used for
drinking or cooking purposes.  They also adsorb excess chlorine.  Carbon filters can be
bought commercially and need regular servicing.
     Carbon filters should not be  expected to be a substitute for sand filtration and
disinfection, however. They are not able to reliably filter raw surface water and will clog
very rapidly when filtering turbid water.
     Weed Control. The growth of weeds around a pond should be controlled by cutting
or pulling. Before weedkillers are used, the local health department should be contacted
for advice, since herbicides often contain compounds that are highly toxic to humans and
animals. Algae in the pond should be controlled,  particularly the blue-green  types that
produce scum and unpleasant odors and that, in unusual instances, may harm livestock.

PACKAGE  PLANTS
     Many small water treatment facilities use "package plants" which can be purchased
as individual unit process modules  or as a complete preassembled unit from a single
manufacturer (see Figure 16).  Such package plants are available from  a number of
manufacturers. They are most commonly supplied for filtration and removal of dissolved
iron and manganese. The package plant usually includes all treatment equipment, pumps,
chemical feeders, and control instrumentation. As soon as the water pipes and electrical
power have been connected, the plant is ready to operate. Some package plants are fully
automated.
     The package plant option is frequently a good, quick choice  to provide the needed
treatment. Many plants can be tailored to the  specific treatment needs of a particular
source water. They also provide a design and equipment that have been proven  to be
effective and reliable in  the field.  However, many states require that package  plant
installations be formally reviewed and approved by appropriate agencies in order to certify
that the plant design will meet specific requirements.
 98

-------
                                                     EffliMM
    FIGURE 16. - Package plant diagram.

From "Technologies for Upgrading or Designing New
      Drinking Water Facilities", EPA (1990)

-------
     Some package plants do not operate automatically. Even those systems that are
automated to some extent by instrumentation require maintenance, repairs, and process
control changes by trained personnel. Such "automatic" plants are easily upset by sudden
changes in source water quality.
     A typical package plant is skid mounted from the factory and includes provisions for
feeding a coagulant chemical and a filter aid polymer before some form of filtration.
Liquid hypochlorite or chlorine gas feed equipment can also be included. Manufacturers
can also make provisions for the addition of other chemicals such as carbon, potassium
permanganate, soda ash, caustic soda, or lime. A typical flow configuration consists  of
coagulant addition, a mix chamber, flocculation chamber, settling, and filtration.  The
filtration step may consist of a zeolite bed at a softening facility. A pump may be included
to pump  finished water to a clearwell, although this may not be required if the clearwell
is located at a lower level than the treatment plant.  The clearwell is usually not part  of
the plant and must be provided separately.
     Filter backwash supply pumps are usually included, although backwash water is not.
They can be provided by the finished water clearwell. Filter backwashing may be initiated
by filter headless (resistance to flow), time clocks, or manually.
     Most equipment manuals from package plant manufacturers include brief sections
on  operating principles,  operating instructions and trouble-shooting guides.  Start-up
training,  essential to the plant operator, should be provided by the manufacturer.  The
owner should also consider requiring follow-up visits by the manufacturer at 6-month  to
1-year intervals to adjust equipment and review operations.

HOUSEHOLD WATER  TREATMENT
     Household treatment can be either point-of-use (POU) or point-of-entry (POE)
equipment. POU devices treat water at a single tap near the location where the water is
used.  They are directly connected to a tap and are only for drinking and cooking water.
POE treatment devices are designed to improve the microbiological or chemical quality
of all water entering a household.  Some POE devices are used specifically for radon
removal, such as carbon filters and aeration units.
     Centralized treatment of water is recommended whenever possible. However, under
certain conditions, the primary health agency may allow the use of POU or POE systems
for a public water supply when a central treatment system is not economically or physically
practicable.   Most of the household water treatment methods  noted below are  more
completely discussed in the previous water treatment  sections, which deal with central
water treatment systems.
     The National Sanitation Foundation (NSF) tests POE and POU household water
treatment units and lists those which have passed their  testing procedures. Although the
NSF evaluation is voluntary, many reputable manufacturers have their equipment tested
by NSF.
Water Softeners
     The most common type of water softeners exchange positively charged ions (i.e., ions
that cause "hardness" and rust stains), with sodium by passing water through a softening
resin.  After a period  of tune, the resin must be recharged by flushing a sodium salt
solution  through the softener.  Sometimes, other  salt solutions can be used,  such  as
potassium salts.
100

-------
     As mentioned above, softening may add sodium salt to drinking water. Softening
only the hot water, leaving the cold drinking water untreated, will avoid this problem.
Softening may also make the water more corrosive, and possibly increase the levels of
metals like lead and copper in the water. Occasional "flushing" of water at  the tap will
help solve the second problem.
Physical Filters
     These can be made of fabric, fiber, ceramic screening, diatomaceous earth or other
material.  Some  can  remove microorganisms (cysts, larger bacteria)  and very small
particles (asbestos fibers); but most only remove larger particles like grit, dirt or rust.
Maintenance includes monitoring the filter performance and changing cartridge filters as
needed.
Activated Carbon Filters
     Activated carbon filters are available  in several forms: granular activated  carbon
(GAC), powdered activated carbon (PAC), PAC coated paper filters, and pressed carbon
block filters.  Activated carbon can remove many organic chemical contaminants, tastes,
odors and color. Organics that are less soluble in water are removed easier than  soluble
ones. Activated carbon is not usually an effective system for removing microorganisms.
Therefore, activated carbon filters by themselves, are not recommended for use with water
which is microbiologicaUy unsafe.
     Some POE units have been used to remove radon from household water. However,
because granular activated carbon (GAC) "collects" the radioactive byproducts of radon,
this method of treatment (i.e., GAC) should not be used where levels of radon  greater
than 1,000 pCi/L  are found in the source water. Aeration of household water would be
more suitable for  radon removal when properly installed with ventilation.
     Depending on your treatment needs, either a point-of-use (POU) unit or a point-of-
entry (POE) device may be used.  For taste and odor reduction or organics removal, a
POU unit would treat only the drinking water at the tap while a POE unit would remove
contaminants from all of the water entering your home.
     If proper  maintenance is not followed, contaminants may be able  to pass through
the filter into the  drinking water.  As such,  carbon filters have a limited life and should
be replaced regularly.  Bacteria can also collect and multiply on the filter's surface.
Periods of non-use, especially in warm areas, promote bacterial growth which can lead to
unpleasant tastes or odors in  the filtered water.
Reverse Osmosis  (R.O.)
     A complete R.O. point-of-use system consists of an R.O. module and a storage tank.
However, many home R.O. systems include one or two activated carbon filter components.
The R.O. module, the heart of the system, contains a semi-permeable membrane which
allows treated water to pass through it and collect in the storage tank.  Other chemicals
and particles are  rejected and flushed to waste.  R.O. is  effective for removing most
contaminants such as salts, metals (including lead),  asbestos, nitrates, and organics.
     For every four gallons of water fed into an average small household R.O. treatment
unit, only about one gallon of drinking water is produced.  The other  three gallons of
water contain the removed contaminants and is waste water.  A small treated-water
storage tank is used with an R.O.  system because of the low pressure and flow from the
treatment unit.
                                                                              101

-------
     Water treated with the R.O. process is corrosive and might dissolve metal from
plumbing or faucets.   R.O. systems which use  cellulose  acetate membranes  are  not
recommended for use on microbiologically unsafe water, partly because some organisms
might leak through broken membranes.  Bacteria can damage cellulose acetate R.O.
membranes and cause them to fail if the manufacturer's recommendations on proper care
and maintenance are not followed.
Ultraviolet (UV) Treatment
     The primary component of a UV unit is the UV h'ght source. The light is enclosed
in a protective transparent sleeve and  mounted  so that the water can pass by and be
exposed to the h'ght.  UV light hi sufficient intensity for a long enough time can destroy
bacteria and inactivate viruses.  UV is not effective in controlling Giardia lamblia  and
other cysts, however.
     Ultraviolet h'ght produces no taste or odor,  and treats without adding chemicals to
the water. However, once the water passes through  the unit, there is no disinfectant
residual in the water to prevent bacteria from regrowing if the water is stored. Turbidity,
dirt build-up on the transparent parts  of the unit and other  visible contaminants  can
degrade the  performance of UV treatment.  Regular inspection and  maintenance is
necessary.
Maintenance of Household Units
     More  sophisticated household systems  can combine two or more treatment
technologies so that the faults of one technology can be covered by another.  However,
this increases both the initial cost of purchase and the operating/maintenance costs over
the life of the system.
     Neglected maintenance is probably the biggest problem with home water treatment.
It is important to be familiar with the maintenance requirements of each treatment unit.
Some units require more maintenance than others.  All should be maintained according
to the manufacturer's recommendations.   Some units have dealer or  manufacturer
maintenance contracts available to ensure proper operation over the  life of the unit.
     Bach water supply and each water treatment unit is different.  Consequently,  one
cannot assume that a specific unit will be the right  one in every case.   The National
Sanitation Foundation (NSF)3, which has a voluntary testing program  for POU and FOE
treatment units, is a good source of information.  In the absence of independent testing
and listing, as by NSF, one should carefully review the data and claims for the units under
consideration and get a specific written performance guarantee from  the seller.
     National Sanitation Foundation, 3475 Plymouth Road, P.O. Box 1468, Ann Arbor, MI 48106.
102

-------
TREATMENT WASTE  DISPOSAL
      Proper design and operation of a water system includes the treatment and disposal
of any wastes that are produced  (which may be sludges or concentrated liquids).  The
various waste products, and their recommended treatment and disposal, are shown as
follows:
Type of
waste
Afum sludge
Lime sludge
Diatomic ffltet sludge
Filter backwash water
R.O./ED/EDR Concentrate
Ion exchange brine
Sludge
lagoon1
X
X
X "
X
Sanitary
Sewer
X
X
X
X
X
Drying
beds
X
X
X
Evaporation
ponds
X
x
      1     Followed by landfilling at approved site (or other benifical use)

      It is also possible to discharge wastes back to their original raw water source.  Care
must be taken to prevent the treatment wastes from re-entering the water system, such as
by discharging upstream of the water intake or into lakes where the wastes can collect and
re-enter the treatment process. Discharges of this nature may require federal, state or
local permits.  Waste  storage areas  should also be located far from the water source
intake to prevent contamination of the supply.
Sludge De-watering Lagoons
      Lagoons are simply shallow sedimentation holding ponds.  Sludge is introduced and
allowed to slowly settle to the bottom while the clear supernatant (top layer), is regularly
drawn off and discharged to an approved receiving water. Lagoons are usually designed
to provide several years of storage, after which the  sludge can be allowed to air dry and
then be removed and properly landfilled or applied to some beneficial use.
Disposal to Sanitary Sewers
      Disposing of sludge  into a sewer merely moves the place of treatment and final
disposal to a wastewater treatment plant.  Considerations in this case include the limits
of sewers to  handle the waste, the ability of the wastewater treatment facility or septic
system receiving the waste, and possible metering of the waste flows for accurate payment
to the wastewater facility.
Sand Drying Beds
      Liquid  sludge can be spread  over  large, open  sand beds with water  removal
occurring by  gravity drainage, and evaporation.  Dried sludge is then manually removed
when it becomes too thick to allow the water to pass  through, and disposed of at a landfill.
Evaporation  Ponds
      Ion exchange and membrane processes produce a liquid concentrate (brine) stream
that may be restricted  from discharge to a sewer.  The concentrate must therefore be
discharged to a lined pond where the  liquid portion  is evaporated, similar to a sludge de-
watering lagoon, but with fewer solids.  These ponds are, therefore, most suited for use
in hot, arid climates. Other disposal methods include well injection into a salty (brackish)
                                                                              103

-------
aquifer, brackish surface water discharge, and spray irrigation after blending with water
which has fewer dissolved solids (lower TDS).
 104

-------
               PartV
                         Pumping,   Distribution
                         and  Storage
TYPES  OF WELL  PUMPS
     Three types of pumps are commonly used in small and individual water distribution
systems.  They are: positive displacement, centrifugal, and jet. These pumps can be used
in either a ground- or surface-source water system. In areas where electricity or other
power (gasoline, diesel oil, solar or windmill)  is available,  it  may be better to use a
power-driven pump.  Where that is not possible, a hand pump or some other manual
method of supplying water must be used.
     Special types of  pumps with  limited  applications  for  small  and  individual
water-supply systems include air lift pumps and hydraulic rams.
Positive Displacement Pump
     The positive displacement pump delivers water at a constant rate regardless of the
pressure it must overcome or the distance it must travel.  These pumps are of several
types.
     Reciprocating Pump. This pump consists of a mechanical device which moves a
plunger back and forth in a closely-fitted cylinder.  The plunger is driven by the power
source, and the power motion is converted  from a rotating action to a back-and-forth
motion by the combined work of a speed reducer, crank, and a connecting rod.  The
cylinder, composed of a cylinder wall, plunger, and check valve, should be located near or
below the static water level to eliminate the need for priming.  The pumping action begins
when the water enters the cylinder. When the piston moves, the intake valve closes, and
forces the water through a check valve, into the plunger. With each stroke of the plunger,
water is forced toward the surface through the discharge pipe.
     Helical or Spiral Rotor Pump.  The helical rotor consists of a shaft with a helical
(spiral) surface which rotates in a rubber sleeve. As the shaft turns, it pockets or traps
the water between the shaft and the sleeve and forces it to the upper end of the sleeve.
     Regenerative Turbine Pump. Other types of positive displacement pumps include the
regenerative turbine type. It incorporates a rotating wheel, or "impeller", which has a
series of blades or fins (sometimes called buckets) on its outer edge.  The wheel is inside
a stationary enclosure called a raceway or casting. Pressures several times that of pumps
relying solely on centrifugal force can be developed.
Centrifugal Pump
     Centrifugal pumps are pumps containing a rotating impeller mounted  on a shaft
turned by the power source. The rotating impeller increases the velocity of the water and
                                                                             105

-------
discharges it into a surrounding casing shaped to slow down the flow of the water and
convert the velocity to pressure.
     Each impeller and its casing is called a stage.  The number of stages necessary for
a particular installation will be determined by the pressure needed for the operation of the
water system,  and the height the water  must be raised from the surface of the water
source to the point of use.
     When more pressure is needed than can be furnished by a single stage, additional
stages  are used. A pump with more than  one stage is called a multistage pump.  In a
multistage pump, water passes through  each stage in succession, with an increase in
pressure at each stage.
     Multistage pumps commonly used in individual water systems are of the turbine and
submersible types.
     Turbine Pump. The vertical-drive turbine pump consists of one or more stages with
the pumping unit located below the drawdown level of the water source. A vertical shaft
connects  the  pumping assembly  to  a drive  mechanism located above the pumping
assembly. The discharge casing, pump-housing, and inlet screen are suspended from the
pump base at the ground surface. The intermediate pump bearings may be lubricated by
either oil or water. From a sanitary point of view, lubrication of pump bearings by water
is preferred, since lubricating oil may leak and contaminate the water.
     Submersible Pump. When a centrifugal pump is driven by a closely- coupled electric
motor  constructed for underwater operation as a single unit, it is called a submersible
pump.  (See Figure  17)   The electrical wiring to the submersible motor must  be
waterproof.  The electrical control should be properly grounded to minimize the possibility
of shorting  and damaging the entire  unit.  Since the pump and motor assembly are
supported by the discharge pipe, the pipe should be large enough so that there is no
possibility of breakage.
     The turbine or submersible pump forces water directly into the water distribution
system. Therefore, the pump assembly must be located below the maximum drawdown
level.  This type of pump  can  deliver water across a wide range of pressures; the only
limiting factor is the size of the unit and  the horsepower apph'ed. When sand is present
or anticipated in the water source, special precautions should be taken before this type of
pump is used since the grinding action of the sand during pumping will shorten the life
of the pump.
Jet (Ejector) Pump
     Jet pumps are actually combined centrifugal and ejector pumps. A portion of the
discharged water from the centrifugal pump is diverted through a nozzle  and "venturi
tube", which has lower pressure than the surrounding area.  Therefore, water from the
source (well) flows into this area of reduced pressure. The speed of the water from the
nozzle  pushes it through the pipe toward  the surface, where the centrifugal pump can lift
it by suction. The centrifugal pump then forces it into the distribution system. (See Figure
18)
Solar Photovoltaic (PV) Pump
     Solar powered pump systems include a photovoltaic (PV) array (the power source),
a motor and a pump. The array is made up of solar PV cells mounted to form modules
which are then wired together. The solar PV cells convert sunlight directly into electricity,
which drives the pump. There are several types of solar pumping systems:  submersible,
106

-------
         Power Cable
          Drop Pipe Connection
                 .Check Valve



                  - Pump Casing

                  'Inlet Screen
               Diffusers 8 Impellers'
                   ' Inlet Body
                     Power Leads
                      Motor Shaft
                  Motor Section
          Lubricant Seal
FIGURE 17. - Exploded view of submersible pump.
                                                         107

-------
                                                                     ^.Pressure
                                                                    J?  Switch
                                                                         Regulating
                                                                       —Pressure Gage
                                                                             Discharges
                       FIGURE 18. - "Over-the-weliyetpump installation.
108

-------
vertical turbine, floating: suction and centrifugal suction pump1. Figure 19 shows two types
of solar installations.
     The most common lands of pumps used in PV systems are self-priming centrifugal
pumps, submersible centrifugal pumps, and positive-displacement (reciprocating piston)
pumps.
     The amount of water output for a PV  pump  depends upon the strength of the
sunlight  falling  on the  PV array,  the  total pumping pressure,  and  the  operating
temperature of the array.  More intense sunlight produces  more electrical output and
more water. On the other hand, cloudiness reduces sunlight and water output.  At times
when no water can be pumped,  the system needs a backup system, or battery bank for
electrical power.   Solar  pumps  require a water storage system so  that water will be
available to users during periods of reduced sunlight.  Energy can be stored either
electrically (using batteries) or hydraulically (water in storage tank).
Wind Pump
     Wind pumping systems, or windmills, convert the energy in wind into mechanical or
electrical energy to  drive  a pump  (Figure 20).  The  energy systems are generally
subdivided into  two  divisions:  horizontal or  vertical-axis machines (rotor axis), and
electrical or mechanical.  The most common wind pump, the horizontal-axis wind wheel,
converts  wind power to rotary shaft power of  the axis.  A windmill "head" changes the
rotary motion of the axis to a vertical back-and-forth motion. This windmill "head" is
       Photovoltaic array
                                                                      motor
                     FIGURE 19. - Typical solar pump system.1
     Renewable Energy Sources for Rural Water Supply. IRC International Reference Center for Community
     Water Supply and Sanitation, December 1986.
                                                                              109

-------
                               Rotor
          Wind
          electro-generator  I   (A) Mechanically couplad wind pump
                                                                     Storage lank
                              (B) Electrically coupled wind pump
                       FIGURE 20. - Typical wind powered pumps.

            From "Renewable Energy Sources for Rural Water Supply"  IRC International
            Reference Center for Community Water Supply and Sanitation, December 1986.
110

-------
 mounted on a tower usually built of preformed steel. A "tail" attached to the head allows
 the -windmill to track the changes in wind direction and stop turning during high winds
 with the aid of a brake. The horizontal aids mechanical system is generally used with a
 reciprocating piston pump.  The other type of wind pump, the vertical axis  design, has
 proven ineffective in pumping water.
      The single most important factor  is the wind speed at the  site.  There is no
 guarantee that a specific amount of water will be delivered over a given period of  time
 because  of variations in wind direction, frequency, and speeds.  A storage tank is needed
 to hold enough water for three to four days to insure availability of water to  users.
 Hand Pump
      All hand pumps depend on human power and therefore have a limited pumping rate
 and pressure range compared to other mechanical systems. Hand pumps (Figure 21)  may
 be used to deliver water to the wellhead or to a storage tank. Other versions include hand
 pumps that deliver to stand pipes, or yard-tap  distribution systems.  There  are  four
 categories of hand pumps:  high-lift positive displacement pumps, intermediate lift pumps,
 low lift pumps and suction pumps.
     High-Lift Pump.  The  most common high-lift pumps are deep-well reciprocating
 piston pumps, progressive  cavity pumps and deep-well diaphragm pumps.
      The deep-well reciprocating piston pumps usually have underwater pump  cylinders
 and are operated with lever-arm pump handles. They can lift water from up to about 600
 feet (180 meters).
      The progressive cavity pump works using a rotor turning within a fixed housing that
 forces water up a pipe. The deep-well diaphragm design pump uses a flexible  membrane
 that is repeatedly stretched  and relaxed  mechanically to  provide  the pumping action.
 These pumps are especially effective for sandy or silty water.  However, they are more
 complex  and expensive then  the reciprocating piston pump.
     Intermediate-Lift/Low-Lift Pumps.   The low and  intermediate lift pumps  are
 simplified versions of the high-lift pumps.  Direct-action systems are suitable only for lifts
 of up  to approximately 40 feet  (12 meters) because  the pumper does not have the
 advantage of a lever arm. These low-lift pumps are  used in areas requiring less  than 400
 gallons per day (1.5 M3/day).
     Suction Pump. These pumps operate by creating a partial vacuum to pull the water
 upward.  They are typically used for very low heads and lift water no more than  about 22
 feet (7 meters).
 Other Types of Pumps
     An air-lift pump (Figure 22) uses bubbles of compressed ah-, injected at the base of
 a discharge pipe, to raise water up to the surface. A fairly high air pressure (increasing
with depth) is  needed to inject compressed air into  the submerged discharge pipe.
Therefore, a great deal of power is needed to run the  compressor.  Advantages of this
system include its simplicity, and the fact that it is not damaged by sand or silt, which are
common hi some wells.   Also, the mechanical equipment (the compressor)  is above
ground, and may be used to operate other air-lift pumped  wells nearby, as needed.
     A hydraulic ram lifts water to a location higher than the surface or stored supply.
It is a simple device that requires no external power supply, and is most suitable ha hilly
areas.  The hydraulic ram converts pressure surges into energy, which forces water into
                                                                             111

-------
                                                         PLUME!
                                                         ROD
                                       LOW rocmoN OF PLUHOCR
                                           SUCTION PUMP (SHALLOW WELL)
              rtUFFlUO

                TWVTUiE


          •fOUIVALVt—*1
                    FORCE PUMP ON SHALLOW WEU.
                                FIGURE 21. - 7>pica/ hand pumps.

                                   From International Reference Center
                                      Technical Paper No. 18 (1987)
112

-------
                                                   COMPRESSOR
                                                  ED PIPE
                      FIGURE 22. - Typical air lift pump.
                 From International Reference Center, Technical Paper No. 18;
                         Adapted from Hofkes and Visscher (1987)

a delivery pipe.  It operates at peak efficiency if the supply pressure is about 1/3 of the
delivery pressure.  The parts of the hydraulic ram are shown in Figure 23.

SELECTION OF PUMPING EQUIPMENT
     The type of pump for a particular installation should be chosen on the basis of the
following basic considerations:

     1.    Well or water source capacity.
     2.    Daily needs and peak demand flows of the users.
     3.    The "usable water" in the pressure or storage tank.
     4.    Quality of water (presence of sand, turbidity,  etc.).
     5.    Size and alignment of the well casing.
     6.    Difference in elevation between ground level and water level in the well during
           pumping.  In other words, how high (vertically) do we have to pump the
           water? (Static pressure).
     7.    Total operating pressure of the pump at normal delivery rates, including lift
           and all friction losses.
     8.    Piping or hose length involved. How far (horizontally) do we have to pump
           the water?
     9.    Availability of electric power, or  other energy source (e.g., solar, wind).
     10.   Ease of maintenance and availability of replacement parts.
     11.   First  cost and economy of operation.
     12.   Reliability of pumping equipment.
                                                                               113

-------
     STROKE
     BOLT
     ADJUSTMENT
                        FIGURE 23. - Typical hydraulic ram.
                  From International Reference Center, Technical Paper No. 18;
                           Adapted from Hofkes and Visscher (1987)
114

-------
      In the  case  of solar and wind powered pumps, there are additional factors to
consider. These include, for example, the average sunlight strength (in order to estimate
solar array size), or estimated wind speeds at the site and at the height of the windmill
(before designing a wind powered system).
      The rate of water delivery required depends on both the time the pump has been
operating and the total water usage between periods of pumping. Total water use can be
determined from Table 3 (Page 23). The period of pump operation depends  on the
quantity of water on hand to meet peak demands and the storage available.  If the well
yield permits, a pump capable of meeting the peak demand should be used.
      When the well yield is low compared to peak demand requirements, an increase in
the storage capacity is required. Excessive starting and stopping will shorten the life of
an electric drive motor.  Therefore, the water system  should be designed  so that the
interval between starting and  stopping is as long as  is possible, but not less  than one
minute.
      Counting the number of fixtures in the home  permits  a  ready determination of
required pump capacity from Figure 24. For example, a home with kitchen  sink, toilet,
bathtub, wash basin, automatic clothes washer, laundry tub and two outside hose spigots,
has a total of eight fixtures.  Referring to the figure, it is seen that eight fixtures requires
a recommended pump capacity between 9 and 11 gallons per minute. The lower value
should be the minimum. The higher value might be preferred if additional fire protection
is desired, or if garden irrigation or farm use is planned (see Table 9).  (Note: This
simple calculation does not take into account the possibility that low well capacity may
limit the size  of  pump that should be  installed. In this case, the  system can be
supplemented with additional storage to help cover periods of peak demand.
      The total "operating head", or operating pressure, of a pump consists  of the "lift"
(vertical distance from pumping level of the water source to the pump), elevation (vertical
distance from pump to highest point of water delivery), any friction losses  in the pipe
and fittings between the water  source and pump (depends upon rate of flow, length, size,
type of pipe,  and on the number and type of fittings), and the discharge pressure at the
pump (vertical height to which water would be raised without any outflow). For general
purposes, the total head of the average system is the sum of the static head, or pressure,
plus  friction losses in the system.  (See Figure 25)
      Pumps  that cannot be  completely submerged  during pumping use suction to raise
water from the source  by reducing the pressure in the pump  column, creating suction.
The vertical distance from the source (pumping level) to the axis of the pump is called the
"suction lift", and for practical purposes cannot exceed between 15 and 25 feet (depending
on the design of the pump and its altitude above sea level).
      Shallow well pumps should be installed with a foot valve at the bottom of the suction
line or with a check valve in the suction line in order to maintain pump prime.
      The selection of a pump for any specific installation should be based on competent
advice. Authorized factory representatives of pump manufacturers are among those best
qualified to provide this service.
                                                                             115

-------
o\
                                              TABLE  9.-Information on pumps.


Type of Pump
Reciprocating;
1. Shallow welt
2, Deep well








Centrifugal:
1< Shallow well
a. Straight ceirtri-
Stase)
"""5?"


b. Regenerative
vane- ^ujp me
type {single
impeller}

-2. Deep well
«, Vertical 8fte
shaft turbine
- (mutts- stage)


Practical
Suction Lift
(1)

32-25 ft.
22-25 ft










20 ft. max


IS "
"" 28ft,niax.

'

<
i_ -_ - _
- Impellers
submerged

',
••
Usual Well-
Pumping
Depth

22-25 ft.
Up to 600 ft





'



:
10-20 ft. ;
i :
\>-
', t
$ ; aJa.
'<• - ' t
i § ''
"v %i '

..„ J.X-. , ._
•JO^ft.


„

Usual
Pressure
Heads

100400 ft
Up to 600 ft
above cylinder









100-15&ft

•* -f j
'.I \''
100-2Qftft,




^ . u
JOO^O&ft

- '




Advantages

J. Positive aclioH,
2, Discharge; against
-variable heads.
3r Pumps watertontaintag
sand and silt.
4 Especially adapted to low
capacity and. higTx lifiSt




^
1. -Smoath, even flow, ;
2. ?wnps water <»ol«laing ,
sand and silt "', ,
3, Pressure on system is wteft
4. Low-starting torque.
5. Usually jeliafefe amfgood
1, Sam&asstraight c«nt»-
%Sl «cept ao* ssitajjli
for pwnping Tvafer tontaift-
ing sand or silt
2, iJjey are $etf-|«u»!flg.
\. -Same as shallow well
turbine.
2. AS electrical components ,
ate: accessible, above
ground,
""


Disadvantages

t- Pulsating discharge,
2. Subject tovibrafiOtt and
noise.
& Maiatenance cost way be
higft<
4. May cause destruction.
pressure if operated
against dosed valve. ;

j


1, Looses prime easHyj.
2. Bftcfettcy 4epen.
•X






-------
      1
-e ts   5 t>

•fffi'fl


1 § IN 11

&1 jS U *t Is *«>
S^3 S § g I

                         3

          *
                             1*
                             1
                                         .*-««.
                                       ^llllll
   « ^ S .

MM  *S id O
BJ  g V ^



 -J 5 ^ »S •
        § . g


        IP

        J'iJ
   •
   M
    eJ C^ 1
                     in"

                  § I f!
          I

          2  i
    1  l|f|f

    fillslil
    IS«SSJ«§>-8
        fl

fia,M'
                                     ,2


                        «j
                        a

    5
    II
    g N!^-
    5> 0
    13 13 •
                                               117

-------
00
                                        8      10      12      14
                                         NUMBER OF FIXTURES
16
20
                             FIGURE 24. - Determining recommended pump capacity.

-------
                                  Friction Head loss
                                       +
                                   Pressure Head
FIGURE 25. - Components of total operatinghead in well pump  installations.
                                                                                119

-------
SANITARY PROTECTION  OF  PUMPING FACILITIES
     The pump  equipment  for  either power-driven or  manual  systems  should be
constructed  and installed  to  prevent the entrance of contamination or objectionable
material either into the well or into the water that is being pumped.
     The pump base or enclosure should be designed so that it is possible to install a
sanitary well seal within the well cover or casing.  The pump head or enclosure should be
designed to prevent pollution of the water by lubricants or other maintenance materials
used during operation. Pollution from hand contact, dust, rain, birds, flies,  rodents or
animals, and similar sources should be prevented from reaching the water chamber of the
pump or the source of supply.
     Design should  facilitate maintenance and repair, and include enough overhead
clearance for removing the drop pipe and other accessories.
     The pumping portion of the assembly should be installed near or below the static
water level in the well so that priming will not be necessary.  If necessary, frost protection
should be considered in designing pump drainage within the well.
     When planning for sanitary protection of a pump, specific considerations must be
made for  each installation. The points below should be considered.
     The only check valve between the pump and storage should be located within the
well, or at least upstream from any portion of a buried discharge line.  This will ensure
that the discharge line at any point will remain under positive system pressure at all points
of contact—whether or not the pump is operating. There should be no check valve at the
inlet to the pressure tank or elevated storage tank. These requirements would not apply
to a concentric piping system, in which the external pipe is constantly under system
pressure.  Many pumps (submersibles, jets) usually have check valves installed within the
well.
     A well vent is recommended on all wells not having a packer-type jet pump.  The
vent prevents a partial vacuum inside the well casing as the pump lowers the water level
in the well.  (The packer-type jet installation cannot have a well vent, since the casing is
under positive system pressure.) The well vent~whether built into the sanitary well cover
or routed to a point  some distance from the well-should be protected from mechanical
damage, have watertight connections, and be resistant to corrosion, vermin, and rodents.
     The opening of the well vent should be located not less than 24 inches above the
highest known flood level. It should be screened with durable and corrosion-resistant
materials  (bronze or  stainless steel No. 24 mesh) or otherwise constructed so that insects
and vermin are kept  out.
     Certain types of power pumps require that the water be introduced into the pumping
system, either to prime the pump or to lubricate rubber bearings that have become dry
while the pump was inoperative. Water used for priming or lubricating should be free of
contamination.
     It is a good idea to provide a water-sampling tap on the discharge line from power
pumps.
120

-------
 INSTALLATION  OF PUMPING  EQUIPMENT
      Where and how the pump and power unit are mounted depend primarily on the type
 of pump employed. The vertical turbine centrifugal pump, with the power source located
 directly over the well and the pumping assembly submerged in the well, is gradually being
 replaced by the submersible unit, where both the power unit (electric motor) and the
 pump are submerged. Similarly, the jet pump is gradually giving way to the submersible
 pump for deeper installations because of the latter's superior performance and better
 operating economy.
 Vertical Turbine Pump
      In the vertical turbine pump installation, the power unit (usually an electric motor)
 is installed directly over the well casing. The pump portion is submerged within the well,
 and the two are connected by a shaft in the pump column. The pump column supports
 the bearing system for the drive shaft and brings the pumped water to the surface   (See
 Figure 26)
      Since  the long  shaft must rotate  at high speed  (1,800 to 3,600 rpm), correct
 alignment of the motor, shaft/and pump is vital to good performance and long life of the
 equipment.  There are two main points to consider in installing the pump correctly. The
 first is correct and stable positioning of the power unit.  The second is the straightness or
 vertical positioning of the pump column within the well.
      Since concrete slabs tend to deteriorate, settle, or crack from weight and vibration,
 it is usually better to attach the discharge head to the well casing.  Figure 26 shows one
 way to accomplish this.  For smoothest  operation and minimum  wear, the plate  (and
 discharge head) should be mounted perpendicular to the axis  of the pump column as
 pump and column hang hi the well.  If the casing is perfectly vertical, the pump column
 axis and the well axis  coincide, and a perfect Installation results. It sometimes happens,
 though, that the well is not perfectly vertical.   In this case, it is necessary to adjust the
 position of the plate so that the axis of the pump column is as close as possible to the axis
 of the well.  If there is enough room inside the casing (and this is one of the reasons for
 installing larger casing), there is a better chance that the pump  and column will be able
 to hang perfectly vertical-or at least  be able to operate smoothly.  Once the correct
 position of the plate is determined, it is welded to the well casing. The discharge head is
 then b'olted securely to the support-plate.
      As explained under "Sanitary Construction of Wells" on Page 58, sanitary well seals
 or covers are available to seal the well casing against contamination.  However,  some
 designs make  it difficult  or impossible to measure water levels within the well.   This
 deficiency should be corrected by welding an access pipe to the side of the casing, to
permit insertion of a water-level measuring device.  First, a hole is cut In the  casing at a
point far enough below the top to permit clear access past the discharge head of the
pump. The angle between the access pipe and the casing should be small enough to  allow
free entry of the measuring line.  The minimum Inside diameter of the pipe should be 3/4
inch, and larger if possible. Before welding the pipe In place, any sharp edges around the
hole through the casing should  be filed smooth so that the measuring device will slide
freely through the hole without  catching or becoming scratched. An angle of one unit
horizontal to four units vertical provides good access.
                                                                             121

-------
                 Bolt
                Lock
                Washer
                 Gasket


              1/2"*
              Support
              Plate
                Flat
                Washer

                Lock
                Washer
                 Nut
Pump
Discharge
Head
                                                  Line
                                                  Shaft
  Weld, Inside,
   and Out
Well
Casing
                *                        '
                 Adequate for 6 and smaller wells

         FIGURE 26. - Vertical (line shaft) turbine pump mounted on well case.
122

-------
     It is recommended that all wells be equipped with access pipes because of the ease
o£ introducing and removing measuring devices, and because the pipe permits chemical
treatment of the well without removing the sanitary well seal and pump.
     The welding around the access pipe should be at least as thick and resistant to
corrosion as the well casing itself.  This is especially important if the connection will be
located below the ground surface.
Submersible Pump
     This pump performs well in casings that are too crooked for vertical turbine pumps,
because all moving parts of the submersible pump are located in one unit within the well.
A problem could arise if there is little space between the inside casing and outside of the
pump-the pump might stick hi the well casing or be damaged during installation. If there
is any doubt about whether there is  enough  space, a "dummy" piece of pipe whose
dimensions are slightly greater than those of the pump should first be run through the
casing to make sure that the pump will pass freely to the desired depth.
     The entire weight of the pump, cable, drop pipe, column of water within the pipe,
and  reaction load when pumping must  be  supported by the drop pipe itself.  It is
important, therefore, that the drop pipe and couplings be of good quality galvanized steel
and  of standard weight.  Cast-iron fittings should not be used where they must support
pumps and pump columns.
     The entire load of submersible pumping equipment is usually suspended from the
sanitary well seal or cover. An exception to this would be the "pitless" installation.
Jet Pump
     Jet pumps may be installed directly over the well, or alongside it.  Since there are
no moving parts in the well, straightness and vertical alignment do not affect the jet
pump's performance.  The equipment in the well is relatively lightweight, being mostly
pipe (often plastic), so that loads are supported easily by the sanitary well seal.  There are
also  a number of good  "pitless adapter"  and "pitless unit" designs for both single and
double pipe jet systems.

ALTERNATE ENERGY SOURCES  AND  PUMPS
Solar Photovoltaic (PV) Pump
     To decide whether a site is suitable for solar pumps, a record of daily irradiation
(solar intensity)  for at least one year (preferably two) is  helpful. The design of a solar
pump system cannot be based on  average daily irradiation, because not enough water
would be pumped in months  of below-average solar Intensity.  The month of lowest
irradiation should be used for designing a solar pump.
     Solar photovoltaic (PV) systems use photovoltaic cells which convert solar irradiation
directly into electricity for pump operation.  Several pumping systems of this type are
                                                                             123

-------
reliable,  and available from a number of manufacturers2.  The main parts of a PV
pumping system are:

           Array of photovoltaic cells which convert solar irradiation into direct current
           (dc) electricity
           Motor and pump
           Control system
           Water storage and distribution system

     Equipment can be added to improve the performance of PV pumps such as tracking
mechanisms, solar concentrating devices and batteries.  While tracking mechanisms and
solar concentrators maximize the use of available irradiation, batteries can help provide
a backup supply of electricity from the varying supply of the PV array. The batteries can
also store electrical energy for use during periods when the array is not producing enough.
However, batteries have several drawbacks, such as heavy power loss, lack of reliability,
need for regular maintenance, and a useful life which is shorter than the rest of the solar
pumping system.
     The reason why PV pump systems are not more widely used is that they require a
large initial investment.  However, analysis of both initial equipment and operating costs
indicates that PV pumps are likely to be  cost-effective in areas of high levels of solar
irradiation, and may become more attractive as increased production of PV cells results
in lower prices.
Wind Pump
     Wind pumps use a rotor to either directly drive a pump or to  drive an electro-
generator (which produces the electricity to operate a pump) (see Figure 20). While the
mechanically driven pump requires a large rotor to capture enough wind to produce useful
power, the  electro-generator uses a smaller rotor, designed for reaching a high speed of
rotation.
     A slow running, multi-bladed rotor  for mechanically driven  pumps  has to be of
sturdy construction because of the considerable load and  force created by the rotor.
Rotary pumps are normally driven by gears on pulleys while a reciprocating-plunger pump
often uses a crank shaft coupling.  Generally, a rotary pump will put a more consistent
load on the wind rotor than a plunger pump, because the power required to run a plunger
pump changes constantly during the pumping cycle. In contrast, a rotary pump imposes
a relatively constant and continuous load on a rotor.
     A two or three-bladed rotor is used to drive the electro-generator through a set-up
gear unit to get to the required high operating rotational speed. If the generator produces
three-phase alternating current, this  power can  be  supplied  directly  to a standard
submersible motor/pump set.  The maximum power rating of the  electric motor should
not be more than about 40 percent of the generator rating.
     Wind pumps should be built using a sturdy tower that can withstand the large forces
exerted on it by the rotor, especially in high winds.  In addition, every wind pump should
     Renewable Energy Sources for Rural Water Supply. IRC International Reference Center for Community
     Water Supply and Sanitation, December 1986.
124

-------
 have a control device to protect it from rotating too fast and being damaged in high \vinds.
 Some of these control devices include brakes, which limit rotational speed, and "pull out"
 devices,  which turn the rotor away from high winds by changing its direction (under
 normal operating conditions, the vane is perpendicular to the wind, but in high winds, the
 force on it makes the rotor turn away from the wind).  Another control device disturbs
 the air stream on the rotor, thereby lowering the pressure on the rotor.
      In  mostly flat  areas with few trees  or buildings, site  selection is not  vital.  In
 mountainous areas or places where obstacles may block the flow of wind, differences in
 surface roughness and obstacles must be taken into account when estimating wind speeds
 for the site. Generally, the windmill tower should be tall enough so the rotor is at least
 15 feet (5 meters) off the ground and that the tower stands above any obstruction within
 a radius  of 400 feet (125 meters).
      Occasionally, one needs to lubricate the bearings, tighten bolts, and make minor
 adjustments and repairs. A complete overhaul is normally needed  every couple of years,
 while cup seals and other moving pump parts may need more frequent maintenance.
 Hand Pump
     When properly maintained, hand pumps can be the least expensive and most reliable
 technology for many uses. Over 50 makes and models of hand
 pumps are available worldwide. As mentioned before, hand pumps can be divided into
 four categories:

           High lift--positive-displacement pumps able to pump from depths of up to 150
           feet
           Intermediate lift-for lifts of  up to 80 feet.
           Low lift-up to 40 feet
           Suction pumps-up to 22 feet

     Capacities of hand pumps varies from 1.5 to 5 gallons per minute depending on the
 pump type, how deep the water is and who  is operating the pump. A hand pump may
 provide up to 1,200 gallons of water per day for a family or very small community.
     The pump heads on most force pumps are designed with a "stuffing box" around the
 pump rod to protect against contamination. Lift pumps with slotted pump head tops are
 open to contamination and should not be used. The pump spout  should be closed and
 directed downward.
     The pump base should be designed to serve a two-fold purpose: first, to support the
 pump on the well cover or casing top; and second, to protect the well opening  or casing
 top from contaminated water or  other harmful material. The base should  be a solid,
 one-piece, recessed type, cast with or threaded to the pump column or stand.  It should
 have enough diameter and depth to permit a 6-inch well casing to  extend at least 1  inch
 above the surface upon which the pump base is to rest.  Using a flanged sleeve embedded
in the concrete well cover or a flange threaded or clamped on the top of the  casing to
 form a support for the pump  base is recommended.  Gaskets should  be used  to insure
tight closure.
     Regular preventative maintenance for hand pumps (such as tightening nuts and bolts
and keeping the area clean), can be performed by the owner. However, when repairs are
                                                                            125

-------
required for below-ground parts, an experienced mechanic should be hired. Some below-
ground parts, that may fail include the cylinder, cylinder seals, drop pipe and pump rods.
     The expected lifetime of hand pumps is difficult to predict since it depends on the
amount of use and preventive maintenance effort.  Typically, one can expect anywhere
from 5 to 10 years of operation.

PUMPHOUSING  AND  APPURTENANCES
     A pumphouse installed above the surface of the ground should be used.  (See Figure
27)  The pumproom floor should be watertight,  preferably  concrete, and should  slope
uniformly away  in all directions from  the well casing or pipesleeve.  It should be
unnecessary to use an underground discharge connection if the pumphouse is insulated
and  heated.  For individual pumphouses  in rural areas, two  60-watt  light  bulbs, a
thermostatically  controlled  electric heater, or a heating cable will generally provide
adequate protection as long as the pumphouse is  properly insulated.
     In areas where power failures  may  occur, an emergency, gasoline-driven power
supply or pump should  be  considered.  A- natural disaster, such  as  a severe storm,
hurricane, tornado, blizzard,  or  flood, may cut off power for hours or even days.  A
gasoline power-driven electrical  unit could supply  enough power for the pump,  basic
lighting, refrigeration, and other  emergency needs.
Lightning Protection
     Voltage and  current surges produced hi powerlines by lightning are a serious threat
to electric motors.  The high voltage can easily pierce and burn the insulation between
motor windings and the motor frame. The submersible pump motor is somewhat more
vulnerable to this kind of damage because it is submerged in ground water, the natural
"ground" sought by the lightning discharge. Actual failure of the motor may be immediate,
or it may be delayed for weeks or months.
     There are simple lightning arresters available to protect motors and appliances from
"near miss" lightning strikes.  (They are seldom effective against direct hits.) The two types
available are the valve type and the expulsion type.  The valve type is preferred because
its "sparkover" voltage remains constant with repeated operation.
     Just as important as selecting a good arrester is installing it properly.  The device
must be installed according to instructions from the manufacturer and connected to a good
ground. In the case of submersible pumps, a good ground connection can be achieved by
connecting the ground terminal  of the arrester to  the submersible  pump motor frame
using a No. 12 stranded bare copper wire. The low resistance of the wire (1 ohm or less)
reduces the voltage surge reaching the motor windings to a level that it can withstand.
     If steel well casing extends below the watertable, the  ground can be made even
better by also connecting the bare copper wire to the well casing.
     IMPORTANT NOTE: Connecting the ground terminal of the arrester to a copper
rod driven into the ground does  not satisfy grounding requirements. Similarly, if a steel
casing that does not reach the ground water is relied upon, the arrester may be ineffective.
     Additional advice on the location and installation of lightning arresters can be gotten
from the power  company serving the area.
 126

-------
Removable
Roof/Walls
                                               Shingles &
                                               Sheathing
    MGURE 27. - Pumphouse.
                                                           127

-------
Pitless Units and Adapters
     Because of  the  pollution hazards involved,  a well pit  to  house  the  pumping
equipment or to permit access to the top of the well is not recommended.  Some states
prohibit its use.
     A commercial unit known as the "pitless adapter" is available to eliminate well pit
construction.  A  specially designed connection between  the underground horizontal
discharge pipe and the vertical casing pipe makes it possible to terminate the permanent,
watertight casing of the well at a safe height (8 Inches or  more) above the final grade
level. The underground section of the discharge pipe is permanently installed and it is not
necessary to disturb it when repairing the pump or cleaning the well.  (See Figures 28
through 31)
     There are numerous makes and models of pitless adapters and units available. Not
all are well-designed, and a few are not acceptable to some states.  The  state or local
health department should be consulted first to learn what is acceptable.
     Both the National  Sanitation Foundation3 and the Water Systems Council4 have
adopted criteria intended to assure that quality materials and workmanship are used in the
manufacture and  installation of these  devices.   Unfortunately,  the safety  of these
installations  is highly  dependent  on the quality  of workmanship  used during their
installation on the site.  For this reason, additional precautions and suggestions are offered
here.
     There are two general types of pitless installations.  One, the "pitless  adapter,"
requires  cutting a hole in the side of the casing at a certain depth below the ground
surface (usually below the frost line). A fitting to accommodate the discharge line from
the pump is then  inserted into the hole and attached.  Its  design varies depending on
whether it is for a pressure line alone or for both pressure and suction lines (a two-pipe
jet pump system with pump mounted away from well).  The other  part of the adapter,
mounted inside the well, supports the pumping components that are suspended in the well.
Watertight connection is accomplished by a system of rubber seals, tightened down by
clamps or by the weight of the equipment itself.
     The second type, the "pitless unit", requires cutting off the well casing at the required
depth and mounting on it factory assembled unit with all necessary attachments.
     Regardless of the type of device employed, certain problems arise, calling for special
care. Some of these are described below, with suggestions for their correction.
     Welding below ground, in cramped quarters and under all-weather conditions, often
does not result in good workmanship. If welding must be done, the welder should be an
expert pipe welder, and have plenty of room for freedom of movement and ease of visual
inspection. A clamp-on, gasketed pitless adapter is easier to install, but requires a smooth
and  clean surface  for the gasket.
     The pitless unit is manufactured and tested under factory conditions. However, its
attachment to the casing may present special problems.  If the well casing is threaded and
coupled (T&C), it may be possible to adjust the height of one of the joints so that it is
      National Sanitation Foundation, 3475 Plymouth Road, Ann Arbor, Michigan 48105.

      Water Systems Council, 600 S. Federal Street, Suite 400, Chicago, Illinois 60605.
128

-------
                               Lift-Out Device

                                            -Frost Line
  Snifter
  Valve
 Submersible
 Pump Power
 Cable
FIGURE 28. - Clamp-on pitless adapter for submersible pump installation.
                                                                      129

-------
                                    Lift-Out Device
                                                Threaded Reid Connection
                                                                  Grout
                                                             motion Seal
       FIGURE 29. - Pitless unit with concentric external piping for jet puny installation.
130

-------
                          .Lift-out Device
                                             Frost Line
                                     Wafer-tight Weld on all Sides
                                             0"-Ring Seal
                                                    lace
                                                    ivstem Pressure'
Space between Pipes Under
 §
FIGURE 30. -   Weld-on pitless adapter with concentric external piping
                 for "shallowwell"pump installation.
                                                                     131

-------
       Pros
                             -Sanitary Well Cover (Vented)
                                                 -Basement Wall
                                                 • Power
                                                 - Fused Disconnect Switch
                                                  or Circuit Breakers
                                                   Pump Controls
                                                            Pressure Tank
                                                                         Outlet
 FIGURE 31. - Pitless adapter with submersible pump installationfor basement storage.
132

-------
 about right for the attachment of the unit. If the height cannot be adjusted, or if welded
 joints have been made, the casing must be cut off at the proper depth below ground and
 then threaded.
      Power-driven pipe-threading machines can be used to thread casing "in place" in
 sizes up to and including four inches. Between ten and twelve full threads should be cut
 on the casing to make  a good, strong joint.  The threads should be of good quality, cut
 with dies in good  condition.
      When it is necessary to weld,  the first requirement is that the casing be cut off
 squarely. This cut can be made by working inside the casing using special casing-cutting
 tools, or by "burning" with an acetylene torch from outside the casing. If the torch method
 is used, it is better to use a jig that attaches to the casing, supporting and guiding the torch
 as the casing is burned off.
      A competent welder should be able to make a strong weld if given enough room to
 work in.  It is not easy to get a watertight joint under these conditions.   Two or three
 "passes" around the pipe should be made, following recommended procedures for pressure
 pipe, welding.  The final welded connection should be at least as thick, as strong, and as
 resistant to corrosion as the well casing itself.
      Clamps  and gaskets are used to attach both adapters and units. These devices have
 been criticized by some health departments because of their structural weakness compared
 with other connections.  It is feared by some that the joint is more easily broken or caused
 to leak by mechanical damage, or by frost-heave acting on the casing or the well slab.5
      A watertight joint requires good contact between the gasket and the surfaces it seals
 off.  Corrosion-resistant, machined surfaces provide better conditions for this seal. When
 the rubber gasket is used as a seal against the casing, special care must be taken to assure
 that the contact surface is clean  and  smooth. Clamp-and-gasket connections should be
 designed  so that forces resulting from weight, misalignment, twisting, settlement,  and
 vibration are absorbed by the metal parts, and not by the rubber gaskets.
      Materials  used in adapters,  adapter units, and accessories  should be selected
 carefully for strength and resistance of corrosion.  Corrosion potential is high closest to
 the surface and where there is moisture and air.  To use metals of differing "potential" in
 contact with each other in a corrosive environment is to invite rapid destruction of one of
 them by electrolytic corrosion. For example, steel clamps would work better with steel
 casing than most other metals or  alloys.  Some metals that by themselves resist corrosion
 (e.g.; bronze, brass, copper, aluminum) may corrode, or  cause others to corrode, when
placed in contact with a different type of metal. Different metals placed  in a corrosive
environment  should  be insulated  from each  other by  rubber,  plastic,  or other
nonconductor.  Care should be taken in the selection of welding materials; the welded
connection is frequently the point where corrosion begins.
      Cast iron is more resistant to corrosion than steel under many conditions of soil and
water corrosiveness.  However,  some grades of cast  iron are unable to resist severe
stresses from  tension, bending, and impact.  Metals used in castings subjected to such
stresses should be chosen, and the parts designed, to meet these requirements. Breakage
     Some States prohibit the use of "Dresser type" connections for pitless units.
                                                                               133

-------
can be serious and expensive, especially if pumping equipment, pipes, and accessories fall
into the well.
     For the same reasons, plastics should be used in adapters and units only where they
are not subjected to severe forces of bending, tension, or shear.
     Excavation around the well produces unstable soil conditions, and later settlement
will occur.  Unless at least a portion of the line is flexible, settlement of the discharge line
will place a load on the adapter connection that could cause it to break or leak. If for
some reason the use of rigid pipe is necessary,  the connection should be by means of a
"gooseneck", a "swing joint",  or other device that will adjust  to the settlement  without
transferring the load to the adapter.  The best fill material to use to minimize settlement
of the  discharge line is fine to medium sand, washed into place. With a correctly placed
cement grout seal around the casing and below the point of attachment (see Figure 32),
the sand will not find its way into the well. Sand does not shrink  or crack in drying, and
several feet of it form  an efficient barrier against bacteria.
     Once a pitless unit has been installed and tested, there  is still a risk of accidental
damage  to  the buried  connection.   There  have been numerous  cases of breakage  by
bulldozers and other vehicles. Until all construction and  grading around the area are
finished, the well should be marked clearly with a post and flag.  A 2- by 4-inch board, 3
or 4 feet long, clamped or wired securely to the well casing and bearing a red flag, will  do
the job.
     If the well is in an area where motor vehicles are  likely to be  driven, the final
installation should include protective pipe posts set in concrete. The posts should be just
high enough to protect the well, but not so high that they interfere with well servicing.
Inspection and Testing of Pitless Devices
      Pitless adapters and units are installed within the upper 10 feet of the well structure,
the zone of greatest potential for corrosion and contamination. Procedures for inspecting
and testing are therefore important.
      The buyer should pick an adapter or unit that  not only satisfies health department
requirements and the design criteria above, but whose manufacturer will stand behind it.
      Hiring a contractor with a reputation for good work is probably the  best assurance
of getting the job done right.  The owner should insist that the contractor guarantee  his
work  for at least 1 year.  Some  state and local health  departments  maintain lists of
licensed or certified contractors authorized by law to construct wells and install pumping
systems.
      Field connections on  pitless  adapters and units can  be  easily tested with  the
equipment shown in Figure 32.  First, the lower plug is positioned just below the deepest
joint to be tested, and then inflated to the  required pressure. The sanitary well seal is
then positioned in the top of the well and tightened securely to form an airtight seal.  This
isolated section of the casing  or unit is then pressurized through the discharge fitting, or
through a fitting in the sanitary well seal. A pressure of 5 to 7 pounds per square inch
should be applied and maintained, without the addition of more air, for  1 hour.  Warning:
Do not hold face over well seal  while pressurized!  While under  pressure,  all field
connections should be tested for leaks with soap foam. Any sign of leakage-either by loss
of pressure or by the appearance of bubbles through the  soap-calls for repair and
retesting.
 134

-------
             Vacuum Gage

               Plug
 Hose Fitting
 for  Negative
 Pressure  Test
                               Pressure Gage

                                  Snifter Valve for
                                  Positive Pressure Test
                                           Petcock Valve
      Sanitary Well Seal
                                           Air Line to
                                           Test Plug
           Safety Chain
           Attached to
           Test Plug
             '$ Aluminum
                Pipe
                                          Capped Discharge
                                          Connection
l-l/T.0Aluminum
      Pipe
                                        Plumbers Test Plug
                                        Inflated to Manufacturers
                                        Recommended
                                        Pressure
Reid Connectio
MGURE 32. - Pitless adapter and unit testing equipment.
                                                                          135

-------
     Adapters and units that depend on rubber or plastic seals in the field connection
should also be tested under "negative" pressure conditions.  This can be accomplished by
connecting the hose fitting (Figure 32) to a source.of vacuum.  The negative pressure is
read on the vacuum gauge.
     Positive pressure may be applied to the isolated section by means of a tire pump,
but a powered source makes the job much easier and encourages better testing.  If an air
compressor is not available or handy, a tire-inflation kit of the kind that uses automobile
engine compression will work.  (Tlie plumber's test plug should only be inflated by a
hand-operated tire pump).
     Negative pressure can be applied by connecting a length of vacuum hose (heavy wall,
small bore) between the hose fitting in the well seal and  the vacuum system of an
automobile engine.  To reach the desired negative pressure range (10 to 14 inches  of
mercury vacuum), it may be necessary to  accelerate the engine for a period of time. Once
the desired pressure range is reached, the hose is clamped shut or plugged, the engine
disconnected, and the vacuum gauge observed over a period of one hour to see whether
there is any detectable loss of negative pressure.
     Leaks found in rubber or plastic seals should be closed by tightening the clamps, if
possible. If a cement sealant must be used, it should be one that will provide a strong yet
flexible bond between  the sealing surfaces, and should be  compounded to provide long
service when buried.

CROSS-CONNECTIONS
     Plumbing cross-connections are connections between a drinkable water supply and
an unsafe, or polluted, water source6.  Contamination caused by cross-connections has
resulted in many disease "outbreaks." In addition, cross-connections can threaten water
quality and public health through the back-flow of such hazardous substances as anti-
freeze, herbicides, propane gas, boiler water, and sewage.  The contaminant enters the
drinking water system when the pressure  of the polluted source is higher than the pressure
of the drinking water source. This .is called back-siphonage or back-flow.
      Cross-connections often occur when plumbing is installed by those unaware of the
dangers of possible contamination. Single valves or other mechanical devices may not be
enough to protect a system from contamination through cross-connections.  Therefore,
those  responsible for  water supplies should be  aware  of both the dangers of cross-
connections  and of situations that require inspection  to  detect hazardous conditions
resulting from cross-connections.
Detection
      Distribution system piping should be examined regularly to identify potential cross
connections,  and actions should be taken to remove any  potential  health hazards.
Connections  to the distribution system  by a location which  uses hazardous  chemicals
should be identified and adequate cross connection protection provided. All connections
between safe and contaminated water should be identified and removed.
      U.S. Environmental Protection Agency, Cross Connection Control Manual, EPA, Office of Water,
      Washington D.C. (1989).
 136

-------
 Prevention
      Tkere are many types of devices useful for preventing backflow at cross-connections.
 The device should be  chosen according to  the degree of hazard posed by the cross-
 connection.  In addition, piping size, location and the need to test the device  regularly
 must be considered.
      Air Gap.  These are non-mechanical backflow preventers and work well to prevent
 back-siphonage and back-pressure conditions. Air gaps stop the piping flow with a loss
 of pressure. Therefore, they are generally used at the ends of the line service.  Each air
 gap requires a reservoir and secondary pumping system.
      Barometric Loop.  The loop consists of a  continuous section of supply piping that
 abruptly rises to a height of approximately 35 feet and returns back to the original level.
 It may be used to protect against back-siphonage, but not against back-pressure.
      Atmospheric Vacuum Breaker. The breaker is constructed of a polyethylene (plastic)
 float which travels freely on a shaft and seals in the uppermost position against a silicone
 rubber disc. Water flow Ms the float and  keeps it in  the upper sealed position.  This
 device is one of the simplest and least expensive back flow preventers. However,  it cannot
 be used as protection against back-pressure.
      Hose Bibb Vacuum Breaker.   This device is a vacuum breaker which is usually
 attached to sill cocks, which serve garden hose type outlets. It consists of a spring-loaded
 check valve that seals against an air outlet once water pressure is applied. Once the water
 supply is off, the breaker vents to the air, thus preventing back siphonage.
      Pressure Vacuum  Breaker.  This is another special type of atmospheric vacuum
 breaker which can be used under constant pressure. It does not protect against back-
 pressure,  and must be installed at least 6 to 12 niches higher than the existing outlet.
      Double Check with Intermediate Atmospheric Vent.  This unique backflow preventer,
 which is useful in 1/2-inch and 3/4-inch piping, is  used under  constant pressure and
 protects against back-pressure.  Construction is basically a double check valve with a vent
 to air located between two check valves.
      Double Check Valve.  This  is essentially two check valves  in one casing with test
 cocks and two tightly closing gate valves. Double check valves are commonly used to
 protect against low to medium hazard sources. They protect against both back-siphonage
 and  back-pressure conditions.
      Double Check Detector Check. An outgrowth of the double check valve, this device
 is usually used in fire lines.  The device protects the  potable water  source from fire
 fighting chemicals, booster pump fire  line  backpressure, stagnant "black water",  and
 additional "raw" water from outside fire pumper connections. It is constructed with test
 cocks to insure proper operation of the primary check valves and the by-pass check valve.
 The  valve permits normal usage flows to be metered  through a by-pass system with
 minimal pressure drop.  However, hi conditions of high flow (such as fires) water passes
 with minimal restriction through two large spring-loaded check valves.
      Residential Dual Check. This device gives reliable and inexpensive protection from
back-pressure. It is sized for half,  three-quarter and one inch service lines and is installed
immediately downstream of the water meter. Plastic check modules with no test cocks or
gate  valves lower the cost of this device.
                                                                               137

-------
     Reduced Pressure Principle Backflow Preventer. This is a modified double check valve
with an atmospheric vent placed between the two checks. The device provides protection
from back-siphonage and back-pressure and can be used under constant pressure in high
hazard conditions.

PIPE AND  FITTINGS
     For reasons of economy and ease of construction, many small public water systems
use plastic pipes and fittings.  Other types of pipes used are cast iron, asbestos-cement,
concrete, galvanized iron, steel and copper. Under certain conditions and in certain areas,
it may be necessary to use protective coatings, galvanizing, or have the pipes  dipped or
wrapped. When corrosive water or soil is encountered, coated copper, brass, wrought
iron, plastic or cast iron pipe, although usually more expensive initially, will have a longer,
more useful life.
     Pipes should be laid as straight as  possible in trenches, with air-relief valves or
hydrants located at the high points on the line.   Failure to provide for the release of
accumulated air in a pipeline on hilly ground may greatly reduce the capacity of the line.
It is necessary that pipeline trenches be deep enough to prevent freezing in the whiter.
Pipes placed in trenches at a depth of more than three feet will also help to keep  the
water in the pipeline cool during the summer months.
Plastic Pipe
     Plastic pipe for cold water is simple to install, has a low initial cost, and has good
hydraulic properties.   When  used in a domestic water system,  plastic pipe  should be
certified by an acceptable testing laboratory (such as the National Sanitation Foundation)
as being nontoxic  and non-taste-producing.  It should be protected against crushing  and
from attack by rodents.
     PVC, or  polyvinylchloride, pipe is the most widely used plastic  pipe.  This pipe
cannot be thawed  electrically, and so creates problems in colder climates where freezing
might occur. It is  fairly flexible, lightweight, resistant to corrosion and has a long  service
life. A special coating must be applied to prevent deterioration of the pipe if exposed to
sunlight.
Cast Iron  Pipe (CIP)
      This pipe has high resistance to corrosion and great strength. A thin  coating of
cement mortar on the inside of the pipe lessens the likelihood of corrosion within the pipe
and provides a more friction-free inside surface. Cast iron is not usually available in sizes
below 2  inches in  diameter, so its use is restricted to larger transmission lines.
Ductile Iron Pipe (DIP)
      Ductile iron pipe is similar to cast iron pipe, but is stronger, more flexible ("ductile"),
lighter and offers  corrosion resistance similar to  or better than cast iron. It is normally
available in 3-inch and larger sizes.  Cement mortar is often used to line the inside of
ductile iron pipe to reduce internal corrosion, and a bituminous coating or polyethylene
wrap may be applied to reduce external corrosion. When properly coated  and lined,
ductile iron pipe provides an extremely long service life.
Asbestos Cement  Pipe (ACP)
      This type of pipe is easy to install and has moderate corrosion resistance. However,
due to its non-conductivity, electrical thawing is impossible. In addition, it is rather fragile
and must be handled, imbedded and installed carefully.  In addition, when "tapping"  into
 138

-------
ACP lines, care must be taken to prevent a release of asbestos debris or fibers into the
\vater supply. The risk of releasing asbestos when in contact with corrosive water is also
a concern. Due to these factors, this type of pipe is rarely encountered in newer systems.
Reinforced Concrete Pipe
      Typically used for larger transmission and distribution mams the concrete pipe is
most economical because of its durability, strength, and carrying capacity. However, it is
difficult to handle, due to its heavy weight and resistance to tapping.
Steel Pipe
      Steel pipe is strong, lightweight, easy to handle and transport, and easily assembled.
This pipe is prone to corrosion and needs to be lined and coated to prolong its life.
Copper Pipe
      This type of pipe has high resistance to corrosion and is easily installed. Fittings are
usually available in the same sizes and materials as piping, but valves are generally cast
in bronze or  other alloys. In certain soils, the use of dissimilar metals in fittings and pipe
may create electrolytic corrosion problems. The use of nonconductive plastic inserts
between pipe and fittings or the installation of sacrificial  anodes is helpful in minimising
this type of corrosion.

PIPE  CAPACITY AND  HEAD  LOSS
      The pipe selected should be large enough to deliver  the required peak flow of water
without excessive loss of pressure.  The normal operating water pressure for household
use ranges from 20 to 60 pounds per square inch,7 or about 45 to 140 feet of head at the
fixture.
      The capacity of a pipeline is determined  by its size, length, and interior surface
condition. Assuming that the length of the pipe is fixed, and its interior condition known,
the key problem in design of a pipeline is that of determining the right diameter of pipe.
      The correct pipe size can be selected with the aid of Figure 33, which gives size as
a function of pressure (head) loss, H, length of pipeline,  L, and peak discharge, Q.  For
example, suppose that  a home and farm installation is served by a reservoir a  minimum
distance of 500 feet from the point of use, whose surface elevation is at least 150 feet
above the level of domestic service,  and in which a minimum service pressure of 30
pounds per square inch is required. It will be necessary first to determine the maximum
operating head loss, i.e., the  difference in total head and the required pressure head at the
service.

                     H =  150 - (2.3 x 30) = 15O - 69 = 81 feet

The maximum peak demand which must be delivered by the pipeline is determined to be
30 gallons per minute based on local usage rates.
                                                                               i
                            Q = 30  gallons per minute
     One pound per square inch is the pressure produced by a column of water 2.31 feet high.


                                                                               139

-------
                O.I
              O.O9
              0.08
              007
              0.06
              0.05
              O.O4
              O.OI
            0.009
            O.OO8
             0.007
            O.OO6
                       (Hazen- William Formula OIOO)
           O.OOO7
           0.0006
           O.OO05
           O.OOO4

           O.OOO3
           O.OOO2
           0.00015
                 1/2"     3/4"     I"     1-1/4"  1-1/2"     2"   2-1/2"    3"      4"

                         Nominal Diameter- Standard Galvanized Pipe
                         FIGURE 33. - Head loss versus pipe size.
140

-------
The hydraulic gradient is 0.162 foot per foot.
                    H  _8l
                    L  500
= 0.162 foot per foot
      Using Figure 33, with the computed values of H/L and Q,  one finds  that the
required standard galvanized pipe size is approximately 1 3/8 inches.  Since pipes are
available only in standard sizes, standard pipe of IVz inches in diameter (the next larger
size) should be used.
      Additional pressure losses may be expected from the use of fittings in the pipeline.
These losses may be expressed in terms of the equivalent to the length and size of pipe
which would produce the same loss if, instead of adding fittings, we added additional pipe.
Table 10 lists some common fitting losses in terms of an equivalent pipe length.
      In the example given above the inclusion of two gate valves  (open), two standard
elbows, and two standard tees (through) would produce a pressure loss equivalent to 15
feet of IVz-inch pipe. From  Table  10, one finds that by using 515 feet of lV£-inch pipe
instead of the actual length of 500 feet (H/L=0.157), the capacity of the system for the
same total head loss is about 38 gallons per minute.  This is a satisfactory flow.

         TABLE  10. -Allowance in equivalent length of pipe for friction loss
                            in valves and treaded fittings
Diameter
of fitting
Inches
3/8
1/2
3/4
1
14/4
1-1/2
2
2-1/2
3
3-1/2
4
5
6
90 degree
ell
Feet
1
2
3,5
3
4
5
7
8
10
12
14
17
20
45 degree
ell
Feet
0.6
1.2
15
1.8
2.4
3.0
4,0
5.0
6.0
7.0
8,0
10.0
12.0
90 degree
tee
Feet
13 -
3
4
5
6
7
10
12
15
18
2l'
25
30
Straight
run
Feet
0.3
0.6
03
0.9
1.2
1.5
2
2.5
•3
3.6
4
5
6
Gate
valve
Feet
OS
0.4
0,5
0.6
m
1.0
1.3
1.6
2
2.4
2,7
3.3
4
Globe
valve
Feet
&
15
20
25
35
45
55
65
80
100
125
140
165
Angle
valve
Feet
4
8
12
15
18
22
28
34
40
50
55:
70
80
     It can be seen from this example that fitting losses are not particularly important for
fairly long pipelines, say greater than about 300 feet. For pipelines less than 300 feet,
fitting losses are very important and have a direct bearing on pipe selected; therefore, they
should be calculated carefully.
     Globe valves, which produce large pressure losses,  should be avoided in main
transmission lines for small water systems.
                                                                              141

-------
     Interior piping, fittings, and accessories should conform to the minimum plumbing
requirements of the National Plumbing Code* or the applicable plumbing code of the
locality.

PROTECTION OF DISTRIBUTION SYSTEMS
     The sanitary  protection of new or repaired  pipelines  can be ensured by close
attention to certain details of construction. All connections should be made  under dry
conditions, either in a dry trench or, if a dry trench is not possible, above the ground on
a  dry  surface.  Soiled piping should be thoroughly cleaned and disinfected  before
connections are made. Flush valves or cleanouts should be installed at low points where
there is no possibility of flooding.
     When  not properly designed  or  installed,  frostproof  hydrants  may  allow
contamination into the water system.  Such hydrants should be provided with good
drainage to a free atmosphere outlet where possible. The drainage from the base of the
hydrant should not be connected to a seepage pit  that is subject to pollution,  or to a
sewer. The water-supply inlet to water tanks used for livestock, laundry tubs, and other
similar installations should be placed with an air gap (twice pipe diameter)  above the
flooding level of  the  fixtures  to prevent back  siphonage.   There  should  be  no
cross-connection, auxiliary intake, bypass, or other arrangements that would allow polluted
water, or water of questionable quality, to be discharged or drawn into the domestic water
supply system.
     Before a distribution system is used, it should be completely flushed and disinfected.

DISINFECTION OF DISTRIBUTION  SYSTEMS
General
     The system's distribution system should be disinfected if untreated or polluted water
has been in the pipe, upon completion and before operating the new system to insure
water  of satisfactory quality, and after maintenance and repair.
Procedure
      The entire system, including tanks and standpipes, should be thoroughly flushed with
water  to remove any sediment that may have collected during construction. After flushing,
the system should  be filled with a disinfecting solution  of calcium hypochlorite. This
solution is prepared by adding 1.2 pounds of high-test 70 percent calcium hypochlorite to
each 1,000 gallons of water, or by adding 2 gallons of ordinary household liquid bleach to
each 1,000 gallons of water. A mixture of this kind provides a solution of at least 10 mg/L
of available chlorine.
      The  disinfectant should be left in the system, tank,  or standpipe, for at  least  24
hours, examined for residual chlorine, and drained out. If no residual chlorine is found,
the process should be repeated.  Next, the system should be flushed with treated water
and tested for coliform. After coliform test results are satisfactory, the system, tank or
stand  pipe can be placed into operation.
      Obtainable at the American Society of Mechanical Engineers, United Engineering Center, 345 East 47th
      St, New York, N.Y. 10017.
 142

-------
DETERMINATION  OF STORAGE VOLUME
     Three types of storage facilities are commonly employed for individual water supply
systems. These are pressure tanks, elevated storage tanks, and ground-level reservoirs and
cisterns.
     When ground water sources with sufficient capacity and quality are used, only a
small artificial storage facility may be needed, since the water-bearing formation itself is
a natural storage area. However, if the well is not able to meet peak water demand or
treatment is required, additional storage volume will be needed.
     If water demand doesn't change, and treatment or well capacities can be increased,
the amount of storage required will  decrease.  Therefore, there is a balance between
providing a larger treatment process or well capacity and providing additional storage.
Pressure Tanks
     Pressure in a distribution system with a pneumatic tank is maintained by pumping
water into the tank. This pumping action compresses a volume of entrapped air.  The air
pressure is equal to the water pressure in the tank and can be kept between desired limits
by using pressure switches. These switches stop the pump at the maximum setting and
start it at the minimum setting.  The capacity of the pressure tank is usually small when
compared to the total daily water consumption.  Only 10 to 40 percent of a pressure tank
volume is usable storage.  For  this reason, pressure  tanks are only designed for peak
demands.  The maximum steady demand the system  can deh'ver is equal to the pump
capacity.
     The usable storage of a pressure tank can be increased by "supercharging" it with air
when it is installed, or by recharging at the factory.  Recharging can only be done in tanks
in which the water space and air space is completely separated by a diaphragm or bladder.
Consult your dealer for design details and characteristics.
     Use the figures in Tables 11 and 12 for the selection of pumps and pressure tanks
for various size homes.  The pump capacity from Table 11 can be used to find the right
tank size for the type (precharged, supercharged, or plain) and pressure range needed.
These tabulated values are recommended by the Water System Council9.
     When a pressure tank is part of the distribution system, there will be no problem
with "water hammer". Otherwise, it may be necessary to provide an air chamber on the
discharge line from the well, located near the pump, to minimize water hammer.

                TABLE 11. - Seven-minute peak demand period usage.
Number of baths in home:
iNojtinal 7-.mtnu.te -peak demand (gaj.)
Minimum size pump to meet demand
without using storage
1
45
7 gpm
!1/2
75
10 gpm
2-2'/a
9S
14 gpm
3-4
122
17 gpm
           NOTE: Values given are average and do not include higher or lower extremes.
     Water Systems Council, 221 North LaSalle Street, Chicago, IL 60601
                                                                             143

-------
    TABLE  12. - Tank selection chart - gallons (Based on present industry practice)
Pump
capacity
pnm
240
300
360
420
480
540
600
660
720
780
840
900
960
1020
:10SP :
1140,
1200
ffom
4
5
. 6
. 7 	
8
	 9 	
10
11
12
13
W '.:;
15
16
17
18
19
20
Minimum
Draw
Down
featt
4
5
6
7
&
9
10
12
13
15
17
19
20
23
25
27
30
Switch setting
pounds per square inch
20-40
•A
15
15
20
20
25
30
30
35
40
45
55
60
65
70
80
85
95"
*B
15
20
20
25
30
30
35
40
45 '
50
60
65
70
80
85
95
105
*C
20
30
35
40
"40
50
55
60
70
80
90
100
110
120
135
150
160
30-50
'A
15
20
25
25
30
35
40
45
50
60
65
75
75
90
95
105
115
*B
20
25
25
30
35
40
45
50
60
65
75
80
90
100
110
120
130
*C
30
40
43-
55
65
70
80
95
105
120
135
150
160
185
200
215
240
40-60
*A
20
25
30
30
35
40
45
55
60
70
75
85
95
105
115
125
140
*B
20
25
30
40
45
50
55
65
70
80
90
105
115
125
140
150
165*
*C
40
50
55
75
85
95
105
125
135
155
175
195
205
240
260
280
310
                           *A - Precharged bladder or diaphragm tank.
                           *B - Supercharged, floating water tank.
                           *C - Plain steel tank.

Elevated Storage
     Elevated tanks should have a capacity of at least two days of average consumption.
Larger storage volume may be necessary to meet special demands, such as firefighting or
equipment cleanup.
Ground-Level Reservoirs and Cisterns
     Reservoirs that receive surface runoff should generally be large enough to supply the
average daily demand over a dry period of the maximum length anticipated. Cisterns are
usually designed with enough capacity to provide water during periods of less than one
year.

PROTECTION  OF STORAGE  FACILITIES
     Suitable storage facilities for relatively small systems may be made of concrete, steel,
brick, and sometimes wood (above the land surface). Such storage facilities should receive
the same care as system installations in the selection of a suitable location and protection
from contamination. Waterproofing the interior of storage units with asphalt or tar is not
recommended because of the unpleasant taste imparted to the water,  and the possibility
of chemical reactions with materials used for treatment. Specifications for painting water
144

-------
tanks are available from the American Water Works Association.10  Appropriate federal,
state, or local health agencies should be consulted about acceptable paint coatings for
interior tank use.
      All storage tanks for domestic water supply should be completely covered and so
constructed to prevent pollution by outside water or other foreign matter. Figures 34 and
35 show some details.for manhole covers and piping connections to prevent pollution by
surface drainage.  Concrete and brick tanks should be made watertight with a lining of
rich cement mortar.  Wood tanks are usually constructed of redwood or cypress and, while
filled, will remain watertight. All tanks require good screening of any openings to protect
against the entrance of small animals, mosquitoes, flies, and other small insects.
      Tanks containing water to be used for livestock should be partially covered and
constructed so  that cattle will not enter the tank.  The area around the tank should  be
sloped to drain away from the tank.
      Figure 34 shows a typical concrete reservoir with screened inlet and outlet pipes.
This figure also illustrates the sanitary manhole cover. The rim should be elevated at least
four inches above the ground with  the cover extending two inches beyond the edge of the
rim. This type  of manhole frame and cover should be designed so that it may be locked
to prevent access by unauthorized persons.
     An emergency water supply, that has been polluted at its source or in transit, should
not be added to storage tanks, cisterns, or pipelines used for drinking water.
     Disinfection of storage facilities after construction or repair should be carried out
in accordance with the recommendations given under "Disinfection of Water Distribution
System" in this  part of the manual.
     It can be seen from this example that fitting losses are not particularly important for
fairly  long pipelines, say greater than about 300 feet.  For pipelines less than 300 feet,
fitting losses are very important and have a direct bearing on pipe selected; therefore, they
should be calculated carefully.
     Globe valves,  which produce large pressure losses, should be avoided  in  main
transmission lines  for small water systems.
     Interior piping, fittings, and accessories should conform to the minimum plumbing
requirements of the National Plumbing Code11 or the applicable plumbing code of the
locality.             ,
     American Water Works Association, 6666 West Quincy Avenue, Denver, Colorado 80235.

     Obtainable at the American Society of Mechanical Engineers, United Engineering Center, 345 East 47th
     St., New York, N.Y. 10017.

                                                                               145

-------
                                Lock
                                                            Switch Control -
            Screened Overflow
            and Vent
                          FIGURE 34. - Topical concrete reservoir.
146

-------
      Overlapping,  Circular Iron Cover
               Iron Cover
          Galvanized Sheet Metal
        ,   Over Wooden Cover
             Concrete Cover

            MANHOLE COVERS
                                                                   Foot Piece or Brick
TYPICAL VALVE AND BOX
                                                           tj,
                                                            * n r-r'
                                                                           -Coupling
                                                         Pipe Connection With
                                                         Anchor Flange Casting
                                                                      Top of Cistern
                                                                      or Reservoir
             OVERFLOW AND VENT  .
                                                    VENT
FIGURE 35. - Typical valve and box, manhole covers, and piping installations.

                                                                                        147

-------

-------
                 Part VI
                          Information,  Assistance  &
                          Community  Support
 INTRODUCTION
      Depending on specific needs, a small community water supply system may take
 various steps to improve water quality and/or supply. These steps may include selecting
 new equipment, or pursuing ways to improve operations and maintenance of the water
 supply system. Other means of improving the water system may include:

       -   Building a better understanding of regulations affecting public and private
           water systems.
           Seeking financial and technical support.
       -   Locating trained personnel to install, operate and/or maintain the water
           system.
           Improving community awareness of water supply issues.
           Creating a climate for active community participation.
           Finding organizations to assist in water supply planning.

      Parts I through V of this manual provide information regarding the selection of a
 suitable water source and  the treatment techniques necessary to  ensure delivery of safe
 drinking water. For this information to be best used, it may also be necessary for a small
 water  system  to obtain current information and locate other means  of technical and
 financial support.  The purpose of this section is to provide direction in identifying s-uch
 resources  available to communities.

 INFORMATION  RESOURCES
     The first and most important tool is information. A small public water system must
 gain information and an understanding of local and federal requirements that apply to
 water supply. The county or other local health authority may be the first contact for this.
 State drinking water agencies are also excellent information sources (Appendix F). EPA
 drinking water offices (Appendix G) are also available to help.  EPA also operates a Safe
 Drinking Water Hotline (1-800-426-4791), so that citizens may obtain current information
 regarding EPA drinking water programs.
     Other organizations provide information or support for small water systems. These
 include the  National Rural Water Association  (NRWA), American  Water  Works
Association (AWWA), National Water Supply Improvement Association (NWSIA), and
                                                                            149

-------
the Rural Community Assistance Program (RCAP).  The address and phone number of
these and other organizations can be found in Appendix H.  Other services provided by
these organizations are described in the Technical and Financial Assistance sections of this
part.
      Another source of valuable  information includes the accumulated knowledge  and
experience of other similar-sized water suppliers.  Systems in the same geographical area
face many  of the same challenges, and their problem solving experience can be shared.
A single contact of this type can often provide valuable information and guidance.
      Information is also available jn many references, which provide detailed explanations
of the various assistance options, source  protection and development methods,  and
treatment techniques described in this manual.  Useful references are included in the
Bibliography.
Public Education
      An informed public can be a valuable ally in the effort to provide a safe and reliable
supply of drinking water. A community needs to be aware of the Safe Drinking Water Act
(SDWA), its purpose, and the impact these regulations may have on their water system-
especially those regulated under SDWA as public water systems.  Public education is a
responsibility shared by many, including the various levels of government, water industry
organizations, and the water system owners.

      Information on water  supply is provided in several forms:
           Distribution of informative pamphlets.
           Monthly newsletters or public service press releases to the news media.
           Events such as seminars, water works conventions,  etc.
           Public appearances  for TV, radio and local clubs.

      Promoting or attending seminars on drinking water quality, health effects and water
source protection will increase public knowledge and interest in water supply. These can
be included with special events such as water awareness week, county health programs,
school tours or  other local activities.  This can be  an effective means of building a
 community's interest in drinking water issues.
      Speaking at local community functions about water supply offers an opportunity for
 an owner or  operator to increase public knowledge of drinking water.  This includes
 informing the public of new water regulations and what is being done locally to improve
 public water supply.

 COMMUNITY  INVOLVEMENT
      A second  powerful tool  is the organization  of information and resources.  The
 organization maybe a person or group of persons in the community who focuses on water
 supply,  studies  and  understands  the  issues,  participates  in  decision  making  and
 communicates with the rest of the community. A water supply  committee may best serve
 as the organizational unit  to perform these functions, but in some cases, less formal
 community participation may be as effective. An organized, informed community can be
 actively involved in the decision making and long-term planning goals, to help create a
  150

-------
 safer and more reliable drinking water supply. Supported by the community and other
 organizations (see Figure 36), a water supply committee can do the following:

           Assist in assuring protection of water source.
           Gather important information  about available water resources, regulations,
           health issues, etc.
           Set priorities for water system.
           Plan and schedule water supply improvements.
           Select contractors, equipment suppliers, engineers, and staff as required.
           Review operations and maintenance procedures periodically.
           Keep abreast of system finances and available sources of funding/loans.
           Seek additional training as needed.
           Report regularly to the community.

 TECHNICAL ASSISTANCE AND TRAINING
      Many sources of assistance for small water systems can be found on Federal, State
 and local levels and from groups such as the American Water Works Association. These
 sources  can  lend  technical  assistance in  the form  of  technical training, hands-on
 operational assistance, design support, and regulatory guidance.
 Technical Support
      Many states have programs specifically  designed  to provide technical support to
 small  community water supply  systems.   Operator training and certification is  an
 established program in more than 40 states. State programs offer a wide range of training
 from beginner level correspondence courses to  advanced, comprehensive water treatment
 courses.  In most states, these programs are organized by  the state drinking water agencies
 (see Appendix F).
      Large water utilities can sometimes help small systems with technical assistance.  In
 some areas "circuit riders" are available to help with the operation and maintenance of
 systems that cannot hire a local person to take on those responsibilities.  Circuit riders are
 licensed operators who provide on-site technical assistance in the operation of a number
 of small water systems within a defined service area. These programs are provided by
 many state regulatory agencies, the National Rural Water Association (NRWA), larger
 utilities and individual operators. A circuit rider assistance program can also be written
 into service contracts with utilities, consulting firms, or equipment vendors.
     The Rural Community Assistance Program (RCAP) can also help rural community
 officials build their skills hi solving local water problems.  It provides on-site technical
 assistance, training and publications, and works to improve federal and state government
 responsiveness to the needs of rural communities.
     In  addition,  local  engineering  consultants  and  equipment  manufacturers
representatives are available  to advise  on matters such as technology, installation,
 operations, etc.
 Operations and Maintenance
     Operations and maintenance  (O&M)  is  a central concern of a water supply, no
matter how simple or complex the system. Operations refers to those activities performed
                                                                              151

-------
K
to
             U,S. EPA
                                                           Water Supply
                                                            Committee
             County
             Agency
            State
            Agency
             Rural
             Water
             Association
             AWWA
Banks, Federal
Assistance, State
Assistance Program
                                                                                                          Citizens
                                                                                                          Consulting
                                                                                                          Engineers
                                                                                                          Industry
                                                                                                          Groups
Equipment
Suppliers


Neighboring
Large Water
Utilities
                                          FIGURE 36. - Sources of information and assistance.

-------
 on a regular basis to ensure that the water system reliably delivers an uninterrupted supply
 of potable water. Operating treatment equipment, adding chemicals, ordering treatment
 supplies and spare parts, performing water quality analysis, and keeping records are typical
 operational duties. Maintenance refers to work carried out to ensure that equipment and
 related materials are able to function, such as periodic cleaning, lubrication or repair of
 equipment.
      A process control program involving laboratory testing and adjustment of chemical
 feed equipment  to  changes  in water quality is a key element in maintaining  system
 performance.  Through training and experience, operators become skilled in evaluating
 changes in raw water quality and making required chemical feed changes to maintain a
 consistent high-quality finished water.
     _ New procedures, requirements, and occasional staff turnover require an on-going
 training program for operators and managers of small water systems.  This is an essential
 and continuous  process.   As mentioned above, state agencies  and water industry
 organizations  sometimes offer training suited for small water systems personnel.  O&M
 costs and the cost of replacing major equipment items must be included in the water rate.
 Loans obtained for water systems may in some cases include provisions requiring revenues
 to cover long-term O&M costs, or a service agreement which provides the O&M needs
 of a water system. Proper O&M guarantees better long-term performance and more cost-
 effective operation of a water supply.
     Several  agencies provide on-site assistance for selection of a general consultant,
 laboratory services, design review,  utility  management, and rate setting. There are also
 operation and maintenance manuals available for the small water system, some of which
 are listed in the Bibliography of this manual.

 FINANCIAL  ASSISTANCE
     Many small water supply systems which only have a few customers over which to
 spread their costs may require financial assistance in order to make improvements to their
 system.  Many federally-funded and state-sponsored financial assistance programs are
 outlined below.
 Farmers Home Administration (FmHA)
    ^ The FmHA of the U.S. Department  of Agriculture has several programs that
 provide grants and loans. These loans and grants are the most important outside source
 of money available to many  small water utilities throughout the United States.  The
FmHA manages several programs that aid  small publicly-owned water utilities. Preference
is given to projects serving low income communities and mergers of small facilities.
     Borrowers of FmHA funds must be unable to secure loans from other sources at
reasonable rates or terms.  They must be financially sound and able to borrow and repay
loans, to pledge security for loans,  and to operate the facilities.  Grants may be used to
cover up  to 75 percent of facility costs  and can be  used along with other financial
assistance. The FmHA will assist those seeking funds in assembling information on the
engineering feasibility, economic soundness, financing and other aspects of the project.
     The FmHA programs provide incentives to prevent building poorly planned water
systems, and to encourage regional systems.  FmHA also urges small water systems to
combine, and generally makes funds available contingent upon cooperative agreements.
     Appendix I contains a listing of FmHA state offices.
                                                                             153

-------
Community Planning and Development
     The Community Planning and Development Agency of the U.S. Department of
Housing and Urban Development (HUD) has Community Development Block Grants
(CDBG) available to cities smaller than 50,000 people.  Priority is given to cities with low
and moderate income. Water and sewer projects are eligible. The number of very small
cities (under 1,000  persons) receiving grants has been  increasing. The CDBG program
has been a good source of construction funding for small water systems in rural areas and
on urban fringes. All but three states (New York, Maryland, Hawaii) operate the program
on a state basis.
     In many states, the Department of Community Affairs administers the program. In
others,  the Department of Economic  and Community  Development, state  planning
agencies, the governor's office and economic or industrial development agencies may
operate the program.  Generally, these state agencies offer financial aid and assistance in
applying for grants.
Economic Development  Administration (EDA)
     The EDA of the U.S. Department of Commerce provides grants for public works
and  development facilities in economically distressed areas and areas in which improved
facilities will encourage the industrial or commercial climate  of the area.  The EDA
program is considered less  useful than some of the other federal programs for smaller
water systems, but in  many cases  it has been combined with a FmHA loan program to
provide a financially possible project.
U.S. Small Business Administration  (SBA)
     The SBA assists small businesses with two types of loans.  The first type is a bank
loan, guaranteed by SBA, with a maximum loan amount of $500,000. The second type is
a direct loan made by SBA to a small business that cannot obtain a SBA guaranteed loan
from a private source.  The largest amount under this  direct loan is $150,000.  The
advantage of the SBA loan program is that it is available  to a privately owned utility.
Even though the funds  are limited, it has been used for  improvements, extensions and
upgrading of facilities.
Revolving Funds
      Several states have revolving funds for providing  loans and/or grants to water
systems needing capital improvements.  To whom these funds are given  is normally
decided based on  need, with priority given to systems which require improvements to
 comply with water quality regulations. While most funding is in the form of low-interest
loans, grants maybe available for systems which serve low-to-moderate income levels and
have limited financial resources to repay a loan.
      The availability and types of grants and/or loans vary among states.  Your state
 drinking water agency can provide information on what is available in your state.
 State Loan and Grant Programs
      State agencies  also  may provide funds to small systems to expand or improve
 facilities in order to comply with the Safe Drinking Water Act or to provide an adequate
 supply of quality drinking water. However, most states do  not provide funding to privately
 owned  facilities under the grant or loan programs.
 154

-------
Industrial Development Bonds
      An often ignored source of low cost financing available to small privately owned
water utilities is the industrial bonding authority of each state, county or municipality.
Pursuant to Section 103(b) of the Internal Revenue Code, each state may issue tax-exempt
bonds to be used for private business. The code specifically allows for furnishing water
for any purpose so long as the water is made available to all members of the public and
the facilities are either operated  by a governmental agency or the rates are regulated by
a governmental agency.  Contact the appropriate state agency for more information on
how this program is applied in your state.
Revenue Bonds
      A common method of financing improvements to water systems today is revenue
bonds.  Although not true "assistance", they are a useful means of financing. These bonds
are issued and backed by the  revenues expected to be received from rates charged for
water consumed by the customers.  The rates set must be enough to cover the operation
and maintenance of the system, provide funds to pay principal and interest to retire the
bonds, and meet any other rules as set forth in the  bond covenant.
General Obligation Bonds
      Another means of financing is through the sale of general obligation bonds, payable
from property taxes. These  are relatively simple bonds based primarily on the ability of
a governmental body to incur debt that  does not exceed  a fixed percent (usually 10
percent) of the assessed value of property within its control. A second factor involved in
issuing these bonds is the requirement in some states that authorization must be obtained
by referendum (direct vote).

WATER  RATES
      The life blood of any utility is an adequate and fair rate structure to provide money
for good management, operation and maintenance and amortize (slowly put money aside
to repay) any outstanding loans. However, in many of the small and very small water
supply systems there is a lack of  earnings to accomplish these utility responsibilities,
resulting in poor  service and poor water quality. Water rates  must be set to cover all
operational and capital costs in order for a system to remain financially stable. Routine
review of the  water system's financial health can provide  an early warning to prevent
financial shortfalls from occurring. A more detailed source of information for determining
proper  water rates  and management practices are available from EPA's booklet  Self-
Assessment for Small Publicly-Owned Water Systems.  Additional booklets are available for
mobile  home parks, privately owned systems, and homeowner associations.
Operating Costs
      Operating costs are the costs related to providing and maintaining the water supply.
Examples include chemicals and electricity for treatment, maintenance parts, tools, routine
replacement of equipment, and payments  on Ipans.  One way to be sure that the funds
collected to operate a water  system are enough to cover operational costs is to calculate
the "operating ratio."
                                                                              155

-------
     The operating ratio is calculated by dividing the total revenues by the total operating
costs. Although this is a simple test, it requires a thorough review of accounting records
to find the numbers. The following table can be used to figure the operating ratio for a
small water system:

                      OPERATING RATIO WORKSHEET
                                 (Year to Date)
     TOTAL REVENUE

          User Service Charges
          Hook Up/Other User Fees
          Taxes/Assessments
          Interest Earnings
          Other Revenue
          Total Revenue

     TOTAL OPERATING EXPENSES

          Administration
          Wages
          Benefits
          Electricity
          Chemicals
          Fuel & Utilities
          Parts
          Equipment Replacement Fund
          Principal & Interest Payments
          Operator Training
          Contractor Fees
          Other
          Total Operating Expenses
     OPERATING RATIO

          Total Revenue

          Total Operating Expenses

          Operating Ratio
divided by

   equals
     It is best to calculate the operating ratio on a year-to-year basis since revenues and
expenses usually vary from month to month.  For a financially healthy water system, an
 156

-------
 operating ratio of 1,00 is a minimum. Special attention should be given to the trend in the
 operating ratio.  A monthly comparison to previous years during the same month can
 provide an early warning of trouble so that shortages in funds can be avoided. A stable
 or upward trend indicates a proper financial balance and that the water rates are properly
 set.                                                                      F  F  y
 Capital Costs
      Examples of capital costs include  those that may be necessary to provide new or
 improved major equipment or facilities need to meet the requirements of the 1986 SDWA
 Amendments,  to replace aged  system parts, or to  meet growing demands.   Mam
 extensions to serve new customers  are  usually charged to  the  developer  or  those
 customers.   To  cover  the cost of installing new connections, some systems  charge
 connection fees for materials and labor for the main connection, service line, and meter
 installation.  Connection fees may also include a portion to cover or share the cost of the
 basic system.
      Impacts on water rates from large capital programs or unexpected emergencies can
 be lessened by careful,  long term planning.  Many water systems wait too long before
 increasing user  service  charges because they fear adverse customer reaction. A good
 public education program  explaining  all costs  and benefits,  together with citizen
 involvement  in water supply, can help to prevent any adverse  reaction.  Planning for
 capital improvements, establishing an emergency reserve fund, and increasing rates slowly
 to meet the financial obligations for improvements can ease the public reaction, and show
 good management practices.

 PERSONAL COMPUTERS
      Personal computers are gaining wider use for maintaining operational and financial
 records for  small  water  systems.   Uses include  maintaining water pumpage and
 consumption records, producing  reports for  regulatory agencies, processing  bills,
 maintaining preventive maintenance program schedules, and calculating revenue needs to
 cover debt service. Accounting records can also be used for determining returns on equity
 investment for building reserves or  returned  earnings, and paying  dividends when
 appropriate.
      Special software packages are available through AWWA and other water industry
information sources which are fairly simple to use for many of the uses listed and can save
 time and money.  The  record maintained by a  personal computer is very useful  for
preparing reports, evaluating system performance and long-term planning.

INSTITUTIONAL ALTERNATIVES
     A small, self-contained water system may not have the resources needed to ensure
a reliable supply of high quality drinking water in a cost effective manner. As institutional
                                                                             157

-------
alternatives to independent small water systems, the following organizational structures
may be considered:

       -   Satellites
           Water districts
           Regionalization
           County utilities
           State utilities
           Contract services

      An institutional alternative is an organizational structure or procedure that better
provides the resources needed to help small water systems provide reliable water service
at the lowest possible cost to the consumer.  Such resources may include the following:

           Financial
           Legal
           Planning
           Engineering
           Accounting and Collection Services
           Laboratory Support
           Licensed Operators
           Training
           Purchasing
           Supply of Spare Parts
            Consultation on Design
           Treatment and Water  Quality Analysis
           Regulatory Liaison
           Leak Detection
            Corrosion Control
            Meter Repair Program
            Emergency Assistance

 Satellite of Larger Utilities
      A satellite operation refers to the process by which a  larger or central water utility
 assists  a small system by one or more of the following:

            Providing technical, operational,  or managerial assistance on a contract basis.
            Providing wholesale treated water with or without additional services.
            Assuming ownership, operation, and maintenance responsibility when the small
            system has a separate distribution system.

      A small system is not considered a satellite when it is physically connected to and
 owned by the larger utility.
      The success of a satellite operation is greatly dependent on the economic condition
 and resources available in the large utility and on the distance, present types of ownership,
 available finances, political structure and local statutory requirements.
 158

-------
   .   Satellite arrangements may reflect the various ownership types of the larger utilities:

           Investor Owned Systems
           Municipal Systems
           Public Service or Utility Districts
           County Utilities
       -   State Utilities
           Non-Profit Corporations
           Cooperative Associations

      Utility satellites can allow a small water system to benefit from the financial strength
of the parent utility, to obtain necessary resources, to improve water quality management
and  can help secure public funds when the parent utility is publicly owned.
Water Districts
      Water districts typically serve water to rural areas and the fringes of urban areas.
Water districts  are formed by  county or local officials (usually  upon the petition  of
citizens) under state laws, to provide one or more water systems in a selected geographical
or franchise area.  They are sometimes called public service districts, water authorities,  or
sanitary districts, depending on the state's laws.
      Forming a water district is normally a fairly easy task for county commissioners,  as
it can usually be done by their own  motion as well  as upon request from consumers.
Usually a signed petition has to be presented to force a referendum, although some states
require a public referendum prior to  setting up a district.  Water districts are attractive
to county officials as a means of providing water service in rural areas and on the fringes
of municipalities having their own systems.  They also have proven to be helpful to private
utilities that desire to expand but do not have capital.  Because public water districts can
obtain public funding,  a distribution system is often set up in which the larger, private
utility then sells water and  other services.  Water districts, along with property owner
associations, have been  quite successful  in obtaining funds from  the Farmers Home
Administration (FmHA) which is discussed in the  "Financial Assistance" section.
      Forming a water district aUows the system to be eligible for public grants and loans,
issue tax free  securities,  and help takeovers of independent, small water systems which
desire to join the public-owned water  system.  It may also contract services  with publicly
owned non-community systems and small  privately owned systems.
Regionalization
      New and existing small public water supply systems may better serve their customers
when merged into a regional system. A regional system is similar to a water district, but
is not owned or managed by a government group.  A regional system can allow its water
systems to take advantage of the economies of scale and good management that can be
achieved through larger organizations. Where it is not economically practical to physically
interconnect, the water systems  can join together  to hire a circuit rider to  help operate
theur water treatment plants, or to contract for joint managerial services.
     In general, small water systems have very poor economies of scale that  can be partly
overcome by regionalization. Sharing management and operations personnel, information
and  equipment resources can allow small water systems to be more able to  meet the
customers needs.
                                                                               159

-------
County Utilities
     County utilities are those that are owned and operated by the county (or township)
Commissioners or by county Public Works Departments.
     Putting a county utility into practice depends on the initiative of the County as well
as the willingness  of the various boards of health and  local authorities to present
complaints to the state.  Such a complaint may start the formation of a county utility to
correct unsafe water supply conditions and protect pubh'c health and welfare.
     Although they require passage of an enabling law before being put into use, county
utilities can provide central management, eligibility for public grants and loans,  and allow
troubled systems to be taken over by a more capable management organization. County
utilities are easy to start and difficult to break up.
State Utilities
     State utilities are those that  are owned  and operated by an  agency of state
government or are state agents which operate and maintain water utilities for the state on
a contractual basis. State utilities include hospitals, camps, colleges, state parks  or similar
facilities.  By providing an umbrella type organization that  offers the required  resources
they allow state government to have a major impact on small water systems.    State
utilities provide  savings through centralized  purchasing, management,  consultation,
planning  and technical  assistance.   This option can also provide  coordination with
regulatory agencies,  sharing of costs of  major  equipment,  and  a  network  of skilled
operators.
Contract Services
     Contract service is one of the most promising options for solving small water system
problems and is used more often as the SDWA provisions go into effect and  consumer
demand for a quality of service increases.
     Contract services may include all or part of the services needed by a small system
to allow it to provide good quality and quantity of water. These services could include any
one or combination of services such as financial, legal, planning, engineering, accounting
and collection, laboratory support, operations assistance, maintenance programs, training,
purchasing, supplying spare  parts,  consulting services, treatment  and  water quality
assistance, regulatory liaison, leak detection,  corrosion control, meter repair, emergency
assistance and others.
     The contract services can provide small water systems with access to  needed
resources  and help them improve water quality management through an easily used
option, however,  not all services needed may  be available through this alternative.
Professional organizations such as AWWA and NRWA, the local health departments or
State agencies may supply information on firms that provide contract services.
 160

-------
                               BIBLIOGRAPHY

               LIST OF REFERENCES ON SMALL PUBLIC WATER
                               SUPPLY SYSTEMS

 American Concrete Pressure Pipe Association, Basic Water Works Management, Arlington
     VA  (1972).                                                *      >     »   ,


 American Public Health Association, American Water Works Association, and Water
     Pollution Control Federation, Standard Methods for the Examination of Water and
     Waste Water, 17th edition, American Public Health Association. Washington, D C
     (1989).                                                           6

 American Water Works Association, Water Utility Management, American Water Works
     Association, Denver, CO (1980).

 American Water Works Association, AWWA Seminar Proceedings, Small Water System
     Problems, American Water Works Association, Denver, CO  (1982).

 American Water Works Association Research Foundation, Institutional Alternatives for
     Small Water Systems, Denver, CO  (1986).

 American Water Works Association, AWWA Seminar Proceedings, Membrane Processes:
     Principles and Practices, Denver, CO (1988).

 American Water Works Association, New Dimensions in Safe Drinking Water 2nd edition,
     American Water Works Association, Denver,  CO  (1988).

 American Water Works Association, Water  Quality and Treatment, 4th edition, McGraw-
     Hill, New York, NY  (1990).

 American Water Works Association and American Society  of Civil Engineers, Water
     Treatment Plant Design, 2nd edition, McGraw-Hill, New York, NY  (1990).

Anderson, Keith E., Water Well Handbook,  Missouri Water Well and Pump Contractors
    Association, Rolla,  MO  (1971).

Baker, R.J., Carroll, L.J., and Laubusch,  E.J., Water Chlorination Handbook, American
    Water Works Association, New York, NY (1972).

Campbell, Stu, The Home Water Supply, Garden Way Publishing, Pownal, VT  (1983).

Capitol Controls Co., "Chlorination Guide." Capitol Controls Co., Colmar, PA  (undated).

Chang, S.L., "lodination of Water," Boletin de la Oficina Sanitaria Panamericana, Vol. 59,
    Pages 317-331  (1966).
                                                                            161

-------
Cotruvo, J. A. , Perler, A. H., and Bathija, B. L., "Drinking Water Analysis Regulatory
    Report", Environmental Lab, Pages 22-27 (1989).

DeMers, L. D., Hanson, B. D., Glick, F. L., and Schultz, R. M., "Design Considerations
    for Package Water Treatment Systems", Journal of The American Water Works
    Association, Vol. 80, No. 8, Pages 58-61  (1988).

Ficlk, K. J., "New Ozone System Designed Specifically for Small Systems", Waterworld
    News, Vol. 6, No. 2, Pages 18-19 (1990).

French, W., and Ytell, E., "Rural  Community Assistance Program", Journal of the
    American Water Works Association, Vol. 80, No. 9, Pages 4-8-51 (1988).

Gollnitz, William D., "Source Protection and The Small Utility", Journal of The American
    Water Works Association, Vol. 80,  No. 8, Pages 52-57  (1988).

Gumerman, R. C., Burris, B. E., and Hanson, S. P., Small Water System Treatment Cost,
    Noyes Data Corporation, Park Ridge, NJ (1986).

Hill,  R.D., and Schwab, G.O., "Pressurized Filter  for  Pond  Water Treatment."
    Transactions of the ASAE,  Vol. 7,  No.4,  Pages 370-374, 379, American Society of
    Agricultural Engineers, St. Joseph,  MI  (1964).

Hooker, Dan, "How to Protect the Submersible Pump from Lightning Surge Damage,"
    Bulletin DPED-27, General Electric Co., Pittsfield, MA (1969).

Kroehler, C. J., "Underground Injection Control in Virginia", Virginia Water Resources
    Research Center, Virginia Polytechnic Institute and State University, Blacksburg, VA
    (1989).

Kroehler,  C.J., What Do TJie Standards Mean?,  Virginia Water Resources Research
    Center, Virginia Polytechnic Institute and State University,  Blacksburg, VA (1990).

Long, B.  W., and Stukenberg,  J. R.,  "SDWA Amendments:   Small  Community
    Compliance", Journal of the  American Water Works  Association, Vol. 80, No. 8.,
    Pages 38-39  (1988).

Midwest Plan Service, Private Water Systems Handbook, Iowa State University, Ames, IA
    (1979).

Miller, G. W., Cromwell HI, J. E., and Marrocco, F. A., "The Role of the States in Solving
    the Small System  Dilemna", Journal of the American Water Works Association,
    Vol. 80, No. 8, Pages 32-37 (1988).
 162

-------
National Association of Plumbing, Heating, and Cooling Contractors, National Standard
    Plumbing Code, National Association of Plumbing, Heating, and Cooling Contractors,
    Washington, D.C.  (1971).

National Fire Protection Association, "Water Supply Systems for Rural Fire Protection,"
    National Fire Codes, Vol. 8, Boston, MA  (1969).

National Sanitation Foundation Testing Laboratory, Seal of Approval Listing of Plastic
    Materials,  Pipe,  Fittings and Appurtenances for Potable Water  and Waste  Water,
    National Sanitation Foundation, Ann Arbor, MI (revised annually).

National Water Well Association, "The Authoritative Primer:  Ground Water Pollution,"
    Water Well Journal, Special Issue, Vol. 24, No. 7 (1970).

New York State Department of Health, Training Manual for Water Distribution Operations
    Grade D, Bureau of Public Water Supply Protection (undated).

Okun, D. A., and Ernst, W. R., Community Piped Water Supply Systems in Developing
    Counties.  The World Bank, Washington, D.C. (1987).

Olin Corporation, "Hypochlorination of Water," Olin Corporation - Chemicals Division,
    New York, NY  (1962).

Renner, R. C., "Survival Tactics for Small Systems", Waterworld News, Vol. 6, No. 2,
    Pages 10-12  (1990).

Sagraves, B. R.,  Peterson, J. H., and Williams, P. C., "Financing Strategies for Small
    Systems",  Journal of the American  Water  Works  Association, Vol. 80, No. 8,
    Pages 40-43  (1988).

Salvato, JA., The Design of Small Water Systems, New York State Department of Health,
    Health Education Service, Albany, NY (1983).

Scharfenaker, Mark A., "AWWA Small Systems Program", Journal of the American Water
    Works Association, Vol. 80, No. 8, Pages 44-47 (1988).

Smalley, G., "Networking: A Weapon  for Small Systems", Waterworld News, Vol. 6,
    No. 2., Pages 14-15  (1990).

Sykes, R. G.,  and Doty, R. N., "The New Regulations - A Challenge for Small Systems",
    Journal of the American Water Works  Association,  Vol. 80, No. 8, Pages 62-64
     (1988).

Tardiff, R.D., and McCabe, L.J., "Rural Water  Quality Problems and the Need for
     Improvement," Second Water Quality Seminar Proceedings, Pages 344-36, American
     Society of Agricultural Engineers, St. Joseph,  MI  (1968).
                                                                              163

-------
 Toft, P., Tobin, R. S., and Sharp. J., "Drinking Water Treatment Small System Alternatives,
     Pergamon Press, Elmsford, NY (1989).

 U.O.P. Johnson Division, Ground Water and Wells, U.O.P. Johnson Division St Paul MN
     (1972).

 U.S. Agency for International Development, WASH Technical Report No. 61, "Pump
     Selection: A Field Guide for Developing Counties", Water and Sanitation for Health
     Project, Washington, D.C.  (1989).

 U.S. Congress, Office of Technology Assessment, "Using Desalination Technologies for
     Water Treatment", U.S. Government Printing Office, Washington, D.C.  (1988).

 U.S. Department of Health and Human Services, Centers for Disease Control, "Water
     Fluoridation", Atlanta, GA  (1986).
                                                                    i
 U.S. Department of Health and Human Services, Indian  Health Service, "Nationwide
     Indian Health Service Federal Photovoltaic Utilization Program", Washington  D C
     (1990).                                                              '

 U.S. Department of the Interior, Geological Survey, "A Primer on Ground Water," U.S.
     Government Printing Office, Washington, D.C. (Reprinted annually).

 U.S.EnvironmentalProtectionAgency,"FluoridationEngmeering Manual," Environmental
     Protection Agency, Water Supply Division, Washington, D.C. (1972).

 U.S. Environmental  Protection  Agency, Manual of Water Well Construction  Practices,
    Environmental Protection Agency, Water Supply Division, Washington, D.C. (1977).

 U.S. Environmental Protection Agency, Cross-Connection Control Manual, Environmental
    Protection Agency, Office of Water, Washington, D.C.  (1989).

 U.S. Environmental  Protection  Agency, "Guidance Manual for Compliance  with The
    Filtration  and Disinfection Requirements for Public Water Systems Using Surface
    Water Sources", Environmental Protection Agency,  Office of Drinking Water
    Washington, D.C.  (1989).

 U.S. Environmental Protection Agency, "Fact Sheet on Home Drinking Water Treatment",
    Environmental Protection Agency, Office  of Water, Washington, D.C.  (1989).

U.S. Environmental Protection Agency, "Self Assessment for Small Publicly Owned Water
    Systems", Environmental  Protection Agency, Office of Water, Washington  D C
    (1989).
164

-------
 U,S. Environmental Protection Agency, "A Water and Wastewater Manager's Guide for
    Staying Financially Healthy", Environmental Protection Agency, Office of Water,
    Washington, B.C. (1989).

 U.S. Environmental Protection Agency,  "Environmental Pollution Control Alternatives:
    Drinking Water Treatment for Small Water Treatment Facilities", Environmental
    Protection Agency, CERI, Cincinnati, OH (1990).

 U. S. Environmental Protection Agency,  Technologies for Upgrading Existing or Designing
    New Drinking Water Treatment Facilities, Environmental Protection Agency, Office of
    Drinking Water, Cincinnati, OH (1990).

 U.S. Environmental Protection Agency, "Fact Sheet, Drinking Water Regulations Under
    the Safe Drinking Water Act", Environmental Protection  Agency,  Criteria and
    Standards Division, Office of Drinking Water, Washington, D.C. (1990).

 Water Systems Council, Water Systems Handbook,  6th edition, Water Systems Council
    Chicago, IL (1977).

 Whitsell, W.J., and Hutchinson, G.D., "Seven Danger Signals for Individual Water Supply
    Systems," Transactions of the American Society of Agricultural Engineers,   American
    Society of Agricultural Engineers, St. Joseph, MI (1990).

 World Health Organization, Guidelines for Drinking Water Quality:  Vol. 3 -Drinking Water
    Quality Control in Small Community Supplies, Geneva, Switzerland (1985).

 World Health Organization, Technical Paper Series (TP 23), Renewable Energy Sources
    for Rural Water Supply, WHO Collaborating Centre, The Hague, The Netherlands
    (1986).

 World Health Organization, Technical Paper Series, Slow Sand Filtration for Community
    Water Supply, WHO Collaborating Center, The Hague, The Netherlands  (1987).

World Health Organization, Technical Paper Series (TP  18), Small Community Water
    Suppliers; Technology of Small Water Supply Systems in Developing Countries, WHO
    Collaborating Center,  The Hague, The Netherlands, (1987).

World Health Organization, Disinfection  of Rural and Small Community Water Supplies,
    Copenhagen, Denmark (1989).

Wright, F. B.,  Rural  Water Supply  and Sanitation,  3rd edition, Robert  E. Krieger
    Publishing Company, Huntington, NY (1977).
                                                                             165

-------

-------
                                APPENDIX A

               Health Effects, Source of Contaminants, and Treatment
Contaminant

Arsenic


Asbestos


Barium



Cadmium



Chromium


Fluoride

Lead




Mercury




Nitrate


Nitrite


Radioactivity
Health Effects

Carcinogenic


Benign tumors
Circulatory system
effects
Kidney effects
Gastrointestinal
effects

Crippling Fluorosis

Gastrointestinal
distress, fatigue,
anemia, paralysis, and
brain damage

Kidney effects
Methemoglobinemia
("blue baby" syndrome)

Methemoglobinemia
("blue baby" syndrome)

Bone cancer
 Contaminant Sources

Geological, pesticides,
pressure treated wood

Geological, asbestos-
cement pipe

Geological, oil and gas
exploration and
production

Geological, mining,
smelting, and corrosion
of galvanized pipe

Geological, faucets
Geological, mining

Geological, lead service
lines, solder and brass
faucets
Used in manufacture
of paint, paper, vinyl
chloride; used in
fungicides; geological

Fertilizer, sewage,
feedlots

Fertilizer, sewage,
feedlots

Geological, mining.,
hospital and nuclear
waste
                                                                              167

-------
Contaminant

Selenium.


Total Trihalomethanes
Turbidity
Health Effects

Neurological effects


Carcinogenic
Adverse health effects
from harbored or
shielded bacteria
Contaminant Sources

Geological, mining,
pesticides

Chlorination of
drinking water,
bleached paper
wastewaters organic
chemical industry

Participate from soil,
organisms and biomass
Benzene

cis-1,2-
Dichloroethylene
1,2-Dichloropropane


Ethylbenzene

Monochlorobenzene



o-Dichlorobenzene


Styrene



Tetrachloroethylene

Toluene
  Organics (Solvents)

Carcinogenic

Nervous system, liver,
kidney
Liver toxin, lung, and
kidney effects

Liver, kidney effects

Respiratory, nervous
system, liver, kidney
effects

Nervous system, lung,
liver, kidney effects

Possible cancer, liver,
central nervous system
effects

Probable cancer

Nervous system, lung,
liver effects
Solvent

Extraction solvent,
dyes, perfumes,
Pharmaceuticals,
lacquers

Pesticide, solvent
Manufacture of styrene

Solvent, pesticide
Industrial solvent,
pesticide

Manufacture of
polystyrene, plastic
Dry-cleaning solvent

Solvent
168

-------
 Contaminant
  Health Effects
  Contaminant Sources
 trans-1,2
 Dichloroethylene
Xylenes (total)
Alachlor

Aldicarb



Aldicarb sulfone



Aldicarb sulfoxide



Atrazine


Carbofuran


Chlordane
Dibronochloro-propane
(DBCP)

2,4-D

Endrin
  Nervous system, liver,
  kidney effects
  Central nervous system
  effects
Pesticides/Herbicides/PCBs

  Probable cancer

  Nervous system toxicity



  Nervous system toxicity



  Nervous system toxicity
 Nervous system, liver,
 heart effects

 Nervous system,
 reproductive effects

 Nervous system, liver
 effects
 Probable cancer


 Liver, kidney effects

 Probable cancer
 Extraction solvent,
 dyes, perfumes,
 Pharmaceuticals,
 lacquers

 Solvent; used to
 manufacture paint,
 dyes, adhesives,
 detergents
Herbicide

Pesticide, herbicide,
restricted in some
areas

Pesticide, herbicide,
restricted in some
areas

Pesticide, herbicide,
restricted in some
areas

Herbicide
Pesticide, herbicide


Pesticide, herbicide,
most uses banned in
1980

Pesticide, canceled in
1977

Herbicide

Insecticide
                                                                                169

-------
Contaminant

Ethylenedibromide
(EDB)
Heptachlor


Heptachlor ep oxide


Lindane



Methoxychlor


PCBs



Pentachlorophenol



Toxaphene



2,4,5-TP (SUvex)
Health Effects

Probable cancer




Probable cancer


Probable cancer
Neurological, liver,
kidney effects
Central nervous system
effects

Probable cancer,
reproductive effects
 Organ, central nervous
 system, fetal effects
 Probable cancer
 Liver, kidney effects
Contaminant Sources

Gasoline additive, soil
fumigant, solvent, most
pesticide uses restricted
in 1984

Insecticide, most uses
restricted in 1983

Insecticide, most uses
restricted in 1983

Insecticide to control
fleas, lice, ticks, some
uses restricted in 1983

Insecticide
Transformers,
capacitors; production
banned in 1977

Wood preservative;
nonwood uses banned
in 1987

Pesticide, herbicide,
most uses canceled in
1977

Herbicide, canceled in
1983
 170

-------
                             Best Treatment Methods
  Organic
  Chemicals
 Acrylamide
 Alachlor
 Aldicarb
 Aldicarb sulfone
 Aldicarb sulfoxide
 Atrazine
 Carbofuran
 Calordane
 2,4-D
 Dibromochloropropane (DBCP)
 o-Dichlorobenzene
 c/j-l,2-Dichloroethylene
Epichlorohydrin
Ethylene dibromide (EDB)
Ethylbenzene
Heptachlor
Heptachlor epoxide
Lindane
Methoxychlor
Monochlorobenzene
PCBs
Pentachlorophenol
Styrene
2,4,5-TP (Silvex)
Tetrachloroethylene
Toluene
Toxaphene
Xylenes (Total)
Granular
Activated
 Carbon
    x
    x
    X
    X
    X
    X
    X
    X
    X
    X
    X
    X

    X
    X
    X
    X
    X
    X
    X
    X
    X
    X
    X
    X
    X
    X
   X
 Packed
 Tower
Aeration
     X
     X
     X
     X

     X
     X
     X
     X
Polymer
Addition
                                                                            171

-------
     Inorganic
     Chemicals
     Arsenic
     Asbestos
     Barium
      Cadmium
      Chromium
      Fluoride


      Mercury




      Nitrate/Nitrite


      Selenium
 Best
Treatment
 Methods
Activated Aluminum
Coagulation/Filtration
Lime Softening
Reverse Osmosis

Coagulation/Filtration
Corrosion Control
Direct and Diatomite Filtration

Ion Exchange
Lime Softening
Reverse Osmosis

Coagulation/Filtration
Ion Exchange
Lime Softening
Reverse Osmosis

Coagulation/Filtration
Ion Exchange (Cation or Anion
Depending on Form)
Lime Softening (Chromium III Only)
Reverse Osmosis

Activated Alumina
 Reverse Osmosis
     '
 Coagulation/Filtration
 Granular Activated Carbon
 Lime Softening
 Reverse Osmosis

 Ion Exchange
 Reverse Osmosis
                      i
 Activated Alumina
 Coagulation/Filtration (Selenium IV
 Only)
 Lime Softening
 Reverse Osmosis
172

-------
Radioactive
 Chemicals
Radium
Radon
Uranium
Gross Beta
Treatment
 Method
Ion Exchange
Lime Softening
Oxidation/Filtration
Reverse Osmosis

Aeration
Granular Activated Carbon

Coagulation/Filtration
Ion Exchange (Anion or Cation
Depending on pH)
Lime Softening
Reverse Osmosis

Ion Exchange
Reverse Osmosis.
Microorganisms

Giardia Lamblia


Bacteria


Viruses
Treatment
Method

Disinfection
Filtration

Disinfection
Filtration

Disinfection
Filtration
                                                                     173

-------

-------
                                 APPENDIX B

                  Collection and Analysis of Bacteriological Samples

 SAMPLING
   Water samples must be collected carefully  to prevent contamination.  The collector
 should follow these steps:

   1. Use a sterile sample bottle or other container provided by the laboratory that will
     examine the sample.
   2. Insure that water taps used for sampling  are  free  of  aerators,  strainers, hose
     attachments, mixing type faucets, and purification devices.
   3. Inspect the outside of the faucet. If water leaks around the outside of the faucet,
     select a different sampling site.
   4. Allow the water to run for enough time (about two minutes) to clear the service line
     before sampling.
   5. When filling the bottle, hold bottle so that no water which contacts the hands runs
     into the bottle. Cap the bottle tightly.
   6. Deliver the sample immediately to the laboratory.  If possible, store the sample in
     an iced cooler during transport. In no case should the time between collection and
     analysis exceed 30 hours. It may be necessary to  send a water sample by overnight
     mail service.

   Under EPA's total conform rule, all water samples must be  collected  from the
 distribution system (e.g., household tap),  rather than from the well or other location.

 ANALYSIS FOR TOTAL COLIFORMS
   As stated in Part I of this manual, total coliforms are used to show whether a water
 supply is contaminated with,  or vulnerable to, fecal pollution.  EPA is approving four
 analytical methods for testing  water in distribution systems to determine whether total
 coliforms are present.   These  are  the  Membrane Filter Technique,  Multiple-Tube
 Fermentation Technique, Presence-Absence Conform Test, and the Mixed Media ONPG-
 MUG test.  In all cases, 100-ml water samples are tested; therefore the sample collector
 must provide  at least 100 ml to the laboratory.  All  microbiology samples which are
 collected to satisfy the drinking water regulations must be analyzed in a laboratory which
 is certified by EPA or the State.
   In the Membrane Filter Technique, a vacuum pulls 100 ml of water sample through a
 membrane filter held in place by a filter-holding device.  Total conform and other bacteria
 are retained on the filter. The filter is then placed on a special medium which allows the
 growth of total coliform, and incubated at  35°C for 22 to 24 hours. If a total coliform-like
 colony(ies) is observed on the membrane, the laboratory should make sure that it is a total
 conform by using another EPA-approved  test.
   The Multiple Tube Fermentation Technique involves adding the water sample to either
 a bottle or a set of tubes, each of which  contains either  lactose broth or lauryl typtose
broth and an inverted tube. The bottle or tubes are then incubated at 35°C for 24 to 48
hours.   If gas production is observed  in  an inverted tube after incubation,  the sample
                                                                             175

-------
contains total coliforms. This is confirmed by adding a small volume of culture from the
positive tube(s) or bottle into a tube containing brilliant green lactose bile (BGLB) broth
and a smaller inverted tube. After incubating for the tube containing BGLB broth for 48
hours, the inverted tube is observed for gas production.  Gas production confirms the
presence of total coliforms.
  In the Presence-Absence Coliform Test, 100 ml of the water sample is added to a bottle
containing P-A Broth, and incubated at 35°C for 24 to 48 hours.  If the broth becomes
yellow-colored, total coliforms are present.  This is confirmed in BGLB broth.
  The Mixed Media  ONPG-MUG  (MMO-MUG)  test  is  the  simplest  of  the
EPA-approved tests for total  conforms.  A 100 ml water sample is added to a bottle or
flask containing the MMO-MUG powder, mixed, and incubated at 35°C for 24 hours. The
formation of a yellow color denotes the presence of total conforms.
  If a laboratory finds that a high level of non-coliform bacteria are obscuring the total
coliform test, it must not use the sample (unless total conforms are present), and request
that the system collect another sample within 24 hours from the same location as the
original sample, and have it analyzed for total coliforms.
  Under the  total coliform  rule,  the laboratory must test all total coliform-positive
samples for the presence of either fecal coliform or E. coli.  The analytical methods for
these bacteria are described elsewhere.

SURFACE WATER  ANALYSIS                                     j
  Under EPA's surface water treatment requirements, a public system using unfiltered
surface water must monitor its source water  quality.  Unlike the total coliform rule, which
requires the system to determine only whether total coliform is present  or absent in a
sample, this rule requires systems to determine the level  of  total  coliforms or fecal
coliforms in a sample.  For counting of total coliforms, EPA has approved the 5-tube or
10-tube Multiple Tube Fermentation Technique, the Membrane Filter Technique, and the
5-tube MMO-MUG test.   For counting fecal coliforms, EPA  has approved the Fecal
Coliform Membrane Filter Procedure and the Fecal Conform Test (EC Medium or A-1
Medium).
  The surface water treatment rule also allows a  system to determine the  amount of
heterotrophic bacteria at a site within the distribution system, if the system does not find
a disinfectant residual at that site. If the concentration does not exceed 500  bacterial
colonies  per ml, then the system is considered to have a disinfectant residual for legal
purposes. The level of heterotrophic bacteria is determined by the Pour  Plate Method,
which involves transferring a small volume of water sample to a sterile petri dish, and
mixing it with a warm nutrient which solidifies below 45°C. This medium is incubated for
48 hours at 35°C and the number of bacterial colonies counted.
  Most  of  the above-cited methods  are described in the 17th Edition of "Standard
Methods for the Examination of Water and Wastewater" (1988).
 176

-------
                                APPENDIX C
  IMPURITY OR
 CONTAMINANT

Hard Water
Grittiness
                         Identification By Human Senses1

                            A.  SENSE OF FEELING
    SYMPTOM

 Soap curd, and
 scum in wash
 basins & bathtub.
 Whitish scale
 deposits in pipes,
 water heater & tea
 kettle.

 Abrasive texture to
 water when
 washing or residual
 left in sink.
                                         Calcium
                                         (limestone) and
                                         magnesium salts.
                                         Excessively fine
                                         sand, silt in water.
                        MEANS OF
                       TREATMENT

                     Cation exchange
                     water softener.
                     Sand trap in ultra-
                     filtration.
                             B. SENSE OF SMELL
  IMPURITY OR
 CONTAMINANT

Odor
    SYMPTOM

Musty, earthy or
wood smell.
                    Chlorine smell.
Generally,
harmless organic
matter.

Excessive
chlorination.
   MEANS OF
  TREATMENT

Activated carbon
filter.
                                                             Dechlorinate with
                                                             activated carbon
                                                             filter.
      This infonnation has been taken principally from a paper titled "Sensitivity:  A Key Water
      Conditioning Skill"  by Wes McGowan.  The paper was published in Water Technology
      September/October 1982.
                                                                           177

-------
 IMPURITY OR
CONTAMINANT
   SYMPTOM

Rotten egg odor
tarnished
silverware.
                    Hot water, rotten
                    egg odor.
                    Detergent odor,
                    water foams when
                    drawn.
                     Gasoline or oil
                     (hydro-carbon)
                     smell.
                     Methane gas.
                                        1. Dissolved
                                        hydrogen sulfide
                                        gas.
                                        2. Presence of
                                        sulfate reducing
                                        bacteria in raw
                                        water.
                     Action of
                     magnesium rod in
                     hot water heater.

                     Seepage of septic
                     discharge into
                     underground water
                     supply.
                     Lack in fuel oil
                     tank or gasoline
                     tank seeping into
                     water supply.

                     Naturally occurring
                     caused by decaying
                     organics.
   MEANS OF
  TREATMENT

Manganese
greensand filter -
constant
chlorination
followed by
filtration/
dechlorination.

Constant
chlorination
followed by
activated carbon
filter.

Remove
magnesium rod
from heater.

1. Locate and
eliminate source of
seepage - then
heavily chlorinate
well.

2. Activated
 carbon filter will
 adsorb limited
 amount.

 No residential
 treatment. Locate
 and eliminate
 seepage.

 Aeration system
 and repump.
 178

-------
  IMPURITY OR
 CO3STTAMINANT
   SYMPTOM
                                              CAUSE
   MEANS OF
  TREATMENT
                    Phenol smell
                    (chemical odor).
                    Industrial waste
                    seeping into
                    surface or ground
                    well supplies.
Activated carbon
filter will adsorb
short-term.
                             C. SENSE OF TASTE
  IMPURITY OR
 CONTAMINANT

Taste
   SYMPTOM
Salty of brackish     High sodium
                    content
                    Alkali taste
                    Metallic taste
                    High dissolved
                    mineral containing
                    alkalinity.  (Stained
                    aluminum
                    cookware.)

                    1. Very low pH
                    water (3.0-5.5).

                    2. Heavy iron
                    concentration in
                    water above 3.0
                    ppm Fe.
   MEANS OF
  TREATMENT

1. Deionize
drinking water only
with disposable
mixed bed -
anion/cation
resins; or

2. Reverse
osmosis; or

3. Home
distillation system.

1. Reduce by
reverse osmosis.
1. Correct with
calcite type filter
(see Acid Water).

2. (See Iron
Water).
                                                                           179

-------
                              D.  SENSE OF SIGHT
  IMPURITY OR
 CONTAMINANT

Turbidity
   SYMPTOM

Dirt, salt, clay
                     Sand grit, silt or
                     clay substances
                     Rust in water
                     Grey string-like
                     fiber
Acid Water
Green stains on
sinks and silver
porcelain
bathroom fixtures.
Blue-green cast to
water.
Suspended matter
in surface water
pond, stream or
lake.

Well sand from
new well or
defective well
screen.

Acid water causing
iron "pick-up".
                     Organic mater in
                     raw water algae,
                     etc.
Water which has
high carbon
dioxide content
(pH below 6.8)
reacting with brass
and copper pipes
and fittings.
   MEANS OF
  TREATMENT

"Calcite" or
Neutralite (media)
type filter - up to
50 ppm

Sand trap and/or
new well screen
Neutralizing calcite
filter to correct low
pH acidity and
remove
precipitated iron

Constant
chlorination
followed by
activated carbon
filter to
dechlorinate

1. Neutralizing
calcite filter down
to pH of 5.5, or

2. Calcite/
Magnesia - oxide
mix (5 to  1) for
higher flow rate
and to correct very
low pll water.
                                                               3.  Soda ash
                                                               chemical feed
                                                               followed by
                                                               filtration.
 180

-------
  IMPURITY OR
 CONTAMINANT

Discolored water
red, "Iron" water
    SYMPTOM

Brown-red stains
on sinks and other
porcelain
bathroom fixtures.
Water turns
brown-red in
cooking or upon
heating. Clothing
becomes
discolored.
1. Dissolved iron
in influent (more
than 0.3 ppm Fe+)
water appears
clear when first
drawn at cold
water faucet.
Above 0.3 ppm Fe
causes sfaining.
                                        2. Precipitate iron
                                        (water not clear
                                        when drawn).
    MEANS OF
   TREATMENT

 1.  Can remove 0.5
 ppm of Fe+ for
 every grain/gal, of
 hardness to 10
 ppm with water
 softener and
 minimum pH of
 6.7.

 2.  Over 10 ppm
 Fe+  chlorination
 with sufficient
 retention tank time
 for full oxidation
 followed by
 filtration/
 dechlorination.

 3. In warm
 climates residential
 aerator and
 filtration will
 substantially
 reduce iron
 content.

 1. Up to 10 ppm
 iron removed by
 Manganese
 Greensand filter, if
 pH 6.7 or higher,
 or

 2. Manganese
 treated, non-
 hydrous aluminum
 silicate filter where
 pH of 6.8 or
 higher and oxygen
 is 15% of total
iron content.
                                                                          181

-------
 IMPURITY OR
CONTAMINANT
SYMPTOM
                    Brownish cast does
                    not precipitate.
                 Iron pick-up from
                 old pipe with water
                 having a pH below
                 6.8.1. Organic
                 (bacterial) iron.
                     Reddish color in
                     water sample after
                     standing 24 hours.
                  Colloidal iron.
   MEANS OF
  TREATMENT

3.  Downflow
water softener with
good backwash, up
to 1.0 ppm Fe.
Above 1 ppm to 10
ppm use calcite
filter followed by
downflow water
softener.

Calcite media type
filter to remove
precipitated iron.

1. Treat well to
destroy iron
bacteria with
solution of
hydrochloric acid
then constant
chlorination
followed by
activated  carbon
media filtration
and dechlorin-
ation.

2.  Potassium
permanganate
chemical  feed
followed by
filtration.

 Constant
 chlorination
 followed  by
 activated carbon
 media filter
 dechiorination.
182

-------
  IMPURITY OR
 CONTAMINANT
    SYMPTOM
                                               CAUSE
                         MEANS OF
                       TREATMENT
Yellow water
Yellowish cast to
water after
softening and/or
filtering.
Milky water
Cloudiness of
water when drawn.
Very high chloride
content in water
Blackening and
pitting of stainless
steel sinks and
stainless ware in
commercial
dishwashers.
1. Tannins (humic
acids) in water
from peaty soil and
decaying
vegetation.
1. Some
precipitant sludge
created during
heating of water.
2. High degree of
air in water from
poorly functioning
pump.

3. Excessive
coagulant-feed
being carried
through filter.

1. Excessive  salt
content.

2. High
temperature drying
creates chloride
concentration
accelerating
corrosion.
1. Adsorption via
special macro-
porous Type I
anion exchange
resin regenerated
with salt (NaCl)
up to 3.0 ppm.

2. Manganese
greensand or
manganese treated
sodium alumino-
silicate under
proper set of
conditions.

1. Blow down
domestic or
commercial hot
water heater tank
periodically.

2. Water will
usually clear
quickly upon
standing.

3. Reduce
coagulant quantity
being fed, service
filters properly.

1. Use other
chloride resistant
metals.

2. Reduce T.D.S.
by reverse osmosis.
                                                                             183

-------
                            E.  SENSE OF HEARING
  IMPURITY OR
 CONTAMINANT

Excess Fluorides
 Nitrates
   SYMPTOM

Yellowish mottled
teeth of children.
(No visible color,
taste, or odor of
water.)
 1. No visible
 color, taste, or
 odor of water
 (above 10.0 ppm as
 N considered
 health hazard for
 infants).

 2. Rotten egg or
 sewage smell -
 water foams.
F-above 1.0 ppm in
natural water
supply.
 1. Heavy use
 commercial
 fertilizers with
 residual NO3
 getting into
 underground water
 supply.

 2. Boiler
 blowdown of
 corrosion inhibitors
 containing nitrates
 entering surface or
 underground water
 supplies.
   MEANS OF
  TREATMENT

1.  Adsorb excess
fluoride and
reduce to 0.2 ppm
with activated
alumina media
type filter, or

2.  Home
distillation system
for drpking and
cooking water, or

3.  Remove F- by
complete water
deionization via
disposable mixed
bed for drinking
water only.

1.  On water less
than 3 ppm,
remove with strong
base Type II anion
exchanger,
regenerated with
NaCl.  Get public
health analysis.

2.  For drinking
and cooking water
only; reverse
osmosis. Limit of
nitrate influent to
25 ppm as N, or

3.  Home
 distillation system
for drinking and
 cooking water.
 184

-------
  IMPURITY OR
  CONTAMINANT
    SYMPTOM
                                          Human or animal
                                          waste pollution
                                          containing
                                          ammonia seepage
                                          in water supplies.
                         MEANS OF
                        TREATMENT

                      4.  Eliminate
                      pollution condition.
                      Sterilize well for 24
                      hours and have
                      public health
                      analysis.
Radioactive
Contaminants
Notices by public
health.  No color,
taste or odor.
Heavy Metals lead,
zinc, copper
cadmium
No visible color,
taste, or odor of
water.
Atmospheric
fallout
contamination of
surface water
supply sources; or
stray isotopes
getting in water
supply from
nuclear wastes.
Naturally occurring
in deep wells.
Radon gas given
off by decaying
radium, dissolved
in water.
1. Industrial waste
pollution.

2. Corrosion
products from
piping caused by
low pH waters.
 1.  Can remove
 most all cationic
 radioactivity with
 residential cation
 exchange water
 softener.

 2.  For complete
 treating assuring
 removal of both
 anionic and
 cationic radioactive
 contaminants treat
 with mixed bed
 deionizer.

 3.  Reverse
 osmosis.

 GAC and aeration
 are effective in
 removing radon
 from water.

 1. Reverse
 Osmosis for
 drinking and
cooking water, or

2. Complete
removal via
disposable mixed
                                                                             185

-------
 IMPURITY OR
 CONTAMINANT
   SYMPTOM
Arsenic
Barium
 Boron
No visible color,
taste, or odor of
water. Usually a
public health
matter.
No visible color,
taste, or odor of
water. Usually a
public health
matter (above 1.0
ppm considered
health risk).
 Distorted potted
 plants and
 chrysanthemums
 (above 1.0 ppm
 considered
 undesirable).
1.  Natural
groundwater
contaminant in
local areas.

2.  Industrial waste
contaminating
water supply.

3.  Herbicides
containing arsenic.
Naturally occurring
in certain
geographic regions.
 Naturally occurring
 in southwest and
 other areas.
   MEANS OF
  TREATMENT

bed deionizer for
drinking water.

3. Water softener
will remove Cu,  Cd
& Zn under
proper conditions -
counter current
brining suggested.

1. Reverse
osmosis will
remove up to 90
percent for
drinking water.

2. Remove arsenic
by complete water
deionization using
disposable mixed
bed; set
conductivity meter
at 256,000  for
exhaustion level for
drinkjng water.
     I
Remove by cation
exchange water
softener,
simultaneously
with calcium and
magnesium
hardness using very
strong brine
 solution.

Removal via a
 selective anion
 exchange resin.
 186

-------
  IMPURITY OR
Pesticides
Herbicides (DDT,
2, 4-D chlordane,
etc.)
Cyanide
"TCE" contamina-
tion (Trichloro-
ethylene)
    SYMPTOM

Sharp chemical
taste or odor in
water (can be
semitoxic).
No visible color,
taste or odor
(above 0.20 ppm
considered health
risk).
Notice from Public
Health
Department
Excessive
agricultural,
spraying and water
run off to surface
supplies.
Industrial waste
pollution from
electroplating, steel
& coking.
Waste degreasing
solution from auto
and electric motor
clean-up, getting
into surface or
underground water
supply.
    MEANS OF
   TREATMENT

Activated carbon
media filter will
adsorb limited
amount. Must
continue to
monitor treated
water.

Continuous
chlorination and
activated carbon
filtration of metals
after pH
adjustment.

Activated carbon
filters in series,
with constant
monitoring
between units for
break-through.
                                                                              187

-------

-------
                                APPENDIX D

                       Recommended Procedure for Cement
                     Grouting of Wells for Sanitary Protection2

     The annular open space on the outside of the well casing is one of the principal
avenues through which undesirable water and contamination may gain access to a well.
The most satisfactory way of eliminating this hazard is to fill the annular space with neat
cement grout. To accomplish this satisfactorily, careful attention should be given to see
that:

     1.   The grout mixture is properly prepared.
     2.   The grout material is placed in one continuous mass.
     3.   The grout material is placed upward from the  bottom of the space to  be
         grouted.

     Neat cement grout should be a mixture of cement and water in the proportion of one
bag of cement (94 pounds) and 5 to 6 gallons of clean water. Whenever possible, the
water content should be kept near the lower limit given. Hydrated lime to the extent of
10 percent of the volume of cement may be added to make the grout mix more fluid and
thereby facilitate placement by the pumping equipment. Mixing of cement or cement and
hydrated-lime with the water must be thorough.  Up to 5 percent by weight of bentonite
clay may be added to reduce shrinkage.
GROUTING PROCEDURE
     The grout mixture must be placed in one continuous mass; hence, before starting the
operation,  sufficient materials  should  be on  hand and other facilities  available  to
accomplish its placement without interruption.
     Restricted passages will result in  clogging and failure to complete the grouting
operation.  The minimum clearance at any point, including couplings, should not be less
than !1/6 inches. When grouting through the annular space, the grout pipe should not be
less than 1-inch nominal diameter.  As the grout moves upward, it picks up much loose
material such as results from caving.  Accordingly, it is desirable to  waste a suitable
quantity of the grout which first emerges from the drill hole.
     In grouting a well so that the material will move upward, there are two general
procedures that may be followed. The grout pipe may be installed within the well casing
or in the annular space between the casing and drill hole if there is sufficient clearance
to permit this. In the latter case, the grout pipe is installed in the annular space to within
a few inches of the bottom. The grout is pumped through this pipe, discharging into the
     This information has been taken principally from a pamphlet of the Wisconsin State
     Board of Health entitled "Method of Cement Grouting for Sanitary Protection of
     Wells."  The subject is discussed in greater detail in that publication.  (NOTE:
     Publication is out of print.)
                                                                            189

-------
surface. In three to seven days the grout will be set, and the well can be completed and
pumping started. A waiting period of only 24 to 36 hours is required  if quick-setting
cement is used.
     When the  grout  pipe  is installed within the  well  casing, the casing should be
supported a few inches above the bottom during grouting to permit grout  to flow into the
annular space. The well casing is fitted at the bottom with  an adapter threaded to receive
the grout  pipe and a check valve to prevent return of grout inside of the casing. After
grout appears at the surface, the casing is lowered to the bottom and the grout pipe is
unscrewed immediately and raised a few inches. A suitable quantity of water should then
be pumped through it,  thereby flushing any remaining grout from it and the casing.  The
grout pipe is then removed from the well and three to seven days are allowed for setting
of the grout.  The well is then cleared by drilling out the adapter, check valve, plug, and
grout remaining within the well.
     A modification of this procedure is the use of the well casing  itself to convey the
grout to the annular space. The casing is suspended in the drill hole and held several feet
off  the bottom.  A spacer is inserted in  the  casing.   The casing is then capped  and
connection made from it to the grout  pump. The estimated quantity of grout, including
a suitable allowance for filling of crevices and other voids, is then pumped into the casing.
The spacer moves before the grout, in turn forcing the  water in the well ahead of it.
Arriving at the lower casing terminal, the spacer is forced  to the bottom of the drill hole,
leaving sufficient clearance to permit  flow of grout into the annular space and upward
through it.
     After the desired amount of grout has been pumped into the casing, the cap is
removed and a second spacer is inserted in the casing.  The cap is then replaced and a
measured volume of water sufficient to fill  all but a few  feet  of the casing is pumped into
it.  Thus all but a small quantity of the grout is forced  from the casing into the annular
space. From three to seven days are  allowed for setting of the grout.  The spacers and
grout remaining in the casing and drill hole are then drilled out and  the well completed.
     If the annular space is to be grouted for only part of  the total depth of the well, the
grouting can be carried out  as directed above when the well reaches the desired depth,
and the well can then be drilled deeper by lowering the tools inside of the first casing.  In
this type of construction, where casings of various sizes telescope within each other, a seal
should be placed at the level where the telescoping begins,  that is, in the annular space
between the two casings. The annular space  for grouting  between two casings should
provide a  clearance of at least 1V£ inches, and the depth of the seal should be not less than
10 feet.
190

-------
                                APPENDIX E

                              Emergency Disinfection

     When ground water is not available and surface water must be used, avoid sources
containing floating material or water with a dark color or an odor.  The water tank from
a surface source should be taken from a point upstream from any inhabited area and
dipped, if possible, from below the surface.
     When the home water supply system is  interrupted by natural or other forms of
disaster, limited amounts of water may be obtained by draining the hot water tank or
melting ice cubes.
     In case of a nuclear attack, surface water should not be used for domestic purposes
unless it is first found to be free from excessive radioactive fallout. The usual emergency
treatment procedures do not remove such substances. Competent radiological monitoring
services as may be available in local areas should be relied upon for this information.
     There are two general methods by which small quantities of water can be effectively
disinfected.  One method is by boning. It is the most positive method by which water can
bef made bacterially safe to drink. Another method is chemical treatment.  If applied with
care, certain chemicals will make most waters free of harmful or pathogenic organisms.
     When emergency disinfection is necessary, the physical condition of the water must
be considered. The degree of disinfection will be reduced in water that is turbid. Turbid
or colored water should be filtered through clean cloths or allowed to settle, and the clean
water drawn off before disinfection. Water prepared for disinfection should be stored only
La clean, tightly covered, noncorrodible containers.

METHODS OF EMERGENCY  DISINFECTION
          1.  Boiling.  Vigorous  boning  for  one minute will kill any  disease-causing
             microorganisms present in water.  The flat taste of boiled water can be
             improved by pouring it back and forth from one container into another, by
             allowing it to stand for a few hours, or by adding a small pinch of salt for
             each quart of water boiled.
       ,  2. Chemical Treatment.  When boiling is not practical, chemical disinfection
             should be used.  The two chemicals commonly used are chlorine and
             iodine.
               a.  Chlorine
                 (1)  Chlorine  Bleach.    Common  household  bleach  contains a
                      chlorine compound that will disinfect water.  The procedure to
                      be followed is usually written on the label.  When the necessary
                      procedure is not given, one  should find the  percentage  of
                      available chlorine on the label and  use the information in the
                      following tabulation as a guide:
                                                                             191

-------
Avalible chlorine'
Wo
4-6%
7-10%
Drops per
quart of
clear water2
10
2
1
                    If strength is unknown, add 10 drops per quart of water.
                    Double amount for turbid or colored water.
                  The treated water should be mixed thoroughly and allowed to stand
                  for 30 minutes.  The water should have a slight chlorine odor; if not,
                  repeat the dosage and allow the water to stand for an additional 15
                  minutes. If the treated water has too strong a chlorine taste, it can be
                  made more palatable by allowing the water to stand exposed to the air
                  for a few hours or by pouring it from one clean container to another
                  several times.
         (2) Granular Calcium Hypochlorite. Add and dissolve one heaping teaspoon
                  of high-test granular calcium hypochlorite (approximately 1/4 ounce)
                  for each 2 gallons of water. This mixture will produce a stock chlorine
                  solution of approximately 500 mg/L, since the calcium hypochlorite
                  has an available chlorine equal to 70 percent  of its  weight.   To
                  disinfect water, add the chlorine solution in the ratio of one part of
                  chlorine solution to each 100 parts of water to be treated.  This is
                  roughly equal to adding 1 pint (16 oz.) of stock chlorine  solution to
                  each  12.5 gallons  of water to  be  disinfected.   To  remove any
                  objectionable chlorine odor,  aerate the water as described above.
              (3) Chlorine  Tablets.  Chlorine  tablets containing  the necessary dosage
                           for drinking  water disinfection can be purchased in  a
                           commercially prepared form.  These tablets are available
                           from drug and sporting goods stores and should be used as
                           stated in the  instructions.   When  instructions are not
                           available, use one tablet for each  quart of water to be
                           purified.
           b. Iodine
              (1) Tincture of Iodine.  Common household iodine  from the medicine
                           chest or first aid package may be used to disinfect water.
                           Add five  drops of 2 percent  United States Pharmacopeia
                           (U.S.P.) tincture of iodine to each quart of clear water. For
                           turbid water add ten drops and let the solution stand for at
                           least 30 minutes.
              (2) Iodine Tablets.  Commercially prepared iodine tablets containing the
                           necessary dosage for drinking water disinfection can be
                           purchased at drug  and sporting goods stores.  They should
                           be used as stated in the instructions. When instructions are
192

-------
                            not available, use one tablet for each quart of water to be
                            purified.

          Water to be used for drinking, cooking, making any prepared drink, or brushing
the teeth should be properly disinfected.
                                                                               193

-------

-------
                               APPENDIX F

                         State Drinking Water Agencies
          Name/Address

Water Supply Branch
Department of Environmental
 Management
1751 Federal Drive
Montgomery,  Alabama 36130

Alaska Drinking Water Program
Water Quality Management
Department of Environment
 Conservation
Pouch O
Juneau, Alaska 99811

Manager, Compliance Unit
Waste and Water Quality Management
Room 202
2005 North Central Avenue
Phoenix, Arizona 85004

Division of Engineering
Arkansas State Department of
 Health
4815 West Markham Street
Little Rock, Arizona 72201

Sanitary Engineering Branch
California Department of Health
714 P Street
Sacramento, California 95814

Drinking Water Section
Colorado, Department of Health
4210 East llth Avenue
Denver, Colorado 80220

Water Supplies Section
Connecticut Department of Health
79 Elm Street
Hartford, Connecticut 06115
         Name/Addres s

Program Director
Office of Sanitary Engineering
Division of Public Health
Jesse Cooper Memorial Building
Capital Square
Dover, Delaware 19901

Drinking Water Section
Department  of Environmental
 Regulation
2600 Blair Stone Road
Tallahassee,  Florida 32301

Program Manager
Department  of Natural Resources
270 Washington Street, SW
Atlanta, Georgia 30334

Drinking Water Program
Sanitation Branch
Environmental Protection and
 Health Services Division
P.O. Box 3378
Honolulu, Hawaii 96801

Bureau of Water Quality
Division of Environment
Idaho Department of Health and
 Welfare Statehouse
Boise, Idaho 83720

Division of Public Water Supplies
Illinois Environmental  Protection
 Agency
2200 Churchill  Road
Springfield, Illinois 62706
                                                                           195

-------
   Name and Address
   Name and Address
Water Supply Division
Department of Water, Air and
 Waste Management
Wallace State Office Building
DCS Moines, Iowa 53019

Division of Water
Department of Environmental
 Protection
18 Reilly Road, Fort Boone Plaza
Frankfort, Kentucky 40601

Support Services Section
Kansas Division of Environment
Forbes Field
Topeka, Kansas 66620

Office of Preventive and Public
 Health Services
Louisiana Department of Health
 and Human Services
P.O. Box 60630
New Orleans, Louisiana 70160

Division of Water Supply
Inspection & Compliance Program
Department of Health and Mental
 Hygiene
Office of Environmental Programs
201 West Preston Street
Baltimore, Maryland 21201

Division of Water Supply
Department of Environmental
 Quality Engineering
One Winter Street
Boston, Massachusetts 02108

Assistant Director
Department of Human Services
Bureau of Health
Division of Health Engineering
State House
Augusta, Maine 04333
Action Director
Division of Public Water Supply
Indiana State Board of Health
1330 West Michigan Street
Indianapolis, Indiana 46202

Water Supply Services Division
Environmental and Occupational
 Health Services Administration
3500 North Logan Street
Lansing, Michigan 48909

Section of Public Water Supplies
Minnesota Department of Health
717 Delaware Street
Minneapolis, Minnesota 55440

Division of Water Supply
State Board of Health
P.O. Box 1700
Jackson, Mississippi 39205

Public Drinking Water Program
Division of Environmental Quality
P.O. Box 1368
Jefferson City,  Missouri 65102

Bureau of Water Quality
Health and Environmental Services
Cogswell Building, Room A206
Helena, Montana 59620

Division of Environmental Health
 and Housing  Surveillance
Nebraska Department of Health
301 Sentenial Mall South
Lincoln, Nebraska 68509

Water Supply Division
New Hampshire Water Supply and
 Pollution Control Commission
P.O. Box 95, Hazen Drive
Concord, New  Hampshire 03301
196

-------
    Name and Address
   Name and Address
 Bureau of Potable Water
 Division of Water Resources
 New Jersey Department of
  Environmental Protection CN-029
 Trenton, New Jersey 08625

 Health Program Manager
 Water Supply Section
 Environmental Improvement Division
 P.O. Box 968
 Santa Fe, New Mexico 87504-0968

 Bureau  of Public Water Supply
  Protection
 State of New York Department of
  Health
 Office of Public Health
 Tower Building
 Nelson A. Rockefeller Empire State
  Plaza
 Albany,  New York 12237

 Water Supply Branch
 Division of Health Services
 P.O. Box 2091
 Raleigh, North Carolina 27602-2091
Division of Water Supply
  and Pollution Control
State Department of Health
1200 Missouri Avenue
Bismarck, North Dakota 58501
Office of Public Water Supply
Ohio Environmental Protection
 Agency
361 East Broad Street
P.O. Box 1049C
Columbus, Ohio 43216
 Water Facility Engineering Service
 Oklahoma State Department of
  Health
 P.O. Box 53551
 Oklahoma City, Oklahoma 73152

 Drinking Water Systems
 Department of Human Resources
 Health Division
 1400 SW 5th Avenue
 Portland, Oregon 97201

 Bureau of Water Supplies
 Department of Environmental
  Resources
 P.O. Box 2063
 Harrisburg, Pennsylvania 17120

 Drinking Water Supply Supervision
  Program
 Puerto Rico Department of Health
 P.O. Box 70184
 San Juan, Puerto Rico 00936

 Division of Water Supply
 Rhode Island Department of Health
 75 Davis Street, Health Building
 Providence, Rhode Island 02908

 Division of Water Supply
 Department of Health and
  Environmental Control
 2600 Bull Street
 Columbia, South Carolina 29201

Bureau of Drinking Water
Water and Natural Resources
Joe Foss Building
523 Capital Avenue, East
Pierre, South Dakota 57501
                                                                          197

-------
   Name and Address
     Name and Address
Bureau of Public Water Supplies
Utah State Department of Health
560 South 300 East
Salt Lake City, Utah 84111

Vermont Department of Health
60 Main Street
P.O. Box 70
Burlington, VT 05402

Division of Water Supply
  Engineering
Virginia State Department of
  Health
James Madison Building
109 Governor Street
Richmond, Virginia 23219

Water Supply and Waste Section
Department of Social and Health
  Services
Mail Stop LD-11
Olympia, Washington 98504

Drinking Water Division
Office of Environmental Health
  Services
State Department of Health
1800 Washington Street E
Charleston, WV 25305

Bureau of Water Supply
Public Water Supply Section
Department of Natural Resources
P.O. Box 7921
Madison, Wisconsin 53707

 Water Quality Division
 Department of Environmental
  Quality
 401 West 19th Street
 Cheyenne, Wyoming 82002
Guam Environmental Protection Agency
Government of Guam
P.O. Box 2999
Agana, Guam 96910

Public Health Engineering
Nevada Department of Human
 Resources
Consumer Health Protection
 Services
505 East King Street, Room 103
Carson City Nevada 89710

Division of Water Supply
Tennessee Department of Health and
 Environment.
150 9th Avenue, North
Nashville, Tennessee 37219-5404

Division of Water Hygiene
Texas Department  of Health
1100 West 49th Street
Austin, Texas 78756
                            _
Division of Environmental Quality
Commonwealth of  the Northern
  Mariana Islands
P.O. Box 1304
Saipan, CM 96950

Environmental Protection Board HQ
Trust Territories of Pacific
  Island
Saipan, CM 96950

Department of Conservation and
  Cultural Affairs
 Government of Virgin Islands
 P.O. Box 4340
 St. Thomas, Virgin Islands 00801
 198

-------
                                APPENDIX G

                              EPA Regional Offices
      Name/Adresses

 USEPA Region I - Connecticut, Maine,
  Massachusetts, New Hampshire,
  Rhode Island, Vermont
 John F. Kennedy Federal Building
 Boston, MA 02203
 (617) 223-5731

 Region II - New Jersey, New York,
  Puerto Rico, Virgin Islands
 Federal Building
 26 Federal Plaza
 New York, NY  10007
 (212) 264-1800

 Region HI - Delaware, District of
  Columbia, Maryland, Pennsylvania,
  Virginia, West Virginia
 Curtis Bldg., 6th & Walnut Streets
 Philadelphia, PA  19106
 (215) 597-8227

 Region IV - Alabama, Florida,
  Georgia, Kentucky,  Mississippi,
  North Carolina, South Carolina,
  Tennessee
 345 Courtland Street
Atlanta, GA 30308
 (404) 881-3781

Region V - Illinois, Indiana,
  Michigan, Minnesota, Ohio
  Wisconsin
230 South Dearborn Street
Chicago, IL 60604
(312) 353-2151
 Name/Addresses

 Region VI - Arkansas, Louisiana,
  New Mexico, Oklahoma, Texas
 1201 Elm Street
 Dallas, TX  75270
 (214) 749-2106

 Region VII - Iowa, Kansas, Missouri,
  Nebraska
 324 E. llth Street
 Kansas City, MO 64106
 (816) 374-5429

 Region VIH - Colorado, Montana,
  North Dakota,  South Dakota, Utah,
  Wyoming
 Lincoln Tower Building
 1860 Lincoln Street
 Denver, CO  80295
 (303) 837-2731

 Region IX - Arizona, California,
  Hawaii, Nevada, Guam, American
  Samoa, Trust Territory of Pacific
  Islands
 215 Fremont Street
 San Francisco, CA 94105
 (415) 974-8106

Region X - Alaska, Idaho, Oregon,
  Washington
1200 Sixth Avenue
Seattle, WA 98101
(206) 442-1223
                                                                           199

-------

-------
                                APPENDIX H

                              National Organizations
 American Water Resources
  Association
 5410 Grosvenor Lane
 Suite 220
 Bethesda, Maryland 20814
 Phone: (301) 493-8600

 American Water Works Association
 6666 West Quincy Avenue
 Denver, Colorado  80235
 Phone: (303) 794-7711

 Association of Boards of
  Certification for Operating
  Personnel
 P.O. Box 786
 Ames, Iowa  50010
 Phone: (515) 232-3623

 Chlorine Institute
 2001 L. Street, N.W.
 Suite 506
 Washington, D.C. 20036
 Phone: (202) 775-2790

 National Lime Association
 3601 N. Fairfax Drive
 Arlington, Virginia  22201
 Phone:  (703) 243-5463

 National Rural Water Association
 2915 South Thirteenth Street
 P.O. Box 1428
Duncan, Oklahoma  73534
Phone:  (405) 252-0629
 National Sanitation Foundation
 P.O. Box 1468
 Ann Arbor, Michigan  48106
 Phone:  (313) 769-8010

 National Small Flows Clearinghouse
 258 Stewart Street
 P.O. Box 6064
 Morgantown, WV 26506-6064
 Phone:  (304) 293-4191

 National Water Supply Improvement
  Association
 P.O. Box 102
 St. Leonard, Maryland 20685
 Phone (301) 855-1173

 National Water Well Association
 6375 Riverside Drive
 Dublin, Ohio  43017
 Phone:  (614) 761-1711

 Rural Community Assistance Program
 602 South King Street
 Suite 402
 Leesburg, Virginia 22075
 Phone:  (703)771-8636

 Water Systems Council
 600 South Federal Street
 Suite 400
 Chicago, Illinois  60605
Phone:  (312) 922-6222
                                                                           201

-------

-------
                                APPENDIX I
                          Farmers Home Administration
 FmHA State Director
 Room 717, Aronov Building
 474 South Court Street
 Montgomery, Alabama 36104
 205-832-7077

 FmHA State Director
 P.O. Box 1289
 Palmer, Alaska 99645
 907-745-2176

 FmHA State Director
 Room 3433, Federal Building
 230 North First Avenue
 Phoenix, Arizona 85025
 602-261-6701

 FmHA State Director
 Room 5529, Federal Office Building
 700 West Capitol
 P.O. Box 72203
 Little Rock, Arkansas 72201
 501-378-6281

 FmHA State Director
 Cleveland Street
 Woodland, California 95695
 916-666-3382

 FmHA State Director
Room 231, 2490 West 26th Avenue
Denver, Colorado 80211
303-837-4347
 FmHA State Director
 151 East Chestnut Hill Road
 Suite 2
 Newark, Delaware 19713
 302-573-6694

 FmHA State Director
 401 S.E. 1st Avenue
 Room 314 Federal Building
 P.O. Box 1088
 Gainseville,  Florida 32602
 904-376-3218

 FmHA State Director
 Stephens Federal Building
 355 E. Hancock Avenue
 Athens, Georgia 30601
 404-546-2162

 FmHA State Director
 345 Kekuanaoa Street
 Hilo, Hawaii 96720
 808-961-4781

 FmHA State Director
 Room  429
 304 N. Eighth Street
Boise, Idaho 83702
208-334-1301

FmHA State Director
2106 W. Springfield Avenue
Champaign, Illinois 61820
217-398-5235
                                                                          203

-------
FmHA State Director
5610 Crawfordsville Road
Suite 1700
Indianapolis, Indiana 46224
317-248-4442

Midwest State Director at Large
Room 176, Federal Building
444 SE Quincy Street
Topeka, Kansas 66683
913-295-2870

FmHA State Director
USDA Office Building
Orono, Maine 04473
207-866-4928

FmHA State Director
One Vahlsing Center
Robbinsville, New Jersey 08691
609-259-3136

FmHA State Director
451 West Street
Amherst, Massachusetts 01002
413-253-3471

FmHA State Director
Room 209, Manly Miles Building
 1405 South Harrison Road
East Lansing, Michigan 48823
517-337-6631

FmHA State Director
Room 252 Federal Building and
  U.S. Courthouse
316 North Robert Street
St. Paul, Minnesota 55101
612-725-5842
FmHA State Director
Suite 831, Federal Building
Jackson, Mississippi 39201
601-960-4316

FmHA State Director
555 Vandriver Drive
Columbia, Missouri 65201
314-442-2271, Ext. 3241

FmHA State Director
Room 234, Federal Building
P.O. Box 850
Bozeman, Montana 59715
406-587-5271, Ext. 4221

FmHA State Director
Room 308 Federal Building
100 Centennial Mall North
Lincoln, Nebraska 68508
402-471-5551

FmHA State Director
Room 3414, Federal Building
517 Gold Avenue,  SW
Albuquerque, New Mexico 87102
505-766-2462

FmHA State  Dkector
Room 871, U.S. Courthouse
  and Federal Building
100 South Clinton Street
Syracuse, New York  13202
315-423-5290
 204

-------
 FmHA State Director
 Room 525
 310 New Bern Avenue
 Raleigh, North Carolina 27601
 919-755-4640

 FmHA State Director
 Room 208, Federal Building
 Third and Rosser
 P.O. Box 1737
 Bismarck, North Dakota 58502
 255-4011, Ext! 4781

 FmHA State Director
 Room 507, Federal Building
 200 North High Street
 Columbus, Ohio 43215
 614-469-5606

 FmHA State Director
 USDA Agricultural Center Building
 Stillwater, Oklahoma 74074
 405-624-4250

 FmHA State Director
 Room 1590, Federal Building
 1220 SW 3rd Avenue
 Portland, Oregon 97204
 503-221-2731

 FmHA State Director
Room 728, Federal Building
P.O. Box 905
Harrisburg, Pennsylvania 17108
717-782-4476
  FmHA State Director
  Room 623
  Federico Degetau Federal Building
  Carlos Chardon Street
  Hato Rey, Puerto Rico 00818
  809-753-4481

  FmHA State Director
  Storm Thurmond Federal Building
  Room 1007
  1835 Assembly Street
-  Columbia, South Carolina 29201
  803-765-5876

  FmHA State Director
  Room 308, Huron Federal Building
  200 4th Street, SW
  Huron, South Dakota 57350
  606-352-8651, Ext. 355

  FmHA State Director
  538 Federal Building & Courthouse
  801 Broadway
  Nashville, Tennessee 37203
  615-251-7341

 FmHA State Director
 Room 1005, Federal Building
 Capser, Wyoming 82602
 307-265-5550, Ext.  5271

 FmHA State Director
 Suite 102, Federal  Building
 101 South Main
 Temple, Texas 76501
 817-774-1301
                                                                          205

-------
FmHA State Director
Room 5434, Federal Building
125 South State Street
Salt Lake City, Utah 84138
801-524-5027

FmHA State Director
141 Main Street
P.O. Box 588
Montpelier, Vermont 05602
802-223-2371

FmHA State Director
Room 8213, Federal Building
400 North Eighth Street
P.O.  Box 10106
Richmond,  Virginia 23240
804-771-2451
FmHA State Director
301 Yakima Street
Wenatchee, Washington 98801

FmHA State Director
75 High Street
Morgantown, West Virginia 26505
304-599-4791

FmHA State Director
1257 Mains Street
Stevens Point, Wisconsin 54481
715-341-5900
  206

-------
                                    INDEX
Acidity	15, 80, 85
Activated aluminum	
Activated carbon filters	101, 102
Aeration  	  91
Air line  	  56
Air rotary drilling	  52
Algae	97-98
Alkalinity	12, 13
Alum	  80
Aluminum 	  13
American Water Works Association
    (AWWA)	2, 151
Analysis of water:
    bacteriological  	  22
    chemical  	  22
    radiological  	  22
Aquifer	  37
Arsenic  	  167
Artesian aquifers  	9
Average daily water use  	22
Artesian wells	  38
                B
Backwash	  83
Bacteria:
    in water	  37
Barium in water	18, 167
Biological characteristics	15, 16
"Blue baby" disease	  14
Bored wells  	44, 46
Cable tool drilling	  50
Cadmium	  18
Calcium hypochlorite  . . .	  85
Calcium	  13
Capillary fringe	9
Carbon dioxide	96, 16
Cartridge filters  	  83
Casings  	46,52
Catchments  	66-73
Centrifugal pumps  	105, 106
Cesspools	34, 37, 39
Check valves	 129
Chemical characteristics:
    of ground water	12-15
    of water	12-15
Chemical disinfection	  84
Chlorides	  13
Chlorination  equipment  	87-89
Chlorine Disinfection	84-87
Chromium	  18
Churn drill	  50
Circuit riders  	 151
Cisterns	66, 68
Coagulation	  80
Conforms	  20
Color	  11
Community Development Block Grants
    (CDBG)   	 154
Community Involvement	2
Community Planning and Development
    Agency	 154
Computers	 157
Cone of depression	  39
Conservation  	24, 25
Consolidated formations	  34
Contact time   	  85
Contamination:
    physical	  21
    chemical  '	  22
    biological	  22
    radiological  	  22
    distances  to sources	  35-36
    evaluating treats	36-38
    sources of	  21
Contract services  	  160
Copper 	  13
Copper sulfate	  97
Corrosion	  96
                                                                            207

-------
Corrosion control	95-96
County utilities	  160
Crib	  44
Cross-connection 	  136-138
Cryptosoridium  	  16
                D
DPD colorimetric test	87
Diatomaceous earth filters  	  83
Disinfection:	  19
    emergency  	  191
    wells  	59-62
    with ozone	  90
Distribution system	28-29
Down-the-hole air hammer	  52
Development of groundwater  . . 38-42
Development of springs  	74-76
Drainage area  	  69
Drawdown	  39
Drilled wells <	  62
Drilling equipment and methods 44-57
Drive (well) points	  48
Driven wells	  46-48, 62
Drying beds	  103
Dug wells	44, 60
                E
Economic Development Administration
    (EDA)	  154
Electrodialysis reversal	90, 91
Embankment	 72
Epsom salts in water  	35
Escherichia coli (E. coli)	16, 20
Evaporation rates	  7, 8
Evaporation ponds	103, 104
Evapotranspiration	7, 8
Farmers Home Administration
    (FmHA)  	2,153,159
Filters  	80-83
Filtration, surface water  	  19
Fluoride removal  	94-95
Financial assistance	2
Fire protection	25-27
Flocculation	  80
Flooding of wells  	  58
Flowing artesian wells	  62
Fluoride	  13
Foaming	  11
Formations:
    consolidated	  34
    unconsolidated	  34
Freezing protection:  	71, 73
General litigation bonds	  155
Giardia lamblia  	, .  16, 65, 83
Glauber's salt	  35
Granular Activated Carbon (GAG) 101
Ground level reservoirs	66-69
Ground water:
    basins 	33-34
    temperature	  35
                 H
Hand pump	  125-126
Hardness	 13
Head loss	  139-142
Herbicides	 11
Home water needs	 24
Household water treatment . .  100-102
Hydraulic ram	 105, 111
Hydraulic rotary drill  	 50
Hydrogen sulfide .	 95
                  I
Industrial development bonds  . . .  155
Infiltration galleries  ......   64, 76-77
Information Resources  .....  149-150
Inspection:
    of pitless installations	  134
    of wells  	 55
Interference	 41
Iodine	  192
Ion exchange  	93-94
208

-------
      bacteria  	92-93
      	14, 91
 Jet pumps  	  106
 Jetted wells 	48-50
                  O
 Odors  	 11
 Operating Ratio	  156
 Organic material	 151, 153
 Ozone	;	 90
 Organic compounds  	 37
 Lakes	  69-71, 73
 Lawn sprinkling	  25
 Lead  	14, 37
 Leak detection	  24
 Lead levels	  19
 Lead control	  21
 Lightning, protection  	  126
 Lime	  96
 Lime-soda ash 	  94
 Limestone	  33
                  M
Man-made radiation	  17
Magnesium in water	  13
Manganese	14, 92
Maximum Contaminant
    Levels (MCL)  	17, 19
Membrane filter (MF)  	  175,176
Monitoring	  19
Mud rotary drilling	50, 52
                  N
Natural radiation  	  17
National Rural Water Association
    (NRWA)	   151
National Sanitation Foundation
    (NSF)  	2,151
National Water Supply Improvement
    Association (NWSIA)	2
National Water Well Association . .  34
Nitrates	  14
Non-artesian wells 	     38
NTU	. .  12
 Package plants	 98-100
 Painting	  145
 Percussion (cable tool) drilling ...  50
 pH  	  15
 Pesticides	14-15
 Photo-Voltaic (PV) array . . .  106-109
 Pipe:
    fittings, friction loss in  	  141
    for distribution systems	  138
    for well casing	  52
 Pitless adapters  	  128-136
 Point of entry treatment  (POE) 100-101
 Point of use treatment (POU)  100-101
 Pollution, sources of	21-22
 Ponds and lakes	69-73
 Positive displacement pumps ....  105
 Potassium permanganate	  100
 Pressure	  26,139-142
 Pressure sand filter	  83
 Pressure tanks 	  143-144
 Preventive Maintenance  . .  . 96-97, 137
 Protection of distribution
    system	145, 148
 Pump:
    alignment in wells  .   113,  117, 121
    lubrication	106, 117
    platforms	
    pruning	105, 109, 116, 120
Pumphouses	126, 127
Pumps:
    centrifugal	  105-106
    hand  	Ill, 125-126
    helical or spiral rotor	  105
    installation of	121r 123
    jet	  106
    line-shaft (vertical) turbine  121-123
                                                                             209

-------
   Regenerative turbine pump . .  105
   positive displacement  	  105
   solar photovoltaic
     (PV) pump  	  106, 109, 123
   wind pump	109,  100, 124, 125
   submersible	  106
   vertical turbine	  106
   reciprocating  	  105
Quantity of water	  22
                  R
Radiation	17, 167
Radioactivity  	  167
Radiological characteristics	  16
Radionudides	37
Radius of influence	  39
Radon	  173
Rapid sand filter	82-83
Rates of How	  139
Reciprocating pumps  	  105
Reconstruction of dug wells . . . 63-64
Reservoir	  144
Revenue bonds	  155
Reverse osmosis	  90
Revolving funds 	  154
Rock formations	  33
Rotary drilling methods  	  52
Rural Community Assistance Program
    (RCAP)	  151
Safe Drinking Water Act
    (SDWA)  	1-3, 17-21
Salt  	  15
Sample collection	  21
Sand  	  48
Sanitary covers:
    for spring boxes, cisterns	74
    for wells	  58
Sanitary protection:
    of distribution systems  	  142
    of springs	  74
    of wells 	  63
    of pumping facilities	  124
Sanitary quality of groundwater  ...  34
Sanitary survey	27-31
Satellite operation  	  158-159
Scale	  96
Screens, well:
    selection of	 53, 54
Seal, cement grout formation   189-190
Secondary Maximum Contaminant
    Levels  (SMCLs)  ....	17, 19
Sedimentation  	  80
Selenium  	  18
Settling basins  	  80
Silver		  15
Skeletal fluorosis  	  94
Slow sand filters	80-82
Sludge	  103
Snow	  10
Sodium  	  15
Softening	93-94
Soil moisture  	9
Solar irradiation   	  123
Solar pumps	106, 109
Surface water	65-77
Specific capacity	  41
Springs . .  . '.	39, 64
Staining of clothing and fixtures . .  14
State utilities	  160
Static pressure 	  113
Steel pipe	  139
Storage tank	  144-145
Storage tanks, painting of ...  144-145
Stream	 10
Submersible pump 	  106
Sulfates  	 15
Superchlorination	 89
Surface Water Treatment Rule
     (SWTR)  	20, 65
 Taste and odor in water ... 11, 73, 95
 Temperature:            :
     of ground water	  35
 210

-------
 Testing;
     pitless adapters and units for leaks
     water for bacteria	  21
     water for minerals  	  21
 Total coliform  	  16
 Total Coliform Rule	  20
 Total dissolved solids (TDS)	  15
 Toxic substances	14-15
 Transpiration rates	 8
 Trihalomethanes (THM)	  11
 Turbidity	10, 12, 83
                  U
 Ultraviolet light  	  89
 Unconsolidated formations	  34
 U.S. Department of Housing and
    Urban Development (HUD) ...  2
 U.S. Geological Survey (USGS)  . .  55
 U.S. Small Business
    Administration	2, 154
Valves:
    check	  112, 114, 129
Vent, well  	:	  120
Vertical turbine pumps	  106
Viruses  ....'.	  65
Volatile Organic Compounds
    (VOCs)	91

                 W

Waste treatment	  79-104
Water conditioning	93-94
Water conservation  	24-25
    conservation methods	24-25
    structural methods  	24-25
    economic methods	  25
    usage restrictions	  25
    legal means 	  25
    public awareness  	  25
Water consumption (demand)  ....  24
Water disinfection:
    with chemicals	   80, 84-89
     with ultraviolet light	89-90
 Water districts  	  159
 Water quality	34-35
 Water rates	 .  155-157
 Water rights	7
 Water scaling	  96
 Water softeners  	93-94
 Water table	  39
 Water testing   	  21
 Water treatment	  79
 Water use  	  220
 Watershed	  10
 Weed control	  98
 Well:
     abandonment (destruction) ...  63
     casing  	  52
     construction	44-63
     covers  	58-59
     development (see also well
      construction)	54-55, 58, 64
     site selection for wells  .... 35-41
     disinfection   	59-63
     failure	55-57
   ^grouting	  59
     pits  	  44
     ponits  	  49
     repair  	  55
     screens  	  53
     seals	58-59
     slabs 	  59
Well testing:
    yield a drawdown	  55
    for capacity   	  41
Windmill 	  109
Wellhead protection	  20
Yield:
    of wells
41-42
Zeolite softening  	93-94
Zinc in water	 15
Zone of saturation	9
                                                                             211

-------

-------