BACT/LEAR Clearinghouse
A Compilation Of Control
Technology Determinations
Volume IIA
Appendix G
Source Type Codes 1.0-5.0
STATE
EPA
LOCAL
00
0)
CO
Developed As Part Of A Joint Effort
Between The U.S. Environmental Protection Agency
And State And Local Air Pollution Control Agencies
-------
-------
BACT/LAER Clearinghouse
Prepared By
Emission Standards And Engineering Division
US. Environmental Protection Agency
Region V, Library
230 South Dearborn Street
Chicago, Illinois 60604
U. S. Environmental Protection Agency
Office of Air Quality Planning and Standards
Research Triangle Park, North Carolina 27711
May 1984
-------
DISCLAIMER
This report was prepared by PEDCo Environmental, Inc., Cincinnati Ohio
under Contract No 68-02-3512, Work Assignment No. 60. It has been renewed'
by the Emission Standards and Engineering Division of the Office of Air Quality
Planning and Standards, U.S. Environmental Protection Agency and approved for
publication Approval does not signify that the contents necessarily reflect
the views and policies of the U.S. Environmental Protection Agency. Mention
of trade names or commercial products is not intended to constitute endorse-
ment or recommendation for use. Copies of this report are available from the
National Technical Information Service, 5285 Port Royal Road, Springfield,
11
-------
CONTENTS
Volume
Figures iv
Acknowledgment v
Introduction 1
Background 1
Report format 2
Improvements to the system 12
Procedures for Future Submissions to the Clearinghouse 16
Appendices
A. Table 1. Index of control technology determinations .... A-l
B. Table 2. Control technology determinations by type
of source - summary of emission limitations B-l
C. Table 2A. Control technology determinations for
external combustion sources C-l
D. Detailed listing of source type codes D-l
E. Abbreviations for process and emission limits E-l
F. Format for BACT/LAER clearinghouse submittals and
instructions for completing BACT/LAER clearing-
house input summary sheet F-l
Volume IIA
G. Detailed source listings
Source type code 1.0 G-l
Source type code 2.0 G-152
Source type code 3.0 G-175
Source type code 4.0 G-255
Source type code 5.0 G-318
Volume I1B
G. (continued) Detail^ soy r^e^i-st Jims
Source type code 6.0 ".''V'l;'v'vn . , G-577
Source type code 7.0 G-723
Source type code 8.0 G-784
Source type code 9.0 G-879
Source type code 10.0 G-1031
Source type code 11.0 G-1134
Source type code 12.0 G-1178
iii
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 1780.00 MVI
____. __ __ __ __ _ _ _..._ -».___ .. __ »,_ -. _ . -» - _... .._ « ^ ...
COMPANY NAME/SITE LOCATION AL ELEC COOP INC ANDALUSIA, AL 36420
P. 0. BOC 550 CHOCTAW COUNTY
»__« ___.».. ..____ .__»_ ._«««_» »^_.w« »._....* __~_ >_~__« __ .. ._ ~ ._«.. _ . «.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 02/24/81
PERMIT NO. AL 071 ESTIMATED DATE OF START-UP 1986
DETERMINATION MADE BY ALABAMA APCD SUE ROBERTSON (205J-834-6570
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
= = = = = = = = = = = = = = = = = r = = = = = = = rr = = = = = = = = = = = = = = = === = r = = = === = = = = = = = = = === = = r = = = = r= = =:= = =====r===== = r ==rr===r ==rr===r= === ====rr= ===r== ===rr=
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
LIGNITE BOILER
4805.00 MMBTU/H EA
PM 144.0000 LB/H
631.0000 T/YR
ESP
S02 3803.0000 LB/H
16653.0000 T/YR
FGD
NOX 2883.0000 LB/H
12628.0000 T/YR
BOILER DESIGN * OPERATION
CO 470.0000 LB/H
2060.0000 T/YR
BOILER DESIGN i OPERATION
NSPS
99.80
NSPS
90.00
NSPS
BACT
NOTES
ESTIMATED STARTUP DATES
UNIT 1, 3/86 - UNIT 2, 5/91 - UNIT 3, 7/96 - UNIT 4, 9/01.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 1
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER AL-0001
SOUKCE TYPE CCDE
1.1
-------
-- DETAILED SOURCE LISTING
EXTE-NAL CCVI:'JSTICM - COAL i^.ec r.j
COMPANY N'-ME-'SITE LOCATION AMERICAN LIGNITE PRODUCTS IONE , CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 01/10/S4
PE^IIT NO. SJ 83-02 ESTIMATED TATE CT STAHT-UP--
DETCR.MI'.'VTIC-) M/DE BY EFA REGION IX JOE SLAMOVICH (<-l5)-<)~^-f.2?S
(iGENCY) (AGEK'CY CONTACT PERSON) (PHONE)
PPOCESSES SL?JECT THi?OU?'^UT POLLUTANT EMISSION LIMITS ...& BASIS
TC THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT CR PROCESS MODIFICATION ... PCT EFF
CC:-'.I;'J37C°, FLUIDIZED BED 23.30 7/H
N02 61.5000 LB/H
CIKCULATIK'3 FLUIFIZED BED
CO 3"+. 2000 LB.-H
CIRCULATING FLUIDIZED BED
S02 65.COOC LB-'H
LIMESTONE INJECTION 94.30
PM 7.5COO LB/H
BAGHOUSE 99.90
NOTES -----------
INITIAL REVIEW POST STARTUP
(*> INDICATES DATUM W?S TPUNCATCD FC1? THIS TADLE. REVIE!! STATUS:
PAGE G- 2 ID N'Jt'BER CA-OOsSA SOV^CE TYPE CCDE 1.1
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 17.00 MW
COMPANY NAME/SITE LOCATION AMERICAN LIGNITE PROD. CO. IONE, CA
DETERMINATION IS DATE OF PERMIT ISSUANCE 12/21/83
PERMIT NO. ESTIMATED DATE OF START-UP 1985
DETERMINATION MADE BY AMADOR COUNTY APCD EARL WITHYCOMBE (916)-862-1233
(AGENCY) (AGENCY CONTACT PERSON) ( FHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FLUID BED COMBUSTION
240.00 MM3TU/H
PM 0.0156 GR/DSCF
BAGHOUSE
S02 115.0000 PFM
LIMESTONE BED
1.5X S FUEL
NOX 150.0000 PFM
FLUID BED
STAGED COMBUSTION
CO 138.0000 PPM
STAGED COMBUSTION
BACT
99.93
BACT
94.25
BACT
BACT
NOTES
RECIRCULATING FLUID BED INCREASES S02/LIMESTONE INTERACTION AND CAPTURE, MAINTENANCE OF BED TEMPERATURE AT 1560 F KEEPS NOX PR
CDUCTION LOW, BAGHOUSE FOLLOWS RECIRCULATIK'G CYCLONE ANO MULTICLONE FOR PARTICULATE CONTROL.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 3
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER CA-004S
SOURCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
C5/22/19S<+
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 350.00 MM
COMPANY NAME/SITE LOCATION ARIZONA PUBLIC SERVICE CO., CHOLLA UNIT* JOSEPH CITY, AZ
-- . *. ^ ___ _ __ __ _______«. ____.________-.__ _______
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 02/15/78
PERMIT KO. AZP 78-01 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION IX JIM HANSON (415 )-97<+-8038
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
" _ __ »__ «.___-._____ __ __«.____.____________ __,_ _ ___»»_»_____ _________ _ _______,, __ _..__
COAL FIRED BOILER 350.00 MW
PM 0.0500 LB/MM3TU
ESP
S02 0.0720 LB/MM3TU
U'ET LIMESTONE SCRUBBING 94.00
LOW S COAL
NOX 0.7000 LB/MN3TU NSPS
COAL HANDLING AREAS
PM
DUST CONTROL SYS
LIMESTONE HANDLING AREAS
PM
DUST CONTROL SYS
NOTES
THE DEGREE OF CONTROL WAS PROPOSED BY CO. IN ITS APPLICATION. FUGITIVE D UST SHALL BE CONTROLLED DURING CONSTRUCTION BY WATER
SPRAY. BOTTOM ASH SHALL BE PUMPED TO A SPRAY POND. ASH SHALL BE MIXED WITH WASTE SLUDGE FROM S02 ABSORBERS AK'D OR
HASTEWATER FROM COOLING TOWER AND TRANSPROTED IN A SLURRY TO A SEPERATE DISPOSIAL AREA
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- <+ ID NUMBER AZ-0003 SOl'"CE TYPE CODE 1.1
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 800.00 KM
COMPANY NAME/SITE LOCATION ARKANSAS PUR & LT CO. NEWARK, AR
INDEPENDENCE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/30/78
PERMIT NO. PSD-AR-48 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214 )-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
~^ -. » _____«.«_ _ -. > _____ __ _____,. .,fc.._»,-,»_____ _ _ . ,.»^._ «... _.._ __ «. __ -,__ ««. « _ _.. _ v __ _ «. ^ _ ____.«._ __. «.^^___ _^_______^»_ «. ._
COAL-FIRED STEAM GEN 800.00 MM
S02 0.9300 LB/MMBTU NSPS
LOW S WESTERN COAL
PM 0.1000 LB/MI-IBTU
ESP 99.50
NOTES
TMTTTftL crviEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FCR THIS TABLE. REVIEW STATUS: 0^/01/1983
PAGES- 5 ic ;':;.> :.- . . . . ,-_ ^^i 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/23/1934
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 730.00 HW
COMPANf NAME/SITE LOCATION ASSOC. ELECT. COOP., INC. , MO
THOMAS HILL STATION RANDOLPH CCUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 02/06/78
PERMIT NO. ESTIMATED DATE OF START-UP-- 1982
DETERMINATION MADE BY EPA REGION VII DANIEL RODRIGUEZ (816)-374-65£5
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
BOILER, COAL FIRED (UNIT 3), PU* 6588.00 MMBTU/H
S02 1.2000 LB/MMBTU BACT
WET LIMESTONE SCRUBBER 90.00
PM 0.1000 LB/MM3TU BACT
COLD-SIDE ESP 99.70
NOX 0.7000 LB/rr.3TU NSPS
BOILER DESIGN
NOTES
PLANT NAME- THOMAS HILL (EXISTING UNIT 1 - 180MVJ, NET, EXISTING UNIT Z - 303 KV4, NET). THE NEW UNIT 3 IS SUBJECT TO NSFS, SUSP
ART D. EXISTING UNITS 1 AND 2 WILL BE LIMITED TO 8.0 LB S02/MMBTU (3-HR. AVG. ) BECAUSE OF POSSIBLE
AMBIENT STANDARD VIOLATIONS. THE EXISTING UNITS WILL BURN WASHED COAL (4.5X S BY WT.). UNIT 3 WILL BURN UNWASHED COAL (5.57. S
BY WT.). MISSOURI COAL
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 6
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1953
ID NUMBER MO-0002
SOURCE TYPE CODE
1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/193
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 1500.00 KW
-.-.«- .. . ,. ._ _ _-.___..__________ _________,._______.__,..____________._ ___________
COMPANY NAME/SITE LOCATION BASIN ELECTRIC POWER COOP. WHEATLANO, WY
_ .._____,.,».. _ ___ »_____ _ _ _ _________ __________.__»__» _ _ - _ __...___-...___.,_« ______ -»___«.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 05/14/76
PERMIT NO. CT-36 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY WYOMING AQD ECKART HAAS (307)-777-7391
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICAT^4 ... PCT EFF
*"- _ __.__._ ___.-.-____ __.«.___«,___....___ ..__ .».__».«.,_____* ,_______ ____ _.»_._ __ __,___...____ _____ __ ___»___ ____., _____H_>«__^
BOILER, COAL, 2 EA 5513.62 MM3TU/H
S02 0.2000 LB/t-fttBTU NSPS
FGQ, WET LIMESTONE SCRUBBER 90.00
PM 0.1000 LB/MH3TU NSPS
ESP 99.50
BOILER, COAL 5513.62 MMBTU/H
S02 0.2000 LB/MMBTU NSPS
FGD, DRY LIME SCRUBBER 90.00
PM 0.1000 LB/MKBTU NSPS
ESP 99.50
NOTES
UNIT 1 START UP WAS 07/01/80. UNIT 2 START UP WAS 07/01/81. UNIT 3, THE FIRST FULL-SCALE DRY SCRUBBER INSTALLED CM A LARGE STE
Aft GENERATOR IN THE U.S., IS PRESENTLY UNDERGOING S'u'BS~ANTIAL MOD. TO MEET S02 EMISSION LIMITS.
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 8 ID HUI1BER WY-0013 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
EXTERNAL COMBUSTION - COAL
880.00 MM
COMPANY NAME/SITE LOCATION BIG RIVERS ELECT. -D.B. WILSON STATION
D.B. WILSON STATION
LIVERMORE, KY 42352
OHIO COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. C-80-41
DETERMINATION MADE BY KENTUCKY DAPC
(AGENCY)
BILL DILLS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 03/11/81
ESTIMATED DATE OF START-UP 1964
< 502 )-564-33S2
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
8 BASIS
PCT EFF
BOILER, COAL FIRED
4585.00 MMBTU/H EA
COAL HANDLING
LIMESTONE HANDLING
NOTES ------ .....
2 C04L FIRED 440 MM BOILERS
3281.00 MT/YR
279000.00 T/YR
PM
S02
NOX
PM
PM
0.0300 LB/MMBTU
ESP
1.2000 LB/MMBTU
WET SCRUBBER
0.6000 LB/M!13TU
BOILER DESIGN & OPERATION
LIMITED OPERATING COrrDITIONS
LIMITED OPERATING CONDITIONS
BACT
99. SO
BACT
90.00
BACT
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 9
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID KLI'.r.ER Ki-0009
SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 2<+6.00 MW
COMPANY NAME/SITE LOCATION BOARD OF PUBLIC UTILITIES KANSAS CITY, KS
WYAMDOTTE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/29/76
PERMIT NO. ESTIMATED DATE OF START-UP-- 1931
DETERMINATION MADE BY EPA REGION VII CHARLES WHITMORE (8161-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PKONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED COts'TROL EQUIPMENT OR PROCESS MODIFICATION . . . PCT EFF
BOILER, COAL FIRED, PULV. 346.00 MW
S02 1.2000 LB/MflBTU BACT
LOW S WESTERN COAL
PM 0.1000 LB/Mr;BTU NSPS
ESP
NOX 0.7000 LB/MMBTU NSPS
BOILER DESIGN
NOTES
PLANT NAME: NEARMAN CREEK. THE UNIT IS SUBJECT TO NSPS, SUSPART D.
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: Gn/01/1933
PAGE G- 10 ID NUMBER KS-0012 SOURCE TYPE CCDE 1.1
-------
APPEKDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL
..___ ,-,____ _____.______.,__ _____.»____ __ ..-._ _.. . -. .
COMPANY NAME/SITE LOCATION B.F. GOODRICH HENRY, IL
MARSHALL COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/16/82
PERMIT NO. 82 03 0046 ESTIMATED DATE OF START-UP 1985
DETERMINATION MADE BY ILLINOIS EPA CHRIS ROMAINE (217J-7S2-2113
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
BOILER, FLUIDIZED BED, RECIRCUL*
150.00 MKBTU/H
PM 0.0600 LB/MMBTU
CYCLONE 4 BAGHOUSE
S02 1.2000 L6/r;^3TU
85.0000 7. REDUCTION
FLUIDIZED LIMESTONE BED
NOX 0.6000 LB/^:BTU
EQUIPMENT DESIGN
CO 400.0000 PFM
EQUIPMENT DESIGN
BACT
99.00
BACT
BACT
BACT
NOTES
CO EMISSION IS SUBJECT TO REVISION BASED UPON RESULTS OF TRIAL OPERATION.
(»> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 11
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NCM3ER IL-0021
SOURCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE
EXTERNAL COMBUSTION - COAL
6507.00 MMBTU/H
COMPANY NAME/SITE LOCATION CAJUN ELECT. POWER COOP.
COUSHATTA, LA
RED RIVER PARISH
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-LA-106
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 03/25/80
ESTIMATED DATE OF START-UP 1935
( PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT
TO THIS PERMIT CAPACITY EMITTED
BOILER, LIGNITE FIRED 6507.00 MMBTU/H
PM
S02
NOX
CO
EMISSION LIMITS ... t BASIS
CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
0.0300 LB/MMBTU
ELECTROSTATIC PRECIPITATOR
1.0800 LB/MM3TU
LIME/LIMESTONE SCRUBBER
0.6000 LB/fiMBTU
02 CONTROL
0.0900 LB/MM3TU
02 CONTROL
NSPS
99.95
80.00
COAL PILES
COAL HANDLING
LIME/LIMESTONE HANDLING AND PIL*
PM 20.7000 LB/H
COMPACTION, CRUSTING AGENT
PM 1.6000'LB/H
BAG FILTER
PM 2.1000 LB/H
BAG FILTER
99.90
99.90
NOTES
A REQUEST FOR PERMIT MODIFICATION WAS RECEIVED AND IS CURRENTLY UNDER REVIEW. BACT WILL BE CHANGED. S02 LIMIT MAY BE EXPRESSED
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 12
INITIAL REVIEU POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER LA-0006
SOURCE TYPE CODE 1.1
-------
AS 0.6 LB/MKBTU, 30-DAY ROLLING AVG.
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
- - - 3 r~r = ±rr~z = rzzr = zr~ = -rrzrrsrzrzssr = z = -~z - = = = - = = = = = = = = = = = = = = = = ~ = = = -:= = = ~~ ~"
PAGE G- 13 ID NUMBER LA-0006 SOURCE TYPE COOE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE---
EXTERNAL COMBUSTION - COAL
6781.00 KMBTU/H
COMPANY NAME/SITE LOCATION CENTRAL POWER & LIGHT
FANNIN, TX
GOLIAD COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-TX-365
DETERMINATION HADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/19/81
ESTIMATED DATE OF START-UP 1933
(2141-767-1594
( FHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COAL FIRED BOILER 6781.00 MMBTU/H
PM 0.0300
S02 0.3900
NOX 0.5000
CO 0.0600
COAL DUMPER, ROTARY 11000.00 T/D COAL
PM 29.7600
149.8000
CONVEYOR TO SAMPLE HOUSE
PM 2.4000
11.7500
CONVEYOR TO ACTIVE PILE
PM 2.2500
2.2500
LB/MMBTU
ELECTROSTATIC PRECIPITATOS
LS/Kr.3TU
FLUE GAS DESULFURIZATION
LB/MN3TU
FIRE BOX DESIGN & 02 CONTROL
LB/MMBTU
02 CONTROL OPTIMAL WITH NOX
LB/H
LB/D
WET SUPPRESSION
LB/H
LB/D
COVERS, WET SUPPRESSION
LB/H
LB/D
TELESCOPIC CHUTE
NSPS
99.60
NSPS
99.60
NSFS
BACT
BACT
50.00
BACT
99.00
BACT
99.00
COVERS, WET SUPPRESSION
PAGE G- 14
-------
(CONTINUED) CENTRAL POWER & LIGHT
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
ACTIVE COAL PILE
INACTIVE COAL PILE
COAL CONVEYOR TO TRANSFER HOUSE
COAL CONVEYOR TO BOILER
FLYASH HANDLING
LIMESTONE CAR DUMP
LIMESTONE CONVEYOR TO STORAGE
LIMESTONE CONVEYOR TO BINS
= = = = = = = = = r = = = = = = = r = = = = r = = sr = s = = = s = ::r = = = = = = = = = r = = = r=r = = = = = :: = = = = = = :::r
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
PM 5.7800 LB/H
COMPACTION & WET SUPPRESSION
PM 2.5000 LB/H
COMPACTION
PM 2.3200 LB/H
6.7200 LB/D
COVERS, WET SUPPRESSION
PM 4.6300 LB/H
13.4400 LB/D
COVERS, WET SUPPRESSION
PM 0.2800 LB/H
1.7000 LB/D
BAG FILTERS
PNEUMATIC CONVEYOR TO SILO
PM 2.7000 LB/H
24.2900 LB/WK
NONE
PM 0.3500 LB/H
3.1200 LB/WK
COVERED BAG COLLECTOR
PM 0.4000 LB/H
3.6000 LB/UX
COVERED BAG COLLECTOR
... £ BASIS
... PCT EFF
BACT
BACT
90.00
BACT
99.00
BACT
99.00
BACT
99.00
BACT
BACT
98.00
BACT
93.00
PAGE G- 15
-------
(CONTINUED) CENTRAL POWER 4 LIGHT
PROCESSES SUBJECT
TO THIS PERMIT
LIMESTONE STORAGE PILE
LIMESTONE RECLAIM
COAL SAMPLE HOUSE
COAL TRANSFER HOUSE
LIMESTONE SILOS
LIMESTONE TRANSFER HOUSE
THROUGHPUT POLLUTANT EMISSION LIMITS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
PM 0.0480 LB/H
NONE
PM 19.9000 LB/H
179.5200 LB/HK
NONE
PM 7.0000 LB/H
34.3000 LB/D
WET SUPPRESSION & COVERED CONVEYORS
PM 7.0000 LB/H
34.3000 LB/D
COVERED CONVEYORS
WET SUPPRESS.* COVERED CONVEY.
PM 0.3500 LB/H
3.1500 LB/WK
BAG FILTER
PM 0.1900 LB/H
1.7100 LB/KK
BAG FILTER
... & BASIS
... PCT EFF
BACT
BACT
BACT
99.00
BACT
99.00
BACT
99.00
BACT
99.00
ENCLOSED CONVEYOR
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 16
INITIAL KVIEW POST STARTUP
REVIEW STATUS-- 0^/01/1933
ID NUMBER TX-0009
SOURCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE-
EXTERNAL COMBUSTION - COAL
1200.00 MW
COMPANY NAME/SITE LOCATION CINCINATI GAS t ELECTRIC CO. - EAST BEN*
KY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. 0-82-072
DETERMINATION MADE BY KENTUCKY DAPC
(AGENCY)
B&LL OfLLS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 05/14/82
ESTIMATED DATE OF START-UP 1981
(502)-564-33S2
(FHCNE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
WIT 82
6313.00 MM3TU/H
UNIT 81
6270.00 MMBTU/H
PM 0.1000 LB/MMBTU
2970.0000 T/YR
ESP, WET SCRUBBER
S02 1.2000 LB/MMBTU
35640.0000 T/YR
WET SCRUBBER
NOX 0.7000 LB/MMBTU
20790.0000 T/YR
PM 0.1000 LB/MMBTU
1650.0000 T/YR
ESP
S02 0.8400 LB/MMBTU
13860.0000 T/YR
WET SCRUBBER
NOX 0.7000 LB/MMBTU
11550.0000 T/YR
99.60
81.50
99.50
85.00
NOTES
PERMIT COVERS ONLY UNIT S2. UNIT SI CONSTRUCTION PERMIT C-78-51 ON 8/25/78
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 17 ID NUMBER KY-0030
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933 02/13/1934
SC'JPCE TYPE CODE 1.1
-------
EST. DATE OF START-UP UNIT *1 IS 01/86.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933 02/13/1984
PAGE G- 18 ID NUMBER KY-0030 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 92.50 MMBTU/H
COMPANY NAME/SITE LOCATION CITY OF WILKES-BARRE WILKES-BARRE, PA
LUZERUE COlflfTY
^____ ^___ ____ ___ __ __ _ . - ~ ~
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 07/01/80
PERMIT NO. 79PA23 ESTIMATED DATE OF START-UP 1980
DETERMINATION MADE BY EPA REGION III DAVID ARNOLD ( 215J-597-793&
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER 92.50 MMBTU/H
PM 8.0000 LB/H BACT
BAGHCUSE/CYCLONE 99.70
S02 199.0000 LB/H BACT
1.5000 LB/MMBTU
S IN FUEL
NOTES
INITIAL REVIEW POST STARTUP
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 19 ID NUMBER PA-0020 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL
COMPANY NAME/SITE LOCATION COLORADO UTE-CRAIG UNIT 93
DETERMINATION IS FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MADE BY EPA REGION VIII
( AGENCY )
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
RR CAR 1.87 MMT/YR
ASH SILO VENT 355.00 MT/YR
ASH UNLOAD 355.00 MT/YR
BOILER, 440 MW 214.00 T/H
NEAR
JOHN DALE
(AGENCY CONTACT PERSON)
POLLUTANT EMISSION LIMITS
1320.00 MW
CRAIG, CO
MOFFAT COUNTY
DATE OF PERMIT ISSUANCE-- 03/27/80
ESTIMATED DATE OF START-UP
(303)-837-3763
( PKOUE )
... & BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
PM 1.0000 T/YR
FF
PM 149.0000 T/YR
FF
PM 34.0000 T/YR
HYDROMIXER
CO
NO CONTROL
VOC
NO CONTROL
NOX 0.5000 LB/W.STU
BOILER DESIGN
PM 0.0300 LB/MM3TU
BAGHOUSE
S02 0.2000 LB/KM3TU
DRY SCRUBBER
BACT
99.80
BACT
99.80
BACT
59.00
BACT
BACT
BACT
65.00
BACT
99.60
BACT
90.00
PAGE G- 20
-------
(CONTINUED) COLORADO UTE-CRAIG UNIT 83
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
* BASIS
PCT EFF
COAL PILE
CONV.
LIME TRANS./STORAGE
TRANS PTS.
1.87 MMT/YR
1.87 MMT/YR
37.40 MT/YR
1.87 MMT/YR
PM
PM
PM
PM
5.0000 T/YR
SURFACTANT
5.0000 T/YR
ENCLOSURES
0.0000 T/YR
FF
0.0000 T/YR
ENC + FF
BACT
85.00
BACT
90.00
BACT
99.80
BACT
99.80
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 21
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NUMBER CO-0007
SCU3CE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 137.00 MMBTU/H
COMPANY NAME/SITE LOCATION CURTISS-KRIGHT CORP. WOOD-RIDGE, NJ 07075
1 PASSAIC ST. BERGEN COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 06/13/80
PERMIT NO. ESTIMATED DATE Or START-UP--
DETERMINATION MADE BY EPA REGION II STEVE RIVA (212J-264-S6S4
(AGENCY) (AGENCY CONTACT PERSON) (FHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...& BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ _ _ _.. _ _ -- __ ..__ -. __ _ _ _«._
PFB BOILER 137.00 MMBTU/H
S02 0.3000 LB/MMBTU SIP
PROCESS MOD. 93.00
CALCIUM/SULFUR, 2/1
PM NONE
PROCESS CYCLONES
NOX NONE
CO NONE
NOTES
TEMPORARY SOURCE - NOT TO OPERATE IN EXCESS OF 3100 H/YR FOR A PERIOD NOT TO EXCEED TWO YEARS FROM START-UP.
INITIAL REVIEU POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/19S3
PAGE G- 22 ID NUMBER NJ-OOO^f SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 550.00 MW
COMPANY NAME/SITE LOCATION DELMARVA POWER 8 LIGHT VIENNA, HD 21869
DORCHESTER COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/30/81
PERMIT NO. 80HT201 ESTIMATED DATE OF START-UP-- 1983
DETERMINATION MADE BY EPA REGION III VERNON BUTLER (2151-597-8711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER
5702.00 MMBTU/H
BOILERS & STORAGE PILES
1.20 HMT/YR
S02 0.6000 LB/M3TU
70.0000 /. EMISSION REDUCTION
SCRU3BER
NOX 0.6000 LB/M3TU
65.0000 /. EMISSION REDUCTION
BURNER DESIGN
CO 0.0400 LB/MBTU
BURNER DESIGN
VOC 0.0100 LB/K3TU
BURNER DESIGN
VE 20.0000 /. OPACITY STACK
PM 0.0300 LB/M3TU
ESP
DUST-SUPPRESSANT LIQUID
BACT
90.00
BACT
BACT
BACT
BACT
BACT
99.65
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 23
INITIAL REVIEW POST STARTUP
S.ATU5: 0^/01/1983
ID NUMBER MD-000^
SCU.7CE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
EXTERNAL COMBUSTION - COAL
800.00 MW
COMPANY NAME/SITE LOCATION DESERET GEN & TRANS, MOON LAKE
NEAR BONANZA, UT
UINTAH COUNTY
DETERMINATION IS
PERMIT NO.
DETERMINATION MADE BY
EPA REGION VIII
(AGENCY)
JOHN DALE
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 02/04/60
ESTIMATED DATE OF START-UP-- 19S4
(303J-S37-3763
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
COAL CONV
COAL CRUSHER
COAL STORAGE
LIMESTONE HAND.
BOILERS, COAL-FIRED, 2 EA
THROUGHPUT POLLUTANT
CAPACITY EMITTED
475.00 T/H COAL
PM
VE
2.70 MMT/YR
PM
VE
2.70 MMT/YR
PM
VE
55.60 MT/YR
FM
VE
400.00 MW
CO
VOC
NOX
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
1.0000 T/YR
ENC t FF
20.0000 y. OPACITY
1.0000 T/YR
ENC i FF
20.0000 7. OPACITY
2.0000 T/YR
WET SUP
20.0000 /. OPACITY
1.0000 T/YR
ENC & FF
20.0000 '/. OPACITY
NO CONTROL
NO CONTROL
0.5500 LB/N"BTU
... & BASIS
... PCT EFF
BACT
99.00
BACT
99.00
BACT
50.00
BACT
90.00
BACT
BACT
BACT
PAGE G- 24
-------
BOILER DESIGN
PM 0.0300 LB/MMBTU
0.0200 GR/DSCF
FF
S02 418.0000 LB/H
0.0550 LB/KMBTU
WET SCRUBBER
VE 20.0000 7. OPACITY
99.60
BACT
99.60
BACT
94.00
NOTES
CEH QA REQUIRED BY 40CFR, PART 60, SUBPART DA. BOILER EMISSION COMPLIANCE FOR S02,
RTS. VE IS STATEPERMIT REQUIREMENT.
NOX, OPACITY WILL BE DETERMINED BY CEM REPO
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE 6- 25
INITIAL ftVIEW POST STARTUP
REVIEW STATUS: 04/01/1°S3
ID NUSER UT-0006
SOURCE TYPE CCDE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 526.00 HW MOD.
COMPANY NAME/SITE LOCATION EAST KENTUCKY POWER COOP. MAYSVILLE, KY 40391
P.O. BOX 707 MASON COUNTY
-, _ _-._ __
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 12/02/76
PERMIT NO. C-76-46 ESTIMATED DATE OF START-UP 1931
DETERMINATION MADE BY KENTUCKY DAPC BILL DILLS (502J-564-3332
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
__»_.._...- __ _.- _. _._ __..__: _ -. -._ ~ _«-, __ _ _-.__..
BOILER, PULV., COAL FIRED, DRY * 6760.00 MMBTU/H
PM 0.1000 LB/MMBTU
HOT SIDE ESP 99.50
PB
HOT SIDE ESP 99.50
S02 1.2000 LB/MM3TU
0.72X S IN FUEL
CO
NOX 0.7000 LB/M!'i3TU
NOTES
UfUT NlfMBER 2
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: C4/01/1933 02/13/1934
PAGE G- 26 ID NUMBER KY-0018 SOLACE T\PE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 670.00 MMBTU/H
COMPANY NAME/SITE LOCATION EASTMAN KODAK CO., KODAK PARK DIV. ROCHESTER, NY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 13/20/82
PERMIT NO. C262800 025 00004 ESTIMATED DATE OF START-UP 1936
DETERMINATION MADE BY NEW YORK DEC FRANK SHATTUCK (716)-£26-246&
(AGENCY) (AGENCY CONTACT PERSON) (PhCNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, COAL FIRED
670.00 MMBTU/H
COAL CAR UNLOADER
CRUSHING
BUNKER
PM
S02
NOX
CO
BE
PM
PM
PM
0.0350 LB/MMBTU
ESP
1.2000 LB/MM3TU
LOU S COAL
0.7000 L6/MM3TU
CCM3USTION CONTROL
o.o<+50 LB/M;;BTU
COMBUSTION CONTROL
0.0010 LB/H
ESP
1.1000 LB/H
FABRIC FILTER
0.7500 LB/H
FABRIC FILTER
0.0230 LB/H
BACT
99.57
BACT
BACT
BACT
BACT
98.40
BACT
99.00
BACT
99.00
BACT
PAGE G- 27
-------
(CONTINUED) EASTMAN KODAK CO., KODAK PARK DIV.
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
ASH HANDLING
PM 0.0750 LB/H BACT
FABRIC FILTER 99.00
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE 6- 28 ID NUMBER NY-0004 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
EXTERNAL COMBUSTION - COAL
600.00 MW, 2 EA
COMPANY NAME/SITE LOCATION E. KENTUCKY POWER CORP.
J.K. SMITH POWER STATION
TRAPP, KY
CLARK COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. C-80-67
DETERMINATION MADE BY KENTUCKY DAPC
(AGEUCY)
BILL DILLS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 08/21/80
ESTIMATED DATE OF START-UP-- 1992
(5C2)-564-33S2
(PHOHE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, COAL FIRED 6760.00 MMBTU/H EA
PM 0.0300 LB/MMBTU
ESP
S02 1.2000 LB/MMBTU
WET SCRUBBER
NOX 0.6000 LB/MHBTU
BOILER DESIGN
BOILER, COAL FIRED 6760.00 MKBTU/H
PM 0.0300 LB/MMBTU
ESP
S02 1.2000 LB/MMBTU
WET SCRUBBER
NOX 0.6000 LB/MMBTU
BOILER DESIGN
BACT
99.80
BACT
90.00
BACT
BACT
99.80
BACT
90.00
BACT
NOTES
STARTUP UNIT 1, 8/92 UNIT 2, 8/93
(«) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 29
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER KY-OC03
SOURCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1934
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 1220.00 BTU/H
COMPANY NAME/SITE LOCATION FLORIDA POWER CORP. CRYSTAL RIVER, FLA., FL 33733
CITRUS COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 01/15/80
PERMIT NO. AC52-36102 ESTIMATED DATE OF START-UP 1933
DETERMINATION MADE BY FLORIDA DER BOB KING < 904 )-4S3-134<*
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
__ _ _»_ __.. -. ______ ____ ..__ ___-,_____ __ ____ -. __ ....., «._ __ ____ ____ ._ .
FLY ASH HANDLING UNITS 55000.00 LB/H
PM 4.0000 LB/H BACT
BAGHOUSE 99.90
NOTES
ADDED ESP TO EXISTING BOILER
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PiGE G- 30
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04'01/19S3 01/25/1934
ID NUMBER FL-0013
SCL'SCE TYPE CODE 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COM3USTION - COAL 58.00 HW
COMPANY NAME/SITE LOCATION GRAND HAVEN BOARD OF LT 4 PRR GRAND HAVEN, MI 49417
HARBOR ISLAND MUSKEGON COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/18/80
PERMIT NO. 541-79 ESTIMATED DATE OF START-UP-- 1933
DETERMINATION MADE BY MICHIGAN DNR GREGORY EDWARDS (5171-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COAL-FIRED BOILER 710.00 MMBTU/H
PM 0.0300 LB/MMBTU
ESP 99.60
SO2 0.8400 LB/MHBTU 300 AV
0.8000 LB/W3TU 24H AV
LIME SLURRY WET SCRUBBER 90.00
NOX 0.6000 LB/Mr.3TU 30D AV
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933 03/13/1964
PAGE G- 31 ID NUMBER MI-0004 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTINS
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 490.00 MW
«, __ -._____.
COMPANY NAME/SITE LOCATION GRAND RIVER DAM AUTHORITY . OK 74361
HAYES COUNTY
__.__ ,.__ ____ ..-._
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/30/78
PERMIT NO. PSD-CK-51 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (£14)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
FROCESSCS SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
.
COAL FIRED GEN STATION 490.00 MW
S02 1.2000 LB/MHBTU
6157.2000 LB/H
LOW S COAL
PM o.iooo LB/nr:sTU
513.1000 LB/H
NOTES
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
~~--~z~-~ = = ~~~~-~- = = ~ = = ~ ~- = = ^-~~ = ~~------~~ = ~--~--~'~~~~='~~ = ~~ = -~~ = ~ = ===-~~ = = = = ===~ = ~-~~=-^-----~~-~ = ~='~~-~~~~~~~~~~~~='~ = ~~~= ===~
PAGE G- 32 ID HUt'BER OK-0001 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE - EXTERNAL COMBUSTION - COAL
COMPANY NAME/SITE LOCATION HOLVOKE WATER POMER CO., MT. TOM PUR PL* HOLYOKE, MA
DETERMINATION IS PACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/27/82
PERMIT NO. AFPR. LTR 10-27-82 ESTIMATED DATE OF START-UP-- 1981
DETERMINATION MADE BY MASSACHUSETTS DEQE - AIR DAVID HOWLAND (617)-727-8640
(AGENCY) (AGENCY CONTACT PERSON) ( FHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PEP-MIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . . . PCT EFF
COAL COMBUSTION 1447.00 MM8TU/H
S 1.2100 LB/MMBTU MONTHLY AV PACT
1.6000 LB/MM3TU DAILY AV
PM O.OSOO LB/HH3TU PACT
ESP 99.51
NOX
NOTES
Of.'E UNIT - 155 MM. VOLUNTARY COAL CONVERSION
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 33 ID N'JtiSER MA-OC05 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 550.00 MW
COMPANY NAME/SITE LOCATION HOUSTON LIGHTING * POWER HOUSTON, TX
-. .._,___ _ ___ _ ___ __-. ___ ..___..___,_
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 10/28/77
PERMIT NO. PSD-TX-33 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI TOM DIGGS (214 )-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...& BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- - -- ». ___ _ _..__..__»,.__ _ -.___.. ____.. __ ____ ________ _ __ __.«. ___ _ ___ __., ____ ___. __. ^. __^____.«__ _
COAL FIRED STEAM ELECT. GEN 550.00 MW
S02 1.2000 LB/MMBTU
573.0000 LB/H
LOM S WESTERN COAL
PM 0.1000 LB/M"3TU
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 34
INITIAL S^-IVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUI13ER TX-0005
SOURCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE
EXTERNAL COMSUSTION - COAL
550.00 MM
COMPANY NAME/SITE LOCATION HOUSTON LIGHTING & POWER
THOMPSONS, TX
FORT BEND COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT HO. PSD-TX-234
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 11/12/81
ESTIMATED DATE OF START-UP
( PHONE )
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
COAL FIRED BOILER
5729.00 MMBTU/H
LIMESTONE UNLOAD
ACTIVE LIMESTONE PILE
INACTIVE LIMESTONE PILE
S02 0.3600 LB/MMBTU
LIMESTONE SCRU3BER
NOX 0.5000 LB/MM3TU
02 CONTROLS, TANGENTIAL BURNERS
CO 0.0590 LB/MM3TU
02 CONTROLS
PM 0.0300 LB/r.r
-------
(CONTINUED) HOUSTON LIGHTING & POHER
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
& B4SIS
FCT EfF
LIMESTONE CONVEYERS fc TRANSFER *
LIMESTONE CRUSHER
LIMESTONE FEED SILO
FLY ASH MIX TANK
PM
PM
PM
PM
0.5000 LB/H
ENCLOSED
0.1000 LB/H
BAGHOUSE
0.1000 LB/H
BAGHOUSE
0.7000 LB/H
WILL BE A SLURRY
BACT
90.00
BACT
99.50
BACT
99.50
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 36
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUI1EER TX-0011
SOL'SCE TYPE CCDE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 727.00 MM
COMPANY NAME/SITE LOCATION IA SOUTHERN UTILITIES (CENTERVILLE, IA.) (NEAR) CHILLICOTHE, IA
OTTUMWA STATION WAFELLO COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/01/76
PERMIT NO. ESTIMATED DATE OF START-UP 1980
DETERMINATION MADE BY EPA REGION VII CHARLES WHITMORE (816J-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHOHE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILERi STEAM GEN, COAL FIRED
S02 1.2000 LB/MMBTU BACT
LOU S COAL
PM 0.1000 LB/MMBTU BACT
ESP
NOTES
THE PERMIT WAS AMMENDED ON 03/30/78 TO ADDRESS PARTICULATE MATTER.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 37 i ID NUMEER IA-0007 SOURCE TYPE CODE 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 165.00 HMBTU/H
_____.. _ _
COMPANY NAME/SITE LOCATION IDAHO NAT ENGINEERING LAB. IDAHO FALLS, ID
_ ... _ __ ____. _________ _____________ __ ______ »-___..____-___ -_«. -.»- __^__ -.-» _._ _ _ _ ______
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 06/05/81
PERMIT NO. (REGION FILE NO.) PSD-XS1-11 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY EPA REGION X DAVID TETTA <206)-442-1193
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8, BASIS
TO THIS PESMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILERS, 2 82.50 M EA
S02 99.2000 LB/H BACT
FLUIDIZIED BED
NOX 0.5000 LB/MM3TU BACT
COMBUSTION CONTROLS
PM 0.0500 GR/DSCF BACT
BAGHOUSE 99.00
FUGITIVE EMISSIONS
PM 0.0100 GR/ACF
BAGHOUSE 99.00
NOTES
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 0^/01/1933
PAGE G- 38 ID NUMBER 10-0002 SCARCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE-
EXTERNAL COMBUSTION - COAL
980.00 MM
COMPANY NAME/SITE LOCATION INDIANA STATEWIDE RURAL ELEC. COOP., ME*
, IN
SULLIVAN COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PEPMIT NO. EPA-5-77-A-7
DETERMINATION MADE BY EPA REGION V
(AGENCY)
BONIFACE THAYIL
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 06/28/77
ESTIMATED DATE OF START-UP
( PHONE )
PROCESSES SUBJECT
TO THIS PEPMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
BOILER, COAL FIRED, 2 EA
490.00 MM
PM
S02
0.1000 LB/MMBTU
1.2000 LB/ttMBTU
NSPS
NSPS
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 39
ID NUMBER IN-0022
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
SOURCE TYPE CODE 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
EXTERNAL COMBUSTION - COAL
2600.00
COMPANY NAME/SITE LOCATION INDIANA & MICHIGAN ELEC. CO., ROCKPORT *
ROCKPORT, IN
DETERHINATION IS BACT FOR A NEW SOURCE.
PEPMIT NO. EPA-5-78-A-1
DETERMINATION MADE BY EPA REGION V
(AGENCY)
BONIFACE THAYIL
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/27/77
ESTIM4TEO DATE OF START-UP--
(3121-686-6054
(FHOME)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
BOILER, COAL FIRED, 2 EA
1300.00 MW
PM
S02
0.1000 LB/MMBTU
1.2000 LB/MfiSTU
NSPS
N'SFS
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 40
ID NUMBER IN-0023
INITIAL REVIEU POST STARTUP
REVIEW STATUS-' 0^/01/1933
SOL'FCE TYPE CCDE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 1950.00 MW
__ ___ _ ______«.__ _ _ .._ _____ __ -. _ __ , . ... »
COMPANY NAME/SITE LOCATION INDIANAPOLIS POUER & LIGHT CO., PATRIOT* IN
SWITZERLAND COLfffTY
~
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/14/79
PERMIT NO. EPA-5-A-80-8 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION V BONIFACE THAYIL <312J-8S6-6054
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
.
BOILER, COAL FIRED, 3 EA 650.00 MW
PM 0.0300 LB/MMBTU
S02 0.5500 LB/re-STU
SCRUBBER 91.00
NOX 0.6000 LB/M!i3TU
NOTES
T..T-T-,, nryyctj POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. i-c.iL^ SIAi'US: 0-V01/19o3
PAGE G- 41 ^ - - .-...,-£. 7ir£ CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
EXTERNAL COMBUSTION - COAL
1640.00 KW
COMPANY NAME/SITE LOCATION INTERKQUNTAIN POHER PROJECT
LYKDLE, UT
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MADE BY UTAH BAQ
(AGENCY)
DAVID KAPTA
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/17/83
ESTIMATED DATE CF START-UP-- 1985
(801J-533-6103
(PHCNE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
BOILER, COAL FIRED, 3
8352.00 MMBTU
COAL HANDLING, UNLOADING, CRUSH* 5.00 MMT/YR
COAL, LIMESTONE, ASH HANDLING
5.00 MMT/YR
PM 0.0200 LB/MMBTU
FABRIC FILTER
S02 0.0150 LB/M!',3TU
LIMESTCS'E SCRUB
NOX 0.5500 LB/MtlBTU
COMBUSTION CONTROL
VE 20.0000 7. OPACITY
FABRIC FILTER
PM 0.0240 G3/DSCF
13 FABRIC FILTERS
VE 20.0000 7. OPACITY
13 FABRIC FILTERS
VE 20.0000 y. OPACITY
WET SUPPRESSION
BACT
99.80
BACT
90.00
BACT
BACT
BACT
99.00
BACT
SACT
50.00
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 42
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER UT-0009A
SCITCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 3000.00 MW
COMPANY NAME/SITE LOCATION INTERMOUNTAIN PWR PROJECT-IPP NEAR LYNNDYL, UT
MILLARD COUNTY
__ ___«.___ _______ _ _ «___»_____ -._-. __-.-. . » _ _._ _ ________ ____ __,-__.___ _
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 06/03/80
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VIII JOHN DALE (303NS37-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ASH UNLOAD
4 BOILERS
COAL CONV
COAL CRUSHING
3000.00 MM
10.00 MMT/YR
10.00 MMT/YR
PM
VE
CO
VOC
NOX
PM
S02
VE
PM
VE
PM
VE
64.0000
20.0000
1248.0000
375.0000
0.5500
0.0200
0.1500
20.0000
17.0000
20.0000
1.0000
20.0000
LB/H
HYDEOMIXER
7. OPACITY
LB/H
LB/H
LB/MMBTU
DESIGN
LB/M"3TU
ESP
LB/MMBTU
SCRUE3ER
/. OPACITY
LB/H
ENCLOSURE
7. OPACITY
LB/H
BAG-HOUSE
'/ OPACITY
BACT
99.00
BACT
BACT
BACT
65.00
BACT
99.80
EACT
90.00
BACT
90.00
BACT
99.60
PAGE G- 43
-------
(CONTINUED) INTERMCUNTAIN PUR FROJECT-IPP
PROCESSES SUBJECT
TO THIS PERMIT
COAL STORAGE
COAL UNLOAD
HAUL ROADS
LIME STORAGE
CONV/TRANSFER
THROUGHPUT POLLUTANT EMISSION LIMITS ...& BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
10.00 MMT/YR
PM
VE
10.00 MMT/YR
PM
VE
PM
PM
VE
10.00 MMT/YR
PM
VE
27.0000
20.0000
2.0000
20.0000
1.0000
0.1000
20.0000
4.0000
20.0000
LB/H
CRUSHING MGMT
X OPACITY
LB/H
WET SUPFRES.
X OPACITY
LB/H
CHEM. SUPFRES.
LB/H
BAGHOUSE
/. OPACITY
LB/H
BAGHOUSE
X OPACITY
BACT
90.00
BACT
98.50
BACT
85.00
BACT
99.60
BACT
9S.80
NOTES
THIS PROJECT IS UNDER CURRENT RE-REVIEW SINCE THE PROJECT HAS BEEN DOWN SIZED TO Z UNITS VERSES THE ORIG.4. STRONGLY RECOMMEND
THIS BE DELETED ANDWE WILL UPDATE THE ABOVE INFO AS SOON AS RE-EVALUATION IS COMPLETED (PROS. MAY 1983.
CEM QA REQUIRED BY 40CFR, PART 60, SUBPART DA.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 4
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 650.00 MW
__ __ _____.,,_..--. .. __«,_^__ _ »_ _. -. *. «- ^ ~
COMPANY NAME/SITE LOCATION IOWA ELECTRIC LIGHT * POWER CO. PANORA, IA
GUTHRIE COUNTY
_..,.._.__.___..__..__«___»_.«..__.___» ~r . _ ^ _«. _._. ___._ _ ____»_w _»__.»__»->__ __.__*._
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 10/29/82
PERMIT HO. ESTIMATED DATE Or START-UP--
DETERMINATION MADE BY EPA REGION VII STEVE KOVAC (8161-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
STEAM GENERATING COAL-FIRED BOI* 400.00 T/H COAL
MATERIAL HANDLING
S02 0.6000 LB/MMBTU DAILY MAX
WET LIMESTONE SCRUBBER
LOW S COAL
NOX 0.5000 LB/MUBTU 300 R AV
COMBUSTION DESIGN
PM 0.0300 LB/MN3TU
ELECT. FRECIP.
VE 20.0000 /. OPACITY
PM 0.0100 GR/DSCF
BAGHOUSES
VE 20.0000 /. OPACITY
BACT
BACT
BACT
BACT
BACT
NOTES
SOURCE IS SUBJECT TO NSPS, SUBPART DA
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 45
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER IA-0011
SO'JRCE TYPE CODE
1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1=34
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 600.00 MM
COMPANY NAME/SITE LOCATION IOWA-ILLINOIS GAS & ELECT. , IA
LOUISA STATION LOUISA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 06/16/81
PERMIT NO. ESTIMATED DATE OF START-UP-- 1983
DETERMINATION MADE BY EPA REGION VII CHARLES WHITMORE (816 )-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER 7000.00 MMBTU/H
NOX 0.6000 LB/MMBTU BACT
EOILER DESIGN
PM 0.0300 LB/MM3TU BACT
ESP
S02 0.8600 LB/ttfiSTU 24H AV BACT
1.0500 LB/rriBTU 3H AV
LOW S COAL
NOTES
PERMIT ORIGINALLY ISSUED 07/07/79.
53600.0 LB/DAY TOTAL ALLOWED
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 46 ID NUMBER IA-0002 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 600.00 MM
COMPANY NAME/SITE LOCATION JACKSONVILLE ELECT. AUTHORITY JACKSONVILLE, FL 32208
HORTHSIDE DUVAL COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 01/01/82
PERMIT NO. (REGION FILE NO.) PSD-FL-010 ESTIMATED DATE OF START-UP 1986
DETERMINATION MADE BY FLORIDA DcR BOB KING (9C4 )-<+S8-1344
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
STEAM GEN. UNIT 600.00 M4 EA
S02 0.7600 LB/MMBTU BACT
LIME/LIMESTONE FGD 90.00
PM 0.0300 LB/HM3TU NSFS
ESP 99.73
NOX 0.6000 LB/MMBTU NSPS
BOILER DESIGN
NOTES
TWO UNITS AT 600.0 MW EACH.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 47
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER FL-0006
SO'JRCE TYPE CODE
1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 630.00 MW
COMPANY NAME/SITE LOCATION KANSAS CITY POWER & LIGHT IATAN, HO
IATAN STATION PLATTE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 01/07/77
PEFMIT NO. ESTIMATED DATE OF START-UP-- 1981
DETERMINATION MADE BY EPA REGION VII DANIEL RODRIGUEZ (816 )-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, COAL FIRED, PULV. 630.00 MW
PM 0.1000 LB/MKBTU BACT
ESP 99.40
SOZ 1.2000 LB/MM3TU BACT
LC'A S WESTERN COAL
NOX 0.7000 LB/MMBTU NSPS
BOILER DESIGN
NOTES
THE UNIT IS SUBJECT TO NSPS, SBPART D. THE PSD REGS. ADDRESSED ONLY PM AND S02.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1953
PAGE G- 48 ID NUMBER MO-0004 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 2880.00 MM (TOTAL, 4 UNIT C*
COMPANY NAME/SITE LOCATION KANSAS POWER & LIGHT CO. ST. MARY'S, KS
JEFFREY ENERGY CENTER POTTAWATOMIE COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/30/78
PERMIT NO. ESTIMATED DATE OF START-UP-- 1964
DETERMINATION MADE BY EPA REGION VII DANIEL RODRIGUEZ (8161-374-6525
(AGEN'CY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ _ -___ ______»_.»___».__.» _________ _ _____________ ___ «.__. __«._««.. ._ ____.._...__..__-__ ___»»____«» -,«, « .-. ._.. __ _ _
COAL FIRED BOILERS, UNITS 3 AST)* 720.00 MW EA
S02 1.2000 LB/MMBTU BACT
WET LIMESTONE SPRAY TOWERS 60.00
PM 0.1000 LB/MMBTU BACT
2 COLD SIDE ESP'S PER UNIT 99.20
NOX 0.7000 LB/MMBTU NSPS
BOILER DESIGN
NOTES
THE UNITS ARE SUBJECT TO NSPS, SUBPART D. BACT EMISSION LIMITS FOR NOX AND CO WERE NOT SET BECAUSE THE REGS. ADDRESSED ONLY PM
AND S02. PLANT NAME: JEFFREY ENERGY CENTER.
UNITS 1 AND 2 WERE NOT SUBJECT TO PSD REVIEW. UNIT 3 STARTUP 1982. UNIT 4 STARTUP 1984.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 49
INITIAL REVIEW POST STARTUP
REVIEW STATUS'- 04/01/1S33
ID NUMBER KS-0010
SOURCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 1300.00 MW
____._.___._._.______.-.____.____-___. __.-.._ _._. . -- -" -- --
COMPANY NAME/SITE LOCATION KENTUCKY POWER - CARR'S FAC. ASHAD, KY
LEWIS COUNTY POWER PLANT LEWIS COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 04/18/80
PERMIT NO. C-80-42 ESTIMATED DATE OF START-UP 1939
DETERMINATION MADE BY KENTUCKY DAPC BILL DILLS (502 >-56<»-3332
(AGENCY) (AGENCY CONTACT PERSON) (P.'iOME)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. fi BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ __v _ ___ ___ _._«. _.«<»_ _ .».._ .». . _ ___..__« .._ _...»«_.««__,«___»___«..«« .- -» .- _ ___» *_ «, ^«-
POWER BOILER 11943.00 MMBTU/H EA
S02 0.6000 LB/MM3TU BACT
FGD 95.00
PM 0.0300 LB/MMBTU BACT
ESP 99.81
NOX 0.6000 LB/KMBTU BACT
BOILER DESIGN & OPERATION
NOTES
TWO UNIT COAL BURNING POWER PLANT
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. r^vlf',' STAn'S: ?-'./01.'l
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1954
SOURCE TYPE/SIZE-
EXTERNAL COMBUSTION - COAL
1300.00 MW
COMPANY NAME/SITE LOCATION KENTUCKY UTILITIES - HANCOCK POWER PLANT
LEXINGTON, KY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. C-82-123
DETERMINATION MADE BY KENTUCKY DAPC
(AGENCY)
BILL DILLS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 04/15/82
ESTIMATED DATE OF START-UP 1990
(502 J-564-33S2
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
UNIT SI
6650.00 MMBTU/H
UNIT S2
6650.00 MMBTU/H
PM 0.0300 LB/MMBTU
874.0000 T/YR
ESP
CO 1397.0000 T/YR
S02 1.2000 LB/MMBTU
15768.0000 T/YR
WET SCRUBBER
NOX 0.6000 LB/Mk18TU
17476.0000 T/YR
PM 0.0300 LB/MMBTU
874.0000 T/YR
ESP
CO 1397.0000 T/YR
S02 1.2000 LB/MMBTU
15763.0000 T/YR
KET SCRUBBER
NOX 0.6000 LB/K,'iBTU
17476.0000 T/YR
99.80
91.50
99.80
91.80
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 51
INITIAL REVIEW POST STAPTUP
REVIEW STATUS: 04/01/1933
ID NUC2ER KY-OC27
SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING 05/22/1934
--------------=-===--======-----=-~=-=--~--===~==~~=
SOURCE TYPE/SIZE EXTERNAL COMBUSTION^COAL
COMPANY NAME/SITE LOCATION LOUISVILLE GAS * ELECT. - TRIMBLE CNTY * ""ES LANDING, KY ^^ ^^
DATE OF PERMIT ISSUANCE-- 12/27/78
DETERMINATION IS ESTIMATED DATE OF START-UP 1936
PERMIT HO. C-78-34 nil I 5 <502J-564-3332
DETERMINATION MADE BY (AGScY CONTACT PERSON) (PHONE.
PROCESSES SUBJECT rTT i ONfSISoUIPMENT OR PROCESS MODIFICATION '.'.'.
TO THIS PERMIT CAPACITY _.___..
IS-OIRECT HEAT EXCHANGER ^51.00 MMBTU/H ^ ^^^ ^^^
1275.0000 T/YR
ESP
S02 1.2000 LB/HMBTU
10790.0000 T/YR
KET SCRUBBER
NOX 0.7000 LB/MM3TU
892^.0000 T/YR
NOTES
UNIT NUMBER 1
(*) INDICATES DATUT1 UAS TRUNCATED FOR THIS
PAGE G- 52
ID NUMBER KY-0025
INITIAL jTtVIEU POST STARTUP
REVIEW STATUS; 0^/01/1^33
SCL'ICE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1964
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL
COMPANY NAME/SITE LOCATION LOUISVILLE GAS & ELECT. - WISE'S LANDIN* , KY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/01/79
PERMIT NO. C-79-53 ESTIMATED DATE OF START-UP 1938
DETERMINATION MADE BY KENTUCKY DAPC BILL DILLS (502 )-564-3382
(AGENCY) (AGENCY CONTACT PERSON) (PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
INDIRECT HEAT EXCHANGER 4851.00 MMBTU/H
PM 0.1000 LB/MMBTU
1275.0000 T/YR
ESP 99.60
S02 1.2000 LB/MM3TU
10790.0000 T/YR
WET SCRUBBER 90.00
NOX 0.7000 LB/MMBTU
8924.0000 T/YR
NOTES
UNIT NUMBER 2.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: OV01/19S3
PAGE G- 53 ID NUMBER KY-00£<* SOURCE TYPE CODE 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/193"+
SOURCE TYPE/SIZE
EXTERNAL COMBUSTION - COAL
4735.00 HMBTU/H
COMPANY NAME/SITE LOCATION LOWER COLORADO RIVER AUTHORITY
, TX
FAYETTE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PEPMIT NO. 9231-34
DETERMINATION HADE BY TEXAS ACB
(AGENCY)
JIM CROCKER
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 12/22/83
ESTIMATED DATE OF START-UP--
(512)-451-5711
(FHCNE)
PROCESSES SUBJECT
TO THIS PERMIT
BOILER, LIGNITE FIRED
COAL HANDLING, CONVEYING SYS.
COAL HANDLING, STORAGE
ASH HANDLING
THROUGHPUT POLLUTANT
CAPACITY EMITTED
4735.00 MMBTU/H
H2S*
PM
HG
VGC
NOX
S02
CO
1200.00 T/H
FM
1800.00 T/H
PM
300.00 T/H
PM
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
954.7000 T/YR
622.0000 T/YR
ESP
0.1300 T/YR
163.2000 T/YR
12350.2000 T/YR
BURNER DESIGN
20736.9000 T/YR
LIMESTONE SCRUBBER
2627.7000 T/YR
53.8000 T/YR
COVERS * UETTING AGENTS
32.9000 T/YR
BAGHOUSE
WET SFRAY
4.7000 T/YR
BAGHOUSE
... 4 BASIS
... PCT EFF
BACT
B/N
99.96
B.4CT
BACT
B/N
B/N
90.00
BACT
BACT
BACT
99.00
BACT
99.00
KET UNLD MIXERS
PAGE G- 54
-------
(CONTINUED) LOWER COLORADO RIVER AUTHORITY
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS - - * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT CR PROCESS MODIFICATION ... PCT EFF
LIMESTONE HANDLING 300.00 T/H
PM 0.7000 T/YR BACT
ENCLOSURE
NOTES
ALT. EMISSION LIMITS ON BOILER ARE 0.6 LB/MMBTU NOX, 0.03 LB/MMBTU PM, 1.0 LB/MMBTU SOZ.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 05/04/1934
PAGE G- 55 ID NUMBER TX-0136 SOURCE TYPE CCCE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 517.60 MtlSTU/H
COMPANY NAME/SITE LOCATION MARQUETTE BOARD OF LT * PUR MARQUETTE, MI 49855
SHIRAS GENERATING STA. MARQUETTE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 04/01/80
PERMIT NO. 65-80 ESTIMATED DATE OF START-UP 1932
DETERMINATION MADE BY MICHIGAN DMR DAVID FERRIER (517)-3£2-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
~ ZZZ ~ ~ ~~~~~~~~'''''~~~~~~~~"~"~""*~~~" .- - ~~
PROCESSES SUBJECT THROUSHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PEPMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
_ ___________ _ »^ . .
BOILER, COAL-FIRED 517.60 MMBTU/H
PM 0.0300 LB/MMBTU
BAGHOUSE 99.90
S02 0.4000 LB/Mt-'BTU
SPRAY LIME FGD UNIT 70.00
LOU SULFUR WESTERN COAL
NOX 0.5000 LB/Mr3TU
LONG. FIRING + EXCESS AIR CON.
COAL & ASH HANDLING & STORAGE
PM 0.0300 GR/DSCF
BAG FILTER CONTROL 99.90
ENCLOSURES, CUST SUPPRESSANTS
NOTES
INITIAL REVIEU POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933 °3/13/193*_
PAGE'G-""^ ID NUMBER Mi-ooi4 SC-JRCE TYPE CCOE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 500000.00 LB/H
COMPANY NAME/SITE LOCATION MICHIGAN SOUTH CENTRAL POWER AGENCY LITCHFIELD, MI
HILLSDALE COUNTY
__________....___._ .. _ -. . - ..... - . -» » ~ " "~
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 05/16/30
PERMIT HO. 607-78 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY MICHIGAN DNR GREGORY EDWARDS (517)-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
.
COAL-FIRED BOILER 500000.00 LB/H
PM 0.0300 LB/MMBTU
ESP 99.70
S02 NSPS
LIMESTONE SPRAY SCRUB 90.00
NOX 0.6000 LB/MMBTU
CONTRL EXCESS & OVERFIRE AIR
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM W4S TRUNCATED FOR THIS TABLE. REVIE^.ST^!:__?^^^!"__..°-.^^!---
-~~57" ID NUMBER MI-0001 SOURCE TYPE CCDE 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING 05/22/1984
_ r-r = -~-- = - = = ~-~~~-- = --* = - = = ----- = ~ = ~ = = -~- = = ~~~---- = = ~~ = ~~~~ = ~~ = ~ = ~~ = ~~~'~=:~~
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL !!°l°!_'j"
COMPANY NAME/SITE LOCATION MINN. POWER & LIGHT CO., CLAY-BOSWELL C°"^S^!l_"!!
DETERMINATION IS BACT FOR A NEW SOURCE.
.DE BY EPA REGION V
(AGENCY)
;T
BOILER, COAL FIRED 500.00 MM LB/MMBTU NSPS
S02 1.2000 LB/MM3TU NSPS
NOTES
INITIAL REVIEW POST STARTUP
(«) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. ^ _--=! = ==I = I= = = = = = = = = = = = = = = = = === = === = = = = = =
^^^ = = ^^^ = ^ = = ^ = = ^ = ^^^^ = ^ = ^^^^^^ SSUrXE TYPE CCDE 1'1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 98.30 MMBTU/H
COMPANY NAME/SITE LOCATION MORGANTOHN ENERGY RESEARCH CENTER MCRGANTOWN, WV
MORGANTOWN ENER3Y RESEARCH CE* MONCNGALIA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/20/79
PERMIT NO. 78WV08 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION III EILEEN GLEN (215 )-597-8187
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
FLUIDIZED BED BOILER
COAL/LIMESTONE DRYER
COAL/LIMESTONE DRYER
COAL/LIMESTONE DRYER
COAL/LIMESTONE UNLOAD
COAL/LIMESTONE CONVEYORS
98.30 MMBTU/H
52.00 CF/H
13230.00 T COAL
66CO.OO T LIMESTONE
20000.00 T COAL LIME*
20000.00 T COAL LIME*
PM 5.4000 LB/H
CENTRIF. COLL. i, FABRIC FILTER
S02 86.0000 LB/H
NOX 34.0000 LB/H
FABRIC FILTER
FABRIC FILTER
FABRIC FILTER
BACT
99.00
BACT
BACT
99.00
99.90
99.90
NOTES
PROJECT CANCELLED
(*) INDICATES D4TUM HAS TRUNCATED FCR THIS TA2LE.
PAGE G- 59
TTTAL REVIEW POST STARTUP
04/01/1933
ID NUriSER WV-0006
SC'JKCE TYPE CODE
1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL
COMPANY NAME/SITE LOCATION MUSCATINE POWER & WATER
MUSCATINE , IA
MUSCATINE COUNTY
DETERMINATION IS B/L FOR A MODIFIED SOURCE.
PEPMIT NO.
DETERMINATION MADE BY EPA REGION VII
(AGENCY)
DANIEL RODRIGUEZ
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 01/24/80
ESTIMATED DATE OF START-UP--
(816)-374-6525
(PHONE)
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
BOILER, UNIT »9, COAL/OIL/GAS 166.00 MW
COAL HANDLING
ASH HANDLING
POLLUTANT EMISSION LIMITS ... & BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
PM 0
S02 0
0
NOX 0
PM 0
PM 0
.0300
.4500
.5600
.6000
.0100
.0200
LB/MM3TU
COLDSIDE ESP
LB/MM3TU 30D R AV
LB/MMSTU MAX D AV
WET-LIHESTCNE SCRUBBER
LB/MMBTU
BOILER DESIGN
GR/SCF
BAGHOUSE
GR/SCF
BAGHOUSE
LAER
99.70
LAER
92.00
BACT
LAER
99.99
LAER
99.93
LAFRSS"ESTABLI^ED BY THE IOWA DEPT. OF ENVIRONMENTAL QUALITY, CONTACT - AFTER ?/i/83, THE IOHA OEPT. OF WATER, AIR, & WASTE M
ANAGEMENT, 515-2S1-8924. UNIT 9 WILL BURN SOUTHERN ILL. COAL. S02 & FM OFFSETS WILL BE CSTAINED.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
PAGE G- 60
ID NUMBER IA-0001
SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING 05/22/198*
___-._-.__,___. ~~~~~~ ~ ~ ~~~~~ ~"
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL ^ _ t!!l°*.!^
COMPANY NAME/SITE LOCATION KE PUBLIC POWER DIST./GENTLEMAN *2 SUTHERLAND, NE LINCOLN COUNTY
GERALD GENTLEMAN STATION (UNI* _ _
DATE OF PERMIT ISSUANCE-- 02/09/77
DETERMINATION IS BACT FOR A NEW SOURCE. ESTIMATED DATE OF START-UP
sr HPA^OH , ISSL^S^LoH, "".'SSS"*
---- = rr = = = r = = = = = = = = = = = = = = = = = ::: = = = - = := = ~ = :::~=:: = ==~ = = = = = = = = :: = = ~ = ===~~~~"'
__
BOILER, STEAM GEN, COAL FIRED 650.00 MW ^ ^^^ LB/MnBTU BACT
LOW S COAL
PM 0.1000 LB/r^iBTU BACT
ESP
NOTES
INITIAL REVIEW POST STARTUP
I.) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. ?!.!I:.-^~""«« = « = «««=
" SOU7CE TYPECCDE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 650.00 MM
COMPANY NAME/SITE LOCATION NEBRASKA PUBLIC POUER DIST. > NE
COMSTOCK STATION
DETERMINATION IS BACT DATE CF PERMIT ISSUANCE 12/16/80
PERMIT NO. ESTIMATED DATE CF STAPT-UP--
DETERMINATION HADE BY NEBRASKA DEC GENE ROBINSON (402J-471-21S6
(AGENCY) (AGENCY CONTACT PERSON) ( FHCS'E )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... i BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
BOILER 650.00 MW
PM 0.0300 LB/MM8TU
FABRIC FILTER 99.90
S02 70.0000 '/. REMOVAL
0.3600 LB/F.N3TU 30D AV
DRY SCRUBBER 70.00
HOX 0.5000 LB/MMBTU 3CD AV
CO 50.0000 PPM
COAL HANDLING
PM 20.0000 7. OPACITY
FABRIC FILTER 99.90
NOTES
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. _ _ !?^'IEW STATUS: C^°*lt:!'!
PAGE~6-~~62 ID NUMBER NE-0002 SO'JICE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 560.00 KW EA
_____ ____ __ ______«. _______ _ ____ __ ^ ___ .. i ^ «..-, »__ _ «,- »^ -. . « «lB~ ~» »- W.
COMPANY NAME/SITE LOCATION NEVADA POWER CO. > NV
25 MILES NE OF LAS VEGAS
___. __ _ -,. ,. .» . .- __. .. »» ^^.» i _ -, ______ _ _
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 04/13/81
PE9MIT NO. NV-77-01 ESTIMATED DATE OF START-UP 1990
DETERMINATION MADE BY EPA REGION IX LARRY BOWERMAN (415)-974-8213
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILERS, 4 EA
560.00 MW
CO
NOX
S02
PM
VOC
PB
BE
HG
320.0000 LB/H
50.0000 PPM AT 20X EXCESS AIR
PROPER BOILER DESIGN
EXCESS AIR HONITORINS
2498.0000 LB/H
0.4400 LB/MK3TU
PROPER BOILER DESIGN W/ COMBUSTION AND LOW NOX*
566.0000 LB/H
0.1000 LB/KMBTU
ONE (1) WET LIME SCRUBBER
TWO (2) STANDBY MODULES TO IMPROVE SYSTEM RELI*
0.0150 LB/KM3TU
10.0000 y. OPACITY
BAGHOUSE, UNLESS ESP DESIGN APPROVED
PROPER BOILER DESIGN
COMBUSTION MONITORS
NONE
SAME AS LEAD
NONE
BACT
BACT
BACT
95.00
BACT
99.76
BACT
PAGE G- 63
-------
FM AND SOS CONTROLS EQUIPMENT
MONITOR HG CONTENT IN COAL
F 9.0000 LB/H
SAME AS MERCURY
H2S* 13.0000 LB/H
SAME AS MERCURY W/0 COAL MONITORING
PAGE G-
-------
(CONTINUED) NEVADA POWER CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
$ BASIS
PCT EFF
COAL FIRED BOILERS, 4
ACTIVE COAL STORAGE SILOS
COAL DEWATERING PLANT
31250.00 T/D
INACTIVE COAL STORAGE PILE
LIME CONVEYING, TRANSFER, STORA*
PM
PM
CO
NOX
SOS
BE
HG
F
H2S*
11.4000 T/YR
VENTURIES TO WET SCRUBBER OR BAGHOUSE
ENCLOSURE AND UETTINS TRANSFER POINTS
TRACE
BAGHOUSE ON SILO VENTS
99.00
95.00
26.0000 LB/H
50.0000 PPM
SAME AS FOR BOILERS
304.0000 LB/H
0.4400 LB/MKSTU
SAME AS FOR BOILERS
46.0000 LB/H
0.1100 LB/MMBTU
SAME AS FOR BOILERS
NONE
SAME AS FOR BOILERS
NONE
SAME AS FOR BOILERS
1.0000 LB/H
e.oooo LB/H
SAME AS FOR BOILERS
1.0000 LB/H
2.0000 LB/H
SAME AS FOR BOILERS
COMPACTION & CHEMICAL STABILIZATION W/BINDING * 90.00
BAGHOUSES ON LIME SILO AND SLAKER VENTS.
PNEUMATIC UHLOADIN3, ENCLOSED CONVEYORS
PAGE G- 65
-------
(CONTINUED) NEVADA POWER CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... 4 BASIS
EMITTED CONTROL EQUIPMENT OS PROCESS MODIFICATION ... PCT EFF
ASH HANDLING,STOR. £ DISPOSAL
PLANT ACCESS t HAUL ROADS
FUEL OIL STORAGE
3.10 MMGAL
FUG*
VOC
SILO VENTED TO BAGHCUSE.
FLY ASH PNEUMATICALLY CONVEYED TO SILO.
MOST ROADS PAVED AND 20 MPH SPEED LIMIT
FIXED OR FLOATING ROOT
NOTES
(250) LB/HR LIMITS APPLY TO ANY CONSECUTIVE E4-HOUR PERIOD, ALL OTHER ARE FORCONSECUTIVE 30-DAY PERIOD AS DETERMINED BY CONTIN
UCUS MONITORING SYS. OPACIT Y LIMIT (6 MINUTE AVERAGE) CANNOT BE EXCEEDED
EXCEPT FOR ONE 6-MINUTE PERIOD PER HOUR OF NOT KCRE THAN 15X OPACITY AS DETERMINED BY METHOD 9 09 THE OPACITY MONITORING SYS.
BACT FOR PM REPRESENTS BACT FOR LEAD. TRACE EQUALS LESS THAN 0.1 T/YR.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 66
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1963
ID NUMBER NV-0001
SOURCE TYPE CODE
1.1
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 1080.00 MW
COMPANY NAME/SITE LOCATION HEW ENGLAND POWER CO., BRAYTON POINT ST* SOMERSET, MA
DETERMINATION IS RACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 11/01/80
PERMIT NO. APFR. LTR 10-01-80 ESTIMATED DATE OF START-UP 1930
DETERMINATION MADE BY MASSACHUSETTS DEQE - AIR VAUGHAN STEEVES t617)-727-1440
(AGENCY) (AGENCY CONTACT PERSON) (PHOh)E)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...& BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- ~ "* ~ _ __________________ ...... _ _..__.,._ .. ___-.___.. -. __ __ _ «.__..______.._.. _________ __________________
COAL COMBUSTION 10625.00 MM3TU/H
S 1.2100 LB/MMBTU MONTHLY AV RACT
2.3100 LB/MMBTU DAILY AV
PM 0.0600 LB/MMBTU RACT
ESP 99.30
NOX
NOTES -
PM TESTED AT 0.03* LB/MMBTU, 0.016 LB/MMBTU, & 0.010 LB/MMBTU FOR UNITS 1-3, RESPECTIVELY. THREE UNITS COMBINED - 250 MW, 25
0 MW, 4 580 MW. VOLUNTARY COAL CONVERSION.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 67 ID NUMBER MA-0006 SOURCE TYPE CODE 1:1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
EXTERNAL COMBUSTION - COAL
7934.00 MMBTU/H
COMPANY NAME/SITE LOCATION NORTHERN INDIANA PUBLIC SERVICE CO.
WHEATFIELD, IN
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. EPA-5-A-80-18
DETERMINATION MADE BY EPA REGION V
(AGEKCY)
BONIFACE THAYIL
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 03/31/80
ESTIMATED DATE OF START-UP
(312)-8S6-6054
(FHCNE)
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
BOILERS, COAL-FIRED, 2 EA 3967.00 MMBTU/H
FUGITIVE EMISSIONS, CRUSHER HOU*
POLLUTANT
EMITTED
PM
S02
NOX
PM
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.0300 LB/MMBTU
ESP
0.6200 LB/HMBTU
SCRUBBER
0.6000 LB/MMSTU
... 4 BASIS
... PCT EFF
99.73
90.00
FUGITIVE EMISSIONS, CONVEYORS
FUGITIVE EMISSIONS, FLYASH 8 HA*
PM
PM
BAGHOUSE
ENCLOSED COAL CONVEYORS
BAGHOUSE
WETTED COAL
NOTES
TWO BOILERS UNDER PERMIT. TRUCKS UTILIZIED FOR ASH DISPOSAL SHALL BE COVERED.
99.00
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 68
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 0'V01/19S3
ID NUMBER IN-0003
SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOUPCE TYPE/SIZE---
EXTERNAL COMBUSTION - COAL
1600.00 MM
COMPANY NAME/SITE LOCATION NORTHERN STATE POWER CO., SHERBURNE STA
BECKER, MN
SHERBURNE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. EPA-5-77-A-2
DETERMINATION MADE BY EPA REGION V
(AGENCY)
BONIFACE THAYIL
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 04/25/77
ESTIMATED DATE OF START-UP--
(312)-8a&-6C54
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
t BASIS
PCT EFF
BOILER, COAL FIRED, 2 EA
800.00 MM
PM
S02
0.1000 LB/MMBTU
1.2000 LB/MM3TU
NSPS
NSPS
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 69
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER MN-0007
SOURCE TYPE CODE
1.1
-------
*d* n
CO II
O- 1
r-l n
X n
c\j n
CJ II
X II
to n
O II
u
n
n
n
n
n
n
n
M
n
i
i
i
i
i
i
i
i
u
u
n
M
n
u
n
u
n
n
n
u
n
i
n
u
n
u
i
n
i
CD II
M II
h- 1
01 1
M 1
_J 1
1
UJ 1
O 1
g !
O I
V) 1
I
O 1
UJ 1
-J 1
M 1
< II
t- M
UJ II
o n
11
1 II
t II
II
X, H
e n
LU II
Q. II
Q. II
< II
1
II
II
H
II
II
II
It
II
II
U
II
}
II
1
H
11
II
II
I
II
II
II
II
II
II
II
II
II
1
I
I
1
t
1
1
1
1
1
I
1
1
_J
«t
O
u
1
"Z.
0
h-
s
o
u
<(
z
CK
UJ
)»
^
UJ
1
1
1
UJ
N
M
CO
X
UJ
CL
^.
r-
UJ
U
g
O
01
^.
L-,
[^
O
u
UJ
u
UJ
1
_J
§
V.
£
M
O
CL
^
h-
3
o
01
r-
u
UJ
1
o
CK
Q.
O
E
UJ
a
UJ
§
h-t
i;
a."
UJ
H~
3
.j
CK n
Z < n
D 01 M
Ol II
01 U- II
MO II
II
r- UJ 11 n
M r- U~i II
E < iH II
CK CJ Ul ~ II
UJ 1 UJ II
0. C r-1 7. n
uj in o n
U. |~ Kl X II
O < 1 CL II
r. n
UJ M - II
< O II
CK z n
U- UJ II
ID II
< 11
» 11
II
II
II
II
II
II
II
II
II
II
II
II
M
II
II
II
II
II
1. II
3 >- n
O (J II
z: z u
01 UJ II
r- to H
a < n
O II
CL II
n
n
u
n
u
u
n
V II
03 II
II
UJ II
r^ D n
01 0 < II
M r-l H II
1 II
z r> z n
O 0 O II
i- i- ii
< O < II
z z z n
MM II
r i- i: n
CK M u; II
UJ n UJ II
1- CK H- II
UJ UJ UJ II
CD CL 0 II
01 U.
M U.
01 UJ
03 h-
U
a CL
, ,
« .
« ,
Z
o
M
<{
(J
U.
M
Q
O
sr
01
01
UJ
o
o
a
CK
o
t-
z
UJ
a.
M
^3
cr
UJ
01
M O
l-l k-
-1 7.
O
Z U
M
Ol
01
M
JZ
UJ
So
< UJ
> *
3 !-
_J M
i y
O UJ
P.
^
a. h-
X M
13 (J
Z) <
O 0.
CK <
pZ
V-
o
UJ
-> t-
CO M
3 n
01 CK
UJ
01 CL
UJ
01 01
01 M
UJ I
O h-
O
a o
U. (-
c- o o
oiO'Oi 010-01 uic>oi
CL a. a. a. n. a.
Z^Z ZCr^Z 2C^Z
_J
<^
O
(J
01
01
UJ
u
o
CK
u.
0
1-
01
o
i:
z
M
O
1-
UJ
01
y.
z
^
t- CK
UJ
CK CK or - u.
uJ uj uj 01 01
h- t- I- uj z
_1 -1 _J CL <
M>- M>- M>- MCK
U.H- U.K U.H Q.H-
UOU OOU UOO >-U.
O CK CL D CK O- D D" D-
XGJO X(DO XCJO OX
CK CL > CL > CKO
U. CL
0 CK
-J O BJ
-j CK i:
< u- D
*jr
CK CK
UJ tH >-
M < M
3 3 3 CK CK a:
1 t 1 uj uj uj
CO CQ tij ^» U- ^
y y~ y i (/j
XI 2Z 3Z 3 2^ O
O. < 01
000 CK -J
CO CO CO O 1- <
. t-
W CJ (VI UJ
a 1- a
Ul OJ -J
M -J
UJ M
U CK DC
UJ UJ
CK K Ul
< Ul
-J 3 3
< O
0 I Zi
OHO
M '!
IX 3 CO
O
u. a j;
UJ O
t- X C£
01 CL M u.
r-l Cg K* UJ UJ E
O O O h- LJ CK
O O O O X Ol M
Q. CL CL Z UJ M <
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 635.00 MW
COMPANY NAME/SITE LOCATION NY STATE ELECT, t GAS - CYUGA STATION SOMERSET, NY
NIAGARA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 06/29/81
PERMIT NO. ESTIMATED DATE OF START-UP 1936
DETERMINATION MADE BY EPA REGION II BARRY TORNICK (212)-264-9579
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
MAIN BOILER
1750.00 MMBTU/H
AUXILIARY BOILERS, 2
195.00 MMBTU/H
PM
S02
NOX
CO
F
PB
HG
BE
S02
NOX
0.0300 LB/MMBTU
ESP
0.7000 LB/MMBTU
0.6000 LB/MM3TU
FGD & 5<3.6X BY WT.
0.6000 LB/MKBTU
GOOD DESIGN ft COMBST PRACT.
GOOD COMBST PRACT.
FGD SYSTEM
ESP/FGD
ESP/FGD
ESP/FGD
USE OF #2 FUEL OIL
BACT
BACT
90.00
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 71
-------
USE OF 82 FUEL OIL
PAGE 6- 7Z
-------
(CONTINUED) NY STATE ELECT. * GAS - CYUGA STATION
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
... t BASIS
. .. PCT EFF
COAL HANDLING
LIMESTONE HANDLING
FLY ASH HANDLING
200000.00 T/YR
PM
Ptl
PM
FABRIC FILTER
H20 SPRAY « ENCLOSED SYS.
FABRIC FILTER
H20 SPRAY & ENCLOSED SYS.
FABRIC FILTER
BACT
BACT
BACT
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 73
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER NY-0003
SOfSCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 550.00 MW
, .
COMPANY NAME/SITE LOCATION OKLAHOMA GAS & ELECT. CO. BEDROCK, OK
NOBLE COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 10/05/81
PERMIT NO. (REGION FILE NO.) PSD-CK-218 ESTIMATED DATE OF START-UP 1986
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214J-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GEN. UNITS, COAL-FIRED, Z EA
5250.00 MMBTU/H
TUNNELS, COAL RECLAM., 2 EA
COAL CRUSHER TOWER
BIN TOWERS, COAL SURGE, Z EA
S02 0.4600 LB/MMBTU
FLUE GAS DESULFURIZATION
NOX 0.5000 LB/Mf!BTU
EXCESS AIR
CO 0.0640 LB/KM3TU
COM. CONTROLS & PROPER OPER.
PM 0.0300 LB/MM3TU
ESP OR BAGHOUSE
PM 2.8000 LB/H
DUST COLLECTOR
PM 3.4000 LB/H
DUST COLLECTOR
PM 3.9000 LB/H
DUST COLLECTOR
NSPS
70.00
NSPS
BACT
NSPS
99.60
BACT
93.00
BACT
98.00
BACT
98.00
PAGE G- 74
-------
(CONTINUED) OKLAHOMA GAS & ELECT. CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
,.. * BASIS
, .. PCT EFF
COAL SILOS, 2 EA
COAL STORAGE PILES
80.00 LB/ACRE-H
PM
PM
3.7000 LB/H
DUST COLLECTOR
5.8000 LB/ACRE
CHEMICAL 4 WATER STABILIZERS
BACT
98.00
BACT
NOTES
OKLAHOMA GAS » ELECTRIC COMPANY, UNIT *3.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 75
INITIAL REVIEW POST STARTUP
REVIEW STATUS-1 0'»/01/1983
ID NUMBER GK-OC03
SOU3CE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 550.00 MW
COMPANY NAME/SITE LOCATION OKLAHOMA GAS & ELECT. CO. MUSKOGEE, OK
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/30/78
PERMIT NO. PSO-OK-57 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (314)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROU3HPUT POLLUTANT EMISSION LIMITS . . . * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
______«._ __».___»_____ ____ ____._____ ~ ___ . ^ " « ^
COAL FIRED BOILER 550.00 MW
S02 1.2000 LB/MMBTU
6180.0000 LB/H
LOU S WESTERN COAL
PM 0.1000 LB/MHBTU
212.0000 LB/H
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 76 ID NUMBER OK-0002 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 500.00 MW
COMPANY NAME/SITE LOCATION PACIFIC POWER * LIGHT POINT OF ROCKS, WY
DETERHINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/01/75
PERMIT NO. CT-23 ESTIMATED DATE OF START-UP 1979
DETERMINATION MADE BY WYOMING AQD LEE SRIBOVICZ (307 )-332-314
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 37.00 MW
COMPANY NAME/SITE LOCATION PANORAMA ENERCORP, INC KETTLE FALLS, WA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 09/22/81
PERMIT NO. (REGION FILE NO.) PSD-X81-15 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION X PAUL BOYS (206 )-4<+2-1193
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER 37.00 MW
PM 0.0070 GR/DSCF 127. C02
ESP 99.00
CO 107.3000 LB/H BACT
VOC 36.5000 LB/H
NOX 0.1700 LB/ttMBTU BACT
NOTES
GENERAL DESIGN CONTRIBUTES TO REDUCTION OF ALL POLLUTANTS AND INCLUDES 1) INCREASED BOILER HEIGHT FOR BETTER EFFICIENCY, 2) 0V
ERFIRE /NO U>;DERFIRE AIR, 3) FEEDWATER HEATERS TO INCREASE EFFICIENCY.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 78
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NUMBER WA-0001
SO'JRCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 625.00 MW ONE
________ _ ________»_______ _ _________________»__ W_«__ »_ « . * - - !^
COMPANY NAME/SITE LOCATION PENNSYLVANIA ELECT. CO. LAKE CITY, PA
COHO-1 ERIE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/18/81
PERMIT HO. 78PA13 ESTIMATED DATE OF START-UP 1989
DETERMINATION MADE BY EPA REGION III DAVID ARNOLD (215)-597-7936
(AGENCY) (AGENCY CONTACT PERSON) ( PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
UTILITY BOILER, COAL FIRED 6280.00 MMBTU/H
PM 0.0300 LB/MMBTU NSPS
ESP 99.70
S02 0.6260 LB/MMBTU BACT
LIME SCRUBBING-??* 99.00
NOX 0.6000 LB/MMBTU NSFS
CO 0.0400 LB/MMBTU NSFS
COAL AND ASH HANDLING
PM BACT
WET SUPPRESSION AND DUST COLLECTORS
NOTES
UP TO 40X SULFUR TO BE REMOVED BY COAL CLEANING PRIOR TO REACHING BOILER.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 79 ID NUMBER PA-0004 SCL"5CE TYPE CODE 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 2471.00 HM3TU/H
COMPANY NAME/SITE LOCATION PLAINS ELECT. GEN & TRANS PREWITT, KM
MCKINLEY COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 05/27/81
PERMIT NO. (REGION, FILE NO.) PSQ-NM-82 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214 )-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHCNE)
r = = = = = = = r = = = r = r = = = = = = = = = = = : = r = = = r = = = = = = : = = :r = = = = = = = - = = = = = = = = = = = = = = = = = r = = = = = = = = ==r = = = = r = = = = = = = r = = = = = = = = = = r = r = r = = = r = = r = r = = = r = = = = = = r =
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT CR PROCESS MODIFICATION ... PCT EFF
STEAM GENERATOR, COAL-FIRED
2471.00 MMBTU/H
COAL HANDLING
STOCKPILING AND STORAGE
LIMESTONE HANDLING
FUGITIVE EMISSIONS
PM
S02
CO
NOX
F
PM
PM
PM
PM
0.0300 LB/T.MBTU
BAGHOUSE
0.2000 LB/MM3TU
FLUE GAS DESULFURIZATICN
0.0630 LB/MKBTU
FIRE BOX DESIGN 4 COM. CONTROL
0.4500 LB/MMBTU
FIRE BOX DESIGN t COM. CONTROL
0.0010 LB/MMBTU
NSPS
99.90
BACT
90.00
BACT
BACT
BACT
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 80
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER NM-0002
SOU"CE TYPE CODE
1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE---
EXTERNAL COMBUSTION - COAL
250.00 MW
COMPANY NAME/SITE LOCATION PLATTE RIVER PWR-RAKHIDE
NEAR FORT COLLINS, CO
LARIMER COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO.
DETERMINATION MADE BY EPA REGION VIII
(AGENCY)
JOHN DALE
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 05/22/80
ESTIMATED DATE OF START-UP
(303)-837-3763
(PHOKE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
BOILER
250.00 MW
COAL CONV
COAL CRUSHING
COAL STORAGE
COAL UNLOAD
870.00 MT/YR
870.00 MT/YR
870.00 MT/YR
870.00 MT/YR
NOX 0.5000 LB/MMBTU
DESIGN
PM 0.0300 LB/MMBTU
BAGHOUSE
S02 0.1300 LB/MMBTU
DRY SCRUBBER
PM 0.5300 LB/H
BAGHOUSE
PM 0.4000 LB/H
BAGHOUSE
PM 40.4000 LB/H
CRUSHING AGENT
PM 1.0500 LB/H
BAGHOUSE
BACT
65.00
BACT
99.70
BACT
80.00
BACT
99.70
BACT
99.70
BACT
80.00
BACT
99.70
PAGE G- 81
-------
(CONTINUED) PLATTE RIVER PWR-RAWHIDE
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATIOM
X BASIS
PCT EFF
LIME STORAGE
SILO(ASH)
5.60 MT/YR
57.70 MT/YR
PM
PM
0.0400 LB/H
BAGHOUSE
0.0100 LB/H
BAGHOUSE
BACT
99.60
BACT
99.70
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 83
ID NUMBER CO-OOia
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 350.00 MM
___ «. «. __..__._.._ » -.-.__ -.-. -.__. -._-. __ «._ _ -.
COMPANY NAME/SITE LOCATION SALT RIVER PROJECT CORONADO STATION UNI* ST. JOHNS, AZ
-.___ ___ ___ __ ____»_ ~_ ~_ ~ -. . * . "" ~
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 04/10/78
PERMIT NO. (REGION FILE NO.) AZP76-1 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION IX JIM HANSON (415)-974-8038
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_____«___.>_____ ___._____,._ ___..______.._____ _______ _, ___ __ _____ __ ___ ..__._ _ _~_ _____ ___ «»__ __.._« __^^.._ _ __ __ _ .._____.__ ___~__ ________
STEAM GEN. UNIT 350.00 MM
PM 0.0820 LB/MMBTU
ESP
S02 0.8000 LB/MM3TU
WET LIMESTONE SCRUBBER 64.00
NOX 0.7000 LB/MMBTU NSPS
NOTES
COAL CONVEYING SYS WILL BE ENCLOSED AND DUST SUPPRESENT ADDED AT TRANSFER POINTS.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: C4/01/19S3
PAGE G- 83 ID NUMBER AZ-0004 SOURCE TYPE C03E 1.1
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 890.00 MW
COMPANY NAME/SITE LOCATION SANDOW STEAM ELECT. STATION ROCKDALE, TX
MILAM COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 09/20/77
PERMIT NO. PSD-TX-28 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI TOM DIGGS <214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. S. BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, LIGNITE FIRED 890.00 MW
S02 1.2000 LB/MMBTU
6827.0000 LB/H
FGD 70.00
PM 0.1000 LB/MMBTU
ESP 99.80
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: O't/01/1933
PA3E G- 84 ID NUMBER TX-0007 SCUPCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 530.50 MM
COMPANY NAME/SITE LOCATION SIERRA PACIFIC POWER CO. VALMY, NV
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 04/04/78
PERMIT NO. (REGION FILE NO.) NV 77-02 ESTIMATED DATE OF START-UP-- 1933
DETERMINATION MADE BY EPA REGION IX DAVID SOLOMON (415)-974-8066
(AGENCY) (AGENCY CONTACT PERSON) (PHON'E)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILERS, COAL FIRED, 2 277.00 MM
S02 1.2000 LB/MMSTU
NOX 0.7000 LB/MM3TU
PM 0.10CO LB/MM5TU
BAGHOUSE 99.75
NOTES
EMISSION LIMITS APPLY TO EACH UNIT SEPERATELY. BASIS DETERMINED BY NAPS AND PSD CLASS II INCREMENT CONSIDERATIONS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 85
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933 02/13/1934
ID NUMBER NV-0002
SCU2CE TYPE CODE 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 235.00 MW
COMPANY NAME/SITE LOCATION SIKESTON BOARD OF MUNICIPAL UTILITIES SIKESTON, MO
SCOTT COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 07/14/77
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VII CHARLES WHITMORE (616 )-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, STEAM GEN, COAL FIRED 235.00 MW
S02 1.2000 LB/MMBTU BACT
WET LIMESTONE SCRUBBER
PM 0.1000 LB/MM3TU BACT
ESP
NOTES
INITIAL REVIEW POST STARTUP
(»> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 66 ID NUMBER MO-0003 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 567.00 MM, 2 EA
COMPANY NAME/SITE LOCATION SOUTHWESTERN PUBLIC SERVICE SUOAN, TX
LAMB COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/30/78
PERMIT NO. (REGION FILE NO.) PSO-TX-50 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI TOM DIGGS (214 )-767-1594
(AGENCY) (AGENCY CONTACT PERSON) ( PHOf^E )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
STEAM TURBINE, COAL-FIRED 567.00 MW
S02 508.8000 LB/H
1.2000 LB/MMBTU
LOU SULFUR FUEL
PM 0.1000 LB/MM3TU
FABRIC FILTER 98.60
SPRINKLE ROADS WITH WATER OR CHEM.
NOTES
TWO UNITS, 567 MW EACH.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 87 ID NUMBER TX-0006 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/3Z/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 348.00 MW (GROSS)
^«_ .- ___ »___w. ^ » -.._ ....__..«. __._.__._.__.«__...».»
COMPANY NAME/SITE LOCATION SUNFLOWER ELECT. COOP., INC. - HAYS, KS. NEAR HOLCOMB, KA, KS
HOLCCMB STATION FINNEY COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 05/19/80
PERMIT NO. ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VII DANIEL RODRIGUEZ (816)-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, COAL-FIRED 3389.00 MMBTU/H
NOX 0.6000 LB/MMBTU BACT
STAGED COMBUST., LEA
SOZ 0.4800 LB/MM3TU 3CD R AV BACT
LIME BASED DRY SCRUBBER SO.00
LIME BASED DRY SCRUBBER
CO 0.0640 LB/MMBTU 300 R AV BACT
Ptl 0.0300 LB/M,'iBTU BACT
FABRIC FILTER
NOTES
THE NOX LIMIT TAKES PRIORITY OVER THE CO LIMIT. IF NECESSARY THE CO LIMIT WILL BE ADJUSTED AFTER THE UNIT HAS BEEN PERFORMANCE
TESTED. THE UNIT WILL BURN LOU S WYOMING COAL.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01V933
PAGE G- 88 ID NUMBER KS-0001 SC'JSCE TYPE CCOE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOUP.CE TYPE/SIZE
EXTERNAL COMBUSTION - COAL
1440.00 MW
COMPANY NAME/SITE LOCATION SW ELECT. POWER
CANTON, TX
VAN ZANDT COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. (RESIGN FILE NO.) PSO-TX-130
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 02/23/81
ESTIMATED DATE OF START-UP--
(214>-767-1594
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
BOILERS, 2 EA
COAL UNLOAD
COAL TRANSFER
COAL STORAGE
THROUGHPUT POLLUTANT
CAPACITY EMITTED
6821.00 HMBTU/H
PM
S02
NOX
CO
PM
PM
PM
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.0300 LB/MMBTU
ELECTROSTATIC PRECIPITATOR
0.9000 LB/Mr.BTU
WET LIMESTONE FLUE SAS DESULFURIZATION
0.6000 LB/KMBTU
LOW NOX BURNERS
FLUE GAS RECIRCULATION
0.1000 LB/"M3TU
LOW EXCESS AIR
2.4000 LB/H
WET SUPPRESSION
2.4000 LB/H
ENCLOSED
2.4000 LB/H
... 4 BASIS
... PCT EFF
NSPS
99.80
BACT
87.40
NSPS
BACT
CHEMICAL STABILIZER
PAGE G- 89
-------
(CONTINUED) SW ELECT. POWER
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OH PROCESS MODIFICATION
. . . & BASIS
... PCT EFF
LIMESTONE UNLOAD
LIMESTONE TRANSFER
LIMESTONE STORAGE
PM
PM
PM
0.2000 LB/H
WET SUPPRESSION
0.6000 LB/H
ENCLOSED
0.2000 LB/H
CHEMICAL STABILIZER
NOTES
NOX LIMIT FOR BOILERS IS 30 DAY ROLLING AVERAGE.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 90
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
10 NUMBER TX-0010
SOURCE TYPE COOE 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 720.00 MM EA
COMPANY NAME/SITE LOCATION SW ELECT. POWER NABORTION, LA 71156
P.O. BOX 21106 DESOTO PARISH PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/01/81
PERMIT HO. (REGION FILE NO.) PSO-LA-117 ESTIMATED DATE OF START-UP--
DETERMINATION HADE BY EPA REGION VI JOHN BUNYAK (2141-767-1594
(AGENCY) {AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, COAL FIRED
BOILER, COAL FIRED
COAL HANDLING
720.00 MW
720.00 MW
S02
NOX
P«
CO
S02
NOX
PM
CO
PM
1.2000 LB/MMBTU
FGD
0.6000 LB/MM3TU
LCVJ NOX BURNERS
0.1000 LB/HMBTU
ESP
0.8000 LB/MMBTU
EFFICIENT COMBUSTION
0.6000 LB/MMBTU
FCO
0.6000 LB/MM3TU
LOW HOX BURNERS
0.0300 LB/Mf.BTU
ESP
0.8000 LB/MM3TU
EFFICIENT OPERATION
SPRAY APPL. & DUST COLLECT.
NSPS
76.00
NSPS
BACT
99.80
BACT
NSPS
89.50
NSPS
BACT
99.SO
BACT
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 91
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER LA-0002
SOURCE TYPE CODE
1.1
-------
NOTES
UNIT 1 UNDER 40CFR PART 60 SUBPART D. UNIT 2 UNDER 40CFR PART 60 SUBPART DA. FUGITIVE DUST CONTROLLED BY WATER SPRAY DURING CO
NSTRUCTION
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 92 ID NUMBER LA-0002 SC'JRCE TYPE C03E 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAt 720.00 MM, 2 EA
COMPANY NAME/SITE LOCATION SH ELECT. POWER DALLAS, TX 75250
2700 ONE MAIN PL.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-
PERMIT HO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (2141-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHOUE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PEP.MIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, COAL FIRED UNIT *1
6780.00 MMBTU/H
BOILER, COAL FIRED UNIT 32
6780.00 MMBTU/H
PM
S02
NOX
CO
PM
S02
NOX
203.0000
0.0300
0.7200
4882.0000
0.6000
4068.0000
0.1300
892.0000
LB/H
LB/MMBTU
ESP
LB/MMBTU
LB/H
DESULFURIZATION SYS.
LB/MMBTU
LB/H
BURNER DESIGN
LB/MMBTU
LB/H
BURNER DESIGN
203.0000 LB/H
0.0300 LB/MMBTU
ESP
0.7200 LB/MMBTU
4882.0000 LB'H
DESULFURIZATION SYS.
0.6000 LB/MMSTU
4068.0000 LB/H
99.90
90.00
99.90
90.00
PAGE G- 93
-------
BURNER DESIGN
CO 0.1300 LB/HKBTU
892.0000 LB/H
BURNER DESIGN
NOTES
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: CV01/19S3
PAGE G- 9^t ID NUMBER TX-0015 SOURCE TYPE CODE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 720.00 MW
COMPANY NAME/SITE LOCATION SW ELECT. POWER HALLSVILLE, TX
DETERMINATION IS BACT FOR A MODIFIED SOURCE. PATE OF PERMIT ISSUANCE 03/30/78
PERMIT NO. PSO-TX-64 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (21A )-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHCHE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
" --- - «- * _ __ ___^.___-. ._«.___-.-.-._ ____ __ _ __»___^_____,. »_.. .._ .,____.._-_____ _ --__..._ _______.._ _»«
COAL FIRED STEAM GEN 720.00 MW
S02 1.2000 LB/MM3TU
682.0000 LB/H
WET LIMESTONE FGO 76.00
PM 0.1000 LB/MM3TU
ESP 99.00
NOTES
TMTTTiL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. ntVXLri STATUS: CH/01/1<=33
PAGE G- 95 ID NUMBER TX-OCS1 SCJ.RCE T'iPE CODE 1.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
EXTERNAL COMBUSTION - COAL
500.00 MW
COMPANY NAME/SITE LOCATION S.C. PUBLIC SERVICE AUTHORITY
CROSS SITE
CROSS, SC
BERKELEY COUNTY
DETERMINATION IS BACT
PERMIT NO. P/C-08-190
DETERMINATION MADE BY
SOUTH CAROLINA DHEC
(AGENCY)
OTTO PEARSON
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 12/03/81
ESTIMATED DATE OF START-UP--
(803)-758-5406
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
S3 GENERATOR
THROUGHPUT POLLUTANT
CAPACITY EMITTED
500.00 MW
PM
S02
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.0300 LB/MMBTU
ESP
0.4100 LB/MMBTU
LOW S COAL
0.6000 LB/f."BTU
EQUIPMENT DESIGN S OPERATION
0.0400 LB/MMBTU
EQUIPMENT DESIGN & OPERATION
... & BASIS
... PCT EFF
NSPS
99.80
BACT
85.00
B/N
BACT
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 96.
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933 04/02/19S<+
ID NUMBER SC-C010
SOURCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 1600.00 MMBTU/H
COMPANY NAME/SITE LOCATION TACOMA CITY LIGHT TACOMA, WA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 05/11/82
PERMIT NO. (REGION FILE NO.) PSD-X-82-06 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION X DAVID TETTA (206 )-<+<»2-1597
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER
1600.00 MMBTU/H
S02
S02
NOX
NOX
0.2300
367.0000
1366.0000
0.5000
786.0000
2926.0000
LB/MMBTU
LB/H
DRY SCRUBBER
T/YR
DRY SCRUBBER
LB/MMBTU
LB/H
T/YR
85.00
85.00
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TASLE.
PAGE G- 97
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01*933
ID NUMBER1 WA-0006
SOURCE TYPE CCDE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - COAL 425.00 I1W
COMPANY NAME/SITE LOCATION TAMPA ELECT. CO. RUSKIN, FL 33601
P.O. BOX 111 HILLSBOSOUGH COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 10/15/81
PERMIT HO. (REGION FILE NO.) FSD-FL-OHO ESTIMATED DATE OF START-UP 19S1
DETERMINATION MADE BY FLORIDA DER BOB KINS (904J-488-1344
(AGENCY) (AGENCY CONTACT PERSON) (PHOME )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, COAL FIRED
425.00 MW
PM 0.0300 LB/MT.6TU
130.0000 LB/H
ESP
S03 0.8200 LB/MMSTU
3576.0000 LB/H
LIMESTONE SCRUBBER
COAL WASHING
NOX 0.6000 L6/t"',6TU
2598.0000 LB/H
EQUIPMENT DESIGN 4 OPERATION
CO 0.0140 LB/KMBTU
61.0000 LB/H
EQUIPMENT DESIGN & OPERATION
NSPS
99.00
NSFS
90.00
BACT
BACT
NOTES
BIG BEND STATION UNIT S4.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 98
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1
-------
-
o
z
UJ
13
~
^^
>-
^
UJ
2
ii
n
ii
n
n
n
n
n
n
u
n
n
u
n
n
n
n
n
n
ii
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
u
n
n
n
u
tt
n
n
M
n
n
n
ii
n
n
n
u
n
n
u
n
n
n
n
n
n
n
ii
ii
n
ii
n
n
u
u
n
n
n
i
n
n
i
n
n
n
n
i
n
n
n
ii
n
u
n
i
n
n
n
n
n
M
it
n
H
n
n
u
n
n
i
n
i
n
n
i
i
i
i
i
i
t
i
i
i
i
i
ii
n
n
n
n
n
n
n
V) u.
HI U-
vi uj
CD t-
CJ
a a.
, ,
«
z
o
M
H-
O
HI
U.
HI
O
O
E
in
in
UJ
8
or
a
o:
o
k~
z
UJ
E
a.
HI
a
UJ
in
H- -1
M 0
E a:
M H-
-J Z
O
Z O
o
M
in
in
M
UJ
5a
< UJ
5 H-
-J HI
-1 E
O UJ
a.
t-
3 >-
D. H-
Z M
13 O
D <
O a.
CK <
I O
H-
H-
u
LU
-> r-
gj HI
in a
UJ
in a.
UJ
in in
in HI
uj :c
0 H-
o
o: o
CJL H~
o
o
t
in
CO
in
z
cc o
UJ HI
CD H-
CO <
3 U
a HI
u u.
in M
o
UJ O
0 *"
H. Z
10 o
g ^?P?
co HI co in m
E x "* § to £
X X >- X K X
CO CO O: CO O CD
_J _J 0 _l U -J
o o o o
<
0 0 E
in z o.
o
o
t
o
in
ro
in
t
M
5
»
^r
UJ
CD
UJ
a-
Hl
U.
1
O
u
o
o^
o-
UJ
in in
SH-
Hl
I 1-
O HI
< 1
CO
z
o
HI
in
in
HI
E
UJ
O
CO
u.
o
z
o
HI
H-
HI
E
UJ
H-
UJ
a
UJ
£
z
HI
O
UJ
in
a.
z
g
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
EXTERNAL COMBUSTION - COAL
700.00 MW
COMPANY NAME/SITE LOCATION TUCSON ELECT. POWER CO. UNITS SI & 2
TUCSON, AZ
APACHE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. (REGIOH FILE NO.) AZ77-01
DETERMINATION MADE BY EPA REGION IX
(AGENCY)
DAVID SOLOMON
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 12/21/77
ESTIMATED DATE OF START-UP-
(415 J-974-8066
I PHONE)
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
COAL FIRED GEN. UNITS, 2 350.00 MW EA
COAL HANDLING
POLLUTANT
EMITTED
PM
SO 2
NOX
PM
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.0340 LB/MM3TU
HOT SIDE ESP
0.6900 LB/Mr3TU
KET LIME SCRUBBER
0.6970 LB/M:!3TU
... & BASIS
... PCT EFF
BACT
BACT
64.00
NSFS
BOTTOM ASH
FLY ASH
PM
PM
SPRAY APPLIC. & DUST COLLECT
HYDRALIC CONVEYANCE
PNE'JMATIC CONVEYANCE
NOTES
DETAILED CONTROL STRATIGIES FOR THESE FACILITIES IS GIVEN IN PERMIT. WET SUPPRESSION SHALL BE USED TO CONTROL FUGITIVE DUST DU
RING CONSTRUCTION. SAMPLING OF COAL IS REQUIRED. THIS DEGREE OF CONTROL WAS PROPOSED BY THE CO. IN ITS A PPLICATION.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 100
INITIAL REVIEW POST STARTUP
REVIEW STATUS'- CH/01/1Q83
ID NUMBER AZ-C002
SOURCE TYPE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE-
EXTERNAL COMBUSTION - COAL
200.00 MM3TU/H
COMPANY NAME/SITE LOCATION TVA - AFBC PILOT PLANT - SHAWNEE STEAM *
AFBC PILOT PLANT
PADACAH, KY 42001
MCCRACKEN COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. C-80-18
DETERMINATION MADE BY KENTUCKY DAPC
(AGENCY)
BILL DILLS
(AGENCY CONTACT PERSON)
DATE Or PERMIT ISSUANCE 04/14/80
ESTIMATED DATE OF START-UP 1962
(502)-564-3382
(PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
. » , ,
FLUIOIZED BED BOILER 200.00 MKBTU/H
S02 1.2000 LB/MMBTU BACT
FLUIOIZIED BED COMBUSTION 85.00
PM 0.1000 LB/flMBTU BACT
BAGHOUSE 99.90
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS'- 04/01/1933 02/1V19S4
PAGE G- 101 ID NUMSER KY-0007 SOURCE TYPE CODE 1.1
-------
CJ M
CJ II
X II
3
XI
o
o
o
ro
CJ
_j
o
u
1
o
w
OKBUST
CJ
Z
or
UJ
H-
X
UJ
t
i
I
UJ
N
M
in
LU
O.
H-
UJ
CJ
b
to
1 >
(-
z
^J
o
o
CD
§
19
uj
J
eP
jc
^~
^
o
CL'
O
CO
V)
UJ
y
tt
o
1
UJ 15
to a
M I
0 tt
a o
< u
a D:
a
1 UJ
< o
> oj
t f^
z
o
M
h-
U
O
UJ
1-
H
in
LU
z
z
a.
g
u
O- i-l
N. o-
UI rH
CJ
X
o
0 1
1
a
1 13
i i
UJ H-
cj D:
Z "^
- >-
LU ^ O
M CJ Z
u. n LU
M t- ID
0 2 <
O LU
r ^
"*
D:
0
u.
CJ CD
CO Is- UJ
~
o o:
o: a: x <
>- >- CD 1
N N < O
t- H- co n:
o o
o o
O 0
, ,
l/t -0
e\j ro
fO rH
E i?
-J
O
U
«. x
h- K
o o
0 0
o o
o o
o o
CJ CJ
2 I
< z
-1 <
a. -i
Q.
CD
z o
HI Z
in x
3 in
a *
u 3
o o
U 0
,
>.
a
h*
O
10
2
*t
tc
J_
(O
to
UJ
J
u_
o
t
4
t
UJ
-J
£D
I
_j
_j
< u.
u.
Z UJ
x
H- ro
O. o
UI
u a.
u r:
< 5
o
o
H- n:
CD CJ
z
M >-
J D:
' <
M H-
2 0
oc
tn
HI
D:
^ UJ
> <
H~ }
ui to
U M
M K
10 M
CC
i : LU
jQ_
tn o
UJ LU I
t tt *f
t- D O
to cy t~i
UJ h-
Z£ D' M
o tn Q
MHO
H- <
2: o to
31 I X
D: O H-
UJ U.
UJ V- 1**
Ct UJ N.
(0 O
1 U. 1
U. rH
< O CO
UJ 1
0:0:0
- h-
)- _J H
H *T H
< 2 o:
-
UJ 1*1 ll K-
M CO II
> a* n LU
LU rH II U
II
-J o
< s.
I O
i in
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE-
EXTERNAL COMBUSTION - COAL
1600.00 MW
COMPANY NAME/SITE LOCATION UTAH Pk'R « LT CO-HUNTER STATION
NEAR CASTLE DALE
UT
EMERY COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MADE BY EPA REGION VIII
(AGENCY)
JOHN DALE
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 06/02/80
ESTIMATED DATE OF START-UP 1983
(303)-837-3763
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
ACTIVE STORAGE
ASH SILO UNLD
ASH SILO VENT
BOILER, 84
THROUGHPUT POLLUTANT
CAPACITY EMITTED
PM
VE
VE
PM
VE
860.00 MW
NOX
PM
S02
VE
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
2.0000 LB/H
SPRAY & ENC.
20.0000 '/. OPACITY
20.0000 7. OPACITY
KEPT DAMP
49.0000 LB/H
FF
20.0000 7. OPACITY
0.5500 LB/MM3TU
BOILER DESIGN
0.0300 LB/MM3TU
FF
0.1200 LB/MHBTU
SCRUBBER
20.0000 /. OPACITY
... t BASIS
. . . PCT EFF
BACT
90.00
BACT
100.00
BACT
99.80
BACT
65.00
BACT
90.00
BACT
90.00
PAGE G- 103
-------
(CONTINUED) UTAH PUR & LT CO-HUNTER STATION
PROCESSES SUBJECT
TO THIS PERMIT
CONV
HAUL ROADS
INACT STORAGE
LIME T/S
SLUDGE MIX(ASH)
TRANS
TRUCK UNLD
===========s======s=========r=r===s====:
THROUGHPUT POLLUTANT
CAPACITY EMITTED
2.50 MMT/YR
PM
VE
PM
PM
VE
VE
VE
2.50 MMT/YR
PM
VE
2.50 MMT/YR
PM
VE
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
5.0000 LB/H
ENC.
20.0000 7. OPACITY
2.7000 LB/H
ASPHALT + H20
40.0000 LB/H
SEAL. & COMP.
20.0000 7. OPACITY
20.0000 '/. OPACITY
FF
20.0000 /. OPACITY
FF
1.0000 LB/H
SPRAYS * ENC.
20.0000 7. OPACITY
0.1000 LB/H
SPRAYS & ENC.
20.0000 7. OPACITY
... & BASIS
... PCT EFF
BACT
90.00
BACT
90.00
BACT
90.00
BACT
99.80
BACT
99.80
BACT
98.50
BACT
98.50
NOTES
CEM QA REQUIRED BY 40CFR, PART 60, SUBPART DA. BOILER EMISSION COMPLIANCE FOR SOX, NOX, OPACITY WILL BE DETERMINED BY CEM REPO
RTS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 104
INITIAL PEVIEH POST STARTUP
L^ 3'iAluS- 04/01/1933 02/13/198'+
ID NUMBER UT-0021
SO'JSCE TYPE CODE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/19S*
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 2080.00 MW
^ __ _ -. __ _ -.__ .__^_____»_ _ _^.___ _-. ___ «._ __«_^_ «.__ _ _________»_
COMPANY NAME/SITE LOCATION WASHINGTON WATER POWER CO. - , WA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 11/17/82
PEPMIT NO. (REGION FILE NO.) PSD-X-S3-01 ESTIMATED DATE OF START-UP 198*
DETERMINATION MADE BY EPA REGION X PAUL BOYS (206 )-<+42-1567
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
CGS BOILER
ROTARY CAR DUMPER (COAL)
ROTARY CAR DUMPER (LIMESTONE)
S02 0.2200 LB/KKBTU 300 R AV
11*0.0000 LB/H 24H D AV
NOX O.SOOO LB/MMBTU S3. COAL
0.6000 LB/t-TSTU BIT. COAL
LIMITS ARE 30 DAY ROLLIN AVG
PM 0.0300 LB/NM3TU
VE 20.0000 7. OPACITY
CO 332.0000 LB/H
VOC 3.3200 LB/H
PB 0.2700 LB/H ANNUAL AV
BE 0.0200 LB/H ANNUAL AV
HG 0.0300 LB/H ANNUAL AV
F 1.1500 LB/H ANNUAL AV
SUL* 80.9000 LB/H ANNUAL AV
PM 0.0100 GR/DSCF
BAGHCUSE
VE 5.0000 /. OPACITY
PM 0.0100 GR/DSCF
BAGHOUSE
VE 5.0000 7. OPACITY
90.00
90.00
PAGE G- 105
-------
(CONTINUED) WASHINGTON WATER POWER CO.
PROCESSES SUBJECT
TO THIS PERMIT
CONVEYORS
COAL CONVEYOR DISCHARGE
COAL CONVEYOR TRIPPERS
TRANSFER HOUSES
COAL SUPPLY SYSTEM
COAL SILOS
LIMESTONE SILOS
BOTTOM ASH DISPOSAL
THROUGHPUT POLLUTANT
CAPACITY EMITTED
PM
VE
PM
VE
PM
VE
PM
VE
PM
VE
PM
VE
PM
VE
PM
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.0100 GR/DSCF
BAGHO'JSE
5.0000 V. OPACITY
TELESCOPIC CHUTES/LOWERING WELL
20.0000 X OPACITY
0.0100 GR/DSCF
BAGHOUSE
5.0000 X OPACITY
0.0100 GR/DSCF
BAGKQUSE
5.0000 X OPACITY
0.0100 GR/DSCF
BAGHOUSE
5.0000 X OPACITY
0.0100 GR/DSCF
BAGHOUSE
5.0000 X OPACITY
0.0100 GR/DSCF
BAGHCUSE
5.0000 X OPACITY
... & BASIS
... PCT EFF
99.00
75.00
99.00
99.00
99.00
99.00
99.00
FIXATED W/SCRUBBER SLUDGE
100.00
PAGE G- 106
-------
(CONTINUED) WASHINGTON WATER POWER CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
ROAD DUST
FLY ASH HANDLING t SILOS
WASTE TREATMENT BLDG.
DEAD STORAGE
PM
PM
VE
PM
VE
PM
VE
CHEM. STABILIZ..DESIGN 8 OPER. PRACT.
0.0100 GR/DSCF
BAGHOUSE
5.0000 X OPACITY
0.0100 GR/DSCF
BAGHOUSE
5.0000 y. OPACITY
20.0000 GR/DSCF
SURFACE STABILIZATION
95.0000 7. OPACITY
85.00
99.00
99.00
NOTES
THE PROPOSED CONTROL SYSTEM CONSISTS OF A LIMESTONE FGD SYSTEM FOR S02 REMOVAL FRECEEDED BY A BAGHOUSE (OR POSSIBLY AN ESP) FO
R PARTICULATE REMOVAL. THE APPLICABLE TRACE MATERIALS WILL ALSO BE REMOVED TO SOME EXTENT
BY THE PARTICULATE AND SQ2 CONTROL SYSTEMS. NOX.CO.VOC ARE MINIMIZED BY COMBUSTION CONTROL (IE. EXCESS AIR CONTROL, ETC.). AMO
UNTS SITED ARE EMISSIONS PER UNIT.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 107
INITIAL REVIEW POST STARTUP
REVIEW STATUS: C4/01/19S3
ID NUMBER WA-0003
SOLACE TYPE CCDE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/192.4
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - COAL 640.00 MW (NET)
COMPANY NAME/SITE LOCATION WEST TEXAS UTILITIES CO. OKLAUNION, TX
WILBERGER COUNTY
tf
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 05/20/82
PERMIT HO. 9015 ESTIMATED D4TE OF START-UP-- 1932
DETERMINATION MADE BY TEXAS ACB JAMES CROCKER (512 )-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . i BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
._.»_..._._. _ ___ __......___.._ »_ __» _______ .._ __ ...... -.____ «. _ _ _ _.__ ._..___..-.__..__
STEAM GENERATOR 6.80 MMMBTU/H
PM 0.0300 LB/MMBTU NSPS
ESP 99.70
S02 0.5000 LB/MM3TU NSPS
WET LIMESTONE SCRUBBER 70.00
NOX 0.5000 LB/ttMBTU
LOW NOX BURNERS
COAL & LIMESTONE STORAGE/HANDLI*
PM 60.0000 LB/H
DUST CONTROL SYSTEM
NOTES
THIS IS A COAL FIRED BOILER BURNING LOW SULFUR COAL ( .bV/. S WORST CASE).
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FCR THIS TABLE. REVIEW STATUS: 04/01/1<533
PAGE G- 108 ID NUMBER TX-C012 SCL'SCE TYPE CCDE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/23/198'+
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - COAL 1160.00 MW
COMPANY NAME/SITE LOCATION WISCONSIN ELEC. POWER CO., PLEASANT PRA* , HI
KENOSHA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/09/76
PERMIT NO. EPA-5-76-A-1 ESTIMATED DATE OF START-UP 1980
DETERMINATION MADE BY EPA REGION V BONIFACE THAYIL (312 )-8S6-6C54
(AGENCY) (AGENCY CONTACT PERSON) (FHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
, .
BOILER, COAL FIRED, Z EA 560.00 MW
PM 0.1000 LB/MMSTU NSPS
ESP 99.00
S02 1.3000 LB/MMBTU COAL NSPS
o.eooo LB/r;r:3TU OIL
LOW S FUEL -- <0.7X COAL, <0.5X OIL
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 0^/01/1983
PAGE G- 109 ID NUMBER WI-0030 S^L'^CE TYPE CCOE 1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
EXTERNAL COMBUSTION - COAL
400.00 MW
COMPANY NAME/SITE LOCATION WISCONSIN POWER & LIGHT CO., EDGEWATER *
SHEBOYGAN, WI
DETERMINATION IS BACT FOR A HEM SOURCE.
PERMIT NO. EPA-5-77-A-3
DETERMINATION MADE BY EPA REGION V
(AGENCY)
BONIFACE THAYIL
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 04/36/77
ESTIMATED DATE OF START-UP
(312)-886-6054
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT 03 PROCESS MODIFICATION
& BASIS
PCT EFF
BOILER, COAL FIRED
400.00 MM
PM
S02
0.1000 LB/MMBTU
1.2000 LB/MM3TU
NSPS
NSFS
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 110
INITIAL REVIEW POST STARTUP
REVIEW STATUS-' 04/01/1933
ID NUMBER WI-0029
SOURCE TYPE CCDE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198<+
SOURCE TYPE/SIZE-
EXTERNAL COMBUSTION - COAL
321.00 MV4
COMPANY NAME/SITE LOCATION WISCONSIN PUBLIC SERVICE CORP., WESTON
MARATHON COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. EPA-5-77-A-4
DETERMINATION MADE BY EPA REGION V
(AGENCY)
PROCESSES SUBJECT
TO THIS PERMIT
BONIFACE THAYIL
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 05/11/77
ESTIMATED DATE OF START-UP--
( PHONE )
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
t BASIS
PCT EFF
BOILER, COAL FIRED
321.00 MW
FM
S02
0.1000 LB/MM3TU
1.2000 LB/Mf!BTU
NSPS
NSPS
NOTES
(*> INDICATES DATUM WAS TRUNCATED FCR THIS TABLE.
PAGE G- 111
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER WI-0028
SC'J"CE TYPE CCDE
1.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - OIL
COMPANY NAME/SITE LOCATION ANGUS PETROTECH » CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 11/29/83
PERMIT NO. 4132002-004 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY KERN COUNTY APCD TOM PAXSON <805 )-661-36S2
(AGENCY) (AGENCY CONTACT PERSON) (FHOfJE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
______ _____«__ _« __»_«___.« ____ ___ ____. .-- __ . __ ^ . - _ -.
BOILER, OIL FIRED 62.50 MMBTU/H
S02 61.4000 LB/D
SCDIUM BASED SCRUBBERS
NOX 199.0000 LB/D
LOW NOX BURNERS
NOTES -
(»> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 112
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER CA-0069
SC'JRCE TYPE CODE
1.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOUPCE TYPE/SIZE- EXTERNAL COMBUSTION - OIL 81.90 MSTU/H
COMPANY NAME/SITE LOCATION HOOKER CHEMICAL & PLASTICS CORP. PERRYVILLE, MO 21903
P.O. BOX D CECIL COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 07/03/79
PERMIT HO. 78MD07 ESTIMATED DATE OF START-UP 1930
DETERMINATION MADE BY EPA REGION III BOB BLASZCZAK ( 215 J-597-8186
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
OIL FIRED BOILER 81.90 MK3TU/H
S02 355.1000 LB/H BACT
S IN FUEL LIM. TO 1.3X BY WT
NOTES -----------
355.1 LB/H, 3 BOILERS (2 EXISTING & 1 NEW) WITH COMMON STACK
NEVER BUILT - COMPANY OUT OF BUSINESS
STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE 6- 113
kEVItW STATUS: 04/01/1933
1.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - OIL 185.00 MM3TU/H EA
COMPANY NAME/SITE LOCATION HOUSTON LIGHTIH3 & POKER » TX 77001
MATAGORDA COUNTY
__ _ __ _ _ ____.-.-.___ ___..___-.____. __. _ _ .___«,___ .. _______ _ _ _ _. ._ _....____-.___ _ _ _ _ _______
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 01/16/80
PEPMIT NO. (REGION FILE NO.) PSD-TX-209 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214>-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, Z EA 185.00 MMBTU/H
S02 0.5000 LB/MMSTU BACT
92.1000 LB/H
LOW SULFUR *2 FUEL OIL
PM 0.1000 LB/MM3TU BACT
18.3500 LB/H
FGD
02 CONTROL
NOX 0.3000 LB/MMSTU BACT
55.0000 LB/H
LCW NOX BURNER
LEA FIRING
NOTES
NO. 2 FUEL OIL < 0.5X SULFUR BY WT. CONTINUOUS OPERATION 8760 HR/YR
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 114 ID NUMBER TX-0013 SOU'SCE TYPE CODE 1.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - OIL
-- __ _ __ ____-._ ____ _ _ _. ____..____ _____ ___.._ __»,.._ _ A«»_ UU_.V^_1»»___W V__.v«««.____^_
COMPANY NAME/SITE LOCATION NORTHERN INDIANA PUBLIC SERVICE CO. , SC* , IN
JASPER COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/16/79
PERMIT NO. EPA-5-79-A-25 ESTIMATED DATE OF START-UP
DETERMINATION HADE BY EPA REGION V BONIFACE THAYIL (312)-eS6-6054
(AGENCY) (AGENCY CONTACT PERSON) (PHC1IE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GENERATOR, OIL FIRED, 2
S02
LIMITED TO O.SX S FUEL OIL
NOX 75.0000 PFM
NOTES
EACH TURBINE RESTRICTED TO 2000 H/YR
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: OVOl^SS
PAGE G- 115 ID N'JJIBER IN-0024 SC'JSCE TYFE CODE 1.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - NATURAL GAS 18.00 KW
COMPANY NAME/SITE LOCATION APPLIED POWER TECHNOLOGY OROVILLE, CA
~ _ _ ._«.._______ ^.___»_ _-.___ «___ _____________ __.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE Of PERMIT ISSUANCE 11/29/83
PERMIT NO. SAC 83-02 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION IX JOE SLAMOVICH (415)-974-8235
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
_ ..-. .. _ _ _ __ _ __ _ _ _ _ »., _...,____ .. __ ____«.
BOILER, 2 307.10 MI1BTU/H
PM 11.9000 LB/H
ESP & MULTICLONES 96.70
NOX 35.4000 LB/H
ccr;3USTioN CONTROLS
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PA3E G- 116
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER CA-0066
SOURCE TYPE CODE
1.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
=.^z = =; = - = i:- -zz = =-----~-- = = -~- = --z:~- = = --~~--- = -~-- = --~~- = ~--~ ---- = -~ -~~-~ = -~~--~:::- = -~~~~~ = ~ = ~~::~ '
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - NATURAL GAS 175.00 MLB/H
-------------
COMPANY NAME/SITE LOCATION CONSUMERS POWER CO. MIDLAND, MI
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE- 06/01/81
PERMIT NO. 99-81 ESTIMATED DATE OF START-UP-- 1932
DETERMINATION MADE BY MICHIGAN DNS DAVID FERRIER (5171-3C2-1333
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
___ _ _ «.-,,___.,_.- . _ _ -.»_ "* "
BOILERS, NAT. GAS, 3 EA 175.00 MLB/H
NOX 0.2000 LB/MHBTU
BURNER DESIGN & EX. AIR CONTRL
NOTES
3 NATURAL GAS-FIRED BOILERS.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 117
INITIAL REVIEW POST STARTUP
REVIEW STATUS: e4/01/1933 03/13/1984
ID NUi!3ER MI-0013
SG'JRCE TYPE CODE
1.3
-------
APPENDIX -- DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - NATURAL GAS
COMPANY NAME/SITE LOCATION MQBAY CHEMICAL CORP. KANSAS CITY, MO
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/16/83
PERMIT NO. 485 ESTIMATED DATE OF START-UP-- 1984
DETERMINATION MADE BY KANSAS CITY AQS LARRY COLE (816)-274-25Cl
(AGENCY) (AGENCY CONTACT PERSON) IPHCHE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
.
BOILER, 2 TOTAL 198.60 MMBTU/H
NOX 0.2000 LB/HMBTU NSPS
S02 MINIMIZE
VOC MINIMIZE
FM MINIMIZE
CO MINIMIZE
NOTES
SOURCE TEST FOR NOX BY MAY 1984. ALLOWABLE FUELS ARE NATURAL GAS / *3 FUEL OIL.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: C4/13/19S4
PASE G- 118
ID NUMBER MO-0006 SOURCE TYPE CODE 1.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE-
EXTERNAL COMBUSTION - NATURAL GAS
2000.00 HP
COMPANY NAME/SITE LOCATION SOUTHERN NAT. GAS
ENTERPRISE, MS
CLARKE COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-MS-036
DETERMINATION MADE BY MISSISSIPPI DNR
(AGENCY)
DWIGHT WILEY
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 08/21/81
ESTIMATED DATE OF START-UP
(60D-354-2550
(PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- - * --. -. _ __»___._»._»_«._: __..__....___..._..__.,..__...«.,.__«,_____ -,__._»__«. _ __ _
ENGINE, NAT. GAS 14000.00 CF/H N. G.
NOX 37.4000 LB/H NSPS
163.9000 T/YR
BOILER DESIGN & OPERATION
CO 10.5000 LB/H NSPS
46.2000 T/YR
BOILER OPERATION & DESIGN
NOTES
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1=33
PAGE G- 119 ID NUMBER MS-0003 SOURCE TYPE CODE 1.3
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - WOOD WASTE 155.62 MMBTU/H
- - ----. . -- -. «.
COMPANY NAME/SITE LOCATION AFTON GENERATING CO. AFTON, WY
» ~ -. . !» -- -.-. «-^ ,-. ^ ^»«- __ .__.._____« _.«^
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 02/15/83
PERMIT NO. CT-483 ESTIMATED DATE OF START-UP 1934
DETERMINATION MADE BY WYOMING AQD LEE GRIBOVICZ (307)-332-3144
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- __ _ _ _ «.___».._ «._ _ _ ___ : «, _ __
BOILER, WOOD & BARK WASTE 155.62 MMBTU/H
PM 0.0500 GR/DSCF AT 127. C02 BACT
0.1000 LB/MM3TU
MULTICLOHE & LOU ENERGY WET SCRUBBER 80.00
CO 0.4400 LB/MM3TU BACT
CCTBUSTION CONTROL
VOC 0.0900 LB/MMBTU BACT
NOX 0.2400 LB/MtlBTU BACT
COMBUSTION CONTROL
NOTES
AS PERMIT CONDITION, AN ADJACENT LUMBER MILL WILL DISCONTINUE USE OF 2 WOOD WASTE BURNERS, A WOOD CHIP FIRED BOILER, AND AN 01
L FIRED BOILER.
INITIAL REVIEW POST STARTUP
<*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 120 ID NUMBER HY-0003 SOURCE T1FE CCDE 1.4
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - WOOD WASTE
COMPANY NAME/SITE LOCATION CO-GEN COEUR D'ALENE, ID
_»__ _.... _ __ __,____ __.«_ ___ __ . _ . w , « _ -. .._ __«.^^..^,. ~ ^ ^ » ^
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/15/83
PERMIT NO. ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY IDAHO AQB CLINT AYER (2081-334-5360
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
z = = r = = = = = r = = = = = = = = = = = = = = = = = = = = = = = = = = = = = === = = = = = = = = =: = = = r = = = ==r = = = = = = = = = = = = = = = = = = = === = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, WOOD FIRED 104.00 MMBTU/H
PM 3.9500 LB/H
MULTICLONE & BAGHOUSE 98.40
CO 5.9000 LB/H
NOX 19.0000 LB/H
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 121
ID NUMBER ID-0001A
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
SC'JHCE TYPE CODE 1.4
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - WOOD HASTE 6.00 MW
COMPANY NAME/SITE LOCATION CO-GEN., INC. COEUR D'ALENE, ID
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/15/83
PERMIT NO. (REGION FILE NO.) PSD-X81-16 ESTIMATED DATE OF START-UP 1933
DETERMINATION MiDE BY EPA REGION X PAUL BOYS (206J-442-1193
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER
6.00 MH
PM
NOX
CO
VOC
0.0340
16.6000
0.1700
88.2000
0.2200
117.6000
0.0800
117.6000
LB/MMBTU
T/YR
ESP
LB/MM3TU
T/YR
LB/MMBTU
T/YR
LB/MMBTU
T/YR
99.00
BACT
BACT
BACT
NOTES
GENERAL DESIGN CONTRIBUTES TO REDUCTION OF OIL POLLUTANTS AND INCLUDES 1) INCREASED BOILER HEIGHT FOR BETTER EFFICIENCY, 2) 0V
ERFIPE ANO U?;DERFIRE AIR, 3) FEEDWATER HEATERS TO INCREASE EFFICIENCY.
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PA3E G- 122
ID NUMBER ID-0001
TNTTTAL "EVIEW POST STARTUP
KLVIt* SIAiUS: 0-+/01/1933
SO'J-CE TYPE CODE 1.4
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - WOOD WASTE
COMPANY NAME/SITE LOCATION HAYFORK COGENERATION PROJECT CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/14/83
PERMIT NO. TAC-012 ESTIMATED DATE OF START-UP 1985
DETERMINATION MADE BY NORTH COAST UNITED AQMD CHUCK SASSENRATH (707 >-443-3093
(AGENCY) (AGENCY CONTACT PERSON) (PHCN'E)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
BOILER, WOOD WASTE 236.00 MH3TU/H
PM 0.0400 LB/MMBTU
MULTICLONE/ESP 99.30
NOX 0.1500 LB/MM3TU
DESIGN
CO 0.3500 LB/M:!3TU
COMBUSTION MODIFICATION
VOC 0.0700 LB/MKSTU
DESIGN
NOTES
STATE FILE 9 A320-024
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 123 ID NUMBER CA-0070 SOURCE TYPE CODE 1.4
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - WOOD WASTE 50.00 M»
COMPANY NAME/SITE LOCATION MCNEIL GENERATING STATION BURLINGTON, VT
BURLINGTON ELECTRIC LIGHT DEP*
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 05/01/80
PERMIT NO. ESTIMATED DATE OF START-UP-- 1984
DETERMINATION MADE BY VERMONT AEC HAROLD GARABEDIAN (802)-62S-3395
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
WOOD FIRED FURNACE 670.00 MMBTU/H
PM 0.0070 LB/MMBTU
0.0070 GR/DSCF AT 12X C02
MEC. DUST COLLECTOR & ESP 99.90
80X-MEC COLLECT. & 99.5X-ESP
NOTES
418000 ACFM AT 310F-CYCLONES-LARGE DIA. CERAMIC-24 TUBE, 58 IN. DIAMETER, 12.3 FT LONG, DELTA P=3.4 IN. H20, INLET VEL. 63.1FT
/SEC-ESP-KEIGHTEO WIRE TYPE .TOTAL PLATE AREA 280000 SQ. FT.,SCA=672 SQ. FT./1000 ACFM, LINEAR VEL. 3 FT/SEC
- 9 FIELDS, 119 GAS PASSAGES, 9 IN. PASSAGE SPACING, 45 FT GAS TRAVEL DISTANCE.
INITIAL REVIEW POST STARTUP
INDICATES DATUM WAS TRUNCATED FCR THIS TABLE. REVIEW STATUS:
PAGE G- 124 ID NUMBER VT-0002 SO'JRCE TYPE CODE 1.4
-------
^.
CO
O-
\
CM
CM
X.
in
o
ID
M
t-
to
M
UJ
O
CO
O
UJ
H
Ul
a
i
i
x
M
i
UJ
a
a
n
it
ii
n
u
n
i
n
n
n
n
n
n
n
n
n
n
ii
n
M
n
n
n
n
n
n
it
u
n
n
n
n
n
n
n
M
ir
n
n
n
it
n
n
u
I
H
n
II
n
it
II
n
u
n
II
n
it
n
II
ii
u
H
II
M
II
n
n
n
n
n
it
n
ii
n
n
u
n
n
n
it
n
n
n
M
n
it
i
i
i
i
I
i
n
n
it
n
u
M
u
it
it
n
ii
n
u
n
it
n
n
it
t
i
i
i
I
I
i
II
it
n
n
ii
n
it
n
ti
n
ti
n
~r
X
3
t~
5-
f~
O
o
Ul
Kl
UJ
H-
to
2f
§
O
3
1
z
o
n
to
3
e
o
u
3J
z
cc
UJ
l-
X
UJ
1
1
UJ
M
N
UJ
a.
^.
t-
UJ
o
CE
8
to
>-
H
Q
u
a
UJ
OL
)
<
>
X
K
*»
f
o
z
M
.
D.
O
O
U
U
£
1-
U
UJ
_J
UJ
(0
^t
^^
Ul
1
1-
8
UJ
K
M
to
UJ
E
Z
z
^
a.
j;
o
o
^
CO
N
O
N
O
1
1
UJ
y
5
3
to
CO
M
1-
l-l
E
a:
UJ
a.
u.
O
Ul
t-
o
t
UJ
g
O
(0
2
UJ
Z
^f
g
u.
1-
(J
«t
to
CO
M
CJ
M
1-
z
J~
n;
UJ
h-
UJ
a
^
CO
a-
i
i
a
3
i
i-
^_
to
u.
0
Ul
t-
<
o
o
UJ
t-
<
r:
M
t-
UJ
(?
-£>
O-
g
t-
M
J^
C*
UJ
a.
M
^
f^
in *^
1 ^
in o
^ X
i a
CM
^i
tn
z
o
C£
Ul
a.
}_-
a: u
UJ <
^: H
u z
o o
t£ O
u
si
> ui
ID
^^
U >-
< o
z
en uj
< CD
in ta-
t
>-
CO
UJ
o
<
i;
o
M
t-
<
z
T.
ci:
UJ
1-
UJ
O
1 10
1 >-l
i to
i -a.
II CO
i
i »
n
n
i
t
ii
i
i
t
i
t
u
i
i
t
t
t
i
i
t
t
n
i
t
i
i
i
i
i
i
t
i
i
t
i
i
1 CO
1 I-
1 M
1 M
1 _J
1
I Z
1 O
1 M
1 CO
to
1 M
I E
1 UJ
II
1
1
II
! z
1 <
1 3
1 -1
1 -I
1 O
i a.
i
n
i
i
i
i
i
i
i h-
! 2
1 X
t 3
1 O
I D:
x.
1 1-
t
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 t-
1 O
I UJ
i ->
1 (0
1 3
1 CO
1
1 10
1 UJ
i to
t to
1 UJ
I O
I O
t a
1 OL
u.
u.
UJ
H
o
a.
t
§
M
^
u
u.
M
O
o
E
(/)
to
UJ
o
o
G?
a.
a
0
k_
z
UJ
x:
CL
M
*"^
CJ
UJ
_ J
o
OL
z
o
u
o
UJ
t-
1
M
y
UJ
1-
t-l
U
a
o
h-
M
D:
Ul
a.
to
n
X
t-
o
0
»- in *- t- i- t-
o o u u o
< CM «t - £D 03 CO BJ
_J U _l _l _l _J
O O O O O
o o o o o
O O CO 0 O
M CJ O CM I-l
* * *
O O O O rH
O X CM
E O O O O
a. > z to u
-,-
3
5
£
o
o
tn
K)
CK
UJ
_J
M
O
CO
z
LU
M
0
M
U.
U.
UJ
UJ
re
o
E
t
>-
n:
<(
D
O
U
UJ
to
UJ
X
h-
fy_
o
u.
X
o
o
z
^(
or
E
M
a.
a.
UJ
[_
O:
O
u.
s:
m
CO
UJ
a
to
UJ
M
O
UJ
M
u to
u. to
U- >-
UJ -J
z z
o <
M
t- U
U M
-J c5
-J Z
o o
u o
UJ
CO 0
UJ H
M
CK UJ
uj 3
to a
z a
M Ul
tt
tO M
z a
O Ul
-1 Lt
U
>- 1-
u p
O
3 tO
>- <
3
to
M -J
O
-J a:
0 1-
i n: z
1 t- 0
z u
to o
tu u E
H- a
O E
Z CL 1-
a.
CO
to
o
a.
UJ
M
UJ
DC
UJ
o
o
-
<
UJ
a;
D:
ut
£0
§
cc
o
to
<
I
CD
UJ
ID
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE---
EXTERNAL COMBUSTION - WOOD WASTE
COMPANY NAME/SITE LOCATION ULTRASYSTEMS
BLUE LAKE, CA
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. HAC-129
DETERMINATION HADE BY NQRTH COAST UNITED AQMO
(AGENCY)
CHUCK SASSENRATH
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/12/6'*
ESTIMATED DATE OF START-UP 1980
<707)-4«-3093
(FHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
4 BASIS
PCT EFF
BOILER, WOOD WASTE
162.00 MH3TU/H
PM
0.0450 LB/MMBTU
MULTICLONE/GRANULAR BED ELECTO-SCRUBBER
99.20
NOTES
STATE FILE A320-029
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 126
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER CA-0077
SO'J"CE TYPE CODE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
EXTERNAL COHBUSTION - MULTIPLE FUELS
65.00 MW
COMPANY NAME/SITE LOCATION AMES MUNICIPAL POWER PLANT
AMES, IA
STORY COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MADE BY EPA REGION VII
(AGENCY)
DANIEL RODRIGUEZ
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 11/05/79
ESTIMATED DATE OF START-UP
<816)-374-6525
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
t BASIS
FCT EFF
BOILER, UNIT 88, STEAM GEN.
769.00 MMBTU/H
PM 0.1000 LB/MMBTU
HOT SIDE ESP'S
S02 1.2000 LB/KMBTU
LOW S COAL
NOX 0.7000 LB/KMBTU
BOILER DESIGN
BACT
99.60
BACT
BACT
NOTES
UPON STARTUP OF UNIT 8, S02 EMISSIONS FROM EXISTING UNITS 5,6, AND 7 WILL BE REDUCED FROM PRE-MODIFICATION EMISSION LEVELS EEC
AUSE OF A PROJECTED VIOLATION OF THE 2<*HR S02/NAAQS. SEE IO',JA CONSENT CRDER 79-A-007. THE STACKS ON TWO EXISTING UNITS
AMD CM PROPOSED UNIT 8 ARE LESS THAN GEP STACK HEIGHT. UNIT «8 WILL BE CAPABLE OF BURNING UP TO 30X REFUSE-DERIVED FUEL. TWO E
SP'S UILL BE INSTALLED, STACKED ONE ON TOP OF THE OTHER BECAUSE OF SPACE LIMITATION.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 127
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NUMBER IA-0006
SOURCE TYPE CCDE
1.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - MULTIPLE FUELS 90.00 MW
COMPANY NAME/SITE LOCATION CITY OF COLUMBUS COLUK8US, OH
FRANKLIN COUNTY
DETERMINATION IS B/L FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 10/16/79
PERMIT NO. EPA-5-A-80-3 ESTIMATED DATE CF START-UP-
DETERMINATION MADE BY EPA REGION V BONIFACE THAYIL (312J-6S6-6054
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
BOILER, REFUSE/COAL FIRED, 6 EA 240.00 MMBTU/H
PM 0.1000 LB/MMBTU
S02 0.9300 LB/MM3TU 6 BOILERS OPER.
1.4400 LB/MI-!3TU,<4 BOILERS OPER.
NOX 0.5000 LB/IiMBTU
0.7000 LB/M!!3TU COAL ONLY
NOTES
REFUSE MUST COMPRISE AT LEAST SOX OF THE TOTAL HEAT INPUT.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 12S ID NUMBER CH-0045 SOURCE TYPE CODE 1.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - MULTIPLE FUELS 3600.00 MMBTU/H
COMPANY NAME/SITE LOCATION FLORIDA POWER & LIGHT SANFORD, FL 32771
BARWICK ROAD VOLUSIA COUNTY
__ ___ __.__« <____» .» -.-. _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ H .. w « . .__...__ _ _ i« «. ~ _ ~ _ . ..^^ _ -. «.«, ____..
DETERMINATION IS FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 02/20/80
PERMIT NO. FL-047 ESTIMATED DATE OF START-UP 1979
DETERMINATION MADE BY FLORIDA DER ED PALAGYI (904)-<488-1344
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
= = = = = = = = = = r; === = = = = = = = rz = = rs = = = = = r = = rrr = = = ; = : = = = r= = = = r = = = = = = 5 = = = = = r = = = = z = = = = = = r = = = = = = = === = = = 5=rr = = r ====r= = = = = = = ==r====r =====rr= = r =
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ __ __ ____ _-._*_-_ .___ __ »__ ___ ___ __ ___ _ _____ _ __ ______«._-. _ _^_ _ _ ____ ~ ___ _ __».,_.-..__._-..- -.-. -. -. -. -.
COAL PULVERIZERS 96000.00 LB/H
PM 7.7000 LB/H NSPS
11.0900 T/YR
BAGHOUSE 99.96
NOTES
TEST FACILITY - 50/50 COAL/OIL FIRED UNIT.
TESTING COMPLETED, SOURCE NO LONGER EXISTS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 129
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3 01/25/1984
ID NUMBER FL-0014
SOURCE TYPE CCDE
1.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - MULTIPLE FUELS 4457.00 MMBTU/H
COMPANY NAME/SITE LOCATION GULF STATES UTILITY WEST LAKE, LA
CALCASIEU PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 07/24/81
PERMIT NO. (REGION FILE NO.) PSD-LA-305 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214J-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE
1390.00 MMBTU/H
COAL GASIFIER
75.34 T/H COAL
NOX
CO
SOS
PM
NOX
CO
S02
PM
0.2700 LB/MMBTU OIL
0.2700 LB/MM3TU GAS
STEAM INJECTION
0.1300 LB/MMBTU OIL
0.0900 LB/MMBTU GAS
EFFICIENT tCMBUSTION
0.6800 LB/MMBTU OIL
0.0010 LB/MMBTU GAS
LOW SULFUR FUEL (.7X)
0.2100 LB/MMBTU OIL
0.0010 LB/MM9TU GAS
EFFICIENT COMBUSTION (.5X ASH)
0.0300 LB/T
EXISTING INTERNAL CONTROLS
0.6900 LB/T
EXISTING INTERNAL CONTROLS
0.1000 LB/T
EXISTING INTERNAL CONTROLS
0.0300 LB/T
EXISTING INTERNAL CONTROLS
NSPS
60.00
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 130
-------
(CONTINUED) GULF STATES UTILITY
PROCESSES SUBJECT
TO THIS PERMIT
BOILER
COAL GASIFIER
TURBINE
COAL DELIVERY
THROUGHPUT POLLUTANT
CAPACITY EMITTED
1706.00 MMBTU/H
NOX
CO
$02
P»
53.65 T/H COAL
NOX
CO
S02
PM
1361.00 MMBTU/H
NOX
CO
S02
PM
PM
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.1900 LB/HMBTU COAL GAS
0.3000 LB/HK3TU OIL
LOW BTU COAL GAS AS FUEL
0.0080 LB/HK3TU COAL GAS
0.0300 LB/MfiBTU OIL
LOW BTU COAL GAS AS FUEL
0.6200 LB/MfSTU COAL GAS
0.6600 LB/MM3TU OIL
LOW BTU COAL GAS AS FUEL
0.0300 LB/t1"BTU COAL GAS
0.0100 LB/MM3TU OIL
LOW BTU COAL GAS AS FUEL
0.0100 LB/T
RECYCLE PROCESS GAS
0.0100 LB/T
EFFICIENT COMBUSTION
0.1900 LB/T
TAIL GAS FLARE
0.0100 LB/T
HONE
0.2500 LB/MMBTU
STEAM INJECTION
0.0900 LB/MK5TU
EFFICIENT COMBUSTION
0.2100 LB/MMSTU
LOW SULFUR FUEL ( .77.)
0.0010 LB/r,:.3TU
COAL GAS SLOW ASH FUEL (.5X)
0.0800 LB/H
WETTING
... 4 BASIS
... PCT EFF
BACT
56.00
BACT
BACT
BACT
BACT
BACT
BACT
BACT
NSPS
BACT
BACT
BACT
BACT
PAGE G- 131
-------
(CCOTINUEO) GULF STATES UTILITY
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
CRUSHING/SCREENING
PULVERIZING
PM 0.1400 LB/H
BAGHOUSE
PM
0.0800 LB/H
BAGHOUSE
BACT
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 132
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1=33
ID NUMBER LA-0004
SOURCE TYPE CODE
1.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/19S4
SOURCE TYPE/SIZE---
EXTERNAL COMBUSTION - MULTIPLE FUELS
442.00 MMBTU/H
COMPANY NAME/SITE LOCATION HARNEY ELECT.
HINES, OH
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT HO. (REGION FILE NO.) FSO-X81-12
DETERMINATION MADE BY EPA REGION X
(AGENCY)
PAUL BOYS
(AGENCY CONTACT PERSON)
t'ATE OF PERMIT ISSUANCE-- 08/14/81
ESTIMATED DATE OF START-UP--
( FHCN'E )
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
BOILERS, Z
221.00 MMBTU/H EA
S02 0.1800 L8/MMBTU
DRY SCRUBBING
NOX 0.5000 LB/M;:BTU
DRY COMBUSTION CONTROLS
BACT
65.00
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 133
ID NUMBER OR-0001
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/~33
SOURCE TYPE CODE 1.5
-------
APPENDIX - DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - MULTIPLE FUELS 350.00 HP
COMPANY NAME/SITE LOCATION INTERNATIONAL PAPER CO. , TX
DALLAS COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 02/04/84
PERMIT NO. 14163 ESTIMATED DATE OF START-UP-- 1984
DETERMINATION MADE BY TEXAS ACS RANDY HAMILTON I 512>-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS .. . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, PACKAGE 14.60 MMBTU/H
P(1 0.0100 LB/MMBTU BACT
VOC O.OOCO LB/MM3TU BACT
NOX 0.1000 LB/MMBTU BACT
AUTOMATIC QZ CONTROL
S02 0.2200 LB/MJ3TU BACT
0.3X S IN OIL
CO 0.0300 LB/MMBTU BACT
NOTES
EMISSION LIMITS ARE BASED ON OIL FIRING WHICH WAY BE USED AS BACK-UP. NATURAL GAS WILL BE PRIMARY FUEL. GAS FIRIN3 EMISSIONS A
RE - NEGLIGIBLE FCR PM, SOS, VOC, AND CO, BUT 0.09 LB/MI13TU FOR NOX.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 134
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER TX-0144
SOURCE TYPE CODE
1.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - MULTIPLE FUELS 700.00 MM
, __«.._..*. _.
COMPANY NAME/SITE LOCATION POWER AUTHORITY STATE OF NEW YORK STATEN, NY
__ ______. ___.._. _...- _. ______ -... -..- *. _«.- *. .
DETERMINATION IS BACT FOR A NEW SOURCE. OVTE 0F PERMIT ISSUANCE-- 02/22/82
PERMIT NO. ESTIMATED DATE OF START-UP-- 1937
DETERMINATION MADE BY EPA REGION II DENNIS SANTELLA (£12>-264-9623
(AGENCY) (AGENCY CONTACT PERSON) (PHCME)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER
6700.00 MMBTU/H
AUX. BOILER
COAL HANDLING
220.00 MMBTU/H
PM 0.0310 LB/MMBTU COAL
0.0300 LB/MMBTU COAL/ROF
PM 0.0120 LB/MK3TU OIL
VE 20.0000 '/. OPACITY
S02 0.4000 LB/MM3TU
FGD
NOX 0.6000 LB/MKBTU COAL
0.3000 LB/KM3TU OIL
GOOD CO:3'JSTION
CO 0.0410 LB/TOSTU
GCCD COtEUSTION
PM 0.0640 LB/MV3TU
GOOD COrSUSTION
S02 0.3000 '/. S FUEL
NOX 0.3000 LB/IC'.STU
COA»
USE OF PRE-WASHED COAL
BACT
BACT
BACT
92.00
BACT
BACT
SIP
BACT
PAGE G- 135
-------
(CONTINUED) POWER AUTHORITY STATE OF NEW YORK
PROCESSES SUBJECT
TO THIS PERMIT
COAL CRUSHED
THROUGHPUT POLLUTANT
CAPACITY EMITTED
PM
VE
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.0300 GR/DSCF
20.0000 X OPACITY
... t BASIS
... PCT EFF
BACT
COOLINS TOWER
PM 0.0020 X OF H20 FLOW
DRIFT ELIMINATOR
NOTES
CONTACT REGION 2 FOR DESIGN SPECIFICS FOR CONTROL DEVICES.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: CV01/19S3
PAGE G- 136 ID NUMBER NY-0005 SOURCE TYPE CCDE 1.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - MULTIPLE FUELS
COMPANY NAME/SITE LOCATION STONE CONTAINER CORP. HODGE, LA
JACKSON PARISH
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 06/02/83
PERMIT NO. PSD-LA-505 ESTIMATED DATE OF START-UP 198*
DETERMINATION MADE BY LAQD/EPA REGION VI BHARAT CONTRACTOR (5041-342-8940
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, COAL FIRED
1023.00 MMBTU/H
BOILER, COMBINATION, BARK/COAL * 680.40 MMBTU/H
S02 1227.6000 LB/H
1.2000
PM 102.3000
0.1000
NOX 716.1000
0.7000
CO 47.6000
0.0465
VOC 14.3000
BE 0.0006
F 0.8200
S02
SIKGLE-ALKALI FGD
LB/H
LB/NMBTU
ESP
LB/H
LB/MMBTU
BOILER DESIGN
LB/H
LB/HMBTU
BOILER DESIGN
LB/H
BOILER DESIGN
LB/H
EOILER DESIGN
LB/H
816.5000 LB/H
1.2000 LB/KMBTU
LOW S FUEL/STACK MONITOR
B/N
95.00
NSPS
99.00
B/N
BACT
BACT
BACT
BACT
B/N
PAGE G- 137
-------
PM 68.0000 LB/H
0.1000 LB/MMBTU
ESP
NOX 476.3000 LB/H
0.7000 LB/MMBTU
OVERFIRE AIR COMPARTMENT
CO 4Z0.4000 LB/H
0.6180 LB/MMBTU
OVERFIRE AIR COMPARTMENT
VOC 105.9000 LB/H
OVERFIRE AIR COMPARTMENT
BE 0.0003 LB/H
OVERFIRE AIR COMPARTMENT
F 3.7500 LB/H
NSPS
99.00
B/N
BACT
BACT
BACT
BACT
NOTES
BASIA OF F LIMIT ON BOILER IS 100. PPM F IN COAL.
(«) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 133
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER LA-0042
SCURCE TYPE CCDE
1.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - OTHER 161000.00 LB/H
COMPANY NAME/SITE LOCATION CALIFORNIA POWER & LIGHT FIREBAUGH, CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 01/01/6*
PERMIT NO. SJ 83-08 ESTIMATED DATE OF START-UP- 1936
DETERMINATION MADE BY EPA REGION IX MATT HABER (415 )-974-8c09
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS - * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
BOILER, 2 EA
80500.00 LB/H BIOMASS
S02 37.0000 LB/H
40.0000 PPM AT 17. 02
DRY SCRUBBER
LIMIT ON FUEL S CONTENT IS 0.21 7..
NOX 140.0000 LB/H
CONTROL OF OVERFIRE 4 UNDER FIRE AIR
CO 309.0000 LB/H
PROPER COMBUSTION
PM 0.0100 GR/DSCF
BAGHOUSE
89.00
THE TOTAL PLANT HAS A NET ELECTRICAL GENERATING CAPACITY OF APPROX. 50 MM. ALL BACT IS DETERMINED BY TECH./ ECONOMICS. TSP LIM
IT IS DISTRICT LAER. CEM'S REQUIRED FOR NOX, S02, OPACITY. FINAL NOX PPM LIMIT WILL BE SET
AFTER OPERATION COMMENCES.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 139
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/19/19S4
ID NUMBER CA-0062
SOURCE TYPE CODE
1.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/19S4
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - OTHER
COMPANY NAME/SITE LOCATION CONTINENTAL CARBON CO. , TX
MOORE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 11/04/82
PERMIT NO. C-9011 ESTIMATED DATE OF START-UP 19S1
DETERMINATION MADE BY TEXAS ACB JAMES CROCKER (512)-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... i BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
WASTE GAS DRYER 13.60 MMBTU/H
PM 3.2000 LB/H
INCIN. OF CARBON BLACK IN C. BLACK REACTOR
NOX 5.8000 LB/H
S02 69.1000 LB/H
NOTES
100X EFF. IN REDUCING REDUCED SULFUR COMPOUNDS « HYDROCARBONS, A CORRESPONDING INCREASE IN SULFUR DIOXIDE EMISSIONS.
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. K.,,iu,, S:«,^b: o:, ;-,/19S4
PAGE G- 140 ID NUMBER TX-0124 SOURCE TYPE CODE 1.6
-------
APPENDIX -- DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE- EXTERNAL COMBUSTION - OTHER 1500.00 MW
________-._----
COMPANY NAME/SITE LOCATION HOUSTON LIGHTING & POWER FARRAR, TX
LIMESTONE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/10/81
PERMIT NO. (REGION FILE NO.) PSD-TX-371 ESTIMATED DATE OF START-UP 19S5
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (2141-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHOHE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, LIGNITE-FIRED, 2 EA
7863.00 MMBTU/H
LIMESTONE RAILCAR UNLOAD
PM 0.0300 LB/MMBTU
ELECTROSTATIC PRECIPITATOR
S02
FLUE GAS DESULFURIZATION
NOX 0.6000 LB/MMBTU
TAKGENTIAL FIRING, LOW NOX BURNER
CO 0.1100 LB/MMBTU
CONTROLLED COMB. 4 02 MON.
VOC 0.0010 LB/HM3TU
BOILER DESIGN
FB o.oooo LB/TMBTU
FLUE GAS DESULFURIZATION
HG 0.0000 LE/M;:3TU
FLUE GAS DESULFURIZATION
BE 0.0000 LB/MI3TU
FLUE GAS DESULFURIZATICN
H2S* 0.0310 LB/tt;i3TU
MIST ELIMINATOR
PM 1.3300 LB/H
WET SUPPRESSION
NSPS
99.95
82.00
NSPS
BACT
BACT
BACT
93.00
BACT
13.00
BACT
99.40
BACT
BACT
PAGE G- 141
-------
(CONTINUED) HOUSTON LIGHTING & POWER
PROCESSES SUBJECT
TO THIS PERMIT
LIMESTONE RECLAIM & TRANSFER
LIMESTONE LOADOUT
LIMESTONE STORAGE PILE
LIMESTONE RECLAIM TUNNEL
LIMESTONE FEED SILO, 3 EA
FLY ASH SILO
FEED SILO, WASTE BLENDING
PUGMILL, WASTE BLENDING
THROUGHPUT POLLUTANT
CAPACITY EMITTED
PM
PM
PM
PM
PM
PM
PM
PM
EMISSION LIMITS
CONTROL EQUIPMENT OP PROCESS MODIFICATION
0.0500 LB/H
BAGHOUSE
0.0200 LB/H
BAGHOUSE
0.3700 LB/H
TELESCOPIC CHUTE
0.0200 LB/H
BAGHOUSE
0.0100 LB/H
BAGHOUSE
0.1200 LB/H
BAGHOUSE
0.1200 LB/H
BAGHOUSE
0.2100 LB/H
BAGHOUSE
...» BASIS
... PCT EFF
BACT
99.80
BACT
99.80
BACT
BACT
99.80
BACT
99.80
BACT
99.80
BACT
99.80
BACT
99.80
NOTES
PM LIMIT TO BE COMPUTED BY APPLICANT USING GRAPH DERIVED FROM NSPS (CONSIDER CONTROL EFFICIENCY AKD FUEL SULFUR CONTENT). SULF
UP 1C ACID MIST LIMIT APPLIES WHEN FIRING LIGNITE WITH UP TO 1.71 LB/M,'3TU.
OTHERWISE, 0.075 LE/MMBTU WHEN FIRING LIGNITE WITH tiCRE THAN 1.71 LB/MiBTU.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 142
INITIAL REVIEW POST STARTUP
REVIEW STATUS: -04/01/**i933
ID NUMBER TX-OOOS
SOURCE TYPE CCDE
1.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - OTHER 2010.00 T/D
COMPANY NAME/SITE LOCATION METROPOLITAN SERVICE DISTRICT OREGON CITY, OR
DETERMINATION IS B/L FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-
PERMIT NO. 03-2667 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY OREGON DEQ LLOYD KOSTOW (503)-229-5186
(AGENCY) (AGENCY CONTACT PERSON) '(PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILERS, 3
2010.00 T/D
PM 0.0150 GR/DSCF
BAGHOUSE
VOC 0.1200 LB/T
GOOD COMBUSTION
S02 0.5730 LB/T
DRY SCRUBBER
NOX 3.5800 LB/T
HG 0.0025 LB/T
BAGHOUSE
CO 1.4300 LB/T
GOOD COMBUSTION
PB 0.0075 LB/T
BAGHOUSE
F 0.0170 LB/T
DRY SCRUBBER
HCL 0.6690 LB/T
DRY SCRUBBER
TET* 0.0000 LB/T
BAGHOUSE
GOOD COMBUSTION
LAER
99.90
BACT
BACT
80.00
BACT
BACT
BACT
BACT
BACT
70.00
BACT
90.00
BACT
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 143
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID N'UI'BER OR-C003
SOURCE TYPE CODE
1.6
-------
NOTES
THE FINAL PERMIT HAS NOT ISSUED BECAUSE APPLICATION WAS WITHDRAWN FOLLOWING DEFEAT OF THE PROJECT BY VOTE ON INITIATIVE. LIMIT
ARE BASED ON PROPOSED PERMIT.
INITIAL REVIEW POST STARTUP
<») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- l
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE
EXTERNAL COMBUSTION - OTHER
80.00 MW
COMPANY NAME/SITE LOCATION OCCIDENTAL GEOTHERMAL - OXY 81
CA
LAKE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. NSR-4-4-1 NC-81-03
DETERMINATION MADE BY EPA REGION IX
(AGENCY)
MATT HABER
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 05/10/82
ESTIMATED DATE OF START-UP--
(415)-974-8209
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
POWER PLANT
80.00 MM
H2S
8.0000 LB/H
STRETFORD PROC..H202 TREAT., DESIGN
99.00
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 145
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983 04/04/1934
ID NUMBER CA-0034
SOURCE TYPE COOE 1.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- EXTERNAL COMBUSTION - OTHER
COMPANY NAME/SITE LOCATION PACIFIC GAS S ELECTRIC CO., GEYSERS UNI* , CA
SONOMA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 07/27/62
PERMIT NO. (REGION FILE NO.) NSR-4-4-3 SSB-31-03 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION IX MATT HABER (415J-974-82C9
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... « B4SIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
POWER PLANT 2.00 MMLB/H STEAM
H2S 10.4000 LB/H BACT
STRETFORD PROCESS i CATALYST SYS
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 146
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1S33 04/04/1934
ID NUMBER CA-OOC9
SC'JPCE TYPE CODE 1.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - OTHER 1500.00 MW
____ _ __ «.___ .. ______ ______ _ ,- _ .___..__ -. . «.-. » __ »_ __ _ _ ___
COMPANY NAME/SITE LOCATION TEXAS UTILITIES SEN CO. FRANKLIN, TX
TWIN OAKS STATION ROBERTSON COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/22/77
PERMIT NO. PSD-TX-32 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
LIGNITE FIRED STEAM 1500.00 MW
S02 1.2000 LB/MMBTU
FGD 71.90
PM 0.1000 LB/MMBTU
ESP 99.50
NOTES
LIGNITE-FIRED
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 147
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER TX-0003
SOURCE TYPE CODE
1.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - OTHER 1500.00 MW
__^ _. ______ _____ _v . ^- -.
COHPANY NAME/SITE LOCATION TEXAS UTILITIES SERVICE, INC. KOSSE, TX 76653
OAK KNOLL STATION LIMESTON COUNTY
--_- _---_ _ ..-.---_- _- _-- ___-_
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 02/09/78
PERMIT NO. PSD-TX-47 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214 J-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS .. . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
-. «. ».. . -.
LIGNITE FIRED STEAM 1500.00 MW
SOZ 1.2000 LB/MMBTU
FGD 74.00
PM 0.1000 LB/MMBTU
ESP 90.00
NOTES
LIGNITE FIRED
INITIAL REVIEW POST STARTUP
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 148 ID NUMBER TX-0002 SOURCE TYPE CODE 1.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - OTHER 792.00 MKMBTU/H
COMPANY NAME/SITE LOCATION TEXAS UTILITIES SERVICE, INC. HENDERSON, TX
MILL CREEK RUSK COUNTY
_ _ __ _ ,....--. .- -. , -. .
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 01/17/78
PERMIT NO. PSD-TX-44 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOE WINKLER (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
_ __ __ ______ ____ « _ __ . » ~~"*~ ~~~
LIGNITE FIRED STEAM ELECT. 750.00 MM
S02 1.2000 LB/MMBTU
FGD 89.70
PM 0.1000 LB/MMBTU
ESP 99.44
NOTES
EMISSIONS ARE BASED ON 1.06 LB/MMSTU S02, 0.1 LB/MMBTU PART., AND 0.6 LB/HR NOX. LOWER EMISSIONS MAY BE REQUIRED.
LIGNITE FIRED
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. rLsitvi STATUS: 04/01/1933
PAGE G- 149 ID f."J"!:C^ T'-'~: C-'J'^E T>FE CODE 1.6
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/198*
_.._ ""S = = = = = = ~ = = = = = = = :==:::= :: =
SOURCE TYPE/SIZE EXTERNAL COMBUSTION - OTHER 2250.00 T/D
___ ___-_- - - - __-----__-. -- - ____ __ - --.--
COMPANY NAME/SITE LOCATION WESTCHESTER COUNTY RESOURCE RECOVERY PECKSKILL, NY
___ ___..._.__ _..-.
DETERMINATION IS BACT FOR A NEW SOURCE. o
DETERMINATION MADE BY EPA REGION II BARRY TORNICK (212J-264-9579
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
» 3 ~ S Z ~~ Z US ~~ ~ ~ 3 IT ~ IT " ". ». ^^
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
INCINERATORS, REFUSE FIRED, WAT* 750.00 T/D
PM 0.0300 GR/DSCF
ESP
AT 12X CO
CO 0.6200 LB/T REFUSE
DESIGN, HIGH XS AIR, GOOD COMBUSTION
NOX 3.0000 LB/T REFUSE
DESIGN, PROPER OPERATION
S02
PB 0.0300 GR/DSCF
ESP
AT 1£X CO
HG 0.0300 GS/DSCF
ESP
AT 12X CO
BE 0.0300 GR/DSCF
ESP
AT 12X CO
ASB* 0.0300 GR/DSCF
ESP
AT 12X CO
BACT
98.50
BACT
BACT
BACT
BACT
93.50
BACT
93.50
BACT
93.50
BACT
98.50
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 150
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1053
ID NUMBER NY-0008
SOURCE TYPE CODE 1.6
-------
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/"i933
PAGE 6- 151 ID NUMBER NY-OOOS SOURCE TYPE CODE 1.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- REFUSE INCINERATION
COMPANY NAME/SITE LOCATION DUTCHESS COUNTY RESOURCE RECOVERY POUGHKEEPSIE, NY
__ »_«. _____ _.» __ . - .« _ _ »_..«. .... . - « .-^... « -. » - -
DETERHINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 10/14/83
PERMIT NO. 134601 0024 ESTIMATED DATE OF START-UP 1986
DETERMINATION MADE BY NEW YORK DEC JAMES HARRINGTON (518)-457-2018
(AGENCY) (AGENCY CONTACT PERSON)
-------
APPEKDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE REFUSE INCINERATION 1800.00 T/D RDF
,«___ ___ w _ . -. » -. ~ -- ~ -1"1 ~~~~ ~-~"-
COMPANY NAME/SITE LOCATION ENERGY ANSWERS CORP. ROCHESTER, MA
SEMASS PROJECT
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/15/82
PERMIT NO. 025-120MA14 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION I JOHN COURCIER (617J-223-4448
(AGENCY) (AGENCY CONTACT PERSON) (FKONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
_-.- __.._ ______..________,___,._.._____ ___ ____«_»____ __-,___»-.__-.-._ . _ , _ __ ". -- ---. --- -- --
BOILER,MATER-COOLED, 3 EA. 600.00 T/D RDF EA
PM 0.0500 GR/DSCF 12X C02 BACT
ESP.3-STAGE 96.00
S02 0.3400 LB/MMBTU BACT
0.3000 X S BY UT, OIL
LOW S 82 FUEL OIL/LOW S RDF
NOX 0.5000 LB/MMBTU BACT
BOILER DESIGN
NOTES
ALL BACT LIMITS WERE DETERMINED SIMPLY BY TECHNOLOGY AVAILABLE AND THE ECONO NOMIC IMPACTS OF OTHER CONTROLS.
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 153 ID NUMBER MA-0002 SOURCE TYPE CODE 2..1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
r:r = : = = rr = = = rr = = = = r = = = : = = r: = = = = r = = = rr== = = = = = = = rrrrrz=r: = r = : = = = = = r = = = = = = r = = = = = = = = = = = r = r = r = = = = = = = = z = = = = = = = = = : = = = = r = r = = r = = = r: = = r = = rr =
SOURCE TYPE/SIZE REFUSE INCINERATION 2360.00 T/D
______.. _______ «.______ _,,..______..______,._.-___ __ ».«____ «- i ^-«- -- «..«. __ «.
COMPANY NAME/SITE LOCATION HOOKER ENERGY CORP. NIAGARA FALLS, NY
NIAGARA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 07/23/81
PERMIT NO. NONE ESTIMATED DATE OF START-UP 19S2
DETERMINATION MADE BY EPA REGION II BARRY TORNICK (212)-264-9579
(AGENCY) (AGENCY CONTACT PERSON) (PHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
RDF/COAL FIRED BOILERS
2360.00 T/D REFUSE
S02 1.2000 LB/MMBTU COAL
0.8000 LB/MMBTU OIL
CONTRL METHOD: FUEL s CONTENT
HOX 0.7000 LB/MMBTU COAL
0.3000 LB/MriBTU OIL
CONTRL METHOD: TEMP t E.A.
PM 0.1000 LB/MMBTU COAL
0.0700 LB/MMSTU OIL
PM 0.0300 GR/DSCF REFUSE
VE 20.0000 /. OPACITY COAL
20.0000 '/. OPACITY OIL
VE 20.0000 7. OPACITY REFUSE
BACT
BACT
NOTES
COAL USE LIMITED TO 30 DAYS PER YEAR. COMBUSTION FUEL EMISSION LIMITS INTERPOLATED BASED ON FUEL MIXTURE RATIO.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 154
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER NY-0002
SOURCE TYPE CODE
2.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- REFUSE INCINERATION
COMPANY NAME/SITE LOCATION KATY SEGHERS CLEARFIELD, UT
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 02/24/84
PERMIT NO. ESTIMATED DATE OF START-UP-- 1985
DETERMINATION MADE BY UTAH BAQ DAVID KOPTA (801J-533-6108
(AGEKCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . i BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
INCINERATOR & BOILER, WASTE HEAT 500.00 T/D
PM 0.0250 GR/DSCF AT 12X C02
ESP
VE 20.0000 7. OPACITY
ESP
S02 22.4000 LB/H
LIME SCRUBBER/INJECTION
HCL 31.8000 LB/H
LIME SCRUBBER/INJECTION
NOX 29.9000 LB/H
COMBUSTION CONTROL
CO 35.5000 LB/H
COMBUSTION CONTROL
F 1.1000 LB/H
ESP
HG 0.1200 LB/H
PB 0.2200 LB/H
ESP
BACT
98.00
BACT
BACT
50.00
BACT
50.00
BACT
BACT
BACT
BACT
BACT
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 155
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER UT-0032
SOURCE TYPE CODE
2.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE REFUSE INCINERATION 1000.00 T/D
COMPANY NAME/SITE LOCATION MCKAY BAY REFUSE-TO-ENERGY PROJECT TAMPA, FL 33602
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 04/25/82
PERMIT NO. AC 29-47277 ESTIMATED DATE OF START-UP 1984
DETERMINATION MADE BY FLORIDA DER JOHN SVEC (904)-4S8-1344
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
MASS BURN FURNACES 1000.00 T/D WASTE
PM 0.0250 GR/DSCF AT 12X 02 LAER
ESP 99.00
VE
CONTINUOUS OPACITY MONITOR
NOTES
CONTINUOUS OPACITY MONITOR LIMITS TO BE DETERMINED DURING PERFORMANCE TESTING. FACILITY TO INCLUDE WASTE HEAT BOILERS ANDTURBI
NE ELECTRICAL GENERATORS.
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 156 ID NUMBER FL-0030 SOURCE TYPE CODE 2.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE
REFUSE INCINERATION
1000.00 T/D
COMPANY NAME/SITE LOCATION MCKAY BAY REFUSE-TO-ENERGY PROJECT
TAMPA, FL 33602
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. (REGION FILE NO.) PSD FL-086
DETERMINATION MADE BY FLORIDA DER
t AGENCY)
DATE OF PERMIT ISSUANCE 07/02/82
ESTIMATED DATE OF START-UP
JOHN SVEC
(AGENCY CONTACT PERSON)
( PHCfJE )
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
MASS BURN FURNACES
1000.00 T/D WASTE
S02 170.0000 LB/H
LOU SULFUR FUEL
NOX 300.0000 LB/H
COMBUSTION TECHNIQUE
VOC 9.0000 LB/H
COMBUSTION TECHNIQUE
PB 3.1000 LB/H
ESP
f 6.0000 LB/H
NONE
HG 0.6000 LB/H
ESP
BE 5.0000 G/D
ESP
98.00
93.00
NOTES
FACILITY DESIGN ALLOWS FOR FUTURE INSTALLATION OF A SCRUBBER SYSTEM; NSPS APPLIES TO THIS FACILITY. FURNACES-FOUR 250 TPD USIN
G VOLUND TECHNOLOGY, WASTE HEAT BOILERS t TURBINE GENERATORS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 157
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER FL-0030A
SOURCE TYPE CODE 2.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- REFUSE INCINERATION 600.00 T/D
.«... .^. .._ »-__ . ___. ___»_ ..» . _ -,»_,.~ «.___»_,______ ._..__ __ ____» ___.»_._,...__ ___,
COMPANY NAME/SITE LOCATION MUNICIPAL INCINERATOR PULASKI HWY BALTIMORE, MD 21237
PULASKI HIGHWAY BALTIMORE CITY COUNTY
- .. __ .»__ «..__«_ _ ___ _n _ ___ ,«..._ .___ ______., __.... _..__.«____.. »«__..«.__.. __ «. __,
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 01/25/80
PERMIT NO. 76MD-09 ESTIMATED DATE OF START-UP-- 1981
DETERMINATION MADE BY EPA REGION III ED VOLLBERG (215)-597-8990
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
u~~ ~~~~~ ~~ *~~" ~ zr~ -. - - »- >.-« -._« _»__«»«.____«___ -r _. ^_ -, __ .,___ «.___ . _ _ _ «. __«.« «. _-.___ ___«.__
-. .--.__ -, _«- _ _ ___ ________^ ____-.__-.«,_______,_____________ _ _._________________ __ .____»___^_^___~~__~~~
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
MUNICIPAL INCINERATOR
600.00 T/D MSW
PM 0.0300 GR/DSCF
81.6000 T/YR
ESP
S02 35.1000 PFH
154.0000 T/YR
PROPER COMBUSTION TECHNIQUES
CO 30.0000 PFH
127.0000 T/YR
PROPER COMBUSTION TECHNIQUES
VOC 1.3000 PPH
5.5000 T/YR
PROPER COMBUSTION TECHNIQUES
NOX 2.6000 FFH
11.4000 T/YR
PROPER COMBUSTION TECHNIQUES
SIP
93.00
BACT
BACT
BACT
BACT
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 158
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER MO-OC02
SOURCE TYPE CODE
2.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE REFUSE INCINERATION 62.50 T/H WASTE
COMPANY NAME/SITE LOCATION NESWC RESOURCE RECOVERY FACILITY NORTH ANDOVER, MA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 05/27/82
PERMIT NO. 029-121MA16 ESTIMATED DATE OF START-UP-- 1983
DETERMINATION MADE BY EPA REGION I JOHN COURCIER (617)-223-4448
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
STEAM GENERATING UNITS, 2 INCIN*
750.00 T/D EA, WAS*
AUXILIARY BOILER, 1
19.60 MMBTU/H
PM 0.0500 GR/DSCF AT 12X C02
ESP
S02 0.3400 LB/MMBTU
LOU S FUEL - 0.3X S »2 OIL
NOX 0.3200 LB/MMBTU
INCINERATOR DESIGN
CO 0.0700 LB/MMBTU
INCINERATOR DESIGN
SOX 0.0200 LB/r.MBTU
INCINERATOR DESIGN
NOX 0.1550 LB/MMBTU
BOILER DESIGN
co 0.0350 LB/MMBTU
BOILER DESIGN
SOX 0.0200 LB/MM3TU
BOILER DESIGN
PM o.iooo LB/t;;;sTU
S02 0.3400 LB/MM3TU
LOW S FUEL - 0.3/C S 32 OIL
B/S
98.66
BACT
BACT
BACT
98.00
BACT
BACT
BACT
98.00
BACT
B/S
BACT
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 159
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER MA-0004
SOURCE TYPE CODE
2.1
-------
NOTES
LIMITS ARE REDUCTION OVER AP-4Z EMISSIONS
INITIAL PEVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1 <>33
PAGE G- 160 ID NUMBER MA-0004 SOURCE TYPE CCDE
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE -
REFUSE INCINERATION
2010.00 T/D 3 UNITS
COMPANY NAME/SITE LOCATION N.E. MARYLAND WASTE DISPOSAL AUTHORITY
1801 OLD ANNAPOLIS ROAD
BALTIMORE, MD 21230
BALTIMORE CITY COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. 81MD01
DETERMINATION MADE BY EPA REGION III
(AGENCY)
BOB BLASZCZAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 09/10/81
ESTIMATED DATE OF START-UP--
(215)-597-8ie6
(PHONE)
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
WATER WALL, 3 EA INCINERATOR 2010.00 T/D
POLLUTANT
EMITTED
S02
CO
NOX
F
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
335.0000 LB/H
1259.0000 T/YR
109.0000 LB/H
406.0000 T/YR
227.0000 LB/H
999.0000 T/YR
4.2000 LB/H
15.7000 T/YR
... t BASIS
. . . PCT EFF
BACT
BACT
BACT
BACT
NOTES
MARYLAND DEPT. OF HEALTH AND MENTAL HYGIENE PERFORMED LAER ANALYSIS FOR PARTICULATE MATTER. 0.019 GR/OSCF CORRECTED TO \Z7. CO
IS BEING CONSIDERED (ESP).
EMISSION RATES BASED ON REFUSE CHARACTERISTICS. PERMITTEE IS TO PROVIDE PROCEDURES TO ENSURE ACCEPTABLE WASTE BEFORE OPERATION
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 161
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1033
ID
N3-3CC
SO'JRCE TYPE CODE
2.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/32/1984
SOLRCE TYPE/SIZE- REFUSE INCINERATION 100.00 T/D SOLID WASTE
COMPANY NAME/SITE LOCATION REDDY CREEK IMPROVEMENT DIST LAKE BUENA VISTA, FL 32830
P.O. BOX 36 ORANGE COUNTY
.
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 02/11/81
PERMIT NO. PSD-FL-044 ESTIMATED DATE OF START-UP-- 1932
DETERMINATION MADE BY FLORIDA DER ED PALAGYI 1904)-4SS-13
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
r = = = = = rrr = z = = rr = rs = = = = = = = = = = z = r=rr = = rrr = = = = = =: = r = = r = = i:r = = = - = = = r = = r = = = r = = ==r^ = =: = r = r = rr = rr = = = = = = = = = =: = = = = = = = = = = = = = = =: = === = == = = = = = = = = = = =
SOURCE TYPE/SIZE REFUSE INCINERATION 960.00 T/D RDF
_.__ _ .._-... »_ *» . .»., .. -- « «. -.*. .
COMPANY NAME/SITE LOCATION REFUSE FUELS, INC. LAWRENCE, MA
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/23/81
PERMIT NO. 023-121MA12 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY EPA REGION I JOHN COURCIER (617)-223-4448
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FURNACE,WATER WALL, BALANCED DR«
960.00 T/D RDF
PM 0.0250 GR/DSCF
ESP,5-FIELD,IN SERIES
S 1.0000 '/. S OIL
1.2000 LB/MM3TU RDF
LOW S So OIL/LOW S RDF
NOX 0.7000 LB/MN3TU RDF
0.3000 L6/MMBTU OIL
BOILER DESIGN
LAER
93.00
BACT
BACT
NOTES
LAER REQUIRED ON TSP FOR NONATTAINMENT AREA IN LAWENCE. BACT ON S02 DETERMINED BY TECHNOLOGY AND ECONOMICS. BACT ON N02 DETERM
IHED BY MEETING NSPS LIMITS F03 FOSSIL FUEL BOLIERS.
1.2 LB/HJ-13TU EQUIV. TO 1.0 7. S OIL.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 163
INITIAL REVIEW POST STARTUP
REVIEW STATUS'- 04/01/1983
ID NUMBER MA-0001
SOURCE TYPE CODE
2.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
==z=========================="=========" === ======"= =^
SOURCE TYPE/SIZE REFUSE INCINERATION 75.00 T/D 2 EA
____ --. -------- __ __- __-_- - - - -------- _-. __ -.-__-- -
COMPANY NAME/SITE LOCATION RESOURCES AUTHORITY SALLATIN, TN ,..
SUMMER COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE- 08/01/80
PERMIT NO ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY TENNESSEE APCD MERVAT AHMED (6151-741-3651
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS - * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILERS, 2 MUNICIPAL REFUSE BUR* 75.00 T/D EA
PM 0.0400 GR/SCF NSPS
SCRUB, t FABRIC FILTERS 99.00
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 164
ID NUMBER TN-0012
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
SOURCE TYPE CODE 2.1
-------
APPEKDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE REFUSE INCINERATION
»_«.»~ .____«._ _.... _ __ _*..._ __ _ _,._ __«_ _._ __ __ ~__ ^»ww«««««v __ww^__».«._..».__» _.. .... -«. -.
COMPANY NAME/SITE LOCATION STEAM SUPPLY CORP. TULSA, OK
. ; . --
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/16/82
PERMIT NO. T82-90 ESTIMATED DATE OF START-UP 1965
DETERMINATION MADE BY TULSA CITY-COUNTY HEALTH DEPT JIM VAN SANDT (918)-744-1000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
INCINERATORS, SOLID WASTE, 3 EA 230.00 T/D
PM 31.7000 LB/H
3 ESP'S, SEE NOTE 82 98.00
SOS 17.5000 LB/H
NOX 46.0000 LB/H
VOC 3.5000 LB/H
CO 54.6000 LB/H
HG 0.2000 LB/H
NOTES
RATES ARE TOTAL EMISSIONS. DSIC CODES 4931 & 4961 ARE ALSO INVOLVED BECAUSE STEAM t ELECTRICITY WILL BE SOLO TO INDUSTRY.
2) PERFORMANCE STANDARDS OF 10X AVG. OPACITY (PER CLOCK HOUR) 8 0.06 GR/DSCF CORRECTED TO 12X CO HAVE BEEN IMPOSED.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 165
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER OK-0013
SCU-CE TYPE CODE
2.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE REFUSE INCINERATION 624.00 T/D
COMPANY NAME/SITE LOCATION TRANS ENERGY BROOKS, OR
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/19/83
PERMIT NO. 24-5398 ESTIMATED DATE OF START-UP 19S7
DETERMINATION MADE BY OREGON DEQ WENDY SIMS (S03)-229-5259
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PPOCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
INCINERATOR, SOLID WASTE, 2 EA
312.00 T/D
PM 0.0300 GR/DSCF AT \Z'/. C02
61.0000 T/YR
BAGHOUSE, OR ESP
NOX 94.0000 LB/H
290.0000 T/YR
EQUIPMENT DESIGN & OPERATION
HCL 23.0000 LB/'H
69.0000 T/YR
SCRUBBER
S02 73.0000 LB/H
220.0000 T/YR
EQUIPMENT DESIGN 4 OPERATION
VE 10.0000 /. OPACITY SEE NOTE
CO 55.0000 LB/H
170.0000 T/YR
EQUIPMENT DESIGN * OPERATION
HS 0.1700 LB/H
0.5100 T/YR
EQUIPMENT DESIGN « OPERATION
VOC 3.1000 LB/H
9.6000 T/YR
EQUIPMENT DESIGN 8, OPERATION
80.00
PAGE G- 166
-------
PB 0.5200 LB/H
1.6000 T/YR
EQUIPMENT DESIGN * OPERATION
FLU* 1.6000 LB/H
4.8000 T/YR
EQUIPMENT DESIGN * OPERATION
NOTES
NOT TO BE EXCEEDED FOR MORE THAN 3 MINUTES IN ANY ONE HOUR PERIOD.
T'.'TTT1L PTVIEM POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. K..J.:.., b.AlLS: 04/19/1984
PAGE G- 167 ID NlT"Cn> C"-000* SC'J"CE TYPE CODE 2.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- SEWAGE SLUDGE INCINERATION
COMPANY NAME/SITE LOCATION CITY OF L.A., HYPERION, BUREAU OF ENGIN* LOS ANGLES, CA
CITY HALL
_ _ -
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 09/30/62
PERMIT NO. (REGION FILE NO.) NSR-4-4-9 LA-82-02 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION IX RICK SUGAREK <415J-974-3224
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_.. _____ ____..___--_____ _»-. _____ __ .i»_ .. ~ ,__» __ -. .- -. _ . . __.«.___ __ _ _ _ ______ ____ ___ __ _ __ ,.-.
GAS TURBINE, 4, DIGESTER GAS FI* 8.00 MW EA
S02 20.0000 PPM DRY BASIS BACT
WET SCRUBBER 90.00
THERMAL PROCESSING WASTE HEAT R*
S02 20.0000 PFM DRY BASIS BACT
9.2000 LB/H
2 STAGE WET SCRUBBER/VENTU3I SCRUB
COUNTER CURRENT TRAY TOWER
HG 0.2890 LB/H BACT
2 STAGE WET SCRUCBER
BE 0.0000 LB/H BACT
FABRIC FILTER/2 STAGE WET SCRUBBER
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 0PE CCDE 2.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE-
SEWAGE SLUDGE INCINERATION
360.00 T/D SLUDGE
COMPANY NAME/SITE LOCATION COUNTY SANITATION DISTRICTS OF L.A. COU*
CARSON, CA
LOS ANGELES COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. LA 83-02
DETERMINATION MADE BY EPA REGION IX
(AGENCY)
JOE SLAMOVICH
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 02/13/84
ESTIMATED DATE OF START-UP
(4151-974-8235
(FHOS'E)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
COMBUSTOR, FLUIDIZED
68.17 MMBTU/H
S02
0.0600 LB/MM3TU
LIMESTONE INJECTION/SFRAY DRYER
99.00
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 169
INITIAL P^VIEW POST STARTUP
REVIEW STATUS:
ID NUMBER CA-0033A
SOURCE TKPE CODE 2.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
==================================================================================================================================
SOURCE TYPE/SIZE OTHER SOLID WASTE DISPOSAL
_. __.____ ____________» ..-_ _ » -. -._ .. - «- -. __ -» _ ..«* - _____
COMPANY NAME/SITE LOCATION CREMATION SERVICES, INC. CLEVELAND, OH 44113
1612 LEONARD ST.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE--
PEPMIT NO. 13-1217 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY CLEVELAND DAPC IKE HABIB (216 1-664-3503
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PEPMIT CAPACITY EMITTED CONTROL EQUIPMENT 05 PROCESS MODIFICATION ... FCT EFF
INCINERATOR, PATHOLOGICAL WASTE 800.00 LB/H
PM 0.5800 T/YR
VE 0.0000 '/. OPACITY
ODOR NONE
NOTES -
INCINERATOR BURN BODIES & INFECTIOUS WASTE FROM HOSPITALS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PA3E G- 170
ID NUMBER OH-0055
INITIAL REVIEW POST STARTUP
REVIEU STATUS;
SOURCE TYPE CODE 2.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE OTHER SOLID WASTE DISPOSAL
COMPANY NAME/SITE LOCATION DELAWARE SOLID WASTE AUTHORITY WILMINGTON, DE
NEW CASTLE COUNTY
DETERMINATION IS BACT FOR A HEW SOURCE. DATE OF PERMIT ISSUANCE 03/14/80
PERMIT NO. 79DE02 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION III BOB BLASZCZAK (215J-597-8186
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
AIR CLASSIFIER
AIR CLASSIFIER
DUST CONTROL SYS
GLASS RECOVERY
AIR KNIFE
SECONDARY AIR CLASSIFER
DRYER
PM 7.7000 LB/H
BAGHOUSE
PM 7.7000 LB/H
PM 5.2000 LB/H
PM 6.2000 LB/H
PM 3.8000 LB/H
PM 4.1000 LB/H
PM 12.8000 LB/H
BACT
99.90
BACT
BACT
BACT
BACT
BACT
BACT
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 171
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID
DE-0003
SOURCE TYPE CODE
2.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
= = = = = = = = r=rr = = = = = = = = = = = = r = = r = = = = = = = = = = s = = = = = = = = = = r = = r = = = = r = = = sr = = = r = = = r = = = = = = r = = = r = = = = = = = = = = = = r = = = = = r = = = = = rr = = = = = = = = = r = = = = = = r = = = = =
SOURCE TYPE/SIZE OTHER SOLID WASTE DISPOSAL
» - "- . . _ ___.-____.._______.__ __»--___..___..._,. ___....___.. ___«._ _____*»
COMPANY NAME/SITE LOCATION DELAWARE SOLID WASTE II WILMINGTON, DE
NEW CASTLE COUNTY
- - _ -._ _ ___.,__.._-___,____ _»._____ ___ _______..__..________________».___.B,-,
DETERMINATION IS EACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/14/80
PERMIT NO. 79DE02 II ESTIMATED DATE CF START-UP--
DETERMINATION MADE BY EPA REGION III BOB BLASZCZAK (215)-597-81S6
(AGENCY) (AGENCY CONTACT PERSON) (FHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS .. . fc BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
DRYER
DRYER
BOILER
BOILER
HEATER
VENTS, 3
PM
PM
PM
PM
PM
PM
0.4800 LB/H
1.0400 LB/H
0.0100 LB/H
0.0200 LB/H
0.0010 LB/H
1.6000 LB/H
BACT
BACT
BACT
BACT
BACT
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 172
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER DE-0003A
SCITCCE TYPE CODE
2.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
OTHER SOLID WASTE DISPOSAL
2880000.00 GAL
COMPANY NAME/SITE LOCATION LUBBOCK FEEOLOTS, INC.
, TX
LUBBCCK COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. X-4142
DETERMINATION MADE BY TEXAS ACB
(AGENCY)
RALPH BOWLER
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 02/16/83
ESTIMATED DATE OF START-UP-
IS^ )-451-5711
(PHCHE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT E
TO THIS PERMIT CAPACITY EMITTED
LOADING DIGESTERS, 12 EA 240000.00 G4L
ODCR
COLLECTING GAS, 12 EA 240000.00 GAL
ODOR
: = = r = = = = = r = = r = = = = =r = = = = = ::_ = = = = = = = = = = =r =
EMISSION LIMITS ... & BASIS
- CONTROL EQUIPMENT OR PROCESS MODIFICATION . . . PCT EFF
SEE NOTE
EMPTYING DIGESTERS, 12 EA
240000.00 GAL
ODOR
H2S COLLECT. IN FE SPOUNGE & PIPED TO CUSTOMER.
SEE NOTE
NOTES
PROCESSES MANURE FROM A CATTLE FEEDLOT.
NOTE SHOULD BE THE SAME AS EXISTINS FEEDLOT ODORS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 173
ID NUMBER TX-0119
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 05/04/1934
SOURCE TYPE CODE 2.3
-------
^ 1
CO i
rH
N i
CM 1
CM t
X 1
O 1
1
1
1
i
1
1
1
1
,
I
1
1
t
1
g
M
t-
M
_J
UJ
U
in
o
UJ
_J
M
1-
UJ
O
|
1
X
D
Z
UJ
C.
C-
1
1
1
1
1 UJ
1 |-
i in
i <
l 3
i
1 00
1
1 1 t
l O
l O
t ^
1
1 D
l \
1 H
I
1 O
i O
1 '
1 O
1 "fr
1 vJ1
1 M
I
t
1
\
I
1
t
1
1
1
1
t
1
1
1
1
1
I
1
1
1
I
1
I
1
1
1
1
1
1
1
1
1
1 -J
I <
> in
1 O
i a.
i to
1 M
1 O
1
i uj
i t
i (/>
i <
i 3
i
1 O
1 M
I -J
l 0
I CO
1
i a
1 UJ
I ^C.
I h-
I O
l
1
l
l
i
l
i
l
l
l l
l i
l i
1 UJ
H N
11 M
II (O
1 \
II UJ
ii a.
n >-
n \-
n
n UJ
II O
ii D:
II ID
II O
M U)
«(
U
7,
0
H
O
Z
M
5
H
3
*
U
2
*
CO
55
^-
13
a
UJ
UJ
2
o
in
h-
3
2
O
^
U
o
UJ
^
rH
in
x
UJ
i:
2
^_
2
a
j:
o
u
O 1
CO 1
X
K)
0 1
X 1
rH
O 1
1
a.
i 3
i i
UJ t
o n:
2 <
< 1
3 I/)
in
in u.
M 0
H- uj o
M t- t\l
31 «C OJ
a: o co
UJ 1 UJ
a Q -a- z
iu r- o
u. >- o- X
o < _i_ a
uj M in
H 1 rH
O UJ s-
2
O
in
a
UJ
a.
^
u
a: r-
UJ Z
^ o
< o
CO
CO O
O 2
CO UJ
in
«-^
>:
-
3 i o o
o r>- uj 2
in t^ u: uj
U
3 < < <
uj _i a
2 _^ uj
*f *
o
a: 2
o
U. UJ
a M >~
UJ U. CD
i 7: uj
O 0
10 rH <
M 13 3Z
UJ
2 D: 2
O O
rH M
1- - 1-
< O <
222
r i- £
tt rH CC
UJ 3~ UJ
r- Ct r-
UJ uj UJ
o a. o
in u.
1 rH U.
i in uj
CO r-
1 0
i « a.
i
i
i «
i
i
i
1 2
l 0
1 M
1 1-
1 <
1 U
1 t-4
1 U.
1 rH
1 0
1 O
1 H
1
i in
i in
1 UJ
i 8
i n:
i a.
i
1 Ct
l O
1
1 1-
1 2
1 UJ
1 ZZ
1 tL
1 M
1 Z3
i a
1 UJ
i in
i i- -i
1 M O
i r a:
1 M 1
1 -1 2
1 0
1 2 0
1 O
1 M
i in
in
1 rH
1 E
1 UJ
1
1
1
1
i ^-
1 2 0
1 < UJ
! i5t
1 _J rH
i -i r:
1 O UJ
1 O.
1
1
1
1
1
1
1
1 1-
1 O >-
1 D. r-
1 X rH
1 IB U
1 ID <
i o a.
i a: <
1 X O
i i-
i
i
i
i
i
i
n
n
n
n
ii
u
n
n
n
n
n
n
n
n
n
ii t-
II U
II UJ
n -> I'-
ll CO rH
ii 5 r
ii in a:
II UJ
n in a.
II UJ
n in in
II I/I M
1 UJ X
1 U t-
1 O
1 CK O
1 0. r-
o o
D; ce o CK in
UJ UJ UJ
< < o < o
_j J J a*
2
O
M U
1- rH
< H
u in
M Z)
U- <
M U
D '
fU
x: or
UJ
2 CO
O CO
M 3 UJ
k- CK in
in u o
^ in o
T. CO 1. XX
x i; x f- x 13
CO O CO UJ CO <<
_l 0 _J 3 -J CO
o o o
O 0 O
0 0 O
O O 0
fO >^ ^
CO «£>
g S C
2 (n a
0
X
1-
o
C3
«
O
^
rH
*
_J
UJ
23
U_
X
UJ
^
CO
3
*«
^
f~
in
rH
§
2
UJ
12
i:
^
UJ
1-
in
.
3 *
h- CO
£E O-
< in
V- X
in -t
in -.T
O o
ti-
ll CM
II
II O
II U
3
UJ Kt
M CO
> O-
l O
X
II UJ
II to-
ll UJ
II U
i o:
I Z>
I O
I in
VI
3
II O
n i
n <
n U
n
II CK
II UJ
II CO
ii r
II D
ii 2
II
II O
II M
CO
in
n
s.
a.
o
o
UJ
l-
<
<
<
Q
in
UJ
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS TURBINES 26.00 MW
COMPANY NAME/SITE LOCATION CHUGACH ELECTRIC ASSOCIATION, UNIT 84 BERNICE LAKE, AK
_ _______ _ _« .. ___ ________. -. _~-~__ ___ ___» _«_ ___ _ w ___ .»..____- _ _...... _ » -. ___
DETERMINATION IS BACT FOR A MODIFIED SOURCE. CATE OF PERMIT ISSUANCE 08/06/82
PERMIT NO. (REGION FILE NO.) PSD-X82-07 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY EPA REGION X PAUL BOYS (206)-442-1567
(AGENCY) (AGENCY CONTACT PERSON) (PHCHE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GAS TURBINE
26.00 MW
NOX 130.0000 LB/H
569.0000 T/YR
WATER INJECTION
PM 12.0000 LB/H
48.2000 T/YR
LCW S COAL,DISTILLATE OIL BACKUP
NOTES
THE BACT NOX EMISSION LIMIT WAS BASED ON THE NSPS. THE BACT PM EMISSION WAS BASED ON THE USE OF *2 DISTILLATE OIL, HOWEVER, TH
E COMPANY PLANS TO USE NATURAL GAS AS THE PRIMARY FUEL. BECAUSE OF LIMITED BACKUP CAPACITY AT THAT LOCATION,
THE COMPANY REQUESTED A PERMIT BASED ON 100X OIL USE.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 175
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER AK-0005
SOURCE TYPE CODE
3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS TURBINES
COMPANY NAME/SITE LOCATION COLORADO INTERSTATE GAS LAKE STATION, KS
KEARNY COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/19/83
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VII STEVE KOVAC (816)-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. RECIP. ENGINES, GAS-FIRED,* 1475.00 HP EA
NOX 760.0000 PPMV .15X 02, DRY BASIS
OPERATE AT MAX EFFICIENCY
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 176
INITIAL REVIEW POST STARTUP
Ehi SiATL'S: 0^/01/1933
ID NUMBER KS-0013
SOIKCE TYPE CODE 3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/2C/19S4
SOURCE TYPE/SIZE NATURAL GAS TURBINES
COMPANY NAME/SITE LOCATION CROWN ZELLERBACH, INC. ANTIOCH, CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/01/83
PERMIT NO. 28179 ESTIMATED DATE OF START-UP 1933
DETERMINATION MADE BY BAY AREA AQMD DOUG WOLF (415)-771-6000
(AGEMCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . .. PCT EFF
GAS TURBINE 32.00 MW
NOX 42.0000 PPM N02 AT 157. 02
WATER/STEAM INJECTION
DUCT BURNER 145.00 MMBTU/H
NOX 88.0000 PPM N02 AT 3X 02
LO-NOX DESIGN
NOTES
BURNING NATURAL GAS
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 177 ID NUMBER CA-0044 SCUSCE TYPE CODE 3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE NATURAL GAS TURBINES
COMPANY NAME/SITE LOCATION DOW CHEMICAL, USA PLAQUEMINE, LA
IBERVILLE PARISH
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 11/14/83
PERMIT NO. PSD-LA-393.M-1 ESTIMATED DATE OF START-UP--
DETERfUNATION MADE BY LAQD/EPA REGION VI BHARAT CONTRACTOR (504 J-342-8940
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_^__________^_ ^^__^_____ _ ____ _^~ _ _____ -- _-- -. --- - --*-- - ~ -*-
TURBINE, 8GT-300 * GT-400, Z EA 100.00 MW
NOX 1194.0000 LB/H N/A
COMB. CONTRL
CO 66.0000 LB/H
VE 0.0000 /. OPACITY
NOTES
THE ORIGINAL PERMIT PSD-LA-393 WAS ISSUED ON 08/11/81. SUBSEQUENT REVISION TO NSPS BY EPA ON 01/27/82 , 40CFR60, SUBPART GG, E
XEMPTEO THESE TURBINES FROM STEAM INJECTION CONTROLS.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 178
INITIAL P^VIEW POST STARTUP
REVIEW STATUS:
ID NUMBER LA-0011A
SOURCE TYPE CODE
3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS TURBINES 300.00 MM
COMPANY NAME/SITE LOCATION GETTY OIL, KERN RIVER COGENERATION PROJ* , CA
KERN COUNTY
____ _-_ ^,»_____ __«._____. *.____ _____ __ . . ^ ~
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 11/03/83
PERMIT NO. SJ 83-03 ESTIMATED DATE OF START-UP 1934
DETERMINATION MADE BY EPA REGION IX MATT HABER (415J-974-S209
(AGENCY) (AGENCY CONTACT PERSON) (PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE, GAS FIRED, 4 EA 825.00 MMBTU/H
CO 9.0000 PPM
17.0000 LB/H
PROPER COMBUSTION
NOTES
1.) EACH TURBINE IS LIMITED TO NOX EMISSION OF 42 PPM & 140 LB/H BY A LOCAL NSR PERMIT. 2.) THE SOURCE HAS APPLIED FOR A MAJOR
MODIFICATION TO INCREASE THE CO LIMIT WHEN FIRING ON DISTILLATE FUEL, THE STAND-BY FUEL.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 179
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/19/1934
ID NUMBER CA-0063
SOURCE TYPE CODE 3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE - NATURAL GAS TUPBINES
COMPANY NAME/SITE LOCATION KISSIMMEE UTILITIES KISSIMMEE, FL
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/30/84
PERMIT NO. AC 49-74656 ESTIMATED DATE OF START-UP 1934
DETERMINATION MADE BY FLORIDA DER TERESA HERON <904)-463-1344
(AGENCY) (AGENCY CONTACT PERSON) (PHC»E)
PROCESSES SUBJECT THROL'SHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE, GAS 400.00 MHBTU/H
NOX 79.0000 PPM GAS FIRED
129.0000 PPM OIL FIRED
WATER INJECTION 40.00
so2 o.sooo LB/M:;STU
FUEL S CONTENT
VE 20.0000 /. OPACITY MAX
BOILER, WASTE HEAT 41.70 HMBTU/H
S02 0.5000 LB/MMBTU
FUEL S CONTENT
NOTES
NSPS SUSPART GG APPLICABLE. TURBINE EXHAUST GASES DISCHARGE INTO A WASTE HEAT BOILER. TOTAL ELECTRIC POWER GENERATED BY THE SY
STEM IS 50 GROSS MEGAWATTS.
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. _ _ REVIEW STATUS:
PAGE G- 160 ID NUMBER FL-0029A SOURCE TYPE CODE 3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS TURBINES 73.50 MW
COMPANY NAME/SITE LOCATION NEVADA PWR CO., CLARK STATION UNIT »7 EAST LAS VEGAS, NV
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/01/79
PERMIT NO. (REGION FILE NO.) NV 78-02 ESTIMATED DATE OF START-UP 1980
DETERMINATION MADE BY EPA REGION IX JIM HANSON (415)-974-8038
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...& BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GEN., GAS TURBINE 73.50 MW
NOX 0.3<+00 LB/MMBTU
WATER INJECTION
PM 0.0300 LB/MflBTU
CO 0.1200 LB/Mt-fBTU
S02
0.25X S FUEL CONTENT
NOTES
REGENERATOR IS SUBJECT TO NSPS.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983 02/13/19S4
PAGE G- 181 ID NUMBER NV-0003 SOURCE TYPE CODE 3.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE-
NATURAL GAS TURBINES
73.50 MW
COMPANY NAME/SITE LOCATION NEVADA PWR CO., CLARK STATION UNIT #8
EAST LAS VEGAS, NV
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT HO. (REGION FILE NO.) NV 60-01
DETERMINATION MADE BY EPA REGION IX
(AGENCY)
LARRY BOWERMAN
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 09/11/80
ESTIMATED DATE OF START-UP 1982
(
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS TURBINES
COMPANY NAME/SITE LOCATION NORTHERN NATURAL GAS CUNNINGHAM, KS
DETERMINATION IS BACT FOR A MODIFIED SOURCE. OATE OF PERMIT ISSUANCE 03/12/82
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VII STEVE KOVAC (816 )-37<+-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. RECIP. ENGINES, DUAL FUEL,* 2250.00 HP EA
NOX 60.0000 LB/H
CO 15.0000 LB/H
VOC 3.9000 LB/H
NOTES
IN CONSIDERATION OF TEST RESULTS, THE CO EMISSION LIMIT WAS CHANGED FROM 9 TO 15 LB/H ON NOV. 29, 1982.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 183 ID NUMBER KS-0015 SOURCE TYPE CODE 3.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- NATURAL GAS TURBINES
COMPANY NAME/SITE LOCATION PANHANDLE EAST. PIPELINE CO. ELKHART STATION, KS
MORTON COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 11/18/81
PERMIT NO. ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VII STEVE KOVAC (816 )-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_..___ __..___ . .... _ _______» _______ -,________,.^..-____..__. __ ___ _.- ___ -. __ ~ __.. -.»__ . _ ___ -._-. «.
I.C. RECIP. ENGINES, GAS FIRED,* 3200.00 HP EA
NOX 600.0000 PPMV 15X 02, DRY BASIS
PRE-IGNITION CHAMBER
NOTES
(#) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- l£
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- NATURAL GAS TURBINES
COMPANY NAME/SITE LOCATION PETRO-TEX CHEMICAL CORP. . TX
HARRIS COUNTY
_ ....-. ., .» «, __.._ _ .. », _.. .... .» -. "- -.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/21/82
PERMIT NO. SEE NOTE ESTIMATED DATE OF START-UP-- 1983
DETERMINATION MADE BY TEXAS ACB JIMMY RANDALL (512(-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE, GAS 982.30 MSCFH
NOX 237.9000 LB/H NSPS
H20 INJECTION
S02 0.7000 LB/H
CO 15.2500 LB/H TECH
NOTES
NOTE PERMIT NUMBER 9199, 9200. EACH PERMIT COVERS ONE TURBINE.
TMTJTSL PCVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. -'L..L,J S.ATUS: 05/04/1934
PAGE G- 185 ID NJI.jLK i,-.--^..' o_ ~t lire CODE 3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198A
SOURCE TYPE/SIZE- NATURAL GAS TUPBINES 217.00 MMBTU/H
COMPANY NAME/SITE LOCATION PROCTOR & GAMBLE SACRAMENTO, CA
DETERMINATION IS DATE OF PERMIT ISSUANCE 05/10/83
PERMIT NO. SAC 83-01 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION IX
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
FPOCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE. GAS
217.00 MKBTU/H
BURNER, DUCT
S02 0.3000 X S BY WT
NOX 75.0000 PPM AT 15X 02, OIL
62.0000 PPM AT 15X 02, GAS
H20 INJECTION
CO 32.0000 LB/H GAS FIRED
22.0000 LB/H OIL FIRED
NOX 0:1500 LB/MMBTU
LOW NOX BURNERS
CO 0.5000 LB/H
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 186
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER CA-0067
SOURCE TYPE CODE
3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
NATURAL GAS TURBINES
303.00 NHP
COMPANY NAME/SITE LOCATION PRUDHOE BAY CONSORTIUM
PRUDHOE BAY, AK
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSO-X81-01
DETERMINATION HADE BY EPA REGION X
(AGENCY)
CATE OF PERMIT ISSUANCE 09/29/81
ESTIMATED DATE OF START-UP--
DAVID TETTA
(AGENCY CONTACT PERSON)
( PHONE )
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
4 BASIS
PCT EFF
TURBINES
HEATERS
303.00 MHP
250.00 MMBTU/H
NOX 150.0000 PPM
DRY CONTROLS
CO 1.0900 LB/MMSCF FUEL
PROPER COMBUSTION
NOX 0.0800 LB/MMBTU
LOW NOX BURNERS
CO 0.0100 LB/MMBTU
PROPER COMBUSTION
BACT
BACT
BACT
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 187
INITIAL VVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NUMBER AK-0004
SOURCE TYPE CCDE
3.1
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS TURBINES 200.00 MM
COMPANY NAME/SITE LOCATION PUGET SOUND POWER fc LIGHT FREDONIA, HA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/23/82
PERMIT NO. PSD-X-82-09 ESTIMATED DATE OF START-UP 1984
DETERMINATION MADE BY EPA REGION X PAUL BOYS (206J-442-1567
(AGENCY) (AGENCY CONTACT PERSON) (PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
GAS TURBINE, 2
100.00 MW EA
NOX 480.0000 LB/H
2061.OCOO T/YR
WATER INJECTION
CO 185.0000 LB/H
645.0000 T/YR
S02 640.0000 LB/H
154.0000 T/YR
PM 2.9000 LB/H
12.5000 T/YR
NOTES
THE NSPS LIMIT FOR NOX WAS THE BASIS FOR BACT. THE S02 BACT LIMIT WAS BASED ON THE USE OF 0.5X S OIL.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE 6- 1S8
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER WA-0007
SOURCE TYPE CODE
3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
= = = : = = = = = = = r = = = = = = = = r = = = = = = = = = = = = = = = = = = = = = r = = = = = = = = = = = = r = = = = = = = = = = = ===r = = = r = = = = == = = = = = = = = = = = = = = = r = = = = = = r = = = = = = ==r = = = = r = = = = = r = = :r = =
SOURCE TYPE/SIZE--- NATURAL GAS TURBINES 1290.00 MW TOTAL
COMPANY NAME/SITE LOCATION SOUTHERN CALIF. EDISON CO. , CA
UPPER JOHNSON VALLEY SAN BERNARDINO COUNTY
DETERMINATION IS BACT DATE OF PERMIT ISSUANCE 04/25/63
PERMIT NO. SE 81-01 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION IX MATT HABER (415 )-974-8209
CAGENCY) (AGENCY CONTACT PERSON) (PHOHE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS .. . t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
GAS TURBINE, 20
64.50 MW EA
S02 0.0960 LB/MMBTU
71.4500 LB/H/TUEBINE
USE OF VERY LOW SULFUR (0.1X) OIL
NOX 44.5000 FFM
140.0000 LB/H/TURBINE
WATER INJECTION
CO 17.0000 LB/H/TURBINE
PROPER COflBUSTION
PB 1.8000 FFM FUEL CONTENT
H2S* 0.1000 SULFUR FUEL OIL
ASB* 2.8500 LB/H/TURBINE
CCMPL. H/TSP LIM. 10 LB/H.& SEMI-ANN. FUEL SAM*
HG 2.8500 LB/H/TUK5INE
COMPL. W/TSP LIM. 10 LB/H.4 SEMI-ANN. FUEL SAM*
NOTES
1) CONTINOUS MONITORS ARE REQUIRED FOR NOX, S02, AND CO. 2) TURBINE CURRENTLY PLANNED FOR IS THE GE FRAME 7. 3) OPERTION IS LI
MITED TO 1500 HR/YR PER TURBINE. ALSO UNDER SOURCE CODES 3.2 & 3.3
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 189
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/19/1934
ID NUMBER CA-0047
SOURCE TYPE CODE
3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- NATURAL GAS TURBINES 3200.00 HP
COMPANY NAME/SITE LOCATION SW GAS STORAGE CO., PANHANDLE EAST. PIP* , KS
BROCHERS STATION MEADE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 12/11/80
PERMIT NO. ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VII STEVE KOVAC (S16)-374-6525
(AGENCY) (AGENCY CONTACT PERSON) ( PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINES, NAT. GAS FIRED, 5 1C R* 3200.00 HP EA
NOX 850.0000 PPM 15X 02 tD) BACT
NOTES
BGRCHERS UNDERGROUND STORAGE FACILITY. (2-CYCLE, TURBO CHARGED ENGINES WITH STANDARD COMBUSTION CHAMBERS, DESIGNED TO OPERATE
AT RELATIVELY LOW SPEED)
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 190
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER KS-0005
SOURCE TYPE CODE
3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/193^
SOURCE TYPE/SIZE
NATURAL GAS TURBINES
18500.00 HP
COMPANY NAME/SITE LOCATION TEXAS EASTERN TRANSMISSION CO.
DELMONT, PA
WESTMORELAfJD COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT HO. 82PA02
DETERMINATION MADE BY EPA REGION III
(AGENCY)
VERNON BUTLER
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 07/07/83
ESTIMATED DATE OF START-UP-- 1982
(215)-597-2711
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS ... & BASIS
CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GAS TURBINE
18500.00 HP
NOX
150.0000 PPM
NATURAL GAS
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 191
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER PA-0027
SOLACE TYPE CCDE 3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1981*
SOURCE TYPE/SIZE
NATURAL GAS TURBINES
88.00 MW
COMPANY NAME/SITE LOCATION TOSCO CORP.
MARTINEZ, CA
CONTRA COSTA COUNTY
DETERMINATION IS
PERMIT NO. 5193
DETERMINATION MADE BY
EPA REGION IX
(AGENCY)
MATT HABER
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 13/13/83
ESTIMATED DATE OF START-UP 1984
(415)-974-8209
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... t BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE, GAS, Z EA
500.00 MMBTU/H
NOX 45.0000 PPM AT 15X 02
75.0000 LB/H
STEAM INJECTION
NOTES
TURBINES ARE GE FRAME 6 TURBINES. CEM REQUIRED FOR NOX. PRIMARY FUEL IS REFINERY FUEL GAS, SECONDARY FUEL IS PIPELINE GAS.
2.) ALSO SOURCE TYPE 5.6
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 192
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/19/1934
ID NUMBER CA-0046B
SCUSCE TYPE CODE 3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS TURBINES 8563.00 KM
COMPANY NAME/SITE LOCATION UNIVERSITY CO-GENERATION LTD-, 1983-1 BELLRIDGE OIL FIELD, CA
DETERMINATION IS FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/21/84
PERMIT NO. 4133001 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY KERN COUNTY APCD TOM PAXSON (805)-861-3682
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE, GAS & BOILER, WASTE HE* 8563.00 KM
NOX 714.0000 LB/D
H20 INJ., 0.9/1.0 W/F 65.00
NOTES
EMISSION LIMITS MAY BE FIXED AT LOWER LEVEL UPON EMISSIONS TESTING - UNIT WILL OPERATE 24 H/D, 7 D/WEEK, 52 WEEK/YR.
INITIAL REVIEW POST STARTUP
(#) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 193 ID NUMBER CA-0064 SOURCE TYPE CODE 3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS TURBINES 39.10 KW
COMPANY NAME/SITE LOCATION VULCAN MATERIALS CO. WICHITA, KS
SEDGWICK COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 07/23/81
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VII STEVE KOVAC (816J-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE, SIMPLE-CYCLE, NAT. GAS 39.10 MW
NOX SEE NOTE BACT
STEAM INJECTION
NOTES
THE UNIT IS SUBJECT TO NSPS, SUBPART GG.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 194
ID NUMBER KS-0009
INITIAL PFVTFW POST STARTUP
_ V _ C r « w1 1 ~-\ o »J O'r/Cl/l?^^
SOURCE TYPE CODE 3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS TURBINES
COMPANY NAME/SITE LOCATION WARREN RED. CO. , CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 10/19/83
PERMIT NO. 2023008 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY KERN COUNTY APCD IVAN NEO (805)-861-3682
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. ENGINE, NATURAL GAS, 3 EA 2133.00 HP
NOX 69.0600 LB/D
CATALYTIC CONVERTOR 86.00
NOTES
STATE FILE 8 A330-020
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 195
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER CA-0068
SOLACE TYPE CODE
3.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS COMPRESSORS 4000.00 BRAKE HP
______ __ ____--____._____.-____.- ___ ,-_- __ ._ _____________ -.__ _.._ _ _ __.... _ .._« _w
COMPANY NAME/SITE LOCATION ALGONQUIN GAS TRANSMISSION CO. CROKWELL, CT
_______ ____.-«.____ ____-__ __.__.. _ ___ ___.._______ ____.^__..__ .-_ _ .. ..-. ~,^~
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE Of PERMIT ISSUANCE 03/05/82
PERMIT NO. 026-042CT01 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY EPA REGION I JOHN COURCIER (617)-223-4448
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
EN3INE,TURBINE COMPRESSION 40.00 BHP
NOX 0.0135 /. BY VOL BACT
MANUFACTURER'S GUARANTEE
NOTES
NSPS USED AS GUIDE, BUT MODIFICATION WAS NOT SUBJECT TO NSPS. BACT BASED ON MANUFACTURER'S GUARANTEE. LIMIT MEASURED AT \S7. 02
DRY BASIS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
INITIAL VVIEW POST STARTUP
REVIEW STATUS: 04/01/1<=33
PAGE G- 196
ID NUMBER CT-0001
SCU^CE TYPE CODE 3.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/82/198*
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION ANR STORAGE CO. EXCELSIOR TUP, MI 49000
KALKASKA COUNTY
_ . _ «. -. _ _ ______,.__..___..___-.___ ____.- _ ______ _______
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 04/01/80
PERMIT NO. 67-80 ESTIMATED DATE OF START-UP 1931
DETERMINATION MADE BY MICHIGAN DNT? DAVID FERRIER (517)-32£-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COMPRESSOR, NAT. GAS, Z EA 3750.00 HP
NOX 12.0000 G/HP-H
RETARDED IGNITION
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 197
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3 03/13/1934
ID NUMBER MI-0015
SOURCE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1934
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS 20.00 MHP
__ _ __ , _ __._.. _ _ __ __
COMPANY NAME/SITE LOCATION CO INTERSTATE GAS, CHEYENNE NEAR ROCKPORT, CO
WELD COUNTY
___ _ _ __.._______-..-__._ _ ___-. ___ _..__ _
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/12/80
PERMIT NO. ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VIII JOHN DALE (303J-837-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHCUE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
2 ENGINES 5130.00 HP
NOX 39.2400 LB/H BACT
DESIGN
2 REC ENGINES 5130.00 HP
CO BACT
NOX 68.0000 LB/H BACT
DESIGN
2 REC ENGINES 12000.00 HP
CO BACT
NOX 158.6000 LB/H BACT
DESIGN
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 198 ID NUMBER CO-0001 SCU9CE TYPE CCQE 3.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- NATURAL GAS COMPRESSORS 20.00 MHP
COMPANY NAME/SITE LOCATION CO INTERSTATE GAS, DEERTRAIL , CO
ELBERT COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 10/24/80
PERMIT NO. ESTIMATED DATE OF START-UP--
DETERMIHATION MADE BY EPA REGION VIII JOHN DALE (303J-837-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINE
2 ENGINES
GEN. ENGINE
HEATER
6000.00 HP
16000.00 HP
425.00 HP
6.00 MMBTU/H
CO
NOX
CO
NOX
CO
NOX
CO
NOX
79.3000 LB/H
DESIGN
211.4000 LB/H
DESIGN
10.2000 LB/H
DESIGN
0.7600 LB/H
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 199
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER CO-0002
SOURCE TYPE CCDE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- NATURAL GAS COMPRESSORS 66.00 MHP
COMPANY NAME/SITE LOCATION CO INTERSTATE GAS, FLANK NEAR LA JUNTA, CO
BACA COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/24/80
PERMIT NO. ESTIMATED DATE OF START-UP--
DETERMIHATION MADE BY EPA REGION VIII JOHN DALE (303J-837-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_____»^__ _____________»_____ __ _____ ____ ~
H3 GLYCO REBOIL 8.00 MMBTU/H
NOX 8610.0000 SCFH BACT
6 REC NG ENGS 13320.00 HP
NOX 83.1000 LB/H BACT
DESIGN
NOTES
INITIAL REVIEW POST STARTUP
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 200 ID NUMSER CO-0003 SC'J-CE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS 44.00 MHP
COMPANY NAME/SITE LOCATION CO INTERSTATE GAS, KIT CARSON NEAR EADS, CO
CHEYENNE COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 09/12/80
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VIII JOHN DALE (3031-837-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ _ _ _ __ _ ___._ _ -. __ -, .___.-..._,..__-.
ENGINE, OPR 370.00 HP
NOX 8.9000 LB/H BACT
DESIGN
CO BACT
3 ENGINES 16000.00 HP
CO BACT
NOX 211.4000 LB/H BACT
DESIGN
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 201 ID NUMBER CO-OC04 SC'JSCE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
NATURAL GAS COMPRESSORS
34.00 MHP
COMPANY NAME/SITE LOCATION CO INTERSTATE GAS, TOTEM/LONG
, CO
ELBERT COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO.
DETERMINATION MADE BY EPA REGION VIII
(AGENCY)
JOHN DALE
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 09/12/80
ESTIMATED DATE OF START-UP--
(303>-837-3763
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
4 ENGINES
6 ENGINES
GENERATOR
2 HEATERS
THROUGHPUT
CAPACITY
1340.00 HP
2130.00 HP
370.00 HP
16.00 MMBTU/H
POLLUTANT
EMITTED
CO
NOX
CO
CO
NOX
CO
NOX
= = - = = = = = = = = rr = = rr = rr = = rrrr = rzr = = r = = r:rrr = = i:rrrrrrr = r =
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
53.1600 LB/H
DESIGN
8.9000 LB/H
2.5200 LB/H
... k BASIS
... PCT EFF
BACT
BACT
BACT
BACT
BACT
BACT
BACT
6 ENGINES
8550.00 HP
NOX 216.6000 LB/H
DESIGN
BACT
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 202
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/oi/i?e3
ID NUMBER CO-0005
SC'J~CE TYPE CODE
3.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
NATURAL SAS COMPRESSORS
60.00 MHP
COMPANY NAME/SITE LOCATION CO INTERSTATE GAS, WATKINS
NEAR WATKINS, CO
ADAMS COUNTY
DETEPMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MADE BY EPA REGION VIII
(AGENCY)
JOHN DALE
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 09/12/80
ESTIMATED DATE OF START-UP--
(333)-837-3763
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
ENGINE
4 ENGINES
5 ENGINES
THROUGHPUT POLLUTANT
CAPACITY EMITTED
1350.00 HP
CO
voc
NOX
10800.00 HP
CO
voc
NOX
30000.00 HP
CO
vcc
NOX
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
17.8400 LB/H
DESIGN
142.7200 LB/H
DESIGN
396.5000 LB/H
. . . fc BASIS
.. . PCT EFF
BACT
BACT
BACT
BACT
BACT
BACT
BACT
B4CT
EACT
DESIGN
NOTES
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 203
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 0^/01/1953
ID NUMBER CO-0006
SOURCE TYPE CCDE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198"+
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS 1600.00 HP 2 EA
COMPANY NAME/SITE LOCATION CONSOLIDATED GAS SUPPLY CORP. . WV
HASTINGS COMPRESSOR STATION WETZEL COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 09/14/81
PERMIT NO. S1WV01 ESTIMATED DATE OF START-UP-- 1932
DETERMINATION MADE BY EPA REGION III BOB BLASZCZAK (215)-597-3186
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...& BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. ENGINE 1600.00 HP
NOX 7.3300 G/SEC BACT
NCNE
NOTES
RELOCATION OF TWO 1600 HP. COOPER BESSEMER I.C. ENGINES. THIS RELOCATION MASA MAJOR MODIFICATION TO THE COMPRESSOR STATION REC
EIVINS THE ENGINES. THE ENGINES WERE 16 YEARS OLD AND NATURAL GAS-FIRED. OPERATION LIMITED TO 5600 HRS./YR.
CONSOLIDATED G4S SUPPLY CO. REQUESTED A MOD. OF PSD PERMIT FROM USEPA REGION 3 ON 01/11/83. HOD. OF PERMIT KOULD INVOLVE ALTER
NATE METHOD OF 0DER. OF COMPRESSOR ENGINES X AN INCREASE IN EMISSION'S OF NOX.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 20<+
INITIAL REVIEW POST STARTUP
REVIEW STATUS-' 04/01/1983
ID NUMBER WV-0001
SCU"CE TYPE CCDE
3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION EL PASO NATURAL GAS CO., WASHINGTON RAN* WHITES CITY, NM
DETERMINATION IS BACT FOR A NEW SOURCE. PATE OF PERMIT ISSUANCE-- 05/14/82
PERMIT NO. NM-428 ESTIMATED DATE OF START-UP 1932
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA (505>-934-0020
(AGENCY) (AGENCY CONTACT PERSON) ( FHQ!,'E )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
ENGINE, I.C. COMPRESSOR 4500.00 HP
NOX 2.4500 G/HP-H
COOPER ENERGY SERVICES
ENGINE, I.C. COMPRESSOR 4500.00 HP
NOX 2.4500 G/HP-H
COOPER ENERGY SERVICES
NOTES
STACK TEST PERFORMED ON THESE TWO ENGINES BUT NO REPORT RECIEVED YET.
INITIAL WVIEM POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 205 ID NUMBER NM-OOC6 SOURCE TYPE CC3E 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOUPCE TYPE/SIZE--- NATURAL GAS COMPRESSORS
_____-__..__ _ ____ _ _ __ _-___..«. ____.-_..___ __-.____ -,____ . _ .._ _ ____ .._-__ _,- ___________
COMPANY NAME/SITE LOCATION ENSERCH EXPLORATION CO. , TX
EASTLAND COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 12/28/82
PERMIT NO. X-4051 ESTIMATED DATE OF START-UP-- 1933
DETERMINATION MADE BY TEXAS ACB RANDY HAMILTON (512J-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
WHITE SUPERIOR 8G825 780.00 HP
NOX 7.7000 T/YR
CATALYTIC CONVERTER 90.00
CO 5.5000 T/YR
VOC 0.7000 T/YR
NOTES
EMISSION LIMITS ARE 1.0 G/HP-H NOX, 0.75 6/HP-H" CO, 0.1 G/HP-H VOC.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: C5/04/19S4
PAGE G- 206 ID NUMBER TX-0133 SOURCE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE -
NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION GETTY OIL CO.
SKELLYTOWN, TX
CARSON COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. X3378
DETERMINATION MADE BY TEXAS ACB
(AGENCY)
RANDY HAMILTON
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/18/82
ESTIMATED DATE OF START-UP 1983
( FKCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
SUPERIOR 126TA 'CLEAN BURN1 ENG* 2000.00 HP
NOX 77.2000 T/YR
COMBUSTION CHAMBER MOD.
CO 115.8000 T/YR
VOC 8.^.000 T/YR
NOTES
2.0 G/HP-H NOX, 3.0 G/HP-H CO, 0.2 G/HP-H VOC
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 207 ID NUMBER TX-0101 SCURCE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS 200.00 MHSCFD
__ _ __ .._,_ _
COMPANY NAME/SITE LOCATION LIQUID ENERGY CORP. . TX
WISE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 11/10/63
PERMIT NO. 9153 ESTIMATED DATE OF START-UP-- 1933
DETERMINATION MADE BY TEXAS ACB KAREN HORNE (512J-451-57I1
(AGENCY) (AGENCY CONTACT PERSON) ( FHOS'E )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE ENGINE COMPRESSOR, 2 EA 3200.00 HP
NOX 1.7500 G/HP-H
MEP-8 RECIPROCATING ENGINE COMP* 2000.00 HP
NOX 4.0000 G/HP-H
TURBOCHARGERS
NOTES
THE EFFECTIVENESS OF TURBOCHARGERS HAS NOT BEEN PROVEN BY PERFORMANCE TESTING YET.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 05/04/19S4
PAGE G- 203 ID NUMBER TX-0128 SOURCE TYPE CCDE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE---
NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION LLANO, INC.
NEAR HCBBS, KM
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. NM-477
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA
rAGENCY) fAGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 06/22/82
ESTIMATED DATE OF START-UP-- 1982
(505)-984-OOcO
CPHCJiE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
.. . & BASIS
... PCT EFF
ENGINE, I.C. COMPRESSOR
ENGINE, I.C. COMPRESSOR
ENGINE, I.C. COMPRESSOR
ENGINE, I.C. COMPRESSOR
ENGINE, I.C. COMPRESSOR
1100.00 HP
1100.00 HP
1100.00 HP
1100.00 HP
1100.00 HP
NOX 2.2000 G/HP-H
NEW DESIGN
NOX 2.2000 G/HP-H
NEW DESIGN
NOX 8.2000 G/HP-H
NEW DESIGN
NOX 2.2000 G/HP-H
NEW DESIGN
NOX 2.2000 G/HP-H
NEW DESIGN
NOTES
STACK TESTS, EPA REF. METHOD 7, WERE PERFORMED ON TWO OF THE ABOVE MENTIONED FIVE ENGINES & THE ACTUAL EMISSIONS WERE 0.38 G/H
P-H t 1.34 G/HP-H.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 209
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID MU.k!3ER KM-0009
SOl'~CE TYPE CODE 3.;
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS COMPRESSORS 4000.00 HP 2 EA
COMPANY NAME/SITE LOCATION MICHIGAN WISCONSIN PIPE LINE CO. CHARLTON TOWNSHIP, MI 49000
OTSEGO COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 11/01/80
PERMIT NO. 660-80 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY MICHIGAN DNR GREGORY EDWARDS (517)-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT ErF
COMPRESSOR, NAT. GAS, 2 EA 4000.00 HP
NOX 12.3000 G/HP-H
COMBUSTION MODIFICATIONS
NOTES
2 NATURAL GAS COMPRESSORS.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 210
ID NUMBER MI-0016
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933 03/13/19S4
SOLACE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE -
NATURAL GAS COMPRESSORS
1669.00 HP
COMPANY NAME/SITE LOCATION PANHANDLE EAST. PIPELINE CO.
COGNAC STATION
KS
GRANT COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MADE BY EPA REGION VII
(AGENCY)
STEVE KOVAC
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 07/28/80
ESTIMATED DATE OF START-UP
(816)-374-6525
(FHQKE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ...» BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. RECIP. ENGINE, UNITS3
1669.00 HP
NOX
700.0000 PPM 15X 02 (D)
PRE-IGNITION CHAMBER
BACT
NOTES
IF CONSTRUCTION COMMENCES PRIOR TO JANUARY/1932, THE UNIT WILL NOT BE SUBJECT TO PROPOSED SUBPART FF OF THE NSPS REGS. THE PER
MIT, HOWEVER, INCORPORATES SEVERAL PROVISION'S OF PROPOSED SUBPART FF AS PERMIT CONDITIONS.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 211
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER KS-0002
SOURCE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL 6AS COMPRESSORS 18.00 MHP
COMPANY NAME/SITE LOCATION PANHANDLE EAST. PIPELINE-FRED. » CO
WELD COUNTY
DETERMINATION IS BACT DATE OF PERMIT ISSUANCE 11/25/81
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VIII JOHN DALE (303>-337-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ __ ... .._ _ _. . _
REC COMP ENG 4500.00 HP
CO BACT
VOC - BACT
NOX 5.5000 6/HP-H BACT
ENS MODS 55.00
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM HAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1=33
PAGE G- 212 ID NUflSER CO-0010 SOLTCE T^PE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS COMPRESSORS 13746.00 HP
COMPANY NAME/SITE LOCATION PANHANDLE EAST., FT. LUPTON , CO
WELD COUNTY
DETERMINATION IS BACT DATE OF PERMIT ISSUANCE 05/29/80
PERMIT NO. ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION VIII JOHN DALE (303)-837-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
REC COMP ENG, 3 2246.00 BRAKE HP EA
NOX 55.0000 LB/H EA BACT
ENS DESIGN & MODIFICATINS
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1033
PAGE G- 213 ID NUJI3ER CO-OC11 SCUSCE TYPE CCDE 3.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/193*
SOURCE TYPE/SIZE--- NATUPAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION PHILLIPS PETROLEUM CO. , TX
WINXLER COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/15/82
PERMIT NO. X-3903 ESTIMATED DATE OF STA9T-UP-- 1932
DETERMINATION MADE BY TEXAS ACB RANDY HAMILTON (512)-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
WAUKESHA 6LRZB-9 220.00 HP
NOX 23.4000 T/YR
EQUAL NOX-CO CARBURETOR SETTING
CO 23.4000 T/YR
VOC 4.5000 T/YR
SUPERIOR 8G825 585.00 HP
NOX 62.1000 T/YR
CO 62.1000 T/YR
VOC 5.4000 T/YR
NOTES
RICH-BU INDICATES DATUM HAS TRUNCATED FCR THIS TABLE. REVIEW STATUS: 05/04/19^%
PAGE G- 214- ID NUMBER TX-0125 SOL-.CE TiPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE--- NATURAL GAS COMPRESSORS
_....__-...-.____«.,,, ____ _ _, _._ .. _ _ -. _ ___ _ -.
COMPANY NAME/SITE LOCATION SANTA FE ENERGY > CA
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 12/02/82
PERMIT NO. 0951 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY VENTURA COUNTY KEITH DUVAL (805 )-65<*-266*
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COMPRESSOR, NATURAL GAS 180.00 HP
NOX 150.0000 PPM
NOTES
STATE FILE * A330-030
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 215
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER CA-0073
SOURCE TYPE CODE 3.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/193'*
SOURCE TYPE/SIZE
NATURAL GAS COMPRESSORS
2000.00 HP EA
COMPANY NAME/SITE LOCATION SOUTHERN NAT. GAS
P.O. BOX 2563
BIRMINGHAM, AL 35202
JEFFERSON COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO. ) PSD-AL-055
DETERMINATION MADE BY ALABAMA APCD
(AGENCY)
SUE ROBERTSON
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/29/80
ESTIMATED DATE OF START-UP--
(205J-S34-6570
(FHCNE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
FCT EFF
VERT COMPRESSOR ENGINES, 3 EA
6000.00 HP
NOX
16.5000 GM/HP-H
COMBUSTION CONTROL
BACT
NOTES
THREE UNITS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS T4BLE.
PAGE G- 216
INITIAL REVIEW POST STARTUP
REVIEW STATUS: C-f/01/lcS3
ID NUMBER AL-0011
SCL'ECE TYPE CC3E 3.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- NATURAL GAS COMPRESSORS 4000.00 HP
COMPANY NAME/SITE LOCATION SOUTHERN NAT. GAS GALLION, AL 36742
P.O. BOX 68 HALE COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 06/04/81
PERMIT NO. PSD-AL-074 ESTIMATED DATE OF START-UP 1962
DETERMINATION" MADE BY ALABAMA APCD SUE ROBERTSON (2C5)-834-6570
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... i BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- -. _ -_-______________fc___»___________ __«_____________________ ___________..___________.».___.. _
VERTICAL COMPRESSOR ENGINE 4000.00 BRAKE HP
NOX 15.0000 G/HP-H
EQUIPMENT OPERATION
NOTES
MANUFACTURER EMISSION TEST
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 217
ID NUMBER AL-0012
INITIAL REVIEW POST STARTUP
REVIEW STATUS-- 04/01/1933
SOURCE TYPE CODE 3.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS 5000.00 BRAKE HP
COMPANY NAME/SITE LOCATION SOUTHERN NAT. GAS ELMCRE, AL 36025
P.O. BOX 67 ELMORE COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 06/04/81
PERMIT NO. (REGION FILE NO.) PSD-AL-075 ESTIMATED DATE OF START-UP-- 1982
DETERMINATION MADE BY ALABAMA APCD SUE ROBERTSON (2051-834-6570
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
VERTICAL COMPRESSOR ENGINE 5000.00 BRAKE HP
NOX 15.0000 6/HP-H BACT
EQUIPMENT OPERATION
NOTES
MANUFACTURER EMISSION TEST
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 218
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/15S3
ID NUMBER AL-0013
SC'JRCE TYPE CCDE
3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS 15500.00 HP
_ _,»_ ___ ___ __». ___.._ _**__-.____.... _ >._....._...._...._...^ ~-.- _ _____ _ -. -. _-.
COMPANY KAME/SITE LOCATION TENNESSEE GAS PIPELINE CO. MARIONVILLE, PA
FOREST COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 03/01/83
PERMIT NO. 27-399-001 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY PENNSYLVANIA BAQ, DER WILLIAM CHARLTON (814)-724-S530
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
= = = r = = = = = r = = = = r = = = = = = r = = = = r = r = = = r = = = :r = = = r = z = = = r = = = = = = = = = = = = = = = = = = r = = = = = = = = = = = = = r = 5 = = = = = = = = = = = = === = = = = r = r = = z = z = = === = = = r= = = = = = r=rr =
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
^ _ . _. ^_ »__ -,__ ____ ___ -,____. ___%.»_ __.,__ . . .
GAS COMPRESSOR 15500.00 HP
NOX PSD
LEAN BURN PROC./AIR-FUEL RATIO ADJUST.
NOTES
EXISTING CAPACITY IS 11500 HP. PROPOSED ADDITIONS ARE 4000 HP. TOTAL CAPACITY WILL BE 15500 HP.
INITIAL REVIEU POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1°S3
PAGE G- 219 ID NUfSER FA-OOCS SOURCE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE--- NATURAL GAS COMPRESSORS 2250.00 HP
. __ -.
COMPANY NAME/SITE LOCATION TRANSCONTINENTAL GAS PIPELINE CORP. GILLIS, LA
BEAUPEGARD PARISH
DETERMINATION IS BACT DATE OF PERMIT ISSUANCE 10/14/83
PERMIT NO. PSO-LA-506 ESTIMATED DATE OF START-UP 1933
DETERMINATION MADE BY LAQD/EPA REGION VI HARENDRA RAOL (504)-342-8S40
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINE, RECIPROCATING COMPRESSOR 2250.00 HP
NOX 29.7000 LB/H
CLEAN BURN ENGINE, MOO. COMB. W/CCNTRLS 55.00
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
_ ___ _ ____» ___ -% __________ _ _,___.___ _ __ -. ~. ~ zz~n ~~~n ~ ~~ ~ ~ ~ ~~~ ~
PAGE G- 220 ID NUMBER LA-0043 SCL.TCE TYFE CCQE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1964
SOURCE TYPE/SIZE- NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION TRANSHESTERN PIPELINE CO., BITTER LAKE * NEAR ROSWELL, NM
- ... ._ .. -. _ . , ,_. . .. ,. _ _ . ._ .._ _
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/23/82
PERMIT NO. NM-274-M-2 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA (505J-934-0020
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINE, I.C. COMPRESSOR 1596.00 HP
NOX 4.0000 G/HP-H
LOW NOX ENGINE
NOTES
STACK TEST PERFORMED, EPA REF. METHOD 20, RESULTS - 2.96 G/HP-H
(*) INDICATES DATUM WAS TRUNCATED FC3 THIS TABLE.
PAGE G- 221
ID NUMBER NM-0013A
Tf-'TTTiL REVIEW POST STARTUP
x STATUS; 04/01/1933
SOURCE TYPE CCQE 3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS
_ _ ____ _______.___ _,
COMPANY NAME/SITE LOCATION TRANSWESTERN PIPELINE CO., BITTER LAKE * NEAR ROSWELL, NM
- -_ -- _--- ---- _-_--_-_--.--------------
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/03/82
PERMIT NO. NM-274-M-1 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA (5051-984-0020
(AGENCY) (AGENCY CONTACT PERSON) (PHCKE)
rr = r = r:r:=r: = = = = = = = = = = r:; = r = = rr = ::rrr: = = = = = = r = = = = : = r = = = r = = = = = = = = = = = = = = rr = = = r = = r = = = = r = r = = = = = = = r = r = = = r = = r = = = = = = = = = = = = = = = - = = = = = = = = = --
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...& BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINE, I.C. COMPRESSOR 1050.00 HP
NOX 5.00CO G/HP-H
LOW NOX ENGINE
NOTES
STACK TEST PERFORMED, EPA REF. METHOD 20, RESULTS - 2.42 G/HP-H
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 222 ID NUMBER NM-0013
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 0^/01/1583
SOURCE TYPE CODE
3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS
_ *. _ ___.-._ -,_._ ^. --«* - ___«._..__...._ .. -. ..
COMPANY NAME/SITE LOCATION TRANSWESTERN PIPELINE CO., ISLER NO. 1 * NEAR ROSWELL, HM
_ _ ___ _ _________«. «.____ _ ____-.-. __-. *_ »
DETERMINATION IS BACT FOR A NEW SOURCE. CATE OF PERMIT ISSUANCE-- 05/08/82
PERMIT NO. NM-464 ESTIMATED DATE Of START-UP 1982
DETERMINATION M4DE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA (5051-984-0020
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
FROCESSCS SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS .. . « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINE, I.C. COMPRESSOR 1588.00 HP
NOX 4.0000 G/HP-H
LOW NOX ENGINE
NOTES
STACK TEST PERFORMED, EPA REF. METHOD 20, RESULTS - 2.06 G/HP-H
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 223
INITIAL FrtVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER NM-0014
SC'JRCE TYPE CODE 3.2
-------
APPEKDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- NATURAL GAS COMPRESSORS
.- _ . _. -.__._.- __.__..____.»___ ___ _____..___.,__ _ ___ ____ _____.__ __ _ __ ____.» ___ _« ___ ..__.._
COMPANY NAME/SITE LOCATION TRANSWESTERN PIPELINE CO., KEMNITZ STAT* NEAR MALJAMAR, MM
~ . ..-- ..P. - -- ... .-.. .. ___ .,__.,_._«_.___...__.1_ _
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/03/82
PERMIT NO. NM-399-M-1 ESTIMATED DATE OF START-UP 1932
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA (505 J-984-0020
(AGENCY) (AGENCY CONTACT PERSON) ( FKON'E )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINE, I.C. COMPRESSOR 1072.00 HP
NOX 5.0000 6/HP-H
LOW NOX ENGINE
NOTES
STACK TEST PERFORMED, EPA REF. METHOD 20, RESULTS - 4.15 G/HP-H
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 224
ID NUMBER NH-0012
INITIAL REVIEW POST STARTUP
REVIEW STATUS: O-VOl/1933
SOURCE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION TRANSU'ESTERN PIPELINE CO., RED BLUFF ST* NEAR ROSWELL, NM
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/03/82
PERMIT NO. NM-411-M-1 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA < 505 )-9S<4-0020
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... i BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINE, I.C. COMPRESSOR 1596.00 HP
NOX A.0000 G/HP-H
LOU NOX ENGINE
NOTES
STACK TEST PERFORMED, EPA REF. METHOD 20, RESULTS 3.58 G/HP-H
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 225
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER NM-0010
SOURCE TYPE CCDE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION TRANSWESTERN PIPELINE CO., RED BLUFF ST* NEAR ROSWELL, NM
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 05/03/82
PERMIT NO. NM-412-M-1 ESTIMATED DATE OF START-UP 19S2
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA (5051-984-0020
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...& BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_________...._____-._ ___. ___ __^___ __ . . _ ____ _. _ ______ «___ ___ r- ___ -.-. -.. _ v _ ____ __
ENGINE, I.C. COMPRESSOR 1073.00 HP
NOX 5.0000 G/HP-H
LOW NOX ENGINE
NOTES
STACK TEST PERFORMED, EPA REF. METHOD 20, RESULTS 2.4 G/HP-H
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 2£6
ID NUMBER NM-0010A
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1033
SCURCE TYPE CCDE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION TRANSWESTERN PIPELINE CO., RED BLUFF ST* NEAR ROSWELL, NM
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/03/82
PERMIT NO. NM-413-M-1 ESTIMATED DATE OF START-UP 1932
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA (505)-934-0020
(AGENCY) (AGENCY CONTACT PERSON) (PHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
___ ._____ »___ _-,___ _ __ _ . ______» ______ ..____«.. __ .... ,.__ «,-.___ -_ ______-__..___ __ ______.-_____ _ ^ _ _ »__._ ______..-.____..
ENGINE, I.C. COMPRESSOR 1588.00 HP
NOX 4.0000 G/HP-H
LOW NOX ENGINE
NOTES
STACK TEST PERFORMED, EPA REF. METHOD 20, RESULTS 2.51 G/HP-H
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 227
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER NM-0010B
SOURCE TYPE CCDE 3.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE - NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION TRANSWESTERN PIPELINE CO., RED BLUFF ST* NEAR ROSWELL, NM
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/03/82
PERMIT NO. NM-414-M-1 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA (505)-984-0020
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINE, I.C. COMPRESSOR 2647.00 HP
NOX 4.0000 G/HP-H
LOW NOX ENGINE
NOTES
STACK TEST PERFORMED, EPA REF. METHOD 20, RESULTS 0.82 G/HP-H
<#> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 228
INITIAL REVIEW POST STARTUP
REVIEW STATUS: o<;/oi/i?33
ID NUMBER NM-0010C
SO'J^CE TYPE CCOE Z.Z
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE---
NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION TRAHSWESTERN PIPELINE CO., RED BLUFF ST*
NEAR ROSWELL, NM
DETERHINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. NM-415-M-1
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA
(AGENCY) (AGEN'CY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 05/03/82
ESTIMATED DATE OF START-UP-- 1932
(5051-934-0020
(PHONE )
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
. .. 8 BASIS
. .. PCT EFF
ENGINE, I.C. COMPRESSOR
25S5.CO HP
NOX
5.0000 6/HP-H
LOW NOX ENGINE
NOTES
STACK TEST PERFORMED, EPA REF. METHOD 20, RESULTS -- 3.2 6/HP-H
(#> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 229
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER NM-0010D
SOURCE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION TRANSHSTERN PIPELINE CO., MALJAMAR STAT* NEAR MALJAMAR, MM
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 05/03/82
PERMIT NO. NM-387-M-1 ESTIMATED DATE OF START-UP 1932
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEID SHANKAR ANANTHAKRISHNA (5051-984-0020
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ ___, .. ____.._ ____ __ » _ __ __.. _ -» ___.._.___.. _ _____ ____-«__ __ __._ .-.» _ - - ---- --- '- »'-
ENGINE, I.C. COMPRESSOR 1073.00 HP
NOX 5.0000 G/HP-H
LOW NOX ENGINE
NOTES
STACK TEST PERRFORMED, EPA RREF. METHOD 20, RESULTS - 3.93 G/HP-H
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 230
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1903
ID NUM3ER NM-0011
SOURCE TYPE CODE 3.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS COMPRESSORS 3000.00 HP
COMPANY NAME/SITE LOCATION VALERO TRANSMISSION CO. OLD OCEAN, TX
BRAZOPIA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/09/82
PERMIT NO. X-3603 ESTIMATED DATE OF START-UP-- 1982
DETERMINATION M^DE BY TEXAS ACB RANDY HAMILTON (512)-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GAS COMPRESSORS, 3 1000.00 HP EA
NOX 34.8000 T/YR
CO 64.4000 T/YR
VOC 0.7000 T/YR
NOTES
GAS TURBINES INHERENTLY CLEAN-BURNING WITH RESPECT TO NOX EMISSIONS. EMISSIONS OF NOX BASED ON 1.2 G/HP-H
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 231 ID NUIIEER TX-C1Q4 SC'JPCE TYPE CODE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS COMPRESSORS
COMPANY NAME/SITE LOCATION WESTAR TRANSMISSION CO. , TX
POTTER COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 12/07/82
PERMIT NO. X-3990 ESTIMATED DATE OF START-UP 19£2
DETERMINATION MADE BY TEXAS ACS RANDY HAMILTON (512J-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
SUPERIOR 8GTLA 1100.00 HP
NOX 21.2000 T/YR
CCM3USTION CHAMBER MODIFICATION
CO 21.2000 T/YR
VOC 7.9000 T/YR
NOTES
EMISSION LIMITS ARE 2.0 G/HP-H NOX, 2.0 G/HP-H CO, 0.75 G/HP-H VOC.
INITIAL k^.VIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FCR THIS TABLE. REVIEW STATUS: 05/04/19S4
PAGE G- 232 ID NUMBER TX-0134 SO'J"CE T1PE CCDE 3.2
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE- OTHER INTERNAL COMBUSTION
COMPANY NAME/SITE LOCATION ARGO PETROLEUM, FERNDALE LEASE , CA
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 09/30/83
PERMIT NO. 03SO ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY VENTURA COUNTY KEITH DUVAL (805 )-65^-2664
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. ENGINE, NATURAL GAS 200.00 HP
NOX 50.0000 PPM
CATALYTIC REDUCTION 96.70
NOTES
STATE FILE 8 A330-031
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 233
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER CA-0074
SOURCE TYPE CODE 3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION 540.00 MW
__ _-.._____________._... _____________,-, _ _«._^.__ _______ . ________ .-, _.__ _ __ _ ______________ _
COMPANY NAME/SITE LOCATION CAJUN ELECT. POWER COOP. NEW ROADS, LA
POINTE COUPE PARISH
__ __________.» ______ _ _____ _ «._______.___ ______ _ ___ _. ... ____ __ ______.»____ . ______. . _.-_ __ _ .-__
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/30/78
PERMIT NO. (REGION FILE NO.) FSD-LA-062 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214J-767-15Q4
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE> COAL FIRED 540.00 MW
S02
LOW SULFUR WESTERN COAL
Ptl
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 234
INITIAL REVIEW POST STARTUP
REVIEW STATUS-- 04/01/1933
ID NUMBER LA-0001
SO'J^CE TYPE CODE
3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/28/1984
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION 6000.00 KW
COMPANY NAME/SITE LOCATION CITY OF AUGUSTA AUGUSTA, KS
(MUNICIPAL ELECT. SYS, PLANT * BUTLER COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/29/81
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VII STEVE KOVAC (S16 )-37
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- OTHER INTERNAL COMBUSTION 18611.00 HP
COMPANY NAME/SITE LOCATION CITY OF KINSMAN KINGMAN, KS 67068
P.O. BOX 168 KINGMAN COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/01/83
PERMIT NO. ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY EPA REGION VII CHARLES WHITMORE (816>-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
1C ENGINE, DUAL FUEL, UNIT 8 3495.00 HP
NOX 1150.0000 PPMV, 15X 02, DRY BACT
EFFICIENT OPERATION OF THE UNIT
NOTES
THE UNIT, A COOPER-BESSEMER MODEL LSV-12-GDT, WAS PREVIOUSLY OPERATED SINCE 1963 BY ANOTHER MUNICIPAL UTILITY. TO ENSURE THAT
S02 EMISSIONS WILL NOT INCREASE BY A "SIGNIFICANT" AMOUNT,
THE AMOUNT OF DISTILLATE FUEL OIL WHICH MAY BE COMBUSTED IS LIMITED TO 10X OF THE TOTAL ANNUAL HEAT INPUT FOR THE UNIT.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 236
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NUMBER KS-0017
SOLACE TYPE CODE
3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION 16624.00 HP (TOTAL, TO BE AD*
COMPANY NAME/SITE LOCATION CITY OF OTTAWA OTTAWA, KS
FRANKLIN COUNTY
«.«._. ______ ___,. __ _ ____ ....___ ____ _ _ __ » «.__>. «.___« ___.._ __ __,- __, . ,. - - *-
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 12/02/80
PERMIT NO. ESTIMATED DATE OF START-UP 1980
DETERMINATION MADE BY EPA REGION VII STEVE KOVAC <816)-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
RECIP. ENGINES, 2 DUEL-FUEL 1C,* 6000.00 KW EA
NOX 1150.0000 PPM 15X 02 (D) BACT
S02 FUEL STANDARD
S IN FUEL LIM. TO 0.5X BY WT.
NOTES
(«) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 237
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER KS-0004
SOURCE TYPE CODE 3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE- OTHER INTERNAL COMBUSTION 90.00 MW
COMPANY NAME/SITE LOCATION EMPIRE DIST. ELECT. CO. , MO
LARUSSELL STATION LAKSENCE COUNTY
_ ___,._ _____ __ _«.__..______ _.._.__,, «. _ _
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 01/07/81
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VII DANIEL RODRIGUEZ (816)-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT 03 PROCESS MODIFICATION ... PCT EFF
COMBUSTION TURBINE, SIMPLE-CYC,* 1056.00 MMBTU/H (MA*
NOX 330.0000 PFMV, 15X 02, (ISO)-STAK'D. DAY COND. BACT
DESIGN
CO 56.0000.LB/H BACT
21.0000 FFfiV
S02 FUEL STANDARD
SEE NOTE
NOTES
THE UNIT IS NOT SUBJECT TO NSPS, SUBPART GG. THE 7. 5 CONTENT OF THE FUEL TO BE BURNED IN UNIT 2 IS LIMITED BY PERMIT CONDITION
S TO 0.8X, BY UT. THE NOX AND CO/EACT LIMITS WERE DERIVED FROM INFO. PROVIDED BY THE TURBINE MANUFACTURER.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 233
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NUMBER MO-0.001
SOURCE TYPE CCOE
3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1934
SOURCE TYPE/SIZE-
OTHER INTERNAL COMBUSTION
252.00 MW
COMPANY NAME/SITE LOCATION FLORIDA POWER
AVON PARK, FL 33733
HIGHLANDS COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. FL 017
DETERMINATION MADE BY FLORIDA DER
(AGENCY)
ED PALAGYI
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/21/81
ESTIMATED DATE OF START-UP 1982
( PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... $ BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE PEAKING UNITS,
-------
APPENDIX -- DETAILED SOURCE LISTING
SOURCE TYPE/SIZE--- OTHER INTERNAL COMBUSTION
COMPANY NAME/SITE LOCATION GENERAL MOTORS CORP., PROVING GROUNDS MILFORD, MI
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/14/84
PERMIT NO. 27-84 ESTIMATED DATE OF START-UP 1933
DETERMINATION MADE BY MICHIGAN DNR KENNETH TERRY (5171-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
DYNAMOMETER, CAR/TRUCK TESTING
VE 20.0000 7. OPACITY
FILTER TOWER, SEE NOTE
NOTES -----------
ONLY BEIN3 USED WHEN 5 OR MORE ENGINES ARE SIMULTANEOUSLY RUNNING OR AN OPACITY PROBLEM EXISTS, OR APPROXIMATELY 1/2 HR PER DA
Y t 3 1/2 HR PER WEEK.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 240
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER MI-0026A
SOURCE TYPE CODE 3.3
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION 2672.00 MMBTU/H
COMPANY NAME/SITE LOCATION GULF STATES UTILITY BATON ROUGE, LA
13 MI. S. BATON ROUGE IBERVILLE PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 01/30/81
PERMIT NO. (REGION FILE NO.) PSD-LA-292 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK <214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COMBUSTION TURBINE(2)
1336.00 MMBTU/H
S02 5.5000 LB/H
0.0040 LB/MMBTU GAS
NATURAL GAS FIRING
NOX 334.0000 LB/H
0.2500 LB/MMBTU GAS
STEAM/WATER INJECTION
CO 125.0000 LB/H
0.0900 LB/MMBTU GAS
COMBUSTION CONTROLS
PM 1.0000 LB/H
0.0010 LB/MMBTU GAS
NATURAL GAS FIRING
S02 296.0000 LB/H
0.2200 LB/M;:BTU OIL
.23X S. FUEL OIL
NOX 362.0000 LB/H
0.2700 LB/MMBTU OIL
STEAM/WATER INJECTION
CO 216.0000 LB/H
0.1600 LB/MMBTU OIL
COM3USTION CONTROLS
NSPS
NSPS
BACT
BACT
NSPS
NSPS
BACT
PAGE G- 241
-------
PM 33.0000 LB/H 8ACT
0.0250 LB/MM8TU OIL
.IX ASH FUEL OIL
NOTES
TWO COMBUSTION TURBINES ARE PERMITTED TO FIRE EITHER NATURAL GAS OR FUEL OIL.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 242 ID NUMBER LA-0005 SOURCE TYPE CODE 3.3
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- OTHER INTERNAL COMBUSTION 100.00 MM
COMPANY NAME/SITE LOCATION GULF STATES UTILITY LAKE CHARLES, LA
6 MI WNW OF LAKE CHARLES CALCASIEL PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 12/22/80
PERMIT NO. (REGION FILE NO.) PSO-LA-29<+ ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
TURBINE
1396.00 MMBTU/H
S02 0.3500 LB/MMBTU OIL
0.0010 LB/MM3TU GAS
LOM SULFUR OIL (0.46X)
NOX 0.2600 LB/MM3TU OIL
0.2500 LB/KM3TU GAS
WATER/STEAM INJECTION
CO 0.1600 LB/MM3TU OIL
0.0900 LB/MM3TU GAS
EFFICIENT DESIGN
PM 0.0900 LB/MMBTU OIL
0.0010 LB/flKBTU GAS
LOU ASH OIL (0.1X)
NSPS
NSPS
60.00
BACT
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 243
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1?33
ID NUMBER LA-0003
SOURCE TYPE COOE
3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- OTHER INTERNAL COMBUSTION 23.30 MKW
COMPANY NAME/SITE LOCATION HOFFMANN-LAROCHE, INC. BELVIDERE, NJ 07823
MAMUNKACHUNK AVENUE WARREN COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 08/17/81
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION II LARRY KARAS (212 )-264-953S
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS .. . « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- * -. _ _ _ _ _ . __ __ «._ _ _ _,_ __.. _ __.».._ -, ..__ _ _: .._ ___.._ ___ _ __-..
DIESEL ENGINE, W/WASTE HEAT BOI* 23.30 MKW
NOX 2272.0000 T/YR NSPS
WASTE HEAT BOILER
RETARD. FUEL INJ. TIMING
NOTES -
SPECIFIC LIMITATIONS IN TERMS OF CAPACITY SHALL BE MET (AS PERMIT CONDITIONS) FOR THE OPERATION OF THE DIESEL COGENERATION FAC
ILITY IN COMBINATION WITH SOME OF THE FIVE EXISTING BOILERS.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 24<+
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 0^/01/1933
ID NUMBER NJ-0003
SO'J°CE TYPE CODE
3.3
-------
-
UJ
0
g
o
V)
£
z
3
O
u
z
o
M
o
E
r -f
H
a
UJ
>
M
a
o
o
(_j
M
O
*»
a:
01
O
i
3
M
^
Z
M
f
8
_j
UJ
t-
M
in
X
UJ
E
<
Z
>-
Z
<
D-
E
O
U
in
o-
rH
i
i
a
1 3
i i
UJ t-
O Q:
Z <
< t-
3 W
in
in u.
M O
f- UJ fl
M H rH
E < rH
DC D CM
Ul 1 UJ
O- O CM Z
Ul CO O
U, r- N I
O -
[y ^_J
X 2
U UJ
is
<(
* a.
LU UJ
U ~
§M O
o z:
*/> i: LU
M CD
U) -J ^
2 M
^
g
H- rH >-
O CJ UJ
< 0
03 O LU
O
in r^ <
M 0 E
Z CM Z
O <0 O
M M
H r-
< O <
z z z
M M
E »- r
D: M a;
UJ 3- uj
1- o: r-
UJ UJ UJ
o a. o
n
n
n
n
u
u
n
n
n
n
n
it
n
u
it
n
n
it
u
n
n
n
n
ii
n
n
n
n
ii
ii
11
n
n
it
it
n
u
it
n
n
n
ii
n
n
n
n
u
ii
n
ii
n
n
ii
n
ii
M
II
II
II
It
II
II
II
II
II
II
II
II
II
II
II
It
II
It
II
II
II
Jj
11
II
II
II
II
II
II
II
II
11
II
II
II
II
II
II
II
II
It
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
U
II
II
II
II
II
II
II
II
II
II
II
II
II
11
II
M U.
in LU
^
10 r-
U
a a
(
, ,
. .
Z
o
M
^
U
M
U.
M
O
g
in
UJ
o
0
fl
o:
o
r-
UJ
r:
a.
M
cr
Ul
i 1
M O
M r-
-J Z
O
Z 0
o
M
in
in
M
E
Ul
lEa
< Ul
ID f
_J M
J 3C
O LU
a.
f~
D >
a H
3Z H
CD U
o a.
-£ (J
r~
r-
o
UJ
-> t-
3 3T
in D;
UJ
in a.
UJ
in tn
in M
UJ I
o >-
o
a: o
a K
in 10
D. n.
in in
Z Z
in w
^ ^
10 ID
1- 1-
U O
3 3
O O
o o
C£ [X
n Q_
Z
U. U- ID
O O M
w
Z Z UJ
O O Q
M M
(-(-!-
< < z
O U UJ
M M z:
u. u- a.
M M I M
E K E a X D
Q. 3 a. 3 fl3 Gf
a. u, a. CL -i ui
o o o
O 0 0
O 0 O
o o o
* *
O LA O
in r^ o-
rH CM
CM X
0 0 O
in z u
o
Ul
a:
M
u.
in
0
t
^
o
o
UJ
z
M
1
r-
O
or
LL
o
E
UJ
a
o
in
ID
o
u
a.
UJ
a.
o
o
M
M
O
o
in
10
M
D:
ID
O
a:
o.
UJ
E
a.
x
UJ
z
M
O
Ul
in
e
in M .
ui tn t-
t- <* o
3 II
f- n to
CK II
< II
t- II
V) II
II UJ
H HO
in no
O II LJ
QL II
II Ul
ii a.
3 n v
UJ IO II f-
M CO II
> O' II Ul
LU rH II U
a x ii CK
rH II D
.J O II CJ
«t x n 10
M ~S- II
r- O II
M II
Z II
M II
in n
3 II
H- II
< II
K II
in n
n
> II
UJ II
EX II
II
II
II
II
II
II
II
II
II
It
II
II
II
II
II
II
It O
II rH
II O
II O
II I
II I
II M
II
II tX.
II UJ
ii rn
CD u
< n
t- ii
n
in n
M II
in it
UJ It
t- II Ul
< II J-
U II CJ
M II
p II I
2 ii 10
M II
II UJ
II ID
* II <
^ ii a.
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION
COMPANY NAME/SITE LOCATION MUNICIPAL GENERATING PLANT BELOIT, KS
_ ___,-_ _ ___ ____-._ _ _ ._ _-,_ -._ __.,_.._.- _ _.._ _ _ _-.__.. ______,,_
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-
PERMIT NO. ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION VII STEVE KOVAC (816)-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENSINE-GENERATOR 6000.00 KW
NOX 1150.0000 PPMV 15'/. 02, DRY BASIS
S02 FUEL STANDARD
S CONTENT LIM. TO 0.7X BY WT.
CO
NOTES
TEST DATA USED TO ESTABLISH NOX STANDARD
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 246
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER KS-001^
SOURCE TYPE CCOE
3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- OTHER INTERNAL COMBUSTION 250.00 MW
COMPANY NAME/SITE LOCATION NEVADA PWR CO./REID GARDNER STATION MOAPA, NV
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 01/03/80
PERMIT NO. (REGION FILE NO.) NV 79-03 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY EPA REGION IX JIM HANSON (415)-974-8038
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GENERATOR 250.00 MM
S02 0.2900 LB/MMBTU
WET SCRUBBER 85.00
NOX 0.5000 LB/MI1BTU S3. COAL
0.6000 LB/MM8TU BIT. COAL
PROPER BOILER DESIGN & OPER.
PM 0.0300 LB/MM3TU
BAGHOUSE 99.60
NOTES
ALL EMISSION LIMITS ARE BASED ON: NSPS, AND BACT DETERMINED BY TECHNOLOGY ANDECONIMICS. ADDITION OF GENERATOR TO AN EXISTING F
ACILITY.
(*) INDICATES DATUM WAS TRUNCATED FOB THIS TABLE.
PAGE G-
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933 02/13/1934
ID NUMBER NV-0004
SCU.7CE TYPE CODE
3.3
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION 4.20 (1MCF/YR
COMPANY NAME/SITE LOCATION ORGANIC FUEL PRODUCTION, INC. , TX
LUBBOCK COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 02/16/83
PERMIT NO. X-4141 ESTIMATED DATE OF START-UP 1983
DETERMINATION HADE BY TEXAS ACB GARY WALLIN t512)-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
-------«--..-.--
DIGESTERS, 7 4.20 MMCF/YR
PM 0.0100 T/YR
S02 0.0020 T/YR
IRON SPONGE
NOX 0.2100 T/YR
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 05/04/1934
PAGE G- 248 ID NUMBER TX-0113 SOLTCE TYPE CCDE 3.3
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION 160.00 MHP
COMPANY NAME/SITE LOCATION PRUDHOE BAY CONSORTIUM PRUDHOE BAY, AK
-. __ _ _ __ »_ _. __ ___._,._._._ .____.«__.__,____..,_
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 12/17/80
PERMIT NO. (REGION FILE NO.) PSD-X81-13 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION X PAUL BOYS (2061-442-1193
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GAS TURBINE, 10 16.00 MHP EA
NOX 150.0000 PPM BACT
DRY CONTROLS
CO 109.0000 LB/MMSCF FUEL BACT
MONTGOMERY PROPER COMBST. COND.
GAS HEATERS
NOX 0.0800 LB/MMBTU BACT
LOU NOX BURNERS
CO 0.0180 LB/MMSTU
MONTGOMERY PROPER COMBST. COND.
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 249 ID HUTSER AK-OOC3 SC'J~CE TYPE CODE 3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE--- OTHER INTERNAL COMBUSTION
COMPANY NAME/SITE LOCATION SEA WORLD, INC. SAN DIEGO, CA 92109
1720 SOUTH SHORES RD.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE- 06/11/82
PERMIT NO. 7801 ESTIMATED DATE OF START-UP-- 1981
DETERMINATION MADE BY SAN DIEGO APCD GUS ANDERSON (6191-565-3925
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. PISTON ENGINE 7.10 MM3TU/H
NOX 1.8000 LB/MHBTU SEE NOTE
SINGLE STAGE CATALYTIC CONVERT.
CO 1.5000 LB/MMBTU SEE NOTE
SINGLE STAGE CATALYTIC CONVERTER
NOTES
COSENERATION UNIT CONSISTING OF 930 BMP I.C. PISTON ENGINE, NATURAL GAS FUELED, 630 KW ELECTRIC GENERATOR AS!D EQUIPPED FOR WAS
TE HEAT RECOVERY.
BEFORE USING THE EMISSION UNITS SHOWN, THE SAN DIEGO AGENCY SHOULD BE CONTACTED.
(*> INDICATES DATUM HAS TRUNCATED FOR THIS TABLE.
PAGE G- 250
INITIAL P*cVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NUMBER CA-0042
SOURCE TYPE CODE
3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION
. -... _«..._. __ «. _ .__ __ ...»»_ _«.«.__ «..»....»,.»_ __..____.__.... __« ________ _«.»__fcfc,ii»^«-.«,«,^ ««_«._
COMPANY NAME/SITE LOCATION SEA WORLD, INC. SAN DIEGO, CA 92109
1720 SOUTH SHORES RD.
_
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 05/12/83
PERMIT NO. 8134 ESTIMATED DATE OF START-UP-- 1983
DETERMINATION MADE BY SAN DIEGO APCD GUS ANDERSON (619J-565-3925
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. PISTON ENGINE 7.10 MMBTU/H
NOX 0.2480 LB/MMBTU
2 STAGE CATALYTIC CONVERT. 90.00
CO 0.2300 LB/Mr'.BTU
2 STAGE CATALYTIC CONVERTER 90.00
NOTES
COGENERATION UNIT CONSISTING OF 930 BHP I.C. PISTON ENGINE, NATURAL GAS FUELED, 630 KM ELECTRIC GENERATOR Af!D EQUIPPED FOR WAS
TE HEAT RECOVERY. PERMIT PENDING
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 251
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER CA-004CA
SOU3CE TYPE CODE
3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1934
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION 40.00 MW
COMPANY NAME/SITE LOCATION SEBRING UTILITIES COMMISSION SEBRING, FL 33870
368 S. COMMERCE AVE. P.O. BOX* HIGHLANDS COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 04/03/81
PERMIT NO. (REGION FILE NO.) PSD-FL-071 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY FLORIDA DER ED PALAGYI (9041-428-1344
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
DIESEL ENGINES
19.53 MW EA
NOX 819.0000 PPMV
COMBUSTION CONTROL
S02 2.6700 LB/MHBTU
Z.57. SULFUR OIL
PM 0.1000 LB/MMBTU
COMBUSTION CONTROL
CO 0.5750 LB/MMBTU
EQUIPMENT OPERATION
VOC 0.2600 LB/KMBTU
EQUIPMENT OPERATION
NSPS
BACT
BACT
NSPS
NSPS
NOTES
HU3E SLOW-SPEED RECIPROCATING INTERNAL COMBUSTION ENGINES TO DRIVE ELECTRICAL GENERATORS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 252.
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933 01/25/1934
ID NUMBER FL-0025
SOURCE TYPE CODE
3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE- OTHER INTERNAL COMBUSTION 27.50 MMCFD
_ ».-.. __ ».______ -, __ »._«. _______ __ _.«»..__».__...,__ ».»~ «».-_ ____.,____
COMPANY NAME/SITE LOCATION SHELL OIL CO. NEAR MCCAMEY, TX
UPTON COUNTY
. .
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/27/81
PERMIT NO. (REGION FILE NO.) PSD-TX-360 ESTIMATED DATE OF START-UP 1981
DETERMINATION MADE BY EPA REGION VI BILL TAYLOR (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. ENGINES, RECIPROCATING FUE* 1215.00 HP
NOX 10.0000 G/HP-H BACT
DERATED OLD ENGINES
NOTES
(*) INDICATES DATUM MAS TRUNCATED FOR THIS TABLE.
PAGE G- 253
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
ID NUMBER TX-0030
SCX'SCE TYPE CODE 3.3
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE OTHER INTERNAL COMBUSTION 12000.00 KW
COMPANY NAME/SITE LOCATION TRENTON DISTRICT ENERGY CO. TRENTON, NJ
S. WARREN BET. LIVINSSTON * F* MERCER COUNTY
__________________________._______,___»_____«____ _ __ __^ ._
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 10/29/81
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION II LARRY KARAS (212)-264-953S
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . t. BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT CR PROCESS MODIFICATION ... PCT EFF
_ _ _ ,_ ___.. _______ ». _ _ . ______ _ _ _ _ _ ___________________________ _-, _________ _ __.».» _,__>. __ _ » «. -. -»
DIESEL ENGINES, W/2 SUP. FIRED * 6.00 MKW EA
PM 71.0000 T/YR
SUPPLEMENTARY FIRED BOILERS
PROPER COMBST. OF EXAUST GASES
S02 432.0000 T/YR SIP
LOW SULFER FUEL
LOU SULFUR FUEL
NOX 1869.0000 T/YR DESI
USE OF MANUFACT. ENS. MOD.
NOTES
GCOO COMBUSTION PRACTICE 4 USE OF LOU SULFUR FUEL OIL, 0.5X BY WT., t USE OF NATURAL GAS AS AVAILABLE,ARE REQUIRED FOR WASTE H
EAT BOILERS. BASIS FOR PM CONTROL IS CONTROL EQUIPMENT.
BASIS FOR FM CONTROL IS CONTROL EQUIPMENT
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1°33
PAGE G- 254 ID NUMBER NJ-0002 SOURCE TYPE CODE 3.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1964
SOURCE TYPE/SIZE SURFACE COATING - CANS/COILS
COMPANY NAME/SITE LOCATION BALL METAL CONTAINER GROUP EAST FINDLAY, OH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE 0F PERMIT ISSUANCE 04/10/81
PERMIT NO. 03-1025 ESTIMATED DATE OF START-UP 1981
DETERMINATION MADE BY OHIO EPA NKD DON WALTERMEYER (419 )-35;i-S461
(AGENCY) (AGENCY CONTACT PERSON) (RHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
" -- -* -- «_ _ __ _ _ __ _ _ __ __ _. ____..__..,____,____ __ ___»_ __________..-.-__,_ _________.___.»______,___.___,._______
EXTERIOR BASE OPERATION 300.00 MM CANS/LIN*
VOC 0.3600 KG/L COATING SOLIDS NSFS
THERMAL INCINERATOR 85.00
INTERNAL COAT 300.00 MM CANS/LIN*
VOC 0.5400 LB/GAL COATING MINUS H20 BACT
NOTES
PERMIT REQUIRES THAT VOC EMISSIONS SHALL NOT EXCEED ANY NSPS LIMITS APPLICABLE TO BEVERAGE CAN SURFACE COATING. IT REQUIRES TH
E SOURCE TO NOTIFY OF 1) CONSTRUCTION DATE, 2) ANTICIPATED STARTUP DATE, 3) ACTUAL STARTUP DATE, AHO 4) DATE
OF PERFORMANCE TESTING
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. PEVIEW STATUS: 04/01/1933
PAGE G- 255 ID NUMBER OH-0035 SCUSCE TYPE CODE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE SURFACE COATING - CANS/COILS
COMPANY NAME/SITE LOCATION CONTINENTAL CAN CO., USA PLANT #82 WEST CARROLLTON, OH
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 07/01/S3
PERMIT HO. 0857101741 ESTIMATED DATE OF START-UP 1933
DETERMINATION M40E BY REGIONAL APCA JAMES GROSS (513)-225-4435
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
___________________ ___ __« »__ __ -.__ -. -._ . - "- - "*-
END SEAM COMPOUND 4.70 GAL/H
VOC 3.0900 LB/GAL COMPOUND, MINUS H20 TECH
38.1600 T/YR
NOTES
PHASED INSTALLATION OF 4 LINES, 4 MACHINES EA. , WILL OCCUR IN A 6 MONTH PERIOD. IN APRIL, 1984, CONTINENTAL CAN WILL BEGAIN EM
PLOYING A NEW END SEAM COMPOUND
WHICH WILL BE COMPOSED OF A VOC CONTENT LESS THAN 3.09 LB/GAL, MINUS WATER.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 256
ID NUMBER OH-0047 SOURCE TYPE COOE 4.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- SURFACE COATING - CANS/COILS
COMPANY NAME/SITE LOCATION EVANS COOPERAGE CO., INC. TULSA, OK
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 05/04/83
PERMIT NO. T82-31 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY TULSA CITY-COUNTY HEALTH DEPT JIM VAN SANDT (918)-744-1000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . fc BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HAND SPRAY DRUM PAINTING 73.00 DRUMS/H
VOC 15.6800 LB/H
HIGH SOLIDS PAINT,43.9X SOLIDS 12.90
NOTES
1) VOC REDUCTION IN PAINTS BACT BECAUSE OF ECONOMIC FACTOR. ANY OTHER CONTROLS WOULD HAVE COST BOX OF THE TOTAL INVESTMENT.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 257
INITIAL REVIEW POST STARTUP
STATUS: 04/01/1933
ID NUMBER OK-0015
SOURCE TYPE CODE 4.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1964
SOURCE TYPE/SIZE-
SURFACE COATING - CAMS/COILS
600.00 MM CANS/YR
COMPANY NAME/SITE LOCATION MILLER BREWING CO.
MOULTRIE, GA
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. 3411-035-6906-C
DETERMINATION MADE BY GEORGIA EPO
(AGENCY)
HAI CHANG
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 07/02/79
ESTIMATED DATE OF START-UP-- 1931
( FHCN'E )
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MCDIFICATION
« BASIS
FCT EFF
BASE COATING
INTERIOR BODY SPRAYING
OVERVARNISH
END SEALING COMPOUND
298.00 T/YR
182.00 T/YR
76.00 T/YR
66.00 T/YR
VOC 1.8500 LB/GAL COATING MINUS H20
LOW SOLVENT COATING
VOC 3.9900 LB/GAL COATING MINUS H20
LOW SOLVENT COATIS'G
VOC 2.3300 LB/GAL COATINS MINUS H20
LOW SOLVENT COATING
VOC 3.7000 LB/GAL COATIK'S MINUS H20
LC'.>f SOLVENT COATINS
NOTES
PLANT CURRENTLY DOES NOT PREFORM ANY BASE COATING OPERATION. COMPLIANCE COATIN'35 ARE NOW BEIN3 USED FCR THE OTHER THREE COATIN
G OPERATION'S.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 258
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER GA-0011
scur:c£ TYPE CCCE
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE- SURFACE COATING - CANS/COILS
COMPANY NAME/SITE LOCATION NATIONAL CAN CORP. CHICAGO, IL
COOK COUNTY
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 11/09/81
PERMIT NO. C 7906091 ESTIMATED DATE OF START-UP 1983
DETERMINATION MiDE BY ILLINOIS EPA CHRIS ROMAINE (217 )-782-2113
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
COATER & OVENS
VOC 209.6000 T/YR LAER
COATINS BREAKDOWN SEE NOTES
NOTES
COATING SOLVENT LIMITATION - INSIDE SPRAY 3.63 LB/GAL, BOTTOM END SPRAY 2.1 LB/GAL, OVERVARNISH 2.1 LB/GAL, BASECOAT 1.8 LB/GA
L
INITIAL RtVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/19'33 CVC4/1-W
PAGE G- 259 ID K"J!!2ER IL-0011 SC'J^CE TfPE CCDE 4.1
-------
APPENDIX DETAILED SOURCE LISTING
05/33/1984
SOURCE TYPE/SIZE - SURFACE COATING - CANS/COILS
COMPANY NAME/SITE LOCATION PREFINISH METALS WALBRIQGE, OH
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 05/04/79
PERMIT HO. 03-746 ESTIMATED DATE OF START-UP 1931
DETERMINATION MADE BY OHIO EPA NWD CHUCK HULL (4191-352-8461
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
Z COIL COATERS 4 OVENS 700000.00 T/H VARIES
VOC 37.0000 LB/H
AFTERBURNERS 97.00
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 260
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1^3
ID NUMBER OH-0039
SOURCE TYPE CODE 4.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE SURFACE COATING - CANS/COILS
COMPANY NAME/SITE LOCATION STROH CONTAINER FREMONT, OH
.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/30/79
PERMIT NO. 03-807 ESTIMATED DATE Or START-UP-- 1931
DETERMINATION MADE BY OHIO EPA NWD DON WALTERMEYER («._« _ _ _
BASE, BOTTOM, AND INTERNAL COAT* 3000.00 CANS/MIN.
VOC ^0.0000 T/YR
CATALYTIC INCINERATOR 90.00
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE 6- 261
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NU::BER OH-oo3&
SOURCE TYPE CODE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198'*
-~z = = = =- = = = = = ~ =-- = - = ---- = --- = - = = = = ----=---- = ~-~~--= = ~ = - = = = = = -- = ~ = ~ = ~---=-~ = ~~~---~ = = ~--- = = ---- = ~~~~ = = ~:~~ = = ~~ = ~ = ~~~ = = = = ~:=~ = ~~~~ = ~~~
SOURCE TYPE/SIZE- SURFACE COATING - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION ALLIED PRINTERS & PUBLISHERS, INC. TULSA, OK
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/13/81
PERMIT NO. T80-74 ESTIMATED DATE OF START-UP-- I960
DETERMINATION MADE BY TULSA CITY-COUNTY HEALTH DEPT JIM VAN SAKDT (918)-744-1000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_____.. ..___. .. ,. , _-.,.-.__ -. ________ _ ~
WEB OFFSET PRINTING PRESS 800.00 FT/SEC
VOC 0.7140 LB/H
STRAIGHT FLAME INCIN., W/PREHEATER 90.00
HIGH SOLIDS INK (68X)
NOTES
1) DECREASE IN VOC CONTENT. EFFICIENCY = IZ.5X. 2) CONVERSION OF PHOTOCHEMICAL REACTANTS TO NON-REACTANT MATERIALS. EFFICIENCY
= 90X
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 262
ID NUMBER OK-0016
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1033
SOL'"CE TYPE CODE <+.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE--- SURFACE COATING - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION AVERY INTERNAT PAINESVILLE TWP., OH
LAKE COUNTY
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 06/11/81
PERMIT NO. 0243110957 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY OHIO EPA NED DENNIS BUSH (216 )-425-9171
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- _ _..__ _.. __________ ...,_ ..__...__.. ___..»___ ___________ _______,.___ _ ___-...
VINYL AND PAPER COATING LINE 63.90 GAL/H
VOC 2.6000 LB/6AL COAT. APPLIED LAER
132.8000 T/YR
LOW SOLVENT COATING
NOTES
LAER LIMITS AND ANNUAL MAX. EMISSION IMPOSED BY PERMIT CONDITIONS WHICH REQUIRES REDUCTIONS FROM SOURCE K007 OF 159.4 TPY TO P
ROVIDE THE OFFSET AMD FURTHER REDUCTIONS FROM 6 (CONT. 27)
OTHER COATINS LINES TO LIMIT VOC EMISSIONS TO 2.05 LB/GAL, EXCL. WATERBY 4-1-82
(*> INDICATES DATUM HAS TRUNCATED FOR THIS TABLE.
PAGE G- 263
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER OH-0014
SOURCE TYPE CODE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- SURFACE COATING - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION DIETZ6EN CORP. DES KOINES, IL
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/11/80
PERMIT NO. C8006034 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY EPA REGION V CHRIS ROMAINE (217 )-732-2113
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE )
PROCESSES SU3JECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ROLLER COATER LINE
VOC 0.6000 LB/GAL COATING LAER
AFTERBURNER 90.00
NOTES :
90X EFFICIENCY REQUIRED OF AFTERBURNER SYSTEM (CAPTURE & DESTRUCTION).
<») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 264
INITIAL REVIEW POST STARTUP
REVIEW STATUS: C^/01/1°S3 04/04/1934
ID NUMBER IL-0013
SOURCE TYPE CODE 4.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
SURFACE COATINS - PAPERS/FABRICS
240.00 LB/H
COMPANY NAME/SITE LOCATION FRYE COPY SYS, INC
GOSHEN, IN
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. PC(20)1460
DETERMINATION MADE BY INDIANA APCO
(AGENCY)
FRANK PROFIT
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 11/07/00
ESTIMATED DATE OF START-UP--
(317)-633-0664
(PHCHE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
PAPER COATING LINE
240.00 LB/H
VOC
25.0000 T/YR
CARBON ABSORBER
95.00
NOTES
4000 MRS/YEAR OPERATION
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 265
ID NUMBER IN-0019
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
SOURCE TYPE CODE 4.2
-------
APPENDIX DETAILED SOURCE LISTING 05/22/1984
SOURCE TYPE/SIZE- SURFACE COATING - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION GAZETTE PRESS PRINTING PITTSBURGH , CA
, " * *"
PERMIT NO. Zoic? .,,,-» -,-,, tn*n
DETERMINATION MADE BY BAY AREA AQMD MOHAMAD MDAZED (415>-771-6000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS'PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . . . PCT JFF
DRYING OVENS 12950.00 CF/M
VOC 9.0000 LB/D
FUME INCINERATOR 95.00
FUME INCINERATOR 13950 CFM KATEC, TVA-8U, FILE A 340-007. SOURCE OPERATES \Z H/0 , 6 D/WEEK, 52 WEEK/YR.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. _ -f^:'-.!!*!-!! ?-!'=?--!! = = = = = = === = = = =
PAGE=6-"6r=S ==== = === = = = = = = = === = === = = = = = " iD~NUM3ER~CA-005*SCISCE TYPE CCDE 4.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE SURFACE COATING - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION H.S. CROCKER CO. PRINTING SAN BURNO, CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/21/82
PERMIT NO. 28709 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY BAY AREA AQMD MOHAMAD MOAZED (415J-771-6000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
FPOCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FRINTIN3 PRESS, 64 INCH
VOC 415.0000 LB/D
SEE NOTE
NOTES
VOC<2.5 LB/GAL LIMIT VOC CONTENT OF INKS. FILE A 340-008. SIX COLOR PRESS OPERATES 14 H/D, 5 D/WEEK, 48 WEEK/YR.
(»> INDICATES DATUM WAS TRl'S'CATEO FOR THIS TABLE.
PAGE G- 267
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/19/1934
ID NUMBER CA-0055
SCt'RCE TYPE CG3E 4.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/l?34
SOURCE TYPE/SIZE SURFACE COATIHS - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION INLAtID, DIVISIOH OF G.M. CORP. VANDALIA, OH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/18/80
PERMIT NO. 0857170135 K001 ESTIMATED DATE OF START-UP-- 1977
DETERMINATION M4DE BY REGIONAL APCA JAMES GROSS <513J-225-4435
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
LEMSO GRAVURE VINYL COATER 45.00 GAL/H
VOC 83.8400 LB/H TECH
CARBON ADSORPTION 73.00
NOTES
THE 73X EFFICIENCY REPRESENTS THE FIRST EFFICIENCY DETERMINATION. SEMI-ANNUAL EVALUATIONS WILL BE PERFORMED.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
P,iGE G- 263
INITIAL RtVIEU POST STARTUP
REVIEW STATUS:
ID NUMBER OH-0048
SOURCE TYPE CODE 4.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1954
= S = ~rs~mrzrs~ *- - _ __ _..«._ ...___ ___ _
* _ _s = r:r:~c rs~~ srzzs^zsi; si: s = ss~~s~ = ~i:s = = = s~ = ^~r
SOURCE TYPE/SIZE SURFACE COATING - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION INTERNAT. LABEL MFG. FAC. CLARKSVILLE, TN
MONTGOMERY COUNTY
"fc "* __ »-_.. __ ___... ta_« _ ... -.___ __ .. _ «n_ _ __ -. .__ .-. -... w. ........ . . ^ v_
PFPMT °R * NEW SOURCE' OATE OF PER»IT ISSUANCE- 03/26/80
PERMIT NO. PSD-TN-060 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY TENNESSEE APCD ANGIE PITCOCK (615)-741-3651
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
:; = :;;: ;; --__..__ = = = = S = = = = = = a = = = = = = = = = = = = = = = = = = = = = r = = = = = = = = = = S = = = S = = = = = = - = = -= = = - = = = = = = -= = = = = = = = =
THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
__.__.____ CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
"~~~~~*-"'~~'"~"'1-* « -»-. **.._ .. _ . ^_ _ ^^_ _ _,._..__ ,^__ ».»^. ^ «.«.-. _ «.
PAPER PRINTING 3454.00 LB/H
VOC 46.9400 T/YR LAER
BOTtFPS NiT TA.J x CA CARBON ADSORP. BEDS + INCIN. 99. ?0
D'JILtRi), NAT. GAS, 3 EA
S02 152.8800 T/YR EACT
NOTES
m INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS-""4/01/1983" ^^ STARTUP
PAGE G- 269 ID NUMBER TN-0004 SOURCE TYPE CODE 4.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE- SURFACE COATING - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION ITEM FIBRE CO. ASHTABULA, OH
ASHTAEULA COUNTY
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/23/81
PERMIT NO. 0204010112 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY OHIO EPA NED DENNIS BUSH <216J-425-9171
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
RESIN COATING LINE
VOC 2.9000 LB/GAL COAT. APPLIED LAER
516.0000 T/YR
LOW SOLVENT COATING
NOTES
COMPANY TO REPORT QUARTERLY OR MONTHLY COATING USE, TOTAL VOC EMISSIONS, AND LB/GAL VOC EMISSIONS RATE.
OFFSETS NOT REQUIRED RURAL APEA.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/19S3
PAGE G- 270 ID NL'MoER OH-0015 SOURCE TYPE CCOE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- SURFACE COATING - PAPERS/FABRICS 450.00 LB/H
COMPANY NAME/SITE LOCATION MURRAY RUBBER, (MEAD COMPANY) HOUSTON, TX 77040
HARRIS COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 07/01/82
PERMIT NO. 9040 ESTIMATED DATE OF START-UP-- 1982
DETERMINATION HADE BY TEXAS ACS ART KELLOGG (5X3J-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHCUE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FABRIC COATER 450.00 LB/H
VOC 27.0000 LB/H
THERMAL OXIDIZER 90.00
NOTES
THIS SYSTEM REDUCES EMISSIONS TO 0.83 LB/GAL APPLIED W/GREATER THAN 90X EFFICIENCY (MAXIMUM). TACB REGULATIONS & EPA GUIDELINE
S ALLOW A MAX. OF 2.9 LB/GAL APPLIED. THE OXIDIZER REQUIRES NO FUEL FOR OFER. OTHER THAN THE DRYER EMIS.
I
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 271
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER TX-0086
SOURCE TYPE C03E 4.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- SURFACE COATING - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION NDM CORP. MORAINE, OH
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 07/23/82
PERMIT NO. 0857101457 K001 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY RAPCA - DAYTON,OH THURMAN SMITH (513>-225-4435
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . ... PCT EFF
PAPER COATINS 30.00 FT/MIN
VOC 19.0000 LB/H
11.4000 T/YR
THERMAL INCINERATOR 99.70
NOTES
THERMAL INCINERATOR WAS TESTED AT 99.77. OVERALL EFFICIENCY. COATING MUST MEET 2.9 LB VOC/GAL COATING OR CONTROL EQUIPMENT MUST
PROVIDE AN EMISSION REDUCTION OF 50.5X. PERMIT RESTRICTS OVERALL EFFICIENCY TO NO LESS THAN 85.5X.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 272
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933 02/13/19C4
ID NUMBER OH-OC43
SOUPCE TYPE CC3E
4.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE SURFACE COATING - PAPERS/FABRICS
COMPANY NAME/SITE LOCATION STECHER-TRAUNG-SCHMIDT NEWARK, CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 10/08/82
PERMIT NO. 28246 ESTIMATED DATE OF START-UP-- 1983
DETERMINATION MADE BY BAY AREA AQMD ELLEN LINDER (4151-771-6000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
OVEN, VARNISHER DRYING 4000.00 SHEETS/H
VOC 67.0000 LB/D BACT
HIRT FUME INCINERATOR 90.00
NOTES
OVERALL EFFICIENCY 90X, 97X IN-OUT OF INCINERATOR.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 273
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/19/1934
ID NUMBER CA-0050
SOURCE TYPE CODE 4.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE SURFACE COATING - AUTO./LIGHT DUTY TRUCKS
__.^_.____«.___.____«._ ^____, ._ . ^ -* - « ^-^ "-
COMPANY NAME/SITE LOCATION CHEVROLET - FLINT MANUFACTURING FLINT, MI
3CO NORTH CHEVROLET AVE
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/07/84
PERMIT NO. 95-84 ESTIMATED DATE OF START-UP 1934
DETERMINATION MADE BY MICHIGAN DNR GREGORY EDWARDS <517)-3£2-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION .... PCT EFF
__,-.______..___..____.. _ _ . __«.___v,H_»«__W» «.^ ._ _ _.-._ _., ______ _ ..»___ _ _ .»__ ___ .. _«__ _ _ _..-..._ _ _______ __ ._
SPRAY BOOTH, SOUND DEADENER 300.00 PARTS/H
VOC 78.5000 LB/H SEE NOTE LAER
108.0000 T/YR SEE NOTE
AIRLESS GUNS S TIMED SPRAYING
SPRAY BOOTH, REINFORCEMENT 300.00 PARTS/H
VOC 78.5000 LB/H SEE NOTE LAER
108.0000 T/YR SEE NOTE
AIRLESS GUNS 4 TIMED SPRAYING
NOTES
NOTE - EMISSION LIMITS ON VOC ARE FOR BOTH BOOTHS COMBINED.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 274 ID NUMBER MI-0035 SOURCE T»FE CC3E 4.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
SURFACE COATING - AUTO./LIGHT DUTY TRUCKS
75.00 CARS/H
COMPANY NAME/SITE LOCATION CHRYSLER CORP.
JEFFERSON AV. ASSEMBLY PLANT
DETROIT, MI 48226
WAYNE COUNTY
DETERMINATION IS LAER FOR A MODIFIED SOURCE.
PERMIT NO. C-5366 THRU C-5369
DETERMINATION MADE BY WAYNE COUNTY APCD
(AGENCY)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
AL SCHEANS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 06/05/80
ESTIMATED DATE OF START-UP 19SO
(313)-224-4693
(PHONE )
POLLUTANT EMISSION LIMITS ... t BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
TACK-OFF BOOTH
COLOR SPRAY BOOTH
COLOR FLASH-OFF BOOTH
DOUBLE-WIDTH OVEN
500000.00 SCFM
10000.00 SCFM
6663.00 SCFM
VOC
VOC
VOC
VOC
EXHAUST THRU SPRAY BOOTH
SEE NOTE
25.2000 LB/GAL APPL. SOL
12.9000 LB/GAL APPL. SOL
OVEN EXHAUST IHCIN.
LAER
LAER
90.00
NOTES
STAGED LAER CONCEPT PROVIDING FCR PHASE-IN OF NEW TECHNOLOGY AS IT IS DEVELOPED - PHASE 1, START UP USING LOW VOLTAGE ELECTROS
TATIC PAINT SPRAYING AND OVEN EXAUST INCINERATION; PHASE 2, INTRCDUCTICM CF HIGH VOLTAGE
ELECTROSTATIC PAINT SPRAYING; PHASE 3, INTRODUCTION OF HIGH SOLIDS TOPCOAT ENAMELS BY 8/31/83.
(*1 irDICATES DATUM WAS TRUNCATED F09 THIS TADLE.
PAGE G- 275
INITIAL REVIEW POST STARTUP
REVIEW STATUS'- 04/01/1SS3
ID N'JtSER MI-COC8
SO'JRCE TYPE CODE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE- SURFACE COATING - AUTO./LIGHT DUTY TRUCKS
COMPANY NAME/SITE LOCATION FHC CORP. - SAN JOSE ORDINANCE SAN JOSE, CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 06/22/82
PERMIT NO. 28310 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY BAY AREA AQMD BRIAN BATEMAN (415)-771-6000
(AGENCY) (AGENCY CONTACT PERSON)
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE
SURFACE COATING - AUTO./LIGHT DUTY TRUCKS
COMPANY NAME/SITE LOCATION F00 MOTOR CO.
MILAN PLASTICS PLANT
MILAN, MI
MONROE COUNTY
DETERMINATION IS LAER FOR A NEW SOURCE.
PERMIT NO. 447-454/79 + 456/79
DETERMINATION MADE BY MICHIGAN DNP
(AGENCY)
GREGORY EDWARDS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/01/80
ESTIMATED DATE OF START-UP 1985
(5171-322-1333
(PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
" _»__________ _ .. __ _ » __ _ .»_ _ __ _ _ ^ _«______.____ ,. __.__ fc_ _«... __ _.«.«_____ »__^,__-._ _ _ ______ _______ _ _ «.__.___.«,__
ELECTROSTATIC PAINT SYS.
VOC 457.5000 LB/H LAER
CATALYTIC INCINERATOR 95.00
ELECTROSTATIC SFRAY BOOTHS
COMPOUND MACHINES, DIRECTIONAL *
VOC 0.7400 LB/H LAER
CARBON ADSORPTION 90.00
VOC 9.0700 LB/H LAER
NONE
NOTES
INITIAL REVIEW POST STARTUP
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01;?933 03/13/19S4
PAGE G- 277 ID NUMBER MI-0017 SOURCE TYPE CODE 4.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE
SURFACE COATING - AUTO./LIGHT DUTY TRUCKS
60.00 TRUCKS/H
COMPANY NAME/SITE LOCATION G(1 WORLD WIDE TRUCK DIV
2601 WEST STROOP ROAD
MORAINE, OH 45439
MONTGOMERY COUNTY
DETERMINATION IS LAER FOR A NEW SOURCE.
PERMIT NO. 08-215
DETERMINATION MADE BY RAPCA - DAYTON,OH
(AGENCY)
GORBY LEE
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 05/13/80
ESTIMATED DATE OF START-UP 19S1
<513)-225-4435
(PHCNE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... 8 BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ELPO PRIME
PRIMER SURFACER
TOP COAT
ANTI-CORROSION
PLASTISOL/ANTI-CHIP
63.50 UNITS/H
63.50 UNITS/H
63.50 UNITS/H
63.50 UNITS/H
63.50 UNITS/H
VOC 1.2000 LB/GAL COATING MINUS H20
CATHODIC EDP
VOC 2.8800 LB/GAL COATING MINUS H20
15.8400 LB/G4.L VOC SOLIDS AFPL
WITH bZ7. TRANSFER EFFICIENCY
VOC 3.6000 LB/GAL COATING MINUS H20
15.0500 LB/GAL VOC SOLIDS AFPL
WITH 59X TRANSFER EFFICIENCY
VOC 4.3000 LB/GAL COATING MINUS H£0
WITH 90X TRANSFER EFFICIENCY
VOC 3.5000 LB/GAL COATING MINUS H£0
WITH 50X TRANSFER EFFICIENCY
LAER
LAER
LAER
LAER
LAER
PAGE G- 278
-------
(CONTINUED) GM WORLD HIDE TRUCK DIV
PROCESSES SUBJECT
TO THIS PERMIT
CHASSIS BLACK
WHEEL PAINT
MAST JACKET
FINAL REPAIR
THROUGHPUT
CAPACITY
63.50 JOB/H
63.50 JOB/H
63.50 JOB/H
63.50 JOB/H
POLLUTANT
EMITTED
VOC
VOC
VOC
VOC
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
3.5000 LB/GAL VOC MINUS HZO
3.7000 LB/GAL VOC MINUS HZO
6.3000 LB/GAL VOC MINUS H20
4.8000 LB/GAL VOC MINUS H20
...& BASIS
... PCT EFF
NOTES
MISCELLANEOUS FUGITIVE VOC EMISSIONS ARE ESTIMATED TO TOTAL 488 TPY FROM THIS FACILITY.
TOTAL VOC EMISSIONS NOT TO EXCEED 2050 TPY
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983 02/13/1934
PAGE G- 279 ID NUMBER OH-0009 SOURCE TYPE CC3E 4.3
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- SURFACE COATING - AUTO./LIGHT DUTY TRUCKS
COMPANY NAME/SITE LOCATION VOLKSWAGEN OF AM STERLING HEIGHTS, MI 48077
16 MILE ROAD t VAN DYKE AVENUE OAKLAND COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 06/01/80
PERMIT NO. 250-80 TO 273-60, 3* ESTIMATED DATE OF START-UP
DETERMINATION MADE BY MICHIGAN DNR JON TROUT (517)-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ __ __ ___-.-__ V . _ _> W _ _ _ . !_ _ -. ____. __w__ ~ __» « ___ _ ___»___-. «. »_____.__ - W .
PAINTING OPERATIONS
VOC SEE NOTE
SEE NOTES
NOTES
CHECK WITH STATE FOR DETAILS. EMISSION LIMITS TOO EXTENSIVE TO MENTION HERE.
INITIAL REVIEW POST STARTUP
(#) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEU STATUS: 04/01/1933 03/13/19&4
PAGE G- 280 ID NUMBER MI-0007 SC'JRCE TYPE CCDE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE SURFACE COATING - METAL FURNITURE
COMPANY NAME/SITE LOCATION KINCAID FURNITURE CO., INC. LENIOR, NC
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/17/83
PERMIT NO. 5276 ESTIMATED DATE OF START-UP 198*
DETERMINATION MADE BY NORTH CAROLINA DEM MIKE SEWELL (919)-733-7015
(AGENCY) (AGENCY CONTACT PERSON) (PHCNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
__-...__ _ __ _ .,___,. _ ______,.__ ___________ _ ____ _______ .,____ ,.__.. _ _
FINISHING OPERATION
voc
NONPHOTOCHEMICALLY REACTIVE FINISHING MATL.
BOILER, WOODWASTE, 2 11.60 MMBTU
VOC
GOOD OPERATING PRACTICES
NOTES
PSD ONLY FOR VOC EMISSIONS.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/19/19S4
PAGE G- 281 ID NUI'.BER NC-0031 SOURCE TYPE CODE 4.4
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE - SURFACE COATING - METAL FURNITURE
COMPANY NAME/SITE LOCATION STEELCASE, INC. GRAND RAPIDS, MI 49501
1120 36TH STREET KENT COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 06/01/80
PERMIT HO. 51-80 ESTIMATED DATE OF START-UP 1981
DETERMINATION MADE BY MICHIGAN DNR JOHN CAUDELL (517J-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, COAL FIRED, 2 EA
40000.00 LB/H
COAL t ASH HANDLING SYS.
PM 0.0500 LB/MMBTU
CYCLONE t BAGHOUSE
S02 1.6000 LB/MM3TU
LOW S COAL, MAX IX
NOX 0.6000 LB/MMSTU
CONTROL EXCESS * OVERFIRE AIR
PM 0.0300 GR/DSCF
FABRIC FILTER
DUST SUPFRESENT
99.00
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 282
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933 03/13/1954
ID NUMBER MI-0018
SOURCE TYPE CC3E
4.4
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE-
SURFACE COVTING - MAGNET WIRE
COMPANY NAME/SITE LOCATION PHELPS DODGE, MAGNET WIRE CORP.
P.O. BOX 768
HOPKINSVILLE, KY
CHRISTIAN COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT HO. C-75-16
DETERMINATION MADE BY KENTUCKY DAPC
(AGENCY)
BILL DILLS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 03/25/75
ESTIMVTED DATE OF START-UP 1976
(502J-5&4-33S2
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
OVENS,
OVENS, FINE WIRE, 10
1501.00 T/YR COATING
165.00 T/YR COATING
OVENS, 1 HEAVY & 1 MEDIAN WIRE 514.00 T/YR COATING
OVENS, 6 HEAVY ft 1 FINE WIRE 2158.00 T/YR COATING
OVEN, 1 FINE WIRE
16.00 T/YR COATING
VOC 40.8000 LB/H
675.4900 T/YR
INCINERATOR
VOC 4.5500 LB/H
19.1100 T/YR
INCINERATOR
VOC 13.9600 LB/H
58.6000 T/YR
INCINERATOR
VOC 31.3000 LB/H
85.9000 T/YR
CATALYTIC (1350 F), THERMAL INCINERATOR
VOC 0.4550 LB/H
1.9100 T/YR
90.00
90.00
90.00
BACT
95.CO
NOTES
(*) INDICATES DATUM UAS TRUNCATED FOR THIS TABLE.
PAGE G- 283 ID NUMBER KY-0035
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1
-------
ALSO COVERS PERMIT NUMBERS C-75-23, C-77-75, C-78-60, C-79-013.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE 6- 2S4
INITIAL REVIEW POST STARTUP
,'ic,; STATUS: 0^/01/1953 02/13/1934
ID NUMBER KY-0035
SOl'~CE TYPE CODE 4.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1964
SOURCE TYPE/SIZE SURFACE COATING - LARGE APPLIANCES
COMPANY NAME/SITE LOCATION SANYO E*E CORP. SAN DIEGO, CA 92123
400 RUFFIN RD.
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 08/21/81
PERMIT NO. 07037 ESTIMATED DATE OF START-UP 1979
DETERMINATION HADE BY SAN OIEGO APCO LORENZO ALEJANDRIA (619)-565-3914
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
COATING LINE 107.50 GAL/D
VOC 275.0000 G/LITER OF COATING BACT
HIGH SOL. COAT. TO LOW SOL. COAT..
NOTES
AVERAGE SOLVENT CONTENT OF COATINGS USED BEFORE MODIFICATION WAS 365.9 G/LITER, * AFTER MODIFICATION, THE SOLVENT CONTENT OF N
EW COATINGS IS 280 G/LITER (WITH 10X DEVIATION FOR UNSTAHDARDIZED TEST METHOD USED t AGREED BY APCD).
COATINS LINE INCLUDES ONE AUTOMATIC PAINT SFSAY BOOTH USING ELECTROSTATIC SPRAY DEVICES, TWO TOUCHUP SPRAY BOOTHS, ONE BAKING
OVEN.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 285
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
ID NUMBER CA-0043
SOURCE TYPE CODE
4.6
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE SURFACE COATING - MISC. METAL PARTS/PRODUCTS
COMPANY NAME/SITE LOCATION ALENCO DIVISION OF REDMAN BUILDING PROD* » TX
BRAZOS COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 04/17/81
PERMIT NO. C-6696 ESTIMATED DATE OF START-UP-- 1981
DETERMINATION MADE BY TEXAS ACB ART KELLOGG (5121-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . i BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
».« _-. __ _-.__ ____-. ____ .__-._.--. ._-.-. __.. _ -. __ -. -.-.-._ -. _ ___...._..__._..,.-...___...,._ ____-. _____-.____ ..
PAINTING EXTRUSIONS 384.00 LB/H PAINT *
VOC 65.1000 LB/H
DIRECT FLAME INCINERATION 6&.00
USE OF HIGH SOLIDS PAINT
NOTES
EFFICIENCY OF THE BAKE OVEN DIRECT FUME INCINERATION IS ESTIMATED TO BE A MINIMUM OF 68'/., PER FIG. Ill ON PG. 181 OF AP-40, B
UT IS THOUGHT TO BE GREATER. HOWEVER, NO SAMPLING WAS REQUIRED FOR THIS LOW EMISSION RATE.
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 05/04*934
PAGE G- 266 ID NUMBER TX-0129 SOURCE TYPE COOE 4.7
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE SURFACE COATING - MISC. METAL PARTS/PRODUCTS
COMPANY NAME/SITE LOCATION AMERICAN METAL DECORATING CO. FREMONT, CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/07/80
PERMIT NO. 27361 ESTIMATED DATE OF START-UP I960
DETERMINATION MADE BY BAY AREA AQMD JOHN PHILLIPS (415)-771-6000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- « »___. _ _«. -._ _ _ _ _ _ ,._ _
COATING LINE 91300.00 GAL/YR
VOC 250.0000 LB/D
FUME INCINERATOR 87.00
NOTES
FILE A 340-006
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 287
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/19/1934
ID NUM3ER CA-0053
SOURCE TYPE CODE 4.7
-------
tf
CO
(H
C\J
CJ
N
LO
O
ID
Z
HI
in
HI
_i
UJ
CJ
a.
**^
O
(0
a
UJ
M
t-
LJJ
O
1
1
X
M
C3
y
UJ
a.
a.
^
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
t
i
t
i
t
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
t
i
i
i
j
i
i
i
i
i
i
i
1 10
1 H
1 U
1 O
1 D
1 O
1 Ct
i a.
1 X
M in
II h-
ii o:
u <
n a.
n
n i
n <
II H-
II UJ
II £
II
II
II U
ii in
II HI
II TC.
u
n i
n
II CD
II Z
II HI
II \
II <
II O
II U
II
II UJ
ii U
II <
II U-
II tt
n ID
n in
n
n
n
n
n
u
ii
u
n
n i
n i
n i
II UJ
II M
M IH
II X
II UJ
II D.
II V
II t-
II
II UJ
II U
II tt
II ~%
II O
ii in
y.
L«
z
o
u
Ul
a
D
fj
X
0
i-H 1
1
D.
i :D
i i
UJ H-
o a
z <
3 In
in
in li-
nt p
1 UJ r4
HI H r-H
£ < r-
ct o in <
UJ ' 1 UJ
D. 0 rH 2
ui ui o
u. i -
Z CJ
«< 2
a: ui
CD
1^
«_,
UJ
O QJ
o; o v
0 < CJ
o z
in in uj
-
U CO
CO UJ
o
in r~ *<
M O £
Z M Z
O X O
HI HI
H. H-
Z Z Z
HI M
£ H. T.
UJ £ 01
H a H-
UJ UJ Ol
a a. o
n
u
i
n
u
u
u
n
n
n
n
u
u
n
u
u
n
i
n
n
u
u
n
u
n
n
i
n
n
u
n
n
u
n
n
n
n
n
u
u
u
n
n
i
u
it
u
u
ii
n
n
n
u
n
n
n
u
n
n
n
ii
n
n
n
n
n
n
n
u
n
u
u
i
n
n
n
n
u
n
i
u
t
t
i
i
i
i
n
u
n
n
n
n
n
n
n
n
i
i
i
u
n
u
n
n
n
n
n
u
n
n
n
u
n
n
n
n
n
u
n
u
u
n
n
n
n
n
n
n
n
in u.
M U-
in uj
CO t-
CJ
« a.
i ,
>
o
M
1-
U
HI
U.
HI
O
O
£
in
in
UJ
CJ
0
m
a.
K
O
h-
Z
UJ
1
3
cr
UJ
M '
t- -i
HI O
£ a.
H t-
1 Z
o
z o
HI
in
in
HI
£
UJ
t-
Z a
< UJ
} H>
O f
-I HI
-I £
O Ul
a.
K
f\ i
X HI
CD U
O <
O 0-
a: <
X CJ
H-
o
Ul
"1 H-
5 3~
in a
UJ
in a.
UJ
in en
in HI
UJ X
o H.
o
a: o
O. H-
o
o
o
o
tv
UJ
1-
_j in
HI in
U. UJ
_j
>- a.
K HI
x
tn -
S" 0
UJ
ID I-
<{
h- Ul
Z X
HI
O. K
Z
O M
HI <
H. Q.
N- UJ
in in
o <
CC <£l
H. S
or o ui
>- UJ H-
X -J <
t- UJ 3
0
o
-a-
f»s
8
CJ
.
in
x
H-
o
o
CO
V
o:
Q.
in
n
II UJ
II O
3
Ul M
HI CO
> O-
UJ i-l
o: x
H
-J O
< X
HI J-
I- O
HI
I UJ
I U
I K
I ZI3
I O
i in
in n
D u
I- n
< n
t- n
in M
3 !'
UJ II
M II
> II
UJ U
a n
n
n
n
n
II X
n i-
M
n tx
II UJ
II (O
*"~
CO
H-
in
ct
o
o
s
a:
h- II CO
< II CO
U II Cxi
l-l II
§11 I
II CD
HI II
II UJ
II CD
* II <
ii a.
-------
APPENDIX DETAILED SOURCE LISTING
___ 05/23/198*
SOURCE TYPE/SIZE SURFACE COATING - MISC. METAL PARTS/PRODUCTS 9.00 GAL/H
COMPANY NAME/SITE LOCATION SQUARE D CO. OXFORD, OH
5735 COLLEGE CORNER RD BUTLER COUNTY
-"" .. _ _ _ ., ___ __ «,_ __.. -_. . __ __ ,__...____ _ ..».»_ _..__ «_ ____._ ___._»,.__..___. __.»___.,_
DETERMINATION IS DATE OF PERMIT ISSUANCE 01/25/8*
PERMIT NO. 18-18* ESTIMATED DATE OF START-UP 193*
DETERMINATION MADE BY SOUTHWEST OHIO APCA THOMAS TUCKER t513)-251-8777
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
~ ~ _ ..____ .__,_ __ «,__ __ _,.____.____ _ __ __.. .._ ___.._ _ ,»_ _, _ ___..____.__»._...___
PAINT TANK, EOP 6000.00 SQF METAL/H
VOC 2.*000 LB/GAL COATING MINUS H20
1.0000 LB/GAU
WATERBASE COATINGS, ELECTRCDEFCSITION
SPRAY BOOTH, TOUCH-UP PAINT
VOC 2.*000 LB/GAL COATING MINUS H20
1.1*00 LB/GAL
WATERBASE COATINGS
NOTES
BACT DETERMINED BY TECHNOLOGY, ECONOMICS, S SOURCE SIZE.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 289 ID NUMBER OH-0060 SOURCE TYPE CODE *.7
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
SURFACE COATING - MISC. METAL PARTS/PRODUCTS
COMPANY NAME/SITE LOCATION TIFTON ALUMINUM CO.
DELHI, LA
RICHLAND PARISH
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. PSD-LA-514
DETERMINATION MADE BY LAQD/EPA REGION VI
(AGENCY)
BHARAT CONTRACTOR
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/10/8*
ESTIMATED DATE OF START-UP-- 19S4
(504)-342-840
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
PAINTING, AUTOMATIC BOOTH, 4 EA 13440.00 ACFM
PAINTING, TOUCH-UP BOOTH, 2 EA 9600.00 ACFM
OVEN, FLASH-OFF
OVEN, BAKE
980.00 ACFM
2870.00 ACFM
VOC 20.1000 LB/H
MAX 6.25 LB/GAL VOC CONT. FOR COATING
VOC 0.9000 LB/H
MAX 6.25 LB/GAL VOC CONT. FOR COATING
VOC 17.4000 LB/H
MAX 6.25 LB/GAL VQC CCNT. FOR COATING
VOC 75.6000 LB/H
MAX 6.25 LB/GAL VOC CONT. FOR COATING
BACT
BACT
BACT
BACT
NOTES
NO APPLICABLE NSPS, RACT, OR CTG. BACT IS BASED ON SURVEY OF ALL STATES IN US. THE BACT WILL BE RE- EVALUATED AFTER ONE YEAR 0
F ACTUAL OFERATICN.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 290
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER LA-0044
SOURCE TYPE CODE 4.7
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
___________.._ _____.______._..,»_____,.______.______________.,_______ ___ __. ;!__ :;;_ _ ___S~ ;r~x sm~~
SOURCE TYPE/SIZE SURFACE COATING - FLATWOOD PANELING 63300.00 SQFT/H
-. _ . _ _ _ «. ____ __ -,__-...___.-..__.._____ __-._____.. ___ ..__.,.________,___
COMPANY NAME/SITE LOCATION ABITIBI-PRICE CORP. TOLEDO, OH 43607
2900 HILL AVE
" " » - .-... . . ,... .._.». __....__.»,._...«._._
DETERHINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 07/07/83
PERMIT HO. 04-204 ESTIMATED DATE OF START-UP 1980
DETERHINATION MADE BY TOLEDO ENVIRONMENTAL SERVICE DALE KRYGIELSKI 1419J-693-0350
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FLATWOOD PANELING
63300.00 SQF/H
VOC 2.4000 LB/MSQFT CLASS II HB
5.3300 LB/MSQFT CLASS I TB
INCINERATION OF SOME VOC EMISSIONS
H£0 BASED COATINGS,LOW VOC HISH SOLIDS COATINGS
59.00
NOTES
FACILITY COATS EITHER HARDBOARD OR TILEBOARD BUT NOT BOTH AT THE SAME TIME. ORIGINAL PTI 04-108 ISSUED 01/78. REVISED PTI ISSU
EO 07/83. INCINERATION AND TOTAL SYSTEM EFFICIENCIES ARE LOWER ESTIMATES SINCE UNDETERMINED AHr.OUNTS OF
FLASHOFF EMISSIONS ARE USED TO COOL THE INCINERATOR EXHAUST. CLASS II HARDSOARD HAS 62.BY. CAPTURE EFFICIENCY AND 94.3+X INCINE
RATION EFFICIENCY. CLASS I TILEBOAKD HAS 57.2* CAPTURE EFFICIENCY AND 95.7+X INCINERATION EFFICENCY
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 291
INITIAL REVIEW POST STARTUP
REVIEW STATUS: C4/13/1964
ID NUMBER OH-0049A
S3l'RCE TYPE CODE
4.8
-------
APPENDIX DETAILED SOURCE LISTING
05/Z2/1984
SOURCE TYPE/SIZE SOLVENT DECREASING
- _ _... _ .. _ _ _ _ ..
COMPANY NAME/SITE LOCATION ALLOYTEK GRANDVILLE, MI
. -. _ _ _ __ ____ _
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/05/83
PERMIT NO. 258-83A ESTIMATED DATE OF START-UP 1933
DETERMINATION HADE BY MICHIGAN DNR DAVID FERRIER <517)-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHOSE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
VAPOR DE6REASER
VOC 8.0000 LB/H
REFRIG. FREEBOARD W/COVER DURING OWN TIME 95.00
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- Z1Z
ID NUMBER MI-0033
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 0<4/19/193<+
SOURCE TYPE CODE 4.9
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
» ~ s^ ~~~~rr~~~ ~~~~~~~ ~ ^ ~ ~ » w __..__....._.__...».___.. ,._ _,_ _ _
_ _ _ .__ _ _ ______.__ ____.,____ _ __________ ._ _ __., _ __ ..__ _., » _ ________ _ ___ __. __ _ ________ ~~_;T~_ ^~
SOURCE TYPE/SIZE- SOLVENT DECREASING
COMPANY NAME/SITE LOCATION BRIGGS « STRATTON CORP. MENOMONEE FALLS, WI
. . . __ .
DETERHINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 03/04/81
PERMIT NO. MAN-10-GEB-81-68-002 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY WISCONSIN DNR EMILIA ESTRADA (608)-266-024
-------
APPENDIX ~ DETAILED SOURCE LISTING
C5/2C/1964
SOURCE TYPE/SIZE SOLVENT DECREASING
COMPANY NAME/SITE LOCATION REGAL INTERNATIONAL, INC. > TX
-.___ __ _._ ___ _ _ ,.____...._.. .- _ _ _
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 09/22/82
PERMIT NO. X-3641 ESTIMATED DATE OF START-UP 1978
DETERMINATION MADE BY TEXAS ACS ART KELLOGG (512)-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
*.-
PAINT SPRAYIUS 49920.00 LB/YR
VOC 4.0000 T/YR
VAPOR DECREASING 18460.00 LB/YR
VOC 1.1500 T/YR
COOLING COILS
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 294
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 05/04/1954
ID NUMBER TX-0132
SOURCE TYPE CCDE
4.9
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE GRAPHIC ARTS
_,._-. _-- ____ __ __ ___ _ -_-.__.._____-.___.___.»____,._ _.,..____..____ ...- ..,.__.._..___.,..__
COMPANY NAME/SITE LOCATION BEMIS CARPHANE FILMS OSHKOSH, WI
--- __-_---__ -------------------- »-- ---«- -----.---- - --- __-_» -,_____._._»__.__. _.«._._,____.___
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/25/81
PERMIT NO. MAN-10-EYE-81-71-083 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY WISCONSIN DNR EMILIA ESTRADA (608)-266-0244
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
SARAN COATERS, 2 EA
VOC 0.3200 KG/L LAER
2.6700 LB/GAL
LOW SOLVENT COATING
NOTES
OFFSET FROM SHUTDOWN OF 814 LAMINATOR AT CURWOOD, NEW LONDON
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 295
INITIAL REVIEW POST STARTUP
REVIEW STATUS; ovoi-^sj
ID NUH3ER WI-0003
SOURCE TYPE CODE 4.12
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
GRAPHIC ARTS
COMPANY NAME/SITE LOCATION BEMIS CO.
OSHKOSH, WI
DETERMINATION IS LAER FOR A NEW SOURCE.
PERMIT NO. MAN-03-80-71-125
DETERMINATION HADE BY WISCONSIN DNR
(AGENCY)
EMILIA ESTRADA
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 11/13/80
ESTIMATED DATE OF START-UP
( PHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FLEXOGRAFHIC PRINTING PRESS *8
VOC 85.0000 7. REDUCTION LAER
LOW SOLVENT COATINGS
EXTRUSION COATER 89
VOC 0.0900 KG/L LAER
1.5600 LB/GAL
LOW SOLVENT COATINGS
LAMINATOR 816
VOC 0.1700 KG/L LAER
1.4300 LB/GAL
LOW SOLVENT COATINGS
NOTES
OFFSET FROM CLOSING 81 SARAN COATER « LAMINATOR Sll
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FCR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 296 ID NUMBER WI-0002 SOL'RCE TYPE CODE 4.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
GRAPHIC ARTS
COMPANY NAME/SITE LOCATION BEMIS SPECIALTY FILMS
OSHKOSH, HI
DETERMINATION IS LAER FOR A NEW SOURCE.
PERMIT NO. KAN-10-EYE-81-71-082
DETERMINATION MADE BY WISCONSIN DNR
(AGENCY)
EMILIA ESTRADA
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 12/21/81
ESTIMATED DATE OF START-UP
<608)-266-0244
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
... & BASIS
... PCT EFF
LAMINATOR 817
COATER S10
COATER *11
FLEXOPRESS COATER 82
VOC 0.0400 KG/I COATING
0.3300 LB/GAL
LOW SOLVENT COATINGS
VQC 0.0300 KG/L COATING
0.2500 LB/GAL
LOW SOLVENT COATINGS
VOC 0.2100 KG/L
1.7700 LB/GAL
LOU SOLVENT COATINGS
VOC 18.0000 7. VOC VOL. IN IKK
LOW SOLVENT COATINGS
LAER
LAER
LAER
LAER
NOTES
OFFSET FROM SHUTDOWN OF 814 LAMINATOR 4 82 SARAN COATER AT CURWOOD, NEW LONDON
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE 6- 297
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER WI-0004
SOURCE TYPE CCDE 4.12
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE GRAPHIC ARTS 102.00 GAL INK/H
_. .
COMPANY NAME/SITE LOCATION BROWN PRINTING ' FRANKLIN, KY 42134
P.O. BOX 451 SIMPSON COUNTY
______ _ _ _ _ __ __________ ______ _ --- --- ..-.
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 07/28/80
PERMIT NO. C-80-95 ESTIMATED DATE OF START-UP 1931
DETERMINATION MADE BY KENTUCKY DAPC BILL DILLS (502)-564-3382
(AGENCY) (AGENCY CONTACT PERSON) (PKOHE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ROTOGRAVURE PRINTING PRESS 102.00 GAL/H INK
VOC 102.0000 GAL/H INK LAER
CARBON ADSORPTION 97.00
NOTES
CHANGING THINNER USAGEi BUT LIMITING INK TO 102 GAL INK/HOUR. 7 UNITS, BACT/LAER WILL BE DETERMINED USING A PHASED APPROCH.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- £98
INITIAL REVIEW POST STARTUP
REVIEW STATUS-- 04/01/1933
ID NUMBER KY-0015
SOURCE TYPE CODE 4.12
-------
APPENDIX -- DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE GRAPHIC ARTS
COMPANY NAME/SITE LOCATION COLUMBUS COATED FABRICS COLUMBUS, OH
DETERMINATION IS LAER FOR A MODIFIED SOURCE. DVTE OF PERMIT ISSUANCE 04/29/81
PERMIT NO. 01-415 ESTIMATED DATE OF START-UP--
DETERMINATICN MADE BY OHIO EPA CD VICTOR FISHER (614)-864-3195
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROU3HPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
INTA-ROTO HL-41 PRINTER 7.00 MT1YD/YR
VOC 4.8000 LB/GAL VINYL « BACT
2.9000 LB/GAL INK
COAT COMPOSIT.<252 SOLV,BY VOL 70.00
NOTES
LIMITS IMPOSED BY PERMIT TO INSTALL, WHICH ALSO REQUIRES NEW PERMIT APPLICATION IF SOLVENT COMPOSITION OR SCHEDULE ARE CHANGED
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 299
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1033
ID NUM3ER OH-0033
SOURCE TYPE CODE 4.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE
GRAPHIC ARTS
360.00 T/YR
COMPANY NAME/SITE LOCATION CONTAINER CORP. OF AM
MUHCIE, IN
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. PC(18)1*77
DETERMINATION MADE BY INDIANA APCD
(AGENCY)
FRANK PROFIT
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/31/80
ESTIMATED DATE OF START-UP--
(317J-633-066*
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
ROTOGRAVURE PRINT PRESS
362.00 T/YR VOC
voc
36.0000 T/YR
FUME INCINERATOR
90.00
NOTES
OPERATES 62*0 MRS/YEAR
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 300
ID NUMBER IN-0018
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1°33
SOSJPCE TYPE CCOE *.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE GRAPHIC ARTS
COMPANY NAME/SITE LOCATION CPS INDUSTRIES
DETERMINATION IS LAER FOR A NEW SOURCE.
PERMIT NO. (REGION FILE NO.) FSD-TN-069
DETERMINATION MADE BY TENNESSEE APCO
(AGENCY)
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
CERUTTI & HELIX PRESSES, 5 1073.30 L8/H TOTAL
1073.30 LB/H
FRANKLIN, TN
DATE OF PERMIT
ESTIMATED DATE
ANN NIELSON ( 615)-741-3651
(AGENCY CONTACT PERSON) { PHOHE )
WILLIAMSON COUNTY
ISSUANCE--
OF START-UP
POLLUTANT EMISSION LIMITS ... t BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
VOC 128.1100 LB/H
SOLVENT REC. SYS & CARBON. BED
LAER
84.00
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 301
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID N'JIIBER TN-0005
SOURCE TYPE CODE 4.12
-------
APPENDIX DETAILED SOURCE LISTING
05/23/198*
SOURCE TYPE/SIZE GRAPHIC ARTS 2400.00 T/YR
COMPANY NAME/SITE LOCATION DIVERSIFIED PRINTING BACKSON, TN 37055
DICKSON CORAMY INDUSTRIAL PARK DICKSON COUNTY
DETERMINATION IS LAER FOR A NEH SOURCE. DATE OF PERMIT ISSUANCE 03/10/81
PERMIT NO. PSD-TN-069 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY TENNESSEE APCD ANGIE PITCOCK (615J-741-3651
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS .. . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
^ -- -- -. -- -- -. .-. -. . ..._ _,-- ___ ___» __.__,__»_._____.______._____._
PRINTING
VOC £400.0000 T/YR LAER
CARBON ADSORPTION 64.00
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 302
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
ID NUMBER TN-0002
SOURCE TYPE CODE 4.12
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE GRAPHIC ARTS 2000.00 FT/MIN
COMPANY NAME/SITE LOCATION R. J. R. ARCHER,INC. WINSTON-SALEM, NC
220 E. POLO RO
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-
PERMIT NO. 00466-0005-P ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY FCSSYTH COUNTY EKV. AFFAIRS KEITH TART (919)-7£7-8S60
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ROTOGRAVURE PRESS 2630.00 LB/H PAPER
VOC 341.0000 LB/H
CARBON ADSORB. SYS & RECOVERY SYS 69.00
NOTES
LOCAL PERMIT TO CONSTRUCT WAS NOT ISSUED. R.J.R. ARCHER, INC. REQUESTED TERMINATION OF PSD EVALUATION BECAUSE THEY CONTROLLED
THE MAJORITY OF THE EXISTING PLANT AND THE OFFSET GENERATED WOULD ELIMINATE THE REQUIREMENTS OF A PSD ANALYSIS.
INITIAL REVIEW POST STARTUP
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 303 ID NUMBER NC-0026 SOURCE TYPE COCE 4.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1 8<»
SOURCE TYPE/SIZE
GRAPHIC ARTS
3368.00 T/YR EA
COMPANY NAME/SITE LOCATION R.R. DONNELLEY & SONS CO.
MATTOON, IL
COLES COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. EPA-5-A-80-17
DETERMINATION MADE BY EPA REGION V
(AGENCY)
BONIFACE THAYIL
(AGENCY CONTACT PERSON)
PROCESSES SUBJECT
TO THIS PERMIT
DATE OF PERMIT ISSUANCE 03/18/80
ESTIMATED DATE OF START-UP 1931
(312)-8S6-6054
(PHONE)
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... 4 B4SIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION .'. '. PCT EFF
ROTOGRAVURE PRESSES, 2 EA
3368.00 T/YR
VOC 212.0000 T/YR
CARBON ABSORBER
BACT
"5.00
NOTES
OPERATING HOURS MAX. 7280 HRS/YR
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 304
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/ei.»_9S3 04/04/19S4
ID NUMBER IL-0002
SOLACE TYPE CODE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE GRAPHIC ARTS 5860.00 LB/H
COMPANY NAME/SITE LOCATION SOUTHWEST COLOR PRINTING CORP. , TX
ANGELINA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/22/82
PERMIT NO. C-9131 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY TEXAS ACS ART KELLOGG (7I3J-634-3357
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION .. . PCT EFF
« . . .,. __ _____,._ _*.__ _,_« __ __ __»»._ ,, __-, ___ ______ ». _ __ __ _, -, _ _ _*.___ _ _ ., _ _ _ _ .._ ___ v ^. _. ». v _«.«.__»^__ _»_»._
OFFSET PRINTERS, 2 5860.00 LB/H PRODUC*
VOC 204.0000 T/YR SEE NOTE
NOX 3.5000 T/YR SEE NOTE
NOTES
NOTE-THESE EMISSION LIMITS ARE WITHOUT CONTROLS. IN LIEU OF ADD-ON CONTROL DEVICES THIS SOURCE IS REQUIRED TO CONVERT TO HIGH-
SOLIDS OR WATER-BORNE INKS WHEN THEY ARE DEMONSTRATED TO BE SATISFACTORY FOR USE IN THE INDUSTRY.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 305
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER TX-0131
SOURCE TYPE CODE 4.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE
GRAPHIC ARTS
32.00 LB/H INK
COMPANY NAME/SITE LOCATION UNITED COLOR PRESS
351 GARVER RD
MONROE, OH
BUTLER COUNTY
DETERMINATION IS
PERMIT NO. 18-176
DETERMINATION MADE BY
SOUTHWEST OHIO APCA
(AGENCY)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
RAY SILBERNAGEL
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 09/17/83
ESTIMATED DATE OF START-UP-- 1983
1513)-251-S777
(PHCNE)
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
* BASIS
PCT EFF
OVEN i PRESS, TITAN
32.00 LB/H INK
VOC
90.0000 '/. CONTROL
CATALYTIC INCINERATOR
TECH
92.00
92XEDESTRUCTION~EFFICIENCY DEMONSTRATED, CAPTURE EFFICIENCY UNDETERMINED. THE SOURCE WAS MOVED FROM PREVIOUS LOCATION, TRIGGER
ING NEW SOURCE REVIEW REQUIREMENTS.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 306
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER OH-0061
SOURCE TYPE CODE 4.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE GRAPHIC ARTS
COMPANY NAME/SITE LOCATION WORLD COLOR PRESS SALEM, IL
MARION COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 01/13/82
PERMIT NO. C 80 10 0006 ESTIMATED DATE OF START-UP 1980
DETERMINATION MADE BY ILLINOIS EPA CHRIS ROMAINE (217 )-782-2113
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ROTOGRAVURE PRESSES
VOC 336.0000 T/YR BACT
CARBON ADSORPTION SYSTEM 94.00
OFFSET PRESSES
VCC 251.0000 T/YR BACT
AFTERBURNER SYSTEM 90.00
OR EQUIVALENT SYSTEM
NOTES
l.BACT RETROSPECTIVELY APPLIED WHEN PSD PROJECT BROUGHT TO LIGHT BY APPLICANT. 2.EFFECTIVENESS OF AFTERBURNERS FOR OFFSET PRES
SES IS BEIN3 INVESTIGATED WITH TRIAL PROGRAM ON ONE PRESS TO BE CONCLUDED 9/84. EVALUATING ADD ON
CONTROLS VS. REDUCTIONS ACHIEVED THROUGH REFORMULATION OF INK AND FOUNTAIN SOLUTION. LIMITS WILL BE ADJUSTED ACCORDINGLY.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 307
INITIAL REVIEW POST STARTUP
REVIEW STATUS: oPE CODE 4.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
- = = = = = = = = = = = r === = = r = = = === === = = = = = = = = === = = = = = = = = = = = : = === = = = = = = = = = = = = = = = = === = = = = = = = === = = ==== = _ = = = = = = = = = = = = = = = === = = = = = = _== = = :: = = = = = = = =
SOURCE TYPE/SIZE GRAPHIC ARTS 120.00 MMBTU/H
COMPANY NAME/SITE LOCATION H.F. HALL PRINTING CO. EVANS, GA
4310 EVANS TO LOCK RD
"~ """""* ~"~" ~" "" _ . _ __^_ .... _ __ -. ..._ -. -, _. _ «._
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF pERMIT ISSUANCE-- 10/04/82
PERMIT NO. 2754-036-8480 ESTIMATED DATE OF START-UP- 1981
DETERMINATION MADE BY GEORGIA EPD BILL FARRISEE <404)-656-4867
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
= = = = = = = r = = rr = = = = ;r = = = r = = : = = = r = = r = = = r = r = = = rr = = = = = = r = : = = ::: = r = = r = = = r = = = = = = r = = r = :: = r = = = =:: = r = r= = r === = = r = = = = r = = = = = r = = = = = = = = = = = = :::: = = = = = = = =
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILERS, 2
CARBON BED ADSORPTION UNIT
60.00 MMBTU/H
513.00 LB/H VOC
PM
S02
VOC
CO
NOX
0.1000 LB/MMBTU
BOILER DESIGN
246.0000 LB/H
O.SOOO LB/MKBTU
BOILER DESIGN
39.0000 LB/H
CARBON ADSORPTION SYSTEM
0.3000 LB/Mf-tBTU
BOILER DESIGN
NSPS
NSPS
LAER
95.00
NSPS
NOTES
PERMIT AMMENDED TO COVER TWO BOILERS INSTEAD OF THREE BOILERS IN ORIGINAL PERMIT AND TO COVER USE OF NO.6 FUEL (2 17. SULFUR) I
NSTEAO OF NO.6 FUEL ( . 9X SULFUR) IN ORIGINAL PERMIT.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 308
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
ID NUMBER GA-0013
SOURCE TYPE CODE 4.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
OTHER ORGANIC EVAPORATION LOSS
300.00 GAL TOPCOAT/D
COMPANY NAME/SITE LOCATION BROYHILL FURNITURE
NEWTON, NC
CATAKBA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. NC-035
DETERMINATION MADE BY NORTH CAROLINA DEN
(AGENCY)
MIKE SEWELL
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-
ESTIMATED DATE OF START-UP--
(919J-733-61E6
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
SPRAY BOOTHS
VOC 688.0000 T/YR
NONE
EQUIPMENT DESIGN & OPERATION
BACT
NOTES
11 SPRAY BOOTHS
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 309
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER NC-0014
SOURCE TYPE CODE
-------
*T* 3003 3dJU 33anOS
===============z=======r========r=z=============s=:
:S(UV1S M3IA33
tuutfvis isoa H3ZA3tt IVXIZHZ
esoo-HO itaeunN 01
OK -a
========
ansvi situ aoj oaiv3Mnai SVM Mtuva saivaxoHi c«>
HA/1 OOSZ't
3QA
M'OOOI
saaruxu nen 'asm SNUMU
*ON
JJ3 13d NOJ1V3IJIOOM SS330iU HO lNBWint)3 1CHUN03 03111113 JHI3VdV3 UWOgf SHU. Ol
szsva t sinm Nozsszua iwinmod ifuusnoiMi xaarons sassaaoaj
==s====r======r===============r=======s====z=zz========s==r========:
laNOHdl INOSlQd 13V1N03 A3N39V1 CA3N39V1
COS£-^99-t 912) 8ZQVN 3XZ 3riVO ONV13A3J13 18 3QTU
--dn-lOTlS JO 31VQ O31Vt4IlS3
~33wnssi iztraM jo itva -33dnos ION v au iova sx
OB H010S OS£*2
9»I*» NO 'S1H OHCUOaQ 'OS 9JM t HEWdZflba lN33S3OOmj MOX1V3O1
ssori NOiivaodVAa outran
-------
APPENDIX DETAILED SOURCE LISTING
__ _ 05/22/1984
SOURCE TYPE/SIZE OTHER ORGANIC EVAPORATION LOSS
COMPANY NAME/SITE LOCATION GUARDIAN INDUSTRIES CORP. , TX
NAVARRO COUNTY
" "" »-» «.__ ___ __ ,....*__ ...... .. _ _ _,.._ _ __ _ __ ».___ .... __ _ _ «..._ _..».__ ___.^__ ».«.___ ___________
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 06/C8/83
PERMIT NO. X-4293 ESTIMATED DATE OF START-UP 1933
DETERMINATION MADE BY TEXAS ACS ROBERT MAUEL (512)-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COATING APPLICATOR
VOC NONE
VACUUM SPUTTERING MACHINE
NOTES
(*) INDICATES DATUM WAS TRUNCATED F03 THIS TABLE.
PAGE G- 311
" TTTH REVIEW POST STARTUP
blATUS- 05/04/1934
C~_~_L T;"E CCDE 4.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE--- OTHER ORGANIC EVAPORATION LOSS
COMPANY NAME/SITE LOCATION MEREDITH CORP. DES MOINES, IA
_ _ ___ ..-._.. -. .. -. -. -. _ __ _ -. -. .._ _..
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 04/15/82
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION HADE BY EPA REGION VII STEVE KOVAC (816)-374-6525
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED . CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
. ____ _ _.. _-. -._ _._-. -.- ,_ _ . _ __., _ __ _,..-
ROTOGRAVURE PRINTING PRESS 1614.00 LB/H SOLVENT
VOC 16.0000 /. VOL SOLVENT USED
SOLVENT RECOVERY SYSTEM 95.00
FLEX03RAFHIC PRINTER
NOTES
THE FLEXOC-3AFHIC PRINTER SHALL NOT USE A RAW INK (OR RELATED COATING) WITH A RATIO OF VOC VOLUME CONTENT TO SOLIDS VOLUME CONT
ENT WHICH IS GREATER THAN 0.64 NOR SHALL RAW INK BE DILUTED WITH ANYTHING OTHER THAN WATER ADDITION.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 312
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER IA-0009
SOURCE TYPE CODE 4.14
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
OTHER ORGANIC EVAPORATION LOSS
COMPANY NAME/SITE LOCATION MR. SPA, INC.
CAMARILLO, CA
VENTURA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. 1240-1
DETERMINATION MADE BY VENTURA COUNTY APCD
(AGENCY)
KEITH DUVAL
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 09/08/83
ESTIMATED DATE OF START-UP 1983
(805)-654-2664
(FHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... « BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FIBERGLASS-POLYESTER RESIN APPL* 3093.00 LB/D RESIN
VOC
120.0000 LB/D
SEE NOTE
NOTES
FILE A 340-A013. INCREASE STYRENE CONTENT IN GEL COAT TO ELIMINATE NEED FOR ACETONE DILUTION, USE OF FILLER MATERIAL IN RESIN
FOR DISPLACEMENT, VAPOR SUPPRESENT IN RESIN.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 313
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/26,1934
ID NUMBER CA-0060
SOURCE TYPE CODE 4.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE OTHER ORGANIC EVAPORATION LOSS
COMPANY NAME/SITE LOCATION PPG INDUSTRIES, INC. CLEVELAND, OH 44111
3800 WEST 143 ST.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 01/06/84
PERMIT NO. 13/18/00/0101,SEE N* ESTIMATED DATE OF START-UP 19S4
DETERMINATION MADE BY CLEVELAND DAPC IKE HABIB (216)-664-3503
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
ENTIRE PLANT, SEE NOTE 82
VOC
THERMAL INCINERATOR SYSTEM 90.00
ODOR
THERMAL INCINERATOR SYSTEM 90.00
FUGITIVE EMISSIONS
PM 898.0000 T/YR
UNCONTROLLED
NOTES
NOTE - SOURCE * P001-P004, P008-P010, P013-P015, P017, P019-P022, P024- P029, P032, P033, P035-P040, P043-P046, 4 T116-T122. N
OTE S2 - INCLUDES SAND MILLS, ATTRITION HILLS, CCHLES 4 HCCKMEYER MIXERS, BATCH BLENDING TANKS,
TANK & TOTE BIN CLEANING BOOTHS.
INITIAL REVIEW POST STARTUP
(*> INDICATES DATUM KAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 314 ID NUMBER OH-0059 , SOURCE TYPE CCCE 4.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
OTHER ORGANIC EVAPORATION LOSS
COMPANY NAME/SITE LOCATION ROCKWELL INTERNATIONAL
TULSA, OK
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. T80-43
DETERMINATION MADE BY TULSA CITY-COUNTY HEALTH DEPT BILL GIBBONS
(AGENCY) (AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 07/08/80
ESTIMATED DATE OF START-UP 1981
(918)-744-1000
(PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS .. . « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
CHEM MASKANT ON ACFT SKINS NOTE *1
VOC 202.0000 T/YR UNCONT..NOTEB2
CARBON ADSORPTION 90.00
BOND PRIME, PRIME & ENAMEL COAT* NOTE #1
VOC 18.4000 T/YR UNCONT.,NOTE*2
3.4000 T/YR CONT.,NOTES2
CARBON ADSORPTION UNITS 80.00
NOTES
1) MASKANT & COATINGS RELATED TO COMMERCIAL AIRCRAFT BODY SECTION PRODUCTION, PERMIT LIMITS PRODUCTION TO 144 SHIP SETS PER YE
AR.
2) BATCH TYPE COATINGS OPERATIONS NEGATES MEANINGFUL HOURLY EMISSION RATE.
INITIAL REVIEW POST STARTUP
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/183
PAGE G- 315 , ID NUMBER OK-0012 SOURCE TYPE CODE 4.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE OTHER ORGANIC EVAPORATION LOSS
COMPANY NAME/SITE LOCATION SOLVENT RESOURCE RECOVERY WEST CARROLLTON, OH
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 07/07/82
PERMIT NO. 0857751346 P004 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY RAPCA - DAYTON,OH GORBY LEE (5131-225-4435
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... i B4SIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_«._, ___,. .__ _ _«._ _ ___ _ _~- ~ _ _ _«_ ___.. _ «__ m. ~ __ V ____.. ~ __ ~_- _»»____.*,__. «.__ -.» -! - ^ * _
DISTILLATION UNIT 300000.00 GAL/YR
VOC 1.2700 LB/D
0.1600 T/YR
CONDENSORS 99.99
NOTES
DISTILLATION UNIT IS OPERATED WITH CONDENSORS WHICH ARE 150X OF DESIGN CAPACITY.
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983 02/13/1934
PAGE G- 316 ID NUMBER OH-0044 SOURCE TYPE CODE 4.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE OTHER ORGANIC EVAPORATION LOSS
COMPANY NAME/SITE LOCATION U.S. AVIEX CO. MILES, MI 49120
1800 TERMINAL ROAD
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 10/14/83
PERMIT NO. 260-83 ESTIMATED DATE OF START-UP 19S3
DETERMINATION MADE BY MICHIGAN DNR ASAD KHAN (517)-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
CONTAMINATED GROUND WATER CLEAN* 200.00 GPfl
1,1* 16.9100 MG/CU METER
3 - 1000 CFM CAP. ADSORPTION UNITS 90.00
CAR* 5.3400 MG/CU METER
TRI* 2.6700 MS/CU METER
CHL* 0.0900 MG/CU METER
VOC 28.4700 MG/CU METER
NOTES
VOC DETERMINED BY BACT REQUIREMENTS PER STATE REGULATIONS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 317
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/19/1934
ID NUMBER MI-0034
SOURCE TYPE CODE 4.14
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1934
SOURCE TYPE/SIZE- PETROLEUM REFINING - SEPARATION 450.00 HMBTU/H
COMPANY NAME/SITE LOCATION ARCO PETROLEUM PROD. CO. CARSON, CA
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 04/06/79
PERMIT NO. (REGION FILE NO.) LA-78-17 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION IX RICK SUGAREK (415)-974-8058
(AGENCY) (AGENCY CONTACT PERSON) ( PHOS'E )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
DISTIL. UNIT, REPLACEMENT CRUDE 450.00 MMBTU/H HEA*
S02 800.0000 PPM S REFIN. GAS
0.2500 /. S FUEL OIL
SULFUR-IN-FUEL
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 318
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3 C4/C4/19S4
ID NUMBER CA-0017
SOURCE TYPE CC2E 5.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE PETROLEUM REFINING - SEPARATION
COMPANY NAME/SITE LOCATION GULF STATES OIL « REFINING CO. CORPUS CHRISTI, TX
NUECES COUNTY
«" -. -.*. -. ___._.._ ._._._ .*_..»___*._ _«.__. ..._...__..___ _____ _____ «_____ ..-._____ ,___ __ ____
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/04/80
PERMIT NO. 8452 ESTIMATED DATE OF START-UP 1981
DETERMINATION MADE BY TEXAS ACS STUART KEIL (5121-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATERS, 4 109.00 MMBTU/H
S02 32.9000 T/YR BACT
NONE - LOW SULFUR FUELS
NOX 19.5000 T/YR AP42
FUGITIVE EMISSIONS
VOC 3.1000 T/YR BACT
MONITORING * MAINTENANCE 75.00
VAC. COLUMN EJECTOR 16000.00 B/D FEED
VOC NONE
VAPORS TO FUEL SYSTEM 100.00
NOTES
VACUUM COLUMN VAPORS ROUTED TO FUEL SYSTEM, STEAM CONDENSATE TO DESALTER. CONSIDERED AS A CLOSED SYSTEM.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS'- OV01/1983
PAGE G- 319 ID NUMBER TX-0087: SOURCE TYPE CODE 5.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - SEPARATION 400.00 MHBTU/H
COMPANY NAME/SITE LOCATION THE DOW CHEMICAL CO. FREEPORT, TX
BRAZORIA COUNTY
_ _«. _______ _..____ ____»_.. _ -- ..____ ___ _____-,__ _____ __ . «, _-.-. __ .«... -.
DETERMINATION IS BACT DATE OF PERMIT ISSUANCE-- 13/03/81
PERMIT HO. (REGION FILE NO.) PSD-TX-405 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK 121""~~~~*"1~*"~~~""~~"
Z VACUUM DISTALL. UNITS, GAS 200.00 MMBTU/H EA
S02 0.0270 LB/MMBTU NSPS
LIMIT H2S TO 0.10 GR/DSCF
NOX 0.1200 LB/HMBTU BACT
COM. AIR CONT. BY BURN. DESIGN
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. _ _ -^'T"' <--T\^-: _^''01/19S3
PAGE G- 320 ID NUMBER TX-C019 SOURCE TYPE CODE 5.1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - CONVERSION 55000.00 BBL/D
COMPANY NAME/SITE LOCATION ASHLAND OIL, INC. LEACH, KY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/21/82
PERMIT HO. C-82-127 SEE NOTE ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY KENTUCKY DAPC BILL DILLS <502 )-564-3362
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
CRACKER, REDUCED CRUDE W/2 FB C*
800.00 MM3TU/H
PM 68.0000 LB/H
298.0000 T/YR
FABRIC FILTER
CO 300.0000 PPM
2234.0000 T/YR
AFTER BURNER
S02 250.0000 PPM
«(260.0000 T/YR
DRY LIME INJ.
NOX 0.2000 LB/MMBTU
713.0000 T/YR
VOC 65.0000 T/YR
PROCESS CHANGE
LAER
99.70
BACT
93.70
LAER
92.90
BACT
LAER
66.20
NOTES
NOTE C-62-127 WAS NOT A NSR/PSD PERMIT. IT MODIFIED FACILITIES BEING CONSTRUCTED UNDER PERMIT C-80-127 ISSUED 12/01/60 KHIC
H WAS BOTH NSR & PSD.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 321
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3 02/13/1964
ID NUMBER KY-0026
SOURCE TYPE CODE
5.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - CONVERSION
COMPANY NAME/SITE LOCATION CHAMPLIN PETROLEUM CO. WILMINGTON, CA
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/24/80
PERMIT NO. LA-79-05 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION IX LARRY BOWERMAN (415)-974-8213
(AGENCY) (AGENCY CONTACT PERSON) (PHOKE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
__w« ___.-__.. _____________.._.. ________..~_~ _ _.___«..____ . _ _ . . _..»___ ______ __ _. ___ _«___._ _ _ -.., i . ^ -, ___ . v ~_ ___ __
FCC UNIT 30000.00 BBL/D
S02 84.0000 LB/H 2H AV
56.0000 LB/H 24H AV
SULFLf? SCAVENGING ZEOLITE CATALYST
DESULFURIZATION OF FEED TO 0.2X S
ALKYLATION UNIT, HYDROFLUORIC A* 8500.00 BBL/D
S02 230.0000 MS/DSCM H2S
0.1000 GR/DSCF
SULFUR IN FUEL
CATALYTIC POLYMERIZATION UNIT 3500.00 BBL/D
S02 230.0000 MG/DSCM H2S
0.1000 GR/DSCF
SULFUR IN FUEL
NOTES
0.2X S FEED. -- FLUIDIZED CATALYTIC CRACKING UNIT
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01^,933 C<+/04/1?S4
PAGE G- 322 ID NUMBER CA-0016 SOURCE TYPE CCDE 5.2
-------
cn z
0 0
ro X
0 0
O H*
w ro
I-" 0
0 0
o r- r- r-
W 0 CO
I"J,^ ^ ij
ci :: T. C:
SB w o ro
\HX-I
ad c
CO OT
n cr
~n sj
Z
x
cn »
M m
Z x
n
n rn
C cn
m CO
r-
Q M
> XI
7. OT
CO >
a o
CO -4
x
rn
j>
^
m
S3
3
X
m
0
0
M
CO
X
<
0
XI
o
-t
m
-(
m
*
J>
O
o
o
1
CO
0
ro
o
t
o
w
ro
o
o r-
OT
1-1 ^
o ;:
,TJ UJ
~\ -H
0 C
co
n
-n
X
CO
f-f
z
n
C
m
r~
01
in
7.
CO
13
cn
Z
o
X
o
i-f
ro
o
o
r- i
O CO
*" ~c
Z "'
p ro
co
c
S3
Z
ft*
m
X
n
in
CO
CO
j»
M
S3
ro
j>
o
H
X
rn
j>
-<
rn
XI
X
m
O
CO
m
Z
m
X
a
XI
o
-4
XI
m
^
H
m
XI
XI
*
ro
VI
o
o
~f
ro
^
x
CO
0
o
a
w
w
o
o r-
ro
M -t
o r:
S3 CU
0 C
r/1
O
-n
x
ro
CO
M
Z
-n
C
r~
5
cn
Z
CO
o
cn
Z
o
X
o
f_<
ro
a
o
r~ r-
o 03
£ X
Z °?
p CD
CD
Z
»
m
X
O
m
CO
CO
>^
XI
03
J>
O
x n
m o
^, p^
-I m
m xi
XI
x
m
m -i
XI m
O XI
CO
m
Z
m
x
o
XI
o
H
m
^
-t
m
O
*
ro
ro -g
£ 09
0 O
0 O
§TJ
CP
~> ^
C C
x x
X X
CO Z
o o
ro X
o o
O M
ro c»
«o o
0 O
o r- r- r~
TO O CO
!-> X i: X
o :? z r:
S3 ro o 5>
C3 C d
CO 03
O C
n si
X ?
ro
cn 8»
M m
z x
0
"n m
C CO
rn cn
r*
G) M
> XI
cn
z ro
cn >
D o
CO -(
-H T3
o ^o
o
H O
X m
M CO
co cn
m
TI cn
m
xi cn
3 C
M ro
H (_
rn
O
H
^
n x
> XI
TI Q
> C
M X
-H T3
-< C
-H
T3
m o
3 r"
M |
H C
H H
m j>
H
m
3
M
cn
cn
M
O
o z
z r-
H M
S3 3
O M
r- -t
CO
rn
C
M
3
m
z
-H
0
XI
T3
S3
O
O
m
cn
CO
3
O
a
M
n
H
n
>
-i
M
O
Z
T3 »
n
H 03
j>
m cn
-n M
-n CO
n
n
n
n
n
n
n
H
u
n
n
n
n
ii
n
n
n
ii
i
i
n
i
i
i
i
i
i
i
i
i
i >
1 G*>
i m
l Z
i O
i -<
i
i
i
l
i
i
l
l
l
l
r
i
1
i
l
l
l ~
i >
1 Q
i m
1 Z
i n
i -<
i
i n
1 O
l Z
1 H
1 >
i n
1 H
i
1 TJ
l m
1 S3
i cn
1 O
i Z
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
1 TJ
1 X
1 O
1 Z
l m
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0-00
m rn m
H XI H
m 3 m
XI M XI
3 H 3
M M
Z Z Z
> O )>
-H -(
O -* O
Z XI Z
m
3 CT M
J» M CO
0 0
m Z CD
CO -n o
< M -»
r-
m n
Z xi
Q
-_-
m 3
T3 TJ O
> cn a
a 1-1
X) 1 TI
rn H M
x rn
M 1 0
O £
z o cn
CO O
5 i
O
m
H
0
^£
0
M
C/J
. rn O
M O) ^"
M H H
4> M m
^* "T
l > 0
vj H H
O- m
^J O TJ
i m
M a xi
3
*O "-^ M
e- rn H
O M
n cn
cn
CO C
-H >
53
-i m
i i
C 1
TJ
1 M
M
X
M
^4
X
09
M
n
o
3
T3
J>
z
r
3
m
X
cn
-l
m
r*
R
-H
M
"Z
TlS
XI 3
M TJ
< 1-
m M
XI Z
XI TJ
O m
§3
X O
cn i
o ft
|i
rn n
XI O
Z
n
o
XI
1
o
X
;O
H
CO
HI
V
3
g
m
O
m
CO
n
(~
2
**i
-<
CO
o
m
H
TJ
m
X
CO
H
N
m
1
1
1
TJ
m
H
XI
O
r-
m
§
XI
m
n
H
z
M
in
i
n
II TJ
II TJ
i m
: §
II M
II X
II
II 1
II 1
II
ii a
n m
II H
n >
II M
ii r-
ii m
i a
u
n cn
n O
" S
II XI
n n
n m
n
ii r~
II M
II tA
II H
II M
II Z
II G7
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
If
II
II
II
II
II
II
(1
II
II
II
II
II
II
II
II
II
II
II
II
II O
(i cn
II X
ii ro
n ro
II X
II H
II -O
n a
ii *
-------
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 324
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
10 NUMBER TX-OQ18
SOURCE TYPE CCDE 5.2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE PETROLEUM REFINING - CONVERSION 6100.00 BBL/D
~~ ---------- ----- - -- - - --- ---- - - -. - - -.- -_ ----_ -«. _-____.-. _«.._«___»._
COMPANY NAME/SITE LOCATION CHEVRON RICHMOND, CA
~~~»» - *- «_. »__ MV. __ ____ _ _______ _.__... ____ __ _____....__ __________ _____ _ _ _______ ___________ »_
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/06/81
PERMIT NO. 27803 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY BAY AREA AQMD JOHN SWANSON «tl5)-771-6000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FCC 61000.00 BPD
PM 10.0000 LB/H
240.0000 LB/D
2 PARALLEL ESP'S 94.00
NOTES
ESP COST $9600000. FILE A 350-009
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 325
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER CA-0045B
SC'JSCE TYPE CCDE 5.2
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
PETROLEUM REFINING - CONVERSION
45.00 MBPSD
COMPANY NAME/SITE LOCATION EXXON CO., USA/BAYWAY REFIN.
1400 PARK AVENUE
LINDEN, NJ 07036
UNION COUNTY
DETERMINATION IS B/L
PERMIT NO.
DETERMINATION MADE BY
EPA REGION II
(AGENCY)
LARRY KARAS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/27/80
ESTIMATED DATE OF START-UP--
(212)-264-953S
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
... t BASIS
... PCT EFF
PROCESS HEATER
HYDROFINER POWER FORMER
TASK AGE
FUGITIVE EMISSIONS
VOC 5.1000 T/YR LAER
02 ANALYZER/EFFICIENT COMBUSTION
NOX 1663.0000 T/YR BACT
CONVENTIONAL BURNERS
S02 195.4000 T/YR BACT
SCRUBBER & SULFUR PLANT
.1 GR/DSCF H2S-FLUEGAS/.5X S BY WT. FUEL OIL
VOC 2.5000 T/YR LAER
FURNACE BURNER
S02 4416.6000 T/YR BACT
3 CLAUS & 1 PARSON BEAVON UNITS
VOC 4.1000 T/YR LAER
EXT. FLOATING ROOF + DOUBLE SEAL
EXT. FLOAT. ROOF t 2 SEALS
VOC 203.0000 T/YR LAER
PROPER COflBUSTION
PROPER MAINTENANCE
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PA3E G- 326
ID NUMBER NJ-0001
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
SOURCE TYPE CODE 5.2
-------
NOTES
A NEW 45 MB/SD CATALYTIC REFORMING UNIT (POWER FORMER) WILL UPGRADE OCTANE LEVELS OF VIRGIN AND ICN NAPHTHAS.
INITIAL REVIEW POST STARTUP
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 0^/01/1933
PAGE G- 327 ID NUMBER NJ-0001 SOURCE TYPE CODE 5.Z
-------
APPENDIX DETAILED SOURCE LISTING
05/28/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - CONVERSION 1480.00 BPSD
COMPANY NAME/SITE LOCATION TEXAS OLEFINS CO. , TX
HARRIS COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERnlT ISSUANCE- 11/23/83
PERMIT NO. 9348 ESTIMATED DATE OF START-UP 19S4
DETERMINATION MADE BY TEXAS ACB . KAREN NEUMANN (BIZ 1-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... j BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . ..' PCT EFF
POLYMERIZATION UNIT 14SO.OO BPSD
VOC 54.8200 T/YR BACT
SEE NOTES
NOX 8.4700 T/YR BACT
LOW NOX BURNERS
CO 1.2600 T/YR BACT
PM 0.3500 T/YR
NOTES
SIC = 2869. VOC CONTROL PROVIDED BY VAPOR RECOVERY UNIT ON TOAOINS OPERATIONS/ DIRECTED MAINTENANCE CH VALVES, PUMPS, ETC / FL
ARES FOR UPSET EMISSIONS/ FLOATING ROOFS WITH SECONDARY SEALS ON TANKS.
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 328
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 05/04/1934
ID NUMBER TX-0140
SOURCE TYPE CODE
5.2
-------
APPENDIX - DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - CONVERSION 20000.00 MBBL/D
COMPANY NAME/SITE LOCATION UNITED REFINING CO. WARREN, PA
HARREN COUNTY
DETERMINATION IS B/L FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 01/25/80
PERMIT NO. 78PA14 ESTIMATED DATE OF START-UP 1980
DETERMINATION MADE BY EPA REGION III VERNON BUTLER (215J-597-2711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FCC UNIT
S02 350.0000 LB/H BACT
0.652 S FUEL OIL
REFORMER HEATER
S02 65.0000 LB/H BACT
IX S IN FUEL OIL
CLAUS PLANT
S02 BACT
REBOILER
S02 24.0000 LB/H NSPS
17. S FUEL OIL
NOTES
S02 EMISSIONS FROM FLUID CATALYTIC CRACKER UNIT, REFORMER HEATER, AND REBOILER IMPACT ON NON-ATTAINMENT AREA
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. KL.Ii.ii STATUS: CVQ1/19S3
PAGE G- 329 ' ID N'JTIBLR PA-CG16 Sw-'-CE TrPE CODE 5.2
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/82/198*
SOURCE TYPE/SIZE- PETROLEUM REFINING - TREATING
COMPANY NAME/SITE LOCATION ENDEVCO, INC. FOUKE, AR ,. , ,.,,-
ST. HWY 134 MILLER COUNTY
;
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE- 13/03/S1
PERMIT NO. AR-240M-1 ESTIMATED DATE OF START-UP- I960
DETERMINATION MADE BY EPA REGION VI TOM DIGGS < 214 J-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
DIETHANOLAMINE RECONCENTRATOR 60000.00 BTU/H
S02 0.1000 LB/H BACT
FIRINS OF NAT GAS
TRIETHYLENE GLYCOL 60000.00 BTU/H
S02 0.1000 LB/H BACT
FIRING OF NAT. GAS
INCIN. _.__
S02 460.0000 LB/H BACT
NO CONTROL,USED TO CONTROL H2S
NOTES
INITIAL REVIEW POST STARTUP
<*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS;__°_4/01/19S3
PAGE~G-~330"ID NUMBER AR-0003 SOURCE TYPE CODE 5.3
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
PETROLEUM REFINING - TREATING
2.00 MMSCFD
COMPANY NAME/SITE LOCATION OIL INTERNATIONAL LTD
OILMONT, MT
TOOLE COUNTY
DETERMINATION IS
PERMIT NO.
DETERMINATION MADE BY
STATE OF MONTANA
(AGENCY)
HARRY KELTZ
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 03/10/83
ESTIMATED DATE OF START-UP
( PHONE )
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
... & BASIS
... PCT EFF
INCINERATOR
2.00 MMSCFD
S02 57.0000 LB/H
2*9.0000 T/YR
INCINERATION
BACT
0.00
NOTES
50 WEEK/YR OPERATION - PLANT IS IN BASICALLY SAME LOCATION AS OLD PERMIT
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 331
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER MT-0003
SOURCE TYPE CODE 5.3
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
z = rzr = = z ~zrr = z = ~~cz __«_ -
SOURCE TYPE/SIZE - PETROLEUM REFINING - TREATING
COMPANY NAME/SITE LOCATION PACIFIC REFINING CORP. HERCULES, CA
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/38/63
PERMIT NO. 29180 ESTIMATED DATE OF START-UP 1986
DETERMINATION MADE BY BAY AREA AQMD LEONARD CLAYTON (415)-771-6000
(AGENCY) (AGENCY CONTACT PERSON) ( FHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICAT^4 ... PCT EFF
FUEL HANDLING, REFINERY FUEL GA* 500000.00 SCF/H
S02 50.0000 PPM H2S IN FUEL GAS BACT
DIGLYCOL AMINE SCRUB SYSTEM 80.00
FURNACE, REFORMING 275.00 MT1BTU/H
NOX 20.0000 PPM AT 3X 02 BACT
SCR & NH3 INJECTION 85.00
NOTES
SCR = SELECTIVE CATALYTIC REDUCTION
INITIAL REVIEW POST STARTUP
(*) IS-OICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/19/1934
PAGE G- 332 ID NUMBER CA-0056 SOURCE TYPE CCDE 5.3
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - TREATING 5.00 HP
COMPANY NAME/SITE LOCATION TOSCO CORP. MARTINEZ, CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 02/19/82
PERMIT NO. 27769 ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY BAY AREA AQMD JIM KARAS 1415 J-771-6COO
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
CENTRIFUGAL PUMPS 5.00 HP
VOC 500.0000 PPM
DOUBLE MECH. SEAL W/HEAVY SEAL OIL
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 333
ID NUMBER CA-0046
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 0^/01/1933
SOURCE TYPE C02E 5.3
-------
APPENDIX DETAILED SOURCE LISTING
05/2 2/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - FEEDSTOCK 10.80 MMGAL
COMPANY NAME/SITE LOCATION AMOCO OIL CO. WHITING, IN
__.» . ___ _____»_______ __,._.,_._,__._.._,_._,._._,_.._._._,_
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 02/27/81
PERMIT NO. PC (45) 1479 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY INDIANA APCD KEN KEARNEY (317)-633-0647
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
=========r=:=r===============r===r==================r=====r===r===r==============r====r====r=r============r====r===r==============
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. fc BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
STORAGE TANKS, GASOLINE 5.40 HKGAL
VOC LAER
WELDED TANKS & INT FLOAT ROOFS
NOTES
2 GASOLINE STORAGE TANKS
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 334
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NUMBER IN-0010
SOURCE TYPE CCDE 5.4
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE
PETROLEUM REFINING - FEEDSTOCK
COMPANY NAME/SITE LOCATION ARCO PIPELINE CO.
FT. MIFFLIN TERMINAL
TINICUM TOWNSHIP, PA
DELAWARE COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. 79PA24
DETERMINATION MADE BY EPA REGION III
(AGENCY)
BOB BUSZCZAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/18/80
ESTIMATED DATE OF START-UP 1981
(£15)-597-8186
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... $ BASIS
EMITTED CONTROL EtJUIPMENT OR PROCESS MODIFICATION . . . FCT EFF
STORAGE TANKS NO. 1
STORAGE TANKS NOS. 2, 13, 15
STORAGE TANKS NOS. 4, 12
STORAGE TANKS NOS. 9, 10
STORAGE TANKS NOS. 11, 14
10.00 MBBL
100.00 MBBL
150.00 MBBL
100.00 MBBL
100.00 MBBL
VOC 0.2700 LB/H
INTERNAL FLOATING ROOFS
VOC 1.6500 LB/H
INTERNAL FLOATING ROOFS
VOC 2.1600 LB/H
INTERNAL FLOATING ROOFS
VOC 1.3200 LB/H
INTERNAL FLOATING ROOFS
VOC 1.6100 LB/H
INTERNAL FLOATING RCOFS
BACT
BACT
BACT
BACT
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 335
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER PA-0010
SOURCE TYPE CODE 5.4
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - FEEDSTOCK
COMPANY NAME/SITE LOCATION VENTECH REFIN.
JCT. HWY 190 * RT. 105
KROTZ SPRINGS, LA 70750
ST. LAN-DRY PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-LA-278A
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
TOM DIGGS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 03/13/80
ESTIMATED DATE OF START-UP
(214>-767-159<+
(PHOKE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... « BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TANKS, 2EA
TANKS, 6EA
TANK
BARGE LOAD/UNLOAD
120000.00 BBL
55000.00 BBL
25000.00 BBL
VCC 0.8700 LB/H
DOUBLE SEALS
VOC 0.0200 LB/H
DOUBLE SEALS
VOC 0.3500 LB/H
DOUBLE SEALS
VOC 3.0200 L8/H
VAPOR COLLECTION k INCIN. SYS
BACT
BACT
BACT
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 336
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1?S3
ID NUMBER LA-0026
SC'J~CE TYPE CODE 5.4
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION ALLIED MATERIALS CORP.
RT. 66
STROUD, OK
LINCOLN COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSO-OK-344
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
BILL TAYLOR
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 09/30/81
ESTIMATED DATE OF START-UP 1931
(ai4)-767-1594
(FHOK'E)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... * BASIS
EMITTED CONTROL EQUIPMENT OP PROCESS MODIFICATION ... PCT EFF
WASTE INCINERATOR/HEAT RECOVERY*
56.00 MM3TU/H
S02
4.4300 LB/MMBTU
NONE APPLICABLE
BACT
NOTES
WASTE INCIN./HEAT RECOVERY UNIT.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 337
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
ID NUMBER OK-0007
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
" _. _ _ .-____.,_____ «.,__ _ _«_._....._.. __ ___ __. «.___ ___.. _«_ ... __-.__..__.__.._ ».^_.«»_..«_ _ ___ » .. __.
COMPANY NAME/SITE LOCATION AMERICAN PETROFINA CO. OF TEXAS , TX
JEFFERSON COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 01/21/83
PERMIT NO. SEE NOTE ESTIMATED DATE OF START-UP 1964
DETERMINATION MADE BY TEXAS ACS STUART KEIL (512 )-451-5711
fAGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
""" -. «.«.-. _. _ _-,_ -.__ __^_ __ _ _______ _..-._.»,».___.»____..___.._.._____
COMBUSTION UNITS
NOX 0.1200 LB/MMSTU GAS
0.3000 LB/MSAL LIQUID
STAGED COMBUSTION
NEW & EXISTING SRU'S
S02 250.0000 PFM NSPS
SCOT TAIL GAS CLEAN-UP
H2S NOTE «2
FUG. MONITOR & MAINTEN. FOR H2S PROCESS LEAKS
NOTES
NOTE -- PERMIT NO. C-9193,9194,9195,9196
NOTE 82 MININIZE FUGITIVES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUHCATED FOR THIS TABLE. Kcvit_,< SIAVUS: 05/0-»,'19o4
PAGE G- 333 ID NUMBER TX-0127 SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE -
PETROLEUM REFINING - AUXILIARY
130.00 MBPSD
COMPANY NAME/SITE LOCATION AMOCO
5TH AVE. S. TEXAS CITY
TEXAS CITY, TX
GALVESTON COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
FESMIT NO. (REGION FILE NO.) FSD-TX-402
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 12/08/81
ESTIMATED DATE OF START-UP
(214J-767-1594
(PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATERS, 12 EA 144.00 MMBTU/H
NOX
S02
SULFUR RECOVERY UNIT 1000.00 LT/0 SULFUR
NOX
so a
SRU FLARE 8.80 MMBTU/H
NOX
SOC
HYDROTREATER FLARES, 2 6.10 MMBTU/H EA
NOX
SOS
0.1200
0.0300
13.0000
250.0000
0.1200
0.0300
0.1200
0.0300
LB/MMBTU
LOW NOX BURNERS
LB/MM3TU
GAS FIRED
LB/H
EFFICIENT OPERATION
PFM
3-STAGE CLAUS UNIT
LB/MMBTU
EFFICIENT OPERATION
LB/MM3TU
GAS FIRED
LB/KM3TU
EFFICIENT OPERATION
LB/MJ1STU
BACT
NSPS
BACT
NSPS
99.90
BACT
NSPS
BACT
BACT
GAS FIRED
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 339
INITIAL REVIEW POST STARTUP
REVIEU STATUS; 04/01/1933
ID NUMBER TX-0020
SOURCE TYPE CC3E 5.5
-------
NOTES
H2S LIMITED TO 0.1 GRAIN/DSCF.
INITIAL PEVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: C-t/ 01/"i9S3
PAGE 6- 340 ID NUMBER TX-OOeO SGU"CE TtFE CC3E 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE
PETROLEUM REFINING - AUXILIARY
50000.00 BPSD
COMPANY NAME/SITE LOCATION AMOCO TEXAS REFINING CO.
2401 5TH AVENUE SOUTH
TEXAS CITY, TX 77490
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. TX-101
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK .
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE--
fSTIflATEO DATE OF START-UP-
<214>-767-1594
( PHCME )
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT 03 PROCESS MODIFICATION
... & BASIS
. .. PCT EFF
FURNACE, EXISTING PREHEAT
FURNACE, EXISTING REHEAT
FURNACE, EXISTING REHEAT
FURNACE, EXISTING HOT OIL
FURNACE, NEW DESULFURIZING
NOX 56.2000 LB/H
LOU NOX/HIGH COMBUST EFF BURN
NOX 63.2000 LB/H
LOW NOX/HIGH COMBUST EFF BURN
NOX 76.5000 LB/H
LOW NOX/HIGH COI18UST EFF BURN
NOX 47.9000 LB/H
LOW NOX/HIGH COMBUST EFF BURN
NOX 21.2000 LB/H
LC-i NOX/HIGH COr-JF.UST EFF 8L'.7M
BACT
BACT
BACT
EACT
BACT
NOTES
MODIFIED GASOLINE REFORMER TO PRODUCE GASOLINE OF LOU LEAD CONTENT. INCREASED REFORMER CHARGE RATE FPOM 49000 TO 5COOO ERL/STS
EAM DAY.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 341
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/C1/1<=33
ID NUMBER TX-0067
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION CALCASIEU REFIN. LAKE CHARLES, LA
CAUSIEU PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 07/23/81
PERMIT NO. (REGION FILE NO.) P5D-LA-293 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK - (214 )-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (FHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATERS, 3 EA 160.00 MMBTU/H
NOX 0.1100 LB/KMBTU BACT
LOW NOX BURNERS 35.00
INCIN. 2.00 MMBTU/H
NOX 0.1000 LB/MMBTU BACT
LOW NOX BURNERS 35.00
NOTES
THREE HEATERS AND ONE INCINERATOR
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/C1/1S83
PAGE G- 342 ID NUMBER LA-0019 SOURCE TYPE CODE 5.5
-------
APPENDIX - DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFININS - AUXILIARY 30000.00 BPSD
COMPANY NAME/SITE LOCATION CAROLINA REFINING & DIST SAVANNAH, GA
STATE HWY 21 CHATHAM COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE CF PERMIT ISSUANCE 09/10/80
PERMIT NO. GA 063 ESTIMATED DATE OF START-UP 1981
DETERMINATION MADE BY GEORGIA EPD BILL MITCHELL (404 )-656-6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION CHAMPLIN PETROLEUM CO. HOUSTON, TX 77002
1200 SMITH ST., SUITE 1900 NUECES COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 04/03/81
PERMIT NO. TX-337 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
PLATFORM CHARGE HEATERS, 3
392.00 MMBTU/H
HEATER, PLATFORMER DEPENTANIZER
25.20 MMBTU/H
502 9.9000 LB/H REFIN. GAS
0.0250 LB/MMSTU REFIN. GAS
TRACE H2S
NOX 47.0000 LB/H REFIN. GAS
0.1200 LB/MMSTU REFIN. GAS
AFR CONTROL, LNB
S02 112.7000 LB/H G/0
0.7600 LB/NMBTU G/0
TRACE H2S
NOX 67.3000 LB/H G/0
0.1700 LB/MMBTU G/0
AFR CONTROLS, LNB
S02 0.6000 LB/H REFIN. GAS
0.0250 LB/MH3TU REFIN. GAS
TRACE H2S
NOX 3.0000 LB/H REFIN. GAS
0.1200 LB/M"3TU REFIN. GAS
S02 17.5000 LB/H G/0
0.7600 LB/MMDTU G/0
TRACE H2S
NSPS
BACT
NSPS
BACT
NSFS
NSPS
PAGE G- 344
-------
NOX 4.4000 LB/H 6/0 BACT
0.1700 LB/MMBTU G/0
APR CONTROLS, LNB
PAGE G- 345
-------
(CONTINUED) CHAMPLIN PETROLEUM CO.
PROCESSES SUBJECT
TO THIS PERMIT
HEATER, PLATFORM AROMATIC
HEATER, HYDROTREATER CHARGE
REBOILER, HYDPOTREATER STRIPPER
THROUGHPUT POLLUTANT
CAPACITY EMITTED
£0.30 MMBTU/H
502
NOX
502
NOX
47.60 MMBTU/H
502
NOX
502
NOX
31.40 MMBTU/H
S02
NOX
S02
NOX
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.5000 LB/H REFIN. 6AS
0.0250 LB/MMBTU REFIN. GAS
TRACE H2S
2.4000 LB/H REFIN. GAS
0.1200 LB/MM3TU REFIN. GAS
APR CONTROL, LNB
13.8000 LB/H G/0
0.7600 LB/MM3TU G/0
TRACE H2S
3.5000 LB/H G/0
0.1700 LB/KMBTU G/0
AFR CONTROL, LNB
1.2000 LB/H REFIN. GAS
0.0250 LB/MM3TU REFIN. GAS
TRACE H2S
5.7000 LB/H REFIN. GAS
0.1200 LB/Ml'.BTU REFIN. SAS
AFR CONTROL, LN3
33.0000 LB/H G/0
0.7600 LB/MMBTU G/0
TRACE H2S
8.2000 LB/H G/0
0.1700 LB/MM3TU G/0
AFR CONTROL, LKB
0.8000 LB/H REFIN. GAS
0.0250 LB/MM3TU REFIN. GAS
TRACE H2S
3.8000 LB/H REFIN. GAS
0.1200 LB/r."STU REFIN. GAS
AFR CONTROLS, LKB
2.2000 LB/H G/0
0.7600 LB/MM3TU G/0
TRACE H2S
5.4000 LB/H G/0
0.1700 LB/MMBTU G/0
... t BASIS
... PCT EFF
NSPS
BACT
NSPS
BACT
NSPS
BACT
NSPS
BACT
NSPS
BACT
NSPS
BACT
PAGE G- 346
-------
AFR CONTROLS, LNB
PAGE 6- 347
-------
(CONTINUED) CHAMPLIN PETROLEUM CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
4 BASIS
FCT EFF
BOILERS, 3 (FUEL GAS ONLY)
47.00 MMBTU/H EA
EMERGENCY FLARE
16.00 SCFM
S02 1.2000 LB/H
0.0250 LB/MMBTU
TRACE H2S
NOX 5.6000 LB/H
0.1200 LB/MMBTU
AFR CONTROL, LNB
S02 0.1000 LB/H
NOME
NOX 0.1000 LB/H
STEAM INJECTION
NSPS
BACT
BACT
BACT
NOTES
FUEL OIL S CONTENT NOT SPECIFIED. PERMITTIE IS REQUIRED TO SAMPLE & ANALYZE S CONTENT OF FUEL OIL AT LEAST ON'CE/DAY TO DETERMI
NE COMPLIANCE WITH THE ALLOWABLE S02 EMISSION LIMITS. EMERGENCY FLARE OPERATED ONLY UNDER EMERGENCY CONDITIONS.
WHEN PROCESS GASES APE VENTED TO FLARE FOR MORE THAN 5 MIN. IN ANY 2 HOUR PERIOD, RECORDS SHALL BE KEPT FCR 2 YEARS FOLLCWINS
SUCH CCCURANCE. TRACE = <0.10 GR/DSCF. LNS = LOW KOX BURNERS. AFR CONTROLS =AIR/FUEL RATIO CONTROLS. G/0 = GAS/OIL MIX.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 348
INITIAL REVIEW POST STARTUP
REVIEW STATUS: C<+/01/133
ID NUMBER TX-0063
SOURCE TYPE CCDE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
=======================- 05/Z2/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 7000.00 GPCD
COMPANY NAME/SITE LOCATION CHEVRON USA REF. BASCAGOULA, MS
JACKSON COUNTY
" , ___,._ _______ _ __. .»___,_»___.,_ ___.._ _ __.». _ __»_ ___ __». _ _
°ATE °F PERMIT I«W«1«- «/"/80
DETERMINATION MADE BY MISSISSIPPI DK>, DWIGHT WILEY fSJES-SSS °? ^P^P"
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
-- = = = =r = r = r=r= = = r=rr = = ==== = r = r = = r = = r== = = = = = r = r = = = = = = = = = ==r::: = = = ==r = = :: = = r = = =:: = = = = = = :;: = = = = = = ===- =
TOTHpFT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
^THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
PROCESS EQUIPMENT 16000.00 GPCD
S02 0.1000 GR/DSCF NSPS
BEAVON S REM. PROC. TAIL GAS
LOW SULFUR
NOX 135.0000 PPM GAS BACT
DESIGN
NOTES
REVIEW sTATusHSSiH"If P°ST STARTUP
MS-0007 ~~~~~~~~~~
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - AUXILIARY
________« __.-._____ _ ______ ______ __ _«___i_ __ _» __ .. .»-... ..» -.-» » __ _ _ _ _..__-____,____ .-
COMPANY NAME/SITE LOCATION CHEVRON USA, INC. RICHMOND, CA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 04/08/83
PERMIT NO. 27797 ESTIMATED DATE OF START-UP-- 1984
DETERMINATION MADE BY BAY AREA AqMD JOHN SWANSON (415J-771-6000
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FURNACE 4
FURNACE 85
FURNACE 86
FURNACE 81
FURNACE 82
FUPNACE 83
57.00 MMBTU/H
18.00 MM3TU/H
15.00 MMBTU/H
12.50 MMBTU/H
19.00 MMBTU/H
66.50 MMBTU/H
NOX 40.0000 PPM K02
ONE SCR
NOX 40.0000 PPM N02
ONE SCR
NOX 40.0000 PPM N02
ONE SCR
NOX 40.0000 PPM N02
ONE SCR
NOX 40.0000 PPM N02
CNE SCR
NOX 40.0000 PPM K02
CNE SCR
AT 37. 02
UNIT ON FURNACES 4,5,6
AT 37. 02
UNIT ON FURNACES 4,5,6
AT 37. 02
UNIT ON FURNACES 4,5,6
AT 37. 02
UNIT ON FURNACES 1,2,3
AT 37. 02
UNIT ON FURNACES 1,2,3
AT 37. 02
UNIT ON FURNACES 1,2,3
PAGE G- 350
-------
(CONTINUED) CHEVRON USA, INC.
PROCESSES SUBJECT
TO THIS PERMIT
FURNACE »7
FURNACE «8
FURNACE 89
FURNACE S10
KinTP1;
THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MCDIFICATICN ... PCT EFF
22.00 MMBTU/H
NOX 40.0000 PPM
ONE
28.00 MMBTU/H
NOX 40.0000 PPM
ONE
26.00 MMBTU/H
NOX 40.0000 PPM
ONE
15.00 MMBTU/H
NOX 40.0000 PPM
ONE
N02
SCR
N02
SCR
NO 2
SCR
NO 2
SCR
AT "*,/. 02
UNIT ON FURN.
AT 3* 02
UNIT ON FURN.
AT 37. 02
UNIT ON FURN.
AT 37. 02
UNIT ON FURN.
7,8,9,10
7,8,9,10
7,8,9,10
7,8,9,10
SCR = SELECTIVE CATALYTIC REDUCTION, FURNACES ARE BURNING REFINERY MAKE GAS OF 1025 BTU/ACF
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 351
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER CA-0045
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION CITIES SERVICE CO. , LAKE CHARLES, LA 70602
P.O. BOX 1562
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 01/18/80
PERMIT HO. ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)~767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
REFORMER FURNACE, B-501,502,506* 198.50 MMBTU/H
REFORMER FURNACE, B-503,504,505* 536.90 MM3TU/H
C REFORMER, REGEN. VENT
A REFORMER FURNACE, B-102 - 106 93.10 MMBTU/H GAS
NOX
VOC
NOX
VOC
NOX
VOC
VOC
0.0030 LB/MM8TU
37.6000 LB/H
LOW NOX BURNERS « LEA FIRING
0.0030 LB/flfSTU
0.6000 LB/H
COM. CCNT. F. G. 02 METER
1
0.1900 LB/MMBTU
101.7000 LB/H
LCN NOX BURNERS
0.0030 LB/MM3TU
1.5000 LB/H
CCM. CONT. F.G. 02 METER
NONE
0.9000 LB/H
0.0100 M."3TU/H
NONE
BACT
BACT
BACT
BACT
BACT
PAGE G- 352
-------
NOX 34.5000 LB/H BACT
0.0400 LB/MM3TU
NONE
PAGE 6- 353
-------
(CONTINUED) CITIES SERVICE CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
,.. & BASIS
... FCT EFF
A REFORMER FURNACE, B-201
64.80 MMBTU/H
A REFORMER FURNACE, B-202
B REFORMER FURNACE, B-401
B REFORMER FURNACE, B-406
B REFORMER FURN4CE, B-402
53.00 HMBTU/H
60.40 MMBTU/H
57.30 MM3TU/H
55.90 MMBTU/H
NOX 14.2000 LB/H
0.0003 LB/MMBTU
NONE
VOC 0.2000 LB/H
0.0030 LB/MMBTU
NONE
NOX 11.6000 LB/H
0.0003 LB/MMBTU
NONE
VOC 0.2000 LB/H
0.0030 LB/MMBTU
NONE
NOX 13.2000 LB/H
0.0003 LB/MMBTU
NONE
VOC 0.2000 LB/H
0.0030 LB/MMBTU
NONE
NOX 12.6000 LB/H
0.0003 LB/MMBTU
NONE
VOC 0.2000 LB/H
0.0030 LB/MM3TU
NCNE
NOX 12.2000 LB/H
0.0003 LB/MMBTU
NONE
VOC 0.2000 LB/H
0.0030 LB/MMBTU
NONE
BACT
BACT
BACT
BACT
EACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 354
-------
(CONTINUED) CITIES SERVICE CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
...4 BASIS
,.. PCT EFF
B REFORMER FURNACE, B-403,404,4* 330.00 MMBTU/H
COKER FURNACE, B-101
COKER FURNACES, B-201
TOPPER FURNACE, B-2C
POWER HOUSE BOILER, B-3, B-3B
103.20 MMBTU/H
82.40 MMBTU/H
65.90 MMBTU/H
173.00 MMBTU/H GAS
NOX 50.8000 LB/H
0.2200 LB/MMBTU
NONE
VOC 2.3000 LB/H
0.0030 LB/MMBTU
NONE
NOX 23.7000 LB/H
0.0030 LB/MMBTU
NONE
VOC 0.3000 LB/H
0.0030 LB/MMBTU
NONE
NOX 18.0000 LB/H
0.2200 LB/MMBTU
NONE
VOC 0.2000 LB/H
0.0030 LB/MMBTU
NONE
NOX 14.4000 LB/H
0.2200 LB/MMBTU
NOME
VOC 0.2000 LB/H
0.0030 LB/MMBTU
NCNE
NOX 60.5000 LB/H
0.0050 LB/MMBTU
NCNE
VOC 0.9000 LB/H
0.0050 LB/f!M8TU
NONE
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 355
-------
(CONTINUED) CITIES SERVICE CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
- CAPACITY
POLLUTANT EMISSION LIMITS ... £ BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
POWER HOUSE BOILER, B-A3.3C
173.00 MMBTU/H
TANKAGE
REFINERY, MSC. SOURCES
COMPLEX COOLING TOWERS
NOX 60.5000 LB/H
0.3500 LB/MM3TU
NONE
VOC 0.9000 LB/H
0.0050 LB/MMBTU
NONE
VOC 581.7000 LB/H \
BACT FOR FUGITIVE'.HC
VOC 291.0000 LB/H
BACT FOR FUGITIVE HC
VOC 234.4000 LB/H
BACT FOR FUGITIVE HC
BACT
BACT
BACT
BACT
EACT
NOTES
REFINERY MODIFICATIONS INCLUDE: INSTALLATION OF NEW "C" REFORMER, REVISION OFREFINERY FUEL BALANCE, INSTALLATION OF AIR PREHEA
T AND FLUE GAS WASTE HEAT BOILERS FOR EMERGENCY CONSERVATION, CRUDE DISTILLATION COLUMN MODIFICATION,
AND CONVERSION OF CONE ROOF TANKS TO INTERNAL FLOATING PANS.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 356
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3
ID NUMBER LA-0033
SCL'^CE TYPE CCDE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION CLARK OIL CO., WOOD RIVER REFIN. HARTFORD, IL 62048
P.O. BOX 7 MADISON COUNTY
DATE OF PERMIT ISSUANCE- 09/25/81
DERMTTp Mnr *v T, , T.HTC ESTIMATED DATE OF START-UP- 1986
DETERMINATION MADE BY ILLINOIS EPA CHRIS RONAINE ( 217J-732-2U3
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
TOTUT SU3JECT THROUGHPUT POLLUTANT EMISSION LIMITS * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
PROCESS HEATERS
NOX 389.3000 T/YR
LCM NOX BURNERS
S02 1.0000 LB/MM3TU
BURNING BYPRODUCT GAS WITH OIL
PM 92.9000 T/YR
STORAGE TANKS C° 55-5°°° T/YR
VOC 70.2000 T/YR
NOTES -----------
NOX EMISSION LIMIT ON PROCESS HEATERS WILL BE SPECIFIED UPON SUBMISSION OF DETAILED ENGINEERING SPECIFICATIONS.
ALSO PERMIT NUMBER 119 050 AAA.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW ***
PAGE G" 357 10 NUMBER iL-0003
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION CLARK OIL, MT. AIRY REFINERY SARYVILLE, LA
ST. JOHN BAPTIST PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 12/22/83
PERMIT NO. PSD-LA-392 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY LAQD/EPA REGION VI BHARAT CONTRACTOR (50$)-342-3940
(AGENCY) (AGENCY CONTACT PERSON) ( PHOK'E )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
RECOVERY UNIT, SULFUR 12.00 LT/D
, S02 50.0000 LB/H B/A
CATALYTIC AFTER BURNER 96.00
NOTES
NSPS NOT APPLICABLE
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PA3E G- 358
INITIAL P^VIEW POST STARTUP
REVIEW STATUS--
ID NUH3ER LA-0045
SO'JPCE TYPE CCDE 5.5
-------
APPENDIX -- DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE-
PETROLEUM REFINING - AUXILIARY
225.00 MBPSO
COMPANY NAME/SITE LOCATION COASTAL STATES PETROLEUM
P.O. DRAWER 521
CORPUS CHRISTI, TX 78043
NUECES COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. TX-243
DETERMINATION HADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/14/80
ESTIMATED DATE OF START-UP--
(2141-767-1594
(PHCHE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
INCIN.
15.70 MMBTU/H
HEATER, COKER CHARGE
HEATER, FCCU FEED
113.00 MMBTU/H
65.00 MMBTU/H
NOX 2.3000 LB/H
0.1500 LB/MKBTU
LEA FIRING
CO 0.3000 LB/H
0.0200 LB/MM3TU
LEA FIRING
NOX 13.6000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 2.0400 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 7.8000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 1.1700 LB/H
O.OEOO LB/flMSTU
LEA FIRING
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 359
-------
(CONTINUED) COASTAL STATES PETROLEUM
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... * BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
REBOILER, ISOSTRIPPER
89.00 MMBTU/H
GAS OIL HDS HEATER
REBOILER, GAS OIL HDS
REBOILER, CRUDE UNIT
HEATER, VACUUM CHARGE
73.00 MMBTU/H
36.00 MMBTU/H
55.00 MMBTU/H
51.00 MM3TU/H
NOX 10.7000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 1.6000 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 8.8000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 1.3100 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 4.3000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 0.6500 LB/H
0.0200 LB/HMBTU
LEA FIRING
NOX 6.6000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 0.9900 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 5.4000 LB/H
0.1200 LB/KM3TU
LEA FIRING/LOW NOX BURNERS
CO 0.9200 LB/H
0.0£00 LB/MMBTU
LEA FIRING
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 360
-------
(CONTINUED) COASTAL STATES PETROLEUM
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... i BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ,.. PCT EFF
HEATER, CRUDE CHARGE
45.00 MMBTU/H
HEATER, TAIL GAS UNIT
HEATER, REFORMER
HEATER, NAPTHA HDS
HEATER, KEROSENE HDS
6.30 MMBTU/H
123.00 MMBTU/H
35.00 MMBTU/H
16.30 MMBTU/H
NOX 5.4000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 0.8100 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 0.8000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 0.1100 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 14.8000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 2.2200 LB/H
0.0200 LB/MM3TU
LEA FIRING
NOX 4.2000 LB/H
0.1200 LB/MMSTU
LEA FIRING/LOW NOX BURNERS
CO 0.6300 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 2.0000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 0.2900 LB/H
0.0200 LB/MMBTU
LEA FIRING
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 361
-------
(CONTINUED) COASTAL STATES PETROLEUM
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... t BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
REBOILER, KEROSENE HDS
12.50 MMBTU/H
HEATER, DIESEL HDS
REBOILER, DESIEL HDS
BOILER, UTILITY
BOILER, UTILITY
9.10 MMBTU/H
10.30 MMBTU/H
83.00 MMBTU/H
88.00 MMBTU/H
NOX 1.5000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 0.2300 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 1.1000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 0.1600 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 1.2000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 0.1800 LB/H
0.0200 LB/MMBTU
LEA FIRING
NOX 10.6000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 1.6000 LB/H
0.0200 LB/flMBTU
LEA FIRING
NOX 10.6000 LB/H
0.1200 LB/MMBTU
LEA FIRING/LOW NOX BURNERS
CO 1.6000 LB/H
0.0200 LB/MMBTU
LEA FIRING
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 362
-------
(CONTINUED) COASTAL STATES PETROLEUM
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
. -. -. -._ .._,»_,»,. ..__..,_ __.,___ __ ______ -.__-.»_ __*. _ _______ ___...«,_.._.. __.._-..._.__..___.._ «. _ «. ». __«.^^ __*_«. __^._« ___^-.___ w.^^.
REGENERATOR, FCCU
NOX 160.0000 LB/H BACT
NONE
CO 103.9000 LB/H BACT
HIGH TEMP. REGENERATION
NOTES
CAPACITY INCREASE FROM 185 TO 225 MBPSD.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 363 ID NUMBER TX-0066 SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - AUXILIARY
12000.00 BPSD
COMPANY NAME/SITE LOCATION CONOCO, INC.
LAKE CHARLES REFIN.
MESTLAKE, LA
CALCASIEU PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-LA-419
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BENHAM
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/08/81
ESTIMATED DATE OF START-UP-- 1982
(214)-767-1594
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... t BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATER, HDS CHARGE
REBOILER, HDS STRIPPER
HEATER, REFORMER CHARGE
HEATER, INTERPASS
HEATER, INTERPASS
39.00 MMBTU/H
39.00 MMBTU/H
52.00 MMBTU/H
46.00 MMBTU/H
37.00 MMBTU/H
NOX 0.1200 LB/MMBTU
LOW NOX BURNERS
LOW EXCESS AIR
NOX 0.1200 LB/MMBTU
LOW NOX BURNERS
, LOW EXCESS AIR
NOX 0.1200 LB/MMBTU
LOW NOX BURNERS
LOW EXCESS AIR
NOX 0.1200 LB/MMBTU
LCW NOX BURNERS
LOW EXCESS AIR
NOX 0.1200 LB/MMBTU
LOW NOX BURNERS
LOW EXCESS AIR
BACT
BACT
BACT
BACT
BACT
PAGE G- 364
-------
(CONTINUED) CONOCO, INC.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS ... ft BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
REBOILER, DEPROPANIZER
32.00 MMBTU/H
NOX O.ieOO LB/MMBTU
LOW NOX BURNERS
LOW EXCESS AIR
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 365
TMTTUl REVIEW POST STARTUP
REVIEW STATUS: 0
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE-
PETROLEUM REFININS - AUXILIARY
100000.00 BBL/D
COMPANY NAME/SITE LOCATION CONOCO, INC.
LAKE CHARLES REFIN.
WESTLAKE, LA
CALCASIEU PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-LA-390
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
TOM DIGGS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 08/10/81
ESTIMATED DATE OF START-UP 1933
(214)-767-1594
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
... i. BASIS
. .. PCT EFF
COKER HEATERS, 2 DELAYED REG.
99.00 MMBTU/H
HEATER, CRACKED DISTIL HYDRO OE* 16.00 MMBTU/H
HEATER, HEAVY VACUUM GAS OIL HY* 15.00 MMBTU/H
INCIN., SULFUR RECOVERY PLANT
9.68 MMBTU/H
NOX 0.1200 LB/MKBTU
LOW NOX BURNER
LOW EXCESS AIR
NOX 0.1200 LB/MMBTU
LOW NOX BURNER
LOW EXCESS AIR
NOX 0.1200 LB/MMBTU
LOW NOX BURNER
LOU EXCESS AIR
NOX 0.1200 LB/WBTU
LOW NOX BURNER
LOW EXCESS AIR
BACT
BACT
BACT
BACT
NOTES
<* FUEL GAS-HEATERS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 366 ID NUMBER LA-0010
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
SOURCE TYPE CODE 5.5
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - AUXILIARY
48000.00 BBU/D
COMPANY NAME/SITE LOCATION CRA.INC.
COFFEYVILLEt KS
MONTGOMERY COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MADE BY EPA REGION VII
(AGENCY)
DANIEL RODRIGUEZ
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 09/04/80
ESTIMATED DATE OF START-UP
(816)-3?4-6525
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT 03 PROCESS MODIFICATION
,.. & BASIS
. .. PCT EFF
HEATER, UNIT 40 (RETROFIT)
51.00 MHBTU/H
HEATER, UNIT 41 (BUILT, BUT NOT» 32.00 MMBTU/H
HEATER, UNIT 42 (RELOCATE) 136.00 MMBTU/H
HEATER, UNIT 43 (RELOCATE)
HEATER, UNIT 44 (NEW)
HEATER, UNIT 45 (NEW)
27.60 MHBTU/H
21.70 MM3TU/H
62.20 MMBTU/H
NOX 0.1300 LB/MMBTU
LOW NOX BURNERS
NOX 0.1500 LB/MMBTU
NOX 0.1600 LB/MMBTU
CONVENT. BURN W/AIR PREHEAT
NOX 0.1300 LB/MMBTU
LOW NOX BURNERS
NOX 0.1300 LB/MMBTU
LOW NOX BURNERS
NOX 0.1300 LB/MMBTU
LOW NOX BURNERS
BACT
BACT
BACT
BACT
BACT
BACT
NOTES
LIMITS FOR UNITS 42 4 43 WERE AMMENDED FROM 0.15 LB/KM5TU ON JULY 6, 1981. SIZE IS REFINERY CAPACITY. UNITS 41 & 42 EQUIPPTED
WITH CONVENTIONAL BURNERS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 367
INITIAL f^VIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER KS-0003
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/82/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 30000.00 BBL/D
COMPANY NAME/SITE LOCATION CYPRESS REFINING CO., HILL PETROLEUM CO. KROTZ SPRINGS, LA
ST. LANDRY PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 01/03/84
PERMIT NO. PSD-LA-504 ESTIMATED DATE OF START-UP 1932
DETERMINATION MADE BY LAQD/EPA REGION VI BHARAT CONTRACTOR (504)-3<*2-8940
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_..___«.__.. «. _-.._ _ ___ _»___-._»._«_«.. __ _ __ _ -, _-, .-.-._ , __ «,_-. _-._ _ ^_ _w____.__ _«._«.___«.___________
BOILER, Sl-82 99.50 MMBTU/H
NOX 15.3200 LB/H BACT
COMB. CONTRL W/02 MONITOR
VE 20.0000 y. OPACITY " BACT
COMB. CONTRL W/02 MONITOR
BOILER, #2-82 99.50 MMBTU/H
NOX 17.5100 LB/H ' BACT
COMB. CONTRL W/02 MONITOR
VE 20.0000 V. OPACITY BACT
COMB. CONTRL W/02 MONITOR
NOTES
BOTH BOILERS ARE FIRED WITH REFINERY FUEL GAS. BOTH BOILERS HAVE THE SAME RATED HEAT INPUT, HOWEVER, THE EMISSION RATES FOR NO
X ARE DIFFERENT DUE TO DIFFERENT FIRE BOX CONFIGURATION.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 368 ID NUMBER LA-0027A SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
=================== _ 05/22/19S4
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 60000.00 BBL/D
COMPANY NAME/SITE LOCATION DIAMOND SHAMROCK CORP. AMARILLO, TX 77173
BOX 631 MOORE COUNTY
DATE OF PERHIT ISSUANCE- 09/04/81
nFTFpMTNATTfiw M*nc nv c0. or-- ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK C214}-76?-159<*
(AGENCY! (AGENCY CONTACT PERSON) (FHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS 4 BASIS
______ CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
PROCESS BOILER, Z
FCCU REGEN STACK, 2
240.00 MM3TU/H
45000.00 BBL/D
S02 103.6700 LB/H
SCRUB FUEL G./.7X S FUEL OIL
NOX 130.0000 LB/H
LOW NOX BURNERS
CO 6.8100 LB/H
EFFICIENT COMBUSTION
PM 10.0600 LB/H
SCRUB FUEL S./.7X FUEL OIL
S02 931.5000 LB/H
NONE
NOX 24.4000 LB/H
HIGH TEMP REGENERATION
CO 195.0000 LB/H
HIGH TEMP RENERATION
PM 22.7000 LB/H
ESP
B/N
BACT
BACT
BACT
BACT
BACT
BACT
BACT
98.80
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 369
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER TX-0034
SCUPCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
*._ »-. * -.-.«. » _ -._ -. _-. _-.-. _ «__ -. __,._.. .._._-._.,...._..,_ _........«._..__,.__..___...___
COMPANY NAME/SITE LOCATION EXXON CHEMICAL AMERICAS BAYTOWN, TX 77520
HARRIS COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 07/30/81
PERMIT NO. (REGION FILE NO.) PSD-TX-302 ESTIMATED DATE OF START-UP 1984
DETERMINATION MADE BY EPA REGION VI TOM DIGGS (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- .._ .- _ _ _ ««.. ______ __ _.»__,«.__,., _ _.«.__,..»»...^_ w_ , __ ____ ______ __ «.«_v»«-.v»-<_..«>~ _« __,___»__«___«_ ..,..^ ^_«-,-_«.«_ .,,.^_
HEATERS, NAT. GAS-FIRED, 3 EA 275.00 MMBTU/H
NOX 0.2300 LB/MMBTU BACT
CONTROL OF EXCESS OXYGEN
NOTES
EPA ORIGINALLY SPECIFIED 0.12 LB/MMBTU AS BACT, BUT EXXON PROVIDED INFORMATION ON THE HEATER DESIGN AND TEST DATA ON SIMILIAR
HEATERS TO JUSTIFY THE NEED FOR0.23 LB/MMBTU.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 370
INITIAL REVIEW POST STARTUP
REVIEW STATUS: OVOl/1963
ID NUMBER TX-0046
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION EXXON CO, USA BENICIA, CA
__, «. __ ._».».__. . __ _ «_^ _ __ -.«. -. _
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/10/80
PERMIT NO. 27599 ESTIMATED DATE OF START-UP-- 1932
DETERMINATION MADE BY BAY AREA AQMD LEONARD CLAYTON (415)-7?l-6000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
.. __ ___._____»_ _ _ _ __ _ _ ____ ___ __., _ ____-._ ______>.___ ___ ___ __,-____. ..__ .__ _ -. . -- . ._____._ _ _ ___ _
FURNACE, REFINERY PROCESS 165.00 MfiBTU/H
NOX ^0.0000 PPM AT 3X 02
207.0000 LB/D
LOW NOX BURNERS & THERMAL DE-NOX 70.00
NOTES
DEMONSTRATED TECHNOLOGY. FILE A 310-010
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 371
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/19/1934
ID NUMBER CA-0057
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1964
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 30000.00 BPSD
______ _ _ .. _ __ _____________ _ _ __ _..____ __ .».._ _ .... , . .-. ~ . . ». .*-
COMPANY NAME/SITE LOCATION FRIENDSWOOD REFIN. HOUSTON, TX
CHOATE ROAD HARRIS COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 06/30/81
PERMIT MO. (REGION FILE NO.) PSD-TX-387 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (2141-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATERS, 4
75.00 MMBTU/H
BOILER
40.00 MMBTU/H
SULFUR RECOVERY UNIT
PM 0.0042 LB/MMBTU
GAS FIRED
S02 0.0224 LB/MMBTU
REFINERY GAS FIRED
NOX 0.1000 LB/MMBTU
LOW NOX BURNERS
CO 0.0142 LB/MKBTU
EFFICIENT COMBUSTION
PM 0.0042 LB/MM3TU
GAS FIRED
S02 0.0214 LB/MMBTU
REFINERY GAS FIRED
NOX 0.1000 LB/MMBTU
LOW NOX BURNERS
CO 0.0142 LB/TMSTU
EFFICIENT COMBUSTION
S02 9.1500 LB/H
CLAUS PLANT
BACT
KSPS
BACT
BACT
BACT
NS~S
EiCT
BACT
BACT
9.00
PAGE G- 372
-------
(CONTINUED) FRIENDSWOOD REFIN.
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
.
FCCU REGENERATOR
PM Z
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 350.00 MMBTU/H
COMPANY NAME/SITE LOCATION GETTY OIL CO. BAKERSFIELD, CA 93308
ROUTE 1, BOX 197-X
_ ____-._____ __-.___ -._ ..... ~ ___~ ___~_ _,_ __«_. __ __ ___ _ __«. _ _,- _ _ ^ ~ ,.. _ __.._ __ v __«. _ _.,_«__-»«_w_.__ ««
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 08/24/8Z
PERMIT NO. SJ-81-11 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION IX JOE SLAMOVICH (415J-974-S235
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
WIKAW > ._VB*M__*»«M_wb_v-»-~ _ >. .._._».___ -. ___«.»««»««.. ,«.i_ «.» _.-._ -. ^ -. «. »
STEAM GENERATOR, 7 240.00 B3L/D
NOX 0.1500 LB/MMBTU PER GEN.
AMMONIA INJECTION 63.00
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 374
ID NUMBER CA-0030
INITIAL REVIEW POST STARTUP
VICrt' STATUS: C-t/ul/lcS3 04/04/1934
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
rr======r===r================================r-=---__-_-_-_-____=___.__^
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 350000.00 BPSD
COMPANY NAME/SITE LOCATION 6000 HOPE REFIN., INC. 6000 HOPE, LA 70079
P.O. BOX 126, 257 PROSPECT AV* ST. CHARLES PARISH
"" - - -» «. __,^«.^.__-,^»..«._ _ _^.__ __ _ _ »__ ^__»___.___,,.__ _ ._ _______ __ _ _ _ _«.«,__ ________
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/08/81
PERMIT NO. ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214>-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
STRIPPER REBOILER
26.00 MMBTU/H
REFORMER STABILIZER
26.00 MMBTU/H
PM 0.3000 LB/H
0.0110 LB/MMBTU
GASEOUS FUEL
S02 0.5000 LB/H
0.0190 LB/MM3TU
0.10 GRH2S/DSCF
NOX 3.1000 LB/H
0.1200 LB/MM3TU
LOW NOX BURNERS, LEA FIRING
CO 0.4000 LB/H
0.0140 LB/MMBTU
COMBUSTION CONTROL
PM 0.3000 LB/H
0.0110 LB/MMBTU
GASEOUS FUEL
S02 0.5000 LB/H
0.0190 LB/MMBTU
0.10 GRH2S/DSCF
NOX 3.1000 LB/H
0.1200 LB/MMBTU
BACT
NSPS
BACT
BACT
BACT
NSPS
BACT
PAGE G- 375
-------
LOW NOX BURNERS, LEA FIRtNS
CO 0.4000 LB/H BACT
0.0140 LB/MHBTU
COMBUSTION CONTROL
PAGE 6- 376
-------
(CONTINUED) GOOD HOPE REFIN., INC.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... 4 BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
CRUDE HEATER
317.00 MMBTU/H
FCCU FURNACE
45.00 MMBTU/H
FCCU FURNACE
39.00 MMBTU/H
PM 3.4000 LB/H
0.0110 LB/MMBTU
GASEOUS FUEL
S02 6.1000 LB/H
0.0190 LB/MMBTU
0.10 GRH2S/DSCF
NOX 38.0000 LB/H
0.1200 LB/MMBTU
LOW NOX BURNERS, LEA FIRING
CO 4.5000 LB/H
0.0140 LB/MM3TU
COMBUSTION CONTROL
PM 0.5000 LB/H
0.0110 LB/MMBTU
GASEOUS FUEL
302 0.9000 LB/H
0.0190 LB/MMBTU
0.10 GRH2S/DSCF
NOX 5.4000 LB/H
0.1200 LB/MMBTU
LOW NOX BURNERS, LEA FIRING
CO 0.6000 LB/H
0.0140 LB/MMBTU
COMBUSTION CONTROL
PM 0.4000 LB/H
0.0110 LB/MMBTU
GASECUS FUEL
S02 0.7000 LB/H
0.0190 LB/MMBTU
0.10 GRH2S/DSCF
NOX 4.7000 LB/H
0.1200 LB/MMBTU
LOW NOX BURNERS, LEA FIRING
CO 0.6000 LB/H
0.0140 LB/MMBTU
BACT
NSPS
BACT
BACT
BACT
NSPS
BACT
BACT
BACT
NSPS
BACT
BACT
PAGE G- 377
-------
COMBUSTION CONTROL
PAGE 6- 378
-------
(CONTINUED) GOOD HOPE REFIN., INC.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
... ft BASIS
... PCT EFF
VACUUM COLUMN FURNACE
244.00 MMBTU/H
DEMEX HEATER
25.00 MKBTU/H
VISEBREAKING FURNACE, 3 EA
40.00 MMBTU/H
PM 2.6000 LB/H
0.0110 LB/MMBTU
GASEOUS FUEL
S02 4.7000 LB/H
0.0190 LB/MMBTU
0.10 GRH2S/DSCF
NOX 29.3000 LB/H
0.1200 LB/MHBTU
LOW NOX BURNERS, LEA FIRING
CO 3.5000 LB/H
0.0140 LB/MMBTU
COMBUSTION CONTROL
PM 0.3000 LB/H
0.0110 LB/MMBTU
GASEOUS FUEL
S02 0.5000 LB/H
0.0190 LB/MtlBTU
0.10 GRH2S/DSCF
NOX 3.0000 LB/H
0.1200 LB/MMBTU
LOW NOX BURNERS, LEA FIRING
CO 0.4000 LB/H
0.0140 LB/MMBTU
COMBUSTION CONTROL
PM 0.4000 LB/H
0.0110 LB/MMBTU
GASEOUS FUEL
S02 0.8000 LB/H
0.0190 LB/MMBTU
0.10 GRH2S/DSCF
NOX 4.6000 LB/H
0.1200 LB/MHBTU
LOW NOX BURNERS, LEA FIRING
CO 0.6000 LB/H
0.0140 LB/MMBTU
BACT
NSPS
BACT
BACT
BACT
NSPS
BACT
BACT
BACT
NSPS
BACT
BACT
PAGE G- 379
-------
COMBUSTION CONTROL
PAGE G- 380
-------
(CONTINUED) GOOD HOPE REFIN., INC.
PROCESSES SUBJECT
TO THIS PERMIT
FCCU REGENERATOR
SULFUR PLANT INCIN.
THROUGHPUT POLLUTANT
CAPACITY EMITTED
82000.00 BBL/D
PM
S02
NOX
CO
S02
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
64.9000 LB/H
THIRD-STAGE CYCLONE SEPARATOR
761.7000 LB/H
SULFUR REDUCTION CATALYST
242.6000 LB/H
LEA FIRING
138.6000 LB/H
COMBUSTION CONTROL
12.8000 LB/H
TAIL-GAS TREATMENT (SCOT)
... ft BASIS
... PCT EFF
NSPS
95.00
BACT
BACT
NSPS
NSPS
93.00
NOTES
<») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
= = = = r:::::r = :: = = = = = = = = = = : = - = = = = = = = = : = = r = = = = = = = = = = = = = = :
PAGE G- 301
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER LA-0032
SOURCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
£ £ ~z:~~~~ ~ ~ ~ ~~ ~ ~ ~ ~
~z: ~~~~ ~~~ ~ ~ ~ ~
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION GULF OIL CO. PORT ARTHUR, TX 77640 ,.,
20 M SE BEAUMONT H 73 JEFFERSON COUNTY
_ _ ., ___ .. _ _ _ _,» .. - ____ .. .._ « -
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/13/81
PERMIT NO. (REGION FILE NO.) PSQ-TX-214 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK < 214 )-767-159"+ v
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
==:================r===:===rr:===:======r========:=r==r===r===r=======r===========rrrrr====^2=====================================
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATERS, 4 EA
£(25.00 MMBTU/H
TREATING UNIT, SCOT TAIL GAS
NOX 0.3000 LB/MMBTU
AIR/FUEL RATIO
S02 0.5800 LB/^3TU
LOW SULFUR FUEL ( .5 7. S)
CO 0.0370 LB/MMSTU
EFFICIENT COMBUSTION
PM 0.0580 LB/MK3TU
EFFICIENT COMBUSTION
S02 70.4000 LB/H
DESULFURIZED FUEL
BACT
NSPS
BACT
BACT
NSPS
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 3S2
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER TX-0049
SOURCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION GULF OIL CO.
P.O. BOX 701
PORT AURTHER, TX 77640
JEFFERSON COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. TX-342
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 10/21/80
ESTIMATED DATE OF START-UP--
(214J-767-1594
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
SOLVENT EXTRACTION UNIT 81843
LUBE VACUUM UNIT *147
GULFINING UNIT 3243
THROUGHPUT POLLUTANT
CAPACITY EMITTED
122.30 MMBTU/H
S02
NOX
124.30 MMBTU/H
S02
NOX
66.70 MMBTU/H
S02
NOX
: = = = = = r = rr = - = rr = r = = =rrrr = r:rrr = rr = = = = r = r = r = = r^: = = r = = rrr
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
2.0000 LB/H
0.0200 LB/MM3TU
NAT. GAS/REFIN. GAS, TRACE H2S
14.6700 LB/H
0.1200 LB/MMBTU
LEA CONTROLS, LN5
72.3000 LB/H
0.6000 LB/HMSTU
NAT. GAS/REFIN. GAS, TRACE H2S
37.3000 LB/H
0.3000 LB/W1BTU
LEA CONTROLS, LN3
38.3000 LB/MM3TU
0.6000 LB/H
NAT. GAS/REFIN. GAS, TRACE H2S
20.0000 LB/H
0.3000 LB/MMBTU
LEA CONTROLS, LNB
... & BASIS
. . . PCT EFF
NSPS
BACT
NSPS
BACT
NSPS
BACT
PAGE G- 383
-------
(CONTINUED) GULF OIL CO.
PROCESSES SUBJECT
TO THIS PERMIT
CATALYTIC DEWAXING UNIT #1944
SULFUR RECOVERY UNIT 8544
SOLVENT DEWAXING UNIT
SOLVENT DEWAXING UNIT 81943
GULFINING UNIT 8244
THROUGHPUT POLLUTANT
CAPACITY EMITTED
20.00 MMBTU/H
S02
NOX
15.70 MMBTU/H
S02
NOX
100.10 MMBTU/H
S02
^
NOX
35.60 MMBTU/H
S02
NOX
60.00 MMBTU/H
S02
NOX
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATICN
11.6000 LB/H
0.6000 LB/MMBTU
NAT. GAS/REFIN. GAS, TRACE H2S
6.0000 LB/H
0.3000 LB/MMBTU
LEA CONTROLS, TRACE H2S
45.0000 LB/H
NAT. GAS FIRED
1.9000 LB/H
LEA CONTROLS, LNB
3.0000 LB/H
0.03"00 LB/MMBTU
NAT. GAS/REFIN. GAS, TRACE H2S
67.4000 LB/H
0.67CO LB/MMBTU
NONE
,
1.1000 LB/H
0.0300 LB/KM3TU
REFIN. GAS/NAT. GAS, TRACE H2S
23.9000 LB/H
0.6700 LB/HM3TU
N3HE
34.9000 LB/H
0.6000 LB/MI3TU
0.5X S IN OIL
18.0000 LB/H
0.3000 LE/HMSTU
... * BASIS
... PCT EFF
NSPS
BACT
NSPS
99.90
BACT
NSPS
BACT
NSPS
BACT
NSPS
BACT
LEA CONTROL, LNS
PAGE G- 384
-------
(CONTINUED) GULF OIL CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
... * BASIS
... PCT EFF
DELAYED COKING UNIT
116.00 MMBTU/H
S02 3.5000 LB/H
0.0200 LB/MMBTU
TRACE H2S
NOX 13.9000 LB/H
0.1200 LB/MMBTU
LEA FIRING,
LNB
NSPS
BACT
NOTES
SOLVENT DEWAXING UNIT 81943: CHANGE FUEL TYPE FROM REFINERY GAS ONLY TO REFINERY GAS/NATURAL EAS. LNB
E H2S -- <0.10 GR H2S/DSCF.
LOW NOX BURNERS. TRAC
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 385
INITIAL RfVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER TX-0062
SOURCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TrPE/SIZE PETROLEUM REFINING - AUXILIARY
_ ________ _________ __ _».», _ _ -,« «. .__ __ . .- *. .. . .- .-
COMPANY NAME/SITE LOCATION HAWAIIAN INDEPEN. REFIN. EWA BEACH, HI
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/18/81
PERMIT NO. (REGION FILE NO.) HI 81-01 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION IX DENNIS BEAURE6ARD (415)-974-8236
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
HEATER, CRUDE OIL,
110.00 MMBTU/H
REFORMER FURNACE, HZ GEN. PUNT 125.00 MMBTU/H
NOX 0.4000 LB/MMBTU
LOW NOX BURNERS
S02 60.0000 LB/MMBTU
0.57. S S6 FUEL OIL
PM 6.1000 LB/H
0.5X S 86 FUEL OIL
NOX 0.1700 LB/MMBTU
LOW NOX BURNERS
S02 2.4000 LB/H
BURN REF GAS - 0.1 GR H2S/DSCF
PM 1.4000 LB/H
NOME
NOTES
BACT IS DETERMINED BY TECHNOLOGY AND ECONOMICS. FACILITY EXPANSION FROM 95000 BBL/DAY TO 125000 B5L/DAY BY INSTALLATION OF A H
EATER AND HYDROGENATION PLANT.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 386
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER HI-0001
SOURCE TYFE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE --- PETROLEUM REFINING - AUXILIARY
" --~ --- __ ---__--^__
COMPANY NAME/SITE LOCATION HIGH PRAIRIE ENERGY CO.
2.00 MMSCFD
-_-.-»««.__.. --- «-__^-_.
NEAR CUT BANK, MT
TOOELE COUNTY
DETERMINATION MADE BY
PROCESSES SUBJECT
TO THIS PERMIT
EPA REGION VIII
(AGENCY)
JOHN DALE
(AGENCY CONTACT PERSON)
DATE °F PERHIT ISSUANCE- 09/05/80
°F
(PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
4 BASIS
PCT EFF
INCINERATOR
NOTES -----------
4 YEAR PERMIT LIMIT
2.00 HMSCFO
S02 65.0000 LB/H
INCINERATION
BACT
0.00
<*) INDICATES DATUM WAS TRUNCATED FOP THIS TABLE.
PAGE G- 387
REVIEW
ID NUMBER MT-OOOI
SOURCE TYPE CODE 5.5
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - AUXILIARY
66550.00 BPSD
COMPANY NAME/SITE LOCATION HILL PETROLEUM
KROTZ SPRINGS TERMIN
KROTZ SPRINGS, LA 70750
ST. LANDRY PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-LA-286A
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
TOM DIGGS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 03/10/80
ESTIMATED DATE OF START-UP--
(2141-767-1594
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
,.. 4 BASIS
. .. PCT EFF
HEATER
HEATER
TANKS, 11 EA
TAWS, 4 EA
TANKS, 2 EA
LOADING DOCK WASTEWATER
146.00 MMBTU/H
31.00 MMBTU/H
80000.00 BBL
100000.00 BBL
150000.00 BBL
VOC 0.0020 LB/MMBTU
EFFICIENT COMBUSTION
VOC 0.0020 LB/MMBTU
EFFICIENT COMBUSTION
VOC 2.4200 LB/H
DOUBLE SEALS
VOC 2.5800 LB/H
DOUBLE SEALS
VOC 7.3200 LB/H
DOUBLE SEALS
VOC 3.8200 LB/H
MAINTENANCE PROGRAM
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 388
-------
(CONTINUED) HILL PETROLEUM
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... * BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
SEPARATOR
PUMP SEALS
VALVES & FLANGES
RELIEF VALVES
COMPRESSOR SEALS
VOC 0.3100 LB/H
MAINTENANCE PROGRAM
VOC 0.6500 LB/H
MAINTENANCE PROGRAM
VOC 7.7200 LB/H
MAINTENANCE PROGRAM
VOC 1.2000 LB/H
MAINTENANCE PROGRAM
VOC 0.1900 LB/H
MAINTENANCE PROGRAM
BACT
BACT
BACT
BACT
BACT
NOTES
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 389
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER LA-0027
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE- PETROLEUM REFINING - AUXILIARY
" «. _ _ _ _ _..______ »^ ______ _^_ __ __,,__.^___ _.. _..__.._________ ._«.».____«.»___ _ .____ ______
COMPANY NAME/SITE LOCATION HYDROCARBON RECYCLERS, INC. TULSA, OK
__ _«.___ ___.... ., _-._.. ____ _^,_. _ __ _ «. _. ,___ «, -._ ___ «,_«__ _ _« __ _ _ _ _-.-.-, -._._ __ ».__
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/14/82
PERMIT NO. T81-15 & T82-101 ESTIMATED DATE OF START-UP 1982
DETERMINATION MADE BY TULSA CITY-COUNTY HEALTH DEPT JIM VAN SANDT (91S)-744-1000
(AGENCY) CAGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ATMOS. & VACUUM DISTIL. USED 01* 500000.00 GAL/YR
VOC 13.0000 T/YR
INCIN. IN OIL PREHEAT FURNACE 98.00
DISTIL. OF CHLORINATED HC 150000.00 GAL/YR
VOC
CLOSED SYS-DISTIL. UNIT i TANKAGE-2"H20 PRV 99.00
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 390 ID NUMBER OK-0014 SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 50.00 MBPSD
COMPANY NAME/SITE LOCATION INDEPENDENT REFIN. WINNIE, TX
JEFFERSON COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/11/81
PERMIT NO. (REGION FILE NO.) PSD-TX-38S ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI TOM DIGGS (214)-767-159*
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATERS, 6 96.50 MMBTU/H
NOX 0.1100 LB/MMBTU NSPS
LOW NOX BURNERS
REBOILER 14.40 MMBTU/H
NOX 0.1100 LB/MM3TU NSPS
LOW NOX BURNERS
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1983
PAGE G- 391 ID NUMBER TX-0021 SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1964
SOURCE TYPE/SIZE- PETROLEUM REFINING - AUXILIARY 404.00 LT/D
COMPANY NAME/SITE LOCATION KOCH REFINING CO. ROSEMOUNT, MM
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 08/18/81
PERMIT NO. 106-81-1-19 ESTIMATED DATE OF START-UP 1933
DETERMINATION MADE BY MINNESOTA PCA AHTO NIEMIOJA (612)-296-7718
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 B4SIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
CLAUS SULFUR RECOVERY UNIT *3 170.00 LT/D
SQZ 250.0000 PPM NSPS
TAIL GAS SCRUBBER 99.85
NOTES
THE EMISSION LIMIT IS BASED ON NSPS AVERAGING TIMES.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 392
INITIAL REVIEW POST STARTUP
ID NUMBER MN-0008
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 404.00 LT/D
COMPANY NAME/SITE LOCATION KOCH REFINING CO. R05EMOUMT, MN
-.-. __ _. ^«,,_ ___»______«. _ _,^_»,_ _ ___-, _.__,____^__.__, _w_.____.__,_.,_ ^^, _,_^_______.__^_w_-.__
DETERMINATION IS LAER FOR A NEW SOURCE. PATE OF PERMIT ISSUANCE 01/25/83
PERMIT NO. 106A-83-I-23 ESTIMATED DATE OF START-UP 19S3
DETERMINATION MADE BY MINNESOTA PCA AHTO NIEMIOJA (612 J-E96-7718
(AGENCY) (AGENCY CONTACT PERSON) (PKGNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
CLAUS SULFUR RECOVERY UNIT «4 234.00 LT/D
S02 150.0000 PPM
TAIL GAS SCRUBBER 99.85
NOTES
THE EMISSION LIMIT IS BASED ON NSPS AVERAGING TIMES. A CONTINOUS EMISSION MONITORING SYSTEM WILL BE USED TO VERIFY COMPLIANCE
OF COMBINED SRU 3 & 4 GASES AS A 30 D ROLLING AVERAGE AT 200 PPM.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 393
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/19/1934
ID NUMBER MN-0008A
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 30000.00 BPSD
COMPANY NAME/SITE LOCATION LOHGVEIW REFIN. LONGVIEW, TX
5 KM SW POST OFFICE GREGG COUNTY
- » _ _ _ __ _». _________________»__,»______,_,___.._
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 05/08/81
PERMIT NO. PSD-TX-364 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (2141-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FCC REGENERATOR
15000.00 BBL/D
TURBINE, 3
HEATERS, 25
6275.00 HP
80.60 MMBTU/H
PM 10.6000 LB/H
ESP
S02 190.3000 LB/H
S REDUCTION CATAYLST
NOX 32.7000 LB/H
NONE
CO 79.5000 LB/H
HIGH TEMP REGENERATION
PM 0.0700 G/HP-H
REF. FUEL GAS
SQ2 0.1200 G/HP-H
REF. FUEL GAS
NOX 1.3000 G/HP-H
CO 0.4900 G/HP-H
EFFICIENT COMBUSTION
PM 0.0100 LB/MMBTU
FUEL GAS/LOW S OIL
S02 0.0270 LB/MJIBTU
FUEL GAS/LOW S OIL
BACT
75.00
BACT
BACT
BACT
BACT
BACT
NSPS
BACT
NSPS
PAGE G-
-------
NOX 0.1200 LB/MM8TU BACT
LOW NOX BURNERS
CO 0.0200 LB/MMBTU BACT
EFFICIENT COMBUSTION
PAGE S- 395
-------
(CONTINUED) LONGVEIW REFIN.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
t BASIS
PCT EFF
BOILERS, 2
74.00 MMBTU/H
SULFUR RECOVERY UNIT
40.00 T/D
PM
S02
NOX
CO
S02
0.0100 LB/MMBTU
FUEL GAS
0.0270 LB/MMBTU
FUEL GAS
0.1200 LB/MMBTU
LOW NOX BURNERS
0.0200 LB/MV3TU
EFFICIENT COMBUSTION
3 STAGE CLAUS PLANT
BACT
BACT
BACT
BACT
NSPS
99.00
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 396 ID NUMBER TX-0029
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 0^/01/1933
SOURCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1964
=r:r==r==="=======:-===================-:--=-===-_-=--_________-____^^
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION MARATHON OIL CO. ROBINSON, IL
CRAWFORD COUNTY
_ __ _ _,_ __«.____«._ _ .. . . . . ____
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/01/80
PERMIT NO. C 600503* ESTIMATED DATE OF START-UP 198Z
DETERMINATION MADE BY ILLINOIS EPA CHRIS ROHAINE (£17 }-78E-ail3
(AGENCY) (AGENCY CONTACT PERSON) (PKGNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATERS
HEATER
250.00 MHBTU/H MAX
£50.00 MKBTU/H MAX
S02 1.0000 LB/MMBTU
H2S FUEL LIM .'0.10 GR/DSCF
NOX 0.3000 LB/MMBTU
LOU NOX BURNERS
PM 0.1000 LB/MMBTU
503 0.6000 LB/MMBTU
NOX 0.3000 LB/MMBTU
LOW NOX BURNERS
PM 0.1000 LB/MM3TU
NOTES
S02 EMISSION LIMIT TO BE MET WITH REFINERY GAS, RESID. OIL, OR ANY COMBINATION. H£S IN FUEL GAS LIMITED TO 0.1 GR/DSCF.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 397
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 0
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION MARATHON OIL CO. TEXAS CITY, TX 77590
P.O. BOX 1191 GALVESTON COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/03/80
PERMIT NO. TX-241 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
HEATER, CRUDE
175.00 MMBTU/H
NOX 36.7400 LB/H NAT GAS
0.2200 LB/MMBTU NAT GAS
LOU NOX BURN./LEA FIRING
S02 4.3000 LB/H NAT GAS
0.0260 LB/MMBTU NAT GAS
<0.1 GR H2S/DSCF
NOX 52.5000 LB/H FUEL OIL
0.3000 LB/MM3TU FUEL OIL
LOW NOX BURN/LEA FIRING
S02 115.8000 LB/H FUEL OIL
0.6600 LB/KMBTU FUEL OIL
0.6'/. S FUEL OIL
BACT
NSPS
BACT
NSPS
NOTES
REPLACES AN EXISTING CRUDE HEATER FIRING REFINERY GAS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 39S
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER TX-0065
SOURCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/Z2/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - AUXILIARY
70000.00 BBL/0
COMPANY NAME/SITE LOCATION NATIONAL COOP. REFIN. ASSOC.
I1CPHERSON, KS
MCPHERSON COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MADE BY EFA REGION VII
(AGENCY)
DANIEL RODRIGUEZ
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 07/17/81
ESTIMATED DATE OF START-UP
(8161-374-6525
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... & BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
PROCESS HEATER, UNIT HF-009
PROCESS HEATER, UNIT HF-010
PROCESS HEATER, UNIT HP-012
64.00 MMBTU/H
64.00 MMBTU/H
33.90 MMBTU/H
NOX 0.1500 LB/MMBTU MAX
LOW EXCESS AIR
NOX 0.1500 LB/MMBTU MAX
LOW EXCESS AIR
NOX 0.1500 LB/MMBTU MAX
LOW EXCESS AIR
BACT
BACT
BACT
NOTES
REFINERY BEING MODIFIED TO ALLOW PROCESSING OF HIGH SULFUR CRUDES (SCC PROJECT). CAPACITY TO BE INCREASED FROM 57000 TO 70000
EBL/D. SOURCE SIZE IS PEFINERY CAPACITY.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 399
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER KS-0003
SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 35.00 MBPSD
-. » -. _ -_ __ _ _ __ _<_.___ _,- «. ___ __«____«_ .._ _.. _ _ »_ _ _ -.«_.._____ .!« « ___ _
COMPANY NAME/SITE LOCATION NEDERLAND PROCESSING CO. NEOERLAND, TX 77627
P.O. BOX 1567 JEFFERSON COUNTY
~ . «. »- . ». . . ..._^ «.«__..^_._.___.,_»___,»_._,,.
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 10/31/80
PERMIT NO. TX-262 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
VACUUM UNIT FURNACE
150.00 MMBTU/H
PM 7.9000 LB/H OIL
0.0530 LB/MMBTU OIL
LIQUID OR GASEOUS FUEL
S02 70.0000 LB/H OIL
0.4670 LB/MMBTU OIL
0.42X S OIL
NOX 45.0000 LB/H OIL
0.3000 LB/MMBTU OIL
LEA FIRING
CO 5.5000 LB/H OIL
0.0370 LB/MMBTU OIL
COMBUSTION CONTROLS
VOC 1.1000 LB/H OIL
0.0070 LB/MMBTU OIL
PM 2.0000 L6/H GAS
0.0130 LB/W13TU GAS
LIQUID 03 GASEOUS FUEL
S02 3.5000 LB/H GAS
0.0230 LB/M?:BTU GAS
O.T/. GR H2S/DSCF
NOX 18.0000 LB/H GAS
BACT
BACT
BACT
BACT
LAER
BACT
NSPS
BACT
PAGE G- 400
-------
0.1200 L8/KMBTU GAS
LEA FIRING
CO 2.3000 LB/H GAS BACT
0.0150 LB/MHBTU GAS
COMBUSTION CONTROLS
VOC 0.4000 LB/H GAS BACT
0.0070 LB/MKSTU GAS
PAGE G- 401
-------
(CONTINUED) NEDERLAND PROCESSING CO.
PROCESSES SUBJECT THROUGHPUT POLLUTANT
TO THIS PERMIT CAPACITY EMITTED
FCCU REGEN
PM
S02
NOX
CO
voc
ISOSTRIPPER REBOILER 90.00 MMBTU/H
PM
S02
NOX
CO
voc
PM
S02
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
8.4000 LB/H
1.0000 LB/MLB COKE
ESP
42.7000 LB/H
S REDUCTION CATALYST
31.5000 LB/H
LEA FIRING
73.5000 LB/H
500.0000 PPMV, LESS THAN
COMBUSTION CONTROL
7.9000 LB/H
4.7000 LB/H OIL
0.0520 LB--W.BTU OIL
LIQUID OR GASEOUS FUEL
42.0000 LB/H OIL
0.4670 LB/MIIBTU OIL
0.42X S OIL
27.0000 LB/H OIL
0.3000 LB/MMBTU OIL
LEA FIRIKS
3.3000 LB/H OIL
0.0370 LB/KH3TU OIL
COI3USTION CONTROLS
0.7000 LB/H OIL
O.OCSO LB/ M^STU OIL
1.2000 LB/H GAS
0.0130 LB/Mri3TU GAS
LIQUID OR GASEOUS FUEL
2.1000 LB/H GAS
0.0230 LB/MM3TU GAS
0.1X GR H2S/DSCF
10.8000 LB/H GAS
0.1200 LB/MM3TU GAS
LEA FIRIN3
1.4000 LB/H GAS
0.0160 LB/MMBTU GAS
... li BASIS
... PCT EFF
NSPS
95.00
BACT
75.00
BACT
NSPS
BACT
BACT
BACT
BACT
BACT
BACT
BACT
NSPS
BACT
BACT
PAGE G- 402
-------
(CONTINUED) NEDERLAND PROCESSING CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
... t BASIS
... PCT EFF
SULFUR PLANT
FLARE
2.70 MMBTU/H GAS
BOILER
170.00 MMBTU/H OIL
S02 2.2000 LB/H
SCOT TAIL GAS TREAT.
NOX 0.3000 LB/H
0.1200 LB/MMBTU
NONE
PM TRACE
SMOKELESS OPERATION
S02 NEGLIGIBLE
NOME
NOX TRACE
SMOKELESS/STEAM INJECTION
CO TRACE
SMOKELESS OPERATION
PM 8.9000 LB/H OIL
0.0520 LB/MMBTU OIL
LIQUID OR GASEOUS FUEL
S02 79.3000 LB/H OIL
0.4670 LB/MM3TU OIL
0.42X S FUEL
NOX 51.0000 LB/H OIL
0.3000 LB/HM3TU OIL
LEA FIRING
CO 6.2000 LB/H OIL
0.0360 ,LB/t',:;3TU OIL
COMBUSTION CONTROLS
VOC 1.2000 LB/H OIL
0.0070 LB/Mr'3TU OIL
PM 2.3000 LB/H GiS
0.0140 LB/MM3TU GAS
LIQUID OR GASEOUS FUEL
S02 4.2000 LB/H GAS
O.OC50 LB/MMBTU GAS
0.1X GR H2S/DSCF
NOX 20.4COO LB/H G^S
0.1200 LB/MMBTU GAS
BACT
95.00
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 404
-------
COMBUSTION CONTROLS
CO 2.6000 LB/H GAS BACT
0.0150 IB/MMBTU GAS
COMBUSTION CONTROL
VOC 0.5000 LB/H GAS BACT
0.0070 LB/MTTBTU GAS
PAGE G- 405
-------
(CONTINUED) NEDERLAND PROCESSING CO.
PROCESSES SUBJECT
TO THIS PERMIT
VALVES -
VALVES -
VALVES -
FLANGES,
- GAS VAPOR, 396
- LIGHT LIQUID, 268
- HEAVY LIQUID, 357
3650
THROUGHPUT POLLUTANT
CAPACITY EMITTED
VOC
VOC
VOC
VOC
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS
2.1000
0.9000
0.2000
2.1000
LB/H
LB/H
LB/H
LB/H
... & BASIS
MODIFICATION ... PCT EFF
BACT
BACT
BACT
BACT
OIL/WATER SEP
PUMPS
PUMPS
COOLING
STORAGE
LIGHT LIQUID, 58
HEAVY LIQUID, 7
TCHER
TANKS, 6
VOC
VOC
VOC
VOC
55.00 MBBL EA
VOC
3.6000
2.0000
0.3000
3.6000
7.8000
LB/H
LB/H
LB/H
LB/H
LB/H TOTAL
BACT
BACT
.
BACT
BACT
BACT
EXTERNAL FLOATING ROOFS
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 406
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 0^/01/1933
ID NUMBER TX-0060
SOURCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION PETRACO VALLEY OIL * REFINING CO.
1201 DAIRY ASHFORD, SUITE 150
HOUSTON, TX
CAMERON COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. TX-236
DETERMINATION HADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/15/80
ESTIMATED DATE OF START-UP--
1-767-1594
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
HEATER, CRUDE CHARGE
HEATER, VACUUM CHARGE
THROUGHPUT POLLUTANT
CAPACITY EMITTED
427.00 MM3TU/H
PM
S02
NOX
VCC
CO
£19.00 MMBTU/H
PM
S02
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
3.2000 LB/H
0.0070 LB/MM3TU
GAS FIRED, F.G. 02 CONTROL
6.6000 LB/H
0.0100 LB/MMBTU
LOW S GAS (0.1 GR H2S/DSCF )
51.3000 LB/H
0.1200 LB/MMBTU
LEA FIRING, F.G. 02 CONTRL
0.8000 LB/H
0.0020 LB/MMBTU
F.G. 02 CONTROL
4.6000 LB/H
0.0100 LB/MUBTU
F.G. 02 CONTROL
1.7000 LB/H
0.0070 LB/MM3TU
GAS FIRED, F.G. 02 CONTRL.
3.5000 LB/H
0.0200 LB/MMBTU
... 8 BASIS
... PCT EFF
BACT
NSFS
BACT
BACT
BACT
BACT
NSPS
PAGE G- 407
-------
LOW S GAS (0.1 GR H2S/DSCF)
NOX 26.2000 LB/H BACT
0.1200 LB/MMBTU
LEA FIRING, F.G. 02 CONTRL
VOC 0.4000 LB/H BACT
0.0020 LB/MMBTU
F.G. 02 CONTROL
CO 2.3000 LB/H BACT
0.0100 LB/MMBTU
F.G. 02 CONTROL
PAGE G- 403
-------
(CONTINUED) PETRACO VALLEY OIL ft REFINING CO.
PROCESSES SUBJECT THROUGHPUT POLLUTANT
TO THIS PERMIT CAPACITY EMITTED
COKER HEATER 401.00 MMBTU/H
PM
soa
NOX
VOC
CO
FCCU REGENERATOR 24.90 MBBL/D
PM
S02
NOX
VOC
CO
HEATER, HYDROHEATER FEED 147.00 MMBTU/H
PM
so2
NOX
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
3.0000 LB/H
0.0070 LB/MMBTU
GAS FIRED, F.G. 0.°. CONTRL
6.7000 LB/H
0.0200 LB/MMBTU
LOW S GAS, (0.1 6R H2S/OSCF )
48.1000 LB/H
0.1200 LB/MH3TU
LEA FIRING, F.G 02 CONTRL
0.9000 LB/H
0.0020 LB/MMBTU
F.G. 02 CONTROL
4.7000 LB/H
0.0100 LB/MMBTU
F.G. OZ CONTROL
16.7000 LB/H
1.0000 LB/MLB COKE
ESP
116.9000 LB/H
S REDUCTION CATALYST
39.3000 LB/H
LEA FIRING, F.G. 02 CONTROL
12.7000 LB/H
F.G. 02 CONTROL
61.2000 LB/H
O.CSOO 7. BY VOL.
F.G. 02 CONTROL
1.1000 LB/H
0.0070 LB/."MBTU
GAS FIRED, F.G. 02 CONTRL
2.6000 LB/H
0.0200 LB/MM5TU
LOU S GAS (0.1 GR H2S/DSCF)
17.6000 LB/H
0.1200 LB/MMBTU
... & BASIS
... PCT EFF
BACT
BACT
BACT
BACT
BACT
NSPS
75.00
BACT
85.00
BACT
BACT
NSPS
BACT
NSPS
BACT
PAGE G- 409
-------
LEA FIRING, F.G. 02 CONTROL
VOC. 0.3000 LB/H BACT
0.0020 LB/MM3TU
F.. 02 CONTROL
CO 1.7000 LB/H BACT
0.0100 LB/HHBTU
F.. 02 CONTROL
PAGE G- 410
-------
(CONTINUED) PETRACO VALLEY OIL fc REFINING CO.
PROCESSES SUBJECT
TO THIS PERMIT
HEATER, HYDROCRACKER
REGENERATOR, PLATFORMER CAT.
HEATER, PLATFORM FEED
THROUGHPUT POLLUTANT
CAPACITY EMITTED
352.00 MMBTU/H
PM
S02
NOX
VOC
CO
PM
S02
NOX
VOC
CO
932.00 MttBTU/H
PM
S02
NOX
VOC
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
2.7000 LB/H
0.0070 LB/MMBTU
GAS FIRED, F.G. 02 CONTRL
6.1000 LB/H
0.0200 LB/HMBTU
LOW S GAS, 0.1 GR H2S/OSCF
42.3000 LB/H
0.1£00 LB/MMBTU
LEA FIRING, F.G. 02 CONTRL
0.8000 LB/H
0.0020 LB/KMBTU
F.G. 02 CONTROL
4.1000 LB/H
0.0100 LB/MMBTU
F.G. 02 CONTROL
TRACE
NONE
0.1000 LB/H
NOS'E
TRACE
NOS'E
TRACE
NOME
TRACE
NOME
53.2000 LB/H
0.0070 LB/MM3TU
OIL FIRED, F.G. 02 CONTRL
570.9000 LB/H
O.OCCO LB/HMSTU
LOW S GAS, 0.7X S/LB
321,9000 LB/H
0.1200 LB/MM3TU
LEA FIRING, F.G. 02 CONTRL
5.3000 LE/H
:.. & BASIS
. . . PCT EFF
BACT
NSPS
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G-
-------
0.0020 LB/MHBTU
F.6. 02 CONTROL
CO 86.8000 LB/H BACT
0.0100 LB/HMBTU
F.6. 02 CONTROLS
PAGE G- 412
-------
(CONTINUED) PETRACO VALLEY OIL 4 REFINING CO.
PROCESSES SUBJECT
TO THIS PERMIT
HEATER, PENEX ISOMER FEED
INCIN., SULFUR PLANT
HEATER, HF ALK ISOSTRIPPER REBO*
THROUGHPUT POLLUTANT
CAPACITY EMITTED
15.00 MMBTU/H
PM
S02
NOX
VOC
CO
48.00 MMBTU/H
PM
S02
NOX
VOC
CO
233.00 MMBTU/H
PM
S02
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.1000 LB/H
0.0070 LB/MMBTU
6AS FIRED, F.G. 02 CONTROL
0.3000 LB/H
0.0200 LB/HMBTU
LOW S GAS, 0.1 GR H2S/DSCF
1.7000 LB/H
0.1200 LB/MMBTU
LEA FIRING, F.S. 02 CONTRL
TRACE
F.G. 02 CONTROL
0.2000 LB/H
0.0100 LB/MI1BTU
F.G. 02 CONTROL
0.4000 LB/H
0.0080 LB/MMBTU
NOME
26.0000 LB/H
0.0200 /. BY VOL.
SULFUR PLANT, SULFUR RECOVERY
67.4000 LB/H
1.4000 LB/MMBTU
LEA FIRING, F.G. 02 CONTRL
0.1000 LB/H
0.0020 LB/rtfBTU
F.G. 02 CONTROL
0.4000 LB/H
0.0080 LB/MMBTU
F.G. 02 CONTROL
1.7000 LB/H
0.0070 LB/MMBTU
GAS FIRED, F.G. 02 CONTRL
4.0000 LB/H
0.0200 LB/MM3TU
...» BASIS
. . . PCT EFF
BACT
NSPS
BACT
BACT
BACT
BACT
NSPS
99.90
BACT
BACT
BACT
BACT
NSPS
LOW S 645, 0.1 GR H2S/DSCF
PAGE G- 413
-------
NOX 28.0000 LB/H BACT
0.1EOO LB/MMBTU
LEA FIRING, F.G. 02 COMTRL
VOC 0.5000 LB/H BACT
0.0020 LB/MMBTU
F.G. 02 CONTROLS
CO 2.7000 LB/H BACT
0.0100 LB/MMBTU
F.G. 02 CONTROL
PAGE G-
-------
(CONTINUED) PETRACO VALLEY OIL & REFINING CO.
PHOCE55ES SUBJECT THROUGHPUT POLLUTANT
TO THIS PERMIT CAPACITY . EMITTED
HEATER, BUTAMER ISOMER 12.00 MMBTU/H
PM
S02
NOX
VOC
CO
FLARE
S02
NOX
VOC
CO
PM
BOILER 255.00 MMBTU/H
PM
S02
NOX
VOC
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.1000 LB/H
0.0070 LB/MMBTU
GAS FIRED, F.G. O2 CONTROL
0.2000 LB/H
0.0200 LB/MMBTU
LOW S GAS, 0.1 GR H2S/OSCF
1.4000 LB/H
0.1200 LB/MMBTU
LEA FIRING, F.G. 02 CCNTRL
TRACE
F.G. 02 CONTROL
0.1000 LB/H
0.0100 LB/MMBTU
F.G. 02 CONTROL
112.1000 LB/H
NONE
78.8000 LB/H
STEAM INJECTION
3.3000 LB/H
STEAM INJECTION
17.8000 LB/H
STEAM INJECTION
0.0000 LB/H
STEAM INJECTION
1.9000 LB/H
0.0070 LB/MMBTU
GAS FIRED, F.G. 02 CONTRL
3.4000 LB/H
0.0100 LB/mSTU
LOW S GiS, 0.1 G3 H2S/DSCF
31.7000 LB/H
0.1200 LB/r;rBTU
LEA FIRING, F.G. 02 OT4TROL
0.4000 LB/H
0.0020 LB/MMBTU
... t BASIS
... PCT EFF
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
NSPS
BACT
BACT
PAGE G- 415
-------
F.G. 02 CONTROL
CO 2.3000 LB/H BACT
0.0100 LB/MMBTU
F.G. 02 CONTROL
PAGE 6-
-------
(CONTINUED) PETRACO VALLEY OIL fc REFINING CO.
PROCESSES SUBJECT THROUGHPUT POLLUTANT
TO THIS PERMIT CAPACITY EMITTED
HEATER, OIL 163.00 MMBTU/H
PM
S02
NOX
VOC
CO
HEATER, SCOT UNIT FEED 5.00 MMBTU/H
PM
so2
NOX
VOC
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
1.8000 LB/H
0.0070 LB/MMBTU
GAS FIRED, F.6. 02 CONTRL
2.8000 LB/H
0.0100 LB/MMBTU
LOW S GAS, 0.1 GR H2S/DSCF
19.6000 LB/H
0.1200 LB/MMBTU
LEA FIRING, F.6. 02 CONTROL
0.4000 LB/H
0.0020 LB/MMBTU
F.G. 02 CONTROL
1.9000 LB/H
0.0100 LB/MMBTU
F.G. 02 CONTROL
TRACE
NOME
0.1000 LB/H
0.0100 LB/MMBTU
NONE
0.6000 LB/H
0.1200 LB/MMBTU
NONE
TRACE
NONE
0.1000 LB/H
0.0100 LB/MMBTU
NONE
... 4 BASIS
... FCT EFF
BACT
NSPS
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 417
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 0*/01/1983
ID NUMBER TX-0073
SOURCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 130000.00 BPSD
__ _ _______ _ ___-, ,-. _ _ _______ ______
COMPANY NAME/SITE LOCATION PHILLIPS PETROLEUM CO. BORGER, TX
BORGER REF NGL CONTR. HUTCHINSON COUNTY
«... _ __ _ _________ ___. ________.-___->____ __ .. . -
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/15/81
PERMIT NO. PSD-TX-102M-1 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214J-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. ENGINE, Z
650.00 HP EA
TURBINE, 2
3000.00 HP EA
S02
NOX
VOC
CO
PM
S02
NOX
0.0320
0.8000
0.1360
0.4000
0.0036
0.0070
0.0170
0.0340
0.0100
0.0700
0.0320
0.8000
0.1360
0.4000
LB/MMBTU GAS
LB/nr'BTU OIL
0.7X S IN OIL
LB/MMBTU GAS
LB/MM3TU OIL
02 MONITORING
LB/MMBTU GAS
LB/MMBTU OIL
02 MONITORING
LB/MMBTU GAS
LB/MM3TU OIL
02 MONITORING
LB/MMBTU GAS
LB/MC3TU OIL
LB/MMBTU GAS
LB/MMBTU OIL
0.7X S IN OIL
LB/MMBTU GAS
LB/MMBTU OIL
02 MONITORING
PAGE G- 418
-------
VOC 0.0036 LB/MMBTU GAS
0.0070 LB/MMBTU OIL
02 MONITORING
CO 0.0170 LB/MMBTU GAS
0.03-+0 LB/MMBTU OIL
02 MONITORING
PM 0.0100 LB/MMBTU GAS
0.0700 LB/MMBTU OIL
PAGE G-
-------
(CONTINUED) PHILLIPS PETROLEUM CO.
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
HEATERS, 4 32.00 MMBTU/H
CRUDE OIL TANKS, 3 200.00 MBBL
FUGITIVE EMISSIONS
CO BOILERS, 2 370.00 MMBTU/H
I.C. COMPRESSOR 720.00 HP
<*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
POLLUTAW
EMITTED
S02
NOX
VOC
CO
PM
VOC
VOC
S02
NOX
VOC
CO
PM
S02
NOX
VOC
CO
PM
f EMISSION LIMITS . . . i BASIS
CONTROL EQUIPMENT OR PROCESS MODIFICATION . . . PCT EFF
0.0320 LB/MMBTU
GAS AS FUEL
0.1360 LB/MMBTU
02 MONITORING
0.0036 LB/M;:BTU
02 MONITORING
0.0170 LB/MMBTU
02 MONITORING
0.0100 LB/MM3TU
GAS AS FUEL
1.8300 T/YR EA
EPA EQUIV. STAND t MAINT. PROG
140.0000 T/YR
EPA EQUIV. STAND & KAINT . PROG
0.1000 LB/Mr.BTU
1.9000 LB/MNBTU
02 MONITORING
0.0014 L3/MM3TU
02 MONITORING
0.0170 LB/NI-STU
02 MONITORING
0.3100 LB/MM3TU
G4S AS FUEL
0.1000 G/HP-H
GAS AS FUEL
10.9000 G/HP-H
4.4COQ G/HP-H
1.3900 G/HP-H
0.0200 G/HP-H
GAS AS FUEL
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
PAGE G- 420
ID NUMBER TX-OOS2
SOURCE TYPE CODE
5.5
-------
NATURAL SAS FIRED
(*_!_I^ICATES_DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:NIo"*/Ol!a9S3W ***
PAGE G- 421 ID ^if«BER TX-0052
SOURCE TYPE CODE 5.5
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/198"+
SOURCE TYPE/SIZE--- PETROLEUM REFINING - AUXILIARY 10000.00 BBL/D
_. -._-. _ _ . -.
COMPANY NAME/SITE LOCATION PROCESS REFIN. CO. BAKERSFIELD, CA
«_««-__-_---_-_ «.____--_____.-._-.------------------------------------------
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 09/19/79
PERMIT HO. SJ-78-27 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION IX MATT HABER (4151-974-8053
(AGENCY) (AGENCY CONTACT PERSON) < PHCh'E )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
VACUUM HEATER £5.00 MMBTU/H
NOX 0.2700 LB/MMBTU
LOW NOX BURNERS 35.00
CRUDE HEATER 20.00 MMBTU/H
NOX 0.2700 LB/MM3TU
LOU NOX BURNERS 35.00
BOILER, 2 EA 4.31 MH3TU/H
NOX 0.2700 LB/HMBTU
LOW NOX BURNERS 35.00
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOS THIS TABLE. REVIEW STATUS^__04/01/19S3____04/04/19S4_
PAGE~G-~422ID NUMBER CA-0013 SOUPCE TYP5 CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 50.00 HBPSO
-
COMPANY NAME/SITE LOCATION PROVIDENT ENERGY CO.
MOBILE, AZ
E 03/03/80
DETERMINATION MADE BY EPA REGION IX JIM HANSON fS^-S-S^S °* *P"
(AGENCY) (AGENCY CONTACT PERSON) (FHCNE)
: = r:rr-=-r = rrr=:= = = zr = z = r: = ==rmr:sr;- = r=r = = ^zrr=:rr=rr=r:rr = r^ = rr-=:r7:^:rr-z- - ---- ___ _.._
THROUGHPUT POLLUTANT EMISSION LIMITS .. & BASIS
._ CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ] !.' PCT EFF
,.__-.____ ___ _ _ __ , _ _<- ^: __ _^_ ^
_ »_ _ ._- - -. __-_____^.__-,_11_^.__,__,___
BOILER & HEATER
NOX 0.4300 LB/tlMBTU 2H AV
LOW NOX BURNERS
S02
CLAUS SULFUR RECOVERY UNIT FUEL LIM^S-.IGR/DSCF.S-.^XWT
H2S
FCC UNIT i CATALYIST REGEN. SC°T TAIL GAS ir
PM 1.0000 LB/MLB COKE BURNED
3 STAGE CATALYST SEP. 4 ESP
CO
CO BOILER
S02
FUEL LIM:H£S-.1GR/DSCF,S-.1XWT
NOTES
COVERED DILUTES SUPER.. WPCH RECOVERY OH LIGHT GASOLINE TANKS, WD DOUBLE SEALED fSjATITO Mwl^ mlrBER eASOLIMt T
«^f!!JB^8^*I!L = «=^LI^!: REVIEW STATUS^SJ/o'l/mf "** *
PAGE G" 4" ID Nl^BER AZ-0001 SOUScrTYFrcODE==:=T5
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - AUXILIARY 100.00 MBPSO
COMPANY NAME/SITE LOCATION SABER REFIN. CORPUS CHRISTI, TX
6560 UPRIVER ROAD NEUCES COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/08/81
PERMIT NO. (REGION FILE NO.) PSD-TX-324 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATERS, 5
365.00 MMSTU/H
FURNACES, 5
REBOILERS, 2
178.00 MMBTU/H
158.00 MMBTU/H
PM 0.0100 LB/MMBTU
REF. FIELD GAS
S02 0.0140 LB/MMBTU
FIRE REFINERY FLUE GAS
NOX 0.1EOO LB/rr,5TU
IQ'A NOX BURNERS
CO 0.0160 LB/MMBTU
EFFICIENT COMBUSTION
PM 0.0100 LB/Mt'.BTU
REF. FUEL GAS
S02 0.0140 LB/f1!'3TU
REF. FUEL GAS
NOX 0.1200 LB/MMBTU
LOW NOX BURNERS
CO 0.0160 LB/71M3TU
EFFICIENT COMBUSTION
PM 0.0100 LB/MMBTU
REF. FUEL GAS
S02 0.0140 LB/MMBTU
BACT
NSPS
BACT
BACT
BACT
NSPS
B4CT
BiCT
BACT
NSPS
PAGE G- 424
-------
REF. FUEL GAS
NOX 0.1200 LB/HMBTU BACT
LCM NOX BURNERS
CO 0.0160 LB/MKBTU BACT
EFFICIENT COMBUSTION
PAGE G-
-------
(CONTINUED) SABER REFIH.
PROCESSES SUBJECT
TO THIS PERMIT
REFORMERS, 2
HEAVY OIL CRACKING UNIT
THROUGHPUT POLLUTANT
CAPACITY EMITTED
356.00 MMBTU/H
PM
S02
NOX
CO
46500.00 BPSD
PM
S02
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.0100 LB/MHBTU
REF. FUEL GAS
0.0140 LB/KMBTU
FIRE REF. FUEL GAS
0.1200 LB/HMBTU
LOW NOX BURNERS
0.0160 LB/MM3TU
EFFICIENT COMBUSTION
5.6000 LB/H
3-STAGE CYCLONE
178.0000 PPM
FLUE GAS DESULFURIZATION
203.0000 LB/H
KO CONTROLS AVAILABLE
178.0000 PPM
WASTE HEAT BOILER
...& BASIS
... FCT EFF
BACT
NSPS
BACT
BACT
BACT
NSPS
93.20
EACT
NSPS
NOTES
H2S CONTENT OF FLUE GAS WILL BE LIMITED TO 0.054 GRAINS/DSCF.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PASE G- 426
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER TX-0041
SCtTCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
= ~ = = = = -~ = = := = = - = :: = :: = = = = :::: = = = = = = = = = = = = = = = = === = = = - = = = = = r = = r: = = = = =:r = = = = r = ===r=: = = = r = = = = = = r = ri: = = r = = = rr = = = =: = r=r = = = = = = rsr = = = = = = = = = = =r = = r = = =
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 67.00 MBPSD
COMPANY NAME/SITE LOCATION SIGMORE REFIN. CO. SAN ANTONIO, TX 78220
P.O. BOX 20267 LIVE OAK COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 12/10/80
PERMIT HO. (REGION FILE NO.) PSD-TX-331 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EFA REGION VI JOHN BUNYAK (214 J-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATER, SI CRUDE
59.50 HMBTU/H
HEATER, LUBE CRUDE
FCCU REGENERATOR
10.80 MM3TU/H
40.00 MBPSD
PM 2.7500 LB/H
EFFICIENT COMBUSTION
S02 22.1800 LB/H
0.7X S FUEL OIL
NOX 9.3400 LB/H
EFFICIENT COMBUSTION
CO 3.1300 LB/H
EFFICIENT CCM3USTION
PM 0.0600 LB/H
EFFICIENT COMBUSTION
S02 0.2300 LB/H
0.7X S FUEL OIL
NOX 2.4800 LB/H
EFFICIENT COMBUSTION
CO 0.1SOO LB/H
EFFICIENT CCMDUSTION
PM 12.0000 LB/H
ESP
S02 205.4COO LB/H
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
NSPS
90.00
BACT
PAGE G- 427
-------
HIGH TEMP REGEN.
NOX 37.0100 LE/H BACT
HIGH TEMP REGEH.
CO 90.1300 LB/H BACT
HIGH TEMP REGEN.
PAGE G-
-------
(CONTINUED) SIGMORE REFIN. CO.
PROCESSES SUBJECT
TO THIS PERMIT
REBOILER, ISOSTRIPPER
BOILER
HEATER, VISBREAKER CHARGE
HEATER, VACUUM DISTALLATION
THROUGHPUT POLLUTANT
CAPACITY EMITTED
48.80 MMBTU/H
PM
S02
NOX
CO
167.80 MMBTU/H
PM
S02
NOX
CO
40.00 MMBTU/H
PM
S02
NOX
CO
96.50 MMBTU/H
PM
soa
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
3.3100 LB/H
EFFICIENT COQMBUSTION
38.6000 LB/H
0.7X S FUEL OIL
32.8700 LB/H
EFFICIENT COMBUSTION
1,6500 LB/H
EFFICIENT COMBUSTION
11.3600 LB/H
EFFICIENT COMBUSTION
138.7200 LB/H
O.T/. S FUEL OIL
113.0400 LB/H
EFFICIENT COMBUSTION
9.6800 LB/H
EFFICIENT COMBUSTION
2.7100 LB/H
EFFICIENT COMBUSTION
31.6400 LB/H
0.7X S FUEL OIL
26.9500 LB/H
EFFICIENT COMBUSTION
1.3500 LB/H
EFFICIENT COMBUSTION
1.6000 LB/H
EFFICIENT COMBUSTION
19.4900 LB/H
.77. S FUEL, SCRUB TO .1 GR/DSCF
CO. 8000 L3/H
EFFICIENT COMBUSTION
2.5000 LB/H
EFFICIENT COMBUSTION
... * BASIS
. . . PCT EFF
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 429
-------
(CONTINUED) SIGMORE REFIN. CO.
PROCESSES SUBJECT
TO THIS PERMIT
HEATER, 82 CRUDE UNIT
HEATER, VISBREAKER CHARGE
HEATER, CRUDE CHARGE
REBOILER, NAPHTHA STABILIZER
THROUGHPUT POLLUTANT
CAPACITY EMITTED
18.10 MMBTU/H
PM
S02
NOX
CO
40.00 MMBTU/H
PM
S02
NOX
CO
130.40 MMBTU/H
PM
SO 2
NOX
CO
19.50 MMBTU/H
PM
S02
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.2700 LB/H
EFFICIENT COMBUSTION
0.0100 LB/H
0.7X S FUEL OIL
4.1600 LB/H
EFFICIENT COMBUSTION
0.31CO LB/H
EFFICIENT COMBUSTION
2.7100 LB/H
EFFICIENT COMBUSTION
31.6400 LB/H
0.7X S FUEL OIL
26.9500 LB/H
EFFICIENT COMBUSTION
1.3500 LB/H
EFFICIENT COMBUSTION
8.8300 LB/H
EFFICIENT COMBUSTION
103.1400 LB/H
0.7X S FUEL OIL
87.8400 LB/H
EFFICIENT CCMSUSTION
4.4200 LB/H
EFFICIENT COMBUSTION
1.3200 LB/H
EFFICIENT CCMBUSTICN
15.4200 LB/H
o.?:: s FUEL OIL
13.1400 LB/H
EFFICIENT COMBUSTION
0.6600 LB/H
EFFICIENT COMBUSTION
... & BASIS
. . . PCT EFF
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
EACT
BACT
BACT
EACT
BACT
BACT
BACT
PAGE G- 430
-------
(CONTINUED) SIGMORE REFIN. CO.
HKULtSSES SUBJECT
TO THIS PERMIT
HEATER, NAPHTHA HDS CHARGE
REBOILER, NAPHTHA SPLITTER
HEATER, 1ST REFORMER
HEATER, 2ND REFORMER
THROUGHPUT POLLUTANT
CAPACITY EMITTED
36.40 MMBTU/H
PM
502
NOX
CO
27.30 MMBTU/H
PM
S02
NOX
CO
59.50 MMBTU/H
PM
S02
NOX
CO
52.80 MM3TU/H
PM
S02
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.1900 LB/H
EFFICIENT COMBUSTION
1.0000 LB/H
FUEL GAS SCRUB. TO 0.1 GR/DSCF
4.4600 LB/H
EFFICIENT COMBUSTION
0.6300 LB/H
EFFICIENT COMBUSTION
0.1400 LB/H
EFFICIENT COMBUSTION
0.7500 LB/H
FUEL GAS SCRUB. TO 0.1 GR/DSCF
3.3400 LB/H
EFFICIENT COMBUSTION
0.4700 LB/H
EFFICIENT COMBUSTION
0.3100 LB/H
EFFICIENT COMBUSTION
1.6300 LB/H
FUEL GAS SCRUB. TO 0.1 GR/DSCF
7.2900 LB/H
EFFICIENT COMBUSTION
1.0300 LB/H
EFFICIENT COMBUSTION
0.2700 LB/H
EFFICIENT CCMEUSTICM
1.4500 LB/H
FUEL GftS SCRUB. TO 0.1 GR/DSCF
6.4700 LE/H
EFFICIENT CCMEUSTICN
0.9200 LB/H
EFFICIENT CCM3USTIOM
... * BASIS
... PCT EFF
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 431
-------
(CONTINUED) SIGT10RE REFIN. CO.
PROCESSES SUBJECT THROUGHPUT POLLUTANT
TO THIS PERMIT CAPACITY EMITTED
HEATER, 3RD REFORMER 26. 40 UMBTU/H
PM
EMISSION LIMITS ... & BASIS
CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
0
.1400
LB/H
BACT
EFFICIENT OPERATION
S02
NOX
CO
HEATER, 4TH REFORMER 13.20 MMBTU/H
PM
S02
NOX
CO
REEOILER, REFORMER STABILIZER 16. 40 MMBTU/H
PM
S02
NOX
CO
REBOILER, KEROSENE HDS STRIPPER 13.60 MMBTU/H
PM
soa
NOX
CO
0
3
0
0
0
1
0
0
0
2
0
0
0
1
0
.7200
.2300
.4600
.0700
.3600
.6200
.2300
.0800
.4500
.0100
.2800
.0700
.3700
.6700
.2400
LB/H
FUEL GAS
LB/H
EFFICIENT
LB/H
EFFICIENT
LB/H
EFFICIENT
LB/H
FUEL GAS
LB/H
EFFICIENT
LB/H
EFFICIENT
LE/H
EFFICIENT
LB/H
FUEL GAS
LB/H
EFFICIENT
LB/H
EFFICIENT
LB/H
EFFICIENT
L3/H
FUEL GAS
LB/H
EFFICIENT
LB/H
EFFICIENT
SCRUB. TO 0.1 GR/DSCF
COMBUSTION
COMBUSTION
COMBUSTION
SCRUB. TO 0.1 GR/DSCF
COMBUSTION
COMBUSTION
COMBUSTION
SCRUB. TO 0.1 GR/DSCF
COMBUSTION
COMBUSTION
CFEPATION
SCRUB. TO 0.1 GR/DSCF
COMBUSTION
COMBUSTION
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
EACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 432
-------
(CONTINUED) SIGMORE REFIN. CO.
PROCESSES SUBJECT THROUGHPUT POLLUTANT
TO THIS PERMIT CAPACITY EMITTED
HEATER, GAS OIL HDS CHARGE 97.80 MMBTU/H
PM
S02
NOX
CO
REBOILER, DEETHANIZER 25.20 MMBTU/H
PM
S02
NOX
CO
= === ==:: = = = = = = = = = = = = = = = ===:: ===r === ==== === = === ======= = = === = ========
EMISSION LIMITS ...» BASIS
CONTROL EQUIPMENT CR PROCESS MODIFICATION . . . PCT EFF
0
2
11
1
0
0
3
0
.5000
.6800
.9800
.7000
.1300
.6900
.0900
.4400
LB/H
EFFICIENT
LB/H
FUEL GAS
LB/H
EFFICIENT
LB/H
EFFICIENT
LB/H
EFFICIENT
LB/H
FUEL GAS
LB/H
EFFICIENT
LB/H
EFFICIENT
COMBUSTION
SCRUB. TO 0.1 SR/DSCF
COMBUSTION
COMBUSTION
COMBUSTION
SCRUB. TO 0.1 GR/DSCF
COMBUSTION
COMBUSTION
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
NOTES
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 433
INITIAL REVIEW POST STARTUP
REVIEW STATUS-' 04/01/1983
ID NUMBER TX-0039
SOURCE TYPE CCDE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/23/198-4
SOURCE TYPE/SIZE- PETROLEUM REFINING - AUXILIARY 31500.00 BPSD
COMPANY NAME/SITE LOCATION SOUTHERN UNION REFIN. LOVINSTON, NM
5 MI SE LOVINSTON LEA COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/05/81
PERMIT NO. HM-350 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATER, 13 EA 85.00 MMBTU/H
PM 0.0050 LB/MMBTU GAS BACT
FUEL GAS OS LOW SULFU3 OIL
S02 0.0270 LB/MMBTU BACT
FUEL OIL OR NATURAL GAS
NOX 0.1200 LB/MM3TU BACT
LOU NOX BURNERS
SULFUR RECOVERY UNIT
S02 0.8400 LB/H BACT
CLAUS UNIT
NOTES
13 HEATERS AND 1 SULFUR RECOVERY UNIT.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 434 ID NUMBER NM-0004 SOURCE TYPE CC3E 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION TENNECO
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. PSD-LA-199
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
HEATERS, 26 287.00 MMBTU/H
BOILERS, 13 160.00 MMBTU/H
CO BOILER 350.00 MMBTU/H
FLARES, Z
SULFUR PLANT 6.60 KM3TU/H
CHAU1ETTE, LA
DATE OF PERMIT
ESTIMATED DATE
TOM DIGSS { £14 )-76 7-1594
(AGENCY CONTACT PERSON) (PHONE)
ST. BERNARD PARISH
ISSUANCE-- 12/23/81
OF START-UP-- 1934
POLLUTANT EMISSION LIMITS ... 4 BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . . . PCT EFF
CO 0.0210 LB/MMBTU GAS
0.0300 LB/MMSTU OIL
02 MONITORING
CO 0.0210 LB/KNBTU GAS
0.0300 LB/MM3TU OIL
02 MONITORING
CO 0.0210 LB/MM3TU GAS
0.0300 LB/Hfi3TU OIL
02 MONITORING
CO 1.6000 LB/H EA
NONE
CO 0.0 330 LE/r,MBTU
NOSE
BACT
BACT
BACT
BACT
BACT
PAGE G- 437
-------
(CONTINUED) TENNECO
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
_ _ _ .... _ ____.. - _-.___ __ _ -. ___-. __ _ _-__,. «. _-. _ -.
FCCU REGEN 42000.00 BPSD
CO 212.8000 LB/H NSPS
COMPLIANCE W/NSPS
NOTES
26 HEATERS RANGING IN SIZE FROM 11 TO 287 MMBTU/HR. 13 BOILERS RANGING IN SIZE FROM 24 TO 160 MMBTU/HR.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/19S3
PAGE G- 438 ID NUMBER LA-0022 SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
= = - = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = === = = r = = = = :: = = = z = = == = = = = == = - = = = = = = :: = = = = :: = = === = :: = = = === = :: = = = = :: = ;: = ,=::- =
SOURCE TYPE/SIZE PETROLEUM REFININS - AUXILIARY 100000.00 BPSD
"" " *- _.-__.-__ ___.___.»____ _^*fc «_«__ _ w.« ________ ^_».___^, __,.. ___ _ _.. _ ___.. _ _« _
COMPANY NAME/SITE LOCATION TEXACO, INC. CONVENT, LA
ST. JAMES PARISH
~~~~~~~~ ~~~~~~~~~^ ~ ~ ~ ^ ^ ~ ^ - ».. .._ *.__....._,»,_..»__
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE- 11/16/81
PERMIT NO. (REGION FILE NO.) PSD-LA-420 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK <214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
= = = rrrrr = rr = r = r = rr = r = rr = = = = = = r = = : = = :r = r = = = r = = = = - = ~rr = = r = = = = = = = = = = = = = = r = rr = = = = = = = = = = = r = = = ::::z:- = ::-:: = :.::_ = =
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ." PCT EFF
~ ----------------- -_- _-_ -.-__«...._ , __ _____^__,... _ ---__-____..___ -__ _ __, _. ^____._ -__fc --_-_._
HEATERS, 15 EA 198.00 MMBTU/H
CO 0.0300 LB/MMBTU BACT
FLUE GAS 02 MONITOR
LOU EXCESS AIR
ACID GAS INCIN. 8.00 MMBTU/H
CO 0.9300 L8/KMBTU BACT
_n_ T.,-T.,cniT« L0'^ EXCESS AIR, FLUE GAS 02 MONITOR
ERG INCINERATOR 13.10 MMBTU/H
CO 0.0200 LB/MMBTU BACT
LOU EXCESS AIR, FLUE GAS 02 MONITOR
S'OTES
<*> INDICATES DATUM WAS TRUNCATED FDR THIS TABLE. REVIEW STATUS^"J/Ol/lS!" P°ST STARTUP
PAGE G- <+39 ID NUMBER LA-0007 SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY 140000.00 BPSD
COMPANY NAME/SITE LOCATION TEXACO, INC. CONVENT, LA
ST. JAMES PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 04/23/81
PERMIT NO. (REGION FILE NO.) PSD-LA-378 ESTIMATED DATE OF START-UP--
DETERMINATION M/DE BY EPA REGION VI JOHN BUNYAK (214>-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
MTU-CRU FLUE GAS COOLER 670.00 MMBTU/H
CO 0.02CO LB/MMBTU BACT
HIGH TEMP REGENERATION (HTR )
INCIN., 3 EA 13.10 MMBTU/H
CO 0.0200 LB/t-r.STU BACT
HIGH TEMP REGENERATION (HTR)
POWER RECOVERY STACK
CO NSPS
LIMIT EMISSIONS TO 500 PPM
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 440 ID NUMBER LA-0024 SO'JRCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
__ 05/22/1984
= - = = = = = = = = :: = = = = :: = = = = = = = ::=:= = = = = = = = = = = = = = = = = = = = = = = = = === = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = r = = = = = = ==r = = === = ==== = -r = r = = = = r = =
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
"~ """ "*"" ~" """" ~ ~ "" ~~~~~~~~~~ ~ ~ ~ ~ ~ __.-.._...-_..,._«,-._
COMPANY NAME/SITE LOCATION TEXACO, INC. PORT ARTHUR, TX 77640
P.O. BOX 712 JEFFERSON COUNTY
~ ~~~ _-- --__..____,. _.»____*. -.-_ ..__-..,__,-,_,__.-.,..__,.____ -.-_ -._-____. _. __»____
°R * "ODIFIED SOURCE- DATE OF PERMIT ISSUANCE- 06/20/79
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK ff767-15 ^ ^^~VP~~
(AGENCY) (AGENCY CONTACT PERSON) CPHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION .LIMITS .. & BASIS
_____ PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
"~ " "*~~~ * «- _ -.__«_-.__. «._^_ -_«_ _ »._ _ « _ ^_-_» «._-.-__. _ _^_ ___-__._»__ fc » -_»__» ^ ^__
FCCU 170.00 MBBL/D
S02 406.3000 LB/H NSPS
HFATFD «^n7 SOX REDUCTION CATALYST 75.00
HEATER 81407 30.74 SCFM
S02 4.5000 LB/H NSPS
FLUE GAS SCRUB./SULFUR RECOVERY °'1 GR/°SCF' ^ ^^
502 1.1000 LB/H SEE NOTE NSPS
TAIL GAS TREATING UNIT 99.97
NOTES -
NOTE: F.G. SCRUB./S RECOVERY EMISSIONS ARE INCREASE ONLY OVER EXISTING CONDITIONS.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS^oJ/Ol/l?"" P°S
PAGE G- 441 ID NUMBER TX-OC64 SCARCE TYPE CCDE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE PETROLEUM REFININS - AUXILIARY
COMPANY NAME/SITE LOCATION TOSCO CORP. BAKERSFIELD, CA
DETERMINATION IS FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 06/18/SO
PERMIT NO. (REGION FILE NO.) SJ-73-26 ESTIMATED DATE OF START-UP-
DETERMINATION HADE BY EPA REGION IX DAVID SOLOMON (415)-974-8066
(AGENCY) (AGENCY CONTACT PERSON) (PHCHE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... « BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
CO BOILER 92700.00 LB/H
CO 45.7000 LB/H LAER
BOILER BURNS CO EMITTED FROM TCC UNIT 99.40
S02 0.5000 7. S FUEL LAER
SULFUR IN AUXILLARY FUEL OIL
NOX 41.0000 LB/H BACT
COMBUSTION MODIFICATION BASED ON 0.3 LB/MMBTU
NOTES
THERMOFOR CATALYTIC CRACKING. INSTALLATION OF CO BOILER ON REFINERY TCC1 UNIT
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 442
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933 04/04/1934
ID NUMBER CA-0007
SCL'SCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
PETROT.EUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION TOSCO CORP.
MARTINEZ, CA
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. 27769
DETERMINATION MADE BY BAY AREA AQMD
(AGENCY)
JIH KARAS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 02/19/82
ESTIMATED DATE OF START-UP 1983
(415J-771-6COO
(PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... i BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
""" ~~~*"~~ *~ ~~-"~ - __ __..______ _» _ «. . __ ._ __ _»_»___ _»._ __ .._______,»._,... __ «. « _.»__«.__ ,__. -._.._____-_ _ _.». _ __. __^.__
FURNACE, REFINERY PROCESS, 2 TO* 119.00 MM3TU/H SEE*
NOX 40.0000 PPM AT 37. 02 BACT
LOW NOX BURNERS/1 SCR UNIT FOR BOTH FURNACES 70.00
FURNACE, REFINERY PROCESS 40.00 t^BTU/H
NOX 40.0000 PFM AT 3X 02 BACT
LOW NOX BURNERS / SCR 70.00
NOTES
BURNING REFINERY FUEL GAS WITH HEAT VALUE OF 1025 BTU/CF. NOTE THROUGH PUT CAPACITY IS TOTAL CAPACITY. ONE IS 67. MfJBTU/H,
THE OTHER IS 52. MHBTU/H.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FCR THIS TABLE. REVIEW STATUS'- 04/19/1984
PAGE G- 443 ID NUMBER CA-0046A SOURCE TYPE CODE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOLACE TYPE/SIZE
PETROLEUM REFINING - AUXILIARY
10000.00 BBL/D
COMPANY NAME/SITE LOCATION UNI OIL
INGLESIDE, TX
SAN PATRICIO COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-TX-229
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 03/12/80
ESTIMATED DATE OF START-UP--
(214J-767-1594
(PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATER, VACUUM 66.65 KMBTU/H
S02 1
0
PM 1
0
NOX 11
0
CO 1
0
VOC 0
0
FCC UNIT 17000.00 BBL/D
S02 64
PM 12
1
.2700 LB/H
.0190 LB/WBTU
FUEL GAS: o.l GR/DSCF H2S
.5100 LE/H
.0230 LB/MM3TU
COMBUSTION CONTROL
.6000 LB/H
.1740 LB/HM3TU
CC^:3US. CONTROL/LOW NOX BURN.
.6700 LB/H
.0250 LB/MM3TU
CCM3USTION CONTROL
.1600 LB/H
.0024 LB/MfiBTU
COMBUSTION CONTROL
.1000 LB/H
F. G. :0.1 GR/DSCF H2S
.0000 LB/H
.COCO LB. MLB COKE BURN OFF
ESP
NSPS
BACT
BACT
BACT
BACT
NSPS
NSPS
PAGE G- 444
-------
NOX 29.4000 LB/H BA.CT
CKBST. CONTRL. fc LOW NOX BURN.
CO 89.1000 LB/H NSPS
HIGH TEMP. REGENERATION
VOC 2.6000 LB/H BACT
COMBUSTION CONTROL
PAGE G- 445
-------
(CONTINUED) UNI OIL
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
HEATER, ISOSTRIPPER 38.24 MMBTU/H
TAIL GAS INCIN
REGENERATOR, HYDROTREATER CATAL*
HEATER, REFORMER 161.00 MM3TU/H
POLLUTANT
EMITTED
S02
PM
NOX
CO
VOC
S02
NOX
S02
PM
S02
PM
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.6300 LB/H
0.0790 LB/MM8TU
F.G. : 0.01 GR/DSCF H2S
0.8700 LB/H
0.0230 LB/MMBTU
COMBUSTION CONTROL
6.8500 LB/H
0.1790 LB/MMBTU
CM3ST. CONTRL./LOW NOX BURN.
1.1100 LB/H
0.0290 LB/Mr;BTU
COMBUSTION CONTROL
0.1600 LB/H
0.0042 LB/MMBTU
COr.BUSTICN CONTROL
39.7000 LB/H
NO CONTROL
0.0790 LB/H
NO CONTROL
0.2400 LB/H
F.G. : 0.1 GR/DSCF H2S
0.7900 LB/H
COMBUSTION CONTROL
1.9000 LB/H
0.0120 LE/t.MBTU
F.G. : 0.1 GR/DSCF
0.0790 LB/H
0.0005 LB/r;r:BTU
cc::3USTioN CONTROL
43.8000 LB/H
0.2700 LB/MM3TU
CMBST. CONTRL./LOW NOX BURN.
6.7500 L3/H
0.0420 LB/MMBTU
... 8 BASIS
. . . PCT EFF
NSPS
BACT
BACT
BACT
BACT
BACT
BACT
NSPS
BACT
NSPS
BACT
BACT
BACT
PAGE G-
-------
COMBUSTION CONTROL
VOC 0.8000 LB/H BACT
0.0050 LB/MMBTU
COMBUSTION CONTROL
PAGE G-
-------
(CONTINUED) UNI OIL
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
HEATER, 80S 40.00 MMBTU/H
BOILER, PACKAGE 103.24 MMBTU/H
NOTES
THE NEW FACILITY WILL NOT INCREACE THE REFINERIES CP.UDE
ED GASOLINE.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
S02 0.4800 LB/H
0.0120 LB/MMBTU
F.G. : 0.1 GR/DSCF H2S
PM 1.4300 LB/H
0.0360 LB/MMBTU
COMBUSTION CONTROL
NOX 10.9000 LB/H
0.2700 LB/MMBTU
CMBST. CONTRL./LOW NOX BURN.
CO 1.6700 LB/H
0.04EO LB/MMBTU
COMBUSTION CONTROL
VOC 0.1600 LB/H
0.0040 LB/MMBTU
COMBUSTION CONTROL
S02 0.7900 LB/H
0.0077 LB/MMBTU
F.S. : 0.1 GR/DSCF
PM 1.5900 LB/H
0.0150 LB/MMBTU
COMBUSTION CONTROL
NOX 7.9400 LB/H
0.0760 LB/MMBTU
COMBUSTION CONTROL
CO 0.7100 LB/H
0.0069 LB/MM3TU
COMDUSTION CONTROL
VOC 0.0600 LB/H
0.0006 LB/t'.r'.BTU
COMBUSTION CONTROL
... S BASIS
. . . FCT EFF
NSPS
BACT
BACT
BACT
BACT
NSPS
BACT
BACT
BACT
BACT
HANDLING CAPACITY, BUT WILL ENABLE THE REFINERY TO MAKE PREMIUM UNLEAD
INITIAL F* VIEW
REVIEW STATUS; 0^/01/1^33
POST STARTUP
PAGE G- 448
ID NUMBER TX-0061
SCURCE TYPE CCOE 5.5
-------
APPENDIX DETAILED SOURCE LISTING
==="= = "="="="~rrr=========r===== ==-..--__=_____:...:______= ^ ^ 05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - AUXILIARY
COMPANY NAME/SITE LOCATION UNION OIL ROHEOVILLE, IL
"""'""'~'"~"~-'" ~"~- "* - » «- __..,._,...___-.M._ ____
DETERMINATION IS BACT FOR A NEW SOURCE
PERMIT NO. 83 01 0013 DATE OF PERMIT ISSUANCE 06/09/83
DETERMINATION HADE BY ILLINOIS EPA CHRIS ROHAINE *1"H llll " START-UP~ 198S
(ASENCY) "AGENCY CONTACT PERSON) (TOME?
iniTS ... i BASIS
^ CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATER, W/AIR PREHEAT, 2 TOTAL 18-*. 00 MMBTU/H
NOX 0.1600 LB/MMBTU BACT
HEATER, W/0 AIR PERHEAT, 3 EA 25.00 KMSTU/H MAX EQUIPMENT DESIGN, EXCESS AIR ANALIZERS
NOX 0.1300 LB/TM8TU BACT
EQUIFMENT DESIGN, EXCESS AIR ANALIZERS
NOTES
PROJECT HAS NOT A MAJOR MODIFICATION FOR S02. S02 EMISSIONS GOVERNED BY NSPS. ALSO PERMIT NtttBER 197 090 AAI.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. DCWTC,, <: INITIAf- REVIEW POST STARTUP
~ ~^z:~zr!~~~~2~' .-._ -* ».__ KtVJtW STATUS *
PAGE G~
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE--- PETROLEUM REFINING - AUXILIARY 46500.00 BPSD
. ________ . .,_.. _ ,,. - .» .-
COMPANY NAME/SITE LOCATION VENTECH REFIN. KROTZ SPRINGS, LA
DETERMINATION IS BACT FOR A NEW SOURCE. DATE QF PERMIT ISSUANCE- 02/13/80
PERMIT NO. (REGION FILE NO.) PSD-LA-232 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK <214 )-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... k BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
CATALYTIC REGEN
SULFUR RECOVERY PLANT
FCCU FURNACE
50.00 MMBTU/H
PM 14.6000 LB/H
3 STAGE CYCLONE
S02 265.2000 LB/H
LOW H2S FUEL (OIL LB/DCSF)
NOX 66.6000 LB/H
LCV4 EXCESS AIR
VOC 2.2000 LB/H
LCW EXCESS AIR
CO 104.7000 LB/H
PLOT REGEN
S02 2.1000 LB/H
NONE
PM 0.0200 LB/Mr3TU
EFFICIENT OPERATION
S02 0.0260 LB/MM3TU
LC^I HCS FUEL
NOX 0.2300 LB/MMSTU
LOU EXCESS AIR - COMBST CONTRL
VOC 0.0060 LB/MMBTU
BACT
94.00
NSPS
BACT
BACT
NSPS
99.90
NSPS
BACT
NSPS
BACT
BACT
PAGE G- 450
-------
EFFICIENT OPERATION
CO 0.0200 LB/MMBTU NSPS
LOW EXCESS AIR
PAGE G- 451
-------
(CONTINUED) VENTECH REFIN.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
« BASIS
PCT EFF
VACUUM FURNACE
100.00 MMBTU/H
PM 0.0200 LB/MNBTU
EFFICIENT OPERATION
S02 0.0260 LB/MM3TU
LOW H2S FUEL
NOX 0.2300 LB/MMBTU
COMBUSTION CONTROLS
VOC 0.0060 LB/MK3TU
EFFICIENT OPERATION
CO 0.0200 LB/MMBTU
LOW EXCESS AIR
BACT
NSPS
BACT
BACT
BACT
NOTES
<*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 452
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER LA-0029
SOUSCE TYPE CODE
5.5
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1934
SOURCE TYPE/SIZE
PETROLEUM REFINING - ENTIRE OPERATION
COMPANY NAME/SITE LOCATION CHEVRON USA LUBE OIL
RICHMOND, CA
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. 27797
DETERMINATION MADE BY BAY AREA AQMD
(AGEK'CY ;
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
ELLEN LINOEP
fAGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 04/OS/82
ESTIMiTED DATE OF START-UP-- 1984
14151-771-6000
(PHONE;
POLLUTANT EMISSION LIMITS . . . £ B
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT
GAS COMPRESSOR, 9 EA
SEE NOTE
voc
0.3000 LB/D PER SEAL
SEAL/VAPOR RECOVERY
99.00
NOTES
CAPACITY 20 HP TO 1000 HP. FILE A 350-011
<*) INDICATES DATUM WAS TRUNCATED FOF? THIS TABLE.
PAGE G- 453
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/19/1^34
ID NUMBER CA-0045A
SOURCE TYPE CODE 5.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - ENTIRE OPERATION
21.00 MBBL/D
COMPANY NAME/SITE LOCATION GARY WESTERN REFIN.
GARY COMMUNITY RUAL STATION
FRUITA, CO 81521
MESA COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MADE BY EPA REGION VIII
(AGENCY)
JOHN DALE
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 06/24/81
ESTIMATED DATE OF START-UP--
(303)-837-3763
(PHCHE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
... & BASIS
... PCT EFF
VAP. REC. GAS CONT.
BOILER *4
CRUDE UNIT
DISTILLATE HDS
GILSONITE MELT
HYDRCCRACKER
18.00 MMSCFD
47.00 MLB/H STEAM
21.00 MBPSD
7.35 MBPSD
565.00 T/D
8.40 M3PSD
NQX 1.2600 LB/H
LOW NOX BURNERS
NOX 8.4100 LB/H
LOW NOX BURNERS
NOX 5.3100 LB/H
LOW NOX BURNERS
NOX 3.4200 LB/H
LOW NOX BURNERS
NOX 3.6000 LB/H
LOW NOX BURNERS
NOX 6.0200 LB/H
LOW NOX BURNERS
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 454
-------
(CONTINUED) GARY WESTERN REFIN.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
MARUZEN LUMMIS
NEW H2 PLANT
PLATFORMER
SUL RECOV PLANT
SUL RECOV PLANT
3.15 MBPSD
650.00 MSCFD
6.30 MBPSD
25.00 T/D
25.00 T/D
NOX 1.4400 LB/H
LOW NOX BURNERS
NOX 13.3200 LB/H
LOW NOX BURNERS
NOX 10.0900 LB/H
LOW NOX BURNERS
502 250.0000 PPM
60.1000 LB/H
TAIL GAS SCRUBBER
NOX 0.3600 LB/H
LOW NOX BURNERS
BACT
BACT
BACT
BACT
99.00
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TADLE.
PAGE G- 455
TNTTIAL OFVIEW POST STARTUP
b. 0 », 01/19S3
5.6
-------
APPENDIX DETAILED SOURCE LISTING ,-,,,«/
05/22/1S8H
SOURCE TYPE/SIZE PETROLEUM REFINING - ENTIRE OPERATION _ 184000.00 EPSD
COMPANY NAME/SITE LOCATION HAMPTON ROADS ENERGY CO, PORTSMOUTH, VA pORTSHOUTH CITY COUNTy
_ -.-. __ «. «. - -*"
_ -. ____ _ _ _ «,__^ » -. ____». -
ncTCDMTwsTrnM T* RAPT FOP A NEW SOURCE OATE OF PERMIT ISSUANCE 01/25/80
PPPMTT m 7RVA01 ESTIMATED DATE OF START-UP-
PERMIT NO. 78VA01 _. _Q, C1C7
DETERMINATION MADE BY EPA REGION III EILEEN GLEN (215 -597-S187
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
=-====-===-======r===========================================
- Eg SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS * BA?Jf
?5 THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
HEATER, RESIDUE HDS, STACK 1.
32.00 MMBTU/H
HEATER, HYDROGEN PLANT, STACK 1. 770.00 MMBTU/H
HEATER, SULFUR PLANT, STACK 1.
50.00 MMBTU/H
PM
SQZ
NOX
CO
PM
S02
NOX
CO
PM
S02
NOX
18.0000
96.0000
60.0000
11.0000
43.0000
£32.0000
144.0000
25.0000
LB/H
LB/H
0.3X S FUEL
LB/H
LOU NOX BURNERS
LB/H
GOOD OPERATION
LB/H
LB/H
0.3X S FUEL
LB/H
LC1.) NOX BURNERS
LB/H
GOOD OPERATION
4.0000 LB/H
15.0000 LB/H
0.3X S FUEL
15.0000 LB/H
LOW NOX BURNERS
BACT
HAAQ
BACT
BACT
BACT
NiU
BACT
BACT
BACT
NAAQ
BACT
PAGE G- 456
-------
CO 2.0000 UB/H BACT
SOOD OPERATION
PAGE G- 457
-------
(CONTINUED) HAMPTON ROADS ENERGY CO.
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
SULFUR RECOVERY UNIT
HEATER, DISTILLATE HDS, STACK 2. 130.00 MMBTU/H
HEATER, NAPHTHA HDS, STACK 2. 260.00 MMBTU/H
HEATER, CATALYTIC REFORMER, STA* 520.00 MMBTU/H
HEATER, ISOMERIZATION UNIT, STA* 95.00 MMBTU/H
POLLUTANT
EMITTED
S02
PM
S02
NOX
CO
PM
S02
NOX
CO
PM
S02
NOX
CO
PM
S02
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
152.0000 LB/H
BEACON UNIT OR EQUIVALENT
7.0000 LB/H
39.0000 LB/H
0.3X S FUEL
24.0000 LB/H
LOW NOX BURNERS
4.0000 LB/H
GOOD OPERATION
15.0000 LB/H
78.0000 LB/H
0.3X S FUEL
49.0000 LB/H
LOW NOX BURNERS
9.0000 LB/H
GOOD OPERATION
29.0000 LB/H
152.0000 LB/H
0.3X S FUEL
97.0000 LB/H
LCW NOX BURNERS
17.0000 LB/H
GOCD OPERATION
6.0000 LB/H
28.0000 LB/H
0.3X S FUEL
18.0000 LB/H
LOW NOX BURNERS
LOW NOX BURNERS
3.0000 LB/H
GOOD OPERATION
... 4 BASIS
. . . FCT EFF
NAAQ
99.50
BACT
NAAQ
BACT
BACT
BACT
NAAQ
BACT
BACT
BACT
NAA3
BACT
BACT
BACT
NAAQ
BACT
BACT
PAGE G- 458
-------
(CONTINUED) HAMPTON ROADS ENERGY CO.
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
HEATER, ATMOS. CRUDE DISTIL, ST* 505.00 MMBTU/H
GEN, UTILITY STEAM, STACK 3 60.00 MMBTU/H
C 1 An Tl 1^*
POLLUTANT
EMITTED
PM
502
NOX
CO
PM
S02
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
29.0000 LB/H
152.0000 LB/H
0.3X S FUEL
95.0000 LB/H
LOW NOX BURNERS
17.0000 LB/H
GOOD OPERATION
34.0000 LB/H
180.0000 LB/H
0.3X S FUEL
106.0000 LB/H
LOW NOX BURNERS
20.0000 LB/H
GOOD OPERATION
... * BASIS
. . . PCT EFF
BACT
NAAQ
BACT
BACT
BACT
NAAQ
BACT
BACT
soz
8.0000 LB/H
BACT
NOTES
"" " «;;""£! p"!""" BY NAAQS & PS° CUSS « INCREHEMT CONSTRAINTS. S02 EMISSIONS FROM START-UP OF LPG PLANT TO BE OF
row t D i KcbUU I xUro rKUfl OTHER SOURCES.
TANKERS BURN FUEL WITH S CONTENT <1.0X.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 459
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
ID NUMBER VA-0005
SCITCCE TYPE CODE
5.6
-------
APPENDIX « DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - ENTIRE OPERATION 750.00 MBPSD
_. _ .. ___ ________ -_ _ _.» .«..*. . ^^,«- ««. ___.»__..»«. «- »-
COMPANY NAME/SITE LOCATION HESS OIL - VIRGIN ISLANDS ST. CROIX, VI 00806
_______.._.._____,,.._- «,_____-______ - «-- -- ----- - ----------- ---- ------- --- - --- --- -
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 02/09/82
PERMIT NO. NONE ESTIMATED DATE OF START-UP 19S5
DETERMINATION MADE BY EPA REGION II ED NOWAK (212)-264-6690
(AGENCY) (AGENCY CONTACT PERSON) (PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FCC UNIT, 2
152734.00 BBL/D
PROCESS HEATERS, 3
SOZ 0.6000 7. BY WT
USE OF LOW S FEED STOCK VOG
PM 0.8UOO LB/MLB COKE BURN
ESP
NOX 175.0000 PFM 2X 02
LEA 4 LCU COMBST TEMPS
CO 500.0000 PPM VOL
CO BURNING REGENERATOR
VOC
CO BURNING REGENERATOR
S02 0.1000 GR/OSCF H2S,GAS
0.5000 7. S OIL
LOW S GAS OR OIL
PM 0.1000 LB/r.!3TU
PROPER MAINTENANCE
NOX 0.2000 LB/MMBTU GAS
0.3000 LB/Mf'.STU OIL
LEA & WASTE HEAT REC.
CO 0.2000 LB/HMBTU GAS
0.3000 LB/MM3TU OIL
LEA fc WASTE HEAT REC.
BACT
BACT
95.00
BACT
BACT
NSPS
NSPS
BACT
BACT
PAGE G- 460
-------
VOC 0.2000 LB/HMBTU GAS BACT
0.3000 LB/MMBTU OIL
LEA & WASTE HEAT REC.
PAGE G-
-------
(CONTINUED) HESS OIL - VIRGIN ISLANDS
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS ... t BASIS
CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FUGITIVE EMISSION SOURCES
VOC
BACT
GOOD ENGINEERING PRACT.
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 462
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER VI-OOOZ
SOURCE TYPE CODE 5.6
-------
APPENDIX DETAILED SOURCE LISTING
-----__-.-___.___.__._______.._ _ _ 05/2Z/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - ENTIRE OPERATION
COMPANY NAME/SITE LOCATION HILL PETROLEUM CO. KROTZ SPRINGS, LA
~~" ~~~' --__ _--_ __-__«. ___ -_«_. -__«,_ ._.. «._- -___-._. _____ »_ __..__
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/09/fiQ
PERMIT NO. (REGION FILE NO.) PSD-LA-286A ?£in£e0 DATE OF START UP 10/°9/8°
DETERMINATION MADE BY EPA REGION VI JOE WINKLEP m-76?-?&5o
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
= = ======== = = « = === = = «=««= = ^^
THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ...PCT EFF
LIQ. STORAGE TANKS « 11.1 PSIA*
LICJ. STORAGE TAWS (> 11.1 PSIA«
LIQUID PETROLEUM PUMPS
LIQUID PETROLEUM BARGES
HEATER, REFORMER CHARGE
100.15 MMBTU/H
VOC
VOC
VOC
VOC
NOX
CO
FLOATING ROOF TANK W/DBL SEALS
PRES. VESSELS W/ VAPOR BAL.
DOUBLE MECHANICAL SEALS
SUBMERGED FILL LINES
0.0610 L6/MM3TU GAS
0.0430 LB/T'MBTU PROPANE
LCM NOX BURNERS W/F.G.
4.0000 LB/Ii;i3TU G\5
1.5000 LB/M:'STU PROPANE
FLUE G4S MONITORING
MONITOR
PAGE G- 463
-------
(CONTINUED) HILL PETROLEUM CO.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
I BASIS
PCT EFF
HEATER, HYDROTREATER CHARGE
HEATER, HYDROTREATER STABLIZER
REBOILER, REFORMER STABILIZER
REBOILER, STABILIZER (GASOLINE)
BOILER
18.29 MMBTU/H
13.58 MMBTU/H
13.93 MMBTU/H
15.49 MMBTU/H
78.15 MMBTU/H
NOX 0.0610 LB/MMBTU
LOW HOX BURNERS W/F.G. MONITOR
CO 4.0000 LB/MMBTU
FLUE GAS MONITORING
NOX 0.0610 LB/MMBTU GAS
0.0430 LB/MMSTU PROPANE
LOW NOX BURNERS W/F.G. MONITOR
CO 4.0000 LB/KM3TU GAS
1.5000 LB/MMBTU PROPANE
FLUE GAS MONITORING
NOX 0.0610 LB/MMBTU GAS
0.0430 LB/NC3TU PROPANE
LCW t.'OX BURNERS W/F.G. MONITOR
CO 4.0000 LB/MMBTU GAS
1.5000 LB/MM3TU PROPANE
FLUE GAS MCMITORING
NOX 0.0610 LB/MM3TU
LOU NOX BURNERS W/F.G. MONITORS
CO 4.0000 LB/MMBTU
FLUE GAS MONITORING
NOX 0.1000 LB/MMBTU GAS
0.1100 LB/MfSTU PROPANE
Ley NOX BURNERS W/F.G. MONITOR
CO 4.0000 LB/f"l3TU GAS
1.5000 LB/?":BTU PROPANE
FLUE GAS MONITORING
NOTES
THE SOURCE WILL OPERATE CONTINUOUSLY, 6640 HRS/YR. ALL CONTROL STRATIGES ARE CONSIDERED BACT.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 464
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER LA-0031
SC'J-CE TYPE CODE
5.6
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - ENTIRE OPERATION
COMPANY NAME/SITE LOCATION MIAMI VALLEY REFIN. CO.
AURORA, IN
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. PC(15)1485
DETERMINATION MADE BY INDIANA APCD
(AGENCY)
FRANK PROFIT
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/07/81
ESTIMATED DATE OF START-UP
(317)-633-C664
C PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS ... & BASIS
CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FBC COAL FIRED BOILER
NOTES
50000.00 BTU/H
PM 0.0600 LB/MM8TU
MULTICLONE « BAGHOUSE
S02 0.1400 LB/MM3TU
99.00
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 465
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER IN-0009
SO'JRCE TYPE CODE 5.6
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - ENTIRE OPERATION
10.00 MBPSD
COMPANY NAME/SITE LOCATION MITCHELL ENERGY
HWY 380, 2 MI W OF BRIDGE PORT
BRIDGEPORT, TX
WISE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-TX-139
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 07/24/81
ESTIMATED DATE OF START-UP
( PHONE )
PROCESSES SUBJECT
TO THIS PERMIT
HEATERS, 2
BOILER
FLARE
THROUGHPUT
CAPACITY
21.34 MMBTU/H
12.55 MMBTU/H
POLLUTANT
EMITTED
VOC
VOC
VOC
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0.0030 LB/MM3TU
EFFICIENT OPERATION
0.0030 LB/MM3TU
EFFICIENT OPERATION
0.0460 LB/MMBTU
... & BASIS
... PCT EFF
BACT
BACT
BACT
MALTHA STORAGE TANKS, 2
KEROSENE STORAGE TANKS, Z
DIESEL STORAGE TANKS, 2
EFFICIENT OPERATION
10000.00 B3L EA
10000.00 BBL EA
10000.00 BBL EA
VOC
VOC
VOC
0.3700 LB/MM3TU
DOUBLE SEALS
0.1600 LB/MMBTU
DOUBLE SEALS
0.1200 LB/MMBTU
DOUBLE SEALS
BACT
BACT
BACT
PAGE G- 466
-------
(CONTINUED) MITCHELL ENERGY
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS . .. « BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
RESIDUE STORAGE TANKS
PROCESS DRAINS
VALVES & FLANGES
PUMP SEALS
CRUDE UNLOAD
PRODUCT UNLOAD
10000.00 BBL EA
VOC 0.0100 LB/MM8TU
DOUBLE SEALS
VOC 0.1600 LB/MMBTU
MAINTENANCE PROG.
VOC 11.7000 LB/MMBTU
MAINTENANCE PROG.
VOC 4.1700 LB/MMBTU
MAINTENANCE PROG.
VOC Z.6200 LB/MMBTU
MAINTENANCE PROG.
VOC 1.4800 LB/MM3TU
MAINTENANCE PROG.
BACT
BACT
BACT
BACT
BACT
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 467
INITIAL REVIEW POST STARTUP
REVIEU STATUS; 04/01/1933
ID NUMBER TX-0050
SOURCE TYPE CODE 5.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - ENTIRE OPERATION 26.30 T/D
COMPANY NAME/SITE LOCATION SOUND REFINING, INC. TACOMA, WA 9S422
2628 MARINE VIEW DRIVE
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 10/17/83
PERMIT NO. N/C 2445 ESTIMATED DATE OF START-UP-- 1984
DETERMINATION MADE BY PUGET SOUND APCA HARRY MATTERS (206 )-344-7334
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
RECOVERY PLANT, SULFUR 26.30 T/D
S02 75.0000 PPM
SEE NOTE 91
NOTES
USIT 150 ALSO SUBJECT TO THE REQUIREMENTS OF 40 CFR PART 60, SUBPART J AND PSAPCA LETTER DATED 10/17/83.
NOTE SI SOUR WATER STRIPPER, AMINE STRIPPER, CLAUS UNIT, BEVIN TAILGAS CATALYTIC UNIT, STRETFOSD UNIT
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE' G- 468
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/13/19S4
.TO NUMBER WA-0010
SOURCE TYPE CCDE
5.6
-------
APPENDIX ~ DETAILED SOURCE LISTING
=========== = _ _ 05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - ENTIRE OPERATION 9010.00 BPD
--- -_..___ _«_ _______ - _-_-__«_ ______ __ __ _ __«.._..__-, _ __«____«
COMPANY NAME/SITE LOCATION SOUND REFINING, INC. TACOMA, WA 9842?
2628 MARINE VIEW DRIVE
'
OR * NEW SOURCE' DATE OF PERMIT ISSUANCE- 10/17/83
PTCDMTU M»r ESTIMATED DATE OF START-UP 1984
DETERMINATION MADE BY PUGET SOUND APCA HARRY MATTERS (206 >-344-733
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM REFINING - ENTIRE OPERATION
COMPANY NAME/SITE LOCATION SUNLAND REFIN. CORP. BAKERSFIELD, CA
DETERMINATION IS LAER FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/22/60
PERMIT NO. SJ-79-22 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION IX DAVID SOLOMON (415)-454-8066
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
STORAGE TANKS
LOADING RACKS
TANK TRUCKS
VALVES/FLANGES/PUMPS/COMFRESSORS
WORK WATER SEPARATOR
SUMP
voc
voc
voc
voc
voc
voc
DOUBLE SEAL INTERNAL FLOATING ROOF
OR VAPOR RECOVERY
30.0000 MG/L OF PRODUCT
CARBON ABSORPTION SYS
TRAILER TANKS TO BE LEAK TIGHT
FUGITIVE I«M PROGRAM
REQUIRED TO BE COVERED
REQUIRED TO BE COVERED
PAGE G- 470
-------
(CONTINUED) SUNUND REFIN. CORP.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS ... $ BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
PROCESS TURNAROUNDS
VACUUM DEVICES
PRESSURE RELIEF VALVES
COMBUSTION SOURCES
SULFUR RECOVERY PLANT
VOC
VOC
VOC
S02
NOX
S02
VENT DEPRESSURED & PURSED TO FUEL GAS SYS
VENTED TO FUEL GAS SYS
VENTED TO FLARE SYS & INCINERATED
0.0300 GR/DSCF H2S
50.0000 PPM 3X 02
LOW NOX BURNERS
NON-CATALYTIC AMMONIA INJECTION
1.0000 LB/H
LAER
LAER
BACT
LAER
NOTES
AWAFOR COLLECTION SYS MUST BE VAPOR TIGHT.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 471
INITIAL REVIEW POST STARTUP
REVIEW STATUS-' 04/01/19S3
10 NUMBER CA-0003
SOURCE TYPE CODE 5.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
PETROLEUM REFINING - ENTIRE OPERATION
26000.00 BPSD
COMPANY NAME/SITE LOCATION SWANN OIL CO.
CHESAPEAKE, VA
CHESAPEAKE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. 78VA04
DETERMINATION MADE BY EPA REGION III
(AGENCY)
EILEEN GLEN
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 03/30/81
ESTIMATED DATE OF START-UP
(215)-597-8187
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
HEATER, CRUDE UNIT ATMOS.
HEATER, CRUDE UNIT VACUUM
HEATER, VISBREAKER
THROUGHPUT POLLUTANT
CAPACITY EMITTED
94.00 MMBTU/H
PM
S02
NOX
CO
18.00 MMBTU/H
PM
S02
NOX
CO
44.00 MMBTU/H
PM
S02
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
9.0000 LB/H
18.0000 LB/H
0.57X S IN FUEL
36.0000 LB/H
2 STAGE + OFF-STOICH. CCMB.
3.0000 LB/H
GOOD OPERATION
2.0000 LB/H
3.0000 LB/H
S IN FUEL 0.37.
7.0000 LB/H
2 STAGE + OFF-STOICH. COK3.
1.0000 LB/H
GOOD OPERATION
4.0000 LB/H
8.0000 LB/H
. . . & BASIS
... PCT EFF
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
S IN FUEL 0.37.
NOX 17.0000 LB/H
2 STAGE + OFF-STOICH. CCtB.
BACT
PAGE G- 472
-------
CO 1.0000 LB/H BACT
GOOD OPERATION
PAGE G- 473
-------
(CONTINUED) SWANN OIL CO.
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
HEATER, NAPHTHA REFORMER 50.00 MMBTU/H
HEATER, NAPHTHA HYOROOESULFURIZ* 16.00 MMBTU/H
HEATER, DISTILLATE HYDRODESULFU» 16.00 MMBTU/H
BOILER, STEAM 29.00 MM3TU/H
EMERGENCY FLARE SYS
POLLUTANT
EMITTED
PM
SOS
NOX
CO
PM
S02
NOX
CO
PM
502
NOX
CO
PM
S02
NOX
CO
S02
NOX
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION . . .
1.0000 LB/H
0.3000 LB/H
BURN REFINERY GAS <0.0063X S
11.0000 LB/H
2 STAGE + OFF-STOICH. COMB.
1.0000 LB/H
GOOD OPERATION
0.3000 LB/H
0.1000 LB/H
BURN REFINERY GAS <0.0063X S
4.0000 LB/H
2 STAGE + CFF-STOICH. COMB.
0.3000 LB/H
GOOD OPERATION
0.3000 LB/H
0.1000 LB/H
BURN REFINERY GAS <0.0063X 5
4.0000 LB/H
2 STAGE * OFF-STOICH. COM3.
0.3000 LB/H
GOOD OPERATION
0.5000 LB/H
0.2000 LB/H
BURN REFINERY GAS <0.0063X S
7.0000 LB/H
2 STAGE « STOICHICMETRIC CCttS
0.6000 LB/H
GOOD OPERATION
0.0100 LB/H
0.2000 LB/H
& BASIS
PCT EFF
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 474
-------
(CONTINUED) SWANN OIL CO.
PROCESSES SUBJECT
TO THIS PERMIT
POWER PUNT., TANKER
THROUGHPUT POLLUTANT
CAPACITY EMITTED
VARIABLE
PM
S02
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
14.0000 LB/H
311. 0000 LB/H
64.0000 LB/H
1.0000 LB/H
... * BASIS
. . . PCT EFF
BACT
BACT
BACT
BACT
S02
14.0000 LB/H
BACT
NOTES
SC2 EMISSIONS FROM ATMOSPHERIC HEATER, VACUUM HEATER, t VISBREAKER HEATER SHALL NOT EXCEED THE SPECIFIED EMISSION RATES ON A 2
- ROLLING AVERAGE BASIS.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 475
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01*933
ID NUMBER VA-0002
SOURCE TYPE CODE
5.6
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM REFINING - ENTIRE OPERATION 200.00 MBPSD
_ - -
COMPANY NAME/SITE LOCATION VIRGIN ISLANDS REFINERY CORP. ST. CROIX, VI
ESTATE BETHLEHAM
__ __._._ _ ._«_.._ _.. . _~_~ . ___ » «, . -.-. _.__~__ _. -. ____ »._.»-. «-»«. ., «i
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/04/81
PERMIT NO. NOKE ESTIMATED DATE OF START-UP 1985
DETERMINATION HADE BY EPA REGION II ED NOWAK (212J-264-8690
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
BOILERS, FOSSIL FIRED, 3
175000.00 BBL/D
HYDROGEN PLANT
CO 14.0000 T/YR
GOOD BOILER OPERATION
VOC 3.0000 T/YR
GOOD BOILER OPERATION
NOX 0.2000 LB/MtlBTU GAS
0.3000 LB/MMBTU OIL
PM 0.3520 LB/MtlBTU
S02 20.0000 PFM H£S GAS
0.3300 X S BY WT, OIL
CO 105.0000 T/YR
GOOD BOILER OPER./NO FUEL OIL
VOC 19.0000 T/YR
GOOD BOOILER OPER./NO FUEL OIL
NOX 1088.0000 T/YR
STOICHIO. COKBST./NO FUEL OIL
PM 0.3520 LB/tir.BTU
S02 3.0000 T/YR
NO GAS<.1 GR/DSCF H2S
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 476
-------
(CONTINUED) VIRGIN ISLANDS REFINERY CORP.
PROCESSES SUBJECT
TO THIS PERMIT
PROCESS HEATERS
FCC UNIT
SULFUR RFrnVFDY Dl AWT
THROUGHPUT POLLUTANT
CAPACITY EMITTED
CO
voc
NOX
PM
S02
175000.00 BBL/D
CO
VOC
NOX
PM
S02
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
369.0000 T/YR
GOOD BOILER OPERATION
73.0000 T/YR
GOOD BOILER OPER.
0.3000 LB/MMBTU OIL
0.2000 LB/MMBTU ALT. FUELS
0.3520 LB/MMBTU
3683.0000 T/YR
OIL<.33XS WT/ALT<.1GR/DSCF H2S
565.0000 T/YR
3247.0000 T/YR
GOOD BOILER OPER.
0.3000 LB/MMBTU OIL
0.2000 LB/MMBTU ALT. FUELS
1.0000 LB/MLB COKE BURN
0.1000 LB/MMBTU SUPP. OIL
79.0000 T/YR
OIL<.33XS WT/ALT<.1GR/DSCF H2S
... 8 BASIS
... PCT EFF
BACT
BACT
BACT
BACT
BACT
NSPS
BACT
BACT
LAER
NSPS
PETROLEUM LIQUID STORAGE TANKS
CO 29.0000 T/YR
GOOD HEATER OPERATION
VOC 35.0000 T/fR
GOOD HEATER OPERATION
NOX 0.3000 LB/MMBTU OIL
0.2000 LB/MMSTU ALT.
PM 0.3520 LB/MMBTU
S02 365.0000 T/YR
CLAUS SYS. W/ 3 UNITS
OIL<.33S WT/ALT<.1GR/DSCF H2S
VOC 937.0000 T/YR
FLOATING ROOF TANKS
BACT
BACT
BACT
BACT
NSPS
NSPS
PAGE G- 477
-------
(CONTINUED) VIRGIN ISLANDS REFINERY CORP.
PROCESSES SUBJECT
TO THIS PERMIT
PUMPS, SEALS, VALVES, FLANGES
MARINE LOAD t UNLOAD FACILITY
THROUGHPUT POLLUTANT
CAPACITY EMITTED
VOC
VOC
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION . . .
177.0000 T/YR
64.0000 T/YR
SEALS
& BASIS
PCT EFF
BACT
SIP
INCINERATOR, MULTI-CHAMBER
API WASTE OIL SEPERATOR
CO NONE
GOOD OPERATION
NOX NONE
GOOD OPERATION
PM 0.3000 LB/H
VOC 436.0000 T/YR
FIXED COVER/FOAM SPHERES
BACT
BACT
NSPS
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 478
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER VI-0001
SOURCE TYPE CODE
5.6
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
= = - = = = = = - = = = = = = = = = = = = = = = = = = = = = =: = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = == = = r = = = = = = = = = = = = = = = r = = = = = = = = = = = = r= = = r = r = = = =r = = = = = r = r = = r
SOURCE TYPE/SIZE BULK TERMINALS
_-.__-_ -_-_-__.._.._..__.... -,._ _..__.. «._---_-.___,.__ ___..___..___,._.______ _______ «.-.__.__ «.»_._«._»«.«
COMPANY NAME/SITE LOCATION AMOCO OIL CO., GRANVILLE MILWAUKEE, WI
°R * NEW SOURCE- DATE OF PERMIT ISSUANCE- 06/23/80
nrrroMT T"064 ESTIMATED DATE OF START-UP- 1981
DETERMINATION MADE BY WISCONSIN DNR ELIZABETH SPAETH (414)-257-4929
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
; = = = = = = = = = = r = = = = r = === = r= = = = = r==r^= = = = = ==r=== = = rrrr = == = = ===== = = = = = = ==r = = = = = i: = = = = = = = = = = = =: = = = = = = = = = = = = = = = = = = == = = = = = _ = = = = = = = = = = = -.-___-
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
""
TERMINAL 214494.00 MGAL GASOLI*
VOC 30.0000 MG/L LAER
_.cnMTl A FLOAT ROOF & VAPOR RECOVERY SYS. 97.00
TERMINAL 71358.00 MGAL 82 OIL
VOC 80.0000 MG/L
VOC 30.0000 MG/L LAER
NOTES
OFFSET OBTAINED BY CLOSING JONES ISLAND TERMINAL, EXTRA EMISSIONS BANKED 41.55 TPY
, , , INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 479 ID NUMBER WI-0005 SC'JSCE TYPE CODE S~7
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE BULK TERMINALS
COMPANY NAME/SITE LOCATION ASHLAND PETROLEUM CO. COVINGTON, KY 41015
30TH « JONES ST. KENTOH COUNTY
_ _____«,_ _-._-. ». _-. -. -. -.-. _ _ .__., _ _-. _
DETERMINATION IS BACT DATE OF PERMIT ISSUANCE 04/01/81
PERMIT NO. C-81-37 ESTIMATED DATE OF START-UP-- 19S1
DETERMINATION MADE BY KENTUCKY DAPC BILL DILLS (502)-564-33S2
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ _ .. __ .. _ H v_ v _ _.* _ _ _ »_ ____________ .. .. _ w _ v_ .»_ . «*»b -_ w « v «.__> . » -, -. -. . .
BOTTOM FILL LOADING RACK 3000.00 GAt/MIN
VOC 80.0000 MG/L GROUND LOADING
CARBON ABSORPTION
NOTES -
THIS PERMIT GRANTED UNDER A VOC BUBBLE REQUEST TO AtlEVATE RETROFITTING EXISTING TANKS W/FLOATING ROOFS. PERMIT N/A TO BACT/LA
ER.
THIS BUBBLE SET THE ALLOWABLE AT 30000. MG/L
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
INITIAL REVIEW POST STARTUP
REVIEW STATUS: OV01/19S3 02/13/1934
PAGE G- 480
ID NUMBER KY-0019
SCL'SCE TYPE CODE 5.7
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE BULK TERMINALS - 476000.00 BBL
COMPANY NAME/SITE LOCATION BAYTANK INC., HOUSTON SEABROOK, TX
HARRIS COUNTY
DATE °F PERMIT ISSUANCE- 02/12/82
DETERMINATION MADE BY TEXAS ACB STUART KEIL ff I' °?
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS t^OIFICATION . . . PCT EFF
STORAGE TANKS, 49 CAPACITY VA*
V°C BACT
FLARING EMIS., SEE NOTE 2 99 00
WASTE WATER SEPERATOR, SEE NOTE» "AT' W/>°'5 PSIA ^ FRESS'
VOC BACT
COVERS W/VENTS TO FLARES 99.00
NOTES
RHTEuTTu onnIEnn'AIER SEPARATOR INCLUDES Z DECANTERS S DOUBLE SKIMMER SYS. NOTE 2 - ALSO MATERIALS WITH < 0.5 PSIA VAP. PRESS
BUT WITH ODGR OR TOXICITY EFFECTS ARE REQUIRED TO MEET THESE EQUIPMENT STANDARDS / TO USE ADSORBERS.
PAGE G- 431 ro HurfBER TX.0108
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TrPE/SIZE- BULK PLANTS 1.00 MMGAL/D
COMPANY NAME/SITE LOCATION TIME OIL CO. RICHMOND, CA
.» _ _ ««.,.... _____<__ _.. w .__. __._ v_ _ __.. ««..._.._ __ _«..__«....*..._._ _ _ _ _«___.- _ _~
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/23/80
PERMIT MO. 27611 ESTIMATED DATE OF START-UP 1981
DETERMINATION MADE BY BAY AREA AQMO KELLY WEE (415 )-771-6000
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
-. .. .. _-.._ __._.._.._«._ .^ ~^ ~~ ~ ^_ _ _._ ____.-._-._..__._.__.__._._,__.__.._.,._.._.».__,.
GASOLINE BULK LOADING RACK 1.00 MMGAL/D
VOC 91.0000 LB/D BACT
90.0000 LB/MMGAL
CARBON ADSORPTION 93.60
NOTES
SOURCE TEST *83062. FILE A 350-004
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 462
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/19/1934
ID NUMBER CA-0051
SOURCE TYPE CODE 5.6
-------
APPENDIX DETAILED SOURCE LISTING
= ---_--__..._____._.____.____..______ 05/22/1984
SOURCE TYPE/SIZE STORAGE OF PETROLEUM LIQUIDS
COMPANY NAME/SITE LOCATION MCKESSON CHEMICAL CO. TULSA, OK
-. .. «. _ _ _ __. ». _.».. _ ___ .'" - - - - .». ....__._,. _^.___ __ __<1-r_ _, _.
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PPpMTT TWIturF in/*,/*,
PERMIT NO. SEE NOTE E OF PERf1IT ISSUANCE 10/01/81
DETERMINATION MADE BY TULSA CITY-COUNTY HEALTH DEPT BILL GIBBONS "IJ1SS-55S ^ START-UP"
{AGENCY) (AGENCY CONTACT PERSON) (PHCHE)
THROUGHPUT POLLUTANT EMISSION LIMITS 4 BASIS
--_--._. CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION !!!pCTEFF
~~~"~~"*""~'~*"" "" "~ ~" ~ ,.__-___ , ^._»_ ___ ___ __w __. _ _.,__ ^
DRUM FILLING FACILITY
VOC
VAPOR RECOVERY LOOP 90.00
NOTES -
CAPACITY
(*) INDICATES DATL'M WAS TRUNCATED FOR THIS TABLE.
PAGE G- 483
INITIAL REVIEW POST STARTUP
REVIEW STATUS: OV01/19S3
ID NU!^3ER CK-0011
SOL"CE TYPE CODE 5.9
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE TRANSPORT « MARKETING - PETROLEUM PRODUCTS
COMPANY NAME/SITE LOCATION COLUMBIA GAS TRANSMISSION CORP. SUGAR GROVE, OH
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 04/13/81
PERMIT NO. 0123000137 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY OHIO EPA CD GEORGE DEMIS (614>-864-3195
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
NAT. GAS FIRED I. C. ENGINES
NOX 5.0000 G/HP-H
ENGINE DESIGN
CO 2.0000 G/HP-H
ENGINE DESIGN
VOC 0.3000 G/HP-H
ENGINE DESIGN
NOTES
(«) INDICATES DATUM WAS TRUNCATED FOP THIS TABLE.
PAGE G- 484
INITIAL REVIEW POST STARTUP
REVIEW STATUS-- 04/01x933
ID NUMBER OH-0024
SOURCE TYPE CCDE 5.11
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE TRANSPORT 8 MARKETING - PETROLEUM PRODUCTS
~~ - . _ «.. _ _.. *.^*»_*»~«WMH.>T« __-.______ w«._ __-,_,» -._«» _ _.» _»_..-.^__. .B_.,-._ _____
COMPANY NAME/SITE LOCATION CRYSEN REFINING, WESTERN DIV. WOODS CROSS, UT
DAVIS COUNTY
CFDHTTI^TI°N IS DATE OF PERMIT ISSUANCE 11/12/82
n^rnM L ESTIMATED DATE OF START-UP 1933
DETERMINATION MADE BY UTAH BAQ DONALD ROBINSON (801 )-533-6108
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION !.. PCT EFF
NAPTHA TANK, 2 365000.00 BBL/YR EA
VOC
INTERNAL FLOATING ROOF
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 485
INITIAL REVIEW POST STARTUP
REVIEW STATUS-- 04/01/1933 22/13/1964
ID NUMBER UT-0027
SOURCE TYPE COCE 5.11
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE TRANSPORT t MARKETING - PETROLEUM PRODUCTS 22600.00 GAL/D
_ __ _ -. _. _____ _.-._. -. -. _ _«__ __
COMPANY NAME/SITE LOCATION DEPT. OF THE NAVY CORPUS CHRIST!, TX
NUECES COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/15/32
PERMIT NO. X3S18 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY TEXAS ACB STUART KEIL (512)-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OF} PROCESS MODIFICATION ... PCT EFF
____.,_.._.. _.,_-.__,_._.._ _ _-. »_., «.__._ -» ^ «»«.. -. -^ »-. -.
LOADING RACK/STORAGE TANKS, 2 6000.00 BBL
VOC NIL EMISSIONS
DISPLACED VAPORS ROUTED TO FLARE 99.0
NOTES
IB'/. OF DISPLACED VAPORS ARE ASSUMED TO BE NOT COLLECTED DUE TO FUGITIVE LOSSES.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1*33
PAGE G- 4S6 ID NUMBER TX-0099 SOURCE TYPE CODE 5.11
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE TRANSPORT ft MARKETING - PETROLEUM PRODUCTS
COMPANY NAME/SITE LOCATION NORTHERN ALASKAN PIPELINE
2000.00 MMCFD
AK
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-X81-03-09
DETERMINATION MADE BY EPA REGION X
(AGEKCY)
PAUL BOYS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 02/23/81
ESTIMATED DATE OF START-UP
(2C6)-442-1193
(PHCHE)
PROCESSES SUBJECT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
... « BASIS
... PCT EFF
MAINLINE COMPRESSOR TURBINE
REFRIG. COMPRESSOR TURBINE
ELECT. GEN. TURBINE
GLYCOL HEATER MISC.
NOTES
NOX 150.0000 PPM
80.0000 KG/H
DRY CONTROLS
NOX 150.0000 PFM
38.0000 KG/H
DRY CONTROL
NOX 150.0000 PPM
15.0000 KG/H
DRY CONTROL
NOX 43.0000 NG/J
4.0000 KG/H
LCU NOX BURNERS
BACT
BACT
BACT
BACT
vn
Tc Ar?
STATION' 7 WILL BE BUILT ALONG PIPELINE. ALSO TOTAL LIMIT FOR EACH STATION OF 175 KG/HR OR 1
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 487
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUflBER AK-0002
SOURCE TYPE CODE 5.11
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE TRANSPORT t MARKETING - PETROLEUM PRODUCTS 933.00 MEBL/D
COMPANY NAME/SITE LOCATION NORTHERN TIER , AK
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 09/14/81
PERMIT NO. (REGION FILE NO.) PSD-X31-14 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION X PAUL BOYS (206)-442-1193
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
NOTES
FOR PERMIT CONDITIONS, SEE ATTACHMENT, ALL ARE BASED ON TECHNOLOGY AND ECONOMICS.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 483
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER AK-0001
SCL'SCE TYPE CC3E 5.11
-------
APPENDIX ~ DETAILED SOURCE LISTING
_ 05/22/1984
= :: = = = = = :::: = = :: = = = = = = = = = = === = = = = = = = = = = r = = = = r===r=r=r = = ====rrr========rr===r==r==r===r= === = = r=r = = = =
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS 55000.00 HP
COMPANY NAME/SITE LOCATION AMERADA HESS TULSA TX
'
"" """" »-. -. «.__. _ _,.
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PEBMIT TSSUANrp
PERMIT HO. (REGION FILE NO. ) PSD-TX-328 S?in!ra ?ATE 0?S?ART"uP
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK "-76?-?W START-UP"
(ASENCY) (AGENCY CONTACT PERSON) (PHONE)
- = = = = = r = s = = r = r = -p*
= - = = = = = = -== = = = - = = - = ===== = = = = = ===rr = r^ri:r = r = = r = =
THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
ENGINE, NAT. GAS, COMPERSSOR, 3* 1600.00 HP
NOX 10.6000 G/HP-H
ADJUSTED AIR FUEL RATIO
VOC 53.0000 T/YR
NORMAL EQUIP. OPERATION
CO 1.4000 G/HP-H
NORMAL EQUIP. OPERATION
SOS 0.2500 T/YR
NORMAL EQUIP. OPERATION
PM TRACE
NORMAL EQUIP. OPERATION
BACT
BACT
8ACT
BACT
BACT
NOTES
(*) INDICATES DATUM WAS TRUNCATED F09 THIS TABLE.
PAGE G- 489
ID NUMBER TX-0017
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
NATURAL GAS/GASOLINE PROCESSING PLANTS
250.00 MMCFO
COMPANY NAME/SITE LOCATION AMOCO PRODUCTION
UINTA, WY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. CT-272
DETERMINATION M40E BY WYOMING AQD
(AGENCY)
BERNIE DAILEY
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 12/20/79
ESTIMATED DATE OF START-UP 1983
(307)-777-7391
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
BOILER, GAS, 2 EA
HEATER, GAS
THROUGHPUT
CAPACITY
65.50 MMBTU/H
33.30 MHBTU/H
POLLUTANT
EMITTED
NOX
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION . . .
0.2000 LB/MMBTU
DESIGN
t BASIS
PCT EFF
BACT
HEATER, GAS
INCINERATOR, SULFUR PLANT
7.10 MMBTU/H
NOX 0.2000 LB/MMBTU
DESIGN
NOX 0.2000 LB/MMBTU
DESIGN
S02 311.5000 LB/H
CLAUS S CBA
BACT
BACT
BACT
93.60
NOTES
AN EXTENSIVE BACT ANALYSIS BASED ON ECONOMIC, ENERGY, & ENVIRONMENTAL FACTORS COMPARING CLAUS-CBA TO CLAUS-SCOT WAS PERFORMED.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 490
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER WY-0008
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE --- NATURAL GAS/GASOLINE PROCESSING PLANTS SEE NOTE
COMPANY NAME/SITE LOCATION AMOCO PRODUCTION CO.
BILLINGS COUNTY
* NE - DATE Of PERMIT ISSUANCE- 01/12/83
DETERMINATION MADE BY NORTH DAKOTA SHD GARY HELBLING --
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
TnTHr FT THROUGHPUT POLLUTANT EMISSION LIMITS . . . g BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
INCINERATOR STACK SEE NOTE
S02 SEE NOTE BACT
CLAUS UNIT « CBA 98.60
NOTES
c
nu,
O"4 LIMIT OF 249 LB/H S02.
T° BE CONSTRUCTED IN "EE STEPS. THE PLANT WILL PROGRESS FROM A 25 MMCF/D PLANT WITH AN EMISSION LIMIT OF 6? 25
5° MMCF/D PUNT "ITH AN EMISSIOM LIMIT OF l««-5 LB/H S02 4 THEN TO A 100 KHCF/D PLANT WITH AN
^JTTT \t DPVTFW Pfr«;T «5TAQTnD
<,*)_INOICATES DATUM WAS TRUNCATED FOR THIS TABLE. KLVltn STATUS: 'o*/01/l?33 TObT5TARTUP
PAGE G- 491 ID K1JHBE3 no.0003 ^^l^CC3E~~~slll
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION ATW COMPANY ISABELLA TUP, MI
ISABELLA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 04/28/83
PERMIT NO. 631-82B ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY MICHIGAN DNR LAURA OTWELL (517)-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GAS SWEETENING AMINE FACILITY 2.30 MMCF/0
S02 24.0000 LB/H
2 STAGE CAUST. SCRUBS..INCINERATOR 99.99
NOTES
RULE 403(4) OF THE MICHIGAN APC RULES REQUIRE BACT ON ALL NEW SWEETENING FACILITIES. DETERMINATION IS BASED ON DETAILED ECOS'CM
1C ANALYSIS AND EXPECTED EFFICIENCIES OF VARIOUS CONTROL SYSTEMS.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS'- 04/19/1964 03/13/1934
PAGE G- 492 ID NUMBER MI-0032 SOLACE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
======= = r=== = ::============!.___:._ = r-==-==5===== 05/22/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS 60.00 MMCFD
COMPANY NAME/SITE LOCATION CHAMPLIN PETROLEUM t MY
UINTA COUNTY
DETERMINATION IS BACT FOR A NEW SOURCF
PERMIT NO. CT-515 SOURCE. DATE Qf pERMIT ISSUANCE_. 11/08/83
DETERMINATION MAnF RY uvnMTui- ir,n ESTIMATED DATE OF START-UP
utitKFUNAJIUN MADE BY WYOMING AQD CHUCK COLLINS (307)-777-7391
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS ft BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION .".".' PCT EFF
COMPRESSOR, 2 EA
HEATER, GAS
TURBINE, 2 EA
2250.00 HP
3.75 MMBTU/H
886.00 HP
NOX 4.0000 G/HP-H
DESIGN
CO 2.0000 G/HP-H
DESIGN
VOC 0.5000 G/HP-H
DESIGN
S02 0.8900 LB/H
NOX 0.2300 LB/MMBTU
CO 0.0200 LB/MH3TU
S02 0.3000 LB/H
NOX 1.0800 G/HP-H
DESIGN
CO 2.0000 G/HP-H
DESIGN
VOC 0.0100 G/HP-H
DESIGN
S02 0.5800 LB/H
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE 6- 493
INITIAL REVIEW POST STARTUP
REVIEW STATUS:
ID NUMBER WY-0005
SOL'?CE TYPE CODE 5.12
-------
NOTES
S02 EMISSIONS LIMITS BASED ON FUEL S CONTENT OF LESS THAN 20 GR/100 SCF.
INITIAL REVIEW POST STARTUP
I*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 494 ID NUMBER WY-COC5 SOURCE TYPE CODE 5.13
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE
NATURAL GAS/GASOLINE PROCESSING PLANTS
260.00 MMCFD
COMPANY NAME/SITE LOCATION CHAMPLIN PETROLEUM CO.
P.O. BOX 310
CARTHAGE, TX
PONALA COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE
PERMIT NO. TX-206
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/11/60
ESTIMATED DATE OF START-UP
)-767-1594
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
I. C. ENGINE
I. C. ENGINE, 2
I. C. ENGINE, 2
THROUGHPUT
CAPACITY
800.00 HP
1050.00 HP EA
730.00 HP EA
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
NOX 19.2000 LB/H
24.0000 LB/MHP-H
CNTRL AIR/FUEL RATIO, IGN TIM.
NOX 25.2000 LB/H EA
24.0000 LB/MHP-H
CNTRL AIR/FUEL RATIO, ISN TIM.
NOX 16.4000 LB/H
24.0000 LB/MHP-H
CNTRL AIR/FUEL RATIO, IGN TIM.
... & BASIS
... PCT EFF
BACT
BACT
BACT
NOTES
MODIFICATION INCREASED CAPACITY FROM 220 MMCFD TO 260 MMCFD.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 495
INITIAL REVIEW POST STARTUP
REVIEW STATUS-- 04/01/1933
ID NUMBER TX-0069
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE
NATURAL GAS/GASOLINE PROCESSING PLANTS
420.00 MKCFD
COMPANY NAME/SITE LOCATION CHEVRON U.S.A.
UINTA, MY
DETERMINATION IS
PERMIT NO. CT-297
DETERMINATION MADE BY
WYOMING AQD
(AGENCY)
LEE GRIBOVICZ
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 05/28/80
ESTIMATED DATE OF START-UP 1983
(307J-332-3144
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS ' ...& BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
SULFUR PLANT & TGU, 3 EA
REHEATER, STACK GAS, 3 EA
HEATER, GLYCOL STILL, 3 EA
HEATER, PROCESS, 3 EA
FURNACE, G4S, 3 EA
1000.00 T/D
23.00 MMBTU/H
10.00 MMBTU/H
62.50 MMBTU/H
10.00 MMBTU/H
CO 220.0000 LB/H
COS 460.0000 LB/H
H2S 8.2000 LB/H
3 STAGE CLAUS - BEAVQN
NOX 0.2000 LB/MMBTU
DESIGN
NOX 0.2000 LB/MM3TU
DESIGN
NOX 0.2000 LB/MMSTU
DESIGN
NOX 0.2000 LB/f^BTU
DESIGN
BACT
BACT
BACT
99.70
BACT
BACT
BACT
BACT
PAGE G- 496
-------
(CONTINUED) CHEVRON U.S.A.
THROUGHPUT POLLUTANT EMISSION LIMITS . t BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . . . PCT EFF
BOILER, GAS, 6 EA
93.80 MMBTU/H
NOX
0.2000 LB/MMBTU
DESIGN
BACT
NOTES
PROCESSINS TRAIN HITH * 1°°° T/D SULFUR RECOVERY CAPACITY. TGU REPRESENTS A TH
INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
INITIAL
REVIEW STATUS--
PAGE G"
ID
WY-0009
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1934
= = £ = " ~~ ~ cr = ~ rrr r~ ~s rs = ~~~s:=~z~ ~~~~~rc z~=~r = ^zc = ~ = ~ = = czc=~ =z =~=~ ~s~~~s~~~~~~~r = ~~~rrr:^z =~~ ~^r^ = c = ~ = ~~~r:=^ = ~~ = s~s ^"~^ z
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS 60.00 MttCFD
COMPANY NAME/SITE LOCATION CIG , WY
SWEETWATER COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/25/76
PERMIT NO. CT-58 ESTIMATED DATE OF START-UP 1977
DETERMINATION MADE BY WYOMING AQD LEE GRIBOVICZ (307)-332-314
-------
APPENDIX DETAILED SOURCE LISTING
05/22/19S4
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS 3.09 KMCFD
COMPANY NAME/SITE LOCATION CRYSTAL EXPLORATION CO. MARATHON TUP, MI
LAPEER COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 11/30/82
PERMIT NO. 238-80E ESTIMATED DATE OF START-UP 1983
DETERMINATION MADE BY MICHIGAN DNR GREGORY EDWARDS (517)-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MOOIFICATION ... PCT EFF
.. --.. . _ _-- _--,
SWEETENING FACILITIES 3.09 MMCF/D
H2S 96.0000 /. REMOVAL FROM ACID GAS STRM
TWO STAGE CAUSTIC SCRUBBER 96.00
SOZ 1350.0000 LB/D
SOUR GAS INCINERATOR 99.50
NOTES
MICHIGAN REGULATIONS REQUIRE BACT FOR ALL NEW NATURAL GAS SWEETENING FACILITIES.
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 499
ID NUMBER MI-0029
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/19S3 04/19/1984
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS 1642.50 MMSCF/YR
COMPANY NAME/SITE LOCATION CRYSTAL OIL CO. HOSSTON, LA
CADDO PARISH
__-, __ - . _ _ __ «._-._«.______._____,_______,.__ _ _ _____
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/19/83
PERMIT NO. PSD-LA-510 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY LAQD/EPA REGION VI NAN KILLEEN (504)-342-8940
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
FLARE, 83-81 300.00 BTU/SCF
S02 144.4800 LB/H
NOTES
NO APPLICABLE NSPS FOR GAS PROCESSING PLANTS. PERMIT INCLUDES PROVISION FOR RE-EVALUATION OF BACT> DEPENDING UPOM K2S CONTENT
OF SCUR GAS STEAM.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 500
ID NUMBER LA-0046
INITIAL REVIEW POST STARTUP
5--
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
================= ====== __ 05/22/1984
=-=======-_=========== ====== = ===== === = ===____________________=__________ = ___
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS 60.00 MMCFD
COMPANY NAME/SITE LOCATION DELHI GAS PIPELINE CORP. ATHENS, TX
HENDERSON COUNTY
DATE OF PERMIT ISSUANCE 04/29/82
DETERMINATION MADE BY TEXAS ACB STUART KEIL ?I-JS-Sm * STA"T-UP" 1983
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS .. & BASIS
___ _ "^ITY _ EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
GAS PROCESSING PLANT - SULFUR 37.70 LT/D
SOS 92.9000 T/YR
400.0000 PPM
GAS PROCESSING PLANT - GAS 60.00 MMCF/D * ^"^ CUUS PLANT/SCOT TA1L GAS 99.70
H2S 1.3000 T/YR
10.0000 PPM
NOTES
CONCENTRATIONS OF S02 AND H2S ARE CALCULATED ON A DRY, OXYGEN FREE BASIS AT INCINERATOR EXIT.
-".I*!H: REVIEW
ID NUMBER TX-0096
-------
APPENDIX -- DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE
NATURAL GAS/GASOLINE PROCESSING PLANTS
11.50 MJ1CFD
COMPANY NAME/SITE LOCATION ENDERCO
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. PSD-704-A
DETERMINATION MADE BY ARKANSAS DEP
(AGENCY)
CECIL HARRELL
(AGENCY CONTACT PERSON)
GARLAND, AR
MILLER COUNTY
DATE OF PERMIT ISSUANCE 02/23/83
ESTIMATED DATE OF START-UP 1933
(50D-562-7444
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT
EMITTED
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
* BASIS
PCT EFF
AMINE SWEETENING CLAUS
11.50 MMCF/D
S02
155.0000 LB/H
CLAUS PLANT
BACT
90.00
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 502
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER AR-0011
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION ETEXAS PRODUCERS 6AS CO.
15.00 HHCFD
TX
SMITH COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. X-3832
DETERMINATION MADE BY TEXAS ACS
(AGENCY)
NOTES
JENNIFER SEINFELD
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/05/82
ESTIMATED DATE OF START-UP 1933
(5ia)-451-5711
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
HOT OIL HEATER
REGENERATION HEATER
COMPRESSOR
THROUGHPUT POLLUTANT
CAPACITY EMITTED
2.26 MMBTU/H
NOX
1.31 MMBTU/H
NOX
700.00 HP
VOC
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
2.1000 T/YR
SHEET NAT GAS FIRED
1.4000 T/YR
SWEET NAT GAS FIRED
3.0000 T/YR
4.4000 G/HP-H
67.0000 T/YR
10.0000 G/KP-H
9.0000 T/YR
1.4COO G/KP-H
... 8 BASIS
... PCT EFF
AP42
AP42
VOC
24.0000 T/YR
AP42
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 503
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 05/04/19S4
ID NUMBER TX-0123
SOURCE TYPE CCDE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
NATURAL GAS/GASOLINE PROCESSING PLANTS
24.00 MMCFD NAT GAS
COMPANY NAME/SITE LOCATION EXXON CO., U.S.A.
6 MI. N. GILMER W. HWY 271
GILMER, TX
UPSHAW COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-TX-362
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 02/09/82
ESTIMATED DATE OP START-UP--
<214)-767-154
(PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT - CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
DIETHENOLAMINE (DEA) REGEN. 4.50 MMBTU/H
S02 t 0.0004 LB/MT!BTU
NAT. GAS AS FUEL
GLYCOL RECONCENTRATOR 0.72 MMBTU/H
S02 0.0003 LB/MMSTU
NAT. GAS AS FUEL
FLARE
S02 129.3500 LB/H
SMOKELESS,NO OTHER TECH. FEAS.
NOTES
INITIAL REVIEW POST STARTUP
<*) INDICATES OATUfl WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS'- C<+/01/19S3
PAGE G- 504 ID NUMBER TX-0031 SOL'FCE TYPE CODE 5.1C
-------
APPENDIX DETAILED SOURCE LISTING
05/23/198*
SOURCE TYPE/SIZE- NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION LIQUID ENERGY CORP.
60.00 MMCFD
NEAR ARTESIA, NM
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. NM-389
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEIO SHANKAR ANANTHAKRISHNA
(AGENCY) (AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 12/10/81
ESTIMATED DATE OF START-UP 1981
(5Q5)-9S4-0020
(PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS . . . & BASIS
--_---______ CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION .. . PCT EFF
.
ENGINE, I.C. COMPRESSOR 2000.00 HP
NOX 3.4000 G/HP-H
ENGINE, I.C. COMPRESSOR 2000.00 HP L°W ^ EN5INE
NOX 3.4000 G/HP-H
ENGINE, I.C. COMPRESSOR 2000.00 HP "* *"* G
NOX 3.4000 G/HP-H
LOW NOX ENGINE
NOTES
2°' WERE PERFORMED ON ALL THREE ENSINES & THE ACTUAL EMISSIONS WERE 2.01 G/HP-H, 2.6 G/HP-H, & 3.
^ ______REVIEW
PAGE G- 5C5 1D NUMQFR KM-0003
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION MAPCO PRODUCTION CO.
NEAR ROSWELL, NM
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. PSD-NM-576
DETERMINATION MADE BY AIR QUALITY BUREAU - NMEIO SHANKAR ANANTHAKRISHNA
(AGENCY) (AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/14/83
ESTIMATED DATE OF START-UP 1983
(5051-934-0020
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... t BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ACID CAS FLARE
ENGINE, I.C. COMPRESSOR
ENGINE, I.C. COMPRESSOR
ENGINE, I.C. COMPRESSOR
ENGINE, I.C. COMPRESSOR
7.50 MMSCFD
446.00 HP
670.00 HP
507.00 HP
278.00 HP
S02 703.0000 LB/H
DIETHANOL AMINE UNIT
NOX 9.0000 G/HP-H
AIR/FUEL RATIO
NOX 9.0000 G/HP-H
AIR/FUEL RATIO
NOX 9.0000 G/HP-H
AIR/FUEL RATIO
NOX
9.0000 G/HP-H
AIR/FUEL RATIO
NOTES
STACK TESTS, EPA REF. METHOD 7, WERE PERFORMED ON ALL FOUR ENGINES S EMISSIONS WERE 7.1 G/HP-H.
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
PAGE G- 5C6
ID NUMBER NM-0007
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTINS
r = = = = = r = = = = = = = = = = ---____.__._______._________ ^ ^ 05/32/1934
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS 7.10 MMCFD
COMPANY NAME/SITE LOCATION MARATHON OIL CO.
> WI
_ PARK COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE
PERMIT NO CT-479 =>"UKLt. DATE Qf PERHIT ISSUANCE__ 01/20/83
DETERMINATION MADE BY WYOMING AQD CHUCK COLLINS ' f- [ 5J^'UP" 19M
<*SENCY) (AGENCY CONTACT PERSON) (PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS , BASIS
-.. CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION \ '.'. PCT EF?
STILL, GLYCOL 0.76 MMBTU/H
HF4TFO HOT nn NOX 0.2000 LB/KMBTU STP
HEATER, HOT OIL 14.20 MM3TU/H SIP
.,._.... CIIIBIIB n, A.rr NOX 0.2000 LB/MMBTU SIp
INCINERATOR, SULFUR PLANT 2.50 MMBTU/H
S02 79.8000 LB/H BACT
31.9000 LB/KMBTU
5 LTD CLAUS 90.00
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 507
INITIAL REVIEW POST STARTUP
REVIEW STATUS;
ID NUMBER WY-0002
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE- NATURAL GAS/GASOLINE PROCESSING PLANTS 12.50 MMCFD
w . -. M-. _» w_____». ««,_.__.._w__. _ H ___ __ __ _..___-._.. _«._«._
COMPANY NAME/SITE LOCATION MOUNTAIN FUEL SUPPLY UINTA, WY
^ j^-. «-. «. ^ _ i^ ». _»_«_ ,^»»^«,^^«.__ ^«._»._.«_ _^ _.__
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/01/78
PERMIT NO. CT-117 ESTIMATED DATE OF START-UP 1
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION PACIFIC ALASKA LNG ASSOCIATES
KENAI, AK
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. 8423-AA002
DETERMINATION MADE BY ALASKA DEC
(AGENCY)
DAVE ESTES
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/30/84
ESTIMATED DATE OF START-UP-- 1987
(907)-465-2666
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
HEATER, PROCESS, GAS FIRED, 5
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED
NOX
... & BASIS
CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
38.0000 NG/J
0.0900 LB/MKBTU
LOW NOX BURNERS
BACT
NOTES
THIS B4CT DETERMINATION RESULTED FROM AN IS MONTH REQUEST FOR EXTENSION AT A FACILITY PREVIOUSLY PERMITTED
BY EPA REGION 10.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 509
TWTTTAL REVIEW POST STARTUP
5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION PHILADELPHIA GAS WORKS PHILADELPHIA, PA
PHILADELPHIA COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/15/79
PERMIT NO. 78PA03 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION III VERNON BUTLER (3151-557-2711
(AGENCY 1 (AGENCY CONTACT PERSON 1 (PHCN'E 1
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS .. . t, BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER 110.00 MBTU/H
PM 5.4000 LB/H BACT
S02 75.0000 LB/H BACT
STRETFORD
LOW S FUEL
NOX 74.0000 LB/H BACT
STORAGE TANKS 1.00 MMBBL/YR
VOC 91.0000 T/YR BACT
DEL SEALS, FLOAT. ROOF TANKS
NOTES
INITIAL REVIEW POST STARTUP
<*! INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/C1/1933
PAGE G- 510 ID NUMBER PA-0002 SOURCE TYPE CODE 5.12
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION PHILLIPS PETROLEUM CO.
30.00 WSCFD
DETERMINATION MADE BY
T00THTf PFPH?TECT
°"
NO
SOURCE-
NORTH DAKOTA SHD
(AGENCY)
GARY HELBINS
(AGENCY CONTACT PERSON)
OF PERMIT
S!-
(PHONE)
WILLIAMS COUNTY
10/25/82
THROUGHPUT
CAPACITY
POLLUTANT- EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
FCT EFF
INCINERATOR STACK
NOTES
30.00 MMCF/D
S02 93.3000 LB/H
CLAUS PLANT
BACT
98.50
ID f!Uf
ND-OOC2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE--- NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION PHILLIPS PETROLEUM CO. MALJAMAR, KM
HWY 126 15 HI. S. OF MALJAMAR LEA COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 10/08/81
PERMIT HO. (REGION FILE NO.) PSD-HM-389 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BENHAM (214(-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ENGINE, I.C. COMPRESSOR, 2 EA 585.00 HP EA
NOX 11.0000 G/HP-H
AIR/FUEL RATIO
NOTES
2 INTERNAL COMBUSTION COMPRESSOR ENGINES.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 512
10 NUMBER NM-0003
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
SOURCE TYPE CODE 5.12
-------
APPENDIX -- DETAILED SOURCE LISTING
--__--.......___ 05/22/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION PHILLIPS PETROLEUM CO. BARTLESVILLE, TX 74009
PHILLIPS BUILDING
~ - -__-, _,-_ _______ ___..__,*.__.._ . _ __._«.__« _.,.______,. -. -.-.__.._,.... _-._ __
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PFDMTT ISSUANCE 01/30/SO
PERMIT NO. (REGION FILE NO.) FSD-TX-314 ESTIMATED OAT? " START-UP--
DETERMINATION MADE BY EPA REGION VI JOE WINKLER (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. COMPRESSOR ENGINES 650.00 HP EA
NOX 12.4000 G/HP-H BACT
TURBINE COMPRESSOR ENGINES 3000.00 HP EA
NOX 1.8000 G/HP-H BACT
NORMAL OPERATION
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 513 I0 NUMBER TX-0045 SOURCE '''''
-------
APPENDIX DETAILED SOURCE LISTING
SOURCE TYPE/SIZE- NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION PROCESS EQUIPMENT CORP. MAYFIELO, MI ^^ TRAVERSE COUNTY
PEP-MIT NO. 813-81 /ci-»i i->o 1111
DETERMINATION MADE BY MICHIGAN DNR DAVID FERRIER (517)-3.2-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
__-__---_^w,--------.-~---- -- ------------------,_------- ..____....___-.._-_- -------- «..--_--- -- - --- - --- - - --------- ------
SOUR GAS SWEETENER 10.00 MMSCFD
S02 81.1000 LB/MMSCF
CLAUS UNIT 85.00
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. ___ ?!-s!I*!i= = = «" = "~ = = =="="«« = =
plGrG-lir"========== = = = r= = = = === = = Z= = " = = " = = = = "="="lo"NUMBER"MI-OOC7 SOIPCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
= = = = = = m = = = = r=- = 05/22/198*
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS 39.00 MM8TU/H
"~'~'""""~~**~"*~"~'1I"~~~'"""*~""""~"~*~ ~"*~~*'~"'"'^ -" * » ^^ ^ -^ » _^_ _ _ _
COMPANY NAME/SITE LOCATION REPUBLIC REFINING CO. JOHNS, MS
RANKIN COUNTY
" " _W __ ,. .»_..___ _*,__«,_ _ __ , .___ _«.
PERMIT NO. (REGION F!LE NO.) PSD-MS-037 ESSIES ofsTA^'uP °8/C3/81
DETERMINATION MADE BY MISSISSIPPI DNR DWIGHT WILEY "JlTJS-2550 START-UP"
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OP PROCESS MODIFICATION ... PCT EFF
NAT. GAS PROCESSING-SULFUR RECO* 50.00 MMCF/D
S02 0.0030 LB/H EA BACT
TREATED NAT. GAS FOR BOILERS
NOTES
TWO BOILERS
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS^il/Ol/lSr ^^ STARTUP
= = = = = " = = = = = = = r = = = = = - = = = = = = - ----_-_-___. = = = = = = = = = r = r = = r = = === = = -::=r = = r = = r = rr = r = = = = z = = r = = = rr = = :r::r = = = = = = = = = = === = = = = =
PAGE G- 515 ID NUISER MS-OOO* SOL'PCE TYPE CCOE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
SOURCE TYPE/SIZE- NATURAL GAS/GASOLINE PROCESSING PLANTS
COMPANY NAME/SITE LOCATION SHELL OIL CO. FREDERIC TOWNSHIP, MI rD,UCnr>n rraiviTY
SECTION 10 . CRAWFORD COUN1T
DETERMINATION MADE BY MICHIGAN DNR LAURA STEINBERGER (517)-322-1333
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
___,«...._.,. - ~ *- "*
_»_ ».» »»»». » « - - -" -" " ""' "* ""**~*~'~""'~*~~'~"'~' """""<~""~~"~""~""~'~°~'~"
GAS SWEETENING FACILITY 7.00 MMCF/D
S02
3-STAGE CLAUS UNIT 93.50
S02 184.0000 LB/H
540.0000 LB/H
GROUND LEVEL INCINERATOR 99.90
NOTES
2NO ALTERNATE LIMIT - 2100 LB/0
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. ?^!".!I*I"!i__?^.!^-!!! . _--.-
= = "" = = = = "=S"" = = " = = :: = = "S io"NUMBER"MI-0031 SOL'PCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS U7.00 HMSCFD
COMPANY NAME/SITE LOCATION SIO RICHARDSON CARBON fc GASOLINE CO. KERMIT, TX
WINKLER COUNTY
DETERMINATION IS BACT FOR A MODIFIED sntlPrp
PERMIT NO 272" nooiFIED SOURCE. OATE OF PERMIT iSSUANCE 01/14/31
DETERMINATION MADF BY TFVAC Arn ESTIMATED DATE OF START-UP 1981
utit.,ruNAIJOH MADE BY TEXAS ACS LES MONTGOMERY (51Z )-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS s e4SIS
_____ CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . . . PCT EFF
~'~^~'~""~""'*"" *"~*"~"~**"* *"""""* '~"*""""""""""~~"""""~~""~*-~ "-- *-- « ~-> ..^ _ __
NATURAL GAS TREATING PLANT 117.00 MMSCFD
S02 816.0000 T/YR
SELECTOX S RECOV. UNIT 95.00
NOTES
v «* NTSULFIDE EXTRACTED FROM RAW NATURAL GAS TO ELEMENTAL SULFUR. THIS UNIT IS A THREE
« TC A M*. /- CONVERSION TO H2S. THE REMAINDER IS INCINERATED TO S02.
THIS IS A SMALL UNIT IN AN ISOLATED LOCATION.
1!---^^.IP.DATUM WAS TRUNCATE0 FOR THIS TABLE. REVIEW STATUS: 04/01/1933" ^^
PAGE G" 51? 1° "UMBER TX-0094 SOUSCE~TYPrcODT=Tl2
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- NATURAL GAS/GASOLINE PROCESSING PLANTS 10.00 MMCFD
COMPANY NAME/SITE LOCATION WARREN PETROLEUM CO. VADA, MM 88267
20 MI. NH OF TATUM LEA COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 12/23/81
PERMIT NO. (REGION FILE NO.) PSO-NM-156M-1 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI TOM DIGGS (214 )-767-159<+
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...& BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
ACID GAS FLARE 10.00 MMSCFD
S02 703.0000 LB/H
0.0016 LB/SCF
DIETHANOL AMINE UNIT
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 518
INITIAL REVIEW POST STARTUP
-.-iCri STAIUS: 0-4, Cl/1933
ID NUMBER NM-0005
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE NATURAL GAS/GASOLINE PROCESSING PLANTS
«- - , _ » _ _ __ _ ___ .. _,.__,.
COMPANY NAME/SITE LOCATION WARREN PETROLEUM CO.
24.00 MMCFD
BILLINGS COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE
PERMIT NO.
DETERMINATION MADE BY NORTH DAKOTA SHD
(AGENCY)
TERRY O'CLAIR
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 01/12/83
ESTIMATED DATE OF START-UP--
(70D-224-2348
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
INCINERATOR STACK
NOTES
«
30 nnCF/D .
S02
534.0000 LB/H
CLAUS & CBA
BACT
93.60
F/N EXISTING SOURCE' E EXISTING SOURCE CURRENTLY PROCESSES 20 - 24 KMCF/0 OF GAS WITH AN EMIS
AFTER EXPANSION THE ^W S02 EMISSION RATE WILL BE 534 LB/H « CAN HAWLE
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 519
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1983
ID NUMBER ND-0001
SOURCE TYPE CODE 5.12
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1984
SOURCE TYPE/SIZE---
ASPHALT * ASSOCIATED PRODUCTS MFG./PROCESSING
COMPANY NAME/SITE LOCATION KERNRIDGE OIL CO.
BELRIQGE OIL FIELD
CA
KERN COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) SJ-79-26
DETERMINATION tUOE BY EPA REGION IX
(AGENCY)
DON HARVEY
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 04/14/81
ESTIMATED DATE OF START-UP--
<415)-974-e223
(FHCME)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... & BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
STEAM GEN., 11 EA
50.00 MKBTU/H
OIL WELL VENTS - EXISTING
OIL U'ELL VENTS - NEW
S02 0.0650 LB/MM3TU
1.2000 '/. S FUEL OIL
S02 SC^L'SSER W/ EQUCTOR/VENTURI
NOX 0.2000 LB/M?!3TU
LC'rl NOX BURNERS EXCESS 02 CONTROLLERS
PM 0.0570 LB/M!-:3TU
S02 SCRUBBER W/ EDUCTCR/VENTURI
PM o.oioo LB/n-t-jTU
SCRUE3ER U/ ESP SECTION
VOC NCNE
VAPOR RECOVERY
VOC NOME
SHUT IN WELLS
95.00
BACT
50.00
LAER
50.00
LAER
90.00
85.00
100.00
NOTES
PM EMISSIONS FROM ONE OF THE UNITS WILL BE CONTROLLED WITH AN ESP WHICH IS AN INNOVATIVE TECHNOLOGY AS APPLIED TO THERMALLY EN
HANGED OIL RECOVERY (TEOR ) .
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE 6- 520
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/ClA933 04/04/1954
ID NU",3ER CA-OC09
SOURCE T\PE CCDE 5.13
-------
APPENDIX DETAILED SOURCE LISTING
SOURCE TYPE/SIZE ASPHALT & ASSOCIATED PRODUCTS MFG./PROCESSING
COMPANY NAME/SITE LOCATION R.A. CHIIDS
130.00 T/YR
, UT
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. MIN 083182-5T
DETERMINATION MADE BY UTAH BAQ
(AGENCY)
DON ROBINSON
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 10/08/82
ESTIMATED DATE OF START-UP 1983
(80D-533-6108
(FKCME)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS ... $ BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
DRUM DRYER
130.00 T/H
PM 0.0200 GR/DSCF
1.4900 LB/H
VENTURI SCRUBBER
VE 20.0000 /. OPACITY
99.00
NOTES
MOBILE ASPHALT PLANT
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 5ZI
INITIAL REVIEW POST STARTUP
REVIEW STATUS: C4/01/1033 02/13/1934
ID NUMBER UT-C030
SCU^CE TYPE CODE 5.13
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
r = r = r:r = : = : = = r = rr = = = = = = = :r = = = r = = :r = - = = = = = = = = = : = ::r; = = = = = = r = = = = = = = = r = = = = = = = rr = = = z= = = = = = r = = = = = = = r = r = = : = = rrrz = = r= = = = = r = r = r = rrr = = = = = = =
SOURCE TYPE/SIZE- ASPHALT 4 ASSOCIATED PRODUCTS MFG./PROCESSING 30000.00 GAL
COMPANY NAME/SITE LOCATION US OIL & REFINING CO. TACOMA, HA 98401
3001 MARSHALL AVE.
- -.-. _ _ _». -,___-__-.__.. _ __ __ .»_
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 08/15/83
PERMIT NO. N/C 2455 ESTIMATED DATE OF START-UP 1984
DETEPMINATION MADE BY FL'GET SOUKT) APCA HARRY WATTERS (205 1-344-7334
(AGENCY) (AGENCY CONTACT PERSON) (PHCNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT CR PROCESS MODIFICATION ... PCT EFF
--_-___- -___--.-_-_-_.--- _- , . _ _. ___ «._-_---_--_^ -_---_-_. -. _____-_- --«_ _.---»_---_-___-
ASPHALT BLOW STILLS, 2 15000.00 GAL EA
P« 0.0200 LB/T ASPHALT CHARGED
INCINERATOR 95.00
S02 0.1000 CR/DSCF H2S IN FUEL GAS
CONTIKO'JS r.CHITCRItiG
NOTES
APPROVED NOTICE OF CONSTRUCTION AND TRANSMITTAL LETTER DATED 08/15/83. ASPHALT TRUCK LOADING RACK WITH HEAP CONTROL, AND 5 ASP
HALT STORAGE TANKS WITH HIGH ENERGY AIR FILTER, HEAF, CONTROL.
SOLACE CLAIMS CCNFIDENTIALITY FCR DETAILS OF PROCESS.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 522
INITIAL REVIEW POST STARTUP
REVIEW STATUS-. 04/13/1934
ID NUMBER WA-0009
SC'Jf7CE TYPE CODE 5.13
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE -
CRUDE OIL/NAT. SAS PRODUCTION (INCL. OIL SHALE)
COMPANY NAME/SITE LOCATION AMINOIL USA, INC.
HUNTINGTON BEACH, CA 92648
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. NS9-4-4-9 LA-82-01
DETERMINATION MADE BY EPA REGION IX
(AGENCY)
DAVID SOLOMON
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 08/04/82
ESTIMATED DATE OF START-UP
(415J-974-8240
(PHONE)
FPOCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS ... 4 BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE 4 WASTE HEAT BOILER
6464.00 KW
SOX 14.0000 LB/H
FGD SYSTEM
BE 0.0000 LB/H
UET SCRUBBER & FGD SYSTEM
BACT
95.00
99.00
NOTES
36.0 BBLS/H OF 1.34X SULFUR CRUDE OIL
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 523
INITIAL REVIEH POST STARTUP
REVIEW STATUS; 04/01/1933 04/04/1934
ID NUMBER CA-0035
SOURCE TYPE CODE 5.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- CRUDE OIL/NAT. GAS PRODUCTION (INCL. OIL SHALE)
COMPANY NAME/SITE LOCATION BEREY HOLDING CO. . CA
MIDWAY-SUNSET OIL FIELD KEP.N COUNTY
_ ___ __ -__ __ _.__ -__. -.__ _-.__ «__ __ _ _ _ _ _ _ ~ _.._._ __ . -. - . .
DETERMINATION IS FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 02/23/61
PERMIT NO. (REGION FILE NO.) SJ-79-17 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY EPA REGION IX DON HARVEY (415)-974-82C3
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . !, BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
COMPRESSOR, ROTARY SCREW,2 EA 500.00 HP
VOC 690.0000 PPM (AS CARBON)
INCINERATION IN STEAM GENERATOR AT 2600 f 95.00
COMPRESSORS, RECIP. BOOSTER, 2 *
VOC 10.5000 LB/H 3X 02
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933 0^/04/196'*
PAGE G- 524 ID NUMBER CA-OOOS SCU^CE TYPE CODE 5.14
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE CRUDE OIL/NAT. GAS PRODUCTION (INCL. OIL SHALE) 450.00 KMBTU/H
~"**~~~'*~"-"~'"1 . _ __ _ ___ _«,_ _«. ..._.__._. __ _. _ _.___._.._ ___«. _____ _______ ___ _ ^ _
COHPANr NAME/SITE LOCATION CHEVRON USA, INC. BAKERSFIELD, CA
P.O. BOX 5355
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE- 07/16/82
PERMiT NO. NSR-4-4-8 SJ-79-33 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION IX BOB BAKER (415)-974-S215
(AGENCY) (AGENCY CONTACT PERSON) (PHCNE)
r = = = = = = r-r = = = - = = = r = = = r = = = = = = = r = r: = = r = = = = = r = = = = = = = = = = = = = = = = = = = = = = = = - = = = = = = = = = - = --- = - = ----_-_ = _ = _-___.___ = _...._.._______._____.__._
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ *_ . ___ .___^_.w._p ^_ « _ _ _,__ __ _-.____to«. _,___.w_ _^.__ _ __«, *. «. _ ._«,_._»_« »__..___
BOILERS, 9 390.00 GAL/H, EA
SOS 18.8000 LB/H BACT
KET SCRUBBERS 90.00
1.5X S LIMIT ON FUEL OIL
PM 3.6000 LB/H LAER
WET SCRUBBERS 50.00
NOTES
INITIAL REVIEW POST STARTUP
m^iraiCATES DATUM MAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933 04/04/1984
PAGE G- 525 10 NUMBER CA-0037 SOURCE TYPE CCOE 5.14
-------
APPENDIX DETAILED SOURCE LISTING 05/22/1984
SOURCE TYPE/SIZE CRUDE OIL/NAT. GAS PRODUCTION (IK'CL. OIL SHALE) ^ ^ 24.00 MHCF
COMPANY NAME/SITE LOCATION EXXON CO NEW ORLEANS, MS rniiNTY
P. 0. BOX 60626 HIHDS
fM A
sr .^ocr «BSo«,
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
Si"? PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PPQCESS MODIFICATION ... PCT EFF
TEST WELL 25.00 MMCF/D
S02 745.0000 T/D 30 D MAX
FLARE 99.00
NOTES
TEST FACILITY EXPECTED LIFE 120 DAYS.
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE 6- 526
INITIAL REVIEW POST STARTUP
REVIEU STATUS: 04/01/1933
ID NUMBER MS-0001
SC'J7CE TYPE CCOE 5.14
-------
APPENDIX DETAILED SOURCE LISTING
SOURCE TYPE/SIZE CRUDE OIL/NAT. GAS PRODUCTION (INCL. OIL SHALE) 426.00 BBL/D
COMPANY NAME/SITE LOCATION GEOKINETICS INC., OIL SHALE 40 MILES S. VERNAL, UT
UINTAH COUNTY
-- --- -- -- -- .-._..-...-..._..____.._.._ __ __._ ___ _-__ __ -. _ _ ....__.«._«,_...________._ __ _.__
DATE OF PERf1IT ISSUANCE-- 11/13/80
NO. ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VIII JOHN DALE ( 303 )-837-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
= = = = = = r = = = = = = = = = = = z = = = = = = == = = = = : = : = = - = = -__---_.._. r = = = = = = = = = = = = = = - = = = = = r = - = = = = = = = = = = = = = = = = = = === = = = = = = = = __-.:__--__.. _____-_______
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... J BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . . ". PCT EFF
------------ - -- -. * _-,___»__.. --- _ __ ___ - »_^__, __ _«
*" '""* *-^ -- » » -. -. . ^ ^^_^»,__,_ «..__
GENERATOR 650.00 HP
NOX 38.9000 LB/H BACT
DESIGN
VE 20.0UOO '/. OPACITY
INCINERATOR 100.00 BBL/D
NOX 45.1000 LB/H BACT
NONE 0.00
S02 135.3000 LB/H BACT
NONE 0.00
VE 20.0000 Y. OPACITY
NOTES ........
3.5 YR OPERATION, LIMITED EXPERIMENTAL VARIANCE.
rv.Tt-T'i nr.-Tr;j PQ3J STARTUP
(*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. KL,i = ^ S FAILS: 0-4/01/1983
PAGE G- 527 ID KUMEcR L'T C-,;, . __ , . 7 , re CC2E 5.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/l«S4
SOURCE TYPE/SIZE
CRUDE OIL/NAT. GAS PRODUCTION (INCL. OIL SHALE)
225.00 MMSCFD
COMPANY NAME/SITE LOCATION MOBIL OIL EXPLORATION
AL
MOBILE COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. AL-07S
DETERMINATION HOE BY ALAB4.MA APCD
(AGENCY)
SUE ROBERTSON
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 10/16/81
ESTIMATED DATE OF START-UP--
(205) -334-6570
(PHONE)
= = : = = : = r: = r: = = :r = = r = = = = r = = r = rr = rzrrr = = = r: = = -:rr = = == = = = r = = = z: = = = = :r = r = = = r = = r = = = = =rr: = = = = = = r = = = r: = = :r = = r = r = = rr: = r: = r = = = = = :
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
NAT. GAS SULFUR REMOVAL 225.00 MMSCFD
S02
DIESEL ENGINES, 4 RIGS 1100.00 HP/ENGINE
CO
S02
NOX
PM
SUPPLEMENTAL BOILER 50.00 MM3TU/H
NOX
S02
SULFUR DEPOT BOILER 5.00 MKBTU/H
NOX
S02
200
9
7
71
3
0
1
0
z
.0000
.4000
.3000
.6000
.4000
.2000
.0000
.2000
.2000
LB/H EA
CLAUS AN'D SCOT TAIL GAS REMOVAL
LB/H-RIG
NONE
LB/H-RIG
LOU S FUEL
LB/H-RIG
NOME
LB/H-RIG
KCN'E
LB/rMSTU
STAGED COMBUSTION £ LOW EXCESS AIR
LB/H
LCW S FUEL
LB/KMSTU
STAGED COMBUSTION * LOW EXCESS AIR
LB/H
... t BASIS
.. . FCT EFF
BACT
Q9.86
54.00
37.00
LOU S FUEL
PAGE G- 528
-------
(CONTINUED) MOBIL OIL EXPLORATION
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
" .».._....__ »,
TURBINE GENERATOR, SAS-FIRED 7.50 KW
NOX 175.0000 PPM BY VOL
NONE
SOZ 1.0000 LB/H
LOW S FUEL
PLATFORM GENERATORS, 5 EA., GAS* 661.00 HP/ENGINE
NOX 146.0000 LB/H-PLATFORM
NONE
CO 146.0000 LB/H-PLATFORM
NONE
SOZ 1.0000 LB/H-PLATFORM
LCa S FUEL
NOTES
DRILLING PERMIT
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01A9S3
PAGE G- 529 jD NUMBER AL-0010
SCl'SCE TYPE CODE 5.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE CRUDE OIL/NAT. GAS PRODUCTION (INCL. OIL SHALE) 1.00 MBBL/D
COMPANY NAME/SITE LOCATION OXY-LOGAN WASH MODIF.1930 NEAR DE BEQUE, CO
GARFIELD COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 06/27/80
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VIII JOHN DALE <3031-S37-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
BOILER, ETC
RETORT
1000.00 BBL/D
CO 2.0000 LB/H
VOC 3.0000 LB/H
CCN'DENSCR
NOX 52.0000 LB/H
COiflJENSCR
PM 7.0000 LB/H
DUST CONTROL
S02 31.0000 LB/H
CO 3640.0000 LB/H
VOC 154.0000 LB/H
CC',DENSCR
H2S 376.0000 LB/H
BACT
BACT
BACT
60.00
BACT
50.00
BACT
BACT
60.00
BACT
NOTES
OPERATION OVER IN 1952
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 530
ID NUMBER CO-0009
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
SC'JSCE TYPE CCDE 5.14
-------
APPENDIX DETAILED SOURCE LISTING
= 05/22/1984
===s="===============-=====s=s===s-=---==s-s=s--===-==.=--ss=s=_==s=ss=s===__s____________________
SOURCE TYPE/SIZE CRUDE OIL/NAT. GAS PRODUCTION (INCL. OIL SHALE)
""' " -- _ ____ _,-__.. _ _ _ _-._,. __,-. _ __ _ _ __.. _____.»_»,__ «._. _
COMPANY NAME/SITE LOCATION PARAHO DEVELOPMENT CORP. f m
UINTAH COUNTY
OF PERM" ISSUANCE- 11/16/82
nFTFPMTMATTrw M«ne cv ,,T.U D1o ESTIMATED DATE OF START-UP-- 1990
DETERMINATION MADE BY UTAH BAO DONALD ROBINSON (801 )-533-6103
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
BOLTING, SCALING, HANDLING, DRI* 75000.00 T/D SHALE
BLASTING
CRUSHING
IN MINE TRANSFER
MINE MOBILE EQUIPMENT
54000.00 LB ANFO/D
75000.00 T/D
75000.00 T/D
11730.00 6AL/D DIESE*
FUG*
CO
NOX
FUG*
PM
PM
PM
NOX
S02
voc
WATER SPRAYING
SETTLING
0.0150 GR/DSCF
BAGHOUSE
0.0150 G3/DSCF
BAGKCUSE
11.0000 LB/MGAL
SETTLING
3S5.2000 L8/MGAL
CATALYTIC CONVERTER
31.2000 LB/M3AL
2.6000 LB/I-'GAL
CATALYTIC COMV.
50.00
50.00
99.90
99.00
50.00
10.00
90.00
PAGE G- 531
-------
CO 4.5000 LB/MGAL
CATALYTIC CONV. 95.00
PAGE G- SZZ
-------
(CONTINUED) PARAHO DEVELOPMENT C03P.
PROCESSES SUBJECT
TO THIS PERMIT
MATERIAL HANDLING
STORAGE PILES
HYDROGEN PLANT REFORMER FURNACE
HYDROTREATER FEED FURNACE
POWER GENERATION FACILITY
THROUGHPUT POLLUTANT
CAPACITY EMITTED
75000.00 T/D
PM
PM
PM
VARIOUS SIZ*
PM
800.00 MMBTU/H
PM
CO
voc
NOX
S02
PM
CO
VOC
NOX
S02
41.25 MMBTU/H
PM
CO
VOC
NOX
SO 2
2110.00 MMBTU/H
FM
CO
VOC
NOX
EMISSION LIMITS
CONTROL EQUIPMENT Of! PROCESS MODIFICATION
0.0100 GR/DSCF
BAGHOUSE
0.0150 GR/DSCF
BAGHOUSE
0.0200 GR/DSCF
WET SCRUBBERS
WATER SPRAYS
15.0000 LB/MMCF
17.0000 LB/MMCF
3.0000 LB/MMCF
161.0000 LB/MMCF
LOU! NOX BURNERS
0.6000 LB/MMCF
0.0150 LB/MM3TU
0.0170 LB/MMBTU
0.0030 LB/MM3TU
0.1610 LB/retSTU
LOW NOX BURNERS
9.8300 LB/H
HOLMES STRETFORD UNIT
15.0000 LB/MMCF
17.0000 LB/MMCF
3.0000 LB/MMCF
161.0000 LB/MMCF
LC'ri NOX BURNERS
o.6ooo LB/M;:CF
0.0150 LB/MMBTU
0.0170 LB/MMBTU
0.0030 LB/i'MBTU
0.2500 LB/MMBTU
... « BASIS
... PCT EFF
99.00
99.00
99.00
50.00
30.00
30.00
99.60
30.00
NSPS
NOX
HATER UASH OF RETORT OFF GAS TO REMOVE NH3
0.2000 LB/MMBTU
97.00
NSFS
PAGE G- 533
-------
WATER WASH OF RETORT OFF GAS TO REMOVE NH3 97.00
S02 0.1400 LB/mSTU
REMOVE H£S BEFORE COMBUST. 99.60
PAGE G- 534
-------
(CONTINUED) PARAHO DEVELOPMENT CORP.
SUBJECT
FERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS .. & BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
PACKAGE BOILER
STORAGE TANKS,
W.50 MM8TU/H
53000.00 BBL
PM
S02
CO
VOC
CRUDE SHALE OIL STORAGE TANKS, 7 150000.00 BBL
VOC
VOC
Z. 0000 LB/MSAL
0.5000 X S CONTENT
5.0000 LB/MGAL
1.0000 LB/MGAL
R°°P »
EXT. FLOAT. ROOF W/F3IMARY 4 SEC. SEAL
95.00
NOTES ---- ..... --
n21f_P«iIuIIATI°N IS F°R URGER BAGHOUSES ON CRUSHERS. PUR. GEN. - 3 STACKS GAS TURBINE ft WASTE HEAT BOILER EA. BOILERS PROVI
DE 36.73X HEAT INPUT. 9 OTHER TANKS WILL CONTAIN EITHER 82 FUEL OIL, PROPANE (CRYC3ENIC) , DIESEL FUEL OR
GASOLINE. NONE OF THEM SUBJECT TO NSPS. S02 EMISSIONS FROM POWER GENERATION FACILITIES INCLUDE RETORT OFF GAS AND WASTE WATER
TREATE ACID GAS.
DATUM WAS TRUNCATED FOR THIS TABLE.
REVIEW
PAGE G- 535
ID NUMBER UT-0024
SOURCE TYPE CODE
-------
SOURCE TYPE/SIZE-
APPENDIX DETAILED SOURCE LISTING
CRUDE OIL/NAT. GAS PRODUCTION (INCL. OIL SHALE)
05/22/1984
2.00 flEBL/D
COMPANY NAME/SITE LOCATION RIO BLANCO OIL SHALE-SI
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO.
DETERMINATION MftDE BY EPA REGION VIII
(AGENCY)
PROCESSES SUBJECT THROUGHPUT
TO THIS PERMIT CAPACITY
2 BOILERS 198.00 MV.BTU/H
HEATER 5.00 MMBTU/H
LUP.GI RETORT EOOO.OO BBL/D OIL S»
ORE CONV-STKPILE 4400.00 T/D SHALE
C°E TRANSFER 4400.00 T/D SHALE
ORE LOADOUT 4400.00 T/D SHALE
NEAR RANGE LY, CO
JOHN
( AGENCY
DALE
CONTACT PERSON)
POLLUTANT EMISSION LIMITS
EMITTED
NOX
NOX
NOX
S02
PM
PM
PM
PM
CONTROL EQUIPMENT
39.6000 LB/H
1.0000 LB/H
127.0000 LB/H
18.0000 LB/H
RETENTION
39.6000 LB/H
ESP
0.4000 LB/H
BAGHOUSE
0.4000 LB/H
BAGHOUSE
0.0800 LB/H
BAGHOUSE
RIO BLANCO COUNTY
DATE OF PERMIT ISSUANCE 12/20/81
ESTIMATED DATE OF START-UP
(3031-837-3763
(PHCME)
... * BASIS
OR PROCESS MODIFICATION ... PCT EFF
BACT
BACT
BACT
BACT
BACT
99.80
BACT
99.00
BACT
99.00
BACT
99.00
PAGE G- 536
-------
(CONTINUED) RIO BUNCO OIL SHALE-ftl
PROCESSES SUBJECT
TO THIS PERMIT
PRIM.
PROC
PROC
SEC.
PROD.
CRUSH/SCR
SHALE TRANS., FEED
SHALE TPANS. DISP
CRUSH/SCR
GAS INC/SCRUB
THROUGHPUT
CAPACITY
4400.00
4400.00
4400.00
4400.00
70.00
T/D SHALE
T/D SHALE
T/D SHALE
T/D SHALE
MMBTU/H
POLLUTANT
EMITTED
Ptl
PM
PM
PM
S02
NOX
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
0
0
0
0
9
24
.2400
.4000
.4000
.3200
.7000
.0000
LB/H
BAGHOUSE
LB/H
BAGHOUSE
LB/H
BAGHOUSE
LB/H
BASHOUSE
LB/H
SCRUE-BER
LB/H
... & BASIS
... PCT EFF
BACT
99.00
BACT
99.00
BftCT
99.00
BACT
99.00
BACT
SO. 00
NOTES
THREE YEAR OPERATION PLANNED.
(*) INDICATES DATUM WAS TRUNCATED F03 THIS TABLE.
PAGE G- 537
ID NUMBER CO-0013
INITIAL REVIEW POST STARTUP
REVIEU STATUS; 04/01/1933
SOURCE TYPE CCDE 5.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198'+
SOURCE TYPE/SIZE--- CRUDE OIL/HAT. GAS PRODUCTION (INCL. OIL SHALE) 50.00 MMBTU/H
_ _ _ _ _______ _._ ___ ___ __-.__.. .._,.__ _.., _____ _ __
COMPANY NAME/SITE LOCATION TEXAS TAR SANDS, LTD LAPRYCR, TX
MAVERICK COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE-- 06/24/82
PE-MIT NO. 9075 ESTIMATED DATE OF START-UP 1932
DETERMINATION MM3E BY TEXAS ACB JAMES CROCKER (512J-451-5711
(AGENCY) (AGENCY CONTACT PERSON) (PHDNE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASTS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_
STEAM GENERATOR 50.00 MMBTU/H
PM 0.0940 LB/MMSTU
FABRIC FILTER 99.30
S02 1.2000 LB/Mr;3TU
LIMESTONE INJECTION 78 00
COAL * LIMESTONE STORAGE/HANDLI*
PM 1.3000 LB/H
DUST CONTROL SYSTEM
NOTES
THIS IS A COAL FIRED SYSTEM. EMISSIONLIMITS ARE BACT, DETERMINED BY TECHNOLOGY 4 ECONOMICS.
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/J.933
PAGE G- 538 ID NUMBER TX-OOS5 SOLACE TYPE CCDE 5.14
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1934
SOURCE TYPE/SIZE CRUDE OIL/NAT. GAS PRODUCTION (INCL. OIL SHALE) 45.00 M5BL/0
COMPANY NAME/SITE LOCATION TOSCO OIL SHALE-1981 NEAR BONANZA, UT
UINTAH COUNTY
» - »._____ __ __ _ __»_ _. «. __,_. _ _ _ «, «. _» ^»_ __.____._ _«._*..-»»._ .-._.-_.._... .. _ _ ... ... . _ _.._.,___.. -,
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 12/09/81
PERMIT NO. ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VIII JOHN DALE <303 )-837-3763
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
Z ^ »^~z~ir~~^ ~ s * ~ t: Z ~» ^S~ ~~ ~ -. _ ^ __ _«.____.__ _ »._ . » »»«.^»_^._ «.
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
Z AUX BOILERS
FEED HEATER
MINE VENTS
OIL REEOILER
CO
NOX
PM
SOZ
CO
NOX
PM
SOS
PM
CO
NOX
PM
SOS
2.9000 LB/H
18.0000 LB/H
DESIGN
3.2000 LB/H
8.0000 LB/H
LOW S COAL
1.1000 LB/H
7.0000 LB/H
1.2000 LB/H
3.1000 LB/H
10.6000 LB/H
14.9000 LB/H
SETTLING
1.5000 LB/H
9.1000 LB/H
1.6000 LB/H
4.0000 LB/H
LOW S FUEL
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
PAGE G- 539
-------
(CONTINUED) TOSCO OIL SHALE-1981
PROCESSES SUBJECT
TO THIS PERMIT
ORE STORAGE
RECL TUNNEL
SEC CRUSHER
SPENT SHALE STOR
2 502 REC. PLANTS
4 REFORM FURN
6 ELUTRIATORS
6 PROCESS SHALE WET
THROUGHPUT POLLUTANT
CAPACITY EMITTED
PM
PM
PM
45.00 MB3L/D
PM
S02
CO
NOX
PM
S02
NOX
PM
S02
PM
= = - = = = = = = = - = = = = = = = = = = = = r: = = = = = = r = r = = = = = = r = rrz = = = r = "r =
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
4.7000 LB/H
BAGHOUSE
6.2000 LB/H
BAGHOUSE
36.6000 LB/H
BAGHOUSE
7.9000 LB/H
WVTER
92.2000 LB/H
CLAUS iTAILGAS
10.8000 LB/H
90.3000 LB/H
12.0000 LB/H
30.1000 LB/H
LCU S FUEL
15.8000 LB/H
42.0000 LB/H
SCRUBBER
5.3000 LB/H
43.2000 LB/H
SCRUBBER
. . . « BASIS
... PCT EFF
BACT
99.70
BACT
99.70
BACT
99. 70
EACT
50.00
BACT
99.60
BACT
BACT
BACT
EACT
BACT
BACT
99.99
BACT
BACT
93.40
PAGE G- 540
-------
{CONTINUED) TOSCO OIL SHALE-1981
6 PREHEAT STK
THROUGHPUT POLLUTAHT EMISSION LIMITS .. . j BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
VOC 303.0000 LB/H BACT
INCINERATOR 85 00
NOX 1583.2000 LB/H BACT
PM 90.0000 LB/H BACT
SCRUBBER 99 99
S02 62.5000 LB/H EACT
ABSORPTION 5.00
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STARTUP
PAGE G- 541 ID NUMBER UT-0020
SCL^CE TYPE CCDE
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE -
CRUDE OIL/TUT. GAS PRODUCTION (INCL. OIL SHALE)
10.00 KSBL/D
COMPANY NAME/SITE LOCATION UNION OIL SHALE SI
NEAR PARACHUTE, CO
GARFIELD COUNTY
DETERMINATION IS
PERMIT HO.
DETERMINATION MADE BY
EPA REGION VIII
(AGENCY)
JOHN DALE
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 05/27/81
ESTIMATED DATE OF START-UP--
(303)-837-3763
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
H2 CHG HTR
DEARSENITER PURGE HTR
DEARSENITER CHARGE HTR
FRACT CHG HTR
REFORMER FURN
STEAM BOILER
THROUGHPUT POLLUTANT
CAPACITY EMITTED
24.00 MMSCFD
NOX
NOX
NOX
NOX
NOX
NOX
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
2.8000 LB/H
DESIGN
1.8000 LB/H
DESIGN
2.3000 LB/H
DESIGN
2.5000 LB/H
DESIGN
53.1000 LB/H
DESIGN
12.0000 LB/H
DESIGN
... 4 BASIS
... FCT EFF
BACT
BACT
BACT
BACT
EACT
BACT
99.90
PAGE G- 542
-------
(CONTINUED) UNION OIL SHALE 81
nUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . .. 4 BASIS
_____ _ CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
SULFUR REC.UNIT la.00 T/0
S02 300.0000 PPM BACT
1.9000 LB/H
CLAUS&TAIL GAS 99.90
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STA"TUP
r = = = - = ; = r = = = -::: = = = : = ::-=: = = = = = = : = - = _ = - = --- = _-__-____.___________________________________________
PAGE G- 543 10 NUMBER CO-001^
SOURCE TYPE CCDE
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE
CRUDE OIL/NAT. GAS PRODUCTION (IHCL. OIL SHALE)
106000.00 BPSD
COMPANY NAME/SITE LOCATION WHITE RIVER SHALE OIL CORP.
BONANZA) UT
UINTAH COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. MAJ 053062-IT
DETERMINATION MADE BY UTAH BAQ
(AGENCY)
CARL BROADHEAD
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 08/04/82
ESTIMATED DATE OF START-UP 1988
(80D-533-6108
(PHCME)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS . . . & BASIS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
IN-MINE PRIMARY CRUSHING
CRUSHING 4 SCREENS
MINE CONVEYOR SURGE BIN
89000.00 TPSD
176000.00 TPSD
176000.00 TPSD
MINE CONVEYOR TRANSFER POINTS 176000.00 TPSD
FEED TO STORAGE SILOS
SURFACE CRUSHING t SCREENS
176000.00 TPSD
176000.00 TPSD
PM
PM
PM
PM
PM
PM
WET SUPPRESSION
0.0200 GR/DSCF
BAGHOUSE
0.0130 6R/DSCF
BtGHOUSE
0.0130 GR/DSCF
BAGHOUSE
0.0130 G3/DSCF
BAGHOUSE
0.0130 GR/DSCF
BAGHOUSE
80.00
99.70
99.70
99.70
99.70
99.70
PAGE G- 544
-------
(CONTINUED) WHITE RIVER SHALE OIL CORP.
PROCESSES SUBJECT
TO THIS PERMIT
CONVEYORS
UNION RETORT SILO FEED
SUPERIOR RETORT SILO FEED
TOSCO RETORT SILO FEED
MAIN ACCESS ROADS
2ND LIGHT DUTY ROADS
--========================================s=====-====-=.==s=-.=_==___._.__=___.__..:.__.=____.:__
THROUGHPUT POLLUTANT EMISSION LIMITS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
TRANSFER 900.00 TPSD
VE 20.0000 X OPACITY
WET SUPPRESSION
PM 0.0130 GR/DSCF
FULLY COVERED
46400.00 TPSD
PM 0.0130 GR/DSCF
ED mooo.00 TPSD W6HOOSE
PM 0.0130 GR/DSCF
BAGHCUSE
18500.00 TPSD
PM 0.0130 GR/DSCF
3 SHALE 39550.00 TPSD
VE 20.0000 X OPACITY
FULLY COVERED CONVEYORS
EYORSHA* 8.000.00 TPSD 20X MOISTURE
VE 20.0000 X OPACITY
FULLY COVERED CONVEYORS
20X MOISTURE
PM
PAVE
PAVINS
... 4 BASIS
... PCT EFF
80.00
90.00
99.70
99.70
99.70
99.00
99.00
95.00
PM
MINIMIZE
CHEMICAL SUPPRESSION
75.00
PAGE S- 545
-------
(CONTINUED) WHITE RIVER SHALE OIL CORP.
PROCESSES SUBJECT THROUGHPUT POLLUTAN"
TO THIS PERMIT CAPACITY EMITTED.
TOSCO PROCESSED CONVEYOR SHALE 15000.00 TPSD
PM
PROCESSED SHALE CONVEYOR TRANSF* 149500.00 TPSD
VE
PROCESSED SHALE DISPOSAL 149500.00 TPSD
PM
LOAD IN 149500.00 TPSD
VE
GROOMING 112.00 SCRAPER H/D
VE
WIND EROSION 30.00 ACRE
PM
LOAD IN, RAW SHALE STOCKPILE 5000.00 TPSD
PM
LIVE STORAGE HIND EROSION, RAW * 175000.00 T
PM
GROOMING, RAW SHALE STOCKPILE 5000.00 TPSD
PM
F EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
MINIMIZE
20X MOISTURE COVERED CONVEYORS
20.0000 X OPACITY
15 X MOISTURE ENCLOSED
MINIMIZE
CHEM. DUST SUPPRES. COMPACT. ,REVEG.
20.0000 X MINIMIZE
15X HATER
20.0000 X OPACITY
WATERING
MINIMIZE
COMPACT. REVEG. 4 CHEM. DUST SUPPRES.
MINIMIZE
LCI.'ERING WELL
MINIMIZE
WATER SPRAYS
MINIMIZE
ViXTER SPRAYS
...» BASIS
... PCT EFF
99.00
99.00
85.00
60.00
50.00
85.00
75.00
50.00
50.00
DEAD STORAGE WIND EROSION, RAW * 2.80 MMT
PAGE G- 546
-------
(CONTINUED) WHITE RIVER SHALE OIL CORP.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
& BASIS
PCT EFF
PHASE III-UNION B RECYCLE GAS H* 960.00 MMBTU/H
PHASE III - HYDRO TREATER REACT* 150.00 MWBTU/H
TOSCO PREHEAT 4 BALL HEATERS
479.00 MM3TU/H
BOILER 8 POWER PLANTS (3 STK) 3438.00 MMBTU/H
PM 0.0210 LB/KttBTU
5.0000 LB/H STACK
S02 0.0230 LB/MM3TU
5.5000 LB/H STACK
TREATED GAS * UPGRADED SHALE OIL
NOX 0.0220 LB/Mf-IBTU
53.1000 LB/H STACK
LOW NOX BURNERS
PM 0.0200 LB/MM3TU
2.6000 LB/H STACK
S02 0.1600 LB/MKBTU
10.0000 LB/H STACK
CLEANED & TREATED HIGH BTU FUEL GAS
NOX 0.2600 LB/M.'STU
39.0000 LB/H STACK
PM 0.0240 GR/DSCF
22.5000 LB/H STACK
VENTL'31 SCRUBBER
S02 0.0020 GR/DSCF
0.5000 LB/H STACK
TREATED FUELS
NOX 0.2200 GR/OSCF
51.9000 LB/H STACK
LOU-NCX BURNERS
PM 0.0300 LB/r,t3TU
73.2000 LB/H
S02 0.0700 LB.'KMBTU
166.9000 LB/H
FGD
CLEANED & TREATED FUEL GAS,
NOX 0.2000 LB/HM5TU
487.5000 LB/H
99.50
50.00
UPGRADED SHALE OIL
80.00
PAGE G- 547
-------
(CONTINUED) WHITE RIVER SHALE OIL CORP.
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
CAPACITY EMITTED CONTROL EQUIPMENT CR PROCESS MODIFICATION ...' PCT EFF
Ha PLANT REFORMER FURNACE
NAPTHA & CRUDE STORAGE TANKS
GAS TREATMENT PLANT, 3 UNITS
FUEL GAS TREATED HIGH BTU
FUEL GAS TREATED LOW BTU
2058.00 MMBTU/H
28.00 MMBTU
PM
S02
NOX
S02
PM
NOX
H2S
T.S*
NH3
S
NH3
0.2000 LB/MMBTU
25.8000 LB/H
0.0070 LB/MM3TU
9.0000 LB/H
CLEANED, TREATED & UPGRADED FUELS
0.2100 LB/MMSTU
267.8000 LB/H
LOW-NOX BURNERS
FLOATING ROOF TANKS W/DBL SEALS
250.0000 PPMV AT OX 02
TREATED HIGH BTU FUEL GAS
0.1000 GR/DSCF
0.4900 GR/DSCF
10.0000 PPMV
75.0000 PFMV
10.0000 PFMV
25.00
NOTES
THE FEASIBILITY APPROVAL ORDER IS BASED ON BACT AS OF 1982. THIS IS A PHASE CONSTRUCTION PROJECT. EACH UNIT OF EACH PHA^E HILL
BE PERMITED BASED ON THE "THEN CUPRENT" BACT. TPSD = TON PER STREAM DAY
DIESEL FUEL SULFUR LIMIT - 0.20X BY WT. FUEL OIL - S = 20 PPMV , KH3 = 1500 PFMV.
{*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 548
ID.NUK3ER UT-0025
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1953
SOLACE TYPE CCDE 5.14
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1964
SOURCE TYPE/SIZE OIL AND GAS FIELD SERVICE
COMPANY NAME/SITE LOCATION DRLGMUD CO.
100000.00 LB/D
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. X-3973
DETERMINATION MADE BY TEXAS ACS
(AGENCY)
ROBERT MAUEL
(AGENCY CONTACT PERSON)
TX
FORT BEKD COUNTY
DATE OF PERMIT ISSUANCE-- 13/22/81
ESTIMATED DATE Or START-UP-- 1932
(512 1-451-5711
(PHONE)
SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS t B.*
..-....!.._. CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION .' '. '. PCT EFF
"~~~~~""""~"~""'~~~**""*~~~~""""""~ ~~*~~~"~~"~~^"""~~"~~*~"*'~~~~~*""~^'""- -*- » » . _ .__»«»,»__
SILO & LOADING 100000.00 LB/0
BAR* 0.1000 LB/H
VENT HOUSE TRAFFIC SHOP MADE FABRIC "LTER "-1°
PM 0.9000 LB/H
NOTES
[?^^TES_D^TUM_UASJRU*CATED FOR THIS TABLE. REVIEW STATUS""^"" " ^"^
PAGE G- 5<+9 ID Kur!BER TX-0116 "~SOUSCE^TYPE~CraE~~~5~15
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE---
OIL AND GAS FIELD SERVICE
COMPANY NAME/SITE LOCATION SIGMOR PIPELINE CO.
306.00 MMGAL/YR
SAN ANTONIO, TX
BEXAR COUNTY
DETERMINATION IS BACT FOR A NEW SOURCE.
PERMIT NO. 6348
DETERMINATION MADE BY TEXAS ACS
(AGENCY)
SAM CROWTHER
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 04/27/78
ESTIMATED DATE OF START-UP-- 1979
(512)-451-5711
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT
CAPACITY
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
S BASIS
PCT EFF
GASOLINE LOADING 3 RACKS (12 SP* 306.00 MMGAL/YR
DIESEL/KERO LOADING
STORAGE TANKS (7)
FUGITIVE VOC
153.00 H-IGAL/YR
217.00 MGAL
VOC 23.6000 T/YR
0.1250 LB/MGAL VOC
CARSON ADSORPTION
VOC 14.1000 T/YR
BOTTOM LOADING (SEE NOTE)
VOC 25.0000 T/YR
INT. FLOAT COVERS, WHITE TANKS
VOC 12.0000 T/YR
NONE
AP42
97.50
AP42
0.00
AP42
97.00
0.00
NOTES
CARBON ADSORPTION UNIT PURCHASE PRICE =$240,000 NOTE - BOTTOM LOADING IS CONSIDERED UNCONTROLLED, FUGITIVE VOC ESTIMATED ONLY
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 550
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER TX-008S
SOURCE TYPE CODE 5.15
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE-
COMPANY NAME/SITE LOCATION UNITED GAS PIPE LINE CO.
OIL AND GAS FIELD SERVICE 2000.00 Hp EA>NAT- GASj
CARTHAGE, TX
PANDLA COUNTY
DETERMINATION MADE BY
TEXAS ACB
(AGENCY)
J1H CARAMAY
{AGENCY CONTACT PERSON)
°" PERMIT ISSUANCE- 05/07X80
°*
(PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
"!ACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
SUPERIOR COMPRESSOR ENGINE 2000.00 HP
NOX 4.2000 G/BHP-H
TU3BQCHARGED
NOTES
<*> INDICATES DATUM WAS TPtWTATFn FPB THT* T4«fe nrvrr,, INITIAL REVIEW POST STARTUP
REVIEW
ID NUMBER TX-OOS4
-------
APPENDIX ~ DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE
PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION BEAR CREEK STORAGE
BIENVILLE, LA
BIENVILLE PARISH
DETERMINATION MADE BY
EPA REGION V!
( AGENCY)
TOM DIGGS
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE- 09/22/79
r*c t-r*nT i m
START-UP"
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS t BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . . '. PCT EFF
I.C. COMPRESSORi
GAS HEATERS, 3
REGENERATOR HEATERS, 3
7000.00 HP EA
UNKNOWN
UNKNOWN
NOX 11.7000 6/HP-H
AIR/FUEL RATIO
CO 1.4000 G/HP-H
AIR/FUEL RATIO
NOX 2.1000 LB/H
AIR/FUEL RATIO
NOX 0.4000 LB/H
AIR/FUEL RATIO
BACT
BACT
BACT
BACT
NOTES
<»> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
==================:======:==r====rzrr=r=r=====rr=
PAGE G- 552
REVIEU
ID NUMBER LA-0023
SGL'RCE TYPE CODE 5.16
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE -
PETROLEUM INDUSTRY OTHER
525600.00 MMGAL/YR
COMPANY NAME/SITE LOCATION CHEVRON USA, INC.
UT
DAVIS COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE
PERMIT NO.
DETERMINATION MADE BY UTAH BAQ
(AGENCY)
DONALD ROBINSON
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 07/08/82
ESTIMATED DATE OF START-UP-- 1933
(8011-533-6108
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS ... 4 BASIS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
SEPARATOR
525.60 MMGAL/YR
VOC
STEEL COVER-TOTAL
95.00
NOTES
AIR TIGHT STEEL COVER PLATES OVER THE ENTIRE SEPARATOR.
(») INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 553
INITIAL REVIEW POST STARTUP
REVIEW STATUS: C4/01/1933 OZ/13/19S4
ID NUMBER UT-002S
SO'JSCE TYPE CODE 5.16
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM INDUSTRY ~ OTHER
~~~l~~""' « "'" -"' -.-. .»_ _______ _ .__ ______ _«> -. __ ,. _.». ___ » _^_«,___
COMPANY NAME/SITE LOCATION COLORADO INTERSTATE GAS COLORADO SPRINGS, OK 80944
P.O. BOX 1087
DETERMINATION IS BACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 02/26/81
PERMIT NO. (REGION FILE NO.) PSD-OK-358 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOE WINKLER (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... 8 BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COMPRESSOR ENGINE
2700.00 HP
EMERGENCY GEN.
370.00 HP
NOX
CO
soa
VOC
PM
NOX
CO
S02
VOC
PM
0.0010 G/HP-H
TUHBOCHARGED CLEAN BURN
0.0010 G/HP-H
EFFICIENT COMBUSTION
0.0010 G/HP-H
EFFICIENT OPERATION
0.0010 G/HP-H
EFFICIENT COMBUSTION
EFFICIENT COMBUSTION
10.9000 G/HP-H
NORMAL OPERATION
1.4000 G/HP-H
NCSfl-'.L OPERATION
0.0010 G/HP-H
NORMAL OPERATION
0.8400 G/HP-H
NORMAL OPERATION
NCP.HAL OPERATION
BACT
BACT
BACT
BACT
BACT
BACT
BACT
BACT
EACT
BACT
PAGE G- 554
-------
(CONTINUED) COLORADO INTERSTATE GAS
PROCESSES SUBJECT THROUGHPUT POLLUTANT
TO THIS PERMIT CAPACITY EMITTED
801 LER 2.60 MM8TU/H
NOX
CO
S02
VOC
PM
EMISSION LIMITS . . . S BASIS
CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
0.3200 LB/H
NORMAL OPERATION
0.0500 LB/H
NORMAL OPERATION
O.OOZO LB/H
NORMAL OPERATION
NORMAL OPERATION
0.0130 LB/H
BACT
BACT
BACT
BACT
BACT
NORMAL OPERATION
NOTES
OPERATED ONLY DURING POWER OUTAGES. BOILER OPERATED ONLY DURING COLD WEATHER.
IAS TRUNCATED FOR THIS TABLE. REVIEW
PACE R_ ccc ,_ ,,
rMJl- ^> ->jj T n *Fi ' . ij , _ i ., ^.
SCJxCE TYPE CCDE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/23/1984
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION HOUSTON PIPE LINE CO. HOUSTON, TX 77001
HOUSTON NAT. GAS BLDG 14TH FL.
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 04/30/81
PERMIT NO. TX-313 . ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK <214 )-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT 07? PROCESS MODIFICATION ... PCT EFF
I.C. ENGINES, 4 TURSO. 2400.00 HP EA
NOX 60.8000 LB/H BACT
11.5000 G/HP-H
AIR/FUEL RATIO CONTROL
DEHYDHATORS, 2 1.25 MMBTU/H EA
NOX 0.1500 LB/H BACT
0.1200 LB/ttt!BTU
COMBUST. CONTRL, EFF. DESIGN
NOTES
EACH OF THE I.C. ENGINES WERE LIMITED TO 0.65 G/HP-H FOR CO, HOWEVER, POLLUTANT WAS NOT REVIEWED UJJDER PSD.
INITIAL P.JVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 556 ID NUMBER TX-00/6 SOURCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER
"" ~"~ ~"~" ~ -" .-__. ___.___.__ ,^,_ __. __ _ __.»____,_____ _ _ _ _ __. _ .. -, _..-._»__ __ .,_ __ _ __ _ « .__ ,»-_ ___ _
COMPANY NAME/SITE LOCATION OASIS PIPELINE CO. HOUSTON, TX 77001
1200 TRAVIS, BOX 1188
FOR * MODIFIED SOURCE- »*TE OF PERMIT ISSUANCE- 10/06/80
DETERMINATION MADE BY EPA PESION VI JOHN BUNYAK
(AGENCY) (AGENCY CONTACT PERSON) ( PHCNE )
THROUGHPUT POLLUTANT EMISSION LIMITS . . . 4 BASIS
___________ CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION . . . PCT EFF
COMPRESSOR ENGINE 1350.00 HP EA
NOX 6.8600 G/HP-H BACT
LOW EX. AIR -- AIR/FUEL RATIO 37 00
VOC 0.7000 G/HP-H BACT
EFFICIENT COMBUSTION
CO 1.4000 G/HP-H BACT
EFFICIENT COMBUSTION
NOTES ........
l:L^^^nL^I^=^!J^^I^=^!_I^!.^Bb!: ____________________________
PAGE G' 55? 10 N^SER TX-003S
-------
APPENDIX DETAILED SOURCE LISTING
05/22/193*
SOURCE TYPE/SIZE
PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION ODESSA NATURAL CORP.
CISCO, TX
EASTLAND COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-TX-36S
DETERMINATION HADE BY EPA REGION VI
(AGENCY)
BILL TAYLOR
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 03/02/81
ESTIMATED DATE OF START-UP--
( PHONE )
PROCESSES SUBJECT
TO THIS PERMIT
TURBINE
I. C. ENGINES, 2 EA
THROUGHPUT POLLUTANT
CAPACITY EMITTED
7660.00 HP
NOX
CO
1560.00 HP
NOX
CO
EMISSION LIMITS
CONTROL EQUIPMENT OR PROCESS MODIFICATION
1.3000 G/HP-H
AIR/FUEL RATIO
0.5000 G/HP-H
AIR/FUEL RATIO
6.5000 G/HP-H
AIR/FUEL RATIO
2.2000 G/HP-H
... i BASIS
... PCT EFF
BACT
BACT
BACT
BACT
AIR/FUEL RATIO
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 55S
ID NUMBER TX-0028
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 0^/01/1933
SOURCE TYPE CCDE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198"+
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION PANHANDLE EAST. PIPELINE
ALVA, OK
WOODS COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE
PERHIT NO. (REGION FILE NO.) PSD-OK-330
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
BILL TAYLOR
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 05/29/81
ESTIMATED DATE OF START-UP--
(214 1-767-1594
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
I.C. ENGINE, 3 EA
I.C. ENGINE
THROUGHPUT
CAPACITY
4500.00 HP
631.00 HP
POLLUTANT EMISSION LIMITS
EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
NOX 6.0000 G/HP-H
AIR/FUEL RATIO
CO 4.8000 G/HP-H
AIR/FUEL RATIO
NOX 11.5000 G/HP-H
AIR/FUEL RATIO
CO 5.5000 G/HP-H
AIR/FUEL RATIO
& BASIS
FCT EFF
BACT
BACT
BACT
BACT
NOTES
<»> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 559
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER OK-0003
SOURCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM INDUSTRY -- OTHER
-. _-. . _._ __ _«. _ _.«._-. .. _-.. -. _ , _ _
COMPANY NAME/SITE LOCATION PANHANDLE EAST. PIPELINE CASHION, OK
CASHION STATION KINGFISHER COUNTY
_. ,_. _.». ... . ,.. _.. ,_ ____..__.. _ _, _ _ _ . _
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 05/08/81
PERMIT NO. (REGION FILE NO.) PSO-CK-329 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA RESICH VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
«- ^ wv. _ IB _ . _ V . _ ^ _v ,» _ . . _ ^ i _. _ »^^ _«._._.- _ _ _ _ _ _ ... _. ... _ _ __ _ .
I. C. ENGINE, 2 EA 4500.00 HP
NOX 9.0000 G/HP-H BACT
AIR/FUEL RATIO
CO 9.0000 G/KP-H BACT
AIR/FUEL RATIO
NOTES -
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 560
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 0^/01/1933
ID NUMBER OK-0009
SOURCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/l8<»
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION PANHANDLE EAST. PIPELINE
TX
DETERMINATION IS BACT FOR A MODIFIED SOURCE
PERMIT NO. (REGION FILE NO.) PSD-TX-321
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 02/11/81
ESTIMATED DATE OF START-UP--
(214)-767-159<»
(PHONE)
THROUGHPUT POLLUTANT EMISSION LIMITS . . . 4 BASIS
-.-.______ CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COMPRESSOR ENGINE 771.00 HP
NOX 11.5000 G/HP-H BACT
AIR/FUEL RATIO
VOC 1.7000 LB/H BACT
EFFICIENT COMBUSTION
CO 5.7000 G/HP-H BACT
EFFICIENT COMBUSTION
NH3 0.0090 LB/H BACT
EFFICIENT COMBUSTION
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 561
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 0^/01/1933
ID NUMBER TX-0042
SO'JSCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/19S1*
SOURCE TYPE/SIZE- PETROLEUM INDUSTRY OTHER
~ ~~~* """^"""~"""""'''"~"*"~~~~I'~"~~""1~*"~ ~~'~""1~""-""*~ » " '" " «» -- - ..___.__,. _.____.
COMPANY NAME/SITE LOCATION PANHANDLE EAST. PIPELINE , TX 64141
6 KM SW GARNER OIL FD. CARSON COUNTY
" -,_» _ ___ .. __..______,.__________________ __________ ,_ _______
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 02/11/81
PERMIT NO. (REGION FILE NO.) PSD-TX-320 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214j-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COMPRESSOR ENGINE
771.00 HP EA
NOX 11.5000 G/HP-H
AIR/FUEL RATIO
VOC 13.5000 LB/H
EFFICIENT COMBUSTION-
CO 5.7000 G/HP-H
EFFICIENT COMBUSTION
NH3 0.6800 LB/H
EFFICIENT COMBUSTION
BACT
BACT
BACT
BACT
NOTES
AIR/FUEL RATIO WITH A RESULTANT Z7. FUEL SACRIFICE
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 562
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID NUMBER TX-0044
SOURCE TYPE CCDE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
= = r = = = = = = -rr = r= = = r = = = rrr = = r = = ___________________________ _ _ 05/32/1934
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER
--- ""* ---- -.-_--- -- _ ----- , -- :_ ---- -- - - -- _ _»___«.___.^«
^*"*"~~*-~*' ~ *- «» '- -« ». . »_«. »._ .» _
COMPANY NAME/SITE LOCATION PANHANDLE EAST. PIPELINE AMARILLO, TX
CARSON COUNTY
DATE OF PERMIT ISSUANCE- 02/11/61
DETERMINATION MADE BY EPA RESION VI TOM DIGSS ?f-2S * START'UP"
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
=== ==^===== = ^======== ============^===========^= ._... _____ ==.. = ... = ......._._........_..
THROUGHPUT POLLUTANT EMISSION LIMITS 4 BASrs
__..._____._ ......... CAPACITY EMITTED CONTROL EQUIPMENT OH PROCESS MODIFICATION .'.'. PCT EFF
*"~""""~~~'~~ --*- - ----- -- -- -*-» ----------^--_--_«- --- -------_ _-_*__. -- _--__»___»_._
I.C. ENGINES, 3 771.00 BRAKE HP EA
NOX 11.5000 G/HP-H BACT
AIR/FUEL RATIO
CO 5.7000 G/HP-H - BACT
AIR/FUEL RATIO
NOTES -----------
THIS TA8LE-
POST STARTUP
-------
APPENDIX DETAILED SOURCE LISTING
05/32/1934
= = = = = = r = = r = = = = = = = = = r = = = = = = r: = rz = = = == = r = === = = = = = = = = = = = = = = = = = === = = = = = = = = = = = = = = = = = = = === = = = = = = ==== = = = = = = = = = = = = -== = = = === === = :: = :: = ::-::: = -- =
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION PETRO-LEWIS CORP. ' CA
DETERMINATION IS LAER FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE- 02/23/84
PERMIT NO. 4052033-037 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY KERN COUNTY APCO TOM PAXSOM (605)-861-3682
(AGENCY) (AGENCY CONTACT PERSON) (PHCME>
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
_ '--------
GENERATOR, STEAM, 5 EA 62.50 MMBTU/H
PM 0.0340 LB/MMBTU
50.6600 LB/D
KET SCRUBBER 61.00
SOX 0.0230 LB/MM3TU
34.8100 LB/D
VENTURI SCRUBBER 30.00
NOX 0.1200 LB/tt3TU
181.3000 LB/D
STAGED COMBUSTION 70.00
NOTES
INITIAL REVIEW POST STARTUP
(*l INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS'-
= -- = = - = = = = r = rrr = = rr = : = :r = r = = = = : = = = = = rr = = = = = = = = = = = = = = = = = = : = = = = = = = = = = = = = = = = = = = = = = = - = = = = ::::: = = = = = = = = = =
PAGE~G-~564ID NUf1BER CA-0053 SOURCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/198'*
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION REFINERY WASTE GAS RECOVERY , CA
KERN COUNTY
DETERMINATION IS DATE OF PERMIT ISSUANCE 03/19/S4
PERMIT NO. SEE NOTE ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY KERN COUNTY APCD TOM PAXSON (8051-861-3682
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
VAPOR COMPRESSOR, VALVES, * FLA* 720000.00 SCF/D
VOC 28.9000 LB/D
I & M TO MINIMIZE FUG. EMIS. 65.00
NOTES
NOTE -- PERMITS NUMBERS 2018008A, 2018012B, 2018046A, 2018062. SOURCE WILL OPERATE 24 H/D, 7 D/WEEK, 52 WEEK/YR.
INITIAL F^VIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS--
PAGE G- 565 ID NUMBER CA-0065 SOURCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER 8200.00 BBL/D
COMPANY NAME/SITE LOCATION SHELL OIL CO. , US 70161
PIKE COUNTY
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/17/80
PERMIT NO. MS 025 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY MISSISSIPPI DK'R DUIGHT WILEY (601 )-35
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1934
SOURCE TYPE/SIZE- PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION SOUTHERN NAT. GAS BIENVILLE, LA
BIENVILLE BIENVILLE PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 09/11/81
PERMIT HO. (REGION FILE NO.) PSO-LA-406 ESTIMATED DATE OF START-UP--
DETERMINATION MADE BY EPA REGION VI BILL TAYLOR (214)-767-15<54
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... S BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. ENGINES, Z EA 448.00 BRAKE HP
NOX 11.0000 G/HP-H BACT
AIR/FUEL RATIO
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 567
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1953
ID NUMBER LA-0009
SOURCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER
« «- ^ «- ^ » -. -^ «, «.-.«..«..._ !_.» ^--^ ._» _^ _ __ _ __
COMPANY NAME/SITE LOCATION SOUTHERN NAT. GAS FRANKLINTON, LA
WASHINGTON PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 07/17/80
PERMIT NO. (REGION FILE NO.) PSD-LA-267 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK 1214)-767-159<+
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
- - -. . _-.-._-. _ _ _-. _ ___ __»_«»_«._ «.«.-. ^ _ _-. «_ ._ ___«__«._ « _w __ »^-.____w.-.-1. ___ _ _-._,.. __ __.»...._ _. __
I.C. ENGINE 5000.00 HP
NOX 182.0000 LB/H BACT
CO <+.0000 LB/H BACT
AIR/FUEL RATIO
NOTES
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 563
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/15S3
ID NUMBER LA-0021
SOURCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/196*
SOURCE TYPE/SIZE
PETROLEUM INDUSTRY ~ OTHER
COMPANY NAME/SITE LOCATION SUN GAS CO.
THREE NORTH PARK EAST ST.
DALLAS, TX
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-TX-R72
DETERMINATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE 02/26/81
ESTIMATED DATE OF START-UP
( PHONE )
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS . . . & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OS PROCESS MODIFICATION ... PCT EFF
COMPRESSOR ENGINE, 2 1200.00 HP
NOX 9.1000 G/HP-H BACT
AIR/FUEL RATIO,IGNITION RETARD
CO 1.2000 G/HP-H BACT
AIR/FUEL RATIO,IGNITION RETARD
COMPRESSOR 600.00 HP
NOX 9.1000 G/HP-H BACT
AIR/FUEL RATIO,IGNITION RETARD
CO 1.2000 G/HP-H BACT
AIR/FUEL RATIO,IGNITION RETARD
NOTES
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 569 ID N'JMSER TX-OC26 , SO'JRCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION TEXACO, INC. EAST COTE BLANCHE BAY, LA
IBERIN PARISH
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 07/30/81
PERMIT HO. (REGION FILE NO.) PSD-LA-382 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BENHAM (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ...» BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
I.C. ENGINE 8 1560.00 BRAKE HP
NOX 10.0000 G/HP-H BACT
AIR/FUEL RATIO
I.C. ENGINE 1 40.00 BRAKE HP
CO 10.0000 G/HP-H BACT
AIR/FUEL RATIO
NOTES
INITIAL REVIEW POST STARTUP
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS: 04/01/1933
PAGE G- 570 ID NUMBER LA-001E SOURCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION TEXACO, INC. NEW ORLEANS, LA 70160
P.O. BOX 60252
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 07/27/81
PEPMIT NO. (REGION FILE NO.) PSD-LA-381 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (21
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM INDUSTRY -- OTHER 6300.00 HP
COMPANY NAME/SITE LOCATION TEXACO, INC. NEW ORLEANS, LA
1501 CANAL ST., P.O. BOX 60252
. .. _.. ,-,_.. .._.. .. *-
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 08/Z9/80
PERMIT NO. (REGION FILE NO.) FSD-LA-301 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... FCT EFF
___._ _ _ _ _ _ .. .* ~ -, » «» . -. ..
ENGINE, I.C., TURBOCHARGED 2650.00 HP
NOX 43.7000 LB/H BACT
7.5000 G/HP-H
IGN. TI. RETARD ENG. SPARK
TURBINE COMPRESSOR, GAS-FIRED 3300.00 HP
NOX 9.4000 LB/H NSPS
1.3000 G/HP-H
I.C. ENGINE, NAT. ASPIRATED 350.00 HP
NOX 7.7000 LB/H BACT
10.0000 G/HP-H
AIR/FUEL RATIO CONTROL
NOTES
INITIAL REVIEW POST STARTUP
<*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEU STATUS: 04/01/1033
PAGE G- 572 ID NUMBER LA-0033 SG'JRCE T1PE CODE 5.16
-------
APPENDIX -- DETAILED SOURCE LISTING
05/22/198*
SOURCE TYPE/SIZE
PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION TEXACO, INC.
1501 CANAL ST
NEW ORLEANS, LA 70160
DETERMINATION IS BACT FOR A MODIFIED SOURCE.
PERMIT NO. (REGION FILE NO.) PSD-LA-300
DETERfUNATION MADE BY EPA REGION VI
(AGENCY)
JOHN BUNYAK
(AGENCY CONTACT PERSON)
DATE OF PERMIT ISSUANCE-- 08/29/80
ESTIMATED DATE OF START-UP
( 214 )-767-159<+
(PHONE)
PROCESSES SUBJECT
TO THIS PERMIT
THROUGHPUT POLLUTANT EMISSION LIMITS
CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION
... & BASIS
... PCT EFF
I. C. ENGINE, TURBOCHARGED
I. C. ENSINE, TURBOCHARGED
I. C. ENGINE, NAT. ASPIRATED
2650.00 HP
2650.00 HP
TURBINE, GAS FIRED, COMPRESSION 3500.00 HP
500.00 HP
NOX 7.5000 G/HP-H
43.7000 LB/H
CON IGN TIM/RETARD ENGINE SPARK
NOX 7.5000 G/HP-H
43.7000 LB/H
CON IGN TIM/RETARD ENSINE SPARK
NOX 1.8000 G/HP-H
14.2000 LB/H
NONE
NOX 10.0000 G/HP-H
11.0000 LB/H
AIR/FUEL RATIO CONTROL
BACT
BACT
BACT
BACT
NOTES
(») INDICATES DATUM WAS TRUNCATED FCR THIS TABLE.
PAGE G- 573
INITIAL REVIEW POST STARTUP
REVIEW STATUS: 04/01/1933
ID N'trBER LA-OO^O
SC'_"CE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE- PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION TRUNKLINE LNG CO. LAKE CHARLES, LA
CALCASIEU PARISH
DETERMINATION IS EACT FOR A NEW SOURCE. DATE OF PERMIT ISSUANCE 04/25/83
PERMIT NO. PSD-LA-97,M-1 ESTIMATED DATE OF START-UP
DETERMINATION MADE BY LAQD/EPA REGION VI BHARAT CONTRACTOR (5041-342-8940
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... * B4SIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
TURBINE, GAS, 2 105.00 MMBTU/H
NOX 79.0000 LB/H N/A
CCMB. CONTRL, 02 & CO MONITOR
VAPORIZER, LNG, 7 EA 72.54 NMBTU/H
NOX 3.6600 LB/H N/A
COMBUSTION CONTROL
HEATER, FUEL GAS, 2 EA 3.50 MMBTU/H
NOX 0.6300 LB/H N/A
NOTES - --
THE ORIGINAL PERMIT, PSD-LA-97, WAS ISSUED ON 02/09/79 BASED ON 75. PPM NOX EMISSION LIMITS UNDER NSPS. HOWEVER, THE NSPS AMME
NDED CM 01/27/82, SPECIFICALLY EXEMPTED THESE TURBINES FROM H20 INJECTION CONTROLS.
INITIAL WIEW POST STARTUP
<*> INDICATES DATUM WAS TRUNCATED FOR THIS TABLE. REVIEW STATUS:
PAGE G- 574 ID NUMBER LA-0047 SOURCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOURCE TYPE/SIZE PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION UNITED GAS PIPE LINE CO. HOUSTON, LA 77001
P.O. BOX 1478
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE 03/04/80
PERMIT NO. (REGION FILE NO.) PSD-LA-230 ESTIMATED DATE OF START-UP-
DETERMINATION MADE BY EPA REGION VI JOHN BUNYAK (214)-767-1594
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... & BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT ErF
" - -* « _ < ..«. ____»,_»_-. »____,_.w.___,_.__ _,, _ 1M««» »... W _ .«_.._._ _«.____w_._ _ _ _._.__-.___ ..____.».__..,_,.__.>__ ..
COMPRESSOR ENGINE, 3 EA 3500.00 HP
NOX 107.9000 LB/H EA BACT
30.8000 LB/MHP-H
CON. AIR/FUEL RATIO, IGN. TIM.
NOTES
(«) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 575
INITIAL REVIEW POST STARTUP
REVIEM STATUS; 0^/01/1933
ID NUMBER LA-0039
SC'JRCE TYPE CODE 5.16
-------
APPENDIX DETAILED SOURCE LISTING
05/22/1984
SOIRCE TYPE/SIZE--- PETROLEUM INDUSTRY OTHER
COMPANY NAME/SITE LOCATION UNITED PIPE LINE CO. HOUSTON, TX 77001
P.O. BOX 1478
DETERMINATION IS BACT FOR A MODIFIED SOURCE. DATE OF PERMIT ISSUANCE-- 03/04/60
PERMIT NO. TX-211 ESTIMATED DATE OF START-UP--
DETERMINATION HADE BY EPA REGION VI JOHN BUNYAK (214J-767-15S4
(AGENCY) (AGENCY CONTACT PERSON) (PHONE)
PROCESSES SUBJECT THROUGHPUT POLLUTANT EMISSION LIMITS ... t BASIS
TO THIS PERMIT CAPACITY EMITTED CONTROL EQUIPMENT OR PROCESS MODIFICATION ... PCT EFF
COMPRESSOR ENGINE, 3 1000.00 HP EA
NOX 31.5000 LB/H BACT
31.5000 LB/MHP-H
CNTRL AIR/FUEL RATIO, IGN TIM.
NOTES
(*) INDICATES DATUM WAS TRUNCATED FOR THIS TABLE.
PAGE G- 576
INITIAL REVIEW POST STARTUP
REVIEW STATUS; 04/01/1933
ID NUMBER TX-0070
SC'JRCE TYPE CODE 5.16
------- |