If the problem seems to be widespread
or potentially serious, it is advisable to
work with your health and safety commit-
tee. If you do not have a health and safety
committee, consider forming one, or
establishing a joint management-tenant
IAQ task force. (See the discussion on
page 13.)
Productive relations will be enhanced if
occupants are given basic information
during the process of investigation and
mitigation. Potential critics can become
allies if they are invited to be part of the
problem-solving process and become
better educated about IAQ and building
operations. Building managers may be
understandably reluctant to share test
results or consultants' reports with their
tenants or employees, but secrecy in such
matters can backfire if information leaks
out at a later time.
Building management staff can be
encouraged to talk directly with occupants
both at the time a complaint occurs and
later during a diagnostic investigation.
Their observations about patterns of
symptoms or building conditions may
provide helpful information.
Confidentiality of records can be
important to occupants, especially if they
are concerned that IAQ complaints will
lead to negative reactions from their
employers. There may be legal penalties
for violating confidentiality of medical
records. By reassuring occupants that
privacy will be respected, investigators are
more likely to obtain honest and complete
information.
It is advisable to explain the nature of
investigative activities, so that rumors and
suspicions can be countered with factual
information. Notices or memoranda can
be delivered directly to selected occupants
or posted in general use areas. Newsletter
articles or other established communica-
tion channels can also be used to keep
building occupants up-to-date.
Problems can arise from saying either
too little or too much. Premature release
of information when data-gathering is still
incomplete can produce confusion,
frustration, and mistrust at a later date.
Similar problems can result from incorrect
representation of risk assuming the
worst case (or the best). However, if
progress reports are not given, people may
think nothing (or something terrible) is
happening. It is good practice to clear
each piece of information with the facility
manager, building owner, or legal counsel.
Management should attempt to be factual
and to the point when presenting informa-
tion such as:
the definition of the complaint area
based upon the location and distribution
of complaints (this may be revised as the
investigation progresses)
the progress of the investigation,
including the types of information that
are being gathered and ways that
occupants can help
factors that have been evaluated and
found not to be causing or contributing
to the problem
how long the investigation might take
attempts that are being made to improve
indoor air quality
work that remains to be done and the
schedule for its completion
Vague discomfort, intermittent symp-
toms, and complex interactions of job
stress with environmental factors, which
make IAQ problems difficult to investi-
gate, can also obscure the effects of
mitigation efforts. Even after the proper
mitigation strategy is in place, it may take
days or weeks for contaminants to dissi-
pate and symptoms to disappear. If
building occupants are informed that their
symptoms may persist for some time after
mitigation, the inability to bring instant
relief is less likely to be seen as a failure.
If the problems
to be widespread or
potentially seriaLB, it
is advisable to vucrk
vuthyoLr health and
safety committee. If
you do not have a
health and safety
cxjitit iLLee,
establishing a joint
IAQ task force.
Effective Communication 17
-------
Building Air Quality
ilililll
mi 11 in 11
iiiiiiiini
mil
Printed on Recycled Paper
-------
. IAQ profile is a description of the
features of the building structure, function,
and occupancy that impact indoor air
quality. When you have completed the
IAQ profile, you should have an under-
standing of the current status of air quality
in the building and baseline information on
the factors that have a potential for causing
problems in the future.
The IAQ profile can help building
management to identify potential problem
areas and prioritize budgets for mainte-
nance and future modifications. Combined
with information on lighting, security, and
other important systems, it can become an
owner's manual that is specific to your
building and that will serve as a reference
in a variety of situations.
The key questions to answer while
developing the IAQ profile are:
How was this building originally
intended to function? Consider the
building components and furnishings,
mechanical equipment (HVAC and non-
HVAC), and the occupant population
and associated activities.
Is the building functioning as designed?
Find out whether it was commissioned.
Compare the information from the
commissioning to its current condition.
What changes in building layout and use
have occurred since the original design
and construction? Find out if the HVAC
system has been reset and retested
to reflect current usage.
What changes may be needed to prevent
IAQ problems from developing in the
future? Consider potential changes in
future uses of the building.
After reading this manual to develop a
feel for the issues involved in maintaining
good indoor air quality in a building, the
development of an IAQ profile should
become a priority. The process of
developing an IAQ profile should require
only a modest effort, from a few days to a
few weeks of staff time, depending on the
complexity of your building and the
amount of detailed information collected.
The work can be done in pieces over a
longer period, if necessary, to fit into a
building manager's busy schedule.
Over time, it is desirable to make some
actual measurements of airflow, tempera-
ture, relative humidity, carbon dioxide
(CO2), and/or pressure differentials (e.g., in
each of the air handling zones or other sub-
areas of the building). These measure-
ments provide far better information on
current conditions than can be obtained
from the plans and specifications, even if
as-built records are available.
In addition, few buildings have been
adequately commissioned, so the system
may never have delivered the airflows
shown on the design drawings. In the
event of litigation around future IAQ
complaints, the value of the IAQ profile as
a resource document will be enhanced by
real-world measurements. (Refer to
Appendix G and the ASHRAE standard on
commissioning. The EPA document on
designing for good indoor air quality,
which is due to be published in 1992, will
contain a more complete discussion of the
process of commissioning buildings.)
Developing an IAQ Profile 19
-------
FIGURE 4-1: Developing;
Profile
START
ilAQ
^^m
1. Collect and
Review Existing
Records
Review design,
construction and
operating documents
Check HVAC mainte-
nance records against
equipment lists
Review complaint
record
2. Conduct a
Wriklnraudhi
Inspection of the
Buldng
Talk with staff and
other occupants
Look for IAQ problem
3L Collect Detailed
HVAC system
condition and
operation
Pollutant pathways
Pollutant sources
Occupants
Go to Section 6
Description of HVAC system
design and operation; set of
operating instructions, manuals
Set of maintenance and calibration
records
Inventory of locations where
occupancy, equipment, or building
have changed
Inventory of complaint locations
List of responsible staff and/or
contractors; evidence of training;
job descriptions
Identification of areas where
positive or negative pressures
should be maintained (sketch
plan)
Record of locations that need
monitoring or correction
Inventory of HVAC system
components needing repair,
adjustment or replacement
Record of control settings and
operating schedules
Completed plan showing airflow
directions or pressure differen-
tials in significant areas
Inventory of significant
pollutant sources and their
locations
Set of Material Safety Data
Sheets for supplies and
hazardous substances that are
stored or used in the building
Zone/Room Record
Yes
SKILLS REQUIRED TO CREATE
IAQ PROFILE
Develop an IAQ management plan (see Section 5)
Many of the resources necessary for the
IAQ profile should already be on hand
within your organization. Additional
information can be collected by the staff
person or persons who have the following
skills:
basic understanding of HVAC system
operating principles
ability to read architectural and mechani-
cal plans and understandmanufacturer's
catalog data on equipment
ability to identify items of office
equipment
ability to work cooperatively with
building occupants and gather informa-
tion about space usage
ability to collect information about
HVAC system operation, equipment
condition, and maintenance schedules
authority to collect information from
subcontractors about work schedules
and materials used (particularly cleaning
and pest control activities)
ability to understand the practical
meaning of the information contained in
the Material Safety Data Sheets
(MSDSs)
If direct measurements are to be
included in the IAQ profile, the staff
should have the tools and training to make
the following measurements (see Appendix
A for guidance on air sampling):
air volumes at supply diffusers and
exhaust grilles
CO2 concentration
temperature
relative humidity
pressure differentials
assessment of thermal and ventilation
load requirements
Section 8 provides guidance on hiring
IAQ professionals if you prefer to use
outside expertise to develop your IAQ
profile.
20 Section 4
-------
STEPS IN AN IAQ PROFILE
The information needed for an IAQ profile
is similar to that which is collected when
solving indoor air quality problems, but
includes the entire building rather than
focusing on areas that may have caused an
identified problem. The IAQ profile
should be an organized body of records
that can be referred to in planning for
renovations, negotiating leases and
contracts, or responding to future com-
plaints.
The process of gathering information
for the IAQ profile can be divided into
three major stages:
1. Collect and review existing records.
2. Conduct a walkthrough inspection of
the building.
3. Collect detailed information on the
HVAC system, pollutant pathways,
pollutant sources, and building
occupancy.
The first two stages should be carried
out as quickly as possible, but the third
stage can be handled as time allows so that
it does not interfere with other staff
responsibilities.
1. Collect and Review Existing
Records
Review construction and operating
documents
Collect any available documents that
describe the construction and operation of
the building: architectural and mechanical
plans, specifications, submittals, sheet
metal drawings, commissioning reports,
adjusting and balancing reports, inspection
records, and operating manuals. Many
buildings may lack some or all of these
documents. If there are no commissioning
reports or balancing reports, actual venti-
lation quantities may be quite different
from those indicated on mechanical design
REVIEW/OF EXISTING RE
I a description of the HVAC system design and operation
(e.g., original plans and specifications with changes indi-
cated or new sketch plans and notes, commisioning reports,
testing and balancing reports)
i a set of operating instructions, maintenance and calibra-
tion records for HVAC system components (e.g., fans,
dampers, filters, chillers, boilers, and control systems)
i an inventory of locations where architectural or engineering
modifications have taken place
i an inventory of locations in which current occupancy or
HVAC system operation represents a change from the
original design
i an inventory of locations where complaints have been
common in the past
drawings. If there are no operating or
maintenance manuals for HVAC equip-
ment, it is difficult for staff to carry out an
adequate preventive maintenance program.
Study the original architectural and
mechanical design so that you understand
the building's layout and intended func-
tions. Identify and note locations in which
changes in equipment or room usage create
a potential for indoor air quality problems
and give them special attention during the
walkthrough inspection.
Items of interest and the questions they
suggest could include the following:
Commissioning reports
Was the building properly commissioned
when it was first constructed, including
testing and balancing of the HVAC
system?
Operating manuals
Do staff members understand how the
HVAC equipment is intended to operate?
Remodeled areas
Has the HVAC system layout been
changed to accommodate new walls,
rearranged partitions, or similar architec-
tural modifications?
Developing an IAQ Profile 21
-------
Addition, removal, or replacement of
HVAC equipment
Where the original equipment has been
replaced, do the newer units have the
same capacity as the originals?
Has new equipment been properly
installed and tested? Where equipment
has been removed, is it is no longer
needed?
Changes in room use
Is there a need for additional ventilation
(supply and/or exhaust) due to increased
occupant population or new activities
within any area of the building?
Have new items of equipment (non-
HVAC) been provided with local exhaust
where needed? Look for unusual types
or quantities of equipment such as copy
machines or computer terminals.
Check HVAC maintenance records
against equipment lists
Collect your existing maintenance and
calibration records and check them against
the construction documents (e.g., equip-
ment lists and mechanical plans). See
whether all components appear to be
receiving regular attention. Equipment that
WALKTHROUGH INSPECTION
At the end of the walkthrough inspection, you should have:
List of staff (and contractors) with responsibilities that could affect
IAQ, including contact information:
names, telephone numbers job descriptions
notes on training and experience of building staff
Notes on the schedules and procedures used in:
facilities operation and maintenance
housekeeping
pest control
Sketch plan with notes showing:
pressure relationships between special use areas and
surrounding rooms
locations in which general indicators of IAQ problems show
the need for close monitoring or corrective action
has been installed in inaccessible or out-of-
the-way locations is frequently overlooked
during routine maintenance. This is
particularly true of items such as filter
boxes and small capacity exhaust fans.
Review records of complaints
If there is an organized record of past
occupant complaints about the building
environment, review those complaints to
identify building areas that deserve
particular attention.
2 Ctanduct a
Inspection of the
king
The intent of the walkthrough inspection is
to acquire a good overview of occupant
activities and building functions and to
look for IAQ problem indicators. No
specific forms are suggested for this stage
of IAQ profile development. However,
the investigator should have a sketch plan
of the building, such as a small floor plan
showing fire exit, so that his or her notes
can be referenced to specific locations.
Detailed measurements of temperature,
humidity, airflow, or other parameters are
more appropriate to a later stage of profile
development. However, chemical smoke
can be used to observe airflow patterns and
pressure relationships between special use
areas or other identified pollutant sources
and surrounding rooms. Odors in inappro-
priate locations (e.g., kitchen odors in a
lobby) may indicate that ventilation system
components require adjustment or repair.
(See Appendix A for further discussion of
the use of chemical smoke.)
The value of IAQ ventilation measure-
ment tools to your operation will grow as
you become more familiar with handling
indoor air quality concerns. For example,
if you do not own a direct-reading carbon
dioxide monitor, it is not necessary to
acquire one for the IAQ profile. Those
who already have access to this type of
instrument can take readings during the
walkthrough as a way to obtain baseline
22 Section 4
-------
information about normal operating
conditions or identify problem locations.
If you begin to suspect that underventila-
tion is a consistent problem, you may
decide that it would be helpful to obtain
more ventilation monitoring equipment.
(See Appendix A for further discussion of
carbon dioxide and other ventilation
measurements.)
Talk with staff and other occupants
A walkthrough inspection provides an
opportunity to introduce facility staff and
other building occupants to the topic of
indoor air quality and to understand current
staff (and contractor) responsibilities in
relation to housekeeping and maintenance
activities. Advance notice of the inspec-
tion will make it seem less intrusive and
may encourage staff and other occupants to
remember important information.
Discussion of routine activities in the
building will help to clarify elements that
should be included in the IAQ manage-
ment plan. Ask staff members about their
job responsibilities, training and experi-
ence. It will be helpful to meet with
responsible staff and contractors to
discuss:
Facility operation and maintenance
(e.g., HVAC, plumbing, electric, interior
maintenance)
HVAC operating schedule (e.g., occu-
pied/unoccupied cycles)
HVAC maintenance schedule (e.g., filter
changes, drain pan maintenance)
use and storage of chemicals
schedule of shipping and receiving,
handling of vehicles at loading dock
scheduling and other procedures for
isolating odors, dust, and emissions from
painting, roof repair, and other contami-
nant-producing activities
budgeting (i.e., how do staff members
influence budget decisions?)
Housekeeping
cleaning schedule
trash storage and schedule of refuse
removal
use and storage of chemicals
Pest control
schedule and location of pesticide
applications
use and storage of chemicals
pest control activities other than use of
pesticides
Look for IAQ problem indicators
The walkthrough inspection can be used to
identify areas with a high potential for IAQ
problems. The following are general
indicators of IAQ problems:
odors
dirty or unsanitary conditions (e.g.,
excessive dust)
visible fungal growth or moldy odors
(often associated with problem of too
much moisture)
sanitary conditions at equipment such as
drain pans and cooling towers
Maintenance is more likely to
be performed on a routine
basis when there is good
access to HVAC equipment
such as that shown in this
photo.
Developing an IAQ Profile 23
-------
Building occupants who are
uncomfortable may try to
improve the situation by
themselves. The small fans
shown above indicate an air
circulation or thermal
discomfort problem. The irony
of this situation is that the fan
motors add heat to the air.
m sanitary conditions in equipment such as
drain pans and cooling towers
poorly-maintained filters
signs of mold or moisture damage at
walls (e.g., below windows, at columns,
at exterior corners), ceilings, and floors
staining and discoloration (Note: Make
sure that stains are removed after leaks
are repaired so that there will be visible
evidence if the leak recurs.)
smoke damage (Note: If a fire has
occurred involving electrical equipment,
determine whether PCBs (polychlori-
nated biphenyls) may have been released
from the equipment.)
presence of hazardous substances
potential for soil gas entry (e.g., unsealed
openings to earth, wet earth smells)
unsanitary mechanical room, or trash or
stored chemicals in mechanical room
unusual noises from light fixtures or
mechanical equipment
In addition to these general indications,
some common problems deserve mention:
Inadequate maintenance: Look for leaks
of oil, water, or refrigerants around HVAC
equipment. Also be aware of signals such
as unreplaced burned-out light bulbs in fan
chambers and staff members who have
difficulty locating specific pieces of
equipment. Dry drain traps can also cause
indoor air quality problems. If traps are
not kept charged with liquid, they could be
allowing sewer gas to enter occupied
spaces.
Signs of occupant discomfort: Notice
uneven temperatures, persistent odors
(including tobacco smoke), drafts, sensa-
tions of stuffiness. You may find that
occupants are attempting to compensate
for an HVAC system that doesn't meet
their needs. Look for propped-open
corridor doors, blocked or taped up
diffusers, popped-up ceiling tiles, people
using individual fans/ heaters or wearing
heavier (or lighter) clothing than normal.
Overcrowding: Future occupant density is
estimated when the ventilation system for a
building is designed. When the actual
number of occupants approaches or
exceeds this occupant design capacity,
managers may find that IAQ complaints
increase. At that point, the outdoor air
ventilation rate will have to be increased.
However, the ventilation and cooling
systems may not have sufficient capacity
to handle the increased loads from the
current use of the space.
Blocked airflow: Check for under-
ventilation caused by obstructed vents,
faulty dampers or other HVAC system
malfunctions, or from problems within the
occupied space. Furniture, papers, or other
materials can interfere with air movement
around thermostats or block airflow from
wall or floor-mounted registers. If office
cubicles are used, a small space (i.e., two
to four inches) between the bottom of the
partitions and the floor may improve air
circulation.
Ceiling plenums: Lift a ceiling tile and
examine the plenum for potential prob-
24 Section 4
-------
lems. Walls or full-height partitions that
extend to the floor above can obstruct or
divert air movement in ceiling plenums
unless transfer grilles have been provided.
If fire dampers have been installed to
allow air circulation through walls or
partitions, confirm that the dampers are
open. Construction debris and damaged or
loose material in the plenum area may
become covered with dust and can release
particles and fibers.
Heat sources: Be aware of areas that
contain unusual types or quantities of
equipment such as copy machines or
computer terminals. Also look for
instances of over-illumination. High
concentrations of electrical fixtures and
equipment can overwhelm the ventilation
and cooling systems.
Special use areas: Confirm that the
HVAC system maintains appropriate
pressure relationships to isolate and
contain odors and contaminants in mixed-
use buildings and around special use areas.
Examples of special use areas include
attached parking garages, loading docks,
print shops, smoking lounges, janitorial
closets, storage areas, and kitchens.
Improperly located vents, exhausts and
air intakes: Check the outdoor air intakes
to see whether they are located near
contaminant sources (e.g., plumbing vents,
exhaust outlets, dumpsters, loading docks,
or other locations where vehicles idle).
Unsanitary mechanical rooms: See if the
space containing the HVAC system is
clean and dry. Examples of problems
include: cleaning or other maintenance
supplies stored in mechanical room; dust
and dirt buildup on floors and equipment;
moisture in mechanical room because of
inadequate insulation, lack of conditioned
air, or failure to provide for air movement.
Unsanitary conditions in the mechanical
room are particularly a problem if
unducted return air is dumped into and
circulated through the mechanical room.
PRODUCTS OF COLLECTING
AILED INFCFHVIVTICN
an inventory of HVAC system components that need to be
repaired, adjusted, or replaced
a current record of control settings and operating schedules
a floor plan of the building showing airflow directions or
pressure differentials around areas intended to run positive or negative
(e.g., special use areas)
an inventory of pollutant sources and their locations
Material Safety Data Sheets for products used or stored within
the building
a record of usage for each zone or room, including the source of outside
air and the presence of local exhaust (if any)
Collect
ledlnforrr
The collection of detailed information for
the IAQ profile can be handled as time is
available. Areas that have been identified
as presenting potential IAQ problems
should be given the highest priority. You
may want to review Section 2 for back-
ground information on the factors that
contribute to indoor air quality.
Inspect HVAC system condition and
operation
Use your current maintenance records in
combination with one or both of the
HVAC Checklists to inspect HVAC
Occupants or staff sometimes
open ceiling tiles into return
plenums when attempting to
eliminate odors. Building
managers should be alert to
such signs of occupant
dissatisfaction in order to
remedy the original problem
and prevent additional
problems, such as the short-
circuiting of supply air.
Developing an IAQ Profile 25
-------
Sarrple Form
HVAD ChecklistShort Form
Mechanical Room
Clean and dry?
(describe items in need of attention)
Stored refuse or chemicals?
Mechanical Equipment
Preventative maintenance (PM) plan in use?
Control System Type
System operation
Sarrple Fcrm
Pollutant Rathuuay Record For IAQ Profile
Building Area
(zone, room)
Use
Intended Pressure
Positive Negative
(+) (-)
Needs
Attention?
(Y/N)
Comments
equipment and make sure that it is in good
operating condition. A portion of the
HVAC Checklist - Short Form is shown
on this page, with the entire form repro-
duced in Tab V. The HVAC Checklist -
Long Form (also reproduced in Tab V) is
recommended where a more detailed
examination is needed. You may want to
create a new form incorporating elements
from your existing inspection forms.
Identify items of equipment that need to
be repaired, adjusted, or replaced. Record
control settings and operating schedules for
HVAC equipment for comparison to
occupancy schedules and current uses of
space.
Inventory pollutant pathways
Using the sketch plan of the building
that was begun during the walkthrough
inspection, indicate architectural connec-
tions (e.g., chases) and mechanical connec-
tions (e.g., ductwork, temperature control
zones). Observe and record airflow
between spaces intended to run positive or
negative and the areas that surround them
(including airflow between perimeter
rooms and outdoors). Note that hidden
pathways such as chases may travel both
vertically and horizontally and transport
pollutants over long distances. Record the
results on the Pollutant Pathway Record
for IAQ Profiles, the sketch plan, or both.
The form is shown at the left (and in Tab
V), and a sample sketch plan is shown on
the opposite page.
Inventory pollutant sources
Use the Pollutant and Source
Inventory (shown in part on page 28 and
reproduced in full in Tab V) to record
potential pollutant sources in the building.
As you fill out the inventory form, note the
locations of major sources. Major sources
such as large items of equipment can be
recorded on the floor plan. The Chemical
Inventory Form (shown on page 28 and
reproduced in Tab V) can be used to record
the names and locations of chemicals or
hazardous substances used or stored within
26 Section 4
-------
A fire escape floorplan is
very useful for recording
information collected
during IAQ profile develop-
ment or while investigating
IAQ complaints. The facility
manager has begun to
identify the areas in which
air pressure relationships
are (or should be) control-
led and some ventilation
and has noted source infor-
mation. Symbols are © for
negative pressure, © for
positive pressure, and ^
for observed direction of
airflow. Utility chases,
tunnels, and suspended
ceilings could also be
drawn in to show pollutant
pathways and driving
forces.
Developing an IAQ Profile 27
-------
Sample Form
Pollutant and Source Inventory Form
Using the list of potential source categories below, record any
indications of contamination or suspected pollutants that may require
further investigation or treatment.
Source Category
Checked
Needs Attention
Location
Comments
SOURCES OUTSIDE THE BUILDING
Contaminated Ambient Air
Pollen, dust
Industrial
contaminants
General vehicular
contaminants
Sample Form
Chemical Inventory Form
The inventory should include chemicals stored or used in the building
for cleaning, maintenance, operations, and pest control. If you have an
MSDS (Material Safety Data Sheet) for the chemical, put a check mark
in the right-hand column. If not, ask the chemical supplier to provide
the MSDS, if one is available.
Date
Cherried/
BlcWl Natre
Use
Storage
LocaticrXs)
IVBDS
on File?
the building, such as those that may be
contained in cleaning materials, biocides,
paints, caulks, and adhesives. Ask your
suppliers to provide you with Material
Safety Data Sheets.
You may be unaware of the potential
hazards of some materials that are com-
monly used in public and commercial
buildings. For example:
In 1990, EPA eliminated the sale of
mercury-containing interior latex paint.
(Enamel paints do not contain mercury.)
People are urged not to use exterior latex
paint indoors, as it may contain mercury.
If you have paint in storage that may
have been manufactured before August
20, 1990, you may contact the manufac-
turer, the National Pesticide Telecommu-
nication Network (1-800-858-7378), or
your State Health
Department for guidance.
In 1990, EPA banned the use of
hexavalent chromium chemicals in
cooling towers, because the chemicals
have been shown to be carcinogenic.
Heating system steam should not be used
in the HVAC humidification system, as
it may contain potentially harmful
chemicals such as corrosion inhibitors.
Collect information on building occu-
pancy
The Zone/Room Record shown on the
following page (and also reproduced in
Tab V) can be used during IAQ profile
development to maintain an up-to-date
record of the way each area of the building
is used, its source of outdoor air, and
whether or not it is equipped with local
exhaust. If underventilation is suspected,
the form can be used to estimate ventila-
tion rates in cubic feet per minute per
person or per square foot floor area, for
comparison to guidelines such as design
documents, applicable building codes, or
the recommendations of ASHRAE 62-
1989 (see the table that is reproduced in
Appendix B).
28 Section 4
-------
SarrpleFam
This form is to be used differently depending on whether the goal is to prevent or diagnose IAQ problems.
During development of a profile, this form should be used to record more general information about the entire
building; during an investigation, the form should be used to record more detailed information about the
complaint area and areas surrounding the complaint area or connected to it by pathways.
PROFILE AND DIAGNOSIS INFORMATION
Building Area
(Zone/Room)
Use**
Source of
Outdoor Air*
Mechanical
Exhaust?
(Write "No"
or estimate
cfm airflow)
Comments
DIAGNOSIS INFORMATION ONLY
Peak Number of
Occupants or
Sq. Ft. Floor Area**
Total Air
Supplied
(in cfm)***
Outdoor Air
Supplied
per Person or
per 1 50 sq.
Ft. Area****
Underventilation problems can occur
even in areas where ventilation rates
apparently meet ASHRAE guidelines;
proper distribution and mixing of supply
air with room air are also essential for
good ventilation.
If the information collected as you
develop the IAQ profile indicates that you
have one or more IAQ problems, Sections
6-8 provide guidance to help you deal with
them. If you need to prioritize these prob-
lems, consider the apparent seriousness of
their consequences. For example, combus-
tion gas odors demand a more rapid
respons than thermostats that are out of
calibration.
Developing an IAQ Profile 29
-------
IVbnacjng Buldngs for
IAQ
Ihe relationships among building
owners, management, staff, and occupants
are an important factor in decisions that
affect indoor air quality. The objectives of
the major players in these relationships
may be very different. Occupants want the
building to be pleasant, safe, and attractive;
if they are paying tenants, they also want
to get the maximum use out of the space
they rent for the least cost. Building
owners and management want to maintain
a reputation for providing quality property
at reasonable cost, but also need to derive a
profit. Facility staff are often caught in the
middle, trying to control operating and
maintenance costs while still keeping
occupants satisfied.
Regardless of the points on which they
may disagree, building occupants, staff,
and management share the goal of provid-
ing a healthy indoor environment. Recog-
nition of this common goal may help avoid
conflict when discussing lAQ-related
policies.
Any IAQ management system will be
successful only if it is organized to fit your
specific building. It would not be appropri-
ate for this document to prescribe any
single approach. However, the skills
associated with IAQ management activities
will be identified to help building manage-
ment decide who will be best able to carry
them out. Education and training programs
for staff and building occupants should be
provided to ensure that new procedures are
understood and adopted.
Managing a building for good indoor air
quality involves reviewing and amending
current practice (and establishing new
procedures, if necessary) to:
Operate and maintain HVAC equipment
keep all equipment and controls in proper
working order
keep interior of equipment and ductwork
clean and dry
Oversee activities of staff, tenants, contrac-
tors, and other building occupants that
impact indoor air quality
smoking
housekeeping
building maintenance
shipping and receiving
pest control
food preparation and other special uses
Maintain communications with occupants
so that management will be informed of
complaints about the indoor environment
in a timely way
identify building management and staff
with IAQ responsibilities
use health and safety committees
Educate staff, occupants, and contractors
about their responsibilities in relation to
indoor air quality
staff training
lease arrangements
contracts
Identify aspects of planned projects that
could affect indoor air quality and
manage projects so that good air quality
is maintained
redecorating, renovation, or remodeling
relocation of personnel or functions
within the building
new construction
[DEVELOPING AN IAQ
IVHNAGEIVENT PLAN
The chart on page 32 shows the elements
of an IAQ management plan. Develop-
ment of the management plan involves
reviewing and revising staff responsibili-
ties so that IAQ considerations become
incorporated into routine procedures.
IAQ management
systems vull oriybe
successful if they
organized to fit your
specific bulking.
Managing Buildings for Good IAQ 31
-------
Organizations may assign responsibility for
operations, recordkeeping, purchasing,
communications, planning, and policy-
making in many different ways. However,
the key elements of good IAQ management
remain the same:
Reach an understanding of the funda-
mental influences that affect indoor air
quality in your building by:
becoming familiar with literature on IAQ
keeping abreast of new information
Select an IAQ manager with:
clearly defined responsibilities
adequate authority and resources
FIGURE 5-1: Developing an IAQ
START
I
Select an IAQ Manager
Review IAQ Profile
and Existing Records
Assign Staff
Responsibilities/Train Staff
Facilities Operation
and Maintenance
Housekeeping
Pest Control
Tenant Relations
Renovation
Redecorating
Remodeling
Smoking
Use the lAQprofile and other available
information to:
evaluate the design, operation, and usage
of the building
identify potential IAQ problem locations
identify staff and contractors whose
activities affect indoor air quality
Review and revise staff responsibilities to
ensure that responsibilities that may affect
indoor air quality are clearly assigned. In
addition, establish lines of communication
for sharing information pertaining to:
equipment in need of repair or
replacement
plans to remodel, renovate, or redecorate
new uses of building space or increases in
occupant population
installation of new equipment
Review standard procedures and make
necessary revisions to promote good
indoor air quality, such as:
terms of contracts (e.g., pest control,
leases)
scheduling of activities that produce dust,
emissions, odors
scheduling of equipment operation,
inspection, and maintenance
specifications for supplies (e.g., cleaning
products, construction materials, furnish-
ings)
policy regarding tobacco smoking within
the building
Review the existing recordkeeping system
and make necessary revisions to:
establish a system for logging IAQ-
related complaints
obtain Material Safety Data Sheets for
hazardous materials used and stored in the
building
Educate building staff, occupants, and
contractors about their influence on
indoor air quality by:
establishing a health and safety committee
instituting training programs as needed
32 Sections
-------
IAQ problems may occur even in
buildings whose owners and managers
conscientiously apply the best available
information to avoid such problems.
Those who can demonstrate their ongoing
efforts to provide a safe indoor environ-
ment are in a strong legal and ethical
position if problems do arise.
Select an IAQ IVbnager
IAQ management will be facilitated if one
individual is given overall responsibility
for IAQ. Whether or not this person is
given the title of "IAQ Manager," he or
she should have a good understanding of
the building's structure and function and
should be able to communicate with
tenants, facility personnel, and building
owners or their representatives about IAQ
issues.
The IAQ manager's ongoing responsi-
bilities might include:
developing the IAQ profile
overseeing the adoption of new
procedures
establishing a system for communicating
with occupants about IAQ issues
coordinating staff efforts that affect
indoor air quality, and making sure that
staff have the information (e.g., operat-
ing manuals, training) and authority to
carry out their responsibilities
reviewing all major projects in the
building for their IAQ implications
reviewing contracts and negotiating with
contractors (e.g., cleaning services, pest
control contractors) whose routine
activities in the building could create
IAQ problems
periodically inspecting the building for
indicators of IAQ problems
managing lAQ-related records
responding to complaints or observations
regarding potential IAQ problems
conducting an initial walkthrough
investigation of any IAQ complaints
PRODUCTS OF THE REVIEWOF THE IAQ PROFILE
AND OTHER EXISTING RECORDS
a priority list of locations and activities within the building that will
require special attention in order to prevent indoor air quality problems
a list of staff and contractors whose responsibilities need to be
included in the IAQ management plan
Review IAQ Profile and Other
Existing Records
If the IAQ manager was not actively
involved in developing the IAQ profile,
one of the first tasks will be to review the
profile carefully. The manager can start by
also identifying building locations with a
potential for IAQ problems, staff and
contractors whose activities impact indoor
air quality, and other building occupants
whose activities impact indoor air quality.
In addition to information from the IAQ
profile, it may be helpful to review lease
forms and other contractual agreements for
an understanding of the respective legal
responsibilities of the building manage-
ment, tenants, and contractors. Incorpora-
tion of IAQ concerns into legal documents
helps to ensure the use of proper materials
and procedures by contractors and can help
to limit the load placed on ventilation
equipment by occupant activities.
IAQ i
twill
naga
be facilitated if <
incf victual is given
overall responsibility
for IAQ
Assign Responsibilities/
Train Staff
The assignment of responsibilities varies
widely between organizations, depending
upon the routine activities to be carried out
and the capabilities of the available
personnel. It would not be appropriate for
this document to suggest how lAQ-related
responsibilities should be allocated in your
organization. For example, issues of
access in buildings with tenant-occupied
space highlight the need for cooperation
between building managers and the
Managing Buildings for Good IAQ 33
-------
A clean mechanical room,
free of tracked-in dirt and
stored chemicals, is an
important element in the
prevention of indoor air
quality problems. Airborne
contaminants in the
mechanical room can be
drawn into ductwork through
return air openings or
unsealed seams in return
ducts and circulated
throughout the building.
tenants' office managers. The building
staff may be limited in its access to tenant
spaces and tenants may not have access to
building operations areas such as mechani-
cal rooms, yet both tenants and building
management have responsibilities for
maintaining good indoor air quality.
Facility personnel are not generally
trained to think about IAQ issues as they
go about their work. Even though building
staff may be observing events and condi-
tions that would indicate potential prob-
lems to an experienced IAQ investigator,
the staff member's attention may be
directed elsewhere. As new practices are
introduced to prevent indoor air quality
problems, an organized system of
recordkeeping will help those practices to
become part of routine operations and to
"flag" decisions that could affect IAQ
(e.g., renovations, new tenants). The best
results can be achieved by taking time to
think about the established channels of
communication within your organization,
so that new forms can be integrated into
decisionmaking with minimum disruption
of normal procedures.
Using information from the IAQ
profile, the IAQ manager should work
with staff and contractors to ensure that
building operations and planning processes
incorporate a concern for indoor air
quality. New procedures, recordkeeping
requirements, or staff training programs
may be needed. (Growing interest in IAQ
is stimulating government agencies and
private sector organizations to develop
training programs. See Appendix G for
additional information.) The flow of
information between the IAQ manager and
staff, occupants, and contractors is
particularly important. Good indoor air
quality requires prompt attention to
changing conditions that could cause IAQ
problems, such as installation of new
equipment or furnishings, increases in
occupant population, or new uses of
rooms.
Facility Operation and Maintenance
Indoor air quality can be affected both
by the quality of maintenance and by the
materials and procedures used in operating
and maintaining the building components
including the HVAC system.
Facility staff who are familiar with
building systems in general and with the
features of their building in particular are
an important resource in preventing and
resolving indoor air quality problems.
Facility personnel can best respond to
indoor air quality concerns if they under-
stand how their activities affect indoor air
quality. It may be necessary to change
existing practices or introduce new
procedures in relation to:
Equipment operating schedules: Confirm
that the timing of occupied and unoccu-
pied cycles is compatible with actual
occupied periods, and that the building is
flushed by the ventilation system before
occupants arrive. ASHRAE 62-1989
provides guidance on lead and lag times
for HVAC equipment. In hot, humid
34 Section 5
-------
climates, ventilation may be needed during
long unoccupied periods to prevent mold
growth.
Control of odors and contaminants:
Maintain appropriate pressure relationships
between building usage areas. Avoid
recirculating air from areas that are strong
sources of contaminants (e.g., smoking
lounges, chemical storage areas, beauty
salons). Provide adequate local exhaust
for activities that produce odors, dust, or
contaminants, or confine those activities to
locations that are maintained under
negative pressure (relative to adjacent
areas). For example, loading docks are a
frequent source of combustion odors.
Maintain the rooms surrounding loading
docks under positive pressure to prevent
vehicle exhaust from being drawn into the
building. Make sure that paints, solvents,
and other chemicals are stored and handled
properly, with adequate (direct exhaust)
ventilation provided. If local filter traps
and adsorbents are used, they require
regular maintenance. Have vendors
provide Material Safety Data Sheets
(MSDSs).
Ventilation quantities: Compare outdoor
air quantities to the building design goal
and local and State building codes and
make adjustments as necessary. It is also
informative to see how your ventilation
rate compares to ASHRAE 62-1989,
because that guideline was developed with
the goal of preventing IAQ problems.
(Note: Increasing ventilation quantities to
meet ASHRAE guidelines may exceed the
capacity of HVAC equipment to condition
the air.)
HVAC equipment maintenance sched-
ules: Inspect all equipment regularly (per
recommended maintenance schedule) to
ensure that it is in good condition and is
operating as designed (i.e., as close to the
design setpoints for controls as possible).
Most equipment manufacturers provide
recommended maintenance schedules for
their products. Components that are
exposed to water (e.g., drainage pans,
coils, cooling towers, and humidifiers)
require scrupulous maintenance to prevent
microbiological growth and the entry of
undesired microbiologicals or chemicals
into the indoor airstream.
HVAC inspections: Modify the HVAC
Checklists (reproduced in Tab V) as
necessary so that they are appropriate for
inspection of the specific equipment in
your building. Be thorough in conducting
these inspections. Items such as small
exhaust fans may operate independently
from the rest of the HVAC system and are
often ignored during inspections. As
equipment is added, removed, or replaced,
document any changes in function,
capacity, or operating schedule for future
reference. It may also be helpful to store
equipment manuals and records of equip-
ment operation and maintenance in the
same location as records of occupant
complaints for easy comparison if IAQ
problems arise.
Building maintenance schedules: Try
to schedule maintenance activities that
interfere with HVAC operation or produce
odors and emissions (e.g., painting, roofing
operations) so that they occur when the
building is unoccupied. Inform occupants
when such activities are scheduled and, if
possible, use local ventilation to ensure
that dust and odors are confined to the
work area.
Purchasing: Review the general informa-
tion provided by MSDS and request
information from suppliers about the
chemical emissions of materials being
considered for purchase.
Note: At present there is no general
system for certifying or labeling low-
emission products nor is there a standard
procedure for building managers to use in
gathering emissions data on products they
are considering for purchase. Limited
information on some materials such as
tharaugj*i in
H\/AC
inspections. Items
such as small exhaust
the rest of the system
and are often inored
during
Managing Buildings for Good IAQ 35
-------
PREVENTIVE MAINTENANCE
An HVAC system requires adequate preventive maintenance (PM) and
prompt attention to repairs in order to operate correctly and provide
suitable comfort conditions and good indoor air quality. The HVAC
system operator(s) must have an adequate understanding of the overall
system design, its intended function, and its limitations. The preventive
maintenance program must be properly budgeted and implemented, not
merely planned on paper.
A well-implemented PM plan will improve the functioning of the
mechanical systems and usually save money when evaluated on a life-
cycle basis. However, in some buildings, because of budgetary
constraints, maintenance is put off until breakdowns occur or complaints
arise, following the "if it isn't broken, don't fix it" philosophy. This type of
program represents a false economy and often increases the eventual
cost of repairs.
Poor filter maintenance is a common example of this phenomenon.
Filters that are not changed regularly can become a bed for fungal
growth, sometimes allowing particles or microorganisms to be distrib-
uted within the building. When filters become clogged, the fans use
more energy to operate and move less air. If the filters are an inexpen-
sive, low-efficiency type that becomes clogged and then "blows out," the
coils then accumulate dirt, causing another increase in energy con-
sumption. Poor air filter efficiency and poor maintenance may cause
dirt to build up in ducts and become contaminated with molds, possibly
requiring an expensive duct cleaning operation.
General elements of a PM plan include:
periodic inspection, cleaning, and service as warranted
adjustment and calibration of control system components
maintenance equipment and replacement parts that are of good
quality and properly selected for the intended function
Critical HVAC system components that require PM in order to
maintain comfort and deliver adequate ventilation air include;
outdoor air intake opening
damper controls
air filters
drip pans
cooling and heating coils
fan belts
humidification equipment and controls
distribution systems
exhaust fans
Some private sector organizations have developed guidance on
preventive maintenance. (See discussion in Guidelines of Care
Developed by Trade Associations on page 43.)
pressed-wood products is available, and
more may be expected in the future.
Public and private sector organizations are
working to develop product testing
procedures for acceptance by such organi-
zations as the American Society for
Testing and Materials (ASTM).
Preventive maintenance management:
Maintenance "indicators" are available to
help facility staff determine when routine
maintenance is required. For example, air
filters are often neglected (sometimes due
to reasons such as difficult access) and fail
to receive maintenance at proper intervals.
Installation of an inexpensive manometer,
an instrument used to monitor the pressure
loss across a filter bank, can give an
immediate indication of filter condition
without having to open the unit to visually
observe the actual filter.
Computerized systems are available that
can prompt your staff to carry out mainte-
nance activities at the proper intervals.
Some of these programs can be connected
to building equipment so that a signal is
transmitted to your staff if a piece of
equipment malfunctions. Individual areas
can be monitored for temperature, air
movement, humidity, and carbon dioxide,
and new sensors are constantly entering the
market. These sensors can be programmed
to record data and to control multiple
elements of the HVAC system.
Housekeeping
Indoor air quality complaints can arise
from inadequate housekeeping that fails to
remove dust and other dirt. On the other
hand, cleaning materials themselves
produce odors and emit a variety of
chemicals.
As they work throughout your building,
cleaning staff or contractors may be the
first to recognize and respond to potential
IAQ problems. Educate them about topics
such as the following:
36 Section 5
-------
Cleaning schedules: Consider how
cleaning activities are scheduled. Manag-
ers may want to schedule the use of some
cleaning agents that introduce strong odors
or contaminants during unoccupied
periods. However, make sure that fumes
from cleaning products are eliminated
before air handling systems switch to their
"unoccupied" cycles.
Purchasing: Become more familiar with
the chemicals in cleaning and maintenance
products and their potential toxicity.
Select the safest available materials that
can achieve your purpose. Review the
information provided by product labels
and Material Safety Data Sheets. Request
information from suppliers about the
chemical emissions of products being
considered for purchase.
Material handling and storage: Review
the use of cleaning materials to ensure
proper use and storage.
Trash disposal: Follow proper trash
disposal procedures. If there is a restau-
rant in the building, require daily pick-up
of perishable refuse. Ensure that the
containers are covered, pest control is
effective, and that the trash collection area
is cleaned at least daily.
Shipping and Receiving
Shipping and receiving areas can create
indoor air quality problems regardless of
the types of materials being handled.
Vehicle exhaust fumes can be minimized
by prohibiting idling at the loading dock.
This is particularly important if the loading
dock is located upwind of outdoor air
intake vents. You can also reduce drafts
and pollutant entry by pressurizing interior
spaces (e.g., corridors) and by keeping
doors closed when they are not in use.
A good preventive maintenance program
can help a facility manager identify and
correct problems before they occur. If this
fan belt breaks, the area served by the air
handling unit may be without ventilation. If
it is slipping, it is already reducing the
airflow.
Atermiticide misapplication resulted in an
indoor air quality problem in this school.
Detectable levels of chlordane were found
in both wipe (surface) and air samples near
the injection holes drilled into the ground
floor. Note the small white circles near the
wall. (Under an agreement with EPA,
manufacturers have withdrawn chlordane
from sale.) Proper application methods are
important for all pesticides.
Managing Buildings for Good IAQ 37
-------
INTEGRATED PEST MRNAGEIVEIXir
Integrated Pest Management (IPM) is a coordinated approach to pest
control intended to prevent unacceptable levels of pests, while causing
the least possible hazard to people, property, and the environment and
using the most cost-effective means. IPM uses a combination of tactics,
including sanitation, monitoring, habitat modification, and the judicious
application of pesticides when absolutely necessary.
IPM methods include:
improved sanitation (e.g., removing food from desks, cleaning)
inspection and monitoring of pest population sites
managing waste (e.g., keeping refuse in tight containers, locating
waste containers away from building if possible)
maintaining structures (e.g., fixing leaking pipes promptly,
sealing cracks)
adding physical barriers to pest entry and movement (e.g.,
screens for chimneys, doors, and windows; air curtains)
modifying habitats (e.g., removing clutter, relocating outside light
fixtures away from doors)
using traps (e.g., light traps, snap traps, and glue boards)
using pesticides judiciously
An efficient IPM program will integrate pest management planning
with preventive maintenance, housekeeping practices, landscaping,
occupant education, and staff training.
Pest Control
Pest control activities that depend upon
the use of pesticides involve the storage,
handling, and application of materials that
can have serious health effects. Common
construction, maintenance practices, and
occupant activities provide pests with air,
moisture, food, warmth, and shelter.
Caulking or plastering cracks, crevices, or
holes to prevent harborage behind walls
can often be more effective than pesticide
application at reducing pest populations to
a practical minimum.
Integrated Pest Management (IPM) is a
low-cost approach to pest control based
upon knowledge of the biology and
behavior of pests. Adoption of an IPM
program can significantly reduce the need
for pesticides by eliminating conditions
that provide attractive habitats for pests.
If an outside contractor is used for pest
control, it is advisable to review the terms
of the contract and include IPM principles
where possible. The following items
deserve particular attention.
Pest control schedule: Schedule pesticide
applications for unoccupied periods, if
possible, so that the affected area can be
flushed with ventilation air before occu-
pants return. Pesticides should only be
applied in targeted locations, with mini-
mum treatment of exposed surfaces. They
should be used in strict conformance with
manufacturers' instructions and EPA
labels. General periodic spraying may not
be necessary. If occupants are to be
present, they should be notified prior to the
pesticide application. Particularly suscep-
tible individuals could develop serious
illness even though they are only mini-
mally exposed.
Materials selection, handling, and
storage: Select pesticides that are species
specific and attempt to minimize toxicity
for humans and non-target species. Ask
contractors or vendors to provide EPA
labels and MSDSs. Make sure that
pesticides are stored and handled properly
consistent with their EPA labels.
Ventilation of areas where pesticides are
applied: If only limited areas of the
building are being treated, adjust the
HVAC system so that it does not distribute
contaminated air throughout the rest of the
building. Consider using temporary
exhaust systems to remove contaminants
during the work. It may be necessary to
modify HVAC system operation during
and after pest control activities (e.g.,
running air handling units on 100%
outdoor air for some period of time or
running the system for several complete air
exchanges before occupants re-enter the
treated space).
38 Section 5
-------
IVATERIAL SAFETY
DATASHEETS
Under OSHA regulations, responsible parties are required to document information on
potentially hazardous products. These Material Safety Data Sheets (MSDSs) may be of
limited help in identifying some products that may pose IAQ concerns. However, profes-
sional judgment and collection of additional information may be necessary in order to make
full use of the MSDS. The following table summarizes some of the issues to keep in mind
when deciding whether information from MSDSs is applicable to emission sources and
exposures of concern in a building.
Item
Substances Covered
Possible Uses
MSDSs may identify significant
airborne contaminants
OomrcrCs
MSDSs may not be available onsite for many
products
some components are listed as proprietary
and are not disclosed
MSDSs do not always highlight products
most likely to be airborne
contaminant byproducts inadvertently
formed during manufacture won't always be
listed
Protection^
First Aid
may suggest precautions for
conducting source inspection
usually relates only to high-level, worst-case
exposures in general industry
Health Effects
generally presents types of health
effects that may be expected primarily
at high level (e.g., industrial)
exposures
symptoms listed may not occur at low-level
concentrations found in indoor air
MSDSs may not include more subtle IAQ
aspects such as nuisance factors and
sensitivity to mixtures
Physical Data
odor description may help identify
sources
volatility may suggest which products
are likely to be airborne
contaminants to expect in event of a
fire or decomposition may be listed
reactivity data may suggest potential
problems with storage or use
reference material on how to use physical
data information to predict IAQ impacts
may be scarce
Control
identifies proper storage and packaging
procedures
identifies steps for cleanup of gross
spills
many office chemicals are kept in much
smaller amounts than found in industrial
settings
spill cleanup may not eliminate airborne
contamination
does not specify routine emission controls
A reasonable effort should be made to collect available MSDSs during IAQ profile develop-
ment. Care should be taken to consider information that is relevant to IAQ concerns. Other
important indicators of how a particular product may affect IAQ are available from direct odor
and dust observations, a review of work practices and interviews with operators and occu-
pants. The manufacturer is a good source of follow-up information on a given product (phone
number should be included on each MSDS).
Managing Buildings for Good IAQ 39
-------
It is important for building
occupants to understand that
their activities can create
indoor air quality problems.
Smoking releases both
carcinogenic and irritating
substances into the air.
Occupant Relations
Managing occupant relations to prevent
IAQ problems involves: allocating space
and monitoring the use of building areas to
isolate odor- and contaminant-producing
activities and avoid re-entrainment; estab-
lishing a communication strategy that is
responsive to complaints and provides
tenants with information about their role in
preventing indoor air quality problems;
and modifying employee manuals or lease
agreements as necessary to clarify the
responsibilities of occupants and building
management. A health and safety commit-
tee or joint tenant-management IAQ task
force that represents all of the major inter-
est groups in the building can be very
helpful in disseminating information and
fostering a cooperative approach to IAQ
management. See Section 3 for a discus-
sion of these points.
Renovation, Redecorating, and
Remodeling
Renovation, redecorating, and re-
modeling activities can create indoor air
problems by producing dust, odors, micro-
biologicals and their spores, and emissions.
It is difficult to prevent IAQ problems if
some building areas are undergoing reno-
vation while adjoining areas continue
normal operations.
Close monitoring of renovation,
redecorating, and remodeling projects is
recommended. The following suggestions
may be helpful:
Working with professional consultants:
Communicate your concern about prevent-
ing indoor air quality problems to the
engineer, architect, interior designer, or
other professionals involved in the project.
Product selection: Specify products and
processes that minimize odors and emis-
sions, while maintaining adequate safety
and efficacy. Review the general informa-
tion provided by the product labels and
MSDSs. Request information from
suppliers about the chemical emissions of
products being considered for purchase.
Work schedules: Schedule activities that
produce dust, odors, or emissions for
unoccupied periods if possible.
Isolation of work areas: Block off return
registers so that contaminants are not
recirculated from the demolition/construc-
tion area into adjoining areas, and install
temporary barriers to confine dust and
noise. If possible, install temporary local
exhaust to remove odors and contaminants,
and check to confirm that the temporary
ventilation system is operating as planned.
Installation of new furnishings: Ask
suppliers to store new furnishings in a
clean, dry, ventilated location so that
volatile organic compounds will be emitted
before installation. Minimize the use of
adhesives during installation or specify
low-emitting products. After new furnish-
ings are installed, increase the ventilation
rate to flush the area with outdoor air and
dilute emissions.
Smoking
Although there are many potential
sources of indoor air pollution, both
research and field studies have shown that
environmental tobacco smoke (ETS) is one
of the most widespread and harmful indoor
air pollutants. Environmental tobacco
smoke is a combination of sidestream
40 Section 5
-------
smoke from the burning end of the
cigarette, pipe, or cigar and the exhaled
mainstream smoke from the smoker. ETS
contains over 4,000 chemicals; 43 of
which are known animal or human
carcinogens. Many other chemicals in
ETS are tumor promoters, tumor initiators,
co-carcinogens (i.e., chemicals that are
able to cause cancer when combined with
another substance), or cancer precursors
(i.e., compounds that can make it easier to
form other carcinogenic chemicals).
In 1986, The Health Consequences of
Involuntary Smoking: A Report of the
Surgeon General on Environmental
Tobacco Smoke concluded that ETS was a
cause of lung cancer in healthy non-
smokers and that "the scientific case
against involuntary smoking as a public
health risk is more than sufficient to justify
appropriate remedial action, and the goal
of any remedial action must be to protect
the non-smoker from environmental
tobacco smoke." In the same year, the
National Research Council of the National
Academy of Sciences issued a report,
Environmental Tobacco Smoke: Measur-
ing Exposures and Assessing Health
Effects, which also concluded that passive
smoking increases the risk of lung cancer
in adults.
In June 1991, NIOSH issued a Current
Intelligence Bulletin (#54) on ETS in the
workplace that dealt with lung cancer and
other health effects. In its Bulletin,
NIOSH concluded that the weight of
evidence is sufficient to conclude that ETS
can cause lung cancer in non-smokers (i.e.,
those who inhale ETS). It recommended
that the preferable method to protect non-
smokers is the elimination of smoking
indoors and that the alternative method is
to require that smoking be permitted only
in separately ventilated smoking areas.
The NIOSH Bulletin emphasized that
provision of such isolated areas should be
viewed as an interim measure until ETS
can be completely eliminated indoors.
ngtoalj
iicport of the SuxjQci i
against inudLrtary
smokincj is time tfvm
SLrfficient toJLBtify
action to protect tli
non-smoker from
environmental to-
bacco smoke."
i ASSIGNMENT OF
RESPONSIBILITIES AND REVIEWQF TRAINING
job descriptions and/or contracts, work procedures, and schedules
revised to reflect indoor air quality concerns
procedures for reviewing purchases of supplies, new projects,
contracts, and policies in relation to indoor air quality
smoking policy revisions, if necessary
plans for educating occupants and training staff training in relation to
indoor air quality
Smoking areas must be separately
ventilated, negatively pressurized in
relation to surrounding interior spaces, and
supplied with much more ventilation than
non-smoking areas. The NIOSH Bulletin
also recommends that the air from the
smoking area should be exhausted directly
outdoors and not recirculated within the
building or vented with the general exhaust
for the building. ASHRAE Standard 62-
1989 recommends that smoking areas be
supplied with 60 cubic feet per minute (60
cfm) per occupant of outdoor air; the
standard also recognized that using transfer
air, which is pulled in from other parts of
the building, to meet the standard is
common practice.
Both EPA and NIOSH advise that
building owners or facility managers
considering the introduction of smoking
restrictions should implement smoking
cessation programs. In addition, employ-
ees and labor unions should be involved in
the development of non-smoking policies
in the workplace.
(Refer to Appendix G for citations on all
the publications mentioned in this section.
See especially NIOSH Current Intelligence
Bulletin (#54), Environmental Tobacco
Smoke in the Workplace: Lung Cancer
and Other Health Effects. Additional
resources on ETS, including an assessment
of respiratory disorders in children and
lung cancer risks in adults, and a guide to
developing effective smoking policies, will
be available from EPA early in 1992.)
Managing Buildings for GoodlAQ 41
-------
Sample Form
Management Checklist
Item
Date Begun
or Completed
(as applicable)
Responsible Person
(name, telephone)
Location
("NA"ifthe item is not
applicable to this building)
IAQ PROFILE
Collect and Review
Existing Records
HVAC design data, operating instructions
and manuals
HVAC maintenance and calibration
records, testing and balancing reports
Inventory of locations where
occupancy, equipment, or building
use has changed
Inventory of complaint locations
Conduct a VtfiHdhraugto
ion of the Buldng
List of responsible staff and/or
contractors, evidence of training,
and job descriptions
Identification of areas where positive or
negative pressure should be maintained
The IAQ Management Checklist shown
in part here and included in full within Tab
V can be used to help confirm that you
have accounted for the major factors that
could cause IAQ problems in your
building.
4 2 Section 5
-------
GUIDELINES OF
CARE DEVELOPED
BY TRADE
ASSOCIATIONS
The following associations have developed guidelines of care that may have a direct or
indirect impact on indoor air quality. These standards are described below so that
building management may become aware of them. Neither EPA nor NIOSH endorse
these standards.
Air Condtionlng
of
America
(ACCA)
Technical Reference Bulletin Series. Indoor air quality is one of the topics covered
in this series of technical bulletins on heating, ventilation and air conditioning
(HVAC). Bulletins can be filed in the ACCA Technical Reference Notebook. The Air
Side Design tab of the notebook includes bulletins devoted to indoor air quality
control.
Air Condtioning and
Refrigeration Insti-
tute (AM)
Air Conditioning and Refrigeration Equipment General Maintenance Guidelines for
Improving the Indoor Environment (1991). General maintenance requirements for
heating ventilation, air conditioning,and refrigeration (HVACR) equipment.
Specific equipment/component maintenance is given for the following: air cleaning
systems; ducts; registers/diffusers and air terminals; dampers/economizers; drain pans;
air handlers; humidifiers; package terminal units; and evaporator, condenser, hydronic
and economizer coils. The guidelines do not supersede any maintenance instructions
that are provided by the manufacturer. In addition, the Institute has issued an Indoor Air
Quality Briefing Paper that addresses the interactions between HVACR equipment and
the quality of indoor air.
Associated Air
Balance Council
CAABQ
National Standards for Testing and Balancing Heating,Ventilation, and Air Conditioning
Systems (1989). Establishes a minimum set of field testing and balancing standards and
provides comprehensive and current data on testing and balancing HVAC systems.
Chapters receiving special attention include Cooling Tower Performance Tests, Sound
Measurements, Vibration Measurements, Fume Hoods, and AABC General Specifica-
tions. The book contains a complete index to the technical data provided.
National
Environmental
(NEBB)
Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems
(1991). A "how-to" set of procedural standards that provide systematic methods for
testing, adjusting, and balancing (TAB) of HVAC systems. Includes sections on TAB
instruments and calibration, report forms, sample specifications, and engineering tables
and charts. A valuable innovation is the "Systems Ready to Balance" start-up checklist
to help organize jobs systematically. Other features include; additional engineering data,
condensed duct design tables/charts, hydronic design tables/charts, and pertinent HVAC
equations in U.S. and metric units.
National Rest Control
Association
(NPCA)
Good Practice Statements. Periodically updated, officially approved and adopted by the
Association's Board of Directors, these "Good Practice Statements" are designed as
guidelines for performing various services rather than standards of operation. In
addition, the Association produces a self-study series for technicians that covers five
areas of pest control, management manuals, an encyclopedia of structural pest control,
a number of specific subject matter technical reference manuals, and a pamphlet series.
Sheet IVetal and
Air Conditiaring
National
Association
(SIVRCNA)
HVAC Duct Construction Standards Metal and Flexible (1985). Primarily for commer-
cial and institutional work, this set of construction standards is a collection of material
from earlier editions of SMACNA's low-pressure, high-pressure, flexible duct, and duct
liner standards. In addition, SMACNA has published a manual entitled Indoor Air Quality
that contains basic information on many aspects of indoor air quality and guidance on
conducting building evaluations and indoor air quality audits. Other related SMACNA
publications include HVAC Duct Systems Inspection Guide, HVAC SystemsTesting,
Adjusting and Balancing, and HVAC
Air Duct Leakage Test Manual.
Managing Buildings for GoodlAQ 4 3
-------
Building Air Quality
linn
mill
HUH
Printed on Recycled Paper
-------
I he goal of the diagnostic building
investigation is to identify and solve the
indoor air quality complaint in a way that
prevents it from recurring and that does not
create other problems. This section
describes a method for discovering the
cause of the complaint and presents a
"toolbox" of diagnostic activities to assist
you in collecting information.
Just as a carpenter uses only the tools
that are needed for any given job, an IAQ
investigator should use only the investiga-
tive techniques that are needed. Many
indoor air quality complaints can be
resolved without using all of the diagnostic
tools described in this chapter. For
example, it may be easy to identify the
source of cooking odors that are annoying
nearby office workers and solve the
problem by controlling pressure relation-
ships (e.g., installing exhaust fans) in the
food preparation area. Similarly, most
mechanical or carpentry problems prob-
ably require only a few of the many tools
you have available and are easily accom-
plished with in-house expertise.
The use of in-house personnel builds
skills that will be helpful in minimizing
and resolving future problems. On the
other hand, some jobs may be best handled
by contractors who have specialized
knowledge and experience. In the same
way, diagnosing some indoor air quality
problems may require equipment and skills
that are complex and unfamiliar. Your
knowledge of your organization and
building operations will help in selecting
the right tools and deciding whether in-
house personnel or outside professionals
should be used in responding to the
specific IAQ problem.
Start (reason far
Initial walkthrough
preparation
visual inspection
talk with occupants and staff
Yes
Do you have
an explanation
for the complaint ?
No
Collect additional
information about
building occupants
the HVAC system
pollutant pathways
pollutant sources
(sample contaminants if needed)
Develop one or more hypotheses
to explain the problem. Test by
manipulating building conditions
or exposure, or by performing
appropriate tests.
Do results
support your
hypothesis ?
FIGURE 6-1:
Conducting an IAQ Investigation
Note: Outside assistance may be needed at any
point in the investigation, depending upon the
complexity of the problem, the skills available in-
house, time pressures, or other factors.
Make necessary
changes so that
the problem will
not recur.
Diagnosing IAQ Problems 4 5
-------
ThelAQii
is often a repetitive
cycle of information-
rin^ hypothesis
hypothesis testing.
OVERVIEW CONDUCTING AN
I AQ INVESTIGATION
An IAQ investigation begins with one or
more reasons for concern, such as occu-
pant complaints. Some complaints can be
resolved very simply (e.g., by asking a few
common sense questions of occupants and
facility staff during the walkthrough). At
the other extreme, some problems could
require detailed testing by an experienced
IAQ professional. In this section "the
investigator" refers to in-house staff
responsible for conducting the IAQ
investigation.
The flowchart on page 45 shows that
the IAQ investigation is a cycle of infor-
mation-gathering, hypothesis formation,
and hypothesis testing. The goal of the
investigation is to understand the IAQ
problem well enough so that you can solve
it. Many IAQ problems have more than
one cause and may respond to (or require)
several corrective actions.
Initial
An initial walkthrough of the problem area
provides information about all four of the
basic factors influencing indoor air quality
(occupants, HVAC system, pollutant
pathways, and contaminant sources). The
initial walkthrough may provide enough
information to resolve the problem. At the
least, it will direct further investigation.
For example, if the complaint concerns an
odor from an easily -identified source (e.g.,
cooking odors from a kitchen), you may
want to study pollutant pathways as a next
step, rather than interviewing occupants
about their patterns of discomfort.
Developing £
I lypoU loses
nd Testing
As you develop an understanding of how
the building functions, where pollutant
sources are located, and how pollutants
move within the building, you may think
of many "hypotheses," potential explana-
tions of the IAQ complaint. Building
occupants and operating staff are often a
good source of ideas about the causes of
the problem. For example, they can
describe changes in the building that may
have occurred shortly before the IAQ
problem was noticed (e.g., relocated
partitions, new furniture or equipment).
Hypothesis development is a process
of identifying and narrowing down
possibilities by comparing them with your
observations. Whenever a hypothesis
suggests itself, it is reasonable to pause
and consider it. Is the hypothesis
consistent with the facts collected so far?
You may be able to test your hypothesis
by modifying the HVAC system or
attempting to control the potential source
or pollutant pathway to see whether you
can relieve the symptoms or other condi-
tions in the building. If your hypothesis
successfully predicts the results of your
manipulations, then you may be ready to
take corrective action. Sometimes it is
difficult or impossible to manipulate the
factors you think are causing the IAQ
problem; in that case, you may be able to
test the hypothesis by trying to predict how
building conditions will change over time
(e.g., in response to extreme outdoor
temperatures).
Collecting Adcitional
If your hypothesis does not seem to be a
good predictor of what is happening in the
building, you probably need to collect
more information about the occupants,
HVAC system, pollutant pathways, or
contaminant sources. Under some
circumstances, detailed or sophisticated
measurements of pollutant concentrations
or ventilation quantities may be required.
Outside assistance may be needed if
repeated efforts fail to produce a successful
hypothesis or if the information required
calls for instruments and procedures that
are not available in-house.
46 Section 6
-------
ResUts of the Investigation
Analysis of the information collected
during your IAQ investigation could
produce any of the following results:
The apparent cause(s) of the complaint(s)
are identified.
Remedial action and follow-up evaluation
will confirm whether the hypothesis is
correct.
Other lAQproblems are identified that
are not related to the original complaints.
These problems (e.g., HVAC malfunc-
tions, strong pollutant sources) should be
corrected when appropriate.
A better understanding of potential IAQ
problems is needed in order to develop a
plan for corrective action.
It may be necessary to collect more
detailed information and/or to expand the
scope of the investigation to include
building areas that were previously
overlooked. Outside assistance may be
needed.
The cause of the original complaint
cannot be identified.
A thorough investigation has found no
deficiencies in HVAC design or operation
or in the control of pollutant sources, and
there have been no further complaints. In
the absence of new complaints, the original
complaint may have been due to a single,
unrepeated event or to causes not directly
related to IAQ.
Using Outside Assistance
Some indoor air quality problems may be
difficult or impossible for in-house
investigators to resolve. Special skills or
instruments may be needed. Other factors
can also be important, such as the benefit
of having an impartial outside opinion or
the need to reduce potential liability from a
serious IAQ problem. You are best able to
make the judgment of when to bring in an
outside consultant. See Section 8 for a
discussion of hiring professional assistance
to solve an IAQ problem.
IIXITIAL WALKTHROUGH
An investigation may require one or many
visits to the complaint area. The amount
of preparatory work needed before the
initial walkthrough varies with the nature
and scope of the complaint and the
expertise of the investigator, among other
factors. For example, an in-house investi-
gator who is already familiar with the
layout and mechanical system in the
building may begin responding to a
complaint about discomfort by going
directly to the complaint area to check the
thermostat setting and see whether air is
flowing from the supply outlets.
If the investigator is not familiar with
the building or is responding to complaints
that suggest a serious health problem, more
preparation may be needed before the
initial walkthrough. The activities listed
below can be directed at a localized
"problem area" or extended to include the
entire building:
Collect easily-available information about
the history of the building and of the
complaints.
Identify known HVAC zones and com-
plaint areas.
Begin to identify potential sources and
pollutants (e.g., special use areas near the
complaint location). Having a copy of
mechanical and floor plans can be helpful
at this stage, especially if they are
reasonably up-to-date.
Notify the building occupants of the
upcoming investigation.
Tell them what it means and what to
expect.
Diagnosing IAQ Problems 4 7
-------
This improvised catch basin
is intended to collect water
seeping into the building from
below grade. Although the
catch basin "solves" the prob-
lem of uncontrolled water
leakage, it also provides an
indoor location that could
support the growth of
microbiologicals and create
IAQ problems.
Identify key individuals needed for access
and information.
A person familiar with the HVAC systems
in the building should be available to assist
the investigator at any time during the
onsite phase. Individuals who have
complained or who are in charge of
potential sources (e.g., housekeeping, non-
HVAC equipment) should be aware that
their information is important and should
be contacted for appointments or telephone
interviews if they will not be available
during the onsite visit.
The initial walkthrough provides an
opportunity to question complainants about
the nature and timing of their symptoms
and to briefly examine the immediate area
of the complaint. The investigator
attempts to identify pollutant sources and
types and observes the condition and
layout of the HVAC system serving the
complaint area. Facility staff can be asked
to describe the operating schedule of
equipment. Obvious problems (e.g.,
blocked diffusers, malfunctioning air
handlers) can be corrected to see if the
complaints disappear. The walkthrough
can solve many routine IAQ problems and
will suggest directions for a more complex
investigation, should one be necessary.
Some investigators avoid taking any
measurements during the initial walk-
through so that they are not distracted from
"getting the big picture." Others find that
using smoke sticks, digital thermometers,
and direct reading CO2 meters or detector
tubes to take occasional measurements
helps them develop a feel for the building.
It may help to keep the following
questions in mind during the initial
walkthrough:
Are there obvious pollutant sources? Do
they appear to be adequately controlled?
Are pollutant indicators present, such as
odors, excessive dust, or staining?
Are there sanitation problems (e.g.,
debris near outdoor air intake, visible
mold growth, major water damage) that
could be introducing air contaminants?
Are there any conditions or activities
occurring in or near the building that
could be related in timing, location and
health effects to the complaints?
Are there any deficiencies in the HVAC
system that serves the complaint area?
Does equipment serving the area (e.g.,
thermostats, diffusers, fans, dampers,
filters) appear to be operating, clean, and
in good condition?
Do operating procedures exist, and does
the staff follow them?
Do records indicate that the system was
commissioned (set, tested, and balanced)
after construction?
Do records indicate that system compo-
nents are regularly inspected, calibrated,
and adjusted?
48 Section 6
-------
Are there pathways and pressure differ-
ences which could be moving contami-
nants into the complaint area from the
outdoors or from other parts of the
building?
COLLECTING ADCmONAL
INFORMATION
Additional information will be needed if
the initial walkthrough does not identify
the cause of the problem. The following
pages present techniques for collecting
information about the occupant com-
plaints, HVAC system, pollutant pathways,
and pollutant sources and using that
information to develop a hypothesis that
could explain the problem. Common sense
will suggest the appropriate sequence of
steps during this part of the investigation.
For example, if the complaint is limited to
a single room, it makes sense to evaluate
pollutant pathways into that room before
attempting to inventory sources in loca-
tions outside of, but connected to, the
complaint area. On the other hand, if the
complaint involves a recognizable odor
(e.g., exhaust fumes), it may be more
practical to begin by locating the potential
source(s) of the odor before trying to
identify pollutant pathways.
Forms and checklists such as the
samples provided in this document (modi-
fied if needed) can help investigators to
record information in an organized way.
Small copies of basic floor plans, such as
fire evacuation plans, are convenient for
noting locations of observations.
Any instruments that will be used
should be inspected to make sure they are
in working order and calibrated. IAQ
investigations generally include the use of,
at a minimum: heatless chemical smoke
devices and instruments for measuring
temperature and humidity.
Carbon dioxide measuring devices
(detector tubes with a hand pump or a
direct reading meter) are helpful for most
investigations. Other instruments may be
needed as the investigation progresses.
See Appendix A for additional guidance on
common IAQ measurements.
Tools for Collecting I i-fori ration
The following pages present strategies,
tools, and forms for the investigator to use
during an in-depth investigation. The
Incident Log shown below (and in Tab V)
can be used to track the course of an inves-
tigation from the receipt of the original
complaint.
SarrpleFarm
Incident Log
File
Number
Date
Problem Location
Investigation Record
(check the forms that were used)
Complaint
Form
Occupant
Interview
£
2-s
3 C8
o r~\
o u
O
0)
11
_l 0
<
Zone/Room
Record
HVAC
Checklist
Pollutant
Pathway
Source
Inventory
Hypothesis
Form
Outcome /
Comments
Log Entry By
(initials)
Diagnosing IAQ Problems 4 9
-------
COLLECTING OCCURANT INFORMATION
Strategies Tools
Review existing
information about
complaints
Existing Records
IAQ Complaint Form
Incident Log
Collect additional
information from
occupants
Occupant Interview
Occupant Diary
An initial walkthrough may
uncover problems such as
this unsanitary condition in
the HVAC system. Bird
droppings have collected in
an air supply plenum near an
outdoor air intake that was
not protected by a birdscreen.
The discussion that follows has been
divided into categories of occupant data,
HVAC system data, pollutant pathway
data, and source data. However, the
suggestions for collecting and using
information reflect the interdependence of
these factors. For example, the operation
of the air distribution system affects
pollutant pathways, and the air distribution
system can also be a source of pollutants.
Indoor air quality-related complaints
may develop from a variety of causes.
Neither the discussion of strategies for
collecting information nor the suggestions
for interpreting data can present the full
range of possible situations encountered in
buildings. They are intended to present a
problem-solving approach that can help
facility staff to understand and resolve
many common indoor air quality prob-
lems. If you decide to hire outside
professionals to resolve your IAQ com-
plaint, this discussion of strategies and
tools should help you to understand and
oversee their investigative work.
COLLECTING INFCRMVTICN
ABOUT OCCUPANT
COR/PLAINTS
Occupant data falls into two categories:
complaints of discomfort or other symp-
toms (e.g., teary eyes, chills) and percep-
tions of building conditions (e.g., odors,
draftiness). Investigators can gather
valuable information about potential
indoor air problems from listening to
occupants, and use that information for:
defining the complaint area within the
building
suggesting directions for further investi-
gation, either by identifying other events
that seem to happen at the same time as
the incidents of symptoms or discomfort,
or by identifying possible causes for the
types of symptoms or discomfort that are
occurring
indicating potential measures to reduce
or eliminate the problem
Review Existin
Con-plaints
I Records of
If there is a record of occupant complaints,
a review of that record can help to define
the location of the IAQ problem and
identify people who should be interviewed
as part of the investigation. Information
about the history of complaints could also
stimulate theories about potential causes of
the problem.
Interview OocLfianls
The most obvious way to collect informa-
tion from building occupants is to talk to
50 Section 6
-------
them in person. If it is not possible to
interview everyone who has complained
about building conditions, the investigator
should attempt to interview a group of
individuals that reflect the concerns of the
affected areas.
The investigation may also include
occupant interviews with building occu-
pants who do not have complaints. Then
conditions in the complaint area can be
compared to conditions in similar building
locations where there are no complaints.
A sample Occupant Interview form is
shown here (there is another copy in
Tab V). It can also be presented in a
written form in order to get information
from more people than can be interviewed.
The following key points will help
interviews to be productive:
Read the discussion of evaluating
occupant data before you conduct
interviews, to be certain that you
understand what sort of information is
needed.
Make a copy of the interview form for
each person you speak with, and use the
form to record the answers to your
questions.
Choose a location in which the person
you are interviewing feels comfortable to
speak freely.
Explain that the interview is intended to
help discover and correct the cause of the
complaints. Encourage the person you
are interviewing to join in this coopera-
tive problem-solving effort.
Give the person you are interviewing
enough time to think about your ques-
tions.
If complainants are reluctant to answer
questions about health symptoms,
respect their desire for privacy. Planning
for how to maintain this privacy is
warranted, and in some cases may be
mandated.
Feel free to expand the interview by
adding questions that help to improve
your understanding or explore their
San-pie Form
r* Interview
SYMPTOM PATTERNS
What kind of symptoms or discomfort are you experiencing?
Are you aware of other people with similar symptoms or concerns?
Yes No
If so, what are their names and locations?
Do you have any health conditions that may make you particularly
susceptible to environmental problems?
TIM ING PATTERNS
When did your symptoms start?
hypotheses (or your own) about what
may be causing the problem. Always be
open to answers that may not fit your
hypotheses.
You may sometimes need to clarify a
question by giving examples of the sort
of information you are interested in. Try
to provide more than one example so that
you don't seem to be telling the person
the answer you want. Be particularly
cautious about mentioning specific
health effects.
The Occupant Interview includes
many basic points that are found in
questionnaires used by professional IAQ
investigators. It is important to note,
however, that this form is not called a
"questionnaire." Formal questionnaires
may be useful for quantitative epidemiol-
ogy, IAQ research, complex IAQ investi-
gations, or when litigation is a possibility.
In these cases, questionnaires must be
carefully designed and executed by people
with an understanding of representative
sampling and expertise in public health,
industrial hygiene, or medicine. Use of
questionnaires for such purposes is beyond
the scope or expertise of most in-house
investigations; if such questionnaire data is
Diagnosing IAQ Problems 51
-------
SarrpleFcrm
On the form below, please record each occasion when you experience
a symptom of ill-health or discomfort that you think may be related to
an environmental condition in the building.
Time/Date
Location
Symptom
Severity/Duration
Comments
SarrpleFcrm
Logof Activi
andSyst
Op
On the form below, please record your observations of HVAC system
operation, maintenance activities, and any other information that you
think may be helpful in identifying the cause of IAQ complaints in this
building. Please report any other observations (e.g., weather, other
associated events) that you think may be important as well.
Equipment and activities of particular interest:
Air Handler(s):
Exhaust Fan(s):
Other Equipment or Activities:
Date/Time
Day of Week
Equipment Item/Activity
Comments
needed, building owners and managers
should use professionals.
Ask OccLfaants and Facility
Staff to Keep IVbre Detailed
Records
Many events occur simultaneously in and
around a complex building, and it can be
very difficult to judge which of those
events might be related to the IAQ
complaints. In trying to resolve stubborn
problems, professional investigators
sometimes ask occupants and facility staff
to keep day-by-day records. Occupants are
asked to record the date and time of
symptoms, where they are when the
symptoms appear, and any other informa-
tion that might be useful. Such informa-
tion could include observations about the
severity and duration of symptoms and
comments on weather conditions, events,
and activities that are happening at the
same time. Facility staff are asked to
record the date and time of events such as
maintenance work, equipment cycles, or
deliveries. If symptoms seem to occur at
particular times of day, staff can focus
their attentions on recording events that
occur before and during those periods.
Such records are likely to produce more
accurate and detailed information than can
be obtained by relying on memory. (Use
the Occupant Diary and the Log of
Activities and System Operations shown
here and included in Tab V.)
5 2 Section 6
-------
USING THE OCCUPANT DATA
The pattern of complaints within the
building helps to define the complaint area.
The timing of symptoms and the types of
symptoms reported may provide clues
about the cause of the problem.
Strategies for Using Occupant Data
m Define the complaint area
Look for timing patterns
Look for symptom patterns
Exhaust fumes are drawn into
this building's outdoor air
intake when trucks are idling
at the nearby loading dock.
Tools such as the Occupant
Diary and Log of Activities
and System Operation can
help to identify intermittent
pollutant sources such as this
one.
Diagnosing IAQ Problems 5 3
-------
SPATIAL PATTERNS
SUGGESTIONS
Widespread, no apparent spatial
pattern
Check ventilation and tem-
perature control for entire
building.
Check outdoor air quality.
Review sources that are spread
throughout building (e.g.,
cleaning materials).
Consider explanation other than
air contaminants.
Localized (e.g., affecting indi-
vidual rooms, zones, or
air handling systems)
Individual(s)
Check ventilation and tempera-
ture control within the complaint
area.
Review pollutant sources
affecting the complaint area.
Check local HVAC system
components that may be acting
as sources or distributors of
pollutants.
Check for drafts, radiant heat
(gain or loss), and other
localized temperature control or
ventilation problems near the
affected individual(s).
Review local pollutant source(s)
near the affected individual(s).
Consider that common back-
ground sources may affect only
susceptible individuals.
Consider the possibility that
individual complaints may have
different causes that are not
necessarily related to the
building (particularly if symp-
toms differ among the individu-
als).
Define the Con-plaint Area
Use the spatial pattern (locations) of
complaints to define the complaint area.
Building locations where symptoms or
discomfort occur define the rooms or zones
that should be given particular attention
during the initial investigation. However,
the complaint area may need to be revised
as the investigation progresses. Pollutant
pathways can cause occupant complaints
in parts of the building that are far
removed from the source of the problems.
54 Section 6
-------
Look far Tirring Patterns
Look for patterns in the timing of com-
plaints. The timing of symptoms and
complaints can indicate potential causes
for the complaints and provide directions
for further investigation. Review the data
for cyclic patterns of symptoms (e.g.,
worst during periods of minimum ventila-
tion or when specific sources are most
active) that may be related to HVAC
system operation or to other activities in
and around the building.
HIVING PATTERNS
Symptoms begin and/or
are worst at the start of
the occupied period
Symptoms worsen over
course of occupied period
Intermittent symptoms
Single event of symptoms
Recent onset of symptoms
SUGGESTIONS
Review HVAC operating cycles.
Emissions from building
materials, or from the HVAC
system itself, may build up
during unoccupied periods.
Considerthat ventilation may
not be adequate to handle
routine activities or equipment
operation within the building.
Look for daily, weekly, or
seasonal cycles or weather-
related patterns, and check
linkage to other events in and
around the building.
Consider spills, other
unrepeated events as sources.
i Ask staff and occupants to
describe recent changes or
events (e.g., remodeling,
renovation, redecorating, HVAC
system adjustments, leaks, or
spills).
Symptoms relieved on leaving the
building, either immediately,
overnight, or (in some cases) after
extended periods away from the
building
i Consider that the problem is
likely to be building-related,
though not necessarily due to air
quality. Other stressors (e.g.,
lighting, noise) may be involved.
Symptoms never relieved,
even after extended absence from
building (e.g., vacations)
Considerthat the problem may
not be building-related.
Diagnosing IAQ Problems 5 5
-------
The following chart lists some
common symptom groups
that can be related to indoor
air quality, along with possible
sources or causes of those
symptoms. Building
managers are cautioned that
this is only a partial listing.
Look for Syrrptarn Patterns
Look for patterns in the types of symptoms
or discomfort. IAQ investigations often
fail to prove that any particular pollutant
or group of pollutants are the cause of the
problem. Such causal relationships are
extremely difficult to establish. There is
little information available about the health
effects of many chemicals. Typical indoor
levels are much lower than the levels at
which toxicology has found specific
effects. Therefore, it may be more useful
to look for patterns of symptoms than
for specific pollutant and health effect
relationships.
Investigators who are not medically
trained cannot make a diagnosis and should
not attempt to interpret medical records.
Also, confidentiality of medical informa-
tion is protected by law in some jurisdic-
tions and is a prudent practice everywhere.
SYlVPTOn/IPATTERNS
SUGGESTIONS
THERMAL DISCOMFORT
Check HVAC condition and operation.
Measure indoor and outdoor temperature and humidity (see Figure 6-2 on
page 57). See if extreme conditions exceed design capacity of HVAC equip-
ment.
Check for drafts and stagnant areas.
Check for excessive radiant heat gain or loss.
COMMON SYMPTOM GROUPS
Headache, lethargy, nausea,
drowsiness, dizziness
Congestion; swelling, itching or
irritation of eyes, nose, or
throat; dry throat; maybe
accompanied by non-specific
symptoms (e.g. headache,
fatigue, nausea)
If onset was acute, arrange for medical evaluation, as the problem may be carbon
monoxide poisoning.
Check combustion sources for uncontrolled emissions or spillage. Check
outdoor air intakes for nearby sources of combustion fumes.
Consider evacuation/medical evaluation if problem isn't corrected quickly.
Consider other pollutant sources.
Check overall ventilation; see if areas of poor ventilation coincide with com-
plaints.
May be allergic, if only small number affected; more likely to be irritational
response if large number are affected.
Urge medical attention for allergies.
Check for dust or gross microbial contamination due to sanitation problems,
water damage, contaminated ventilation system.
Check outdoor allergen levels (e.g., pollen counts).
Check closely for sources of irritating chemicals such as formaldehyde or those
found in some solvents.
Cough; shortness of breath;
fever, chills and/or fatigue after
return to the building
May be hypersensitivity pneumonitis or humidifier fever. A medical evaluation
can help identify possible causes.
Check for gross microbial contamination due to sanitation problems, water
damage, or contaminated HVAC system.
Diagnosed infection
Suspected cluster of rare or
serious health problems such
as cancer, miscarriages
May be Legionnaire's disease or histoplasmosis, related to bacteria or fungi found
in the environment.
Contact your local or State Health Department for guidance.
Contact your local or State Health Department for guidance.
OTHER STRESSORS
Discomfort and/or health
complaints that cannot be
readily ascribed to air contami-
nants or thermal conditions
Check for problems with environmental, ergonomic, and job-related
psychosocial stressors.
56 Section 6
-------
Figure 6-2 shows the range of tempera-
tures and relative humidities that fall
within the comfort zone for most individu-
als dressed in "typical" clothing and
involved in light, mostly sedentary
activity. Recent research suggests that
indoor air quality is judged to be worse as
temperatures rise above 76°F, regardless of
the actual air quality.
There is considerable debate among
researchers, IAQ professionals, and health
professionals concerning recommended
levels of relative humidity. In general, the
range of humidity levels recommended by
different organizations seems to be 30% to
60%. Relative humidities below this
level may produce discomfort from
dryness. On the other hand, maintaining
relative humidities at the lowest possible
level helps to restrict the growth of mold
and mildew. The concerns (comfort for
the most part) associated with dry air must
be balanced against the risks (enhanced
microbiological growth) associated with
humidification. If temperatures are
maintained at the lower end of the comfort
range (68 - 70°F) during heating periods,
relative humidity in most climates will not
fall much below 30% (also within the
comfort range) in occupied buildings.
FIGURE &2 Acceptable Ranges of Temperature and Relative
Humidity During Summer and Winter1
COLLECTING INFORMATION
HVAC SYSTEM
IAQ complaints often arise because the
quantity or distribution of outdoor air is
inadequate to serve the ventilation needs of
building occupants. Problems may also be
traced to air distribution systems that are
introducing outdoor contaminants or
transporting pollutants within the building.
The investigation should begin with the
components of the HVAC system(s) that
serve the complaint area and surrounding
rooms, but may need to expand if connec-
tions to other areas are discovered. Your
goal is to understand the design and
operation of the HVAC system well
Relative Humidity
30%
40%
50%2
60%
Winter Temperature
68.5°F-76.0°F
68.5°F-75.5°F
68.5°F-74.5°F
68.0°F-74.0°F
Summer Temperature
74.0°F-80.0°F
73.5°F-79.5°F
73.0°F-79.0°F
72.5°F-78.0°F
' Applies for persons clothed in typical summer and winter clothing, at light,
mainly sedentary activity.
2 See left for discussion of relative humidities.
SOURCE: Adapted from ASHRAE Standard 55-1981, Thermal Environmental
Conditions for Human Occupancy
enough to answer the following questions:
Are the components that serve the
immediate complaint area functioning
properly?
Is the HVAC system adequate for the
current use of the building?
Are there ventilation (or thermal com-
fort) deficiencies?
Should the definition of the complaint
area be expanded based upon the HVAC
layout and operating characteristics?
An evaluation of the HVAC system
may include limited measurements of
temperature, humidity, air flow, and CO2,
as well as smoke tube observations.
Complex investigations may require more
extensive or sophisticated measurements of
the same variables (e.g., repeated CO2
measurements taken at the same location
under different operating conditions,
continuous temperature and relative
humidity measurements recorded with a
data logger). A detailed engineering study
may be needed if the investigation discov-
ers problems such as the following:
airflows are low
HVAC controls are not working or are
working according to inappropriate
strategies
building operators do not understand (or
are unfamiliar with) the HVAC system
WHAT DO YOU
KIMOUUSOFAR?
Use the Hypothesis
Form on page 223 to
make brief notes after
reviewing the occupant
data.
Decide whether you
have a hypothesis that
might explain the
complaints. If so, test it.
(See page 78 for a
discussion of
hypothesis testing.
Decide what else you
need to know.
Consider whether
in-house expertise is
sufficient or outside
assistance is needed
(See Section 8 for
guidance on hiring
outside assistance.)
Diagnosing IAQ Problems 5 7
-------
COLLECTING HVAC SYSTEMINFGRIVKnGN
Strategies Tools
Review Docxmentaticn on
HVAC Design Installation, and
Review existing documen-
tation on HVAC design,
installation, and operation
Collect:
design documents, testing and
balancing reports
operating instructions, control
manufacturer's installation data
Talk to facilities staff
Ask facilities staff to record their observa-
tions of equipment cycles, weather
conditions, and other events using
Log of Activities and System Operations
Inspect system layout,
condition, and operation
Use:
Zone/Room Record
HVAC Checklist - Short Form and/or
HVAC Checklist - Long Form
thermometer and sling psychrometer
(or electronic equivalent) to measure
temperature and humidity
micromanometer (or equivalent) to
measure pressure differentials
0-2" and 0-10" water gauge (w.g.)
to measure at fans and intakes
0-.25" w.g. with pitot tube to check
airflow in ducts
chemical smoke for observing airflow
patterns
a device to assess airflow from
diffusers
rough quantitative: anemometer;
velometer
accurate quantitative: flow hood
carbon dioxide measurement devices
detector tubes with a hand pump
direct reading meter
Use additional instruments
as appropriate
Instruments often used by professional
IAQ consultants include:
a hygrothermograph to log temperature
and humidity
tracer gas and measurement equip-
ment
a device to measure airborne particu-
lates
measurement devices for carbon
monoxide and other contaminants
of interest
A review of existing documentation (e.g.,
plans, specifications, testing and balancing
reports) should provide information about
the original design and later modifications,
particularly:
the type of HVAC system (e.g., constant
volume, VAV)
locations and capacities of HVAC
equipment serving the complaint area
the planned use of each building area
supply, return, and exhaust air quantities
location of the outdoor air intake and of
the supply, return, and exhaust registers,
diffusers, and grilles that serve the
complaint area
The most useful way to record this
information is to make a floor plan of the
complaint area and surrounding rooms.
You may be able to copy an existing floor
plan from architectural or mechanical
drawings, fire evacuation plans, or some
other source.
If there is no documentation on the
mechanical system design, much more on-
site inspection will be required to under-
stand the HVAC system. The HVAC
system may have been installed or
modified without being commissioned,
so that it may never have performed
according to design. In such cases, good
observations of airflow and pressure
differentials are essential. In addition, load
analyses may be required.
Talk to Facility Staff
Facility staff can provide important current
information about equipment operating and
maintenance schedules and breakdowns or
other incidents. There may be inspection
reports or other written records available
for review. Staff members who are
familiar with building systems in general
and with the specific features of the
58 Section 6
-------
building under investigation can be very
helpful in identifying conditions that may
explain the indoor air quality complaints.
Some facility operators have extensive
preventive maintenance programs. On the
other hand, discussion could reveal that
facility staff are not operating the building
according to its design, because:
they do not understand the design logic
of the HVAC system
they have been asked to run the HVAC
system at the lowest possible energy cost
they do not have the manpower to
operate the building properly
the HVAC system has not been modified
to accommodate changes in the use of
space or increases in the occupant
population
Staff may have noticed occupant
activities that are indicators of inadequate
ventilation or poorly-controlled tempera-
tures, such as:
desktop fans, heaters, or humidifiers
supply diffusers blocked off with tape or
cardboard
popped-up ceiling tiles
interference with thermostat settings
IAQ complaints are often intermittent.
Discussions with staff may reveal patterns
that relate the timing of complaints to the
cycles of equipment operation or to other
events in the building such as painting,
installation of new carpeting, or pest
control. These patterns are not necessarily
obvious. Keeping a day-to-day record may
help to clarify subtle relationships between
occupant symptoms, equipment operation,
and activities in and around the building.
(See Occupant Diary and Log of Activi-
ties and System Operations on page 52
and in Tab V.) Staff members may have
theories about the cause of
the problem.
Inspect SystemLayoL*,
Goncf ticn, and Operation
If the building is new or if there is a pre-
ventive maintenance program with recent
Above: An investigation of this building
revealed no problems with the HVAC sys-
tem, although the amount of outdoor air was
very low. In a more thorough inspection of
the HVAC system, investigators found that
the wiring to this outdoor air damper motor
had never been connected. No outdoor air
was entering the building through the intake
controlled by this damper. Below: These
investigators are examining a perimeter fan-
coil unit. Self-contained heating or cooling
units such as this one are often overlooked
during routine maintenance. There may be
many such units in a single building, some-
times in remote or inaccessible locations.
Diagnosing IAQ Problems 5 9
-------
The design specifications for
this building called for a mini-
mum 20% setting on the
outdoor air damper control.
Facility staff lowered the
minimum outdoor air setting
to 10% in order to save en-
ergy and reduce operating
costs. As a result, the build-
ing was underventilated
whenever outdoor tempera-
tures were either very hot or
very cold.
test and balance reports, it is possible (but
not necessarily likely) that the HVAC
system is functioning according to its
original design. Otherwise it is probable
that one or more features of building usage
or system operation have changed in ways
that could affect indoor air quality.
Elements of the on-site investigation
can include (but are not limited to) the
following:
Check temperature and/or humidity to see
whether the complaint area is in the com-
fort range.
Take more than one measurement to ac-
count for variability over time and from
place to place. Compare to Figure 6-2 on
page 57 (see also Appendix B).
Check thermostat operation.
Check whether the supply air tempera-
ture corresponds to the design criteria.
Use a hygrothermograph (if available) to
log temperature and humidity changes in
the complaint area.
Check for indicators of inadequate
ventilation.
Check supply diffusers to see if air is
moving (using chemical smoke). If it is
not, confirm that the fan system is operat-
ing, and then look for closed dampers,
clogged filters, or signs of leaks.
Compare design air quantities (if avail-
able) to building codes for the current
occupancy or ventilation guidelines (e.g.,
ASHRAE 62-1989, see Appendix B). If
the HVAC system, performing as de-
signed, would not provide enough venti-
lation air for current needs, then there is
good reason to believe that actual ventila-
tion rates are inadequate.
Measure carbon dioxide (CO2) in the
complaint area to see whether it indicates
ventilation problems. (See Appendix A
for a discussion of techniques for measur-
ing and interpreting CO2 concentrations.)
Measure air quantities supplied to and
exhausted from the complaint area, in-
cluding calculation of outdoor air quanti-
ties (see Appendix A for further guid-
ance). Be aware of damper settings and
equipment cycles when you are measur-
ing (e.g., are you evaluating minimum
outdoor air, "normal" conditions, or
maximum airflow?). Note that evalua-
tion of variable air volume (VAV) sys-
tems requires considerable expertise.
Compare the measured air quantities to
your mechanical system design specifica-
tions and applicable building codes. Also
compare ventilation rates to ASHRAE
62-1989. Some of the ventilation recom-
mendations of ASHRAE 62-1989 are
reproduced in Appendix B.
Check that equipment serving the com-
plaint area (e.g., grilles, diffusers, fans) is
operating properly.
Confirm the accuracy of reported operat-
ing schedules and controls sequences; for
example, power outages may have dis-
rupted time clocks, fans reported as
"always running" may have been acci-
dentally switched off, and controls can be
in need of calibration.
60 Section 6
-------
Check to see that equipment is properly
installed. For example, look for shipping
screws that were never removed or fans
that were reversed during installation, so
that they move air in the wrong direc-
tion.
Compare the current system to the
original design.
Check to see that all equipment called
for in the original design was actually
installed.
See whether original equipment may
have been replaced by a different model
(i.e., a model with less capacity or differ-
ent operating characteristics).
See whether the layout of air supplies,
returns, and exhausts promotes efficient
air distribution to all occupants and iso-
lates or dilutes contaminants.
(See Appendix A for guidance on using
chemical smoke to study airflow and mix-
ing patterns and CO2 to help determine the
adequacy of ventilation.)
If supplies and returns are close together,
heatless chemical smoke can be used to
check for short-circuiting (supply air that
does not mix properly with air in the
breathing zone, but moves directly to the
return grille). CO2 can also be used to
evaluate air mixing.
Use heatless chemical smoke to observe
airflow patterns within the complaint
area and between the complaint area and
surrounding spaces, including outdoors.
Compare airflow directions under vari-
ous operating conditions.
If the system layout includes ceiling
plenums, look above the ceiling for inter-
ruptions such as walls or full-height
partitions.
Consider whether the HVAC system itself
may be a source of contaminants.
Check for deterioration or unsanitary
conditions (e.g., corrosion, water damage
or standing water, mold growth or exces-
sive dust in ductwork, debris or damaged
building materials in ceiling plenums).
If the mechanical room serves as a mix-
ing plenum (i.e., return and outdoor air
are drawn through the room into the air
handler), check very carefully for poten-
tial contaminants such as stored solvents
and deteriorated insulation.
Use the forms provided in this document
to inspect the HVAC system.
Use the Zone/Room Record to describe
the ventilation system serving the com-
plaint area and surrounding rooms or
zones. The Zone/Room Record is
reproduced on page 62 and in Tab V.
Use the HVAC Checklist (short and/or
long form) to evaluate the condition of
HVAC system components that affect air
distribution and IAQ in the complaint
area. A portion of the HVAC Checklist-
Short Form is reproduced on page 62.
The HVAC Checklist - Long Form is
useful for more detailed examination of
the system. Complete copies of both
forms can be found in Tab V.
The dark streaks at the
outlet of this supply diffuser
could indicate a filtration prob-
lem. Poorly maintained or im-
properly sized filters
can allow dirt to be distrib-uted
through the building.
Diagnosing IAQ Problems 61
-------
SanpleFcnn
Record
This form is to be used differently depending on whether the goal is to prevent or diagnose IAQ problems.
During development of a profile, this form should be used to record more general information about the entire
building; during an investigation, the form should be used to record more detailed information about the
complaint area and areas surrounding the complaint area or connected to it by pathways.
PROFILE AND DIAGNOSIS INFORMATION
Building Area
(Zone/Room)
Use"
Source of
Outdoor Air*
Mechanical
Exhaust?
(Write "No"
or estimate
cfm airflow)
Comments
DIAGNOSIS INFORMATION ONLY
Peak Number of
Occupants or
Sq. Ft. Floor Area*
Total Air
Supplied
(in cfm)**
Outdoor Air
Supplied
per Person or
per 150 sq.
Ft. Area****
SarrpleForm
HVAC ChecklistShort Form
Sections 2, 4 and 6 and Appendix B discuss the relationships between the
HVA C system and indoor air quality.
MECHANICAL ROOM
Clean and dry?
_Stored refuse or chemicals?
Describe items in need of attention
MAJOR MECHANICAL EQUIPMENT
Preventive maintenance (PM) plan in use?
Control System
Type
System operation
USING THE HVAC SYSTEM
DATA
As you review the HVAC data, consider
whether the system is adequate to serve
the use of the building and whether the
timing, location, and impact of apparent
deficiencies appear related to the IAQ
complaint. Deficiencies in HVAC
design, operation, or maintenance may
exist without producing the complaint
under investigation; some defects may
not cause any apparent IAQ problems.
Strategies for Using the HVAC
System Data
Compare the original design to the
current system.
Compare the original uses of space to
current uses.
Consider the condition of the HVAC
system.
62 Section 6
-------
HEALTH AND SAFETY CONSIDERATIONS FOR
IAQ INVESTIGATORS
Normal safety precautions observed during routine operation of the building must be
followed closely during IAQ inspections. When the IAQ investigator is not familiar with
the mechanical equipment in that particular facility, an operator or engineer should be
present at all times in equipment areas. Potential safety hazards include:
electrocution
injury from contacting fans, belts, dampers or slamming doors
burns from steam or hot water lines
falls in ventilation shafts or from ladders or roofs
Investigators evaluating building IAQ generally do not encounter situations in which
specific personal protection measures (e.g., protective garments and respirators) are
required. However, safety shoes and eyeglasses are generally recommended for
working around mechanical equipment. When severe contamination is present (e.g.,
microbiological, chemical, or asbestos), IAQ investigators may need additional
protection in the vicinity of certain building areas or equipment. Such decisions are
site specific and should be made in consultation with an experienced industrial
hygienist. General considerations include the following:
Microbiological: Care must be taken when serious building related illness (e.g.,
Legionnaire's disease) is under investigation or when extensive microbiological growth
has occurred. Investigators with allergy problems should be especially cautious. The
array of potential contaminants makes it difficult to know what sort of personal protec-
tion will be effective. At a minimum, investigators should minimize their exposure to air
in the interior of ducts or other HVAC equipment unless respiratory protection is used.
If there is reason to suspect biological contamination (e.g., visible mold growth), expert
advice should be obtained about the kind of respiratory protection to use and how to
use it. Possible protective measures against severe microbiological contamination
include disposable coveralls and properly fitted respirators.
Chemical: Where severe chemical contamination is suspected, specific precautions
must be followed if OSHA action levels are approached. Such instances rarely occur
in IAQ investigations. One possible exception might be a pesticide spill in a confined
space. In this case, an appropriate respirator and disposable coveralls may be
needed.
Asbestos: An IAQ investigation often includes inspection above accessible ceilings,
inside shafts, and around mechanical equipment. Where material suspected of
containing asbestos is not only present, but also has deposited loose debris, the
investigator should take appropriate precautions. This might include disposable
coveralls and a properly fitted respirator.
Note: The requirements for proper fit, physical condition of the wearer, and other considerations
involved in selection of the proper respirator must be evaluated by an occupational safety and
health specialist. There is a NIOSH Respirator Decision Logic for proper respirator selection, and
OSHA has regulations for an appropriate respirator protection program.
VXnenthelAQi
gator is not familiar
vuth the mechanical
equipment in that
partkxiar facility.
shoLid be present at
all tii-i-ps inequp-
Diagnosing IAQ Problems 63
-------
ALL SYSTEMS
Ventilation and
temperature
control zones
Changes in
equipment
Operating
cycles
SUGGESTIONS
Revise definition of complaint area (if
needed) to add spaces linked to the
original complaint area by ductwork or
controls.
Check to see that thermostats
are properly located and function
properly.
Note equipment changes that
could be affecting the system's
performance (e.g., removal or addition
of equipment, replacement by a differ-
ent model).
Review operating procedures for oc-
cupied and unoccupied periods.
Compare timing of occupied/
unoccupied periods to equipment
cycles and occupant complaints.
Confirm that time clocks are reading
the actual time. See ASHRAE 62-
1989 for suggested lead times to allow
proper flushing before occupants ar-
rive. In some cases (e.g., warm, hu-
mid climates), fans may need to oper-
ate during unoccupied periods to pre-
vent mold growth or other problems.
Con-pare the Gricpnal Design to
the Current HVAC System
Consider the original HVAC design and
compare it to the current equipment,
layout, and controls. A variety of HVAC
system designs have been used in public
and commercial buildings. The type of
system used in your building affects the
control of ventilation air quantities and
distribution, as well as thermal comfort.
See Appendix B for a discussion of HVAC
system types.
64 Section 6
-------
Use HVAC Data to Evaluate
Mtigaticn IVfeasunes
As you use the HVAC data to evaluate
potential mitigation measures, review the
suggestions made in both the box on the
facing page for all HVAC systems and in
the box on this page for the type of HVAC
system in your building.
SYSTEIVTTYPES
No mechanical
ventilation or
exhaust only
Room units
(e.g., unit
ventilators)
Constant
volume
Variable
air volume
(VAV)
SUGGESTIONS
i Identify the source(s) of ventilation air
(e.g., operable windows, doors
propped open).
i Check whether the location of open
windows, doors, or other openings
promotes the introduction of odors or
contaminants.
i Check whether outdoor air intakes are
obstructed. Does their location pro-
mote the introduction of odors or con-
taminants?
i Note design airflows in the complaint
area (outdoor air, supply, return, and
exhaust) and surrounding spaces;
compare to ASHRAE
62-1989 and to actual measured
airflows.
i Note design airflows in the complaint
area (outdoor air, supply, return, and
exhaust) and surrounding spaces;
compare to applicable building codes,
ASHRAE 62-1989, and to actual mea-
sured airflows.
i Check whether outdoor air intakes are
obstructed. Does their location pro-
mote the introduction of odors or con-
taminants? Check for unsanitary con-
ditions.
i Check outdoor air damper controls.
In addition to all suggestions made for
constant volume systems:
Confirm whether the system design al-
lows regulation of outdoor air quanti-
ties. Do VAV boxes have stops to en-
sure that minimum amounts of out-
door air are delivered at all times dur-
ing occupied periods? Are the system
controls providing a constant ventila-
tion rate per person regardless of total
system airflows?
Observe changes (if any) in airflow
patterns within and around the com-
plaint area as the VAV system
throttles from maximum to
minimum flow.
Diagnosing IAQ Problems 65
-------
ROOMUSE CHANGES SUGGESTIONS
Increased occupant
density
Change in type of occu-
pant population
Compare temperature and humidity to
comfort zone in ASHRAE 55-1981
guidelines.
Compare minimum outdoor air
quantities to the original design,
applicable building codes, and
ASHRAE 62-1989 guidelines.
For example introduction of a more
physically active group of occupants can
change thermal comfort requirements.
Compare temperature and humidity to
comfort zone in ASHRAE 55-1981
guidelines.
Compare minimum outdoor air
quantities to the original design,
applicable building codes, and
ASHRAE 62-1989 guidelines.
Check for low-level contaminant
sources.
Ctrrpare the Crignal Uses of
Space to GLrrent Uses
Compare the original uses of the complaint
area and surrounding rooms to current
uses of those areas. Indoor air quality
problems often arise when the usage of
rooms changes without corresponding
adjustments to the HVAC system. For
example, if ventilation appears to be a
problem despite a properly-functioning
HVAC system, the existing system may
be inadequate to meet current needs.
Additional non-HVAC
equipment
Compare temperature and humidity to
comfort zone in ASHRAE 55-1981
guidelines.
Consider the need for local exhaust at
point sources of contaminants.
Conversion to or addition
of special uses
Example: Modifications that convert or
add such special uses as smoking
lounges, print shops, or kitchen facilities
may also require changes in the
operation of the HVAC system.
Check pressure relationships between
special use areas and surrounding
spaces.
Consider the need for local exhaust at
point sources of contaminants.
Rearrangement of work
stations (e.g., relocation of
partitions)
Check that thermostats are properly
located. Compare temperature and
humidity to comfort zone in ASHRAE
55-1981 guidelines.
Check layout of supplies, returns, and
exhausts.
Check to make sure that partitions do
not block proper air circulation.
66 Section 6
-------
Consider the Concf ticn of the
HVAC System
Consider whether the HVAC system is
reasonably clean and functioning properly.
Review the results of the onsite inspection.
If you identified sanitary or operating
problems in the HVAC system serving the
complaint area, you may want to correct
those problems and see whether the
complaints are resolved before continuing
with the investigation.
SYSTEMGONnTIONS
SUGGESTIONS
Unsanitary conditions
Moisture or standing water
Debris
Dust and/or mold growth
Correct sanitary problems and
adopt necessary measures to
prevent recurrence of problems.
HVAC malfunctions
Equipment breakdown
Obstructed diffusers or grilles
Air distribution or mixing problems:
(e.g., equipment is
out of balance, requires
calibration, or needs other adjust-
ment)
Air bypasses filters (due to
loose filter tracks, incorrect filter
size, or filter overloaded with dirt)
Air distribution system leaks (e.g.,
leaky ductwork; unin-tended
openings in pressurized ceilings or
in return air plenums)
Evaluate whether the HVAC
defect could have caused the
IAQ complaint.
Correct the malfunction(s), and
see whether complaints are
resolved.
Review maintenance program
and revise as needed to prevent
future problems.
HVAC functions properly.
However, there is evidence of
underventilation.
Considerwhat adjustments
could be made to increase the
supply of outdoor air (or
decrease the ventilation
demand) in the complaint area.
WHAT DO YOU
KNOW5OFAR?
Use the Hypothesis
Form on page 223 to
make brief notes.
Decide whether you
have a hypothesis
that might explain the
complaints. If so, test
it. (See page 78 for a
discussion of hypoth-
esis testing.)
Decide what else you
need to know.
Consider whether in-
house expertise is
sufficient or outside
assistance is needed
(See Section 8 for
guidance on hiring
outside assistance.)
Diagnosing IAQ Problems 67
-------
COLLECTING INFORMVTICN
ABOUT POLLUTANT PATHWAYS
AND DRIVING FORCES
Unless the IAQ problem is caused by an
obvious contaminant located in the
complainant's immediate workspace, you
will need to understand the patterns of
airflow into and within the complaint area.
Correction of IAQ problems often involves
controlling pollutant movement through
sealing of pollutant pathways or manipula-
tion of the pressure relationships.
If the complaints being investigated are
limited to a few areas of the building, pollut-
ant pathways can be evaluated so that the
complaint area is properly defined before
conducting the source inventory. If com-
plaints are spread throughout the building,
COLLECTING PATHVAAY INFORMATION
Strategies Tools
Identify pollutant
pathways
Observe direction
of air movement
Architectural and mechanical
drawings
Pollutant Pathway Form for Investigations
Sketch plan of complaint area
Testing and balancing reports
Chemical smoke tests
Micromanometer or equivalent
evaluation of pathways could be a very
time-consuming process, and it may be
more practical to look for major contami-
nant sources before trying to discover how
the contaminants move within the building.
Identify Polluter* Pathways
Architectural and mechanical pathways
allow pollutants to enter the complaint area
from surrounding spaces, including the
outdoors. An examination of architectural
and mechanical plans can help in develop-
ing a list of connections to surrounding
areas. These include:
doors
operable windows
stairways
elevator shafts
utility chases
ductwork and plenums
areas served by common HVAC controls
(e.g., shared thermostats)
Onsite inspection is needed to confirm
the existence of these connections and to
identify other openings (e.g., accidental
openings such as cracks and holes). Fire
codes usually require that chases and hid-
den openings be firestopped. Check for the
existence and condition of firestops in
chases, especially those that connect both
vertically and horizontally.
Chemical smoke is being
used to detect the direction
and amount of airflow through
this closed doorway. A
building investigator must
know how the ventilation in
the building is designed to
operate in order to decide
whether the observed flow of
smoke is appropriate.
68 Section 6
-------
The Pollutant Pathway Form for
Investigations shown to the right can be
used along with a sketch plan of the
complaint area (similar to the example on
page 70) to record pathways and directions
of pollutant movement. A blank copy of
the form is included in Tab V.
GbserueAir IVbuemenfc
Din
The airflow quantities shown in mechani-
cal plans or in testing and balancing
reports can be used to determine the
direction of air movement intended by the
designer. Onsite examination is necessary
to determine the actual direction of airflow
at each available pathway.
Chemical smoke tubes can be used to
determine airflow directions between the
complaint area and surrounding spaces
(including the outdoors), and to reveal air
circulation patterns within the complaint
area. A micromanometer (or equivalent)
can measure the magnitude of pressure
differences between these areas. The
sketch plan and the Pollutant Pathway
Form for Investigations can be used to
record the results.
It may be necessary to make observa-
tions under different conditions, as airflow
direction can change depending upon
weather conditions, windspeed and
direction, equipment operation within the
building, traffic through doors, and other
factors (e.g., as VAV systems throttle
back). Switching air handlers or exhaust
fans on and off, opening and closing doors,
and simulating the range of operating
conditions in other ways can help to show
the different ways that airborne contami-
nants move within the building. Dust
tracking patterns around door frames can
reveal the dominant direction of air and
pollutant movement.
Some investigators study air movement
by releasing a small amount of peppermint
oil at the opening to a suspected pathway
and asking an assistant to sniff for the
Sarrple Form
Pollutant PatfTuuay for
Building Name
Address:
Investigations Form
File Number
Completed By (name):
Rooms or Zones
Connected to the
Complaint Area by
Pathways
Use
Pressure Relative to
Complaint Area
+/-
date/time
Comments
(e.g., potential
polluntant
sources)
"toothpaste" smell. If this technique is
used, it is important that the assistant have
an acute sense of smell. If the building is
in use during the investigation, occupants
may also notice the odor and could find it
distracting. Some investigators prefer to
use methods that release an odor during
unoccupied periods. Investigators should
note two common causes of false negative
results (falsely concluding that no pathway
exists):
The nose quickly becomes tolerant of
strong odors, so that the assistant may
need to take a long rest (breathing fresh
air) between tests.
If there is substantial airflow through the
pathway, the peppermint oil odor could
be diluted so that it is imperceptible.
Tracer gases such as sulfur hexafluo-
ride (SF6) can provide qualitative and
quantitative information on pollutant path-
ways and ventilation rates. Use of tracer
gases to obtain quantitative results re-
quires considerable technical expertise. If
it appears that a sophisticated study of
pathways (or ventilation rates) is required,
you need to use trained investigators.
Diagnosing IAQ Problems 69
-------
Reception
Area
Vestibule
^
0
USING POLLUTANT PATHWAY
DATA
Pollutant pathway information helps the
investigator to understand airflow patterns
in and around the complaint area. The
pollutant pathway data may indicate a need
to enlarge the complaint area, or may direct
attention toward contaminant sources that
deserve close study.
Strategies for Using Pathway
Information
Evaluate airflow patterns
Confirm or revise boundaries of the com-
plaint area
Conference
Room
Mechanical
Room
<
<
Computer Room
u
oo^-
^ Supply
Storage
Office
The receptionist and office occupants in
Zone 1 have complained of food odors.
The investigator is using a fire escape
plan to record air movement, sources,
and complaint information. The inves-
tigator has noted one hypothesis about
the cause of the complaints in the room
marked "Lounge."
70 Section 6
-------
EVE*
Airflow Patterns
Evaluate airflow patterns into and
within the complaint area. Because of
the complexity and variability of air-
flow patterns, investigators cannot be
expected to understand how air moves
within the building under all potential
operating conditions. However, data
on pathways and driving forces can
help to locate potential pollutant
sources and to understand how con-
taminants are transported to building
occupants.
AIRFLOW PATTERNS
Onsite observations
SUGGESTIONS
Look for temporal patterns
linking changes in airflow
direction to incidents of
complaints.
Look for spatial patterns
linking potential sources to
the locations of complaints.
Gonfirmar Revise I
aries of the Corrplaint Area
The discovery of unexpected pollutant
pathways can show a need to study
areas of the building that may be
distant from the original complaint
area.
COMPLAINT AREA
Complaint area connected
by architectural features to
other areas
Complaint area connected
by mechanical system to
other areas
Unintentional pathways
(e.g., cracks, holes)
SUGGESTIONS
i Check whether pressure relationships
between complaint area and sur-
rounding locations follows intent of
ventilation design.
i Check whether air from other
locations flows into the complaint
area under some conditions. If so,
consider expanding the investigation
to inventory pollutant sources (and
perhaps collect HVAC or occupant
data) in those locations.
WHAT DO YOU
KIMOWSOFAR?
Use the Hypothesis
Form on page 223 to
make brief notes after
reviewing the pollutant
pathway data.
Decide whether you
have a hypothesis that
might explain the
complaints. If so, test it.
(See page 78 for a
discussion of hypothesis
testing.)
Decide what else you
need to know. Consider
whether in-house
expertise is sufficient or
outside assistance is
needed. (See Section 8
for guidance on hiring
outside assistance.)
Diagnosing IAQ Problems 71
-------
COLLECTING SOURCE II^GRtVATION
Strategies Tools
Conduct onsite
inspection
Pollutant and Source Inventory
Chemical Inventory
Talk with building
occupants, facilities
staff, and contractors
SarrpleFctm
Pollutant and Sou
Pollutant and Source Inventory
Chemical Inventory
s Inventory Fomn
Using the list of potential source categories below, record any
indications of contamination or suspected pollutants that may require
further investigation or treatment.
Source Category
Checked
Needs Attention
Location
Comments
SOURCES OUTSIDE THE BUILDING
Contaminated Ambient Air
Pollen, dust
Industrial
contaminants
General vehicular
contaminants
San-pie Font
The inventory should include chemicals stored or used in the building
for cleaning, maintenance, operations, and pest control.
Date
Chemical/
Brand Name
Use
Storage
Location(s)
MSDS
on File?
COLLECTING INFORMATION
ON POLLUTANT SOURCES
Throughout the investigation, the building
investigator will try to identify pollutant
sources that may be causing the occupant
complaints. Any public or commercial
building is likely to contain a number of
sources that produce odors, contaminants,
or both. The investigator's task is to
identify the source(s) that may be respon-
sible for the complaint(s).
The area included in the pollutant source
inventory should be defined by the invest-
igator's understanding of the building's
architectural and mechanical layout and
pollutant pathways. Common sense will
help to differentiate unusual sources (e.g.,
spills, strong odors from new furnishings
or equipment) from those that are normally
found within or near the building.
Remember that very few sources of
indoor air contaminants are both continu-
ous and constant in volume over time.
Pollutant concentrations often vary in
strength over time, and may not be evident
at the time of the site visit. Some sources
are subtle and might only be noticed by a
trained investigator. As the investigation
progresses, the inventory of pollutant
sources may need to be revised by expand-
ing the definition of the complaint area or
examining specific locations more closely
(e.g., under various operating conditions).
Onsite Inspection
Depending upon the nature of the com-
plaint, the investigator may find some of
the following activities to be useful. This
list is not intended to be complete.
Inventory outdoor sources
m Examine the area around the outdoor air
intake for unsanitary conditions, standing
water, or nearby pollutant sources such
as exhaust vents or motor vehicles.
Observe patterns of traffic, construction
activity, and other potential sources in
the neighborhood of the building.
7 2 Section 6
-------
Inquire about outdoor ambient air
problems in the area. (This information
may be available from your local Health
Department.)
Observe soil gas entry points.
Inventory equipment sources
Review non-HVAC equipment, particu-
larly large office equipment such as
engineering drawing reproduction
machines and wet-process copiers.
Learn about usage patterns and identify
items that are not equipped with local
exhaust.
Review biocides, water treatment used
on HVAC equipment.
Review building components and
furnishings
Check drain traps to make sure they are
not dry.
Identify areas of excessive dust and/or
deteriorated furnishings.
Identify areas of soil or water damage.
Identify locations of new furnishings.
Inventory other potential sources
Identify special use areas such as
smoking lounges, laboratories, print
shops.
Identify areas where remodeling, repair,
or redecorating activities are in progress
or recently completed. Check proce-
dures being used to isolate demolition
dust, paint fumes, and other contami-
nants related to the process.
Inventory cleaning materials used in the
building.
(See Section 4 for another discussion of
problem indicators and common problems
that may become obvious during a
walkthrough of the building.)
The Pollutant and Source Inventory
can be used to record your observations.
The Chemical Inventory form is intended
to serve as a record of materials such as
solvents, biocides, pesticides, and cleaning
compounds that may require special care in
storage and handling. Material Safety
Data Sheets (MSDSs) should be collected
on these materials whenever possible.
(See Section 4 for further discussion of
MSDSs.) Portions of both forms are
shown on the poopsite page; the complete
form is included in Tab V.
Talk V\Hh Bulcfng Occxparts
and Facility Staff
Building occupants and facility staff can
provide valuable information about the
location and timing of activities that
produce odors or contaminants (e.g.,
smoking, cooking, housekeeping, mainte-
nance). They may also suggest explana-
tions for the IAQ problem that can help in
the development of hypotheses. Facility
staff and outside contractors (e.g., persons
involved in housekeeping, pest control, or
remodeling) should be interviewed or
asked to provide a current list of materials,
procedures, and schedules used for
cleaning and pest control.
It may be useful to discuss the following
items with building occupants:
Inventory activities
Review smoking policy (and actual
practice; cleaning staff may know where
smoking occurs in violation of policy,
especially in private offices).
Identify areas of overcrowding.
Review products used for housekeeping,
maintenance, and pest control and the
schedules of their use.
Inquire about housekeeping schedules
and procedures.
Identify supply storage areas and check
for well-sealed containers and proper
ventilation.
Discuss incidents that could be sources
Inquire about prior and neighboring uses
of land (e.g., landfills, underground fuel
tanks).
Inquire about events such as spills, fires,
or leaks.
If such events have occurred, learn what
remedial actions were taken to clean up
after the incidents and to prevent their
recurrence.
Diagnosing IAQ Problems 7 3
-------
PATTERNS
Location(s)
of sources
SUGGESTIONS
Compare locations of sources to locations of
complaint(s).
Identify pathways linking potential sources to the
complaint area.
Revise definition of complaint area if necessary.
Timing Note whether the sources emit on a continuous
of emissions or intermittent basis.
Compare the timing of emissions to the timing
of complaints.
Identify occasions when the source is likely to be
strongest.
Determine whether pathways between the
source(s) and the complaint location could
account for the occasions of complaints.
identify potential contaminant sources that
are unrelated to the present IAQ complaint
(i.e., either the location of the source, the
timing of emissions, or both fit poorly with
the pattern of complaints). These should
be prioritized for remedial work according
to their potential for causing health
problems or complaints in the future.
A detailed study of pollutants and
sources may involve an engineering
evaluation of equipment that is releasing
IAQ contaminants, diagnostic sampling to
assess sources in operation, or other
measurements. These may require skills or
instruments that are not available in-house.
WHAT DO YOU
KNOUVSOFAR?
Use the Hypothesis
Form on page 223 to
make brief notes after
reviewing the pollutant
source data.
Decide whether you
have a hypothesis
that might explain the
complaints. If so, test
it. (See page 78 for a
discussion of hypoth-
esis testing.)
Decide what else you
need to know.
Consider whether in-
house expertise is
sufficient or outside
assistance is needed.
(See Section 8 for
guidance on hiring
outside assistance.)
USING POLLUTANT SOURCE
DATA
If a strong pollutant source is identified in
the immediate vicinity of the complaint, a
simple test (e.g., sealing, covering, or
removing the source) can sometimes reveal
whether or not it is the cause of the IAQ
problem. If a number of potential sources
have been found in and around the
complaint area, other data (e.g., the pattern
of symptoms, the HVAC system design
and operation, and pollutant pathways)
may be needed in order to determine which
source(s), if any, may be related to the
complaint.
Strategies for Using Source
Information
Identify patterns linking emissions to
complaints
Evaluate unrelated sources
Identify Patterns Linking
Emissions toGornplainls
Look for patterns linking emissions from
potential sources to the IAQ complaints.
Eval
Ur
Evaluate sources that appear unrelated to
the complaints. It is not unusual to
SAIVPUNG AIR FOR
CONTAMIMANTS AND
INDICATORS
Although air sampling might seem to be
the logical response to an air quality
problem, such an approach may not be
required to solve the problem and can even
be misleading. Air sampling should not be
undertaken until some or all of the other
investigative activities mentioned previ-
ously have been used to collect consider-
able information. Before beginning to take
air samples, investigators should develop a
sampling strategy that is based on a
comprehensive understanding of how the
building operates, the nature of the
complaints, and a plan for interpreting the
results.
It may be desirable to take certain
routine air quality measurements during an
investigation to obtain a "snapshot" of
current conditions. These tests should be
limited to those that are indicative of very
common IAQ concerns such as tempera-
ture, relative humidity, air movement, or
carbon dioxide (CO2). Unusual readings
may or may not indicate a problem, and
should always be interpreted in perspec-
tive, based upon site-specific conditions.
Measurement of specific chemical or
biological contaminants can be very
expensive. Before expending time and
74 Section 6
-------
money to obtain measurements of indoor
air pollutants, you must decide:
how the results will be used
(e.g., comparison to standards or
guidelines, comparison to levels in
complaint-free areas)
what substances(s) should be measured
where to take samples
when to take samples
what sampling and analysis method to
use so that the results provide useful
information
It is often worthwhile for building staff
to develop skills in making temperature,
humidity, airflow, and CO2 measurements
and assessing patterns of air movement
(e.g., using chemical smoke). Appendix A
provides a brief introduction to ventilation
and thermal measurement strategies and to
methods of sampling for specific air
contaminants.
How Will the ResiJts Be Used?
Although air sampling will generate
numbers, it will not necessarily help
resolve the IAQ problem. Many IAQ
complaints are resolved without sampling
or with inconclusive sampling results.
The design of an air sampling strategy
should fit the intended use of the measure-
ments. Potential uses of indoor air
measurements include:
1. Comparing different areas of the building
or comparing indoor to outdoor condi-
tions in order to:
Confirm that a control approach has
the desired effect of reducing pollutant
concentrations or improving ventilation
Establish baseline conditions so that
they can be compared to concentrations
at other times or locations, such as
concentrations in outdoor air
concentrations in areas where no
symptoms are reported
expected "background" range for
typical buildings without perceived
IAQ problems
Test a hypothesis about the source of the
problem, such as
checking emissions from a piece of
equipment
2. Testing for "indicator" compounds
associated with particular types of
building conditions:
Peak carbon dioxide (CO2) concentra-
tions over 1000 ppm (parts per million)
are an indicator of underventilation
Carbon monoxide (CO) over several
ppm indicates inappropriate presence
of combustion by-products (which may
also account for high CO2 readings)
3. Comparing measured concentrations
to guidelines or standards
Occupational exposure standards and
guidelines, such as
OSHA PELs (Occupational Safety and
Health Administration's Permissible
Exposure Limits)
NIOSH RELs (National Institute for
Occupational Safety and Health's
Recommended Exposure Limits)
ACGIH TLVs (American Conference
of Governmental Industrial Hygienists'
Threshold Limit Values)
Occupants in this one-story
office building were complain-
ing of intermittent gasoline
odors. Exhausts from under-
ground gasoline storage tank
vent pipes (visible in the
lower right portion of this
photograph) were being
drawn into the office building
through outdoor air intakes on
this roof. The gasoline stor-
age tanks belonged to an
adjacent service station.
Diagnosing IAQ Problems 7 5
-------
It is prudent to begjn
apragnamofcherri-
cal sampling only if
symptoms or obser-
vations strongly
dfic pollutant or a
specific source may
be the cause of Uic
conrplaint and if
sampling results
tant in deter-
Public health guidelines for specific
pollutants
m EPA National Ambient Air Quality
Standards
World Health Organization Air Quality
Guidelines
Canadian Exposure Guidelines for
Residential Air Quality
There are no widely accepted procedures
to define whether IAQ test results are ac-
ceptable. Extreme caution must be used in
comparing contaminant concentrations to
existing occupational standards and guide-
lines. Although a contaminant concentra-
tion above those guidelines is a clear prob-
lem indicator, occupants may still experi-
ence health and comfort problems at con-
centrations well within those guidelines. It
is extremely rare for occupational stan-
dards to be exceeded or even ap-
proached in public and commercial
buildings, including those experiencing
indoor air quality problems.
Where specific exposure problems are
suspected, more detailed diagnostic testing
may be needed to locate or understand
major sources, confirm the exposure, and
to develop appropriate remedial actions.
For example, the control of microbial or
pesticide contamination may involve sur-
face or bulk sampling. (Surface sampling
involves wiping a measured surface area
and analyzing the swab to see what organ-
isms are present, while bulk sampling
involves analyzing a sample of suspect
material.) Specialized skills, experience,
and equipment may be needed to obtain,
analyze, and interpret such measurements.
WE* Substance(s) Should
IVeasured?
Measurement of "indicator" compounds
such as CO2 or CO can be a cost-effective
strategy. Such measurements can help the
investigator understand the nature of the
problem and define the complaint area.
Air sampling for specific pollutants
works best as an investigative tool when it
is combined with other types of informa-
tion-gathering. It is prudent to begin a
program of chemical sampling only if
symptoms or observations strongly suggest
that a specific pollutant or a specific source
may be the cause of the complaint and if
sampling results are important in determin-
ing an appropriate corrective action.
I/Irene Should fir Samples Be
Taken?
The identified problem area is an obvious
site for air sampling. Measurements taken
outdoors and in a control location (e.g., a
complaint-free area of the building) are
helpful in interpreting results from the
complaint area.
The conditions experienced by building
occupants are best simulated by sampling
air from the "breathing zone" away from
the influence of any particular individual.
However, if an individual sits at a desk all
day (except for brief periods), samplers
placed on the desk when the individual is
elsewhere can provide a good estimate of
that person's exposure.
There are several ways to locate sam-
pling sites for an IAQ investigation. One
approach first divides the building into
homogeneous areas based on key factors
identified in the building inspection and
interviews. Examples of how a building
might be divided include:
control zones (e.g., individual rooms)
types of HVAC zones (e.g., interior vs.
perimeter)
complaint vs. non-complaint areas
relationship to major sources
(e.g., spaces directly, indirectly, or not
impacted by smoking areas)
complaint types
Test sites can then be selected to repre-
sent complaints, controls, and potential
sources with a reasonable number of
samples.
76 Section 6
-------
Mrien Should Indoor fir
Sarrples Be Taken?
Samples may be designed to obtain "worst-
case" conditions, such as measurements
during periods of maximum equipment
emissions, minimum ventilation, or distur-
bance of contaminated surfaces. Worst-
case sample results can be very helpful in
characterizing maximum concentrations to
which occupants are exposed and identify-
ing sources for corrective measures.
It is also helpful to obtain samples during
average or typical conditions as a basis of
comparison. It may, however, be difficult
to know what conditions are typical. Re-
search shows that exposure to some pollut-
ants may vary dramatically as building
conditions change. Devices that allow
continuous measurements of key variables
can be helpful.
Symptoms or odors that only occur occa-
sionally will not generally be seen during
the IAQ investigation. Air samples should
not be taken if an incident is not occurring,
unless the purpose of the sample is to es-
tablish a baseline for future comparisons.
One approach to intermittent IAQ prob-
lems is for the IAQ investigator to ask
appropriate building staff or other occu-
pants to document changes over time using
day-to-day records such as the Occupant
Diary and Log of Activities and System
Operation. When an odor episode does
occur, the building engineer could inspect
the air handler and intake area while an-
other staff member documents the status of
several potential sources.
Another strategy is to manipulate
building conditions to create worst-case
conditions during the building investiga-
tion (e.g., arrange for the trash truck to idle
at the loading dock or close outdoor air
dampers to minimum settings). Chemical
smoke and tracer gases can be used to
assess where emissions may travel under
various building conditions. (Such
strategies should be carried out in ways
that minimize occupant exposure.)
1/lnat Sampling and Analysis
IVfetnod Should Be Used?
Take care to select appropriate measure-
ment techniques and to provide interpreta-
tions so that the results provide useful
information. Appendix A provides
guidance on measurement techniques that
are commonly used in IAQ investigations.
COIVPLAINTS DUE TO
OOIXDTICNS OTHER THAN
POOR AIR QUAUTY
Complaints that initially seem to be linked
to thermal discomfort, underventilation, or
indoor air pollutants may actually be
caused or complicated by factors such as:
environmental stressors (e.g., lighting,
noise, vibration)
ergonomic stressors
job-related psychosocial (human rela-
tions) stressors
The following briefly discusses each of
these three kinds of stressors. Investiga-
tors should bear in mind that complaints
produced by these stressors are sometimes
mistakenly blamed on contaminated air.
To complicate matters, such stressors also
can produce a heightened sensitivity to
poor indoor air quality. Thus, even when
specific stressors are obvious, the investi-
gator should not assume that they are the
only reason for the complaints.
Lighting
Stresses from inadequate or poorly
designed lighting (e.g., glare, flicker, poor
illumination of work surfaces) can produce
symptoms such as eyestrain and head-
aches. Lack of natural sunlight can also be
a source of stress. These complaints are
sometimes mistakenly interpreted as signs
of poor indoor air quality. Lighting
problems may be evident in large areas or
localized in particular workspaces.
tigators should
1 in rrind that
con-plaints pioduocd
by these stressors
are son'ctoii'cs rns-
takerly blamed on
oontamnated air. To
oon|3licalje matters,
such stressors also
ened sensitivity to
poor indoor air qual-
ity-
Diagnosing IAQ Problems 7 7
-------
The glare from the windows
was causing a variety of
occupant complaints in this
building and was disrupting
the workers' ability to use the
video display terminals.
Complaints such as
headaches are sometimes
incorrectly blamed on poor
indoor air quality.
Noise
Noisy surroundings can reduce the ability
to concentrate and produce stress-related
symptoms such as headaches. Noise can
also contribute to job dissatisfaction,
particularly if the problem is caused by
overcrowding or other factors likely to
produce a sense of substandard work
conditions.
The ear gets used to sounds quickly, so it
is possible for a complainant to be unaware
of a constant or regular sound. Investiga-
tors should recognize that noise can be a
source of stress, even if it is not reported as
a problem and is within current industrial
exposure criteria (which are designed
primarily to prevent hearing loss).
Vibration
Low-frequency vibration is another source
of stress that may go unreported by
building occupants or become confused
with pollutant problems. Vibration can be
caused by nearby machinery or movement
of the building as a whole; motion sickness
has been reported in some high rise
buildings that sway in the wind.
Eropnomc Stressors
Fatigue, circulatory problems, and other
physical problems can be produced by
furniture that is mismatched to the task,
such as chairs that are the wrong height for
computer terminals. If IAQ investigators
inquire about whether new furniture has
recently been installed in the problem area
(to determine if the furniture could be
contributing to increased contaminant
levels), they should also ask about
whether the occupant finds the furniture
comfortable.
Stressors
It is well documented that various job-
related psychosocial conditions can
produce symptoms in workers. Excessive
workload and work pressure are easily
recognized job Stressors. Lack of clarity
about what is expected of the worker (role
ambiguity) and the presence of conflicting
expectations (role conflict) are also
commonly encountered Stressors in
modern organizations. Poor interpersonal
relations, management styles that allow
little participation in decision-making, and
factors related to career development are
also thought to be potentially stressful.
FGRMIMG AND TESTI IMG
HYPOTHESES
As the building investigation progresses,
you should be developing one or more
hypotheses that could explain the occupant
complaints. The investigation can then be
shaped to collect information that will
either support or refute your hypotheses.
The Hypothesis Form on the opposite
page is designed to pull together the
separate pieces of information that have
been collected by summarizing the results
of the investigation. More pages can be
added if desired, but the form is designed
for brief notes that can be scanned easily.
As you review the information, write down
78 Section 6
-------
any explanation(s) for the IAQ problem that
make sense, and think about how the
pieces of the puzzle fit together when
building conditions are compared to
occupant complaints.
Is all (or most) of your information
consistent with your hypothesis? If not, is
there a reasonable explanation for the
inconsistencies? A different hypothesis
might provide a better fit with your
information.
You may find that there are several IAQ
problems (e.g., underventilation in one
zone, a strong contaminant source in
another room). If you have discovered
potential IAQ problems that do not appear
related to the original complaint, they can
be prioritized and corrected as time and
funding permit.
Think of ways to test your hypotheses.
You may want to change ventilation rates,
change the pressure relationship between
spaces, cover or remove suspected sources,
seal pathways, or temporarily relocate
affected individuals. If your manipulations
can reduce occupant complaints, you have
found a reasonable hypothesis. Sometimes
it is not possible (or not practical) to
manipulate important factors. You can also
test your hypothesis by seeing how accu-
rately you can predict changes in building
conditions (e.g., as outdoor temperature
changes).
If you are having difficulty developing
hypotheses, review the information you
have collected and the suggestions about
how to use that information. For sugges-
tions on using occupant complaint data, see
pages 53-57; on using HVAC system
information, see pages 62-67; on using
pollutant pathway information, see pages
70-71; on using pollutant/source inventory
data, see page 74; on using air sampling
information, see pages 75-76.
The changes that are made during
hypothesis testing may offer a practical
solution to the IAQ problem, or may be
only temporary measures. The mitigation
chapter presents a variety of approaches
that have been used in correcting some
selected categories of IAQ problems and
discusses how to evaluate those strategies.
Sarrple Perm
Hypothesis Form
Complaint Area (may be revised as the investigation progresses):
Complaints (e.g., summarize patterns of timing, location, people
affected):
HVAC: Does the ventilation system appear to provide adequate air,
efficiently distributed to meet occupant needs in the complaint area? If
not, what problems do you see?
Pathways: What pathways and driving forces connect the complaint
area to locations of potential sources?
Diagnosing IAQ Problems 7 9
-------
Mtigating IAQ Problem
Oe
"er the years many types of mitigation
(correction) strategies have been imple-
mented to solve indoor air quality prob-
lems. The purpose of this section is to
provide an understanding of basic ap-
proaches to mitigation and the various
solutions that can be effective in treating
commonly-encountered IAQ problems. It
is not intended to provide detailed instruc-
tions for using each type of mitigation
approach but rather to give guidance in
selecting a mitigation strategy and in
judging proposals from in-house staff or
outside consultants.
Mitigation of indoor air quality prob-
lems may require the involvement of
building management and staff represent-
ing such areas of responsibility as:
facility operation and maintenance
housekeeping
shipping and receiving
purchasing
policymaking
staff training
Successful mitigation of IAQ problems
also requires the cooperation of other
building occupants, including the employ-
ees of building tenants. Occupants must be
educated about the cause(s) of the IAQ
problems and about actions that must be
taken or avoided to prevent a recurrence of
the problems.
BACKGROUND: CONTROLLING
INDOOR AIR PROBLEIVB
Section 2 introduced the idea that indoor
air quality problems result from interac-
tions between contaminant source,
building site, building structure, activities
within the building, mechanical equipment,
climate, and occupants. Efforts to control
indoor air contaminants change the
relationships between these factors. There
are many ways that people can intervene in
these relationships to prevent or control
indoor air contaminant problems. Control
strategies can be categorized as:
source control
ventilation
air cleaning
exposure control
Successful mitigation often involves a
combination of these strategies. Possible
remedies for the other environmental
stressors discussed in Section 6 are
discussed briefly below.
Source Control
All efforts to prevent or correct IAQ
problems should include an effort to
identify and control pollutant sources.
Source control is generally the most cost
effective approach to mitigating IAQ
problems in which point sources of
contaminants can be identified. In the case
of a strong source, source control may be
the only solution that will work.
The following are categories and
examples of source control:
Remove or reduce the source
prohibit smoking indoors or limit
smoking to areas from which air is
exhausted, not recirculated (NIOSH
regards smoking areas as an interim
solution)
relocate contaminant-producing equip-
ment to an unoccupied, better ventilated,
or exhaust-only ventilated space
select products which produce fewer or
less potent contaminants while maintain-
ing adequate safety and efficacy
Mitigating IA Q Problems 81
-------
modify other occupant activities
Seal or cover the source
m improve storage of materials that
produce contaminants
seal surfaces of building materials that
emit VOCs such as formaldehyde
Modify the environment
after cleaning and disinfecting an area
that is contaminated by fungal or
bacterial growth, control humidity to
make conditions inhospitable for
regrowth
Source removal or reduction can
sometimes be accomplished by a one-time
effort such as thorough cleaning of a spill.
In other cases, it requires an ongoing
process, such as establishing and enforcing
a non-smoking policy.
Sealing or covering the source can be a
solution in some cases; application of a
barrier over formaldehyde-emitting
building materials is an example. Sealing
may also involve educating staff or
building occupants about the contaminant-
producing features of materials and
supplies and inspecting storage areas to
ensure that containers are properly
covered.
In some cases, modification of the
environment is necessary for effective
mitigation. If the indoor air problem
arises from microbiological contaminants,
for example, disinfection of the affected
area may not eliminate the problem.
Regrowth of microbiologicals could
occur unless humidity control or other
steps, such as adding insulation to prevent
surface condensation, are taken to make
the environment inhospitable to micro-
biologicals.
Ventilation
Ventilation modification is often used to
correct or prevent indoor air quality
problems. This approach can be effective
either where buildings are underventilated
or where a specific contaminant source
cannot be identified. Ventilation can be
used to control indoor air contaminants by:
Diluting contaminants with outdoor air
increase the total quantity of supply air
(including outdoor air)
increase the proportion of outdoor air to
total air
improve air distribution
Isolating or removing contaminants by
controlling air pressure relationships
install effective local exhaust at the
location of the source
avoid recirculation of air that contains
contaminants
locate occupants near supply diffusers
and sources near exhaust registers
use air-tightening techniques to maintain
pressure differentials and eliminate
pollutant pathways
make sure that doors are closed where
necessary to separate zones
Diluting contaminants by increasing
the flow of outdoor air can be accom-
plished by increasing the total supply
airflow in the complaint area (e.g., opening
supply diffusers, adjusting dampers) or at
the air handling unit, (e.g., cleaning the
filter on the supply fan). An alternative is
to increase the proportion of outdoor air
(e.g., adjusting the outdoor air intake
damper, installing minimum stops on
variable air volume (VAV) boxes so that
they satisfy the outdoor air requirements of
ASHRAE 62-1989).
Studies have shown that increasing
ventilation rates to meet ASHRAE
Standard 62-1989 (e.g., from 5 to 15 or 20
cfm/person) does not necessarily signifi-
cantly increase the total annual energy
consumption. The increase appears to be
less than 5% in typical commercial
buildings. The cost of ventilation is
generally overshadowed by other operating
costs, such as lighting. Further, improved
maintenance can produce energy savings
to balance the costs that might otherwise
result from increased ventilation.
82 Section 7
-------
The cost of modifying an existing
HVAC system to condition additional
outdoor air can vary widely depending
upon the specific situation. In some
buildings, HVAC equipment may not have
sufficient capacity to allow successful
mitigation using this approach. Original
equipment is often oversized so that it can
be adjusted to handle the increased load,
but in some cases additional capacity is
required.
Most ventilation deficiencies appear to
be linked to inadequate quantities of
outdoor air. However, inadequate distribu-
tion of ventilation air can also produce
IAQ problems. Diffusers should be
properly selected, located, installed, and
maintained so that supply air is evenly
distributed and blends thoroughly with
room air in the breathing zone. Short-
circuiting occurs when clean supply air is
drawn into the return air plenum before it
has mixed with the dirtier room air and
therefore fails to dilute contaminants.
Mixing problems can be aggravated by
temperature stratification. Stratification
can occur, for example, in a space with
high ceilings in which ceiling-mounted
supply diffusers distribute heated air.
Note the side effects of increased
ventilation:
mitigation by increasing the circulation
of outdoor air requires good outdoor air
quality
increased supply air at the problem
location might mean less supply air in
other areas
increased total air in the system and
increased outdoor air will both tend to
increase energy consumption and may
require increased equipment capacity
any approach which affects airflow in
the building can change pressure
differences between rooms (or zones)
and between indoors and outdoors, and
might lead to increased infiltration of
unconditioned outdoor air
increasing air in a VAV system may
overcool an area to the extent that
terminal reheat units are needed
Ventilation equipment can be used to
isolate or contain contaminants by
controlling pressure relationships. If the
contaminant source has been identified,
this strategy can be more effective than
dilution. Techniques for controlling air
pressure relationships range from adjust-
ment of dampers to installation of local
exhaust.
Using local exhaust confines the spread
of contaminants by capturing them near the
source and exhausting them to the out-
doors. It also dilutes the contaminant by
drawing cleaner air from surrounding areas
into the exhaust airstream. If there are
return grilles in a room equipped with local
exhaust, the local exhaust should exert
enough suction to prevent recirculation of
contaminants. Properly designed and
installed local exhaust results in far lower
contaminant levels in the building than
could be accomplished by a general
increase in dilution ventilation, with the
added benefit of costing less.
Note that replacement air must be able
to flow freely into the area from which the
exhaust air is being drawn. It may be
necessary to add door or wall louvers in
order to provide a path for the make-up air.
(Make sure that this action does not violate
fire codes.)
Correct identification of the pollutant
source and installation of the local exhaust
is critically important. For example, an
improperly designed local exhaust can
draw other contaminants through the
occupied space and make the problem
worse.
The physical layout of grilles and
diffusers relative to room occupants and
pollutant sources can be important. If
supply diffusers are all at one end of a
room and returns are all at the other end,
the people located near the supplies may
be provided with relatively clean air while
those located near the returns breathe air
that has already picked up contaminants
from all the sources in the room that are
not served by local exhaust.
Mitigating IA Q Problems S 3
-------
Elimination of pollutant pathways by air
sealing (e.g., caulking cracks, closing
holes) is an approach that can increase the
effectiveness of other control techniques.
It can be a difficult technique to implement
because of hidden pathways (e.g., above
drop ceilings, under raised flooring
against brick or block walls). However, it
can have other benefits such as energy
savings and more effective pest control (by
eliminating paths used by vermin).
Air Clearing
The third IAQ control strategy is to clean
the air. Air cleaning is usually most effec-
tive when used in conjunction with either
source control or ventilation; however, it
may be the only approach when the source
of pollution is outside of the building.
Most air cleaning in large buildings is
aimed primarily at preventing contaminant
buildup in HVAC equipment and enhanc-
ing equipment efficiency.
Air cleaning equipment intended to
provide better indoor air quality for occu-
pants must be properly selected and de-
signed for the particular pollutants of inter-
est (for example, gaseous contaminants can
be removed only by gas sorption). Once
installed, the equipment requires regular
maintenance in order to ensure good per-
formance; otherwise it may become a
major pollutant source in itself. This main-
tenance requirement should be borne in
mind if an air cleaning system involving a
large number of units is under consider-
ation for a large building. If room units are
used, the installation should be designed
for proper air recirculation.
There are four technologies that remove
contaminants from the air:
paniculate filtration
electrostatic precipitation
negative ion generation
gas sorption
The first three approaches are designed
to remove particulates, while the fourth is
designed to remove gases.
Particulate filtration removes sus-
pended liquid or solid materials whose
size, shape and mass allow them to remain
airborne for the air velocity conditions
present. Filters are available in a range of
efficiencies, with higher efficiency indicat-
ing removal of a greater proportion of
particles and of smaller particles. Moving
to medium efficiency pleated filters is
advisable to improve IAQ and increase
protection for equipment. However, the
higher the efficiency of the filter, the more
it will increase the pressure drop within the
air distribution system and reduce total
airflow (unless other adjustments are made
to compensate). It is important to select an
appropriate filter for the specific
application and to make sure that the
HVAC system will continue to perform as
designed. Filters are rated by different
standards (e.g., arrestance and dust spot)
which measure different aspects of
performance.
Electrostatic precipitation is another
type of paniculate control. It uses the
attraction of charged particles to oppo-
sitely charged surfaces to collect airborne
par-ticulates. In this process, the particles
are charged by ionizing the air with an
electric field. The charged particles are
then col-lected by a strong electric field
generated between oppositely-charged
electrodes. This provides relatively high
efficiency filtration of small respirable
particles at low air pressure losses.
Electrostatic precipitators may be in-
stalled in air distribution equipment or in
specific usage areas. As with other filters,
they must be serviced regularly. Note,
however, that electrostatic precipitators
produce some ozone. Because ozone is
harmful at elevated levels, EPA has set
standards for ozone concentrations in out-
door air, and NIOSH and OSHA have
84 Section 7
-------
established guidelines and standards, re-
spectively, for ozone in indoor air. The
amount of ozone emitted from electrostatic
precipitators varies from model to model.
Negative ion generators use static
charges to remove particles from the indoor
air. When the particles become charged,
they are attracted to surfaces such as walls,
floors, table tops, draperies, and occupants.
Some designs include collectors to attract
the charged particles back to the unit.
Negative ion generators are not available
for installation in ductwork, but are sold as
portable or ceiling-mounted units. As with
electrostatic precipitators, negative ion
generators may produce ozone, either
inten-tionally or as a by-product of use.
Gas sorption is used to control com-
pounds that behave as gases rather than as
particles (e.g., gaseous contaminants such
as formaldehyde, sulfur dioxide, ozone, and
oxides of nitrogen). Gas sorption involves
one or more of the following processes
with the sorption material (e.g., activated
carbon, chemically treated active clays): a
chemical reaction between the pollutant
and the sorbent, a binding of the pollutant
and the sorbent, or diffusion of the con-
taminant from areas of higher concentration
to areas of lower concentration. Gas sorp-
tion units are installed as part of the air
distribution system. Each type of sorption
material performs differently with different
gases. Gas sorption is not effective for
removing carbon monoxide. There are no
standards for rating the performance of
gaseous air cleaners, making the design and
evaluation of such systems problematic.
Operating expenses of these units can be
quite high, and the units may not be effec-
tive if there is a strong source nearby.
Exposure Control
Exposure control is an administrative ap-
proach to mitigation that uses behavioral
methods, such as:
Scheduling contaminant-producing acti-
vities to avoid complaints
schedule contaminant-producing activi-
ties to occur during unoccupied periods
notify susceptible individuals about up-
coming events (e.g., roofing, pesticide
application) so that they can avoid contact
with the contaminants
Scheduling contaminant-producing ac-
tivities for unoccupied periods whenever
possible is simple common sense. It may
be the best way to limit complaints about
activities (such as roofing or demolition)
which unavoidably produce odors or dust.
Relocating susceptible individuals
move susceptible individuals away from
the area where they experience symptoms
Controlling exposure by relocating sus-
ceptible individuals may be the only practi-
cal approach in a limited number of cases,
but it is probably the least desirable option
and should be used only when all other
strategies are ineffective in resolving com-
plaints.
Remedies for Gornplainls Not
Attributed to Poor Air Quality
Specific lighting deficiencies or localized
sources of noise or vibration can sometimes
be readily identified, and remedial action
may be fairly straightforward (more or
fewer lights on, adjustments for glare; relo-
cating, replacing or acoustically insulating a
noise or vibration source). Similarly, fla-
grant ergonomic stress or blatant psycho-
social stress may be apparent even to
an untrained observer.
In other cases, however, problems may
be more subtle or solutions more complex.
Since specialized knowledge, skills, and
instrumentation are usually needed to
evaluate lighting, noise, vibration, ergo-
nomic stress, or psychosocial stress, such
evaluations are generally best done by a
qualified professional in that particular
field.
Mitigating IA Q Problems 8 5
-------
Remedial actions for lighting, noise,
and vibration problems might range from
modifications of equipment or furnishings
to renovation of the building. Ergonomic
deficiencies may require furniture or
equipment changes or different work
practices. The solution to psychosocial
problems may involve new management
practices, job redesign, or resolution of
underlying labor-management problems.
SAIVPLE PROBLEMS AIXD
SOLUTIONS
In the investigation section you were
introduced to a variety of problems that are
often found in buildings. This section
presents fifteen categories of IAQ prob-
lems. Specific problem "examples" are
given, followed by solutions" that have
been used for that category of problem.
Most of the problems presented here are
common and do not have serious, life-
threatening consequences. At the end of
the section is a brief description of
problems that can have severe health
impacts. The basic correction principles
that apply to these serious problems are
similar to those used in less critical
situations.
Reading these examples may help you
to think about the best way to solve your
indoor air quality problems. Remember
that these are brief sketches, and apparent
parallels to your building could be mis-
leading. It is better to carry out a building
investigation and learn the specific facts in
your own case, rather than adopt a mitiga-
tion approach that might not be appropri-
ate. Attempting to correct IAQ problems
without understanding the cause of those
problems can be both ineffective and
expensive.
You will note that some solutions are
simple and low-cost, while others are
complex and expensive. Do not assume
that each solution listed would be an
effective treatment for all of the problems
in its category.
The example problems and solutions are
presented in the following sequence:
Problem #1: Outdoor air ventilation rate
is too low
Problem #2: Overall ventilation rate is
high enough, but poorly
distributed and not sufficient
in some areas
Problem #3: Contaminant enters building
from outdoors
Problem #4: Occupant activities contrib-
ute to air contaminants or to
comfort problems
Problem #5: HVAC system is a source of
biological contaminants
Problem #6: HVAC system distributes
contaminants
Problem #7: Non-HVAC equipment is a
source or distribution mecha-
nism for contaminants
Problem #8: Surface contamination due to
poor sanitation or accidents
Problem #9: Mold and mildew growth
due to moisture from con-
densation
Problem #10: Building materials and
furnishings produce
contaminants
Problem #11: Housekeeping or mainte-
nance activities contribute to
problems
Problem #12: Specialized use areas as
sources of contaminants
Problem #13: Remodeling or repair activi-
ties produce problems
Problem #14: Combustion gases
Problem #15: Serious building-related
illness
86 Section 7
-------
Outdoor Air Ventilation
Rate is Too Low
Routine odors from occupants and
normal office activities result in problems
(e.g., drowsiness, headaches, discomfort)
Measured outdoor air ventilation rates do
not meet guidelines for outdoor air supply
(e.g., design specifications, applicable
codes, or ASHRAE 62-1989)
Peak CO Concentrations above 1000
ppm indicate inadequate ventilation
Corrosion of fan casing causes air
bypassing and reduces airflow in system
Solutions
Open, adjust or repair air distribution
system
outdoor air intakes
mixing and relief dampers
supply diffusers
fan casings
Increase outdoor air within the design
capacity of
air handler
heating and air conditioning equipment
distribution system
Modify components of the HVAC system
as needed to allow increased outdoor air
(e.g., increase capacity of heating and
cooling coils)
Design and install an updated ventilation
system
Reduce the pollutant and/or thermal load
on the HVAC system
reduce the occupant density: relocate
some occupants to other spaces to
redistribute the load on the ventilation
system
relocate or reduce usage of heat-
generating equipment
Malfunctioning controls such as this broken
damper linkage can virtually eliminate
intake of outdoor air. Such problems may
go undetected for years without a careful
investigation of the HVAC system
components.
Mitigating IA Q Problems 8 7
-------
Overall Ventilation Rate Is
High Enough, But Poorly
Distributed and Not
Sufficient in Some Areas
Complaining of discomfort, building
occupants blocked air supply diffusers in
their work areas. The HVAC system in this
building was in poor condition and was not
balanced.
Exarrples
Measured outdoor air meets guidelines at
building air inlet, but there are zones
where heat, routine odors from occu-
pants, and normal office activities result
in complaints
(e.g., drowsiness, headaches, comfort
complaints)
Solutions
Open, adjust, or repair air distribution
system
supply diffusers
return registers
Ensure proper air distribution
balance the air handling system
make sure that there is an air gap at tops
and bottoms of partitions to prevent dead
air space
relocate supply and/or return diffusers to
improve air distribution
Seal leaky ductwork
Remove obstructions from return air
plenum
Control pressure relationships
install local exhaust in problem areas
and adjust HVAC system to provide
adequate make-up air
move occupants so that they are closer to
supply diffusers
relocate identified contaminant sources
closer to exhaust intakes
Reduce source by limiting activities or
equipment use that produce heat, odors,
or contaminants
Design and install an appropriate
ventilation system
88 Section 7
-------
Contaminant Entering
Building From Outdoors
.^5
Soil gases
(e.g., radon, gasoline from tanks, methane
from landfills)
Contaminants from nearby activities
(e.g., roofing, dumpster, construction)
Outdoor air intake near source
(e.g., parking, loading dock, building
exhaust)
Outdoor air contains pollutants or excess
moisture
(e.g., cooling tower mist entrained in
outdoor air intake)
Solutions
Remove the source, if it can be moved
easily
remove debris around outdoor air intake
relocate dumpster
Reduce source (for example, shift time of
activity to avoid occupied periods)
painting, roofing, demolition
housekeeping, pest control
Relocate elements of the ventilation
system that contribute to entry of outdoor
air contaminants
separate outdoor air intakes from sources
of odors, contaminants
separate exhaust fan outlets from
operable windows, doors, air intakes
make rooftop exhaust outlets taller than
intakes
-------
Problem #4
Occupant Activities
Contribute to Air
Contaminants or to
Comfort Problems
Personal equipment such as humidifiers
brought in by building occupants can
become a source of contaminants if not
properly maintained. An effective
communication strategy can help
occupants to understand their role in
causing indoor air quality problems and in
correcting those problems.
Exarrples
Smoking
Special activities such as print shops,
laboratories, kitchens
Interference with HVAC system
operation:
blockage of supply diffusers to eliminate
drafts
turning off exhaust fans to eliminate
noise
use of space heaters, desktop humidifiers
to remedy local discomfort
(Note: While such interference can cause
IAQ problems, it is often initiated in
response to unresolved ventilation or
temperature control problems.)
Solutions
Remove the source by eliminating the
activity
(Note: This may require a combination of
policy-setting and educational outreach.)
smoking
use of desktop humidifiers and other
personal HVAC equipment
unsupervised manipulation of HVAC
system
Reduce the source
select materials and processes which
minimize release of contaminants while
maintaining adequate safety and efficacy
(e.g., solvents, art materials)
Install new or improved local exhaust to
accommodate the activity, adjust HVAC
system to ensure adequate make-up air,
and verify effectiveness
smoking lounge, storage areas which
contain contaminant sources
laboratory hoods, kitchen range hoods
(venting to outdoors, not recirculating)
90 Section 7
-------
HVAC System is a Source of
Biological Contaminants
The HVAC system can act as a source of
contaminants by providing a hospitable
environment for the growth of microorgan-
isms and by then distributing biologically-
contaminated air within the building.
Surface contamination by molds (fungi),
bacteria
drain pans
interior of ductwork
air filters and filter media (collected
debris).
Solutions
Remove source by improving mainte-
nance procedures
inspect equipment for signs of corrosion,
high humidity
replace corroded parts
clean drip pans, outdoor air intakes,
other affected locations
use biocides, disinfectants, and sanitizers
with extreme caution and ensure that
occupant exposure is minimized
(Note: See discussion of duct cleaning in
Appendix B.)
Provide access to all the items that
must be cleaned, drained, or replaced
periodically
This blackish deposit was scraped from a
poorly-maintained air handling unit drain
pan. The pan contained nutrients caused
by poor upstream filtration and stagnant
water that fostered the growth of
microbiological contaminants.
Mitigating IA Q Problems 91
-------
HVAC System Distributes
Contaminants
Standing water on a roof can cause water
damage and potential mold growth sites
inside the building as well as providing a
breeding area for insects and
microbiologicals such as Legionella. The
outside air intake (near the far left of this
photograph) is located close to the
standing water and could be drawing in
insects and microbiological contaminants.
Exarrples
Unfiltered air bypasses filters due to
problems
filter tracks are loose
poorly-maintained filters sag when they
become overloaded with dirt
filters are the wrong size
Recirculation of air that contains dust or
other contaminants
system recirculates air from rooms
containing pollutant sources
return air plenum draws air from rooms
that should be exhausted (e.g. janitor's
closets)
return air plenums draw soil gases from
interiors of block corridor walls that
terminate above ceilings
Solutions
Modify air distribution system to
minimize recirculation of contaminants
provide local exhaust at point sources of
contaminants, adjust HVAC system to
provide adequate make-up air, and test to
verify performance
increase proportion of outdoor air
seal unplanned openings into return air
plenums and provide alternative local
ventilation (adjust HVAC system to
provide adequate make-up air and test to
verify performance)
Improve housekeeping, pest control,
occupant activities, and equipment use to
minimize release of contaminants from
all sources
Install improved filtration equipment to
remove contaminants
Check filter tracks for any gaps
92 Section 7
-------
Non-HVAC Equipment is
a Source or Distribution
Mechanism for Contaminants
This discussion pertains to medium- to
large-scale pieces of equipment.
Non-HVAC equipment can produce
contaminants, as in the case of:
wet process copiers
large dry process copiers
engineering drawing reproduction
machines
It can also distribute contaminants, as in
the case of:
elevators, which can act as pistons and
draw contaminants from one floor to
another
Solutions
Install local exhaust near machines
(Note: Adjust HVAC system to provide
adequate make-up air, and test to verify
performance.)
Reschedule use to occur during periods of
low occupancy
Remove source
relocate occupants out of rooms
that contain contaminant-generating
equipment
relocate equipment into special use
areas equipped with effective exhaust
ventilation (test to verify control of air
pressure relationships)
Change air pressure relationships to
prevent contaminants from entering
elevator shaft
Sometimes there are unusual sources of
indoor air quality problems. An inspection
of the HVAC system revealed air filters
covered with a graphite dust deposit from a
broken elevator motor generator. The
motor generator was repaired and
corrections were made to prevent the
crossover of ventilation air from the motor
generator into the HVAC mechanical room.
Mitigating IA Q Problems 9 3
-------
Surface Contamination
Due to Poor Sanitation or
Accidents
The carpet on this floor was flooded
and an outbreak of humidifier fever
occurred. To eliminate microbiologicals,
the contaminated carpet was removed and
new carpet was installed.
Biological contaminants result in aller-
gies or other diseases
fungal, viral, bacterial (whole organisms
or spores)
bird, insect, or rodent parts or droppings,
hair, dander (in HVAC, crawlspace,
building shell, or near outdoor air
intakes)
Accidents
spills of water, beverages, cleansers,
paints, varnishes, mastics or specialized
products (printing, chemical art supplies)
fire damage: soot, odors, chemicals
Solutions
Clean
HVAC system components
some materials and furnishings (others
may have to be discarded)
(Note: Use biocides, disinfectants, and
sanitizers with caution and ensure that
occupant exposure is minimized.)
Remove sources of microbiological
contamination
water-damaged carpet, furnishings, or
building materials
Modify environment to prevent recur-
rence of microbiological growth
improve HVAC system maintenance
control humidity or surface temperatures
to prevent condensation
Provide access to all items that require
periodic maintenance
Use local exhaust where corrosive
materials are stored
Adjust HVAC system to provide adequate
make-up air, and test to verify perfor-
mance
94 Section 7
-------
PraUem#a
Mold and Mildew Growth
Due to Moisture from
Condensation
Interior surfaces of walls near thermal
bridges
(e.g., uninsulated locations around struc-
tural members)
Carpeting on cold floors
Locations where high surface humidity
promotes condensation
Solutions
Clean and disinfect to remove mold and
mildew.
(Note: Follow up by taking actions to
prevent recurrence of microbiological
contamination. Use biocides, disinfec-
tants, and sanitizers with caution and
ensure that occupant exposure is mini-
mized.)
Increase surface temperatures to treat
locations that are subject to condensation
insulate thermal bridges
improve air distribution
Reduce moisture levels in locations that
are subject to condensation
repair leaks
increase ventilation (in cases where
outdoor air is cold and dry)
dehumidify (in cases where outdoor air
is warm and humid)
Dry carpet or other textiles promptly after
steam cleaning
(Note: Increase ventilation to accelerate
drying.)
Discard contaminated materials
This is a school crawlspace in which
moisture should be controlled. The fungus
is Fusarium, some species of which are
toxigenic and should not be inside. The
spores were distributed by the air handler
because the return plenum was open to the
crawlspace.
Mitigating IA Q Problems 9 5
-------
Building Materials and
Furnishings Produce
Contaminants
Odors from newly installed carpets,
furniture, wall coverings
Newly dry cleaned drapes or other textiles
Low levels of contaminants are emitted
from many of the building materials
and furnishings in an office. Dust can
accumulate on stacks of papers and
open shelves. Depending on how
they are cared for, plants potentially
add moisture, soil microbiologicals,
and pesticides.
Solutions
Remove source with appropriate cleaning
methods
steam clean carpeting and upholstery,
then dry quickly, ventilating to acceler-
ate the drying process
accept only fully dried, odorless
drycleaned products
Encapsulate source
seal surfaces of building materials that
emit formaldehyde
Reduce source
schedule installation of carpet, furniture,
and wall coverings to occur during
periods when the building is unoccupied
have supplier store new furnishings in a
clean, dry, well-ventilated area until
VOC outgassing has diminished
Increase outdoor air ventilation
total air supplied
proportion of fresh air
Remove the materials that are producing
the emissions and replace with lower
emission alternatives
(Note: Only limited information on
emissions from materials is available at
this time. Purchasers can request that
suppliers provide emissions test data, but
should use caution in interpreting the test
results.)
96 Section 7
-------
Problem#11:
Housekeeping or Maintenance
Activities Contribute to
Problems
Cleaning products emit chemicals, odors
Particulates become airborne during
cleaning (e.g., sweeping, vacuuming)
Contaminants are released from painting,
caulking, lubricating
Frequency of maintenance is insufficient
to eliminate contaminants
Solutions
Remove source by modifying standard
procedures or frequency of maintenance
(Note: Changing procedures may require a
combination of policy-setting and training
in IAQ impacts of staff activities.)
improve storage practices
shift time of painting, cleaning, pest
control, other contaminant-producing
activities to avoid occupied periods
make maintenance easier by improving
access to filters, coils, and other compo-
nents
Reduce source
select materials to minimize emissions of
contaminants while maintaining ad-
equate safety and efficacy
use portable HEPA (high efficiency
paniculate arrestance") vacuums vs. low-
efficiency paper-bag collectors
Use local exhaust
on a temporary basis to remove contami-
nants from work areas
as a permanent installation where
contaminants are stored
Indoor air quality problems can be caused
by lack of adequate house-keeping
practices. On the other hand, deodorizers,
cleansers and other products can also
produce odors and contaminants.
Mitigating IA Q Problems 9 7
-------
Specialized Use Areas as
Sources of Contaminants
.^
^$ "
%
&* ^
Pi5* * *
^
\
%
i,
X
S
^
^
^
A*.^^
?, " ^ \«
Exarrples
Food preparation
Art or print rooms
Laboratories
Solutions
Change pollutant pathway relationships
ran specialized use area under negative
pressure relative to surrounding areas
install local exhaust, adjust HVAC
system to provide make-up air, and test
to verify performance
Remove source by ceasing, relocating, or
rescheduling incompatible activities
Reduce source by selecting materials to
minimize emissions of contaminants
while maintaining adequate safety and
efficacy
Reduce source by using proper sealing
and storage for materials that emit
contaminants
This chemical storage room should be
maintained under negative pressure.
Properly designed and maintained local
exhaust will achieve the proper air pressure
relationship with surrounding areas.
Otherwise, such storage areas can be a
source of occupant exposure to many
airborne contaminants.
98 Section 7
-------
Remodeling or Repair
Activities Produce Problems
Temporary activities produce odors and
contaminants
installation of new particleboard,
partitions, carpet, or furnishings
painting
reroofing
demolition
Existing HVAC system does not provide
adequate ventilation for new occupancy
or arrangement of space
Solutions
Modify ventilation to prevent recircula-
tion of contaminants
install temporary local exhaust in
work area, adjust HVAC system to
provide make-up air, and test to
verify performance
seal off returns in work area
close outdoor air damper during
re-roofing
Reduce source by scheduling work for
unoccupied periods and keeping ventila-
tion system in operation to remove odors
and contaminants
Reduce source by careful materials
selection and installation
select materials to minimize emissions
of contaminants while maintaining
adequate safety and efficacy
have supplier store new furnishings in a
clean, dry, well-ventilated area until
VOC outgassing has diminished
request installation procedures (e.g.,
adhesives) that limit emissions of
contaminants
Modify HVAC or wall partition layout if
necessary
partitions should not interrupt airflow
relocate supply and return diffusers
adjust supply and return air quantities
adjust total air and/or outdoor air supply
to serve new occupancy
Remodeling may involve
many activities that can
cause IAQ problems.
Ventilation modifications can
be used to isolate the work
area and prevent pollutant
build-up in occupied spaces.
Proper storage practices can
minimize the release of
contaminants.
Mitigating IA Q Problems 9 9
-------
Combustion Gases
Combustion odors can indicate the
existence of a serious problem. One
combustion product, carbon monoxide, is
an odorless gas. Carbon monoxide
poisoning can be life-threatening.
Air intakes are frequently located near the
loading dock for aesthetic reasons.
Unfortunately, this air intake placement can
draw car and truck exhaust into the
building, causing a variety of indoor air
quality complaints.
Exarrples
Vehicle exhaust
m offices above (or connected to) an
underground parking garage
rooms near (or connected by pathways
to) a loading dock or service garage
Combustion gases from equipment
(e.g., spillage from inadequately vented
appliances, cracked heat exchanger, re-
entrainment because local chimney is too
low)
areas near a mechanical room
distributed throughout zone or entire
building
Solutions
Seal to remove pollutant pathway
close openings between the contaminant
source and the occupied space
install well-sealed doors with automatic
closers between the contaminant source
and the occupied space
Remove source
improve maintenance of combustion
equipment
modify venting or HVAC system to
prevent backdrafting
relocate holding area for vehicles at
loading dock, parking area
turn off engines of vehicles that are
waiting to be unloaded
Modify ventilation system
install local exhaust in underground
parking garage (adjust HVAC system to
provide make-up air and test to verify
performance)
relocate fresh air intake (move away
from source of contaminants
Modify pressure relationships
pressurize spaces around area containing
source of combustion gases
100 Section 7
-------
Serious Building-Related
Illness
Some building-related illnesses can be life-
threatening. Even a single confirmed
diagnosis (which involves results from
specific medical tests) should provoke an
immediate and vigorous response.
Exarrples
Legionnaire's disease
(Note: If you suspect Legionnaire's
disease, call the local public health
department, check for obvious problem
sites, and take corrective action. There is
no way to be certain that a single case of
this disease is associated with building
occupancy; therefore, public health
agencies usually do not investigate single
cases. Watch for new cases.)
Hypersensitivity pneumonitis
(Note: Affected occupant(s) should be
removed and may not be able to return
unless the causative agent is removed from
the affected person's environment.)
Solutions
Work with public health authorities
evacuation may be recommended or
required
Remove source
drain, clean, and decontaminate drip
pans, cooling towers, room unit air
conditioners, humidifiers, dehumidifiers,
and other habitats of Legionella, fungi,
and other organisms using appropriate
protective equipment
install drip pans that drain properly
provide access to all the items that must
be cleaned, drained, or replaced periodi-
cally
modify schedule and procedures for
improved maintenance
Discontinue processes that deposit
potentially contaminated moisture in air
distribution system
air washing
humidification
cease nighttime shutdown of air handlers
This air intake is located
between the cooling towers.
If the water in the cooling
towers becomes
contaminated with Legionella,
there is potential for
Legionnaire's disease in the
building.
Mitigating IA Q Problems 101
-------
The most eoonorrical
and successful
solutions to IAQ
|3raUoii% arc those
in vtf-ich the operat-
ing principle of the
strategy
tand is
suted to the prob-
lem
JUDGING PROPOSED
MTIGATICN DESIGNS
AND THEIR SUCESS
Mitigation efforts should be evaluated at
the planning stage by considering the
following criteria:
permanence
operating principle
degree to which the strategy fits the job
ability to institutionalize the solution
durability
installation and operating costs
conformity with codes
Mitigation efforts that create permanent
solutions to indoor air problems are clearly
superior to those that provide temporary
solutions (unless the problems are also
temporary). Opening windows or running
air handlers on full outdoor air may be
suitable mitigation strategies for a tempo-
rary problem such as outgassing of volatile
compounds from new furnishings, but
would not be good ways to deal with
emissions from a print shop. A permanent
solution to microbiological contamination
involves not only cleaning and disinfec-
tion, but also modification of the environ-
ment to prevent regrowth.
Operating Principle
The most economical and successful
solutions to IAQ problems are those in
which the operating principle of the
correction strategy makes sense and is
suited to the problem. If a specific point
source of contaminants has been identified,
treatment at the source (e.g., by removal,
sealing, or local exhaust) is almost always
a more appropriate correction strategy than
dilution of the contaminant by increased
general ventilation. If the IAQ problem is
caused by the introduction of outdoor air
that contains contaminants, increased
general ventilation will only make the
situation worse (unless the outdoor air is
cleaned).
Degree to V\Nch tti
Fits the Job
Strategy
It is important to make sure that you
understand the IAQ problem well enough
to select a correction strategy whose size
and scope fit the job. If odors from a
special use area such as a kitchen are
causing complaints in a nearby office,
increasing the ventilation rate in the office
may not be a successful approach. The
mitigation strategy should address the
entire area affected.
If mechanical equipment is needed to
correct the IAQ problem, it must be
powerful enough to accomplish the task.
For example, a local exhaust system
should be strong enough and close enough
to the source so that none of the contami-
nant is drawn into nearby returns and
recirculated.
Ability to Institutionalize
the Solution
A mitigation strategy will be most success-
ful when it is institutionalized as part of
normal building operations. Solutions that
do not require exotic equipment are more
likely to be successful in the long run than
approaches that involve unfamiliar
concepts or delicately maintained systems.
If maintenance or housekeeping proce-
dures or supplies must change as part of
the mitigation, it may be necessary to plan
for additional staff training, new inspection
checklists, or modified purchasing prac-
tices. Operating schedules for HVAC
equipment may also require modification.
Durability
IAQ mitigation strategies that are durable
and low-maintenance are more attractive to
owners and building staff than approaches
that require frequent adjustment or
102 Section?
-------
specialized maintenance skills. New items
of equipment should be quiet, energy-
efficient, and durable, so that the operators
are encouraged to keep them running.
Installation and Operating
Oasts
The approach with the lowest initial cost
may not be the least expensive over the
long run. Other economic considerations
include: energy costs for equipment opera-
tion, increased staff time for maintenance;
differential cost of alternative materials
and supplies; and higher hourly rates if
odor-producing activities (e.g., cleaning)
must be scheduled for unoccupied periods.
Although these costs will almost certainly
be less than the cost of letting the problem
continue, they are more readily identifi-
able, so an appropriate presentation to
management may be required.
Cofformty with Codes
Any modification to building components
or mechanical systems should be designed
and installed in keeping with applicable
fire, electrical, and other building codes.
Judging the Success of a
Mtigation Effort
Two kinds of criteria can be used to judge
the success of an effort to correct an indoor
air problem:
reduced complaints
measurement of properties of the indoor
air (often only of limited usefulness)
Reduction or elimination of complaints
appears to be a clear indication of success,
but that is not necessarily the case.
Occupants who see that their concerns are
being heard may temporarily stop report-
ing discomfort or health symptoms, even if
the actual cause of their complaints has not
been addressed. Lingering complaints may
also continue after successful mitigation if
people have become upset over the
IVBNAGING MTIGATION PROJECTS
INVOLVING SEVERE CONTAM NATION
Elements
Cautions
Identify the extent of contami-
nation
Locating the original source of a chemi-
cal release or microbiological growth
may only be the tip of the iceberg.
Pollutants often tend to migrate through
a building and collect in "sinks", from
which they can be resuspended into the
air. For example, particles accumulate
on horizontal surfaces that are not
subject to regular housekeeping; odors
may adsorb (stick) to porous materials.
Detailed surface and/or bulk sampling
may be needed to locate such "second-
ary" sources in order to solve an air
quality problem.
Develop a precise scope of
work specifying exactly how
remediation will be performed
Depending on the problem, a detailed
knowledge of chemistry, microbiology,
building science, and health and safety
may be required.
Monitor remediation to ensure
work practices are followed
Include air sampling along with regular
inspections if needed. Decontamination
of areas within an occupied building is
especially critical.
Conduct clearance
sampling
In the event of severe contamination,
representative air samples should be
collected to ensure that key indicators
have returned to background levels and
that the space can be safely reoccupied.
Many routine IAQ problems can be
corrected by a common sense approach
not requiring special expertise. However,
when complex exposure or contamination
issues are involved, more detailed techni-
cal assistance may be needed for success-
ful remediation. Efforts such as those
outlined above are sometimes needed to
deal with severe contamination.
Mitigating IAQ Problems 103
-------
I f you haue made
several LTBuooessftl
offo'ts tocxji Aid a
praUoii^ tlicn it may
be advisable to seek
outside assistance.
handling of the problem. Ongoing (but
reduced) complaints could also indicate
that there were multiple IAQ problems and
that one or more problems are still unre-
solved.
However, it can be very difficult to use
measurements of contaminant levels as a
means of determining whether air quality
has improved. Concentrations of indoor
air pollutants typically vary greatly over
time; further, the specific contaminant
measured may not be causing the problem.
If air samples are taken, readings taken
before and after mitigation should be
interpreted cautiously. It is important to
keep the "before" and "after" conditions as
identical as possible, except for the
operation of the control strategy. For
example, the same HVAC operation,
building occupancy and climatic condi-
tions should apply during both measure-
ment periods. "Worst-case" conditions
identified during the investigation should
be used.
Measurements of airflows, ventilation
rates, and air distribution patterns are the
more reliable methods of assessing the
results of control efforts. Airflow mea-
surements taken during the building
investigation can identify areas with poor
ventilation; later they can be used to
evaluate attempts to improve the ventila-
tion rate, distribution, or direction of flow.
Studying air distribution patterns will show
whether a mitigation strategy has success-
fully prevented a contaminant from being
transported by airflow.
Persistent Problem*
Solving an indoor air quality problem is a
cyclical process of data collection and
hypothesis testing. Deeper and more
detailed investigation is needed to suggest
new hypotheses after any unsuccessful or
partially-successful control attempt.
Even the best-planned investigations
and mitigation actions may not produce a
resolution to the problem. You may have
made a careful investigation, found one or
more apparent causes for the problem, and
implemented a control system. Nonethe-
less, your correction strategy may not have
caused a noticeable reduction in the
concentration of the contaminant or
improvement in ventilation rates or
efficiency. Worse, the complaints may
persist even though you have been
successful at improving ventilation and
controlling all of the contaminants you
could identify. When you have pursued
source control options and have increased
ventilation rates and efficiency to the limits
of your expertise, you must decide how
important it is to pursue the problem
further.
If you have made several unsuccessful
efforts to control a problem, then it may be
advisable to seek outside assistance. The
problem is probably fairly complex, and it
may occur only intermittently or cross the
borders that divide traditional fields of
knowledge. It is even possible that poor
indoor air quality is not the actual cause of
the complaints. Bringing in a new
perspective at this point can be very
effective.
The next section provides guidance on
hiring professional indoor air quality
assistance. An interdisciplinary team (such
as people with engineering and medical or
health backgrounds) may be needed to
solve particularly difficult problems.
104 Section 7
-------
IVI
ly IAQ problems are simple to
resolve when facility staff have been
educated about the investigation process.
In other cases, however, a time comes
when outside assistance is needed. Profes-
sional help might be necessary or desirable
in the following situations, among others:
Mistakes or delays could have serious
consequences (e.g., health hazards, li-
ability exposure, regulatory sanctions).
Building management feels that an inde-
pendent investigation would be better
received or more effectively documented
than an in-house investigation.
Investigation and mitigation efforts by
facility staff have not relieved the
IAQ problem.
Preliminary findings by staff suggest the
need for measurements that require
specialized equipment and training
beyond in-house capabilities.
You may be able to find help by
looking in the yellow pages of your
telephone book (e.g., under "Engineers,"
"Environmental Services," "Laboratories -
Testing," or "Industrial Hygienists").
Local or State health or air pollution
agencies may have lists of firm offering
IAQ services in your area. It may also be
useful to seek out referrals from other
building management firms.
Local, State, or Federal government
agencies may be able to provide expert
assistance or direction in solving IAQ
problems. It is particularly important to
contact your local or State Health
Department if you suspect that you have a
serious building-related illness potentially
linked to biological contamination in your
building.
If available government agencies do not
have personnel with the appropriate skills
to assist in solving your IAQ problem, they
may be able to direct you to firms in your
area with experience in indoor air quality
work. Note that even certified profession-
als from disciplines closely related to IAQ
issues (such as industrial hygienists,
ventilation engineers, and toxicologists)
may not have the specific expertise needed
to investigate and resolve indoor air
problems. Individuals or groups that offer
services in this evolving field should be
questioned closely about their related
experience and their proposed approach to
your problem.
As with any hiring process, the better
you know your own needs, the easier it
will be to select a firm or individual to
service those needs. Firms and individuals
working in IAQ may come from a variety
of disciplines. Typically, the skills of
HVAC engineers and industrial hygienists
are useful for this type of investigation,
although input from other disciplines such
as chemistry, chemical engineering, archi-
tecture, microbiology, or medicine may
also be important. If problems other than
indoor air quality are involved, experts in
lighting, acoustic design, interior design,
psychology, or other fields may be helpful
in resolving occupant complaints about the
indoor environment.
IVBKE SURE THAT THEIR
APPROACH FITS YOUR IXEEDS
As you prepare to hire professional ser-
vices in the area of indoor air quality, be
aware it is a developing area of knowledge.
Most consultants working in the field re-
ceived their primary training in other areas.
A variety of investigative methods may be
employed, many of which are ineffective
for resolving any but the most obvious
As you prepare to
hire professional
of indoor air quality,
be auuare that it is a
cleuelopii ioj oraa of
knowledge.
Hiring Professional Assistance to Solve an IAQ Problem 105
-------
Diagnostic outaoncs
to auoid include an
evaluation that <
errphasize
pollutants and a
report that links all
the bulking to the
problem vuthcut
idering their
vuthth
rplainls.
situations. Inappropriately designed studies
may lead to conclusions that are either
false negative (e.g., falsely concludes that
there is no problem associated with the
building) or false positive (e.g., incorrectly
attributes the cause to building conditions).
Diagnostic outcomes to avoid include:
an evaluation that overemphasizes
measuring concentrations of pollutants
and comparing those concentrations to
numerical standards, and
a report that lists a series of major and
minor building deficiencies and links all
the deficiencies to the problem without
considering their actual association with
the complaints.
Considerable care should be exercised
when interviewing potential consultants to
avoid those subscribing to these strategies.
A qualified IAQ investigator should have
appropriate experience, demonstrate a
broad understanding of indoor air quality
problems and the conditions which can
lead to them, and use a phased diagnostic
approach.
SELECTION CRITERIA
Most of the criteria used in selecting a
professional to provide indoor air quality
services are similar to those used for other
professionals:
company experience in solving similar
problems, including training and experi-
ence of the individuals who would be
responsible for the work
quality of interview and proposal
company reputation
knowledge of local codes and regional
climate conditions
cost
An EPA survey of firms providing IAQ
services found that almost half had been
providing IAQ diagnostic or mitigation
services in non-industrial settings for ten or
fewer years.
Ask how much IAQ work and what type
of IAQ work the firm has done.
Have the firm identify the personnel who
would be responsible for your case, their
specific experience, and related qualifi-
cations. Contract only for the services of
those individuals, or require approval for
substitutions.
Quality of Interview and
Several guidelines may be of assistance in
hiring IAQ professionals.
1. Competent professionals will ask
questions about your situation to see
whether they feel they can offer services
that will assist you.
The causes and potential remedies for
indoor air quality problems vary greatly.
A firm needs at least a preliminary
understanding of the facts about what is
going on in your building to evaluate if it
has access to the professional skills
necessary to address your concerns and to
make effective use of its personnel from
the outset. Often a multi-disciplinary team
of professionals is needed.
2. The proposal for the investigation
should emphasize observations rather
than measurements.
Section 6 describes the four types of
information that may need to be gathered
in an investigation in order to resolve an
indoor air quality problem: the occupant
complaints, the HVAC system, pollutant
pathways, and pollutant sources. There is
also a discussion of the role of monitoring
106 Sections
-------
within an investigation. Non-routine
measurements (such as relatively expen-
sive sampling for VOCs) should not be
provided without site-specific justification.
3. The staff responsible for building in-
vestigation should have a good under-
standing of the relationship between IAQ
and the building structure, mechanical
systems, and human activities.
For example, lack of adequate ventila-
tion is at least a contributing factor in
many indoor air quality problem situations.
Evaluating the performance of the ventila-
tion system depends on understanding the
interaction between the mechanical system
and the human activity within the building.
In some cases building investigators
may have accumulated a breadth of
knowledge. For example, a mechanical
engineer and an industrial hygienist see
buildings differently. However, a me-
chanical engineer with several years of
experience in IAQ problem investigations
may have seen enough health-related
problems to cross the gap; likewise, an
industrial hygienist with years of experi-
ence studying problems in an office setting
may have considerable expertise in HVAC
and other building mechanical systems.
Either in the proposal or in discussion,
the consultant should:
Describe the goal(s), methodology, and
sequence of the investigation, the
information to be obtained, and the
process of hypothesis development and
testing, including criteria for decision-
making about further data-gathering.
The proposal should include an explana-
tion of the need for any proposed
measurements. The goal is to reach a
successful resolution of the complaints,
not simply to generate data.
Identify any elements of the work that
will require a time commitment from the
client's own staff, including information
to be collected by the client.
Identify additional tasks (and costs)
which are part of solving the IAQ
problem but are outside the scope of the
contract. Examples might include
medical examination of complainants,
laboratory fees, and contractor's fees for
mitigation work.
Describe the schedule, cost, and work
product(s), such as a written report,
specifications, and plans for mitigation
work; supervision of mitigation work;
and training program for building staff.
Discuss communication between the
IAQ professional and the client: How
often will the contractor discuss the
progress of the work with the client?
Who will be notified of test results and
other data? Will communications be in
writing, by telephone, or face-to-face?
Will the consultant meet with building
occupants to collect information? Will
the consultant meet with occupants to
discuss findings if requested to do so?
Reputation
There are no Federal regulations covering
professional services in the general field of
indoor air quality, although some disci-
plines (e.g., engineers, industrial hygien-
ists) whose practitioners work with IAQ
problems have licensing and certification
requirements.
Building owners and managers who
suspect that they may have a problem with
a specific pollutant (such as radon, asbes-
tos, or lead) may be able to obtain assis-
tance from local and State Health Depart-
ments. Government agencies and affected
industries have developed training pro-
grams for contractors who diagnose or
mitigate problems with these particular
contaminants.
Firms should be asked to provide refer-
ences from clients who have received
comparable services. In exploring refer-
The goal of the
investigative process
is toreachasuDoess-
fll resolution of the
con-plaints, not
sin-ply to generate
Hiring Professional Assistance to Solve an LAQ Problem 107
-------
ences, it is useful to ask about long-term
follow-up. After the contract was com-
pleted, did the contractor remain in contact
with the client to ensure that problems did
not recur?
Knowledge of Local Codes and
Regional Climate Cbnditians
Familiarity with State and local regulations
and codes helps to avoid problems during
mitigation. For example, in making
changes to the HVAC system, it is impor-
tant to conform to local building codes.
Heating, cooling, and humidity control
needs are different in different geographic
regions, and can affect the selection of an
appropriate mitigation
approach. Getting assurances that all firms
under consideration have this knowledge
becomes particularly important if it
becomes necessary to seek expertise
from outside the local area.
Cost
It is impossible for this document to give
specific guidance on the cost of profes-
sional services. If projected costs jump
suddenly during the investigation process,
the consultants should be able to justify
that added cost.
The budget will be influenced by a
number of factors, including:
complexity of the problem
size and complexity of the building and
its HVAC system(s)
quality and extent of recordkeeping by
building staff and management
type of report or other product required
number of meetings required (formal
presentations can be quite expensive)
air sampling (e.g., use of instruments,
laboratory analysis) if required
108 Sections
-------
Building Air Quality
linn
mill
HUH
Printed on Recycled Paper
-------
Appendix A:
Common IAQ Measurements - A General Guide
I he following is a brief introduction to
making measurements that might be
needed in the course of developing an IAQ
profile or investigating an IAQ complaint.
Emphasis has been placed on the param-
eters most commonly of interest in non-
research studies, highlighting the more
practical methods and noting some
inappropriate tests to avoid. Most of the
instruments discussed in this section are
relatively inexpensive and readily available
from many local safety supply companies.
Consult the guidance in Section 6 on pages
72-73 before determining whether to
proceed with air sampling.
OVERVIEW OF SAMPLING DEVICES
Air contaminants of concern in IAQ can be
measured by one or more of the following
methods:
Vacuum Pump:
A vacuum pump with a known airflow rate
draws air through collection devices, such
as a filter (catches airborne particles), a
sorbent tube (which attracts certain
chemical vapors to a powder such as
carbon), or an impinger (bubbles the
contaminants through solution in a test
tube). Tests originated for industrial
environments typically need to be adjusted
to a lower detection limit for IAQ work.
Labs can be asked to report when trace
levels of an identifiable contaminant are
present below the limit of quantification
and detection.
In adapting an industrial hygiene
sorbent tube sampling method for IAQ, the
investigator must consider at least two
important questions. First: are the
emissions to be measured from a product's
end use the same as those of concern
SELECTING MEASUREMENT DEVICES
The growing interest in indoor air quality is stimulating the development of
instruments for IAQ research and building investigations. As you evaluate
the available measurement devices, it may be helpful to consider the
following criteria:
Ease of use
portability
direct-reading vs. analysis required
ruggedness
time required for each measurement
Quality assurance
availability of service and customer support
maintenance and calibration requirements
Output
time-averaged vs. instantaneous readings
sensitivity
compatibility with computer or data logging accessories
Cost
single use only vs. reusable
purchase vs. rental
during manufacturing? Second: is it
necessary to increase the air volume
sampled? Such an increase may be needed
to detect the presence of contaminants at
the low concentrations usually found in
non-industrial settings. For example, an
investigator might have to increase
sampling time from 30 minutes to 5 hours
in order to detect a substance at the low
concentrations found during IAQ investi-
gations. In cases where standard sampling
methods are changed, qualified industrial
hygienists and chemists should be con-
sulted to ensure that accuracy and preci-
sion remain acceptable.
Direct-reading Meter:
Direct-reading meters estimate air concen-
trations through one of several detection
principles. These may report specific
Common IAQ Measurements A General Guide 109
-------
Above: A smoke tube, which is one type of
chemical smoke device. Used to observe
patterns of air movement and the direction
(negative or positive) of pressure differ-
ences. Below: A microman-ometer. Used
for measuring pressure differentials to learn
about airflow. Provides quantitative data,
as compared to the qualitative information
provided by chemical smoke.
chemicals (e.g., CO2 by infrared light),
chemical groups (e.g., certain volatile or-
ganics by photoionization potential) or
broad pollutant categories (e.g., all respi-
rable particles by scattered light). Detec-
tion limits and averaging time developed
for industrial use may or may not be appro-
priate for IAQ.
Detector tube kit:
Detector tube kits generally include a hand
pump that draws a known volume of air
through a chemically treated tube intended
to react with certain contaminants. The
length of color stain resulting in the tube
correlates to chemical concentration.
Personal monitoring devices:
Personal monitoring devices (sometimes
referred to as "dosimeters") are carried or
worn by individuals and are used to mea-
sure that individual's exposure to particular
chemical(s). Devices that include a pump
are called "active" monitors; devices that
do not include a pump are called "passive"
monitors. Such devices are currently used
for research purposes. It is possible that
sometime in the future they may also be
helpful in IAQ investigations in public and
commercial buildings.
SIMPLE VENTILATION/COMFORT
INDICATIONS
Thermal Comfort: Temperature and
Relative Humidity
The sense of thermal comfort (or discom-
fort) results from an interaction between
temperature, relative humidity, air move-
ment, clothing, activity level, and indi-
vidual physiology. Temperature and
relative humidity measurements are
indicators of thermal comfort.
Methodology
Measurements can be made with a simple
thermometer and sling psychrometer or
with electronic sensors (e.g., a thermo-
hygrometer). Accuracy of within + or - 1°F
is recommended for temperature measure-
110 Appendix A
-------
ments. For each measurement, time should
be allowed for the reading to stabilize to
room conditions. Refer to the specifica-
tions for the measuring device; some take
several minutes to stabilize. Electronic
relative humidity (RH) meters must be
calibrated frequently.
Indoor relative humidity is influenced
by outdoor conditions. A single indoor
measurement may not be a good indication
of long-term relative humidity in the build-
ing. Programmable recording sensors can
be used to gain an understanding of tem-
perature or humidity conditions as they
change overtime.
Using the Results
Temperature and humidity directly affect
thermal comfort. They may also provide
indirect indications of HVAC condition
and the potential for airborne contamina-
tion from biological or organic com-
pounds. There is considerable debate
among researchers, IAQ professionals, and
health professionals concerning recom-
mended levels of relative humidity; how-
ever, the humidity levels recommended by
different organizations generally range
between 30% and 60% RH.
Comparison of indoor and outdoor
temperature and humidity readings taken
during complaint periods can indicate
whether thermal discomfort might be due
to extreme conditions beyond the design
capacity of HVAC equipment or the build-
ing envelope.
Measure next to thermostats to confirm
calibration. Measure at the location of
complaints to evaluate whether or not
temperature and humidity at that location
are within the comfort zone (see Figure 6-2
on page 57).
Readings that show large variations
within the space may indicate a room air
distribution or mixing problem. Readings
that are highly variable over time may
indicate control or balance problems with
the HVAC systems.
Tracking Air Movement with
Chemical Smoke
Chemical smoke can be helpful in evaluat-
ing HVAC systems, tracking potential
contaminant movement, and identifying
pressure differentials. Chemical smoke
moves from areas of higher pressure to
areas of lower pressure if there is an
opening between them (e.g., door, utility
penetration). Because it is heatless,
chemical smoke is extremely sensitive to
air currents. Investigators can learn about
airflow patterns by observing the direction
and speed of smoke movement. Puffs of
smoke released at the shell of the building
(by doors, windows, or gaps) will indicate
whether the HVAC systems are maintain-
ing interior spaces under positive pressure
relative to the outdoors.
Methodology
Chemical smoke is available with various
dispensing mechanisms, including smoke
"bottles," "guns," "pencils," or "tubes."
The dispensers allow smoke to be released
in controlled quantities and directed at
specific locations. It is often more
informative to use a number of small puffs
of smoke as you move along an air
pathway rather than releasing a large
A psychrometer. Used to
measure dry bulb and wet
bulb temperatures and to
determine relative humidity
based upon a psychometric
chart. The NIOSH protocol
for indoor air investigations
always includes measurement
of indoor and outdoor relative
humidity. There are two
types of psychrometers: aspi-
rated (with a fan) or sling
(without a fan).
Common IAQ Measurements A General Guide 111
-------
amount in a single puff. (Note: Avoid
direct inhalation of chemical smoke,
because it can be irritating. Do not release
smoke directly on smoke detectors.)
Using the Results
Smoke released mid-room: Observation
of a few puffs of smoke released in mid-
room or mid-cubicle can help to visualize
air circulation within the space. Dispersal
of smoke in several seconds suggests good
air circulation, while smoke that stays
essentially still for several seconds
suggests poor circulation. Poor air
circulation may contribute to sick building
syndrome complaints or may contribute to
comfort complaints even if there is
sufficient overall air exchange.
Smoke released near diffusers, grilles:
Puffs of smoke released by HVAC vents
give a general idea of airflow. (Is it in or
out? Vigorous? Sluggish? No flow?)
This is helpful in evaluating the supply and
return system and determining whether
ventilation air actually reaches the breath-
ing zone. (For a variable air volume
system, be sure to take into account how
the system is designed to modulate. It
could be on during the test, but off for
much of the rest of the day.) "Short-
circuiting" occurs when air moves
relatively directly from supply diffusers to
return grilles, instead of mixing with room
air in the breathing zone. When a substan-
tial amount of air short-circuits, occupants
may not receive adequate supplies of
outdoor air and source emissions may not
be diluted sufficiently.
Carbon Dioxide (CO2) as an
Indicator of Ventilation
CO2 is a normal constituent of the atmo-
sphere. Exhaled breath from building
occupants is an important indoor CO2
source. Indoor CO2 concentrations can,
under some test conditions, provide a good
indication of the adequacy of ventilation.
Comparison of peak CO2 readings between
rooms, between air handler zones, and at
varying heights above the floor, may help
to identify and diagnose various building
ventilation deficiencies.
Methodology
CO2 can be measured with either a direct-
reading meter or a detector tube kit. The
relative occupancy, air damper settings,
and weather should be noted for each
period of CO2 testing.
CO2 measurements for ventilation
should be collected away from any source
that could directly influence the reading
(e.g., hold the sampling device away from
exhaled breath). Individual measurements
should be short-term. As with many other
measurements of indoor air conditions, it is
advisable to take one or more readings in
"control" locations to serve as baselines for
comparison. Readings from outdoors and
from areas in which there are no apparent
IAQ problems are frequently used as
controls. Outdoor samples should be taken
near the outdoor air intake.
Measurements taken to evaluate the
adequacy of ventilation should be made
when concentrations are expected to peak.
It may be helpful to compare measure-
ments taken at different times of day. If
the occupant population is fairly stable
during normal business hours, CO2 levels
will typically rise during the morning, fall
during the lunch period, then rise again,
reaching a peak in mid-afternoon. In this
case, sampling in the mid- to late-after-
noon is recommended. Other sampling
times may be necessary for different
occupancy schedules.
Using the Results
Peak CO2 concentrations above 1000 ppm
in the breathing zone indicate ventilation
problems. Carbon dioxide concentrations
below 1000 ppm generally indicate that
ventilation is adequate to deal with the
routine products of human occupancy.
112 Appendix A
-------
However, there are several reasons not to
conclude too quickly that a low CO2
reading means no IAQ problem exists.
Problems can occur in buildings in which
measured CO2 concentrations are below
1000 ppm. Although CO2 readings
indicate good ventilation, for example, if
strong contaminant sources are present,
some sort of source control may be needed
to prevent IAQ problems. Errors in
measurement and varying CO2 concentra-
tions over time can also cause low readings
that may be misleading.
Elevated CO2 may be due to various
causes alone or in combination, such as:
increased occupant population, air ex-
change rates below ASHRAE guidelines,
poor air distribution, and poor air mixing.
A higher average CO2 concentration in the
general breathing zone (at least two feet
from exhaled breath) than in the air
entering return grilles is an indication of
poor air mixing. Smoke tubes and
temperature profiles will help to clarify air
circulation patterns.
If CO2 measurements taken before the
occupied period begins are higher than
outdoor readings taken at the same time,
there may be an operating problem with
the HVAC system. Potential problems
include the following:
ventilation terminated too early the
evening before (as compared with the
occupancy load on the space)
combustion by-products from a nearby
roadway or parking garage are drawn
into the building
a gas-fired heating appliance in the
building has a cracked heat exchanger
Outdoor CO2 concentrations above 400
ppm may indicate an outdoor contamina-
tion problem from traffic or other combus-
tion sources. Note, however, that detector
tubes cannot provide accurate measure-
ments of CO2 in hot or cold weather.
Measuring Airflow
Measurements of airflow allow investiga-
tors to estimate the amount of outdoor air
that is entering the building and to evaluate
HVAC system operation. The most
appropriate measurement technique
depends on the characteristics of the
measurement location.
Methodology
Airflow quantities can be calculated by
measuring the velocity and cross-sectional
area of the airstream. For example, if air is
moving at 100 feet per minute in a 24" x
A flow hood. Used to
measure the total air flow
(outdoor plus recirculated air)
from a diffuser.
Common IAQ Measurements A General Guide 113
-------
A vacuum pump with
attachments for sampling
with a filter, a sorbent tube,
and an impinger. Use in a
non-industrial setting may
require a larger volume of air.
Consult with qualified
industrial hygienists and
chemists if adapting sampling
methods.
12" duct, the airflow is:
100 feet/minute x 2 square feet duct area
= 200 cubic feet/minute
Air velocity can be measured with a pitot
tube or anemometer. Air velocity within
an airstream is likely to vary considerably.
For example, it is extremely difficult to
measure air velocity at supply diffusers
because of turbulence around the mixing
vanes. The best estimates of air velocity
can be achieved by averaging the results of
a number of measurements. ASTM
Standard Practice D 3154 provides
guidance on making such measurements.
This method is available from ASTM.
(See Appendix G for ASTM's address and
phone number.) The cross-sectional area
of the airstream is sometimes easy to
calculate (e.g., in a straight run of rectan-
gular ductwork), but can be very compli-
cated at other locations such as mixing
boxes or diffusers.
Flow hoods can be used for direct
measurement of airflows at locations such
as grilles, diffusers, and exhaust outlets.
They are not designed for use in ductwork.
Using the Results
Airflow measurements can be used to
determine whether the HVAC system is
operating according to design and to
identify potential problem locations.
Building investigations often include
measurements of outdoor air quantities,
exhaust air quantities, and airflows at
supply diffusers and return grilles.
Estimating Outdoor Air Quantities
Outdoor air quantities can be evaluated by
measuring airflow directly. Investigators
often estimate the proportion of outdoor air
quantities using techniques such as thermal
mass balance (temperature) or CO2
measurements. Estimation of outdoor air
quantity using temperature measurements
is referred to as "thermal balance" or
sometimes "thermal mass balance."
Thermal Balance: Methodology
Use of this test requires the following
conditions:
1. Airstreams representing return air,
outdoor air, and mixed air (supply air
before it has been heated or cooled) are
accessible for separate measurement.
Some systems are already equipped with
an averaging thermometer that is strung
diagonally across the mixed air chamber;
the temperature is read out continuously on
an instrument panel. Some panels read out
supply, return, outdoor, and/or mixed air
temperature.
2. There is at least a several degree
temperature difference between the
building interior and the outdoor air.
3. Total air flow in the air handling system
can be estimated either by using recent
balancing reports or pitot tube measure-
ments in ductwork. As an alternative, the
supply air at each diffuser can be estimated
(e.g., using a flow measuring hood), and
the results can be summed to calculate
total system air flow.
Temperature measurements can be made
with a simple thermometer or an electronic
sensor. Several measurements should be
taken across each airstream and averaged.
114 Appendix A
-------
It is generally easy to obtain a good tem-
perature reading in the outdoor air and
return airstreams. To obtain a good aver-
age temperature reading of the mixed air-
stream, a large number of measurements
must be taken upstream of the point at
which the airstream is heated or cooled.
This may be difficult or impossible in
some systems.
The percentage or quantity of outdoor air
is calculated using thermal measurements
as shown to the right.
Methodology: Carbon Dioxide
Measurements
CO2 readings can be taken at supply outlets
or air handlers to estimate the percentage
of outdoor air in the supply airstream. The
percentage or quantity of outdoor air is cal-
culated using CO2 measurements as shown
to the right.
Using the Results
The results of this calculation can be
compared to the building design specifica-
tions, applicable building codes, or
ventilation recommendations such as
ASHRAE 62-1989 (see page 136 in
Appendix B) to see whether under-
ventilation appears to be a problem.
AIR CONTAMINANT
CONCENTRATIONS
Volatile Organic Compounds (VOCs)
Hundreds of organic (carbon-containing)
chemicals are found in indoor air at trace
levels. VOCs may present an IAQ
problem when individual organics or
mixtures exceed normal background
concentrations.
Methodology: Total Volatile Organic
Compounds (TVOCs)
Several direct-reading instruments are
ESTIMATING OUTDOOR AIR QUANTITIES
Using Thermal Mass Balance
Outdoor air (percent) =
return air - mixed air
return air - outdoor air
x100
Where: T = temperature (degrees Farenheit)
Using Carbon Dioxide Measurements
Outdoor air (%) = s' R x 100
Where: Cs = ppm CO2 in the supply air (if measured in a room), or
Cs = ppm of CO2 in the mixed air (if measured at an air
handler)
CR = ppm of CO2 in the return air
C0 = ppm of C02 in the outdoor air
(All these concentrations must be measured, not assumed.)
Converting Percent To CFM
Outdoor air (in cfm) =
Where: cfm = cubic feet per minute
Outdoor air (percent) t , r, / t *
x total airflow (cfm)
100
The number used for total airflow may be the air quantity supplied to a
room or zone, the capacity of an air handler, or the total airflow of the
HVAC system. Note: The actual amount of airflow in an air handler is
often different from the quantity in design documents.
available that provide a low sensitivity
"total" reading for different types of
organics. Such estimates are usually
presented in parts per million and are
calculated with the assumption that all
chemicals detected are the same as the one
used to calibrate the instrument. A
photoionization detector is an example of a
direct-reading instrument used as a
screening tool for measuring TVOCs.
A laboratory analysis of a sorbent tube
can provide an estimate of total solvents in
the air. Although methods in this category
report "total volatile organic compounds"
(TVOCs) or "total hydrocarbons" (THC),
Common IAQ Measurements A General Guide 115
-------
analytical techniques differ in their
sensitivity to the different types of organ-
ics. (For discussion of measurement
devices and their sensitivity, see Overview
of Sampling Devices on page 109.)
Using the Results
Different measurement methods are useful
for different purposes, but their results
should generally not be compared to each
other. Direct-reading instruments do not
provide sufficient sensitivity to differenti-
ate normal from problematic mixtures of
organics. However, instantaneous readouts
may help to identify "hot spots," sources,
and pathways. TVOCs or THC deter-
mined from sorbent tubes provide more
accurate average readings, but are unable
to distinguish peak exposures. A direct-
reading instrument can identify peak
exposures if they happen to occur during
the measurement period.
Methodology: Individual Volatile
Organic Compounds (VOCs)
High concentrations of individual volatile
organic compounds (VOCs) may also
cause IAQ problems. Individual VOCs
can be measured in indoor air with a
moderate degree of sensitivity (i.e.,
measurement in parts per million) through
adaptations of existing industrial air
monitoring technology. Examples of
medium sensitivity testing devices include
XAD-4 sorbent tubes (for nicotine),
charcoal tubes (for solvents), and
chromosorb tubes (for pesticides). After a
sufficient volume of air is pumped through
these tubes, they are sent to a lab for
extraction and analysis by gas
chromatography. Variations use a passive
dosimeter (charcoal badge) to collect the
sample or a portable gas chromatograph
onsite for direct injection of building air.
These methods may not be sensitive
enough to detect many trace level organics
present in building air.
High sensitivity techniques have
recently become available to measure
"trace organics" VOCs in the air (i.e.
measurements in parts per billion.)
Sampling may involve Tenax and multiple
sorbent tubes, charcoal tubes, evacuated
canisters, and other technology. Analysis
involves gas chromatography followed by
mass spectroscopy.
Using the Results
Guidelines for public health exposure (as
opposed to occupational exposure) for a
few VOCs are available in the World
Health Organization (WHO) Air Quality
Guidelines for Europe. These guidelines
address noncarcinogenic and carcinogenic
effects. Occupational exposure standards
exist for many other VOCs. No rule-of-
thumb safety factor for applying these
occupational limits to general IAQ is
currently endorsed by EPA and NIOSH.
Measurement of trace organics may
identify the presence of dozens to hundreds
of trace VOCs whose significance is
difficult to determine. It may be helpful to
compare levels in complaint areas to levels
in outdoor air or non-complaint areas.
Formaldehyde
Formaldehyde is a VOC that has been
studied extensively. Small amounts of
formaldehyde are present in most indoor
environments. Itching of the eyes, nose, or
throat may indicate an elevated concentra-
tion. Sampling may be helpful when
relatively new suspect materials are
present.
Methodology
A number of measurement methods are
available. Sensitivity and sampling time
are very important issues in selecting a
method; however, many methods allow
detection of concentrations well below
0.1 ppm (see Using the Results below).
Measurement of short-term peaks (around
a two-hour sample time) is ideal for
116 Appendix A
-------
evaluating acute irritation. Dosimeters
may accurately record long-term exposure
but may miss these peaks.
Two commonly used methods that are
generally acceptable for IAQ screening
involve impingers and sorbent tubes.
Other appropriate methods are also
available.
Using the Results
Various guidelines and standards are
available for formaldehyde exposure.
Several organizations have adopted
0.1 ppm as guidance that provides
reasonable protection against irritational
effects in the normal population.
Hypersensitivity reactions may occur at
lower levels of exposure. Worst-case
conditions are created by minimum
ventilation, maximum temperatures, and
high source loadings.
Biological Contaminants
Human health can be affected by exposure
to both living and non-living biological
contaminants. The term "bioaerosols"
describes airborne material that is or was
living, such as mold and bacteria, parts of
living organisms (e.g., insect body parts),
and animal feces.
Testing for biological contaminants
should generally be limited to:
cases where a walkthrough investigation
or human profile study suggests micro-
biological involvement
cases in which no other pollutant or
physical condition can account for
symptoms
Methodology
Inspection of building sanitary conditions
is generally preferred over sampling,
because direct sampling can produce
misleading results. Any sampling should
be accompanied by observations of
sanitary conditions and a determination as
to whether any health problems appear
likely to be related to biological contami-
nation.
No single technique is effective for
sampling the many biological contami-
nants found in indoor environments. A
variety of specific approaches are used to
retrieve, enumerate, and identify each kind
of microorganism from water, surfaces,
and air. Other specific methods are used
for materials such as feces or insect parts.
The utility of these techniques depends
upon their use by professionals who have a
thorough understanding of the sample site
and the target organism.
Where air sampling is desired, several
approaches are available. The most
common type of air sampler uses a pump
to pull air across a nutrient agar, which is
then incubated. Any bacterial or fungal
colonies that subsequently grow can be
counted and identified by a qualified
microbiologist. Different types of agar and
incubation temperatures are used to culture
different types of organisms. Only living
organisms or spores in the air are counted
by this method. Settling plates, which are
simply opened to room air and then
incubated, are sometimes used to identify
which bioaerosols are present in different
locations. The drawbacks to this technique
are that it does not indicate the quantity of
bioaerosols present and that only the
A viable impactor. Used to
sample for biologicals.
Training is required in order
to analyze the results.
Common IAQ Measurements A General Guide 117
-------
High-flow indoor paniculate
sampler. Used to measure
particles 10 microns and
smaller that are readily
inhaled.
bioaerosols that are heavy enough to fall
out onto the agar will be recorded.
Using the Results
Quantities and types of bioaerosols can
vary greatly over time in any given
building, making sampling results difficult
to interpret. Comparison of relative
numbers and types between indoors and
outdoors or between complaint areas and
background sites can help to establish
trends; however, no tolerance levels or
absolute guidelines have been established.
Low bioaerosol results by themselves are
not considered proof that a problem does
not exist, for a variety of reasons:
the sampling and identification tech-
niques used may not be suited to the
type(s) of bioaerosols that are present
biological growth may have been
inactive during the sampling period
the analysis technique used may not
reveal non-living bioaerosols (e.g., feces,
animal parts) that can cause health
reactions
Airborne Dust
Particles and fibers suspended in the air
generally represent a harmless background
but can become a nuisance or cause serious
health problems under some conditions.
Methodology
A variety of collection and analytical
techniques are available. Dust can be
collected by using a pump to draw air
through a filter. The filter can then be
weighed (gravimetric analysis) or exam-
ined under a microscope. Direct readouts
of airborne dust are also available (such as
using meters such as those equipped with a
"scattered light" detector).
Using the Results
IAQ measurements for airborne dust will
be well below occupational and ambient
air guidelines except under the most
extreme conditions. Unusual types or
elevated amounts of particles or fibers can
help identify potential exposure problems.
Combustion Products
Combustion products are released by
motor vehicle exhaust, tobacco smoke, and
other sources, and contain airborne dust
(see the previous section) along with
potentially harmful gases such as carbon
monoxide and nitrogen oxides.
Methodology
Direct-reading meters, detector tubes, and
passive dosimeters are among the tech-
niques most commonly used to measure
carbon monoxide and nitrogen oxides.
Using the Results
Comparison with occupational standards
118 Appendix A
-------
will reveal only whether an imminent
danger exists. Any readings that are
elevated above outdoor concentrations or
background building levels may indicate a
mixture of potentially irritating combustion
products, especially if susceptible indi-
viduals are exposed.
Other Inorganic Gases
Although they are not routinely sampled in
most IAQ studies, a variety of other gases
may be evaluated where conditions
warrant. Examples might include ammo-
nia, ozone, and mercury.
Methodology
EPA, NIOSH, and ASTM references
should be consulted for specific sampling
techniques. Detector tubes or impinger
methods are applicable in some cases.
Using the Results
No generalization can be applied to this
diverse group of substances.
Common IAQ Measurements A General Guide 119
-------
Appendix B:
HVAC Systems and Indoor Air Quality
I his appendix provides information
about specific HVAC system designs and
components in relation to indoor air
quality. It also serves as introductory
material for building owners and managers
who may be unfamiliar with the terminol-
ogy and concepts associated with HVAC
(heating, ventilating, and air conditioning)
system design. Further detailed informa-
tion can be found in ASHRAE manuals
and guides and in some of the guidance
developed by other trade and professional
associations. (See Guidelines of Care
Developed by Trade Associations in
Section 5.) Additional information can be
obtained using Appendix G or through
discussion with your facility engineer.
BACKGROUND
All occupied buildings require a supply of
outdoor air. Depending on outdoor
conditions, the air may need to be heated
or cooled before it is distributed into the
occupied space. As outdoor air is drawn
into the building, indoor air is exhausted or
allowed to escape (passive relief), thus
removing air contaminants.
The term "HVAC system" is used to
refer to the equipment that can provide
heating, cooling, filtered outdoor air, and
humidity control to maintain comfort
conditions in a building. Not all HVAC
systems are designed to accomplish all
of these functions. Some buildings rely
on only natural ventilation. Others lack
mechanical cooling equipment (AC), and
many function with little or no humidity
control. The features of the HVAC system
in a given building will depend on several
variables, including:
age of the design
climate
building codes in effect at the time of
the design
budget that was available for the project
planned use of the building
owners' and designers' individual
preferences
subsequent modifications
HVAC systems range in complexity
from stand-alone units that serve
individual rooms to large, centrally
controlled systems serving multiple zones
in a building. In large modern office
buildings with heat gains from lighting,
people, and equipment, interior spaces
often require year-round cooling. Rooms
at the perimeter of the same building (i.e.,
rooms with exterior walls, floors, or roof
surfaces) may need to be heated and/or
cooled as hourly or daily outdoor weather
conditions change. In buildings over one
story in height, perimeter areas at the lower
levels also tend to experience the greatest
uncontrolled air infiltration.
Working with the electrical
components of an HVAC
system involves the risk of
electrocution and fire. A
knowledgeable member of
the building staff should
oversee the inspection of the
HVAC controls.
HVAC Systems and Indoor Air Quality 121
-------
Some buildings use only natural
ventilation or exhaust fans to remove odors
and contaminants. In these buildings,
thermal discomfort and unacceptable
indoor air quality are particularly likely
when occupants keep the windows closed
because of extreme hot or cold tempera-
tures. Problems related to underventilation
are also likely when infiltration forces are
weakest (i.e., during the "swing seasons"
and summer months).
Modern public and commercial build-
ings generally use mechanical ventilation
systems to introduce outdoor air during the
occupied mode. Thermal comfort is
commonly maintained by mechanically
distributing conditioned (heated or cooled)
air throughout the building. In some
designs, air systems are supplemented by
piping systems that carry steam or water to
the building perimeter zones. As this
document is concerned with HVAC
systems in relation to indoor air quality,
the remainder of this discussion will focus
on systems that distribute conditioned air
to maintain occupant comfort.
Roles of the HVAC System Operator
and Facility Manager
The system operator(s) and facility
manager(s) (or IAQ manager) are among
the most significant factors in determining
whether IAQ problems will occur in a
properly designed, constructed, and
commissioned HVAC system. HVAC
systems require preventive maintenance and
prompt repairs if they are to operate
correctly and provide comfortable condi-
tions. The operators) must have an
adequate understanding of the overall
system design and its limitations. The
HVAC system capacity and distribution
characteristics should be evaluated before
renovations to the building, changes in its
occupancy, or changes in the use of an area.
System operators must be able to
respond appropriately to occupant com-
plaints. For example, if an occupant
complains that it is too cold or too hot and
the observed (measured) conditions are
outside of the ASHRAE comfort zone,
then the HVAC system needs to be
evaluated. Sometimes the problem can be
relieved by fine tuning or repairing the
HVAC system, but in some cases the
system cannot perform as expected, and a
long-term solution must be investigated.
TYPES OF HVAC SYSTEMS
Single Zone
A single air handling unit can only serve
more than one building area if the areas
served have similar heating, cooling, and
ventilation requirements, or if the control
system compensates for differences in
heating, cooling, and ventilation needs
among the spaces served. Areas regulated
by a common control (e.g., a single
thermostat) are referred to as zones.
Thermal comfort problems can result if the
design does not adequately account for
differences in heating and cooling loads
between rooms that are in the same zone.
This can easily occur if:
The cooling load in some area(s) with-
in a zone changes due to an increased
occupant population, increased lighting,
or the introduction of new heat-produc-
ing equipment (e.g., computers, copiers).
Areas within a zone have different solar
exposures. This can produce radiant heat
gains and losses that, in turn, create
unevenly distributed heating or cooling
needs (e.g., as the sun angle changes
daily and seasonally).
Multiple Zone
Multiple zone systems can provide each
zone with air at a different temperature by
heating or cooling the airstream in each
zone. Alternative design strategies involve
delivering air at a constant temperature
while varying the volume of airflow, or
modulating room temperature with a
122 Appendix B
-------
supplementary system (e.g., perimeter hot
water piping).
Constant Volume
Constant volume systems, as their name
suggests, generally deliver a constant
airflow to each space. Changes in space
temperatures are made by heating or
cooling the air or switching the air han-
dling unit on and off, not by modulating
the volume of air supplied. These systems
often operate with a fixed minimum
percentage of outdoor air or with an "air
economizer" feature (described in the
Outdoor Air Control discussion that
follows).
Variable Air Volume
Variable air volume systems maintain
thermal comfort by varying the amount of
heated or cooled air delivered to each
space, rather than by changing the air
temperature. (However, many VAV
systems also have provisions for resetting
the temperature of the delivery air on a
seasonal basis, depending on the severity
of the weather). Overcooling or
overheating can occur within a given zone
if the system is not adjusted to respond to
the load. Underventilation frequently
occurs if the system is not arranged to
introduce at least a minimum quantity (as
opposed to percentage) of outdoor air as
the VAV system throttles back from full
airflow, or if the system supply air
temperature is set too low for the loads
present in the zone.
BASIC COMPONENTS OF AN HVAC
SYSTEM
The basic components of an HVAC system
that delivers conditioned air to maintain
thermal comfort and indoor air quality are:
outdoor air intake
mixed-air plenum and outdoor air control
air filter
heating and cooling coils
humidification and/or de-humidification
equipment
TESTING AND BALANCING
Modern HVAC systems typically use sophisticated, automatic controls to
supply the proper amounts of air for heating, cooling, and ventilation in
commercial buildings. Problems during installation, operation, mainte-
nance, and servicing the HVAC system could prevent it from operating as
designed. Each system should be tested to ensure its initial and contin-
ued performance. In addition to providing acceptable thermal conditions
and ventilation air, a properly adjusted and balanced system can also
reduce operating costs and increase equipment life.
Testing and balancing involves the testing, adjusting, and balancing of
HVAC system components so that the entire system provides airflows that
are in accordance with the design specifications. Typical components
and system parameters tested include:
all supply, return, exhaust, and outdoor airflow rates
control settings and operation
air temperatures
fan speeds and power consumption
filter or collector resistance
The typical test and balance agency or contractor coordinates with the
control contractor to accomplish three goals: verify and ensure the most
effective system operation within the design specifications, identify and
correct any problems, and ensure the safety of the system.
A test and balance report should provide a complete record of the
design, preliminary measurements, and final test data. The report should
include any discrepancies between the test data and the design specifica-
tions, along with reasons for those discrepancies. To facilitate future
performance checks and adjustments, appropriate records should be kept
on all damper positions, equipment capacities, control types and loca-
tions, control settings and operating logic, airflow rates, static pressures,
fan speeds, and horsepowers.
Testing and balancing of existing building systems should be per-
formed whenever there is reason to believe the system is not functioning
as designed or when current records do not accurately reflect the actual
operation of the system. The Associated Air Balance Council recom-
mends the following guidelines in determining whether testing and
balancing is required:
When space has been renovated or changed to provide for new occu-
pancy.
When HVAC equipment has been replaced or modified.
When control settings have been readjusted by maintenance or other
personnel.
After the air conveyance system has been cleaned.
When accurate records are required to conduct an IAQ investigation.
When the building owner is unable to obtain design documents or
appropriate air exchange rates for compliance with IAQ standards or
guidelines.
Because of the diversity of system types and the interrelationship of
system components, effective balancing requires a skilled technician with
the proper experience and instruments. Due to the nature of the work,
which involves the detection and remediation of problems, it is recom-
mended that an independent test and balance contractor be used and
that this contractor report directly to the building owner, facility manager,
or IAQ manager.
HVA C Systems and Indoor A ir Quality 123
-------
FIGURE B-1: Typical HVAC System Components
Courtesy Terry Brennan
Camroden Associates
Oriskny, N. Y.
supply fan
ducts
terminal device
return air system
exhaust or relief fans and air outlet
self-contained heating or cooling unit
control
boiler
cooling tower
water chiller
The following discussion of these
components (each of which may occur
more than once in any total HVAC system)
emphasizes features that affect indoor air
quality. It may be helpful to refer to this
section when using the HVAC Checklists.
The illustration above shows the
general relationship between many of
these components; however, many
variations are possible.
Outdoor Air Intake
Building codes require the introduction of
outdoor air for ventilation in most build-
ings. Most non-residential air handlers are
designed with an outdoor air intake on the
return side of the ductwork. Outdoor air
introduced through the air handler can be
filtered and conditioned (heated or cooled)
before distribution. Other designs may
introduce outdoor air through air-to-air
heat exchangers and operable windows.
124 Appendix B
-------
Indoor air quality problems can be
produced when contaminants enter a
building with the outdoor air. Rooftop or
wall-mounted air intakes are sometimes
located adjacent to or downwind of
building exhaust outlets or other contami-
nant sources. Problems can also result if
debris (e.g., bird droppings) accumulates at
the intake, obstructing airflow and poten-
tially introducing microbiological contami-
nants.
If more air is exhausted than is
introduced through the outdoor air intake,
then outdoor air will enter the building at
any leakage sites in the shell. Indoor air
quality problems can occur if the leakage
site is a door to a loading dock, parking
garage, or some other area associated with
pollutants.
Mixed-Air Plenum and Outdoor Air
Controls
Outdoor air is mixed with return air (air
that has already circulated through the
HVAC system) in the mixed-air plenum of
an air handling unit. Indoor air quality
problems frequently result if the outdoor
air damper is not operating properly (e.g.,
if the system is not designed or adjusted to
allow the introduction of sufficient outdoor
air for the current use of the building. The
amount of outdoor air introduced in the
occupied mode should be sufficient to
meet needs for ventilation and exhaust
make-up. It may be fixed at a constant
volume or may vary with the outdoor
temperature.
When dampers that regulate the flow of
outdoor air are arranged to modulate, they
are usually designed to bring in a mini-
mum amount of outdoor air (in the
occupied mode) under extreme outdoor
temperature conditions and to open as
outdoor temperatures approach the desired
indoor temperature. Systems that use
outdoor air for cooling are called "air
economizer cooling" systems. Air
economizer systems have a mixed air
Above: The air intake in the background is
located too close to the sanitary vents (the
straight pipes to the left and in the center
foreground) and the bathroom
exhaust vent (next to the sanitary vent on
the right side). Below: The return air
dampers in this mixed-air plenum are open
(top), but the outdoor air damper (left) is al-
most completely closed. Complaints in the
building indicate that
under-ventilation is a problem.
HVA C Systems and Indoor A ir Quality 125
-------
temperature controller and thermostat
that are used to blend return air (typically
at 74°F) with outdoor air to reach a mixed
air temperature of 55° to 65°F. (Mixed air
temperature settings above 65°F may lead
to the introduction of insufficient quanti-
ties of outdoor air for office space use.)
The mixed air is then further heated or
cooled for delivery to the occupied spaces.
Air economizer systems have a sensible
or enthalpy control that signals the outdoor
air damper to go to the minimum position
when it is too warm or humid outdoors.
Note that economizer cycles which do not
provide dehumidification may produce
discomfort even when the indoor tempera-
ture is the same as the thermostat setting.
If outdoor air make-up and exhaust are
balanced, and the zones served by each air
handler are separated and well defined, it is
possible to estimate the minimum flow of
outdoor air to each space and compare it to
ventilation standards such as ASHRAE 62-
1989. Techniques used for this evaluation
include the direct measurement of the
Proper air filtration can play an impor-tant
role in protecting the rest of the HVAC
system and in maintaining good indoor air
quality in occupied spaces. Air filters
should be selected and main-tained to
provide maximum filtration, while not
overtaxing the supply fan capability or
leading to "blowout"situa-tions with no air
filtration. Shown above
are roll filter (top) and bag, panel, and
pleated filters (below).
outdoor air at the intake and the calculation
of the percentage of outdoor air by a
temperature or CO2 balance. Carbon
dioxide measured in an occupied space is
also an indicator of ventilation adequacy.
Some investigators use tracer gases to
assess ventilation quantities and airflow
patterns. There are specific methods for
each of these assessments. See Appendix A
for more information.
Many HVAC designs protect the coils
by closing the outdoor air damper if the
airstream temperature falls below the
setpoint of a freezestat. Inadequate
ventilation can occur if a freezestat trips
and is not reset, or if the freezestat is set to
trip at an excessively high temperature.
Stratification of the cold outdoor air and
warmer return air in the mixing plenums is
a common situation, causing nuisance
tripping of the freezestat. Unfortunately,
the remedy often employed to prevent this
problem is to close the outdoor air damper.
Obviously, solving the problem in this way
can quickly lead to inadequate outdoor air
in occupied parts of the building.
Air Filters
Filters are primarily used to remove
particles from the air. The type and design
of filter determine the efficiency at
removing particles of a given size and the
amount of energy needed to pull or push
air through the filter. Filters are rated by
different standards and test methods such
as dust spot and arrestance which measure
different aspects of performance. See the
discussion of ASHRAE Standard 52-76 on
page 138 of this appendix.
Low efficiency filters (ASHRAE Dust
Spot rating of 10% to 20% or less) are
often used to keep lint and dust from
clogging the heating and cooling coils of a
system. In order to maintain clean air in
occupied spaces, filters must also remove
bacteria, pollens, insects, soot, dust, and
dirt with an efficiency suited to the use of
the building. Medium efficiency filters
(ASHRAE Dust Spot rating of 30% to
126 Appendix B
-------
60%) can provide much better filtration
than low efficiency filters. To maintain the
proper airflow and minimize the amount of
additional energy required to move air
through these higher efficiency filters,
pleated-type extended surface filters are
recommended. In buildings that are
designed to be exceptionally clean, the
designers may specify the equipment to
utilize both a medium efficiency pre-filter
and a high efficiency extended surface
filter (ASHRAE Dust Spot rating of 85%
to 95%). Some manufacturers recommend
high efficiency extended surface filters
(ASHRAE Dust Spot rating of 85%)
without pre-filters as the most cost
effective approach to minimizing energy
consumption and maximizing air quality in
modern HVAC VAV systems that serve
office environments.
Air filters, whatever their design or
efficiency rating, require regular mainte-
nance (cleaning for some and replacement
for most). As a filter loads up with
particles, it becomes more efficient at
particle removal but increases the pressure
drop through the system, therefore
reducing airflow. Filter manufacturers can
provide information on the pressure drop
through their products under different
conditions. Low efficiency filters, if
loaded to excess, will become deformed
and even "blow out" of their filter rack.
When filters blow out, bypassing of
unfiltered air can lead to clogged coils and
dirty ducts. Filtration efficiency can be
seriously reduced if the filter cells are not
properly sealed to prevent air from
bypassing.
Filters should be selected for their
ability to protect both the HVAC system
components and general indoor air quality.
In many buildings, the best choice is a
medium efficiency, pleated filter because
these filters have a higher removal
efficiency than low efficiency filters, yet
they will last without clogging for longer
than high efficiency filters.
Choice of an appropriate filter and
proper maintenance are important to
keeping the ductwork clean. If dirt
accumulates in ductwork and if the relative
humidity reaches the dewpoint (so that
condensation occurs), then the nutrients
and moisture may support the growth of
microbiologicals. Attention to air filters is
particularly important in HVAC systems
with acoustical duct liner, which is
frequently used in air handler fan housings
and supply ducts to reduce sound transmis-
sion and provide thermal insulation. Areas
of duct lining that have become contami-
nated with microbiological growth must be
replaced. (See later discussion of ducts
and duct cleaning .) Sound reduction can
also be accomplished with the use of
special duct-mounted devices such as
attenuators or with active electronic noise
control.
Air handlers that are located in difficult-
to-access places (e.g., in places which
require ladders for access, have inconve-
nient access doors to unbolt, or are located
on roofs with no roof hatch access) will be
Pleated medium efficiency
filters are often preferred over
low efficiency filters because
they offer added protection
to both the HVAC equipment
and to indoor air quality, yet
they do not clog as easily as
high efficiency filters.
Medium efficiency filters do
need routine maintenance,
however, which the filter in
this photo did not receive.
HVA C Systems and Indoor A ir Quality 127
-------
Without proper installation
and maintenance, rust and
corrosion may accumulate in
condensate pans under
heating and cooling coils.
The rust in the pan indi-cates
that it was installed without a
pitch or was pitched in the
wrong direction, so that water
did not drain out properly.
more likely to suffer from poor air filter
maintenance and overall poor mainte-
nance. Quick release and hinged access
doors for maintenance are more desirable
than bolted access panels.
Filters are available to remove gases
and volatile organic contaminants from
ventilation air; however, these systems are
not generally used in normal occupancy
buildings. In specially designed HVAC
systems, permanganate oxidizers and
activated charcoal may be used for gaseous
removal filters. Some manufacturers offer
"partial bypass" carbon filters and carbon
impregnated filters to reduce volatile
organics in the ventilation air of office
environments. Gaseous filters must be
regularly maintained (replaced or regener-
ated) in order for the system to continue to
operate effectively.
Heating and Cooling Coils
Heating and cooling coils are placed in the
airstream to regulate the temperature of the
air delivered to the space. Malfunctions of
the coil controls can result in thermal
discomfort. Condensation on under-
insulated pipes and leakage in piped
systems will often create moist conditions
conducive to the growth of molds, fungus,
and bacteria.
During the cooling mode (air condition-
ing), the cooling coil provides dehumidifi-
cation as water condenses from the air-
stream. Dehumidification can only take
place if the chilled fluid is maintained at a
cold enough temperature (generally below
45°F for water). Condensate collects in the
drain pan under the cooling coil and exits
via a deep seal trap. Standing water will
accumulate if the drain pan system has not
been designed to drain completely under
all operating conditions (sloped toward the
drain and properly trapped). Under these
conditions, molds and bacteria will
proliferate unless the pan is cleaned
frequently.
It is important to verify that condensate
lines have been properly trapped and are
charged with liquid. An improperly
trapped line can be a source of contamina-
tion, depending on where the line termi-
nates. A properly installed trap could also
be a source, if the water in the trap
evaporates and allows air to flow through
the trap into the conditioned air.
During the heating mode, problems can
occur if the hot water temperature in the
heating coil has been set too low in an
attempt to reduce energy consumption. If
enough outdoor air to provide sufficient
ventilation is brought in, that air may not
be heated sufficiently to maintain thermal
comfort or, in order to adequately condi-
tion the outdoor air, the amount of outdoor
air may be reduced so that there is insuffi-
cient outdoor air to meet ventilation needs.
128 Appendix B
-------
Humidification and Dehumidification
Equipment
In some buildings (or zones within
buildings), there are special needs that
warrant the strict control of humidity (e.g.,
operating rooms, computer rooms). This
control is most often accomplished by
adding humidification or dehumidification
equipment and controls. In office facili-
ties, it is generally preferable to keep
relative humidities above 20% or 30%
during the heating season and below 60%
during the cooling season. ASHRAE
Standard 55-1981 provides guidance on
acceptable temperature and humidity
conditions. (See also the discussion of
humidity levels in Section 6.)
The use of a properly designed and
operated air conditioning system will
generally keep relative humidities below
60% RH during the cooling season, in
office facilities with normal densities and
loads. (See the previous discussion of the
cooling coil.)
Office buildings in cool climates that
have high interior heat gains, thermally
efficient envelopes (e.g., insulation), and
economizer cooling may require humidi-
fication to maintain relative humidity
within the comfort zone. When humidi-
fication is needed, it must be added in a
manner that prevents the growth of micro-
biologicals within the ductwork and air
handlers.
Steam humidifiers should utilize clean
steam, rather than treated boiler water, so
that occupants will not be exposed to
chemicals. Systems using media other
than clean steam must be rigorously
maintained in accordance with the
manufacturer's recommended procedures
to reduce the likelihood of microbiological
growth.
Mold growth problems are more likely
if the humidistat setpoint located in the
occupied space is above 45%. The high
limit humidistat, typically located in the
ductwork downstream of the point at
Above: Occupants of this building
complained of an inter-mittant fish tank odor.
An investigation showed that this water spray
humidifi-cation system is regularly
maintained. The coils are washed roughly
every two weeks using fresh tap water,
eliminating the need for any use ofalgacides.
Below: Further investigation identified the
fact that the maintenance practice was
causing the odor problem. This picture of
the downstream side of the coils was taken
one day after the washing. A high pressure
stream of water caused algae in the water
to foam and float for several days,
coinciding with the occupant complaints.
HVA C Systems and Indoor A ir Quality 129
-------
DUCT LEAKAGE
Leakage of air from ducts can cause or exacerbate air quality problems, in
addition to wasting energy. In general, sealed duct systems specified with
a leakage rate of less than 3% will have a superior life cycle cost analysis
and reduce the likelihood of problems associated with leaky ductwork.
Examples of excessive duct leakage leading to problems include:
leakage of light troffer-type diffusers at the diffuser/light fixture interface
when they are installed in a return plenum. Such leakage has been
known to cause gross short-circuiting between supply and return,
wasting much of the conditioned air. If the "room" thermostat is
located in the return plenum, the room can be very uncomfortable while
the temperature in the plenum is operating at the control setpoint.
leakage of supply ductwork due to loose-fitting joints and connections
or "blow outs" of improperly fabricated seams
leakage of return ducts located in crawl spaces or below slabs, allowing
soil gases and molds to enter the ductwork
which water vapor is added, is generally
set at 70% to avoid condensation (with a
potential for subsequent mold growth) in
the ductwork. Adding water vapor to a
building that was not designed for
humidification can have a negative impact
on the building structure and the
occupants' health, if condensation occurs
on cold surfaces or in wall or roof cavities.
Supply Fans
After passing through the coil section
where heat is either added or extracted, air
moves through the supply fan chamber and
the distribution system. Air distribution
systems commonly use ducts that are
constructed to be relatively airtight.
Elements of the building construction can
also serve as part of the air distribution
system (e.g., pressurized supply plenums
or return air plenums located in the cavity
space above the ceiling tiles and below the
deck of the floor above). Proper coordina-
tion of fan selection and duct layout during
the building design and construction phase
and ongoing maintenance of mechanical
components, filters, and controls are all
necessary for effective air delivery.
Fan performance is expressed as the
ability to move a given quantity of air
(cubic feet per minute or cfm) at a given
resistance or static pressure (measured in
inches of water column). Airflow in
ductwork is determined by the size of the
duct opening, the resistance of the duct
configuration, and the velocity of the air
through the duct. The static pressure in a
system is calculated using factors for duct
length, speed of air movement and changes
in the direction of air movement.
It is common to find some differences
between the original design and the final
installation, as ductwork must share
limited space with structural members and
other "hidden" elements of the building
system (e.g., electrical conduit, plumbing
pipes). Air distribution problems can
occur, particularly at the end of duct runs,
if departures from the original design
increase the friction in the system to a
point that approaches the limit of fan
performance. Inappropriate use of long
runs of flexible ducts with sharp bends also
causes excessive friction. Poor system
balancing (adjustment) is another common
cause of air distribution problems.
Dampers are used as controls to
restrict airflow. Damper positions may be
relatively fixed (e.g., set manually during
system testing and balancing) or may
change in response to signals from the
control system. Fire and smoke dampers
can be triggered to respond to indicators
such as high temperatures or signals from
smoke detectors. If a damper is designed
to modulate, it should be checked during
inspections to see that it is at the proper
setting. ASEQIAE and the Associated Air
Balance Council both provide guidance on
proper intervals for testing and balancing.
Ducts
The same HVAC system that distributes
conditioned air throughout a building air
can distribute dust and other pollutants,
including biological contaminants. Dirt or
130 Appendix B
-------
dust accumulation on any components of
an air handling system its cooling coils,
plenums, ducts, and equipment housing
may lead to contamination of the air
supply.
There is widespread agreement that
building owners and managers should take
great precautions to prevent dirt, high
humidity, or moisture from entering the
ductwork; there is less agreement at
present about when measures to clean up
are appropriate or how effective cleaning
techniques are at making long-term
improvements to the air supply or at
reducing occupant complaints.
The presence of dust in ductwork does
not necessarily indicate a current microbio-
logical problem. A small amount of dust
on duct surfaces is normal and to be
expected. Special attention should be
given to trying to find out if ducts are
contaminated only where specific prob-
lems are present, such as: water damage or
biological growth observed in ducts, debris
in ducts that restricts airflow, or dust
discharging from supply diffusers.
Problems with dust and other contami-
nation in the ductwork are a function of
filtration efficiency, regular HVAC system
maintenance, the rate of airflow, and good
housekeeping practices in the occupied
space. Problems with biological pollutants
can be prevented by minimizing dust and
dirt build-up, promptly repairing leaks and
water damage, preventing moisture
accumulation in the components that are
supposed to be dry, and cleaning the
components such as the drip pans that
collect and drain water.
In cases where sheet metal ductwork
has become damaged or water-soaked,
building owners will need to undertake
clean-up or repair procedures. For
example, in cases where the thermal liner
or fiberboard has become water-soaked,
building managers will need to replace the
affected areas. These procedures should
be scheduled and performed in a way that
does not expose building occupants to
increased levels of pollutants and should
be carried out by experienced workers.
Correcting theproblems that allowed the
ductwork to become contaminated in the
first place is important. Otherwise, the
corrective action will only be temporary.
The porous surface of fibrous glass duct
liner presents more surface area (which
can trap dirt and subsequently collect
water) than sheet metal ductwork. It is
therefore particularly important to pay
attention to the proper design, installation,
filtration, humidity, and maintenance of
ducts that contain porous materials. In
addition, techniques developed for
cleaning unlined metal ducts often are not
suitable for use with fibrous glass thermal
liner or fiberboard. Such ducts may
require a special type of cleaning to
maintain the integrity of the duct (i.e., no
heavy brushing tools that might fray the
inner lining) while removing dirt and
debris.
More research on both the efficacy and
the potential for unintended exposures to
building occupants from various cleaning
techniques is needed before firm guidance
can be provided regarding duct cleaning.
Pay attention to worker safety when
working with air handling systems
including during duct cleaning. Any
worker who may potentially breathe duct
contaminants or biocides should wear
suitable protective breathing apparatus.
Workers who are doing the duct cleaning
should be encouraged to also look for
other types of problems, such as holes or
gaps in the ducts that could allow contami-
nants to enter the ventilation airstream.
Building managers can obtain more
information on the issue of HVAC
contamination and cleaning from the
professional standards developed by some
trade associations (See Guidelines of Care
Developed by Professional and Trade
Associations in Section 5 and refer to
Appendix G for a list of organizations
with expertise and materials on these
issues.)
HVAC Systems and Indoor Air Quality 131
-------
PRELIMINARY RECOMMENDATIONS ON DUCT CLEANING
1. Any duct cleaning should be
scheduled during periods when
the building is unoccupied to
prevent exposure to chemicals
and loosened particles.
The air handling unit should not be
used during the cleaning or as an air
movement device for the cleaning
process. The National Air Duct
Cleaning Association recommends
that the system should be run to
allow at least eight air changes in the
occupied space when duct cleaning
has been completed.
2. Negative air pressure that will
draw pollutants to a vacuum
collection system should be
maintained at all times in the
duct cleaning area to prevent
migration of dust dirt, and
contaminants into occupied
areas.
Where possible, use vacuum
equipment or fans during cleaning
and sanitizing to make sure that
cleaning vapors are exhausted to the
outside and do not enter the occu-
pied space.
3. If it is determined that the
ductwork should be cleaned,
careful attention must be given
to protecting the ductwork.
When gaining access to sheet metal
ducts for cleaning purposes, it is
essential to seal the access hole
properly in order to maintain the
integrity of the HVAC system.
Access doors are recommended if
the system is to be cleaned periodi-
cally, and all access holes should be
identified on the building's mechani-
cal plans.
Particular attention is warranted
when cutting fibrous glass ducts, and
manufacturers' recommended
procedures for sealing should be
followed stringently. Use existing
duct system openings where
possible because it is difficult to
repair the damage caused by cutting
new access entries into the
ductwork. Large, high volume
vacuum equipment should only be
used with extreme care because high
negative pressure together with limited
airflow can collapse ducts.
4. Duct cleaning performed with
high velocity airflow (i.e., greater
than 6,000 cfm) should include
gentle, well-controlled brushing of
duct surfaces or other methods to
dislodge dust and other particles.
Duct cleaning that relies only on a high
velocity airflow through the ducts is not
likely to achieve satisfactory results
because the flow rate at the duct
surface remains too low to remove
many particles.
5. Only HEP A filtered (high-
efficiency particle arrestor) vacu-
uming equipment should be used if
the vacuum collection unit is inside
the occupied space.
Conventional vacuuming equipment
may discharge extremely fine panicu-
late matter back into the atmosphere,
rather than collecting it. Duct cleaning
equipment that draws the dust and dirt
into a collection unit outside the
building is also available. People
should not be allowed to remain in the
immediate vicinity of these collection
units.
6. If biocides are to be used, then
select only products registered by
EPA for such use, use the products
according to the manufacturer's
directions, and pay careful atten-
tion to the method of application.
At present, EPA accepts claims and
therefore registers antimicrobials for
use only as sanitizers, not disinfectants
or sterilizers in HVAC systems. (See
Appendix Ffor definitions of antimicro-
bials.) There is some question about
whether there are
any application techniques that
will deposit a sufficient amount of the
biocideto kill bacteria, germs,
or other biologicals that may be
present. Materials such as deodorizers
that temporarily eliminate odors caused
by microorganisms provide only a fresh
smell, and are not intended to provide
real control of microbiological
contaminants.
7. Use of sealants to cover
interior ductwork surfaces is not
recommended.
No application techniques have been
demonstrated to provide a complete
or long-term barrier to microbiological
growth, nor have such materials been
evaluated for their potential health
effects on occupants. In addition,
using sealants alters the surface
burning characteristics of the duct
material and may void the fire safety
rating of the ductwork.
8. Careful cleaning and sanitizing
of any parts of coils and drip pans
can reduce microbiological
pollutants.
Prior to using sanitizers, deodorizers,
or any cleansing agents, carefully
read the directions on the product
label. Once cleaned, these compo-
nents should be thoroughly rinsed
and dried to prevent exposure of
building occupants to the cleaning
chemicals.
9. Water-damaged or contami-
nated porous materials in the
ductwork or other air handling
system components should be
removed and replaced.
Even when such materials are
thoroughly dried, there is no way to
guarantee that all microbial growth
has been eliminated.
10. After the duct system has
been cleaned and restored to
use, a preventive maintenance
program will prevent the recur-
rence of problems.
Such a program should include
particular attention to the use and
maintenance of adequate filters,
control of moisture in the HVAC
system, and periodic inspection and
cleaning of HVAC system compo-
nents. (See discussion of Preventive
Maintenance on page 36 in Section
5.)
132 Appendix B
-------
Terminal Devices
Thermal comfort and effective contami-
nant removal demand that air delivered
into a conditioned space be properly
distributed within that space. Terminal
devices are the supply diffusers, return and
exhaust grilles, and associated dampers
and controls that are designed to distribute
air within a space and collect it from that
space. The number, design, and location
(ceiling, wall, floor) of terminal devices
are very important. They can cause a
HVAC system with adequate capacity to
produce unsatisfactory results, such as
drafts, odor transport, stagnant areas, or
short-circuiting.
Occupants who are uncomfortable
because of distribution deficiencies (drafts,
odor transport, stagnant air, or uneven
temperatures) often try to compensate by
adjusting or blocking the flow of air from
supply outlets. Adjusting system flows
without any knowledge of the proper
design frequently disrupts the proper
supply of air to adjacent areas. Distribu-
tion problems can also be produced if the
arrangement of movable partitions,
shelving, or other furnishings interferes
with airflow. Such problems often occur if
walls are moved or added without evaluat-
ing the expected impact on airflows.
Return Air Systems
In many modern buildings the above-
ceiling space is utilized for the unducted
passage of return air. This type of system
approach often reduces initial HVAC
system costs, but requires that the designer,
maintenance personnel, and contractors
obey strict guidelines related to life and
safety codes (e.g., building codes) that
must be followed for materials and devices
that are located in the plenum. In addition,
if a ceiling plenum is used for the collec-
tion of return air, openings into the ceiling
plenum created by the removal of ceiling
tiles will disrupt airflow patterns. It is
particularly important to maintain the
integrity of the ceiling and adjacent walls
in areas that are designed to be exhausted,
such as supply closets, bathrooms, and
chemical storage areas.
After return air enters either a ducted
return air grille or a ceiling plenum, it is
returned to the air handlers. Some systems
utilize return fans in addition to supply
fans in order to properly control the
distribution of air. When a supply and
return fan are utilized, especially in a VAV
system, their operation must be coordi-
nated in order to prevent under- or over-
pressurization of the occupied space or
overpressurization of the mixing plenum in
the air handler.
Exhausts, Exhaust Fans, and
Pressure Relief
Most buildings are required by law (e.g.,
building or plumbing codes) to provide for
exhaust of areas where contaminant
sources are strong, such as toilet facilities,
janitorial closets, cooking facilities, and
parking garages. Other areas where
exhaust is frequently recommended but
Return air is frequently car-
ried through non-ducted ple-
nums. It is more difficult to
control leakage of pollutants
into or out of this type of re-
turn air system than a ducted
system.
HVA C Systems and Indoor A ir Quality 133
-------
may not be legally required include:
reprographics areas, graphic arts facilities,
beauty salons, smoking lounges, shops,
and any area where contaminants are
known to originate.
For successful confinement and exhaust
of identifiable sources, the exhausted area
must be maintained at a lower overall
pressure than surrounding areas. Any area
that is designed to be exhausted must also
be isolated (disconnected) from the return
air system so that contaminants are not
transported to another area of the building.
In order to exhaust air from the build-
ing, make-up air from outdoors must be
brought into the HVAC system to keep the
building from being run under negative
pressure. This make-up air is typically
drawn in at the mixed air plenum as
described earlier and distributed within the
building. For exhaust systems to function
properly, the make-up air must have a clear
path to the area that is being exhausted.
It is useful to compare the total cfm of
powered exhaust to the minimum quantity
of mechanically-introduced outdoor air.
To prevent operating the building under
negative pressures (and limit the amount of
unconditioned air brought into the building
by infiltration), the amount of make-up air
drawn in at the air handler should always
be slighter greater than the total amount of
relief air, exhaust air, and air exfiltrating
through the building shell. Excess make-
up air is generally relieved at an exhaust or
relief outlet in the HVAC system, espe-
cially in air economizer systems. In
addition to reducing the effects of un-
wanted infiltration, designing and operat-
ing a building at slightly positive or neutral
pressures will reduce the rate of entry of
soil gases when the systems are operating.
For a building to actually operate at a
slight positive pressure, it must be tightly
constructed (e.g., specified at less than
one-half air change per hour at 0.25
pascals). Otherwise unwanted exfiltration
will prevent the building from ever
achieving a neutral or slightly positive
pressure.
Self-Contained Units
In some designs, small decentralized units
are used to provide cooling or heating to
interior or perimeter zones. With the
exception of induction units, units of this
type seldom supply outdoor air. They are
typically considered a low priority mainte-
nance item. If serf-contained units are
overlooked during maintenance, it is not
unusual for them to become a significant
source of contaminants, especially for the
occupants located nearby.
Controls
HVAC systems can be controlled manually
or automatically. Most systems are con-
trolled by some combination of manual and
automatic controls. The control system can
be used to switch fans on and off, regulate
the temperature of air within the conditioned
space, or modulate airflow and pressures by
controlling fan speed and damper settings.
Most large buildings use automatic controls,
and many have very complex and sophisti-
cated systems. Regular maintenance and
calibration are required to keep controls in
good operating order. All programmable
timers and switches should have "battery
backup" to reset the controls in the event of a
power failure.
Local controls such as room thermostats
must be properly located in order to
maintain thermal comfort. Problems can
result from:
thermostats located outside of the
occupied space (e.g., in return plenum)
poorly designed temperature control
zones (e.g., single zones that combine
areas with very different heating or
cooling loads)
thermostat locations subject to drafts or
to radiant heat gain or loss (e.g., exposed
to direct sunlight)
134 Appendix B
-------
thermostat locations affected by heat
from nearby equipment
To test whether or not a thermostat is
functioning properly, try setting it to an
extreme temperature. This experiment will
show whether or not the system is respond-
ing to the signal in the thermostat, and
also provides information about how the
HVAC system may perform under extreme
conditions.
Boilers
Like any other part of the HVAC system, a
boiler must be adequately maintained to
operate properly. However, it is particu-
larly important that combustion equipment
operate properly to avoid hazardous
conditions such as explosions or carbon
monoxide leaks, as well as to provide good
energy efficiency. Codes in most parts of
the country require boiler operators to be
properly trained and licensed.
Both ASME and ASHRAE have made
recommendations of how much combus-
tion air is needed for fuel burning appli-
ances.
Elements of boiler operation that are
particularly important to indoor air quality
and thermal comfort include:
Operation of the boiler and distribution
loops at a high enough temperature to
supply adequate heat in cold weather.
Maintenance of gaskets and breeching to
prevent carbon monoxide from escaping
into the building.
Maintenance of fuel lines to prevent any
leaks that could emit odors into the
building.
Provision of adequate outdoor air for
combustion.
Design of the boiler combustion exhaust
to prevent re-entrainment, (especially
from short boiler stacks, or into multi-
story buildings that were added after the
boiler plant was installed).
Modern office buildings tend to have
much smaller capacity boilers than older
buildings because of advances in energy
efficiency. In some buildings, the primary
heat source is waste heat recovered from
the chiller (which operates year-round to
cool the core of the building).
Cooling Towers
Maintenance of a cooling tower ensures
proper operation and keeps the cooling
tower from becoming a niche for breeding
pathogenic bacteria, such as Legionella
organisms. Cooling tower water quality
must be properly monitored and chemical
treatments used as necessary to minimize
conditions that could support the growth of
significant amounts of pathogens. Proper
maintenance may also entail physical
cleaning (by individuals using proper
protection) to prevent sediment accumula-
tion and installing drift eliminators.
It is important to determine
periodically whether the
HVAC controls are correctly
calibrated. In addition, time
clocks must be checked to
see if they are properly set
and running. Power failures
frequently cause time clocks
to be out of adjustment.
HVA C Systems and Indoor A ir Quality 135
-------
FIGURE B-2: Selected Ventilation Recommendations
Application
Food and Beverage
Service
Offices
Public Spaces
Retail Stores, Sales Floors,
Showroom Floors
Sports and
Amusement
Theaters
Education
Hotels, Motels,
Resorts,
Dormitories
Dining rooms
Cafeteria, fast food
Bars, cocktail lounges
Kitchen (cooking)
Office space
Reception areas
Conference rooms
Smoking lounge
Elevators
Basement and street
Upper floors
Malls and arcades
Smoking lounge
Spectator areas
Game rooms
Playing floors
Ballrooms and discos
Lobbies
Auditorium
Classroom
Music rooms
Libraries
Auditoriums
Bedrooms
Living rooms
Lobbies
Conference rooms
Assembly rooms
Occupancy
(people/1000 ft2)
70
100
100
20
7
60
50
70
30
20
20
70
150
70
30
100
150
150
50
50
20
150
30
50
120
Cfm/person Cfm/ft2
20
20
30
15
20
15
20
60
60
15
25
20
25
20
15
15
15
15
15
15
20
15
1.00
0.30
0.20
0.20
30 cfm/room
30 cfm/room
SOURCE: ASHRAE Standard 62-1989, Ventilation for Acceptable Air Quality
136 Appendix B
-------
Water Chillers
Water chillers are frequently found in large
building air conditioning systems because
of the superior performance they offer. A
water chiller must be maintained in proper
working condition to perform its function
of removing the heat from the building.
Chilled water supply temperatures should
operate in the range of 45°F or colder in
order to provide proper moisture removal
during humid weather. Piping should be
insulated to prevent condensation.
Other than thermal comfort, IAQ
concerns associated with water chillers
involve potential release of the working
fluids from the chiller system. The rupture
disk (safety release) of the system should
be piped to the outdoors, and refrigerant
leaks should be located and repaired.
Waste oils and spent refrigerant should be
disposed of properly.
ASHRAE STANDARDS AND
GUIDELINES
Standard 62-1989, "Ventilation for
Acceptable Air Quality"
ASHRAE 62-1989 is intended to assist
professionals in the proper design of
ventilation systems for buildings. The
standard presents two procedures for
ventilation design, a "Ventilation Rate"
procedure and an "Air Quality" procedure.
With the Ventilation Rate procedure,
acceptable air quality is achieved by
specifying a given quantity and quality of
outdoor air based upon occupant density
and space usage. Examples of the tables
listing the prescriptive amounts of outdoor
air for the Ventilation Rate procedure are
presented at the end of this section.
The Air Quality procedure is a perfor-
mance specification that allows acceptable
air quality to be achieved within a space by
controlling for known and specifiable
contaminants. This procedure is seldom
used because source strength is usually not
known.
Whichever procedure is utilized in the
design, the standard states that the design
criteria and assumptions shall be docu-
mented and made available to those
responsible for the operation and mainte-
nance of the system.
Important features of ASHRAE 62-
1989 include:
a definition of acceptable air quality
a discussion of ventilation effectiveness
the recommendation of the use of source
control through isolation and local
exhaust of contaminants
recommendations for the use of heat
recovery ventilation
a guideline for allowable carbon dioxide
levels
appendices listing suggested possible
guidelines for common indoor pollutants
Standard 55-1981, "Thermal
Environmental Conditions for
Human Occupancy"
ASHRAE 55-1981 covers several environ-
mental parameters including: temperature,
radiation, humidity, and air movement.
The standard specifies thermal environ-
mental conditions for the comfort of
healthy people in normal indoor environ-
ments for winter and summer conditions.
It also attempts to introduce limits on the
temperature variations within a space. In
addition to specifications for temperature
and humidity, guidelines are given for air
movement, temperature cycling, tempera-
ture drift, vertical temperature difference,
radiant asymmetry, and floor temperatures.
Adjustment factors are described for
various activity levels of the occupants,
and different clothing levels.
Important features of this standard
include:
a definition of acceptable thermal
comfort
HVA C Systems and Indoor A ir Quality 137
-------
This air washer is used to
remove particles and
water-soluble gaseous
contaminants and may also
control temperature and
humidity in the airstream.
Such systems are subject
to severe bacterial
contamination.
a discussion of the additional
environmental parameters that must
be considered
recommendations for summer and winter
comfort zones for both temperature and
relative humidity
a guideline for making adjustment for
activity levels
guidelines for making measurements
It should be noted that space tempera-
tures above 76°F but within the summer
comfort envelope have nevertheless been
associated with IAQ complaints in offices.
Note: As of summer 1991, a revised
Standard 55 was nearly ready.
Standard 52-76, "Method of Testing
Air-Cleaning Devices Used in
General Ventilation for Removing
Paniculate Matter"
This standard is intended to assist profes-
sionals in the evaluation of air cleaning
systems for particle removal. Two test
methods are described: the weight
arrestance test and the atmospheric dust
spot test. The standard discusses differ-
ences in results from the weight arrestance
test and the atmospheric dust spot test.
The atmospheric dust spot test is the test
used to determine the "efficiency " of an
air cleaner. The values obtained with
these two tests are not comparable. For
example, a filter with a weight arrestance
of 90% may have an efficiency by the
atmospheric dust spot test below 40%.
The weight arrestance test is generally
used to evaluate low efficiency filters
designed to remove the largest and
heaviest particles; these filters are com-
monly used in residential furnaces and/or
air-conditioning systems or as upstream
filters for other air cleaning devices. For
the test, a standard synthetic dust is fed
into the air cleaner and the proportion (by
weight) of the dust trapped on the filter is
determined. Because the particles in the
standard dust are relatively large, the
weight arrestance test is of limited value in
assessing the removal of smaller, respi-
rable-size particles from indoor air.
The atmospheric dust spot test is
usually used to rate medium efficiency air
cleaners. The removal rate is based on the
cleaner's ability to reduce soiling of a
clean paper target, an ability dependent on
the cleaner removing very fine particles
from the air. However, it should be noted
that this test addresses the overall effi-
ciency of removal of a complex mixture of
dust, and that removal efficiencies for
different size particles may vary widely.
Recent studies by EPA, comparing
ASHRAE ratings to filter efficiencies for
particles by size, have shown that efficien-
cies for particles in the size range of 0.1 to
1 microgram are much lower than the
ASHRAE rating.
Important features of this ASHRAE
standard include:
definitions of arrestance and efficiency
establishment of a uniform comparative
testing procedure for evaluating the
performance of air cleaning devices used
in ventilation systems
138 Appendix B
-------
establishment of a uniform reporting
method for performance
methods for evaluating resistance to
airflow and dust-holding capacity
No comparable guidelines or standards
are currently available for use in assessing
the ability of air cleaners to remove gas-
eous pollutants or radon and its progeny.
Guideline 1-1989, "Guideline for the
Commissioning of HVAC Systems"
This guideline is intended to assist profes-
sionals by providing procedures and meth-
ods for documenting and verifying the
performance of HVAC systems so that
they operate in conformity with the design
intent. The guideline presents a format for
documenting the occupancy requirements,
design assumptions, and the design intent
for the HVAC system. It provides a for-
mat for testing the system for acceptance
by the owner. In addition, the guideline
addresses adjustments of the system to
meet actual occupancy needs within the
capacity of the system when changes in
building use are made and
recommissioning is warranted.
Important features of this guideline
include:
definition of the commissioning process
discussion of the process involved in a
proper commissioning procedure
sample specification and forms for log-
ging information
recommendation for the implementation
of corrective measures as warranted
guideline for operator training
guidelines for periodic maintenance and
recommissioning as needed
HVA C Systems and Indoor A ir Quality 139
-------
Appendix C:
Moisture, Mold and Mildew
M,
I olds and mildew are fungi that grow
on the surfaces of objects, within pores,
and in deteriorated materials. They can
cause discoloration and odor problems,
deteriorate building materials, and lead to
allergic reactions in susceptible individu-
als, as well as other health problems.
The following conditions are necessary
for mold growth to occur on surfaces:
temperature range above 40°F and below
100°F
mold spores
nutrient base (most surfaces contain
nutrients)
moisture
Human comfort constraints limit the use
of temperature control. Spores are almost
always present in outdoor and indoor air,
and almost all commonly used construc-
tion materials and furnishings can provide
nutrients to support mold growth. Dirt on
surfaces provides additional nutrients.
Cleaning and disinfecting with non-
polluting cleaners and antimicrobial agents
provides protection against mold growth.
Other sections of this document have
discussed the importance of building
maintenance and proper sanitation in
preventing IAQ problems. However, it is
virtually impossible to eliminate all
nutrients. Moisture control is thus an
important strategy for reducing mold
growth.
Mold growth does not require the
presence of standing water; it can occur
when high relative humidity or the
hygroscopic properties (the tendency to
absorb and retain moisture) of building
surfaces allow sufficient moisture to
accumulate. Relative humidity and the
factors that govern it are often misunder-
stood. This appendix is intended to give
building managers an understanding of the
factors that govern relative humidity, and
to describe common moisture problems
and their solutions.
BACKGROUND ON RELATIVE
HUMIDITY, VAPOR PRESSURE,
AND CONDENSATION
Water enters buildings both as a liquid and
as a gas (water vapor). Water, in its liquid
form, is introduced intentionally in
bathrooms, kitchens, and laundries and
accidentally by way of leaks and spills.
Some of that water evaporates and joins
the water vapor that is exhaled by building
occupants as they breathe or that is
introduced by humidifiers. Water vapor
also moves in and out of the building as
part of the air that is mechanically intro-
duced or that infiltrates and exfiltrates
through openings in the building shell. A
There were complaints of vis-
ible water damage and musty
odors in this senior citizen
housing complex. Investiga-
tors confirmed that the prob-
lem was rain entry by using
an array of hoses to spray the
walls with
water, while operating the
building under negative pres-
sure. The test showed that
rain was entering at the joints
of the exterior
cladding, rather than at
cracks around windows.
Moisture, Mold and Mildew 141
-------
FIGURE C-1: Moisture Gain in a Building
AS? leakage
{carrying mot&tumJ
y cienar Qpsftif30& #n
cracks arsd crevicas
moi$tw«
fey peoples,
wall
Moisture Gain
Diffusion -f Internal
Courtesy of Dean Wallace
Shakun, Clayton State
College, Morrow, GA
lesser amount of water vapor diffuses into
and out of the building through the
building materials themselves. Figure C-1
illustrates locations of moisture entry.
The ability of air to hold water vapor
decreases as the air temperature is lowered.
If a unit of air contains half of the water
vapor it can hold, it is said to be at 50%
relative humidity (RH). As the air cools,
the relative humidity increases. If the air
contains all of the water vapor it can hold,
it is at 100% RH, and the water vapor
condenses, changing from a gas to a liquid.
It is possible to reach 100% RH without
changing the amount of water vapor in the
air (its "vapor pressure" or "absolute
humidity"); All that is required is for the air
temperature to drop to the "dew point."
Relative humidity and temperature
often vary within a room, while the
absolute humidity in the room air can
usually be assumed to be uniform. There-
fore, if one side of the room is warm and
the other side cool, the cool side of the
room has a higher RH than the warm side.
The highest RH in a room is always
next to the coldest surface. This is referred
as the "first condensing surface," as it will
142 Appendix C
-------
FIGURE C-2: Relationship of Temperature, Relative Humidity, and Moisture in the Air
A relative humidity reading taken in a room will only give an accurate
indication of the actual amount of moisture present if a temperature
reading is taken at the same time. The chart below shows that air at
70° F and 40% RH contains approximately 0.006 pounds of
moisture per pound of dry air (as indicated by the bold line), while
air that is at 50 °F and 40% RH contains approximately 0.003
pounds of moisture per pound of dry air (as indicated by the dashed
line). Although both are at 40% RH, the 70 °F air contains roughly
twice as much moisture as the 50 °F air.
SOURCE: Adapted from Psychometric Chart from ASHRAE Fundamentals, 1981
be the location where condensation first
occurs, if the relative humidity at the
surface reaches 100%. It is important to
understand this when trying to understand
why mold is growing on one patch of wall
or only along the wall-ceiling joint. It is
likely that the surface of the wall is cooler
than the room air because there is a void in
the insulation or because wind is blowing
through cracks in the exterior of the
building.
TAKING STEPS TO REDUCE
MOISTURE
Mold and mildew growth can be reduced
where relative humidities near surfaces can
be maintained below the dew point. This
can be accomplished by reducing the
moisture content (vapor pressure) of the
air, increasing air movement at the surface,
or increasing the air temperature (either the
general space temperature or the tempera-
ture at building surfaces).
Moisture, Mold and Mildew 143
-------
Above: In this building, mold and mildew
spots appeared on drywall
joints on the interior walls. When the wall
was cut open, mold growth was visible in
the wall cavity and the structural steel
showed corrosion. The problem was
caused by construction moisture trapped
between the interior finish and the exterior
sheathing. The solution was to modify the
exterior wall so that moisture could vent to
the outdoors. Below: This is visual
evidence of air movement through the
building shell. The water vapor in the
warm, humid indoor air has condensed and
frozen on the exterior wall.
Either surface temperature or vapor
pressure can be the dominant factor in
causing a mold problem. A surface
temperature-related mold problem may not
respond very well to increasing ventilation,
whereas a vapor pressure-related mold
problem may not respond well to increas-
ing temperatures. Understanding which
factor dominates will help in selecting an
effective control strategy.
Consider an old, leaky, poorly insulated
building. It is in a heating climate and
shows evidence of mold and mildew.
Since the building is leaky, its high natural
air exchange rate dilutes interior airborne
moisture levels, maintaining a low absolute
humidity during the heating season.
Providing mechanical ventilation in this
building in an attempt to control interior
mold and mildew probably will not be
effective in this case. Increasing surface
temperatures by insulating the exterior
walls, and thereby reducing relative
humidities next to the wall surfaces, would
be a better strategy to control mold and
mildew.
Reduction of surface temperature-
dominated mold and mildew is best
accomplished by increasing the surface
temperature through either or both of the
following approaches:
Increase the temperature of the air near
room surfaces either by raising the
thermostat setting or by improving air
circulation so that supply air is more
effective at heating the room surface.
Decrease the heat loss from room
surfaces either by adding insulation or by
closing cracks in the exterior wall to
prevent wind-washing (air that enters a
wall at one exterior location and exits
another exterior location without
penetrating into the building).
Vapor pressure-dominated mold and
mildew can be reduced by one or more of
the following strategies:
144 Appendix C
-------
source control (e.g., direct venting of
moisture-generating activities such as
showers) to the exterior
dilution of moisture-laden indoor air
with outdoor air that is at a lower
absolute humidity
dehumidification
Note that dilution is only useful as a
control strategy during heating periods,
when cold outdoor air tends to contain less
moisture. During cooling periods, outdoor
air often contains as much moisture as
indoor air.
IDENTIFYING AND CORRECTING
COMMON PROBLEMS FROM MOLD
AND MILDEW
Exterior Corners
Exterior corners are common locations for
mold and mildew growth in heating
climates, and in poorly insulated buildings
in cooling climates. They tend to be closer
to the outdoor temperature than other parts
of the building surface for one or more of
the following reasons:
poor air circulation (interior)
wind-washing (exterior)
low insulation levels
greater surface area of heat loss
Sometimes mold and mildew growth
can be reduced by removing obstructions
to airflow (e.g., rearranging furniture).
Buildings with forced air heating systems
and/or room ceiling fans tend to have
fewer mold and mildew problems than
buildings with less air movement, other
factors being equal.
"Set Back" Thermostats
Set back thermostats are commonly used to
reduce energy consumption during the
heating season. Mold and mildew growth
can occur when building temperatures are
lowered during unoccupied periods.
(Maintaining a room at too low a tempera-
ture can have the same effect as a set back
thermostat.) Mold and mildew can often
HOW TO IDENTIFY THE CAUSE OF A MOLD AND MILDEW
PROBLEM
Mold and mildew are commonly found on the exterior wall surfaces of
corner rooms in heating climate locations. An exposed corner room is
likely to be significantly colder than adjoining rooms, so that it has a higher
relative humidity (RH) than other rooms at the same water vapor pressure.
If mold and mildew growth are found in a corner room, then relative
humidities next to the room surfaces are above 70%. However, is the RH
above 70% at the surfaces because the room is too cold or because there
is too much moisture present (high water vapor pressure)?
The amount of moisture in the room can be estimated by measuring
both temperature and RH at the same location and at the same time.
Suppose there are two cases. In the first case, assume that the RH is
30% and the temperature is 70°F in the middle of the room. The low RH
at that temperature indicates that the water vapor pressure (or absolute
humidity) is low. The high surface RH is probably due to room surfaces
that are "too cold." Temperature is the dominating factor, and control
strategies should involve increasing the temperature at cold room sur-
faces.
In the second case, assume that the RH is 50% and the temperature is
70°F in the middle of the room. The higher RH at that temperature
indicates that the water vapor pressure is high and there is a relatively
large amount of moisture in the air. The high surface RH is probably due
to air that is "too moist." Humidity is the dominating factor, and control
strategies should involve decreasing the moisture content of the indoor
air.
be controlled in heating climate locations
by increasing interior temperatures during
heating periods. Unfortunately, this also
increases energy consumption and reduces
relative humidity in the breathing zone,
which can create discomfort.
Air Conditioned Spaces
The problems of mold and mildew can be
as extensive in cooling climates as in
heating climates. The same principles
apply: either surfaces are too cold,
moisture levels are too high, or both.
A common example of mold growth in
cooling climates can be found in rooms
where conditioned "cold" air blows against
the interior surface of an exterior wall.
This condition, which may be due to poor
duct design, diffuser location, or diffuser
performance, creates a cold spot at the
interior finish surfaces. A mold problem
can occur within the wall cavity as outdoor
air comes in contact with the cavity side of
the cooled interior surface. It is a particu-
lar problem in rooms decorated with low
Moisture, Mold and Mildew 145
-------
maintenance interior finishes (e.g.,
impermeable wall coverings such as vinyl
wallpaper) which can trap moisture
between the interior finish and the gypsum
board. Mold growth can be rampant when
these interior finishes are coupled with
cold spots and exterior moisture.
Possible solutions for this problem
include:
preventing hot, humid exterior air from
contacting the cold interior finish (i.e.,
controlling the vapor pressure at the
surface)
eliminating the cold spots (i.e., elevating
the temperature of the surface) by
relocating ducts and diffusers
ensuring that vapor barriers, facing
sealants, and insulation are properly
specified, installed, and maintained
increasing the room temperature to avoid
overcooling
In this case, increasing temperature
decreases energy consumption, though it
could cause comfort problems.
Thermal Bridges
Localized cooling of surfaces commonly
occurs as a result of "thermal bridges,"
elements of the building structure that are
highly conductive of heat (e.g., steel studs
in exterior frame walls, uninsulated
window lintels, and the edges of concrete
floor slabs). Dust particles sometimes
mark the locations of thermal bridges,
because dust tends to adhere to cold spots.
The use of insulating sheathings
significantly reduces the impact of thermal
bridges in building envelopes.
Windows
In winter, windows are typically the
coldest surfaces in a room. The interior
surface of a window is often the first
condensing surface in a room.
Condensation on window surfaces has
historically been controlled by using storm
windows or "insulated glass" (e.g., double-
glazed windows or selective surface gas-
filled windows) to raise interior surface
temperatures. The advent of higher
performance glazing systems has led to a
greater incidence of moisture problems in
heating climate building enclosures,
because the buildings can now be operated
at higher interior vapor pressures (moisture
levels) without visible surface condensa-
tion on windows. In older building
enclosures with less advanced glazing
systems, visible condensation on the
windows often alerted occupants to the
need for ventilation to flush out interior
moisture (so they opened the windows).
Concealed Condensation
The use of thermal insulation in wall
cavities increases interior surface tempera-
tures in heating climates, reducing the
likelihood of interior surface mold, mildew
and condensation. However, the use of
thermal insulation also reduces the heat
loss from the conditioned space into the
wall cavities, decreasing the temperature in
the wall cavities and therefore increasing
the likelihood of concealed condensation.
The first condensing surface in a wall
cavity in a heating climate is typically the
inner surface of the exterior sheathing, the
"back side" of plywood or fiberboard. As
the insulation value is increased in the wall
cavities, so does the potential for hidden
condensation.
Concealed condensation can be con-
trolled by either or both of the following
strategies:
Reducing the entry of moisture into the
wall cavities (e.g., by controlling
infiltration and/or exfiltration of mois-
ture-laden air)
Elevating the temperature of the first
condensing surface. In heating climate
locations, this change can be made by
installing exterior insulation (assuming
that no significant wind-washing is
occurring). In cooling climate locations,
this change an be made by installing
insulating sheathing to the interior of the
wall framing and between the wall
framing and the interior gypsum board.
146 Appendix C
-------
Appendix D: Asbestos
"As
Asbestos" describes six naturally
occurring fibrous minerals found in certain
types of rock formations. When mined
and processed, asbestos is typically sepa-
rated into very thin fibers that are normally
invisible to the naked eye. They may
remain in the air for many hours if re-
leased from asbestos-containing material
(ACM) and may be inhaled during this
time. Three specific diseases asbestosis
(a fibrous scarring of the lungs), lung
cancer, and mesothelioma (a cancer of the
lining of the chest or abdominal cavity)
have been linked to asbestos exposure. It
may be 20 years or more after exposure
before symptoms of these diseases appear;
however, high levels of exposure can re-
sult in respiratory diseases in a shorter
period of time.
Most of the health problems resulting
from asbestos exposure have been experi-
enced by workers whose jobs exposed
them to asbestos in the air over a pro-
longed period without the worker protec-
tion that is now required. Asbestos fibers
can be found nearly everywhere in our
environment (usually at very low levels).
While the risk to occupants is likely to be
small, health concerns remain, particularly
for the custodial and maintenance workers
in a building. Their jobs are likely to bring
them into proximity to ACM and may
sometimes require them to disturb the
ACM in the performance of maintenance
activities.
EPA estimates that "friable" (easily
crumbled) ACM can be found in an esti-
mated 700,000 public and commercial
buildings. About 500,000 of those build-
ings are believed to contain at least some
damaged asbestos. Significantly damaged
ACM is found primarily in building areas
not generally accessible to the public, such
as boiler and mechanical rooms, where
asbestos exposures generally would be
limited to service and maintenance work-
ers. However, if friable ACM is present in
air plenums, it can be distributed through-
out the building, thereby possibly exposing
building occupants.
When is asbestos a problem? Intact and
undisturbed asbestos materials do not
pose a health risk The mere presence of
asbestos in a building does not mean that
the health of building occupants is endan-
gered. ACM which is in good condition,
and is not damaged or disturbed, is not
likely to release asbestos fibers into the air.
When ACM is properly managed, release
of asbestos fibers into the air is reduced,
and the risk of asbestos-related disease is
thereby correspondingly reduced.
There are a number of guidelines and
regulations that govern asbestos exposure.
Occupational standards for preventing
asbestos-related diseases are recommended
by NIOSH and promulgated by OSHA.
NIOSH guidance contain Recommended
Exposure Limits (RELs) and OSHA
standards set Permissible Exposure Limits
(PELs). The standards also contain many
other measures, such as surveillance,
medical screening, analytical methods, and
methods of control. OSHA regulations
and the EPA Worker Protection Rule also
provide guidance on day-to-day activities
that may bring workers in contact with
ACM. EPA National Emission Standards
for Hazardous Air Pollutants (NESHAP)
define acceptable practices for renovation
and demolition activities that involve as-
bestos-containing materials. In addition,
many States have set exposure standards
and other regulations concerning asbestos.
Asbestos 147
-------
OSHA requires that signs be
posted around areas where
work is being done that
involves damaged asbestos-
containing materials. These
signs must communicate
specific types of information.
EPA and NIOSH recommend a practical
approach that protects public health by
emphasizing that ACM in buildings should
be identified and appropriately managed,
and that those workers who might disturb
it should be properly trained and protected.
EPA AND NIOSH
POSITIONS ON ASBESTOS
In an effort to calm unwarranted fears that
a number of people seem to have about the
mere presence of asbestos in their build-
ings and to discourage the decisions by
some building owners to remove all ACM
regardless of its condition, the EPA Ad-
ministrator issued an Advisory to the Pub-
lic on Asbestos in Buildings in 1991. This
advisory summarized EPA's policies for
asbestos control in the presentation of the
following "five facts":
Although asbestos is hazardous, the risk
of asbestos-related disease depends upon
exposure to airborne asbestos fibers.
Based upon available data, the average
airborne asbestos levels in buildings
seem to be very low. Accordingly, the
health risk to most building occupants
also appears to be very low.
Removal is often not a building owner's
SS.-X -. y
? ; V % -v.
%v s -..,
-
vw % - AS
best course of action to reduce asbestos
exposure. In fact, an improper removal
can create a dangerous situation where
none previously existed.
EPA only requires asbestos removal in
order to prevent significant public expo-
sure to airborne asbestos fibers during
building demolition or renovation
activities.
EPA does recommend a pro-active, in-
place management program whenever
asbestos-containing material is
discovered.
NIOSH's position on asbestos exposure
has been expressed in NIOSH policy state-
ments and internal reports and at OSHA
public hearings:
NIOSH recommends the goal of elimi-
nating asbestos exposure in the work-
place. Where exposures cannot be elimi-
nated, exposures should be limited to the
lowest concentration possible.
NIOSH contends that there is no safe
airborne fiber concentration for asbestos.
NIOSH therefore believes that any de-
tectable concentration of asbestos in the
workplace warrants further evaluation
and, if necessary, the implementation of
measures to reduce exposures.
NIOSH contends that there is no scien-
tific basis to support differentiating
health risks between types of asbestos
fibers for regulatory purposes.
Copies of the EPA and NIOSH policy
statements and public advisories are avail-
able, respectively, from those agencies.
See the last section in this appendix and
the Resources section for information on
how to obtain them.
148 Appendix D
-------
PROGRAMS FOR MANAGING AS-
BESTOS IN-PLACE
In some cases, an asbestos operations and
maintenance program is more appropriate
than other asbestos control strategies, in-
cluding removal. Proper asbestos manage-
ment is neither to rip it all out in a panic nor
to ignore the problem under the false pre-
sumption that asbestos is "risk free."
Health concerns remain, particularly for
custodial and maintenance workers.
In-place management does not mean "do
nothing." It means having a program to
ensure that the day-to-day management of
the building is carried out in a manner that
minimizes release of asbestos fibers into the
air, and that ensures that when asbestos
fibers are released, either accidentally or
intentionally, proper control and clean-up
procedures are implemented. Such a pro-
gram may be all that is necessary to control
the release of asbestos fibers until the as-
bestos-containing material in a building is
scheduled to be disturbed by renovation or
demolition activities.
The first responsibility of a building
owner or manager is to identify asbestos-
containing materials, through a building-
wide inventory or on a case-by-case basis,
before suspect materials are disturbed by
renovations or other actions. The Asbestos
Hazard Emergency Response Act
(AHERA) program requires that in schools
an inventory of asbestos materials be done
by properly accredited individuals. Starting
in late 1991 or 1992, there will also be a
requirement that if an inventory of asbestos
materials is done in public and commercial
buildings, the inventory must be done by
properly accredited individuals. In public
and commercial buildings facing major
renovations or demolition, inspections for
the presence of ACM are required, accord-
ing to the 1990 revision of the EPA Asbes-
tos NESHAP. A carefully designed air
monitoring program can be used as an ad-
junct to visual and physical evaluations of
the asbestos-containing materials.
After the material is identified, the build-
ing management and staff can then insti-
tute controls to ensure that the day-to-day
management of the building is carried out
in a manner that prevents or minimizes the
release of asbestos fibers into the air.
These controls will ensure that when as-
bestos fibers are released, either acciden-
tally or intentionally, proper management
and clean-up procedures are implemented.
Another concern of EPA, NIOSH, and
other Federal, State, and local agencies that
are concerned with asbestos and public
health is to ensure proper worker training
and protection. In the course of their daily
activities, maintenance and service work-
ers in buildings may disturb materials and
thereby elevate asbestos fiber levels and
asbestos exposure, especially for them-
selves, if they are not properly trained and
protected. For these persons, risk may be
significantly higher than for other building
occupants. Proper worker training and
protection, as part of an active in-place
management program, can reduce any
unnecessary asbestos exposure for these
workers and others. AHERA requires this
training for school employees whose job
activities may result in asbestos distur-
bances.
In addition to the steps outlined above,
an in-place management program will
usually include notification to workers and
occupants of the existence of asbestos in
their building, periodic surveillance of the
material, and proper recordkeeping. EPA
requires all of these activities for schools
and strongly recommends that other build-
ing owners also establish comprehensive
asbestos management programs. Without
such programs, asbestos materials could be
damaged or could deteriorate, which might
result in elevated levels of airborne asbes-
tos fibers. While the management costs of
all the above activities will depend upon
the amount, condition, and location of the
materials, such a program need not be
expensive.
Asbestos 149
-------
WHERE TO GO FOR ADDITIONAL
INFORMATION
For guidance on asbestos, building owners
and managers are urged to become familiar
with two EPA documents: Managing
Asbestos in Place (published in 1990 and
also known as the "Green Book") and
Guidance for Controlling Asbestos-Con-
taining Materials in Buildings (published
in 1985 and also known as the "Purple
Book").
To obtain copies of the guidance publi-
cations and other materials mentioned
above, or to get additional information on
technical issues, call or write:
Environmental Assistance Division
Office of Toxic Substances
U.S. EPA (TS-799)
401M Street SW
Washington, DC 20460
Telephone (TSCA Information Hotline):
202-554-1404
National Institute for Occupational
Safety and Health
Technical Information Branch
4676 Columbia Parkway
Cincinnati, OH 45226
Telephone: 1-800-35-NIOSH or
1-800-356-4674
Contact State air pollution control or health
agencies for information on pertinent State
activities and regulations. To find an as-
bestos contact in State agencies, consult
the EPA Directory of State Indoor Air
Contacts. For a more complete listing of
publications concerning asbestos, refer to
Appendix G.
150 Appendix D
-------
Appendix E: Radon
Ivadon is a radioactive gas produced by
the decay of radium. It occurs naturally in
almost all soil and rock. Radon migrates
through the soil and groundwater and can
enter buildings through cracks or other
openings in their foundations. Radon's
decay products can cause lung cancer, and
radon is second only to smoking as a cause
of lung cancer in America.
Based on early data, the EPA concen-
trated its radon reduction efforts on one-
and two- family homes. Citing results
from a radon survey conducted jointly
with 25 States, the EPA and the Surgeon
General's office issued a National Health
Advisory that called for testing most
homes for the presence of radon. Ex-
tensive research and case studies in the
field have demonstrated practical remed-
iation methods that typically reduce the
indoor radon concentrations below 4 pCi/L,
the current EPA action level for all occu-
pied buildings.
Now that EPA technical guidance is
being successfully used to reduce human
health risk in homes, the EPA is emphasiz-
ing the development of radon measure-
ment, mitigation, and prevention tech-
niques for schools and large buildings.
Preliminary data from a nationwide survey
of Federal buildings indicates that radon
will probably not be as widespread a prob-
lem in large buildings as it is in homes.
One of the major factors for this difference
is that multi-story buildings have propor-
tionally less space in direct contact with
the earth when compared to homes.
Some of the control technologies utilized
for homes are being studied for their ap-
propriateness to other building types, in-
cluding schools and large buildings. In
addition, new methods and technologies are
being developed to ensure a practical and
cost-effective reduction of radon in these
buildings. As a result, published docu-
ments on guidance and protocols for mea-
surement and remediation of radon in large
buildings are not currently available.
This publication provides an overview of
radon issues, and should be used only as
background information. For more infor-
mation, refer to other sources of informa-
tion that are specific to radon in indoor air.
BUILDING MEASUREMENT,
DIAGNOSIS, AND REMEDIATION
Protocols specific to the measurement of
radon and radon progeny in large buildings
are tentatively scheduled to be published by
EPA in early 1992. These large building
measurement protocols can assist skilled
building owner or facility personnel in
making initial screening tests for the
presence of radon. A new protocol specific
to large buildings is necessary due to the
major differences in building dynamics,
HVAC systems, and occupancy patterns
between large buildings and homes, and
how these impact radon.
As part of its effort to develop wide-
spread State and private sector capabilities,
the EPA established a voluntary proficiency
program (Radon Measurement Proficiency
Program) for radon laboratories and com-
mercial measurement firms. A State Profi-
ciency Report (EPA 520/1-91-014), which
gives information on specific radon mea-
surement firms in your area, can be ob-
tained from your State radon office or from
your EPA Regional Office.
Radon 151
-------
Three elements must be present for
radon to be a problem: a radon source, a
pathway that allows radon to enter the
building, and a driving force that causes
the radon to flow through the pathway and
into the building. Preventing radon from
entering the building is always desirable
compared with mitigation after radon has
entered. The reduction of pathways and
driving forces are therefore usually the
focus of attention during diagnostic and
remediation efforts.
Due to the diversity and complexity of
large buildings, and because the research
and development of appropriate radon
remediation technologies for these struc-
tures are in the early phases, generalized
building diagnostic and remediation meth-
odologies are not yet available. For assis-
tance, please contact the appropriate orga-
nizations on the following list or a profes-
sional engineering firm or mitigation com-
pany with experience in this matter.
WHERE TO GO FOR ADDITIONAL INFORMATION
State Radon Offices
There are several ways to get the name of a
contact person in your State radon office or
information about that office. You can call
the radon contact in the EPA Regional
Office for your state or you can order the
Directory of State Indoor Air Contacts
from the EPA Public Information Center.
(See list of IAQ and radon contacts and list
of EPA publications in Appendix G.)
Regional Radon Training Centers
As part of its effort to develop State and
private sector capabilities for radon reduc-
tion, the EPA has coordinated the forma-
tion of four Regional Radon Training
Centers (RRTCs). The RRTCs provide a
range of radon training and proficiency
examination courses to the public for a fee.
Eastern Regional Radon
Training Center
Rutgers, The State University
Livingston Campus, Building 4087
New Brunswick, NJ 08903-0231
908-932-2582
Mid-West Universities
Radon Consortium
University of Minnesota
1985 Buford Avenue (240)
St. Paul, MN 55108-6136
612-624-8747
Western Regional Radon
Training Center
Guggenheim Hall
Colorado State University
Fort Collins, CO 80523
1-800-462-7459/303-491-7742
Southern Regional Radon
Training Center
Auburn University
Housing Research Center
Harbert Engineering Center
Auburn University, AL 36849-5337
205-844-6261
EPA Regional Offices
If you want additional information from
EPA regarding radon, start with the EPA
Regional Offices. Telephone numbers
for radon information contacts are given
in the list of EPA Regional Offices in
Appendix G of this publication.
EPA Radon Division
If information is unavailable from the
above sources, please contact the EPA
Radon Division at:
Radon Division (ANR-464)
U.S. EPA
401M Street, SW
Washington, DC 20460
202-260-9605
152 Appendix E
-------
Appendix F: Glossary and Acronyms
ACGIH American Conference of
Governmental Industrial Hygienists.
ASHRAE American Society of
Heating, Refrigerating, and Air-Condition-
ing Engineers.
ASTM American Society for Testing
and Materials.
Air Cleaning An IAQ control strategy
to remove various airborne particulates
and/or gases from the air. The three types
of air cleaning most commonly used are
paniculate filtration, electrostatic precipita-
tion, and gas sorption.
Air Exchange Rate Used in two ways:
1) the number of times that the outdoor air
replaces the volume of air in a building per
unit time, typically expressed as air
changes per hour; 2) the number of times
that the ventilation system replaces the air
within a room or area within the building.
Antimicrobial Agent that kills micro-
bial growth. See "disinfectant," "sani-
tizer", and "sterilizer."
BRI See "Building-Related Illness."
Biological Contaminants Agents
derived from or that are living organisms
(e.g., viruses, bacteria, fungi, and mammal
and bird antigens) that can be inhaled and
can cause many types of health effects
including allergic reactions, respiratory
disorders, hypersensitivity diseases, and
infectious diseases. Also referred to as
"microbiologicals" or "microbials."
Breathing Zone Area of a room in
which occupants breathe as they stand, sit,
or lie down.
Building Envelope Elements of the
building, including all external building
materials, windows, and walls, that enclose
the internal space.
Building-Related Illness Diagnosable
illness whose symptoms can be identified
and whose cause can be directly attributed
to airborne building pollutants (e.g.,
Legionnaire's disease, hypersensitivity
pneumonitis).
CFM Cubic feet per minute.
CO Carbon monoxide.
CO2 Carbon dioxide.
Ceiling Plenum Space below the
flooring and above the suspended ceiling
that accommodates the mechanical and
electrical equipment and that is used as
part of the air distribution system. The
space is kept under negative pressure.
Commissioning Start-up of a building
that includes testing and adjusting HVAC,
electrical, plumbing, and other systems to
assure proper functioning and adherence to
design criteria. Commissioning also
includes the instruction of building
representatives in the use of the building
systems.
Conditioned Air Air that has been
heated, cooled, humidified, or dehumidi-
fied to maintain an interior space within
the "comfort zone." (Sometimes referred to
as "tempered" air.)
Constant Air Volume Systems Air
handling system that provides a constant
air flow while varying the temperature to
meet heating and cooling needs.
Dampers Controls that vary airflow
through an air outlet, inlet, or duct. A
damper position may be immovable,
manually adjustable, or part of an auto-
mated control system.
Glossary and Acronyms 153
-------
Diffusers and Grilles Components of
the ventilation system that distribute and
diffuse air to promote air circulation in the
occupied space. Diffusers supply air and
grilles return air.
Disinfectants One of three groups of
antimicrobials registered by EPA for
public health uses. EPA considers an
antimicrobial to be a disinfectant when it
destroys or irreversibly inactivates
infectious or other undesirable organisms,
but not necessarily their spores. EPA
registers three types of disinfectant
products based upon submitted efficacy
data: limited, general or broad spectrum,
and hospital disinfectant.
EPA United States Environmental
Protection Agency.
ETS Environmental tobacco smoke.
Environmental Agents Conditions
other than indoor air contaminants that
cause stress, comfort, and/or health
problems (e.g., humidity extremes, drafts,
lack of air circulation, noise, and over-
crowding).
Ergonomics Applied science that
investigates the impact of people's
physical environment on their health and
comfort (e.g., determining the proper chair
height for computer operators).
Exhaust Ventilation Mechanical
removal of air from a portion of a building
(e.g., piece of equipment, room, or general
area).
Gas Sorption Devices used to reduce
levels of airborne gaseous compounds by
passing the air through materials that
extract the gases. The performance of
solid sorbents is dependent on the airflow
rate, concentration of the pollutants,
presence of other gases or vapors, and
other factors.
HEPA High efficiency paniculate
arrestance (filters).
HVAC Heating, ventilation, and air-
conditioning system.
Hypersensitivity Diseases Diseases
characterized by allergic responses to
animal antigens. The hypersensitivity
diseases most clearly associated with
indoor air quality are asthma, rhinitis, and
hypersensitivity pneumonitis. Hypersensi-
tivity pneumonitis is a rare but serious
disease that involves progressive lung
damage as long as there is exposure to the
causative agent.
IAQ Indoor air quality.
IPM Integrated pest management.
Indicator Compounds Chemical
compounds, such as carbon dioxide, whose
presence at certain concentrations may be
used to estimate certain building condi-
tions (e.g., airflow, presence of sources).
MCS See "Multiple Chemical Sensitiv-
ity."
MSDS Material Safety Data Sheet.
Make-up Air Air brought into a
building from the outdoors through the
ventilation system that has not been
previously circulated through the system.
Microbiologicals See "Biological
Contaminants."
Multiple Chemical Sensitivity A term
used by some people to refer to a condition
in which a person is considered to be
sensitive to a number of chemicals at very
low concentrations. There are a number of
views about the existence, potential causes,
and possible remedial actions regarding
this phenomenon.
NIOSH National Institute for Occupa-
tional Safety and Health.
NTIS National Technical Information
Service.
Negative Pressure Condition that
exists when less air is supplied to a space
than is exhausted from the space, so the air
pressure within that space is less than that
in surrounding areas.
OSHA Occupational Safety and Health
Administration.
154 Appendix F
-------
PELs Permissible Exposure Limits
(standards set by OSHA).
PM Preventive Maintenance.
Plenum Air compartment connected to
a duct or ducts.
Positive Pressure Condition that exists
when more air is supplied to a space than
is exhausted, so the air pressure within that
space is greater than that in surrounding
areas.
Psychosocial Factors Psychological,
organizational, and personal stressors that
could produce symptoms similar to poor
indoor air quality.
RELs Recommended Exposure Limits
(recommendations made by NIOSH).
Radiant Heat Transfer Radiant heat
transfer occurs when there is a large differ-
ence between the temperatures of two
surfaces that are exposed to each other, but
are not touching.
Re-entrainment Situation that occurs
when the air being exhausted from a build-
ing is immediately brought back into the
system through the air intake and other
openings in the building envelope.
SBS See "Sick Building Syndrome."
Sanitizer One of three groups of anti-
microbials registered by EPA for public
health uses. EPA considers an antimicro-
bial to be a sanitizer when it reduces but
does not necessarily eliminate all the mi-
croorganisms on a treated surface. To be a
registered sanitizer, the test results for a
product must show a reduction of at least
99.9% in the number of each test microor-
ganism over the parallel control.
Short-circuiting Situation that occurs
when the supply air flows to exhaust regis-
ters before entering the breathing zone. To
avoid short-circuiting, the supply air must
be delivered at a temperature and velocity
that results in mixing throughout the space.
Sick Building Syndrome Term some-
times used to describe situations in which
building occupants experience acute health
and/or comfort effects that appear to be
linked to time spent in a particular build-
ing, but where no specific illness or cause
can be identified. The complaints may be
localized in a particular room or zone, or
may be spread throughout the building.
Soil Gases Gases that enter a building
from the surrounding ground (e.g., radon,
volatile organics, pesticides).
Stack Effect Pressure-driven airflow
produced by convection as heated air rises,
creating a positive pressure area at the top
of a building and a negative pressure area
at the bottom of a building. The stack
effect can overpower the mechanical sys-
tem and disrupt ventilation and circulation
in a building.
Static Pressure Condition that exists
when an equal amount of air is supplied to
and exhausted from a space. At static
pressure, equilibrium has been reached.
Sterilizer One of three groups of anti-
microbials registered by EPA for public
health uses. EPA considers an antimicro-
bial to be a sterilizer when it destroys or
eliminates all forms of bacteria, fungi,
viruses, and their spores. Because spores
are considered the most difficult form of a
microorganism to destroy, EPA considers
the term sporicide to be synonymous with
"sterilizer."
TLVs Threshold Limit Values (guide-
lines recommended by ACGIH).
TVOCs Total volatile organic com-
pounds.
Tracer Gases Compounds, such a
sulfur hexafluoride, which are used to
identify suspected pollutant pathways and
to quantify ventilation rates. Tracer gases
may be detected qualitatively by their odor
or quantitatively by air monitoring equip-
ment.
VAV Variable air volume system.
VOCs See "Volatile Organic Com-
pounds."
Glossary and Acronyms 155
-------
Variable Air Volume System Air
handling system that conditions the air to a
constant temperature and varies the outside
airflow to ensure thermal comfort.
Ventilation Air Defined as the total air,
which is a combination of the air brought
into the system from the outdoors and the
air that is being recirculated within the
building. Sometimes, however, used in
reference only to the air brought into the
system from the outdoors.
Volatile Organic Compounds (VOCs)
Compounds that evaporate from the many
housekeeping, maintenance, and building
products made with organic chemicals.
These compounds are released from
products that are being used and that are in
storage. In sufficient quantities, VOCs can
cause eye, nose, and throat irritations,
headaches, dizziness, visual disorders,
memory impairment; some are known to
cause cancer in animals; some are sus-
pected of causing, or are known to cause,
cancer in humans. At present, not much is
known about what health effects occur at
the levels of VOCs typically found in
public and commercial buildings.
WHO World Health Organization.
156 Appendix F
-------
Appendix G: Resources
FEDERAL AGENCIES WITH MAJOR
INDOOR AIR RESPONSIBILITY FOR
PUBLIC AND COMMERCIAL
BUILDINGS
U.S. Environmental
Protection Agency
Conducts a non-regulatory indoor air
quality program that emphasizes research,
information dissemination, technical
guidance, and training. Issues regulations
and carries out other activities that affect
indoor air quality under the laws for
pesticides, toxic substances, and drinking
water.
Public Information Center
(PM-211B)
401M Street, SW
Washington, DC 20460
202-382-2080
Distributes indoor air quality
publications.
National Pesticides Telecommunications
Network National toll-free number:
1-800-858-PEST
In Texas: 806-743-3091
Provides information on pesticides.
TSCA Hotline Service
202-554-1404
Provides information on asbestos and
other toxic substances.
Occupational Safety and Health
Administration
Promulgates safety and health standards,
facilitates training and consultation, and
enforces regulations to ensure that
workers are provided with safe and
healthful working conditions. (For further
information contact OSHA Regional
Offices.)
National Institute for
Occupational Safety and Health
Conducts research, recommends standards
to the U.S. Department of Labor, and
conducts training on various issues
including indoor air quality to promote
safe and healthful workplaces. Undertakes
investigations at request of employees,
employers, other federal agencies, and
state and local agencies to identify and
mitigate workplace problems.
Requests for Field Investigations
NIOSH
Hazard Evaluations and Technical
Assistance Branch (R-9)
4676 Columbia Parkway
Cincinnati, OH 45226
513-841-4382
Requests for Information:
1-800-35-NIOSH
or 1-800-356-4674
Resources 157
-------
EPA Regional Offices
Address inquiries to the contacts in the
EPA Regional Offices at the following
addresses:
(CT,ME,MA,NH,RI,VT)
EPA Region 1
John F. Kennedy Federal Building
Boston, MA 02203
617-565-3232 (indoor air)
617-565-4502 (radon)
617-565-3744 (asbestos)
617-565-3265 (NESHAP)
(NJ,NY,PR,VI)
EPA Region 2
26 Federal Plaza
New York, NY 10278
212-264-4410 (indoor air)
212-264-4410 (radon)
212-264-6671 (asbestos)
212-264-6770 (NESHAP)
(DE,DC,MD,PA,VA,WV)
EPA Region 3
841 Chestnut Building
Philadelphia, PA 19107
215-597-8322 (indoor air)
215-597-4084 (radon)
215-597-3160 (asbestos)
215-597-1970 (NESHAP)
(AL,FL,GA,KY,MS,NC,SC,TN)
EPA Region 4
345 Courtland Street, NE
Atlanta, GA 30365
404-347-2864 (indoor air)
404-347-3907 (radon)
404-347-5014 (asbestos)
404-347-5014 (NESHAP)
(IL,IN,MI,MN,OH,WI)
EPA Region 5
230 South Dearborn Street
Chicago, IL 60604
Region 5 Environmental Hotline:
1-800-572-2515 (IL)
1-800-621-8431 (IN, MI, MN, OH, WI)
312-886-7930 (outside Region 5)
(AR,LA,NM,OK,TX)
EPA Region 6
1445 Ross Avenue
Dallas, TX 75202-273 3
214-655-7223 (indoor air)
214-655-7223 (radon)
214-655-7223 (asbestos)
214-655-7223 (NESHAP)
(IA,KS,MO,NE)
EPA Region 7
726 Minnesota Avenue
Kansas City, KS 66101
913-551-7020 (indoor air)
913-551-7020 (radon)
913-551-7020 (asbestos)
913-551-7020 (NESHAP)
(CO,MT,ND,SD,UT,WY)
EPA Region 8
999 18th Street Suite 500
Denver, CO 80202-2405
303-293-1440 (indoor air)
303-293-0988 (radon)
303-293-1442 (asbestos)
303-294-7611 (NESHAP)
(AZ,CA,HI,NV,AS,GU)
EPA Region 9
75 Hawthorne Street, A-l-1
San Francisco, CA 94105
415-744-1133 (indoor air)
415-744-1045 (radon)
415-744-1136 (asbestos)
415-744-1135 (NESHAP)
(AK,ID,OR,WA)
EPA Region 10
1200 Sixth Avenue
Seattle, WA 98101
206-553-2589 (indoor air)
206-553-7299 (radon)
206-553-4762 (asbestos)
206-553-1757 (NESHAP)
158 Appendix G
-------
OSHA Regional Offices
(CT,ME,MA,NH,RI,VT)
OSHA Region 1
133 Portland Street, 1st Floor
Boston, MA 02114
617-565-7164
(NJ,NY,PR,VI)
OSHA Region 2
210 Varick Street, Room 670
New York, NY 10014
212-337-2376
(DE,DC,MD,PA,VA,WV)
OSHA Region 3
Gateway Building, Suite 2100
3535 Market Street
Philadelphia, PA 19104
215-596-1201
(AL,FL,GA,KY,MS,NC,SC,TN)
OSHA Region 4
1375 Peachtree Street, ME, Suite 587
Atlanta, GA 30367
404-347-3573
(IL,IN,MI,MN,OH,WI)
OSHA Region 5
230 South Dearborn Street, Room 3244
Chicago, IL 60604
312-353-2220
(AR,LA,NM,OK,TX)
OSHA Region 6
525 Griffin Street, Room 602
Dallas, TX 75202
214-767-4731
(IA,KS,MO,NE)
OSHA Region 7
911 Walnut Street, Room 406
Kansas City, MO 64106
816-426-5861
(CO,MT,ND,SD,UT,WY)
OSHA Region 8
Federal Building, Room 1576
1961 Stout Street
Denver, CO 80294
303-844-3061
(AZ,CA,HI,NV,AS,GU)
OSHA Region 9
71 Stevenson Street, 4th Floor
San Francisco, CA 94105
415-744-6570
(AK,ID,OR,WA)
OSHA Region 10
1111 Third Avenue, Suite 715
Seattle, WA 98101-3212
206-442-5930
Resources 159
-------
OTHER FEDERAL AGENCIES WITH
INDOOR AIR RESPONSIBILITIES
Bonneville Power Administration
P.O. Box3621-RMRD
Portland, OR 97208
503-230-5475
Provides radon-resistant construction
techniques, source control, and removal
technology for indoor air pollutants.
Consumer Product Safety Commission
5401 Westbard Avenue
Bethesda, MD 20207
1-800-638-CPSC
Reviews complaints regarding the safety of
consumer products and takes action to
ensure product safety.
General Services Administration
18th and F Streets, NW
Washington, DC 20405
202-501-1464
Writes indoor air quality policy for Fed-
eral buildings. Provides proactive indoor
air quality building assessments. Assesses
complaints and provides remedial action.
U.S. Department of Energy
Office of Conservation and Renewable
Energy
1000 Independence Avenue, SW, CE-43
Washington, DC 20585
202-586-9455
Quantifies the relationship among reduced
infiltration, adequate ventilation, and ac-
ceptable indoor air quality.
U.S. Department of Health and Human
Services
Office on Smoking and Health
National Center for Chronic Disease
Prevention and Health Promotion
Centers for Disease Control
1600 Clifton Road, NE
Mail Stop K50
Atlanta, GA 30333
404-488-5705
Disseminates information about the health
effects of passive smoking and strategies
for eliminating exposure to environmental
tobacco smoke.
Tennessee Valley Authority
Occupational Hygiene Department
328 Multipurpose Building
Muscle Shoals, AL 35660
205-386-2314
Provides building surveys and assessments
associated with employee indoor air
quality complaints.
STATE AND LOCAL AGENCIES
Your questions and concerns about indoor
air problems can frequently be answered
most readily by the government agencies
in your State or locality. Responsibilities
for indoor air quality issues are usually
divided among many different agencies.
You will often find that calling or writing
the agencies responsible for health or air
quality control is the best way to start
getting information from your State or
local government. The EPA and Public
Health Foundation publication, Directory
of State Indoor Air Contacts, lists State
agency contacts. (See publications list for
information on ordering this publication.)
160 Appendix G
-------
PRIVATE SECTOR CONTACTS
The private sector organizations that have
information for the public on indoor air
quality issues in commercial and public
buildings include the following:
Building Management Associations
Association of Physical Plant Adminis-
trators of Universities and Colleges
1446 Duke Street
Alexandria, VA 22314-3492
703-684-1446
Building Owners and Managers
Association International
1201 New York Ave., NW, Suite 300
Washington, DC 20005
202-408-2684
Institute of Real Estate Management
430 North Michigan Avenue
Chicago, IL 60611
312-661-1930
International Council of Shopping
Centers
1199 North Fairfax Street, Suite 204
Alexandria, VA 22314
703-549-7404
International Facilities Management
Association
Summit Tower, Suite 1710
11 Greenway Plaza
Houston, TX 77046
713-623-4362
National Apartment Association
1111 14th Street, NW, Suite 900
Washington, DC 20005
202-842-4050
National Association of Industrial and
Office Parks
1215 Jefferson Davis Highway, Suite 100
Arlington, VA 22202
703-979-3400
Organizations
Air and Waste Management Association
P.O. Box 2861
Pittsburgh, PA 15230
412-232-3444
Air-Conditioning and Refrigeration
Institute
1501 Wilson Blvd., Suite 600
Arlington, VA 22209
703-524-8800
American Conference of Governmental
Industrial Hygienists
6500 Glenway Avenue, Building D-7
Cincinnati, OH 45211
513-661-7881
American Industrial Hygiene
Association
P.O. Box 8390
345 White Pond Drive
Akron, OH 44320
216-873-2442
American Society for Testing and
Materials
1916 Race Street
Philadelphia, PA 19103
215-299-5571
American Society of Heating,
Refrigerating, and Air-Conditioning
Engineers
179 ITullie Circle, NE
Atlanta, GA 30329
404-636-8400
National Conference of States on
Building Codes and Standards, Inc.
505 Huntmar Park Drive, Suite 210
Herndon, VA 22070
703-437-0100
Product Manufacturers
Professional and Standard Setting
Resources 161
-------
Adhesive and Sealant Council
1627 K Street, NW, Suite 1000
Washington, DC 20006-1707
202-452-1500
Asbestos Information Association
1745 Jefferson Davis Highway, Room 509
Arlington, VA 22202
703-979-1150
Business Council on Indoor Air Quality
1225 19th Street, Suite 300
Washington, DC 20036
(202) 775-5887
Carpet and Rug Institute
310 Holiday Avenue
Dalton, GA 30720
404-278-3176
Chemical Specialties Manufacturers
Association
1913 I Street, NW
Washington, DC 20006
202-872-8110
Electric Power Research Institute
P.O. Box 10412
Palo Alto, CA 94303
415-855-2902
Formaldehyde Institute, Inc.
1330 Connecticut Avenue, NW
Washington, DC 20036
202-822-6757
Foundation of Wall and Ceiling
Industries
1600 Cameron Street
Alexandria, VA 22314-2705
703-548-0374
Gas Research Institute
8600 West Bryn Mawr Avenue
Chicago, IL 60631
312-399-8304
National Paint and Coatings Association
1500 Rhode Island Avenue, NW
Washington, DC 20005
202-462-6272
Thermal Insulation Manufacturers
Association Technical Services
Air Handling Committee
1420 King Street
Alexandria, VA 22314
(703) 684-0474
Building Service Associations
Air-Conditioning and Refrigeration
Institute
1501 Wilson Boulevard, 6th floor
Arlington, VA 22209
703-524-8800
Air-Conditioning Contractors of
America
1513 16th Street, NW
Washington DC 20036
202-483-9370
American Consulting Engineers Council
1015 15th Street, NW, Suite 802
Washington, DC 20005
202-347-7474
Associated Air Balance Council
1518 K Street, NW
Washington, DC 20005
202-737-0202
Association of Energy Engineers
4025 Pleasantdale Rd., Suite 420
Atlanta, GA 30340
404-447-5083
Association of Specialists in Cleaning
and Restoration International
10830 Annapolis Junction Road, Suite 312
Annapolis Junction, MD 20701
301-604-4411
National Air Duct Cleaners Association
1518 K Street, NW, Suite 503
Washington, DC 20005
202-737-2926
National Association of Power Engineers
3436 Haines Way, Suite 101
Falls Church, VA 22041
703-845-7055
National Energy Management Institute
601 North Fairfax Street, Suite 160
162 Appendix G
-------
Alexandria, VA 22314
703-739-7100
National Environmental Balancing
Bureau
1385PiccardDrive
Rockville, MD 20850
301-977-3698
National Pest Control Association
8100 Oak Street
Dunn Loring, VA 22027
703-573-8330
Sheet Metal and Air Conditioning
Contractors National Association
4201 LaFayette Center Drive
Chantilly, VA 22021
703-803-2980
Unions
AFL-CIO
Department of Occupational Safetyand
Health
815 16th Street, NW
Washington, DC 20006
202-637-5000
American Federation of Government
Employees
80 F Street, NW
Washington, DC 20001
202-737-8700
American Federation of State, County,
and Municipal Employees
1625 L Street, NW
Washington, DC 20036
(202) 429-1215
American Federation of Teachers
555 New Jersey Avenue, NW
Washington, DC 20001
202-879-4400
Communication Workers of America
5013rd Street, NW
Washington, DC 20001
202-434-1160
International Union of Operating
Engineers
1125 17th Street, NW
Washington, DC 20036
202-429-9100
Service Employees International Union
1313 L Street, NW
Washington, DC 20005
Environmental/Health/
Consumer Organizations
American Academy of Allergy and
Immunology
611 East Wells Street
Milwaukee, WI 53202
414-272-6071
American Lung Association
or your local lung association
1740 Broadway
New York, NY 10019
Consumer Federation of America
1424 16th Street, NW, Suite 604
Washington, DC 20036
National Center for Environmental
Health Strategies
1100 Rural Avenue
Voorhees,NJ 08043
609-429-5358
National Environmental Health
Association
720 South Colorado Blvd.
South Tower, Suite 970
Denver, CO 80222
303-756-9090
National Foundation for the Chemically
Hypersensitive
P.O. Box 9
Wrightsville Beach, NC 28480
517-697-3989
Occupational Health Foundation
1126 16th Street, NW
Washington, DC 20036
202-842-7840
PUBLICATIONS
Resources 163
-------
Items marked * are available from EPA
Public Information Center (PM-211B),
401M Street, SW, Washington, DC
20460. 202-382-2080.
Items marked ** are available from TSCA
Assistance Hotline (TS-799), 401 M
Street, SW, Washington, DC 20460.
(202)554-1404.
Items marked*** are available from
NIOSH Publications Dissemination,
4676 Columbia Parkway, Cincinnati, OH
45202. 513-533-8287.
General Information
Cone, James E. and Michael J. Hodgson,
MD, MPH. Problem Buildings: Build-
ing-Associated Illness and the Sick
Building Syndrome. 1989. From the
series "Occupational Medicine: State of
the Art Reviews." Hanley & Belfus, Inc.,
210 South 13th Street, Philadelphia, PA
19107.
Godish, Thad. Indoor Air Pollution
Control. 1989. Lewis Publishers, 121
South Main Street, Chelsea, MI 48118.
Rajhans, G.S., Report of the Inter-
ministerial Committee on Indoor Air
Quality, 1988. Contact: G. Rajhans,
Health and Safety Support Services
Branch, Ministry of Labour, 400 Univer-
sity Avenue, 7th Floor, Toronto, Ontario,
Canada M7A 1T7.
Sheet Metal and Air Conditioning
Contractor's National Association, Inc.
(SMACNA). Indoor Air Quality. 1988.
8224 Old Courthouse Road, Vienna,
Virginia 22180.
U.S. Environmental Protection Agency.
and the Public Health Foundation. Direc-
tory of State Indoor Air Contacts. Up-
dated, 1991. *
U.S. Environmental Protection Agency.
Designing for Good Indoor Air Quality:
An Introduction for Design Professionals.
(In progress).
U.S. Environmental Protection Agency.
Project Summaries: Indoor Air
Quality in Public Buildings. 1988.
Contains findings of research on IAQ in 10
new public and commercial buildings and
on building material emissions. *
U.S. Environmental Protection Agency
and the U.S. Consumer Product Safety
Commission. The Inside Story: A Guide
to Indoor Air Quality. 1988. Addresses
residential indoor air quality primarily, but
contains a section on offices. *
U.S. Environmental Protection Agency.
Sick Building Syndrome. Indoor Air
Quality Fact Sheet #4. Revised, 1991.*
U.S. Environmental Protection Agency.
Ventilation and Air Quality in Offices.
Indoor Air Quality Fact Sheet #3.
Revised, 1990.*
World Health Organization. Air Quality
Guidelines for Eiurope. 1987. WHO
Regional Publications, European Series No.
23. Available from WHO Publications
Center USA, 49 Sheridan Avenue, Albany,
NY 12210.
Asbestos
Keyes, Dale L. and Jean Chesson. A Guide
to Monitoring Airborne Asbestos in
Buildings. 1989. Environmental Sciences,
Inc., 105 E. Speedway Blvd., Tucson,
Arizona 85705.
U.S. Department of Health and Human
Services, Public Health Service, U.S.
Centers for Disease Control, National
Institute of Occupational Safety and
Health. Testimony of NIOSH on the
Occupational Safety and Health
Administration's Proposed Rule on
Occupational Exposure to Asbestos,
Tremolite, Anthophyllite, and Actinolite.
June 1984, May 1990, and January 1991.
NIOSH Docket Office, C-34, 4676 Colum-
164 Appendix G
-------
bia Parkway, Cincinnati, OH 45226.
U.S. Environmental Protection Agency. A
Guide to Respiratory Protection for the
Asbestos Abatement Industry. 1986. EPA
560/OTS 86-001. **
U.S. Environmental Protection Agency.
Abatement of Asbestos-Containing Pipe
Insulation. 1986. Technical Bulletin No.
1986-2. **
U.S. Environmental Protection Agency.
Asbestos Abatement Projects: Worker
Protection. Final Rule 40 CFR. 763.
February 1987. **
U.S. Environmental Protection Agency.
Asbestos Ban and Ph aseout Rule. 40
CFR 763.160 to 763.179. Federal Regis-
ter, July 12, 1989. **
U.S. Environmental Protection Agency.
Asbestos in Buildings: Guidance for
Service and Maintenance Personnel (in
English and Spanish). 1985. EPA 560/5-
85-018. ("Custodial Pamphlet"). **
U.S. Environmental Protection Agency.
Asbestos in Buildings: Simplified Sam-
pling Scheme for Surfacing Materials.
1985. 560/5-85-030A. ("Pink Book"). **
U.S. Environmental Protection Agency.
Guidance for Controlling Asbestos-
Containing Materials in Buildings. 1985.
EPA 560/5-85-024. ("Purple Book"). **
U.S. Environmental Protection Agency.
Guidelines for Conducting the AHERA
JEM Clearance Test to Determine
Completion of an Asbestos Abatement
Project, EPA 560/5-89-001. **
U.S. Environmental Protection Agency.
Managing Asbestos In Place: A Building
Owner's Guide to Operations and
Maintenance Programs for Asbestos-
Containing Materials, 1990. ("Green
Book").**
U.S. Environmental Protection Agency.
Measuring Airborne Asbestos Following
An Abatement Action. 1985. EPA 600/4-
85-049. ("Silver Book"). **
U.S. Environmental Protection Agency.
National Emission Standards for Hazard-
ous Air Pollutants. 40 Code of Federal
Regulation 61. April 1984.**
U.S. Environmental Protection Agency.
Transmission Electron Microscopy
Asbestos Laboratories: Quality Assurance
Guidelines. 1989. EPA 560/5-90-002.**
U.S. Department of Labor. OSHA Regula-
tions. 29 Code of Federal Regulation
1910.1001. General Industry Asbestos
Standard. 29 Code of Federal Regulation
1926.58. Construction Industry Asbestos
Standard. June 1986; Amended September
1988. DOL-OSHA Docket, 200 Constitu-
tion Avenue, NW, Room N 2625,
Washington, DC 20210
U.S. Department of Labor. OSHA Regula-
tions. 29 Code of Federal Regulation
1910.134 Respiratory Protection Stan-
dard. June 1974. DOL-OSHA Docket,
200 Constitution Avenue, NW, Room
N 2625, Washington, DC 20210
Biologicals
American Council of Governmental Indus-
trial Hygienists. Guidelines for the Assess-
ment of Bioaerosols in the Indoor Envir-
onment. 1989. 6500 Glenway Avenue,
Building D-7, Cincinnati, OH 45211.
Morey, P., J. Feeley, and J. Otten.
Biological Contaminants in Indoor
Environments. 1990. American Society
for Testing and Materials Publications,
1916 Race Street, Philadelphia, PA 19103.
Building Management, Investigation,
and Remediation
Bazerghi, Hani and Catherine Arnoult.
Practical Manual for Good Indoor Air
Quality. 1989. Quebec Association for
Energy Management. 1259 Berri Street,
Suite 510, Montreal, Quebec, Canada, H2L
4C7.
Hansen, Shirley 1., Managing Indoor Air
Quality. 1991. Fairmont Press, 700 Indian
Resources 165
-------
Trail, Lilburn, GA 30247.
U.S. Department of Health and Human
Services. Public Health Service. Centers
for Disease Control. National Institute for
Occupational Safety and Health. Indoor
Air Quality: Selected References.
1989.***
U.S. Department of Health and Human
Services. Public Health Service. Centers
for Disease Control. National Institute for
Occupational Safety and Health. Guid-
ance for Indoor Air Quality Investiga-
tions. 1987.***
Weekes, Donald M. and Richard B.
Gammage. The Practitioner's Approach
to Indoor Air Quality Investigations.
Proceedings of the Indoor Air Quality
International Symposium. 1989. American
Industrial Hygiene Association, P.O. Box
8390, Akron Ohio 44320.
Environmental Tobacco Smoke
National Research Council. Environmen-
tal Tobacco Smoke: Measuring Expo-
sures and Assessing Health Effects. 1986.
National Academy Press. 2001 Wisconsin
Avenue, NW, Washington, DC 20418.
U.S. Department of Health and Human
Services. Public Health Service. Office
on Smoking and Helath. The Health
Consequences of Involuntary Smoking,
A Report of the Surgeon General 1986.
1600 Clifton Road, NE (Mail Stop K50)
Atlanta, GA 30333.
U.S. Department of Health and Human
Services, Public Health Service. Centers
for Disease Control, National Institute for
Occupational Safety and Health. Current
Intelligence Bulletin 54: Environmental
Tobacco Smoke in the Workplace
Lung Cancer and Other Health Effects.
DHHS (NIOSH) Publication No. 91-108.
1991 ***
U.S. Department of Health and Human
Services, National Cancer Institute.
Office of Cancer Communications. A
series of one-page information sheets on
all aspects of smoking in the workplace.
For copies, call 1-800-4-CANCER.
U.S. Environmental Protection Agency.
Environmental Tobacco Smoke. Indoor
Air Quality Fact Sheet #5. 1989.*
U.S. Environmental Protection Agency.
Environmental Tobacco Smoke: A Guide
to the Development of Effective Smoking
Policies. (In progress.) *
U.S. Environmental Protection Agency.
Health Effects of Passive Smoking:
Assessment of Lung Cancer in Adults and
Respiratory Disorders in Children. (In
progress.) *
PCBs
U.S. Department of Health And Human
Services. Public Health Service. Centers
for Disease Control.. National Institute of
Occupational Safety and Health. Current
Intelligence Bulletin 45: Poly chlorinated
BiphenylsPotential Health Hazards
from Electrical Equipment Fires or
Failures . DHHS (NIOSH) Publication
No. 86-111. 1977. Available from the
National Technical Information Service,
5285 Port Royal Road, Springfield, VA
22161.
U.S. Department of Health and Human
Services. Public Health Service. Centers
for Disease Control. National Institute for
Occupational Safety and Health. A
Recommended Standard for Occupational
Exposure to Poly chlorinated Biphenyls
DHHS (NIOSH) Publication No. 77-225.
1977. Available from the National
Technical Information Service, 5285 Port
Royal Road, Springfield, VA 22161.
U.S. Environmental Protection Agency.
Transformers and the Risk of Fire: A
Guide for Building Owners. 1986. OP A/
86-001. **
Radon
U.S. Environmental Protection Agency.
166 Appendix G
-------
State Proficiency Report. 1991. EPA
520/1-94-014. Available from State
radon offices. List of laboratories that
have demonstrated com- petence in radon
measurement analysis.
Standards and Guidelines
American Conference of Government
Industrial Hygienists. Threshold Limit
Values and Biological Exposure Indices.
1990-1991. 6500 Glenway Avenue,
Building D-7, Cincinnati, OH 45211.
U.S. Department of Health and Human
Services. Public Health Service. Centers
for Disease Control. National Institute for
Occupational Safety and Health . NIOSH
Recommendations for Occupational
Safety and Health. Compendium of
Policy Documents and Statements.
DHHS (NIOSH) Publications 91-109.
1991.***
U.S. Department of Labor. OSHA
Rrgulations. 29 CFR Part 1910.1000.
OSHA Standards for Air Contaminants.
Available from the U.S. Government
Printing Office, Washington, DC 20402.
202-783-3238. Additional health
standards for some specific air contami-
nants are also available in Subpart Z.
Ventilation/Thermal Comfort
Brief descriptions of the ASHRAE
standards listed below are included in
Appendix B. ASHRAE materials are
available from their Publication Sales
Department, 1791 Tullie Circle, ME,
Atlanta, GA 30329. 404-636-8400.
ASHRAE Guideline 1-1989. Guideline
for the Commissioning ofHVAC
Systems. 1989.
ASHRAE Journal. October 1989 issue.
Several articles describing ASHRAE
Standard 62-1989.
ASHRAE Standard 52-76. Method of
Testing Air-Cleaning Devices Used in
General Ventilation for Removing
Particulate Matter. 1976.
ASHRAE Standard 55-1981. Thermal
Environmental Conditions for Human
Occupancy. 1981.
ASHRAE Standard 62-1989. Ventila-
tion for Acceptable Indoor Air Quality.
1989.
National Conference of States on Building
Codes and Standards, Inc. The Ventilation
Directory. 505 Huntmar Park Drive, Suite
210,Herndon, VA 22070. 703-481-2020.
Summarizes natural, mechanical, and
exhaust ventilation requirements of the
model codes, ASHRAE standards, and
unique State codes.
TRAINING
American Industrial Hygiene Associa-
tion (AIHA). P.O. Box 8390, 345 White
Pond Drive, Akron, OH 44320. 216-873-
2442. Sponsors indoor air quality courses
in conjunction with meetings for AIHA
members only.
American Society of Heating, Refriger-
ating, and Air-Conditioning Engineers
(ASHRAE). 1791 Tullie Circle NE,
Atlanta, GA 30329. 404-636-8400.
Sponsors professional development
seminars on indoor air quality.
NIOSH Division of Training and
Manpower Development and NIOSH-
funded Educational Resource Centers.
4676 Columbia Parkway, Cincinnati, OH
45226. 513-8221. Provide training to
occupational safety and health profession-
als and paraprofessionals.
OSHA Training Institute. 155 Times
Drive, Des Plaines, II 60018. 708-297-
4913. Provides courses to assist health
and safety professionals in evaluating
indoor air quality.
Resources 167
-------
Indoor Air Quality Forms
I his section of the document is a collec-
tion of the forms that appear or are men-
tioned in the text. Consider making copies
of the forms, blocking out the page infor-
mation at the bottom of the copies, and then
reproducing these copies for use in your
building. Some or all of them may require
adaptation to meet your specific needs.
Blank formatted sheets are included for
preparing your own HVAC Checklist and
Pollutant and Source Inventory.
The forms appear in the following
sequence:
Management Checklist: (4 pages): for
keeping track of the elements of the IAQ
profile and IAQ management plan.
Pollutant Pathway Record For IAQ
Profiles: for identifying areas in which
negative or positive pressures should be
maintained.
Zone/Room Record: for recording infor-
mation on a room-by-room basis on the
topics of room use, ventilation, and occu-
pant population.
Ventilation Worksheet: to be used in con-
junction with the Zone/Room Record when
calculating quantities of outdoor air that are
being supplied to individual zones or rooms.
IAQ Complaint Form: to be filled out by
the complainant or by a staff person who
receives information from the complainant.
Incident Log: for keeping track of each
IAQ complaint or problem and how it is
handled.
Occupant Interview (2 pages): for record-
ing the observations of building occupants
in relation to their symptoms and condi-
tions in the building.
Occupant Diary: for recording incidents
of symptoms and associated observations
as they occur.
Log of Activities and System Operation:
for recording activities and equipment
operating schedules as they occur.
HVAC Checklist - Short Form (4 pages):
to be used as a short form for investigating
an IAQ problem, or for periodic inspec-
tions of the HVAC system. Duplicate
pages 2 through 4 for each large air han-
dling unit.
HVAC Checklist - Long Form (14 pages,
followed by one blank formatted sheet):
to be used for detailed inspections of the
HVAC system or as a long form for inves-
tigating an IAQ problem. Duplicate pages
1 through 11 for each large air handling
unit.
Pollutant Pathway Form For
Investigations: to be used in conjunction
with a floor plan of the building.
Pollutant and Source Inventory (6 pages,
followed by one blank formatted sheet):
to be used as a general checklist of poten-
tial indoor and outdoor pollutant sources.
Chemical Inventory: for recording
information about chemicals stored or
used within the building.
Hypothesis Form: to be used for
summarizing what has been learned during
the building investigation, a tool to help
the investigator collect his or her thoughts.
Indoor Air Quality Forms 169
-------
Building Air Quality
linn
mill
HUH
Printed on Recycled Paper
-------
IAQ Management Checklist
Page 1 of4
Building Name:
Address:
Date:.
Completed by (name/title):
Use this checklist to make sure that you have included all necessary elements in your IAQ profile and
IAQ management plan. Sections 4 and 5 discuss the development of the IAQ profile and IAQ management plan.
Item
IAQ PROFILE
Collect and Review Existing
IVUUUIVJs
HVAC design data, operating
instructions and manuals
HVAC maintenance and calibration
records, testing and balancing reports
Inventory of locations where occu-
pancy, equipment, or building use has
changed
Inventory of complaint locations
CVmkr£ a VUdlctf-vnfii
I-iwvuitfvtw-riHil. -_f iim-i Ph JljBmma
IbptJCtlCllOl in& tJUICIrK|
List of responsible staff and/or contrac-
tors, evidence oftraining,
and job descriptions
Identification of area where
positive or negative pressure
should be maintained
Record of locations that need
monitoring or correction
UOMtid IJrHraieg II ! rBUGTI
Inventory of HVAC system
components needing repair, adjustment,
or replacement
Record of control settings and operating
schedules
Date begun
or completed
(as applicable)
Responsible person
(name, telephone)
Location
("NA" if the item is not
applicable to this building)
Indoor Air Quality Forms 1T1
-------
IAQ Management Checklist
Page 2 of 4
Item
Plan showing airflow directions or
pressure differentials in significant
areas
Inventory of significant polluntant
sources and their locations
MSDSs for supplies and
hazardous substances that are
stored or used in the building
Zone/Room Record
Date begun
or completed
(as applicable)
Responsible person
(name, telephone)
Location
("NA" if the item is not
applicable to this building)
lAQIVniUAGEIVENT PLAN
select i/o-t ivBnagsr
ReuiewlAQ Profile
Assicpi Staff Responsibilities/
Train Staff
Facilities Operation and Maintenance
confirm that equipment operating
schedules are appropriate
confirm appropriate pressure relation-
ships between building
usage areas
compare ventilation quantities to
design, codes, and ASHRAE 62-1989
schedule equipment inspections
per preventive maintenance or recom-
mended maintenance schedule
modify and use HVAC Checklist(s);
update as equipment is added, re-
moved, or replaced
schedule maintenance activities to
avoid creating IAQ problems
HTZIndoor Air Quality Forms
-------
IAQ Management Checklist
Page 3 of 4
Item
review MSDSs for supplies; request
additional information as needed
consider using alarms or other devices
to signal need for HVAC maintenance
(e.g., clogged filters)
Housekeeping
evaluate cleaning schedules and
procedures; modify if necessary
review MSDSs for products in use; buy
different products if necessary
confirm proper use and storage of
materials
review trash disposal procedures;
modify if necessary
Shipping and Receiving
review loading dock procedures
(Note: If air intake is located nearby,
take precautions to prevent intake of
exhaust fumes.)
check pressure relationships around
loading dock
Pest Control
consider adopting IPM methods
obtain and review MSDSs; review
handling and storage
review pest control schedules and
procedures
review ventilation used during
pesticide application
Date begun
or completed
(as applicable)
Responsible person
(name, telephone)
Location
("NA" if the item is not
applicable to this building)
Indoor Air Quality Forms 173
-------
IAQ Management Checklist
Page 4 of 4
Item
Occupant Relations
establish health and safety committee
or joint tenant/
management IAQ task force
review procedures for responding
to complaints; modify if necessary
review lease provisions; modify
if necessary
Renovation, Redecorating,
Remodeling
discuss IAQ concerns with
architects, engineers, contractors,
and other professionals
obtain MSDSs; use materials
and procedures that minimize
IAQ problems
schedule work to minimize
IAQ problems
arrange ventilation to isolate
work areas
use installation procedures
that minimize emissions from
new furnishings
Smoking
eliminate smoking in the building
if smoking areas are designated,
provide adequate ventilation and
maintain under negative pressure
work with occupants to develop
appropriate non-smoking policies,
including implementation
of smoking cessation programs
Date begun
or completed
(as applicable)
Responsible person
(name, telephone)
Location
("NA" if the item is not
applicable to this building)
174/wrfoor Air Quality Forms
-------
This form should be used in combination with a floor plan such as a fire evacuation plan.
Building Name: File Number:
Address:
Completed by:_
Title:
Date:
Sections 2, 4 and 6 discuss pollutant pathways and driving forces.
Building areas that contain contaminant sources (e.g., bathrooms, food preparation areas, smoking lounges, print rooms, and
art rooms) should be maintained under negative pressure relative to surrounding areas. Building areas that need to be
protected from the infiltration of contaminants (e.g., hallways in multi-family dwellings, computer rooms, and lobbies) should be
maintained under positive pressure relative to the outdoors and relative to surrounding areas.
List the building areas in which pressure relationships should be controlled. As you inspect the building, put a Y or N in the
"Needs Attention" column to show whether the desired air pressure relationship is present. Mark the floor plan with arrows,
plus signs (+) and minus signs (-) to show the airflow patterns you observe, using chemical smoke or a micromanometer.
Building areas that appear isolated from each other may be connected by airflow passages such as air distribution zones,
utility tunnels or chases, party walls, spaces above suspended ceilings (whether or not those spaces are serving as air
plenums), elevator shafts, and crawlspaces. If you are aware of pathways connecting the room to identified pollutant sources
(e.g., items of equipment, chemical storage areas, bathrooms), it may be helpful to record them in the "Comments" column, on
the floor plan, or both.
Building Area
(zone, room)
Use
Intended Pressure
Positive
(+)
Negative
(-)
Needs
Attention?
(Y/N)
Comments
Indoor Air Quality Forms 175
-------
Building Name:
Address:
File Number:
Completed by:
Date:
Title:
This form is to be used differently depending on whether the goal is to prevent or to diagnose IAQ problems. During the development of a profile, this form should be used
to record more general information about the entire building; during an investigation, the form should be used to record more detailed information about the complaint area
and areas surrounding the complaint area or connected to it by pathways.
Use the last three columns when underventilation is suspected. Use the Vertilaticn Worksheet and Appendix A to estimate outdoor air quantities
Compare results to the design specifications, applicable building codes, or ventilation guidelines such as ASHRAE 62-1989. (See Appendix A for some outdoor air
quantities required by ASHRAE 62-1989.) Note: For VAV systems, minimum outdoor air under reduced flow conditions must be considered.
PROFILE AND DIAGNOSIS INFORMATION
Building Area
(Zone/Room)
Use"
Source of
Outdoor Air*
Mechanical
Exhaust?
(Write "No"
or estimate
cfm airflow)
Comments
DIAGNOSIS INFORMATION ONLY
Peak Number of
Occupants or
Sq. Ft. Floor Area**
Total Air
Supplied
(in cfm)***
Outdoor Air Supplied
per Person or
per 150 Sq. Ft. Area
(in cfm)****
* Sources might include air handling unit (e.g., AHU-4), operable windows, transfer from corridors.
** Underline the information in this column if corrent use or number of occupants is different from design specifications.
*** Mark the information with a Pif it comes from the mechanical plans or an IVif it comes from actual measurements, such as
recent test and balance reports.
**** ASHRAE 62-1 989 gives ventilation guidance per 150 sq. ft.
to
s
a
-------
Building Name:
Address:
File Number:
Completed by (name):_
Date:
This worksheet is designed for use with the Zone/Room Record. Appendix A provides guidance on methods of estimating
the amount of ventilation (outdoor) air being introduced by a particular air handling unit. Appendix B discusses the
ventilation recommendations of ASHRAE Standard 62-1989, which was developed for the purpose of preventing indoor
air quality problems. Formulas are given below for calculating outdoor air quantities using thermal or CO2 information.
The equation for calculating outdoor air quantities LBing thermal ireasLrerrerfts is:
Outdoor air (in percent) =
return air mixed air
return air outdoor air
x100
Where: T = temperature in degrees Fahrenheit
The equation for calculating outdoor quantities LBing carbon deride
us:
Outdoor air (in percent) =
VCr
x100
Where: Cs= ppm of carbon dioxide in the supply air (if measured in a room), or
Cs= ppm of carbon dioxide in the mixed air (if measured at an air handler)
Cr= ppm of carbon dioxide in the return air
Co= ppm of carbon dioxide in the outdoor air
Using the table below to estimate the ventilation rate in any room or zone. Note: ASHRAE 62-1989 generally states ventilation
(outdoor air) requirements on an occupancy basis; for a few types of spaces, however, requirements are given on a floor area
basis. Therefore, this table provides a process of calculating ventilation (outdoor air) on either an occupancy or floor area
basis.
Zone/Room
Percent of
Outdoor Air
A
Total Air
Supplied to
Zone/Room
(cfm)
B
Peak Occupancy
(number of people)
or
Floor Area
(square feet)
C
D=A
c
Total Air
Supplied Per Person
(or per square foot area)
D
E = (Ax1 00) x D
Outdoor Air
Supplied Per Person
(or per square foot area)
E
Air Ounlitv
-------
Indoor Air Quality Complaint Form
This form can be filled out by the building occupant or by a member of the building staff.
Occupant Name: Date:
Department/Location in Building:
Completed by:
Title:
Phone:
Phone:
This form should be used if your complaint may be related to indoor air quality. Indoor air quality problems include concerns
with temperature control, ventilation, and air pollutants. Your observations can help to resolve the problem as quickly as
possible. Please use the space below to describe the nature of the complaint and any potential causes.
We may need to contact you to discuss your complaint. What is the best time to reach you?_
So that we can respond promptly, please return this form to:
IAQ Manager or Contact Person
Room, Building, Mail Code
OFFICE USE ONLY
File Number:
Received By:
Date Received:
Indoor Air Quality Forms 181
-------
C8 ! suuoj fytjrmQ My joopuj
z
CT if
CD
D
0)
of
r~ TJ
o o
a> o"
II
Complaint
Form
Occupant
Interview
Occupant
Diary
Log of
Activities
Zone/Room
Record
HVAC
Checklist
Pollutant
Pathway
Source
Inventory
Hypothesis
Form
"o"
31
CD
O
^
S?
"a
O?
it
9§
fil -PI
"S?
^- CD
S 0
CD O
s a
c
If
CD
Q.
O
£
o
o
1
o
o
3
|
1
V)
"c"
8
3
0
CD
p+
3"
01
o
5'
CD
^i
=
cl
Q.
CD
|-
1m
S. 3
K->3
~ 00
Q.
Q.
CD
cn
en
CD
.
Q)
CD
O
O
3
-
CD
Q.
Q)
CD
CD
cn
o
3
-------
Irtterview page /
Building Name: File Number:
Address:
Occupant Name: Work Location:
Completed by: Title: Date:_
Sections 4 discusses collecting and interpreting information from occupants.
SYIVPTCMRATTERNS
What kind of symptoms or discomfort are you experiencing?
Are you aware of other people with similar symptoms or concerns? Yes No
If so, what are their names and locations?
Do you have any health conditions that may make you particularly susceptible to environmental problems?
Q contact lenses Q chronic cardiovascular disease Q undergoing chemotherapy or radiation therapy
Q allergies Q chronic respiratory disease Q immune system suppressed by disease or
other causes
Q chronic neurological problems
TIMIMG PATTERNS
When did your symptoms start?
When are they generally worst?
Do they go away? If so, when?
Have you noticed any other events (such as weather events, temperature or humidity changes, or activities in the building) that
tend to occur around the same time as your symptoms?
Indoor Air Quality Forms 1
-------
I rtterview page 2 of 2
SPATIAL PATTERNS
Where are you when you experience symptoms or discomfort?
Where do you spend most of your time in the building?
ADDITIONAL INFORMATION
Do you have any observations about building conditions that might need attention or might help explain your symptoms (e.g.,
temperature, humidity, drafts, stagnant air, odors)?
Have you sought medical attention for your symptoms?
Do you have any other comments?
Indoor Air Quality Forms 1
-------
Occupant Name:_
Location:
Title:
Phone:
File Number:
On the form below, please record each occasion when you experience a symptom of ill-health or discomfort that you think
may be linked to an environmental condition in this building.
It is important that you record the time and date and your location within the building as accurately as possible,
because that will help to identify conditions (e.g., equipment operation) that may be associated with your problem.
Also, please try to describe the severity of your symptoms (e.g., mild, severe) and their duration (the length of time that they
persist). Any other observations that you think may help in identifying the cause of the problem should be noted
in the "Comments" column. Feel free to attach additional pages or use more than one line for each event if you need more
room to record your observations.
Section 6 discusses collecting and interpreting occupant information.
Time/Date
Location
Symptom
Severity/Duration
Comments
Indoor Air Quality Forms 187
-------
Building Name:
Completed by:_
Address:
Title:
File Number:_
Phone:
On the form below, please record your observations of the HVAC system operation, maintenance activities, and any other
information that you think might be helpful in identifying the cause of IAQ complaints in this building. Please
report any other observations (e.g., weather, other associated events) think may be important as well.
Feel free to attach additional pages or use more than one line for each event.
Equipment and activities of particular interest:
Air Handler(s):
Exhaust Fan(s):
Other Equipmer
Date/Time
t or Activities:
Day of Week
Equipment Item/Activity
Observations/Comments
Indoor Air Quality Forms 189
-------
HVAC Checklist - Short Form
Building Name: Address:
Page 7 of 4
Completed by: Date: File Number:
Sections 2, 4 and 6 and Appendix B discuss the relationships between the HVAC system and indoor air quality.
MECHANICAL ROOM
Clean and dry? Stored refuse or chemicals?.
Describe items in need of attention
MAJOR MECHANICAL EQUIPMENT
Preventive maintenance (PM) plan in use?
Control System
Type
System operation
Date of last calibration
Boilers
Rated Btu input Condition
Combustion air: is there at least one square inch free area per 2,000 Btu input?
Fuel or combustion odors
Cooling Tower
Clean? no leaks or overflow? Slime or algae growth?.
Eliminator performance
Biocide treatment working? (list type of biocide)
Spill containment plan implemented? Dirt separator working?
Chillers
Refrigerant leaks?
Evidence of condensation problems?.
Waste oil and refrigerant properly stored and disposed of?
191 Indoor Air Quality Forms
-------
HVAC Checklist - Short Form
Building Name: Address:
Page 2 of 4
Completed by: Date: File Number:
AIR HANDLING UNIT
Unit identification Area served .
Outdoor Air Intake, Mixing Plenum, and Damper
Outdoor air intake location
Nearby contaminant sources? (describe)
Bird screen in place and unobstructed? _
Design total cfm outdoor air (O.A.) cfm date last tested and balanced.
Minimum % O.A. (damper setting) Minimum cfm O.A. (total cfm x minimum % O.A.) =
Current O.A. damper setting (date, time, and HVAC operating mode)
Damper control sequence (describe)
ite)
itures supply air
es supply air
mixed air return air
mixed air return air
outdoor air
outdoor air
Condition of dampers and controls (note date)
Fans
Control sequence
Condition (note date)
Indicated temperatures
Actual temperatures
Coils
Heating fluid discharge temperature AT cooling fluid discharge temperature AT_
Controls (describe)
Condition (note date)
Humidifier
Type if biocide is used, note type
Condition (no overflow, drains trapped, all nozzles working?)
No slime, visible growth, or mineral deposits?
Indoor Air Quality Forms 192
-------
HVAC Checklist - Short Form
Building Name: Address:
Completed by: Date:
Page 3 of 4
File Number:
DISTRIBUTION SYSTEM
Zone/
Room
System
Type
Supply Air
ducted/
unducted
cfm*
Return Air
ducted/
unducted
cfm*
Power Exhaust
cfm*
control
serves
(e.g. toilet)
Condition of distribution system and terminal equipment (note locations of problems)
Adequate access for maintenance?
Ducts and coils clean and obstructed? .
Air paths unobstructed? supply _
return
transfer.
exhaust
make-up
Note locations of blocked air paths, diffusers, or grilles
Any unintentional openings into plenums?
Controls operating properly?
Air volume correct?
Drain pans clean? Any visible growth or odors?
Filters
Location
Type/Rating
Size
Date Last Changed
Condition (give date)
193 Indoor A ir Quality Forms
-------
HVAC Checklist - Short Form
Page 4 of 4
Building Name:
Completed by: _
Address:
Date:
File Number:
OCCUPIED SPACE
Zone/
Room
Thermostat
Location
What Does
Thermostat
Control?
(e.g., radiator,
AHU-3)
Setpoints
Summer
Winter
Measured
Temperature
Day/
Time
Zone/
Room
Humidistat/
Dehumidistat
Location
What Does It
Control?
Setpoints
(%RH)
Measured
Temperature
Day/
Time
Potential problems (note location)
Thermal comfort or air circulation (drafts, obstructed airflow, stagnant air, overcrowding, poor
thermostat location)
Malfunctioning equipment
Major sources of odors or contaminants (e.g., poor sanitation, incompatible uses of space)
Indoor Air Quality Forms 194
-------
HVAC Checklist - Long Form
Page 7 of 14
Building:
File Number:
Completed by:.
Title:
Date Checked:
Appendix B discusses HVAC system components in relation to indoor air quality.
Component
OK
Needs
Attention
Not
Applicable
Comments
Outside Air Intake
I nnatinn
Open during occupied hours?
Unobstructed?
Standing water, bird droppings
in vicinity?
Odors from outdoors?
(rtpsrrihp)
Carryover of exhaust heat?
Cooling tower within 25 feet?
Exhaust outlet within 25 feet?
Trash compactor within 25 feet?
Near parking facility, busy road,
loading dock?
Bird Screen
Unobstructed?
General condition?
Size of mesh? (W minimum)
Outside Air Dampers
Operation acceptable?
Seal when closed?
Indoor Air Quality Forms 195
-------
HVAC Checklist - Long Form
Page 2 of 14
Building:.
Completed by:
File Number:
Title:
Date Checked:
Component
Actuators operational?
OK
Needs
Attention
Not
Applicable
Comments
Outdoor Air (O.A.) Quantity
(Check against applicable codes
andASHRAE 62-1989.)
Minimum % O.A.
Measured % O.A.
Note day, time, HVAC operating modt
under "Comments"
Maximum % O.A.
Is minimum O.A. a separate damper?
For VAV systems: is O.A. increased as
total system air-flow is reduced?
Mixing Plenum
Clean?
Floor drain trapped?
Airtightness
of outside air dampers
of return air dampers
of exhaust air dampers
All damper motors connected?
All damper motors operational?
Air mixers or opposed blades?
196 Indoor A ir Quality Forms
-------
HVAC Checklist - Long Form
Page 3 of 14
Building:.
Completed by:
File Number:
Title:
Date Checked:
Component
Mixed air temperature control
setting °F
Freeze star setting °F
Is mixing plenum under negative
pressure? Note: If it is under
positive pressure, outdoor air
may not be entering.
OK
Needs
Attention
Not
Applicable
Comments
Filters
Type
Complete coverage?
(i.e., no bypassing)
Correct pressure drop? (Compare to
manufacturer's recommendations.)
Contaminants visible?
Odor noticeable?
Spray Humidifiers or
Air Washers
Humidifier type
All nozzles working?
Complete coil coverage?
Pans clean, no overflow?
Drains trapped?
Biocide treatment working?
A/nfp- /.<; /W.SD.S nn filp.7
Spill contaminant system in place?
Indoor Air Quality Forms 197
-------
HVAC Checklist - Long Form
Page 4 of14
Building:
Completed by:.
File Number:
Title:
Date Checked:
Component
OK
Needs
Attention
Not
Applicable
Comments
Face and Bypass Dampers
Damper operation correct?
Damper motors operational?
Cooling Coil
Inspection access?
Clean?
Supply water temp °F
Water carryover?
Any indication of condensation
problems?
Condensate Drip Pans
Accessible to inspect and clean?
Clean, no residue?
No standing water, no leaks?
Noticeable odor?
Visible growth (e.g., slime)?
Drains and traps clear, working?
Trapped to air gap?
Water overflow?
198 Indoor A ir Quality Forms
-------
HVAC Checklist - Long Form
Page 5 of 14
Building:
Completed by:.
File Number:
Title:
Date Checked:
Component
OK
Needs
Attention
Not
Applicable
Comments
Mist Eliminators
Clean, straight, no carryover?
Supply Fan Chambers
Clean?
No trash or storage?
Floor drain traps are wet or sealed?
No air leaks?
Doors close tightly?
Supply Fans
1 nnatinn
Fan blades clean?
Belt guards installed?
Proper belt tension?
Excess vibration?
Corrosion problems?
Controls operational, calibrated?
Indoor Air Quality Forms 199
-------
HVAC Checklist - Long Form
Page 6 of 14
Building:.
Completed by:
File Number:
Title:
Date Checked:
Component
Control sequence conforms
to design/specifications?
(describe changes)
No pneumatic leaks?
OK
Needs
Attention
Not
Applicable
Comments
Heating Coil
Inspection access?
Clean?
Contol sequence conforms to
design/specifications?
(describe changes)
Supply water temp. °F
Discharge thermostat?
(air temp, setting °R
Reheat Coils
Clean?
Obstructed?
Operational?
Steam Humidifier
Humidifier type
Treated boiler water
Standing water?
200 Indoor A ir Quality Forms
-------
HVAC Checklist - Long Form
Page 7 of 14
Building:
Completed by:.
File Number:
Title:
Date Checked:
Component
Visible growth?
Mineral deposits?
Control setpoint °F
High limit setpoint °F
Duct liner within 12 feet? (If so,
check for dirt, mold growth.)
OK
Needs
Attention
Not
Applicable
Comments
Supply Ductwork
Clean?
Sealed, no leaks, tight connections?
Fire dampers open?
Access doors closed?
Lined ducts?
Flex duct connected, no tears?
Light troffer supply?
Balanced within 3-5 years?
Balanced after recent renovations?
Short circuiting or other air
distribution problems? Note
location(s)
Pressurized Ceiling
Supply Plenum
No unintentional openings?
All ceiling tiles in place?
Indoor Air Quality Forms 201
-------
HVAC Checklist - Long Form
Page 8 of 14
Building:.
File Number:
Completed by:
Title:
Date Checked:
Component
Barrier paper correctly placed and
in good condition?
Proper layout for air distribution?
Supply diffusers open?
Supply diffusers balanced?
Noticeable flow of air?
Short circuiting or other air
distribution problems? Note
location(s) in "Comments"
OK
Needs
Attention
Not
Applicable
Comments
Terminal Equipment (supply)
Housing interiors clean and unob-
structed?
Controls working?
Delivering rated volume?
Balanced within 3-5 years?
Filters in place?
Condensate pans clean, drain
freely?
VAV Box
Minimum stops %
Minimum outside air %
(from page 2 of this form)
Minimum airflow cfm
Minimum outside air cfm
202 Indoor A ir Quality Forms
-------
HVAC Checklist - Long Form
Page 9 of 14
Building:.
File Number:
Completed by:
Title:
Date Checked:
Component
Supply setpoint °F (summer)
°F (winter)
OK
Needs
Attention
Not
Applicable
Comments
Thermostats
Type
Properly located?
Working?
Setpnints °F (summer)
°F (winter)
Spare temperature °F
Humidity Sensor
Humiriistat setpoints % RH
nehiimiirlistat setpnints % RH
Actual RH %
Room Partitions
Gap allowing airflow at top?
Gap allowing airflow at bottom?
Supply, return each room?
Indoor Air Quality Forms 203
-------
HVAC Checklist - Long Form
Page 10 of 14
Building:.
Completed by:
File Number:
Title:
Date Checked:
Component
OK
Needs
Attention
Not
Applicable
Comments
Stairwells
Doors close and latch?
No openings allowing
uncontrolled airflow?
Clean, dry?
No noticeable odors?
Return Air Plenum
Tiles in place?
No unintentional openings?
Return grilles?
Balancing capability?
Noticeable flow of air?
Transfer grilles?
Fire dampers open?
Ducted Returns
Balanced within 3-5 years?
Unobstructed grilles?
Unobstructed return air path?
Return Fan Chambers
Clean and no trash or storage?
No standing water?
Floor drain traps are wet or sealed?
204 Indoor A ir Quality Forms
-------
HVAC Checklist - Long Form
Page 11 of 14
Building:
Completed by:.
File Number:
Title:
Date Checked:
Component
No air leaks?
Doors close tightly, kept closed?
OK
Needs
Attention
Not
Applicable
Comments
Return Fans
Location
Fan blades clean?
Belt guards installed?
Proper belt tension?
Excess vibration?
Corrosion problems?
Controls working, calibrated?
Controls sequence conforms to
design/specifications?
(describe changes)
Exhaust Fans
Central?
Distributer! (locations)
Operational?
Controls operational?
Toilet exhaust only?
Gravity relief?
Indoor Air Quality Forms 205
-------
HVAC Checklist - Long Form
Page 12 of 14
Building:.
Completed by:
File Number:
Title:
Date Checked:
Component
Total pnwereri exhaust cfm
Make-up air sufficient?
OK
Needs
Attention
Not
Applicable
Comments
Toilet Exhausts
Fans working occupied hours?
Registers open, clear?
Make-up air path adequate?
Volume according to code?
Floor drain traps wet or scalable?
Bathrooms run slightly negative rela-
tive to building?
Smoking Lounge Exhaust
Room runs negative relative to
building?
Print Room Exhaust
Room runs negative relative
to building?
Garage Ventilation
Operates according to codes?
Fans, controls, dampers all operate?
206 Indoor A ir Quality Forms
-------
HVAC Checklist - Long Form
Page 13 of 14
Building:
Completed by:.
File Number:
Title:
Date Checked:
Component
Garage slightly negative relative
to building?
Doors to building close tightly?
Vestibule entrance to building
from garage?
OK
Needs
Attention
Not
Applicable
Comments
Mechanical Rooms
General condition?
Controls operational?
Pneumatic controls:
compressor operational?
air dryer operational?
Electric contols?
EMS (Energy Management System) o
DDC (Direct Digital Control):
operator on site?
controlled off-site?
are fans cycled "off" while
building is occupied?
is chiller reset to shed load?
Preventive Maintenance
Spare parts inventoried?
Spare air filters?
Control drawing posted?
Indoor Air Quality Forms 207
-------
HVAC Checklist - Long Form
Page 14 of 14
Building:
Completed by:.
File Number:
Title:
Date Checked:
Component
PM (Preventive Maintenance)
schedule available?
PM followed?
OK
Needs
Attention
Not
Applicable
Comments
Boilers
Flues, breeching tight?
Purge cycle working?
Door gaskets tight?
Fuel system tight, no leaks?
Combustion air: at least 1 square
inch free area per 2000 Btu input?
Cooling Tower
Sump clean?
No leaks, no overflow?
Eliminators working, no carryover?
No slime or algae?
Biocide treatment working?
Dirt separator working?
Chillers
No refrigerant leaks?
Purge cycle normal?
Waste oil, refrigerant properly
disposed of and spare refrigerant
properly stored?
Condensation problems?
208 Indoor A ir Quality Forms
-------
HVAC Checklist - Long Form
Page of_
Building:.
Completed by:
File Number:
Title:
Date Checked:
Component
OK
Needs
Attention
Not
Applicable
Comments
Indoor Air Quality Forms 209
-------
Inuestioations
Building Name:
Address:
File Number:
Completed by:
This form should be used in combination with a floor plan such as a fire evacuation plan.
Building areas that appear isolated from each other may be connected by airflow passages such as air distribution zones,
utility tunnels or chases, party walls, spaces above suspended ceilings (whether or not those spaces are serving as air ple-
nums), elevator shafts, and crawl spaces.
Describe the complaint area in the space below and mark it on your floor plan. Then list rooms or zones connected to the
complaint area by airflow pathways. Use the form to record the direction of air flow between the complaint area and the
connected rooms/zones, including the date and time. (Airflow patterns generally change overtime). Mark the floor plan with
arrows or plus (+) and minus (-) signs to map out the airflow patterns you observe, using chemical smoke or a
micromanometer. The "comments" column can be used to note pollutant sources that merit further attention.
Rooms or zones included in the complaint area:
Sections 2, 4 and 6 discuss pollutant pathways and driving forces.
Rooms or Zones
Connected to the
Complaint Area
By Pathways
Use
Pressure Relative to
Complaint Area
+/-
date/time
Comments (e.g., potential pollutant sources)
-------
Page 1of6
Building Name:
Completed by: _
Address:
Date:
File Number:
Using the list of potential source categories below, record any indications of contamination or suspected pollutants that may
require further investigation or treatment. Sources of contamination may be constant or intermittent or may be linked to single,
unrepeated events. For intermittent sources, try to indicate the time of peak activity or contaminant production, including
correlations with weather (e.g., wind direction).
Sections 2, 4 and 6 discuss pollutant sources. Appendix A provides guidance on common measurements.
Source Category
Checked
Needs
Attention
Location
Comments
SOURCES OUTSIDE BUILDING
Contaminated Ambient Air
Pollen, dust
Industrial contaminants
General vehicular contaminants
Emissions from Nearby Sources
Vehicle exhaust (parking areas,
loading docks, roads)
Dumpsters
Re-entrained exhaust
Debris near outside air intake
Soil Gas
Radon
Leaking underground tanks
Sewage smells
Pesticides
Indoor Air Quality Forms 213
-------
Page 2 of 6
Building Name:
Completed by: _
Address:
Date:
File Number:
Using the list of potential source categories below, record any indications of contamination or suspected pollutants that may
require further investigation or treatment. Sources of contamination may be constant or intermittent or may be linked to single,
unrepeated events. For intermittent sources, try to indicate the time of peak activity or contaminant production, including
correlations with weather (e.g., wind direction).
Source Category
Checked
Needs
Attention
Location
Comments
Moisture or Standing Water
Rooftop
Crawlspace
EQUIPMENT
HVAC System Equipment
Combustion gases
Dust, dirt, or microbial growth
in ducts
Microbial growth in drip pans,
chillers, humidifiers
Leaks of treated boiler water
Non HVAC System Equipment
Office equipment
Supplies for equipment
Labratory equipment
Indoor Air Quality Forms 214
-------
Page 3 of 6
Building Name:
Completed by: _
Address:
Date:
File Number:
Using the list of potential source categories below, record any indications of contamination or suspected pollutants that may
require further investigation or treatment. Sources of contamination may be constant or intermittent or may be linked to single,
unrepeated events. For intermittent sources, try to indicate the time of peak activity or contaminant production, including
correlations with weather (e.g., wind direction).
Source Category
Checked
Needs
Attention
Location
Comments
HUMAN ACTIVITIES
Personal Activities
Smoking
Cosmetics (odors)
Housekeeping Activities
Cleaning materials
Cleaning procedures (e.g., dust
from sweeping, vacuuming)
Stored supplies
Stored refuse
Maintenance Activities
Use of materials with volatile
compunds (e.g., paint, caulk,
adhesives)
Stored supplies with volatile
compounds
Use of pesticides
Indoor Air Quality Forms 215
-------
Page 4 of 6
Building Name:
Completed by: _
Address:
Date:
File Number:
Using the list of potential source categories below, record any indications of contamination or suspected pollutants that may
require further investigation or treatment. Sources of contamination may be constant or intermittent or may be linked to single,
unrepeated events. For intermittent sources, try to indicate the time of peak activity or contaminant production, including
correlations with weather (e.g., wind direction).
Source Category
Checked
Needs
Attention
Location
Comments
BUILDING COMPONENTS/FURNISHINGS
Locations Associated with Dust or Fibers
Dust-catching area
(e.g., open shelving)
Deteriorated furnishings
Asbestos-containing materials
Unsanitary Conditions/Water Damage
Microbial growth in or on soiled
or water-damaged furnishings
Indoor Air Quality Forms 216
-------
Page 5 of 6
Building Name:
Completed by: _
Address:
Date:
File Number:
Using the list of potential source categories below, record any indications of contamination or suspected pollutants that may
require further investigation or treatment. Sources of contamination may be constant or intermittent or may be linked to single,
unrepeated events. For intermittent sources, try to indicate the time of peak activity or contaminant production, including
correlations with weather (e.g., wind direction).
source Category
Checked
Needs
Attention
Location
Comments
Chemicals Released From Building Components or Furnishings
Volatile compounds
OTHER SOURCES
Accidental Events
Spills (e.g., water, chemicals,
beverages)
Water leaks or flooding
Fire damage
Indoor Air Quality Forms 217
-------
Page 6 of 6
Building Name:
Completed by: _
Address:
Date:
File Number:
Using the list of potential source categories below, record any indications of contamination or suspected pollutants that may
require further investigation or treatment. Sources of contamination may be constant or intermittent or may be linked to single,
unrepeated events. For intermittent sources, try to indicate the time of peak activity or contaminant production, including
correlations with weather (e.g., wind direction).
Source Category
Checked
Needs
Attention
Location
Comments
Special Use/Mixed Use Areas
Smoking lounges
Food preparation areas
Underground or attached
parking garages
Laboratories
Print shops, art rooms
Exercise rooms
Beauty salons
Redecorating/Repair/Remodeling
Emissions from new furnishings
Dust, fibers from demolition
Odors, volatile compounds
Indoor Air Quality Forms 218
-------
Page of
Building Name:
Completed by: _
Address:
Date:
File Number:
Using the list of potential source categories below, record any indications of contamination or suspected pollutants that may
require further investigation or treatment. Sources of contamination may be constant or intermittent or may be linked to single,
unrepeated events. For intermittent sources, try to indicate the time of peak activity or contaminant production, including
correlations with weather (e.g., wind direction).
Sections 2, 4 and 6 discuss pollutant sources. Appendix A provides guidance on common measurements.
Source Category
Checked
Needs
Attention
Location
Comments
Indoor Air Quality Forms 219
-------
Chemical Inventory
Building Name:
Address:
File Number:
Completed by:
Phone:
The inventory should include chemicals stored or used in the building for cleaning, maintenance, operations, and pest
control. If you have an MSDS (Material Safety Data Sheet) for the chemical, put a check mark in the right-hand column.
If not, ask the chemical supplier to provide the MSDS, if one is available.
Sections 2 and 6 discuss pollutant sources. Section 4 discusses MSDSs.
Date
Chemical/Brand Name
Use
Storage Location(s)
MSDS on file?
Indoor Air Quality Forms 221
-------
Hypothesis Form page 7 Of2
Building Name: File Number:
Address:
Completed by:
Complaint Area (may be revised as the investigation progresses):
Complaints (e.g., summarize patterns of timing, location, number of people affected):
HVAC: Does the ventilation system appear to provide adequate outdoor air, efficiently distributed to meet occupant needs
in the complaint area? If not, what problems do you see?
Is there any apparent pattern connecting the location and timing of complaints with the HVAC system layout, condition or
operating schedule?
Pathways: What pathways and driving forces connect the complaint area to locations of potential sources?
Are the flows opposite to those intended in the design?
Sources: What potential sources have been identified in the complaint area or in locations associated with the complaint
area (connected by pathways)?
Is the pattern of complaints consistent with any of these sources?
Indoor Air Quality Forms 223
-------
Hypothesis Form
Hypothesis: Using the information you have gathered, what is your best explanation for the problem?
Hypothesis testing: How can this hypothesis be tested?
If measurements have been taken, are the measurement results consistent with this hypothesis?
Results of Hypothesis Testing:
Additional Information Needed:
224 Indoor Air Quality Forms
-------
distribution, see also HVAC system, Ventilation 7-8,24-27,35,38,57-71,82-84,88,92-93, 111-115, 121-135, 146,
177, 193, 201-206
Air handling units, see also HVAC system 124-130, 177, 192, 199
Air pressure, see HVAC system, Pressure relationships, and Ventilation
Airflow, see also Pressure relationships and Ventilation 24, 26, 64, 71, 99, 104, 114, 121-122, 125
Asbestos 63, 147-150, 164-165
ASHRAE, see also Standards, guidelines, and advisories 121, 167
Guideline 1-1989 139
Standard 52-1976 126, 138
Standard 55-1981 57, 66, 129, 137
Standard 62-1989 8, 14, 28, 34-35, 41, 60, 64-66, 82-87, 115, 126, 136-137
oaerosols, see Biological contaminants
Biocides 5, 73, 91, 94-95, 132
Biological contaminants 5, 24, 35-36, 40, 48, 56, 63, 76, 82, 86, 91-95, 102-105, 117-118, 125, 127, 129, 131-132, 135,
138, 141-146, 165
measuring 105, 117
Boilers, see also HVAC system 87-88, 113, 124, 135
Building-related illness (BRI) 11, 86, 101, 105
Carbon dioxide (CO2) 36, 49, 57-58, 60-61, 74-76, 87, 110-115
Carbon monoxide (CO) 10, 37, 56, 58, 75-77, 100, 113, 118, 135
Chemical Inventory 23, 26, 72-73, 169, 221
Chemical smoke 22, 60-61, 68, 75, 77, 110-112
Chillers, see also HVAC system 124, 135, 137
Cleaning materials 32, 36, 73, 97
Combustion gases 29, 56, 75, 86, 89, 100, 113
Complaint area 49, 53-54, 65, 68-69, 76
Complaints 10-11, 27, 32, 46, 103
Indoor Air Quality Complaint Form 15, 32, 169, 181
responding to 14-17
Control systems, see also HVAC system 8, 19-21, 23, 26, 31, 34-36, 47, 57, 60, 64-65, 76, 82, 92,
122-126, 128-130, 134-135, 145
Cooling coils, see also HVAC system 35, 67, 97, 123-124, 126, 128
Cooling towers, see also HVAC system 24, 28, 35, 89, 101, 135
Dmpers, see also HVAC system 24, 60, 65, 87, 125, 130, 133
fire dampers 25, 130
mixing boxes (mixed air plenums) 124-126
outdoor air dampers 59-60, 125
Diffusers, see also HVAC system 58-61, 67, 82-83, 87-88, 113-114, 133
Index 225
-------
Ductwork, see also HVAC system 36, 61, 73, 91, 102, 127, 131-132
cleaning 36, 61, 73, 91, 102, 127, 131-132
leakage 67, 87, 130
plenum 24-25, 61, 67, 87, 92, 123, 125, 130, 131, 133
return 65, 87, 99, 130, 133
supply 61,65,99-100,114,123
Dust 23, 25, 32, 67, 72-73, 1 18, 126, 131,138
Eevators 68- 69, 93
Environmental stressors II, 55-56, 77-78, 85
Environmental tobacco smoke (ETS) 6, 9-10, 24-25, 32, 35, 40-41, 66, 73, 81-82, 90, 116, 118, 166
EPA, see Standards, guidelines, and advisories
Ergonomic stressors 55-56, 78, 85
Exhaust air, see HVAC system and Ventilation 8-9, 58, 65, 82, 89, 114, 124, 133, 154
Exhaust fumes 53,72,100
Fans, see also HVAC system 22, 48, 87, 89, 124, 130, 133, 145
Filters, see also HVAC system 2, 36, 48, 60-61, 84, 91-92, 123, 126-128, 130, 138
Firecodes 27, 58, 83
Formaldehyde 56, 82, 85, 116-117
Furnishings 34, 40, 72-73, 78, 86, 93, 96, 99, 102, 122, 133, 145
Halthand safety 52, 56, 63, 76, 101, 105, 117, 147
committee 16-17, 40, 76
considerations for investigators 52, 56, 63, 76, 101, 105
Humidification, see also HVAC system 35, 56, 60, 90, 101, 129, 141
Humidity, see Moisture 24, 49, 56, 67, 60, 82, 89, 94, 1 10-1 1 1, 123, 125, 129
HVAC Checklist - Long Form 26, 58, 61, 169, 175, 195-209
HVAC Checklist - Short Form 26, 58, 61-62, 169, 191-194
HVAC system 5, 6-9, 57-59, 62, 79, 86, 89, 1 1 1, 121, 123, 154
components 57, 64, 83, 87, 94, 123-137
design types 7-8, 57-59, 61- 62, 64- 65, 121-123
maintenance 22-23, 62, 67, 91, 122
operation 6, 25, 52, 55-59, 62, 89, 122, 189
zones 47, 58, 76, 82, 112, 121-122, 169
Hypothesis
developing and testing hypotheses 46, 57, 67, 71, 74-75, 78-79, 223
Hypothesis Form 57, 67, 71, 74, 78-79, 169, 223-224
Incident Log 16, 49, 169, 183
IAQ Management Checklist 42, 169, 171-174
IAQ management plan flowchart 32
IAQ manager 32-33
IAQ profile flowchart 20
IAQ task force 13,17,40
Indoor Air Quality Complaint Form 15, 169, 181
Infiltration, see Airflow and Pressure relationships
Integrated Pest Management (IPM), see Pest control
226 Index
-------
Intermittent problems 10, 55, 59, 72, 74, 77
Interview, see Occupant Interview
Investigation
collecting additional information 20, 25-29, 49-74
flowchart 45
forming hypotheses, see Hypothesis, developing and testing
outside assistance 20, 40, 45, 47, 63, 105-108, 117
reviewing existing records 20-22, 50, 58
sampling 74-77, 109-119
walkthrough 45,47-49
Legionnaire's disease 11,56,101
Lighting 11,24-25,55,77-78,85-86
Loading docks 23, 25, 37, 89, 100
Local exhaust, see also HVAC system and Pressure relationships 9, 22, 40, 65, 82-83, 90, 92, 94, 97, 99-100, 102, 137
Log of Activities and System Operations 52, 53, 58, 77, 139, 169, 189
IVlntenance 24, 31, 34, 36, 67, 97
preventive 23,36
records 22-23
schedule 23, 34-35, 139
Manometer 36, 58, 68-69, 110
Material Safety Data Sheets (MSDS) 20, 28, 32, 35, 38-40, 73
Measurement
comparing to standards and guidelines 75- 76, 87
devices 48,58,75,109-119
developing measurement strategy 48, 74-77
Microbiological contaminants, see Biological contaminants
Mildew, see Biological contaminants
Mitigation
evaluating approaches 102-103
judging success 75, 103-104
managing projects 103
persistent problems 104
using air cleaning 81, 84-85, 89, 92
using exposure control 81, 85, 93, 96-99
using source control 81-82, 89-101
using ventilation 41, 81-84, 87-100
Mixing boxes, see also HVAC system 61, 124-126
Moisture 23-24, 95, 128, 131, 141-146
humidity 24, 60, 120, 122, 137-138, 141-146
waterdamage 24, 73, 94, 128, 131-132, 141-142
Mold, see Biological contaminants
Multiple chemical sensitivity (MCS) 12
IMoSH, see also Standards, guidelines, and advisories 41, 63, 75, 81,84, 111, 116, 119, 147-149, 154, 157,
164-165, 167
Noise 11,55, 77-78, 85-86, 127
Index 227
-------
Occupants 5, 10-11
complaints 10, 46, 48, 50, 72, 131
density 24, 66, 73, 78, 87, 122, 136
Occupant Diary 52, 77, 169, 187
Occupant Interview 50-52, 169, 185
occupant relations (IAQ management plan) 40
Odors 8, 24-25, 49, 65
Outdoor air intake 5, 10, 25, 56, 58, 65, 89, 99-100, 121, 124-125
Outdoor sources of contaminants 5, 25, 56- 57, 72-74, 86, 89, 102, 113, 127
I^ppermint oil 69
Pest control 23, 32, 37-38, 43, 73, 84, 89
Integrated Pest Management (1PM) 3 8
pesticides 23, 32, 37-38, 76, 85, 96, 116
Pollutant pathways and driving forces 5, 9-10, 50, 54, 69-70, 79, 82, 84, 89, 97, 100, 115, 152
Pollutant and Source Inventory 25-26, 28, 72-74, 169, 213
Pollutant Pathway Form for Investigations 67, 69, 169, 211
Pollutant Pathway Record IAQ Profile 26-27, 33, 169, 175
Pressure relationships, see also Airflow and HVAC system 8-9, 27, 35, 37, 45, 66-68, 71, 82-83, 89, 93, 98, 100-111, 127,
133-134, 144
negative/positive 8, 26-27, 37, 70, 82-83, 89, 98, 100, 110-111, 127, 132, 141, 154-155
Preventive Maintenance, see also Maintenance 36, 132
Psychrometer 111, 143
Psychosocial stressors 11, 55- 56, 77-78
Purchasing 32, 35, 37, 41, 81
Ridon 5,89,151-152,167
Recirculation, see Ventilation
Redecorating/Renovation/Remodeling 21, 32, 34, 40, 55, 66, 73, 86, 99
Return air, see HVAC system and Ventilation
Roofing 23, 85, 89, 99
Sampling and analysis, see Measurement
Sick building syndrome (SBS) 11,155
Smoking, see Environmental tobacco smoke
Sources, see also Pollutant and Source Inventory and specific sources (by name) 5, 6, 8-9, 26, 28, 35, 48, 72-74, 76,
81-82, 90
Special use areas 25, 65, 73, 86, 90, 93, 96, 98, 133-134
Standards, guidelines, and advisories, see also ASHRAE, NIOSH 43, 75-76, 167
Storage practices 23, 25, 37, 73, 97
Supply air, see HVAC system and Ventilation
Surface contamination, see also Biological contaminants 6, 37, 76, 86, 91, 94
Terminal devices, see HVAC system
Testing and balancing 21, 43, 48, 58, 87, 92, 94, 98-99, 103, 123
Thermal comfort 7, 24, 56-57, 87, 89, 110-111, 121,133-134,137,167
Thermal mass balance 114-115
Thermostats, see also HVAC system 24, 59-60, 64-65, 67, 111, 122, 134-135, 145
228 Index
-------
Tools
for IAQ investigations 45, 48-50, 58, 68, 72, 77, 109-1 19
for IAQ profiles 20, 22
Total volatile organic compounds (TVOCs) 115-116
Tracergas 58, 69, 77, 1 12-1 13, 126
Trainingm 31, 33, 41, 117, 139, 167
Trash disposal 23,37,89
it ventilators, see HVAC system
Unsanitary conditions 24-25, 38, 65, 67, 72, 94, 1 17
ifentilation, see also Airflow, ASHRAE 62-1989, HVAC system, Pressure relationships 7, 8-10, 24, 65, 83-84, 110, 113,
122, 126, 130-131, 133, 136, 139, 144, 167
air distribution 61, 69, 86-87, 95, 104
outdoor air 24, 65, 82-83, 86-87, 91-92, 96, 99-100, 102, 113-115, 121, 122-125, 135, 145
measuring 87-88
recirculation 82, 92
total air 65, 82-83, 95, 99, 104, 1 13-1 14
underventilation 24, 56-57, 60, 66-67, 82-83, 87-88, 1 12-113
Ventilation Worksheet 169, 179
Vibration 11,77-78,85-86
Volatile organic compounds (VOCs) 6, 82, 96, 99, 102, 115-1 16
Wkthrough
profile 20-25
investigation 45, 47-49
Water chillers, see also HVAC system 137
Water, see Moisture
Zone/Room Record 28-29, 61- 62, 169, 177
Index 229
-------