vvEPA
United States
Environmental Protection Office of Water  EPA-815-R-98-001
Agency       4607     September 1998
Small System
Compliance Technology
List for the Surface
Water Treatment Rule
and Total Coliform Rule

-------
                               TABLE OF CONTENTS
1.  Introduction                                                           1
    Section 1.1:  Safe Drinking Water Act Implementation                     1
    Section 1.2:  Need for a Small System Technology Requirement             1
    Section 1.3:  Small System Treatment Technology Requirements            2
    Section 1.4:  Format of the Small System Compliance Technology
        List for the SWTR and TCR                                        5
    Section 1.5:  Content of the Small System Compliance Technology
        List for the SWTR and TCR                                        5
    Section 1.6:  Stakeholder Involvement                                   6
    Section 1.7:  Key Stakeholder Input                                     7
    Section 1.8:  Organization of the Document                              7

2.  Compliance Technology List for SWTR                                   8
    Section 2.1:  Background of the Surface Water Treatment and
        Total Coliform Rules                                              8
    Section 2.2:  Technologies Evaluated for the Compliance
        Technology List                                                  8
    Section 2.3:  Compliance Technology Evaluation of Disinfection
         Technologies                                                    9
        Disinfection Treatment Technologies Listed in the 1989 SWTR
                  Ozone                                                 10
                  Chlorine                                               11
                  Chloramines                                            12
                  Chlorine Dioxide                                        12
        Additional Listed Disinfection Treatment Technologies
                  UV Radiation                                           13
                  On-site Oxidant Generation                              15
    Section 2.4:  Degree of Pilot Testing for Filtration Technologies
        on the Compliance Technology List                                  17
    Section 2.5: Compliance Technology Evaluation of Filtration
        Technologies                                                     17
        Filtration Treatment Technologies Listed in the Original SWTR
                  Conventional Filtration                                   19
                  Direct Filtration                                         20

-------
                   Slow Sand Filtration                                     21
                   Diatomaceous Earth (DE) Filtration                       21
        Additional Listed Filtration Technologies
           Membrane processes
                   Reverse Osmosis (RO) Filtration                          24
                   Nanofiltration (NF)                                      24
                   Ultrafiltration (UF)                                      24
                   Microfiltration (MF)                                     25
           Bag and cartridge type filters
                   Bag Filtration                                           25
                   Cartridge Filtration                                      27
                   Backwashable Depth Filtration                            28
    Section 2.6: Summary of Compliance Technologies for the SWTR           29

3. Compliance Technologies for the Total Coliform Rule                       38

4.  Emerging Technologies and Issues for Further Consideration                 40
    Section 4.1: Emerging Technologies:
                   Advanced Ultraviolet Treatments                          41
                   Advanced Oxidation Processes                            43
    Section 4.2: Additional  Issues for Consideration                           44

                                     List of Figures
Figure 1. Compliance Technologies                                           4


                                     List of Tables
Table 1. Surface Water Treatment Compliance Technologies
    (A) Disinfection Technologies                                           31
    (B) Filtration Technologies                                             34
Table 2. Total Coliform Rule Compliance Technologies                        39

-------
                                Appendices


Appendix A: Relevant Parts of Sections 1412 of the Revised
    Safe Drinking Water Act (SOWA)
Appendix B: Additional References on SWTR-Approved Filtration
    Technologies
Appendix C: Memorandum Regarding TCR Technologies

-------
1.  INTRODUCTION

Section 1.1: Safe Drinking Water Act Implementation

    The Safe Drinking Water Act (SDWA) Amendments were signed by the President on August
6, 1996. There are over 70 statutory deadlines in the 1996 SDWA for the Environmental Protection
Agency (EPA). The Amendments contain a challenging set of activities for EPA, States, Indian
tribes, public water systems, and other stakeholders.

    Due to the 1996 SDWA Amendments' emphasis on public information and participation, as well
as EPA's desire to seek a broad range of public input, the stakeholder process that was begun during
the  1995 drinking water program redirection effort has been  greatly expanded.  Many of the 70
statutory deadlines have been grouped into twelve project areas. Each of these areas has a broad set
of stakeholders that will provide information  and comments.  In addition to the stakeholders'
participation, the National Drinking Water Advisory Council (NDWAC) has formed working groups
to address several of the relevant issues.  These working groups make recommendations to the full
Council, which in turn advises EPA on individual regulations, guidances, and policy matters.

    One of the twelve project areas created by the 1996 SDWA is being addressed by EPA's
Treatment Technology Team. The mission of the Treatment Technology Team is to identify and/or
develop high quality, cost-effective treatment technologies to meet regulation development and
program implementation objectives and deadlines.  Short-term goals of this team were to prepare:
(1) the list of technologies that small systems can use to comply with the Surface Water Treatment
Rule (SWTR),  completed August 6, 1997; (2) the list of technologies that small systems can use to
comply with all of the other National Primary Drinking Water Regulations (NPDWRs), by August
6, 1998; and (3) the list of variance technologies for small systems for the appropriate NPDWRs, by
August 6,  1998.  Longer-term goals include the identification of: (1) small system compliance and
variance technologies for all future regulations;  (2) best available  technologies (BATs) for larger
systems in future regulations; and (3) emerging technologies that should be evaluated as potential
compliance or variance technologies for both existing and future regulations. This document relates
to the updating of the SWTR and the listing of Total Coliform Rule (TCR) small system compliance
technologies.  These have been  grouped  into  one publication as they both address  microbial
contaminants and their indicators in drinking water.

Section 1.2: Small System Technology Definitions

    The earlier 1986 SDWA Amendments identified a process for setting maximum contaminant
                                           1

-------
levels (MCLs) as close to the maximum contaminant level goal (MCLG) as is "feasible."  The Act
states that "... the term "feasible" means feasible with the use of the best technology, treatment
techniques and other means which the Administrator finds, after examination for efficacy under field
conditions and not solely under laboratory conditions, are available (taking cost into consideration)"
[Section 1412(b)(4)(D)]. The technologies that met this feasibility criterion are called "best available
technologies" (BATs) and are listed in the final regulations. This process is retained in the amended
1996 SDWA.

    The Surface Water Treatment Rule (SWTR) requires compliance with a treatment technique
rather than an MCL. Section 1412(b)(7)(A) of the 1986 SDWA listed the conditions under which
a treatment technique could be promulgated in lieu of an MCL. When these conditions are met, the
Act states that ". .  . the Administrator must identify those treatment techniques which, in the
Administrator's judgement, would prevent known or anticipated adverse  effects  on the health of
persons to the extent feasible".  The TCR, promulgated in 1989, requires compliance with an MCL
and specifies treatments and other means for water system compliance.

    Before the 1996 SDWA Amendments, cost assessments for the treatment technology feasibility
determinations were based upon impacts to regional and large metropolitan water systems.  This
protocol was  established when the SDWA was originally enacted in 1974 [H.R. Rep. No. 93-1185
at 18(1974)] and was carried over when the Act was amended in 1986 [132 Cong. Rec. S6287(May
21,  1986)].   The  service population  size categories that EPA has used to make feasibility
determinations for regional and large metropolitan water systems has varied among different
regulation packages. The most common population size categories used were 50,000 - 75,000 people
and 100,000 - 500,000 people.  The  technical  demands and costs associated with technologies that
are feasible based on regional and large metropolitan water systems often make these technologies
inappropriate  for small systems.  The 1996 SDWA Amendments attempt to redress this problem in
part through the previously described series of small system compliance technologies. This guidance
is the part of a series of publications (begun in 1997 for the SWTR) aimed at helping small systems
comply with drinking water standards.

Section 1.3:  Small System Treatment Technology Requirements

    Since large systems were previously used as the basis for all feasibility determinations, the
existing BATs for MCL compliance and the treatment techniques require further analysis for small
system applications. The 1996 SDWA Amendments specifically require EPA to make technology
assessments relevant to the three categories of small systems for both existing regulations (e.g.,
SWTR and TCR) and future requirements.  The three population-based size categories  of small
systems thus defined are: 10,000 - 3,301 persons, 3,300 - 501 persons, and 500 - 25 persons.

    The  1996 SDWA Amendments identify two  classes of technologies  for small  systems:
compliance technologies and variance technologies. A "compliance technology" may refer to both
a technology or other means that is affordable  and that achieves compliance with the MCL and to a
technology or other means that satisfies a treatment technique requirement. Possible compliance

-------
technologies include packaged or modular systems and point-of-entry (POE) or point-of-use (POU)
treatment units [see Section 1412(b)(4)(E)(ii)]. Variance technologies are only specified for those
system size/source water quality combinations for which there are no listed compliance technologies
[Section 1412(b)(15)(A)]. Thus, the listing of a compliance technology for a size category/source
water combination prohibits the listing of variance technologies for that combination. While variance
technologies may not achieve compliance with the MCL or treatment technique requirement, they
must achieve the maximum reduction or inactivation efficiency that is affordable considering the size
of the system and the quality of the source water. Variance technologies must also achieve a level
of contaminant reduction that is protective of public health [Section 1412(b)(15)(B)].

    The variance procedure for small systems was significantly revised in 1996.  Under the 1986
SDWA Amendments systems were required to install a technology before applying for a variance;
if they were unable to meet the MCL, they could then apply for a variance. The 1996 Amendments
have given the variance option additional flexibility in that variances can be applied for and granted
before the variance technology is installed, thus ensuring that the system will have a variance before
it invests in treatment.  Under the 1996 Amendments there is a new procedure available for small
systems (systems serving fewer than 10,000): the "small system variance". The difference between
a regular variance  and  a small system variance is  the  basis for the feasibility (technical and
affordability) determination.  For the former, large systems are the basis;  for the latter, small systems
are the basis. If there are no affordable compliance technologies listed by the EPA for a small system
size category/source water quality combination, then the system  may apply for a small system
variance.  One of the criteria for obtaining a small system variance is that the system must install a
variance technology listed  for  that  size category/source  water quality  combination [Section
1415(e)(2)(A)].  A small system variance may only be obtained if alternate source, treatment, and
restructuring options are unaffordable at the system-level.

    There are additional SDWA requirements that affect the listing of variance technologies. Critical
in regard to this particular listing are the following: (1) small system variances are not available for
any MCL or treatment technique for a contaminant with respect to which a national primary drinking
water regulation was promulgated prior to January 1,  1986 [Section 1415(e)(6)(A)]; and, (2) small
system variances are not available for regulations addressing microbiological contamination (including
contamination by bacteria, viruses, or other organisms) or any indicator or treatment technique for
a microbial contaminant [Section 1415(e)(6)(B)]. Therefore, there are no variances or variance
technologies available for the SWTR and TCR.

    In addition, since the SWTR and TCR address microbial contamination, the affordability criteria
discussed undertheEPA/SDWA affordability project do not apply.  For the SWTR and TCR the only
screening criterion beyond treatment efficacy will be the ability of small  water systems to install and
reliably operate the process.

    The flow chart in Figure 1 depicts how the compliance technology and exemption processes may
be utilized in decision-making under the SWTR and TCR drinking water regulations.

-------
           Insert Fig. 1
(Not available in electronic format)

-------
Section 1.4: Format of the Small System Compliance Technology List for the SWTR and TCR

    The 1996 SDWA Amendments do not specify the format for the compliance technology lists.
Section 1412(b)( 15)(D) states that the variance technology lists can be issued either through guidance
or regulations. EPA believes that the compliance technology list may also be appropriately provided
through guidance rather than through rule-making.  Since the listing provided in this guidance is
meant to be informational and interpretative, it does not require any changes to existing rules or the
promulgation of new ones. The purpose of this guidance is to provide small systems with information
concerning the types  of  technologies that can be  used to  comply with the SWTR and  TCR
requirements; it does not over-ride any of the regulatory requirements.

    Both the SWTR and TCR were published in the Federal Register on June 29, 1989. Even
though many systems have already installed treatment, there are systems that still need to select a
treatment technology to comply with the SWTR and/or the TCR. The importance of meeting the
deadlines set forth under the rules further justifies EPA's decision to issue this compliance technology
list as guidance.

    In summary, EPA has chosen to issue the list through a guidance document because regulation
development is unnecessary and could considerably delay publication of the list and/or subsequent
updates. Issuing a list in this  fashion will allow EPA to provide information to more small  systems
and regulators in a timely manner as they make treatment technology decisions.

Section 1.5: Content of the Updated Small System  Compliance Technology List for the SWTR
and TCR

    The SDWA does not specify the content of the compliance technology lists. This listing provides
greater detail than earlier listings, on the capabilities, applicability ranges, water quality concerns, and
operational and maintenance requirements forthe identified compliance technologies. This listing also
includes, in summary format, tabulations (at end of  Chapters 2 and 3) which include details on issues
identified by EPA and  its stakeholders in their review of draft materials.

    Technologies with which the reader may be less familiar are included in the listing, and these are
given greater  coverage; there  are other technologies discussed in Chapter 4 as  "emerging"
technologies, that is those technologies which indicate a likelihood of success in meeting the specific
treatment goals and which require further evaluation.  The listing will evolve and be issued annually
or as required. The listing will not be product-specific because EPA's Office  of Ground Water and
Drinking Water does not have the resources to review each product for each potential application and
since this would be beyond EPA's purview.  Information on specific products may be available
through other mechanisms:

(1)  EPA's Office of Research and Development and the National Sanitation Foundation (NSF)
International are conducting a pilot proj ect under the Environmental Technology Verification (ETV)
Program designed to provide treatment purchasers with performance data from independent third

-------
party organizations.  The EPA and NSF are cooperatively conducting this project to provide the
mechanism for "verification testing" of packaged drinking water treatment systems. This pilot proj ect
includes: development of verification protocols and test plans; independent testing and validation of
packaged equipment; partnerships among test/verification entities to obtain credible  cost  and
performance data; and preparation of product verification reports for wide-spread distribution. It will
be through the distribution of this data by which EPA expects the greatest amount of performance
information sharing, leading to efficient and effective technology applications to meet safe drinking
water goals.  (For more information on this project consult the NSF-ETV Web site http://www.
nsf.org/verification/verification.html)

(2) The National Drinking Water Clearinghouse,  at West Virginia  University, has developed the
RESULTS database. RESULTS was designed as an electronic means to access data on small water
treatment systems  employing  both conventional and non-conventional treatment technologies.
Information and on-site contacts may be obtained on these treatment applications. (Clearinghouse:
phone (304)293-4191, or Web  site http://www.ndwc.wvu.edu)

    Finally, it is likely that this  SWTR and TCR listing may in future years develop in tandem with
or eventually merge with the long-term enhanced surface water treatment requirements (LTESWTR).
Obviously, as EPA develops information on technologies applicable to small public water systems for
microbial control under the SWTR and LTESWTR these efforts may completely merge.

Section 1.6:  Stakeholder Involvement

    EPA held stakeholder meetings in Washington, D.C., on July 22 and 23, 1997, and May 18 and
19, 1998. Stakeholders at the  meetings included representatives of States, public water systems,
trade associations, and equipment manufacturers.  At the 1998 meeting the proposed draft 1998
listings for SWTR and TCR were presented to stakeholders.  Stakeholders were asked to consider
the revised compliance technology information, and to provide comments.

Section 1.7: Key Stakeholder Input

    The May 18-19, 1998 SWTR/TCR stakeholder discussions centered  on EPA's tabulation of
listed and "emerging" technologies for the SWTR, and to a lesser extent on TCR technologies. EPA
tables provided detailed information on the following technology-specific subject areas: treatment
efficacy,  including ranges of microbial  inactivation; treatment complexity and operator skill levels
required; byproducts formed (both chemical and physical byproducts of treatment); raw water quality
concerns; and other important limitations of the listed treatments. Stakeholder discussions were very
fruitful and resulted  in several proposed changes to EPA's draft listing:

     !    Stakeholders suggested that EPA group several technologies into the "advanced oxidation"
         heading; and, that modifications to traditional ultraviolet radiation be grouped together as
         "advanced ultraviolet" treatment. Both  groups are considered emerging treatments for
         small drinking water systems. [Stakeholders generally agreed with EPA that the above-

-------
         referenced treatment groups  should still be considered "emerging" due to significant gaps
         in information: such  as the the lack of availability of treatment efficacy data and/or
         operational data in a small systems or drinking water setting.  It was also noted that the
         above-cited EPA/NSF verification program may provide results on the testing of some of
         the disinfection technologies later in the year, and that results may be available prior to the
         next listing for the subject microbial regulations.
     !    EPA was advised to note (in guidance) that bag filters should be handled carefully due to
         the fragility of the materials, and that seals on cartridge filters can damage and require
         special attention.
     !    EPA was advised that in reference to bag and cartridge filtration it would not be advisable
         to specify maximum raw water turbidity levels (i.e., the 2 to 3 NTU cited). Such limits may
         be more a function of pretreatment and system economy, and that levels up to 10- 30 NTU
         have been treated successfully.
     !    EPA was advised as to the use of ozonation at many small systems in the U. S. and that the
         International Ozone Association has recently compiled and presented operational case study
         data (copies  of  a tabulated listing  and  presentation by R.  Rice  at the  May 1998
         NSF/WHO/PAHO Small  Systems Symposium were provided); however, it is generally
         believed that "advanced" combinations involving ozone have yet to be demonstrated or
         even practical for small supplies; ozone representatives also pointed  out that previously
         cited cleaning problems have been largely overcome in the past 5 years due to use of pure
         oxygen feeds (in lieu of air feed) to newer ozone generators.
     !    It was generally agreed by the participants that an annual update to the SWTR listing of
         technologies would be appropriate in order to capture any developments in the treatment
         technology field.
     !    Relative  to the proposed TCR listing  of compliance technologies, no  specific changes or
         sustantive comments were received.

EPA received and reviewed additional information from other sources who were  not present at the
stakeholder meeting, and these  are cited as needed within Chapter 2 technology discussions.

Section 1.8: Organization of the Document

    This guidance document is organized into chapters describing the small systems compliance
treatment technologies for the SWTR and  TCR. Chapter  1 discusses the requirements of the 1996
SDWA Amendments and the approach EPA is following to meet those requirements.  Chapter 2
discusses the technologies that were evaluated including those previously listed by EPA in 1997. The
listing is found also in tabular format at the end of the chapter. Chapter 3 contains the Total Coliform
Rule compliance technology listing. Chapter 4 contains emerging technologies and additional criteria
that may require  further consideration  prior to future technology listings. Appendices contain
relavant background information.

-------
 2. COMPLIANCE TECHNOLOGY LIST FOR SWTR

Section 2.1:  Background of the Surface Water Treatment Rule

    The SWTR, published in the Federal Register on June 29,  1989,  set national standards for
treating public surface water supplies and ground water supplies under the direct influence of surface
water. The SWTR includes: (1) criteria under which filtration is required and procedures by which
the States are to determine which systems must install filtration; and (2) disinfection requirements.
The filtration and disinfection requirements are treatment technique requirements to protect the public
against  potential adverse health effects of exposure to the protozoa  Giardia lamblia, viruses,
Legionella, and heterotrophic bacteria, as well as many other pathogenic organisms that are removed
by these treatment techniques. The SWTR also contains certain limits on turbidity as criteria for: (1)
determining whether a public water system is required to filter; and (2) determining whether filtration
is alone adequate. [Note: additional surface water treatment requirements for small water systems
are expected to come into effect under the Long Term Enhanced Surface Water Treatment Rule
(LTESWTR), including provisions for control of Cryptosporidium through filtration  and revised
turbidity standards.  These will be addressed as in subsequent listings.]

Section 2.2:  Technologies Evaluated for the Compliance Technology List

    The SWTR enables EPA to issue "log removal credits" to water utilities through requirements
for particular water treatments, rather than a requirement for utilities to meet an MCL: a microbial
MCL would require the technically difficult feat of monitoring for the microorganisms. Inactivation
requirements are 99.9% (3 log) for Giardia cysts and 99.99% (4 log) for viruses. The inactivation
requirements can be met through disinfection alone or a combination of filtration and disinfection.
The 1989 SWTR listed four filtration technologies: conventional filtration including sedimentation;
direct filtration;  diatomaceous  earth filtration; and slow sand filtration. Disinfection treatment is
required to follow all of these filtration treatments. The disinfection technologies listed in the 1989
SWTR were chlorine, ozone, chlorine dioxide, and chloramines. Additional filtration and disinfection
technologies were subsequently listed by EPA as discussed below.

      In 1997 EPA began evaluating information on the originally listed technologies and several
alternate technologies (i.e., treatments not listed in the 1989 rule), for SWTR application at small
public water supplies. Among the alternative treatments considered were: mixed-oxidant disinfection
(on-site oxidant generation); ultraviolet (UV) disinfection; four membrane filtration technologies
(reverse osmosis, microfiltration, ultrafiltration, nanofiltration); bag filtration; and cartridge filtration.
The Agency presented a proposed listing of these technologies and,  after receiving considerable input
from its stakeholders, listed all the proposed technologies in August 1997 (EPA 815-R-97-002). In
addition, while some small system caveats were included in that listing, the technologies were listed
for all the SDWA-specified small system size categories. As part  of the  1997 listing EPA included
abbreviated information on any known limitations regarding each of the compliance technologies;
operator skill levels; and other issues that would be important to consider before site-specific choices
are made.

-------
    EPA undertook the following in 1998: (1) to further organize specific operational characteristics
of treatment and data on treatment efficacy, and to specify any other known limitations on the listed
treatments; and (2) to determine if other emerging treatments may be considered viable for the SWTR
small systems compliance technology listing. The emerging treatments were identified as advanced
oxidation (or perozone),  pulsed ultraviolet, and ultraviolet oxidation (i.e., UV plus peroxide or
ozone).

    In identifying the disinfection and filtration  compliance technologies in this chapter, EPA
discusses disinfection technologies in Section 2.3; pilot testing for filtration treatment systems in
Section 2.4; and  filtration technologies in  Section 2.5;  also, a tabular summary of compliance
technologies for the SWTR is provided in Section 2.6.

    EPA notes that the listing  of SWTR technologies is not intended to be a comprehensive or
exclusive list.  Systems may choose alternative treatment technologies: i.e., technologies not listed
which may be found to meet the requirements of the SWTR.   EPA lists in Chapter 4 "emerging
technologies" that in the future may be evaluated more fully and, if found applicable, would be listed
as small systems compliance technologies under SWTR.

    The removal and/or inactivation of target or surrogate microorganisms is considered the primary
test of a treatment technology's efficacy; however,  other factors are considerably important in
evaluating treatment including the plausibility of operating the system under a range of conditions.
EPA researched available information  on each disinfection and filtration treatment type and has
written up those listed in this document in accordance with available data. Most references cited are
from the published literature except in cases where ongoing research results are mentioned.  There
is not a single template from which to determine viability of a technology for listing; a certain level
of judgement is required when evaluating data on new or emerging technologies. Finally, it is noted
that additional pertinent information on each of the disinfection and filtration technologies has been
included in a table at the end of this chapter.

Section 2.3: Compliance Technology Evaluation of Disinfection  Technologies

    Since passage of the 1996  SDWA amendments, several disinfection technologies have been
evaluated by EPA as possible compliance technologies. The viability of four disinfection technologies
listed in the 1989 SWTR (i.e., free chlorine, ozone, chlorine dioxide, and preformed chloramines) was
discussed at length in the  1989 EPA  SWTR guidance  manual (3), therefore those technology
summaries in this report are relatively brief.

    CT values required for achieving a certain degree of inactivation for each disinfectant are listed
in CT tables in the above-cited  SWTR guidance manual.  CT refers  to the product of the residual
disinfectant concentration in mg/L, "C", and the disinfectant contact time in minutes,  "T".  The
disinfectant contact time is defined as the time required for the water being treated to flow from the
point of disinfectant application to a point before or at the first customer during peak hourly flow.
There is  a relationship between CT values and inactivation rates (or log inactivation) for a given

-------
disinfectant. Since the determination of log inactivation of a microbiological contaminant is more
technically demanding than the calculation of CT, CT is used as a surrogate for log inactivation for
a given disinfectant under specific water quality conditions (e.g., temperature, pH). The SWTR and
associated guidance provide CT values for free  chlorine, ozone, chlorine dioxide, and preformed
chloramines that correspond to 1-log inactivation oi Giardia lamblia cysts. Viruses are generally
inactivated at much lower dosages of disinfectant (inactivations of the more resistant surrugate MS-2
bacteriophage are in several cases mentioned in this and other reference material). Where this report
mentions information on inactivation of Cryptosporidium oocysts it is for informational purposes
since the SWTR does not specifically address Cryptosporidium.

DISINFECTION TREATMENT TECHNOLOGIES LISTED IN THE ORIGINAL SWTR

Ozone Ozone is a powerful oxidant with high disinfectant capacity. A study found that within a pH
range of 6 to 10, at 3 to 10 °C, and with ozone residuals between 0.3 to 2.0 mg/L, bacteriophage
MS-2 (a surrogate test organism) and Hepatitis A virus were completely inactivated. Inactivations
ranged from >3.9-log to >6-log, and occurred within very short contact periods (i.e., 5 seconds) (1).
A 1992 research report describes treatment studies conducted on MS-2, poliovirus, and Giardia
cysts. It found that MS-2 in natural waters are very sensitive to ozone in comparison to poliovirus
type 3.  In addition, Giardia muris and enteric viruses may be inactivated by ozone (as the primary
disinfectant) with 5 minutes contact time and ozone residuals of 0.5 to 0.6 mg/L to 3-log and 4-log
removals, respectively. The report concludes that design of ozone as a primary treatment should be
based on simple criteria including ozone contact concentrations, competing ozone demands, and a
minimum contact time to meet the required cyst and viral inactivation requirements, in combination
with USEPA guidance recommendations (2). Viral inactivation CT values for ozone were published
in the original USEPA guidance manual for the SWTR (3).

         EPA notes that ozonation technology requires  careful monitoring for ozone leaks which
pose a hazard. Also, use of ozonation may increase biodegradable organics in water which may affect
distributed water quality.  Additional treatment may be used as necessary.  Also, where bromides
are present in raw water there is an increased potential for formation of disinfection byproducts, i.e.,
brominated organics and bromate, which should be minimised.  Secondary disinfection with chlorine
or chloramines may help in this regard, by balancing treatment needs with the need for also protecting
distributed water quality.

    It has been brought to EPA's attention at stakeholder meetings that recent advancements in
ozonation technology include use of high purity  oxygen  feed systems, rather than ambient air feed
systems. Ozonation treatment is therefore said to run  cleaner and require less cleaning-related
maintenance than had the earlier versions of this  technology.

    EPA has reviewed survey data submitted by the International Ozone Association and found that
ozonation has been applied at many drinking water treatment facilities in the U. S. Ozonation systems
with capacities greater than 100,000 gal/day, as well as small water systems serving as little as 500
gal/day, have been documented (4,5). Ozonation, according to these same sources, is often applied
                                            10

-------
for drinking water disinfection as well as for other water treatment objectives, such as for oxidation
of dissolved iron and manganese, and control of taste and odor and/or trihalomethanes. Ozonation
technology for the subject public water system application is available from a number of suppliers.
Ozone treatment is a listed compliance technology for all size categories of public water systems.

 References

1. Hall, R.M., and Sobsey, M.D.  Inactivation of Hepatitis A Virus and MS2 by Ozone and Ozone-
Hydrogen Peroxide in Buffered Water.  Water Science and Technology, Vol. 27, No. 3-4, pp. 371-
378.

2. Finch,  G.R., Labatiuk, C.W., Helmer, R.D. and Belosevic, M.   Ozone and Ozone-Peroxide
Disinfection ofGiardia and Viruses.  Prepared for AWWA Research Foundation, Denver (1992).

3. U. S. Environmental Protection Agency. Guidance Manual for Compliance with the Filtration and
Disinfection Requirements for Public Water Systems Using Surface Water Sources (1989 and 1991).

4. Dimitriou, M.A.  Letter with  attachments attributed to R.G. Rice, from the International Ozone
Association to U.S. Environmental Protection Agency, May 23, 1997.

5. Rice, R. Small (<10,000 persons or < 1 MGD) U.S. Potable Water Treatment Plants  Using
Ozone- In Operation.  Assembled for the International Ozone Association. March 11, 1998.

Chlorine  Chlorine in its several forms is the most widely used disinfectant at public water supplies.
Hypochlorites are available in solid (e.g., tablet) or liquid (solution pump-fed) forms.  The use of
gaseous chlorination (while available) at small water supplies may not be among the best disinfection
options due to the hazardous nature of the material. Use of gaseous chlorine places greater demand
on the need for isolated plant space, on providing trained and attentive operating staff and their
protection from any hazards, and, possibly, on liability issues which may boost insurance costs for
small public water systems.

    Stakeholders have indicated that provision of adequate CTs for chlorination may be problematic
and require additional consideration, particularly where contact time (basins) may be an expensive
option for small  systems.  However, stakeholders agree that all public  water supply systems,
regardless of size, would benefit from the listing of chlorine for meeting the SWTR. Chlorination
technologies for even the smallest public water system applications are available, in gaseous, solid and
liquid-feed forms, from a number of suppliers.  Cautions regarding use of gaseous chlorine are
appropriate, and attention should be paid to staffing and their protection, as noted above. Use of
hypochlorite solutions also warrants the following precautions: with time the disinfectant strength of
the solution decreases; and, toxic chlorate levels in solution can increase. Awareness regarding the
potential for producing elevated levels of halogenated disinfect on by products, e.g., trihalomethanes,
inorganic  byproducts, and others, is also essential.  Chlorination  treatment is a listed compliance
technology for all size categories of public water systems.
                                            11

-------
Reference

1. U.S. Environmental Protect! on Agency. Guidance Manual for Compliance with the Filtration and
Disinfection Requirements for Public Water Systems Using Surface Water Sources (1989 and 1991).

Chloramines Chloramines, while possessing certain advantages over other disinfectants (e.g., long
residual effect and low production  of disinfection byproducts), have  not been widely used in
disinfection at small  public water systems.  Compared to free chlorine and ozone, chloramines
possess less potency  as a germicidal agent, and would therefore require  longer CTs; and, as noted
above, stakeholders have informed the USEPA that provision of suitable CTs  for such chemical
disinfection may be costly and/or problematic and requires adequate consideration.

    Chloramine disinfection requires careful monitoring of the ratio of added chlorine to ammonia.
Failure to do so can result in  odor and taste problems or biological instability of water in the
distribution system. Excess ammonia (i.e., low chlorine:ammonia) can promote growth of nitrifying
bacteria, which convert ammonia to nitrates and nitrates. Ammonia dose should be tempered by any
natural ammonia occurring in raw water (1).

    USEPA and stakeholders agree that all public water supply systems, regardless of size, would
benefit from the listing of chloramines  for SWTR small systems application, with the caveats
mentioned above.  The Agency has not seen documentation of applied use at small  facilities.
Chloramination technologies for even the smallest public water system applications may be available
from treatment vendors.  Chloramination is a listed compliance technology for all size categories of
public water systems.

Reference

1. White, G.C. Handbook ofChlorination and Alternate Disinfectants.  Volume 3. Van Nostrand
Co.,N.Y.,N.Y.  (1992).

Chlorine Dioxide  Chlorine dioxide, although a powerful oxidant, may be more difficult to handle
than other forms of chlorine.  Chlorine dioxide requires trained staff to manage its use and is so
reactive (thus, is consumed very readily) that it may not provide a residual disinfectant in the
distribution system.  Photochemical decomposition of C1O2 in reservoirs  may increase chlorate
concentrations,  and other factors including the generation process used and  water pH can affect
chlorate and chlorite levels.   The  Agency  has  not  seen documentation of applied use of this
technology at small  facilities.   However, stakeholders have urged USEPA not to exclude this
treatment  for disinfection.  It is noted that chlorine dioxide units for small  public water system
applications may be available from treatment vendors.  Chlorine dioxide  is a listed treatment for all
categories of public water systems.

ADDITIONAL LISTED DISINFECTION TREATMENT TECHNOLOGIES
                                           12

-------
UV Radiation Ultraviolet (UV) radiation has been found to be an effective disinfectant in treatment
of relatively clean source waters.  Historically, UV has been adapted to disinfect reclaimed water,
treated sewage, industrial process water, and small groundwater supplies.  Simplicity of installation,
ease of operation and maintenance, and low costs relative to chemical disinfection, make UV a useful
small  systems disinfection technology option.   Stakeholders have suggested that users of this
technology consider UV within the framework of the multiple barrier approach as put forward by the
Agency under the SWTR.

    UV radiation as a germicidal agent is effectively applied at a wavelength of 253.7 nanometers
(or a range of 250-270 nanometers) through application of low-pressure mercury lamps.  Other
wavelengths are effective in the destruction of chemical contaminants, but this is not addressed in this
guidance.   UV dose is expressed in units of milliwatt-sec per square centimeter (mW-sec/cm2), the
product of the intensity (I) of the UV lamp (mW/cm2) and time (T) of exposure (sec). UV treatment
of water is therefore comparable to the CT as described above for chemical disinfection, since UV
dose is expressed in terms of the IT values.

    The relatively resistant test organisms MS-2 and Bacillus subtilis have been inactivated by UV
at a level of 3-logs at dosages of approximately 20 to 40 mWsec/cm2, and a level of 4-logs at dosages
of approximately 60 to 90 mWsec/cm2. These test results  were reported in a 1996 USEPA overview
of UV disinfection efficacy, operation, and cost (1).  In addition, a recent pilot study on groundwater
containing 0.65 ppm iron indicated a 4-log inactivation of MS-2 at 87 mWsec/cm2 (2). These doses
would likely inactivate  poliovirus, Hepatitis A, and rotavirus. Rotavirus, a UV-resistant virus, was
the subject of testing  in buffered,  distilled water, which yielded 3- and 4-log inactivations  at
approximately 30 and 40 mWsec/cm2, respectively  (3).

    Research has confirmed that UV effectiveness is relatively insensitive  to temperature and pH
differences, and  that application of UV  as  a primary disinfectant (followed by chlorination  or
chloramination) does not contribute to disinfection by-product formation. In addition, UV application
was found not to convert nitrate to nitrite or bromide to bromines or bromates (3).

    However, it has long been observed that turbidity,  natural  organics, iron, calcium hardness,
suspended solids, and  other factors can  reduce  UV transmission  and cause  lamp fouling, thus
lowering disinfection effectiveness. Studies have tracked UV performance and transmission, through
use of new-generation electronic UV sensors.  (Some older UV sensors exhibited erratic readings and
a loss of performance overtime.) Testing found that correlations may be established between system
performance (MS-2 inactivation) and UV sensor readings.  This may prove invaluable in maintaining
the reliability of UV sensor readings. Bioassay techniques and chemical actinometry were cited by
researchers as tools available for obtaining appropriate correlations, and for recalibrating sensors
periodically.  The same studies found that manual cleaning of fouled UV sleeves and sensors, with
commercially-available, 20 percent muriatic acid solution, was effective and not labor-intensive, i.e.,
requiring one-half to one hour of labor (2).

    The UV dose needed for a particular application may vary depending on source water quality.


                                            13

-------
A suggested lower bound of 38 mWsec/cm2 is based on ANSI/NSF standard 55, which is intended
for disinfecting visually clear water pre-filtered for cyst reduction.  That dose corresponds to an
approximate 4-log rotavirus inactivation, utilizing no multiplier/factor-of-safety. An upper bound of
140  mWsec/cm2 is based on above-cited  lab and field study data, i.e.,  4-log viral  or MS-2
inactivations (1, 4), and use of a factor-of-safety or multiplier of 2 to 3.

[Note: Table E-14 of the SWTR Guidance Manual, Inactivation of Viruses by UV, was based on less
resistant Hepatitis A virus, at 2- and 3-log inactivations in lab-prepared media. The current guidance
may be more conservative in approaching UV design needs.]

    Protozoan cysts require greater UV doses  for inactivation.  For example, one test in a distilled
water medium indicated a 2-log inactivation ofGiardia lamblia at a UV dose of 180 mWsec/cm2 and
a 1-log inactivation ofGiardia lamblia at a UV dose of approximately 40 mWsec/cm2 (5). A factor
of safety or multiplier of 2 to 3 applied to this dosage produces a dose of 80 to 120 mWsec/cm2 to
achieve a 1-log inactivations ofGiardia lamblia.  As a practical matter, conventional UV systems
may not be cost effective for control ofGiardia at greater than 1-log removal, although  advanced
ultraviolet treatment systems which may produce 2- to 4-log inactivations of Cryptosporidium are
being investigated (see Chapter 4) for potential application under the forthcoming EPA Enhanced
Surface Water Treatment Regulation.

    In addition to pretreatment and/or automatic cleaning systems to remove above-cited dissolved
and/or suspended materials, which can impede UV performance, a secondary disinfectant is necessary
to provide a residual protection of water in distribution systems. Continuous dose measurement,
remote alarms, automatic cleaning of UV components, and annual UV sensor maintenance may also
be important design components to prevent deposition or scaling and to minimize on-site operator
attention. UV treatment systems appear to be commercially available for drinking water application,
within the dose ranges suggested above. Ultraviolet disinfection is a listed technology for all three
categories of small public water  systems.

[Note: The Agency expects, as data become available, to improve upon and possibly refine the
recommended UV doses for meeting viral inactivations requirements. In addition, EPA briefly
discusses as "emerging" technologies the following variations on conventional UV treatment: pulsed
UV; medium pressure UV; and UV oxidation (i.e., as used in combination with peroxide or ozone
(see Chapter 4).]

References

1. U.S. Environmental Protection Agency.  Ultraviolet Light Disinfection Technology in Drinking
Water Application: An Overview.  Office of Water. EPA 81 l-R-96-002 (1996).

2. Snicer, G.A.,  Malley,  J.P., Margolin, A.B. and Hogan,  S.P.  Evaluation of Ultraviolet (UV)
Technology for Groundwater Disinfection.  Prepared for AWWA Research Foundation, Denver
(1997).
                                            14

-------
3. Malley, J.P., Shaw, J.P, and Roppy. J.R.  Evaluation of By-Products Produced by Treatment of
Groundwaters With Ultraviolet Irradiation. Prepared for AWWA Research Foundation, Denver
(1995).

4. Wilson, B.R. et al.  Coliphage MS-2 as  a UV Water Disinfection Efficacy Test Surrogate for
Bacterial and Viral Pathogens.   Proceedings  of Water Quality Technology Conference; Part I,
Toronto, Canada (1993).

5. Karanis, P., et al. UV Sensitivity of Protozoan Parasites. Journal of Water Supply Research and
Technology-Aqua. Vol. 41, No. 2, pp. 95-100 (1992).

On-Site Oxidant Generation (Also known as anodic oxidation and salt brine electrolysis) On-site
oxidant generation may be accomplished by an electrolytic process which generates a concentrated
solution of oxidants, mainly free chlorine.   This process involves passage of an electric current
through a continuous-flow brine (salt) solution within a cell.   The electrolyzed brine solution
containing the  concentrated disinfectant is injected into water  for treatment.  The concentrated
solution is diluted approximately one hundred-fold in drinking water treatment.

    EPA's previous listing included "mixed oxidant disinfection," and the Agency has decided to
characterize this technology in another manner.  Recently completed research, as discussed below,
has not determined that additional oxidants  (other than free chlorine) are produced to a significant
degree by the electrolytic action within this process.  In its application this treatment is similar to
chlorination, however rather than apply commercially available gaseous,  solid or liquid forms of
chlorine, the process produces a strong disinfectant solution on-site. This treatment method has been
successfully tested, applied, and accepted mainly due to the convenience, ease of operation, and basic
level of operator skill required.

    On-site oxidant generators have been  reported to produce  multiple oxidants.  However, the
individual oxidants in  solution have  proven to  be difficult to characterize.    Recent research,
sponsored by EPA, investigated the composition of the generated  solutions as well as the analytical
techniques available for measurement of the individual species. Lab and full-scale units were studied,
and a variety of analytical methods and chemical masking techniques were tested for blocking the
interference of free chlorine in the measurement of ozone in solution. The experiments confirmed that
chlorine is the primary oxidant in the electrolyzed  solution (measured at  200 to 400 mg/L), with
ozone, hydrogen peroxide, and chlorine dioxide undetected. Lab-prepared solutions containing free
chlorine and ozone were also tested and it was shown that, due to the rapid rate of reaction between
the two oxidants (in the millisecond time-scale),  any ozone that may be in solution becomes, in a very
short time, unavailable for the purpose of disinfection. Based on kinetic studies, ozone levels were
calculated by researchers to be less than 0.5  mg/L immediately following generation (1).

    It may be assumed until further investigations bear results that units of this type may use various
grades of raw material, salt, and this may in turn result in differing amounts of oxidants and associated
byproducts in solution.  It is noteworthy that this process may also produce chlorate (C1O3") and
                                            15

-------
bromate (BrO3") in solution: the former species being a function of free chlorine decomposition, the
latter, a human carcinogen, is produced as a result of reactions with bromide in the salt used in
preparation of the electrolytic solution.  The above-cited study (1) reported relatively low levels of
chlorite, chlorate and bromate ions in solution in concentrated anolyte liquor (less than 0.05 mg/L
chlorite, and 1 to 2 mg/L both chlorate and bromate in full-scale system); the study also detected
bromate in finished water but was not specific about concentration.

    Researchers have studied the effects on-site electrolysed salt brine disinfection in relation to
Cryptosporidium oocysts and Clostridiumperfringens spores as an indicator of oocyst inactivation:
at a dosage of 5 mg/L, mixed oxidation achieved greater than 2-1 og Cryptosporidium inactivation at
1-hour contact time (2).  A technical report by the Los Alamos Technical Associates, Inc., reported
a 4-log inactivation of/ f-2 bacteriophage in water at a relatively short contact time, i.e., CT of 4 (3).
In order to provide a complete and useful set of data, studies on inactivation of Cryptosporidium are
under way by EPA (4) and by others, including the American Water Works Research Foundation,
with results anticipated in 1999.

    On-site oxidant generation for disinfection purposes has been used in full scale water treatment
applications at a variety  of locations. Field applications have indicated the ease of operation and
effectiveness  of these systems.   Examples of full-scale applications of  on-site  generation  of
disinfectants, in several U.S. states, may provide some guidance to interested parties on the use and
efficacy of this technology.

    Given that on-site generation of oxidants may have advantages over other treatment methods,
EPA suggests that small systems consider this disinfection technique for compliance purposes. Given
information  regarding the  disinfectant  generated, EPA  suggests taking a  course  of utilizing
chlorination CT tables when designating chemical dosing for these systems.  Additional studies in
1998-99 may yield appropriate data on CT requirements for this technology.

References

1. Gordon, G.  "Electrochemical Mixed Oxidant Treatment: Chemical Detail of Electrolyzed Salt
Brine Technology." Miami University Department of Chemistry and Biochemistry, Oxford OH.
Prepared for IT Corporation and U.S. Environmental Protection Agency.  May,  1998.

2. Venczel, L.V., Arrowood, M., Kurd, M., Sobsey, M.D., "Inactivation of Cryptosporidiumparvum
Oocysts and Clostridium perfringens Spores by a Mixed-Oxidant Disinfection and by Free Chlorine,"
Applied and Environmental Microbiology (April 1997): 1598-1601.

3. Bradford, W.L., Baker, F.A. Design, Fabrication and Testing of a Laboratory Test Electrolytic
Water Disinfection Unit (EWDU): Adendum Number 2.  Los Alamos Technical Report LATA/MX-
94/0009.  Los Alamos Technical Associates, Inc.  Los Alamos, NM (1994).

4.  Goodrich,  J.  Personal communication with Marc Parrotta.  U.S. Environmental Protection
                                            16

-------
Agency (June 1998).

Section 2.4:  Degree of Pilot testing for New Filtration  Technologies on the Compliance
Technology List

    The current SWTR lists four types of filtration technologies and associated requirements. These
are described in 40 CFR §141.73(a) - (d): (1) conventional filtration treatment or direct filtration; (2)
slow  sand  filtration; (3)  diatomaceous earth filtration; and  (4)  other (alternative)  filtration
technologies. A public water system could not use an alternative filtration technology unless it could
demonstrate to the State through the use of pilot plant studies or other means that the technology,
in combination with disinfection as described under §141.72(b), meets the required three log removal
ofGiardia and four log removal of viruses.

    For these alternative filtration technologies, there are typically two stages of evaluation prior to
approval.   The first stage is to determine if the process effectively  removes the contaminants of
concern. The second stage is to determine if the individual system can effectively operate the process
and to assess site-specific considerations that can affect the technology's performance. Under the
SWTR, the filtration processes listed in §141.73(a)-(c) already meet the first stage requirement, but
generally require some degree of site-specific testing to meet the second stage. The "other filtration
technologies" [§141.73(d)] require pilot testing to meet both criteria.

    For alternative filtration technologies on the SWTR compliance technology list, the national-level
pilot testing for viability may be waived under §141.73(d). Pilot plant studies are just one mechanism
identified in § 141.73 (d) to demonstrate that the process is capable of meeting the goals of the SWTR.
The filtration technology can be demonstrated  using "other means" besides pilot testing.  Those
alternative filtration technologies on the compliance technology list have been determined by EPA
to be effective under § 141.73(d) and thus do not require national-level pilot testing for viability. This
puts new filtration technologies  on the same regulatory footing  as the technologies  listed in
§141.73(a) - (c) in terms  of national-level pilot testing.  A State may still require site-specific pilot
testing to assess factors that affect technology performance for all of the compliance technologies.
A State may as a practical measure require  such testing to demonstrate that a system is capable of
operating  a given treatment process.

    For filtration technologies that are not on the compliance technology list, the existing mechanism
in the SWTR for alternative filtration technologies can still be used. Pilot testing for viability could
be required for these systems under §141.73(d).

Section 2.5: Compliance Technology Evaluation of Filtration Technologies

    Filtration technologies have been evaluated and listed as  compliance technologies.  Since the
viability of the four technologies listed in § 141.73(a)-(c) has already been summarized in the SWTR
guidance manual, those technology summaries do not contain all information previously reported by
EPA.  (Appendix B contains references published on the filtration technologies listed in the SWTR
                                            17

-------
since 1989.)  Seven filtration technologies have been added as compliance technologies for small
systems. Summary information on the filtration technologies is included in a table at the end of this
chapter.

FILTRATION TREATMENT TECHNOLOGIES LISTED IN THE 1989 SWTR

    Filtration is the most commonly used treatment for reducing turbidity and microbial contaminant
levels in domestic water supplies. Common drinking water filtration processes involve passing water
through a filter media to remove suspended particulate material, larger colloidal materials, and, for
some filter media,  to reduce levels of smaller colloidal and dissolved contaminants. Examples of
suspended particulates include clay and silt, microorganisms, humic and other aggregated organic
materials, and aluminum and  iron oxide precipitates.  Typical filter  media include  silica sand,
diatomaceous earth, garnet or ilmenite, and a combination of coarse anthracite coal overlaying finer
sand. Filtration may involve single media, dual media (e.g., coal-sand), and tri-media (e.g., an added
third layer of sand). Filtration may be rapid or slow, depending upon the application, and may involve
different removal processes, cleaning methods, and operation methods (1, 2, 3).

    The filtration technologies discussed in this section are used to remove suspended particulate
matter from water.  For filtration processes  that involve  the addition of a chemical coagulant,
coagulation refers  to the complex process of particle aggregation within a water being treated,
including coagulant formation, particle destabilization (surface charge alteration of suspended
particles), and inter-particle collisions. Flocculation may be considered a part of the  coagulation
process and refers to the process of promoting inter-particle collisions and thus the aggregation of
larger particles (floe).   Larger suspended particles may be removed  by simple filtration or by
sedimentation (gravity settling) or flotation (floe rises to the surface and is skimmed off).  Simple
filtration involves the physical trapping of suspended particles that are larger than the pore volumes
of the filter media; the bulk water passes through unimpeded and leaves the particles behind. As finer
suspended particles pass through the filter medium, they are destabilized,  resulting in coagulation and
adherence to the filter medium (2, 4).  In the case of slow sand filtration, which does not involve the
addition  of coagulants, colloidal and  dissolved  organic materials may be removed by biological
processes in the schmutzdecke ("black layer"  or biologically-active layer) and in the filter medium
below.  In the case of direct filtration, which  requires influent water with much less turbidity, the
coagulation and flocculation step is followed immediately by filtration. Since there is less aggregated
material to remove, sedimentation or flotation is not required to prolong the filter cycle.  Some
dissolved chemicals may be removed by chemical sorption at the surface of the filter media, especially
in the cases of higher surface area filter media (e.g., fine sand and diatomaceous earth), but these
processes account  for much less of the bulk contaminant removal compared to physical sorption
processes (1, 2, 3,  5).

    For the purposes of meeting the performance criteria  under the SWTR and to protect public
health, disinfection treatment is applied following filtration.

    In regard to improving the operation of fitration plants, recent advances in telemetry devices
                                            18

-------
have made it possible for a single operator to remotely monitor and operate one or more small water
systems within a given area.  These "circuit rider" operators can work from a central location,
receiving information (including alarms) from the various plants via FAX or modem. Remote control
capabilities allow the operator to control certain aspects of the treatment process (e.g., chemical
coagulant or disinfection dosage) via modem or other means.  This reduces operator costs, and can
reduce the amount of chemicals required for treatment (6).  These telemetric devices may make
technologies that require full-time operator attention more feasible for many small systems. The
combined use of package  plants and telemetric monitoring may well extend the use of the more
complex water treatment technologies to the universe of small systems.

    The following technologies are listed in this guidance as compliance technologies for all three
size categories of small public water systems; disinfection is assumed to follow filtration treatment.
The first four filtration technologies were listed and described in the SWTR (5).

Conventional Filtration  and Specific Variations  Conventional filtration includes chemical
coagulation, rapid mixing, and flocculation, followed by floe removal via sedimentation (or flotation).
The clarified water is then  filtered. Common filter media designs include sand, dual-media, and tri-
media. Design criteria for specific sites are influenced by site-specific conditions and thus individual
components of the treatment train may vary in design criteria  between systems.  Conventional
treatment has demonstrated removal efficiencies greater than 99% for viruses and 97 to 99.9% (rapid
filtration with coagulation  and  sedimentation) for Giardia lamblia (5).

    There are a variety of coagulation/filtration package plants applicable to small systems (2, 6, 7,
8). In package plants that utilize sedimentation, the sedimentation step usually occurs in tube settlers.
In  "dual-stage   filtration"  (8,  9),   the  sedimentation  step  is  replaced  by   a  passive
flocculation/clarification step that occurs in an initial "depth clarifier" tank. The clarified water is then
passed through a depth filter.  Other modes of clarification are possible, including the use  of the
various upflow and downflow flocculation/filtration processes,  also known as "roughing  filter"
processes.  Typically, roughing filters are not as versatile as  sedimentation or flotation, but some
varieties may perform comparably.  One example of a package  plant of this type uses a buoyant
crushed plastic medium used in an upflow mode as a contact flocculator and roughing filter ahead of
a downflow triple-media bed (2). Coagulation/filtration package units have demonstrated the ability
to effectively remove turbidity, color,  disinfection by-product precursors, viruses, bacteria,  and
protozoa (e.g., Cryptosporidium and Giardia cysts) (6, 7, 8, 9).

    The dissolved air flotation (DAF) process includes coagulation and flocculation, but instead of
gravity sedimentation, the floe is carried up  to the water surface by rising air bubbles, where the floe
can be skimmed off (2, 6, 10). DAF may be more applicable than other  conventional filtration
systems for removing particulate matter that does not readily  settle, e.g., algae-rich waters, highly
colored waters, low turbidity/low alkalinity waters, and cold waters. DAF is less appropriate for very
turbid waters due to their higher silt and clay contents.  The National Research Council suggests an
upper turbidity limit of 30 to 50 NTU for small systems using DAF (6).  For lower turbidity waters,
DAF performance is comparable to  conventional filtration employing sedimentation, and may be


                                            19

-------
superior in removal of turbidity, especially low density turbidity (11).

    Conventional filtration is the most widely used technology for treating surface water supplies for
turbidity and microbial contaminants, but may be less applicable to the smallest water system size
category (those serving 25 to 500 persons)  due to relatively high costs and technical complexity.
Although conventional filtration has the advantage that it can treat a wide range of water qualities,
it has the disadvantage that it requires advanced operator skill and has high monitoring requirements.
Thus, small systems without access to a skilled operator should not use conventional treatment, given
that waterborne pathogens are acute contaminants and that the disruption of chemical pre-treatment
can lead  to  pathogen introduction into the distribution system (2, 6,  9).  The performance of
conventional filtration is extremely sensitive to the proper management of the coagulation chemistry
involved; if the coagulation step is disrupted or improperly executed, the removal efficiencies for
turbidity and microbiological contaminants  decrease dramatically in a matter of minutes.  For this
reason, EPA suggests that only those systems with full-time access to a skilled operator use
conventional filtration.

Direct filtration Direct filtration has several effective variations; all direct filtration systems include
a chemical coagulation step followed by rapid mixing, and all exclude the use of a sedimentation or
other clarification step prior to filtration. Following chemical mix, water is filtered through dual- or
mixed-media filters using pressure  or gravity units. Pressure units, which are used primarily by small
systems (2),  have the advantage of not requiring repumping for delivery of the filtrate to the point of
use. Gravity units have the advantage of allowing easy visual inspection of the filter medium during
and after backwash. In addition to the mode of filtration, variations of direct filtration include filter
media type and mixing requirements. In-line filtration (12) is the simplest form of direct filtration and
consists of filters preceded by direct influent chemical  feed and static mixing. In general, direct
filtration usually requires low turbidity raw water and is attractive because of its low cost relative to
conventional treatment (12,13). The National Research Council (6) has suggested that small systems
not use direct filtration for waters with average turbidities above 10 NTU  or maximum turbidities
above 20 NTU.  Two  other important considerations are color and algae.  Since color removal
requires coagulant additions in proportion to the  degree of color,  an upper limit of color is
appropriate for direction filtration. An AWWA Committee report (14) suggests an upper limit of 40
color  units.  Algae removal must be  evaluated on a case by case basis.  Direct  filtration has
demonstrated removal efficiencies of 90 to 99%  for viruses, 50% for  Giardia lamblia without
coagulation, and 95-99% for Giardia lamblia with coagulation pre-treatment (5).

    Direct filtration has the disadvantage  that it requires advanced  operator skill and has high
monitoring requirements.  Thus, small systems without access to a skilled operator should not use
direct filtration, given that waterborne pathogens are acute contaminants and that the disruption of
chemical pre-treatment can lead to pathogen introduction into the distribution system (2, 3, 6).  The
performance of direct filtration is extremely sensitive to the proper management of the coagulation
chemistry  involved;  if the coagulation step  is disrupted or improperly  executed, the  removal
efficiencies for  turbidity and microbiological contaminants decrease  dramatically in a matter of
minutes. For this reason, EPA suggests that only those systems with full-time access to a skilled
operator use direct filtration.

                                            20

-------
Slow sand filtration  Slow sand filters are simple, are easily used by small systems, and have been
adapted to package plant construction (6, 7). Slow sand filters are similar to single media rapid-rate
filters in some respects, but there are crucial differences in the mechanisms employed (other than the
obvious difference in flow rate). The schmutzdecke, the top-most, biologically active layer of filter,
removes suspended organic materials and microorganisms by biodegradation and other processes,
rather than relying solely on simple filter straining or physico-chemical sorption. Advantages of slow
sand filtration include its low maintenance requirements (since it does not require backwashing and
requires less frequent cleaning) and the fact that its efficiency does not depend on actions of the
operator.  However,  slow sand filters do require time for the schmutzdecke to develop after each
cleaning: during this "ripening period," however, filter performance steadily improves. The ripening
period  can last from six hours to two weeks, but typically requires less than two days.  A two day
filter-to-waste period is recommended for typical sand filters (2). Since few remedies are available
to an operator when the process is ineffective, particularly if a system has little storage capacity, slow
sand filtration should be used with caution and should not be used without pretreatment or process
modifications (e.g., GAC  layer addition) unless the raw water is low in turbidity, algae, and color
(15). Package plant versions with a granular activated carbon layer located beneath the slow sand
can adsorb organic materials that are resistant enough to biodegradation to pass through  the
schmutzdecke. When used with source water of the appropriate quality, slow sand filtration may be
the most suitable filtration technology for small systems (6).  Slow sand filtration has demonstrated
removal efficiencies in the 90 to 99.9999% range for viruses and greater than 99.99% for Giardia
lamblia (5).

Diatomaceous earth (DE) filtration DE filtration, also known as pre-coat or diatomite filtration,
can be  used to directly treat low turbidity raw water supplies or chemically  coagulated, more turbid
water sources . DE filters consist of a pre-coat layer of DE, approximately 1/8-inch thick, supported
by a septum or filter element. To properly maintain the DE pre-coat layer, and to maintain porosity,
treatment  is supplemented  by a continuous-body feed of diatomite  and recycled filtered water.
Intermittant operation of DE filters is not advised unless the system recycles water through the filter
during  production down times.  Maintaining the filter in this manner optimizes performance, extends
the filtration cycle, and lowers filter maintenance requirements.

    Normally the DE filter is backwashed and the septum cleaned after each break in filtration. Then
a fresh  layer of precoat is applied. If changes in water quality occur, body feed rates may be adjusted
immediately and/or a re-precoat may be applied.  DE filtration plants can be designed to make such
adjustments automatically.

    DE filtration is very effective for removing Giardia cysts, but filtration studies with plain DE
have not indicated a marked capability to remove very small particles, e.g., viruses (2, 6,16).  Some
research has shown that specific modifications can lead to 99 percent virus removal (2). In addition,
recent studies have indicated excellent removal rates (e.g., 6-1 og) of Cryptosporidium oocysts for DE
grades  commonly used by smaller systems (17)  .

     Since chemical coagulation is not required, DE filtration is very attractive as a small systems
technology and it has been used successfully by small systems for many years. Waters that are low

                                            21

-------
in turbidity, color and other organic matter (disinfection by-product precursors) are most suitable for
direct application of DE technology (6).

References

1.  U.S.  Environmental Protection  Agency. "Technologies  and Costs for the Removal of
Microbiological Contaminants from Potable Water Supplies". October 1988.

2.  Cleasby,  John  L.  "Filtration".  AWWA, Water Quality  and Treatment: A Handbook of
Community Water Supplies, 4 ed. Pontius, F.W., ed.  McGraw-Hill, Inc. New York. 1990.

3. Letterman, R.D. Filtration Strategies to Meet the Surface Water Treatment Rule.  American
Water Works Association. Denver, CO. 1991.

4. Stumm, W. and Morgan, James J.  Aquatic Chemistry, 2nded. John Wiley and Sons, Inc. New
York.  1981.

5. U.S. Environmental Protection Agency. 40 CFR Parts 141 and 142. Drinking Water;  National
Primary Drinking Water  Regulations; Filtration, Disinfection; Turbidity, Giardia lamblia, Viruses,
Legionella, and Heterotrophic Bacteria; Final Rule.  Federal Register, 27486, V. 54, N. 124, June
29, 1989.

6. National Research Council (NRC).  Safe Water From Every Tap: Improving Water Service to
Small Communities. National Academy Press.  Washington, DC. 1997.

7. Campbell, Susan, Lykins, B.W., Jr., Goodrich, J.A., Post, D., and Lay, T.  "Package plants for
small systems: afield study". Journal of the American Water Works Association. November, 1995.
pp. 39-47.

8. Brigano, F.A., McFarland, J.P., Shanaghan, P.E., and Burton, B.  "Dual-Stage Filtration Proves
Cost Effective". Journal of the American Water Works Association. May 1994. p. 75.

9. Horn, J.B., Hendricks, D.W., Scanlan, J.M., Rozelle, L.T., and Trnka, C.  "Removing Giardia
Cysts and Other Particles from Low Turbidity Waters Using Dual-Stage Filtration".  Journal of the
American  Water  Works Association.  February 1988.  pp. 68-77.

10.   American  Water  Works  Association.   "International  Conference Examines Flotation
Technology". Journal of the American Water Works Association. March 1994. p. 26.

11. Malley,  J.P., Jr. and Edzwald,  J.K.  "Laboratory Comparison of DAF with Conventional
Treatment". Journal of the American Water Works Association. September 1991. pp.  56-61.

12. U.S. Environmental Protection Agency. "Very Small Systems Best Available Cost Document".
September 1993.

                                           22

-------
13. Westerhoff et al. "Plant-Scale Comparison of Direct Filtration Versus Conventional Treatment
of a Lake Erie Water".  Journal of the American Water Works Association. March 1980. p. 148.

14. AWWA Committee Report. "The Status of Direct Filtration". Journal of the American Water
Works Association.  July 1980. p. 405.

15. Cleasby,J.L. "Source Water Quality and Pre-treatment Options for Slow Sand Filters". Chapter
3 in Slow Sand Filtration. Gary Logsdon, ed. American Society of Civil Engineers.  New York.
1991.

16. Logsdon, Gary S.  "Comparison of Some Filtration Processes Appropriate for Giardia Cyst
Removal". Presented at the Calgary Giardia Conference, Calgary, Alberta, Canada. February 23-25,
1987.

17. Ongerth, I.E. and Hutton, P.E.  "DE Filtration to Remove Cryptosporidium".  Journal of the
American Water Works Association. December 1997. p. 39.

ADDITIONAL LISTED FILTRATION TREATMENT TECHNOLOGIES

                                  Membrane Processes

    The four treatments listed below are membrane processes, which make use of pressure-driven
semi-permeable membrane filters.  Membranes are manufactured in a variety of configurations,
materials and pore size distributions.  The selection of membrane treatment for a particular drinking
water application would be determined by a number of factors, such as: targeted material(s) to be
removed, source water quality characteristics, treated water quality  requirements, membrane pore
size, molecular weight cutoff (MWCO), membrane materials and system/treatment configuration (1).
    The membrane technologies listed below have been historically employed for specific drinking
water uses: (1) reverse osmosis treatment in a high pressure mode, in removal of salts from brackish
water and seawater; (2) nanofiltration, also referred to as membrane softening or low pressure RO,
in removal of calcium and magnesium ions (hardness) and/or  natural organics and disinfection
byproducts control; (3) ultrafiltration, characterized by a wide band of MWCs and pore sizes, for
removal of specific dissolved organics (e.g., humic substances, for control of disinfection byproducts
in finished water) and for removing particulates;  and (4) microfHtration, as  with ultrafiltration
utilizing low operating pressures, for removal of particulates including pathogenic cysts (1, 2).

    Pre-filtration and scale-inhibiting chemical addition may be utilized to protect membranes from
plugging effects, fouling and/or scaling, and to  reduce operational and maintenance costs.  For the
purposes of meeting the performance criteria under the SWTR and as a safety measure, a disinfectant
is commonly applied following membrane treatment to protect distributed water quality.

    Stakeholders have requested that USEPA include the following information as part of the listing

                                           23

-------
of these technologies: (1) the degree of operator skill level, which often depends on water quality and
amount of pre- and post-treatment required; (2) higher operator skills are often needed for chemical
cleaning  of membranes;  (3) test piloting of membrane filtration  systems may be required; (4)
monitoring of membrane  integrity, as well as alarm and back-up systems, may be required but that
state reviewers should have latitude to decide on such requirements; (5) while the first two listed
membrane treatments are absolute barriers  to viruses, it should be noted that ultrafiltration and
microfiltration are not, therefore the latter two should not be given credit for viral reductions; (6) no
distinction is  made in terms of membrane configuration type, e.g., spiral bound or other, in this
guidance; (7) regarding other treatment goals, microfiltration will pass all organic  compounds in
water whereas ultrafiltration will capture some organics; and, (8) since designations of membrane
absolute  or nominal  pore size have often been  irregularly specified, causing some confusion in
interpreting a membrane's exclusion capability,  state  reviewers  may wish to request  specific
information from manufacturers or suppliers for particular applications.

    The following membrane processes are listed SWTR technologies for all three categories of small
public water systems:

Reverse Osmosis (RO) Filtration RO is a listed technology for all three categories of small public
water systems. Due to typical RO membrane pore sizes and size exclusion capability (in the metallic
ion and aqueous salt range), RO filtration is  effective for removal of cysts, bacteria and viruses (2,
3); however, RO produces the most wasted  water, at between 25-50% of the feed.
Disinfection is also recommeded to ensure safety of water.

Nanofiltration (NF) NF  is  a listed technology for all three categories of small public water systems.
Due to typical NF membrane pore sizes and  size exclusion capability (1  nanometer range, e.g.,
organic compounds), NF is  effective for removal of cysts, bacteria and viruses. Disinfection is also
recommeded to ensure safety of water.

Ultrafiltration (UF) UF  is  a listed technology for all three categories of small public water systems.
Due to typical UF membrane pore sizes and  size exclusion capability (e.g., 0.01 micron, molecular/
macromolecular range), UF  is effective for absolute removal ofGiardia cysts and partial removal of
bacteria and viruses, and when used in combination with  disinfection appears to control these
microorganisms in water (4,5). Tests have also shown that filtrate turbidity may be kept consistently
at or below 0.1  NTU (6).  Due to the importance of disinfection providing a second barrier to
contamination,  and due  to stakeholders'  above-mentioned concern regarding maintenance  of
additional non-membrane treatment for viral inactivation credit, EPA stresses the need for disinfection
in conjunction with membrane treatment.

Microfiltration (MF) MF is a listed technology for all three categories of small public water systems.
Due to typical MF membrane pore sizes  and  size exclusion (e.g., 0.1 to 0.2 micron, macro-
molecular/microparticle range), MF is effective for absolute removal of Giardia cysts and partial
removal of bacteria and viruses, and when used in combination with disinfection appears to control
these microorganisms in water (4, 5).  Tests have also determined that filtrate turbidity may be kept
below 0.2 NTU (7),  typically at or below 0.1 NTU (6).  Due to the importance of disinfection

                                           24

-------
providing a second barrier to contamination, and due to stakeholders'  above-mentioned concern
regarding maintenance of additional non-membrane treatment for viral inactivation credit, EPA
stresses the need for disinfection in conjunction with membrane treatment.
References

1. Jacangelo, J.G. The Development of Membrane Technology. International Report (IR 3) Water
Supply: Review Journal of the International Water Supply Association. Vol. 9, Numbers 3/4 (1991).

2. Taylor, J.S., Duranceau, S.J., Barrett, W.M., and Goigel, J.F.  Assessment of Potable  Water
Membrane Applications and Research Needs. Prepared for AWWA Research Foundation, Denver
(1989).

3. U. S. Environmental Protection Agency. Guidance Manual for Compliance with the Filtration and
Disinfection Requirements for Public Water Systems Using Surface Water Sources (1989 & 1991).

4. Jacangelo, J.G., Adham, S., and Laine, J-M. Application ofMembrane Filtration Techniques for
Compliance With the Surface Water and Groundwater Treatment Rules. Prepared for AWWA
Research Foundation, Denver (1995).

5. Jacangelo, J.G., Laine, J-M., Cams, K.E., Cummins, E.W., and Mallevialle, J. "Low-Pressure
Membrane Filtration for Removing Giardia and Microbial Indicators."  JournAWWA, September,
1991.

6. Letterman,  R.D. et al.  Evaluation  of Alternative Surface  Water Treatment Technologies.
Sponsored by New York State Department of Health (1991).

7. Olivieri, V.P., Parker, D.Y., Willinghan, G.A. and Vickers, J.C. ContinuousMicrofiltration of
Surface Water.  AWWA Seminar Proceedings: Membrane Technologies in the Water Industry.
AWWA Membrane Processes Conference, Orlando (1991).

                           Bag and Cartridge Type Filtration

Bag filtration  Bag filtration systems are based on the physical screening process to remove particles.
If the pore size of the bag filter is small enough, parasite removal will occur (1). In a bag filtration
unit system, water to be treated passes through a  bag-shaped  filter where the particulates are
collected allowing filtered water to pass to the outside of the bag (2). Bag filters are manufactured
and supplied by a variety of companies. Bags are available in a variety of material compositions and
pore size  ratings (typically from 1 to 40 micron).  The sizing of the bag filtration component is
conditional on  the on raw water quality, including the amount of particulate matter and turbidity (3).
 Unless the quality of the raw water precludes the need for pre-treatment, EPA  recommends
pretreatment of the raw water using sand or multimedia  filters, followed by preliminary bag or
cartridge filters of 10 micron or larger pore size, and the use of 1-5 micron filters as final filters to

                                           25

-------
increase particulate removal efficiencies and to extend the life of the filter (2, 4).  Contingent on the
filter manufacturer,  bag filters can accommodate turbidity units from 0.1 to 10.0 NTU and flow
between  10 and 50  gpm (4). However, the bag filters will only last a few hours when turbidity
consistently exceeds 1 NTU.

    Bag filters in combination with cartridge filtration units have been used to  remove Giardia
lamblia at several locations serving small systems (3, 5). Bag filter studies have shown mixed results
in the removal of Cryptosporidium, ranging from approximately  70%  to 99.9% (1).  Studies of
various membranes using beads as surrogates for Cryptosporidium oocysts also  showed variability
in the removal of this organism (6).

    Bag filtration field testing also showed poor to excellent reductions in turbidity.  However, this
variability might be  due to improper installation of the units, leaks or tears in the systems, or local
water quality conditions, or as a result of problems with pre-filters (2, 4).  In any case, general trends
in field experience seems to show that the smaller the pore size rating, the better the filter efficiency.

    Stakeholders emphasized that bag filters have been successfully used in water systems across the
country.  Site-specific pilot testing has been used to determine applicability at individual systems. The
stakeholders also identified two other factors that can lead to variability in performance.  The bag
filter must fit the housing, and different manufacturer's products may not be interchangeable. Some
products use nominal pore size ratings rather than absolute pore size ratings, and since nominal pore
size ratings refer to some average pore size rather than the largest, particles larger than the nominal
pore size may pass through the filter.

    Stakeholders have indicated that bags can be fragile and that care must be taken  during
installation of replacements, to prevent bag tearing. They also noted that monitoring of filter integrity
may be needed, but  that State reviewers should have the latitude to decide on such requirements.

    To further inactivate microorganisms, the final filter effluent would need disinfection to meet the
SWTR requirements.

    Bag filters have been used successfully in water systems across the country. One key to success
is preliminary pilot  testing  of the process to ensure adequate removals.   Pilot testing prior to
installation of a bag filter is recommended to address any performance variability factors. Bag filters
are best suited for systems in the first two small system size categories (i.e., systems serving up
to 3,300).  However, bag filters are listed  as a compliance technology for all three system size
categories.

References

1.  Goodrich,  J.A.    and Fox, K.  R.,  "Small  System  Control of Cryptosporidium  for  WQA
Recertification Credit,"  Water Conditioning and Purification (February 1996): 50-58.

2. New York State  Department of Health Bureau of Public Water Supply Protection, Alternative

                                            26

-------
Technology Filtration Study, May 1993.

3. Brandt, B. '"Remote Control' Used to Fight Giardia," Journal of the American Water Works
Association v 86 n 2 Feb 1994. p 137-138..

4. Smith, G.G., Small Surface Water Systems Alternate Filtration Report. Minnesota Department
of Health, June 1994.

5. The Greeley-Polhemus Group, Inc. and Malcolm Pirnie, Inc., "Case Studies Assessing Low-Cost,
In-Place Technologies At Small Water Systems," Prepared for The Association of State Drinking
Water Administrators.  July 1992.

6. Goodrich, J.A. et al, "Cost and Performance Evaluations of Alternate Filtration Technologies for
Small Systems." Proceedings of the American Water Works Association, Annual Convention, 1995.

Cartridge filtration  Cartridge filtration relies  on a simple physical screening process to remove
particles.  Due to materials used and the direction of flow, these are distinct from bag filters.  Small
pore size openings prevent passage of contaminants through the filter (1). Typical cartridge filters
are pressure filters withglass fiber or ceramic membranes, or strings wrapped around a filter element,
housed in a pressure vessel (2).  The pleating allows for higher surface area for filtration. These
filters are manufactured and supplied by a variety of companies with different pore size ratings (0.3
to 80 micron) and materials (2, 3).  Similar to bag filtration, these units are very compact and do not
require much space.

     The pore size rating of the cartridge filtration component used is dependent on the on raw water
quality, including the amount of particulate matter and the turbidity (3).   Depending on the quality
of the raw water, prefiltration of the raw water using sand or multimedia filter, followed by bag or
cartridge filters of 10 microns or larger pore size as preliminary filter, and the use of 1-5 micron filters
as final filters are recommended to increase particulate removal efficiencies and to extend the life of
the filter (6, 7).

     Cartridge filters can be used for  removal  of Giardia lamblia (2, 3, 4).  Filtration studies
conducted by EPA to determine Cryptosporidium removal using beads as surrogates showed that
cartridge filtration with 2 micron rated units exhibited log removals of 3.51 and 3.68 (5).

     Stakeholders emphasized that cartridge filters have been successfully used in water  systems
across the country.  Site-specific pilot testing was  used to  determine  applicability at individual
systems. The stakeholders also identified a factor that can lead to variability in performance.  Some
products use nominal pore size ratings rather than absolute pore size ratings. Since nominal pore size
ratings refer to some average pore size rather than the largest, particles larger than the nominal pore
size may pass through the filter.

     Stakeholders have noted that cartridge filter seals are subject to damage, and that the housing
material may be improperly specified, resulting in leakage and/or other treatment malfunctions; they

                                            27

-------
also have noted that monitoring of filter integrity may need to be required, but that State reviewers
should have the latitude to decide on such requirements.

    To further inactivate the microorganisms, the final filter effluent would need disinfection to meet
the SWTR requirements.

    Cartridge filters have been used successfully in water system across the country for up to ten
years.  One key to success is upfront pilot testing of the process to ensure adequate removals. Pilot
testing prior to installation of a cartridge filter is recommended to ensure adequate performance.
Cartridge filters are best suited for systems in the first two small system size categories (i.e.,
those serving up to 3,300 people).  However, cartridge filters are listed as a compliance technology
for all three system size categories.

References

1.  Goodrich,  J.A.  and Fox, K.R.   "Small System  Control  of Cryptosporidium for WQA
Recertification Credit." Water Conditioning and Purification (February 1996): 50-58.

2. U.S. Environmental Protection Agency.  "Very Small  Systems Best Available Technology Cost
Document".  September 1993.

3. Brandt, Barbara '"Remote control' used to fight Giardia," Journal of the American Water Works
Association, v. 86 n. 2,  pp. 137-138. February 1994.

4. The Greeley-Polhemus Group, Inc. and Malcolm Pirnie, Inc. "Case Studies Assessing Low-Cost,
In-Place Technologies At Small Water Systems," Prepared for The Association of State Drinking
Water Administrators. July 1992.

5. Goodrich, J.A. et al, "Cost and Performance Evaluations of Alternate Filtration Technologies for
Small Systems." Proceedings of the American Water Works Association Annual Convention, 1995.

6. New York State Department of Health Bureau of Public Water Supply Protection. Alternative
Technology Filtration Study, May 1993.

7. Smith,  G.G.  Small Surface Water Systems Alternate Filtration Report. Minnesota Department
of Health, June 1994.

Backwashable depth filtration Backwashable depth filters operate in part like cartridge filters in
that water flows radially inward allowing the process of particle screening. In one system, bundles
of fibers (the filter medium) are rotated and compressed  during the  filtration mode; monitoring of
pressure is used to indicate clogging, which triggers a reverse flow of washwater under pressure;
during  the backwash cycle the fibers are relaxed, stretched and squeezed to allow for the release of
trapped deposits. Tests in Europe have indicated greater than 2-log removal of the relatively small
microorganism, Cryptosporidium (1)(2).

                                           28

-------
    The NSF International protocol for  testing backwashable  depth filters (3) describes the
technology as such:  a  bag filter,  cartridge  filter, or granular  media  filter intended to  filter
uncoagulated water and designed to be backwashed when terminal head loss is attained or turbidity
breakthrough occurs. The protocol notes that surface waters of high quality are the most appropriate
waters for backwashable depth filters, and that feed water turbidity may not be an adequate indicator
of suitability for this treatment. Parti culate matter may consist of incompressible and/or compressible
substances such as algae or other biological matter (compressible particles being more problematic,
affecting frequency of filter backwashing).   Therefore, the volume of water treated prior to
backwashing may vary greatly depending on the type of particulate matter in source water. NSF also
cautions that since backwashable depth filters are not intended to remove viruses, the burden of virus
control falls entirely on the disinfection process.

    EPA finds that backwashable depth filters, while not used and tested extensively  in the  U.S.,
present similar characteristics as the above cited bag and cartridge filters. These filters may be best
suited for systems in the first two  small system size categories ( i.e., those serving  up to 3,300
people).  However, backwashable depth filters are listed as a compliance technology for all  three
small system size categories.

References
1.  Ives, KJ.  et al.   "An Evaluation  of the Effectiveness of the Fibrotex Filter in Removing
Cryptosporidial Oocysts from a Surface Water Supply." Protozoan Parasites and Water. Edited by
W.B. Betts, et al., University of York, United Kingdom (1995).

2.  Bernhardt, H. et al.   "Investigations  of  the Retention Efficiency of Fibrotex Filters for
Cryptosporidium  Oocysts Applying Low Turbid Waters  from  a  Water  Treatment Plant."
Unpublished study by Wahnbacktalsperrenverband Siegburg,  Universitat Bonn, and Kalsep Ltd.

3.  NSF International.  Draft NSF Equipment Verification  Testing  Plan: Backwashable Depth
Filtration for the Removal of Microbiological and particulate Contaminants (1998).

Section 2.6: Summary of Compliance Technologies for the SWTR

    The following Tables l(a) and l(b), on  disinfection and filtration  treatments, respectively,
summarize the current listing of small water system compliance technologies for the SWTR. Water
system managers and other reviewers should examine the several columns included in this tablulation.
The filtration and the disinfection treatment tables  each are split into Parts 1 and 2 to accomodate the
information categories presented. Limitations included in the tabulation are also described in the text
of this chapter, and in references cited.  The technologies are listed for all three of the  subject size
categories unless otherwise indicated.

    EPA has assigned each technology a level of complexity, reflective of ease of treatment operation
and, quite generally, the level of operator skill and knowledge that would be required to run the water
treatment plant to meet the subject regulations. If a given treatment is operationally complex, or

                                            29

-------
"advanced," then the plant operator must have some form of training for such "advanced" treatment.
    The tables characterize the skill level for each listed technology, ranging from basic, through
intermediate and advanced. For a unit technology that requires "basic operator skill", an operator
with minimal experience in the water treatment field can perform the necessary system operation and
monitoring if provided with  written instruction.  "Intermediate operator skill" implies that the
operator understands the  principles of water treatment and has a knowledge of the regulatory
framework. "Advanced operator skill" implies that the operator possesses a thorough understanding
of the principles of system operation, including water treatment and regulatory requirements. If
pretreatment is required at a given site, it may be assumed that the required operator skill levels will
increase; likewise, if certain features of a treatment train advance technologically, such that operation
is simplified or automated, then skill level may decrease. Further information on skill levels may be
found in publications by the American Water Works Association, and in protocols developed by the
NSF International under the previously-cited treatment verification program.

    The SWTR compliance  technology list includes new technological, operational, and other
information not listed previously by EPA.  Information is  provided on important  raw water
parameters, chemical and physical byproducts produced, and other possible limitations that should
be considered in selection and design of treatment.  The following tabulation is meant for quick
reference regarding the listed compliance treatment technologies. It should be recognized that site-
specific conditions may preclude certain applications, and that conditions may necessitate other forms
or variants of the listed treatment to maximize control of the subject microbiological contaminants.
                                            30

-------
                          Table la.   SURFACE WATER TREATMENT COMPLIANCE TECHNOLOGY TABLE
                                                   DISINFECTION TECHNOLOGIES (Part 1)
     Unit
 Technologies
            Removals:
 Log Giardia & Log Virus w/CT's
         indicated in ()J
    Complexity:
  Ease of Operation
   (Operator Skill)
                         Raw Water, Pretreatment
                       & Other Water Quality Issues
Free Chlorine
3 log (104) & 4 log (6)
Basic
Better with high quality. Pretreatment may be needed to reduce disinfection
byproduct (DBF) precursors; and/or to reduce pH, turbidity, and/or chlorine dose.  If
high potential for DBFs, chloramination may be best for distribution protection.
Where Fe/Mn high, sequestration or physical removal may be needed.
Ozone
3 log (1.43) & 4 log (1.0)
Intermediate
Better with high quality. pH 7 to 9 and/or above normal temperatures may increase
cyst inactivations.  Pretreatment may control DBF formation; and Fe/Mn may
necessitate sequestration or physical removal.
Chloramines
3 log (1850) & 4 log (1491)
Intermediate
Better with high quality. Excess ammonia (low C12 to N ratio) can promote growth
of nitrifying bacteria in filters, which convert ammonia to nitrates and nitrites;
nitrification in covered reservoirs also likely. Ammonia dose should be tempered by
natural ammonia levels in water.
Ultraviolet
Radiation
1 log Giardia (80-120) &
4 log viruses (90-140) mWsec/cm2
doses in parentheses2
Basic
Relatively clean source water required. UV adsorption (e.g., Fe, NOM) and scattering
constituents (e.g., particles) affect dosage for microbial inactivation, and therefore
system design/cost. Data indicate strong correlation between dose required and iron;
bench-scale studies using microbial surrogate recommended.3
On-Site
Oxidant
Generation
Research pending on CT values
Basic
Better with high quality. Other factors: Chlorine production rates may vary; CT
based on chlorination is suggested. See also Free Chlorine.
         JCT (Concentration x Time), in mg-min/L, based upon 1989 Surface Water Treatment Rule Guidance Manual.  Temp. IOC,
 mid-pH range, unless otherwise indicated.

         UV dose is product of mW/cm2 (intensity) x sec (time); bases of viral inactivation ranges are rotavirus and MS-2 tests (see text).

         3Unpublished research results of Malley et al. (1997-98) suggest correlations; groundwater principally studied.

                                                                  31

-------
Chlorine
Dioxide
3 log (23) & 4 log (25)
Intermediate
Better with high quality. DBFs include chlorite and chlorate.  Photochemical
decomposition of C1O2 in uncovered reservoirs may increase chlorate concentrations
in water. Generation process, pH, and other factors, can affect chlorate/chlorite
levels.
                                                                     32

-------
Table la. SURFACE WATER TREATMENT COMPLIANCE TECHNOLOGY TABLE
DISINFECTION TECHNOLOGIES (Part 2)
Unit Technologies
Free Chlorine
Ozone
Chloramines
Chlorine Dioxide
On-site Oxidant
Generation
Ultraviolet Radiation
Disinfection Byproducts
Concerns
Trihalomethanes, haloacetic acids,
aldehydes, inorganic byproducts,
others.
Organic acids, aldehydes, AOC, and
others. If bromide present, brominated
organics and bromate.


Chlorate (C1O3~), bromate (BrO3~), and
chlorinated THMs
NA
Other Limitations
Fe and Mn demand, pH and other factors influence dose. DBF production
should be monitored where precursors occur. Providing adequate CT
(time/storage) may be a problem for some supplies. Chlorine gas requires
special caution in handling and storage, and operator training.
Ozone leaks represent hazard: air monitoring required. Ozone used as primary
disinfectant (i.e., no residual protection). Biodegradable organics may affect
distributed water quality. Personnel time requirements for system cleaning may
be fairly substantial.
Long CT. Requires care in monitoring of ratio of added chlorine to ammonia.
Storage and handling precautions: exposure to heat, sunlight, or UV light may
decrease product strength; spillage would require rapid recovery /sumps, and
access to water for cleanup.
Research will determine CT values appropriate for electolyzed salt brine. Other
oxidants (other thatn chlorine) not detected in solution by significant research
effort.
No disinfectant residual protection for distributed water. Periodic calibration of
UV sensors and other special maintenance may be required.
33

-------
                    Table Ib.  SURFACE WATER TREATMENT COMPLIANCE TECHNOLOGY TABLE
                                            FILTRATION TECHNOLOGIES (Part 1)
    Unit Technologies
           Removals:
     Log Giardia & Log Virus
                        Raw Water, Pretreatment
                      & Other Water Quality Issues
Conventional Filtration and
Specific Variations on
Conventional
2-3 log Giardia & 1 log viruses
Wide range of water quality. DAF more applicable for removing
particulate matter that doesn't readily settle: algae, high color, low turbidity
(up to 30-50 NTU) and low-density turbidity.  Prior to filtration: chemical
coagulation, rapid mix, flocculation, sedimentation or flotation (depth
clarifiers or roughing filters may replace sedimentation).
Direct Filtration
0.5 log Giardia & 1-2 log
viruses (and 1.5-2 log Giardia
with w/coagulation)
Suggested limits: average turbidity 10 NTU; maximum turbidity 20 NTU;
40 color units; algae on a case-by-case basis4.  Prior to filtration: chemical
coagulation and rapid mixing.
Slow Sand Filtration
4 log Giardia & 1-6 log viruses
"Schmutzdecke" formation prerequisite. Pretreatment or process
modifications required if raw water high in turbidity, color, and/or algae.
Diatomaceous Earth
Filtration
Very effective for Giardia (2
to3-log) and Cryptosporidium
(up to 6-log); low bacteria and
virus removal
Low turbidity, low color water; low organic DBF precursors.  Pretreatment
may be used to decrease turbidity and DBF precursors, although chemical
coagulation is not typically necessary.
        4National Research Council, Committee on Small Water Supply Systems. "Safe Water From Every Tap: Improving Water
  Service to Small Communities." National Academy Press, Washington, D.C. (1997).
                                                            34

-------
Reverse Osmosis
Very effective, absolute barrier
(cysts and viruses)
May require conventional or other pretreatment for surface water to
protect membrane surfaces: may include turbidity or Fe/Mn removal;
stabilization to prevent scaling; reduction of dissolved solids or hardness;
pH adjustment.5
Nanofiltration
Very effective, absolute barrier
(cysts and viruses)
Very high quality or pretreatment required (e.g., micro- or ultra-filtration to
reduce fouling/extend cleaning intervals).6  See also Reverse Osmosis
pretreatments, above.
Ultrafiltration
Very effective Giardia, >5-6
log7; Partial removal viruses
(disinfect for virus credit)
High quality or pretreatment required (e.g., microfiltration).  TOC rejection
generally low, so if DBF precursors are a concern, NF may be preferable.
Microfiltration
Very effective Giardia, >5-6 log;
Partial removal viruses
(disinfect for virus credit)
High quality or pretreatment required. Same note as for ultrafiltration
regarding TOC.
Cartridge/
Bag/Backwashable Depth
Filtration
Variable Giardia removal &
Disinfection required for virus
removal
Very high quality or pretreatment required, due to low particulate loading
capacity. Depending on raw water quality, sand or multi-media prefilter,
and 10 micron preliminary filter prior to 1 to 5 micron filter, recommended.
See also NSF protocols.
        5Ref "Recommended Standards for Water Works."  Policy Statement on Reverse Osmosis Treatment by the Great Lakes-
 Upper Mississippi River Board of State Public Health & Environmental Managers (1997).

        6Ref. Chellam, S. Et al., "Effect of Pretreatment on Surface Water Nanofiltration." JAWWA, October 1997 (Vol. 89, Issue 10).
 And, Lozier, J., et al, "Integrated Membrane Treatment in Alaska," JAWWA, October 1997 (Vol. 89, Issue 10). It is noted that the use
 of microfiltration as pretreatment may not result in removal of all foulants, i.e., nanofilters may require more frequent chemical cleaning
 than when ultrafilter is used as pretreatment.

        7Ref Adham,S.S, Jacangelo, J.G., and Laine, J.M. "Characteristics and Costs of MF and UF Plants." JAWWA, May 1996.

                                                            35

-------
                    Table Ib. SURFACE WATER TREATMENT COMPLIANCE TECHNOLOGY TABLE
                                               FILTRATION TECHNOLOGIES (Part 2)
     Unit Technologies
       Complexity:
    Ease of Operation
   (Operator Skill Level)
     Secondary Waste
        Generation
            Other Limitations/Drawbacks
Conventional Filtration and
Specific Variations on
Conventional
Advanced
Sludge (varying solids %),
backwash, filter to waste
High monitoring requirements; full-time operator or
"circuit rider" attention.
Direct Filtration
Advanced
Filter backwash
High monitoring requirements; full-time operator or
"circuit rider" attention.
Slow Sand Filtration
Basic
Filter cake. Filter to waste
(2-day) each ripening period
Algae (especially seasonal blooms) in raw water can clog
filters and cause variations in run length. Not very
effective in removal of DBF precursors or color.  Most
effective on high quality source water, i.e., those of low
turbidity, algae and color.
Diatomaceous Earth
Intermediate
Diatomaceous filter residue
(substantial amounts)
Intermittent operation of DE filters not advised unless the
system recycles water through the filter: this will extend
the filtration cycle and lower filter maintenance.  Low raw
water turbidity/color water.
Reverse Osmosis
Intermediate: increases with
pre/post-treatment and
membrane cleaning needs.
Briney waste. High volume,
e.g.,25 to 50 percent. May
be toxic to some species
Bypassing of water (to provide blended/stabilized
distributed water) cannot be practiced at risk of increasing
microbial concentrations in finished water. Post-
disinfection required under regulation, and recommended
as a safety measure and for residual maintenance. Other
post-treatments may include degassing of CO2 or H2S,
and pH adjustment.
Nanofiltration
Intermediate: increases with
pre/post-treatment and
membrane cleaning needs.
Concentrated waste. 5 to 20
percent volume
Disinfection required under regulation, and recommended
as a safety measure and residual protection.
                                                                       36

-------
Ultrafiltration
Basicincreases with
pre/post-treatment and
membrane cleaning needs.
Concentrated waste. 5 to 20
percent volume. Waste may
include sand, silt, clays,
cysts, algae, viruses and
humic material (Ref. 2).
Disinfection required for viral inactivation.
Microfiltration
Basicincreases with
pre/post-treatment and
membrane cleaning needs.
Low volume waste may
include sand, silt, clays,
cysts, and algae.
Disinfection required for viral inactivation.
Cartridge/Bag/Backwashable
Depth Filtration
Basic
Discarding of cartridges and
filters. Backwashable depth
filters may be equipped with
inactivation devices to
disinfect waste.
Requires relatively pure raw water.  Care must be taken
not to damage clean cartridges, or tear bags, upon
installation. Cartridge replacement may be frequent,
increasing O&M requirements. Algae and fragments of
biological material may disrupt filter. Disinfection is
required for viral inactivation, i.e., disinfection CxT,
following filtration. May be more applicable to systems
serving fewer than 3,300.
                                                                          37

-------
3.  COMPLIANCE TECHNOLOGIES FOR THE TOTAL COLIFORM  RULE

    EPA promulgated the total coliform rule (TCR) in June 1989. The TCR contains a listing of "best
technologies, treatment techniques, or other means available for achieving compliance with the maximum
contaminant level (MCL) for total coliforms" [ from 40 CFR Ch. 1, § 141.63 (d)].  Listed as best techniques
under TCR are:

    •   Protection of wells from contamination (ground water)
    •   Maintenance of disinfection residual for distribution
        Proper maintenance of distribution systems
    •   Filtration and/or disinfection
        State WHPP (ground water)

At the time these techniques were codified, no specific notation as to applicability to categories of public
water system size was included.  However, with passage of the Safe Drinking Water Act of 1996, EPA is
to specify compliance technologies for three small water system size categories, defined by the Act as those
serving 10,000 -  3,301 persons; 3,300 - 501 persons;  and 500 - 25 persons.

    As mentioned in Chapter  1,  there  are no variance provisions  for regulations  that control
microbiological contamination.

    Following presentation at the May  1998 meeting with stakeholders of EPA's proposed TCR
compliance technology listing, which essentially is the same as the above-cited 1989 listing, EPA has not
received substantive  comments  on this listing.  Therefore, the Agency  is  listing the same treatment
techniques and other means for small systems compliance as were codified in the 1989 rule.

    The following Table 2  contains some explanatory comments regarding each of the treatments and
other means listed. The comments are only meant as additional guidance in that certain codes of practice
may be useful in  addressing a problem; or in terms of pointing out where additional constituents in water
may need additional attention (e.g., iron and manganese, ammonia, TFDVI precursors).

    It is also necessary to note that determining application of a treatment technique or other means to
comply would be highly dependent upon what factors are contributing to an MCL violation.  For example,
faulty maintenance procedures and/or a leaking pipeline that may have triggered an MCL violation would
obviously require a different technological response than where a compromised well structure has been
found to be the cause of microbiological pollution. In addition, depending  on the number and types of
faults that are found, a system may need to implement more than one compliance technology to adequately
safeguard its water system.
                                              38

-------
                               Table 2: TOTAL COLIFORM RULE COMPLIANCE TECHNOLOGIES
          40 CFR Ch. 1 §141,63(d)
Best Technologies or Other Means to Comply
        (Complexity Level Indicated)
                              Comments/Water Quality Concerns
Protection of wells from contamination, i.e.,
placement and construction of well(s)

                                   (Basic)
Ten States Standards and others (AWWA A100-90) apply; setback distances and protective vadose
zones; interfacing with other programs essential (e.g., source water protection program).
Maintenance of a disinfection residual for
distribution system protection

                             (Intermediate)
Source water constituents may affect disinfection: Fe/Mn, organics, ammonia, other factors may affect
dosage and water quality. TTHM production and corrosion (Pb/Cu) may be issues.  Biofilm formation
and other deposits in pipes may affect water quality.
TCR remains unspecific on type/amount of disinfectant, as each type differs in concentration, time,
temperature, pH, interaction with other constituents, etc.
Proper maintenance of distribution system: pipe
repair/replacement, main flushing programs,
storage/ reservoir and O&M programs
(including cross-connection control/ backflow
prevention), and maintenance of positive
pressure throughout
                             (Intermediate)
O&M programs particularly important for smaller systems needing to maintain water purity.  States may
vary on distribution protection measures.  See also Appendix C EPA memorandum (Issue #2) in
reference to cross-connection control as proper maintenance; and EPA's Cross-Connection Control
Manual (# EPA 570/9-89-007).
Filtration and/or Disinfection of surface water or
other groundwater under direct influence
(Subpart H/SWTR); or disinfection of
groundwater          (Basic thru Advanced)
Same issues as cited above under maintaining disinfection residual; pretreatment requirements affect
complexity of operation.

Refer to SWTR Compliance Technology List; and other regulations under development.
Groundwaters: Compliance with State Weil-
Head Protection Program
                              (Intermediate)
EPA/State WHPP implementation (per §1428 SDWA): may be used to assess vulnerability to
contamination, and in determination of sampling and sanitary survey frequencies.
                                                                  39

-------
4.  "EMERGING" TECHNOLOGIES AND ISSUES FOR FURTHER CONSIDERATION

Section 4.1: Emerging Technologies

    In 1997 EPA listed additional new or "emerging" technologies that merit further consideration as small
system compliance technologies under the SWTR and/or TCR.  The Agency stated that if found to be
viable, these newer technologies would be incorporated in forthcoming lists. Identified were the following
emerging treatments or means to comply:

  • Advanced oxidation or perozone
  • Pulsed ultraviolet
  • Ultraviolet oxidation
  • Point-of-entry (POE) devices*

*NOTE: POE treatment as a centrally managed treatment option was considered by EPA, however, the
Agency feels that POE application for addressing microbial contamination would be very limited due to
the concern for disinfecting water properly (following filtration) and the complexity of monitoring POE
systems individually.

    Stakeholders at the May 1998 meeting agreed that this listing of technologies should remain very
inclusive, and that the emerging technologies should be investigated as more data on their use become
available. Stakeholders also advised that EPA should not be overly "prescriptive" in this listing on specific
factors that would impinge on site-specific designs.  The listing should, therefore, continue to develop as
a tool for State regulatory personnel and small water system managers in their decision making.

    EPA reviewed available information and industry-supplied  data on the above emerging treatment
technologies, and determined that current data do not support the listing of the "advanced ultraviolet" and
"advanced oxidation" type processes in this context. In most cases, while appropriate in treating water
contaminated with other substances (such as organic contaminants), these treatments have not yet found
use at water systems for inactivating the target microorganisms.  Two main reasons  are cited for not
listing these as compliance technologies at this time:

    (1) The Agency has not reviewed data on inactivation by these advanced processes ofGiardia cysts
    and viruses subject to the requirements of the SWTR.

    (2) These processes may not have been tested/piloted in the field for meeting the subject regulatory
    requirements.  This may be due to a lack  of penetration into and/or acceptance within the small
    systems market at this time, or due to a perception that advanced treatments are not necessary, or may
    be  burdensome  to operate  for  smaller systems, given that  simpler, single-oxidant treatment
    technologies have proven effective for the purposes stated.

    The following is a brief summary of information EPA has reviewed on the above-mentioned advanced
treatment technologies. It should be noted that the Agency would continue to accept and review data that
may indicate progress in application of these treatments for control of microorganisms in water.
                                             40

-------
                        ADVANCED ULTRAVIOLET TREATMENTS

Pulsed Ultraviolet (UV)  Pulsed ultraviolet radiation treatment is application of UV technology to a water
column via repeated high intensity bursts (or "high power density" pulses (1)) of radiation, as opposed to
continuous wave UV application which typically applies constant but lower levels of power and irradiation.
Tests on this technology have centered  on efficacy of pulsed-UV treatment  in treating oocysts of
Cryptosporidium (2)( 3) (4), and to some extent on inactivation of bacteria (5). A study presented in 1997
indicated that a pulsed UV system had produced an approximate 2-log inactivation of Cryptosporidium
oocysts (4). EPA has not viewed data on Giardia inactivation, or small systems applications of this
technology; American Waterworks Association Research Foundation research results may be of assistance
in determining pulsed UV efficacy, likely targeting Cryptosporidium in water.

(l)LaFrenz, R. Application of Pulsed UV for Water Disinfection. Innovatech, Inc. Presented at AWWA
Water Quality Technology Conference, 1997.

(2) Cryptosporidium Testing Using Pulsed UV Light. US Centers for Disease Control, Atlanta Georgia,
February 10, 1994.

(3) Lorenzo-Lorenzo, MJ. et al. Effect of Ultraviolet Disinfection of Drinking Water on the Viability of
Cryptosporidium parvum  Oocysts. Journal of Parasitology. 79(1)67-70 (1993).

(4) Clancy, J.L. et al. Inactivation o/Cryptosporidium parvum Oocysts in Water Using Ultraviolet Light.
Clancy Environmental  Consultants,  University of Arizona, and United Water- NJ. in  collaboration:
Presented at the AWWA International Symposium on Cryptosporidium and Cryptosporidiosis, Newport
Beach CA (March 1997).

(5) Bank, H.L. et al. Bactericidal Effectiveness of Modulated UV Light.  Applied and Environmental
Microbiology, 56(12)3888-3889.

Ultraviolet Oxidation  This treatment is the combination of ultraviolet and a strong chemical oxidant such
as hydrogen peroxide (or ozone).  One study indicates 3-4 log reductions of coliphages, at doses of 10
mmol/L H2O2 and ultraviolet at 0.8 W/L (no time indicated)  (1).  One stakeholder reported that the
combination of UV and ozone has been in use overseas, though apparently not in the U.S.  Ultraviolet
oxidation appears to have been applied more so in non-drinking water settings, e.g., in control of organic
compounds in wastewater.  Testing on Giardia cysts (for characterizing of dosing requirements) have
apparently  not been conducted.   This treatment  combination may be useful  in pre-oxidizing iron,
manganese, and/or Arsenic (III) in raw water and providing disinfection credit.

(1) Rajala R.L., et al.  Effect of Advanced Oxidation Processes on Inactivation of Coliphages,  Water
Science and Technology (1995).

Other Ultraviolet Variations Other modifications of the conventional or continuous wave UV application
include:

                                              41

-------
 !   A medium pressure lamp system using a collimated beam was been pilot tested in an advanced
    wastewater treatment application, at the Montreal wastewater plant. Fecal coliforms were inactivated
    (over 3-logs) at doses of approximately 35 mWs/cm2, and other factors were investigated such as
    turbidity, particle size distribution, UV transmittance, dissolved organics and iron. Photoreactivation
    and dark repair mechanisms were found to increase microbial counts at higher UV doses (1).

 !   An advanced ultraviolet cryptosporidium inactivation device incorporates within its design two
    chambers that successively screen/trap microorganisms and irradiate them while trapped, at successive
    doses of 4,000  mWs/cm2 (i.e., total dose approx. 8,000 mWs/cm2). Results of testing have been
    presented to EPA and others: the tests indicate that greater than 4-log (99.99%) of Cryptosporidium
    oocysts were inactivated by the process in a full-scale "pilot" test; results also indicated a need to
    assess the maximal levels of inactivation, which may exceed 4-log, and to demonstrate the efficacy and
    applicability of the treatment in real world applications, i.e., beyond the test's carefully controlled trial
    conditions  (2).  An additional challenge test using E.coli bacteria and B. subtilis (more resistant
    bacterial endospores) on this same device resulted in a 4.9 log reduction in E. Coli, and a 1.3 log
    reduction in B. subtilis (3).  AWWA's Opflow (4) monthly included an article on a demonstration of
    the UV treatment unit (and ozonation) at a plant in Wisconsin.

 !   Additional  research has been conducted on medium-pressure UV systems, and on pulsed UV using
    xenon lamps. Also, thin film UV designs are being considered , possibly for reduction of dose and
    power requirements. More research may result in more efficient designs for SWTR or enhanced
    SWTR applications.

(1) Cairns, W.L., Sakamoto, G., Comair, C.B., and Gehr, R.  Assessing UV Disinfection of a Physico-
chemical Effluent by Medium Pressure Lamps Using a Collimated Beam and Pilot Plant. " Trojan
Technologies, DigiPen Computer Graphics, and McGill University in collaboration: Presented at the WEF
Specialty Conference on Effluent Disinfection Systems.  New Jersey (May 1993).

(2) Clancy, J.L.  et al. Inactivation o/Cryptosporidium parvum Oocysts in Water Using Ultraviolet Light.
Clancy Environmental  Consultants, University of Arizona, and United Water- N.J. in  collaboration:
Presented at the AWWA International Symposium on Cryptosporidium and Cryptosporidiosis, Newport
Beach CA (March 1997).

(3) Evaluation  of the Disinfection Capabilities of the Safe Water Solutions L.L.C. Cryptosporidium
Inactivation Device. Clancy Environmental Consultants, report commissioned by Safe Water Solutions
L.L.C. (December 1996).

(4) Johnson, R.C. Getting the Jump on Cryptosporidium with  UV.  Opflow: American Water Works
Association, v.23, no. 10 (October 1997).
                                              42

-------
                           ADVANCED OXIDATION PROCESSES

    Advanced oxidation processes (AOPs) are oxidation processes that generate highly reactive hydroxyl
radicals.  Hydroxyl radicals are produced by an accelerated the ozone decomposition rate, through the
addition of  hydrogen peroxide (H2O2)  and/or ultraviolet (UV) light to ozonated water.  The most
commonly used AOP is the combination of hydrogen peroxide and ozone, also referred to as peroxone or
perozone (see above section on ultraviolet oxidation for more information on the UV-chemical oxidation
disinfection process).

    Peroxide-ozone treatment has primarily been used to treat organics in water such as taste and odor
compounds and chlorinated organics.  Metropolitan Water District  (MWD) of Southern California
conducted extensive research into the removal of geosmin and 2-methylisoborneol (MIB).  MWD also
performed studies on the inactivation of microorganisms using the peroxone process. The inactivation rates
were comparable to ozone at hydrogen peroxide to ozone ratios ranging from 0.2-0.3. E. coli, MS2 and
f2 coliphages were inactivated at rates greater than 5 Iog10, and hetrotrophic plate count (HPC) bacterium
was inactivated at approximately 1.2-2.5 Iog10. In other studies, inactivation of Giardia muris cysts using
peroxone was also comparable to ozone.  The inactivation rate for Giardia muris was  2.3 ± 0.2 Iog10,
suggesting that peroxone is slightly more potent in inactivating this microbe than ozone.  This advanced
process may also be of use in lowering brominated disinfection byproducts where bromides are present.
    Regarding raw water  quality, higher levels  of alkalinity affect  the  ozone residual, increasing
microorganism inactivations.  Finch, et al., indicates O3 dose, pH, turbidity and temperature all affect
advanced oxidation efficiency. Also, above 0.5:1 application rate (hydrogen peroxide to ozone) there is no
apparent benefit; and as a precaution, above a 1:1 ratio of hydrogen peroxide to ozone the toxicity of H2O2
is an issue.

    Since the primary components in the peroxone system are ozone and hydrogen peroxide, it has the
same limitations as ozone. Peroxone can only be used as a primary disinfectant due to its high reactivity
rate; it does not maintain an appreciable residual level. Performance is based upon an optimal hydrogen
peroxide to ozone ratio of less than 0.5. Peroxone treatment may also have some small system limitations
because ozone must be generated at the point of use due to its instability, and hydrogen peroxide is
considered a hazardous material requiring secondary containment storage facilities.

    Advanced oxidation  is considered an emerging technology.  The majority  of advanced  oxidation
research as been for treatment of organics. Because of peroxone's oxidative properties, a system which
uses ozone as the primary disinfectant may want to consider advanced oxidation if they need to treat
organics as well. More studies will have to be performed before advanced oxidation becomes a common
technology for disinfection.

(1) Roy Wolfe, et al.  Inactivation of Giardia muris and Indicator Organisms Seeded in Surface Water.
ES&T,  1989

(2) Roy Wolfe, et al. Disinfection of Model Indicator Organisms in a Drinking Water Pilot Plant by using
PEROXONE. Applied & Environmental Microbiology, 1989.

                                              43

-------
(3) Rajala, R.L. et al. Effect of Advanced Oxidation Processes on Inactivation of Coliphages.
Wat. Sci. Tech., 1995.

(4) McGuire, M.J., et al. Treating Water with Peroxone: A Revolution in the Making.
WATER/Engineering & Management, May 1988.

(5) Finch, G.R. et al.  Ozone and Ozone-Peroxide Disinfection of Giardia and Viruses.
AWWARF & AWWA, 1992.
Section 4.2: Additional Issues for Consideration

    EPA will continue to seek, through voluntary submittal  by stakeholders of on-going treatment
evaluations, and through other developmental activities, new information that may be useful to users of this
guide.  It is anticipated that many of the technology issues discussed in this listing will be clarified when
further information is available. EPA particularly seeks information on treatment availability; design and
operational factors including raw water concerns and byproducts issues, system management, and of course
on treatment efficacy.

    EPA will also keep abreast of other efforts underway in the  fields of equipment testing, certification,
on-site verification, State-developed or other independently developed protocols for equipment tests,
operational issues, and other related concerns. The Agency is committed to continuing its dialogue with
stakeholders,  both in terms of identifying issues and resolving them.

    Finally, it should be noted that this listing may be viewed as a transitional listing as EPA considers
further regulations that will impact large, and small, water supplies; EPA has begun this transition  by
including in this listing data that will be of greater import to systems as they prepare to provide the next
level of control of microbial pathogens in water,  namely enhanced surface water treatment needs and
inactivation/removal of oocysts such as Cryptosporidium, which is to be addressed in later EPA rules.
Research in this area is moving rapidly, and results of national  survey data will be forthcoming. These are
expected to be of use in regard to determining suitable compliance technologies for meeting the enhanced
surface water treatment requirements.
                                              44

-------
                                 APPENDIX A

RELEVANT PARTS OF SECTIONS 1412 OF THE REVISED SAFE DRINKING WATER ACT
                (SECTION 1412(b)(4)(E)(ii) thru (v) as amended in 1996)

-------
SEC. 105. TREATMENT TECHNOLOGIES FOR SMALL SYSTEMS.

  Section 1412(b)(4)(E) (42 U.S.C. 300g-l(b)(4)(E)) is amended by
adding at the end the following:
               "(ii) List of technologies for small
             systems.—The Administrator shall include in the
             list any technology, treatment technique, or other
             means that is affordable, as determined by the
             Administrator in consultation with the States, for
             small public water systems serving—
                     "00 a population of 10,000 or
                  fewer but more than 3,300;
                     "(II) a population of 3,300 or
                  fewer but more than 500; and
                     "(III) a population of 500 or fewer
                  but more than 25;
             and that achieves compliance with the maximum
             contaminant level or treatment technique,
             including packaged or modular systems and point-
             of-entry or point-of-use treatment units. Point-
             of-entry and point-of-use treatment units shall be
             owned, controlled and maintained by the public
             water system or by a person under contract with
             the public water system to ensure proper operation
             and maintenance and compliance with the maximum
             contaminant level or treatment technique and
             equipped with mechanical warnings to ensure that
             customers are automatically notified of
             operational problems. The Administrator shall not
             include in the list any point-of-use treatment
             technology, treatment technique, or other means to
             achieve compliance with a maximum contaminant
             level or treatment technique requirement for a
             microbial contaminant (or an indicator of a
             microbial contaminant). If the American National
             Standards Institute

[[Page 110STAT. 1626]]

             has issued product standards applicable to a
             specific type of point-of-entry or point-of-use
             treatment unit, individual units of that type
             shall not be accepted for compliance with a
             maximum contaminant level or treatment technique
             requirement unless they are independently
             certified in accordance with such standards. In
             listing any technology, treatment technique, or

-------
other means pursuant to this clause, the
Administrator shall consider the quality of the
source water to be treated.
  "(iii) List of technologies that achieve
compliance.-Except as provided in clause (v), not
later than 2 years after the date of enactment of
this clause and after consultation with the
States, the Administrator shall issue a list of
technologies that achieve compliance with the
maximum contaminant level or treatment technique
for each category of public water systems
described in subclauses (I), (II), and (III) of
clause  (ii) for each national primary drinking
water regulation promulgated prior to the date of
enactment of this paragraph.
  "(iv) Additional technologies.—The
Administrator may, at any time after a national
primary drinking water regulation has been
promulgated, supplement the list of technologies
describing additional or new or innovative
treatment technologies that meet the requirements
of this  paragraph for  categories of small public
water systems described in subclauses (I), (II),
and (III) of clause (ii) that are subject to the
regulation.
    (v) <
-------
                          APPENDIX B




ADDITIONAL REFERENCES ON SWTR-APPROVED FILTRATION TECHNOLOGIES

-------
Cleasby, J.L. "Source Water Quality and Pre-treatment Options for Slow Sand Filters". Chapter 3 in Slow
Sand Filtration.  Gary Logsdon, ed. American Society of Civil Engineers.  New York.  1991.

Collins, M. Robin.  "Removing natural organic matter by conventional slow sand filtration". American
Water Works Association Journal, v. 84 (May '92) p. 80-90.

Collins, M. Robin.  Evaluating modifications to slow sand filters. American Water Works Association
Journal, v. 83 (Sept. '91) p. 62-70.

Fogel, Doug. "Removing Giardia and Cryptosporidium by slow sand filtration". American Water Works
Association Journal, v. 85 (Nov. '93) p. 77-84.

Fulton, George P. "Diatomaceous earth filtration for reduced risk water treatment." PUBLIC WORKS v.
126 (Nov. '95)  p. 34-6.

Gifford, John S. et al. "Synergistic effects of potassium permanganate and PAC in direct filtration systems
for THM precursor removal." WATER RESEARCH v. 23 (Oct. '89) p. 1305-12.

Goding, Clifford. "(Very) ancient filter medium."  WATER/ENGINEERING & MANAGEMENT v. 136
(Oct. '89) p. 36.

Graham, Nigel J. D. et al. "Evaluating the removal of color from water using direct filtration  and dual
coagulants." AMERICAN WATER WORKS ASSOCIATION JOURNAL v. 84 (May '92) p. 105-13.

Haarhoff,  Johannes, et al. "Direct filtration of Chlorella with cationic polymer."   JOURNAL OF
ENVIRONMENTAL ENGINEERING v. 115 (Apr. '89) p. 348-66.

Knocke, William R. et al. "Examining the reactions between soluble iron, DOC, and alternative oxidants
during conventional treatment." AMERICAN WATER WORKS ASSOCIATION JOURNAL v. 86 (Jan.
'94) p.  117-27.

Lay, Trudie.  "Slow sand: timeless technology for modern applications".  American Water Works
Association Journal, v. 84 (May '92) p. 10.

Leland, David E. Slow sand filtration in small systems in Oregon. American Water Works Association
Journal, v. 82 (June '90) p. 50-9.

Logsdon, Gary S. et al. "Testing direct filtration for the treatment of high-turbidity water." AMERICAN
WATERWORKS ASSOCIATION JOURNAL v. 85 (Dec. '93) p. 39-46.

Ongerth, Jerry E. "Evaluation of treatment for removing Giardia cysts." AMERICAN WATER WORKS
ASSOCIATION JOURNAL v. 82 (June '90) p. 85-96.

Nieminski, Eva C. et al. "Removing Giardia and Cryptosporidium by conventional treatment and direct
filtration."  AMERICAN WATER WORKS ASSOCIATION JOURNAL v. 87 (Sept. '95) p. 96-106.

Peer, George J.  et al.  "Spiking tests prove DE filtration works for high Giardia  concentrations."

-------
WATER/ENGINEERING & MANAGEMENT v. 140 (June '93) p. 18-19.

Randall, Nick. "A small town helps itself—to time-tested slow sand filter technology".  Public Works, v.
122 (Aug. '91) p. 104-6.

Rees, Robert H. et al. "Let diatomite enhance your filtration." CHEMICAL ENGINEERING v. 97 (Aug.
'90) p. 76-9.

Rees, Robert. "Diatomites cut filtration costs." POLLUTION ENGINEERING v. 22 (Apr. '90) p. 67-8+.

Riesenberg, F., Walters, B., Steele, A., and Ryder, R. Slow sand filters for a small water system.  American
Water Works Association Journal, v.  87 (Nov. '95) p.48-56.

Schuler, Peter F. et al. "Diatomaceous earth filtration of cysts and  particulates using chemical additives."
AMERICAN WATER WORKS ASSOCIATION JOURNAL v. 82 (Dec. '90) p. 67-75.

Schuler, Peter F. Slow sand and diatomaceous earth filtration of cysts and other parti culates. Water
Research, v. 25 (Aug. '91) p. 995-1005.

Spencer, Catherine  M. et  al.  "Improving precursor removal."   AMERICAN  WATER WORKS
ASSOCIATION JOURNAL v. 87 (Dec. '95) p.  71-82.

Tobiason, John E. et al.  "Pilot study of the effects of ozone and PEROXONE on in-line direct filtration."
AMERICAN WATER WORKS ASSOCIATION JOURNAL v. 84 (Dec. '92) p. 72-84.

VanArnam, David  G.  et al. "Diatomaceous-earth water filtration."  WATER/ENGINEERING &
MANAGEMENT v. 136 (Oct. '89) p. 35-6.

Visscher, Jan Teun.   Slow sand filtration:  design, operation, and maintenance. American Water Works
Association Journal, v.  82 (June '90) p. 67-71.

Walton, Harris G. "Diatomite filtration: why it removes Giardia from water." WATER/ ENGINEERING
& MANAGEMENT v.  136  (Oct. '89) p. 38.

Wiesner, Mark R. et al. "Cost estimates for membrane filtration and conventional treatment." AMERICAN
WATERWORKS ASSOCIATION JOURNAL v. 86 (Dec. '94) p. 33-41.

-------
               APPENDIX C




MEMORANDUM REGARDING TCR TECHNOLOGIES

-------
MEMORANDUM

SUBJECT:         Clarification of Issues Concerning the Revised Total Coliform Rule

FROM:            Michael B. Cook, Director
                   Office of Drinking Water (WH-550D)

TO:                Water Supply Branch Chiefs
                   Environmental Services Division Directors
                   Quality Assurance Officers
                   Regions-I-X

     Several Regions and States have requested clarification on parts of the revised total coliform
rule, promulgated June 19, 1989. These clarifications  appear below.

1.    ISSUE: Why is it the total coliform rule does not distinguish between transient non-community
water systems and non-transient non-community water systems like some rules regulating chemical
contaminants?

     Regulations on chemical contaminants generally  deal with chronic exposure, i.e., lifetime
exposure; this differs from microbiological regulations  where a single exposure may result in illness.
Moreover, the vast majority of non-community water systems will sample fewer than five times per
month, and thus be required to have a sanitary survey every 5 years (with some exceptions), the same
as like-sized community water systems.  For such systems, sanitary surveys are more important for
protecting public health than  monitoring. Thus, it is less important to differentiate between the two
types of non-community water systems.

2.    ISSUE: Is a cross-connection control program included as a best available means for achieving
compliance with the MCL?

     §141.63(d) identifies the best technology, treatment techniques,  or other means available for
achieving compliance with the MCL for total coliforms.  This list includes paragraph (3) in that
section, "Proper maintenance of the distribution system including appropriate pipe replacement and
repair procedures, main flushing programs, proper operation and maintenance of storage tanks and
reservoirs, and continual maintenance of positive water pressure in all parts of the distribution
system..."  EPA considers this statement as including a cross-connection control program.

3.    ISSUE: Where is a fourth repeat sample collected?

     §141.21(b)(2) states that a system which has a total coliform-positive sample must collect at
least one repeat sample from  the sampling tap where the  original total coliform-positive sample was
taken, and at least one repeat sample at a tap within five  service connections upstream and at least one
repeat sample at a tap within  five service connections downstream of the original sampling site. EPA

-------
did not specifically state that a system required to take a fourth repeat sample by §141.21(b)(l) was to
take it within five service connections of the original sample, but that was implied in the rule in
§141.21(b)(2), and was the Agency's intention (see definition of repeat sample in the preamble on 54
FR 27553, column 1, first paragraph).

4.    ISSUE: Where are additional sets of repeat samples collected?

     §141.21(b)(4) states that if one or more samples in a set of repeat samples 4-s total coliform-
positive, the system must collect an additional set of repeat samples.  The rule, however, is not clear
on where the additional set is to be collected, five adjacent service connections from the original total
coliformpositive tap or the repeat total coliform-positive tap (assuming only one repeat sample is total
coliform-positive). EPA believe's that this situation would generally occur only when the distribution
system is contaminated, and consequently will allow the system to decide on which of the two taps to
center the second set of repeat samples.

5.    ISSUE: If a system  has a fecal col'lform-positive sample and all repeat samples are total
coliform-negative, does that system have an acute violation of the MCL for total coliforms?

     §141.63(b) specifies the MCL for total coliforms, based upon the presence of fecal coliforms  or
E. coli. Based upon this paragraph, if a system has a total coliform-positive routine sample which is
also fecal coliform-positive (or E.  colipositive), and all repeat samples are total coliform-negative,
then the system has not violated the MCL in §141.63(b).

 6.   ISSUE: Invalidation of total coliform-positive samples.

     §141.21(c)(l) lists the conditions under which a  State may invalidate a total coliform-positive
sample. A State may invalidate such a sample only on a case-by-case basis for eadh instance; the
State may not invalidate total coliform-positive samples prospectively or genetically.

7.    ISSUE: MCL violations for persistent violators of monitoring or reporting requirements.

     No EPA rule, including the revised total coliform rule,  states that systems which repeatedly
violate specified monitoring or reporting requirements are, as a consequence, in violation of the MCL.
However, States should not be discouraged from choosing such an approach.

8.    ISSUE: Collection of a routine sample(s) the next month by a small system after the State
waives the requirement for five samples the next month after a total coliform-positive sample.

     §141.21(b)(5)(ii) states that when a State waives the requirement for a system which collects
fewer than five routine samples/month to collect at least five routine samples during the next month
after a total coliform-positive sample, the system must still take at least one routine sample before the
end of the next month, unless the State has determined that the system has corrected the
contamination problem before the system took the set of repeat samples. EPA did not intend to
suggest by this statement that  systems could ignore the routine monitoring frequency requirements
specified under §§141.21(a)(2)-(3). A system must still collect the number of routine samples
specified by §§141.21(a)  (2)-(3).

-------
9.    ISSUE: Mixed Medium ONPG-MUG (MMO-MUG) test

     To date, the only commercially available formulation of the approved MMO-MUG test of which
EPA is aware is the Autoanalysis Colilert Test.  Other methods which are identical in formulation and
procedure would also be acceptable. Variations in formulation or procedure of the MMO-MUG test
that was approved in the Federal Register (54 FR 27544; June 29, 1989) should be submitted to
EPA's Environmental Monitoring Systems Laboratory in Cincinnati for review.

-------