United States
                   Environmental Protection
                   Agency	
Water Engineering
Research Laboratory
Cincinnati OH 45268
                   Research and Development
EPA/600/S2-88/022 May 1988
x°/EPA          Project  Summary
                    Aeration  Equipment  Evaluation:
                    Phase  I  -  Clean Water  Test
                    Results
                    Fred W. Yunt and Tim 0. Hancuff
                      An oxygen transfer performance
                   evaluation  was  conducted  on
                   submerged air aeration systems  at
                   the  Joint Water Pollution  Control
                   Plant of  Los  Angeles  County
                   Sanitation  Districts (LACSO).  The
                   non-steady  state clean water  test
                   procedure  was used.  Systems
                   chosen for evaluation represented
                   various submerged generic  aeration
                   devices including several types  of
                   both  fine  and  coarse   bubble
                   dfffusers. Jet aerators and static
                   aerators were also tested.
                      Seven  manufacturers,  repre-
                   senting  seven  different aeration
                   systems, participated  in the study.
                   An eighth system utilized historically
                   in many LACSD treatment plants and
                   throughout the country was tested to
                   provide a reference point All testing
                   was conducted in the  same  outdoor
                   tank  using identical procedures  in
                   order to standardize test conditions.
                      The  results  of  this  study
                   indicated that, of the systems tested,
                   fine  bubble  diffusion equipment
                   transferred oxygen most efficiently in
                   clean water. Jet aerators transferred
                   oxygen more efficiently than static
                   aerators  and other coarse bubble
                   systems but not as efficiently as fine
                   bubble diffusers.  Because the values
                   of wastewater  correction  factors
                   (alpha and beta) are dependent on
                   the type of aeration device tested,
                   the  relative  performance  of  one
                   aerator to another in wastewater may
                   be different than observed in these
                   clean water tests.
                      This Project  Summary  was
                   developed by EPA's Water Engineering
Research Laboratory, Cincinnati, OH,
to announce  key findings of the
research project that  is  fully
documented  in a  separate  report  of
the same title (see Project Report
ordering information at back).

Introduction
   Analysis of clean water test data for
various submerged  aeration devices  is
the first step toward defining the oxygen
transfer performance of such equipment.
While clean water test results indicate
general trends in an aeration system's
oxygen transfer performance, they do not
necessarily  reflect that system's
performance under  process conditions.
The logical second step, therefore, is an
oxygen transfer evaluation of selected
submerged aeration  equipment in mixed
liquor under field operating conditions.
   A comparison of the data  generated
by the above two types of tests provides
an estimation  of the wastewater  alpha
correction factor.  The  alpha factor
typically is less than unity and results in
lower oxygen  transfer rates in process
waters than in clean (tap) waters. The
value  of alpha varies with wastewater
characteristics, process operating
conditions such as  SRT  and the F/M
loading rate, type of aeration equipment
(bubble size), aeration system  layout,
aeration tank  geometry, the degree  of
prior  treatment received (e.g., the alpha
factor has a higher  value at the effluent
end than the influent end of a plug flow
aeration tank), and  the relative state  of
aerator cleanliness. The last factor refers
primarily  to fine  bubble (fine  pore)
diffusers, which tend to clog or foul with
time  in mixed liquor operation. Because

-------
partially fouled  diffusers  generally
transfer less oxygen than clean diffusers,
the term apparent  alpha  factor  rather
than  alpha factor  is  used  when
comparing  the  mixed liquor  and clean
water oxygen  transfer performance of
diffusers that  are  operating  with  an
indeterminate degree of fouling.
    Since  clean  and process  water
oxygen  transfer performance can vary
widely,  it  was  considered  essential to
undertake  a two-phase  test  program.
The first phase, which is the subject of
this  report,  included  only  clean water
testing.  Several fine and  coarse bubble
submerged aeration systems were tested
in  the  same  tank under the  same
operating  conditions.  Based  on  the
results of these tests,  the three systems
with the highest  oxygen transfer rates
were selected for further oxygen transfer
testing under process water conditions.
    The  clean  water  tests  were
conducted  in the  Districts' Joint Water
Pollution Control  Plant in  Carson,  CA.
The subsequent  process  water (mixed
liquor) tests were carried out in parallel
trains  at  LACSD's Whittier  Narrows
Water  Reclamation Plant  in  El Monte,
CA.  The results  of the process water
testing  will  be  presented in a  follow-on
report.
    The three  major  objectives of  this
project were to:
•  evaluate the  clean  water oxygen
    transfer performance of various
    generic types of submerged aeration
    equipment under  identical testing
    conditions and using identical testing
    methods,
•  demonstrate the effects of  changing
    water  depth  and  operating  power
    levels  on  aeration  equipment
    performance, and
•  evaluate   the  two  most  highly
    regarded  oxygen transfer data
    analysis methods currently in use.

Project Outline
    This  study  was  devised  as  an
evaluation  of  distinct generic  types  of
submerged aeration equipment;  it  was
not  intended  to be  an  evaluation  of
various manufacturers' equipment of the
same  generic  type.  Due  to  the large
variety  of  fixed  orifice coarse bubble
diffusers on the market,  however, more
than  one example  of  this  generic  type
was  tested. The  aeration  equipment
tested is summarized in Table 1.
     System  H,  FMC  Corporation's
coarse  bubble Deflectofuser* (sparger),
was not included  in the  initial  scope.  It
was added at a later date and tested only
at the 4.6-m  (15-ft)  water  depth
because  of  its  widespread use  at  that
depth  both  nationwide  and  in  the
Districts' treatment plants.
    The tests were conducted at water
depths of 3.0 m (10 ft), 4.6 m  (15 ft), 6.1
m (20 ft),  and 7.6 m (25 ft). A range of
nominal power  densities was evaluated
at each depth.  The manufacturers,  with
the exception of  FMC  Corporation for
their Deflectofuser system, were given
the choice to test at one of the following
two ranges of power options:
  Option 1:   13.2, 26.3, and 39.5 nominal
            W/m3  (0.5, 1.0, and  1.5
            nominal hp/1,000 ft3),
  Option 2:   7.9, 13.2, and 26.3 nominal
            W/m3  (0.3, 0.5, and  1.0
            nominal hp/1,000 ft3).
   It was hoped that each  manufacturer
would  select the range that  was most
typical of its equipment's application in
mixed  liquor. All manufacturers tested
chose Option 1  with the exception of the
Norton Company, which selected Option
2. The 3  to  1  range  in power for  both
options was intended to demonstrate the
aeration  equipment's  ability  to  handle
diurnal variations representative of typical
process loading patterns.
   The manufacturers  were responsible
for  designing  the  layout  of their
equipment subject  to the constraints of
this study.  Each  manufacturer  was
allowed,  if  desired,  to  change its
equipment configuration at each depth
tested. It was required, however,  that the
same configuration  be used for  all  tests
at a given depth.

Test  Facility
   An  outdoor,  all-steel, rectangular
aeration tank located at the LACSD  Joint

  •"Mention of trade names or commercial products
  does  not  constitute  endorsement  or
  recommendation for use.
                            Water  Pollution  Control  Plant  with
                            dimensions of 6.1 m x 6.1  m  x 7.6 m
                            sidewater depth (SWD) (20 ft x 20 ft x 25
                            ft) was used for all tests. Prior to the start
                            of this project,  the tank  was  steam
                            cleaned and  all exposed metal surfaces
                            were coated with  coal tar epoxy. Potable
                            water was  used in all  clean  water  tests
                            conducted  in  this  study. Average
                            characteristics of the  supplied water
                            were: total  dissolved solids = 500 mg/L,
                            pH =  8.25,  hardness  = 225  mg/L as
                            CaCOs, and turbidity <0.1 turbidity units.
                               The air  delivery system used for this
                            project consisted  of  a  Roots  Model
                            RAS-60 rotary positive blower driven by
                            a  56-kW   (75-hp)  electric  motor.
                            System air was filtered by an Air Maze
                            DA  dry-type  filter. A 1-m3  (35-ft3)
                            pulsation  dampening  tank was  also
                            included in  the  system between  the
                            blower and  the  airflow  measurement
                            elements. System air rate  was adjusted
                            by bleeding off excess air at the blower.

                            Test  Procedures
                               The basic clean water test procedure
                            employed  was the  non-steady  state
                            method. This method uses sodium sulfite
                            to deoxygenate  the  clean  water  and
                            cobalt chloride to catalyze  the reaction
                            Samples were withdrawn from the  tank
                            and  collected  in  BOD  bottles  and
                            chemically  fixed  for  later  dissolved
                            oxygen (DO) measurement  by  the
                            lodometric (Winkler) method.

                            Airflow Measurements
                               Airflow measurements were made with
                            two  different  primary  flow elements: an
                            orifice  plate  and an Annubar.  Dual flow
                            measurements  were  taken to  ensure
                            greater accuracy. Furthermore, to provide
                            acceptable accuracy over the wide  range
                            of flow  rates encountered,  two different
 Table 1.
 System
Description of Aeration Systems Subjected to Clean Water Testing
        Description
Manufacturer
    A  Fine bubble ceramic dome diffusers applied
       in a total floor coverage configuration
    B  Fine bubble plastic tube diffusers applied in
       a dual aeration configuration (Pearlcomb)

    C  Jet aerators
    D  Static tube aerators
    £  Variable orifice coarse bubble diffusers

    F  Fixed orifice coarse bubble diffusers

    G  Fixed orifice coarse bubble diffusers
    H  Fixed orifice coarse bubble diffusers
       (Deflectofuser) [tests conducted at a 4.6-m
       (15-ft) depth only]
                                 Norton Company

                                 FMC Corporation

                                 Pentech-Houdaille Industries, Inc.
                                 Kenics Corporation
                                 C-E Bauer of Combustion
                                 Engineering, Inc.

                                 Sanitaire - Water Pollution Control
                                 Corporation
                                 Envirex,  Inc.
                                 FMC Corporation

-------
sized air  lines  were  used,  both  with
appropriately  sized  orifice plates and
Annubar equipment.

DO Sample Collection

Sample Locations
  Water samples to be analyzed by the
Winkler method were collected from four
locations  in  the  aeration tank.  Two
vertical  sampling  "stacks"  were
employed, each  with two  sampling
locations.  Submersible sample pumps
were installed in the first  stack at mid-
depth and  at 0.6 m (2.0 ft)  off the bottom
of the  tank;  the  second stack had
submersible  pumps installed  at mid-
depth  and 0.6  m (2.0 ft)  below  the
surface of the tank.  The heights of the
pumps were adjustable for  proper
placement at  the  various  water depths
evaluated.

Sample Collection  Procedure
  Samples  for  DO   analysis  were
pumped through  plastic tubing  by
submersible pumps from the  aeration
tank to the  sampling station where
samples were collected in BOD bottles.
Copper discharge  nozzles for the four
pumped samples  were mounted  on  a
plywood board to enable one operator to
control the four samples simultaneously.
  An  attempt was made  to collect
approximately eight samples  for  the
Winkler analysis between 20% and 80%
saturation, although  additional samples
were taken below  20% and above 80%
saturation. Sample water  was  pumped
continuously  to  purge  the BOD bottles
until the desired time, "t," after which the
sampling device was withdrawn and the
BOD bottles stoppered. If necessary,  1
or 2  sec were allowed  before  stoppering
the  BOD bottles to  allow  any small air
bubbles to rise  to the  surface and
escape. The  overflow  water from  the
BOD  bottles  was  caught in a 208-L
(55-gal) tank  and  continuously  pumped
back to the aeration tank.

Sampling Rates
  The  submersible  pumps  for  the
Winkler samples were  sized  so a BOD
bottle could be filled three to five times in
15 sec (0.06 to 0.10 L/sec =  1.0 tq 1.6
gpm). This was done to ensure adequate
displacement  of the water in the BOD
bottle and  to minimize the  detention time
in the  sample lines (approximately 10
sec).  All pump  rates  and sample  line
lengths were  maintained  equal so  that
the  samples from  the  various locations
would represent the same time "t."
DO Measurements
   The official  DO  measurements  were
made  by  the  Winkler  method on
captured   samples.   The   azide
modification of  the  Winkler  titration
method was  used with  alkali-iodide-
azide  reagent #2 as stated in Standard
Methods. This reagent  was  selected
because it  reportedly  reduced  the
volatility of  iodine and thus provided  a
more  accurate  DO  measurement.
Samples were  set up immediately after
capture and  titrated within 1.5  hr.  The
thiosulfate  used  for the titrations  was
standardized once each day.

Deoxygenation Procedure
   Cobalt chloride was used as a catalyst
in  the  deoxygenation reactions. It  was
added  once at a dosage of 0.1  mg/L as
cobalt  ion  to each batch of test water.
The chemical crystals were added to the
mix tank and allowed to dissolve for at
least 30 min prior to discharging the
solution into the aeration tank. After
cobalt  addition to the  aeration  tank, at
least another 30 min was  allowed prior to
the start of the first test.
   Anhydrous sodium sulfite was used to
deoxygenate the water prior to  the start
of  each test.  The amount of sodium
sulfite  added  was approximately  1.5
times the stoichiometric  requirement for
oxygen removal.  The salt was dissolved
in  approximately 379 L (100 gal) of water
prior to the start of each run. The  brine
addition to  the tank was accomplished
within a 2-min  period. The solution  was
pumped equally  into   the  four  tank
quadrants through a  4-hose  addition
system. Distribution was, therefore, as
even   and  rapid  as  possible.   The
chemical mix tank and  delivery  hoses
were immediately flushed with tap water
to  wash all residual sodium  sulfite into
the aeration tank.
   A decision was made to discard each
water  batch after the  accumulated
sodium sulfite concentration had reached
1,000 mg/L.  At that time, samples were
taken  for  laboratory   analyses to
determine the chemical properties of the
"post-test"  water. Analyses  were  also
conducted prior to using a water batch to
determine  the  "pre-test" condition.
These  measurements  included  pH,
alkalinity,  hardness,   sulfate, total
dissolved solids, cobalt,  iron,  and
manganese.

Aerator Power Determinations
   In addition to power for an air supply,
aeration equipment may  also  require
power  for  a mixer or a  pump. Of the
eight  systems evaluated  in this  study,
only the jet aeration  system  required
pump power in addition to the power for
the air supply.  Power  determination  is
discussed in  detail  in  the  full  Project
Report,  and  equations are given  for
calculating  air  nominal  power,  air
delivered power, air brake power, air wire
power,  pump delivered  power,  pump
brake power,  and pump wire power. All
power requirements used in this report to
calculate aeration efficiencies (kg or Ib QZ
transferred  per kWh  or hp-hr of
electricity consumed, respectively) were
based on wire power.

Analysis Methods
   The transfer of gas into a liquid can be
described  by   the two-film theory
proposed  by  Lewis  and Whitman
(Principles of Gas Adsorption, Ind.  Eng.
Chem.,  16:1215,  1924),  expressed as
follows:
    dC/dt = KLat(C*-C)            (1)
where:
   dC/dt = oxygen  transfer rate per unit
           volume, mg/Uhr
    K|_at = overall  volumetric  mass
           transfer coefficient for test
           conditions, hr1
      C* = DO saturation value, mg/L
      C = DO concentration, mg/L
   This  is the differential form of the
basic equation and states that the oxygen
transfer  rate per unit volume  is directly
proportional to the DO deficit (C* - C).
The oxygen transfer rate,  dC/dt,  is a
function of many variables, including the
type  of aerator,  the  aeration  tank
geometry, the nature of the liquid, and
the liquid temperature. Equation  1  was
originally developed to  describe oxygen
transfer  in  small, shallow containers. It
has  been generalized  to the case  of
large, deep  aeration  basins that are
completely  mixed. If complete mixing is
not achieved, the use of Equation  1  to
define the oxygen transfer capabilities of
an  aeration system  may  lead  to
significant errors.
   All data  analysis  methods share one
common trait; they  define an analytical
procedure to  calculate  oxygen transfer
rate.  This  always  includes  the
fundamental determination  of both  the
volumetric mass transfer coefficient, K|_at,
and the DO saturation value,  C*.
   Eight  data analysis  methods  were
originally planned to be incorporated in
the Project  Report. A computer program
was developed to analyze data using  all
eight methods.  It  was later decided,
however, to include only the analysis
results in the Project Report of the two

-------
most highly regarded methods. The two
methods  the Districts  considered  to be
the most highly regarded were  1) the
log-deficit  model  with  a  measured
equilibrium, hereinafter referred to as the
equilibrium   method,  and  2)  the
transformed integrated form of the basic
equation, hereinafter referred to  as the
exponential method.
   The equilibrium method is described
by the following equation:
    ln(C*-C)  =  KLat(t/3600)
      + In(C'-Cj)                  (2)
where:
    Cj  = initial DO concentration, mg/L
    t   = time in sec
The conversion factor of 3600 is  utilized
to make compatible the units of  K|_at in
hr1and t in sec.
   The  equation  for  the exponential
method is given below:
    C  =  C*  •  (C*-C-^
      exp [-KLat (t/3600)]           (3)
   The  two  methods  of  analysis are
different in the ways the error structure of
the data is handled and the saturation
value  is  obtained. The exponential
method  provides estimates  of  three
parameters, K|_at,  C*, and Cj. It uses the
entire  data  set  to estimate  C*. The
equilibrium  method   involves  a log
transformation  of the data, such that the
latter  measurements of C in a test run
are weighted more heavily than the early
measurements. This method utilizes  a
measured saturation value obtained from
a  few  data  points  at equilibrium
conditions  and,  thus,   provides an
estimation of only  a  single  parameter,
K|_at-  Both methods assume the same
model (Equation 1), and if all the data fit
this model exactly, no differences would
exist between the  respective estimates of
the parameters. In general, however, the
exponential  method  is  the preferred
procedure because it  does  not  require
long aeration times to obtain  an accurate
estimate of C* and  it provides more
accurate estimates of K|_at if the test data
do not precisely fit the basic model. The
exponential method is the basis  of the
recommended  ASCE  Standard  for
Measurement  of  Oxygen Transfer  in
Clean Water  (ASCE,  ISBN  0-87262-
430-7, New York,  NY, July 1984).

Test  Results

Overview
   To  utilize  clean  water  test  data
intelligently,  it is  essential  that  the
limitations of  the  test  be realized. Clean
water  data  alone  cannot be  used  to
predict oxygen transfer performance  in
mixed  liquor. To  relate  clean water
oxygen  transfer  results to anticipated
aerator performance in mixed liquor, two
correction factors are required. The first
factor, alpha  (a), is  the oxygen transfer
coefficient correction factor. The second
factor, beta (P), is the  oxygen saturation
correction factor.  These correction
factors are applied  to the basic aeration
equation as follows:
    dC/dt = a KLat(pC* - C)        (4)
   Only  with  accurate  alpha  and beta
factors,  used  in  conjunction with  clean
water data, can successful prediction of
oxygen transfer performance in activated
sludge  be  achieved. As previously
mentioned, the alpha factor, the ratio of
wastewater K[_a to clean water K|_a, can
vary widely  as  a  function  of several
site-specific  considerations.  For  the
type of equipment tested during this
study,  alpha  factors from 0.35 to  0.95
have been reported. Beta factors of 0.96
to  0.99 are  common for municipal
waste waters.
   Since  aeration   equipment  oxygen
transfer  efficiency is usually  highly
dependent  on  test  medium char-
acteristics, it is  common to  specify
equipment compliance requirements  on
the basis of clean water tests. Because a
clean water test is repeatable, it may  be
used  to  demonstrate  general  trends in
aeration performance with regard  to
airflow  rates, diffuser location, tank
geometry, and other parameters. When
the aerator's  alpha  and beta factors are
known for a particular wastewater, clean
water tests also provide meaningful data
for activated sludge aeration system
design.  Even then, the  process  flow
regime used can have a significant effect
on  alpha.  For example, alpha will tend to
approach  a constant value throughout a
completely mixed aeration tank, whereas
it will increase from inlet  to outlet of a
plug flow tank as the influent wastewater
becomes progressively more treated.

Tabular Data
   The Project Report contains 16 tabular
summaries of the test data, two each  for
the eight aeration  systems tested. One
table for each  system   contains  the
results of the exponential  method of data
analysis,  the  other the  results of  the
equilibrium method  of analysis. Only one
table (Table  2) is presented in this
Summary,  a comparison  of   the
exponential  method  and equilibrium
method analysis results  for the Norton
fine bubble dome diffuser system.
    Information provided in the first four
columns  of  Table 2  identifies  and
characterizes  the  tests.  Results  of  the
exponential  method  of analysis  are
summarized in columns 5 through 9. The
last five columns  summarize the results
of the  equilibrium method  of  analysis.
The K|_a2o  values shown are the overall
volumetric mass transfer coefficients at a
standard water temperature of 20°C,
while  the  C*0  numbers are the  DO
saturation values at 20 °C and a standard
barometric pressure of 1.00 atmosphere.
Standard  oxygen  transfer efficiency
(SOTE),  standard  delivered  aeration
efficiency (SDAE),  and  standard  wire
aeration  efficiency   (SWAE)  data
represent actual  field  determined clean
water  values corrected to standard
conditions  of 20°C, 1  atmosphere,  0
mg/L DO, and 36% relative humidity.
   The data  in Table 2  indicate close
agreement  in test results between  the
two data analysis  methods for the Norton
system. Similar agreement was observed
for the other seven aeration systems. The
average  ratios  of   Ktaarj  (exp.
method)/K|_a2O   (equil.  method)  and
SWAE  (exp. method)/SWAE  (equil.
method)  were  0.990  and  0.995,
respectively, for all  eight  systems
encompassing 100 test runs.  For  the
K|_a2o  rat'°. the maximum value for  any
one run  was  1.10,  while the  minimum
ratio was 0.88. For  the SWAE ratio, the
maximum and minimum run values were
1.06 and 0.93 respectively. The close
agreement  in these  results indicates  that
the test data fit the basic model (Equation
1) extremely well for all eight systems.

Graphical Data
   A total of  15 graphs are presented  in
the Project  Report comparing the oxygen
transfer  performance  of  the  various
aeration  systems.  Four of  these  15
graphs are  presented  in  this  Project
Summary to  illustrate key representative
results of the entire test program. SOTE
and  SWAE are  shown  as functions  of
water depth for the middle nominal power
density in Figures 1 and 2, respectively.
In Figures 3 and 4, SOTE and SWAE are
graphed, respectively,  against delivered
power density for  the 4.6-m  (15-ft)
water  depth. This  water depth  was
selected  because many municipal
treatment plants  around the country use
aeration tanks with a similar depth.
   The  middle nominal  power density
data plotted in Figures 1 and 2 represent
a power level of 26.3 W/m3 (1.0 hp/1,000
ft3) for all aeration equipment  except
Norton. Norton selected a middle power
density of 13.2 W/m3 (0.5 hp/1,000 ft3)
   The data   points at  the four water
depths tested are connected by straight

-------
  •
o
«


o
X]
^.
|
i
«
1

I
}


1

o

1


s

*
i
5
S

s
S



.?
§
i
^

£
>t

e
§
1
°il

d
5-
C
•S.

€.

£

Q
%
5
I;
^

>~
.
Q

Th W ^ »»
CM m u> o
OQ N. QQ CQ
^ ^t1 (Q ^i
C*J CM C^ C"J
SCNl *- O
N C\j ^
^* CM CM co
. ^ GO .
^ oi oi S
 ^ IV to
CM O co oo
CM * 10 *-
00 Is! 00 CO
»• O 10 is.
^ ^» Cft CO
»* _• ~! _;
*O *N PJ PJ

oi <^ to CM
^ CM CM co
3 5 S *


•S S 5: ?
w ^ is.' to
oo cq o> 10
co 10* PJ ^*



CM 10 co co
0 C> C3 0

10 O O UJ
CM
IS. fs IS. IV.
CM CM CM CM
CO ^ ^ ^
CO
PJ
Is.'
«
>-
s
o>
CM
?
o
oi
oi
CO
is!
8
w
N
«
,
O

Is.
00
O)
O
to
CM


IO
o

10

R
to
CM
^t-
R
IO
CM
0)
IS.
00
to
CM
co
IO
10
O)
s:
£
IO
CO
oi
to
«
s
o'

s
is!
^
CO
IO
CM

CM
"

10

g
CM
TJ
8
IS.'
00
CM
o
o
§
UJ
oi
R
N
R
CM
00
$
CM
>~

IV.
0)
O>
to
CM


IO
C)

o
CM
S
i
IO
3
10
K
0)
«
PJ
PJ
IS.
O)
o
to
SI
IO
3
oi
s
%
8
<-

CO
s
„
to

CM
10

"~


CM
g
1
IO
to
IO
00
o>
,
IS.
CO
?
SJ
IS.
IO
10
J.
oi
to
n
fe
<-

<0
^-
^.
CM

CM
to

*~

IO
CM
00
fi
§
25
10
N
IS.
CO
CM
to
co
to
S
06
S
is:
to
CM
$
to
8
i~

IO
00°
10
IV


o
IO
o

IO
CM
§
1
10
00
00
o
t
Is.
CM
•*
IO
CM
CM
to
to
00
K
^
UJ
UJ
CO
PJ
1~

£
to
PJ
to



PJ
o


CM
R
^
io
O)
10
IO
IO
o>
CO
IO
en
o
C)
CO
O)
oi
N
UJ
S
00

s
N
O

<0
O)
PJ
CO

CM

PJ
»~

o
>-
00
^
IO
T-
10
IO
00
IS.
o>
co
s
CM
O
't
IO
00
to
UJ
00
§
B

^
?
1*.

OD
U>
O
10
IS.

o
co
0

o
CM
R
to
10
                                                                        fcq
                                                                        43
                                                                        3 .   
-------
lines in  Figures 1 and 2 for five of the
seven  systems  represented.  For  the
Kenics and Sanitaire Systems, however,
discontinuous lines are shown. It was felt
that equipment configuration changes at
the different depths  strongly  influenced
the results of  these  two  systems;
                              consequently, only points for  the  same
                              configuration layout are connected for
                              Kenics and Sanitaire.
                                 It  is  apparent  in  Figure  1   that
                              increases in  water depth  produced
                              increases in SOTE for each manufacturer
                              configuration tested.  The three  highest
  3?

  fc
  o
     50
     40
     30
     20
     10
      0
• Norton
• Kenics
* Pentech
* FMC (Pearlcomb)
o Sanitaire
o Bauer
& Envirex
                                                   NOTE:
                                                     7  ft = 0.305 m
                                                           20
        0           5            10           15

                                  Water Depth (ft)

 Figure 1.    Comparative plot of SOTE vs. water depth at middle power density tested.
                                                                        25
     10
          • Norton
          • Kenics
          * Pentech
          * FMC (Pearlcomb)
          o Sanitaire
          o Bauer
          A Envirex
                                t	
            NOTES:

             7 n = 0.305 m
             7 Ib/wire hp-hr = 0.608 kg/kWh
           	I	1	
                                10           15

                                  Water Depth Iff)
                                                          20
                                                                      25
 Figure 2.    Comparative plot of SWAE vs. water depth at middle power density tested.
curves represent the ceramic dome and
plastic tube fine bubble diffusers and the
jet aerators.  The coarse bubble aeration
equipment tested is  represented by the
lower curves. The variable orifice coarse
bubble diffuser SOTE curve  is at the
bottom of the  coarse  bubble diffuser
band.
   The data  in Figure 2 indicate that the
effects of  increasing  water depth on
SWAE depend on  the  generic type  of
aeration equipment tested. While the fine
bubble diffusers appear to have  been
relatively unaffected by changes in  water
depth, SWAE improved with increasing
water depth  for  the  coarse bubble
diffusers, static aerators, and jet aerators.
The two highest curves represent the two
fine bubble diffuser systems, while the jet
aerators,  static tube aerators, and coarse
bubble diffusers   generally  grouped
together in the lower band  of curves. The
variable orifice diffuser results again were
the lowest.
   The jet  aeration system's SWAE
values  are  lower   in  relation  to the
SWAE's  of  the  coarse bubble aeration
systems  than would be expected  based
on the comparative iSOTE values  of the
two  types  of equipment.  This is   most
likely due  to the  need for two   prime
movers (blower and pump) to operate the
jet aerators  versus  only one (blower) to
operate  any of  the  other  systems
evaluated.
   As seen  in  Figure 3, the aeration
equipment  producing  fine bubbles  -
Norton, FMC Pearlcomb,  and  Pentech -
exhibited   peak   oxygen  transfer
efficiencies  at the lowest delivered  power
density  for the  4.6-m  (15-ft)   water
depth. Equipment that  produces  coarse
bubbles  generally showed  the opposite
trend, with  peak valves occurring  at the
greatest  delivered  power density. The
curves for  most of the equipment are
relatively  straight with  the  exception of
the  jet aeration system.  The order in
SOTE values, from  highest to lowest, is
as  follows: Norton,  Pentech,   FMC
 Pearlcomb,  and Kenics, followed   by the
other coarse bubble systems clustered
closely  together.  Similar trends and
orders were observed at  the other water
depths studied, with the  exception that
the  Kenics  static tube aerator SOTE  fell
 within rather than  above the coarse
 bubble curve band.
   Five of the systems demonstrated little
 variation in SWAE  for the 4.6-m  (15-ft)
 water depth over the  range of delivered
 power densities evaluated (Figure 4). The
 systems that  did exhibit significant
 variation over this range  - Norton, FMC
 Pearlcomb, and  Pentech - all generate

-------
  /iall  bubbles.  Both Norton  and FMC
produced their peak SWAE values at the
lowest delivered power density, while for

      40 r
      30
  SS
  s
      20
      10
                                    Pentech, the peak SWAE occurred at the
                                    middle  delivered power  density. From
                                    highest to lowest, the order in SWAE


                                                  • Norton
                                                  • Kenics
                                                  A Pentech
                                                  + FMC (Pearlcomb)
                                                  O Sanitaire
                                                  0 Bauer
                                                  A Envirex
                                                  0 FMC (Deflectofuser)
                                           NOTE:
                                           / hp/1.000 ft3 - 0.026 kW/m3
        0             0.5             1.0            1.5            2.0

                   Delivered Power Density (hp/1000 ft3)

 figure 3.    Comparative plot of SOT£ vs. delivered power density at J5-ft water depth.
  ki
10


 9


 8


 7


 6


 5





 3


 2


 1
                                                  • Norton
                                                  • Kenics
                                                  A Pentech
                                                  + FMC (Pearlcomb)
                                                  O Sanitaire
                                                  O Bauer
                                                  A Envirex
                                                  0 FMC (Deflectofuser)
                       O—
                             NOTES:

                             1 hp/1.000 ft3 = 0.026 kW/m3
                             1 Ib/wire hp-hr = 0.068 kg/kWh
                      0.5             1.0            1.5

                       Delivered Power Density (hp/'WOO ft3)
                                                             2.0
Figure 4.    Comparative plot of SWAE vs. delivered power density at 15-ft water depth.
values  is  Norton;  FMC  Pearlcomb;
Kenics;  Pentech;  FMC  Deflectorfuser,
Envirex, and Sanitaire grouped together;
and  Bauer.  The impact of two  prime
movers  on the energy  consumption of
the jet aeration system  in relation to its
relative high SOTE  values is again clearly
evident. The Norton and FMC Pearlcomb
systems also generated  the  highest
SWAE values at the other depths tested.


Conclusions
   This  clean  water  study provided
considerable insight into oxygen transfer
performance characteristics of various
submerged  aeration  devices.  The
following conclusions were reached:
•  For a given water depth and delivered
   power density, the SWAE's of the fine
   bubble  dome diffusers (Norton) in a
   total  floor coverage mode  were
   substantially better than  those of any
   other system tested.
•  For a given water depth and delivered
   power density, the SWAE's of the fine
   bubble  tube   diffusers  (FMC
   Pearlcomb) in a dual aeration mode
   were substantially better than those of
   either the jet aerators (Pentech) or  the
   various  coarse bubble  devices
   (Kenics,  Sanitaire,  Envirex, FMC
   Deflectofuser, and Bauer).
•  For a given water depth and delivered
   power density, the SWAE's of the jet
   aerators were usually better than those
   of the various coarse bubble diffusers
   (with  the exception of the Sanitaire
   fixed orifice coarse bubble diffusers in
   a total floor coverage mode).
•  For a given water depth, delivered
   power  density,  and  with  similar
   configurations,  the SWAE's  of   the
   various coarse bubble diffusers  were
   similar.
•  For a given configuration and water
   depth, SWAE decreased significantly
   with  increasing delivered  power
   density  for  the fine bubble  tube
   diffusers,  reached a  mid-point
   maximum  value  for the jet aerators,
   and exhibited very little change for the
   coarse bubble diffusers.
•  For  a  given  configuration   and
   delivered power density, the SWAE
   values  of  the fine  bubble diffusers
   were relatively  unaffected   by
   increases in  water depth and usually
   increased  significantly for the other
   aeration devices with the exception of
   the static tube  aerators  at the upper
   water depths.
•  For a given water depth and delivered
   power density, the SOTE's of the fine
   bubble dome diffusers in a total floor

-------
 coverage  mode  were  substantially
 better than those of any other system
 tested.
 For a given water depth and delivered
 power density, the SOTE's of the fine
 bubble  tube  diffusers in  a dual
 aeration mode  and the jet  aerators
 were similar  and  significantly better
 than those of the various  coarse
 bubble diffusers.
 For a given water depth and delivered
 power  density,  the SOTE's  of  the
 various  coarse  bubble  diffusers were
 very similar when installed in similar
 configurations.
 For a given configuration "and water
 depth,  SOTE decreased significantly
 for the  fine bubble diffusers and jet
 aerators   with  increasing  delivered
            power density  and usually increased
            slightly for the  various coarse bubble
            diffusers (with  the exception of the
            static tube aerators, where SOTE was
            not significantly affected by  changes
            in delivered power density).
            For  a given   configuration   and
            delivered  power density, SOTE
            increased substantially with increasing
            water depth for all systems tested.
            The use  of a  total  floor coverage
            configuration with the Sanitaire  fixed
            orifice coarse  bubble  diffusers
            appeared to improve the performance
            of this system significantly.
            With  the  exception  of the  Sanitaire
            system,  the  changes  in  aerator
            configuration  selected   by   the
            manufacturers   at  different   water
  Fred W. Yunt and Tim O. Hancuff are with the County Sanitation Districts of Los
        Angeles  County, Los Angeles, CA 90607.
  Richard C. Brenner is the EPA Project Officer (see below).
  The complete report, entitled "Aeration Equipment Evaluation:  Phase I - Clean
        Water Test Results,"  (Order No. PB  88-180  351/AS; Cost: $25.95,
        subject to change) will be available only from:
            National Technical Information Service
            5285 Port Royal Road
            Springfield, VA22161
            Telephone:  703-487-4650
  The EPA Project  Officer can be contacted at:
            Water  Engineering Research Laboratory
            U.S. Environmental Protection Agency
            Cincinnati, OH 45268
  depths  did  not appear  to  result in
  significant changes in oxygen transfer
  performance.
• The  exponential  and  equilibrium
  methods of clean  water data analysis
  provided nearly identical  results under
  the conditions of this study.  Based on
  100 test analyses, the average ratio of
  the  SWAE  obtained with  the
  exponential  method  to  the  SWAE
  obtained with the  equilibrium method
  was 0.995, with a standard deviation in
  the ratio of 0.0169.
  The  full  report  was  submitted in
fulfillment of  Contract  No. 14-12-150
by the County Sanitation Districts of Los
Angeles  County  under  the  partial
sponsorship  of the  U.S.  Environmental
Protection Agency.
United States
Environmental Protection
Agency
Center for Environmental Research
Information
Cincinnati OH 45268
              BULK RATE
        POSTAGE & FEES PAID
                  EPA
           PERMIT No. G-35
Official Business
Penalty for Private Use $300

EPA/600/S2-88/022
                                                                         
-------