United States Environmental Protection Indoor Environments Division (6609J) Office of air and Radiation EPA-402-S-01 -001 E January 2000 Aganry Energy Cost and IAQ Performance of Ventilation Systems and Controls Project # 5 Peak Load Impacts of Increasing Outdoor Air Flows from 5 cfm to 20 cfm per Occupant in Large Office Buildings ------- Energy Cost and IAQ Performance of Ventilation Systems and Controls Project Report # 5: Peak Load Impacts of increasing Outdoor Air Flows from 5 to 20 cfm per Occupant in Large Office Buildings Indoor Environments Division Office of Radiation and Indoor Air Office of Air and Radiation United States Environmental Protection Agency Washington, D.C. 20460 January 2000 ------- Energy Cost and IAQ Performance of Ventilation Systems and Controls Project Report #5: Peak Load Impacts of increasing Outdoor Air Flows from 5 to 20 cfm per Occupant in Large Office Buildings INTRODUCTION Purpose and Scope of this Report In order to achieve acceptable indoor air quality in office environments, ASHRAE Standard 62- 1989 (and subsequently ASHRAE Standard 19991) raised the recommended outdoor air ventilation rates from 5 cfm/occupant to 20 cfm/occupant. This four-fold increase has raised a number of questions concerning the feasibility and cost of implementing this standard. A companion paper (Project Report # 4) quantifies the energy and energy cost impact of raising outdoor air ventilation rates in office buildings. That report suggests that raising outdoor air flow rates from 5 to 20 cfm/occupant only modestly changes energy costs by $0.02 - $0.06 per square foot in most cases. However, in extreme cases, energy costs were reduced as much as $0.02 per square foot, and increased by as much as $0.19 per square foot. High occupant density and extended operating hours had the most profound effects on the energy cost impact. The purpose of this report is to examine the peak load impacts which occur when outdoor air flow rates are raised. This issue is important for both new and existing buildings. First, downsizing is an important feature of many energy conscious designs and retrofit strategies. This report sheds light on the extent to which downsizing is possible when buildings operate at elevated outdoor air flow rates. Second, owners of existing buildings which may have been designed to operate at relatively low outdoor air flow rates are being asked to raise these rates in order to improve indoor air quality. This report also addresses the extent to which such increases are feasible for these buildings, and identifies situations in which serious problems may occur if capacity issues are not properly addressed. 1 This project was initiated while ASHRAE Standard 1989 was in effect. However, since the outdoor air flow rates for both the 1989 and 1999 versions are the same, all references to ASHRAE Standard 62 in this report are stated as ASHRAE Standard 62-1999. Energy Cost and IAQ 1 Report # 5 ------- Background This report is part of a larger modeling project to assess the compatibilities and trade-offs between energy, indoor air, and thermal comfort objectives in the design and operation of HVAC systems in commercial buildings, and to shed light on potential strategies which can simultaneously achieve superior performance on each objective. It is hoped that this project will contribute to the body of new data needed by professionals and practitioners who design and operate ventilation systems as they attempt to reduce costs and save energy without sacrificing thermal comfort or outdoor air flow performance. The methodology used in this project has been to refine and adapt the DOE-2.1 E building energy analysis computer program for the specific needs of this study, and to generate a detailed database on the energy use, indoor climate, and outdoor air flow rates of various ventilation systems and control strategies. Constant volume (CV) and variable air volume (VAV) systems in different buildings and with different outdoor air control strategies under alternative climates provided the basis for parametric variations in the database. Seven reports, covering the following topics, describe the findings of this project: Seven reports, covering the following topics, describe the findings of this project: • Project Report #1: Project objective and detailed description of the modeling methodology and database development • Project Report #2: Assessment of energy and outdoor air flow rates in CV and VAV ventilation systems for large office buildings: • Project Report #3: Assessment of the distribution of outdoor air and the control of thermal comfort in CV and VAV systems for large office buildings • Project Report #4: Energy impacts of increasing outdoor airflow rates from 5 to 20 cfm per occupant in large office buildings • Project Report #5: Peak load impacts of increasing outdoor airflow rates from 5 to 20 cfm per occupant in large office buildings • Project Report #6: Potential problems in IAQ and energy performance of HVAC systems when outdoor airflow rates are increased from 5 to 15 cfm per occupant in auditoriums, education, and other buildings with very high occupant density • Project Report #7: The energy cost of protecting indoor environmental quality during energy efficiency projects for office and education buildings Energy Cost and IAQ 2 Report # 5 ------- DESCRIPTION OF THE BUILDINGS AND VENTILATION SYSTEMS MODELED A large 12 story office building (Building A), along with 13 additional parametric variations (Buildings B-N) were modeled in three different climates representing cold (Minneapolis), temperate (Washington D.C., and hot/humid (Miami) climate zones. All buildings have an air handler on each floor servicing four perimeter zones corresponding to the four compass orientations, and a core zone. A dual duct constant volume (CV) system, and a single duct variable volume (VAV) system with reheat were modeled using alternative outdoor air control strategies. Constant volume systems control the thermal conditions in the space by altering the temperature of a constant volume of supply air, while VAV systems alter the supply air volume while maintaining a constant supply air temperature. The building and HVAC parameters used in this analysis are described in Exhibit 1. The basic outdoor air control strategy which was modeled for both CV and VAV systems is one that provides the design outdoor air flow during all operating conditions. To this basic strategy, a temperature air-side economizer strategy is also presented. To avoid humidity problems, the economizer is shut off at outdoor temperatures above 65°F. The outdoor air flow rate reverts to its base level (5 or 20 cfm per occupant) when the economizer is in the "off" mode. A more detailed description of all the buildings and ventilation systems modeled in this project is provided in Report #1. APPROACH The CV and VAV systems were each modeled for the entire year for each HVAC system in each of the three climates using 5 cfm and 20 cfm of outdoor air per occupant. From the data, the peak hourly load on the heating coil, cooling coil, and preheat coil were identified. Comparisons were then made between the two runs (5 cfm and 20 cfm per occupant) to determine the impact of an increased outdoor air flow on these peak loads. RESULTS Exhibits 2 and 3 presents the peak load impacts of raising outdoor air flow rates in CV systems (with and without economizers) in each of the three climates. Exhibits 4 and 5 presents the same data for VAV systems. Peak Cooling Loads Peak Coiling Loads at 5cfm Per Occupant Peak cooling loads for CV and VAV systems were similar, except that CV systems experienced peak cooling loads which were generally 5-10% higher in all climates compared to VAV systems. Energy Cost and IAQ 3 Report # 5 ------- A low efficiency shell and a high perimeter to core ratio raised the peak cooling load, since these buildings are most affected by outdoor climate conditions. Buildings with a high exhaust rate experienced a higher peak cooling load because they have a higher flow of replacement air which, during the heat of the summer, will raise the peak cooling load. Similarly, buildings which operate over 24 hours tend to had higher peak cooling loads because there are a larger number of hours where the peak may occur. The highest peak cooling loads were experience by the high occupant density building. Occupants generate heat which increases the demand for cooling, so that the peak cooling load rises as occupant density rises. Economizers do not affect peak cooling loads because when the peak occurs, the economizer is shut off. In addition, the peak cooling load is not predictably affected by climate. The peak cooling load in Minneapolis, for example, was not much different than the peak cooling load in Miami or Washington, D.C. even though the overall weather patterns are substantially different. Impact of Higher Outdoor Air Flow Rates on Peak Cooling Load Raising outdoor airflow rates from 5 cfm to 20 cfm per occupant typically increased peak cooling loads by 15%-25% with the highest increases in the Miami climate. CV and VAV systems had comparable increases in peak cooling load. Economizers made no difference, since the economizer was not operating when the peak cooling load occurs. The one notable exception is that occupant density had a dramatic influence, increasing the peak cooling load impact to 41% for both CV and VAV systems in Miami, and approximately 30% in Washington, D.C. and Minneapolis. The dramatic effect that occupant density had on the impact on peak cooling loads from increased outdoor airflow rates raises potentially serious issues concerning the viability of raising outdoor airflow in very high density buildings such as education buildings, auditoriums, and theaters. These issues are explored in detail in a companion report (Project Report #6). Peak Heating Loads Peak Heating Loads at 5 cfm Per Occupant Unlike peak cooling loads that were not significantly affected by outdoor climate, peak heating loads were significantly affected by outdoor climate, especially for CV systems. For example, the peak heating load for the CV system of the base building in Miami was only 191 kBTU/h while it was 6,649 kBTU/h for the same building in Minneapolis. The effect of climate on peak heating loads for VAV systems was much less dramatic than for CV systems because the VAV system modeled here uses a zone reheat system, which heats the supply air at the VAV box after it has been cooled. The heatng coil load is therefore less dependent on outdoor weather conditions. Thus, for the VAV system, the same building experienced peak heating loads of 1,940 kBTU/h in Miami and 6,131 kBTU/h in Minneapolis. Energy Cost and IAQ 4 Report # 5 ------- In contrast to the cooling coil, economizers significantly increased the peak load on the heating coil, though this is true only for the CV systems. For example, the peak heating coil load for the CV system in the base building in Washington, D.C. without economizer was 2,572 kBTU/h. Adding an economizer increased this to 3936 k BTU/h. This is because the economizer increases the flow of outdoor air in the winter to take advantage of free cooling. This increased the heating requirement in zones requiring heat. In VAV systems, the economizer did not affect the peak heating load because heating needs are accommodated by reheating 55°F air at the VAV box, and this is not affected by an economizer. As expected, buildings with low shell efficiency and high perimeter to core ratios experienced higher peak heating loads than buildings with high shell efficiency and low perimeter to core ratios. Impact of Higher Outdoor Air Flow Rates on Peak Heating Coil Loads Raising the outdoor airflow rate from 5 cfm to 20 cfm per occupant typically raised the peak heating coil load by 5% - 20%, but sometimes this increase was as high as 40-45%. The most important feature which can drive the heating coil impact up appears to be high occupant density. However, low perimeter to core ratios and high efficiency shell resulted in high heating coil impacts. The absolute impact of higher outdoor flow rates in Miami was small, but it was sometimes proportionally high because the base peak heating coil loads were generally low. The data present some odd results which are not easily predicted or explained. For example, in some buildings with CV systems, the peak heating load impact was reduced. An examination of the data reveals that the peak typically occurred at start-up. Since the system only occasionally cycles on at night, the indoor climate conditions at start up are highly dependent on when the system was last on before start-up. Raising the outdoor air flow rate from 5 to 20 cfm per occupant could affect the on/off cycle at night and therefore the indoor climate conditions at start-up, and this could present counterintuitive results on the peak heating coil. For example, some CV systems without economizers in Miami experienced a decrease in peak heating coil load when outdoor air flow rates were increased. Peak Preheat Coil Loads Peak Preheat Coil Loads at 5 cfm Per Occupant The preheat coil for both CV and VAV systems in all buildings in all climates experienced no load when outdoor flow rates were at 5 cfm per occupant. Impact of Higher Outdoor Air Flow Rates on the Preheat Coil Load Even when the outdoor air flow rates are raised from 5 cfm to 20 cfm per occupants, none of the CV systems experienced a preheat coil load in any climate. This is because the preheat coil loads only occur when the mixed air temperature is below 45°F. Since return air is at or above Energy Cost and IAQ 5 Report # 5 ------- room air temperature, the mixed air temperature can only fall below 45°F if the outdoor air temperature is cold and the outdoor air fraction is high. Since CV systems have high winter supply air flow rates relative to VAV systems, the outdoor air fraction of the CV systems was evidently not high enough to trigger the need for preheat coils, even in the cold climate of Minneapolis. However, VAV systems have much lower outdoor air fractions, so that in almost every VAV building in the Minneapolis climate, the system experienced a preheat coil load when the outdoor air flow rate was raised to 20 cfm per occupant. The loads which typically appeared at 20 cfm per occupant ranged from 700 to 1500 kBTU/h. However, both the medium and high occupant density building were above this range, resulting in loads of 2700 and 5800 kBTU/h respectively. Economizers made no meaningful difference in peak preheat coil load impact. In general, the preheat peak loads experienced are moderate and may well fall within the excess capacity range of existing systems or within the safety factor of most new system designs. However, many existing buildings do not have preheat coils. Raising the outdoor air flow rate to 20 cfm in these building, even in temperate climates, runs the risk of damaging the coil, particularly for medium or high occupant density buildings, or buildings that operate with extended operating hours. This is an especially high risk for cold climates, though buildings in cold climates are more likely to have some preheat coil capacity. SUMMARY AND CONCLUSIONS With the exception of very low occupant density buildings, every HVAC system in every building in every climate experienced a large peak load increase in one of the three coil systems. Because many buildings have excess capacity precisely in order to avoid unexpected problems, this analysis may overstate the potential problem in many buildings. However, in individual cases, this analysis suggests that it would be extremely unwise for owners of existing buildings to raise outdoor air flow rates without first carefully performing a load analysis. Occupant density was the single most important factor in determining the increase in peak coil loads when outdoor air flow rates are increased. This suggests that buildings with exceptionally high occupant densities, such as education buildings, auditoriums, or theaters may have significant capacity issues associated with high outdoor airflow rates. These issues are examined in detail in a companion report (Project Report #6). Buildings that were built with energy efficiency in mind may have the least excess capacity and therefore may have the greatest difficulty in raising outdoor airflow rates to meet current ASHRAE standards. In addition, this report suggests that downsizing as an energy conservation strategy ought to be judiciously applied, taking into account the increased capacity needed to accommodate outdoor airflow rates consistent with indoor air quality. Energy Cost and IAQ 6 Report # 5 ------- BIBLIOGRAPHY Harriman, L. G., Plager, D., Kosar, D. 1997. Dehumidification and cooling loads from ventilation air. ASHRAE Journal 39(11): 37-45 Hathaway, A. 1995. The link between lighting and cooling. Engineered Systems Maintenance July 1995: 18- 19. Meckler, M. 1994. Desiccant-assisted air conditioner improves IAQ and comfort. Heating/Piping/Air Conditioning October 1994: 75-84. Rengarajan, K., Shirey, D. B., Raustad, R. A. 1996. Cost-effective HVAC technologies to meet ASHRAE Standard 62-1989 in hot and humid climates. ASHRAE Transactions 102(1): 3949. Shirey, D. B., Rengarajan, K. 1996. Impacts of ASHRAE 62-1989 on small Florida offices. ASHRAE Transactions 102(1): 3948 Energy Cost and IAQ 7 Report # 5 ------- Exhibit 1 Building and HVAC Characteristics Building Configuration Window R-Value Window Shading Coeffic. Roof Insulation Infiltration Rate Chiller COP Boiler Effic. (%) Occup. Density (Occup/ 1000 SF) P/C Ratio Exhaust Flow Rate (cfm) Daily Operating Hours (hrs/day) A. Base Case 2.0 0.8 10 0.5 3.5 70 7 0.5 750 12 B. High Effic. Shell 3.0 0.6 20 0.75 3.5 70 7 0.5 750 12 C. Low Effic. Shell 1.0 1.0 5 0.25 3.5 70 7 0.5 750 12 D. High Effic. HVAC 2.0 0.8 10 0.5 4.5 80 7 0.5 750 12 E. Low Effic. HVAC 2.0 0.8 10 0.5 2.5 60 7 0.5 750 12 F. High Occup.Density 2.0 0.8 10 0.5 3.5 70 15 0.5 750 12 G. Med Occup. Density 2.0 0.8 10 0.5 3.5 70 10 0.5 750 12 H. High P/C Ratio 2.0 0.8 10 0.5 3.5 70 7 0.8 750 12 I. Low P/C Ratio 2.0 0.8 10 0.5 3.5 70 7 0.3 750 12 J. High Exhaust Rate 2.0 0.8 10 0.5 3.5 70 7 0.5 1500 12 K. Low Occup Density 2.0 0.8 10 0.5 3.5 70 5 0.5 750 12 L. Very Low Occ. Density 2.0 0.8 10 0.5 3.5 70 3 0.5 750 12 M. Extended Oper. Hours 2.0 0.8 10 0.5 3.5 70 7 0.5 750 18 N. 24 Hour Operation 2.0 0.8 10 0.5 3.5 70 7 0.5 750 24 Energy Cost and IAQ Report # 5 ------- Exhibit 2 Changes in Peak Coil Load Due to Increased Outdoor Air Flow Rates From 5 to 20 cfm per Occupant: CV Systems without Economizers {cv(foaf)> Miami, FL Washington, DC Minneapolis, MN Building Configuration Cooling Heating Preheat Cooling Heating Preheat Cooling Heating Preheat (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) A. Base Case @5 9258 191 0 9017 2572 0 9288 6649 0 increase 1876 443 1752 1047 1421 649 Percent Increase 20% 232% None 19% 41% None 15% 10% None B. High Eff. Shell @5 8662 37 0 8110 1023 0 8307 4298 0 Increase 1851 -12 1856 2000 1398 1864 Percent Increase 21% -31 % None 23% 196% None 17% 43% None C. Low Eff. Shell @5 10482 1267 0 10368 5160 0 10361 8818 0 Increase 1845 133 1553 445 1442 71 Percent Increase 18% 10% None 15% 9% None 14% 1% None D. High Eff. HVAC @5 9258 191 0 9017 2572 0 9296 6649 0 Increase 1876 443 1752 1047 1423 649 Percent Increase 20% 232% None 19% 41% None 15% 10% None E. Low Eff. HVAC @5 9258 191 0 9017 2572 0 9296 6649 0 Increase 1876 443 1752 1047 1423 649 Percent Increase 20% 232% None 19% 41% None 15% 10% None F. High P/C Ratio @5 10301 919 0 10277 4007 0 10414 8349 0 Increase 1812 -339 1521 763 1401 380 Percent Increase 18% -37% None 15% 19% None 13% 5% None G. Low P/C Ratio @5 8056 55 0 7940 1452 0 7899 4427 0 Increase 1995 206 1668 1305 1439 1217 Percent Increase 25% 377% None 21% 90% None 18% 28% None H. High Exhaust @5 9817 305 0 9465 2886 0 9727 6917 0 Increase 1317 330 1314 733 993 382 Percent Increase 13% 108% None 14% 25% None 10% 6% None 1. High Occ. Dens. @5 10775 129 0 10927 2923 0 10509 7059 0 Increase 4384 547 3522 1532 3206 1158 Percent Increase 41% 424% None 32% 52% None 31% 16% None J. Medium Occ. Dens. @5 9741 168 0 9665 2803 0 9644 6777 0 Increase 2929 472 2465 1099 2192 666 Percent Increase 30% 281 % None 26% 39% None 23% 10% None K. Low Occ. Dens. @5 9034 221 0 8949 2704 0 9041 6643 0 Increase 1192 421 953 594 960 909 Percent Increase 13% 190% None 11% 22% None 11% 14% None L. Very Low Occ. Dens. @5 8811 222 0 8893 2661 0 8786 6566 0 Increase 494 93 247 279 400 406 Percent Increase 6% 42% None 3% 10% None 5% 6% None M. Extended Op. Hours @5 9066 810 0 9003 2679 0 8986 5975 0 Increase 1975 316 1572 1482 1490 588 Percent Increase 22% 39% None 17% 55% None 17% 10% None N. 24 Hour Operation @5 9621 759 0 8903 3106 0 8896 6657 0 Increase 1331 353 1569 2186 1453 1992 Percent Increase 14% 47% None 18% 70% None 16% 30% None Energy Cost and IAQ 9 Report # 5 ------- Energy Cost and IAQ 10 Report # 5 ------- Exhibit 3 Changes in Peak Coil Load Due to Increased Outdoor Air Flow Rates From 5 to 20 cfm per Occupant: VAV Systems without Economizers (VAV(COA)} Miami, FL Washington, DC Minneapolis, MN Building Configuration Cooling Heating Preheat Cooling Heating Preheat Cooling Heating Preheat (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) A. Base Case @5 8670 1940 0 8517 4638 0 8688 6131 0 increase 1862 1659 1320 456 897 Percent Increase 21% None None 19% None None 15% 7% Increase B. High Eff. Shell @5 8010 967 0 7855 3552 0 7966 4868 0 Increase 1881 1695 101 1303 479 745 Percent Increase 23% None None 22% 3% None 16% 10% Increase C. Low Eff. Shell @5 9591 3066 0 9360 6168 0 9580 8795 0 Increase 1697 1621 345 1332 50 514 Percent Increase 18% None None 17% 6% None 14% 1% Increase D. High Eff. HVAC @5 8670 1940 0 8517 4638 0 8688 6131 0 Increase 1862 1659 1320 456 897 Percent Increase 21% None None 19% None None 15% 7% Increase E. Low Eff. HVAC @5 8670 1940 0 8517 4638 0 8688 6131 0 Increase 1862 1659 1320 456 897 Percent Increase 21% None None 19% None None 15% 7% Increase F. High P/C Ratio @5 9567 2680 0 9672 5641 0 9666 7862 0 Increase 1759 1425 1298 613 382 Percent Increase 18% None None 15% None None 13% 8% Increase G. Low P/C Ratio @5 7551 1158 0 7476 3490 0 7427 4834 0 Increase 2029 1597 153 1390 515 864 Percent Increase 27% None None 21% 4% None 19% 11% Increase H. High Exhaust @5 9238 1940 0 8971 4637 0 9106 6127 0 Increase 1293 1196 934 457 896 Percent Increase 14% None None 13% None None 10% 7% Increase I. High Occ. Dens. @5 10119 1981 0 10128 5598 0 9944 6314 0 Increase 4190 262 3290 979 1539 2899 899 5801 Percent Increase 41% 13% None 32% 17% Increase 29% 14% Increase J. Medium Occ. Dens. @5 9151 1981 0 9110 4876 0 9098 6203 0 Increase 2782 13 2081 423 451 1993 783 2743 Percent Increase 30% 1% None 23% 9% Increase 22% 13% Increase K. Low Occ. Dens. @5 8407 1938 0 8496 4576 0 8436 5900 0 Increase 1198 972 878 493 Percent Increase 14% None None 11% None None 10% 8% None L. Very Low Occ. Dens. @5 8168 1936 0 8282 4550 0 8262 5859 0 Increase 503 407 368 Percent Increase 6% None None 5% None None 4% None None M. Extended Op. Hours @5 8363 2321 0 8433 4498 0 8389 6337 0 Increase 1772 1474 114 15 1273 547 1386 Percent Increase 21% None None 17% 3% Increase 15% 9% Increase N. 24 Hour Operation @5 8249 2214 0 8336 4827 0 8228 6659 0 Increase 1725 64 1471 24 36 1265 618 1494 Percent Increase 21% 3% None 18% 1% Increase 15% 9% Increase Energy Cost and IAQ 11 Report # 5 ------- Energy Cost and IAQ 12 Report # 5 ------- Exhibit 4 Changes in Peak Coil Load Due to Increased Outdoor Air Flow Rates From 5 to 20 cfm per Occupant: CV Systems with Economizers (CV(FOAF)Econ} Miami, FL Washington, DC Minneapolis, MN Building Configuration Cooling Heating Preheat Cooling Heating Preheat Cooling Heating Preheat (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) A. Base Case @5 9258 3446 0 9017 3936 0 9288 6707 0 increase 1876 1755 35 1421 623 Percent Increase 20% None None 19% 1% None 15% 9% None B. High Eff. Shell @5 8406 2715 0 8110 2786 0 8307 4326 0 Increase 2010 1855 246 1398 1839 Percent Increase 24% None None 23% 9% None 17% 43% None C. Low Eff. Shell @5 10482 3817 0 10368 5532 0 10361 8901 0 Increase 1845 30 1553 135 1442 Percent Increase 18% 1% None 15% 2% None 14% None None D. High Eff. HVAC @5 9258 3446 0 9017 3936 0 9296 6707 0 Increase 1876 1755 35 1423 623 Percent Increase 20% None None 19% 1% None 15% 9% None E. Low Eff. HVAC @5 9258 3446 0 9017 3936 0 9296 6707 0 Increase 1876 1755 35 1423 623 Percent Increase 20% None None 19% 1% None 15% 9% None F. High P/C Ratio @5 10301 4546 0 10277 5451 0 10414 8476 0 Increase 1812 1536 -61 1401 299 Percent Increase 18% None None 15% -1% None 13% 4% None G. Low P/C Ratio @5 8056 1950 0 7940 2360 0 7899 4461 0 Increase 1995 22 1668 412 1439 1190 Percent Increase 25% 1% None 21% 17% None 18% 27% None H. High Exhaust @5 9817 3446 0 9465 3949 0 9727 6967 0 Increase 1317 1317 32 993 364 Percent Increase 13% None None 14% 1% None 10% 5% None I. High Occ. Dens. @5 10775 3238 0 10927 3067 0 10509 7110 0 Increase 4384 3522 1407 3206 1261 Percent Increase 41% None None 32% 46% None 31% 18% None J. Medium Occ. Dens. @5 9741 3371 0 9665 3974 0 9644 6834 0 Increase 2929 -58 2445 2192 626 Percent Increase 30% -2% None 25% None None 23% 9% None K. Low Occ. Dens. @5 9034 3580 0 8949 3996 0 9041 7006 0 Increase 1192 953 960 588 Percent Increase 13% None None 11% None None 11% 8% None L. Very Low Occ. Dens. @5 8811 3155 0 8893 3940 0 8786 6952 0 Increase 494 248 400 276 Percent Increase 6% None None 3% None None 5% 4% None M. Extended Op. Hours @5 9067 3232 0 9003 3575 0 8986 6031 0 Increase 1975 1572 591 1490 562 Percent Increase 22% None None 17% 17% None 17% 9% None N. 24 Hour Operation @5 9621 3056 0 8903 4528 0 8896 9783 0 Increase 1331 1569 2062 1453 1748 Percent Increase 14% None None 18% 46% None 16% 18% None Energy Cost and IAQ 13 Report # 5 ------- Energy Cost and IAQ 14 Report # 5 ------- Exhibit 5 Changes in Peak Coil Load Due to Increased Outdoor Air Flow Rates From 5 to 20 cfm per Occupant: VAV Systems with Economizers (VAV(COA)Econ} Miami, FL Washington, DC Minneapolis, MN Building Configuration Cooling Heating Preheat Cooling Heating Preheat Cooling Heating Preheat (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) (kBtu/H) A. Base Case @5 8670 1949 0 8517 4638 0 8688 6148 0 increase 1862 1659 1336 444 897 Percent Increase 21% None None 19% None None 15% 7% Increase B. High Eff. Shell @5 8010 967 0 7855 3552 0 7962 4868 0 Increase 1881 1694 101 1364 479 745 Percent Increase 23% None None 22% 3% None 17% 10% Increase C. Low Eff. Shell @5 9591 3064 0 9360 6168 0 9580 8806 0 Increase 1697 1621 355 1331 514 Percent Increase 18% None None 17% 6% None 14% None Increase D. High Eff. HVAC @5 8670 1949 0 8517 4638 0 8688 6148 0 Increase 1862 1659 1336 444 897 Percent Increase 21% None None 19% None None 15% 7% Increase E. Low Eff. HVAC @5 8670 1949 0 8517 4638 0 8688 6148 0 Increase 1862 1659 1336 444 897 Percent Increase 21% None None 19% None None 15% 7% Increase F. High P/C Ratio @5 9567 2691 0 9672 5641 0 9662 7875 0 Increase 1759 1425 1298 602 382 Percent Increase 18% None None 15% None None 13% 8% Increase G. Low P/C Ratio @5 7551 1082 0 7476 3490 0 7427 4834 0 Increase 2029 -17 1596 153 1390 515 864 Percent Increase 27% -2% None 21% 4% None 19% 11% Increase H. High Exhaust @5 9238 1949 0 8971 4637 0 9106 6141 0 Increase 1293 1196 947 448 897 Percent Increase 14% None None 13% None None 10% 7% Increase I. High Occ. Dens. @5 10119 1984 0 10128 5598 0 9961 6325 0 Increase 4190 262 3290 979 1539 2903 888 5801 Percent Increase 41% 13% None 32% 17% Increase 29% 14% Increase J. Medium Occ. Dens. @5 9151 1956 0 9110 4876 0 9114 6218 0 Increase 2782 2082 423 451 1995 767 2743 Percent Increase 30% None None 23% 9% Increase 22% 12% Increase K. Low Occ. Dens. @5 8407 1947 0 8496 4576 0 8436 5900 0 Increase 1198 972 878 493 Percent Increase 14% None None 11% None None 10% 8% None L. Very Low Occ. Dens. @5 8168 1935 0 8282 4550 0 8262 5859 0 Increase 503 407 368 Percent Increase 6% None None 5% None None 4% None None M. Extended Op. Hours @5 8363 2331 0 8433 4500 0 8389 6337 0 Increase 1772 1474 121 18 1273 547 1386 Percent Increase 21% None None 17% 3% Increase 15% 9% Increase N. 24 Hour Operation @5 8249 2344 0 8335 4921 0 8228 6659 0 Increase 1725 1472 37 1265 618 1494 Percent Increase 21% None None 18% None Increase 15% 9% Increase Energy Cost and IAQ 15 Report # 5 ------- Energy Cost and IAQ 16 Report # 5 ------- |