vvEPA
                  United States
                  Environmental Protection
                  Agency
                 Region 5
                 230 South Dearborn Street
                 Chicago, Illinois 60604
                  Municipal Facilities Branch - Technical Support Section
September 1988


 905R88003
Ujtra Violet
Disinfection
Special  Evaluation
Project
        • •••••• • v* » •••••••••*••••••«•*•••»•
        • •••••••••••• •*• «•••••*•••• >v£*^ • • •
        • * • ..••>•••••!.••••••••••••• m^r* • • *

-------
                   Ultraviolet Disinfection -  Region  V  Update
                       Special Evaluation Project  Report

                                 September 1988


A.  Introduction

    The question of toxicity to resident aquatic species  from  chlorine  resi-
    duals, with the resultant need  for  dechlorination systems,  has  fostered
    increased interest in several  alternative  disinfection  systems  among
    communities that currently either chlorinate their  effluent or  are
    constructing entirely new wastewater treatment systems.  One of these
    alternative disinfection systems  is ultraviolet (UV)  disinfection.
    This report will update the 1984  Region V  data base on  UV  disinfection
    of wastewater in order to analyze the effect of recent  changes  in the
    design, operation, and maintenance  of UV disinfection systems.

    The data collected for this report  was assembled  from manufacturer's lit-
    erature, various WPCF articles  on UV disinfection,  USEPA's  design manual
    on municipal wastewater disinfection, specifications  for UV disinfection
    from several plants in Michigan and Ohio,  discussions with  plant operators
    in the Region who work at plants  using UV  disinfection, capital  cost data
    found in planning documents for several  communities in  Indiana  and  Ohio,
    and on-site visits at various  plants using UV  disinfection.

B.  Background

    The earliest operating (1981)  Region V municipal  UV disinfection facil-
    ity is located in Lyons, Wisconsin.  Since 1984,  the  number of  municipal
    wastewater treatment plants (WWTP)  that are either  planning, designing,
    building, or operating UV disinfection systems in Region V has  approxi-
    mately tripled from about 20 to 60  plants  (see Tables 1 &  3).   Michigan
    has experienced the largest increase in plants using  UV disinfection,
    with Wisconsin and Ohio not far behind.  Several  communities in Indiana
    are currently planning to use  UV  disinfection, but  have not yet reached
    the design stage.  Minnesota and  Illinois  have a  handful of plants  that
    employ UV disinfection systems.

C.  System Description

    Disinfection by UV radiation is a physical  process  relying  on the trans-
    ference of electromagnetic energy from a source (lamp)  to  an organism's
    genetic material.  The lethal  effects of this  energy  result in  the  ir-
    radiated cell being unable to  replicate.  The  primary,  and  most widely
    used, source of UV light energy is  the low-pressure mercury arc lamp.
    Approximately 85% of its energy output is  at the wavelength of  253.7
    nanometers (nm), which falls within the optimum wavelength  range of 250
    to 270 nm for germicidal effects.  The lamps are  long,  thin (1.5-2.0 cm)
    tubes similar to fluorescent lamps  but transparent  instead  of opaque.
    The lamps typically come in two lengths  (0.75  and 1.5 m).   The  radiation

-------
    is generated by striking an electric arc through  mercury  vapor.   The
    discharge of energy generated by excitation  of the mercury results  in
    the emission of UV light.

    Currently, there are two basic generic types of reactors  that  are in
    use.  The first, generally called the quartz-tube reactor, is  a  contact
    reactor in which the lamps are submerged in  the wastewater (see  Fig.  1).
    The lamps are sheathed in  quartz jackets that are slightly larger than
    the lamp.  Flow can be either parallel or perpendicular to the lamps.
    The contact reactor configuration may be further  divided  into  either  an
    enclosed vessel system or  an open-channel  system.  These  systems consist
    of, respectively, a lamp battery enclosed in a reactor shell and a  lamp
    battery that is capable of being dipped into a plant's effluent  channel.
    In the second generic type of reactor, called the teflon-tube  reactor,
    the UV lamps are suspended outside a transparent  teflon conduit  carry-
    ing the wastewater to be disinfected.  This  type  of reactor has  only
    this type of parallel flow configuration.

    In addition to the lamp batteries and reactors, a complete UV  system
    must include ballasts for  the lamps.  The ballast is placed in series
    with the lamp to provide a starting voltage  and to maintain constant
    current.  Generally, the ballasts are held either in enclosures  above
    the lamp battery or in separate power panels remote from  the reactor.
    The instrumentation in a UV system generally includes UV  intensity
    monitors and individual lamp monitoring and  operations circuitry, which
    can be included as part of the reactor or the power panel.

    A recent addition to the field of UV disinfection is the  medium  pres-
    sure mercury arc lamp.  This lamp has an energy output over 25 times
    greater than the more commonly used low pressure  lamps and uses  a
    permanent transformer instead of expendable  ballasts to control  current
    and voltage.  Although the cost of the medium pressure lamp is about
    four or five times that of the low pressure  lamp  and the  life  cycle is
    about half of the low pressure lamps, the reduced number  of lamps neces-
    sary for adequate disinfection may make this lamp more cost-effective.
    More data needs to be collected regarding the medium pressure  lamp  in
    municipal applications before definitive statements can be made.  There
    is currently one municipal installation of this type in Region V at
    Lewisburg, Ohio that has been in operation for less than  1 year.

D.  Critical Design Areas

    There are three key areas  that govern the design  and eventual  capabil-
    ity of a UV disinfection system to produce an, effluent that complies
    with permit standards.  The first area relates to the hydraulic  proper-
    ties of the particular reactor that is being used.  The path that an
    organism in the reactor takes will determine whether it will come into
    contact with strong enough UV radiation for  a sufficient  amount  of  time
    to enable the radiation to render that organism sterile (i.e., unable
    to replicate or non-infectious).  Thus, the  reactor must  be designed  so

-------
that the greatest number of organisms come into contact with the strong-
est UV radiation for the longest possible time.  The ideal  hydraulic
design of a UV reactor is one with plug flow and minimal  axial  disper-
sion.  The flow should also be radially (perpendicular to flow path)
turbulent to encourage mixing in the nonuniform intensity field in the
reactor.  Although early reactor designs did not consider the hydraulic
properties necessary for proper disinfection of wastewater, with the
result that many reactors exhibited shortcircuiting problems inhibiting
adequate disinfection, most recent designs and specifications have in-
cluded these design considerations so that short-circuiting is  no longer
a problem.

The second area that should be considered in the design of a UV disinfec-
tion system is the intensity of the UV radiation that ultimately reaches
the target organism.  The intensity will be affected by not only the age
of the lamps and their configuration, but also by the surfaces  and mate-
rial that stands between the UV radiation and the target organisms.  The
minimum bacterial density level that can be achieved by the UV disinfec-
tion process is a function of the suspended solids concentration and is
called the particulate bacterial density.  A reduced UV disinfection
efficiency with increased dose is attributed to the aggregation or occlu-
sion of bacteria in particulate matter.  UV light is unable to  penetrate
this material  and inactivate the bacteria.  This is the reason for the
inability of the UV process to adequately disinfect wastewaters that
contain more than about 30 mg/1 of suspended solids.  Presently, there is
no commercially available detector which can measure the true intensity
in a complex lamp reactor.  This is because only light which is normal to
the surface of the detector, i.e., collimated light, will  be fully mea-
sured.  In a reactor, however, the target organisms are exposed to UV
light in a three dimensional setting, usually from more than one source.

An effective method for estimating delivered dose and system intensity in
a given reactor is the bioassay procedure.  The species selected for the
assay should be one which is easy to culture, identify, harvest, and
which has a consistent and reproducible dose-response.  Bacillus subtil is
spores are the most commonly used species for this assay.   Using a col-
limated light  device, which allows an accurate measurement of the in-
tensity directly with a commercial radiometer, equal portions of a B.
subtil is suspension are exposed to a set intensity for a series of fixed
time intervals, yielding known doses.  The response is plotted  against
the dose, and  this relationship serves as the calibration for the subse-
quent reactor  assays.  The reactor to be tested is set to the desired
flow and operating conditions and the culture is injected into  the in-
fluent.  The effluent is then sampled at set time intervals and assayed
for the known  bacterium.  This is repeated with the lamps  not in opera-
tion.  The log survival rate for each time interval is determined and the
equivalent dose is estimated from the previous dose response calibration
curve.  Plotting dose against time then yields the dose-rate or intensity.
The bioassay procedure is an independent verification of system design

-------
    and, as such, it can be used either to verify  the  appropriateness  and
    validity of a design or to compare the performance of  competing  com-
    mercial units during design and/or bid phases  prior to installation.
                                                            ^
    The third area of concern in the design of UV  disinfection  systems
    is the quantification of the various characteristics of  the wastewater
    that is to be disinfected.  The parameters of  primary  concern  regard-
    ing the wastewater characteristics are the flow rate,  suspended  solids,
    initial coliform density, and the UV absorbance of the wastewater.
    Even though the first two parameters are set by the design  of  the
    plant, and the coliform density and the UV absorbance  of the waste-
    water (commonly referred to as the UV absorbance coefficient)  must be
    measured prior to design, all  wastewater characteristics should  be
    empirically measured for confirmation of actual  values prior to  design
    of a UV disinfection system.  These measurements should  be  collected
    as grab samples during the times corresponding to  peak diurnal flows
    which reflect the maximum bacterial  density levels and maximum loading
    periods for a WWTP.

    The design criteria that are applicable to the design  of a  UV  disinfec-
    tion system at a particular site should be determined  by pi lot-testing
    or in-place performance testing.  Since the composition  of  the waste-
    water is different from site to site, the only way to  ensure that  the
    UV disinfection system will operate properly and enable  the plant  to
    meet permit limits is to do this testing.  Although some recent  specifi-
    cations include testing as a means of setting  the  system design  para-
    meters, this has not been a universal practice.   Since UV disinfection
    of wastewater is still a relatively new technology, there may  be engi-
    neers that are not fully familiar with all  of  the  necessary aspects of
    a properly designed municipal  UV disinfection  system (see Table  4).

    A quick comparison of several  similar communities  in Indiana and Ohio
    (see Table 5) emphasizes this point.  Although more in-depth analysis
    needs to be done, it is interesting to note that in those communities
    with higher effluent limits (CBOD5 = 25, TSS = 25) UV  disinfection was
    the chosen alternative tor disinfection, while in  communities  where the
    effluent limits were more favorable for UV disinfection  (CBOD5 = 10,
    TSS = 10), chlorination/dechlorination was selected.  Although there
    are always site-specific reasons for cost variances, the wide  disparity
    in present worth costs for similar communities further suggests  a  gap
    in knowledge about municipal UV disinfection systems and application of
    that knowledge to design.

E.  Critical Operation and Maintenance Areas

    Important components of a successfully designed UV disinfection  system
    are the operation and maintenance (0 & M) of that  system.   The 0 & M
    of a UV disinfection system is geared primarily to ensure that enough
    UV radiation is transmitted to the organisms to render them sterile.
    Essentially, this means that the lamp, ballasts, and reactor are

-------
functioning at peak efficiency and that all  surfaces between the UV
radiation and the organisms are clean so that maximum radiation can be
transmitted.
                                                        i

Since UV lamps will progressively deteriorate with increasing number
of starts, care must be taken not to have frequent on/off cycles that
rapidly shorten lamp life.  The normally cited lamp life is  about 7500
hours which is approximately equal to 1 year of use.  In the field,
however, replacement of lamps has not always been practiced  according to
recommendations.  Some plants replace lamps  three times per  year (every
2500 hours), while at some plants the lamps  are not replaced until  they
burn out.  While costs per lamp vary from $25 - $100, there  doesn't seem
to be a correlation between cost and replacement frequency.   For more
effective control of power outputs and lamp  usage, voltage dimming, which
avoids the on/off cycling that reduces lamp  life, in conjunction with
the ability to turn portions of the system on and off on the basis  of
time, should be incorporated into the design of a UV disinfection system.
Adjustments can then be made on a diurnal basis to reflect the normal
variation in a plant's flow.  Although some  early designs incorporated
float activated switches, timers, or the ability to control  lamp banks
according to flow, this was not a universal  practice.  It is important
to include some kind of control to prolong lamp life, since  lamp replace-
ment is a major operational cost.

In order to protect the lamps from breakage  and internal clogging,  re-
movable screens should be placed ahead of the unit to prevent debris
from entering the system.  This is especially important for  quartz-tube
reactors where the tubes are in the wastewater flow.  The efficiency ot
a lamp is also affected by the temperature of the lamp wall.  The
optimum wall temperature is between 95 and 122° F.  The reactor design
that is most conducive to control of lamp wall temperature is the non-
contact (i.e., lamps not in wastewater stream) reactor, otherwise known
as the teflon-tube reactor, where it is possible to maintain the lamps
at their optimum wall temperature by controlling the temperature of the
air surrounding the lamps.  In quartz-tube reactors, newer designs  pro-
vide 0-ring spacers that can be slipped over the lamps to prevent
direct contact with the cooler quartz sheath.  Another consideration
for UV lamps is the type of quartz sheath that surrounds the lamp in a
quartz-tube reactor.  Quartz is transparent  to energy at the 185 nm
wavelength.  Energy at this wavelength will  ionize free oxygen to form
ozone, which is an absorber of UV energy at  the germicidal wavelength
of 253.7 nm.  This means that a UV lamp with a fused quartz  sheath  will
not produce the amount of UV energy necessary for proper disinfection.
It is appropriate, therefore, to use lamp sheaths that have  a low
transmittance at the 185 nm wavelength, such"as vycor or other high
transmission glass.  Most current UV lamp designs use such a sheath and
this is not a problem.

It is important to ensure that the ballasts  that are used in a UV dis-
infection system are compatible with the lamps.  Improperly  mated lamps

-------
and ballasts will either not work or will  have much shorter life cycles.
The ballasts should also have a mechanism that forces shutdown in case
of overheating.  The life cycle of ballasts (5-7 years) is greatly
shortened by excessive heat.  It is important, therefore,  to have ade-
quate ventilation for the power panel that normally contains the bal-
lasts.  This has been a problem in many early designs and  the cause of
rapid failure of numerous ballasts.  Since ballast replacement costs
($50-$70) are similar to lamp replacement costs, this can  be a source
of significant unnecessary expenditure.

One of the most common causes of a UV disinfection system's non-perform-
ance is inadequate cleaning frequency.  This refers to both the reactor
itself, as well as the lamp, quartz and teflon surfaces.  Over time,
both the quartz and teflon-tube reactors will  experience fouling of the
lamp and tube surfaces.  In a quartz reactor,  the outside  of the quartz
sheath surrounding the lamps will become befouled.  This is particularly
the case where the wastewater is from primary or secondary effluent, has
a high grease and oil content, or has a high hardness content.  Compounds
of iron, calcium, magnesium and manganese, which are found in hard water,
will precipitate out on the quartz sheath and prevent the  UV light from
penetrating into the wastewater.  Also, an organic film will develop on
the quartz sheaths if low quality wastewater is present, or if the
wastewater has a high grease and oil content.   The teflon-tube reactor
experiences similar reductions in UV transmittance with time.  A film
will settle in the teflon conduit carrying the wastewater, similar to
the film on the quartz sheaths.  In addition,  the UV lamps will become
a place for dust to settle, thereby scattering and reducing the amount of
UV light available for disinfection.

There are several methods available to clean the fouled lamp, quartz
and teflon surfaces:  chemical cleaning, mechanical wipers, ultrasonics,
and high pressure spray wash.  The last three methods are  meant to
augment chemical cleaning, which is the recommended means  of cleaning
for both quartz and teflon-tube reactors.   The most prevalent cleaning
agent in use today is citric acid, however, various other  acid solu-
tions (e.g., muriatic, sulfuric, phosphoric, oxalic) are also used.
These solutions work best on inorganic depositions that are prevalent
in wastewater that has a high hardness content.  Other cleaning agents
such as mild vinegar solutions and sodium hydrosulfite are also ef-
fective.  Sodium hydrosulfite, in particular,  is effective in closed
reactor systems.  In the case of organic fouling from wastewaters with
high grease or oil content, detergents, alone or in combination with
other cleaning agents, are effective in restoring the lamp and reactor
surfaces.  Often, various chemical cleaning agents must be tried in
order to find the appropriate agent for the particular wastewater.  The
frequency of chemical cleaning will vary frorff plant to plant depending
on the characteristics of the wastewater.   The most prevalent method

-------
used to determine if cleaning is necessary is visual  inspection of the
UV reactor.  NPDES violations of coliform levels are  used by many
plant operators as an indication that cleaning is necessary, however,
cleaning should be done before a violation occurs.   Thru experience,
the proper cleaning frequency can be established, however, wastewater
characteristics may experience subtle changes, where  visual  evaluation
and experience may not be enough.  Current designs, therefore,  include
either intensity monitors or radiometers, the latter  of which are used
in conjunction with the UV absorbance measurements  that should  be part
of a plant's regular sampling program for operational  control.

In order to keep the UV disinfection system operating at peak efficency,
properly scheduled maintenance is necessary.  At least once a year, the
total system should be overhauled and all critical  components (lamps,
ballasts, reactor, monitoring systems, etc.) should be checked  to en-
sure that deterioration has not occurred and that all  surfaces  are
clean.  The accessibility to the lamps, quartz sheaths, and Teflon tubes
is critical to the ease of maintenance.  This is more of a consideration
for the enclosed vessel than the open-channel systems, however, both
types should be installed in an area that offers adequate space to per-
form all of the required maintenance tasks.  This is  more of a  problem
in plants where another means of disinfection has been used and a UV
disinfection system is being retrofitted into existing buildings,
chlorine contact tanks, or effluent channels.  A lot  of early retrofit
installations, in order to take advantage of gravity-flow, have been  in
cramped and tight quarters making accessibility and maintenance very
difficult.  Since a lot of future UV disinfection systems are going to
be retrofit installations, design must include a consideration  of ade-
quate space for proper maintenance.

Unlike chlorine, which has a measurable residual than can be used as  an
indicator in monitoring system performance, UV disinfection has no such
indicator.  This can lead to over-utilization of the  system in  an at-
tempt to simplify operations and ensure adequate disinfection.   Un-
fortunately, this will also increase the costs to operate the process.
A key operational tactic is to use only that portion  of the system that
is necessary to meet current performance demands.  This will entail
frequent sampling and analysis.  The system should  be sampled several
times weekly during periods of peak diurnal flows when the maximum
bacterial density levels and maximum loading are expected.  The influ-
ent to the UV system should be analyzed for suspended solids, UV
absorbance and coliform density.  At the time of sampling, the  flow
rate as well as the operating condition of the reactor (number  of lamps
in operation, etc.) should be recorded.  The effluent from the  UV re-
actor should be analyzed for coliform density.  Although at currently
operating municipal UV disinfection systems such analyses are not being
routinely performed, it is important to collect this  data to not only
evaluate system performance under current wastewater  conditions, but
also to be used as a tool in controlling the system and optimizing
operations for maximum use of^lamps and minimal  use of energy.   The con-
tinuous collection of this data will also aid in a  rational  approach to
troubleshooting a non-performing system.

-------
F.  Conclusions

    Region V will  continue to see more installations  of municipal  UV dis-
    infection systems,  especially retrofit installations for  plants  where
    chlorine residual  toxicity is an issue.  As  such,  design  engineers  must
    be made fully  aware of all  of the critical aspects of a properly designed
    municipal UV disinfection system.  There are three key areas  that govern
    the design of  a UV disinfection system:  hydraulics, UV intensity,  and
    wastewater characteristics.

    The hydraulic  properties of a particular UV  reactor must  be  such that
    the greatest number of organisms come into contact with the  strongest
    UV radiation for the longest possible time.   As part of their respon-
    sibilities, the UV manufacturer must provide evidence (dye tests) that
    there is greater than 90% plug flow and no shortcircuiting within the
    reactor.

    The intensity  of the UV radiation that ultimately  reaches the target
    organisms will  be  affected by the condition  and configuration of the
    lamps, as well  as  the particulate bacterial  density.  These  factors
    establish the  lower limit of disinfection efficiency. In order  to
    verify the validity and appropriateness of a particular design,  a bio-
    assay procedure to  estimate delivered dose and system intensity  must
    be performed.   This procedure could also be  used  to compare  the  per-
    formance of competing commercial units during design and/or  bid  phases
    prior to installation.

    Wastewater characterises are site-specific  and parameters such  as  the
    flow rate, suspended solids, initial  coliform density, and the UV
    absorbance of  the  wastewater must be empirically  measured for confirma-
    tion of actual  values prior to design.  These measurements should be
    taken during peak  diurnal flows when a WWTP  experiences the  maximum
    bacterial density  levels and maximum loading periods.

    Once a UV disinfection system has been designed and built, the opera-
    tion and maintenance of that system will  determine the ability of the
    process to meet permit limits.  The emphasis of 0  & M is  to  maintain
    the lamps, ballasts, and reactor at peak  efficiency while also ensuring
    that all surfaces  between the UV radiation and the target organisms are
    clean for consistent kill ratios.

    UV lamps have  a finite lite that can be prolonged  by the  use  of  voltage
    dimming.  Frequent  on/oft cycles will  decrease  lamp life.  Inlet screens
    will prevent large  debris from entering the  UV disinfection  system,
    clogging the reactor or breaking lamps.

    Ballasts have  to be protected from excessive heat  which shortens their
    useful life.  Adequate ventilation must be provided for the  power panel
    that normally  contains  the ballasts.   It  is  also  important to ensure
    that the ballasts  are properly mated to the  UV  lamps.

-------
Inadequate cleaning frequency is one ot the most common causes ot a UV
disinfection system's non-performance.  The surfaces of the lamps
and/or teflon tubes should be kept clean at all  times tb ensure that
adequate radiation is being transmitted.  There  are several methods
available to clean the surfaces in a UV reactor, but a chemical clean-
ing system that is integrated with the disinfection system is  necessary
regardless of what other methods are used.
Properly scheduled maintenance is
system operating efficiently.  At
total system should be overhauled
also be thoroughly cleaned at the
season.  In order to accomplish al
the UV disinfection system must be
room to remove and replace lamps,
ports, as well as sampling points
system.
necessary to keep the UV disinfection
lease once a disinfection season the
and checked out.  The system should
beginning and end of a disinfection
1  of the necessary maintenance tasks,
 accessible and there must be enough
sheaths, etc.  Drains, inspection
must also be a part ot a complete
Frequent sampling and analysis (several times per week) during periods
of peak diurnal  flows should be done as a tool  to certify system per-
formance, as well as, to control  the system and to optimize operations.
A key operational tactic and energy conserving  measure is to use only
that portion ot  the system that will meet current permit limits.
                     This report was prepared by

                  Valdis Aistars and Charles Pycha
                      Environmental  Engineers

                     Technical  Support Section
                     Municipal  Facilities Branch
                     USEPA - 5WFT-TUB-9
                     230 S.  Dearborn Street
                     Chicago, IL  60604
                     (312) 353-2144

-------
     END VIEW
         EFFLUENT LEVEL
    SIDE VIEW
                                  CONTROL BOX
                                  *•    AND
                                  POWER SUPPLY
             \
UV MODULE —
EFFLUENT LEVELl—
               V
     Figure 1.  Schematic of the ultraviolet disinfection unit
              in the sewage treatment plant effluent channel

-------

 1 H i-. f f
 I < O *C f
flff
U-rt
  •si
             It M
             2  -
   \ V.
  ,gP
             k  I
             £•0^
S'C
el
     I
    i ^
    !a
        fM
        O
        d
   CO 1-
  Qj 1-1 n.
  M
        li
Muriat
acia
                  -8,
                     -


                   •f~>
                   8
           s
           d
            2-1
            CD —t L
            fl) 00 g
            ?i2 a
                 11
M .
13
                          fS,
                    "»
                    g|R
                    p-( (Q
                               i
                                i
                                IA
                           11
                           l1*
                                        H
                                        Q>
                                        &
                                 SI
                               TO
                                       ^1 CO rt
                                       Tl
                                       iH
                                       0)

um
te
                                        ^
                                        QJ
                                        »
                                              X,
                                              m
                     I.
                                       H
                                      S2
                                      ffw
                                                             o
                                                            "C 13
                                                            3 TJ
                                                             u «9
                                    o aj
                                    CM a
                                                 fi  S-
                                    o
                                    d
                                                    o
                                                    d
IM
en

13

-------
!
•§*&
Ol 3 Q
H O C
M rH -r-
"5 jj "** 1
05 2 O T
U 'rH
i § s?
O u if:



B ?
•" S ~"
m -H **•
O C O
* — *
i
8
«l ^
llll
Ii
^ 4,



u oL
c 57

ffj
a
v
Manufact
N C
"H "
off £

>
Cleaning
S~c/3


c S
P -
iis
M
lltl
§

c/
C
t
3 v.
ul S C


C j-
c -H a
- Q
00 w
•^ in
2
V
•rH
l*-t
0) M
W S
r
5
t



u
•f-t
M t
•3»
-
I|
O t

IS


csS



2
U

o
O
in va
r- tr


H

y
i"
o



rH
in
CM
I


?

a
o
rH
oo
0
in
CM
(M
O



y
ro (t
* S
-^ in

Ii


s





r* "*
TO CJ
O V-

\ 0


Ni


10
1;
CJ







!

y
i
o



m

o
ro
V

in
CM

ft


m
N

(NJ
^i



CO
s
1
CM
I
Cos
gg|


§


U
-r-t
is.S
oS
U) >
a c
S ji
•H
o a
^ (5
|j


c



a
u






ir
•H X

y
M
0



|
rH


rH
t-
rH

S

CM

O

N
O



V.
fn n.

— in

^S
o
CO V
8lt
r^ —


-rt
^4 "O
U (a
CD r-l
y« V
15 ^
(u
"^ u<
i
CM
>
-H
£
Ii
1
j
S


CJ

I-H i
o rt
ID A
i§
|5

10 1
CO |
s i


o



5
o




ii

o
Is

H
M
O






m
V

in
V

8





m
d
^
in
00
rH y;
CM f
g|
— m
S
!i

-------
                                  Table 2


    Current manufacturers of UV disinfection systems at Region V WWTP's
    Aquiom'cs Incorporated
    Kenton Lands Road
    P.O. Box 18395
    Erlanger, Kentucky  41018
    Phone #:  (606) 341-0710
2.  Northland Technologies, Inc.
    1115 Chestnut Street
    Burbank, California  91506
    Phone #:  (818) 841-8080
3.  Trojan Technologies, Inc.
    845 Consortium Court
    London, Ontario  N6E 2S8
    Phone #:  (519) 685-6660
4.  Ultra Dynamics Corporation
    1631 Tenth Street
    Santa Monica, California  90404
    Phone #:   (213) 450-6461
5.  Ultraviolet Purification Systems, Inc.
    299 Adams Street
    Bedford Hills,  New York  10507
    Phone #:   (914) 666-3355
    Ultraviolet Systems, Inc.
    P.O.  Box 707
    4902  Calumet Avenue
    Hammond, Indiana  46320
    Phone #:  (219)  937-4500

-------
      Ultraviolet Facilities in Region V in Design or Under Construction
Illinois  (1)                        Chip (5)

La Moille                           Ashland
                                    Hillsboro
Michigan  (18)                       Senecaviiie
                                    Williamsburg
Almont                              Wilmington
Bessemer
Blissfield                          Wisconsin
Clare
Flushing                            Beloit
Frankenmuth                         Casco
Imlay City                          Eagle River
Macomb  (Village of Armada)          Fish Creek
Manchester                          Marinette
Manistee                            Port Washington
Marlette
Milford
Mt. Clemens
Oscoda
Port Washington
St. Ignace
Vassar
Williamston
Wixom

-------
                                             idered, in.
                      of a W disinfection system     v

system design parameters (flow rate, TSS, BOD, wastewater temperature,
absorption coefficient  (0.35-0.5), initial coliform density, etc.)
prequalification  (bioassay-dose response curve and unit dosage
determination )
reduction of coliform count to NPDES limits after 7500 hours of lanp use
minimum design dosage (16,000 microwatts/cm2/sec ) at 70% of lamp output
greater than 90% plug flow and no short-circuiting (dye-test)
production of 90% of UV light at 253.7 nm
65% UV transmissivity (minimum of 50%)
rated lifetime of 7500 hours for UV lamps
no significant production of ozone
integrated chemical cleaning system
minimum contact time (5-7 seconds)
ballast cooling system
lamp temperature control system (95-122°F)
inlet screens
provision to drain reactor
easy access cleanout/inspection ports
suitable materials of construction (304 or 316 SS, resistant to UV, etc.)
light dimming capability
flow proportioning (ability to turn lamps on or off in relation to flow)
monitoring systems (UV  intensity, ballast temperature, lamp conditions,
etc. )
acceptance testing (after installation, at manufacturer's cost for re-
testing)
manufacturer's representative to be on-site for verification of proper
installation, start-up, and operation
ballasts certified by manufacturer to be compatible with lamps
sampling ports at both  inlet and outlet of the UV reactor
1 disinfection reason minimum warranty on system (coliform levels, minimum
dosage , operation of individual components , etc . )

-------
     yr T*lmrinatinn vs.  TV rtiKinfartiim for several
and CM <3p"""nlties* tJ^*** have exist ijjq phlorination
           IN
                                   JMHMBl
Facility
Ttown of
Churubusco
CBCt)5=20,25
TSS=24.30
Town of
Ferdinand
CBCD5=20,25
TSS=24.30
Kent land

City of
Greensburg
001)5=10,25
TSS=12,30
Average Design
Flow (M3D)

0.25

0.34

0.46

2.4
"includes
post aeration
i Capital
Icost
i
Cl-DeCl 170,000
i
UV (*) ! 50, 000
1
1
C1-D6C1 ! 15, 500
(*) !
i
UV i 66, 646
I
C1-D&C1 ! 92,000
|
UV (*) [82.000
* i
C1-D&C1 1204,000
1
* UV (*) |396,000
I
1
1
0,MtR
Cost
10,500
6,000
24,000
16 , 150
10.850
10.250
271^,000
113,000
Salvage
Value _,
8,215
4,929


Uf333
2.667
9,000
7,000
Present
Worth
165,300
104,300
134,514
215.379
189.864
175.921
546.000
502,000
                                        QUID
Facility
Village of
North Baltimore
(3005=10
TSS=12 _,
City of
Van wert
CBOD5=10
OSS=J.2
Village of
Richwood
CBGD5=10
TSS=12
Village of
Jefferson
CBCD5=10
OSS=15
Average Design
Flow (M3D)

0.80

2.6

0.38

1.21


Cl-DeCl
(*)
L UV _,
C1-DBC1
(*J
UV
Cl-BeCl
<*)
UV
Cl-DeCl
(*)

UV
Total
Capital
cost
131,959
116.054
29,000
201.300
224,400
170,500
110,410

I89f?70 '
Annual
OiW Cost _
1,130
2.820
4,500
8.000
8,500
8.600
Present Wbrtfi
Of OiN
124,170
100.800
Total
Present
_Worti^
150,968
154.602
79,600
328.800
304,100
308.400
225,510

274 .520
(*) * selected alternative
 *  - derived from piannning documents

-------