-------
TABLE 3-17. SUMMARY OF HYGROSCOPIC GROWTH FACTORS3
Dry Size (/xm)
0.05
0.2
0.4
0.5
i Dry Size (j«m)
0.05
0.10
0.20
0.30
0.40
1987 SCAQS, Claremont,
More Hygroscopic Peak
Dp(90 + 3% RH)
rDp(0%RH)
1.14 + 0.05
1.23 + 0.08
1.63 ± 0.11
1.59 ± 0.08
1990 NGS Visibility Study, Grand
More Hygroscopic Peak
D (89 + 4% RH)
rDp(0%RH)
1.36 ± 0.08
1.42 + 0.08
1.49 ± 0.11
1.51 ± 0.09
1.43 + 0.10
CA
Less Hygroscopic Peak
D (87 + 2% RH)
Dp(0% RH)
1.03 ± 0.03
1.02 ± 0.02
1.04 ± 0.05
1.07 ± 0.03
Canyon, AZ
Less Hygroscopic Peak
D (89 + 4% RH)
rDp(0%RH)
1.14 ± 0.10
1.17 ± 0.09
1.17 ± 0.10
1.14 + 0.10
1.07 ± 0.03
aValues are mean ± standard deviations.
-------
o>
Q
o
JO
O"
•o
• RH = 99% 8/12/90, 0200 hr
+ RH < 50%
?+
Sulfate Size Distributions + +
.•• • t
0.01
0.1 1
Diameter (urn)
Q
o>
o
RH = 95% 8/4/90, 0200 hr
RH < 50%
Sulfate Size Distributions + •+ *
+• ++.
i i i
0.01
Diameter
10
Figure 3-30. Example of growth in particle size due primarily to increases in relative
humidity from Uniontown, PA.
Source: Lowenthal et al. (1995).
3-176
-------
There are also studies of the behavior of ambient aerosols as the relative humidity is
reduced by heating the sampled air. Shaw and Rood (1990) report a study using a heated
integrating nephelometer in which crystallization RHs of 4 to 67% were observed. Similar
studies in Washington, D.C. by Fitzgerald et al. (1982) found no evidence of crystallization
or efflorescence when RH was reduced to 30% RH.
Further experimental evidence of the effect of decreasing relative humidity on aerosol
size distribution is provided by impactor data reported by Berner (1989) and is shown in
Figure 3-31. One impactor sampled aerosol in its humidified state directly from the
atmosphere. The inlet of a second impactor was warmed =7 °C above the ambient
temperature of «5 °C in order to evaporate most of the particle-bound water before
collecting the aerosol. The water and other volatile material in both the "wet" and the "dry"
samples would evaporate in the laboratory prior to weighing the impactor stages. As can be
seen, in the ambient air most of the non-volatile mass was above 1.0 pm with significant
amounts above 2.5 /xm. However, after heating the size of the aerosol was reduced so that
most of the non-volatile mass was below 1.0 /xm. Berner treated the distributions as
monomodal and derived growth factors of 4.9 for fog and 4.1 for haze. If the observations
are treated as multimodal, good bimodal, or as shown in Figure 3-31, trimodal fits are
obtained. This splitting into "more" and "less" hygroscopic modes at high relative humidity
has been observed by McMurry and co-workers (McMurry and Stolzenberg, 1989; Zhang et
al., 1993) (Figure 3-29) and Lowenthal et al. (1995) (Figure 3-30). In some cases, reported
by Pitchford and McMurry (1994), splitting into three modes of varying hygroscopicity was
observed. However, the separation into two "more" hygroscopic modes may represent, as
suggested by Berner, variations in relative humidity extremes during different parts of the
overnight sampling period.
In measuring light scattering with the integrating nephelometer, the aerosol community
has been very concerned about the difference in relative humidity and temperature in the
ambient air and in the volume of air in which particle scattering is actually measured (Covert
et al., 1972; Fitzgerald et al., 1982). Temperature differences between the measurement
volume and ambient air of 1 or 2 °C can change the relative humidity and change the
observed light scattering. Great efforts have been made to minimize this temperature
3-177
-------
80.0
Bologna Haze, Wet (Bemer, 1989)
s
i
o-
Mode MMAD aa %Mass
1 0.204 1.69 9.9
2 1.95 1.97 23.5
3 3.50 2.65 66.5
>
^
/
s~
*\
N
\
0.01
0.1 1.0 10.0
Aerodynamic Diameter, Dn (>tm)
100.0
100.0
8
0 50.0-
i
•a
Bologna Haze, Dry (Berner, 1989)
Mode MMAD a. %Mass
1 0.130 1.42 10.8
2 0.589 1.34 57.4
3 1.65 1.36 31.8
% Dry mass lost
upon healing
15.8%
0.01
0.1 1.0 lO'.O
Aerodynamic Diameter, DM (urn)
100.0
70.0
Bologna Fog, Wet (Bemer, 1989)
Mode MMAD ofl %Mass
1 0.310 2.09 30.8
2 1.34 1.93 36.4
3 5.31 1.91 32.8
0.01
0.1 1:0
Aerodynamic Diameter, DM
16.0
100.0
200.0
S
Q 100.0-
0.0
0.01
Bologna Fog, Dry (Berner, 1989)
Mode MMAD o. %Mass
1 0.145 1.39 17.8
2 0.524 1.36 65.4
3 1.56 1.32 13.9
% Dry mass lost
upon heating
0.1 i'o "16.0
Aerodynamic Diameter, DM(|im)
100.0
Figure 3-31. Mass size distribution of non-volatile aerosol material. The aerosol was
collected at ambient conditions, "wet", or after evaporation of water,
"dry".
Source: Berner (1989).
3-178
-------
difference. However, researchers have not been nearly as careful in considering temperature
and relative humidity effects when measuring size distribution, either with impactors or
particle counters, even though effects have been reported in the early literature (Wagman
et al., 1967; Sverdrup and Whitby, 1980).
A recent paper by Cass and coworkers (Eldering et al., 1994) provides some insight
into how differences in RH resulting from heating can cause differences between
particle-counting distributions and impactor distributions. Particle size distributions were
obtained by counting particles by mobility (electrical aerosol analyzer) and light scattering
(optical particle counter). An example is shown in Figure 3-32. Almost no particles were
found between 1.0 and 2.5 /im diameter. When these particle number data were converted
to total expected light scattering, they agreed with measurements made by a heated, but not
an unheated, integrating nephelometer; and when converted to expected mass, agreed with
filter measurements of dry mass. Eldering et al. (1994) conclude that even the moderate
heating occurring in mobility and optical counters was enough to change the size of the
particles, especially when the ambient air was close to 100% RH. It seems likely that most
particle counting systems produce some heating of the aerosol, and thus some reduction of
the measured particle size from that existing in the ambient air. On the other hand, if
particle-size measuring devices were located in air conditioned or heated trailers or
laboratories, the temperature of the sampled air would be changed and the measured particle
size distribution would be different from that existing in the ambient air (Sverdrup and
Whitby, 1980).
During the high relative humidities that occur at nighttime, growth of hygroscopic
components can result in the growth of some fine mode aerosol to diameters greater than
1.0 ^m and perhaps even above 2.5 /xm. As can be seen in Figure 3-28, dry ammonium
sulfate particles having a dry diameter of 0.5 ^m will grow to =2.5 /xm at a relative
humidity between 99 and 100%. When the relative humidity actually reaches 100%, the
particles will continue to grow to maintain the relative humidity at 100%, and eventually
become fog droplets that are large enough to be collected in the fraction larger than 2.5
Ammonium sulfate particles with dry sizes greater than 0.5 /xm would also grow into the
larger than 2.5 urn size range.
3-179
-------
CO
3.
Q.
Q
O)
_g
;o
•a
100.00
80.00"
60.00--
40.00--
20.00--
0.(
August 27, 1987
Claremont Case B
)-0900
0900-1300 PST
1300-1700 PST
1700-2400 PST
0.01
0.1
Geometric Diameter, Dp,
1.0
10
Figure 3-32. Example of particle-counting volume distribution obtained in Claremont,
CA. Compare to Figures 3-14 and 3-31. Heating of the sampled air by
the mobility and optical counters are believed to have resulted in a
distribution representative of a lower than ambient relative humidity.
Source: Eldering et al. (1994).
The addition of water to hygroscopic particles, discussed in the previous section, is a
reversible process. Particles absorb water and grow as RH increases; as RH decreases some
of the particle-bound water evaporates and the particles shrink. However, the large amount
of liquid water associated with hygroscopic particles at high relative humidity provides a
medium for liquid phase transformation process. A number of atmospheric process, which
convert SO2 to sulfate or NOX to nitrate, can take place in water solutions but not in the gas
phase. These processes are not reversible but lead to an accumulation of sulfate or nitrate
and lead to an increase in the dry size of the particle. Of course as more sulfate or nitrate is
added to the particle it will absorb more water so that the wet size will also increase.
The first observation and clear discussion of these combined effects of relative humidity
on growth and SO2 conversion to sulfate are given by Hering and Friedlander (1982) as
3-180
-------
shown in Table 3-18. Using a low pressure impactor, they observed that days with higher
relative humidity had higher sulfate concentration and higher MMAD's compared to days
with lower relative humidity. Hering and Friedlander (1982) named the small mode the
condensation mode and suggested that it was formed by the gas phase conversion of SOj to
sulfate and subsequent nucleation, coagulation, and growth by condensation. They named
the larger mode the droplet mode and discussed possible formation mechanisms. This mode
is now believed to result from the reaction of SO2 in fog or cloud droplets (Meng and
Seinfeld, 1994).
TABLE 3-18. COMPARISON OF SULFATE CONCENTRATION
AND MASS MEAN DIAMETERS OF AEROSOLS FOR DAYS
WITH HIGHER AND LOWER RELATIVE HUMIDITY
Minimum RH, %
Maximum RH, %
Sulfate concentration, /ig/m3
Mass median aerodynamic diameter, /xm
Low RH Days
17-35
45-68
3-9
0.20 ± 0.02
High RH Days
26-66
69- 100
3 -52
0.54 ± 0.07
Source: Hering and Friedlander (1982).
In a series of papers McMurry and co-workers make use of the aerosol growth law,
originally developed by Heisler and Friedlander (1977), to study the mechanism and rates of
sulfate formation in ambient air (McMurry et al., 1981; McMurry and Wilson, 1982, 1983).
They were able to apportion growth to condensation and droplet mechanisms and observed
droplet growth in particles up to 3 /im in diameter.
A process of aerosol growth due to increasing relative humidity (Figure 3-33) has also
been utilized by Cahill et al. (1990) to explain observations of sulfate size changes during the
1986 Carbonaceous Species Methods Comparison Study in Glendora, CA. Cahill used a
DRUM sampler to measure sulfate in nine size ranges. By tracking the mass of sulfate in the
0.56 to 1.15 fj,m size range Cahill et al. could follow the expansion and contraction of
aerosol particles containing sulfate. Because of the relative high time resolution of the
DRUM sampler (4 h except for an 8-h increment each night from midnight to 8 a.m.),
3-181
-------
50
40
E
i
$
o 30
20
10
0
Poor Period, 8/12-8/16
0000-0800
on
a
o
o
o Fair Period, 8/17-8/20
•0000-0800
20
40
60
80
100
Relative Humidity (%)
Figure 3-33. Relative humidity versus sulfur, during the 1986 Carbonaceous Species
Methods Comparison Study, for particles with Dae > 0.56 /on. The
approximate trajectories followed during each day by the Dae > 0.56 urn
sulfur size fraction are shown for period P and period F. Note that even
when the humidities are low, 30 to 50 %, the period P aerosols remain
coarser by a factor of three than those of period F. The water content
incorporated in the aerosols during the 0000- to 0800-h time periods is lost
only slowly, giving a strong hysteresis effect in sulfur size.
Source: Cahill et al. (1990).
Cahill et al. (1990) could follow this process as the relative humidity increased during the
night and decreased during the day. These data indicate that during the "Poor Period" (low
visibility) particles grow as relative humidity increases. However, they did not return to the
smaller size observed during the "Fair Period" (good visibility). This could be due to a
combination of growth due to reaction of SO2 to sulfate within the particles or failure of the
droplet to crystallize thus maintaining particle-bound water in a supersaturated state.
3-182
-------
John et al. (1990), in studies in the Los Angeles area, observed a number of sulfate size
distributions with MMAD near 1.0 /xm. A histogram of the sulfate MMADs from his study
is shown in Figure 3-34. John et al. (1990) have provided a qualitative explanation to
account for these large MMADs for fine mode aerosol. In analyzing their data John et al.
plotted sulfate mass as a function of sulfate MMAD and found two distinct regions, as shown
in Figure 3-35. Distributions with particles near 0.2 /mi diameter are probably still dry; the
particles have not reached their deliquescent point. As the relative humidity increases they
reach their deliquescent point and grow rapidly into the 0.5 to 0.7 /mi size range. During
the formation of fog, the hygroscopic particles act as fog condensation nuclei, and with
relative humidity at 100%, grow into 1 to 10 /mi fog droplets. Sulfur dioxide dissolves in
the fog droplets and is rapidly oxidized to sulfate by atmospheric oxidants such as H2O2 or
O3, or by catalysis by Fe or Mn. These particles lose some of their water as the relative
humidity decreases below 100% RH, but will have substantially more sulfate than prior to
activation. Similar processes occur in clouds (Schwartz, 1984a, 1986a).
This type of process probably accounts for the large size of the fine mode observed in
Vienna (Berner et al., 1979; Berner and Lurzer, 1980). Winter and summer size
distributions are shown in Figure 3-36. Berner et al. reported that fog occurred during the
night time during the winter study. In this European study, as in American studies, instances
of fine mode size distributions with MMADs near or above 1 /mi seem to occur only when
fog or very high relative humidity conditions have been present. Two log-normal
distributions are fit to the accumulation mode to suggest the separation, at high relative
humidity, into hygroscopic and hydrophobic components. No distribution was fit to the
coarse mode because only a fraction of the coarse size range was measured.
Similar results have been observed in sampling with dichotomous samplers. A large
humidity driven shift of normally fine mode material into the coarse mode was observed by
Keeler et al. (1988). In the extreme case, 60% of the SO4= and 50% of the PM2 5 mass was
shifted to the coarse fraction. Such occurrences were not rare, occurring in 12 out of
83 several-hour sampling periods.
In an analysis of data from the IMPROVE network Cahill and co-workers (Eldred
et al., 1994) report that 20% of the total sulfate is found in the coarse fraction of PM10.
Studies in Philadelphia using dichotomous samplers have also reported that 20% of the total
3-183
-------
I*
Q>
CT
s.
35
30
25
20
15
10
5
0
Summer All Sites SOt <
(a)
0.1 1
Aerodynamic Mode Diameter (urn)
10
400 -
Summer All Sites SOt -
(b)
1
Aerodynamic Mode Diameter (|im)
10
Figure 3-34. Data from the South Coast Air Quality Study (John et al., 1990). Plots
show (a) frequency of sulfate modes of various sizes as a function of mode
diameter and (b) average sulfate mode concentration as a function of mode
diameter. Note that although there are only a few instances when the
mode diameter is near 1.0 /an, it is these situations that give rise to the
highest sulfate concentrations. Modes with diameters above 2.5 /tm may
be due to collection of fog droplets containing sulfate or reaction of SO2 in
liquid droplets of NaCl due to NaCl sea spray droplets in which SO2 has
dissolved and reacted to form sulfate and release HC1 gas.
3-184
-------
1,000^
0.1 1
Aerodynamic Mode Diameter (urn)
Figure 3-35. Log-log plot of sulfate mode concentration versus aerodynamic mode
diameter from Claremont, CA, during the summer SCAQS (John et al.,
1990). The solid lines have slopes corresponding to mode concentration
increasing with the cube of the mode diameter. A transition between the
two modes is believed to occur at approximately the sulfate mode
concentration indicated by the horizontal dashed line.
sulfate is found in the coarse fraction (Dzubay et al., 1988). Cahill and coworkers suggest
that sulfate particles may grow larger than 2.5 jum in diameter and thus be sampled in the
PM10 fraction but not the PM2 5 fraction. It is possible for SO2 to react with basic carbonate
coarse particles to form a sulfate coating or to dissolve in wet NaCl particles, from oceans,
lakes, or salt placed on streets to dissolve ice, and be converted to sulfate with the release of
HC1. However, there also is substantial evidence that some fine sulfate, and therefore
possibly other fine mode material, may be found in the size range above 1.0 /*m and even
3-185
-------
Vienna, Summer
10
Aerodynamic Diameter, Dae,
Vienna. Winter
0.1 1.0
Aerodynamic Diameter, Dae,
Figure 3-36. Typical results of size-distribution measurements taken with a Berner
impactor in a Vienna street with heavy automotive traffic:
(a) measurements taken during summer at three different elevations, (b)
measurements taken during winter at three different elevations, fog was
frequently present during the winter sampling period.
Source: Berner and Liirzer (1980).
above 2.5 /xm diameter, due to the growth of hygroscopic particles at very high relative
humidity.
These observations, indicating that, during near 100% relative humidity conditions,
significant amounts of normally fine mode material will be found in the coarse fractions
(>2.5 um diameter), have broader implications than selection of a cut point to separate fine
3-186
-------
and coarse particles. Such shifts could cause problems for receptor modeling using chemical
mass balance or factor analysis, for interpretation of exposure data in epidemiological
studies, and in estimated removal of paniculate matter by deposition.
3.7.7 Conclusions
This review of atmospheric particle-size-distributions was undertaken to provide
information which could be used to determine what cut-point; 1.0 j«m, 2.5 /mi, or something
in between; would give the best separation between the fine and coarse particle modes. The
data do not provide a clear or obvious answer. Depending on conditions, a significant
amount of either fine or coarse mode material may be found in the intermodal region
between 1.0 and 3 /im. However, the analysis does demonstrate the important role of
relative humidity in influencing the size of the fine particle mode and indicates that
significant fine mode material is found above 1.0 /im only during periods of very high
relative humidity.
Thus, a PM2 5 sample will contain most of the fine mode material, except during
periods of RH near 100 %. However, especially in conditions of low RH, it may contain
5 to 20 % of the coarse mode material below 10 /mi in diameter. A PMt 0 sample will
prevent misclassification of coarse mode material as fine but under high RH conditions will
result in some of the fine mode material being misclassified as coarse.
A reduction in RH, either intentionally or inadvertently, will reduce the size of the fine
mode. A sufficient reduction in RH will yield a dry fine particle mode with very little
material above 1.0 /mi. However, reducing the RH by heating will result in loss of
semi volatile components such as ammonium nitrate and semi volatile organic compounds.
No information was found on techniques designed to remove particle-bound water without
loss of other semivolatile components.
3.8 SUMMARY
Atmospheric paniculate matter (PM) refers to solid or liquid particles suspended in air.
The term atmospheric aerosol refers to both the suspended particles and the air (including
gaseous pollutants) in which the particles are suspended. However, the term aerosol is
3-187
-------
frequently used to refer only to the suspended particles. The terms paniculate matter and
particles will be used most frequently in this document.
Paniculate matter is not a single pollutant but rather a mixture of many classes of
pollutants. The components of PM differ in sources; formation mechanisms; composition;
size; and chemical, physical, and biological properties. Particle diameters span more than
four orders of magnitude, ranging from a few nanometers (nm) to one hundred micrometers
0*m). Because of this wide size range, plots of particle-size distribution are almost always
plotted versus the logarithm of the particle diameter. Diameter usually refers to the
aerodynamic diameter, defined as the diameter of a spherical particle with an equal settling
velocity but a density of 1 g/cm3. This normalizes particles of different shapes and densities.
One of the most fundamental divisions of atmospheric particles is the naturally
occurring separation into a fine particle mode and a coarse particle mode as shown in Figure
3-3. The terms fine mode particles and coarse mode particles are used to refer to particles in
the fine or coarse particle distributions. The two distributions overlap between 1 and 3 /im
aerodynamic diameter.
Particles may also be defined by the size cut of the collection or measuring device. A
frequently used descriptor is the 50% cut point. This is the aerodynamic diameter at which
the efficiency of the device for particle collection is 50%. As particles increase in size above
the 50% cut point, they are collected with decreasing efficiency, eventually reaching 0%; as
particles decrease in size below the 50% cut point, they are collected with increasing
efficiency, eventually reaching 100%. The indicator for the current particle standard is PM10
(i.e. particles with a 50% cut point of 10 /urn aerodynamic diameter). However, PM10
contains some particles larger than 10 fj,m and does not contain all particles below 10 ^m.
Fine is also used to refer to particles with an upper cut point of 3.5, 2.5 (PM2 5), 2.1, or
1.0 nm. Coarse is also used to refer to particles between 2.5 and 10 /zm (PM(10.2 5)) or
particles collected by the high volume sampler as well as the entire coarse mode.
Size fractions may also be characterized in terms of their entrance into various
compartments of the body. Thus, inhalable particles enter the respiratory tract, including the
head airways. Thoracic particles travel past the larynx and reach the lung airways and the
gas-exchange regions of the lung. Respirable particles reach the gas-exchange region of the
3-188
-------
lung. PMjQ is an indicator of thoracic particles; PM2 5 is an indicator of fine mode particles;
and PM(10_2 5) is an indicator of the thoracic component of coarse mode particles.
The fine and coarse particle distributions are frequently approximated by log-normal
distributions. However, finer distinctions can be made. The fine particles consist of a nuclei
mode, composed of particles recently formed from gases, and an accumulation mode, into
which the nuclei grow and accumulate (Figure 3-6). Ultrafine particles, defined in this
document as distributions with mass median diameters below 0.1 jum, are associated with the
nuclei mode (Figures 3-1, 3-2, and 3-13). In the presence of fogs or clouds, the
accumulation mode may split into a smaller, less hygroscopic mode and a larger droplet
mode. The latter is formed by gases dissolving in the fog or cloud droplets, reacting, and
forming particles when the water of the droplets evaporates (Figure 3-14). There may also
be several modes within the coarse particle distribution or mode but these are usually less
distinct.
The terms primary and secondary, anthropogenic and biogenic, outdoor and indoor
microenvironment have significant applications to particulate matter. Primary fine particles
are emitted from sources, either directly as particles or as vapors which rapidly condense to
form particles. Primary coarse particles are usually formed by mechanical processes.
Secondary fine particles are formed within the atmosphere as the result of gas-phase or
aqueous-phase chemical reactions. Anthropogenic particles may be formed by primary or
secondary processes. Similarly, biogenic particles include primary particles of biological
origin, including bioallergens, as well as secondary particles formed from biogenic
precursors such as terpenes emitted into the atmosphere. The term outdoor refers to
community atmospheres. These are the atmospheres which are usually monitored for
particulate matter. Indoor microenviroments include homes, apartments, schools, office
buildings and other indoor work places, large enclosed areas such as malls, vehicles used for
commuting, etc.
Some general classes of particles, such as organic particles, can occur not only as fine
or coarse particles, but can be of either anthropogenic and biogenic origin, and can be
produced both in outdoor and indoor microenvironments. Organic particles also can be
present in air as primary fine particles from combustion processes or as secondary fine
particles formed as a result of atmospheric reactions involving higher molecular weight
3-189
-------
volatile anthropogenic alkenes and aromatics or from the atmospheric reactions of volatile
biogenic compounds such as terpenes. Therefore, there is considerable overlap for chemical
species among the categories listed above.
A substantial fraction of the fine particle mass, especially during the warmer months of
the year, is secondary PM, formed as a result of atmospheric reactions. Such reactions
involve the gas phase conversion of SO2 to H2SO4 by OH radicals and aqueous-phase
reactions of SO2 with H2O2, O3, or O2 (catalyzed by Fe and Mn). The NO2 portion of NOX
can be converted to HNO3 by reaction with OH radicals during the day. During nighttime
NO2 is converted into HNO3 by a series of reactions involving 03 and the nitrate radical
(NO3). Both H2SO4 and HNO3 react with atmospheric ammonia (NH3). Gaseous NH3
reacts with gaseous HNO3 to form paniculate NH4NO3. Gaseous NH3 reacts with H2SO4 to
form acidic HSO4 and neutral (NH4)2SO4. A number of volatile organic compounds can
react with O3 and/or OH radical to form fine organic particles. In addition, acid gases such
as SO2 and HNO3 may react with coarse particles such as CaCO3 and NaCl to form coarse
particles of different chemical composition.
The concentrations of OH radicals, O3, and H2O2, formed by gas phase reactions
involving volatile organic compounds and NOX, depend on the concentrations of the
reactants, and on meteorological conditions including temperature, solar radiation, wind
speed, mixing volume and passage of high pressure systems. Therefore, formation of a
substantial fraction of fine particles can depend on the gas phase reactions which also
produce O3 and a variety of other volatile products.
The fine particle fraction, in addition to SO4= and NO§ , contains elemental carbon
(EC), organic carbon (OC), H+ (hydrogen ions or acidity) and a number of metal
compounds at lower concentrations. Species such as SO4= , NO3 and some organic species
are associated with substantial amounts of particle-bound water. NH4N03 is in equilibrium
with HNO3 and NH3 so it can vaporize from particles. Organic particles can also be in
equilibrium with their vapor. Such species are called semi-volatile. A number of trace
elements including, but not necessarily limited to, Pb, Zn, Ni, Cd, Na, Cl, Br, Se and As
have been measured in the PM2 5 fraction of fine particles. The coarse particles are largely
composed of the crustal elements Si, Ca, Al, and Fe. However, a considerable number of
elements are found in both the fine and coarse fractions.
3-190
-------
Chemical reactions of SO2 and NOX within plumes are an important source of H+,
and NO§. These conversions can occur by gas-phase and aqueous-phase mechanisms.
In point-source plumes emitting SO2 and NOX, the gas-phase chemistry depends on
plume dilution, sunlight and background volatile organic compounds mixed into the diluting
plume. For the conversion of SO2 to H2SO4, the gas-phase rate in such plumes during
summer midday conditions in the eastern United States typically varies between 1 and 3 % h"1
but in the cleaner western United States rarely exceeds 1 % h"1. For the conversion of NOX
to HNO3, the gas-phase rates appear to be approximately three times faster than the SC^
conversion rates. Winter rates for SO2 conversion were approximately an order of
magnitude lower than the summer rates.
The contribution of aqueous-phase chemistry to particle formation in point-source
plumes is highly variable, depending on the availability of the aqueous phase (wetted
aerosols, clouds, fog, and light rain) and the photochemically generated gas-phase oxidizing
agents, especially H2O2 for SO2 chemistry. The in-cloud conversion rates of SO2 to SO4=
can be several times larger than the gas-phase rates given above. Overall, it appears that
SO2 oxidation rates to SO4= by gas-phase and aqueous-phase mechanisms may be
comparable in summer, but aqueous phase chemistry may dominate in winter.
In the western United States, markedly higher SO2 conversion rates have been reported
in smelter plumes than in power plant plumes. The conversion is predominantly by a gas-
phase mechanism. This result is attributed to the lack of NOX in smelter plumes. In power
plant plumes NO2 depletes OH and competes with SO2 for OH.
In urban plumes, the upper limit for the gas-phase SO2 conversion rate appears to be
about 5% h"1 under the more polluted conditions. For NO2, the rates appear to be
approximately three times faster than the SO2 conversion rates. Conversion rates of SO2 and
NOX in background air are comparable to the peak rates in diluted plumes. Neutralization of
H2SO4 formed by SO2 conversion increases with plume age and background NH3
concentration. If the NH3 concentrations are more than sufficient to neutralize H2SO4 to
(NH4)2SO4, the HNO3 formed from NOX conversions may be converted to NH4NO3.
The lifetimes of particles vary with size. Coarse particles can settle rapidly from the
atmosphere within hours, and normally travel only short distances. However, when mixed
high into the atmosphere as in dust storms the smaller sized coarse mode particles may have
3-191
-------
longer lives and travel distances. Nuclei mode particles rapidly grow into the accumulation
mode. However, the accumulation mode does not grow into the coarse mode.
Accumulation-mode fine particles are kept suspended by normal air motions and have very
low deposition rates to surfaces. They can be transported thousands of km and remain in the
atmosphere for a number of days. Both accumulation-mode and nuclei-mode (or ultrafine)
particles have the ability to penetrate deep into the lungs. Dry deposition rates are expressed
in terms of a deposition velocity which varies as the particle size, reaching a minimum
between 0.1 and 1.0 /*m aerodynamic diameter. Accumulation-mode particles are removed
from the atmosphere primarily by cloud processes. Fine particles, especially particles with a
hygroscopic component, grow as the relative humidity increases, serve as cloud condensation
nuclei, and grow into cloud droplets. If the cloud droplets grow large enough to form rain,
the particles are removed in the rain. Falling rain drops impact coarse particles and remove
them. Ultrafine or nuclei mode particles are small enough to diffuse to the falling drop and
be removed. Falling rain drops, however, are not effective in removing accumulation-mode
particles.
There are many reasons for wanting to collect fine and coarse particles separately.
However, because fine-mode particles and coarse-mode particles overlap in the size range
between 1.0 and 3 //m diameter, it is not clear what 50% cut point will give the best
separation.
A review of atmospheric particle-size-distribution data did not provide a clear or
obvious answer. Depending on conditions, a significant amount of either fine or coarse
mode material may be found in the intermodal region between 1.0 and 3 /mi. However, the
analysis of the existing data did demonstrate the important role of relative humidity in
influencing the size of the fine particle mode and indicated that significant fine mode material
is found above 1.0 /xm only during periods of very high relative humidity.
Thus, a PM2 5 sample will contain most of the fine mode material, except during
periods of RH near 100 %. However, especially in conditions of low RH, it may contain
5 to 20 % of the coarse mode material below 10 /xm in diameter. A PMj 0 sample will
prevent misclassification of coarse mode material as fine but under high RH conditions will
result in some of the fine mode material being misclassified as coarse.
3-192
-------
A reduction in RH, either intentionally or inadvertently, will reduce the size of the fine
mode. A sufficient reduction in RH will yield a dry fine particle mode with very little
material above 1.0 /mi. However, techniques to reduce the RH without loss of semivolatile
components such as ammonium nitrate and semivolatile organic compounds have not yet been
developed.
3-193
-------
REFERENCES
Adamson, A. W. (1976) Physical chemistry of surfaces New York, NY: John Wiley & Sons, Inc.
Akhter, M. S.; Chughtai, A. R.; Smith, D. M. (1984) Reaction of hexane soot with NO2/N2O4. J. Phys. Chem.
88: 5334-5342.
Akhter, M. S.; Chughtai, A. R.; Smith, D. M. (1985) The structure of hexane soot I: spectroscopic studies.
Appl. Spectrosc. 39: 143-153.
Aleic-Juretic, A.; Cvitas, T.; Klasinc, L. (1990) Heterogeneous polycyclic aromatic hydrocarbon degradation
with ozone on silica gel carrier. Environ. Sci. Technol 24: 62-66.
Alkezweeny, A.; Powell, D. (1977) Estimation of transformation rate of SO2 to SO4 from atmospheric
concentration data. Atmos. Environ. 11: 179-182.
Allen, D. T.; Palen, E. J.; Haimov, M. I.; Hering, S. V.; Young, J. R. (1994) Fourier transform infrared
spectroscopy of aerosol collected in a low pressure impactor (LPI / FTIR): method development and field
calibration. Aerosol Sci. Technol. 21: 325-342.
All wine, K. J. (1993) Atmospheric dispersion and tracer ventilation in a deep mountain valley. J. Appl.
Meteorol. 32: 1017-1037.
Alofs, D. J.; Hagen, D. E.; Trueblood, M. B. (1989) Measured spectra of the hygroscopic fraction of
atmospheric aerosol particles. J. Appl. Meteorol. 28: 126-136.
Altshuller, A. P. (1983) Review: natural volatile organic substances and their effect on air quality in the United
States. Atmos. Environ. 17: 2131-2165.
Altshuller, A. P. (1987) Potential contribution of sulfate production in cumulus cloud droplets to ground level
particle sulfur concentrations. Atmos. Environ. 21: 1097-1105.
American Conference of Governmental Industrial Hygienists (ACGIH). (1994) Appendix D: particle size-selective
sampling criteria for airborne paniculate matter. In: 1994-1995 threshold limit values for chemical
substances and physical agents and biological exposure indices. Cincinnati, OH: American Conference of
Governmental Industrial Hygienists; pp. 43-46.
Anderson, J. R.; Aggett, F. J.; Buseck, P. R.; Germani, M. S.; Shattuck, T. W. (1988) Chemistry of individual
aerosol particles from Chandler, Arizona, an arid urban environment. Environ. Sci. Technol.
22: 811-818.
Andreae, M. O.; Charlson, R. J.; Bruynseels, F.; Storms, H.; Van Grieken, R.; Maenhaut, W. (1986) Internal
mixture of sea salt, silicates, and excess sulfate in marine aerosols. Science (Washington, DC)
232: 1620-1623.
Andrews, E.; Larson, S. M. (1993) Effect of surfactant layers on the size changes of aerosol particles as a
function of relative humidity. Environ. Sci. Technol. 27: 857-865.
Appel, B. R.; Tokiwa, Y.; Hsu, J.; Kothny, E. L.; Halm, E. (1985) Visibility as related to atmospheric aerosol
constituents. Atmos. Environ. 19: 1525-1534.
Appel, B. R.; Cheng, W.; Salaymeh, F. (1989) Sampling of carbonaceous particles in the atmosphere—II.
Atmos. Environ. 23: 2167-2175.
3-194
-------
Arimoto, R.; Duce, R. A.; Ray, B. J.; Unni, C. K. (1985) Atmospheric trace elements at Enewetak Atoll:
2. transport to the ocean by wet and dry deposition. J. Geophys. Res. [Atmos.] 90: 2391-2408.
Arnts, R. R.; Gay, B. W., Jr. (1979) Photochemistry of some naturally emitted hydrocarbons. Research Triangle
Park, NC: U.S. Environmental Protection Agency, Environmental Sciences Research Laboratory; EPA
report no. EPA-600/3-79-081. Available from: NTIS, Springfield, VA; PB80-131980.
Atkinson, R.; Aschmann, S. M. (1987) Kinetics of the gas-phase reactions of alkylnaphthalenes with O3, N2O5
and OH radicals at 298+2 K. Atmos. Environ. 21: 2323-2326.
Avissar, R.; Pielke, R. A. (1989) A parameterization of heterogeneous land surfaces for atmospheric numerical
models and its impact on regional meteorology. Mon. Weather Rev. 117: 2113-2136.
Ayers, G. P.; Larson, T. V. (1990) Numerical study of droplet size dependent chemistry in oceanic, wintertime
stratus clouds at southern mid-latitudes. J, Atmos. Chem. 11: 143-167.
Back, S. O.; Field, R. A.; Goldstone, M. E.; Kirk, P. W.; Lester, J. N.; Perry, R. (1991) A review of
atmospheric polycyclic aromatic hydrocarbons: sources, fate and behavior. Water Air Soil Pollut.
60: 279-300.
Bagnold, R. A. (1941) The physics of blown sand and desert dunes. London, United Kingdom: Methuen & Co.
Baker, M. B.; Latham, J. (1979) The evolution of droplet spectra and the rate of production of embryonic
raindrops in small cumulus clouds. J. Atmos. Sci. 36: 1612-1615.
Baldwin, A. C. (1982) Heterogeneous reactions of sulfur dioxide with carbonaceous particles. Int. J. Chem.
Kinet. 14: 269-277.
Barnard, W. R.; Gatz, D. F.; Stensland, G. J. (1987) Chemical characterization of aerosols emitted from vehicle
traffic on unpaved roads. Presented at: 80th annual meeting of the Air Pollution Control Association;
June; New York, NY. Pittsburgh, PA: Air Pollution Control Association; paper no. 87-14.3.
Barnard, W. R.; Stansland, G. J.; Gatz, D. F. (1988) Flux of alkaline materials from unpaved roads in the
southwestern United States. In: Paniculate matter/fugitive dusts: measurement and control in western arid
regions. Proceedings of an Air Pollution Control Association meeting. Pittsburgh, PA: Air Pollution
Control Association; pp. 27-39.
Barrie, L. A. (1985) Scavenging ratios, wet deposition, and in-cloud oxidation: an application to the oxides of
sulphur and nitrogen. J. Geophys. Res. [Atmos.] 90: 5789-5799.
Barrie, L. A.; Georgii, H. W. (1976) An experimental investigation of the absorption of sulphur dioxide by
water drops containing heavy metal ions. Atmos. Environ. 10: 743-749.
Barth, M. C. (1994) Numerical modeling of sulfur and nitrogen chemistry in a narrow cold-frontal rainband: the
impact of meteorological and chemical parameters. J. Appl. Meteorol. 33: 855-868.
Barth, M. C.; Hegg, D. A.; Hobbs, P. V. (1992) Numerical modeling of cloud and precipitation chemistry
associated with two rainbands and some comparisons with observations. J. Geophys. Res. [Atmos.]
97: 5825-5845.
Bassett, M.; Seinfeld, J. H. (1983) Atmospheric equilibrium model of sulfate and nitrate aerosols. Atmos.
Environ. 17: 2237-2252.
3-195
-------
Bassett, M. E.; Seinfeld, J. H. (1984) Atmospheric equilibrium model of sulfate and nitrate aerosols - II. particle
size analysis. Atmos. Environ. 18: 1163-1170.
Behymer, T. D.; Hites, R. A. (1988) Photolysis of polycyclic aromatic hydrocarbons adsorbed on fly ash.
Environ. Sci. Technol. 22: 1311-1319.
Benkovitz, C. M.; Berkowitz, C. M.; Easter, R. C.; Nemesure, S.; Wagener, R.; Schwartz, S. E. (1994)
Sulfate over the North Atlantic and adjacent continental regions: evaluation for October and November
1986 using a three-dimensional model driven by observation-derived meteorology. J. Geophys. Res.
[Atmos.] 99: 20,725-20,756.
Benner, C. L.; Eatough, D. J.; Eatough, N. L.; Bhardwaja, P. (1991) Comparison of annular denuder and filter
pack collection of HNO3 (g), HNO2 (g), SO2 (g), and particulate-phase nitrate, nitrite and sulfate in the
south-west desert. Atmos. Environ. Part A 25: 1537-1545.
Bergstrom, R. W.; Seigneur, C.; Babson, B. L.; Holman, H.-Y.; Wojcik, M. A. (1981) Comparison of the
observed and predicted visual effects caused by power plant plumes. Atmos. Environ. 15: 2135-2150.
Beraer, A. (1989) Haze and its relation to atmospheric accumulation aerosol. Sci. Total Environ. 86: 251-263.
Berner, A.; Liirzer, C. (1980) Mass size distributions of traffic aerosols at Vienna. J. Phys. Chem.
84: 2079-2083.
Berner, A.; Liirzer, Ch.; Pohl, F.; Preining, O.; Wagner, P. (1979) The size distribution of the urban aerosol in
Vienna. Sci. Total Environ. 13: 245-261.
Bernstein, D. M.; Rahn, K. A. (1979) New York Summer Aerosol Study: trace element concentrations as a
function of particle size. In: Kneip, T. J.; Lippmann, M., eds. The New York Summer Aerosol Study,
1976. Ann. N. Y. Acad. Sci. 322: 87-97.
Bidleman, T. F. (1988) Atmospheric processes. Environ. Sci. Technol. 22: 361-367.
Biggins, P. D. E.; Harrison, R. M. (1980) Chemical speciation of lead compounds in street dusts. Environ. Sci.
Technol. 14: 336-339.
Bjarseth, A.; Olufsen, B. S. (1983) Long-range transport of polycyclic aromatic hydrocarbons. In: Bjerseth, A.,
ed. Handbook of polycyclic aromatic hydrocarbons. New York, NY: Marcel Dekker, Inc.; pp. 507-524.
Bj0rseth, A.; Lunde, G.; Lindskog, A. (1979) Long-range transport of polycyclic aromatic hydrocarbons. Atmos.
Environ. 13: 45-53.
Bott, A. (1991) On the influence of the physico-chemical properties of aerosols on the life cycle of radiation fogs.
Boundary Layer Meteorol. 56: 1-31.
Bott, A.; Carmichael, G. R. (1993) Multiphase chemistry in a microphysical radiation fog model—a numerical
study. Atmos. Environ. Part A 27: 503-522.
Bower, K. N.; Choularton, T. W. (1993) Cloud processing of the cloud condensation nucleus spectrum and its
climatological consequences. Q. J. R. Meteorol. Soc. 119: 655-679.
Bower, K. N.; Hill, T. A.; Coe, H.; Choularton, T. W. (1991) SO2 oxidation in an entraining cloud model with
explicit microphysics. Atmos. Environ. Part A 25: 2401-2418.
3-196
-------
Boyce, S. D.; Hoffmann, M. R. (1984) Kinetics and mechanism of the formation of hydroxymethanesulfonic acid
at low pH. J. Phys. Chem. 88: 4740-4746.
Braaten, D. A.; Paw U, K. T. (1992) A stochastic particle resuspension and deposition model. In: Schwartz,
S. E.; Slinn, W. G. N., eds. Precipitation scavenging and atmosphere-surface exchange: proceedings of
the fifth international conference, v. 2: the Semonin volume: atmosphere-surface exchange processes;
July 1991; Richland, WA. Washington, DC: Hemisphere Publishing Corporation; pp. 1143-1152.
Braaten, D. A.; Paw U, K. T.; Shaw, R. H. (1989) Particles resuspension in a turbulent boundary
layer—observed and modeled. J. Aerosol Sci. 21: 613-628.
Brauer, M.; Koutrakis, P.; Keeler, G. J.; Spengler, J. D. (1991) Indoor and outdoor concentrations of inorganic
acidic aerosols and gases. J. Air Waste Manage. Assoc. 41: 171-181.
Briggs, G. A.; Binkowski, F. S. (1985) Research on diffusion in atmospheric boundary layers: a position paper
on status and needs. Research Triangle Park, NC: U.S. Environmental Protection Agency, Atmospheric
Sciences Research Laboratory; EPA report no. EPA/600/3-85/072. Available from: NTIS, Springfield,
VA; PB86-122587.
Brosset, C.; Andreasson, K.; Perm, M. (1975) The nature and possible origin of acid particles observed at the
Swedish west coast. Atmos. Environ. 9: 631-642.
Brown, N. J.; Dod, R. L.; Mowrer, F. W.; Novakov, T.; Williamson, R. B. (1989) Smoke emission factors
from medium-scale fires: part 1. Aerosol Sci. Technol. 10: 2-19.
Buat-Menard, P.; Duce, R. A. (1986) Precipitation scavenging of aerosol particles over remote marine regions.
Nature (London) 321: 508-510.
Burkhard, E. G.; Dutkiewicz, V. A.; Husain, L. (1994) A study of SC^, 804" and trace elements in clear air and
clouds above the midwestern United States. Atmos. Environ. 28: 1521-1533.
Burton, R. M.; Lundgren, D. A. (1987) Wide range aerosol classifier: a size selective sampler for large
particles. Aerosol Sci. Technol. 6: 289-301.
Burtscher, H. (1992) Measurement and characteristics of combustion aerosols with special consideration of
photoelectric charging and charging by flame ions. J. Aerosol Sci. 23: 549-595.
Burtscher, H.; Leonardi, A.; Steiner, D.; Baltensperger, U.; Weber, A. (1993) Aging of combustion particles in
the atmosphere - results from a field study in Zurich. Water Air Soil Pollut. 68: 137-147.
Cadle, S. H.; Dasch, J. M. (1988) Wintertime concentrations and sinks of atmospheric particulate carbon at a
rural location in northern Michigan. Atmos. Environ. 22: 1373-1381.
Cahill, T. A.; Surovik, M.; Wittmeyer, I. (1990) Visibility and aerosols during the 1986 Carbonaceous Species
Methods Comparison Study. Aerosol Sci. Technol. 12: 149-160.
Calvert, J. G.; Su, F.; Bottenheim, J. W.; Strausz, O. P. (1978) Mechanism of the homogeneous oxidation of
sulfur dioxide in the troposphere. In: Sulfur in the atmosphere: proceedings of the international
symposium; September 1977; Dubrovnik, Yugoslavia. Atmos. Environ. 12: 197-226.
Calvert, J. G.; Lazrus, A.; Kok, G. L.; Heikes, B. G.; Walega, J. G.; Lind, J.; Cantrell, C. A. (1985)
Chemical mechanisms of acid generation in the troposphere. Nature (London) 317: 27-35.
Cambray, R. S. (1989) Radioactive fallout in air and rain: results to the end of 1987. Harwell, United Kingdom:
Atomic Energy Establishment; report no. AERE-R 13226.
3-197
-------
Cambray, R. S.; Cawse, P. A.; Garland, J. A.; Gibson, J. A. B.; Johnson, P.; Lewis, G. N. J.; Newton, D.;
Salmon, L.; Wade, B. O. (1987) Observations on radioactivity from the Chernobyl accident. Nucl.
Energy (Br. Nucl. Energy Soc.) 26: 77-101.
Carpenter, S. B.; Montgomery, T. L.; Leavitt, J. M.; Colbaugh, W. C.; Thomas, F. W. (1971) Principal plume
dispersion models: TVA power plants. J. Air Pollut. Control Assoc. 21: 491-495.
Carras, J. N.; Williams, D. J. (1981) The long-range dispersion of a plume from an isolated point source.
Atmos. Environ. 15: 2205-2217.
Carras, J. N.; Williams, D. J. (1988) Measurements of relative ay up to 1800 km from a single source. Atmos.
Environ. 22: 1061-1069.
Carter, E. J.; Borys, R. D. (1993) Aerosol-cloud chemical fractionation: enrichment factor analysis of cloud
water. J. Atmos. Chem. 17: 277-292.
Cass, G. R. (1979) On the relationship between sulfate air quality and visibility with examples in Los Angeles.
Atmos. Environ. 13: 1069-1084.
Cass, G. R.; Shair, F. H. (1984) Sulfate accumulation in a sea breeze/land breeze circulation system.
J. Geophys. Res. [Atmos.] 89: 1429-1438.
Cass, G. R.; Boone, P. M.; Macias, E. S. (1982) Emissions and air quality relationships for atmospheric carbon
particles in Los Angeles. In: Wolff, G. T.; Klimisch, R. L., eds. Paniculate carbon: atmospheric life
cycle. New York, NY: Plenum Press; pp. 207-243.
Cawse, P. A. (1981) Trace elements in the atmosphere of the United Kingdom. Presented at: ESNA meeting;
September-October; Aberdeen, Scotland.
Chamberlain, A. C. (1983) Deposition and resuspension. In: Pruppacher, H. R.; Semonin, R. G.; Slinn,
W. G. N., eds. Precipitation scavenging, dry deposition, and resuspension, v. 2: dry deposition and
resuspension: proceedings of the fourth international conference; November-December 1982; Santa
Monica, CA. New York, NY: Elsevier; pp. 731-751.
Chameides, W. L. (1984) The photochemistry of a remote marine stratiform cloud. J. Geophys. Res. [Atmos.]
89: 4739-4755.
Chameides, W. L.; Davis, D. D. (1982) The free radical chemistry of cloud droplets and its impact upon the
composition of rain. J. Geophys. Res. C: Oceans Atmos. 87: 4863-4877.
Chan, W. H.; Tang A. J. S.; Chung, D. H. S.; Lusis, M. A. (1986) Concentration and deposition of trace
metals in Ontario - 1982. Water Air Soil Pollut. 29: 373-389.
Chan, C. K.; Flagan, R. C.; Seinfeld, J. H. (1992) Water activities of NH4NO3/(NH4)2SO4 solutions. Atmos.
Environ. Part A 26: 1661-1673.
Chang, S. G.; Brodzinsky, R.; Gundel, L. A.; Novakov, T. (1982) Chemical and catalytic properties of
elemental carbon. In: Wolff, G. T.; Klimisch, R. L., eds. Paniculate carbon: atmospheric life cycle.
New York, NY: Plenum Press; pp. 158-181.
3-198
-------
Chang, J. S.; Middleton, P. B.; Stockwell, W. R.; Walcek, C. J.; Pleim, J. E.; Lansford, H. H.;
Madronich, S.; Binkowski, F. S.; Seaman, N. L.; Stauffer, D. R. (1991) The regional acid deposition
model and engineering model. In: Irving, P. M., ed. Acidic deposition: state of science and technology,
volume I: emissions, atmospheric processes, and deposition. Washington, DC: The U.S. National Acid
Precipitation Assessment Program. (State of science and technology report no. 4).
Chapman, E. G.; Luecken, D. J.; Dana, M. T.; Easter, R. C.; Hales, J. M.; Laulainen, N. S.; Thorp, J. M.
(1987) Inter-storm comparisons from the OSCAR high-density network experiment. Atmos. Environ.
21: 531-549.
Cheng, Y.-S.; Carpenter, R. L.; Barr, E. B.; Hobbs, C. H. (1985) Size distribution of fine particle emissions
from a steam plant with a fluidized-bed coal combustor. Aerosol Sci. Technol. 4: 175-189.
Ching, J. K. S.; Alkezweeny, A. J. (1986) Tracer study of vertical exchange by cumulus clouds. J. Clim. Appl.
Meteorol. 25: 1702-1711.
Choularton, T. W.; Wicks, A. J.; Downer, R. M.; Gallagher, M. W.; Penkett, S. A.; Bandy, B. J.; Dollard,
G. J.; Jones, B. M. R.; Davies, T. D.; Gay, M. J.; Tyler, B. J.; Fowler, D.; Cape, J. N.; Hargreaves,
K. J. (1992) A field study of the generation of nitrate in a hill cap cloud. Environ. Pollut. 75: 69-73.
Chow, J. C.; Watson, J. G.; Lowenthal, D. H.; Solomon, P. A.; Magliano, K. L.; Ziman, S. D.; Richards,
L. W. (1992) PM10 source apportionment in California's San Joaquin Valley. Atmos. Environ. Part A
26: 3335-3354.
Chow, J. C.; Watson, J. G.; Pritchett, L. C.; Pierson, W. R.; Frazier, C. A.; Purcell, R. G. (1993a) The DRI
thermal/optical reflectance carbon analysis system: description, evaluation and applications in U.S. air
quality studies. In: Lodge, J. P., Jr. Fourth international conference on carbonaceous particles in the
atmosphere; April 1991; Vienna, Austria. Atmos. Environ. Part A 27: 1185-1201.
Chow, J. C.; Watson, J. G.; Lowenthal, D. H.; Solomon, P. A.; Magliano, K. L.; Ziman, S. D.; Richards,
L. W. (1993b) PM10 and PM2 5 compositions in California's San Joaquin Valley. Aerosol Sci. Technol.
18: 105-128.
Chow, J. C.; Watson, J. G.; Fujita, E. M.; Lu, Z.; Lawson, D. R.; Ashbaugh, L. L. (1994) Temporal and
spatial variations of PM2 5 and PM10 aerosol in the Southern California Air Quality Study. Atmos.
Environ. 28: 2061-2080.
Chughtai, A. R.; Jassim, J. A.; Peterson, J. H.; Stedman, D. H.; Smith, D. M. (1991) Spectroscopic and
solubility characteristics of oxidized soots. Aerosol Sci. Technol. 15: 112-126.
Clark, T. L.; Cohn, R. D. (1990) The Across North America Tracer Experiment (ANATEX) model evaluation
study. Research Triangle Park, NC: U.S. Environmental Protection Agency, Atmospheric Research and
Exposure Assessment Laboratory; EPA report no. EPA/600/3-90/051. Available from: NTIS,
Springfield, VA; PB90-261454.
Clark, P. A.; Fletcher, I. S.; Kallend, A. S.; McElroy, W. J.; Marsh, A. R. W.; Webb, A. H. (1984)
Observations of cloud chemistry during long-range transport of power plant plumes. Atmos. Environ.
18: 1849-1858.
Clarke, A. D. (1989) Aerosol light absorption by soot in remote environments. Aerosol Sci. Technol.
10: 161-171.
Clarke, A. D. (1992) Atmospheric nuclei in the remote free-troposphere. J. Atmos. Chem. 14: 479-488.
3-199
-------
Clarke, A. D. (1993) Atmospheric nuclei in the Pacific midtroposphere—their nature, concentration, and
evolution. J. Geophys. Res. [Atmos.] 98: 20,633-20,647.
Clarke, A. G.; Karani, G. N. (1992) Characterisation of the carbonate content of atmospheric aerosols.
J. Atmos. Chem. 14: 119-128.
Clarke, A. G.; Radojevic, M. (1987) Oxidation of SO2 in rainwater and its role in acid rain chemistry. Atmos.
Environ. 21: 1115-1123.
Clarke, J. F.; Clark, T. L.; Ching, J. K. S.; Haagenson, P. L.; Husar, R. B.; Patterson, D. E. (1983)
Assessment of model simulation of long-distance transport. Atmos. Environ. 17: 2449-2462.
Clarke, A. D.; Weiss, R. E.; Charlson, R. J. (1984) Elemental carbon aerosols in the urban, rural and
remote-marine troposphere and in the stratosphere: interferences from light absorption data and
consequences regarding radiative transfer. Sci. Total Environ. 36: 97-102.
Cobourn, W. G.; Husar, R. B.; Husar, J. D. (1978) Continuous in situ monitoring of ambient paniculate sulfur
using flame photometry and thermal analysis. In: Husar, R. B.; Lodge, J. P., Jr.; Moore, D. J., eds.
Sulfur in the atmosphere: proceedings of the international symposium; September 1977; Dubrovnik,
Yugoslavia. Atmos. Environ. 12: 89-98.
Cocks, A. T.; McElroy, W. L.; Wallis, P. G. (1982) The oxidation of sodium sulphite solutions by hydrogen
peroxide. Central Electricity Research Laboratories; report no. RD/L/2215N81.
Cofer, W. R., Ill; Stevens, R. K.; Winstead, E. L.; Pinto, J. P.; Sebacher, D. I.; Abdulraheem, M. Y.;
Al-Sahafi, M.; Mazurek, M. A.; Rasmussen, R. A.; Gaboon, D. R.; Levine, J. S. (1992) Kuwaiti oil
fires: compositions of source smoke. J. Geophys. Res. [Atmos.] 97: 14,521-14,525.
Cohen, M. D.; Flagan, R. C.; Seinfeld, J. H. (1987a) Studies of concentrated electrolyte solutions using the
electrodynamic balance. 1. Water activities for single-electrolyte solutions. J. Phys. Chem.
91: 4563-4574.
Cohen, M. D.; Flagan, R. C.; Seinfeld, J. H. (1987b) Studies of concentrated electrolyte solutions using the
electrodynamic balance. 2. Water activities for mixed-electrolyte solutions. J. Phys. Chem.
91: 4575-4582.
Colbeck, I.; Appleby, L.; Hardman, E. J.; Harrison, R. M. (1990) The optical properties and morphology of
cloud-processed carbonaceous smoke. J. Aerosol Sci. 21: 527-538.
Collett, J. L., Jr.; Oberholzer, B.; Mosimann, L.; Staehelin, J.; Waldvogel, A. (1993a) Contributions of cloud
processes to precipitation chemistry in mixed phase clouds. Water Air Soil Pollut. 68: 43-57.
Collett, J., Jr.; Oberholzer, B.; Staehelin, J. (1993b) Cloud chemistry in Mt. Rigi Switzerland: dependence on
drop size and relationship to precipitation chemistry. Atmos. Environ. Part A 27: 33-42.
Colvile, R. N.; Choularton, T. W.; Gallagher, M. W.; Wicks, A. J.; Downer, R. M.; Tyler, B. J.;
Storeton-West, K. J.; Fowler, D.; Cape, J. N.; Dollard, G. J.; Davies, T. J.; Jones, B. M. R.; Penkett,
S. A.; Bandy, B. J.; Burgess, R. A. (1994) Observation on Great Dun Fell of the pathways by which
oxides of nitrogen are converted to nitrate. Atmos. Environ. 28: 397-408.
Countess, R. J.; Wolff, G. T.; Cadle, S. H. (1980) The Denver winter aerosol: a comprehensive chemical
characterization. J. Air Pollut. Control Assoc. 30: 1194-1200.
3-200
-------
Coutant, R. W.; Brown, L.; Chuang, J. C.; Riggin, R. M.; Lewis, R. G. (1988) Phase distribution and artifact
formation in ambient air sampling for polynuclear aromatic hydrocarbons. Atmos. Environ. 22: 403-409.
Coutant, R. W.; Callahan, P. J.; Chuang, J. C.; Lewis, R. G. (1992) Efficiency of silicone-grease-coated
denuders for collection of polynuclear aromatic hydrocarbons. Atmos. Environ. Part A 26: 2831-2834.
Covert, D. S.; Heintzenberg, J. (1984) Measurement of the degree of internal/external mixing of hygroscopic
compounds and soot in atmospheric aerosols. Sci. Total Environ. 36: 347-352.
Covert, D. S.; Charlson, R. J.; Ahlquist, N. C. (1972) A study of the relationship of chemical composition and
humidity to light scattering by aerosols. J. Appl. Meteorol. 11: 968-976.
Covert, D. S.; Heintzenberg, J.; Hansson, H.-C. (1990) Electro-optical detection of external mixtures in
aerosols. Aerosol Sci. Technol. 12: 446-456.
Covert, D. S.; Kapustin, V. N.; Quinn, P. K.; Bates, T. S. (1992) New particle formation in the marine
boundary layer. J. Geophys. Res. [Atmos.] 97: 20,581-20,589.
Cronn, D. R.; Charlson, R. J.; Knights, R. L.; Crittenden, A. L.; Appel, B. R. (1977) A survey of the
molecular nature of primary and secondary components of particles in urban air by high-resolution mass
spectrometry. Atmos. Environ. 11: 929-937.
Currie, L. A.; Stafford, T. W.; Sheffield, A. E.; Klouda, G. A.; Wise, S. A.; Fletcher, R. A.; Donahue, D. J.;
Ml, A. J. T.; Linick, T. W. (1989) Microchemical and molecular dating. Radiocarbon 31: 448-463.
Currie, L. A.; Sheffield, A. E.; Riederer, C.; Gordon, G. E. (1994) Improved atmospheric understanding
through exploratory data analysis and complementary modeling: the urban K-Pb-C system. Atmos.
Environ. 28: 1359-1369.
Daisey, J. M. (1987) Chemical composition of inhalable paniculate matter—seasonal and intersite comparisons.
In: Lioy, P. J.; Daisey, J. M., eds. Toxic air pollution: a comprehensive study of non-criteria air
pollutants. Chelsea, MI: Lewis Publishers, Inc.; pp. 45-65.
D'Almeida, G. A. (1989) Desert aerosol: characteristics and effects on climate. In: Leinen, M.; Sarnthein, M.
Paleoclimatology and paleometeorology: modern and past patterns of global atmospheric transport.
Boston, MA: Kluwer Academic Publishers; pp. 311-338. (NATO ASI series. Series C, mathematical and
physical sciences: v. 282).
Dana, M. T.; Drewes, D. R.; Glover, D. W.; Hales, J. M. (1976) Precipitation scavenging of fossil-fuel
effluents. Research Triangle Park, NC: U.S. Environmental Protection Agency, Environmental Sciences
Research Laboratory; report no. EPA-600/4-76-031. Available from: NTIS, Springfield, VA;
PB-256649.
Danielsen, E. F. (1961) Trajectories: isobaric, isentropic and actual. J. Meteorol. 18: 479-486.
Dasch, J. M.; Cadle, S. H. (1989) Atmospheric carbon particles in the Detroit urban area: wintertime sources
and sinks. Aerosol Sci. Technol. 10: 236-248.
Daum, P. H. (1988) Processes determining cloudwater composition: inferences from field measurements.
In: Unsworth, M. H.; Fowler, D., eds. Acid deposition at high elevation sites. Dordrecht,
The Netherlands: Kluwer; pp. 139-153.
Daum, P. H.; Kelly, T. J.; Schwartz, S. E.; Newman, L. (1984a) Measurements of the chemical composition of
stratiform clouds. Atmos. Environ. 18: 2671-2684.
3-201
-------
Daum, P. H.; Schwartz, S. E.; Newman, L. (1984b) Acidic and related constituents in liquid water stratiform
clouds. J. Geophys. Res. [Atmos.] 89: 1447-1458.
Daum, P. H.; Kelly, T. J.; Strapp, J. W.; Leaitch, W. R.; Joe, P.; Schemenauer, R. S.; Isaac, G. A.; Anlauf,
K. G.; Wiebe, H. A. (1987) Chemistry and physics of a winter stratus cloud layer: a case study.
J. Geophys. Res. [Atmos.] 92: 8426-8436.
Daum, P. H.; Kleinman, L. I.; Hills, A. J.; Lazrus, A. L.; Leslie, A. C. D.; Busness, K.; Boatman, J. (1990)
Measurement and interpretation of concentrations of H2O2 and related species in the upper midwest
during summer. J. Geophys. Res. [Atmos.] 95: 9857-9871.
Daum, P. H.; Al-Sunaid, A.; Busness, K. M.; Hales, J. M.; Mazurek, M. (1993) Studies of the Kuwait oil fire
plume during midsummer 1991. J. Geophys. Res. [Atmos.] 98: 16,809-16,827.
Da'umer, B.; Niessner, R.; Klockow, D. (1992) Laboratory studies of the influence of thin organic films on the
neutralization reaction of H2SO4 aerosol with ammonia. J. Aerosol Sci. 23: 315-325.
Davidson, C. I.; Wu, Y.-L. (1990) Dry deposition of particles and vapors. In: Lindberg, S. E.; Page, A. L.;
Norton, S. A., eds. Acidic precipitation: v. 3, sources, deposition, and canopy interactions. New York,
NY: Springer-Verlag; pp. 103-216.
De Bock, L. A.; Van Malderen, H.; Van Grieken, R. E. (1994) Individual aerosol particle composition
variations in air masses crossing the North Sea. Environ. Sci. Technol. 28: 1513-1520.
Delumyea, R. D.; Kalivretenos, A. (1987) Elemental carbon and lead content of fine particles from American
and French cities of comparable size and industry, 1985. Atmos. Environ. 21: 1643-1647.
Dennis, R. L.; McHenry, J. N.; Barchet, W. R.; Binkowski, F. S.; Byun, D. W. (1993) Correcting RADM's
sulfate underprediction: discovery and correction of model errors and testing the corrections through
comparisons against field data. Atmos. Environ. Part A 27: 975-997.
De Raat, W. K.; Bakker, G. L.; de Meijere, F. A. (1990) Comparison of filter materials used for sampling of
mutagens and polycyclic aromatic hydrocarbons in ambient airborne particles. Atmos. Environ. Part A
24: 2875-2887.
De Santis, F.; Allegrini, I. (1992) Heterogeneous reactions of SO2 and NO2 on carbonaceous surfaces. Atmos.
Environ. Part A 26: 3061-3064.
De Valk, J. P. J. M. M. (1994) A model for cloud chemistry: a comparison between model simulations and
observations in stratus and cumulus. Atmos. Environ. 28: 1665-1678.
Dickerson, R. R.; Huffman, G. J.; Luke, W. T.; Nunnermacker, L. J.; Pickering, K. E.; Leslie, A. C. D.;
Lindsey, C. G.; Slinn, W. G. N.; Kelly, T. J.; Daum, P. H.; Delany, A. C.; Greenberg, J. P.;
Zimmerman, P. R.; Boatman, J. F.; Ray, J. D.; Stedman, D. H. (1987) Thunderstorms: an important
mechanism in the transport of air pollutants. Science (Washington, DC) 235: 460-465.
Dittenhoefer, A. C.; de Pena, R. G. (1978) A study of production and growth of sulfate particles in plumes from
a coal-fired power plant. Atmos. Environ. 12: 297-306.
Dlugi, R. (1989) Chemistry and deposition of soot particles in moist air and fog. Aerosol Sci. Technol.
10: 93-105.
Dlugi, R.; Glisten, H. (1983) The catalytic and photocatalytic activity of coal fly ashes. Atmos. Environ.
17: 1765-1771.
3-202
-------
Dod, R. L.; Brown, N. J.; Mowrer, F. W.; Novakov, T.; Williamson, R. B. (1989) Smoke emission factors
from medium-scale fires: part 2. Aerosol Sci. Technol. 10: 20-27.
Doyle, G. J.; Tuazon, E. C.; Graham, R. A.; Mischke, T. M.;.Winer, A. M.; Pitts, J. N., Jr. (1979)
Simultaneous concentrations of ammonia and nitric acid in a polluted atmosphere and their equilibrium
relationship to paniculate ammonium nitrate. Environ. Sci. Technol. 13: 1416-1419.
Draxler, R. R. (1982) Measuring and modeling the transport and dispersion of Krypton-85 1500 km from a point
source. Atmos. Environ. 16: 2763-2776.
Draxler, R. R. (1984) Diffusion and transport experiments. In: Randerson, D., ed. Atmospheric science and
power production. Washington, DC: U.S. Department of Energy, Office of Scientific and Technical
Information; pp. 367-422; report no. DOE/TIC-27601. Available from: NTIS, Springfield, VA;
DE84-005177.
Draxler, R. R.; Dietz, R.; Lagomarsino, R. J.; Start, G. (1991) Across North America Tracer Experiment
(ANATEX): sampling and analysis. Atmos. Environ. Part A 25: 2815-2836.
Drewes, D. R.; Hales, J. M. (1982) SMICK—a scavenging model incorporating chemical kinetics. Atmos.
Environ. 16: 1717-1724.
Duce, R. A.; Mohnen, V. A.; Zimmerman, P. R.; Grosjean, D.; Cautreels, W.; Chatfield, R.; Jaenicke, R.;
Ogren, J. A.; Pellizzari, E. D.; Wallace, G. T. (1983) Organic material in the global troposphere. Rev.
Geophys. Space Phys. 21: 921-952.
Durham, J. L.; Wilson, W. E.; Ellestad, T. G.; Willeke, K.; Whitby, K. T. (1975) Comparison of volume and
mass distributions for Denver aerosols. Atmos. Environ. 9: 717-722.
Dzubay, T. G.; Stevens, R. K.; Gordon, G. E.; Olmez, I.; Sheffield, A. E.; Courtney, W. J. (1988)
A composite receptor method applied to Philadelphia aerosol. Environ. Sci. Technol. 22: 46-52.
Eatough, D. J.; Richter, B. E.; Eatough, N. L.; Hansen, L. D. (1981) Sulfur chemistry in smelter and power
plant plumes in the western U.S. In: White, W. H.; Moore, D. J.; Lodge, J. P., Jr., eds. Plumes and
visibility: measurements and model components: proceedings of the symposium; November 1980; Grand
Canyon National Park, AZ. Atmos. Environ. 15: 2241-2253.
Eatough, D. J.; Christensen, J. J.; Eatough, N. L.; Hill, M. W.; Major, T. D.; Mangelson, N. F.; Post, M .E.;
Ryder, J. F.; Hansen, L. D.; Meisenheimer, R. G.; Fischer, J. W. (1982) Sulfur chemistry in a copper
smelter plume. Atmos. Environ. 16: 1001-1015.
Eatough, D. J.; Arthur, R. J.; Eatough, N. L.; Hill, M. W.; Mangelson, N. F.; Richter, B. E.; Hansen, L. D.;
Cooper, J. A. (1984) Rapid conversion of SO2(g) to sulfate in a fog bank. Environ. Sci. Technol.
18: 855-859.
Eatough, D. J.; Sedar, B.; Lewis, L.; Hansen, L. D.; Lewis, E. A.; Farber, R. J. (1989) Determination of
semivolatile organic compounds in particles in the Grand Canyon area. Aerosol Sci. Technol.
10: 438-449.
Eatough, D. J.; Wadsworth, A.; Eatough, D. A.; Crawford, J. W.; Hansen, L. D.; Lewis, E. A. (1993)
A multiple-system, multi-channel diffusion denuder sampler for the determination of fme-particulate
organic material in the atmosphere. Atmos. Environ. Part A 27: 1213-1219.
3-203
-------
Eatough, D. J.; Tang, H.; Cui, W.; Machir, J. (1995) Determination of the size distribution and chemical
composition of fine paniculate semi-volatile organic material in urban environments using diffusion
denuder technology. In: Phalen, R. F.; Bates, D. V., eds. Proceedings of the colloquium on paniculate
air pollution and human mortality and morbidity, part II; Janaury 1994; Irvine, CA. Inhalation Toxicol.
7: 691-710.
Eisele, F. L.; Bradshaw, J. D. (1993) The elusive hydroxyl radical: measuring OH in the atmosphere. Anal.
Chem. 65: 927A-939A.
Eisele, F. L.; Tanner, D. J. (1993) Measurement of the gas phase concentration of H2SO4 and methane sulfonic
acid and estimates of H2SO4 production and loss in the atmosphere. J. Geophys. Res. [Atmos.]
98: 9001-9010.
Eldering, A.; Cass, G. R.; Moon, K. C. (1994) An air monitoring network using continuous particle size
distribution monitors: connecting pollutant properties to visibility via Mie scattering calculations. Atmos.
Environ. 28: 2733-2749.
Eldred, R. A.; Cahill, T. A.; Flocchini, R. G. (1994) Comparison of PM10 and PM2 5 aerosols in the IMPROVE
network. In: Proceedings of an international specialty conference on aerosol and atmospheric optics:
radiative balance and visual air quality, volume A. Pittsburgh, PA: Air and Waste Management
Association. Air Waste: submitted.
Eltgroth, M. W.; Hobbs, P. V. (1979) Evolution of particles in the plumes of coal-fired power plants—
II. A numerical model and comparisons with field measurements. Atmos. Environ. 13: 953-975.
Er-El, J.; Peskin, R. L. (1981) Relative diffusion of constant-level balloons in the southern hemisphere.
J. Atmos. Sci. 38: 2264-2274.
Erickson, R. E.; Yates, L. M.; Clark, R. L.; McEwen, D. (1977) The reaction of sulfur dioxide with ozone in
water and its possible atmospheric significance. Atmos. Environ. 11: 813-817.
Facchini, M. C.; Fuzzi, S.; Lind, J. A.; Fierlinger-Oberlinninger, H.; Kalina, M.; Puxbaum, H.;
Winiwarter, W.; Arends, B. G.; Wobrock, W.; Jaeschke, W.; Berner, A.; Kruisz, C. (1992)
Phase-partitioning and chemical reactions of low molecular weight organic compounds in fog.
Tellus Ser. B 44B: 533-544.
Falerios, M.; Schild, K.; Sheehan, P.; Paustenbach, D. (1992) Airborne concentrations of trivalent and
hexavalent chromium from contaminated soils at unpaved partially paved commercial/industrial sites.
J. Air Waste Manage. Assoc. 42: 40-48.
Ferber, G. J.; Telegadas, K.; Heffter, J. L.; Dickson, C. R.; Dietz, R. N.; Krey, P. W. (1981) Demonstration
of a long-range atmospheric tracer system using perfluorocarbons. Silver Springs, MD: National Oceanic
and Atmospheric Administration; NOAA report no. NOAA TM ERL ARL-101.
Ferber, G. J.; Heffter, J. L.; Draxler, R. R.; Lagomarsino, R. J.; Thomas, F. L.; Dietz, R. N.; Benkovitz,
C. M. (1986) Cross-Appalachian Tracer Experiment (CAPTEX-83) final report. Silver Springs, MD:
National Oceanic and Atmospheric Administration; NOAA report no. NOAA TM ERL ARL-142.
Fernandez de la Mora, J. (1986) Inertia and interception in the deposition of particles from boundary layers.
Aerosol Sci. Technol. 5: 261-266.
Fernandez de la Mora, J.; Friedlander, S. K. (1982) Aerosol and gas deposition to fully rough surfaces: filtration
model for blade-shaped elements. Int. J. Heat Mass Transfer 25: 1725-1735.
3-204
-------
Finlayson-Pitts, B. J.; Pitts, J. N., Jr. (1986) Atmospheric chemistry: fundamentals and experimental techniques.
New York, NY: John Wiley & Sons; pp. 783-1007.
Fitzgerald, J. W. (1973) Dependence of the supersaturation spectrum of CCN on aerosol size distribution and
composition. Presented at: the second international workshop on condensation and ice nuclei;
August 1970; Fort Collins, CO. J. Atmos. Sci. 30: 628-634.
Fitzgerald, J. W.; Hoppel, W. A.; Vietti, M. A. (1982) The size and scattering coefficient of urban aerosol
particles at Washington, DC as a function of relative humidity. J. Atmos. Sci. 39: 1838-1852.
Flossmann, A. I.; Hall, W. D.; Pruppacher, H. R. (1985) A theoretical study of the wet removal of atmospheric
pollutants. Part I: The redistribution of aerosol particles captured through nucleation and impaction
scavenging by growing cloud drops. J. Atmos. Sci. 42: 583-606.
Foitzik, L. (1950) Zur meteorologischen Optik von Dunst und Nebel: Teil II [The meteorological optics of haze
and fog: part II]. Z. Meteorol. 4: 321-329.
Foreman, W. T.; Bidleman, T. F. (1990) Semivolatile organic compounds in the ambient air of Denver,
Colorado. Atmos. Environ. Part A 24: 2405-2416.
Forkel, R.; Seidl, W.; Dlugi, R.; Deigele, E. (1990) A one-dimensional numerical model to simulate formation
and balance of sulfate during radiation fog events. J. Geophys. Res. [Atmos.] 95: 18,501-18,515.
Forrest, J.; Newman, L. (1973) Sampling and analysis of atmospheric sulfur compounds for isotope ratio studies.
Atmos. Environ. 7: 561-573.
Forrest, J.; Newman, L. (1977a) Further studies on the oxidation of sulfur dioxide in coal-fired power plant
plumes. Atmos. Environ. 11: 465-474.
Forrest, J.; Newman, L. (1977b) Oxidation of sulfur dioxide in the Sudbury smelter plume. Atmos. Environ.
11: 517-520.
Forrest, J.; Garber, R.; Newman, L. (1979) Formation of sulfate, ammonium and nitrate in an oil-fired power
plant plume. Atmos. Environ. 13: 1287-1297.
Forrest, J.; Garber, R. W.; Newman, L. (1981) Conversion rates in power plant plumes based on filter pack
data: the coal-fired Cumberland plume. Atmos. Environ. 15: 2273-2282.
Freeman, D. J.; Cattell, F. C. R. (1990) Woodburning as a source of atmospheric polycyclic aromatic
hydrocarbons. Environ. Sci. Technol. 24: 1581-1585.
Frick, G. M.; Hoppel, W. A. (1993) Airship measurements of aerosol size distributions, cloud droplet spectra,
and trace gas concentrations in the marine boundary layer. Bull. Am. Meteorol. Soc. 74: 2195-2202.
Fried, A.; Henry, B. E.; Calvert, J. G.; Mozurkewich, M. (1994) The reaction probability of N2O5 with sulfuric
acid aerosols at stratospheric temperatures and compositions. J. Geophys. Res. [Atmos.] 99: 3517-3532.
Friedlander, S. K. (1970) The characterization of aerosols distributed with respect to size and chemical
composition. J. Aerosol Sci. 1: 295-307.
Friedlander, S. K.; Turner, J. R.; Hering, S. V. (1986) A new method for estimating dry deposition velocities
for atmospheric aerosols. J. Aerosol Sci. 17: 240-244.
3-205
-------
Fung, C. S.; Misra, P. K.; Bloxam, R.; Wong, S. (1991) A numerical experiment on the relative importance of
H2O2 and O3 in aqueous conversion of S02 to SO42'. Atmos. Environ. Part A 25: 411-423.
Fuzzi, S.; Castillo, R. A.; Jiusto, J. E.; Lala, G. G. (1984) Chemical composition of radiation fog water at
Albany, New York, and its relationship to fog microphysics. J. Geophys. Res. [Atmos.] 89: 7159-7164.
Fuzzi, S.; Orsi, G.; Nardini, G.; Facchini, M. C.; McLaren, S.; McLaren, E.; Mariotti, M. (1988)
Heterogeneous processes in the Po Valley radiation fog. J. Geophys. Res. [Atmos.] 93: 11,141-11,151.
Gagosian, R. B.; Peltzer, E. T.; Merrill, J. T. (1987) Long-range transport of terrestrially derived lipids in
aerosols from the south Pacific. Nature (London) 325: 800-803.
Galloway, J. N.; Thornton, J. D.; Norton, S. A.; Volchok, H. L.; McLean, R. A. N. (1982) Trace metals in
atmospheric deposition: a review and assessment. Atmos. Environ. 16: 1677-1700.
Garland, J. A. (1979) Resuspension of paniculate matter from grass and soil. Harwell, United Kingdom: Atomic
Energy Research Establishment; report no. AERE-R9452. Available from: NTIS, Springfield, VA.;
AERE-R9452.
Gatz, D. F. (1977) Scavenging ratio measurements in METROMEX. In: Semonin, R. G.; Beadle, R. W., eds.
Precipitation scavenging (1974): proceedings of a symposium; October 1974; Champaign, IL. Oak Ridge,
TN: Energy Research and Development Administration; pp. 71-87. Available from: NTIS, Springfield,
VA; CONF-741003. (ERDA symposium series no. 41).
Gebhart, K. A.; Malm, W. C.; Day, D. (1994) Examination of the effects of sulfate acidity and relative humidity
on light scattering at Shenandoah National Park. Atmos. Environ. 28: 841-849.
Gerde, P.; Scholander, P. (1989) Mass transfer rates of polycyclic aromatic hydrocarbons between micron-size
particles and their environment—theoretical estimates. Environ. Health Perspect. 79: 249-258.
Germani, M. S.; Buseck, P. R. (1991) Automated scanning electron microscopy for atmospheric particle
analysis. Anal. Chem. 63: 2232-2237.
Gervat, G. P.; Clark, P. A.; Marsh, A. R. W.; Choularton, T. W.; Gay, M. J. (1988) Controlled chemical
kinetic experiments in cloud: a review of the CERL/UMIST Great Dun Fell project. In: Unsworth,
M. H.; Fowler, D., eds. Acid deposition at high elevation sites: proceedings of the NATO advanced
research workshop; September 1986; Edinburgh, United Kingdom. Dordrecht, The Netherlands: Kluwer
Academic Publishers; pp. 283-298. (NATO ASI series C: mathematical and physical sciences v. 252).
Gery, M. W.; Fox, D. L.; Jeffries, H. E.; Stockburger, L.; Weathers, W. S. (1985) A continuous stirred tank
reactor investigation of the gas-phase reaction of hydroxyl radicals and toluene. Int. J. Chem. Kinet.
17: 931-955.
Gery, M. W.; Fox, D. L.; Kamens, R. M.; Stockburger, L. (1987) Investigation of hydroxyl radical reactions
with o-xylene and m-xylene in a continuous stirred tank reactor. Environ. Sci. Technol. 21: 339-348.
Ghan, S. J.; Chuang, C. C.; Penner, J. E. (1993) A parameterization of cloud droplet nucleation, part I: single
aerosol type. Atmos. Res. 30: 198-221.
Gifford, F. A., Jr. (1961) Use of routine meteorological observations for estimating atmospheric dispersion.
Nucl. Saf. 2: 47-51.
Gill, P. S.; Graedel, T. E.; Wechsler, C. J. (1983) Organic films on atmospheric aerosol particles, fog droplets,
cloud droplets, raindrops and snowflakes. Rev. Geophys. Space Phys. 21: 903-920.
3-206
-------
Gillani, N. V. (1985) Modeling of chemical transformations of SOX and NOX in the polluted atmosphere—
an overview of approaches and current status. In: De Wispelaere, C., ed. Air pollution modeling and its
application IV. New York, NY: Plenum Publishers; pp. 163-192.
Gillani, N. V. (1986) Ozone formation in pollutant plumes: a reactive plume model with arbitrary crosswind
resolution. Research Triangle Park, NC: U.S. Environmental Protection Agency, Atmospheric Sciences
Research Laboratory; EPA report no. EPA/600/3-86/051. Available from: NTIS, Springfield, VA;
PB86-236973.
Gillani, N. V.; Husar, R. B. (1976) Synoptic-scale haziness over the eastern US and its long range transport.
Presented at: 4th National AMS/SAF conference on fire and forest meteorology; Boston, MA.
Gillani, N. V.; Pleim, J. E. (1995) Subgrid-scale features of anthropogenic emissions of VOC and NOx in the
context of regional Eulerian models. Atmos. Environ.: in press.
Gillani, N. V.; Wilson, W. E. (1980) Formation and transport of ozone and aerosols in power plant plumes.
Ann. N. Y. Acad. Sci. 338: 276-296.
Gillani, N. V.; Wilson, W. E. (1983) Gas-to-particle conversion of sulfur in power plant plumes—
II. observations of liquid-phase conversions. Atmos. Environ. 17: 1739-1752.
Gillani, N. V.; Husar, R. B.; Husar, J. D.; Patterson, D. E.; Wilson, W. E., Jr. (1978) Project MISTT: kinetics
of paniculate sulfur formation in a power plant plume out to 300 km. Atmos. Environ. 12: 589-598.
Gillani, N. V.; Kohli, S.; Wilson, W. E. (1981) Gas-to-particle conversion of sulfur in power plant plumes—
I. parametrization of the conversion rate for dry, moderately polluted ambient conditions.
Atmos. Environ. 15: 2293-2313.
Gillani, N. V.; Colby, J. A.; Wilson, W. E. (1983) Gas-to-particle conversion of sulfur in power plant plumes-
Ill, parameterization of plume-cloud interactions. Atmos. Environ. 17: 1753-1763.
Gillani, N. V.; Shannon, J. D.; Patterson, D. E. (1984) Transport processes. In: Altshuller, A. P.; Linthurst,
R. A., eds. The acidic deposition phenomenon and its effects: critical assessment review papers, v. 1:
atmospheric sciences. Washington, DC: U.S. Environmental Protection Agency, Office of Research and
Development; report no. EPA/600/8-83/016AF. Available from: NTIS, Springfield, VA; PB85-100030.
Gillani, N. V.; Schwartz, S. E.; Leaitch, W. R.; Strapp, J. W.; Isaac, G. A. (1995) Field observations in
continental stratiform clouds: partitioning of cloud particles between droplets and unactivated interstitial
aerosols. J. Geophys. Res. [Atmos.] 100: 18,687-18,706.
Gillette, D. A. (1974) On the production of soil wind erosion aerosols having the potential for long range
transport. J. Rech. Atmos. 8: 735-744.
Gillette, D. (1980) Major contributions of natural primary continental aerosols: source mechanisms. In: Kniep,
T. J.; Lioy, P. J., eds. Aerosols: anthropogenic and natural, sources and transport. Ann N. Y. Acad.
Sci. 338: 348-358.
Gillette, D. A.; Hanson, K. J. (1989) Spatial and temporal variability of dust production caused by wind erosion
in the United States. J. Geophys. Res. [Atmos.] 94: 2197-2206.
Gillette, D.; Nagamoto, C. (1992) [Size distribution and single particle composition for two dust storms in Soviet
Central Asia in September 1989 and size distributions and chemical composition of local soil].
In: Golitsyn, G., ed. Soviet-American experiment for the investigation of arid aerosols. St. Petersburg,
USSR: Typhoon; pp. 130-140.
3-207
-------
Gillette, D. A.; Passi, R. (1988) Modeling dust emission caused by wind erosion. J. Geophys. Res. [Atmos.]
93: 14,233-14,242.
Gillette, D. A.; Sinclair, P. C. (1990) Estimation of suspension of alkaline material by dust devils in the United
States. Atmos. Environ. Part A 24: 1135-1142.
Gillette, D. A.; Walker, T. R. (1977) Characteristics of airborne particles produced by wind erosion of sandy
soil, high plains of west Texas. Soil Sci. 123: 97-110.
Gillette, D. A.; Clayton, R. N.; Mayeda, T. K.; Jackson, M. L.; Sridhar, K. (1978) Tropospheric aerosols from
some major dust storms of the southwestern United States. J. Appl. Meteorol. 17: 832-845.
Gillette, D. A.; Stensland, G. J.; Williams, A. L.; Barnard, W.; Gatz, D.; Sinclair, P. C.; Johnson, T. C.
(1992) Emissions of alkaline elements calcium, magnesium, potassium, and sodium from open sources in
the contiguous United States. Global Biogeochem. Cycles 6: 437-457.
Gleason, J. F.; Sinha, A.; Howard, C. J. (1987) Kinetics of the gas-phase reaction HOSC^ + O2 -* HO2 + SO3.
J. Phys. Chem. 91: 719-724.
Godish, T. (1985) Air quality. Chelsea, MI: Lewis Publishers, Inc.
Godowitch, J. M. (1989) Evaluation and sensitivity analyses results of the MESOPUFF II model with CAPTEX
measurements. Research Triangle Park, NC: U.S. Environmental Protection Agency, Atmospheric
Research and Exposure Assessment Laboratory; EPA report no. EPA/600/3-89/056. Available from:
NTIS, Springfield, VA; PB89-198253.
Goldberg, E. D. (1985) Black carbon in the environment: properties and distribution. New York, NY: John
Wiley & Sons. (Metcalf, R. L.; Stumm, W., eds. Environmental science and technology series).
Gordon, G. E. (1991) Airborne particles on global and regional scales. Environ. Sci. Technol. 25: 1822-1828.
Gordon, R. J.; Trivedi, N. J.; Singh, B. P.; Ellis, E. C. (1988) Characterization of aerosol organics by diffuse
reflectance Fourier transform infrared spectroscopy. Environ. Sci. Technol. 22: 672-677.
Goschnick, J.; Fichtner, M.; Lipp, M.; Schuricht, J.; Ache, H. J. (1993) Depth-resolved chemical analysis of
environmental microparticles by secondary mass spectrometry. Appl. Surf. Sci. 70/71: 63-67.
Graedel, T. E.; Goldberg, K. I. (1983) Kinetic studies of raindrop chemistry: 1. inorganic and organic processes.
J. Geophys. Res. C: Oceans Atmos. 88: 10,865-10,882.
Graedel, T. E.; Weschler, C. J. (1981) Chemistry within aqueous atmospheric aerosols and raindrops. Rev.
Geophys. Space Phys. 19: 505-539.
Graedel, T. E.; Hawkins, D. T.; Claxton, L. D. (1986) Atmospheric chemical compounds: sources, occurrence,
and bioassay. Orlando, FL: Academic Press, Inc.
Granat, L.; Soderland, R. (1975) Atmospheric deposition due to long and short distance sources with special
reference to wet and dry deposition of sulfur. Stockholm, Sweden: Stockholm University, Meteorological
Institute; report no. MISU-A32.
Gray, H. A. (1986) Control of atmospheric fine primary carbon particle concentration [Ph.D. thesis]. Pasadena,
CA: California Institute of Technology; EQL report no. 23.
3-208
-------
Gray, H. A.; Cass, G. R.; Huntzicker, J. J.; Heyerdahl, E. K.; Rau, J. A. (1984) Elemental and organic carbon
particle concentrations: a long-term perspective. Sci. Total Environ. 36: 17-25.
Gray, H. A.; Cass, G. R.; Huntzicker, J. J.; Heyerdahl, E. K.; Rau, J. A. (1986) Characteristics of atmospheric
organic and elemental carbon particle concentrations in Los Angeles. Environ. Sci. Technol.
20: 580-589.
Grell, G. A.; Dudhia, J.; Stauffer, D. R. (1994) A description of the fifth-generation Perm State/NCAR
mesoscale model (MM5). Boulder, CO: National Center for Atmospheric Research; technical note no.
NCAR/TN-398+STR.
Grosjean, D. (1977) Aerosols. In: Ozone and other photochemical oxidants. Washington, DC: National Academy
of Sciences; pp. 45-125.
Grosjean, D. (1984a) Paniculate carbon in Los Angeles air. Sci. Total Environ. 32: 133-145.
Grosjean, D. (1984b) Photooxidation of 1-heptane. Sci. Total Environ. 37: 195-211.
Grosjean, D. (1985) Reactions of o-cresol and nitrocresol with NOX in sunlight and with ozone-nitrogen dioxide
mixtures in the dark. Environ. Sci. Technol. 19: 968-974.
Grosjean, D. (1992) In situ organic aerosol formation during a smog episode: estimated production and chemical
functionality. Atmos. Environ. Part A 26: 953-963.
Grosjean, D.; Friedlander, S. K. (1975) Gas-particle distribution factors for organic and other pollutants in the
Los Angeles atmosphere. J. Air Pollut. Control Assoc. 25: 1038-1044.
Grosjean, D.; Seinfeld, J. H. (1989) Parameterization of the formation potential of secondary organic aerosols.
Atmos. Environ. 23: 1733-1747.
Gundel, L. A.; Guyot-Sionnest, N. S.; Novakov, T. (1989) A study of the interaction of NOj with carbon
particles. Aerosol Sci. Technol. 10: 343-351.
Gundel, L. A.; Lee, V. C.; Mahanama, K. R. R.; Stevens, R. K.; Daisey, J. M. (1995) Direct determination of
the phase distributions of semi-volatile poly cyclic aromatic hydrocarbons using annular denuders. Atmos.
Environ. 29: 1719-1733.
Hahn, J. (1980) Organic constituents of natural aerosols. Ann. N. Y. Acad. Sci. 338: 359-376.
Hales, J. M. (1991) Atmospheric processes research and process model development. Section 4. Precipitation
scavenging. In: Irving, P. M., ed. Acidic deposition: state of science and technology, volume I:
emissions, atmospheric processes, and deposition. Washington, DC: The U.S. National Acid Precipitation
Assessment Program; pp. 2-109 - 2-168. (State of science and technology report no. 2).
Hales, J. M.; Dana, M. T. (1979) Precipitation scavenging of urban pollutants by convective storm systems.
J. Appl. Meteorol. 18: 294-316.
Hales, J. M.; Hicks, B. B.; Miller, J. M. (1987) The role of research measurement networks as contributors to
federal assessments of acid deposition. Bull. Am. Meteorol. Soc. 68: 216-225.
Hall, F. P., Jr.; Duchon, C. E.; Lee, L. G.; Hagan, R. R. (1973) Long-range transport of air pollution: a case
study, August 1970. Mon. Weather Rev. 101: 404-411.
3-209
-------
Hamilton, R. S.; Mansfield, T. A. (1991) Airborne paniculate elemental carbon: its sources, transport and
contribution to dark smoke and soiling. Atmos. Environ. Part A 25: 715-723.
Hampton, C. V.; Pierson, W. R.; Schuetzle, D.; Harvey, T. M. (1983) Hydrocarbon gases emitted from
vehicles on the road. 2. Determination of emission rates from diesel and spark-ignition vehicles. Environ.
Sci. Technol. 17: 699-708.
Hanel, G. (1976) The properties of atmospheric aerosol particles as functions of the relative humidity at
thermodynamic equilibrium with the surrounding moist air. In: Landsberg, H. E.; Van Mieghem, J., eds.
Advances in geophysics: v. 19. New York, NY: Academic Press; pp. 73-188.
Hansen, A. D. A.; Novakov, T. (1989) Real-time measurements of the size fractionation of ambient black carbon
aerosols at elevated humidities. Aerosol Sci. Technol. 10: 106-110.
Hansen, A. D. A.; Rosen, H. (1990) Individual measurements of the emission factor of aerosol black carbon in
automobile plumes. J. Air Waste Manage. Assoc. 40: 1654-1657.
Hansen, A. D. A.; Benner, W. H.; Novakov, T. (1991) Sulfur dioxide oxidation in laboratory clouds. Atmos.
Environ. Part A 25: 2521-2530.
Harrison, L. (1985) The segregation of aerosols by cloud-nucleating activity. Part II: Observation of an urban
aerosol. J. Clim. Appl. Meteorol. 24: 312-321.
Harrison, R. M.; Kitto, A.-M. N. (1992) Estimation of the rate constant for the reaction of acid sulphate aerosol
with NH3 gas from atmospheric measurements. J. Atmos. Chem. 15: 133-143.
Harrison, R. M.; Msibi, I. M. (1994) Validation of techniques for fast response measurement of HNOj and NH3
and determination of the [NH3][HNO3] concentration product. Atmos. Environ. 28: 247-255.
Harrison, R. M.; Pio, C. A. (1983) A comparative study of the ionic composition of rainwater and atmospheric
aerosols: implications for the mechanism of acidification of rainwater. Atmos. Environ. 17: 2539-2543.
Harrison, R. M.; Laxen, D. P. H.; Wilson, S. J. (1981) Chemical associations of lead, cadmium, copper, and
zinc in street dusts and roadside soils. Environ. Sci. Technol. 15: 1378-1383.
Hart, K. M.; Pankow, J. F. (1994) High-volume air sampler for particle and gas sampling. 2. Use of backup
filters to correct for the adsorption of gas-phase polycyclic aromatic hydrocarbons to the front filter.
Environ. Sci. Technol. 28: 655-661.
Hasan, H.; Dzubay, T. G. (1987) Size distributions of species in fine particles in Denver using a microorifice
impactor. Aerosol Sci. Technol. 6: 29-39.
Hatakeyama, S.; Tanonaka, T.; Weng, J.; Bandow, H.; Takagi, H.; Akimoto, H. (1985) Ozone-cyclohexene
reaction in air: quantitative analysis of paniculate products and the reaction mechanism. Environ. Sci.
Technol. 19: 935-942.
Hatakeyama, S.; Ohno, M.; Weng, J.; Takagi, H.; Akimoto, H. (1987) Mechanism for the formation of gaseous
and paniculate products from ozone-cycloalkene reactions in air. Environ. Sci. Technol. 21: 52-57.
Hatakeyama, S.; Izumi, K.; Fukuyama, T.; Akimoto, H. (1989) Reactions of ozone with a-pinene and /8-pinene
in air: yields of gaseous and paniculate products. J. Geophys. Res. [Atmos.] 94: 13,013-13,024.
3-210
-------
Hatakeyama, S.; Izumi, K.; Fukuyama, T.; Akimoto, H.; Washida, N. (1991) Reactions of OH with a-pinene
and /3-pinene in air: estimate of global CO production from the atmospheric oxidation of terpenes.
J. Geophys. Res. [Atmos.] 96: 947-958.
Hegg, D. A. (1985) The importance of liquid-phase oxidation of SO2 in the troposphere. J. Geophys. Res.
[Atmos.] 90: 3773-3779.
Hegg, D. A.; Hobbs, P. V. (1979) Some observations of paniculate nitrate concentrations in coal-fired power
plant plumes. Atmos. Environ. 13: 1715-1716.
Hegg, D. A.; Hobbs, P. V. (1980) Measurements of gas-to-particle conversion in the plumes from five coal-fired
electric power plants. Atmos. Environ. 14: 99-116.
Hegg, D. A.; Hobbs, P. V. (1982) Measurements of sulfate production in natural clouds. Atmos. Environ.
16: 2663-2668.
Hegg, D. A.; Hobbs, P. V. (1983a) Errata [Hegg and Hobbs (1982)]. Atmos. Environ. 17: 1059.
Hegg, D. A.; Hobbs, P. V. (1983b) Author's reply: measurements of sulfate production in natural clouds.
Atmos. Environ. 17: 2632-2633.
Hegg, D. A.; Hobbs, P. V. (1986) Sulfate and nitrate chemistry in cumuliform clouds. Atmos. Environ.
20: 901-909.
Hegg, D. A.; Hobbs, P. V. (1987) Comparisons of measured sulfate production due to ozone oxidation in clouds
with a kinetic rate equation. Geophys. Res. Lett. 14: 719-721.
Hegg, D. A.; Hobbs, P. V. (1988) Comparisons of sulfate and nitrate production in clouds on the mid-Atlantic
and Pacific Northwest Coasts of the United States. J. Atmos. Chem. 7: 325-333.
Hegg, D. A.; Larson, T. V. (1990) The effects of microphysical parameterization on model predictions of sulfate
production in clouds. Tellus Ser. B 42B: 272-284.
Hegg, D. A.; Hobbs, P. V.; Radke, L. F. (1984) Measurements of the scavenging of sulfate and nitrate in
clouds. Atmos. Environ. 18: 1939-1946.
Hegg, D. A.; Radke, L. F.; Hobbs, P. V. (1990) Particle production associated with marine clouds. J. Geophys.
Res. [Atmos.] 95: 13,917-13,926.
Hegg, D. A.; Radke, L. F.; Hobbs, P. V. (1991) Measurements of Aitken nuclei and cloud condensation nuclei
in the marine atmosphere and their relation to the DMS-cloud-climate hypothesis. J. Geophys. Res.
[Atmos.] 96: 18,727-18,733.
Hegg, D. A.; Yuen, P.-F.; Larson, T. V. (1992) Modeling the effects of heterogeneous cloud chemistry on the
marine particle size distribution. J. Geophys. Res. [Atmos.] 97: 12,927-12,933.
Heintzenberg, J.; Winkler, P. (1984) Elemental carbon in the urban aerosol: results of a seventeen month study
in Hamburg, FRG. Sci. Total Environ. 36: 27-38.
Heintzenberg, J.; Ogren, J. A.; Noone, K. J.; Gardneus, L. (1989) The size distribution of submicrometer
particles within and about stratocumulus cloud droplets on Mt. Areskutan, Sweden. Atmos. Res.
24: 89-101.
3-211
-------
Heisler, S. L.; Friedlander, S. K. (1977) Gas-to-particle conversion in photochemical smog - aerosol growth laws
and mechanisms for organics. Atmos. Environ. 11: 157-168.
Hering, S. V.; Friedlander, S. K. (1982) Origins of aerosol sulfur size distributions in the Los Angeles basin.
Atmos. Environ. 16: 2647-2656.
Hering, S. V.; McMurry, P. H. (1991) Optical counter response to monodisperse atmospheric aerosols. Atmos.
Environ. Part A 25: 463-468.
Hering, S. V.; Lawson, D. R.; Allegrini, I.; Febo, A.; Perrino, C.; Possanzini, M.; Sickles, J. E., II; Anlauf,
K. G.; Wiebe, A.; Appel, B. R.; John, W.; Ondo, J.; Wall, S.; Braman, R. S.; Sutton, R.; Cass,
G. R.; Solomon, P. A.; Eatough, D. J.; Eatough, N. L.; Ellis, E. C.; Grosjean, D.; Hicks, B. B.;
Womack, J. D.; Horrocks, J.; Knapp, K. T.; Ellestad, T. G.; Paur, R. J.; Mitchell, W. J.;
Pleasant, M.; Peake, E.; MacLean, A.; Pierson, W. R.; Brachaczek, W.; Schiff, H. I.; Mackay, G. I.;
Spicer, C. W.; Stedman, D. H.; Winer, A. M.; Biermann, H. W.; Tuazon, E. C. (1988) The nitric acid
Shootout: field comparison of measurement methods. Atmos. Environ. 22: 1519-1539.
Hicks, B. B. (1984) Dry deposition processes. In: Altshuller, A. P.; Linthurst, R. A., eds. Acidic deposition
phenomenon and its effects: critical assessment review papers, volume I, atmospheric sciences.
Washington, DC: U.S. Environmental Protection Agency, Office of Research and Development; pp. 7-1
to 7-70; EPA report no. EPA/600/8-83/016AF. Available from: NTIS, Springfield, VA; PB85-100030.
Hicks, B. B.; Meyers, T. P. (1989) Atmosphere-surface exchange processes. Presented at: 82nd annual meeting
of the Air & Waste Management Association; June; Anaheim, CA. Pittsburgh, PA: Air & Waste
Management Association; paper no. 89-113.4.
Hicks, B. B.; Wesely, M. L.; Lindberg, S. E.; Bromberg, S. M., eds. (1986) Proceedings of the NAPAP
workshop on dry deposition; March; Harpers Ferry, WV. Oak Ridge, TN: National Oceanic and
Atmospheric Administration.
Hicks, B. B.; Draxler, R. R.; Dodge, M.; Hales, J. M.; Albritton, D. L.; Schwartz. S. E.; Meyers, T. P.;
Fehsenfeld, F. C.; Tanner, R. L.; Vong, R. J. (1991) Atmospheric processes research and process model
development. In: Irving, P. M., ed. Acidic deposition: state of science and technology, volume I:
emissions, atmospheric processes, and deposition. Washington, DC: The U.S. National Acid Precipitation
Assessment Program. (State of science and technology report no. 2).
Hildemann, L. M. (1990) A study of the origin of atmospheric organic aerosols [Ph.D. thesis]. Pasadena, CA:
California Institute of Technology. Available from: University Microfilms, Ann Arbor, MI; order no.
AAC90-14378.
Hildemann, L. M.; Russell, A. G.; Cass, G. R. (1984) Ammonia and nitric acid concentrations in equilibrium
with atmospheric aerosols: experiment vs theory, Atmos. Environ. 18: 1737-1750.
Hildemann, L. M.; Cass, G. R.; Mazurek, M. A.; Simoneit, B. R. T. (1993) Mathematical modeling of urban
organic aerosol: properties measured by high-resolution gas chromatography. Environ. Sci. Technol.
27: 2045-2055.
Hildemann, L. M.; Klinedinst, D. B.; Klouda, G. A.; Currie, L. A.; Cass, G. R. (1994a) Sources of urban
contemporary carbon aerosol. Environ. Sci. Technol. 28: 1565-1576.
Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1994b) Seasonal trends in Los Angeles
ambient organic aerosol observed by high-resolution gas chromatography. Aerosol Sci. Technol.
20: 303-317.
3-212
-------
Hill, T. A.; Choularton, T. W.; Penkett, S. A. (1986) A model of sulphate production in a cap cloud and
subsequent turbulent deposition onto the hill surface. Atmos. Environ. 20: 1763-1771.
Hinds, W. C. (1982) Aerosol technology. New York, NY: John Wiley and Sons.
Hobbs, P. V.; Bowdle, D. A.; Radke, L. F. (1985) Particles in the lower troposphere over the high plains of the
United States. Part I: size distributions, elemental compositions and morphologies. J. Clim. Appl.
Meteorol. 24: 1344-1356.
Hoffmann, M. R.; Boyce, S. D. (1983) Catalytic autooxidation of aqueous sulfur dioxide in relationship to
atmospheric systems. Adv. Environ. Sci. Technol. 12: 147-189.
Hoffmann, M. R.; Calvert, J. G. (1985) Chemical transformation modules for Eulerian acid deposition models:
volume II, the aqueous-phase chemistry. Research Triangle Park, NC: U.S. Environmental Protection
Agency, Atmospheric Sciences Research Laboratory; EPA report no. EPA/600/3-85/036. Available from:
NTIS, Springfield, VA; PB85-198653/AS.
Hoffmann, M. R.; Edwards, J. O. (1975) Kinetics of the oxidation of sulfite by hydrogen peroxide in acidic
solution. J. Phys. Chem. 79: 2096-2098.
Hoffmann, M. R.; Jacob, D. J. (1984) Kinetics and mechanisms of the catalytic oxidation of dissolved sulfur
dioxide in aqueous solution: an application to nighttime fog water chemistry. In: Calvert, J. G., ed. S02,
NO and N02 oxidation mechanisms: atmospheric considerations. Boston, MA: Butterworth Publishers;
pp. 101-172. (Teasley, J. I., ed. Acid precipitation series: v. 3).
Hoffmann, H. E.; Kuehnemann, W. (1979) Comparison of the results of two measuring methods determining the
horizontal standard visibility with the visual visibility range. Atmos. Environ. 13: 1629-1634.
Holsen, T. M.; Noll, K. E.; Fang, G.-C.; Lee, W.-J.; Lin, J.-M.; Keeler, G. J. (1993) Dry deposition and
particle size distributions measured during the Lake Michigan Urban Air Toxics Study. Environ. Sci.
Technol. 27: 1327-1333.
Hong, M.-S.; Carmichael, G. R. (1986a) An investigation of sulfate production in an orographic storm using a
detailed transport/chemistry model coupled with a detailed cloud scavenging model. Atmos. Environ.
20: 1989-1997.
Hong, M.-S.; Carmichael, G. R. (1986b) Examination of a subgrid-scale parameterization for the transport of
pollutants in a nonprecipitating cumulus cloud ensemble. Atmos. Environ. 20: 2205-2217.
Hoppel, W. A. (1988) The role of non-precipitating cloud cycles and gas-to-particle conversion in the
maintainence of the submicron aerosol size distribution over the tropical oceans. In: Hobbs, P. V.;
McCormick, M. P., eds. Aerosols and climate. Hampton, VA: A. Deepak Publishers; pp. 9-19.
Hoppel, W. A.; Frick, G. M. (1990) Submicron aerosol size distributions measured over the tropical and South
Pacific. Atmos. Environ. Part A 24: 645-659.
Hoppel, W. A.; Frick, G. M.; Larson, R. E. (1986) Effect of nonprecipitating clouds on the aerosol size
distribution in the marine boundary layer. Geophys. Res. Lett. 13: 125-128.
Hoppel, W. A.; Fitzgerald, J. W.; Frick, G. M.; Larson, R. E.;, et al. (1990) Aerosol size distributions and
optical properties found in the marine boundary layer over the Atlantic Ocean. J. Geophys. Res. [Atmos.]
95: 3659-3686.
3-213
-------
Hoppel, W. A.; Frick, G. M.; Fitzgerald, J.; Larson, R. E. (1994) Marine boundary layer measurements of new
particle formation and the effects nonprecipitating clouds have on aerosol size distribution. J. Geophys.
Res. [Atmos.] 99: 14,443-14,459.
Horvath, H.; Noll, K. E. (1969) The relationship between atmospheric light scattering coefficient and visibility.
Atmos. Environ. 3: 543-550.
Hosker, R. P., Jr.; Lindberg, S. E. (1982) Review: atmospheric deposition and plant assimilation of gases and
particles. Atmos. Environ. 16: 889-910.
Hov, O.; Isaksen, I. S. A. (1981) Generation of secondary pollutants in a power plant plume: a model study.
Atmos. Environ. 15: 2367-2376.
Huang, P.-F.; Turpin, B. J.; Pipho, M. J.; Kittelson, D. B.; McMurry, P. H. (1994) Effects of water
condensation and evaporation on diesel chain-agglomerate morphology. J. Aerosol Sci. 25: 447-459.
Hubbe, J. M. (1989) Assessing procedures for estimating deposition rates for pollutants of interest. Sacramento,
CA: California Air Resources Board, San Joaquin Valley Air Pollution Study Agency; San Joaquin
Valley Air Quality Study technical support study no. 8.
Hudischewskyj, A. B.; Seigneur, C. (1989) Mathematical modeling of the chemistry and physics of aerosols in
plumes. Environ. Sci. Technol. 23: 413-421.
Huntzicker, J. J.; Hoffman, R. S.; Ling, C.-S. (1978) Continuous measurement and speciation of
sulfur-containing aerosols by flame photometry. Atmos. Environ. 12: 83-88.
Huntzicker, J. J.; Gary, R. A.; Ling, C.-S. (1980) Neutralization of sulfuric acid aerosol by ammonia. Environ.
Sci. Technol. 14: 819-824.
Huntzicker, J. J.; Johnson, R. L.; Shah, J. J.; Gary, R. A. (1982) Analysis of organic and elemental carbon in
ambient aerosols by a thermal-optical method. In: Wolff, G. T.; Klimisch, R. L., eds. Paniculate
carbon - atmospheric life cycle: proceedings of an international symposium; October 1980; Warren, MI.
New York, NY: Plenum Press; pp. 79-88.
Husain, L.; Dutkiewicz, V. A.; Hussain, M. M.; Khwaja, H. A.; Burkhard, E. G.; Mehmood, G.; Parekh,
P. P.; Canelli, E. (1991) A study of heterogeneous oxidation of SO2 in summer clouds. J. Geophys. Res.
[Atmos.] 96: 18,789-18,805.
Husar, R. B.; Gillani, N. V.; Husar, J. D. (1976) Paniculate sulfur formation in power plant: urban and regional
plumes. Presented at: Symposium on aerosol science and technology at the 82nd national meeting of the
AIChE; August-September; Atlantic City, MD.
Husar, R. B.; Patterson, D. E.; Husar, J. D.; Gillani, N. V.; Wilson, W. E., Jr. (1978) Sulfur budget of a
power plant plume. In: Husar, R. B.; Lodge, J. P., Jr.; Moore, D. J., eds. Sulfur in the atmosphere:
proceedings of the international symposium; September 1977; Dubrovnik, Yugoslavia. Atmos. Environ.
12: 549-568.
Husar, R. B.; Holloway, J. M.; Patterson, D. E.; Wilson, W. E. (1981) Spatial and temporal pattern of eastern
U.S. haziness: a summary. Atmos. Environ. 15: 1919-1928.
Huss, A., Jr.; Lim, P. K.; Eckert, C. A. (1982a) Oxidation of aqueous sulfur dioxide. 1. Homogeneous
manganese(II) and iron(II) catalysis at low pH. J. Phys. Chem. 86: 4224-4228.
3-214
-------
Huss, A., Jr.; Lim, P. K.; Eckert, C. A. (1982b) Oxidation of aqueous sulfur dioxide. 2. High-pressure studies
and proposed reaction mechanisms. J. Phys. Chem. 86: 4229-4233.
Ibusuki, T.; Takeuchi, K. (1987) Sulfur dioxide oxidation by oxygen catalyzed by mixtures of manganese(II) and
iron(III) in aqueous solutions at environmental reaction conditions. Atmos. Environ. 21: 1555-1560.
Irwin, J. S. (1983) Estimating plume dispersion—a comparison of several sigma schemes. J. Clim. Appl.
Meteorol. 22: 92-114.
Isaksen, I. S. A.; Hov, O.; Hesstvedt, E. (1978) Ozone generation over rural areas. Environ. Sci. Technol.
12: 1279-1284.
Izumi, K.; Fukuyama, T. (1990) Photochemical aerosol formation from aromatic hydrocarbons in the presence of
NOX. Atmos. Environ. Part A 24: 1433-1441.
Izumi, K.; Murano, K.; Mizuochi, M.; Fukuyama, T. (1988) Aerosol formation by the photooxidation of
cyclohexene in the presence of nitrogen oxides. Environ. Sci. Technol. 22: 1207-1215.
Jackson, M. L.; Gillette, D. A.; Danielsen, E. F.; Blifford, I. H.; Bryson, R. A.; Syers, J. K. (1973) Global
dustfall during the quaternary as related to environments. Soil Sci. 116: 135-145.
Jacob, D. J. (1986) Chemistry of OH in remote clouds and its role in the production of formic acid and
peroxymonosulfate. J. Geophys. Res. [Atmos.] 91: 9807-9826.
Jacob, D. J.; Hoffmann, M. R. (1983) A dynamic model for the production of H+, NO3", and SO42" in urban
fog. J. Geophys. Res. C: Oceans Atmos. 88: 6611-6621.
Jacob, D. J.; Waldman, J. M.; Munger, J. W.; Hoffmann, M. R. (1985) Chemical composition of fogwater
collected along the California coast. Environ. Sci. Technol. 19: 730-736.
Jacob, D. J.; Munger, J. W.; Waldman, J. M.; Hoffmann, M. R. (1986a) The H2SO4-HNO3-NH3 system at
high humidities and in fogs: 1. spatial and temporal patterns in the San Joaquin Valley of California.
J. Geophys. Res. [Atmos.] 91: 1073-1088.
Jacob, D. J.; Waldman, J. M.; Munger, J. W.; Hoffmann, M. R. (1986b) The H2S04-HNO3-NH3 system at
high humidities and in fogs: 2. comparison of field data with thermodynamic calculations. J. Geophys.
Res. [Atmos.] 91: 1089-1096.
Jaffrezo, J.-L.; Colin, J.-L. (1988) Rain-aerosol coupling in urban area: scavenging ratio measurement and
identification of some transfer processes. Atmos. Environ. 22: 929-935.
Japar, S. M.; Brachaczek, W. W.; Gorse, R. A., Jr.; Norbeck, J. M.; Pierson, W. R. (1986) The contribution
of elemental carbon to the optical properties of rural atmospheric aerosols. Atmos. Environ.
20: 1281-1289.
Jassim, J. A.; Lu, H. P.; Chughtai, A. R.; Smith, D. M. (1986) The origin of infrared absorption bands of soot
in the region 750 to 900 cm'1. Appl. Spectrosc. 40: 113-116.
John, W.; Sethi, V. (1993) Threshold for resuspension by particle impaction. Aerosol Sci. Technol. 19: 69-79.
John, W.; Wang, H.-C. (1991) Laboratory testing method for PM-10 samplers: lowered effectiveness from
particle loading. Aerosol Sci. Technol. 14: 93-101.
3-215
-------
John, W.; Wall, S. M.; Ondo, J. L.; Winklmayr, W. (1990) Modes in the size distributions of atmospheric
inorganic aerosol. Atmos. Environ. Part A 24: 2349-2359.
John, W.; Winklmayr, W.; Wang, H.-C. (1991) Particle deagglomeration and reentrainment in a PM-10 sampler.
Aerosol Sci. Technol. 14: 165-176.
Johnson, R. L.; Shah, J. J.; Gary, R. A.; Huntzicker, J. J. (1981) An automated thermal-optical method for the
analysis of carbonaceous aerosol. In: Macias, E. S.; Hopke, P. K., eds. Atmospheric aerosol: source/air
quality relationships; based on a symposium jointly sponsored by the Divisions of Nuclear Chemistry and
Technology at the 180th national meeting of the American Chemical Society; August 1980; Las Vegas,
NV. Washington, DC: American Chemical Society; pp. 223-233. (Comstock, M. J., ed. ACS
symposium series: 167).
Johnson, C. A.; Sigg, L.; Zobrist, J. (1987) Case studies on the chemical composition of fogwater: the influence
of local gaseous emissions. Atmos. Environ. 21: 2365-2374.
Joos, F.; Baltensperger, U. (1991) A field study on chemistry, S(IV) oxidation rates and vertical transport during
fog conditions. Atmos. Environ. Part A 25: 217-230.
Junge, C. E. (1963) Air chemistry and radioactivity. New York, NY: Academic Press. (Van Mieghem, J.;
Hales, A. L., eds. International geophysics series: v. 4).
Junge, C. E. (1977) Basic considerations about trace constituents in the atmosphere as related to the fate of global
pollutants. In: Suffet, I. H., ed. Fate of pollutants in the air and water environments: part I, mechanism
of interaction between environments and mathematical modeling and the physical fate of pollutants,
papers from the 165th national American Chemical Society meeting; April 1975; Philadelphia, PA. New
York, NY: John Wiley & Sons; pp. 7-25. (Advances in environmental science and technology: v. 8).
Junge, C.; McLaren, E. (1971) Relationship of cloud nuclei spectra to aerosol size distribution and composition.
J. Atmos. Sci. 28: 382-390.
Kadowaki, S. (1994) Characterization of carbonaceous aerosols in the Nagoya urban area. 2. Behavior and origin
of paniculate «-alkanes. Environ. Sci. Technol. 28: 129-135.
Kahl, J. D.; Samson, P. J. (1986) Uncertainty in trajectory calculations due to low resolution meteorological
data. J. Clim. Appl. Meteorol. 25: 1816-1831.
Kahl, J. D.; Samson, P. J. (1988) Trajectory sensitivity to rawinsonde data resolution. Atmos. Environ.
22: 1291-1299.
Kahl, J. D.; Schnell, R. C.; Sheridan, P. J.; Zak, B. D.; Church, H. W.; Mason, A. S.; Heffter, J. L.; Harris,
J. M. (1991) Predicting atmospheric debris transport in real-time using a trajectory forecast model.
Atmos. Environ. Part A 25: 1705-1713.
Kamens, R. M.; Jeffries, H. E.; Gery, M. W.; Wiener, R. W.; Sexton, K. G.; Howe, G. B. (1981) The impact
of a-pinene on urban smog formation: an outdoor smog chamber study. Atmos. Environ. 15: 969-981.
Kamens, R. M.; Gery, M. W.; Jeffries, H. E.; Jackson, M.; Cole, E. I. (1982) Ozone-isoprene reactions:
product formation and aerosol potential. Int. J. Chem. Kinet. 14: 955-975.
Kamens, R.; Odum, J.; Fan, Z.-H. (1995) Some observations on times to equilibrium for semivolatile polycyclic
aromatic hydrocarbons. Environ. Sci. Technol. 29: 43-50.
3-216
-------
Kaplan, I. R.; Gordon, R. J. (1994) Non-fossil-fuel fine-particle organic carbon aerosols in Southern California
determined during the Los Angeles Aerosol Characterization and Source Apportionment Study. Aerosol
Sci. Technol. 21: 343-359.
Karamchandani, P.; Venkatram, A. (1992) The role of non-precipitating clouds in producing ambient sulfate
during summer: results from simulations with the Acid Deposition and Oxidant Model (ADOM) Atmos.
Environ. Part A 26: 1041-1052.
Katrinak, K. A.; Re/, P.; Buseck, P. R. (1992) Structural variations in individual carbonaceous particles from an
urban aerosol. Environ. Sci. Technol. 26: 1967-1976.
Katrinak, K. A.; Rez, P.; Perkes, P. R.; Buseck, P. R. (1993) Fractal geometry of carbonaceous aggregates
from an urban aerosol. Environ. Sci. Technol. 27: 539-547.
Kawamura, K.; Ng, L.-L.; Kaplan, I. R. (1985) Determination of organic acids (CrCJO) in the atmosphere,
motor exhausts, and engine oils. Environ. Sci. Technol. 19: 1082-1086.
Keeler, G. J.; Brachaczek, W. W.; Gorse, R. A., Jr.; Japar, S. M.; Pierson, W. R. (1988) Effect of ambient
humidity on dichotomous sampler coarse/fine ratios. Atmos. Environ. 22: 1715-1720.
Keeler, G. J.; Japar, S. M.; Brachaczek, W. W.; Gorse, R. A., Jr.; Norbeck, J. M.; Pierson, W. R. (1990) The
sources of aerosol elemental carbon at Allegheny Mountain. Atmos. Environ. Part A 24: 2795-2805.
Kelly, N. A. (1987) The photochemical formation and fate of nitric acid in the metropolitan Detroit area:
ambient, captive-air irradiation and modeling results. Atmos. Environ. 21: 2163-2177.
Kelly, T. J.; Schwartz, S. E.; Daum, P. H. (1989) Detectability of acid producing reactions in natural clouds.
Atmos. Environ. 23: 569-583.
Kerminen, V. M.; Wexler, A. S. (1994a) Particle formation due to SO2 oxidation and high relative humidity in
the remote marine boundary layer. J. Geophys. Res. [Atmos.] 99: 25607-25625.
Kerminen, V.-M.; Wexler, A. S. (1994b) Post-fog nucleation of H2SO4-H2O particles in smog. Atmos. Environ.
28: 2399-2406.
Khlystov, A.; ten Brink, H. M.; Wyers, G. P. (1993) Hygroscopic growth rates of aerosols at high relative
humidity. Petten, The Netherlands: Netherlands Energy Research Foundation ECN; report no.
ECN-C-93-011.
Kim, Y. J. (1995) Response of the Active Scattering Aerosol Spectrometer Probe (ASASP-100X) to particles of
different chemical composition. Aerosol Sci. Technol. 22: 33-42.
Kim, D.; Hopke, P. K. (1988) Classification of individual particles based on computer-controlled scanning
electron microscopy data. Aerosol Sci. Technol. 9: 133-151.
Kim, Y. P.; Seinfeld, J. H. (1995) Atmospheric gas-aerosol equilibrium: III. Thermodynamics of crustal
elements Ca2+, K+, and Mg2+. Aerosol Sci. Technol. 22: 93-110.
Kim, M. G.; Yagawa, K.; Inoue, H.; Lee, Y. K.; Shirai, T. (1990) Measurement of tire tread in urban air by
pyrolysis-gas chromatography with flame photometric detection. Atmos. Environ. Part A 24: 1417-1422.
Kim, Y. P.; Seinfeld, J. H.; Saxena, P. (1993a) Atmospheric gas-aerosol equilibrium: I. thermodynamic model.
Aerosol Sci. Technol. 19: 157-181.
3-217
-------
Kim, Y. P.; Seinfeld, J. H.; Saxena, P. (1993b) Atmospheric gas-aerosol equilibrium: II. analysis of common
approximations and activity coefficient calculation methods. Aerosol Sci. Technol. 19: 182-198.
Kim, Y. J.;.Boatman, J. P.; Gunter, R. L.; Wellman, D. L.; Wilkison, S. W. (1993c) Vertical distribution of
atmospheric aerosol size distribution over south-central New Mexico. Atmos. Environ. Part A
27: 1351-1362.
Kim, Y. P.; Pun, B. K.-L.; Chan, C. K.; Flagan, R. C.; Seinfeld, J. H. (1994) Determination of water activity
in ammonium sulfate and sulfuric acid mixtures using levitated single particles. Aerosol Sci. Technol.
20: 275-284.
Kitsa, V.; Lioy, P. J. (1992) Near field dispersion of mechanically resuspended dust from an unpaved road.
Transactions AWMA 1: 199-210.
Kitsa, V.; Lioy, P. J.; Chow, J. C.; Watson, J. G.; Shupack, S.; Howell, T.; Sanders, P. (1992) Particle-size
distribution of chromium: total and hexavalent chromium in inspirable, thoracic, and respirable soil
particles from contaminated sites in New Jersey. Aerosol Sci. Technol. 17: 213-229.
Klee, A. J. (1984) Source control - municipal solid waste incinerators. In: Calvert, S.; Englund, H. M., eds.
Handbook of air pollution technology. New York, NY: John Wiley & Sons; pp. 513-550.
Klouda, G. A.; Currie, L. A.; Verkouteren, R. M.; Einfeld, W.; Zak, B. D. (1988) Advances in
microradiocarbon dating and the direct tracing of environmental carbon. J. Radioanal. Nucl. Chem.
123: 191-197.
Koenig, L. R.; Murray, F. W. (1976) Ice-bearing cumulus cloud evolution: numerical simulation and general
comparison against observations. J. Appl. Meteorol. 15: 747-762.
Kohler, H. (1936) The nucleus in and the growth of hygroscopic droplets. Trans. Faraday Soc. 32: 1152-1161.
Kolb, C. E.; Jayne, J. T.; Worsnop, D. R.; Molina, M. J.; Meads, R. F.; Viggiano, A. A. (1994) Gas phase
reaction of sulfur trioxide with water vapor. J. Am. Chem. Soc. 116: 10314-10315.
Koutrakis, P.; Wolfson, J. M.; Slater, J. L.; Brauer, M.; Spengler, J. D.; Stevens, R. K.; Stone, C. L. (1988a)
Evaluation of an annular denuder/filter pack system to collect acidic aerosols and gases. Environ. Sci.
Technol. 22: 1463-1468.
Koutrakis, P.; Wolfson, J. M.; Spengler, J. D. (1988b) An improved method for measuring aerosol strong
acidity: results from a nine-month study in St. Louis, Missouri and Kingston, Tennessee. Atmos.
Environ. 22: 157-162.
Koutrakis, P.; Wolfson, J. M.; Spengler, J. D.; Stern, B.; Franklin, C. A. (1989) Equilibrium size of
atmospheric aerosol sulfates as a function of the relative humidity. J. Geophys. Res. [Atmos.]
94: 6442-6448.
Koutrakis, P.; Thompson, K. M.; Wolfson, J. M.; Spengler, J. D.; Keeler, G. J.; Slater, J. L. (1992)
Determination of aerosol strong acidity losses due to interactions of collected particles: results from
laboratory and field studies. Atmos. Environ. Part A 26: 987-995.
Krieger, M. S.; Kites, R. A. (1992) Diffusion denuder for the collection of semivolatile organic compounds.
Environ. Sci. Technol. 26: 1551-1555.
Krieger, M. S.; Kites, R. A. (1994) Measurement of polychlorinated biphenyls and polycyclic aromatic
hydrocarbons in air with a diffusion denuder. Environ. Sci. Technol. 28: 1129-1133.
3-218
-------
Kunen, S. M.; Lazrus, A. L.; Kok, G. L.; Heikes, B. G. (1983) Aqueous oxidation of SO; by hydrogen
peroxide. J. Geophys. Res. C: Oceans Atmos. 88: 3671-3674.
Kuo, Y.-H.; Skumanich, M.; Haagenson, P. L.; Chang, J. S. (1985) The accuracy of trajectory models as
revealed by the observing system simulation experiments. Mon. Weather Rev. 113: 1852-1867.
Lamb, B.; Guenther, A.; Gay, D.; Westberg, H. (1987) A national inventory of biogenic hydrocarbon emissions.
Atmos. Environ. 21: 1695-1705.
Lane, D. A.; Johnson, N. D.; Barton, S. C.; Thomas, G. H. S.; Schroeder, W. H. (1988) Development and
evaluation of a novel gas and particle sampler for semivolatile chlorinated organic compounds in ambient
air. Environ. Sci. Technol. 22: 941-947.
Langner, J.; Rodhe, H. (1991) A global three-dimensional model of the tropospheric sulfur cycle. J. Atmos.
Chem. 13: 225-263.
Larson, S. M.; Cass, G. R. (1989) Characteristics of summer midday low-visibility events in the Los Angeles
area. Environ. Sci. Technol. 23: 281-289.
Larson, S. M.; Cass, G. R.; Gray, H. A. (1989) Atmospheric carbon particles and the Los Angeles visibility
problem. Aerosol Sci. Technol. 10: 118-130.
Lawrence, J. E.; Koutrakis, P. (1994) Measurement of atmospheric formic and acetic acids: methods evaluation
and results from field studies. Environ. Sci. Technol. 28: 957-964.
Lawson, D. R. (1990) The Southern California Air Quality Study. J. Air Waste Manage. Assoc. 40: 156-165.
Lazrus, A. L.; Haagenson, P. L.; Kok, G. L.; Huebert, B. J.; Kreitzberg, C. W.; Likens, G. E.; Mohnen,
V. A.; Wilson, W. E.; Winchester, J. W. (1983) Acidity in air and water in a case of warm frontal
precipitation. Atmos. Environ. 17: 581-591.
Leaitch, W. R.; Strapp, J. W.; Wiebe, H. A.; Isaac, G. A. (1983) Measurements of scavenging and
transformation of aerosol inside cumulus. In: Pruppacher, H. R.; Semonin, R. G.; Slinn, W. G. N., eds.
Precipitation scavenging, dry deposition, and resuspension: proceedings of the fourth international
conference, v. 1: precipitation scavenging; November-December 1982; Santa Monica, CA. New York,
NY: Elsevier; pp. 53-69.
Leaitch, W. R.; Strapp, J. W.; Wiebe, H. A.; Anlauf, K. G.; Isaac, G. A. (1986a) Chemical and microphysical
studies of nonprecipitating summer cloud in Ontario, Canada. J. Geophys. Res. [Atmos.]
91: 11,821-11,831.
Leaitch, W. R.; Strapp, J. W.; Isaac, G. A.; Hudson, J. G. (1986b) Cloud droplet nucleation and cloud
scavenging of aerosol sulphate in polluted atmospheres. Tellus Ser. B 38B: 328-344.
Leaitch, W. R.; Bottenheim, J. W.; Strapp, J. W. (1988) Possible contribution of N2O5 scavenging to HNO3
observed in winter stratiform cloud. J. Geophys. Res. [Atmos.] 93: 12,569-12,584.
Lee, Y.-N.; Schwartz, S. E. (1983) Kinetics of oxidation of aqueous sulfur(IV) by nitrogen dioxide.
In: Pruppacher, H. R.; Semonin, R. G.; Slinn, W. G. N., eds. Precipitation scavenging, dry deposition,
and resuspension: proceedings of the fourth international conference, v. 1: precipitation scavenging;
November-December 1982; Santa Monica, CA. New York, NY: Elsevier; pp. 453-470.
Leone, J. A.; Flagan, R. C.; Grosjean, D.; Seinfeld, J. H. (1985) An outdoor smog chamber and modeling study
of toluene-NOx photooxidation. Int. J. Chem. Kinet. 17: 177-216.
3-219
-------
Lewis, R. S.; Been, W. M. (1994) Kinetics of the reaction of nitric oxide with oxygen in aqueous solutions.
Chem. Res. Toxicol. 7: 568-574.
Lewis, C. W.; Baumgardner, R. E.; Stevens, R. K.; Claxton, L. D.; Lewtas, J. (1988) Contribution of
woodsmoke and motor vehicle emissions to ambient aerosol mutagenicity. Environ. Sci. Technol.
22: 968-971.
Li, W.; Montassier, N.; Hopke, P. K. (1992) A system to measure the hygroscopicity of aerosol particles.
Aerosol Sci. Technol. 17: 25-35.
Li, S.-M.; Anlauf, K. G.; Wiebe, H. A. (1993) Heterogeneous nighttime production and deposition of particle
nitrate at a rural site in North America during summer 1988. J. Geophys. Res. [Atmos.] 98: 5139-5157.
Liang, C. S. K.; Waldman, J. M. (1992) Indoor exposures to acidic aerosols at child and elderly care facilities.
Indoor Air 2: 196-207.
Liebsch, E. J.; de Pena, R. G. (1982) Sulfate aerosol production in coal-fired power plant plumes. Atmos.
Environ. 16: 1323-1331.
Ligocki, M. P.; Pankow, J. F. (1989) Measurements of the gas/particle distributions of atmospheric organic
compounds. Environ. Sci. Technol. 23: 75-83.
Ligocki, M. P.; Salmon, L. G.; Fall, T.; Jones, M. C.; Nazaroff, W. W.; Cass, G. R. (1993) Characteristics of
airborne particles inside southern California museums. Atmos. Environ. Part A 27: 697-711.
Lin, X.; Chameides, W. L. (1991) Model studies of the impact of chemical inhomogeneity on SC«2 oxidation in
warm stratiform clouds. J. Atmos. Chem. 13: 109-129.
Lin, J.-M.; Fang, G.-C.; Holsen, T. M.; Noll, K. E. (1993) A comparison of dry deposition modeled from size
distribution data and measured with a smooth surface for total particle mass, lead and calcium in
Chicago. Atmos. Environ. Part A 27: 1131-1138.
Lin, J. J.; Noll, K. E.; Holsen, T. M. (1994) Dry deposition velocities as a function of particle size in the
ambient atmosphere. Aerosol Sci. Technol. 20: 239-252.
Lind, J. A.; Lazrus, A. L. (1983) Aqueous phase oxidation of sulfur IV by some organic peroxides [abstract].
EOS Trans. 64: 670.
Lindberg, S. E. (1982) Factors influencing trace metal, sulfate and hydrogen ion concentrations in rain. Atmos.
Environ. 16: 1701-1709.
Linton, R. W.; Loh, A.; Natusch, D. F. S.; Evans, C. A., Jr.; Williams, P. (1976) Surface predominance of
trace elements in airborne particles. Science (Washington, DC) 191: 852-854.
Lioy, P. J.; Daisey, J. M. (1986) Airborne toxic elements and organic substances. Environ. Sci. Technol.
20: 8-14.
Lioy, P. J.; Watson, J. G., Jr. ; Spengler, J. D. (1980) APCA specialty conference workshop on baseline data
for inhalable paniculate matter. J. Air Pollut. Control Assoc. 30: 1126-1130.
Lippmann, M. (1980) Size distributions in urban aerosols. In: Kneip, T. J.; Lioy, P. J., eds. Aerosols:
anthropogenic and natural, sources and transport. Ann. N. Y. Acad. Sci. 338: 1-12.
3-220
-------
Liu, P. S. K.; Leaitch, W. R.; Strapp, J. W.; Wasey, M. A. (1992) Response of particle measuring systems
airborne to ASASP and PCASP to NaCl and latex particles. Aerosol Sci. Technol. 16: 83-95.
Liu, P. S. K.; Leaitch, W. R.; Macdonald, A. M.; Isaac, G. A.; Strapp, J. W.; Wiebe, H. A. (1993) Sulphate
production in summer cloud over Ontario, Canada. Tellus Ser. B 45B: 368-389.
Lowenthal, D. H.; Rogers, C. F.; Saxena, P.; Watson, J. G.; Chow, J. C. (1995) Sensitivity of estimated light
extinction coefficients to model assumptions and measurement errors. Atmos. Environ. 29: 751-766.
Lundgren, D. A.; Burton, R. M. (1995) Effect of particle size distribution on the cut point between fine and
coarse ambient mass fractions. In: Phalen, R. F.; Bates, D. V., eds. Proceedings of the colloquium on
paniculate air pollution and human mortality and morbidity; January 1994; Irvine, CA. Inhalation
Toxicol. 7: 131-148.
Lundgren, D. A.; Hausknecht, B. J. (1982a) Ambient aerosol mass distribution of 1 to 100 pm particles in five
cities. Presented at: 75th annual meeting of the Air Pollution Control Association; June; New Orleans,
LA. Pittsburgh, PA: Air Pollution Control Association; paper no. 82-45.4.
Lundgren, D. A.; Hausknecht, B. J. (1982b) Ambient aerosol size distribution determination using a mobile wide
range aerosol classifier. Research Triangle Park, NC: U.S. Environmental Protection Agency,
Environmental Monitoring Systems Laboratory; EPA contract no. CR-808606-01-1.
Lundgren, D. A.; Hausknecht, B. J.; Burton, R. M. (1984) Large particle size distribution in five U.S. cities and
the effect on a new ambient paniculate matter standard (PM10). Aerosol Sci. Technol. 7: 467-473.
Lusis, M. A.; Anlauf, K. G.; Barrie, L. A.; Wiebe, H. A. (1978) Plume chemistry studies at a northern Alberta
power plant. Atmos. Environ. 12: 2429-2437.
Maahs, H. G. (1983) Kinetics and mechanism of the oxidation of S(IV) by ozone in aqueous solution with
particular reference to SO2 conversion in nonurban tropospheric clouds. J. Geophys. Res. C:
Oceans Atmos. 88: 10,721-10,732.
Macias, E. S.; Zwicker, J. O.; White, W. H. (1981) Regional haze case studies in the southwestern U.S.—
II. source contributions. In: White, W. H.; Moore, D. J.; Lodge, J. P., Jr., eds. Plumes and visibility:
measurements and model components: proceedings of the symposium; November 1980; Grand Canyon
National Park, AZ. Atmos. Environ. 15: 1987-1997.
Makhonko, K. P. (1986) Wind dust lift from the grass surface. Meteorol. Gidrol. 10: 61-65.
Malm, W. C.; Gebhart, K. A.; Molenar, J.; Cahill, T.; Eldred, R.; Huffman, D. (1994) Examining the
relationship between atmospheric aerosols and light extinction at Mount Rainier and North Cascades
National Parks. Atmos. Environ. 28: 347-360.
Mamane, Y.; Stevens, R. K.; Dzubay, T. G. (1990) On the sources of fine and coarse carbon particles in the
Great Lakes. J. Aerosol Sci. 21(suppl. 1): S353-S356.
Mansoori, B. A.; Johnston, M. V.; Wexler, A. S. (1994) Quantitation of ionic species in single microdroplets by
on-line laser desorption/ionization. Anal. Chem. 66: 3681-3687.
Martin, L. R. (1984) Kinetic studies of sulfite oxidation in aqueous solution. In: Calvert, J. G., ed. SO2, NO and
NO2 oxidation mechanisms: atmospheric considerations. Boston, MA: Butterworth Publishers;
pp. 63-100. (Teasley, J. I., ed. Acid precipitation series: v. 3).
3-221
-------
Martin, L. R. (1994) Aqueous sulfur(IV) oxidation revisited. In: Nriagu, J. O.; Simmons, M. S., eds.
Environmental oxidants. New York, NY: John Wiley & Sons, Inc.; pp. 221-268. (Nriagu, J. O., ed.
Advances in environmental science and technology: v. 28).
Martin, L. R.; Damschen, D. E. (1981) Aqueous oxidation of sulfur dioxide by hydrogen peroxide at low pH.
Atmos. Environ. 15: 1615-1621.
Martin, L. R.; Hill, M. W. (1987a) The iron catalyzed oxidation of sulfur: reconciliation of the literature rates.
Atmos. Environ. 21: 1487-1490.
Martin, L. R.; Hill, M. W. (1987b) The effect of ionic strength on the manganese catalyzed oxidation of
sulfur(IV). Atmos. Environ. 21: 2267-2270.
Martin, L. R.; Hill, M. W.; Tai, A. F.; Good, T. W. (1991) The iron catalyzed oxidation of sulfur(IV) in
aqueous solution: differing effects of organics at high and low pH. J. Geophys. Res. f Atmos.]
96: 3085-3097.
Martonen, T. B. (1993) Mathematical model for the selective deposition of inhaled Pharmaceuticals. J. Pharm.
Sci. 82: 1191-1199.
Mason, A. S.; Gifford, F. A. (1992) Atmospheric tracer dispersion over a 24-h time span. Atmos. Environ.
Part A 26: 3203-3205.
Mazurek, M. A.; Simoneit, B. R. T. (1984) Characterization of biogenic and petroleum-derived organic matter
in aerosols over remote, rural and urban areas. In: Keith, L. H., ed. Identification and analysis of
organic pollutants in air: [papers from a symposium at the 184th national American Chemical Society
meeting]; September 1982; Kansas City, MO. Woburn, MA: Butterworth Publishers; pp. 353-370.
Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1989) Interpretation of high-resolution gas chromatography /
mass spectrometry data aquired from atmospheric organic aerosol samples. Aerosol Sci. Technol.
10: 408-420.
Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1991) Biological input to visibility-reducing aerosol particles
in the remote arid southwestern United States. Environ. Sci. Technol. 25: 684-694.
McArdle, J. V.; Hoffmann, M. R. (1983) Kinetics and mechanism of the oxidation of aquated sulfur dioxide by
hydrogen peroxide at low pH. J. Phys. Chem. 87: 5425-5429.
McHenry, J. N.; Dennis, R. L. (1991) Partitioning of the sulfate budget into gas- and aqueous-phase components
in the regional acid deposition model (RADM). In: Proceedings of the 7th joint AMS-AWMA
conference: applications of air pollution meteorology; New Orleans, LA; pp. 143-147.
McHenry, J. N.; Dennis, R. L. (1994) The relative importance of oxidation pathways and clouds to atmospheric
ambient sulfate production as predicted by the Regional Acid Deposition Model. J. Appl. Meteorol.
33: 890-905.
McMahon, T. A.; Denison, P. J. (1979) Empirical atmospheric deposition parameters—a survey. Atmos.
Environ. 13: 571-585.
McMurry, P. H.; Friedlander, S. K. (1979) New particle formation in the presence of an aerosol. Atmos.
Environ. 13: 1635-1651.
McMurry, P. H.; Grosjean, D. (1985) Photochemical formation of organic aerosols: growth laws and
mechanisms. Atmos. Environ. 19: 1445-1451.
3-222
-------
McMurry, P. H.; Stolzenburg, M. R. (1989) On the sensitivity of particle size to relative humidity for Los
Angeles aerosols. Atmos. Environ. 23: 497-507.
McMurry, P. H.; Wilson, J. C. (1982) Growth laws for the formation of secondary ambient aerosols:
implications for chemical conversion mechanisms. Atmos. Environ. 16: 121-134.
McMurry, P. H.; Wilson, J. C. (1983) Droplet phase (heterogeneous) and gas phase (homogeneous)
contributions to secondary ambient aerosol formation as functions of relative humidity. J. Geophys. Res.
88: 5101-5108.
McMurry, P. H.; Zhang, X. Q. (1989) Size distributions of ambient organic and elemental carbon. Aerosol Sci.
Technol. 10: 430-437.
McMurry, P. H.; Rader, D. J.; Stith, J. L. (1981) Studies of aerosol formation in power plant plumes—
I. growth laws for secondary aerosols in power plant plumes: implications for chemical conversion
mechanisms. In: White, W. H.; Moore, D. J.; Lodge, J. P., Jr., eds. Plumes and visibility:
measurements and model components: proceedings of the symposium; November 1980; Grand Canyon
National Park, AZ. Atmos. Environ. 15: 2315-2327.
McMurry, P. H.; Zhang, X.; Lee, C.-T. (1996) Issues in aerosol measurement. J. Geophys. Res. [Atmos.]: in
press.
McNider, R. T.; Moran, M. D.; Pielke, R. A. (1988) Influence of diurnal and inertial boundary-layer
oscillations on long-range dispersion. Atmos. Environ. 22: 2445-2462.
Meagher, J. F.; Stockburger, L.; Bailey, E. M.; Huff, O. (1978) The oxidation of sulfur dioxide to sulfate
aerosols in the plume of a coal-fired power plant. Atmos. Environ. 12: 2197-2203.
Meagher, J. F.; Stockburger, L., Ill; Bonanno, R. J.; Bailey, E. M.; Luria, M. (1981) Atmospheric oxidation of
flue gases from coal-fired power plants—a comparison between conventional and scrubbed plumes.
Atmos. Environ. 15: 749-762.
Meagher, J. F.; Olszyna, K. J.; Weatherford, F. P.; Mohnen, V. A. (1990) The availability of H2O2 and 03 for
aqueous phase oxidation of S02. The question of linearity. Atmos. Environ. Part A 24: 1825-1829.
Meng, Z.; Seinfeld, J. H. (1994) On the source of the submicrometer droplet mode of urban and regional
aerosols. Aerosol Sci. Technol. 20: 253-265.
Meng, Z.; Seinfeld, J. H.; Saxena, P.; Kim, Y. P. (1995) Contribution of water to paniculate mass in the South
Coast Air Basin. Aerosol Sci. Technol. 22: 111-123.
Michaud, D.; Baril, M.; Perrault, G. (1993) Characterization of airborne dust from cast iron foundries by
physico-chemical methods and multivariate statistical analyses. Air Waste 43: 729-735.
Milford, J. B.; Davidson, C. I. (1985) The sizes of paniculate trace elements in the atmosphere—a review.
J. Air Pollut. Control Assoc. 35: 1249-1260.
Milford, J. B.; Davidson, C. I. (1987) The sizes of paniculate sulfate and nitrate in the atmosphere—a review.
JAPCA 37: 125-134.
Miller, D. F.; Alkezweeny, A. J. (1980) Aerosol formation in urban plumes over Lake Michigan. In: Kneip,
T. J.; Lioy, P. J., eds. Aerosols: anthropogenic and natural, sources and transport. Ann. N. Y. Acad.
Sci. 338: 219-232.
3-223
-------
Miller, F. J.; Gardner, D. E.; Graham, J. A.; Lee, R. E., Jr.; Wilson, W. E.; Bachmann, J. D. (1979) Size
considerations for establishing a standard for inhalable particles. J. Air Pollut. Control Assoc.
29: 610-615.
Mohnen, V. A.; Kadlecek, J. A. (1989) Cloud chemistry research at Whiteface Mountain. Tellus Ser. B 41B:
79-91.
Moran, M. D. (1992) Numerical modeling of mesoscale atmospheric dispersion [Ph.D. dissertation]. Ft. Collins,
CO: Colorado State University, Department of Atmospheric Science.
Morandi, M. T. (1985) Development of source apportionment models for inhalable paniculate matter and its
extractable organic fractions in urban areas of New Jersey [Ph.D. dissertation]. Syracuse, NY: New York
University. Available from: University Microfilms, Ann Arbor, MI; order no. AAC85-10516.
Morandi, M. T.; Lioy, P. J.; Daisey, J. M. (1991) Comparison of two multivariate modeling approaches for the
source apportionment of inhalable paniculate matter in Newark, NJ. Atmos. Environ. Part A
25: 927-937.
Moyers, J. L.; Ranweiler, L. E.; Hopf, S. B.; Korte, N. E. (1977) Evaluation of paniculate trace species in
southwest desert atmosphere. Environ. Sci. Technol. 11: 789-795.
Mozurkewich, M.; Calvert, J. G. (1988) Reaction probability of N2O5 on aqueous aerosols. J. Geophys. Res.
[Atmos.] 93: 15,889-15,896.
Mueller, P. K.; Fung, K. K.; Heisler, S. L.; Grosjean, D.; Hidy, G. M. (1982) Atmospheric paniculate carbon
observations in urban and rural areas of the United States. In: Wolff, G. T.; Klimisch, R. L., eds.
Paniculate carbon: atmospheric life cycle: proceedings of an international symposium; October 1980;
Warren, MI. New York, NY: Plenum Press; pp. 343-370.
Mulhbaier, J. L.; Williams, R. L. (1982) Fireplaces, furnaces and vehicles as emission sources of paniculate
carbon. In: Wolff, G. T.; Klimisch, R. L., eds. Paniculate carbon: atmospheric life cycle. New York,
NY: Plenum Press; pp. 185-205.
Munger, J. W.; Jacob, D. J.; Waldman, J. M.; Hoffmann, M. R. (1983) Fogwater chemistry in an urban
atmosphere. J. Geophys. Res. C: Oceans Atmos. 88: 5109-5121.
Munger, J. W.; Jacob, D. J.; Hoffmann, M. R. (1984) The occurrence of bisulfite-aldehyde addition products in
fog- and cloudwater. J. Atmos. Chem. 1: 335-350.
Munger, J. W.; Collett, J., Jr.; Daube, B., Jr.; Hoffmann, M. R. (1990) Fogwater chemistry at Riverside,
California. Atmos. Environ. Part B 24: 185-205.
Mylonas, D. T.; Allen, D. T.; Ehrman, S. H.; Pratsinis, S. E. (1991) The sources and size distributions of
organonitrates in Los Angeles aerosol. Atmos. Environ. Part A 25: 2855-2861.
Nair, S. K.; Peters, L. K. (1989) Studies on non-precipitating cumulus cloud acidification. Atmos. Environ.
23: 1399-1423.
National Research Council. (1979) Airborne particles. Baltimore, MD: University Park Press.
National Research Council. (1983) Polycyclic aromatic hydrocarbons: evaluation of sources and effects.
Washington, DC: National Academy Press.
3-224
-------
National Research Council. (1993) Protecting visibility in national parks and wilderness areas. Washington, DC:
National Academy Press. 3v.
Newman, L. (1981) Atmospheric oxidation of sulfur dioxide: a review as viewed from power plant and smelter
plume studies. Atmos. Environ. 15: 2231-2239.
Newman, L.; Forrest, J.; Manowitz, B. (1975a) The application of an isotopic ratio technique to a study of the
atmospheric oxidation of sulfur dioxide in the plume from an oil-fired power plant, Atmos. Environ.
9: 959-968.
Newman, L.; Forrest, J.; Manowitz, B. (1975b) The application of an isotopic ratio technique to a study of the
atmospheric oxidation of sulfur dioxide in the plume from a coal fired power plant. Atmos. Environ.
9: 969-977.
Nicholson, K. W. (1988) The dry deposition of small particles: a review of experimental measurements. Atmos.
Environ. 22: 2653-2666.
Nielsen, T. (1984) Reactivity of polycyclic aromatic hydrocarbons toward nitrating species. Environ. Sci.
Technol. 18: 157-163.
Nielsen, T.; Ramdahl, T.; Bj0rseth, A. (1983) The fate of airborne polycyclic organic matter. Environ. Health
Perspect. 47: 103-114.
Noone, K. J.; Ogren, J. A.; Hallberg, A.; Hansson, H.-C; Wiedensohler, A.; Swietlicki, E. (1992a)
A statistical examination of the chemical differences between interstitial and scavenged aerosol.
Tellus Ser. B 44B: 581-592.
Noone, K. J.; Ogren, J. A.; Hallberg, A.; Heintzenberg, J.; Strom, J.; Hansson, H.-C.; Svenningsson, B.;
Wiedensohler, A.; Fuzzi, S.; Facchini, M. C.; Arends, B. G.; Berner, A. (1992b) Changes in aerosol
size- and phase distributions due to physical and chemical processes in fog. Tellus Ser. B 44B: 489-504.
Novakov, T. (1984) The role of soot and primary oxidants in the atmospheric chemistry. Sci. Total Environ.
36: 1-10.
Novakov, T.; Penner, J. E. (1993) Large contribution of organic aerosols to cloud-condensation-nuclei
concentrations. Nature (London) 365: 823-826.
Noxon, J. F. (1983) NO3 and NO2 in the mid-Pacific troposphere. J. Geophys. Res. C: Oceans Atmos.
88: 11,017-11,021.
Nunes, T. V.; Pio, C. A. (1993) Carbonaceous aerosols in industrial and coastal atmospheres. Atmos. Environ.
Part A 27: 1339-1346.
Oberdorster, G. (1995) Lung particle overload: implications for occupational exposures to particles. Regul.
Toxicol. Pharmacol. 27: 123-135.
O'Brien, R. J.; Crabtree, J. H.; Holmes, J. R.; Hoggan, M. C.; Bockian, A. H. (1975) Formation of
photochemical aerosol from hydrocarbons: atmospheric analysis. Environ. Sci. Technol. 9: 577-582.
O'Dell, R. A.; Taheri, M.; Kabel, R. L. (1977) A model for uptake of pollutants by vegetation. J. Air Pollut.
Control Assoc. 27: 1104-1109.
Ogren, J. A.; Charlson, R. J. (1992) Implications for models and measurements of chemical inhomogeneities
among cloud droplets. Tellus Ser. B 44B: 208-225.
3-225
-------
Olmez, I.; Sheffield, A. E.; Gordon, G. E.; Houck, J. E.; Pritchett, L. C.; Cooper, J. A.; Dzubay, T. G.;
Bennett, R. L. (1988) Compositions of particles from selected sources in Philadelphia for receptor
modeling applications. JAPCA 38: 1392-1402.
Olson, T. M.; Hoffman, M. R. (1989) Hydroxyalkylsulfonate formation: its role as a S(IV) reservoir in
atmospheric water droplets. Atmos. Environ. 23: 985-997.
Otani, Y.; Wang, C. S. (1984) Growth and deposition of saline droplets covered with a monolayer of surfactant.
Aerosol Sci. Technol. 3: 155-166.
Pack, D. H.; Ferber, G. J.; Heffter, J. L.; Telegadas, K.; Angell, J. K.; Hoecker, W. H.; Machta, L. (1978)
Meteorology of long-range transport. Atmos. Environ. 12: 425-444.
Palen, E. J.; Allen, D. T.; Pandis, S. N.; Paulson, S. E.; Seinfeld, J. H.; Flagan, R. C. (1992) Fourier
transform infrared analysis of aerosol formed in the photo-oxidation of isoprene and /3-pinene. Atmos.
Environ. Part A 26: 1239-1251.
Pandis, S. N.; Seinfeld, J. H. (1989a) Sensitivity analysis of a chemical mechanism for aqueous-phase
atmospheric chemistry. J. Geophys. Res. [Atmos.] 94: 1105-1126.
Pandis, S. N.; Seinfeld, J. H. (1989b) Mathematical modeling of acid deposition due to radiation fog.
J. Geophys. Res. [Atmos.] 94: 12,911-12,923.
Pandis, S. N.; Seinfeld, J. H.; Pilinis, C. (1990a) The smog-fog-smog cycle and acid deposition. J. Geophys.
Res. [Atmos.] 95: 18,489-18,500.
Pandis, S. N.; Seinfeld, J. H.; Pilinis, C. (1990b) Chemical composition differences in fog and cloud droplets of
different sizes. Atmos. Environ. Part A 24: 1957-1969.
Pandis, S. N.; Paulson, S. E.; Seinfeld, J. H.; Flagan, R. C. (1991) Aerosol formation in the photooxidationof
isoprene and /8-pinene. Atmos. Environ. Part A 25: 997-1008.
Pandis, S. N.; Harley, R. A.; Cass, G. R.; Seinfeld, J. H. (1992a) Secondary organic aerosol formation and
transport. Atmos. Environ. Part A 26: 2269-2282.
Pandis, S. N.; Seinfeld, J. H.; Pilinis, C. (1992b) Heterogeneous sulfate production in an urban fog. Atmos.
Environ. Part A 26: 2509-2522.
Pandis, S. N.; Wexler, A. S.; Seinfeld, J. H. (1993) Secondary organic aerosol formation and transport—
II. predicting the ambient secondary organic aerosol size distribution. Atmos. Environ. Part A
27: 2403-2416.
Pankow, J. F. (1987) Review and comparative analysis of the theories on partitioning between the gas and
aerosol paniculate phases in the atmosphere. Atmos. Environ. 21: 2275-2283.
Pankow, J. F. (1988) Gas phase retention volume behavior of organic compounds on the sorbent
poly(oxy-/w-terphenyl-2'-5'-ylene). Anal. Chem. 60: 950-958.
Pankow, J. F. (1989) Overview of the gas phase retention volume behavior of organic compounds on
polyurethane foam. Atmos. Environ. 23: 1107-1111.
Pankow, J. F. (1991) Common y-intercept and single compound regressions of gas-particle partitioning data vs.
l/T. Atmos. Environ. Part A 25: 2229-2239.
3-226
-------
Pankow, J. F. (1994a) An absorption model of gas/particle partitioning of organic compounds in the atmosphere.
Atmos. Environ. 28: 185-188.
Pankow, J. F. (1994b) An absorption model of the gas/aerosol partitioning involved in the formation of
secondary organic aerosol. Atmos. Environ. 28: 189-193.
Pankow, J. F.; Bidleman, T. F. (1991) Effects of temperature, TSP and per cent non-exchangeable material in
determining the gas-particle partitioning of organic compounds. Atmos. Environ. Part A 25: 2241-2249.
Pankow, J. F.; Bidleman, T. F. (1992) Interdependence of the slopes and intercepts from log-log correlations of
measured gas-particle partitioning and vapor pressure -1. theory and analysis of available data. Atmos
Environ. Part A 26: 1071-1080.
Pankow, J. F.; Storey, J. M. E.; Yamasaki, H. (1993) Effects of relative humidity on gas/particle partitioning of
semivolatile organic compounds to urban paniculate matter. Environ. Sci. Technol. 27: 2220-2226.
Parrish, D. D.; Fahey, D. W.; Williams, E. J.; Liu, S. C; Trainer, M.; Murphy, P. C.; Albritton, D. L.;
Fehsenfeld, F. C. (1986) Background ozone and anthropogenic ozone enhancement at Niwot Ridge,
Colorado. J. Atmos. Chem. 4: 63-80.
Pasquill, F. (1974) Atmospheric diffusion. New York, NY: John Wiley and Sons.
Pasquill, F.; Smith, F. B. (1983) Atmospheric diffusion. 3rd ed. New York, NY: John Wiley.
Pastuszka, J. S.; Kwapulinski, J. (1988) The change in mass size distribution of aerosol near dumps as a result of
resuspension of dust. Presented at: 81st annual meeting of Air Pollution Control Association; June;
Dallas, TX. Pittsburgh, PA: Air Pollution Control Association; paper no. 88-151.3.
Patrinos, A. A. N. (1985) The impact of urban and industrial emissions on mesoscale precipitation quality. J. Air
Pollut. Control Assoc. 35: 719-727.
Patrinos, A. A. N.; Brown, R. M. (1984) Mesoscale wetfall chemistry around Philadelphia during frontal storms.
Geophys. Res. Lett. 11: 561-564.
Patrinos, A. A. N.; Leach, M. J.; Brown, R. M.; Tanner, R. L.; Binkowski, F. S. (1989) An acid rain study in
the Washington, D.C. area. J. Appl. Meteorol. 28: 948-968.
Patterson, E. M.; Gillette, D. A. (1977a) Commonalities in measured size distributions for aerosols having a
soil-derived component. J. Geophys. Res. 82: 2074-2082.
Patterson, E. M.; Gillette, D. A. (1977b) Measurements of visibility vs. mass-concentration for airborne soil
particles. Atmos. Environ. 11: 193-196.
Patterson, R. K.; Wagman, J. (1977) Mass and composition of an urban aerosol as a function of particle size for
several visibility levels. J. Aerosol Sci. 8: 269-279.
Peirson, D. H.; Cawse, P. A.; Salmon, L.; Cambray, R. S. (1973) Trace elements in the atmospheric
environment. Nature (London) 241: 252-256.
Penkett, S. A. (1972) Oxidation of SO2 and other atmospheric gases by ozone in aqueous solution. Nature
(London) 240: 105-106.
3-227
-------
Penkett, S. A.; Jones, B. M. R.; Brice, K. A.; Eggleton, A. E. J. (1979) The importance of atmospheric ozone
and hydrogen peroxide in oxidising sulphur dioxide in cloud and rainwater. Atmos. Environ.
13: 123-137.
Penner, J. E.; Eddleman, H.; Novakov, T. (1993) Towards the development of a global inventory for black
carbon emissions. Atmos. Environ. Part A 27: 1277-1295.
Peters, K.; Eiden, R. (1992) Modelling the dry deposition velocity of aerosol particles to a spruce forest. Atmos.
Environ. Part A 26: 2555-2564.
Peterson, J. T.; Junge, C. E. (1971) Sources of paniculate matter in the atmosphere. In: Matthews, W. H.;
Kellogg, W. W.; Robinson, G. D., eds. Man's impact on the climate. Cambridge, MA: MIT Press.
Pickle, T.; Allen, D. T.; Pratsinis, S. E. (1990) The sources and size distributions of aliphatic and carbonyl
carbon in Los Angeles aerosol. Atmos. Environ. Part A 24: 2221-2228.
Pielke, R. A.; et al. (1992) A comprehensive mesoscale modeling system - RAMS. Meteorol. Atmos. Phys.
49: 69-91.
Pierson, W. R.; Brachaczek, W. W. (1983) Particulate matter associated with vehicles on the road. II. Aerosol
Sci. Technol. 2: 1-40.
Pierson, W. R.; Brachaczek, W. W. (1990) Dew chemistry and acid deposition in Glendora, California, during
the 1986 Carbonaceous Species Methods Comparison Study. Aerosol Sci. Technol. 12: 8-27.
Pierson, W. R.; Brachaczek, W. W.; Gorse, R. A., Jr.; Japar, S. M.; Norbeck, J. M. (1986) On the acidity of
dew. J. Geophys. Res. [Atmos.] 91: 4083-4096.
Pierson, W. R.; Brachaczek, W. W.; Japar, S. M.; Cass, G. R.; Solomon, P. A. (1988) Dry deposition and dew
chemistry in Claremont, California, during the 1985 Nitrogen Species Methods Comparison Study.
Atmos. Environ. 22: 1657-1663.
Pilinis, C.; Seinfeld, J. H. (1987) Continued development of a general equilibrium model for inorganic
multicomponent atmospheric aerosols. Atmos. Environ. 21: 2453-2466.
Pilinis, C.; Seinfeld, J. H. (1988) Development and evaluation of an Eulerian photochemical gas-aerosol model.
Atmos. Environ. 22: 1985-2001.
Pilinis, C.; Seinfeld, J. H.; Grosjean, D. (1989) Water content of atmospheric aerosols. Atmos. Environ.
23: 1601-1606.
Pinnick, R. G.; Fernandez, G.; Hinds, B. D.; Bruce, C. W.; Schaefer, R. W.; Pendleton, J. D. (1985) Dust
generated by vehicular traffic on unpaved roadways: sizes and infrared extinction characteristics. Aerosol
Sci. Technol. 4: 99-121.
Pinnick, R. G.; Fernandez, G.; Martinez-Andazola, E.; Hinds, B. D.; Hansen, A. D. A.; Fuller, K. (1993)
Aerosol in the arid southwestern United States: measurements of mass loading, volatility, size
distribution, absorption characteristics, black carbon content, and vertical structure to 7 km above sea
level. J. Geophys. Res. [Atmos.] 98: 2651-2666.
Pires, M.; Rossi, M. J.; Ross, D. S. (1994) Kinetic and mechanistic aspects of the NO oxidation by ©2 in
aqueous phase. Int. J. Chem. Kinet. 26: 1207-1227.
3-228
-------
Pitchford, M. L.; McMurry, P. H. (1994) Relationship between measured water vapor growth and chemistry of
atmospheric aerosol for Grand Canyon, Arizona, in winter 1990. Atmos. Environ. 28: 827-839.
Pitts, J. N., Jr.; Atkinson, R.; Sweetman, J. A.; Zielinska, B. (1985a) The gas-phase reaction of naphthalene
with N2O5 to form nitronaphthalenes. Atmos. Environ. 19: 701-705.
Pitts, J. N., Jr.; Zielinska, B.; Sweetman, J. A.; Atkinson, R.; Winer, A. M. (1985b) Reaction of adsorbed
pyrene and perylene with gaseous N2O5 under simulated atmospheric conditions. Atmos. Environ.
19: 911-915.
Pitts, J. N., Jr.; Paur, H.-R.; Zielinska, B.; Arey, J.; Winer, A. M.; Ramdahl, T.; Mejia, V. (1986) Factors
influencing the reactivity of polycyclic aromatic hydrocarbons adsorbed on filters and ambient POM with
ozone. Chemosphere 15: 675-685.
Placet, M.; Battye, R. E.; Fehsenfeld, F. C.; Bassett, G. W. (1991) Emissions involved in acidic deposition
processes. In: Irving, P. M., ed. Acidic depostion: state of science and technology, volume I: emissions,
atmospheric processes, and deposition. Washington, DC: The U.S. National Acid Precipitation
Assessment Program. (State of science and technology report no. 1).
Pleim, J.; Venkatram, A.; Yamartino, R. J. (1984) The dry deposition model, v. 4. Rexdale, ON, Canada:
Ontario Ministry of the Environment, ADOM/TADAP Model Development Program.
Post, J. E.; Buseck, P. R. (1985) Quantitative energy-dispersive analysis of lead halide particles from the
Phoenix urban aerosol. Environ. Sci. Technol. 19: 682-685.
Pratsinis, S.; Ellis, E. C.; Novakov, T.; Friedlander, S. K. (1984) The carbon containing component of the Los
Angeles aerosol: source apportionment and contributions to the visibility budget. J. Air Pollut. Control
Assoc. 34: 643-650.
Pratsinis, S. E.; Zeldin, M. D.; Ellis, E. C. (1988) Source resolution of the fine carbonaceous aerosol by
principal component-stepwise regression analysis. Environ. Sci. Technol. 22: 212-216.
Pruppacher, H. R.; Klett, J. D. (1980) Microphysics of clouds and precipitation. Boston, MA: D. Reidel
Publishing Company.
Pueschel, R. F.; Van Valin, C. C.; Castillo, R. C.; Kadlecek, J. A.; Ganor, E. (1986) Aerosols in polluted
versus nonpolluted air masses: long-range transport and effects on clouds. J. Clim. Appl. Meteorol.
25: 1908-1917.
Rabano, E. S.; Castillo, N. T.; Torre, K. J.; Solomon, P. A. (1989) Speciation of arsenic in ambient aerosols
collected in Los Angeles. JAPCA 39: 76-80.
Rader, D. J.; McMurry, P. H. (1986) Application of the tandem differential mobility analyzer to studies of
droplet growth or evaporation. J. Aerosol Sci. 17: 771-787.
Radke, L. F.; Hobbs, P. V. (1991) Humidity and particle fields around some small cumulus clouds. J. Atmos.
Sci. 48: 1190-1193.
Radke, L. F.; Brock, C. A.; Lyons, J. H.; Hobbs, P. V.; Schnell, R. C. (1989) Aerosol and lidar measurements
of hazes in mid-latitude and polar airmasses. Atmos. Environ. 23: 2417-2430.
Raga, G. B.; Jonas, P. R. (1993) On the link between cloud-top radiative properties and sub-cloud aerosol
concentrations. Q. J. R. Meteorol. Soc. 119: 1419-1425.
3-229
-------
Ramdahl, T. (1983) Polycyclic aromatic ketones in environmental samples. Environ. Sci. Technol. 17: 666-670.
Ramdahl, T.; Becher, G.; Bjrsaeth, A. (1982) Nitrated polycyclic aromatic hydrocarbons in urban air particles.
Environ. Sci. Technol. 16: 861-865.
Ramdahl, T.; Bjerseth, A.; Lokensgard, D.; Pitts, J. N., Jr. (1984) Nitration of polycyclic aromatic
hydrocarbons adsorbed to different carriers in a fluidized bed reactor. Chemosphere 13: 527-534.
Ranade, M. B. (Arun); Woods, M. C.; Chen, F.-L.; Purdue, L. J.; Rehme, K. A. (1990) Wind tunnel
evaluation of PM10 samplers. Aerosol Sci. Technol. 13: 54-71.
Rao, A. K.; Whitby, K. T. (1978) Non-ideal collection characteristics of inertial impactors—I. single-stage
impactors and solid particles. J. Aerosol Sci. 9: 77-86.
Rau, J. A. (1989) Composition and size distribution of residential wood smoke particles. Aerosol Sci. Technol.
10: 181-192.
Reeks, M. W.; Reed, J.; Hall, D. (1988) On the resuspension of small particles by a turbulent flow. J. Phys. D:
Appl. Phys. 21:574-589.
Richards, L. W. (1983) Comments on the oxidation of NO2 to nitrate - day and night. Atmos. Environ.
17: 397-402.
Richards, L. W.; Anderson, J. A.; Blumenthal, D. L.; Brandt, A. A.; McDonald, J. A.; Waters, N.; Macias,
E. S.; Bhardwaja, P. S. (1981) The chemistry, aerosol physics, and optical properties of a western
coal-fired power plant plume. Atmos. Environ. 15: 2111-2134.
Richards, L. W.; Anderson, J. A.; Blumenthal, D. L.; McDonald, J. A. (1982a) Nitrogen and sulfur chemistry
and aerosol formation in plumes. Presented at: 75th annual meeting of the Air Pollution Control
Association; June; New Orleans, LA. Pittsburgh, PA: Air Pollution Control Association; paper no.
82-24.6.
Richards, L. W.; Anderson, J. A.; Blumenthal, D. L.; McDonald, J. A. (1982b) Comparison of the optical
properties of particles in smelter and western power plant plumes [poster presentation]. Presented at: 75th
annual meeting of the Air Pollution Control Association; June; New Orleans, LA. Pittsburgh, PA: Air
Pollution Control Association; poster presentation no. 82-7P.5
Richards, L. W.; Blumenthal, D. L.; Bergstrom, R. W.; Seigneur, C.; Smith, T. B.; Macias, E. S.; Hering,
S. V.; Bhardwaja, P. S.; Wilson, W. E. (1982c) VISTTA authors' reply. Atmos. Environ.
16: 2363-2365.
Richards, L. W.; Anderson, J. A.; Blumenthal, D. L.; McDonald, J. A.; Macias, E. S.; Hering, S. V.; Wilson,
W. E., Jr. (1985) Chemical, aerosol and optical measurements in the plumes of three midwestern
coal-fired power plants. Atmos. Environ. 19: 1685-1704.
Richards, L. W.; Blanchard, C. L.; Blumenthal, D. L. (1991) Navajo generating station visibility study,
draft #2. Santa Rosa, CA: Sonoma Technology, Inc.; final report STI-90200-1124-FRD2.
Richardson, C. B.; Hightower, R. L. (1987) Evaporation of ammonium nitrate particles. Atmos. Environ.
21: 971-975.
Richardson, C. B.; Spann, J. F. (1984) Measurement of the water cycle in a levitated ammonium sulfate particle.
J. Aerosol Sci. 15: 563-571.
3-230
-------
Roberts, D.; Williams, D. (1979) The kinetics of oxidation of sulphur dioxide within the plume from a sulphide
smelter in a remote region. Atmos. Environ. 13: 1485-1499.
Roelofs, G. J. H. (1992a) Drop size dependent sulfate distribution in a growing cloud. J. Atmos. Chem.
14: 109-118.
Roelofs, G. J. H. (1992b) On the drop and aerosol size dependence of aqueous sulfate formation in a continental
cumulus cloud. Atmos. Environ. Part A 26: 2309-2321.
Roelofs, G. J. H. (1993) A cloud chemistry sensitivity study and comparison of explicit and bulk cloud model
performance. Atmos. Environ. Part A 27: 2255-2264.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1991) Sources of fine
organic aerosol. 1. Charbroilers and meat cooking operations. Environ. Sci. Technol. 25: 1112-1125.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1993a) Sources of fine
organic aerosol. 2. Noncatalyst and catalyst-equipped automobiles and heavy-duty diesel trucks. Environ.
Sci. Technol. 27: 636-651.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1993b) Sources of fine
organic aerosol. 3. Road dust, tire debris, and organometallic brake lining dust: roads as sources and
sinks. Environ. Sci. Technol. 27: 1892-1904.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1993c) Sources of fine
organic aerosol. 4. Paniculate abrasion products from leaf surfaces of urban plants. Environ. Sci.
Technol. 27: 2700-2711.
Rogge, W. F.; Mazurek, M. A.; Hildemann, L. M.; Cass, G. R.; Simoneit, B. R. T. (1993d) Quantification of
urban organic aerosols at a molecular level: identification, abundance and seasonal variation. Atmos.
Environ. Part A 27: 1309-1330.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1994) Sources of fine
organic aerosol. 6. Cigarette smoke in the urban atmosphere. Environ. Sci. Technol. 28: 1375-1388.
Rolph, G. D.; Draxler, R. R. (1990) Sensitivity of three-dimensional trajectories to the spatial and temporal
densities of the wind field. J. Appl. Meteorol. 29: 1043-1054.
Rood, M. J.; Larson, T. V.; Covert, D. S.; Ahlquist, N. C. (1985) Measurement of laboratory and ambient
aerosols with temperature and humidity controlled nephelometry. Atmos. Environ. 19: 1181-1190.
Rood, M. J.; Shaw, M. A.; Larson, T. V.; Covert, D. S. (1989) Ubiquitous nature of ambient metastable
aerosol. Nature (London) 337: 537-539.
Rounds, S. A.; Pankow, J. F. (1990) Application of a radial diffusion model to describe gas/particle sorption
kinetics. Environ. Sci. Technol. 24: 1378-1386.
Rubel, G. O.; Gentry, J. W. (1984) Measurement of the kinetics of solution droplets in the presence of adsorbed
monolayers: determination of water accommodation coefficients. J. Phys. Chem. 88: 3142-3148.
Sakugawa, H.; Kaplan, I. R.; Tsai, W.; Cohen, Y. (1990) Atmospheric hydrogen peroxide: does it share a role
with ozone in degrading air quality? Environ. Sci. Technol. 24: 1452-1462.
Satsumabayashi, H.; Kurita, H.; Yokouchi, Y.; Ueda, H. (1989) Mono- and di-carboxylic acids under long-range
transport of air pollution in central Japan. Tellus Ser. B 41B: 219-229.
3-231
-------
Satsumakayashi, H.; Kurita, H.; Yokouchi, Y.; Ueda, H. (1990) Photochemical formation of paniculate
dicarboxylic acids under long-range transport in central Japan. Atmos. Environ. Part A 24: 1443-1450.
Savoie, D. L.; Prospero, J. M.; Nees, R. T. (1987) Washout ratios of nitrate, non-sea-salt sulfate and sea-salt on
Virginia Key, Florida and on American Samoa. Atmos. Environ. 21: 103-112.
Saxena, P. (1994) Authors' response to comments on "Coupling thermodynamic theory with measurements to
characterize acidity of atmospheric particles." Aerosol Sci. Technol. 20: 287-288.
Saxena, V. K.; Hendler, A. H. (1983) In-cloud scavenging and resuspension of cloud active aerosols during
winter storms over Lake Michigan. In: Pruppacher, H. R.; Semonin, R. G.; Slinn, W. G. N., eds.
Precipitation scavenging, dry deposition, and resuspension, v. 1: precipitation scavenging: proceedings of
the fourth international conference; November-December 1982; Santa Monica, CA. New York, NY:
Elsevier; pp. 91-101.
Saxena, P.; Hildemann, L. M. (1996) Water-soluble organics in atmospheric particles: a critical review of the
literature and applications of thermodynamics to identify candidate compounds. J. Atmos. Chem.:
accepted.
Saxena, P.; Seigneur, C. (1987) On the oxidation of SO2 to sulfate in atmospheric aerosols. Atmos. Environ.
21: 807-812.
Saxena, P.; Mueller, P. K.; Kim, Y. P.; Seinfeld, J. H.; Koutrakis, P. (1993) Coupling thermodynamic theory
with measurements to characterize acidity of atmospheric particles. Aerosol Sci. Technol. 19: 279-293.
Saxena, P.; Hildemann, L. M.; McMurry, P. H.; Seinfeld, J. H. (1995) Organics alter hygroscopic behavior of
atmospheric particles. J. Geophys. Res. [Atmos.]: in press.
Say lor, R. D. (1989) A study of mesoscale acid deposition in the lower Ohio River Valley [Ph.D. dissertation].
Lexington, KY: University of Kentucky, Chemical Engineering Department.
Schlesinger, R. B. (1994) Comments on "Coupling thermodynamic theory with measurements to characterize
acidity of atmospheric particles" by P. Saxena et al. Aerosol Sci. Technol. 20: 285-286.
Schmidt, J. A.; Andren, A. W. (1980) The atmospheric chemistry of nickel. In: Nriagu, J. O., ed. Nickel in the
environment. New York, NY: John Wiley & Sons, Inc.; pp. 93-135.
Schroeder, W. H.; Dobson, M.; Kane, D. M.; Johnson, N. D. (1987) Toxic trace elements associated with
airborne paniculate matter: a review. JAPCA 37: 1267-1285.
Schuetzle, D.; Cronn, D.; Crittenden, A. L.; Charlson, R. J. (1975) Molecular composition of secondary aerosol
and its possible origin. Environ. Sci. Technol. 9: 838-845.
Schwartz, S. E. (1979) Residence times in reservoirs under non-steady-state conditions: application to
atmospheric SO2 and aerosol sulfate. Tellus 31: 530-547.
Schwartz, S. E. (1984a) Gas-aqueous reactions of sulfur and nitrogen oxides in liquid-water clouds. In: Calvert,
J. G., ed. SO2, NO and NO2 oxidation mechanisms: atmospheric considerations. Boston, MA:
Butterworth Publishers; pp. 173-208. (Teasley, J. I., ed. Acid precipitation series: v. 3).
Schwartz, S. E. (1984b) Gas- and aqueous-phase chemistry of HO2 in liquid water clouds. J. Geophys. Res.
[Atmos.] 89: 11,589-11,598.
3-232
-------
Schwartz, S. E. (1986a) Chemical conversions in clouds. In: Lee, S. D.; Schneider, T.; Grant, L. D.;
Verkerk, P., eds. Aerosols: research, risk assessment and control strategies, proceedings of the second
U.S.-Dutch international symposium; May 1985; Williamsburg, VA. Chelsea, MI: Lewis Publishers,
Inc.; pp. 349-375.
Schwartz, S. E. (1986b) Mass-transport considerations pertinent to aqueous-phase reactions of gases in
liquid-water clouds. In: Jaeschke, W., ed. Chemistry of multiphase atmospheric systems. Berlin, Federal
Republic of Germany: Springer-Verlag; pp. 415-471. (NATO advanced science institutes series G:
ecological sciences v. 6).
Schwartz, S. E. (1987) Both sides now: the chemistry of clouds. Ann. N. Y. Acad. Sci. 502: 83-144.
Schwartz, S. E. (1988) Mass-transport limitation to the rate of in-cloud oxidation of SO2: re-examination in the
light of new data. Atmos. Environ. 22: 2491-2499.
Schwartz, S. E. (1989) Acid deposition: unraveling a regional phenomenon. Science (Washington, DC)
243: 753-763.
Schwartz, S. E.; Freiberg, J. E. (1981) Mass-transport limitation to the rate of reaction of gases in liquid
droplets: application to oxidation of SO2 in aqueous solutions. Atmos. Environ. 15: 1129-1144.
Schwartz, S. E.; Newman, L. (1978) Processes limiting oxidation of sulfur dioxide in stack plumes. Environ.
Sci. Technol. 12: 67-73.
Schwartz, S. E.; Newman, L. (1983) Measurements of sulfate production in natural clouds [discussion of Hegg
and Hobbs (1982)]. Atmos. Environ. 17: 2629-2632.
Schwartz, S. E.; White, W. H. (1983) Kinetics of reactive dissolution of nitrogen oxides into aqueous solution.
In: Schwartz, S. E., ed. Trace atmospheric constituents: properties, transformations, and fates. New
York, NY: John Wiley & Sons; pp. 1-116. (Advances in environmental science and technology: v. 12).
Scott, B. C.; Laulainen, N. S. (1979) On the concentration of sulfate in precipitation. J. Appl. Meteorol.
18: 138-147.
Sega, K.; Fugas, M. (1984) Seasonal and spatial differences in mass concentration levels and particle size
distribution of aerosols over an urban area. Atmos. Environ. 18: 2433-2437.
Sehmel, G. A. (1973) Particle resuspension from an asphalt road caused by car and truck traffic. Atmos.
Environ. 7: 291-309.
Sehmel, G. A. (1980) Particle and gas dry deposition: a review. Atmos. Environ. 14: 983-1011.
Sehmel, G. A. (1984) Deposition and resuspension. In: Randerson, D., ed. Atmospheric science and power
production. Washington, DC: U.S. Department of Energy, Office of Scientific and Technical
Information; report no. DOE/TIC-27601; pp. 533-583. Available from: NTIS, Springfield, VA;
DE84-005177.
Seidl, W. (1989) Ionic concentrations and initial S(IV)-oxidation rates in droplets during the condensational stage
of cloud. Tellus Ser. B 41B: 32-50.
Seigneur, C. (1982) A model of sulfate aerosol dynamics in atmospheric plumes. Atmos. Environ.
16: 2207-2228.
3-233
-------
Seigneur, C.; Constantinou, E. (1995) Chemical kinetic mechanism for atmospheric chromium. Environ. Sci.
Technol. 29:222-231.
Seigneur, C.; Saxena, P. (1984) A study of atmospheric acid formation in different environments. Atmos.
Environ. 18: 2109-2124.
Seigneur, C.; Saxena, P. (1988) A theoretical investigation of sulfate formation in clouds. Atmos. Environ.
22: 101-115.
Seigneur, C.; Wegrecki, A. M. (1990) Mathematical modeling of cloud chemistry in the Los Angeles basin.
Atmos. Environ. Part A 24: 989-1006.
Seigneur, C.; Saxena, P.; Roth, P. M. (1984) Computer simulations of the atmospheric chemistry of sulfate and
nitrate formation. Science (Washington, DC) 225: 1028-1030.
Seinfeld, J. H.; Flagan, R. C.; Petti, T. B.; Stern, J. E.; Grosjean, D. (1987) Aerosol formation in aromatic
hydrocarbon-NOx systems. Pasadena, CA: California Institute of Technology; project no. AP-6.
Sergides, C. A.; Jassim, J. A.; Chughtai, A. R.; Smith, D. M. (1987) The structure of hexane soot. Part III:
Ozonation studies. Appl. Spectrosc. 41: 482-492.
Shah, J. J.; Johnson, R. L.; Heyerdahl, E. K.; Huntzicker, J. J. (1986) Carbonaceous aerosol at urban and rural
sites in the United States. J. Air Pollut. Control Assoc. 36: 254-257.
Shao, Y.; Raupach, M. R.; Findlater, P. A. (1993) Effect of saltation bombardment on the entrainment of dust
by wind. J. Geophys. Res. [Atmos.] 98: 12,719-12,726.
Shaw, M. A.; Rood, M. J. (1990) Measurement of the crystallization humidities of ambient aerosol particles.
Atmos. Environ. Part A 24: 1837-1841.
Sheridan, P. J.; Schnell, R. C.; Kahl, J. D.; Boatman, J. F.; Garvey, D. M. (1993) Microanalysis of the aerosol
collected over south-central New Mexico during the ALIVE field experiment, May-December 1989.
Atmos. Environ. Part A 27: 1169-1183.
Shinn, J. H.; Homan, D. N.; Gay, D. D. (1983) Plutonium aerosol fluxes and pulmonary exposure rates during
resuspension from bare soils near a chemical separation facility. In: Pruppacher, H. R.; Semonin, R. G.;
Slinn, W. G. N., eds. Precipitation scavenging, dry deposition, and resuspension, v. 2: dry deposition
and resuspension: proceedings of the fourth international conference; November-December 1982; Santa
Monica, CA. New York, NY: Elsevier; pp. 1131-1143.
Sievering, H.; Van Valin, C. C.; Barrett, E. W.; Pueschel, R. F. (1984) Cloud scavenging of aerosol sulfur: two
case studies. Atmos. Environ. 18: 2685-2690.
Sievering, H.; Boatman, J.; Galloway, J.; Keene, W.; Kim, Y.; Luria, M.; Ray, J. (1991) Heterogeneous sulfur
conversion in sea-salt aerosol particles: the role of aerosol water content and size distribution. Atmos.
Environ. Part A 25: 1479-1487.
Sievering, H.; Gorman, E.; Kim, Y.; Ley, T.; Seidl, W.; Boatman, J. (1994) Heterogeneous conversion
contribution to the sulfate observed over Lake Michigan. Atmos. Environ. 28: 367-370.
Simoneit, B. R. T. (1984) Organic matter of the troposphere—III. characterization and sources of petroleum and
pyrogenic residues in aerosols over the western United States. Atmos. Environ. 18: 51-67.
3-234
-------
Simoneit, B. R. T. (1986) Characterization of organic constituents in aerosols in relation to their origin and
transport: a review. Presented at: the 2nd workshop on chemistry analysis of hydrocarbons in the
environment; November 1985; Barcelona, Spain. Int. J. Environ. Anal. Chem. 23: 207-237.
Simoneit, B. R. T. (1989) Organic matter of the troposphere - V: application of molecular marker analysis to
biogenic emissions into the troposphere for source reconciliations. Presented at: the international
symposium on biosphere-atmosphere exchange; March 1986; Mainz, Federal Republic of Germany.
J. Atmos. Chem. 8: 251-275.
Simoneit, B. R. T.; Mazurek, M. A. (1982) Organic matter of the troposphere—II. natural background of
biogenic lipid matter in aerosols over the rural western United States. Atmos. Environ. 16: 2139-2159.
Sisler, J. F.; Malm, W. C. (1994) The relative importance of soluble aerosols to spatial and seasonal trends of
impaired visibility in the United States. Atmos. Environ. 28: 851-862.
Sisterson, D. L.; Bowersox, V. C.; Olsen, A. R.; Meyers, T. P.; Olsen, A. R.; Vong, R. L. (1991) Deposition
monitoring: methods and results. In: Irving, P. M., ed. Acidic deposition: state of science and
technology, volume I: emissions, atmospheric processes, and depostition. Washington, DC: The U.S.
National Acid Precipitation Assessment Program. (State of science and technology report no. 6).
Slinn, W. G. N. (1983) Air-to-sea transfer of particles. In: Liss, P. S.; Slinn, W. G. N., eds. Air-sea exchange
of gases and particles. Boston, MA: D. Reidel Publishing Company; pp. 299-405. (NATO ASI series.
Series C, mathematical and physical sciences; no. 108).
Sloane, C. S. (1982) Visibility trends—II. mideastern United States 1948-1978. Atmos. Environ. 16: 2309-2321.
Sloane, C. S.; Groblicki, P. J. (1981) Denver's visibility history. Atmos. Environ. 15: 2631-2638.
Sloane, C. S.; Watson, J.; Chow, J.; Pritchett, L.; Richards, L. W. (1991) Size-segregated fine particle
measurements by chemical species and their impact on visibility impairment in Denver. Atmos. Environ.
Part A 25: 1013-1024.
Smith, T. B. (1981) Some observations of pollutant transport associated with elevated plumes. Atmos. Environ.
15: 2197-2203.
Smith, D. M.; Akhter, M. S.; Jassim, J. A.; Sergides, C. A.; Welch, W. F.; Chughtai, A. R. (1989) Studies of
the structure and reactivity of soot. Aerosol Sci. Technol. 10: 311-325.
Snider, J. R.; Vali, G. (1994) Sulfur dioxide oxidation in winter orographic clouds. J. Geophys. Res. [Atmos.]
99: 18,713-18,733.
Spann, J. F.; Richardson, C. B. (1985) Measurement of the water cycle in mixed ammonium acid sulfate
particles. Atmos. Environ. 19: 819-825.
Spengler, J. D.; Keeler, G. J.; Koutrakis, P.; Ryan, P. B.; Raizenne, M.; Franklin, C. A. (1989) Exposures to
acidic aerosols. In: Symposium on the health effects of acid aerosols; October 1987; Research Triangle
Park, NC. Environ. Health Perspect. 79: 43-51.
Spicer, C. W. (1977a) Photochemical atmospheric pollutants derived from nitrogen oxides. Atmos. Environ.
11: 1089-1095.
Spicer, C. W. (1977b) The fate of nitrogen oxides in the atmosphere. In: Pitts, J. N., Jr.; Metcalf, R. L.; Lloyd,
A. C., eds. Advances in environmental science and technology: v. 4. New York, NY: John Wiley and
Sons, Inc.; pp. 163-261.
3-235
-------
Stein, S. W.; Turpin, B. J.; Cai, X.; Huang, P.-F.; McMuny, P. H. (1994) Measurements of relative
humidity-dependent bounce and density for atmospheric particles using the DMA-impactor technique.
Atmos. Environ. 28: 1739-1746.
Steiner, D.; Burtscher, H.; Gross, H. (1992) Structure and disposition of particles from a spark-ignition engine.
Atmos. Environ. Part A 26: 997-1003.
Stelson, A. W.; Seinfeld, J. H. (1981) Chemical mass accounting of urban aerosol. Environ. Sci. Technol.
15: 671-679.
Stelson, A. W.; Seinfeld, J. H. (1982a) Relative humidity and temperature dependence of the ammonium nitrate
dissociation constant. Atmos. Environ. 16: 983-992.
Stelson, A. W.; Seinfeld, J. H. (1982b) Relative humidity and pH dependence of the vapor pressure of
ammonium nitrate-nitric acid solutions at 25°C. Atmos. Environ. 16: 993-1000.
Stern, J. E.; Flagan, R. C.; Grosjean, D.; Seinfeld, J. H. (1987) Aerosol formation and growth in atmospheric
aromatic hydrocarbon photooxidation. Environ. Sci. Technol. 21: 1224-1231.
Stevens, R. K.; Dzubay, T. G.; Lewis, C. W.; Shaw, R. W., Jr. (1984) Source apportionment methods applied
to the determination of the origin of ambient aerosols that affect visibility in forested areas. Atmos.
Environ. 18: 261-272.
Stewart, D. A.; Liu, M.-K. (1981) Development and application of a reactive plume model. Atmos. Environ.
15: 2377-2393.
Storey, J. M. E.; Pankow, J. F. (1992) Gas-particle partitioning of semi-volatile organic compounds to model
atmospheric paniculate materials—I. Sorption to graphite, sodium chloride, alumina, and silica particles
under low humidity conditions. Atmos. Environ. Part A 26: 435-443.
Strapp, J. W.; Leaitch, W. R.; Anlauf, K. G.; Bottenheim, J. W.; Joe, P.; Schemenauer, R. S.; Wiebe, H. A.;
Isaac, G. A.; Kelly, T. J.; Daum, P. H. (1988) Winter cloud water and air composition in Central
Ontario. J. Geophys. Res. [Atmos.] 93: 3760-3772.
Suh, H. H.; Spengler, J. D.; Koutrakis, P. (1992) Personal exposures to acid aerosols and ammonia. Environ.
Sci. Technol. 26: 2507-2517.
Suh, H. H.; Allen, G. A.; Aurian-Blajeni, B.; Koutrakis, P.; Burton, R. M. (1994a) Field method comparison
for the characterization of acid aerosols and gases. Atmos. Environ. 28: 2981-2989.
Suh, H. H.; Koutrakis, P.; Spengler, J. D. (1994b) The relationship between airborne acidity and ammonia in
indoor environments. J. Exposure Anal. Environ. Epidemiol. 4: 1-23.
Suh, H. H.; Allen, G. A.; Koutrakis, P.; Burton, R. M. (1995) Spatial variation in acidic sulfate and ammonia
concentrations within metropolitan Philadelphia. J. Air Waste Manage. Assoc. 45: 442-452.
Sutherland, A. J. (1967) Proposed mechanism for sediment entrainment by turbulent flows. J. Geophys. Res.
72: 6183-6194.
Svenningsson, B.; Hansson, H.-C.; Wiedensohler. A.; Noone, K.; Ogren, J.; Hallberg, A.; Calvile, R. (1994)
Hygroscopic growth of aerosol particles and its influence on nucleation scavenging in cloud: experimental
results from Kleiner Feldberg. J. Atmos. Chem. 19: 129-152.
3-236
-------
Sverdrup, G. M.; Whitby, K. T. (1980) The effect of changing relative humidity on aerosol size distribution
measurements. In: Hidy, G. M.; Mueller, P. K.; Grosjean, D.; Appel, B. R.; Wesolowski, J. J., eds.
The character and origins of smog aerosols: a digest of results from the California Aerosol
Characterization Experiment (ACHEX). New York, NY: John Wiley & Sons; pp. 527-558. (Advances in
environmental science and technology: v. 10).
Sviridenkov, M. A.; Gillette, D. A.; Isakov, A. A.; Sokolik, I. N.; Smirnov, V. V.; Belan, B, D.; Pachenko,
M. V.; Andronova, A. V.; Kolomiets, S. M.; Zhukov, V. M.; Zhukovsky, D. A. (1993) Size
distributions of dust aerosol measured during the Soviet-American experiment in Tadzhikistan, 1989.
Atmos. Environ. Part A 27: 2481-2486.
TSI. (1993) Model 390045 DISTFIT™ aerosol data fitting software. St. Paul and Golden Valley, MN: TSI, Inc.
and Chimera Software.
Tang, I. N. (1980) Deliquescence properties and particle size change of hygroscopic aerosols. In: Willeke, K.,
ed. Generation of aerosols and facilities for exposure experiments. Ann Arbor, MI: Ann Arbor Science;
pp. 153-167.
Tang, I. N.; Munkelwitz, H. R. (1977) Aerosol growth studies—III. ammonium bisulfate aerosols in a moist
atmosphere. J. Aerosol Sci. 8: 321-330.
Tang, I. N.; Munkelwitz, H. R. (1993) Composition and temperature dependence of the deliquescence properties
of hygroscopic aerosols. Atmos. Environ. Part A 27: 467-473.
Tang, I. N.; Munkelwitz, H. R. (1994) Water activities, densities, and refractive indices of aqueous sulfates and
sodium nitrate droplets of atmospheric importance. J. Geophys. Res. [Atmos.] 99: 18,801-18,808.
Tang, I. N.; Munkelwitz, H. R.; Davis, J. G. (1978) Aerosol growth studies - IV. phase transformation of mixed
salt aerosols in a moist atmosphere. J. Aerosol Sci. 9: 505-511.
Tang, I. N.; Wong, W. T.; Munkelwitz, H. R. (1981) The relative importance of atmospheric sulfates and
nitrates in visibility reduction. Atmos. Environ. 15: 2463-2471.
Tani, B.; Siegel, S.; Johnson, S. A.; Kumar, R. (1983) X-ray diffraction investigation of atmospheric aerosols in
the 0.3-1.0 /un aerodynamic size range. Atmos. Environ. 17: 2277-2283.
Tao, Y.; McMurry, P. H. (1989) Vapor pressures and surface free energies of C14-C18 monocarboxylic acids
and C5 and C6 dicarboxylic acids. Environ. Sci. Technol. 23: 1519-1523.
Taylor, G. I. (1922) Diffusion by continuous movements. Proc. London Math. Soc. 20: 196-212.
Taylor, G. R. (1989) Sulfate production and deposition in midlatitude continental cumulus clouds. Part II:
Chemistry model formulation and sensitivity analysis. J. Atmos. Sci. 46: 1991-2007.
Ten Brink, H. M.; Schwartz, S. E.; Daum, P. H. (1987) Efficient scavenging of aerosol sulfate by liquid-water
clouds. Atmos. Environ. 21: 2035-2052.
Thibodeaux, L. J.; Nadler, K. C.; Valsaraj, K. T.; Reible, D. D. (1991) The effect of moisture on volatile
organic chemical gas-to-particle partitioning with atmospheric aerosols—competitive adsorption theory
predictions. Atmos. Environ. Part A 25: 1649-1656.
Thomas, P.; Vogt, S. (1990) Mesoscale atmospheric dispersion experiments using tracer and tetroons. Atmos.
Environ. Part A 24: 1271-1284.
3-237
-------
Thompson, K. M.; Koutrakis, P.; Brauer, M.; Spengler, J. D.; Wilson, W. E.; Burton, R. M. (1991)
Measurements of aerosol acidity: sampling frequency, seasonal variability, and spatial variation.
Presented at: 84th annual meeting and exhibition of the Air & Waste Management Association; June;
Vancouver, BC, Canada. Pittsburgh, PA: Air & Waste Management Association; paper no. 91-89.5.
Thurston, G. D.; Gorczynski, J. E., Jr.; Jaques, P.; Currie, J.; He, D. (1992) An automated sequential sampling
system for paniculate acid aerosols: description, characterization, and field sampling results. J. Exposure
Anal. Environ. Epidemiol. 2: 415-428.
Tuazon, E. C.; Atkinson, R.; Plum, C. N.; Winer, A. M.; Pitts, J. N., Jr. (1983) The reaction of gas phase
N2O5 with water vapor. Geophys. Res. Lett. 10: 953-956.
Turpin, B. J.; Huntzicker, J. J. (1991) Secondary formation of organic aerosol in the Los Angeles basin:
a descriptive analysis of organic and elemental carbon concentrations. Atmos. Environ. Part A
25: 207-215.
Turpin, B. J.; Huntzicker, J. J. (1995) Identification of secondary organic aerosol episodes and quantitation of
primary and secondary organic aerosol concentrations during SCAQS. Atmos. Environ. 29: 3527-3544.
Turpin, B. J.; Gary, R. A.; Huntzicker, J. J. (1990) An in situ, time-resolved analyzer for aerosol organic and
elemental carbon. Aerosol Sci. Technol. 12: 161-171.
Turpin, B. J.; Huntzicker, J. J.; Larson, S. M.; Cass, G. R. (1991) Los Angeles summer midday particulate
carbon: primary and secondary aerosol. Environ. Sci. Technol. 25: 1788-1793.
Turpin, B. J.; Liu, S.-P.; Podolske, K. S.; Gomes, M. S. P.; Eisenreich, S. J.; McMurry, P. H. (1993) Design
and evaluation of a novel diffusion separator for measuring gas/particle distributions of semivolatile
organic compounds. Environ. Sci. Technol. 27: 2441-2449.
Twohy, C. H.; Austin, P. H.; Charlson, R. J. (1989) Chemical consequences of the initial diffusional growth of
cloud droplets: a clean marine case. Tellus Ser. B 4IB: 51-60.
Twomey, S. (1959) The nuclei of natural cloud formation: part II: the supersaturation in natural clouds and the
variation of cloud droplet concentration. Geofis. Pura Appl. 43: 243-249.
U.S. Environmental Protection Agency. (1982) Air quality criteria for particulate matter and sulfur oxides.
Research Triangle Park, NC: Office of Health and Environmental Assessment, Environmental Criteria
and Assessment Office; EPA report no. EPA-600/8-82-029aF-cF. 3v. Available from: NTIS, Springfield,
VA; PB84-156777.
U.S. Environmental Protection Agency. (1986a) Health assessment document for nickel and nickel compounds.
Research Triangle Park, NC: Environmental Criteria and Assessment Office; report no.
EPA/600/8-83/012FF. Available from: NTIS, Springfield, VA; PB86-232212.
U.S. Environmental Protection Agency. (1986b) Air quality criteria for lead. Research Triangle Park, NC: Office
of Health and Environmental Assessment, Environmental Criteria and Assessment Office; EPA report no.
EPA-600/8-83/028aF-dF. 4v. Available from: NTIS, Springfield, VA; PB87-142378.
U.S. Environmental Protection Agency. (1995) Compilation of air pollutant emission factors, v. I: stationary
point and area sources. 5th ed. Research Triangle Park, NC: Office of Air Quality Planning and
Standards; sections 1.1 and 1.2; report no. AP-42.
Uliasz, M. (1993) The atmospheric mesoscale dispersion modeling system. J. Appl. Meteorol. 32: 139-149.
3-238
-------
Valerio, F.; Bottino, P.; Ugolini, D.; Cimberle, M. R.; Tozzi, G. A.; Frigerio, A. (1984) Chemical and
photochemical degradation of polycyclic aromatic hydrocarbons in the atmosphere. Sci. Total Environ.
40: 169-188.
Valsaraj, K. T.; Thoma, G. J.; Reible, D. D.; Thibodeaux, L. J. (1993) On the enrichment of hydrophobic
organic compounds in fog droplets. Atmos. Environ. Part A 27: 203-210.
Van Borm, W. A.; Adams, F. C.; Maenhaut, W. (1989) Characterization of individual particles in the Antwerp
aerosol. Atmos. Environ. 23: 1139-1151.
Vanderpool, R. W.; Lundgren, D. A.; Marple, V. A.; Rubow, K. L. (1987) Cocalibration of four large-particle
impactors. Aerosol Sci. Technol. 7: 177-185.
Van Doren, J. M.; Watson, L. R.; Davidovits, P.; Worsnop, D. R.; Zahniser, M. S.; Kolb, C. E. (1990)
Temperature dependence of the uptake coefficients of HNO3, HC1, and N2O5 by water droplets. J. Phys.
Chem. 94: 3265-3272.
Van Grieken, R.; Xhoffer, C. (1992) Microanalysis of individual environmental particles. J. Anal. At. Spectrom.
7: 81-88.
Van Valin, C. C.; Luria, M.; Ray, J. D.; Boatman, J. F. (1990) Hydrogen peroxide and ozone over the
northeastern United States in June 1987. J. Geophys. Res. [Atmos.] 95: 5689-5695.
Venkataraman, C.; Friedlander, S. K. (1994) Size distributions of polycyclic aromatic hydrocarbons and
elemental carbon. 2. Ambient measurements and effects of atmospheric processes. Environ. Sci. Technol.
28: 563-572.
Venkataraman, C.; Hildemann, L. M. (1994) Factors affecting the distribution of primary semivolatile organic
compounds of urban aerosol particles. Environ. Sci. Technol.: submitted.
Venkataraman, C.; Lyons, J. M.; Friedlander, S. K. (1994) Size distributions of polycyclic aromatic
hydrocarbons and elemental carbon. 1. Sampling, measurement methods, and source characterization.
Environ. Sci. Technol. 28: 555-562.
Wagman, J.; Lee, R. E., Jr.; Axt, C. J. (1967) Influence of some atmospheric variables on the concentration and
particle size distribution of sulfate in urban air. Atmos. Environ. 1: 479-489.
Walcek, C. J.; Stockwell, W. R.; Chang, J. S. (1990) Theoretical estimates of the dynamic, radiative and
chemical effects of clouds on tropospheric trace gases. Atmos. Res. 25: 53-69.
Waldman, J. M.; Lioy, P. J.; Thurston, G. D.; Lippmann, M. (1990) Spatial and temporal patterns in
summertime sulfate aerosol acidity and neutralization within a metropolitan area. Atmos. Environ. Part B
24: 115-126.
Waldman, J. M.; Koutrakis, P.; Allen, G. A.; Thurston, G. D.; Burton, R. M.; Wilson, W. E. (1995) Human
exposures to particle strong acidity. In: Phalen, R. F.; Bates, D. V., eds. Proceedings of the colloquium
on paniculate air pollution and human mortality and morbidity, part II; January 1994; Irvine, CA.
Inhalation Toxicol. 7: 657-669.
Wall, S. M.; John, W.; Ondo, J. L. (1988) Measurement of aerosol size distributions for nitrate and major ionic
species. Atmos. Environ. 22: 1649-1656.
Wang, C.; Chang, J. S. (1993) A three-dimensional numerical model of cloud dynamics, microphysics, and
chemistry: 4. cloud chemistry and precipitation chemistry. J. Geophys. Res. [Atmos.] 98: 16,799-16,808.
3-239
-------
Wang, H.-C.; John, W. (1987) Comparative bounce properties of particle materials. Aerosol Sci. Technol.
7: 285-299.
Wang, H.-C.; John, W. (1988) Characteristics of the Berner impactor for sampling inorganic ions. Aerosol Sci.
Technol. 8: 157-172.
Wang, S.-C.; Paulson, S. E.; Grosjean, D.; Flagan, R. C.; Seinfeld, J. H. (1992a) Aerosol formation and
growth in atmospheric organic/NOx systems—I. Outdoor smog chamber studies of C7- and
Cg- hydrocarbons. Atmos. Environ. Part A 26: 403-420.
Wang, S.-C.; Flagan, R. C.; Seinfeld, J. H. (1992b) Aerosol formation and growth in atmospheric organic/NOx
systems—II. aerosol dynamics. Atmos. Environ. Part A 26: 421-434.
Warner, T. T. (1981) Verification of a three-dimensional transport model using tetroon data from Project
STATE. Atmos. Environ. 15: 2219-2222.
Warren, R. S.; Birch, P. (1987) Heavy metal levels in atmospheric particulates, roadside dust and soil along a
major urban highway. Sci. Total Environ. 59: 253-256.
Watson, J. G.; Chow, J. C. (1992) Data bases for PM10 and PM2 5 chemical compositions and source profiles.
Transactions AWMA 1: 61-91.
Watson, J. G.; Chow, J. C.; Lurmann, F. W.; Musarra, S. P. (1994a) Ammonium nitrate, nitric acid, and
ammonia equilibrium in wintertime Phoenix, Arizona. Air Waste 44: 405-412.
Watson, J. G.; Chow, J. C.; Lu, Z.; Fujita, E. M.; Lowenthal, D. H.; Lawson, D. R.; Ashbaugh, L. L.
(1994b) Chemical mass balance source apportionment of PM10 during the Southern California Air Quality
Study. Aerosol Sci. Technol. 21: 1-36.
Weathers, K. C.; Likens, G. E.; Bormann, F. H.; Bicknell, S. H.; Bormann, B. T.; Daube, B. C., Jr.; Eaton,
J. S.; Galloway, J. N.; Keene, W. C.; Kimball, K. D.; McDowell, W. H.; Siccama, T. G.; Smiley, D.;
Tarrant, R. A. (1988) Cloudwater chemistry from ten sites in North America. Environ. Sci. Technol.
22: 1018-1026.
Weber, R. J.; McMurry, P. H.; Eisele, F. L.; Tanner, D. J. (1995) Measurement of expected nucleation
precursor species and 5 to 500 nm diameter particles at Mauna Loa, Hawaii. J. Atmos. Sci.
52: 2242-2257.
Wesely, M. L.; Hicks, B. B. (1977) Some factors that affect the deposition rates of sulfur dioxide and similar
gases on vegetation. J. Air Pollut. Control Assoc. 27: 1110-1116.
Wexler, A. S.; Seinfeld, J. H. (1990) The distribution of ammonium salts among a size and composition
dispersed aerosol. Atmos. Environ. Part A 24: 1231-1246.
Wexler, A. S.; Seinfeld, J. H. (1992) Analysis of aerosol ammonium nitrate: departures from equilibrium during
SCAQS. Atmos. Environ. Part A 26: 579-591.
Wexler, A. S.; Eldering, A.; Pandis, S. N.; Cass, G. R.; Seinfeld, J. H.; Moon, K. C.; Hering, S. (1992)
Modeling aerosol processes and visibility based on the SCAQS data. Final report. Sacramento, CA:
California Air Resources Board; contract no. A932-054.
Whitby, K. T. (1978) The physical characteristics of sulfur aerosols. Atmos. Environ. 12: 135-159.
Whitby, K. T. (1980) Aerosol formation in urban plumes. Ann. N. Y. Acad. Sci. 338: 258-275.
3-240
-------
Whitby, K. T. (1984) Physical and optical behavior of sulfate-nitrate aerosols in equilibrium with atmospheric
water vapor, ammonia and nitric acid. In: Ruhnke, L. H.; Deepak, A., eds. Hygroscopic aerosols:
technical proceedings of the workshop on hygroscopic aerosols in the planetary boundary layer; April
1982; Vail, CO. Hampton, VA: A. Deepak Publishing; pp. 45-63.
Whitby, K. T.; Sverdrup, G. M. (1980) California aerosols: their physical and chemical characteristics. In: Hidy,
G. M.; Mueller, P. K.; Grosjean, D.; Appel, B. R.; Wesolowski, J. J., eds. The character and origins
of smog aerosols: a digest of results from the California Aerosol Characterization Experiment (ACHEX).
New York, NY: John Wiley & Sons, Inc.; pp. 477-517. (Advances in environmental science and
technology: v. 9).
Whitby, K. T.; Husar, R. B.; Liu, B. Y. H. (1972) The aerosol size distribution of Los Angeles smog.
J. Colloid Interface Sci. 39: 177-204.
Whitby, K. T.; Charlson, R. E.; Wilson, W. E.; Stevens, R. K. (1974) The size of suspended particle matter in
air. Science (Washington, DC) 183: 1098-1099.
White, W. H.; Macias, E. S. (1989) Carbonaceous particles and regional haze in the western United States.
Aerosol Sci. Technol. 10: 111-117.
White, W. H.; Anderson, J. A.; Blumenthal, D. L.; Husar, R. B.; Gillani, N. V.; Husar, J. D.; Wilson,
W. E., Jr. (1976) Formation and transport of secondary air pollutants: ozone and aerosols in the
St. Louis urban plume. Science (Washington, DC) 194: 187-189.
White, W. H.; Patterson, D. E.; Wilson, W. E. (1983) Urban exports to the nonurban troposphere: results from
Project MISTT. J. Geophys. Res. 88: 10,745-10,752.
White, W. H.; Seigneur, C.; Heinold, D. W.; Eltgroth, M. W.; Richards, L. W.; Roberts, P. T.; Bhardwaja,
P. S.; Conner, W. D.; Wilson, W. E., Jr. (1985) Predicting the visibility of chimney plumes:
an intercomparison of four models with observations at a well-controlled power plant. Atmos. Environ.
19: 515-528.
Wiedensohler, A.; Aalto, P.; Covert, D.; Heintzenberg, J.; McMurry, P. H. (1994) Intercomparison of four
methods to determine size distributions of low-concentration (~ 100 cm'3), ultrafine aerosols
(3 < Dp < 10 nm) with illustrative data from the Artie. Aerosol Sci. Technol. 21: 95-109.
Willeke, K.; Whitby, K. T. (1975) Atmosperic aerosols: size distribution interpretation. J. Air Pollut. Control
Assoc. 25: 529-534.
Willetts, B. (1992) [Personal communication]. Aberdeen, Scotland: University of Aberdeen.
Williams, D. J.; Carras, J. N.; Milne, J. W.; Heggie, A. C. (1981) The oxidation and long-range transport of
sulphur dioxide in a remote region. Atmos. Environ. 15: 2255-2262.
Wilson, W. E. (1978) Sulfates in the atmosphere: a progress report on project MISTT. Atmos. Environ.
12: 537-547.
Wilson, W. E., Jr. (1981) Sulfate formation in point source plumes: a review of recent field studies. Atmos.
Environ. 15: 2573-2581.
Wilson, J. C.; McMurry, P. H. (1981) Studies of aerosol formation in power plant plumes—II. secondary
aerosol formation in the Navajo generating station plume. In: White, W. H.; Moore, D. J.; Lodge, J. P.,
eds. Plumes and visibility: measurements and model components: proceedings of the symposium;
November 1980; Grand Canyon National Park, AZ. Atmos. Environ. 15: 2329-2339.
3-241
-------
Wilson, W. E.; Suh, H. H. (1996) Fine and coarse particles: concentration relationships relevant to
epidemiological studies. J. Air Waste Manage. Assoc.: accepted.
Wilson, W. E.; Spiller, L. L.; Ellestad, T. G.; Lamothe, P. J.; Dzubay, T. G.; Stevens, R. K.; Macias, E. S.;
Fletcher, R. A.; Husar, J. D.; Husar, R. B.; Whitby, K. T.; Kittelson, D. B.; Cantrell, B. K. (1977)
General Motors sulfate dispersion experiment: summary of EPA measurements. J. Air Pollut. Control
Assoc. 27:46-51.
Wilson, J. C.; Gupta, A.; Whitby, K. T.; Wilson, W. E. (1988) Measured aerosol light scattering coefficients
compared with values calculated from EAA and optical particle counter measurements: improving the
utility of the comparison. Atmos. Environ. 22: 789-793.
Winklmayr, W.; Wang, H.-C.; John, W. (1990) Adaptation of the Twomey algorithm to the inversion of cascade
impactor data. Aerosol Sci. Technol. 13: 322-331.
Wolff, G. T. (1981) Paniculate elemental carbon in the atmosphere. J. Air Pollut. Control Assoc. 31: 935-938.
Wolff, G. T.; Korsog, P. E. (1985) Estimates of the contributions of sources to inhalable paniculate
concentrations in Detroit. Atmos. Environ. 19: 1399-1409.
Wolff, G. T.; Lioy, P. J.; Wight, G. D.; Meyers, R. E.; Cederwall, R. T. (1977) An investigation of long-range
transport of ozone across the midwestern and eastern United States. Atmos. Environ. 11: 797-802.
Wolff, G. T.; Groblicki, P. J.; Cadle, S. H.; Countess, R. J. (1982) Paniculate carbon at various locations in the
United States. In: Wolff, G. T.; Klimsch, R. L., eds. Paniculate carbon: atmospheric life cycle. New
York, NY: Plenum Press; pp. 297-315.
Wolff, G. T.; Ruthkosky, M. S.; Stroup, D. P.; Korsog, P. E. (1991) A characterization of the principal PM-10
species in Claremont (summer) and Long Beach (fall) during SCAQS. Atmos. Environ. Part A
25: 2173-2186.
Wu, P.-M.; Okada, K. (1994) Nature of coarse nitrate particles in the atmosphere—a single particle approach.
Atmos. Environ. 28: 2053-2060.
Yamartino, R. J.; Scire, J. S.; Carmichael, G. R.; Chang, Y. S. (1992) The CALGRID mesoscale
photochemical grid model—I. Model formulation. Atmos. Environ. Part A 26: 1493-1512.
Yamasaki, H.; Kuwata, K.; Miyamoto, H. (1982) Effects of ambient temperature on aspects of airborne
polycyclic aromatic hydrocarbons. Environ. Sci. Technol. 16: 189-194.
Zafiriou, O. C.; Gagosian, R. B.; Peltzer, E. T.; Alford, J. B.; Loder, T. (1985) Air-to-sea fluxes of lipids at
Enewetak Atoll. J. Geophys. Res. [Atmos.] 90: 2409-2423.
Zhang, X.; McMurry, P. H. (1991) Theoretical analysis of evaporative losses of adsorbed or absorbed species
during atmospheric aerosol sampling. Environ. Sci. Technol. 25: 456-469.
Zhang, S.-H.; Shaw, M.; Seinfeld, J. H.; Flagan, R. C. (1992) Photochemical aerosol formation from a-pinene
and j3-pinene. J. Geophys. Res. [Atmos.] 97: 20,717-20,729.
Zhang, X. Q.; McMurry, P. H.; Hering, S. V.; Casuccio, G. S. (1993) Mixing characteristics and water content
of submicron aerosols measured in Los Angeles and at the Grand Canyon. Atmos. Environ. Part A
27: 1593-1607.
3-242
-------
Zhang, J.; Wilson, W. E.; Lioy, P. J. (1994) Indoor air chemistry: formation of organic acids and aldehydes.
Environ. Sci. Technol. 28: 1975-1982.
Zimmerman, P. R. (1979) Testing of hydrocarbon emissions from vegetation, leaf litter and aquatic surfaces, and
development of a methodology for compiling biogenic emission inventories: final report. Research
Triangle Park, NC: U.S. Environmental Protection Agency, Office of Air Quality Planning and
Standards; EPA report no. EPA-450/4-79-004. Available from: NTIS, Springfield, VA; PB-296070.
Zwozdziak, J. W.; Zwozdziak, A. B. (1990) Sulphate aerosol production in the upper parts of the Sudety Range,
Poland. J. Aerosol Sci. 21(suppl. 1): S369-S372.
3-243
-------
4. SAMPLING AND ANALYSIS METHODS FOR
PARTICULATE MATTER AND ACID DEPOSITION
4.1 INTRODUCTION
Assessment of health risks associated with airborne aerosols implies that measurements
be made defining the aerosol characteristics, concentrations and exposures that contribute to,
or simply correlate with, adverse health effects. The proper selection of an aerosol sampling
or analysis methodology to accomplish such measurements requires that rationales be applied
that consider how the resulting data will be used and interpreted, in addition to the data
quality required. As an example, treatment of a sample to remove particle-associated liquid
water, either by heating the sample during the collection process or by equilibrating the
sample at a low relative humidity subsequent to collection, may lead to changes in the
character of the collected particles, relative to the dispersed particles, in addition to the
removal of water (e.g. Meyer et al., 1995). Similarly, integrated collection of acidic fine
aerosols, without selectively removing the larger, more basic particles, will cause
neutralization (i.e., modification) of the sample on the substrate (Stevens et al., 1978). The
same logic applies to the selective removal of gas phase components during sampling that
might react with the deposited aerosol sample, in a manner inconsistent with naturally
occurring transformation processes. The assumption that fixed-location measurements are
representative of inhalation exposure implies that the effects of local spatial and temporal
gradients are understood and appropriately applied to the sampler siting criteria (Spengler
et al., 1994). Development of relationships between aerosol characteristics and health or
ecological responses requires that the aerosol sampling and analysis processes are truly
representative and adequately defined.
The application of sampling and analytical systems for aerosols must recognize that
particles exist modally as size distributions generated by distinctively different source
categories and having distinctly different chemistries, as discussed in Chapter 3. Two
important reasons for making size-specific aerosol measurements are (a) to relate the in situ
aerosol character to the potential deposition sites, and thus toxicity, of the respiratory system,
and (b) separation of the size distribution modes to identify sources, transformation processes
4-1
-------
or aerosol chemistry. The interpretation of particle size must be made based on the diameter
definition inherent in the measurement process. Since the respiratory system classifies
particles of unknown shapes and densities based on aerodynamic diameter, elucidation of
aerosol relationships with health responses requires that sampling techniques either
incorporate inertial aerodynamic sizers or provide mechanisms to accurately convert the
measured diameters (e.g., optical) to an aerodynamic basis. All particle diameters described
in this chapter are aerodynamic, unless otherwise specified.
Friedlander (1977) provided the descriptive matrix shown in Figure 4-1 for placing
measurement techniques that define aerosol characteristics into perspective, in terms of their
particle sizing capabilities, resolution times and chemical identification attributes. This
approach defined these characteristics by resolution (single particle or greater), discretizing
ability, and averaging process. The author notes that the "perfect" aerosol sampler would
characterize particle size with "perfect" resolution, determine the chemistry of each particle
"perfectly", and operate in real-time with no "lumping" of classes. These characteristics
could be amended in "real-world" terms by suggesting that the "perfect" sampler would also
have minimal cost and operator intervention. Also, if the aerosol measurement design goal is
to mimick the respiratory system, physiological averaging characteristics must be considered.
Size-specific, integrated aerosol measurements have improved significantly and their
capabilities are better characterized since the 1987 PM10 NAAQS, but a "perfect" aerosol
sampling system has not been devised. As discussed below, the methodologies required to
adequately define the performance specifications of aerosol samplers have yet to be devised.
Many recent developmental efforts in aerosol measurement technologies have addressed
the need to perfect the chemical characterization of reactive or volatile species collected on
filtration substrates (e.g., Lamb et al., 1980; Koutrakis et al., 1988). Some of the most
significant recent advances in aerosol measurement technologies have come in the form of
analysis system "protocols", rather than individual pieces of hardware. Recognizing that
there is no single "perfect" sampler, these protocols attempt to merge several aerosol
sampling and analysis technologies into an adaptable and analytically versatile system.
System attributes typically include one or more size-specific aerosol inlets, subsequent
fractionators to separate the fine and coarse particle modes, and denuders and/or sequential
filter packs to selectively account for reactive gas phase species. Examples include EPA's
4-2
-------
Instrument
Resolution
Size
Time Chemical
Composition
Quantity
Measured
(Integrand x N^1)
Perfect Single
Particle Counter
Analyzer
g
Optical Single
Particle Counter
Electrical
Mobility
Analyzer
[V2[gdn=dv
Condensation
Nuclei
Counter
Jg dv dnj - 1
Impactor
dndv
Impactor
Chemical
Analyzer
9 HJ dnjdv
Whole Sample
Chemical Analyzer
{ {gnj
Key:
<0 Resolution of single particle level
Discretizing process
/ Averaging process
Figure 4-1. Characteristics of aerosol measurement instruments.
Source: Friedlander (1977).
Versatile Air Pollution Sampler (VAPS) (Conner et al., 1993), the Southern California Air
Quality Study (SCAQS) sampler (Fitz et al., 1989) and the Interagency Monitoring of
PROtected Visual Environments (IMPROVE) sampler (Malm et al., 1994).
Recognizing that personal exposure concentrations for aerosols may differ from
classical outdoor fixed-location measurements has produced much smaller and less obtrusive
4-3
-------
samplers using the same sizing techniques for application indoors, or even to be worn on the
body during normal activities. Miniaturization of aerosol separators stretches the limits of
current technologies to maintain required sampling precisions and accuracies. One of the
most significant limitations imposed by the low flowrates inherent in personal exposure
samplers is the extremely small sample size available for chemical analysis.
This chapter briefly describes the technical capabilities and limitations of aerosol
sampling and analytical procedures in Sections 4.2 and 4.3, respectively, focusing on
(1) those that were used to collect data supporting other sections in this document, (2) those
supporting the existing PM10, TSP1 and Pb regulations, (3) those that were used to support
health and welfare response studies, (4) those having application in development of a possible
fine particle standard, and (5) discussing the attributes of several new technologies. The
discussion of aerosol separation technologies is divided between (a) devices used to mimic
the larger particle (> 10 /xm) penetration rationales for the upper airways, and (b) those
devices generally used to mimic smaller particle penetration (< 10 /xm) to the thoracic
regions. These device descriptions are followed by sampling considerations for their
applications. The applications of performance specifications to define these measurement
systems for regulatory purposes are discussed, along with a number of critical observations
suggesting that the current specification process does not always ensure the accuracy or
representativeness necessary in the field. The EPA program designating PM10 reference and
equivalent sampling systems is then briefly described, along with a current list of designated
devices. Selected measurement systems used to provide more detailed characterization of
aerosol properties for research studies are discussed, with a focus on the determination of
particle size distributions.
Aerosol sampling systems for specialty applications, including automated samplers,
personal exposure samplers and the sampling systems used in aerosol apportionment studies
are briefly described. The chapter then presents a short section (4.4) on sampling and
analysis of bioaerosols Nevalainen et al. (1992). Also, Nevalainen et al. (1993), and Qian
et al. (1995) provide excellent summaries of the principles involved in bioaerosol sampling
and the most commonly used techniques.
'Subsequent identifications in this chapter: "TSP" for Total Suspended Particulates by high volume sampler,
"PM10" for the fraction less than 10 /nm, "fine" for the fraction less than 2.5 /mi.
4-4
-------
4.2 SAMPLING FOR PARTICULATE MATTER
4.2.1 Background
The development of relationships between airborne paniculate matter and human or
ecological effects requires that the aerosol2 measurement process be accurately, precisely
and representatively defined. Improvements in sampling methodologies since the 1982 Air
Quality Criteria Document for Paniculate Matter and Sulfur Oxides (U.S. Environmental
Protection Agency, 1982)3 was released, have resulted from improved sensor technologies,
and more importantly, a better understanding of the aerosol character in situ4. Additionally,
health studies and atmospheric chemistry research in the past decade have focused more
closely on smaller, better-defined aerosol size fractions of known integrity, collected
specifically for subsequent chemical characterization.
The system of aerosols in ambient air is a continuum of particle sizes in a gas phase
carrier formed as the summation of all size distributions produced by individual sources and
secondary transformations. Portions of the composite distributions are often found to exist
lognormally (Baron and Willeke, 1993; see also Chapter 3, Section 3.3.3). Aerosol systems
also exist as a continuum of particle "ages", resulting from loss and transformation
mechanisms such as agglomeration, settling, volatilization, gas-particle reaction, and rain-out
affecting freshly generated particles. The chemical compositions of the various portions
(modes) of the aerosol size distribution are more discreet, and sampling strategies must
consider a specific range of sizes for a given chemical class. The constantly changing
character of the atmosphere (or of indoor air) places a premium on sampling strategies both
to collect representative aerosol samples from the air and to protect their integrity until
analyzed.
The 1982 Criteria Document provided basic descriptions of many aerosol measurement
techniques still used today. These included both older optically-based techniques, such as
"Black Smoke" or "British Smoke" (BS) or "coefficient of haze" (COH) methods and certain
Consistent with recent literature (e.g., see Willeke and Baron, 1993), the term "aerosol" will refer to the continuum
of suspended particles and the carrier gas.
3Referred to in the text subsequently as an entity as the "1982 Criteria Document".
4The in situ characteristics of particles in the ambient air medium can be substantially modified by the sampling
and analysis processes. For example, a particle counter which draws particles through a restrictive or heated inlet
before they reach the sensing volume, may perceive the particle properties (e.g. scattering coefficients, size
distributions) differently from those that existed in the ambient.
4-5
-------
other now lesser used gravimetric methods, that are only briefly mentioned here but not
described in detail. Instead the reader is referred to the earlier Criteria Document (U.S.
Environmental Protection Agency, 1982) for more information on those methods not
extensively covered here. This section mainly highlights the more recent peer-reviewed
research on aerosol measurement technologies since 1982 and notes salient points that should
be considered in their application. The aerosol sampling section is not intended to be an
exhaustive treatise, but is structured to highlight important concepts and technologies relevant
to the development of aerosol measurement/response relationships, or supporting existing and
potential EPA aerosol regulations. Ancillary reference texts, describing basic aerosol
mechanics (e.g., Hinds, 1982; Reist, 1984) and applied aerosol mechanics and measurements
(e.g., Willeke and Baron, 1993; Hering, 1989; Lundgren et al., 1979; Liu, 1976) should be
consulted for more fundamental details.
4.2.2 Large Particle Separators
4.2.2.1 Cutpoint Considerations
The collection of an aerosol sample is defined by the penetration characteristics of the
inlet, overlaid on the existing in situ size distribution. Cooper and Guttrich (1981) describe
this process mathematically, and they estimate the influences of non-ideal penetration
characteristics. Miller et al. (1979) described the considerations for the possible selection of
15 ju,m (designated "inhalable") as a standard for size-selective particle sampling with upper
airway respiratory deposition as the primary consideration. The selection of the most
appropriate aerodynamic criteria for ambient aerosol sampling was only partially resolved by
the 1987 EPA designation (U.S. Environmental Protection Agency, 1987) of a 10 /xm
(PM 10) cutpoint. The "ideal" PM10 inlet was referenced to the thoracic penetration model
of Lippmann and Chan (1979). Ogden (1992) noted that the standardization for aerosol
cutpoint sizes and separation sharpness is still under debate across settings (ambient air,
occupational) and across national and international governmental entities. As shown in
Figure 4-2 (from Jensen and O'Brien, 1993), the international conventions for cutpoints have
been roughly categorized as Respirable, Thoracic and Inhalable (previously, Inspirable).
These cutpoints are related to the penetration, respectively, to the gas exchange region of the
lung, the larynx, and the nasal/oral plane. The influences of physiological variables on these
4-6
-------
e
I
01
1
100
80
60
40
20
0/100
80
60
40
20
0/100
80
60
40
20
-Inhalable
• ACGIH(1994)
• Proposed ISO (1992)
-ISO (1983)
ACGIH (1994)
Proposed 150(1992)
180(1983)
-Respirable
•ACGIH (1994)
1 Proposed ISO(1992)
•ISO (1983)
' BMRC (1959)
0.1
1
10
100
Aerodynamic Diameter (urn)
Figure 4-2. American Conference of Governmental Industrial Hygienists (ACGIH),
British Medical Research Council (BMRC), and International Organization
for Standardization (ISO) size-selective sampling criteria.
Source: Jensen and O'Brien (1993).
4-7
-------
cutpoints are described by Soderholm (1989). The British Standard EN 481 (CEN [European
Committee for Standardization], 1993) describes size fraction definitions for workplace
aerosol sampling, and identifies inhalable "conventions" relative to thoracic, respirable,
extra-thoracic and tracheobronchial penetration (but not necessarily deposition) hi the
respiratory system. They define a thoracic cumulative lognormal distribution with a median
of 11.64 /mi and a geometric standard deviation of 1.5, such that 50% of airborne particles
with Da = 10 /*m are in the thoracic region. The American Conference of Governmental
and Industrial Hygienists (ACGIH, 1994) also adopted these convention definitions. Owen
et al. (1992) provides an extensive list of the outdoor and indoor particles by type and source
category that are found in or overlap these ranges. Willeke et al. (1992) describe the
sampling efficiencies and test procedures for bioaerosol monitors.
The concept of using an inlet or separator that has the same sampling (penetration)
characteristics as portions of the respiratory system has been discussed by a number of
researchers, including Marple and Rubow (1976), Lippmann and Chan (1979), Vincent and
Mark (1981), Soderholm (1989), Liden and Kenny (1991) and John and Wall (1983). They
describe sampler design considerations for matching penetration models for respirable,
thoracic and inhalable fractions that have been proposed by a number of governing bodies.
Since all models proposed for the same fraction do not necessarily coincide, given the
variability and differences in interpretation of respiratory system data, Soderholm (1989)
proposed compromise conventions for each fraction. Watson et al. (1983), Wedding and
Carney (1983), and van der Meulen (1986) mathematically evaluated the influences of inlet
design parameters on collection performance relative to proposed sampling criteria. These
analyses suggested that factors such as extremes in wind speed and coarse particle
concentration could pose significant problems in meeting performance specifications.
An analysis of the human head as an aerosol sampler was discussed by Ogden and
Birkett (1977), who noted that breathing is an anisokinetic sampling process. The concept of
a "total inhalable" fraction that passes the oral and nasal entry planes was refined by Mark
and Vincent (1986) with the development of a personal aerosol sampling inlet that mimicked
this penetration as a function of aerodynamic size. The inlet was designated the IOM for the
Institute for Occupational Medicine in Edinburgh, Scotland, where it was developed with the
cutpoint as a function of wind speed and aerosol type shown in Figure 4-3. The total
4-8
-------
t-
i9n
i £\j
100
^~***
t, 80
fr
c
'o _
;= 60
^ w
LU
0)
"I 40
CO
CO
20
n
w
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
;
— 2 / —
O . Qmls /
VT- A o \ /w
i'"*l*'*'« ^V /
" A \ -;
-•„ ^ \ , r W
• ' ^ £ \ / T
O _ 4m/s ^ ^"
^*'*'*i» ^\. »"
v ^% „, • \N^ •/' 4.
^— 1IB'%'"'*"'^^ ^^_^ >v*
yK"\ BB l'*'»,|^l""'"'"'"«l"' ^A ^B
^ ...« ^\ ™"
V n /
° ^ / A 4 -
n 1m/s ^
O
+ ?
, , , | , , i i i i i i
1 10 10
Aerodynamic Diameter (urn)
0
Inhalable
Convention
Solid Particles
Aloxite
• 1m/s
A 2m/s
• 4m/s
^ 6m/s
V 9m/s
Sodium Fluorescein
O lm/s
A 2m/s
n 4m/s
O 6m/s
V 9m/s
Droplets
nFH^
L/cno
O 6m/s
+ 9m/s
Figure 4-3. Sampling efficiency of IOM ambient inhalable aerosol sampler for three different types of test aerosol.
Source: Mark et al. (1992).
-------
inhalable approach has been adopted by the International Standards Organization (ISO,
1993), European Committee for Standardization (CEN, 1993) and by the American
Conference on Governmental and Industrial Hygienists (ACGIH, 1985; ACGIH, 1994) for
workplace aerosol sampling. The ACGIH (1985) reference provides a detailed rationale for
the selection of various cut sizes. The total inhalable fraction using the IOM inlet was
selected for a total human exposure study (Pellizzari et al., 1995) to provide the total body
burden for metals (lead and arsenic) by the air exposure route.
Similar thoracic penetration conventions have been adopted by ISO, CEN, ACGIH and
EPA, each with D50 values of 10.0 /xm (ISO, 1993; CEN, 1993; ACGIH, 1994; and
U.S. EPA, 1987). The EPA definition was based primarily on the data of Chan and
Lippmann (1980). The exact shapes of each efficiency curve were mathematically defined by
Soderholm (1989) and are slightly different for each convention.
The respirable conventions have had D50 values ranging from 3.5 to 5.0 /*m, but a
compromise convention has been accepted internationally by several organizations. It has a
D50 of 4.0 fj.ro. (Soderholm, 1989). ISO (1993) calls this the "healthy adult respirable
convention". Liden and Kenny (1992) discuss the performance of currently available
respirable samplers. EPA's emphasis on the 2.5 /im cutpoint was more closely associated
with separating the fine and coarse atmospheric aerosol modes, rather than mimicking a
respiratory deposition convention. The exact location of this minimum in the atmospheric
size distribution is currently under debate. It is noteworthy that ISO (1993) defines a "high
risk" respirable convention which is claimed to relate to the deposition of particles in the
lungs of children and adults with certain lung diseases. The respirable "high risk"
convention has a D50 of 2.4 /mi, so it could be identified closely with the EPA samplers
having a cutpoint of 2.5 pm.
The PMjo size fraction has become nearly universal for ambient air sampling in the
U.S., with the implementation of the 1987 standard (U.S. Environmental Protection Agency,
1987). The setting of performance specifications, even with their limitations, has provided a
more consistent PM10 data base, with better definition of the data quality. As additional
information becomes available on the sources of biases in aerosol collection methodologies,
further characterizations of older methods may be needed to better define the quality of
collected data. Factors that affect bias, and especially representativeness, should be
4-10
-------
identified and their influences determined as a function of particle size. As examples, Appel
et al. (1984) studied gas/particle and particle/substrate interactions for sulfates and nitrates,
volatilization losses of nitrates were reported by Zhang and McMurry (1992), while losses
for organics were reported by Eatough et al. (1993). Because of the prevalence of these
chemical classes in the fine fraction, the effect of the losses on larger fractions (e.g., PM10,
TSP) would be proportionately smaller and can now be estimated. The losses of larger
particles through aerosol inlet sampling lines (Anand et al., 1992) has a substantial influence
on PM10 coarse fraction samples. This was demonstrated for the British smoke shade
sampler inlet line by McFarland et al. (1982). Inlet losses would be expected to play only a
minor role in sampling the fine particle fraction (<2.5 /*m). Biases in concentration for
samplers with large particle cutpoints are exacerbated by the large amount of mass present
near the cutpoints and the steep slope of mass versus aerodynamic size. Thus, small changes
in cutpoint can give significant and hard-to-predict mass biases.
4.2.2.2 Total Suspended Particulates
The TSP high volume sampler has remained essentially unchanged since the sampler's
identification as a reference ambient sampling device in 1971 (Federal Register, 1971). The
sampling performance (e.g., wind speed and direction sensitivity) was described in detail in
the 1982 Criteria Document, and the TSP sampler was shown by McFarland and Ortiz
(1979) to collect particles with aerodynamic diameters exceeding 40 jum. More importantly,
its particle collection characteristics were shown to be significantly sensitive to wind speed
(2 to 24 km/h) and wind direction. Only minor technical updates have been incorporated in
commercially available units, such as in the types of available sequence and elapsed timers
(mechanical, electronic) and in the types of flow controllers (mass flow, volumetric). Also,
cassettes are now available that protect the fragile glass or quartz fiber filters during handling
and transport. Size fractionating inlets for smaller size cutpoints (e.g., 2.5, 6.0 and
10.0 (jLm) and cascade impactors have been developed. Similar to the Pb strategy of using
the TSP high volume sampler to collect a "total" sample, asbestos sampling utilizes an
aerosol inlet that attempts to collect a "total" sample, by using an open-faced filter holder
with a conductive inlet cowling. Baron (1993) discusses the potential anisokinetic problems
4-11
-------
that can occur with such a simple inlet, but notes that the small Stokes number for typical
asbestos fibers provides efficiencies close to 100%.
4.2.2.3 Total Inhalable Particles
The toxicity of contaminants such as lead poses health concerns as total body burdens,
suggesting that penetration of all aerosols inhaled into the nose and mouth must be
considered, rather than just thoracic penetration. The TSP sampler for atmospheric lead is
thought (Federal Register, 1978) to more closely capture this larger size fraction than would
a PM10 counterpart, but was not specifically designed to mimic inhalability. The ISO
"inhalable" draft sampling convention (ISO, 1993) is intended to apply to such situations,
defining collection of all particles passing the oral/nasal entry planes. The total inhalable
cutpoint is currently available only in a personal sampler version. Mark and Vincent (1986)
described the development of an inhalable particle inlet (designated as the IOM) meeting the
ISO (1992), CEN (1993) and ACGIH (1994) conventions for inspirable dust. This inlet was
improved by Upton et al. (1992) and tested by Mark et al. (1992) and shown to satisfy the
ACGIH criteria for wind speeds of 0.5 and 1.0 m/s.
4.2.2.4 PM10
The penetration of ambient aerosols through a size-fractionating inlet to the collection
substrate must be characterized over the ranges of operating conditions (meteorology and
aerosol types) that may be encountered. The range of conditions currently required by EPA
PM10 performance specifications was given in U.S. Environmental Protection Agency
(1987). Ranade et al. (1990) and John and Wall (1983) described the required testing, which
specifies a controlled flow wind tunnel, monodispersed fluorescently-tagged wet and dry
aerosols, and an isokinetic nozzle aerosol sampling reference to determine aerodynamic
penetration through candidate PM10 inlets.
Marple and Rubow (1976) placed inertial impactors on the inlet of an optical particle
counter to provide an aerodynamic calibration of the optical readout for non-ideal particles.
Buettner (1990) noted that an aerodynamically calibrated optical particle counter could in turn
be used to test the sampling performance of other devices only if the particle shape and
refractive index of the test aerosol were consistent between calibrations. Maynard (1993)
4-12
-------
used this approach to determine the penetration of a respirable cyclone to polydisperse glass
micro-spheres, using the TSI, Inc. Aerodynamic Particle Sizer (APS). John and Wall (1983)
noted that inaccurate inlet sizing results may be obtained using poly-disperse AC test dust, as
the result of agglomeration. Kenny and Lid6n (1991) used the APS to characterize personal
sampler inlets and observed that, on theoretical grounds, calm air sampling would be
expected to provide unity aspiration efficiencies for particles below about 8 /mi. Tufto and
Willeke (1982) used an optical particle counter (OPC) to monitor monodisperse aerosols in a
wind tunnel setting to determine the performance of aerosol sampling inlets relative to an
isokinetic nozzle. Yamada (1983) proposed using electron microscopy to determine the size
distributions of polydispersed particles using manual counting techniques before and after a
candidate aerosol separator. Penetration data from this technique were found to be
significantly less precise and more difficult to interpret compared with data for the same
separators using fluorometric methods.
The aerosol cutpoint performance of two PM10 samplers that have met the EPA
performance specifications is illustrated (see Figure 4-4) by the data for the Andersen 321A
and Wedding IP10 high volume sampler inlets at 8 km/h from Ranade et al. (1990). The data
show that the cutpoint requirements, defined as a D50 of 10.0 ptm ± 0.5 /wm and mimicking
a modeled cutpoint sharpness (a ), were met for each of the tested wind speeds. These
&
performance results were verified by repeating the tests in wind tunnels located at two other
research facilities. A diagram (U.S. Environmental Protection Agency, 1992) of the
two-stage Sierra-Andersen PM10 high volume sampler inlet with a design flowrate of
1.13 m3/min is shown in Figure 4-5. The buffer chamber of this inlet serves to dampen the
particle-laden air stream passing through two sets of acceleration nozzles, which deposit
particles larger than PM10 on internal collection surfaces. The PM10 fraction is typically
collected by a glass fiber filter. An oiled impaction shim was incorporated into the first
stage fractionator of the 321A to minimize reentrainment of deposited particles during field
sampling. This modified version (Sierra-Andersen 32IB) was designated as an EPA
reference method for PM10 in 1987. A subsequent single-stage fractionator (Sierra-Andersen
1200) was developed5 and designated as an EPA reference method, with a D50 of 9.5 /mi
and a hinged design to facilitate cleaning and oiling of the oiled impaction shim.
5Graseby-Andersen, Inc., Atlanta, GA.
4-13
-------
Wedding IR0
Model 321A
4 5 6 7 8 910 15 20
Aerodynamic Diameter (urn)
Figure 4-4. Liquid particle sampling effectiveness curves with solid particle points
superimposed for the Wedding IP10 (•) and the Andersen Samplers
Model 321A inlets at 8 km/h.
Source: U.S. Environmental Protection Agency (1992).
A diagram of the cyclone-based Wedding6 PM10 high volume sampler inlet (U.S.
Environmental Protection Agency, 1990) with a design flowrate of 1.13 m3/min is shown in
Figure 4-6. This inlet uses an omni-directional cyclone to accelerate the particle-laden air
stream to deposit particles larger than PM10 on an oiled collection surface. Two additional
turns are made to alter the flow into a downward trajectory toward the collection filter.
A brush is used to clean the deposited aerosol from the absorber surface through an access
port. This inlet was designated as an EPA reference method for PM10 in 1987.
6Wedding and Associates, Fort Collins, CO.
4-14
-------
H-'
Ui
Figure 4-5. Two-stage Sierra Andersen PM10 sampler.
Source: U.S. Environmental Protection Agency (1992).
Buffer Chamber
NPL_ Air Flow
Acceleration Nozzle
Impaction Chamber
Acceleration Nozzle
Impaction Chamber
Vent Tubes
Filter Cassette
Filter
Filter Support
Screen
Motor Inlet
-------
/- Maintenance Access Port
£
Vanes
Vane
Assembly
Base
Insect
Screen
Tube Perfect
IUDe Absorber
No-Bounce
Surface
Housing
Deflector
Spacing
Protective
Housing
Aerodynamic
Inlet
Pathway
Aerodynamic Flow
Deflector
Outer Tube
Figure 4-6. Sampling characteristics of two-stage size-selective inlet for liquid aerosols.
Source: U.S. Environmental Protection Agency (1992).
4-16
-------
The aerosol collection performances for 16.67 1pm PM10 inlets for the dichotomous
sampler are described by Wedding et al. (1982) and McFarland and Ortiz (1984) and are
illustrated by the penetration data in Figure 4-7. The variability of the performance as a
function of wind speed for the Andersen 321A PM10 inlet is shown in Figure 4-8 from data
by McFarland et al. (1984). This is a dramatic improvement over the variability shown by
the TSP high volume sampler (McFarland and Ortiz, 1979) for the same wind speed range.
An attempt to simplify the complexity and improve the availability of wind tunnels to test
PM10 inlets was addressed by Teague et al. (1992), who describe a compact tunnel 6 m long
by 1.2 m high that is capable of testing inlets against the EPA PM10 specifications.
Watson and Chow (1993) noted that the EPA PM10 performance specifications allowed
a tolerance range around the D50 that permitted inlets to be undesirably "fine tuned" to
provide a cutpoint on the lower or upper end of the range. Since a significant amount of
mass in the atmospheric aerosol may be associated with particles in the allowable tolerance
range, a "reduction" in reported concentrations could be achieved by simply using a lower
(e.g., 9.6 /Ltm) cutpoint inlet that is still within the acceptable D50 range. The biases
between acceptable samplers have been apparent in the data from field aerosol comparison
studies (e.g., Rodes et al., 1985; Purdue et al., 1986; Thanukos et al., 1992). Most of the
reported biases between samplers were less than 10%, although some differences greater than
30% were reported. The data suggested that the collection efficiency of the high volume
sampler PM10 inlets based on cyclonic separation (Wedding, 1985) were consistently lower,
while those based on low velocity impaction (McFarland et al., 1984) were consistently
higher. Sweitzer (1985) reported results of a field comparison of these two high volume
sampler types at an industrial location and reported average biases of 15%. It was noted that
this amount of bias was unacceptable for compliance monitoring and more stringent
performance requirements should be used. Rodes et al. (1985) observed that the PM10
concentration data from the dichotomous sampler (regardless of the inlet design) gave the
most predictable results.
Wang and John (1988) were critical of the EPA PM10 performance specification on
allowable particle bounce (U.S. Environmental Protection Agency, 1987), stating that the
criteria can lead to a 30% overestimation of mass under worst-case conditions. In a related
paper, John et al. (1991) reported that although reentrainment by air flow alone of particles
4-17
-------
100
80
CO
V)
CD
c
-------
100 -
80
60
c
o
0
c
0 Ar.
0_ 40
20
i 1—i—i—i—i—r
o 2 km/h
A 8 km/h
n 24 km/h
4 6 8 10 20
Aerodynamic Particle Diameter (|im)
40
Figure 4-8. Collection performance variability illustrating the influence of wind speed
for the Andersen 321A PM10 inlet.
Source: McFarland et al. (1984).
(2.2%/gram deposited) and strongly suggested that periodic cleaning and re-oiling should be
required for PM10 inlets. Ozkaynak et al. (1993) observed that immediately after inlets of
4-19
-------
the Wedding (1985) design were cleaned, an underestimation (compared to the dichotomous
sampler) occurred of 14%. This bias was followed by a steady "recovery" period of 2 days,
until the expected performance returned. They also observed a strong influence of diurnal
temperature change on the ratios of concentrations between the Wedding (1985) design
samplers and other PM10 samplers. This influence could not be attributed to a physical
phenomenon.
The EPA PM10 performance specification program should be considered successful
(John and Wall, 1983) in providing consistent aerosol collection results during field
sampling. As noted by Thanukos et al. (1992), the cases of greatest concern were those
where the measured concentrations were near an exceedance level. Wiener et al. (1994)
noted that EPA was scrutinizing the current performance of designated reference and
equivalent sampling methods for PM10 in light of reassessment of the existing standard.
A review of the current PM10 performance requirements and possible amendments of the
existing specifications may be appropriate, given the information base now available.
Laboratory and field testing reported in the literature since 1987 suggest that the EPA
PM10 Federal Reference Method (FRM) specifications and test requirements have not
adequately controlled the differences observed in collocated ambient PM10 sampling. The
most significant performance flaws have combined to produce excessive (up to 60%) mass
concentration biases. These biases apparently resulted from the combined factors of
(1) allowing a cutpoint tolerance (10 ± 0.5 ^im), (2) an inadequate restriction placed on
internal particle bounce, and (3) a degradation of particle separation performance as certain
technology PM10 inlets became soiled. Particle bounce or soiling problems have not been
reported for the PM10 inlets for the dichotomous sampler.
A cutpoint tolerance of ±0.5 /xm was required to account for expected differences
between different wind tunnel laboratories testing the same hardware. The between-sampler
bias from this tolerance limit alone is predictable and should provide PM10 concentration
differences significantly less than ±10% in most cases. Particle bounce allowances are not
as predictable, but design practices (primarily surface coatings with viscous oil, as suggested
by John et al. [1991]) to minimize the penetration caused by bounce and resuspension have
been shown to be very effective when properly serviced. The influences of internal surface
soiling on PM10 inlet performance were not recognized when the FRM was established in
4-20
-------
1987, but were found to have severe consequences for some separation technologies. The
magnitude of biases from soiling is also not readily predicted, but can be ameliorated by not
allowing the inlet to become excessively dirty during operation by routine cleaning prior to
sampling.
Although the EPA test procedures have not been formally amended since 1987, the
manufacturers of the designated PM10 reference methods (see section 4.2.6) have voluntarily
modified their hardware designs and instruction procedures to accommodate particle bounce
and soiling concerns. The SA-321b and SA-321c PM10 inlets were voluntarily withdrawn
from the market by the vendor because of excessive biases attributed to particle bounce. The
manufacturer now sells the SA1200 inlet which provides oiled surfaces to eliminate particle
bounce and access screws to facilitate cleaning. The manufacturer also amended the
instruction manuals to require a routine cleaning schedule. Similarly, the manufacturer for
the Wedding PM10 inlet now provides an access port in the inlet and a cleaning procedure
that can be applied prior to the collection of each sample. Based on our current
understanding of the PM10 sampling process, it could be expected that sampling systems can
be designed and concentration measurements made that are within 10% of the true
concentrations.
4.2.3 Fine Particle Separators
4.2.3.1 Cutpoint Considerations
Although a particle separation at 2.5 pun has been utilized by the dichotomous sampler
for a number of years, the 1987 standard reassessment (U.S. Environmental Protection
Agency, 1987) did not specifically require routine monitoring for fine particles. It has
become apparent (see Chapters 8 and 12) that certain health and ecological responses are
most strongly correlated with fine particles, significantly smaller than 10 jum, and their
related chemistry. Since the mass of a particle is proportional to the cube of its diameter,
larger particles (especially above 10 /im) can totally dominate the mass of PM,0 and TSP
samples. The 2.5 /im cutpoint generally occurs near a minimum in the mass distribution,
minimizing mass concentration differences between samplers with cutpoint biases. The
development of control strategies based on mass concentrations from a smaller cutpoint
4-21
-------
standard must be carefully constructed, especially if large particle interference problems
(e.g., particle bounce) cannot be appropriately minimized.
Practical considerations would be the time and expense required to develop separators
with 1.0 fjtm cutpoints that meet required specifications, conduct validation testing, and
retrofit existing samplers. A virtual impaction "trichotomous" sample was described by
Marple and Olson (1995) that uses a PM10 inlet and separators for both 2.5 and 1.0 /mi
cutpoints. They also noted that technology was not a limiting factor in providing a fine
particle separator. Given the body of data available at 2.5 /mi, a focused effort may prove
practical that defines the characteristics of the particle mass and chemistry between 1.0 and
2.5 /mi. This would add to the technical knowledge base, allow interpretive corrections
between cutpoints to be made, and permit continued sampling at 2.5 /mi with a minimum of
additional resources.
4.2.3.2 Virtual Impactors
The dichotomous sampler utilizes virtual impaction to separate the fine (<2.5 /mi) and
coarse (2.5 to 10 /mi) fractions into two separate flowstreams (see, for example, Novick and
Alvarez, 1987) for collection on filters. The calibration of a nominal 2.5 /mi impactor,
including wall loss data, is shown in Figure 4-9 (from Loo and Cork, 1988). The current
separator design was shown to provide a relatively sharp cutpoint with minimal internal
losses. A virtual impactor has been designed with a 1.0 /mi cutpoint (Marple et al., 1989),
and for cutpoints as small as 0.12 /mi (Sioutas et al., 1994). After a cross-channel
correction factor for the coarse mode is applied, the mass concentrations of each fraction and
the total mass (using a PM10 inlet) can be determined gravimetrically. An inherent
consideration with virtual separation is contamination of the coarse fraction by a portion of
the fine fraction, equivalent to the ratio of the coarse channel flow to the total flow (typically
10%). Although a straightforward mathematical correction can account for the particle mass
between channels, this can influence subsequent chemical and physical characterizations, if
significant differences exist between the chemistry of each fraction (e.g., acidic fine fraction
and basic coarse fraction). Stevens et al. (1993) utilized this limited addition of fine particles
to the coarse fraction to advantage in the SEM analysis of samples collected on Nuclepore
4-22
-------
100 -
20
Figure 4-9. Aerosol separation and internal losses for a 2.5-/im dichotomous sampler
virtual impactor.
Source: Loo and Cork (1988).
filters. Keeler et al. (1988) showed that the growth of fine aerosols at elevated relative
humidities can significantly alter the ratio of fine to coarse collection for the dichotomous
sampler. During early morning periods when the humidity approached 100%, an apparent
loss of up to 60% of the fine mass (to the coarse channel) was observed. Keeler et al.
(1988) concluded that analyzing only the fine fraction of the measured aerosol may not be
appropriate, especially for short integration intervals.
A high volume (1.13 m3/min) virtual impactor assembly was developed by Marple,
et al. (1990) that can be placed on an existing high volume sampler to permit larger total
collections than the dichotomous sampler for chemical speciation by size fraction.
4-23
-------
By placing a number of virtual impactors in parallel, a separation can be achieved at higher
flows, while reducing the total pressure drop. Marple et al. (1993) provide a list of
commercially available virtual impactors by flowrate and available cutpoints. They also note
that virtual separators inherently concentrate the particles in the coarse fraction (typically by
a factor of 10), making them useful as pre-concentrators for sensors with marginal
sensitivities. John et al. (1983) found that an oiled Nuclepore filter with a nominal 8 fj,m
porosity could provide a D50 cutpoint of 2.5 pm, similar to that of a virtual impactor, if
operated at the appropriate face velocity and for a sampling period short enough to minimize
overloading.
4.2.3.3 Cyclones
Cyclones have been used as aerosol separators in personal exposure sampling in
occupational settings for many years. Lippmann and Chan (1979) summarized the cyclones
for sampling aerosol sizes below 10 /Am and noted that the aerosol penetration through a
cyclone can be designed to closely mimic respiratory deposition. An intercomparison of
three cyclone-based personal exposure samplers under occupational conditions (concentrations
typically > 1 mg/m3) was described by Groves et al. (1994). They reported that even
though the cyclones were reportedly designed to mimic similar respirable conventions, biases
as large as a factor of two were noted, possibly attributable to overloading problems.
Marple et al. (1993) provided a list of commercially available air sampling cyclones, by
sampling flowrate and D50 range. Cyclones can be used individually or in a cascade
arrangement to provide a size distribution. Bartley and Breuer (1982) describe methods to
reduce biases when using a 10 mm (diameter) personal air sampling cyclone, especially as
related to cutpoint shifts caused by flowrate changes. Saltzman (1984) provided a similar
analysis for atmospheric sampling cyclones. Sass-Kortsak et al. (1993) observed that
substantial uniformity-of-deposition problems can occur on the filters downstream of personal
sampling cyclones. Wedding and Weigand (1983) used a cyclone within a high volume
aerosol inlet to provide a PM6 0 cutpoint for ambient sampling that did not allow penetration
of particles greater than 10.0 pm.
The simplicity of cyclones has prompted their use as inlets and subsequent separators in
samplers designed to fractionate the aerosol sample for chemical analysis. The "Enhanced
4-24
-------
Method" employed by EPA for sampling acidic aerosols uses a glass cyclone with a 2.5
cutpoint as the sampler inlet (U.S. EPA, 1992). The percent collection as a function of
aerodynamic diameter is shown in Figure 4-10 (Winberry et al., 1993). The modest cutpoint
sharpness exhibited by some cyclones should be considered when attempting to separate
particle size fractions that may interact chemically. Hering et al. (1990) describe several
validated aerosol systems for sampling carbonaceous particles that utilize cyclones with
2.5 /im cutpoints to sample the fine fraction on either Teflon or quartz substrates. Spagnolo
and Paoletti (1994) describe a dual cyclone ambient aerosol sampler with a 15 pun inlet
(described by Liu and Piu, 1981). This sampler was designed to collect a 20 to 15 /xm
fraction, a 20 to 4.0 /xm fraction, and a 0 to 2.5 /xm fraction. Malm et al. (1994) describe a
sampling system with a PM10 inlet and three parallel channels following a 2.5 /zm cutpoint
cyclone that was used for the 40 site IMPROVE network. Over 120,000 fine particle filter
substrates of Teflon®, nylon and quartz were collected for chemical analysis over a 6 year
period.
4.2.3.4 Impactors
Impactors have been developed for a wide range of cutpoints and flowrates. In cascade
arrangements (see Section 4.2.7.1.1) with a characterized inlet, impactors provide particle
distribution information over a range of aerodynamic sizes. Impactors used as components
of inlets or as in-line fractionators stop and retain the aerosol on a surface (e.g., oil-soaked,
sintered metal or glass) that provides consistent performance (primarily minimal bounce) over
the entire sampling interval. Recovery and analysis of the deposited particles in these
situations are usually not considerations. Koutrakis et al. (1990) described the design of
2.1 /xm cutpoint impactor for a single stage annular denuder system that exhibited internal
losses of less than 3%. Marple (1978) described the use of multiple nozzle impactors in a
single stage to emulate selected respiratory penetration curves.
Marple et al. (1993) noted that the three primary limitations of impactors are particle
bounce, overloading of collection stages and interstage losses. Particles can bounce from a
stage after impaction if the surface forces are not adequate for their retention. Wang and
John (1988) described the effects of surface loading and relative humidity on particle bounce
and growth, and they noted that if less than 6% of the impact area was covered by deposited
4-25
-------
100
80
60
o>
1 40
O
20
0
2 2.5 4 6
Aerodynamic Diameter (urn)
8
10
Figure 4-10. Percent collection as a function of aerodynamic diameter for the U.S. Environmental Protection Agency
enhanced method glass cyclone.
Source: Winberry et al. (1993).
-------
particles, particle-to-particle collisions (and bounce) could be neglected. They also showed
that ammonium sulfate aerosol growth with increasing humidity resulted in a 25% shift in
cutpoint as the relative humidity increased to 64%. Biswas et al. (1987) showed that,
especially in low pressure zones, the relative humidity and temperature can change rapidly
within a cascade impactor, potentially altering cutpoints and losses. Wang and John (1988)
in subsequent work did not observe these shifts, noting that the transit time in a jet is only on
the order of 10 /zs. Turner and Hering (1987) noted that the stage substrate materials
(Mylar*, stainless steel and glass) with the same grease (Vaseline*) could produce
substantially different particle adhesion characteristics. Vanderpool et al. (1987) showed that
using glass fiber filters as impactor surfaces can produce drastically reduced performance as
compared to a greased substrate (see Figure 4-11). Markowski (1987) suggested that adding
a duplicate (same cutpoint) serial impactor stage can permit reasonable bounce and
re-entrainment corrections to be made.
4.2.4 Sampling Considerations
4.2.4.1 Siting Criteria
Selection of aerosol sampling locations is partially guided by siting criteria under the
1987 PM10 regulation (U.S. Environmental Protection Agency, 1987), which provided
limited guidance for Pb and PM10 samplers. The details behind these guidelines for PM10
are provided in a guidance document (U.S. Environmental Protection Agency, 1987), which
relates physical and chemical characteristics of aerosols to the spatial scales (regional, urban,
neighborhood, middle and micro) required to define the influences of sources on various
populations. Guidance was also provided on the influences of nearby point, line and area
sources on sampling location as a general function of particle size. Only limited information
was noted to be available on specific influences of local obstructions and topography
(e.g., trees, buildings) on measured aerosol concentrations. The primary focus was
establishment of the degree that a sampling location was representative of a specific scale.
The high purchase cost, and occasionally physical size, of aerosol samplers have
restricted the number of sampling sites used in air monitoring studies. This may pose
problems if the selected sites are not truly representative of the exposures for the populations
at risk. To address the biases resulting from too few aerosol samplers in a field study, a
4-27
-------
100
4th Impactor
80
O Greased Substrate
D Glass-Fiber Filter
| 60'
'o
1
o
••5 40
^
o
O
20
0
5 10 20 40
Aerodynamic Particle Diameter (iim)
Figure 4-11. Performance of glass fiber filters compared to greased substrate.
Source: Vanderpool et al. (1987).
"saturation" sampler approach has been used, utilizing an inexpensive, miniature and
battery-powered PM10 sampler that can be deployed at a large number of sites. Phillips
et al. (1994) reported application of this approach, using 15 PM10 saturation samplers in
conjunction with one dichotomous sampler to study the contribution of diesel emissions to
total PM levels in Philadelphia. Although the mean for PM10 concentrations of the saturation
samplers was essentially identical to that of the dichotomous sampler, the saturation data
showed site-to-site mean differences of up to 30 /ig/m3.
4.2.4.2 Averaging Time/Sampling Frequency
The collection frequency for samples to support the EPA PM10 NAAQS has typically
been on an every-6th-day schedule. Shaw et al. (1982) raised a statistically-based concern
4-28
-------
that infrequent collection increases the coefficient of variation about the overall mean
concentration value; that is, the variability of computed fine mass concentration means
increased as the square root of the number of intervals between individual measurements.
Symanski and Rappaport (1994), using time series analyses, described the influences of
autocorrelation and non-stationary behavior in occupational settings on concentration
distributions constructed from infrequent sampling. They recommended a random sampling
design where a sufficient number of locations are sampled repeatedly over an adequate period
of time to account for the full range of exposure possibilities. Hornung and Reed (1990)
described a method of estimating non-detectable (or missing) values to lessen variance about
the estimate of the geometric mean, by assuming that the concentration distribution is
log-normal.
Insufficient sample collections can be remedied by more frequent operation of manual
samplers. The recent PM10 equivalency designations (see section 4.2.5) of two beta gauge
samplers and the TEOM sampler can provide the necessary information, with hourly rather
than daily resolution. The initial cost of an automated sampler is typically 2-3 times that of a
manual, single channel PM10 sampler, but can be offset by savings in operator labor costs.
If inherent biases described in section 4.2.3.4 for the beta and TEOM samplers can be
overcome (and they are field reliable), these approaches should prove very useful in routine
regulatory and research monitoring studies. Potential also exists for the integrating
nephelometer to be an acceptable exceedance monitor7, using site specific calibrations
relating the measured scattering coefficient, bsp, to fine aerosol mass concentrations (e.g.,
Larson etal., 1992).
Another consideration for defining sampling intervals is the setting of start and stop
clock times. Daily 24-h sampling is most often done from midnight-to-midnight, but
occasionally from noon-to-noon to either reduce the number of samplers required or to
reduce operator burden. Sampling locations with highly variable diurnal aerosol
concentration patterns (e.g., from night time wood smoke influence or day time traffic dust),
or marked differences between week days and weekend days may require special
consideration. These influences can be especially significant for <24-h sampling periods.
7 A Pollutant Standard Index (PSI) monitor used to estimate when a pre-determined exceedance level has been
reached or exceeded, to potentially trigger the operation of an equivalent PM10 gravimetrically-based sampler.
4-29
-------
4.2.4.3 Collection Substrates
The selection of a filtration substrate for integrated collection of particles must be made
with some knowledge of the expected particle characteristics and a pre-determined analytical
protocol. The expected sampled size distribution places a requirement on the porosity of the
filter media to effectively trap a reasonably high percentage of the particles with a minimum
of pressure drop. The most common filter types used in air sampling are fiber and
membrane. Fiber filters tend to be less expensive than membrane filters, have low pressure
drops, and have high efficiencies for all particle sizes. They are most commonly available in
glass fiber, Teflon coated glass fiber and quartz materials. Membrane filters retain the
particles on the surface for non-depth analyses (e.g., X-Ray Fluorescence), can have specific
porosity's, and are available in a wide variety of materials. Teflon is a popular membrane
material because of its inertness, but is 2 to 4 times as expensive as more common materials.
Liu et al. (1978) summarize the effective penetration characteristics as a function of particle
size and pressure drops for a wide variety of fiber and membrane filters. The selection of
filter diameter for a given flowrate influences the face velocity and the loading capacity
before the pressure drop becomes unacceptable. A 47mm filter provides a surface area that
is 60% larger than that of a 37mm filter. Polycarbonate filters with well defined porosities
(e.g., Nuclepore®) have been used in "stacked" arrangements as fine particle separators.
John et al. (1983) describe using an 8 pim porosity filter in series with a back-up filter to
effectively provide a 3.5 /nm separation of fine and coarse particles in a small, inexpensive
package. Samplers based on this principle were widely used in the early 1980's (Cahill
et al., 1990) and their performance under field conditions was shown to be equivalent to later
cyclone based PM2 5 samplers in the IMPROVE network.
The reactivities of filter substrates with the aerosol have been reported extensively.
A common problem with glass fiber filters used on high volume samplers is the basic pH of
the glass material and its effective conversion of SO2 to paniculate sulfates (e.g., Pierson
et al., 1976). Appel et al. (1984) also reported similar conversions of nitrogen oxides to
particulate nitrates on glass fiber filters. Witz et al. (1990) reported losses of particulate
nitrates, chlorides and ammonium (19, 51 and 65%, respectively) from quartz fiber filters
during storage. No significant losses of sulfates were reported from quartz filters.
Similarly, Zhang and McMurry (1992) reported the anomalous loss of fine particle nitrates
4-30
-------
from Teflon filters and noted that predictive loss theories were insufficiently accurate to
permit corrections. Lipfert (1994) also observed that nitrate artifacts on glass fiber filters
were difficult to quantify on a routine basis. Measurements of paniculate nitrate using nylon
filters by the IMPROVE protocols show, however, that such effects are minor except in
California (Malm et al., 1994). Eatough et al. (1993) found significant losses of paniculate
organic compounds on quartz filters due to volatilization, such that ambient concentrations of
paniculate carbon may be underestimated substantially. Lipfert (1994) investigated filter
artifacts in a field study in New York and concluded that positive sulfate artifacts inflated
PM10 values from glass fiber filters by 6 /*g/m3. It was noted that the combination of sulfate
and nitrate artifacts on glass fiber filters may inflate TSP measurements by as much as 10 to
20 /ig/m3.
4.2.4.4 Chemical Speciation Sampling
The collection of aerosol samples for chemical speciation analysis adds another
dimension to the complexity of the sampling protocol (also see Section 4.3). The simplest
approach utilizes a characterized inlet or separator to define a size fraction, provides an
aerosol collection substrate compatible with the analytical technique, and collects an adequate
quantity of sample for analysis. This approach is applicable for relatively nonreactive and
stable components such as heavy metals. An important consideration is the potential
reactivity of the sampling substrate with either the collected aerosols or the gas phase. Appel
et al. (1984) predicted effects of filter alkalinity on conversion of acid gases to sulfates and
nitrates and provided an upper limit estimate for artifact sulfate formation (added mass) for
TSP high volume sampling of 8-15 pig/m3 for a 24-h sample.
Analyses for semi-volatile organics found in both the particle and vapor phases must be
collected by adding a vapor trap (e.g., polyurethane foam plug) downstream of the sampling
filter. Arey et al. (1987) noted that this arrangement of sequential sampling reservoirs may
account for the total mass of organics, but not accurately describe their phase distribution in
situ, due to "blow-off" from the filter during sampling. Van Vaeck et al. (1984) measured
the volatilization "blow-off" losses of organic species from cascade impactor sampling to be
up to 30%, while the loss of total mass was only 10%. McDow and Huntzicker (1990)
characterized the face velocity dependence for organic carbon sampling and provided
4-31
-------
correction models, based on adsorption losses to a backup filter. Turpin et al. (1994)
examined organic aerosol sampling artifacts and highlighted the distinction between "organic
carbon" and individual organic species. They observed that organic carbon sampled from the
atmosphere is unlikely to attain equilibrium between that in the gas phase and that adsorbed
on a quartz fiber back-up filter. They also noted that under typical sampling conditions,
adsorption is the dominant artifact in the sampling of paniculate organic carbon, and longer
sampling periods reduce the percentage of collected material that is adsorbed vapor. It was
recommended that collection of aerosols for carbon analyses be made on a pre-fired quartz
filter, with estimates of the adsorption artifact made from a quartz filter placed behind a
Teflon filter in a parallel sampler.
For more highly reactive and unstable species, the recognition of the in situ character
of the aerosol in the air must be identified and preserved during all facets of the sampling
process to provide a representative and accurate sample. Durham et al. (1978) described a
denuder to remove sulfur dioxide while sampling for sub-micron aerosols. Spicer and
Schumacher (1979) observed that many artifact reactions may occur if stripping of nitric
acid, sulfuric acid and ammonia is not performed during speciated aerosol sampling.
Appel et al. (1988a) described the various loss mechanisms that apply to the aerosol and
vapor phases while sampling for nitric acid. They noted that residence time, surface material
compositions, and conditioning prior to sampling were the predominant variables affecting
transmission efficiency.
The determination of strong acidity for atmospheric aerosols (U.S. Environmental
Protection Agency, 1992) describes an "enhanced" method that recognizes the inter-
relationships between the vapor and aerosol phases for each constituent and the potential
interferences. An inlet cyclone or impactor is used to provide a 2.5 pm cutpoint to exclude
the higher pH aerosols found in the coarse fraction of PM10. As shown in Figure 4-12,
denuders are used in the flowstream which selectively remove gas phase components with
minimal, characterized losses of aerosol. Ye et al. (1991) determined the aerosol losses
through an 10 1pm annular denuder system as a function of particle size. They noted that
total particle losses were less than a few percent whether the denuders were coated or
uncoated. Also, using parallel annular denuders, Forrest et al. (1982) found aerosol losses
of only 0.2 to 2.2% for 0.3 to 0.6 jum particles and 4 to 5% for 1 to 2 pm particles.
4-32
-------
Filter Pack>
Coated
Filters
.Citric Acid
Teflon Filter
d4
d3
d2
Coupler (Typical)—-
d1
Coupler/ ImpactOF-
1
1
T3
0
0
£
NO2
HN03
NH3
f, NH^SOJ, NO;
1
T
NH3
I
co
si
(0
z
T
NO2 , HNO2 , SO2
1
CO
8
CM
CO
HCL, HNO2
HNCJ3, SO2
i
T
HNQj
sa
Figure 4-12. Schematic diagram of an annular denuder system.
Source: U.S. Environmental Protection Agency (1992).
4-33
-------
Filter packs have been developed, consisting of a sandwich of filters and collection
media of various types in series, to collect aerosols and selectively trap gases and aerosol
volatilization products. Benner et al. (1991) described an annular denuder sampling system
using Teflon and nylon filter packs and annular denuders to quantitatively collect the
distributed ammonium nitrate, nitric acid and ammonia in the vapor and aerosol species.
They observed that volatile nitrates were 71% ± 27% of the total nitrates during the day and
55% ± 30% at night in arid, southwestern U. S. locations. Masia et al. (1994) described
the anomalous uptake of ammonia on the nylon filters, which were expected to collect only
the gas phase nitric acid. Wang and John (1988) reported volatilization losses of ammonium
nitrate in the Berner impactor of 7% under hot, dry (18% Rh) conditions.
Vossler et al. (1988) reported the results of improvements in an annular denuder
system, including Teflon coating of the internal glass surfaces. They found an apparent
particle bounce problem with the cyclone inlets (with or without Teflon coating) and
proposed adding an additional in-line, greased impactor. John et al. (1988) found that
anodized aluminum surfaces absorb nitric acid efficiently and irreversibly. Several method
comparison studies have been reported for systems utilizing annular denuder/filter pack
technologies, including Harrison and Kitto (1990), Sickles et al. (1990), and Benner et al.
(1991).
4.2.4.5 Data Corrections/Analyses
Aerosol concentration data are reported in units of mass per volume (e.g., jig/m3). The
current EPA regulations for sampling TSP, PM10 and Pb require that sampler flowrates be
controlled and the sampled volumes be standardized to 760 mm Hg and 25 °C. These
requirements may pose problems in the interpretation of concentrations from aerosol
samplers. Wedding (1985) notes that the flowrate through inertial impactors should be
maintained at "local" temperatures and pressures to retain the separator's aerodynamic
calibration. Mass flow controllers may significantly affect the separator flow velocity during
large diurnal temperature changes, excessively biasing the resulting cutpoint diameter.
Subsequent correction of the sampled aerosol volume to "standard" conditions by
mathematically compensating for average meteorological conditions may improperly report
the aerosol concentration measurement. If the rationale for aerosol sampling was to mimic
4-34
-------
respiratory penetration (which occurred at local conditions), a correction after-the-fact may
not be appropriate. These corrections are typically small (less than a few percent) except in
locations at higher altitudes and those with large diurnal or seasonal temperature changes.
The basis for mandating flowrate controller performance for aerosol samplers is sound, but
the subsequent requirements for concentration corrections for temperature and pressure are
complex. Although the issue of sampled volume correction for local temperature and
pressure is beyond the scope of this document, the scientific bases should be reassessed for
aerosol sampling to determine if this requirement is consistent with EPA goals.
The matching of aerosol measurement capabilities with data quality requirements is
discussed by Baron and Willike (1993). They note that although aerosol sampler precision
can be determined from collocated measurements, field sampling accuracy is more difficult to
define. Generation of mono- or poly disperse calibration aerosols are rarely done in field
settings because of the complexity of the calibration process. Typically, only the aerosol
sampler flowrate accuracy is determined in the field. Biases between the means from
collocated aerosol samplers using different separation techniques, may result from sampler
operational errors, or from inadequacies in determining the performance specifications during
laboratory testing.
4.2.5 Performance Specifications
4.2.5.1 Approaches
A significant step in the standardization process for aerosol sampling was the EPA
definition (U.S. Environmental Protection Agency, 1987) of the PM10 size fraction, based on
the aerodynamic diameter of particles capable of penetrating to the thoracic region of the
respiratory system. This definition was followed by implementation of the PM10 provisions
of EPA's Ambient Air Monitoring Reference and Equivalent Methods regulation (U.S.
Environmental Protection Agency, 1987). The format of the latter regulation included
adoption of performance specifications for aerosol samplers, based on controlled wind tunnel
testing with mono-dispersed aerosols. Controlled laboratory testing is followed by limited
field testing, including tests of candidate equivalent methods to demonstrate comparability to
designated reference methods. The stringency of the field testing to elucidate potential
4-35
-------
sampling biases is strongly influenced by the local sampling site environment, including
factors such as wind speed, nearby point sources, and the probability of fugitive dust events.
This approach was chosen, rather than the design specification approach taken in 1971
(Federal Register, 1971), which identified the high volume sampler and associated
operational procedures as the reference method for Total Suspended Particulates (TSP). The
1971 regulation had no provisions for the use of alternative or equivalent methods, and
subsequent to this design designation, significant problems of the TSP high volume sampler,
such as wind speed and direction dependency (McFarland et al., 1979) and off-mode
collection (Sides and Saiger, 1976), were reported. These inherent biases complicated the
interpretation of TSP concentration data (U.S. Environmental Protection Agency, 1982) and
weakened correlations with other measures. The problems were estimated to have induced
biases of less than 10% for most situations, but occasionally as high as 30%. The
subsequent development of aerosol testing programs for size selective aerosol samplers
(e.g., McFarland and Ortiz, 1979; Wedding, 1980; John and Wall, 1983; Ranade et al.,
1990; Hall et al., 1992) more rapidly identified weaknesses in existing technologies and
facilitated the development of better methods.
No reference standard exists for aerosol concentration measurements in air. The
calibration of aerosol samplers relies primarily on characterizations under controlled
conditions of the sampler sub-systems, including the size selective inlet, sample conditioning
and transmission system, the flow control system, and, if used, subsequent size separators,
sample collection and storage elements, and sensors and associated electronics. Although the
precision of an aerosol sampler is readily obtained by using replicate, collocated samplers,
the accuracy can only be estimated by comparison with either designated "reference"
samplers or with computations of expected aerosol mass collections. Performance
specification limits are used to control the overall aerosol sampling accuracy. As noted by
John and Wall (1983) the selection of a comprehensive list of sampling elements requiring
inclusion and the setting of the performance limits for each element is a difficult task,
especially when the range of "real-world" sampling situations is considered.
Performance specifications were utilized for the PM10 standard to allow the broadest
spectrum of measurement technologies, hopefully encouraging the development of new and
better methods. A research program was implemented by EPA in parallel with preparation
4-36
-------
and review of the 1982 Criteria Document to identify the critical specifications and
understand the inter-relationships among the parameters influencing the aerosol sampling
process. Studies of the influences of factors such as wind velocity, particle character, flow
rate stability, particle bounce and wall losses on precision and accuracy substantially
advanced the science of large particle sampling. The performance specification approach was
a significant improvement over the design specification approach used for the TSP high
volume sampler, in that it fostered the development of new information and technologies and
provided for the use of alternative methods. In retrospect, the primary weakness of the
design specification approach for the TSP reference method was not the process per se, but
the technical inadequacy of the development and testing program that produced the high
volume sampler design.
The utilization of a performance specification approach requires that a minimum level
of knowledge be available about the measurement process and the associated test procedures.
Some significant drawbacks subsequently observed in the performance specification approach
for PM10 included the complexity, expense and scarcity of aerosol wind tunnel test facilities,
and the difficulty in defining comprehensive specifications that considered all of the nuances
of aerosol sampling. Wind tunnel evaluation and limited field tests do not always identify
sampler related problems encountered during extended periods of ambient sampling (e.g.,
John and Wang, 1991). Future performances tests should ideally include extended field
testing, for example, to evaluate performance in different geographic regions and seasons, as
well as under different meteorological conditions.
4.2.5.2 Performance Testing
Since the 1982 Criteria Document (U.S. Environmental Protection Agency, 1982a),
aerosol sampling research studies have identified numerous factors that influence the
precision and accuracy of samplers in both wind tunnel and field performance testing. Rodes
et al. (1985), Purdue et al. (1986), and Cook et al. (1995) showed, in field evaluations under
a variety of sampling situations, that PM10 samplers meeting the EPA performance
specifications provide aerosol concentration measurements with a precision of 10% or less
when samplers of the same model were compared. However, significant biases were evident
when different types of samplers were compared. The Andersen SA-321A PM10 sampler
4-37
-------
was found to collect an average of 58% more mass than a collocated Wedding PM10 sampler
(Perdue et al., 1986). This was partly attributed to the (predicted) bias associated with
cutpoint differences between the inlets. A more significant bias (not predicted) was
associated with degraded performances in opposite directions (Andersen over-sampling,
Wedding under-sampling) due to soiling of the separators during extended sampling periods.
Rodes et al. (1985) noted that sampler precisions (coefficients of variation) were better than
±10%, with several samplers better than ±5%. Cook et al. (1995) reported good agreement
(variability less than 15%) among several types of PM2 5 samplers. Other sampler types
showed significant biases. Under the conditions of the study, high concentrations of
NH4NO3 and organic carbon (winter in Bakerfield, CA), samplers which heated the collected
particles to 30 °C or 50 °C during sampling gave lower mass values than filter samples
which were collected at ambient conditions and equilibrated for 24 hours at 23 ± 3 °C and
40 ± 5% relative humidity. Coefficient of Haze (COH) measurements by an American Iron
and Steel (AISI) tape sampler and light scattering (bscat) measured by an intergrating
nephelometer heated to 17 °C correlate well with PM2 5 measurments (COH, r = 0.82 to
0.91;bscat, r = 0.91 to 0.98).
Mark et al. (1992) reviewed the attributes of wind tunnel testing, and noted that tests
using controlled conditions are a necessity to determine whether an aerosol sampler meets a
basic set of established performance specifications. Hollander (1990) suggested that sampler
performance criteria should be evaluated in controlled outdoor tests, given the inability of
wind tunnels to accurately mimic the influences of outdoor meteorological conditions on
sampling. The current EPA PM10 performance testing requires field tests to demonstrate
sampler precision and flow rate stability, and the comparability of equivalent methods to
designated reference methods. The stringency of such tests are highly dependent on the
sampling location chosen, local aerosol sources, the existing meteorology and the season.
Kenny and Liden (1991) noted that the EPA PM10 sampler performance specifications
(U.S. Environmental Protection Agency, 1987) provided inadequate consideration for
defining the uncertainty in each parameter, and they suggested that bias mapping approaches
be considered. Bias mapping relates the allowable precision of a parameter to the critical
values of expected bias that just meet the specifications. A similar but less robust procedure
is used in the EPA performance specifications. Botham et al. (1991) recommended that the
4-38
-------
wind tunnel test system duplicate the expected field sampling scenarios as closely as possible,
including characteristic flow obstructions. They described the wind tunnel testing of personal
aerosol samplers mounted on an anthropogenically consistent (e.g., breathing, heated)
mannequin. Hoffman et al. (1988) and John et al. (1991) described the adverse influence of
internal surface soiling on aerosol collection performance during extended field operation,
and noted that the existing EPA PM10 performance specifications only considered clean
samplers. Mark et al. (1992) noted that even though wind tunnel performance testing cannot
exactly emulate outdoor turbulence scales, testing in the controlled tunnel environment is a
necessity to adequately characterize particle samplers.
Significant new innovations in aerosol sensing technologies that meet the PM10
performance specification and have earned designations as equivalent methods (see
Section 4.2.6) have occurred since the 1982 Criteria Document. These indirect8 methods
include automated beta attenuation monitors (e.g., Merrifield, 1989; Wedding and Weigand,
1993), and the automated Tapered Element Oscillating Microbalance (TEOM®) technology
(Patashnick and Rupprecht, 1991). The TEOM® sampler does not use gravimetric analysis
on a balance, but computes mass based on the frequency shift as particles are deposited on an
oscillating element. These designations added automated sampling capabilities to the
previously all-manual list of sampling methods. Recent field tests of both the beta and
TEOM methodologies suggest that biases compared to gravimetrically-based samplers may
exist that were not identified by the EPA performance test requirements. Arnold et al.
(1992) provide data suggesting that the mass concentration data from a Wedding beta gauge
averaged 19% lower than a collocated Wedding PM10 gravimetric sampler. Several
researchers reported that the TEOM can yield mass concentrations that are either lower or
higher than those observed in reference method measurements (Hering, et al., 1994; Meyer,
et al., 1992; Meyer et al., 1995). The TEOM operates at an elevated temperature (30 °C or
50 °C) during the collection and measurement process in order to ensure the removal of
liquid water associated with particles. In the reference method, the particle-associated water
is removed during an equilibration period in a specified temperature and relative humidity
range. Both techniques are subject to loss of semivolatile materials such as NH4NO3 and
8An alternate technology used instead of direct gravimetric analysis to infer mass concentrations from developed
relationships.
4-39
-------
some organic components. The TEOM may lose semivolatile material that is volatilized due
to the higher than ambient sampling temperatures. The reference method may lose
semivolatile material during sampling (if concentrations decrease or temperature increases
during the sampling period). The reference method is also subject to loss of semivolatile
materials during equilibration and storage prior to weighing. These processes, in areas or
times during which semivolatile aerosol components are a significant component of the
ambient aerosol mass, can cause either technique to yield a significant under-estimation of
the mass of particulate matter in the ambient air. This also applies to some degree to any
integrated sample collected on a substrate. Devising comprehensive performance
specifications and test procedures for aerosol samplers, given the complexities of aerosol
chemistry, physics, and mechanics, is a demanding task.
The size-selective, gravimetrically-based, 24-h manual aerosol concentration
measurement has been the mainstay of compliance sampling for at least two decades.
Although several new sensor technologies have been designated as Equivalent methods for
PM10 by EPA, no superior technology has been developed that is a better reference method
than that based on collection of a discreet aerosol sample followed by gravimetric analysis.
Improvements have been made since 1982 in the accuracy and precision of integrated,
manual aerosol sampling. Some of the most significant advances have occurred in aerosol
size separation technologies, improved performance characterization test methods, and
speciation sampling techniques.
As discussed by Lippmann (1993), there may be no threshold for health responses
down to the lowest aerosol concentrations. This implies that the precision and lower
detection limit requirements will continue to be important for aerosol measurements across
the concentration spectrum. These factors become even more critical as the size fraction of
interest becomes smaller and fewer total particles are collected. At low concentrations
(especially with small size fractions), normally insignificant factors can become important
contributors to biases. Witz et al. (1990) reported rapid and substantial losses of nitrates,
chlorides and ammonium ion (19, 65 and 51%, respectively) from quartz high volume
sampler filters during storage periods of one week prior to analyses. Transformations can
also occur on glass fiber substrates during sampling, as reported by Sickles and Hodson
(1989) for the rapid conversion of collected nitrites to nitrates in the presence of ozone.
4-40
-------
Zhang and McMurry (1992) showed that nearly complete evaporative losses of Fine particle
nitrate can occur during sampling on Teflon filters. Lioy et al. (1988), in a study using
PM10 samplers, reported 25 to 34% lower concentration values resulting from losses of glass
fibers from the filter to the filter holder gasket during sampling. Feeney et al. (1984)
reported weight gains in Teflon filters used in contaminated ring cassettes, that posed
significant problems for light aerosol loadings. Grinshpun et al. (1993) suggest that if
unavoidable changes in the aerosol occur during sampling, development of a model that
permits back-calculation of the in situ characteristics can be considered.
4.2.6 Reference and Equivalent Method Program
Ambient air PM10 measurements are used (among other purposes) to determine whether
defined geographical areas are in attainment or non-attainment with the National Ambient Air
Quality Standards (NAAQS) for PM10. These measurements are obtained by the States in
their state and local air monitoring station (SLAMS) networks as required under 40 CFR
Part 58. Further, Appendix C of Part 58 requires that the ambient air monitoring methods
used in these EPA-required SLAMS networks must be methods that have been designated by
the EPA as either reference or equivalent methods.
Monitoring methods for particulate matter (i.e., PM10) are designated by the EPA as
reference or equivalent methods under the provisions of 40 CFR Part 53, which was
amended in 1987 to add specific requirements for PM10 methods. Part 53 sets forth
functional specifications and other requirements that reference and equivalent methods for
each criteria pollutant must meet, along with explicit test procedures by which candidate
methods or samplers are to be tested against those specifications. General requirements and
provisions for reference and equivalent methods are also given in Part 53, as are the
requirements for submitting an application to the EPA for a reference or equivalent method
determination. The distinction between reference and equivalent methods is a technical one.
On one hand, it provides for detailed, explicit specification of a selected measurement
technology for reference methods. On the other hand, it allows alternative (including
innovative and potentially improved) methodologies for equivalent methods, based only on
meeting specified requirements for functional performance and for comparability to the
reference method. For purposes of determining attainment or non-attainment with the
4-41
-------
NAAQS, however, the distinction between reference and equivalent methods is largely, if not
entirely, immaterial.
Under the Part 53 requirements, reference methods for PM10 must be shown to use the
measurement principle and meet the other specifications set forth in 40 CFR 50, Appendix J
(Code of Federal Regulations, 1991). They must also include a PM10 sampler that meets the
requirements specified in Subpart D of 40 CFR 53. Appendix J specifies a measurement
principle based on extracting an air sample from the atmosphere with a powered sampler that
incorporates inertial separation of the PM10 size range particles followed by collection of the
PM10 particles on a filter over a 24-h period. The average PM10 concentration for the
sample period is determined by dividing the net weight gain of the filter over the sample
period by the total volume of air sampled. Other specifications are prescribed in Appendix J
for flow rate control and measurement, flow rate measurement device calibration, filter
media characteristics and performance, filter conditioning before and after sampling, filter
weighing, sampler operation, and correction of sample volume to EPA reference temperature
and pressure. Also, sampler performance requirements in Subpart D of Part 53 include wind
tunnel tests for "sampling effectiveness" (the efficacy of the PM10 particle size separation
capability) at each of three wind speeds and "50 percent cutpoint" (the accuracy of the
primary 10-micron particle size separation). Field tests for sampling precision and flow rate
stability are also specified. In spite of the instrumental nature of the sampler, this method is
basically a manual procedure, and all designated reference methods for PM10 are therefore
defined as manual methods.
Equivalent methods for PM10, alternatively, need not be based on the measurement
principle specified in Appendix J nor meet the other Appendix J requirements. Instead,
equivalent methods must meet the "sampler" performance specifications set forth in
Subpart D of Part 53 and demonstrate comparability to a reference method as required by
Subpart C of Part 53. The provisions of Subpart C specify that a candidate equivalent
method must produce PM10 measurements that agree with measurements produced by
collocated reference method samplers at each of two field test sites. For this purpose,
agreement means a regression slope of 1 ± 0.1, a regression intercept of 0 ± 5 /xg/m3, and
a correlation >0.97. These requirements allow virtually any type of PM10 measurement
4-42
-------
technique, and therefore an equivalent method for PM10 may be either a manual method or a
fully automated instrumental method (i. e., analyzer).
As of this writing, the EPA has designated seven reference methods and three
equivalent methods for PM10, as listed in Table 4-1. The reference methods include four
methods featuring high-volume samplers from two manufacturers, with one using a cyclone-
type size separator and the others using an impaction-type separator. The other reference
methods include a low-volume sampler (from a third manufacturer), a low-volume sampler
featuring a secondary size separation at 2.5 microns (dichotomous sampler), and a medium-
volume, non-commercial sampler. The three designated equivalent methods are all
automated PM10 analyzers and include two operating on the beta-attenuation principle and
one based on a tapered element oscillating microbalance (TEOM™). It should be noted that
although these latter three automated PM10 analyzers may be capable of providing continuous
or semi-continuous PM10 concentration measurements, only 24-h average PM10
measurements are recognized as approved under their equivalent method designations.
4.2.7 Determination of Size Distribution
The determination of aerosol size distributions can be a powerful research tool when
studying source contributions and transformation processes. A number of techniques are
available as described by texts such as Willeke and Baron (1993) to make near real-time,
single particle aerosol measurement in addition to cascade impactors.
4.2.7.1 Cascade Impactors
In cascade applications, the aerosol is impacted and trapped onto a series of removable,
coated substrates (e.g., greased foils), including a final total stage collection on a filter for
gravimetric analysis. Marple et al. (1993) list over 30 single stage and cascade impactors
that are either commercially available or still commonly used. The design and calibration of
a miniature eight-stage cascade impactor for personal air sampling in occupational settings is
described by Rubow et al. (1987), operating at 2.0 1pm. Evaluations of the most commonly
used cascade impactor systems have been reported by Vaughan (1989) for the Andersen MK1
and MK2 7-stage cascade impactors, Marple et al! (1991) for the 10-stage Micro-Orifice
Uniform Deposit Impactor (MOUDI), and Wang and John (1988) and Hillamo and
4-43
-------
TABLE 4-1. U.S. ENVIRONMENTAL PROTECTION AGENCY-DESIGNATED REFERENCE
AND EQUIVALENT METHODS FOR PM10
Method No.
Identification
Description
Type
Date
RFPS-1087-062
RFPS-1287-063
RFPS-1287-064
RFPS-1287-065
Wedding & Associates PM10
Critical Flow High- Volume
Sampler.
Sierra-Andersen or General Metal
Works Model 1200 PM10 High-
Volume Air Sampler System
Sierra- Andersen or General Metal
Works Model 321-B PM10 High-
Volume Air Sampler System
Sierra-Andersen or General Metal
Works Model 321-C PM10 High-
Volume Air Sampler System
High-volume (1.13 m3/min) sampler with cyclone-
type PM10 inlet; 203 x 254 cm (8 x 10 in) filter.
High-volume (1.13 m3/min) sampler with
impaction-type PM10 inlet; 203 x 254 cm (8 x 10
in) filter.
High-volume (1.13 m3/min) sampler with
impaction-type PM10 inlet; 203 x 254 cm (8 x 10
in) filter. (No longer available.)
High-volume (1.13 m3/min) sampler with
impaction-type PM10 inlet; 203 x 254 cm (8 x 10
in) filter. (No longer available.)
Manual reference
method
Manual reference
method
Manual reference
method
Manual reference
method
10/06/87
12/01/87
12/01/87
12/01/87
RFPS-0389-071
Oregon DEQ Medium Volume
PM10 Sampler
Non-commercial medium- volume (110 L/min)
sampler with impaction-type inlet and automatic
filter change; two 47-mm diameter filters.
Manual reference
method
3/24/89
RFPS-0789-073
Sierra-Andersen Models SA241 or
SA241M or General Metal Works
Models G241 and G241M PM10
Dichotomous Samplers
Low-volume (16.7 L/min) sampler with impaction-
type PM10 inlet; additional particle size separation
at 2.5 micron, collected on two 37-mm diameter
filters.
Manual reference
method
7/27/89
EQPM-0990-076
Andersen Instruments Model
FH62I-N PM10 Beta Attenuation
Monitor
Low-volume (16.7 L/min) PM10 analyzers using
impaction-type PM10 inlet, 40 mm filter tape, and
beta attenuation analysis.
Automated
equivalent method
9/18/90
-------
TABLE 4-1 (cont'd). U.S. ENVIRONMENTAL PROTECTION AGENCY-DESIGNATED REFERENCE
AND EQUIVALENT METHODS FOR PM10
Method No.
Identification
Description
Type
Date
EQPM-1090-079
EQPM-0391-081
Rupprecht & Patashnick TEOM
Series 1400 and Series 1400a
PM10 Monitors
Wedding & Associates PM10 Beta
Gauge Automated Particle
Sampler
Low-volume (16.7 L/min) PM10 analyzers using
impaction-type PM10 inlet, 12.7 mm diameter
filter, and tapered element oscillating microbalance
analysis.
Low-volume (16.7 L/min) PM10 analyzer using
cyclone-type PM10 inlet, 32 mm filter tape, and
beta attenuation analysis.
Automated
equivalent method
Automated
equivalent method
10/29/90
3/5/91
RFPS-0694-098
Rupprecht & Patashnick Partisol
Model 2000 Air Sampler
Low-volume (16.7 L/min) PM10 samplerwith
impaction-type inlet and 47 mm diameter filter.
Manual reference
method
7/11/94
-------
Kauppinen (1991) for the 6-stage Berner, low pressure cascade impactor. The smallest
particle stages of these impactors can have very small diameter jets and/or very low total
pressures to achieve the sub-micron separations. The MOUDI impactor has 2000 holes on
the lowest cutpoint stage. Raabe et al. (1988) describe an 8 stage cascade slit impactor with
slowly rotating impactor drums instead of flat plates. This arrangement, in combination with
a PIXIE analyzer, permitted aerodynamic sizing of elemental components, with temporal
resolution. The skill and care required in the operation of cascade impactors suggests that
they are research rather than routine samplers.
The importance of the aerosol calibration of a cascade impactor is illustrated by
Vaughan (1989) in Figure 4-13, which compares the experimental data with the
manufacturer's calibrations and indicates biases as large as 1.0 fim. Marple et al. (1991)
provided a similar type of stage calibration for the MOUDI impactor and included data on
the internal particle losses (see Figure 4-14). These loss data showed that an improperly
designed inlet to the impactor, combined with the inertial and interception losses of the larger
particle sizes, can substantially bias the first stage collections. This was also demonstrated
for the inlet to the Andersen impactor by McFarland et al. (1977). Cascade impactors that
cover wide particle size ranges inherently require design compromises among competing
factors, including cutpoint sharpness, internal stage losses and the physical size of the device.
Cascade impactors can be used to construct distributions of mass and speciated
constituents as a function of aerodynamic diameter. These distributions can be constructed
graphically or using matrix inversion techniques. Marple et al. (1993) notes that impactor
stage calibrations which do not demonstrate sharp cutoffs can cause significant between-stage
sizing errors if not accommodated. John et al. (1990) measured distributions over the
0.08 to 16 [j.m range for mass and inorganic ions for several sites in Southern California.
They identified the standard coarse mode and two separate, previously unreported modes in
the 0.1 to 1.0 /*m range. This latter range was referred to by Whitby (1978) as a single
"accumulation" mode. John et al. (1990) described a "condensation" mode at 0.2 ± 0.1 /mi
containing gas phase reaction products, and a "droplet" mode at 0.7 ± 0.2 /*m which grows
from the "condensation" mode by the addition of water and sulfates. Fang et al. (1991)
described the effects of flow-inducted relative humidity changes on the sizing of acid aerosols
in the MOUDI impactor. They noted that it may not be possible to measure size
4-46
-------
00
S
I
00
a
'S
Fractional Retention
c
3
a.
n
a
»*•
i-
S'
0
o
1
O
ho 1
p-
co
-
P-
Ul_
*
B
n
o ~
g
1
a
9
>«
"O
5
I
C?
S
a.
3 ro
03 '
o"
O
CD
CD
o 3
-------
oo
100
80
^60
C/J
(/»
3
-------
distributions of small (less than about 0.2 to 0.5 /mi) particles with impactors at relative
humidities exceeding 80%.
4.2.7.2 Single Particle Samplers
Aerosol size distribution data are useful for studies of particle transport and
transformation processes, source characterization, and particle sizing and collection device
performance. In addition to cascade impactors, a number of real time or near real time
sizing instruments are available and described in texts such as Willeke and Baron (1993).
While cascade impactors provide distributions in terms of aerodynamically sized mass, single
particle sampling devices can produce optically sized distributions as a function of particle
number (count), with surface area and volume distributions computed during the data
reduction, assuming spherical particles. Particle density and shape information as a function
of size are required to convert from volume distributions to an estimated mass basis.
Individual particle sizing and counting instruments are generally limited to a particle
detection range of a decade or so, but several devices can overlap to cover the range of
approximately 0.001 to 10 /mi. The principle of detection of an instrument restricts the
particle sizes which can be detected. For example, instruments using electrical mobility
analysis are limited to particle sizes less than about 1 /mi. Optical methods are typically
used to measure particles larger than about 0.1 to 0.3 /mi. Inlet and transport system losses
of coarse particles above about 2 /mi, prior to the sensing volume, must be factored into
reported size distributions.
The three most commonly used single particle sampler types are aerodynamic particle
sizers, electrical mobility analyzers and optical particle counters (OPC's). Aerodynamic
particle sizers use laser doppler anemometry to measure the velocity of particles in a jet.
The acceleration of the particle is related to the aerodynamic particle diameter. This
technique is typically applied to particles larger than about 0.5 /mi. In electrical mobility
analysis, aerosol with a known charge distribution flows through an electric field. The
particles migrate according to their mobility which can be related to size. The original TSI
electrical aerosol analyzer (EAA) performed this separation in an integrated manner over the
total size distribution and detected the particles by unipolar diffusion charging. A more
versatile approach, the differential mobility analyzer or DMA (Liu et al., 1978), is able to
4-49
-------
examine a narrow slice of the size distribution in an equilibrium charge state, detected by a
condensation nucleus counter (CNC). Differential mobility analyzers have been employed in
pairs (Tandem Differential Mobility Analyzer, or TDMA) to examine both (a) particle
characteristics such as NH3 and H2SO4 reaction rates (McMurry et al., 1983) and (b) the
sensitivity of the size distributions of Los Angeles aerosol to relative humidity (McMurry and
Stolzenburg, 1989). The latter research used the first DMA to select particles of known
mobility from the input aerosol, a humidification system to condition the selected particles,
and the second DMA to determine mobility changes. Optical particle counters pass a jet of
aerosol through an optical system. Light scattered from individual particles is detected and
the signal in processed in a multi-channel analyzer. Discreet signals are counted and sorted
by intensity and by optical size. One example of a forward-scattering counter with an open
sensing volume (for use on aircraft) is the Particle Measuring Systems, Inc., FSSP-300,
which can provide high resolution (31 channel) count distributions over the size range of 0.3
to 20 fim (Rader and O'Hern, 1993). Gebhart (1993) described currently available OPC's
and their counting efficiencies over a range of diameters.
Single particle samplers have common considerations, as dicussed below.
Calibration: They are calibrated with reference aerosol either by the manufacture or by
the user. If the properties of the aerosol measured are quite different than the calibration,
the indicated size distribution may be quite different than actual distribution. Brockman
et al. (1988) demonstrated that the APS calibration can vary significantly with the type of test
aerosol and showed substantial response biases between oleic acid and polystyrene latex
spheres above 10 jan. Wang and John (1989) described a procedure to correct the APS
response for aerosol particle density. Particle shape can also provide serious sizing errors,
and specific calibrations are needed for particles with shape factors significantly different
from unity (spherical). Yeh (1993) commented that the calculated geometric standard
deviations (ag) determined by the EAA and DMA are generally larger than 1.3, even if the
correct value is significantly closer to unity. Woskie et al. (1993) observed, as did Willeke
and Degarmo (1988), that optical particle counting devices must be appropriately calibrated
using realistic aerosols, especially for low concentration applications. Harrison and Harrison
(1982) suggested that the ratio of fine particle mass concentration to optical scattering
4-50
-------
extinction will be more variable when a significant contribution is made by irregular (shaped)
particles - an event likely to occur when the mean mass diameter exceeds 1 /mi.
Particle Concentration Effects: Gebhart11993) noted that the response of single
particle counters may be influenced by extremely high particle concentrations. Wake (1989)
and Heitbrink et al. (1991) described the coincidence problems of the APS when sampling
high total particle concentrations, especially for sizes greater than 1 jum. Baron et al. (1993)
reported that the concentration levels giving 1 % coincidence in an aerodynamic particle sizer
for 0.8, 3 and 10 pm particles, respectively, are the relatively low values of 558, 387 and
234 particles/cm3. Optical particle counters can experience coincidence errors (two particles
are detected as a single particle) and counter saturation at high particle concentrations. Hinds
and Kraske (1986) described the performance of the PMS, Inc. LAS-X and noted a sizing
accuracy of ±2 channel widths, with coincidence errors of less than 10% for concentrations
below 10,000 particles/cm3. Clearly, typical particle concentrations found in the atmosphere
may produce significant errors if sample dilution is not utilized.
4.2.8 Automated Sampling
Automated methods to provide measures of aerosol concentrations in the air have
existed for decades in an attempt to provide temporal definition of suspended particles and
enhance every-sixth-day sampling schedules with a minimum labor expense. Arnold et al.
(1992) collected daily 24-h PM10 samples with an automated monitor and noted that 80% of
the highest 10 daily concentrations between 1989 and 1990 were not encountered by the
every-sixth-day sampling schedule. Some of the automated samplers (e.g., British Smoke
Shade and AISI tape samplers) described in the 1982 Criteria Document were indicator
measures of aerosol concentration, using calibrations relating aerosol concentrations to
reflected or absorbed light. Tape samplers were used in the U. S. primarily as exceedance
(index) monitors.
The beta attenuation and integrating nephelometer techniques described in the 1982
Criteria Document primarily were research methods. Since that time, the beta gauge
sampling approach has been refined and a new approach, based on the Tapered Element
Oscillating Microbalance (TEOM) principle, has been developed. Samplers based on these
techniques have been designated as equivalent methods for PM10.
4-51
-------
Although one could be readily constructed, there are presently no commercially
available, automated high volume (> 1 m3/min flowrate) aerosol samplers, excluding the
possibility of the timed operation of an array of manual samplers. The physical size of such
a sampling system using 8 x 10 inch filters is impractical. The dichotomous sampler is
currently the only low volume, gravimetrically-based sampler commercially available in an
automated version.
4.2.8.1 Smoke Shade (British Smoke, Black Smoke)
Historically, the British smoke shade sampler was one of the earliest ambient PM
sampling devices to be developed and to gain widespread use as an automated optical PM
monitoring method. Key features and limitations of the British or black smoke (BS) method
were discussed in EPA's 1982 Criteria Document. As indicated in Chapters 3 and 14 of that
Criteria Document, the BS method typically involves use of a sampler that draws ambient air
through an inverted funnel and approximately 3m of plastic tubing to deposit collected
particles on white filter paper. The amount of PM deposited during a given time period
(e.g., 1-h during severe episodes, or more typically, 24-h) is determined by measuring the
blackness of the stain on the filter paper. An automated version of the sampler can collect
daily samples sequentially for up to eight days.
It is important to note, as described in the 1982 Criteria Document, that the BS method
and its variations (e.g., the OECD version) in routine use typically employ standard
monitoring equipment with a D50 cutpoint =4.5 ^im, which mainly allows fine-mode particles
and small coarse mode particles (some ranging up to ~ 8 to 10 /urn) to be collected. Thus,
regardless of whether larger particles are present in the atmosphere, the BS method collects
predominately small particles. Also, the BS method neither directly measures mass nor
determines chemical composition of the collected PM. Rather, it measures light absorption
of particles as indicated by reflectance from the stain formed by the particles collected on the
filter paper, which depends both on the density of the stain, or amount of PM collected, and
the optical properties of the collected PM. Smoke particles composed of elemental carbon,
found in incomplete fossil-fuel combustion products, typically make the greatest contribution
to the darkness of the stain, especially in urban areas. Thus, the amount of elemental
carbon, but not organic carbon, present in the stain tends to be most highly correlated with
4-52
-------
BS reflectance readings. Other nonblack, noncarbon particles also have optical properties
such that they can affect the reflectance readings, although their contribution to optical
absorption is usually negligible.
Since the relative proportions of atmospheric carbon and noncarbon PM can vary
greatly from site to site or from one time to another at the same site, the same absolute BS
reflectance reading can be associated with markedly different amounts (or mass) of collected
particles or, in unusual circumstances, even with markedly different amounts of carbon.
Site-specific calibrations of reflectance readings against actual mass measurements obtained
by collocated gravimetric monitoring devices are therefore necessary to obtain estimates of
atmospheric concentrations of paniculate matter based on the BS method. A single
calibration curve relating mass or atmospheric concentration (in /xg/m3) of particulate matter
to BS reflectance readings obtained at a given site may serve as a basis for crude estimates of
the levels of PM (mainly small particles) at that site over time, so long as the chemical
composition and relative proportions of elemental carbon and noncarbon PM do not change
substantially. However, the actual mass or smoke concentrations present at a particular site
may differ markedly (by factors of two or more) from the values calculated from a given
reflectance reading on either of the two most widely used standard curves (the British and
OECD standard smoke curves)9. Thus, great care must be taken in interpreting the meaning
of any BS value reported in terms of y«g/m3, especially as employed in the British and other
European epidemiological studies discussed in Chapter 12 of this document.
There has existed long standing interest with regard to relationships between ambient
PM concentrations indexed by BS readings (based on conversion of reflectance values to
estimated jwg/m3 concentrations by means of standard calibration curves) and those obtained
by gravimetric methods. The 1982 Criteria Document noted that Ball and Hume (1977) and
Waller (1963) found that such relationships are site, season, and particle-source dependent.
Also, Lee et al. (1972) noted, from collocated TSP hi-vol and smoke shade sampler
9For this reason, smoke data reported in ^g/m3 based on either the British or OECD Standard curve are
appropriately interpreted in terms of "nominal" ftg/m3 smoke units and cannot be accepted as accurate estimates of
airborne PM mass unless corroborated by local site-specific gravimetric calibrations. In other words, unless based
on local site-specific calibrations, smoke readings in ;*g/m3 cannot yield quantitative estimates of atmospheric PM
concentrations. In the absence of such calibrations, smoke readings only allow for rough qualitative (i.e., <; =;
or >) comparisons of amounts of PM present at a given time versus another time at the same site and do not permit
meaningful comparisons between PM levels at different geographic areas having airborne PM of different chemical
composition (especially in terms of relative proportions of elemental carbon).
4-53
-------
comparisons made at various sites in England, that the overall correlation coefficients
between these measurements for all sites was 0.618. However, the individual coefficients
ranged from 0.936 (good correlation) to 0.072 (no correlation). Bailey and Clayton (1980)
showed that smoke shade measurements correlated more closely with soot (elemental carbon)
content than with gravimetric mass. Other work by Paschel and Egner (1981) and Clayton
and Wallin (1982) showed consistently higher TSP values than BS readings (converted to
/jg/m3) from collocated samplers in various U.S. and U.K. cities, respectively (as would be
expected given that the BS measurements of fine and small coarse mode particles typically
represent only some fraction of the wider range of particles sampled by TSP measurements).
Clayton and Wallin (1982), not surprisingly, also found widely variable ratios of TSP to BS
readings from different U.K. cities reflecting the varying proportions of small particles
present in the total ambient mix of particles at different sites. Likewise, varying (site- and
season-dependent) relationships between BS measurements and ambient PM measurements
made by various gravimetric methods have been reported in the Federal Republic of
Germany (Laskus, 1983) and in the semi-arid climate of Baghdad, Iraq (Kanbour et al.,
1990). Lastly, Muir and Laxton (1995) reported that, for Bristol (a moderate size U.K.
city), daily average BS (averaged over six urban background sites) appears to be a reasonable
predictor of daily average PM10 and daily 1-h peak PM10 values; but different relationships
apply for winter versus summer, indicating that BS and PM10 measure different components
of airborne PM (i.e., BS may be a better index of fine-mode particles than PM10, which has
a D50 cutpoint of = 10 /mi).
Only limited examples exist of derivation of models of interrelationships between BS
readings and gravimetric measurements for particular time periods in a given location. For
example, see Mage (1995) for discussion of an empirical model relating BS to TSP values
during London winters of the 1950s and 1960s.
4.2.8.2 Coefficient of Haze (AISI/ASTM Tape Sampler)
The 1982 Criteria Document also described a second type of automated optical PM
measurement methods. Developed before 1940, the American Iron and Steel Institute (AISI)
light transmittance method is similar in approach to the BS technique and has been employed
for routine monitoring in some American cities. The instrument collects particles with a D50
4-54
-------
cutpoint of =5.0 /xm aerodynamic diameter and uses an air intake similar to that of the BS
method. Ambient PM is collected on a filter-paper tape that is periodically advanced to
allow accumulation of another stain. Opacity of the stain is determined by transmittance of
light through the deposited material and the tape. The results are expressed in terms of
optical density or coefficient of haze (CoH) units per 1,000 linear feet of air sampled (rather
than in mass units). Readings in CoH units are somewhat more responsive to noncarbon
particles than are BS measurements; but, again, the AISI method neither directly measures
mass nor determines chemical composition of the PM collected. Any attempt to relate CoHs
to j«g/m3 requires site-specific calibration of CoH readings against mass measurements
determined by a collocated gravimetric device, but the accuracy of such mass estimates are
still subject to question.
Few attempts have been reported on calibration of COH measurements versus results
from collocated gravimetric devices. One notable attempt (Ingram, 1969; Ingram and
Golden, 1973) was reported for New York City, but the results are of very limited
applicability to New York City aerometric data of the 1960's. Also, Regan et al. (1979)
showed that CoH readings correlate favorably with gravimetric measurements limited to
smaller particle sizes. Edwards (1980) and Edwards et al. (1983) have also shown that BS
reflectance measurements can be related to the absorption coefficient of the atmosphere and
that BS measurements can be converted to approximate CoH measurements made by AISI
tape sampler using the absorption coefficient relationships. As several investigators noted,
(e.g., Lodge, et al., 1981), if a relationship could be developed between optical and
gravimetric measurements, it would be site specific, but still variable because of seasonal and
long-term differences in the sources of collected particle size fractions and their carbon
content.
4.2.8.3 TEOM® Sampler
The Tapered Element Oscillating Microbalance (R & P, Inc.) sensor, as described by
Patashnick and Rupprecht (1991), consists of an oscillating tapered tube with a filter on its
free end (see the diagram in Figure 4-15). The change in mass of the filter and collected
aerosol produces a shift in the oscillation frequency of the tapered tube that is directly related
to mass. Rupprecht et al. (1992) suggested that the filter can be archived after sampling for
4-55
-------
Flow
Flow
Sampling Head
Heated Air Inlet
Filter Cartridge
Tapered Element
Electronic
Feedback System
'
Microprocessor
to Flow Controller
Figure 4-15. Rupprecht and Patashnick TEOM® sampler.
Source: Patashnick and Rupprecht (1991).
4-56
-------
subsequent analysis. The sampler inlet has a PM10 cutpoint and operates at 16.67 1pm.
A flow splitter samples a 3 1pm portion of this flow to be filtered. Since the fraction of
volatile species (e.g., water, nitrates, organics) in the aerosol is a function of ambient
temperature, the TEOM® sampler heats the inlet air stream to a constant 30 or 50 °C to keep
moisture in the vapor phase. The mass transducer is also heated to 50 °C to stabilize the
measurement process. Operation with the flow stream heated to a lower temperature
(e.g., 30 °C) is possible, but care must be taken to avoid moisture condensation that will
confound the measurement. The transducer is also heated to 50 °C to stabilize the mass
measurement. A factory calibration regression is used to electronically correct the computed
mass from the TEOM® sampler to that measured by a reference PM10 sampler.
Although several studies (e.g. Patashnick and Rupprecht, 1991; Kalthoff and Grumpier,
1990) have shown consistent and linear relationships between the TEOM® sampler and
gravimetric PM10 samplers, a number of studies have shown biases under certain conditions.
Several researchers, including Cahill et al. (1994), Hering (1994) and Meyer et al. (1992)
have reported that the modification of the aerosol by the elevated operating temperature
appears to have a significant effect (loss) on mass concentration. Meyer et al. (1992)
collocated a TEOM® sampler with an PM10 SA1200 gravimetric sampler in Mammoth
Lakes, CA during a winter heating season (heavy wood stove usage). The regressions
between the TEOM® sampler and PM10 sampler gave strong correlations (r2 > 0.98), with
slopes of 0.55 for operation at 50 °C, and 0.66 for operation at 30 °C. The negative bias of
the TEOM was attributed primarily to losses of semi-volatile organics from the filter.
Cahill et al. (1994) reported that the TEOM® sampler showed biases on the order of 30%
low and poor correlations with PM10 samplers in dry, dusty conditions. The reasons for this
discrepancy were unknown. The field comparison data of Patashnick and Rupprecht (1990)
showed near unity (1 ± 0.06) regression slopes for the TEOM with the Wedding IP10 and
Sierra-Andersen dichotomous samplers in El Paso, TX and Birmingham, AL. Since aerosol
composition is highly dependent on local sources and meteorology, volatilization losses could
be expected to be site- and season-dependent. This could significantly affect the rigor of
collocated field sampling. A WESTAR (1995) council report summarizes the relationships
between TEOM® monitors and other direct gravimetric samplers in at least 10 states in the
western U.S. This report concluded that on average the TEOM® sampler concentrations
4-57
-------
were 21.8% Lower than other collocated PM10 samplers for concentrations > 50 /ig/m3.
This would significantly affect the TEOM® sampler's ability to be used as a "trigger"
monitor for control strategy plans. More data are needed to determine the implications of
these problems on the ability of the TEOM® sampler to be used in a regulatory setting.
Although it is clear that the TEOM® sampler can provide PM10 data comparable to the
existing reference method samplers, the specific field sampling conditions where excessive
bias might be expected to occur have not been completely defined. A portion of the bias is
undoubtedly due to concomitant variabilities in the associated gravimetric measurements.
4.2.8.4 Beta Gauge
The Andersen FH 62I-N beta attenuation sampler was described by Merrifield (1989)
and uses a 30 mCi Krypton-85 source and detector to determine the attenuation caused by
deposited aerosols on a filter (see diagram in Figure 4-16). To improve the stability over
time, a reference reading is periodically made of a foil with an attenuation similar to that of
the filter and collected aerosol. The Wedding beta attenuation sampler was described by
Wedding and Weigand (1993) and uses a 100 mCi 14C source. Both samplers have inlets
with a PM10 cutpoint, with the Andersen sampler operating at 16.67 1pm and the Wedding at
18.9 1pm. The filter material is contained on a roll and advances automatically on a time
sequence, or when a preset aerosol loading is reached. An automatic beta gauge sampler
was also described by Spagnolo (1989), using a 15 />im inlet and a 14C source. The
calibration of a beta gauge is site specific, and a calibration regression must be processed
electronically to provide accurate mass readings. Rupprecht et al. (1992) suggested that the
closer link between deposited mass and frequency shift for the TEOM principle should
provide less site-specific response, compared to the aerosol compositional sensitivity of the
beta gauge technique.
Arnold et al. (1992) provided data over a 2 year period in Denver, CO for the mass
concentration regression data from a Wedding beta gauge, showing a range of correlations
(r2 from 0.72 to 0.86), varying by sampler and season. The authors suggested that
installation of a newer technology beta gauge accounted for the higher correlations, but noted
that unexplained outliers resulted in poorer than expected results. The regression slopes
between the two sampler types showed that the beta gauge averaged 19% lower than a
4-58
-------
MC
CC
C
Measuring Chamber
Compensation Chamber
Chamber for Dust Precipitation
and Measurement
30 m Ci KR-85 Source
Filter Feed Spool
Filter Takeup
High-Voltage Power Supply
mperature / Pressure
Bit
I/O
50-Pin
Connector
V24/RS232
Rotary Vane Pump
Figure 4-16. Andersen beta gauge sampler.
-------
collocated Wedding PM10 gravimetric sampler. It should be noted that the Wedding PM10
inlet has typically been reported (see Section 4.2.2.4) to be 10 to 15% lower in collocated
field tests with Sierra-Andersen PM10 inlets. A WESTAR (1995) council report summarizes
the relationships between beta gauge monitors and other direct gravimetric samplers in at
least five states in the western U.S. This report concluded that on average beta gauge
concentrations were 8.6% lower than other collocated PM10 samplers for concentrations
> 20 pig/m3. Field data from Wedding and Weigand (1993) at two sites (Fort Collins, CO
and Cleveland, OH) using the same samplers produced regressions exhibiting strong
correlations (r2 = 0.99) with no apparent outliers and a composite slope of 1.00.
Arnold et al. (1992) operated the PM10 high volume samplers on the required every-6th-day
schedule and the beta attenuation monitors continuously, and noted that only 22.5% of the
exceedance days, as measured by the beta monitor, were operational days for the high
volume samplers.
4.2.8.5 Nephelometer
The integrating nephelometer is commonly used as a visibility monitor; it measures the
light scattered by aerosols, integrated over as wide a range of angles as possible.
A schematic diagram of the integrating nephelometer is shown in Figure 4-17 (from Hinds,
1982). The measured scattering coefficient of particles, bsp, can be summed with the
absorption coefficient, bap, and the comparable coefficients for the gas phase to compute the
overall atmospheric extinction coefficient, bext. Methods for estimating absorption and
extinction for atmospheric particles are discussed in 8.2.2. The atmospheric extinction has
been related to visibility as visual range. The particle scattering coefficient is dependent
upon particle size, index of refraction and illumination wavelength, as shown by Charlson
et al. (1968) in Figure 4-18, while the absorption coefficient is relatively independent of size.
The field calibration of nephelometers has historically been based on the refractive index of
Freon-12 (and occasionally carbon dioxide), but newer calibration procedures using atomized
sugar aerosols have been proposed (Horvath and Kaller, 1994) as more environmentally
conscious. Nephelometry over a narrow wavelength band or at a selected wavelength can be
applied to measure the laser light scattered from a volume of aerosol containing a number of
4-60
-------
o\
Power
Supply
Flash Tube
Power Supply
Clean Air
Purge
Photomultiplier
Tube
Amplifier
Aerosol
Outlet
Collimating
Disks
Recorder
t
€Z9-X)pal Glass
Scattering
Volume
I A I
Aerosol
Inlet
Clean Air
Purge
Figure 4-17. Integrating nephelometer.
Source: Hinds (1982).
-------
10
oo
CO
g
-------
particles. Gebhart (1993) described devices such as the MIE, Inc.10. MINIRAM, often
used in portable applications to estimate real-time aerosol concentrations. Cantrell et. al.
(1993) showed that MINIRAM calibration was significantly different for diesel and mine
aerosols. Woskie et al. (1993) described the performance of a MINIRAM (using the
manufacturer's calibration) against gravimetric borate concentrations for particles as large as
30 pim, and found significant biases (a regression slope = 4.48). This bias was expected,
since the large mass median particle diameters were substantially outside the respirable
particle range recommended by the manufacturer.
The relative insensitivity of the nephelometer to particles above ~ 2 /*m results in poor
correlations with PM10 mass. Larson et al. (1992) showed strong correlations (r2 = 0.945)
between bsp and fine fraction mass (see Figure 4-19) for a woodsmoke impacted
neighborhood near Seattle, WA, with a slope of 4.89 m2/g. They noted that this slope fell
within the range of values reported by others and was predicted by Mie scattering theory.
The slope of the Larson et al. (1992) data could be compared with other site-specific
calibrations, such as the data of Waggoner and Weiss (1980), which gave a composite slope
of 3.13 m2/g, characterized by the authors as representative of a "wide range" of sites.
Lewis (1981) provided an analysis of the relationships of the features of the ambient size
distribution to bsp. The inlet air stream to the nephelometers for the latter data was heated
from 5 to 15 °C above background. Rood et al. (1987) conducted a controlled comparison
of the influence of aerosol properties on bsp in Riverside, CA and reported a regression
slope against fine mass (defined as less than 2.0 /xm) of 2.1 m2/g with an r2 value of 0.92.
In this experiment, the relative humidity for bsp determinations was controlled to less than
35% and the gravimetric filter substrate was nylon. The authors attributed the smaller than
normal slope reading to possible nitrate evaporation from the filtered aerosol and artifact
reactions with the nylon substrate material. Thomas et al. (1993) demonstrated that the
influence of relative humidity on the relationship between photometer response and collocated
gravimetric particle concentrations can be predicted.
The data scatter in Figure 4-19 (if assumed to be typical of such comparisons) would
suggest that fine particle mass concentration estimates from bsp values were typically within
5 to 7 fig/m3 of the gravimetrically determined values. To be useful as a surrogate measure
10Bedford, MA.
4-63
-------
2.2
2.0
1.8
1.6
1.4 -
1.2 -
1.0 -
0.8 -
0.6 -
0.4 -
0.2 -
0
Lake Forest Park
Weekly Average Values
January 17,1991 to December 19,1991
Slope = 4.89m /g
R2= 0.945
10
15
20
25
30
35
40
45
Figure 4-19. Correlation of bsp and fine fraction mass.
Source: Larson et al. (1992).
for mass concentration, the site-specific nephelometer calibration should be valid for a wide
range of situations, especially during episodes where the concentration levels approach or
exceed an action limit. The scattergram of b versus fine particle mass provided by Rood
et al. (1987) showed much greater variability, with a given bsp value providing an estimated
20 to 25 jLtg/m3 concentration range. They noted that metastable H2O contributed 5 to 20%
of the total particle light scattering coefficient, especially during the late afternoon and early
evening. The precisions and biases of the dependent and independent variables between bsp
4-64
-------
and fine mass concentration are not constants, since at least one factor - moisture content of
the aerosol - affects both measures. The gravimetric sample filters are typically equilibrated
to a specific relative humidity range (e.g., 40 to 60%) to normalize the tare weighings.
Sloane (1986) and others have noted that light scattering from particles is not solely a
function of mass but are also very dependent on a summation of the scattering coefficients of
each species. The scattering cross section of a particle is dependent on the water content,
and, hence, the relative humidity in situ. Pre-heating of the inlet air of the nephelometer
normalizes the response to water content, but biases the reading relative to the in situ case.
Sloane (1986) also gave the computed and measured scattering coefficients for ammonium
sulfate and noted that chemical interactions can cause a two-fold variation in scattering
response to a change in the mass of hygroscopic constituents. It was also observed that the
light scattering efficiency of an aerosol such as ammonium acid sulfate is not a constant, but
varies with the overall aerosol composition. Eldering et al. (1994) developed and validated a
predictive model for bsp in Southern California. This model used composite size
distributions constructed from a TSI, Inc.11 EAA, a PMS, Inc.12 LAS-X and a Climet,
Inc.13 multi-channel OPC, and filter-based estimates of refractive indices for ammonium
sulfate, ammonium nitrate, organic carbon, elemental carbon and residual aerosol mass
concentrations as independent variables. The quality of their comparisons with nephelometer
data suggested that this approach could be used to test models that predict visual range from
source emissions. Further research is needed to determine the effectiveness of the integrating
nephelometer as a predictor of fine particle mass concentrations.
4.2.9 Specialized Sampling
4.2.9.1 Personal Exposure Sampling
The application of aerosol measurement technologies to smaller and less obtrusive
samplers have resulted in devices used as fixed-location indoor aerosol samplers and personal
exposure monitors (PEMs) worn on the body to estimate exposure. The reduction in
physical size of personal aerosol sampling systems to reduce participant burden sometimes
11 Minneapolis, MN.
I2Boulder, CO.
13Redlands, CA.
4-65
-------
results in poorer aerosol collection performance as compared to the outdoor counterparts.
Wiener and Rodes (1993) noted that personal sampling systems generally have poorer
precisions than outdoor aerosol samplers, due to the smaller sampler collections (from lower
flowrates) and poorer flow controllers. Ozkaynak et al. (1993) reported that the precisions
of collocated PEMs in the PTEAM study operating at 4.01 pm for a 12-h period were 3 to
4% (RSD). Wallace et al. (1994) reported biases for the Particle Total Exposure Assessment
Methodology study averaging a factor of two between personal exposure measurements and
fixed location PM10 concentrations. He was unable to completely account for the biases, but
attributed portions to proximity to indoor sources, a difference in inlet cutpoints (11.7 pan
versus 10.0 /mi) and the collection of aerosols from the "personal cloud" caused by body
dander. Rodes et al. (1991) showed that the ratio of personal to indoor aerosol
measurements for the EPA PTEAM study appeared to be log-normally distributed with a
median value of 1.98 and an unexpectedly high value of 3.7 at the 90th ("most exposed")
percentile. Ingham and Yan (1994) suggested that the performance of a personal aerosol
sampling inlet in an isolated mode (without mounting on a representative humanoid bluff
body) can result in substantial under-sampling for larger particles. The relationship between
measured aerosol exposure at some external location on the body and actual uptake through
oral and nasal entry is very complex.
Buckley et al. (1991) described the collection efficiency of an MSP, Inc.14 personal
aerosol sampler at 4.0 1pm as shown in Figure 4-20. They evaluated this sampler in a field
comparison study with collocated PM10 high volume and dichotomous samplers. The
precision for the personal sampler was found to be very good (CV = +3.2%) with strong
correlations (r2 = 0.970) with the dichotomous samplers. Lioy et al. (1988) described a
similar comparison for a 10 1pm Air Diagnostics and Engineering, Inc.15 indoor air
sampler, with a PM10 inlet characterized by Marple et al. (1987). Correlations against the
PM10 dichotomous sampler were also described as very strong (r2 > 0.970), but noted a
substantial bias caused by the loss of fragments from indoor air sampler's glass fiber filters.
They recommended that exposure studies using samplers that collect small total volumes
should utilize filters with greater integrity, such as Teflon. Colome et al. (1992) describe an
14Minneapolis, MN.
15Naples, ME.
4-66
-------
100
80
I" 60
o>
o
- 40
20
o
O
1
10
Aerodynamic Particle Diameter (urn)
Figure 4-20. Collection efficiency of the MSP personal aerosol sampler inlet.
Source: Buckley et al. (1991).
indoor/outdoor sampling study using an impactor characterized by Marple et al. (1987) with
a PM10 cutpoint that had duplicate impactors with the same cutpoint in series. This
sequential arrangement, in combination with a coating of 100 jul of light oil, was used to
minimize particle bounce at 4.0 1pm for 24 h period.
Personal aerosol sampler systems have typically been characterized as burdensome
(excessive weight, size, noise). The success of passive detector badges for gaseous
pollutants has recently prompted research into passive aerosol samplers. Brown et al. (1994)
described a prototype aerosol sampler utilizing electrostatic charge to move the particles to a
collection substrate. They noted that preliminary results are encouraging, but the effective
sampling rate and size-selectivity of the sampler was dependent on the electrical mobility of
the aerosol. This posed calibration problems for real aerosols with a distribution of electrical
4-67
-------
mobility's. Hollander (1992) described a passive pulsed-corona sampler that has similar
collection characteristics as a PM10 inlet, with only modest wind speed dependence.
The performance characterization of PEMs has been considered for occupational
settings by Kenny and Liden (1989), who reviewed the ACGIH, National Institute for
Occupational Safety and Health (NIOSH), and EPA PM10 aerosol sampler performance
programs. They proposed that an international consensus be reached on the basic principles
underlying the experimental protocols for testing personal samplers, as an essential
prerequisite to the setting of standards. An ISO working group has made progress in
developing such a consensus (Kenny, 1992). As EPA becomes more focused on exposure
assessment and personal exposure sampling, it will become even more important for the
agency to consider establishing performance specifications for personal aerosol samplers.
Models have become powerful tools in understanding aerosol behavior in the vicinity of
personal exposure samplers. This is demonstrated by particle trajectory models that can
predict the influences of the geometries and flow field on aerosol capture and losses (e.g.,
Okazaki and Willeke, 1987, Ingham and Yan, 1994, and Tsai and Vincent, 1993). These
models have not only permitted more rapid design changes to accommodate new cutpoints
and flowrates, but have added insights as to the influence of air flow obstructions on
sampling efficiencies. Vincent and Mark (1982) suggested that there is a critical particle
trajectory that determines whether a particle is sampled or rejected by an inlet worn on the
body. An extension of this model applicable to personal exposure sampling by Ingham and
Yan (1994) suggested that testing the performance of a personal aerosol sampling inlet in an
isolated mode (without mounting the inlet on a representative bluff body) can result in under-
sampling for larger particles by a factor of two. Validation of this model may explain a
portion of the bias reported by Wallace et al. (1994) between personal and indoor sampler
measurements.
4.2.9.2 Receptor Model Sampling
Receptor modeling has become an established tool to relate ambient concentrations of
pollutants to major source categories, by apportioning the components in collected ambient
aerosol samples using complimentary source "signatures". Various approaches developed for
constructing source/receptor relationships were described by Henry et al. (1984), who also
4-68
-------
provided a review of modeling fundamentals. They listed the advantages and disadvantages
of multivariate models and discussed multi-collinearity problems associated with the presence
of two or more sources with nearly identical signatures. Javitz et al. (1988) described the
basic Chemical Mass Balance (CMB) approach and showed the influence of the variance in
identifying a component in the source signature sample on the projected apportionment.
Dzubay et al. (1984) described aerosol source and receptor collection schemes that permitted
the separation of ambient samples into fine and coarse fractions for mass, elemental and
volatile carbon, and metals analyses. Stevens and Pace (1984) suggested the addition of
Scanning Electron Microscopy to permit additional categorization using x-ray diffraction
analysis. The most widely used aerosol receptor model is the EPA CMB 7.0 model
described by Watson et al. (1990). This paper describes the structure of the model and
computer code and the data requirements to evaluate the validity of the estimates. Numerous
papers have been published describing the applications of receptor models to the
apportionment of the sources of aerosols, with the receptor modeling conference summary by
Watson et al. (1989b) descriptive of the state-of-the-art.
Stevens et al. (1993) described (see Figure 4-21) a modified dichotomous sampler with
a PM10 inlet, two Fine channels operating at 15 1pm and one coarse channel operating at
2.0 1pm, designated as the Versatile Air Pollution Sampler (VAPS). The additional fine
fraction channel permitted sampling on a 47 mm Teflon filter for elemental analysis and a
47-mm quartz filter for carbon speciation (elemental and volatile). A Nuclepore filter was
used on the Coarse channel for Scanning Electron Microscopy (SEM) evaluation and energy
dispersive x-ray diffraction analysis for selected particles.
4.2.9.3 Particle Acidity
An emphasis was placed on sampling sulfuric acidic aerosols in the 1982 Criteria
Document. This was followed by a number of research efforts (e.g., Perm, 1986; Koutrakis
et al., 1988; Pierson et. al., 1989) to identify and study the in situ rate reactions, develop
sampling strategies to representatively remove the acid particle from the air, identify the
co-existing reactive species (e.g., ammonia, nitric acid, aerosol sulfates and nitrates), and
protect the collected aerosol prior to analysis. A "Standard" and an "Enhanced" method
were subsequently described (U.S. Environmental Protection Agency, 1992) for the
4-69
-------
32 l/min
-p.
o
25-urn Cut Annular Denuder Teflon Filter
Receiver Jet Collects Mass,H+,
(VAPS Body) SO0, HNCL, HCI Elemental Composition
Accelerator
Jet
VAPS Impactor
10-(imCut
Impactor Press
#47 FP
Adapter
PUF Adapter
with Quick
Disconnect to
Vacuum Pump
PUF Trap
80 mm x 32 mm
Figure 4-21. Modified dichotomous sampler (YAPS).
Source: Stevens et al. (1993).
-------
determination of aerosol acidity (titratable H+) using annular denuder technology. The
"Standard" method did not account for potential interferences from nitric acid, ammonium
nitrate aerosol, or other ammonium salts. The "Enhanced" method added an additional
denuder prior to filtration, with nylon and treated glass fiber backup filters to account for
these species. These sampling technologies utilized either an inlet impactor or a cyclone with
2.5 /tfn cutpoints to sample the fine fraction. This technology has recently been extended to
other reactive aerosol systems, including semi-volatile organics (e.g., Vossler et al., 1988).
Bennett et al. (1994) describe a PM2 5 cyclone-based, filter pack sampling system designed
for fine particle network sampling and acidity measurements, as part of the Acid MODES
program. The sampler operated at 8.8 1pm, and was designed to selectively remove
ammonia, speciate gas and particle phase sulfur compounds, as well as collect gas phase
nitric acid. An intercomparison of 18 nitric acid measurement methods was reported by
Hering et al. (1988), who noted that measurements differed by as much as a factor of four
and biases increased as nitric acid loadings increased. In general the filter pack systems
reported the highest acidity measurements, while the denuder-difference techniques reported
significantly lower measurements. Benner et al. (1991) in a comparison of the SCENES
filter pack sampler with a denuder-based sampler found excellent agreement between sampler
types for both nitric acid and total nitrates. They attributed the close agreement to limited
positive artifact formation, since the test field site had high nitric acid gas to particulate
nitrate ratios. John et al. (1988) noted that internal aluminum sampler surfaces denude nitric
acid, and describe the design of an aluminum denuder for the inlet of a commercially
available dichotomous sampler to quantitatively remove nitric acid for extended periods.
Brauer et al. (1989) describe the design of a miniature personal sampler to collect acid
aerosols and gases. A significant finding was the lower than expected personal acidity
levels, attributed to the "personal cloud" production of ammonia by the body. Personal
exposure levels of acid aerosols were reported to be lower than indoor measurements.
4.2.10 Measurement Method Comparisons
4.2.10.1 Nitrate
Methods for measuring particle nitrate and gaseous nitric acid were compared in the
field as part of the 1985 Nitrogen Species Methods Comparison Study conducted over an
4-71
-------
8-day period in the summer of 1985 in Claremont, CA (Bering et al., 1988). Particle nitrate
methods included sampling with filter packs (teflon and nylon filters operated in series),
sampling with nylon or impregnated filters operated downstream of a denuder to remove
vapor nitric acid (Possanzini et al., 1983; Shaw et al., 1982; Appel et al., 1981), and
sampling with an impactor (Wall et al., 1988). Results from that study showed that the
precision for identical samplers was about 4% (Anlauf et al., 1988; Solomon et al., 1988).
Denuded nylon filter methods were used in 6 different samplers operated by 4 different
groups (Appel et al., 1988; John et al., 1988; Pierson et al., 1988; Solomon et al., 1988).
Data from these 6 methods show no systematic bias among samplers. The average
measurement precision (coefficient of variation) was 11%. Impactor results were also in
agreement with that from the denuded nylon filters (Wall et al., 1988). In contrast, fine
particle nitrate values from teflon filter of the filter packs were 43 to 59% lower than those
measured by denuded nylon filters, with higher discrepancies for longer sampling times
(Soloman et al., 1988). The lower results on filter pack sampling are due to the
volatilization of nitrate particles from the filter. The vaporized nitrate is measured as nitric
acid on the backup filter (Hering et al., 1988; Solomon et al., 1988). To summarize,
sampling with denuded nylon filters or with impactors gave equivalent values for fine particle
nitrate, whereas teflon filter sampling was biased low due to the volatilization losses.
The results of the 1985 Nitrogen Species Methods Comparison Study were confirmed
by data collection as part of the 1987 Southern California Air Quality Study (Chow et al.,
1994). In this study, sampling times were 4 to 7 h. Samples were retrieved immediately,
within 30 minutes of the end of sampling. Fine particle samples were collected by teflon
filters, by denuded nylon filters and by impactors. Results, stratified by time of day and
season, are illustrated in Figures 4-22 and 4-23 for central Los Angeles, CA and Claremont,
CA, respectively. Losses from the teflon filters are greatest in the summer, especially for
daytime samples (10 a.m. to 2 p.m., and 2 p.m. to 6 p.m.). Over 11 summer sampling days
at 8 basin locations for Claremont, CA, an average of 79% or 9.9/ng/m3 of the fine particle
nitrate was volatilized from the teflon filters for summer daytime sampling. For nighttime
and morning samples, 40% was lost. The percentage losses are smaller for winter samples,
but the absolute magnitude remains high at 8.9 /xg/m3 for daytime samples. Impactor data
are in much closer agreement with those from the denuded nylon filter than the teflon filter.
4-72
-------
40r
Central Los Angeles: Summer
A 30--
20--
z
I
il
o
in
cvi
Summer: Night
Summer: Morning
O Summer: Day
- 1:1 Line
10--
80--
70--
10 20 30
PM2.5 Denuded Nylon Filter Nitrate (ng/rn3)
Central Los Angeles: Winter
• Winter: Night
• Winter: Morning
O Winter: Day
- 1:1 Line
10 20 30 40 50 60 70
PM2.5 Denuded Nylon Filter Nitrate (ng/rn3)
80
Figure 4-22. Comparison of PM2.5 nitrate mass measurements from Teflon® filter
versus denuded nylon filter sample collection for Los Angeles, CA.
Source: Chow, et al. (1994).
4-73
-------
40-r
Filter Comparisons for Claremont: PM2.5 Nitrate
Summer: Night
Summer: Morning
O Summer: Day
- 1:1 Line
40r
CO
I
~ 30
20--
Q.
o
E 10--
10 20 30
PM2.5 Denuded Nylon Filter Nitrate (iig/nr?)
Impactor Comparison for Claremont: PM2.5 Nitrate
• Summer: Night
® Summer: Morning
O Summer: Day
- 1:1 Line
10 20 30
PM2.5 Denuded Nylon Filter Nitrate
40
Figure 4-23. Comparison of PM2 5 nitrate mass measurements from Teflon® filter
versus denuded nylon filter sample collection for Claremont, CA.
Source: Chow, et al. (1994).
4-74
-------
4.2.10.2 Carbonaceous Particulate Matter
Methods for measuring carbonaceous aerosol, classified as either "organic" or "black"
carbon, were compared in a similar study conducted in the summer of 1986 in Glendora, CA
(Bering et al., 1990). In that study, analytical methods were compared, as were differences
in simultaneous ambient sampling of PM2 5 aerosol with quartz filters, adsorption-corrected
quartz filters and two types of impactors. The results showed generally good agreement
among analytical methods for total carbon, with 5 of the 6 laboratories reporting values
within 9% of each other. In contrast, ambient sampling results showed variations among
methods. Quartz filter results, whether or not corrected for carbon vapor adsorption were
within 40% of each other. Concentrations from impactors, exclusive of after-filter, were
lower than the mean from the filter samplers by as much as 50%. Addition of the after-filter
carbon brought impactor values to within 10% of the mean, but the lack of "black" carbon
on these after-filters leads to the conclusion that vapor adsorption led to a positive bias for
quartz filter sampling on these days. Similar results were found for the 1987 Southern
California Air Quality Study, for which impactor measurements of carbon were
systematically lower than filter measurements (Chow, et al., 1994).
4.3 ANALYSIS OF PARTICULATE MATTER
The interest in the composition of aerosol particles lies in the areas of: (1) explaining
and inventorying the observed mass, (2) establishing the effect of aerosols on health and
welfare, and (3) attributing ambient aerosols to pollution sources. While any compositional
measurement will address one or more of these goals, certain methods excel for specific
tasks. In general, no single method can measure all chemical species, and comprehensive
aerosol characterization programs use a combination of methods to address complex needs.
This allows each method to be optimized for its objective, rather than be compromised to
achieve goals unsuitable to the technique. Such programs also greatly aid quality assurance
objectives, since confidence may be placed in the accuracy of a result when it is obtained by
two or more methods on different substrates and independent samplers.
In the sections that follow, some of the more commonly used methods that address the
goals stated above are described. The sections are designed to be illustrative rather than
4-75
-------
exhaustive, since new methods are constantly appearing as old methods are being improved.
These chemical analysis methods for the following section are divided into four categories:
(1) mass, (2) elements, (3) water-soluble ions, and (4) organics. Material balance comparing
the sum of the chemical species to the PM mass concentrations show that elements, water
soluble ions, and organic and elemental carbon typically explain 65 to 85% of the measured
mass and are adequate to characterized the chemical composition of measured mass for filter
samples collected in most urban and non-urban areas. Some of these chemical analysis
methods are non-destructive, and these are preferred because they preserve the filter for
other uses. Methods which require destruction of the filter are best performed on a section
of the filter to save a portion of the filter of other analyses or as a quality control check on
the same analysis method. Table 4-2 identifies the elements and chemical compounds
commonly found in air using these methods with typical detection limits.
Less common analytical methods, which are applied to a small number of specially-
taken samples, include isotopic abundances (Jackson, 1981; Currie, 1982; Hirose and
Sugimura, 1984); mineral compounds (Davis, 1978, 1980; Schipper et al., 1993); and
functional groups (Mylonas et al., 1991; Palen et al., 1992; 1993; Allen et al., 1994).
Recent advances in infrared optics and detectors have resulted in the quantitative
determination of the major functional groups (e.g., sulfate, nitrate, aliphatic carbons,
carbonyl carbons, organonitrates, and alcohols) in the atmospheric aerosol (Allen et al.,
1994). The advantages of functional analysis in source apportionment are that the number of
functional groups is much less than the number of organic compounds to be classified. The
cited references provide information on sampling and analysis methods for these highly-
specialized methods.
The following section focuses on:
• Physical analysis of elements and single particle size, shape, and composition,
• Wet chemical analysis of anions and cations, and
• Organic analysis of organic compounds and elemental/organic carbon.
4-76
-------
TABLE 4-2. INSTRUMENTAL DETECTION LIMITS FOR
PARTICLES ON FILTERS
Minimum Detection Limit in ng/m3a
Be
Na
Mg
Al
Si
P
S
Cl
K
Ca
Sc
Ti
V
Cr
Mn
Fe
Co
Ni
Cu
Zn
Ga
As
Se
Br
Rb
Sr
Y
Zr
Mo
Pd
Ag
Cd
In
Sn
ICP/
AESM
0.06
NA
0.02
20
3
50
10
NA
NA
0.04
0.06
0.3
0.7
2
0.1
0.5
1
2
0.3
1
42
50
25
NA
NA
0.03
0.1
0.6
5
42
1
0.4
63
21
AA
FlameM
2d
0.2d
0.3
30
85
100,000
NA
NA
2d
ld
50
95
52
2
1
4
6d
5
4
1
52
100
100
NA
NA
4
300
1000
31
10
4
1
31
31
AA
Furnace13
0.05
< 0.05
0.004
0.01
0.1
40
NA
NA
0.02
0.05
NA
NA
0.2
0.01
0.01
0.02
0.02
0.1
0.02
0.001
NA
0.2
0.5
NA
NA
0.2
NA
NA
0.02
NA
0.005
0.003
NA
0.2
INAAb-f
NAh
2
300
24
NA
NA
6,000
5
24
94
0.001
65
0.6
0.2
0.12
4
0.02
NA
30
3
0.5
0.2
0.06
0.4
6
18
NA
NA
NA
NA
0.12
4
0.006
NA
PIXE«
NA
60
20
12
9
8
8
8
5
4
NA
3
3
2
2
2
NA
1
1
1
1
1
1
1
2
2
NA
3
5
NA
NA
NA
NA
NA
XRFC
NA
NA
NA
5
3
3
2
5
3
2
NA
2
1
1
0.8
0.7
0.4
0.4
0.5
0.5
0.9
0.8
0.6
0.5
0.5
0.5
0.6
0.8
1
5
6
6
6
8
ICb
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
ACb
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
TORb
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
4-77
-------
TABLE 4-2 (cont'd). INSTRUMENTAL DETECTION LIMITS FOR
PARTICLES ON FILTERS
Minimum Detection Limit in ng/m3a
Species
Sb
I
Cs
Ba
La
Au
Hg
Tl
Pb
Ce
Sm
Eu
Hf
Ta
W
Th
U
Cl-
NO3-
SO^
NH4+
OC
EC
ICP/
AESb-d
31
NA
NA
0.05
10
2.1
26
42
10
52
52
0.08
16
26
31
63
21
NA
NA
NA
NA
NA
NA
AA
FlameM
31
NA
NA
3d
2,000
21
500
21
10
NA
2,000
21
2,000
2,000
1,000
NA
25,000
NA
NA
NA
NA
NA
NA
AA
Furnaceb
0.2
NA
NA
0.04
NA
0.1
21
0.1
0.05
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
INAAb-f
0.06
1
0.03
6
0.05
NA
NA
NA
NA
0.06
0.01
0.006
0.01
0.02
0.2
0.01
NA
NA
NA
NA
NA
NA
NA
PIXEg
NA
NA
NA
NA
NA
NA
NA
NA
3
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
XRFC
9
NA
NA
25
30
2
1
1
1
NA
NA
NA
NA
NA
NA
NA
1
NA
NA
NA
NA
NA
NA
ICb
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
50
50
50
NA
NA
NA
ACb
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
50
NA
NA
TORb
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
100
100
"Minimum detection limit is three times the standard deviation of the blank for a filter of 1 mg/cm2 areal
density.
ICP/AES = Inductively Coupled Plasma with Atomic Emission Spectroscopy.
AA = Atomic Absorption Spectrophotometry.
PIXE = Proton Induced X-ray Emissions Spectrometry.
XRF = Non-Dispersive X-ray Fluorescence Spectrometry.
INAA = Instrumental Neutron Activation Analysis.
1C = Ion Chromatography.
AC = Automated Colorimetry.
TOR = Thermal Optical Reflectance.
bConcentration is based on the extraction of 1/2 of a 47 mm quartz-fiber filter in 15 ml of deionized-distilled
water, with a nominal flow rate of 20 L/min for 24-h samples.
Concentration is based on 13.8 cm2 deposit area for a 47 mm ringed teflon-membrane filter, with a nominal
flow rate of 20 L/min for 24-h samples with 100 sec radiation time.
dHarman (1989).
eFernandez de la Mora (1989).
fOlmez (1989).
8Eldred et al. (1993).
hNot Available.
4-78
-------
4.3.1 Mass Measurement Methods
Paniculate mass concentration is the most commonly made measurement on aerosol
samples. It is used to determine compliance with PM10 standards and to select certain
samples for more detailed, and more expensive, chemical analyses. As noted in Section 2,
the beta attenuation and inertial microbalance methods have been incorporated into in situ
measurement systems which acquire real-time mass measurements. Gravimetric analysis is
used almost exclusively to obtain mass measurements of filters in a laboratory environment.
The U.S. Environmental Protection Agency (1976) has published detailed procedures for
mass analyses associated with 20.32 cm X 25.40 cm fiber filters, but the guidance for other
types of filters used for chemical analyses is less well documented.
Gravimetry measures the net mass on a filter by weighing the filter before and after
sampling with a balance in a temperature- and relative humidity-controlled environment.
PM10 reference methods require that filters be equilibrated for 24 h at a constant (within
±5%) relative humidity between 20 and 40% and at a constant (within +3 °C) temperature
between 15 and 30 °C. These are intended to minimize the liquid water associated with
soluble compounds and to minimize the loss of volatile species. Nominal values of 30% RH
and 15 to 20 °C best conserve the particle deposits during sample weighing.
Balances used to weigh 20.32 cm x 25.40 cm filters from high volume PM10 samples
must have a sensitivity of at least 100 /*g. Balances used for medium volume PM10 samples
should have a sensitivity of at least 10 /ig, and those used for low-volume PM10 samples
should have a sensitivity of at least 1 /*g. Modifications to the balance chamber are
sometimes needed to accommodate filters of different sizes. All filters, even those from
high-volume PM10 samplers, should be handled with gloved hands when subsequent chemical
analyses are a possibility.
Balance calibrations should be established before and after each weighing session using
Class M and Class S standards, and they should be verified with a standard mass every
10 filters. Approximately one out of ten filters should be re-weighed by a different person at
a later time. These re-weights should be used to calculate the precision of the measurement
as outlined by Watson et al. (1989a).
Feeney et al. (1984) examined the gravimetric measurement of lightly loaded membrane
filters and obtained excellent precision and accuracy. The sensitivity of the electrobalance is
4-79
-------
about ±0.001 mg, though tolerances on re-weights of Teflon-membrane filters are typically
±0.010 mg. The main interference in gravimetric analysis of filters results from
electrostatic effects. Engelbrecht et al. (1980) found that residual charge on a filter could
produce an electrostatic interaction between the filter on the pan and the metal casing of the
electrobalance. This charge can be removed by exposing the filter to a radioactive polonium
source before and during sample weighing.
Beta attenuation methods have been applied in the laboratory as well as in the field, and
the results are comparable to those of gravimetric measurements. The precision of
beta-gauge measurements has been shown to be ±5 /zg/m3 or better for counting intervals of
one minute per sample, which translates into ±32 /ig/filter for 37 mm diameter substrates.
This is substantially higher than the ±6 /xg/filter precision determined by gravimetric
analysis using an electrobalance (Feeney et al., 1984). Jaklevic et al. (1981) found
equivalent accuracy and precision for both techniques as they were used in that study.
Courtney et al. (1982) found beta attenuation and gravimetric mass measurements to differ
by less than ±5%. Patashnick and Rupprecht (1991) examine results from TEOM samplers
operated alongside filter-based PM10 samplers, and Shimp (1988) reports comparisons with
beta attenuation field monitors; these comparisons all show good agreement for mass
measurements.
4.3.2 Physical Analysis
The most common interest in elemental composition derives from concerns about health
effects and the utility of these elements to trace the sources of suspended particles.
Instrumental neutron activation analysis (INAA), photon-induced x-ray fluorescence (XRF),
particle-induced x-ray emission (PIXE), atomic absorption spectrophotometry (AAS),
inductively-coupled plasma with atomic emission spectroscopy (ICP/AES), and scanning
electron microscopy with x-ray fluorescence (SEM/XRF) have all been applied to elemental
measurements of aerosol samples. A AS and ICP/AES are also appropriate for ion
measurements when the particles are extracted in deionized-distilled water (DDW). Since air
filters contain very small particle deposits (20 to 100 pig/cm2), preference is given to methods
that can accommodate small sample sizes. XRF and PIXE leave the sample intact after
analysis so that it can be submitted to additional examinations by other methods. Excellent
4-80
-------
agreement was found for the intercomparison of elements acquired form the XRF and PIXE
analyses (Cahill, 1980). The analytical measurement specifications of air filter samples for
the different elemental analysis is shown in Table 4-2.
4.3.2.1 X-Ray Fluorescence of Trace Elements
In x-ray fluorescence (XRF) (Dzubay and Stevens, 1975; Hammerle and Pierson, 1975;
Jaklevic et al., 1977; Torok and Van Grieken, 1994), the filter deposit is irradiated by high
energy x-rays that eject inner shell electrons from the atoms of each element in the sample.
When a higher energy electron drops into the vacant lower energy orbital, a fluorescent x-ray
photon is released. The energy of this photon is unique to each element, and the number of
photons is proportional to the concentration of the element. Concentrations are quantified by
comparing photon counts for a sample with those obtained from thin-film standards of known
concentration.
XRF methods can be broadly divided into two categories: wavelength dispersive x-ray
fluorescence (WDXRF), which utilizes crystal diffraction for observation of fluorescent
x-rays, and energy dispersive x-ray fluorescence (EDXRF), which uses a silicon
semiconductor detector. The WDXRF method is characterized by high spectral resolution,
which minimizes peak overlaps. It requires high power excitation to overcome low
sensitivity, resulting in excessive sample heating and potential degradation. Conversely,
EDXRF features high sensitivity but less spectral resolution, requiring complex spectral
deconvolution procedures.
XRF methods can be further categorized as direct/filtered excitation, where the x-ray
beam from the tube is optionally filtered and then focused directly on the sample, or
secondary target excitation, where the beam is focused on a target of material selected to
produce x-rays of the desired energy. The secondary fluorescent radiation is then used to
excite the samples. The direct/filtered approach has the advantage of delivering higher
incident radiation flux to the sample for a given x-ray tube power, since about 99% of the
incident energy is lost in a secondary fluorescence. However, the secondary fluorescence
approach, produces a more nearly monochromatic excitation that reduces unwanted scatter
from the filter, thereby yielding better detection limits.
4-81
-------
XRF is usually performed on Teflon-membrane filters for a variety of trace elements.
A typical XRF system is schematically illustrated in Figure 4-24. The x-ray output stability
should be within ±0.25% for any 8-h period within a 24-h duration. Typically, analyses are
controlled, spectra are acquired, and elemental concentrations are calculated by software on a
computer that is interfaced to the analyzer. Separate XRF analyses are conducted on each
sample to optimize detection limits for the specified elements. A comparison of the
minimum detectable limits of Teflon-membrane and quartz-fiber filters is listed in Table 4-3.
Figure 4-25 shows an example of an XRF spectrum.
Three types of XRF standards are used for calibration, performance testing, and
auditing: (1) vacuum-deposited thin-film elements and compounds (Micromatter);
(2) polymer films (Dzubay et al., 1981); and (3) National Institute of Science and
Technology (NIST, formerly NBS) thin-glass films. The thin film standards cover the
largest number of elements and are used to establish calibration curves, while the polymer
film standards are used to verify the accuracy of the thin film standards. The NIST
standards are used to validate the accuracy of the calibration curves. NIST produces the
definitive standard reference materials, but these are only available for the species of
aluminum, silicon, calcium, iron, cobalt, copper, manganese, and uranium (SRM 1832), and
silicon, potassium, titanium, iron, zinc, and lead (SRM 1833). One or more separate
Micromatter thin-film standards are used to calibrate the system for each element.
Sensitivity factors (number of x-ray counts per pig/cm2 of the element) are determined
for each excitation condition. These factors are then adjusted for absorption of the incident
and emitted radiation in the thin film. These sensitivity factors are plotted as a function of
atomic number and a smooth curve is fitted to the experimental values. The calibration
sensitivities are then read from these curves for the atomic numbers of each element in each
excitation condition. NIST standards are analyzed on a periodic basis to verify the sensitivity
factors. A multi-layer thin film standard prepared by Micromatter is analyzed with each set
of samples to check the stability of the instrument response. When deviations from specified
values are greater than ±5%, the system should be re-calibrated.
The sensitivity factors are multiplied by the net peak intensities yielded by ambient
samples to obtain the /ig/cm2 deposit for each element. The net peak intensity is obtained
4-82
-------
Sample,
^Characteristic
x-rays
X-ray excitation
ilicon detector
FET
preamp
" Pulse
processor
Secondary
target
Be/
window
Analog-to-
digital
converter
Electron beam
X-ray tube
Multi-
channel
, analyzer
Data output
Mini-
computer
Video
display
Signal
processing
Data
handling
Figure 4-24. Schematic of a typical X-ray fluorescence system.
4-83
-------
TABLE 4-3. MINIMUM DETECTABLE LIMITS3 FOR X-RAY FLUORESCENCE
ANALYSIS OF AIR FILTERS
Element
Al
Si
P
S
Cl
K
Ca
Ti
V
Cr
Mn
Fe
Co
Ni
Cu
Zn
Ga
As
Se
Br
Rb
Sr
Y
Zr
Mo
Pd
Ag
Cd
In
Condition
Numberd
5
5
5
5
4
4
4
3
3
3
3
3
3
3
3
3
2
2
2
2
2
2
2
2
4
1
1
1
1
Quartz-Fiber
Filterb
Protocol QA-
A ng/cm2 e
NAf
NA
NA
406
30
40
100
50
20
8
7
15
5
4
4
6
8
9
5
5
5
8
8
10
20
20
20
25
30
Teflon Membrane Filter^
Protocol A
ng/cm2 d
10
6.3
5.6
5.0
10
6.1
4.5
2.9
2.5
1.9
1.6
1.5
0.88
0.89
1.1
1.1
1.9
1.6
1.2
1.0
1.0
1.1
1.3
1.7
2.7
11
12
12
13
Protocol B
ng/cm2
7.2
4.4
4.0
3.5
7.4
4.3
3.2
2.1
1.7
1.4
1.1
1.1
0.62
0.63
0.76
0.76
1.4
1.1
0.86
0.72
0.68
0.78
0.92
1.2
1.9
7.6
8.6
8.6
9.5
Protocol C
ng/cm2
3.6
2.2
2.0
1.8
3.7
2.2
1.6
1.0
0.87
0.67
0.56
0.54
0.31
0.31
0.38
0.38
0.68
0.56
0.43
0.36
0.34
0.39
0.46
0.59
0.95
3.8
4.3
4.3
4.8
Protocol D
ng/cm2
2.5
1.4
1.4
1.2
2.6
1.5
1.1
0.73
0.62
0.48
0.40
0.38
0.22
0.22
0.27
0.27
0.48
0.39
0.31
0.25
0.24
0.28
0.33
0.42
0.67
2.7
3.0
3.0
3.4
4-84
-------
TABLE 4-3 (cont'd). MINIMUM DETECTABLE LIMITS3 FOR X-RAY
FLUORESCENCE ANALYSIS OF AIR FILTERS
Quartz-Fiber
Filterb Teflon Membrane Filter0
Condition Protocol QA- Protocol A Protocol B Protocol C Protocol D
Element Numberd A ng/cm2 e ng/cm2 d ng/cm2 ng/cm2 ng/cm2
Sn 1 40 17 12 6~24^4
Sb
Ba
La
Au
Hg
Tl
Pb
U
1
1
1
2
2
2
2
2
50
170
190
NA
20
NA
14
NA
18
52
62
3.1
2.6
2.5
3.0
2.3
13
37
44
2.2
1.8
1.8
2.2
1.7
6.4
18
22
1.1
0.91
0.88
1.1
0.83
4.5
13
16
0.77
0.65
0.62
0.76
0.59
aMDL defined as three times the standard deviation of the blank for a filter of 1 mg/cm2 areal density.
bAnalysis times are 100 sec. for Conditions 1 and 4, and 400 sec. for Conditions 2 and 3. Actual MDL's for
quartz filters vary from batch to batch due to elemental contamination variability.
cStandard protocol, developed at the Desert Research Institute, University and Community College System of
Nevada, Reno, NV, analysis times are 100 sec. for Conditions 1, 4 and 5, and 400 sec. for Conditions 2 and 3
for Protocol A; 200 sec. for Conditions 1, 4 and 5 and 800 sec. for Conditions 2 and 3 for Protocol B; 800
sec. for Conditions 1,4 and 5 and 3,200 sec. for Conditions 2 and 3 for Protocol C; and 1600 sec. for
Conditions 1, 4 and 5 and 6400 sec. for Conditions 2 and 3 for Protocol D.
dCondition 1 is direct mode excitation with a primary excitation filter of 0.15 mm thick Mo. Tube voltage is
50 KV and tube current is 0.6 mA. Condition 2 is direct mode excitation with a primary excitation filter of
0.13 mm thick Rh. Tube voltage is 35 KV and tube voltage is 2.0 mA. Condition 3 uses Ge secondary target
excitation with the secondary excitation filtered by a Whatman 41 filter. Tube voltage is 30 KV and tube
current is 3.3 mA. Condition 4 uses Ti secondary target excitation with the secondary excitation filtered by
3.8 /xm thick mylar film. Tube voltage is 30 KV and tube current is 3.3 mA. Condition 5 uses direct mode
excitation with a primary excitation filter consisting of 3 layers of Whatman 41 filters. Tube voltage is 8 KV
and tube current os 0.6 mA. Multi-channel analyzer energy range is 0 to 40 KeV for condition 1, 0 - 20 KeV
for condition 2, and 0 to 10 KeV for conditions 3,4, and 5.
Typical exposed area is 406 cm2 for standard high-volume filters; 6.4 cm2 for 37 mm ringed Teflon-membrane
filters; and 13.8 cm2 for 47 mm ringed Teflon-membrane filters.
Information not available.
gFor condition 4.
4-85
-------
26-Oct-1992 18:09:56
SJTT046
Vert" 2000 counts Disp= 1
Preset-
Comp= 2 Elapsed=
100 sees
400 sees
San Jose, 1/21/92, PM 10
18:01 - 06:00
Excitation Condition 3
0.320 Range- 10.230 keV
Integral 0
10.230 >•
243425
1111(111- 1 I
5 10
Figure 4-25. Example of an X-ray fluorescence spectrum.
Source: Chow and Watson (1994).
by: (1) subtracting background radiation; (2) subtracting spectral interferences; and
(3) adjusting for x-ray absorption.
XRF analysis of air paniculate samples has had widest application to samples collected
on membrane-type filters such as Teflon- or polycarbonate-membrane filter substrates. These
membrane filters collect the deposit on then* surfaces, which eliminates biases due to
absorption of x-rays by the filter material. These filters also have a low areal density which
minimizes the scatter of incident x-rays, and their inherent trace element content is very low.
Quartz-fiber filters used for high-volume aerosol sampling do not exhibit these features.
As noted earlier, blank elemental concentrations in quartz-fiber filters that have not
undergone acceptance testing can be several orders of magnitude higher than the
4-86
-------
concentrations in the particulate deposits. The concentrations vary substantially among the
different types of quartz-fiber filters and even within the same filter type and manufacturing
lot. Blank impurity concentrations and their variabilities decrease the precision of
background subtraction from the XRF spectral data, resulting in higher detection limits.
Impurities observed in various types of glass- and quartz-fiber filters include aluminum,
silicon, sulfur, chlorine, potassium, calcium, iron, nickel, copper, zinc, rubidium, strontium,
molybdenum, barium, and lead. Concentrations for aluminum, silicon, phosphorus, sulfur,
and chlorine cannot be determined for quartz-fiber filters because of the large silicon content
of the filters.
Quartz-fiber filters also trap particles within the filter matrix, rather than on the
surface. This causes absorption of X rays within the filter fibers yielding lower
concentrations than would otherwise be measured. The magnitude of this absorption
increases exponentially as the atomic number of the measured element decreases and varies
from sample to sample. Absorption factors generally are "1.2" or less for iron and heavier
elements, but can be from "2" to "5" for sulfur.
Quartz-fiber filters are much thicker than membrane filters resulting in an increased
scattering of x-rays and a consequent increase in background and degradation of detection
limits. The increased x-ray scatter also overloads the x-ray detector which requires samples
to be analyzed at a lowered x-ray intensity. These effects alone can result in degradation of
detection limits by up to a factor of 10 with respect to Teflon-membrane substrates.
Larger particles collected during aerosol sampling have sufficient size to cause
absorption of x-rays within the particles. Attenuation factors for fine particles (PM2 5,
particles with aerodynamic diameters equal to or less than 2.5 ^m) are generally negligible
(Criss, 1976), even for the lightest elements, but these attenuations can be significant for
coarse fraction particles (particles with aerodynamic diameters from 2.5 to 10 pirn).
Correction factors for XRF have been derived using the theory of Dzubay and Nelson (1975)
and should be applied to coarse particle measurements.
4.3.2.2 Particle Induced X-Ray Emission of Trace Elements
Particle Induced X-Ray Emission (PIXE) is another form of elemental analysis based on
the characteristics of x-rays and the nature of x-ray detection (Cahill et al., 1987; 1989).
4-87
-------
PIXE uses beams of energetic ions, consisting of protons at an energy level of 2 to 5 MeV,
to create inner electron shell vacancies. As inner electron shell atomic vacancies are filled
by outer electrons, the emitted characteristics of x-rays can be detected by wavelength
dispersion (which is scattering from a crystal) or by energy dispersion (which involves direct
conversion of x-rays). The development of focusing energetic proton beams (proton
microprobes) has expanded the application of PIXE from environmental and biological
sciences to geology and material sciences. Figure 4-26 illustrates a typical PIXE setup in a
thin target mode (Cahill, et al., 1989). PIXE analysis is often used for impactor samples or
small filter substrates, since proton beams can be focused to a small area with no loss of
sensitivity (Cahill and Wakabayashi, 1993).
Very thick filters or thick particle deposits on filter substrates scatter the excitation
protons and lower the signal-to-noise ratio for PIXE. X-ray analysis methods, such as PIXE
and XRF, require particle size diameter corrections (for low atomic number targets)
associated with a spherical particle of a given diameter (typically particles with aerodynamic
diameters >2.5 /mi) and compositions typical in ambient aerosol studies. These analyses
also require correction for sample loadings that reflect the passage of x-rays through a
uniform deposit layer. Procedures for instrument calibration, spectrum process, and quality
assurance are similar to those documented in Section 4.3.1.2 for XRF.
PIXE analysis can provide information on one of the widest range of elements in a
single analysis, since x-ray results require two or three separate anodes. However, attempts
to improve sensitivity of PIXE analysis may result in damage to Teflon-membrane filters.
Recent developments (Malm et al., 1994) using PIXE analysis at moderate sensitivity plus
single anode XRF analysis at high sensitivity for transition/heavy metals have achieved the
minimum detectable limits of less than 0.01 ng/m3. With the addition of hydrogen analysis
(a surrogate for organic matter), almost all gravimetric mass concentrations can be explained
(Cahill, etal., 1987).
XRF and PIXE are the most commonly used elemental analysis methods owing to their
nondestructive multi-element capabilities, relatively low cost, high detection limits, and
preservation of the filter for additional analyses. XRF sometimes needs to be supplemented
with INAA when extremely low detection limits are needed, but the high cost of INAA
precludes this method from being applied to large numbers of samples. A AS is a good
-------
00
Proton
Deposit" Beam
Beam
lollimator
, Faraday Cup j
PIXE-2
(Fe-Mo)
PIXE-1
(Na-Mn)
Figure 4-26. Schematic of a PIXE/PESA analysis system.
-------
alternative for water-soluble species, especially for low atomic number. ICP/AES analysis
is a viable alternative, but it is less desirable because of the sample extraction elements such
as sodium and magnesium, but it requires large dilution factors to measure many different
elements expense and the destruction of the filter.
4.3.2.3 Instrumental Neutron Activation Analysis of Trace Elements
Instrumental neutron activation analysis (INAA) (Dams et al., 1970; Zoller and
Gordon, 1970; Olmez, 1989; Ondov and Divita, 1993) basically involves irradiation of a
thin membrane filter sample in the core of a nuclear reactor for periods ranging from a few
minutes to several hours. Bombardment of the sample with neutrons induces a nuclear
reaction of the stable isotopes in the sample. The energies of the gamma rays emitted by the
decay of this induced radioactivity are used to identify them, and therefore, their parents.
With the use of prepared elemental standards, the amount of parent element in the sample
can be determined since the intensity of these gamma rays are proportional to their number.
The gamma-ray spectra of radioactive species are usually collected with a high
resolution germanium detector utilizing commercially available amplifiers and multi-channel
analyzers. Typical detector efficiencies range from 10 to 40% relative to a 3 x 3 in. sodium
iodide detector. Detector system resolution, measured as the full-width at half-maximum for
Table 4-4, the 1,332 KeV gamma-ray peak of 60Co, should be less than 2.3 KeV in order to
provide adequate resolution between isotopes of neighboring energies.
In order to obtain a full suite of elemental analysis results (often over 40 elements),
multiple counting periods and irradiations are performed on the same sample (e.g., two
irradiations would produce elements separated into short- and long-lived decay products).
An example of the elements determined from multiple irradiations and counting periods and
the irradiation, cooling, and counting times used for ambient paniculate samples collected on
Teflon-membrane filter material are summarized in Table 4-4 (Divita, 1993). These
irradiations were performed at the 20-MW NIST Research Reactor operated at 15-MW
(neutron flux of 7.7 x 1013 and 2.7 X 1013 neutron/cm2 x s).
The power of INAA is that it is not generally subject to interferences like XRF or
PIXE due to a much better ratio of gamma ray peak widths to total spectral width, by a
factor of about 20. INAA does not quantify some of the abundant species in ambient
4-90
-------
TABLE 4-4. INSTRUMENTAL NEUTRON ACTIVATION ANALYSIS COUNTING
SCHEME AND ELEMENTS MEASURED
Counting
Period
Irradiation
Time
Cooling
Time
Counting
Time
Elements Measured
Short-Lived 1 10 min
Short-Lived 2
Long-Lived 1 4-6 h
Long-Lived 2
5 min
20 min
30 days
5 min
20 min
3-4 days 6-8 h
12-24 h
Mg, Al, S, Ca, Ti, V, Cu
Na, Mg, Cl, K, Ca, Mn,
Zn, Ga, Br, Sr, In, I, Ba
Na, K, Ga, As, Br, Mo,
Cd, Sb, La, Nd, Sn, Yb,
Lu, W, Au, U
Sc, Cr, Fe, Co, Zn, Se,
Sr, Ag, Sb, Cs, Ba, Ce,
Nd, Eu, Gd, Tb, Lu, Hf,
Ta, Th
paniculate matter such as silicon, nickel, tin, cadmin, mercury, and lead. While IN A A is
technically nondestructive, sample preparation involves folding the samples tightly and
sealing it in plastic, and the irradiation process makes the filter membrane brittle and
radioactive. These factors limit the use of the sample for subsequent analyses by other
methods. The technique also suffers from the fact that a nuclear reactor is usually used as a
source of neutrons. However, since the advent of high-resolution gamma-ray detectors,
individual samples can be analyzed for numerous elements simultaneously, most at
remarkably trace levels without the need for chemical separation. This greatly diminishes the
danger of contamination due to excessive sample handling and introduction of chemical
reagents used for separation procedures.
4.3.2.4 Microscopy Analysis of Particle Size, Shape, and Composition
Morphological and chemical features of particles can be used to identify the sources and
transport mechanism of airborne particles. The chemical analysis of individual particles
allows the attribution of specific pollution sources more straightforward while the abundance
of a specific group is a representative of the source strength. Both light (optical) and
scanning electron microscopy have been applied in environmental studies to examine the
4-91
-------
single particles (e.g., Casuccio et al., 1983; Bruynseels et al., 1988; Van Borm and Adams,
1988; Van Borm et al., 1989; Cornille et al., 1990; Hopke and Casuccio, 1991; Turpin
etal., 1993a).
Light microscopy has been used for providing particle size information regarding the
morphology of microscopic features (Crutcher, 1982). The practical resolution of optical
microscopes is limited by the wavelengths associated with light of the visible spectrum.
When features of interest occur in micron and submicron size ranges, detailed resolution
cannot be obtained. The practical resolution of light microscopy is typically 1 to 2 pm
(Meyer-Arendt, 1972).
The use of accelerated electrons in electron microscopy (a) allows for the formation of
magnified images and an increased depth of field and (b) provides the resolution of a few
angstroms (10"4 /«n). Electron microscopy has now evolved to include: (1) the transmission
electron microscope (TEM); (2) the scanning electron microscope (SEM), and; (3) the
scanning transmission electron microscope (STEM) (Hearle et al. 1972; Lee et al., 1979; Lee
and Fisher, 1980; Lee and Kelly, 1980; Lee et al., 1981; Johnson et al., 1981; Mclntyre and
Johnson, 1982; Casuccio et al., 1983; Wernisch, 1985, 1986; Kim et al., 1987; Kim and
Hopke, 1988; Dzubay and Mamane, 1989; Schamber, 1993).
The SEM and STEM use accelerated electrons to strike the sample. As the electron
beam strikes the samples, various signals (e.g., secondary, backscattered, and Anger
electrons, characteristic x-rays, photons, and cathodoluminescence) are generated. These
signals can be collected to provide highly detailed information on a point-by-point basis. The
secondary electron signal yields a sample image with three-dimensional prospective, high
depth of field, and illuminated appearance. Back scattered electron images are used to
separate phases containing elements of different atomic number.
The information obtained from light and scanning microscopy analyses are usually
considered to be qualitative, due to the limited number of particles counted. To achieve a
quantitative analysis, a sufficient number of particles must be properly sized and identified by
morphology and/or chemistry to represent the entire sample. The selection of filter media,
optimal particle loadings, and sample handling methods are also of importance. In this
manner, the microscopic characteristics can be directly and reliably related to the bulk or
macroscopic properties of the sample (Casuccio et al., 1983).
4-92
-------
Microscopic analysis requires a high degree of skill and extensive quality assurance to
provide quantitative information. The techniques is complex and expensive when quantitative
analysis is required. The evolution of computer technology has allowed for quantitative
analysis of particle samples of an entire population of features. With advanced pattern
recognition methods, data from individual particle features can be sorted and summarized by
size and composition, permitting improved quantitative source apportionment (Bruynseels
et al., 1988; Hopke and Casuccio, 1991). Casuccio et al. (1983) summarized the pros and
cons of automatic scanning electron microscopy.
Recent development of the SEM/XRF allows analysis of elemental compositions and
morphological information on small quantities of material (Bruynseels et al., 1988). Coupled
with statistical data analysis, computer controlled scanning electron microscopy shows great
promise for identifying and quantifying complex pollution sources in the field of receptor
modeling source apportionment (e.g., Griffin and Goldberg, 1979; Janocko et al., 1982;
Johnson et al., 1982; Massart and Kaufman, 1983; Hopke, 1985; Derde et al., 1987, Saucy
et al., 1987; Mamane, 1988; Dzubay and Mamane, 1989).
4.3.3 Wet Chemical Analysis
Aerosol ions refer to chemical compounds that are soluble in water. The water-soluble
portion of suspended particles associates itself with liquid water in the atmosphere when
relative humidity increases, thereby changing the light scattering properties of these particles.
Different emissions sources may also be distinguished by their soluble and non-soluble
fractions. Gaseous precursors can also be converted to their ionic counterparts when they
interact with chemicals impregnated on the filter material.
Several simple ions, such as soluble sodium, magnesium, potassium, and calcium are
best quantified by atomic absorption spectrometry (AAS) as described above. In practice,
AAS has been very useful for measuring water-soluble potassium and sodium, which are
important in apportioning sources of vegetative burning and sea salt, respectively.
Polyatomic ions such as sulfate, nitrate, ammonium, and phosphate must be quantified by
other methods such as ion chromatography (1C) and automated colorimetry (AC). Simple
ions, such as chloride, chromium III, and chromium IV, may also be measured by these
methods along with the polyatomic ions.
4-93
-------
All ion analysis methods require filters to be extracted in DDW and then filtered to
remove the insoluble residue. The extraction volume needs to be as small as possible, lest
the solution become too dilute to detect the desired constituents. Each square centimeter of
filter should be extracted in no more than 2 ml of solvent for typical sampler flow rates of
20 to 30 L/min and sample durations of 24 h. This often results in no more than 20 ml of
extract that can be submitted to the different analytical methods, thereby giving preference to
those methods which require only a small sample volume. Sufficient sample deposit must be
acquired to account for the dilution volume required by each method.
When other analyses are to be performed on the same filter, the filter must first be
sectioned using a precision positioning jig attached to a paper cutter. For rectangular filters
(typically 20.32 cm by 25.40 cm), a 2.0 cm by 20.32 cm wide strip is cut from the center
two-thirds of the filter. Circular filters of 25-, 37-, and 47-mm diameters are usually cut in
half for these analyses, so the results need to be multiplied by two to obtain the deposit on
the entire filter. Filter materials that can be easily sectioned without damage to the filter or
the deposit must be chosen for these analyses.
4.3.3.1 Ion Chromatographic Analysis for Chloride, Nitrate, and Sulfate
Ion chromatography (1C) can be used for both anions (fluoride [F~], chloride [Cl~],
nitrite [NO£], bromide [Br~], nitrate [NO§], phosphate [PO^3], sulfate [SO4=]) and cations
(soluble potassium [K+], ammonium [NH4+], soluble sodium [Na+]) with separate columns.
Applied to aerosol samples, the anions are most commonly analyzed by 1C with the cations
being analyzed by a combination of atomic absorption spectrophotometry (AAS) and
automated colorimetry (AC) (U.S. EPA, 1994). In 1C (Small et al., 1975; Mulik et al.,
1976; Butler et al., 1978) the sample extract passes through an ion-exchange column that
separates the ions in time for individual quantification, usually by a electroconductivity
detector. Figure 4-27 shows a schematic representation of the 1C system. Prior to detection,
the column effluent enters a suppressor column where the chemical composition of the eluent
is altered, resulting in a lower background conductivity. The ions are identified by their
elution/retention times and are quantified by the conductivity peak area or peak height. 1C is
especially desirable for particle samples because it provides results for several ions with a
single analysis and it uses a small portion of the filter extract with low detection limits.
4-94
-------
Delivery Module—
Chromatography Module —
Detector Module —
Eluent
Reservoir
Pump
Sample
Injector
Guard
Column
Separator
Column
Suppressor
Device
Conductivity
Cell
Figure 4-27. Schematic representation of an ion chromatography system.
4-95
-------
Water-soluble chloride (Cl"), nitrate (NOj), and sulfate (SO4~) are the most commonly
measured anions in aerosol samples. Figure 4-28 shows an example of an 1C anion
chromatogram. 1C analyses can be automated by interfacing to an automatic sampler that
can conduct unattended analysis of as many as 400 samples (Tejada et al., 1978).
18,000-
15,500-
13,000-
10,500-
8,000-
5,500-
3,000-
500-
-2,000-
0.
Fluoride
I
^
I Chloride
Nitrite
Nitrate
\ l\ Phosphate Sffe
\ 1 \ rx / \
30
5.00 10.00
Minutes
Figure 4-28. Example of an ion chromatogram showing the separation of fluoride,
chloride, nitrite, nitrate, phosphate, and sulfate ions.
Several independent quality assurance (QA) standards should be used to check the
calibration curve. The standards that are traceable to NIST simulated rainwater standards
are: Environmental Resource Associates (ERA, Arvada, CA) custom standards containing
the anions measured at a concentration of 100 ug/ml, ERA Waste Water Nutrient Standard,
ERA Waste Water Mineral Standard, and Alltech individual standards at 200 ug/ml. The
QA standards are diluted in DDW to concentrations that are within the range of the
calibration curve.
Calibration curves are performed weekly. Chemical compounds are identified by
matching the retention time of each peak in the unknown sample with the retention times of
4-96
-------
peaks in the chromatograms of the standards. The QA standards are analyzed at the
beginning of each sample run to check calibrations. A DDW blank is analyzed after every
20 samples and a calibrations standard is analyzed after every 10 samples. These quality
control (QC) checks verify the baseline and calibration respectively.
4.3.3.2 Automated Colorimetric Analysis for Ammonium, Nitrate, and Sulfate
Automated Colorimetry (AC) applies different colorimetric analyses to small sample
volumes with automatic sample throughput. The most common ions measured are
ammonium, chloride, nitrate, and sulfate (Butler et al., 1978; Fung et al., 1979). Since
1C provides multi-species analysis for the anions, ammonium is most commonly measured by
AC.
The AC system is illustrated schematically in Figure 4-29. The heart of the automated
colorimetric system is a peristaltic pump, which introduces air bubbles into the sample
stream at known intervals. These bubbles separate samples in the continuous stream. Each
sample is mixed with reagents and subjected to appropriate reaction periods before
submission to a colorimeter. The ion being measured usually reacts to form a colored liquid.
The liquid absorbance is related to the amount of the ion in the sample by Beer's Law. This
absorbance is measured by a photomultiplier tube through an interference filter specific to the
species being measured.
The standard AC technique can analyze =60 samples per hour per channel, with
minimal operator attention and relatively low maintenance and material costs. Several
channels can be set up to simultaneously analyze several ions. The methylthymol-blue
(MTB) method is applied to analyze sulfate. The reaction of sulfate with MTB-barium
complex results in free ligand, which is measured colorimetrically at 460 nm. Nitrate is
reduced to nitrite that reacts with sulfanilamide to form a diazo compound. This compound
is then reacted to an azo dye for colorimetric determination at 520 nm. Ammonium is
measured with the indophenol method. The sample is mixed sequentially with potassium
sodium tartrate, sodium phenolate, sodium hypochlorite, sodium hydroxide, and sodium
nitroprusside. The reaction results in a blue-colored solution with an absorbance measured at
630 nm. The system determines carry-over by analysis of a low concentration standard
4-97
-------
Sampler
Heater
(optional)
Mixing
Cell
Reagent Line #1
Reagent Line #2
Sample Line
Reagent Line #3
Reagent Line #4
Reagent Line #5
Reagent Line #6
Flow
Cell
Optical
Filter
Photomultiplier
Detector
Peristatic
Pump
Figure 4-29. Schematic of a typical automated colorimetric system.
following a high concentration. The percent carry-over is then automatically calculated and
can be applied to the samples analyzed during the run.
Intercomparison studies between AC and 1C have been conducted by Butler et al.
(1978) and Fung et al. (1979). Butler et al. (1978) found excellent agreement between
sulfate and nitrate measurements by AC and 1C. The accuracy of both methods is within the
experimental errors, with higher blank values observed for AC techniques. Comparable
results were also obtained between the two methods by Fung et al. (1979). The choice
between the two methods for sample analysis is dictated by sensitivity, scheduling, and cost
constraints.
Two milliliters of extract in sample vials are placed in an autosampler that is controlled
by a computer. Five standard concentrations (e.g., (NH4)2SO4, Na2SO4, NaNO3) are
prepared from American Chemical Society reagent-grade chemicals following the same
procedure as that for 1C standards. Each set of samples consists of two DDW blanks to
establish a baseline, five calibration standards and a blank, then sets of ten samples followed
by analysis of one of the standards and a replicate from a previous batch. The computer
4-98
-------
control allows additional analysis of any filter extract to be repeated without the necessity of
loading the extract into more than one vial.
4.3.3.3 Atomic Absorption Spectrophotometric (AAS) and Inductive Coupled Plasma
Atomic Emission Spectro (ICP/AES) Photometry Analyses for Trace
Elements
In atomic absorption Spectrophotometric (AAS) analysis (Fernandez de la Mora, 1989),
the sample is first extracted in a strong solvent to dissolve the solid material; the filter or a
portion thereof is also dissolved during this process. A few milliliters of this extract are
introduced into a flame where the elements are vaporized. Most elements absorb light at
certain wavelengths in the visible spectrum, and a light beam with wavelengths specific to the
elements being measured is directed through the flame to be detected by a monochrometer.
The light absorbed by the flame containing the extract is compared with the absorption from
known standards to quantify the elemental concentrations. AAS requires an individual
analysis for each element, and a large filter or several filters are needed to obtain
concentrations for a large number of the elements specified in Table 4-3. AAS is a useful
complement to other methods, such as XRF and PIXE, for species such as beryllium,
sodium, and magnesium that are not well-quantified by XRF and PIXE. Airborne particles
are chemically complex and do not dissolve easily into complete solution, regardless of the
strength of the solvent. There is always a possibility that insoluble residues are left behind
and soluble species may co-precipitate on them or on container walls.
In inductive coupled plasma atomic emission Spectrophotometric (ICP/AES), (Lynch
et al., 1980; Harman, 1989), the dissolved sample is introduced into an atmosphere of argon
gas seeded with free electrons induced by high voltage from a surrounding Tesla coil. The
high temperatures in the induced plasma raise valence electrons above their normally stable
states. When these electrons return to their stable states, a photon of light is emitted which
is unique to the element which was excited. This light is detected at specified wavelengths to
identify the elements in the sample. ICP/AES acquires a large number of elemental
concentrations using small sample volumes with acceptable detection limits for atmospheric
samples. As with AAS, this method requires complete extraction and destruction of the
sample.
4-99
-------
4.3.4 Organic Analysis
4.3.4.1 Analysis of Organic Compounds
Organic compounds comprise a major portion of airborne particles in the atmosphere,
thus contributing to visibility degradation, and affecting the properties of clouds into which
these particles are scavenged. Specific groups of organic compounds (e.g., polycyclic
aromatic hydrocarbons, PAHs) have also been implicated in human health effects. However,
due to the very complex composition of the organic fraction of atmospheric aerosols, the
detailed composition and atmospheric distributions of organic aerosol constituents are still not
well understood.
Sampling techniques for atmospheric particulate matter have been extensively
investigated, resulting in the development of collection methods suspended in a wide range of
sizes. Particles are most frequently collected on glass or quartz-fiber filters that have been
specially treated to achieve low "carbon blanks". Ambient organic particulate matter has
also been collected on a variety of particle sizing devices, such as low pressure impactors
and Micro Oriface Uniforms Deposit Impactors("MOUDI"). Very recently, diffusion
denuder based samplers have been used as well (Tang et al., 1994). However, the task of
sampling organic compounds in airborne particles is complicated by the fact that many of
these compounds have equilibrium vapor pressures (gaseous concentrations) that are
considerably larger than their normal ambient concentrations. This implies a temperature-
and concentration-dependent distribution of such organics between particulate and vapor
phases. It also suggests that artifacts may occur due to volatilization during the sampling
process (Coutant et al., 1988). Such volatilization would cause the under-estimation of the
particle-phase concentrations of organics. Conversely, the adsorption of gaseous substances
on deposited particles or on the filter material itself, a process driven by the lowered vapor
pressure over the sorbed material, would lead to over-estimation of the particle-phase fraction
(Bidleman et al., 1986; Ligocki and Pankow, 1989; McDow and Huntzicker, 1990). In
addition, several studies have suggested that chemical degradation of some organics may
occur during the sampling procedure (Lindskog et al., 1985; Arey et al., 1988; Parmar and
Grosjean, 1990).
The partitioning of semi-volatile organic compounds (SOC) between vapor and particle
phases has received much attention (Cautreels and Cauwenberghe, 1978; Broddin et al.,
4-100
-------
1980; Hampton et al., 1983; Ligocki and Pankow, 1989; Gotham and Bidleman, 1992; Lane
et al., 1992; Kaupp and Umlauf, 1992; Pankow, 1992; Turpin et al., 1993b, 1996). Most
estimates of partition have relied on high-volume (hi-vol) sampling, using a filter to collect
particles followed by a solid adsorbent trap to collect the gaseous portion of SOC (e.g.,
Kaupp and Umlauf, 1992, Foreman and Bidleman, 1990). Kaupp and Umlauf (1992)
recently reported that this approach, although not absolutely free from sorption and
desorption artifacts, produces reliable results. The maximum differences observed between
hi-vol filter-solid adsorbent sampling and impactor sampling (the latter believed to be less
susceptible to these sampling artifacts) did not exceed a factor of two.
There is good theoretical and experimental evidence that use of a diffusion denuder
technique significantly improves measurements of vapor-particle phase partitioning (Coutant
et al., 1988, 1989, 1992; Lane et al., 1988). However, at the present state of their
technological development, the reliability of denuders for investigation of atmospheric
partitioning of non-polar SOC needs to be improved, as suggested by contradictions in
published field data (e.g., Kaupp and Umlauf, 1992). Gundel et al. (1992) used a
proprietary XAD-4-coated tube for vapor collection, followed by filter collection of organic
aerosol particles and a sorbent bed to quantitatively retain desorbed (volatilized) organic
vapors. Denuders that remove ozone from the air before it reaches the filter reduce the
potential for artifact formation on the captured paniculate material during sampling (Williams
and Grosjean, 1990).
Since the organic fraction of airborne paniculate matter is typically a complex mixture
of hundreds to thousands of compounds distributed over many organic functional groups, its
chemical analysis is an extremely difficult task (Appel et al., 1977; Simoneit, 1984; Flessel
et al., 1991; Hildemann et al., 1991; Li and Kamens, 1993; Rogge et al., 1993a, 1993b,
1993c). Analyses of organics generally begin with solvent extraction of the paniculate
sample. A variety of solvents and extraction techniques have been used in the past. One
common method is sequential extraction with increasingly polar solvents, which typically
separates the organic material into nonpolar, moderately polar, and polar fractions (Daisey
et al., 1982). This step is usually followed by further fractionation using open-column liquid
chromatography and/or high-performance liquid chromatography (HPLC) in order to obtain
several less complicated fractions (e.g., Schuetzle and Lewtas, 1986; Atkinson et al., 1988).
4-101
-------
These fractions can then be analyzed further with high resolution capillary-column gas
chromatography (GC), combined with mass spectrometry (GC/MS), Fourier transform
infrared (GC/FTIR/MS) or other selective detectors.
Much of the recent work on the identification of nonpolar and semi-polar organics in
airborne samples has used bioassay-directed chemical analysis (Scheutzle and Lewtas, 1986),
and has focused on identification of fractions and compounds that are most likely to be of
significance to human health. In particular, PAHs and their nitro-derivatives (nitroarenes)
attracted considerable attention due to their mutagenic and, in some cases, carcinogenic
properties. More than 100 PAHs have been identified in the PM2 5 fraction of ambient
paniculate matter (Lee et al., 1981). While most of the nitroarenes found in ambient
particles are also present in primary combustion-generated emissions, some are formed from
their parent PAH in the atmospheric nitration reactions (e.g., Arey et al., 1986; Zielinska
et al., 1989, Ramdahl et al., 1986).
Little work has been done to date to chemically characterize the polar fraction in detail,
even though polar material accounts for up to half the mass and mutagenicity of soluble
ambient particulate organic matter (Atherholt et al., 1985; Gundel et al., 1994). Until
recently the polar fraction has remained analytically intractable, since very polar and labile
species interact with conventional fractionation column packing materials and cannot be
recovered quantitatively. Recently, very polar particulate organic matter has been
successfully fractionated using cyanopropyl-bonded silica (Gundel et al., 1994), with good
recovery of mass and mutagenicity (Kado et al., 1989). However, ambient particulate polar
organic material cannot be analyzed with conventional GC/MS because of GC column losses
resulting from adsorption, thermal decomposition, and chemical interactions. New analytical
techniques, such as HPLC/MS and MS/MS, need to be applied if the chemical constituents
of polar particulate organic matter are to be identified and quantified.
Most of the recent work on the identification of particulate organic matter has focused
on mutagenic and carcinogenic compounds that are of significance to human health.
Relatively little work has been done to characterize individual compounds or classes of
compounds that are specific to certain sources of organic aerosol. In urban and rural
atmospheres, as well as in the remote troposphere, organic composition corresponding to
chemical source profiles for of plant waxes, resin residues, and long-chain hydrocarbons
4-102
-------
from petroleum residues have been found (e.g., Gagosian et al., 1981; Simoneit, 1984;
Mazurek et al., 1987, 1989, 1991; Simoneit et al., 1991). However, a variety of smaller,
multi-functional compounds characteristic of gas-to-particle conversion have also been
observed (e.g., Finlayson-Pitts and Pitts, 1986). These compounds tend to be present in the
polar fraction of ambient organic aerosol particles, having been formed from atmospheric
chemical reactions of less polar precursors. Little is currently known about the chemical
composition of this polar fraction due to the serious analytical difficulties mentioned above.
4.3.4.2 Analysis of Organic and Elemental Carbon
Three classes of carbon are commonly measured in aerosol samples collected on
quartz-fiber filters: (1) organic, volatile, or non-light absorbing carbon; (2) elemental or
light-absorbing carbon; and 3) carbonate carbon. Carbonate carbon (i.e., K2CO3, Na2CO3,
MgCO3, CaCO3) can be determined on a separate filter section by measurement of the
carbon dioxide (CO2) evolved upon acidification (Chow et al., 1993b; Johnson et al., 1981).
Though progress has been made in the quantification of specific organic chemical compounds
in suspended particles (e.g., Rogge et al., 1993a,b,c), sampling and analysis methods have
not yet evolved for use in practical monitoring situations.
Many methods have been applied to the separation of organic and elemental carbon in
ambient and source paniculate samples (Mueller et al., 1971; Lin et al., 1973;
Gordon, 1974; Grosjean, 1975; Smith et al., 1975; Appel et al., 1976, 1979; Kukreja and
Bove, 1976; Dod et al., 1979; Johnson and Huntzicker, 1979; Macias et al., 1979; Malissa,
1979; Weiss et al., 1979; Cadle et al., 1980a; Johnson et al., 1981b; Daisey et al., 1981;
Novakov, 1982; Cadle and Groblicki, 1982; Gerber, 1982; Huntzicker et al., 1982; Stevens
et al., 1982; Wolff et al., 1982; Japar et al., 1984; Chow et al., 1993b). Comparisons
among the results of the majority of these methods show that they yield comparable
quantities of total carbon in aerosol samples, but the distinctions between organic and
elemental carbon are quite different (Countess, 1990; Hering et al., 1990).
The definitions of organic and elemental carbon are operational and reflect the method
and purpose of measurement. Elemental carbon is sometimes termed "soot", "graphitic
carbon," or "black carbon." For studying visibility reduction, light-absorbing carbon is a
more useful concept than elemental carbon. For source apportionment by receptor models,
4-103
-------
several consistent but distinct fractions of carbon in both source and receptor samples are
desired, regardless of their light-absorbing or chemical properties. Differences in ratios of
the carbon concentrations in these fractions form part of the source profile that distinguishes
the contribution of one source from the contributions of other sources.
Light-absorbing carbon is not entirely constituted by graphitic carbon, since there are
many organic materials that absorb light (e.g., tar, motor oil, asphalt, coffee). Even the
"graphitic" black carbon in the atmosphere has only a poorly developed graphitic structure
with abundant surface chemical groups. "Elemental carbon" is a poor but common
description of what is measured. For example, a substance of three-bond carbon molecules
(e.g., pencil lead) is black and completely absorbs light, but four-bond carbon in a diamond
is completely transparent and absorbs very little light. Both are pure, elemental carbon.
Chow et al. (1993b) document several variations of the thermal (T), thermal/optical
reflectance (TOR), thermal/optical transmission (TOT), and thermal manganese oxidation
(TMO) methods for organic and elemental carbon. The TOR and TMO methods have been
most commonly applied in aerosol studies in the United States.
The TOR method of carbon analysis developed by Huntzicker et al. (1982) has been
adapted by several laboratories for the quantification of organic and elemental carbon on
quartz-fiber filter deposits. While the principle used by these laboratories is identical to that
of Huntzicker et al. (1982), the details differ with respect to calibration standards, analysis
time, temperature ramping, and volatilization/combustion temperatures. In the TOR method
(Chow et al., 1993b), a filter is submitted to volatilization at temperatures ranging from
ambient to 550°C in a pure helium atmosphere, then to combustion at temperatures between
550 to 800°C in a 2% oxygen and 98% helium atmosphere with several temperature ramping
steps. The carbon that evolves at each temperature is converted to methane and quantified
with a flame ionization detector. The reflectance from the deposit side of the filter punch is
monitored throughout the analysis. This reflectance usually decreases during volatilization in
the helium atmosphere owing to the pyrolysis of organic material. When oxygen is added,
the reflectance increases as the light-absorbing carbon is combusted and removed. Organic
carbon is defined as that which evolves prior to re-attainment of the original reflectance, and
elemental carbon is defined as that which evolves after the original reflectance has been
re-attained. By this definition, "organic carbon" is actually organic carbon that does not
4-104
-------
absorb light at the wavelength (632.8 nm) used, and "elemental carbon" is light-absorbing
carbon (Chow et al., 1993b). The TOT method applies the same thermal/optical carbon
analysis method except that transmission through instead of reflectance off of the filter punch
is measured. Thermal methods apply no optical correction and define elemental carbon as
that which evolves after the oxidizing atmosphere is introduced.
The TMO method (Fung, 1990) uses manganese dioxide (MnO2), present and in contact
with the sample throughout the analysis, as the oxidizing agent, and temperature is relied
upon to distinguish between organic and elemental carbon. Carbon evolving at 525 °C is
classified as organic carbon, and carbon evolving at 850°C is classified as elemental carbon.
Carbon analysis methods require a uniform filter deposit because only a small portion
of each filter is submitted to chemical analysis. The blank filter should be white for light
reflection methods, and at least partially transparent for light transmission methods. The
filter must also withstand very high temperatures without melting during combustion.
Since all organic matter contains hydrogen as the most common elemental species,
analysis of hydrogen by proton elastic scattering analysis (PESA) has been developed by
Cahill et al. (1989). A correction must be made for hydrogen in sulfates and nitrates, but
since the analysis is done in a vacuum, water is largely absent. PESA has excellent
sensitivity which is approximately 20 times better than combustion techniques. This method
requires knowledge of the chemical state of sulfates, nevertheless, reasonable agreement was
found as compared to the combustion techniques.
4.3.4.3 Organic Aerosol Sampling Artifacts
Sampling artifacts contribute to inaccuracies in mass measurements of particulate
organic matter collected by filtration. They can generally be classified into two types:
(1) adsorption on filters or collected particulate matter of organic gases normally in the vapor
phase causes particulate organic mass to be overestimated, and (2) volatilization of collected
organic material during sampling leads to an underestimate of particulate organic mass.
These artifacts can cause significant errors in particle mass measurements in areas where a
large fraction of the particulate mass is organic.
4-105
-------
Vaporization Artifact
Significant loss of organic mass from filter samples occurs when clean air or nitrogen is
pumped through them after collection (Commins, 1962; Rondia, 1965; Van Vaeck et al.,
1984). This has frequently been referred to as "blow-off" or "volatilization artifact"
(Broddin et al., 1980; Konig et al., 1980; Van Vaeck et al., 1984). Van Vaeck et al. (1984)
found up to 70% of some n-alkanes volatilized from the filter on exposure to a clean air
stream. Coutant et al. (1988) reported that the amount of fluoranthene and pyrene lost
through the volatilization artifact for a set of ambient samples ranged from 7 to 62% and
16 to 83%, respectively. Eatough et al. (1989) concluded that 40 to 80% of the organic
material was lost after collection from samples at Hopi Point in the Southwestern United
States. It has been proposed that an upper limit for the volatilization artifact is reached if the
concentration of the volatilizing species reaches its equilibrium vapor concentration in the air
exiting the filter, but that actual loss from the filter can be substantially lower because of
slow volatilization kinetics or strong adsorption on particulate matter (Pupp et al., 1974).
The volatilization artifact has been offered as a possible explanation for frequently observed
variations in concentrations of particulate organic matter with flow rate, face velocity and
sampling period duration (Delia Fiorentina et al., 1975; Appel et al., 1979; Schwartz et al.,
1981). An increase in pressure drop across the filter during sampling can also promote
volatilization artifact if enough particulate matter is collected (Van Vaeck et al., 1984).
However, pressure drop does not appear to explain artifact behavior under typical sampling
conditions if the pressure drop across the filter does not change during sampling (McDow
and Huntzicker, 1990; Turpin et al., 1994).
Adsorption Artifact
Other workers have been more concerned with adsorption of the gas-phase organics.
Cadle et al. (1983) reported that adsorbed vapor accounted for an average of 15% of the
organic carbon collected on quartz fiber filters. In the recent Carbonaceous Species Methods
Intercomparison Study it was estimated that organic vapor adsorption on filters caused
organic aerosol concentrations to be overestimated by 14 to 53% (Hering et al., 1990).
Significant adsorption of organic vapors has also been observed on backup filters from a
variety of different primary aerosol sources (Hildemann et al., 1991). The adsorption
4-106
-------
artifact appears to be inversely related to participate organic matter concentration, so that
artifact correction becomes more important at lower concentrations of particulate organic
matter as shown in Figure 4-30 (McDow and Huntzicker, 1990). Adsorption artifact also
varies with face velocity (McDow and Huntzicker, 1990; Turpin et al., 1993b) and sampling
duration (McDow and Huntzicker, 1993), and significant amounts of adsorbed vapor
volatilizes when clean air flows across the filter (McDow and Huntzicker, 1993). Because of
this, it is not possible to distinguish between adsorption and volatilization artifacts either by
blowing clean air across a filter or by a simple comparison of variations of collected organic
mass with face velocity or sampling duration. Adsorption occurs to a greater extent on
filters which have already collected organics on the filter surface during sampling than on
clean filters not previously used for sampling, suggesting that the filter becomes an
increasingly better adsorbent as adsorbed vapors build up on the filter (Gotham and
Bidleman, 1992).
The following compounds have been observed to be adsorbed on quartz or glass fiber
filters: n-alkanes (Eichmann et al., 1979; Hart and Pankow, 1990), PAH (Ligocki and
Pankow, 1989), and formaldehyde (Klippel and Warneck, 1980). Appel et al. (1989)
analyzed backup filters for carbonate and ruled out carbon dioxide as a major contributor to
adsorption artifact in Los Angeles on the basis of these analyses.
Artifact Correction
Appel et al. (1989) advocated a simple backup filter correction procedure described by
Equation 4-1:
Cp = QQ1- QQ2 (4-1)
where Cp is artifact corrected particulate concentration, QQ1 represents the mass collected
on filter QQ1 and QQ2 represents the mass collected on downstream backup filter QQ2
(Figure 4-31). In some cases a modified backup filter correction procedure described by
Equation 4-2 appears to be more accurate (McDow and Huntzicker, 1990):
Cp = QQ1 - TQ2 (4-2)
4-107
-------
50
40
I 30
o
S 20
10
0
4 6 8 10 12
Uncorrected OC (ngC/m3)
14
16
Figure 4-30. Percent correction for vapor adsorption on quartz fiber filters for
submicrometer particle sampling at a face velocity of 40 cm s-1 for
13 samples in Portland, OR.
Source: McDow and Huntzicker (1990).
where Cp is artifact corrected particulate concentration, QQ1 represents the mass collected
on filter QQ1 in Figure 4-31, and TQ2 represents the mass collected from filter TQ2, the
backup filter behind a Teflon filter in a parallel sampling port.
Several approaches have been used to attempt to determine the relative importance of
the adsorption and volatilization artifacts. Using quartz fiber denuders to remove vapors
upstream of filter samples, Appel et al., (1989) found 59% and Fitz (1990) found 80% on
average of the organic mass adsorbed on the backup filter could be removed by the denuder,
indicating that the 41% or 20% of the organic mass adsorbed on the backup filter was
volatilized from the collected particulate matter.
4-108
-------
Inlet
Inlet
] QQ1
TQ1
] QQ2
] TQ2
Figure 4-31. Two types of filter series used for adsorption artifact corrections. QQ1 is
a quartz fiber filter, and QQ2 is a quartz fiber backup filter to a quartz
filter. TQ1 is a Teflon membrane filter, and TQ2 is a quartz fiber backup
filter to a Teflon filter.
Source: McDow and Huntzicker (1990).
McDow and Huntzicker (1990) used Equation 4-3 to correct for adsorption artifacts in
samples simultaneously collected at three different face velocities. They found that in four
experiments more than 80% of the observed difference in organic carbon mass was
eliminated by this correction procedure. In contrast, if the organic carbon mass on the
backup filter was added to that of the front filter the difference between samples collected at
different face velocities was significantly greater. This suggests that adsorption artifact is
more likely to account for observed face velocity differences than volatilization artifact.
Eatough et al. (1989, 1993) felt that both the adsorption and the volatilization artifacts
were important. Eatough concluded that the backup filter, either QQ2 or TQ2 in
Figure 4-32, would adsorb both organic material from the gas phase and organic vapors
volatilized from the collected paniculate matter. In order to obtain a correct measure of the
4-109
-------
Sampler 1
DENUDER-
FILTER
Sampler 2
FILTER-
DENUDER
Legend
Diffusion
Denuder
Quartz
Filter
Sorbent
Filter
Figure 4-32. Schematic of the BYU Organic Sampling System. Sampler 1
(denuder/filter) and sampler 2 (filter/denuder).
Source: Eatough (1995).
4-110
-------
organic paniculate matter, present in the ambient air in paniculate form, it would be
necessary to eliminate the adsorption artifact and add back the volatilization artifact.
Accordingly, Eatough collected paniculate matter using two parallel sampling trains
described in Figure 4-32 (Eatough et al., 1989, 1993; Eatough, 1995) and proposed as an
artifact correction equation:
Cp = Ql,l + Ql,2 + CIF1J/E - CIF2J/E (4-3)
where: Cp is artifact corrected particulate concentration; Ql,l and Ql,2 are the organic
carbon masses collected on the first and second filters following the denuder in sampler 1 of
Figure 4-32, respectively; CIF1,1 and CIF2,1 are the carbon masses collected on the sorbent
samplers, carbon impregnated filters (GIF) in samplers 1 and 2 in Figure 4-32, respectively;
and E is the vapor collection efficiency of the denuder. Eatough (1995) demonstrated that
the denuder, made from carbon impregnated filter paper (GIF), removed all of the gas phase
organic that could be adsorbed on the quartz fiber filter material. Thus, the organic material
on Ql,2 would be due to the volatilization artifact only and Q2,2 - Ql,2 would give an
indication of the adsorption artifact (assuming independent adsorption of both artifacts). Any
organic material volatilized from the organic particles collected on Q 1,1 and not adsorbed on
Ql.l or Ql,2 would be adsorbed on CIF1.1. While the denuder is 100% efficient in
removing organic material that would adsorb on quartz fiber filters, it is not 100% efficient
for adsorbing the organic material that would be adsorbed by the carbon impregnated filters.
Therefore, assuming that all of the organic material vaporized from particles collected on
Q2,l would be adsorbed on Q2,l, Q2,2 or the denuder in Sampler 2, CIF2,1 may be used to
correct CIF2,2 for any organic material which passed through the denuder on sampler 1 and
was adsorbed on CIF1,2. Since the carbon impregnated filters in the denuders are not 100%
efficient they are each corrected for their efficiency (measured separately by comparing the
organic mass on several carbon impregnated filters in series).
Several types of samplers have also been designed to reduce sampling artifacts. Van
Vaeck et al. (1984) designed a sampler which automatically replaced filters after short time
intervals. This prevented large increases in pressure drop across the filter observed during
the relatively long sampling periods they typically used. Several denuder systems have also
4-111
-------
been designed to reduced sampling artifacts (Appel, et al., 1989; Coutant et al., 1988;
Eatough et al., 1989, 1993; Fitz, 1990). Turpin et al. (1993b) developed a laminar flow
separator, which also utilizes differences in diffusion rates between vapors and particles to
reduce sampling artifacts.
Little is known concerning the chemical species responsible for sampling artifacts, with
the exception of the few species reported here. Volatile organic compounds (VOCs) such as
formaldehyde make a contribution to the adsorption artifact. Semi-volatile organic
compounds (SVOCs), those compounds such as n-alkanes and poly cyclic aromatic
hydrocarbons, which are generally distributed between the vapor phase and paniculate matter
in the atmosphere, play a role in both types of artifacts.
Equilibrium partitioning of SVOCs between condensed phase, vapor phase and adsorbed
phase depends on their temperature- dependent vapor pressure, the surface area of the
collection material, and their concentration. (Section 3.3.3; Junge, 1977; Yamasaki et al.,
1982; Pankow, 1987). Some examples of possible causes of SVOC phase equilibrium shifts
leading to sampling artifacts are (1) changes in temperature, either if the air temperature
changes during sampling, if the sampler is cooled or heated, or if samples are allowed to
stand in room air with a different temperature than during sampling, (2) changes in surface
area, either in ambient aerosol surface area, or the increase in available surface area for
adsorption experienced when an SVOC encounters additional filter surface area, (3) changes
in SVOC concentration, which can also occur during sampling or after sample collection if
samples are exposed to room air. Thus SVOCs can vaporize during the temperature and
relative humidity conditioning prescribed by the Federal Reference Method for measuring
paniculate mass.
Conclusions
The following conclusions can be drawn from this literature review. (1) There is
general agreement that sampling artifacts can cause significant errors in the measurement of
paniculate organic mass. (2) Disagreement exists about whether adsorption artifact or
volatilization artifact are the most important sampling artifact to consider. It is not clear to
what extent disagreements between studies are caused by differences in the aerosol sampled,
sampling procedures used, or interpretation of sampling results. (3) Little is known about
4-112
-------
the causes of sampling artifacts or the individual species involved. (4) Sampling artifacts
may be strongly influenced by changes in temperature or organic vapor concentration during
sampling and storage. Procedures which do not take these factors into consideration are
likely to contribute to sampling artifact errors. (5) Organic aerosol sampling artifacts can
cause significant errors in particle mass measurements in areas where a large fraction of the
paniculate mass is organic.
4.3.5 Methods Validation
The use of multiple methods and parallel samplers achieves both optimum performance
and quality assurance. While this has been a part of major research studies since the 1970s,
its extension to long-term monitoring of aerosols was most extensively introduces in the
SCENES and IMPROVE visibility programs (Eldred and Cahill, 1984). The concept was
labeled, "Integral Redundancy," and was recently adopted by the United Nation's Global
Atmospheric Watch Program.
The internal consistency checks applied to the IMPROVE network are listed as follows:
(1) Mass (gravimetric) is compared to the sum of all elements on the Teflon-membrane
filter of Channel A (PIXE, PESA, XRF analysis; Internally XRF and PIXE are
compared for elements around iron). This was pioneered in the SCENES program
and is now the standard practice for many aerosol studies.
(2) Sulfate, by ion chromatography on Channel B's nylon filter, after an acidic vapor
denuder, is compared to sulfur (X3) from Channel A's Teflon-membrane filter by
PIXE. Agreement is excellent, except for summer.
(3) Organic matter, by combustion on Channel C's quartz-fiber filter stack, is
compared to organic matter via PESA analysis of hydrogen on Channel A's Teflon-
membrane filter. This is an exceptionally sever test due to the nature of organics.
These comparisons are made for every IMPROVE analysis, yielding about 25,000
comparisons to date (Malm et al., 1994).
These types of data validation checks should be carried out in every PM measurement
program to ensure the accuracy, precision, and validity of the chemical analysis data.
4-113
-------
4.4 BIOAEROSOLS SAMPLING AND ANALYSIS
4.4.1 Analytical Methods
Because of the complexity of the particles contained in the term "bioaerosols" no single
analytical method is available that will allow assessment of all of the potential biologically-
derived particle in an aerosol. Table 4-5 is an overview of the available analytical methods,
examples of the kinds of agents detected, and some sampling considerations.
TABLE 4-5. OVERVIEW OF ANALYTICAL METHODS
Culture
Microscopy
Immunoassay
Bioassay
Kinds of Agents
culturable
organisms
recognizable
particles
agents that
stimulate
antibodies
agents exerting
observable effects
Examples
fungal spores, yeasts,
bacteria, viruses (rarely
used)
pollen, fungal spores,
bacteria
allergens, aflatoxin, glucan
endotoxin, cytotoxins
Sampling
Considerations
viability must be
protected
good optical
quality is
required
agents must be
elutable from
sampling
medium.
Activity must be
preserved
same as
immunoassay
Chemical assays
Molecular
techniques
in a biological
system
chemicals with
recognized
characteristics
DNA or RNA-
containing particles
trichothecene toxins
specific organisms
same as
immunoassay
A good principle to guide the kind of analysis for use in detecting a particular
bioaerosol is to use the approach that best characterizes the agent of disease rather than the
4-114
-------
agent-bearing particle. Thus, while culture is appropriate where infectious disease is of
concern, or where you know that allergens are only released as a spore germinates, it is
likely to be only a poor indicator for mycotoxin exposure. Culture always underestimates
actual levels of any viable aerosol because no culture conditions are appropriate for all cells.
The extent of the underestimate can be very large if an aerosol is damaged or consists
primarily of non-living cells. The reason culture is not the best approach for evaluating
mycotoxins is because it is unlikely that viability is a necessary requirement for mycotoxin
release from spores (although this has not been studied).
Microscopy allows direct counts of identifiable particles. Light microscopy will reveal
particles as small as 1.5 /mi reliably. Identification of the type of particle requires either
some morphological characteristic unique to the particle, or some factor that can be labelled
with a visible dye. Most pollens and many fungal spores can be placed in relevant groupings
by microscopy alone. Bacteria, on the other hand, can only be counted. Specific techniques
to enhance visibility based on specific immune responses or DNA polymerization techniques
have yet to be developed.
Immunoassays detect the actual agent of hypersensitivity disease. Two types are
commonly used: one based on a mixture of polyclonal antibodies that detects a relatively
wide range of allergens, and the other based on monoclonal antibodies that detects only the
single allergen to which the antibody is detected. Endotoxin is measured using a bioassay
that involves dose-dependant clotting of lysate from the amoebocytes of horseshoe crabs.
This is not only an agent-specific assay, but actually measures biological activity of the
endotoxin rather than simply the number of molecules.
4.4.2 Sample Collection Methods
Bioaerosol particles follow the principles of physics like any other particle type, and are
collected from aerosols by equipment that use these common physical principles. Bioaerosol
sampling devices were recently reviewed in depth by Macher et al., 1995. The most
commonly used bioaerosol samplers are suction sieve impactors that collect particles directly
on culture media. The second most commonly used types are slit impactors that collect
particles either on rotating plates of agar, or on grease-coated surfaces. Rotating arm
impactors are often used for the collection of pollen in clinical allergy practices across the
4-115
-------
country (American Academy of Allergy and Immunology, 1994). In addition to the
impactors, bioaerosols are also collected using filtration, either with filters mounted in
cassettes or on large sheets of filter material mounted in high-volume suction samplers.
Liquid impingers are also used under research conditions.
Analysis of culture plate samples is more or less restricted to static culture, although
one group has developed a procedure for suspending the catch in a liquid, and using dilution
culture to increase the upper level of sensitivity. For static culture, the maximum number of
fungal colonies on a 100 mm petri plate that does not result in inhibition between colonies is
about 30. The number of bacteria is much higher (~ 100). Sieve plate impactors have a
limited number of sites available for deposition, so that above some given number than
depends on the number of holes in the sieve plate, multiple impactions occur. For biological
aerosols, this means that only one colony of one organism is likely to appear at each site
although several different kinds of organisms might have been collected. Rotating slit culture
samplers do not present this constraint, although the upper limit to prevent competition losses
remains in effect.
Analysis of samples collected on greased surfaces is generally limited to microscopy,
although some attempts have been to transfer allergens to nitrocellulose membranes and
analyze by immunoassay (immunoblotting). Filtration samples can be analyzed by culture,
microscopy, and by elution followed by immuno- or bioassay. Obviously these are the most
versatile devices. However, cultural counts made from filter collections may severely
underestimate actual levels because of desiccation on the filter. Microscopic analysis
requires large numbers of particles on the filter, so that, unless long sampling times are used,
the sensitivity can be poor. Filter collections have been the choice for samples to be
analyzed by immunoassay (e.g., cat allergens) and bioassay (e.g., Endotoxin).
4.5 SUMMARY
Though much of the discussion in the preceding sub-sections has been specific to
different sampling and analysis methods, several generalizations can be drawn.
First, it is found that samples taken to determine compliance with air quality standards
are often used for other purposes, such as source apportionment, personal exposure, and
4-116
-------
chemical characterization. Different sampling systems that are more closely coupled to the
intended analysis methods may be needed to attain additional monitoring objectives.
Second, though off-site gravimetric analysis of filter samples is straightforward and
relatively inexpensive in terms of equipment, more costly in-situ monitors have the potential
to provide higher time resolution, more frequent sampling intervals, and possibly reduced
manpower requirements. The mass concentrations obtained may not always be comparable
between the manual and automated methods, owing to differences in particle volatilization
and liquid water content of off-site and in situ measurements.
Third, technology is now proven and available to measure the major chemical
components of suspended particles, e.g. many separate elements, organic carbon, elemental
carbon, sulfate, nitrate, ammonium, and H+ ions. With reasonable assumptions regarding
oxide and hydrocarbon forms, most of the measured mass at many locations can be
accounted for by these chemical measurements. This technology could be applied more
routinely than it has in the past to better characterize particles to determine compliance with
future air quality standards.
Fourth, since ambient particle size distributions contain fine and coarse particle modes,
with a minimum between them in the 1 to 3 /urn size range, shifts in inlet cut-points near the
2.5 urn size range are not expected to have a large effect on the mass collected owing to the
low proportion of particles with sizes near this cut-point. This contrasts to the sensitivity of
PM10 mass concentrations to small shifts in the cutpoints of PM10 inlets, where the maximum
of the coarse mode occurs between 6 and 25 /im (Lundgren and Burton, 1995).
Fifth, concentrations of volatile chemicals (such as ammonium nitrate or certain organic
compounds) and liquid water may change during sampling, during sample transport and
storage, and during sample analysis. Liquid water may be removed by lowering the relative
humidity surrounding the sample by heating the sampled air stream, or by selectively
denuding the airstream of water vapor. Several sampling systems involving diffusion
denuders and absorbing substrates operating in series and in parallel have been demonstrated
to quantify volatilized particles, but these are not practical for sustained, long-term
monitoring on limited budgets.
Finally, collocated studies show substantial differences between mass concentration
measurements acquired by different sampling systems. They also show differences for
4-117
-------
similar sampling systems for which procedures are somewhat different. Inlet maintenance,
filter handling and storage, laboratory analyses, and quality control procedures are just as
important variables as sampler design in explaining these differences. Inlet characteristics
and particle volatilization properties are the most important variables that cause mass
concentrations to differ. The lack of common calibration standards is one of the major
reasons for differences between certain chemical analysis results.
This chapter also briefly describes the technical capabilities and limitations of specific
aerosol sampling procedures, focusing on those that (1) were used to collect data supporting
other sections in this document, (2) supported the existing PM10, TSP and Pb regulations,
and (3) have application in development of a possible fine particle standard. The discussion
of aerosol separation technologies is divided between devices used to mimic the larger
particle penetration rationales for the upper airways, and those used to mimic smaller particle
penetration to the sub-thoracic regions. The applications of performance specifications to
define these measurement systems for regulatory purposes are discussed with observations
suggesting that the current specification process has not always assured the necessary
sampling accuracy. Particle sampling systems for specialty applications, including automated
samplers and personal exposure monitors, are briefly described.
4.5.1 PM10 Sampling
Laboratory and field testing reported in the literature since 1987 suggest that the EPA
specifications and test requirements for PM10 samplers have not adequately controlled the
differences observed in collocated ambient sampling. The most significant performance
flaws have combined to produce mass concentration biases as large as 60%. These biases
appear to have resulted from the combined factors of (1) allowing a cutpoint tolerance of
10 ± 0.5 f*,m, (2) placing an inadequate restriction on internal particle bounce, and
(3) allowing a degradation of particle separation performance as certain technology PM10
inlets became soiled. The between-sampler bias from a ±0.5 /m tolerance limit is
predictable and should provide PM10 concentration differences significantly less than ±10%
in almost all cases. Design practices (primarily surface coatings with viscous oil) to
minimize the penetration caused by bounce and resuspension have been shown to be very
effective. The magnitude of biases from soiling events can be accommodated by not
4-118
-------
allowing the inlet to become excessively dirty during operation through routine cleaning prior
to sampling. Particle bounce or soiling problems have not been reported for the PM10 inlets
for the dichotomous sampler.
Based on the current understanding of the PM10 sampling process, it could be expected
that sampling systems can now be designed and concentration measurements made that are
within 10% of the true concentration. This range poses the greatest concern where the
measured concentrations are near a standard exceedance level. A review by EPA of the
current PM10 performance requirements and possible amendments of the existing
specifications may be appropriate, given the information base now available.
4.5.2 Fine Particle Sampling
The technology is available to provide an accurate Fine particle cutpoint (e.g. 1.0 or
2.5 /im) for routine sampling. Virtual impactors and cyclones have been shown to be the
most trouble-free and versatile methodologies. The exclusion of larger particles using a
scalping inlet eliminates many of the transport and loss problems encountered during PM10
sampling. The absence of the Coarse particle fraction, however, exaggerates the problems
inherent with Fine particle chemistry, such as particle-substrate interactions and sublimation
losses. Although it could be expected that Fine particle mass concentration measurements
can be made within 10% of the true concentration, accurate chemical speciation may require
more comprehensive sampling system components, including gas stream denuders and
sequential filter packs.
4.5.3 Concentration Corrections to Standard Conditions
The appropriateness of the correction of particulate concentrations to a reference
temperature and pressure is currently under review at EPA. Aerodynamic sampling requires
incorporation of local conditions to provide the correct velocities for accurate particle size
separation. Correcting the collection volume to standard conditions may improperly
influence interpretations of the developed relationships between particle concentration and
adverse health responses. It appears to be more appropriate to compute particle
concentrations at site conditions and provide temperature and barometric pressure data
subsequently, as needed for data interpretation.
4-119
-------
4.5.4 Performance Versus Design Specifications for Sampling Systems
The current EPA PM10 Reference and Equivalent Method program established in 1987
is based on providing the necessary data quality by using sampling performance
specifications. Several research studies have recently reported that key elements of the
sampling process were inadequately considered when the original performance specifications
were developed. The observations from these controlled studies have been bolstered by
reviews of field data from collocated PM10 samplers that showed substantial biases under
certain conditions. The particle sampling process is complex. Obtaining an acceptable bias
level using performance standards is difficult, but not impossible, if the appropriate
developmental research is identified and implemented. The alternative approach of defining
sampling systems by design specifications seems attractive, but may ultimately pose more
problems than are solved without producing better quality data. Additionally, specification
of a sampling system by design would have the undesirable attribute of virtually eliminating
further new technology research. The approach for specifying particle sampling systems is
currently under review at EPA.
4.5.5 Automated Sampling
The performances of two sampling methods that are currently designated as Equivalent
PM10 methods by EPA - beta attenuation and the TEOM sampler - have been evaluated
extensively in field settings. Although acceptable comparisons with EPA Reference sampling
methods are reported in collocated field studies, attention must be paid to situations where
significant biases existed. These biases have been attributed to a number of factors, but
focused on the treatment of the particle sample during and after collection. The presence of
highly reactive or unstable particles at sampling locations in the western U.S. appears to
cause the greatest concern, because of a higher proportion of these species. These bias
issues are significant because they complicate the use of automated samplers as "triggers" for
control strategy actions, and they question the adequacy of the existing performance
specifications for equivalent PM10 sampling systems.
4-120
-------
4.5.6 PM Samplers for Special Applications
Reviews of typical U.S. personal activity patterns suggest that personal exposure
sampling for particulates should also be considered in developing population risk
assessments. Relatively unobtrusive personal sampling systems have been designed for a
number of particle size cutpoints, and recent studies suggest that acceptable accuracies and
precisions are possible. The collection of particle size distribution data can assist in
identifying paniculate sources and subsequent studies of particle transport and fate. Well
characterized cascade impactors are available that cover the aerodynamic size range from at
least 0.1 to 10 /mi. More automated optical systems are also available, providing either
optical or aerodynamic diameter ranges from about 0.5 to 10 /*m. Source apportionment
sampling systems are available to assist in relating the chemical attributes of ambient
paniculate matter to the chemical "signatures" from various source categories. This is
accomplished by using sampling system components and collection substrates designed to
collect specific chemical classes (e.g., a suite of individual metals, speciated carbon) in
defined particle size categories.
4-121
-------
REFERENCES
Allen, D. T.; Palen, E. J.; Haimov, M. I.; Hering, S. V.; Young, J. R. (1994) Fourier transform infrared
spectroscopy of aerosol collected in a low pressure impactor (LPI/FTIR): method development and field
calibration. Aerosol Sci. Technol. 21: 325-342.
American Academy of Allery & Immunology. (1994) Aeroallergen Monitoring Network 1994 pollen and spore
report. Milwaukee, WI: American Academy of Allery & Immunology.
American Conference of Governmental Industrial Hygienists (ACGIH). (1985) Particle size-selective sampling in
the workplace: report of the ACGIH technical committee on air sampling procedures. Cincinnati, OH:
American Conference of Governmental Industrial Hygienists.
American Conference of Governmental Industrial Hygienists (ACGIH). (1994) 1994-1995 threshold limit values
for chemical substances and physical agents and biological exposure indices. Cincinnati, OH: American
Conference of Governmental Industrial Hygienists.
Anand, N. K.; McFarland, A. R.; Kihm, K. D.; Wong, F. S. (1992) Optimization of aerosol penetration through
transport lines. Aerosol Sci. Technol. 16: 105-112.
Anlauf, K. G.; MacTavish, D. C.; Wiebe, H. A.; Schiff, H. I.; Mackay, G. I. (1988) Measurement of
atmospheric nitric acid by the filter method and comparisons with the tuneable diode laser and other
methods. Atmos. Environ. 22: 1579-1586.
Appel, B. R.; Colodny, P.; Wesolowski, J. J. (1976) Analysis of carbonaceous materials in southern California
atmospheric aerosols. Environ. Sci. Technol. 10: 359-363.
Appel, B. R.; Hoffer, E. M.; Haik, M.; Wall, S. M.; Kothny, E. L.; Knights, R. L.; Wesolowski, J. J. (1977)
Characterization of organic paniculate matter. Final report. Sacramento, CA: California Air Resources
Board; report no. ARB-R-5-682-77-72. Available from: NTIS, Springfield, VA; PB-279209.
Appel, B. R.; Hoffer, E. M.; Kothny, E. L.; Wall, S. M.; Haik, M.; Knights, R. L. (1979) Analysis of
carbonaceous material in southern California atmospheric aerosols. 2. Environ. Sci. Technol. 13: 98-104.
Appel, B. R.; Tokiwa, Y.; Haik, M. (1981) Sampling of nitrates in ambient air. Atmos. Environ. 15: 283-289.
Appel, B. R.; Tokiwa, Y.; Haik, M.; Kothny, E. L. (1984) Artifact particulate sulfate and nitrate formation on
filter media. Atmos. Environ. 18: 409-416.
Appel, B. R.; Povard, V.; Kothny, E. L. (1988a) Loss of nitric acid within inlet devices intended to exclude
coarse particles during atmospheric sampling. Atmos. Environ. 22: 2535-2540.
Appel, B. R.; Tokiwa, Y.; Kothny, E. L.; Wu, R.; Povard, V. (1988b) Evaluation of procedures for measuring
atmospheric nitric acid and ammonia. Atmos. Environ. 22: 1565-1573.
Appel, B. R.; Cheng, W.; Salaymeh, F. (1989) Sampling of carbonaceous particles in the atmosphere—
II. Atmos. Environ. 23: 2167-2175.
Arey, J.; Zielinska, B.; Atkinson, R.; Winer, A. M.; Ramdahl, T.; Pitts, J. N., Jr. (1986) The formation of
nitro-PAH from the gas-phase reactions of fluoranthene and pyrene with the OH radical in the presence
of NOj. Atmos. Environ. 20: 2339-2345.
4-122
-------
Arey, J.; Zielinska, B.; Atkinson, R.; Winer, A. M. (1987) Polycyclic aromatic hydrocarbon and nitroarene
concentrations in ambient air during a wintertime high-NO^ episode in the Los Angeles basin. Atmos.
Environ. 21: 1437-1444.
Arey, J.; Zielinska, B.; Atkinson, R.; Winer, A. M. (1988) Formation of nitroarenes during ambient
high-volume sampling. Environ. Sci. Technol. 22: 457-462.
Arnold, S.; Hague, W.; Pierce, G.; Sheetz, R. (1992) The use of beta gauge monitors for PSI and every day
SIP monitoring: an overview of the Denver experience. In: Chow, J. C.; Ono, D. M., eds. PM10
standards and nontraditional paniculate source controls, an A&WMA/EPA international specialty
conference, v. I; January; Scottsdale, AZ. Pittsburgh, PA: Air & Waste Management Association;
pp. 13-23. (A&WMA transactions series no. 22).
Atherholt, T. B.; McGarrity, G. J.; Louis, J. B.; McGeorge, L. J.; Lioy, P. J.; Daisey, J. M.; Greenberg, A.;
Darack, F. (1985) Mutagenicity studies of New Jersey ambient air particulate extracts. In: Waters,
M. D.; Sandhu, S. S.; Lewtas, J.; Claxton, L.; Strauss, G.; Nesnow, S., eds. Short-term bioassays in
the analysis of complex environmental mixtures IV. New York, NY: Plenum Press; pp. 211-231.
(Environmental science research: v. 32).
Atkinson, R.; Arey, J.; Winer, A. M.; Zielinska, B. (1988) A survey of ambient concentrations of selected
polycyclic aromatic hydrocarbons (PAH) at various locations in California [final report]. Sacramento,
CA: California Air Resources Board; contract no. A5-185-32.
Bailey, D. L. R.; Clayton, P. (1980) The measurement of suspended particulate and carbon concentrations in the
atmosphere using standard smoke shade methods. Stevenage, Hertfordshire, United Kingdom: Warren
Spring Laboratory; report no. LR 325 (AP).
Ball, D. J.; Hume, R. (1977) The relative importance of vehicular and domestic emissions of dark smoke in
greater London in the mid-1970s, the significance of smoke shade measurements, and an explanation of
the relationship of smoke shade to gravimetric measurements of particulate. Atmos. Environ.
11: 1065-1073.
Baron, P. A. (1993) Measurement of asbestos and other fibers. In: Willeke, K.; Baron, P. A., eds. Aerosol
measurement: principles, techniques, and applications. New York, NY: Van Nostrand Reinhold;
pp. 560-590.
Baron, P. A.; Willeke, K. (1993) Aerosol fundamentals. In: Willeke, K.; Baron, P. A., eds. Aerosol
measurement: principles, techniques, and applications. New York, NY: Van Nostrand Reinhold;
pp. 8-22.
Baron, P. A.; Mazumder, M. K.; Cheng, Y. S. (1993) Direct-reading techniques using optical particle detection.
In: Willeke, K.; Baron, P. A., eds. Aerosol measurement: principles, techniques, and applications.
New York, NY: Van Nostrand Reinhold; p. 381-409.
Bartley, D. L.; Breuer, G. M. (1982) Analysis and optimization of the performance of the 10 mm cyclone.
Am. Ind. Hyg. Assoc. J. 43: 520-528.
Benner, C. L.; Eatough, D. J.; Eatough, N. L.; Bhardwaja, P. (1991) Comparison of annular denuder and filter
pack collection of HNO3 (g), HNO2 (g), SO2 (g), and particulate-phase nitrate, nitrite and sulfate in the
south-west desert. Atmos. Environ. Part A 25: 1537-1545.
Bennett, R. L.; Stockburger, L.; Barnes, H. M. (1994) Comparison of sulfur measurements from a regional fine
particle network with concurrent acid modes network results. Atmos. Environ. 28: 409-419.
4-123
-------
Bidleman, T. F.; Billings, W. N.; Foreman, W. T. (1986) Vapor-particle partitioning of semivolatile organic
compounds: estimates from field collections. Environ. Sci. Technol. 20: 1038-1043.
Biswas, P.; Jones, C. L.; Flagan, R. C. (1987) Distortion of size distributions by condensation and evaporation
in aerosol instruments. Aerosol Sci. Technol. 7: 231-246.
Botham, R. A.; Hughson, G. W.; Vincent, J. H.; Mark, D. (1991) The development of a test system for
investigating the performances of personal aerosol samplers under actual workplace conditions. Am. Ind.
Hyg. Assoc. J. 52: 423-427.
Brauer, M.; Koutrakis, P.; Spengler, J. D. (1989) Personal exposures to acidic aerosols and gases. Environ. Sci.
Technol. 23: 1408-1412.
Brockmann, J. E.; Yamano, N.; Lucero, D. (1988) Calibration of the aerodynamic particle sizer
3310 (APS-3310) with polystyrene latex monodisperse spheres and oleic acid monodisperse
particles. Aerosol Sci. Technol. 8: 279-281.
Broddin, G.; Cautreels, W.; Van Cauwenberghe, K. (1980) On the aliphatic and polyaromatic hydrocarbon levels
in urban and background aerosols from Belgium and the Netherlands. Atmos. Environ. 14: 895-910.
Brown, R. C.; Wake, D.; Thorpe, A.; Hemingway, M. A.; Roff, M. W. (1994) Preliminary assessment of a
device for passive sampling of airborne paniculate. Ann. Occup. Hyg. 38: 303-318.
Bruynseels, F.; Storms, H.; Van Grieken, R.; Van der Auwera, L. (1988) Characterization of North Sea
aerosols by individual particle analysis. Atmos. Environ. 22: 2593-2602.
Buckley, T. J.; Waldman, J. M.; Freeman, N. C. G.; Lioy, P. J.; Marple, V. A.; Turner, W. A. (1991)
Calibration, intersampler comparison, and field application of a new PM-10 personal air-sampling
impactor. Aerosol Sci. Technol. 14: 380-387.
Buettner, H. (1990) Measurement of the size of fine nonspherical particles with a light-scattering particle counter.
Aerosol Sci. Technol. 12: 413-421.
Butler, F. E.; lungers, R. H.; Porter, L. F.; Riley, A. E.; Toth, F. J. (1978) Analysis of air particulates by ion
chromatography: comparison with accepted methods. In: Sawicki, E.; Mulik, J. D.; Wittgenstein, E.,
eds. Ion chromatographic analysis of environmental pollutants. Ann Arbor, MI: Ann Arbor Science
Publishers, Inc.; pp. 65-76.
CEN (European Committee for Standardization). (1993) Workplace atmospheres—size fraction definitions for
measurement of airborne particles. London, United Kingdom: British Standards Institution; publication
no. BS EN 481: 1993; BS 6069: section 3.5: 1993.
Cadle, S. H.; Groblicki, P. J. (1982) An evaluation of methods for the determination of organic and elemental
carbon in paniculate samples. In: Wolff, G. T.; Klimisch, R. L., eds. Paniculate carbon: atmospheric
life cycle. New York, NY: Plenum Press; pp. 89-109.
Cadle, S. H.; Groblicki, P. J.; Stroup, D. P. (1980a) Automated carbon analyzer for paniculate samples.
Anal. Chem. 52: 2201-2206.
Cadle, S. H.; Nebel, G. J.; Williams, R. L. (1980b) Measurements of unregulated emissions from General
Motors' light-duty vehicles. SAE Trans. 88: 2381-2401.
Cadle, S. H.; Groblicki, P. J.; Mulawa, P. A. (1983) Problems in the sampling and analysis of carbon particles.
Atmos. Environ. 17: 593-600.
4-124
-------
Cahill, T. A. (1980) Proton microprobes and particle-induced X-ray analytical systems. Annu. Rev. Nucl. Part.
Sci. 30: 211-252.
Cahill, T. A.; Wakabayashi, P. (1993) Compositional analysis of size-segregated aerosol samples. In: Newman,
L., ed. Measurement challenges in atmospheric chemistry. Washington, DC: American Chemical Society;
pp. 211-228. (Advances in chemistry series no. 232).
Cahill, T. A.; Eldred, R. A.; Kusko, B. H.; Feeney, P. J.; Malm, W. C. (1987) Concentrations of natural
hydrocarbon particles at National Park Service sites as derived from mass/hydrogen/sulfur correlations.
In: Bhardwaja, P. S., ed. Visibility protection: research and policy aspects, an APCA international
specialty conference; September 1986; Grand Teton National Park, WY. Pittsburgh, PA: Air Pollution
Control Association; pp. 407-417. (APCA transactions series no. TR-10).
Cahill, T. A.; Eldred, R. A.; Motallebi, N.; Malm, W. C. (1989) Indirect measurement of hydrocarbon aerosols
across the United States by nonsulfate hydrogen-remaining gravimetric mass correlations. Aerosol Sci,
Technol. 10: 421-429.
Cahill, T. A.; Eldred, R. A.; Feeney, P. J.; Beveridge, P. J.; Wilkinson, L. K. (1990) The stacked filter unit
revisited. In: Mathai, C. V., ed. Visibility and fine particles: an A&WMA/EPA international specialty
conference; October 1989; Estes Park, CO. Pittsburgh, PA: Air & Waste Management Association;
pp. 213-221. (A&WMA transactions series no. TR-17).
Cahill, T. A.; Gill, T. E.; Gillette, D. A.; Gearhart, E. A.; Reid, J. S.; Yau, M.-L. (1994) Generation,
characterization and transport of Owens (Dry) Lake dusts [final report]. Sacramento, CA: California Air
Resources Board; contract no. A132-105.
Cantrell, B. K.; Williams, K. L.; Watts, W. P., Jr.; Jankowski, R. A. (1993) Mine aerosol measurement.
In: Willeke, K.; Baron, P. A., eds. Aerosol measurement: principles, techniques, and applications.
New York, NY: Van Nostrand Reinhold; pp. 591-611.
Casuccio, G. S.; Janocko, P. B.; Lee, R. J.; Kelly, J. F.; Dattner, S. L.; Mgebroff, J. S. (1983) The use of
computer controlled scanning electron microscopy in environmental studies. J. Air Pollut. Control Assoc.
33: 937-943.
Cautreels, W.; Van Cauwenberghe, K. (1978) Experiments on the distribution of organic pollutants between
airborne paniculate matter and the corresponding gas phase. Atmos. Environ. 12: 1133-1141.
Chan, T. L.; Lippmann, M. (1980) Experimental measurements and empirical modelling of the regional
deposition of inhaled particles in humans. Am. Ind. Hyg. Assoc. J. 41: 399-409.
Charlson, R. J.; Ahlquist, N. C.; Horvath, H. (1968) On the generality of correlation of atmospheric aerosol
mass concentration and light scatter. Atmos. Environ. 2: 455-464.
Chow, J. C.; Watson, J. G. (1994) Contemporary source profiles for geological material and motor vehicle
emissions [final report]. Research Triangle Park, NC: U.S. Environmental Protection Agency, Office of
Air Quality Planning and Standards.
Chow, J. C.; Watson, J. G.; Ono, D. M.; Mathai, C. V. (1993a) PM10 standards and nontraditional particulate
source controls: a summary of the A&WMA/EPA international specialty conference. J. Air Waste
Manage. Assoc. 43: 74-84.
4-125
-------
Chow, J. C.; Watson, J. G.; Pritchett, L. C.; Pierson, W. R.; Frazier, C. A.; Purcell, R. G. (1993b) The DRI
thermal/optical reflectance carbon analysis system: description, evaluation and applications in U.S. air
quality studies. In: Lodge, J. P., Jr. Fourth international conference on carbonaceous particles in the
atmosphere; April 1991; Vienna, Austria. Atmos. Environ. Pan A 27: 1185-1201.
Chow, J. C.; Fujita, E. M.; Watson, J. G.; Lu, Z.; Lawson, D. R.; Ashbaugh, L. L. (1994) Evaluation of
filter-based aerosol measurements during the 1987 Southern California Air Quality Study.
Environ. Monit. Assess. 30: 49-80.
Clayton, P.; Wallin, S. C. (1982) Comparison of ambient suspended paniculate matter concentrations as
measured by the British smoke sampler and the high volume sampler. Atmos. Environ. 16: 2031-2032.
Code of Federal Regulations. (1991) Appendix J to Part 50—reference method for the determination of paniculate
matter as PM10 in the atmosphere. C. F. R. 40: §50.
Colome, S. D.; Kado, N. Y.; Jaques, P.; Kleinman, M. (1992) Indoor-outdoor air pollution relations: paniculate
matter less than 10 /on in aerodynamic diameter (PM10) in homes of asthmatics. Atmos. Environ. Part A
26: 2173-2178.
Commins, B. T. (1962) Interim report on the study of techniques for determination of polycyclic aromatic
hydrocarbons in air. In: Sawicki, E.; Cassel, K., Jr., eds. Analysis of carcinogenic air pollutants:
[proceedings of a symposium]; August 1961; Cincinnati, OH. Bethesda, MD: U.S. Department of
Health, Education, and Welfare, Public Health Service, National Cancer Institute; pp. 225-233.
(National Cancer Institute monograph no. 9).
Conner, T. L.; Miller, J. L.; Willis, R. D.; Kellogg, R. B.; Dann, T. F. (1993) Source apportionment of fine
and coarse particles in southern Ontario, Canada. Presented at: 86th annual meeting & exhibition of the
Air & Waste Management Association; June; Denver, CO. Pittsburgh, PA: Air & Waste Management
Association; paper no. 93-TP-58.05.
Cook, J. P.; Oslund, W. E.; Frank, N. (1995) Evaluation of fine paniculate samplers (PM2 5) in an area of
volatile constituents. In: Paniculate matter: health and regulatory issues: proceedings of an international
specialty conference; April; Pittsburgh, PA. Pittsburgh, PA: Air & Waste Management Association;
pp. 277-296. (A&WMA publication VIP-49).
Cooper, D. W.; Guttrich, G. L. (1981) A study of the cut diameter concept for interpreting particle sizing data.
Atmos. Environ. 15: 1699-1707.
Cornille, P.; Maenhaut, W.; Pacyna, J. M. (1990) Sources and characteristics of the atmospheric aerosol near
Damascus, Syria. Atmos. Environ. Part A 24: 1083-1093.
Cotham, W. E.; Bidleman, T. F. (1992) Laboratory investigations of the partitioning of organochlorine
compounds between the gas phase and atmospheric aerosols on glass fiber filters. Environ. Sci. Technol.
26: 469-478.
Countess, R. J. (1990) mterlaboratory analyses of carbonaceous aerosol samples. Aerosol Sci. Technol.
12: 114-121.
Courtney, W. J.; Shaw, R. W.; Dzubay, T. G. (1982) Precision and accuracy of a /3 gauge for aerosol mass
determinations. Environ. Sci. Technol. 16: 236-239.
Coutant, R. W.; Brown, L.; Chuang, J. C.; Riggin, R. M.; Lewis, R. G. (1988) Phase distribution and artifact
formation in ambient air sampling for polynuclear aromatic hydrocarbons. Atmos. Environ. 22: 403-409.
4-126
-------
Coutant, R. W.; Callahan, P. J.; Kuhlman, M. R.; Lewis, R. G. (1989) Design and performance of a
high-volume compound annular denuder. Atmos. Environ. 23: 2205-2211.
Coutant, R. W.; Callahan, P. J.; Chuang, J. C.; Lewis, R. G. (1992) Efficiency of silicone-grease-coated
denuders for collection of polynuclear aromatic hydrocarbons. Atmos. Environ. Part A 26: 2831-2834.
Criss, J. W. (1976) Particle size and composition effects in x-ray fluorescence analysis of pollution samples.
Anal. Chem. 48: 179-186.
Crutcher, E. R. (1982) Light microscopy as an analytical approach to receptor modeling. In: A specialty
conference on: receptor models applied to contemporary pollution problems; October; Danvers, MA.
Pittsburgh, PA: Air Pollution Control Association; pp. 266-284. (SP-48).
Currie, L. A. (1982) Contemporary paniculate carbon. In: Wolff, G. T.; Klimisch, R. L., eds. Paniculate
carbon: atmospheric life cycle. New York, NY: Plenum Press; pp. 245-260.
Daisey, J. M.; McCaffrey, R. J.; Gallagher, R. A. (1981) Polycyclic aromatic hydrocarbons and total extractable
paniculate organic matter in the Arctic aerosol. Atmos. Environ. 15: 1353-1363.
Daisey, J. M.; Hershman, R. J.; Kneip, T. J. (1982) Ambient levels of paniculate organic matter in New York
City in winter and summer. Atmos. Environ. 16: 2161-2168.
Dams, R.; Robbins, J. A.; Rahn, K. A.; Winchester, J. W. (1970) Nondestructive neutron activation analysis of
air pollution particulates. Anal. Chem. 42: 861-867.
Davis, B. L. (1978) Additional suggestions for X-ray quantitative analysis of high-volume filter samples.
Atmos. Environ. 12: 2403-2406.
Davis, B. L. (1980) "Standardless" X-ray diffraction quantitative analysis. Atmos. Environ. 14: 217-220.
Delia Fiorentina, H.; De Wiest, F.; De Graeve, J. (1975) Determination par spectrometrie infrarouge de la
matiere organique non volatile associee aux particules en suspension dans 1'air—II. Facteurs influencant
1'indice aliphatique. [Determination of the nonvolatile organic matter associated with suspended particles
by infrared spectrometry—II. Factors influencing the aliphatic index]. Atmos. Environ. 9: 517-522.
Derde, M.-P.; Buydens, L.; Guns, C.; Massart, D. L.; Hopke, P. K. (1987) Comparison of rule-building expert
systems with pattern recognition for the classification of analytical data. Anal. Chem. 59: 1868-1871.
Divita, F., Jr. (1993) Size distributions and sources of submicrometer atmospheric particles in Washington, D.C.
and Philadelphia, PA [Ph.D. dissertation]. College Park, MD: University of Maryland. Available from:
University Microfilms, Ann Arbor, MI; publication no. AAC94-25018.
Dod, R. L.; Rosen, H.; Novakov, T. (1979) Atmospheric aerosol research annual report for 1977-1978.
Berkeley, CA: Lawrence Berkeley Laboratories; document no. 8696.
Durham, J. L.; Wilson, W. E.; Bailey, E. B. (1978) Application of an SO2-denuder for continuous measurement
of sulfur in submicrometric aerosols. Atmos. Environ. 12: 883-886.
Dzubay, T. G.; Mamane, Y. (1989) Use of electron microscopy data in receptor models for PM-10.
Atmos. Environ. 23: 467-476.
Dzubay, T. G.; Nelson, R. O. (1975) Self absorption corrections for X-ray fluorescence analysis of aerosols.
Adv. X-Ray Anal. 18: 619-631.
4-127
-------
Dzubay, T. G.; Stevens, R. K. (1975) Ambient air analysis with dichotomous sampler and X-ray fluorescence
spectrometer. Environ. Sci. Technol. 9: 663-668.
Dzubay, T. G.; Morosoff, N.; Whitaker, G. L.; Yasuda, H. (1981) Evaluation of polymer films as standards for
X-ray fluorescence spectrometers. In: Electron microscopy and X-ray applications to environmental and
occupational health analysis. Ann Arbor, MI: Ann Arbor Science Publishers, Inc.
Dzubay, T. G.; Stevens, R. K.; Balfour, W. D.; Williamson, H. J.; Cooper, J. A.; Core, J. E.;
De Cesar, R. T.; Crutcher, E. R.; Dattner, S. L.; Davis, B. L.; Heisler, S. L.; Shah, J. J.;
Hopke, P. K.; Johnson, D. L. (1984) Intel-laboratory comparison of receptor model results for
Houston aerosol. Atmos. Environ. 18: 1555-1566.
Eatough, D. J. (1995) BOSS, the Brigham Young University Organic Sampling System: determination of
paniculate carbonaceous material using diffision denuder sampling technology. In: Lane, D.,
ed. Gas/phase partition measurements of atmospheric organic compounds. New York, NY: Gordon and
Breach Science Publishers; in press.
Eatough, D. J.; Sedar, B.; Lewis, L.; Hansen, L. D.; Lewis, E. A.; Farber, R. J. (1989) Determination of
semivolatile organic compounds in particles in the Grand Canyon area. Aerosol Sci. Technol.
10: 438-449.
Eatough, D. J.; Wadsworth, A.; Eatough, D. A.; Crawford, J. W.; Hansen, L. D.; Lewis, E. A. (1993)
A multiple-system, multi-channel diffusion denuder sampler for the determination of fine-particulate
organic material in the atmosphere. Atmos. Environ. Part A 27: 1213-1219.
Edwards, J. D. (1980) A comparison of the British smoke shade method and the intergrating plate method
[Ph.D thesis]. Seattle, WA: University of Washington.
Edwards, J. D.; Ogren, J. A.; Weiss, R. E.; Charlson, R. J. (1983) Paniculate air pollutants: a comparison of
British "Smoke" with optical absorption coefficient and elemental carbon concentration. Atmos. Environ.
17:2337-2341.
Eichmann, R.; Neuling, P.; Ketseridis, G.; Hahn, J.; Jaenicke, R.; Junge, C. (1979) n-alkane studies in the
troposphere—I. Gas and paniculate concentrations in North Atlantic air. Atmos. Environ. 13: 587-599.
Eldering, A.; Cass, G. R.; Moon, K. C. (1994) An air monitoring network using continuous particle size
distribution monitors: connecting pollutant properties to visibility via Mie scattering calculations.
Atmos. Environ. 28: 2733-2749.
Eldred, R. A.; Cahill, T. A. (1994) Trends in elemental concentrations of fine particles at remote sites in the
United States of America. Atmos. Environ. 28: 1009-1019.
Eldred, R. A.; Cahill, T. A.; Feeney, P. J. (1993) Comparison of independent measurements of sulfur and
sulfate in the IMPROVE network. Presented at: 86th annual meeting and exhibition of the Air & Waste
Management Association; June; Denver, CO. Pittsburgh, PA: Air & Waste Management Association;
paper no. 93-RA-110.02.
Engelbrecht, D. R.; Cahill, T. A.; Feeney, P. J. (1980) Electrostatic effects on gravimetric analysis of
membrane filters. J. Air Pollut. Control Assoc. 30: 391-392.
Fang, C. P.; McMurry, P. H.; Marple, V. A.; Rubow, K. L. (1991) Effect of flow-induced relative humidity
changes on size cuts for sulfuric acid droplets in the microorifice uniform deposit impactor (MOUDI).
Aerosol Sci. Technol. 14: 266-277.
4-128
-------
Federal Register. (1971) National primary and secondary ambient air quality standards. F. R. (April 30)
36:8186-8201.
Federal Register. (1978) Reference method for the determination of lead in suspended paniculate matter collected
from ambient air. F. R. (October 5) 43: 46258.
Feeney, P.; Cahill, T.; Olivera, J.; Guidara, R. (1984) Gravimetric determination of mass on lightly loaded
membrane filters. J. Air Pollut. Control Assoc. 31: 376-378.
Perm, M. (1986) Concentration measurements and equilibrium studies of ammonium, nitrate and sulphur species
in air and precipitation [Ph.D. thesis]. Goteborg, Sweden: Goteborg University, Department of Inorganic
Chemistry. Available from: Library of Congress, Washington, DC; call no. QC879/.6/.F47/1986.
Fernandez de la Mora, J. (1986) Inertia and interception in the deposition of particles from boundary layers.
Aerosol Sci. Technol. 5: 261-266.
Finlayson-Pitts, B. J.; Pitts, J. N., Jr. (1986) Atmospheric chemistry: fundamentals and experimental techniques.
New York, NY: John Wiley & Sons; pp. 783-1007.
Fitz, D. R. (1990) Reduction of the positive organic artifact on quartz filters. Aerosol. Sci. Technol.
12: 142-148.
Fitz, D.; Chan, M.; Cass, G.; Lawson, D.; Ashbaugh, L. (1989) A multi-component size-classifying aerosol and
gas sampler for ambient air monitoring. Presented at: 82nd annual meeting of the Air & Waste
Management Association; June; Anaheim, CA. Pittsburgh, PA: Air & Waste Management Association;
paper no. 89-140.1.
Flessel, P.; Wang, Y. Y.; Chang, K.-L; Wesolowski, J. J.; Guirguis, G. N.; Kim, I.-S.; Levaggi, D.; Siu, W.
(1991) Seasonal variations and trends in concentrations of filter-collected polycyclic aromatic
hydrocarbons (PAH) and mutagenic activity in the San Francisco Bay Area. J. Air Waste Manage.
Assoc. 41: 276-281.
Foreman, W. T.; Bidleman, T. F. (1990) Semivolatile organic compounds in the ambient air of Denver,
Colorado. Atmos. Environ. Part A 24: 2405-2416.
Forrest, J.; Spandau, D. J.; Tanner, R. L.; Newman, L. (1982) Determination of atmospheric nitrate and nitric
acid employing a diffusion denuder with a filter pack. Atmos. Environ. 16: 1473-1485.
Friedlander, S. K. (1977) Smoke, dust and haze: fundamentals of aerosol behavior. New York, NY: John Wiley
& Sons.
Fung, K. (1990) Paniculate carbon speciation by MnO2 oxidation. Aerosol Sci. Technol. 12: 122-127.
Fung, K. K.; Heisler, S. L.; Price, A.; Nuesca, B. V.; Mueller, P. K. (1979) Comparison of ion
chromatography and automated wet chemical methods for analysis of sulfate and nitrate in ambient
paniculate filter samples. In: Mulik, J. D.; Sawicki, E., eds. Ion chromatographic analysis of
environmental pollutants: volume 2. Ann Arbor, MI: Ann Arbor Science Publishers Inc.; pp. 203-209.
Gagosian, R. B.; Peltzer, E. T.; Zafiriou, O. C. (1981) Atmospheric transport of continentally derived lipids to
the tropical North Pacific. Nature (London) 291: 312-314.
Gebhart, J. (1993) Optical direct-reading techniques: light intensity systems. In: Willeke, K.; Baron, P. A., eds.
Aerosol measurement: principles, techniques, and applications. New York, NY: Van Nostrand Reinhold;
pp. 313-344.
4-129
-------
Gerber, H. E. (1982) Optical techniques for the measurement of light absorption by participates. In: Wolff,
G. T.; Klimisch, R. L., eds. Paniculate carbon: atmospheric life cycle. New York, NY: Plenum Press;
pp. 145-158.
Gordon, R. J. (1974) Solvent selection in extraction of airborne paniculate matter. Atmos. Environ. 8: 189-191.
Griffin, J. J.; Goldberg, E. D. (1979) Morphologies and origin of elemental carbon in the environment. Science
(Washington, DC) 206: 563-565.
Grinshpun, S.; Willeke, K.; Kalatoor, S. (1993) A general equation for aerosol aspiration by thin-walled
sampling probes in calm and moving air. Atmos. Environ. Part A 27: 1459-1470.
Grosjean, D. (1975) Solvent extraction and organic carbon determination in atmospheric paniculate matter: the
organic extraction-organic carbon analyzer (OE-OCA) technique. Anal. Chem. 47: 797-805.
Groves, W. A.; Hahne, R. M. A.; Levine, S. P.; Schork, M. A. (1994) A field comparison of respirable dust
samplers. Am. Ind. Hyg. Assoc. J. 55: 748-755.
Gundel, L. A.; Stevens, R. K.; Daisey, J. M.; Lee, V.; Mahanama, K. R. R. (1992) Annular denuders for
sampling semi-volatile polycyclic aromatic hydrocarbons and other organic species. Presented at:
11th annual meeting of the American Association for Aerosol Research; October; San Francisco, CA.
Gundel, L. A.; Mahanama, K. R. R.; Daisey, J. M. (1994) Fractionation of polar organic extracts of airborne
paniculate matter using cyanopropyl-bonded silica in solid-phase extraction. J. Chromatogr. 629: 75-82.
Hall, D. J.; Mark, D.; Upton, S. L. (1992) A new large wind tunnel for dust and aerosol studies. J. Aerosol Sci.
23(suppl. 1): S591-S594.
Hammerle, R. H.; Pierson, W. R. (1975) Sources and elemental composition of aerosol in Pasadena, Calif.,
by energy-dispersive X-ray fluorescence. Environ. Sci. Technol. 9: 1058-1068.
Hampton, C. V.; Pierson, W. R.; Schuetzle, D.; Harvey, T. M. (1983) Hydrocarbon gases emitted from
vehicles on the road. 2. Determination of emission rates from diesel and spark-ignition vehicles.
Environ. Sci. Technol. 17: 699-708.
Harman, J. N., Chairman. (1989) Inductively coupled plasma emission spectroscopy. In: Lodge, J. P., Jr., ed.
Methods of air sampling and analysis. 3rd ed. Chelsea, MI: Lewis Publishers, Inc.; pp. 89-92.
Harrison, L.; Harrison, H. (1982) A comparison of optical and aerodynamic aerosol sizes: the effects of
inhomogeneous particles. Atmos. Environ. 16: 293-300.
Harrison, R. M.; Kitto, A.-M. N. (1990) Field intercomparison of filter pack and denuder sampling methods for
reactive gaseous and paniculate pollutants. Atmos. Environ. Part A 24: 2633-2640.
Hart, K. M.; Pankow, J. F. (1990) Comparison of n-alkane and PAH concentrations collected on quartz fiber
and Teflon membrane filters in an urban environment. J. Aerosol Sci. 21(suppl. 1): S377-S380.
Hearle, J. W. S.; Sparrow, J. T.; Cross, P. M. (1972) The use of the scanning electron microscope. New York,
NY: Pergamon Press.
Heitbrink, W. A.; Baron, P. A.; Willeke, K. (1991) Coincidence in time-of-flight aerosol spectrometers:
phantom particle creation. Aerosol Sci. Technol. 14: 112-126.
4-130
-------
Henry, R. C.; Lewis, C. W.; Hopke, P. K.; Williamson, H. J. (1984) Review of receptor model fundamentals.
Atmos. Environ. 18: 1507-1515.
Hering, S. V., ed. (1989) Air sampling instruments for evaluation of atmospheric contaminants. 7th ed.
Cincinnati, OH: American Conference of Governmental Industrial Hygienists.
Hering, S. V.; Lawson, D. R.; Allegrini, I.; Febo, A.; Perrino, C.; Possanzini, M.; Sickles, J. E., II;
Anlauf, K. G.; Wiebe, A.; Appel, B. R.; John, W.; Ondo, J.; Wall, S.; Braman, R. S.; Sutton, R.;
Cass, G. R.; Solomon, P. A.; Eatough, D. J.; Eatough, N. L.; Ellis, E. C.; Grosjean, D.; Hicks, B. B.;
Womack, J. D.; Horrocks, J.; Knapp, K. T.; Ellestad, T. G.; Paur, R. J.; Mitchell, W. J.;
Pleasant, M.; Peake, E.; MacLean, A.; Pierson, W. R.; Brachaczek, W.; Schiff, H. I.; Mackay, G. I.;
Spicer, C. W.; Stedman, D. H.; Winer, A. M.; Biermann, H. W.; Tuazon, E. C. (1988) The nitric acid
Shootout: field comparison of measurement methods. Atmos. Environ. 22: 1519-1539.
Hering, S. V.; Appel, B. R.; Cheng, W.; Salaymeh, F.; Cadle, S. H.; Mulawa, P. A.; Cahill, T. A.; Eldred,
R. A.; Surovik, M.; Fitz, D.; Howes, J. E.; Knapp, K. T.; Stockburger, L.; Turpin, B. J.; Huntzicker,
J. J.; Zhang, X.-Q.; McMurry, P. H. (1990) Comparison of sampling methods for carbonaceous aerosols
in ambient air. Aerosol Sci. Technol. 12: 200-213.
Hering, S. V.; Roberts, P. T.; Taylor, C. A. (1994) Particle measurements for the Children's Health Study:
development of a two-week sampler [abstract]. Presented at: Sixth conference of the International Society
for Environmental Epidemiology/fourth conference of the International Society for Exposure Analysis;
September; Research Triangle Park, NC. Chapel Hill, NC: University of North Carolina, School of
Public Health; p. 260.
Hildemann, L. M.; Markowski, G. R.; Cass, G. R. (1991) Chemical composition of emissions from urban
sources of fine organic aerosol. Environ. Sci. Technol. 25: 744-759.
Hillamo, R. E.; Kauppinen, E. I. (1991) On the performance of the Berner low pressure impactor. Aerosol Sci.
Technol. 14: 33-47.
Hinds, W. C. (1982) Aerosol technology. New York, NY: John Wiley and Sons.
Hinds, W. C.; Kraske, G. (1986) Performance of PMS model LAS-X optical particle counter. J. Aerosol Sci.
17: 67-72.
Hirose, K.; Sugimura, Y. (1984) Excess 228Th in the airborne dust: an indicator of continental dust from the east
Asian deserts. Earth Planet. Sci. Lett. 70: 110-114.
Hoffman, A. J.; Purdue, L. J.; Rehme, K. A.; Holland, D. M. (1988) 1987 PM10 sampler intercomparison
study. In: Mathai, C. V.; Stonefield, D. H., eds. PM-10: implementation of standards, an APCA/EPA
international specialty conference; February; San Francisco, CA. Pittsburgh, PA: Air Pollution Control
Association; pp. 138-149. (APCA transactions series TR-13).
Hollander, W. (1990) Proposed performance criteria for samplers of total suspended paniculate matter.
Atmos. Environ. Part A 24: 173-177.
Hollander, W. (1992) Ambient aerosol sampling without pumps. J. Aerosol Sci. 23(suppl. 1): S619-S622.
Hopke, P. K. (1985) Receptor modeling in environmental chemistry. New York, NY: John Wiley & Sons.
Hopke, P. K.; Casuccio, G. S. (1991) Scanning electron microscopy. In: Hopke, P. K., ed. Receptor modeling
for air quality management: v. 7. Amsterdam, The Netherlands: Elsevier; pp. 149-212.
4-131
-------
Hornung, R. W.; Reed, L. D. (1990) Estimation of average concentration in the presence of nondetectable
values. Appl. Occup. Environ. Hyg. 5: 46-51.
Horvath, H.; Kaller, W. (1994) Calibration of integrating nephelometers in the post-halocarbon era.
Atmos. Environ. 28: 1219-1223.
Huntzicker, J. J.; Johnson, R. L.; Shah, J. J.; Gary, R. A. (1982) Analysis of organic and elemental carbon in
ambient aerosols by a thermal-optical method. In: Wolff, G. T.; Klimisch, R. L., eds. Paniculate
carbon - atmospheric life cycle: proceedings of an international symposium; October 1980; Warren, MI.
New York, NY: Plenum Press; pp. 79-88.
Ingham, D. B.; Yan, B. (1994) The effect of a cylindrical backing body on the sampling efficiency of a
cylindrical sampler. J. Aerosol Sci. 25: 535-541.
Ingram, W. T. (1969) Smoke curve calibration. New York, NY: New York University, School of Engineering
and Science; PHS contract no. PH-86-68-66.
Ingram, W. T.; Golden, J. (1973) Smoke curve calibration. J. Air Pollut. Control Assoc. 23: 110-115.
International Standards Organization (ISO). (1983) Air quality: particle size fraction definitions for health-related
sampling. Geneva, Switzerland: International Standards Organization; technical report ISO/TR7708-1983.
International Standards Organization (ISO). (1992) Air quality—particle size fraction definitions for health-related
sampling (draft revision of ISO/TR 7708:1983). Geneva, Switzerland: International Organization for
Standardization; draft international standard no. ISO/DIS 7708.
International Standards Organization (ISO). (1993) Air quality—particle size fraction definitions for health-related
sampling (revision of ISO/TR 7708:1983). Geneva, Switzerland: International Organization for
Standardization; approved international standard no. ISO/DIS 7708.
Jaklevic, J. M.; Loo, B. W.; Goulding, F. S. (1977) Photon-induced X-ray fluorescence analysis using
energy-dispersive detector and dichotomous sampler. In: Dzubay, T. G., ed. X-ray fluorescence analysis
of environmental samples. Ann Arbor, MI: Ann Arbor Science Publishers, Inc.; pp. 3-18.
Jaklevic, J. M.; Gatti, R. C.; Goulding, F. S.; Loo, B. W. (1981) A /3-gauge method applied to aerosol samples.
Environ. Sci. Technol. 15: 680-686.
Janocko, P. B.; Casuccio, G. S.; Dattner, S. L.; Johnson, D. L.; Crutcher, E. R. (1982) The El Paso airshed;
source apportionment using complementary analyses and receptor models. In: A specialty conference on:
receptor models applied to contemporary pollution problems; October; Danvers, MA. Pittsburgh, PA: Air
Pollution Control Association; pp. 249-265. (SP-48).
Japar, S. M.; Szkarlat, A. C.; Gorse, R. A., Jr.; Heyerdahl, E. K.; Johnson, R. L.; Rau, J. A.; Huntzicker,
J. J. (1984) Comparison of solvent extraction and thermal-optical carbon analysis methods: application
to diesel vehicle exhaust aerosol. Environ. Sci. Technol. 18: 231-234.
Javitz, H. S.; Watson, J. G.; Robinson, N. (1988) Performance of the chemical mass balance model with
simulated local-scale aerosols. Atmos. Environ. 22: 2309-2322.
Jensen, P. A.; O'Brien, D. (1993) Industrial hygiene. In: Willeke, K.; Baron, P. A., eds. Aerosol measurement:
principles, techniques, and applications. New York, NY: Van Nostrand Reinhold; pp. 537-559.
John, W.; Wall, S. M. (1983) Aerosol testing techniques for size-selective samplers. J. Aerosol Sci.
14: 713-727.
4-132
-------
John, W.; Wang, H.-C. (1991) Laboratory testing method for PM-10 samplers: lowered effectiveness from
particle loading. Aerosol Sci. Technol. 14: 93-101.
John, W.; Hering, S.; Reischl, G.; Sasaki, G.; Goren, S. (1983) Characteristics of Nuclepore filters with large
pore size—II. filtration properties. Atmos. Environ. 17: 373-382.
John, W.; Wall, S. M.; Ondo, J. L. (1988) A new method for nitric acid and nitrate aerosol measurement using
the dichotomous sampler. Atmos. Environ. 22: 1627-1635.
John, W.; Wall, S. M.; Ondo, J. L.; Winklmayr, W. (1990) Modes in the size distributions of atmospheric
inorganic aerosol. Atmos. Environ. Part A 24: 2349-2359.
John, W.; Winklmayr, W.; Wang, H.-C. (1991) Particle deagglomeration and reentrainment in a PM-10 sampler.
Aerosol Sci. Technol. 14: 165-176.
Johnson, R. L.; Huntzicker, J. J. (1979) Analysis of volatilizable and elemental carbon in ambient aerosols.
In: Novakov, T., ed. Proceedings: carbonaceous particles in the atmosphere; March 1978; Berkeley, CA.
Berkeley, CA: University of California, Lawrence Berkeley Laboratory; pp. 10-13; report no. LBL-9037.
Johnson, D. L.; Mclntyre, B. L.; Fortmann, R.; Stevens, R. K.; Hanna, R. B. (1981a) A chemical element
comparison of individual particle analysis and bulk analysis methods. Scanning Electron Microsc.
1: 469-476.
Johnson, R. L.; Shah, J. J.; Gary, R. A.; Huntzicker, J. J. (1981b) An automated thermal-optical method for the
analysis of carbonaceous aerosol. In: Macias, E. S.; Hopke, P. K., eds. Atmospheric aerosol: source/air
quality relationships; based on a symposium jointly sponsored by the Divisions of Nuclear Chemistry and
Technology at the 180th national meeting of the American Chemical Society; August 1980; Las Vegas,
NV. Washington, DC: American Chemical Society; pp. 223-233. (Comstock, M. J., ed. ACS
symposium series: 167).
Junge, C. E. (1977) Basic considerations about trace constituents in the atmosphere as related to the fate of global
pollutants. In: Suffet, I. H., ed. Fate of pollutants in the air and water environments: part I, mechanism
of interaction between environments and mathematical modeling and the physical fate of pollutants,
papers from the 165th national American Chemical Society meeting; April 1975; Philadelphia, PA. New
York, NY: John Wiley & Sons; pp. 7-25. (Advances in environmental science and technology: v. 8).
Kado, N. Y.; Kozmicky, P. A.; Hsieh, D. P. H.; Gundel, L. A.; Daisey, J. M.; Mahanama, K. R. R.;
Schuetzle, D. (1991) Mutagenic activity of the polar organic matter and its fractions from airborne
particles. Presented at: AAAR meeting; October; Traverse City, MI.
Kalthoff, K.; Crumpler, J. (1990) PM10 methods comparison test report [unpublished material]. Sacramento, CA:
California Air Resources Board, Instrumentation and Operations Support Section.
Kanbour, F. L; Altai, F. A.; Yassin, S.; Harrison, R. M.; Kitto, A.-M. N. (1990) A comparison of smoke
shade and gravimetric determination of suspended paniculate matter in a semi-arid climate (Baghdad,
Iraq). Atmos. Environ. Part A 24: 1297-1301.
Kaupp, H.; Umlauf, G. (1992) Atmospheric gas-particle partitioning of organic compounds: comparison of
sampling methods. Atmos. Environ. Part A 26: 2259-2267.
Keeler, G. J.; Brachaczek, W. W.; Gorse, R. A., Jr.; Japar, S. M.; Pierson, W. R. (1988) Effect of ambient
humidity on dichotomous sampler coarse/fine ratios. Atmos. Environ. 22: 1715-1720.
4-133
-------
Kenny, L. C. (1992) Report of progress towards the development of a performance standard for aerosol sampling
instruments used in occupational hygiene. J. Aerosol Sci. 23: 773-779.
Kenny, L. C.; Liden, G. (1989) The application of performance standards to personal airborne dust samplers.
Ann. Occup. Hyg. 33: 289-300.
Kenny, L. C.; Lide"n, G. (1991) A technique for assessing size-selective dust samplers using the APS and
polydisperse test aerosols. J. Aerosol Sci. 22: 91-100.
Kim, D.; Hopke, P. K. (1988) Classification of individual particles based on computer-controlled scanning
electron microscopy data. Aerosol Sci. Technol. 9: 133-151.
Kim, D. S.; Hopke, P. K.; Massart, D. L.; Kaufman, L.; Casuccio, G. S. (1987) Multivariate analysis of
CCSEM auto emission data. Sci. Total Environ. 59: 141-155.
Klippel, W.; Warneck, P. (1980) The formaldehyde content of the atmospheric aerosol. Atmos. Environ.
14: 809-818.
Konig, J.; Funcke, W.; Balfanz, E.; Grosch, B.; Pott, F. (1980) Testing a high volume air sampler for
quantitative collection of polycyclic aromatic hydrocarbons. Atmos. Environ. 14: 609-613.
Koutrakis, P.; Wolfson, J. M.; Slater, J. L.; Brauer, M.; Spengler, J. D.; Stevens, R. K.; Stone, C. L. (1988)
Evaluation of an annular denuder/filter pack system to collect acidic aerosols and gases. Environ. Sci.
Technol. 22: 1463-1468.
Koutrakis, P.; Wolfson, J. M.; Brauer, M.; Spengler, J. D. (1990) Design of a glass impactor for an annular
denuder/filter pack system. Aerosol Sci. Technol. 12: 607-612.
Kukreja, V. P.; Bove, J. L. (1976) An enrichment method for polycyclic aromatic hydrocarbons (PAH's)
collected on glass fiber filters using hydrofluoric acid. J. Environ. Sci. Health Part All: 517-524.
Lamb, S. I.; Petrowski, C.; Kaplan, I. R.; Simoneit, B. R. T. (1980) Organic compounds in urban atmospheres:
a review of distribution, collection and analysis. J. Air Pollut. Control Assoc. 30: 1098-1115.
Lane, D. A.; Johnson, N. D.; Barton, S. C.; Thomas, G. H. S.; Schroeder, W. H. (1988) Development and
evaluation of a novel gas and particle sampler for semivolatile chlorinated organic compounds in ambient
air. Environ. Sci. Technol. 22: 941-947.
Lane, D. A.; Johnson, N. D.; Hanley, M.-J. J.; Schroeder, W. H.; Ord, D. T. (1992) Gas- and particle-phase
concentrations of a-hexachlorocyclohexane, 7-hexachlorocyclohexane, and hexachlorobenzene in Ontario
air. Environ. Sci. Technol. 26: 126-133.
Larson, T. V.; Yuen, P. F.; Maykut, N. N. (1992) Weekly composite sampling of PM10 for total mass and trace
elemental analysis. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional paniculate
source controls, an A&WMA/EPA international specialty conference, v. I; January; Scottsdale, AZ.
Pittsburgh, PA: Air & Waste Management Association; pp. 39-50. (A&WMA transactions series no. 22).
Laskus, L. (1983) Comparative measurements of suspended particulates using several gravimetric methods and
the British smoke sampler. Sci. Total Environ. 31: 23-40.
Lee, R. J.; Fisher, R. M. (1980) Quantitative characterization of particulates by scanning and high voltage
electron microscopy. Washington, DC: National Bureau of Standards; special publication.
4-134
-------
Lee, R. J.; Kelly, J. F. (1980) Overview of SEM-based automated image analysis. Scanning Electron Microsc.
1: 303-310.
Lee, R. E., Jr.; Caldwell, J. S.; Morgan, G. B. (1972) The evaluation of methods for measuring suspended
particulates in air. Atmos. Environ. 6: 593-622.
Lee, R. J.; Fasiska, E. J.; Janocko, P.; McFarland, D.; Penkala, S. (1979) Electron-beam paniculate analysis.
Ind. Res. Dev. (June): 105-108.
Lee, R. J.; Spitzig, W. A.; Kelly, J. F.; Fisher, R. M. (1981) Quantitative metallography by
computer-controlled scanning electron microscopy. J. Met. 33(3): 20-25.
Lewis, C. W. (1981) On the proportionality of fine mass concentration and extinction coefficient for bimodal size
distributions. Atmos. Environ. 15: 2639-2646.
Li, C. K.; Kamens, R. M. (1993) The use of polycyclic aromatic hydrocarbons as source signatures in receptor
modeling. Atmos. Environ. Part A 27: 523-532.
Liden, G.; Kenny, L. C. (1991) Comparison of measured respirable dust sampler penetration curves with
sampling conventions. Ann. Occup. Hyg. 35: 485-504.
Liden, G.; Kenny, L. C. (1992) The performance of respirable dust samplers: sampler bias, precision and
inaccuracy. Ann. Occup. Hyg. 36: 1-22.
Ligocki, M. P.; Pankow, J. F. (1989) Measurements of the gas/particle distributions of atmospheric organic
compounds. Environ. Sci. Technol. 23: 75-83.
Lin, C.; Baker, M.; Charlson, R. J. (1973) Absorption coefficient of atmospheric aerosol: a method for
measurement. Appl. Opt. 12: 1356-1363.
Lindskog, A.; Brorstrom-Lunden, E.; Sjodin, A. (1985) Transformation of reactive PAH on particles by
exposure to oxidized nitrogen compounds and ozone. Environ. Int. 11: 125-130.
Lioy, P. J.; Wainman, T.; Turner, W.; Marple, V. A. (1988) An intercomparison of the indoor air sampling
impactor and the dichotomous sampler for a 10-/im cut size. JAPCA 38: 668-670.
Lipfert, F. W. (1994) Filter artifacts associated with particulate measurements: recent evidence and effects on
statistical relationships. Atmos. Environ. 28: 3233-3249.
Lippmann, M. (1993) Environmental toxicology and exposure limits for ambient air. Appl. Occup. Environ.
Hyg. 8: 847-858.
Lippmann, M.; Chan, T. L. (1979) Cyclone sampler performance. Staub Reinhalt. Luft 39: 7-11.
Liu, B. Y. H., ed. (1976) Fine particles: aerosol generation, measurement, sampling, and analysis. New York,
NY: Academic Press, Inc.
Liu, B. Y. H.; Pui, D. Y. H. (1981) Aerosol sampling inlets and inhalable particles. Atmos. Environ.
15: 589-600.
Liu, B. Y. H.; Pui, D. Y. H.; Rubow, K. L.; Kuhlmey, G. A. (1978) Progress report: research on air sampling
filter media. Minneapolis, MN: University of Minnesota, Mechanical Engineering Department, Particle
Technology Laboratory; publication no. 366.
4-135
-------
Lodge, J. P., Jr.; Waggoner, A. P.; Klodt, D. T.; Grain, C. N. (1981) Non-health effects of airborne paniculate
matter. Atmos. Environ. 15: 431-482.
Loo, B. W.; Cork, C. P. (1988) Development of high efficiency virtual impactors. Aerosol Sci. Technol.
9: 167-176.
Lundgren, D. A.; Burton, R. M. (1995) Effect of particle size distribution on the cut point between fine and
coarse ambient mass fractions. In: Phalen, R. F.; Bates, D. V., eds. Proceedings of the colloquium on
paniculate air pollution and human mortality and morbidity; January 1994; Irvine, CA. Inhalation
Toxicol. 7: 131-148.
Lundgren, D. A.; Lippmann, M.; Harris, F. S., Jr.; Clark, W. E.; Marlow, W. H.; Durham, M. D., eds.
(1979) Aerosol measurement: [papers from a workshop]; March 1976; Gainesville, FL. Gainesville, FL:
University Presses of Florida.
Lynch, A. J.; McQuaker, N. R.; Brown, D. F. (1980) ICP/AES analysis and the composition of airborne and
soil materials in the vicinity of a lead/zinc smelter complex. J. Air Pollut. Control Assoc. 30: 257-260.
Macher, J.; Chatigny, M. A.; Burge, H. A. (1995) Sampling airborne microorganisms and aeroallergens. In: Air
sampling instruments. 8th ed. Cincinnati, OH: American Conference of Governmental Industrial
Hygienists.
Macias, E. S.; Blumenthal, D. L.; Anderson, J. A.; Cantrell, B. K. (1979) Characterization of visibility-reducing
aerosols in the Southwest. Project VISTTA. Progress report no. 1 (final report). Research Triangle Park,
NC: U.S. Environmental Protection Agency, Environmental Sciences Research Laboratory; EPA report
no. EPA-600/7-79-243. Available from: NTIS, Springfield, VA; PB80-139041.
Mage, D. T. (1995) The relationship between total suspended paniculate matter (TSP) and British Smoke
measurements in London: development of a simple model. J. Air Waste Manage. Assoc. 45: 737-739.
Malissa, H. (1979) Some analytical approaches to the chemical characterization of carbonaceous particulates.
In: Novakov, T., ed. Proceedings: carbonaceous particles in the atmosphere; March 1978; Berkeley, CA.
Berkeley, CA: University of California, Lawrence Berkeley Laboratory; pp. 3-9; report no. LBL-9037.
Malm, W. C.; Sisler, J. F.; Huffman, D.; Eldred, R. A.; Cahill, T. A. (1994) Spatial and seasonal trends in
particle concentration and optical extinction in the United States. J. Geophys. Res. [Atmos.]
99: 1347-1370.
Mamane, Y. (1988) Estimate of municipal refuse incinerator contribution to Philadelphia aerosol—I. source
analysis. Atmos. Environ. 22: 2411-2418.
Mark, D.; Vincent, J. H. (1986) A new personal sampler for airborne total dust in workplaces. Ann. Occup.
Hyg. 30: 89-102.
Mark, D.; Lyons, C. P.; Upton, S. L.; Hall, D. J. (1992) A review of the rationale of current methods for
determining the performance of aerosol samplers. J. Aerosol Sci. 23(suppl. 1): S611-S614.
Markowski, G. R. (1987) On identifying and correcting for reentrainment in cascade impactor measurements.
Aerosol Sci. Technol. 7: 143-159.
Marple, V. A. (1978) Simulation of respirable penetration characteristics by inertial impaction. J. Aerosol Sci.
9: 125-134.
4-136
-------
Marple, V. A.; Olson, B. A. (1995) A high volume PM10/PM2 5/PM1 0 trichotomous sampler. In: Paniculate
matter: health and regulatory issues: proceedings of an international specialty conference; April;
Pittsburgh, PA. Pittsburgh, PA: Air & Waste Management Association; pp. 237-261.
(A&WMA publication VIP-49).
Marple, V. A.; Rubow, K. L. (1976) Aerodynamic particle size calibration of optical particle counters.
J. Aerosol Sci. 7: 425-433.
Marple, V. A.; Rubow, K. L.; Turner, W.; Spengler, J. D. (1987) Low flow rate sharp cut impactors for indoor
air sampling: design and calibration. JAPCA 37: 1303-1307.
Marple, V. A.; Liu, B. Y. H.; Olson, B. A. (1989) Evaluation of a cleanroom concentrating aerosol sampler.
In: Proceedings of the 35th annual meeting of the Institute of Environmental Sciences. Anaheim, CA:
Institute of Environmental Sciences; pp. 360-363.
Marple, V. A.; Liu, B. Y. H.; Burton, R. M. (1990) A high volume dichotomous sampler: design and
evaluation. Presented at: 83rd annual meeting & exhibition of the Air & Waste Management Association;
June; Pittsburgh, PA. Pittsburgh, PA: Air & Waste Management Association; paper no. 90-84.2.
Marple, V. A.; Rubow, K. L.; Behm, S. M. (1991) A microorifice uniform deposit impactor (MOUDI):
description, calibration, and use. Aerosol Sci. Technol. 14: 434-446.
Marple, V. A.; Rubow, K. L.; Olson, B. A. (1993) Inertia!, gravitational, centrifugal, and thermal collection
techniques. In: Willeke, K.; Baron, P. A., eds. Aerosol measurement: principles, techniques, and
applications. New York, NY: Van Nostrand Reinhold; pp. 206-232.
Masia, P.; Di Palo, V.; Possanzini, M. (1994) Uptake of ammonia by nylon filters in filter pack systems.
Atmos. Environ. 28: 365-366.
Massart, D. L.; Kaufman, L. (1983) The interpretation of analytical chemical data by the use of cluster analysis.
New York, NY: John Wiley & Sons (Elving, P. J.; Winefordner, J. D., eds. Chemical analysis: a series
of monographs on analytical chemistry and its applications: v. 65).
Maynard, A. D. (1993) Respirable dust sampler characterisation: efficiency curve reproducibility. J. Aerosol Sci.
24(suppl. 1): S457-S458.
Mazurek, M. A.; Simoneit, B. R. T.; Cass, G. R.; Gray, H. A. (1987) Quantitative high-resolution gas
chromatography and high-resolution gas chromatography/mass spectrometry analyses of carbonaceous fine
aerosol particles. Int. J. Environ. Anal. Chem. 29: 119-139.
Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1989) Interpretation of high-resolution gas
chromatography/ mass spectrometry data aquired from atmospheric organic aerosol samples. Aerosol Sci.
Technol. 10: 408-420.
Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1991) Biological input to visibility-reducing aerosol particles
in the remote arid southwestern United States. Environ. Sci. Technol. 25: 684-694.
McDow, S. R.; Huntzicker, J. J. (1990) Vapor adsorption artifact in the sampling of organic aerosol: face
velocity effects. Atmos. Environ. Part A 24: 2563-2571.
McDow, S. R.; Huntzicker, J. J. (1993) Vapor adsorption artifact in the sampling of organic aerosol.
In: Winegar, E. D.; Keith, L. H., eds. Sampling and analysis of airborne pollutants. Boca Raton, FL:
Lewis Publishers, Inc.; pp. 191-208.
4-137
-------
McFarland, A. R.; Ortiz, C. A. (1979) Aerosol characterization of ambient paniculate samplers used in
environmental monitoring studies. College Station, TX: Texas A&M Research Foundation;
contract no. 68-02-2720.
McFarland, A. R.; Ortiz, C. A. (1984) Characterization of Sierra-Andersen model 321a um size selective inlet
for hi-vol samplers. College Station, TX: Texas A&M University, Department of Civil Engineering, Air
Quality Laboratory; report no. 4716/01/02/847ARM.
McFarland, A. R.; Wedding, J. B.; Cermak, J. E. (1977) Wind tunnel evaluation of a modified Andersen
impactor and an all weather sampler inlet. Atmos. Environ. 11: 535-539.
McFarland, A. R.; Ortiz, C. A.; Rodes, C. E. (1979) Characteristics of aerosol samplers used in ambient air
monitoring. Presented at: 86th national meeting of the American Institute of Chemical Engineers; April;
Houston, TX. College Station, TX: Texas A&M University.
McFarland, A. R.; Ortiz, C. A.; Rodes, C. E. (1982) Wind tunnel evaluation of the British smoke shade
sampler. Atmos. Environ. 16: 325-328.
McFarland, A. R.; Ortiz, C. A.; Bertch, R. W., Jr. (1984) A 10 /xm cutpoint size selective inlet for hi-vol
samplers. J. Air Pollut. Control Assoc. 34: 544-547.
Mclntyre, B. L.; Johnson, D. L. (1982) A particle class balance receptor model for aerosol apportionment in
Syracuse, NY. In: Dattner, S. L.; Hopke, P. K., eds. A specialty conference on receptor models applied
to contemporary pollution problems; October; Danvers, MA. Pittsburgh, PA: Air Pollution Control
Association. (SP-48).
McMurry, P. H.; Stolzenburg, M. R. (1989) On the sensitivity of particle size to relative humidity for
Los Angeles aerosols. Atmos. Environ. 23: 497-507.
McMurry, P. H.; Takano, H.; Anderson, G. R. (1983) Study of the ammonia (gas)-sulfuric acid (aerosol)
reaction rate. Environ. Sci. Technol. 17: 347-352.
Merrifield, T. (1989) The measurement of PM-10 by /8-absorption. Presented at: 82nd annual meeting and
exhibition of the Air & Waste Management Association; June; Anaheim, CA. Pittsburgh, PA: Air &
Waste Management Association; paper no. 89-66A.2.
Meyer, M. B.; Lijek, J.; Ono, D. (1992) Continuous PM10 measurements in a woodsmoke environment.
In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional paniculate source controls,
an A&WMA/EPA international specialty conference, v. I; January; Scottsdale, AZ. Pittsburgh, PA:
Air & Waste Management Association; pp. 24-38. (A&WMA transactions series no. 22).
Meyer, M. B.; Rupprecht, E.; Patashnick, H. (1995) Considerations for the sampling and measurement of
ambient paniculate matter. In: Paniculate matter: health and regulatory issues: proceedings of an
international specialty conference; April; Pittsburgh, PA. Pittsburgh, PA: Air & Waste Management
Association; pp. 204-210. (A&WMA publication VIP-49).
Meyer-Arendt, J. R. (1972) Introduction to classical and modern optics. Englewood Cliffs, NJ: Prentice Hall,
Inc.
Miller, F. J.; Gardner, D. E.; Graham, J. A.; Lee, R. E., Jr.; Wilson, W. E.; Bachmann, J. D. (1979) Size
considerations for establishing a standard for inhalable particles. J. Air Pollut. Control Assoc.
29: 610-615.
4-138
-------
Mueller, P. K.; Mosley, R. W.; Pierce, L. B. (1971) Carbonate and noncarbonate carbon in atmospheric
particles = carbon, carbonate et non carbonate, dans les particules atmospherique. In: Englund, H. M.;
Beery, W. T., eds. Proceedings of the second international clean air congress; December 1970;
Washington, DC. New York, NY: Academic Press, Inc.; pp. 532-539.
Muir, D.; Laxen, D. P. H. (1995) Black smoke as a surrogate for PM10 in health studies? Atmos. Environ.
29: 959-962.
Mulik, J.; Puckett, R.; Williams, D.; Sawicki, E. (1976) Ion chromatographic analysis of sulfate and nitrate in
ambient aerosols. Anal. Lett. 9: 653-663.
Mylonas, D. T.; Allen, D. T.; Ehrman, S. H.; Pratsinis, S. E. (1991) The sources and size distributions of
organonitrates in Los Angeles aerosol. Atmos. Environ. Part A 25: 2855-2861.
Nevalainen, A.; Pastuszka, J.; Liebhaber, F.; Willeke, K. (1992) Performance of bioaerosol samplers: collection
characteristics and sampler design considerations. Atmos. Environ. Part A 26: 531-540.
Nevalainen, A.; Willeke, K.; Liebhaber, F.; Pastuszka, J.; Burge, H.; Henningson, E. (1993) Bioaerosol
sampling. In: Willeke, K.; Baron, P. A., eds. Aerosol measurement: principles, techniques, and
applications. New York, NY: Van Nostrand Reinhold; pp. 471-492.
Novakov, T. (1982) Soot in the atmosphere. In: Wolff, G. T.; Klimisch, R. L., eds. Paniculate carbon:
atmospheric life cycle. New York, NY: Plenum Press; pp. 19-41.
Novick, V. J.; Alvarez, J. L. (1987) Design of a multistage virtual impactor. Aerosol Sci. Technol. 6: 63-70.
Ogden, T. L. (1992) Inhalable and respirable dust - moving from aerosol science to legislation. J. Aerosol Sci.
23(suppl. 1): S445-S448.
Ogden, T. L.; Birkett, J. L. (1977) The human head as a dust sampler. In: Walton, W. H., ed. Inhaled particles
IV, part 1: proceedings of an international symposium; September 1975; Edinburgh, Scotland. Oxford,
United Kingdom: Pergamon Press; pp. 93-105.
Olmez, I. (1989) Trace element signatures in groundwater pollution. In: Watson, J. G., ed. Receptor models in
air resources management: an international specialty conference; February 1988; San Francisco, CA.
Pittsburgh, PA: Air & Waste Management Association; pp. 3-11. (APCA transactions series: no. 14).
Olmez, I.; Harman, J. N. (1989) Instrumental neutron activation analysis of atmospheric paniculate matter.
In: Lodge, J. P., Jr., ed. Methods of air sampling and analysis. 3rd ed. Chelsea, MI: Lewis Publishers,
Inc.; pp. 143-150.
Ondov, J. M.; Divita, F., Jr. (1993) Size spectra for trace elements in urban aerosol particles by instrumental
neutron activation analysis. J. Radioanal. Nucl. Chem. 167: 247-258.
Owen, M. K.; Ensor, D. S.; Sparks, L. E. (1992) Airborne particle sizes and sources found in indoor air.
Atmos. Environ. Part A 26: 2149-2162.
Ozkaynak, H.; Xue, J.; Weker, R.; Butler, D.; Spengler, J. (1993) The particle TEAM (PTEAM) study:
analysis of the data, volume III [draft final report]. Research Triangle Park, NC: U.S. Environmental
Protection Agency; EPA contract no. 68-02-4544.
Palen, E. J.; Allen, D. T.; Pandis, S. N.; Paulson, S. E.; Seinfeld, J. H.; Flagan, R. C. (1992) Fourier
transform infrared analysis of aerosol formed in the photo-oxidation of isoprene and /3-pinene.
Atmos. Environ. Part A 26: 1239-1251.
4-139
-------
Palen, E. J.; Allen, D. T.; Pandis, S. N.; Paulson, S.; Seinfeld, J. H.; Flagan, R. C. (1993) Fourier Transform
Infrared analysis of aerosol formed in the photo-oxidation of 1-octene. Atmos. Environ. Part A
27: 1471-1477.
Pankow, J. F. (1987) Review and comparative analysis of the theories on partitioning between the gas and
aerosol paniculate phases in the atmosphere. Atmos. Environ. 21: 2275-2283.
Pankow, J. F. (1992) Application of common y-intercept regression parameters for log Kp vs l/T for predicting
gas-particle partitioning in the urban environment. Atmos. Environ. Part A 26: 2489-2497.
Parmar, S. S.; Grosjean, D. (1990) Laboratory tests of KI and alkaline annular denuders. Atmos. Environ. Part
A 24: 2695-2698.
Pashel, G.; Egner, D. (1981) A comparison of ambient suspended paniculate matter concentrations as measured
by the British smoke sampler and the high volume sampler at 16 sites in the United States.
Atmos. Environ. 15: 919-927.
Patashnick, H.; Rupprecht, E. G. (1990) Continuous PM-10 measurements using the tapered element oscillating
microbalance. Presented at: 83rd annual meeting and exhibition of the Air & Waste Management
Association; June; Pittsburgh, PA. Pittsburgh, PA: Air & Waste Management Association;
paper no. 90-84.1.
Patashnick, H.; Rupprecht, E. G. (1991) Continuous PM-10 measurements using the tapered element oscillating
microbalance. J. Air Waste Manage. Assoc. 41: 1079-1083.
Pellizzari, E.; Lioy, P.; Quackenboss, J.; Whitmore, R.; Clayton, A.; Freeman, N.; Waldman, J.; Thomas, K.;
Rodes, C.; Wilcosky, T. (1995) Population-based exposure measurements in EPA Region 5: Phase I field
study in support of the National Human Exposure Assessment Survey. J. Exposure Anal. Environ.
Epidemiol. 5: 327-358.
Phillips, B.; Lumpkin, T.; Pleasant, M. (1994) Philadelphia diesel paniculate matter monitoring study.
In: Measurement of toxic and related air pollutants: proceedings of the U.S. EPA/A&WMA international
symposium; May; Durham, NC. Pittsburgh, PA: Air Waste Manage. Assoc.; pp. 640-645. (A&WMA
specialty conference VIP-39).
Pierson, W. R.; Hammerle, R. H.; Brachaczek, W. W. (1976) Sulfate formed by interaction of sulfur dioxide
with filters and aerosol deposits. Anal. Chem. 48: 1808-1811.
Pierson, W. R.; Brachaczek, W. W.; Japar, S. M.; Cass, G. R.; Solomon, P. A. (1988) Dry deposition and dew
chemistry in Claremont, California, during the 1985 Nitrogen Species Methods Comparison Study.
Atmos. Environ. 22: 1657-1663.
Pierson, W. R.; Brachaczek, W. W.; Gorse, R. A., Jr.; Japar, S. M.; Norbeck, J. M.; Keeler, G. J. (1989)
Atmospheric acidity measurements on Allegheny Mountain and the origins of ambient acidity in the
northeastern United States. Atmos. Environ. 23: 431-459.
Possanzini, M.; Febo, A.; Liberti, A. (1983) New design of a high-performance denuder for the sampling of
atmospheric pollutants. Atmos. Environ. 17: 2605-2610.
Pupp, C.; Lao, R. C.; Murray, J. J.; Pottie, R. F. (1974) Equilibrium vapour concentrations of some polycyclic
aromatic hydrocarbons, As4O6 and SeO2 and the collection efficiencies of these air pollutants.
Atmos. Environ. 8: 915-925.
4-140
-------
Purdue, L. J.; Rodes, C. E.; Rehme, K. A.; Holland, D. M.; Bond, A. E. (1986) Intercomparison of
high-volume PM10 samplers at a site with high paniculate concentrations. J. Air Pollut. Control Assoc.
36: 917-920.
Qian, Y.; Willeke, K.; Ulevicius, V.; Grinshpun, S. A.; Donnelly, J. (1995) Dynamic size spectrometiy of
airborne microorganisms: laboratory evaluation and calibration. Atmos. Environ. 29: 1123-1129.
Raabe, O. G.; Braaten, D. A.; Axelbaum, R. L.; league, S. V.; Cahill, T. A. (1988) Calibration studies of the
drum impactor. J. Aerosol Sci. 19: 183-195.
Rader, D. J.; O'Hern, T. J. (1993) Optical direct-reading techniques: in situ sensing. In: Willeke, K.;
Baron, P. A., eds. Aerosol measurement: principles, techniques, and applications. New York, NY: Van
Nostrand Reinhold; pp. 345-380.
Ramdahl, T.; Zielinska, B.; Arey, J.; Atkinson, R.; Winer, A. M.; Pitts, J. N., Jr. (1986) Ubiquitous
occurrence of 2-nitrofluoranthene and 2-nitropyrene in air. Nature (London) 321: 425-427.
Ranade, M. B. (Arun); Woods, M. C.; Chen, F.-L.; Purdue, L. J.; Rehme, K. A. (1990) Wind tunnel
evaluation of PM10 samplers. Aerosol Sci. Technol. 13: 54-71.
Regan, G. F.; Goranson, S. K.; Larson, L. L. (1979) Use of tape samplers as fine paniculate monitors. J. Air
Pollut. Control Assoc. 29: 1158-1160.
Reist, P. C. (1984) Introduction to aerosol science. New York, NY: Macmillan Publishing Company.
Rodes, C. E.; Holland, D. M.; Purdue, L. J.; Rehme, K. A. (1985) A field comparison of PM10 inlets at four
locations. J. Air Pollut. Control Assoc. 35: 345-354.
Rodes, C. E.; Kamens, R. M.; Wiener, R. W. (1991) The significance and characteristics of the personal
activity cloud on exposure assessment measurements for indoor contaminants. Indoor Air 2: 123-145.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1993a) Sources of fine
organic aerosol. 2. Noncatalyst and catalyst-equipped automobiles and heavy-duty diesel trucks. Environ.
Sci. Technol. 27:636-651.
Rogge, W. F.; Mazurek, M. A.; Hildemann, L. M.; Cass, G. R.; Simoneit, B. R. T. (1993b) Quantification of
urban organic aerosols at a molecular level: identification, abundance and seasonal variation. Atmos.
Environ. Part A 27: 1309-1330.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1993c) Sources of fine
organic aerosol. 3. Road dust, tire debris, and organometallic brake lining dust: roads as sources and
sinks. Environ. Sci. Technol. 27: 1892-1904.
Rondia, D. (1965) Sur la volatilite des hydrocarbures polycycliques [Volatility of polycyclic hydrocarbons].
Int. J. Air Water Pollut. 9: 113-121.
Rood, M. J.; Covert, D. S.; Larson, T. V. (1987) Hygroscopic properties of atmospheric aerosol in Riverside,
California. Tellus Ser. B 39B: 383-397.
Rubow, K. L.; Marple, V. A.; Olin, J.; McCawley, M.A. (1987) A personal cascade impactor: design,
evaluation and calibration. Am. Ind. Hyg. Assoc. J. 48: 532-538.
Rupprecht, E.; Meyer, M.; Patashnick, H. (1992) The tapered element oscillating microbalance as a tool for
measuring ambient paniculate concentrations in real time. J. Aerosol Sci. 23(suppl. 1): S635-S638.
4-141
-------
Saltzman, B. E. (1984) Generalized performance characteristics of miniature cyclones for atmospheric paniculate
sampling. Am. Ind. Hyg. Assoc. J. 45: 671-680.
Sass-Kortsak, A. M.; O'Brien, C. R.; Bozek, P. R.; Purdham, J. T. (1993) Comparison of the 10-mm nylon
cyclone, horizontal elutriator, and aluminum cyclone for silica and wood dust measurements. Appl.
Occup. Environ. Hyg. 8: 31-37.
Saucy, D. A.; Anderson, J. R.; Buseck, P. R. (1987) Cluster analysis applied to atmospheric aerosol samples
from the Norwegian Arctic. Atmos. Environ. 21: 1649-1657.
Schamber, F. H. (1993) SEM for nontraditional users. Am. Lab. 25(9): 34, 36-38.
Schipper, L. B., Ill; Chow, J. C.; Frazier, C. A. (1993) Paniculate air toxic emission estimation of the PMi0
fraction in natural aggregate processing facilities. Presented at: 86th annual meeting and exhibition of the
Air & Waste Management Association; June; Denver, CO. Pittsburgh, PA: Air Waste Manage. Assoc.;
paper no. 93-MP-6.03.
Schuetzle, D.; Lewtas, J. (1986) Bioassay-directed chemical analysis in environmental research. Anal. Chem.
58: 1060A-1076A.
Schwartz, G. P.; Daisey, J. M.; Lioy, P. J. (1981) Effect of sampling duration on the concentration of
particulate organics collected on glass fiber filters. Am. Ind. Hyg. Assoc. J. 42: 258-263.
Shaw, R. W., Jr.; Stevens, R. K.; Bowermaster, J.; Tesch, J. W.; Tew, E. (1982) Measurements of atmospheric
nitrate and nitric acid: the denuder difference experiment. Atmos. Environ. 16: 845-853.
Shimp, D. R. (1988) Field comparison of beta attenuation PM-10 sampler and high-volume PM-10 sampler.
In: Mathai, C. V.; Stonefield, D. H., eds. PM10: implementation of standards, an APCA/EPA
international specialty conference; February; San Francisco, CA. Pittsburgh, PA: Air Pollution Control
Association; pp. 171-178. (APCA transactions series TR-13).
Sickles, J. E., II; Hodson, L. L. (1989) Fate of nitrous acid on selected collection surfaces. Atmos. Environ.
23: 2321-2324.
Sickles, J. E., II; Grohse, P. M.; Hodson, L. L.; Salmons, C. A.; Cox, K. W.; Turner, A. R.; Estes, E. D.
(1990) Development of a method for the sampling and analysis of sulfur dioxide and nitrogen dioxide
from ambient air. Anal. Chem. 62: 338-346.
Sides, J. O.; Saiger, H. F. (1976) Effects of prolonged static exposures of filters to ambient air on high volume
sampling results. Topeka, KS: Department of Health and Environment.
Simoneit, B. R. T. (1984) Organic matter of the troposphere—HI. characterization and sources of petroleum and
pyrogenic residues in aerosols over the western United States. Atmos. Environ. 18: 51-67.
Simoneit, B. R. T.; Sheng, G.; Chen, X.; Fu, J.; Zhang, J.; Xu, Y. (1991) Molecular marker study of
extractable organic matter in aerosols from urban areas of China. Atmos. Environ. Part A
25: 2111-2129.
Sioutas, C.; Koutrakis, P.; Olson, B. A. (1994) Development and evaluation of a low cutpoint virtual impactor.
Aerosol Sci. Technol. 21: 223-235.
Sloane, C. S. (1986) Effect of composition on aerosol light scattering efficiencies. Atmos. Environ.
20: 1025-1037.
4-142
-------
Small, H.; Stevens, T. S.; Bauman, W. C. (1975) Novel ion exchange chromatographic method using
conductimetric detection. Anal. Chem. 47: 1801-1809.
Smith, R. G.; Bryan, R. J.; Feldstein, M.; Locke, D. C.; Warner, P. O. (1975) Tentative method for the
determination of carbon monoxide (detector tube method). Health Lab. Sci. 12: 171-172.
Soderholm, S. C. (1989) Proposed international conventions for particle size-selective sampling. Ann. Occup.
Hyg. 33: 301-320.
Solomon, P. A.; Larson, S. M.; Fall, T.; Cass, G. R. (1988) Basinwide nitric acid and related species
concentrations observed during the Claremont Nitrogen Species Comparison Study. Atmos. Environ.
22: 1587-1594.
Spagnolo, G. S. (1989) Automatic instrument for aerosol samples using the beta-particle attenuation. J. Aerosol
Sci. 20: 19-27.
Spagnolo, G. S.; Paoletti, D. (1994) Automatic system for three fractions sampling of aerosol particles in
outdoor environments. J. Air Waste Manage. Assoc. 44: 702-706.
Spengler, J.; Schwab, M.; Ryan, P. B.; Colome, S.; Wilson, A. L.; Billick, I.; Becker, E. (1994) Personal
exposure to nitrogen dioxide in the Los Angeles Basin. J. Air Waste Manage. Assoc. 44: 39-47.
Spicer, C. W.; Schumacher, P. M. (1979) Paniculate nitrate: laboratory and field studies of major sampling
interferences. Atmos. Environ. 13: 543-552.
Stevens, R. K.; Pace, T. G. (1984) Overview of the mathematical and empirical receptor models workshop
(Quail Roost II). Atmos. Environ. 18: 1499-1506.
Stevens, R. K.; Dzubay, T. G. ; Russwurm, G.; Rickel, D. (1978) Sampling and analysis of atmospheric sulfates
and related species. Atmos. Environ. 12: 55-68.
Stevens, R. K.; McClenny, W. A.; Dzubay, T. G.; Mason, M. A.; Courtney, W. J. (1982) Analytical methods
to measure the carbonaceous content of aerosols. In: Wolff, G. T.; Klimisch, R. L., eds. Paniculate
carbon: atmospheric life cycle. New York, NY: Plenum Publishing Corp.; pp. 111-129.
Stevens, R.; Pinto, J.; Mamane, Y.; Ondov, J.; Abdulraheem, M.; Al-Majed, N.; Sadek, M.; Cofer, W.;
Ellenson, W.; Kellogg, R. (1993) Chemical and physical properties of emissions from Kuwaiti oil fires.
Water Sci. Technol. 27: 223-233.
Stott, W. R.; Chatfield, E. J. (1979) A precision SEM image analysis system with full feature EDXA
characterization. Scanning Electron Microsc. 2: 53-60.
Sweitzer, T. A. (1985) A field evaluation of two PM10 inlets in an industrialized area of Illinois. J. Air Pollut.
Control Assoc. 35: 744-746.
Symanski, E.; Rappaport, S. M. (1994) An investigation of the dependence of exposure variability on the interval
between measurements. Ann. Occup. Hyg. 38: 361-372.
Tang, H.; Lewis, E. A.; Eatough, D. J.; Burton, R. M.; Farber, R. J. (1994) Determination of the particle size
distribution and chemical composition of semi-volatile organic compounds in atmospheric fine particles
with a diffusion denuder sampling system. Atmos. Environ. 28: 939-947.
4-143
-------
league, S. V.; Raabe, O. G.; Eldred, R. A. (1992) A bench top wind tunnel for testing PM10 sampling inlets.
In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional paniculate source controls, an
A&WMA/EPA international specialty conference, v. I; January; Scottsdale, AZ. Pittsburgh, PA: Air &
Waste Management Association; pp. 2-12. (A&WMA transactions series no. 22).
Tejada, S. B.; Zweidinger, R. B.; Sigsby, J. E., Jr.; Bradow, R. L. (1978) Modification of an ion
chromatograph for automated routine analysis: applications to mobile source emissions. In: Sawicki, E.;
Mulik, J. D.; Wittgenstein, E., eds. Ion chromatographic analysis of environmental pollutants. Ann
Arbor, MI: Ann Arbor Science Publishers, Inc.; pp. 111-124.
Thanukos, L. C.; Miller, T.; Mathai, C. V.; Reinholt, D.; Bennett, J. (1992) Intercomparison of PM10 samplers
and source apportionment of ambient PM10 concentrations at Rillito, Arizona. In: Chow, J. C.; Ono,
D. M., eds. PMi0 standards and nontraditional paniculate source controls, an A&WMA/EPA
international specialty conference, v. I; January; Scottsdale, AZ. Pittsburgh, PA: Air & Waste
Management Association; pp. 244-261. (A&WMA transactions series no. 22).
Thomas, A.; Gebhart, J.; Miiller, J. (1993) Effect of relative humidity on light scattering of atmospheric
aerosols. J. Aerosol Sci. 24(suppl. 1): S117-S118.
Torok, S. B.; Van Grieken, R. E. (1994) X-ray spectrometry. Anal. Chem. 66: 186R-206R.
Tsai, P.-J.; Vincent, J. H. (1993) Impaction model for the aspiration efficiencies of aerosol samplers at large
angles with respect to the wind. J. Aerosol Sci. 24: 919-928.
Tufto, P. A.; Willeke, K. (1982) Dynamic evaluation of aerosol sampling inlets. Environ. Sci. Technol.
16: 607-609.
Turner, J. R.; Hering, S. V. (1987) Greased and oiled substrates as bounce-free impaction surfaces. J. Aerosol
Sci. 18: 215-224.
Turpin, B. J.; Huang, P.-F.; Roos, A.; McMurry, P. H. (1993a) Elemental analysis of single atmospheric
particles influencing visibility at the Grand Canyon. In: Bailey, G. W.; Rieder, C. L., eds. Proceedings
of the 51st annual meeting of the Microscopy Society of America; August; Cincinnati, OH. San
Francisco, CA: San Francisco Press, Inc.; pp. 1124-1125.
Turpin, B. J.; Liu, S.-P.; Podolske, K. S.; Gomes, M. S. P.; Eisenreich, S. J.; McMurry, P. H. (1993b)
Design and evaluation of a novel diffusion separator for measuring gas/particle distributions of
semivolatile organic compounds. Environ. Sci. Technol. 27: 2441-2449.
Turpin, B. J.; Huntzicker, J. J.; Hering, S. V. (1994) Investigation of organic aerosol sampling artifacts in the
Los Angeles basin. Atmos. Environ. 28: 3061-3071.
Turpin, B. J.; Huang, P.-F.; McMurry, P. H.; Hawkins, D. M.; Hering, S. V.; Casuccio, G. S. (1996)
Description of a cluster analysis technique to characterize single particle compositions and application to
Grand Canyon aerosols. Aerosol Sci. Technol.: submitted.
U.S. Environmental Protection Agency. (1976) Laboratory procedures for the analysis of ammonia in particulates
collected by means of HI-VOL samplers-Technicon autoanalyzer II procedures. Research Triangle Park,
NC: Analytical Chemistry Branch.
U.S. Environmental Protection Agency. (1982) Air quality criteria for paniculate matter and sulfur oxides: v. II.
Research Triangle Park, NC: Office of Health and Environmental Assessment, Environmental Criteria
and Assessment Office; report no. EPA-600/8-82-029bF. Available from: NTIS, Springfield, VA;
PB84-120419.
4-144
-------
U.S. Environmental Protection Agency. (1987) PM10 SIP development guideline. Research Triangle Park, NC:
U.S. Environmental Protection Agency, Office of Air Quality Planning and Standards; EPA report no.
EPA-450/2-86-001. Available from: NTIS, Springfield, VA; PB87-206488.
U.S. Environmental Protection Agency. (1992) Determination of the strong acidity of atmospheric fine-particles
(<2.5 ^m) using annular denuder technology. Washington, DC: Atmospheric Research and Exposure
Assessment Laboratory; EPA report no. EPA/600/R-93/037.
U.S. Environmental Protection Agency. (1994) Guidelines for PM-10 sampling and analysis applicable to
receptor modeling. Research Triangle Park, NC: Office of Air Quality Planning and Standards; report
no. EPA/452/R-94/009. Available from: NTIS, Springfield, VA; PB94-177441.
Upton, S. L.; Mark, D.; Hall, D. J. (1992) Improvements to the design and performance of an ambient inhalable
aerosol sampler. J. Aerosol Sci. 23(suppl. 1): S595-S598.
Van Borm, W. A.; Adams, F. C. (1988) Cluster analysis of electron microprobe analysis data of individual
particles for source apportionment of air paniculate matter. Atmos. Environ. 22: 2297-2307.
Van Borm, W. A.; Adams, F. C.; Maenhaut, W. (1989) Characterization of individual particles in the Antwerp
aerosol. Atmos. Environ. 23: 1139-1151.
Van der Meulen, A. (1986) The relationship between PM10 and thoracic particle sampling. J. Air Pollut. Control
Assoc. 36: 383-387.
Vanderpool, R. W.; Lundgren, D. A.; Marple, V. A.; Rubow, K. L. (1987) Cocalibration of four large-particle
impactors. Aerosol Sci. Technol. 7: 177-185.
Van Vaeck, L.; Van Cauwenberghe, K.; Janssens, J. (1984) The gas-particle distribution of organic aerosol
constituents: measurements of the volatilisation artefact in hi-vol cascade impactor sampling. Atmos.
Environ. 18: 417-430.
Vaughan, N. P. (1989) The Andersen impactor: calibration, wall losses and numerical simulation. J. Aerosol Sci.
20: 67-90.
Vincent, J. H.; Mark, D. (1981) The basis of dust sampling in occupational hygiene: a critical review. Ann.
Occup. Hyg. 24: 375-390.
Vincent, J. H.; Mark, D. (1982) Applications of blunt sampler theory to the definition and measurement of
inhalable dust. Ann. Occup. Hyg. 26: 3-19.
Vossler, T. L.; Stevens, R. K.; Paur, R. J.; Baumgardner, R. E.; Bell, J. P. (1988) Evaluation of improved
inlets and annular denuder systems to measure inorganic air pollutants. Atmos. Environ. 22: 1729-1736.
WESTAR Council. (1995) Comparative data review of manual and continuous PM10 sampling methods. Seattle,
WA: U.S. Environmental Protection Agency, Region 10; July.
Waggoner, A. P.; Weiss, R. E. (1980) Comparison of fine particle mass concentration and light scattering
extinction in ambient aerosol. Atmos. Environ. 14: 623-626.
Wake, D. (1989) Anomalous effects in filter penetration measurements using the aerodynamic particle sizer
(APS 3300). J. Aerosol Sci. 20: 13-17.
Wall, S. M.; John, W.; Ondo, J. L. (1988) Measurement of aerosol size distributions for nitrate and major ionic
species. Atmos. Environ. 22: 1649-1656.
4-145
-------
Wallace, L. A.; Duan, N.; Ziegenfus, R. (1994) Can long-term exposure distributions be predicted from
short-term measurements? Risk Anal. 14: 75-85.
Waller, R. E. (1963) Acid droplets in town air. Int. J. Air Water Pollut. 7: 773-778.
Wang, H.-C.; John, W. (1988) Characteristics of the Bemer impactor for sampling inorganic ions. Aerosol Sci.
Technol. 8: 157-172.
Wang, H.-C.; John, W. (1989) A simple iteration procedure to correct for the density effect in the aerodynamic
particle sizer. Aerosol Sci. Technol. 10: 501-505.
Watson, J. G.; Chow, J. C.; Shah, J. J.; Pace, T. G. (1983) The effect of sampling inlets on the PM-10 and
PM-15 to TSP concentration ratios. J. Air Pollut. Control Assoc. 33: 114-119.
Watson, J. G.; Bowen, J. L.; Chow, J. C.; Rogers, C. F.; Ruby, M. G.; Rood, M. J.; Egami, R. T. (1989a)
High-volume measurement of size classified paniculate matter. In: Lodge, J. P., Jr., ed. Methods of air
sampling and analysis. 3rd ed. Chelsea, MI: Lewis Publishers, Inc.; pp. 427-439.
Watson, J. G.; Chow, J. C.; Mathai, C. V. (1989b) Receptor models in air resources management: a summary
of the APCA international specialty conference. JAPCA 39: 419-426.
Watson, J. G.; Robinson, N. F.; Chow, J. C.; Henry, R. C.; Kim, B. M.; Pace, T. G.; Meyer, E. L.; Nguyen,
Q. (1990) The USEPA/DRI chemical mass balance receptor model, CMB 7.0. Environ. Software
5: 38-49.
Wedding, J. B. (1980) Ambient aerosol sampling: history, present thinking and a proposed inlet for inhalable
particulate matter. Presented at: 73rd annual meeting of the Air Pollution Control Association; June;
Montreal, PQ, Canada. Pittsburgh, PA: Air Pollution Control Association; paper no. 80-38.1.
Wedding, J. B. (1985) Errors in sampling ambient concentrations with instruments employing setpoint
temperature compensated mass flow transducers. Atmos. Environ. 19: 1219-1222.
Wedding, J. B.; Carney, T. C. (1983) A quantitative technique for determining the impact of non-ideal ambient
sampler inlets on the collected mass. Atmos. Environ. 17: 873-882.
Wedding, J. B.; Weigand, M. A. (1983) Preliminary communication: a thoracic particle inlet (d50 = 6 /tm,
do = 1 /xm) for the high-volume sampler. Atoms. Environ. 17: 1203-1204.
Wedding, J. B.; Weigand, M. A. (1993) An automatic particle sampler with beta gauging. J. Air Waste Manage.
Assoc. 43: 475-479.
Wedding, J. B.; Weigand, M. A.; Carney, T. C. (1982) A 10 ^m cutpoint inlet for the dichotomous sampler.
Environ. Sci. Technol. 16: 602-606.
Wedding, J. B.; Weigand, M. A.; Lodge, J. P., Jr. (1983) A thoracic particle inlet (d^ = 6 /mi, d0 = 10 /an)
for the high-volume sampler. Atmos. Environ. 17: 1203-1204.
Weiss, R. E.; Waggoner, A. P.; Charlson, R. J.; Thorsell, D. L.; Hall, J. S.; Riley, L. A. (1979) Studies of the
optical, physical & chemical properties of light absorbing aerosols. In: Novakov, T., ed. Proceedings:
carbonaceous particles in the atmosphere; March 1978; Berkeley, CA. Berkeley, CA: University of
California, Laurence Berkeley Laboratory; pp. 257-262; report no. LBL-9037.
Wernisch, J. (1985) Quantitative electron microprobe analysis without standard samples. X-ray Spectrom.
14: 109-119.
4-146
-------
Wernisch, J. (1986) Application of different $ (pz) distributions in quantitative electron probe microanalysis
without standard samples. Radex Rundsch. 2/3: 110-113.
Whitby, K. T. (1978) The physical characteristics of sulfur aerosols. Atmos. Environ. 12: 135-159.
Wiener, R. W.; Rodes, C. E. (1993) Indoor aerosols and aerosol exposure. In: Willeke, K.; Baron, P. A., eds.
Aerosol measurement: principles, techniques, and applications. New York, NY: Van Nostrand Reinhold;
pp. 659-689.
Wiener, R. W.; Rehme, K. A.; Eisner, A.; Vanderpool, R. W. (1994) Review and comparison of PM10 sampler
performance. Presented at: Fourth international aerosol conference; August; Los Angeles, CA.
Willeke, K.; Degarmo, S. J. (1988) Passive versus active aerosol monitoring. Appl. Ind. Hyg. 3: 263-266.
Willeke, K.; Baron, P. A., eds. (1993) Aerosol measurement: principles, techniques and applications.
New York, NY: Van Nostrand Reinhold Publishers.
Willeke, K.; Grinshpun, S. A.; Chang, C.-W.; Juozaitis, A.; Liebhaber, F.; Nevalainen, A.; Thompson, M.
(1992) Inlet sampling efficiency of bioaerosol samplers. J. Aerosol Sci. 23(suppl. 1): S651-S654.
Williams, E. L., II; Grosjean, D. (1990) Removal of atmospheric oxidants with annular denuders. Environ. Sci.
Technol. 24: 811-814.
Winberry, W. T., Jr.; Forehand, L.; Murphy, N. T.; Ceroli, A.; Phinney, B.; Evans, A. (1993) Determination
of reactive acidic and basic gases and particulate matter in indoor air (annular denuder technique).
In: Methods for determination of indoor air pollutants: EPA methods. Park Ridge, NJ: Noyes Data
Corporation.
Witz, S.; Eden, R. W.; Wadley, M. W.; Dunwoody, C.; Papa, R.; Torre, K. J. (1990) Rapid loss of particulate
nitrate, chloride and ammonium on quartz fiber filters during storage. J. Air Waste Manage. Assoc.
40: 53-61.
Wolff, G. T.; Groblicki, P. J.; Cadle, S. H.; Countess, R. J. (1982) Particulate carbon at various locations in the
United States. In: Wolff, G. T.; Klimsch, R. L., eds. Particulate carbon: atmospheric life cycle. New
York, NY: Plenum Press; pp. 297-315.
Woskie, S. R.; Shen, P.; Finkel, M.; Eisen, E. A.; Smith, T. J.; Smith, R.; Wegman, D. H. (1993) Calibration
of a continuous-reading aerosol monitor (Miniram) to measure borate dust exposures. Appl. Occup.
Environ. Hyg. 8: 38-45.
Yamada, Y. (1983) A new method for the determination of collection efficiency of an aerosol sampler by
electron microscopy. Atmos. Environ. 17: 369-372.
Yamasaki, H.; Kuwata, K.; Miyamoto, H. (1982) Effects of ambient temperature on aspects of airborne
polycyclic aromatic hydrocarbons. Environ. Sci. Technol. 16: 189-194.
Ye, Y.; Tsai, C.-J.; Pui, D. Y. H.; Lewis, C. W. (1991) Particle transmission characteristics of an annular
denuder ambient sampling system. Aerosol Sci. Technol. 14: 102-111.
Yeh, H.-C. (1993) Electrical techniques. In: Willeke, K.; Baron, P. A., eds. Aerosol measurement: principles,
techniques, and applications. New York, NY: Van Nostrand Reinhold; pp. 410-426.
Zhang, X.; McMurry, P. H. (1992) Evaporative losses of fine particulate nitrates during sampling. Atmos.
Environ. Part A 26: 3305-3312.
4-147
-------
Zielinska, B.; Arey, J.; Atkinson, R.; Winer, A. M. (1989) The nitroarenes of molecular weight 247 in ambient
paniculate samples collected in southern California. Atmos. Environ. 23: 223-229.
Zoller, W. H.; Gordon, G. E. (1970) Instrumental neutron activation analysis of atmospheric pollutants utilizing
Ge(Li) 7-ray detectors. Anal. Chem. 42: 257-265.
4-148
-------
5. SOURCES AND EMISSIONS OF
ATMOSPHERIC PARTICLES
5.1 INTRODUCTION
Unlike gaseous criteria pollutants (SO2, NO2, CO, O3), which are well defined
chemical entities, atmospheric particles comprise a complex mixture of chemical constituents.
Because of this fact, sources of each constituent of the atmospheric aerosol must be
considered in turn. Since paniculate matter (PM) is composed of both primary and
secondary constituents, emissions of both the primary components and the gaseous precursors
must be considered. The chemical composition of ambient aerosols was treated in general
terms in Chapter 3. Information on ambient concentrations of particles of various sizes
(PM10, PM2 5) and their chemical composition, based on specific field studies, is presented in
Chapter 6.
Tables 5-1A and 5-IB summarize anthropogenic and natural sources for the major
primary and secondary aerosol constituents of fine and coarse particles. Anthropogenic
sources can be further divided into stationary and mobile sources. Stationary sources include
fuel combustion for electrical utilities and industrial processes; construction and demolition;
metals, minerals, petrochemicals and wood products processing; mills and elevators used in
agriculture; erosion from tilled lands; waste disposal and recycling; and fugitive dust from
paved and unpaved roads. Mobile, or transportation related, sources include direct emissions
of primary PM and secondary PM precursors from highway and off-highway vehicles and
nonroad sources. Also shown are sources for precursor gases whose oxidation forms
secondary paniculate matter. In general, the nature of sources of paniculate matter shown in
Table 5-1A is very different from that for paniculate matter shown in Table 5-1B. A large
fraction of the mass in the fine size fraction is derived from material that has been volatilized
in combustion chambers and then recondensed to form primary fine PM, or has been formed
in the atmosphere from precursor gases as secondary PM. Since precursor gases and fine
paniculate matter are capable of travelling great distances, it is difficult to identify individual
sources of constituents shown in Table 5-1A. The PM constituents shown in Table 5-1B
5-1
-------
TABLE 5-1A. CONSTITUENTS OF ATMOSPHERIC FINE PARTICLES (<2.5 fim)
AND THEIR MAJOR SOURCES
Sources
Primary
Secondary
Aerosol
species
S04=
Natural Anthropogenic
Sea spray Fossil fuel
combustion
Natural
Oxidation of reduced
sulfur gases emitted
by the oceans and
wetlands; and SO2
and H2S emitted by
volcanism and forest
fires
Anthropogenic
Oxidation of SO2
emitted from fossil
fuel combustion
NO,
Minerals
Erosion,
re-entrainment
Organic
carbon
(OC)
Wild fires
Elemental Wild fires
carbon
Metals
Volcanic
activity
Bioaerosols Viruses,
bacteria
Motor vehicle
exhaust
Fugitive dust; paved,
unpaved roads;
agriculture and
forestry
Motor vehicle
exhaust
Open burning, wood
burning, cooking,
motor vehicle
exhaust, tire wear
Motor vehicle
exhaust, wood
burning, cooking
Fossil fuel
combustion,
smelting, brake wear
Oxidation of NOX
produced by soils,
forest fires, and
lighting
Emissions of NH3
from wild animals,
undisturbed soil
Oxidation of
hydrocarbons emitted
by vegetation,
(terpenes, waxes);
wild fires
Oxidation of NOX
emitted from fossil
fuel combustion; and
in motor vehicle
exhaust
Emissions of NH3
from animal
husbandry, sewage,
fertilized land
Oxidation of
hydrocarbons emitted
by motor vehicles,
open burning, wood
burning
5-2
-------
TABLE 5-1B. CONSTITUENTS OF ATMOSPHERIC COARSE PARTICLES
(>2.5 jim) AND THEIR MAJOR SOURCES
Sources
Aerosol species
Minerals
Metals
Miscellaneous
ions
Organic carbon
Organic debris
Bioaerosols
Primary
Natural
Erosion,
re-entrainment
Erosion,
re-entrainment,
organic debris
Sea spray
—
Plant, insect
fragments
Pollen, fungal
spores, bacterial
agglomerates
Anthropogenic
Fugitive dust; paved,
unpaved road dust,
agriculture and forestry
—
Road salting
Tire and asphalt wear
—
Secondary
Natural Anthropogenic
_ _
— —
— —
— —
have shorter lifetimes in the atmosphere, so their impacts tend to be more localized. Only
major sources for each constituent are listed in Tables 5-1A and 5-1B.
Natural sources of primary PM include windblown dust from undisturbed land, sea
spray, and plant and insect debris. The oxidation of a fraction of terpenes emitted by
vegetation and reduced sulfur species from anaerobic environments leads to secondary PM
formation. Ammonium (NH4+) ions which are crucial for regulating the pH of particles are
derived from emissions of ammonia (NH3) gas. Source categories for NH3 have been
divided into emissions from undisturbed soils (natural) and emissions which are related to
human activities (e.g., fertilized lands, domestic and farm animal waste). It is difficult to
describe emissions from biomass burning as either natural or anthropogenic. Clearly, fuel
wood burning is an anthropogenic source of PM, whereas wildfires would be a natural
source. Forest fires have been included as a natural source, because of the lack of
information on the amount of prescribed burning or accidental fires caused by humans.
5-3
-------
Similar considerations apply to the biogenic emissions of trace metals which may be
remobilized from anthropogenic inputs.
Although a large number of potential source contributions have been listed for
paniculate matter and gaseous precursors in Tables 5-1A and 5-1B, it should be noted that
emissions inventories have been compiled for only a limited number of entries for either
aerosol constituents or source categories. The remainder of the chapter includes discussion
of the processes responsible for the most important sources of primary and secondary PM in
Sections 5.2 and 5.3, respectively, followed by discussion of emissions estimates for the
United States in Section 5.4. Applications of emissions inventories and other techniques, such
as receptor modeling for inferring sources of ambient particulate matter, are then discussed
in Section 5.5.
5.2 SOURCES OF PRIMARY PARTICULATE MATTER
This section discusses processes responsible for the emissions of primary particulate
matter. The order of sources roughly follows their estimated relative source strengths for the
United States to be presented in Section 5.4. Emissions of mineral particles produced as the
result of natural wind erosion and human activities are discussed in 5.2.1. Sources of
primary particulate matter produced by fossil fuel combustion and other stationary
anthropogenic sources are discussed in 5.2.2, while sources of secondary particulate matter
are discussed in section 5.3. Motor vehicle emissions are discussed in 5.2.3. Vegetation
burning in woodstoves and forest fires is discussed as a source of particulate matter in 5.2.4.
Sea salt aerosol production, the suspension of organic debris, and the production of trace
metals by natural processes are discussed in 5.2.5. Data for the chemical composition and
particle size distribution for each of these sources of particulate matter are included where
available along with information about techniques for measuring source compositions and
emissions rates.
5.2.1 Wind Erosion and Fugitive Dust
Windblown dust constitutes a major component of the atmospheric aerosol, especially in
arid and semi-arid areas of the world. Windblown dust represents the largest single category
5-4
-------
in global emissions inventories, constituting about 50% of the total global source of primary
and secondary paniculate matter (IPCC, 1995). Since the next major category is sea-salt
aerosol production, which is estimated to constitute about 40% of total emissions, it can be
seen that about 70% of non-sea-salt aerosol emitted is in the form of mineral dust. If one-
half of the dust is assumed to be emitted in the PM10 size range, then it can be seen that
54% of non-sea-salt PM10 emitted globally is dust, less than about 10% of which originates
in the United States.
Many areas of the western United States are classified as arid or semi-arid, potentially
leading to a larger contribution of dust to the mass of the ambient aerosol there compared to
the eastern United States. Large-scale dust events are generally associated with semi-arid
regions where marginal lands are used for agriculture and herding. During times of drought,
the denuded and broken soil surface is easily carried away, periodically forming "dust bowl"
conditions as in the midwestern U.S. (Prospero, 1995).
Emission rates of mineral aerosols are found to be strongly dependent on
meteorological parameters such as wind velocity and precipitation. Wind tunnel experiments
(Bagnold, 1941; Chepil, 1945) have shown that the motion of loose particles on the surface
is initiated when the surface wind stress (The wind stress acting on the surface is supplied by
the downward transport of momentum from the mean winds. In micrometeorological
applications, u*, or the square root of the ratio of the wind stress to the air density is used.)
acting on erodible particles exceeds the downward force of gravity and the interparticle
cohesion forces acting on the particles. Particle motion occurs when u* exceeds the threshold
friction velocity, u*t, which is dependent on particle properties. Values of u*t are strongly
size dependent, with a minimum for particles having diameters of about 60 /im (Bagnold,
1941). Individual smaller particles are held by cohesive forces and larger particles are
constrained by the force of gravity. Measurements of u*t are available for a number of
different soil types (e.g., Gillette et al., 1980).
Three types of particle motion were characterized in the early wind tunnel experiments:
suspension, saltation, and creeping. Suspension refers to the upward transport of dust
(d< 60 f*m) by turbulent eddies; saltation to the horizontal motion of particles (60 < d <
2000 jLtm) which can reach heights of up to a meter above the surface before they fall back;
5-5
-------
creeping to particles too massive (d > 2000 /xm) to be lifted from the surface so they roll
along.
Because of strong cohesive forces in soil crusts and rock surfaces, particles are not
suspended directly by the transfer of momentum from the wind but by sandblasting and
abrasion by saltating particles. The impact of saltating grains then results in the emission of
smaller particles (Shao et al., 1993). The flux of saltating particles increases rapidly with
wind speed, and varies as (u*)2(u*-u*t). The size distribution of the suspended aerosol is then
controlled by the aerosol microphysical processes of coagulation and sedimentation.
Non-erodible elements on natural surfaces cut down on the surface area available for
erosion, and they take up wind momentum which would otherwise be available for erosion.
Soil moisture, salts, and organic matter mainly affect soil cohesion (e.g., Gillette et al.,
1982) and thus the size distribution of soil particle aggregates. Chepil (1956), Belly (1964),
Bisal and Hsieh (1966), and Svasek and Terwindt (1974) show that substantially greater wind
€>
forces are needed when soil surface moisture is increased by less than 1% from its dry state.
The moisture content of soils will vary throughout the year depending on the frequency and
intensity of precipitation events, irrigation, and the relative humidity and temperature of the
surrounding air. Large amounts of rain falling during 1 mo of a year will not be as effective
in stabilizing dust as the same amount of rain interspersed at intervals throughout the year.
An operational difficulty arises because u* is derived from anemometers placed at a
height of 5 or 10 m above the surface and requires assumptions about the wind profile down
to the surface. The challenge is to derive values for wind stress acting on erodible elements
(Alfaro and Gomes, 1995) which are valid for large areas. Alfaro and Gomes (1995) have
derived relations between wind velocity measurements made at conventional heights and
surface wind stresses using radar imagery to characterize surface roughness. Surface
roughness is determined by the presence of vegetation, structures, rocks and boulders,
topographic irregularities and surface obstructions. Marticorena and Bergametti (1995) have
developed parameterizations including these physical considerations suitable for use in large
scale models.
Apart from the large-scale, mean flow small-scale atmospheric vortices are also capable
of suspending dust. Dust devils, so-called because of the dust they entrain, may be found in
arid areas along roads or where the surface has been disturbed by human activity (Hall,
5-6
-------
1981; Snow and McClelland, 1990). Hall (1981) proposed that dust devils could constitute
the major source of suspended dust on hot summer days with light winds and convectively
unstable conditions, as an example in Pima Co., AZ demonstrates. Hall (1981) estimated
that large scale winds could raise 171 kg km"2 day"1 and motor vehicles could raise
48 kg km"2 day"1 on an annually averaged basis, while dust devils could raise up to
250 kg km"2 day"1 of dust (in all size ranges) on hot summer days. Atmospheric vortices are
not a source component currently treated in emissions inventories.
Apart from sources within the continental United States, an additional source of
windblown dust involves the long-range transport of dust from the Sahara desert westward
across the Atlantic Ocean. Individual dust storms have been tracked across the Atlantic,
after emerging from the northwest coast of Africa, to the east coast of the United States (Ott
et al., 1991). Saharan dust is carried into the Miami area, capable of producing dense hazes
during the summer (Prospero et al., 1987). While summertime monthly mean dust
concentrations are about 10 jwg/m3 (Prospero et al., 1993), dust events are highly sporadic
and of short duration. In a one-year study of Saharan dust deposition in Miami, Prospero
et al. (1987) found that 22% of the annual deposition occurred in one day and 68% in rain
events that occurred during two dust episodes spread over a total of four days. Gatz (1995)
has found evidence suggesting that Saharan dust has reached as far as central Illinois in at
least one episode which occurred during the summer of 1979. Up to 20 /*g/m3 of the
ambient aerosol may have originated in the Sahara desert and the Sahel during this episode.
These dust events are highly sporadic and more work needs to be done to characterize the
frequency, magnitude, and variability of these events. Similar dust transport may also occur
from the deserts of Asia across the Pacific Ocean (Prospero, 1995), but it is not clear to
what extent any of this dust reaches the United States (See Chapter 6 for more information
on long distance transport of dust particles into the United States from Africa or Asia.)
The compositions of soils and average crustal material are shown in Table 5-2 (adapted
from Warneck, 1988). Two entries are shown as representations of average crustal material.
Differences from the mean soil composition shown can result from local geology and climate
conditions. Major elements in both soil and crustal profiles are Si, Al, and Fe which are
found in the form of various minerals. In addition, organic matter constitutes a few percent,
5-7
-------
TABLE 5-2. AVERAGE ABUNDANCES OF MAJOR
ELEMENTS IN SOIL AND CRUSTAL ROCK
Elemental Abundances (ppmw)
Element
Si
Al
Fe
Ca
Mg
Na
K
Ti
Mn
Cr
V
Co
Soil
(a)
330,000
71,300
38,000
13,700
6,300
6,300
13,600
4,600
850
200
100
8
Crustal
(b)
277,200
81,300
50,000
36,300
20,900
28,300
25,900
4,400
950
100
135
25
Rock
(c)
311,000
77,400
34,300
25,700
33,000
31,900
29,500
4,400
670
48
98
12
Source: (a) Vinogradov (1959); (b) Mason (1966); (c) Turekian (1971), Model A; as quoted in Warneck
(1988).
on average, of soils. In general, the soil profile is similar to the crustal profiles, except for
the depletion of soluble elements such as Ca, Mg, and Na.
Because of the enormous difficulties encountered in developing theoretical estimates of
windblown dust emissions, most current estimates rely on the results of empirical studies.
These studies typically involve the placement of wind tunnels over natural surfaces and then
measuring emission rates and size distributions for different wind conditions. The emissions
of fugitive dust raised as the result of human activities are also extremely difficult to
quantify. Fugitive dust emissions arise from paved and unpaved roads, building construction
and demolition, storage piles, and agricultural tilling in addition to wind erosion.
Figure 5-1 shows examples of size distributions in dust from paved and unpaved roads,
agricultural soil, sand and gravel, and alkaline lake bed sediments which were measured in a
5-8
-------
100
80
60
40
20
Paved
Road Dust
Unpaved
Road Dust
:1.0|im [^<
Agricultural
Soil
Soil/Gravel
ITSP
Alkaline
Lake Bed
Figure 5-1. Size distribution of particles generated in a laboratory resuspension
chamber.
Source: Chow et al. (1994).
laboratory resuspension chamber as part of a study in California (Chow et al., 1994). This
figure shows substantial variation in particle size among some of these fugitive dust sources.
The PMt 0 abundance (6.9%) in the alkaline lake bed dust is twice its abundance in paved
and unpaved road dust. Approximately 10% of TSP is in the PM2 5 fraction and
approximately 50% of TSP is in the PM10 fraction. The sand/gravel dust sample shows that
65% of the mass is hi particles larger than the PM10 fraction. The PM2.5 fraction of TSP is
approximately 30% to 40% higher in alkaline lake beds and sand/gravel than hi the other soil
types. The tests were performed after seiving and with a short (< 1 min) waiting period
prior to sampling. It is expected that the fraction of PMt 0 and PM2 5 would increase with
distance from a fugitive dust emitter as the larger particles deposit to the surface at a larger
velocity than the smaller particles. Additional data shown in Figure 5-2 (Houck et al., 1989,
1990) were obtained hi a study characterizing particle sources hi California.
5-9
-------
100
80
60
40
20
52.3%
10.7%
(<2.5n)
4.5%
92.8%
82.7%
81.6%
95.8%
93.1%
(<2.5n!
92.4%
96.2%
(<10ji)
92.3%
(<2.5|*)
91.8%
99.2%
97.4%
(<2.5n)
87.4%
34.9%
Road and Agricultural Residential Diesel
Soil Dust Burning Wood Truck
Combustion Exhaust
Crude Oil Construction
Combustion Dust
Code: f""~l >10(i
2.5ji -
- 2.5\i
Figure 5-2. Size distribution of California source emissions, 1986.
Source: Houck et al. (1989, 1990).
5-10
-------
Unpaved roads and other unpaved areas with vehicular activity are essentially unlimited
reservoirs of dust loading when vehicles are moving. These surfaces are always being
disturbed, and wind erosion seldom has an opportunity to increase their surface roughness
sufficiently to inhibit particle suspension. The U.S. EPA AP-42 emission factor (U.S.
Environmental Protection Agency, 1995a) for unpaved road dust emissions contains variables
which account for silt loading, mean vehicle speed, mean vehicle weight, mean number of
wheels, and number of days with detectable precipitation, to determine annual PM10 dust
emissions for each vehicle-kilometer traveled. Dust loadings on a paved road surface build
up by being tracked out from unpaved areas such as construction sites, unpaved roads,
parking lots, and shoulders; by spills from trucks carrying dirt and other particulate
materials; by transport of dirt collected on vehicle undercarriages; by wear of vehicle
components such as tires, brakes, clutches, and exhaust system components; by wear of the
pavement surface; by deposition of suspended particles from many emissions sources; and by
water and wind erosion from adjacent areas. Moisture causes dust to adhere to vehicle
surfaces so that it can be carried out of unpaved roads, parking lots, and staging areas.
Carry out also occurs when trucks exit heavily watered construction sites. This dust is
deposited on paved roadway surfaces as it dries, where it is available for suspension far from
its point of origin. Fugitive dust emissions from paved roads are often higher after
rainstorms in areas where unpaved accesses are abundant, even though the rain may have
flushed existing dust from many of the paved streets.
The size distribution of samples of paved road dust obtained from a source
characterization study in California is shown in Figure 5-2. As might be expected, most of
the emissions are in the coarse size mode. The chemical composition of paved road dust
obtained in Denver, CO, during the winter of 1987-1988 is shown in Figure 5-3. The
chemical composition of paved road dust is much like an ambient PM10 sample, which
consists of a complex mixture of particulate matter from a wide variety of sources. Hopke
et al. (1980) found that the inorganic composition of urban roadway dust in samples from
Urbana, IL could be described in terms of contributions from natural soil, automobile
exhaust, rust, tire wear, and salt. Automobile contributions arose from exhaust emissions
enriched in Pb; from rust as Fe; tire wear particles enriched in Zn; brake linings enriched in
Cr, Ba, and Mn; and cement particles derived from roadways by abrasion. The complexity
5-11
-------
&e&&f&&&&/P^# ^ ^GP" ^c!^
A> y-O .<*w ^- oo ^ "A Cj* *$r ~ ^"
Chemical Compound
*>*
^
Figure 5-3. Chemical abundances for PM2.s emissions from paved road dust in Denver,
CO. Solid bars represent fractional abundances, and the error bars
represent variability in species abundances. Error bars represent detection
limits when there are no solid bars.
Source: Watson and Chow (1994).
of paved road dust is also evident in the comparison of a paved road dust profile reported by
Chow et al. (1991) for Phoenix, AZ, with profiles from other geological sources in the area.
Chow et al. (1991) noted that the abundance of organic carbon in the profile was 11 ±9%,
larger and more variable than its abundance in profiles from agricultural land, construction
sites, and vacant lots. The presence of particles produced by automotive emissions, tire
wear, organic detritus, and engine oils may account for this enrichment for organic carbon.
The abundances of Pb and Br in Phoenix paved road dust were more than double the
concentrations in the other geological profiles, indicating the presence of tailpipe exhaust
5-12
-------
from vehicles burning leaded fuels. The contribution of tire wear could have been from
4 to 45 % of that of motor vehicle exhaust, based on the results of Pierson and Brachaczek
(1974). Enrichments in species from clutch and brake wear were not detectable in the
Phoenix paved road dust profiles. These are often composed of asbestos and/or semi-metal
carbon composites. Cooper et al. (1987) examined the elemental composition of semi-metal
brake shoes and found abundances of -45% Fe, -2% Cu, -0.5% Sn, -3% Ba, and
— 0.5% Mo. None of these species were found in the Phoenix paved road dust profiles at
levels significantly in excess of their abundances in other geological sub-types.
Many fugitive dust sources are episodic rather than continuous emitters. Though
windblown dust emissions are low on an annual average, they can be quite large during those
few episodes when wind speeds are high. In Coachella Valley, CA, the South Coast Air
Quality Management District (1994) calculated 24-h emissions based on a worst windy day.
On a day when wind gust speeds exceeded 96 km/h, fugitive dust emissions could account
for 20% of the entire annual emissions. Since the rate of dust suspension varies as the cube
of the wind speed for large wind speeds, estimates of windblown dust emissions use highest
wind speeds quoted in National Weather Service Local Climatological Summaries.
Construction activities are also episodic in nature. Reeser et al. (1992) reported that fugitive
dust emissions during wintertime in Denver, CO, were 44% higher than those found in the
annual inventory using standard emissions inventory methods.
Finally, the spatial disaggregation for fugitive dust emissions is poorer than that for all
other source categories. Whereas most mobile sources are confined to established roadways
and most area sources are located in populated regions, suspendable dust sources are
everywhere. Most fugitive dust emissions are compiled on a county-wide basis and are not
allocated to specific fields, streets, unpaved roads, and construction sites possibly
contributing to high airborne PM concentrations. Several of these limitations may be
impossible to overcome, but many result from old methods being applied to the problem.
The inherent variability of fugitive dust emissions may preclude absolute emissions
estimates. Nevertheless, this examination of physical processes shows that better knowledge
of the locations of these emissions, the joint frequencies of activities and different
meteorological conditions, and more site specific measurements of key parameters could
provide much better absolute emissions rates than are now available.
5-13
-------
5.2.2 Stationary Sources
The combustion of fossil fuels, such as coal and oil, leads to the formation of both
primary and secondary paniculate matter. Fossil fuels are mainly composed of a mixture of
the remnants of plant matter and surrounding soils which have been processed at elevated
temperatures and pressures over periods of up to three hundred million years. The process
of coal formation results in a matrix of high molecular weight, highly cross-linked
polyaromatic carbocyclic and heterocyclic ring compounds containing C, H, O, N, P, and S,
and crustal materials. The hydrogen, nitrogen and phosphorus contents of coal are lower
than the original biomass, reflecting losses by microbial utilization and thermal processing.
Petroleum consists of long chain straight and branched alkanes with high carbon numbers
(i.e., C25-C50), alkenes and aromatic hydrocarbons. The trace element content of these fuels
reflects the trace element content of the initial organic matter and soil, subsequent
hydrothermal alteration during diagenesis and industrial processing. Because of the inherent
variability in each of these factors, the trace element content of fossil fuels is highly variable.
Coal combustion in the high temperature combustion zones of power plants results in
the melting and volatilization of refractory crustal components, such as aluminosilicate
minerals which condense to form spherical fly ash particles. Fly ash is enriched with metals
compared to ordinary crustal material by the condensation of metal vapors. The sulfur
content of fossil fuels ranges from fractions of a percent to about 4%. The sulfur in the fuel
is released primarily as SO2 along with smaller amounts of sulfate. Ratios of sulfate S to
total S range from about 1 % for modern coal fired power plants to several percent in
residential, commercial and industrial boilers (Goklany et al., 1984).
The elemental composition of primary particulate matter emitted in the fine fraction
from a variety of power plants and industries in the Philadelphia area is shown in Table 5-3
as a representative example of emissions from stationary fossil combustion sources (Olmez
et al., 1988). Entries for the coal fired power plant show that Si and Al followed by sulfate
are the major primary constituents produced by coal combustion, while fractional abundances
of elemental carbon were much lower and organic carbon species were not detected. Sulfate
is the major particulate constituent released by the oil fired power plants examined in this
study; and, again, elemental and organic carbon are not among the major species emitted.
Olmez et al. (1988) also compared their results to a number of similar studies and concluded
5-14
-------
TABLE 5-3. COMPOSITION OF FINE PARTICLES RELEASED BY
VARIOUS STATIONARY SOURCES IN THE PHILADELPHIA AREA
Species
(Units)
C-v (%)
C-e (%)
NH4 (%)
Na(%)
Al (%)
Si(%)
P(%)
S(%)
S04 (%)
Cl (%)
K(%)
Ca(%)
Sc (ppm)
Ti(%)
V (ppm)
Cr (ppm)
Mn (ppm)
Fe (%)
Co (ppm)
Ni (ppm)
Eddystone Coal-
Fired Power
Plant
ND
0.89 + 0.12
1.89 + 0.19
0.31 + 0.03
14 + 2
21.8 ± 1.6
0.62 + 0.10
3.4 + 0.6
11.9 + 1.2
0.022 ±0.11
1.20 ± 0.09
1.4 ± 0.5
42 + 2
1.1 ± 0.2
550 + 170
390 ± 120
290 ± 15
7.6 ± 0.4
93 ± 10
380 ± 50
Oil-Fired Power Plants
N
3
3
3
3
9
9
9
3
3
9
3
3
3
3
3
3
3
3
9
Eddystone
2.7 ± 1.2
7.7 + 1.5
3.5 ± 1.6
3.0 + 0.8
0.45 + 0.09
1.9 + 0.6
1.5 ± 0.4
11 ± 2
40 ±4
0.019 ± 0.009
0.16 ±0.05
3.6 ± 1.0
0.17 ±0.02
0.040 + 0.044
11500 ± 3000
235 ± 10
380 ± 40
1.6 ± 0.2
790 ± 150
15000 + 5000
N
3
3
3
3
3
9
9
9
3
2
9
3
3
9
3
3
3
3
3
9
Schuylkill
0.75 ± 0.63
0.22 ± 0.17
3.7 ± 1.7
3.3 ± 0.8
0.94 ± 0.08
2.6 ± 0.4
1.0 ± 0.2
13 ± 1
45 ± 7
ND
0.21 ± 0.03
2.3 ± 1.0
0.47 ± 0.02
0.12 ± 0.02
20000 ± 3000
230 ± 70
210 ± 50
1.7 ± 0.4
1100 + 200
19000 ± 2000
N
4
4
4
3
3
11
11
11
4
11
3
3
11
3
3
3
3
3
11
— Secondary
Al Plant
1.6 ± 1.5
0.18 ± 0.10
2.2 ± 0.9
16.3 ± 0.8
1.74 ± 0.09
3.1 ± 2.2
0.45 ± 0.27
3 ±4
5.9 ± 2
21 ± 4
10.9 ± 1.5
0.12 ± 0.09
0.092 ± 0.039
0.024 ± 0.003
36 ± 7
410 ± 20
120 ± 15
0.31 ± 0.02
13 ± 2
300 ± 100
N
2
2
2
1
1
2
2
2
2
1
2
2
1
2
1
1
1
1
1
2
Fluid Cat.
Cracker
ND
0.16 ± 0.05
0.43 ± 0.22
0.38 ± 0.05
6.8 ± 1.2
9.8 ± 20.0
ND
4.2 ± 12.6
38 ± 4
ND
0.031 ± 0.005
0.030 ± 0.004
2.7 ± 0.4
0.38 ± 0.1
250 ± 70
59 ± 8
14 + 3
0.20 ± 0.03
15 ± 2
220 ± 30
N
3
3
3
3
9
9
3
9
9
3
3
3
3
3
9
3
9
Municipal
Incinerator
0.57 + 0.26
3.5 ± 0.2
0.36 ± 0.07
6.6 ± 3.5
0.25 ± 0.10
1.7 ± 0.3
0.63 ± 0.12
2.9 + 0.8
6.8 ± 2.3
29 ± 5
7.6 ± 2.3
0.23 ± 0.10
0.11 ± 0.02
0.030 ± 0.015
8.6 ± 5.3
99 ± 31
165 ± 40
0.22 ± 0.05
3.7 + 0.8
290 ± 40
N
4
4
4
3
3
10
10
10
4
3
10
10
1
10
2
3
3
3
3
10
-------
TABLE 5-3 (cont'd). COMPOSITION OF FINE PARTICLES RELEASED
BY VARIOUS STATIONARY SOURCES IN THE PHILADELPHIA AREA
ON
Species
(Units)
Cu (ppm)
Zn(%)
As (ppm)
Se (ppm)
Br (ppm)
Rb (ppm)
Sr (ppm)
Zr (ppm)
Mo (ppm)
Ag (ppm)
Cd (ppm)
In (ppm)
Sn (ppm)
Sb (ppm)
Cs (ppm)
Ba (ppm)
La (ppm)
Ce (ppm)
Nd (ppm)
Sm (ppm)
Eddystone
Coal-Fired
Power Plant
290 + 20
0.041 + 0.005
640 ± 80
250 + 20
35 + 8
190 ± 80
1290 + 60
490 ± 190
170 + 60
ND
ND
0.71 + 0.04
ND
(a)
9.2 ± 0.9
ND
120 + 10
180 ± 10
80 ± 26
23 ± 2
Oil-Fired Power Plants
N
9
3
3
3
3
1
9
9
2
2
2
3
2
3
3
Eddystone
980 + 320
1.3 ± 0.3
33 ± 6
26 + 9
90 ± 60
ND
160 ± 50
140 ± 180
930 ± 210
ND
ND
ND
320 + 230
370 + 410
ND
1960 + 100
130 ± 30
89 + 23
28 + 5
3.7 ± 0.7
N
9
3
1
3
9
9
9
3
9
3
3
3
3
2
3
Schuylkill
1100 + 500
0.78 ± 0.30
50 + 16
23 + 7
45 ± 17
ND
280 + 70
100 ± 120
1500 ± 300
ND
ND
ND
200 ± 80
1020 ± 90
ND
2000 + 500
450 + 30
360 ± 20
230 + 20
20.5 + 1.5
N
11
3
3
3
11
11
11
3
11
3
3
3
3
3
3
Secondary
Al Plant
450 ± 200
0.079 ± 0.006
15 + 6
66 + 3
630 ± 70
97 ± 38
ND
ND
ND
ND
ND
ND
550 ± 540
6100 + 300
ND
ND
19 + 2
ND
ND
ND
Fluid Cat.
N Cracker
2 14 ± 8
1 0.0026 + 0.0007
1 ND
1 15 + 1
2 5.6 + 1.8
1 ND
36 ± 6
130 + 50
ND
ND
ND
ND
2 ND
1 7.7 ± 1.5
ND
290 + 90
1 3300 + 500
2700 + 400
1800 + 250
170 ± 20
N
9
3
3
9
9
2
3
2
3
3
3
3
Municipal
Incinerator N
1300 ± 500 3
10.4 + 0.5 3
64 + 34 3
42 ± 16 3
2300 + 800 10
230 + 50 2
87 ± 14 10
ND
240 ± 130 10
71 ± 15 3
1200 ± 700 3
4.9 + 1.4 3
6700 ± 1900 10
1300 + 1000 3
5.9 + 3.0 3
ND
1.1 + 0.5 1
ND
ND
ND
-------
TABLE 5-3 (cont'd). COMPOSITION OF FINE PARTICLES RELEASED
BY VARIOUS STATIONARY SOURCES IN THE PHILADELPHIA AREA
Species
(Units)
Eu (ppm)
Gd (ppm)
Tb (ppm)
Yb (ppm)
Lu (ppm)
Hf (ppm)
Ta (ppm)
W (ppm)
Au (ppm)
y. Pb (%)
^^
•~j
Th (ppm)
% mass
Eddystone
Coal-Fired
Power Plant
5.1 + 0.5
ND
3.3 + 0.3
10.3 + 0.5
ND
5.8 + 0.8
ND
20 + 8
ND
0.041 + 0.004
24 + 2
24 + 2
Oil-Fired Power Plants
N
3
3
1
3
1
9
3
6
Eddystone
ND
ND
ND
ND
ND
0.39 ± 0.07
ND
60 ± 5
0.054 + 0.017
1.8 + 0.6
1.9 + 0.5
93.5 + 2.5
N
1
2
2
9
2
6
Schuylkill N
0.65 + 0.23 3
ND
0.90 ± 0.29 3
ND
ND
ND
ND
ND
ND
1.0 + 0.2 11
ND
96 + 2 6
Secondary
Al Plant
ND
ND
ND
ND
ND
ND
ND
ND
ND
0.081 + 0.014
ND
81 + 10
Fluid Cat.
N Cracker
4.9 ± 0.7
71 + 10
8.9 + 1.3
3.7 + 0.4
0.59 ± 0.17
0.99 + 0.08
0.56 ± 0.10
ND
ND
2 0.0091 ± 0.0021
6.2 + 0.7
2 97 + 2
N
3
3
3
3
3
3
3
9
3
7
Municipal
Incinerator
ND
ND
ND
ND
ND
ND
ND
ND
0.56 ± 0.27
5.8 + 1.2
ND
89 ± 2
N
3
10
7
N = Number of samples.
ND = Not detected.
The "% mass" entries give the average percentage of the total emitted mass found in the fine fraction.
(a) Omitted because of sample contamination.
Source: Adapted from Olmez et al. (1988).
-------
that their data could have much wider applicability to receptor model studies in other areas
with some of the same source types. The high temperature of combustion in power plants
results in the almost complete oxidation of the carbon in the fuel to CO^ and very small
amounts of CO. A number of trace elements are greatly enriched over crustal abundances
(in different fuels), such as Se in coal and V and Ni in oil. In fact, the higher V content of
the fuel oil than in coal could help account for the higher sulfate seen in the profiles from the
oil-fired power plant compared to the coal-fired power plant since V is known to catalyze the
oxidation of reduced sulfur species. Although Table 5-3 only gives values of the fine particle
composition, measurements of coarse particle composition were also reported by Olmez et al.
(1988) which were qualitatively similar.
The composition of the organic carbon produced by stationary sources has not been
well characterized. Information is available for the composition of polycyclic aromatic
hydrocarbons, or PAH's (Daisey et al., 1986), while data for the composition of other
classes of organic compounds are sparse. In addition, the phase distribution of a number of
PAH's and other organic compounds will depend strongly on ambient atmospheric
conditions. It may be expected that the composition of emissions in systems operating at low
temperatures (e.g., residential coal combustion) will reflect that of the unburaed fuel.
Emissions from stationary sources are determined mainly by stack sampling with a
variety of techniques. All these techniques rely on measurements of stack flow rates and
concentrations of pollutants to determine emissions. Method 5 (Federal Register, 1977)
consists of a sampling train which is commonly used to measure emissions of various trace
metals. The method is cumbersome and is limited in the number of species that can be
sampled. Based on the realization that direct sampling of hot undiluted stack gases may not
yield an accurate representation of the chemical composition and size distribution of particles
leaving the stack, dilution sampling has also been used (e.g., Olmez et al., 1988).
Condensation, coagulation, and chemical reactions occur as stack gases are cooled and
diluted. In dilution sampling, stack gases are diluted with filtered ambient air in an attempt
to partially simulate processes occurring in upper portions of the stack and in the plume
leaving the stack. Another advantage in the use of dilution systems is that the same sampling
substrates and analytical techniques used in ambient sampling can be used. As a result, a
wider variety of constituents can be sampled than in conventional direct sampling techniques
5-18
-------
and biases resulting from the use of separate sampling systems in source apportionment
studies are eliminated. Remote monitoring methods (e.g., differential optical absorption
spectroscopy) have also been used to determine emissions of species such as Hg. The size
distribution of particles emitted by burning crude oil is shown in Figure 5-2. As can be
seen, almost all of the mass is in the fine fraction.
Apart from emissions in the combustion of fossil fuels, trace elements are emitted as
the result of various industrial processes such as steel and iron manufacturing and
non-ferrous metal production (e.g., for Pb, Cu, Ni, Zn, and Cd) as may be expected,
emissions factors for various trace elements are highly source-specific (Nriagu and Pacyna,
1988). Inspection of Table 5-3 reveals that the emissions from the catalytic cracker and the
oil-fired power plant are greatly enriched in rare-earth elements such as La compared to
other sources.
Emissions from municipal waste incinerators are dominated by Cl arising mainly from
the combustion of plastics and metals that form volatile chlorides. The metals can originate
from cans or other metallic objects and some metals such as Zn and Cd are also additives in
plastics or rubber. Many elements such as S, Cl, Zn, Br, Ag, Cd, Sn, In, and Sb are
enormously enriched compared to their crustal abundances. A comparison of the trace
elemental composition of incinerator emissions in Philadelphia, PA (shown in Table 5-3) with
the composition of incinerator emissions in Washington D.C., and Chicago, IL, (Olmez et
al., 1988) shows agreement for most constituents to better than a factor of two. High levels
of Hg associated with emissions from medical waste incinerators from discarded
thermometers, mercurials, mercury batteries, etc., have been declining because of reductions
in the use of Hg for medical purposes (Walker and Cooper, 1992). A sizable fraction of the
Hg may be particulate Hg(II) as opposed to gas phase Hg°.
5.2.3 Mobile Sources
Particulate matter from motor vehicles originates from tailpipe exhaust and from
friction acting on individual components such as tires and brakes. Both diesel and gasoline
fueled vehicles are sources of primary and secondary particulate matter. The rates of
emission and the composition of particles emitted by motor vehicles have been measured
using dynamometers with samples collected directly in the exhaust of individual vehicles
5-19
-------
(e.g., Lang et al., 1982) or at the vents of inspection facilities (e.g., Watson et al., 1994a);
or in tunnels and along open roadways (e.g., Pierson and Brachaczek, 1983; Szkarlat and
Japar, 1983). Each approach has its merits and limitations and each approach is best used to
augment the other. The principal components emitted by diesel and gasoline fueled vehicles
are organic carbon (OC) and elemental carbon (EC) as shown in Table 5-4. As can be seen,
the variability among entries for an individual fuel type is large and overlaps that found
between different fuel types. On average, the abundance of elemental carbon is larger than
that of organic carbon in the exhaust of diesel vehicles, while organic carbon is the dominant
species in the exhaust of gasoline fueled vehicles. There appears to be a tendency for
emissions of elemental carbon to increase relative to emissions of organic carbon for gasoline
fueled vehicles as simulated driving conditions are changed from a steady 55 km /hr to those
in the Federal Test Procedures (FTP's). Also shown are the results of sampling from mixed
vehicle types along roadsides and in tunnels.
The results shown in Table 5-4 were obtained during the late 1980's, and, so, the
results may not be entirely representative of current vehicles. Examples of data for the trace
element composition of motor vehicle emissions obtained in Phoenix, AZ are shown in
Table 5-5. SO2 emissions are also shown in relation to the mass of fine particles emitted.
As can be seen, small quantities of soluble ions such as SO4= and NH4+ are emitted. The
ammonium may be emitted as the result of an improperly functioning catalytic converter, or
may simply be the result of contamination during sample handling and analysis. Four
fractions are given for the organic carbon fraction and three for elemental carbon. These
refer to abundances measured at different temperatures in a thermographic analysis.
Temperatures for OC1, OC2, OC3, and OC4 are 120 °C, 250 °C, 450 °C, and 550 °C,
respectively; and, for EC1, EC2, EC3, they are 550 °C, 700 °C, and 800 °C, respectively,
in He/2% O2. The abundances of trace elements are all quite low, with most being less than
1 %. It is not clear what the source of the small amount of Pb seen in the auto exhaust
profile is. It is extremely difficult to find suitable tracers for automotive exhaust since Pb
has been removed from gasoline. However, it should also be remembered that restrictions in
the use of leaded gasoline have resulted in a dramatic lowering of ambient Pb levels. Huang
et al. (1994) attempted to identify marker elements in motor vehicle emissions, based on
sampling the exhaust of 49 automobiles. They proposed that the combination of Zn, Br, and
5-20
-------
TABLE 5-4. FRACTIONAL ORGANIC AND ELEMENTAL CARBON
ABUNDANCES IN MOTOR VEHICLE EMISSIONS
Fuel Type
Diesel
Denver, COa
Los Angeles, CAa
Bakersfield, CAb
Phoenix, AZb
Unleaded gasoline
Denver, COa
Los Angeles, CAC
Los Angeles, CAa
Phoenix, AZb
Leaded gasoline
Denver, COa
Los Angeles, CAC
Los Angeles, CAa
Mixed (tunnel and roadside)
Denver, CO
Los Angeles, CAd
Phoenix, AZ
Organic
23
36
49
40
76
93
49
30
67
52
31
50
38
39
±
±
±
±
±
±
±
±
±
±
±
±
±
±
Carbon
8%
3%
13%
7%
29%
52%
10%
12%
23%
4%
20%
24%
6%
19%
Elemental Carbon
74
52
43
33
18
5
±
±
±
+
±
±
21%
5%
8%
8%
11%
7%
39 ± %
14
16
13
15
28
38
36
±
±
±
±
±
±
±
8%
7%
1%
2%
19%
5%
11%
Ne
3
2
3
8
8
11
11
9
3
3
3
3
Sources
1,2
3, 4, 5,
7
8
1,2
3, 4, 5,
3, 4, 5,
8
1,2
3, 4, 5,
3, 4, 5,
1,2
3
8
6
6
6
6
6
Sources: (1) Watson et al. (1990a), (2) Watson et al. (1990b), (3) Cooper et al. (1987), (4) NBA (1990a),
(5) NEA (1990b), (6) NBA (1990c), and (7) Houck et al. (1989), cited in (8) Watson et al. (1994a).
Notes: (a) Modified Federal Test Procedures followed in dynamometer tests; (b) Roof monitoring at
inspection station; (c) 55 km/hr steady speed in dynamometer tests; (d) Rt. 1 tunnel at LA airport,
(e) N = Number of samples.
Sb could be used for this purpose. However, the relative abundances of these species in
automobile exhaust were shown to be highly variable, implying that other sources of these
elements may limit their usefulness as automotive tracers in some locations. To minimize
5-21
-------
TABLE 5-5. PHOENIX PM2 5 MOTOR VEHICLE EMISSIONS PROFILES (% MASS)
Chemical Species
NO3-
SO42'
NH4+
OC
OC1
OC2
OC3
OC4
EC
EC1
EC2
EC3
Al
Si
P
S
Cl
K
Ca
Ti
Cr
Mn
Fe
Cu
Zn
Sb
Ba
La
Pb
S02a
Auto
3.9 ± 2.9
2.3 ± 1.3
1.7 ± 1.0
30.1 ± 12.3
11.3 ± 3.5
9.2 ± 6.8
4.6 ± 2.2
3.5 ± 1.5
13.5 ± 8.0
11.7 ± 7.2
3.1 ± 1.6
0.15 ± 0.30
0.41 ± 0.20
1.64 ± 0.88
0.11 ± 0.07
1.01 ± 0.48
0.34 ± 0.32
0.25 ± 0.14
0.71 ± 0.41
0.07 ± 0.13
0.02 ± 0.01
0.10 ± 0.04
0.68 ± 0.42
0.07 ± 0.06
0.27 ± 0.22
0.02 ± 0.13
0.06 ± 0.40
0.15 ± 0.51
0.16 ± 0.07
32.8 ± 13.9
Diesel
0.31 ± 0.40
2.4 ± 1.0
0.87 ±0.13
40.1 ± 6.6
21.0 ± 6.3
9.1 ± 1.9
5.9 ± 1.3
4.0 ± 1.5
32.9 ± 8.0
4.4 ± 1.3
27.9 ± 5.6
0.69 ± 0.82
0.17 ±0.12
0.46 ± 0.18
0.06 ± 0.06
1.24 ±0.28
0.03 ± 0.06
0.04 ± 0.03
0.16 ± 0.06
0.00 ±0.15
0.00 ± 0.01
0.01 ± 0.01
0.16 ± 0.07
0.01 ± 0.01
0.07 ± 0.02
0.01 ± 0.14
0.14 ± 0.47
0.18 ± 0.59
0.01 ± 0.03
66.9 ± 24.0
Source: Watson et al. (1994a).
Note: Elemental abundances <0.01% (V, Co, Ni, Ga, As, Se, Br, Rb, Sr. Y, Zr, Mo, Pd, Ag, Cd, In, Sn,
Au, Hg, Tl, U) in XRF analyses excluded; OC = organic carbon; EC = elemental carbon.
"Relative to total PM2 5.
5-22
-------
errors arising from the loss of Br from filters, samples should be analyzed as soon as
possible after collection (O'Connor et al., 1977).
The chemical mechanisms responsible for the formation of carbonaceous particles in
diesel engines are not well established but are thought to involve the intermediate formation
of poly cyclic aromatic hydrocarbons, or PAH's (U.S. Environmental Protection Agency,
1993). Elemental carbon particles may be formed by the polymerization of gaseous
intermediates adsorbed on a core of refractory material. The particles are in the form of
chain or cluster agglomerates at temperatures above 500 °C. At temperatures below 500 °C,
high molecular weight organic compounds condense on the carbon chain agglomerates.
Roughly 10-40% of paniculate emissions from diesels are extractable into organic solvents
(National Research Council, 1982). In a typical profile, 50% of the extract is composed of
aliphatic hydrocarbons with 14-35 C atoms and alkyl substituted benzenes; 4% are PAH's
and heterocycles; and about 6% are PAH oxidation products including a small fraction of
nitro-PAH's. The highly polar fraction of the organic emissions has not been as well
characterized (Johnson, 1988). Inorganic compounds such as sulfuric acid are also produced
in diesel engines (Truex et al., 1980).
Particulate matter is also formed in internal combustion engines as the result of the
incomplete combustion of gasoline with contributions from engine oil. The particles consist
essentially of a solid carbon core with a coating of organic compounds, sulfate, and trace
elements. The composition of PAH's, oxy-PAH's and their alkyl homologues in tailpipe
emissions from gasoline fueled vehicles is similar to that produced in diesel engines
(Behymer and Hites, 1984). Particles produced by gasoline fueled vehicles range from
0.01 to 0.1 pirn in diameter with a peak at around 0.02 /xm, while the majority of particles in
diesel exhaust range from 0.1 to 1.0 /xm with a peak at around 0.15 pim (U.S. Environmental
Protection Agency, 1993).
The concentrations of particulate matter and total hydrocarbons in the exhaust of
gasoline fueled vehicles were found to be roughly correlated with each other by Hammerle
et al. (1992). Emission factors for particulate matter in the exhaust of gasoline fueled
vehicles range from 0.011 g/km for light duty vehicles to 0.12 g/km for heavy duty gasoline
vehicles, and from 0.23 g/km in the exhaust of diesel passenger vehicles to 1.20 g/km for
5-23
-------
heavy duty diesel vehicles (Radwan, 1995). These values are based on characteristics of the
motor vehicle fleet in 1990.
As mentioned before, the composition of automotive emissions is sampled using
individual vehicles on chassis dynamometers or by collecting aerosol samples along roadsides
or in tunnels. The control over operating characteristics by using dynamometers allows the
development of models which can predict emissions on the basis of variables such as vehicle
make and age and driving cycle. The representativeness of dynamometer test data can be
questioned if volunteered vehicles, as opposed to randomly selected vehicles, are sampled.
In addition, measuring emissions from individual vehicles is also costly and the sample
numbers are usually small, as reflected in the small number of samples shown in Table 5-4.
Moreover, a number of driving practices are not reflected in the Federal Test Procedures
leading to significant underestimates of emissions of CO and hydrocarbons (Calvert et al.,
1993). It is still not clear what effects superemitters and off-cycle driving practices have on
particle emissions rates. If the relation between paniculate matter and hydrocarbon
emissions discussed above is representative of the vehicle fleet, the effects could be
substantial. Hansen and Rosen (1990) measured the ratio of light-absorbing carbon to CO2
in the exhausts of 60 gasoline fueled vehicles. They found a factor of 250 difference
between the highest and lowest ratios measured. Larger scale studies designed to assess the
variability of paniculate emissions from motor vehicles are lacking.
Roadside and tunnel measurements sample large numbers of vehicles of different types
and have demonstrated their potential for validating the predictions of emissions models.
However, the extent to which traffic conditions in the tunnel reflect those in the situation
under study must be defined for the results to be considered representative. The same
considerations can be extended to dynamometer studies and to open-road studies along road
segments. Results from some tunnel studies are of limited usefulness because they have been
obtained under highway driving conditions which may not be representative of the conditions
found in most urban and suburban areas. Additional uncertainties result from resuspended
dust in using tunnel and roadside studies to characterize motor vehicle emissions. However,
methods are available for estimating contributions from tire wear (Pierson and Brachaczek,
1974, 1976). Remote measurements of elemental carbon in the exhaust plumes of individual
5-24
-------
vehicles (Hansen and Rosen, 1990) can overcome many of these difficulties, but the method
cannot yet be applied to aerosol constituents other than elemental carbon.
5.2.4 Biomass Burning
In addition to fossil fuels, biomass in the form of wood may be burned in forest fires or
as fuel for heating or cooking. At first glance these two broad categories might seem to
serve to distinguish between natural and anthropogenic sources. However, many forest fires
result from human intervention, either deliberately through prescribed burning in forest
management or accidentally through the improper disposal of flammable material or fugitive
sparks (e.g., Andreae, 1991). On the other hand, human intervention also suppresses
lightning triggered fires. Not enough data is available to assess the effects of humans on
forest fires, except for land clearing for agriculture. In contrast to the mobile and stationary
sources discussed earlier, emissions from biomass burning in woodstoves and forest fires are
strongly seasonal and can be highly episodic within their peak emissions seasons. Burning
fuelwood is confined mainly to the winter months and is acknowledged to be a major source
of ambient air particulate matter in the northwestern United States during the heating season.
Forest fires mainly occur during the driest seasons of the year in different areas of the
country and are especially prevalent during prolonged droughts.
An example of the composition of fine particles (PM2 5) produced by woodstoves is
shown in Figure 5-4. These data were obtained in Denver during the winter of 1987-1988
(Watson and Chow, 1994). As was the case for motor vehicle emissions, organic and
elemental carbon are the major components of particulate emissions from wood burning.
It should be remembered that the relative amounts shown for organic carbon and elemental
carbon will vary with the type of stove, the stage of combustion and the type and condition
of the fuelwood. Potassium (K) is by far the major trace element found in woodstove
emissions (Watson and Chow, 1994), making it suitable for use as a tracer for vegetation
burning (Lewis et al., 1988). Fine particles are dominant in studies of wood burning
emissions. For instance, the mass median diameter of wood-smoke particles was found to be
about 0.17 nm in a study of the emissions from burning hardwood, softwood and synthetic
logs (Dasch, 1982).
5-25
-------
Figure 5-4. Chemical abundances for PM2>5 emissions from wood burning in Denver,
CO. Solid bars represent fractional abundances, and the error bars
represent variability in species abundances. Error bars represent detection
limits when there are no solid bars.
Source: Watson and Chow (1994).
Measurements of aerosol composition, size distributions, and aerosol emissions factors
have been made in biomass burning plumes either on towers (Susott et al., 1991) or aloft on
fixed wing aircraft (e.g., Radke et al., 1991) or on helicopters (e.g., Cofer et al., 1988).
As was found for woodstove emissions, the composition of biomass burning emissions is
strongly dependent on the stage of combustion (i.e., flaming, smoldering, or mixed), and the
type of vegetation (e.g., forest, grassland, scrub). Over 90% of the dry mass in paniculate
biomass burning emissions is composed of organic carbon (Mazurek et al., 1991). Ratios of
organic carbon to elemental carbon are highly variable ranging from 10:1 to 95:1, with the
highest ratio found for smoldering conditions and the lowest for flaming conditions.
Ambient particle concentrations were about two mg/m3 during the measurement period.
Available measurements suggest that K is by far the most abundant trace element in biomass
burning plumes. Although there is considerable inter-sample variation, results from tower
5-26
-------
samples also suggest that S, Cl, and K are highest during flaming stages, while Al, Si, Ca,
and Fe tend to increase during the smoldering phase (Susott et al., 1991). Emissions factors
for total paniculate emissions increase by factors of two to four in going from flaming to
smoldering stages in the individual fires studied by Susott et al. (1991). These measurements
were made when ambient particle concentrations ranged from 15 to 40 mg/m3.
Particles in biomass burning plumes from a number of different fires were found to
have three distinguishable size modes, namely a nucleation mode, an accumulation mode,
and a coarse mode (Radke et al., 1991). Based on-an average of 81 samples, approximately
70% of the mass was found in particles < 3.5 pm in aerodynamic diameter. The fine
particle composition was found to be dominated by tarlike, condensed hydrocarbons and the
particles were usually spherical in shape. Additional information for the size distribution of
particles produced by vegetation burning was shown in Figure 5-2.
5.2.5 Sea-Salt Production and Other Natural Sources of Aerosol
Although sea-salt aerosol production is confined to salt water bodies, it is included here
because many marine aerosols can exert a strong influence on the composition of the ambient
aerosol in coastal areas. In some respects, the production of sea-salt aerosols is like that of
windblown dust in that both are produced by wind agitation of the surface. The difference
between the two categories arises because sea-salt particles are produced from the bursting of
air bubbles rising to the sea surface. Air bubbles are formed by the entrainment of air into
the water by breaking waves. The surface energy of a collapsing bubble is converted to
kinetic energy in the form of a jet of water which can eject drops above the sea surface. The
mean diameter of the jet drops is about 15% of the bubble diameter (Wu, 1979). Bubbles in
breaking waves range in size from a few /xm to several mm in diameter. Field
measurements by Johnson and Cooke (1979) of bubble size spectra show maxima in
diameters at around 100 ^m, with the bubble size distribution varying as (d/dg)"5 with
do = 100 /xm.
Since the water jet receives its water from the surface layer, which is enriched in
organic compounds, the aerosol drops are composed of this organic material in addition to
sea salt (about 3.5% by weight in sea water). Na+ (30.7%),C1" (55.0%), SO4= (7.7%),
Mg2+ (3.6%), Ca2+ (1.2%), K+ (1.1%), HC(V (0.4%), and Br (0.2%) are the major ionic
5-27
-------
species by mass in sea water (Wilson, 1975). The composition of the marine aerosol also
reflects the occurrence of displacement reactions which enrich sea-salt particles in SO4" and
NO3" while depleting them of Cl" and Br". As the drops travel upward above the water
surface, they encounter lower relative humidities and lose water until they come into
equilibrium with their environment. The resulting marine aerosol size distribution reflects
the processes of coagulation, coalescence, and sedimentation.
Seasalt is concentrated in the coarse size mode with a mass median diameter of about
7 jwm for samples collected in Florida, the Canary Islands and Barbados (Savoie and
Prospero, 1982). The size distribution of sulfate is distinctly bimodal. Sulfate in the coarse
mode is derived from sea water but sulfate in the submicron aerosol arises from the oxidation
of dimethyl sulfide (CH3SCH3) or DMS. DMS is produced during the decomposition of
marine micro-organisms. DMS is oxidized to MSA (methane sulfonic acid) a large fraction
of which is oxidized to sulfate (e.g., Hertel et al., 1994).
Apart from sea spray, other natural sources of particles include the suspension of
organic debris and volcanism. Particles are released from plants in the form of seeds,
pollen, spores, leaf waxes and resins, ranging in size from 1 to 250 /*m (Warneck, 1988).
Fungal spores and animal debris such as insect fragments are also to be found in ambient
aerosol samples in this size range. While material from all the foregoing categories may
exist as individual particles, bacteria are usually found attached to other dust particles
.(Warneck, 1988). Smaller bioaerosol particles include viruses, individual bacteria, protozoa,
and algae (Matthias-Maser and Jaenicke, 1994). In addition to natural sources, other sources
of bioaerosol include industry (e.g., textile mills), agriculture, and municipal waste disposal
(Spendlove, 1974).
Trace metals are emitted to the atmosphere from a variety of sources such as sea spray,
wind blown dust, volcanoes, wild fires and biotic sources (Nriagu, 1989). Biologically
mediated volatilization processes (e.g., biomethylation) are estimated to account for 30-50%
of the worldwide total Hg, As, and Se emitted annually, whereas other metals are derived
principally from pollens, spores, waxes, plant fragments, fungi, and algae. It is not clear,
however, how much of the biomethylated species are remobilized from anthropogenic inputs.
Median ratios of the natural contribution to globally averaged total sources for trace metals
are estimated to be 0.39 (As), 0.15 (Cd), 0.59 (Cr), 0.44 (Cu), 0.41 (Hg), 0.35 (Ni),
5-28
-------
0.04 (Pb), 0.41 (Sb), 0.58 (Se), 0.25 (V), and 0.34 (Zn), suggesting a not insignificant
natural source for many trace elements. It should be noted though that these estimates are
based on emissions estimates which have uncertainty ranges of an order of magnitude.
5.3 SOURCES OF SECONDARY PARTICIPATE MATTER (SULFUR
DIOXIDE, NITROGEN OXIDES, AND ORGANIC CARBON)
Secondary paniculate matter is an important contributor to suspended particle mass.
Sulfate is formed by the oxidation of SO2, nitrate by the oxidation of NO2, and aerosol
organic carbon species by the oxidation of a large number of precursors. Thus, the
formation rate of a substantial fraction of aerosol mass is given by a complex function of
both emission rates of precursor gases and the rates of photochemical processes in the
atmosphere. In order to use precursor emissions estimates effectively, however, it is
necessary to understand the nature of the processes that cause them to convert to paniculate
matter. Mechanisms for the oxidation of SO2 to SO4=, and NO2 to NO3", have been
discussed in Chapter 3. Both species are oxidized during daytime in the gas phase by
hydroxyl (OH) radicals. At night, NOX is also oxidized to nitric acid by a sequence of
reactions initiated by O3, that include nitrate radicals (NO3) and dinitrogenpentoxide (N2O5).
SO2 is also oxidized by heterogeneous reactions occurring in films of atmospheric particles
and in cloud and fog droplets. Data for primary and secondary components of aerosol mass
at a number of locations across the United States can be found in Chapter 6.
While the mechanisms and pathways for forming inorganic secondary paniculate matter
are fairly well known, those for organic secondary aerosol are not well understood.
Numerous precursors participate in these conversions, and the rates at which these convert
from gas to particles are highly dependent on the concentrations of other pollutants and
meteorological conditions. Pandis et al. (1992) identified three mechanisms for secondary
organic PM formation: (1) condensation of oxidized end-products of photochemical reactions
(e.g., ketones, aldehydes, organic acids, and hydroperoxides); (2) adsorption of organic
gases onto existing solid particles (e.g., polycyclic aromatic hydrocarbons); and
(3) dissolution of soluble gases which can undergo reactions in particles (e.g., aldehydes).
The first and third mechanisms are expected to be of major importance during the
5-29
-------
summertime when photochemistry is at its peak. The second pathway can be driven by
diurnal and seasonal temperature and humidity variations at any time of the year. Turpin and
Huntzicker (1991) and Turpin et al. (1991) provided strong evidence that secondary PM
formation occurs during periods of photochemical ozone formation in Los Angeles.
Haagen-Smit (1952) first demonstrated that hydrocarbons irradiated in the presence of
NOX produce light scattering aerosols. Results of later studies summarized by Altshuller and
Bufalini (1965) indicated that aerosols are produced by the irradiation of mixtures of NOX
and numerous six-carbon and higher molecular weight acyclic and cyclic olefins and aromatic
hydrocarbons. Cyclic olefins were shown to be more effective in aerosol formation than
acyclic olefins of similar molecular weight by Stevenson et al. (1965). The possibility that
aerosols might be formed from biogenic hydrocarbon emissions was investigated by Went
(1960) and Rasmussen and Went (1965). Analyses of the aerosol produced from the
photooxidation of a-pinene and NOX mixtures indicated the presence of pinonic acid and
norpinonic acid (Wilson et al., 1972).
Numerous smog chamber studies of the formation of secondary organic aerosol from
the photooxidation of terpene precursors have been performed since these earlier studies.
A study of the reaction of a-pinene and /3-pinene with O3 by Hatakeyama et al. (1989)
obtained aerosol carbon yields (mass of aerosol carbon produced per mass of C reacted), or
ACY's, of 18% and 14%, respectively, for HC levels ranging from 10-120 ppb C. In this
study, pinonaldehyde, pinenic acid, nor-pinonaldehyde, and nor-pinonic acid accounted for
less than 10% of the aerosol yield from the reaction of a-pinene. Hatakeyama et al. (1991)
subsequently obtained ACY's of 56 ± 4% and 79 ± 8% following the reaction of a-pinene
and /3-pinene, respectively, for initial HC levels of 820-3170 ppb C and NOX levels of
210-2550 ppb. Pandis et al. (1991) obtained ACY's ranging from 0.1 to 8% for the
oxidation of /3-pinene for HC levels ranging from 20-250 ppb C and NOX levels ranging from
39 to about 700 ppb. Zhang et al. (1992) obtained ACY's ranging from 0 to 5.3% for
HC levels ranging from 37-582 ppb C and NOX levels ranging from 31-380 ppb for the
oxidation of a-pinene. Results from the above studies showed that aerosol yields strongly
depend on the initial concentration of terpenes and the ratio of hydrocarbons (HC) to NOX in
the reaction chamber. However, Hooker et al. (1985) did not find a significant dependence
of aerosol yield on initial HC abundance for HC levels ranging from 3.1-50 ppb C. Their
5-30
-------
approach differed from that used in all of the above studies because they used 14C-a-pinene.
Of the 14C-a-pinene which reacted, 38-68% was found in aerosol products, 6-20% was found
in gas phase products, and 11-29% was lost to the walls of their reaction chamber.
After reaction of the a-pinene with OH radicals or O3, the radical product will add
O2 to form a peroxy radical. Zhang et al. (1992) proposed that the peroxy radical may react
with NO initiating a series of reactions forming pinonaldehyde, which may condense
depending on its concentration, or the peroxy radical may react with HO2 or other free
radicals to form aerosol products. The inhibition of the second pathway by the addition of
NO was proposed by Zhang et al. (1992) to explain the decrease of aerosol yield with added
NO. They also suggested that the dependence of aerosol yield on initial HC concentration
arises because the concentration of pinonaldehyde can more easily exceed its saturation value
and the rate of formation of aerosol products in the other pathway will also increase.
Pandis et al. (1991) found no aerosol products formed in the photooxidation of
isoprene, although they and Zhang et al. (1992) found that the addition of isoprene to
reaction mixtures increased the reactivity of the systems studied. Based on their
experimental results and the high ratio of terpene to NOX concentration ratios found in rural
and remote areas, Zhang et al. (1992) suggested that the upper limits for aerosol yields they
obtained should be used in estimating the aerosol yields from the oxidation of biogenic
hydrocarbons.
The aerosol forming potentials of a wide variety of individual anthropogenic and
biogenic hydrocarbons were compiled by Pandis et al. (1992) based mainly on estimates
made by Grosjean and Seinfeld (1989) and data from Pandis et al. (1991) for j8-pinene and
Izumi and Fukuyama (1990) for aromatic HC's. The estimates given by Pandis et al. (1992)
were converted to aerosol carbon yields below. Examples of compounds with zero ACY's
are all CrC7 alkanes, all C2-C6 acyclic alkenes, benzene, and aldehydes; examples of
compounds with lowest ACY's (< 2.0%) are C8-C10 alkanes, C6-C8 cycloalkanes, C7-C9
acyclic alkenes, C5 cyclic alkenes and p-xylene; examples of compounds with intermediate
values (2.0%-4.0%) are Cn-C14 alkanes, C9-C10 cycloalkanes, alkyl benzenes other than
p-xylene, C10-C13 alkenes and C6+ cycloalkenes; and examples of compounds with high
values (>4.0%) are C15+ alkanes, Cn+ cycloalkanes, C14+ cyclic alkenes and
monoterpenes.
5-31
-------
Studies of the production of secondary OC in ambient air have focussed on the Los
Angeles Basin. Based on aerosol yields shown above, Pandis et al. (1991) suggested that
about 1-4 tons day"1 of secondary OC in the Los Angeles basin is formed from the oxidation
of monoterpenes which are emitted at the rate of 10-40 tons day"1. This estimate may be
compared to the secondary OC production rate of 7.5 tons day"1 estimated to result from the
oxidation of anthropogenic hydrocarbons which are emitted at the rate of 1200 tons day"1
(Grosjean and Seinfeld, 1989). The overall yield of secondary OC from anthropogenic
sources in this example is about 0.6%. Pandis et al. (1991) also proposed that most of the
secondary OC in highly vegetated urban areas such as Atlanta is produced by the oxidation
of monoterpenes.
As part of the Southern California Air Quality Study (SCAQS), Turpin and Huntzicker
(1991) measured elemental and organic carbon at Claremont, CA in the summer of 1987
with an in situ carbon analyzer with 2 hour time resolution. During an air pollution episode
centered on August 28, 1987, airmass trajectories arriving at Claremont were directed
eastward (i.e., inland from the coast), allowing the entrainment of substantial hydrocarbon
precursors during transit. Peak OC concentrations (23 jig/m3) and highest OC to EC ratios
(4.6 ± 0.4) occurred together at Claremont from about 1500 to 1700 PDT. In addition,
correlations between EC and OC were low throughout the day (R2 =0.38). Turpin and
Huntzicker (1991) also measured OC and EC concentrations at Long Beach in November of
1987 with the same instrumentation. On the basis of these data, they suggested that OC to
EC ratios of 2.2 + 0.7 are characteristic of primary OC in the Los Angeles area.
Pandis et al. (1992) constructed a Lagrangian trajectory model to simulate the chemical
formation, transport and deposition of secondary OC during the August episode. They used
estimates of aerosol yields from HC oxidation compiled by Grosjean and Seinfeld (1989),
updated as necessary (e.g., Pandis et al., 1991) along with estimates of daily emissions, to
predict that 28% of the peak secondary OC on Aug. 28 at Claremont resulted from the
oxidation of toluene, 38% from other aromatic HC's, 9% from biogenic HCs, 21% from
alkanes and cycloalkanes, and the remaining 4% from other species. Values were somewhat
different on a daily average basis (19% from toluene, 46% from other aromatic HC's, 16%
from biogenic HC's, 15% from alkanes, and 4% from alkenes). There was reasonable
agreement with the data of Turpin and Huntzicker (1991) throughout most of the day, but
5-32
-------
calculated peak secondary OC levels ( ~- 5 jig/m3) were about half those inferred by Turpin
and Huntzicker (1991). A combination of factors could have contributed to this
underprediction including errors in emissions, deposition rates, chemical reaction rate data
and aerosol yields. In general, the calculated secondary OC represented 15-27% of the daily
average total OC at inland locations (Burbank, Claremont, Azusa, and Rubidoux) on August
28, 1987 and 5-19% of the average total OC at coastal sites.
Attempts were made during SCAQS to determine the composition of the organic carbon
fraction of the ambient aerosol. Organic nitrates were measured on size segregated samples
collected on zinc selenide disks which were later analyzed by transmission FTIR by Mylonas
et al. (1991). Concentrations of organic nitrates in the particle phase ranged from 0.8 to
4.0 /ig/m3, with maximum mass loadings in the 0.05 to 0.075 pirn and 0.12 to 0.26 pirn size
ranges. Concurrently, Pickle et al. (1990) used infrared spectroscopy to measure the total
abundance of compounds containing carbonyl groups and aliphatic compounds. Maximum
absorption at wavelengths characteristic of carbonyl groups was observed for particles in the
0.12 to 0.26 jum and 0.5 to 1.0 pirn size ranges. These results suggest that carbonyl
compounds are largely of secondary origin and that IR absorption by aliphatic compounds in
particles smaller than 0.12 /xm was correlated directly with automotive emissions.
Kao and Friedlander (1995) examined the statistical properties of a number of PM
components in the South Coast Air Basin. They found that the concentrations of non-
reactive, primary components of PM10 have approximately log normal frequency
distributions and constant values of geometric standard deviations (GSDs) regardless of
source type and location within their study area. However, aerosol constituents of secondary
origin (e.g., SO4=, NH4+, and NO3") were found to have much higher GSD's. Surprisingly,
the GSD's of organic (1.87) and elemental (1.74) carbon were both found to be within la
(0.14) of the mean GSD (1.85) for non-reactive primary species, compared to GSD's of 2.1
for sulfate, 3.5 for nitrate, and 2.6 for ammonium. These results suggest that most of the
OC seen in ambient samples is of primary origin. Pinto et al. (1995) found similar results
for data obtained during the summer of 1994. Further studies are needed to determine if
these relations are valid at other locations and to determine to what extent the results might
be influenced by the evaporation of volatile constituents after sampling.
5-33
-------
It must be emphasized that the inferences drawn from field studies in the Los Angeles
Basin are unique to that area and cannot be extrapolated to other areas of the country.
In addition, there is a high degree of uncertainty associated with all aspects of the calculation
of secondary OC concentrations which is compounded by the volatilization of OC during and
after sampling. Grosjean and Seinfeld (1989) derived a factor of five range in estimates of
production rates of secondary OC in the Los Angeles area by comparison of results obtained
from four different methods. Aerosol yields from the oxidation of individual hydrocarbons
reported by different investigators vary by an order of magnitude (Grosjean and Seinfeld,
1989). Significant uncertainties always arise in the interpretation of smog chamber data
because of wall reactions. Limitations also exist in extrapolating the results of smog
chamber studies to ambient conditions found in urban airsheds and forest canopies.
Concentrations of tetpenes and NOX are much lower in forest canopies (Altshuller, 1983)
than are commonly used in smog chamber studies. The identification of aerosol products of
terpene oxidation has not been a specific aim of field studies, making it difficult to judge the
results of model calculations of secondary OC formation. Uncertainties may also arise
because of the methods used to measure biogenic hydrocarbon emissions. Khalil and
Rasmussen (1992) found much lower ratios of terpenes to other hydrocarbons (e.g., isoprene)
in forest air than were expected, based on their relative emissions strengths and rate
coefficients for reaction with OH radicals and O3. They offered two explanations, either the
terpenes were being rapidly removed by some heterogeneous process or emissions were
artificially enhanced by feedbacks caused by the bag enclosures they used. If the former
consideration is correct, then the production of aerosol carbon from terpene emissions could
be substantial; if the latter is correct, then terpene emissions could have been overestimated
by the techniques used.
5.4 EMISSIONS ESTIMATES FOR PRIMARY PARTICIPATE
MATTER AND SO2, NOX, AND VOCs IN THE UNITED STATES
The emissions of a pollutant can be expressed by the following equation:
E = £ Aj-Fj-a-Cj) (5-1)
5-34
-------
where E is the total emissions rate from all sources; Aj is the activity rate for source i; Fj is
the emissions factor for the production of the pollutant by source i; and Ceff j is the fractional
efficiency of control devices used by source i. Activity rates relevant to the entries shown
in Tables 5-6 to 5-10 might refer to the electricity generated by power plants, the amount of
coke produced by a coke oven, the distance travelled by motor vehicles, the amount of
biomass consumed by forest fires per year, etc. The mass of pollutant emitted per unit
activity of a source is then expressed in terms of an emissions factor (e.g., amount of NOX
emitted per kw-hour of energy generated or per vehicle mile travelled). Emissions factors
are given in compilations (e.g., AP-42 [U.S. Environmental Protection Agency, 1995a]) or
are calculated by emissions models, which include a number of variables which can affect
emissions. Examples include the U.S. Environmental Protection Agency's PARTS model for
estimating particulate motor vehicle emissions, and BEIS which is used to calculate emissions
of hydrocarbons from vegetation (Geron et al., 1994). The product of Aj x Fj yields an
estimate of the uncontrolled emissions from a particular source i. These are then multiplied
by a factor incorporating the effects of any control devices that might be used. It is
acknowledged that control equipment breaks down, and its efficiency might not be
maintained over its lifetime of operation. Therefore, the optimum efficiencies of control
devices are multiplied by a rule effectiveness factor. The default value for the rule
effectiveness factor is taken to be 0.8 in the inventory calculations, unless a better factor can
be justified (U.S. Environmental Protection Agency, 1989). Equation 5-1 was used in the
preparation of the emissions inventories shown in Tables 5-6 through 5-10. Further details
about collection and reporting methods may be found in the National Emissions Inventory
Trends data base (U.S. Environmental Protection Agency, 1994).
Table 5-6 shows the primary PM10 emissions estimated for the period of 1985 through
1993 using the National Emissions Inventory Trends data base (U.S. Environmental
Protection Agency, 1994). Emissions are shown in the original units used in their
calculation. A short ton is equal to 2,000 pounds or 9.08 x 105 gm. Between 1985 and
1993, PM10 emissions from stationary and mobile sources decreased almost 10 percent.
During this period, contributions from highway vehicles decreased by 27 percent, reflecting
emissions controls on diesel vehicles. Contributions from industrial fuel production
5-35
-------
o\
TABLE 5-6. NATIONWIDE PRIMARY PM10 EMISSION ESTIMATES FROM
MOBILE AND STATIONARY SOURCES, 1985 TO 1993
(Thousands short tons/year)
Source Category
Fuel Combustion - Electric Utilities
Fuel Combustion - Industrial
Fuel Combustion - Other
Chemical and Allied Product Manufacturing
Metals Processing
Petroleum and Related Industries
Other Industrial Processes
Solvent Utilization
Storage and Transport
Waste Disposal and Recycling
Highway Vehicles
Off-Highway
Total
1985
284
234
896
67
147
32
317
2
57
279
271
368
2,953
1986
289
231
902
68
137
31
321
2
56
275
265
372
2,949
1987
282
226
910
68
131
30
314
2
54
265
261
350
2,893
1988
278
230
918
73
141
29
314
2
54
259
256
387
2,942
1989
278
229
922
74
142
28
308
2
54
251
253
372
2,909
1990
291
228
930
74
140
28
306
2
54
242
239
372
2,907
1991
253
229
942
72
136
28
300
2
53
245
223
367
2,849
1992
255
223
819
75
137
27
303
2
53
246
210
379
2,729
1993
270
219
723
75
141
26
311
2
55
248
197
395
2,661
Note: The sums of sub-categories may not equal total due to rounding (1 short ton = 9.08 x 105 gins).
Source: U.S. Environmental Protection Agency (1994).
-------
TABLE 5-7. MISCELLANEOUS AND NATURAL SOURCE PRIMARY PM10 EMISSION ESTIMATES,
1985 TO 1993
(Thousands short
Source Category
Fugitive Dust
Unpaved roads
Paved roads
Construction/mining and quarrying
Agriculture and Forestry
Agricultural crops
Agricultural livestock
Other Combustion
!*» Wildfires
Managed burning
Other
Natural Sources wind erosion
Total
1985
14,719
6,299
13,009
6,833
275
142
523
59
3,565
45,424
1986
14,672
6,555
12,139
6,899
285
142
530
59
9,390
50,671
1987
13,960
6,877
12,499
7,008
330
142
536
59
1,457
42,868
1988
15,626
7,365
12,008
6,090
376
142
555
59
17,509
60,730
1989
15,346
7,155
11,662
6,937
397
142
549
59
11,862
54,073
tons/year)
1990
15,661
7,299
10,396
6,999
381
717
546
59
4,192
46,250
1991
14,267
7,437
10,042
6,965
363
457
537
59
10,054
50,181
1992
14,540
7,621
10,899
6,852
386
341
547
59
4,655
45,900
1993
14,404
8,164
11,368
6,842
394
418
549
59
628
42,826
Note: The sums of sub-categories may not equal total due to rounding (1 short ton = 9.08 x 105 gms).
Source: U.S. Environmental Protection Agency (1994).
-------
TABLE 5-8. NATIONWIDE SULFUR OXIDES EMISSION ESTIMATES, 1984 TO 1993
00
Source Category
Fuel Combustion - Electric Utilities
Fuel Combustion - Industrial
Fuel Combustion - Other
Chemical and Allied Product
Manufacturing
Metals Processing
Petroleum and Related Industries
Other Industrial Processes
Solvent Utilization
Storage and Transport
Waste Disposal and Recycling
Highway Vehicles
Off-Highway
Miscellaneous
Total
1984
16,023
2,723
728
229
1,387
707
923
0
0
25
445
198
9
23,396
1985
16,273
3,169
578
456
1,042
505
425
1
4
34
446
208
7
23,148
1986
15,701
3,116
611
432
888
469
427
1
4
35
449
221
7
22,361
1987
15,715
3,068
663
425
616
445
418
1
4
35
457
233
7
22,085
(Thousands
1988
15,990
3,111
660
449
702
443
411
1
5
36
468
253
7
22,535
short tons/year)
1989
16,218
3,086
623
440
657
429
405
1
5
36
480
267
7
22,653
1990
15,898
3,106
597
440
578
440
401
1
5
36
480
265
14
22,261
1991
15,784 15
3,139 2
608
442
544
444
391
1
5
36
478
266
11
22,149 21
1992
,417
,947
600
447
557
417
401
1
5
37
483
273
10
,592
1993
15,836
2,830
600
460
580
409
413
1
5
37
438
278
11
21,888
Note: The sums of sub-categories may not equal the totals, due to rounding (1 short ton = 9.08 X 105 gms).
Source: U.S. Environmental Protection Agency (1994).
-------
TABLE 5-9. NATIONWIDE NO/ EMISSION ESTIMATES, 1984 TO 1993
u»
(Thousands short tons/year)
Source Category
Fuel Combustion - Electric Utilities
Fuel Combustion - Industrial
Fuel Combustion - Other
Chemical and Allied Product Manufacturing
Metals Processing
Petroleum and Related Industries
Other Industrial Processes
Solvent Utilization
Storage and Transport
Waste Disposal and Recycling
Highway Vehicles
Off-Highway
Miscellaneous
Total
1984
7,268
3,415
670
161
54
70
203
0
0
90
8,387
2,644
210
23,172
1985
6,916
3,209
701
374
87
124
327
2
2
87
8,089
2,734
201
22,853
1986
9,909
3,065
694
381
80
109
328
3
2
87
7,773
2,777
202
22,409
1987
7,128
3,063
710
371
76
101
320
3
2
85
7,662
2,664
203
22,386
1988
7,530
3,187
737
398
82
100
315
3
2
85
7,661
2,914
206
23,221
1989
7,607
3,209
730
395
83
97
311
3
2
84
7,662
2,844
205
23,250
1990
7,516
3,256
732
399
81
100
306
2
2
82
7,488
2,843
384
23,192
1991
7,482
3,309
745
401
79
103
298
2
2
81
7,373
2,796
305
22,977
1992
7,473
3,206
735
411
80
96
305
3
3
83
7,440
2,885
272
22,991
1993
7,782
3,176
732
414
82
95
314
3
3
84
7,437
2,966
296
23,402
"Emissions calculated as NO2.
Note: The sums of sub-categories may not equal total due to rounding (1 short ton = 9.08 x 105 gms).
Source: U.S. Environmental Protection Agency (1994).
-------
TABLE 5-10. NATIONWIDE VOLATILE ORGANIC COMPOUND EMISSION ESTIMATES, 1984 TO 1993
(Thousands short tons/year)
Source Category
Fuel Combustion - Electric Utilities
Fuel Combustion - Industrial
Fuel Combustion - Other
Chemical and Allied Product Manufacturing
Metals Processing
Petroleum and Related Industries
Other Industrial Processes
Solvent Utilization
Storage and Transport
Waste Disposal and Recycling
Highway Vehicles
Off-Highway
Miscellaneous
Total
1984
45
156
917
1,620
182
1,253
227
6,309
1,810
687
9,441
1,973
951
25,572
1985
32
248
508
1,579
76
797
439
5,779
1,836
2,310
9,376
2,008
428
25,417
1986
34
254
499
1,640
73
764
445
5,710
1,767
2,293
8,874
2,039
435
24,826
1987
34
249
482
1,633
70
752
460
5,828
1,893
2,256
8,201
2,038
440
24,338
1988
37
271
470
1,752
74
733
479
6,034
1,948
2,310
8,290
2,106
458
24,961
1989
37
266
452
1,748
74
731
476
6,053
1,856
2,290
7,192
2,103
453
23,731
1990
36
266
437
1,771
72
737
478
6,063
1,861
2,262
6,854
2,120
1,320
24,276
1991
36
270
426
1,778
69
745
475
6,064
1,868
2,217
6,499
2,123
937
23,508
1992
35
271
385
1,799
72
729
482
6,121
1,848
2,266
6,072
2,160
780
23,020
1993
36
271
341
1,811
74
720
486
6,249
1,861
2,271
6,094
2,207
893
23,312
Note: The sums of sub-categories may not equal total due to rounding (1 short ton = 9.08 x 105 gms).
Source: U.S. Environmental Protection Agency (1994).
-------
decreased by 6 percent, leading to an overall decrease of about 10% in emissions from all of
these categories from 1985 to 1993.
Table 5-7 shows PM10 emissions from natural and miscellaneous sources for 1985 to
1994. Fugitive dust is the largest source in the miscellaneous category. No clear trend is
evident in overall fugitive dust emissions, because increases in paved road dust are offset by
decreases in the mining and quarrying and construction categories. The large year-to-year
variability in wind erosion reflects changes in precipitation and regional soil conditions. For
instance, the values for 1993 reflect the flooding and extremely wet conditions that occurred
in the midwestern United States.
Tables 5-8 through 5-10 show nationwide emissions for sulfur dioxide, oxides of
nitrogen, and VOC's, which are all precursors for secondary aerosol formation, for the
period from 1984 through 1993. Electric utilities account for the largest fraction of sulfur
dioxide, nearly 70% of total emissions in 1993 (Table 5-8). Estimates of sulfur dioxide
emissions from industrial fuel combustion increased by approximately 16% from 1984 to
1985, and decreased by 11% between 1985 and 1993. Sulfur dioxide emissions from
chemical manufacturing doubled between 1984 and 1985, with emissions leveling off between
0.42 and 0.46 million short tons/year after 1985. Sulfur dioxide emissions from highway
vehicles were estimated to have increased by 8% from 1984 to 1989, then levelling off and
then decreasing by about 10% from 1992 to 1993, reflecting the introduction of regulations
for the desulfurization of diesel fuel. Off-highway vehicle emissions increased from 0.20
million short tons per year in 1984 to 0.28 million short tons per year in 1993. Major sulfur
dioxide emissions reductions were observed for petroleum processing and other industrial
processes, with decreases of 40% to 50% over the ten-year period. In total, however, sulfur
dioxide emissions estimates in 1993 decreased by 6% from those given for 1984.
Table 5-9 shows no significant variations in total nitrogen oxides emissions over the
10-year period. Electric utility and motor vehicle emissions each account for about one-third
of total emissions. Emissions from (a) industrial and other fuel combustion and (b) from
off-highway vehicles each account for about one-sixth of total emissions. There is little
change in total emissions from 1984 to 1993. Moderate increases are seen in the electric
utility, industrial and other fuel combustion, and off-highway vehicles categories with much
5-41
-------
larger relative increases for chemical manufacturing and metals processing. These increases
are offset by decreases in fuel combustion by industry and on-highway vehicles.
Volatile organic compound (VOC) emissions in Table 5-10 are dominated by highway
vehicles and solvent use. These two sources together account for 50 to 60% of total
emissions. Off-highway vehicles, petroleum-related industries, chemical manufacturing, and
petroleum storage and transport account for most of the remaining amounts. VOC emissions
from highway vehicles were reduced between 1984 and 1993 by 35%, in spite of increased
vehicle mileage. Most of this decrease is due to the presumed effectiveness of emissions
controls on newer vehicles. VOC emissions from petroleum industries also were reduced by
43% between 1984 and 1993. Total VOC emissions decreased by 9% between 1984 and
1993. It should be noted that emissions from natural sources are not reflected in the above
discussion.
Although total emissions of gaseous precursors (SO2, NOX, and VOC's) are shown in
Tables 5-8, 5-9, and 5-10, it should be remembered that these values cannot be directly
translated into production rates of paniculate matter. Dry deposition and precipitation
scavenging of some of these gases can occur before they are oxidized to aerosols in the
atmosphere. In addition, some fraction of these gases are transported outside of the domain
of the continental United States before being oxidized. Likewise, emissions of these gases
from areas outside the United States can result in the transport of their oxidation products
into the United States. While the chemical oxidation of SO2 will lead quantitatively to the
formation of SO4=, the formation of aerosol from the oxidation of VOC's will be much less
because only a small fraction of VOC's react to form particles, and those that do have
efficiencies less than 10% (c.f. Section 5.3). The oxidation of NO2 will yield HNO3, some
of which may dry deposit or be scavenged by precipitation, and the remainder will form
paniculate nitrate.
Projections of future emissions of primary PM10, SO2, and NOX are shown in
Table 5-11. Controls mandated by the Clean Air Act Amendments of 1990 are expected to
reduce PM10 emissions in nonattainment areas. However, because emissions in
nonattamment areas constitute a small subset of total emissions, overall emissions are
projected as still likely to increase. Fugitive dust sources contribute the major share of the
increase. Changes in emissions after 1996 solely reflect activity level changes with the
5-42
-------
TABLE 5-11. PROJECTED TRENDS IN PARTICIPATE MATTER (PM10), SULFUR DIOXIDE (SOj),
AND OXIDES OF NITROGEN (NOJ EMISSIONS (1Q6 short tons yi"1)
PM10 Source Categories
Fuel Combustion3
1990
1993
1996
1999
2000
2002
2005
2008
2010
Natural3
4.36
1.98
4.36
4.36
4.36
4.36
4.36
4.36
4.36
Misc.a-b
36.3
37.9
43.6
48.5
49.8
51.8
54.9
57.4
59.0
Electric
Utilities
0.28
0.26
0.31
0.33
0.34
0.35
0.37
0.40
0.42
Industrial
0.24
0.23
0.21
0.20
0.20
0.19
0.19
0.18
0.18
Other
0.55
0.54
0.66
0.59
0.66
0.59
0.64
0.69
0.73
OSC
0.90
0.91
0.89
0.93
0.94
0.97
1.01
1.04
1.06
Mobile3
On-Road
0.36
0.32
0.15
0.13
0.12
0.13
0.13
0.13
0.12
Nonroad
0.37
0.40
0.44
0.47
0.48
0.50
0.53
0.55
0.56
Total3
43.3
42.5
50.6
55.9
56.9
59.0
62.2
64.7
66.4
S02d
22.4
21.5
18.1
17.6
17.4
17.1
16.7
16.1
15.7
N0xd
23.0
23.3
21.9
21.8
20.5
20.5
20.8
21.3
21.6
aSame categories as used in Tables 5-6 and 5-7.
bThe miscellaneous category includes fugitive dust from unpaved and paved roads, and other sources; wildfires and managed burning; and agricultural and
forestry related emissions.
COS refers to other stationary sources such as chemical manufacturing, metal processing, petroleum refining, other industrial processes, solvent utilization,
storage and transport, waste disposal and recycling.
dOnly total emissions are shown.
Source: U.S. Environmental Protection Agency (1995b).
-------
exception of on-road vehicles. Emission factors for on-road vehicles are expected to
decrease mainly because of stringent standards for diesel emissions. Diesel vehicle emissions
are expected to decrease nationwide by about 70% from 1990 to 2010 (U.S. Environmental
Protection Agency, 1993). This decrease results mainly from a roughly 90% decrease in
emissions factors which are partially offset by an increase in total diesel vehicle miles
travelled. As can be seen from Table 5-11, emissions from non-road sources (e.g., marine
vessels, railroads, aircraft, vehicles used in construction, industry, agriculture, airport
services, and landscaping) are projected to exceed those from on-road vehicles from 1990
to 2010.
Emissions of SO2 from fossil fuel combustion by electric utilities show an expected
continued decline through 2010. Emissions from all other categories in Table 5-7 show a
slight increase from 1993 to 2002 and then level off to the year 2010. Total NOX emissions
show a decrease of over 10% from 1993 to 2002, then increase by about 5% by the year
2010. This pattern reflects projected emissions for the major categories of fuel combustion
by electric utilities and on-road vehicles.
Emissions of ammonia and ammonium are not included in the U.S. Environmental
Protection Agency inventories for criteria pollutants. Dentener and Crutzen (1994) have
constructed a global inventory of NH3 emissions. Anthropogenic sources (animals kept for
human use, fertilizer applications, and biomass burning) and natural sources (wild animals,
vegetation, and the oceans) were included. Emissions from sewage were not included,
though.
Vegetation was found to be either a source or a sink for NH3 depending on ambient
concentrations and vegetation type. Animals kept for human use represent the largest single
source category. Highest emission rates in North America were found in the central United
States. Matthews (1994) found that about 75% of U.S. NH3 emissions from the application
of nitrogenous fertilizers occur in the central United States, with the remainder about evenly
divided between the eastern and western United States. Emissions of approximately 0.51 Tg
NH3-N yr"1 were calculated for the United States. The Dentener and Crutzen (1994)
estimate of NH3 emissions for North America of 5.2 Tg N yr"1 may be compared to a wet
deposition rate of NH4+ in the United States of 3 -4.5 Tg N yr"1, and three separate emission
inventories yielding values of 1.2, 8.8, and 2.8 Tg N yr"1 for the U.S. (Placet et al., 1991).
5-44
-------
While emissions of organic carbon (OC) and elemental carbon (EC) are included
implicitly in the emissions inventories for PM10, it is still useful to consider independent
estimates. Zhang et al. (1992) estimated the total production of secondary organic aerosol to
be about 1.2 Tg yr"1 in the United States. Liousse et al. (1996) have constructed OC and EC
emissions inventories for use in a global scale chemical tracer model. They estimate OC
emissions of 0.80 Tg OC yr"1 from live biomass combustion, 1.4 Tg OC yr"1 from fossil fuel
combustion, and 0.59 Tg OC yr"1 from the oxidation of naturally emitted terpenes assuming
a fractional aerosol yield of 5 %. Carbon values for OC sources have been multiplied by a
factor of 1.2 to account for the presence of oxidized species. EC emissions from the
combustion of live biomass and fossil fuels are estimated to be 0.11 Tg EC yr"1 and
0.30 Tg C yr"1, respectively. These estimates are roughly 8% of total particulate emissions
shown in Tables 5-6 and 5-7. Comparisons of model results with observations from the
IMPROVE/NESCAUM network by Liousse et al. (1996) suggest that both the OC and
EC emissions derived for their model may be systematically underestimated by at least a
factor of two.
The regional nature of total primary particulate matter emissions is illustrated in
Figure 5-5. At least 80% of the emissions in any single region arises from fugitive dust
sources and wind erosion. SO2 regional emissions are shown in Figure 5-6 as a reminder
that they are highest in the eastern United States and that the oxidation of SO2 to SO4= can
constitute a substantial fraction of the aerosol mass in the eastern United States. It can also
be seen that the ratio of SO2 to primary PM10 emissions tends to be much higher in the
eastern than in the western United States.
Annual averages do not reflect the seasonality of certain emissions. Residential wood
burning in fireplaces and stoves, for example, is a seasonal practice which reaches its peak
during cold weather. Cold weather also affects motor vehicle exhaust particulate emissions,
both in terms of chemical composition and emission rates (e.g., Watson et al., 1990b; Huang
et al., 1994). Planting, fertilizing, and harvesting are also seasonal activities. Forest fires
occur mainly during the local dry season and during periods of drought.
Several of the sources in Tables 5-6 through 5-10 are episodic rather than continuous in
nature. This is especially true of prescribed and structural fires and fugitive dust emissions.
Although windblown dust emissions are low on an annual average, they are likely to be quite
5-45
-------
Figure 5-5. Estimates of primary PM10 emissions by U.S. Environmental Protection
Agency region for 1992.
Units = 106 short tons/yr (1 short ton = 9.08 x 105 gins).
Source: U.S. Environmental Protection Agency (1993).
Figure 5-6. Estimates of sulfur dioxide emissions by U.S. Environmental Protection
Agency region for 1992.
Units = 106 short tons/yr (1 short ton = 9.08 x 10s gms).
Source: U.S. Environmental Protection Agency (1993).
5-46
-------
large during those few episodes when wind speeds are high. The transport of Saharan dust
to the continental United States is also highly episodic.
5.5 APPLICATIONS AND LIMITATIONS OF EMISSIONS
INVENTORIES AND RECEPTOR MODELS
This section examines requirements for the design and construction of emissions
inventories and potential areas of uncertainty and limitations in their use. Receptor modeling
methods to apportion sources to mass components in ambient aerosol measurements, and
results for a number of aerosol monitoring studies, will then be presented. Some general
considerations of the relative strengths and weaknesses of using emissions inventories and
receptor models to assign sources to particulate matter components in ambient samples will
then be discussed. Finally, results from specific receptor modeling studies in the eastern and
western United States will be discussed.
5.5.1 Uncertainties in Emissions Estimates
It is difficult to assign uncertainties quantitatively to entries in emissions inventories.
Methods that can be used to verify or place constraints on emissions inventories are sparse.
In general, the overall uncertainty in the emissions of a given pollutant includes contributions
from all of the terms on the right hand side of Eq. 5-1 (activity rates, emissions factors, and
control device efficiencies). Additional uncertainties can arise during the compilation of an
emissions inventory because of missing sources and arithmetical errors. The variability of
emissions can cause errors when annual average emissions are applied to applications
involving shorter time scales.
Activity rates for well-defined point sources (e.g., power plants) should have the
smallest uncertainty associated with their use, since accurate production records need to be
kept. On the other hand, activity rates for a number of areally dispersed fugitive sources are
extremely difficult to quantify. Emissions factors for easily measured fuel components which
are quantitatively released during combustion (e.g., CO2 and SO2) should be the most
reliable. Emissions of components formed during combustion are more difficult to
characterize as the emissions rates are dependent on factors specific to individual combustion
5-47
-------
units and on combustion stage (i.e., smoldering or active). Although the AP-42 emissions
factors (U.S. Environmental Protection Agency, 1995a) contain extensive information for a
large number of source types, these data are very limited in the number of sources sampled.
The efficiency of control devices is determined by their age, their maintenance history, and
operating conditions. It is virtually impossible to assign uncertainties in control device
performance due to these factors. It should be noted that the largest uncertainties occur for
those devices which have the highest efficiencies (>90%). This occurs because the
efficiencies are subtracted from one and small errors in assigning efficiencies can lead to
large errors in emissions.
Ideally an emissions inventory should include all major sources of a given pollutant.
This may be an easy task for major point sources, but becomes problematic for poorly
characterized area sources. As an example, it was recently realized that meat cooking could
be a significant source of organic carbon (Hildemann et al., 1991). Further research is
needed to better characterize the sources of pollutants in order to reduce this source of
uncertainty. Errors can arise from the misreporting of data, and arithmetic errors can occur
in the course of compiling entries from thousands of individual sources. A quality assurance
program is required to check for outliers and arithmetic errors.
Because of the variability in emissions rates, there can be errors in the application of
inventories developed on an annually averaged basis (as are the inventories shown in
Tables 5-6 to 5-10) to episodes occurring on much shorter time scales. As an example, most
modeling studies of air pollution episodes are carried out for periods of a few days.
Uncertainties in annual emissions were estimated to range from 4 to 9% for SO2 and
from 6 to 11% for NOX in the 1985 NAPAP inventories for the United States (Placet et al.,
1991). Uncertainties in these estimates increase as the emissions are disaggregated both
spatially and temporally. The uncertainties quoted above are conservative estimates and refer
only to random variability about the mean, assuming that the variability in emissions factors
was adequately characterized and that extrapolation of emissions factors to sources other than
those for which they were measured is valid. The estimates do not consider the effects of
weather or variations in operating and maintenance procedures. Fugitive dust sources, as
mentioned above, are extremely difficult to quantify, and stated emission rates may only
represent order-of-magnitude estimates. As rough estimates, uncertainties in emissions
5-48
-------
estimates could be as low as 10% for the best characterized source categories, while
emissions figures for windblown dust should be regarded as order-of-magnitude estimates.
Given (a) uncertainties in the deposition of SO2 and its oxidation rate, (b) the variability seen
in OC and EC emissions from motor vehicles along with the findings from past verification
studies for NMHC and CO to NOX ratios, (c) ranges of values found among independent
estimates for emissions of individual species (NH3, OC), and (d) the predominance of
fugitive emissions, PM emissions rates should be regarded as order-of-magnitude estimates.
There have been few field studies designed to test emissions inventories observationally.
The most direct approach would be to obtain cross-sections of pollutants upwind and
downwind of major urban areas from aircraft. The computed mass flux through a cross
section of the urban plume can then be equated to emissions from the city chosen. This
approach has been attempted on a few occasions. Results have been ambiguous because of
contributions from fugitive sources, non-steady wind flows, and general logistic difficulties.
Greater success, albeit on a smaller scale, has been achieved in studies that tested
predictions of the State of California EMFAC emissions model. An ambient-air study in the
Los Angeles basin (Fujita et al., 1992) showed that motor vehicle emissions of CO and
nonmethane hydrocarbons (NMHC) were being systematically underpredicted in the
emissions model by a factor of about 2.5, assuming that NOX emissions were much better
known; i.e., the CO to NOX and NMHC to NOX ratios were underpredicted by the model. A
study performed in a tunnel in the Los Angeles basin (Ingalls, 1989; Pierson et al., 1990)
showed that motor vehicle NOX emission rates (g/mi) were predicted approximately correctly
but that the CO and NMHC emission rates were systematically underpredicted in the
emissions model by factors of two to three. Similar tests need to be performed for
particulate matter emissions from motor vehicles.
A completely different approach to obtaining area-wide emissions of pollutants relies on
the construction of inversion algorithms applied in the context of atmospheric transport
models (Brown, 1993). Emissions of a pollutant that are required to produce a specified
distribution of surface concentrations are solved for by using model-derived transport and
chemical loss terms. Uncertainties in the emissions fields are then generated in terms of
specified uncertainties in the observed data and in the model transport and chemistry fields.
5-49
-------
A number of factors limit the ability of an emissions inventory driven, chemical tracer
model to determine the effects of various sources on particle samples obtained at a particular
location apart from uncertainties in the inventories given above. Air pollution model
predictions represent averages over the area of a grid cell, which in the case of the Urban
Airshed Model typically has been 25 km2 (5 km X 5 km). The contributions of sources to
pollutant concentrations at a monitoring site are strongly controlled by local conditions which
cannot be resolved by an Eulerian grid-cell model. Examples would be the downward
mixing of tall stack emissions and deviations from the mean flow caused by buildings. The
impact of local sources may not be accurately predicted, because their emissions would be
smeared over the area of a grid cell or if the local wind flow were in the wrong direction
during sampling.
For these reasons, receptor models have been used to determine source contributions to
paniculate matter at individual monitoring sites. Receptor models are strictly diagnostic in
their application and do not have the prognostic, or predictive, capability of chemical
transport models. In addition, receptor models have been developed for apportioning sources
of primary particulate matter and are not formulated to include the processes of secondary
paniculate matter formation which are explicitly included in the chemical transport models.
5.5.2 Receptor Modeling Methods
Receptor models relate source contributions to ambient concentrations based on
composition analysis of ambient particulate samples. They depend on the assumption of
mass conservation and the use of a mass balance. As an example, assume that the total
concentration of particulate lead measured at a site can be considered to be the sum of
contributions from a number of independent sources,
Pbtotal = Pbmotor vehicle + Pbsoil + PbSmeUer + ' ' ' (5'2>
Since most sources emit particles that contain a number of chemical elements or compounds,
the atmospheric concentration of an element can be considered to be the product of the
abundance of the element of interest (ng/mg) in the effluent and the mass concentration of
particles from that source in the atmosphere (mg/m3). For lead from motor vehicles, for
example,
5-50
-------
motor vehicles Pb, mv J mv
where apb mv is the abundance of lead in motor vehicle emissions, and fmv is the mass
concentration of motor vehicle emitted particles in the atmosphere. Extending this idea to
m chemical elements, n samples, and p independent sources,
•ft 4 (5"4)
where Xy is the ith elemental concentration measured in the jth sample (ng m"3), aik is the
gravimetric abundance of the 1th element in material from the k1*1 source (ng mg"1), and
fkj is the airborne mass concentration of material from the kth source contributing to the
jl sample (mg m" ). The fk: are the quantities to be determined from Equation 5-4. To
distinguish the contributions of one source type from another using receptor models, the
chemical and physical characteristics must be such that (1) they are present in different
proportions in different source emissions, (2) these proportions remain relatively constant
for each source type, and (3) changes in these proportions between source and receptor are
negligible or can be empirically represented.
A number of specialty conference proceedings, review articles, and books have been
published to provide greater detail about source apportionment receptor models (Cooper and
Watson, 1980; Watson et al., 1981; Macias and Hopke, 1981; Dattner and Hopke, 1982;
Pace, 1986; Watson et al., 1989; Gordon, 1980, 1988; Stevens and Pace, 1984; Hopke,
1985, 1991; Javitz et al., 1988). Watson et al. (1994b) present data analysis plans which
include receptor models as an integral part of visibility and PM10 source apportionment and
control strategy development.
The first step in attempting to relate ambient particulate matter measured at a
particular location to source contributions is typically data evaluation. The objectives for
data evaluation are: (1) to summarize the accuracy and precision of measurements; (2) to
identify and investigate extreme and inconsistent values; (3) to perform data comparisons
and investigate discrepancies; and (4) to estimate the equivalence of measurements of the
same variable by different methods.
Even with the most stringent quality assurance, it is prudent to perform several
straightforward analyses to identify the presence of any discrepancies in atmospheric
5-51
-------
particulate data and to correct, flag, or eliminate them. Investigating the equivalence of
different measurement methods for the same variable is especially important for particulate
chemical measurements, which may show substantial differences in concentration depending
upon how they were made. Data evaluation activities include: (1) plotting and examining
pollutant time series data to identify spikes and outliers for investigation; (2) comparing the
sum of chemical species with PM,0 mass measurements; and (3) comparing measurements
of the same variables at the same or nearby sites using different measurement devices and
procedures.
After data evaluation the next step in an analysis of particulate air quality in a region
is a process that can be termed a descriptive air quality analysis. The objectives of a
descriptive air quality analysis are: (1) to identify similarities and differences in air quality
at different sampling sites; and (2) to depict temporal and spatial variations in particulate
and gaseous precursor measurements. Descriptive air quality analysis includes:
(1) statistical summaries of median and extreme values of air quality variables for different
sites, episodes, and times of day; (2) time series plots of PM10 and selected chemical
components; (3) spatial pie plots of particulate chemical composition; and (4) spatial and
temporal correlations between PM10 and chemical composition measurements. The product
of this analysis is a quantitative overview of particulate concentrations during the period of
interest.
Performed at the same time as a descriptive air quality analysis, a descriptive
meteorological analysis is carried out to: (1) describe the spatial structure, temporal
variability, and statistical distribution of meteorological conditions; (2) describe the
transport and mixing patterns in the study domain; and (3) identify relationships between
meteorology and atmospheric particulate concentrations. Data normally available would
include wind speed, wind direction, temperature, relative humidity, and solar radiation at
ground level and aloft (if available).
Descriptive meteorological analysis activities include: (1) statistical summaries of
meteorological variables; (2) time series and spatial plots of meteorological variables,
including wind vectors, with examination for phenomena such as inter-basin transport,
stagnation, slope flows, convergence zones, and recirculation; (3) identification of layers
and orographic phenomena that change with elevation; (4) tabulations of fog occurrences,
5-52
-------
frequencies, locations, and intensities; and (5) meteorological descriptions and comparisons
with meteorology during high PM]0 episodes from prior years.
The product of these analyses is a conceptual understanding of how meteorological
phenomena influence atmospheric particulate concentrations in a particular region.
The next step in receptor modeling for particulate matter is a source profile
compilation. The objectives of source profile compilation analysis are: (1) to combine
profiles from individual samples into composite profiles; and (2) to assign source profiles to
source categories based on their degree of similarity or difference. Data needed for this
study are the chemical measurements on samples from representative source types that are
expected to contribute to airborne particulate matter during study periods. Major source
types include, for example: (1) suspended geological material from roads and from
agricultural and unpaved areas; (2) primary particle exhaust from gasoline- and
diesel-powered vehicles; (3) industrial sources; (4) residual oil combustion; and
(5) secondary ammonium sulfate and ammonium nitrate originating from gaseous
precursors. Source profile compilations include: (1) tables and plots of individual profiles
and their uncertainties; (2) calculation of averages and standard deviations for category
profiles; and (3) calculation of weighted composite profiles for source categories which are
found for the source apportionment modeling described below. It is important to emphasize
that source and ambient samples must be analyzed using the same protocols and methods
(U.S. Environmental Protection Agency, 1994).
The chemical mass balance (CMB) receptor model is the model most commonly used
for particulate matter source apportionment. The CMB model uses the chemical and
physical characteristics of gases and particles measured at source and receptor to both
identify the presence of, and quantify source contributions to, the receptor (Friedlander,
1973).
The CMB consists of an effective variance least-squares solution to the set of linear
equations (5-4) that expresses each concentration of a chemical species at a receptor site as
a linear sum of products of source profile species and source contributions. The source
profile species, i.e., the fractional amount of the species in the emissions from each source
type, and the receptor concentrations, with appropriate uncertainty estimates, serve as input
data to the CMB model. The output consists of: (1) the source contribution estimates of
5-53
-------
each source type; (2) the standard errors of these source contribution estimates; and (3) the
amount contributed by each source type to each chemical species. The model calculates
values for the contributions from each source type and the uncertainties associated with
those values. Input data uncertainties are used both to weight the importance of input data
values in the solution and to calculate the uncertainties of the source contributions. The
CMB model assumptions are: (1) compositions of source emissions are constant over the
period of ambient and source sampling; (2) chemical species do not react with each other,
i.e., they add linearly; (3) all sources with a potential for significantly contributing to the
receptor have been identified and their emissions have been characterized; (4) the source
compositions are linearly independent of each other; (5) the number of sources or source
categories is less than or equal to the number of chemical species; and (6) measurement
uncertainties are random, uncorrelated, and normally distributed. Assumptions 1 through
6 for the CMB model are fairly restrictive and will never be completely satisfied in actual
practice. Fortunately, the CMB model can tolerate reasonable deviations from these
assumptions, although these deviations increase the stated uncertainties of the source
contribution estimates.
The CMB modeling procedure requires: (1) identification of the contributing source
types; (2) selection of chemical species to be included; (3) estimation of the fraction of each
of the chemical species which is contained in each source type (i.e., the source
compositions); (4) estimation of the uncertainty in both ambient concentrations (including
artifacts during sampling and storage such as gas absorption or volatilization in filter
samples) and source compositions; (5) estimation of differential losses during transport
from source to receptor; (6) solution of the chemical mass balance equations; and
(7) validation and reconciliation. Each of these steps requires different types of data.
Uncertainties in the modeling results can be noticeably reduced by obtaining source profile
measurements which correspond to the period of ambient measurements (Glover et al.,
1991; Dzubay et al., 1988; and Olmez et al., 1988). Stratifying data according to wind
direction can also increase the number of source types that can be resolved as shown in the
above studies.
Emissions inventories are examined to determine the types of sources that are most
likely to influence a receptor. These emissions inventories for particulate matter are
5-54
-------
frequently far from complete, however, and other measures are needed to infer the influence
of uninventoried sources. The Principal Components Analysis and Empirical Orthogonal
Function models described below can aid in this identification. Once these sources have
been identified, profiles acquired from similar sources can be examined to select the
chemical species to be measured. The more species measured, the better the precision of
the CMB apportionment.
The Principal Components Analysis (PCA) receptor model classifies variables into
groups identifiable as causes of particulate matter levels measured at receptors. Typical
causes are emissions sources, chemical interactions, or meteorological phenomena. The
PCA model uses ambient concentrations of chemical species and meteorological data as
inputs. PCA does not use source emissions measurements, as does the CMB model, but it
may require 50 or more measurements of many species from different time periods at a
single receptor site.
The PCA procedure is as follows: (1) select the chemical species and measurement
cases to be included; (2) calculate the correlation coefficients between the species;
(3) calculate the eigenvectors and eigenvalues of the correlation matrix; (4) select
eigenvectors to be retained; (5) rotate these eigenvectors into a more physically meaningful
space; and (6) interpret the rotated vectors as air pollution sources based on the chemical
species with which they are highly correlated. Freeman et al. (1989) describe the computer
software and methods required to use the PCA model for PM10 source assessment. See
also Henry (1991).
The PCA model assumptions are: (1) compositions of source emissions are constant
over the period of ambient and source sampling; (2) chemical species concentrations add
linearly; (3) measurement errors are random and uncorrelated; (4) the case-to-case
variability of actual source contributions is much larger than the variability due to other
causes, such as measurement uncertainty or changes in source profiles due to process and
fuel changes; (5) causes of variability that affect all sources equally (such as atmospheric
dispersion) have much smaller effects than causes of variability for individual source types
(such as wind direction or emission rate changes); (6) the number of cases exceeds the
number of variables in the PCA model to an extent that statistical stability is achieved; and
(7) eigenvector rotations are physically meaningful.
5-55
-------
There are a number of examples of the application of PCA models. Photochemical
factors were found to influence particulate matter measurements from Los Angeles, CA,
New York, NY (Henry and Hidy, 1979), St. Louis, MO (Henry and Hidy, 1982),
Lewisburg, WV (Lioy et al., 1982), and Detroit, MI (Wolff et al., 1985a). These
photochemical factors were consistently associated with daily average and maximum ozone
(O3), maximum temperatures, and absolute humidity. The photochemical factors found for
Los Angeles data (Henry and Hidy, 1979) were highly correlated with daily maximum and
minimum relative humidity measurements. Local source factors were found for Salt Lake
City (Henry and Hidy, 1982) and Los Angeles (Henry and Hidy, 1979) and were highly
correlated with sulfur dioxide (SO2) and the wind direction frequency distributions.
Dispersion/stagnation factors were found for St. Louis, Salt Lake City, and Lewisburg. The
variables correlated with the dispersion/stagnation factor were nitric oxide (NO), nitrogen
dioxide (NO2), wind speed at midnight and noon, average wind speed, morning mixing
height, maximum hourly precipitation, and average precipitation. PCA has also been used
to identify sources which may not be inventoried (Wolff and Korsog, 1985; Cheng et al.,
1988; Henry and Kim, 1989; Koutrakis and Spengler, 1987; Zeng and Hopke, 1989).
The PCA procedure as outlined above provides only a qualitative assessment of air
pollution sources. In some circumstances, however, the procedure can be extended to
produce quantitative estimates of the source impacts. For example, a chemical species
strongly associated with a single PCA group may be suitable as a source tracer for use in a
subsequent multiple linear regression receptor model (Kleinman et al., 1980)
The Empirical Orthogonal Function (EOF) receptor model is applied to a spatially
dense network of measurements to identify the locations of emissions sources and to
estimate the net fluxes (emissions minus deposition) of those pollutants. The EOFs
manifest themselves as isopleth maps of flux density. When a major point source is the
emitter, such as a coal-fired power plant, the EOFs have been shown (Gebhardt et al.,
1990) to surround that source. EOFs have been applied to air pollution measurements by
Peterson (1970), Ashbaugh et al. (1984), Wolff et al. (1985b), and Henry et al. (1990).
Henry et al. (1990) were the first researchers to place this method 6n a firm theoretical
foundation and to demonstrate that EOFs reproduce the net fluxes used as input to a
dispersion model.
5-56
-------
In prior studies, the EOF model was applied to single chemical constituents, such as
sulfur dioxide, sulfate, and total particulate mass concentrations. In a recent study (Watson
et al., 1991), the EOF model was applied to the source contribution estimates calculated for
each sample from the CMB modeling described above. In this way, source-type specific
patterns of net flux were determined. For example, the geological source contributions may
be represented as a linear sum of EOFs which correspond to a dirt road, a construction site,
and an area of intense agricultural activity. The motor vehicle exhaust source contributions
may be represented by a linear sum of EOFs which correspond to a major highway, a large
truck stop, or an urban core area. The EOF model may also be applied to specific chemical
species which are identified as potential markers for uninventoried sources.
The EOF procedure is similar to the PC A procedure: (1) select the source contribution
estimates and measurement cases to be included; (2) calculate the covariance coefficients
between the species measured at the same time at several sites; (3) calculate the
eigenvectors and eigenvalues of the covariance matrix; (4) select eigenvectors to be
retained; (5) rotate these eigenvectors into a more physically meaningful space; and
(6) interpolate between the values of these eigenvectors to supply the net flux patterns. The
main difference between PCA and EOF is that PCA operates on many samples from a
single site taken over an extended time period, while EOF operates on many samples from
many sites taken over a single time period.
The formulation of Henry et al. (1990), termed Source Identification Through
Empirical Orthogonal Functions (SITEOF), uses wind velocities as input in addition to the
spatially distributed source contribution estimates. The SITEOF assumptions are: (1) net
fluxes of spatially-distributed pollutants add linearly; (2) pollutants are homogeneously
distributed vertically in the mixed layer; (3) measurement errors are random and
uncorrelated; (4) the number of sampling sites exceeds the number of source locations to an
extent that statistical stability is achieved; and (5) measurement locations are located in
positions to maximize spatial gradients from major source emissions. The major unknown
concerning the SITEOF model is the extent to which assumptions 4 and 5 can be met in
actual practice. Motor vehicle exhaust is confined to specific areas (e.g., roads and parking
lots), and it is a straightforward task to locate monitors close to and far from these known
locations. Fugitive dust, on the other hand, can be emitted from many locations.
5-57
-------
The SITEOF model is one of a class of procedures referred to as "hybrid receptor
models". Such models make use of not only the ambient species concentration
measurements that form the input data for a pure receptor model, but in addition source
emission rates or atmospheric dispersion or transformation information characteristic of
dispersion models. By exploiting simultaneously the strengths of the two complementary
approaches their individual weaknesses should be minimized. A survey of hybrid receptor
models is available (Lewis and Stevens, 1987).
Ashbaugh et al., (1985) developed the concept of the potential source contribution
function (PSCF) for performing the apportionment of secondary species, for combining air
parcel back trajectories from a receptor site with chemical data at the site to infer possible
source locations. The PSCF is an estimate of the conditional probability that a trajectory
which passed through a given cell in the emissions grid (g-) contributed a concentration
greater than some threshold value to ambient concentrations at the receptor site. Gao et al.
(1993) extended the PSCF analysis to provide an apportionment of secondary species. By
multiplying the PSCF by the emissions rate in g^, an estimate of the maximum contribution
of sources in gy to the concentrations measured at the receptor site is obtained. Further
research is needed to quantify the uncertainties associated with this method. These
uncertainties are related to unidentified sources, background sources, emissions estimates at
the time of calculation, the differential loss of species (e.g., by deposition), and mixing of
air parcels from different cells during transit from source to receptor. Gao et al. (1993)
have applied PSCF's along with emissions estimates to the apportionment of SO2 and SO4=
at sites in the South Coast Air Basin, and Cheng et al. (1996) have also applied this
technique to the apportionment of NOX and NH3 in this area.
The use of 14C isotopic analysis has been used to distinguish between fossil fuel and
biomass sources of carbon in aerosol samples. An example would be to determine the
fraction of ambient aerosol mass concentration in wintertime samples originating from
woodburning. This method has been particularly useful in validating less expensive
receptor methods of achieving the same goal (Wolff et al., 1981; Lewis et al., 1988).
The preceding sections have dealt with receptor models that rely on chemical
information obtained from bulk samples. It is worth noting that in addition there are
powerful receptor modeling methods which also use the morphology and composition of
5-58
-------
individual particles to provide clues to their source origin (Dzubay and Mamane, 1989).
Scanning electron microscopy (SEM) along with energy dispersive X-ray analysis (EDX)
has allowed the size distribution of particles to be characterized according to shape and
elemental composition. This technique has proven to be extremely useful for distinguishing
between fly ash and soil derived particles; both types of particles have similar composition,
but fly ash particles are spherical while soil particles are irregularly shaped.
Manually performing SEM/EDX analyses of the large number individual particles
necessary to characterize a size distribution is extremely time consuming. Automated
methods have been developed for the rapid characterization of the shapes of hundreds of
particles in aerosol samples (Xie et al., 1994a, 1994b). The morphology data can then be
used along with EDX data to assign particles to clusters related to specific source types
(Van Espen, 1984).
5.5.3 Source Contributions to Ambient Particles Derived by Receptor
Models
Receptor modeling has been used for obtaining information about the nature of
sources of ambient aerosol samples. The results of several studies will be discussed to
provide an indication of different sources of particulate matter across the United States.
First, results obtained by using the CMB approach for estimating contributions to PM2 5 and
PM(10_2 5) from different source categories at monitoring sites in the United States east of
the Mississippi River will be discussed. Estimated contributions from a number of source
categories to PM10 in ambient samples, obtained mainly at sites west of the Mississippi
River, will then be discussed.
Dzubay et al. (1988) estimated source category contributions to 24-hour PM25 and
PM/jQ.25) samples obtained by a dichotomous sampler at three widely separated sites in the
Philadelphia, PA area (NE airport in Philadelphia, PA; Camden, NJ; and a site about 30 km
to the SW of Camden, NJ) during the summer of 1982. They used a composite of CMB,
multiple linear regression (MLR), and wind trajectory receptor models. Source
compositions shown in Table 5-3 were obtained partly to provide input to this study (Olmez
et al., 1988). Ambient concentrations of individual species used by Dzubay et al. (1988)
are shown in Table 6A-2a (Chapter 6, Appendix A). Sulfate, associated NH4+ and water
5-59
-------
constituted about 70% of PM2 5. Since the mean fractional abundances of PM2 5 to PM10
was 0.75, it can be seen that sulfate components contributed approximately 53% of PM10. Coal-
and oil-fired power plants located east of the Mississippi River were found to contribute
50 ± 6% and 11 ± 4% of PM2 5, by using Se as a tracer for coal combustion and V and Ni
as tracers for oil combustion, based on an MLR analysis.
The study was performed during a period (summer of 1982) when the Pb content of
gasoline was declining markedly, and so Pb could not be used as a unique tracer of motor
vehicle emissions. CMB was used to determine nonvehicular Pb, which was subtracted
from the measured Pb concentration to yield a tracer for vehicle exhaust. Motor vehicle
exhaust was then found to contribute about 8%, on average, to PM2 5. Local sources of
sulfate (determined from the MLR intercept) were found to contribute 13%, on average,
with smaller contributions from local industrial sources, incinerators, and crustal matter to
PM2.5.
Crustal matter constituted about 76%, on average, of PM^10.2 5). Sulfate and
associated NH4+ and water constituted only about 7% of PM/10_2 5y Other contributions to
PM,10_2 5) were found to arise from sea-salt and incinerators. In a study of the Philadelphia
aerosol in the summer of 1994, Pinto et al. (1995) found close agreement with Dzubay et
al. (1988) both in measured concentrations and in the magnitude of the inferred fractional
contribution of regional sulfate sources.
Glover et al. (1991) estimated the contributions of different source categories to
24-hour PM2 5 and PM(10_2 5-> samples obtained with a dichotomous sampler at a site in
Granite City, IL. Again, sulfate was the major constituent of PM25, constituting from
59% of PM2 5 with SSW winds to 86.6% of PM2 5 with NNW winds. Inferred
contributions from specific source types were also shown to be strongly dependent on wind
direction. Inferred contributions from iron works ranged from 3.4% with NNW winds to
16.4% with SSE winds. Inferred contributions from a Pb smelter ranged from 2.8% with
WNW winds to 11.6% with SSW winds. Inferred contributions from other sources (e.g.,
motor vehicles, incinerators, other smelters, and soil) were all typically a few per cent.
Sulfate was a relatively minor constituent (< 10%) of PM(10_25) samples. Major
inferred contributions were from iron works, ranging from 5.7% with WNW winds to
53.8% with ENE winds; soil, ranging from 4.2% with WSW winds to 35.8% with ESE
5-60
-------
winds; street dust, ranging from 1.4% SSE winds to 45.6% with WNW winds; with
generally smaller contributions from the other sources listed for PM25.
These results demonstrate the different nature of PM2 5 and PM,10_2 5) sources
(i.e., PM25 was derived from regional sources, while PM^]0.25^ was derived from local
industries); the utility of wind sectoring to help locate sources; and the need to obtain
site-specific source composition profiles. The use of site-specific source profiles instead of
profiles culled from the literature resulted in decreases in predicted error values, especially
for fugitive dust.
Results obtained at a number of monitoring sites in the central and western United
States obtained by using the CMB model are shown in Table 5-12 for PM10. The sampling
sites represent a variety of different source characteristics within different regions of
Arizona, California, Colorado, Idaho, Illinois, Nevada and Ohio. Several of these are
background sites, specifically Estrella Park, Gunnery Range, Pinnacle Peak, and Corona de
Tucson, AZ, and San Nicolas Island, CA. Definitions of source categories also vary from
study to study. In spite of these differences, several features can be observed from the
values in this table.
Fugitive dust (geological material) from roads, agriculture and erosion appears as a
highly variable contributor to PM10 at nearly all sampling sites shown in Table 5-12,
contributing about 40% of the average PM10 mass concentration. The average fugitive dust
source contribution is highly variable among sampling sites within the same urban areas, as
seen by differences between the Central Phoenix (33 /ig/m3) and Scottsdale (25 /^g/m3) sites
in Arizona, and it is also seasonally variable, as evidenced by the summer and fall
contributions at Rubidoux, CA. These studies found that the source profiles for fugitive
dust were chemically similar, even though the dust came from different emitters, so that
further apportionment into sub-categories was not possible by the CMB model alone. Road
sand often contains salts that allow it to be distinguished from other fugitive dust sources.
It is usually the only exposed fugitive dust source when other sources are covered by
snowpack. Dust from some construction activities and cement plants can also be separated
from other sources due to enrichments in calcium content of these emissions, as seen in
studies at Rubidoux, CA, Rillito, AZ (near cement plants), and Pocatello, ID (near chemical
and fertilizer production plants).
5-61
-------
TABLE 5-12. RECEPTOR MODEL SOURCE CONTRIBUTIONS TO PM
10
ftg/m3
Sampling Site
Central Phoenix, AZ (Chow et al., 1991)
Craycroft, AZ (Chow et al., 1992a)
Hayden 1, AZ (Garfield) (Ryan et al., 1988)
Hayden2, AZ (Jail) (Ryan et al., 1988)
Phoenix, AZ (Estrella Park) (Chow et al., 1991)
Phoenix, AZ (Gunnery Rg-) (Chow et al., 1991)
Phoenix, AX (Pinnacle Pk.) (Chow et al., 1991)
Rillito, AZ (Thanukoset al., 1992)
Scottsdale, AZ (Chow et al., 1991)
West Phoenix, AZ (Chow et al., 1991)
Bakersfield, CA (Magliano, 1988)
Bakerfield, CA (Chow et al., 1992b)
Oi
OS Crows Landing, CA (Chow et al., 1992b)
10 Fellows, CA (Chow et al., 1992b)
Fresno, CA (Magliano, 1988)
Fresno, CA (Chow et al., 1992b)
Indio, CA (Kim et al., 1992)
Kern Wildlife Refuge, CA (Chow et al., 1992b)
Long Beach, CA (Gray et al., 1988)
Long Beach, CA (Summer) (Watson et al., 1994b)
Long Beach, CA (Fall) (Watson et al., 1994b)
Riverside, CA (Chow et al., 1992c)
Rubidoux, CA (Gray et al., 1988)
Rubidoux, CA (Summer) (Watson et al., 1994b)
Rubidoux, CA (Fall) (Watson et al., 1994b)
Rubidoux, CA (Chow et al., 1992c)
San Nicolas Island, CA (Summer) (Watson et al.,
1994b)
Primary
Time Period Geological
Winter 1989-1990
Winter 1989-1990
1986
1986
Winter 1989-1990
Winter 1989-1990
Winter 1989-1990
1988
Winter 1989-1990
Winter 1989-1990
1986
1988-1989
1988-1989
1988-1989
1986
1988-1989
1988-1989
1986
Summer 1987
Fall 1987
1988
1986
Summer 1987
Fall 1987
1988
Summer 1987
33.0
13.0
5.0
21.0
37.0
20.0
7.0
42.7
25.0
30.0
27.4
42.9
32.2
29.0
17.1
31.8
33.0
15.1
20.7
11.1
11.3
32.6
43.1
34.9
19.2
48.0
1.6
Primary
Motor
Primary Vehicle
Construction Exhaust
0.0
0.0
2.0b
4.0"
0.0
0.0
0.0
13.8b
0.0
0.0
3.0
1.6
0.0
1.4
0.7
0.0
3.0
2.0
0.0
0.0
0.0
0.0
4.0J
4.5
16.1
0.0
0.0
25.0
8.3
0.0
0.0
10.0
5.5
2.9
1.2f
19.0
25.0
5.5
7.7
2.2
2.1
4,0
6.8
4.4
2.2
5.11
6.3
42.8
7.0
5.61
17.3
30.3
10.2
0.9
Primary
Vegetative
Burning
2.3
0.0
0.0
0.0
0.9
0.0
1.0
0.0
7.4
10.0
9.61
6.5
3.4
3.4
9.2'
5.1
7.1
4.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Secondary
Ammonium
Sulfate
0.2
0.7
4.0
4.0
1.6
1.0
0.9
0.0
0.6
0.4
5.6
5.5
2.8
5.1
1.8
3.6
3.6
3.3
8.0
10.9
3.8
4.8
6.4
9.5
2.1
5.3
3.7
Secondary Misc.
Ammonium Source
Nitrate 1
2.8
0.6
0.0
0.0
0.0
0.0
0.0
0.0
3.6
3.1
0.0
12.7
6.5
7.5
0.0
10.4
4.1
1.5
9.2
0.8
23.2
21.4
21.3
27.4
31.6
21.7
0.5
0.0
1.2'
74.0C
28.0C
0.0
0.0
0.0
11.6s
0.0
0.0
0.5J
1.0m
0.5m
7.0m
0.1'
0.3m
0.2J
0.5m
0.1J
0.1J
0.0)
0.3J
0.3J
0.0>
0.0*
0.4>
0.0)
Misc.
Source
2
0.0
0.0
5.0"
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.5"
1.5"
1.4"
0.0
1.0"
1.0"
1.5"
2.0h
2.2h
2.7h
1.3"
1.0h
5.1h
1.1"
1.5"
4.3h
Misc. Misc.
Source Source
3 4
0.0
0.0
1.0"
1.0"
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.6k
1.2"
1.4"
0.0
O.lk
0.0
0.7k
6.4"
0.0
0.0
1.1°
5.9k
0.0
0.0
5.7°
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Measured
PM10
Concentration
64.0
23.4
105.0
59.0
55.0
27.0
12.0
79.5
55.0
69.0
67.6
79.6
52.5
54.6
48.1
71.5
58.0
47.8
51.9
46.1
96.1
64.0
87.4
114.8
112.0
87.0
17.4
-------
TABLE 5-12 (cont'd). RECEPTOR MODEL SOURCE CONTRIBUTIONS TO PM10
/ig/m3
Sampling Site
Stockton, CA (Chow et al., 1992b)
Pocatello, ID (Houcketal., 1992)
S. Chicago, IL (Hopke et al., 1988)
S.E. Chicago, IL (Vermette et al., 1992)
Reno, NV (Chow et al., 1988)
Sparks, NV (Chow et al., 1988)
Follansbee, WV (Skidmore et al., 1992)
Mingo, OH (Skidmore et al., 1992)
Steubenville, OH (Skidmore et al., 1992)
Time Period
1989
1990
1986
1988
1986-1987
1986-1987
1991
1991
1991
Primary
Geological
34.4
8.3
27.2
14.7V
14.9
15.1
10.0
12.0
8.3
Primary
Construction
0.5
7.51
2.4
0.0
0.0
0.0
0.0
0.0
0.0
Primary
Motor
Vehicle
Exhaust
5.2
0.1
2.8
0.9f
10.0
11.6
35.0
14.0
14.0
Primary
Vegetative
Burning
4.8
0.0
0.0
0.0
1.9
13.4
0.0
4.1
0.8
Secondary
Ammonium
Sulfate
3.1
0.0
15.4s
7.7
1.3
2.7
16.0
15.0
14.0
Secondary
Ammonium
Nitrate
7.0
0.0
__
-
0.6
0.9
—
-
-
Misc.
Source
1
0.7m
0.0
15.1'
0.8'
0.0
0.0
9.3'
3.4'
3.8'
Misc.
Source
2
1.8"
0.0
2.2"
0.3h
0.0
0.0
0.0
11.0"
5.0*
Misc.
Source
3
0.0k
84. lr
0.0
1.1"
0.0
0.2k
0.0
0.0
0.0
Misc.
Source
4
0.0
0.0
0.0
7.78
0.0
0.0
0.0
0.0
0.0
Measured
PM10
Concentration
62.4
100.0
80.1
41.0
30.0
41.0
66.0
60.0
46.0
"Smelter background aerosol.
bCement plant sources, including kiln stacks, gypsum pile, and kiln area.
cCopper ore.
dCopper tailings.
'Copper smelter building.
fHeavy-duty diesel exhaust emission.
8Background aerosol.
hMarine aerosol, road salt, and sea salt plus sodium nitrate.
'Motor vehicle exhaust from diesel and leaded gasoline.
JResidual oil combustion.
Secondary organic carbon.
'Biomass burning.
""Primary crude oil.
"NaCl + NaN03.
"Lime.
PRoad sanding material.
qAsphalt industry.
'Phosphorus/phosphate industry.
'Regional sulfate.
'Steel mills.
"Refuse incinerator.
"Local road dust, coal yard road dust, steel haul road dust.
"Incineration.
Unexplained mass.
-------
Dust sources constitute 88% of the annual average PM10 National Emissions Inventory
(U.S. Environmental Protection Agency, 1994), but they average more than 50% of the
contribution to average PM]0 concentrations in only about 40% of the entries shown in
Table 5-12. The reasons for this apparent discrepancy are not clear. In addition to errors
in inventories or source apportionments, weather-related factors (wind speed and ground
wetness) and the dominance of local sources on spatial scales too small to be captured in
inventories may be involved. It should be remembered that dust emissions are widely
dispersed and highly sporadic. Dust particles also have short atmospheric residence times
and as a result their dominance in emissions inventories may not be reflected in samples
collected near specific sources. The contributions from primary motor vehicle exhaust,
residential wood combustion, and industrial sources would be underestimated if values from
the National Emissions Inventory Trends data base (U.S. Environmental Protection Agency,
1994) were used. Some of these deficiencies, such as fugitive dust emissions, are probably
intractable, and the best that can be done is to estimate the uncertainties in these emissions
and to value the data accordingly when decisions are made.
In Table 5-12, primary motor vehicle exhaust contributions account for up to 40% of
average PM10 at many of the sampling sites. Vehicle exhaust contributions are also
variable at different sites within the same study area. The mean value and the variability of
motor vehicle exhaust contributions reflects the proximity of sampling sites to roadways
and traffic conditions during the time of sampling. Vegetation burning, which includes
agricultural fires, wildfires, prescribed burning, and residential wood combustion, was found
to be significant at residential sampling sites such as: Craycroft, Scottsdale, and West
Phoenix, AZ; Fresno, Bakersfield, and Stockton, CA; Sparks, NV; and Mingo, OH. The
predominance of these contributions during winter months and the local rather than regional
coverage indicates that residential wood combustion was the major sub-category, even
though chemical profiles are too similar to separate residential combustion from other
vegetative burning sources. For example, Chow et al. (1988) show substantial differences
between the residential Sparks, NV and urban-commercial Reno, NV burning contributions
even though these sites are separated by less than 10 km. Sites near documented industrial
activity show evidence of that activity, but not necessarily involving primary particles
emitted by point sources. Hayden, AZ, for example, contains a large smelter, but the major
5-64
-------
smelter contributions appear to arise from fugitive emissions of copper tailings rather than
stack emissions. Secondary sulfate contributions at Hayden were low, even though SO2
emissions from the stack were substantial during the time of the study. Fellows, CA is in
the midst of oilfield facilities that burn crude oil for tertiary oil extraction. These have
been converted to natural gas since the 1988 to 1989 study period. The Follansbee, WV,
Mingo, OH, and Steubenville, OH sites are all close to each other in the Ohio River Valley
and show evidence of the widespread steel mill emissions in that area.
Marine aerosol is found, as expected, at coastal sites such as Long Beach (average
3.8% of total mass), and San Nicolas Island (25%). These contributions are relatively
variable and are larger at the more remote sites. Individual values reflect proximity to local
sources. Of great importance are the contributions from secondary ammonium sulfate and
ammonium nitrate in the western United States. These are especially noticeable at sites in
California's San Joaquin Valley (Bakersfield, Crows Landing, Fellows, Fresno, Kern
Wildlife, and Stockton) and in the Los Angeles area.
In addition to these commonly measured components, it is possible that isotopic ratios
in source emissions may vary in an informative way with the nature of the combustion
process and with the geologic age and character of the source input material. Carbon-14,
for example, has been used to separate contemporary carbon due to vegetative burning from
carbon emitted by fossil fuel combustion (Currie et al., 1984). Organic compounds (Rogge
et al., 1991, 1993a, 1993b, 1993c, 1993d, 1993e; Lowenthal et al., 1994; Hildemann et al.,
1991, 1993) show great promise for further differentiation among sources, but measurement
methods need to be standardized and made more cost-effective to take advantage of
extended chemical source profiles.
Several aspects of the data in Table 5-12 limit the generalizations that can be drawn
from it:
• The source contribution estimates for the receptor sites shown are for different years
and different times of year. The results, therefore, do not show the temporal
variability which may exist in relative source contributions and should not be used
to infer differences between sites.
• Samples selected for chemical analysis are often biased toward the highest PM10
mass concentrations in these studies, so average source contribution estimates are
probably not representative of annual averages.
5-65
-------
Many studies were conducted during the late 1980s, when a portion of the vehicle
fleet still used leaded gasoline. While the lead and bromine in motor vehicle
emissions facilitated the distinction of motor vehicle contributions from other
sources, it was also associated with higher emission rates than vehicles using
unleaded fuels. Lead has been virtually eliminated from vehicle fuels.
Uncertainties of source contribution estimates are not usually reported with the
average values summarized in Table 5-12. Estimates of standard errors are
calculated in source apportionment studies, and typically range from 15 to 30% of
the source contribution estimate. They are much higher when the chemical source
profiles for different sources are highly uncertain or too similar to distinguish one
source from another.
Different measurement sites within the same airshed show different proportions of
contributions from the same sources. Most often, the sites in close proximity to an
emitter show a much larger contribution from that emitter than sites that are distant
from that emitter, even by distances as short as 10 km (e.g., Chow et al., 1988;
1992c).
Given the mass, trace element, ion, and carbon components measured in source and
receptor samples in most of the studies from Table 5-12, greater differentiation
among sources (e.g., diesel and gasoline vehicle exhaust, meat cooking and other
organic carbon sources, different sources of fugitive dust, and secondary aerosol
precursors) is not possible for the studies shown in Table 5-12.
5.6 SUMMARY AND CONCLUSIONS
Ambient particulate matter contains both primary and secondary components. Due to
the complexity of the composition of ambient PM10, sources are best discussed in terms of
individual constituents of both primary and secondary PM10. Each of these constituents can
have anthropogenic and natural sources, as shown in Tables 5-1A and 5-IB. The
distinction between natural and anthropogenic sources is not always obvious. While
windblown dust might seem to be the result of natural processes, highest emission rates are
associated with agricultural activities in areas that are susceptible to periodic drought.
Examples include the dust bowl region of the midwestern United States and the Sahel of
Africa. Most forest fires in the United States may ultimately be of human origin, either
through prescribed burning or accident.
Windblown dust from whatever source represents the largest single source of PM in
U.S. and global emissions inventories. Although dust emissions (88% of total U.S. PM10)
5-66
-------
are far in excess of any other source of primary or secondary PM10 in any region of the
country, measurements of soil constituents in ambient samples suggest that the overall
contribution from this source could be much lower. The reasons for this apparent
discrepancy are not clear. In addition to errors in inventories or source apportionments,
weather-related factors (wind speed and ground wetness) and the dominance of local
sources on spatial scales too small to be captured in inventories may be involved. It should
be remembered that dust emissions are widely dispersed and highly sporadic. Dust particles
also have short atmospheric residence times and, as a result, their dominance in emissions
inventories may not be reflected in samples collected near specific sources.
There is a great deal of spatial and temporal variability which is still not reflected in
emissions inventories. Apart from seasonal variability, many of the sources discussed in
this chapter are highly episodic even within their peak emissions seasons. Examples
include the long-range transport of Saharan dust to the United States, regional dust storms,
volcanism, and forest fires. Their spatial variability is also evident. Annual estimates for
an area can easily be exceeded in a few days by unusual events involving these sources.
Less dramatic examples of strong seasonal variability, such as wood burned for home
heating in the northwestern United States, may be the major source of winter PM there.
It might be thought that enough data are available to adequately characterize mobile
and stationary source emissions. However, data characterizing the variability of PM
emissions from mobile sources are quite sparse. Available data suggest that elemental
carbon followed by organic carbon species are the major components of diesel particulate
emissions, while organic carbon emissions are larger than elemental carbon emissions in the
case of gasoline fueled vehicles.
Emissions from biomass burning are also composed mainly of organic carbon species
and elemental carbon, although the ratio of organic carbon to elemental carbon is much
higher than in motor vehicle emissions. Power plant emissions are not significant sources
of aerosol carbon. The fractional yield of secondary organic carbon from the oxidation of
natural and anthropogenic hydrocarbons is highly uncertain. Yields from the oxidation of
anthropogenic hydrocarbons are probably less than a few percent, and larger yields are
found in the oxidation of terpenes emitted by vegetation.
5-67
-------
As seen in Table 5-IB, emissions of surface dust, organic debris, and sea spray are
concentrated mainly in the coarse fraction of PM10 ( > 2.5 urn aero. diam.). A small
fraction of this material is in the PM25 size range ( < 2.5 urn aero, diam., c.f. Figure 5-1).
Nevertheless, concentrations of crustal material can be appreciable especially during dust
events. It should also be remembered that all of the Saharan dust reaching the United
States is in the PM2 5 size range. Emissions from combustion sources (mobile and
stationary sources, biomass burning) are predominantly in the PM2 5 size range.
As shown in Table 5-6, estimated primary PM10 emissions decreased by about 10%
from 1985 through 1993. A high degree of variability is evident for emissions from
miscellaneous (fugitive dust, biomass burning, and agriculture) and natural (wind erosion of
natural surfaces) categories shown in Table 5-7. Estimated SO2 emissions decreased by
several per cent from 1984 through 1993 as shown in Table 5-8. Estimated emissions of
NOX show little variation over the same time period as shown in Table 5-9. Emissions of
primary PM10 are projected to increase to the year 2010 mainly because of increases in
fugitive dust emissions, while emissions of SO2 and NOX are expected to decrease over the
same time period.
Uncertainties in emissions inventories are difficult to quantify. They may be as low
as 10% for well-defined sources (e.g., for SO2) and may range up to a factor of 10 or so
for windblown dust. As a rule, total PM emissions rates should be regarded as
order-of-magnitude estimates. Because of the large uncertainty associated with emissions
of suspended dust, trends of total PM10 emissions should be viewed with caution and
emissions from specific source categories are best discussed on an individual basis.
Emissions inventories are generally not the most appropriate way to apportion material
in ambient samples. Receptor modeling has proven to be an especially valuable tool in this
regard. Compositional profiles developed for receptor modeling applications are perhaps
the most accessible and reliable means to characterize the composition of emissions.
Quoted uncertainties in source apportionments of constituents in ambient aerosol samples
typically range from 15 to 30%. Receptor modeling studies in the western United States
have found that motor vehicles and fugitive dust are major sources of PM10. Likewise, a
limited number of studies in the eastern United States have found that fossil fuel
combustion and fugitive dust are major sources of PM10. Techniques are currently being
5-68
-------
developed to use receptor modeling techniques along with ambient data to refine emissions
inventory estimates. Because of the site-specific nature of receptor modeling results, more
rigorous methods for determining site locations and methods for applying receptor model
results to larger spatial scales are needed for this purpose. Again, it should be emphasized
that, because of limitations in receptor modeling methods in treating secondary components,
these efforts are more likely to be successful for primary components, although it should be
mentioned that methods are being developed to apportion secondary constituents.
5-69
-------
REFERENCES
Alfaro, S. C.; Gomes, L. (1995) Improving the large-scale modeling of the saltation flux of soil particles in
presence of nonerodible elements. J. Geophys. Res. [Atmos.] 100: 16,357-16,366.
Altshuller, A. P. (1983) Review: natural volatile organic substances and their effect on air quality in the United
States. Atmos. Environ. 17: 2131-2165.
Altshuller, A. P.; Bufalini, J. J. (1965) Photochemical aspects of air pollution: a review. Photochem. Photobiol.
4: 97-146.
Andreae, M. 0. (1991) Biomass burning: its history, use, and distribution and its impact on environmental
quality and global climate. In: Levine, J. S., ed. Global biomass burning: atmospheric, climatic,
and biospheric implications. Cambridge, MA: MIT Press; pp. 1-21.
Ashbaugh, L. L.; Myrup, L. O.; Flocchini, R. G. (1984) A principal component analysis of sulfur concentrations
in the western United States. Atmos. Environ. 18: 783-791.
Ashbaugh, L. L.; Malm, W. C.; Sadeh, W. Z. (1985) A residence time probability analysis of sulfur
concentrations at Grand Canyon National Park. Atmos. Environ. 19: 1263-1270.
Bagnold, R. A. (1941) The physics of blown sand and desert dunes. London, United Kingdom: Methuen & Co.
Behymer, T. D.; Hites, R. A. (1984) Similarity of some organic compounds in spark-ignition and diesel engine
paniculate extracts. Environ. Sci. Technol. 18: 203-206.
Belly, P.-Y. (1964) Sand movement by wind. Washington, DC: U.S. Army Corps of Engineers, Coastal
Engineering Research Center; technical memorandum no. 1.
Bisal, F.; Hsieh, J. (1966) Influence of moisture on erodibility of soil by wind. Soil Sci. 102: 143-146.
Brown, M. (1993) Deduction of emissions of source gases using an objective inversion algorithm and a chemical
transport model. J. Geophys. Res. [Atmos.] 98: 12,639-12,660.
Calvert, J. G.; Heywood, J. B.; Sawyer, R. F.; Seinfeld, J. H. (1993) Achieving acceptable air quality: some
reflections on controlling vehicle emissions. Science 261: 37-45.
Cheng, M.-D.; Lioy, P. J.; Opperman, A. J. (1988) Resolving PM 10 data collected in New Jersey by various
multivariate analysis techniques. In: Mathai, C. V.; Stonefield, D. H., eds. PM-10: implementation of
standards, an APCA/EPA international specialty conference; February; San Francisco, CA. Pittsburgh,
PA: Air Pollution Control Association; pp. 472-483. (APCA transactions series TR-13).
Cheng, M.-D.; Gao, N.; Hopke, P. K. (1996) Source apportionment study of nitrogen species measured in
sourthern California in 1987. J. Environ. Eng. (N. Y.) 122: in press.
Chepil, W. S. (1945) Dynamics of wind erosion. Soil Sci. 60: 305-320.
Chepil, W. S. (1956) Influence of moisture on erodibility of soil by wind. Soil Sci. Soc. Am. Proc. 20: 288-292.
Chow, J. C.; Watson, J. G.; Frazier, C. A.; Egami, R. T.; Goodrich, A.; Ralph, C. (1988) Spatial and
temporal source contributions to PM10 and PM2 5 in Reno, NV. In: Mathai, C. V.; Stonefield, D. H.,
eds. PM-10: implementation of standards, an APCA/EPA international specialty conference; February;
San Francisco, CA. Pittsburgh, PA: Air Pollution Control Association; pp. 438-457. (APCA transactions
series TR-13).
5-70
-------
Chow, J. C.; Watson, J. G.; Richards, L. W.; Haase, D. L.; McDade, C.; Dietrich, D. L.; Moon, D.;
Sloane, C. (1991) The 1989-90 Phoenix PMi0 study, v. II: source apportionment [final report].
Phoenix, AZ: Arizona Department of Environmental Quality; report no. 8931.6F1; Table 3-1.
Chow, J. C.; Watson, J. G.; Lowenthal, D. H.; Frazier, C. A.; Hinsvark, B. A.; Prichett, L. C.;
Neuroth, G. R. (1992a) Wintertime PMi0 and PM2 5 chemical compositions and source contributions
in Tucson, Arizona. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional paniculate
source controls, an A&WMA/EPA international specialty conference, v. I; January; Scottsdale, AZ.
Pittsburgh, PA: Air & Waste Management Association; pp. 231-243. (A&WMA transactions series
no. 22).
Chow, J. C.; Watson, J. G.; Lowenthal, D. H.; Solomon, P. A.; Magliano, K. L.; Ziman, S. D.;
Richards, L. W. (1992b) PM10 source apportionment in California's San Joaquin Valley.
Atmos. Environ. Part A 26: 3335-3354.
Chow, J. C.; Liu, C. S.; Cassmassi, J.; Watson, J. G.; Lu, Z.; Pritchett, L. C. (1992c) A neighborhood-scale
study of PM10 source contributions in Rubidoux, California. Atmos. Environ. Part A 26: 693-706.
Chow, J. C.; Watson, J. G.; Houck, J. E.; Pritchett, L. C.; Rogers, C. F.; Frazier, C. A.; Egami, R. T.;
Ball, B. M. (1994) A laboratory resuspension chamber to measure fugitive dust size distributions
and chemical compositions. Atmos. Environ. 28: 3463-3481.
Cofer, W. R.; Levine, J. S.; Sebacher, D. I.; Winstead, E. L.; Riggan, P. J.; Brass, J. A.; Ambrosia, V. G.
(1988) J. Geophys. Res. [Atmos.] 93: 5207-5212.
Cooper, J. A.; Watson, J. G., Jr. (1980) Receptor oriented methods of air paniculate source apportionment.
J. Air Pollut. Control Assoc. 30: 1116-1125.
Cooper, J. A.; Redline, D. C.; Sherman, J. R.; Valdovinos, L. M.; Pollard, W. L.; Scavone, L. C.;
Badgett-West, C. (1987) PM10 source composition library for the South Coast Air Basin: volume I,
source profile development documentation final report. El Monte, CA: South Coast Air Quality
Management District; July 15.
Currie, L. D.; Gerlach, R. W.; Lewis, C. W.; Balfour, W. D.; Cooper, J. A.; Dattner, S. L.; De Cesar, R. T.;
Gordon, G. E.; Heisler, S. L.; Hopke, P. K.; Shah, J. J.; Thurston, G. D.; Williamson, H. J. (1984)
Interlaboratory comparison of source apportionment procedures: results for simulated data sets.
Atmos. Environ. 18: 1517-1537.
Daisey, J. M.; Cheney, J. L.; Lioy, P. J. (1986) Profiles of organic paniculate emissions from air pollution
sources: status and needs for receptor source apportionment modeling. J. Air Pollut. Control Assoc.
36: 17-33.
Dasch, J. M. (1982) Paniculate and gaseous emissions from wood-burning fireplaces. Environ. Sci. Technol.
16: 639-645.
Dattner, S. L.; Hopke, P. K. (1982) Receptor models applied to contemporary pollution problems:
an introduction. In: Frederick, E. R., ed. A specialty conference on: receptor models applied to
contemporary pollution problems; October; Danvers, MA. Pittsburgh, PA: Air Pollution Control
Association; pp. 1-5. (APCA specialty conference proceedings SP-48).
Dentener, F. J.; Crutzen, P. J. (1994) A three-dimensional model of the global ammonia cycle. J. Atmos. Chem.
19: 331-369.
5-71
-------
Dzubay, T. G.; Mamane, Y. (1989) Use of electron microscopy data in receptor models for PM-10.
Atmos. Environ. 23: 467-476.
Dzubay, T. G.; Stevens, R. K.; Gordon, G. E.; Olmez, I.; Sheffield, A. E.; Courtney, W. J. (1988)
A composite receptor method applied to Philadelphia aerosol. Environ. Sci. Technol. 22: 46-52.
Federal Register. (1977) Method 5 - determination of paniculate emissions from stationary sources. F. R.
(August 18) 42: 41776-41783.
Freeman, D. L.; Chow, J. C.; Egami, R. T.; Watson, J. G. (1989) A receptor and dispersion modeling software
package. In: Watson, J. G., ed. Receptor models in air resources management: an international specialty
conference; February 1988; San Francisco, CA. Pittsburgh, PA: Air & Waste Management Association;
pp. 243-268. (APCA transactions series: no. 14).
Friedlander, S. K. (1973) Chemical element balances and identification of air pollution sources. Environ. Sci.
Technol. 7: 235-240.
Fujita, E. M.; Croes, B. E.; Bennett, C. L.; Lawson, D. R.; Lurmann, F. W.; Main, H. H. (1992) Comparison
of emission inventory and ambient concentration ratios of CO, NMOG, and NOX in California's south
coast air basin. J. Air Waste Manage. Assoc. 42: 264-276.
Gao, N.; Cheng, M.-D.; Hopke, P. K. (1993) Potential source contribution function analysis and source
apportionment of sulfur species measured at Rubidoux, CA during the Southern California Air Quality
Study, 1987. Anal. Chim. Acta 277: 369-380.
Gatz, D. F. (1995) A large silicon-aluminum aerosol plume in central Illinois: Saharan Desert dust?
Atmos. Environ.: accepted.
Gebhart, K. A.; Lattimer, D. A.; Sisler, J. F. (1990) Empirical orthogonal function analysis of the paniculate
sulfate concentrations measured during WHITEX. In: Mathai, C. V., ed. Visibility and fine particles:
an A&WMA/EPA international specialty conference; October 1989; Estes Park, CO. Pittsburgh, PA:
Air & Waste Management Association; pp. 860-871. (A&WMA transactions series no. TR-17).
Geron, C. D.; Guenther, A. B.; Pierce, T. E. (1994) An improved model for estimating emissions of volatile
organic compounds from forests in the eastern United States. J. Geophys. Res. [Atmos.]
99: 12,773-12,791.
Gillette, D. A.; Adams, J.; Endo, A.; Smith, D.; Kihl, R. (1980) Threshold velocities for input of soil particles
into the air by desert soils. J. Geophys. Res. C: Oceans Atmos. 85: 5621-5630.
Gillette, D. A.; Adams, J.; Muhs, D. R.; Khil, R. (1982) Threshold friction velocities and rupture moduli for
crusted desert soils for the input of soil particles into the air. J. Geophys. Res. B 87: 9003-9015.
Glover, D. M.; Hopke, P. K.; Vermette, S. J.; Landsberger, S.; D'Auben, D. R. (1991) Source apportionment
with site specific source profiles. J. Air Waste Manage. Assoc. 41: 294-305.
Goklany, I. M.; Hoffnagle, G. F.; Brackbill, E. A. (1984) Acidic and total primary sulfates: development of
emission factors for major stationary combustion sources. J. Air Pollut. Control Assoc. 34: 124-134.
Gordon, G. E. (1980) Receptor models. Environ. Sci. Technol. 14: 792-800.
Gordon, G. E. (1988) Receptor models. Environ. Sci. Technol. 22: 1132-1142.
5-72
-------
Gray, H. A.; Landry, B.; Liu, C. S.; Henry, R. C.; Cooper, J. A.; Sherman, J. R. (1988) Receptor modeling
for PM10 source apportionment in the South Coast Air Basin of California. In: Mathai, C. V.;
Stonefield, D. H., eds. PM-10: implementation of standards, an APCA/EPA international specialty
conference; February; San Francisco, CA. Pittsburgh, PA: Air Pollution Control Association;
pp. 399-418. (APCA transactions series TR-13).
Grosjean, D.; Seinfeld, J. H. (1989) Parameterization of the formation potential of secondary organic aerosols.
Atmos. Environ. 23: 1733-1747.
Haagen-Smit, A. J. (1952) Chemistry and physiology of Los Angeles smog. Ind. Eng. Chem. 44: 1342-1346.
Hall, F. F., Jr. (1981) Visibility reductions from soil dust in the western U.S. In: White, W. H.; Moore, D. J.;
Lodge, J. P., Jr., eds. Plumes and visibility: measurements and model components: proceedings of the
symposium; November 1980; Grand Canyon National Park, AZ. Atmos. Environ. 15: 1929-1933.
Hammerle, R. H.; Korniski, T. J.; Weir, J. E.; Chladek, E.; Glerczak, C. A.; Chase, R. E.; Hurley, R. G.
(1992) Effect of mileage accumulation on paniculate emissions from vehicles using gasoline with
methylcyclopentadienyl manganese tricarbonyl. Presented at: International congress & exposition;
February; Detroit, MI. Warrendale, PA: Society of Automotive Engineers; SAE technical paper
no. 920731.
Hansen, A. D. A.; Rosen, H. (1990) Individual measurements of the emission factor of aerosol black carbon in
automobile plumes. J. Air Waste Manage. Assoc. 40: 1654-1657.
Hatakeyama, S.; Izumi, K.; Fukuyama, T.; Akimoto, H. (1989) Reactions of ozone with a-pinene and /3-pinene
in air: yields of gaseous and paniculate products. J. Geophys. Res. [Atmos.] 94: 13,013-13,024.
Hatakeyama, S.; Izumi, K.; Fukuyama, T.; Akimoto, H.; Washida, N. (1991) Reactions of OH with a-pinene
and /3-pinene in air: estimate of global CO production from the atmospheric oxidation of terpenes.
J. Geophys. Res. [Atmos.] 96: 947-958.
Henry, R. C. (1991) Multivariate receptor models. In: Hopke, P. K., ed. Receptor modeling for air quality
management. Amsterdam, The Netherlands: Elsevier; pp. 117-147.
Henry, R. C.; Hidy, G. M. (1979) Multivariate analysis of paniculate sulfate and other air quality variables by
principal components—part I: annual data from Los Angeles and New York. Atmos. Environ.
13: 1581-1596.
Henry, R. C.; Hidy, G. M. (1982) Multivariate analysis of paniculate sulfate and other air quality variables by
principal components—II: Salt Lake City, Utah and St. Louis, Missouri. Atmos. Environ. 16: 929-943.
Henry, R. C.; Kim, B. M. (1989) A factor analysis receptor model with explicit physical constraints.
In: Watson, J. G., ed. Receptor models in air resources management: an international specialty
conference; February 1988; San Francisco, CA. Pittsburgh, PA: Air & Waste Management Association;
pp. 214-225. (APCA transactions series: no. 14).
Henry, R. C.; Wang, Y.-J.; Gebhart, K. A. (1990) The relationship between empirical orthogonal functions and
sources of air pollution. Atmos. Environ. Part A 24: 503-509.
Hertel, O.; Christensen, J.; Hov, 0, (1994) Modelling of the end products of the chemical decomposition of
DMS in the marine boundary layer. Atmos. Environ. 28: 2431-2449.
5-73
-------
Hildemann, L. M.; Markowski, G. R.; Jones, M. C.; Cass, G. R. (1991) Submicrometer aerosol mass
distributions of emissions from boilers, fireplaces, automobiles, diesel trucks, and meat-cooking
operations. Aerosol Sci. Technol. 14: 138-152.
Hildemann, L. M.; Cass, G. R.; Mazurek, M. A.; Simoneit, B. R. T. (1993) Mathematical modeling of urban
organic aerosol: properties measured by high-resolution gas chromatography. Environ. Sci. Technol.
27: 2045-2055.
Hooker, C. L.; Westberg, H. H.; Sheppard, J. C. (1985) Determination of carbon balances for smog chamber
terpene oxidation experiments using a 14C tracer technique. J. Atmos. Chem. 2: 307-320.
Hopke, P. K. (1985) Receptor modeling in environmental chemistry. New York, NY: John Wiley & Sons.
Hopke, P. K., ed. (1991) Receptor modeling for air quality management. New York, NY: Elsevier Science
Publishing Company, Inc. (Vandeginste, B. G. M.; Kvalheim, O. M., eds. Data handling in science
and technology: v. 7).
Hopke, P. K.; Lamb, R. E.; Natusch, D. F. S. (1980) Multielemental characterization of urban roadway dust.
Environ. Sci. Technol. 14: 164-172.
Hopke, P. K.; Wlaschin, W.; Landsberger, S.; Sweet, C.; Vermette, S. J. (1988) The source apportionment of
PM10 in south Chicago. In: Mathai, C. V.; Stonefield, D. H., eds. PM-10: implementation of standards,
an APCA/EPA international specialty conference; February; San Francisco, CA. Pittsburgh, PA: Air
Pollution Control Association; pp. 484-494. (APCA transactions series TR-13).
Houck, J. E.; Chow, J. C.; Watson, J. G.; Simons, C. A.; Pritchett, L. C.; Goulet, J. M.; Frazier, C. A.
(1989) Determination of particle size distribution and chemical composition of paniculate matter
from selected sources in California: volume I and executive summary (final report). Sacramento, CA:
California Air Resources Board.
Houck, J. E.; Goulet, J. M.; Chow, J. C.; Watson, J. G.; Pritchett, L. C. (1990) Chemical characterization of
emission sources contributing to light extinction. In: Mathai, C. V., ed. Visibility and fine particles:
an A&WMA/EPA international specialty conference; October 1989; Estes Park, CO. Pittsburgh, PA:
Air & Waste Management Association; pp. 437-446. (A&WMA transactions series no. TR-17).
Houck, J. E.; Rau, J. A.; Body, S.; Chow, J. C. (1992) Source apportionment: Pocatello, Idaho PM10
nonattainment area. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional paniculate
source controls, an A&WMA/EPA international specialty conference, v. I; January; Scottsdale, AZ.
Pittsburgh, PA: Air & Waste Management Association; pp. 219-230. (A&WMA transactions series
no. 22).
Huang, X.; Olmez, I.; Aras, N. K.; Gordon, G. E. (1994) Emissions of trace elements from motor vehicles:
potential marker elements and source composition profile. Atmos. Environ. 28: 1385-1391.
Ingalls, M. N. (1989) On-road vehicle emission factors from measurements in a Los Angeles area tunnel.
Presented at: 82nd annual meeting & exhibition of the Air and Waste Management Association; June;
Anaheim, CA. Pittsburgh, PA: Air and Waste Management Association; paper no. 89-137.3.
Intergovernmental Panel on Climate Change. (1995) Climate change 1995: the science of climate change: draft
summary for policymakers (SPM) of the draft contribution of Working Group I to the IPCC second
assessment report. Geneva, Switzerland: World Meteorological Association, IPCC Secretariat;
November.
5-74
-------
Izumi, K.; Fukuyama, T. (1990) Photochemical aerosol formation from aromatic hydrocarbons in the presence of
NOX. Atmos. Environ. Part A 24: 1433-1441.
Javitz, H. S.; Watson, J. G.; Guertin, J. P.; Mueller, P. K. (1988) Results of a receptor modeling feasibility
study. JAPCA 38: 661-667.
Johnson, J. H. (1988) Automotive emissions. In: Watson, A. Y.; Bates, R. R.; Kennedy, D., eds. Air pollution,
the automobile, and public health. Washington, D.C.: National Academy Press; pp. 39-76.
Johnson, B.; Cooke, R. C. (1979) Bubble populations and spectra in coastal waters: a photographic approach.
J. Geophys. Res. C: Oceans Atmos. 84: 3763-3766.
Kao, A. S.; Friedlander, S. K. (1995) Frequency distributions of PM10 chemical components and their sources.
Environ. Sci. Technol. 29: 19-28.
Khalil, M. A. K.; Rasmussen, R. A. (1992) Forest hydrocarbon emissions: relationships between fluxes and
ambient concentrations. J. Air Waste Manage. Assoc. 42: 810-813.
Kim, B. M.; Zeldin, M. D.; Liu, C. S. (1992) Source apportionment study for state implementation plan
development in the Coachella Valley. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and
nontraditional paniculate source controls, an A&WMA/EPA international specialty conference, v. II;
January; Scottsdale, AZ. Pittsburgh, PA: Air & Waste Management Association; pp. 979-991.
(A&WMA transactions series no. 22).
Kleinman, M. T.; Pasternack, B. S.; Eisenbud, M.; Kneip, T. J. (1980) Identifying and estimating the relative
importance of sources of airborne particulates. Environ. Sci. Technol. 14: 62-65.
Koutrakis, P.; Spengler, J. D. (1987) Source apportionment of ambient particles in Steubenville, OH using
specific rotation factor analysis. Atmos. Environ. 21: 1511-1519.
Lang, J. M.; Snow, L.; Carlson, R.; Black, F.; Zweidinger, R.; Tejada, S. (1982) Characterization of
particulate emissions from in-use gasoline-fueled motor vehicles. Warrendale, PA: Society of
Automotive Engineers; SAE technical paper no. 811186.
Lewis, C. W.; Stevens, R. K. (1987) Hybrid receptor models. In: Johnson, R. W.; Gordon, G. E.; Calkins, W.;
Elzerman, A. Z., eds. The chemistry of acid rain: sources and atmospheric processes; developed from
a symposium sponsored by the Divisions of Petroleum Chemistry, Inc., Nuclear Chemistry and
Technology, Environmental Chemistry, and Fuel Chemistry at the 191st meeting of the American
Chemical Society; April 1986; New York, NY. Washington, DC: American Chemical Society;
pp. 58-65. (ACS symposium series: 349).
Lewis, C. W.; Baumgardner, R. E.; Stevens, R. K.; Claxton, L. D.; Lewtas, J. (1988) Contribution of
woodsmoke and motor vehicle emissions to ambient aerosol mutagenicity. Environ. Sci. Technol.
22: 968-971.
Liousse, C.; Penner, J. E.; Chuang, C.; Walton, J. J.; Eddleman, H.; Cachier, H. (1996) A global
three-dimensional model study of carbonaceous aerosols. J. Geophys. Res. [Atmos.] 101: in press.
Lioy, P. J.; Mallon, R. P.; Lippmann, M.; Kneip, T. J.; Samson, P. J. (1982) Factors affecting the variability
of summertime sulfate in a rural area using principal component analysis. J. Air Pollut. Control Assoc.
32: 1043-1047.
5-75
-------
Lowenthal, D. H.; Zielinska, B.; Chow, J. C.; Watson, J. G.; Gautam, M.; Ferguson, D. H.; Neuroth, G. R.;
Stevens, K. D. (1994) Characterization of heavy-duty diesel vehicle emissions. Atmos. Environ.
28: 731-743.
Macias, E. S.; Hopke, P. K., eds. (1981) Atmospheric aerosol: source/air quality relationships; based on a
symposium jointly sponsored by the Divisions of Nuclear Chemistry and Technology at the 180th national
meeting of the American Chemical Society; August 1980; Las Vegas, NV. Washington, DC: American
Chemical Society. (Comstock, M. J., ed. ACS symposium series: 167).
Magliano, K. L. (1988) Level 1 PM10 assessment in a California air basin. In: Mathai, C. V.; Stonefield, D. H.,
eds. PM-10: implementation of standards, an APCA/EPA international specialty conference; February;
San Francisco, CA. Pittsburgh, PA: Air Pollution Control Association; pp. 508-517. (APCA transactions
series TR-13).
Marticorena, B.; Bergametti, G. (1995) Modeling the atmospheric dust cycle: I. design of a soil-derived dust
emission scheme. J. Geophys. Res. [Atmos.] 100: 16,415-16,430.
Mason, B. (1966) Principles of geochemistry. 3rd ed. New York, NY: John Wiley & Sons, Inc.
Matthews, E. (1994) Nitrogenous fertilizers: global distribution of consumption and associated emissions of
nitrous oxide and ammonia. Global Biogeochem. Cycles 8: 411-439.
Matthias-Maser, S.; Jaenicke, R. (1994) Examination of atmospheric bioaerosol particles with radii > 0.2 ^m.
J. Aerosol Sci. 25: 1605-1613.
Mazurek, M. A.; Cofer, W. R., Ill; Levine, J. S. (1991) Carbonaceous aerosols from prescribed burning of a
boreal forest ecosystem. In: Levine, J. S., ed. Global biomass burning: atmospheric, climatic, and
biospheric implications. Cambridge, MA: MIT Press; pp. 258-263.
Mylonas, D. T.; Allen, D. T.; Ehrman, S. H.; Pratsinis, S. E. (1991) The sources and size distributions of
organonitrates in Los Angeles aerosol. Atmos. Environ. Part A 25: 2855-2861.
NBA. (1990a) E..aancement of the south coast air basin source profile library for chemical mass balance receptor
model applications: volume I, final report. Beaverton, OR: NBA.
NBA. (1990b) Enhancement of the south coast air basin source profile library for chemical mass balance receptor
model applications: volume II, source profile library supplement. Beverton, OR: NBA.
NBA. (1990c) Enhancement of the south coast air basin source profile library for chemical mass balance receptor
model applications: volume III, appendices. Beverton, OR: NBA.
National Research Council. (1982) Diesel cars: benefits, risks and public policy: final report of the Diesel
Impacts Study Committee. Washington, DC: National Academy Press.
Nriagu, J. O. (1989) A global assessment of natural sources of atmospheric trace metals. Nature (London)
338: 47-49.
Nriagu, J. O.; Pacyna, J. M. (1988) Quantitative assessment of worldwide contamination of air, water and soils
by trace metals. Nature (London) 333: 134-139.
O'Connor, B. H.; Kerrigan, G. C.; Hinchliffe, P. (1977) The loss of Br from thin-film samples during X-ray
fluorescence analysis. X-Ray Spectrom. 6: 83-85.
5-76
-------
Olmez, I.; Sheffield, A. E.; Gordon, G. E.; Houck, J. E.; Pritchett, L. C.; Cooper, J. A.; Dzubay, T. G.;
Bennett, R. L. (1988) Compositions of particles from selected sources in Philadelphia for receptor
modeling applications. JAPCA 38: 1392-1402.
Ott, S.-T.; Ott, A.; Martin, D. W.; Young, J. A. (1991) Analysis of a trans-Atlantic saharan dust outbreak based
on satellite and GATE data. Mon. Weather Rev. 119: 1832-1850.
Pace, T. G., ed. (1986) Receptor methods for source apportionment: real world issues and applications, an
APCA international specialty conference; March 1985; Williamsburg, VA. Pittsburgh, PA: Air Pollution
Control Association. (APCA transactions no. TR-5).
Pandis, S. N.; Paulson, S. E.; Seinfeld, J. H.; Flagan, R. C. (1991) Aerosol formation in the photooxidation of
isoprene and /3-pinene. Atmos. Environ. Part A 25: 997-1008.
Pandis, S. N.; Harley, R. A.; Cass, G. R.; Seinfeld, J. H. (1992) Secondary organic aerosol formation and
transport. Atmos. Environ. Part A 26: 2269-2282.
Peterson, J. T. (1970) Distribution of sulfur dioxide over metropolitan St. Louis, as described by empirical
eigenvectors, and its relation to meteorological parameters. Atmos. Environ. 4: 501-518.
Pickle, T.; Allen, D. T.; Pratsinis, S. E. (1990) The sources and size distributions of aliphatic and carbonyl
carbon in Los Angeles aerosol. Atmos. Environ. Part A 24: 2221-2228.
Pierson, W. R.; Brachaczek, W. W. (1974) Airborne paniculate debris from rubber tires. Presented at: Joint
meeting of the American Chemical Society, Rubber Division, and the Chemical Institute of Canada,
Macromolecular Science Division; May; Toronto, Ontario, Canada. Rubber Chem. Technol.
47: 1275-1299.
Pierson, W. R.; Brachaczek, W. W. (1976) Paniculate matter associated with vehicles on the road. Presented at:
SAE automotive engineering congress and exposition; February; Detroit, MI. Warrendale, PA: Society of
Automotive Engineers; SAE technical paper no. 760039.
Pierson, W. R.; Brachaczek, W. W. (1983) Paniculate matter associated with vehicles on the road.
II. Aerosol Sci. Technol. 2: 1-40.
Pierson, W. R.; Gertler, A. W.; Bradow, R. L. (1990) Comparison of the SCAQS tunnel study with other
on-road vehicle emission data. J. Air Waste Manage. Assoc. 40: 1495-1504.
Pinto, J. P.; Pleasant, M.; Kellogg, R.; Torok, Sz.; Stiles, D.; Willis, R. D.; Koutrakis, P.; Allen, G. A.
(1995) Chemical characterization of the ambient aerosol in Philadelphia. Presented at: Paniculate matter:
health and regulatory issues: an A&WMA international specialty conference; April; Pittsburgh, PA.
Pittsburgh, PA: Air & Waste Management Association; submitted abstract.
Placet, M.; Battye, R. E.; Fehsenfeld, F. C.; Bassett, G. W. (1991) Emissions involved in acidic deposition
processes. In: Irving, P. M., ed. Acidic depostion: state of science and technology, volume I: emissions,
atmospheric processes, and deposition. Washington, DC: The U.S. National Acid Precipitation
Assessment Program. (State of science and technology report no. 1),
Prospero, J. M. (1995) The atmospheric transport of particles to the ocean. In: Ittekkot, V.; Honjo, S.; Depetris,
P. J., eds. SCOPE report: particle flux in the ocean. New York, NY: John Wiley & Sons, Ltd.; in press.
Prospero, J. M.; Nees, R. T.; Uematsu, M. (1987) Deposition rate of paniculate and dissolved aluminum
derived from Saharan dust in precipitation at Miami, Florida. J. Geophys. Res. [Atmos.]
92: 14,723-14,731.
5-77
-------
Prospero, J. M.; Savoie, D. L.; Arimoto, R.; Huang, F. (1993) Long-term trends in African mineral dust
concentrations over the western North Atlantic: relationship to North African rainfall. EOS Trans. Am.
Geophys. Union 74: 146.
Radke, L. F.; Hegg, D. A.; Hobbs, P. V.; Nance, J. D.; Lyons, J. H.; Laursen, K. K.; Weiss, R. E.;
Riggan, P. J.; Ward, D. E. (1991) Paniculate and trace gas emissions from large biomass fires in
North America. In: Levine, J. S., ed. Global biomass burning: atmospheric, climatic, and biospheric
implications. Cambridge, MA: MIT Press; pp. 209-224.
Radwan, C. (1995) Paniculate emissions trends predicted in the PARTS model. In: Paniculate matter: health and
regulatory issues: proceedings of an international specialty conference; April; Pittsburgh, PA. Pittsburgh,
PA: Air & Waste Management Association; pp. 599-607. (A&WMA publication VIP-49).
Rasmussen, R. A.; Went, F. W. (1965) Volatile organic material of plant origin in the atmosphere. Proc. Natl.
Acad. Sci. U. S. A. 53: 215-220.
Reeser, W. K.; Zimmer, R. A.; Cummins, P.; Briggs, K. R. (1992) An episodic PM10 emissions inventory for
Denver, Colorado. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional paniculate
source controls, an A&WMA/EPA international specialty conference, v. I; January; Scottsdale, AZ.
Pittsburgh, PA: Air & Waste Management Association; pp. 131-145. (A&WMA transactions series
no. 22).
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1991) Sources of fine
organic aerosol. 1. Charbroilers and meat cooking operations. Environ. Sci. Technol. 25: 1112-1125.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1993a) Sources of fine
organic aerosol. 2. Noncatalyst and catalyst-equipped automobiles and heavy-duty diesel trucks.
Environ. Sci. Technol. 27: 636-651.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1993b) Sources of fine
organic aerosol. 5. Natural gas home appliances. Environ. Sci. Technol. 27: 2736-2744.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1993c) Sources of fine
organic aerosol. 4. Paniculate abrasion products from leaf surfaces of urban plants. Environ. Sci.
Technol. 27:2700-2711.
Rogge, W. F.; Hildemann, L. M.; Mazurek, M. A.; Cass, G. R.; Simoneit, B. R. T. (1993d) Sources of fine
organic aerosol. 3. Road dust, tire debris, and organometallic brake lining dust: roads as sources and
sinks. Environ. Sci. Technol. 27: 1892-1904.
Rogge, W. F.; Mazurek, M. A.; Hildemann, L. M.; Cass, G. R.; Simoneit, B. R. T. (1993e) Quantification of
urban organic aerosols at a molecular level: identification, abundance and seasonal variation. Atmos.
Environ. Part A 27: 1309-1330.
Ryan, W. M.; Badgett-West, C. R.; Holtz, D. R.; Peters, T. A.; Cooper, J. A.; Ono, D. (1988) Reconciliation
of receptor and dispersion modeling impacts of PM10 in Hayden, Arizona. In: Mathai, C. V.; Stonefield,
D. H., eds. PM-10: implementation of standards, an APCA/EPA international specialty conference;
February; San Francisco, CA. Pittsburgh, PA: Air Pollution Control Association; pp. 419-429.
(APCA transactions series TR-13).
Savoie, D. L.; Prospero, J. M. (1982) Particle size distribution of nitrate and sulfate in the marine atmosphere.
Geophys. Res. Lett. 9: 1207-1210.
5-78
-------
Shao, Y.; Raupach, M. R.; Findlater, P. A. (1993) Effect of saltation bombardment on the entrainment of dust
by wind. J. Geophys. Res. [Atmos.] 98: 12,719-12,726.
Skidmore, L. W.; Chow, J. C.; Tucker, T. T. (1992) PMi0 air quality assessment for the Jefferson County,
Ohio air quality control region. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional
paniculate source controls, an A&WMA/EPA international specialty conference, v. II; January;
Scottsdale, AZ. Pittsburgh, PA: Air and Waste Management Association; pp. 1016-1031.
(A&WMA transactions series no. 22).
Snow, J. T.; McClelland, T. M. (1990) Dust devils at White Sands Missile Range, New Mexico: 1. temporal
and spatial distributions. J. Geophys. Res. [Atmos.] 95: 13,707-13,721.
South Coast Air Quality Management District. (1994) State implementation plan for PM10 in the Coechella
Valley: 1994 "BACM" revision. Diamond Bar, CA: South Coast Air Quality Management District.
Spendlove, J. C. (1974) Industrial, agricultural, and municipal microbial aerosol problems. In: Current problems
in aerobiology: proceedings of the thirtieth general meeting of the Society for Industrial Microbiology;
August 1973; Evanston, IL. Dev. Ind. Microbiol. 15: 20-27.
Stevens, R. K.; Pace, T. G. (1984) Overview of the mathematical and empirical receptor models workshop
(Quail Roost II). Atmos. Environ. 18: 1499-1506.
Stevenson, H. J. R.; Sanderson, D. E.; Altshuller, A. P. (1965) Formation of photochemical aerosols. Int. J. Air
Water Pollut. 9: 367-375.
Susott, R. A.; Ward, D. E.; Babbitt, R. E.; Latham, D. J. (1991) The measurement of trace emissions and
combustion characteristics for a mass fire. In: Levine, J. S., ed. Global biomass burning: atmospheric,
climatic, and biospheric implications. Cambridge, MA: MIT Press; pp, 245-257.
Svasek, J. N.; Terwindt, J. H. J. (1974) Measurements of sand transport by wind on a natural beach.
Sedimentology 21: 311 -322.
Szkarlat, A. C.; Japar, S. M. (1983) Optical and chemical properties of particle emissions from on-road vehicles.
J. Air Pollut. Control Assoc. 33: 592-597.
Thanukos, L. C.; Miller, T.; Mathai, C. V.; Reinholt, D.; Bennett, J. (1992) Intercomparison of PM10 samplers
and source apportionment of ambient PM10 concentrations at Rillito, Arizona. In: Chow, J. C.;
Ono, D. M., eds. PM]0 standards and nontraditional paniculate source controls, an A&WMA/EPA
international specialty conference, v. I; January; Scottsdale, AZ. Pittsburgh, PA: Air & Waste
Management Association; pp. 244-261. (A&WMA transactions series no. 22).
Truex, T. J.; Pierson, W. R.; McKee, D. E. (1980) Sulfate in diesel exhaust. Environ. Sci. Technol.
14: 1118-1121.
Turekian, K. K. (1971) Elements, geochemical distribution of. In: Encyclopedia of science and technlogy,
v. 4. New York, NY: McGraw-Hill Book Company; pp. 627-630.
Turpin, B. J.; Huntzicker, J. J. (1991) Secondary formation of organic aerosol in the Los Angeles basin:
a descriptive analysis of organic and elemental carbon concentrations. Atmos. Environ. Part A
25: 207-215.
Turpin, B. J.; Huntzicker, J. J.; Larson, S. M.; Cass, G. R. (1991) Los Angeles summer midday paniculate
carbon: primary and secondary aerosol. Environ. Sci. Technol. 25: 1788-1793.
5-79
-------
U.S. Environmental Protection Agency. (1989) Procedures for estimating and applying rule effectiveness in
post-1987 base year emission inventories for ozone and carbon monoxide state implementation plans.
Research Triangle Park, NC: Office of Air Quality Planning and Standards.
U.S. Environmental Protection Agency. (1993) Motor vehicle-related air toxics study. Ann Arbor, MI: Office of
Mobile Sources; EPA report no. EPA/420/R-93/005. Available from: NTIS, Springfield, VA;
PB93-182590/XAB.
U.S. Environmental Protection Agency. (1994) National air quality and emissions trends report, 1993. Research
Triangle Park, NC: Office of Air Quality Planning and Standards; EPA report no. EPA 454/R-94-026.
U.S. Environmental Protection Agency. (1995a) Compilation of air pollutant emission factors, volume I:
stationary point and area sources. 5th ed. Research Triangle Park, NC: Office of Air Quality Planning
and Standards; report no. AP-42.
U.S. Environmental Protection Agency. (1995b) National air pollutant emission trends, 1900 - 1994. Research
Triangle Park, NC: Office of Air Quality Planning and Standards; report no. EPA-454/R-95-011.
Van Espen, P. (1984) A program for the processing of analytical data (DPP). Anal. Chim. Acta 165: 31-49.
Vermette, S. J.; Williams, A. L.; Landsberger, S. (1992) PM10 source apportionment using local surface dust
profiles: examples from Chicago. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional
paniculate source controls, an A&WMA/EPA international specialty conference, v. I; January;
Scottsdale, AZ. Pittsburgh, PA: Air & Waste Management Association; pp. 262-278. (A&WMA
transactions series no. 22).
Vinogradov, A. P. (1959) The geochemistry of rare and dispersed chemical elements in soils. 2nd ed. New
York, NY: Consultants Bureau, Inc.
Walker, B. L.; Cooper, C. D. (1992) Air pollution emission factors for medical waste incinerators. J. Air Waste
Manage. Assoc. 42: 784-791.
Warneck, P. (1988) Chemistry of the natural atmosphere. New York, NY: Academic Press, Inc.
Watson, J. G.; Chow, J. C. (1994) Clear sky visibility as a challenge for society. Annu. Rev. Energy Environ.
19: 241-266.
Watson, J. G.; Henry, R. C.; Cooper, J. A.; Macias, E. S. (1981) The state of the art of receptor models
relating ambient suspended paniculate matter to sources. In: Macias, E. S.; Hopke, P. K., eds.
Atmospheric aerosol: source/air quality relationships; based on a symposium jointly sponsored by the
Divisions of Nuclear Chemistry and Technology and Environmental Chemistry at the 180th national
meeting of the American Chemical Society; August 1980; Las Vegas, NV. Washington, DC: American
Chemical Society; pp. 89-106. (Comstock, M. J., ed. ACS symposium series: 167).
Watson, J. G.; Chow, J. C.; Mathai, C. V. (1989) Receptor models in air resources management: a summary of
the APCA international specialty conference. JAPCA 39: 419-426.
Watson, J. G.; Chow, J. C.; Pritchett, L. C.; Houck, J. A.; Burns, S.; Ragazzi, R. A. (1990a) Composite
source profiles for paniculate motor vehicle exhaust source apportionment in Denver, CO.
In: Mathai, C. V., ed. Visibility and fine particles: an A&WMA/EPA international specialty conference;
October 1989; Estes Park, CO. Pittsburgh, PA: Air & Waste Management Association; pp. 422-436.
(A&WMA transactions series no. TR-17).
5-80
-------
Watson, J. G.; Chow, J. C.; Pritchett, L. C.; Houck, J. A.; Ragazzi, R. A.; Burns, S. (1990b) Chemical source
profiles for paniculate motor vehicle exhaust under cold and high altitude operating conditions.
Sci. Total Environ. 93: 183-190.
Watson, J. G.; Chow, J. C.; Pace, T. G. (1991) Chemical mass balance. In: Hopke, P. K., ed. Data handling in
science and technology: v. 7, receptor modeling for air quality management. New York, NY: Elsevier
Press; pp. 83-116.
Watson, J. G.; Chow, J. C.; Lowenthal, L. C.; Pritchett, C. A.; Frazier, C. A.; Neuroth, G. R.;
Robbins, R. (1994a) Differences in the carbon compostion of source profiles for diesel-
and gasoline-powered vehicles. Atmos. Environ. 28: 2493-2505.
Watson, J. G.; Chow, J. C.; Blumenthal, D. L.; Lurmann, F. W.; Hackney, R. J.; Magliano, K. L.;
Pederson, J. R.; Neff, W. D.; Roth, P. M.; Solomon, P. A.; Thuillier, R. H.; Ziman, S. D. (1994b)
Planning for data analysis. In: Solomon, P. A.; Silver, T. A., eds. Planning and managing regional air
quality modeling and measurement studies: a perspective through the San Joaquin Valley air quality study
and AUSPEX. Boca Raton, FL: Lewis Publishers; pp. 335-349.
Went, F. W. (1960) Organic matter in the atmosphere, and its possible relation to petroleum formation.
Proc. Natl. Acad. Sci. U. S. A. 46: 212-221.
Wilson, T. R. S. (1975) Salinity and major elements of sea water. In: Riley, J. P.; Skirrow, G., eds. Chemical
oceanography. 2nd ed. London, United Kingdom: Academic Press; pp. 365-413.
Wilson, W. E.; Schwartz, W. E.; Kinzer, G. W. (1972) Haze formation—its nature and origin. New York, NY:
Coordinating Research Council; report no. CRC-APRAC-CAPA-6-68-3. Available from: NTIS,
Springfield, VA; PB-212609.
Wolff, G. T.; Korsog, P. E. (1985) Estimates of the contributions of sources to inhalable paniculate
concentrations in Detroit. Atmos. Environ. 19: 1399-1409.
Wolff, G. T.; Countess, R. J.; Groblicki, P. J.; Ferman, M. A.; Cadle, S. H.; Muhlbaier, J. L. (1981)
Visibility-reducing species in the Denver "brown cloud"—II. sources and temporal patterns.
Atmos. Environ. 15: 2485-2502.
Wolff, G. T.; Korsog, P. E.; Kelly, N. A.; Ferman, M. A. (1985a) Relationships between fine paniculate
species, gaseous pollutants and meteorological parameters in Detroit. Atmos. Environ. 19: 1341-1349.
Wolff, G. T.; Korsog, P. E.; Stroup, D. P.; Ruthkosky, M. S.; Morrissey, M. L. (1985b) The influence of local
and regional sources on the concentration of inhalable paniculate matter in southeastern Michigan.
Atmos. Environ. 19: 305-313.
Wu, J. (1979) Sea spray in the atmospheric surface layer: review and analysis of laboratory and oceanic results.
J. Geophys. Res. [Atmos.] 84: 1683-1704.
Xie, Y.; Hopke, P. K.; Casuccio, G.; Henderson, B. (1994a) Use of multiple fractal dimensions to quantify
airborne particle shape. Aerosol Sci. Technol. 20: 161-168.
Xie, Y.; Hopke, P. K.; Casuccio, G.; Henderson, B. (1994b) Use of chain code histogram method to quantify
airborne particle shapes. Aerosol Sci. Technol. 21: 210-218.
5-81
-------
Zeng, Y.; Hopke, P. K. (1989) Three-mode factor analysis: a new multivariate method for analyzing spatial and
temporal composition variation. In: Watson, J. G., ed. Receptor models in air resources management:
an international specialty conference; February 1988; San Francisco, CA. Pittsburgh, PA: Air & Waste
Management Association; pp. 173-189. (APCA transactions series: no. 14).
Zhang, S.-H.; Shaw, M.; Seinfeld, J. H.; Flagan, R. C. (1992) Photochemical aerosol formation from a-pinene
and /8-pinene. J. Geophys. Res. [Atmos.] 97: 20,717-20,729.
5-82
-------
6. ENVIRONMENTAL CONCENTRATIONS
6.1 BACKGROUND, PURPOSE, AND SCOPE
This chapter summarizes the concentrations of particulate matter over the United States,
including the spatial, temporal, size and chemical aspects. The information needs for
assessing the major aerosol effects of concern are summarized in Table 6-1. The general
approach followed in preparing this chapter was to organize, evaluate, and summarize the
existing large scale aerosol data sets over the United States. Emphasis was placed on complete
national coverage as well as the fusion and reconciliation of multiple data sets.
Space is the main organizing dimension used to structure this chapter. Aerosol
concentration data are presented on global, continental, national, regional, and
sub-regional/urban scales. Within each spatial domain, the spatial-temporal structure, size,
and chemical composition are presented. An overview of the pattern analysis methods is given
in the remainder of Section 6.1. The presentation of aerosol patterns begins from the global
and continental perspective (Section 6.2). Next, nationwide aerosol patterns (Section 6.3)
derived from nonurban and urban PM10 and PM2 5 monitoring networks are examined.
Section 6.3 also includes a discussion of various measures of background PM2 5 and PM10.
In Section 6.4 the aerosol characteristics over seven subregions of the conterminous United
States are examined in more detail. The 10-year trends, seasonal patterns, relationships
between PM2 5 and PM10, and fine particle chemical composition are examined for each
region. Section 6.5 focuses further on the subregional and urban-scale aerosol pattern over
representative areas of the United States. Section 6.6 presents more detailed information on
the chemical composition of the aerosol from a number of intensive field studies. Section 6.7
deals with measurements of fine particle acidity. Section 6.8 focuses on the concentration of
ultrafine particles and Section 6.9 on the chemical composition of ultrafine particles. Section
6.10 examines trends and relationships for PM2 5, PM(10.2.5), and PM10 in data bases having
long term data on both components.
Aerosol concentration data for the United States have been reported by many aerosol
researchers over the past decade. This chapter draws heavily on the contribution, of research
6-1
-------
groups that have produced data, reports, and analyses of nonurban data. However, their
maps, charts, and computations have been re-done for consistency with urban data reports.
6.1.1 Dimensionality and Structuring of the Aerosol Data Space
Aerosol concentration patterns contain endless detail and complexity in space, time, size,
and chemical composition. Aerosol samples from the conterminous United States reveal the
coexistence of sulfates, hydrogen ions, ammonium, organic carbon (OC), nitrates, elemental
carbon (EC [soot]), soil dust, sea salt, and trace metals. This chemically rich aerosol mixture
arises from the multiplicity of contributing aerosol sources, each having a unique chemical
mixture for the primary aerosol at the time of emission. The primary aerosol chemistry is
further enriched by the addition of species during atmospheric chemical processes. Finally, the
immensely effective mixing ability of the lower troposphere stirs these primary and secondary
particles into a mixed batch with varying degrees of homogeneity, depending on location and
time.
A major consideration in structuring the aerosol pattern analysis is that it has to be
consistent with the physical and chemical processes that determine the concentrations of the
aerosol. The concentration of paniculate matter (C), at any given location and tune is
determined by the combined interaction of emissions (E), dilution (D), and chemical
transformation and removal processes (T),expressed as:
C=f(D,T,E)
Dilution, transformation/removal, and emissions are generic operators and can, in
principle, be determined from suitable measurements and models. However, for consideration
of aerosol pattern analysis it is sufficient to recognize and separate these three major causal
factors influencing the aerosol concentration pattern.
It is convenient to categorize the highly variable aerosol signal along the following major
dimensions: space, time, size and chemical composition. The dependence of concentration on
space and time is common to all pollutants. However, both the distribution with respect to
particle size as well as the chemical distribution within a given size range constitute unique
6-2
-------
dimensions of paniculate matter that are not present for other pollutants. The concentrations
of single-compound gaseous pollutants can be fully characterized by their spatial and temporal
pattern. This classification by dimensions is consistent with the size-chemical composition
distribution function introduced by Friedlander (1977). It could be said that particulate matter
is a composite of hundreds of different substances exhibiting a high degree of spatial and
temporal variability.
6.1.2 Spatial Pattern and Scales
The spatial dimension covers the geographic scale and pattern of aerosols. Based on
consideration of emissions, meteorology, and political boundaries, the spatial dimension can
be broken into global, national, regional-synoptic, meso, urban, and local scales. Some of the
characteristics of these spatial scales are illustrated in Table 6-1.
TABLE 6-1. SPATIAL REGIONS AND SCALES
Global
Continent
10,000-
50,000 km
National
Country
5,000 -
10,000km
Regional
Multi-state
1,000-
5,000 km
Meso
State
100-
1,000km
Urban
County
10 - 100 km
Local
City center
1-10 km
6.1.3 Temporal Pattern and Scales
The time dimension of aerosols extends over at least six different scales (Figure 6-1).
A significant, unique feature of the temporal domain is the existence of periodicities. The
secular time scale extends over several decades or centuries. Given climatic and chemical
stability of the atmosphere the main causes of secular concentration trends are changes in
anthropogenic emissions. Emissions, atmospheric dilution, as well as chemical/removal
processes, can be influenced by the seasonal cycle. The synoptic scale covers the duration of
6-3
-------
Dilution |X I Chemistry/Removal |sa| Concentration
Secular
Yearly
Weekly
Synoptic
Daily
Microscale
Minutes
Figure 6-1. Time scales for particle emissions.
synoptic meteorological events (3-5 days). Its role is primarily reflected in dilution and
chemical/removal processes. The daily cycle strongly influences the emissions, dilution, and
chemical/removal processes. Microscale defines variation of the order of an hour caused by
short-term atmospheric phenomena. In the analysis that follows we will emphasize secular
trends and yearly cycles, with some consideration of daily aerosol pattern. The microscale
patterns will be largely ignored.
6.1.4 Space-Time Relationships
The spatial and time scales of aerosol pattern are linked by the atmospheric residence
time of particles. Short residence times restrict the aerosol to a short transport distance from a
source, causing strong spatial and temporal gradients. Longer residence times yield more
6-4
-------
10'
10'
e
"5
E
20 urn)
10
10'
10'
10'
10'
10'
Residence Time, seconds
10
Figure 6-2. Relationship of spatial and temporal scales for coarse and fine particles.
uniform regional patterns caused by long range transport. The relationship between spatial
and temporal scales for coarse and fine particles is illustrated in Figure 6-2.
The aerosol residence time itself is determined by the competing rates of chemical
transformations and removal. Secondary aerosol formation tends to be associated with multi-
day long range transport because of the time delay necessary for the formation. For sulfates,
for example, the residence time is 3-5 days. For fine particles, 0.1 //m to several /urn, the
main removal mechanism involves cloud processing, while coarse particles above 10 Atm are
deposited by sedimentation. Ultrafine particles, below 0.1 fj.m, also rapidly coagulate to form
particles in the 0.1 to 1.0 /urn size range. Another factor which must be considered is local
turbulence. As a consequence of low removal rates, aerosols in the 0.1-1.0 /um size range
reside in the atmosphere for longer periods than either smaller or larger particles (Figure 6-3).
6-5
-------
10'
10~~ 10'° 10'" 10"' 10" 10' 10" 10
Radius, pen
Figure 6-3. Residence time in the lower troposphere for atmospheric particles from 0.1 to
1.0 jim. ( — Background aerosol, 300 particles cm*3; — continental aerosol,
15,000 particles cm'3.)
Source: Jaenicke (1980).
If aerosols are lifted into the mid- or upper-troposphere their residence time will increase to
several weeks. Large scale aerosol injections into the stratosphere through volcanoes or deep
convection result in atmospheric residences of a month or two months for ash and ^ 2 years
for sulfates formed from SO2 oxidation.
In the context of the specific analysis that follows, the space-time-concentration
relationship in urban and mountainous areas is of particular importance (Figure 6-4). Urban
^'4,
areas have strong spatial emission gradients and also may have corresponding concentration
gradients for directly emitted species, particularly in the winter under poor horizontal and
vertical transport conditions.
In mountainous regions, the strong concentration gradients are caused by both
topography that limits transport as well as the prevalence of emissions in valley floors. Strong
6-6
-------
Summer
rural
Winter
rural
urban
-•;.-:V.r-:----^
urban
rural
^•{•^^•'
rural
Summer
mountain
valley
Winter
mountain
valley
Figure 6-4. Space-time relationship in urban and mountainous areas.
mountain
mountain
wintertime inversions tend to amplify the valley-mountain top concentration difference. Fog
formation also accelerates the formation of aerosols in valleys
6.1.5 Particle Size Distribution
The aerosol size distribution is of importance in quantifying both the formation
(generation) as well as the effects of aerosols. Condensation of gaseous substances during
combustion in the atmosphere generally produces fine particles below 1 jum in diameter.
Resuspension of soil dust and dispersion of sea spray produces coarse particles above 1 /*m.
The size distribution of particles also influences both the atmospheric behavior and the
effects of aerosols. Atmospheric coagulation, cloud scavenging, and removal by impaction
and settling are strongly size dependent (Figure 6-3). The effects on human health depend on
size-dependent lung penetration. The effects of light scattering on visibility and climate are
also strongly dependent on particle size.
Measurements over the past decades (Whitby et al., 1972; Whitby, 1978) show that
atmospheric aerosols may be classified as fine mode particles or coarse mode particles. The
size distribution of atmospheric particles is discussed in Section 3.7. The sources, formation
mechanisms, and chemical compositions of these two aerosol modes are different. In general,
6-7
-------
the two aerosol size modes have independent spatial and temporal patterns as described
throughout this chapter. Coarse dust particles tend to be more variable in space and time and
can be suspended through natural or human activities. Fine particles during the wanner
months of the year are largely of secondary origin and their spatial-temporal pattern is more
regional. Notable exceptions are urban-industrial hotspots and mountain valleys where
primary submicron size smoke particles can prevail.
6.1.6 Aerosol Chemical Composition
The chemical composition of atmospheric aerosol is believed to influence the effect on
human health. While the causal mechanisms are not fully understood, the acidity,
carcinogenicity, and other forms of toxicity are chemical properties considered relevant to
human health.
The aerosol chemical composition has also become an important property for identifying
source types based on chemical "fingerprints" in the ambient aerosol. Since aerosols reside in
the atmosphere for days and weeks, there is a substantial amount of mixing that takes place
among the contributions of many sources. At any given "receptor" location and time, the
aerosol is a mixture of many source contributions each having a chemical signature for
possible source type identification.
Fine particles are generally composed of sulfates, hydrogen ions, ammonium, organics,
nitrates, elemental carbon (soot), as well as a portion of the trace metals (Section 6.6). Each
major chemical form has sub-species such as acidic and neutral sulfates, light and heavy
organics, ammonium and sodium nitrates, etc.
The chemical composition of coarse particles is dominated by the elements of the earth's
crust, Si, Al, Fe, and other elements commonly found in soil. Near industrial sources, coarse
particles may be contaminated by lead and other trace metals. At ocean shores, coarse
particles may consist of sea salt arising from breaking of waves. Both resuspended dust and
sea salt are primary particles, carrying the chemical signatures of their sources.
6-8
-------
6.2 GLOBAL AND CONTINENTAL SCALE AEROSOL PATTERN
There are two data sets which can be used to provide information on fine particle
concentration patterns on continental and global scales. Routine visibility distance
observations, recorded hourly at many U.S. airports by the U.S. Weather Service, provide an
indication of fine particle pollution over the United States. The visibility distance data have
been converted to aerosol extinction coefficients and used to access patterns and trends of
aerosol pollution over the United States (Husar et al., 1994; Husar and Wilson, 1993).
Routine satellite monitoring of backscattered solar radiation over the oceans by the Advanced
Very High Resolution Radiometer sensors on polar orbiting meteorological satellites provides
a data set which can be used to give an indication of aerosol over the world's oceans. These
two data sets have been merged to provide a global and continental perspective. The data
analyses presented here were performed for this Criteria Document and have not yet been
published elsewhere.
Aerosol detection over the oceans is facilitated by the fact that the ocean reflectance at
0.6 /mi is only 0.02. Hence, even small backscattering from aerosols produces a measurable
aerosol signal. The backscattering is converted to a vertically integrated equivalent aerosol
optical thickness assuming a shape for the aerosol size distribution or phase function. Clouds
are eliminated by a cloud mask, so the data are biased toward clear-sky conditions. The
oceanic aerosol maps represent a two-year average (July 1989-June 1991) prior to the eruption
of Mt. Pinatubo, when the stratosphere was unusually clear of aerosol. Consequently, the
images reflect mainly the spatial pattern of tropospheric aerosol.
A continental-scale perspective for North America is shown in Figure 6-5. Seasonal
depictions of the oceanic aerosol for the entire globe are shown in Figure 6-6. The average
aerosol map of Eastern North America for June, July and August (Figure 6-5) shows areas of
high optical depth over the Mid-Atlantic States and over the Atlantic Ocean. The aerosol
concentration over the oceans is highest near the coast and declines with distance from the
coast. This indicates that the aerosol is of continental origin and represents a plume
originating in eastern North America, heading north-east across the Atlantic ocean. This
plume can also be seen in the spring and summer season oceanic aerosol patterns shown in
Figure 6-6.
6-9
-------
March, April,
ontinental - Visibility
Oceanic - AVHRR Satellite:
July, August, Sept
- Visibility
Oceanic - AVHRR Satellite
Figure 6-5. Continental scale pattern of aerosols derived from visibility observations over
land and satellite monitoring over the oceans: North America.
6-10
-------
9
Figure 6-6. Global pattern of oceanic aerosols derived from satellite observations.
-------
The continental aerosol extinction coefficient data for the southwest coast of North
America indicate elevated aerosol extinction over southern California. The area includes the
hazy South Coast and the San Joaquin Valley air basins. It is interesting to note that somewhat
elevated aerosol optical thickness is also recorded over the Pacific near Southern California.
However, the low aerosol signal and the semi-quantitative satellite data preclude a clear cause
and effect association.
The seasonal aerosol pattern over the oceans reveals that the highest aerosol signal is
found near the tropics, where wind-blown dust and biomass burning in Africa and southern
Asia produce 5,000 km long aerosol plumes (Figure 6-6). Further aerosol belts which may be
of marine origin are observed just north of the Equator and at 30 to 60° latitudes in both
hemispheres. The backscattering in the summer hemispheres exceeds the winter values by a
factor of 5 to 10. There is a pronounced seasonality in each aerosol region (Figure 6-7); the
higher aerosol levels appear in the summer hemisphere although many continental and marine
regions show a spring maximum. Thus, the global tropospheric aerosol is a dynamic
collection of independent aerosol regions, each having unique sources and temporal patterns.
The seasonal oceanic aerosol maps show two distinctly different spatial patterns: aerosol
plumes originating from continents, and oceanic aerosol patches that are detached from the
continents. The continental aerosol plumes are characterized by high values near the coastal
areas and a decline with distance from the coast. The most prominent aerosol plume is seen
over the equatorial Atlantic, originating from West Africa and crossing the tropical Atlantic.
It is the well known Sahara dust plume. Additional continental plumes emanate form
Southwest Africa, Indonesia, China-Japan, Central America and eastern North America.
Aerosols which may be of marine origin dominate large zonal belts (30 to 60° N and S) in the
summer hemispheres as well as near the Equator. In summary, the global tropospheric aerosol
is a collection of largely independent aerosol regions, each having a bio-geochemically active
source and unique spatial temporal pattern.
Based on the above global and continental-scale observations, it can be concluded that the
continental plume from eastern North America is not as intense as those from other industrial
and non-industrial regions of the world. However, quantitative aerosol comparisons of global
regions are not available.
6-12
-------
0
H DO cr tr >
< LJJ < Q. <
^ "- S < 2
-i o Q- !TT > o
33E8i£
160
140
120
100
80
60
40
20
0
NW Pacific. b
N Atlantic
EC Pacific
New Zealand
CD
LU
CC>Z=iOQ-l->O
0-<^2^lijOoiiJ
<5-5^<(/>OzQ
SE Pacific
N 30-60
S 30-60
Shifted 6 months
N Hemisphere
f
Figure 6-7. Seasonal pattern of oceanic aerosols derived from satellite observations.
6-13
-------
6.3 U.S. NATIONAL AEROSOL PATTERN AND TRENDS
Our current understanding of the U.S. national aerosol pattern arises from nonurban,
regional background monitoring networks, the Interagency Monitoring of Protected Visual
Environments (IMPROVE) (Sisler et al., 1993) and the Northeast States for Coordinated Air
Use Management (NESCAUM) (Poirot et al., 1990, 1991), and from a mainly urban network,
the Aerometric Information Retrieval System (AIRS) (AIRS, 1995). The nonurban and urban
networks yield markedly different national patterns, particularly over the western United
States. For this reason the results from the two sets of observations are presented separately
and the differences between two networks are evaluated. The data analyses presented here
were performed for this Criteria Document and have not yet been published elsewhere.
6.3.1 Nonurban National Aerosol Pattern
Nonurban aerosol concentrations are measured at remote sites, away from
urban-industrial activities. Size-segregated aerosol mass and chemical composition data are
available for 50 sites, through the IMPROVE (Joseph et al., 1987; Eldred et al., 1987, 1988,
1990; Eldred and Cahill, 1994) and NESCAUM (Poirot et al., 1990, 1991; Flocchini et al.,
1990) networks. These are located mostly in national parks and wilderness areas. The PM10
and PM2 5 mass concentrations are sampled and analyzed on separate filters. The sampling
frequency is generally twice a week (Wednesdays and Saturdays) for 24 hours. The PM2 5
samples are analyzed for chemical composition which makes the data sets suitable for chemical
mass balance computations (e.g., Sisler et al., 1993; Malm et al., 1994b). The
IMPROVE/NESCAUM aerosol data are available from 1988 through 1993.
Measurements of PM are available from the IMPROVE/NESCAUM network at a
smaller number of sites compared to the number of sites for which measurements are available
from the AIRS network. The nonurban sites also have very different geographical
distributions from those sites in the urban network. Therefore, the ability to compare PM10
concentrations from the nonurban and urban networks is severely limited by these factors.
The monthly distributions of chemical species, the chemical mass balances, obtained
from the measurements at nonurban sites are incomplete. Only sulfate, organics, soil, and
soot (elemental carbon) are considered. The contributions of hydrogen ion, water, trace
6-14
-------
metals and sea salt are not listed. The contribution of nitrate is included on a national basis,
but not in the subsequent discussion for regions.
The results of the national spatial and temporal pattern analysis are presented in quarterly
contour maps and monthly seasonal time charts. The contours drawn for the eastern United
States are derived from only 15 to 20 stations. As a consequence, these contour lines are to be
taken as guides to the eye and not as actual patterns. The quarters of the year are calendrical.
6.3.1.1 Nonurban PM2 5 Mass Concentrations
Maps of seasonal average nonurban PM2 5 concentrations are shown in Figure 6-8. The
maps divide the country roughly into eastern and western halves. The eastern United States is
covered by large, contiguous PM2 5 concentrations that range from 10 /ug/m3 in Quarter 1, and
17 //g/m3 in Quarter 3. During the transition seasons (Quarters 2 and 4) the eastern U.S.
nonurban PM2 5 concentrations are at about 12 /ug/m3. Within the eastern U.S., there are
subregions such as New England that have lower concentrations ranging between 8 and
12 Aig/m3. During the third quarter, there is a wider range of geographic distribution of PM2 5
concentrations in the eastern United States than in other quarters of the year.
The lowest nonurban PM2 5 concentrations are measured over the central mountainous
western states. The low winter concentrations are at about 3 /wg/m3, while the summer values
are around 6 Atg/m3. Somewhat elevated PM2 5 concentrations are observed over the
southwestern border adjacent to Mexico as well as in California and the Pacific Northwest.
The nonurban fine particle mass clearly shows multiple aerosol regions over the conterminous
U.S., each exhibiting unique spatial and seasonal characteristics.
6.3.1.2 Nonurban Particulate Matter Coarse Mass Concentrations
In classifying size fractions of PM, PM10 refers to PM collected in a sampler with a
50% cutpoint of 10 /*m aerodynamic diameter and PM2 5 to PM collected in a sampler with a
cutpoint of 2.5 /mi aerodynamic diameter. PMCoarse or coarse will be used to refer to the
PM between the cutpoints of 2.5 and 10 /un, whether determined by subtracting a PM2 5
sample mass from a PM10 sample mass or determined directly from the coarse particle channel
of a dichotomous sampler with a PM10 (or PM15) /mi diameter upper cutpoint. Fine will also
6-15
-------
Quarter 1
Quarter 2
o\
Fine Mass
Quarter 3
Fine Mass
Fine Mass ' Fine Mass
Figure 6-8. Fine mass concentration derived from nonurban IMPROVE/NESCAUM networks.
Quarter 4
-------
be used to refer to PM2 5. PM2 5 is an indicator of the fine mode particle mass but it is not an
exact indicator, since PM2 5 may contain some coarse mode PM. Likewise, PMCoarse or
coarse refers to the inhalable fraction of the coarse mode, not the entire coarse mode. Under
high relative humidity conditions PMCoarse may contain some fine mode PM.
The nonurban coarse aerosol mass concentration in the size range 2.5 to 10 pm is given
in the seasonal maps in Figure 6-9. It is plotted on the same concentration scale as the
nonurban PM2 5 and PMCoarse maps to show that the nonurban coarse mass concentration is
less than the fine mass concentration over most of the country. The lowest nonurban coarse
particle concentration is recorded during the first, second, and fourth calendar quarters when
virtually the entire conterminous United States showed values < 10 //g/m3. The industrialized
Midwest, adjacent to the Ohio River, shows low PMCoarse concentration (< 10 Mg/m3)
comparable to the relatively clean Rocky Mountains states. The highest nonurban coarse mass
concentrations appear during quarters 2 and 3. In quarter 2, the southwestern United States
adjacent to the Mexican border shows the highest nonurban coarse mass concentrations. In
quarter 3, the monitoring sites hi Florida and Southern California exhibit high concentrations
6.3.1.3 Nonurban PM10 Mass Concentrations
Maps of seasonal average nonurban PM10 concentrations are shown hi Figure 6-10.
PM10 is the sum of the PM2 5 and PMCoarse. The spatial pattern from east to west, including
the delineation of aerosol regions, is generally similar to the PM2 5. However, the PM10
concentrations exceed the PM2 5 by up to a factor of two depending on region and season.
The sparseness of nonurban sites over large areas of the central United States limits the
reliability of profiles in these areas.
In the eastern U.S., PM10 concentrations range between 12 //g/m3 in Quarter 1 and
25 jug/m3 in Quarter 3. During the transition seasons (Quarters 2 and 4) the eastern U.S.
non-urban PM10 concentrations are about 15 ^g/m3, except hi New England. The lowest
PM10 concentrations are measured over the central mountainous states, 5 A*g/m3 hi Quarter 1,
10 /ig/m3 in Quarter 3, and 7 yug/m3 during the transition seasons. Higher PM10
concentrations, between 10 and 20 //g/m3, were measured over the southwestern United States
6-17
-------
Quarter 1
Quarter 2
Coarse Mass
Coarse Mass
o\
H-*
00
Quarter 3
Quarter 4
Coarse Mass
Coarse Mass
Figure 6-9. Coarse mass concentration derived from nonurban IMPROVE/NESCAUM networks.
-------
Quarter 1
Quarter 2
PM10 Mass
PMIOMass
Quarter 3
Quarter 4
PM10 Mass
PM10 Mass
Figure 6-10. PM10 mass concentration derived from nonurban EVfPROVE/NESCAUM networks.
-------
as well as over the Pacific states from California to the Northwest than over the central
mountainous states.
6.3.1.4 PM2 5/PM10 Ratio at Nonurban Sites
The PM10 aerosol mass is composed of fine mass (PM2 5) and coarse mass, below
(Figure 6-10). Both the sources and the effects of fine particles differ markedly from those of
coarse particles. For this reason it is beneficial to examine the relative contribution of PM2 5
and PM10 concentrations. Figure 6-11 shows the seasonal fine mass as a fraction of PM10.
Nationally, the fine fraction at nonurban sites ranges between 0.4 and 0.8. The highest
fine fraction is recorded east of the Mississippi River, where 60 to 70% of the PM10 mass is in
particles <2.5 jum in size. This is also the region that shows the highest PM10 concentrations;
thus, fine particles dominate the nonurban aerosol concentrations east of the Mississippi River.
The fine fraction exceeds the coarse fraction at the nonurban northwestern sites. The fine
fraction is the lowest in the southwestern United States (< 50%), particularly in the spring
season (Quarter 2).
Spatial and seasonal variation of the fine fraction is a further indication for the existence
of different aerosol regions over the conterminous U.S. This is further illuminated in Section
6.4 where the aerosol characteristics over different regions of the United States are discussed.
6.3.1.5 Nonurban Fine Particle Chemistry
The elemental composition of nonurban fine particles over the conterminous United
States is now reasonably well understood. The IMPROVE/NESCAUM network provides over
five years of aerosol mass and chemical composition data. The data from these networks
allows the chemical apportionment of the fine particle mass into aerosol types such as sulfates,
organic carbon, elemental carbon, and fine soil (Schichtel and Husar, 1991; Sisler et al., 1993,
Sisler and Malm, 1994). The quantification of these aerosol types is relevant to both the
determination of aerosol effects and source apportionment of particle mass. It should be
emphasized that urban areas, mountain valleys, and remote monitoring sites are likely to have
different relative concentrations of the aerosol types. Also, the quantification of semivolatile
organic compounds, nitrates, and other unstable species is subject to major uncertainties.
6-20
-------
Quarter 2
Fine Fraction of PM10 Mass
Fine Fraction of PM10 Mass
to
Quarter 3
Fine Fraction of PM10 Mass 2 Fine Fraction of PM10 Mass
Figure 6-11. Fine fraction of PM10 derived from nonurban EMPROVE/NESCAUM networks.
Quarter 4
-------
Much work remains in order to define the chemical, as opposed to the elemental, composition,
especially for organic compounds.
At nonurban eastern U.S. sites, a large fraction of the fine aerosols are composed of
sulfate and related species (ammonium ions, hydrogen ions, and associated water) and organic
compounds. In the northeastern and southeastern U.S., organic carbon appear to equal sulfate
in the fourth quarter of the year. In the southwestern U.S., wind blown dust is a major
component of fine mass while sulfate is less important (Schichtel and Husar, 1991).
Annually averaged fine particle sulfate, as ammonium sulfate; organic carbon; elemental
carbon; and nitrate, as ammonium nitrate, concentrations from the IMPROVE network across
the U.S. are shown in Figures 6-12 and 6-13 (Sisler et al., 1993; Malm et al., 1994b). The
station density is limited, especially in the eastern U.S. The contour lines in the annual
average maps are to be used as guides to the eye, rather than precise values. Concentrations of
sulfate in the eastern U.S. (Figure 6-12a) exceeds those over the mountainous western states by
factor of five or more. Elevated sulfate in excess of 1 Atg/m3 is also reported over the Pacific
coast states. Sulfates typically contribute over 50% of the fine particulate mass in the eastern
U.S., while sulfates contribute 30% or below in the West.
Fine particle nitrates (Figure 6-12b) are highest in California, exceeding 4 ^g/m3 at most
sites. Their share of the fine mass at several California sites exceeds 20%. Organic carbon
concentrations (Figure 6-13a) are high over California and northwestern sites, as well as at the
eastern U.S. sites. Organic carbon contributes over 50% of the fine particle mass in the
Northwest, and about 30% throughout the eastern U.S. There is a high degree of uncertainty
associated with the measurement of particulate nitrate and organic carbon because of artifacts
arising from the adsorption of vapors or the loss of semivolatile materials. The elemental
carbon concentrations (Figure 6-13b) are significant over the Northwest and southern
California, as well as at the Washington, DC, site. Over most of the country elemental carbon
is 5% or less of the fine particle mass.
The chemical composition of PM10 and PM2 5 aerosols in the IMPROVE network
(Eldred et al., 1994b) revealed that the average coarse mass does not differ significantly
between the East and West; however, the fine mass is higher in the East. Also about 80% of
6-22
-------
to
U)
% NO
Figure 6-12. Yearly average absolute and relative concentrations for sulfate and nitrate.
Source: Sisler et al. (1993) and Malm et al. (1994b).
-------
ON
Organic
Carbon, pg/m3
Elemental
Carbon, ug/m3
% Elemental
Carbon
Figure 6-13. Yearly average absolute and relative concentrations for organic carbon and elemental carbon.
Source: Sisler et al. (1993) and Malm et al. (1994b).
-------
soil elements and 20% of sulfur were found in the coarse fraction. Most trace elements were
found hi the fine fraction, both hi the East and in the West. The spatial and seasonal patterns
hi particle concentrations and then- relationships to optical extinction in the United States from
the IMPROVE network were summarized by Malm et al. (1994b).
In studying the regional patterns of nonurban trace metals in the IMPROVE network,
Eldred et al. (1994a) found a good correlation between selenium and sulfur at all sites hi the
East. The correlation in the West is lower. Comparison of the S/Se ratios for summer and
whiter shows that there is approximately twice the sulfur relative to selenium in summer
compared to whiter. Se is a tracer for S emitted from coal-fired fossil fuel power plants; this
shift hi S/Se from summer to winter is consistent with a substantial secondary photochemical
contribution to SO^" during the summer. Zinc is highest at the sites in the central East.
It does not correlate well with sulfur. Lead and bromine are relatively uniform, with slightly
higher mean concentrations hi the East. There is poor correlation between lead and bromine.
Copper and arsenic are highest hi the Arizona copper smelter region. Copper is also higher hi
the central East.
Trends (1982 to 1992) of nonurban fine particle sulfur, zinc, lead, and soil elements
were reported by Eldred et al. (1994a) using the IMPROVE network data. They observe that
hi the southwest, sulfur trends in spring, summer, and fall decreased, while most of the whiter
trends increased. The trends hi the Northwest increase slightly. The two eastern sites
(Shenandoah and Great Smoky Mountains) have increased almost 4% per year in summer,
increased 1 to 3% hi spring and fall, and decreased 2% hi whiter. The annual increase was
between 2 and 3%. Generally, there were no significant trends in zinc and the soil elements.
Lead at all sites decreased sharply through 1986, corresponding to the shift to unleaded
gasoline. The ten year trends reported by Eldred et al. (1994b) have not been compared and
reconciled with other compatible data.
6.3.1.6 Seasonally of the Nonurban Chemistry
This section discusses the seasonality of size segregated chemical composition at
non-urban monitoring sites (IMPROVE/NESCAUM) over the entire U.S. (Figure 6-14).
6-25
-------
PM 2.5 Concentration - U.S.
IMPROVE/NESCAUM Data
PM10, PM2.5 and PMC-U.S.
IMPROVE/NESCAUM Data
40,000
35,000
30,000
E
01 25,000
o
O
20,000
15,000
10,000
5,000
(b)
1989 Mar May Jul Sep Nov
-S-PM10 -^~ PM2.5 -A- PM Coarse
Chemical Fine Mass Balance - U.S.
IMPROVE/NESCAUM Data
IB
I
(C)
0.0
1989 Mar May
-fr- Sulfate
4,000
3,500
3,000
E
01 2,500
Chemical Tracers - U.S.
IMPROVE/NESCAUM Data
o
I
o
O
2,000
1,500
1,000
500
(d)
Jul Sep Nov
^OC -HSoil
-o- Sulfate + OC + Soil + EC
1989 Mar May Jul
-&- Sulfur -Max = 4000
~i~Vanadium - Max = 10
Sep Nov
-B-Selenium - Max = 4
-e- S/Se - Max = 4000
Figure 6-14. Seasonal pattern of nonurban aerosol concentrations for the entire
United States: (a) monitoring locations; (b) PM10, PM2 5, and PMCoarse
(PMC); (c) sulfate, soil, organic carbon (OC), and elemental carbon (EC)
fractions; and (d) tracers.
6-26
-------
The nationally aggregated average PM10, PM2 5 and PMCoarse is shown in
Figure 6-14b (See Section 6.3.1.2 for a definition of PMCoarse.). The nonurban PM10
concentration ranges from 8 |Ug/rn3 in the winter, December through February, to about
15 /ug/m3 in June to August. On the national scale the PM10 seasonality is clearly sinusoidal
with a summer peak. Fine particles over the nonurban conterminous United States account for
about 50 to 60% of the PM10 mass concentration throughout the year. The coarse mass
accounts for 40 to 50% throughout the year. Hence, the fine-coarse aerosol ratio does not
change dramatically for the average nonurban aerosol.
The relative chemical composition of the aggregated nonurban aerosol pattern is shown
in Figure 6-14c, including sulfates, organic carbon, soil, and elemental carbon as a fraction of
the fine particle mass concentration. The Figure also shows the sum of these four aerosol
species to indicate the fraction of the fine aerosol mass that is not accounted for. Most notable
among the missing species is the contribution of nitrates, ammonium ion, and hydrogen ion.
There is mild seasonality in the nationally aggregated sulfate and organic carbon
fractions. Throughout the year, sulfate aerosol, including the ammonium cation, accounts for
30 to 40% of the fine mass. Organic carbon also contribute 30 to 40% of the nationally
averaged fine particle mass. Thus, sulfates and organic carbon are the two dominant species,
contributing about 70% of the fine aerosol mass.
The contribution of soil dust to the fine mass ranges between 4% in the winter months to
12% during April through July. Elemental carbon is about 2% during the summer and 5%
during the winter.
The sum of the four measured fine mass components, sulfates, soil, organic carbon, and
elemental carbon add up to about 80% of the measured fine mass throughout the year. The
remaining, unaccounted fine mass may be contributed by nitrates, trace metals (e.g., Pb, Br,
sea salt [NaCl], etc.).
The seasonal pattern of concentration of primary emission tracers, selenium, Se and
vanadium, V is shown Figure 6-14d. Se is a known tracer for coal combustion, while V is a
trace constituent of fuel oil (Altshuller, 1980; Kleinman et al., 1980; Cass and McRae, 1983;
Tuncel et al. 1985). The Figure also shows the monthly average concentration of fine particle
sulfur as well as the S/Se ratio.
6-27
-------
The national average Se concentration is rather uniform over the seasons, ranging
between 400 to 600 pg/m3. Since Se is a primary pollutant, the seasonal invariance means that
the combined effect of emissions and dilution is seasonally invariant over the year.
The concentration of V is between 500 to 700 pg/m3, with the higher concentrations
occurring in the winter season. Evidently, the contributions from V-bearing fuel oil are more
pronounced during the cold season. The monthly average sulfur in aerosols exhibits the
highest concentrations 1.5 ^g/m3, during June, July, and August, and the lowest values
0.9 Aig/m3, during November, December, and January.
The S/Se mass ratio is about 700 during November to January and climbs to about
1,500 during April through September. The higher S/Se ratio during the warm season is an
indication of secondary sulfate production from SO2 in the plumes of coal fired power plants
(Chapter 3).
Eastern United States
The seasonal pattern of the eastern U.S. aerosol chemistry is shown in Figure 6-15. The
concentration of PM10, PM2 5, PMCoarse (Figure 6-15b) indicates a similar seasonality,
highest concentrations in the summer, and lowest in the winter. The PM10 levels range
between 12 to 24 /ug/m3, the PM2 5 ranges between 8 to 12 Mg/ni3, while PMCoarse ranges
between 4 to 7 Mg/m3 over the year. The size segregated aerosol data for the nonurban East
show that the fine mass concentration (8 to 12 //g/m3) is higher than the national average (4 to
8 //g/m3), while the coarse mass concentration is comparable to the national average. Eastern
U.S. nonurban fine particles contribute 60 to 70% of the fine mass throughout the year.
The apportionment of the fine particle mass into its chemical components (Figure 6-15c)
favors sulfates which amount to 40 to 50% of the fine mass throughout the year, compared to
about 30% of organic carbon. The contribution of soil dust is about 5% throughout the year,
while soot is more important in the winter (6%) than in the summer (3%). The above three
aerosol chemical components account for 85 to 90% of the measured fine particle mass,
leaving only relatively small contribution to nitrates, hydrogen ions, trace metals, and sea salt.
The coal tracer selenium (Figure 6-15d) exhibits a modest winter peaked seasonality
between 600 to 800 ng/m3. The fuel oil tracer vanadium on the other hand, is factor of two
6-28
-------
PM2.5 Concentration - Eastern U.S.
IMPROVE/NESCAUM Data
PM10, PM2.5 and PMC - Eastern U.S.
IMPROVE/NESCAUM Data
40,0001 ' . . . . . . . . . •-
o
o
35,000
30,000
25,000
20,000
15,000
10,000
5,000
(b)
1989 Mar May Jul Sep Nov
-B-RM10 H-PM2.5 -A-PM Coarse
Chemical Fine Mass Balance - Eastern U.S.
IMPROVE/NESCAUM Data
Chemical Tracers - Eastern U.S.
IMPROVE/NESCAUM Data
o.e
0.8
-------
higher in the winter (1,500 ng/m3) compared to the summer (750 ng/m3). Evidently, the
primary contribution from fuel oil is winter peaked. The S/Se ratio is about 1,000 in the
winter, and it is over 2,000 in the summer months. This suggests the seasonality of secondary
sulfate formation during the summer months.
Western United States
The aggregated western U.S. aerosol seasonality is presented in Figure 6-16. The
non-urban aerosol concentrations for PM10, PM2 5, and PMCoarse are well below the
concentrations over the eastern United States (Figure 6-16b). The western United
States differs from the eastern United States, having lower fine mass concentrations, which
range between 3 to 5 ,ag/m3. The coarse mass concentration (4 to 8 ^g/m3) and seasonality is
similar over the East and the West. It is worth emphasizing, however, that these measurements
are at remote national parks and wilderness areas in both East and West. The examination of
monitoring data in urban areas and confined airsheds (Sections 6.4 and 6.5) reveals a highly
textured pattern in space and time.
The fine particle chemical mass balance (Figure 6-16c) for the aggregated western United
States shows the substantial contribution of organic carbon, which account for 30 to 45 % of
the fine mass. The higher organic carbon fraction occurs in the November through January
season. Sulfates range between 20 to 25 % throughout the year. Soil dust plays a prominent
role in the western fine mass balance, contributing 20% in April through May, but declining to
5% by January. Elemental carbon ranges between 5% in the winter and 2 % during the
summer. About 25% of the fine mass over the western United States is not accounted for by
sulfates, soil, organic carbon, and elemental carbon. It is known that nitrates are major
contributors to the fine particle mass in the South Coast Basin, as well as other western
regions (White and Macias, 1987a; Chow et al., 1992a, 1993a, 1995a).
The concentration of the trace substances (Figure 6-16d) selenium and vanadium shows
both low concentrations and weak seasonality. The sulfur concentrations are also less than
half of the eastern U.S. values. The S/Se ratio is about 500 in the winter months and 1,000
during the summer. The lower S/Se ratios compared to those in the eastern U.S. are the result
6-30
-------
PM2.5 Concentration -Western U.S.
IMPROVE/NESCAUM Data
1
o
o
Chemical Fine Mass Balance -Western U.S.
IMPROVE/NESCAUM Data
0.6
O.B
0.7
-------
of selenium emitting coal-fired power plants not being the only sources of western U.S. sulfur.
Smelters make a contribution to S but not Se in the atmosphere.
The above general discussion of national pattern of chemical and size dependence do not
provide the more detailed spatial and temporal texture of the U.S. aerosol pattern discussed in
the following sections. However, it provides the national scale gross features and serves as a
broader context for the more detailed examinations.
6.3.1.7 Background Concentrations of Particle Mass and Chemical Composition
The concentration and chemical composition of background paniculate matter can very
with geographic location, from monitoring site to monitoring site; with season of the year; and
with meteorological conditions which affect the emissions and secondary production of
biogenic or geogenic species to the background.
A number of types of background can be considered. These backgrounds include the
following: (1) a "natural" background excludes all anthropogenic contributions. This
background includes any natural sources contributing to the background for chemical species
in North America or globally; (2) a background which excludes all anthropogenic sources
within North America, but not from anthropogenic sources contributing to background from
outside of North America; (3) a background which excludes the anthropogenic sources inside
the United States, but not from elsewhere in North America; (4) a background which excludes
anthropogenic sources from other regions into a specified region hi the United States; (5) a
background which would exclude all sources of paniculate matter except those associated with
a particular urban area. The two backgrounds directly relevant to the Criteria Document are
backgrounds (1) and (2). The problems and limitations in obtaining reasonably accurate
annual average and seasonal values for these backgrounds are discussed below. Backgrounds
(4) and (5) can be more readily be obtained by measurements. These backgrounds are relevant
to subsequent stages in the implementation process. The averaging period over which
background levels are defined should also be stated. Annual and seasonal averages may be
more appropriate for risk assessments but daily peak values may be more relevant for control
strategy implementation.
6-32
-------
More specifically, the term non-manmade is meant to encompass sources such as
geogenic dust plumes and sea salt as well as biogenic sources. Biogenic sources include
(a) combustion products of biomass burning caused by lightning; (b) emissions of volatile
sulfur compounds from marshes, swamps or oceans; (c) organic paniculate matter formed by
the atmospheric reactions of biogenic volatile organic compounds such as terpenes; and
(d) particulate nitrates formed by the atmospheric reactions of NOX emitted from soils. There
is an intermediate class of sources associated with agricultural activities. These include
biomass burning caused by human intervention and the addition of fertilizers to soils resulting
in emissions of NH3 and NOX (Section 5.2, 5.3).
Anthropogenic sources include vehicular and stationary sources which emit particles
directly or precursors such as sulfur dioxide, nitrogen oxides, or those volatile organic
compounds capable of reacting in the atmosphere to form organic particles. Stationary sources
of primary particulate matter as well as sulfur oxides and nitrogen oxide precursors include
fossil fuel power plants, while smelters are sources of primary particles and sulfur oxides.
Vehicles emit primary particulate matter as well as nitrogen oxides and volatile organic
compounds. Solvent usage, agricultural coatings, and many other industrial operations also
may emit precursors or particulate matter. Wood burning for heating of homes is a source of
organic carbon and elemental carbon (Section 5.2, 5.3).
The formation of sulfates from sulfur dioxide emitted by power plant plumes can occur
over distances exceeding 300 km and 12 h of transport (Section 3.4.2.1). Nitric acid also can
be formed in these plumes and it can be converted to ammonium nitrate, if sufficient ammonia
is available to first neutralize the sulfate in plumes. Similar transport can occur in urban
plumes. The transport distances in plumes depend on both formation rates of particles and
their removal by deposition processes. However, the residence times of fine particles can be
long. For example, if the dominant removal process is dry deposition, fine particles
transported through a 1000 m deep mixed layer near the surface with deposition velocities of 1
to 0.1 cm/s have atmospheric residence times ranging from 1 to 11 days (Section 3.5.1,
3.5.3). When particles are trapped in a layer well aloft they may survive even longer periods.
Therefore, transport distances of several hundred to several thousand kilometers are possible.
6-33
-------
Direct evidence of such transport aloft is available from satellite monitoring of back
scattered solar radiation. The most prominent plume is that of Sahara dust from West Africa
(Section 6.2). This plume has been observed to extend during the spring and summer months
to the east coast of the United States, especially over Florida (Figure 6-6). Ground level
measurements in Bermuda indicate that southeasterly winds bring high concentrations of soil-
and crustal-related aerosols which appear to be from the Sahara desert (Wolff et al., 1986).
Other large plumes exist, such as the Asian plume. However, the satellite observations do not
indicate that it reaches the west coast of the United States (Figure 6-6).
Field measurements and modeling studies can be used as aids in the derivation of
background values for aerosol constituents. Either approach is subject to considerable
uncertainty and each has its own advantages and limitations. Field data would be the most
logical choice if it could be shown to be completely free of anthropogenic influences
originating within North America, i.e., background (2), (following the guidelines set out
above for defining background levels unaffected by pollution sources within North America).
A number of difficulties arise in interpreting field data for this purpose, namely: (a) there are
very few tracers (e.g., 14C) which can be used to distinguish between anthropogenic and
biogenic source categories of aerosol constituents; (b) multilayer trajectories should be used to
identify source regions since layer-average trajectories may underestimate the geographic area
contributing pollutants to the air mass sampled; (c) sampling must also be carried out for long
enough periods to obtain statistically representative values over seasonal tune scales.
Determining the history of air parcels is difficult in locations subject to small scale circulations
such as cumulus convection and land-sea or mountain-valley breezes. In addition, all small
localized anthropogenic sources of particulate matter must be identified during sampling.
Ideally, measurements should be carried out long enough for the measurements to be shown to
be generally representative of the time period of interest e.g., seasonal average, annual
average.
Alternatively, models which include only natural sources and anthropogenic sources
located outside North America could be used. Their utility is limited by inadequacies in model
formulation, such as grid spacing and knowledge of the strengths, locations, and variability of
various sources. Since a large fraction of particulate matter is secondary, uncertainties in the
6-34
-------
chemistry of precursor gases will play a large role in determining the uncertainty of the final
results. These uncertainties are especially large for the yield of aerosol produced by the
oxidation of biogenic hydrocarbons as pointed out in Chapters 3 and 5. Uncertainties in the
chemistry of NOX and SO2 are also important hi that they affect estimates of the yield of
aerosol products versus the deposition of intermediate species.
Trijonis (1982, 1991) has attempted to estimate PM2 5 and PM10 concentrations
corresponding to background (1), the "natural" background. His approach was to obtain
concentration values only from those biogenic and geogenic sources which are at or below
those possibly associated with preindustrial conditions over North America. Annual average
concentrations of the chemical species in particulate matter were estimated for the eastern
United States and for mountain/desert regions of the western United States. Seasonal
"natural" background concentration values were not estimated. The annual average
concentrations of fine particles were estimated separately for sulfates; as NH4HSO4, nitrates;
as NH4NO3; organic carbon; elemental carbon; soil dust and water (Trijonis, 1982, 1991). In
the later work, coarse particle concentration values were also estimated (Trijonis, 1991). In
addition, in the later work, it was emphasized that the concentration values proposed can have
error factors ranging from 1.5 to 3 for individual chemical species in particulate matter.
In the earlier work (Trijonis, 1982), a fine particle "natural" background for the eastern
United States is estimated at 5.5 ± 2.5 //g/m3. Excluding water, the background value would
be 4 ± 2 ,ug/m3 with the largest contribution, 2 //g/m3, from organic carbon. In the later
estimates (Trijonis, 1991), a fine particle "natural" background for the eastern United States of
3.3 //g/m3 is estimated. Excluding water, this background would be 2.3 Atg/m3 with
1.5 //g/m3 associated with organic carbon. A separate estimate is given for the fine particle
"natural" background over the mountain/desert regions of the western United States of
1.2 /ug/m3. Excluding water, this background would be 1 /^g/m3 with 0.5 ^g/m3 associated
with organic carbon. The coarse particle "natural" background for both the eastern and
western United States is estimated at 3 /ug/m3.
Fernam et al. (1981) also estimated "natural" background concentrations for PM2 5
constituents in the eastern United States during summer. They estimated natural contributions
6-35
-------
to sulfate of 0.5-1.9 yug/m3, to organic carbon of 3.7 /ug/m3, and to crustal material of
To obtain these "natural" background estimates, a wide range of approaches are used
varying from natural SO2 and NOX emissions inventories to SO 4, NO 3 and elemental carbon
concentration measurements in remote locations in the northern and southern hemispheres.
Carbon isotope ratios and organic composition measurements for organic components are used
from several sites in the southwestern United States.
Results of three-dimensional models that could be used to estimate each of the five
background levels for all the major categories of aerosol composition listed above are not
available. Liousse et al. (1996) have performed three-dimensional chemical tracer model
simulations of the global distribution of elemental and organic carbon. Background values
assuming only natural sources (background 1) were also calculated. Average organic carbon
concentrations calculated for the month of July were all less than 1 jwg/m3 in the United States.
These calculations were made assuming a 5% yield of secondary organic carbon from the
oxidation of terpenes (cf. Section 5-3).
Another approach is to use results from rural/remote sites in national parks, wilderness
areas and national monuments from the IMPROVE monitoring measurements. Results for the
period between March 1988 and February 1991 have been published (Malm et al., 1994). The
tabulations of results are given on an annual average basis for individual IMPROVE sites and
on a seasonal basis by IMPROVE subregion for fine mass; sulfate, as (NH4)2SO4; nitrate, as
NH4NO3; organic and elemental carbon; fine soil and coarse mass. These measurements do
not differentiate between anthropogenic and non-anthropogenic contributions and do not
stratify measurements values by wind direction or by use of trajectories representing various
air masses (Malm et al., 1994). However, a large set of measurements, including seasonal
measurements, are provided at a substantial number of rural/remote sites, especially in the
western United States.
In stratifying the IMPROVE results a problem arises because the Colorado plateau
"subregion" with seven sites straddles the boundary between the southwest and northwest used
subsequently (Figure 6-28). Four of the sites are north of the boundary in Utah and Colorado
and three of the sites are south of the boundary in Arizona and New Mexico. The authors
6-36
-------
place the Colorado plateau in the southwest for purposes of a fine mass composition budget
(Malm et al., 1994). Since they assign only one other subregion, Sonora desert, with two sites
to the southwest, the method of assigning sites can significantly affect the resulting estimates
of regional fine mass concentrations. This problem can be avoided for the annual average
values which are shown by individual sites, but not for the seasonal values which are lumped
by subregion. This lumping also requires deciding whether a subregion with five sites, central
Rocky Mountains, should be given the same or five times the weight of the other subregions in
the northwest with only one or two sites each. For the annual average values given in
Table 6-2 the sites are assigned consistent with the division between the northwestern and
southwestern regions shown in Figure 6-28, excluding three sites in the northern California
coastal mountains considered separately. A transitional region between the western mountains
and deserts and the eastern United States has been considered consisting of five sites in three
subregions from West Texas (2), to South Dakota (1) up to the Boundary Waters subregion (2)
near the Canadian border. In addition, the result for paniculate matter from the Appalachian
subregion (2) are given. Previous measurements of particulate matter at sites in the eastern
mountains are available (Stevens et al., 1980); Pierson et al., 1980b; Wolff et al., 1983). The
measurements listed in Table 6-2 include PM2 5 sulfate, as (NH4)2SO4, organic carbon, and
PM(10-2.5)-
The annual average PM2 5 increases substantially from west to east in Table 6-2 from a
value of 3.55 /ug/m3 in the northwestern United States to 10.91 /ug/m3 in the Appalachian
mountains. The annual average (NH4)2SO4 concentration increases even more substantially
from west to east from a value of 0.88 Mg/m3 in the northwestern United States to 6.33 /ug/m3
in the Appalachian Mountains. The lowest annual average organic carbon concentration of
1.38 £tg/m3 occurs in the southwestern United States and increases to 2.97 jUg/m3 in the
Appalachian Mountains. A smaller range of concentrations occurs for organic carbon from
west to east than for PM2 5 and (NH4)2SO4. The (NH4)2SO4, as a percentage of PM2 5,
increases into the transitional region and the Appalachian Mountains from as low as 25 % of
the PM2 5 at sites in the northwestern United States up to 58% at sites in the Appalachian
Mountains. Conversely, organic carbon decrease as a percentage of PM2 5 from 46% at sites
in northwestern United States down to 27% in the Appalachian Mountains. Within the
6-37
-------
TABLE 6-2. ANNUAL AVERAGE CONCENTRATIONS AND
CHEMICAL COMPOSITION FROM IMPROVE MONITORING SITES
Northwest3
Southwest15
California Coastal Mountains0
Transitional Regiond
Appalachian Mountains0
No. of
15
5
3
5
2
Annual
3.55
3.91
4.99
5.15
10.91
Average Concentrations, /ug/m3 and Composition
(NH4)2S04/
0.88/25
1.28/33
1.41/28
1.97/38
6.33/58
Organics/
1.63/46
1.38/35
1.95/39
2.01/39
2.97/27
PM
4.46
5.62
8.85
6.54
6.24
8.0
9.5
13.8
11.7
17.2
aCascades (1), central Rocky Mt. (5), Great Basin (1), N. Rocky Mt. (1), Sierra Nevada (1), Sierra Humboldt
(2), and Colorado Plateau (4)
"Colorado Plateau (3), Sonora Desert (2)
cSame as subregion
dWestern Texas (2), northern Great Plains (1), Boundary Waters (2).
western United States there are somewhat higher percentages of (NH4)2SO4 and lower
percentages of organic particles in the southwestern United States than in the northwestern
United States. (NH4)2S04 plus organic carbon account for from 67% to 85% of PM2 5, with
the higher percentages at IMPROVE sites east of the Rocky Mountains (Table 6-2).
Compared to the estimates discussed by Trijonis (1982, 1991) for "natural" background,
PM2 5 values in the western United States of 1 Aig/m3, the average measured contractions of
PM2 5 in the northwestern and southwestern United States of 3.55 /ug/m3 and 3.91 /ag/m3
suggest anthropogenic contributions. The IMPROVE measurements are likely to include
anthropogenic contributions from sources within North America (background 3). Even the
lowest annual average PM2 5 value in the contiguous United States of 2.5 Mg/m3 at Bridger
Wilderness Area, WY, is over twice the "natural" background. The Denali NP in Alaska has
an average annual PM2 5 of 2 /ug/m3 (Malm et al., 1994). The organic carbon concentrations
measured there are somewhat closer to the estimated "natural" background in the western
mountains/desert of 0.5 /ug/m3 (Trijonis, 1991). However, average annual concentrations in
the northwestern and southwestern United States are higher with values of 1.63 /ug/m3 and
1.38 //g/m3. The annual average values at several IMPROVE monitoring sites in the Rocky
Mountains are near 1 /ug/m3, while the Denali NP in Alaska has an average annual organic
6-38
-------
carbon concentration of 0.85 /ug/m3. These latter organic carbon concentration values ares at
the two fold upper limit of uncertainly in the estimate of "natural" background. On the other
hand, the (NH4)2SO4 concentrations measured in the west are far above the "natural"
background for (NH4)2SO4 of 0.1 /ug/m3 (Trijonis, 1991). The lowest measured annual
average (NH4)2SO4 at several sites are near 0.5 /ug/m3. For PM(10_2 5), the annual average
concentrations in the northwestern and southwestern United States of 4.46 /ug/m3 and
5.62 /ug/m3 are within the two fold upper limit of uncertainty in the estimate of "natural"
background. At a number of individual sites, annual average PM(10_2 5) concentrations are
3 /ug/m3 to 3.5 /ug/m3, close to the estimated "natural" background. Therefore, the largest
deviations from the "natural" background estimates for a major component occur for
(NH4)2S04.
Comparisons of the measured concentration values in the "transitional" area of the
eastern United States, using sites from west Texas to the Boundary Waters, find that the
average annual concentrations for PM2 5 of 5.15 /ug/m3; (NH4)2SO4 of 1.97 /ug/m3; organic
carbon of 2.01 /ug/m3 and PM(10_2 5) of 6.54 /ug/m3 (Table 6-2) usually are well above the
estimates of "natural" background in the eastern United States (Trijonis, 1991) for PM2 5 of
2.3 /ug/m3; (NH4)2SO4 of 0.2 /ug/m3; organics of 1.5 /ug/m3; and PM(10.2 5) of 3 /ug/m3. As in
the western United States, the measured (NH4)2SO4 concentration values are far above the
"natural" background value, while the measured concentrations of organics are well within the
two fold uncertainty in the "natural" background value.
Another source of lower PM10 concentrations are rural/remote AIRS monitoring sites.
Based on 1993 measurements, the lowest values of PM10 are as follows: Rosebud Co., MT
(maximum of 10 /ug/m3, annual mean of 4.5 /ug/m3); Campbell Co., WY (maximum of
15 /ug/m3, annual mean of 7.0 /ug/m3); and Washington Co., ME (maximum of 23 /ug/m3,
annual mean of 8.8 /ug/m3). These PM10 values agree within a factor of two with the
estimated "natural" background PM10 in the western United States of 4 /ug/m3, and in the
eastern United States of 5.3 /ug/m3 (Trijonis, 1991).
Seasonal variations in particulate matter are also important and have been considered.
The source used for these seasonal values in particulate matter is the IMPROVE monitoring
network (Malm et al., 1994). Because the seasonal values are reported only by IMPROVE
6-39
-------
subregions, there is no good approach to averaging values from differing numbers of sites
within the varying geographical extent of IMPROVE subregions. Therefore, the values of
annual average, summer and winter values for PM2 5, (NH4)2SO4, organic carbon, and
PM(10-2.5) are listed for a number of IMPROVE subregions (Table 6-3).
TABLE 6-3. ANNUAL SUMMER AND WINTER CONCENTRATIONS FROM
IMPROVE MONITORING SITES"
Subregion
Central Rockies
Colorado Plateau
Coastal Mountains
Sonora Desert
West Texas
Northern Great
Plains
Boundary Waters
Appalachian
Mountains
No of Seasons of
Region of U.S. Sites the Year
NW 5 annual
summer
winter
NW-SW 7 annual
summer
winter
NW 3 annual
summer
winter
SW 2 annual
summer
winter
Transitional to 2 annual
east summer
winter
Transitional to 1 annual
east summer
winter
Transitional to 2 annual
east summer
winter
Eastern U.S. 2 annual
summer
winter
PM
3.3
4.8
2.0
3.4
4.1
2.9
5.0
4.5
5.6
4.4
5.6
3.2
5.4
6.6
3.6
4.5
5.6
3.4
5.3
6.2
5.2
10.9
16.6
6.5
(NH4)2S04
0.8
1.0
0.5
1.1
1.3
0.9
1.4
1.9
0.9
1.5
2.1
1.2
2.1
2.5
1.5
1.5
1.8
1.2
2.0
2.2
2.0
6.3
10.5
3.0
Organics
1.5
2.4
0.9
1.2
1.6
1.1
1.9
1.4
2.3
1.5
1.8
1.1
1.5
1.7
1.1
1.5
2.2
1.1
2.1
3.1
1.4
3.0
4.4
2.0
PM
Coarse
4.8
7.5
3.0
4.7
6.4
3.2
8.9
10.7
7.7
6.0
7.6
3.3
7.5
7.4
5.1
6.3
9.7
3.9
5.7
8.2
3.2
6.2
11.2
3.1
a From Malm et al., 1994.
6-40
-------
Annual average concentration almost always are intermediate between the summer and
winter concentration of particulate matter listed in Table 6-3. With a few exceptions, the
summer concentrations are higher than winter concentrations. The exceptions are the higher
winter concentrations for PM2 5 and organics in the coastal mountains. Ratios of summer to
winter concentrations can equal or exceed two for all listed particulate components in both the
central rockies subregion and the Appalachian Mountains. The summer to winter
concentration ratios for PM2-5 are within the 1.5 to 2.5 range except for the coastal mountains
and Boundary Waters subregion. The summer to winter concentration ratios for PM coarse
equal or exceeds two except for the coastal mountains. Therefore, in most rural remote sites
hi IMPROVE subregions summer concentrations of particulate matter substantially exceed
winter concentrations. However, it must be emphasized that it is not appropriate to
extrapolate these results obtained at IMPROVE sites in 1988 to 1991 to other sites or even to
other years of monitoring at IMPROVE sites.
Within the continental United States, there are measurements of particulate mass and
chemical composition under conditions identified as "clean" background conditions
(Wolff et al., 1983). These are based on 7 days of measurements during the summer of 1978
at a site 40 km northwest of Pierre, South Dakota and 18 days during the summer of 1979 at a
site 15 km north of the Gulf Coast, near Abbeville, LA. At the South Dakota site the small
variations in anthropogenic pollutants observed was attributed to a lack of any major pollution
sources along the trajectories. In contrast, at the Louisiana site the days were stratified into
"clean" days when the air had passed over the Gulf of Mexico for several days and much more
polluted episode days when the maritime air was modified by air which had undergone
transport from the midwestern and northeastern United States.
Fine particle mass on "clean" days averaged 11 to 13 /ig/m3 and coarse mass between 9
and 19 /tg/m3 at the two sites. The total mass averaged between 21 and 32 /ig/rn3. Organic
carbon at both sites was the most important fine particle species averaging 4 to 8 /ig/m3
(organic mass multiplied by 1.2 to include H and O), while sulfate averaged 3 /Ag/m3.
At the closest IMPROVE site, the Badlands National Monument, SD in the northern
great plains subregion (Table 6-3), for the summers of 1988 and 1989 (Malm et al., 1994) the
concentrations were PM2.5, 5.6 jig/m3; (NH4)2SO4, 1.8 ,ug/m3; organic carbon, 2.2 yUg/m3 and
6-41
-------
PM(10.2 5)» 9.7 //g/m3. These concentration values are substantially lower than those obtained
at the site 40 km northwest of Pierre, SD in the summer of 1978 as follows: PM2 5,
13 //g/m3, (NH4)2SO4, 3.2 /ug/m3; organic carbon 3.8 Aig/m3 and PM(10.2 5), 19 /ug/m3.
There are several reasons for the differences between the "clean" values and the
IMPROVE values, (a) The measured background varies from year to year and site to site.
(b) Precipitation periods were excluded by Kelly et al. (1982) and Wolff et al. (1983), but the
IMPROVE monitoring network measurements include all weather conditions. All other
conditions being the same, the inclusion of precipitation events in the IMPROVE
measurements probably biases the results low because of rain-out of particulate matter, (c) On
the other hand, the presence of material from anthropogenic sources probably biases the results
high. Wolff et al. (1983) used trajectory analyses to exclude periods with intrusions of
polluted air from their analysis. This was not done with the IMPROVE results. However, the
layer-averaged trajectories used by Wolff et al. (1983) may have underestimated the mixing of
air parcels from surrounding geographical areas leading to an underestimate of the potential
for anthropogenic contributions. The exact causes for the differences between these two types
of "background" estimates cannot be quantitated from available data.
For sulfate, it is possible to make a limited comparison with measurements at rural sites
outside of St. Louis with air flow from the northwest during the third quarters of 1975 and
1976 (Altshuller, 1987), background 5. The average third quarter sulfate concentrations at
these sites for these two years was 7 yug/m3, a substantially higher sulfate concentration than in
South Dakota (Wolff et al., 1983), but lower than measured in other wind directions. These
measurements outside of St. Louis also indicate substantially lower sulfate concentrations
during the first and fourth quarters of 1975, 1976, and 1977 averaging 3.4 /^g/m3, comparable
to the third quarter sulfate concentrations in South Dakota.
It is important to emphasize that the "background" for particulate matter moving toward
cities along the east coast over the Great Smoky Mountains (Stevens et al., 1980); the
Allegheny Mountains (Pierson et al., 1980b) and the Blue Ridge Mountains (Wolff et al.,
1983), background 4, are much higher than for the "clean" air days in South Dakota and
Louisiana. For example, the fine particle matter at the Blue Ridge Mountain site in July and
August 1980 with trajectories from the midwest source areas and the Tennessee Valley source
6-42
-------
area averaged 27 and 24 //g/m3, approximately twice the values under "clean" air conditions in
South Dakota and Louisiana (Wolff et al, 1983). The sulfate concentrations for these two
trajectory directions averaged 14 and 9 //g/m3, with sulfate substantially exceeding organic
carbon. This result is a reversal in the chemical composition under the "clean" air conditions
in South Dakota and Louisiana, but more consistent with the chemical composition under
"episodic" conditions in Louisiana when the sulfate concentration averaged 20 //g/m3 and the
organic carbon averaged 15 /ug/m3.
Because of the repeated occurrence of (NH4)2SO4 concentrations far above "natural"
background even at rural/remote sites, this aspect justifies additional consideration.
A low contribution of natural sources of gaseous sulfur (both terrestrial and marine)
occurs in the eastern United States (Trijonis, 1991). However, a more detailed consideration
of the contribution of natural sources of gaseous sulfur indicates wide variations over the
United States (Placet, 1991). The following estimates for the ratios of total natural gaseous
sulfur to total anthropogenic gaseous sulfur by region (Placet, 1991) are as follows: northeast,
0.01; southeast, 0.03; west gulf, 0.03; southwest, 0.12; northwest, 0.19. The corresponding
ratios for coastal areas are higher with an estimate of 0.52 for the California coastal areas. If
these ratios are converted to ratios of total natural gaseous sulfur to total gaseous sulfur, the
ratios would be 0.11 in the southwest and 0.16 in the northwest. If the following assumptions
are made (a) both natural and anthropogenic sulfur are converted to (NH4)2SO4 to about the
same extent; (b) the concentrations of natural (NH4)2SO4 can be obtained by multiplying the
above ratios by the measured (NH4)2SO4 concentrations, the natural sulfur concentrations in
the southeast would range from 0.1 to 0.15 /ug/m3 and in the northwest from 0.08 Atg/m3 to
0.2 Mg/m3.
A more detailed consideration of the contribution of natural gaseous sulfur at sites near
the Pacific coast is available (Kreidenweis, 1993). In particular, comparisons with measured
(NH4)2SO4 concentrations were made at the Crater Lake National Park in southwestern
Oregon with estimates of natural (NH4)2S04 concentrations. The measured annual average
concentration at this site of (NH4)2SO4 was 0.5 Atg/m3 and an average "low" concentration was
approximately 0.13 fj.g/m3 (Kreidenweis, 1993). This latter value can be compared with
several estimates of natural (NH4)2SO4 concentration based on the following approaches (a) a
6-43
-------
natural source column burden between 35 to 50° north of 0.05 to 0.15 /ug/m3; (b) a Pacific
natural source column estimate between 35 to 50° N of 0.18 /ug/m3 and (c) a 3 D model value
of 0.14 to 0.28 Atg/m3. Other approaches gave higher possible values for natural (NH4)2SO4
(a) "clean" rainfall sulfate concentrations of 0.1 to 0.5 ^g/m3 and (b) another 3-D model value
of 0.6 Aig/m3. These comparisons results in a wide range of annual average values of
(NH4)2SO4 from less than 0.1 Mg/m3 to less than 0.5 /ag/m3 (Kreidenweis, 1993).
Even an upper limit value for natural (NH4)4SO4 of 0.5 Mg/m3 would be a third to a half
of the measured (NH4)2SO4 at IMPROVE sites near the Pacific Coast (Malm et al., 1994).
Further inland, at interior western sites, the marine sources of natural sulfur should make an
even smaller contribution to the measured concentrations of (NH4)2SO4. Comparison of these
(NH4)2SO4 with the estimates based on regional sulfur inventories (Placet, 1991) of 0.08 to
0.2 Atg/m3 would indicate a significant anthropogenic contribution even at relatively remote
western IMPROVE sites. This result suggests that background 3 may have a substantial
contribution from anthropogenic sulfur sources in North America.
As a summary to the discussion in Section 6.3.1.7, the estimated lower limit and upper
limit background concentrations for PM10 and PM2 5 are given on an annual average basis and
for winter and summer for the western and eastern United States in Table 6-4.
TABLE 6-4. SUMMARY OF ANNUAL AND SEASONAL AVERAGE RANGES OF
BACKGROUND CONCENTRATION LEVELS OF PM10 AND PM2 5
PM
PM10
PM2.5
PM10
PM2.5
PM10
PM2.5
Annual or Seasonal
Annual average
Annual average
Winter
Winter
Summer
Summer
Concentrations, yug/m3
Western United States Eastern United States
4-
1-
4-
1-
4-
1-
8
4
6
3
12
5
5-
2-
5-
2-
5-
2-
11
5
8
4
14
6
6-44
-------
The lower limit concentrations are based on the "natural" background midrange
concentrations discussed (Trijonis 1991). There are error factors associated with the chemical
species used to obtain these concentrations range from 1.5 to 3.
The upper limit concentrations are based on measured concentrations from IMPROVE
monitoring sites (Malm et al., 1994). The PM2 5 concentrations are the sum of concentrations
measured for individual chemical species. As noted earlier in Section 6.3.1.7, these measured
concentrations can include some anthropogenic source contributions within North America.
Therefore, the upper limit concentrations represent conservative values for the upper end of
the background concentration type.
To obtain the upper limit concentrations, the averages were obtained from the
concentrations for nine subregions in the western United States giving each region equal
weight and also weighing the contribution of each subregion by the number of sites in the
subregion. The median values were also obtained. For the eastern United States, the averages
were obtained from the concentrations for three subregions in the "transitional" region. For
the annual average from 23 individual sites in the western United States and 5 sites in the
"transitional" region (Table 6-3). The resulting values for upper limit concentrations were
closely clustered usually with a 1 Atg/m3 range. Within these values, the lower whole value
concentration was listed in Table 6-4.
As a supplement to the data collected in the IMPROVE/NESCAUM networks, seasonal
and annual average PM10 concentrations were also taken from AIRS (1990 - 1995). Four
inhabited areas with the lowest annual average PM10 concentrations were chosen in areas
without nearby IMPROVE/NESCAUM sites. Annual, summer, and winter averages for
Penobscot Co., ME (11.1, 13.8, and 10.0 /ig/m3); Marquette, MI (11.2, 15.5, and
7.0 /ig/m3); Mercer Co., ND (11.7, 12.9, and 10.6 /ig/m3); and Lakeport, CA (11.6, 14.3,
and 10.0 /ig/m3) all fall within the upper limits set for PM10 shown in Table 6-4. All areas
exhibit summertime maxima and wintertime minima. The similarity of these results to the
upper limits shown in Table 6-4 suggests an anthropogenic component to those upper limits,
since the AIRS values were obtained in inhabited areas.
Again, it should be mentioned that seasonal or annual average "background" values
presented above will likely underpredict 24-hour maximum "background" values. Ambient
6-45
-------
data could be used to estimate 24-hour maximum values, but their use is subject to
considerable uncertainty because of possible anthropogenic inputs.
6.3.2 Urban National Aerosol Pattern—Aerometric Information Retrieval
System
The urban monitoring network is operated by state and local agencies as mandated by the
Clean Air Act. The data from this network are used to determine exceedences above the
paniculate matter standards. Federal regulations also require that these monitoring data be
submitted to the EPA Aerometric Information and Retrieval System (AIRS). In what follows,
AIRS PM10 refers to the PM10 mass concentration extracted from the AIRS database. The
AIRS database is a useful resource for analyzing trends and concentration patterns, and
relationships between the fine, coarse, and PM|0 components of the atmospheric aerosol
(Husar and Frank, 1991; Husar and Poirot, 1992).
The national average AIRS concentrations were calculated utilizing all of the available
data since the beginning of 1985, when less than 100 monitoring stations were operational
(Figure 6-17). Since that time, the number of monitoring stations has risen to more than
1,300 (Figure 6-17). The implications of the changing stations density to the above described
national PM10 trend is not well studied. The emergence of new stations appeared to be in
rough proportion to the final station density shown in Figure 6-17. In other words, in 1985,
the national coverage had a pattern similar to 1994, except less dense. Changes in sampling
equipment and monitoring protocols are also possible causes of systematic errors in the
reported spatial pattern and trends.
The AIRS PM10 database reports the concentrations every sixth day for a 24-h sampling
period, synchronously over the entire country. The sample duration is one day which, over
the long run, provides the concentration distribution function of daily samples. For
determination of the effects (human health, visibility, acid deposition) the concentration has to
be known at the specific location where the sensitive receptors reside. Also the concentrations
have to be known at a short (e.g., daily) time scale, as well as over the long term.
In order to characterize the one day-scale temporal variation over a given region, the
entire available data aggregated over the entire region for each monitoring day are plotted as
6-46
-------
Valid F»IS/I1O Stations
LJS, XX.II Stations
1 986
1 988
1 99O
1 992
Figure 6-17. Trend of valid PM10 monitoring stations in the AIRS database.
time series. It is recognized that during the other five non-monitored days, the concentrations
may be different from the reported value. The six day sample increment ensures that both
weekday and weekend data are properly taken into account.
The AIRS PM10 stations are mostly in urban areas but some suburban and nonurban sites
are also reported. The analysis presented in this section is based on PM10 and PM2 5 data
retrieved from AIRS in October 1994.
The results of AIRS PM10 aerosol pattern analysis are presented in quarterly contour
maps, as well as seasonal time charts. For valid monthly and quarterly aggregation, it was
required to have at least two samples a month, and six samples per quarter. For the seasonal
maps all the available data between 1985 to 1994 were used.
The seasonal contour maps also show the location of the PM10 monitoring sites. The
size of the rectangle at each site is proportional to the quarterly average PM10 concentration
6-47
-------
using all available data between 1985 to 1994. Hence, sampling biases due to station density
that changed over time can not be excluded.
The quarterly concentration pattern of PM10 is shown in Figure 6-18. The high
sampler density allows the resolution of spatial texture on the scale of 100 km, particularly
over major metropolitan areas. However, remote regions in the central and western states
have poor spatial density. In the absence of rural monitoring data computerized contour
plotting of PM10 is biased toward extrapolating (spreading) high concentrations over large
areas. This bias is particularly evident in the maps for Quarters 1 and 4 in the western states,
where the area of high concentration hot spots is exaggerated.
The AIRS PM10 concentrations over the eastern United States are lowest during
Quarter 1, ranging between 20 to 30 /ug/m3. The higher concentrations exceeding 30 Mg/m3
are confined to metropolitan areas.
6.3.2.1 National Pattern and Trend of Aerometric Information Retrieval System PM10
Two trend analysis approaches were used to obtain the 1988 to 1993 trends in PM10
shown in Figure 19b are subsequent figures providing AIRS concentration patterns. One of
these approaches uses all of the available stations operational each year between 1988 and
1994. The second approach uses only those stations operational from 1988 to 1994, the long
term coverage, trend, stations.
During the 1988 to 1994 period there were decreases in the annual average PM10 for
the continental U.S. from 33 //g/m3 to 25 /ug/m3, for all sites and from 35 Aig/m3 to 28 /ug/m3
for trend sites resulting in 24% or 20% reductions in PM10.
The Figure 6-19b also shows the standard deviation among the yearly average PM10
concentrations for each year. On the national scale the standard deviation of yearly average
concentrations is about 40% of the mean.
The concentrations of PM2 5 and PM10 are compared in the scatter chart in
Figure 6-19c. Each point represents a pair of PM2 5-PM10 monthly average concentrations.
The diagonal line is the 1:1 line and shows the fine particle concentration ranges between
20 and 85% of PMi0. The heavy solid line is derived from a linear best fit regression. The
detailed correlation statistics is reproduced in the upper-left corner of the scatter charts. The
6-48
-------
Quarter 1
Quarter 2
PMIOMass
ng/m3
50
140
30
20
[10
0
PM10 Mass
Quarter 3
Quarter 4
PM10 Mass
u.g/m3
150
140
130
120
[10
0
PM10 Mass
Figure 6-18. AIRS PM10 quarterly concentration maps using all available data.
-------
PM10 Average - Continental US
(a)
PM10 Cone. Trend - Continental U.S.
EPA AIRS database
150
140
130
120
110
100
m
^ 90
o>
^
uT 80
e\i
I 70
60
50
40
30
20
10
PM2.5 vs. PM10 - Conterminous U.S.
EPA AIRS - Monthly Averages
CORRELATION STATS:
Avg X : 33.67
AvgY: 19.23
Avg Y/Avg X : 0.57
CorrCoeff: 0.82
Slope : 0.56
Y offset • 0.24
Data Pointi • 2269
(c)
20
40 60
80
PM10(pg/rri )
100 120 140
3v
1988 1969 1990 1991 1992 1993 1994
-A- Avg for all sites -B- Avg for trend sites
-+- Avg + Std. Dev. -9- Avg - Std. Dev.
Seasonal PM Pattern - Continental U.S.
EPA AIRS Database
50
5
a. 25
20
(d)
1986 Mar May Jul Sep Nov
-A-PM10 -B-PM2.5 -t-PM Coarse
Figure 6-19. AIRS PM10 and PM2.5 concentration patterns for the conterminous
United States.
6-50
-------
ratio of overall average PM2 5 and overall average PM10 is also indicated. For the data when
both PM2.5 and PM10 data were available, nationally aggregated PM2 5 particles accounted for
57% of the PM10 mass.
The seasonal pattern of the national PM10 concentration is also depicted in
Figure 6-19d, utilizing all available data in AIRS. The national average PM10 seasonally
ranges between 27 /ug/m3 in March and April, and 33 /ug/m3 in July and August, yielding a
modest 16% seasonal modulation. There is also evidence of slight bimodality with the
December through January peak.
The seasonal chart also shows the annual variation of PM2 5, and PM10-PM2 5 (i.e.,
coarse particles). The national fine particle concentration shows clear evidence of bimodality
with peaks in July and December. It is shown below that the fine particle winter peak arises
from western sites, while the summer peak is due to eastern U.S. contributions. The national
average coarse particle concentration has a 50 % yearly modulation with a single peak in July.
Stratifying the national PM10 concentrations one can obtain results showing that the
country has several major aerosol regions, as discussed in more detail below. Each region has
a discernible geographic extent as well as seasonal pattern. Over the plains of the eastern
United States the spatial texture of PM10 is driven by the pattern of the emission fields, while
the seasonality of concentrations is likely to be determined by the chemical transformation and
removal processes, as well as by the regional dilution. In the mountainous western and Pacific
states, pockets of wintertime PM10 concentrations exist that well exceed the eastern U.S.
values. It is believed that haze and smoke in confined mountain valleys and air basins are
strongly influenced by topography which in turn influences the emission pattern, dilution, as
well as the chemical transformation and removal rate processes.
Given the regionality of the aerosol concentration pattern much of the discussion that
follows will be focused on the characteristics of these aerosol regions. The Rocky Mountains
produce a natural division between the eastern and western aerosol regimes which will be
discussed next.
6-51
-------
6.3.2.2 Eastern U.S. PM10 Pattern and Trend
During the 1988 to 1994 period there were decreases in the annual average PM10 for
the eastern U.S. from 31 Mg/rn3 to 26 //g/m3 for all sites and from 34 /ug/m3 to 28 fj.g/m3 for
trend sites resulting in 16% or 18% reductions in PM10 (Figure 6-20b). The decline is rather
steady over time.
The highest eastern U.S. AIRS PM10 concentrations are recorded in Quarter 3
(Figure 6-20d). The peak concentrations are over the Ohio River Valley stretching from
Pittsburgh to West Virginia, southern Indiana and St. Louis. In this region, the PM10
concentration over the industrialized Midwest during the summer can exceed 40 /ug/m3.
Additional hot-spots with > 40 //g/m3 are recorded in Birmingham, AL, Atlanta, GA,
Nashville, TN, Philadelphia, PA and Chicago. IL. The summertime PM10 concentrations in
New England and upstate Michigan are < 20 //g/m3.
The transition seasons Quarters 2 and 4 (Figure 6-20d) show PM10 concentrations
ranging from 25 Atg/m3 to about 30 /ug/m3 over much of the eastern U.S., with concentration
hot-spots over the industrial Midwest as well as in the Southeast, Atlanta, GA and
Birmingham, AL. The PM10 concentrations in urban-industrial "hot-spots" exceed their rural
surrounding by less than a factor of two.
The spatial variability of PM10 occurring over the eastern United States is driven
primarily by the varying primary aerosol emission density. This can be deduced from the
coincidence of higher concentrations within urban industrial areas. The atmospheric dilution
(i.e., horizontal and vertical dispersion) in these areas is not likely to be spatially variable.
Also, the chemical aerosol formation and removal processes are likely to have weak spatial
gradients when averaged over a calendrical quarter. Hence, the main factor that is believed to
be responsible for the spatial variability is the emission field of primary PM10 particles and the
SO2, NOX, and VOC precursors of secondary aerosols.
PM10 concentration in excess of 30 //g/m3 is recorded over the agricultural states of
Iowa, Kansas, Nebraska, and South Dakota. The elevated PM10 concentrations over this
region tend to persist over all four seasons. The eastern PM10 seasonality (Figure 6-20d) is
rather pronounced, with winter concentrations (December through March) of 24 /ug/m3, and
6-52
-------
PM10 Average - Eastern US
PM10 Cone. Trend - Eastern U.S.
EPA AIRS database
PM2.5 vs. PM10 - Eastern U.S.
EPA AIRS - Monthly Averages
140
130
120
110
100
co 90
CORRELATION STATS:
AvgX- 31.4
AvgY: 18 86
Avg Y/Avo X . 06
CorrCoeff. 0.63
Slope 0.58
Y off»et: 0.35
Data Polntt • 1651
(c)
198B 1989 1990 1991 1992 1993 1994
•A- Avg for all sites -H-Avg for trend sites
-l-Avg + Std. Dev. -e-Avg - Std. Dev.
Seasonal PM Pattern - Eastern U.S.
EPA AIRS Database
55
50
45
40
0)
25
15
20 40 60 80 100 120
PM10(Mg/m3)
140
(d)
1986 Mar May Jul Sep Nov
-A-PM10 -B-PM2.5 -I-PM Coarse
Figure 6-20. AIRS concentration data for east of the Rockies: (a) monitoring locations;
(b) PM10 concentration trends; (c) PM10 and PM2.5 relationship; and
(d) PM10, PM2 5, and PMCoarse seasonal pattern.
6-53
-------
July through August peak of 35 ^g/rn3. The amplitude of the PM10 seasonal concentrations is
about 30%.
The scatter chart of the eastern AIRS PM2 5-PM10 relationship shows a significant
amount of scatter, with a slope of 0.58 (Figure 6-20b). The ratio of the overall average PM2 5
and PM10 concentration is 0.6 such that 60% of PM10 in the sub 2.5 pan size range. The
seasonally of the fine AIRS particle concentration over the East is bimodal with a major peak
in July and a smaller winter peak in January (Figure 6-20d). As shown in Figure 6-15b, the
nonurban IMPROVE/NESCAUM network results for the eastern U.S. for PM2 5 show a peak
in summer but does not show a winter peak. The coarse particle concentration shows a single
broad peak over the warm season, April through October (Figure 6-20d), but with a somwhat
different pattern than shown in Figure 6-15b for nonurban cities in the eastern U.S. It is
therefore evident that fine and coarse particles (from urban and nonurban measurements) have
different seasonal dynamics in the East.
6.3.2.3 Western U.S. PM10 Pattern and Trend
The mountainous states, west of the Rockies (Figure 6-21) have higher PM10
concentrations in Quarters 1 and 4 than in Quarters 2 and 4 and shown ever higher PM10
concentrations (>50 /-fg/m3) at localized hot-spots. These higher concentrations occur over
both metropolitan areas such as Salt Lake City, as well as in smaller towns in mountain valleys
of states west of the Rockies.
The main geographic feature regions considered in California are the Los Angeles basin
and the San Joaquin Valley. Both basins show monthly PM10 concentrations sometimes in
excess of 50 /ug/m3. These basins are also confined by surrounding mountains that limit the
dilution, facilitate cloud formation, and have emissions that are confined to the basin floor.
Accordingly, they represent airsheds with characteristic spatial and temporal pattern. It is
likely that the actual local effects on the PM10 concentration field in the mountainous western
states are greater than depicted in Figure 6-21a.
It appears that the spatial pattern of these high concentration hot spots is driven by
emissions as well as by the restricted wintertime ventilation due to mountainous terrain. Over
the mountainous western states the atmospheric dilution by horizontal and vertical dispersion is
6-54
-------
PM10 Average -Western US
PM10 Cone. Trend - Western U.S.
EPA AIRS database
150
140
13D
120
110
100
80
dp
| B0
in 70
CM
Q. 60
50
40
30
20
10
PM2.5 vs. PM10 - Western U.S.
EPA AIRS - Monthly Averages
CORRELATION STATS:
AvgX:
AvjY:
Avg Y/Avg X
Corr Coftff:
Slope :
Y offwt:
Data Points : 618
20 40 60 80 100 120 140
PM10 (pg/m3)
40
I351
(b) .
1988 1989 1990 1991 1992 1993 1994
-A- Avg for all sites -B- Avg for trend sites
-I- Avg + Std. Dev. -©- Avg - Std. Dev.
Seasonal PM Pattern - Western U.S.
EPA AIRS Database
55
5
a.
(d)
1986 Mar May Jul Sep Nov
-A- PM10 -B- PM2.5 -+- PM Coarse
Figure 6-21. AIRS concentration data for west of the Rockies: (a) monitoring trends;
(b) PM10 concentration trends; PM10 and PM2t5 relationship; and (d) PM10,
PM2 5, and PMCoarse seasonal pattern.
6-55
-------
severely restricted by mountain barriers and atmospheric stratification due to strong and
shallow inversions. Radiative cooling also causes fog formation which enhances the
production rate of hydroscopic aerosols in the valleys. As a consequence, mountain tops are
generally protruding out of haze layers. Emissions arising from industrial, residential,
agricultural, unpaved roadways and other sources are generally confined to mountain valleys.
In the wintertime the mountain valleys are frequently filled with fog. All three major factors
that determine the ambient concentrations (i.e., emissions, dilution, and chemical rate
processes) are strongly influenced by the topography. For this reason, many of the maps
depicting the regional pattern use shaded topography as a backdrop.
In the western half of the U.S., west of and including the Rockies, there was a decrease
in the PM10 concentration of 1988 to 1994 from 36 /ug/m3 to 25 jUg/m3 for all sites and from
39 (Ug/m3 to 28 ,ug/m3 for trend sites (Figure 6-2 Ib). The reductions were 31% for all sites
and 28% for trend sites. Standard deviation among the western stations of yearly average
PM10 concentrations is about 40%.
The western AIRS PM2 5-PM10 relationship (Figure 6-21c) shows that on the average
about 50% of the PM10 is contributed by fine particles. The scatter of data points
(Figure 6-21c) also shows that during high concentration PM10 episodes the fine fraction
dominates.
The western PM10 seasonality (Figure 6-2Id) is also rather pronounced, having about
30% amplitude. However, the lowest concentrations (26 Atg/m3) are reported in the late spring
(April through June), while the highest values occur in late fall (October through January).
The seasonality of PM2 5 west of the Rockies (Figure 6-21d) is strongly peaked in
November through January. In fact, the PM2 5 is several times higher than the summertime
values. On the other hand, the coarse fraction shows a broad peak during late summer, July
through October. It is to be noted that in Figures 6-20 and 6-21, the fine and coarse particle
concentrations do not add up to PM 10, because size resolved samples were only available for
tens of sites, while the PM10 concentrations were obtained from hundreds of monitoring
stations.
In summary, there is a 20 to 24% reduction of PM10 concentrations for the continental
U.S. between 1988 and 1993. On the national average the PM10 seasonality is weak.
6-56
-------
Desegregation of the national averages into east and west of the Rockies, shows that the
downward trend west of the Rockies is more pronounced than over the eastern half of the U.S.
The east-west desegregation also shows that the lack of national PM10 seasonally arises from
two strong seasonal signals that are phase shifted, the eastern United States has a summer
peak, the West a fall and winter peak, and the sum of two signals is a weakly modulated
seasonal pattern. Nationally, PM2 5 mass accounts for about 57% of PM10 mass. The East
and West show comparable average fine particle fractions (60% in the East and 50% in the
West). Fine particles tend to dominate during the fall and winter season in the western U.S.,
except in the southwest.
It is evident that further examination discussed in the next sections will show that the
East-West division itself is rather crude and that dividing the conterminous United States into
additional subregions is beneficial in explaining the PM10 concentration pattern and trends.
6.3.2.4 Short-Term Variability of PM10 Concentrations
The previous aerosol concentration patterns were expressed as quarterly averages.
However, for health and other effects, the variance of the concentration, in particular the
occurrence of extreme high concentrations is of importance. The PM10 concentrations exhibit
marked differences in the shape of their distribution functions around the mean values. For
example in Figure 6-22, the day to day variations of PM10 concentrations in Knoxville, TN are
about 40% of the mean value of 35 /ug/m3. On the other hand, the concentration time series
for Missoula, MT shows a coefficient of variation of 60% over the mean of 34 ^g/m3. During
the winter season the coefficient of variation is even higher. It is therefore evident, that for
comparable mean concentrations the Missoula, MT site exhibits significantly higher short-term
variations. Also note the large variations from a high concentration day to the lower
concentrations on the day before and/or the day after (Figure 6-22).
The variability of concentration is examined spatially and seasonally by computing
logarithmic standard deviation (ratio of 84/50 concentration percentiles) for each monitoring
site. These deviations were then contoured for each season. The results are depicted in the
seasonal maps of the logarithmic standard deviation (Figure 6-23). The highest logarithmic
standard deviation is recorded over the northern and northwestern states during the cold
6-57
-------
'239
Mean
CoVa
Min
Max
Points
1988
80
60
1989
1990
1991
1992
1993
40
20
Mean
CoVa
Min
Max
Points
35
39.92
9
73
258
1988
1989
1990
1991
1992
1993
Figure 6-22. Short-term PM10 concentration time series for Missoula, MT, and
Knoxville, TN.
season, Quarters 1 and 4. Regionally, the logarithmic standard deviation in the north-
northwest is about 2.0 with pockets of high winter variability such as Salt Lake City, UT, and
Missoula, MT. The lowest variability prevails over the warm season, Quarters 2 and 3,
covering the southeastern and southwestern states. Over multistate regions in the southern
states the summertime logarithmic standard deviation is below 1.5. This means that these
areas are covered more or less uniformly by summertime PM10, while the northern states are
more episodic.
6-58
-------
Quarter 1
Quarter 2
o\
Quarter 3
Quarter 4
'Q "9
Figure 6-23. Geographic variation of the standard deviation, og, of the lognormal distribution of PM10 concentrations from
the AIRS.
-------
6.3.2.5 Aerometric Information Retrieval System PM2 5 Concentrations
The mass concentration of fine particles in urban areas is not well known. Sampling and
analysis of PM25 is limited by small number of stations (<50), sampling period restricted to
few years, and different, non-standard sampling equipment was utilized for PM2 5
The yearly average AIRS PM2 5 concentrations are shown in Figure 6-24. Figure 6-24
also shows the location and magnitude of PM2 5 concentrations from measurements of
IMPROVE/NESCAUM monitoring networks. The fine particle data from the
IMPROVE/NESCAUM show a pattern of high concentrations (> 15 /-ig/m3) occurring over
the eastern United States. This pattern of nonurban fine particle concentrations was discussed
in Section 6.3.1.
6.3.2.6 Other National Surveys
A summary of urban PM10, PM2 5, PMCoarse at eight urban areas, Birmingham, AL,
Buffalo, NY, Houston, TX, Philadelphia, PA, Phoenix, AZ, Pittsburgh, PA, Rubidoux, CA,
and Steubenville, OH was reported by Rodes and Evans (1985). The overall ratio of the PM10
to Total Suspended Paniculate (TSP) was 0.486. The relationships between PM10 and the
15 fj.m fraction (IP) are linear for all sites. With exception of Phoenix, AZ, and Houston, TX,
PM2 5 exceeded the PMCoarse mass concentration in all six urban areas.
Spengler and Thurston (1983) reported PM concentrations in six U.S. cities: Portage,
WI, Topeka, KS, Kingston, TN, Watertown, MA, St. Louis, MO, and Steubenville, OH,
using dichotomous virtual impactors in the two size ranges, PM2 5 , having dp<2.5 //m, and
coarse particle mass with 2.5
-------
AIRS PM2.5 - IMPROVE PM2.5 Comparison
Os
AIRS PM2.5
IMPROVE/NESCAUM PM2.5
Figure 6-24. Annual PM2-5 concentration pattern obtained from IMPROVE/NESCAUM and AIRS networks.
-------
30
20
10
Portage, Wl
• IP mass
* Fine mass
_ • Course mass
• Total sulfate mass
JFMAMJJASONDJFMAMJJASONDJFMAMJJASOND
1979 1980 1981
Harriman, TN
OU
50
40
CO
E
^>30
20
10
: / V*.
•. \
/ *
> \ *
* • / \-«
/ *
•^'s^v.V
*• •• «> *
•<
•IP mass
* Fine mass .
•Course mass
* Total sulfate mass .
» ,^B
V
•
•
k •*
.•••*
f"
JFMAMJJASONDJFMAMJJASONDJFMAMJJASOND
1979 1980 1981
90
80
70
60
50
40
30
20
10
Topeka, KS
• IP mass
A Fine mass
• Course mass
•Total sulfate mass
\ /
60
50
JFMAMJJASONDJFMAMJJASONDJFMAMJJASOND
1979 1980 1981
Watertown, MA
40
m
E
20
10
• IP mass
• Fine mass
. • Course mass
• Total sulfate mass
JFMAMJJASONDJFMAMJJASONDJFMAMJJASOND
1979 1980 1981
70
60
50
CO
E 40
o>
20
10
St. Louis, MO
• IP mass
•Fine mass
'Course mass
'Total sulfate mass
JFMAMJJASONDJFMAMJJASONDJFMAMJJASOND
1979 1980 1981
90
80
70
60
m
E50
=L40
30
20
10
Steubenville, OH
•IP mass
•Fine mass
•Course mass
•Total sulfate mass
1 *
A A' ^ /' r.
li. . i • . \ i \ i
JFMAMJJASONDJFMAMJJASONDJFMAMJJASOND
1979 1980 1981
Figure 6-25. Monthly mean concentrations in micrograms per cubic meter of PM15 (IP,
inhalable mass), PM2 5 (fine mass), coarse mass (PM15-PM2 5), and total
sulfate as (NH^SC^ in Portage, WI; Topeka, KS; Harriman, TN;
Watertown, MA; St. Louis, MO; and Steubenville, OH.
6-62
-------
The quartz content and elemental composition of aerosols, collected in dichotomous
samplers in selected sites in the EPA Inhalable Participate network, were reported by Davis
et al. (1984). For all network sites, an average of only 4.9 weight per cent of the coarse
particle mass and 0.4 weight per cent of the fine mass consisted of quartz. Continental interior
sites show the highest average quartz content as well as the greatest variability. The coastal
regions and eastern interior sites reveal the lowest quartz concentrations. The complete X-ray
spectra from some samples in Portland, OR, show that Si comes primarily from minerals such
as feldspars, where the Si in the Buffalo, NY aerosols comes from quartz.
6.3.3 Comparison of Urban and Nonurban Concentrations
Seasonal maps of the AIRS PM10-IMPROVE/NESCAUM PM10 spatial concentrations
are given in Figure 6-26. In evaluating the subsequent comparisons of the differences between
AIRS and IMPROVE/NESCAUM spatial concentrations possible sampling biases and
differences in sampling equipment and monitoring protocols may be significant. In addition,
the differences in geographical location between the stations for the two networks also can
influence the reliability of these comparisons. The AIRS PM2 5 concentrations everywhere
exceed their adjacent IMPROVE/ NESCAUM concentrations. The highest AIRS PM2 5 are
reported over the eastern urban industrial centers, such as Philadelphia and Pittsburgh, where
the concentrations of 20 to 30 /ug/m3 exceed the nonurban PM2 5 by a factor of 2 to 3.
However, the excess urban PM2 5 concentrations are evidently confined to the immediate
vicinity of urban centers. This indicates that over the eastern United States a regionally
homogeneous background of PM2 5 concentration exists that has smooth spatial gradients.
Superimposed on the smooth regional pattern are local hot-spots with excess concentrations of
factor of 2 to 3 that are confined within a few miles of urban industrial centers. The regional
homogeneity is an indication that the eastern U.S. PM2 5 is composed of a secondary aerosol
that is produced several days after the emission of its gaseous precursors. Similar results have
been discussed for SO42" since the 1970's (Altshuller, 1980). The excess PM2 5 concentration
in urban centers suggests that primary emissions such as automobile exhaust and heating
furnaces are responsible for much the urban PM2 5 hot-spots.
6-63
-------
Quarter 1
Quarter 2
PM10 AIRS - PM10 IMPROVE
PM10 AIRS - PM10 IMPROVE
Quarters
Quarter 4
PM10 AIRS - PM10 IMPROVE
PM10 AIRS - PM10 IMPROVE
Figure 6-26. Spatial maps of PM10 concentration difference between AIRS and IMPROVE/NESCAUM networks.
-------
The reported AIRS PM2 5 concentrations over the Pacific states are generally higher and
average at 20 to 50 /ug/m3. This is 5 to 10 times higher than their companion IMPROVE
PM2 5 concentrations. The dramatic difference is attributable to the pronounced concentration
differences between urban-industrial-agricultural centers that exist in mountainous air basins
and the concentrations monitored at remote national parks and wilderness areas that are
generally at higher elevations. However, it is fair to presume that the AIRS and IMPROVE
PM2 5 data sets represent the extreme of aerosol concentration ranges that exist over the
western U.S. The challenging task of filling in the details (i.e., spatially and temporally
extrapolating the aerosol concentrations over the rugged western United States) is discussed in
further detail in later regionally and locally focused sections below.
Comparisons have been made of the seasonality of the urban (AIRS) concentrations
relative to the nonurban (IMPROVE/NESCAUM) data. In Figure 6-27 the difference in
PM10, PM2.5, and PMCoarse between AIRS and IMPROVE/NESCAUM sites, using all
available data, is used to indicate the urban excess particle concentration compared to the rural
concentration. No attempt has been made to evaluate the possible uncertainties in these
difference values.
Nationally, the urban excess fine particle concentration ranges between 18 //g/m3 in
December through February and 10 /^g/m3 in April through June (Figure 6-21 a). The urban
excess coarse mass concentration ranges between 10 to 7 ,ug/m3. The sum of the fine and
coarse national urban excess mass concentration is about 25 ,ug/m3 in the winter season, and
18 /ug/m3 during the spring season. Hence, the nationally aggregated urban and nonurban data
confirm that urban areas may have excess concentrations on the order of 20 yug/m3, and well
over half is due to fine particles, particularly in the winter season.
The urban excess (AIRS-IMPROVE/NESCAUM difference) over the eastern United
States (Figure 6-27b) shows fine particles excess of 8 to 12 /-tg/m3, with higher value
occurring during both winter and summer. The urban excess coarse mass in the eastern
United States is only 5 to 8 //g/m3, peaking during spring and summer. The sum of fine and
coarse urban excess is 15 to 18 ,ug/ni3 throughout the year.
6-65
-------
Urban Excess
60
I—I—I—I—I—I—I—I—I—I—I
Jan Mar May Jul Sep Nov Jan Jan Mar May Jul Sap Nov Jan Jan Mar May Jul Sep Nov Jan
Fine + Coarse Mass
Fine
— c— Coarse
Figure 6-27. Urban excess concentrations (AIRS minus IMPROVE) for (a) the United
States, (b) the eastern United States, and (c) the western United States.
The excess urban (AIRS-IMPROVE/NESCAUM) aggregated over the western United
States is much more pronounced in magnitude and seasonality. The urban excess fine mass is
about 30 A^g/m3 in November through January and drops to 8 to 10 Mg/m3 in April through
August. The urban excess coarse mass is less in magnitude and seasonality 15 to 18 y.g/m3 in
July through December, and 10 to 12 yug/m3 in March through May. The sum of the urban
excess fine and coarse mass is 40 to 50 //g/m3 in November through January and about
20 Mg/m3 in the spring March through June. The urban AIRS and nonurban IMPROVE)
networks in the western United States monitor aerosols differently because of different goals
and mandates. The urban nonurban difference is such that the western nonurban
concentrations contribute little to the much higher urban values, particularly in the winter
season. On the other hand, the eastern urban sites are greatly influenced by the nonurban,
regionally representative concentrations, particularly in the summer season.
6-66
-------
6.4 REGIONAL PATTERNS AND TRENDS
This section describes the spatial, temporal, size, and chemical characteristics of seven
aerosol regions of the conterminous U.S. The sizes and locations of these regions were
chosen mainly on the basis of the characteristics of their aerosol pattern. The main criteria for
delineating a region were (1) the region had to possess some uniqueness in aerosol trends,
seasonality, size distribution, or chemical composition; (2) each territory of the conterminous
United States had to belong to one of the regions; and (3) for reasons of computational
convenience the shape of the regions were selected to be rectangular on unprojected latitude
longitude maps. The resulting criteria yielded seven rectangular aerosol regions as shown in
Figure 6-28. It is recognized that this selection is arbitrary and for future analysis additional
regional definition criteria would be desirable. The limitations in the data bases of the two
different networks discussed previously also apply to the subsequent discussion.
For sake of consistency and intercomparisons each region is described using maps
delineating the spatial pattern and the sampling locations in the subsequent figures (Section a).
For the figures showing AIRS monitoring results, Section b shows trends in average PM10
concentrations and ± a. As discussed in Section 6.3.2.1 included in (b) are the results of two
trend analyses. One of these uses the annual concentrations from all available stations in
operation any time in the 1985 to 1994 period. The second approach uses the annual
concentrations from only those stations operated continuously from 1985 to 1994, the long
term coverage or trend stations. Section c show plots and correlations relating PM10 and
PM2.s. Monthly AIRS concentrations (Section d) for a given region were computed by
averaging all the available data for the specific month. In case of nonurban aerosol chemistry
some regions only had two to four monitoring stations. The monthly nonurban PM2 5,
PMCoarse and PM10 shown in the subsequent figures (Section b) over regions illustrate the
relative seasonality of each aerosol type. The nonurban regional average chemical
composition is presented as seasonal charts of chemical aerosol components as a fraction of the
fine mass concentration (Section c). The role of some primary sources, such as coal and fuel
oil combustion is indicated through seasonal charts of selenium (coal) and vanadium (fuel oil)
trace metals (Section d). In addition, for each region figures will be provided showing shorter
term variability of PM10 concentrations and PM10 urban excess concentrations.
6-67
-------
Northwest
PM10 = 28
PM2.5= 16
PM2.5/10 = 0.59
Upper
Midwest
PM10 = 31
PM2.5 = 12
PM2.5/10 = 0.38
Industrial
Midwest
PM10 = 29
PM2.5=17
PM2.5/10 = 0.59
Northeast
PM10 = 34
PM2.5 = 21
PM2.5/10 = 0.62
S.California
PM10=53
PM2.5=26
PM2.5/10=0.49
Southeast
PM 10=29
PM2.5=17
PM2.5/10=0.58
Southwest
PM10=34
PM2.5=12
PM25/10=037
Figure 6-28. Aerosol regions of the conterminous United States.
6.4.1 Regional Aerosol Pattern in Eastern New York, New Jersey, and the
Northeast
The Northeast aerosol region covers the New England states, including eastern
Pennsylvania and eastern Virginia to the south (Figure 6-29a). In the Northeast, terrain
features that significantly influence regional ventilation occur over the mountainous upstate
New York, Vermont and New Hampshire. Throughout the year, the Northeast is influenced
by Canadian as well as Gulf air masses. The region includes the Boston-New York
megalopolis, as well as other urban-industrial centers. It is known that the Northeast is
influenced by both local sources, as well as long range transport of fine particles and
transformations of precursors to particles from other regions, as well as transport
6-68
-------
PM2.5 Concentration - Northeast
IMPROVE/NESCAUM Data
Chemical Fine Mass Balance - Northeast
IMPROVE/NESCAUM Data
0.7
0.5
o
c
o
73 0.4
0.0
1989 Mar
May Jul Sep Nov
-B-oc -(-Soil
-©-Sulfate + OC + Soil + EC
PM10, PM2.5 and PMC - Northeast
IMPROVE/NESCAUM Data
40,000
1989 Mar May Jul Sep Nov
-+- PM2.5 -A- PM Coarse
Chemical Tracers - Northeast
IMPROVE/NESCAUM Data
4,000
3.500
3,000
2.500
a
1 2.000
c
o
O
1,500
1,000
500
(d)
1989 Mar May Jul
-A- Sulfur - Max = 4000
-+- Vanadium - Max =10
Sep Nov
-B- Selenium - Max = 4
-e- S/Se - Max = 4000
Figure 6-29. IMPROVE/NESCAUM concentration data for the Northeast: (a) monitoring
locations; (b) PM10, PM2 5, and PMCoarse (PMC); (c) sulfate, soil, organic
carbon (OC), and elemental carbon (EC) fractions; and (d) tracers.
6-69
-------
and transformation of precursors in single and multiple urban plumes within the region
(Chapter 3).
6.4.1.1 Nonurban Size and Chemical Composition in the Northeast
The summary of the nonurban aerosol chemical composition in the Northeast is presented
in Figure 6-29c. The region has 14 monitoring sites, 8 of which are part of NESCAUM in
upper New England. The geographic locations with respect to nearby urban areas vary from
those sites within the northeast corridor to rural sites near the Canadian border.
The PM10 concentration exhibits a factor of two seasonal amplitude between 12 /ug/m3 in
the winter, and 25 //g/m3 in June and July (Figure 6-29b). About 60% of PM10 is contributed
by fine particles throughout the year. The PM2 5 also contributes to the summer-peaked
seasonality.
Data from a two year fine particle network in the Northeast (Bennett et al., 1994) yielded
a geometric mean concentration of PM2 5 of 12.9 ,ug/m3 and particulate sulfur (1.4 Mg/m3,
equivalent to 4.2 A*g/m3 of sulfate), which is somewhat lower than other comparable rural
data.
Sulfates are the most important contributors of the fine particle mass in the Northeast,
particularly in the summer season when they account for half of the fine mass (Figure 6-29c).
The regionality of sulfate in the northeastern U.S. has been dicussed for many years
(Altshuller, 1980). The organic carbon ranges from 30 to 40%, with the higher percentages
occurring in the fall and winter, September through January. In fact, during the late fall the
contributions of sulfate and organic carbon are comparable at 40%. Fine particle soil is
unimportant throughout the year (<5%). Elemental carbon, on the other hand, is somewhat
more significant, particularly during the fall when it contributes about 10% of the fine mass.
The sum of the above four nonurban fine particle aerosol components, account for over 90%
of the measured fine particle mass throughout the year. These results would appear to indicate
ammonium ion, hydrogen ion, nitrates, trace metals and sea salt are of minor importance in
the northeastern U.S. fine particle chemical mass balance.
6-70
-------
The seasonality of both selenium and vanadium indicates a winter peak (Figure 6-29d).
In particular, the vanadium concentration increases by a factor of two for December and
January compared to the summer values. Also, the V concentration is higher than over any
other region indicating the strongest contribution of fuel oil emissions. The S/Se ratio is
strongly seasonal with a winter value of 1,000 and a summer peak of 2,000 to 2,500 consistent
with a substantial secondary photochemical contribution of SO42" during the summer.
6.4.1.2 Urban Aerosols in the Northeast
In the northeastern U.S. there was a decrease in the annual average PM10 concentration
between 1988 and 1994 from 28 /ug/m3 to 23 //g/m3 for all sites and from 31 /ug/m3 to
25 ,ug/m3 for trend sites (Figure 6-30b). The reductions were 18% for all sites and 19% for
trend sites. The standard deviation among the monitoring stations for any given year is about
30%. The map of the Northeast shows the magnitude of PM10 concentrations in proportion of
circle radius. The highest AIRS PM10 concentrations tend to occur in larger urban centers
(Figure 6-30a).
The seasonality of the urban Northeast PM10 concentration (Figure 6-30d) is a modest
20%, ranging from 25 to 31 Mg/m3, smaller than the seasonality of the nonurban northwest
PM10 (Figure 6-29b). There is a summer peak in July, and a rather uniform concentration
between September and May showing only a slight winter peak. The PM2 5-PM10 relationship
(Figure 6-30c) shows that on the average 62% of PMj0 is contributed by fine particles.
In general, the regional scale emissions are not expected to vary significantly from one
day to another. However, both meteorological transport (i.e., dilution), as well as aerosol
formation and removal processes, are important modulators of daily aerosol concentration.
The daily concentration of particulate matter exhibits strong fluctuation from one day to
another, mainly due to the role of the meteorological transport variability.
The regionally averaged daily concentration is associated with the regional scale
meteorological ventilation. High regionally averaged concentrations indicate poor ventilation
(i.e., a combination of low wind speeds and low mixing heights and the absence of fast aerosol
removal rates, such as cloud scavenging and precipitation). Low regional concentrations, on
the other hand, represent strong horizontal transport, deep mixing heights, or high regional
6-71
-------
PM10 Average - Northeast
PM10 Cone. Trend - Northeastern U.S.
EPA AIRS database
140
no
120
110
100
5
a.
PM2.5 vs. PM10 - Northeast
EPA AIRS - Monthly Averages
?988 1989 1990 1991 1992 1993 1994
-A- Avg for all sites -B- Avg for trend sites
-f-Avg + Std. Dev. -©-Avg - Std. Dev.
Seasonal PM Pattern - Northeast
EPA AIRS Database
(c)
CORRELATION STATS
Avg X : 34 28
AvgY:
Avg Y/Avg X
Corr Coeff:
Slop* :
YoffMt:
D»ta Points •
80
55
so
45
i35
(d)
20 40 60 80 100 120 140
PM10(pg/m3)
1986 Mar May Jul
-A-PM10 -B-PM2.5
Sep Nov
• PM Coarse
Figure 6-30 AIRS concentration data for the Northeast: (a) monitoring locations;
(b) regional PM10 concentration trends; (c) PM10 and PM2>5 relationship;
and (d) PM10, PM2.s> and PMCoarse seasonal pattern.
6-72
-------
removal rates. Advection of high aerosol content air masses from neighboring regions may
also be a cause of elevated concentration in a given region.
The daily variation of the regional averaged urban PM10 concentration for the Northeast
is shown in Figure 6-31. The single day concentration data for every sixth day are connected
by a line between the data points, although five in-between days are not monitored. The
lowest regionally averaged daily urban PM10 is about 10 /wg/m3, while the highest is about
55 //g/m3, with a regional average in the early 1990s of 25 /ag/m3. The highest concentrations
(> 40 /ug/m3) occur primarily in the summer season. The time series also indicate that the
high concentration episodes do not persist over consecutive six day periods. This is consistent
with the notion that the regional ventilation that is caused by synoptic scale air mass changes,
which typically occur every four to seven days over eastern U.S. The daily time series also
convey the fact that day to day variation in PM10 is higher than the seasonal amplitude. In
fact, in Figure 6-31 the concentration seasonality is barely discernible. It can be stated,
therefore, that the PM10 concentration in the Northeast is highly episodic (i.e., the temporal
concentration variation is both substantial and irregular). The excess urban PM10 (AIRS-
IMPROVE) is shown in Figure 6-32. The excess urban PM10 concentration in the Northeast
is a relatively small part of the total urban PM10 concentration between May and October.
The reliability of such estimates of excess regional urban PM10 concentrations discussed
earlier should be considered (Section 6.3.3).
6.4.2 Regional Aerosol Pattern in the Southeast
The Southeast rectangle stretches from North Carolina to eastern Texas (Figure 6-33).
From the point of view of regional ventilation the Southeast terrain is flat, with the exception
of the mildly rolling southern Appalachian Mountains. The region is known for increasing
population over the past decades, high summertime humidity, and poor regional ventilation
due to stagnating high pressure systems.
6.4.2.1 Nonurban Size and Chemical Composition in the Southeast
Only six nonurban stations were available in the Southeast with the absence of
monitoring over the southern (Gulf Coast) part of the region, except for Florida. The
6-73
-------
Northeast Every Sixth Day
CO
5
a.
1991
1992
1993
Figure 6-31. Short-term variation of PM10 average for the Northeast. Data are reported
every sixth day.
40
Northeast urban excess
35 --
30 --
25
O)
20 +
10 --
0
Jan Mar May Jul Sep Nov Jai
Figure 6-32. Urban excess concentration (AIRS minus IMPROVE) for the Northeast.
6-74
-------
PM2.5 Concentration - Southeast
IMPROVE/NESCAUM Data
Chemical Fine Mass Balance - Southeast
IMPROVE/NESCAUM Data
0.9
« °7
«
m
S
a 0.8
0.3
(c)
0.0
1989 Mar
-^Sulfate
-e-EC
May Jul Sep Nov
-B-QC n-Soll
-e>-Sulfate + OC + Soil + EC
PM10, PM2.5 and PMC - Southeast
IMPROVE/NESCAUM Data
40,000
O
1
35,000
30,000
25,000
20,000
O
O
15,000
10,000
5,000
(b)
1989 Mar May Jul Sep Nov
-+- PM2.5 -A- PM Coarse
Chemical Tracers - Southeast
IMPROVE/NESCAUM Data
4,000
3,500
3.000
01 2.500
I
~ 2,000
8
o
o
1.500
1,000
500
(d)
1989 Mar May Jul
-A- Sulfur - Max = 4000
-+- Vanadium - Max =10
Sep Nov
-B- Selenium - Max = i
-e- s/Se - Max = 4000
Figure 6-33. IMPROVE/NESCAUM concentration data for the Southeast: (a) monitoring
locations; (b) PM10, PM2 5, and PMCoarse (PMC); (c) sulfate, soil, organic
carbon (OC), and elemental carbon (EC) fractions; and (d) tracers.
6-75
-------
nonurban PM10 concentration in the Southeast (Figure 6-33b) is roughly comparable to the
Northeast, exhibiting about factor of two seasonal concentration amplitude between 12 ,ug/m3
in the winter, and 25 /ug/m3 in the summer. An anomalous high PM10 concentration is shown
in July which appears to be contributed by an excess coarse particle concentration of about
10 /ug/rn3. With exception of July, the fine particle mass accounts for about 70% of the
nonurban PM10, leaving the coarse mass of 30% or less throughout the year (Figure 6-33b).
The most prominent aerosol species in the Southeast are sulfates contributing 40 to 50%
of the fine mass (Figures 6-33c). The anomalously low sulfate fraction (35%) during July
coincides with the high (20%) soil contribution during July. For the other months, soil
contribution is < 5% of the fine mass. The relative role of the organic carbon in the nonurban
Southeast is most pronounced during the winter (40%), but declines to 25% during the
summer months. The contribution of elemental carbon varies between 2% in the summer to
6% in the winter months.
The trace element concentrations of selenium and vanadium (Figure 6-33d) are constant
throughout the year, implying that the combined role of emissions and dilution is seasonally
invariant. The concentration of sulfur, on other hand shows a definite summer peak, that is
two to three times higher than the winter concentrations. Consequently, the S/Se ratio is
strongly seasonal. In fact, the warm season S/Se ratio of 2,500 is higher than over any other
region of the country. If Se-bearing coal combustion is the dominant source of sulfur in the
Southeast, then the high S/Se ratio implies that the secondary photochemical sulfate production
in the summer is several times that in the winter.
6.4.2.2 Urban Aerosols in the Southeast
In the southeastern U.S. there was a decrease in the annual average PM10 concentrations
between 1988 and 1994 from 33 /ug/m3 to 27 //g/m3 for all sites and from 35 /zg/m3 to
29 //g/m3 for trend sites (Figure 6-34b). The reductions were 18% for all sites and 17% for
trend sites. The Southeast PM10 concentration trends and the PM10 seasonality resemble the
industrial Midwest described below. A unique feature of the Southeast is the uniformity of the
aerosol concentration among the monitoring stations. In fact the 17% station to station
6-76
-------
PM10 Average - Southeast
150
140
130
120
110
100
«*"• eo
3 80
U)
« 70
O.
60
50
40
30
20
10
0
PM10 Cone. Trend - Southeastern U.S.
EPA AIRS database
80
PM2.5 vs. PM10 - Southeast
EPA AIRS - Monthly Averages
1989 1990 1991 1992 1993 1994
-A- Avg for all sites -B-Avg for trend sites
-t-Avg + Std. Dev. -*-Avg - Std. Dev.
Seasonal PM Pattern - Southeast
EPA AIRS Database
CORRELATION STATS:
AvgX: 29.19
AvgY- 18.32
Avg Y/Avg X : 0.55
CorrCoeff: 0.63
Slopa : 0.43
Y offtet: 3.61
D»ti Polnte : 352
50
45
(d)
20 40 60 80 100 120 140
PM10(jjg/m3)
1986 Mar May Jul Sep Nov
-A-PM10 -B-RM2.5 -t-PM Coarse
Figure 6-34. AIRS concentration data for the Southeast: (a) monitoring locations;
(b) regional PM10 concentration trends; (c) PM10 and PM2>5 relationship;
and (d) PM10, PM2.s» antl PMCoarse seasonal pattern.
6-11
-------
standard deviation is by far the lowest among the aerosol regions (Figure 6-34b). This result
would appear to be associated with regional meteorological patterns.
The Southeast is also characterized by high seasonal amplitude of 37%, ranging between
22 //g/m3 in December through February and 35 //g/m3 in July through August
(Figure 6-34d). There is no evidence of a winter peak for the southeastern U.S.
The scattergram of PM2 5-PM10 for the Southeast (Figure 6-34c) shows an average of
58% fine particle contribution, with considerable scatter. It should be noted, however, that
size segregated samples were available only briefly and these only for two monitoring sites
which may not be representative for the large southeastern region.
The regionally averaged daily PM10 concentrations over the Southeast (Figure 6-35)
shows a clearly discernible seasonally. The concentrations during the winter months are
about factor of two lower than during the summer. Overall, the lowest concentrations are
about 12 //g/m3, and the highest about 50 //g/m3, which is about factor of four. However,
seasonality of the temporal signal accounts for about half of the variation. Hence, within a
given season the sixth day to sixth day variation is only about 50%. It can be concluded that
the PM10 concentration over the southeastern United States region is quite uniform during
shorter tune intervals, although it exhibits a substantial seasonality. The southeastern United
States also exhibits the highest spatial homogeneity (i.e., the smallest average deviations of
average concentrations between the stations). The PM10 urban excess (AIRS-IMPROVE) for
the southeast region is given in Figure 6-36. The range of monthly urban excess
concentrations in the Southeast is within approximately the same range, 5 Mg/m3 to 10 //g/m3,
as for the Northeast. The one distinct feature is the sharp decrease in the urban excess in July
which corresponds to the sharp peak attributed to the nonurban coarse soil contribution in July
for the Southeast (Figure 6-33).
6.4.3 Regional Aerosol Pattern in the Industrial Midwest
This aerosol region stretches between Illinois and western Pennsylvania, including
Kentucky on the south (Figure 6-37a). The industrial Midwest is covered by flat terrain west
of the Appalachian Mountains. In the winter the region is under the influence of cold
Canadian air masses, while during the summer moist air masses transported from the Gulf
6-78
-------
Southeast Every Sixth Day
eo
O)
O~
1991
1992
1993
Figure 6-35. Short-term variation of PM10 average for the Southeast. Data are reported
every sixth day.
Southeast urban excess
4O
Jan Mar May Jul Sep Nov
Figure 6-36. Urban excess concentration (AIRS minus IMPROVE) for the Southeast.
6-79
-------
PM2.5 Concentration - Industrial Midwest
IMPROVE/NESCAUM Data
PM10, PM2.5 and PMC - Industrial Midwest
IMPROVE/NESCAUM Data
40,000
35,000
30,000
£ 20,000
O
O
15,000
10,000
5,000
(b)
1989 Mar May
-B-PM10 -
Jul Sep Nov
PM2.5 -A- PM Coarse
Chemical Fine Mass Balance - Industrial Midwest
IMPROVE/NESCAUM Data
i
I
0.4
0.1
(C)
0.0
1989 Mar
-A-Sulfate
-9-EC
Chemical Tracers - Industrial Midwest
IMPROVE/NESCAUM Data
4,0001 ' 1 . 1 1 1 1 . i-
3,500
3,000
«">
i
» 2,500
I
o
O
2,000
1,500
1,000
(d)
May Jul Sep Nov
-B-oc -HSoil
-e-Sulfate + OC + Soil + EC
1989 Mar May Jul
-A- Sulfur - Max = 4000
-+- Vanadium - Max =10
Sep Nov
-B- Selenium - Max = 4
-e- S/Se - Max = 4000
Figure 6-37. IMPROVE/NESCAUM concentration data for the industrial Midwest:
(a) monitoring locations; (b) PM10, PM2 5, and PMCoarse (PMC);
(c) sulfate, soil, organic carbon (OC), and elemental carbon (EC) fractions;
and (d) tracers.
6-80
-------
Coast prevail. However, the northern most portion of this region in Michigan and Wisconsin is
cooler and may be influenced by Canadian air flow at times during the summer. This region
includes the Ohio and Mississippi River Valleys that are known for high sulfur emission
densities. The region also includes major metropolitan areas.
6.4.3.1 Nonurban Size and Chemical Composition in the Industrial Midwest
The seasonal pattern of the nonurban aerosol in the Industrial Midwest is shown in
Figure 6-37b. Only five nonurban monitoring sites are available widely separately
geographically between those at the northern most sites and those in the southern portion of
the region with no sites over most of the region. Their representativeness is questionable.
The PM10 concentrations range between 10 and 22 /ug/m3, comparable to the nonurban levels
in other eastern U.S. regions. From 70 to 80% of PM10 is contributed by fine particles
throughout the year. The coarse particle concentrations are 4 to 5 //g/m3, which is lower than
over any other region of the U.S. Hence, the contribution of wind blown dust, fly ash, or
other man-induced dust entrainment is not a significant factor in the nonurban areas of the
Industrial Midwest.
The chemical mass balance (Figure 6-37c) shows that sulfates are 45 to 55% of the fine
mass which is higher than the sulfate fractions in other regions. The concentration of
vanadium, which is a tracer for oil combustion, is low throughout the year. The concentration
of fine particle sulfur Organics exhibit a variable contribution that is high (40%) during the
cold season (October through February) and quite low (20%) in July and August. The strong
winter peak for the organic fraction differs markedly from the Northeast where the organics
are seasonal. Another unusual feature of the chemical mass balance is that the sum of sulfate,
organic carbon, soil, and elemental carbon is about 75% during the summer and 95% in the
winter. It is not known what is the composition of the missing 25% during the summer tune,
but the missing fraction could be associated with nitrates, ammonium ion, hydrogen ion, and
water.
Chemical tracer data are shown in Figure 6-37d. The chemical tracer for coal
combustion, selenium ranges between 1,000 and 1,500 pg/m3, which is higher than in any
other region. There is a sizeable month to month variation in Se concentration (partly due to a
6-81
-------
small number of data points) and the seasonality is not appreciable. This means that the
combined effects of coal combustion source strength and meteorological dilution are seasonally
invariant over the industrial Midwest, exhibits random monthly variation but indicates a
summer peak. The S/Se ratio is a rather smooth seasonal curve ranging between 1,000 in the
winter and 2,000 during the summer months. Hence, the sulfate yield is about twice as high
during the summer as during winter months. For comparison both the Northeast and
Southeast exhibit somewhat higher seasonality (factor of 2.5) in S/Se ratio. A possible
explanation for this change in S/Se ratio is that over the industrial Midwest the average age of
the SO2 emissions traveling downwind may be less than over the Northeast or Southeast.
6.4.3.2 Urban Aerosols in the Industrial Midwest
In the industrial midwester U.S. there was a decrease in the annual average PM10
concentrations between 1988 and 1994 from 33 fj.g/m3 to 29 ^g/m3 for all sites and from
37 ,ug/m3 to 30 ^g/m3 for trend sites (Figure 6-38b). The reductions were 12% for all sites
and 19% for trend sites. There is also a 28% deviation among the stations within the region.
As in the Northeast, the higher concentrations occur within the larger urban-industrial areas
(Figure 6-38a). The PM10 seasonality (Figure 6-38d) is virtually identical (37% amplitude) to
the seasonality of the Southeast: the lowest concentrations (25 /^g/m3) occur between
November and February, while the highest values are recorded in June through August
(40 /ug/m3). The trends and the seasonality of the midwestern PM10 aerosols are comparable
to those of the Southeast.
Fine particles contribute 60% of the PM10 concentration on the average (Figure 6-38c),
and high PM10 can occur when either fine or coarse particles dominate.
Daily concentration over the industrial Midwest (Figure 6-39) varies between 14 and
75 //g/m3. The lowest regional concentrations occur during the winter months, while the
highest values (in excess of 40 /ug/m3) occur during the summer. It is evident that seasonality
is an important component of the time series, accounting for about half of the variance. The
elevated concentrations occur only one sixth day observation at a time, consistent with the low
frequency of prolonged episodes. The industrial Midwest also shows substantial spatial
variability. The urban excess PM10 (AIRS-IMPROVE) for the industrial midwest is given in
6-82
-------
PM10 Average - Industrial Midwest
PM10 Cone. Trend - Industrial Midwest
EPA AIRS database
PM2.5 vs. PM10 - Industrial Midwest
EPA AIRS - Monthly Averages
1989 1990 1991 1992 1993 1994
-A- Avg for all sites -B- Avg for trend sites
-l-Avg + Std. Dev. -»-Avg - Std. Dev.
Seasonal PM Pattern - Industrial Midwest
EPA AIRS Database
130
120
110
100
CO
E
«. 80
CM
5
0. 70
CORRELATION STATS:
. Avg X 29.02
AvgY- 17.62
Avg Y/Avg X : 0.6
Corr Coeff 0.66
• Slope • 0.53
Y offtet. 2 08
Dita Points : 465
(c)
55
45
0.
(d)
0 20 40 60 BO 100 120 140
PM10
1986 Mar May Jul
-A-PM10 -B-PM2.5 '
Sep Nov
-PM Coarse
Figure 6-38. AIRS concentration data for the industrial Midwest: (a) monitoring
locations; (b) regional PM10 concentration trends; (c) PM10 and PM2.5
relationship; and (d) PM10, PM2.5, and PMCoarse seasonal pattern.
6-83
-------
Industrial Midwest Every Sixth Day
o
i
Q_
1991
1992
1993
Figure 6-39. Short-term variation of PM10 average for the industrial Midwest. Data are
reported every sixth day.
Figure 6-40. The pattern for the urban excess PM10 differs seasonally from that in the
northwest (3-32) or southeast (6-34).
6.4.4 Regional Aerosol Pattern in the Upper Midwest
The upper Midwest covers the agricultural heartland of the country (Figure 6-41). The
region is void of any terrain features that would influence the regional ventilation. Industrial
emissions and the population density are comparatively low. However, the relatively high
PM10 concentrations in this region warrant a more detailed examination. In the winter, the
region is covered by cold Canadian air masses, while in the summer moist Gulf air alternates
and drier Pacific air masses occur.
6.4.4.1 Nonurban Size and Chemical Composition in the Upper Midwest
There is a lack of nonurban monitoring sites in the upper midwest (Figure 6-4la).
Compared to the urban sites (Figure 6-42a), these nonurban sites are poorly representative of
6-84
-------
Industrial Midwest urban excess
o
Nov
Jan Mar May Jul Sep
Figure 6-40. Urban excess concentration (AIRS minus IMPROVE) for the industrial
Midwest.
the region. Based on these few sites in the upper Midwest, the PM10 concentration is about
8 /ug/m3 during the November through April winter season, and increases to 15 Mg/rn3 during
the summer. Fine and coarse particles have a comparable contribution to the PM10 mass
(Figure 6-4 Ib).
The chemical mass balance (Figure 6-41c) indicates that during the March through May
spring season sulfates dominate, but during July through October season organics prevail.
This is a rather unusual pattern not observed over any other region. The contribution of fine
particle soil exceeds 10% in the spring as well as in the fall season.
Chemical tracers are shown in Figure 6-41d. Selenium concentration is low throughout
the year (400 to 600 pg/m3), with the highest concentrations observed during the summer.
This suggests that either the Se sources from coal-fired power plants or the Se transport into
the Upper Midwest from other regions is stronger in the summer. The concentration of the
fine particle sulfur is < 500 ng/m3 throughout the year, but somewhat higher during March
and April. The spring peak of fine particle sulfur has not been observed in any other region.
It is also worth noting that S/Se ratio is the highest during the spring and lowest in July
6-85
-------
PM2.5 Concentration - Upper Midwest
IMPROVE/NESCAUM Data
PM10, PM2.5 and PMC - Upper Midwest
IMPROVE/NESCAUM Data
40.000
35,000
30,000
25,000
5
o
O
20,000
15,000
10,000
6,000
(b)
1989 Mar May Jul Sep Nov
-0-PM10 -t-PM2.5 -&-PM Coarse
Chemical Fine Mass Balance - Upper Midwest
IMPROVE/NESCAUM Data
|
£ 0.4
(C)
1989 Mar
-A-Sulfate
Chemical Tracers - Upper Midwest
IMPROVE/NESCAUM Data
4,000
3,500
3.000
•& 2.500
i
S 2,000
o
O
1.500
1,000
(d)
May Jul Sep Nov
-B-OC H-Soil
-e-Sulfate + OC + Soil + EC
1989 Mar May Jul
-A- Sulfur- Max = 4000
-I- Vanadium - Max =10
Sep Nov
-B- Selenium - Max = 4
-e- S/Se - Max = 4000
Figure 6-41. IMPROVE/NESCAUM concentration data for the upper Midwest:
(a) monitoring locations; (b) PM10, PM2 5, and PMCoarse (PMC);
(c) sulfate, soil, organic carbon (OC), and elemental carbon (EC) fractions;
and (d) tracers.
6-86
-------
PM10 Average - Upper Midwest
PM10 Cone. Trend - Upper Midwest
EPA AIRS database
1989 1990 1991 1992 1993 1994
-A-Avg for all sites -B-Avg for trend sites
-l-Avg + Std. Dev. -©-Avg - Std. Dev.
PM2.5 vs. PM10 - Upper Midwest
EPA AIRS - Monthly Averages
"
150
140
130
120
110
100
90
— 60
in
40
30
20
10
(C)
CORRELATION STATS
AvgX: 31.41
AvflY. 12.16
Avg Y/Avg X : 0.38
CorrCoeff: 0.54
Slope: 0.18
Y oH»t . 6.46
O>t« PoinU : 34
20 40 60 80 100 120 140
PM10 (\iglm3)
Seasonal PM Pattern - Upper Midwest
EPA AIRS Database
(d)
1986 Mar May Jul
-A-PM10 -B-PM2.5
Sep Nov
PM Coarse
Figure 6-42. Aerometric Information Retrieval System (AIRS) concentration data for the
upper Midwest: monitoring locations; regional PM10 monitoring trends;
PM10 and PM2>5 relationship; and PM10, PM2-5, and PMCoarse seasonal
trends.
6-87
-------
through September. It needs to be pointed out again that the above chemical patterns are based
on only two monitoring stations.
6.4.4.2 Urban Aerosols in the Upper Midwest
The agricultural upper Midwest (Figure 6-42b) shows the smallest decline in PM10
concentrations among the regions. In the upper midwestern U.S. there was a decrease hi the
annual average PM10 concentration between 1988 and 1994 from 30 ptg/m3 to 25 jtg/m3 for all
sites and from 32 //g/m3 to 26 /ug/m3 for trend sites (Figure 6-42b). The reductions were 17%
for all sites and 19% for trend sites. As over the eastern U.S., the highest concentrations
occur in the vicinity of urban areas. Some of the station-to-station concentration spread arises
from low concentrations over western North Dakota. On the average, the deviation among the
stations over the region is a moderate 30% (Figure 6-39). The upper Midwest is also unique
in that it shows the regionally lowest seasonal amplitude of 19%, with the slightly lower
concentrations occurring in December and January. The sparse size segregated data indicate
that only 38% of PM10 is contributed by fine particles. This is an indication that coarse wind
blown dust from natural or man-induced sources prevails. In this sense, the region is similar
to the Southwest (see below).
The daily regionally averaged PMi0 concentrations in the upper Midwest (Figure 6-43)
range between 14 and 45 /^g/m3. The highest values (>40 /ug/m3) generally occur in the
summer season, while the low regional concentrations occur mainly in the cold season, but
low values also occur in the summer. It is interesting that the lowest PM10 concentrations
over the upper Midwest (15 /ug/m3) are comparable to the Southeast and the industrial
Midwest, but differ from these regions by the absence of immediately subsequent high
concentration events or episodes. In fact, the PM10 "episodes" over the upper Midwest are all
in the 40 to 45 /zg/m3 concentration range, compared to 50 to 75 //g/m3 in the Midwest. The
seasonality is barely discernible from the tune series confirming that the day to day variation
exceeds the seasonal modulation. The urban excess PM10 (AIRS-IMPROVE) for the upper
midwest is given in Figure 6-44, but its reliability may be in question because of the very
small number of nonurban sites.
-------
Upper Midwest Every Sixth Day
CO
5
CL
1991 1992 1993
Figure 6-43. Short-term variation of PM10 average for the Upper Midwest. Data are
reported every sixth day.
Jan
Upper Midwest urban excess
Mar
Nov
May Jul Sep
Figure 6-44. Urban excess concentration (AIRS minus IMPROVE) for the Upper
Midwest.
6-89
-------
6.4.5 Regional Aerosol Pattern in the Southwest
The Southwest covers the arid states from western Texas to Arizona (Figure 6-45a). The
Southwest is characterized by mountainous terrain features between the southern Rockies and the
Colorado Plateau. The industrial activity and agriculture is minor compared to other regions.
Major population centers include El Paso, Phoenix, and Tucson. The meteorology of the region
is characterized by low annual precipitation, except during the periods when moist air penetrates
from the Gulf of Mexico toward these states, bringing moisture and precipitation.
6.4.5.1 Nonurban Size and Chemical Composition in the Southwest
The PM10 concentrations at nonurban southwestern sites show a double peak, one during
the late spring (April through July), and another in October. This bimodal seasonality is
imposed by the coarse particle mode. The PM2 5 mass concentration is unimodal with a
summer maximum. Overall, the nonurban PM10 concentrations are comparatively low (8 to
15 /ug/m3) and over 60% contributed by coarse particles (Figure 6-45b).
The chemical mass balance (Figure 6-45c) shows sulfates to be the larger contributor
during the winter (December through March) as well as in late summer (July through
October). However, sulfate and organic carbon contributions are comparable during March
through June as well as during November through December. Fine particle soil plays a
prominent role in the spring fine particle chemical mass balance reaching 25 %, but the
contribution of soil decreases during the summer, and during December through February
dwindles to below 10%.
The selenium and vanadium concentrations (Figure 6-45d) are very low and rather
invariant throughout the year. The fine particle sulfur concentration is low and exhibiting a
weak maximum during August. The S/Se ratio is comparatively low and bimodal, with peaks
in April through May as well as August through October.
6.4.5.2 Urban Aerosols in the Southwest
In the southwestern U.S. there was a decrease in PM10 concentrations between 1988 and
1994 from 38 ^g/m3 to 24 Aig/m3 for all sites and from 43 ^g/m3 to 29 /ug/m3 for trend sites
(Figure 6-46b). The reductions were 37% for all sites and 33% for trend sites. The
6-90
-------
PM2.5 Concentration - Southwest
IMPROVE/NESCAUM Data
PM10, PM2.5 and PMC - Southwest
IMPROVE/NESCAUM Data
40.0001 1 , 1 , 1 . , 1 , , r-
35,000
30,000
25,000
20,000
5 15.000
10,000
5,000
(b)
Jan Mar May Jut
-EHPM10 -HPM2.5
Sep Nov
Coarse
Chemical Fine Mass Balance - Southwest
IMPROVE/NESCAUM Data
0.7
H 0.8
B
c
~ 0.6
•5
I
(C)
0.0
Jan Mar
-fi-Sulfate
-e-soot
May Jul Sep Nov
-B-Organics -t-Soil
Org + Soil + Soot
4,000
3,600
3,000
2,500
Chemical Tracers - Southwest
IMPROVE/NESCAUM Data
B 2.000
O
O
1,000
(d)
Jan Mar May Jul Sep Nov
-A-Sulfur-Max = 4000 -B-Selenium - Max = 4
-+- Vanadium -Max = 10 -©- S/Se - Max = 4000
Figure 6-45. IMPROVE/NESCAUM concentration data for the Southwest:
(a) monitoring locations; (b) PM10, PM2.5, and PMCoarse (PMC);
(c) sulfate, soil, organic carbon (OC), and elemental carbon (EC) fractions;
and (d) tracers.
6-91
-------
PM10 Average - Southwest
PM10 Cone. Trend - Southwest
EPA AIRS database
150
140
130
120
110
^ 100
I >°
10 BO
2
Q. 70
60
50
40
30
20
10
PM2.5 vs. PM10 - Southwest
EPA AIRS - Monthly Averages
1989 1990 1991 1992 1993 1994
-A-Avg for all sites -B-Avg for trend sites
-l-Avg + Std. Dev. -e-Avg - Std. Dev
Seasonal PM Pattern - Southwest
EPA AIRS Database
CORRELATION STATS .
AvgX. 3758
AvgY: 1328
AV9 Y/Avg X : 0.35
Corr Coeff:
Slope :
Y offtet :
Data Polntt. 107
45
"E 3S
- 30
s
a.
is
20
15
10
(d)
20 40 60 80 100 120 140
PM10(M9/m3)
1986 Mar May Jul
-A-PM10 -B-PM2.5 -
Sep Nov
• PM Coarse
Figure 6-46. AIRS concentration data for the Southwest: (a) monitoring locations;
(b) regional PM10 monitoring trends; (c) PM 10 and PM2.5 relationship; and
(d) PM10, PM2.5, and PMCoarse seasonal trends.
6-92
-------
downward trends in PM10 concentrations were not monotonic. In the Southwest is the large
concentration spread of 45% among the monitoring sites (Figure 6-46b). Sites with low
concentrations (<20 Atg/m3) occur adjacent to high concentration sites (>50 ^tg/m3).
Seasonally, the Southwest PM10 concentration shows two peaks, one in late spring April
through June, and another during the fall October through November. The concentration dip
in August and September has not been observed for any other region. The late summer
concentration drop coincides with the occurrence of the moist air flows from the Gulf of Mexico.
The size segregated aerosol samples from the Southwest clearly show that coarse
particles make the major contribution to the PM10 concentration, the fine particles contributing
only 37% (Figure 6-46a). The scatter in Figure 6-46c indicates that high PM10 concentration
months can occur with low concentrations of fine particles. In the Southwest natural and man-
induced coarse particle dust is a major contributor to PM10 aerosols (Figure 6-45c).
The short term PM10 concentration over the Southwest (Figure 6-47) exhibits a highly
irregular pattern, that ranges between 11 to 52 f^g/w? regional average. Both the lowest (10 to
15 /ug/m3) as well as the highest values are dispersed throughout the year.
o
s
Q_
Southwest Every Sixth Day
1991
1992
1993
Figure 6-47. Short-term variation of PM10 average for the Southwest. Data are reported
every sixth day.
6-93
-------
The urban excess PM10 (AIRS-IMPROVE) for the Southwest is given in Figure 6-48,
and the urban excess is substantially larger than in the regions discussed previously.
Southwest urban excess
Jan Mar May Jul Sep Nov
Figure 6-48. Urban excess concentration (AIRS minus IMPROVE) for the Southwest.
6.4.6 Regional Aerosol Pattern in the Northwest
The Northwest is defined to cover the bulk of the western United States north of the
Arizona border (Figure 6-49a). It is covered by mountainous terrain of the Rockies, as well as
the Sierra-Cascade mountain ranges. The Northwest is actually a collection of many aerosol
subregions. The meteorology is highly variable between the Pacific Northwest and the Rocky
Mountains with prevailing winds generally from the west. The main feature of the Northwest
is pronounced elevation ranges between mountain tops and valleys, and the resulting
consequences on emission pattern (confined to the valleys) and limited ventilation. The
Northwest has also industrial population centers, such as Seattle, Portland, Salt Lake City and
Denver.
6-94
-------
PM2.5 Concentration - Northwest
IMPROVE/NESCAUM Data
Chemical Fine Mass Balance - Northwest
IMPROVE/NESCAUM Data
0.8
0.7
-------
6.4.6.1 Nonurban Size and Chemical Composition in the Northwest
The nonurban PM10 concentrations show low values ranging between 7 to 14 //g/m3 in
the northwestern U.S. The seasonality shows a peak in the summer which is contributed by
both fine and coarse particles. Coarse particles account for more than half of the PM10,
particularly during March through June spring season (Figure 6-49b).
The chemical mass balance (Figure 6-49c) shows roughly comparable contributions from
sulfates and organics, but their seasonality is phase shifted. Sulfates prevail during the spring
season while organics dominate during late fall (October through January). Fine particle soil
dust contributes 20% during April and May, but decline well below 10% during the winter
months (November through February). Overall, about 80% of the fine mass is accounted for
by the sulfates, organic carbon, soil, and elemental carbon.
Examining the carbonaceous particles and regional haze in the western and northwestern
U.S., White and Macias (1989) concluded that in the rural areas the concentrations of
particulate carbon are comparable to those of sulfate. Examining paniculate nitrate, White and
Macias (1987) showed that the particulate nitrate concentration in the northern states (MT,
ID, WY) were substantially higher than sulfate concentrations. Aerosol particulate nitrates
over rural mountainous West were also episodic (i.e., few samples contributed a large
fraction of the fine particle integrated dosage).
Both selenium and vanadium concentrations (Figure 6-49d) are low in the Northwest, but
there is an indication of a summer peak of Se. The S/Se ratio is between 500 to 1,000, which
is the lowest among the regions. This ratio has both spring peak as well as fall peak, similar
to the pattern observed for the southwestern United States.
6.4.6.2 Urban Aerosols in the Northwest
In the northwestern U.S. there was a decrease in the annual average PM10 concentration
between 1988 and 1994 from 33 ^g/m3 to 24 yug/m3 for all sites and from 35 Aig/m3 to
27 /^g/m3 for trend sites (Figure 6-50b). The reductions were 27% for all sites and 23% for
trend sites. However, the 1985 to 1994 reductions may be overestimates because of the low
station density in the early years. Once again, the average 1993 concentration is 25 //g/m3
which is comparable to the 1993 concentrations of the eastern U.S. regions. The spread of
6-96
-------
PM10 Average - Northwest
PM10 Cone. Trend - Northwest
EPA AIRS database
140
130
120
110
100
— 90
M
ra ao
S ^o
* 60
50
40
30
20
10
PM2.5 vs. PM10 - Northwest
EPA AIRS - Monthly Averages
1989 1990 1991 1992 1993 1994
!r- Avg for all sites -B- Avg for trend sites
4- Avg + Std. Dev. -G- Avg - Std. Dev.
Seasonal PM Pattern - Northwest
EPA AIRS Database
CORRELATION STATS
Ava X : 29.85
AvgY: 17.29
Avg Y/Avg X 0.57
CorrCoaff- 0.9
Slop* . 0.72
YoH»t. -4.42
Data Polnta • 347
(c)
60
55
SO
45
1
s
Q_
(d)
20 40 60 80 100 120 140
PM10
1986 Mar May Jul Sep Nov
•A- PM10 -B- PM2.5 -I- PM Coarse
Figure 6-50. AIRS concentration data for the Northwest: (a) monitoring locations;
(b) regional PM10 monitoring; (c) PM10 and PM2 5 relationship; and
(d) PM10, PM2>5, and PMCoarse seasonal trend.
6-97
-------
concentration among the Northwest stations is large, with standard deviation of
45% (Figure 6-50b). This spread in the concentration values is also evident from the various
circle sizes of the Northwest map (Figure 6-50a). The highest PMjQ concentrations in the
Northwest occur in more remote mountainous valleys, rather than in the center of
urban-industrial areas.
The seasonally of the northwestern United States has an amplitude of 36% which is
comparable to the strong seasonality of the eastern U.S. The peak PM10 concentrations occur
in the winter. The lowest PM10 concentration occurs during March through May and
gradually increases to a peak in December through January, falling sharply between January
and March.
The limited PM2 5-PM10 data for the Northwest indicate that on the average 57% of
PM10 particles are PM2 5. Figure 6-50c also indicates that the extreme PM10 concentrations
are contributed mainly by fine particles. Furthermore, the extreme PM10 concentrations also
occur in the winter season.
The daily concentration when averaged over the large and heterogeneous northwestern
region exhibits a remarkably small sixth day to sixth day variation (Figure 6-51).
Furthermore, there is clear seasonality with a strong whiter peak. Within a given season, the
regionally averaged concentrations only vary by 20 to 40% from one sixth day to another.
Examination of the logarithmic standard deviation (Figure 6-50b) shows that the Northwest is
spatially the most heterogeneous and has the highest logarithmic standard deviation among all
regions. Evidently, in the Northwest high concentration PM10 pockets in topographically
confined airsheds result in strong spatial and temporal variations. However, large scale
elevated PM10 concentrations that cover the entire Northwestern region do not exist because
high concentrations are not "synchronized" among the different airsheds. In this sense, the
Northwest differs markedly from the eastern U.S., where large regional scale air masses with
elevated PM10 determine the regionally averaged values. The urban excess PM10 (AIRS-
IMPROVE) for the Northwest is given in Figure 6-52. The winter urban excesses are almost
as large as in the Southwest (Figure 6-48). However, if the region is a collection of aerosol
subregions, the small number of nonurban sites may not be representative of this collection of
subregions.
6-98
-------
Northwest Every Sixth Day
^>
1991 1992 1993
Figure 6-51. Short-term variation of PM10 average for the Northwest. Data are reported
every sixth day.
Northwest urban excess
Jan Mar May Jul Sep Nov
Figure 6-52. Urban excess concentration (AIRS minus IMPROVE) for the Northwest.
6-99
-------
6.4.7 Regional Aerosol Pattern in Southern California
The region covers California south of San Francisco Bay (Figure 6-53a). It was
considered as a separate region primarily because of the known high aerosol concentrations in
the Los Angeles and San Joaquin basins. Meteorologically the region is exposed to the air
flows from the Pacific that provide the main regional ventilation toward the south and
southeast. The precipitation in the region occurs in the winter season, with the summer being
hot and dry. The regional ventilation of the San Joaquin Valley is severely restricted by the
Sierra Nevada Mountain range. Also, the San Gabriel Mountains constitute an air flow
barrier east of the Los Angeles basin. Both basins have high population, as well as industrial
and agricultural activities. Hence, human activities are believed to be the main aerosol sources
of the region.
6.4.7.1 Nonurban Size and Chemical Composition in Southern California
The PM10 concentration at the few nonurban sites over southern California ranges
between 10 ,ug/m3 during December through February, and 20 to 25 /ig/m3 in April through
October. Coarse particles contribute more than 50% of the PM10 during the warm season
May through October. Both the fine and coarse aerosol fractions are lowest during the winter
months (December through March). The summer peak fine particle seasonally at nonurban
southern California sites is in marked contrast to the strongly fall peaked urban fine particle
concentrations (Figures 6-53b, 6-54d).
The chemical mass balance (Figure 6-53c) of nonurban southern California aerosol has a
substantial contribution by organics of 30 to 40% throughout the year. Sulfates account for
only 10 to 15% of the fine mass in the winter, and about 20% in the summer months. The
sulfate fraction of the nonurban southern California fine mass is the lowest among the regions.
Fine particle soil dust is about 10% between April through November and drops to 5% during
the winter months. A notable feature of the southern California chemical mass balance is that
45% of the winter, and 35% of the summer fine mass concentration is not accounted by
sulfates, soils, organic carbon,and elemental carbon. Nitrates are a major contributor to the
southern California aerosols (Solomon et al., 1989).
6-100
-------
PM2.5 Concentration - S. California
IMPROVE/NESCAUM Data
PM10, PM2.5 and PMC - S. California
IMPROVE/NESCAUM Data
Chemical Fine Mass Balance - S. California
IMPROVE/NESCAUM Data
(C)
1989 Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
-A-Eulfate -Q-Organic« -4— Soil
-©-Soot
-e-Sulf + Org + Soil* Soot
35,000
30,000
25,000
20,000
15,000
10,000
5,000
(b)
1989 Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
-B-PM10 -I-PM2 5 -A-PM Coaraa
Chemical Tracers - S. California
IMPROVE/NESCAUM Data
4,000
3,500
3,000
2,500
2,000
1,500
1,000
(d)
1989 Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
-A-Sulfur- Max- 4000 -B-Selenium - Max - 4
-(-Vanadium - Max- 10 -©-S/Se - Max - 4000
Figure 6-53. IMPROVE/NESCAUM concentration for Southern California:
(a) monitoring locations; (b) PM10, PM2 5, and PMCoarse (PMC); (c) sulfate,
soil, organic carbon (OC), and elemental carbon (EC) fractions; and
(d) tracers.
6-101
-------
Both selenium and vanadium (Figure 6-53d) show low values throughout the year
without significant seasonally. On the other hand the fine particle sulfur concentration shows
a definite summer peak at 500 ng/m3, compared to 200 ng/m3 during the winter.
Consequently, the S/Se ratio increase from 500 in the winter 1,000 to 1,500 in the summer.
6.4.7.2 Urban Aerosols in Southern California
In the southern California region there was a decrease in the annual average PM10
concentration between 1988 and 1994 from 41 /ug/m3 to 30 Atg/m3 for all sites and from
42 //g/m3 to 32 ,ug/m3 for trend sites (Figure 6-54b). The reductions were 27% for all sites
and 241 % for trend sites. There is a sizable concentration spread among the stations (40%
standard deviation). Inspection of the circle sizes in the map points (Figure 6-54a) to
uniformly high concentrations in the San Joaquin Valley as well as in the Los Angeles basin.
The low concentration sites are located either on the Pacific coast outside of the Los Angeles
basin or in the Sierra Nevada Mountains. Thus there are clear patterns of basin-wide elevated
PM10 concentrations with lower values in more remote areas (Figure 6-54a).
The seasonality of the PM10 pattern in southern California is significant at 27%.
Furthermore, the seasonal pattern is unique that the highest concentrations occur in November
and the lowest in March. However, it is a see saw rather than a sinusoidal pattern.
On the average, about half of southern California PM10 is contributed by fine particles as
shown in the PM2 5-PM10 scattergram. Most of the high PM10 concentration months
dominated by fine particles tend to be in the fall.
The sixth day average time series for the southern California region (Figure 6-55) shows
remarkably high sixth daily variance, between 10 and 75 /ug/m3. The lowest values tend to
occur between January and April, while the highest concentrations (>50 /ug/m3) tend to occur
during October through December. Concentration excursions of a factor of two are common
between two consecutive six day time periods. However, visual inspection of the sixth daily
signal also reveals a substantial seasonality highest in the fall (September through December)
and lowest in the spring.
The urban excess PM10 (AIRS-IMPROVE) for Southern California is given in
Figure 6-56. The urban excesses are larger especially in winter, as are the urban excesses
6-102
-------
PM10 Average - Southern California
PM10 Cone. Trend - S. California
EPA AIRS database
150
140
130
120
110
100
c*^
£ 90
en
•2 BO
in
csi
5 70
Q.
60
SO
40
30
20
10
PM2.5 vs. PM10 - S. California
EPA AIRS - Monthly Averages
1989 1990 1991 1992 1993 1994
-A-Avg for all sites -B-Avg for trend sites
-l-Avg + Std. Dev. -e-Avg - Std. Dev.
Seasonal PM Pattern - S. California
EPA AIRS Database
CORRELATION STATS
AvgX 54.1
Avg Y : 26 76
Avg Y/Avg X : 0 49
CorrCoiff: 0.87
Slope : 0 66
Y ofl.et: -9
Data Pointa : 209
(c)
so
15
(d)
20
40 60 80
PM10
100 120 140
^986 Mar May Jul
-A-PM10 -B-PM2.5
Sep Nov
• PM Coarse
Figure 6-54. AIRS concentrations for Southern California: (a) monitoring locations;
(b) regional PM10 monitoring trends; (c) PM10 and PM2.S relationship; and
(d) PM10, PM2.5, and PMCoarse seasonal trend.
6-103
-------
CO
^)
o"
i
0-
Southern California Every Sixth Day
1991
1992
1993
Figure
6-55. Short-term variation of PM 10 average for Southern California. Data are
reported every sixth day.
Southern California urban excess
Jan Mar May Jul Sep Nov
Figure 6-56. Urban excess concentration (AIRS minus IMPROVE) for Southern
California.
6-104
-------
in the Northwest. Again, these results depend on measurements from a small number of
nonurban sites.
6.5 SUBREGIONAL AEROSOL PATTERNS AND TRENDS
The health and other effects of aerosols are imposed on individuals, and the density of
population varies greatly in space. Consequently, the evaluation of effects requires the
knowledge of aerosol concentrations over specific locations where sensitive receptors reside.
The purpose of this section is to characterize the aerosol pattern at specific sites, small airsheds
or subregions. The discussions is organized by region and then by monitoring site within a
region. Most urban aerosol sampling is confined to PM10 or in some instances to PM2 5 and
PMCoarse . However, detailed chemical composition data are reviewed for several urban areas.
6.5.1 Subregional Aerosol Pattern in the Northeast
In the northeastern region, the Shenandoah National Park and Washington, DC constitute
a useful urban-nonurban set of size and chemically resolved aerosol data. New York City and
Philadelphia are also major metropolitan areas with substantial aerosol data bases. Whiteface
Mountain site distinguishes itself from its background by high elevation.
6.5.1.1 Shenandoah National Park
The PM10 concentration at the Shenandoah National Park IMPROVE site (Figure 6-57'a)
exhibits a pronounced summer peak (27 /^g/rn3), which is a factor of three higher than the
winter value of 9 /ug/m3. The strong seasonality is driven by the seasonal modulation of the
fine mass which accounts for 70 to 80% of the PM10 mass (Figure 6-57a). The coarse particle
concentration ranges between 3 and 6 Mg/m3, which is small compared to the fine particle
mass, particularly in the summer season, when it accounts for < 25% of the PM10. It is clear
that at this nonurban site, in the vicinity of industrial source regions, fine particles determine
the magnitude of PM10.
The chemical mass balance for the Shenandoah IMPROVE monitoring site
(Figure 6-57b) clearly documents the dominance of sulfate aerosols, which contribute about
6-105
-------
90T-9
\w
I
ro
en
CO
CD
cs
o
B>
55
CD
Fraction of Fine Mass
Concentration
2
4-
CO
CO
CO
CO
to
5 e5 s
S: 7 •>»
e? ~*
5T " Q>
S *• *<
» §
CO CO
» §
X
II
o>
X
II
-------
60% of the fine mass during April through September and about 50% during the winter months.
Organic carbon, on the other hand, range from 20% in summer to 30% in the winter months.
The contribution of fine particle soil and elemental carbon is well below 5%. Throughout the
year about 90% of the fine mass is accounted for by these measured substances. At the
Shenandoah site, the sulfate aerosols constitute a higher percentage of the chemical mass
balance, and lower percentages of organic carbon and elemental carbon than for the averaged
nonurban Northeastern sites (Figure 6-29).
Chemical tracer data are shown in Figure 6-57c. The concentration of coal-tracer selenium
shows two maximum, one during December through March, and another in June through
September. Vanadium is relatively constant throughout the year. The fine particle sulfur
concentration is almost a factor of five higher in August (3,300 ng/m3) than in December
(700 ng/m3). This extreme sulfur seasonally is stronger at the Shenandoah site relative to the
averages for sulfur seasonality at all nonurban Northeastern sites (Figure 6-29). The S/Se ratio
has a remarkably smooth but highly seasonal variation that varies by about factor of four
between the winter (700) and summer (2,600) values. If Se-bearing coal combustion is the
exclusive source of sulfur at the Shenandoah National Park, then the sulfate production from the
SO2 associated with coal-fired sources is 3 to 4 times higher in the summer than in the winter.
An examination of the nature and sources of haze in the Shenandoah Valley/Blue Ridge
Mountains area (Ferman et al., 1981) showed that sulfate aerosols were the most important
visibility reducing species. Averaging 55% of the fine particle mass, sulfates (and associated
water) accounted for 78% of the total light extinction. The second most abundant fine particles,
accounting for 29% of the fine mass, was organic carbon. The remaining particle mass and
extinction were due to crustal materials.
Using an in-situ rapid response measurement of H2SO4/(NH4)2SO4 aerosol in Shenandoah
National Park, VA, Weiss et al. (1982) found that the summer sulfate and ammonium ions
average 58% of particle mass smaller than 1 mm. The particle composition in terms of
NH4+/SO42" molar ratio ranged from 0.5 to 2.0 with strong diurnal variation. The particles were
most acidic at 1500 EDT and least acidic in the period 0600 to 0900 EOT. The water contained
in ambient aerosol particles was more strongly associated with sulfate and ammonium ions than
with the remainder of the fine particle mass.
6-107
-------
6.5.1.2 Washington, District of Columbia
The PM10 concentration at Washington DC (at the top of the National Park Service
Headquarters building) is virtually constant over the seasons at 25 to 30 /ug/ni3. Fine particles
contribute over 70% of PM10 throughout the year (Figure 6-5 8a). The weak seasonally in the
fine particle mass is in sharp contrast to the factor of three seasonal fine mass modulation at the
Shenandoah National Park. The coarse particle concentration in Washington, DC is 8 to
10 Mg/m3 throughout the year, exhibiting virtually no seasonality.
PM2 5 at the urban Washington, DC site (figure 6-5 8b) is dominated by sulfates during the
summer months (over 50%), but declines to 30% in January. Organic carbon, on the other hand,
is 40% during October through January but only 30% during May through August. Thus, the
relative roles of organics and sulfates at the Washington, DC urban site is fully phase shifted by
half a year. Elemental carbon is a substantial contributes 9 to 12% during October through
December. Fine particle soil contributes a low 2 to 5% to PM2 5 at this urban site.
The chemical tracer species are shown in Figure 6-5 8c. The concentration of the coal tracer
selenium ranges between 1.5 to 2.0 pg/m3 without appreciable seasonality. The urban Se in
Washington, DC, is much higher than the Se at the northeastern nonurban sites. Vanadium, the
tracer for fuel oil, varies by factor of two between the high winter values (>8 pg/m3) and low
summer values (3 pg/m3). The pronounced V concentration seasonality is a clear indication of
that the emissions from fuel oil and other vanadium sources are seasonal. The fine particle sulfur
concentration varies by about factor of two between 1,400 ng/m3 winter concentration, and about
3,000 ng/m3 summer peak. The seasonal modulation of sulfur in Washington, DC is only factor
of two compared to the factor of four fine sulfur modulation at Shenandoah National Park. The
difference is primarily due to the elevated winter sulfur in Washington, DC. The S/Se ratio is
about 600 in the winter and about 1500 in the summer. It differs from Shenandoah by the lower
summer S/Se ratios. This result may be associated with differences in the air parcels involved in
long-range transport and transformation of SO2 to sulfate at Shenandoah compared to
Washington, DC.
6-108
-------
60T-9
4-
-o
ro
en
CO
tt>
c~>
O
o>
CD
Fraction of Fine Mass
CO CO
I
•t-
O
<3
o>
1'
f
s:
O
CO -H CO
O ' CD
2. co -o
CO
8
Concentration
5
o>
=
o>
x
n
o>
X
II
CO CO
£ i-
-------
6.5.1.3 Comparison of Nonurban (Shenandoah) to Urban (Washington, District of
Columbia) Aerosols
The Washington, DC, urban site and the companion nonurban Shenandoah monitoring site
constitute a rare data pair that allows the quantification of urban-rural differences in fine and
coarse particle concentration, and chemical composition. Within Washington, DC, industrial
emissions are moderate compared to the industrial midwestern cities. However, both
automobile emission density and emissions from winter time heating are expected to be high. In
this section the excess aerosol concentrations in Washington, DC, over the Shenandoah site are
examined to elucidate the urban influence.
The Washington, DC, excess PM10 concentration (Figure 6-59a) ranges between
15-20 Atg/m3 in the winter, and <3 //g/m3 in the summer. Hence, there is almost an order of
magnitude higher urban excess during the winter, compared to the summer. The seasonally of
the excess PM10 is driven by the winter peak excess fine particle concentration of 10-12 ,ag/m3.
The modest excess coarse particles is in the 3 to 6 £tg/m3 range throughout the year. Thus, the
urban Washington, DC concentration exceeds its nonurban regional aerosol values during the
winter season, and the excess winter time urban aerosol is largely contributed by fine particle
mass. This indicates the smaller role of coarse particle fly ash, road dust resuspended by
automobiles or construction, road salt and all other sources of urban coarse particles in
Washington, DC, in winter.
The chemical composition of the excess fine particle concentration over the Shenandoah
nonurban background is also shown in Figure 6-59b. Fine organic carbon dominates the urban
excess ranging between 1 /ug/m3 during the summer, and 5.5 Atg/m3 during the winter. The
seasonally of excess organic carbon also drives the seasonality of excess fine mass. There is an
excess sulfate concentration of 1 to 2 //g/m3 in Washington, DC, except during July, August, and
September. In fact, in August in Washington, DC, sulfate concentration is about 0.3 //g/m3
below the Shenandoah values. The urban excess elemental carbon concentration is 1 to 2 //g/m3
throughout the year. The soil contribution to the fine particle mass is identical to the values of
the Shenandoah National Park, yielding virtually no excess fine soil contribution in the urban
area.
6-110
-------
PM10, PM2.5, and PMC Monthly Average
Washington DC - Shenandoah NP Difference
Chemical Fine Mass Balance
Washington DC - Shenandoah NP Difference
1989 Mir May Jul
-H-RM10 -+PM2.5
Sep Nov
•*" PH Coarse
1989 Mar May Jul Sep Nov
-fr Sulfate -B- QC -+- Soil -«- EC
-*• Sulfate + OC + Soil + EC
Figure 6-59. Excess aerosol concentration at Washington, DC, compared to Shenandoah
National Park: (a) PM10, PM2 5, and PMCoarse (PMC); (b) concentration of
sulfate, soil, organic carbon (OC), and elemental carbon (EC).
The short-term fine mass concentration at Washington, DC and Shenandoah National Park
for the year 1992 is shown in Figure 6-60a. Although the sampling is conducted Wednesdays
and Saturdays for 24 h, the data points have been connected. The figure also compares the daily
(Wednesdays and Saturdays) fine particle sulfur concentrations at the two monitoring sites. The
fine mass concentration time series for Washington, DC, show elevated concentrations
(>30 Atg/m3) that can occur throughout the year. On the other hand, high fine mass levels at
Shenandoah are recorded only during the summer season. Particulate sulfur concentrations at the
urban and nonurban site are often comparable during the summer (Figure 6-60b). This indicates
that particulate sulfur often is a large part of the regional air mass that at any given day
influences Washington, DC, and the Shenandoah National Park. Fine particle mass, on the other
hand, shows an excess concentration at Washington, DC, particularly during the winter months.
The fine mass daily time series clearly indicates that the concentration change from one daily
sample to another can be an order of magnitude different. Consequently, most of the
concentration variance is due to random synoptic air mass changes, and to a lesser degree due to
periodic seasonal variations.
6-111
-------
O)
c
in
in
n
S
1992 Mar May Jul
•A" Washington D.C.
-a-Shenandoah National Park
Nov
1992 Mar May Jul Sep Nov
-*• Washington D.C.
-EJ- Shenandoah National Park
Figure 6-60. Daily concentration of (a) fine mass and (b) fine sulfur at Washington, DC,
and Shenandoah National Park.
6.5.1.4 New York City, New York
The New York City metropolitan area is characterized by high population density,
moderate industrial activity, and relatively flat terrain. The PM10 concentration over the
metropolitan area is shown in Figure 6-6 la. The circles in the map show the locations of the
monitoring sites and the magnitude of each circle is proportional to the average PM10
concentration at that site using all available data. The observed average concentrations change by
about of factor of two to three from one location to another. Higher average concentrations tend
to occur near the center of the metropolitan area.
In the New York City metropolitan area there was a decrease in the annual PM10
concentration between 1988 and 1994 from 35 ^g/m3 to 27 /ug/m3 for all sites and from
41 /^g/m3 to 34 Aig/m3 for trend sites (Figure 6-61b). The reductions were 23% for all sites and
17% for trend sites. There was unusually large difference between the two trends. The average
6-112
-------
PM10 Cone. Trend - New York City
EPA AIRS database
Seasonal PM Pattern - New York City
EPA AIRS Database
i
0.
60
55
45
40
35
30
25
20
15 -
10 -,
PM10 Station Months : 1676
PM2.5 Station Months : 258
PMC Station Months : 258
(C)
1989 1990 1991 1992 1993 1994 "1986 Mar May Ju, Sep
for all sites ^Avg for trend sites ^pM1Q ^PM25
Avg + Std. Dev. -®-Avg - Std. Dev.
PM Coarse
Figure 6-61. New York City region: (a) aerosol concentration map, (b) trend, and
(c) seasonal pattern.
6-113
-------
seasonal pattern over the subregion (Figure 6-6 Ic) is 25 to 30 //g/m3 throughout the year, but
rises to about 40 /ug/m3 in July.
The seasonal pattern at three different individual monitoring sites in the New York City
metropolitan area is shown in Figure 6-62a. The three sites all show similar seasonally with a
summer peak, but with elevated concentrations closer to the city center.
Size segregated aerosol samples in New York City (Figure 6-62b,c) show that at both sites,
PM10 concentrations are contributed primarily by fine particles. Based on the discussion of the
more extensive Washington, DC (Section 6.5.1.2) measurements, it can be inferred that the
summer peak in the fine mass is mainly due to the regional formation of the fine aerosols, while
the winter peak is contributed by the local sources, confined to the inner metropolitan area.
As part of the New York Summer Aerosol study (Leaderer et al., 1978) continuous size
monitoring confirmed the expected bimodal volume distribution with modes between 0.1 to
1.0 fj.m and >3.0 fj.m. A number of interesting patterns were observed when the size distribution
was averaged by hour of day. The diurnal average total number concentration showed a pattern
which corresponded closely with the normalized diurnal traffic pattern. Particles <0.1 //m
showed the most marked diurnal variation, following the total number curve. Moreover,
particles in size ranges >0.1 //m showed little variation in the diurnal pattern. Analysis of
samples processed by the diffusion battery indicated that approximately 54%±18% of the sulfate
measured was in the suboptical range (approximately 0.04 um to 0.3 jam) with the remainder
above 0.3 /um. Little sulfate mass was found in particles in the nuclei range (<0.04 fj.m).
Analysis of impactor samples for sulfates consistently showed that more than 85% of all water
soluble sulfates were <2.0 /j,m in size. Virtually no nitrate was present in the nuclei size range
while the suboptical size range accounted for approximately 30% of the total nitrate. 70% of the
total nitrate was found in the size range >0.3 //m. Analysis of large stages of Anderson impactor
showed that approximately 50% of particulate nitrate was greater than 5.5 //m in size.
Urban and rural particulate sulfur monitoring near New York City in the summer (Leaderer
et al., 1982) indicated that sulfate concentration distributions were regionally homogeneous and
increased with increasing ozone levels and covariant with several other pollutant and
meteorological parameters. Sulfate concentrations correlated strongly with ammonium and
strong acid at all sites. Strong acid concentrations were highest at the rural and semi-rural sites,
6-114
-------
70
.50
40
30
20
(a)
1985 Mar May Jul Sop Nov
-A-- PM10AVG NEW YORK CITY
-B- = PM2.5 AVG NEW YORK CITY
-I- = PMC AVG NEW YORK CITY
90
(b)
100
90
80
70
50
40
(c)
1985 Mar May Jul Sep Nov
-A- = PM10 AVG NEW YORK CITY
-B- = PM2.5 AVG NEW YORK CITY
-+- = PMC AVG NEW YORK CITY
1985 Mar May Jul Sep Nov
-&-= PM10AVG NEW YORK CITY
-B-= PM2.5 AVG NEW YORK CITY
-H= PMC AVG NEW YORK CITY
Figure 6-62a,b,c. Fine, coarse, and PM10 particle concentrations at three New York City
sites.
6-115
-------
lowest at the urban sites, increased with increasing ozone levels and exhibited diurnal patterns
which matched the ozone diurnal patterns.
Size dependent, mass and composition of New York aerosol for low, medium, and high
visibility levels was reported by Patterson and Wagman (1977). At all levels of visibility,
bimodal or multimodal particle size distribution were observed for total mass and for individual
components. Decreased visibility corresponded to increased particle mass concentrations
especially in the fine particle fraction. Increases in the proportion of particulate sulfate and to a
lesser extent of nitrate, chloride, ammonium, and carbon were also associated with decreased
visibility.
Aerosol pattern analysis of a major wintertime (1983) pollution episode near New York
City in northern New Jersey (Lioy et al., 1985) revealed that the intensity of the episode was the
greatest in the area of the highest commercial, residential and industrial activities, and that the
atmospheric stagnation conditions resulted in the significant accumulation of aerosol mass. The
aerosol mass was primarily fine aerosols, and the extractable organic matter comprising about
50% of the particle mass.
6.5.1.5 Philadelphia, Pennsylvania
The metropolitan area of Philadelphia includes urban-industrial emissions over flat terrain.
Relatively uniform PM10 concentrations throughout the metropolitan area, with the exception of
a single site (AIRS #421010149) in the middle of the urban area (Figures 6-63 and 6-64).
The downward trends in PM10 concentrations between 1988 and 1994 were largely or
completely negated by the upward trends in 1993 and 1994 (Figure 6-63b). The decrease in
annual PM10 concentrations at trend sites between 1988 and 1994 for all sites was from 39 /ug/m3
to 32 //g/m3, a decrease of 18%. The seasonal concentration of PM|0 (Figure 6-63c) is about
30 to 35 /-tg/m3 throughout the year, except during the summer months when it rises above
40 Aig/m3.
The seasonal average PMi0 concentrations for four sites near the center of Philadelphia is
shown in Figure 6-64. The high concentration site noted on the metropolitan map in
Figure 6-63a and two nearby sites in the industrial area long the riverfront are shown in
Figure 6-64a. The average PM10 concentration at that site ranges between 100 to 150
6-116
-------
PM10 Cone. Trend - Philadelphia
EPA AIRS database
198B 1989 1990 1991 1992 1993 1994
for all sites fl-Avg for trend sites
+ Std. Dev. -e-Avg - Std. Dev.
Seasonal PM Pattern - Philadephia
EPA AIRS Database
60
55
SO
45
40
35
30
25
20
15
10
PM10 Station Months : 1263
PM2.5 Station Months : 59
PMC Station Months : 59
(C)
1986 Mar May Jul Sep Nov
^PM2.5 -HPM Coarse
Figure 6-63. Philadelphia region: (a) aerosol concentration map, (b) trend, and
(c) seasonal pattern.
6-117
-------
E
OJ
1985 Mar May Jul Sep Nov
PM10, Philadelphia. AIRS #42-101-xxxx
Sites, -A-=0149, -B-= 0449, -+-=0049
100
90
80
70
60
50
40
30
20
10
(b)
°1985 Mar May Jul Sep Nov
Philadelphia, AIRS #42-101-0004
-A-= PM 10, -B-= PM 2.5, H-= PM Coarse
figure 6-64a,b. Seasonal particle concentrations at four Philadelphia sites. (Note scale
for (a) is 150 ug/m3.)
which is a factor of 2 to 3 higher than the concentration at the neighboring sites. The daily
concentrations at these source monitoring sites correlate poorly with a nearby site (Figure 6-64b)
that is only 4 km away but outside the industrial area. This is an indication that the
concentrations at the industrial sites are under the influence of a strong local source of PMi0. In
contrast, community sites in downtown and suburban Philadelphia that are as much as 30 km
apart show a strong correlation of daily measurements, indicating that a spatially uniform
regional aerosol influences the daily values in Philadelphia.
Size segregated aerosol samples (Figure 6-64b) show that fine particles contribute more
than coarse particles to the PM10 at this site. It is possible, however, that at other sampling sites,
e.g., the industrial sites (Figure 6-64a), coarse particles may prevail.
Outdoor summertime sulfate (SOJ) concentrations were found to be uniform within
metropolitan Philadelphia (Suh et al., 1995). However, aerosol strong acidity (H+)
6-118
-------
concentrations were found to vary spatially. Also, the wintertime sulfate pattern was likely to be
more heterogeneous in space and time. This variation generally was independent of wind
direction, but was related to local factors, such as the NH3 concentration, population density, and
distance from the center of the city.
6.5.1.6 Whiteface Mountain, New York
The AIRS sampling location at the Whiteface Mountain in Upstate New York is a
high mountain top site elevated from the surrounding terrain. The monitoring site offers the
possibility of comparing mountain top concentrations to the surrounding lower elevation sites.
The seasonal pattern of PM10 concentration for Whiteface Mountain and the surrounding low
elevation sites, Saranac Lake and Saratoga Springs, is shown in Figure 6-65. The concentration
at the three sites is virtually identical during June through September. However, during the
winter the mountain top site at Whiteface has a PM10 concentration which is only one third of the
low elevation sites. This indicates that during the winter, the Whiteface mountain top is above
the surface-based aerosol layer, while during the summer the height of the well mixed aerosol
layer rises above the mountain top producing a reasonably uniform concentration at all sites.
6.5.2 Subregional Aerosol Pattern in the Southeast
6.5.2.1 Atlantic Coast States
The average yearly concentration in the southeast Atlantic coast states for all sites and trend
sites has decreased from 32 to 24 ug/m3 and 25 ug/m3 (Figure 6-66a,b). The reductions were
25% and 22%. Seasonal concentrations show a summer peak largely due to PM2 5
(Figure 6-66c). Comparison of three AIRS PM10 monitoring sites in North Carolina's
Piedmont, Winston-Salem, Greensboro, and Raleigh-Durham (Figure 6-66d) shows virtually
identical concentrations (within 10%), both in absolute magnitudes and in the seasonally with
summer peaks in PM10. This is an indication that these sites in this subregion are exposed to
essentially the same air masses throughout the year. It also suggests that the excess PM10
concentrations due to local urban sources probably are not signficant.
6-119
-------
i
- - RM10 AVO
" — PM1O A.VO »Atf*ANAtG I_
- - F»M10 A\/O SARATOGA
Figure 6-65. PMlo concentration seasonally at Whiteface Mountain and neighboring
low-elevation sites.
Size segregated monitoring data for Winston-Salem (Figure 6-66f) show that fine particles
contribute 70 to 80% of the PMlo mass of 25 to 35 A*g/m3. Coarse particles are seasonally
invariant at about 10 //g/m3 which is typical for eastern U.S.
The PMjQ concentration at monitoring sites in Florida (Orlando, Miami, Tampa) show
virtually identical concentrations ranging between 25 to 30 yug/m3 throughout the year, without
appreciable seasonality (Figure 6-66e).
6.5.2.2 Texas and Gulf States
The average yearly concentration between 1 988 and 1 994 in the Texas-Gulf states has
decreased for all sites and tend sites from 28 to 25 ^ig/m3 (Figure 6-67b), a reduction of 1 1%.
Seasonal concentrations show a summer peak largely due to PM2.5 (Figure 6-68c). The seasonal
PMlo concentration at sites in Odessa, Amarillo, and Lubbock, TX, and in New Orleans, LA,
Mobile and Birmingham, AL show uniformity (20 to 40 /ig/m3) with modest seasonality
6-120
-------
Southeast Atlantic Coast States
PM10 Cone. Trend
SMMMlPMPMkm
(C)
fo
0)
Miy Jul 8«p
•A- • ran /wa WMSTOH-SALEM
-&-PM10AVO GREENSBORO
+ -PM10AVO RALEIGH
toy Jul Sw
* -raiOAVG ORLANDO
&-PM10AVQ TAMPA
+ >rail>AVGMAIII
Mty Jul S^>
-ft- • PMU AVG WMTON-SALEII
•e-• PMU AVG WMSTON-SA1EH
-I— PMC AV6 WMSTON-MUM
Figure 6-66. Aerosol concentration patterns for the Southeast Atlantic Coast states and sites in North Carolina and Florida:
(a) monitoring sites, (b) trends, (c) seasonal pattern, (d) North Carolina sites, (e) Florida sites, and (f) seasonal
pattern for Winston-Salem.
-------
PM10 Cone. Trend - S. Texas/Alabama
EPA AIRS database
Seasonal PM Pattern - Texas/Alabama
EPA AIRS Database
1988 1989 1990 1991 1992 1993
-A-Avg for all sites -B-Avg for trend sites
H-Avg + Std. Dev. -e-Avg - Std. Dev.
1994
60
55
50
45
40
35
30
25
20
15
10
PM10 Station Months : 6774
PM2.5 Station Months: 1B5
PMC Station Months : 1B5
(C)
Sep Nov
ODESSA
-B-= PM10 AVG AMARILLO
-H= PM10 AVG LUBBOCK
50
40
«
E 30
75>
=•20
5
°- 10
1986 Mar May Jul Sep Nov
-A-PM10 -B-PM2.5 H-PM Coarse
1985 Mar May Jul Sep Nov
-&-= PM10 AVG NEW ORLEANS
-H-= PM10AVG MOBIL
+= PM10 AVG BIRMINGHAM
Figure 6-67a,b,c,d,e,f,g,h,i. Aerosol concentration patterns in Texas and Gulf states.
6-122
-------
100
90
80
70
£
CD
a.
a.
60
50
40
30
20
10
(f)
1985 Mar May Jul Sep Nov
-&-= PM10 AVG HOUSTON
-Q-= PM10 AVQ AUSTIN
H-- PM10 AVG SAN ANTONIO
100,
90
80
70
60
50
40
30
20
10
(h)
1985 Mar May Jul Sep Nov
-A-=PM10AVG FORTWORTH
-3- = PM2.5 AVG FORTWORTH
-H= PMC AVG FORTWORTH
100
90
80
70
60
50
40
30
20
10
(9)
1985 Mar May Jul Sep Nov
-6-= PM10 AVG CORPUS CHRISTI
-B-= PM2.5 AVG CORPUS CHRISTI
-+- = PMC AVG CORPUS CHRISTI
100
90
80
70
60
50
40
30
20
10
0)
1*985 Mar May Jul Sep Nov
-A-= PM10AVG NEW ORLEANS
-B- = PM2.5 AVG NEW ORLEANS
-+- = PMC AVG NEW ORLEANS
Figure 6-67 (cont'd). Aerosol concentration patterns in Texas and Gulf states.
6-123
-------
(Figure 6-67d,e). The sites in Houston, Austin, and San Antonio, TX show a wider range of
PM10 values with summer peaks (Figure 6-67f).
The size segregated aerosol samples collected in the cities of the Gulf states, Corpus
Christi, Forth Worth and New Orleans, LA (Figure 6-67g,h,i) all show fine particle
concentrations that are relatively low (10 to 20 //g/m3) compared to large eastern cities. Coarse
particle concentrations, on the other hand, can account for more than half of the PM10 mass. The
coarse particle contribution is most pronounced during the summer season.
In Houston, TX, Dzubay et al. (1982) found that in summertime fine particle mass
contained 58% sulfate and 18% of carbonaceous material. They also found that the coarse
fraction (2.5 to 15 fj.ro) consisted of 69% crustal matter, 12% carbon, and 7% nitrate species.
6.5.2.3 Atlanta
Characterization of the Atlanta area aerosol (Marshall et al., 1986) show that elemental
carbon and particulate sulfur represent, respectively 3.1 to 9.9% and 1.9 to 9.4% of the total
suspended particulate mass. The concentrations of elemental carbon, sulfur, and TSP exhibit
strong seasonal variations, with elemental carbon decreasing from winter to summer, and sulfur
and TSP increasing. Elemental carbon appears to be statistically separate from sulfur, indicating
that the sources for elemental carbon and particulate sulfur are distinct.
6.5.2.4 Great Smoky Mountains
Size segregated fine and coarse aerosol concentrations were measured at the Great Smoky
Mountains National Park in September of 1980 (Stevens et al., 1980). Sulfate and its associated
ions contributed to 61% of the fine particle mass, followed by organics (10%) and elemental
carbon (5%).
6.5.3 Subregional Aerosol Pattern in the Industrial Midwest
Since the turn of the century, the major cities in the industrial midwestern states had air
pollution problems due to smoke and dust. Pittsburgh, St. Louis, Chicago, and Detroit were
among the formerly notorious air pollution hot spots. The recently acquired PM10 database now
6-124
-------
allows the re-examination of these metropolitan areas in the industrial Midwest for their
concentration pattern in the 1990s.
6.5.3.1 Pittsburgh, Pennsylvania
The average PM10 concentrations for sites in the extended metropolitan area is shown in
Figure 6-68. The Pittsburg, PA subregion includes the industrial cities, Steubenville, OH, and
Weirton, OH, located on the Ohio River. The average PM10 concentration at the 80 sites shown
on the map varies only by about 20% from site to site. Outstanding high concentration hot spots
are now absent. It is thus evident that during the 1985 to 1993 period, the average PM10
concentrations in the Pittsburgh subregion were spatially rather uniform.
In the Pittsburgh, PA metropolitan area there was a decrease in the annual average PM10
concentrations between 1988 and 1994 from 37 /ug/m3 to 32 //g/m3 for all sites and from
41 /ug/m3 to 33 /^g/m3 for trend sites (Figure 6-68b). The reductions were 14% for all sites and
19% for trend sites. Figure 6-68b also marks the concentration standard deviation among the
monitoring sites for each year, which is about 15 to 20% and shrinking over time.
The seasonality of the PM10 pattern (Figure 6-68c) is dominated by a summer peak
(45 //g/m3), which is about 50% higher than the winter concentrations (30 //g/m3). The sites in
Pittsburgh, PA, Weirton, OH, and Steubenville, OH (Figure 6-69) show comparable seasonality
and values that are slightly above the subregional average. Hence, the particles at these formerly
highly polluted locations are now virtually identical to their subregional background.
Size segregated aerosol samples in Pittsburgh, PA and Steubenville, OH (Figure 6-69)
show that fine particles contribute 70 to 80% of the PM10 mass, and also dictate the summer-
peak seasonality of the PM10 concentrations. As in other urban monitoring sites in the eastern
U.S., the coarse particle concentration in Pittsburgh is about 10 /ug/m3 and seasonally invariant.
The size segregated seasonal data for Steubenville, OH, exhibit more random fluctuations as well
as a discrepancy between the sum of fine and coarse on one hand, and PM10 on the other. The
discrepancy is attributed to the small number of size segregated aerosol samples.
Sulfate acidity measurements (Waldman et al., 1991) at Chestnut Ridge, PA (east of
Pittsburgh), suggest higher acidity occurred in the overnight period (0000-0800) in the late fall,
while sulfate had its highest levels in the morning to afternoon period.
6-125
-------
PM10 Cone. Trend - Pittsburgh
EPA AIRS database
E
O)
3.
5
O.
1969 1990 1991 1992 1993 1994
-A- Avg for all sites -B- Avg for trend sites
-+- Avg + Std. Dev. -e- Avg - Std. Dev.
60
55
50
45
40
35
30
25
20
15
10
5
Seasonal PM Pattern - Pittsburgh
EPA AIRS Database
PM 10 Station Months : 2937
PM2.5 Station Months : 159
PMC Station Months : 162
(C)
1986 Mar
May Jul
-B-PM2.5
Sep Nov
PM Coarse
Figure 6-68. Pittsburgh subregion: (a) aerosol concentration map, (b) trends, and
(c) seasonal pattern.
6-126
-------
100
90
80
70
E
o>
3.
s
Q.
80
SO
40
10
(a)
1985 Mar May Jul Sep Nov
A . PM10 AVQ PITTSBURGH
-B-. PM10 AVO WEIRTON
-+-• PM10 AVQ STEUBENVILLE
100
90
80
70
m 60
E
^ so
2
Q.
40
20
10
(c)
1°985 Mar May Jul Sep Nov
-A-" PM10 AVG PITTSBURGH
-B-. PM2.5 AVO PITTSBURGH
~t-- PMC AVQ PITTSBURGH
100
90
80
60
40
20 -
(b)
1985 Mar May Jul Sep Nov
-&-- PM10 AVQ STEUBENVILLE
-B-- PM2.5 AVO STEUBENVILLE
-H- PMC AVQ STEUBENVILLE
100
90
70
60
40
20
10
(d)
1985 Mar May Jul Sep Nov
-&-- PM10 AVQ PITTSBURGH
-B-» PM2.5 AVQ PITTSBURGH
H-- PMC AVG PITTSBURGH
Figure 6-69a,b,c,d. Fine, coarse, and PM10 concentration at sites in or near Pittsburgh.
6-127
-------
Pierson et al. (1980b, 1989) found no appreciable night/day difference in aerosol H+
(or NH4+ or SO42") - and almost no diurnal variation in O3 - at two elevated sites (Allegheny
Mountain and Laurel Hill, elevations 838 and 850 m) in southwest Pennsylvania. The contrast
with behavior at lower sites and particularly with the concurrent measurements at Deep Creek
Lake (Vossler et al., 1989) is attributable to isolation from ground-based processes at the
elevated sites at night.
The remarkable uniformity of fine particle mass and elemental composition from site to site
in the Ohio River Valley was also shown by Shaw and Paur (1983). Sulfur was the predominant
element in fine particles. Factor analysis of element concentrations indicated three clusters
throughout the year (1) coarse particle crustal elements (2) fine particle sulfur and selenium
(3) fine particle manganese, iron and zinc.
The chemical mass balance of Weirton-Steubenville aerosol was examined by Skidmore
et al. (1992). Primary aerosols from motor vehicles and secondary ammonium sulfate were
dominant contributors to the PM2 5 aerosol. Steel emissions were also significant contributors to
PM2 5. Wood burning and oil combustion were occasionally detected. Geological material was
the major contributor to the coarse aerosol fraction. Primary geological material, primary motor
vehicle exhaust, and secondary sulfate were the major contributors to PM10 at all five monitoring
sites.
The composition of size-fractionated summer aerosol in nearby Charleston, West Virginia
was reported by Lewis and Macias (1980). Ammonium sulfate was the largest single chemical
component (41%) of the fine aerosol mass. Carbon was also a large component of both fine and
coarse particle mass constituting 16% and 12% respectively. Factor analysis indicated that four
factors were sufficient to satisfactorily represent the variance of 26 measured parameters. The
factors were characteristic of crustal material, ammonium sulfate, automotive emissions, and
unidentified anthropogenic sources.
6.5.3.2 St. Louis, Missouri
Historically, the St. Louis metropolitan area has been known for high particulate
concentrations. The map of the metropolitan area (Figure 6-70a) shows about factor of 2 to
3 concentration differences among the PM10 monitoring stations.
6-128
-------
PM10 Cone. Trend - St. Louis
EPA AIRS databate
Seasonal PM Pattern - Pittsburgh
EPA AIRS Databat •
1989 1990 1991 1992 1993 1994
-&- Avg for all sites -B- Avg for trend sites
-+- Avg + Std. Dev. -©- Avg - Std. Dev.
PM10 Station Months : 2937
PM2.5 Station Months : 159
PMC Station Months : 162
1986 Mar May Jul Sep Nov
-B-PM2.5 H-PM Coarse
Figure 6-70. St. Louis subregion: (a) aerosol concentration map, (b) trends, and
(c) seasonal pattern.
6-129
-------
In the St. Louis metropolitan area there was a decrease in the annual average PM10
concentration between 1988 and 1994 from 37 //g/m3 to 30 [J,g/m3 for all sites and from
40 /ug/m3 to 31 yug/m3 for trend sites (Figure 6-70b). The reductions were 23% for all sites and
22% for trend sites. This decline is comparable to the average reductions over the industrial
midwestern region. The seasonality of the sub-regionally averaged concentrations (Figure 6-70c)
shows the summer peak with 40 to 50 /ug/m3 which is about 50% higher than the winter
averages.
Seasonal comparison of the individual monitoring sites in the area shows that Granite City,
IL and East St. Louis, IL have higher PM10 concentrations throughout the year compared to
western St. Louis, MO sites.
Size segregated aerosol samples at three sites west of the Mississippi River (Ferguson, MO,
Affton, MO, and Clayton, MO) show that fine particles are mostly responsible for PM10,
including the seasonality (Figure 6-71). Coarse particles contribute 10 /ug/m3 or less throughout
the year, although corresponding size segregated aerosol data for the more polluted east side of
the Mississippi River are not available.
Monitoring the diurnal and seasonal patterns of particulate sulfur and sulfuric acid in
St. Louis, Cobourn and Husar (1982) noted an afternoon increase in particulate sulfur
concentration of about 20%. For the summertime, particulate sulfur concentration was higher
than the annual mean by 40%.
Measurements were made using dichotomous samplers of PM10 (expressed as PM20),
PM2 5 and S at urban, suburban, semi-rural, and rural sites in and around St. Louis, MO, during
1975 to 1976 as part of the Regional Air Pollution Study (RAPS) (Altshuller, 1982). Unlike the
nonurban sites compared from the IMPROVE/NESCAUM network with urban sites from AIRS,
these rural sites were within 45 km of the center of St. Louis. The comparisons are between
three urban sites (103, 105,106) and three rural sites (118,112,124).
The PM2 5 constituted 45 to 60% of the PM10 with the percentages at rural sites ranging
from 0 to 10% higher than at urban sites. The ratios of the concentrations of PM2 5 at urban sites
to PM2 5 at rural sites ranged from 1.4 to 1.5 for the six quarters between the third quarter of
1975 to the fourth quarter of 1976. The ratios of the concentrations of PMCoarse at urban sites
to PMCoarse at rural sites ranged from 1.5 to 1.8 for the same six quarters. For fine S, the ratios
6-130
-------
80
70
O9
=• 50
S
o.
40
30
10
(a)
1965 Mar May Jul Sep Nov
-A- ,
• PM10AVOST LOUIS
• PM10 AVO GRANITE CITY
• PM10 AVO EAST ST LOUIS
80
« 60
E
o>
30
(c)
1985 Mar May Jul Sep Nov
~^~ - PM10 AVG CLAYTON
~B' - PM2.5 AVG CLAYTON
~~l"~ - PMC AVG CLAYTON
100
80
80
SO
40
10
(b)
1985 Mar May Jul Sep Nov
A 'PM10 AVG FERGUSON
~B~ * PM2.5 AVO FERGUSON
~+~ * PMC AVG FERGUSON
•0
70
30
20
10
(d)
1985 Mar May Jul Sep Nov
-A- ,
-B-
PM10AVG AFFTON
PM2.S AVG AFFTON
PMC AVG AFFTON
Figure 6-71a,b,c,d. Fine, coarse, and PM10 seasonal concentration patterns in or near
St. Louis.
6-131
-------
between urban and rural sites ranged from 1.1 to 1.2, while for coarse S, the ratios between urban
and rural sites ranged from 1.7 to 2.6 for the same six quarters.
These results indicate a very strong regional influence on fine S with a lesser regional
influence on PM2 5. The ratios of PMCoarse and coarse S indicate stronger local influences on
their concentrations than on fine S and PM2 5. The percentage of fine S expressed as (NH4)2 SO4
to the PM2 5 was consistently higher at rural sites than at urban sites in and around St. Louis
(Altshuller, 1982). In the third quarters of 1975 and 1976, these percentages averaged 70% at
rural sites and 55% at urban sites, while in the fourth quarters of 1975 and 1976, these
percentages averaged 45% at rural sites and 35% at urban sites.
As observed near New York City (Leaderer et al., 1982), the fine S in the St. Louis area
was regionally homogenous and, during episodic periods, the fine S concentrations followed the
variations in O3 concentrations reasonably closely (Altshuller, 1985). A linear relationship was
obtained for fine S and O3 flows into St. Louis. The fine S with increasing fine S concentration
constituted an increasingly large percentage of the PM2 5 at an urban site (Altshuller, 1985).
6.5.3.3 Chicago, Illinois
Historically, Chicago has been known for industrial dust, smoke, and haze, as in adjacent
East Chicago and Gary, IN. The average PM]0 concentrations over the Chicago subregion
(Figure 6-72a) vary by a factor of two or less throughout the subregion. In the Chicago
subregion, there was a decrease in the annual average PM10 concentrations between 1988 and
1994 from 32 /ug/m3 to 29 /ug/m3 for all sites and from 39 //g/m3 to 31 /ug/m3 for trend sites
(Figure 72b). The reductions were 9% for all sites and 20% for trend sites. The seasonality of
PM10 is also typical with the summer peak of 40 /ug/m3 and winter values of 20 to 30 /ug/m3.
Superposition of seasonal PM10 data at Chicago, IL, East Chicago, IL, and Gary, IN,
demonstrates significant spatial uniformity, as well as indicating in more recent years
comparatively low PM10 concentrations in this area that has historically been a smoky and dusty
industrial subregion.
In the Chicago subregion there was a decrease in the annual average PM10 concentration
between 1985 and 1994 from 40 /ug/m3 to 29 /ug/m3 for all sites and from 40 /ug/m3 to 31 /ug/m3
for trend sites (Figure 6-72b). The reductions were 28% for all sites and 23% for trend sites.
6-132
-------
PM10 Cone. Trend - Chicago
EPA AIRS database
Seasonal PM Pattern - Chicago
EPA AIRS Database
1989 1990 1991 1992 1993 1994
-&- Avg for all sites -B- Avg for trend sites
-i- Avg + Std. Dev. -e- Avg - Std. Dev.
15
PM10 Station Months : 3245
PM2.S Station Months : 0
PMC Station Months : 0
(c)
150
140
130
120
110
100
90
rt
E »"
CP)
=• 70
S
Q. 60
50
40
30
20 -
10
(d)
Mar May Jul
-A- PM10 -B- PM2.5
Sep Nov
PM Coarse
1°985 Mar May Jul Sep
-A-= PM10AVG CHICAGO
Nov
-B-= PM10 AVG EAST CHICAGO
-H- PM10AVGGARY
Figure 6-72. Chicago subregion: (a) aerosol concentration map, (b) trends, (c) and
(d) seasonal patterns.
6-133
-------
Chemical composition measurements in Chicago (Lee et al., 1993) showed that mean
concentrations for SO42- (5.55 //g/m3), NH4+ (2.74 Aig/m3), NH3 (1.63 Atg/m3), HNO3
(0.81 ^g/m3), HNO2 (0.99 /ug/m3), for SO2 (21.2 /ug/m3), NO3' (4.21 //g/m3), and H+
(7.7 nmol/m3). The highest values occurred in the summer, except for HNO2 and NO3" which
had the highest values in the winter.
Comparison of atmospheric coarse particles at an urban and nonurban site near Chicago,
IL, show that the concentration were 50% higher during mid-day than at night. Dry ground
samples were 30 % higher than wet ground and 90% higher than frozen ground samples. (Noll
etal., 1985).
The analysis of coarse particles in Chicago, IL (Noll et al., 1990) show that the coarse
particle mass could be divided into two categories: material that was primarily of crustal origin
(Al, Ca, Fe, and Si) and material that was primarily of anthropogenic origin (Cd, Cu, Mn, Ni, Pb,
and Zn). The mass of crustal material varied between 14 and 24% of the total coarse mass. The
mass of Cd, Cu, Mn, Ni, Pb, and Zn totaled less than 1%.
The composition of atmospheric coarse particles at urban (Chicago, IL) and nonurban
(Argonne, IL) were reported by Noll et al. (1987). Limestone and silicates were the main source
of material at the non urban site. Anthropogenic sources, represented by flyash and coal, were
present in the industrial sector sample and rubber tire was present in the commercial sector
sample.
6.5.3.4 Detroit, Michigan
In Detroit, in July, 1981 (Wolff and Korsog, 1985) the average fine mass was found to
be 42.4 A*g/m3. The chemical composition of the fine particles (Wolff et al., 1982) was 52%
sulfates, 27% organic carbon, 4% elemental carbon, 8% soil dust. Nitrate was found to be
absent from fine mass. Fine particles themselves contributed about 64% of the aerosol mass.
The sulfate associated with coal combustion contributed to 50% of the fine particles. The
coarse fraction, which averaged as 25.8 /^g/m3, was dominated by crustal material which
accounted for about two-thirds of the coarse material. Significant contributions were also
identified from motor vehicles (mostly due to re-entrained road dust) and iron and steel industry
emissions.
6-134
-------
The seasonal variations in nitric acid, nitrate, strong aerosol acidity, and ammonia in
Warren, MI, was examined by Cadle (1985). The greatest variations was for ammonia, which
was 8.5 times higher in summer than winter. The least variation was for particulate nitrate which
had a summer maximum only 1.8 times higher than in spring minimum. It was noted that
ammonium nitrate volatilization from filters and impactors can cause large errors in
summertime measurements, but the errors are not significant during the winter.
The influence of local and regional sources on the concentration of particulate matter in
urban and rural sites near Detroit, MI was investigated by Wolff et al. (1985). Analysis of spatial
variations of the various particulate components revealed: (1) at all four sites the PM2 5 was
dominated by regional influences rather than local sources. The site in industrial sector had the
largest impact of local sources, but even at his site the local influences appears to be smaller than
the regional ones. (2) The regional influences were most pronounced on the sulfate levels which
accounted for 40 to 50% of the PM2 5. (3) Organic carbon compounds were the second most
abundant PM2 5 species accounting for 20 to 40% of the mass. Organic carbon seems to be
controlled by both local and regional organic carbon influences. Vehicular emissions and
possibly secondary reactions appear to affect the organic carbon concentrations. (4) Elemental
carbon appears to be dominated by local emission. (5) PMCoarse was dominated by local
sources, but at the industrial site unknown non-crustal elements were significant components
of coarse mass.
6.5.5 Subregional Aerosol Pattern in the Southwest
The arid southwestern U.S. includes metropolitan areas (El Paso, TX, Phoenix-Tucson,
AZ) with modest industry and national parks (Grand Canyon) where the prevention of
visibility degradation has been stated as a national goal. The southwest is a dusty region and
much of the discussion below pertains to coarse particles and soil dust.
6.5.5.1 El Paso, Texas
The PM10 concentration in the El Paso, TX, subregion shows that the high and low
concentration sites occur near each other (Figure 6-73a). This is an indication that local
sources of PM10 with limited range of impact are important. In the El Paso, TX, subregion
6-135
-------
PM10 Cone. Trend - El Paso
EPA AIRS database
1989 1990 1991 1992 1993 1994
-A- Avg for all sites -Q- Avg for trend sites
H-Avg + Std. Dev. -6-Avg - Std. Dev.
60
Seasonal PM Pattern - El Paso
EPA AIRS Database
55
50 -
45
40
35
25
20
15
10
PM10 Station Months : 1108
PM2.5 Station Months : 32
PMC Station Months : 32
(C)
1986 Mar May Jul Sep Nov
-&- PM10 -a- PM2.5 -+- PM Coarse
Figure 6-73. £1 Paso subregion: (a) aerosol concentration map, (b) trends, and
(c) seasonal pattern.
6-136
-------
there is a decrease in the annual average PM10 concentration between 1988 and 1994 from
46 Mg/m3 to 25 //g/m3 for all sites and from 57 //g/m3 to 34 /ug/m3 for trend sites
(Figure 6-73b). The reductions were 46% for all sites and 40% for trend sites. This
substantial reduction exceeds the PM10 decline over the entire southwestern region
(Figure 6-46b).
The seasonality of PM10 over the El Paso, TX subregion (Figure 6-73c) is bimodal with
peaks in the spring time, March through July, as well as another stronger peak, October
through November. This double peak seasonality at El Paso, TX, also parallels the
seasonality of the entire region. The concentration reduction in August which coincides with
the arrival of moist flow from the Gulf of Mexico into states in the southwest (Figure 6-46d).
Size segregated aerosol samples for El Paso, TX (AIRS #481410037) show that coarse
particles dominate the PM10 concentrations, accounting for about 70% of the PM10 mass
(Figure 6-74a). This is consistent with the important role of coarse particles over the arid
Southwest. In comparison, size segregated data for San Antonio, TX (Figure 6-74b) located
closer to the Gulf Coast in Texas, show that fine and coarse mass have comparable contributions,
similar to Houston, TX.
6.5.5.2 Phoenix and Tucson, Arizona
The Phoenix-Tucson subregion (Figure 6-75a) shows a substantial PM10 concentration
range. Samplers within the Phoenix or Tucson area indicate 2 to 3 times higher concentrations
than the more remote sites, particularly the ones in the mountains. For the Phoenix-Tucson
subregion there was a decrease in the annual average PM10 concentration between 1988 and 1993
from 39 A*g/m3 to 28 A*g/m3 for all sites and from 49 Atg/m3 to 32 fj.g/m3 for trend sites
(Figure 6-75b). The reductions were 28% for all sites and 35% for trend sites. The decrease in
PM concentration were not monotonic. The average PM10 seasonality of the Phoenix-Tucson
subregion (Figure 6-75c) shows the bimodal spring and fall peak pattern which is characteristic
for the entire Southwest region.
During the Phoenix Urban Haze Pilot Study during the winter 1988 to 1989 (Frazier, 1989)
a definite diurnal cycle in PM2 5 concentrations was observed. The maximum, generally but not
6-137
-------
100
90 -
BO
70 -
60
I
3. 50
5
Q.
40
30
20
10
(a)
100
90
80
70
SO
50
40
30
20
10
(b)
1985 Mar May Ju\ Sep Nov
-A- = PM10AVGELPASO
-B- = PM2.5AVGELPASO
-+- = PMC AVG EL PASO
19B5 Mar May Jul Sep Nov
-&- = PM10AVG SAN ANTONIO
-H- = PM2.5 AVG SAN ANTONIO
-+- = PMC AVG SAN ANTONIO
Figure 6-74a,b. Fine, coarse, and PM10 concentration patterns in El Paso and San
Antonio.
always, occurred at night, which is consistent with the meteorological observations of poor
dispersion and dilution.
The wintertime aerosol chemical pattern in Phoenix was reported by Chow et al. (1990)
and Solomon and Moyers (1986). These investigators found fine particle crustal species,
sulfates, nitrates, and organic and elemental carbon to be at least five times higher in
concentration when comparing samples during a period of limited visibility to samples taken
during good visibility.
A chemical characterization of wintertime fine particles in Phoenix, AZ (Solomon and
Moyers, 1986) showed a dominance of organic carbon and nitrate aerosols. The composition in
Phoenix is most like that of Denver, CO, a city which also experiences wintertime inversions
6-138
-------
PM10 Cone. Trend - Phoenix/Tucson
EPA AIRS database
Seasonal PM Pattern - Phoenix/Tucson
EPA AIRS Database
60
55
50
45
40
35
30
25
20
15
10
PM10 Station Months: 1630
PM2.5 Station Months : 0
PMC Station Months : 0
(C)
1986 Mar May Jul
-&- PM10 -B- PM2.5
Sep Nov
PM Coarse
198B 19B9 1990 1991 1992 1993 1994
-A- Avg for all sites -Q- Avg for trend sites
~+- Avg + Std. Dev. "^ Avg - Std. Dev.
Figure 6-75. Phoenix-Tucson subregion: (a) aerosol concentration map, (b) trends, and
(c) seasonal pattern.
6-139
-------
(Pierson and Russell, 1979; Countess et al., 1980; Groblicki et al., 1981). In both cities, the
average measured NO3" concentrations were about 1 to 2 times that of the average SOJ
concentration. In addition, the average SOJ concentration measured in Phoenix was much lower
than those observed at other locations throughout the U.S., but similar to the regional values
observed in the Southwest (Moyers, 1982).
Wintertime PM10 and PM2 5 chemical compositions and source contributions in
Tucson, AZ (Chow et al., 1992a) show that the major contributors to the highest PM10
concentrations were geological material (>50%) and primary motor vehicle exhaust (> 30%) at
three urban sampling sites. Secondary ammonium sulfate, secondary ammonium nitrate, and
copper smelter aerosols were found to contribute less than 5% to elevated PM10 concentrations.
The OC/EC ratio was one to one at Phoenix sites. The average arsenic concentrations in
Phoenix was four times higher than observed in other cities, which indicates the potential
influence of Arizona smelters located within 100 miles of Phoenix. Average sulfate levels in
Phoenix were higher than they were in Denver, which has less local emissions of SO2.
6.5.5.3 Grand Canyon National Park
McMurry and Zhang (1989) reported the size distribution of ambient organic and
elemental carbon near the Grand Canyon and in the Los Angeles basin. Virtually all of the
carbon was found in the submicron range, some below 0.1 ^m. However, positive sampling
artifacts for sub 0. Iptm organics were considered significant.
At the Grand Canyon National Park, Zhang et al. (1994) showed that sulfates and
carbonaceous particles were the major contributor to PM2 5 particle scattering during the three
winter months and that their contributions were comparable. Scattering by nitrates and soil
dust was typically a factor of five to ten smaller. The low pressure impactor measurements
also showed that sulfur size distributions vary considerably (0.07 to 0.66 //m).
6.5.6 Subregional Aerosol Pattern in the Northwest
The mountainous northwestern United States has many aerosol regions with different
characteristics. The discussion below will examine South Lake Tahoe, as a case study for
6-140
-------
mountain-valley difference, Salt Lake City, UT, Denver, CO, Idaho-Montana sites, and
several Washington-Oregon sites.
6.5.6.1 South Lake Tahoe
South Lake Tahoe IMPROVE monitoring site is located in a in a populated area on the
south shore of Lake Tahoe. The Bliss State Park IMPROVE monitoring site is to the
northwest, elevated (700ft) and removed from the populated areas. The pair of sites illustrates
the populated area-remote difference hi aerosol pattern. The aerosol and visibility at the two
lake Tahoe sites were also examined (Molenar et al., 1994).
The concentration of all aerosol components is substantially higher on the south lake
shore compared to the more remote site. The seasonally and chemical composition is also
substantially different. The excess PM10 concentration at the S. Lake Tahoe site compared to
Bliss State Park (Figure 6-76) is about 5 /ug/m3 during the warm season, May through
September, and it climbs to 28 /^g/m3 excess hi January. The factor of five seasonal
modulation for valley excess PM10 is likely contributed by winter tune emission sources, poor
dispersion compared to the summer, as well as fog, all of which tend to enhance the aerosol
formation. Fine and coarse particles contribute roughly equally to excess PM10 mass
concentrations. However, fine particles contribute about 60% during the fall season and
coarse particles prevail (> 60%) during the spring. Both fine and coarse particles show a
winter peak concentration.
The chemical composition of the valley excess fine particle mass concentration also
shows a strong seasonality for organic carbon and elemental carbon. In fact, the excess
organic carbon concentration hi the whiter (13 //g/m3) is almost an order of magnitude higher
than the summer values. The seasonal concentration of excess elemental carbon is similar to
that of the organic carbon. However, the relative magnitude of organic carbon compared to
elemental carbon is higher in the winter (factor of five) than in the summer (factor of two).
The concentration of fine particle sulfate is virtually identical for South Lake Tahoe and Bliss
State Park. This implies that the South Lake Tahoe aerosol sources do not contain sulfur. It is
also worth noting that the excess fine particle soil at South Lake Tahoe is below 1 /^g/m3, which
is a small fraction of the coarse mass. Thus, the crustal component of the South Lake
6-141
-------
^
ff
w
*
o
85
n
3
09
i
a
o
B
=
O
5
•a
o
09
Mass
o
B
Concentration pg/m3
§
«•+•
tf
r
B*
BT
O
A
O
O
5
I
8-
a
ir
-k ro to to
-------
Tahoe aerosol contributes to the coarse mass but not appreciably to the fine mass
concentration.
In summary, there is a significant excess PM10 aerosol concentration at S. Lake
Tahoe compared to the adjacent Bliss State Park remote site, particularly during the winter
season (28 ,ug/m3). The excess mass is about equally distributed between fine and coarse
particles. The fine mass is largely composed of organics.
6.5.6.2 Salt Lake City, Utah, Subregion
Salt Lake City, Ogden, and Provo, UT, are part of an airshed that is confined by tall
mountains to the East, limiting the dispersion by westerly winds.
The seasonal average PM10 concentration at three AIRS sites in Salt Lake City, Ogden, and
Provo, UT, is shown in Figure 6-77b. All three sites show virtually identical seasonality, having
peak concentrations during December through January. This confirms that the three sites belong
to the same airshed with similar source pattern, meteorological dispersion and chemical
transformation and removal processes.
During the 1988 to 1994 period there were overall decreases in the annual average PM10
for the Salt Lake City, UT subregion from 49 /ug/m3 to 29 fj-g/m3 for all sites and from 54 //g/m3
to 30 /^g/m3 for trend sites (Figure 6-77b). The reductions were 41% for all sites and 48% for
trend sites. The trends were not monotonic, but showed substantial shifts upwards and
downwards during the 1988 to 1994 period.
The size segregated fine and coarse concentration data exhibit a dynamic seasonal pattern.
Fine particles clearly dominate the high winter concentrations reaching 40 to 50 /ug/m3,
compared to summer concentrations of 10 ^ug/m3. This magnitude of fine mass concentration is
among the highest recorded in the AIRS data system. Coarse particles are less seasonal and they
are more important during the dry summer season. The formation of sulfate and nitrate during
winter inversion fogs near Salt Lake City, UT were studied by Mangelson et al. (1994).
6-143
-------
PM10 Cone. Trend - Salt Lake City
EPA AIRS d
Seasonal PM Pattern - Salt Lake City
EPA AIRS Dltabut
(d)
* • PM1D AVG SALT LAKE CITY
-B-- PMtO AVG 06DEN
+ • PMtO AVG PROVO
(c)
Miy Jill
PMtO -B- PM2.5
S>p
- PM CMIM
• PMtO AVG NOTINA CITY
O » PM2 5 AVG NOTINA CITY
-I- » PMC AVG NOTINA CITY
My M Sip
• PM10 AVO SALT LAKE CITY
* PM2 5 AVG SALT LAKE CITY
- PMC AVG SALT LAKE CITY
Figure 6-77. Salt Lake City region: (a) aerosol concentration map, (b) trends, (c) seasonal pattern, and (d,e,f) seasonal patterns
at sites in or near Salt Lake City.
-------
6.5.6.3 Denver, Colorado
The Denver brown cloud is a manifestation of high wintertime concentration of particles
and gases. Several recent studies have focused on the characterization of the Denver brown
cloud aerosols.
Size distribution measurements of winter Denver aerosol (Countess et al., 1981) show that
on high pollution days that the mass median aerodynamic diameter of the accumulation mode
aerosol was about 0.31 //m with Og±2.0. Wolff et al. (1981) found that on the average motor
vehicles were responsible for 27% of the elemental carbon while wood burning was responsible
for 39% of the elemental carbon.
The chemical composition of wintertime Denver fine aerosol mass (16.4 //g/m3) (Sloane
et al., 1991) shows the dominance of total carbon consisting of organic carbon (8.1 //g/m3)
and elemental carbon (2.6 //g/m3) over sulfate (1.2 //g/m3) and nitrate (3.4 //g/m3). The fine
particle size distribution of sulfate and nitrates were bimodal.
6.5.6.4 Northern Idaho-Western Montana Subregion
The mountainous northern Idaho and western Montana subregion is characterized by
deep valleys and the absence of major industrial sources or large urban-metropolitan areas.
Nevertheless, PM10 monitoring sites in northern Idaho and western Montana report
concentrations that are among the highest in the nation, as illustrated hi Figure 6-78a, while
neaby sites are among the lowest. The large spatial concentration variability is evidently
related to the rugged terrain. Most of the monitoring sites are located in the flat valleys.
In the northern Idaho-western Montana subregion there was a decrease in the annual
average PM10 concentrations between 1988 and 1993 from 41 //g/m3 to 30 //g/m3 for all sites
and from 40 //g/m3 to 31 //g/m3 for trend sites. The reductions were 27% for all sites and
23% for trend sites (Figure 6-78b). The average seasonality of the subregion is strongly
whiter peaked (Figure 6-78c) with a factor of two modulation between 25 and 45 //g/m3.
The high spatial variability is illustrated hi an example from northern Idaho
(Figure 6-79a). Three sites in Missoula, MT, show winter monthly averaged peak
concentrations from less than 40 to more than 100 //g/m3. This is higher than the monthly
average PM10 concentration anywhere in the eastern U.S. The site closest to the city center
6-145
-------
PM10 Cone. Trend - N. Idaho/NW Montana Seasonal PM Pattern - Idaho/Montana
EPA AIRS database EPA AIRS Database
60
55
50
45
40
30
25
20
15
10
PM10 Station Months : 1985
PM2.5 Station Months : 0
PMC Station Months : 0
(C)
1988 1989 1990 1991 1992 1993 1994 19B6 Mar May Jul Sep Nov
-A- Avg for all sites -B-Avg for trend sites ^ PM10 -a- PM2.5 -t- PM Coarse
+ Std. Dev. ^Avg - Std. Dev.
Figure 6-78. Northern Idaho-Northwestern Montana subregion: (a) aerosol concentration
map, (b) trends, and (c) seasonal pattern.
6-146
-------
100
10 -
•P985
Mar May Jul Sep Nov
•*"= PM10AVG MISSOULA
-&-= PM10AVG MISSOULA
-*-= PM10AVG MISSOULA
100
90
70
SO
40
30
20
10
(C)
Mar
May Jul Sep Nov
= PM10 AVG BOISE CITY
sPM 10 AVG SALMON
= PM10AVG IDAHO FALLS
1985 Mar May Jul Sep Nov
« PM10 AVG ANACONDA- DEER LODGE COUNTY
= PM10 AVG ANACONDA DEER LODGE COUNTY
= PM10 AVG ANACONDA- DEER LODGE COUNTY
Figure 6-79a,b,c. PM10 concentration patterns at sites in the Northern Idaho-
Northwestern Montana subregion.
6-147
-------
shows the highest winter peak (> 100 Mg/m3), but has summer values that are comparable to
the other two sites. It is evident that in Missoula, MT, high concentration gradients exist
between the populated areas and remote sites. Boise and Salmon, ID (Figure 6-79b) also show
elevated PM10 concentrations during the cold season. Idaho Falls, ID, on the other hand, is
seasonally uniform at about 30 //g/m3, which is comparable to the lowest Missoula, MT, site.
Unusually low PM10 concentrations of 10 /ug/m3 are reported at three PM10 monitoring
sites near Anaconda-Deer, ID (Figure 6-79c). This result is unexpected because the sites are
in a valley. The characteristic winter peak is completely absent. This suggests that pristine,
low, PMjQ sites can exist in the northwestern valleys, and hence the region is not uniformly
covered by wintertime haze or smoke.
6.5.6.5 Washington-Oregon Subregion
The Pacific Northwest is also a mountainous subregion that exhibits unique aerosol
characteristics. During 1988 to 1994, there were decreases in the annual average PM10
concentrations for the Washington-Oregon subregion from 36 /jg/m3 to 26 /xg/m3 for all sites
and from 39 /*g/m3 to 28 /xg/m3 for trend sites. The reductions were 28% for both all sites
and trend sites. The subregion shows a strong seasonally with a winter peak due to PM2 5
(Figure 6-80b). PM10 monitoring sites in Seattle, Bellevue, and Tacoma, WA (Figure 6-80d),
show relatively low concentrations and a lower seasonality although higher values occur in the
winter. A much more pronounced seasonality of PM10 concentrations is recorded in southern
Oregon. Medford, Grants Pass, and Klamath Falls, OR (Figure 6-80e) evidently belong to an
airshed hi which emissions, dispersion, and aerosol formation mechanisms are conducive to
the formation of whiter tune aerosol (60 to 80 /ug/m3).
Fine and coarse particle data collected over a limited period in 1987 show that the winter
peak of PM10 is entirely due to the strong winter peak of fine particle mass (50 to 100 /ug/m3).
Coarse mass, on the other hand, is seasonally invariant at about 10 to 20 /ug/m3. Fine
particles clearly are responsible for the whiter peak. This is somewhat different from the
observations at South Lake Tahoe, where the winter peak was attributed to both fine and
coarse particles.
6-148
-------
PM10 Cone. Trend - Washington/Oregon
EPA AIRS databau
Seasonal PM Pattern -Washington/Oregon
EPA AIRS Database
n 35
E
25
PM 10 Station Months 5142
PM2.5 Station Montht 68
PMC Station Month! : 97
(C)
1986 Mar May Jul
-6-PM10 -B-PM25
8ep Nov
~PM Coarte
f9B8 1989 1990 1991 1992 1993 1994
for all cite* "O"Avo for trend cites
-Avg * Std. Dev. -S-Avg - Std. D«v.
40
30
(d)
1985 Mar May Jul Sep
-A- » PM10 AVQ SEATTLE
Nov
-B-
• PM10 AVG BELLEVUE
= PM10AVQ TACOMA
Figure 6-80a,b,c,d,e,f,g,h. Aerosol concentration patterns in Washington State and
Oregon.
6-149
-------
1985 Mar May Jul Sep Nov
A = PM10AVG MEDFORD
~B~ » PM10 AVQ GRANTS PASS
~+~ = PM10 AVQ KLAMATH FALLS
100
80
70
BO
40
30
10
(g)
1985 Mar May Jul Sep Nov
-&~ -PM 10 AVQ BEND
-B- -PM2.SAVO BEND
-*-" = PMC AVQ BEND
100
BO
BO
70
60
SO
30
20
10
(f)
1985 Mar May Jul Sep Nov
-&- = PM10AVQ MEDFORD
-B- - PM2.5 AVO MEDFORD
~+~ = PMC AVQ MEDFORD
100
90
80
70
BO
40
30
20
10
(h)
1985 Mar May Jul Sep Nov
~&~ « PM10 AVQ CENTRAL POINT
-B- » PM2.S AVQ CENTRAL POINT
~+~ = PMC AVQ CENTRAL POINT
Figure 6-80 (cont'd). Aerosol concentration patterns in Washington State and Oregon.
6-150
-------
The size segregated aerosol data for Bend and Central Point, OR (Figure 6-80g,h), show
diminishing concentrations compared to Medford (Figure 6-80f), where the reduction of PM10
is mainly due to the decrease of the fine particle mass during the winter season.
In Portland, OR, carbonaceous aerosol was found to account for about 50% of fine
aerosol mass (Shah et al., 1984).
6.5.6.6 Other Northwestern Locations
Dresser (1988) investigated the winter PM10 concentrations in a small ski resort town,
Telluride, CO, and found that the street dirt and sand are major contributors, particularly
during the dry post snow period. Wintertime source apportionment attributed to 45% of the
PM10 mass to residential wood combustion in San Jose, CA (Chow et al., 1995a).
6.5.7 Subregional Aerosol Pattern in Southern California
The southern California region has two subregions, the San Joaquin Valley and the
Los Angeles-South Coast Air Basin, discussed separately in sections below.
6.5.7.1 San Joaquin Basin
The wide air basin between the coastal mountain ranges of California to the west and the
Sierra Nevada Mountains to the east shows reasonably uniform PM10 concentrations as
indicated on the map (Figure 6-8la). There is evidence of PM10 concentration reduction but
the trend is not conclusive (Figure 6-8 Ib). The seasonal modulation amplitude over the San
Joaquin Valley (Figure 6-81c) is about factor of 2.5 between the low spring concentration
30 to 35 Mg/m3, and high fall concentration (60 to 70 //g/m3). The unique feature of this
seasonality is the fall peak which differs from the summer peak in the eastern United States
and winter peak over the mountainous northwestern states.
The AIRS database contains valuable size segregated fine and coarse particle concentration
data within the San Joaquin Valley, as shown in Figure 6-82 for Fresno, Madera, Visalia, and
Bakersfield, CA. These monitoring sites show virtually identical concentration patterns for fine
and coarse mass. Both coarse and fine particles are important contributors to the San Joaquin
Valley PM10 aerosol. However, their respective prevalence is phase shifted. Fine particles are
6-151
-------
100
80
80
70
40
20
10
PM10 Cone. Trend - San Joaquin Valley
EPA AIRS ditibMQ
(b)
Seasonal PM Pattern - San Joaquin Valley
EPA AIRB DotablM
100
to
BO
PM10 Station Month! : 1335
. PM2.5 Station Month* : 123
PMC Station Months : 123
10
?8BB 19(t 1«<0 1»1 1992 1883 1894
•A- AVB for ill >tt*> •& Avg tor Irond (Ho*
-H Avg + std. Dov. -9- Avg - Std. Dov.
1886 Fob Mar Apr May Jun Jul Aug Sop Oet Nov Doe
•A-PM10 -B-PM2.5 -HPMCoorao
Figure 6-81. San Joaquin Valley: aerosol concentration map, trends, and seasonal
pattern.
6-152
-------
100
ao
70
•o
S
a.
so
40
30
20
10
(a)
1985 Mar May Jul Sep Nov
-*-. PM10 AVG FRESNO
-B-. PM2.5 AVG FRESNO
-•--PMC AVG FRESNO
100
to
so
70
5
Q.
SO
40
30
20
10
(C)
1985 Mar May Jul Sep Nov
-*- • PM10 AVG VISALIA
-B-« PM2.5 AVG VISALIA
~*~ • PMC AVG VISALIA
100
90
SO
70
eo
so
40
30
20
10
(b)
1985 Mar May Jul Sep Nov
A « PM10 AVQ MADERA
-B-- PM2.S AVQ MADERA
-+-- PMC AVG MADERA
100
•0
BO
70
eo
so
40
30
20
10
1985 Mar May Jul Sep Nov
-&- - PM10 AVQ BAKERSFIELD
-B- - PM2.S AVQ BAKERSFIELD
H-« PMC AVG BAKERSFIELD
Figure 6-82. Fine, coarse, and PM10 seasonal patterns in the San Joaquin Valley.
6-153
-------
most important during the November through February winter season, while coarse particles
prevail during April through September. In November, both coarse and fine particles contribute
to the seasonal peak of PM10. During March through May, neither fine or coarse particles are
abundant and the PM10 concentration is lowest during the spring season.
The temporal dynamics of the emissions, ventilation and aerosol formation in the San
Joaquin Valley has been the subject of detailed aerosol monitoring, and source apportionment
studies.
The aerosol composition at nonurban sites (Chow et al., 1995b) provides further
characteristics of the central California aerosol pattern (Figure 6-82). A PM10 aerosol study was
carried out at six sites in California's San Joaquin Valley from 14 June 1988 to 9 June 1989, as
part of the 1988 to 1989 Valley Air Quality Study (VAQS). Concentrations of PM10 and
PM2 5 mass, organic and elemental carbon, nitrate, sulfate, ammonium, and elements were
determined in 24-h aerosol samples collected at three urban (Stockton, Fresno, Bakersfield)
and three non-urban (Crows Landing, Fellows, Kern Wildlife Refuge) locations (Chow et al.,
1993a). The VAQS data indicate the federal 24-h PM10 standard of 150 ^g/m3 was exceeded
at four out of the six sites and for reasons which differ by season and by spatial region of
influence. The annual average source contributions to PM10 at Bakersfield, the site with the
highest annual average, were 54% from primary geological material, 15% from secondary
ammonium nitrate, 10 % from primary motor vehicle exhaust, 8% from primary
construction, the remaining 4% is unexplained. The results of the source apportionment at all
sites show that geological contributions dominate in summer and fall months, while secondary
ammonium nitrate contributions derived from direct emissions of ammonia and oxides of
nitrogen from agricultural activities and engine exhaust are largest during winter months.
(Chowetal., 1992b).
6.5.7.2 Los Angeles-South Coast Air Basin-Southeastern Desert Air Basin
The Los Angeles basin is confined by the San Gabriel Mountains which limit the
ventilation during westerly winds. Intensive emissions from automotive and industrial sources
produce the Los Angeles smog with numerous secondary photochemical reaction products
from primary emissions. The map of the Los Angeles subregion shows (Figure 6-83a) the
6-154
-------
1988 1989 1990 1991 1992 1993
1985 Mar May Jul Sep Nov
Figure 6-83. Los Angeles: (a) aerosol concentration map, (b) trends, and (c) seasonal
pattern.
magnitude of PM10 concentrations for individual monitoring stations. Isopleths of PM10
concentration for 1992 are consistent with these results showing the highest PM10
concentrations are measured in the center of the LA basin with the lower concentration of
PM10 near the ocean and out in the desert and the mountains (Hoggan et al., 1993).
There has been a substantial reduction of subregion average PM10 concentration from
1988 to 1993 from 54 /zg/m3 down to 38 ^g/m3 (Figure 6-83b), a reduction of 30%. The
seasonality of the basin averaged PM10 concentration shows a 50% amplitude, with the peak
concentration (60 //g/m3) during October and the lowest values (40 //g/m3) during January
through March (Figure 6-83c). Hence, this fall peaked seasonality is similar to the fall peak over
the San Joaquin Valley.
6-155
-------
The PM10 air quality in the California South Coast Air Basin (CSCAB) and to a limited
extent in the Southeastern Desert Air Basin have been analyzed for the 1985 to 1992 period
(Hoggan et al., 1993). Although a larger number of monitoring stations exist in more recent
years, the analysis involved only the monitoring stations with complete data in Long Beach,
Burbank, El Toro, Ontario, Rubidoux, Banning, and Indio. Measurements in downtown Los
Angeles also are used in parts of the analysis (Hoggan et al., 1993). The annual average PM10
trend line for 1985 to 1992 showed a statistical significant trend downwards with the decrease
averaging 3% per year. The sulfate and nitrate also were measured and they accounted for
about one-third of the decrease in PM10. The decreases between 1989 and 1993 for this set of
stations were smaller than for the larger group of stations (Figure 6-83b). There was a
statistically significant decrease (0.05 level of significance) at Burbank, Long Beach,
Rubidoux, and Banning. Use of both a decision tree analysis and a multiple linear regression
analysis showed that the temperature at 850 mb, a measure of mass stability, was an important
variable associated with PM10 in the CSCAB. Use of this variable suggests that the observed
decreases in annual average PM10 concentrations between 1987 and 1992 are not an artifact of
meteorology. A more detailed discussion of these analyses as related to various aspects of
meteorology is given (Hoggan et al., 1993).
The diurnal patterns of PM10 also are discussed (Hoggan et al., 1993). The Rubidoux
monitoring station showed peaks in PM10 at about the time of peak commuter traffic. The Los
Angeles monitoring station showed higher PM10 concentrations in the morning and evening
than at midday. Azusa and Long Beach monitoring stations showed broad daytime peaks.
The Indio monitoring station showed an evening peak.
The weekday to weekend mean PM10 concentrations at all monitoring stations showed
significantly lower concentrations on weekends (Hoggan et al., 1993). At the two SEDAB
stations, Indio and Banning, Saturday PM10 concentrations were slightly lower than weekdays,
but Sunday PM10 concentrations fell within the range of weekday means.
Some seasonal characteristics of the Los Angeles basin are depicted in Figure 6-84. The
monitoring sites at different parts of the basin have markedly different seasonal concentration
patterns. Hawthorne and Long Beach near the Pacific Coast and Burbank in an inland valley
have the higher PM10 concentration in late fall and early winter (Figure 6-84b,c). On the
6-156
-------
150
140
130
120
110
100
90
CO
I"
5 70
Q.
60
50
40
30
20
10
(a)
1985 Mar May Jul Sep Nov
~*~ - PM10 AVG HAWTHORNE
~&~ - PM10 AVQ RUBIDOUX
-+- - PM10 AVQ BURBANK
100
90
SO
70
co 60
e
o»
- 50
Q.
40
30
20
10
(c)
1985 Mar May Jul Sep
"*" • PM10 AVG AZUSA
~B~ - PM2.5 AVG AZUSA
-+- • PMC AVG AZUSA
Nov
100
90
70
80
50
40
30
20
10
(b)
1985 Mar May Jul Sep Nov
~&~ - PM10 AVG LONG BEACH
-B- - PM2.5 AVG LONG BEACH
~+- - PMC AVG LONG BEACH
100
80
80
70
60
50
40
30
20
10
1985 Mar
May
Jul Sep
RUBIDOUX
PM2.5 AVG RUBIDOUX
PMC AVG RUBIDOUX
Nov
Figure 6-84a,b,c,d. Fine, coarse, and PM10 seasonal patterns near Los Angeles. (Note
scale for (a) is 150 ug/m3.)
6-157
-------
other hand, Azuza and Rubidoux in the eastern part of the basin exhibits the higher PM10
concentration during the May to October 'smog season' (Hoggan et al., 1993)
(Figure 6-84b,d,e). The main causes of different seasonalities are likely to be associated with
seasonally varying meteorological, transport, and chemical transformation patterns. The role
of coarse and fine particles in the Los Angeles basin is also illustrated in Figure 6-84.
At Long Beach, near the coast (adjacent to Hawthorne), the fine particles dominate the PM10
during the November through February winter season (40 to 50 //g/m3). Coarse particles at
Long Beach are constant throughout the year at about (20 yug/m3). At Azuza and Rubidoux
fine and coarse particles contribute roughly equally to the high PM10 concentrations. Thus,
the PM10 aerosols over the smoggiest parts of the Los Angeles basin are not dominated by fine
secondary aerosols but contributed by both fine and coarse particles.
The Rubidoux site in 1985 to 1988 showed violations of the 24-h PM10 standard
approximately 12% of the tune with a large contribution from ammonium nitrate (Chow et al.,
1992c). A large group of dairies and animal husbandry operations hi the Chino area
approximately 13 km west of the Rubidoux site were identified as major ammonia emitters
(Russell and Cass, 1986). To better evaluate the immediate area, measurements were made at
the Rubidoux, Riverside-Magnolia, and Riverside sites. The results indicated that the
Rubidoux site did represent urban-scale contributions of primary motor vehicle exhaust,
secondary sulfate, and secondary nitrate. However, there also were significant
neighborhood-scale and urban-scale contributions of primary geological sources and
lime/gypsum sources contributing to the PMj0 concentration (Chow et al., 1992c).
The Los Angeles smog has been the subject of extensive spatial, temporal, size and
chemical composition studies since the 1960s (Appel et al., 1976, 1978, 1979; Hidy et al.,
1980). A number of individual studies are discussed below.
The chemical characteristics of the PM10 aerosols were measured throughout 1986
(Solomon et al., 1989). Five major aerosol components (carbonaceous material, elemental
carbon and organic carbon [measured value multiplied by 1.4 to account for O and H associated
with C], nitrate, sulfate, ammonium, and soil-related materials, as measured) accounted for over
80% of the 1986 annual average PM10 mass. In all, measured chemical components were
included from 80 to 94% of the PM10 mass was chemically identified. The nitrate and
6-158
-------
ammonium concentrations were substantially higher at the Rubidoux and Upland sites than at
other sites. Measurements made off the coast at San Nicolas Island suggest that from 28 to 44%
of the annual average concentration at individual on-land sites can be associated with a regional
background (Solomon et al., 1989).
More recently the LA aerosol characteristics during 11 summer days and 6 fall days in
1987 have been further elucidated by Southern California Air Quality Study (SCAQS) (Lawson,
1990). Several of the SCAQS studies reported are discussed below. The SCAQS study is also
discussed in Chapter 3, Section 3.4.2.3.
Nitrate, sulfate, ammonium, and organic and elemental carbon were the most abundant
species in the PM2 5 fraction during SCAQS (Chow et al., 1994a). The coarse particle fraction
was composed largely of soil-related elements (e.g., aluminum, silicon, calcium, iron) at the
inland sites and with marine-related elements (e.g., sodium, chloride) at the coastal sites.
Average concentrations for most chemical compounds were higher during the fall than during the
summer, except for sulfate which was more abundant in summer. The PM2 5 constituted one-half
to two-thirds of PM10 at all sampling sites. PM2 5 nitrate and ammonium concentrations were
negatively biased for daytime samples compared to nighttime samples, consistent with diurnal
changes in temperature and the effect of these changes on the equilibrium between particulate
ammonium nitrate and gaseous ammonia and nitric acid. (Chow et al., 1994a; Watson et al.,
1994a).
Wolff et al. (1991) measured the smog aerosol pattern during SCAQS at Claremont, CA,
and Long Beach, CA, in the eastern and western Los Angles basin, respectively. Claremont's
air quality during the summer was characterized by high concentrations of photochemically
produced pollutants including ozone, nitric acid, particulate nitrate, and particulate organic
carbon (OC). The highest concentrations of these species were experienced during the
daytime sampling period (0600 to 1800) and were associated with transport from the western
part of the basin. Long Beach's air quality during the fall was characterized by frequent
periods of air stagnation that resulted in high concentrations of primary pollutants including
PM10, OC and elemental carbon (EC) as well as particulate nitrate. Night -tune levels of most
constituents exceeded daytime levels due to poorer night-time dispersion conditions. At
Claremont, OC and nitrate compounds accounted for 52% of PM10 , while at Long Beach they
6-159
-------
accounted for 67% of PM10. On the average, there appears to be sufficient paniculate
ammonium to completely neutralize the nitrate and acidic sulfates.
In situ, time resolved analysis for aerosol organic and elemental carbon in Glendora, CA
(Turpin et al., 1990), showed strong diurnal variations with peaks occurring in the daylight
hours. Comparison of the diurnal profile of organic carbon with those of elemental carbon
provided evidence for the secondary formation of organic aerosol in the atmosphere. Turpin
et al. (1991) observed that secondary organic aerosol appears to have contributed roughly half
of the organic aerosol hi Pasadena during midday summer conditions.
Turpin and Huntzicker (1991) also found that the organic and elemental carbon
concentrations exhibit strong diurnal variations. Peak concentrations occur during the daylight
hours in the summer and at night in the fall. The maximum concentrations observed in the fall
(maximum total carbon, 88 Mg/m3) were two to three times higher than the summer maxima
(maximum total carbon, 36 /ug/m3). Measurements of elemental and organic carbon have been
carried out by Gray et al. (1986). Extensive efforts have been made by Cass and coworkers
(e.g. Rogget et al., 1993; Hildemann et al., 1991) to identify the molecular composition of the
organic component. While some tracers have been identified, only a fraction of the organic
PM has been characterized in terms of its molecular composition.
Gaseous nitric acid and fine particulate nitrate at Claremont, CA (Pierson and
Brachaczek, 1988) both showed pronounced (~ 10-fold) diurnal variations; however, coarse
particles showed little diurnal variation. The average concentrations over the September 11 to
19 study period were for HNO3, 7.1 Mg/rn3; fine NO^, 7.29 /ug/m3; and coarse NO^,
7.1 /^g/m3. Fine NO§ may have been underestimated due to volatilization during or after
sampling. This problem is discussed in Chapter 4, Section 4.2.10.1.
Careful size distribution measurements in the Los Angeles basin (John et al., 1990) shed
light on the size spectrum dynamics for ammonium, sulfate and nitrate. Three modes, two
submicron and one coarse, were sufficient to fit all of the size distributions. The smallest
mode, at 0.2±0.1 /um aerodynamic diameter, is probably a condensation mode containing gas
phase reaction products. A larger mode at 0.7±0.2 ^m is defined as a droplet mode. Most of the
inorganic particle mass was found in the droplet mode. The observed condensation and droplet
modes characterize the overall size distribution in the 0.1 to 1.0 yum range, previously described
6-160
-------
by Whitby and coworkers as a single accumulation mode (Whitby et al., 1972; Whitby, 1978).
Wall et al. (1988) also found that in September 1985 at Claremont, CA fine particle nitrate was
associated with ammonium, while coarse mode nitrate was associated with both ammonium and
sodium. Sulfate was primarily in two submicrometer modes.
A clear demonstration of the effect of relative humidity and aerosol loading on atmospheric
sulfate size distributions is given by Hering and Friedlander (1982). Days of high relative
humidity and aerosol loading correspond to high mass median diameters (0.54±0.07 yum) for the
sulfate while low relative humidity and low aerosol loadings correspond to small mass median
diameters (0.2±0.02 /um). According to their interpretation, the larger (0.54 /nm) sulfate particles
resulted from aqueous phase reactions of SO2. The finer (0.2 /mi) sulfate resulted from
homogeneous gas phase reactions leading to the nucleation of sulfuric acid particles.
McMurry and Stolzenburg (1989) provide evidence that Los Angeles smog aerosols are
externally mixed. Monodisperse ambient aerosols were often found to split into nonhygroscopic
(no water uptake) and hygroscopic portions when humidified. An average of 30% of the
particles in the 0.2 to 0.5 /mi range were nonhygroscopic. However, the proportion of particles
that were nonhygroscopic varied considerably from day to day and on occasion was 70 to 80%
of the particles. The data show that for the hydrophilic aerosol, the larger particles (0.4 to
0.5 /mi) grew more when humidified than did smaller particles (0.05 to 0.2 /mi).
Size distributions of aerosol phase aliphatic and carbonyl groups at Claremont, CA (Pickle
et al., 1990) showed maxima in the 0.12 to 0.26 /mi and the 0.5 to 1.0 /mi size functions. From
the aliphatic carbon absorbency, the ambient samples generally showed maxima in the 0.076 to
0.12 fj,m size fraction. The authors attribute the carbonyl absorbance almost entirely attributed to
products of atmospheric reactions and the aliphatic absorbencies in particles smaller than 0.12
yum to automotive emissions.
Cahill et al. (1990) found that the sulfate aerosol size at Glendora, CA, is smaller, 0.33 /mi
(MMD) during clear days compared to 0.5 /mi on smoggy days.
The size distributions of organic nitrate groups in ambient Los Angeles aerosol were
typically bimodal (Mylonas et al., 1991). During periods of high photochemical activity, the
maxima in the mass loadings were in the 0.05 to 0.075 /mi and the 0.12 to 0.26 /mi size
fractions. During periods of low-moderate ozone concentrations, the distributions were shifted to
6-161
-------
slightly larger sizes, with maxima appearing in the 0.075 to 012 fj.m and the 0.5 to 1.0 //m size
fractions. A principal component analysis of the organonitrate loadings revealed strong
correlations with ozone concentrations and with aerosol phase carbonyl loadings.
The analysis of coarse particles in Claremont, CA (Noll et al., 1990) show that the coarse
particle mass could be divided into two categories: material that was primarily of crustal origin
(Al, Ca, Fe, and Si) and material that was primarily of anthropogenic origin (Cd, Cu, Mn, Ni, Pb,
and Zn). The mass of crustal material varied between 33 and 49% of the total coarse mass, while
the mass of anthropogenic elements listed above were <1%.
The daily frequency distribution of the chemical components of the Los Angeles aerosol
measured over a 1-year period were approximately lognormal (Kao and Friedlander, 1994). For
nonreactive aerosol components, the geometric standard deviation (GSD) is nearly constant at
1.85±0.14 even for components from different source types. An apparent bimodal frequency
distribution for sulfates probably corresponds to the two differing reaction pathways by which
gas-to-particle conversion occurs. However, the bimodal sulfate distribution function was not
found at other Los Angeles sites (Kao and Friedlander, 1995). The authors suspect a relationship
between GSD and the level of complexity of the stochastic physical and chemical processes
affecting the distributions of the individual species. They also point out that the chemical
concentration of the Los Angeles aerosol that corresponded to the peak in the (nearly) lognormal
frequency distribution of the total mass is lower than he simple average chemical concentration.
A long term data base for organic and elemental carbon has been constructed (Cass et al.,
1984; Gray et al., 1984). The average elemental carbon concentrations at seven monitoring sites
in the Los Angeles area, for the 24-year period (1958 to 1982), were estimated to range from
6.4 Atg/m3 at downtown Los Angeles to 4.5 Atg/m3 at West Los Angeles. At most monitoring
sites studied, elemental carbon concentration were lower in recent years than during the late
1950s and early 1960s.
6-162
-------
6.6 CHEMICAL COMPOSITION OF PARTICULATE MATTER
AEROSOLS AT URBAN AND NONURBAN SITES
This section summarizes selected data from a number of studies for the composition of
atmospheric particles in suburban, urban, and a few rural areas for comparison purposes.
Emphasis has been placed on the Harvard six-city study and the inhalable particulate network
(1980-1981). Data for fine particle mass and elemental composition were available from these
studies. Data for sulfate, nitrate, and elemental and organic carbon content are included from
other studies to provide an overview of the chemical composition of the atmospheric aerosol in
the United States. Tables presented in Appendix 6A provide relatively detailed representations
of the properties of atmospheric particles to which U.S. populations are exposed. Unfortunately,
data this complete are generally collected only during intensive studies. The tables are meant to
provide examples of the types of information that could be collected as part of future monitoring
efforts in support of human exposure investigations.
A summary of all the aerosol sampling studies included in this compilation is given in
Tables 6A-la, 6A-lb, and 6A-lc. Sampling studies have been grouped by geographical region
roughly corresponding to the eastern, central, and western United States. Data are tabulated for
the PM2.5 (d < 2.5 urn), the coarse fraction of PM10 (2.5 um< d < 10 urn) and PM-10 (d < 10
/^m) size fractions of the ambient aerosol in Tables 6A-2a, 6A-2b, and 6A-2c. Compositional
data for all size fractions were broken down into the following major components: sulfate, as
SOJ; carbon, as organic carbon (OC), which as been multiplied by a factor of 1.4 to account
for the presence of oxidized species, and elemental carbon (EC); nitrate as NO3"; and remaining
trace elements. The NH4+, that would be required to neutralize all acidic species in the samples,
is shown as (NH4+)*. Representing sulfate as ammonium sulfate and using a factor of 1.4 to
account for the mass of organic carbon present in oxidized forms allows a firm lower limit to be
placed on the fractional mass that is not chemically identified in filter samples. Acidity is given
in units of nmoles/M3 in Tables 6A-2a and 6A-2c. The masses of the trace elements from
sodium through lead have been calculated by assuming they are in their most stable forms for
conditions at the earth's surface. Reconstructed masses calculated in this way are shown by the
entry, Sum, along with measured masses, and the ratio of the two are shown at the bottom of the
individual summaries for each size fraction. Not all compositional categories were measured in
6-163
-------
the studies for inclusion in the tables. For instance, data for characterizing the carbon or nitrate
content of the ambient aerosol are not available for many of the studies listed. Average data are
shown in graphical form in Figures 6-85a, 6-85b, and 6-85c for studies in the eastern, central,
and western United States.
As can be seen from inspection of Figure 6-85a, sulfate is the major identified component
of mass for fine particles (34.1%), followed by elemental and organic carbon (24.8%), minerals
(4.3%), and nitrate (1.1%) for studies in the eastern United States. However, this last inference is
based on only a few studies in which nitrate was measured. Pierson et al. (1980a,b, 1989)
measured nitrate as constituting only 0.8% to 1.4% of aerosol mass at Allegheny Mountain and
Laurel Hill in southwest Pennsylvania in the summers of 1977 and 1983. Presumably, the low
nitrate in these and other studies in the eastern United States is related to aerosol acidity. Coarse
particles are seen to consist mainly of mineral forming elements (51.8%) and sulfate (4.9%). Not
enough data were available to determine abundances of carbon species and nitrate in the coarse
fraction. A sizable fraction of both the fine (22.8%) and coarse (41.5%) particle mass is shown
as unknown. This unknown mass is assumed to be mainly water, either bound as water of
hydration or associated with hygroscopic particles. A small fraction of the mass, especially in
the coarse fraction, may be present as carbonates. Carbonates are difficult to quantify, in part
because of artifact forming reactions with atmospheric CO2 and acids on filters. Stable
carbonates could be identified by SEM in regions where they are known to represent a
substantial fraction of soil composition.
Fine particles sampled in the studies shown in Table 6A-1 in the central United States
(Figure 6-85b) are seen to consist mainly of sulfate (22.3%), minerals (7.6%), and elemental and
organic carbon (53.6%). The reconstructed mass percentages sum to 124.8%. This could be due
to an overestimation of the carbon content which was estimated from only a few samples
collected during winter in woodsmoke impacted areas. Coarse particles were found to consist
mainly of minerals (62.8%), sulfate (3.1%) and an unknown fraction (33.0%). No nitrate or
carbon data were available for the coarse fraction from the studies in the central United States.
While gross fine particle composition appears to be broadly similar between the eastern and
central United States on the basis of the studies shown in Tables 6 A-la, 6A-lb, and 6A-lc, the
fine particle composition is seen to be distinctly different in the western United States
6-164
-------
PM2.5 Mass Apportionment
•Minerals 4.3%
Unknown 22.8%
EC 3.9%
SOj 34.1%
OCx 1.4 20.9%
NO; 1.1% — "
-------
PM2.5 Mass Apportionment
EC 9.0% v / Minerals 7.6%
OCx1.4 44.6%
so; 22.3%
(NHJ)* 10.2%
NOj 8.1%
Reconstructed sum = 124.8%
Coarse Mass Apportionment
Unknown 33.0%
(NHJ)* 1.1%
SO° 3.1%
Minerals 62.8%
Insufficient Nitrate, OC, and EC data available
PM10 Mass Apportionment
EC 29.6%
Minerals 35.8%
OCx 1.4 5.0%
S04 3.3%
NO, 23.7% ' (NHJ)* 6.5%
Nitrate based on 2 studies; OC and EC based on 4 studies
Reconstructed sum = 103.9%
Figure 6-85b. Major constituents of particles measured at sites in the central United States,
as shown in Tables 6A-2a, 6A-2b, and 6A-2c. (NH4+)* represents the
concentration of NH4+ that would be required if all SO 4= were present as
(NH4)2SO4 and all NO3' as NH4NO3. Therefore, (NH4+)* represents an upper
limit to the true concentration of NH4+.
6-166
-------
PM2.5 Mass Apportionment
EC 14.7%
j 10.8%
OCX 1.4 38.9%
(NHJ )* 7.5%
j 15.7%
Reconstructed sum = 102.2%
Coarse Mass Apportionment
Unknown 27.0%
)* 0.8%
SO" 3.1%
Minerals 69.9%
Insufficient Nitrate, OC, and EC data available
PM10 Mass Apportionment
EC 5.1%
OCX 1.4 30.0%
Minerals 36.3%
NO-3 24.0% ' (N )* 6.7%
Reconstructed sum = 111.4%
Figure 6-85c. Major constituents of particles measured at sites in the western United States,
as shown in Tables 6A-2a, 6A-2b, and 6A-2c. (NH4+)* represents the
concentration of NH4+ that would be required if all SO4 = were present as
(NH4)2SO4 and all NO3' as NH4NO3. Therefore, (NH4+)* represents an upper
limit to the true concentration of NH4+.
6-167
-------
(Figure 6-85c). Elemental plus organic carbon species (53.6%) are the major identified
component of mass, instead of sulfate (10.8%), and minerals and nitrate account for a larger
fraction of total mass. While minerals are seen to account for most of the coarse particle mass
(69.9%), available data were insufficient to estimate the contributions of elemental and organic
carbon species to the coarse mass. Table 6A-3 shows a comparison of selected ratios of mass
components for studies conducted in each of the three broad regions of the United States.
Many of the studies listed in Table 6A-3 involved data collected at more than one site
within an airshed. Information about the variability of particle mass within an airshed can yield
information about the nature of sources of the particles. The variability of mean concentrations
measured at multiple sites within a study area is used as a measure of the intersite variability in
fine particle composition and is shown in Tables 6A-4a and 6A-4b.
6.7 ACID AEROSOLS
6.7.1 Introduction
Acid aerosols are secondary pollutants formed primarily through oxidation of sulfur
dioxide (SO2), a gas emitted by the combustion of fossil fuels. Oxidation of SO2 forms sulfate
(SO4=), the major component of acid aerosols. Sulfate is formed to a lesser extent through the
oxidation of sulfur species (H2S and CH3SCH3) from natural sources. The oxidation of SO2
occurs through a series of heterogeneous (gas-particle) or homogeneous (gas or aqueous) phase
oxidation reactions that convert SO2 to sulfuric acid (H2SO4) particles. The sulfate species are
typically expressed in terms of total SOJ, with the acidic fraction expressed in terms of titratable
H+ ([H+] + [HSO^]) and referred to as aerosol strong acidity. The chemical aspects of oxidation
of S02 and formation of aerosol strong acidity are discussed in Chapter 3, Section 3.3.1. H+ is
usually found in the fine particle size fraction (aerodynamic diameter (Dp) < 1.0 um) (Koutrakis
and Kelly, 1993; Pierson et al., 1980a, 1989). However, acidity may be found in larger particles
during periods of fog or very high relative humidity. Keeler et al. (1988) and Pierson et al.
(1989) report finding acidity in the > 2.5 /um size range when the relative humidity was close to
100%. Although recent research has shown a high correlation between SOJ and acidity, data
6-168
-------
from summertime sampling have shown that SO4 is not always a reliable predictor of H+ for
individual events at a given site (Lipfert and Wyzga, 1993).
A major determinant of the lifetime of H+ in the atmosphere is the rate of neutralization by
ammonia (NH3). Ammonia reacts with H2SO4 to form ammonium sulfate [(NH4)2SO4] and
ammonium bisulfate (NH4HSO4). The major sources of ammonia in the environment are
animals and humans (Fekete and Gyenes, 1993). The then current state-of-knowledge regarding
acid aerosols was reviewed by EPA in 1989 (U.S. Environmental Protection Agency, 1989) and
by Spengler et al, 1990. A more recent summary is given by Waldman et al. (1995).
6.7.2 Geographical Distribution
In North America, ambient concentrations of H+ tend to be regional in nature with the
highest concentrations found in the northeastern United States and southwestern Canada.
Spengler et al. (1990) have collected information on maximum values of SO4 and H+ found
across the U.S. and southern Canada. This information is shown in Table 6-5.
6.7.3 Spatial Variation (Regional-Scale)
Recent evidence has shown that meteorology and regional transport are extremely
important to acid sulfate concentrations. Elevated levels of ambient H+ were measured
simultaneously during a regional episode at multiple sites located from Tennessee to Connecticut
(Keeler et al., 1991). Lamborg et al. (1992) measured H+ concentrations to investigate the
behavior of regional and urban plumes advecting across Lake Michigan. Results suggested that
aerosol acidity is maintained over long distances (up to 100 km or more) in air masses moving
over large bodies of water. Lee et al. (1993) reported that H+ and SOJ concentrations measured
in Chicago over a year were similar to levels measured in St. Louis. In an analysis of acid sulfate
concentrations measured at Pittsburgh, State College, and Uniontown, PA, Liu et al. (1996)
reported high correlations for H+ between all three locations. The three locations are separated
by large distances (approximately 60 to 240 km) and have vastly different population densities.
It is commonly believed that the source region for most of the H+ precursors (primary inorganic
pollutant gases —SO2 and NOX) is the Ohio River Valley (Lioy et al., 1980). The conversion of
the primary gases to secondary pollutants takes place as the prevailing winds carry the precursors
6-169
-------
TABLE 6-5. MAXIMUM 804 AND H+ CONCENTRATIONS
MEASURED AT NORTH AMERICAN SITES
(H+ concentrations expressed as sulfuric acid (H2SO4)equivalents;
"SC" indicates semi-continuous measurements.)
Location
Lennox, CA
Smoky Mountains
High Point, NJ
Brookhaven, NY
Tuxedo, NY
St. Louis, MO
St. Louis, MO
Los Angeles, CA
Harriman, TN
Watertown, MA
Fairview Lake, NJ
Warren, MI
Whiteface Mt, NY
Toronto, ON, Canada
Allegheny Mt., PA
Laurel Hill, PA
Harriman, TN
St. Louis, MO
Topeka, KS
Watertown, MA
Steubenville, OH
Portage, WI
Kanawha Valley, WV
Dunville, ON, Canada
Hendersonville, TN
Livermore, CA
Morehead, KY
Monroeville, PA
Pembroke, ON, Canada
Springdale, AR
Newtown, CT
Allegheny Mt., PA
Uniontown, PA
State College, PA
Philadelphia, PA
Pittsburgh, PA
Sample Duration (h)
2-8
12
6
3
1-12
SC
SC
12
SC
SC
SC,4
24
24
8,16
7,10
7,10
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
12
12,24
12
24
6,24
Maximum
SO^g-m'3)
18
17
37
24
41
25
43
10
47
31
27
37
59
75
45
56
28
40
14
23
56
33
46
31
23
9
23
42
29
11
26
33
52
47
39
27
Concentration
H2S04(Mg-m-3)
0.1
10
18
10
9
7
34
3
18
14
12
9
14
19
31
42
14
6
3
9
18
4
22
15
11
2
14
18
14
2
8
20
39
25
9
15
Source: Spengler et al. (1990).
6-170
-------
from the source region, northeastward to the northeastern United States and southwestern
Canada. This type of northeasterly wind flow occurs on the backside (western side) of
mid-latitude anti-cyclones (high pressure systems).
Pierson et al. (1980a,b, 1989) conducted studies of atmospheric acidity on Allegheny
Mountain and Laurel Hill in southwest Pennsylvania, 80 and 100 km southeast of Pittsburgh, in
the summers of 1977 and 1983. The aerosol H+ appeared to represent the net after H2SO4
reaction with NH3(g). The resulting H+/SO4 ratio depended on SO4 concentration, approaching
that of H2SO4*at the highest SO4 concentrations. The atmospheric was acidic; the average
concentrations of HNO3 (78 nmole/m3) and aerosol H+ (205 nmole/m3), NH4+ (172 nmole/m3),
and SO4 (201 nmole/m3), and the dearth of NH3 (<15 nmole/m3), show that the proton acidity of
the air exceeded the acid-neutralizing capacity of air by a factor of >2, with one 10-hour period
averaging 263 nmole/m3 for HNO3 and 844 nmole/m3 for H+. SO2 added another 900 nmole/m3
(average) of potential H+ acidity. HNO3 and aerosol H+ episodes were concurrent, on 7-8 day
cycles, unrelated to SO2 which existed more in short-lived bursts of apparently more local origin.
NOX was sporadic like SO2. Laurel and Allegheny, separated by 35.5 km, were essentially
identical in aerosol SO4, and in aerosol H+, less so in HNO3; apparently, chemistry involving
HNO3 and aerosol H+ or SO4 was slow compared to inter-site transport times (1-2 hours). From
growth of bscat and decline of SO2, daytime rate coefficients for SO2 oxidation and SO2 dry
deposition were inferred to have been, respectively, -0.05 and ^0.1 hr"1-
HNO3 declined at night. Aerosol H+ and SO4 showed no significant diurnal variation, and
03 showed very little; these observations, together with high PAN/NOX ratios, indicate that
regional transport rather than local chemistry is governing. The O3 concentration (average
56 ppb or 2178 nmole/m3) connotes an oxidizing atmosphere conducive to acid formation.
Highest atmospheric acidity was associated with (1) slow westerly winds traversing
westward SO2 source areas, (2) local stagnation, or (3) regional transport around to the back side
of a high pressure system. Low acidity was associated with fast-moving air masses and with
winds from the northerly directions; upwind precipitation also played a moderating role in air
parcel acidity. Much of the SO2 and NOX, and ultimately of the HNO3 and aerosol H+, appeared
to originate from coal-fired power plants. An automotive contribution to the NOX and HNO3
could not be discerned.
6-171
-------
Size distributions of aerosol H+ and SO4 were alike, with MMED -0.7 //m, in the optimum
range for efficient light scattering and inefficient wet/dry removal. Thus, light scattering and
visual range degradation were attributable to the acidic SO^ aerosol. With inefficient removal of
aerosol H+, and inefficient nighttime removal of HNO3, strong acids may be capable of long-
distance transport in the lower troposphere. Water associated with the acidic aerosol was shown
to account for much of the light scattering.
6.7.4 Spatial Variation (City-Scale)
A study of acid aerosols and ammonia (Suh et al., 1992) found no significant spatial
variation of IT1" at Uniontown, Pennsylvania, a suburb of Pittsburgh. Measurements at the central
monitoring site accounted for 92% of the variability in outdoor concentrations measured at
various homes throughout the town. There was no statistical difference (p > 0.01) between
concentrations of outdoor H+ among five sites (a central site and four satellite sites) in Newtown,
Connecticut (Thompson et al., 1991). However, there were differences in peak values which
were probably related to the proximity of the sampling sites to ammonia sources. These studies
suggest that long-term averages should not substantially differ across a suburban community,
although peak values may differ significantly.
In small suburban communities outdoor concentrations of H+ are fairly uniform, suggesting
that minor differences in population density do not significantly affect outdoor H+ or NH3
concentrations (Suh et al., 1992). In urban areas, however both H+ and NH3 exhibit significant
spatial variation. Waldman et al. (1990) measured ambient concentrations of H+, NH3, and SOJ
at three locations in metropolitan Toronto. The sites, located up to 33 km apart, had significant
differences in outdoor concentrations of H+. Waldman and co-workers reported that the sites
with high NH3 measured low H+ concentrations. However, the limited number of sampling sites
did not allow for a conclusive determination of the relationship between population density,
ammonia concentrations, and concentrations of acid aerosols.
An intensive monitoring study has been conducted during the summers of 1992 and 1993
in Philadelphia (Suh et al., 1995). Twenty-four hour measurements of aerosol acidity (H+)
sulfate and NH3 were collected simultaneously at 7 sites in metropolitan Philadelphia and at
Valley Forge, 30 km northeast of the city center. The researchers reported that SOJ was evenly
6-172
-------
distributed throughout the measurement area but H+ concentrations varied spatially within
metropolitan Philadelphia. This variation was related to local NH3 concentrations and the local
population density (Figure 6-86). The amount of NH3 available to neutralize H+ increased with
population density, resulting in lower H+ concentrations in more densely populated areas. The
extent of the spatial variation in H+ concentrations did not appear to depend on the overall H+
concentration. It did, however, show a strong inverse association with local NH3 concentrations.
o
i
0.5
0.4
0.3
0.2
0.1
0.0
in-** 3
120
90
! 60
O
-------
September (Figure 6-87). Little or no seasonal variation was observed at sites with low acidity.
These findings were supported by those of Thurston et al. (1992) in which H+ concentrations
measured at Buffalo, Albany, and White Plains, NY, were found to be highest during the
summertime. Thurston and co-workers also reported that moderate concentrations of H+ could
occur during non-summer months
n
E
a>
1 90-
w
c
&
'o
<^60-
"c
0
g.30-
2
n-
0 Hendersonville, TN • Morehead. KY
SDunnville, Ontario, Canada
S Pembroke, Ontario, Canada
^Livermore, CA
n
L| h
iLi ilii
:
: ,
:
i
ii
;
||
|;|
• Penn Hills, PA
i
i
:\
i i
1 ^
!|
DNewtown, CT
DSpringdale, AR
i
,
1
1
i
1 UH ^1 Ufil
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
Month
Figure 6-87. Average monthly aerosol strong acidity for Year 1 sites of the Harvard 24-City
Study.
Source: Thompson et al. (1991).
6.7.6 Diurnal Variation
Evidence exists of a distinct diurnal pattern in outdoor H+ concentrations. Wilson et al.
(1991) examined concentration data for H+, NH3, and 804 from the Harvard 24-City Study for
evidence of diurnal variability (Figure 6-88). This investigation found a distinct diurnal pattern
for H+ concentrations and the H+/SC>4 ratio, with daytime concentrations being substantially
6-174
-------
•o
c
(D
at
3
O
CO
0)
o
E
c
9 ' '?' ' ?
a Sulfate
A Hydrogen Ion
20 40 60 80 100 120 140 160 180 200
Hours
to
TJ
c
CO
CO
E
"to
q>
o
E
c
3.2
3.0
2.8
2.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
-D-Sulfate
~*— Hydrogen Ion
0 2 4 6 8 10 12 14 16 18 20 22 24
Hour
Figure 6-88. Diurnal pattern of sulfate and hydrogen ion at Harriman, TN, weekly pattern
and daily average.
Source: Wilson etal. (1991).
6-175
-------
higher than nighttime levels. Both H+ and SO4 concentrations peaked between noon and
6:00 pm. No such diurnal variation was found for NH3. Wilson and co-workers concluded that
the diurnal variation in H+ and SOJ was probably due to atmospheric mixing. Air containing
high concentrations of H+ and SOJ mixes downward during daylight hours when the atmosphere
is unstable and well-mixed. During the night, ammonia emitted from ground-based sources
neutralizes the acid in nocturnal boundary layer, the very stable lower part of the atmosphere, but
a nocturnal inversion prevents the ammonia from reacting with the acid aerosols aloft. Then in
the morning as the nocturnal inversion dissipates, the acid aerosols mix downward again as the
process begins anew. Spengler et al. (1986a) also noted diurnal variations in sulfate and sulfuric
acid concentrations and suggested atmospheric dynamics as the cause. The diurnal variation in
SOJ has been observed by other workers and discussed in terms of atmospheric dynamics by
Wolff et al. (1979) and Wilson and Stockberger (1990).
This diurnal variation in mixing heights and concentrations does not seem to hold at
elevated sites. For example, Pierson et al. (1980a,b, 1989) found no appreciable night/day
difference in aerosol H+ (or NH4+ or SOJ), and almost no diurnal variation in O3, at two
elevated sites (Allegheny Mountain and Laurel Hill, elevations 838 and 850 m) in southwest
Pennsylvania. They contrasted this behavior with that at lower sites, and particularly with the
concurrent measurements at Deep Creek Lake (Vossler et al., 1989). The differences were
attributed to isolation from ground-based processes at the elevated sites at night.
6.7.7 Indoor and Personal Concentrations
Several studies have examined indoor concentrations of acid aerosols and personal
monitoring. Brauer et al. (1989) monitored personal exposures to particles (including acidic
sulfates) and gases in metropolitan Boston in the summer of 1988, and compared these to
measurements collected at a centrally located ambient monitor. They found that personal
concentrations of acidic aerosols and gases differed significantly from those measured at the
centrally located site. Summer and winter concentrations of acid aerosols and gaseous pollutants
also collected in Boston (Brauer et al., 1991) showed indoor/outdoor ratios of H+ to be 40-50%
of the indoor/outdoor SO4= ratio indicating neutralization of the acid by the higher indoor NH3
levels, which were reported.
6-176
-------
Indoor, outdoor, and personal acid aerosol monitoring was performed for children living in
Uniontown, Pennsylvania, during the summer of 1990 (Suh et al., 1992). The indoor, outdoor,
and personal measurements were compared to outdoor measurements collected from a centrally
located ambient monitor. Personal concentrations were lower than corresponding outdoor levels
but higher than indoor levels. Air conditioning was found to be an important predictor of indoor
H+, while NH3 was found to influence indoor and personal H+ concentrations. Similar results
were obtained in a study of the relationships between indoor/outdoor concentrations of H+ and
NH3 conducted in State College, PA, in 1991 (Suh et al., 1994).
In a study characterizing H+ concentrations at child and elderly care facilities, Liang and
Waldman (1992) measured indoor and outdoor acid aerosol concentrations. Results from this
study showed that indoor/outdoor H+ and SOJ ratios were comparable to those measured inside
residential buildings. Air conditioner use and indoor NH3 concentrations were again identified
as important determinants of indoor H+ concentrations.
6.8 NUMBER CONCENTRATION OF ULTRAFINE PARTICLES
6.8.1 Introduction
Recent work has suggested that ultrafine particles may be responsible for some of the
health effects associated with exposure to particulate matter (Chapter 11, Section 11.4). The
hypothesis for explaining a biological effect of ultrafine particles is based on the number,
composition and size of particles rather than their mass (Seaton et al., 1995). This has led to an
interest in the number concentration of ambient particles. This section examines data on particle
number concentration and the relationship between particle number and particle mass or volume.
6.8.2 Ultrafine Particle Number-Size Distribution
In the context of ambient particles, the term ultrafine particles refers to those particles with
diameters below 0.1 //m. Ultrafine aerosol size distributions from an urban site at Long Beach,
California (Karch et al., 1987), and from a background site in the Rocky Mountains, Colorado
(Kreidenwies and Brechtel, 1995) are shown in Figures 6-89 and 6-90. Both of these sets of data
were obtained by electrical mobility measurements. For the urban aerosols of Long Beach, the
6-177
-------
120,000 T
100,000"
" 80,000"
o
^*
Q 60,000"
o>
o
Z 40,000"
T>
20,000"
0.00
(a)
Long Beach, CA
•1200-2400
•1200-1300
•1400-1500
•2100-2200
0.01
Particle Diameter (^m)
0.10
(b)
Long Beach, CA
CO
E
o
*r s-
E
a.
Q. R.
Q 6
_o
T3
-•- 1200-2400
-A- 1200-1 300
-O- 1400-1 500
-0-2100-2200
2"
o-
0.00
-o—o—a—a—a—a—a i o o«-"
0.01
Particle Diameter (pm)
0.10
Figure 6-89. Aerosol number (a) and volume (b) size distributions from an urban site at
Long Beach, CA.
6-178
-------
1.200T
Rocky Mountains, CO
11/23/941304
11/23/941804
11/24/941205
0.1
Particle Diameter (urn)
0.6T
Rocky Mountains, CO
dV/dlogDp (|jm3/cm3)
0.5'
0.4'
0.3'
0.2'
•' ' -0-11/23/941304
-•-11/23/941804
-0-11/24/941205
Particle Diameter, Dp (urn)
Figure 6-90. Aerosol number (a) and volume (b) size distributions from a background site in
the Rocky Mountains, CO.
6-179
-------
number geometric mean diameter can vary from 0.012 ^m to 0.043 //m. Some of the ultrafme
distributions, such as that shown for the 1,200 to 1,300 PST time period, are bimodal. The
number concentrations were higher in the early afternoon, 1400-1500 PST, as shown in
Figure 6-91. For the background aerosols from Rocky Mountains the number geometric mean
diameter of the ultrafine aerosols was somewhat larger than for Long Beach, with geometric
mean diameters ranging from 0.047 to 0.075 fj.m for periods without urban influence. A bimodal
character for the ultrafine distribution was also observed for some measurements, as seen in
Figure 6-90.
90,000-
80,000"
E 70,000-
a.
° 60,000-
v 50,000-
CO
I 40,000"
n 30,000 ••
a.
o> 20,000-
n
1 10,000"
z
ol
12
14
16
20
22
24
18
Time of Day
Figure 6-91. Number concentrations as a function of time of day at Long Beach, CA.
The contrast between urban and background ultrafine aerosol size distribtution is
demonstrated in Figure 6-92, where a change in the wind direction brought transport from an
urban area to the background site at Rocky Mountains. Within a 2-h period, the number
6-180
-------
60,000 T
Rocky Mountains, CO
TJ
z 20,000
"D
12/25/94 1524
12/25/941550
12/25/94 1648
0.1
Particle Diameter, Dp (Mm)
3T
Rocky Mountains, CO
(b)
dV/dlogDp (jjm3/cma
2.5'
2"
1.5-
r
-0- 12/25/94 1453
-*- 12/25/94 1546
-0- 12/25/94 1653
0.5"
0.1 1
Particle Diameter, Dp (urn)
Figure 6-92. Number (a) and volume (b) size distributions at the Rocky Mountain site
showing an intrusion of urban air.
6-181
-------
concentration increased from 850 cm"3 to 19,000 cm'3, an increase of more than a factor of 20.
In contrast, the volume distribution increased by less than a factor of 5. The number geometric
mean diameter decreased from 0.052 /urn for the background aerosol to 0.024 //m for the urban
influenced aerosol. For the urban influenced size distributions, over 96% of the particle number
was measured in particles below 0.1 fj,m, while 80% of the particle volume was associated with
particles above that size.
6.8.3 Relation of Particle Number to Particle Mass
In general, the majority of airborne particle volume and mass is associated with particles
above 0.1 //m, while the highest number concentration of particles is found in particles below
0.1 /^m. This was shown for volume in Figures 6-89 to 6-92 and can be seen for mass in the
recent data collected in the Los Angeles, CA shown in Figure 6-93. As with the data of Whitby
and Sverdrup (1980), the size distributions of Figure 6-93 show data collected by several
instruments. Physical size distributions were measured with an electrical aerosol analyzer for
particles between 0.01 and 0.4 /zm, and with a laser optical particle counter for particles between
0.14 and 3 /^n. Additionally, Berner (John et al., 1989,1990) and MOUDI (Marple et al., 1991)
impactors were used to measure the mass size distribution of inorganic ion species and
carbonacous species. These data have been combined (Hering et al., 1996) to give a total mass
distribution from which the number distribution has been calculated assuming an effective
aerosol density of 1.6 g/cm3 and assuming that the water associated with the aerosol is 15% of
the measured dry particle mass (see McMurry and Stolzenburg, 1989). The optical particle
counter was calibrated with ambient particles, size classified by a differential mobility analyzer.
The ambient aerosol has a lower effective refractive index than the polystyrene latex usually used
for calibration (Hering and McMurry, 1991). No fitting was applied to match the different size
distributions in the region of overlap.
Figure 6-93 shows the average of distributions collected over six different days in the fall
of 1987 in downtown Los Angeles, as part of the Southern California Air Quality Study. Particle
number distributions emphasize the ultrafine particles, or "nuclei" mode. Volume distributions
place importance on 0.1 to 1 /urn particles which are associated with the "accumulation" mode.
For this average distribution 88% of the particle number is associated with particles below 0.1
6-182
-------
125,000
.•^
^ 100,000
o^
Q" 75,000
o
^
z 50,000
"O
25,000
0.01
0.1 1
Particle Diameter, Dp(um)
Impactor -O— OPC
EAA
Los Angeles Particle Volume and Mass Distribution
0.1 1 10
Particle Diameter, Dn(um)
Figure 6-93. Number (a), and volume and mass (b) size distributions from Los Angeles, CA,
showing comparison of three measurement techniques.
6-183
-------
fj.m, but 99% of the particle volume is from particles above that size. Both the impactor and
optical counter data indicate a weakly bimodal character for the accumulation mode aerosol.
For unimodal, log normal size distributions, the particle volume Vis simply related to the
particle number N by the relation:
V = - D 3exp -In20 \N
6 *" 2 '}
where D is the number geometric mean diameter, and ogis the geometric standard deviation.
However, because of the multimodal character of ambient aerosol size distributions, one does not
expect this simple relationship to hold in the atmosphere. The relationship between particle
number and particle volume was examined for data from the Southern California Air Quality
Study collected at Riverside, CA over 11 days in the summer of 1987, and at downtown Los
Angeles in the fall of 1987 using the methods described above. As shown in Figure 6-94,
particle number concentrations are correlated with the volume associated with particles below
0.1 fj,m, but are not correlated with the total fine particle volume. Similar results are found for
the data reported from Rocky Mountains, CO and for the data reported by Whitby and Sverdrup
(1980).
6.8.4 Conclusion
The size distribution measurements of aerosols in urban and continental background
regions indicate number geometric mean diameters which vary from 0.01 to 0.08, with the larger
values found in background regions. Particle number concentrations may vary from less than
1,000/cm3 at clean, background sites to over 100,000/cm3 in polluted urban areas. Particle
number concentrations are dominated by the ultrafine or nuclei mode aerosols. In contrast, the
volume (or mass) of fine particles is associated with particles above 0.1 jun, which are associated
with the accumulation mode identified by Whitby and coworkers (Willeke and Whitby, 1975;
Whitby and Sverdrup, 1980). Particle number concentrations are correlated with the volume of
particles below 0.1 //m. The number concentration of ultrafine particles results from a balance
between formation and removal. The rate of removal by coagulation with accumulation mode
6-184
-------
760,000-
740,000-
•T 720,000-
I
f 100,000-
o>
•Q
| 80,000"
| 60,000-
'•5
0. 40,000
20,000
0
0.(
- , \ m
O
'..-
•**
' &B$±*
A
* \ \ \ \
30 2.00 4.00 6.00 8.00
Volume < 0.1 urn (um3/cm3)
160,000-
140,000-
^120,000-
i: 7 00, 000-
| 80,000-
•§ 60,000-
'•5
a 40,ooo-
20,000'
(
\(t» '
0
•
• •
'.
• •
• • •
J • • ••
1 o tf •
• •
1 '° "o« o D
i sffr * i
? 50 100 150 200
• Los Angeles
O Riverside
A Whitby Background
0 Whitby Urban
A Rocky Mountains
• Los Angeles
D Riverside
A Whitby Background
0 Whitby Urban
A Rocky Mountains
Volume < 2.5um (um3/cm3)
Figure 6-94. Relationship between particle number and particle volume ([a] volume <0.1 and
[b]<2.5,
6-185
-------
particles will increase as the number (and mass and volume) of accumulation mode particles
increases. Therefore, a correlation between number and accumulation mode volume or mass on
a short term (e.g., hourly basis), would not be anticipated. However, as suggested by the
differences in particle number concentrations from 850 cm'3 at a remote site in the Rocky
Mountains, to 19,000 cm"3 in air transported from an urban area, to in excess of 105 cm"3 in
polluted urban areas, a correlation, between the total number concentration and the total fine
article mass or volume, might be expected if comparisons were made over longer periods, e.g.
days. However, no such studies have been done.
6.9 AMBIENT CONCENTRATIONS OF ULTRAFINE METALS
6.9.1 Introduction
Nucleation theory (Seinfeld, 1986) indicates that ultrafine particles will consist of materials
that have very low vapor pressure but which will, at some time, exist in significant vapor
concentrations. This could be the result of rapid formation of a condensible vapor from chemical
conversion of a gas or the formation of a vapor at relatively high concentrations during
combustion. Very small particles, because of their high curvature, have a higher vapor pressure
than larger particles. This is known as the Kelvin effect and becomes increasingly important as
the particle size decreases below 0.1 /^m in diameter. The critical size, at which a particle will
grow instead of evaporating, depends on the saturation ratio, the ratio of the vapor pressure of the
particle, pA, to the vapor pressure over a flat surface, p^) (S = PA\PA)» me surface tension; and
the molar volume of the condensed phase. Thus, materials such a elemental carbon, formed in
flames, or metal (or metal compound) vapor, formed during combustion, are likely candidates
for ultrafine particles. Sulfuric acid can also form ultrafine particles (Weber et al., 1995) but
whether it nucleates into ultrafine particles or condenses on existing particles depends on the
balance between the formation rate of sulfuric acid and the surface area of preexisting particles
(Seinfeld, 1986).
Thus, ultrafine aerosols may be primary, formed from vapor generated during combustion,
or secondary, formed from vapor generated by chemical reactions in the atmosphere. Because of
their small size, ultrafine particles diffuse rapidly and are lost by deposition to surfaces or by
6-186
-------
growth into larger particles by coagulation. Ultrafine particles also serve as nuclei for
condensation of vapors. Thus, ultrafine particles grow rapidly by coagulation and
condensation, into the accumulation mode. For these reasons, the mass of ultrafine particles
in the ambient atmosphere is generally much smaller than that of the accumulation mode,
where removal rates of particles reach a minimum in non-cloud conditions. The result is that
in ambient conditions, the ultrafine mode is generally indistinct or absent from mass or volume
profiles of aerosol particles versus size. However, a distinct ultrafine mode below 0.1 //m
diameter has been observed in quasi-ambient samples taken close to combustion sources. In
these cases, the distinct ultrafine particle mode is referred to as the nuclei mode (Whitby,
1978).
While there is consensus that ultrafine metal particles are produced and emitted into the
atmosphere, there is little information on ambient concentrations of ultrafine metals. The few
direct measurements available can be extended with some confidence using indirect methods;
i.e., from particle counting techniques that have size information but no chemical information,
or from filter collection methods that have limited size information but detailed compositional
information. Nevertheless, it is clear that more data on ultrafine metals are urgently needed to
gain confidence in the spatial and temporal concentration profiles of this key atmospheric
component.
6.9.2 Formation of Ultrafine Particles
Nucleation theory establishes that high temperature processes are generally required to
form ultrafine metallic aerosols. Such processes are usually anthropogenic, although natural
fires, volcanic eruptions, and other such events can contribute to ultrafine transition and heavy
metals in some circumstances. Table 6-6, taken from Seeker (1990), gives the vaporization
temperature of EPA-regulated metals (Federal Register, 1986) as a function of temperature,
with and without chlorine available in the combustion process.
Note the dramatic shift in temperature for several elements, including lead, for the
chlorine-rich combustion scenario. A similar process has been used to prevent lead from
coating surfaces in internal combustion engines using leaded gasoline. The process used
6-187
-------
TABLE 6-6. REGULATED METALS AND THE VOLATILITY TEMPERATURE
With No Chlorine
Metal
Chromium
Nickel
Beryllium
Silver
Barium
Thallium
Antimony
Lead
Selenium
Cadmium
Osmium
Arsenic
Mercury
Volatility
Temp. (°F)
2935
2210
1930
1660
1560
1330
1220
1160
605
417
105
90
57
Principal
Species
CrO2/CrO3
Ni(OH)2
Be(OH)2
Ag
Ba(OH)2
T1203
Sb2O3
Pb
SeO2
Cd
OsO4
As2O3
Hg
With 10% Chlorine in Waste
Volatility
Temp. (°F)
2930
1280
1930
1160
1660
280
1220
5
605
417
105
90
57
Principal
Species
CrO2/CrO3
NiCl2
Be(OH)2
AgCl
BaCl2
T1OH
Sb203
PbCl4
SeO2
Cd
OsO4
As2O3
Hg
Source: Seeker (1990).
chlorine and bromine-containing additives to form compounds such as PbBrCl which are
gaseous at combustion temperatures but form ultrafine particles after leaving the vehicle.
Numerous theoretical and laboratory studies have shown that the typical size of metals
derived from combustion is ultrafine (Friedlander, 1977; Senior and Flagan, 1982; Seeker,
1990). Analysis of particles from coal combustion by Natusch and Wallace, 1974 and Natusch
et al., 1974 showed an additional aspect. There is a tendency for the condensing metal vapors
to form relatively uniform thickness surface coatings on more refractory particles present in
the combustion effluent stream. If the particles upon which the metals coat themselves are
crustal, as in coal fly ash, this results hi a final particle whose enrichment factor compared to
crustal averages depends upon the initial size of the refractory particle—minor for large
particles, extreme for ultrafine particles (Davison et al., 1974). This result also places the
(potentially) toxic metals on the biologically-accessible surface.
6-188
-------
Thus, the presence of metals in a combustion process such as incineration of biological
and chemical wastes or treatment of contaminated soils poses a problem. Raising the
temperature of combustion high enough to completely (> 99.99%) destroy the biological and
chemical species will also enhance the volatilization of metallic components hi the feed stock,
requiring more efficient removal methods for ultrafine and accumulation mode metals.
Figure 6-95 shows the enhanced volatilization of metals as the combustion temperature is
raised from 1000 °F (540 °C) to 1800 °F (980 °C) (Seeker, 1990).
As
40
30
E
.c
o
,5 20
0)
10
1000F
Cd
Pb
1800F
Sb
Cu
Zn
Cr
Figure 6-95. Impact of treatment temperature on the enrichment of metals in the fly ash
after the thermal treatment of soils from a Superfund site.
Source: Seeker (1990).
6-189
-------
The combustion effluent can be partitioned into three components (Seeker, 1990;
Barton et al., 1990); emitted (as fly ash), captured (assuming there is an attempt to capture
fine particles), and collected in the bottom ash. Assuming no particle removal equipment is in
place on the combustion process, emitted particles will include both the "emitted" component
and most of the "captured" component. In an uncontrolled incineration facility, 96% of
mercury, 88% of cadmium, 58% of lead, and 11% of copper might by emitted into the
atmosphere. If control is attempted, the capture efficiency is only 25% for mercury, but is
better for most other metals, ranging from 86% for cadmium to 91 % for copper (Barton
et al., 1990). In addition, the chemical state of the metals in the ultrafine mode can vary from
the more toxic phases (for example, arsenite versus arsenate) as a function of combustion
conditions (Chesworth et al. 1994). Thus, we must expect that ultrafine metallic components
will be emitted from high temperature processes in both toxic and less toxic forms.
6.9.3 Techniques for Collecting and Analyzing Ultrafine Metals
Relatively little information exists on concentrations of ultrafine metal particles in
ambient air samples away from combustion sources. There are many reasons. The ultrafine
mode falls off rapidly away from the combustion source, due to the rapid migration of some
types of ultrafine particles into the accumulation mode, and increased dispersion as one moves
away from the source. Many sources of ultrafine metals use tall exhaust stacks, which
enhances dispersion. The largest of the ultrafine particles can overlap the smallest particles of
the much more abundant accumulation mode, roughly 0.2 to 0.7 //m aerodynamic diameter.
Particles must be size-separated using a device with a sharp cut point, ususally a multistage
physical impactor, that entails problems in particle collection and analysis. Since ultrafine
particles may be hard and dry, adhesive coatings are essential in order to avoid particle bounce
in the impactors. Particle bounce typically translates coarser particles onto finer stages,
contaminating the ultrafine particles with the enormously more abundant coarser particles.
Finally, one can collect only a few monolayers of particles (at most) on the adhesive stages
before particle bounce becomes important, assuming the particles themselves are not "sticky".
A few monolayers of particles of 0.1 //m diameter amounts to only about 50 /ug/cm2 of total
deposit. If one then desires to perform minor or trace elemental analysis of the deposit, one is
6-190
-------
then faced with analytical requirements that reach picogram (10'12 gm) sensitivities. This
clearly limits analytical options.
For these reasons, much of the data available on ultrafme particles does not depend on
compositional analysis. Most information on the presence of ultrafme particles is derived
from particle counting techniques such as the Electrical Mobility Analyzer (EMA), in
situations in which the source is well known (source-enriched). This was the method
pioneered in the 1972 ACHEX studies of Los Angeles (Whitby, 1978). Particle counting
devices do not normally result in collection of ultrafme particles in a manner suitable for
compositional analysis, although some of the devices ("particle classifiers") could be modified
to provide samples for subsequent compositional analysis, if desired. The same can be argued
for devices such as diffusion batteries, but to date little has been done along this line in
ambient conditions.
Integrated samples of fine particles can be collected on substrates suitable for analysis.
While some optical information is available as one approaches the ultrafine size, most optical
techniques do not work in the ultrafine size range, which is well below the wavelength of
light. A Scanning Electron Microscope (SEM) beam can still resolve ultrafine particles
although some details are lost. The ultrafine particle distribution can then be derived by
particle counting techniques, either manual or automated, and metal composition can be found
by X-ray analysis of the single particles. The enormous gain in signal to noise ratio by
selecting individual particles offsets the loss of X-ray sensitivity (typically parts per thousand)
caused by use of the electron beams to induce the X rays. SEM and electron microprobe
analyses rarely achieve any better than one part per thousand sensitivity. However, for single
particles, this is often enough to classify them by source. Proton microprobes are, at present,
not quite able to operate in the 0.1 //m diameter region, but can perform Proton Induced X-ray
Emission (PIXE) analysis to one part per million by mass on single particles as small as
0.3 /mi (Cahill, 1980).
Impactors are designed to separate particles by aerodynamic size in such a way as to
allow compositional analysis. Yet here, too, ultrafine particles pose problems. First, most
impactors can not operate effectively below 0.1 ^m. The Stokes number for separation of a
0.1 //m diameter particle from an air stream requires either extremely high jet velocities,
6-191
-------
extremely low pressures in the gas stream, or both. While such performance can be achieved
in a physical impactor, most impactors used for ambient particle collection in the 1970's and
early 1980's did not possess this capability. For example, the very popular cyclones and
virtual impactors are ineffective below about 0.5 //m diameter. The Lundgren-type impactors
widely used in California studies (Lundgren,1967; Flocchini et al., 1976; Barone et al. 1978)
used 0.5 fj.m as the lowest cut point. Everything smaller was collected on a filter. The
Battelle-type samplers (Mercer, 1964) favored by other groups (Van Grieken et al., 1975) used
a lowest cut point of 0.25 //m diameter. Thus, while both these units generated copious
information on aerosol composition, they could not separate ultrafine aerosols from
accumulation mode aerosols.
In the mid-1980's four new impactors were developed capable of providing information
on the composition of particles near 0.1 fj.m diameter: the Low Pressure Impactor, (LPI)
(Hering et al., 1978), the Berner Low Pressure Impactor (BLPI) (Berner and Ltirzer, 1980;
Wang and John, 1988), the Davis Rotating-drum Unit for Monitoring impactor, (DRUM)
(Cahill et al., 1985; Raabe et al., 1988), and the Multiple Orifice Uniform Deposit Impactor
(MOUDI) (Marple et al., 1986; Marple et al., 1991). Battelle-type impactors were also
modified to add two size cuts below 0.25 /urn diameter. However, unlike the other four units,
no certification of performance has been published to date on its performance in the ultrafine
region. The development of reliable, clean adhesive coatings such as Apiezon™-L grease was
also a major advance in the field (Wesolowski et al., 1977; Cahill, 1979), allowing separation
of abundant soils from ultrafine size ranges even in dry, dusty conditions. For nominally
PM-10 soils, for example, a ratio of coarse to ultrafine soils was measured at 6,600:1 at a
temperatures above 30 °C and relative humidity below 20% (Cahill et al., 1985).
Performances and specifications of all these units is included in a recent review paper (Cahill
and Wakabayashi, 1993)
It is important to mention, however, that the motivation for development of this ultrafine
capability was not for extensive studies of ultrafine metals, but rather to get a more complete
picture of the accumulation mode behavior of sulfates, nitrates, organics, and other major
components of the fine aerosol mix. Thus, compositional analysis was often limited to these
species even when suitable samples had been collected. For example, many LPI samples were
6-192
-------
collected on stainless steel substrates, ideal for combustion analysis of sulfur, but unsuitable
for analysis of transition metals by X-ray techniques.
6.9.4 Observations of Very Fine Metals
Few techniques exist for collecting particles below 0.1 yum diameter for chemical
analysis. No compositional data was found for particles below 0.1 /urn diameter. However,
since ultrafine particles rapidly grow into the accumulation mode, it may be assumed that
measurements of the small-size tail of the accumulation mode provide some insight into the
composition of the ultrafine particles. Thus, the concentration of metals in the smallest
available size-cut will be examined. In order to avoid problems with definitions, particles in
the smallest size-cut, which may extend to diameters above 0.1 ^m, will be called "very fine"
and ultrafine will be reserved for particle distributions with a mass mean diameter below
0.1 /um.
6.9.4.1 Stack and Source-Enriched Aerosols
Observation of very fine metals in source or source-enriched situations lessens problems
with dilution of the sample and identification of the source. This eases both particle collection
and analysis. Figure 6-96 shows the results of such a study on a coal fired power plant
(Maenhaut et al., 1993) using the Berner Low Pressure Impactor (BLPI). The extreme
volatilization of selenium is clearly seen, which is also confirmed in aircraft sampling of
power plant stacks. Note, however, that the enrichment factor, as a function of particle size,
for both sulfur and its chemical analog selenium. More refractory elements, on the other
hand, are strongly enhanced in the very fine particles as compared to coarser modes.
The BLPI cuts are as follows: Stage number 1-0.011 ^m diameter, 2-0.021, 3-0.032,
4-0.07, 5-0.17, 6-0.30, 7-0.64, 8-1.4, 9-2.6, 10-5.5, 11-10.7 ^m. All are for particle density
2.45 g/cm3 and a temperature 120 °C, the conditions of stack sampling in the coal fired power
plant. Both these figures were normalized to Earth crustal averages. Thus, even a two order
of magnitude rise in the normalized concentration may not result in a visible "combustion
mode" since the mass of soil falls very rapidly as one moves towards very fine particles. This
is exactly what is predicted by the results of Natusch et al. (1974). Thus, source testing
6-193
-------
1,000
8 10
•o
O
Z
0.1
•e-
0.1 xSe
-»-
S
-e-
Ca
-*-
At
•+•
Si
-*-
K
1,000 a
123456789 10
Stage number
23456789 10
Stage number
Figure 6-96. Average normalized concentrations as a function of stage number, for
selenium (Se), sulfur (S), calcium (Ca), aluminum (AI), silicon (Si),
potassium (K), molybdenum (Mo), tungsten (W), nickel (Ni), and chromium
(Cr) for five BLPI samples from a coal fired power plant. The smallest size
mode is to the left, Stage number 1, 0.011 to Stage number 11, 10.7 //m
diameter. Normalization is to average crustal composition.
Source: Maenhaut et al. (1993).
confirms nucleation theory and the laboratory studies and predicts emissions of metals in the
very fine particle size range from many types of high temperature combustion sources.
6.9.4.2 Ambient Aerosols
Direct Observations
Because of the difficulties in sampling and analysis, there is relatively little information
on the concentrations of very fine metal particles in ambient air. Some quantitative
determinations of ambient concentrations have become available in the past 15 years, however,
6-194
-------
generally as a result of a number of short but intensive aerosol studies. Examples include the
extensive studies near the Grand Canyon National Park (NP) in 1979 (Macias et al., 1981) to
the Mohave Studies near the Grand Canyon NP in 1993 and the Southern is California Air
Quality Study (SCAQS) in 1985-1987 (Hering et al., 1990; Cahill et al., 1990; Cahill et al.,
1992a); studies at Shenandoah NP in 1991 (Cahill and Wakabayashi, 1993) and Mt. Rainier
NP in 1992 (Malm et al., 1994a; Cahill and Wakabayashi, 1993), and others. While almost
all of these studies used several different types of impactors with ultrafine capabilities,
relatively few were analyzed for trace metal content.
An example of very fine particles persisting in ambient air is shown in Figure 6-97 using
data collected at Grand Canyon NP 1984 (Cahill et al., 1987). The very fine particles behave
independently from the accumulation mode, in fact often showing a net anti-correlation in
concentrations of sulfur as well as dramatic differences in metals (Table 6-7). The very fine
particles in Table 6-8 can be attributed to non-ferrous metal smelting activities in the region
(Eldred et al., 1983; Small et al., 1981), which puts the nearest important sources a hundred
miles away from the sampling site. The completely different behaviors of the accumulation
and very fine particles in this arid site also show that mis-sizing by particle bounce is not
significant.
Table 6-8 presents a summary of more recent data for major EPA-regulated metals (lead,
nickel) and other metals, at Long Beach, CA, December in 1987 (Cahill et al., 1992a) and at
Shenandoah NP in 1991 (Cahill and Wakabayashi, 1993). The elements span the range from
refractory metals like nickel and vanadium to metals with low melting temperatures such as
zinc and lead. These data were all taken with the same unit, the Davis Rotating-drum Unit for
Monitoring (DRUM) using greased stages and a single orifice impactor (Cahill et al., 1985).
The last two stages were modified form the Gand Canyon configuration as a result of
theoretical and laboratory studies (Raabe et al., 1988), yielding 0.069 to 0.24 //m for Stage 8,
and 0.24 to 0.34 fj.m diameter for Stage 7.
The DRUM data were used for several reasons: the DRUM'S slowly rotating greased
stages have a documented ability to handle large amounts of coarse, dry soils without
contaminating the very fine stages (Cahill et al., 1985; Cahill and Wakabayashi, 1993), the
elemental data are of unprecedented sensitivity for ambient very fine trace metals (PIXE and
6-195
-------
400
200
fc 400
15
E 200
o
400
-------
TABLE 6-7. COMPOSITION OF THE AEROSOLS PRESENT AT GRAND CANYON
NATIONAL PARK IN THE SUMMER OF 1984 FOR THE SULFATE EPISODES OF
AUGUST 15 (ACCUMULATION MODE, STAGE 6) AND AUGUST 16
(VERY FINE PARTICLES, STAGE 8)
Elements
Sodium
Silicon and Aluminum
Sulfur
Chlorine
Potassium
Calcium
Titanium
Vanadium
Iron and Nickel
Copper
Zinc
Arsenic
Bromine
Lead
Stage 8,
0.088-0. 15 Aim
(ng/m3)
420
8
204
208
59
150
2
2
2
100
931
13
2
63
Stage 6,
0.24-0.34 /zm
(ng/m3)
10
6
392
5
3
5
4
3
2
1
2
2
2
4
Source: Cahill et al. (1987).
source. In order to obtain sulfate, multiply sulfur by 3.0. These average values, however,
obscure a great deal of structure as a function of time.
The variability as a function of size and tune is shown in Figure 6-98 for nickel,
selenium, and lead in Long Beach, CA as part of the SCAQS studies of 1987. By 1987, much
of the lead was no longer automotive, and there are significant changes hi the very fine
fraction over periods of four to twelve hours. Note the behavior of very fine metals; almost
total absence for selenium, partial absence for nickel, and constant presence for lead. Almost
all elements at almost every site show similarly complex behavior. Thus, the summary of
Table 6-8 can include only the most basic types of information on fine and very fine metals in
the atmosphere.
6-197
-------
TABLE 6-8. MEASUREMENTS OF FINE AND VERY FINE METALS
Site Name
Duration
Frequency
Dates
Particle
Aerodynamic
Diameters
Very Fine
Particles
Accumulation Mode
Long Beach, CA
6 days
6 samples/day
(11, 12/87)
Mean detectable
limit - 0.3 ng/m3
Shenandoah NP
21 days
6 samples/day
(9/91)
Mean detectable
limit - 0. 15 ng/m3
(Dae, Mm)
Element
Vanadium
Nickel
Zinc
Selenium
Lead
Sulfur8
Vanadium
Nickel
Zinc
Selenium
Lead
Sulfur3
From
To
0.069
0.24
Maximum
Values
(ng/m3)
6.6
3.4
51
MDL
199
1.2
1.2
3.8
2.7
50
From
To
0.069
0.24
2.5
1.3
17.6
MDL
71.4
200
0.24
0.58
1.42
0.14
5.38
334
From
To
0.24
0.34
Mean
6.1
4.4
46.3
0.32
47.6
250
0.67
0.48
2.16
0.11
5.49
929
From
To
0.34
0.56
Values (ng/m
10.5
7.7
From
To
0.56
1.15
3)
12.2
4.5
140.4 189.4
3.0 1.4
59.9
350
0.52
0.13
2.60
0.52
3.01
1235
69.9
500
0.30
0.03
1.92
0.35
10.87
1727
From
To
1.15
2.5
8.6
0.5
39
0.65
25.4
250
0.80
0.01
1.66
0.14
16.06
101
"Estimated from graphs.
Source: Cahill et al. (1992a, 1996a).
In addition to the limited US data, comparison data have also become available from
foreign sources such as from the Kuwaiti oil fires (Reid et al., 1994) and a study in Santiago,
Chile (Cahill et al., 1996). While the former is a unique situation, the Santiago data are
6-198
-------
'o.o-
Dec. 10
Long Beach, CA Nickel
Dec. 11
Dec. 12
Dec. 13
Selenium
Dec. 10
Dec. 11
Dec. 12
Dec. 13
Lead
0.0
Dec. 10
Dec. 11
Dec. 12
Dec. 13
Figure 6-98. Concentration, in micrograms per cubic meter, of fine and very fine metals
(nickel, selenium, and lead) in Long Beach, CA, December 10 through 13,
1987, in 4-h increments. Stage 8 is very fine, 0.069-0.24 //m; then 0.34,
0.56, 1.15, 2.5 /urn aerodynamic diameter for the upper size-cut.
Source: Cahill et al. (1992a).
6-199
-------
especially useful since leaded gasoline is still routinely used in Chile and other countries,
generating data impossible to obtain hi the United States. Table 6-9 summarizes some of these
data for a refractory element, nickel, and a volatile metal, lead. However, the full data set
includes 450 samples of four to six hours duration, each analyzed in five fine size fractions,
generally with about 20 elements found in each fraction, or approximately 40,000 individual
elemental values.
Some general observations can be made from the data; first, there is an
enormous variation in the concentration of fine and very fine metals, sometimes spanning 4 or
5 orders of magnitude in a few days. Such behavior can be modeled by plumes of particles
that sweep over the site episodically, as opposed to area or regional sources. Second, one
often finds a mixture of very fine particle or nuclei mode behavior as well as accumulation
mode behavior. However, these modes may be physically separated in time.
Lead in the United States follows a variety of very different patterns. In the
rural samples, lead tends to be bimodal, with a coarse component above 1.0 fj,m diameter and
a very fine component below 0.34 //m diameter. This can be modeled by a very fresh fine
particle mode and a coarser mode associated with resuspended soil. Urban sites, however,
both in the U.S. and in Santiago, show lead in very fine particles as well as in the
accumulation mode. Lead in resuspended soil is found in the coarse particle mode.
Other metals at Long Beach, however, lack a distinct concentration of very fine
particles all the time (selenium) or part of the time (nickel), merely possessing an accumulation
mode that closely mimics sulfates and other secondary species (Cahill et al., 1990). It is well
known that nickel and vanadium were derived from high temperature combustion sources, and
since each is highly refractory, they will occur primarily as very fine particles near the source.
Thus, the similarity between the distributions of these elements and less refractory elements
such as zinc can be understood through a rapid condensation and coagulation of the abundant
secondary species around these metals, leading to an accumulation mode distribution as the
secondary acidic species hydrate. Clearly, such processes are weaker at dry sites such as the
arid west in summer (Table 6-8). On the other hand, Shenandoah NP has a mixture of urban
and rural behavior, with occasional sharp peaks of very fine metals (nickel) superimposed on
an accumulation mode behavior (sulfur, selenium) with some coarse contribution (lead,
6-200
-------
TABLE 6-9. MEASUREMENTS OF FINE AND VERY FINE METALS
(LEAD AND NICKEL)
Site
Duration
Frequency
Dates Element
Long Beach Lead
6 days
4 samples/
day (11/87) Nickei
Shenandoah NP Lead
21 days
6 samples/
day (9/91) Nickei
Mt. Rainier NP Lead
28 days
6 samples/
day (7, 8/92) Nickei
Santiago, Chile Lead
14 days
6 samples/
day (9/93)
Kuwait Lead
14 days
4 samples/
day(6/91) Nickel
Particle
Aerodynamic
Diameters
(Dae, //m)
Mean
Maximum
Mean
Maximum
Mean
Maximum
Mean
Maximum
Mean
Maximum
Mean
Maximum
Mean
Maximum
Mean
Maximum
Mean
Maximum
Very
Fine
Particles
From
To
0.069
0.24
ng/m3
71.4
199
1.3
3.4
5.4
50
0.58
1.2
2.3
6
Always less
MDL
101
920
429.9
2580
1.5
5
Accumulation
From
To
0.24
0.34
ng/m3
47.6
95
4.4
11.4
5.5
20
0.48
1.6
6.5
15
From
To
0.34
0.56
ng/m3
59.9
129
7.7
15.0
3.0
16
0.13
0.8
2.0
21
From
To
0.56
1.15
ng/m3
69.9
164
4.5
13.4
10.9
70
0.03
1.0
3.4
14
Mode
From
To
1.15
2.5
ng/m3
25.4
58
0.5
3.7
16.1
130
0.01
0.14
6.7
29
than MDL
0.4
53
340
154.2
580
2.5
18
0.8
38
320
84.7
128
4.3
11
0.4
108
640
44.7
86
3.7
8
0.7
41
270
38.1
70
6.0
9
MDLa
0.45
0.22
0.2
0.09
0.5
0.07
8
0.35
0.22
aMDL = minimum detectable limit at 95% confidence level, in nanograms per cubic meter
Source: Cahill et al. (1992a,b, 1996a), Malm et al. (1994a), Reid et al. (1994), Cahill and Wakabayashi (1993).
6-201
-------
vanadium). Only through a detailed study of meteorology and knowledge of emission sources
can such ambient behavior be understood.
Indirect Methods
Lacking a large body of direct data on very fine metallic aerosols, there are indirect ways
to increase our knowledge of such aerosols;
1. Combustion studies have established the formation mechanism of very fine metallic
aerosols, and,
2. Considerable ambient data exist that, when combined with known combustion
processes, yield estimates for the concentration of very fine metallic aerosols by time
and locations.
3. In conditions of low ambient concentrations of particles and low humidity, very fine
particles have been shown to persist for many hours. (Cahiil et al., 1985).
Thus, the numerous observations of fine (Dp < 2.5 //m) metallic aerosols in low
humidity conditions can yield estimates of the presence of such metals in the very fine particles
and set upper limits on their concentrations. The relatively small number of actual
measurements can then serve as tests or as confirmation of our level of understanding of these
biologically important aerosols. As an example, Figure 6-99 shows concentration profiles of
sulfur, selenium, zinc, and arsenic, all of which can occur as very fine particles in the western
United States. Arsenic and zinc are annual averages, March, 1993 to February, 1994, while
the sulfur (for sulfate, times 3.0) and selenium are for summer, 1993. This was done to
exhibit the correlation of these elements, which are chemically akin, during the eastern U.S.
sulfate maximum each summer. The regional nature of the elements is very evident, as are
certain strong sub-regional sources such as the copper smelter region of Arizona and New
Mexico (arsenic).
The non-urban values shown in Figure 6-99, which are derived from the cleanest areas of
the United States, are surprisingly relevant to urban areas in the same region for some of the
species. Table 6-10 compares major and minor fine elements at Shenandoah NP, where there
are detailed measurements of particle size, and Washington, DC, where such size information
is lacking. Summer 1993 is the comparison period. Finally, two western sites are compared,
both downwind of Los Angeles; San Gorgonio Wilderness, and Grand Canyon NP.
6-202
-------
ON
fc
O
UJ
Arsenic
Oonafl Notional Park OJO7
Hatoakala Not. Pan QJ37
' ai*
Selenium
Hadaral Park 0.03
limaftliillll Not. Pw« Q.07
Vlrqirt »IOIMtt M> 0.21
Figure 6-99. Patterns of zinc, arsenic, sulfur, and selenium in the United States.
-------
TABLE 6-10. COMPARISON OF SELECTED SPECIES AT SHENANDOAH
NATIONAL PARK; WASHINGTON, DISTRICT OF COLUMBIA;
SAN GORGONIO WILDERNESS, CALIFORNIA; AND
GRAND CANYON NATIONAL PARK DURING SUMMER 1993
Shenandoah Washington, San Gorgonio Grand Canyon
Concentration (Mg/m3) National Park DC Wilderness National Park
Mass-PM10 31.00 34.90 21.70 9.37
Mass-PM25 22.50 26.50 10.30 4.50
Composition - PM2 5
Ammonium sulfate 11.80 14.60 2.55 1.09
Ammonium nitrate 0.40 1.47 4.44 0.25
Organic matter 2.84 5.42 3.88 1.22
Soil 1.41 1.55 0.86 0.63
Trace compositon (ng/m3)
Nickel 0.24 0.97 0.18 0.09
Copper 1.06 3.37 0.76 0.30
Zinc 7.93 13.90 3.72 0.63
Arsenic 0.22 0.56 0.16 0.18
Selenium 1.58 2.48 0.44 0.18
Bromine 2.14 4.18 3.67 2.11
Lead 2.17 4.48 1.36 0.51
Bio-smoke tracer 8.33 < 2.00 10.00 32.30
(non-soil fine potassium)
Optical Absortion 19.60 41.90 13.90 5.40
(b(abs), lO^m'1)
Source: Malm et al. (1994b).
Inhalation of Very Fine Metals
An extensive literature exists on the deposition of fine metals in the human lung, much of
which was derived from laboratory studies, some using radioactive tracer isotopes. But an
example of one of the few direct measurements of lung capture of ambient very fine metals is
found in Desaedeleer et al. (1977) and shown in Figure 6-100. The lower cut point is only
0.25 /urn, but even so, the increased capture efficiency of the lung for very fine and very fine
particles is clearly shown.
6-204
-------
*-*
C
g>
!5
E
^
•o
j>
n
c.
x
o
01
0.2
•2 0.1
(0
0>
o
c
o
O
0.05
0.02
A A Pb
• D Br
• Cl
6
543
Particle Size Class
0
20
40
60
80
90
92
94
96
98
c
o
'w
o
Q.
0)
O
Q>
Figure: 6-100. Apparent deposition of automotive lead aerosol in the respiratory tract of
one of the authors as determined by cascade impactor and Proton Induced
X-ray Emissions (PIXE), as a function of aerodynamic diameter for >4,4 to
2,2 to 1,1 to 0.5,0.5 to 0.25, and < 0.25 //m particles of size classes 1
through 6, respectively. Extension of the curve to particles of diameter
>2 fj.m (classes 2 and 1) is supported by separateexperiments using chalk
dust aerosol.
Source: Desaedeleer et al. (1977).
6.9.5 Conclusions
There are few data on ambient concentrations of ultrafine metals. The few direct
measurements can be extended with some confidence using indirect methods; i.e., particle
counting techniques that have size information but no chemical information, or filter collection
methods that have limited size information but detailed compositional information.
6-205
-------
Nevertheless, it is clear that more information is needed on the size and concentration and the
spatial and temporal concentration profiles of ultrafine metal particles.
Ultrafine metals are produced by a wide variety of anthropogenic activities and emitted
into the ambient air. Ambient concentrations of such metals have been seen not only in urban
settings but also at the cleanest sites in the United States. Concentrations are highly variable
as a function of site and time. While ultrafine metals have been seen to persist for many
hours, or more, in the clean, dry environment of the arid west, they appear to be rapidly
transformed into the accumulation mode in polluted urban or humid rural sites.
6.10 FINE AND COARSE PARTICULATE MATTER TRENDS
AND PATTERNS
Data for characterizing PM10 are available from a number of AIRS sites across the country.
However, data for characterizing PM2 5 and PM(10_2 5) as well as PM10 are not readily available.
As discussed in 6.3.1.7, data for PM2 5 and PM(10_2 5) have been obtained at sites in the
IMPROVE/NESCAUM networks. However, these sites are located in uninhibited areas.
Measurements suitable for determining trends and patterns of PM2 5 and PM(10_2 5) in populated
areas are available from only a few sites.
Most such data have been obtained with dichotomous samplers which measure PM2 5 (an
indicator of fine mode particles) and PM(10.2.5) (an indicator of the coarse fraction of PM10).
These two fractions may be added together to give PM10. PM2 5 is sometimes referred to as
fine and PM(10_2 5) as coarse although it is understood that PM2 5 will contain that fraction of
the coarse mode PM below 2.5 //m diameter and neither PM10 nor PM(10_2 5) will contain that
portion of the coarse mode above 10/^m diameter. Sources of PM2 5 (fine) and PM(10.2 5)
(coarse) data include EPA's Aerometric Information Retrieval System (AIRS) (AIRS, 1995),
IMPROVE (Eldred and Cahill, 1994; Cahill, 1996), The California Air Resources Board
(CARB) (CARB, 1995), the Harvard Six-Cities Data Base (Spengler et al., 1986b; Neas,
1996), and the Harvard Philadelphia Data Base (Koutrakis, 1995). The Inhalable Paniculate
Network (IPN) (IPN, 1985; Rodes and Evans, 1982) provides TSP, PM15 and PM2 5 data with
only a small amount of PM10 data.
6-206
-------
Data suitable for characterizing the daily variability in PM2 5 and PM10 are available
from only one site in southwestern Philadelphia. The National Weather Service provides daily
observations of visual range, which when suitably treated, can provide an indication of fine
mode particle concentration. The Harvard Six Cities study obtained data for PM2 5 and PM15
every other day for several years. The California Air Resources Board operates about twenty
sites that collect PM2 5 and PM(10_2 5) data with a sampling frequency of every sixth day.
Every sixth day data for a few sites may be found in AIRS. Because of the small number of
data sets for PM2 5 and either PM(10.2 5) or PM10 levels detailed intercomparisons of the
behavior of these aerosol size fractions in different regions of the United States cannot yet be
made. Data for characterizing the daily and seasonal variability of PM2 5, PM(10_2 5), and
PM10 will be discussed in 6.10.1, the longer term variability (i.e., trends) of PM2 5, PM10_2 5,
and PM10 will be discussed in 6.10.2, and the interrelations and correlations among the
various PM components and parameters will be discussed in 6.10.3.
The results presented in this section were derived from data bases available to the public.
Except for the visibility and National Park trend data, the results presented in this section were
prepared for this Criteria Document and have not yet been published elsewhere.
6.10.1 Daily and Seasonal Variability in PM2 5 and PM10
In addition to considering patterns of seasonal variations over broad geographical areas,
a great deal of information, useful for relating ambient concentrations to health effects, can be
obtained by analyzing long time series of concentration data at a single site. Collocated
24-hour PM2 5 and PM10 filter samples were collected at a site in southwestern Philadelphia
from May 1992 through April 1995 (Koutrakis, 1995). This unique data set was collected on
a nearly daily basis, thereby allowing an assessment of day-to-day variability in aerosol
properties.
The data are presented as box plots showing the lowest, lowest tenth percentile, lowest
quartile, median, highest quartile, highest tenth percentile, and highest PM2 5 values in
Figure 6-101. The four three-month averaging periods shown (March-May, June-August,
September-November, December-February) correspond to the so-called climatological or
meteorological seasons. Highest median (20.8 jig/m3) and extreme (72.6 /ig/m3)
6-207
-------
ou -
70 -
60 -
m
o> 50 -
c
o 40 -
2
"c
m _ _
o 30 -
c.
o
O
20 -
10 -
n -
•
•
n
- A
4
I
? T
Philadelphia - PBY site
PM2.5
(n = 1024)
••
_
m
A A
LI LI
1 1 =
Mar-May
Jun-Aug
Sep-Nov
Dec-Feb
Figure 6-101. Concentrations of PM2 5 measured at the PBY site in southwestern
Philadelphia. The data show the lowest, lowest tenth percentile, lowest
quartile, median (black circles), highest quartile, highest tenth percentile,
and highest PM2 5 values.
PM2 5 concentrations were found during summer, with a difference of 50 ^ig/rn3 between
them. Median PM2 5 concentrations are 14.6, 14.2, and 13.4 ^ig/m3 for the three quarterly
periods from September through May, while maximum concentrations ranged from 41 to
55 /ig/m3. Corresponding PM10 data are shown in Figure 6-102. PM10 concentrations exhibit
strong maxima during both the summer (82.4 /ig/m3) and winter (77.5 pg/m3). Maximum
PM10 concentrations during spring and fall are 54.7 and 58.5 /xg/m3. The difference between
median and maximum values was 54.4 ^ig/m3 during summer and 58.3 pig/m3 during winter.
The median PM10 concentration was 28.0 /jg/m3 in summer, and ranged between 19.2 and
20.9 /ig/m3 during the other seasons.
PM2 5 and PM10 concentrations were highly correlated (r=0.92). PM10 and PM(10.2 5)
concentrations were less highly correlated (r=0.63) and PM2 5 and PM(10_2 5) concentrations
were even less well correlated (r=0.30). The day-to-day difference in PM2 5 concentrations
was 6.8 ± 6.5 /ig/m3 and the maximum difference was 54.7 /xg/m3, while the day-to-day
6-208
-------
E
o>
o>
o
c
o
o
9O --
8O --
7O -•
60 --
5O -•
40 --
30 --
2O --
1O --
Philadelphia - PBY site
PM1O
(n = 1O24)
n
•
i
Mar-May
Jun-Aug
Sep-Nov
Dec-Feb
Figure 6-102. Concentrations of PM10 measured at the PBY site in southwestern
Philadelphia. The data show the lowest, lowest tenth percentile, lowest
quartile, median (black circles), highest quartile, highest tenth percentile,
and highest PM2 5 values.
difference in PM10 concentrations was 8.6 ± 7.5 /*g/m3 with a maximum difference of
50.4 fig/m3. The day-to-day difference in PM(10.2>5) concentrations was 3.7 ± 3.5 jig/m3 with
a maximum difference of 35.1 /*g/m3. The ratio of PM2 5 to PM10 throughput the
measurement period was 0.71 ± 0.13. The high correlation coefficient between PM2 5 and
PM10 along with the high ratio of PM2.5 to PM10 suggests that variability in PM2 5 was driving
the variability in PM10 levels.
Frequency distributions for the entire three-year PM2 5, PM(10.2 5), and PM10 data sets
are shown in Figures 6-103, 6-104, and 6-105, respectively. Concentrations predicted from
the log-normal distribution, using mean values and geometric standard deviation derived from
the data, are also shown. The small number of apparently negative PM(10_2 5) values reflects
measurement error at low concentration levels. Frequency distributions of aerosol
concentrations at several sites in the South Coast Air Basin (Kao and Friedlander, 1995) have
also been shown to be reasonably approximated by log-normal distributions.
6-209
-------
350
PM
2.5
geometric mean = 15.2 pg/m
og= 1 .69
1O 2O 3O 4O
Concentration
5O 6O
3)
7O
8O
Figure 6-103. Frequency distribution of PM25 concentrations measured at the PBY site in
southwestern Philadelphia. Log-normal distribution fit to the data shown as
solid line.
450
4OO -•
35O --
£ 300 --
o_
£ 25O --
CO
CO
"o 2OO --
o
z 1 5O --
1OO --
5O -•
n.
.Fl.
1O
6O
TO
2O 3O 4O 5O
Concentration (|jg/m 3)
Figure 6-104. Frequency distribution of coarse mode mass derived by difference between
PM10 and PM2.5. Log-normal distribution not shown because of derivative
nature of entries.
6-210
-------
25O
PM10
geometric mean = 21.4 pg/m3
og= 1.66
10 2O 30 4O 5O 60
Concentration (Mg/m3)
7O
8O
Figure 6-105. Frequency distribution of PM10 concentrations measured at the PBY site in
southwestern Philadelphia. Log-normal distribution fit to the data shown as
solid line.
In general, the highest PM2 5 values are observed when winds are from the southwest
during sunny but hazy high presure conditions. In contrast, the lowest values are found after
significant rainstorms during all seasons of the year. The highest PM2 5 values were observed
during episodes driven by high sulfate abundances and are due, at least partly, to higher
sulfate concentrations. Correlation coefficients between SO4= and PM2 5 were 0.97 during the
summer of 1993. Similar correlations between SO4= and PM2 5 were found at a site in
northeastern Philadelphia (24 km distant from the site under discussion) during the summer of
1993. In addition, PM2 5 was found to be stongly correlated (r > 0.9) between seven urban
sites and one background site (Valley Forge, PA) during the summer of 1993 (Suh et al.,
1995). The same relations were also found during the summer of 1994 at four monitoring
sites as part of a separate study (Pinto et al., 1995). The results from these studies strongly
suggest that PM2 5 and SO4= concentrations are spatially uniform throughout the Philadelphia
area, and that variablility in PM10 levels is caused largely by variability in PM2 5 (Wilson and
6-211
-------
Suh, 1996). However, not enough data are available from regional sites to define the total
areal extent of the spatial homogeneity observed in the urban concentrations.
Different conclusions could be drawn about data collected elsewhere in the United
States. PM2 5 and PM(10_2 5) data were obtained at a number of sites in California on a
sampling schedule of every six days with dichotomous samplers (California Air Resources
Board, 1995). As an example, frequency distributions of PM2 5, PM(10.2.5), and PM10
concentrations (calculated as the sum of PM2 5 and PM(10_2 5) obtained at Riverside-Rubidoux
from 1989 to 1994 are shown in Figures 6-106, 6-107, and 6-108, respectively. It can be seen
that the data cannot be satisfactorily fit by a single function, mainly as the result of the
complexity of the concentration distribution of the coarse size mode shown in Figure 6-107.
so
70-
20
4O SO 8O 1OO 12O 14O 1 SO
Concentration (pg/m3)
18O
Figure 6-106. Frequency distribution of PM2-5 concentrations measured at the Riverside-
Rubidoux site.
The data are also presented as box plots showing the lowest, lowest tenth percentile,
lowest quartile, median, highest quartile, highest tenth percentile, and highest PM2 5 values in
Figure 6-109 for four three-month averaging periods (January-March, April-June,
6-212
-------
a>
«*_
o
d
so-
7O-
6O-
5O-
4O-
3O-
20-
10-
0 20 40 60 8O 100 120 14O 160 18O
Concentration (pg/m3)
Figure 6-107. Frequency distribution of PM(10_2.5) concentrations measured at the
Riverside-Rubidoux site.
50-
40-
S. 30-
a.
re
in
o 20-
10-
—
20 40 60 80 100 120 140 160 180
Concentration (pg/m3)
Figure 108. Frequency distribution of PM10 concentrations calculated as the sum of
PM2 5 and PM(10_2-5) masses measured at the Riverside-Rubidoux site.
6-213
-------
Riverside-Rubidoux
f
o
o
140-
120-
100-
80-
60-
40-
20-
Fine
(n = 382)
r
•
i &
I II F
J-U |
>
i
•
y v Y
Jan - Mar Apr-Jun Jul -
1 st Qtr 2nd Qtr 3rd
Y
Sept Oct - Dec
Qtr 4th Qtr
Figure 6-109. Concentrations of PM2 5 measured at the Riverside-Rubidoux site. The
data show the lowest, lowest tenth percentile, lowest quartile, median
(black squares), highest quartile, highest tenth percentile, and highest
PM2>5 values.
July-September, October-December). Data for PM(10_2 5) and reconstructed PM10 are
similarly plotted in Figures 6-110 and 6-111. As can seen from these figures, variability in
concentrations within an averaging period is high. Differences between median and maximum
PM2 5 levels range from 40 /ig/m3 during the spring to 123 /ig/m3 during the winter, while
differences between median and maximum PM^o^.s) levels range from 23 /ig/m3 during
winter to 83 /ig/m3 during summer. Variations in both size fractions combine to yield
differences between median and maximum PM10 levels ranging between 83 /ig/m3 and
136 /ig/m3. Median PM2 5 levels do not show a clear seasonal cycle. However, PM(10_2 5)
concentrations show a maximum during the summer which causes a weak maximum in PM10
levels. In fact, median PM2 5 (30 /ig/m3) and PM(10_2 5) (34 /ig/m3) levels are identical during
the spring and fall quarters. The ratio of PM2 5 to PM10 mass throughout the measurement
period was 0.48 ± 0.13 and PM2 5 and PM10 levels were moderately correlated (r = 0.47).
An examination of the data from Philadelphia, PA and Riverside, CA indicates that
substantial differences exist in aerosol properties between widely separated geographic
6-214
-------
Riverside-Rubidoux
120-
_ 100-
€0
f
3: 80-
c
o
1
1 6°-
I
° 40-
20-
o-'
Coarse
(n = 382)
i
•
A
n
•
g V
V i
T
Jan - Mar Apr
T
.
LJ
V
L y
1 1
- Jun Jul - Sept Oct - Dec
1st Qtr 2nd Qtr 3rd Qtr 4th Qtr
Figure 6-110. Concentrations of PM(10.2-5) measured at the Riverside-Rubidoux site. The
data show the lowest, lowest tenth percentile, lowest quartile, median
(black squares), highest quartile, highest tenth percentile, and highest
PMcoarse values-
200
Riverside-Rubidoux
Concentration
150-
-L
o
o
i
en
o
i
PM10
(n = 382)
n.
a
tr
Jan - Mar
1st Qtr
Apr -Jun
2nd Qtr
Jul - Sept
3rd Qtr
Oct - Dec
4th Qtr
Figure 6-111. Concentrations of PM10 measured at the Riverside-Rubidoux site. The
data show the lowest, lowest tenth percentile, lowest quartile, median
(black squares), highest quartile, highest tenth percentile, and highest
PM10 values.
6-215
-------
regions. Fine mode particles make up most of the PM10 mass observed in Philadelphia and
appear to drive the daily and seasonal variability in PM10 concentrations there. Coarse mode
particles are a larger fraction of PM10 mass in Riverside and drive the seasonal variability in
PM10 seen there. The range in the seasonal variation of the ratio of PM2 5 to PM10 mass is
much smaller in Philadelphia (0.70 to 0.75) than in Riverside (0.41 to 0.57) for the four
averaging periods used. Differences between median and maximum concentrations in any size
fraction are much larger at the Riverside site than at the Philadelphia site. Many of these
differences could reflect the more sporadic nature of dust suspension at Riverside. These
considerations demonstrate the hazards in extrapolating conclusions about the nature of
variability in aerosol characteristics inferred at one location to another.
6.10.2 Fine and Coarse Participate Matter Trends and Relationships
6.10.2.1 Visual Range/Haziness
Observations of visual range, obtained by the National Weather Service and available
through the National Climatic Data Center of the National Oceanic and Atmospheric
Administration, provide one of the few truly long-term, daily records of any parameter related
to air pollution. After some manipulation, the visual range data may be used as an indicator of
fine mode particle pollution. The data reduction process and analyses of resulting trends have
been reported by Husar et al. (1994), Husar and Wilson (1993), and Husar et al. (1981).
Visual range i.e., the maximum distance at which an observer can discern the outline of
an object, is an understandable and for many purposes an apporpriate measure of the optical
environment. It has the disadvantage, however, of being inversely related to aerosol
concentration. It is usual, therefore, to convert visual range to a direct indicator of fine mode.
particle concentration. The quantitative measure of haziness is the extinction coefficient, Bext,
defined as Bext=K/visual range, where K is the Koschmieder constant. The value of K is
determined both by the threshold sensitivity of the human eye and the initial contrast of the
visible object against the horizon sky. Husar et at. (1994) use K= 1.9 in accordance with the
data by Griffmg (1980). The extinction coefficient is in units of km"1 and is proportional to
the concentration of light scattering and absorbing aerosols and gases. The radiative transfer
6-216
-------
characteristics which determine the visual range depend on time of day. Only local noon
observations are used.
Haze Trend Summary
The U.S. haze patterns and trends since 1960 are presented in 16 haze maps that
represent four tune periods and four seasons (Figure 6-112). The selected time periods are
5 year averages centered at 1960, 1970, 1980, and 1990. The quarters are calendrical,
i.e., winter is January, February, and March. View horizonally for secular trends by quarter.
View vertically for seasonal variation by decade.
The overall national view shows two large contiguous haze regions, one over the eastern
U.S. and another over the western Pacific states. The two haze regions are divided by a
low-haze territory between the Rocky Mountains and the Sierra-Cascade mountain ranges.
This general pattern is preserved over the past 30-year period. However, notable trends have
occurred over both the western and eastern haze regions.
The haziness in the western Pacific states covers all of the coastal states, with California
having the highest values. In the 1960s a large fraction of western California was very hazy,
particularly during Quarters 1 and 4. By the 1990s the magnitude of the Pacific Coast
haziness has declined markedly for all seasons.
The eastern haze region extends from the East Coast to the Rocky Mountains. The
western boundary of the eastern haze region has been markedly constant over both the seasons
and the years. In fact, haze in the mid-section of the U.S., extending from the Rocky
Mountains to the Mississippi River, has changed little over the 30-year history.
The most dynamic pattern can be observed over the eastern U.S., extending from the
Mississippi River to the East Coast. The eastern U.S. shows a significant seasonal variation.
There is also a significant trend over the past 30 years. Furthermore, these seasonal and
secular (long-term) trends are different for sub-regions within the eastern U.S., such as the
Northeast, Mid-Atlantic and Gulf States regions.
In the 1960s, the highest extinction values were recorded for the cold season (Ql, Q4),
with significantly lower values for the warm quarters (Q2, Q3). The remarkable reduction in
haziness during the cold season and the strong increase during the warm season has shifted the
6-217
-------
o\
tl>
i—»
00
Figure 6-112. United States trend maps for the 75th percentile extinction coefficient, Bcxt for winter (Ql), spring (Q2),
summer (Q3), and fall (Q4). Bext [km'1] is derived from visual range, VR, data by Bext=1.9/VR. Data
obtained during natural obstructions to vision (i.e., rain, snow, fog) were eliminated.
-------
haze peak from winter to summer. This seasonal change has been accompanied by a regional
shift in highest haze pattern. In the 1960s, the worst haziness occurred around Lake Erie and
the New York-Washington megalopolis, during the cold season. By the 1990s the area with
the worst haze had shifted southward toward Tennessee and Carolinas and occurred in the
summer season.
The decade of the 1980s shows less change than the earlier decades. However, there has
been a continued haze reduction in the Northeast, north of the Ohio and east of the Mississippi
Rivers. The southeastern U.S. as well as the Pacific states remained virtually unchanged in
the 1980s.
Regional Pattern
Trends for specific regions in the eastern U.S., and the number and location of visual
range reporting stations for each region, are shown in Figure 6-113. The trend graphs
represent the 75th percentile of Bext for the stations located within the designated region. The
trends are presented for Quarters 1 (winter) and 3 (summer) separately. The northwestern
U.S. exhibits an increase of Quarter 3 haze between 1960 and 1970, and a steady decline
between 1973 (0.22) and 1992 (0.12). In the winter quarter the haziness has steadily declined
from 0.15 to 0.10 in the 30-year period. The Mid-Atlantic region that includes the Virginias
and Carolinas shows a strong summer increase between 1960 and 1973, followed by a decline.
The winter haze was virtually unchanged over the 30-year period. The haziness over the Gulf
states increased between 1960 and 1970, and remained virtually unchanged since then. The
central Midwest including Missouri and Arkansas exhibit virtually no change during the winter
season and a slight increased in the summer (1960-1970). The upper Midwest (Figure 14) shows
an opposing trend for summer and winter. While summer haze has increased, mostly 1960-1973,
the winter haze has declined.
6.10.2.2 IMPROVE
The National Park Service-EPA monitoring network for Class I areas is designed to
monitor visibility in national parks and other designated areas. Most of these are remote.
However, data from two southeastern sites, Shenandoah National Park and the Great Smoky
6-219
-------
g
Upper Midwest
Midwest
0.28
3L O-24
J 0.20
Cs 0.16
£ 0.12
« 0.08
O
CO 0.04
o
,faW
I 1 St L
f AM*
/fu
v^
West Gulf
Southeast
Mid Atlantic
Northeast
Quarter:
1»401S601980197016801980 1(4019601990197016601990 1 MO 1»S019*0167019801980 184019S01880197019801900 1*4019501890197019(101990 184019801980197018901980
0.28
0.24
£5 0.20
to
fc, 0.16
"5< 0.12
on o.oa
0.04
n
jl s ,
*m j^ ^ { fu^
jl ^>yv^i"i ^
'
1
A t.
^ jj r\A. , » n II
rf v ^ njp
, *\
v
-------
Mountains National Park, provide useful information on the regional background of sulfate
(Eldred and Cahill, 1994; Cahill et al., 1996b). As shown in Figure 6-114, there is a distinct
increase in sulfate. This increase can be correlated with increases in SO2 emissions in the
summer from power plants in the Tennessee Valley (Cahill et al., 1996b). The increased
emissions may be related to an increase in demand for power for air conditioning. The increase
in regional background will impact urban centers along the eastern U.S. Visibility
measurements over the northeastern U.S. show an increase in haze from 1960 to 1970 in both
winter and summer. Between 1970 and 1983, there was a decrease in haze in the winter but little
change during the summer (Husar and Wilson, 1993; Husar et al., 1994). Concern has been
expressed that the indicated trends may have been impacted, or even produced, by changes in
monitoring protocols (White, 1996a,b). However, these issues have been addressed by Cahill
etal. (1996b).
6.10.2.3 Philadelphia
Philadelphia is of special interest because of the extensive monitoring conducted there
and the use of Philadelphia data in epidemiological studies. Extensive measurements of TSP
have been conducted in Philadelphia. Several data sets have been combined to give an indication
of long-term trends in Philadelphia (Figure 6-115). The TSP data set was construed from the
AIRS data base (Wyzga and Lipfert, 1996; Li and Roth, 1995). There was a steady decrease in
TSP from 1973 to 1983 with variable but slightly increasing TSP levels between 1983 and 1990.
Fine PM was estimated from the Inhalable Particle Network (Rodes and Evans, 1985)
from 1980 to 1983, from AIRS (AIRS, 1995), from 1987 to 1990, and from the Harvard Data
Base (Koutrakis, 1996) for 1993 and 1994. During the period 3/79 to 12/83, the Inhalable
Particulate Network conducted measurements in Philadelphia with dichotomous samplers. These
used 15 (j,m upper cut points except for a period at the end of the study (3/82 to 12/83) when two
co-located PM10 samplers were run at one site. The IPN data set allows construction of four
annual averages for 1980 through 1983 by averaging PM2 5 data from PMl5fPM2 5 dichotomous
samplers from the several IPN sites across Philadelphia. These are shown in Figure 6-115, along
with the one year of PM2 5 data from PM10/PM2 5 dichotomous samplers at the South Broad St.
site.
6-221
-------
Sulfate Concentration Trends
1982
1984
1986
1988
1990
1994
1983 1985 1987 1989 1991
a Shenandoah + Smoky Mountains
1993
Figure 6-114. Eastern U. S. regional background trend of sulfate indicated by seasonal
trend data from Shenadoah and Great Smoky Mountains National Parks.
A PM10/PM2 5 dichotomous sampler, run in the Philadelphia area from 1987 through
1990 allows annual averages of PM2 5 for those years to be added to Figure 6-115. Harvard
University measured PM10 and PM2 5 at the Presbyterian Home site from 5/92 to 5/92 allowing
annual averages for 93 and 94 to be added to the graph. Since PM2 5 is expected to be relatively
uniform across Philadelphia (Wilson and Suh, 1996), this data can be used to estimate a PM2 5
trend from 1979 to 1994. A downward trend is indicated.
The samplers were not at the same sites during the different time periods. Since
PM(10_2 5) does not seem to be uniform across Philadelphia (Wilson and Suh, 1996), no PM10 or
PM,10_2 5) trend could be constructed. Comparisons of PM10 and PM(|0_2 5) and PM2 5/PMi0
(Figure 6-116) for 1983 and 1993 are shown. Differences in PM(10_2 5) and the ratio of
6-222
-------
95
90
85
« 80
E
O.
CO
75
70
65
60
55
TSP and PM25Trends
IPN, AIRS, and Harvard Databases
A
30
25
20 "
"o>
15 *
>O
CN
10 Q.
1973 1975 19771 1979 1981 1983 19851 19871 1989 1991 I 1993
1974 1976 1978 1980 1982 1984 1986 1988 1990 1992 1994
Year
D TSP + PM2s.IPNAvg o PM25. IPN, SBROAD A PM2J..AIRS x PMJ5,PBY
Figure 6-115. TSP and PM2-5 trend data for the city of Philadlphia from AIRS, IPN, and
Harvard database.
PM2 s/PM10 may represent geographical differences in the coarse fraction of PM10 as well as
relative changes in PM2 5 and PM(10_2 5).
6.10.2.4 Harvard Six-Cities Study
During 1979 to 1986, the Harvard School of Public Health measured paniculate matter in
6 cities in eastern and central United States (Spengler et al., 1986b; Neas, 1996). Means and 90th
percentiles for fine, coarse, PM15, and TSP are shown in Figures 6-117 to 6-119. (Measurements
were made with dichotomous samplers with a 15 yum diameter cut point from 1979 to 1984 and
with a 10/^m diameter cut point from 1984 to 1986. The coarse fractions of PM10 and PM15
were not significantly different during the overlapping year.) In the dirtier cities, Steubenville,
St. Louis, and Harrison, there were decreases in all PM indicators, especially in the earlier years.
6-223
-------
o\
§
30
S. Broad, 1983
PM,., and PM,10.2J>
PHILADELPHIA
PBY, 1983
PM23 and PM,,.
24-Jan-83 2S-Mi
23-Fab-83
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
r-83 I 24-May-B3 I 23-Jul-83 { 21-Sap-83 ZO-Nov-83 I
24-Apr-83 23-Jun-B3 22-Aug-»3 21-Oct-83 20-Dac-83
Oat*
as a Fraction of PM ,„
(c)
24-Jan-83 I 25-Mar-83 I 24-May-B3 I 23-Jul-83 I 21-Sep-83
23-F»b-83 -' - — — • — — • ~ -- -
2O-NOV-83
24-Apr-S3 23-Jun-83 22-AuS-83 21-Oct-83 20-DOC-83
Data
O1JAN93 I OSMAR93 I O6MAY93 I O8JUL93 I O8SEP93 I OTNOV93
01FEB93 OSAPR93 O8JUN93 O8AUO93 07OCT93 08DEC93
Data
n PM2
2.
PM25 as a Fraction of PM ,
O1JAN93 I 05MAR93 > 06MAY93 I 06JUL93 I D8SEP93 \ 07NOV93 I
01FEB93 OSAPR93 08JUNB3 08AUO93 07OCT93 08OEC93
Figure 6-116
Data Data
>. Comparison of fine and coarse particle parameters in Philadelphia in 1983 and 1993: (a) PM2 5 and PM(10.2 5j at
South Broad St. site, 1983; (b) PM2 5/PM10 at South Broad St. site, 1983; (c) PM2 5 and PM(10_2 5) at
Presbyterian Home site, 1993; (d) PM2 5/PM10 at Presbyterian Home Site, 1993.
-------
80
70
BO
50
4O
30
20
1O
O
Stubenville
S.
150
140
13O
120
11°
100
90
"°
70
60
50
«
30
20
10
0
Harvard Six Cities Data
80
St. Louis
1980
1984
1981 1982 1983
Year
O PM2.5 • PM-C • PM15 • TSP
Stubenville
150
140
130
120
11°
100
90
80
70
60
50
40
30
20
10
980 1981 1982 1983 1984
Year
I PM2.5 • PM-C • PM15 • TSP
St. Louis
(d)
1979 1980 1981 1982 1983 1984 1985 1986
Year
O PM2.5 • PM-C • PM15 • TSP
I PM2.5
81 1982 1983
Year
• PM-C • PM15
1985
1986
• TSP
Figure 6-117. Trend data from the Harvard Six-Cities Study: (a) Steubenville, fine, coarse, PM15, and TSP means;
(b) Steubenville, fine, coarse, PM15, and TSP 90th percentiles; (c) St. Louis, fine, coarse, PM15, and TSP
means; (d) St. Louis, fine, coarse, PM10, and TSP 90th percentiles.
-------
a\
Harvard Six Cities Data
19BO
1981
150
14O
130
120
0>
•S 110
g 1OO
ID 90
£ 80
i «
„• 80
^ 50
o>
=L 40
30
20
10
0
1982 1983
Year
OPM2.5 » PM-C *PM15
Harriman
1984
• TSP
(b)
1979
1980
1981
1982 1983
Year
OPM2.5 • PM-C «PM15
1984
• TSP
1986
150
140
130
120
£ 110
| 100
£ 90
9
a- BO
S 7°
a. 80
«•>
£ 50
» 40
30
20
10
0
1980 1981 1982 1983
Year
OPM2.5 • PM-C *PM15
Watertown
1984
• TSP
(d)
1980
1981
1982 1983
Year
OPM2.S • PM-C »PM15
1984
• TSP
1985
1986
Figure 6-118. Trend data from the Harvard Six-Cities Study: (a) Harriman, fine, coarse, PM15, and TSP means;
(b) Harriman, fine, coarse, PM15, and TSP 90th percentiles; (c) Watertown, fine, coarse, PM15, and
TSP means; (d) Watertown, fine, coarse, PM15, and TSP 90th percentiles.
-------
"a 30
20
10
0
Portage
Harvard Six Cities Data
80
(a)
1980
1981
1984
1982 1983
Year
OPM2.5 • PM-C »PM15 • TSP
70
60
50
40
30
20
10
0
Topeka
(c)
1980
1981
1984
1982 1983
Year
OPM2.S • PM-C *PM15 »TSP
ON
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
Portage
(b)
1979
1980
1981
O PM2.5
1982 1983
Year
• PM-C • PM15
1985
1986
150
140
13O
120
•1 110
« 100
a 90
I 8°
O 70
40
30
20
10
Topeka
(d)
• TSP
1980
O PM2.5
1 1982 ' 1983
Year
• PM-C • PM1S
1985
1986
• TSP
Figure 6-119. Trend data from the Harvard Six-City Study: (a) Portage, fine, coarse, PM15, and TSP means; (b) Portage, fine,
coarse, PM15, and total TSP 90th percentiles; (c) Topeka, fine, coarse, PM15, and TSP means; (d) Topeka, fine,
coarse, PM15, and TSP 90th percentiles.
-------
There was also an apparent decrease in Topeka, one of the cleaner cities. No trend can be
discerned in Watertown or Portage. It is difficult to determine whether there was a greater trend
in fine or coarse particles.
6.10.2.5 AIRS
The AIRS data base was searched for sites with 4 or more years of fine and coarse data
(AIRS, 1995). Five such sites were found. Values for the mean and the 90th percentile are
shown in Figures 6-120 to 6-123. No significant trends are evident in PM2 5 or PM(i0_2 5) either
in the means or the 90th percentile values. PM10 and PM(i0_2 5) at the dirtier site in New York
City do appear to have decreased from 1988 to 1992 but to have increased between 1992 and
1994.
6.10.2.6 California Sites
The California Air Resources Board conducted dichotomous sample measurements, every
sixth day, beginning in 1989 at a number of California sites (CARB, 1995). Some results from 8
sites are shown in Figures 6-124 to 6-130. The means (Panel a) and 90th percentile values
(Panel b) are given for PM2 5, PM(10_2 5), and PM10. Most of the sites show slight downward
trends for PM10 and both PM2 5 and PM(10_2 5).
The California sites are of special interest because of the substantial seasonal and daily
variability. The individual every-sixth-day values are plotted for 1991 (plus 1 day in the
preceeding and following years)(Panel c). Strong seasonal and daily variation are evident.
Based on the every-sixth-day measurements, it would appear that the day-to-day variability at
the California sites is higher than in Philadelphia. Also shown is the PM2 5 fraction of PM10
(Panel d). These ratios are also show a strong seasonal variation.
6.10.3 Interrelations and Correlations
The availability of data on four PM size fractions at several sites for a number of years
makes it possible to examine relationships and correlations among PM2 5, PM(10_2.5), PM10, and
TSP. It is also possible to examine the distribution of values in the upper range and the
relationship of the fine fraction to other PM parameters. Sufficient data for these purposes are
6-228
-------
New York, NY
0\
to
to
Site 69
Annual Arithmetic Mean (ug/m3 )
Site 71
Annual Arithmetic Mean (ug/m3 )
70
60
50
40
30
20
10
°8
—
6 8
„- '
7 8
— •
8 8
H r\
^^
9 9
0 S
11 £
2 S
(a)
3 £
Dftfl 1 C
70
60
50
40
30
20
10
4 °8
NAAQ
6 8
S
7 8
D mi 4
^
8 8
n _
\
9 9
p^
0 S
^
1 S
^— — •
2 S
. . . . D
(c)
^^
^
3 £
HJIO K
90th Percentile (ug/m3)
90th Percentile (ug/m3)
100
80
60
40
20
e
^
6 8
X
7 8
^
8 8
n
^
9 S
0 9
1 9
2 9
(b)
3 £
OHO C
100
80
60
40
20
4
6 a
7 8
DM 1 r
.
X
X
8 8
\
^s
9 £
\
10 9
1 9
^
2 9
(d)
^
X
X
3 £
MO C
Figure 6-120. Trend data from AIRS: (a) New York City, Site 69, fine, coarse, and PM10 means; (b) New York City,
Site 69, fine, coarse, and PM10 90th percentiles; (c) New York City, Site 71, fine, coarse, and PM10 means;
(d) New York City, Site 71, fine, coarse, and PM10 90th percentiles.
-------
Detroit, Ml
Annual Arithmetic Mean (ug/m3 )
St. Louis,MO-IL
Annual Arithmetic Mean (ug/m3 )
70
60
50
40
30
20
10
°£
NAAC
6 8
S
7 E
DI« i r
^-^~^MM
8 E
i — *
—
9 £
^~"
0 £
\
^
1 J
2 £
... D
(a)
3 £
mi C
70
60
50
40
30
20
10
°E
NAAC
6 8
S
7 E
. DM 1
8 E
r\
—
9 £
0 £
•• ••
1 S
-
2 £
.... c
(c)
^^
3 g
51/1O C
Detroit, Ml
90th Percentile (\iglm3)
St.Louis,
90th Percentile (ug/m3)
100
80
60
40
20
«
6 E
7 8
O R4 mo c
Figure 6-121. Trend data from AIRS: (a) Detroit, fine, coarse, and PM10 means; (b) Detroit, fine, coarse, and PM10 90th
percentiles; (c) St. Louis, fine, coarse, and PM10 means; (d) St. Louis, fine, coarse, and PM10 90th percentiles.
-------
Philadelphia, PA - NJ
Annual Arithmetic Mean (pg/m3 )
ro
6O
so
4O
3O
20
10
'
B
NAAQS
6 8
-
7 8
o iv/i -i r
'
8 8
^
^^^
^~~
9 9
--
^^
O 9
*-* ^ 1*^^
^
"^\
1 9
2 9
• • • P>IWI
(a)
^ -
^^^
3 9
^? «^
4
1OO
8O
6O
40
2O
86
9Oth Percentile
(b)
87 88
PM 1 O
89 9O 91
Coarse
92 93 94
PM2.5
Figure 6-122. Trend data from AIRS: (a) Philadelphia, fine, coarse, and PM10 means;
(b) Philadelphia, fine, coarse, and PM10 90th percentiles.
1
2
3
4
5
6
7
available from several sites in California (CARB, 1995) and from Philadelphia (IPN, 1985;
AIRS, 1995; Harvard 1995). However, only the Philadelphia data allows examination of the
relationship of PM2 5 and PM10 with TSP.
6.10.3.1 Upper Range of Concentration for Various PM Size Fractions
Some information on the upper range of concentrations and relationships among the four
PM size fractions are shown in Tables 6-11 and 6-12. The maximum value; the 2nd, 3rd, 4th,
6-231
-------
Annual Arithmetic Mean (|Jg/m )
to
u>
to
100
80
60
40
20
(a)
; I J ! NAAQS
90th Percentile (pg/m )
San Jose, CA
100
90
80
70
BO
~5> so
3.
40
30
20
10
Every Sixth Day. 1991
1
0.9
0.8
0.7
2° 0.6
a.
I 0.5
8 0.4
O.3
0.2
0.1
0
(c)
01/06/91 I 03AM/91 I OS/D6/91 I 07/05/91 I 09/0*3/91 I 11/0*2/91 112/20/91
02/05/91 04/06/91 06/05/91 08 AM/91 10/03/91 12/02/91
Date
O Coarse * Fine
PMa.5 as a Fraction of PMio
01/17/90 I 01/06/91 I 01/01/92 I 01/01/93 I 01/02/94 I 01/04/95 109/30/95
07/04/90 07/05/91 O7/05/92 07/06/93 07/O1/94 07/02/95
Date
Figure 6-123. Trend data from San Jose from CARB: (a) Fine, coarse and total means; (b) Fine, coarse and total
90th percentiles; (c) Every sixth day fine and coarse mass for 1991; (d) Fine and coarse mass as a
fraction of PM10.
-------
-------
Is)
-------
Bakersfield.CA
Annual Arithmetic Mean (ug/m3)
100
90 91 92 93 94 95
110
100
go
80
70
: 80
L SO
40
30
20
10
Every Sixth Day. 1991
01/08/91 I 03/07/91 I 05/1*2/91 I 07/0*5/91 I 09/04/91 I 11/0*2/91 I 12/28/91
02/08/91 04/08/91 06/05/91 08/04/91 10/03/91 12/02/91
Date
D Coarse + Fine
1
0.9
0.8
0.7
0.8
0.5
0.4
0.3
0.2
0.1
0
PM2 5 as a Fraction of PM 10
01/04/88 I 01/0*5/90 I 01/06/911 01/01/921 01/01/93 Id 1/08/94*
07/03/89 07/04/90 07/05/91 07/07/92 07/06/93 04/08/94
Figure 6-126. Trend data from Bakersfield from CARB: (a) Fine, coarse and total means; (b) Fine, coarse and total
90th percentiles; (c) Every sixth day fine and coarse mass for 1991; (d) Fine and coarse mass as a
fraction of PM10.
-------
U)
180
160 J
140
120^
100
8 CM
60
40
20
0
Annual Arithmetic Mean (ug/m3)
Azusa, CA
100
80
60
40
20
0
8
^^
' — "•••?•.
^
«.
•- »-t*"
\
•>
""* *"*'•*.
I'X* .— ..
(a)
NAAQS
9 90 91 92 93 94 9
90th Percentile (ug/m^
(b)
89
90
• Total
91
92 93
Coarse
94 95
Fine
t
110
1OO
90
80
70
60
SO
40
30
20
10
0
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
Every Sixth Day, 1991
01/12/91 03/13/91 05/08/91 07/05/91
02/05/91 04/D6/81
08/05/91 08/04/91
Date
Coarse + Fine
PM2 5 as a Fraction of PM10
(d)
01/04/8903/38/89 07/04/90 107/05/91 IO7/05/92 I 07/06/93 lo7/01/94 dr/02/9sl
05/28/89 01/05/90 01/12/91 01/01/92 01/01/93 01/08/94 01/03/95 09/30/95
Date
Figure 6-127. Trend data from Azusa from CARB: (a) Fine, coarse and total means; (b) Fine, coarse and total
90th percentiles; (c) Every sixth day fine and coarse mass for 1991; (d) Fine and coarse mass as a
fraction of PM10.
-------
ON
Annual Arithmetic Mean (\ig/m )
100
80
60
40
20
0
: I-.
•I-
Riverside-Rubidoux, CA
(a)
89 90 91 92 93
Total Coarse
90th Percentile (wg/m3)
95
180
160
140
120
100
80
60
40
20
0
Fine
(b)
89
90
• Total
92 93
— Coarse
94 95
Fine
0.8
0.7
I o.e
•s
| 0.5
I 0.4
0.3
0.2
0.1
Every 6th Day, 1991
01/08/91 I 03/01/91 105/12/91 I 07/D5/9ll 09/D3/91I 11/0*2/91 lo 1/01/92
02/05/91 04/08/91 06/O5/91 08/10/91 10/03/91 12/02/91
Date
D Fine + Coarse
PM2 5 as a Fraction of PM 10
(d)
01/22/89 I 02/17/90 I 03/13/91 I 04/30/92 I 05/25/93 I 06/01/94 I 05/27/95
08/02/89 08/21/90 10/15/61 11/26/92 11/27/93 11/28/94
Date
Figure 6-128. Trend data from Riverside-Rubidoux from CARB: (a) Fine, coarse and total means; (b) Fine, coarse and
total 90th percentiles; (c) Every sixth day fine and coarse mass for 1991; (d) Fine and coarse mass as a
fraction of PM10.
-------
U)
oo
Annual Arithmetic Mean (pg/m3)
100
80
60
40
20
0
e
^—-^
- —
•
(a)
NAAQS
I9 90 91 92 93 94 9
Lone Pine, CA
4O|—
90th Percentile (kig/m 3)
180
160
140
120
100
80
60
40
ZO
0 '
(b)
89 90 91 92 93 94 9
25
20
1S
10
5
Every Sixth Day, 1991
(C)
01/06/91 I 03/01/91 I 05/06/91 b7/03/9ll 09/03/81 I 11/02/91 112/14/91
02/05/91 04/06/91 06/29/11 08/04/91 10/03/91 12/02/91
Date
a Coarse + Fine
0.9
0.8
0.7
s o.e
i 0.5
I 0.4
* 0.3
0.2
0.1
PM2 5 as a Fraction of PM10
01/16/80 I 01/05/80 I 01/08/81 I 01/31/82 I 01/01/83 b 1/02/94 101/08/85
07/03/89 07/04/90 07/05/91 07/05/92 07/08/93 07/01/94
Date
Figure 6-129. Trend data from Lone Pine from CARB: (a) Fine, coarse and total means; (b) Fine, coarse and total
90th percentiles; (c) Every sixth day fine and coarse mass for 1991; (d) Fine and coarse mass as a
fraction of PM10.
-------
Annual Arithmetic Mean (|jg/m3)
El Centre, CA
89 90 91 92 93 94 95
Total Coarse Fine
90th Percentile (M9/m3)
90 91 92 93 94 95
Total Coarse Fine
120
110
100
90
80
70
«
E 60
Ol
* 50
40
30
20
0.9
0.8
0.7
0.6
0.5
"
0.3
0.2
0.1
Every Sixth Day, 1991
01/06/91 I 03/01/91 I 05/08/91 I 07/11/91 I 09/06/91 I 11/02/91 M2/14/91
02/05/91 04/08/91 06/05/91 06/O4/91 1O/O3/91 12/O2/B1
Date
D Coarse + Fine
PM2 s as a Fraction of PM10
(d)
01/04/69|o9/19/6B|oS/2l3/9oloi/3'iO/9l|lO/03/91l06/23/92|o3fO2/93|lO/26/93l07/Oi'7/94|o3/22/95
05/22/89 01/17/90 09/14/90 06/05/91 02/18/92 11/02/92 06/30/93 03/03/94 11/16/94
Date
Figure 6-130. Trend data from El Centro from CARB: (a) Fine, coarse and total means; (b) Fine, coarse and total
90th percentiles; (c) Every sixth day fine and coarse mass for 1991; (d) Fine and coarse mass as a
fraction of PM10.
-------
TABLE 6-11. MAXIMUM VALUE; 2ND, 3RD, 4TH, AND 5TH HIGHEST VALUES;
98TH AND 95TH PERCENTILE VALUES; 50TH PERCENTILE VALUE (MEDIAN); A,
THE DIFFERENCE BETWEEN THE MEDIAN AND THE MAXIMUM VALUES AND
#, THE NUMBER OF MEASUREMENTS AVAILABLE FROM EIGHT CALIFORNIA
AIR RESOURCES BOARD SITES:
(a) PMj* (b) PMno.2.Si,and(c)PM10
PM25
SITE
Riverside
Azusa
Bakersfield
Visalia
Stockton
San Jose
El Centre
Lone Pine
Max
142
98
447
140
94
105
73
29
2nd
130
95
147
121
92
88
62
23
3rd
129
88
119
105
91
86
52
22
4th
122
88
100
91
75
69
49
19
5th
121
87
98
91
75
66
47
18
98%
114
84
93
82
70
59
39
17
95%
77
60
77
69
55
44
26
13
50%
29
23
16
15
11
9
11
6
A
113
75
431
125
83
96
62
23
#
368
371
296
389
381
341
392
322
PM(10-2.5)
Riverside
Azusa
Bakersfield
Visalia
Stockton
San Jose
El Centre
Lone Pine
123
108
320
86
66
55
324
107
114
98
104
75
57
45
176
105
87
71
99
74
57
41
160
84
86
62
98
73
56
39
150
71
86
61
90
70
56
32
132
67
76
57
76
64
54
64
108
42
68
50
61
51
41
51
63
26
34
24
27
21
16
11
27
10
89
84
293
65
50
44
297
97
368
371
296
389
381
341
392
322
PM10
Riverside
Azusa
Bakersfield
Visalia
Stockton
San Jose
El Centre
Lone Pine
194
203
766
187
126
151
347
122
189
152
218
164
119
109
228
120
189
139
183
138
112
102
222
101
182
139
163
137
110
87
167
93
182
135
144
130
102
85
158
76
178
127
135
109
98
76
130
54
130
99
120
98
82
61
90
36
68
50
48
43
30
22
39
16
126
153
718
144
96
129
308
106
368
371
296
389
381
341
392
322
6-240
-------
TABLE 6-12. MAXIMUM VALUE; 2ND, 3RD, 4TH, AND 5TH HIGHEST
VALUES; 98TH AND 95TH PERCENTILE VALUES; 50TH PERCENTILE
VALUE (MEDIAN); A, THE DIFFERENCE BETWEEN THE MEDIAN AND
THE MAXIMUM VALUES AND #, THE NUMBER OF MEASUREMENTS
AVAILABLE FOR STIES IN PHILADELPHIA FROM 1979 TO 1995:
(a) PM2 s (b) PM,1ft.^, and (c) PM1fl,AND (d) TSP
Philadelphia
Site
IPN
Average
IPN
S. Broad
AIRS
Harvard
PBY
Dates
3/79
12/83
3/82
12/83
1/87
12/90
5/92
5/59
Max
98
54
55
73
PM25
2nd
94
54
55
72
3rd
74
52
47
56
4th
65
50
46
53
5th
65
50
45
53
98%
61
53
46
43
95%
50
50
43
36
50%
21
22
18
15
A
74
32
37
58
#
366
91
219
1014
PMnn-9 «
IPN
Average
IPN
S. Broad
AIRS
Harvard
PBY
3/79
12/83
3/82
12/83
1/87
12/90
5/92
5/59
NA
28
39
40
NA
25
39
28
NA
20
38
27
NA
19
37
25
NA
17
30
24
NA
25
37
18
NA
18
25
15
NA
9
12
6
NA
19
27
34
0
91
219
970
PM,n
IPN
Average
IPN
S. Broad
AIRS
Harvard
PBY
3/79
12/83
3/82
12/83
1/87
12/90
5/92
5/59
NA
71
86
82
NA
66
83
78
NA
66
82
72
NA
65
79
64
NA
64
73
64
NA
67
79
54
NA
64
60
48
NA
30
31
22
NA
41
55
60
0
91
219
1025
TSP
IPN
Average
IPN
S. Broad
AIRS
Harvard
PBY
3/79
12/83
3/82
12/83
1/87
12/90
5/92
5/59
196
116
131
NA
150
107
124
NA
148
105
116
NA
140
101
116
NA
138
99
112
NA
129
109
116
NA
114
100
104
NA
64
61
56
NA
132
55
75
NA
366
91
219
0
6-241
-------
and 5th highest values; the 98th and 95th percentile values; the 50th percentile (median value)
and the difference between the median and the maximum value are given for the measurement
period available at each site. The maximum PM2 5, PM(10-2.5)» and PM10 levels were
substantially higher at all the California sites, including the site at Lone Pine (estimated
1980 population, 1800), than at the Philadelphia sites. Differences between maximum and
median levels are also larger at the California sites. The causes for the extremely high values
observed at the Bakersfield site are not known. Data on the upper ranges of TSP are shown
for Philadelphia sites as available.
6.10.3.2 Relationships Between PM2 5; PM(10_2 5), PM10, and TSP in Philadelphia
Epidemiologists have made extensive use of a long-term TSP data set from Philadelphia
(Chapter 12; Wyzga and Lipfert, 1996; Li and Roth, 1995) to investigate the statistical
relationships between TSP and mortality. It is possible, however, that PM2 5 or PM10, instead
of TSP, may be the causal agent and that TSP may serve as an indicator for PM2 5 or PM10.
PM indicators for Philadelphia, other than TSP, have not been available until recently.
Therefore, an examination of relationships between TSP, PM2 5, and PM10 in the Philadelphia
area may provide data that will be useful in interpreting the epidemiological results obtained in
Philadelphia with TSP. Such relationships are displayed in a series of Figures (6-131 to
6-135) that show: (Panel a) TSP plotted versus PMX (where PMX is either PM2 5 or PM10)
(Panel b) the distribution of values of PMX/TSP, (Panel c) PMX/TSP plotted versus PMX, and
(Panel d) PM/TSP plotted versus TSP.
It would appear from Figures 6-131 to 6-135 that there is some relationship between PMX
and TSP and that the relationship improves at higher values of TSP. The PMX/TSP ratio does not
appear to vary significantly with PMX. However, the ratio does appear to increase with TSP
until a certain level of TSP is reached and then levels off. These visual observations are
quantified by comparison of the PMX/TSP ratios at various levels and statistical regressions of
PMX with various TSP fractions shown in Table 6-13.
6-242
-------
Frequency Distribution of PM^./TSP
to
PHILADELPHIA, IPN, 3/79 to 12/83
Comparison of TSP and PM2i
40 60 80 100 120 140 160 180 200
TSP. (jg/m*
0.15 0.25 I 0.35 I 0.45 I 0.55 0.65 0.75 I
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
PM2S/TSP
00
.o
0.7
0.6
0.0.5
CO
t
S0.4
o.
0.3
0.2
0.1
Q
uunipciii»uii ui riYi25 MMU ri«25M or n „ comparison OT i or ana KM25/I SK
n
-
D
n a D
D D a
D D D a Da a
on Da EJ o o D
^ ODD%^|^*DD^DD "
B 2qfi'r»!£B*_n™n Q
~
-
&5ag> a a
a
a
i i i i i i i i i i
u.o
0.7
0.6
a. °'5
CO
S 0-4
a.
0.3
0.2
0.1
n
n
-
D
n n
a o D
D DDnaDna
no DD aa D o D
- 0° DD^^D^^ ° "S» 1 D
'"b a^asiuSr ^SL j=pS raP D DD
DaI"^n^^^&^nDQn °
°^||ppvD *
iPftna^D a a
D
n
I I I I I I I I I I I 1 1 1 1 1 1 1 :
0 20 40 60 80 100 " 20 40 60 80 100 120 140 160 180 200
PM , (jg/m TSP, |jg/m!
Figure 6-131. PM2 5 and TSP Relationships in Philadelphia, IPN Average, 3/79 to 12/83: (a) comparison of PM2 5 with
TSP, (b) frequency distribution of PM2 5/TSP, (c) comparison of PM2 5 /TSP with PM2 5 , (d) comparison
ofPM25/TSPwithTSP.
-------
PHILADELPHIA, IPN, S. BROAD, 3/82-12/83; PM2
60
50
- 40
E
S 30
s
o.
20
10
0°
20
0.7
0.6
0.5
a.
to
3 0.4
0.3
0.2
0.1
Comparison of PM2,5 and Average TSP
D a
DD
D O
a
aa
o
ffl D
40
100
60 80
TSP, pg/m3
Comparison of PM25 /Avg TSP and PM 2,
120
a a
g a o
D Dg, DD a n
n a a D
a n a a
a „ an
D
15
25 35
PM,., |jg/m3
45
55
0.7
0.6
0.5
a.
CO
t
2 0.4
0.3
0.2
0.1
Distribution of PM ;5/Average TSP
0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.8 0.65 0.7
PM2S/AveraoeTSP
Comparison of PM2>/TSP and Average TSP
a a
a a
mi
D
a D
a o a°*
D a ™ a a D
a a a
20
40
60
TSP, (jg/m3
80
100
120
Figure 6-132. PM2 5 and TSP Relationships in Philadelphia, IPN, South Broad Site, 3/82 to 12/83: (a) comparison of PM2 5
with TSP, (b) frequency distribution of PM2 5/TSP, (c) comparison of PM25/TSP with PM25,
(d) comparison of PM2 5/TSP with TSP.
-------
Os
S
0.
60
50
40
30
20
10
Comparison of TSP and PM;
PHILADELPHIA, AIRS, 1987-1990; PM2.5
D
G
a
D
a
DO I
-,0 D.
ID aafaa n n °
oa a
D
D D
D D
D
D
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
20 40 60 80 100
TSP, ug/m3
Comparison of TSP and PM
120
i?_
3D
DDD
n °
, D a a
°BDD OUB£ D°o D D
>s D
20
40
PM
140
60
Distribution of PM25/Average TSP
I 0.15 0.25 0.35 0.45 I 0.55 I 0.65 I 0.75 I 0.85
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
PMj.5/TSP
Comparison of TSP and PM2.5
E
GK
0."
03
t
s
a.
i.i
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
n
n
D
n
n
n n
d3 D n
Q j-i Q
D n
% eg D o a
o^ D«Dana D Qa a D
- *DP|O 0DDOrfSP^ J^n*8^ DDD °n
" QDo ^fl'J'^D D^ff0*1 a^ B* * D' °
D Da#*aig]?i Dcptn'°D DQ Dan °
" a go a
D D
i i i i i i i i i i i i i
TSP, ug/m3
Figure 6-133. PM25 and TSP Relationships in Philadelphia, AIRS, 1987 to 1990: (a) comparison of PM2 5 with TSP,
(b) frequency distribution of PM2 5/TSP, (c) comparison of PM2-5 /TSP with PM2.5, (d) comparison of
PM25//TSP with TSP.
-------
PHILADELPHIA, IPN, S. BROAD, 3/62-12/83; PM,0
ON
tb
4*.
ON
E
"3»
a.
S
0.
80
70
60
SO
40
30
20
10
n
Comparison of PM10 and Average TSP
__ D
D Dn
n
~~ D
D
D ° 0 D "
D DQ °
n a
0 a
a aa D GD
n ana D
a n o a a
Q SU on B D
a D Q, n a n n
BaH3 a DO a
TID OD
a am rP a Q n
cP D a ^ H D
n ^b n D
i i i i i i i i i i i
a.
eo
0.9
0.8
0.7 -
0.6 -
0.5 -
0.4
0.3 -
0.2
0.1
0
TSP, (jg/m*
Comparison of PM
0.4
0.3
0.2
0.1
0
Distribution of PM10 /Average TSP
0.3 0.35 0.4 0.45 0.5 0.55 0.8 0.85 0.7 0.75 0.8 0.85
PM10 /Average TSP
Comparison of PM10 /Average TSP and PM,0
a
a
cP
D a a1
I
D urn
a a
a
D
10
30
50
70
PM10 , pg/m'
Figure 6-134. PM10 and TSP Relationships in Philadelphia, IPN, South Broad Site, 3/82 to 12/83: (a) comparison of PM10
with TSP, (b) frequency distribution of PM10/TSP, (c) comparison of PM10/TSP with PM10, (d) comparison
ofPM10/TSPwithTSP.
-------
ON
80
70
60
50
40
30
20
10
0
Comparison of TSP and PM1
PHILADELPHIA, AIRS, 1987-1990;
cna
20
40
60 60
TSP,
100
120
140
E
Q>
a.
o."
ia
t
0
s
Q.
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
n ?
Comparison of PM,n /Avg TSP and Avg TSP
n
_
D
-
D
D
n
c^
- n D
D Dn n DD o D cP D
DD rJ?n ^ ° @a
-------
oo
TABLE 6-13. RELATIONSHIPS BETWEEN PMX (PM2 5 OR PM10) AND TSP AS A FUNCTION OF TSP
CONCENTRATION LEVELS FOR SEVERAL SITES IN PHILADELPHIA: (a) RATIO OF PMX TO TSP,
(b) COEFFICIENT OF DETERMINATION (R2)
(a) Ratio of PMX/TSP
Philadelphia
Site
IPN
Average
IPN
S. Board
AIRS
Philadelphia
Site
IPN
Average
IPN
S. Board
AIRS
Dates
3/79
12/83
3/82
12/83
1/87
12/90
Dates
3/79
12/83
3/82
12/83
1/87
12/90
TSP
All
0.335 ±0.108
0.371 ± 0.105
0.345 ±0.137
TSP
All
0.64
0.57
0.45
PM25/TSP
TSP
<80
0.325 + 0.107
0.361 ± 0.106
0.350 ± 0.114
PM2 5 with
TSP
<80
0.36
0.38
0.29
TSP
>80
0.363 ±0.107
0.416 ± 0.090
0.317 ± 0.083
(b) Coefficients
TSP
>80
0.50
0.48
0.34
TSP
All
NA
0.525 ±0.105
0.573 ±0.187
of Determination, R2
TSP
All
NA
0.78
0.55
PM10/TSP
TSP
<80
NA
0.516 ±0.107
0.581 ±0.194
PM10 with
TSP
<80
NA
0.57
0.42
TSP
>80
NA
0.573 ± 0.079
0.528 ±0.131
TSP
>80
NA
0.61
0.24
-------
6.10.3.3 Correlations Between PM2>5, PM(10.2.s)> and PM10
The analysis of epidemiological results suggest that the smaller size fraction of
particulate matter may have a stronger association with health outcomes than fractions that
contain larger size particles (Chapter 12). It is of interest, therefore, to examine the
correlations between PM2 5, PM(10_2 5), and PM10. The means of these fractions and the
coefficient of determinination, R2, for their relationships are shown in Table 6-14 for eight
sites in California (CARB, 1995) and in Table 6-15 for several sites and times for Philadelphia
(IPN, 1985; AIRS, 1995; Harvard, 1995).
If correlation between PM2 5 and PM10 is high but the correlation of PM(10_2 5) with both
PM2 5 and PM10 is low, it is possible that PM10 is serving as an indicator of PM2 5 and that
any health effects of PM(10_2 5> would be masked by the larger PM2 5 (Wilson and Suh, 1996).
This may be the case in Philadelphia since PM2 5 to PM10. In general, PM(10_2 5) is a larger
fraction of PM10 at the California sites than at the Philadelphia site. However, there is still
substantial variability (-40% from minimum to maximum) in this ratio in the data sets from
California. Correlations between PM2 5 and PM(10_2 5) are highly variable at the sites in
California and encompass the Philadelphia value. The large correlations seen between PM2 5
and PM(10_2 5) at several California sites suggest a significant contribution from crustal
material to PM2 5. In contrast, at the Philadelphia site, only PM2 5 and not PM(10_2 5) was
highly correlated with PM10. These data support the desirability of having independent data
on fine mode particles and coarse mode particles for epidemiological investigations.
6.10.3.4 Fine Fraction
The fine fractions of PM10 (PM2 5/PM10) were shown for Philadelphia in Figure 6-116
(Panels c and d) and for California sites in Figures 6-123 to 6-130. A strong seasonal
variation is evident at the California sites but not in Philadelphia. Numerical values of the
PM2 5 fractional contribution to PM10 are given for Philadelphia and for several California
sites in Table 6-16. These variations in PM2.5/PM10 demonstrate the difficulty of inferring
PM2 5 from PM10 measurements unless some information is available on PM2 5/PM10 on a
seasonal and geographic basis.
6-249
-------
TABLE 6-14. MEANS AND STANDARD DEVIATIONS FOR PM2 5, PM(10_2 ^
AND PM10 AND COEFFICIENTS OF DETERMINATION (R2) BETWEEN PAIRS
FOR EIGHT CALIFORNIA AIR RESOURCES BOARD SITES DURING
THE PERIOD 1989 TO 1990
Mean ± Standard Deviation
Site
Riverside
Azusa
Bakersfield
Visalia
Stockton
San Jose
El Centra
Lone Pine
PM2.5
34.1 ±24.3
25.9 ± 17.2
24.2 ± 24.2
23.0 ± 20.5
17.4 ± 16.7
13.9 ± 14.1
12.3 ± 8.2
6.5 ± 3.7
PM(10-2.5)
34.5 ± 19.5
25.5 ± 14.5
33.7 ± 33.6
23.3 ± 15.9
17.8 ± 10.8
11.9 ±6.7
31.5 ± 25.4
12.1 ± 11.7
PM10
68.6 ± 37.6
51.3 ± 27.7
57.0 ± 27.7
46.3 ± 26.7
35.6 ± 21.8
25.8 ± 17.9
43.8 ± 30.5
18.6 ± 13.8
Coefficient of Determination, R2
Site
Riverside
Azusa
Bakersfield
Visalia
Stockton
San Jose
El Centra
Lone Pine
PM2 5 to PM(10.2.5)
0.21
0.27
0.36
0.36
0.05
0.16
0.27
0.19
PM2 5 to PM10
0.79
0.79
0.86
0.66
0.77
0.88
0.50
0.42
PM(10.,5)toPMlo
0.67
0.71
0.74
0.41
0.44
0.48
0.94
0.94
6-250
-------
TABLE 6-15. MEANS AND STANDARD DEVIATIONS FOR PM2 5, PM(10_2>5), PM10,
and TSP AND COEFFICIENTS OF DETERMINATION (R2) BETWEEN PAIRS
FOR SEVERAL SITES IN PHILADELPHIA DURING
PERIODS FROM 1979 TO 1995
Philadephia
Site
IPN Average
IPN S. Board
AIRS
Harvard PBY
Site
IPN Average
IPN S. Board
AIRS
Harvard PBY
Mean ± Standard Deviation
Dates
3/79
12/83
3/82
12/83
1/87
12/90
5/92
5/95
Dates
3/79
12/83
3/82
12/83
1/87
12/90
5/92
5/95
PM2.5 PM(10.2.5) PMjo TSP
23.3 ± 13.3 NA
22.6 ±11.0 9.7 ±4.
19.9 ± 10.0 13.1 ± 6
17.4 ± 9.4 7.0 ± 4.
Coefficient of
PM2 5 with PM2 5
PM(io-2.3) with PM
NA NA
0.14 0.90
0.32 0.86
0.11 0.88
NA 68.2 ± 24.7
7 32.1 ± 13.5 61.1 ±20.5
.7 33.0 ± 14.9 58.4 ± 21.9
3 24.3 ± 11.5 NA
Determination, R2
PM(iO-2.5) PM2.5
10 with PM10 with TSP
NA 0.64
0.42 0.57
0.69 0.45
0.41 NA
6.11 SUMMARY AND CONCLUSIONS
This chapter presents ambient concentration measurements of paniculate mass, PM10,
PM2 5, and PM(10_2 5), and of the chemical composition of particulate matter. For PM10
measurements the number of urban monitoring stations in the AIRS network increased rapidly
hi the years immediately after 1985, but the increase slowed substantially hi the early 1990s.
The measurements of PM10 at most of these stations were made every 6th day. Measurements
6-251
-------
TABLE 6-16. PM2 S/PM10 (FRACTION OF PM10 CONTRIBUTED BY PM2 s)
Mean Standard Deviation
Philadelphia
Mar-May
Jun-Aug
Sept-Nov
Dec-Feb
Azusa
Visalia
San Jose
Riverside
Stockton
Bakersfield
Lone Pine
El Centre
Riverside
Winter
Spring
Summer
Fall
0.71
0.73
0.73
0.72
0.75
0.50
0.49
0.49
0.49
0.46
0.44
0.38
0.29
0.57
0.48
0.41
0.48
0.13
0.14
0.16
0.17
0.15
0.13
0.22
0.15
0.14
0.18
0.19
0.14
0.10
0.14
0.13
0.09
0.15
Coefficient of Variation
(%) Range
18
19
22
24
20
26
45
31
29
39
43
37
34
25
27
22
15
0.09-1.09
0.30-1.56
0.17-1.81
0.03-1.55
0.22-0.99
0.22-0.76
0.23-0.69
0.16-0.74
of chemical species in urban areas usually are obtained in special studies of limited duration.
Data for chemical species in urban areas are discussed as appropriate in the text.
The mass concentration measurements in urban areas have been used to obtain (a) annual
trends in PM10, (b) ratios and correlations of PM2 5 to PM(10_2 5) and PM10 and (c) seasonal
variations in PM10, PM2 5, and PM(10.2.5)-
The measurements at non-urban sites were collected at a much smaller number of
locations relative to the number of urban stations by region. The geographical location of the
sites in the IMPROVE/NESCAUM networks were not selected to optimize their locations
relative to AIRS stations in the same region. As a result, not only are there small numbers of
6-252
-------
non-urban sites by region, but most of these sites are geographically well displaced from urban
areas.
The non-urban concentration measurements include both mass and chemical composition
so they were used to obtain (a) the variations in PM10, PM2 5, and PM(10_2 5) with month of the
year, (b) the chemical balances for sulfates, organic carbon, elemental carbon, and soil with
month of the year and (c) the variations in the concentrations of S, Se, and V and the S to Se
ratio with month of the year.
From the urban and non-urban PM10 concentration measurements, an "urban excess" was
obtained from the monthly differences in AIRS and IMPROVE/NESCAUM PM10 values.
Because of the limitations mentioned above and the lack of tests of statistical significance,
these "urban excess" values should be viewed as preliminary and used very cautiously with
respect to quantitative results.
Additional sections of Chapter 6 include the following discussions: (1) the mass
apportionment of chemical species obtained from a group of selected research studies of the
chemical composition at locations in the eastern, central and western U.S.; (2) acid sulfate
study results by (a) their geographical distribution in the U.S. and southern Canada, (b) spatial
variations on a city and urban scale, (c) seasonal variations, (d) diurnal variations, and
(e) indoor and personal monitoring relative to outdoor hydrogen ion concentration
measurements; (3) particle number concentrations with emphasis on ultrafine particles;
(4) some information on metals potentially present in ultrafine particles; and (5) information
on fine and coarse PM trends and patterns for sites where both fine and coarse PM
measurements were available.
Based on these various concentration measurements a considerable number of
conclusions may be obtained. Many of these conclusions are limited by (a) the number of
monitoring sites available, (b) their geographical location, (c) the frequency of measurement
and (d) differences in methodology used between networks or stations as well as between
individual studies of chemical composition.
Trends in PM10 mass concentration, averaged over regions or by city, usually indicate a
substantial decrease in PM10 concentrations by year from 1988 to 1994. There are exceptions
to this significant downward trend in Philadelphia and at some locations within the Southern
6-253
-------
California Basin. The trend plots shown in Chapter 6 have not been tested for statistical
significance. The trend plots can also be influenced by the approach taken in the selection of
stations. Since the number of stations increased rapidly between 1985 and 1990, the trends
that might be obtained using early data could be biased by the added stations being influenced
by location towards higher or lower PM10 concentration measurements. For this document,
the set of stations in operation from 1988 to 1994 was used to obtain PM10 concentration
trends during this period. It should also be noted that meteorological influences which are
known to be important for deducing trends of O3 concentrations also may affect PM10
concentrations on a year-to-year basis.
Keeping the limitations mentioned above in mind, urban trend analyses for PM10 are
presented using all stations in operation in a given year and the smaller set of trend stations in
operation over the entire 1988 to 1994 time period. The range for the averaged decrease in
PM10 between 1988 and 1994 at urban stations was: for the contiguous U.S., all sites, 24%,
trend sites, 20%; for the eastern U.S., all sites, 16%, trend sites, 18%; and for the western
U.S., all sites, 31%, trend sites 28%. There were appreciable differences between regions in
the range of averaged decreases in PM10 between 1988 and 1994 with the decrease for urban
stations in the northeast ranging from 18% (all) to 19% (trend) while in the industrial midwest
the decreases ranged from 12% (all) to 19% (trend). The ranges of averaged decreases for the
three western regions were from 27% to 37% (all) and 23% to 33% (trend). These decreases
in PM10 concentrations resulted in 1994 annual average regional AIRS concentrations in the
range of 25 Mg/m3 to 32 /ug/m3.
For individual cities, both between and within cities, the decreases in PM10 for individual
stations could show substantial variability. In the Los Angeles Basin, 3 of 6 stations showed
statistically significant downward trends in PM10 while other stations showed no significant
trends. In the western U.S. several large cities showed larger downward trends in PM10 than
the regional averages. PM2.5 and PM(10-2.5) or PMIO data, suitable for determining trends
of both fine and coarse components of PMIO, are available from only a few sites in the eastern
United States and a few sites in California. While a general decrease is evident in both fine
and coarse components of PMIO at most sites where data is available, it is not possible to
ascertain differential trends in the two components.
6-254
-------
A few attempts to infer various types of background levels of PM2 5 and PM10 have been
made. The backgrounds most relevant to the Criteria Document include a "natural"
background which excludes all anthropogenic sources anywhere in the world, and a
background which excludes anthropogenic sources in North America, but not elsewhere.
Annual average natural background levels of PM10 have been estimated to range from 4 to
8 fig/m3 in the western United States and 5 to 11 /ig/m3 in the eastern United States.
Corresponding PM2 5 levels have been estimated to range from 1 to 4 /-ig/m3 in the western
United States and 2 to 5 /Ltg/m3 in the eastern United States. Twenty-four hour average
concentrations may be substantially higher than the annual or seasonal average background
concentrations presented in Chapter 6. The 24-hour averages are usually considered for
control strategies while the annual and seasonal averages are suitable for risk analyses.
Based either on the correlation of individual values or on the average PM2 5 to PM10
values, the annual ratios of PM2 5 to PM10 from urban stations fell within a relatively narrow
range of 0.55 to 0.6, for both the entire eastern and western U.S. However, for two regions,
the upper midwest and southwest, the correlations yielded ratios of less than 0.2 while the
average PM2 5 to PM10 values yielded ratios between 0.3 and 0.4.
Ratios of PM2 5 to PM(10_2 5) from urban stations can vary with season as well as
between regions. In the northeast, southeast, and industrial midwest regions, there is
appreciable uniformity with PM2 5 exceeding PM(10_2 5) during all seasons of the year.
In contrast, in the southwest, the PM2 5 is less than the PM coarse during all seasons of the
year. In the northwest and in southern California, PM2 5 exceeds PM10 in the fall and winter
with the reverse occurring in the spring and summer.
Measurements of the day to day variability in PM2 5 and PM10 are available from only
one site located in Philadelphia, PA. The data show day to day variations of 8.6±7.5 /ig/m3
for PM10, 6.8±6.5 pcg/m3 for PM2 5, and 3.1 ±3 A /*g/m3 for PM10_2 5 from May 1992 to
April 1995. Maximum day to day differences were 50 /ig/m3 for PM10, 55 /-ig/m3 for PM2 5,
and 35 /*g/m3 for PM(10.2 5). The ratio of PM2 5 to PM10 was 0.72±0.16 over the
measurement period and the correlation between PM2 5 and PM10 was 0.86 (R2) suggesting
that variability in PM2 5 was forcing the variability in PM10. Data collected by dichotomous
samplers at several sites in California showed that PM(10_2 5) accounted for roughly half of
6-255
-------
PM10 and that both PM2 5 and PM(10_2 5) were highly correlated with PM10. Differences
among the Philadelphia data set and the California data sets illustrate the dangers in
extrapolating relations among different size fractions from one region of the country to other
regions.
Comparisons of seasonal profiles of PM10 show summer peaks for both urban and
nonurban sites in the northeast, southeast, and industrial midwest. These summer peaks
usually, but not exclusively, are associated with the summer peaks in PM2 5. The PM2 5
concentrations at non-urban sites in the northeast, southeast, and industrial midwest exceed the
PM(10_2 5) concentrations in all seasons of the year, as is the case for urban stations. The
northwest urban PM10 and PM2 5 concentrations show a spring and early summer minimum
with the highest values in fall and winter, while the non-urban PM10 and PM2 5 concentrations
show a summer peak similar to the seasonal profiles in the eastern U.S. In southern
California, the urban PM10 and PM2 5 seasonal profiles show fall peaks, while the non-urban
seasonal profiles have a relatively flat maximum from spring into early fall. Again it must be
emphasized that with so few nonurban sites in most regions any conclusions drawn from the
comparisons above are very tentative for most regions of the U.S.
The every-sixth-day urban PM10 averaged concentrations for most regions of the
United States ranged during 1990 to 1994 from 10 to 15 //g/m3 up to 40 to 60 Mg/m3. The
southern California region had PM10 values averaging up to 70 to 75 //g/m3. Day-to-day
variations in PM10 concentrations in Knoxville, TN, ranged from 10 to 20 Mg/m3, while hi
Missoula, MT, PM10 concentrations ranged from < 10 to 120 to 140 Aig/m3 with one value
over 200 Mg/m3.
A quantity termed an urban excess has been discussed extensively in the text of
Chapter 6. In view of the distinctions discussed above between the number and geographical
distribution of urban and non-urban sites, the quantitative results probably should be
interpreted with considerable caution. While it is reasonable that additional sources within
cities should increase PM10 concentrations significantly above those at non-urban sites, the
quantitative differences can be sensitive to the location of the non-urban sites with respect to
individual cities. The most striking feature of the urban excess is its large increase hi the fall
and whiter in the western United States compared to the eastern United States.
6-256
-------
The chemical compositions at the nonurban IMPROVE/NESCAUM sites are discussed
within the earlier sections of Chapter 6. Later in Chapter 6 an independent evaluation of
chemical composition is given based on a mixture of intensive studies at both urban and
nonurban sites. The results from both approaches appear reasonably consistent in showing
geographical variations in chemical composition.
Both approaches indicate that sulfate, presumably present either as (NH4)HSO4 or as
(NH4)2SO4, is the largest contributor to the chemical species measured in the eastern
United States. Other results indicate that a large regional background of sulfate is
superimposed on a smaller urban contribution. Results also indicate that sulfate is relatively
uniform in concentration throughout much of the eastern United States. These results are less
pronounced in the late fall and winter months. The contribution of sulfate to PM10 is
somewhat smaller than sulfate is to PM2 5. Comparisons of the eastern United States with the
central United States and western United States show a decreasing contribution of sulfate to the
chemical composition. Conversely, the soil and/or mineral concentrations become an
increasingly important contributor to PM10 and PM2 5 going from the eastern to the western
United States. The nitrates, as NH4NO3, also appear to be a much more important contributor
to the composition in areas of the western United States than in the eastern United States.
Organic compounds also appear to increase in importance relative to sulfate going from the
eastern to the western United States. For PM(10_2-5), sulfates are relatively unimportant. Soil
or mineral components dominate the PM(10_2 5), but there is a substantial unknown fraction of
PM(10-2.5)'
Particle strong acidity, defined as H2SO4 plus HSO4, is a regional pollutant fairly evenly
distributed across large areas of the central portion of the eastern United States. It is relatively
evenly distributed across small cities, but in the one large urban area from which results have
been reported, the higher concentrations of ammonia in the central city apparently neutralize a
significant portion of the acidity. Thus, higher concentrations of acidity are found in rural
areas, small towns, and suburban areas than in the centers of larger urban areas. The
concentration of acidity is higher in the summer and peaks during the early afternoon in urban
areas. Indoor, outdoor, and personal monitoring indicates that indoor and personal
concentrations of acidity are lower than outdoor concentrations, presumably due to
6-257
-------
neutralization by indoor ammonia. Particle strong acidity is normally found exclusively in the
fine particle mode. Coarse particles tend to be basic. Exceptions may occur during periods of
fog or very high relative humidity.
The number concentration of particles is generally dominated by particles below 0.1 /urn
or 100 nm in diameter, termed ultrafine particles. When a distinct mode is present, it is called
the nuclei mode. Number geometric mean diameter ranged from 12 to 43 nm in Long Beach,
CA and 47 to 75 nm in clean air in the Rocky Mountains. Particle number concentrations
varied from less than 1,000/cm3 at clean background sites to over 100,000/cm3 in polluted
urban areas and were correlated with the volume of particles below 0.1 /urn. Particle number
concentrations were not found to be correlated with accumulation mode volume on an hourly
basis. Correlations of particle number and accumulation mode volume might be expected if
compared over longer time intervals (e.g., days), but such studies have not yet been done.
An examination of the size distribution of metals suggests that metals that may be
volatilized during combustion may appear as ultrafine particles. Such metals include copper,
zinc, and lead and possibly nickel and vanadium, as well as nonmetals selenium and sulfur.
Ultrafine particles appear to exist longer under conditions of low concentrations and high
relative humidity.
6-258
-------
REFERENCES
AIRS, Aerometric Information Retrieval System [database]. (1995) [PM10 and PM2 5 data]. Research Triangle
Park, NC: U.S. Environmental Protection Agency, Office of Air Quality Planning and Standards.
Altshuller, A. P. (1980) Seasonal and episodic trends in sulfate concentrations (1963-1978) in the eastern United
States. Environ. Sci. Technol. 14: 1337-1349.
Altshuller, A. P. (1982) Relationships involving particle mass and sulfur content at sites in and around St. Louis,
Missouri. Atmos. Environ. 16: 837-843.
Altshuller, A. P. (1985) Relationships involving fine particle mass, fine particle sulfur and ozone during episodic
periods at sites hi and around St. Louis, MO. Atmos. Environ. 19: 265-276.
Altshuller, A. P. (1987) Relationships between direction of wind flow and fine particle sulfur concentrations
within and upwind of St. Louis, MO. Atmos. Environ. 21: 1023-1032.
Appel, B. R.; Colodny, P.; Wesolowski, J. J. (1976) Analysis of carbonaceous materials in southern California
atmospheric aerosols. Environ. Sci. Technol. 10: 359-363.
Appel, B. R.; Kothny, E. L.; Hoffer, E. M.; Hidy, G. M.; Wesolowski, J. J. (1978) Sulfate and nitrate data
from the California Aerosol Characterization Experiment (ACHEX). Environ. Sci. Technol.
12: 418-425.
Appel, B. R.; Hoffer, E. M.; Kothny, E. L.; Wall, S. M.; Haik, M.; Knights, R. L. (1979) Analysis of
carbonaceous material in southern California atmospheric aerosols. 2. Environ. Sci. Technol.
13: 98-104.
Ashbaugh, L. L.; Watson, J. G.; Chow, J. (1989) Estimating fluxes from California's dry deposition monitoring
data. Presented at: 82nd annual meeting of the Air & Waste Management Association; June; Anaheim,
CA. Pittsburgh, PA: Air & Waste Management Association; paper no. 89-65.3.
Barone, J. B.; Cahill, T. A.; Eldred, R. A.; Flocchini, R. G.; Shadoan, D. J.; Dietz, T. M. (1978)
A multivariate statistical analysis of visibility degradation at four California cities. Atmos. Environ.
12: 2213-2221.
Barton, R. G.; Clark, W. D.; Seeker, W. R. (1990) In: Proceedings of the 1st international conference on toxic
combustion byproducts.
Bennett, R. L.; Stockburger, L.; Barnes, H. M. (1994) Comparison of sulfur measurements from a regional fine
particle network with concurrent acid modes network results. Atmos. Environ. 28: 409-419.
Berner, A.; Lurzer, C. (1980) Mass size distributions of traffic aerosols at Vienna. J. Phys. Chem.
84: 2079-2083.
Brauer, M.; Koutrakis, P.; Spengler, J. D. (1989) Personal exposures to acidic aerosols and gases. Environ. Sci.
Technol. 23: 1408-1412.
Brauer, M.; Koutrakis, P.; Keeler, G. J.; Spengler, J. D. (1991) Indoor and outdoor concentrations of inorganic
acidic aerosols and gases. J. Air Waste Manage. Assoc. 41: 171-181.
Burton, R. M.; Liu, L. J. S.; Wilson, W. E.; Koutrakis, P. (1995) Comparison of aerosol acidity hi urban and
semi-rural environments. Atmos. Environ.: submitted.
6-259
-------
Cadle, S. H. (1985) Seasonal variations in nitric acid, nitrate, strong aerosol acidity, and ammonia in an urban
area. Atmos. Environ. 19: 181-188.
Cahill, T. A. (1979) Comments on surface coating for Lundgren-type impactors. In: Lundgren, D. A.;
Lippmann, M.; Harris, F. S., Jr.; Clark, W. E.; Marlow, W. H.; Durham, M. D., eds. Aerosol
measurement: [papers from a workshop]; March 1976; Gainesville, FL. Gainesville, FL: University
Presses of Florida; pp. 131-134.
Cahill, T. A. (1980) Proton microprobes and particle-induced X-ray analytical systems. Annu. Rev. Nucl. Part.
Sci. 30:211-252.
Cahill, T. A. (1996) [Data from IMPROVE data base.] Research Triangle Park, NC: U.S. Environmental
Protection Agency, Office of Air Quality Planning and Standards.
Cahill, T. A.; Wakabayashi, P. (1993) Compositional analysis of size-segregated aerosol samples.
In: Newman, L., ed. Measurement challenges in atmospheric chemistry. Washington, DC: American
Chemical Society; pp. 211-228. (Advances in chemistry series no. 232).
Cahill, T. A.; Goodart, C.; Nelson, J. W.; Eldred, R. A.; Nasstrom, J. S.; Feeney, P. J. (1985) Design and
evaluation of the drum impactor. In: Ariman, T.; Veziroglu, T. N., eds. Proceedings of the international
symposium on particulate and multi-phase processes. Washington, DC: Hemisphere Publishing
Corporation; pp. 319-325.
Cahill, T. A.; Feeney, P. J.; Eldred, R. A. (1987) Size-time composition profile of aerosols using the drum
sampler. In: Proceedings of the 4th international PIXE conference; June 1986; Tallahassee, FL. Nucl.
Instrum. Methods Phys. Res. B22: 344-348.
Cahill, T. A.; Surovik, M.; Wittmeyer, I. (1990) Visibility and aerosols during the 1986 Carbonaceous Species
Methods Comparison Study. Aerosol Sci. Technol. 12: 149-160.
Cahill, T. A.; Wakabayashi, P.; Raabe, O.; Teague, S. (1992a) A new inertial impactor for visibility-reducing
aerosols. Presented at: 85th annual meeting and exhibition of the Air & Waste Management Association;
June; Kansas City, MO. Pittsburgh, PA: Air & Waste Management Association; paper no. 92-60.08.
Cahill, T. A.; Wilkinson, K.; Schnell, R. (1992b) Composition analyses of size-resolved aerosol samples taken
from aircraft downwind of Kuwait, spring 1991. J. Geophys. Res. [Atmos.] 97: 14,513-14,520.
Cahill, T. A.; Morales, R.; Miranda, J. (1996a) Comparative aerosol studies of Pacific rim cities—Santiago,
Chile (1987); Mexico City, Mexico (1987-1990); and Los Angeles, U.S.A. (1973 and 1987). Atmos.
Environ. 30: 747-749.
Cahill, T. A.; Eldred, R. A.; Wakabayashi, P. H. (1996b) Trends in fine particle concentrations at Great Smoky
Mountains National Park. For presentation at: Annual meeting of the Air & Waste Management
Association; June; Nashville, TN. Pittsburgh, PA: Air & Waste Management Association; submitted
paper no. 96-MP1A.05.
California Air Resources Board. (1995) [Data base provided by John R. Holmes, Chief, Research Division.]
Sacramento, CA: California Air Resources Board.
Cass, G. R.; McRae, G. J. (1983) Source-receptor reconciliation of routine air monitoring data for trace metals:
an emission inventory assisted approach. Environ. Sci. Technol. 17: 129-139.
Cass, G. R.; Conklin, M. H.; Shah, J. J.; Huntzicker, J. J.; Macias, E. S. (1984) Elemental carbon
concentrations: estimation of an historical data base. Atmos. Environ. 18: 153-162.
6-260
-------
Chesworth, S.; Yang, G.; Chang, D. P. Y.; Jones, A. D.; Kelly, P. B.; Kennedy, I. M. (1994) The fate of
arsenic in a laminar diffusion flame. Combust. Flame 98: 259-266.
Chow, J. C.; Watson, J. G.; Frazier, C. A.; Egami, R. T.; Goodrich, A.; Ralph, C. (1988) Spatial and temporal
source contributions to PM10 and PM2 5 in Reno, NV. In: Mathai, C. V.; Stonefield, D. H., eds.
PM-10: implementation of standards, an APCA/EPA international specialty conference; February; San
Francisco, CA. Pittsburgh, PA: Air Pollution Control Association; pp. 438-457. (APCA transactions
series TR-13).
Chow, J. C.; Watson, J. G.; Pritchett, L.; Lowenthal, D.; Frazier, C.; Neuroth, G.; Evans, K.; Moon, D.
(1990) Wintertime visibility in Phoenix, Arizona. Presented at: the 83rd annual meeting & exhibition;
June; Pittsburgh, PA. Pittsburgh, PA: Air & Waste Management Association; paper no. 90-66.6.
Chow, J. C.; Watson, J. G.; Lowenthal, D. H.; Frazier, C. A.; Hinsvark, B. A.; Prichett, L. C.; Neuroth,
G. R. (1992a) Wintertime PM10 and PM2 5 chemical compositions and source contributions in Tucson,
Arizona. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional paniculate source
controls, an A&WMA/EPA international specialty conference, v. I; January; Scottsdale, AZ. Pittsburgh,
PA: Air & Waste Management Association; pp. 231-243. (A&WMA transactions series no. 22).
Chow, J. C.; Watson, J. G.; Lowenthal, D. H.; Solomon, P. A.; Magliano, K. L.; Ziman, S. D.; Richards,
L. W. (1992b) PM10 source apportionment in California's San Joaquin Valley. Atmos. Environ. Part A
26: 3335-3354.
Chow, J. C.; Liu, C. S.; Cassmassi, J.; Watson, J. G.; Lu, Z.; Pritchett, L. C. (1992c) A neighborhood-scale
study of PM10 source contributions in Rubidoux, California. Atmos. Environ. Part A 26: 693-706.
Chow, J. C.; Watson, J. G.; Lowenthal, D. H.; Solomon, P. A.; Magliano, K. L.; Ziman, S. D.; Richards,
L. W. (1993a) PM10 and PM2 5 compositions in California's San Joaquin Valley. Aerosol Sci. Technol.
18: 105-128.
Chow, J. C.; Watson, J. G.; Ono, D. M.; Mathai, C. V. (1993b) PM10 standards and nontraditional particulate
source controls: a summary of the A&WMA/EPA international specialty conference. J. Air Waste
Manage. Assoc. 43: 74-84.
Chow, J. C.; Watson, J. G.; Fujita, E. M.; Lu, Z.; Lawson, D. R.; Ashbaugh, L. L. (1994a) Temporal and
spatial variations of PM2 5 and PM10 aerosol in the Southern California Air Quality Study. Atmos.
Environ. 28: 2061-2080.
Chow, J. C.; Watson, J. G.; Solomon, P. A.; Thuillier, R. H.; Magliano, K. L.; Ziman, S. D.; Blumenthal,
D. L.; Richards, L. W. (1994b) Planning for SJVAQS/AUSPEX particulate matter and visibility
sampling and analysis. In: Solomon, P. A.; Silver, T. A., eds. Planning and managing regional air
quality: modeling and measurement studies: a perspective through the San Joaquin Valley air quality
study and AUSPEX. Boca Raton, FL: Lewis Publishers; pp. 171-216.
Chow, J. C.; Fairley, D.; Watson, J. G.; DeMandel, R.; Fujita, E. M.; Lowenthal, D. H.; Lu, Z.; Frazier,
C. A.; Long, G.; Cordova, J. (1995a) Source apportionment of wintertime PM10 at San Jose, Calif.
J. Environ. Eng. (NY) 121: 378-387.
Chow, J. C.; Watson, J. G.; Lu, Z.; Lowenthal, D. H.; Frazier, C. A.; Solomon, P. A.; Thuiller, R. H.;
Magliano, K. (1995b) Descriptive analysis of PM2 5 and PM10 regionally representative locations during
SJVAQS/AUSPEX. Atmos. Environ.: in press.
Cobourn, W. G.; Husar, R. B. (1982) Diurnal and seasonal patterns of particulate sulfur and sulfuric acid in
St. Louis, July 1977-June 1978. Atmos. Environ. 16: 1441-1450.
6-261
-------
Conner, T. L.; Miller, J. L.; Willis, R. D.; Kellogg, R. B.; Dann, T. F. (1993) Source apportionment of fine
and coarse particles in southern Ontario, Canada. Presented at: 86th annual meeting & exhibition of the
Air & Waste Management Association; June; Denver, CO. Pittsburgh, PA: Air & Waste Management
Association; paper no. 93-TP-58.05.
Countess, R. J.; Wolff, G. T.; Cadle, S. H. (1980) The Denver winter aerosol: a comprehensive chemical
characterization. J. Air Pollut. Control Assoc. 30: 1194-1200.
Countess, R. J.; Cadle, S. H.; Groblicki, P. J.; Wolff, G. T. (1981) Chemical analysis of size-segregated
samples of Denver's ambient paniculate. J. Air Pollut. Control Assoc. 31: 247-252.
Davis, B. L.; Johnson, L. R.; Stevens, R. K.; Courtney, W. J.; Safriet, D. W. (1984) The quartz content and
elemental composition of aerosols from selected sites of the EPA inhalable paniculate network. Atmos.
Environ. 18: 771-782.
Davison, R. L.; Nacusch, D. F. S.; Wallace, J. R.; Evans, C. A., Jr. (1974) Trace elements in fly ash:
dependence of concentration on particle size. Environ. Sci. Technol. 8: 1107-1113.
Desaedeleer, G. G.; Winchester, J. W.; Akselsson, K. R. (1977) Monitoring aerosol elemental composition in
particle size fractions for predicting human respiratory uptake. Nucl. Instrum. Methods 142: 97-99.
Desert Research Institute. (1995) [Unpublished data]. Reno, NV: Energy and Environmental Engineering Center.
Dockery, D. W.; Schwartz, J.; Spengler, J. D. (1992) Air pollution and daily mortality: associations with
particulates and acid aerosols. Environ. Res. 59: 362-373.
Dockery, D. W.; Pope, C. A., Ill; Xu, X.; Spengler, J. D.; Ware, J. H.; Fay, M. E.; Ferris, B. G., Jr.;
Speizer, F. E. (1993) An association between air pollution and mortality in six U.S. cities. N. Engl. J.
Med. 329: 1753-1759.
Dresser, A. L. (1988) A dispersion and receptor model analysis of a western community's PM-10 problem.
JAPCA38: 1419-1421.
Dzubay, T. G. (1980) Chemical element balance method applied to dichotomous sampler data. Ann. N. Y. Acad.
Sci. 338: 126-144.
Dzubay, T. G.; Stevens, R. K.; Lewis, C. W.; Hern, D. H.; Courtney, W. J.; Tesch, J. W.; Mason, M. A.
(1982) Visibility and aerosol composition in Houston, Texas. Environ. Sci. Technol. 16: 514-525.
Dzubay, T. G.; Stevens, R. K.; Gordon, G. E.; Olmez, L; Sheffield, A. E.; Courtney, W. J. (1988)
A composite receptor method applied to Philadelphia aerosol. Environ. Sci. Technol. 22: 46-52.
Eldering, A.; Cass, G. R. (1994) A source-oriented model for air pollutant effects on visibility. J. Geophys. Res.
[Atmos.]: submitted.
Eldred, R. A.; Cahill, T. A. (1994) Trends in elemental concentrations of fine particles at remote sites in the
United States of America. Atmos. Environ. 28: 1009-1019.
Eldred, R. A.; Ashbaugh, L. L.; Cahill, T. A.; Flocchini, R. G.; Pitchford, M. L. (1983) Sulfate levels in the
southwest during the 1980 copper smelter strike. J. Air Pollut. Control Assoc. 33: 110-113.
6-262
-------
Eldred, R. A.; Cahill, T. A.; Feeney, P. J.; Malm, W. C. (1987) Regional patterns in paniculate matter from the
National Park Service network, June 1982 to May 1986. In: Bhardwaja, P. S., ed. Visibility protection:
research and policy aspects, an APCA international specialty conference; September 1986; Grand Teton
National Park, WY. Pittsburgh, PA: Air Pollution Control Association; pp. 386-396. (APCA
transactions series no. TR-10).
Eldred, R. A.; Cahill, T. A.; Pitchford, M.; Malm, W. C. (1988) IMPROVE-a new remote area paniculate
monitoring system for visibility studies. Presented at: 81st annual meeting of the Air Pollution Control
Association; June; Dallas, TX. Pittsburgh, PA: Ah" Pollution Control Association; paper no. 88-54.3.
Eldred, R. A.; Cahill, T. A.; Wilkinson, L. K.; Feeney, P. J.; Chow, J. C.; Malm, W. C. (1990) Measurement
of fine particles and their chemical components in the IMPROVE/NPS networks. In: Mathai, C. V., ed.
Visibility and fine particles: an A&WMA/EPA international specialty conference; October 1989; Estes
Park, CO. Pittsburgh, PA: Air & Waste Management Association; pp. 187-196. (A&WMA transactions
series no. TR-17).
Eldred, R. A.; Cahill, T. A.; Feeney, P. J. (1994a) Regional patterns of selenium and other trace elements in the
IMPROVE network. In: Proceedings of the international specialty conference on aerosol and atmospheric
optics: radiative balance and visual air quality, volume A. Pittsburgh, PA: Air and Waste Management
Association.
Eldred, R. A.; Cahill, T. A.; Flocchini, R. G. (1994b) Comparison of PM10 and PM2 5 aerosols hi the
IMPROVE network. In: Proceedings of an international specialty conference on aerosol and atmospheric
optics: radiative balance and visual air quality, volume A. Pittsburgh, PA: Air and Waste Management
Association. Air Waste: submitted.
Ellenson, W. D.; Schwab, M.; Egler, K. A.; Shadwick, D.; Willis, R. D. (1994) Draft technical report for the
pilot project of lower Rio Grande valley environmental study. ManTech Environmental Technology.
Submitted to U.S. EPA.
Fan-ley, D. (1990) The relationship of daily mortality to suspended particulates hi Santa Clara county, 1980-86.
Environ. Health Perspect. 89: 159-168.
Federal Register. (1986) Hazardous waste management system; land disposal restrictions. F. R. (November 7)
51: 40572-40654.
Fekete, K. E.; Gyenes, L. (1993) Regional scale transport model for ammonia and ammonium. Atmos. Environ.
Part A 27: 1099-1104.
Ferman, M. A.; Wolff, G. T.; Kelly, N. A. (1981) The nature and sources of haze in the Shenandoah
Valley/Blue Ridge Mountains area. J. Air Pollut. Control Assoc. 31: 1074-1082.
Flocchini, R. G.; Cahill, T. A.; Shadoan, D. J.; Lange, S. J.; Eldred, R. A.; Feeney, P. J.; Wolfe, G. W.;
Simmeroth, D. C.; Suder, J. K. (1976) Monitoring California's aerosols by size and elemental
composition. Environ. Sci. Technol. 10: 76-82.
Flocchini, R. G.; Cahill, T. A.; Eldred, R. A.; Feeney, P. J. (1990) Paniculate sampling hi the northeast:
a description of the Northeast States for Coordinated Air Use Management (NESCAUM) network.
In: Mathai, C. V., ed. Visibility and fine particles: an A&WMA/EPA international specialty conference;
October 1989; Estes Park, CO. Pittsburgh, PA: Air & Waste Management Association; pp. 197-206.
(A&WMA transactions series no. TR-17).
Frazier, C. A. (1989) Letter [report on mass and chemical concentrations and babs measurements for Phoenix pilot
study samples]. Reno, NV: Desert Research Institute, Energy and Environmental Engineering Center.
6-263
-------
Friedlander, S. K. (1977) Smoke, dust and haze: fundamentals of aerosol behavior. New York, NY: John Wiley
&Sons.
Gray, H. A.; Cass, G. R.; Huntzicker, J. J.; Heyerdahl, E. K.; Rau, J. A. (1984) Elemental and organic carbon
particle concentrations: a long-term perspective. Sci. Total Environ. 36: 17-25.
Gray, H. A.; Cass, G. R.; Huntzicker, J. J.; Heyerdahl, E. K.; Rau, J. A. (1986) Characteristics of atmospheric
organic and elemental carbon particle concentrations in Los Angeles. Environ. Sci. Technol.
20: 580-589.
Griffing, G. W. (1980) Relations between the prevailing visibility, nephelometer scattering coefficient and
sunphotometer turbidity coefficient. Atmos. Environ. 14: 577-584.
Groblicki, P. J.; Wolff, G. T.; Countess, R. J. (1981) Visibility-reducing species hi the Denver "brown cloud" -
I. relationships between extinction and chemical composition. In: White, W. H.; Moore, D. J.; Lodge,
J. P., Jr., eds. Plumes and visibility: measurements and model components, proceedings of the
symposium; November 1980; Grand Canyon National Park, AZ. Atmos. Environ. 15: 2473-2484.
Hasan, H.; Dzubay, T. G. (1987) Size distributions of species in fine particles hi Denver using a microorifice
impactor. Aerosol Sci. Technol. 6: 29-39.
Hering, S. V.; Friedlander, S. K. (1982) Origins of aerosol sulfur size distributions in the Los Angeles basin.
Atmos. Environ. 16: 2647-2656.
Hering, S. V.; McMurry, P. H. (1991) Optical counter response to monodisperse atmospheric aerosols. Atmos.
Environ. Part A 25: 463-468.
Hering, S. V.; Flagan, R. C.; Friedlander, S. K. (1978) Design and evaluation of new low-pressure impactor.
I. Environ. Sci. Technol. 12: 667-673.
Hering, S. V.; Appel, B. R.; Cheng, W.; Salaymeh, F.; Cadle, S. H.; Mulawa, P. A.; Cahill, T. A.; Eldred,
R. A.; Surovik, M.; Fitz, D.; Howes, J. E.; Knapp, K. T.; Stockburger, L.; Turpin, B. J.; Huntzicker,
J. J.; Zhang, X.-Q.; McMurry, P. H. (1990) Comparison of sampling methods for carbonaceous
aerosols in ambient air. Aerosol Sci. Technol. 12: 200-213.
Hering, S.; Eldering, A.; Seinfeld, J. H. (1996) Bimodal character of accumulation mode aerosols in southern
California. Atmos. Environ.: submitted.
Hidy, G. M.; Mueller, P. K.; Grosjean, D.; Appel, B. R.; Wesolowski, J. J., eds. (1980) The character and
origins of smog aerosols: a digest of results from the California Aerosol Characterization Experiment
(ACHEX). New York, NY: John Wiley & Sons.
Hildemann, L. M.; Markowski, G. R.; Cass, G. R. (1991) Chemical composition of emissions from urban
sources of fine organic aerosol. Environ. Sci. Technol. 25: 744-759.
Hoggan, M. C.; Banayan, S. C.; Sin, R. W.; Davidson, A. (1993) An analysis of PM10 air quality in California's
South Coast Air Basin, 1985-1992. In: Criteria air pollutants: volume 3B, papers from the 86th annual
meeting & exhibition of the Air & Waste Management Association; June ; Denver, CO. Pittsburgh, PA:
Air & Waste Management Association; paper no. 93-WA-75.04. (A&WMA publication no. AM93-3).
6-264
-------
Houck, J. E.; Rau, J. A.; Body, S.; Chow, J. C. (1992) Source apportionment: Pocatello, Idaho PM10
nonattainment area. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional particulate
source controls, an A&WMA/EPA international specialty conference, v. I; January; Scottsdale, AZ.
Pittsburgh, PA: Air & Waste Management Association; pp. 219-230. (A&WMA transactions series
no. 22).
Husar, R. B.; Frank, N. H. (1991) Interactive exploration and analysis of EPA's Aerometric Information and
Retrieval System (AIRS) data sets. Presented at: 84th annual meeting and exhibition of the Air & Waste
Management Association; June; Vancouver, BC, Canada. Pittsburgh, PA: Air & Waste Management
Association; paper no. 91-119.4.
Husar, R. B.; Poirot, R. (1992) Exploration of the AIRS database: weekly cycle of ozone and PM 10 aerosols.
Presented at: 85th annual meeting of the Air & Waste Management Association; June; Kansas City, MO.
Pittsburgh, PA: Air & Waste Management Association; paper no. 92-77.06.
Husar, R. B.; Wilson, W. E. (1993) Haze and sulfur emission trends in the eastern United States. Environ. Sci.
Technol. 27: 12-16.
Husar, R. B.; Holloway, J. M.; Patterson, D. E.; Wilson, W. E. (1981) Spatial and temporal pattern of eastern
U.S. haziness: a summary. Atmos. Environ. 15: 1919-1928.
Husar, R. B.; Elkins, J. B.; Wilson, W. E. (1994) U.S. visibility trends, 1960-1992, regional and national.
Presented at: 87th annual meeting of the Air & Waste Management Association; June; Cincinnati, OH.
Pittsburgh, PA: Air & Waste Management Association; paper no. 94-MP3.05.
IPN. (1985) [Inhalable Particulate Network Database.] Research Triangle Park, NC: U.S. Environmental
Protection Agency, National Exposure Research Laboratory; Jose M. Sune, contact.
Jaenicke, R. (1980) Natural aerosols. In: Kneip, T. J.; Lioy, P. J., eds. Aerosols: anthropogenic and natural,
sources and transport. Ann. N. Y. Acad. Sci. 338: 317-329.
Japar, S. M.; Brachaczek, W. W.; Gorse, R. A., Jr.; Norbeck, J. M.; Pierson, W. R. (1986) The contribution of
elemental carbon to the optical properties of rural atmospheric aerosols. Atmos. Environ. 20: 1281-1289.
John, W.; Wall, S. M.; Ondo, J. L.; Winklmayr, W. (1989) Acidic aerosol size distributions during SCAQS.
Sacramento, CA: California Air Resources Board; report no. CA/DOH/AIHL/SP-51.
John, W.; Wall, S. M.; Ondo, J. L.; Winklmayr, W. (1990) Modes in the size distributions of atmospheric
inorganic aerosol. Atmos. Environ. Part A 24: 2349-2359.
Johnson, R. L.; Shah, J. J.; Cary, R. A.; Huntzicker, J. J. (1981) An automated thermal-optical method for the
analysis of carbonaceous aerosol. In: Macias, E. S.; Hopke, P. K., eds. Atmospheric aerosol: source/air
quality relationships; based on a symposium jointly sponsored by the, Divisions of Nuclear Chemistry and
Technology at the 180th national meeting of the American Chemical Society; August 1980; Las Vegas,
NV. Washington, DC: American Chemical Society; pp. 223-233. (Comstock, M. J., ed. ACS
symposium series: 167).
Johnson, D. L.; Davis, B. L.; Dzubay, T. G.; Hasan, H.; Crutcher, E. R.; Courtney W. J.; Jaklevic, J. M.;
Thompson, A. C.; Hopke, P. K. (1984) Chemical and physical analyses of Houston aerosol for
interlaboratory comparison of source apportionment procedures. Atmos. Environ. 18: 1539-1553.
6-265
-------
Joseph, D. B.; Metsa, J.; Malm, W. C.; Pitchford, M. (1987) Plans for IMPROVE: a federal program to
monitor visibility in class I areas. In: Bhardwaja, P. S., ed. Visibility protection: research and policy
aspects, an APCA international specialty conference; September 1986; Grand Teton National Park, WY.
Pittsburgh, PA: Air Pollution Control Association; pp. 113-125. (APCA transactions series no. TR-10).
Kao, A. S.; Friedlander, S. K. (1994) Chemical signatures of the Los Angeles aerosol (dp<3.5 //m). Aerosol
Sci. Technol. 21: 283-293.
Kao, A. S.; Friedlander, S. K. (1995) Frequency distributions of PM10 chemical components and their sources.
Environ. Sci. Technol. 29: 19-28.
Karch, R.; Kruisz, C.; Reischl, G. P.; Winklmayr, W. (1987) Continuous measurement of ultrafine particle size
distributions hi the range from 2 to 200 nm from the southern California air quality study, June-July 1987
[preliminary report]. Vienna, Austria: Institut fur Experimentalphysik der Universitat Wien.
Keeler, G. J.; Brachaczek, W. W.; Gorse, R. A., Jr.; Japar, S. M.; Pierson, W. R. (1988) Effect of ambient
humidity on dichotomous sampler coarse/fine ratios. Atmos. Environ. 22: 1715-1720.
Keeler, G. J.; Japar, S. M.; Brachaczek, W. W.; Gorse, R. A., Jr.; Norbeck, J. M.; Pierson, W. R. (1990) The
sources of aerosol elemental carbon at Allegheny Mountain. Atmos. Environ. Part A 24: 2795-2805.
Keeler, G. J.; Spengler, J. D.; Castillo, R. A. (1991) Acid aerosol measurements at a suburban Connecticut site.
Atmos. Environ. Part A 25: 681-690.
Kelly, N. A.; Wolff, G. T.; Ferman, M. A. (1982) Background pollutant measurements in air masses affecting
the eastern half of the United States - 1. air masses arriving from the northwest. Atmos. Environ.
16: 1077-1088.
Kim, B. M.; Zeldin, M. D.; Liu, C. S. (1992) Source apportionment study for state implementation plan
development in the Coachella Valley. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and
nontraditional paniculate source controls, an A&WMA/EPA international specialty conference, v. II;
January; Scottsdale, AZ. Pittsburgh, PA: Air & Waste Management Association; pp. 979-991.
(A&WMA transactions series no. 22).
Kleinman, M. T.; Pasternack, B. S.; Eisenbud, M.; Kneip, T. J. (1980) Identifying and estimating the relative
importance of sources of airborne particulates. Environ. Sci. Technol. 14: 62-65.
Koutrakis, P. (1995) [PM2 5 and PM10 data for Philadelphia, 1992-1995]. Boston, MA: Harvard School of Public
Health.
Koutrakis, P.; Kelly, B. P. (1993) Equilibrium size of atmospheric aerosol sulfates as a function of particle
acidity and ambient relative humidity. J. Geophys. Res. [Atmos.] 98: 7141-7147.
Koutrakis, P.; Spengler, J. D. (1987) Source apportionment of ambient particles in Steubenville, OH using
specific rotation factor analysis. Atmos. Environ. 21: 1511-1519.
Kreidenweis, S. M. (1993) Towards development of a northern hemisphere natural sulfate aerosol budget.
Presented at: 86th annual meeting of the Air & Waste Management Association; June; Denver, CO.
Pittsburgh, PA: Air & Waste Management Association; paper no. 93-MP-4.08.
Kreidenweis, S.; Brechtel, F. (1995) [Particle number and size-distribution database]. Fort Collins, CO: Colorado
State University, Foothill Campus, Atmospheric Sciences Department.
6-266
-------
Lamborg, C.; Keeler, G. J.; Evans, G. (1992) Atmospheric acidity measurements during the Lake Michigan
Urban Air Toxics Study. Research Triangle Park, NC: U.S. Environmental Protection Agency,
Atmospheric Research and Exposure Assessment Laboratory; EPA report no. EPA/600/A-92/250.
Available from: NTIS, Springfield, VA; PB93-121069.
Lawson, D. R. (1990) The Southern California Air Quality Study. J. Air Waste Manage. Assoc. 40: 156-165.
Leaderer, B. P.; Bernstein, D. M.; Daisey, J. M.; Kleinman, M. T.; Kneip, T. J.; Knutson, E. O.;
Lippmann, M.; Lioy, P. J.; Rahn, K. A.; Sinclair, D.; Tanner, R. L.; Wolff, G. T. (1978)
Summary of the New York summer aerosol study (NYSAS). J. Air Pollut. Control Assoc. 28: 321-327.
Leaderer, B. P.; Tanner, R. L.; Holford, T. R. (1982) Diurnal variations, chemical composition and relation to
meteorological variables of the summer aerosol in the New York subregion. Atmos. Environ.
16: 2075-2087.
Lee, H. S.; Wadden, R. A.; Scheff, P. A. (1993) Measurement and evaluation of acid air pollutants hi Chicago
using an annular denuder system. Atmos. Environ. Part A 27: 543-553.
Lewis, C. W.; Dzubay, T. G. (1986) Measurement of light absorption extinction in Denver. Aerosol Sci.
Technol. 5: 325-336.
Lewis, C. W.; Macias, E. S. (1980) Composition of size-fractionated aerosol hi Charleston, West Virginia.
Atmos. Environ. 14: 185-194.
Lewis, C. W.; Baumgardner, R. E.; Stevens, R. K.; Russwurm, G. M. (1986) Receptor modeling study of
Denver whiter haze. Environ. Sci. Technol. 20: 1126-1136.
Li, Y.; Roth, H. D. (1995) Daily mortality analysis by using different regression models hi Philadelphia County,
1973-1990. In: Phalen, R. F.; Bates, D. V., eds. Proceedings of the colloquium on paniculate air
pollution and human mortality and morbidity; January 1994; Irvine, CA. Inhalation Toxicol. 7: 45-58.
Liang, C. S. K.; Waldman, J. M. (1992) Indoor exposures to acidic aerosols at child and elderly care facilities.
Indoor Ah- 2: 196-207.
Liousse, C.; Penner, J. E.; Chuang, C.; Walton, J. J.; Eddleman, H.; Cachier, H. (1996) A global
three-dimensional model study of carbonaceous aerosols. J. Geophys. Res. [Atmos.] 101: hi press.
Lioy, P. J.; Samson, P. J.; Tanner, R. L.; Leaderer, B. P.; Minnich, T.; Lyons, W. (1980) The distribution and
transport of sulfate "species" hi the New York metropolitan area during the 1977 summer aerosol study.
Atmos. Environ. 14: 1391-1407.
Lioy, P. J.; Daisey, J. M.; Greenberg, A.; Harkov, R. (1985) A major wintertime (1983) pollution episode hi
northern New Jersey: analyses of the accumulation and spatial distribution of inhalable paniculate matter,
extractable organic matter and other species. Atmos. Environ. 19: 429-436.
Lipfert, F. W.; Wyzga, R. E. (1993) On the spatial and temporal variability of aerosol acidity and sulfate
concentration. Air Waste 43: 489-491.
Liu, L.-J. S.; Burton, R.; Wilson, W. E.; Koutrakis, P. (1996) Comparison of aerosol acidity hi urban and
semi-rural environments. Atmos. Environ. 30: 1237-1245.
Lundgren, D. A. (1967) An aerosol sampler for determination of particle concentration as a function of size and
time. J. Air Pollut. Control Assoc. 17: 225-229.
6-267
-------
Macias, E. S.; Zwicker, J. O.; Ouimette, J. R.; Bering, S. V.; Friedlander, S. K.; Cahill, T. A.; Kuhlmey,
G. A.; Richards, L. W. (1981) Regional haze case studies in the southwestern U.S. -1. aerosol chemical
composition. In: White, W. H.; Moore, D. J.; Lodge, J. P., Jr., eds. Plumes and visibility:
measurements and model components, proceedings of the symposium; November 1980; Grand Canyon
National Park, AZ. Atmos. Environ. 15: 1971-1986.
Maenhaut, W.; Royset, O.; Vadset, M.; Kauppinen, E. I.; Lind, T. M. (1993) Analysis of size-fractionated coal
combustion aerosols by PIXE and other analytical techniques. Nucl. Instrum. Methods Phys. Res. Sect.
B 75: 266-272.
Malm, W. C.; Gebhart, K. A.; Molenar, J.; Cahill, T.; Eldred, R.; Huffman, D. (1994a) Examining the
relationship between atmospheric aerosols and light extinction at Mount Rainier and North Cascades
National Parks. Atmos. Environ. 28: 347-360.
Malm, W. C.; Sisler, J. F.; Huffman, D.; Eldred, R. A.; Cahill, T. A. (1994b) Spatial and seasonal trends in
particle concentration and optical extinction in the United States. J. Geophys. Res. [Atmos.]
99: 1347-1370.
Mangelson, N. F.; Rees, L. B.; Lewis, L.; Joseph, J. M.; Cui, W.; Machir, J.; Eatough, D. J.; Wilkerson,
T. D.; Jensen, D. T. (1994) The formation of sulfate and nitrate during whiter inversion fogs in Cache
Valley, Utah. In: Proceedings of an international specialty conference on aerosol and atmospheric optics:
radiative balance and visual air quality, volume A. Pittsburgh, PA: Air and Waste Management
Association.
Marple, V.; Rubow, K.; Ananth, G.; Fissan, H. J. (1986) Micro-orifice uniform deposit impactor. J. Aerosol
Sci. 17: 489-494.
Marple, V. A.; Rubow, K. L.; Behm, S. M. (1991) A microorifice uniform deposit impactor (MOUDI):
description, calibration, and use. Aerosol Sci. Technol. 14: 434-446.
Marshall, B. T.; Patterson, E. M.; Grams, G. W. (1986) Characterization of the Atlanta area aerosol, elemental
composition and possible sources. Atmos. Environ. 20: 1291-1300.
McMurry, P. H.; Stolzenburg, M. R. (1989) On the sensitivity of particle size to relative humidity for Los
Angeles aerosols. Atmos. Environ. 23: 497-507.
McMurry, P. H.; Zhang, X. Q. (1989) Size distributions of ambient organic and elemental carbon. Aerosol Sci.
Technol. 10: 430-437.
Mercer, T. T. (1964) The stage constants of cascade impactors. Ann. Occup. Hyg. 7: 115-124.
Molenar, J. V.; Dietrich, D. L.; Cismoski, D. S.; Cahill, T. A.; Wakabayashi, P. H. (1994) In: Proceedings of
an international specialty conference on aerosol and atmospheric optics: radiative balance and visual air
quality, volume A. Pittsburgh, PA: Air & Waste Management Association.
Moyers, J. L. (1982) 1981-1982 aerosol studies for nine southwest national parks and monuments. Washington,
DC: U.S. Department of the Interior, National Park Service, Southwest Region.
Mukerjee, S.; Fox, D. L.; Stevens, R. K.; Shy, C. M.; Vescio, N.; Lumpkin, T. A.; Kellogg, R. B. (1993)
A methodology to apportion ambient air measurements to investigate potential effects on air quality near
waste incinerators. Research Triangle Park, NC: U.S. Environmental Protection Agency, Atmospheric
Research and Exposure Assessment Laboratory; report no. EPA/600/A-93/104. Available from: NTIS,
Springfield, VA; PB93-191393.
6-268
-------
Mylonas, D. T.; Allen, D. T.; Ehnnan, S. H.; Pratsinis, S. E. (1991) The sources and size distributions of
organonitrates in Los Angeles aerosol. Atmos. Environ. Part A 25: 2855-2861.
Natusch, D. F. S.; Wallace, J. R. (1974) Urban aerosol toxicity: the influence of particle size. Particle size,
adsorption, and respiratory deposition profiles combine to determine aerosol toxicity. Science
(Washington, DC) 186: 695-699.
Natusch, D. F. S.; Wallace, J. R.; Evans, C. A., Jr. (1974) Toxic trace elements: preferential concentration in
respirable particles. Science (Washington, DC) 183: 202-204.
Neas, L. M. (1996) [Data provided for 1986 from Harvard six cities data base.] Boston, MA: Harvard School of
Public Health.
Noll, K. E.; Pontius, A.; Frey, R.; Gould, M. (1985) Comparison of atmospheric coarse particles at an urban and
non-urban site. Atmos. Environ. 19: 1931-1943.
Noll, K. E.; Draftz, R.; Fang, K. Y. P. (1987) The composition of atmospheric coarse particles at an urban and
non-urban site. Atmos. Environ. 21: 2717-2721.
Noll, K. E.; Yuen, P.-F.; Fang, K. Y.-P. (1990) Atmospheric coarse paniculate concentrations and dry
deposition fluxes for ten metals in two urban environments. Atmos. Environ. Part A 24: 903-908.
Patterson, R. K.; Wagman, J. (1977) Mass and composition of an urban aerosol as a function of particle size for
several visibility levels. J. Aerosol Sci. 8: 269-279.
Pickle, T.; Allen, D. T.; Pratsinis, S. E. (1990) The sources and size distributions of aliphatic and carbonyl
carbon in Los Angeles aerosol. Atmos. Environ. Part A 24: 2221-2228.
Pierson, W. R.; Brachaczek, W. W. (1988) Coarse- and fine-particle atmospheric nitrate and HNO3(g) in
Claremont, California, during the 1985 Nitrogen Species Methods Comparison Study. Atmos. Environ.
22: 1665-1668.
Pierson, W. R.; Russell, P. A. (1979) Aerosol carbon hi the Denver area hi November 1973. Atmos. Environ.
13: 1623-1628.
Pierson, W. R.; Brachaczek, W. W.; Korniski, T. J.; Truex, T. J.; Butler, J. W. (1980a) Artifact formation of
sulfate, nitrate, and hydrogen ion on backup filters: Allegheny Mountain experiment. J. Air Pollut.
Control Assoc. 30: 30-34.
Pierson, W. R.; Brachaczek, W. W.; Truex, T. J.; Butler, J. W.; Korniski, T. J. (1980b) Ambient sulfate
measurements on Allegheny Mountain and the question of atmospheric sulfate hi the northeastern United
States. Ann. N. Y. Acad. Sci. 338: 145-173.
Pierson, W. R.; Brachaczek, W. W.; Gorse, R. A., Jr.; Japar, S. M.; Norbeck, J. M. (1986) On the acidity of
dew. J. Geophys. Res. [Atmos]. 91: 4083-4096.
Pierson, W. R.; Brachaczek, W. W.; Gorse, R. A., Jr.; Japar, S. M.; Norbeck, J. M.; Keeler, G. J. (1987) Acid
rain and atmospheric chemistry at Allegheny Mountain. Environ. Sci. Technol. 21: 679-691.
Pierson, W. R.; Brachaczek, W. W.; Gorse, R. A., Jr.; Japar, S. M.; Norbeck, J. M.; Keeler, G. J. (1989)
Atmospheric acidity measurements on Allegheny Mountain and the origins of ambient acidity in the
northeastern United States. Atmos. Environ. 23: 431-459.
6-269
-------
Pinto, J. P.; Pleasant, M.; Kellogg, R.; Torok, Sz.; Stiles, D.; Willis, R. D.; Koutrakis, P.; Allen, G. A. (1995)
Chemical characterization of the ambient aerosol in Philadelphia. Presented at: Paniculate matter: health
and regulatory issues: an A&WMA international specialty conference; April; Pittsburgh, PA. Pittsburgh,
PA: Air & Waste Management Association; submitted abstract.
Placet, M.; Battye, R. E.; Fehsenfeld, F. C.; Bassett, G. W. (1991) Emissions involved in acidic deposition
processes. In: Irving, P. M., ed. Acidic deposition: state of science and technology, volume 1:
emissions, atmospheric processes, and deposition. Washington, DC: The U.S. National Acid
Precipitation Assessment Program. (State of science and technology report no. 1).
Poirot, R. L.; Flocchini, R. G.; Husar, R. B. (1990) Winter fine particle composition in the northeast:
preliminary results from the NESCAUM monitoring network. Presented at: 83rd annual meeting of the
Air & Waste Management Association; June; Pittsburgh, PA. Pittsburgh, PA: Air & Waste Management
Association; paper no. 90-84.5.
Poirot, R. L.; Galvin, P. J.; Gordon, N.; Quan, S.; Van Arsdale, A.; Flocchini, R. G. (1991) Annual and
seasonal fine particle composition in the northeast: second year results from the NESCAUM monitoring
network. Presented at: 84th annual meeting and exhibition of the Air & Waste Management Association;
June; Vancouver, BC, Canada. Pittsburgh, PA: Air & Waste Management Association; paper no.
91-49.1.
Pope, C. A., Ill; Schwartz, J.; Ransom, M. R. (1992) Daily mortality and PM10 pollution in Utah valley. Arch.
Environ. Health 47: 211-217.
Raabe, O. G.; Braaten, D. A.; Axelbaum, R. L.; Teague, S. V.; Cahill, T. A. (1988) Calibration studies of the
drum impactor. J. Aerosol Sci. 19: 183-195.
Reid, J. S.; Cahill, T. A.; Wakabayashi, P. H.; Dunlap, M. R. (1994) Geometric/aerodynamic equivalent
diameter ratios of ash aggregate aerosols collected in burning Kuwaiti well fields. Atmos. Environ.
28: 2227-2234.
Rodes, C. E.; Evans, E. G. (1985) Preliminary assessment of 10 ^m paniculate sampling at eight locations in the
United States. Atmos. Environ. 19: 293-303.
Rogge, W. F.; Mazurek, M. A.; Hildemann, L. M.; Cass, G. R.; Simoneit, B. R. T. (1993) Quantification of
urban organic aerosols at a molecular level: identification, abundance and seasonal variation. Atmos.
Environ. Part A 27: 1309-1330.
Russell, A. G.; Cass, G. R. (1986) Verification of a mathematical model for aerosol nitrate and nitric acid
formation and its use for control measure evaluation. Atmos. Environ. 20: 2011-2025.
Schichtel, B. A.; Husar, R. B. (1991) Apportionment of light extinction by aerosol types over the U.S. Hawscom
Air Force Base, MA: Air Force Systems Command, Phillips Laboratory; scientific report no. 4.
Schwartz, J. (1994) Air pollution and hospital admissions for the elderly in Birmingham, Alabama. Am. J.
Epidemiol. 139: 589-598.
Schwartz, J.; Dockery, D. W. (1992) Increased mortality hi Philadelphia associated with daily air pollution
concentrations. Am. Rev. Respir. Dis. 145: 600-604.
Seaton, A.; MacNee, W.; Donaldson, K.; Godden, D. (1995) Paniculate air pollution and acute health effects.
Lancet (8943): 176-178.
6-270
-------
Seeker, W. R. (1990) Waste combustion. In: Proceedings of the 23rd international symposium on combustion;
pp. 867-885.
Seinfeld, J. H. (1986) Atmospheric chemistry and physics of air pollution. New York, NY: John Wiley and Sons.
Senior, C. L.; Flagan, R. C. (1982) Ash vaporization and condensation during combustion of a suspended coal
particle. Aerosol Sci. Technol. 1: 371-383.
Shah, J. J.; Watson, J. G., Jr.; Cooper, J. A.; Huntzicker, J. J. (1984) Aerosol chemical composition and light
scattering in Portland, Oregon: the role of carbon. Atmos. Environ. 18: 235-240.
Shaw, R. W., Jr.; Paur, R. J. (1983) Composition of aerosol particles collected at rural sites in the Ohio River
Valley. Atmos. Environ. 17: 2031-2044.
Sisler, J. F.; Malm, W. C. (1994) The relative importance of soluble aerosols to spatial and seasonal trends of
impaired visibility in the United States. Atmos. Environ. 28: 851-862.
Sisler, J. F.; Huffman, D.; Lattimer, D. A.; Malm, W. C.; Pitchford, M. L. (1993) Spatial and temporal
patterns and the chemical composition of the haze in the United States: an anlysis of data from the
IMPROVE network, 1988-1991. Fort Collins, CO: Colorado State University, Cooperative Institute for
Research in the Atmosphere (CIRA).
Skidmore, L. W.; Chow, J. C.; Tucker, T. T. (1992) PM10 air quality assessment for the Jefferson County,
Ohio air quality control region. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional
paniculate source controls, an A&WMA/EPA international specialty conference, v. II; January;
Scottsdale, AZ. Pittsburgh, PA: Air and Waste Management Association; pp. 1016-1031. (A&WMA
transactions series no. 22).
Sloane, C. S.; Watson, J.; Chow, J.; Pritchett, L.; Richards, L. W. (1991) Size-segregated fine particle
measurements by chemical species and their impact on visibility impairment in Denver. Atmos. Environ.
Part A 25: 1013-1024.
Small, M.; Germani, M. S.; Small, A. M.; Zoller, W. H.; Moyers, J. L. (1981) Airborne plume study of
emissions from the processing of copper ores in southeastern Arizona. Environ. Sci. Technol.
15: 293-299.
Solomon, P. A.; Moyers, J. L. (1986) A chemical characterization of wintertime haze in Phoenix, Arizona.
Atmos. Environ. 20: 207-213.
Solomon, P. A.; Fall, T.; Salmon, L.; Cass, G. R.; Gray, H. A.; Davidson, A. (1989) Chemical characteristics
of PM10 aerosols collected in the Los Angeles area. JAPCA 39: 154-163.
Spengler, J, D.; Thurston, G. D. (1983) Mass and elemental composition of fine and coarse particles in six U.S.
cities. J. Air Pollut. Control Assoc. 33: 1162-1171.
Spengler, J. D.; Allen, G. A.; Foster, S.; Severance, P.; Ferris, B., Jr. (1986a) Sulfuric acid and sulfate aerosol
events in two U. S. cities. In: Lee, S. D.; Schneider, T.; Grant, L. D.; Verkerk, P. J., eds. Aerosols:
research, risk assessment and control strategies - proceedings of the second U.S.-Dutch international
symposium; May 1985; Williamsburg, VA. Chelsea, MI: Lewis Publishers, Inc.; pp. 107-120.
Spengler, J. D.; Briggs, S. L. K.; Ozkaynak, H. (1986b) Relationship between TSP measurements and
size-fractionated particle mass measurements in six cities participating in the Harvard Air Pollution
Health Study. Research Triangle Park, NC: U.S. Environmental Protection Agency, Office of Air
Quality Planning and Standards; EPA cooperative agreement no. CR-812667-01-0; December 5.
6-271
-------
Spengler, J. D.; Brauer, M.; Koutrakis, P. (1990) Acid air and health. Environ. Sci. Technol. 24: 946-956.
Stevens, R. K. (1985) Sampling and analysis methods for use in source apportionment studies to determine impact
of wood burning on fine particle mass. Environ. Int. 11: 271-283.
Stevens, R. K. (1995) [Unpublished data].
Stevens, R. K.; Dzubay, T. G.; Shaw, R. W., Jr.; McClenny, W. A.; Lewis, C. W.; Wilson, W. E. (1980)
Characterization of the aerosol hi the Great Smoky Mountains. Environ. Sci. Technol. 14: 1491-1498.
Stevens, R. K.; Dzubay, T. G.; Lewis, C. W.; Shaw, R. W., Jr. (1984) Source apportionment methods applied
to the determination of the origin of ambient aerosols that affect visibility in forested areas. Atmos.
Environ. 18: 261-272.
Stevens, R. K.; Hoffman, A. J.; Baugh, J. D.; Lewis, C. W.; Zweidinger, R. B.; Cupitt, L. T.; Kellogg, R. B.;
Simonson, J. H. (1993) A comparison of air quality measurements in Roanoke, VA, and other integrated
air cancer project monitoring locations. In: Measurement of toxic and related air pollutants: proceedings
of the 1993 U.S. EPA/A&WMA international symposium; May; Durham, NC. Pittsburgh, PA: Air &
Waste Management Association; pp. 185-189. (A&WMA specialty conference VIP-34).
Sun, H. H.; Spengler, J. D.; Koutrakis, P. (1992) Personal exposures to acid aerosols and ammonia. Environ.
Sci. Technol. 26: 2507-2517.
Suh, H. H.; Koutrakis, P.; Spengler, J. D. (1993) Validation of personal exposure models for sulfate and aerosol
strong acidity. J. Air Waste Manage. Assoc. 43: 845-850.
Suh, H. H.; Koutrakis, P.; Spengler, J. D. (1994) The relationship between airborne acidity and ammonia in
indoor environments. J. Exposure Anal. Environ. Epidemiol. 4: 1-23.
Suh, H. H.; Allen, G. A.; Koutrakis, P.; Burton, R. M. (1995) Spatial variation in acidic sulfate and ammonia
concentrations within metropolitan Philadelphia. J. Air Waste Manage. Assoc. 45: 442-452.
Thanukos, L. C.; Miller, T.; Mathai, C. V.; Reinholt, D.; Bennett, J. (1992) Intercomparison of PM10 samplers
and source apportionment of ambient PMjo concentrations at Rillito, Arizona. In: Chow, J. C.; Ono,
D. M., eds. PM10 standards and nontraditional paniculate source controls, an A&WMA/EPA
international specialty conference, v. I; January; Scottsdale, AZ. Pittsburgh, PA: Air & Waste
Management Association; pp. 244-261. (A&WMA transactions series no. 22).
Thompson, K. M.; Koutrakis, P.; Brauer, M.; Spengler, J. D.; Wilson, W. E.; Burton, R. M. (1991)
Measurements of aerosol acidity: sampling frequency, seasonal variability, and spatial variation.
Presented at: 84th annual meeting and exhibition of the Air & Waste Management Association; June;
Vancouver, BC, Canada. Pittsburgh, PA: Air & Waste Management Association; paper no. 91-89.5.
Thurston, G. D.; Gorczynski, J. E., Jr.; Jaques, P.; Currie, J.; He, D. (1992) An automated sequential sampling
system for paniculate acid aerosols: description, characterization, and field sampling results. J. Exposure
Anal. Environ. Epidemiol. 2: 415-428.
Trijonis, J. (1982) Existing and natural background levels of visibility and fine particles hi the rural East. Atmos.
Environ. 16: 2431-2445.
6-272
-------
Trijonis, J. C. (1991) Visibility: existing and historical conditions-causes and effects. Appendix A:
characterization of natural background aerosol concentrations. In: Irving, P. M., ed. Acidic deposition:
state of science and technology, volume HI: terrestrial, materials, health and visibility effects.
Washington, DC: The U.S. National Acid Precipitation Assessment Program; pp. 24-A1 - 24-AT. (State
of science and technology report no. 24).
Trijonis, J.; McGown, M.; Pitchford, M.; Blumenthal, D.; Roberts, P.; White, W.; Macias, E.; Weiss, R.;
Waggoner, A.; Watson, J.; Chow, J.; Flocchini, R. (1988) Visibility conditions and causes of visibility
degradation in the Mojave Desert of California: executive summary, RESOLVE project final report.
China Lake, CA: Department of the Navy, Naval Weapons Center; document no. NWC TP 6869.
Available from: NTIS, Springfield, VA; AD-A206 322.
Tuncel, S. G.; Olmez, I.; Parrington, J. R.; Gordon, G. E.; Stevens, R. K. (1985) Composition of fine particle
regional sulfate component in Shenandoah Valley. Environ. Sci. Technol. 19: 529-537.
Turpin, B. J.; Huntzicker, J. J. (1991) Secondary formation of organic aerosol in the Los Angeles basin:
a descriptive analysis of organic and elemental carbon concentrations. Atmos. Environ. Part A
25: 207-215.
Turpin, B. J.; Gary, R. A.; Huntzicker, J. J. (1990) An in situ, time-resolved analyzer for aerosol organic and
elemental carbon. Aerosol Sci. Technol. 12: 161-171.
Turpin, B. J.; Huntzicker, J. J.; Larson, S. M.; Cass, G. R. (1991) Los Angeles summer midday paniculate
carbon: primary and secondary aerosol. Environ. Sci. Technol. 25: 1788-1793.
U.S. Environmental Protection Agency. (1989) An acid aerosols issue paper: health effects and aerometrics.
Research Triangle Park, NC: Office of Health and Environmental Assessment, Environmental Criteria
and Assessment Office; EPA report no. EPA-600/8-88-005F. Available from: NTIS, Springfield, VA;
PB91-125864.
Van Grieken, R. E.; Johansson, T. B.; Winchester, J. W.; Odom, L. A. (1975) Micro-determination of
zirconium-hafnium ratios in zircons by proton induced X-ray emission. Z. Anal. Chem. 275: 343-348.
Vermette, S. J.; Williams, A. L.; Landsberger, S. (1992) PM10 source apportionment using local surface dust
profiles: examples from Chicago. In: Chow, J. C.; Ono, D. M., eds. PM10 standards and nontraditional
paniculate source controls, an A&WMA/EPA international specialty conference, v. I; January;
Scottsdale, AZ. Pittsburgh, PA: Air & Waste Management Association; pp. 262-278. (A&WMA
transactions series no. 22).
Vossler, T. L.; Lewis, C. W.; Stevens, R. K.; Dzubay, T. G.; Gordon, G. E.; Tuncel, S. G.; Russwurm,
G. M.; Keeler, G. J. (1989) Composition and origin of summertime air pollutants at Deep Creek Lake,
Maryland. Atmos. Environ. 23: 1535-1547.
Waldman, J. M.; Lioy, P. J.; Thurston, G. D.; Lippmann, M. (1990) Spatial and temporal patterns in
summertime sulfate aerosol acidity and neutralization within a metropolitan area. Atmos. Environ. Part B
24: 115-126.
Waldman, J. M.; Liang, S.-K. C.; Lioy, P. J.; Thurston, G. D.; Lippmann, M. (1991) Measurements of sulfate
aerosol and its acidity in the SO2 source region of Chestnut Ridge, PA. Atmos. Environ. Part A
25: 1327-1333.
6-273
-------
Waldman, J. M.; Koutrakis, P.; Allen, G. A.; Thurston, G. D.; Burton, R. M.; Wilson, W. E. (1995) Human
exposures to particle strong acidity. In: Phalen, R. F.; Bates, D. V., eds. Proceedings of the colloquium
on paniculate air pollution and human mortality and morbidity, part II; January 1994; Irvine, CA.
Inhalation Toxicol. 7: 657-669.
Wall, S. M.; John, W.; Ondo, J. L. (1988) Measurement of aerosol size distributions for nitrate and major ionic
species. Atmos. Environ. 22: 1649-1656.
Wang, H.-C.; John, W. (1988) Characteristics of the Berner impactor for sampling inorganic ions. Aerosol Sci.
Technol. 8: 157-172.
Watson, J. G.; Chow, J. C.; Richards, L. W.; Neff, W. D.; Andersen, S. R.; Dietrich, D. L.; Houck, J. E.;
Olnez, I. (1988) The 1987-88 metro Denver brown cloud study: v. I, II, III. Reno, NV: Desert Research
Institute; final report no. 8810.1F(l-3).
Watson, J. G.; Chow, J. C.; Lu, Z.; Fujita, E. M.; Lowenthal, D. H.; Lawson, D. R.; Ashbaugh, L. L. (1994a)
Chemical mass balance source apportionment of PM10 during the Southern California Air Quality Study.
Aerosol Sci. Technol. 21: 1-36.
Watson, J. G.; Roth, P. M.; Blumenthal, D. L.; Ranzieri, A. J.; Solomon, P. A.; Thuillier, R. H. (1994b)
Recommendations on planning a large-scale combined monitoring and modeling effort based on the
SJVAQS/AUSPEX air quality study. In: Solomon, P. A.; Silver, T. A., eds. Planning and managing
regional air quality modeling and measurement studies: a perspective through the San Joaquin Valley air
quality study and AUSPEX. Boca Raton, FL: Lewis Publishers; pp. 369-382.
Weber, R. J.; McMurry, P. H.; Eisele, F. L.; Tanner, D. J. (1995) Measurement of expected nucleation
precursor species and 5 to 500 nm diameter particles at Mauna Loa, Hawaii. J. Atmos. Sci.
52: 2242-2257.
Weiss, R. E.; Larson, T. V.; Waggoner, A. P. (1982) In situ rapid-response measurement of ^SO^NH^SC^
aerosols in rural Virginia. Environ. Sci. Technol. 16: 525-532.
Wesolowski, J. J.; John, W.; Devor, W.; Cahill, T. A.; Feeney, P. J.; Wolfe, G.; Flocchini, R. (1977)
Collection surfaces of cascade impactors. In: Dzubay, T. G., ed. X-ray fluorescence analysis of
environmental samples. Ann Arbor, MI: Ann Arbor Science Publishers, Inc.; pp. 121-131.
Whitby, K. T. (1978) The physical characteristics of sulfur aerosols. Atmos. Environ. 12: 135-159.
Whitby, K. T.; Sverdrup, G. M. (1980) California aerosols: their physical and chemical characteristics. In: Hidy,
G. M.; Mueller, P. K.; Grosjean, D.; Appel, B. R.; Wesolowski, J. J., eds. The character and origins
of smog aerosols: a digest of results from the California Aerosol Characterization Experiment (ACHEX).
New York, NY: John Wiley & Sons, Inc.; pp. 477-517. (Advances hi environmental science and
technology: v. 9).
Whitby, K. T.; Husar, R. B.; Liu, B. Y. H. (1972) The aerosol size distribution of Los Angeles smog.
J. Colloid Interface Sci. 39: 177-204.
White, W. H. (1996a) Alternative perspectives on a trend hi eastern fine-particle sulfur concentrations. Environ.
Manager: hi press.
White, W. H. (1996b) Deteriorating air or improving measurements?—on interpreting concatenate time series.
J. Geophys. Res. [Atmos.]: submitted.
6-274
-------
White, W. H.; Marias, E. S. (1987) Particulate nitrate measurements in rural areas of the western United States.
Atmos. Environ. 21: 2563-2571.
White, W. H.; Macias, E. S. (1989) Carbonaceous particles and regional haze in the western United States.
Aerosol Sci. Technol. 10: 111-117.
Willeke, K.; Whitby, K. T. (1975) Atmosperic aerosols: size distribution interpretation. J. Air Pollut. Control
Assoc. 25: 529-534.
Wilson, W. E.; Stockburger, L. (1990) Diurnal variations in aerosol composition and concentration.
In: Masuda, S.; Takahashi, K., eds. Aerosols: science, industry, health and environment: proceedings of
the third international aerosol conference, v. 2; September; Kyoto, Japan. Oxford, United Kingdom:
Pergamon Press pic; pp. 962-965.
Wilson, W. E.; Suh, H. H. (1996) Fine and coarse particles: concentration relationships relevant to
epidemiological studies. J. Air Waste Manage. Assoc.: accepted.
Wilson, W. E.; Koutrakis, P.; Spengler, J. D. (1991) Diurnal variations of aerosol acidity, sulfate, and ammonia
in the atmosphere. Presented at: 84th annual meeting and exhibition of the Air & Waste Management
Association; June; Vancouver, BC, Canada. Pittsburgh, PA: Air & Waste Management Association;
paper no. 91-89.9.
Wolff, G. T.; Korsog, P. E. (1985) Estimates of the contributions of sources to inhalable paniculate
concentrations hi Detroit. Atmos. Environ. 19: 1399-1409.
Wolff, G. T.; Monson, P. R.; Ferman, M. A. (1979) On the nature of the diurnal variation of sulfates at rural
sites hi the Eastern United States. Environ. Sci. Technol. 13: 1271-1276.
Wolff, G. T.; Countess, R. J.; Groblicki, P. J.; Ferman, M. A.; Cadle, S. H.; Muhlbaier, J. L. (1981)
Visibility-reducing species in the Denver "brown cloud"~II. sources and temporal patterns. Atmos.
Environ. 15: 2485-2502.
Wolff, G. T.; Ferman, M. A.; Kelly, N. A.; Stroup, D. P.; Ruthkosky, M. S. (1982) The relationships between
the chemical composition of fine particles and visibility hi the Detroit metropolitan area. J. Air Pollut.
Control Assoc. 32: 1216-1220.
Wolff, G. T.; Kelly, N. A.; Ferman, M. A.; Morrissey, M. L. (1983) Rural measurements of the chemical
composition of airborne particles in the eastern United States. J. Geophys. Res. C: Oceans Atmos.
88: 10,769-10,775.
Wolff, G. T.; Korsog, P. E.; Stroup, D. P.; Ruthkosky, M. S.; Morrissey, M. L. (1985) The influence of local
and regional sources on the concentration of inhalable paniculate matter hi southeastern Michigan.
Atmos. Environ. 19: 305-313.
Wolff, G. T.; Ruthkosky, M. S.; Stroup, D. P.; Korsog, P. E.; Ferman, M. A.; Wendel, G. J.; Stedman, D. H.
(1986) Measurements of SOX, NOX and aerosol species on Bermuda. Atmos. Environ. 20: 1229-1239.
Wolff, G. T.; Ruthkosky, M. S.; Stroup, D. P.; Korsog, P. E. (1991) A characterization of the principal PM-10
species hi Claremont (summer) and Long Beach (fall) during SCAQS. Atmos. Environ. Part A
25: 2173-2186.
Wyzga, R. E.; Lipfert, F. W. (1996) [Philadelphia TSP data.] Palo Alto, CA: Electric Power Research Institute.
6-275
-------
Zhang, X.; Turpin, B. J.; McMurry, P. J.; Herring, S. V.; Stolzenburg, M. R. (1994) Mie theory evaluation of
species contributions to the 1990 wintertime visibility reduction in the Grand Canyon. J. Air Waste
Manage. Assoc. 44: 153-162.
6-276
-------
APPENDIX 6A:
TABLES OF CHEMICAL COMPOSITION OF
PARTICIPATE MATTER
6A-1
-------
TABLE 6A-la. SUMMARY OF PM2 s STUDIES
EAST
Smoky Mtn.
Shenandoah
Camden
Philadelphia
Deep Creek
Roanoke
Raleigh
Watertown
Hartford
Boston
Res.Tr. Pk.
Charlotte
Allegheny Mtn.
Allegheny Mtn.
Laurel Hill
REF
1
1
2
3
4
5
5
6,7
8
8
8
20
44
45-50
45-50
NOTE WEST
Boise
Tarrant CA
b Five Points CA
Riverside CA
c San Jose
d Honolulu
d Winnemucca NV
Portland
a Seattle
a Southern California
a San Joaquin Valley
e Phoenix
Nevada
REF
5
8
8
8
8
8
8
8
8
9,31
10
11
12
NOTE CENTRAL
d Albuquerque
a St. Louis
a Steubenville
a Harriman
a Portage
a Topeka
a Inglenook AL
a Braidwood IL
a Kansas City KS
g,h Minneapolis
i St. Louis
j Kansas City MO
f Akron
Cincinnati
Buffalo
Dallas
El Paso
Denver
Urban Denver
Non-urban
Denver
Chicago
Houston
St.Louis
Harriman
St. Louis
Steubenville
Brownsville
Ontario
REF
5
6,7
6,7
6,7
6,7
6,7
8
8
8
8
8
8
8
8
8
8
8
13
14
14
15
16
17
17
18
21
24
37
NOTE
d
a
a
a
a
a
a
a
a
a
a
a
m
aa
k
n
1
6A-2
-------
TABLE 6A-lb. SUMARY OF COARSE FRACTION STUDIES
EAST
Smoky Mtn.
Shenandoah
Camden
Philadelphia
Watertown
Hartford
Boston
Res.Tr. Pk.
Allegheny Mtn.
Allegheny Mtn.
Laurel Hill
REF NOTE
1 0
1 0
2 b
3 ab
6,7 o,p
8 a,o
8 a,o
8 a,o
44
45-50
45-50
WEST
Tarrant CA
Five Points CA
Riverside CA
San Jose
Honolulu
Winnemucca NV
Portland
Seattle
Southern California
San Joaquin Valley
Phoenix
REF
8
8
8
8
8
8
8
8
9,31
10
11
NOTE
a,o
a,o
a,o
a,o
a,o
a,o
a,o
a,o
g
i
j
CENTRAL
St. Louis
Steubenville
Harriman
Portage
Topeka
Inglenook AL
Braidwood IL
Kansas City KS
Akron
Cincinnati
Buffalo
Dallas
El Paso
Denver
Chicago
Houston
St. Louis
Harriman
St. Louis
Brownsville
Ontario
REF
6,7
6,7
6,7
6,7
6,7
8
8
8
8
8
8
8
8
13
15
16
17
17
18
24
37
NOTE
o.p
o,p
o,p
o,p
o.p
a,o
a,o
a,o
a,o
a,o
a,o
a,o
a,o
0
s
o
k,r
n
1
6A-3
-------
TABLE 6A-lc. SUMMARY OF PM10 STUDIES
EAST
Smoky Mtn.
Shenandoah
Camden
Philadelphia
Kingston
Watertown
Hartford
Boston
Res.Tr. Pk.
Allegheny Mtn.
Allegheny Mtn.
Laurel Hill
REF NOTE
1 o,q
1 o,q
2 b
3 ab
6,7 p,q
6,7 p,q
8 a,q
8 a,q
8 a,q
44
45-50
45-50
WEST
Tarrant CA
Five Points CA
Riverside CA
San Jose CA
Honolulu HI
Winnemucca NV
Portland OR
Seattle
Southern California
San Joaquin Valley
Phoenix
San Fran. Bay
San Jose
Palm Springs
Pocatello, ID
Tuscon
Rillito, AZ
REF
8
8
8
8
8
8
8
8
9,31
10
11
29
29
38
39
40
42
NOTE
a,q
a,q
a,q
a,q
a,q
a,q
a,q
a,q
g,h
i
j
V
w
t
u
CENTRAL
St. Louis
Harriman
Steubenville
Portage
Topeka
Inglenook AL
Braidwood IL
Kansas City KS
Minneapolis
St. Louis
Kansas City MO
Akron
Cincinnati
Buffalo
Dallas
El Paso
Denver
Chicago
Houston
St. Louis
Harriman
St. Louis
Brownsville
Utah Valley
Ontario
SE Chicago, IL
Ohio
REF
6,7
6,7
6,7
6,7
6,7
8
8
8
8
8
8
8
8
8
8
8
13
15
16
17
17
18
24
26
37
41
43
NOTE
p,q
p,q
p,q
p,q
p,q
a,q
a,q
a,q
a,q
a,q
a,q
a,q
a,q
a,q
a,q
a,q
q
s
q
X
1
y
6A-4
-------
FOOTNOTES FOR TABLES 6A-la THROUGH 6A-2c
a. Inhalable Particle Network (IPN) Data. Only represents days of elevated concentrations—dichot filter
loadings >50 /tg/cm2.
b. Data from Site 28 only.
c. Average of all 6-h samples.
d. Avg over all day/nite samples.
e. Average of all 12-h samples at 2 incin. sites and 2 background sites. Only XRF values which
exceeded associated uncertainties more than half the time at all four sites were included.
f. Average from Sparks site and Reno site.
g. Sampling only during intensive episodes.
h. Averages based on 12-h day/nite samples. There were 59 sampling days at Claremont and 23 sampling
days at Long Beach.
i. Avg over all sites: Stockton, Crow's Landing, Fresno, Kem, Fellows, and Bakersfield.
j. Average of Central Phoenix, West Phoenix, and Scottsdale sites.
k. Avg of RAPS site 106.
1. Average from Walpole, Windsor 1, and Windsor 2 sites.
m. Avg of 3 urban sites: Auraria, Federal, and Welby.
n. Median VAPS values from Central site.
o. 2.5-15 iaa.
p. Coarse concentrations may be 30% or more underestimated due to losses from handling filters.
q. PM15.
r. 2.4-20 ftm.
s. No upper size cutoff on VAPS inlet.
t. Average of Palm Springs and Indio, CA.
u. Avg. of Downtown Tuscon, Orange Grove, Craycroft, and Corona de Tuscon sites.
v. Mean of annual avgs (1988-1992) from ~9 sites in Alameda, San Francisco, and Santa Clara counties.
w. 24-h average of day/nite concentrations at two sites in San Jose.
x. PM20. Average from RAPS site 106.
y. Avg. of Follansbee, Mingo, Sewage Plant, Steubenville, and WTOV Tower sites in Ohio.
z. Average of urban sites: Fresno, Bakersfield and Stockton.
aa. Average of nonurban sites: Brighton and Tower.
ab. Castor Avenue site only.
6A-5
-------
APPENDIX FOR TABLES 6A-la THROUGH 6A-2c. BIBLIOGRAPHY FOR PM STUDIES
Ref No.
Sites
Dates
Types of Samples
Data
Comments
>
1) Smoky Mtn.
2) Shenandoah Valley
3) Abastumani Mtn.
Philadelphia - 3 sites
Philadelphia
Deep Creek Lake
1) Albuquerque
2) Raleigh
3) Boise
4) Roanoke
Portage,
Topeka,Harriman,
Kingston, St. Louis,
Steubenville, Watertown
1) Sept 1978
2) Jul-Aug 1980
3) Mar 24-Jul 1979
Jul 14-Aug 13 1982
Jul 25-Aug 14 1994
August, 1983
1) Dec 1984-Mar 1985
2) Jan 1985-Mar 1985
3) Dec 1986-Mar 1987
4) Oct 1988-Feb 1989
1979-1981
Multi-season
F+C(2.5-15), EC, OC,
SO^, Nitrate. 12-h
samples.
F+C(2.5-10), EC, OC,
S04=, NOj. 12-h (0600-
1800) and (1800-0600).
Fine mass, elements, OC,
EC, SD, uncert., from 4
sites
Day/nite sampling (1000-
2200, 2200-1000).
Dichots. FM, CM, OC, EC,
Gases, FP nitrate
F & C (2.5-10) + Carbon,
EOM, VOCs. 12-h samples,
Day/night:
0700-1900,1900-0700.
FP & IP(2.5-15). 24-h
(midnite-midnite), every
other day. No Carbon data.
1) Comparison of avg F&C
composition for 3 sites.
1) F+C composition at site 28.
2) 9-source CMB source app. for
site 28.
3) Mass Balance for 3 sites.
1) Measured PM2 5 mass, OC, EC,
elements, SD, unc. at each site.
1) Mean FP mass, OC, EC, nitrate,
elements stratified by day/nite/all.
1) Mean comp. of F mass, EC,
OC EOM, at 4 sites. 2) daytime/
nightime/24-havgs for key species
at 4 sites.
1) Mean-t-SE by city for F+C
mass, metals.
2) Box-line plots by city showing
means and percentiles for F+C
mass, sulfate, Cl.
3) Time-series plots of F+C mass
& tot Sulfate.
4) Data summaries only-no raw
data.
No CP data
presented;
Sampling only in
winter; focus on
woodstove
impact
Source of info
on geographical
and temporal PM
composition
variability.
-------
APPENDIX FOR TABLES 6A-la THROUGH 6A-2c (cont'd). BIBLIOGRAPHY FOR PM STUDIES
Ref No.
Sites
Dates
Types of Samples
Data
Comments
Harvard 6-cities
1) 1977-1985 TSP
2) 1979-1985 PM10
&PM25
3) 1979-1984
Sulfate
IPN study -25 sites. Throughout 1980.
Los Angeles
(SCAQS)
40 locations
Aerosol composition
Summer (11
episode days) and
fall (7 episode
days) 1987
F+C(2.5-15), 24-h sample
every 6th day. Only moderately
or highly-loaded samples were
included. No Carbon.
Sequential 4-, 5-, and 7-h
PM2 5 and PM10 on summer
episode days, and 4- and 6-h
samples in fall.
Mass, elements, ions, sulfate,
nitrate, Carbon, ammonium.
1) Table of Mean Air pollution
values for 6 cities: TSP,
Inhalable, Fine, Sulfate. No
comp.
1) F+C mass for -25 sites.
2) F+C mass, composition for
22 sites (No carbon)
1) Avg & Max PM10 and PM2 5
mass, ions, comp, Cv, Ce
stratified into summer and fall.
2) Plots of temp and spatial
variations of PM2 5 and PM10,
PM2 5 nitrate.
3) Ctot/EC for some sites
Temp and spatial
variations of PM2 5
and PM10
10 San Joaquin Valley
6 sites
Aerosol Composition
Jun 1988-Jun 1989 24-h PM10 & PM2 5 every
6 days.
Mass, elements, ions (K+,
SO^, NH4+,Na+), EC, OC
1) Summary of annual geometric
avg, arith. avg, max 24-h PM10
and PM2 5 mass by site.
2) Ann. Avg Mass and comp. for
PM10 and PM2 5 by site.
PM10 highest in winter
and dominated by F
mass; C >50% of
PM10 in summer and
fall. Data show
spatial and temporal
variations of PM10 and
-------
APPENDIX FOR TABLES 6A-la THROUGH 6A-2c (cont'd). BIBLIOGRAPHY FOR PM STUDIES
Ref No.
11
12
13
Sites
Phoenix PM Study
Phoenix
4 sites
Also comparison
aerosol data from
Denver, Reno, and
Sparks
Denver
Dates
Oct. 1989 - Jan.
1990
Sept. 1989 - Jan.
1990
Jan. 11-30, 1982
Types of Samples
F&C mass, elements, uncertainties
from 6 sites
6-h samples, 2x/day, (0600-1200,
1300-1900)
PM10 & PM2 5: mass, elements,
HNO3, SO2, NH3, FP NO3and SO^,
ionic species, OC, EC.
Dichotomous sampler, OC, EC,
nitrate, sulfate
Data
1) temporal variation of PM2 5
mass at 4 sites.
2) Mean, SD, & Max: PM2 5, EC,
OC, NOj, SO|% NH^ and
elements for 3 Phoenix sites
3) Same for Denver (11/87-1/88)
4) Same for Reno (11/86-1/87)
5) Same for Sparks (11/86-1-87)
1) Measured PM2 5 and Coarse,
elements, OC, EC, nitrate,
day/night samples; light extinction.
Comments
Moudi size-
resolved (0-
5.6 pm in 9 bins)
mass, NOj SO^,
OC, EC.
Source
apportionment for
F&C particles and
14
oo
15
16
17
Denver (SCENIC)
Nov. 1987-Jan.
1988
2x daily (0900-1600, 1600-0900).
PM2 5 mass, comp, sulfate, nitrate,
OC, EC, ionic species, gases
Chicago
Houston
St. Louis & Harriman
July, 1994
Sept. 10-19, 1980
Sept. 1985 - Aug.
1986
VAPS & Dichot. FM, CM, OC, EC,
elements, S02> HONO, HNO3.
Dichotomous sampler: 0.1-2.5, 2.5-
15. 4 sites. Consecutive 12 h samples.
Daily F&C (2.5-10^m). Also SO2,
NO2, and 03.
1) Avg, SD, Mm, Max PM2 5
mass for 6 sites.
2) Avg, SD, Min, Max, for PM2 5
mass, ionic species, EC, OC,
elements for 3 sites.
3) Source profiles
4) SCE for 4 sites by day and
night
1) Avg VAPS mass, SD, uncert.
for F&C, OC, EC.
1) Average F&C mass, elements,
Carbon, NH^~, NOj, Sulfate
1) Mean, SD, range for PM10,
PM25, S04=, H+, S02, N02, 03
for both sites.
extinction.
Source
Apportionment
study
Source
apportionment.
-------
APPENDIX FOR TABLES 6A-la THROUGH 6A-2c (cont'd). BIBLIOGRAPHY FOR PM STUDIES
Ref No.
Sites
Dates
Types of Samples
Data
Comments
18
19
20
21
22
23
24
St. Louis
1) Albuquerque
2) Denver
Charlotte (2 incin
sites and 2 control
sites).
Steubenville
Review of PM
studies
Phoenix
10
Jul 1976-Aug 1976
(St. Louis)
RAPS data for St.
Louis exist for May
1975-Mar 1977 but
were not in this
article
F(<2.4) & C (2.4-20) 6-12 hr.
No Carbon.
1) Jan 3-4, 1983
2) Jan 19-20, 1982
F & C (2.5-10) + Carbon, Nitrate
& Sulfate (1C) 12-h samples,
Day/Night:
0700-1900,1900-0700.
Apr 30-Jun 4, 1992 VAPS F&C + Acid gases.
& Sept 21-28, no carbon. 12-h samples
1992.
Jan-Dec 1984 24-h, F+C. No Carbon
1984-1990
Jan 5-27, 1983
PM
Brownsville — Spring+Summer
residential and central 1993
sites.
10
F(<2.8)+C(>2.8). 1800-0800
12 h samples.
1)FP MES indoor/outdoor
2) VAPS central site
3) Dichot central site
1) 2-mo avg of F+C mass, metals, sulfate,
for one site.
2) F+C composition of selected samples
(different sites) during events.
3) CMB apportionment of F+C fractions to
6 components (crustal shale, crustal
limestone, ammonium sulfate, motor
vehicles, steel, paint).
4) Plots ofintercity variations in source
component concentrations
1) Mean daytime and nightime comp. of
F&C, EC, OC, nitrate, sulfate, for each site.
2) Source app. of Denver winter FP
composition.
1) Mean ambient FP cone. + XRF unc. at 4
sites
2) CMB results for FP.
1) avg F mass + comp.
2) avg source contributions by SRFA
3) SRFA-derived source profiles
1) SCE's for PM10 mass for -15 studies
l)avg F+C nightime comp, mass, Cv.Ce,
1) Crude CMB
source
apportionment of
FP with 6
sources.
More complete
source app
results in Lewis
& Enfield paper.
ambient PM10
data sources are
cited but no data
is presented
2) CMB of FP
1) min, med, max for fine MES comp+mass No avg values,
2) min, med, max F+C comp, mass for only median .
VAPS and dichot at central site
-------
APPENDIX FOR TABLES 6A-la THROUGH 6A-2c (cont'd). BIBLIOGRAPHY FOR PM STUDIES
Ref No.
Sites
Dates
Types of Samples
Data
Comments
25
26
27
28
>
h—'
o
29
30
Sparks, Reno, Verdi,
NV (SNAPS)
Utah Valley (Linden
site)
Santa Clara County
San Joaquin Valley
6 sites
Source apportionment
SF Bay Area
2 sites
Los Angeles
(SCAQS)
40 locations
CMB Source Apport.
Apr 1986-Mar
1987
Apr 1985-Dec 1989
1980-1986: only
Nov, Dec, Jan data
used.
Jun 1988-Jun 1989
Dec 16, 1991-Feb
24, 1992
Summer (11
episode days) and
fall (7 episode
days) 1987
1) PM2 5 & PMj0 every 6th day.
24-h samples. Also diurnal
sampling.
1) PM10 for 1736 days. Also, SO2,
NO2, O3, acidity data.
"COH" -coefficient of haze.
[COH/PM10=1.87or 1.64 (1985
and 1986)].
24-h PM10 & PM2 5 every 6 days.
Mass, elements, ionic species,
Carbon,
12-h daily day & nite (0600-1800,
1800-0600) PMi0 samples.
Mass, elements, ions (K+,C1,
SOJ , NH^ , Na+) Carbon,
ammonium.
Sequential 4-, 5-, and 7-h PM2 5
and PM10 on summer episode days,
and 4- and 6-h samples in fall.
Mass, elements, ions, sulfate,
nitrate, Carbon, ammonium.
1) Seasonal avg SCE for PM10 at
3 sites, (geological, motor veh,
construction, vegetative, sulfate,
nitrate, OC, EC)
l)avg PM10 = 47 jig/m3.
sd=38, (min.max)=(1,365 ftg/m3).
2) freq distribution of PM10 mass.
1) Plots of COH vs daily mortality
for 2-yr periods.
1) Table of arm. avg. SCE to PM10
and PM2.5 for data above, by site
l)Table of arm. avg. PM10 mass,
sulfate, nitrate statistics at 3 sites for
1988-1992
2) Avg. & Max day & nite PM10
mass, ions, comp, EC, OC, for both
sites
3) Source profiles
4) SCE pie charts for each site.
1) Source profiles
2) PMjQ SCE for summer and fall.
3) Diurnal SCE to PM10 at each site.
No raw data
no comp. data.
Highest pmlO
during winter.
Examines relation
between mortality
and COH
For PM10 Mass,
Sulfate, and
Nitrate data, see
ref 27.
1. Highest PM10
mass during Nov,
Dec, Jan.
2. Wood combust.
contributes
-45% of PM10.
Data show diurnal
changes in SCE
for PM10 mass.
-------
APPENDIX FOR TABLES 6A-la THROUGH 6A-2c (cont'd). BIBLIOGRAPHY FOR PM STUDIES
Ref No.
Sites
Dates
Types of Samples
Data
Comments
31
32
33
34
35
1) Claremont (SCAQS) 1) Summer 1987
(59d)
2) Long Beach (SCAQS) 2) Fall 1987
(23d)
CADMP - 8 sites:
Gasquet, Fremont,
Bakersfield, Yosemite,
Sequoia, Long Beach,
Los Angeles, Azusa
Central California -53
sites in SF Bay area,
Sacramento Valley, San
Joaquin Valley, North
and South Central Coast,
Mountain Counties
Birmingham
Philadelphia
Continuous 12-h
PM10 and PM25.
Mass, elements, ionic species,
EC, OC
Summer 1988
1) 1989
2) July & August,
1988
1986-1989
2 samples every 6th day.
0600-01800, 1800-0600.
PM2 5, PM10. Mass, ionic
species,
PM10 every 6th day. Sulfate and
nitrate measured on a subset of
these samples.
1973-1980
Daily 24-h PM]0 mass. Also
Ozone data.
No composition data.
24-h (midnite-midnite) TSP.
No composition data.
1) Mean, SD, & Max: PM10, FPM,
CPM, EC, OC, N03 , SOJ ,
NH4+ .
2) Mean values of above species
during intensive and non-intensive
periods.
3) Day/nite values of above
4) PM10 and PM2 5 mass balances
5) Summary of EC, OC data.
1) Graph of avg PM10 & PM2 5
mass and ratio at 8 sites
2) Graphs of PM10 & PM2 5 ionic
concentrations.
1) 1989 Max and Avg PM10 mass,
Sulfate, and Nitrate for ~53 sites.
2) Summertime 1988 Avg, SD, and
Max PM10 and PM2 5 Mass, comp,
OC.EC, Ionic species, for 3
SJVAQS sites. [Annual data
summary is in ref 20].
1) Table of percentile points of the
distribution of PM10, O3, T,
DewPoint, Pneumonia, Chronic
obstructive pulmonary disease.
2) Avg PM10 and O3 by season
1) Table of percentile points of the
distribution of TSP, SO2, T,
DewPoint, Mortality.
Ask Chow/Watson for
raw data.
Aside: Indoor/Outdoor
ratios of 0.63 for PM10
were reported in
Tuscon.
36
State College, PA
summer 1990
Indoor, outdoor, personal
H+,andNH3
Validation of personal
exposure models
-------
44
45-50
APPENDIX FOR TABLES 6A-la THROUGH 6A-2c (cont'd). BIBLIOGRAPHY FOR PM STUDIES
Ref No.
37
38-43
Sites
Southern Ontario
3 sites
Miscellaneous sites
14 sites
Dates
Jan.-Nov., 1991
1984-1990
Types of Samples
24-h, midnite-midnite, every 6th
day. PMjQ dichot sampler.
PMj0 concentrations.
Data
l)Avg mass, elements, for F&C
fractions, for 3 sites. No OC, EC.
1) Measured PM10 mass and avg
source contributions (up to 10 source
Comments
Primary reference
is Ref 10.
Allegheny Mtn. SW PA July 24-Aug. 10
elev. 838 m 1977
Allegheny Mtn. and
Laurel Hill, SW PA
separation 35.5 km
Aug. 5-Aug. 28,
1983
Filters, impactors, gas samplers,
day/night
Filters, dichotomous samplers,
impactors, denuders, gas analyzers,
day/night
categories).
Aerosol mass, elements, H+,
SO 4 , NO3 , total C, size distributions,
scat'
Fine, coarse, and PM10 mass,
elements, EC, H+, NH| , SO^ ,
NC>3 , size distributions, CN counts,
bscat, babs, Lv, HNO3 and other gases,
rain, dew, 2-site correlation
Strong aerosol H+
found, associated
with SO^
Coordinated with
Deep Creek Lake
experiment, Ref.
4, =60 km to
SSW
References:
1. Stevens et al. (1984)
2. Dzubay et al. (1988)
3. Pinto et al. (1995)
4. Vossler et al. (1989)
5. Stevens et al. (1993)
6. Spengler and Thurston (1983)
7. Dockery et al. (1993)
8. Davis et al. (1984)
9. Chow et al. (1994a)
10. Chow et al. (1993a)
11. Desert Research Institute (1995)
12. Chow et al (1990)
13. Lewis et al. (1986);
Lewis and Dzubay (1986)
14. Watson et al. (1988)
15. Stevens, R. K (1995) [Unpublished
data].
16. Johnson et al. (1984)
17. Dockery et al. (1992)
18. Dzubay (1980)
19. Stevens (1985)
20. Mukerjee et al. (1993)
21. Koutrakis and Spengler (1987)
22. Chow et al. (1993b)
23. Solomon and Moyers (1986)
24. Ellenson et al. (1994)
25. Chow et al. (1988)
26. Pope et al. (1992)
27. Fairley (1990)
28. Chow et al. (1992b)
29. Chow et al. (1995a)
30. Watson et al. (1994a)
31. Wolff etal. (1991)
32. Ashbaugh et al. (1989)
33. Chow et al. (1994b);
Watson et al. (1994b)
34. Schwartz (1994)
35. Schwartz and Dockery
(1992)
36. Suh et al. (1993)
37. Conner et al. (1993)
38. Kim et al. (1992)
39. Houck et al. (1992)
40. Chow et al. (1992a)
41. Vermette et al. (1992)
42. Thanukos et al. (1992)
43. Skidmore et al. (1992)
44. Pierson et al. (1980b)
45. Pierson et al. (1986)
46. Japar et al. (1986)
47. Pierson et al. (1987)
48. Keeler et al. (1988)
49. Pierson et al. (1989)
50. Keeler et al. (1990)
-------
TABLE 6A-2a. PM2 5 COMPOSITION FOR THE EASTERN UNITED STATES (/ig/m3)
Ref
Site
Dates
Time
Duration
(h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity$
Al
As
Ba
Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
1
Smoky Mm.
9/20-26/78
0-12-24
12
12
24.00
2.22
1.10
0.30
12.00
<0.054
<0.003
0.018
0.016
< 0.010
0.003
0.028
0.040
1
Shenandoah
7/23-5/08/80
0-12-24
12
28
27.00
0.44
1.12
13.60
< 0.105
< 0.003
0.008
0.035
0.010
0.005
0.054
0.061
2(b)
Camden
7/14-8/13, 1982
6-18-6
12
50
28.70
2.05
1.87
<0.48
11.20
0.053
0.001
0.029
0.040
0.002
0.003
0.002
0.091
0.101
0.006
0.001
0.146
0.011
3
Philadelphia
7/25-8/14/94
9-9
24
21
32.18
4.51
0.76
0.114
0.009
0.058
0.026
0.007
0.127
0.060
0.023
0.003
0.070
0.007
4(c)
Deep Creek
8/83
4x daily
6
98
40.00
1.45
0.18
0.57
0.001
0.005
0.048
0.058
0.044
0.003
0.034
46, 49, 50
Allegheny Mm.
8/5-28/83
day /night
-10
44
49
2
1.2
0.5
17
9
0.058
0.0005
0.0048
0.004
0.027
0.0004
0.061
0.0016
0.0012
0.046
0.041
0.011
0.0032
0.0037
0.036
0.0009
46, 49, 50
Laurel Hill
8/6-27/83
day /night
-10
39
46
2
1.4
0.6
18
10
0.048
0.0006
0.0033
0.004
0.023
0.0004
0.038
0.0011
0.0020
0.062
0.040
0.009
0.0038
0.0031
0.034
0.0011
5(d)
Raleigh
1/85-3/85
7-19-7
12
NR
30.30
10.00
0.50
0.009
0.001
0.028
0.018
0.007
0.020
0.044
0.159
0.003
0.001
5(d)
Roanoke
10/88-2/89
7-19-7
12
NR
19.90
7.30
1.50
0.176
0.002
0.005
0.047
0.053
0.001
0.007
0.114
0.177
0.012
0.001
6,7
Watertown
5/79-6/81
00-24
24
354
14.90
5.85
20.300
0.088
0.041
0.084
0.074
0.004
0.009
8(a)
Hartford
1980
NR
24
2
26.75
0.035
0.036
0.070
0.003
0.043
0.125
0.171
0.007
0.010
8(a)
Boston
1980
NR
24
1
34.80
0.002
0.020
0.070
0.004
0.035
0.121
0.096
0.001
0.012
8(a)
Res.Tr.Pk
1980
NR
24
3
28.77
0.073
0.002
0.007
0.035
0.016
0.120
0.148
0.003
0.001
-------
TABLE 6A-2a (cont'd). PM2 5 COMPOSITION FOR THE EASTERN UNITED STATES 0*g/m3)
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
> Sr
i
£ Ti
V
Zn
1
Smoky Mm.
9/20-26/78
00-12-24
12
12
0.097
3.744
0.001
0.038
< 0.006
<0.004
0.009
1
Shenandoah
7/23-5/08/80
00-12-24
12
28
0.052
4.539
0.001
0.116
< 0.010
<0.010
0.011
2(b)
Camden
7/14-8/13 '82
6-18-6
12
50
0.249
4.200
0.079
0.002
0.103
<0.012
< 0.002
< 0.027
0.013
0.082
3
Philadelphia
7/25-8/14/94
9-9
24
21
0.015
0.019
3.251
< 0.002
0.165
< 0.042
<0.013
0.041
4(c)
Deep Creek
8/83
4x daily
6
98
0.048
6.700
0.001
0.003
0.150
0.001
0.013
44, 45-50
Allegheny Mm.
8/5-28/83
day/night
-10
44
0.013
0.035
0.0005
5.9
0.0006
0.0018
0.23
0.0026
0.0041
0.0019
0.010
45-50
Laurel Hill
8/6-27/83
day /night
-10
39
0.019
0.039
0.0002
5.5
0.0006
0.0020
0.21
0.0027
0.0047
0.0017
0.012
5(d)
Raleigh
1/85-3/85
7-19-7
12
NR
0.096
1.729
0.002
0.076
0.003
0.015
5(d)
Roanoke
10/88-2/89
7-19-7
12
NR
0.027
1.177
0.002
0.077
0.004
0.083
6,7
Watertown
5/79-6/81
00-24
24
354
0.329
1.800
0.001
0.100
0.022
8(a)
Hartford
1980
NR
24
2
0.510
2.219
0.001
0.177
0.002
0.017
0.079
8(a)
Boston
1980
NR
24
1
0.009
0.285
3.869
0.001
0.144
0.020
0.046
8(a)
Res.Tr.Pk
1980
NR
24
3
0.042
0.106
2.835
0.002
0.350
0.018
References are listed in Table 1 Appendix. Associated notes are explained in Table 1.
"Values for this size fraction are calculated from the average measured values reported for the other two size fractions.
'Units for acidity are nmoles/m3.
NR = not reported.
-------
TABLE 6A-2a (cont'd). PM2 5 COMPOSITION FOR THE WESTERN UNITED STATES (/ig/m3)
ON
Ref
Site
Dates
Time
Duration (h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity*
Al
As
Ba
Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
9(g)
Los Angeles
Summer 1987
NR
4,5 and 7
1 1 days
41.10
8.27
2.37
4.34
9.41
0.035
0.022
0.015
0.013
0.022
0.093
0.022
0.063
0.099
0.041
0.024
0.016
0.202
0.005
9(g)
Los Angeles
Fall 1987
NR
4 and 6
6 days
90.20
18.46
7.28
22.64
4.38
0.250
0.015
0.043
0.065
0.335
0.453
0.025
0.273
0.557
0.217
0.075
0.043
0.466
0.007
100)
San Joaquin
Valley
6/88-6/89
NR
24
-35
29.89
4.87
3.24
8.17
3.00
0.152
0.012
0.010
0.0%
< 0.007
0.094
0.003
0.0%
0.180
0.188
0.006
0.016
H(j)
Phoenix
10/13/89-
1/17/90
NR
6 h, 2x/day
- 100 days
29.37
10.10
7.47
3.60
1.33
0.130
<0.020
<0.106
0.011
0.170
<0.018
0.365
0.003
0.015
0.216
0.207
0.023
<0.006
0.003
5(d)
Boise
12/86-3/87
7-19-7
12
NR
35.70
12.70
1.70
0.102
0.002
0.014
0.026
0.122
0.001
0.011
0.022
0.145
0.002
0.002
12(1)
Nevada
11/86-1/87
00-24
24
24
56.92
19.97
15.17
2.43
1.67
0.275
0.001
0.013
0.033
0.215
0.145
0.002
0.010
0.310
0.280
0.015
0.006
8(a)
Tarrant CA
1980
NR
24
6
57.05
0.177
0.102
0.455
0.002
0.047
0.316
0.186
0.032
0.003
8(a)
Five Points
CA
1980
NR
24
3
31.80
0.239
0.015
0.150
0.004
0.001
0.024
0.216
0.244
0.005
0.025
8(a)
Riverside
CA
1980
NR
24
4
35.18
0.036
0.037
0.301
0.009
0.040
0.127
0.120
0.007
0.007
8(a)
San Jose
CA
1980
NR
24
6
36.28
0.123
0.001
0.188
0.089
0.050
0.003
0.043
0.148
0.248
0.006
0.006
8(a)
Honolulu
1980
NR
24
1
21.10
1.127
0.017
1.024
0.518
0.004
0.018
0.726
0.371
0.020
0.002
8(a)
Winnemucca
1980
NR
24
5
9.68
0.361
0.006
0.243
0.026
0.231
0.149
0.003
0.001
8(a) 8(a)
Portland Seattle
1980 1980
NR NR
24 24
4 1
37.18 10.70
0.581 0.002
0.012 0.006
0.093 0.019
0.154 0.037
0.021
0.009 0.002
0.072 0.024
0.270 0.098
0.218 0.080
0.052 0.004
0.027 0.006
-------
TABLE 6A-2a (cont'd). PM2 5 COMPOSITION FOR THE WESTERN UNITED STATES Gig/m3)
Ref
9(g)
9(g)
10(i)
H(j)
5(d)
12(f)
8(a)
8(a)
8(a)
Five Points Riverside
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
ON
> Si
i
ON Sn
Sr
Ti
V
Zn
Los Angeles
Summer 1987
NR
4, 5 and 7
1 1 days
0.060
0.038
2.832
0.013
0.052
0.019
0.005
0.006
0.090
Los Angeles
Fall 1987
NR
4 and 6
6 days
0.046
0.185
1.998
0.011
0.520
0.028
0.060
0.007
0.298
San Joaquin
Valley
06/88-06/89
NR
24
-35
0.007
0.029
0.001
1.242
< 0.002
0.001
0.460
<0.015
0.002
0.017
0.015
0.078
Phoenix
10/13/89-
1/17/90
NR
6 h, 2x/day
- 100 days
< 0.051
0.039
< 0.0025
0.437
< 0.033
< 0.002
0.430
<0.028
< 0.030
< 0.016
0.056
Boise
12/86-3/87
7-19-7
12
NR
0.045
0.603
0.001
0.069
0.001
0.019
Nevada
1 1/86-1/87
00-24
24
24
0.041
0.115
0.001
0.765
0.860
0.004
0.043
0.009
0.033
Tarrant CA
1980
NR
24
6
0.619
2.578
0.583
0.010
0.095
CA
1980
NR
24
3
0.007
0.087
1.129
0.001
0.656
0.005
0.006
0.016
CA
1980
NR
24
4
0.376
1.653
0.001
0.234
0.003
0.029
8(a)
San Jose
CA
1980
NR
24
6
0.013
0.891
0.852
0.292
0.002
0.061
8(a)
Honolulu
1980
NR
24
1
0.002
0.071
0.313
2.363
0.063
0.001
0.011
8(a)
8(a)
Winnemucca Portland
1980
NR
24
5
0.042
0.358
0.914
0.009
0.011
1980
NR
24
4
0.017
0.422
1.944
0.001
0.377
0.005
0.014
0.081
8(a)
Seattle
1980
NR
24
1
0.006
0.215
0.831
0.001
0.092
0.059
References are listed in Table 1 Appendix. Associated notes are explained in Table 1.
"Values for this size fraction are calculated from the average measured values reported for the other two size fractions.
$Units for acidity are nmoles/m3.
NR = not reported.
-------
TABLE 6A-2a (cont'd). PM2 5 COMPOSITION FOR THE CENTRAL UNITED STATES
Ref
Site
Dates
Time
Duration (h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity*
Al
As
Ba
Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
5(d)
Albuquerque
12/84-3/85
7-19-7
12
NR
20.60
13.20
2.10
0.077
0.085
0.059
0.036
0.045
0.074
13
Denver
1/11-30/82
6-18-6
12
-26
20.73
7.11
2.15
2.22
2.06
0.394
< 0.002
0.031
0.103
0.047
0.006
0.052
< 0.009
0.010
0.079
0.079
0.011
0.003
14(m) 14(aa)
Urban Denver Non-urban Denver
11/87-1/88 11/87-1/88
9-16-9 9-16-9
7&17 7&17
-136 -150
19.67 10.35
7.25
4.41
3.96
1.55
0.037
0.018
0.058
0.005
0.141
0.003
0.017
0.111
0.077
0.012
0.002
15
Chicago
7/94
8-8
24
16
13.57
5.39
1.31
0.046
< 0.003
<0.091
0.004
0.045
< 0.029
0.011
< 0.005
0.011
0.089
0.061
0.012
0.005
< 0.002
0.022
<0.001
16
Houston
9/10-19/80
NR
12
20
38.60
5.68
1.42
0.59
14.61
0.123
< 0.005
0.048
0.055
0.155
< 0.003
0.032
< 0.005
0.028
0.162
0.119
0.014
<0.38
0.004
6,7
Harriman
5/80-5/81
00-24
24
256
20.80
8.10
36.1
0.038
0.150
0.021
0.120
0.017
BQL
17 6,7
Harriman Kingston
9/85-8/86 5/80-6/81
NR 00-24
24 24
330 169
21.00 24.60
8.70
36.1
0.044
0.120
BQL
0.097
0.010
BQL
6,7
Portage
3/79-5/81
00-24
24
271
11.00
4.95
10.5
0.011
0.045
0.027
0.049
0.003
BQL
6,7
Topeka
8/79-5/81
00-24
24
286
12.50
4.40
11.6
0.045
0.250
0.031
0.090
0.004
BQL
8(a)
El Paso
1980
NR
24
10
27.16
0.155
0.025
0.070
0.332
0.001
0.036
0.134
0.127
0.004
0.001
8(a)
Inglenook
1980
NR
24
8
32.03
0.082
0.001
0.040
0.326
0.003
0.002
0.032
0.281
0.408
0.037
0.001
-------
TABLE 6A-2a (cont'd). PM2 s COMPOSITION FOR THE CENTRAL UNITED STATES Otg/m3)
ON
00
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
Sr
Ti
V
Zn
5(d)
Albuquerque
12/84-3/85
7-19-7
12
NR
0.237
0.507
0.076
0.007
13
Denver
1/11-30/82
6-18-6
12
-26
0.043
0.326
< 0.003
0.709
0.277
< 0.003
< 0.027
0.046
14(m)
Urban Denver
11/87-1/88
9-16-9
7&17
-136
0.075
0.642
0.004
0.001
0.272
0.006
0.001
0.009
0.031
14(aa) 15
Non-urban Denver Chicago
11/87-1/88 7/94
9-16-9 8-8
7&17 24
-150 16
0.008
0.027
1.321
< 0.042
<0.001
0.074
< 0.049
< 0.029
<0.009
0.052
16
Houston
9/10-19/80
NR
12
20
0.028
0.465
< 0.002
4.834
0.006
< 0.002
0.210
< 0.005
< 0.002
<0.014
<0.008
0.084
6,7
Harriman
5/80-5/81
00-24
24
256
0.180
2.500
0.002
0.120
BQL
17 6,7
Harriman Kingston
9/85-8/86 5/80-6/81
NR 00-24
24 24
330 169
0.194
2.400
0.002
0.200
BQL
6,7
Portage
3/79-5/81
00-24
24
271
0.061
1.400
0.001
0.075
BQL
6,7
Topeka
8/79-5/81
00-24
24
286
0.163
1.100
0.190
BQL
8(a)
El Paso
1980
NR
24
10
0.481
0.823
0.002
0.436
0.003
0.055
8(a)
Inglenook
1980
NR
24
8
0.008
0.309
2.655
0.001
0.685
0.133
-------
TABLE 6A-2a (cont'd). PM2 5 COMPOSITION FOR THE CENTRAL UNITED STATES Gig/m3)
Ref
Site
Dates
Time
Duration (h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity*
Al
As
Ba
Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
8(a)
Braidwood
1980
NR
24
1
28.20
0.089
0.003
0.084
0.024
0.071
0.052
0.001
0.001
8(a)
Kansas City KS
1980
NR
24
8
25.66
0.091
0.003
0.027
0.519
0.004
0.032
0.189
0.311
0.006
0.002
8(a) 8(a)
Minneapolis Kansas City MO
1980 1980
NR NR
24 24
6 3
15.50 16.77
0.004 0.007
0.047 0.064
0.103 0.213
0.001 0.002
0.035 0.021
0.087 0.140
0.092 0.142
0.005 0.006
0.001 0.001
8(a)
Akron
1980
NR
24
7
36.09
0.046
0.012
0.039
0.110
0.010
0.037
0.609
0.268
0.085
0.006
8(a)
Cincinnati
1980
NR
24
2
29.80
0.062
0.013
0.024
0.062
0.003
0.024
0.174
0.136
0.011
0.004
8(a)
Buffalo
1980
NR
24
14
38.75
0.192
0.009
0.003
0.218
0.002
0.026
0.671
0.310
0.033
0.008
8(a)
Dallas
1980
NR
24
4
28.93
0.111
0.033
0.223
0.691
0.005
0.043
0.248
0.125
0.015
0.002
8(a)
St. Louis
1980
NR
24
5
23.06
0.119
0.003
0.025
0.090
0.018
0.076
0.126
0.002
0.002
18(k)
St. Louis
8-9/76
NR
6-12
NR
34.00
0.203
0.002
0.020
0.132
0.132
0.004
0.087
0.006
0.029
0.275
0.261
0.036
0.004
6,7
St. Louis
9/79-6/81
00-24
24
306
19.00
7.40
10.3
0.078
0.101
0.052
0.190
0.021
0.003
17 6,7
St. Louis Steubenville
9/85-8/86 4/79-4/81
NR 00-24
24 24
311 499
17.70 29.60
8.00 10.94
9.7 25.2
0.042
0.097
0.092
0.590
0.029
0.005
-------
TABLE 6A-2a (cont'd). PM2 5 COMPOSITION FOR THE CENTRAL UNITED STATES (jig/m3)
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
|> Sr
Ni Ti
O
V
Zn
8(a)
Braidwood
1980
NR
24
1
0.041
2.060
0.001
0.220
0.011
8(a)
Kansas City KS
1980
NR
24
8
0.013
0.180
1.816
0.001
0.434
0.004
0.034
8(a)
Minneapolis
1980
NR
24
6
0.308
0.907
0.001
0.169
0.045
8(a)
Kansas City MO
1980
NR
24
3
0.369
0.763
0.177
0.046
8(a)
Akron
1980
NR
24
7
0.059
0.412
3.419
0.008
0.522
0.009
0.150
8(a)
Cincinnati
1980
NR
24
2
0.043
0.343
2.876
0.005
0.328
0.003
0.053
8(a)
Buffalo
1980
NR
24
14
0.060
0.359
3.706
0.005
0.241
0.001
0.078
8(a)
Dallas
1980
NR
24
4
0.018
1.066
1.514
0.442
0.007
0.002
0.054
8(a)
St. Louis
1980
NR
24
5
0.020
0.277
2.333
0.002
0.170
0.023
1800
St. Louis
8-9/76
NR
6-12
NR
0.001
0.688
4.655
0.006
0.004
0.458
0.009
0.002
0.112
0.002
0.101
6,7
St. Louis
9/79-6/81
00-24
24
306
0.327
2.100
0.002
0.160
BQL
17 6,7
St. Louis Steubenville
9/85-8/86 4/79-4/81
NR 00-24
24 24
311 499
0.216
4.700
0.005
0.290
0.011
References are listed in Table 1 Appendix. Associated notes are explained in Table 1.
"Values for this size fraction are calculated from the average measured values reported for die omer two size fractions.
JUnits for acidity are nmoles/m3.
NR = not reported.
-------
TABLE 6A-2b. COARSE PARTICLE COMPOSITION FOR THE EASTERN UNITED STATES
to
Ref
Site
Dates
Time
Duration (h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity*
Al
As
Ba
Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
Ko)
Smoky Mm.
9/20-26/78
NR
12
12
5.60
< 0.300
<0.001
0.005
0.322
< 0.012
< 0.005
0.118
0.108
< 0.002
Ko)
Shenandoah
7/23-5/08/80
NR
12
28
7.40
0.78
0.311
< 0.002
0.003
0.304
0.179
0.006
0.158
0.129
< 0.006
< 0.003
2(b)
Camden
7/14-8/13 '82
6-18-6
12
50
11.40
<3.00
0.42
0.57
<0.90
0.550
0.015
0.360
< 0.006
0.069
< 0.009
0.490
0.151
0.011
0.004
3(ab)
Philadelphia
7/25-8/14/94
NR
24
21
8.42
0.325
0.003
0.421
0.047
0.014
0.352
0.100
0.104
0.006
0.136
0.002
4(c) 46,49,50
Deep Creek Allegheny Mm.
8/83 8/5-28/83
4x daily day /night
6 -10
98 44
15
0.39
0.0002
0.007
0.0011
0.27
0.0004
0.044
0.0014
0.0016
0.24
0.11
0.060
0.0063
0.0026
0.054
0.0008
46,49,50 5(d)
Laurel Hill Raleigh
8/6-27/83 1/85-3/85
day/night 7-19-7
-10 12
39 NR
13
0.39
0.0002
0.006
0.0011
0.28
0.0003
0.039
0.0015
0.0025
0.24
0.10
0.061
0.0068
0.0021
0.044
0.0009
5(d) 6,7(o,p)*
Roanoke Watertown
10/88-2/89 5/79-6/81
7-19-7 00-24
12 24
NR 354
9.30
0.65
0.022
0.209
0.305
0.276
0.006
8(a,o)
Hartford
1980
NR
24
2
27.85
1.875
0.046
0.864
0.302
0.008
0.026
1.070
0.310
0.021
0.005
8(a,o)
Boston
1980
NR
24
1
105.60
3.458
0.001
0.025
1.069
0.301
0.004
0.023
1.612
0.533
0.029
0.022
8(a,o)
Res.Tr.Pk
1980
NR
24
3
8.17
0.606
0.003
0.086
0.002
0.010
0.182
0.068
0.003
-------
TABLE 6A-2b (cont'd). COARSE PARTICLE COMPOSITION FOR THE EASTERN UNITED STATES Gtg/m3)
NJ
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
Sr
Ti
V
Zn
1(0)
Smoky Mm.
9/20-26/78
NR
12
12
0.014
< 0.560
< 0.0006
0.580
0.018
< 0.004
1(0)
Shenandoah
7/23-5/08/80
NR
12
28
0.009
<0.711
<0.001
0.813
0.017
0.006
2(b)
Camden
7/14-8/13 '82
6-18-6
12
50
0.054
0.230
0.181
<0.0015
1.610
<0.009
0.002
0.065
0.007
0.030
3(ab)
Philadelphia
7/25-8/14/94
NR
24
21
0.027
0.013
BQL
BQL
0.933
0.030
BQL
0.052
4(c) 46,49,50
Deep Creek Allegheny Mtn.
8/83 8/5-28/83
4x daily day /night
6 -10
98 44
0.006
0.007
0.0004
0.59
0.0002
0.0003
1.48
0.0029
0.029
0.0011
0.010
46,49,50 5(d)
Laurel Hill Raleigh
8/6-27/83 1/85-3/85
day /night 7-19-7
-10 12
39 NR
0.007
0.007
0.0005
0.56
0.0002
0.0003
1.41
0.0025
0.027
0.0010
0.011
5(d) 6,7(o,p)*
Roanoke Watertown
10/88-2/89 5/79-6/81
7-19-7 00-24
12 24
NR 354
0.076
0.200
1.000
8(a,o)
Hartford
1980
NR
24
2
0.033
0.171
0.428
4.517
0.094
0.008
0.054
8(a,o)
Boston
1980
NR
24
1
0.016
0.177
0.502
6.760
0.154
0.008
0.054
8(a,o)
Res.Tr.Pk
1980
NR
24
3
0.013
0.223
1.387
0.021
0.007
References are listed in Table 1 Appendix. Associated notes ate explained in Table 1.
"Values for this size fraction are calculated from the average measured values reported for the other two size fractions.
$Units for acidity are nmoles/mj.
NR = not reported.
-------
TABLE 6A-2b (cont'd). COARSE PARTICLE COMPOSITION FOR THE WESTERN UNITED STATES Oig/m3)
-------
TABLE 6A-2b (cont'd). COARSE PARTICLE COMPOSITION FOR THE WESTERN UNITED STATES Otg/m3)
ON
N>
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
Sr
Ti
V
Zn
9(g)*
Los Angeles
Summer
1987
NR
4,5 and 7
1 1 days
0.127
0.046
0.520
BQL
1.988
BQL
0.072
BQL
0.024
9(g)*
Los Angeles
Fall 1987
NR
4 and 6
6 days
0.053
0.066
0.264
BQL
1.642
BQL
0.106
0.003
BQL
10(i)*
San loaquin
Valley
6/88-6/89
NR
24
-35
0.052
0.032
0.222
7.577
0.012
0.130
BQL
0.016
110)
Phoenix
10/13/89-
1/17/90
NR
6 h, 2x/day
- 100 days
0.038
0.022
0.003
0.178
< 0.030
< 0.002
7.013
< 0.026
0.014
0.121
<0.014
0.034
5(d) 12(f) 8(a,o)
Tarrant
Boise Nevada CA
12/86-3/87 11/86-1/87 1980
7-19-7 00-24 NR
12 24 24
NR 24 6
0.002
0.167
0.310
5.208
0.083
0.052
8(a,o)
Five Points
CA
1980
NR
24
3
0.148
0.018
0.293
16.001
0.272
0.007
0.016
8(a,o)
Riverside
CA
1980
NR
24
4
0.144
0.113
0.720
7.544
0.182
0.030
8(a,o)
San Jose
CA
1980
NR
24
6
0.032
0.228
0.257
5.214
0.086
0.044
8(a,o)
Honolulu
1980
NR
24
1
0.022
0.258
3.766
0.067
0.008
8(a,o)
Winnemucca
1980
NR
24
5
0.021
0.215
11.903
0.164
0.015
8(a,o)
Portland
1980
NR
24
4
0.011
0.115
0.427
12.128
0.186
0.004
0.038
8(a,o)
Seattle
1980
NR
24
1
0.077
0.121
4.332
0.091
0.034
References are listed in Table 1 Appendix. Associated notes are explained in Table 1.
Values for this size fraction are calculated from the average measured values reported for the other two size fractions.
JUnits for acidity are nmoles/m3.
NR = not reported.
-------
TABLE 6A-2b (cont'd). COARSE PARTICLE COMPOSITION FOR THE CENTRAL UNITED STATES (jig/m3)
Ref
Site
Dates
Time
Duration (h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity*
Al
As
Ba
Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
5(d) 13(o)
Albuquerque Denver
12/84-3/85 1/11-30/82
7-19-7 6-18-6
12 12
NR -26
35.73
0.39
2.900
0.058
0.024
0.658
0.012
1.235
< 0.009
0.008
0.954
0.648
0.021
0.005
14(m) 14(ab) 15(s)
Urban Denver Non-urban Denver Chicago
11/87-1/88 11/87-1/88 7/94
9-16-9 9-16-9 8-8
7 & 17 7 & 17 24
-136 -150 16
14.97
0.223
<0.0013
<0.038
0.007
0.716
<0.012
0.036
< 0.0024
0.006
0.344
0.101
0.106
0.008
< 0.0017
<0.017
< 0.0007
16(o)
Houston
9/10-19/80
NR
12
20
24.80
3.10
1.63
0.91
1.093
<0.006
0.091
0.036
2.780
< 0.006
0.366
0.007
0.018
0.604
0.170
0.021
<0.74
0.004
6,7(o,p)* 17 6,7(o,p)*
Harriman Harriman Kingston
5/80-5/81 9/85-8/86 5/80-6/81
00-24 NR 00-24
24 24 24
256 330 169
11.70 9.00 10.80
0.014 0.012
1.650 0.840
0.029 0.018
0.570 0.263
0.021 0.018
0.001 BQL
6,7(o,p)*
Portage
3/79-5/81
00-24
24
271
7.20
0.35
0.003
0.335
0.056
0.181
0.006
0.001
6,7(o,p)*
Topeka
8/79-5/81
00-24
24
286
13.90
0.40
0.010
2.150
0.490
0.016
0.001
8(a,o)
El Paso
1980
NR
24
10
49.05
2.748
0.012
0.033
3.632
0.043
0.003
0.047
0.812
0.496
0.023
0.001
8(a,o)
Inglenook
1980
NR
24
8
40.43
2.426
0.021
2.598
0.004
0.027
1.193
0.309
0.041
0.002
-------
TABLE 6A-2b (cont'd). COARSE PARTICLE COMPOSITION FOR THE CENTRAL UNITED STATES Otg/m3)
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
Sr
Ti
V
Zn
5(d) 13(o)
Albuquerque Denver
12/84-3/85 1/11-30/82
7-19-7 6-18-6
12 12
NR -26
0.113
0.099
0.005
<0.48
7.460
0.009
0.090
0.039
14(m) 14(ab) 15(s)
Urban Denver Non-urban Denver Chicago
11/87-1/88 11/87-1/88 7/94
9-16-9 9-16-9 8-8
7 & 17 7 & 17 24
-136 -150 16
0.027
0.005
0.043
<0.017
<0.0006
0.739
<0.021
0.019
< 0.004
0.038
16(o)
Houston
9/10-19/80
NR
12
20
<0.1
0.124
<0.003
<1.29
< 0.009
2.990
<0.009
< 0.008
0.036
<0.03
0.058
6,7(o,p)* 17
Harriman Harriman
5/80-5/81 9/85-8/86
00-24 NR
24 24
256 330
0.057
SQL
1.880
6,7(o,p)*
Kingston
5/80-6/81
00-24
24
169
0.040
SQL
1.700
6,7(o,p)*
Portage
3/79-5/81
00-24
24
271
0.013
SQL
0.905
6.7(o,p)*
Topeka
8/79-5/81
00-24
24
286
0.040
BQL
2.310
8(a,o)
El Paso
1980
NR
24
10
0.191
0.249
0.001
5.377
0.077
0.057
8(a,o)
Inglenook
1980
NR
24
8
0.022
0.079
0.314
6.312
0.116
0.055
-------
TABLE 6A-2b (cont'd). COARSE PARTICLE COMPOSITION FOR THE CENTRAL UNITED STATES Qtg/m3)
Ref
Site
Dates
Time
Duration (h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity*
Al
As
Ba
Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
8(a,o)
Braidwood
1980
NR
24
1
28.70
1.931
0.002
0.003
1.406
0.002
0.020
0.656
0.303
0.017
0.001
8(a,o)
Kansas City KS
1980
NR
24
8
41.67
2.284
0.003
0.029
3.754
0.530
0.004
0.015
0.979
0.361
0.025
0.002
8(a,o)
Minneapolis
1980
NR
24
6
30.85
2.191
0.001
0.022
1.571
0.293
0.002
0.022
0.744
0.310
0.026
0.001
8(a,o)
Kansas City MO
1980
NR
24
3
41.67
2.284
0.003
0.029
3.754
0.530
0.004
0.015
0.979
0.361
0.025
0.002
8(a,o)
Akron
1980
NR
24
7
34.81
2.509
0.003
0.025
1.431
0.572
0.014
0.018
1.640
0.324
0.044
0.005
8(a,o)
Cincinnati
1980
NR
24
2
33.15
2.910
0.017
1.312
0.103
0.002
0.014
0.883
0.363
0.021
0.003
8(a,o)
Buffalo
1980
NR
24
14
44.57
2.808
0.012
2.550
0.728
0.015
0.022
2.040
0.206
0.078
0.009
8(a,o)
Dallas
1980
NR
24
4
32.63
1.294
0.006
0.051
3.436
0.029
0.005
0.023
0.720
0.210
0.020
0.002
8(a,o)
St. Louis
1980
NR
24
5
33.76
3.837
0.001
0.021
1.784
0.053
0.001
0.014
0.587
0.291
0.017
0.002
18(k,r)
St. Louis
8-9/76
NR
6-12
28.00
1.209
0.001
0.034
0.047
2.817
0.001
0.257
0.009
0.014
1.218
0.392
0.035
0.005
6,7(o,p)*
St. Louis
9/79-6/81
00-24
24
306
12.40
0.70
0.021
1.499
0.093
0.580
0.019
0.002
17 6,7(o,p)*
St. Louis Steubenville
9/85-8/86 4/79-4/81
NR 00-24
24 24
311 499
9.90 16.90
1.86
0.010
1.023
0.211
1.610
0.039
0.004
-------
TABLE 6A-2b (cont'd). COARSE PARTICLE COMPOSITION FOR THE CENTRAL UNITED STATES 0*g/m3)
I
oo
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
Sr
Ti
V
Zn
8(a,o)
Braidwood
1980
NR
24
1
0.014
0.013
0.572
0.001
5.767
0.083
0.012
8(a.o)
Kansas City KS
1980
NR
24
8
0.109
0.280
4.809
0.074
0.040
8(a,o)
Minneapolis
1980
NR
24
6
0.098
0.224
4.679
0.062
0.027
8(a,o)
Kansas City MO
1980
NR
24
3
0.109
0.280
4.809
0.074
0.040
8(a,o)
Akron
1980
NR
24
7
0.097
0.451
5.009
0.107
0.069
8(a,o)
Cincinnati
1980
NR
24
2
0.037
0.099
0.389
6.633
0.096
0.148
8(a,o)
Buffalo
1980
NR
24
14
0.108
0.765
2.675
0.051
0.043
8(a,o)
Dallas
1980
NR
24
4
0.252
0.240
3.210
0.051
0.030
8(a,o)
St. Louis
1980
NR
24
5
0.095
0.279
4.468
0.058
0.021
18(k,r)
St. Louis
8-9/76
NR
6-12
0.098
0.189
0.002
0.533
0.001
0.001
4.470
0.001
0.007
0.475
0.004
0.074
6,7(o,p)*
St. Louis
9/79-6/81
00-24
24
306
0.088
0.200
1.940
BQL
17 6,7(o,p)*
St. Louis Steubenville
9/85-8/86 4/79-4/81
NR 00-24
24 24
311 499
0.043
0.800
2.010
0.002
References are listed in Table 1 Appendix. Associated notes are explained in Table 1.
"Values for this size fraction are calculated from the average measured values reported for the other two size fractions.
$Units for acidity are nmoles/m3.
NR = not reported.
-------
TABLE 6A-2c. PM10 COMPOSITION FOR THE EASTERN UNITED STATES Otg/m3)
Ref
Site
Dates
Time
Duration (h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity*
Al
As
Ba
Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
Ko.q)*
Smoky Mm.
9/20-26/78
NR
12
12
29.60
2.22
1.10
0.30
12.00
BQL
BQL
0.023
0.338
BQL
0.003
0.146
0.148
BQL
l(o,q)*
Shenandoah
7/23-5/08/80
NR
12
28
34.40
0.44
1.12
14.38
0.311
0.011
0.339
0.189
0.011
0.212
0.190
BQL
BQL
2(b)*
Camden
7/14-8/13 '82
6-18-6
12
50
40.10
2.05
2.29
0.57
11.20
0.603
0.001
0.044
0.400
0.002
0.072
0.002
0.581
0.252
0.017
0.001
0.146
0.015
3(ab)* 4(c)
Philadelphia Deep Creek
7/25-8/14/94 8/83
NR 4x daily
24 6
21 98
40.60
4.51
0.76
0.439
0.012
0.479
0.073
0.021
0.479
0.160
0.126
0.010
0.206
0.009
5(d) 5(d) 6,7(p,q)
Raleigh Roanoke Watertown
1/85-3/85 10/88-2/89 5/79-6/81
7-19-7 7-19-7 00-24
12 12 24
NR NR 354
24.20
6.50
0.110
0.250
0.389
0.350
0.009
0.011
8(a,q)*
Hartford
1980
NR
24
2
54.60
1.910
0.082
0.934
0.302
0.011
0.069
1.195
0.481
0.028
0.015
8(a,q)*
Boston
1980
NR
24
1
140.40
3.458
0.003
0.045
1.139
0.301
0.008
0.058
1.733
0.629
0.030
0.034
8(a,q)*
Res.Tr.Pk
1980
NR
24
3
36.93
0.679
0.002
0.010
0.121
0.002
0.026
0.302
0.216
0.006
0.001
-------
TABLE 6A-2c (cont'd). PM10 COMPOSITION FOR THE EASTERN UNITED STATES 0*g/m3)
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
> Sr
g Ti
V
Zn
Ko,q)*
Smoky Mm.
9/20-26/78
NR
12
12
0.111
3.744
0.001
0.618
0.018
BQL
0.009
Ko.q)*
Shenandoah
7/23-5/08/80
NR
12
28
0.061
4.539
0.001
0.929
0.017
BQL
0.017
20))'
Camden
7/14-8/13/82
6-18-6
12
50
0.303
4.430
0.260
0.002
1.713
BQL
0.002
0.065
0.020
0.112
3(ab)* 4(c)
Philadelphia Deep Creek
7/25-8/14/94 8/83
NR 4x daily
24 6
21 98
0.042
0.032
3.251
1.098
0.030
0.092
5(d) 5(d) 6,7(p,q)
Raleigh Roanoke Watertown
1/85-3/85 10/88-2/89 5/79-6/81
7-19-7 7-19-7 00-24
12 12 24
NR NR 354
0.405
2.000
0.001
1.100
0.022
8(a,q)*
Hartford
1980
NR
24
2
0.033
0.681
2.647
0.001
4.694
0.096
0.025
0.133
(a,q)*
Boston
1980
NR
24
1
0.025
0.462
4.371
0.001
6.904
0.154
0.028
0.100
8(a,q)*
Res.Tr.Pk
1980
NR
24
3
0.042
0.119
3.058
0.002
1.737
0.021
0.025
References are listed in Table 1 Appendix. Associated notes are explained in Table 1.
"Values for this size fraction are calculated from the average measured values reported for the other two size fractions.
$Units for acidity are nmoles/m3.
NR = not reported.
-------
TABLE 6A-2c (cont'd). PM10 COMPOSITION FOR THE WESTERN UNITED STATES (/tg/m3)
Ref
Site
Dates
Time
Duration (h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity5
Al
§> As
W Ba
^ Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
9(g)
Los Angeles
Summer 1987
NR
4,5 and 7
11 days
67.40
11.61
3.19
9.47
11.28
0.758
0.007
0.070
0.016
0.585
1.119
0.023
0.022
0.836
0.237
0.335
0.033
1.632
0.005
9(g)
Los Angeles
Fall 1987
NR
4 and 6
6 days
98.70
23.35
8.49
27.50
5.39
0.847
0.019
0.127
0.072
1.190
0.880
0.042
0.178
2.192
0.460
0.287
0.063
0.518
0.005
10(i)
San Joaquin Valley
Jun. 1998-Jun. 1989
NR
24
-35
74.05
10.59
5.62
10.55
3.62
3.570
0.051
0.015
1.057
0.487
0.010
0.087
1.633
0.820
0.037
0.010
ll(j) 5(d)*
Phoenix Boise
10/13/89-1/17/90 12/86-3/87
NR 7-19-7
6 h, 2x/day 12
- 100 days NR
62.45
14.56
8.30
4.46
2.34
2.669
BQL
0.013
0.014
2.099
BQL
0.559
0.011
0.036
1.475
0.876
BQL
0.054
BQL
BQL
0.006
12(f) 8(a,q)*
Tarrant
Nevada CA
11/86-1/87 1980
00-24 NR
24 24
24 6
100.90
2.407
0.149
4.543
0.007
0.077
1.257
0.441
0.067
0.006
8(a,q)*
8(a,q>*
Five Points Riverside
CA CA
1980
NR
24
3
124.37
7.317
0.019
1.786
0.026
0.007
0.037
3.275
1.437
0.055
0.037
1980
NR
24
4
8(a,q)*
San Jose
CA
1980
NR
24
6
8(a,q)*
Honolulu
1980
NR
24
1
106.20 66.68 46.90
3.549
0.065
5.082
0.173
0.005
0.061
2.015
1.081
0.049
0.013
2.053
0.001
0.250
0.771
0.480
0.009
0.071
1.214
0.508
0.027
0.014
2.992
0.023
1.981
1.456
0.009
0.025
1.384
0.665
0.034
0.005
8(a,q)*
Winnemucca
1980
NR
24
5
8(a,q)*
Portland
1980
NR
24
4
65.42 117.55
6.925
0.010
2.177
0.176
0.006
0.043
1.995
1.200
0.044
0.003
6.932
0.014
0.121
1.459
0.197
0.019
0.109
2.059
0.805
0.108
0.036
8(a,q)*
Seattle
1980
NR
24
1
36.00
2.296
0.008
0.033
0.585
0.228
0.005
0.041
1.001
0.231
0.022
0.007
-------
TABLE 6A-2c (cont'd). PM10 COMPOSITION FOR THE WESTERN UNITED STATES Gig/m3)
N)
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
Sr
Ti
V
Zn
9(g)
Los Angeles
Summer 1987
NR
4,5 and 7
11 days
0.187
0.084
3.353
0.008
2.040
0.018
0.077
0.005
0.114
9(g)
Los Angeles
Fall 1987
NR
4 and 6
6 days
0.099
0.251
2.262
0.010
2.162
0.024
0.165
0.009
0.293
10(0
San Joaquin Valley
Jun. 1988 -Jun. 1989
NR
24
-35
0.059
0.061
0.004
1.463
0.001
8.037
0.014
0.147
0.014
0.094
ll(j) 5(d)* 12(f)
Phoenix Boise Nevada
10/13/89-1/17/90 12/86-3/87 11/86-1/87
NR 7-19-7 00-24
6 h, 2x7day 12 24
- 100 days NR 24
0.054
0.062
BQL
0.615
BQL
BQL
7.443
BQL
0.014
0.136
BQL
0.090
8(a.q)*
Tarrant
CA
1980
NR
24
6
0.002
0.786
2.888
5.791
0.093
0.147
8(a,q)*
Five Points
CA
1980
NR
24
3
0.155
0.105
1.422
0.001
16.657
0.277
0.013
0.032
8(a,q)*
Riverside
CA
1980
NR
24
4
0.144
0.489
2.373
0.001
7.778
0.182
0.003
0.059
8(a,q)*
San Jose
CA
1980
NR
24
6
0.045
1.119
1.109
5.506
0.086
0.002
0.105
8(a,q)*
Honolulu
1980
NR
24
1
0.002
0.093
0.571
6.129
0.130
0.001
0.019
8(a,q)*
Winnemucca
1980
NR
24
5
0.063
0.573
12.817
0.173
0.026
8(a,q)"
Portland
1980
NR
24
4
0.028
0.537
2.371
0.001
12.505
0.191
0.018
0.119
8(a,q)*
Seattle
1980
NR
24
1
0.006
0.292
0.952
0.001
4.424
0.091
0.093
References are listed in Table 1 Appendix. Associated notes are explained in Table 1.
"Values for this size fraction are calculated from the average measured values reported for the other two size fractions.
$Units for acidity are nmoles/m3.
NR = not reported.
-------
TABLE 6A-2c (cont'd). PM10 COMPOSITION FOR THE CENTRAL UNITED STATES Oig/m3)
Ref 8(a,q)*
Site Albuquerque
Dates 12/84-3/85
Time 7-19-7
Duration (h) 12
Number NR
Mass
OC
EC
Nitrate
Sulfate
Acidity*
Al
As
Ba
Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
P
Pb
13(q)*
Denver
1/11-30/82
6-18-6
12
-26
56.46
7.11
2.15
2.22
2.45
3.294
< 0.004
0.089
0.127
0.705
0.018
1.287
<0.018
0.018
1.033
0.727
0.031
0.008
0.155
0.424
14(m) 14(aa) 15(s)*
Urban Denver Non-urban Denver Chicago
11/87-1/88 11/87-1/88 7/94
9-16-9 9-16-9 8-8
7 & 17 7 & 17 24
-136 -150 16
28.54
5.39
1.31
5.46
0.269
< 0.0043
< 0.130
0.011
0.761
<0.041
0.047
< 0.0073
0.017
0.432
0.161
0.118
0.013
< 0.0041
0.022
<0.0018
0.035
0.032
16(q)*
Houston
9/10-19/80
NR
12
20
63.40
8.78
1.42
2.22
15.52
1.216
<0.015
0.139
0.091
2.935
<0.012
0.398
0.007
0.046
0.766
0.289
0.035
<1.49
0.008
0.128
0.589
6,7(p,q)
Harriman
5/80-5/81
00-24
24
256
32.50
8.10
0.052
1.800
0.050
0.690
0.038
0.001
0.237
17* 6,7(p,q)
Harriman Kingston
9/85-8/86 5/80-6/81
NR 00-24
24 24
330 169
30.00 35.40
8.70
36.1
0.056
0.960
0.018
0.360
0.027
ND
0.234
6,7(p,q)
Portage
3/79-5/81
00-24
24
271
18.20
5.30
0.014
0.380
0.083
0.230
0.009
0.001
0.074
6,7(p,q)
Topeka
8/79-5/81
00-24
24
286
26.40
4.80
0.055
2.400
0.031
0.580
0.020
0.001
0.203
8(a,q)*
El Paso
1980
NR
24
10
76.21
2.903
0.037
0.103
3.964
0.043
0.004
0.083
0.946
0.623
0.027
0.002
0.672
8(a,q)*
Inglenook
1980
NR
24
8
72.45
2.508
0.001
0.061
2.924
0.003
0.006
0.059
1.474
0.717
0.078
0.003
0.030
0.388
-------
TABLE 6A-2c (cont'd). PM10 COMPOSITION FOR THE CENTRAL UNITED STATES (jig/m3)
Ref 8(a,q)*
Site Albuquerque
Dates 12/84-3/85
Time 7-19-7
Duration (h) 12
Number NR
Rb
S
Sb
Se
Si
Sn
Sr
Ti
V
Zn
13(q)*
Denver
1/11-30/82
6-18-6
12
-26
0.005
0.709
<0.004
< 0.004
7.737
<0.004
0.009
0.09
<0.004
0.085
14(m) 14(aa) 15(s)*
Urban Denver Non-urban Denver Chicago
11/87-1/88 11/87-1/88 7/94
9-16-9 9-16-9 8-8
7 & 17 7 & 17 24
-136 -150 16
1.363
< 0.059
< 0.0017
0.813
< 0.070
0.019
<0.013
0.090
16(q>*
Houston
9/10-19/80
NR
12
20
< 0.006
4.83
0.006
< 0.003
3.200
0.036
<0.045
0.142
6,7(p,q)
Harriman
5/80-5/81
00-24
24
256
2.500
0.002
2.000
ND
17* 6,7(p,q)
Harriman Kingston
9/85-8/86 5/80-6/81
NR 00-24
24 24
330 169
2.400
0.002
1.900
ND ERR
6,7(p,q)
Portage
3/79-5/81
00-24
24
271
1.500
0.001
0.980
ND
6,7(p,q)
Topeka
8/79-5/81
00-24
24
286
1.200
2.500
ND
8(a,q)*
El Paso
1980
NR
24
10
1.072
0.003
5.813
0.080
0.112
8(a,q)*
Inglenook
1980
NR
24
8
2.969
0.001
6.997
0.116
0.188
-------
TABLE 6A-2c (cont'd). PM10 COMPOSITION FOR THE CENTRAL UNITED STATES Qtg/m3)
Ref
Site
Dates
Time
Duration (h)
Number
Mass
OC
EC
Nitrate
Sulfate
Acidity5
Al
As
ON
> Ba
i
$ Br
Ca
Cd
Cl
Cr
Cu
Fe
K
Mg
Mn
Mo
Na
Ni
8(a,q)*
Braidwood
1980
NR
24
1
56.90
2.020
0.002
0.006
1.490
0.002
0.044
0.727
0.355
0.018
0.002
8(a,q)*
Kansas City KS
1980
NR
24
8
70.33
2.144
0.003
0.036
4.371
0.010
0.048
0.989
0.660
0.026
0.005
8(a,q)*
Minneapolis
1980
NR
24
6
46.35
2.191
0.005
0.069
1.674
0.293
0.003
0.057
0.831
0.402
0.031
0.002
8(a,q)*
Kansas City MO
1980
NR
24
3
58.43
2.284
0.010
0.093
3.967
0.530
0.006
0.036
1.119
0.503
0.031
0.003
8(a,q)*
Akron
1980
NR
24
7
70.90
2.555
0.015
0.064
1.541
0.572
0.024
0.055
2.249
0.592
0.129
0.011
8(a,q)*
Cincinnati
1980
NR
24
2
62.95
2.972
0.013
0.041
1.374
0.103
0.005
0.038
1.057
0.499
0.032
0.007
8(a,q)*
Buffalo
1980
NR
24
14
83.32
3.000
0.009
0.015
2.768
0.728
0.017
0.048
2.711
0.516
0.111
0.017
8(a,q>*
Dallas
1980
NR
24
4
61.55
1.405
0.039
0.274
4.127
0.029
0.010
0.066
0.968
0.335
0.035
0.004
8(a,q)*
St. Louis
1980
NR
24
5
56.82
3.956
0.004
0.046
1.874
0.053
0.001
0.032
0.663
0.417
0.019
0.004
18(x)*
St. Louis
8-9/76
NR
6-12
62.00
1.412
0.003
0.054
0.179
2.949
0.005
0.344
0.015
0.043
1.493
0.653
0.071
0.009
6,7(p,q)
St. Louis
9/79-6/81
00-24
24
306
31.40
8.10
0.099
1.600
0.145
0.770
0.040
0.005
17* 6,7(p,q)
St. Louis Steubenville
9/85-8/86 4/79^/81
NR 00-24
24 24
311 499
27.60 46.50
8.00 12.80
9.7
0.052
1.120
0.303
2.200
0.068
0.008
-------
TABLE 6A-2c (cont'd). PM10 COMPOSITION FOR THE CENTRAL UNITED STATES (jig/m3)
Ref
Site
Dates
Time
Duration (h)
Number
P
Pb
Rb
S
Sb
Se
Si
Sn
>. Sr
U> Ti
V
Zn
8(a,q)*
Braidwood
1980
NR
24
1
0.014
0.054
2.632
0.002
5.987
0.083
0.023
8(a,q)*
Kansas City KS
1980
NR
24
8
0.013
0.237
2.031
0.001
4.976
0.076
0.060
8(a,q)*
Minneapolis
1980
NR
24
6
0.406
1.131
0.001
4.848
0.062
0.072
8(a,q)*
Kansas City MO
1980
NR
24
3
0.478
1.043
4.986
0.074
0.086
8(a,q)*
Akron
1980
NR
24
7
0.059
0.509
3.870
0.008
5.531
0.116
0.219
8(a,q)*
Cincinnati
1980
NR
24
2
0.080
0.442
3.265
0.005
6.961
0.099
0.201
8(a,q)*
Buffalo
1980
NR
24
14
0.060
0.467
4.471
0.005
2.916
0.051
0.001
0.121
8(a,q)"
Dallas
1980
NR
24
4
0.018
1.318
1.754
3.652
0.058
0.002
0.084
8(a,q)*
St. Louis
1980
NR
24
5
0.020
0.372
2.612
0.002
4.638
0.058
0.044
18(x)*
St. Louis
8-9/76
NR
6-12
0.099
0.877
0.002
5.188
0.007
0.005
4.928
0.010
0.009
0.587
0.006
0.175
6,7(p,q)
St. Louis
9/79-6/81
00-24
24
306
0.415
2.300
0.002
2.100
ND
17* 6,7(p,q)
St. Louis Steubenville
9/85-8/86 4/79-4/81
NR 00-24
24 24
311 499
0.259
5.500
0.005
2.300
0.013
References are listed in Table 1 Appendix. Associated notes are explained in Table 1.
"Values for this size fraction are calculated from the average measured values reported for the other two size fractions.
$Units for acidity are nmoles/m3.
NR = not reported.
-------
TABLE 6A-3. SELECTED RATIOS OF PM COMPOSITION BY
GEOGRAPHIC REGION
EAST
FM/CM
FM/PM10
Tot Carbon/FM
SO4= /FM
Mean
2.59
0.65
0.25
0.34
N
8
8
7
12
WEST
Mean
0.89
0.41
0.54
0.11
N
11
11
5
13
CENTRAL
Mean
1.06
0.51
0.64
0.28
N
25
25
5
28
N = number of studies contributing to the calculated ratios.
FM, CM, PM10 = Mass concentrations of PM2 5, Coarse fraction, and PMi0 respectively.
Total Carbon = (OC x 1.4 + EC).
6A-37
-------
u>
00
Study Area
No. of Sites
Study Dates
Reference
Fine Mass
OC
EC
Nitrate
Sulfate
Al
Br
Ca
Cl
Cr
Cu
Fe
K
Mn
Ni
Pb
S
Si
Ti
V
Zn
TABLE 6A-4a.
Denver Metropolitan
3,a
11/2/87- 1/31/88
14
Mean
19.672
7.245
4.409
3.956
1.547
0.037
0.018
0.058
0.141
0.003
0.017
0.111
0.077
0.012
0.002
0.075
0.642
0.272
0.009
0.031
Spread
2.889
0.789
0.780
0.931
0.162
0.006
0.006
0.001
0.013
0.002
0.008
0.023
0.009
0.003
0.002
0.017
0.077
0.009
0.001
0.008
SITE-TO-SITE VARIABILITY OF PM2 5 CONCENTRATIONS
Phoenix
3,b
10/13/89 - 1/17/90
11
Mean
29.379
10.089
7.490
3.597
1.329
0.131
0.011
0.167
0.366
0.003
0.015
0.216
0.209
0.023
0.003
0.039
0.436
0.430
0.056
Spread
3.493
2.690
1.710
0.370
0.240
0.015
0.003
0.034
0.356
0.001
0.003
0.035
0.020
0.010
0.001
0.009
0.038
0.066
0.030
Philadelphia
4,c
7/25/94 - 8/14/94
3
Mean
32.183
4.164
0.685
13.426
0.114
0.009
0.058
0.026
0.007
0.127
0.060
0.003
0.007
0.019
3.251
0.165
0.019
0.041
Spread
2.172
0.935
0.215
0.333
0.009
0.005
0.014
0.007
0.001
0.037
0.008
0.000
0.002
0.010
0.081
0.022
0.003
0.018
San Joaquin Valley
6,d
6/14/88 - 6/9/89
10
Mean
29.888
4.873
3.242
8.165
3.003
0.152
0.010
0.096
0.094
0.003
0.096
0.180
0.188
0.006
0.016
0.029
1.242
0.460
0.017
0.015
0.078
Spread
10.020
2.695
2.580
2.270
1.325
0.055
0.006
0.050
0.070
0.002
0.036
0.060
0.080
0.003
0.030
0.021
0.565
0.245
0.004
0.028
0.027
Mean = Mean over all sites of the average concentrations determined at each site for the sampling period.
Spread = ABS ({Highest Mean Cone. - Lowest Mean Conc.}/2) for all the sites.
a. Federal, Auraria, and Welby sites in urban Denver.
b. Central Phoenix, Scottsdale, and Western Phoenix sites.
c. Broad Street, Castor Avenue, Roxboro, and Northeast Airport sites.
d. Stockton, Crow's Landing, Fresno, Kern, Fellows, and Bakersfield sites.
-------
TABLE 6A-4b. SITE-TO-SITE VARIABILITY OF PM10 CONCENTRATIONS
Study Area
No. of Sites
Study Dates
Reference
Fine Mass
OC
EC
Nitrate
Sulfate
Al
Br
Ca
Cl
Cr
Cu
Fe
K
Mn
Ni
Pb
S
Si
Ti
V
Zn
San Jose
2,a
12/16/91 -
29
Mean
64.950
19.390
9.015
10.900
2.240
0.845
0.012
0.670
0.728
0.003
0.029
0.834
0.823
0.014
0.003
0.035
1.147
2.905
0.088
0.007
0.065
2/24/92
Spread
1.650
0.150
0.415
0.600
0.090
0.035
0.001
0.049
0.032
0.001
0.002
0.027
0.021
0.001
0.000
0.004
0.091
0.045
0.024
0.003
0.005
Phoenix
3,b
10/13/89 -
11
Mean
62.465
14.549
8.327
4.459
1.704
2.670
0.014
2.096
0.559
0.011
0.036
1.475
0.878
0.054
0.006
0.062
0.615
7.442
0.121
0.090
1/17/90
Spread
7.064
3.481
1.777
0.452
0.287
0.273
0.003
0.317
0.349
0.002
0.009
0.170
0.083
0.014
0.002
0.013
0.041
0.862
0.024
0.034
San Joaquin Valley
6,c
6/14/88 -
10
Mean
62.920
7.870
3.505
9.437
3.565
2.993
0.012
0.950
0.388
0.009
0.084
1.413
0.720
0.030
0.019
0.039
1.472
7.517
0.128
0.022
0.085
6/9/89
Spread
17.280
4.150
2.760
3.015
1.460
1.570
0.005
0.390
0.225
0.003
0.046
0.445
0.220
0.011
0.032
0.027
0.605
1.765
0.033
0.031
0.029
Mean = Mean over all sites of the average concentrations determined at each site for the sampling period.
Spread = ABS ({Highest Mean Cone. - Lowest Mean Conc.}/2) for all the sites.
a. San Carlos St. and Fourth St. sites.
b. Central Phoenix, Scottsdale, and Western Phoenix Sites.
c. Stockton, Crow's Landing, Fresno, Kern, Fellows, and Bakersfield sites.
6A-39
-------
7. HUMAN EXPOSURE TO PARTICULATE MATTER:
RELATIONS TO AMBIENT AND INDOOR
CONCENTRATIONS
7.1 INTRODUCTION
The 1982 Air Quality Criteria Document for Paniculate Matter and Sulfur Oxides
(U.S. Environmental Protection Agency, 1982) thoroughly reviewed the PM exposure
literature through 1981. The later "Second Addendum to Air Quality Criteria for Particulate
Matter and Sulfur Oxides (1982)" (U.S. Environmental Protection Agency, 1986a) added
coverage of newly available health effects information up to 1986. This chapter first
summarizes key points from the 1982 Criteria Document, and then thoroughly reviews the
PM exposure literature from 1982 through 1995 and includes some literature published and
in press through February, 1996.
The U.S. Environmental Protection Agency (U.S. EPA) regulatory authority for PM
only extends to the ambient air, defined in 40 CFR 50.1(e) as that portion of the atmosphere,
external to buildings, to which the general public has access (Code of Federal Regulations,
1994). By the operative definition of ambient air, polluted air inside a building, or on
private property owned or controlled by the source of pollution, is not regulated by the
National Ambient Air Quality Standards (Costle, 1980; Bennett, 1983). However, it is
necessary to consider total personal exposure to PM, both from the regulated ambient air and
non-regulated indoor air. This is because ambient (outdoor) particles penetrate into non-
ambient environments (indoors) where people spend approximately 85% of their time (U.S.
Environmental Protection Agency, 1989). Therefore, when people are indoors, they are
exposed to a mixture of ambient PM and particles generated indoors from non-regulated
sources, such as PM from cigarette smoke and personal activities.
Personal exposure to total PM is important in itself, because the body may react
differently to ambient and non-ambient particles of identical size but different chemical
composition. Comparison of personal exposures to indoor and outdoor concentrations may
provide clues as to whether or not these two types of PM have similar toxicity on a unit size
and mass basis. Personal exposure may also act as a confounder in epidemiological studies
7-1
-------
which use an inferred community exposure to ambient PM as a parameter to correlate with
community health parameters, and an individual's personal exposure to total PM is a critical
parameter for analysis if that person is a member of a cohort whose health outcomes are
being tracked individually. Therefore, this chapter examines not only indoor air quality in
regard to PM, but also community and individual exposures to PM, which include that
portion of ambient PM which penetrates into indoor microenvironments (^Es). This is to aid
in interpretation of acute and chronic epidemiology studies assessed in Chapter 12, in which
ambient PM concentrations are assumed to be an indicator or a surrogate for mean
community exposure to ambient PM or an individual exposure to ambient PM. Thus, this
chapter has three objectives: (a) to provide a review of pertinent studies of indoor and
personal exposures to PM; (b) to evaluate linkages between monitored personal exposures
and exposures estimated from a fixed-site monitor located at some central monitoring site;
and (c) to quantify the contribution of ambient air to personal PM exposure.
In this chapter, Sections 7.1.1-7.1.3 discuss the concept of ambient PM as a surrogate
for a personal exposure and the relationship of a measured personal PM exposure to the
ambient and nonambient concentrations of PM that may influence it.
Section 7.2 next reviews PM concentrations found indoors where people spend about
85% of their time (U.S. Environmental Protection Agency, 1989). This subject is discussed
in detail because of the importance of indoor conditions for understanding total exposure to
PM. Indoor air particles from indoor sources may be an important factor in the analysis and
interpretation of epidemiology studies, because they may influence both the personal PM
exposure and personal health of the exposed people.
Section 7.2.5 reviews the literature covering biological aerosols, which may produce
direct health effects or act as a source of antigens capable of sensitizing people to the effects
of other PM exposures.
Section 7.3 reviews the fundamental principles of personal PM monitoring and factors
that influence the personal PM measurement.
Section 7.4 covers the literature on direct measurements of personal exposures to PM
and PM constituents such as sulfates.
7-2
-------
Section 7.5 reviews the literature on indirect exposure estimation procedures that
predict exposures from time-weighted averages of concentrations measured indoors and
outdoors.
Section 7.6 discusses the relationship of individual PM exposures to ambient PM
concentrations and establishes a linkage between average personal PM exposures in a
community to the ambient PM concentrations.
Section 7.7 discusses implications of PM exposure relationships for mortality and
morbidity analyses.
Section 7.8 provides a Summary of Conclusions for Chapter 7.
7.1.1 Ambient Particulate Matter Concentration as a Surrogate for
Particulate Matter Dosage
The health effects of PM experienced by an individual depend upon the mass, size and
composition of those particles deposited within various regions of the respiratory tract during
the time interval of interest. The amount of this potential dose will depend on the
concentration inhaled (e.g., the instantaneous personal exposure); the ventilation rate
(a function of physical activity and basal metabolism); and the fractional deposition, which is
a function of ventilation rate, mode of breathing (e.g., oral or nasal), and any alterations due
to lung dysfunction. If all people had identical ventilation rates and deposition patterns, then
the potential-dosage distribution could be linearly scaled to the personal exposure distribution
which would serve as a suitable primary surrogate. The usage of ambient PM concentration
in health studies as a surrogate for personal PM exposure, and thereby a secondary surrogate
for the PM dosage, would be suitable if ambient concentration was also linearly related to the
personal exposure (Mage, 1983).
Adult ventilation rates are lowest (mean « 6 L/min) during the night while asleep, at a
maximum (mean « 12 L/min; peak = 60 L/min) during the day while awake
(Adams, 1993), and in phase with PM exposure, which is also lower at night than during the
day (Clayton et al., 1993). Consequently, the product of the 24-h average PM exposure, the
24-h average ventilation rate, and the average deposition parameter for the average
ventilation would seriously under-predict the amount of PM deposited in the respiratory tract
(Mage, 1980).
7-3
-------
In practice, when relating human health to PM pollution variables (as in Chapter 12)
one is forced to use time-weighted-average (TWA) ambient PM concentration as a surrogate
for PM exposure and PM dosage because only fragmentary data are typically available on
personal exposures to PM in populations. Data are also limited on ventilation rates as a
function of basal metabolism and physical activities (Adams, 1993), as are data on pulmonary
deposition rates of particles people are inhaling, since the size distribution is unknown and
deposition is affected by unmeasured individual physiological parameters. According to
Hodges and Moore (1977), "even when an explanatory variable (ambient PM concentration)
can be measured with negligible error it may often be standing as a proxy for some other
variable (dosage) which cannot be measured directly, and so it (dosage) is subject to
measurement error". Pickles (1982) shows "that (such) uncertainties in air pollution levels
lead to two kinds of error in the air pollution/mortality regression coefficient - a systematic
underestimate and a random scatter". In addition, measurement error can also bias a
threshold in the dose-response function towards zero (Yoshimura, 1990).
In the sections that follow, the relationships between ambient PM concentration, indoor
PM concentrations and personal exposures to PM are discussed hi detail. The following five
caveats should be kept in mind while reading this chapter:
1. Ambient PM concentrations are often measured as a 24-h time-weighted-average
(TWA) expressed as /ig/m3. This quantity, by necessity, is assumed to be a
surrogate for the mass of ambient PM deposited hi people's respiratory tracts per
unit body weight, expressed as jig/kg-day.
2. This daily quantity of ambient PM deposited per unit body weight is in turn a
surrogate for the amount of the true (but unknown) species and/or size fraction of
the total PM that is the specific etiologic toxic agent(s) that act by a presently
unknown mechanism. This latter quantity should be the independent variable for
delineating underlying relationships between ambient PM TWA concentrations to
the health indices used as the dependent variables.
3. Virtually all analyses and discussions of exposure presented here are based on
personal exposure to PM of non-smokers. Only Dockery and Spengler (1981b)
included 6 smokers out of 37 subjects. Smokers are often excluded from these
studies because a personal exposure monitor (PEM) on a smoker will not capture
the main-stream tobacco smoke that is directly inhaled. In Section 7.2 on indoor air
pollution, it is shown that side-stream environmental tobacco smoke (ETS) is the
largest identifiable indoor source of PM where smoking occurs. For the average
smoker, the amount of direct inhalation (several milligrams of PM per cigarette) can
be two-to-three orders of magnitude greater than the microgram amounts of ETS
7-4
-------
which the PEM captures (Federal Trade Commission, 1994). The relationships
presented below, of ambient PM concentration to individual total PM exposure,
therefore only apply to non-smokers.
4. A total TWA personal exposure to PM (ambient PM plus indoor PM) will be a poor
surrogate for the personal exposure to PM of ambient origin for those people whose
personal exposures are dominated by indoor (residential and occupational) sources,
such as ETS.
5. All studies of indoor concentrations and personal exposures described below
evaluated subjects recruited either in a nonrandom manner or in a scientific
probability sampling scheme. In the former case, the results cannot be extrapolated
with confidence beyond the subjects themselves. In the latter case, the results can
be extrapolated with a known confidence to the target population from which the
sample was drawn. However, in both cases, there is a cohort of people who are
nonresponders. If the reason for their refusal to participate in the survey is directly
or indirectly related to their PM exposure, then the study results represent a sample
with a bias of unknown sign and magnitude.
7.1.2 General Concepts for Understanding Particulate Matter Exposure
and Microenvironments
Particulate matter represents a generic class of pollutants which requires a different
interpretation of exposure in contrast to that for the other specific criteria gaseous pollutants,
such as CO (Mage, 1985). Whereas a molecule of CO emitted from a motor vehicle is
indistinguishable from a molecule of CO emitted from a fireplace, a l-/xm aerodynamic
diameter (AD) particle emitted from a motor vehicle and a 1-^im particle emitted from a
fireplace can have a different shape, mass, chemical composition, and/or toxicity. Thus,
a "particle" can be a single entity, or an agglomeration of smaller particles, such as a small
Pb particle bound to a larger crustal particle. Furthermore, indoor sources of particles
produce a wide variety of particles of varying size and composition that people are exposed
to, as shown in Figure 7-1 (Owen et al., 1992). Given that the health effects of inhalation of
any particle can depend upon its mass and chemical composition, it would be of use to
measure PM exposure in terms of mass and chemical composition as a function of size
distribution (Mage, 1985).
The total PM exposure of an individual during a period of time is composed of
exposure to many different particles from various sources in different microenvironments
(/xE). A pE was defined by Duan (1982) as "a chunk of air space with homogeneous
7-5
-------
Particle Diameter (urn)
0
Plant
Animal
Mineral
Combustion
Home/
Personal
Care
Radioactive
.01 0.1 1 10 100 1.000
- Coffee Roast Soot "4 Jjlold ^. Coffee ^.
^ Starches ^
- nnmxtnmh ». ^ Milled Flow. <3rourjo^Corn_ »- "" Grain Dusts
.MusWlg. ^Ginger g Tea Dust
-_ Carbon Black -* ^ *"
~~ ^ Channel Black ^
^ Pudding Mix ^Com Cob Chaff » ^
^ Snuff •» - ^ Cayenne Pepper »
Bacteriophage -« Droplet Nuclei 1 ^ Bacteria
^ * ^ ^ Gelatin ^ ,,
> V1""""5 »» Spider Web ""^ Hair " ^
•^ ** Spray Dried Milk • ni.«» UM«»
•* »• Disintegrated Feces •* i=i^ ^ •< Bu*1 Nll'es »
" — r-eces Bono Dust ^
_ Asbestos _
-< Clay * »- ^
^ ^Caldum. Zinc • Lead Dust ^ "
MMMF' ~ Special Use insulation ^ Fiberglass C3ia»» wool -^
MetaJuraical Dusts and Fumes Textiles ^ ^ »* FettlllZBT, Ground Limnstona ^
- NH^CI Fume fc Cement Dust ^
^ SeaSalt »»
_, Tobacco Smoke ^
Burnlna Wood
^ Rosin Smoke "* *" Smouldering or Flaming Cooking Oil
"* Coal Flue Qas - °" Sm°ke Fly Ash
^— - = Spray Paint Spray pa]nt Dus,
^ Air Freshener ^ *
" Anti-Stick Sorav L.
- Humidifier £ < Fabric Protector
. . _. -" ^ ^ Nebulizer Droos to
— Paint Pigments ^ ^ ^
;, Alkali Fume « Insecticide Du^ts > ^-^ Emolllems
Face Powder: > ^^ »• Clumps ^ ^ MoCO, ^
CnniarTonm- Pioment fc „ Binder
Copier Toner. ,- •• - ^ ».Artlflclal Textile Fibers
— Radon Progeny ^
1 Liquid droplets containing bacteria etc.. sneezed. Me
2 Man-made mineral fibers
Figure 7-1. Sizes of various types of indoor particles.
Source: Owen et al. (1992).
-------
pollutant concentration"; it has also been defined (Mage, 1985) as a volume in space, during
a specific time interval, during which the variance of concentration within the volume is
significantly less than the variance between that fiE and its surrounding jiEs. For example, a
kitchen with a wood stove can constitute a single pE for total PM when the stove is off, and
all people in the kitchen would have similar PM exposures. When the stove is in operation,
the kitchen could have a significant vertical PM concentration gradient and a child on the
floor in a far corner and an adult standing at the stove could be exposed to significantly
different PM concentrations.
In a given pE, such as one in the kitchen example, the particles may come from a wide
variety of sources. PM may be generated from within (e.g. the stove, deep frying, burning
toast), from without (ambient PM entering through an open window), from another indoor
/iE (cigarette smoke from the living room), or from a personal activity that generates a
heterogeneous mix of PM (sweeping the kitchen floor and resuspending a mixture of PM
from indoor and outdoor sources that had settled out).
In general, as people move through space and time, they pass through a series of /iEs
and their average total exposure (X /xg/m3) to PM for the day can be expressed by the
following equation,
X = EXjtj/Etj (7-1)
where X4 is the total exposure to PM in the Ith /wE, visited in sequence by the person for a
time interval tt (Mage, 1985).
With appropriate averaging over sets of 4 classes of jtEs (e.g., indoors,
ambient-outdoors, occupational, and in-traffic) Equation 7-1 can be simplified as follows
(Mage, 1985):
**• = (Xjn tin + Xout tout + Xocc tocc + Xtra ttjj) / T (7-2)
where each value of X is the mean value of total PM concentration in the j*E class while the
subject is in it, tune (t) is the total time the subject is in that /iE during the day, and T is
equal to the sum of all times (usually one day). Similar equations may be written for
personal exposures to particles from specific sources (e.g., diesel soot), for specific
chemicals (e.g., Pb), or for specific size intervals (PM < 2.5 /mi AD).
7-7
-------
Many excellent studies have reported data on air quality concentrations in pE settings
that do not meet a rigorous definition of an exposure, which requires actual occupancy by a
person (Ott, 1982). Section 7.2, on Indoor Concentrations and Sources of PM, cites
Thatcher and Layton (1995) who report that "merely walking into a room increased the
particle concentration by 100%". Consequently, an integrated measurement of air quality in
an enclosed space that includes time when it is unoccupied may not be a valid measure that
can be used to estimate an exposure while occupied. If this measure includes periods of time
when the space is unoccupied, it will tend to be biased low as a measure of the exposure
within it during periods of occupancy. For example, it is incorrect to associate an average
PM exposure to a person while cooking at a stove hi a kitchen with a kitchen concentration
measurement that is influenced by periods when the stove was off (Smith et al., 1994).
The literature on 24-h average PM concentrations in indoor /tEs, such as residential
settings, is treated separately in Section 7.2, as is done for 24-h average ambient PM
concentrations in Chapter 6. In the exposure portion of this chapter, specific reference is
made to some studies where simultaneous personal PM exposures and indoor PM
measurements have been made, so that the relationship between indoor concentration and
personal exposure can be examined.
In practice, a cascade sampler can collect ambient PM samples by size fractionation for
separate chemical analyses, but such a complete definition of personal exposure to PM by
chemistry and size is difficult to obtain. Although some personal monitors can be equipped
with a cyclone or impactor separator and several filters to capture several PM sizes (e.g.,
<2.0 /am, 2.0 to 10 pirn, and > 10 /xm; Tamura et al., 1996), most published studies of PM
exposure used a PEM with a single integrated measurement of particle mass collected (e.g.,
<2.5 pm or < 10 /mi). Consequently, health studies on individuals are usually only able to
develop associations between their observed health effects and their observed exposure
expressed as an integral mass of PM collected and its average chemical composition.
Health studies on populations can make multiple measurements of ambient and indoor
PM concentrations simultaneously (e.g., PM2 5, PM10, TSP) along with components of PM,
such as polycyclic aromatic hydrocarbons (PAHs), to help understand the size distribution
and chemistry of the particles in the ambient and indoor atmospheres.
7-8
-------
7.1.3 Summary of State-of-Knowledge in the 1982 Criteria Document
In 1982 it was known, from personal monitoring and indoor monitoring, that SC^ is
almost always lower indoors than outdoors because of the virtual absence of indoor sources
and the presence of sinks for SO2 in indoor settings (exceptions can occur if high sulfur coal
or kerosene are used as fuel in a poorly vented stove or space heater). However, this
relationship does not hold for PM, as the indoor and personal monitoring data show both
higher- and lower-than ambient PM concentrations in indoor settings as a function of particle
size and human activity patterns.
The largest coarse mode particles (> 10 pirn), which are generally of nonanthropogenic
origin (wind blown dust, etc.), require turbulence to provide vertical velocity components
greater than their settling velocity to allow them to remain suspended in the air (Figure 7-1).
Outdoor particles enter into an indoor setting either by bulk flow, as through an open
window, in which all particles can enter at the inlet condition, or by pressure driven drafts
and diffusional flows through cracks and fissures in the barriers of the building envelope
when all windows are closed. In the latter mode of entry, velocities are relatively lower,
thereby settling out the largest coarse particles (> 25 /xm AD) in the passage through the
barriers (Thatcher and Layton, 1995).
Indoor settings are usually quiescent (Matthews et al., 1989), and ambient particles that
enter indoors quickly settle out by gravity or electrostatic forces, leading to familiar dust
layers on horizontal surfaces and vertical TV screens that require constant cleaning
(Raunemaa et al., 1989). However, human activity in indoor settings, such as smoking,
dusting, vacuuming and cooking, does generate fine particles (<2.5 /im) and coarser
particles (>2.5 /im) and resuspends coarse particles (> 10 p.m) that previously had settled
out (Thatcher and Layton, 1995; Litzistorf et al., 1985).
Only three studies of personal PM exposures, compared to ambient PM concentrations,
were referenced in the 1982 Criteria Document (U.S. Environmental Protection Agency,
1982). Binder et al. (1976) reported that "outdoor air measurements do not accurately reflect
the air pollution load experienced by individuals who live in the area of sampling", in a study
in Ansonia, CT, where personal exposures to PM5 were double the outdoor PM
concentrations measured as TSP (115 versus 58 /ig/m3). Spengler et al. (1980) was cited as
reporting that "there was no correlation [R2 = 0.04] between the outdoor level [of respirable
7-9
-------
particles] and the personal exposure of individuals" in a study in Topeka, KS. Figure 7-2,
from Repace et al. (1980), was cited as an example of the variability of PM exposures which
show very little influence of ambient concentration. Thus, at the time of the 1982 Criteria
Document, two major factors were known to influence ambient PM relationships to indoor
PM air quality: (1) the variability of indoor levels of PM compared to outdoor
concentrations as a function of particle size (e.g., fine indoor > fine outdoor, and coarse
indoor < coarse outdoor); and (2) the variation of exposures of individuals related to
different activities involved in local generation of particles in their immediate surroundings
(smoking, traffic, dusting and vacuuming at home, etc.). This understanding was
summarized on pg. 5-136 of the 1982 Criteria Document, as follows:
• long term personal exposures to fine fraction PM (<2.5 jtrn) of outdoor origin, may
be estimated by ambient measurements of the <2.5 /zm PM fraction.
Personal activities and indoor concentrations cause personal exposures to PM to vary
substantially. Ambient measurements appear to be a poor predictor of personal
exposure to PM.
Tobacco smoke is an important contributor to indoor concentrations and personal
exposures where smoking takes place (U.S. Environmental Protection Agency,
1982).
7.2 INDOOR CONCENTRATIONS AND SOURCES OF PARTICIPATE
MATTER
7.2.1 Introduction
Although EPA regulates particles in ambient air, which excludes the air internal to
buildings, it is still important to consider indoor air. Most people spend most of their time
indoors. A U.S. Environmental Protection Agency (1989) report indicates that U.S.
residents spend 85.2% of their time indoors, 7.4% in or near a vehicle, and only 7.4%
outdoors. Also, it is important to understand how outdoor particles are affected as they cross
building envelopes. For a home with no indoor sources, how much protection is offered
against particles of various size ranges? How do parameters such as volume of the house,
air exchange rate, cleaning frequency and methods, and materials in the home affect
7-10
-------
280
260
240
220
CO
E 200
?180
160
140
120
100
80
60
40
20
0
I
o
O
I I I I I I I I I I I I I I I I I I I I I I T
• Indoors
• In Transit
O Outdoors
Cafeteria, Smoking Section
Behind Smoky Diesel Truck
Office
Commuting • ^ ^
. Bedroom .Ji
Well-Ventilated Kitchen
Outside Cigar
Smoker's Office
Street Suburbs, Outdoor
Suburbs
Vehicle
In City
I I I I I I I
Library. Unoccupied Cafeteria
Cafeteria,
Nonsmoking
Section
Sidewalk
edroom
Livin_ _
Commuting Room —
Suburbs _
ogging
Living. Room
Dining ~i
;oom
City, Outdoor
I I I I
12 1
Midnight
234
567
A.M.
8 9 10 11 12 1
Noon
Time of Day
Figure 7-2. An example of personal exposure to respirable particles.
234
567
P.M.
8 9 10 11 12
Source: Repace et al. (1980).
-------
concentrations of particles of outdoor origin? This section has several parts that address
these questions.
The first part (7.2.2; 7.2.3; and 7.2.4) deals with field studies of particles indoors and
outdoors, focussing mainly on large-scale surveys of many homes and buildings. Besides
presenting observed indoor and outdoor particle concentrations, information on important
parameters such as air exchange rates, source emission rates, and deposition rates is also
reported. This section also discusses a few studies dealing with inorganic and organic
constituents of particles, as well as other considerations such as the role of house dust in
exposure to metals. Section 7.2.3 provides a brief introduction to indoor air quality models.
Finally, Section 7.2.4 summarizes the main findings.
The second part (7.2.5) is a discussion of bioaerosols from plants, molds, insects, etc.
Although these sources of PM are uncontrolled by EPA, they affect measured PM indoors
and can potentiate the effects of PM from other sources through allergenic properties.
In keeping with EPA's regulatory responsibilities, the many studies in industrial
workplaces and the "dusty trades" are omitted, as are studies of lead (Pb) in indoor locations,
since lead is a separate criteria pollutant and such studies are reviewed in a separate lead
criteria document (U.S. Environmental Protection Agency, 1986b).
7.2.2 Concentrations of Particles in Homes and Buildings
At least seven major reviews of field studies of indoor particles have been published
since 1980 (Sterling et al., 1982; National Research Council, 1986; Repace, 1987; Guerin
et al., 1992; U.S. Environmental Protection Agency, 1992; Holcomb, 1993; Wallace, 1996).
The last of these reviews reports on several recently completed important studies, including
EPA's major probability-based PTEAM Study. Since the two microenvironments where
people spend the most time are (a) home and (b) work or school, studies of these
environments are summarized in turn, with emphasis on the former.
7.2.2.1 Particle Concentrations in Homes: Large-Scale Studies in the United States
There have been three large-scale studies (greater than 150 homes) of airborne particles
inside U.S. homes. In chronological order, these are:
7-12
-------
1. The Harvard Six-City study, carried out by the Harvard School of Public Health
from 1979 through 1988, with measurements taken in 1,273 homes;
2. The New York State ERDA study, carried out by Research Triangle Institute (RTI)
in 433 homes in two New York State counties during 1986;
3. The EPA Particle TEAM (PTEAM) study, carried out by RTI and Harvard School
of Public Health in 178 homes in Riverside, CA in 1990.
The findings of each are discussed in detail, since these studies present the most complete
investigations to date of indoor and outdoor concentrations of particles.
7.2.2.1.1 The Harvard Six-City Study
The Harvard Six-City Study is a prospective epidemiological study of health effects of
particles and sulfur oxides. Focused mainly on children, it has included pulmonary function
measurements on more than 20,000 persons in the six cities, chosen to represent low
(Portage, WI and Topeka, KS), medium (Watertown, MA and Kingston-Harriman, TN), and
high (St. Louis, MO and Steubenville, OH) outdoor particle and sulfate concentrations.
The study took place in two measurement phases. The first involved monitoring of
about 10 homes in each city for respirable particles (PM3 5), with measurements made every
sixth day (24-h samples) for one to two years. In the second phase, a larger sample of 200
to 300 homes was selected from each city, with week-long PM2 5 samples collected both
indoors and outdoors during two weeks of sampling in summer and winter. Ultimately,
more than 1,200 homes were monitored in this way.
Spengler et al. (1981) described the first five years of the study. During the Phase I
period, pulmonary function measurements were made for 9,000 adults, and 11,000 children
in grades 1 through 6. In each home, a 24-h sample (beginning at midnight) was collected
every sixth day, using a cyclone sampler with a cut point of »3.5 /im at a flow rate of
1.7 Lpm. About 10 sites in each city were kept hi operation for two years. The annual
mean indoor and outdoor PM3 5 concentrations are shown in Figure 7-3. The indoor
concentrations exceeded the outdoor levels in all cities except Steubenville, OH, where the
outdoor levels of about 46 jug/m3 slightly exceeded the indoor mean of about 43 ^g/m3. The
authors noted that the major source of indoor particles was cigarette smoke, and categorized
their data by number of smokers in the home (Table 7-1).
7-13
-------
II IWV
140j-
100
<9
E 80
1
S
o.
40
20
—
(376)
X
' VVJ'-'C7
0
(1
(342)
00)
X
X
-
2£
X
)
V,
X
ond
highest
(183)
X
WUIUUWI
( ) No. of samples
B«— Highest site mean
*— Composite overall mean
4 — Lowest site mean
C
(274)
86)
X
!|j%B
P T K W SL S
P T K W SL S
Figure 7-3. The annual mean concentration of respirable particles (PM3 5) for the
highest and lowest site from the network of indoor and outdoor monitors in
each city (P-Portage, T-Topeka, K-Kingston/Harriman, W-Watertown,
SL-St. Louis, S-Steubenville) in the Harvard Six-City study. Overall
composite mean and the number of samples are also shown.
Source: Spengler et al. (1981).
TABLE 7-1. CONCENTRATIONS OF PARTICLES (PM3 5) IN HOMES OF
CHILDREN PARTICIPATING IN THE HARVARD SIX-CITY STUDY
Location
No. of Homes
No. of Samples Mean (SD) G*g/m3)
Indoors
No smokers
One smoker
Two or more smokers
Outdoors
35
15
5
55
1,186
494
153
1,676
24.4(11.6)
36.5 (14.5)
70.4 (42.9)
21.1 (11.9)
Source: Spengler et al. (1981).
7-14
-------
Dockery and Spengler (1981a) provided additional data analyses drawn from the same
study but including data from 68 homes compared to the 55 reported on in Spengler et al.
(1981). Annual (every sixth day) mean indoor PM3 5 concentrations (in /ig/m3) were 20 and
23 in the two "clean" locations (Portage and Topeka); 31 and 36 in the two "medium"
locations (Watertown and Kingston-Harriman); and 39 and 47 in the two "dirty" locations
(Steubenville and St. Louis). Outdoor PM2 5 concentrations measured by dichotomous
samplers every other day ranged from 13 /ng/m3 in Portage and Topeka to 20 /xg/m3 in St.
Louis, 24 jig/m3 in Kingston-Harriman, and 36 /xg/m3 in Steubenville (Spengler and
Thurston, 1983). A mass balance model allowed estimation of the impact of cigarette
smoking on indoor particles. Long-term mean infiltration of outdoor PM3 5 was estimated to
be 70% for homes without ah* conditioners, but only 30% for homes with air conditioners.
A contribution of 0.88 /ig/m3 per cigarette (24-h average) was estimated for homes without
air conditioning; for homes with air conditioning, it increased to 1.23 pig/m3 per cigarette.
A residual amount of 15 ^ig/rn3 not explained by the model was attributed to indoor sources
such as cooking, vacuuming and dusting.
From the one to two years of indoor-outdoor data on 57 homes in the six cities, Letz
et al. (1984) developed an equation relating indoor to outdoor particle concentrations:
Cm = 0.385 Cout + 29.4 (Smoking) + 13.8.
Thus, homes with smokers had a PM3 5 ETS component of 29.4 /ig/m3. The residual of
13.8 /^g/m3 was assumed to be due to other household activities.
Neas et al. (1994) presented summary results for the entire Phase 2 of the Six-City
Study (1983 to 1988). In Phase 2, for 1,237 homes containing white, never-smoking
children, 7 to 11 years old at enrollment, three questionnaires were completed and two weeks
of summer and whiter monitoring indoors and outdoors for PM2 5 was done, using the
Harvard PM2 5 impactor. At the start of the indoor monitoring study, 55% of the children
were exposed to ETS in the home, and 32% were exposed to two or more smokers.
Household smoking status changed for 173 children, (13% of smoking households ceased to
smoke, and 15% of the nonsmoking households became smoking ones). The annual (winter
and summer) household PM2 5 mean concentration for the 580 children living in consistently
smoking households was 48.5 ± 1.4 (SE) /ig/m3 compared to 17.3 ± 0.5 /ig/m3 for the
7-15
-------
470 children in consistently nonsmoking households. Among the 614 exposed children for
whom complete information on smoking consumption was available, 36% were exposed to
< 1/2 pack daily, 40% to 1/2 to 1 pack daily, and 25% to > 1 pack daily. The distribution
of household concentrations for children in these smoking categories is shown in Figure 7-4.
Spengler et al. (1985) reported on the Kingston-Harriman, TN data from the Six-City
Study. Of 101 participants, 28 had cigarette smoke exposure at home, and each had an
indoor and personal monitor (cutpoints of 3.5 ^tm). Each town had a centrally located
outdoor dichotomous sampler providing two size fractions (2.5 pm and 15 /mi). Both towns
had similar outdoor PM2.5 concentrations of 18 /xg/m3, so the values were pooled for
subsequent analyses. Indoor concentrations averaged 42 + 2.6 (SE) /ig/m3. Indoor values
in homes with smoking averaged 74 ± 6.6 /jg/m3, compared to 28 + 1.1 /*g/m3 in homes
without smoking (p < 0.0001). No significant correlations between indoor and outdoor
concentrations were observed.
Lebret et al. (1987) reported on the Watertown, MA portion of the Six-City Study
where 265 homes were monitored for two one-week periods. Homes with smoking averaged
54 /ig/m3 (N = 147 and 152 during weeks 1 and 2), while homes without smoking averaged
21.6 /ig/m3 (N = 70 and 74). The effect of smoking one cigarette/day was estimated at
0.8 /xg/rn3 of PM25.
Spengler et al. (1987) reported on a new round of measurements in three Six-City
Study communities: Watertown, MA; St. Louis, MO; and Kingston-Harriman, TN. In each
community, about 300 children were selected to take part in a year-long diary and indoor air
quality study. PM2 5 measurements were taken indoors at home for two consecutive weeks
in winter and in summer, using the automated Harvard sampler which collected an integrated
sample for the week except for 8 a.m. to 4 p.m. weekday periods when the child was at
school. During this 40-h period, samples were taken in one classroom in each of the
elementary schools involved. Results were presented for smoking and non-smoking homes in
each city by season (Figure 7-5); the authors noted that mean concentrations in homes with
smokers were about 30 /xg/m3 greater than homes without smokers, the difference being
greater in winter than in summer for all cities.
Santanam et al. (1990) reported on a more recent and larger-scale monitoring effort in
Steubenville and Portage as part of the Six-City Study; 140 homes in each city, equally
7-16
-------
120-1
00
in
c\i
a- 80
CD
CD
S 60
o
'•c
CO
a.
CD
§
"a.
CO
0
CC
20-
90th %tile
75th %tile
50th %tile
1 0th %tile
l I
Never Changed
and Status
Former
i i i
Consistently Smoking
Pack
1/2-1
Pack
Packs
Figure 7-4. Distribution percentiles for annual average concentrations of indoor
respirable particulate matter (PM2>5) by household smoking status and
estimated number of cigarette packs smoked in the home during Phase 2
Harvard Six-City study.
Source: Neas et al. (1994).
7-17
-------
IOU
150-
140-
130-
120-
4 4 n
— 110
m
£ 100-
2 90-
^ 80-
^ 70-
Q- 60-
50-
40-
30-
20-
10-
0J
S = smoking
N = non-smoking
--- - outdoors
1
i
1
-
Tl g
'?'•• ™
• 1
i
i
p
Ij
1
ii ?4- J-i
SN SN SN SN SN
Winter Summer Winter Summer Winter
90th %tile
75th %tile
Mean
50th %tile
25th %tile
10th %tile
i
•-
i
?4-
S N
Summer
Watertown St. Louis Kingston
Figure 7-5. PM2>5 (/ig/m3) in smoking (S) and nonsmoking (N) homes in three of the
Harvard Six-City Study sites.
Source: Spengler et al. (1987).
distributed among households with and without smoking were monitored for one week in
summer and in winter. The Harvard impactor sampler was used to collect PM2 5 samples
between 4 p.m. and 8 a.m. on weekdays and all day on weekends, corresponding to likely
times of occupancy for school-age children. Outdoor samples were collected from one site in
each city. Target elements were determined by XRF. A source apportionment using
principal components analysis (PCA) and linear regressions on the elemental data were
carried out (Table 7-2a,b). Cigarette smoking was the single largest source in smokers'
homes, accounting for 20 to 27 jug/m3 indoor PM2-5 in Steubenville (Table 7-2a) and 10 to
25 /ig/m3 hi Portage (Table 7-2b). Wood smoke was estimated to account for about 4 /ig/m3
indoors and outdoors in Steubenville in winter, but only for about 1 /ig/m3 indoors and
outdoors in Portage. Sulfur-related sources accounted for 8 to 9 /xg/m3 indoors and
16 ptg/m3 outdoors in Steubenville in the summer, but were apparently not important in
winter. Auto-related sources accounted for 2 to 5 /ig/m3 in the two cities. Soil sources
7-18
-------
TABLE 7-2a. RECONSTRUCTED SOURCE CONTRIBUTIONS
TO INDOOR PM2 5 MASS FOR STEUBENVILLE, OH1
Source
Soil
Wood smoke
O.C.-I
Tobacco Smoke
Sulfur-related
Auto-related
O.C.-II
Indoor dust
Unexplained
Total
Smokers'
Homes
7.9 (3.45)
9.5 (4.15)
10.3 (4.47)
45.6 (19.9)
NS
NS
NS
NS
26.7(11.6)
100 (43.57)
WINTER
Non-Smokers'
Homes
17.6 (3.45)
21.2(4.15)
22.9 (4.47)
NA
NS
NS
NS
NS
38.3 (7.47)
100 (19.54)
Outdoor
Site
9.6(1.79)
23.0 (4.31)
24.8 (4.65)
NA
NS
NS
NS
NA
42.6 (7.95)
100 (18.7)
Smokers'
Homes
NS
NS
NS
53.7 (26.8)
17.8 (8.90)
7.3 (3.65)
8.8 (4.40)
7.4 (3.70)
5.0 (2.4)
100 (49.85)
SUMMER
Non-Smokers'
Homes
NS
NS
NS
NA
33.3 (8.23)
14.8 (3.65)
16.5 (4.07)
15.0 (3.70)
20.4 (5.05)
100 (24.7)
Outdoor
Site
NS
NS
NS
NA
52.5
(15.5)
5.3(1.55)
26.0
(7.67)
NA
16.2
(4-78)
100 (29.5)
!A11 entries in %
NS = not significant.
NA = not applicable.
O.C.-I: Iron and steel, and auto-related sources.
O.C.-II: Iron and steel, and soil sources.
Source: Santanam et al. (1990).
TABLE 7-2b. RECONSTRUCTED SOURCE CONTRIBUTIONS
TO INDOOR PM2 5 MASS FOR PORTAGE, WI1
Source
Sulfur-related
Auto-related
Soil
Tobacco Smoke
Wood smoke
Unexplained
Total
Smokers'
Homes
13.2 (4.56)
5.1 (1.78)
3.8(1.31)
71.0(24.6)
2.7 (0.94)
4.2(1.38)
100 (34.6)
WINTER
Non-Smokers'
Homes
30.7 (4.56)
12.0(1.78)
8.8(1.31)
NA
6.3 (0.94)
42.2 (6.23)
100 (14.8)
Outdoor
Site
39.2 (4.04)
17.3 (1.78)
13.4 (1.38)
NA
13.0(1.34)
17.1 (1.80)
100 (10.3)
Smokers'
Homes
23.3 (5.80)
18.1 (4.50)
7.5(1.86)
40.1 (9.99)
NA
11.0(2.75)
100 (24.9)
SUMMER
Non-Smokers'
Homes
38.1 (5.30)
29.6(4.12)
13.4(1.86)
NA
NA
18.9 (2.62)
100 (13.9)
Outdoor
Site
45.8 (6.23)
35.6 (4.84)
16.5 (2.25)
NA
NA
2.10(0.28)
100 (13.6)
entries in % 0*g/m3)
NA = not applicable.
Source: Santanam et al. (1990).
7-19
-------
accounted for only about 1 to 3 /xg/m3 of indoor and outdoor PM2 5 concentrations.
Nonsmoking homes in both cities had indoor mean PM2 5 concentrations very close to the
outdoor mean concentrations. Quite large percentages of particle concentrations were due to
unexplained sources.
7.2.2.1.2 The New York State ERDA Study
Sheldon et al. (1989) studied PM2 5 and other pollutants in 433 homes in two New
York State counties. One goal of the study was to determine the effect of kerosene heaters,
gas stoves, wood stoves or fireplaces, and cigarette smoking on indoor concentrations of
combustion products. A stratified design included all 16 combinations of the four
combustion sources and required about 22,000 telephone calls to fill all cells. The sampler
was a portable dual-nozzle impactor developed at Harvard University. Two oiled impactor
plates in series were used to reduce the probability that some particles larger than 2.5 /-im
would reach the filter. Samples were collected in the main living area and in one other room
(containing a combustion source if possible) using a solenoid switch to collect alternate
15-min samples over a 7-day period. Outdoor samples were collected at a subset of 57
homes. All samples were collected during the winter (January to April) of 1986.
PM2 5 mean concentrations indoors for all homes, with and without any combustion
sources, were approximately double those outdoors in both counties (Table 7-3). However,
in homes without combustion sources, PM2 5 concentrations were approximately equal
(Leaderer et al., 1990). Of the four combustion sources, only smoking created significantly
higher indoor PM2 5 concentrations in both counties (Table 7-4). Use of kerosene heaters
was associated with significantly higher concentrations in Suffolk (N = 22) but not in
Onondaga (N = 13). Use of wood stoves/fireplaces and gas stoves did not significantly
elevate indoor concentrations in either county.
Leaderer et al. (1990) extended the analysis of these data by collapsing the gas stove
category, reducing the number of categories from 16 to 8 (Table 7-5). By inspection of
Table 7-5, it is clear that smoking was the single strongest source of indoor fine particles,
with geometric means of indoor PM ranging from 28.5 to 61.4 /^g/m3, whereas the four
nonsmoking categories ranged from 14.1 to 22.0 jug/m3.
7-20
-------
TABLE 7-3. WEIGHTED SUMMARY STATISTICS BY NEW YORK COUNTY FOR
RESPIRABLE SUSPENDED PARTICIPATE (PM2 5) CONCENTRATIONS Qtg/m3)
Main Living Area
Percent Detected
Sample Size
Population Estimate
Arithmetic Mean (/*g/m3)
Arithmetic Standard Error
Geometric Mean (pig/m3)
Geometric Standard Error
Minimum (/*g/m3)
Maximum (/ig/m3)
Percentiles
10th
16th
25th
50th (median)
75th
84th
90th
95th
99th
Onondaga
98.9
224
94,654
36.7a
2.14
25.7a
1.07
0.72
172
9.93
11.2
13.5
23.9
48.4
68.0
85.2
112
136
Suffolk
99.6
209
286,580
46.4
2.77
35.9
1.06
2.18
284
13.8
16.8
18.9
33.6
62.8
76.6
89.4
112
155
Outdoors
Onondaga
100
37
16.8
1.00
15.8
1.06
6.32
28.4
12.8
15.1
20.5
Suffolk
100
20
21.8
4.54
18.6
1.11
12.0
106
13.6
16.7
22.3
a Significantly different between counties at 0.05 level.
Source: Sheldon et al. (1989).
Leaderer and Hammond (1991) continued analysis of the New York State data by
selecting a subset of 96 homes for which both nicotine and PM2 5 data were obtained. In the
47 homes where nicotine was detected (detection limit = 0.1 /xg/m3), the mean concentration
of RSP was 44.1 (± 25.9 SD) jig/m3 compared to 15.2 (± 7.4) ng/m3 in the 49 homes
without detected nicotine. Thus, homes with smoking had an increased weekly mean PM2 5
concentration of about 29 jig/m3. Imperfect agreement with reported smoking was observed,
with nicotine being measured in 13% of the residences that reported no smoking, while
nicotine was not detected in 28% of the residences that reported smoking. A regression on
7-21
-------
TABLE 7-4. WEIGHTED ANALYSIS OF VARIANCE OF RESPIRABLE
SUSPENDED PARTICULATE (PM2 5) CONCENTRATIONS (/tg/m3) IN THE MAIN
LIVING AREA OF HOMES VERSUS SOURCE CLASSIFICATION
Onondaga (R2 = 0.17)
Model
Independent variables:
Intercept
Gas stove
Kerosene heater
Tobacco smoking
Wood stove/fireplace
Suffolk (R2 = 0.21)
Model
Independent variables:
Intercept
Gas stove
Kerosene heater
Tobacco smoking
Wood stove/fireplace
F Value
20.5
1.87
1.06
81.6
2.42
36.9
0.13
12.0
114
0.71
Probability
0.00
0.17
0.30
0.00
0.12
0.00
0.72
0.00
0.00
0.40
Coefficient
20.3
5.25
5.05
45.1
7.81
26.1
-1.52
30.1
46.8
9.88
Source: Sheldon et al. (1989).
TABLE 7-5. RESPIRABLE SUSPENDED PARTICULATE (PM2 5)
CONCENTRATION Qtg/m3) IN HOMES BY SOURCE CATEGORY
Suffolk Onondaga
Source
None
W
K
S
KW
SW
SK
SKW
Outdoor
N
30
15
7
61
29
23
6
19
Mean
17.3
18.1
22.0
49.3
38.0
61.4
30.3
16.9
Standard
1.7
1.6
1.6
1.8
1.8
2.0
1.4
1.3
N
45
16
4
80
4
31
4
4
36
Mean
14.1
19.1
21.2
36.5
19.7
33.9
35.3
28.5
15.8
Standard
1.7
1.7
1.0
2.4
1.5
2.2
1.5
1.6
1.5
Abbreviations: W = woodstove; K = kerosene heater; S = tobacco smoking.
Source: Leaderer et al. (1990).
7-22
-------
all (smoking and nonsmoking) homes of PM2.5 on total number of cigarettes smoked during
the week (T) gave the result:
PM2.5 = 17.7 + 0.322T (N = 96; R2 = 0.55).
For the subset of 47 homes with measured nicotine, the regression gave the result:
PM2 5 = 24.8 + 0.272T (N = 47; R2 = 0.40).
Thus each cigarette produces about a 0.3 (±0.03) /tg/m3 increase hi the weekly mean PM2 5
concentration, equivalent to a 2.1 (±0.2) jiig/m3 increase in the daily concentration.
Koutrakis et al. (1992) also analyzed the New York State data, using a mass-balance
model to estimate PM2 5 and elemental source strengths for cigarettes, wood burning stoves,
and kerosene heaters. Homes with cigar or pipe smoking and fireplace use were eliminated,
resulting in 178 indoor air samples. PM2 5 source strength for smoking was estimated at
12.7 ± 0.8 (SE) mg/cigarette; but PM2 5 source strengths could not be estimated for wood
burning or kerosene heater usage (only seven homes in each category were available for
analysis). For a residual category of all other indoor sources, a source strength of 1.16 mg/h
was calculated. For nonsource homes (N = 49), the authors estimated that 60% (9 jig/m3)
of the total PM2 5 mass was from outdoor sources and 40% (6 pig/m3) from unidentified
indoor sources. However, indoor concentrations were not significantly correlated with
outdoor levels. For smoking homes, they estimated that 54% (26 /xg/m3) of the PM2 5 mass
was from smoking, 30% (15 jig/m3) from outdoor sources, and 16% (8 /ig/m3) from
unidentified sources. The elemental emissions profile for cigarettes included potassium
(160 /ig/cig), chlorine (69 /xg/cig), and sulfur (65 /ig/cig), as well as smaller amounts of
bromine, cadmium, vanadium, and zinc. The woodburning profile included three elements:
potassium (92 /xg/h), silicon (44 /*g/h) and calcium (38 /xg/h). The kerosene heater profile
included a major contribution from sulfur (1500 /tg/h) and fairly large inputs of silicon
(195 /ig/h) and potassium (164 /xg/h). A drawback of the mass-balance model was an
inability to separately estimate the value of the penetration coefficient P and the decay rate
7-23
-------
k for particles and elements; Koutrakis et al. (1992) assumed a constant rate of 0.36 h"1 for
fc, and then solved for P.
7.2.2.1.3 The U.S. Environmental Protection Agency Particle Total Exposure Assessment
Methodology Study
EPA designed a study of exposure to particles and associated elements in the late
1980s. Personal exposure and indoor and outdoor PM2 5 and PM10 concentrations were
measured. The personal exposure portion of the study is discussed in 7.4.1.1.1. The study
was carried out under the Total Exposure Assessment Methodology (TEAM) program, and is
known as the Particle TEAM, or PTEAM Study.
A pilot study was undertaken in nine homes in Azusa, CA in March of 1989 to test the
sampling equipment. The first five households were monitored concurrently for seven days
(March 6-13, 1989; Wiener, 1988, 1989; Wiener et al., 1990; Spengler et al., 1989); the last
four households were then monitored for four consecutive days (March 16-20, 1989). Indoor
and outdoor particle concentrations were monitored using impactors with a 10 Lpm pump
(Marple et al., 1987). Indoor monitors, capable of sampling both fine and inhalable particles
simultaneously, were placed in different rooms in each house to determine the magnitude of
room-to-room variation.
Room-to-room variation of 12-h integrated particle levels was generally less than 10%.
Therefore the several indoor values in a particular house were averaged to provide a single
mean indoor value to compare to the corresponding outdoor value. The mean (SE) 24-h
indoor PM10 concentration was 58.7 (3.4) pig/m3 compared to the outdoor mean of
62.6 (3.5) /ig/m3. Corresponding PM2 5 concentrations were 36.3 (2.6) /zg/m3 indoors and
42.6 (3.0) /ig/m3 outdoors.
Regressions of indoor on outdoor concentrations (N = 26 for each size fraction and
time period) resulted in the following equations for PM10:
Cfc(day) = 36 (11) + 0.44(0.14) Cout (R2 = 0.17)
Cin (night) = 44 (11) + 0.14 (0.19) Cout (R2 = 0.01)
and for PM2 5:
qn(day) = 18 (5) + 0.47(0. 10) COM, (R2 = 0.30)
7-24
-------
Cin (night) = 24 (6) + 0.23 (0.15) Cout (R2 = 0.05)
where the values in parentheses are the standard errors of the parameter estimates. (In most
epidemiology studies, PM exposures are related to PM concentrations at a community
ambient monitoring station, rather than to these PM concentrations measured outside
indivdual homes).
The R2 values unproved considerably when the regressions for individual homes were
calculated (Wallace, 1996; see also Table 7-6). For the five homes with seven days of
monitoring (14 12-h periods) all slopes were significant, and R2 values ranged from 0.34 to
0.79 for PM10 and from 0.49 to 0.85 for PM2 5. For the four homes having only four days
of monitoring, only home 8 had significant slopes and R2 values above 0.5.
TABLE 7-6. REGRESSIONS OF INDOOR ON OUTDOOR PM10
AND PM2 5 CONCENTRATIONS (/tg/m3): PARTICLE TOTAL EXPOSURE
ASSESSMENT METHODOLOGY PREPILOT STUDY
PM10 G*g/m3)
House
1
2
3
4
5
6
7
8
9
N
13
13
14
13
14
8
8
8
7
Intercept
23
-25
13
16
14
175
30
-2.7
48
SE
9
17
7
9
13
38
34
23
42
P
0.026
NS
NS
NS
NS
0.004
NS
NS
NS
Slope
0.27
1.14
0.64
0.52
0.67
-1.52
0.34
1.38
0.94
SE
0.12
0.23
0.1
0.14
0.16
0.78
0.62
0.5
0.87
P
0.038
0.0003
0.00002
0.004
0.001
NS
NS
0.03
NS
R2
0.34
0.7
0.79
0.54
0.59
0.39
0.05
0.56
0.19
PM2 5 (/xg/m3)
House
1
2
3
4
5
6
7
8
9
N
14
14
14
13
14
8
8
8
8
Intercept
14
-12
7.3
6
11
65
10
-0.34
37
SE
3.4
9
4.5
5
6
26
8
13
47
P
0.001
NS
NS
NS
NS
0.046
NS
NS
NS
Slope
0.19
0.96
0.72
0.52
0.58
-0.32
0.35
0.99
0.78
SE
0.06
0.16
0.09
0.13
0.1
1.01
0.22
0.39
1.3
P
0.005
0.00007
0.00001
0.002
0.0001
NS
NS
0.045
NS
Rz
0.49
0.74
0.85
0.6
0.72
0.02
0.3
0.51
0.05
Source: Data from PTEAM Prepilot Study upon which R2 values were generated as reported by
Wallace (1996).
7-25
-------
After the pilot study in Azusa, CA, the EPA sponsored a study of personal, indoor, and
outdoor concentrations of PM10, and indoor and outdoor concentrations of PM2 5 in
Riverside, CA (Pellizzari et al., 1992, 1993; Perritt et al., 1991; Sheldon et al., 1992;
Clayton et al., 1993; Thomas et al., 1993; Ozkaynak et al., 1993a,b, 1996). Personal
exposure results of this study are discussed hi Section 7.4.1.1.2. The main goal was to
estimate the frequency distribution of exposures to PM10 for all nonsmoking Riverside
residents aged 10 and above; and 178 households were selected, using probability sampling
to represent about 61,000 households throughout most of the city of Riverside. Homes were
sampled between September 22 and November 9, 1990, and each home had two 12-h
samples for both size fractions. A central site operated throughout the 48 days of the study,
producing 96 12-h samples collected by side-by-side reference samplers (dichotomous
samplers and modified hi-volume samplers) along with the low-flow (4 Lpm) impactors with
nominal cutpoints at 2.5 and 10 /nm designed for this study. (Laboratory tests [Thomas
et al., 1993] revealed that the actual cutpoints were 2.5 /un and 11.0 /mi, but this section
shall refer to PM10 in keeping with the investigators [Clayton et al., 1993] who reported their
data as PM10). A subset of the homes was monitored for PAHs (Sheldon et al., 1992);
125 were monitored indoors and 65 of those were monitored outdoors for two consecutive
12-h periods.
The precision of the three types of particle samplers at the central site was excellent,
with median RSDs of about 4 to 5% (Wallace, et al., 1991a). The low-flow sampler
produced estimates about 12% greater than the dichotomous sampler, which was about 7%
greater than the modified hi-vol sampler (Wallace, et al., 1991b). Part of the difference may
be due to the different cutpoints (estimated to be 11 pun for the new sampler, 9.5 for the
dichot, and 9.0 for the modified hi-vol), and part due to particle bounce (large particles
bouncing off the impactor and being re-entrained in the flow to the filter), such that the
PM2 5 and PM10 fractions in the low-flow sampler may be contaminated with a small number
of larger-size particles. However, particle bounce was found in laboratory tests to account
for less than 7% of the total mass.
The population-weighted distributions of personal (PEM), indoor (SIM), and outdoor
(SAM) particle concentrations are provided in Table 7-7. PM10 mean concentrations
(150 /ig/m3) were more than 50% higher than either indoor or outdoor levels (95
7-26
-------
TABLE 7-7. WEIGHTED DISTRIBUTIONS OF PERSONAL, INDOOR, AND
OUTDOOR8 PARTICLE CONCENTRATIONS
DAYTIME
PM2.5
Sample size
Minimum
Maximum
Mean
(Std. error)
Geometric Mean
(Std. error)
Std. deviation
Geometric std. deviation1*
Percentiles
10th
25th
50th (median)
75th
90th
Std. errors of percentiles
10th
25th
50th
75th
90th
SAM
167
7.4
187.8
48.9
(3.5)
37.7
(2.5)
37.6
2.07
14.9
23.4
35.5
60.1
102.2
1.6
2.1
4.0
3.9
4.6
SIM
173
2.8
238.3
48.2
(4.1)
35.0
(3.3)
41.2
2.25
11.5
19.3
33.5
61.5
101.0
3.4
1.4
4.5
3.3
6.7
SAM
165
16.2
506.6
94.9
(5.5)
82.7
(4.1)
57.2
1.68
42.8
56.9
84.1
110.8
157.2
2.3
4.5
4.7
4.0
7.2
NIGHTTIME
PM10
SIM
169
16.6
512.8
94.7
(5.7)
78.2
(5.0)
61.4
1.88
30.9
49.5
81.7
127.2
180.7
3.4
4.3
8.3
9.4
11.0
PM2.5
PEM
171
35.1
454.8
149.8
(9.2)
128.7
(8-5)
84.3
1.75
59.9
86.1
129.7
189.1
263.1
4.0
9.4
7.5
10.8
12.0
SAM
161
3.4
164.2
50.5
(3.7)
37.2
(3.1)
40.3
2.23
14.5
23.0
35.0
64.9
120.7
2.1
2.7
2.4
4.6
5.8
SIM
166
2.9
133.3
36.2
(2.2)
26.7
(1.9)
29.5
2.21
10.0
14.8
25.9
48.9
82.7
0.9
1.3
2.4
5.3
5.8
SAM
162
13.6
222.9
86.3
(4.4)
74.5
(4.0)
47.7
1.74
39.3
53.6
74.1
103.7
167.8
7.4
3.4
4.8
5.1
4.3
PM10
SIM
163
14.1
180.3
62.7
(3.2)
53.1
(3.1)
37.4
1.78
25.2
33.5
51.6
84.8
116.9
1.5
2.4
3.5
4.7
5.3
PEM
168
19.1
278.3
76.8
(3.5)
67.9
(3.1)
39.7
1.64
36.6
48.1
66.2
98.8
135.0
1.5
3.1
4.3
8.2
10.1
"Statistics other than the sample size, minimum, and maximum are calculated using weighted data; they provide estimates for the target population of person-days
(PEM) or of household-days (SIM, SAM).
bln contrast to the other statistics, the gsd is a unitless quantity.
Source: Pellizzari et al. (1992).
-------
Overnight mean personal PM10 concentrations (77 pig/m3) were similar to the indoor
(63 /ig/m3) and outdoor (86 fig/m3) levels. The reason for the higher daytime personal
exposures (PEM) than daytime SIM or SAM is not completely understood: it may be due to
persons often being close to sources of particles (e.g., cooking, dusting, or vacuuming) or to
re-entrainment of household dust (Thatcher and Layton, 1995). It appears not to be due to
skin flakes or clothing fibers; many skin flakes were found on filters but their mass does not
account for more than 10% of the excess personal exposure (Mamane, 1992).
Mean PM2 5 daytime concentrations were similar indoors (48 /xg/m3) and outdoors
(49 /ig/m3), but indoor concentrations fell off during the sleeping period (36 /xg/m3)
compared to 50 /ig/m3 outdoors. Thus the fine particle contribution to PM10 concentrations
averaged about 51% during the day and 58% at night, both indoors and outdoors. The
distributions of these ratios are provided in Table 7-8.
TABLE 7-8. WEIGHTED DISTRIBUTIONS8 OF
PM2 5/PM10 CONCENTRATION RATIO
Daytime
Sample Size
Mean
(Std. error)
Geometric Mean
(Std. error)
Percentiles
10th
25th
50th (median)
75th
90th
Std. errors of percentiles
10th
25th
50th
75th
90th
Statistics other than sample
Outdoor
160
0.470
(0.016)
0.444
(0.017)
0.274
0.371
0.469
0.571
0.671
0.018
0.018
0.015
0.019
0.012
size are calculated usini
Indoor
167
0.492
(0.021)
0.455
(0.022)
0.250
0.347
0.498
0.607
0.735
0.030
0.046
0.020
0.024
0.028
z weighted data: they PI
Nighttime
Outdoor
154
0.522
(0.017)
0.497
(0.019)
0.308
0.406
0.515
0.646
0.731
0.023
0.028
0.022
0.027
0.016
rovide estimates for the
Indoor
160
0.550
(0.014)
0.517
(0.016)
0.301
0.440
0.556
0.694
0.771
0.023
0.017
0.015
0.023
0.012
target
population of household-days.
Source: Pellizzari et al. (1992).
7-28
-------
Unweighted distributions are displayed in Figures 7-6 and 7-7 for 24-h average PM10
and PM2 5 personal, indoor, and outdoor concentrations. For 24-h data, the indoor PM is
less than the outdoor PM at all percentiles. Most of the distributions were not significantly
different from log-normal distributions, as determined by a chi-square test. About 25% of
the nonsmoking population of Riverside was estimated to have 24-h personal PM10 exposures
exceeding the 150 jtg/m3 24-h NAAQS for ambient air. Since participants were monitored
for only one day, the percentage of persons with exposures exceeding the outdoor 24-h
standard more than once per year would be greater than 25 %.
a.
o
300
270
240
210
180
150
,120
90
60
30
- o"'
Personal
-A- Indoor
Outdoor
300
270
240
210
180
150
120
90
60
25 50 75 90 95 96 99
Cumulative Frequency (%)
30
Figure 7-6. Cumulative frequency distribution of 24-h personal, indoor, and outdoor
PM10 concentrations in Riverside, CA.
Source: Adapted from PTEAM study data (Pellizzari et al., 1992).
The 48-day sequence of outdoor PM10 and PM2-5 concentrations is shown in Figure 7-8
(Wallace et al., 1991a). At least two extended episodes of high fine-particle concentrations
occurred, and four days of high Santa Ana winds, with correspondingly high coarse-particle
concentrations from desert sand, were observed.
7-29
-------
50 75 90 95 98 99
Cumulative Frequency (%)
20
Figure 7-7. Cumulative frequency distribution of 24-h indoor and outdoor PM2>5
concentrations in Riverside, CA.
Source: Adapted from PTEAM study data (Pellizzari et al., 1992).
200
Dichot coarse —Dichot-10
20 40 60 80 100
12-Hour Periods Beginning Sept. 22,1990
Figure 7-8. Forty-eight day sequence of PM10 and coarse PM (PM10 - PM2-5) in
Riverside, CA, PTEAM study. Santa Ana wind conditions are noted by
an asterisk.
Source: Wallace et al. (1991a).
7-30
-------
Central-site PM2 5 and PM10 concentrations agreed well with back yard concentrations.
Pearson correlations of the log-transformed data were 0.96 and 0.92 for overnight and
daytime PM2 5 and 0.93 for overnight PM10 values (Ozkaynak et al., 1993a), but dropped to
0.64 for daytime PM10 values. However, two homes in one Riverside area showed very
high outdoor concentrations of 380 and 500 /Lig/m3 on one day, while two homes in another
Riverside area and the central-site monitor showed more typical concentrations. A local
event likely produced the higher concentrations at the former two homes. If they are
removed from the data set, the correlation improves from 0.64 to 0.90, suggesting that a
single central-site monitor can represent well PM2 5 and PM10 concentrations throughout a
wider area such as a town or small city (at least in the Riverside area) except for unusual
local conditions.
Daytime indoor PM10 and PM2 5 concentrations showed low-to-moderate Pearson
correlations of 0.46 and 0.55, respectively, with outdoor concentrations (N = 158 to 173).
At night, the correlations improved somewhat to 0.65 and 0.61, respectively
(N = 50 to 168). Outdoor PM10 concentrations explained about 27% of the variance of
indoor levels (Figure 7-9) with the two outliers included.
Simple regressions of indoor on outdoor PM10 and PM2 5 resulted in the following
equations (standard errors in parentheses):
Indoor PM10 = 48 (9) + 0.51 (0.08) x Outdoor PM10 (day) N=159 R2 = 0.22
Indoor PM10 = 20 (5) + 0.52 (0.05) X Outdoor PM10 (night) N = 151 R2 = 0.42
Indoor PM2 5 = 14 (4) + 0.70 (0.07) X Outdoor PM2 5 (day) N=162 R2 = 0.42
Indoor PM25 = 9 (3) + 0.56 (0.04) X Outdoor PM25 (night) N = 153 R2 = 0.54
Simple regressions of personal PM10 on outdoor and indoor PMj0 resulted hi the
following equations:
Personal PM10 = 71 (9) -I- 0.78 (0.08) x Indoor PM10 (day) N = 163 R2 = 0.40
Personal PM10 = 21 (4) + 0.90 (0.05) X Indoor PM10 (night) N=158 R2 = 0.65
Personal PM10 = 100 (12) + 0.48 (0.10) X Outdoor PM10 (day) N=158 R2 = 0.12
Personal PM10 = 31 (6) + 0.53 (0.06) x Outdoor PM10 (night) N=155 R2 = 0.38
7-31
-------
-600
~ 500
o
400
Indoor - 0.54*Outdoor + 32
R2=27% (n = 309)
100 200 300 400 500 600
Average 12-h outdoor concentration (ng/m3)
Figure 7-9. Average indoor and outdoor 12-h concentrations of PM10 during the
PTEAM study in Riverside, CA.
Source: Ozkaynak et al. (1993b).
Correlation analyses and regressions relating personal to indoor, indoor to outdoor, and
personal to outdoor concentrations of the 14 prevalent elements were carried out for the
appropriate size fractions and both 12-h monitoring periods. For most of the elements, as
with particle mass, moderate correlations were noted for personal-indoor and indoor-outdoor
concentrations but low correlations for personal-outdoor concentrations. One element was a
strong exception to this rule: sulfur. Unlike any of the other elements, sulfur was not
elevated in the PEM relative to the SIM, and, thus, personal concentrations were much more
closely related to indoor concentrations (rs = 0.91 during the day and 0.95 at night).
Moreover, because few sources of sulfur are found indoors, the indoor-outdoor correlations
were high (rs varied between 0.90 and 0.95 for both size fractions), and even the personal-
outdoor correlations showed little degradation (the Spearman correlation rs = 0.85 during the
day and 0.92 at night).
Regressions of outdoor sulfur on indoor levels gave the following results for PM10
sulfur (/ig/m3):
7-32
-------
Sta (day) = 0.26 (0.06 SE) + 0.80 (0.02) 5out N = 164 R2 = 0.88
5in (night) = 0.20 (0.06) + 0.71 (0.03) 5out N = 155 R2 = 0.84
and for fine (PM2 5) sulfur:
S.m (day) = 0.046 (0.04 SE) + 0.85 (0.02) 5out N = 164 R2 = 0.92
S-m (night) = 0.061 (0.04) + 0.80 (0.02) 5out N = 154 R2 = 0.89
Stepwise regressions resulted in smoking, cooking, and either air exchange rates or
house volumes being added to outdoor concentrations as significant variables (Table 7-9).
Homes with smoking added about 27 to 32 jig/m3 to the total PM2 5 concentrations and about
29 to 37 jwg/m3 to the PM10 values. Cooking added 12 to 26 ^g/m3 to the daytime PM10
concentration and about 13 /ig/m3 to the daytime PM2 5 concentration, but was not significant
during the overnight period.
A model developed by Koutrakis et al. (1992) was solved using nonlinear least squares
to estimate penetration factors, decay rates, and source strengths for particles and elements
from both size fractions in the PTEAM study. In this model, which assumes perfect
instantaneous mixing and steady-state conditions throughout each 12-h monitoring period, the
indoor concentration of particles or elements is given by
PaCout + Qis'V (7.3)
- -
where
Cin = indoor concentration (ng/m3 for elements, /ig/m3 for particles)
P = penetration coefficient
a = air exchange rate (h"1)
out
Qh = mass flux generated by indoor sources (ng/h or /ig/h)
V = volume of room or house (m3)
k = decay rate due to diffusion or sedimentation (h"1)
Cout = outdoor concentration (ng/m3 or /tg/m3)
From initial multivariate analyses, the most important indoor sources appeared to be
smoking and cooking. Therefore the indoor source term QK was replaced by the following
expression:
7-33
-------
TABLE 7-9. STEPWISE REGRESSION RESULTS FOR INDOOR AIR
CONCENTRATIONS OF PM10 AND PM2 5 0*g/m3)
COEFFICIENTS (STANDARD ERRORS OF ESTIMATES)
PM10
Variable
N
R2
Intercept
Outdoor air
Smoking3
No. cigarettes1"
Cooking0
Air exchange
House volumed
All
310
41%
0.52
(0.05)
37
(6)
3.2
(0.7)
20
(5)
5.2
(2.0)
-0.08
(0.02)
Day
158
39%
57
(21)
0.66
(0.09)
29
(8)
3.0
(1.0)
26
(9)
-2.7
(1)
Night
147
58%
0.45
(0.05)
38
(11)
3.9
(0.9)
12
(5)
12
(5)
All
324
55%
0.64
(0.04)
28
(3.5)
2.5
(0.4)
9.4
(2.9)
Day
156
53%
21
(7.8)
0.71
(0.07)
27
(7)
2.4
(0.6)
13
(5)
-2.0
(0.6)
Night
149
71%
0.53
(0.04)
32
(10)
4.0
(0.6)
4.5
(2)
All listed coefficients significantly different from zero at p < 0.05.
aBinary variable: 1 = at least one cigarette smoked in home during monitoring period.
bThis variable was interchanged with the smoking variable in alternate regressions to avoid colinearity problems.
cBinary variable: 1 = cooking reported for at least one min in home during monitoring period.
dVolume in thousands of cubic feet.
Source: Ozkaynak et al. (1996).
Qis = ("dgScig + TcookScook)/T + Qother (7-4)
where
T = duration of the monitoring period (h)
Wcig = number of cigarettes smoked during monitoring period
5"cig = mass of elements or particles generated per cigarette smoked (ng/cig or
rcook = time spent cooking (min) during monitoring period
•^cook = mass °f elements or particles generated per min of cooking (ng/min or
ptg/min)
Cother = mass flux °f elements or particles from all other indoor sources (ng/h or
7-34
-------
With these changes, the equation for the indoor concentration due to these indoor
sources becomes
^cig^cig + ^cook^cook Qother (7.5)
(a + k)V T (a + k)V
The indoor and outdoor concentrations, number of cigarettes smoked, monitoring
duration, time spent cooking, house volumes, and air exchange rates were all measured or
recorded. The penetration factor, decay rates, and source strengths for smoking, cooking,
and all other indoor sources (Cother) were estimated using a nonlinear model (NLIN in SAS
software). The Gauss-Newton approximation technique was used to regress the residuals
onto the partial derivatives of the model with respect to the unknown parameters until the
estimates converge. On the first run, the penetration coefficients were allowed to "float"
(no requirement was made that they be < 1). Since nearly all coefficients came out close to
1, a second run was made bounding them from above by 1. The NLIN program provides
statistical uncertainties (upper and lower 95 % confidence intervals) for all parameter
estimates. However, it should be noted that these uncertainties assume perfect measurements
and are therefore underestimates of the true uncertainties.
Results are presented in Table 7-10 for the combined day and night samples. The
penetration factors were very close to unity for nearly all particles and elements. The
calculated average decay rate (lower and upper 95% confidence levels) for PM2 5 was
0.39 (0.22; 0.55) h'1, and for PM10 was 0.65 (0.36; 0.93) h'1. Since PM10 contains the
PM2.s fraction, a separate calculation was made for the coarse particles (PM10 — PM2 5)
with a resulting decay rate of 1.01 (0.6; 1.4) h"1. Each cigarette emitted 22 (14; 30) mg of
PM10 on average, about two-thirds of which 14 (10; 17) mg is in the fine fraction. Cooking
emitted 4.1 (2.6; 5.7) mg/min of inhalable particles, of which about 40% or 1.7 (1.0; 2.3)
mg/min, was in the fine fraction. All target elements emitted by cooking were limited
almost completely to the coarse fraction. Sources other than cooking and smoking emitted
about 5.6 (2.6; 8.7) mg/h of PM10, of which only about 1.1 mg/h (0.0; 2.1) (20%) was in
the fine fraction.
Decay rates for elements associated with the fine fraction were generally lower than for
elements associated with the coarse fraction, as would be expected. For example, sulfur,
7-35
-------
TABLE 7-10. PENETRATION FACTORS, DECAY RATES, AND SOURCE STRENGTHS: NONLINEAR ESTIMATES
Penetration
VAR
PM2.S>
Al
Mn
Br
Pb
Ti
Cu
Sr
Si
Ca
Fe
K
S
Zn
Cl
PM10»
Al
Mn
Br
Pb
Ti
Cu
Sr
Si
Ca
Fe
K
S
Zn
Cl
Mean
1.00
1.00
0.87
0.90
195 u95
0.89 1.11
0.95 1.05
0.78 0.95
0.81 0.99
Decay Rate (1/h)
Mean
0.39
0.03
0.23
0.28
195b
0.22
-0.03
0.07
0.15
u95
0.55
0.09
0.38
0.41
S cook (pg/min)
Mean
1.7
0.9
0.1
0.1
195b
1.0
-1.4
-0.1
0.0
u95
2.3
3.1
0.2
0.2
Mean
13.8
9.0
0.2
1.9
S smoke (/tg/cig)
195"
10.2
-2.5
-0.4
1.3
u95
17.3
20.5
0.8
2.5
Other Sources (figfti)
Mean
1.1
3.0
0.5
0.6
195b
0.0
-3.7
0.2
0.3
u95
2.1
9.8
0.9
0.9
Fail to converge
Fail to converge
1.00
0.97
0.98
1.00
1.00
1.00
1.00
0.71
0.50
1.00
1.00
1.00
1.00
1.00
1.00
0.83
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.94
0.56 M
0.93 .01
0.75 .20
0.65 .35
0.76 .24
0.81 .19
0.97 .03
0.57 0.86
0.28 0.72
0.85 .15
0.80 .20
0.80 .20
0.90 .10
0.89 .11
0.80 .20
0.62 .05
0.83 .16
0.81 .19
0.68 .32
0.80 .20
0.83 .17
0.96 .04
0.81 .19
0.44 .43
1.63
0.07
0.54
0.61
0.70
0.16
0.16
0.78
0.64
0.65
0.80
0.69
0.21
0.14
0.60
0.77
0.62
0.62
0.63
0.66
0.46
0.21
0.37
2.36
0.38
0.01
0.04
-0.02
0.11
-0.04
0.12
0.31
0.05
0.36
0.38
0.30
0.11
0.01
0.22
0.18
0.28
0.26
0.06
0.26
0.17
0.17
0.10
0.48
2.88
0.12
1.05
1.25
1.29
0.37
0.19
1.25
1.24
0.93
1.21
1.07
0.32
0.26
0.98
1.36
0.97
0.97
1.20
1.06
0.75
0.26
0.64
4.24
0.6
0.0
6.1
11.9
4.5
0.0
1.0
0.4
5.9
4.1
69.5
0.9
0.1
0.0
4.0
0.5
0.3
149.3
118.7
46.7
17.6
6.8
1.2
45.7
0.0
0.0
-8.6
-0.6
-3.3
-4.4
-3.9
-0.5
0.1
2.6
16.6
0.1
0.0
-0.3
0.3
0.0
0.0
26.9
37.3
8.5
0.1
-0.7
-0.2
17.6
1.2
0.0
20.9
24.4
12.3
4.4
5.9
1.2
11.6
5.7
122.4
1.7
0.3
0.3
7.8
1.1
0.5
271.8
200.1
84.8
35.2
14.3
2.5
73.9
3.7
0.1
14.4
165.6
23.8
121.3
27.1
2.9
102.6
21.9
97.6
1.1
1.8
2.1
10.0
3.5
2.6
296.4
800.0
73.0
215.7
68.0
4.0
320.2
0.2
-0.1
-58.3
72.0
-16.3
85.7
2.4
-1.5
54.0
13.6
-159.0
-2.7
1.2
0.4
-8.4
0.4
1.2
-293.9
329.0
-109.8
116.9
29.3
-3.0
107.0
7.2
0.2
87.2
259.1
63.9
156.9
51.7
7.4
151.2
30.2
354.2
4.9
2.5
3.9
28.4
6.5
3.9
886.6
1271.0
255.9
314.5
106.7
11.0
533.4
3.8
0.1
57.3
34.1
23.8
8.9
4.0
7.5
20.6
5.6
154.5
1.2
0.4
0.0
10.3
3.2
0.9
237.8
107.6
51.5
43.6
22.7
7.4
148.4
1.4
0.0
12.5
3.4
1.8
-0.5
-3.7
4.2
7.2
2.6
52.0
-0.2
0.1
-0.6
2.6
1.3
0.3
16.1
-27.0
-15.5
8.6
10.4
3.4
49.4
6.3
0.2
102.0
64.8
45.7
18.3
11.7
10.9
34.0
8.7
257.0
2.6
0.6
0.6
18.1
5.1
1.5
459.6
242.3
118.5
78.5
34.9
11.4
247.4
"Mass units in mg for PM2 5 and PM10 only.
bA negative lower confidence interval implies a nonzero mean is not statistically significant.
Source: Ozkaynak et al. (1993a).
-------
which has the lowest mass median diameter of all the elements, had calculated decay rates of
0.16 (0.12; 0.19) h'1 and 0.21 (0.17; 0.26) h'1 for PM25 and PM10 fractions, respectively.
The crustal elements (Ca, Al, Mn, Fe) had decay rates ranging from 0.6 to 0.8 h"1.
Based on the mass-balance model, outdoor air was the major source of indoor particles,
providing about 3/4 of fine particles and 2/3 of thoracic particles in the average home. It was
also the major source for most of the target elements, providing 70 to 100% of the observed
indoor concentrations for 12 of the 15 elements. It should be noted that these conclusions
are applicable only to Riverside, CA. In five of the six cities studied by Harvard and in both
New York counties, outdoor air could not have provided as much as half of the indoor air
particle mass for the average home, because the observed indoor-outdoor ratios of the mean
concentrations were > 2. However, for homes without smoking or combustion sources
(Santanam et al., 1990; Leaderer et al., 1990; Table 7-5), indoor-outdoor ratios were « 1.
In general, homes in areas with colder winters (such as New York) would be expected to
have tighter construction than homes in warmer areas (such as Riverside) and, therefore,
more protection against outdoor air particles.
Unidentified indoor sources accounted for most of the remaining particle and elemental
mass collected on the indoor monitors. The nature of these sources is not yet completely
understood (Thatcher and Layton, 1995). They apparently do not include smoking, other
combustion sources, cooking, dusting, vacuuming, spraying, or cleaning, since all these
sources together account for less than the unidentified sources. For example, the unidentified
sources accounted for 26% of the average indoor PM10 particles, whereas smoking accounted
for 4% and cooking for 5% (Figure 7-10).
Of the identified indoor sources, the two most important were smoking and cooking
(Figures 7-11 and 7-12). Smoking was estimated to increase 12-h average indoor
concentrations of PM10 and PM2 5 by 3.2 and 2.5 /ig/m3 per cigarette, respectively. Homes
with smokers averaged about 30 /xg/m3 higher levels of PM10 than homes without smokers,
most of this increase being in the fine fraction. Cooking increased indoor concentrations of
PM10 by about 0.6 /-ig/m3 per minute of cooking, most of the increase being in coarse
particles.
Emission profiles for target elements were obtained for smoking and for cooking.
Major elements emitted by cigarettes were K, Cl, and Ca; those from cooking included Al,
7-37
-------
Outdoor
76%
Cooking
4%
Other Indoor
14%
Smoking
5%
N = 352 Samples from 178 homes
Cooking
5%
Outdoor
66%
Other Indoor
26%
Smoking
4%
N - 350 Samples from 178 homes
Figure 7-10. Sources of fine particles (PM2 5) (top) and thoracic particles (PM10)
(bottom) in all homes (Riverside, CA).
Source: Ozkaynak et al. (1993a).
7-38
-------
Coftin9 Other Indoor
3/0 7%
Outdoor
60%
Smoking
30%
N - 61 Samples from 31 homes
Cooking
Outdoor
56%
Other Indoor
16%
Smoking
24%
N - 61 Samples from 31 homes
Figure 7-11. Sources of fine particles (PM2.5) (top) and thoracic particles (PM10)
(bottom) in homes with smokers (Riverside, CA).
Source: Ozkaynak et al. (1993a).
7-39
-------
Cooking
25%
Outdoor
62%
Smoking
N - 62 Samples from 33 homes
Other Indoor
8%
Cooking
25%
Outdoor
56%
\ V /
Other Indoor
16%
Smoking
4%
N - 62 Samples from 33 homes
Figure 7-12. Sources of fine particles (PM2.5) and thoracic particles (PM10), top and
bottom panels, respectively, for homes with cooking during data collection
(Riverside, CA).
Source: Ozykaynak et al. (1993a).
7-40
-------
Fe, Ca, and Cl. Other household activities such as vacuuming and dusting appeared to make
smaller contributions to indoor particle levels. Commuting and working outside the home
resulted in lower particle exposures than for persons staying at home. As with the particle
mass, daytime personal exposures to 14 of 15 elements were consistently higher than either
indoor or outdoor concentrations. At night, levels of the elements were similar in all three
types of samples.
7.2,2.1.4 Comparison of the Three Large-Scale Studies
The three studies had somewhat different aims and therefore different study designs.
The Harvard Six-City study selected homes based on various criteria, especially a
requirement that a school-age child be in the home, but did not employ a probability-based
sample. Therefore the results strictly apply only to the homes in the sample and not to a
wider population; however, the very large number of homes suggests that the results should
be broadly applicable to homes with school-age children in the six cities. The New York
State study used a probability-based sample, but stratified on the basis of combustion
sources. Hence, there are likely to be a higher fraction of homes with kerosene heaters,
wood stoves, and fireplaces in the sample than in the general population. The PTEAM study
used a fully probability-based procedure, and its results are likely the most broadly applicable
to the entire population of Riverside households. However, the participants were limited to
nonsmokers, so homes with only smokers were excluded; as a consequence, maximum
indoor concentrations were likely underestimated. Also, the three studies used different
monitors, with different cutpoints precluding exact comparisons. However, large differences
between the PM3 5 and PM2 5 cutpoints and the PMn and PM10 cutpoints are not likely
(Willeke and Baron, 1993); thus, these results can be more readily compared. In what
follows, the term "fine particles" refers to the PM3 5 and PM2.5 size fractions collected in the
three studies.
Indoor-Outdoor Relationships. Outdoor concentrations of fine particles in five of the
Harvard six cities and the two New York counties were relatively low, typically in the range
of 10 to 20 ptg/m3 (Table 7-11). Only Steubenville, with an annual mean of 45 jtg/m3 (but a
range among the outdoor sites of 20 to 60 pcg/m3) approached the mean outdoor level of
50 Mg/m3 observed in Riverside. It is interesting to note that average indoor concentrations
7-41
-------
TABLE 7-11. INDOOR-OUTDOOR MEAN CONCENTRATIONS (/tg/m3)
OF FINE PARTICLES IN THREE LARGE-SCALE STUDIES
Study Name
Harvard Six-City Study
Portage, WI
Topeka, KS
Kingston-Harriman, TN
Watertown, MA
St. Louis, MO
Steubenville, OH
New York State ERDA Study
Onondaga County
Suffolk County
EPA Particle TEAM Study
Riverside, CA
Homes
11
10
8
8
10
8
224
209
178
Out
10
10
18
15
18
45
17
22
50
In
20
22
44
29
42
42
37
46
43
In/Out
2.0
2.2
2.4
1.9
2.3
0.9
2.2
2.1
0.9
Harvard: PM3 5 measured using cyclone sampler. Samples collected every sixth day for one year (May 1986
to April 1987).
NYS: PM2 5 measured using impactor developed at Harvard. Samples collected for one week at each
household between January and April 1986.
PTEAM: PM2 5 measured using Marple-Harvard-EPA sampler. Samples collected for two 12-h periods at each
home between September and November 1990.
Source: Harvard data—Spengler et al. (1981); NYS data—Sheldon et al. (1989); PTEAM data—Pellizzari
et al. (1992).
exceeded outdoor concentrations in the seven sites with low outdoor levels, (indoor/outdoor
ratios were contained in a small range between 1.9 and 2.4), but were slightly less than
outdoor concentrations in the two sites with high outdoor levels (ratios of 0.9).
Effect of Smoking. All three studies found cigarette smoking to be a major source of
indoor fine particles. Multivariate calculations in all three studies result in rather similar
estimates of the effect of smoking on fine particle concentrations. Spengler et al. (1981)
estimated an increase of about 20 /ig/m3 per smoker based on 55 homes from all six cities.
Since the 20 homes with at least one smoker averaged at least 1.25 smokers per home, this
corresponds to about 25 //g/m3 per smoking home. Spengler et al. (1985) found a smoking
effect of about 32 /zg/m3 for smoking homes in multivariate models based on the Kingston-
Harriman data. Santanam et al. (1990) found a smoking-related increase of 20-27 /ig/m3 in
Steubenville and Portage (winter only) but only 10 jug/m3 in Portage in summer. Sheldon
et al. (1989) found an increase of 45 (Onondaga) and 47 (Suffolk) ftg/m3 per smoking home
in a multivariate model of the New York State data. Ozkaynak et al. (1993b) found an
7-42
-------
increase of about 27 to 32 jwg/m3 in homes with smokers in a multivariate regression model
of the PTEAM PM2 5 data. Thus, the effect of a home with smokers on indoor fine particle
concentrations was estimated to be about 20 to 30 /xg/m3 in the Six-City and PTEAM
studies, but about 45 jug/m3 in the New York State study.
Dockery and Spengler (1981a) found an effect of 0.88 jug/m3 per cigarette for homes
without air conditioning, and 1.23 /ig/m3 per cigarette for homes with air conditioning, based
on 68 homes from all six cities. Lebret et al. (1987) found an effect of 0.8 ^ig/m3 per
cigarette for homes in the Watertown, MA, area. Leaderer and Hammond (1991) found an
effect ranging between 1.9 and 2.3 /xg/m3 per cigarette contribution to a 24-h average. In a
series of stepwise regressions on the PTEAM data, Ozkaynak et al. (1993b) found an effect
ranging between 1.2 and 2.4 /ig/m3 per cigarette smoked during a 24-h period. Taking the
midpoint of these ranges leads to estimates for the Harvard Six-City, New York State and
PTEAM studies of about 1.1, 2.1, and 1.8 /-ig/m3 increases in fine particle concentrations per
cigarette smoked in the home over a 24-h period.
Both the New York State study and the PTEAM study were able to estimate source
strengths for different variables using a mass-balance model. The estimates for PM2 5
emissions from cigarettes were very comparable, with Koutrakis et al. (1992) estimating
12.7 mg/cig compared to the PTEAM estimate of 13.8 mg/cig (Ozkaynak et al., 1993a).
Both studies also found similar elemental profiles for smoking, with potassium and chlorine
being emitted in substantial amounts.
Effect of Other Variables. In the PTEAM Study, the second most powerful indoor
source of PM10, and possibly PM2 5 particles, was cooking. Quite large emission strengths
of several mg/minute of cooking were determined from the mass-balance model, while
multiple regressions indicated that cooking could contribute between 10 and 20 /tg/m3 PM10,
and somewhat smaller amounts of PM2 5, to the 12-h concentration.
Both the New York State and PTEAM studies also measured air exchange in every
home, and both studies found that air exchange significantly affected indoor particle
concentrations. In the PTEAM study, increased air exchange led to increased indoor air
concentrations for both PM2 5 and PM10 at night only, perhaps because outdoor
concentrations were larger than indoor levels at night. In the New York State study,
increased air exchange led to decreased RSP concentrations in Onondaga (p < 0.02) but no
7-43
-------
effect was noted in Suffolk (p < 0.90). In both of these counties, indoor levels generally
exceeded outdoor levels, so increased air exchange would generally reduce indoor
concentrations.
7.2.2.2 Other Studies of PM Indoors
Several other large-scale studies of indoor PM in homes have taken place in other
countries, and a number of smaller U.S. studies have been conducted. These are discussed
below hi order of the number of homes included in the study.
Lebret et al. (1990) carried out week-long RSP measurements (cutpoint not described)
in 260 homes in Ede and Rotterdam, The Netherlands, during the winters of 1981 to 1982
and 1982 to 1983, respectively; 60% of the Ede homes and 66% of the Rotterdam homes
included smokers. Diary information collected during the measurement period indicated that,
on average, one to two cigarettes were smoked during the week, presumably by guests, even
in the nonsmoking homes. Homes with one smoker averaged seven cigarettes smoked per
day at home in Ede (N = 53) and 11 per day in Rotterdam (N = 35). Homes with two
smokers averaged 21 cigarettes per day in Ede (N = 23) and 25 per day in Rotterdam
(N = 15).
Geometric means for the combined smoking and nonsmoking homes were similar in the
two cities (61 and 56 jig/m3, respectively), with maxima of 560 and 362 /*g/m3. Outdoor
concentrations averaged about 45 jig/m3 (N not given). Indoor concentrations in the homes
with smokers averaged about 70 |Kg/m3 (calculated from data in the paper), compared to
levels in the nonsmoking homes of about 30 /-ig/m3. Multiple regression analysis indicated
that the number of smoking occupants explained about 40% of the variation in the log-
transformed RSP concentrations—family size, frequency of vacuuming, volume of the living
room, type of space heating, and city (Ede versus Rotterdam) had no significant effect on
RSP concentrations. In a second regression, the number of smoking occupants was replaced
by the number of cigarettes and cigars smoked during the week. The regression equation
was
log(RSP) = 1.4 + 0.37 log(# cigarettes) + 0.53 log(# cigars)
+ 0.03 log(family size)
R2 = 0.49; d.f. =250 F = 83.7 p < 0.0001
7-44
-------
From this equation, the authors estimated that one cigarette smoked per day would increase
weekly average indoor RSP concentrations by 2 to 5 /ig/m3, whereas one cigar smoked per
day would increase indoor levels by 10 /ig/m3. Instantaneous RSP concentrations were
measured using a TSI Piezobalance on the day the technicians were setting up the equipment.
Table 7-12 shows the influence of smoking on these measurements.
TABLE 7-12. INFLUENCE OF RECENT CIGARETTE SMOKING
ON INDOOR CONCENTRATIONS OF PARTICIPATE MATTER1
Time Since Smoking
No smoking
More than 1 h ago
Between 1/2 and 1 h ago
Less than 1/2 an hour ago
During the measurements
N
98
18
7
27
54
RSP (geom. mean) (/*g/m3)
41
52
76
141
191
'Size cuts for measured particles not specified.
Source: Lebret et al. (1990).
Heavner et al. (1995) studied PM3 5 at home and at work for 104 New Jersey and
Pennsylvania females. The personal sampler used consisted of a cyclone sampling head
attached to a 37-mm Fluoropore filter, connected by Tygon tubing to a 1.7 Lpm pump. The
sampling head was worn on a lapel, collar, or pocket in the breathing zone of the participant
until she went to bed, when the sampler was placed on the bedside table. The "home"
pumps were turned on at 6 p.m. and sampled until about 8 a.m. the next morning
(an average of 14 h); the "work" pumps were turned on at work and sampled for an average
of 7 h. Participants were selected to include those with exposure to smoking at home or at
work or both or neither. The 14-h evening and overnight concentrations hi the homes
averaged 86.7 ± 145.4 (SD) /*g/m3 for 30 homes with smokers and 27.6 ± 19.9 jig/m3 for
58 homes without smokers. Corresponding values for workplaces were 67.0 ± 44.3 /ig/m3
for those 28 allowing smoking and 30.3 ± 17.6 ng/m? for the 52 without smoking, the
differences being significant at p < 0.0001 (Wilcoxon rank sum) for both comparisons.
-------
Diemel et al. (1981) measured particles in 101 residences in an epidemiological study
related to a lead smelter in Arnhem, the Netherlands. The indoor sampler collected samples
at a flowrate of 1 to 1.5 Lpm. The authors stated that particles < 3 to 4 j«n diameter
should have been sampled efficiently, but presented no data on measured cutpoint size. The
outdoor samplers (number not given) were high-volume samplers. The 28-day average levels
indoors ranged from 20 to 570 jig/m3, with an arithmetic mean of 140 pig/m3 (SD not
presented) and a geometric mean of 120 jig/m3; corresponding outdoor concentrations (2-mo
averages of 24-h daily samples) ranged from 53.7 to 73.3 /*g/m3 (N not given), with nearly
identical arithmetic and geometric means of 64 /ig/m3.
Kulmala et al. (1987) measured indoor and outdoor air in approximately 100 dwellings
(including some office buildings) in Helsinki, Finland between 1983 and 1986. Samples
were collected on Nuclepore filters using a stacked foil technique. The geometric mean for
the combined fine particle (< 1 /mi) samples indoors was 16 /zg/m3, with a 95% range of
4 to 67 /xg/rn3. The corresponding value for the indoor coarser particles (> 1 /mi) was
13 /ig/m3 with a range of 3 to 63 /xg/m3. Outdoors, the fine particles had a geometric mean
of 20 /ig/m3 with a 95% range of 5 to 82 jug/m3, and the coarser particles had a geometric
mean of 16 /Ag/m3 with a range of 3 to 91 /ig/m3.
Quackenboss et al. (1989) reported PM10 and PM2 5 results from 98 homes in the
Tucson, AZ area selected as part of a nested design for an epidemiological study. The
Harvard-designed dual-nozzle indoor air sampler (Marple et al., 1987) was used for indoor
air measurements. Outdoor air was measured within each geographic cluster by the same
instrument; supplementary data were obtained from the Pima County Air Quality Control
District, but these data did not include PM2 5 measurements and some data were apparently
PM15. Homes were classified by (a) tobacco smoking and (b) use of evaporative ("swamp")
coolers, which apparently act as a removal mechanism for particles (Table 7-13). Homes
without smoking averaged about 15 /-ig/m3 PM2 5, compared to 27 /ig/m3 for homes reporting
one or less pack a day, and 61 /ig/m3 for homes reporting more than one pack a day. PM2 5
particles accounted for about half of the PM10 fraction in nonsmoking homes, increasing with
the amount of smoking to about 80% in those homes with heavy smoking. Outdoor PM10
particles were not strongly correlated with indoor levels (R2 = 0.18; N = 90).
7-46
-------
TABLE 7-13. INDOOR AVERAGE PM2 5 AND PM10 Gig/m3)
BY REPORTED SMOKING IN THE HOME AND EVAPORATIVE
COOLER USE DURING SAMPLING WEEK FOR TUCSON, AZ STUDY
Smoking
Cigarettes/Day
None
1-20
>20
Evaporative
Cooler
Yes
No
Total
Yes
No
Total
Yes
No
Total
Mean
8.8
20.3
15.2
19.3
32.3
27.3
36.2
82.7
60.8
PM25
S.D.
5.0
19.0
15.5
8.8
28.5
23.6
32.9
55.4
50.8
Homes
(20)
(25)
(45)
(10)
(16)
(26)
(8)
(9)
(17)
Mean
21.0
38.4
30.3
33.9
53.4
46.2
47.4
102.5
75.0
PM10
S.D.
9.7
22.9
19.9
12.0
33.9
29.1
39.6
60.6
57.2
Homes
(20)
(23)
(43)
(10)
(17)
(27)
(9)
(9)
(18)
PM2 5: Significant (p < 0.01) main effects for smoking and evaporative cooler use; two-way interaction nearly
significant (p = 0.06).
PMi0: Significant (p < 0.01) main effects for evaporative cooler and smoking.
Source: Quackenboss et al. (1989).
Quackenboss et al. (1991) extended the analysis of the Tucson homes over three
seasons. Median indoor PM2 5 levels in homes with smokers were about 20 /xg/m3 in the
summer and spring/fall seasons compared to about 10 /ig/m3 in homes without smokers in
those seasons. In winter, however, the difference was considerably increased, with the
median level in 24 homes with smokers at about 36 jwg/m3 compared to 13 /ig/m3 in
26 homes without smokers.
Sexton et al. (1984) reported on a study in Waterbury, VT. This study included
24 homes, 19 with wood-burning appliances, and none with smokers. 24-h samples were
collected in each home every other day for two weeks, providing 163 valid indoor samples.
Indoor RSP levels ranged from 6 to 69 /ig/m3 with a mean value of 25 /xg/m3. Outdoor
levels ranged from 6 to 30 jtg/m3 with a mean value of 19 /ug/m3. Indoor concentrations
were not significantly correlated with outdoor concentrations (r = 0.11, p > 0.16.)
Kim and Stock (1986) reported results for 11 homes in the Houston, TX area.
(Year and the season not reported in the paper.) For most homes, two 12-h PM2 5 samples
(day and night) were collected for approximately one week. Sampling methods were not
fully discussed, but apparently they involved samples collected using a mobile van near each
home. The mean weekly concentrations in the five smoking homes averaged
33.0 ± 4.7 (SD) /ig/m3, versus mean outdoor concentrations averaging 24.7 ± 7.4
7-47
-------
(calculated from data presented in paper). Indoor concentrations in the six nonsmoking
homes averaged 10.8 ± 4.9 /xg/m3 compared to outdoor levels of 12.0 ± 5.9 /tg/m3.
Morandi et al. (1986) reported on 13 Houston, TX, homes monitored during 1981 as
part of a larger personal monitoring study of 30 nonsmoking participants. The TSI
Piezobalance (cutpoint at about PM3 5) was employed for personal monitoring, with
technicians "shadowing" the participants and taking consecutive 5-min readings. At the
homes, dichotomous samplers (cutpoints at PM2 5 and PM10) were used for two 12-h daytime
samples (7 a.m. to 7 p.m.) both inside and outside the homes for seven consecutive days.
Little difference was noted in the indoor concentrations at homes (25 ± 30 (SD) jig/m3) and
at work or school (29 ± 25 ^g/m3). The highest overall respirable suspended particle (RSP)
concentrations occurred in the presence of active smoking (89 jig/m3), significantly different
from mean RSP values measured in the absence of smokers (19 /ig/m3; p < 0.0001).
Among homes with smokers, those homes with central air conditioning were significantly
(p< 0.0001) higher (114 versus 52 /ig/m3) than those with no air conditioning. Cooking was
associated with significantly higher RSP concentrations (27 /xg/m3 compared to 20 pig/m3,
p < 0.01). The single highest RSP concentration (202 jug/m3) was found in a home with no
smokers and no air conditioning but with active cooking. The authors concluded that
cooking was a more important source of indoor RSP than smoking, at least in the few homes
they studied.
Coultas et al. (1990) measured PM2 5 in 10 homes containing at least one smoker, using
the Harvard aerosol impactor. Samples were collected for 24 h every other day for 10 days
and then for 24 h every other week for 10 weeks, resulting in 10 samples per household.
The mean concentrations of PM2.5 ranged from 32.4 + 13.1 (SD) to 76.9 ± 32.9 /*g/m3.
Outdoor particle concentrations were not reported; thus it is difficult to calculate the portion
of the observed PM2 5 that might be due to ETS.
Kamens et al. (1991) measured indoor particles in three homes without smokers in
North Carolina in November and December 1987 (no measurements of outdoor particles
were taken). Two dichotomous samplers (PM2 5 and PM10), several prototype personal
samplers (also PM2 5 and PM10), three particle sizing instruments including a TSI electrical
aerosol mobility analyzer (EAA) with 10 size intervals between 0.01 and 1.0 ptm, and two
optical scattering devices covering the range of 0.09 to 3.0 and 2.6 to 19.4 pm were
7-48
-------
employed. Air exchange measurements were made using SF6 decay over the course of the
seven 8-h (daytime) sampling periods. There were also three 13-h (evening and overnight)
sampling periods. For the entire study, 37% of the estimated total mass collected was hi the
fine fraction, and another 37% was > 10 /mi. The remainder (26%) was in the inhalable
coarse (PM10 — PM2 5) fraction. However, considerable variation was noted in these size
distributions. For example, on one day with extensive vacuuming, cooking, and vigorous
exercising of household pets, 52% of the total mass appeared hi the fraction > 10 /mi, but
only 18% hi the fine fraction. The peak in particle mass on that day coincided with
vacuuming and sweeping of carpets and floors. On another day, cooking of stir-fried
vegetables and rice produced a large number of small particles, with those <0.1 /mi
accounting for 30% of the total EAA particle volume, much more than the normal amount.
The cooking contribution of that one meal to total 8-h daytime particle volume exposure was
calculated to be in the range of 5 to 18%. The authors concluded that the most significant
indoor source of small particles (<2.5 /mi) in all three of these nonsmoking homes was
cooking, while the most significant source of large particles (> 10 /mi) was vacuum
sweeping. Inhalable coarse particles (PM10 — PM2.5) appeared to be of largely biological
(human dander and insect parts) and mineral (clay, salt, chalk, etc.) origin.
In a test of a new sampling device (a portable nephelometer), Anuszewski et al. (1992)
reported results from indoor and outdoor sampling at nine Seattle, WA, homes sampled for
an average of 18 days each during the whiter of 1991 to 1992. The nephelometer is a light-
scattering device with rapid (1-min) response to various household activities such as
sweeping, cigarette smoking, frying, barbecuing, and operating a fireplace. Homes with
fewer activities showed high correlations of indoor and outdoor light-scattering coefficients,
both between hourly averages and 12-h averages. However, homes with electrostatic
precipitators, with weather-stripped windows or doors, and with gas cooking or heating
devices showed weak 12-h indoor-outdoor correlations.
Chan et al. (1995) studied particles and nicotine hi seven homes with one smoker each
in Taiwan. Sampling was carried out in summer and winter of 1991. Each home had one
indoor PM5 sampler in the living room and another in the yard. In the winter study, two
homes had PM10 samplers added inside and outside and at two central sites. Indoor mean
7-49
-------
PM5 concentrations averaged 44 ± 32 (SD) /ig/m3 in summer compared to outdoor levels of
27 ± 15 /ig/m3. Corresponding winter values were 107 ± 44 /ig/m3 and 92 ± 40 /tg/m3.
Daisey et al. (1987) measured RSP, PAH, and extractable organic matter (EOM) in
seven Wisconsin homes with wood stoves; one 48h (1,000 m3) sample was collected during
woodburning and a second sample was collected when no woodburning occurred. Five of
seven homes had somewhat higher RSP levels during woodburning, but the mean difference
was not significant.
Highsmith et al. (1991) reported on two 20-home studies in Boise, ID and Roanoke,
VA. The Boise study assessed the effects of wood burning on ambient and indoor
concentrations in the area. Ten homes with wood burning stoves were matched with
10 homes without such stoves. One matched pair of homes was monitored from Saturday
through Tuesday for eight consecutive 12-h periods. Ambient PM2 5 levels increased by
about 50% at night, suggesting an influence of woodburning. Indoor PM2 5 concentrations
also were increased (by about 45%) in the homes with the wood burning stoves compared to
those without (26.3 versus 18.2 /ig/m3), although coarse particles showed no increase
(10.2 versus 9.7 /ig/m3). The Roanoke study, designed to assess the effects of residential oil
heating, showed no effects on indoor levels of fine or coarse particles.
Lofroth et al. (1991) measured particle emissions from cigarettes, incense sticks,
"mosquito coils," and frying of various foods. Emissions were 27 and 37 mg/g for two
brands of Swedish cigarettes, 51 and 52 mg/g for incense sticks and cones, and 61 mg/g for
the mosquito coil. Emissions from frying pork, hamburgers, herring, pudding, and Swedish
pancakes ranged from 0.07 to 3.5 mg/g.
Mumford et al. (1991) measured PM10, PAH, and mutagenicity in eight mobile homes
with kerosene heaters. Each home was monitored for 2.6 to 9.5 h/day (mean of 6.5 h) for
three days a week for two weeks with the kerosene heaters off and for two weeks with them
on (average on-time of 4.5 h). Mean PM10 levels were not significantly increased when the
heaters were on (73.7 ± 7.3 (SE) /tg/m3 versus 56.1 ± 5.7 /ig/m3), but in two homes levels
increased to 112 and 113 /ig/m3 when the heaters were on. Outdoor concentrations averaged
18.0 ± 2.1 /ig/m3.
Colome et al. (1990) measured particles using PM10 and PM5 (cyclone) samplers inside
and outside homes of 10 nonsmokers, including eight asthmatics, living in Orange County,
7-50
-------
CA. Indoor PM10 samples were well below outdoor levels for all homes (mean of
42.5 ± 3.7 (SE) /ig/m3 indoors versus 60.8 ± 4.7 /ig/m3 outdoors). No pets, wood stoves,
fireplaces, or kerosene heaters were present in any of these homes.
Lioy et al. (1990) measured PM10 at eight homes (no smokers) for 14 days in the
winter of 1988 in Phillipsburg, NJ, which has a major point source consisting of a grey-iron
pipe manufacturing company. The Harvard impactor was used indoors to collect 14 24-h
samples beginning at 4:30 p.m. each day; Wedding hi-vol PM10 samples were deployed at
three outdoor sites. A fourth outdoor site was located on a porch of one of the homes,
directly across the street from the pipe manufacturer. The first three sites showed little
difference from one another, whereas on day 4 and day 6 of the study, the outdoor sampler
on the porch had readings that were considerably (about 40 /xg/m3) higher than the other
outdoor samplers, suggesting an influence of the nearby point source. The geometric mean
outdoor PM10 concentration was 48 /ig/m3 (GSD not provided) compared to 42 /ig/m3
indoors. A simple regression equation for all homes (N = 101 samples) explained 45% of
the cross-sectional variance in indoor PM10:
Indoor PM10 = 0.496 Outdoor PM10 + 21.5 (R2 = 0.45)
However, individual regressions by home showed much better R2 values in most cases,
ranging from 0.36 to 0.96 (Table 7-14). All slopes were significant.
Thatcher and Layton (1995) measured optical particle size distributions inside and
outside a residence in the summer. Measured deposition velocities for particles between
1 and 5 /im closely matched the calculated gravitational settling velocities; however, for
particles >5 /mi, the deposition velocity was less than the calculated settling velocity,
perhaps due to the non-spherical nature of these particles. The deposition velocities
determined by the authors corresponded to a particle deposition rate k of 0.46 h"1 for
particles of size range 1 to 5 /ma and 1.36 h"1 for particles of size range 5 to 10 /im. These
values are very comparable with the values of 0.39 h"1 for particles less than 2.5 /tm and
1.01 h"1 for particles between 2.5 and 10 /mi found by the PTEAM Study. The authors
measured the penetration factor P by the following method: They first carried out vigorous
house cleaning activities to raise the level of resuspended dust well above outdoor levels.
7-51
-------
TABLE 7-14. REGRESSION OF INDOOR ON OUTDOOR PM10
CONCENTRATIONS: THEES STUDY, PHILLIPSBURG, NJ Otg/m3)
House
1
2
3
4
5
6
7
8
N
14
14
9
14
13
13
12
14
Intercept
19
16
9
20
6
-1
24
27
SE
9
14
5
21
10
18
25
8
P
NS
NS
NS
NS
NS
NS
NS
S
Slope
0.44
0.40
0.55
0.73
0.43
0.89
0.70
0.54
SE
0.06
0.08
0.04
0.15
0.07
0.13
0.29
0.05
P
S
S
S
S
S
S
S
S
R2
0.79
0.68
0.96
0.66
0.75
0.81
0.36
0.91
S = Significant
NS = Non-significant
Source: Data from THEES Study (Lioy et al., 1990).
They then left the house, while automated instruments measured the deposition rate k for the
different particle sizes and the ah- exchange rate a for SF6 tracer gas. With these values of
a and k in hand, they solved the equation for P, using the steady-state values for Cin and Cout
observed long after the dust had settled:
P - ^*> (7-6)
c«,"
For all size ranges tested, including the largest (10 to 25 /on), the experimentally determined
value for P was not significantly different from 1 (Figure 7-13). This result is hi agreement
with the PTEAM conclusion that P is 1 for both fine and coarse particles, although the latter
conclusion was derived from a nonlinear (statistical) approach whereas the present result was
experimentally obtained.
The resuspension results of Thatcher and Layton (1995) (Figure 7-14) show the effect
of a vigorous housecleaning activity. The authors concluded "Although particles larger than
5 /*m show significant resuspension hi these experiments, particles smaller than 5 fan are not
readily resuspended, and particles less than 1 pun show almost no resuspension even with
vigorous activity." Figure 7-15 shows that just one person walking hi and out of a carpeted
7-52
-------
1 to 3 urn
i i
3 to 6 urn
1 to 5 urn
I
§1
s.
1234
Experiment Number
Figure 7-13. Results of six penetration experiments in a test home.
Source: Thatcher and Lsyton (1995).
Particle Diameter
• 0.3 to 1 urn
B 1 to 5 urn
* 5 to 10 urn
e 10 to 25 urn
^ > 25 urn
10
50
60
20 30 40
Time (minutes)
Figure 7-14. The change in suspended particle mass concentration versus tune, as
measured by optical particle counter, assuming spherical particles of unit
density. All resuspension activities are stopped at t = 0.
Source: Thatcher and Layton (1995).
7-53
-------
Cleaning
2Min
Walk/Sit
4 People
5 minutes
4 People
30 minutes
Walk In
0.5 to 1 urn
m 5 to 10
Particle Diameter (\im)
10 to 25 jim
Figure 7-15. The ratio of the suspended particle concentration after a resuspension
activity to the indoor concentration before that activity, by particle size.
The activities tested are (1) vigorous vacuuming and housecleaning,
(2) 2 min of continuous walking and sitting in the living area by one
person, (3) 5 nun of normal activity by four people, (4) 30 min of normal
activity and (5) one person walking into and out of the living area.
Source: Thatcher and Layton (1995).
living area can increase indoor particle concentrations in the ranges 5 to 10 /tin by 100% and
10 to 25 /im by 200%. The absolute increase in indoor concentrations by this activity is a
function of the surface dust loading in those size ranges. Surface dust loadings (/ig/m2)
increase with the time since last cleaning (Raunemaa et al., 1989; Wilmoth et al., 1991).
Because fluffy house dust can be resuspended, it will contribute to total airborne
exposure to particles and constituents such as metals and pesticides. Roberts et al. (1990)
studied 42 homes in Washington State. Geometric mean lead concentration hi 6 homes
where shoes were removed on entry was 240 /ig/m2 on carpets, compared to 2,900 /ig/m2 on
carpets in 36 homes where shoes were kept on. In Japan, where shoes are removed on entry
and straw mats (tatami) are usually used instead of carpets, Tamura et al. (1996) found
7-54
-------
evidence of negligible PM10 resuspension. These findings suggest that most of the carpet
dust in a home enters via track-in on shoes rather than by infiltration of ambient air.
7.2.2.3 Personal Exposures to Environmental Tobacco Smoke.
Jenkins et al. (1995a) reported on the first 12 cities of a 16-city sampling survey
comparing ETS exposures at home and at work. About 100 nonsmoking persons in each city
were recruited to wear a personal monitor at work and another personal monitor away from
work. The monitors collected PM3 5 particles, which were then analyzed for tobacco smoke
markers (UVPM, FPM and solanesol). Nicotine and other gas-phase markers were also
collected. Subjects provided saliva samples, which were used to screen out smokers
reporting themselves as nonsmokers. (Using different cutoff points of 10, 30, or 100 jug/L,
between 1.82 and 5.2% of the 1073 subjects would have been misclassified as nonsmokers).
Four cells were defined: persons exposed to smoke at home and at work (N = 119); persons
exposed at home but not at work (110); persons exposed at work but not at home (163); and
persons exposed neither at home nor at work (504). All four particle markers agreed in
ranking the four cells for total ETS exposure in the order listed—that is, nonwork (including
home) ETS exposures were greater than work exposures as shown in Table 7-15. The
authors identified several problems with the selection of the sample. First, the sample was
68% female. Secondly, the socioeconomic level was biased high, with about twice as many
persons having some college or being college graduates as the population as a whole. It is
well known that smoking rates decrease as education and income rise, and this study
confirmed that observation-when broken out by income, ETS markers decreased by factors
of 2 to 5 as annual income rose from $10,000 to $100,000. The authors compared ETS
levels in offices with no smoking (N = 629), restricted smoking (N = 297) and unrestricted
smoking (N = 113). Median (mean) levels of RSP increased from 13 (18) to 16 (28) to
33 (58) /ig/m3 in the three categories, with corresponding nicotine medians (means) of
0.025 (0.11), 0.09 (0.87), and 0.44 (2.7) /xg/m3.
Jenkins et al. (1995b) updated the results to the full 16 cities. The final number of
participants in the four cells were 157, 234, 281, and 808, respectively. The median RSP
(PM3 5) values changed only slightly, increasing to 33.6 from 32 /xg/m3 in Cell 1 and
decreasing to 23.3 /xg/m3 in Cell 2, with no changes in the remaining two cells.
7-55
-------
TABLE 7-15. MEDIAN VALUES (jig/m3) FOR
ENVIRONMENTAL TOBACCO SMOKE MARKERS
Cell (N)
1 (119)
2 (110)
3 (163)
4 (504)
Nonwork
S
S
NS
NS
Work
S
NS
S
NS
RSP
32
24
20
15
UVPM
12
7.6
2.3
1.1
FPM
7.7
5.9
1.2
0.6
Solanesol
0.113
0.058
0.003
ND
Nicotine
1.46
0.56
0.11
0.02
S = smoker; NS = nonsmoker; ND = not detectable.
Source: Jenkins et al. (1995a).
ETS Exposures in Restaurants and Buildings. Oldaker et al. (1993) reported results
of analyzing ETS markers in four office buildings. Median RSP levels were 30 and
34 jug/m3 in two buildings allowing smoking, compared to 5 and 7 jug/m3 in two buildings
without smoking. Grouse et al. (1989) reported on measurements of RSP (PM3 5) in
42 North Carolina restaurants. Geometric mean (arithmetic mean) values were 5.3 (8.6),
26.1 (34.1) and 62.0 (80.8) jig/m3, respectively. Oldaker et al. (1990) measured PM3 5 in
33 restaurants in the Winston-Salem, NC, area during the summer of 1986 and the winter of
1988 to 1989; in the winter, the cutpoint was changed to PM2 5. A wide range of particle
concentrations was noted, from 18 to 1,374 jug/m3 in the summer, and <25 to 281 jig/m3 in
winter.
7.2.2.4 The Fraction of Outdoor Air Particles Penetrating Indoors
Having reviewed the literature on particles in homes, it is useful to return to one of the
questions we asked at the outset: For a home with no indoor sources or resuspension of
settled dust of ambient origin, how much protection is offered against outdoor particles of
various size ranges?
The governing equation in this case is
Cin Pa
(7-6)
7-56
-------
Thus, there are three parameters affecting the fraction of outdoor air particles to be found
indoors: the penetration factor P, the air exchange rate a, and the particle deposition rate k.
Penetration Factor P. The penetration factor P is a measure of the ability of a gas or
particle to penetrate the building envelope; 0 < P < 1. For a nonreactive gas, such as CO,
the factor is expected to be 1. For large particles, the factor would be expected to go to zero
with increasing particle size and decreasing air exchange rate. The question is at what
combinations of size range and air exchange rate does the factor P begin to decrease
significantly from unity for PM?
Two recent studies have attempted to determine the value of P for different particle size
ranges. The PTEAM study (Ozkaynak et al., 1996) found a value of P « 1 for both PM2 5
and PM10 particles. The value was determined statistically by a nonlinear solution of
Equation 7-5 (including all indoor sources) for 178 homes. Thatcher and Layton (1995) also
found a value of P « 1 for all size ranges tested, including the ranges 1 to 3 jum, 3 to 6 /xm,
1 to 5 pm, 5 to 10 pun, and 10 to 25 jrni. The authors determined their values
experimentally by direct measurement on one instrumented house. The results for the first
two size ranges were obtained in five replicate experiments; for the last three size ranges, in
only one experiment (Figure 7-13). Thus the two studies used different methods but arrived
at the same conclusion: particles less than 10 \im in aerodynamic diameter penetrate
building envelopes with an efficiency approaching that of nonreactive gases. Clearly, more
work needs to be done to test this finding at lower air exchange rates.
Air Exchange Rate a. Air exchange rates in residences depend on three major factors:
building construction, ambient conditions, and resident activities.
The building construction determines the lower bound of the air exchange rate. That
is, rates cannot be reduced below the rate allowed by diffusion through the building cracks,
holes, and other uncontrolled means of particle ingress in the absence of wind and buoyancy
differences. Tests by building pressurization (e.g., using "blower doors") are able to
determine a parameter ("crack length") that quantifies this lower bound. Buildings that are
extremely tightly constructed for energy efficiency are able to reduce the lower bound of the
air exchange rate to the order of 0.1 air change per hour (ach, or h"1).
7-57
-------
Ambient conditions, particularly temperature and wind velocity, can also drive air
exchange rates. Strictly speaking, it is the difference between indoor and outdoor
temperatures that creates either a pressure difference (closed windows) or a convective
behavior (open windows) leading to higher air exchange rates as the temperature difference
increases. As wind velocity rises, pressure differences also increase and therefore the air
exchange rate rises. Besides these immediate ambient conditions we also have climatic
conditions. A region that can expect a daily sea breeze is more likely to use open windows
than air conditioning for ventilation. Northern areas are more likely to have tightly
constructed buildings than southern areas in the USA.
In most cases, by far the most important factor affecting air exchange rates is the
behavior of the resident(s). This includes such considerations as the number of residents, the
number and age of children, the number of pets that spend time outdoors, whether or not air
conditioning is used, and how much time doors and windows are open. Since residents are
more active during the day, and doors are opened and closed more often, air exchange rates
during the day typically exceed those at night, both in winter and in summer. In the
PTEAM Study, the median daytime air exchange rate was 1.02 h"1 compared to an overnight
median of 0.80 h'1 (Wallace et al., 1993). In the Parkville community of Baltimore, MD, in
the spring, the daytime median was 0.40 h"1 and the overnight median was 0.28 h"1. In Los
Angeles coastal communities in the summer, the daytime median was 2.2 h"1 and the
overnight median was 1.2 h"1. (All values derived from U.S. Environmental Protection
Agency, 1995)
Fortunately, a large number of surveys have been carried out in which air exchange
rates of homes have been measured. These include the three major particle studies already
mentioned, and some studies of other pollutants. A paper collecting results from many
surveys found a geometric mean for 2844 U.S. residences of 0.53 h"1 with a geometric
standard deviation of 2.3 (Murray and Burmaster, 1995). The mean value for all
2844 homes was 0.76 h"1, which corresponded to the 70th percentile. However, the
geometric means varied by season (a low of 0.31 h"1 hi fall and a high of 1.00 h"1 in
summer) and by region (a low of 0.31 h"1 in the North and a high of 0.69 h"1 in the
South—mainly southern California). The geometric standard deviations for individual
seasons and regions were generally very close to 2, ranging from 1.9 to 2.5. (It should be
7-58
-------
noted here that the homes were not selected to represent the nation, and that there are very
great disparities in the number of homes sampled in any one region.)
A second paper (Koontz and Rector, 1995) used a nearly identical data set, but
weighted the 2889 measured homes by the state populations to estimate more closely the
national distribution. Their estimates are similar to those of Murray and Burmaster (1995)
with an arithmetic mean of 0.63 h"1, a geometric mean of 0.46 h"1 and a GSD of 2.25.
However, certain smaller areas with pronounced climatic conditions could have very
much higher air exchange rates. In a region such as the South Bay of Los Angeles, Wallace
et al. (1991c) found that 49 of 50 homes had no air conditioning and depended on the daily
land-sea breeze for ventilation. In this area, winter air exchange rates had a geometric mean
of 0.75 h"1 and summer air exchange rates were much higher, with a geometric mean of
2.16 h"1. Both these ranges are much higher than the typical values reported above. Thus, it
is important to consider the individual geographic region of study and its local climatic
characteristics before selecting a range of air exchange rates to characterize the region.
With that caveat, the empirical distribution for a large number of U.S. homes across all
seasons, but with disparate representation among the various regions of the country, appears
to have a median value of about 0.5 h"1, with a one geometric standard deviation (+ a) range
of 0.2 to 1.1 h'1, and a ±2o range of 0.1 to 2.2 h'1 (Murray and Burmaster, 1995; Koontz
and Rector, 1995).
Deposition Rate k. In a residence, the deposition rate k depends on many factors, such
as scale of turbulence, and the size, shape, electrostatic charge, and density of the particle.
For larger particles, the deposition rate is determined largely by gravitational settling; for
smaller particles, deposition on vertical surfaces by diffusion may also be important
(Nazaroff et al., 1993). Unfortunately, fine particle deposition rates are not well
characterized. Typically, one must measure over very long periods of time (weeks to
months) to collect enough particles for analysis by sophisticated techniques. A series of
studies in nearly unoccupied buildings containing telephone-switching electrical equipment
resulted in average values for the deposition velocity of sulfate particles ranging from
0.003 to 0.005 cm/s (Sinclair et al., 1988, 1990, 1992; Weschler et al., 1989); these values
correspond to values of k (using a surface to volume ratio of 3 m"1) of 0.3 to 0.5 h"1.
7-59
-------
However, another series of studies in museums resulted in values an order of magnitude
smaller (Ligocki et al., 1990; Nazaroff et al., 1990a,b). Results for the sulfur (PM2 5)
deposition rate in the PTEAM studies were 0.16 h"1, lying between the values found by these
two groups. Nazaroff et al. (1993) concluded that deposition rates could vary as a result of
different surfaces or near-surface air flows, amount of thermal isolation of the surfaces from
building walls, turbulence, and many other factors. Thus it is not likely that theoretical
calculations of deposition rates will provide trustworthy estimates. Nor is it likely that
chamber studies, with their limited ability to reproduce the variety of floor coverings and air
flows found in residences, can provide much information relevant to real-world residences.
In the absence of precise theory or widely applicable chamber study estimates, the
largest study of residences including a calculation of empirical deposition rates is the
PTEAM study. The estimate for PM25 was 0.39 h'1, for PM10 it was 0.65 h'1, while for the
coarse fraction (the difference between PM10 and PM2 5) it was 1.01 h"1.
What Is the Fraction of Outdoor Air Particles Found Indoors at Equilibrium?
Based on the values of P, a, and k discussed above, an answer can be provided to this
question. Figure 7-16 shows the fraction of outdoor fine and coarse particles found in homes
under equilibrium conditions for a range of air exchange rates. This fraction is calculated
using the value of P = 1 determined in the PTEAM and the Thatcher and Layton (1995)
studies, and the values of k for fine and coarse particles calculated in the PTEAM study.
The fractions are displayed over the 95% range of observed air exchange rates (0.1 to
2.2 h"1) in studies reported on by Murray and Burmaster (1995). It can be seen that at the
mean air exchange rate of 0.76 h"1 reported in Murray and Burmaster (1995), the fractions of
outdoor fine (<2.5 jirn) and coarse particles (>2.5 and < 10 /im) that will be found indoors
under equilibrium conditions are 66% and 43%, respectively. The fraction of PM10 found
indoors will lie between these two curves, with the exact placement dependent on the relative
proportions of fine and coarse particles constituting the PM10.
The actual distribution of values of a/(a+k) observed in the PTEAM Study is provided
in Table 7-16 for PM10 and for its fine and coarse fractions. As can be seen, the average
values across day and night were about 67% for fine particles and 47% for coarse particles,
with PM10 exactly between the two size fractions at 57%.
7-60
-------
u.
2.5
0.5 1 1.5 2
Air exchange rate (air changes per hour)
Deposition rate - 0.39/h for fine particles, 1.01/h for coarse
Figure 7-16. Fraction of indoor participate matter (PM) from outdoor airborne PM,
under equilibrium conditions, as a function of air-exchange rate, for two
different size fractions.
Source: Calculated from PTEAM database (Ozkaynak et al., 1993a; Wallace, 1996).
These results suggest that if persons at risk of health effects from outdoor particle
pollution are able to significantly decrease the air exchange rates in their homes
(by weatherization, installation of air conditioning to reduce use of windows, etc.) they could
decrease the fraction of outdoor air particle concentration in their homes. A decrease in the
air exchange rate from the mean level of 0.76 h'1 reported above to an achievable (16th
percentile) value of 0.25 h"1 would decrease the indoor air level of outdoor-generated fine
PM2 5 particles from 66% to 39% of the outdoor level, and of PM10 from 54% to 28%.
7.2.2.5 Studies of PM in Buildings
The single largest study of particles in buildings was carried out by the Lawrence
Berkeley Laboratory (LBL) for the Bonneville Power Administration (BPA) (Turk et al.,
1987, 1989). Thirty-eight buildings were chosen from two climatic regions in the Pacific
Northwest: Portland-Salem, OR (representing mild coastal conditions), and Spokane-Cheney,
7-61
-------
TABLE 7-16. FRACTION OF CONCENTRATION OF
OUTDOOR PARTICLES ESTIMATED TO BE FOUND INDOORS AT
EQUILIBRIUM: RESULTS FROM THE PARTICIPATE TOTAL EXPOSURE
ASSESSMENT METHODOLOGY STUDY
Daytime (N =
Statistic
Mean
Standard deviation
Standard error
Geometric mean
Minimum
25th percentile
Median
75th percentile
Maximum
Fine
0.68
0.17
0.013
0.66
0.28
0.55
0.70
0.83
0.95
PM10
0.58
0.19
0.015
0.55
0.19
0.42
0.58
0.75
0.93
174)
Coarse
0.49
0.20
0.015
0.45
0.13
0.32
0.47
0.65
0.89
Overnight (N = 175)
Fine
0.66
0.15
0.012
0.64
0.28
0.55
0.66
0.79
0.94
PM10
0.55
0.17
0.013
0.53
0.19
0.43
0.54
0.69
0.90
Coarse
0.46
0.17
0.013
0.42
0.13
0.32
0.43
0.59
0.85
Fractions calculated from the formula Pa/(a+k), where
/>= 1;
k = 0.39 h'1 for fine particles, PM2 5;
k = 0.65 h4 for PMi0; and
k = 1.01 h"1 for coarse particles 2.5 ^m < AD < 10 ftm.
Values for a measured in 175 homes during the PTEAM Study.
Source of data: Values calculated from PTEAM database (Wallace, 1996).
WA (representing extreme inland conditions). The buildings were studied for a variety of
pollutants to determine how ventilation rates affect indoor air quality. Buildings were
measured in winter (21 buildings in both regions), spring (10 buildings in both regions) and
summer (nine buildings in the inland region only). All but four buildings were government
or public properties, and therefore the 38 buildings cannot be considered to represent the full
mix of building types.
Each building was monitored for 10 working days over a two-week period. From four
to eight particle sampling sites were chosen in each building according to size. The sampler
was an LBL-developed flow controlled device with a 3 /xm cutpoint. The pumps sampled
only during hours the building was occupied. If filters had to be changed due to excessive
loading, the combined weight of all filters from one site was determined—thus all values are
7-62
-------
approximately 10 working-day (80-h) averages. Buildings had varied types of smoking
policies, from relatively unrestricted to very tightly controlled, as in one elementary school.
In most buildings, an attempt was made to site at least one monitor in an area where smoking
was allowed. Data were obtained from smoking areas in about 30 of the 38 buildings.
Results comparing smoking and non-smoking areas are provided in Table 7-17 and
Figure 7-17. Mean RSP concentrations in the smoking areas were more than three times
higher than in the non-smoking areas (70 versus 19 /xg/m3). Since these arithmetic means
showed evidence of being driven by one or two high values, the geometric mean (averaged
across all sites in a building) may be a better comparison. Here the ratio is very close to
3 to 1 (44 versus 15 jiig/m3). Outdoor results at 30 sites had the identical arithmetic mean as
the indoor non-smoking sites: 18.9 /^g/m3.
Repace and Lowrey (1980) sampled 19 establishments allowing smoking (seven
restaurants, three bars, church bingo games, etc.) and 14 where no smoking occurred
(including five residences and four restaurants) between March and early May of 1978.
Sampling occurred for short periods of time (2 to 50 min) using a TSI Piezobalance to
measure PM3 5. Indoor concentrations ranged from 24 to 55 ptg/m3 in the areas without
smoking, and from 86 to 697 pig/m3 in places with active smoking.
Miesner et al. (1989) sampled particles and nicotine in 57 locations within 21 indoor
sites in Metropolitan Boston, MA, between July 1987 and February 1988. PM2 5 was
sampled using Harvard aerosol impactors. Sampling times ranged from about 3 h in a bus
station to 16 h in a library, depending partly on how "clean" the environment was perceived
to be. PM2 5 concentrations ranged from 6 /xg/m3 (in the library) to 521 /ig/m3 in a smoking
room in an office building. For 42 measurements in non-smoking areas, the mean PM2 5
concentration was 25 ± 30 (SD) /^g/m3. Six of these measurements included a classroom
with visible levels of chalk dust on the impactor, four measurements in subways, and the bus
station. The remaining 36 nonsmoking areas had a mean PM2 5 concentration of
15 ± 7 /ig/m3. The 15 smoking areas ranged from 20 to 520 /ig/m3 with a mean of
110 ± 120/ig/m3.
Sheldon et al. (1988a,b) reported on the EPA 10-building study of hospitals, homes for
the elderly, schools, and office buildings. Particle measurements were taken in six buildings
using a National Bureau of Standards portable particle sampler (McKenzie et al., 1982) to
7-63
-------
TABLE 7-17. SMOKING, NONSMOKING, AND
OUTDOOR RSP CONCENTRATIONS AND RATIOS
Building No.
1
2
3
4
5
6
7
8
9
10
11"
12
13
14
15
16
17b
18
19
20
21
22
23
24
25
26
27
28
29
30b
31
32
33
34
35
36*
37
38
39
40
AM
ASD
GM
GSD
fcg/m3)
ND
ND
ND
8
BD
35
35
8
8
9
8
ND
10
6
BD
10
7
7
7
18
17
20
11
11
68
32
52
65
29
33
13
ND
ND
16
18
20
19
14
11
11
19
16
14
2.2
InHnnr
0»g/m3) Arithmetic Mean (Range)
Nonsmoking
25(19-36)
19(18-21)
ND
7(6-8)
13(13)
12(11-13)
38(32-44)
7(7-8)
11(11)
65(53-74)
23(9-49)
10(10)
5(5-6)
ND
11(7-14)
9(8-11)
11(10-13)
ND
ND
11(10-11)
11(9-12)
18(18)
9(BD-20)
44(10-77)
35(32-38)
45(20-70)
36(33-38)
36(29-43)
10(8-12)
24(20-30)
12(8-18)
13(10-17)
ND
13(10-16)
20(6-35)
14(9-18)
21(12-32)
7(BD-9)
8(8-9)
10(8-12)
19
14
15
1.9
Smoking0
ND
ND
20(16-25)
ND
14(14)
35(23-59)
39(39)
ND
16(13-20)
95(67-127)
209(209)
63(63)
ND
30(26-34)
12(12)
73(73)
105(105)
19(19)
20(11-29)
ND
ND
57(22-165)
ND
24(24)
109(109)
82(55-123)
61(33-89)
BD
144(144)
113(113
268(268)
36(21-52)
29(12-74)
54(13-117)
50(50)
72(17-127)
27(11-62)
308(308)
13(11-14)
26(11-40)
70
73
44
2.7
"Repeated test of building #11.
'"Repeated test of building #17.
cSmoking within
10 m radius of site
Meand
25(19-36)
19(18-21)
20(16-25)
7(6-8)
13(13-14)
28(11-59)
38(32-44)
7(7-8)
15(11-20)
86(53-127)
63(9-209)
36(10-63)
5(5-6)
30(26-34)
11(7-14)
31(8-73)
40(10-105)
19(19)
20(11-29)
11(10-11)
11(9-12)
50(18-165)
9(BD-20)
37(10-77)
60(32-109)
67(20-123)
48(33-89)
24(BD-43)
32(8-144)
37(20-113)
64(8-268)
21(10-52)
29(12-74)
28(10-117)
23(6-50)
28(9-127)
25(11-62)
46(BD-308)
11(8-14)
15(8-40)
30
19
24
2.0
NA
ND
BD
Ratios
Indoor Indoor
Nonsmoking •*• Smoking -s-
Outdoor
NA
NA
NA
0.9
NA
0.3
1.1
0.9
1.3
7.0
2.9
NA
0.5
NA
NA
0.9
1.6
NA
NA
0.6
0.7
0.9
0.8
4.0
0.5
1.4
0.7
0.6
0.3
0.7
0.9
NA
NA
0.8
1.1
0.7
1.1
0.5
0.7
0.9
1.2
1.3
0.9
2.0
= Not applicable.
= No data collected.
= Below detection limit.
Outdoor
NA
NA
NA
NA
NA
1.0
1.1
NA
2.0
11.0
26.1
NA
NA
5.0
NA
7.3
15.0
2.7
2.9
NA
NA
2.9
NA
2.2
1.6
2.6
1.2
NA
5.0
3.4
20.6
NA
NA
3.4
2.8
3.6
1.4
22.0
1.3
2.4
6.0
7.2
3.6
2.6
Indoor
Mean -s-
Outdoor
NA
NA
NA
0.9
NA
0.8
1.1
0.9
1.9
9.6
7.9
NA
0.5
5.0
NA
3.1
6.1
2.7
2.9
0.6
0.7
2.5
0.8
3.4
0.9
2.1
0.9
0.4
1.1
1.1
4.9
NA
NA
1.8
1.3
1.4
1.3
3.3
1.0
1.4
2.3
2.2
1.7
2.3
dArithmetic average of all sites in building.
Source: Turk et al. (1987).
7-64
-------
80
70
^ 60
CO
I so
3 40
I 30
20
10
0
Mean Concentrations
Smoking areas Nonsmoking areas Outdoors
CO
50
40
30
Geometric Means
a> 20
DC
10
Smoking areas Nonsmoking areas Outdoors
Figure 7-17. Comparison of respirable particles in smoking and nonsmoking areas of
38 buildings in the Pacific Northwest.
Source: Turk et al. (1987).
7-65
-------
collect two size fractions: PM3 and a coarse fraction between PM3 and PM15. The sampler
employed two filters in series: an 8.0 fan Nuclepore filter for PM15 and a 3 jum Ghia Zefluor
Teflon filter for fine particles. The flow rate was 6 Lpm for a 24-h sample. Three
consecutive 24-h samples were collected at each building. Additional particle monitoring
was provided at certain locations (e.g., smoking lounge, cafeteria) using a Piezobalance
(PM3 5) and a dichotomous sampler (PM2 5 and PM10).
In areas without smoking, indoor concentrations of both size fractions were generally
lower than outdoor levels; for example, the coarse fraction ranged from 0.2 to 0.66 of the
outdoor level (13 to 17 ^g/m3) in the three buildings with no smoking. The fine fraction was
present at higher indoor-outdoor ratios, ranging from 0.56 to 0.99 in the same three
buildings (outdoor fine fraction ranged from 16 to 33 ptg/m3). The fine fraction was elevated
in the regions of smoking (range of 14 to 56 jug/m3). Piezobalance results for several
buildings showed uniformly low (7 to 29 /ig/m3) for 800 min of monitoring in nonsmoking
areas.
Concentrations in the areas allowing smoking were more often in the 40 to 60 ^g/m3
range, with short-term peaks as high as 345 jug/m3. It was possible to use the observed
declines in PM3 5 following cessation of smoking to calculate an effective air exchange rate
and thus a source strength for PM3 5 emissions from cigarettes. Four estimates gave an
average value of about 6 mg/cigarette, somewhat below the chamber study estimates of 10 to
15 mg/cig. An estimate due to Repace and Lowrey (1980) of concentrations of respirable
particulates due to smoking was also tested, with good agreement. The Repace and Lowrey
equation is
C fig/m3 = 27.6 Pala (7-7)
where Pa is smoking occupancy in persons per 100 square meters and a is the air exchange
rate h"1. Equation 7-7 was developed assuming one of every three occupants are smokers
who smoke two cigarettes per hour. Assuming a background concentration of 15 /zg/m3, the
measured values for the smoking lounge for zero, three, and nine smokers were 10, 78, and
284 /ig/m3, respectively. Equation 7-7 predicts 0, 99, and 296 /ig/m3, respectively. In two
of the homes for the elderly, apartments with smokers and nonsmokers were measured for
7-66
-------
three consecutive days using the NBS samplers. In one building, the smoker's apartment had
a 2-day PM3 average of 39 ptg/m3, compared to 9.4 pig/m3 in the nonsmoker's apartment; in
the other home for the elderly, where two smokers shared one apartment, the average 2-day
PM3 concentration was 88 /-ig/m3 compared to 8.6 jwg/m3 in the nonsmoking apartment. The
simultaneous ambient values were not measured at Home 1. At Home 2, the ambient value
was 11 /ig/m3.
Owen et al. (1990) studied particle size distributions in an office under varying
conditions of ventilation and occupancy. The unoccupied office using minimum outdoor air
had concentrations at least as low as the occupied office using maximum outdoor air. PM3 5
concentrations (measured using the TSI Piezobalance) were about twice as high (75 versus
39 /ig/m3) in the occupied office when the dampers were closed as when they were open.
The main source of particle generation appeared to be the hallway, suggesting that
resuspension of tracked-in dust was an important indoor source of particles as reported by
Roberts et al. (1990) for residences.
7.2.3 Indoor Air Quality Models and Supporting Experiments
Indoor concentrations of particles are a function of penetration of outdoor particles and
generation of particles indoors. The concentrations are modified by air exchange rates and
deposition rates of the particles onto indoor surfaces.
7.2.3.1 Mass Balance Models
Mass balance models have been used for more than a century in various branches of
science. All such models depend on the law of the conservation of mass. They simply state
that the change in mass of a substance in a given volume is equal to the amount of mass
entering that volume minus the amount leaving the volume. Usually they are written in the
form of first-order linear differential equations. That is, consider a volume V filled with a
gas of mass m. The change in mass Am over a small time Ar will simply be the difference
between the mass entering the volume (/nin) and the mass leaving the volume (mout):
7-67
-------
Am _ \mm mout) (7_g)
"AT At
Taking the limit as At approaches zero, we have the differential equation for the rate of
change of the mass:
— = — (m - m ) (7-9)
dt dt m out
If we require that the mass be uniformly distributed throughout the volume at all times,
we have a condition that the physical chemists call "well-mixed". We assume that any mass
gained or lost in the volume V is instantaneously distributed evenly throughout the volume.
We may then replace the mass term (m) by the concentration C = m/V, so that
dm/d?= VdC/dt.
The above equations are the basis for all such mass-balance models. Equation 7-9 takes
on many forms depending on the type of processes involved in transporting mass into or out
of the volume being considered. A large class of models assume that the volume V is a
single perfectly mixed compartment. More complex models assume multiple compartments
to allow for incomplete mixing in the total volume V (Mage and Ott, 1996). A detailed
mass-balance model that includes changes in particle size, chemical composition, and
turbulence is described in Nazaroff and Cass (1989).
7.2.4 Summary of Indoor Particulate Matter Studies
At low outdoor levels of fine (PM3 5 or PM2 5) particles (as in most of the cities in the
Harvard Six-City and New York State studies), mean indoor concentrations have been found
to be twice as high as outdoor levels. However, for homes without smokers or combustion
sources, indoor levels are often roughly equal to outdoor levels (Santanam et al., 1990;
Leaderer et al., 1994; Neas et al., 1994). At high outdoor levels, mean indoor
concentrations have been about 10% lower than the mean outdoor concentrations in the two
areas studied (Steubenville, OH, and Riverside, CA). Indoor concentrations are considerably
higher during the day, when people are active, than at night. Based on a mass-balance
model, outdoor air was the major source of indoor particles in the PTEAM study, providing
7-68
-------
about 3/4 of fine particles (PM2 5) and 2/3 of inhalable particles (PM10) in the average home.
However, outdoor air contributed less than half of the indoor particle concentrations at seven
out of eight other sites with extensive indoor-outdoor measurements. Indoor concentrations
are much higher during the day, when people are active, than at night.
In the PTEAM study (with very high outdoor particle concentrations), indoor levels
were significantly influenced by outdoor levels, but with relatively low R2 values ranging
between 0.22 and 0.54. In the other two major studies, no significant indoor-outdoor
relation was observed. Regressions of indoor on outdoor particles seldom explained more
than half the variance of any study (R2 < 50%). However, in those studies with repeated
measures on the same house, (e.g., the PTEAM prepilot [Table 7-6], the Phillipsburg, NJ,
study [Table 7-15] and Tamura et al. [1996] in Section 7.4.2.1), longitudinal regressions of
indoor on outdoor particles often had much higher R2 values of 0.6 to 0.9 for each individual
house. Since the epidemiological studies of health effects of particles have been studies of
variation over time, the longitudinal regressions by individual home are expected to be more
relevant to the epidemiology studies than cross-sectional regressions across all homes in the
study. The better relationship showed by these regressions suggests that whatever structural
or behavioral characteristics affect indoor particle concentrations in the home tend to persist
or be repeated over tune. This gives better support to the epidemiological findings than
would be inferred from the typically low R2 values reported for the cross-sectional
regressions performed in most studies.
Deposition rates k ranged from 0.16 h"1 for sulfur to 0.4 h'1 for fine (PM2 5) particles
to 1 h"1 for coarse particles (PM10 - PM2 5), with an intermediate estimate of 0.65 h"1 for
PM10. The penetration factor P for both fine and coarse fractions was estimated to be unity.
For a home with no indoor sources whatever and a typical air exchange rate of about
0.75 h"1, these values for k and P would imply that sulfur indoors would be about
0.75/(0.16 + 0.75) = 82% of the outdoor value at equilibrium, fine particles indoors would
be about 0.75/(0.4+0.75) = 65% of the outdoor value at equilibrium, indoor PM10 would
be about 54% of outdoor levels, and indoor coarse particles would be about 43% of outdoor
levels. Since very few homes were observed to have concentrations this low, it can be
inferred that very few homes are free of important indoor sources of particles.
7-69
-------
A crucial question is the impact of outdoor particles on indoor particle concentrations.
It was found that the governing equation is a function of only two parameters: air exchange
rate a and particle deposition rate k: a/(a+k). Air exchange rates measured in the United
States appear to follow a roughly log-normal distribution with a geometric mean of 0.5 and a
geometric standard deviation about 2. With the values for the deposition rates provided
above, one can calculate the impact of outdoor particles on indoor concentrations for any
given value of the air exchange rate. At a low air exchange rate of, say, 0.4 h"1, sulfates
indoors will be 71% of their outdoor values, fine particles indoors will be 50% of their
outdoor values, while coarse particles will be 0.4/1.4 or 28% of their outdoor values. At a
higher air exchange rate of 1 h"1, sulfates will be 86% of their outdoor concentration, fine
particles will be 1/1.4 or 71% of their outdoor concentration, whereas coarse particles will
be 50% the outdoor concentration. The difference in both cases between the two size
fractions is about 0.2; that is, for the entire range of realistic air exchange rates (from 0.2 h"1
to 2 h"1), if the fraction of outdoor coarse (PM10 — PM25) particles found indoors is/, then
the fraction of fine particles found indoors will be approximately/ + 0.2. It can be seen
that a reduction in air exchange rate would reduce the impact of outdoor air on indoor air
particle concentrations.
7.2.5 Bioaerosols
Biologically-derived particles are frequently ignored components of both ambient and
indoor aerosols. This lack of attention is, in part, due to the fact that the bioaerosols are
considered "natural" and not amenable to control. Methods for their analysis are, in many
cases, highly variable, and very little exposure or exposure/response information is available.
Measurement methods for bioaerosols are discussed in Chapter 4 (Section 4.4). Various
health effects associated with bioaerosols are discussed in Chapter 11. A few reference
works that focus on bioaerosols include Gregory (1973), Edmonds (1979), Cox (1987),
Lighthart and Mohr (1994), and Cox and Wathes (1995).
For bioaerosols, there is considerable confusion among the terms reservoir, source,
particle, and agent. For the purposes of this chapter, the following definitions apply:
• Reservoir: the environmental niche in which source organisms are living
• Source: the organism that produced the particle
7-70
-------
• Particle: the particle shed from the organism
• Agent: the part(s) of the particle that actually mediate the disease process.
Examples of bioaerosol sources, particles and agents are presented in Table 7-18.
TABLE 7-18. AN OVERVIEW OF ORGANISMS, AEROSOLS,
AND DISEASE AGENTS
Sources
Aerosol Particles
Disease Agents
Plants
Animals
Fungi
Bacteria
Viruses
Pollen and pollen fragments, fragments of
other plant parts, spores (ferns, mosses), algal
cells
Skin scales, secretions (saliva, skin secretions),
excreta, body parts (arthropods)
Spores, hyphae, yeast cells, metabolites
(toxins, digested substrate material)
Cells, fragments, metabolites (toxins, digested
substrate material)
Viral particles
Glycoprotein allergens
Glycoprotein allergens
Glycoprotein
allergens, infectious
units, glucans,
mycotoxins
Infectious units,
allergens, endotoxin,
exotoxins
Infectious units
7.2.5.1 Plant Aerosols
Pollen
Pollen is produced by vascular flowering plants: trees (pines, cedars, birch, elm,
maple, oak, hickory, walnut, etc.), grasses, and weeds (ragweed, sage, Russian thistle,
lambs quarters, etc.). Within these large groupings, specific types are regionally common.
For example, ragweed is most common in the eastern United States. Birch pollen dominants
the spring pollen season in New England, while mountain cedar pollen is abundant early in
the year hi the southwest (Lewis et al., 1983).
Pollen levels outdoors are controlled by the number of plants available for pollen
release, the amount of pollen produced by each plant, factors that control pollen release and
dispersion from the plant, and factors that directly affect the aerosols (Edmonds, 1979). The
number of plants available depends on the many environmental factors that control plant
7-71
-------
prevalence, some of which are human factors. As an example, the abundance of the ragweed
plant in a particular year depends on the number of plants that produced seed in the previous
year, disturbed ground available for seed germination and growth, and meteorological factors
during the growing season. Once a crop of ragweed has been produced, pollen production
depends on temperature, rainfall, and day length.
Pollen grains are relatively large complex particles that consist of cellular material
surrounded by a cell membrane and a complex wall. Pollen grain structure has been well
studied. Pollen shed is controlled by temperature, humidity, wind, and rain. Pollen levels in
air depend on all of these factors as well as wind and rain conditions after release, and on
surfaces available for impaction. Figure 7-18 represents day to day ragweed pollen
prevalence in Kalamazoo, MI, for 1994.
1994 Kalamazoo, Michigan
1,000
£
3
100
I 10
nut nit i i
NlWIN I II
Jan-1 Jan-31 Mar-2 Apr-1 May-1 May-31 Jun-30 Jul-30 Aug-29 Sep-28 Oct-28 Nov-27 Dec-27
24-hour Total Pollen Counts
Figure 7-18. Chart of ragwood pollen prevalence. Sampling was not conducted before
April and during the first few days of October.
Source:
Pollen allergens are (apparently) water-soluble glycoproteins that rapidly diffuse from
the grain when it contacts a wet surface. The glycoproteins are (generally) specific to the
type of pollen, although large groups may be represented by a single allergen. For example,
7-72
-------
many different kinds of grasses carry similar allergens in their pollen grains. A number of
pollen allergens have been characterized: Amb a I (ragweed), Bet p I (birch), Par j I
(parietaria), etc.
Other Natural Plant Aerosols
Other plant-derived particles that are a natural part of outdoor air include algal cells;
spores of mosses, liverworts, club mosses, and ferns; and fragments of all kinds of plants.
Very little has been reported about the prevalence or human impact of any of these aerosol
particles, although they are presumed to carry allergens.
Man-Made Plant Aerosols (Soy, Latex, Occupational)
Man-made accumulations of plant material that are subsequently handled inevitably
produce bioaerosols. The most common practices that involve such accumulations are
storage, handling, and transport of farm products (hay, straw, grain), composting, and
manufacturing processes that involve the use of plant material. In addition, the use of some
plant products can result in disease-causing aerosols (Alberts and Brooks, 1992). The
aerosols produced from most of these processes are complex, and few have been accurately
characterized.
Grain Dust. It is well-recognized that grain dusts include respirable-size particles
(< 10 nm) although the exact nature of the particles and the agents of disease remain
speculative. Soybean dust aerosols released from freighters unloading the beans in port have
been blamed for epidemics of asthma.
Wood Dust. Wood trimmer's disease (from particles released from wood during high-
speed cutting). Sewage composting involves the use of wood chips that can release
allergenic aerosols.
iMtex. Latex-containing powder aerosols are produced when surgical gloves are used.
Latex particles also may be released from automobile tires.
7-73
-------
7.2.5.2 Animal Aerosols
Mammalian Aerosols
All mammals produce aerosols, from humans to the smallest mouse. Human aerosols
(skin scales, respiratory secretions) do not cause disease except, of course, for agents of
infection (see below). Other mammals release aerosols that cause hypersensitivity diseases.
The most common of these are cats, dogs, farm animals, laboratory animals, and house
mice, although all animals release aerosols that could be sensitizing under appropriate
conditions (Burge, 1995). Mammals only cause human disease when appropriate exposure
conditions occur. For cats, simply having a cat in a house will create such conditions, as
will handling any animal regardless of the environment. Cat allergens apparently become
aerosolized on very small particles (< 1 /xm) shed from skin and saliva. There is some
indication that dog, mouse, and other rodent allergens are borne on dried urine particles, and
particle sizes are similar to those of cat allergen. Little is known about other mammalian
aerosols. Cat and dog allergens have been characterized (Pel d I, Can f I) and other
mammalian allergens are under active study.
Avian Aerosols
Wild and domesticated birds associated with disease-causing aerosols include for
example: starlings (histoplasmosis); pigeons (histoplasmosis, pigeon-breeders disease);
parrots (psittacosis); poultry (poultry-handlers disease); etc. Of these diseases, only the
hypersensitivity diseases (pigeon breeders and poultry handlers disease) are caused by "bird"
aerosols. The others are infections caused by agents inhabiting the birds (see below). The
birds that release antigens that have caused human disease are those that are confined or
congregate close to people. The avian aerosol-hypersensitivity diseases are almost
exclusively confined to sites where birds are bred and handled extensively, especially in
indoor environments. Relatively little is known about avian aerosols. Probably skin scales,
feather particles, and fecal material are all released as antigen-containing aerosols. The
antigens (allergens) responsible for avian-related diseases have not been characterized.
7-74
-------
Insect Aerosols
Dust Mites. Dust mites are arthropods belonging to the family Pyrogliphidae. There
are two common species in temperate climates: Dermatophagoides farinae (which
proliferates under relatively dry conditions) and D. pteronyssinus which dominates
populations in more humid environments (Arlian, 1989). Dust mites thrive in environments
where relative humidity consistently exceeds 60 % and where skin scales and fungal spores
are available as a food source. Primary reservoirs for exposure are bedding and carpet dust.
The mite itself is about 100 /-im long, but it excretes 20 /mi membrane-bound fecal particles
that contain the allergens. Exposure to dust mite allergens apparently occurs only when
reservoirs are disturbed. Dust mites produce allergens that are a major cause of sensitization
hi children. The allergens are digestive enzymes that gradually diffuse from fecal particles
after deposition on mucous membranes. Several dust mite allergens have been characterized
and monoclonal antibodies against each have been raised and cloned. These include Der f I
and II, and Der p I and II (Platts-Mills and Chapman, 1987).
Cockroaches. Cockroaches are insects belonging to the Orthoptera (Mathews, 1989).
The most common cockroach infesting temperate climate buildings is Blatella germanica, the
German cockroach. Cockroaches are nocturnal, and inhabit dark environments where food
and water are available. Common food sources include stored animal or human food, and
discarded food (garbage). Cockroaches are extremely prolific, given appropriate
environmental conditions. Population pressure will eventually drive the roaches into the
daylight in search of food. Cockroaches shed body parts, egg cases, and fecal particles, all
of which probably carry allergens. Little is known about the particles that actually carry the
allergens. Two German cockroach allergens have been characterized: Bla g I, and Bla g II.
The function within the cockroach of these allergens is unknown. Cockroach allergens are
probably a major cause of asthma for some populations of children.
Other Insects. Fragments of gypsy moths and other insects that undergo massive
migrations can become abundant in ambient air. Sizes, nature, and allergen content of such
particles have not been studied. Cases of occupational asthma from exposure to insects (e.g.,
sewer flies) have been reported.
7-75
-------
Other Animal Allergens
It is likely that proteinaceous particles shed from any animal could cause sensitization if
exposure conditions are appropriate. For example, exposure to proteins aerosolized during
seafood processing have caused epidemics of asthma.
7.2.5.3 Fungal Aerosols
Fungi are primarily filamentous microorganisms that reproduce and colonize new
environments by means of airborne spores. Most use complex non-living organic material
for food, require oxygen, and have temperature optima within the human comfort range.
The major structural component of the cell wall is acetyl-glucosamine polymers (chitin).
Cell walls also may contain B-glucans, waxes, mucopolysaccharides, and a wide variety of
other substances. In the process of degrading organic material, the fungi produce CO2,
ethanol, many other volatile organic compounds, water, organic acids, ergosterol, and a
broad spectrum of secondary metabolites including many antibiotics and mycotoxins.
The fungi colonize dead organic materials in both outdoor and indoor environments.
Some fungi are able to invade living plant tissue and cause many important plant diseases.
A few fungi will invade living animal hosts, including people. Fungi are also universally
present in indoor environments unless specific efforts are made for their exclusion (i.e., as in
clean rooms). The kinds of fungi that are able to colonize indoor materials are generally
those with broad nutritional requirements (e.g., Cladosporium sphaerospermum), those that
are able to colonize very dry environments (e.g., members of the Aspergillus glaucus group),
or organisms that readily degrade the cellulose and lignin present in many indoor materials
(e.g., Chaetomium globosum, Stachybotrys atra, Merulius lacrymans). Yeasts (which are
unicellular fungi) and other hydrophilic taxa (e.g., Fusarium, Phialophora) are able to
colonize air/water interfaces. Water, in fact, is the most important factor controlling indoor
fungal growth, since food sources are ubiquitous (Kendrick, 1992).
Particles that become airborne from fungal growth include spores (the unit of most
fungal exposure), fragments of the filamentous body of the fungus, and fragments of
decomposed substrate material. Fungal spores range from about 1.5 /icm to > 100 /mi in size
and come in many different shapes. The simplest are smooth spheres; the most complex are
large multicellular branching structures. Most fungal spores are near unit density or less.
7-76
-------
Some include large air-filled vacuoles. Fungal spores form the largest and most consistently
present component of the outdoor bioaerosols. Levels vary seasonally, with lowest levels
occurring during periods of snow. While rain may initially wash large dry spores from the
air, these are immediately replaced by wet (hydrophilic) spores that are released in response
to the rain.
Some kinds of spores are cosmopolitan hi outdoor air (e.g., Cladosporium herbarum,
Alternaria tenuissima). Others produced by fungi with more fastidious nutritional
requirements are only locally abundant. A typical indoor fungal aerosol is composed of
particles penetrating from outdoors, particles released from active growth on indoor
substrates, and reaerosolized particles that have settled into dust reservoirs. Indoor fungal
aerosols are produced by active forcible discharge of spores, by mechanisms intrinsic to the
fungus that "shake" spores from the growth surface, and (most commonly) by mechanical
disturbance (e.g., air movement, vibration).
Allergic rhinitis and asthma are the only commonly reported diseases resulting from
fungal exposures outdoors, and which also commonly occur indoors. The allergens of fungi
are probably digestive enzymes that are released as the spore germinates. Other spore
components (of unknown function) may also be allergenic. Only very few fungal allergens
(out of possibly hundreds of thousands) have been characterized: (e.g., Alt a I, Cla h I, and
Aspfl).
Allergic fungal sinusitis and allergic bronchopulmonary mycoses occur when fungi
colonize thick mucous hi the sinuses or lungs of allergic people. The patterns of incidence of
allergic fungal sinusitis may be explained hi part by geographic variability in ambient fungal
exposures. Figure 7-19 shows total fungal spore counts in Kalamazoo, MI, for 1994. This
disease is most commonly caused by Bispora, Curvularia, and other dark-spored fungi.
Exposure patterns required for allergic bronchopuhnonary mycoses are unknown. This
disease is usually caused by Aspergillus fumigatus. Histoplasmosis and Coccidioidomycoses
are fungal infectious diseases that result from outdoor exposures to Histoplasma capsulatum
(a fungus that contaminates damp soil enriched with bird droppings) and Coccidioides inmitis
(a fungus that growth in desert soils. Indoor aerosol-acquired fungal infections are rare, and
restricted to immunocompromised people (Rippon, 1988).
7-77
-------
1994 Kalamazoo, Michigan
10,000
1.000
Jan-1 Jan-31 Mar-2 Apr-1 May-1 May-31 Jun-30 Jul-30 Aug-29 Sep-28 Oct-28 Nov-27 Dec-27
24-hour Total Spore Counts
Figure 7-19. Chart of fungal spore prevalence in Kalamazoo, MI, for 1994.
Source:
Toxic agents produced by fungi include antibiotics, mycotoxins, and some cell-wall
components that have toxic or irritant properties. The antibiotics and mycotoxins are
secondary metabolites that are produced during fungal digestion of substrate materials, and
their presence depends, in part, on the nature of the substrate. The locations of the toxins in
spores or other mycelial fragments are unknown, as are the dynamics of release in the
respiratory tract. Aerosol exposure to fungal antibiotics in levels sufficient to cause disease
is unlikely. Mycotoxicoses have been reported as case studies from exposure to spores of
Stachybotrys atra (Croft et al., 1986), and epidemiologically for Aspergillus flavus (Baxter
etal., 1981).
7.2.5.4 Bacterial Aerosols
Bacteria, in contrast to plants, animals and fungi, contain neither nuclei or
mitochondria. Most are unicellular, although some form "pseudo" filaments when cells
remain attached following cell division. The actinomycetes are bacteria that do form
filaments and (in some cases) dry spores designed for aerosol dispersal. The bacteria can be
broadly categorized into two groups based on a response to the Gram stain procedure. The
cell walls of Gram positive bacteria are able to absorb a purple stain; the walls of Gram
7-78
-------
negative bacteria resist staining. The Gram negative cell wall contains endotoxin (see
above).
Most infectious agents are maintained in diseased hosts. A few, including Legionella
pneumophila, reside in water-filled environmental reservoirs such as water delivery systems,
cooling towers, air conditioners, and (outdoors) oceans, lakes, streams, etc.
Infectious agents are often released from hosts in droplets released from the respiratory
tract. Each droplet contains one or more of the infectious agent, probably one or more other
organisms, and respiratory secretions. Most droplets are very large and fall quickly.
Smaller droplets dry quick to droplet nuclei, which range in size from the size of the
individual organism (< 1 /zm for the smallest bacteria) to clumps of larger organisms
(> 10 /xm for larger bacteria). Environmental-source aerosols are produced by mechanical
disturbances that include wind, rain splash, wave action, and by mechanical disturbance such
as occurs in recirculation and sprays of washes and coolants, and in humidifiers. Particle
sizes from all of these activity cover a wide range from well below 1 /xm to >50 /an. The
thermophilic actinomycetes produce dry aerial spores that require only slight air movements
to stimulate release. Each spore is about 1 ^m in diameter.
Whole living bacteria are agents of infectious disease (e.g., Tuberculosis, Legionnaires'
disease). For tuberculosis, a single virulent bacterial cell deposited in the appropriate part of
the lung is likely to cause disease in a host without specific immunity. For Legionnaires'
disease, the number of organisms required to make disease development likely depends on
how well the host's general protective immune system is operating. Some bacteria release
antigens that cause hypersensitivity pneumonitis. The antigens may be enzymes (e.g.,
Bacillus subtilis enzymes used in the detergent industry) or may be cell wall components as
in the thermophilic actinomycetes. Bacteria also produce toxins of which endotoxin is the
most important from an aerosol exposure point of view.
7.2.5.5 Viral Aerosols
The viruses are units of either RNA or DNA surrounded by a protein coat. They have
no intrinsic mechanism for reproduction, and require living cells whose enzyme systems they
utilize to make new particles. They can be crystallized and remain able to reproduce, and
are often considered intermediates between non-life and life. Because viruses require living
7-79
-------
cells to reproduce, reservoirs for them are almost exclusively living organisms. Rarely,
viruses survive (but do not reproduce) in environmental reservoirs from which they are
re-aerosolized to cause disease. The Hanta virus that causes severe respiratory disease in
people exposed to intense aerosols of infected mouse urine is an example of this
phenomenon. Viral aerosols are produced when the infected organism coughs, sneezes, or
otherwise forces respiratory or other secretions into the air. The viral particles are coated
with secretions from the host, and, as for the bacteria, there may be one to many in a single
droplet. The size of a single viral particle is very small (a small fraction of a ^m).
However, infectious droplets are probably within a much larger size range (1 to 10 pm).
Each kind of virus produces a specific disease, although some of the diseases present with
similar symptoms. Thus, the measles virus produces measles, the chicken pox viruses
produces chicken pox and shingles. Influenza and common colds are produced by a range of
viruses all of which produce symptoms that are similar (but not necessarily identical).
7.2.5.6 Ambient and Indoor Air Concentrations of Bioaerosols
A general rough estimate of the contribution of bioaerosols to collected PM mass can
be made as follows: for an "average" 3 /jm spherical spore of 0.9 density, each spore would
weigh «13 x 10"6 jug; for a clean indoor environment with «103 spores/m3 the mass would
be on the order of 0.01 /*g/m3; for a typical outdoor condition, with « 50 x 103 spores/m3,
the contribution would be on the order of 0.5 pig/m3. In contaminated indoor environments,
where spore levels above 106 spores/m3 are possible, the spore weight could be on the order
of 10 pig/m3 or more.
In summary, the minor mass concentrations of bioaerosols in ambient and indoor air
are independent of the concentrations of the non-bioaerosol constituents in ambient and
indoor air. However, the deposition of bioaerosols at the same respiratory tract loci as the
other PM can cause irritation and infection foci that may make the affected host more
susceptible to the effects of other deposited PM.
7-80
-------
7.3 DIRECT METHODS OF MEASUREMENT OF HUMAN PM
EXPOSURE BY PERSONAL MONITORING
7.3.1 Personal Monitoring Artifacts
Human exposure to air pollution can be measured by placing a personal exposure
monitor (PEM) close to the breathing zone of an individual. However, the very act of
studying the subjects can alter their behavior, which influences the measured values of their
exposures and creates an erroneous reading. This influence, known as the "Hawthorne
Effect" (Mayo, 1960; Last, 1988), arises because the subjects are aware of the study
objectives, and the presence of the PEM on their body is a constant reminder.
The physical location of the monitor inlet, as worn by the subject, can also influence
the subject's PM exposure and the recorded PM (Cohen et al., 1982, 1984). The movements
of the subject's body and the PEM sampling flow rate can alter the air currents in the
subject's breathing zone. "The presence of the body and its movement affect what a
personal sampler collects" (Ogden et al., 1993). When in close proximity to a source
actively emitting PM (within a meter) a small change in PEM position (e.g. from left side to
right side) can vary the PM measurement. The vertical position of the personal monitor
sampling inlet (e.g., at the waist or at the lapel near the breathing zone), can influence the
captured amount of PM that is generated from the floor and stuffed furniture (Aso et al.,
1993).
In performance of a personal monitoring study, people often refuse to participate. The
refusal rate increases with the burden on the respondents due to the time required to
complete questionnaires, diaries and the need to carry the personal monitor with them
throughout the study. If the cohort of people who refuse to participate have significantly
different personal PM exposures than the participants, then the study will produce a biased
estimate of the exposures of the total population.
Two other important errors that influence the personal exposure measurements are:
(1) "the monitor effect", by which the monitor reduces PM concentration in the breathing
zone by "self dilution" (Cohen et al., 1984), the alteration of stream lines in the area of the
nose and mouth, or by electrostatic charge on a plastic cassette filter holder collecting
charged particles (Cohen et al., 1982); and (2) "the subject effect", by which the subject
7-81
-------
contaminates the data set by a purposeful action, such as blowing smoke into the inlet, or
forgetting to wear the monitor and not admitting that error in the log of daily activity.
These unquantifiable "errors" in a PM PEM measurement study may be greater than
the filter weighing errors and flow rate measurement errors that can be quality controlled
through calibration procedures. This may be important for interpretation of published
PM PEM data because these errors likely inflate the variance of the measurements.
7.3.2 Characterization of Particulate Matter Collected by Personal
Monitors
The amount of PM collected by different types of personal monitors with the identical
nominal cut-point can be variable. The difference between two PM measurements, made by
two nominally identical monitors of different design, can be a function of the wind speed and
the size distribution of the PM in the air mass being sampled. A recent field comparison by
Groves et al. (1994) of different types of respirable dust samplers used in occupational
settings where coarse mode PM predominates shows that there is considerable difference
between the mass collected by sets of paired cyclones and paired impactors sampling in a
concentration range of 500 to 6600 A*g/m3. The cyclones collected from 53 to 165% of the
mass collected by the impactors. This type of comparison study has not been done for
personal monitors used in nonoccupational studies at ambient and indoor respirable PM
concentrations on the order of 10 to 100 /ig/m3, where the fine mode can be more important.
7.3.3 Microscale Variation and the Personal Cloud Effect
The study of Thatcher and Layton (1995) described in Section 7.2.2.2 reports the
increase of indoor PM of various size ranges from household activities, such as walking into
and out of a room. The tendency for such human activity in the home or at work to generate
a "personal activity cloud" of particles from clothing and other items (stuffed furniture,
carpet, etc.), that will be intense in the breathing zone and diluted near an area monitor
located several meters away, has also been cited as a contributing factor to the discrepancy
between personal measures of exposure and time-weighted-average (TWA) exposures using
microenvironmental measurements (Martinelli et al., 1983; Cohen et al., 1984; Rodes et al.,
1991). Fletcher and Johnson (1988) also measured metal concentrations (measurement
7-82
-------
method and size unspecified) in an occupational exposure situation (metal spraying of
spindles on a lathe) and found 50% higher concentrations measured from the left lapel
compared to the right lapel, which reflected the orientation of the operator to the lathe.
7.4 NEW LITERATURE ON PARTICLE EXPOSURES SINCE 1981
The following sections review studies that measured PEM PM in the general non-
smoking population. In these studies, the subjects spent tune at home and in other indoor
environments that include time at work. In the USA, recent data indicate that on a daily
basis, an average US resident spends approximately 21 h indoors (85.6%), 100 minutes in
(or near) a vehicle (7.2%), and 100 minutes outdoors (7.2%) (U.S. Environmental Protection
Agency, 1989).
Almost all the studies of PM exposure in the general public have been conducted on
urban and suburban residents. These subjects are often working in occupations that do not
require PM monitoring to assure that occupational standards are being met (e.g. in an
office). However, PM monitoring in an industrial workplace by a subject - independently of
an official corporate industrial hygiene program - can have legal or security implications for
an employer. A further complication arises from the fact that industrial exposures tend to be
dominated by a specific type of particle. Coal miners are exposed to coal dust, textile
workers are exposed to cotton dust, etc.
7.4.1 Personal Exposures in U.S. Studies
Dockery and Spengler (1981b) compared personal PM3 5 exposures and ambient PM3 5
concentrations in Watertown, MA, and in Steubenville, OH. In Watertown, 24-h personal
samples were collected on a 1-in 6-day schedule, and in Steubenville, 12-h personal samples
(8 a.m. to 8 p.m.) were collected on a Monday-Wednesday-Friday schedule. A correlation
coefficient of 0.692 between the mean personal and the mean ambient concentration for
37 subjects, 18 in Watertown and 19 in Steubenville, was reported for the pooled data.
However, this appears to be an artifact of two separate clusters formed by these data, each
with considerably lower correlation. When these data are analyzed separately, the regression
7-83
-------
coefficient between personal and ambient for Watertown is R2 = 0.00 and for Steubenville it
isR2 = 0.18.
Sexton et al. (1984) studied personal exposures to respirable particles (PM3 5) for
48 nonsmokers during a winter period in Waterbury, VT, where firewood was either the
primary or secondary heating source for the subject. Their results showed that personal
exposures were 45 % higher than indoor averages (36 /*g/m3 versus 25 /*g/m3) and indoor
averages were 45% higher than outdoor averages (25 /xg/m3 versus 17 /*g/m3). Ambient air
pollution, measured by an identical stationary ambient monitor (SAM) outside each residence
(a pump contained in a heated box was connected to an external cyclone and filter), had no
correlation with the residents' personal exposures (R2 = 0.00) and 95% of the subjects had
personal exposures greater than the median outdoor concentration.
Spengler et al. (1985) reported a study of PM3 5 exposures in the non-industrial cities of
Kingston and Harriman, TN, during the winter months of February through March, 1981.
In this study, two Harvard/EPRI PM3 5 monitors were used for each person. One stationary
indoor monitor (SIM) remained indoors in the home, and the second monitor (PEM) was
carried for 24-h to obtain the personal exposure. In each community, identical
Harvard/EPRI samplers (SAM) were placed at a central site to represent ambient PM3 5
concentrations. The results of the study are shown in Table 7-19. In both communities,
95% of the subjects had personal exposures to PM3 5 greater than the average ambient
concentrations. The mean personal exposure and indoor concentrations (44 + 3 /ug/m3 and
42 + 3 /ig/m3) were more than 100% greater than the mean ambient average of
18 + 2 fjigfm3 sampled on the same days.
For the complete cohort, the correlation between PM PEM and PM SAM was r = 0.07
(p = 0.30), and between PM PEM and PM SIM was r = 0.70 (p = 0.0001). The
correlation between simultaneous PM PEM and PM SAM was r = 0.15 for 162 nonsmoke
exposed individual observations (p = 0.06). For 63 observations on smoke exposed
individuals, the correlation r = 0.16 was not significant (p = 0.16) between PM PEM and
PM SAM. An important finding was that in nonsmoking households, the PM PEM is always
higher than SIM and SAM. "This implies that individuals encounter elevated concentrations
away from home and/or that home concentrations are elevated while they are at home and
reduced while they are away". This observation is supported by the findings of Thatcher and
7-84
-------
TABLE 7-19. QUANTILE DESCRIPTION OF PERSONAL, INDOOR,
AND OUTDOOR PM3S CONCENTRATIONS Gig/m3),
BY LOCATION IN TWO TENNESSEE COMMUNITIES
City
Kingston
Harriman
Total3
Group
Personal
Indoor
Outdoor
Personal
Indoor
Outdoor
Personal
Indoor
Outdoor
N
133
138
40
93
106
21
249
266
71
"Includes samples from 13 subjects living
personnel residing in these communities.
N = number of samples.
S.E. = Standard error.
95%
99
110
28
122
129
34
113
119
33
outside
75%
47
47
22
54
45
23
48
46
23
Kingston and
50%
34
31
16
35
27
15
34
29
17
Harriman
25%
26
20
12
24
18
13
26
20
13
town limits
5%
19
10
6
15
10
9
17
10
7
and from
Mean
42
42
17
47
42
18
44
42
18
S.
2.
3.
2.
4.
4.
4.
2.
2.
2.
E.
5
5
7
8
1
0
8
6
1
four field
Source: Spengler et al. (1985).
Layton (1995), reported in Section 7.2.2.2: merely walking into a room can raise the
concentrations of PM by 100%. This study is relevant to the analyses by Dockery et al.
(1992) of PM mortality in St. Louis, MO, and in Eastern Tennessee counties surrounding
Kingston and Harriman as discussed in Chapter 12. Although the Spengler et al. (1985) and
Dockery et al. (1992) studies are not directly comparable, because different years of data
were used (1981 versus 1985/1986), the authors' assumption in Dockery et al. (1992) that
the Harriman, TN, data represent exposures to PM in all of eastern Tennessee is called into
question.
Morandi et al. (1988) investigated the relationship between personal exposures to PM
and indoor and outdoor PM concentrations, using a TSI Model 3500 piezobalance that
measures respirable particles in the range <3.5 /mi. For the group of 30 asthmatics in
Houston, TX, that were studied, outdoor concentrations averaged 22 /xg/m3, indoor
concentrations averaged 22% higher than outdoor (27 /ig/m3) and, in motor vehicles, the
average concentration of particles was 60% higher than the average outdoors (35/xg/m3).
7-85
-------
Personal 12-h (7 a.m. to 7 p.m.) daytime exposures to PM were not predicted as well by
fixed site dichotomous sampler ambient monitors (R2 = 0.34) as by the indoor exposures
(R2 = 0.57). However, for 1-h exposures, they found no correlation (R2 = 0.00) between
the personal exposures to PM5 and the indoor exposures measured with a TSI model 5000
stationary continuous piezobalance located in the "den" area of the home. The authors noted
that use of home air conditioning and recirculation tended to increase the PM exposures.
Lioy et al. (1990) reported a study done during the winter (January 1988) in the
industrial community of Phillipsburg, NJ, where personal PM10 was monitored along with
indoor and outdoor PM10. They collected PM10 (fine plus coarse particles on a single filter).
In this study of eight residences of 14 nonsmoking individuals not smoke exposed at home,
geometric mean 24-h concentrations were 68, 48 and 42 /ig/m3 for personal, outdoor and
indoor sites, respectively. The arithmetic mean personal PM exposure of 86 /xg/m3 was 45%
higher than the mean ambient concentration of 60 /*g/m3. The higher ambient than indoor
concentrations in this study, a reversal of the relationships found in the Sexton et al. (1984),
Spengler et al. (1985) and Morandi et al. (1988) studies, may be caused by the local
industrial source of coarse particles in that community and the absence of cigarette smokers
in the residences sampled. This difference also may be partially explained by the 10 /xm
particle sizes sampled in the NJ study and the 3.5 /mi particle sizes in the other studies. The
regression coefficient between personal and ambient PM10 for all 14 people on the 14 days of
the study (n = 191 valid personal values) was 0.19 (R2 = 0.037, p = 0.008). With three
personal exposure extreme values removed (n = 188 personal values) and without correction
for missing data, the coefficient was 0.50 (R2 = 0.25, p = 0.007).
Lioy et al. (1990) report individual regression equations of PEM and SAM for the six
of 14 subjects with significant relationships (p < 0.01). These data are shown in
Table 7-20. For individuals with constant daily activities in the same microenvironments, the
increment of PM exposure due to nonambient sources is repeatable with lower variability
than that of the ambient PM. Therefore their variation of personal exposure from day-to-day
is highly driven by the variation of the ambient PM. For subjects with intermittent
exposures to nonambient PM, through non-repetitive activity patterns or intermittent source
operation, the regression of PEM on SAM can become non-significant. This improvement in
7-86
-------
TABLE 7-20. REGRESSION EQUATION OF THOSE INDIVIDUALS
HAVING STATISTICALLY SIGNIFICANT RELATIONSHIPS OF
EXPOSURE (PEM) WITH OUTDOOR AIR CONCENTRATIONS (SAM)
Participant
01
31
52
62
81
91
y
y
y
y
y
y
= 0.62
= 0.55
= 0.63
= 1.29
= 1.07
= 0.59
Equation
(0.12)
(0.07)
(0.11)
(0.27)
(0.24)
(0.12)
X +
X +
X +
X +
X +
X +
26.5 (17.
7.3 (9.9)
15.3 (14.
33.0 (37.
39.0 (32.
42.0 (19.
3)
7)
1)
6)
9)
R2
0
0
0
0
0
0
.66
.83
.74
.67
.63
.63
N
14
14
14
13
14
13
P
< 0
< 0
< 0
< 0
< 0
< 0
.01
.01
.01
.01
.01
.01
y = Personal air PM-10.
X = Outdoor air PM-10.
() = Confidence interval.
Source: Lioy et al. (1990).
correlation was also shown for their indoor versus outdoor relationships, between cross-
sectional and individual comparisons, as described in Section 7.4.2.3.
In all these studies, the personal PM was measured to be higher than either the indoor
or the outdoor PM measurements. This relationship of PEM > SIM and PEM > SAM has
also been found in the PTEAM study (Clayton et al., 1993) described in detail in
Section 7.2.2.1.3 and later in Section 7.4.1.1. For the PTEAM study during the day
(7 a.m. to 7 p.m.) average personal PM10 exposure data (150 Mg/m3) were 57% higher than
the average indoor and outdoor concentrations, which were virtually equal (95 /xg/m3).
Consequently, a tune-weighted-average (TWA) of the daytime indoor and outdoor PM
concentrations appears to always underestimate the personal exposures to PM because the
daytime PEM data are higher than either the SIM or SAM data. At night (7 p.m. to 7 a.m.)
average PM10 personal exposures (77 jig/m3) were higher than the average indoor
concentrations (63 /-ig/m3) but lower than the average outdoor concentration (86 /*g/m3).
It has been proposed (World Health Organization, 1982a; Spengler et al., 1985; Mage,
1985) that such a discrepancy between the TWA and the personal monitoring measurements
may be caused by two factors described as follows: (1) human exposure to PM at work and
in traffic are only partially accounted for in a TWA of indoor and outdoor ambient PM
7-87
-------
values; and (2) indoor and outdoor averages reflect periods of low concentration during
which the subject is not present. The PM pollution generating activities in a home usually
occur only when a person is at home, as discussed in Section 7.1.2 concerning Equation 7-2.
Therefore, the PM in a home will be higher when a person is present than when the home is
unoccupied. A 24-h average of the indoor concentration thereby underestimates the average
exposure of a person while in that home.
Ambient PM is also higher during the day (when industry and traffic are active, and
wind speeds are high) than at night when PM generating activities are at a minimum and the
air is still (Miller and Thompson, 1970). Consequently, a 24-h average ambient PM value
generally underpredicts the concentrations during the daylight hours and the exposures of
people going outdoors during that period.
7.4.1.1 The Particle Total Exposure Assessment Methodology Study
In 1986, the U. S. Congress mandated that EPA's Office of Research and Development
"carry out a TEAM Study of human exposure to particles." The main goal of the study was
to estimate the frequency distribution of exposures to particles for nonsmoking Riverside,
CA, residents. Another goal was to determine particle concentrations in the participants'
homes and immediately outside the homes. The detailed analyses of the indoor PM and
outdoor PM data were described in Section 7.2.2.1.3.
7.4.1.1.1 Pilot Study
Study Design
A prepilot study, described in Section 7.2.2.1.3, was undertaken in nine homes in
Azusa, CA in March of 1989 to test the sampling equipment (Ozkaynak et al., 1990).
Newly-designed personal exposure monitors (PEMs) were equipped with thoracic (PM10) and
fine (PM2 5) particle inlets. The PEMs were impactors with 4-Lpm Casella pumps (Wiener,
1988). Two persons in each household wore the PEMs for two consecutive 12-h periods
(night and day). Each day they alternated inlet nozzles. A central site with a PEM, a
microenvironmental monitor (MEM), and two EPA reference methods (dichotomous and
high-volume samplers) with a 10 /xm size-selective inlet was also operated throughout the
11 days (22 12-h periods) of the study.
7-i
-------
Results
The personal exposure levels were about twice as great as the indoor or outdoor
concentrations for both PM10 (Table 7-21a) and PM2 5 (Table 7-21b). Considerable effort
was expended to demonstrate that this was not a sampling artifact, due for example to the
constant motion of the sampler; however, no evidence could be found for an artifactual
effect. Nonetheless, to reduce chances for an artifactual finding in the main study, it was
decided to use identical PEMs for both the personal and fixed (indoor and outdoor) samples
in the main study. Cross-sectional personal exposures were essentially uncorrelated (slightly
negatively) with outdoor concentrations (R2 = 0 to 2%) (Ozkaynak et al., 1993a). However,
a serial correlation analysis of these pilot PTEAM data were performed for the six or eight
12-h averages that comprised the three or four 24-h averages reported for the residents of the
first five homes in Table 7-21a,b. The residents of four homes only carried the PEM for
two days, so the four 12-h individual measurements were too few for development of a
meaningful serial relationship. The results for the ten people in homes 1 to 5 are shown in
Table 7-22. The medians of R2 equal 0.12 for PEM PM2 5 vs SAM PM2 5 and 0.07 for
PEM PM10 vs SAM PM10, neither of which is significant. More importantly, the serial
slopes were positive for 15 of the 20 cases which is the expected behavior, as opposed to the
counter-intuitive negative correlation found for the pooled PEM vs SAM data for all
residents of the nine homes.
In Azusa, the excess PM2 5 and PM10 generated by personal activities increased the
personal exposures by approximately 100% above the average of the indoor and outdoor
values. These results are in marked contrast to the data of Tamura and Ando (1994) and
Tamura et al. (1996) in which seven Japanese elderly housewives and male retirees had PM10
PEM exposures less than the time weighted average of SIM and SAM PM10 concentrations.
7.4.1.1.2 Main Study
Study Design
Ultimately 178 residents of Riverside, CA took part in the study in the fall of 1990.
Respondents represented 139,000 ± 16,000 (S.E.) nonsmoking Riverside residents aged
10 and above. Their homes represented about 60,000 Riverside homes. Each participant
wore the PEM for two consecutive 12-h periods. Concurrent PM10 and PM2 5 samples were
7-89
-------
TABLE 7-21a. PARTICLE TOTAL EXPOSURE ASSESSMENT METHODOLOGY
PREPILOT STUDY: 24-HOUR PM10 CONCENTRATIONS (/tg/m3)
House
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
5
5
5
6
6
7
7
8
8
9
9
Mean
SD
SE
Day
1
3
5
7
1
3
5
7
1
3
5
7
2
4
6
2
4
6
8
10
9
11
9
11
8
10
Person 1 Person 2
102
142
158
92
109
99
131
62
98
100
143
76
109
90
99
80
70
80
130
150
209
80
135
97
136
273
117.2
44.9
8.8
86
125
150
127
158
140
87
56
107
141
132
103
92
77
122
104
77
78
152
102
126
71
178
151
102
91
112.9
30.8
6.0
Indoors
54
38
49
34
122
37
41
32
86
39
71
36
77
34
36
76
62
54
114
106
46
29
73
38
63
121
60.3
28.5
5.6
Outdoors
132
49
70
49
112
48
70
46
115
45
79
44
102
47
37
99
65
50
39
51
72
39
59
28
43
48
63.0
27.1
5.3
Source: Data from PTEAM Prepilot Study used to calculate R2 values as shown in Table 7-22 and published by
Wallace (1996).
7-90
-------
TABLE 7-21b. PARTICLE TOTAL EXPOSURE ASSESSMENT METHODOLOGY
PREPILOT STUDY: 24-H PM2 5 CONCENTRATIONS (jtg/m3)
House
1
1
1
2
2
2
3
3
3
4
4
4
4
5
5
5
5
6
6
7
7
8
8
9
9
Mean
SD
SE
Day
2
4
6
2
4
6
2
4
6
1
3
5
7
1
3
5
7
9
11
8
10
8
10
9
11
Person 1
44
55
55
58
46
51
53
62
109
75
46
118
40
65
59
40
34
71
77
64
111
53
110
178
105
71.2
32.7
6.5
Person 2
96
88
382
53
100
50
66
94
88
61
43
94
40
69
70
56
53
81
75
135
67
100
1453*
48
58
140.8*
275.5
55.1
Indoors
22
25
21
31
27
28
48
30
39
33
19
31
17
62
35
42
25
56
53
17
32
27
35
70
42
34.7
13.7
2.7
Outdoors
67
39
33
52
43
40
58
35
39
71
29
46
26
96
38
55
28
33
18
27
35
27
35
40
28
41.6
16.8
3.4
* Horseback riding at an indoor ring. If this point is deleted, mean = 86.1.
Source: Data from PTEAM Prepilot Study used to calculate R2 values as shown in Table 7-22 and published by
Wallace (1996).
7-91
-------
TABLE 7-22. REGRESSIONS OF PERSONAL EXPOSURE ON INDOOR AND
OUTDOOR PM10 AND PM2 5 CONCENTRATIONS: PARTICULE TOTAL
EXPOSURE ASSESSMENT METHODOLOGY PREPILOT STUDY
House
PM10:
1
2
3
4
5
PM2.5:
1
2
3
4
5
Person
Personal vs.
1
2
1
2
1
2
1
2
1
2
Personal vs.
1
2
1
2
1
2
1
2
1
2
N
Intercept
SE
P
Slope
SE
P
R2
Outdoor
8
8
8
8
8
8
6
6
6
6
124
134
47
26
83
116
87
106
47
22
42
60
44
52
47
54
20
28
31
26
0.03
NS
NS
NS
NS
NS
0.01
0.02
NS
NS
-0.0004
-0.16
0.77
1.22
0.3
0.07
0.2
-0.15
0.42
0.9
0.51
0.73
0.58
0.68
0.61
0.7
0.29
0.4
0.41
0.35
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
0
0.01
0.23
0.35
0.04
0.002
0.1
0.03
0.2
0.63
Outdoor
6
6
6
6
6
6
8
8
8
8
41
274
8.8
47
87
40
40
45
27
46
20
266
20
34
58
54
24
22
15
16
NS
NS
NS
NS
NS
NS
NS
NS
NS
0.03
0.22
-1.8
0.96
0.47
-0.29
0.97
0.7
0.34
0.42
0.3
0.4
5.3
0.41
0.7
1.25
1.2
0.48
0.45
0.24
0.27
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
0.07
0.03
0.58
0.1
0.01
0.15
0.26
0.09
0.34
0.17
NS = not significant (p > 0.05).
N = Number of 12-h observations.
Source: Wallace (1996).
collected by the stationary indoor monitor (SIM) and stationary ambient monitor (SAM) at
each home. A total of ten particle samples were collected for each household (day and night
samples from the PEM10, SIM10, SIM2 5, SAM10, and SAM2 5). Air exchange rates were
also determined for each 12-h period. Participants were asked to note activities that might
involve exposures to increased particle levels. Following each of the two 12-h monitoring
7-92
-------
periods, they answered an interviewer-administered questionnaire concerning their activities
and locations during that time. A central outdoor site was maintained over the entire period
(September 22, 1990 through November 9, 1990). The site had two high-volume samplers
(Wedding & Assoc.) with 10-jum inlets (actual cutpoint about 9.0 jum), two dichotomous
PM10 and PM2 5 samplers (Sierra-Andersen) (actual cutpoint about 9.5 pm), one PEM, one
PM10 SAM, and one PM2 5 SAM.
Results
Of 632 permanent residences contacted, 443 (70%) completed the screening interview.
Of these, 257 were asked to participate and 178 (69%) agreed.
Quality of the Data
More than 2,750 particle samples were collected, about 96% of those attempted. All
filters were analyzed by X-ray fluorescence (XRF) for a suite of 40 metals. More than
1,000 12-h average air exchange rate measurements were made. A complete discussion of
the quality of the data is found in Pellizzari et al. (1993) and in Thomas et al. (1993).
Concentrations
Concentrations of particles and target elements have been reported (Clayton et al.,
1993; Ozkaynak et al., 1993a; Pellizzari et al., 1993; Wallace et al., 1993). Population-
weighted daytime personal PM10 concentrations averaged about 150 ^g/m3, compared to
concurrent indoor and outdoor mean concentrations of about 95 /ig/m3 (Table 7-23). The
overnight personal PM10 mean was much lower (77 /xg/m3) and more similar to the indoor
(63 /itg/m3) and outdoor (86 jug/m3) means. About 25% of the population was estimated to
have exceeded the 24-h National Ambient Air Quality Standard for PM10 of 150 /xg/m3.
Over 90% of the population exceeded the 24-h California Ambient Air Quality Standard of
50 /ig/m3.
Correlations
The central site appeared to be a moderately good estimator of outdoor particle
concentrations throughout the city. Spearman correlations of the central-site concentrations
7-93
-------
TABLE 7-23. POPULATION-WEIGHTED8 CONCENTRATIONS AND
STANDARD ERRORS (/ig/m3) PTEAM STUDY
Sample type
Daytime PM10
Personal
Indoor
Outdoor
Overnight PM10
Personal
Indoor
Outdoor
Daytime PM2 5
Indoor
Outdoor
Overnight PM2 5
Indoor
Outdoor
N
171
169
165
168
163
162
173
167
166
161
Geom.
Mean
129
78
83
68
53
74
35
38
27
37
GSD
1.75
1.88
1.68
1.64
1.78
1.74
2.25
2.07
2.21
2.23
Arith.
Mean ± SE
150 ± 9
95 ± 6
94 + 6
77 ± 4
63 ± 3
87 ± 4
48 ± 4
49 ± 3
36 ± 2
51 ±4
Percentile
90% ± SE
260 ± 12
180 ± 11
160 ± 7
140 ± 10
120 ± 5
170 ± 5
100 ± 7
100 ± 6
83 ± 6
120 ± 5
98%
380
240
240
190
160
210
170
170
120
160
aPersonal samples weighted to represent nonsmoking population of 139,000 Riverside residents aged 10 or
above. Indoor-outdoor samples weighted to represent 61,500 homes with at least one nonsmoker aged 10 or
above.
Source: Pellizzari et al. (1993).
measured by all three methods (PEM-SAM, dichot, Wedding) with outdoor near-home
concentrations as measured by the SAMs ranged from 0.8 to 0.85 (p< 0.00001). Linear
regressions indicated that the central-site 12-h readings could explain 57% of the variance
observed in the near-home 12-h outdoor concentrations (Figure 7-20).
Outdoor 12-h concentrations of PM10 could explain about 25 to 30% of the variance
observed in indoor concentrations of PM10, but only about 16% of the variance in 12-h
personal exposures to PM10 (Figure 7-21). This is understandable in view of the importance
of indoor activities such as smoking, cooking, dusting, and vacuuming on exposures to
7-94
-------
600
500
o 400
o
E 300
CO
"t 20°
< 100
0
Backyard = 1.03*Central + 17.6
R2 - 0.57 N - 323
50 100 150 200
Central site reference monitor mean (ug/m3)
250
Figure 7-20. Residential outdoor monitors versus central-site mean of two dichotomous
samplers in Riverside, CA. R2 = 57%.
Source of Data: Pellizzari et al. (1993).
500
400
w
8> 300
V)
§.
CO
o
200
100
0
Pers = 0.54*Out + 62
R2- 16% N - 312
u°
100 200 300 400
Backyard concentrations
500
600
Figure 7-21. Personal exposures versus residential (back yard) outdoor PM10
concentrations in Riverside, CA. R2 = 16%.
Source of Data: Pellizzari et al. (1993).
7-95
-------
particles. The higher daytime exposures were even less well represented by the outdoor
concentrations.
Indoor concentrations accounted for about half of the variance in personal exposures.
However, neither the indoor concentrations alone, nor the outdoor concentrations alone, nor
time-weighted averages of indoor and outdoor concentrations could do more than explain
about two-thirds of the observed variance in personal exposures. The remaining portion of
personal exposure is assumed to arise from personal activities or unmeasured
microenvironments that are not well represented by fixed indoor or outdoor monitors.
Discussion
The more than 50% increase in daytime personal exposures compared to concurrent
indoor or outdoor concentrations suggested that personal activities were important
determinants of exposure. However, the nature of this "personal cloud" of particles has not
yet been determined. An approach to the composition of the personal cloud is elemental
analysis, using X-ray fluorescence. Analysis of all personal and indoor filters showed that
14 of 15 elements were elevated by values of 50 to 100% in the personal filters compared to
the indoor filters (Figure 7-22). This observation suggests that a component of the personal
cloud is an aerosol of the same general composition as the indoor aerosol. This could be
particles created by activities (e.g., cooking) or re-entrained household dust from motion
(walking across carpets or sitting on upholstered furniture; Thatcher and Layton, 1995).
House dust is a mixture of airborne outdoor PM (primarily coarse mode), tracked-in soil and
road dust, and PM produced by indoor sources. As such, it should contain crustal elements
from soil, lead and bromine from automobiles, and other elements from combustion sources.
This would be consistent with the observation that nearly all elements were elevated in
personal samples. The lack of elevated values for sulfur may be due to the fact that
submicron particles are not resuspended by human activity (Thatcher and Layton, 1995).
The personal overnight samples that showed smaller mass increases than the personal
daytime samples are also consistent with the fact that the participants were sleeping for much
of the 12-h overnight monitoring period and were thus not engaging in these particle-
generating or reentraining activities.
7-96
-------
40 60 80 100
Percent increase in personal cloud
120
Figure 7-22. Increased concentrations of elements in the personal versus the indoor
samples.
Source: Ozkaynak et al. (1996).
A source apportionment of the personal PM10 mass during the daytime period is shown
on Figure 7-23 (Ozkaynak et al., 1996). This chart is derived by subtracting the average
SIM and SAM (95 /xg/m3) from the mean PEM (150 /*g/m3) given on Table 7-23. The
55 jttg/m3 difference is shown as the 37% fraction of the total of 150 /tg/m3 labelled Personal
37%. The source of this "personal cloud" is indeterminable from the SIM, SAM and PEM
data. As discussed previously, it is likely to consist primarily of resuspended dust that would
have a composition of a mixture of all the other sources. The 15% other-indoor PM
represents the indoor mass that could not be assigned to ETS, cooking or ambient PM. It is
likely that the 52% of other-indoor plus personal-cloud categories contains an appreciable
amount of ambient PM that came indoors over a long period of time and is resuspended by
activity. If so, then the PEM would be about 50% of ambient origin.
7.4.2 Personal Exposures in International Studies
As part of World Health Organization/United Nations Environment Programme
(WHO/UNEP) Global Environment Monitoring System (GEMS) activities, four pilot studies
7-97
-------
Outdoor
42%
Personal
37%
Smoking
3%
N- 166 Samples
Cooking
3%
Other Indoor
15%
Figure 7-23. Source apportionment of PTEAM PM10 Personal Monitoring (PEM) Data.
"Other Indoor" represents PM found by the indoor monitor (SIM), for
which the source is unknown. "Personal" represents the excess PM
captured by the PEM that cannot be attributed to either indoor (SIM) or
outdoor (SAM).
Source: Clayton et al. (1993).
of personal exposure to PM were conducted in: Zagreb (World Health Organization, 1982a);
Toronto (World Health Organization, 1982b); Bombay (World Health Organization, 1984);
and Beijing (World Health Organization, 1985). In these studies, people who worked in the
participating scientific institutes were recruited to carry a PM sampler, and their exposures
were matched to the ambient concentrations measured outside their home or at a central
station in their communities. The results of these studies, expressed as mean personal
exposure (PEM) and mean ambient (SAM) concentration, and the cross-sectional regression
R2 between them are presented in Table 7-24.
The net result of these four international studies is that they appear to confirm the lack
of a consistent cross-sectional relationship between individual personal PM exposures and
ambient concentrations as found in the U.S. studies described in Section 7.4.1.
7-98
-------
TABLE 7-24. SUMMARY OF WHO/UNEP GLOBAL ENVIRONMENT
MONITORING SYSTEM/PERSONAL EXPOSURE PILOT STUDY RESULTS
Location
Season
Toronto
Winter
Summer
Zagreb
Summer
Winter
Bombay
Winter
Summer
monsoon
Beijing
Winter
Summer
PM Size
Cut (pan) N m
25* 13
72
78
5 12
12
12
3.5 15
105
102
101
3.5 20
71
40
PEM
Time Mean ± SE
8-h
1-wk
24-h
24-h
1-wk
122 ±9
124 ±4
114±?
187 ±?
127 ±6
67±3
58±3
177±?
66±?
SAM
Mean ± SE
68 ±9
78 ±4
55±?
193 ±?
117±5
65 ±3
51±2
421 ±?
192±?
R2PEM
vs. SAM
0.15
0.10
0.00
0.50
0.26
0.20
0.02
0.07
0.03
P
NS
NS
NS
NR
NR
NR
NS
NS
NS
N = number of subjects carrying personal exposure monitor (PEM).
m = total number of observations.
PEM = mean ± SD of PM concentrations (in /ig/m3) from personal exposure monitors.
SAM = mean ± SD of PM concentrations (in ng/m3) from stationary ambient monitors.
NR = Not Reported, but listed as significant.
NS = Not significantly different from 0.
? = Not Reported.
*25 jj.m AD computed from flow rate and open filter design.
Source: World Health Organization (1982a,b, 1984, 1985).
7.4.2.1 Personal Exposures in Tokyo (Itabashi Ward), Japan
Tamura and Ando (1994), National Institute for Environmental Studies (1994) and
Tamura et al. (1996) report results of a PM personal monitoring study conducted during
1992 in Tokyo. Seven elderly non-smoke exposed individuals who lived in traditional
Japanese homes with "tatami" reed mat or carpeting on tatami or wooden flooring, and
cooked with city gas, carried a PEM cascade impactor with cut-points of 2 /mi and 10 /xm
(Sibata Science Technology, Ltd.). The seven individuals lived near the Itabashi monitoring
station close to a main road. Indoor PM (SIM) and outdoor PM (SAM) were measured
simultaneously for 11 48-h periods distributed in all four seasons of the year. The dataset
was screened to remove observations that included indoor combustion source exposures, such
as ETS from visitors, and burning of incense or mosquito coils. The reported findings were
as follows:
7-99
-------
1. The cross sectional correlation coefficient of SIM vs SAM was "relatively high"
(r2 = 0.72), but the individual coefficients for each house were higher as shown in
Figure 7-24.
2. The cross sectional correlation coefficient of PEM vs SAM (measured under the
eaves of the subject's house) was "relatively high" (r2 = 0.70), but the individual
coefficients for most of the subjects were higher as shown in Table 7-25.
3. The cross sectional correlation coefficient of PEM vs PM measured at the Itabashi
monitoring station was slightly lower than that for the outside air (r2 = 0.68), as
shown in Figure 7-25, and the individual coefficients for most of the subjects were
higher as shown in Table 7-25.
4. The individual SAM values were all linearly related with the central monitor at the
Itabashi station with the coefficient of regression (R2) in the range between 0.70 and
0.94.
5. The individual PEM values varied from 30% to 50% of the SAM values. These
{PEM < SAM} data are quite different from the US data sets, such as PTEAM,
where {PEM > SAM}, because they were designed to measure the influence of the
outdoors on personal exposures. The difference may be due to the exclusion of
ETS exposure and incense/mosquito coil burning and the Japanese customs of using
reed mat (tatami) flooring and taking shoes off when entering a home. These
factors would all tend to reduce the generation and resuspension of PM in the home.
Tamura and Ando (1994) and Tamura et al. (1996) confirm the findings of Thatcher
and Layton (1995) that PM < 5 jrni AD has negligible resuspension in homes.
Their SIM PM2 and SIM (PM10 - PM2) were highly correlated with the SAM of
identical size (r = 0.879 and 0.839 respectively) but there was a negative
correlation between the SIM and SAM (TSP - PM10) fraction (r = - 0.036).
The importance of this study is that it demonstrates that there are very strong
correlations between PEM and SAM (0.747 < r < 0.964) when the masking influences of
indoor combustion sources are removed and resuspension of PM is minimized. This
provides strong support to the use of an ambient monitoring station to represent the exposure
of people in the community to PM of ambient origin.
7.4.2.2 Personal Exposures in the Netherlands
Janssen et al. (1995) preliminarily reported in an abstract results of personal PM
monitoring conducted during 1994 in Amsterdam and Wageningen, NL as part of a doctoral
study. Participants were 13 non-smoking adults (age 50 to 70) in Amsterdam (urban) with
7-100
-------
12U-
110-
100-
— 90-
™E 80-
|70-
§50-
140-
30-
20-
10-
Q
E
a •
a a
o c%
BB° "
Ift'tf1 B r- 0.922
™B Winter r- 0.920
Summer r - 0.961
\iiitiiii
40
80
120
160
40
80
120
160
40
80
120
160
Outdoor (iig/m3)
200
izu —
110-
100-
"i?
•5™
J 50-
1 40-
30-
20-
10-
F
a a
QB
B
mm •*
g g
0 0™ ™
JlB1 r - 0.897
tf Winter r - 0.702
Summer r - 0.970
\i\\\\\\\
200
1
-------
TABLE 7-25. SUMMARY OF CORRELATIONS BETWEEN PM10 PERSONAL
EXPOSURES OF 7 TOKYO RESIDENTS AND THE PM10 MEASURED OUTDOORS
UNDER THE EAVES OF THEIR HOMES, AND THE PM MEASURED AT THE
ITABASHI MONITORING STATION
Subject ID
A
B
C
D
E
F
G
A-G
Number of Samples
48-h PM10
9
9
11
9
10
7
9
64
Correlation between
Personal and Outdoor at
home (r)
0.958
0.874
0.846
0.922
0.960
0.776
0.961
0.834
Correlation between
Personal and Itabashi
Station (r)
0.876
0.747
0.848
0.964
0.925
0.801
0.952
0.830
Source: Tamura et al. (1996).
140-
130-
120-
«•£ 110-
5100-
¥ 90-
o 80^
I
60-
o
2 40-
O 30-
20-
10- ""
0^
0
n
B
y - 1.07 x - 0.4 (R = 0.901)
n
y = 0.46 x
I f I T \ 1 \ I \ Y
20 40 60 80 100
0.825)
120
Itabashi Monitoring Station (ng/m3 )
140
Figure 7-25. Correlations between PM10 at the Itabashi monitoring station and PM10 in
outdoor and personal exposure (D= outdoor; + = personal).
Source: Tamura and Ando (1994); Tamura et al. (1996).
7-102
-------
no occupational exposure to PM, and 15 children (age 10 to 12) in Wageningen (rural) who
are presumably non-smokers. Four to eight measurements were obtained for each subject
which allowed for correlating PEM and SAM within individuals (longitudinally). Only the
median individual regressions were reported, as follows: adults, PEM = 26 + 0.70 SAM,
R = 0.57, R2 = 0.32; and children, PEM = 78 + 0.43 SAM, R = 0.67, R2 = 0.44. For
the children, parental smoking explained 35% of the variance between PEM and SAM. For
the adults, "living near a busy road", time spent in traffic, and exposure to ETS explained
75% of the variance between PEM and SAM. The authors interpreted their preliminary
results to "suggest a reasonably high correlation between personal and ambient PMIQ within
individuals". Janssen et al. (1995) also note that the low correlations observed in most of the
other studies reported in the literature were cross-sectional (calculated on a group level), and
were therefore mostly determined by the variation between subjects (e.g., ETS exposed and
non-ETS exposed subjects combined in the same regression).
7.4.2.3 Reanalysis of Phillipsburg, NJ Data
With insight from the Jansen work, Wallace (1996) reanalyzed the complete Lioy et al.
(1990) data from Phillipsburg, NJ, as shown partially in Table 7-20 (see also Table 7-37).
Wallace (1996) compared the cross-sectional regressions of PEM on SAM for all the
14 subjects on each of the 14 days sampled, to the longitudinal regressions of each of the
14 subjects on all 14 days sampled. He found that the median R2 (range) of the
14 individual (longitudinal) regressions was 0.46 (0.02 to 0.82); and that for the 14 daily
(cross-sectional) regressions was 0.06 (0.00 to 0.39). The difference appears to indicate
that, although one household may have a smoker and another not, the relationship of the
indoor air in each home to the outdoor air may be the same from day to day
(i.e., consistently higher than ambient in the first case, but may be consistently similar in the
second). Because it provides a linkage between PEM and SAM, it bears reiteration to make
certain that it is clearly understood. This PEM vs SAM relationship can be visually
demonstrated with the following hypothetical example as shown on Figure 7-26a,b.
• Let two people live next door to each other at a location where the ambient
PM for 5 consecutive days has a sequence {1, 2, 3, 4, 5}.
• Let person A live without ETS exposure and have a corresponding PEM
series {1, 2, 3, 4, 5}, (R2 = 1).
7-103
-------
5 -
SAM
Figure 7-26. Example of difference between serial correlation (a) and cross-sectional
correlation (b) of PEM and SAM, showing how pooling of individuals
together can mask an underlying relationship of PEM and SAM.
• Let neighbor B live with ETS exposure and have a corresponding PEM
series {11, 12, 13, 14, 15}, (R2 = 1).
• When their PEM values are pooled so that they are analyzed together
(cross-sectionally) {(1,11), (2,12), (3,13), (4,14), (5,15)} vs the SAM set
{1, 2, 3, 4, 5}, thenR2 = 0.074.
• However, had the two PEM series been averaged each day, the sequence of
averages {6, 7, 8, 9, 10} would have a correlation of R2 = 1 with the same
SAM sequence. This averaging process is described later in more detail in
Section 7.6.2.
The explanation by Janssen et al. (1995) for the low cross-sectional correlations of PM PEM
with PM SAM found in the literature and the new analyses reported by Tamura et al. (1996),
Jansen et al. (1995), and Wallace (1996) represent a major advance in our understanding of
contributions of ambient PM to personal exposures.
7-104
-------
7.4.2.4 Overview of Comparison of Personal Exposure to Ambient PM Concentrations
The PTEAM Study and the other key PEM studies discussed in this chapter so far are
summarized in Table 7-26. This table shows that many of the early studies reported no
statistically significant correlation between PEM and SAM. However, these early studies
were all characterized by a non-probability sample and a relatively small sample size. The
PTEAM study in Riverside which was a probability sample (Clayton et al., 1993) and the
Lioy et al. (1990) study in Phillipsburg, which was not a probability sample, have large
sample sizes and achieved significance. The other studies, such as World Health
Organization (1982a,b) or Morandi et al. (1988) are equivocal. In the following sections,
PEM/SAM comparisons for some PM constituents and two means of visualizing the complex
relationships of PM measured by a SAM and a PEM are developed.
7.4.3 Personal Exposures to Constituents of Particulate Matter
Suh et al. (1993) measured personal exposures to sulfate (SO4=) and acidity (H+), and
ambient and indoor concentrations in State College, PA, summer 1991. The correlations
between personal and ambient values of sulfate and acidity were R2 = 0.92 and
0.38 respectively, which is in marked contrast to the R2 « 0 between earlier reported
ambient PM and personal PM studies (Table 7-26). This relationship is supported by
Figure 7-22, indicating that personal activities in the PTEAM study do not generate or
resuspend sulfates less than 10 /mi.
Figure 7-27 shows the consistent relation between ambient and personal sulfate
measurements (slope = 0.78 ± 0.02), and Figure 7-28 shows the improvement in prediction
by using the TWA with a correction factor (estimated personal sulfate = 0.885TWA,
R2 = 0.95 with slope = 0.96 ± 0.02). Personal acidity was also computed by the same
equation with a correction for personal ammonia (NH3) exposure that gave an R2 = 0.63.
As opposed to PM which has both indoor and outdoor sources, the sulfate and acidity are
virtually all of outdoor origin. Consequently, only the characteristics of the indoor
environment, such as air conditioning and ammonia sources, modify the personal exposures
indoors.
7-105
-------
o
ON
TABLE 7-26. COMPARISON OF PERSONAL EXPOSURE MONITOR (PEM) EXPOSURE OF
INDIVIDUALS TO THE SIMULTANEOUS AMBIENT PARTICULATE MATTER (SAM)
CONCENTRATION IN SEVERAL U.S. AND FOREIGN CITIES (jig/m3)
Reference
Binder et al.
Dockery and Spengler
Dockery and Spengler
Spengler et al.
World Health
Organization
Spengler et al.
World Health
Organization
Sexton et al.
World Health
Organization
World Health
Organization
Morandi et al.
Lioy et al.
Perritt et al.
Clayton et al.
Tamura et al.
Year2
1976
1981b
1981b
1980
1982a
Winter
Summer
Winter
Summer
1985
1982b
Summer
Winter
1984
1984
Winter
Summer
Monsoon
1985
Winter
Summer
1988
1990
1991
1993
1996
Location
Ansonia
Watertown
Steubenville
Topeka
Toronto
Non-asthmatic
Non-asthmatic
Asthmatic
Asthmatic
Kingston/
Harriman
Zagreb
Waterbury
Bombay
Beijing
Houston
Phillipsburg
Azusa
Riverside
Tokyo
PM/um
5
3.5
3.5
3.5
25
3.5
5
3.5
3.5
3.5
3.5
10
2.5
10
10
10
N
20
18
19
46
13
13
13
13
97
12
48
15
20
30
14"
14C
9
9
141
7
Time
24-h
24-h
12-h
12-h
8-h
8-h
8-h
8-h
24-h
1-wk
24-h
24-h
24-h
1-wk
12-h
24-h
24-h
24-h
24-h
24-h
48-h
Mean PEM
115
35
57
30
122
124
91
124
44
114
187
36
127
67
58
177
66
27
86
76
79
115
113
37
Mean SAM
59
17
64
13
68
78
54
80
18
55
193
17
117
65
51
421
192
16
60
60
43
62
84
56
R2 PEM vs SAM
NS
0.00
0.19
0.04
0.15
0.10
0.00
0.07
0.00
0.00
0.50
0.00
0.26
0.20
0.02
0.07
0.03
0.34
0.04
0.25
0.01
0.01
0.23
0.68
P
NS
NS
NR
NS
NS
NS
NS
NS
NS
NS
NR
NS
NR
NR
NS
0.09
NS
<0.05
0.008
0.001
NS
NS
NR
0.000
N = Number of individuals carrying personal monitors.
NS = Not statistically significant from 0.
NR = p Value not reported, but mentioned as significant.
a = Year of publication.
= 14 Subjects carried PEMS for 14 days for 191 valid measurements.
c = Three outliers are removed and regression is for 188 measurements.
-------
600
500
400
300
200
100
100
200
300
400
500
600
Outdoor Sulfate (nmoles/m J)
Figure 7-27. Personal versus outdoor SO4 . Open circles represent children living in
air conditioned homes; the solid line is the 1:1 line.
Source: Suh et al. (1993).
500
Measured Sulfate {nmoles/m3)
Figure 7-28. Estimated ("best fit" model) versus measured personal SO4=. Model
includes indoor and outdoor concentration and activity data. Open circles
are air conditioned homes; the solid line is the 1:1 line.
Source: Suh et al. (1993).
7-107
-------
Similar high correlations for total sulfur were found by Ozkaynak et al. (1996) in the
PTEAM study. Regressions of personal exposures in the PM10 fraction on outdoor sulfur
gave the following results (^g/m3):
5pers (day) = 0.62 (0.07 SE) + 0.69 (0.03) 5out N = 168 R2 = 0.78
5pers (night) = 0.27 (0.06) + 0.68 (0.03) 5out N = 162 R2 = 0.81
Another important consideration in evaluating personal exposures, from the indoor and
outdoor environmental measurements, is that the chemical composition of the excess in
personal exposure compared to the TWA exposure calculation may be significantly different
than that predicted from the indoor and ambient data alone.
In addition to the two factors cited just above, a microscale "personal cloud" can be
generated by the person's activities which complicates the exposure measurement process.
This effect is most important in occupational settings where personal exposures are not
readily comparable to weighted area sampling measurements. For example, Lehmann et al.
(1990) measured workers exposure to diesel engine exhaust by personal monitoring of PM10
with a range of 0.13 to 1.2 mg/m3, compared to an area estimate range of 0.02 to
0.80 mg/m3. The U.S. Centers for Disease Control (1988) reports the exposures of nurses
and respiratory therapists to the aerosols of ribavirin during treatment of patients by ribavirin
aerosols administered inside an oxygen tent. Bedside area monitors averaged 317 /ixg/m3
while personal exposures ranged from 69 to 316 /xg/m3 with an average of 161 /*g/m3.
Environmental Tobacco Smoke (ETS) is a category of PM found in many indoor
settings where smoking is taking place or recently occurred. As stated in Section 7.2, ETS
is the major indoor source of PM where smoking occurs. Because of the depth of discussion
of ETS in Section 7.2.2.2, no further discussion is made here other than to note that ETS
adds on the order of 25 to 30 /ig/m3 to 24-h average personal exposures and residential
indoor environments where smoking takes place (Holcomb, 1993; Spengler et al., 1985).
The random ETS increment will tend to reduce the correlation between PEM and SAM.
If one were able to subtract out the ETS from the PEM PM data, the correlation of SAM
with the non-ETS PEM PM might be improved (Dockery and Spengler, 1981b). As stated
as a caveat in the introductory section 7.1, the inhalation of main-stream tobacco smoke will
be a major additive exposure to PM for the smokers, which dwarfs the nonsmoker's
PEM PM. Therefore the results presented so far apply only to nonsmokers, and a major
7-108
-------
proportion of the US population (e.g., smokers) has a total exposure to PM that is at least
one order of magnitude greater than that of the nonsmokers.
7.5 INDIRECT MEASURES OF EXPOSURE
7.5.1 Time-Weighted Averages of Exposure
The early air pollution literature related health to ambient paniculate matter (TSP)
concentrations as a surrogate for personal exposures to PM. Although this relationship has
been shown to be highly questionable for specific individuals, it still is used in studies such
as Pengelly et al. (1987) who estimated TSP exposures of school children in Hamilton,
Ontario, by interpolation of ambient TSP concentrations to the school locations.
The first usage of a time-weighted-average (TWA) of environmental exposures to
estimate total human personal exposure to an air pollutant (Pb) was by Fugas et al. (1973).
In theory, a human exposure to PM could be estimated by use of Equation 7-2 and
knowledge of the average PM concentration while in each microenvironment (/^E) that a
person experiences and the duration of the exposure in each such /*E (Duan, 1982; Mage,
1985). For a room with no source in operation, the whole room could be treated as a
single fjE. However, when a PM source is in operation and gradients exist, that very same
room may need to be described by multiple jiEs. These fiEs could have dimensions of an
order of a few centimeters close to the source and of several meters farther from the source.
Ogden et al. (1993) compared exposures from personal sampling and static area
sampling data for cotton dust exposures. The British cotton dust standard specifies static
sampling, because the 1960 dose-response study used to set the standard used static sampling
data to compute worker exposure and dosage. Ogden et al. (1993) found median personal
exposures of 2.2 mg/m3 corresponding to a mean static background concentration of
0.5 mg/m3. They concluded that "The presence of the body and its movement affect what a
personal sampler collects, so static comparisons cannot be used to infer anything about the
relationship of the (static) method with personal sampling." Ingham and Van (1994)
confirmed this finding by modelling the human body as a cylinder and showing that unless
the personal monitor length/diameter ratio was greater than four, the aspiration efficiency
7-109
-------
(the fraction of particles sampled that would be sampled in the absence of the body) could be
greatly affected.
Rodes et al. (1991) compared the literature relationships of personal exposure
monitoring (PEM) to ptE area monitoring (MEM) for PM, as shown in Figure 7-29, to which
Ogden et al. (1993) is added as a single point. The authors found that PEM/MEM ratios
ranged from 3 to 10 in occupational settings, and from 1.2 to 3.3 in residential settings.
These combined data show that approximately 50% of all measured PEM PM values are
more than 100% greater than the estimated simultaneous MEM values using the TWA
approach. Their explanation points to this excess PM as due to the spatial gradient about
indoor sources of PM which are usually well away from area monitors which thus fail to
capture the high exposures individuals may get when in close proximity to a source. They
suggest that clothing lint and skin dander could only add, at most, a few percent to the total
PM mass collected by a personal exposure monitor.
The Tokyo PM10 data of Tamura et al. (1996), added on Figure 7-29, show that for
their cohort of five elderly housewives and two male retirees that there is no evidence of a
large personal cloud effect as seen in the other studies listed. Japanese people customarily
take shoes off before entering a home and do not use wall-to-wall carpets, which would
reduce track-in of soil and eliminate a major reservoir for resuspension of dust. However,
this same cohort does display a "personal cloud" effect for the PM greater than PM10, with a
maximum PEM/MEM value of 3.3 for PEM = 55 ^g/m3 vs MEM 17 /*g/m3. This is
consistent with the findings of Thatcher and Layton (1995) showing, on Figure 7-15, an
indoor increase due to human activity, primarily for the PM greater than 10 pm in size, and
Sheldon et al. (1988a,b) showing two U.S. homes for the elderly with less than 10 jug/m3
PM3 over a 72-h period in a nonsmoker's room.
7.5.2 Personal Exposure Models Using Time-Weighted Averages of Indoor
and Outdoor Concentrations of Particulate Matter
Several studies have used the relationship of Equation 7-2 to compute the time-
weighted-average (TWA) PM exposure of subjects. The procedure calls for a time-activity
diary to be kept so that the time at-home, outdoors, at-work, in-traffic, etc., can be defined.
By use of fiE monitoring data from the study itself (or literature values of PM concentrations
7-110
-------
100
95 98
° Stevens (1969)
Fletcher and Johnson
O Parker etal. (1990)
oLioyetal. (1990)
EPA PTEAM data
©Ogdenetal. (1993)
^Tamuraetal. (1996)
Data median
30 50 70
Cumulative % less than
Figure 7-29. Personal activity cloud (PEM) and time-weighted average exposure
(MEM).
Source: Rodes et al. (1991), Ogden et al. (1993), Tamura et al. (1996).
in similar /xEs) and concurrent ambient monitoring, one can predict the concentration that
would be measured if the subject had carried a PEM.
Because people in the United States spend, on average, 21 h indoors each day (U.S.
Environmental Protection Agency, 1989), the concentration hi indoor /*Es is a most
7-111
-------
important quantity for usage within a TWA PM model. The important articles on indoor air
quality for PM have been reviewed extensively by Wallace (1996) and are covered in Section
7.2. The articles that are discussed here predict PM exposures of non-smokers that include
ETS, and most provide PEM data for comparison. As opposed to the gaseous pollutants for
which continuous hour-to-hour time series of SAM data are available, PM SAM monitoring
data have been often only available as a time series of 24-h SAM measurements.
Consequently, in much of the early PM TWA literature, the modelers assumed, by necessity,
the same ambient PM in the morning and evening, which might not be accurate (Dockery
and Spengler, 1981b).
Spengler et al. (1980) in a study of PEM, SAM and SIM in Topeka, Kansas, found the
averages of PEM = 30 /xg/m3, SIM = 24 /Ag/m3 and SAM = 13 /^g/m3. They note
"It suggests that somewhere in an individual's daily activities, they are being exposed to PM
at concentrations higher than what is measured either indoors or outdoors". This relationship
has been found in almost all other studies, such as PTEAM (Clayton et al., 1993) where
daytime PEM averaged 150 pig/m3 and SIM and SAM averaged just under 100 ^g/m3.
Spengler et al. (1985) measured 24-h PEM, SIM and SAM. The resulting relationship based
on Equation 7-1 was: PEM = 17.7 /ig/m3 + 0.9 TWA. The authors noted, in addition to
the previous suggestion, that the excess of PEM over TWA may be due to an incorrect
assumption that the indoor and outdoor are constant during the 24-h sampling period.
Koutrakis et al. (1992), in a study discussed in Section 7.2 on Indoor Air, report that
their source-apportionment mass-balance model predicts penetration from outdoors to
indoors on the order of 85-90% for Pb and sulfur compounds. The authors claim that:
"We can satisfactorily predict indoor fine aerosol mass and elemental concentrations
using the respective outdoor concentrations, source type and usage, house volume and
air exchange rate."
The authors further note that this may be a cost-effective approach to estimating peoples'
exposure while indoors, since the necessary ambient data may be available and the housing
profile may be collected with a simple interview.
Colome et al. (1992) measured indoor and outdoor PM-10 at homes of asthmatics in
California. Their personal monitoring data, limited to three individuals, confirmed the
relation in Figure 7-16 that "some protection from higher outdoor concentration is afforded
by shelter if smokers and other particulate sources are not present". This observation may
7-112
-------
be important for estimating the exposure of elderly and infirm people who are assumed to be
the susceptible cohort (Sheldon et al., 1988a,b).
Klepeis et al. (1994) present an up-to-date TWA PM Model that uses, as an input, real-
time hourly PM SAM data and a mass balance equation to predict exposures of nonsmokers
in various indoor settings based on ambient PM data, presence of PM sources such as
smokers, and other variables relating to air exchange rates. The inclusion of the additive
terms that allow for sources, such as cooking and presence of smokers adds to the TWA of
Equation 7-2, which in effect is a correction for the underprediction of the fjE concentration.
In summary, as described by several authors, the PM PEM exposure of individuals who
are not smoke exposed has been shown to be higher than their corresponding TWA of SIM
and SAM in U.S. studies. The exact reason for this excess in PM, sometimes called a
"personal cloud", is not known (Rodes et al., 1991). It has been thought to reflect the fact
that the person's presence itself can stir up loosely settled-dust by induced air motion and
vibration (Ogden et al., 1993; Aso et al., 1993). Thatcher and Layton (1995) gave an
example where merely walking into and out of a room raised the total suspended dust (PM10)
by 100%. A study by Litzistorf et al. (1985) of asbestos type fibers in a classroom showed
how fibers (f) were stirred up when it was occupied. The levels rose from below the
detectable level of 10000 f/m3 to 80000 f/m3 when occupied, and they returned to below
detectable levels within 1 h after the end of the class. Millette and Hays (1994) present a
detailed discussion of the general topic of resuspended dust in their text on settled asbestos
dust.
It may not be a proper procedure to use a 24-h average concentration in a physical
setting, such as a kitchen, to estimate a person's exposure while in the kitchen. As described
previously in the discussion of the definition of a microenvironment in Section 7.1.2, the
same kitchen can constitute one or more /*Es depending on the source operation pattern.
In many studies, such as Spengler et al. (1985), the SIM sampled the indoor residential
setting for 24-h in phase with the PEM. The resulting average SIM will often underestimate
the person's exposure while they are at home and may contribute to the difference between a
TWA exposure and the PEM.
In a similar manner, a person's workplace exposure may be more or less than that in
their home. In the PTEAM study (Clayton et al., 1993), there was a general decrease in
7-113
-------
exposure for those employed outside their home. However, employment in a "dusty trade",
such as welding, may increase their PM PEM. Lioy et al. (1990) give an example of a
subject with a hobby involving welding having a 24-h PEM reading of 971 /ig/m3.
Indirect estimation of a person's time-weighted-average (TWA) PM exposure may be a
cost-effective alternative to direct PEM PM measurement. Mage (1991) compared the
advantages and disadvantages of the TWA indirect method compared to the direct PEM
method. The primary advantages of the indirect method are the lower cost and lower burden
on the subject, because it uses only a time-activity diary and no PM PEM is required; the
disadvantage is the lower accuracy. The primary advantage of the PEM PM method is that it
is a higher accuracy direct measurement; the main disadvantages are the higher cost and
higher burden on the subject (see Section 7.3.1). Mage (1991) proposed a combined study
design in which direct measurements on a subset of subjects can be used to calibrate the
TWA estimates of other subjects. Duan and Mage (1996) present an expression for the
optimum fraction of subjects to carry the PEM as a function of the relative cost of the PM
PEM to the TWA PM estimate and the correlation coefficient between the PM PEM data and
the PM TWA estimates.
7.6 DISCUSSION
7.6.1 Relation of Individual Exposures to Ambient Concentration
The previous sections discussed the individual PM PEM vs PM SAM relationships of
the studies listed in Table 7-26. In many of the cross-sectional PM studies, no statistically
significant linear relationship was found between PEM and SAM, but in some other studies
the relationship is positive and statistically significant. However, as shown by Lioy et al.
(1990), Janssen et al. (1995), and Tamura et al. (1996), the serial correlations between PEM
and SAM within an individual's tune series are often highly positive and significant. This
section discusses these data in terms of understanding the complex relationship between the
SAM concentrations and the individual PEM exposures. In the following section, the
relationship of the SAM to the mean PEM in the community surrounding the SAM will be
presented.
7-114
-------
The principle of superposition is offered as a basis for visualization of the process
involved in creating a total exposure. A linear system will exist for respirable-PM PEM
exposures if the expected PEM response to a source emitting 2 mg/min of PM is exactly
twice the PEM response to that identical source emitting 1 mg/min of identical PM.
If superposition applies, then we can construct the total exposure by adding all the
increments of exposures from the various source classes and activities that a subject performs
on a given day.
Let the SAM be representative of the macroscale ambient PM concentration in the
community as shown on Figure 7-30a. This is the exposure that would be measured for a
person if they spent 24-h per day outdoors near the SAM site. Neglecting local microscale
variation (e.g. backyard barbecue or leaf burning), while people are outdoors they are
exposed to 100% of the SAM value (Figure 7-30b). Assume that this exposure is also the
baseline PM for a location in traffic which occurs outdoors. The increment produced by the
local traffic is considered later.
While people are indoors, they are exposed to a variable fraction of tune-lagged
SAM PM. This constitutes an amount of (1) the fresh PM which depends on recent SAM
and the air exchange rate between indoors and outdoors, and the PM deposition sinks
(filtration of recirculated air, surfaces, etc.), and (2) PM from outdoor sources that had been
deposited in the past but is resuspended due to human activity and air currents. PTEAM
(Ozkaynak et al., 1996), as cited in Section 7.2, found that outdoor air was the major source
of indoor particles, accounting for 75% of the fine fraction (<2.5 /xm AD) and 67% of the
thoracic fraction (< 10 fjan AD) in indoor air. It is noted that these average fractions will
be lower in communities with lower average SAM values. Lewis (1991) reported an
apportionment of indoor air PM in 10 homes within a wood burning community in
Boise, ID. The results showed that 50% of the fine PM was of outdoor origin (SAM), and
in 9 of 10 homes, 90% of the sulfur was from outdoors (one home had an anomalous sulfate
injection from a humidifier using tap water). This is consistent with indoor sources varying
independently of the SAM in a stationary manner (constant mean and variance), so that the
relative contribution of indoor sources to indoor exposures decreases as SAM increases.
Figure 7-30c represents the increment to PEM from outdoor sources of SAM while the
7-115
-------
"E
0>
6 12 18 24
Time - Hours
6 12 18
Time - Hours
6 12 18
Time - Hours
24
SAM
SIM
Indoors
non-ETS
non-SAM
SAM
Traffic
Increment
to SAM
6 12 18 24
Time - Hours
Occupational
Exposure
Increment
to SIM
SAM
0 6 12 18 24
Time - Hours
ETS
Exposure
6 12 18 24
Time - Hours
0 6 12 18 24
Time - Hours
Figure 7-30. Components of personal exposure.
"E
E
•*•
"g
20 -*
Cigarettes
Smoked
SAM
^> .
--
s>*
'*
*-,
-..
^
6 12 18 24
Time - Hours
7-116
-------
subjects are indoors at home and at work. The SAM value is shown as the dotted line for
reference in this and all the following Figures 7-30c to 7-30h.
While people are indoors, at home, and at work, they also are exposed to-PM emitted
by indoor sources - other than ETS from passive smoking and specific occupational sources.
These sources, such as cooking, lint from clothing and furnishings, mold, insects, etc.,
create PM that agglomerates and deposits as visible dust that can be continuously
resuspended, which constitutes an additional PEM increment. Figure 7-30d shows the
additive effect of this source. In traffic, or near vehicles in a parking garage or parking lot,
people are exposed to an increment of PM over and above the SAM value for that location.
Figure 7-30e shows the additive PM for this setting that would be added to Figure 7-30b for
the local vehicular emissions.
At work in a "dusty trade" (e.g., welder, mechanic, or miner) there is an increment of
exposure associated with these occupational activities that generate PM. Figure 7-30f
represents the additive PM for these activities which are assumed to take place "indoors".
In an indoor setting, in the presence of a smoker or the wake of a smoker, a PEM will
record an increment of ETS associated with the act of smoking. Figure 7-30g shows the
added PM increment for this source.
Last, but not least, is the physical act of smoking itself. As described previously, the
main stream smoke from a cigarette, cigar, or pipe is inhaled directly without being sampled
by a PEM. The mass of PM directly inhaled from smoking one-pack-per-day of cigarettes
rated as delivering "1 mg 'tar' per cigarette by FTC method" is 20 mg per day (Federal
Trade Commission, 1994). If this were distributed into a nominal 20 m3 of air inhaled per
day, it would be an additive increment on the order of 1 mg/m3 to a 24-h PEM reading. Tar
emissions as rated by the Federal Trade Commission (1994) range from <0.5 mg/cigarette
to 27 mg/cigarette. Therefore one-pack-per-day smokers can have a PM exposure standard
deviation that is much larger than the mean exposure to PM of non-smokers, simply from
choice of brand. Figure 7-30h represents the impact of the act of smoking as creating
exposures represented by the vertical spikes with an integral area > 1 mg-day/m3 per day.
For all subjects, by the principle of superposition, the sum of the areas shown in
Figures 7-30b and 7-30c represents the exposure of an individual to the PM constituents that
are characterized by a SAM PM concentration. The additional exposure categories that are
7-117
-------
independent of the SAM concentration (Figures 7-30d through 7-30g) and are appropriate for
that subject would represent the portion of 24-h PEM PM that is not associated with SAM.
Variance of SAM should explain much of the variance in the SAM related PEM fraction as
defined by Figures 7-30b and 7-30c. The summation over a full day for all categories 7-30b
to 7-30g would be the PEM for any subject, such as is shown in Figure 7-2 (Repace and
Lowery, 1980).
Although there are no data for PEM PM exposures of individuals living in homes
without any indoor sources of PM, there are data for PEM sulfate as discussed previously in
Section 7.4.3. Given that there are negligible sources of sulfur (S) that originate in the home
(matches, low-grade kerosene, humidifiers using tap water), the high correlation of
PEM sulfate and SAM sulfate (R2 = 0.92) of Figure 7-27 reported by Suh et al. (1993),
where no appreciable sources of S were present, is an indication that the same relationship
should hold for all SAM PM of that size range. The data of Anuszewski et al. (1992) show
that light scattering particles measured by nephelometry had a very high correlation between
indoor and outdoor concentrations (R2 > 0.9) for one home, but were lower for others.
Lewis (1991) and Cupitt et al. (1994) report that PM10 appears to penetrate with an average
factor of 0.5 in Boise homes without woodburning. The factor goes up to 0.7 with
woodburning, and the authors assume that the factor would go up to 0.9 in the summer when
homes are less tightly sealed. However, the authors did not consider the deposition rate k.
This is in contrast to the data of Thatcher and Lay ton (1995), who measured k and found
penetration factors of 1.0 for all PM sizes < 10 /im.
If the variance of the PEM PM portion which is uncorrelated to SAM (Figure 7-30d to
7-30g) is very large, the percentage of the variance of the PEM PM that can be explained by
the variance of SAM PM will be very small. It may be possible that the different
populations sampled, cited in the studies of Table 7-26, have widely different home
characteristics, occupations, mode of commuting, and smoking exposures that contribute to
the different PEM vs SAM relationships. In some of the cleaner communities (such as
Watertown, MA; Topeka, KS; Waterbury, VT; and Kingston and Harriman, TN) SAM
averaged less than 20 /*g/m3. The non-SAM increments to PEM exposure in these locales
were greater than the SAM and may have been so variable between people (eg. ETS and
non-ETS exposures pooled together) that the PEM PM became insignificantly correlated with
7-118
-------
the SAM PM data. The exception is Houston, TX, with a SAM = 16 ^g/m and a
significant R2= 0.34 (0.005 < p < 0.05). However, Morandi et al. (1988) note that
deletion of two outlier observations would reduce R2 and make it nonsignificantly different
from 0 (p > 0.2). This is in contrast to the three studies in communities with high SAM
levels (Tamura et al., 1996; Clayton et al., 1993; Lioy et al., 1990), where the relations
between PEM and SAM were significant.
All discussions above relate to nonsmokers. As for the smoker, the exposure from
Figure 7-30h would outweigh the sum of all the other exposures, 7-30b through 7-30g. This
smoking increment may have an important implication for interpretation of epidemiology
studies that relate ambient PM, as a surrogate of exposure, to mortality or morbidity.
Because the daily amount of individual smoking and other exposures from indoor
sources (cooking, ETS, resuspension of settled dust by walking into carpeted rooms, hobbies)
is independent of the daily SAM value, the variance of the PM SAM value is a surrogate for
the variance component of total personal exposures to PM associated with PM SAM. For
nonsmokers ambient PM reflects about 50 to 70% of their PM10 exposure that by definition
does not contain directly inhaled smoke exposure (Tamura et al., 1996; Ozkaynak et al.,
1996). This relationship would also hold for the total PM exposure of smokers minus the
effective increment they receive from their direct smoking which is independent of PM
SAM. Therefore, a relationship between ambient PM (SAM) and human exposure to PM
(PEM) that makes sense, is that the SAM value is a surrogate for personal exposure to PM
(PEM) from PM originating in the ambient air. This relationship would apply to everyone,
smokers and nonsmokers alike. However, treating SAM as a surrogate for total personal
exposure to PM from all sources, including those major sources of PM that vary
independently of SAM (active smoking and occupational exposures), would be wrong.
7.6.2 Relation of Community Participate Matter Exposure to Ambient
Particulate Matter Concentration
For the morbidity/mortality studies described in Chapter 12 that use SAM as the
independent variable, that SAM can be interpreted to stand as a surrogate for the average
community exposure to PM from sources that influence the SAM data. These sources of
ambient PM do not include indoor sources such as the "personal cloud" of skin flakes and
7-119
-------
lint, ETS, cooking fumes, and resuspended PM from walking on a dirty carpet. Thus, if we
could subtract off from each PEM measurement the contribution to the total exposure from
the indoor sources, such as smoking, cooking, carpets, and personal clouds, the residual PM
from ambient sources would probably improve the correlation with SAM, as described by the
data of Tamura et al. (1996) for nonsmoking-noncarpeted homes occupied by elderly people.
Mage and Buckley (1995) tested the relationship of the mean PEM to SAM as a means to
minimize the affect of variations of these indoor sources of PM on the relation of PEM to
SAM, and their results, with modifications, are presented in the following section.
There are several different models for these analyses and although most describe the
same linear relationship, the models differ greatly in their assumptions about the error terms.
The discussion of the various models is followed by U.S. EPA reanalyses of five different
PEM-SAM data sets described previously in Section 7.4.
7.6.2.1 Methodology
Methods for Missing Data
One common difficulty in the use of aerometric data is the presence of missing data
elements. For example, consider the following PEM data from the study of Tamura et al.
(1996). The authors measured the 48-h personal exposure to PM10 for seven individuals
living near a main road for 11 periods in four seasons distributed over a complete year. This
example has a great deal of missing data, and for purposes of computation, the data were
split into a group living close to the road (persons A, B, C, and D), and a group living
farther from the road (persons E, F, and G). Their indoor and outdoor data were shown
previously on Figure 7-24. The PEM data for the first group are shown in Table 7-27.
Unless pairwise correlations are computed, the standard solution to the problem is to
delete all observations for which any of the variables are missing. This approach, known as
a complete-case analysis, is standard in the majority of the statistical packages. For this
example, we would be left with only 5 of the original 11 periods of observation. This
section will describe a model which will allow for the inclusion of all available data.
The reason for the missingness of the data is extremely important because it determines
our ability to obtain maximum likelihood estimates (MLE). The following definitions are
paraphrased from Little and Rubin (1987): If the probability of being missing is independent
7-120
-------
TABLE 7-27. 48-HOUR PERSONAL EXPOSURE TO PM10 (jtg/m3)
(Data Taken by Subjects Living Along a Main Road in Tokyo)
Period Person A
1 43.7
2 27.4
3 30.2
4 22.4
5 57.4
6 M
7 M
8 24.6
9 31.0
10 22.9
11 68.7
Person B
40.4
31.5
39.2
29.2
43.2
26.1
37.9
M
34.5
M
51.8
Person C
37.5
29.8
32.7
25.9
43.3
27.9
35.8
41.4
36.0
24.3
52.6
Person D
52.3
26.0
M
38.2
M
39.9
34.6
39.8
45.6
30.6
68.1
M = Missing observation.
Source: Tamura et al. (1996).
of both the variables missing and the variables present, then the data are said to be missing
completely at random (MCAR). If the probability of being missing depends on the variables
present, but not on the variables missing, then the data are said to be missing at random
(MAR). If neither situation holds, then there are no general solutions to the problem. This
would happen if the value of the missing variable (which is not known to us) is directly
related to its probability of being missing. Laird (1988) discusses models used for maximum
likelihood estimation with missing data, as well as a detailed discussion of the non-response
mechanism.
One solution is to assume that the measurements are distributed as a multivariate
normal distribution (or to assume that some transformation of the data give a multivariate
normal distribution). The estimation of the parameters of a multivariate normal model with
missing data is a problem which has been discussed for many years (see Afifi and Elashoff,
1966). The first general solution to the problem of estimating a mean vector and covariance
matrix from a multivariate normal distribution with data missing at random was given by
Woodbury and Hasselblad (1970). The solution, referred to as the "Missing Information
7-121
-------
Principle", was generalized to other missing data problems by Orchard and Woodbury
(1972). Proof that the method always improved the likelihood was given by Dempster et al.
(1977), and the generalized solution method was named the E-M algorithm.
To describe the problem, the following notation will be used. Let x = x1,x2,...,xk be a
k-dimensional random vector from a multivariate normal distribution
1S |
(7-10)
where E is a symmetric positive definite matrix and A* is a vector. The mean of the vector x
is n and its covariance is £. Assume that we have n observations from this distribution,
X1,X2,...,Xn.
The E-M algorithm can be used to estimate the parameters of a multivariate normal
distribution. The method starts with any reasonable first estimate of the parameters.
Assume that we have initial estimates of the parameters jt and E, which can be obtained by
filling in the missing data with the column means and then estimating the parameters in the
usual manner. The E step consists of estimating the sufficient statistics. For this model, the
sufficient statistics are the sums and sums of squares of cross products.
Assume that at one particular point, Xj, some of the observations are missing and some
of the observations are present. Without loss of generality, we will drop the subscript, i, and
rearrange the subscripts so that the vector X is [Xj, X2] where all of the observations, Xj,
are missing and all the observations X2 are present. Partition the mean vector n and the
covariance matrix E in a similar fashion
and
12
(7-11)
Compute the regression of the missing observations on the observations present
-i
P = S12S22-
(7-12)
Estimate the missing values, Xlf by their expected values
7-122
-------
-14)- (7'13)
Compute the correction to the expected sums of squares
_-i _ r?-14^
Now add the vector X to the sums and XX' to the sums of squares and cross products using
their expected values for the missing values; remember to add EU i 2 to the cross products
corresponding to Xj.
The M step consists of recomputing the estimates of /* and £ from the completed sums
and sums of squares and cross products. This procedure will converge, typically taking five
to 20 iterations for a moderately sized problem. Using the methods just described, the
estimates of both the missing values and the parameters for the data of Tamura et al. (1996),
based on U.S. EPA reanalyses, are shown in Table 7-28.
This method was also used to fill in the missing values for persons E, F, and G (shown
in Table 7-29). Once the missing data were estimated, the average across all seven persons
was computed and compared with the ambient measurement monitor as shown in Table 7-30.
These data will be used as examples for the next section.
Linear Regression Models
The various linear regression models are illustrated next using the average personal
exposure values from the Tamura et al. (1996) data set which were described in the previous
section. For these examples, the average personal exposure will be considered the
dependent variable and the ambient concentration at the Itabashi site will be the independent
variable.
The first model is often referred to as the fixed independent variable model (see Dunn
and Clark, 1974, p. 225). The model assumes that the dependent variable is a linear
function of the independent variable with random error which is normally distributed (this is
a bad assumption but this is the most commonly used model). This can be written as
7-123
-------
TABLE 7-28. PARAMETER ESTIMATES FOR 48-HOUR PM10 PERSONAL
EXPOSURE MONITOR DATA TAKEN BY SUBJECTS LIVING
NEAR A MAIN ROAD IN TOKYO Otg/m3)
(Estimated Missing Values Shown in Parentheses)
Day
1
2
3
4
5
6
7
8
9
10
11
Means
Person A
43.7
27.4
30.2
22.4
57.4
(29.3)
(28.9)
24.6
31.0
22.9
68.7
35.1
Person B
40.4
31.5
39.2
29.2
43.2
26.1
37.9
(43.3)
34.5
(26.7)
51.8
36.7
Covariance/Correlation Matrix
Person A
Person B
Person C
Person D
215.8
0.745
0.819
0.888
83.9
58.9
0.949
0.731
Person C
37.5
29.8
32.7
25.9
43.3
27.9
35.8
41.4
36.0
24.3
52.6
35.2
(Correlation below
96.4
58.4
64.3
0.816
Person D
52.3
26.0
(37.4)
38.2
(58.4)
39.9
34.6
39.8
45.6
30.6
68.1
42.8
diagonal)
157.4
67.6
79.0
145.6
Source: Parameter estimates, including the calculation of estimated missing values, and covariance/correlation
matrix results from reanalyses by U.S. EPA of data from Tamura et al. (1996).
Yj = P0 + pjXj + e,, where (7-15)
i = l,2,...,n, n is the number of observations, and et is normal with mean 0 and variance o2.
No assumption is made about the distribution of the independent variable since it is
considered to be fixed.
Using the previous example, the estimated coefficients are given in Table 7-31, and the
results are shown graphically in Figure 7-31.
The second model is often referred to as the bivariate normal model (see Dunn and
Clark, 1974, p. 239). This model assumes that the dependent variable and the independent
variable are both normally distributed. Actually, the assumption is stronger—it assumes that
7-124
-------
TABLE 7-29. PARAMETER ESTIMATES FOR 48-H PM10 PERSONAL EXPOSURE
MONITOR DATA TAKEN BY SUBJECTS LIVING FARTHER FROM THE SAME
TOKYO MAIN ROAD DESCRIBED IN TABLE 7-28 (in /tg/m3)
(Estimated Missing Values Shown in Parentheses)
Period
1
2
3
4
5
6
7
8
9
10
11
Person E
57.1
(30.9)
26.8
32.9
68.6
31.2
26.5
35.8
40.7
29.8
62.5
Person F
62.2
26.5
23.1
(30.6)
(69.2)
26.6
24.0
(28.7)
(36.9)
27.5
51.2
Person G
(37.1)
(29.0)
25.3
27.2
48.0
24.4
29.7
37.7
35.4
22.4
61.0
Source: Parameter estimates, including the calculation of estimated missing values, based on reanalyses by
U.S. EPA of data from Tamura et al. (1996).
the joint distribution of the two variables is bivariate normal. The bivariate normal
distribution is a special case of the multivariate normal distribution described earlier. The
intercept, (3Q, and regression coefficient, j8ls are estimated by the same formulas as were used
in the first model even though the assumption is not the same. The R-squared term is also
the same, but the ANOVA Table no longer makes any sense.
The third linear model is the same as the first except that a lognormal error term is
used. This kind of model requires the use of a general linear model fitting routine. The
model gives less weight to large deviations about the predicted line where the predicted
values are already large. The model still assumes that the independent variable is fixed and
measured without error. The fit to the previous example is shown in Table 7-32. There is
no measure comparable to R2, but the log-likelihoods can be compared directly. Note that
7-125
-------
TABLE 7-30. AVERAGE PERSONAL EXPOSURE DATA COMPARED WITH
ITABASHI SITE MONITOR (PM10; jig/m3)
Period
1
2
3
4
5
6
7
8
9
10
11
Itabashi Site
66.5
30.1
37.9
50.3
90.5
40.7
40.5
55.1
70.6
31.9
99.5
Average Personal
47.2
28.7
30.7
29.5
55.4
29.3
31.1
35.9
37.2
26.3
59.4
Source: Data from Tamura et al. (1996).
TABLE 7-31. RESULTS OF LINEAR REGRESSION ANALYSIS, ASSUMING A
NORMAL ERROR USING THE EXPOSURE DATA FROM JAPAN
Linear regression
Y = intercept + slope X
Variable Beta Std. Err. Beta
Intercept 11.32 3.025
Slope 0.466 0.050
ANOVA Table
Source Sum of Squares Mean Square Error D.F. F-value
Regression 1194.3 597.2 2 42.9
Error 125.3 13.9 9
TOTAL 1319.6 120.0 11
R-squared = 0.905
Log-likelihood = -28.99
Source: U.S. EPA reanalyses of data from Tamura et al. (1996).
7-126
-------
80
60
(8
§ 40
J2
S.
-------
the linear model with a lognormal error fits slightly better than the normal error model,
although the difference of 0.49 in the log-likelihood is not statistically significant.
Orthogonal Regression Models
Orthogonal regression is also known as principle components regression. There is no
real assumption about the model. The purpose of the analysis is to pass a line through the
data such that as much of the variation is explained as possible. Variation is measured as the
squared distance from the points to the fitted line. Because no distributional assumptions are
made, no confidence limits can be placed on the estimated line. The measure of the total
variation is
Total variation = ouo22 - o12. (7-16)
The fraction of the variation explained is derived from the eigenvalues of the covariance
matrix, and the regression line corresponds to the first eigenvector. That is, the eigenvalues
are the solution of
/ -, /% \
= 0. (7-17)
°11
a!2
°U
°22,
- A
1
0
0 \
1 J
The values of X which satisfy equation (7-17) are
. _ gll + °22 ± qil- q22 + °2 (7-18)
A — .
The slope of the line corresponding to the largest eigenvalue, Xl5 is
(7-19)
The intercept, 00, is easily calculated because the line must pass through the mean of the
data.
7-128
-------
The measure, percent of variation explained, is a generalization of the multiple R2
measure from a single dependent variable, but its behavior is somewhat different. For a two
variable problem it can be calculated as X^CXj + X2). In general, for correlations near 1, it
will be about twice as good (.975 to .98 instead of .95), but for correlations near 0, the
behavior is not as simple. As a result, it can only be used to compare one orthogonal
regression with another. Because the standard correlation coefficient is a non-parametric
measure of association, it can be used for orthogonal regression as well. The results of
fitting by U.S. EPA of an orthogonal regression model to the previous example are in
Table 7-33. The slope and intercept are almost identical to the normal error model values
shown in Table 7-31.
TABLE 7-33. RESULTS OF AN ORTHOGONAL REGRESSION
ANALYSIS OF THE EXPOSURE DATA FROM JAPAN
Y = intercept + slope X
Variable Beta
Intercept 10.83
Slope 0.475
Total variation 5686.9
Percent explained 98.5
Source of data: U.S. EPA reanalyses of data from Tamura et al. (1996).
Measurement Error Models
In general, most linear regression analyses assume the independent variable has no
measurement error. When this error exists and no correction is made for it, the estimated
regression coefficients tend to be biased towards zero. Because we often have multiple
monitors we can often attempt to estimate these components of variation, and therefore
correct our estimated regression coefficients. The solution usually requires some additional
assumptions—in particular the assumption of multivariate normality is necessary for most of
the solutions. Additionally, some information must be available about the error variance.
Either the error variance of the independent variable or the dependent variable, or the ratio
7-129
-------
of the error variance to the variance of the dependent variable must be known exactly.
In some cases, these values are known with sufficient accuracy from other experiments so
that the values can be treated as known.
Much of the material on measurement error in continuous variables comes from the
work of Kendall and Stuart (1961) and Fuller (1987). Both authors make the same
distinction that was made in the earlier section regarding the fixed or random nature of the
independent variable. We will consider the more interesting case of measurement error in an
independent random variable.
This subsection assumes a model with a continuous dependent variable and a continuous
independent variable whose values are considered to be random and measured with error.
For example, Hasabelnaby et al. (1989) described an analysis of pulmonary function data
using measurements of NO2 exposure as a covariate. The true NO2 exposure was assumed
to be a random variable which was estimated by sampling NO2 levels in the home for two
weeks out of the year. The other terms in the model were height and gender of the
individual, and these were measured with little or no error.
The single random independent variable model assumes a single independent variable
whose values, xi5 are random values. The model is
y, = Po +
and we wish to estimate /30 and j3l. Assume that the expected value of x is f^, the expected
value of y is /iy, and that the variance of x is axx. We do not observe yt and Xj, but rather Y;
and Xj, where
Yf = y{ + Yj and (7-21)
Xt - xt + 6,, (7-22)
and where % is normal with mean 0 and variance
-------
assumption implies that the vector (Y,X) is distributed as a bivariate normal vector with
mean
= P
(7-23)
and covariance
°rr °XY
XX
r l~xx
a~ + O
yy.
(7-24)
Let $! be the standard regression estimate based on the observed data,
VI n
E (*< -
The expected value of ^ is
(7-25)
(7-26)
Thus, for the bivariate normal model, the least squares regression coefficient is biased
towards zero. The ratio, axx l°xx *s known by several names including the attenuation, the
reliability ratio, and in genetics as the heritability (Fuller, 1987).
Maximum likelihood equations can be set up for the bivariate normal model with
measurement error. The first and second moments, which are sufficient to determine the
distribution, will give five equations in the six unknown parameters, JLIX, axx,
-------
maximum likelihood estimate of aYy, and SXY be the maximum likelihood estimate of aXY.
The maximum likelihood estimate of #1 becomes
P, = V/(*a-<0- (7-27)
Note that this estimator reduces to equation (7-25) when the measurement error in x, axx,
isO.
If the measurement error in Y, ayy, is known, then there is a comparable solution. Let
Sxx, SYY, and SXY be defined as before. The maximum likelihood estimate of /3j becomes
P, = (*„ - ow)/Sw. (7-28)
All of this was based on the assumption that there was a true relationship between x and
y that had no error. If, in fact, there was some error so that
yt = Po + M, + «,. <
where ej is normal with mean 0 and variance
-------
Components of Variance Models
If we have measurements from several individuals over time or several ambient
monitors over time, then these measurements can be used in an analysis of variance
(ANOVA) model. The purpose of the model is to estimate the variation between individuals
and/or the variation between monitors. This information can then be used to adjust our slope
estimates as described earlier, as well as letting us estimate the correlation between ambient
and personal monitors assuming we had an infinite sample of both.
The logical analysis for this kind of data is a repeated measures design (see Winer,
1962, pp. 105-124). For most examples, the necessary components can be obtained from the
results of a standard two-way ANOVA table. For example, consider the data of Tamura et
al. (1996) after the missing values have been estimated (Tables 7-28, 7-29). There are
7 individuals measured over 11 48-h periods, resulting in the following ANOVA Table 7-34.
TABLE 7-34. RESULTS OF AN ANOVA ANALYSIS OF THE EXPOSURE DATA
FROM JAPAN
Source of Variation
date
person
date x person
Total
D.F.
10
6
60
76
S.S.
9235.41
634.53
2248.66
12118.60
M.S.
923.54
105.76
37.48
Source of data: U.S. EPA reanalyses of data from Tamura et al. (1996).
These results indicate that the mean square error for person is 105.76. This represents
an estimate of 7 ayy + aee (mean squared error). The value, 37.48, represents an estimate
of aee, so that ayy can be estimated by (105.76 - 37.48) / 7 = 9.75. Because we will
actually use the mean of 7 persons to estimate the average, the variance component we need
for equation (7-28) is estimated by 9.75/7 = 1.39.
For example, consider the data of Tamura et al. (1996). From the above analysis, we
have an estimate of the person variation,
-------
7.6.3 U.S. EPA Analysis of Data Sets
7.6.3.1 Tokyo, Japan Data Set
The data set of Tamura and Ando (1994) and Tamura et al. (1996) presents an
interesting problem. Shown in Table 7-35 is the correlation matrix for average personal
exposure with the two nearby ambient sites as well as their average. The Yamato site is
located near a highway intersection 0.7 km from the central Itabashi site.
TABLE 7-35. COVARIANCE AND CORRELATION MATRIX FOR AVERAGE
PERSONAL EXPOSURE AND AMBIENT EXPOSURES FROM JAPAN
Covariance/Correlation Matrix (Correlation below diagonal)
Average person
Itabashi site
Yamato site
Average site
Average Personal
119.97
(0.951)
(0.736)
(0.840)
Itabashi Site
232.83
499.30
(0.874)
(0.949)
Yamato Site
308.81
748.50
1467.62
(0.983)
Average Site
270.82
623.90
1108.06
865.98
Source of data: U.S. EPA reanalyses of data from Tamura et al. (1996).
Note that the correlation of the average personal exposure is much higher with the
Itabashi site than with the Yamato Site or the Average of the two sites. The estimated
components of variance can give strange results when there are only two sites and one is
much more highly correlated. For this reason, only the Itabashi site is used in the following
analyses. If there had been additional sites it would have been possible to make all of the
analyses in Table 7-36, but only those single site analyses are included at this time.
7.6.3.2 Phillipsburg, New Jersey Data Set
The personal exposure data (Lioy et al., 1990) contained some missing values and three
outlier values, and they all were estimated as described earlier. The results of U.S. EPA
reanalyses are shown in Table 7-37. In order to estimate the error variances, these data were
used in an analysis of variance as described earlier. The results are shown in Table 7-38.
7-134
-------
TABLE 7-36. SUMMARY OF RESULTS OF THE
ANALYSIS OF THE EXPOSURE DATA FROM JAPAN
Regression Model
Linear, normal error
Linear, lognormal error
Orthogonal
Linear adjusted for person error
Linear adjusted for ambient error
Measures of Association
Correlation of personal averages with Itabashi site
Correlation adjusted for measurement error
Average correlation of ambient with mean person
Average correlation of person with mean ambient
Fraction of variation explained by orthogonal regression
01 00
0.466 11.3
0.431 13.1
0.475 10.8
0.509 8.9
(Not available)
Value
0.951
(Not available)
(Not available)
0.872
0.985
Source: U.S. EPA reanalyses of data from Tamura et al. (1996).
The site monitoring data contained some missing values, and they were estimated by
U.S. EPA as described in Section 7.6.2.1. The means, covariances and correlations were
also estimated. The results are in Table 7-39. In order to estimate the error variances, the
same data were used in an analysis of variance as described earlier. The results of the EPA
analyses are shown in Table 7-40. The individual exposure values were averaged as well as
the site exposure values. These means are shown in Table 7-41.
The same regression analyses described earlier were performed by U.S. EPA. A plot
of the linear regression is shown in Figure 7-32. The orthogonal regression gives virtually
an identical plot and is not shown. The results of the analyses are in Table 7-42.
Note that all estimated regression equations are quite similar. The interesting value is
the correlation adjusted for measurement error. This represents an estimate of the
correlation between the mean of an infinite number of personal samplers and the mean of an
infinite number of fixed site samplers. This value is relatively close to one, but we do not
have good estimates of its variance to tell if the value is really different from one.
7-135
-------
o\
TABLE 7-37. PERSONAL EXPOSURE SUSPENDED PARTICULATE MATTER DATA FROM
PHILLIPSBURG, NEW JERSEY. MISSING VALUES ESTIMATED (); OUTLIER VALUES RECOMPUTED [ ].
Person Identifier (/xg/m3)
Day
1
2
3
4
5
6
7
8
9
10
11
12
13
14
01
59
52
74
115
65
45
75
104
84
55
10
39
26
45
02
85
58
69
88
37
16
77
81
29
29
60
59
44
44
11
54
85
94
136
139
56
65
79
48
70
65
80
65
89
31
39
17
56
104
38
22
35
67
56
35
25
23
35
17
41
(53.2)
(76.7)
86
65
77
34
36
83
85
59
36
127
31
105
42
36
45
77
116
64
27
80
32
122
81
[48.1
57
47
117
51
41
50
90
112
56
28
27
69
30
25
49.4]
32
114
(24.8)
52
28
53
93
120
52
21
34
61
36
39
43
35
67
24
61
123
104
200
125
184
60
92
112
57
199
93
121
47
117
62
67
56
134
272
190
58
(110.2)
91
96
77
84
95
95
63
81
96
50
166
193
79
57
124
144
156
63
99
31
71
44
82
79
49
81
98
49
12
77
69
123
41
32
45
18
14
91
50
66
77
164
(95.7)
54
107
96
91
66
78
63
31
57
92
32
63
187
172
89
99
184
198
[100.6]
135
122
72
109
108
Source: Data from Lioy et al. (1990). Missing values estimates and recomputed outlier values calculated by U.S. EPA.
-------
TABLE 7-38. RESULTS OF AN ANOVA ANALYSIS OF THE PERSONAL
EXPOSURE DATA OF PHILLIPSBURG, NEW JERSEY
Source of Variation
Date
Person
Date x Person
Total
d.f.
13
13
169
195
s.s.
119,600
103,300
149,900
372,800
m.s.
9202
7942
887
Source: U.S. EPA reanalyses of data from Lioy et al. (1990).
TABLE 7-39. SAM SITE CONCENTRATIONS, PM10 DATA (/tg/m3)
FROM PHILLIPSBURG, NEW JERSEY
[Missing Values Estimated ()].
Day Site 101 Site 102
01
02
03
04
05
06
07
08
09
10
11
12
13
14
Means
Covariance/Correlation
Site 101
Site 102
Site 103
Site 020
26
51
94
148
76
15
44
101
59
46
37
28
27
21
55
41
(55.6)
(101.8)
155
81
17
47
105
67
52
36
33
27
23
.2 60.1
Matrix (Correlation below
1313
0
0
0
.9 1346.5
.995 1393.8
.996 0.994
.943 0.935
Site 103
28
55
112
165
76
13
49
119
68
50
35
28
27
19
60.3
diagonal)
1538.9
1581.4
1816.2
0.929
Site 020
24
46
98
209
85
50
51
99
66
57
34
28
25
38
65.0
1596.6
1630.9
1850.1
2183.4
Source: U.S. EPA reanalyses of data from Lioy et al. (1990).
7-137
-------
TABLE 7-40. RESULTS OF AN ANOVA ANALYSIS OF THE SITE EXPOSURE
DATA OF PHILLIPSBURG, NEW JERSEY
Source of Variation
Site
Day
Site x Day
Total
d.f.
3
13
39
55
s.s.
671
90286
3615
94572
m.s.
223.6
6945.1
92.7
Source: U.S. EPA reanalyses of data from Lioy et al. (1990).
TABLE 7-41. AVERAGE PERSONAL PM10 EXPOSURE DATA COMPARED WITH
THE SITE EXPOSURE DATA FOR PHILLIPSBURG, NEW JERSEY
Day
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Ambient Average (/jg/m3)
29.75
51.55
101.45
169.25
79.5
23.75
47.75
106
65
51.25
35.5
29.25
26.5
25.25
Average Personal (/ig/m3)
60.15
58.91
106
134.29
86.76
42.07
80.23
91.86
79.19
69.57
60.74
62.79
57.14
62.04
Source: U.S. EPA reanalyses of data from Lioy et al. (1990).
7.6.3.3 Beijing, China Data Set
The Beijing, China data set reported by the World Health Organization (1985) is listed
in Table 7-43. From these data, daily mean values of the ambient and personal exposure
values were computed. An U.S. EPA reanalysis of these data is shown in Table 7-44 and in
Figure 7-33. The results of the analysis indicate that there is not a significant linear
relationship between the personal and ambient monitoring data. For this reason, it does not
7-138
-------
200
150
Q.
100
< 50
50 100 150
Average Site PMi0 ng/rrr3
200
Figure 7-32. Plot of relationship between average personal PM10 exposure versus
ambient PM10 monitoring data from Phillipsburg, NJ and regression line
calculated by U.S. EPA.
Source: Lioy et al. (1990).
make any sense to adjust the coefficient for measurement error. The subjects all worked at
the same institute so their daytime personal exposures may not have been independent of
each other.
7.6.3.4 Riverside, California Data Set
Both the personal exposure and the monitoring data used in analyses by Clayton et al.
(1993) contained some missing values, and they were estimated by U.S. EPA as described
earlier. The estimated correlation/covariance matrix results of U.S. EPA reanalyses of these
data are shown in Table 7-45.
Because the individual monitors were placed on different individuals each period, we
can't really estimate the variation between individuals. Based on previous analyses, we know
that most of the residual is variation between individuals, and so we will use this as a
7-139
-------
TABLE 7-42. RESULTS OF THE ANALYSIS OF THE
EXPOSURE DATA FROM PHILLIPSBURG, NEW JERSEY
Regression Model
Linear, normal error
Linear, lognormal error
Orthogonal
Linear adjusted for person error
Linear adjusted for ambient error
Measures of Association
Correlation of averages
Correlation adjusted for measurement error
Average correlation of ambient with mean person
Average correlation of person with mean site
Fraction of variation explained by orthogonal regr.
01 ft)
0.546 42.3
0.560 41.4
0.556 41.9
0.556 41.9
0.587 40.1
Value
0.955
0.974
0.944
0.633
0.984
Source: U.S. EPA reanalyses of data from Lioy et al. (1990).
surrogate. On average there were 3.5 persons per period and this number of individuals was
used in the analysis of variance shown in Table 7-46. The dichot monitoring data contained
little missing data, and so it was analyzed against the personal monitoring data for those days
with data. The results of the linear regression are in Table 7-47 and are shown graphically
in Figure 7-34. The individual exposure values were averaged so that they could be
compared with the site exposure values. These means are shown in Table 7-48. Note that
the orthogonal regression slope is larger than either of the linear regression slopes. Note
also that the linear regression slope adjusted for measurement error is larger than any of the
other slopes.
7.6.3.5 Azusa, CA Data Set
The Azusa, CA data set for PM10 reported on by Wiener et al. (1990) was described
earlier in Section 7.4.1.1.1 and presented in Table 7-21a. The same regression analyses
described earlier in this section were performed on the 24-h cross-sectional data and the
results are shown in Table 7-49. A plot of the linear regression analysis, resulting in a
7-140
-------
TABLE 7-43. PERSONAL AND AMBIENT EXPOSURE
DATA FOR BEIJING, CHINA (mg/m3)
Day
1
2
2
2
2
2
3
3
3
4
4
4
4
4
4
5
5
5
5
5
5
5
Personal
0.13
0.15
0.10
0.12
0.23
0.14
0.11
0.09
0.09
0.31
0.12
0.13
0.35*
0.12
0.25
0.10
0.22
0.32
0.12
0.08
0.13
0.07
Ambient
0.19
0.25
0.25
0.25
0.25
0.25
0.31
0.31
0.31
0.33
0.33
0.33
0.33
0.33
0.33
0.36
0.36
0.36
0.36
0.36
0.36
0.36
Day
6
6
6
6
6
6
7
7
7
8
9
9
9
9
10
11
11
11
11
11
11
11
Personal
0.15
0.17
0.13
0.16
0.21
0.08
0.35
0.24
0.20
0.15
0.23
0.18
0.10
0.38
0.11
0.23
0.32
0.11
0.21
0.11
0.20
0.29
Ambient
0.42
0.42
0.42
0.42
0.42
0.42
0.44
0.44
0.44
0.53
0.55
0.55
0.55
0.55
0.59
0.69
0.69
0.69
0.69
0.69
0.69
0.69
*The only personal value higher than the ambient value.
Source: World Health Organization (1985).
TABLE 7-44. RESULTS OF LINEAR REGRESSION ANALYSIS
FOR THE BEIJING, CHINA EXPOSURE DATA
Linear regression analysis of average personal exposure versus ambient exposure
Y = intercept + slope X
Variable Beta Std. Error Beta
Intercept 0.116 0.040
Slope 0.142 0.088
ANOVA Table
Source Sum of Squares Mean Square Error D.F. F-Value
Regression 0.0179 0.00893 2 1.2911
Error 0.2835 0.00692 41
TOTAL 0.3014 0.00701 43
R-squared = 0.05925, r = 0.2434
Log-likelihood = -46.95
Source: U.S. EPA reanalyses of data from World Health Organization (1985).
7-141
-------
400
300
100
200 400 600
Ambient PM10(ng/m3)
800
Figure 7-33. Plot of means of personal exposures and ambient PM10 from Beijing,
China and regression line calculated by U.S. EPA.
Source: U.S. EPA reanalyses of data from World Health Organization (1985).
TABLE 7-45. ESTIMATED MEAN VECTOR, COVARIANCE MATRIX,
AND CORRELATION MATRIX OF PERSONAL EXPOSURE
PM10 DATA FROM RIVERSIDE, CALIFORNIA (24-h,
Monitor
Means
Personal
109.9
Covariance/Correlation Matrix
Personal
Indoor
Backyard
Dichot
Wedding
PEM-SAM
1055.0
(0.849)
(0.725)
(0.707)
(0.721)
(0.736)
Indoor
79.9
(Correlation below
917.4
1107.6
(0.703)
(0.767)
(0.753)
(0.776)
Backyard
91.7
diagonal)
1024.7
1017.9
1893.2
(0.821)
(0.832)
(0.858)
Dichot
71.2
749.0
832.7
1165.6
1063.4
(0.956)
(0.989)
Wedding
68.4
838.9
897.0
1296.9
1116.6
1282.8
(0.976)
PEM-SAM
80.4
913.7
987.4
1427.4
1232.9
1337.1
1462.3
Source: U.S. EPA reanalyses of data reported on by Pellizzari et al. (1992).
7-142
-------
TABLE 7-46. RESULTS OF AN ANOVA ANALYSIS OF
THE PERSONAL EXPOSURE DATA OF RIVERSIDE, CALIFORNIA
Source of Variation
period
residual
Total
D.F.
46
114
160
S.S.
167,400
275,000
442,400
M.S.
3640
2412
Source: U.S. EPA reanalyses of data reported on by Pellizzari et al. (1992).
TABLE 7-47. RESULTS OF THE ANALYSIS OF THE
EXPOSURE DATA FROM RIVERSIDE, CALIFORNIA
Regression Model
Linear, normal error
Linear, lognormal error
Orthogonal
Linear adjusted for person error
Linear adjusted for ambient error
Measures of Association
Correlation of averages
Correlation adjusted for measurement error
Fraction of variation explained by orthogonal regr.
01
0.6174
0.6185
0.8071
0.9675
(Not applicable)
ft)
59.7
57.1
44.2
31.0
Value
0.721
(Not applicable)
0.864
Source: U.S. EPA reanalyses of data reported on by Pellizzari et al. (1992).
negative slope, is shown in Figure 7-35. There clearly is no relationship between the pooled
PEM and SAM variables for this data set. The statistical explanation for the negative
correlation and slope (PEM decreases with increasing SAM) is that one of the observations
(PEM = 273 jig/m3, SAM = 48 /-ig/m3, for House 9, Day 10, person 1, as shown in
Table 7-21a) is an outlier (273 /-ig/m3 > mean + 3*SD). Removal of this single datum
point changes both the correlation and the slope to slightly positive values of similar
magnitude. Because of the insignificance of the slope and correlation, further adjustments
for measurement error do not make sense.
7-143
-------
200
150
n
I
I 100
50
50 100 150
Ambient SAM ng/m3
200
Figure 7-34. PTEAM mean 24-h PM10 data compared for personal PEM and SAM.
Source: U.S. EPA reanalyses of data reported on by Pellizzari et al. (1992).
7.6.4 Discussion of Statistical Analyses: Mean PEM Versus Mean SAM
The Beijing study had an insignificant positive slope and the Azusa study gave an
estimated slope less than zero that becomes insignificant positive with the removal of one
outlier. Possible explanations for the low slope of the Beijing study may be related to the
unusually low ratio of PEM to SAM of order 0.4. Either the SAM PM3 5 monitor that was
used may have been influenced by a local PM source, and thereby was not representative of
the Beijing locality where the subjects worked and lived, or the air exchange between indoors
and outdoors during the winter period was greatly minimized for personal comfort.
In the Beijing dataset of 44 pairs of simultaneous SIM and SAM (Table 7-43) only one
PM3 5 PEM value was greater than SAM, as opposed to Azusa where in the 50 pairs of
simultaneous SIM and SAM (Table 7-21b) only six PM2 5 PEM values were less than SAM.
On a day where SAM PM3 5 reached 690 /ig/m3 in Beijing, seven simultaneous PEM values
all ranged between 110 ng/m3 and 320 /ig/m3. In relation to Figure 7-16, these PEM/SAM
ratios between 0.16 and 0.45 correspond to low air exchange rates of order 0.1 to 0.3 air
changes per hour. In the tightly-sealed poorly-heated building where all the subjects worked
7-144
-------
TABLE 7-48. AVERAGE 24-HOUR PM10 PERSONAL EXPOSURE DATA
COMPARED WITH THE PEM-SAM SITE EXPOSURE DATA
FOR RIVERSIDE, CALIFORNIA (/tg/m3)
Period
1
3
5
7
9
11
15
17
19
21
23
25
27
29
31
37
39
41
43
47
49
51
53
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
91
93
95
Average Personal
48.3
83.6
108.6
88.3
68.3
121.0
68.2
95.8
102.5
116.8
160.5
97.7
72.2
107.6
103.0
165.3
144.4
135.6
168.2
173.8
144.9
65.0
76.7
110.9
78.4
136.1
103.1
142.4
163.6
153.7
144.2
150.6
125.4
112.1
63.7
67.5
102.2
92.0
100.0
88.9
113.0
82.4
97.3
PEM-SAM Site
35.1
41.7
56.9
64.1
51.7
55.8
56.0
69.1
92.0
108.2
126.4
79.4
60.7
52.9
87.4
66.8
106.2
138.5
107.5
175.9
112.9
77.9
42.8
17.6
46.7
61.1
78.4
77.9
127.6
150.4
147.4
166.4
139.6
59.2
42.7
61.4
75.8
35.7
65.3
75.3
122.7
48.8
57.1
Source: U.S. EPA-calculated 24-h averages, based on 12-h data reported on by Pellizzari et al. (1992).
7-145
-------
TABLE 7-49. RESULTS OF THE LINEAR REGRESSION
ANALYSIS OF THE EXPOSURE DATA FROM AZUSA, CALIFORNIA
Variable
Intercept
Slope
Covariance Matrix of Parameter Estimates
Intercept
Slope
Log-likelihood = -263.4
Beta
119.1
-0.054
Intercept
' 189.7
-2.543
Std. Error Beta
13.77
0.201
Slope
-2.543
0.040
ANOVA Table
Source
Regression
Error
TOTAL
R-squared = 0.0015
Sum of Squares
111.2
76590
76700
Mean Square Error
55.6
1531.8
1475.1
D.F.
2
50
52
F-Value
0.0363
Source: U.S. EPA reanalyses of data reported on by Wiener et al. (1990).
300
LLI
Q.
° 200
Q. 100
•
50 100 150
PMio Ambient SAM ng/m3
200
Figure 7-35. Plot of ambient and personal monitoring PM10 data from Azusa, CA and
calculated (slightly negative slope) regression line, which becomes positive
if single outlier value (/} is deleted.
Source: U.S. EPA reanalyses of data reported on by Wiener et al. (1990).
7-146
-------
during the Beijing winter, a small variation in air exchange could result in a relatively large
difference in the indoor PM, which would result in PEM that appears to be uncorrelated with
SAM. If a contribution of PM generated by personal activity and ETS is subtracted from the
PEM values then the estimated air exchange rates would be even lower. The remaining
discussion will be based on the other three studies, realizing that the discussion is not
supported by these two studies.
The major conclusions which can be reached from the remaining three studies are as
follows.
(1) The average of several ambient monitors correlates better with mean personal
exposure than does an individual site (as would be predicted by the Central Limit
Theorem).
(2) The average of several personal monitors correlates better with mean ambient
exposure than does the ensemble of individual monitors.
(3) There is no evidence of the existence of a maximum (ceiling) correlation between
personal and ambient measurements. The only study with fixed multiple (n > 2)
ambient SAM locations and multiple personal monitors is the Phillipsburg, NJ,
study. The estimated correlation adjusted for measurement error was 0.97. The
true (unknown) correlation between an infinite average of personal monitors with
an infinite average of fixed site monitors may be different (smaller) in other
locations, but we do not have the data to evaluate that.
(4) The correlation coefficient is probably the best measure of association between
personal and ambient measurements. It can be used independent of the regression
technique or model and does not assume a distributional form. The "percent of
variation explained" as derived from orthogonal regression is not comparable to
any measure used for other models.
(5) The choice of a model (linear, linear with lognormal error, orthogonal) makes less
difference than the adjustment for measurement error.
(6) Based on the results of the Phillipsburg, NJ, analysis, one or more fixed site
monitors can do an excellent job of predicting the average of all personal exposures
(if they could be measured) even though the prediction for most individual
exposures is quite poor. This is also supported by the Tokyo, Japan, data set
(Tamura et al., 1996). The other data sets did not provide adequate information to
either confirm or deny this conclusion.
The value of the improvement of the mean PEM relationship to SAM is that it provides
a better visualization that helps in understanding how mean PEM varies with SAM. It thus
provides a measure of the validity of the use of a daily PM SAM as a surrogate for the mean
7-147
-------
PM PEM in the community for nonsmokers. It is clear that the uncertainty in predicting
mean personal exposure PM is much smaller than the uncertainty in predicting the personal
exposure PM for a nonsmoking individual when we note that the means have a much smaller
variability about the line as shown in Figures 7-31, 7-32, and 7-34.
There appears to be two distinct categories of cross-sectional exposure studies that were
examined: In the first type of study, such as Lioy et al. (1990), Clayton et al. (1993), and
Tamura et al. (1996), there is a significant R2 between individual PM PEM and PM SAM.
In this category, there is an appreciable improvement in correlation between the mean PEM
and SAM. It has been suggested that these cases with higher correlation of PEM PM with
SAM PM may arise where the fine portion of the ambient PM (PM2 5) is highly variable
from day-to-day, and the ambient coarse fraction is relatively constant (Wilson and Suh,
1995). In an urban area, the fine particle composition and the fine particle concentration are
often highly correlated from site-to-site on any given day. This is due, in part, to the gas
phase reactions of SOX and NOX, associated with regional sources, to produce sulfates and
nitrates in the submicron range. Because of the long residence times of these species due to
their negligible deposition velocities, they are well mixed throughout the air mass (Suh et al.,
1995; Burton etal., 1996).
On the other hand, ambient coarse particles are generated locally, and they have higher
deposition velocities than the fine particles. Their impact may then be limited by fallout to a
locality downwind of their emission point, as they are not readily transported across an urban
area. Therefore, during an air pollution episode, people living in an urban area may be
exposed to fine PM of similar chemical composition and concentrations, whereas they will be
exposed to coarse PM of ambient origin with a chemical composition that can depend on the
location of the exposure. Because ambient PM penetrates readily into a nonambient setting,
the correlation between the mean PM2 5 PEM and PM2 5 SAM would be high because all the
people would have similar exposure to the ambient fine PM - plus exposure to indoor
generated PM2 5 which may have less fluctuation in the absence of smoking.
In the second type of study, such as Sexton et al. (1984), Spengler et al. (1985), and
Wiener et al. (1990), there is negligible correlation between individual PEM PM and SAM
PM, and consequently there will be little correlation between their mean PEM and the SAM.
In these cases, if the fine fraction is not an appreciable portion of the ambient PM, or there
7-148
-------
are significant indoor sources, then the correlations between mean PM PEM and PM SAM
will be lower and possibly not significantly different from zero.
7.7 IMPLICATIONS FOR PARTICULATE MATTER AND
MORTALITY MODELING
PM related mortality may be specific to the most highly susceptible portion of the
population. Such a cohort may be the elderly people with the most serious chronic
obstructive pulmonary disease (COPD) and cardiac insufficiency. Smithard (1954) relates
the findings of Dr. Arthur Davies (Lewisham coroner) who autopsied 44 people who died
suddenly during the 1952 London Fog:
"The great majority of deaths occurred in people who had pre-existing heart and lung
trouble, that is to say they were chronic bronchitic and emphysematous people with
consequent commencing myocardial damage. The suddenness of the deaths, Dr. Davies
thought, was due to a combination of anoxia and myocardial degeneration resulting in
acute right ventricular dilatation."
Mage and Buckley (1995) hypothesized that these people with compromised cardio-
pulmonary systems may be relatively inactive, while selecting to live in homes or
institutional settings without sources of indoor pollution. When their tune is spent in clean
settings (e.g. where smoking is prohibited), they would have little exposure to PM other than
from the ambient pollution that intrudes into their living quarters (Sheldon et al., 1988a,b).
The exposure to PM of this cohort, would be highly correlated with PM SAM, and so would
be their mortality, if this ambient PM was reactive in their pulmonary tracts as described by
West (1982). However, there have been no results reported of an exposure study done on
people with COPD who correspond to the Lewisham mortality cohort. The cohort of five
elderly housewives and two male retirees in Tokyo (Tamura et al., 1996) may come close to
this susceptible cohort. Individual PM PEM of people outside these cohorts, who could be
relatively insensitive to ambient PM, might not be significantly correlated with PM SAM, as
reported in most of the other studies of nonsmokers cited in Table 7-26. This suggests a
model to relate PM and mortality as follows. Let any person (j) on a given day have a
probability of mortality, p(m) = kj Xj, where kj is the unit probability of mortality per /ig/m3
of PM per day, .Xj j& the daily average exposure to PM, /ig/m3, independent of kj. Let us
7-149
-------
assume that each individual (j) has their own personal value of fc that can vary from day-to-
day with changes in their respiratory health, such as a transient pulmonary infection (West,
1982).
The expectation of total mortality (M) in a community of size N can be shown to be the
summation of k X over all individuals (j = 1 to N) as follows:
M = E kj Xj (7-31)
If kj is independent of Xj, then we can define K as (1/N) E kj, and the mean community
exposure X as (1/N) E Xj, and it follows
M = NKX (7~32)
This implies that, given a linear relationship of mortality with PM PEM exposure (X)
as assumed in most studies discussed in Chapter 12, the expected mortality is proportional to
the mean community personal exposure to PM. The individual in the community, on any
given day, with the highest probability of dying from a PM exposure related condition is that
individual with the highest product kj Xj, not necessarily the highest exposed individual with
the maximum value of Xj (West, 1982).
The Phillipsburg, NJ, data set is a case in point. In this study, three subjects had
excessively high PEM PM. These values were caused by a hobby involving welding in a
detached garage (971 ^g/m3), a home remodeling activity (809 jug/m3) and usage of an
unvented kerosene heater (453 pig/m3). Excessive PM generating activities are not expected
of elderly people who may have compromised pulmonary systems. In fact, the elderly and
infirm husband of the remodeler had a personal exposure of 45 /xg/m3 on the day of the
remodeling activity. The indoor monitors in the homes of the welder and remodeler only
recorded 55 ^g/m3 and 19 /wg/m3, respectively, during those events, indicating the specificity
of the high exposure to only the individual involved. These three outliers were removed
from the analysis and were replaced by the procedure for missing data of section 7.6.2.1,
which estimates their exposures as if they had not done those specific activities responsible
for their noncharacteristic exposures (see Table 7-37). This procedure is reasonable, since it
7-150
-------
is unlikely that these activities would be performed by individuals with pulmonary conditions
similar to those of the Lewisham mortality cohort (Smithard, 1954). As shown on
Table 7-42 and Figure 7-32, the regression improves markedly to a value of R2 = 0.914.
It is this relation of the average PM PEM exposure to PM SAM concentration, as
shown in Figure 7-32 that may be a better representation of the true situation underlying the
PM vs mortality relationships because of the "healthy worker" effect. Chronically ill people
who are sensitive to PM might change their behavior to minimize their exposure to irritants.
Consequently, healthy people with high PEM PM measures in occupations and indoor
settings can cause the regression R2 between PEM and SAM for nonsmokers to be low, but
they may not be the individuals at highest risk of the acute effects of PM exposure.
7.7.1 Relative Toxicity of Ambient Particulate Matter and Indoor
Particulate Matter
In the previous sections the SAM PM was evaluated as a predictor of PEM PM of
nonsmokers on the implied basis that the health effects of PM were only mass dependent,
and independent of chemical composition. It was shown in Table 7-26 that many early PM
studies of PEM had a low correlation between PEM and SAM on a cross-sectional basis that
was often not significantly different from zero. But, in the later studies (Tamura et al.,
1996; Lioy et al., 1990), a significant relationship was observed between PEM and SAM on
an individual basis. Further analysis showed that on a daily basis, SAM would appear to be
a good predictor of mean community exposure to ambient PM10 of nonsmoke exposed people
from the results of the Tokyo, Japan; Riverside, CA; and Phillipsburg, NJ; studies.
However, there can be a large difference in toxicity of PM per unit mass which is related to
the chemical composition, solubility and size of the particles. For example, mercury (Hg)
and arsenic (As) have significantly different toxicities in their inorganic and organic forms.
Hexavalent chromium (Cr) is more toxic than trivalent Cr. Anthropogenic PM, from
combustion of fossil fuels, is much more toxic than PM of natural origin (Beck and Brain,
1982; Mage et al., 1996). Fine urban particulate matter generated by coal smoke during the
1952 London Fog at concentrations of order 2,000 /xg/m3 caused thousands to die (Holland et
al., 1979; United Kingdom Ministry of Health, 1954) but 2,000 /ig/m3 of soil dust from dust
storms (Hansen et al., 1993) would not have been as deadly.
7-151
-------
Soil constituents that are tracked-in to a home on shoes, and are subsequently
resuspended, contribute to the personal cloud (Roberts et al., 1990; Thatcher and Layton,
1995). "Even if this crustal PM is relatively inert, its presence in the lung potentiates the
toxicity of the anthropogenic particles because it increases the residence time of the more
toxic PM (WHO, 1995)" (Mage et al., 1996). This increase in soil constituents was also
shown in the PTEAM study (Ozkaynak et al., 1996) on Figure 7-22 "by observation that
nearly all [soil] elements were elevated in personal samples" but sulfur, which is in the
ambient fine mode, was not a personal cloud constituent. This is consistent with the
observations of Wilmoth et al. (1991) that "extremely small particles (below two
micrometers) require local airflow (sampling) velocities near 100 miles per hour [45 m/s] to
overcome surface attraction forces and dislodge [them] for sampling".
Figure 7-36 shows an example of resuspension of Pb in a Denver, CO, home
(Moschandreas et al., 1979). During the one-week sample, a wind shift brought a clean air
mass to below 0.01 /ig/m3. In this time period, the average indoor Pb dropped from
0.085 to 0.048 /xg/m3. The residual 0.048 ^g/m3 represents the effect of resuspension by
human activity. When the wind shifted again, and ambient Pb rose to 0.360 /xg/m3 the
indoor Pb rose to 0.180 /*g/m3. Note the peaks in the indoor concentration of Pb up to and
above 0.10 /ig/m3 during the clean air period which are indicative of variations in
resuspension by human activities.
There is also some indication in laboratory animal studies, using transpleural
catheterization and intratracheal instillation, that products of fossil fuel combustion are more
acutely toxic to animals than wood smoke and soil constituents (U.S. Environmental
Protection Agency, 1982, Table 12-6; Beck and Brain, 1982). Although these laboratory
animal studies may have no direct relation to toxicity in humans, they provide an indication
of their relative toxicity in animals when administered by those two routes.
In summary, there is evidence that not all PM constituents have the same toxicity per
unit mass. These differences are due to differences in aerodynamic diameter and chemical
composition. As shown on a Venn diagram (Figure 7-37, Mage [1985]), the focusing of the
description of a PM10 exposure increases the ability to estimate the potential toxicity of the
exposure. In the sequential description given below, the uncertainty in the toxicity of the
mixture is decreased as more information is provided.
7-152
-------
0.90
I
o
To 0.10
8
o
O
0.01
I I I
Pb Outdoors
V
0.90
c
g
to 0.10
o
O
0.01
\ I l
Pb Indoors
0.90
0.10
40 80 120 160 "" 0 40 80 120 160
Time, hours Time, hours
Figure 7-36. Comparison of indoor and outdoor concentrations of lead in a home in
Denver, October 1976, for 1 week, starting at 1600 h. Mean values are
given by horizontal bars.
Source: Moschandreas et al. (1979).
0.01
1. 2 /ig/m3 of PM10.
2. 2 /ig/m3 of PM10 in the size interval 2 to 2.5 /mi.
3. 2 /ig/m3 of PM10 in the size interval 2 to 2.5 /un, 50% of automotive origin and
50% of indoor source origin.
4. 2 /ig/m3 of PM10 in the size interval 2 to 2.5 /im, 50% of automotive origin and
50% of indoor source origin, 0.5 /ig/m3 of Pb, 0.5 /xg/m3 of BaP and 1 /ig/m3 of
unspecified inorganic material.
As applied to human exposure to PM, this concept of differential toxicity suggests that
data collections might benefit by providing data that would allow the toxicity of a PM
exposure to be evaluated in terms of chemical information, in addition to the mass collected
per unit volume.
7-153
-------
Figure 7-37. Venn diagram (Mage, 1985) showing focusing of information to more
completely specify toxicity of a given PM mixture: (1) universe of all
possible mixtures of PM with concentration of 2 /ig/m3; (2) subuniverse of
all combinations of PM with concentration of 2 /*g/m3 in size interval
2.0 to 2.5 pm; (3) subuniverse of all combinations of PM with
concentration of 2 jig/m3 in size interval 2.0 to 2.5 pm AD with 50% of
automotive origin and 50% from indoor sources; and (4) subuniverse of all
combinations of PM with concentration of 2 /tg/m3 in size interval 2.0 to
2.5 fim AD with 50% of automotive origin and 50% from indoor sources;
25% Pb, 25% BaP and 50% unspecified inorganic materials.
7.7.2 Summary: Linkage of Ambient Concentrations of Participate
Matter to Personal Exposures to Particulate Matter
As described by Wilson and Suh (1995), total exposure to ambient PM (X.,e) of any
given size range is equal to the summation of exposures to ambient PM over both ambient
(Xa) and nonambient (Xna) microenvironmental conditions. Total exposure to PM is equal to
Xae plus exposure to nonambient PM concentrations generated independently of personal
activities (Xnai) and nonambient PM concentrations generated dependently on personal
7-154
-------
activities (Xnap) which may correspond to smoking and the personal cloud effect. For a
period (T) of constant ambient PM a subject spends time Ta outdoors and time (T - Ta) in
n different nonambient microenvironments. The total exposure to ambient PM can be
expressed as:
„ [TaXa + (T-Ta)XJ „
For a nonambient microenvironment, the equilibrium concentration of ambient particles
in it will be equal to
Xa P a
X = —
118 (a + *)
where P = penetration fraction of PM in the ambient air entering the nonambient
microenvironment,
a = air exchange rate, h"1
k = deposition rate (a function of AD), h"1.
As discussed in section 7.2, the penetration factor P is virtually equal to 1 for all
particles less than 10 too. (Thatcher and Layton, 1995) and the fraction of Xj,a/Xa is as shown
on Figure 7-16. Combining equations 7-33 and 7-6, we obtain
Xa[Ta * SWfrj + *)] (7-34)
ae
where T - Ta = £ tj, total time spent indoors,
j = 1 to n, index of indoor microenvironment visited.
Defining z as the overall ratio of exposure to ambient PM (X^) to the ambient
concentration (Xa), so that Xae = z Xa, letting v = Ta/T, the fraction of time the subject is
outdoors, we obtain the average relation,
7-155
-------
d-y) « , (7-35)
a + A:
where I—-— is a time weighted average.
a + k
As shown on Figure 7-38, on a daily basis, z can vary by an appreciable amount by
spending a fraction (y) of time outdoors. For y = 1/3 (8 h), exposures to fine ambient
PM2 5 increase by 100% for people living in homes with an ah" exchange rate a = 0.1 h"1.
The total exposure (X) can now be written as,
x = z x + j J (7-36)
a
where £ [(Xnai)j + (Xnap)j] tj / T = |8, the personal exposure hicrement produced by sources
that do not influence the ambient concentration as measured by a stationary ambient monitor
(SAM). Simplifying, we can rewrite Equation 7-36 as,
X = z Xa + p (7-37)
which gives a physical significance to the slope and intercepts of the regressions of PEM (X)
versus SAM (Xa) as discussed hi Section 7.6.
The values of z, which depend on y, a, k and P can be determined from their
independent measurements described previously. P = 1 for all PM < 10 pm A.D.
(Thatcher and Layton, 1995) and y = 0.074 [U.S. mean fraction of tune spent outdoors per
day; U.S. Environmental Protection Agency (1989)]. From PTEAM (Wallace et al., 1993),
a = 0.9 h"1 as a median value for night and day. Ozkaynak et al. (1993a,b) have determined
values for k as follows:
For sulfatefc = 0.16 hA
For PM2 5 k = 0.39 h'1
ForPM10fc =1.01 h'1
7-156
-------
Air exchange rate (air changes per hour)
Figure 7-38. Fraction of ambient PM to which people are exposed (z) as a function of
fraction of time outdoors (y) and air exchange rate for fine (PM2 5) and
coarse (PM10 - PM2t5) particles.
From the equation z = y + (1 -y) P a/(a + k)
for sulfate, z = 0.074 + 0.926 (0.9)7(0.9 + 0.16) = 0.859
for PM2 5 it is z = 0.074 + 0.926 (0.9)/(0.9 + 0.39) = 0.720
for PM10 it is z = 0.074 + 0.926 (0.9)7(0.9 + 1.01) = 0.512
These predicted values match closely to the reported values of z cited in this Chapter 7 as
follows:
Suh et al. (1993) report z = 0.87 ± 0.02 (r2 = 0.92) for SO4=
Tamura et al. (1996) [Table 7-32] report z = 0.466 (r2 = 0.905) for PM10,
Lioy et al.(1990) [Table 7-44] report z = 0.546 (r2 = 0.91) for PM10
It is not known what the average values of y and a were for the State College, PA, and
Phillipsburg, NJ, cohorts of Suh et al. (1995) and Lioy et al. (1990), or the Tokyo, Japan,
7-157
-------
cohort of Tamura et al. (1996). Therefore these results can only be considered as tentative
at this time.
The parameter 6 in Equation 7-37 represents the contribution to personal exposures
(PEM) from nonambient sources both independent of and dependent on personal activities.
In general the composition of the PM emitted by indoor sources (or resuspended by human
activity) that influence 6 will be different from the PM emitted into the ambient atmosphere
from sources controlled by State Implementation Plans (SIP)s. The nonambient /*E emissions
are from the activities of the subject (cooking, heating, smoking, resuspension of housedust,
hobbies, etc.) or independent activities of others in the same juE that are independent of the
ambient concentration (Xa).
For the situation in Tokyo (Tamura and Ando, 1994; Tamura et al., 1996) the
PM10 PEM vs PM10 SAM correlation is good for all subjects individually, as well as their
average PEM, because the data were collected in a manner to minimize 6. These data for
the seven nonsmoke exposed elderly subjects were culled to remove observations which were
influenced by overt particle generating activities such as visitors' smoking, burning of
incense, and burning of antimosquito coils. The custom of taking off shoes on entry into
Japanese residences and use of "tatami" mat flooring minimized resuspension of PM less than
10 ^m AD, although indoor activity did raise dust above 10 /im AD (Tamura et al., 1996).
For the U.S. cities of Phillipsburg, NJ, and Riverside, CA, with large numbers of
observations, the correlations of PEM vs SAM for PM10 were significantly positive but less
than for Tokyo, Japan, possibly due to the passive smoking and house dust generation in the
Riverside, CA, and Phillipsburg, NJ, studies. Even so, in Riverside, CA, ambient sources
provided about 67% of PM10 mass measured indoors (Ozkaynak et al., 1996). Finally, the
results of the studies in Beijing, China, and Azusa, CA, gave positive correlations of PEM
and SAM that were not significantly different from zero (If one outlier is included in the
Azusa analysis, the PEM vs SAM correlation is negative). These low correlations may be
due to low air exchange rates in Beijing during the winter as evidenced by the low
PEM/SAM ratios, and the presence of indoor sources in Azusa, as evidenced by the PEM
almost double the SIM or SAM. These latter studies are typical of the results in other U.S.
cities such as Kingston and Harriman, TN (Spengler et al., 1985), where ambient pollution is
relatively low, so that the personal cloud and indoor source effects predominate.
7-158
-------
In summary, it appears that the first exposure conclusion of the previous PM criteria
document (U.S. Environmental Protection Agency, 1982), quoted in section 7.1.3, has been
generally supported by recent studies. If the relation of equation 7-35 which appears to
predict the observed relations in several studies cited in this document is a reasonable model
of the personal exposure to ambient PM, then that conclusion can be adjusted more
specifically as follows:
1 . Long-term personal exposures to fine PM sulfates of outdoor origin may be
estimated by approximately 85% of the sulfate in the fine fraction of ambient PM.
2. Long-term personal exposures to PM < 2.5 /tm A.D. of outdoor origin may be
estimated by approximately 70% of the PM < 2.5 /xm A.D. in the ambient PM.
3. Long-term personal exposures to PM < 10 ^m A.D. of outdoor origin may be
estimated by approximately 50% of the PM < 10 /mi A.D. in the ambient PM.
These relationships still need to be validated in populations other than those from which
they were derived. Variations will exist for cohorts with different fractions of time spent
outdoors (y) and air exchange rates (a) than the values chosen for representing the national
averages.
Ambient concentrations of PM10 measured at properly sited monitoring stations are
highly uniform in urban areas (Burton et al., 1996, Suh et al., 1995), have no losses in
penetration into /xEs (Thatcher and Lay ton, 1995), and may be highly correlated with
personal exposures to PM10 (Tamura et al., 1996) where indoor sources of PM10 are
minimal. Even where indoor sources of PM10 exist, they tend to produce different chemical
species than those found in the PM2 5 fraction, as shown by the sulfates which do not appear
in the personal cloud (Ozkaynak et al., 1996; Suh et al., 1993).
It is therefore concluded that the presence of variable indoor sources of PM10 tends to
lower the observed correlations between PEM PM10 (derived from both ambient and
nonambient sources) and SAM PM10 (derived only from ambient sources) and even achieve
values nonsignificantly different from zero. Consequently, the use of an ambient
concentration of PM2 5 or PM10 in relation to daily changes of mortality and morbidity may
be a reasonable surrogate for the average personal exposure of people in the community to
the PM2 5 or PM10 generated by ambient sources. "The consistently higher R2 values
observed in the longitudinal regressions support the epidemiological findings more strongly
7-159
-------
than the poor correlations noted in the standard cross-sectional regressions" (Wallace, 1996),
as per the U.S. EPA reanalyses shown in Tables 7-36 and 7-42.
7.8 SUMMARY AND CONCLUSIONS
For PM, the total exposure of an individual consists of the summation of the
individual's exposure to PM in a variety of microenvironments. This typically includes
exposures while (a) outdoors and (b) indoors (at-home or in microenvironments such as
shops and public buildings; at-work in an office or factory; and in a vehicle). The principle
of superposition is a useful mechanism to visualize the summation process. A simplification
of this summation process for an arbitrary individual, described in detail by Figure 7-30, is
illustrated in Figure 7-39. In each sub-figure (a to d) of Figure 7-39, the shaded area
represents PM exposure (in /xg-h/m3) of ambient origin appropriately indexed by a central
(community) monitoring station. The clear area represents that PM exposure (in jttg-h/m3)
the individual is exposed to which is not characterized by the PM measured at the central
monitoring station.
Figure 7-39a shows that while outdoors, the subject can be exposed to (a) widely
dispersed ambient PM that is represented by the community monitoring station and,
independently, also to (b) proximal PM that does not markedly influence the monitoring
station reading (from tobacco smoking, standing over a grill at a backyard barbecue,
"personal cloud", etc.). For example, in the PTEAM Study, backyard concentrations of
PM2 5 and PM10 had a correlation on the order of 0.9 with a central monitoring station.
Also, in Tokyo (Figure 7-25), outdoor concentrations immediate to the homes of subjects
studied by Tamura et al. (1996) had a correlation of 0.9 with the local ambient monitoring
station.
Figure 7-39b shows that, while indoors (not at work), the subject can be exposed not
only to (a) ambient PM (represented by the monitoring station) that infiltrates indoors but
also to (b) PM of indoor origin that does not influence the ambient monitoring station reading
(from smoking, cooking, vacuuming, "personal cloud", etc.). Obviously, the proportion of
exposure to PM of ambient origin versus that of indoor origin can vary widely, depending
on: outdoor concentrations of the ambient PM; the air exchange rate of indoor spaces; the
7-160
-------
a.
x
UJ
24 hours
-14 hours
(a) Outdoors
Figure 7-39.
(b) Indoors
At-home, etc.
(Non-work)
(c) Indoors
At-work
(d) In-traffic
(e) Total
Exposure
Conceptual representation of potential contributions of PM of ambient
origin and PM generated indoors to total human exposure of a
hypothetical individual. The total personal exposure (e) of that
individual will consist of the sum of exposures to widely dispersed PM
of ambient origin (shaded areas) characterized by measurements at a
centrally-located community monitoring site and all other exposures
(non-shaded areas) to proximally generated particles either outdoors
or indoors in situations designated for (a), (b), (c), and (d). Times of
exposure in the various situations reflect typical time-action patterns
for U.S. adults. Depicted exposures to PM of non-ambient origin may
vary greatly from those shown there for qualitative impression only,
depending on various factors described in the text.
presence or absence of indoor PM sources; and the removal efficiency of indoor sinks for
specific constituents of the respective PM of ambient or indoor origin. In the absence of
major indoor PM sources (e.g., smoking), the percentage of total exposure contributed by
PM of ambient origin can be substantial. For example, as shown in Table 7-2, between 60%
and 80% of indoor air PM was estimated by source apportionment methods to be of ambient
origin in non-smokers' homes in two U.S. cities (Steubenville, OH; Portage, WI) included in
the Harvard Six-City Study. Even in smokers' homes, it was estimated that 60% of the non-
smoking related PM was of ambient origin in the same two cities. The New York State
7-161
-------
ERDA Study (see page 7-23) also showed that, in homes without combustion sources, 60%
of the total indoor PM2 5 was from outdoor sources. For homes with smokers in the same
study, about 66% of the non-tobacco smoke indoor particles were found to be of ambient
origin. Similarly, based on the Tamura et al. (1996) data shown in Figure 7-24, it can be
estimated that as much as 80% of the measured indoor PM10 in Japanese homes without
combustion sources was of ambient origin.
Figure 7-39c shows that while indoors at work the subject can also be exposed to
(a) ambient PM (represented by the community monitoring station) which infiltrates indoors,
and (b) PM of indoor origin that does not influence the monitoring station reading (from
smoking, welding, machining, "personal cloud", etc.). It can be expected that, for office-
type work, similar relationships as described above for the other indoor conditions (e.g.,
smokers' or non-smokers' homes) would apply. However, for work conditions involving
particle generation (e.g., wood working, welding, mining, etc.), the personal exposure of
"dusty-trade" workers to indoor-generated particles can be several orders of magnitude
greater than their exposure to indoor particles of ambient origin.
Figure 7-39d shows that while in traffic, the subject can be exposed to (a) ambient PM
that is represented by the monitoring station (via ambient air infiltration into the vehicle), and
(b) PM of on-board or proximal vehicle origin that does not directly influence the community
monitoring station reading (from smoking, exhaust penetration from nearby vehicles, etc.).
For example, in one study, Morandi et al. (1988) found that the average concentration of
PM3 5 in motor vehicles in traffic (55 /*g/m3) was 60% higher than the average outdoor
PM3 5 level (35 jig/m3).
Figure 7-39e is a simple rearrangement of the shaded and non-shaded areas to show
that an individual's total daily exposure (/ig-h/m3) can be thought of as the sum of two
quantities: (a) exposure to PM characterized by the local community monitoring station, and
(b) exposure to PM of immediately proximal origin that varies independently of the PM
measured at the monitoring station. Conceptually, everyone in the community will be
exposed to the mix of PM represented by the shaded area that is characterized by the local
monitoring station, due to their time outdoors and the penetration of PM into indoor
microenvironments and vehicles. However, not everyone in the community will be exposed
to the identical mix of PM represented by the clear area, because this exposure and its
7-162
-------
chemical composition is idiosyncratically related to their individual habits and practices
(smoking, home cleanliness, hobbies, "personal cloud", etc.), their occupation (home maker,
student, office worker, welder, miner, etc.) and their mode and usage of transportation (car,
bus, train, etc.).
Evaluation of information useful in determining relative contributions of ambient
(outdoor) and non-ambient (indoor) particles to total human exposures leads to the following
key conclusions:
(1) For PM, the ambient environment can be a major source of indoor pollution due
to air exchange and infiltration. Whether the ambient is the dominant source of
indoor PM depends on the relative magnitude of indoor sources of PM.
(2) For PM of size fractions that include coarse particles, some studies have identified
statistically significant relationships between personal exposures and ambient
concentrations, while other studies have not, probably due to overwhelming effects
of indoor sources, "personal clouds" and other individual activities.
(3) Cross-sectional regressions of personal exposure on outdoor PM2 * and PM10
concentrations generally explain less than 25% of the variance (R^ < 0.25).
However, longitudinal regressions for each person in the study (in those cases
where the person was measured repeatedly) often show much better relationships
between personal exposure and outdoor air concentrations.
(4) Personal exposures to outdoor-generated PM of any size fraction < PM10 can be
estimated from the fraction of time spent indoors and an estimate of the air
exchange rate and deposition rate associated with that size fraction.
(5) The relationship between ambient concentration and personal exposure is better for
finer size fractions of ambient PM, than for coarser PM. Higher correlations
between ambient concentration and personal exposures have been found for fine
PM constituents (such as sulfates) without indoor sources.
(6) For a study population of nonsmokers in which there is a significant positive
correlation between personal exposures and ambient concentrations, the ambient
concentration can predict the mean personal exposure with much less uncertainty
than it can predict the personal exposure of any given individual.
(7) For Riverside, CA, where 25% of the nonsmoking population was estimated to
have personal exposures on the day they were monitored that exceeded the 24-h
National Ambient Air Quality Standard for PM10 of 150 /ug/rn3, approximately
50% of this mass was found to be of ambient origin.
(8) The personal exposure to PM of smokers is dominated by the milligram quantities
of PM inhaled with each cigar, pipe, or cigarette smoked.
7-163
-------
(9) For the U.S. studies, almost all personal exposures to PM are greater than the
ambient concentrations.
(10) The penetration factor from outdoors to indoors for both PM2 5 and PM10 was
found to be unity in the PTEAM and Thatcher and Layton (1995) studies.
(11) Deposition rates in indoor microenvironments for PM10 and its fine and coarse
fractions were determined in the PTEAM Study. Similar deposition rates were
found by Thatcher and Layton (1995). Deposition reduces exposure to ambient
PM; coarse mode PM is removed more rapidly than PM2 5, which is removed
more rapidly than sulfate.
(12) Under equilibrium conditions, residential indoor concentrations of outdoor-
generated PM of any size fraction < PM10 can be estimated for any given air
exchange rate, by employing the deposition rate associated with that size fraction.
(13) For PM, studies have detected a "personal cloud" related to the activities of an
individual who may generate significant levels of airborne PM in his/her vicinity
which may not be picked up by an indoor PM monitor at a distance.
(14) There is some evidence that nonsmoke-exposed elderly people have lower
residential indoor PM concentrations than the simultaneous ambient PM
concentrations, as opposed to the general population who have indoor PM
concentrations comparable to or greater than ambient PM concentrations.
(15) Measured indoor air concentrations of PM2 5 and PM10 generally exceed outdoor
air concentrations (often by a factor of two) except in areas where outdoor
concentrations are high (e.g., Steubenville, OH and Riverside, CA).
(16) Indoor concentrations are higher during the day than at night.
(17) Correlations between indoor and outdoor particle mass concentrations were not
significant in two of the three major studies reviewed. In the third (PTEAM)
study, they ranged between 0.22 and 0.54.
(18) Regressions of indoor on outdoor PM2 5 and PM10 concentrations generally
explain less than half of the variance (R2 < 50%) if the regressions are carried
out simultaneously on all homes in the study. However, regressions for a single
home (in those cases where homes were measured repeatedly) often have much
better indoor-outdoor relationships (R2 up to 90%). Since most epidemiological
studies deal with repeated measurements over time, "longitudinal" regressions by
individual home may be more relevant to these studies than "cross-sectional"
regressions across all homes.
(19) The largest identified indoor source of particles in both homes and buildings is
cigarette smoking. Homes with smokers have an ETS-related PM2 5 concentration
increment ranging between 25 and 45
7-164
-------
(20) The second largest identified indoor source of particles is cooking. Homes with
cooking had increased levels of PM10 on the order of 10 to 20 /ig/m3.
(21) Unknown indoor sources accounted for a substantial fraction (25%) of indoor
concentrations of both PM2 5 and PM10 in the PTEAM Study. These sources
appear to be due to personal activities, including resuspension of house dust.
(22) Variations in personal exposure due to fluctuations produced by indoor sources of
PM are independent of the variations in personal exposure produced by ambient
sources.
7-165
-------
REFERENCES
Adams, W. C. (1993) Measurement of breathing rate and volume in routinely performed daily activities [final
report]. Davis, CA: University of California, Physical Education Department, Human Performance
Laboratory; contract no. A033-205.
Afifi, A. A.; Elashoff, R. M. (1966) Missing observations in multivariate statistics: I. review of the literature.
J. Am. Stat. Assoc. 61: 595-604.
Alberts, W. M.; Brooks, S. M. (1992) Advances in occupational asthma. Clin. Chest Med. 13: 281-302.
American Academy of Allery & Immunology. (1994) Aeroallergen Monitoring Network 1994 pollen and spore
report. Milwaukee, WI: American Academy of Allery & Immunology.
Anuszewski, J.; Larson, T. V.; Koenig, J. Q. (1992) Simultaneous indoor and outdoor particle light-scattering
measurements at nine homes using a portable nephelometer. Presented at: 11th annual meeting of the
American Association for Aerosol Research; October; San Francisco, CA. Cincinnati, OH: American
Association for Aerosol Research; paper no. 3A.5.
Arlian, L. G. (1989) Biology and ecology of house dust mites, Dermatophagoides spp. and Euroglyphus spp.
Immunol. Allergy Clin. North Am. 9: 339-356.
Aso, N.; Yoshizawa, S.; Tang, H. (1993) Behavior of particles generated from floor. In: Kalliokosi, P.;
Jantunen, M.; Seppanen, O., eds. Indoor air '93: proceedings of the 6th international conference on
indoor air quality and climate, v. 4, particles, microbes, radon; July; Helsinki, Finland. Helsinki,
Finland: Indoor Air '93; pp. 43-48.
Baxter, C. S.; Wey, H. E.; Burg, W. R. (1981)A prospective analysis of the potential risk associated with
inhalation of aflatoxin-contaminated grain dusts. Food Cosmet. Toxicol. 19: 765-769.
Beck, B. D.; Brain, J. D. (1982) Prediction of the pulmonary toxicity of respirable combustion products from
residential wood and coal stoves. In: Proceedings: residential wood & coal combustion specialty
conference; March; Louisville, KY. Pittsburgh, PA: Air Pollution Control Association; pp. 264-280.
Bennett, K. M. (1983) [Letter to H. H. Hovey, Jr., New York State Department of Environmental Conservation,
regarding the national ambient air quality standards]. Washington, DC: U.S. Environmental Protection
Agency, Assistant Administrator for Air, Noise, and Radiation; March 18.
Binder, R. E.; Mitchell, C. A.; Hosein, H. R.; Bouhuys, A. (1976) Importance of the indoor environment in air
pollution exposure. Arch. Environ. Health 31: 277-279.
Burge, H. A. (1995) Bioaerosols in the residential environment. In: Cox, C. S.; Wathes, C. M., eds. Bioaerosols
handbook. Boca Raton, FL: CRC Press, Inc.; pp. 579-597.
Burton, R. M.; Suh, H. H.; Koutrakis, P. (1996) Spatial variation in paniculate concentrations within
metropolitan Philadelphia. Environ. Sci. Technol. 30: 400-407.
Chan, C.-C.; Huang, S.-K.; Chen, Y.-C.; Wang, J.-D. (1995) Personal, indoor, and outdoor concentrations of
respirable suspended particulates (RSP) and nicotine in seven smoker's families in Taiwan.
Atmos. Environ.: submitted.
7-166
-------
Clayton, C. A.; Perritt, R. L.; Pellizzari, E. D.; Thomas, K. W.; Whitmore, R. W.; Wallace, L. A.;
Ozkaynak, H.; Spengler, J. D. (1993) Particle total exposure assessment methodology (PTEAM) study:
distributions of aerosol and elemental concentrations in personal, indoor, and outdoor air samples in a
southern California community. J. Exposure Anal. Environ. Epidemiol. 3: 227-250.
Code of Federal Regulations. (1994) National primary and secondary ambient air quality standards; definitions.
C. F. R. 40: part 50, §50.1.
Cohen, B. S.; Chang, A. E.; Harley, N. H.; Lippmann, M. (1982) Exposure estimates from personal lapel
monitors. Am. Ind. Hyg. Assoc. J. 43: 239-243.
Cohen, B. S.; Harley, N. H.; Lippmann, M. (1984) Bias in air sampling techniques used to measure inhalation
exposure. Am. Ind. Hyg. Assoc. J. 45: 187-192.
Colome, S. D.; Kado, N. Y.; Jacques, P.; Kleinman, M. (1990) Indoor-outdoor relationships of particles less
than 10 ftm in aerodynamic diameter (PM10) in homes of asthmatics. In: Indoor air '90: precedings of
the 5th international conference on indoor air quality and climate, volume 2, characteristics of indoor air;
July-August; Toronto, ON, Canada. Ottawa, ON, Canada: International Conference on Indoor Air
Quality and Climate, Inc.; pp. 275-280.
Colome, S. D.; Kado, N. Y.; Jaques, P.; Kleinman, M. (1992) Indoor-outdoor air pollution relations: paniculate
matter less than 10 jtm in aerodynamic diameter (PM10) in homes of asthmatics. Atmos. Environ. Part A
26: 2173-2178.
Costle, D. M. (1980) [Letter to J. Randolph, U.S. Senate, regarding EPA's definition of "ambient"].
Washington, DC: U.S. Environmental Protection Agency, Administrator; December 19.
Coultas, D. B.; Samet, J. M.; McCarthy, J. F.; Spengler, J. D. (1990) Variability of measures of exposure to
environmental tobacco smoke in the home. Am. Rev. Respir. Dis. 142: 602-606.
Cox, C. S. (1987) The aerobiological pathway of microorganisms. New York, NY: John Wiley & Sons.
Cox, C. S.; Wathes, C. M., eds. (1995) Bioaerosols handbook. Boca Raton, FL: CRC Press, Inc.
Croft, W. A.; Jarvis, B. B.; Yatawara, C. S. (1986) Airborne outbreak of trichothecene toxicosis. Atmos.
Environ. 20: 549-552.
Grouse, W. E.; Ireland, M. S.; Johnson, J. M.; Striegel, R. M., Jr.; Williard, C. S.; DePinto, R. M.;
Oldaker, G. B., Ill; McBride, R. L. (1989) Results from a survey of environmental tobacco smoke
(ETS) in restaurants. In: Harper, J. P., ed. Combustion processes and the quality of the indoor
environment: transactions of an international specialty conference; September 1988; Niagara Falls, NY.
Pittsburgh, PA: Air & Waste Management Association; pp. 214-222. (A&WMA transactions series:
TR-15).
Cupitt, L. T.; Glen, W. G.; Lewtas, J. (1994) Exposure and risk from ambient particle-bound pollution in an
airshed dominated by residential wood combustion and mobile sources. In: Symposium of risk assessment
of urban air: emissions, exposure, risk identification, and risk quantitation; May-June 1992; Stockholm,
Sweden. Environ. Health Perspect. 102(suppl. 4):75-84.
7-167
-------
aisey, J. M.; Spengler, J. D.; Kaarakka, P. (1987) A comparison of the organic chemical composition of
indoor aerosols during woodburning and non-woodburning periods. In: Seifert, B.; Esdorn, H.;
Fischer, M.; Riiden, H.; Wegner, J., eds. Indoor air '87: proceedings of the 4th international conference
on indoor air quality and climate: v. 1, volatile organic compounds, combustion gases, particles and
fibres, microbiological agents; August; Berlin, Federal Republic of Germany. Berlin, Federal Republic of
Germany: Institute for Water, Soil and Air Hygiene; pp. 215-219.
Dempster, A. P.; Laird, N. M.; Rubin, D. B. (1977) Maximum likelihood from incomplete data via the EM
algorithm. J. R. Stat. Soc. Ser. B 39: 1-38.
Diemel, J. A. L.; Brunekreef, B.; Boleij, J. S. M.; Biersteker, K.; Veenstra, S. J. (1981) The Arnhem lead
study: II. indoor pollution, and indoor/outdoor relationships. Environ. Res. 25: 449-456.
Dockery, D. W.; Spengler, J. D. (198la) Indoor-outdoor relationships of respirable sulfates and particles.
Atmos. Environ. 15: 335-343.
Dockery, D. W.; Spengler, J. D. (1981b) Personal exposure to respirable particulates and sulfates. J. Air Pollut.
Control Assoc. 31: 153-159.
Dockery, D. W.; Schwartz, J.; Spengler, J. D. (1992) Air pollution and daily mortality: associations with
particulates and acid aerosols. Environ. Res. 59: 362-373.
Duan, N. (1982) Models for human exposure to air pollution. Environ. Int. 8: 305-309.
Duan, N.; Mage, D. T. (1996) Combination of direct and indirect approaches for exposure assessment.
J. Exposure Anal. Environ. Epidemiol.: accepted.
Dunn, O. J.; Clark, V. A. (1974) Applied statistics: analysis of variance and regression. New York, NY: John
Wiley & Sons; pp. 221-251. (Wiley series in probability and mathematical statistics).
Edmonds, R. L., ed. (1979) Aerobiology: the ecological systems approach. Stroudsburg, PA: Dowden,
Hutchinson & Ross, Inc. (US/IBP synthesis series 10).
Federal Trade Commission. (1994) Tar, nicotine, and carbon monoxide of the smoke of 933 varieties of domestic
cigarettes. Washington, DC: Federal Trade Commission.
Fletcher, B.; Johnson, A. E. (1988) Comparison of personal and area concentration measurements and the use of
a manikin in sampling. In: Vincent, J. H., ed. Ventilation '88. New York, NY: Pergamon Press;
pp. 161-165.
Fugas, M.; Wilder, B.; Paukovic, R.; Hrsak, J.; Steiner-Skreb, D. (1973) Concentration levels and paniculate
size distribution of lead in the air of an urban and an industrial area as a basis for the calculation of
population exposure. In: Barth, D.; Berlin, A.; Engel, R.; Recht, P.; Smeets, J., eds. Environmental
health aspects of lead: proceedings [of an] international symposium; October 1972; Amsterdam, The
Netherlands. Luxembourg: Commission of the European Communities; pp. 961-968; report no.
EUR 5004 d-e-f.
Fuller, W. A. (1987) Measurement error models. New York, NY: John Wiley & Sons.
Gregory, P. H. (1973) The microbiology of the atmosphere. 2nd ed. New York, NY: John Wiley & Sons.
Groves, W. A.; Hahne, R. M. A.; Levine, S. P.; Schork, M. A. (1994) A field comparison of respirable dust
samplers. Am. Ind. Hyg. Assoc. J. 55: 748-755.
7-168
-------
Guerin, M. R.; Jenkins, R. A.; Tomkins, B. A. (1992) The chemistry of environmental tobacco smoke:
composition and measurement. Chelsea, MI: Lewis Publishers.
Hansen, A. D. A.; Kapustin, V. N.; Kopeikin, V. M.; Gillette, D. A.; Bodhaine, B. A. (1993) Optical
absorption by aerosol black carbon and dust in a desert region of central Asia. Atmos. Environ. Part A
27:2527-2531.
Hasabelnaby, N. A.; Ware, J. H.; Fuller, W. A. (1989) Indoor air pollution and pulmonary performance:
investigating errors in exposure assessment. Stat. Med. 8: 1109-1126.
Heavner, D. L.; Morgan, W. T.; Ogden, M. W. (1995) Determination of volatile organic compounds and ETS
apportionment in 49 homes. Environ. Int. 21: 3-21.
Highsmith, V. R.; Hoffman, A. J.; Zweidinger, R. B.; Cupitt, L. T.; Walsh, D. (1991) The IACP: overview of
the Boise, Idaho, and the Roanoke, Virginia, field studies. Presented at: 84th annual meeting and
exhibition of the Air & Waste Management Association; June; Vancouver, BC, Canada. Pittsburgh, PA:
Air & Waste Management Association; paper no. 91-131.1.
Hodges, S. D.; Moore, P. G. (1977) Data uncertainties and least squares regression. Appl. Stat. 44: 185-195.
Holcomb, L. C. (1993) Indoor air quality and environmental tobacco smoke: concentration and exposure.
Environ. Int. 19: 9-40.
Holland, W. W.; Bennett, A. E.; Cameron, I. R.; Florey, C. du V.; Leeder, S. R.; Schilling, R. S. F.;
Swan, A. V.; Waller, R. E. (1979) Health effects of paniculate pollution: reappraising the evidence.
Am. J. Epidemiol. 110: 525-659.
Ingham, D. B.; Van, B. (1994) The effect of a cylindrical backing body on the sampling efficiency of a
cylindrical sampler. J. Aerosol Sci. 25: 535-541.
Janssen, N. A. H.; Hoek, G.; Harssema, H.; Brunekreef, B. (1995) A relation between personal and ambient
PM10. Epidemiology 6(suppl.): S45.
Jenkins, R. A.; Palausky, M. A.; Counts, R. W.; Guerin, M. R.; Dindal, A. B.; Bayne, C. K. (1995a)
Determination of personal exposure of nonsmokers to environmental tobacco smoke in the United States.
Lung Cancer: submitted
Jenkins, R. A.; Palausky, M. A.; Guerin, M. R.; Dindal, A. B.; Counts, R. W.; Bayne, C. K. (1995b) Personal
exposure to environmental tobacco smoke in workplace and away-from work settings: a 16 city case
study. In: Measurement of toxic and related air pollutants, 1995 abstracts book of an EPA/A&WMA
international symposium; May; Research Triangle Park, NC. Pittsburgh, PA: Air & Waste Management
Association; pp. 40-41.
Kamens, R.; Lee, C.-T.; Wiener, R.; Leith, D. (1991) A study to characterize indoor particles in three
non-smoking homes. Atmos. Environ. Part A 25: 929-948.
Kendall, M. G.; Stuart, A. (1961) The advanced theory of statistics, v. 2: inference and relationship. London,
United Kingdom: Charles Griffin & Co., Ltd.; pp. 378-415.
Kendrick, B. (1992) The fifth kingdom. 2nd ed. Newburyport, MA: Focus Information Group.
Kim, Y. S.; Stock, T. H. (1986) House-specific characterization of indoor and outdoor aerosols. Environ. Int.
12: 75-92.
7-169
-------
iepeis, N. E.; Ott, W. R.; Switzer, P. (1994) A Total Human Exposure Model (THEM) for Respirable
Suspended Particles (RSP). Presented at: 87th annual meeting & exhibition of the Air & Waste
Management Association; June; Cincinnati, OH. Pittsburgh, PA: Air & Waste Management Association;
paper no. 94-WA75A.03.
Koontz, M. D.; Rector, H. E. (1995) Estimation of distributions for residential air exchange rates: final report.
Washington, DC: U.S. Environmental Protection Agency, Office of Pollution Prevention and Toxics;
contract nos. 68-D9-0166 and 68-D3-0013.
Koutrakis, P.; Briggs, S. L. K.; Leaderer, B. P. (1992) Source apportionment of indoor aerosols in Suffolk and
Onondaga Counties, New York. Environ. Sci. Technol. 26: 521-527.
Kulmala, M.; Saari, H.; Raunemaa, T.; Olin, M. (1987) Indoor air aerosols: outdoor air influence on indoor air.
In: Seifert, B.; Esdorn, H.; Fischer, M.; Riiden, H.; Wegner, J., eds. Indoor air '87: proceedings of the
4th international conference on indoor air quality and climate, v. 1, volatile organic compounds,
combustion gases, particles and fibres, microbiological agents; August; Berlin, Federal Republic of
Germany. Berlin, Federal Republic of Germany: Institute for Water, Soil and Air Hygiene; pp. 564-568.
Laird, N. M. (1988) Missing data in longitudinal studies. Stat. Med. 7: 305-315.
Last, J. M., ed. (1988) A dictionary of epidemiology. 2nd ed. New York, NY: Oxford University Press; p. 56.
Leaderer, B. P.; Hammond, S. K. (1991) Evaluation of vapor-phase nicotine and respirable suspended particle
mass as markers for environmental tobacco smoke. Environ. Sci. Technol. 25: 770-777'.
Leaderer, B.; Koutrakis, P.; Briggs, S.; Rizzuto, J. (1990) Impact of indoor sources on residential aerosol
concentrations. In: Indoor air '90: precedings of the 5th international conference on indoor air quality and
climate, volume 2, characteristics of indoor air; July-August; Toronto, ON, Canada. Ottawa, ON,
Canada: International Conference on Indoor Air Quality and Climate, Inc.; pp. 269-274.
Leaderer, B. P.; Koutrakis, P.; Briggs, S. L. K.; Rizzuto, J. (1994) The mass concentration and elemental
composition of indoor aerosols in Suffolk and Onondaga Counties, New York. Indoor Air 4: 23-34.
Lebret, E.; McCarthy, J.; Spengler, J.; Chang, B.-H. (1987) Elemental composition of indoor fine particles.
In: Seifert, B.; Esdorn, H.; Fischer, M.; Ruden, H.; Wegner, J., eds. Indoor air '87: proceedings of the
4th international conference on indoor air quality and climate: v. 1, volatile organic compounds,
combustion gases, particles and fibres, microbiological agents; August; Berlin, Federal Republic of
Germany. Berlin, Federal Republic of Germany: Institute for Water, Soil and Air Hygiene; pp. 569-574.
Lebret, E.; Boleij, J.; Brunekreef, B. (1990) Environmental tobacco smoke in Dutch homes. In: Indoor air '90:
precedings of the 5th international conference on indoor air quality and climate, volume 2, characteristics
of indoor air; July-August; Toronto, ON, Canada. Ottawa, ON, Canada: International Conference on
Indoor Air Quality and Climate, Inc.; pp. 263-268.
Lehmann, E.; Rentel, K.-H.; Allescher, W.; Hohmann, R. (1990) Messung von Dieselabgas am Arbeitsplatz
[Measurement of diesel exhaust at the workplace]. Zentralbl. Arbeitsmed. Arbeitsschutz Prophyl. Ergon.
40:2-11.
Letz, R.; Ryan, P. B.; Spengler, J. D. (1984) Estimated distributions of personal exposure to respirable particles.
Environ. Monit. Assess. 4: 351-359.
Lewis, C. W. (1991) Sources of air pollutants indoors: VOC and fine paniculate species. J. Exposure Anal.
Environ. Epidemiol. 1: 31-44.
7-170
-------
Lewis, W. H.; Vinay, P.; Zenger, V. E. (1983) Airborne and allergenic pollen of North America. Baltimore,
MD: The Johns Hopkins University Press.
Lighthart, B.; Mohr, A. J. (1994) Atmospheric microbial aerosols: theory and applications. New York, NY:
Chapman & Hall.
Ligocki, M. P.; Liu, H. I. H.; Cass, G. R.; John, W. (1990) Measurements of particle deposition rates inside
Southern California museums. Aerosol Sci. Technol. 13: 85-101.
Lioy, P. J.; Waldman, J. M.; Buckley, T.; Butler, J.; Pietarinen, C. (1990) The personal, indoor and outdoor
concentrations of PM-10 measured in an industrial community during the winter. Atmos. Environ. Part B
24: 57-66.
Little, R. J. A.; Rubin, D. B. (1987) Statistical analysis with missing data. New York NY: John Wiley & Sons.
Litzistorf, G.; Guillemin, M. P.; Buffat, P.; Iselin, F. (1985) Influence of human activity on the airborne fiber
level in paraoccupational environments. J. Air Pollut. Control Assoc. 35: 836-837.
Lofroth, G.; Stensman, C.; Brandhorst-Satzkorn, M. (1991) Indoor sources of mutagenic aerosol paniculate
matter: smoking, cooking and incense burning. Mutat. Res. 261: 21-28.
Mage, D. T. (1980) The statistical form for the ambient particulate standard annual arithmetic mean vs annual
geometric mean. J. Air Pollut. Control Assoc. 30: 706-708.
Mage, D. T. (1983) Public health aspects of air quality surveillance. Public Health Rev. 11: 5-54.
Mage, D. T. (1985) Concepts of human exposure assessment for airborne particulate matter. Environ. Int.
11:407-412.
Mage, D. T. (1991) A comparison of the direct and indirect methods of human exposure. In: Gledhill, B. L.;
Mauro, F., eds. New horizons in biological dosimetry: proceedings of the international symposium on
trends in biological dosimetry; October 1990; Lerici, Italy. New York, NY: Wiley-Liss, Inc.;
pp. 443-454. (Progress in clinical and biological research: v. 372).
Mage, D. T.; Buckley, T. J. (1995) The relationship between personal exposures and ambient concentrations of
particulate matter. Presented at: 88th annual meeting of the Air & Waste Management Association; June;
San Antonio, TX. Pittsburgh, PA: Air & Waste Management Association; paper no. 95-MP18.01.
Mage, D. T.; Ott, W. R. (1996) Accounting for nonuniform mixing and human exposure in indoor
environments. In: Tichenor, B. A., ed. Characterizing sources of indoor air pollution and related sink
effects. Philadelphia, PA: American Society for Testing and Materials; pp. 263-278.
Mage, D.; Ozolins, G.; Peterson, P.; Webster, A.; Orthofer, R.; Vandeweerd, V.; Gwynne, M. (1996) Urban
air pollution in megacities of the world. Atmos. Environ. 30: 681-686.
Mamane, Y. (1992) Characterization of PTEAM indoor aerosol samples (electron microscopy analysis). Research
Triangle Park, NC: U.S. Environmental Protection Agency, Atmospheric Research and Exposure
Assessment Laboratory.
Marple, V. A.; Rubow, K. L.; Turner, W.; Spengler, J. D. (1987) Low flow rate sharp cut impactors for indoor
air sampling: design and calibration. JAPCA 37: 1303-1307.
Martinelli, C. A.; Harley, N. H.; Lippmann, M.; Cohen, B. S. (1983) Monitoring real-time aerosol distribution
in the breathing zone. Am. Ind. Hyg. Assoc. J. 44: 280-285.
7-171
-------
ews, K. P. (1989) Inhalant insect-derived allergens. Immunol. Allergy Clin. North Am. 9: 321-338.
itthews, T. G.; Thompson, C. V.; Wilson, D. L.; Hawthorne, A. R.; Mage, D. T. (1989) Air velocities
inside domestic environments: an important parameter in the study of indoor air quality and climate.
Environ. Int. 15: 545-550.
Mayo, E. (1960) Hawthorne and the Western Electric Company. In: Merrill, H. F., ed. Classics in management.
New York, NY: American Management Association; pp. 417-436.
McKenzie, R. L.; Bright, D. S.; Fletcher, R. A.; Hodgeson, J. A. (1982) Development of a personal exposure
monitor for two sizes of inhalable particulates. Environ. Int. 8: 229-233.
Miesner, E. A.; Rudnick, S. N.; Hu, F.-C.; Spengler, J. D.; Ozkaynak, H.; Preller, L.; Nelson, W. (1989)
Particulate and nicotine sampling in public facilities and offices. JAPCA 39: 1577-1582.
Miller, A.; Thompson, J. M. (1970) Elements of meteorology. Columbus, OH: Charles E. Merrill Publishing
Co.; p. 50.
Millette, J. R.; Hays, S. M. (1994) Resuspension of settled dust. In: Settled asbestos dust sampling and analysis.
Boca Raton, FL: CRC Press, Inc.; pp. 59-65.
Morandi, M. T.; Stock, T. H.; Contant, C. F. (1986) Characterization of indoor microenvironmental exposures
to respirable particulate matter. Presented at: 79th annual meeting of the Air Pollution Control
Association; June; Minneapolis, MN. Pittsburgh, PA: Air Pollution Control Association; paper no.
86-67.2.
Morandi, M. T.; Stock, T. H.; Contant, C. F. (1988) A comparative study of respirable particulate
microenvironmental concentrations and personal exposures. Environ. Monit. Assess. 10: 105-122.
Moschandreas, D. J.; Winchester, J. W.; Nelson, J. W.; Burton, R. M. (1979) Fine particle residential indoor
air pollution. Atmos. Environ. 13: 1413-1418.
Mumford, J. L.; Williams, R. W.; Walsh, D. B.; Burton, R. M.; Svendsgaard, D. J.; Chuang, J. C.; Houk,
V. S.; Lewtas, J. (1991) Indoor air pollutants from unvented kerosene heater emissions in mobile homes:
studies on particles, semivolatile organics, carbon monoxide, and mutagenicity. Environ. Sci. Technol.
25: 1732-1738.
Murray, D. M.; Burmaster, D. E. (1995) Residential air exchange rates in the United States: empirical and
estimated parametric distributions by season and climatic region. Risk Anal. 15: 459-465.
National Institute for Environmental Studies. (1994) Experimental studies on the health effects of air pollutants
containing diesel exhaust particles [FY 1988-1992 ]. Kokuritsu Kogai Kenkyusho Tokubetsu Kenkyu
Hokoku (SR-14-'94): 26-32.
National Research Council. (1986) Environmental tobacco smoke: measuring exposures and assessing health
effects. Washington, DC: National Academy Press.
Nazaroff, W. W.; Cass, G. R. (1989) Mathematical modeling of indoor aerosol dynamics. Environ. Sci.
Technol. 23: 157-166.
Nazaroff, W. W.; Salmon, L. G.; Cass, G. R. (1990a) Concentration and fate of airborne particles in museums.
Environ. Sci. Technol. 24: 66-77.
7-172
-------
Nazaroff, W. W.; Ligocki, M. P.; Ma, T.; Cass, G. R. (1990b) Particle deposition in museums: comparison of
modeling and measurement results. Aerosol Sci. Technol. 13: 332-348.
Nazaroff, W. W.; Gadgil, A. J.; Weschler, C. J. (1993) Critique of the use of deposition velocity in modeling
indoor air quality. In: Nagda, N. L., ed. Modeling of indoor air quality and exposure. Philadelphia, PA:
American Society for Testing and Materials; pp. 81-104. (ASTM special technical publication no. 1205).
Neas, L. M.; Dockery, D. W.; Ware, J. H.; Spengler, J. D.; Ferris, B. G., Jr.; Speizer, F. E. (1994)
Concentration of indoor paniculate matter as a determinant of respiratory health in children.
Am. J. Epidemiol. 139: 1088-1099.
Ogden, T. L.; Bartlett, I. W.; Purnell, C. J.; Wells, C. J.; Armitage, F.; Wolfson, H. (1993) Dust for cotton
manufacture: changing from static to personal sampling. Ann. Occup. Hyg. 37: 271-285.
Oldaker, G. B., Ill; Ogden, M. W.; Maiolo, K. C.; Conner, J. M.; Conrad, F. W., Jr.; DeLuca, P. O. (1990)
Results from surveys of environmental tobacco smoke in restaurants in Winston-Salem, North Carolina.
In: Indoor air '90: precedings of the 5th international conference on indoor air quality and climate,
volume 2, characteristics of indoor air; July-August; Toronto, ON, Canada. Ottawa, ON, Canada:
International Conference on Indoor Air Quality and Climate, Inc.; pp. 281-285.
Oldaker, G. B., Ill; Taylor, W. D.; Parrish, K. B. (1993) Investigations of ventilation, smoking activity, and
indoor air quality at four large office buildings. In: Proceedings of IAQ '92. American Society of
Heating, Refrigerating and Air-Conditioning Engineers, Inc.; pp. 365-374.
Orchard, T.; Woodbury, M. A. (1972) A missing information principle: theory and applications. In: LeCam, L.;
Newman, J.; Scott, E., eds. Proceedings of the 6th Berkeley symposium on mathematical statistics and
probability, v. 1. Berkeley, CA: University of California Press; pp. 697-715.
Ott, W. R. (1982) Concepts of human exposure to air pollution. Environ. Int. 7: 179-196.
Owen, M. K.; Ensor, D. S.; Hovis, L. S.; Tucker, W. G.; Sparks, L. E. (1990) Particle size distributions for an
office aerosol. Aerosol Sci. Technol. 13: 486-492.
Owen, M. K.; Ensor, D. S.; Sparks, L. E. (1992) Airborne particle sizes and sources found in indoor air.
Atmos. Environ. Part A 26: 2149-2162.
Ozkaynak, H.; Spengler, J. D.; Ludwig, J. F.; Butler, D. A.; Clayton, C. A.; Pellizzari, E.; Wiener, R. W.
(1990) Personal exposure to paniculate matter: findings from the Particle Total Exposure Assessment
Methodology (PTEAM) prepilot study. In: Indoor air '90: precedings of the 5th international conference
on indoor air quality and climate, volume 2, characteristics of indoor air; July-August; Toronto, ON,
Canada. Ottawa, ON, Canada: International Conference on Indoor Air Quality and Climate, Inc.;
pp. 571-576.
Ozkaynak, H.; Xue, J.; Weker, R.; Butler, D.; Spengler, J. (1993a) The particle TEAM (PTEAM) study:
analysis of the data, volume III [draft final report]. Research Triangle Park, NC: U.S. Environmental
Protection Agency; EPA contract no. 68-02-4544.
Ozkaynak, H.; Spengler, J. D.; Xue, J.; Koutrakis, P.; Pellizzari, E. D.; Wallace, L. (1993b) Sources and
factors influencing personal and indoor exposures to particles, elements and nicotine: findings from the
particle TEAM pilot study. In: Jantunen, M.; Kalliokoski, P.; Kukkonen, E.; Saarela, K.; Seppanen, O.;
Vuorelma, H., eds. Indoor air '93: proceedings of the 6th international conference on indoor air quality
and climate, v. 3, combustion products, risk assessment, policies; July; Helsinki, Finland. Helsinki,
Finland: Indoor Air '93; pp. 457-462.
7-173
-------
Ozkaynak, H.; Xue, J.; Spengler, J. D.; Wallace, L. A.; Pellizzari, E. D.; Jenkins, P. (1996) Personal
exposures to airborne particles and metals: results from the particle TEAM study in Riverside, California.
In: Lippmann, M., ed. Papers from the ISEA-ISEE annual meeting; September 1994; Research Triangle
Park, NC. J. Exp. Anal. Environ. Epidemiol.: in press.
Pellizzari, E. D.; Thomas, K. W.; Clayton, C. A.; Whitmore, R. W.; Shores, R. C.; Zelon, H. S.; Perritt,
R. L. (1992) Particle total exposure assessment methodology (PTEAM): Riverside, California pilot study,
volume I [final report]. Research Triangle Park, NC: U.S. Environmental Protection Agency,
Atmospheric Research and Exposure Assessment Laboratory; EPA report no. EPA/600/R-93/050.
Available from: NTIS, Springfield, VA; PB93-166957/XAB.
Pellizzari, E. D.; Thomas, K. W.; Clayton, C. A.; Whitmore, R. C.; Shores, H.; Zelon, S.; Peritt, R. L.
(1993) Particle total exposure assessment methodology (PTEAM): Riverside, California pilot study -
volume I [project summary]. Research Triangle Park, NC: U.S. Environmental Protection Agency,
Atmospheric Research and Exposure Assessment Laboratory; EPA report no. EPA/600/SR-93/050.
Pengelly, L. D.; Goldsmith, C. H.; Kerigan, A. T.; Furlong, W.; Toplack, S. (1987) The Hamilton study:
estimating exposure to ambient suspended particles. JAPCA 37: 1421-1428.
Perritt, R. L.; Clayton, C. A.; Pellizzari, E. D.; Thomas, K. W.; Wallace, L. A.; Spengler, J. D.;
Ozkaynak, H. (1991) Particle Total Exposure Assessment Methodology (PTEAM) Pilot Study: personal,
indoor, and outdoor paniculate concentration distributions for southern California fall 1990 - preliminary
results. In: Measurement of toxic and related air pollutants: proceedings of the 1991 U.S. EPA/A&WMA
international symposium, v. 2; May; Durham, NC. Pittsburgh, PA: Air & Waste Management
Association; pp. 665-671. (A&WMA publication VIP-21).
Pickles, J. H. (1982) Air pollution estimation error and what it does to epidemiological analysis. Atmos. Environ.
16: 2241-2245.
Platts-Mills, T. A. E.; Chapman, M. D. (1987) Dust mites: immunology, allergic disease, and environmental
control. J. Allergy Clin. Immunol. 80: 755-775.
Pope, C. A., Ill; Thun, M. J.; Namboodiri, M. M.; Dockery, D. W.; Evans, J. S.; Speizer, F. E.; Heath,
C. W., Jr. (1995) Paniculate air pollution as a predictor of mortality in a prospective study of U.S.
adults. Am. J. Respir. Crit. Care Med. 151: 669-674.
Quackenboss, J. J.; Lebowitz, M. D.; Crutchfield, C. D. (1989) Indoor-outdoor relationships for paniculate
matter: exposure classifications and health effects. Environ. Int. 15: 353-360.
Quackenboss, J. J.; Krzyzanowski, M.; Lebowitz, M. D. (1991) Exposure assessment approaches to evaluate
respiratory health effects of paniculate matter and nitrogen dioxide. J. Exposure Anal. Environ.
Epidemiol. 1: 83-107.
Raunemaa, T.; Kulmala, M.; Saari, H.; Olin, M.; Kulmala, M. H. (1989) Indoor air aerosol model: transport
indoors and deposition of fine and coarse particles. Aerosol Sci. Technol. 11: 11-25.
Repace, J. L. (1987) Indoor concentrations of environmental tobacco smoke: field surveys. In: O'Neill, I. K.;
Brunnemann, K. D.; Dodet, B.; Hoffmann, D., eds. Environmental carcinogens: methods of analysis and
exposure measurement, volume 9 - passive smoking. Lyon, France: World Health Organization;
pp. 141-162. (IARC scientific publications: no. 81).
Repace, J. L.; Lowrey, A. H. (1980) Indoor air pollution, tobacco smoke, and public health. Science
(Washington, DC) 208: 464-472.
7-174
-------
Repace, J. L.; Ott, W. R.; Wallace, L. A. (1980) Total human exposure to air pollution. Presented at: 73rd
annual meeting of the Air Pollution Control Association; June; Montreal, PQ, Canada. Pittsburgh, PA:
Air Pollution Control Association; paper no. 80-61.6.
Rippon, J. W. (1988) Medical mycology: the pathogenic fungi and the pathogenic actinomycetes. 3rd ed.
Philadelphia, PA: W. B. Saunders Company.
Roberts, J. W.; Camann, D. E.; Spittler, T. M. (1990) Monitoring and controlling lead in house dust in older
homes. In: Indoor air '90: precedings of the 5th international conference on indoor air quality and
climate, volume 2, characteristics of indoor air; July-August; Toronto, ON, Canada. Ottawa, ON,
Canada: International Conference on Indoor Air Quality and Climate, Inc.; pp. 435-440.
Rodes, C. E.; Kamens, R. M.; Wiener, R. W. (1991) The significance and characteristics of the personal
activity cloud on exposure assessment measurements for indoor contaminants. Indoor Air 2: 123-145.
Santanam, S.; Spengler, J. D.; Ryan, P. B. (1990) Paniculate matter exposures estimated from an indoor-outdoor
source apportionment study. In: Indoor air '90: precedings of the 5th international conference on indoor
air quality and climate, volume 2, characteristics of indoor air; July-August; Toronto, ON, Canada.
Ottawa, ON, Canada: International Conference on Indoor Air Quality and Climate, Inc.; pp. 583-588.
Sexton, K.; Spengler, J. D.; Treitman, R. D. (1984) Personal exposure to respirable particles: a case study in
Waterbury, Vermont. Atmos. Environ. 18: 1385-1398.
Sheldon, L. S.; Handy, R. W.; Hartwell, T. D.; Whitmore, R. W.; Zelon, H. S.; Pellizzari, E. D. (1988a)
Indoor air quality in public buildings: v. I. Washington, DC: U.S. Environmental Protection Agency,
Office of Acid Deposition, Environmental Monitoring, and Quality Assurance; report no. EPA
600/6-88/009a. Available from: NTIS, Springfield, VA; PB89-102503.
Sheldon, L.; Zelon, H.; Sickles, J.; Eaton, C.; Hartwell, T. (1988b) Indoor air quality in public buildings:
volume II. Research Triangle Park, NC: U.S. Environmental Protection Agency, Environmental
Monitoring Systems Laboratory; report no. EPA 600/6-88/009b. Available from: NTIS, Springfield, VA;
PB89-102511.
Sheldon, L. S.; Hartwell, T. D.; Cox, B. G.; Sickles, J. E., II; Pellizzari, E. D.; Smith, M. L.; Perritt, R. L.;
Jones, S. M. (1989) An investigation of infiltration and indoor air quality: final report. Albany, NY:
New York State Energy Research and Development Authority; New York State ERDA contract no.
736-CON-BCS-85.
Sheldon, L.; Clayton, A.; Keever, J. Perritt, R.; Whitaker, D. (1992) PTEAM: monitoring of phthalates and
PAHs in indoor and outdoor air samples in Riverside, California, volume II [final report]. Sacramento,
CA: California Environmental Protection Agency, State Air Resources Board, Research Division;
contract no. A933-144. Available from: NTIS, Springfield, VA; PB93-205649/XAB.
Sinclair, J. D.; Psota-Kelty, L. A.; Weschler, C. J. (1988) Indoor/outdoor ratios and indoor surface
accumulations of ionic substances at Newark, New Jersey. Atmos. Environ. 22: 461-469.
Sinclair, J. D.; Psota-Kelty, L. A.; Weschler, C. J.; Shields, H. C. (1990) Measurement and modeling of
airborne concentrations and indoor surface accumulation rates of ionic substances at Neenah, Wisconsin.
Atmos. Environ. Part A 24: 627-638.
Sinclair, J. D.; Psota-Kelly, L. A.; Peins, G. A.; Ibidunni, A. O. (1992) Indoor/outdoor relationships of
airborne ionic substances: comparison of electronic equipment room and factory environments.
Atmos. Environ. Part A 26: 871-882.
7-175
-------
i, K. R.; Apte, M. G.; Ma, Y.; Wongsekiarttirat, W.; Kulkarni, A. (1994) Air pollution and the energy
ladder in Asian cities. In: Tyler, S.; Sathaye, J.; Goldman, N., eds. Energy use in Asian Cities. Energy
(Oxford) 19: 587-600.
Smithard, E. H. R. (1954) The 1952 fog in a metropolitan borough. Mon. Bull. Minist. Health Public Health
Lab. Serv. (G. B.) 13: 26-35.
Spengler, J. D.; Thurston, G. D. (1983) Mass and elemental composition of fine and coarse particles in six U.S.
cities. J. Air Pollut. Control Assoc. 33: 1162-1171.
Spengler, J. D.; Dockery, D. W.; Reed, M. P.; Tosteson, T.; Quinlan, P. (1980) Personal exposures to
respirable particles. Presented at: 73rd annual meeting of the Air Pollution Control Association; June;
Montreal, PQ, Canada. Pittsburgh, PA: Air Pollution Control Association; paper no. 80-61.5b.
Spengler, J. D.; Dockery, D. W.; Turner, W. A.; Wolfson, J. M.; Ferris, B. G., Jr. (1981) Long-term
measurements of respirable sulfates and particles inside and outside homes. Atmos. Environ. 15: 23-30.
Spengler, J. D.; Treitman, R. D.; Tosteson, T. D.; Mage, D. T.; Soczek, M. L. (1985) Personal exposures to
respirable particulates and implications for air pollution epidemiology. Environ. Sci. Technol.
19: 700-707.
Spengler, J. D.; Ware, J.; Speizer, F.; Ferris, B.; Dockery, D.; Lebret, E.; Brunnekreef, B. (1987) Harvard's
indoor air quality respiratory health study. In: Seifert, B.; Esdorn, H.; Fischer, M.; Riiden, H.; Wegner,
J., eds. Indoor air '87: proceedings of the 4th international conference on indoor air quality and climate:
v. 2, environmental tobacco smoke, multicomponent studies, radon, sick buildings, odours and irritants,
hyperreactivities and allergies; August; Berlin, Federal Republic of Germany. Berlin, Federal Republic of
Germany: Institute for Water, Soil and Air Hygiene; pp. 218-223.
Spengler, J. D.; Ozkaynak, H.; Ludwig, J.; Allen, G.; Pellizzari, E. D.; Wiener, R. (1989) Personal exposures
to particulate matter: instruments and methodologies P-TEAM. In: Measurement of toxic and related air
pollutants: proceedings of the 1989 U.S. EPA/A&WMA international symposium; May; Raleigh, NC.
Pittsburgh, PA: Air & Waste Management Association; pp. 449-463. (A&WMA publication VIP-13).
Sterling, T. D.; Dimich, H.; Kobayashi, D. (1982) Indoor byproduct levels of tobacco smoke: a critical review
of the literature. J. Air Pollut. Control Assoc. 32: 250-259.
Sun, H. H.; Koutrakis, P.; Spengler, J. D. (1993) Validation of personal exposure models for sulfate and aerosol
strong acidity. J. Air Waste Manage. Assoc. 43: 845-850.
Sun, H. H.; Allen, G. A.; Koutrakis, P.; Burton, R. M. (1995) Spatial variation in acidic sulfate and ammonia
concentrations within metropolitan Philadelphia. J. Air Waste Manage. Assoc. 45: 442-452.
Tamura, K.; Ando, M. (1994) Suspended particulate matter in indoor and outdoor air along a main road and
personal exposure assessment. Presented at: Sixth conference of the International Society for
Environmental Epidemiology/fourth conference of the International Society for Exposure Analysis joint
conference; September; Research Triangle Park, NC. Chapel Hill, NC: University of North Carolina,
School of Public Health; abstract no. 116.
Tamura, K.; Ando, M.; Sagai, M.; Matsumoto, Y. (1996) Estimation of levels of personal exposure to
suspended particulate matter and nitrogen dioxide in Tokyo. Environ. Sci. (Tokyo) 6: accepted.
Thatcher, T. L.; Layton, D. W. (1995) Deposition, resuspension, and penetration of particles within a residence.
Atmos. Environ. 29: 1487-1497.
7-176
-------
Thomas, K. W.; Pellizzari, E. D.; Clayton, C. A.; Whitaker, D. A.; Shores, R. C.; Spengler, J.;
Ozkaynak, H.; Froehlich, S. E.; Wallace, L. A. (1993) Particle total exposure assessment
methodology (PTEAM) 1990 study: method performance and data quality for personal, indoor,
and outdoor monitoring. J. Exposure Anal. Environ. Epidemiol. 3: 203-226.
Turk, B. H.; Brown, J. T.; Geisling-Sobotka, K.; Froehlich, D. A.; Grimsrud, D. T.; Harrison, J.; Koonce,
J. F.; Prill, R. J.; Revzan, K. L. (1987) Indoor air quality and ventilation measurements in 38 Pacific
Northwest commercial buildings: final report to the Bonneville Power Administration, volume I:
measurement results and interpretation [final report]. Berkeley, CA: U.S. Department of Energy,
Lawrence Berkeley Laboratory, Indoor Environment Program; report no. LBL-22315-1/2. Available
from: DE88014064/XAB.
Turk, B. H.; Grimsrud, D. T.; Brown, J. T.; Geisling-Sobotka, K. L.; Harrison, J.; Prill, R. J. (1989)
Commercial building ventilation rates and particle concentrations. ASHRAE Trans. 95(part 1): 422-433.
U.S. Centers for Disease Control. (1988) Assessing exposures of health-care personnel to aerosols of
ribavirin—California. Morb. Mortal. Wkly. Rep. 37: 560-563.
U.S. Environmental Protection Agency. (1982) Air quality criteria for paniculate matter and sulfur oxides.
Research Triangle Park, NC: Office of Health and Environmental Assessment, Environmental Criteria
and Assessment Office; EPA report no. EPA-600/8-82-029aF-cF. 3v. Available from: NTIS, Springfield,
VA; PB84-156777.
U.S. Environmental Protection Agency. (1986a) Second addendum to air quality criteria for paniculate matter
and sulfur oxides (1982): assessment of newly available health effects information. Research Triangle
Park, NC: Office of Health and Environmental Assessment, Environmental Criteria and Assessment
Office; EPA report no. EPA-600/8-86-020F. Available from: NTIS, Springfield, VA; PB87-176574.
U.S. Environmental Protection Agency. (1986b) Air quality criteria for lead. Research Triangle Park, NC: Office
of Health and Environmental Assessment, Environmental Criteria and Assessment Office; EPA report no.
EPA-600/8-83/028aF-dF. 4v. Available from: NTIS, Springfield, VA; PB87-142378.
U.S. Environmental Protection Agency. (1989) Exposure factors handbook. Washington, DC: Office of Health
and Environmental Assessment; EPA report no. EPA/600/8-89/043. Available from: NTIS, Springfield,
VA; PB90-106774.
U.S. Environmental Protection Agency. (1992) Respiratory health effects of passive smoking: lung cancer and
other disorders. Washington, DC: Office of Research and Development, Office of Health and
Environmental Assessment; EPA report no. EPA/600/6-90/006F. Available from: NTIS, Springfield,
VA; PB93-134419/XAB.
U.S. Environmental Protection Agency. (1995) PFT database for residential air flow measurements: database
documentation, final report. Washington, DC: Office of Toxic Substances; contract no. 68-D3-0013, task
3-18.
United Kingdom Ministry of Health. (1954) Mortality and morbidity during the London fog of December 1952.
London, United Kingdom: Her Majesty's Stationery Office. (Reports on public health and medical
subjects no. 95).
Wallace, L. (1996) Indoor particles: a review. J. Air Waste Manage. Assoc. 46: 98-126.
7-177
-------
.ce, L.; Clayton, A.; Whitmore, R.; Shores, R.; Thomas, K.; Whitaker, D.; Reading, P.; Pellizzari, E.;
Spengler, J.; Ozkaynak, H.; Froehlich, S.; Jenkins, P.; Ota, L.; Westerdahl, D. (1991a) Initial results
from the PTEAM study: survey design, population response rates, monitor performance and quality
control. In: Measurement of toxic and related air pollutants: proceedings of the 1991 U.S.
EPA/A&WMA international symposium, v. 2; May; Durham, NC. Pittsburgh, PA: Air & Waste
Management Association; pp. 659-664. (A&WMA publication VIP-21).
Wallace, L. A.; Pellizzari, E.; Sheldon, L.; Whitmore, R.; Zelon, H.; Clayton, A.; Shores, R.; Thomas, K.;
Whitaker, D.; Reading, P.; Spengler, J.; Ozkaynak, H.; Froehlich, S.; Jenkins, P.; Ota, L.;
Westerdahl, D. (1991b) The TEAM study of inhalable particles (PM10): study design, sampler
performance, and preliminary results. Presented at: 84th annual meeting of the Air & Waste
Management Association; June; Vancouver, British Columbia, Canada. Pittsburgh, PA: Air & Waste
Management Association; paper no. 91-171.3.
Wallace, L.; Nelson, W.; Ziegenfus, R.; Pellizzari, E.; Michael, L.; Whitmore, R.; Zelon, H.; Hartwell, T.;
Perritt, R.; Westerdahl, D. (1991c) The Los Angeles TEAM study: personal exposures, indoor-outdoor
air concentrations, and breath concentrations of 25 volatile organic compounds. J. Exposure Anal.
Environ. Epidemiol. 1: 157-192.
Wallace, L. A.; Ozkaynak, H.; Spengler, J. D.; Pellizzari, E. D.; Jenkins, P. (1993) Indoor, outdoor, and
personal air exposures to particles, elements, and nicotine for 178 southern California residents.
In: Jantunen, M.; Kalliokoski, P.; Kukkonen, E.; Saarela, K.; Seppanen, O.; Vuorelma, H., eds. Indoor
air '93: proceedings of the 6th international conference on indoor air quality and climate, v. 3,
combustion products, risk assessment, policies; July; Helsinki, Finland. Helsinki, Finland: Indoor
Air '93; pp. 445-450.
Weschler, C. J.; Shields, H. C.; Kelty, S. P.; Psota-Kelly, L. A.; Sinclair, J. D. (1989) Comparison of effects
of ventilation, filtration and outdoor air at telephone office buildings. In: Nagda, N. L.; Harper, J. P.,
eds. Design and protocol for monitoring indoor air quality. Philadelphia, PA: American Society for
Testing and Materials; pp. 9-34. (ASTM special technical publication 1002).
West, J. B. (1982) Pulmonary pathophysiology—the essentials. 2nd ed. Baltimore, MD: Williams & Wilkins;
p. 168.
Wiener, R. W. (1988) Measurement and evaluation of personal exposure to aerosols. In: Measurement of toxic
and related air pollutants: proceedings of the 1988 EPA/APCA international symposium; May; Research
Triangle Park, NC. Pittsburgh, PA: Air Pollution Control Association; pp. 84-88. (APCA publication no.
VIP-10).
Wiener, R. W. (1989) Particle total exposure assessment methodology—an overivew of planning and
accomplishments. In: Measurement of toxic and related air pollutants: proceedings of the 1989 U.S.
EPA/A&WMA international symposium; May; Raleigh, NC. Pittsburgh, PA: Air & Waste Management
Association; pp. 442-448. (A&WMA publication VIP-13).
Wiener, R. W.; Wallace, L.; Pahl, D.; Pellizzari, E.; Whittaker, D.; Spengler, J.; Ozkaynak, H. (1990) Review
of the particle TEAM 9 home field study. In: Measurement of toxic and related air pollutants:
proceedings of the 1990 EPA/A&WMA international symposium, v. 2; May; Raleigh, NC. Pittsburgh,
PA: Air & Waste Management Association; pp. 452-460. (A&WMA publication VIP-17).
Willeke, K.; Baron, P. A., eds. (1993) Aerosol measurement: principles, techniques and applications.
New York, NY: Van Nostrand Reinhold Publishers.
Wilmoth, R. C.; Powers, T. J.; Millette, J. R. (1991) Observations on studies useful to asbestos O&M activities.
Microscope 39: 299-312.
7-178
-------
Wilson, W. E.; Sun, H. H. (1995) Differentiating fine and coarse particles: definitions and exposure relationships
relevant to epidemiological studies. In: Schmidt-Ott, A., ed. Trends in aerosol research IV: new
approaches in aerosol science and technology, proceedings of the seminar; January; Gerhard Mercator
University, Duisburg, Germany. Duisburg, Germany: Gerhard Mercator University of Duisburg;
pp. 57-71.
Winer, B. J. (1962) Statistical principles in experimental design. New York, NY: McGraw-Hill Book Co., Inc.;
pp. 105-124.
Woodbury, M.; Hasselblad, V. (1970) Maximum likelihood estimates of the variance covariance matrix from the
multivariate normal. In: Proceedings of SHARE XXXIV, v. 3; pp. 1550-1561.
World Health Organization. (1982a) Human exposure to carbon monoxide and suspended paniculate matter in
Zagreb, Yugoslavia. Geneva, Switzerland: World Health Organization; GEMS (Global Environmental
Monitoring System) report no. EFP/82.33.
World Health Organization. (1982b) Human exposure to SO2, NO2 and suspended particulate matter in Toronto,
Canada. Geneva, Switzerland: World Health Organization; GEMS (Global Environmental Monitoring
System) report no. EFP/82.38.
World Health Organization. (1984) Human exposure to suspended particulate matter and sulfate in Bombay,
India. Geneva, Switzerland: World Health Organization; GEMS (Global Environment Monitoring
System) report no. EFP/84.86.
World Health Organization. (1985) Human exposure to carbon monoxide and suspended particulate matter in
Beijing, People's Republic of China. Geneva, Switzerland: World Health Organization; GEMS (Global
Environmental Monitoring System) report no. PEP/85.11.
World Health Organization. (1995) Interpretation of WHO air quality guidelines: report of an expert working
group. Geneva, Switzerland: World Health Organization; report no. WHO/EOS/95; in press.
Yoshimura, I. (1990) The effect of measurement error on the dose-response curve. Environ. Health Perspect.
87: 173-178.
7-179
' Ll* tV.S. GOVERNMENT PRINTING OFTICE: 1996-752-126/49039
-------