EPA 460/3-81-017
        A Study of Emissions
               from
        Light-Duty Vehicles
                in
              Denver
      Contract No. 68-03-3022
           prepared for:

  Environmental Protection Agency
        2565 Plymouth Road
        Ann Arbor, MI 48105
          August 31,  1981
           submitted by:

Automotive Testing Laboratories, Inc.
       19900 E. Coif ax Avenue
       Aurora, Colorado 80011
          (303) 343-8938

-------
                                    ABSTRACT




     A sample of 300 light-duty vehicles normally operated in the Denver metropolitan




area was  tested  for emissions and fuel economy.   The vehicles  were  from the  1978




through 1982 model years and  included both passenger cars and  light-duty trucks.  One




purpose of the  program was to gather  information for  calculations and projections  of




ambient  air quality.   Another  purpose was to assemble data on  current model  year




vehicles for use in support of Inspection/Maintenance  and other regulatory programs.




     The test sequence on  all  of the veh'des  included the Federal Test Procedure, the




Highway Fuel  Economy test, and a series of short tests consisting of  the Bagged Idle




Test, the  50 mph Cruise Test, the Four  Speed Idle Test,  and the Loaded Two Mode Test.




Some vehicles which exceeded  Federal  Frnission standards were subjected to restorative




maintenance and  retested.   [Evaporative emission tests using the Sealed Housing for




Evaporative Determination  (Slinn) procedure were performed on 125  of the  1980-1982




model  year vehicles.




     Other actions were taken in  relation  to each  vehicle lested.  These included  an




engine and  emission control system  maladjustment/disablement and  status inspection,




driveabilily evaluations,  and owner interviews to  obtain vehicle  maintenance  and usage




data.
                                        ui

-------
                              TABLE OF CONTENTS
                                                                             Page
ABSTRACT                                                                     iii

1.    INTRODUCTION                                                           1-1

2.    TECHNICAL DISCUSSION                                                  2-1

     2.1   PROGRAM OBJECTIVE                                               2-1

     2.2   PROGRAM DESIGN                                                   2-1

     2.3   TEST VEHICLE PROCUREMENT                                       2-2

          2.3.1   Sample Criteria                                               2-2

          2.3.2   Procurement Plan                                             2-3

          2.3.3   Incentives       .                                             2-4

          2.3.4   Test Vehicle General Handling                                  2-4

     2.4   FACILITIES AND EQUIPMENT                                         2-5

          2.4.1   Test Location and Facility                                      2-5

          2,,4.2   Chassis Dynamometers                                         2-5

          2.4.3   Constant  Volume Sampler                                      2-6

          2.4.4   Analytical Instruments                                         2-6

          2.4.5   Data Acquisition                                              2-7

          2.4.6   Sealed Housing for Evaporative Determination                   2-7

          2.4.7   Laboratory Standard Calibration Gases                          2-8

          2.4.8   Miscellaneous Equipment                                       2-9

     2.5   EQUIPMENT CALIBRATION AND VERIFICATION                       2-9

          2.5.1   Chassis Dynamometer                                          2-9

          2.5.2   Constant  Volume Sampler                                    2-10

          2.5.3   Analytical Instruments                                       2-11

          2.5.4   Sealed Housing for Evaporative Determination                 2-12

-------
     2.6  TEST PROCEDURES                                                  2-12




          2.6.1    Vehicle Preparation                                           2-13




          2.6.2    Equipment Preparation                                        2-13




          2.6.3    Federal Exhaust Emission Test Procedure                       2-15




          2.6.4    Evaporative Emission Test Procedure                           2-17




          2.6.5    Bagged Idle Test Procedure                                    2-18




          2.6.6    50 (mph) Cruise Test Procedure                                2-18




          2.6.7    Highway Fuel Economy Test Procedure                         2-19




          2.6.8    Four Speed Idle Test                                          2-19




          2.6.9    Loaded Two Mode Test                                        2-19




          2.6.10  Vehicle Inspection Procedure                                  2-20




          2.6.11  Restorative Maintenance Evaluation                            2-20




          2.6.12  Daily Test Schedule Procedure                                 2-21




     2.7  DATA HANDLING                                                    2-21




          2.7.1    Data Collection                                               2-21




          2.7.2    Data Processing                                               2-21




          2.7.3    Quality Control                                               2-22




          2.7.4    Calculation of Results                                         2-23




3.    ACKNOWLEDGEMENTS                                                    3-1

-------
                                1. INTRODUCTION




     The U. S. Environmental Protection Agency (EPA), under authority  of  the  Clean




Air Act, develops, implements and  administers a program to assess, quantify and reduce




pollution of the nation's resources.  Authority for parts of this program is delegated to




the agency's Emission Control Technology Division (ECTD). The ECTD's responsibility is




to assess, quantify and reduce air pollution from in-use motor  vehicles.  Such responsi-




bility includes designing, implementing and administering the Emission Factors  Program.




     The Emission Factors (EF) program consists of a series of annual studies designed




to obtain data  from  in-use vehicles operated  under a  variety of  topographical  and




climatological  conditions.   Data obtained from these studies are used  in calculating




current and projecting future light-duty vehicle emission factors.




     EF studies  began in  the  EPA's Fiscal Year (FY)  1971.   Subsequent studies were




conducted in Fiscal Years  1972, 1973, 1974, 1975, 1977 and 1979.  Extensions  to the FY




75 and FY  77 programs precluded separate EF studies in each fiscal year following those




in which these studies  were initiated and by which  they are  identified.  Vehicles have




been tested annually  with  exceptions as indicated in either six or seven of  the following




U. S. cities:  Chicago, Houston,  Denver, Los Angeles, Detroit, Phoenix, St.  Louis  and




Washington, D.C.




     In the EF program's  initial stages,  vehicles of interest covered a relatively large




number of  the  most current model years.  As more and more  information  was obtained




from these  studies, however, the  model  year  span  was reduced with  each successive



program year.




     Program test procedures have also been changed as  testing technology changed and




new emission control  technologies were introduced.  The Sealed Housing for Evaporative




Determination  (SHED) came into use for determining fuel evaporative emission factors




as concern over this pollution source emerged.  For determining modal emission  factors,
                                        1-1

-------
procedures of the EPA's Surveillance Driving Sequence and Steady State tests also came




into use.




     The scope of EF study programs has also been expanded over  the years. A recent




inclusion is the collection ol mass and direct tailpipe emission data by abbreviated test




procedures.   Abbreviated emission tests have come under consideration in recent years




for use  in state and  local vehicle emission inspection and maintenance programs.  Also




included are investigations  of  the individual and combined  effects of emission control




system  malfunction,  disablement  and  maladjustment  on  vehicle  emissions and  fuel




economy.




     The FY 80 Emission Factors study, is the  subject of this report.  To execute  a




portion  of this study, the EPA contracted with  Automotive Testing  Laboratories, Inc.




(ATL) to provide  data from vehicles  operating  in the  metropolitan area of Denver,



Colorado.
                                        1-2

-------
                           2. TECHNICAL DISCUSSION



2.1 PROGRAM OBJECTIVE



     The  program's  objective was  that of obtaining emission  test, fuel economy test,



vehicle  emission control system maintenance and other data  from light-duty vehicles



operating  in  the  Denver metropolitan area.  These data are used in calculating and



projecting light-duty vehicle emission factors and in satisfying other of the EPA's data




needs.



2.2 PROGRAM DESIGN



     Three hundred  (300) vehicles  from  the  1978-1982 model  years were tested in the




program.



     Lists which  prescribed the composition of each sample were provided by the EPA.



Substitutions  were allowed within certain limits.  Procedures by which  the test vehicles



were obtained were  in keeping with an EPATapproved procurement strategy.  Although



some of the vehicles were from car fleets, most were privately owned.  Incentives were



offered to promote owner participation.



     Ail vehicles  were subjected to the  1975 Federal Test Procedure (FTP)  which deals



with cold and hot  start exhaust emissions testing.  All vehicles were also subjected to the



Highway Fuel Economy (HFET) and to a series  of short tests  comprised of the Bagged



Idle, 50 Cruise, Four Speed Idle and the Loaded  Two-Mode tests.  One hundred twenty-



five  vehicles  received  an  evaporative emissions  (SHED)  test.   Some vehicles which



exceeded Federal Exhaust Emissions standards applicable to their model year, were given



restorative maintenance followed by another test sequence.
                                       2-1

-------
      Other actions  were taken in relation to each vehicle tested.  These included:  an




engine parameters and emission control system maladjustment/disablement inspection, a




tire inspection, a vehicle driveability evaluation and an interview of the vehicle owner to




obtain historical information on the vehicle's maintenance and use.




      Other study-related activities  pertained to test  equipment calibration and  data




review, reduction and reporting.  Details concerning  these and the  activities described




above are presented in the remainder of this section.




2.3 TEST VEHICLE PROCUREMENT




2.3.1  Sample Criteria




      Criteria for  the procurement and selection of test vehicles were  provided  by the




EPA.  Criteria for the basic emission factors sample were given on a list describing 300




vehicles from the  1978-1982 model  years.  Vehicles required  were specified by model




year,  vehicle make,  vehicle type (passenger car or light-duty truck), model, and in some




cases engine size  (number  of  cylinders).  The test vehicles were selected by the  EPA




based on national sales volumes within each model year.  Quantities required by model




year were  weighted for  the  most part  toward the later model  years.  Vehicles from the




later  model years  are equipped with the latest in emission  control technology and are




also those on which the least amount of in-use data are available.




      The EPA also  stipulated  that each model year  sample be comprised  of 20%  high




mileage vehicles;  high  mileage was  defined  as greater  than 4,000,  15,000,  30,000 and




30,000 miles for the 1981, 1980, 1979, and 1978 model years respectively.




      Other criteria for the emission  factors sample consisted of limitations  on procure-




ment  sources.  The use of fleet and rental vehicles was limited to no  more than twenty




percent for the 1981-1982 model  years.  Test vehicles from the 1978-1980 model years




were  to be acquired  exclusively through the use of registration lists.
                                        2-2

-------
2.3.2 Procurement Plan




     The plan  for  acquiring  test  vehicles  consisted primarily of  the  use of vehicle




registration lists and direct maiJ solicitations.




     Registration lists for counties containing Denver  and the surrounding area were




obtained from the State of Colorado.  A computerized search  of the entire registration




list was  then  conducted which resulted in  an individual  candidate  list  for each vehicle.




The individual list contains all candidate vehicles in the specified area. To  insure that a




random  test  fleet  was procured  each  of the individual  lists was randomized using




standard computer  techniques.   The  resulting list  consisted of  candidate   vehicles




assigned numbers  one  through n where n  was  the total number  of candidates on  the




individual list.  The  first ten of these  were  then used in  the  mailings to vehicle owners,




with number  one  being the most  desired,  number two  next  most  desired, etc.  The




selected owners were mailed a letter,  a program explanation, and a post-paid reply card.




The reply was provided to  enable the owner to supply information otherwise not  available




and to indicate  willingness to  participate.  The  letter and explanation served to solicit




participation and described the program's purpose and nature.




     Selection was  based  on the random number generated for the vehicle  in  question.




The lowest number on the returned reply cards  was contacted first.  If for some reason




the vehicle  was no longer available the  next lowest numbered vehicle owner  was then




contacted.  If a vehicle could not be acquired from returned reply cards, non-respondents




were then contacted and asked to participate.




     The mail solicatations produced  all of the test vehicles except those that  had been




available for only  a short  time and  were therefore not yet included in the registration




files.  These test vehicles  were obtained from car lots, rental car agencies, and  referrals




from other participants.
                                         2-3

-------
2.3.3 Incentives




     An incentive  package prescribed by the EPA was  offered and provided  for each




vehicle tested.  The package consisted  of:




     A  $100 U. S. Savings Bond




     A  late-model loan vehicle to serve as a substitute for the test vehicle




     Fuel for the loan vehicle




     A  full  tank of  fuel for the test vehicle upon return to its owner




2.3.4 Test Vehicle General Handling




     Vehicle owners  were contacted from  telephone numbers given on the  reply cards.




Vehicle  information was confirmed and any missing information was obtained during this




contact.  Test  schedules were also established at  this time.  Privately owned vehicles




were delivered  to the laboratory. Laboratory personnel picked up and  returned vehicles




which were  procured from rental car agencies and car lots.




     The prospective test  vehicle  was  examined  upon  arrival  at the  laboratory  to




confirm  compliance with  the  sample specification and to assure suitability for testing.




Relatively few  vehicles were  rejected at this or some  subsequent  point due to exhaust




system leakage, transmission  problems, brake problems or related  factors.  Acceptance




activities included  an  incoming vehicle  status inspection  which was used  to  limit




laboratory liability.   Test and loan vehicle exchange agreements were completed upon



acceptance  of the test  vehicle and  an EPA-furnished questionnaire was administered to




the owner.   The questionnaire  is  designed to gain  useage,  maintenance and  other




information  concerning the  vehicle.  The vehicle  was subsequently moved to a staging




area where remaining pre-test operations were completed.




     The vehicle was returned to  the staging area for depreparation procedures  and




refueling after testing  was  completed.  It  was then moved to a  parking  area where it




remained until picked up by the owner.

-------
2.4 FACILITIES AND EQUIPMENT

2.4.1 Test Location and Facility

     One permanent laboratory facility  was used  in  the study.  The location  and

elevation above sea level is as follows:

     Denver                                    '  19900 East Coif ax Avenue
                                                  Aurora, Colorado
                                                  5,480 ft

     The laboratory in Denver  is a permanent facility containing about 30,000 square

feet of office and laboratory area. The facility is situated east of Denver, two miles  (3.2

km)  from  the  city  limits.  Testing  under the  contract  was  performed  in  an  area

containing about 15,000 square feet.  Ambient air temperature was maintained through

the use of gas operated heaters and evaporative coolers.

2.4.2 Chassis Dynamometers

     The chassis dynamometer used in the study  was  Clayton Model ECE-50. The ECE-

50 has two  continuous rolls,  78  inches in length and 8 5/8  inches in diameter.  Axial

spacing  of the rolls is  17  1/4 inches.  The tach-generator was installed on the rear roll.

A counter which measured distance traveled by the test vehicle was also  installed on the

rear  roll.   Actual distance  measurements were taken which  were used  by the  data

contractor in calculating test results.  Accuracy of the counter was such that it recorded

distance traveled in increments under 0.001 of a mile.

     The dynamometer was  equipped with  a digital  speed meter  which is linear  with

speed and accurate to  within _+ 2.0 km/hr (+  1.2 mph) over the  0  to 95 km/hr (0-59 mph)

range.  It was also  equipped with a digital power meter which is accurate to ^ 0.25 hp (+

0.187 kw).

     The dynamometer  was also equipped with direct drive  inertia assemblies which

provide  125  pound inertia increments from 1000 to 5500 pounds.

     The dynamometer  was lubricated  and maintained  in  accordance  with  Clayton's

requirements.
                                        2-5

-------
2.4.3 Constant Volume Sampler

     The constant  volume sampler  (CVS)  used  was the AESI  Model 1000.  The Model

1000 is a positive displacement purnp (PDF)  type  equipped with a gas to water  heat

exchanger and six sample bags. All plumbing in the sampling and calibration systems was

of stainless steel or teflon construction. Leak light convoluted stainless steel tubing was

used to connect the CVS and the vehicle tailpipe. Several lengths were provided to keep

the exhaust run as short as practical.  Accuflex brand silicone rubber adapters were used

to connect the tubing to the tailpipe.

     Samplers  were  modified from  the  conventional  design  to facilitate  automated

sampling system evacuation/leak check.

2.4.4 Analytical Instruments

     Listed below are instrument  models, and ranges, which were part of the analytical

system used for FTP, HFET and Bagged Idle dilute sample analyses:

     2 each Beckman Model 400 FID's providing full scale C  ranges of:
           0-50 ppm, 0-100 pprn, 0-300 ppm, 0-1,000  ppm, 0-3,000 ppm and 0-10,000 ppm

     1 each TECO Model 10 CL NO  analyzer with full scale ranges of:
           0-100 ppm, 0-250 ppm, 0-1,000 ppm and 0-2,500 ppm

     2 each Horiba Model OPE-115 NDIR CO analyzer providing full scale ranges of:
           0-100 ppm, 0-500 ppm, 0-1,000 ppm, 0-.3%, 0-1%, 0-3% and 0-5%

     1 each Beckman Model 864B NDIR CO~ analyzer with full scale ranges of:
           0-2.5%, 0-4% and 0-896

     Undiluted emission analysis  (50 rnph Cruise,  Four Speed Idle, Loaded Two Mode

tests) was performed using the following analyzers and ranges:

     Chrysler Model III  C NDIR CO analyzer with full scale ranges of:
           0-300 ppm C, and 0-2,000 ppm C,
           0-0.5% CO and 0-10% CO

     TECO Model  10A CL NO  analyzer with full scale ranges of:
           0-100 ppm, 0-250 pprn, 0-1.000 ppm and 0-2,500 ppm

     Beckman Model 864 NDIR CO?  analyzer with full scale ranges of:
           0-8% and 0-1696

     The diluted and undiluted exhaust analyzers and the evaporative emission analyzers

were respectively situated within  rack-type console cabinets.  Sampling, analytical and

                                       2-6

-------
calibration system plumbing was of stainless steel or teflon construction.

2.14.5 Data_Acguisitio_n

     The following equipment was used for the acquisition of test data:

     Wet and  dry bulb temperatures  of air supplied  to  the  vehicle under  test and
     temperature of  the CVS exhaust gas/dilution air mixing point were recorded on  a
     Soltec Model DB, three channel, ink stylus, strip chart recorder, with a chart width
     of approximately eleven inches.

     Barometric pressure was recorded on a Taylor Model 6450 recording barometer.

     Soak  area temperature was recorded on  a Rustrak Model 2133, single  channel,
     pressure stylus, strip  chart recorder,  with a chart width of  approximately two
     inches and a range from 10°C to 37.5°C  (50°F to 100°F).

     The driver's aid  was an Esterline Angus two channel, off-set heat stylus, strip chart
     recorder, with a chart width  of  approximately eleven inches.  The  leading pen
     records  the dynamometer speed command signal;  the  lagging pen  records the
     feedback signal.

     Exhaust  emission analyzers were connected to Texas Instruments (Tl) Model Servo-
     riter  II,  two  channel, ink  stylus, strip chart  recorders,  with  a chart  width  of
     approximately eleven  inches and  100  division  full scale chart  paper.  Diluted CO
     and CO~ were connected  to one  of these recorders.   Diluted  HC and NO  were
     connected to a second. I 'ndiluted  CO and CO.- were connected to a third.

     Undiluted HC and NO  were recorded on a Soltec Model DB4 ink stylus, strip chart
     recorder, with a chart  of approximately  11 inches.

     CVS pump revolutions  were displayed on an electronic digital meter.

     A Data  Genet al Model Nova  II computer  was used to generate  driving  schedule
     traces and as a cross-check   to  ensure accuracy of the  analyzer  ranges.  The
     computer  also provides print-outs  of  distance  traveled by  the test  vehicle and
     integrates analyse'" and test cell temperature traces.

2.4.6 Sealed Housing for Evaporative Determination

     The evaporative emission test conducted in Denver was performed using the Sealed

Housing  for Evaporative Determination (SHED)  technique.  The SHED is primarily  of

aluminum construction.  Five expansion panels or windows, each of  two  feet  by three

feet dimensions, are situated in  the back and in one of the side walls of the enclosure.

The door of the enclosure is also designed to act as  an expansion panel. The panels are

of Tedlar construction.  The SHED  has nominal  dimensions of twenty-one feet deep  by

twelve feet wide by ten teet high.
                                        2-7

-------
     Two air-to-water heat exchangers regulated the ambient air temperature inside the



enclosure between 20 C  and  30 C (68 F and 86 F) during testing.  Each of the heaters



was  equipped with a radiator and a  propeller-type fan.  The  radiator and fan were



contained by a small aluminum enclosure with the fan located behind the  radiator.  In



this configuration  each  unit supplied about  ^50 cubic feet of air per minute.  The units



were located  in opposite corners of the SHED  with  the air flow directed  along  the



enclosure's side.  SHED  radiator pairs  were cooled with a closed  system water supply.



The temperature of the water was maintained at 21.1°C + 1.1°C (70° +_ 2° F).



     Two type 3 (iron-constantan) thermocouples were installed  on opposite walls of the



SHED to  measure enclosure  temperature.   Each was  located along  the front-to-rear



midline  of the wall, three feet  from the floor.  The  thermocouples were electrically



joined to average temperatures of the enclosure at the two points.



     A  two kw (maximum) heating blanket was used to heat vehicle tank fuel during the



diurnal (or heat build) segment of the test.  A manually adjustable rheostat controlled



power to the blanket  which, in turn,  controlled the heat-build rate  of the fuel.  To



monitor the heat-build rate,  a type 3  thermocouple was  used.   The thermocouple joint



was soldered to a cleaned area of the vehicle tank at the approximate mid-point between



tank bottom and the forty percent fuel fill line.



     A  Beckman  Model  ^fOO  FID HC  analyzer monitored hydrocarbon  concentrations



within the enclosure during the test.  Operational ranges of this analyzer were 0-50 ppm,



0-100 ppm, 0-300 ppm and 0-1,000 ppm C.



2.^.7 Laboratory Standard Calibration Gases



     A  set of secondary calibration  gas  standards was used to  calibrate the analytical



instruments. All secondary calibration standards were  identified from a set of primary



standards which, in turn, were identified by the EPA's laboratory in  Ann Arbor.



     Primary and secondary  calibration  gases were bi-blends (CO, CO- and NO  plus
                                                                     £.         X.


zero-grade N? as the diluent, HC  as propane plus zero-grade air as the diluent).

-------
     FID fuel gases were a mixture of 40% H2 and 60% N2-  Fuel for the SHED FID was




a mixture of  40% H- and 60% He. Zero gas impurities were maintained below 1 ppm C,




1 ppm CO, 400 ppm CO- and 0.1  ppm NO.  NO  calibration gases contained less than 2%
                      £.                     yV



NOr




2.4.8 Miscellaneous Equipment




     As-received  vehicle tank fuel  was analyzed for lead content.   The analysis was




performed using a Science Essentials fuel lead test kit (Mobil Method 1125-74).




     A  Hartzell Model N24DW propeller-type fan, nominally air flow rated at 5300 cubic




feet per minute, was used in connection with  dynamometer testing to supply vehicle




frontal and underhood cooling air.




     Wheel chocks and  a ratcheting-type winch were used to secure vehicles on the




dynamometer and  prevent them  from rocking  on the  roils.  A rubber belt  dressing was




applied  to drive tires immediately before cold start  testing began to reduce slippage




between the drive tires and dynamometer rolls; however, belt dressing was not applied to




the tires of vehicles subject to the SHED procedure.




     The usual complement of ignition scopes, timing lights,  tachometers,  hand tools




and  other engine diagnostic and tune-up equipment was used to perform the emission-




related  inspections, adjustments and repairs.  Special diagnostic and repair  equipment




was provided  and used as  needed.




2.5 EQUIPMENT CALIBRATION AND VERIFICATION




     Program  test  equipment  calibration and verification requirements  were  met




through  application of the following procedures.



2.5.1 Chassis  Dynamometer




     Dynamometer calibration was performed initially and confirmed each  two weeks




thereafter.




     Initial calibration included  setting  the speed meter to true  zero with the dyna-




mometer at rest followed by establishment of the upscale span point  (46.3 mph). A fixed
                                       2-9

-------
rate strobe-light was used to establish the upscale span point.  The  power meter  was




zeroed with no weight applied to the  torque  area.  A  known weight  was subsequently




applied  and the power meter was  adjusted accordingly.   Dead weight  calibration  was




followed by  dynamic  calibration  using the  coast down  technique  to establish  the




relationship between indicated and actual horsepower.




     Bi-weekly calibration confirmations included the speed point checks and the coast-




downs.  Coastdown calibrations were maintained within  + 0.746 kw (+ 1 hp) for all inertia




weights.




     Calibration of  the  driver's  aid  was checked in  relation to  the speed meter




indication  before and  after  each  test.   Pre-test driver's  aid  speed  checks were




maintained within +• 1 mph of the  indication on the dynamometer speed  meter.




2.5.2 Constant Volume Sampler




     The constant  volume  sampler  was  subjected to an  initial checkout and  flow




calibration. A Meriam Model 50-MC2-6F laminar flow  element (LFE), which has an air




flow rating of 1,000  cfm, was used  as the flow standard. LFE calibration is traceable to




the National  Bureau of Standards.  A minimum  of ten  points,  five on each  side of the




normal  set point, were measured on the CVS pump's  single range.   Auxiliary devices




employed for the calibration included:  a mercury barometer  for  measuring absolute




ambient pressure, a close  tolerance mercury thermometer  for measuring  blower  inlet




temperature, a  U-tube water manometer for measuring pressure drop  across the blower




and blower inlet pressure and a close tolerance inclined water manometer for measuring




pressure drop across the LFE.  Calibration  was such that no data point deviated more




than 0.5% from  the  least squares best-fit line through  the points measured  and that no




data point  deviated  more than 0.25%  from the  least squares best-fit  line  through all




points.




     CVS calibration was confirmed daily thereafter by propane injection and recovery.




The injected  amount  was  such as to produce  a  concentration falling  in the upper one-






                                       2-10

-------
third of the 0-300  ppm FID  range.  Recovery within + 296 of the injected amount  was



acceptable. A recovery outside the acceptable range required corrective action and  two



successive  recoveries within range before testing was resumed.



2.5.3 Analytical Instruments



     Emission  analyzers  were set-up in accordance with procedures specified by  the



manufacturers  and  subjected  to initial calibration.   FID, NO ,  CO  and CO- analyzers
                                                           A             £


were  calibrated  at seven points  spread somewhat  evenly  across each range.  Initial



calibration curves were maintained that  the actual calibration point  was within 4- 5% of



the curve value and the difference between the actual point and the curve was within •+• 1



% of the full scale value.  Complete calibrations were conducted on a monthly basis.



     Calibration curves  for  the  analyzers were subjected  to a complete check on a



weekly basis.  Each curve point was maintained within +_  1  division (100 divisions,  full



scale) of the point established in the original calibration.



     Analyzers were zeroed with zero gas and spanned on the range in-use at 80 percent



to 100 percent of full scale.



     Efficiency  of the  NO   analyzer  converter  was checked daily and  maintained



between ninety and 100 percent.



     CVS  sample bags  were purged with nitrogen, evacuated and leak-checked prior to



each test.  Other procedural precautions included zero and span point sets immediately



before  exhaust sample  analysis  and zero   and  span  point verification immediately



following  sample analysis.  Verified zero and span  points were maintained within  + 1



division of the set  points.  Noise levels of recorded analyzer outputs were maintained



within j- 0.5 divisions.



     Analyzers used for undiluted  tailpipe  emission measurements were  zeroed with



zero gas and  spanned  with  known  span gases immediately before each  test.   These



analyzers were otherwise operated in accordance with the manufacturer's specifications.
                                        2-11

-------
2.5.4 Sealed Housing for Evaporative Determination




     SHED calibrations were performed initially and each thirty days thereafter.




     After purging with fresh air the enclosure was sealed, a  background hydrocarbon




reading was obtained  and approximately four grams of instrument-grade propane were




injected into the enclosure.  Heat exchanger fans were in operation during the injection




and subsequent period.  After five minutes of mixing,  the enclosure's hydrocarbon level




was measured and the amount of piopane recovered was calculated. Recovery within +_ 2




percent of the injected amount indicated an acceptable calibration.




     A retention  test  was  performed  following  each  calibration.   The enclosure




remained sealed over an additional period of  four hours with the heat exchanger  fans in




continuous  operation.   The amount of hydrocarbon remaining in  the enclosure at the end




of this period was again measured and converted to propane by calculation.  A four hour




retention within  +  4 percent of original recovery indicated the retention quality of the




enclosure to be acceptable.




     The enclosure was initially checked for hydrocarbon background emissions.  After




purging with fresh air the enclosure was sealed, an initial hydrocarbon measurement was




taken  and  a final hydrocarbon measurement was taken four hours later.  A four hour




increase of  0.4  grams of  hydrocarbon  or  less indicated  the  enclosure's emission




characteristic to be acceptable.




2.6 TEST PROCEDURES



     Tests were  performed in the following sequence:




     Diurnal segment of the SHED tests (if applicable)




     Federal Test Procedure



     Hot loss segment of the SHED test (if applicable)




     Bagged Idle Test




     50 Cruise test




     Highway Fuel Economy Test
                                       2-12

-------
      Four Speed Idle Test




      Two Mode Loaded Test




      A flow chart of the testing flow is shown on page 2-14.




 2.6.1 Vehicle Preparation




      Subsequent to  acceptance the vehicles were drained of as-received fuel and refilled




 to forty percent of tank capacity.  A sample of fuel drained from  each vehicle was




 retained for lead analysis.   Those vehicles requiring unleaded  fuel were  supplied with




 Indolene Clear.  All others were supplied with Indolene 30.




      Subsequent to  draining but prior  to refueling, those vehicles which were scheduled




 to receive SHED tests were subjected  to a  pressure check.  The  fuel system  was first




 sealed and a stabilized pressure of fourteen  inches H~0 was applied to the  system.  Fuel




 system pressure was observed and  recorded  five  minutes  after  stabilization  was




 achieved.  A loss of 2"  l-^O or more  would indicate  a leaky evaporative  system.   The




 thermocouple used  in the  heat build  segment of the  test  was attached  to  the  tank




 following the pressure check.




      All  vehicles were operated  for a period of ten minutes on  a  predetermined road




 route subsequent to  refueling.  The purpose of this operation was to purge  non-test fuel




 from the fuel system, to bring the  vehicle to normal operating temperature and to assess



 vehicle operating characteristics.  Any moderate to severe  operating difficulties  were



 noted for  later reference in  the cold start tests.




      After  the test  preparation procedures  were completed, the  vehicle was driven  to an




 indoor, temperature  controlled area and shut down to begin the temperature stabilization




(soak) period prescribed by the  Federal Test  Procedure.




2.6.2 Equipment Preparation




     Equipment which had  been idle or in  a stand-by condition was fully  activated to




begin warm-up.  Such equipment included the  water heater and  mass pump of the CVS






                                       2-13

-------
                 FY80 EMISSION FACTORS
Schedule
Vehicle



Vehicle
Arrival



Acceptance
Inspection
i

    SHED Prep
      Soak
     Diurnal
       FTP
    Hot Soak
    505 Prep
„ M & D Repair ^
Part Replacement
  Major Tune-up
    Non-SHED
      Prep
      Soak
FTP, Bagged Idle,
50 Cruise, HFET,
Z»Spd Idle, 2Mode
                       veSr
Questionnaire
4 Agreement
i

• yes<

        SHED Test?
l)
                                  •no
        Non-SHED
          Prep
          Soak
           FTP
                           Spd Idle, 2 Mode
                            Maladjustment
                            & Disablement
                             Inspection
                              Fail FTP
                             Standards?
                   \no
                !_/
                                   yea
yes/  One of First   \no
   v50 Cars to Fail?;
                                                       Pass
                                                 \  Inspection?
                                                           no
                               Return
                              To Owner
                            2-14

-------
and each of the analytical instruments. If not subjected to extended operation in the two



hour period preceding a  test the dynamometer was  warmed-up for fifteen minutes at



thirty mph with a non test vehicle.



     With ail equipment at normal operating temperature, sensitivity  of  the constant



volume  sampler's automatic  leak  detection system was checked and  adjusted as



necessary. A leak-check of the undiluted tailpipe analytical system was also performed.



Efficiency of the NO  analyzer thermal converter was checked,  strip-chart recorders
                    X.


and other elements of the data acquisition  system were aligned with analyzer outputs



and the propane recovery test was performed.  Calibration of the dynamometer speed



meter and driver's aid recorder was also checked for accuracy and adjusted as needed.



     Other minor laboratory maintenance and pre-test requirements were attended to



during the daily three hour non-test period as needed.



2.6.3 Federal Exhaust Emission Test Procedure



     The Federal Exhaust Emission Test was performed in accordance with those parts



of 42 Federal Register 124 and as  amended in Volume 43,  No.  220 which deal with  cold



and hot start tests.



     This  test,  commonly referred  to as the Federal Test Procedure  (FTP) is  a  test



which utilizes a  constant volume sampler (CVS) and  which produces mass emission  test



results.  It is  preceded by a minimum vehicle soak period of twelve hours and a maximum



of thirty six hours during which the vehicle remaines unstarted and with all accessories



off in ambient temperatures between 20° C and 30° C (68° F and 86° F).



     At  the  end of the soak period the vehicle was placed  on  the dynamometer in



preparation for  the  cold start portion of the  test.  A cooling fan which directs air to the



vehicle only during  exhaust sampling periods  was  situated  with its center at the middle



of the vehicle grille and twelve inches away. The engine compartment hood was fully



opened and the CVS exhaust collector tube was attached to the  vehicle tailpipe.
                                       2-15

-------
     The FTP consists of  three  sampled portions.   Background air and  CVS  diluted




exhaust samples are collected for each portion.  The cold transient portion  is nominally




505 seconds long and covers a distance of 5.78 km (3.59 miles) with an average speed of




41.19 km/hr (25.6 mph). The cold stabilized portion is  nominally 869 seconds in duration




covering 6.21 km (3.86 miles) with an average speed of 25.74 km/hr (16.0 mph).  The hot




transient portion is a hot start repetition of the cold transient portion.




     Cold  transient CVS  sampling commenced with the engagement of  the  engine




starter.  The cold transient portion of the FTP driving schedule begins after the engine




starts.   The time between starter  engagement and  the point at which the engine begins




to run of its own accord is added to the sampling interval.  Also, any stall(s)  encountered




during  this or the two  subsequent  FTP portions  is added to the  sampling interval of the




portion in which it occurs.  The driving schedule is stopped when a stall occurrs at other




than an idle  mode and is  restarted from that same place after the  engine  is restarted.




Cold transient sampling is  terminated at the 505  second point of the driving schedule.




     Cold stabilized sampling begins at the 506  second point of  the driving schedule and




terminated 5 seconds after the engine stopped running  after the ignition was turned off




at the  1369 second point,  the end  of the driving schedule.  Any after-run of the engine




added to the sampling period of this test portion.




     A soak period  of ten minutes  followed  the  end of the  cold  stabilized portion.




During this period the engine and cooling fan  were off, the engine compartment was




closed  and the CVS exhaust collection tube was disconnected from the tailpipe.  At 10+^




1 minutes into the soak period, the engine compartment was re-opened, the collector




tube was reconnected  and  the engine starter was engaged once more to begin the hot




transient portion.  The fan was turned on upon engagement of the starter and sampling




also  commenced.  Hot transient  sampling continued  to the 505 second  point  of  the




schedule at which time the test was concluded.
                                       2-16

-------
2.6.4 Evaporative Emission Test Procedure




     Evaporative emission tests were performed in accordance with those parts of  41



Federal Register  164 which  deal with evaporative emission  testing,  the  Sealed  Housing




for Evaporative Determination (SHED) test.




     The SHED  test consists of two segments:  the diurnal (or heat build) segment and




the hot loss segment.




     The diurnal  segment was preceded by a soak period of eleven  to thirty-five  hours in




duration. At the  end of this period, test fuel (which was put in the vehicle  prior to the




10 minute preconditioning drive) was  drained and chilled fuel at a temperature between




10° C  and 13.2° C (50°F and 55°F) was added to forty percent of the  tank's capacity.




The vehicle was  subsequently placed  in the enclosure with the fuel filler cap  off, the




luggage compartment and all windows open and with the enclosure ventilation  system  in




operation.  The  vehicle  tank heater  (blanket)  was attached to the tank and the tank




thermocouple was connected to a recorder.  Power was applied  to  the  heater  and the




rising temperature of tank fuel  was observed.  When tank temperature reached the 15.6




C  (60°F) point,  the  vehicle tank cap  was installed,  the enclosure ventilation  systems




were  turned  off, the  enclosure was sealed  and  the  initial  hydrocarbon  background




 .^asurement was taken.  Tank  fuel was heated so that  its temperature rose  linearly




within  + 1.1° C  (+ 2°  F) from  15.6°C  to 29.1°C (60°F to 84°F) within one hour.  The




enclosure interior hydrocarbon measurements were taken at fifteen minute intervals.  At




the end of the one hour diurnal soak  period a final hydrocarbon reading was taken.  The




enclosure was opened and purged, and the  heater and thermocouple  were disconnected.




The vehicle  was  then moved to the dynamometer for the  FTP.  Maximum  permissable




time lapse between the end of the diurnal test and the start of the FTP is  one hour.




     Upon conclusion of  the FTP the vehicle was moved into the enclosure for the SHED




test's hot loss segment.  Just before  entering  the enclosure,  if driven,  the engine was




shut-down.    The enclosure ventilation  systems were  in  operation during the period
                                       2-17

-------
immediately preceding vehicle entry. The vehicle's windows and luggage compartments




were opened, SHED ventilation systems were turned off,  the enclosure was sealed and




the initial hot loss hydrocarbon background reading was obtained. The vehicle remained




in the  enclosure  for one hour.  (Hydrocarbon  measurements were taken  each fifteen




minutes).   At  the  end of this  period  the final hydrocarbon reading was taken, the




enclosure was opened and ventilated and the vehicle was removed.




     Ambient air temperatures in  the  enclosures were monitored continuously  during




each of the diurnal and hot loss  segments of  the  test.  Two electrically  connected




thermocouples placed on the front to rear centerlines of the two enclosure sidewalls




monitored the ambient air  temperature  which  was maintained between 20°C  and 30°C




(68 F and 86 F) during both segments of the test.




2.6.5 Bagged Idle  Test Procedure




     This test  followed the FTP and consisted of mass emission measurem'ents of HC,
CO, COj and  NO   with the  vehicle  operated  for three minutes  at idle  with the




transmission  is drive.   Manual  transmission vehicles were tested in neutral with the




clutch engaged.




      If  a SHED test had been performed on the vehicle  a "505"  preconditioning  cycle




was performed prior to the Bagged Idle Test. In any event the test was preceded by a six




minute + one minute engine-off soak period. A three minute sample period followed the



soak period. Sample collection was initiated at the time of starter engagement such that




engine cranking was included as part of the sample.




2.6.6 50 (mph) Cruise Test Procedure




     The 50  Cruise  Test was conducted during the three  minute fifty mph  precondi-




tioning period which preceded the Highway Fuel Economy Test. It was preceded by  a 6 +_



1 minute idle  period with the cooling fan on and the engine  compartment open.




     Undiluted  HC,  CO, CO7 and NO   emission  measurements  were  recorded
                                       2-18

-------
continuously  throughout  this  test.   Equilibrium of  vehicle speed, engine speed  and




analyzer traces  were obtained before the  reported  test readings were  bracketed  and




integrated.




2.6.7 Highway Fuel Economy Test Procedure




     The Highway  Fuel  Economy Test (HFET)  was started  within the fifteen  minute




period following  conclusion of the Bagged Idle Test.




     This test is preceded by a three  minute period of operation at 50 mph.  Within one




minute following the end of this  period the vehicle  was brought  to idle  and the HFET




driving schedule was begun.   CVS sampling  began upon commencement  of  the  driving




schedule and  continued to the end of the 765 second, 16.4 km (10.2 miles) HFET  driving




schedule.   Fuel  economy was calculated by means  of  the Federal Register-contained




carbon balance method.  Power settings, inertia  weights, emission sampling  procedures,




cooling air temperatures  and cooling fan placement and operation were identical to those




of the Federal Test Procedure.




2.6.8 Four Speed Idle Test




     Employing  volumetric  sampling, the  Four Speed  Idle  test has four  modes with




automatic transmissions and three with manual transmissions.  It is preceded by the 6+1




minute idle period with the cooling fan on  and the engine compartment open. The test




sequence is:  idle in neutral, idle at 2,500 engine rpm, idle in  neutral and  in  the case of




an automatic transmission-equipped vehicle,  idle in drive with the brakes applied. The




maximum period for each mode was thirty  seconds.  Speed and HC, CO,  CO- and NO




readings were bracketed and integrated.




2.6.9 Loaded Two Mode Test




     The Loaded Two Mode Test employs volumetric exhaust  emission sampling with the




vehicle operating at 30 rnph and 9 hp and with the engine idling and the transmission in




neutral.  Maximum duration of each mode is thirty seconds.  Speed and HC, CO, CO? and




NO were bracketed and integrated.
                                       2-19

-------
     This test is  also  preceded by the 6 +  1  minute idle  period with  the  underhood




cooling fan on and the engine compartment open.  Dynamometer inertia setting for the




cruise mode was 1,000 pounds.




2.6.10 Vehicle Inspection Procedure




     The procedure used to determine the incoming condition of test vehicles consisted




of the measurement of basic engine parameters  and  visual and functional inspections of




emission control systems, subsystems and parts.  Parameters measured were idle speed,




ignition timing, dwell and idle HC and CO emissions.  Whether the idle mixture was rich




or lean for the given vehicle was also determined by enriching the mixture with propane.




Visual inspections  were  performed to determine:  the presence or absence  of  an air




pump,  catalytic  converter,  idle  adjustment limiters,  modulators,  delay  valves,  the




routing of wires, vacuum lines and any modifications which would affect emission control




system operation.   The  fuel filler neck was inspected for tampering which would enable




the use of leaded fuel.  Functional checks were performed to  determine operational




status of the ignition, distributor,  induction,  fuel, EGR,  air injection,  PCV, exhaust and




evaporative systems.  The  engine  assembly, catalyst and cooling systems  were also




inspected.




2.6.11 Restorative Maintenance Evaluation




     The first fifty vehicles which failed one or more of the Federal HC, CO and NO



exhaust standards  were subjected  to a restorative maintenance  procedure and  then




tested again.




     The restorative maintenance  procedure consisted  of repairing all maladjusted or



disabled emission control components, replacement of defective emission control parts,




and a major tune-up as specified by the appropriate manufacturers maintenance schedule




for such  tune-up.    This  procedure was then followed  by another  complete  test




sequence, excluding SHED testing.
                                       2-20

-------
2.6.12 Daily Test Schedule Procedure




      Overall  program  scheduling  was dictated by  personnel,  equipment  and facility




availability and the time  constraint of the contract.  These  factors, as  well as site




workload requirements, dictated the daily testing rates.




      Tests were conducted on a two shift per day, five day per week basis.  Shifts  began




at 8:00 AM and 5:00 PM.  Daily equipment quality assurance and maintenance activities




took place outside of the testing schedule.




      Vehicle  acceptance activities generally took place between the morning hours of




7:00 - 9:00 and the evening hours of 5:00 - 7:00 as a convenience to participants.




2.7 DATA HANDLING




2.7.1  Data Collection




      Many parameters  directly associated with the emission tests were recorded on strip




charts.  Included  were:  temperature of  the soak  area, wet and dry bulb temperatures




of air supplied to the vehicle under  test, temperature  of the CVS dilution air/exhaust gas




mixing point  and the  output  of  each emission analyzer.  Barometric pressure was




recorded on a  seven-day circular chart. Recorders  monitoring emission analyzer outputs




were  allowed  to run continuously during  calibration  and emission analysis.   An on-line




mini-computer was used  to  integrate  analyzer  readings  during diluted  and undiluted




emission analysis and as a cross check  to verify analyzer  deflections and ranges in use.



Other test  data were manually collected and recorded.



2.7.2 Data  Handling




      After an on-site  review,  raw data  in the form of individual test packets were




delivered to the data processing department for final review and disposition.  Processing




of the raw data was performed manually.  Manual processing consisted of combining data




from the raw  data sheets to card format data forms.  Once combined, these data forms




were  assembled into the specified  collation and assembled into a packet containing all
                                       2-21

-------
 forms, instrument charts and other back up information.  The assembled packets  were




 then forwarded to the data contractor.




 2.7.3 Quality Control




     Quality  of the test data  was  assured  through  reviews and  edits  which  were




 conducted at several stages in the collection and subsequent handling processes.




     The first of two reviews was  conducted immediately after test  completion.  After




 the completion of each test sequence all data were collected and assembled into a single




 test packet.  Materials  in the test packet included:  data sheets used to  identify the




 vehicle, vehicle exchange agreements, the completed vehicle-owner  questionnaire, raw




 data sheets associated with each test in the sequence, analyzer  strip-chart recordings




 and on-line computer print-outs, cooling air temperature and humidity  recordings for




 each test in the  sequence, tank heat-build  and SHED enclosure internal temperature




 strip-chart recordings and data sheets  used to document vehicle preparation procedures




 and  inspection  results.   Upon  assembly, each  of  these  materials  was reviewed for




 completeness  and accuracy.  This  review  was  started  as  soon after  test sequence




 completion  as practicable  in an effort to have it completed before the vehicle started




 into another testing sequence or was returned to its owner.  The practice of early review




 was employed for two reasons:  to  keep  the necessity for  vehicle recall and retest to a




 minimum and to facilitate immediate feedback  to test personnel of errors and omissions




 as they emerged.  Following this part  of the quality assurance program the test packets



 were sent to the data department.




     Soak area  temperature traces, raw data sheets and strip-chart  recordings used  to




document periodic calibrations and checks of the test  equipment and other materials




common to tests on a group of vehicles were subjected to a similar review, packaged and




also sent to  the data department.




     Upon arrival in the data department, each packet was reviewed a second time for



completeness and accuracy.
                                       2-22

-------
     Federal Test Procedure and Highway Fuel Economy test results were processed and




the results inspected on a reasonability basis.  Data was  then transferred to the EPA




supplied  card  format forms and coding  checked for  consistency  to  the EPA supplied




coding formats.




     Errors found in  the  course of  on-site  reviews  were usually associated with




inconsistencies between materials in the test packet (eg,  information on the vehicle-




owner  questionnaire conflicted with that of the after-test  vehicle inspection) and errors




in transposing  data from  strip charts to  raw data  sheets  (eg,  analyzer  ranges  and




deflections).  Problems  dealt with in subsequent stages of review were most frequently




associated with insufficient verbal information backing up numerical emission component




failure and vehicle maintenance action codes  and inconsistencies in responses within the




vehicle-owner questionnaire.




2.7.1+ Calculation of Results




     Results for the mass emission tests (i.e., those employing the  CVS) were calculated




by means of the formulae of 42 Federal Register 124.  Actual distances traveled by the




test vehicle were  measured in  connection with the tests.  These distances were used by




the data contractor in the final calculations of  the  test results. Distance constants of




the 42 Federal Register 124 exhaust emission test  (FTP)  driving schedule and distance




constants of  other of the  mass emission tests  were respectively  used by ATL in the




preliminary data supplied to the data contractor.  The equations of 42 Federal Register




124 applied to the  following  tests:




     Federal Exhaust Emission Test (FTP)



     Highway Fuel Economy Test




     The carbon balance equations of 42 Federal Register 176 which take mass HC, CO




and CO- emissions into  account were used to  calculate fuel economy data for the above
                                        2-23

-------
tests.  The distance constants  associated with each test were respectively used for fuel




economy calculations, as well.




     Results of the Evaporative Emission Tests were calculated using the equations of




41 Federal Register 16*f.




     Volumetric test results were reported  as measured.  Volumetric results applied to




the following tests:




     50 Cruise test




     Four Speed Idle Test




     Loaded Two Mode Test
                                        2-2*

-------
                            3. ACKNOWLEDGEMENTS




Mr. Matt Macocha, the EPA's Project Officer, is acknowledged for his able guidance and




assistance.




Mssrs. John Shelton, Thomas Bejma and other EPA staff members are acknowledged for




their assistance in site start-up operations.
                                       3-1

-------