United States
                    Environmental Protection
                    Agency
Municipal Environmental Research ^»  '"i
Laboratory                    ^Er*
Cincinnati OH 45268             '/1  i
                    Research and Development
EPA-600/S2-84-087  May 1984
&ERA         Project Summary
                    Operation  and  Maintenance  of
                    Selected  Ozone and Ultraviolet
                    Disinfection  Systems
                    Randy Junkins
                      A series of onsite evaluations were
                    made of wastewater and drinking water
                    treatment plants that use ozone or ultra-
                    violet (UV) light disinfection in place of
                    chlorine disinfection. The object was to
                    compile design and operational informa-
                    tion on such plants. The  evaluations
                    were conducted at 10 municipal waste-
                    water treatment  plants (7 that have
                    used or are using ozone for disinfection
                    and 3 that have used or are using UV
                    disinfection) and at 5  drinking water
                    treatment plants (all of which use ozone
                    for disinfection or odor control or both).
                    During these plant visits, operating data
                    were reviewed, operational  practices
                    were observed, and operating personnel
                    were interviewed to establish factors
                    related to both poor and efficient pro-
                    cess performance.  Typical operation
                    and maintenance problems are listed,
                    and the recommended remedial actions
                    for correcting those problems are pre-
                    sented.

                      This Project Summary was developed
                    by EPA's Municipal Environmental Re-
                    search Laboratory,  Cincinnati. OH, to
                    announce key findings of the  research
                    project that is fully documented in  a
                    separate report of the same  title (see
                    Project Report ordering information at
                    back).
                    Introduction
                      Alternatives to chlorine disinfection of
                    municipal wastewater have been given
                    increased attention in recent years. Two
                    alternative approaches that have gener-
                    ated particular interest  are ozone and
                    ultraviolet (UV) light disinfection. This
project was initiated to identify operation
and maintenance (O&M) factors affecting
the performs nee of ozone a nd U V disi nf ec-
tion systems. The study was part of U.S.
Environmental  Protection Agency (EPA)
efforts to compile and promulgate design
and operational information on ozone and
UV light disinfection of municipal waste-
water.
  The object of the study was to deter-
mine, analyze, and set priorities for those
O&M factors that affect the operational
efficiencies of ozone and UV disinfection
systems. During the study, onsite evalua-
tions were conducted at 10 municipal
wastewater treatment plants and  5
municipal water treatment plants that
use ozonation or UV irradiation for disin-
fection or taste and odor control or both.
During these plant visits, operating per-
sonnel were  interviewed,  operational
practices were observed, and operating
data were  reviewed to identify  O&M
factors related to both poor and efficient
process performance. The  information
compiled was documented in individual
plant evaluation reports, which are sum-
marized in  the final project report. The
project report presents the O&M problems
encountered, conclusions drawn concern-
ing their cause, and recommendations for
their resolution.

Results
  Fifteen sites were  visited  during the
study. Twelve of the facilities used ozone
systems for disinfection or taste and odor
control or both, and three of the plants
used UV disinfection systems. Data con-
cerning the ozone and UV systems evalu-
ated are presented in Tables 1 and 2,
respectively.

-------
Table 1.
Plant
No.
1
2*

3

4

5t

6f

7t
8

9

10

11
12

System Data
Number
of
Generators
17
2

3

13

2

3

3
2

4

6

4
4

for Ozone Plants
Generator
Manufacturer
Union Carbide
Welsbach

Emery

Union Carbide

Emery

Emery

Union Carbide
PCI

Welsbach

Trailigaz

Trailigaz
Degremont

Total
Capacity
kg/day
(Ib/day)
2,082
(4,590)
69
(152)
782
(1.725)
1,562
(3,445)
113
(250)
381
(840)
571
(1.260)
204
(450)
453
(1.000)

3,479
(7,680)
204
(450)
227
' '
Carrier
Gas
02
Air

Air

02

Air

02

°*
Air

Air

Air

Air
Air

Actual
03
Transfer
Efficiency*
50
50

60

95

67

84


—

85

80

--
94

"Transfer efficiency = OzfinJ-Osfout)
• Ozone system electronics are too
complicated for plant personnel to
perform routine maintenance and
repair work.
• Corrosion problems occur with Oa
analyzer valve components.
• Ozone contact tanks were constructed
belowthe system control room, and Oa
leaks cause instrumentation rubber
seals to corrode.
• System equipment (i.e., generators and
compressors) is very noisy.

• The system includes numerous pieces
of equipment that must be maintained.
• System instrumentation must be con-
tinually calibrated.
• Ozone generators are a high mainte-
nance item and continually blowf uses.
• Corrosion problems with compressors
occur because of wet gases.
• Catalyst poisoning occurs in 03 de-
struction system.

• No dew point monitoring equipment is
provided with the ozone system.
• Excessive heat buildup in the O3
generator room causes generator
heaters to shut down units.
A MnnfnmnntiHIf* matariale ftret ncoH in
                     O3 fin)


Table 2.   System Data for UV Plants
t/Vof in operation.
Plant
No.
13
14
15
UV
Manu-
facturer
Pure Water
Systems
Aquafine
Ultraviolet
Technology,
Inc.
No. of
Sections
6
4
3
Total
Number of
Lamps
392
128
48
Lamp
Length
m (in.)
1.5
(60)
1.5
(60)
0.8
(30)
Cleaning
Mechanisms
Mechanical
Wiper
Mechanical
Wiper
Chemical
Detergent
Flow/
Unit
m3/d
(mgd)
2.839
(0.75)
4,163
(1.25)
113
(0.03)
Arc Length
Unit of Flow.
m/m3/per
day
(in./gpm)
44,451
(4.6)
28,990
(330)
289.902
(30)
Costs

  Annual costs for ozone plants  with
compiled  historical cost, data  are  pre-
sented in Table 3. The average ozone
production cost for the 12 plants surveyed
is $4.20/kg ($1.90/lb) of ozone gener-
ated. Very few operating cost data were
available for  the  UV plants surveyed
during the project. One plant reported a
UV disinfection operating cost of approxi-
mately $0.18/1,000 gallons treated.
                                        Typical Problems Encountered
                                          Typical O&M problems encountered
                                        with ozone  disinfection systems  were
                                        maintenance-related and are as follows:

                                        • Multiple and frequent failures occur in
                                           the ozone generator cell.
                                        • Failures occur  in the silicone control
                                           rectifier (SCR).
                                        • Severe foam problems occur with the
                                           contact tank gas recovery system.
  construction: Rubber sleeves are used
  on  compressors,  and  chlorinated,
  rubber-based paint is used to seal the
  ozone contact chamber.
  Dew point meters are not reliable.
  Improper  (i.e.,  too  high)  dew  point
  setting causes dielectric failures.
  Improper cleaning procedures for  di-
  electric tubes cause pitting and crack-
  ing of tubes.
  Typical  O&M  problems encountered
with UV disinfection systems included
the following:

• Ballasts on the UV lamps overheat and
   shut down the system.
• Unit does not consistently disinfect
   plant effluent to the degree required by
   National Pollution Discharge Elimina-
   tion System (NPDES) permit.
• Foam buildup interferes with operation
   of the cleaning mechanism.
• Low flow rate causes  the unit  to
   overheat.
• Algae accumulations in the unit inter-
   fere with system operation.

-------
Conclusions
  Most of the O&M problems experienced
with the ozone disinfection systems sur-
veyed were site-specific and not prevalent
problems that repeatedly occurred at all
the sites visited. The most common prob-
lems identified were the following:

• Inefficient  ozone destruction  in  the
   destruct unit.
• Ozone generator cell failure.
• Ozone leakage from the generator.
• Inadequate  air-drying in the inlet air
   desiccant dryer.
• Improper sealing of the ozone contact
   tank.
• Malfunctioning of the ozone concen-
   tration monitors.

  Limited information was available con-
cerning the operation of UV disinfection
systems; but as with ozone disinfection,
most of the O&M  problems identified
were site-specific and  not widespread
occurrences.
Table 3.    O&M Cost Summary for Ozone Systems
Plant
No.
1

2

3

5

8

9

10

11

12
0.5

Plant Name
Rocky River WWTP

Upper Thompson WWTP*

Frankfort WWTP

Brookings WWTP*

Monroe WTP

Bay Metro WTP

Charles J. Des Baillets WTP

Pierrefonds WTP

Sherbrooke WTP


Current
Average
Flow
ma/day
(mgd)
45.420
(12.0)
2.271
(0.6)
17.033
(4.5)
8.327
(2.2)
26.469
(7.0)
37.851
(10.0)
798.656
(211)
56.800
(15)
58,700

(15.51
Ozone
Production
kg/day
(Ib/day)
1.010
(2.227)
22
(49)
85
(187)
27
(60)
36
(79)
97
(214)
1.740
(3.836)
135
(298)
113

(250)
Ozone
Production Cost
(/kg Ozone
Produced
(C/lb)
63
(28)
602
(272)
382
(173)
488
(221)
903
(408)
575
(261)
191
(86)
342
(154)
259

(116)
C/m3 of O2
Treated
(C/ 1.000 gal)
1.4
(5.2)
5.8
(22)
1.9
(7.1)
1.2
(5.9)
1.2
(4.8)
1.5
(5.8)
0.4
(1.4)
0.8
(2.9)


(2.0)
*Not in operation.
Remedial Actions
Recommended

  Remedial  actions recommended for
correcting O&M problems observed at
ozone and UV plants are  presented in
Tables 4 and 5.
Table 4.
           Recommended Remedial Actions for Correcting O&M Problems Observed at Ozone
           Plants
             Problem
                                                   Remedial Actions
Foam buildup in Oa contact tank


Os generator cell failure


Poor Oa transfer efficiency in the
Oa contact tank

Oa leakage from generator


Poor O3 destructor performance
                                           Premature shutdown of feed-gas
                                           compressor

                                           Failure of silicone control rectifier
                                           System air compressors discharge
                                           more air than required

                                           Refrigerant dryer, overloaded
                                           Inefficient performance of inlet
                                           air desiccant dryer
Provide foam sprayer in contact tank or separate foam
spray tanks between O3 contact tanks and O3 destruct unit.

Purge O3 generator before startup to ensure the unit is
clean and free of dust or rust particles.

Routinely inspect Oa diffusers and clean when required.
Replace damaged cells in generator; adequately ventilate
the Oa generator room.

Increase the quantity of catalyst in the destruct unit; install
an electric airpreheater before the destruct unit; check for
leakage from destruct unit; replace catalyst.

Replace faulty surge/vibration monitor.
                                 Determine cause of problem and replace faulty silicone
                                 control rectifier.

                                 Change pulley size to reduce operating speed.
                                 Check the  inlet  air compressor water seal system to
                                 ensure that the compressor is not overheating and heating
                                 the inlet air to the dryer.

                                 Recharge the dryer with new desiccant material; check
                                 that the desiccant generation heaters are not operating at
                                 too high a  temperature; install a dew point indicator/
                                 controller to initiate  the  desiccant regeneration  cycle
                                 automatically when "wet  air" is being discharged from
                                 dryer; check the desiccant to ensure  it is not being
                                 contaminated with sulfate. chloride, iron (rust) or some
                                 other constituent; clean the purge-air filter.

-------
Table 4.    (continued)
              Problem
                  Remedial Actions
Standby electrical generator will
only operate one Oa generator
at a time

Oa piping leakage
Ozone contact tank not covered
and/or properly sealed


High O3 levels in the WWTP
nonpotable water system

Insufficient number of Oa monitors
at WWTP

Dielectric tubes overheating and
breaking because of corrosion
problems


Malfunction of cooling H2O flow and
Oa generator gas pressure sensors/
alarms

Fluctuating ozone generation
Voltage surges that damage
electrical components and
instrumentation


Malfunction of Oa concentration
monitor

High noise levels around Oa
generation equipment


Drive belts on exhaust fans in Oa
generation room frequently fail

Oa generator side panel fasteners
frequently fail

Oa gas sampling equipment leaks
 Oa generator shutdown because
 of high temperatures in generator
 room

 Oa exhaust vent located too near
 building air intake causing high
 ambient 03 concentration inside
 building

 Ice buildup at outlet of Oa exhaust
 vent caused blockage of vent

 Switchover valves on inlet air
 dryer towers ma/function

 Dielectric fuses allow current
 flow even when burned out

 Residual ozone meter readings
 O3 contact tank are unstable

 decompression blowers at Oa
 contact tank  malfunction
Size standby electrical generator to operate sufficient
number of Oa generators.


Install Oa resistant piping (stainless steel); use welded
joints, not threaded joints.

Completely cover and tightly seal the Oa contact tank; do
not use the  Oa contact tank for a filter backwash supply
tank; install additional seal/gasket material.

Do not use ozonated water as a nonpotable water supply
source.

Provide Oa monitors for both the lab and other plant
working areas; provide standby Oa monitor.

Check for leaky air release parts in Oa generator cooling
water system; add corrosion prevention chemicals to the
cooling water; thoroughly clean dielectrics and final rinse
with alcohol.

Check for rust particle  fouling; add rust prevention
chemical to cooling HxO; check for ozone destruction of
diaphragms in pressure sensors.

Check operation of  Oa meters; increase frequency of
cleaning and calibrating meters; check generator opera-
tion and power source.

Check for flow surges to plant resulting from on-off
operation of pumping stations that cause Oa  dosage
control to fluctuate;  dampen flows to WWTP; install
voltage-control transformer.

Increase frequency of cleaning and calibration check to
once per day if required.

Provide noise abatement provisions around compressors
and generators; install acoustical material around
equipment and in equipment rooms.

Install fans so drive belts have minimum exposure to
exhausted air; use more ozone-resistant belts.

Install heavy-duty, screw-type fasteners on side panels.


Ensure pumps, valves, connections, and piping are
constructed of Oa-resistant material.

Provide ventilation in O3 generator room.
 Relocate exhaust vent; extend height of exhaust vent.




 Heat trace and insulate the exhaust vent.


 Pneumatic cylinders must be rebuilt.


 Replace fuses with different type.


 Relocate probe closer to section of contact tank where Oa
 is being injected.

 Check seals and bearings for deterioration as a result of
 Oa attack.

-------
able 5.
          Recommended Remedial Actions for Correcting O&M Problems Observed at UV
          Plants
            Problem
                                                 Remedial Actions
                                Slowly open inlet  valve into UV chamber; position
                                mechanical wiper mechanism in the middle of the
                                chamber for added support.

                                Replace powerstat  with unit that allows finer adjustment-
                                check minimum power requirements for UV lamps;
                                replace powerstat  with shut-off switch that shuts off
                                lamps for close control.

                                Check for faulty LED, burned out LED, or malfunctioning
                                ballast.
                                Before startup of unit, be sure that the wiper has not dried
                                out and become stuck to UV lamps; routinely check wiper
                                for proper alignment.

                                Provide adequate difference in elevation between high-
                                and low-level settings; use time-delayed relays for water
                                level sensors.

                                Routinely check flow meter calibration; be sure that it
                                accurately monitors entire flow range.

                                Provide foam control measures such as water sprays
                                before UV chambe/; thoroughly clean tubes before startup
                                to prevent scum buildup and jamming of lamp wiper.

                                Slightly slope the teflon tubes to ensure that they remain
                                full of water during no-flow periods.
udden flow surge into UV
iamber causes damage to
V lamps

tulty powerstat does not allow
jeration of UV system at low
iwer levels resulting in electrical
lergy wastage

ght-emitting diode (LED)  does
it give true indication of whether
V lamp is actually operational

V lamp wiper mechanism
equentlyjams
'ater level monitoring system in
V chamber malfunctions.
V chamber influent flow meter
 faulty

lam builds up in UV chamber
^logical growth on teflon tubes
'.curs during intermittent flow
inditions
   Randy Junkins is with Roy F. Weston. Inc., West Chester, PA 19380.
   Francis L. Evans, III is the EPA Project Officer (see below).
   The complete report, entitled "Operation and Maintenance of Selected Ozone and
     Ultraviolet Disinfection Systems," (Order No. PB 84-180 124; Cost: $22.00,
     subject to change) will be available only from:
           National Technical Information Service
           5285 Port Royal Road
           Springfield, VA 22161
           Telephone: 703-487-4650
   The EPA Project Officer can be contacted at:
           Municipal Environmental Research Laboratory
           U.S. Environmental Protection Agency
           Cincinnati, OH 45268

-------
United States
Environmental Protection
Agency
Center for Environmental Research
Information
Cincinnati OH 45268
Official Business
Penalty for Private Use $300
                            P O     0 0 •) J 3 d ^
                            '.*  b   civVlK  HrciHECTiUN
                            W t C* I '-I I'<   3  L I ^ K A K Y
                            <^iO   5  -J^rtKauWN  bTKht
                            C h 1 C ^ o u   I L   o 0 o 0 4
                                                                                            U.S. GOVERNMENT PRINTING OFFICE: 1984-759-102/9*

-------