United States
                    Environmental Protection
                    Agency
Water Engineering
Research Laboratory
Cincinnati OH 45268
                    Research and Development
EPA/600/S2-87/022 May 1987
&EPA          Project  Summary
                    Aqueous-Phase Oxidation  of
                    Sludge  Using  the  Vertical
                    Reaction  Vessel  System
                      This study provides plant-scale oper-
                    ating data on the wet oxidation of mu-
                    nicipal wastewater sludge by the Verti-
                    cal Reactor Vessel* (VRV) system. An
                    important consideration in the evalua-
                    tion was the effect of the return flow
                    from the wet oxidation process on the
                    operation of the wastewater treatment
                    plant. The investigation was carried out
                    at the Longmont, CO, Wastewater
                    Treatment Plant (WWTP).
                      The VRV system consists of a series
                    of long concentric tubes placed in the
                    earth using conventional oil field tech-
                    nology. The reason for  using vertical
                    construction is to produce a  large hy-
                    drostatic head at the bottom of the sys-
                    tem. The pressure is needed to prevent
                    boiling at the temperatures required for
                    wet oxidation. By utilizing hydrostatic
                    pressure, pumping is required only to
                    overcome frictional losses. The need to
                    add energy for pressurization is elimi-
                    nated. Sludge is introduced along with
                    air or oxygen into the multiphase fluid
                    downcomer which is the second con-
                    centric space from the outside.  It is
                    pumped down this space where  it is
                    heated by hot oxidized sludge rising in
                    the outermost concentric space within
                    the vessel. In the bottom of the vessel,
                    temperatures of 250°C or higher are at-
                    tained and the oxidation of organic ma-
                    terials takes place with resulting  heat
                     production. At the center of the reac-
                     tion vessel is a tubular  heat-exchange
                     system which can either extract excess
                     heat or provide heat for startup of the
                     process.
                    *Mention of trade names or commercial products
                      does not constitute endorsement or recommenda-
                      tion for use.
  At temperatures above 260°C it was
 possible to achieve total chemical oxy-
 gen demand (COD) reduction of about
 80% and total volatile solids reductions
 of over 90%. For the 25-cm reaction ves-
 sel installed at Longmont, the capacity
 of the system using air was limited to 5
 metric tons per day. Using oxygen it
 was possible to increase capacity to
 about 30 metric tons per day. Returning
 the supernatant liquid from the process
 to the wastewater treatment system
 did not have a significant effect on the
 effectiveness of that system.
   This Project Summary  was devel-
 oped by EPA's Water Engineering Re-
 search Laboratory, Cincinnati,  OH, to
 announce key findings of the research
 project that is fully documented in a
 separate report of the same title (see
 Project Report ordering information at
 back).


 Introduction
   Treatment and disposal of municipal
 wastewater treatment plant  sludge is
 expensive, with the cost constituting as
 much as one-half of the total cost for
 wastewater treatment. In addition, dis-
 posal of the sludge after treatment is
 becoming an increasing  problem in
 many locations. There is growing resis-
 tance to disposal in landfills because of
 possible groundwater contamination,
 and strong resistance to increased
 ocean disposal from communities near
 the  coasts. Incineration, which  accom-
 plishes disposal except for a relatively
 small volume of residual ash, is being
 questioned because of possible air pol-
 lution problems.

-------
   Wet oxidation of sludge, which is sim-
 ilar in some ways to incineration, pro-
 duces a greatly reduced  volume of a
 material similar to ash. It  has a signifi-
 cantly reduced  air pollution potential,
 but does produce a liquid waste stream
 containing low molecular weight or-
 ganic materials, especially acids. This
 liquid waste stream can be sent to the
 mafn treatment system and does not
 cause a disposal problem.  Although the
 technical feasibility of wet oxidation for
 sludge treatment has been recognized,
 the process is expensive  and  has not
 been widely used. In the 1970's the con-
 cept of carrying out wet oxidation in a
 vertical  reactor placed in the ground
 was investigated. Using conventional
 oil field technology, a very  long reaction
 vessel, over 1,000  m, could  be  con-
 structed which would provide  high
 pressure at the bottom from the hydro-
 static head. Sufficient pressure could be
 developed to prevent vaporization of
 water at temperatures above the 250°C
 required to carry out sludge oxidation.
 This vertical configuration eliminated
 the need to provide energy for  pressur-
 izing the wet sludge. A system of con-
 centric tubes was developed which pro-
 vided an  annulus  for pumping the
 sludge down the reactor  and  another
 annulus where the sludge returned to
 ground level. In addition, tubes were
 provided  for circulation of  a heat-
 transfer  fluid down the reactor to add
 heat during startup and to remove ex-
 cess heat  during operation. The  eco-
 nomics of this vertical configuration ap-
 peared  reasonable because of the
 elimination  of  an  expensive above-
 ground pressure vessel, the need for
 only a small land area, and reduction of
 pumping energy to only that needed to
 overcome wall friction.
  A pilot test of the vertical configura-
tion was carried out in the late 1970's at
the Lowry Bombing Range near Denver.
The depth of the system was only about
460 m, and did not produce high
enough static pressure to prevent boil-
ing without pressurizing the  system at
the surface. The results of this study
were sufficiently encouraging to test an
improved design at a municipal waste-
water treatment plant. The size of the
system needed to be sufficient  to treat
all the sludge from the treatment plant.
  The full-scale evaluation of a VRV sys-
tem was carried out at the Longmont
WWTP. The overall objective  of  this
study was to provide plant-scale operat-
ing data on sludge oxidation. Two
specific goals were:
   • To determine operating parameters
     for the process which would result
     in  effective reduction of COD and
     total suspended solids (TSS).
   • To determine the effects of the re-
     turn of wet oxidation supernatant
     on the biological treatment  in the
     Longmont system.
 Procedure
   A VRV system was sized to treat the
 approximately 3,600  kg/day of sludge
 produced by the Longmont plant and
 was  installed on the treatment  plant
 grounds. A diagram of the total sludge
 treatment system is shown in Figure 1
 and indicates the path of the sludge
 through the reactor. The section  of the
 reactor containing heat transfer oil con-
 sists of an outer and inner tube. Insula-
 tion between the tubes reduces heat
 transfer between them. The diameter of
 the reactor  is 25 cm and the length is
 1,600 m. It was intended to operate the
 system using air for oxidation, but this
 procedure limited capacity and reduced
 the effective hydrostatic head because
 of  the presence of  relatively insoluble
 nitrogen bubbles. A source of oxygen
 was added  to allow operation over a
 range of oxygen contents up to 100%. A
 Lamella Solids Separator, which is a va-
 riety of tube settler, was used to sepa-
 rate the oxidized, ash-like residue from
 the wet-oxidation supernatant. Provi-
 sion was made for returning the super-
 natant  to the wastewater treatment
 plant.
  The system  was operated during
 most of 1984 and 1985 under a variety
 of operating conditions. COD removals
 obtained are shown  in Figure 2. Al-
 though  COD reduction is plotted  as a
 function of temperature, the effect of
 other variables is also  included and ap-
 pears as scatter in the data. Ranges for
 these variables are shown in the table
 included on  the figure. Figure 3 shows
 volatile suspended solids reduction as a
 function of temperature. Just as for the
 COD plot, this plot includes data cover-
 ing a range  of other variables as  indi-
 cated by the table on the figure. These
 results  indicate that at temperatures
 above 260°C very good reduction  of
 COD  is obtained,  and most of the
 volatile suspended matter is both solu-
 bilized and largely oxidized.  The  proc-
 ess is, therefore, quite effective for pro-
 ducing a low-volatile-content, ash-like
 material. Return of the supernatant
from the oxidized product after solids
separation did  not have a  significant
 negative effect in terms of effluent bio-
chemical oxygen demand (BOD) or sus-
pended solids  content. There was a
slight increase in ammonia content in
the treatment plant effluent. The degree
of oxidation was not greatly affected by
the amount of excess oxygen available.
Good operation should be possible with
only slightly more than the stoichiomet-
ric amount required for COD reduction.

Conclusions
 1. With the use of air, the system ca-
   pacity was limited to 5 metric tons
   per day for the Longmont 25-cm re-
   action vessel. The use of oxygen in-
   creased system capacity to a maxi-
   mum of 30 metric tons per day.
 2. For bottomhole temperatures of
   260°C and above,  COD reductions
   of 75% to 80% were achieved and
   reproducible. Temperature had the
   largest effect on COD reduction. By
   recycling the effluent, the reduction
   in COD was  increased about 5%.
 3. BOD in the VRV effluent stream was
   readily biodegradable, showing a
   140% increase in the  efficiency of
   the trickling  filter that served  as a
   roughing treatment upstream of a
   rotating biological  contactor. As a
   result, the Longmont WWTP was
   able to process all the recycled BOD
   and still meet its NPDES discharge
   limit, even during periods when ad-
   ditional sludge was hauled in.
4. During autogenous operation, that
   is,  operation in which heat  pro-
   duced by oxidation was sufficient to
   maintain the reactor temperature,
   total volatile suspended solids re-
   ductions averaged 96.5%, and total
   volatile solids reductions averaged
   93.9%. Total suspended solids re-
   ductions averaged 78.7%, and COD
   reductions averaged 76.3%.
5. An  industrial hygiene  survey indi-
   cated that trace components in the
   off-gas were usually about 2 orders-
   of-magnitude below the permissi-
   ble  limit for  an 8-hr worker expo-
   sure.
6. A metallurgical inspection of the re-
   action vessel by Material Science
   Corp. showed  insignificant corro-
   sion, consistent with a 20-year life.
   Materials of construction for the
   VRV and the surface equipment
   proved satisfactory.
7. Based on  the  Longmont demon-
   stration, it was possible to establish
   operating and  maintenance costs
   for a 25-cm reaction vessel operat-
   ing  at maximum  capacity. Operat-

-------
From Atmos.
Nitrogen-*- — . i
Feed f^ K.
(^ JWea

' — * — t
r
Sludge Thickent
?--•£"—--"--'
*.' -' ^i — '""
V_y ^ 1
r*- |
1 — J
Longmont \
* n
Sludge Feed -»• — cxj-LJ-
TrucA S/urffl
Connection'*'™"] Grind
Process ~ t-j-
M/afer
Process ? o
Wa^er >—J 'j
Effluent ^ \
Recycle
,^c
__,-
Sca/e
Inhibitor
CO— »• 	 cxi 	
f Xlffenf Tan/r ^y compressor

xt~£ \m \ I
tea? Xlffenr f^ X ft '
^"'""^ nr^i ff8'6'' ' M * **
Heaf
Exchanger

reeu
Tank heed (S-3) . ; .
.Raw Sludge (S-1) \
•t^*— t-o-jT^"3 ["^"^^i*^
e S/odffe *J^" :
er Pump Feed Pump ;
Diluent (S-2) •
\ M •
r Diluent
? Pump . '
r - |
^ V^
flea
Ve
Gas to _„ _
/i.^^o i Off -Gases
Effluent (S-4) Atmos^.
\ Gas Separator
I-, 	 1 	 1 — -txj-4 > — •
' Stilling
Well
To
;. £fluent^^
I Recycle
_y i
cf/on
sse/
X
^Supernatant (S-5)
• • /* \
-™-\ Solids
\Separator) Underfh
^^^ £o/ids (S
Ash I
{— 1 S/arry
| 1 Pum» \ { {
\ \ \\ l-l
1 J±1.*J -"S/7 P/'fS ]
Sump Pump '
-*-t»*- Effluent
                                                                                                         Hauling
                                                                                                      Ash
                                                                                                          Truck
Figure 1.    Process flow diagram.
10,
11
ing and maintenance costs for a
Longmont-sized  unit  are  below
$100 per metric ton with an  energy
recovery credit of $17 per  metric
ton.
The  ash  is  nonhazardous.
Leachates from the EP Toxicity Test
were  typically  2 orders-of-
magnitude below limits set by EPA.
Ash in the VRV effluent was easily
dewatered. Solid contents of 40% to
75% were obtained after dewater-
ing by a centrifuge without any opti-
mization of centrifuge operation.
The system operated from  non-
autogenous  to extraction of heat.
Operation in the autogenous mode
was extremely smooth. Wash-out
heat was limited to a temperature
rise between influent and effluent
of 11-17°C (20-30°F) during autoge-
nous operation.
High  mechanical  availability
(96.7%) of the  system and its com-
    ponents did not limit the test pro-
    gram in any substantial way.
12.  COD reduction for the full-scale sys-
    tem at Longmont was successfully
    predicted from laboratory batch re-
    actor (LBR) tests.
13.  VRV operation was consistent and
    reproducible at fixed operating
    parameters.

Recommendations
  The following are recommendations
for improving system design, based on
the results of the demonstration period:
 1.  Biological treatment of the reaction
    vessel effluent should be further in-
    vestigated to optimize COD reduc-
    tion.  Benefits of anaerobic polish-
    ing should be tested.
 2.  The VRV effluent return appeared to
    influence the  biological speciation
    and caused more rapid reduction of
    BOD. Identification of biological
    species before, during, and after ox-
   idation system operating periods
   should be included in future tests.
3.  Returning the VRV effluent stream
 '  to the headworks of the Longmont
   WWTP would provide flow  equal-
   ization and reduce concentration
   prior to undergoing biological
   degradation. An option should be
   provided to allow VRV effluent re-
   turn either to the  headworks or to
   the trickling filters.
4.  The unit installed at Longmont was
   oversized.  A  new reaction  vessel
   more closely matching Longmont's
   sludge generating capacity should
   be installed and tested.
5.  Higher influent heat transfer fluid
   temperatures were  required  for
   startup due  to welding failures
   which occured in four sections of
   the insulated tubulars. Coupling de-
   sign also  contributed to greater
   heat loss than expected. However,
   the  system was still able to reach

-------
;oor
35
90
SB
Of
80
75
70
65
6O
%Q
|55
'§50
835
°30

25
20
15
10

Q

Q
D "^ H D
«$? 'ftnt
f'fi ,
IP
LJ - " u k
D D cP D F) cP1
n tn
D
D


a

-, 3ij3°anjn|5nr
|ij"JHffjjSJTtjjl
pSP^IJibjppl
a l"^ ffie a
n o
a rj]






Pj^Jfc

] rBJD
no
Hh
n


° 0 D Operating Conditions
; Q
COD Influent, mg/L
COD Effluent, mg/L
0 COD Reduction %

Bottomhole Temp. C
Sludge Load, Ib/hr
Liquid Flow, gpm

Air Flow. Ib/min
Oxygen Flow, Ib/min
22O 225 230 235 24O 245 250 255 260 265
Bottomhole Temperature (C)
Figure 2. CODT reduction vs. bottomhole temperature.





100-f
95
90
oc
GO
80'
75-
70
65
60
St 55
,| 50
||45
» 40
co 35
to
£30
J.O
20
15
10

•
o
n
n r] a
n jfi^pfp3
cfl
en
a a
a




Average
21.400
5,030
76.3

267.5
1200.0
108.8

3.4
17.2
270 275








Sxi QjiLE
-fPl-raTb
a





fidnoG
(Low-High)
5,600-48,500
1,400-19,400
32.3-92. 1

228-282
0-1,930
65-145

0-24.0
9.5-25.4
280 285 290








S&j-a-n
TP""






required bottomhole temperatures.
Improved insulated tubular design
should eliminate failures in future
installations. The performance of
the insulated tubular has minimal
effect during autogenous opera-
tion.
6. Pressure measurement tubing
caused organic fouling and suf-
fered mechanical damage during
installation and operation. Organic
fouling limited the length of operat-
ing runs. This fouling is not antici-
pated to occur in a commercial re-
action vessel, since downhole
pressure measurements will not be
required for VRV operation.
7. Mechanical dewatering of the ash
slurry should be installed. Polymer
addition should be optimized to re-
duce dewatering costs.
8. The use of ash as a filler material for
brick manufacture was demon-
strated and could be implemented
at future installations where appro-
priate.
9. The VRV should be insulated or
constructed so as to reduce heat
losses to the formation. High-
boiling-temperature oil should not
be present in the annular space be-
tween the reaction vessel wall and
the primary casing string. These im-
provements will reduce initial heat-
up and time to restart after a shut-
down, and will increase heat
recovery.
The full report was submitted in fulfill-
ment of CS-809337-01 by The City of
Longmont, CO, under the partial spon-
sorship of the U.S. Environmental Pro-
tection Agency.


Operating Conditions


COD Influent, mg/L
COD Effluent, mg/L
COD Reduction %
Bottomhole Temp. C
Sludge Load, Ib/hr
Liquid Flow, gpm

Air Flow, Ib/min
Oxygen Flow, Ib/min
Heat Transfer Fluid, Ib/min


Average
12.700
2,700
69.0
267.0
700.0
111.0

11.7
8.7
310.0

235 24O 245 25O 255 260 265 270
flange
(Low-High)
2,200-32,400
900-10,900
50-83.9
247-280
150-1,500
93-136

0-20.2
0-22.0
0-470

275 280














                               Bottomhole Temperature (C)
Flgura 3.    TVSS reduction vs. bottomhole temperature.
                                      4

-------

-------
      This Project Summary was prepared by staff of the City of Longmont, CO 80501.
      Edward J.  Opatken was the EPA Project Officer (see below).
      The complete report, entitled "Aqueous-Phase Oxidation of Sludge Using the
        Vertical Reaction Vessel System," (Order No. PB 87-170  320/AS;  Cost:
        $18.95, subject to change) will be available only from:
              National Technical Information Service
              5285 Port Royal Road
              Springfield. VA 22161
              Telephone: 703-487-4650
      For further information. Carl Brunner can be contacted at:
              Water Engineering Research Laboratory
              U.S. Environmental Protection Agency
              Cincinnati, OH 45268
United States
Environmental Protection
Agency
Center for Environmental Research
Information
Cincinnati OH 45268
     BULK RATE
POSTAGE & FEES PAID
        EPA
  PERMIT No. G-35
Official Business
Penalty for Private Use $300
EPA/600/S2-87/022

-------