Underground Storage Tank Program Grant Guidelines                Secondary Containment
                Draft For Public Comment Only - 5/24/O6
              Grant Guidelines To States
                 For Implementing The
          Secondary Containment Provision
          Of The Energy Policy Act Of 2005
              U.S. Environmental Protection Agency
               Office of Underground Storage Tanks
                       Washington, DC
                      www. epa. gov/oust

                       EPA-510-D-06-001
                          May 2006

-------
Underground Storage Tank Program Grant guidelines                    Secondary Containment
                    Draft For Public Comment Only - 5/24/O6
                               Contents
Overview Of The Secondary Containment Grant Guidelines	1
      Why Is EPA Issuing These Guidelines?	1
      What Is In These Guidelines?	2
      When Do These Guidelines Take Effect?	2

Requirements For Secondary Containment	3
      What Tanks, Piping, And Motor Fuel Dispenser Systems Do These Guidelines
       Apply To?	3
      What Definitions Are Used In These Guidelines?	3
      What Is Tank And Piping Secondary Containment?	5
      Where Is Secondary Containment Required?	7
      What Is The Difference Between Repair And Replace For Underground Tanks,
        Piping, And Motor Fuel Dispenser Systems?	8
      What Are The Requirements For Motor Fuel Dispenser Systems?	9
      How May States Determine If An Underground Storage Tank, Piping, Or Motor
        Fuel Dispenser System Is Within 1,000 Feet Of An Existing Community Water
        System Or Existing Potable Drinking Water Well?	10
      How Will The State Underground Storage Tank Program Ensure That Under-
        Dispenser Containment And Secondary Containment Are Installed When
        Required?	10
      May State Underground Storage Tank Agencies Choose To Implement
        Requirements More Stringent Than Those Described In These Guidelines?	11
      What Enforcement Authority Must States Have For Secondary Containment?	11
      How Will States Demonstrate Compliance With These Guidelines?	11
      How Will EPA Enforce States' Compliance With The Requirements In
       These Guidelines?	12
For More Information About The Secondary Containment Grant
Guidelines	13
      Background About The Energy Policy Act Of 2005	13

-------
Underground Storage Tank Program Grant guidelines                       Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
      Overview Of The Secondary Containment Grant Guidelines
Why Is EPA Issuing These Guidelines?

      The U.S. Environmental Protection Agency (EPA), in consultation with states,
developed these grant guidelines to implement the secondary containment provision in
Section 9003(i)(1) of the Solid Waste Disposal Act (SWDA), enacted by the
Underground Storage Tank Compliance Act, part of the Energy Policy Act of 2005
signed by President Bush on August 8, 2005.

      Section 1530 of the Energy Policy Act amends Section 9003 in Subtitle I of the
Solid Waste Disposal Act to add requirements for additional measures to protect
groundwater from contamination. In order to be In compliance with statutory
requirements applicable to Subtitle  I, state underground storage tank (UST) programs
must, at a minimum, implement either the secondary containment and under-dispenser
containment requirements in these  guidelines or the financial responsibility and installer
certification requirements described in separate guidelines. EPA must require each
state that receives funding under Subtitle I meet, at a minimum, one of the following:

      1. Tank And Piping Secondary Containment - Each new underground storage
      tank, or piping connected to  any such new tank, that is within 1,000 feet of any
      existing community water system or any existing potable drinking water well must
      be secondarily contained and monitored for leaks.  In the case of a replacement
      of an existing underground storage tank or existing piping connected to the
      underground storage tank, the secondary containment and monitoring shall apply
      only to the specific underground storage tank or piping being replaced, not to
      other underground storage tanks and connected pipes comprising such system.
      In addition, each new motor  fuel dispenser system installed within 1,000 feet of
      any existing community water system or any existing potable drinking water well
      must have under-dispenser containment. These requirements do not apply to
      repairs meant to restore an underground storage tank, pipe, or dispenser to
      operating condition.

      Or,

      2. Evidence Of Financial Responsibility And Certification - A person that
      manufactures an underground storage tank or piping for an underground storage
      tank system or installs an underground storage tank system must maintain
      evidence of financial responsibility under Section 9003(d) of Subtitle I in order to
      provide for the costs of corrective actions directly related to releases caused by
      improper manufacture or installation unless the person can demonstrate

-------
Underground Storage Tank Program Grant guidelines                       Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
      themselves to be already covered as an owner or operator of an underground
      storage tank under Section 9003 of Subtitle I.  In addition, installers must be
      certified, or they must certify the installation of underground storage tank systems
      they install. These provisions do not affect or alter the liability of any owner or
      operator of an underground storage tank.  Owners and operators must still
      comply with all technical regulations.  For example, they must comply with the
      requirements to report a release and perform all necessary corrective action and
      to maintain financial responsibility to pay for corrective action and compensate
      third parties.

      EPA's Office of Underground Storage Tanks (OUST) is issuing these grant
guidelines to establish the minimum requirements states must meet in order to comply
with the secondary containment requirements in the Energy Policy Act.

What Is In These Guidelines?

      These guidelines describe the minimum requirements for secondary containment
that a state's underground storage tank program must contain in order for a state to
comply with statutory requirements for Subtitle I.  These guidelines include definitions,
requirements, and examples for states choosing to implement the secondary
containment provision.

When Do These Guidelines Take Effect?

      States must implement either the secondary containment requirements described
in these guidelines or the financial responsibility and installer certification requirements
(described in separate guidelines) by February 8, 2007.

-------
Underground Storage Tank Program Srant guidelines                       Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
               Requirements For Secondary Containment
What Tanks, Piping, And Motor Fuel Dispenser Systems Do These Guidelines
Apply To?

      These guidelines apply to tanks and piping regulated under Subtitle I except
those excluded by regulation at 40 CFR 280.10(b) and those deferred by regulation at
40 CFR 280.10(c).  Tanks used for emergency power generation [deferred from release
detection by 280.10(d)] and piping using a suction system for product delivery must
meet these guidelines. These guidelines also apply to new motor fuel dispenser
systems connected to tanks and piping covered by these guidelines.

What Definitions Are Used In These Guidelines?

      The following are definitions for purposes of these guidelines.

Community Water System (CWS) - A public water system that -
      (A) serves at least 15 service connections used by year-round residents of the
          area served by the system; or
      (B) regularly serves at least 25 year-round residents.
The definition of community water system was taken from the Safe Drinking Water Act,
Section 1401(15). For purposes of these guidelines, the following are included as part
of the community water system for purposes of measuring the 1,000 feet distance:
      •   The wellhead for groundwater and/or intake point(s) for surface water;
      •   Collection, treatment, storage, and distribution facilities that are part of the
          community water system; and
      •   The piping distribution system that delivers the water to the community.

Existing - For purposes of these guidelines, existing means that a tank,  piping, motor
fuel dispensing system, facility, community water system or potable drinking water well
is in place when a new installation or replacement of a tank, piping, or motor fuel
dispensing system begins.

Installation Of A New Motor Fuel Dispenser System - The installation of a new
motor fuel dispenser and the equipment necessary to connect the dispenser to the
underground storage tank system. It does not mean the installation of  a motor fuel
dispenser installed separately from the equipment needed to connect the dispenser to
the underground storage tank system. For purposes of these guidelines, this equipment
may include flexible connectors, risers, or other transitional components that are
beneath the dispenser and connect the  dispenser to the piping.

-------
Underground Storage Tank Program Grant guidelines                      Secondary Containment
                      Draft For Public Comment Only - 5/24/O6

Motor Fuel - Petroleum or a petroleum-based substance that is motor gasoline,
aviation gasoline, No. 1 or No. 2 diesel fuel, or any grade of gasohol, and is typically
used in the operation of a motor engine.

Piping - For purposes of these guidelines, piping is the hollow cylinder or the tubular
conduit constructed of non-earthen materials that routinely contains and conveys
regulated substances from the tank(s) to the dispenser(s) or other end-use equipment.
It does not mean vent, vapor recovery, or fill lines that do not routinely contain regulated
substances.

Potable Drinking Water Well - Any hole (dug, driven,  drilled, or bored) that extends
into the earth until it meets a water-bearing formation (aquifer) consisting solely of
groundwater or groundwater under the direct influence  of surface water that provides
water deemed suitable for people to drink in its ambient state or after treatment as
approved by the state or local authority having jurisdiction over such wells. Such wells
may be either privately or publicly owned and may provide water to a single-family
residence, a group  of residences, or a community. The definition of potable drinking
water well was developed by EPA's Office of Water.

Replace - This term applies to underground storage tanks, piping, and motor fuel
dispenser systems.

      Underground storage tank- Replace means to remove an existing tank and
      install a new tank1.

      Piping - Replace means to remove and put back in an amount of piping
      associated with a single underground storage tank defined by the state to be a
      replacement. States  may determine the amount of piping associated with a
      single tank that triggers replacement by piping length, percent of piping replaced,
      percent of piping replacement cost, or some combination of these.  At a
      minimum, states must consider a piping replacement to have occurred when 100
      percent of the piping  associated with a single underground storage  tank is
      removed and put back in.

      Motor fuel dispenser  systems- Replace means  to remove an existing dispenser
      and the equipment necessary to connect the dispenser to the underground
      storage tank system and install a new dispenser and the equipment necessary to
      connect the dispenser to the underground storage tank system.  For purposes of
      these guidelines, this equipment may include flexible connectors, risers, or other
      transitional components that are beneath the dispenser and connect the
      dispenser to the piping.

Note: EPA is seeking input from commenters on an alternate definition of replace
for piping. Please provide any input you might have on this alternative:
1 A new tank is a tank that meets the new tank standards in 40 CFR 280.20, whether or not the tank was ever used before.

-------
Underground Storage Tank Program 6rant Guidelines                       Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
      With respect to piping, replace means to repair or otherwise remove and put
      back in more than 5 feet of piping associated with a single underground storage
      tank system within a 30-day period.  Justification: Tank and dispenser sumps
      typically contain 5 feet or less of piping that can be fixed without digging or
      breaking concrete. In addition, repairs to piping usually occur on small lengths of
      piping.

Secondarily-Contained - A release detection and prevention system that meets the
requirements of 40 CFR 280.43(g) but shall not include under-dispenser spill
containment or control systems.

Under-Dispenser Containment (UDC) - Containment underneath a dispenser that will
prevent leaks from the dispenser from reaching soil or groundwater. Such containment
must:
      •  Be liquid-tight on its sides, bottom, and at any penetrations;
      •  Be compatible with the substance conveyed by the piping; and
      •  Allow for visual inspection and access to the components in the containment
         system.

Underground Storage Tank (UST) - This term has the same meaning given to it in
Section 9001 of Subtitle I, except that such term does not include tank combinations or
more than a single underground pipe connected to a tank. For purposes of these
guidelines, this term does not include those tanks identified in 40 CFR 280.10 (b) and
280.10 (c) as excluded or deferred underground storage tanks.

What Is Tank And Piping Secondary Containment?

      For purposes of these guidelines, secondary containment means that an
underground storage tank and/or piping have both a release prevention system and a
release detection system (i.e., interstitial monitoring). The release prevention part of
secondary containment is a tank and/or pipe that have an inner and outer barrier.
Between these two barriers is a space for monitoring.  The release detection  part of
secondary containment is a method of monitoring the space between the inner and
outer barriers for a leak or release of regulated substances from the primary wall (called
interstitial monitoring).  Interstitial monitoring must meet the release detection
requirements in 40 CFR 280.43(g).

      Current EPA regulations [see 40 CFR 280.42 (b) (1)] for hazardous substance
tanks and piping require secondary containment systems be designed, constructed, and
installed to:
      •  Contain regulated substances released from the tank system until they are
         detected and removed,
      •  Prevent the release of regulated substances to the environment at any time
         during the operational life of the underground storage tank system, and
      •  Be checked for evidence of a release at least every 30 days.

-------
Underground Storage Tank Program Grant guidelines                       Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
      These requirements should also apply to new tank and piping installations
covered by these guidelines.  Therefore, states must have requirements in place to
ensure that secondarily-contained tanks and piping will contain a release until it is
detected and removed, that tanks and piping will prevent a release to the environment
at any time during the operational life of the underground storage tank system, and that
tanks and piping are checked for evidence of a release at least every 30 days. For
example, one way states may meet this requirement is to require interstitial monitoring
to be used that checks for evidence of a release at least every 30 days and is able to
detect a breach in both barriers (for example, by pressure, vacuum, or liquid-filled
interstitial spaces).

      The Energy Policy Act does not require  dispenser sumps to be included as part
of the secondary containment requirement for piping.  Under-dispenser containment is
required when installing a new motor fuel dispenser system, but the under-dispenser
containment requirement does not trigger the secondary containment requirement for
the existing piping system. However, in cases where piping secondary containment is
required, under-dispenser containment may be necessary for secondary containment of
the piping near the dispenser.

      The following is an example of tanks that meet the release prevention part of the
secondary containment requirement:

      Tanks having secondary containment that meet, at a  minimum, a code of
      practice developed by a nationally-recognized association or independent
      testing laboratory.  Examples of standards include, but are not limited to:
          •  Underwriters Laboratories (UL) Standard 58 (Steel  Underground Tanks for
            Flammable and Combustible Liquids),
          •  UL Standard 1316 (Glass-Fiber-Reinforced Plastic  Underground Storage
            Tanks for Petroleum Products, Alcohols, and Alcohol-Gasoline Mixtures),
            and
          •  Steel Tank Institute Standard F841 (Standard for Dual Wall Underground
            Steel Storage Tanks).

      The following is an example of piping that meets the release prevention part of
the secondary containment requirement:

      Piping having secondary containment that meets, at a minimum, a code of
      practice developed by a nationally-recognized association or independent
      testing laboratory.  Examples of standards include, but are not limited to:
          •  UL Standard 971 (Nonmetallic Underground Piping for Flammable
             Liquids).
      Such  piping may be:
          •  100 percent secondarily contained or
          •  Secondarily-contained piping with single-walled piping ends that
             terminate in tank and dispenser sumps.

-------
Underground Storage Tank Program Brant Guidelines                       Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
      The following are some examples that meet the interstitial monitoring (monitored
at least every 30 days) part of the secondary containment requirement:
          • Systems that place the interstitial space under vacuum or pressure,
          • Liquid-filled interstitial spaces,
          • Monitoring devices between the inner and outer barriers of the tanks and
            piping that can detect a leak or release of product from the primary barrier,
            and
          • Manually monitored interstitial spaces.

      The following are some examples of tank, piping, and release detection systems
that do not meet the secondary containment requirement.
          • Tanks and piping that do not meet a code of practice developed by a
            nationally-recognized association or independent testing laboratory for
            secondary containment.
          • Single-walled piping installed in a chase (a larger diameter pipe which the
            single-walled piping is pulled through) where the chase has not been
            determined (such as by recognition by the manufacturer or the
            implementing agency) to be adequate as secondary containment.
          • Tanks with an internally-fitted liner that are not monitored for release
            detection with an automated device.

Where Is Secondary Containment Required?

      For new underground storage tank installations, secondary containment,
including interstitial monitoring, is required for each storage tank and associated piping
that is within 1,000 feet of any existing community water system or any existing potable
drinking water well. If an existing tank is replaced, the secondary containment and
interstitial monitoring  requirement applies only to the new tank. If existing piping
associated with an underground storage tank is replaced, the secondary containment
and interstitial monitoring requirement applies to all of the piping associated with that
tank, not to existing piping associated with other underground storage tanks. If an
existing tank and associated piping are replaced, the secondary containment and
interstitial monitoring  requirement applies to the new tank and all piping associated with
that tank.  In addition, each new motor fuel dispenser system installed within 1,000 feet
of any existing community water system or any existing potable drinking water well must
have under-dispenser containment.  States are not required to apply the requirements
in these guidelines to repairs meant to restore a tank, piping, or dispenser to operating
condition.

      Special Case #1: If a new motor fuel dispenser system is installed at an existing
underground storage tank facility and new piping is added to the underground storage
tank system to connect the new dispenser to the existing system, then that new piping
must meet the secondary containment requirements (including interstitial  monitoring)
described in these guidelines.  However, the existing piping to which the new piping is

-------
Underground Storage Tank Program Grant guidelines                       Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
connected is not required to meet the secondary containment requirements in these
guidelines.

      Special Case #2 - New underground storage tank facilities:  If a new
underground storage tank facility will be installed that is not within 1,000 feet of any
existing community water system or any existing potable drinking water well and the
owner will install a potable drinking water well within 1,000 feet of the tanks, piping, or
motor fuel dispenser systems as part of the new underground storage tank facility
installation, then secondary containment and under-dispenser containment are required,
regardless of whether the well is installed before or after the tanks, piping, and motor
fuel dispenser systems.

      Although not required by these guidelines, states may want to consider the
following when developing secondary containment and under-dispenser containment
requirements for new and replaced tanks, piping, and motor fuel dispenser systems:
          • Designated source water protection areas,
          • Drinking water sources such as natural springs and surface waters, and
          • Planned locations for new community water systems and new potable
            drinking water wells.

      EPA encourages state underground storage tank programs to work with state
agencies with responsibility for drinking water programs and state well permitting
authorities to protect source water and other sensitive areas.

What Is The Difference Between Repair And Replace For Underground Tanks,
Piping, And Motor Fuel Dispenser Systems?

      This section describes the difference between repair and replace for
underground tanks, piping, and motor fuel dispenser systems described in these
guidelines.  Underground tanks and piping that are replaced and are within 1,000 feet of
any existing community water system or any existing potable drinking water well must
be secondarily contained. Likewise, motor fuel dispenser systems that are replaced
and are within 1,000 feet of any existing community water system or any existing
potable drinking water well must have under-dispenser containment. For purposes of
these guidelines, a repair is any activity that does not meet the definition of replace.
The replace definitions for tanks, piping, and motor fuel dispenser systems are
discussed in the paragraphs below.

      Underground Tanks - A tank is considered to have been replaced when the
entire tank is removed and a new tank is put in the ground.  Replaced tanks that are
within 1,000 feet of an existing community water system or existing potable drinking
water well must be secondarily contained (including interstitial monitoring). Repairing
an existing underground tank where the entire tank is not removed does not require that
the existing tank be replaced with a secondarily-contained tank.

-------
Underground Storage Tank Program Grant Guidelines                      Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
      Piping - These guidelines provide states with flexibility in defining replace for
piping. Replace for piping means to remove and put back in an amount of piping
associated with a single underground storage tank as defined by the state to be a
replacement. States may choose to define replace using length of piping, a percentage
of piping, a percentage of piping replacement cost, or some combination of these.  At a
minimum, states must consider a piping replacement to have occurred when 100
percent of the piping associated with a single underground storage tank is removed and
put back in.  When the replace definition is triggered for existing piping, all the piping
associated with the underground storage tank must be secondarily contained and have
interstitial  monitoring.

      Motor Fuel Dispenser Systems - A motor fuel dispenser system is considered to
have been replaced when an existing dispenser and the equipment necessary to
connect the dispenser to the underground storage tank system are removed and
another dispenser and the equipment necessary to connect the dispenser to the
underground storage tank system are put in its place.  For purposes of these guidelines,
this equipment may include flexible connectors, risers, or other transitional components
that are beneath  the dispenser and connect the dispenser to the piping. Repairs to an
existing dispenser where the entire dispenser and the equipment that connects the
dispenser to the piping are not replaced do not trigger the under-dispenser containment
requirement.

What Are The Requirements For Motor Fuel Dispenser Systems?

      New or replaced motor fuel dispenser systems must have under-dispenser
containment if the new dispenser is located within 1,000 feet of an existing community
water system or existing potable drinking water well. A motor fuel dispenser system is
considered new or replaced  when:

      1.   A dispenser is installed at a location where there previously was no
          dispenser (new underground storage tank facility or new dispenser location
          at an existing underground storage tank facility), or

      2.   An existing dispenser is removed and replaced with another dispenser and
          the equipment used to connect the dispenser to the underground storage
          tank system is replaced.  This equipment may include flexible connectors,
          risers, or other transitional components that are beneath the dispenser and
          connect the dispenser to the piping.

      The following are several examples of when under-dispenser containment is not
required for motor fuel dispenser systems within 1,000 feet of an existing  community
water system or existing potable drinking water well.
      •   An existing dispenser is repaired.
      •   An existing dispenser is replaced with another dispenser and existing
          equipment is used to connect the dispenser to the underground storage tank
          system.

-------
Underground Storage Tank Program Grant Guidelines                       Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
How May States Determine If An Underground Tank, Piping, Or Motor Fuel
Dispenser System Is Within 1,000 Feet Of An Existing Community Water System
Or Existing Potable Drinking Water Well?

      Unless a state underground storage tank program requires secondary
containment for all new installations and replacements, the state must have a system in
place for determining when a tank, piping, or motor fuel dispenser system is within
1,000 feet of an existing community water system or existing potable drinking water
well. There are various options for making this determination.  The following are some
examples for meeting this requirement.

      •  States may determine,  or establish criteria for determining, when new or
         replaced tanks, piping,  or motor fuel dispenser systems are within 1,000 feet.
      •  States may designate another entity to determine whether a motor fuel
         dispenser system, tank, or piping is within 1,000 feet.
      •  States may require that owners or operators show or prove that their motor
         fuel dispenser system, tank, or piping is not within 1,000 feet.  The absence
         of proof means that the tank, piping, or dispenser is considered to be within
         1,000 feet and must meet the additional measures to protect groundwater
         requirement.

      EPA encourages state underground storage tank programs to work with state
agencies with responsibility for drinking water programs and state well permitting
authorities to help determine and ensure that the within 1,000 feet requirement is being
met. In addition, local underground utility locator services may be able to provide
assistance in locating underground water piping for community water systems.

How Will The State Underground Storage Tank Program Ensure That Under-
Dispenser Containment And Secondary Containment Are Installed When
Required?

      To ensure the requirements for secondary containment and under-dispenser
containment are met, state underground storage tank agencies may need to require that
owners or operators notify the state before installing or replacing a tank, piping, or motor
fuel dispenser system. Currently,  EPA requires notification within 30 days of bringing
an underground storage tank system into operation.  EPA does not have a notification
requirement prior to installing an underground storage tank. In addition, EPA currently
has no notification requirement for dispenser installation or replacement.  As a result, for
states that have notification requirements no more stringent than EPA, tanks, piping, or
dispensers requiring secondary containment or under-dispenser containment might be
installed without secondary containment or under-dispenser containment. Unless a
state underground storage tank program requires secondary containment and under-
dispenser containment for all new installations and replacements,  the state must
establish requirements for ensuring secondary containment and under-dispenser
containment are installed where required. The following are examples states may
                                      10

-------
Underground Storage Tank Program Grant Guidelines                       Secondary Containment
                      Draft For Public Comment Only - 5/24/O6
choose to implement to help ensure compliance with the requirements in these
guidelines.
      •   Require pre-notification for owners and operators (for example, some states
          require permitting before new installations may begin).
      •   Require the installer to notify the state before installation, replacement, or
          repair.
      •   Require installer certification where installers must install secondary
          containment systems where appropriate.

       EPA encourages state underground storage tank programs to work with state
agencies that regulate motor fuel dispenser systems to ensure that the requirements in
these guidelines are met.

May State Underground Storage Tank Agencies Choose To Implement
Requirements More Stringent Than Those Described In These Guidelines?

      State underground storage tank agencies may choose to develop more stringent
requirements than described in these guidelines. For example, states may choose to
require secondary containment for all new installations and replacements; if a state
chooses this option,  then issues such as determining the within 1,000 feet proximity and
advance notification  are no longer considerations because secondary containment is
required at all installations and replacements. Likewise, states may choose to develop
more stringent definitions. For example, states may decide that any repair activity
constitutes replacement.

What Enforcement Authority Must States Have For Secondary Containment?

      At a minimum, states must have the same enforcement authorities for violations
of their secondary containment requirements as they have for violations of current
underground storage tank requirements.

How Will States Demonstrate Compliance With These  Guidelines?

      After February 8, 2007, the effective date of the secondary containment
requirements, and before receiving future grant funding, states must provide one of the
following to EPA:

   •  For a state that has met the requirements for secondary containment, the state
      must submit a certification indicating that the state meets the requirements in the
      guidelines.
   •  For a state that has not yet met the requirements for secondary containment, the
      state must provide a document that describes the state's efforts to meet the
      requirements. This document must include:
         -  A description of the state's activities to date to meet the requirements in
            the guidelines;
                                      11

-------
Underground Storage Tank Program Grant guidelines                      Secondary Containment
                      Draft For Public Comment Only - 5/24/O6

         -  A description of the state's planned activities to meet the requirements;
            and
         -  The date by which the state expects to meet the requirements.

How Will EPA Enforce States' Compliance With The Requirements In These
Guidelines?

      As a matter of law, each state that receives funding under Subtitle I, which would
include a Leaking Underground Storage Tank (LUST) Cooperative Agreement, must
comply with the underground storage tank requirements of the Energy Policy Act.  EPA
anticipates State and Tribal Assistance Grants (STAG) funds will be available under the
2007 Appropriations Act for certain purposes authorized by the Energy Policy Act, and
EPA will condition STAG grants with compliance with these guidelines. Absent a
compelling reason to the contrary, EPA expects to address noncompliance with these
STAG grant conditions by  utilizing EPA's grant enforcement authorities under 40 CFR
Part 31.43, as necessary and appropriate.
                                      12

-------
Underground Storage Tank Program Grant guidelines                           Secondary  Containment
                           Draft For Public Comment Only - 5/24/O6
                          For More Information About The
                    Secondary Containment Grant Guidelines

Visit the EPA Office of Underground Storage Tanks' web site at www.epa.gov/oust or call 703-
603-9900.
                       Background About The Energy Policy Act Of 2005


        On August 8, 2005, President Bush signed the Energy Policy Act of 2005.  Title XV, Subtitle B of this
        act (entitled the Underground Storage Tank Compliance Act) contains amendments to Subtitle I of the
        Solid Waste Disposal Act - the original legislation that created the underground storage tank (UST)
        program.  This new law significantly affects federal and state underground storage tank programs, will
        require major changes to the programs, and is aimed at reducing underground storage tank releases
        to our environment

        The underground storage tank provisions of the Energy Policy Act focus on preventing releases.
        Among other things, it expands eligible uses of the Leaking Underground Storage Tank (LUST) Trust
        Fund and includes provisions regarding inspections, operator training, delivery prohibition, secondary
        containment and financial responsibility, and cleanup of releases that contain oxygenated fuel
        additives.

        Some of these provisions require implementation by August 2006, others will require implementation
        in subsequent years. To implement the new law, EPA and states will work closely with tribes, other
        federal agencies, tank owners and operators, and other stakeholders to bring about the mandated
        changes affecting underground storage tank facilities.

        To see the full text of this new legislation and for more information about EPA's work to implement the
        underground storage tank provisions of the law, see: http://www.epa.gov/ous1/fedlaws/nrg05 01 .htm
                                               13

-------