United States
                     Environmental Protection
                     Agency
 Air and Energy Engineering
 Research Laboratory
 Research Triangle Park NC 27711
                     Research and Development
 EPA/600/S7-85/011   May 1985
c/EPA          Project  Summary
                     Porous  Dike  Intake  Evaluation
                     Barry A. Ketschke and Richard C. Toner
                       A small-scale porous dike test facility
                     was constructed and  continuously
                     operated for 2 years under field condi-
                     tions. Two stone dikes of gabion con-
                     struction were tested: one consisted of
                     7.5 cm stones; and the other, 20 cm
                     stones. Approach velocity was set at 3
                     cm/sec. Using a test flume, laboratory
                     studies were also conducted on the
                     avoidance response of fish to a porous
                     dike intake.
                       Flow through a porous dike, induced
                     by a hydraulic head of about 61 cm,
                     depended on the cross-sectional area
                     (tidal height). Throughout the experi-
                     ment, flow resistance changed, depend-
                     ing on the fouling. Increases in  flow
                     resistance resulted in lower flow rates
                     at constant hydraulic head. Flow rates
                     could be increased by backflushing the
                     stone dike. Throughout the experiment,
                     the porous dike showed a steady ac-
                     cumulation of silt and organic matter,
                     but the flow rates tended not to decrease
                     with time.
                       Analysis of field and laboratory data
                     showed that the number of zooplankton
                     is reduced passing through a porous
                     dike by a combination of physical filtra-
                     tion  and cropping.  No zooplankton
                     avoidance was substantiated. Analysis
                     also indicated that the number of pas-
                     sively drifting larval fish  is reduced
                     passing through a porous dike by filtra-
                     tion or cropping. No conclusive field
                     evidence was obtained  to explain if
                     actively  swimming larval  fish avoid
                     passing  through  the  dike; however,
                     limited laboratory results suggest avoid-
                     ance may occur. Results with juvenile
                     and adult fish show that  they avoid
                     passing through a porous dike.
   This Project Summary was developed
 by EPA's Air and Energy Engineering
 Research Laboratory, Research Triangle
 Park. NC, to announce key findings of
 the research project that is fully docu-
 mented in a separate report of the same
 title (see Project Report ordering infor-
 mation at back).

 Introduction
  Several industries, particularly  the
 steam-electric industry, have large re-
 quirements for cooling water. All cooling
 water systems, whether they recirculate
 the water (as in cooling towers) or not (as
 in once-through  cooling systems), must
 have  an  intake  system.  These intake
 systems  direct  water, including  the
 aquatic organisms contained in the water,
 into the industrial facility. The combina-
 tion of screening,  heat, mechanical action
 and, in some cases, chemicals added to
 the cooling water, can result in mortality
 to aquatic organisms.
  The Federal Clean Water Act Amend-
 ments of 1972 ultimately require that all
 cooling water intakes be equipped with
the best technology available to minimize
the environmental  impacts on aquatic
organisms. After the  Clean Water Act
became law, the USEPA and the industrial
 users of cooling water began to examine
and experiment with cooling water intake
designs.
  One method considered feasible was a
 rock (or porous) dike.  Conceptually,  the
 porous dike would be similar to a stone
 breakwater and surround the intake. All
 cooling water would then  flow through
 the rock dike. By selecting a very low
 approach  velocity, about 3 cm/sec (0.1
ft/sec), and relatively small stones,  7.5
 cm (3 in.) to 20 cm (8 in.), it was theorized
that the system could act  as a  physical
 barrier for large mobile aquatic organisms

-------
(e.g., fish) and as a behavioral barrier for
small weak swimming  aquatic  forms
(e.g., larval fish and microscopic animal
plankton).
  For a porous dike system to be con-
sidered a feasible intake, it was necessary
to establish that it was in fact a barrier to
aquatic  organisms and that the system
would maintain porosity and not clog.
  The research covered in this report was
designed to examine these two questions.
Specifically, the research was designed
to examine the ability of a porous dike to
keep zooplankton, larval fish, juvenile fish,
and adult fish out of  industrial cooling
water systems. A second objective was to
examine the hydraulic characteristics and
clogging rates of a porous dike.

Materials and Methods

General Procedures
  All hydraulics, fouling, and field screen-
ing performance testing was conducted
at a small-scale porous dike test facility,
at Brayton Point Station, Somerset MA.
  The porous dike test facility (Figure 1)
was a reinforced concrete and steel
structure 6.4 m wide, 18.3 m long, and
6.1m deep. The chamber was a  concrete
box, open at the top and front and divided
into three cells by wooden timbers. Each
cell was 1.8 m wide. A single axial flow
pump in the back (downstream) end of the
box drew water through the structure. At
the front (upstream) end of the box,
gabions were placed in the first and third
cells. One cell had gabions filled with 7.5
cm stone, and the other had gabions filled
with 20 cm stone. Each gabion was 1.8 m
wide, 0.9 m high, and 0.9  m deep. They
were placed on top of each other to form a
wall approximately 4.3 m high. In the 20
cm test section, three rows of gabions
made a 2.7 m thick section. In the 7.5 cm
test section, two rows made a 1.8 m thick
section. The center cell was sealed and
not used. Flow was regulated  by flow-
control baffles. Approach velocities were
initially set at about 3 cm/sec(0.1 ft/sec).
The test facility went  into full operation
on July 16,1979.

Hydraulic Performance
  Hydraulic characteristics were meas-
ured by recording over the 2  years of
operation the  frictional  losses through
the  stones  or  head  loss (h)  and the
volumetric flow (Q) through the stones.
Additionally,  special  hydraulic studies
were conducted to address the efficiency
of  back-flushing and the relationship
between increased head and volumetric
flow.
r- a
Impoundment 4$^ •
Net 'f.
®
Flow^
20 cm Stones L,
7.5 cm Stones
\xC
\^j)
Flow^
1 Plan
. . ' • .'•••• •••" '. -'' '• •' .. / '*/:
lEC r '

/?

° •<&* '© 'i
**i &y /.sm ^









h
Flow
- Control
Gates

'


":":•
In
.
U-T7
'•;.

,-{v.-.|
/7
]
/Ax/a/ Pump


                         -18.3 m-
         -6.4m-
 K
     °
                *•*.-.
                9 -V*
                    •*
                                ®. ®. © -Biological Sampling
                                           Stations
                                 h-Head Staff
                                 v - Velocity/Flow
                                           6.1 m


                                             ~ Fouling Boxes
                          Section a-a

Figure 1.    Porous dike test facility.

  Head loss was measured by recording
the water level at positions upstream of
the gabions, downstream of the gabions,
downstream of the  flow control baffle,
and downstream of the pump (Figure 1).
Additionally, some measurements of h
were made in the gabion slots.
  Water level was measured with 4.6 m
(15 ft) measuring staffs which were fixed
to the walls of the  test facility. In the
gabion slots, water level was measured
using a float and graduated rod. Head loss
through the stones was calculated as the
difference between the upstream water
level and the downstream water level for
each test station.
  Volumetric flow  was  measured by
recording the velocity of water passing
under the known area of the flow control
baffle gate. Velocity under the flow control
baffle gate was  measured in each test
section  at  six fixed locations using a
portable current meter. The current meter
was fixed to a 6.1 m (20 ft) pole equipped
with a mounting bracket which fit into a
slot on the baffle gate. This setup ensured
that measurements were made  at the
same depth and location on each survey.
  Two backflush studies were conducted—
in May 1981 and in July 1981. In both
studies, the methodology was the same.
                     At time zero, the flow volume and corre-
                     sponding  head loss values were meas-
                     ured throughout a tidal cycle. These flows
                     and heads represented the initial  or
                     baseline values. After initial flows were
                     measured, the upstream face of the  20
                     cm stone section was cleaned using a
                     diver-operated pump. The speed of the
                     gasoline-engine-powered pump was ad-
                     justed to yield a suction which penetrated
                     no more than 5 cm (2 in.) into the dike.
                     After this face cleaning, flow volumes
                     and head readings were taken for com-
                     parison to the initial Q and h readings.
                       This  face cleaning was  designed to
                     determine if the increased flow resistance
                     was due to a surface fouling film. After
                     the flow and head readings were taken,
                     following  the face cleaning, backflushing
                     was initiated. Backflushing was achieved
                     by  turning the axial flow pump off. The
                     facility  was  allowed to backflush  for
                     varying periods, upto216 hours(cumula-
                     tive). After each backflush, the pump was
                     operated briefly, and the h and Q readings
                     recorded.
                       The  relationship between increased
                     head differential and flow volume was
                     examined by augmenting the flow rate of
                     the axial flow pump with three gasoline-
                     engine-powered  pumps. Pumps were

-------
added in sequence to increase the head
differential and the resultant flow meas-
ured.

Fouling Rate
  The fouling rate was measured by the
change in weight and void space of the
gabions. The changes in gabion weight
and  void  space  were  measured  with
fouling boxes, small removable sections
of the gabions. Fouling boxes were 22 cm
x 22 cm x 59 cm stainless steel boxes
open at each end and filled with 7.5 cm or
20  cm  stones. These  boxes were in
drawers between the bottom and next-to-
bottom  gabions  on  the upstream  and
downstream face of each test section at
start-up. Prior to installation, the weight
and displacement volume  of  each  box
was measured and recorded. Every  3
months, one box from the upstream face
of each test section was removed and the
weight and displacement volume meas-
ured and recorded. After each fouling box
was removed, all biofouling was identified
and  measured. All  non-living detrital
material was collected and weighed.

Laboratory Screening
Performance Tests
  Laboratory screening tests for zooplank-
ton, larval fish, and juvenile and adult fish
were  conducted  in  a T-shaped  flume
(Figure 2). Dimensions of the long arm of
the T were 3.0 m x 0.5 m x 0.5  m.  The
short arm measured 2.4 m xO.5 m xO.5 m.
Valves, between a 10 hp (7.46 kW) pump
and the flume, controlled both current
velocity and direction of flow. Velocity
could be maintained between 0.5  and
about 30 cm/sec (0.02 to 1 ft/sec).  The
flume was directly connected  with  fish
holding facilities  and a  mechanical  and
biological filter system which permitted
test animals  to acclimate in the same
water used in flume experiments. Light
level and water temperature were also
controlled.
  Laboratory Zooplankton  Screening
Tests. Zooplankton tests were run in the
flume with valve openings set to yield an
equal volume of water flowing down each
arm toward locations B and C (Figure 2).
Under this arrangement, water  flowed
down the short arm (from location A): at
the  intersection,  half the water  flowed
down the long arm;  and the other half,
down the short arm.
  Live  zooplankton  of  known species
composition and number were  placed in
the  flume  at location  A. Under test
conditions, a small rock dike 51 cm thick
made of 20 cm stones was placed in the
                Removable Gabion
                   A, B, C - Sampling
                          Locations
                   a, b- Flow Readings
Figure 2.   Laboratory test flume.


long arm at the  intersection. Under
control  conditions, the  stones were
removed.
  The zooplankton introduced  into the
short arm at location A were captured
downstream of the intersection in both
the long (C) and short (B) arms. Current
velocity  was maintained at 3 cm/sec.
  All preserved samples were analyzed
by microscope as to type and number of
species  present. All density data were
converted to the ratio of the number
captured over the number introduced
before gabion and after gabion. These
ratios were  used in  a paired  t-test to
determine whether any differences exist
between the control  and experimental
conditions.
  Laboratory Fish Screening Tests. Ex-
periments designed to assess the porous
dike concept were conducted with the T-
shaped  flume (Figure  2). A small rock
dike, 51 cm thick and made of 20 cm
stones, was constructed where the long
arm of the flume joined the short arm. The
rocks were  carefully  packed between
stainless steel racks or gabion so that
channels through which water could flow
unimpeded did not exist along the sides or
bottom of the flume. Rock panels affixed
to the walls alongside the gabion gave the
appearance of a continuous rock wall
along the back of the forward chamber. In
certain experiments, rocks,  similar to
those in the dike, were widely scattered
on the bottom. In others, 10 to 15 mm
gravel was spread in a single layer on the
bottom. Water current was directed from
A to B (Figure 2) across the face of the
rock.  Approximately half the  volume
passed in front of the stone dike, and the
other half passed through the dike.
  To ensure that the behavior of test
animals was not influenced  by an  ob-
server, a viewing screen was constructed
around the face of the short arm.
  Current velocity was generally main-
tained at 2, 3, or 6 cm/sec (0.07, 0.1 or
0.2 ft/sec) measured at 1  m downstream
of the rockdike. Velocities under 3 cm/sec
were measured by timing the movement
of dye or a neutrally buoyant, water-filled
table tennis ball  since both flowmeters
were insensitive to such low velocities.
  Light was generally maintained at 65
lux provided by  4 incandescent  lights
mounted above the small arm  of  the
flume. Two additional incandescent lights
provided about 45 lux above the long arm.
A rheostat was used to reduce light levels;
for 24-hour studies, a timer incorporating
a twilight period was used.

-------
  Since water temperature in the flume
continually increased,  due to friction
between the water and flume surfaces as
well as pump work, temperatures were
maintained within 2.5°C  of  the initial
acclimation temperature  by  exchange
with cooler, ambient seawater or  ex-
change between the flume and a separate
insulated reservoir containing two cooling
units.
  The basic experimental procedure con-
sisted of introducing small fish or larvae
into the short arm of the T at  location A
and recording their behavior for periods
of from 30 minutes  to several  hours.
Before release, each sample of fish was
acclimated in the current for  20-30
minutes in either a screened 8-liter pail or
screened 1 -liter beaker with  removable
bottom.
  An additional study was conducted to
observe the filtering capacity of the stone
in the porous dike test facility. A fouling
box containing 20 cm stone was removed
from the test facility  at Brayton Point,
transferred to the flume, and placed at the
intersection. The leading edge of the  box
was fitted into a wooden panel cut to fit
the exact dimensions of the box mouth so
that all water flowing down the long arm
of the flume passed through the box. A
small  0.33 mm mesh net with cod end
was tied to the back edge of  the box to
catch all material passing through it. Flow
rate through the box was set at 3 cm/sec.
  Samples of preserved  larval winter
flounder and labrid eggs were released at
the face of the box while the flume was
operating. Flow was  maintained  for 7
minutes at which time the flume pump
was shut off, the net removed and washed
down,  and the sample preserved until
counted.


Field Screening
Performance Tests
  All field screening tests for zooplankton
and larval, juvenile, and adult fish were
conducted at the porous dike field test
facility (Figure 1).
  Field Zooplankton  Screening Tests.
Zooplankton field studies were conducted
on 90 days between July 1979 and July
1981.
  Evaluation of the effectiveness of a dike
in reducing zooplankton entrainmentwas
based on comparisons of the  population
density at locations upstream  and down-
stream of, and within the dike. Sequential
sampling was carried out during daylight
at locations A, B, and C for both the 7.5
and 20 cm rock channels (7.5 A, 7.5 B, 7.5
C, 20 A, 20 B, and 20 C—see Figure 1)
eight times each sampling day. Collec-
tions at each pair of locations (7.5 A—20
A, etc.) were made simultaneously using
identical gear for  both  channels. Each
sample was taken  by pumping 500 liters
of water through No. 30 (59 (im) mesh
nets using  gasoline-engine-powered
pumps. To ensure that  all of the water
column was sampled, one-third of each
sample was pumped from the bottom
third of the water column, from mid-
depth, and from the top third of the water
column, and eight samples from each
sampling location  in each channel were
combined into a single composite sample
which represented the zooplankton popu-
lation for that location.  During the first
year, sampling was conducted weekly,
with 48-hour die! sampling once a month.
During the second year, sampling was
reduced to biweekly, with a 24-hour diet
sampling once a month.
  In the  laboratory, each  sample was
reduced in volume to a  concentration of
300-500 organisms/ml, and three 1 ml
aliquots were removed and analyzed as to
type and number of each organism pre-
sent. To facilitate analysis, volumes were
kept under  1,000  ml. If  necessary, sam-
ples were split with a plankton splitter.
  Data were analyzed for density differ-
ences.
  Field Larval Fish Screening Tests.
Ichthyoplankton densities on the upstream
and downstream sides of the porous dike
were sampled between August 1979 and
July 1981 during March, April, May, June,
July and August—when ichthyoplankton
were most abundant.
  Ichthyoplankton samples were taken
with a gas-driven trash pump using 10 cm
intake and discharge hoses and a 0.33 mm
mesh plankton net. To improve the condi-
tion of ichthyoplankton,  the last 2.4 m of
discharge hose was increased to 15 cm
diameter and the net was submerged.
Pumping duration per sample ranged from
15  to 30  minutes  depending on the
abundance  of ichthyoplankton in  the
samples. During each  pumping period,
the intake hose was moved at set intervals
so  that surface, mid-depth, and near-
bottom were sampled equally.
  Pumping volume was determined  by
recording the time necessary to fill a 757-
liter box suspended in the same position
as  the  sampling net.  A tachometer,
accurate to within ±2%, was used with
the pump to ensure operational accuracy
between sampling and calibration.
  In 1979 and  1980,  sampling was
conducted 2 days  per week, 1 day in the
7.5 cm channel, and 1 day in the 20 cm
channel. In July and August 1980, sam-
pling frequency was increased to 3 days
per week to compensate to some extent \
for time lost when the facility was shut
down for repair. In  1981, sampling was
again conducted 2 days per week with 1
(March—mid-June) or 2 (mid-June—July)
night sampling periods, in addition to the
day periods.
  On each sampling day, samples were
taken at locations  A and C (Figure  1).
Generally 4 to 10 sets of samples were
taken each day, depending on pumping
duration. Although the original sampling
design included collecting within the slots
between gabions (B positions in Figure 1),
a problem developed when the weight of
stone caused the gabions to bulge into
the slots. In the 20 cm stone channel, the
slots were so narrow that the 10 cm hose
could not be  lowered  into the water.
Initially, sampling was possible at position
B of the 7.5 channel, but only near high
tide because the hose could not always be
fitted  far enough into the slot to reach
water level. Beginning in May 1980, an
additional intake  hose was obtained for
the B position of the 7.5 cm channel. This
hose was worked into the slot and left in
place so that the samples could be taken
regularly at  that position. Because the
hose could not be raised or lowered in the
slot,  sampling was restricted to one
depth—about 1.2 m above the bottom.
  All  samples were preserved in 10%
Formalin and returned to the laboratory
for microscopic analysis. Fish eggs and
larvae were identified to  the  lowest
distinguishable taxonomic category and
counted.
  Data were analyzed for density differ-
ences.
  FieldFish Screening Tests. Field finfish
experiments were conducted  at  the
porous dike between September 1979
and July 1981, using the impoundment
enclosures shown  in Figure 1. The en-
closures were constructed  at 4.7 mm
nylon mesh including a complete bottom,
but were open where they joined the dike.
Each  enclosure  was 4.3 m high. The
mouth of each enclosure was held open
by a metal frame which fit tightly within
U-shaped slots in front of each channel.
The offshore section of each net was held
in place by a system of haul lines and
anchor poles. The head ropes were fitted
with floats and were pulled tight to keep
them above high water.
  Fish to be tested were collected by
beach seine, otter trawl, lift net, or on the
revolving screens at Brayton Point Power
Station. Typically, the nets were set, a
known number of test fish were released
in each enclosure, and the system was

-------
 left undisturbed for a period of time
 ranging generally from 24 to 72 hours. At
 the end of the test period, the nets were
 hauled, mouth first, and the fish remain-
 ing inside were counted and measured.
  Fish were selected by size such that
 they were too large to escape through the
 enclosure meshes and yet small enough
 to enter the spaces between rocks of the
 dike if they chose to do so. During the
 winter months, tests were run whenever
 fish were available and weather permit-
 ted.
  Since  early in the study, it was not
 possible to  determine whether missing
 fish had escaped or entered the stones.
 Therefore, a method of seining the down-
 stream  section of each channel was
 developed in July and August 1980. All
 fish introducedto the impoundments from
 that point on were  finclipped so they
 could be easily identified if subsequently
 collected in the downstream channels.
  The seine measured 3 m x 3 m, was
 constructed of 4.7 mm delta mesh, and
 was lashed along  the vertical edges to
 two 3 m long wooden poles. The bottom
 edge  of  the seine was weighted with
 chain; the  bottom  of each  pole was
 weighted with lead. To assist in hauling
 the seine over the length of the channel,
 haul  lines were fixed to the top and
 bottom of each pole. To confine fish in the
 channels during seining, 4.7  mm mesh
 screens were constructed to slide down
 in slots fixed to the channel walls in front
 of the openings under the baffle gates.
 Generally, three seine passes were made
 whenever  an  impoundment test was
 conducted.

 Conclusions
  The results of studies of the hydraulic
 characteristics of flow through a rock dike
 demonstrated that a low flow velocity of 3
 cm/sec can be induced and maintained
 by  a  relatively low  hydraulic head  of
 approximately 61 cm. Increasing hydraulic
 head and cross-sectional area result in
 increased volumetric flow through the
 stones.  In tidal water, the  decrease  in
 flow due to  decreasing depth is greater
than would  be predicted based on the
 reduction cross-sectional area, indicating
 higher flow resistance in the lower stone
sections.
  Flow volume induced by  a relatively
constant head varied throughout the
experiment.  Some seasonal trends were
evident with lowest flows occurring dur-
ing  the warmest months. Flow volume
 increased both seasonally and in response
to backflushing. Flow volume  could be
maintained by backflushing.
  The major resistance to flow was in the
 upstream 0.9 m of dike. Organic matter
 and debris continued to accumulate with-
 in the stones through the 2-year experi-
 ment. About 70% of the fouling material
 was detritus,  including organic  debris.
 Variations in flow appeared to  be co-
 related more to seasonal surface fouling,
 particularly hydroids and shelled forms,
 than  to  the accumulation of material
 within the stones. About 5 yd3 (0.382 m3)
 of silt and debris accumulated downsteam
 of the dike over the 2-year test period.
  There was no difference in the hydraulic
 performance between the two stone sizes
 tested (7.5 cm and 20 cm). The fouling
 organisms in the two stone dikes showed
 some differences: the 20 cm stone diking
 had more larger shelled organisms, and
 the 7.5 cm dike had more small attached
 organisms.
  The number of zooplankton per volume
 of water was reduced by passing through
 a porous dike. The amount of reduction
 was less during the colder months. The
 reduction was attributed to physical filtra-
 tion and predation by the fouling com-
 munity. No evidence, either in the field or
 the laboratory, could substantiate a zoo-
 plankton avoidance response.
  The numbers of fish eggs and larvae
 per volume of water were reduced, in
 most cases, passing through the porous
 dike.  The  reduction in the density of
 passively drifting fish eggs was attributed
 to physical filtration and perhaps preda-
 tion by the fouling organisms within the
 stones. The reduction in the number of
 passively drifting larvae such as winter
 f lou nder (Pseudopleuronectes americanus)
 was attributed to physical filtration and
 perhaps cropping. Winter flounder were
 shown to exhibit no directional swimming
 ability or avoidance response in laboratory
 test flume experiments; the reduction in
 density observed in the field was, there-
 fore, attributed to filtration or predation.
 No conclusive evidence was obtained in
 the field  to establish whether or  not
 density differences for actively swimming
 larvae were due to avoidance or filtration/
 predation. Laboratory tests did show that
 some species of larvae  exhibit a direc-
 tional swimming ability and avoidance
 response.
  Results of both laboratory and field
 tests have demonstrated that the porous
 dike is an effective barrier to juvenile and
 adult fish.

 Recommendations
  The role of filtration, predation, and
 avoidance in reducing the density of larval
fish needs to be investigated further. This
investigation could include an evaluation
of the effect of flow path length on filtra-
tion capacity.
  A larger scale test of a porous  dike
intake is  also needed, to address the
specific  hydraulic  design parameter
needed for widespread commercial appli-
cation. These studies could examine
various structural designs that would
capitalize  on  the localized fouling  and
backflushing potential.
                                                                                . S. GOVERNMENT PRINTING OFFICE: 1985/559 111/10851

-------
    B. Ketschkeis with New England Electric System, Westboro, MA;R. Toner is with
      Marine Research, Inc.. Fa/mouth, MA.
    Julian W. Jones is the EPA Project Officer (see below).
    The complete report, entitled "Porous Dike Intake Evaluation," (Order No. PB
      85-185 908/AS; Cost: $14.50,  subject to change) will be available only from:
           National Technical Information Service
           5285 Port Royal Road
           Springfield, VA22161
           Telephone: 703-487-4650
    The EPA Project Officer can be contacted at:
           Air and Energy Engineering Research Laboratory
           U.S.  Environmental Protection Agency
           Research Triangle Park, NC 27711
United States
Environmental Protection
Agency
Center for Environmental Research
Information
Cincinnati OH 45268
Official Business
Penalty for Private Use $300
          OCOC329   PS

          U  S  ENVIR  PROTECTION  AGENCY
          REGION  5 LIBRARY
          230  S  DEARBORN  STREET
          CHICAGO               IL   £0604

-------