United States
                    Environmental Protection
                    Agency
Risk Reduction
Engineering Laboratory
Cincinnati OH 45268
                    Research and Development
 EPA/600/S2-88/067  Jan. 1990
<>EPA          Project  Summary

                    Field and  Laboratory
                    Testing  of  a  Compacted
                    Soil  Liner
                   Bill R. Elshury, Gregory A. Sraders, David C. Anderson, James A. Rehage,
                   Joseph O. Sai, and David E. Daniel
                     This project was initiated to provide
                   information on  the construction
                   criteria that control the performance
                   of compacted  soil liners. The infor-
                   mation generated by this study is
                   intended to  be used in regulating,
                   designing, and  constructing soil
                   liners  to meet  the  mandated
                   maximum  hydraulic conductivity of 1
                   x 10-7 cm per sec.
                     The construction criteria that have
                   the  greatest impact on soil liner
                   performance were identified. A field
                   liner was designed and constructed.
                   After construction,  the hydraulic
                   conductivity of  the  liner  was
                   measured  in the field using four 25-
                   sq-ft (2.3-sq-m) sealed infiltrometers
                   set in the liner surface and a  256-sq-ft
                   (23.8-sq-m) lysimeter set in  a gravel
                   underdrain. Dye was introduced into
                   one of the  infiltrometers and  a
                   borehole, and the  adjacent liner was
                   dissected  to expose the features of
                   the liner that  control  its hydraulic
                   conductivity.
                     An extensive program of laboratory
                   testing  of compacted  specimens,
                   prepared from the same soil as the
                   liner, was completed. Test specimens
                   were prepared using impact  compac-
                   tion, kneading compaction, and static
                   compaction,  with  two  levels  of
                   compactive effort  for each  time  of
                   compaction.  Laboratory tests were
                   also performed on samples of the
                   field liner using several techniques.
                     This Project  Summary was devel-
                   oped by EPA's Riske  Reduction Engi-
                   neering  Laboratory, Cincinnati, OH, to
announce key findings of the research
project that is fully documented in a
separate report of the same title (see
Project Report ordering information at
back).

Introduction
  In response to the widespread use of
low-permeability compacted soil liners for
hazardous  waste facilities and  the
scarcity of  performance data  on  such
liners, the U.S. Environmental Protection
Agency (EPA) initiated this project to
develop a better understanding of the
construction  criteria that  affect  the
hydraulic conductivity of compacted soil
liners.
  The principal purposes of  this project
were to:

• identify the construction  criteria  that
  control the  hydraulic conductivity of
  compacted soil liners,

• measure the hydraulic conductivity of a
  field liner constructed with full-sized
  construction equipment, and

• determine the applicability of labora-
  tory tests to in-the-field performance.

  The research  program  began by
identifying the construction criteria  that
are  most influential in  determining the
hydraulic conductivity of compacted soil
liners (Phase I). Based on the findings of
the  initial  efforts,  a program  of
construction and field testing of a series
of small, 2-ft-thick (61-cm-thick)  test
liners, which  were to be  constructed

-------
using a variety of compaction equipment
and  various soil  moisture contents, was
planned (Phase II). A "trial pad" was buiit
with  full-sized construction  equipment
using two  compaction  techniques.  The
hydraulic conductivity of that liner  was
measured with both  field and laboratory
techniques. Laboratory  hydraulic  con-
ductivity  tests   were  conducted  on
samples of soil  used  to  construct the
liner. Dye was introduced into the liner at
two locations,  and morphological  exam-
inations  were  made  to  study  the
mechanisms of   seepage  through the
liner.
  After the trail pad  was completed, the
scope of the project was reduced and the
trial  pad,  which  was  intended  to be
mostly for technique verification, became
the only field liner constructed. The trail
nature of the liner led  to some choices
during design and construction that would
have been  different had the other  liners
not been planned.


Field Liner
  In  general terms,  the  field  liner  con-
sisted of two 6-in. lifts of clay compacted
over  an underdrain of clean  coarse
gravel, with a fabricated wall to impound
1 ft  (30 cm) of water. The ponded  area
was about 32 ft (9.8 m) by 37 ft (11.3 m)
in plan dimensions.
  The  liner was  constructed  of  highly
plastic clay (CH), which had an average
liquid limit of  56, an average  plasticity
index of 41, 82 percent passing the No.
200  sieve, and 4 percent  calcium
carbonate.  The clay fraction  of the soil
(about 42 percent finer  than  2 pm) was
predominantly smectite.
  The liner  was  constructed  in  two
portions with a padfoot  roller that  could
be operated either in a  static or vibratory
mode. One of the  two sections  of the
liner was  constructed with 8  passes  of
the roller in  the  static  mode, and the
other was compacted by 3 to 4 passes of
the roller in the vibratory mode. The roller
had  a single  drum  with 104 pads that
were 3 in. (76  mm)  high and had an end
area of  21  sq in. (135 sq cm). The roller
weighed about 15,950 Ib (7240  kg); it
could deliver a vibratory  force of 26,500
Ib (118 kN) at a frequency of 30.8 Hz and
an amplitude of 0.040 in. (1.0 mm).
  Construction testing of the static  sec-
tion  (7 tests) gave  an  average moisture
content of  15.7 percent with  a standard
deviation of 0.8 percent and  an average
dry density of 110.4 Ib  per cu ft (17.34
kN per cu m) with a standard deviation of
2.7 Ib per  cu ft  (0.42 kN  per cu m). All
tests  met  the  planned  95  percent  of
maximum standard  Proctor dry density.
Maximum standard  Proctor  dry  density
was 108 Ib per cu ft (17.0 kN per cu m) at
17  percent moisture,  and  maximum
modified  Proctor dry density was  123 Ib
per cu ft (19.3 kN per cu m) at 12 percent
moisture.
  Construction testing  of  the  vibratory-
compacted section  (30 tests) gave an
average moisture content of 16.4 percent
with a standard  deviation of 1.3 percent
and an average  dry  density of 108.9 Ib
per cu ft (17.11 kN per  cu  m)  with a
standard  deviation of 6.3 Ib per cu ft (0.99
kN per cu m). Five of the  tests failed to
meet the planned  95   percent  of
maximum standard Proctor dry density.
  The pond was filled  with water  to a
depth of  1 ft (30 cm) for 22 days,  during
which time several sets of measurements
of hydraulic conductivity were taken with
the  lysimeter  and the infiltrometers.  Data
from the  observations are given in  Figure
1. The average hydraulic conductivity of
the  portion of the  liner compacted  with
the roller in the static mode was 3 x 10-5
cm  per  sec,  and  the  average for  the
portion compacted with vibration was 1 x
10-4cm per sec.
  After the pond was drained, methylene
blue dye was introduced into one of the
infiltrometers and a borehole in the liner.
The  adjacent  liner was later  dissected.
The dye penetrated  over  80 percent of
the thickness  of  the liner in thin, isolated
channels that  were separated by intact
clods of clay with no dye staining.
  Samples of the liner were taken  before
pondinq  using 3-in.- and  6-in.-diameter
(76-mm-  and  152-mm-) thin-walled  tube
samplers.  Two hand  trimmed  block
samples  were taken  after  the  pond was
drained.

Laboratory Hydraulic
Conductivity Tests
  Samples of  the soil used for the  liner
were  compacted using 7 different pro-
cedures as listed in Table  1. The soil for
one series  of tests was prepared  by air
drying  and passing  it  through a  No. 4
sieve. The other samples were molded
with soil  that  had not been predried and
that had a maximum  clod size  of 0.75 in.
(19 mm). Four  compaction curves for
soils compacted with impact compaction
are given in Figure 2.
  The compacted specimens were  sub-
jected to laboratory  hydraulic conduc-
tivity tests using  principally  fixed-wall
permeameters. The results of these tests
are presented in Figure 3, which  shows
the influence of moisture  content on
hydraulic conductivity.  The  influence of
soil dry  density  is shown on  Figure
The values  from  the  field  hydrau
conductivity  tests  are  shown  in  bo
figures  for  comparison.  Laborato
hydraulic  conductivity tests were al
conducted on samples  of the liner,
given in Table 2.


Conclusions
  The factors  that  are  believed
influence  the  hydraulic conductivity
compacted soil  liners were divided in
five  groups:  (1) soil type,  (2)  bas
compaction  objectives,  (3)  essenti
choices that  are  necessary to  meet tl
basic objectives, (4) supporting elemen
that are included in or subsidiary  to tl
essential  choices,  and  (5) other co
siderations.
  The "basic objectives" that  must  I
met  for  a compacted liner to have
hydraulic conductivity of 1 x 10-7 cm p
sec or  less  are: (1)  destruction  of si
clods and (2) bonding  between lifts.
  The "essential choices" to be made
achieve the "basic objectives" are (1) tl
moisture content of the soil, (2) the tyi
and weight of the roller,  (3) the  thickne
of each lift,  (4) the size  of clods  befo
compaction,  and  (5) the number
passes by the roller.  Soil moisture co
tent  is  considered  the  most  importa
essential choice. The soil  must be w
(and therefore soft) enough for  the roll
to thoroughly remold both the new lift ar
any loose soil at the top of the underlyir
lift. The soil for the field  liner constructs
in this study was too dry (and  thereto
too strong) for the relatively light  roll
used to construct the liner.
  The "supporting elements" of densi
and degree of saturation are important
achieving low hydraulic  conductivity ar
are  useful   indicators   in  controllir
compaction in the field. But, if the  "bas
objectives" are not met, both factors ha>
little meaning.
  Examinations  of the dye-stained ffc
paths in the field liner  clearly showed th
the seepage was predominantly throuc
macrovoids between soil clods and alor
the interlift  boundary, not  through tt
finer pores between the  soil particles
the clods.  The observations do n
support the flocculated/dispersed  mec
anism that is frequently  used to  expla
flow through compacted soils.
  Both  the  sealed  double  ring infiltr
meters and  the underdrain  lysimet
worked well  and gave results  that we
consistent with each other.
  The laboratory hydraulic conductivi
tests  on  laboratory  compacted  spec
mens  were  poor specific  indicators

-------
      10'
   O
   CM
   •s  10-
   13
   I
   u

   I
                                                             Infiltrometer No. 1
Record
Section
Infiltrometer No. 3


Infiltrometer No. 2'

Infiltrometer No. 4
                                10
                                                      20
                                                                            30
                                       Time (days)
 Figure 1.    Field hydraulic conductivity values measured with the record section and
             infiltrometers.
Table 1.  Summary  of  Laboratory  Hydraulic  Conductivity Testing Program for Laboratory-
         Compacted Soils
Type Of
Permeameter
Flexible Wall
Fixed Wall
Fixed Wall
Fixed Wall
Fixed Wall
Fixed Wall
Fixed Wall
Fixed Wall
Method of
Compaction
Impact
Impact
Impact
Impact
Kneading
Kneading
Static
Static
Compactive
Effort
Std. Proctor
Std. Proctor
Std. Proctor
Mod. Proctor
Low
High
Low
High
Maximum
Size of Clods'
3/4 in.
314 in.
No. 4 Sieve
3/4 in.
3/4 in.
3/4 in.
314 in.
3/4 in.
Number of
Tests
4
5
4
5
4
4
4
4
'314 in. =  19 mm; No. 4 Sieve = 4.8 mm
field performance. Matching both density
and moisture content, the laboratory tests
underpredict field hydraulic conductivity
by about 100,000 times.
  No tests  on  laboratory-compacted
specimens predicted the performance of
the  liner based on  correlations with
density  alone; in this  case they under-
predicted the hydraulic conductivity of
the field liner by about 100  to 100,000
times, based on  correlations with density.
It is postulated that laboratory  tests can
suggest a minimum density a compacted
soil  must exceed to  achieve  a  target
hydraulic  conductivity; however, density
tests provide no  information on whether a
given construction  procedure  has pro-
duced or can produce  a liner that  meets
the "basic objectives" that control field
performance.
  With respect to moisture  content alone,
the performance of the laboratory tests
ranged  from poor to good. Test  speci-
mens prepared  from large clods  using
standard  Proctor  (ASTM  D  698)  and
kneading compaction procedures snowed
a strong sensitivity  to  molding moisture
content and  gave hydraulic conductivities
that  came relatively close to  matching
field performance. The other  procedures
underpredicted  field performance  by as
much as 1,000,000 times.
  Laboratory tests on samples taken from
the field liner with 3-in.-diameter (76-mm)
thin-walled  tubes underpredicted the
hydraulic conductivity of the field liner by
a factor of about 20,000 times, because:
(1) the paths followed by seepage in the
field had  lateral dimensions  larger than
the laboratory specimens; (2) taking and
extruding tube  samples  can  densify
unsaturated  soils, which can  close the
voids that  cause high  field  hydraulic
conductivity, and (3) the spacing between
the voids in  the  liner provides opportun-
ities for  them to not be represented in
laboratory specimens.
  Laboratory  tests  on  hand-trimmed
block samples  gave results that under-
predicted the hydraulic conductivity of
the liner by only  2 to 10,000 times, which
is  better than the performance of thin-
walled tube samples.
  The effective porosity of the  field liner
was shown to be much less than the total
porosity; the quantity  of data  collected
was  not  sufficient to quantify  the  differ-
ence.

Recommendations
  Further research  is needed (1) to
assess the performance of various types
of  rollers  in  compacting  soil to achieve
low  hydraulic conductivity and  (2) to

-------
       725
       115
  I
  s
  I
  >•>
  I
105
        95
        85
                 8
                        10
                                12
                                       14
                                               16
                                               18
                                                             20
22
                                                                    24
                                Water Content, %

                 Q  Standard Proctor

                 •f  Modified Proctor

                 X  Standard Proctor,
                    Flexible- Wall Permeameter

                 4k  Standard Proctor,
                    No. 4 Sieve Clod Size

Note: 3/4-in. (19-mm) maximum clod size was used for all compacted specimens except where
      indicated.


Figure 2.    Compaction curves for soils compacted with impact compaction.
develop/assess  laboratory test methods
for  predicting  and  evaluating  the
performance of soil liners.
  The full report was  submitted in ful-
fillment of Contract  No. 68-03-3250 by
McClelland Engineers under the sponsor-
ship of the U.S. Environmental Protection
Agency.

-------
          10-

    !
    o

          io-
          10~
          10-
          10-
                             O Standard Proctor
                             • Modified Proctor
                             X Low-Effort Kneading
                             O High-Effort Kneading
                             m Low-Effort Static
                             •f High-Effort Static
                             A Standard Proctor.
                               No. 4 Sieve Clod Size
                             A Standard Proctor,
                               Flexible-Wall
                               Permeameter
                                                                                                              —O
                                                                            I
                                       10
                                                   12
 14          16

Water Content, %
                                                                                       18
20
22
                           Note: 3/4-in.  (19-mm) maximum clod size and fixed-wall permeameters were used for all
                                 specimens except where indicated.
                                                                                                                           24
Figure 3.     Hydraulic conductivity versus molding water content for all soils compacted in the laboratory, plus field points.

-------
1
/o-3
c Conductivity, cm/sec
o o q
J, A i
W10
| • | i | i | i | i | i
I •*• £ • Field Points
r « m o A
' O /
* O /
r •
r
[
r
i

O Standard Proctor
+ Standard Proctor,
No. 4 Sieve Clod Size
X Modified Proctor
O Low-Effort Kneading
• High-Effort Kneading
-1- Low-Effort Static
A High-Effort Static
A Standard Proctor,
Flexible- Wall
Permeameter
1 • 1
«
% 0*
X
X X
X
1 1 1 1 1 1 I
               70
                                                   90                100               110

                                                             Dry Unit Weight, Ib/cu ft
120
                                                                                                                           130
                              Note: 3/4-in. (19-mm) maximum clod size and fixed-wall permeameters were used for all
                                   specimens except where indicated.
Figure 4.     Hydraulic conductivity versus dry unit weight for all soils compacted in the laboratory, plus field points.

-------
Table 2.  Hydraulic Conductivities Measured on Field-Compacted Soil
Location of
Sample
Lower Lift
Lower Lift
Upper Lift
Upper Lift
Lift Interface"
Lower Lift
Upper Lift
Sample
Number
5
6
1
2
-
-
-
Type of Sampler
Thin-Walled Tube
Thin-Walled Tube
Thin-Walled Tube
Thin-Walled Tube
Thin-Walled Tube
Block
Block
Initial Water
Content (%)
16.1
16.7
15.3
17.5
16.4
25.2
25.2
Initial Dry
Unit Weight
(Ib/cu ft)"
113.2
115.3
113.9
113.2
103.7
87.4
91.1
k (cm/sec)
5.0 x JO-9
3.0 x 70-9
2.0 x 10'9
6.3 x 10'10
1.2 x 10-7
7.5 x 10'5
1.1 X JO'8
 "100.0 Ib/cu ft = 15.71 kN/cu m.
"Test specimen trimmed for the equivalent of horizontal flow.
All specimens from the liner cell compacted with the roller in the vibratory mode.
Bill R.  Elsbury  and Gregory A. Sraders  are  with  McClelland Engineers,  Inc.,
  Houston,  TX 76244;  David C.  Anderson, James A. Rehage, and Joseph A. Sai
  are with K. W. Brown & Associates, College Station, TX 77840; and David E.
  Daniel is with the University of Texas, Austin, TX 78712.
Jonathan G. Herrmann is the EPA Project Officer (see below).
The complete report, entitled "Field and Laboratory  Testing of a Compacted Soil
  Liner," (Order No. PB 89-125 9421 AS; Cost:  $21.95, subject to change) will be
  available only from:
    National Technical Information Service
    5285 Port Royal Road
    Springfield,  VA22161
    Telephone: 703-487-4650
The EPA Project Officer can be contacted at:
    Risk Reduction Engineering Laboratory
    U.S. Environmental Protection Agency
    Cincinnati, OH 45268

-------
United States                 Center for Environmental Research                                  BULK RATE
Environmental Protection        Information                                               POSTAGE & FEES PAIC
Agency                      Cincinnati OH 45268                                                EPA
                                                                                    PERMIT No. G-35

Official Business
Penalty for Private Use $300

EPA/600/S2-88/067
      000085956                _    132
      JON  GSASID
      OSEPA  REGION  V
      230  S  DEARBORN  ST
      CHICAGO              IL 60604

-------