United States
              Environmental Protection
              Agency
Air and Energy Engineering
Research Laboratory
Research Triangle Park NC 27711
              Research and Development
EPA/600/S8-91/P.10 May 1991
EPA      Project Summary
              Follow-up  Durability
              Measurements and  Mitigation
              Performance  Improvement
              Tests  in  38  Eastern  Pennsylvania
              Houses  Having  Indoor  Radon
              Reduction Systems
              W.O. Findlay, A. Robertson, and A.G. Scott
                Follow-up testing was conducted In
              38 houses in eastern Pennsylvania
              where indoor radon reduction systems
              had been installed under an  EPA-
              sponsored demonstration project 2 to 4
              years ago. These study houses were
              mostly "difficult" basement houses, in
              that soil gas radon concentrations were
              extremely elevated, and sub-slab com-
              munication was often not good. This
              follow-up testing  was to assess: the
              durability of these mitigation systems;
              why the systems had not consistently
              reduced residual radon concentrations
              below 4 pCi/L* in some of the houses;
              and methods for reducing the installa-
              tion and operating costs of systems.
                The durability testing indicated that
              indoor radon levels, and the flows and
              pressures in  the mitigation systems,
              have not experienced any significant
              deterioration since installation, except
              in six houses where system fans have
              failed,  and except where the system
              has been turned off by the homeowner.
              Where indoor radon levels over the
              years have varied by an amount greater
              than twice the standard deviation ex-
              pected based upon measurement un-
              certainty and natural variations, this
              situation is not due to  failure of the
              systems to adequately prevent soil gas
              entry through the slabs. Rather, the
              variations in indoor levels  have likely
               *1 pCi/L = 37 Bq/m3
 resulted from changes in re-entrainment
 of the high-radon exhaust from active
 soil depressurization systems, and/or
 from radon released to the air from well
 water.
   Testing to assess the causes of el-
 evated residual radon levels in some of
 these houses Indicates that—with one
 exception—failure to adequately de-
 pressurize beneath the slab is not the
 cause for elevated levels in houses
 having sub-slab depressurization (SSD)
 or drain-tile depressurization (DTD)
 systems. (Inadequate depressurization
 beneath the slab might be a contribut-
 ing cause in houses having block-wall
 depressurization (BWD) systems.) The
 primary cause for  elevated  residual
 levels in  houses with SSD and DTD
 systems are: 1) re-entrainment of the
 exhaust from the systems; and 2) air-
 borne radon resulting from high radon
 concentrations In the well water. Es-
 sentially all of the houses could be re-
 duced below 4 pCi/L, and probably be-
 low 2 pCi/L, if these two sources of
 radon could be eliminated. The signifi-
 cance of re-entrainment (due to high
 radon levels in system exhausts) and of
 well water as a source results from the
 high radon content in the soil gas, a
 characteristic of this region that makes
 these houses  "difficult" to mitigate.
 Testing showed that the elevated re-
 sidual indoor levels are not the result of
 unduly elevated radon concentrations

          Oy6 Printed on Recycled Paper

-------
 In the outdoor air, or to undue emana-
 tion of radon from the concrete slabs
 and foundation walls.
   Testing to assess means for reduc-
 ing  Installation  and operating  costs
 showed that pre-mltlgatlon sub-slab
 suction field extension measurements
 using a vacuum cleaner would  have
 given  general  guidance regarding
 whether the sub-slab communication
 was  good  or poor. However, where
 communication was poor, the diagnos-
 tics would not  have  given definitive
 guidance regarding the required number
 and location of SSD suction pipes, over-
 predicting the number required. Where
 communication was good or intermedi-
 ate, as shown by the diagnostics, test-
 Ing confirmed that the number of SSD
 pipes In some of these systems could
 ba reduced significantly (from four or
 six, to two or perhaps less). Fan capacity
 could  not  be reduced  significantly
 without increasing Indoor radon levels,
 despite diagnostic results suggesting
 that such capacity reductions should
 be possible. SSD systems will not al-
 ways  provide  adequate  treatment of
 block walls, necessitating a BWD com-
 ponent to the system. Between 6  and
 42% of the system exhaust consisted of
 air withdrawn from the basement.
   TTife Project  Summary was devel-
 oped by EPA's Air and  Energy Engi-
 neering Research Laboratory, Research
 Triangle Park, NC, to announce  key
 findings of the research project thai Is
 fully documented In a separate report
 of the  same title (see Project Report
 ordering Information at back).

 Introduction
   During the period June 1985 through
June  1987, devebpmental indoor radon
 reduction systems were installed and tested
 In 40  houses in communities on  the
 Reading Prong in eastern  Pennsylvania.
All of the houses had  basements,  and
several had an adjoining slab-on-grade or
crawl-space wing. The primary mitigation
 method in all but eight of these houses
was some  form  of active soil  depres-
surization (ASD). Four of the eight houses
received active block-wall pressurization,
three received air-to-air heat exchangers,
and one received only  a  radon-in-water
removal unit. The initial evaluation of these
systems was conducted primarily by means
of short-term (several-day) radon mea-
surements with the  systems on  and off,
obtained using Pylon AB-5  continuous ra-
don monitors.  Various  other  diagnostic
tests,  such as measurements of  suctions
and flows in ASD system piping, were also
 conducted. This project, including the re-
 sults from the short-term measurements,
 is reported in detail elsewhere.
    To evaluate the performance of these
 radon reduction systems over a longer
 time period, follow-up alpha-track detector
 (ATD) radon concentration measurements
 were subsequently made in 38 of these 40
 demonstration houses.over several periods,
 after the systems had been in operation for
 a year or more. Only 38 of the original 40
 houses were measured; one of the houses
 had been removed from the original site,
 and the owner of a second house  had
 discontinued participation in the project.
    The first, 3-month ATD measurement
 period was during the winter of 1987-88, at
 which time the systems had been in op-
 eration for 1  to 3 years.  The second, 4-
 month measurement period was over the
 winter of 1988-89, after an additional year
 of system 'operation. The winter quarters
 were selected for these 3- to 4-month ex-
 posure periods in order to determine the
 performance  of the 'systems during cold
 weather, which would normally be expected
 to provide the greatest challenge to the
 systems. For these winter-quarter mea-
 surements, detectors were deployed both
 in the basements of the houses, and in the
 living area on the story above the base-
 ment. Finally, during the 12-month period
 December 1988 through December 1989,
 an annual ATD measurement was made in
 the living area of the 38 houses, to estimate
 the impact of the mitigation systems on the
 actual annual average exposure of the
 occupants.
   These previous follow-up projects were
 limited to ATD measurements, and to the
 collection of any system failure information
 that could be obtained by inteiviewing the
 homeowner.  None of these follow-up
 campaigns included any other "diagnostic"
 testing (such as ASD system suction/flow
 measurements in system piping, or suction
 field extension measurements underneath
 basement slabs), to obtain a more complete
 assessment of system durability.
   The systems in these 38 houses repre-
 sent some of the earliest mitigation instal-
 lations of this type in the U. S. Most of the
 relatively limited number of  prior installa-
 tions in this country had addressed indoor
 radon resulting from human-activity-reiated
 sources (in particular, where uranium mill
 tailings were used as fill during construction
 or as aggregate in the construction materi-
 als). With human-activity-related sources,
 mitigation  approaches  often focused on
 source removal, and the cost of mitigation
 was less of a concern, since this cost was
 usually not borne by the homeowner. But
for naturally occurring radon in soil gas, as
 for the eastern  Pennsylvania houses,
 source  removal was not an option,  and
 cost was crucial, since homeowners would
 ultimately be  paying for such systems
 themselves. Adding to the difficulties was
 the fact that the  indoor concentrations in
 many houses in this region were extremely
 high (commonly 200 to 1,500 pCi/L, much
 higher than generally experienced with hu-
 man-activity-related sources), requiring the
 immediate attention of the homeowners.
   In view of this environment, a primary
 objective of the early project was to dem-
 onstrate that: 1) effective systems (capable
 of reducing these highly-elevated houses
 to 4 pCi/L and less) could be designed;
 and 2) such systems  could be installed at
 relatively low cost, with  equipment and
 with a skill level comparable to that of the
 typical worker  in the  building trades. Ac-
 cordingly, the intent was to demonstrate
 that  systems could be  successfully  de-
 signed for a significant number of houses
 without  elaborate diagnostic  testing, and
 that most of the information needed could
 be obtained from visual inspection supple-
 mented by information that could be pro-
 vided by the homeowner. To compensate
 for the reduced pre-mitigation diagnostics,
 and in view of the much  more limited un-
 derstanding of mitigation  systems existing
 at that early stage, it was less expensive to
 simply over-design the  system, utilizing
 more  ASD suction pipes or a larger fan.
 Because of the need to demonstrate suc-
 cess (< 4 pCi/L) on a fair number of houses
 (ultimately 40), extensive adjustments were
 not possible in an effort to optimize the
 systems or to further improve performance,
 once the goal of 4 pCi/L had apparently
 been met.
   The results of this necessary approach
 were that:
   1)  some  of the houses were not re-
 duced below 4 pCi/L on a long-term basis
 (although,  for all, the percentage  radon
 reductions were substantial). For example,
 from the annual ATD  measurements, 6 of
 the 28 houses where the mitigation system
 had been operating throughout the year
 had an average annual indoor radon con-
 centration above 4 pCi/L in the living area.
   2) some houses were  reduced well be-
 low 4 pCi/L, and it was not known to what
 degree the system fan capacity might have
 been reduced, or the number of suction
 pipes  reduced, and still  have met  the 4
 pCi/L goal.
   Since this original project was com-
 pleted, interest has increased in being able
to reduce radon concentration well below
4 pCi/L (e.g., to < 2 pCi/L). Only 13 of the
28 houses with  continuously-operating
systems were reduced to an annual aver-

-------
age of 2 pCi/L and less in the living area.
The ability to achieve below 2 to 4 pCi/L in
these eastern  Pennsylvania houses is of
particular interest because they represent
"difficult" houses, due to the poor commu-
nication beneath some of the slabs, and to
the very  high  radon source term under
many of the slabs.

Project Objectives
   In view of  the above considerations,
the project described in this report had two
objectives: 1) to further  evaluate system
durability, and  2) to test  improvements to
some of the systems in an effort to achieve
< 2  pCi/L In  these "difficult" basement
houses and to  reduce costs.

System Durability
   A more  complete assessment was
made of  the durability of the  mitigation
systems in these houses, beyond what
had been possible in the previous follow-
up AID measurements.  These ASD sys-
tems, among the oldest in the U. S., had
been operating 2 to 4 years at the outset of
this  study. This  duration is only a few
percent of the required system lifetime, but
it is still long enough to provide an insight
into the early failure modes of ASD systems.
   This more complete measure of dura-
bility included:
     Further evaluation of  the  previous
     follow-up ATD measurements  in
     these houses.
     Measurement of the pressures, flows,
     and radon concentrations in system
     piping,  for comparison  against mea-
     surements made soon  after installa-
     tion.
 •   Thorough inspection of the system to
     more completely identify hardware
     and materials failures.
     Inspection of the  houses and sys-
     tems,  and appropriate measure-
     ments, to evaluate the causes for any
     apparent degradation in system per-
     formance, and the causes for ob-
     served  hardware and materials fail-
     ures.
 •   Measurements with the mitigation
     systems turned off for one to four
     days, to assess the long-term impact
     of ASD systems on the radon source
     term under the slabs.

System Evaluation/Improvements
   There were two elements to this objec-
tive:  1) to assess how the performance of
selected installations (initially achieving >
4 pCi/L) might be improved to achieve < 2
pCi/L in these "difficult" basement houses,
and 2) to assess how costs might be  re-
duced by scaling down  selected systems
which were initially achieving below 2 to 4
pCi/L, and thus seeming to be over-de-
signed.
   Testing addressing element 1, above,
involved efforts to determine why certain
houses were still above 2 or above 4 pCi/
L, and what  additional steps  would be
necessary to achieve levels below 2 pCi/L.
These efforts included:
 •   Measurements of sub-slab pressures
     with the original system operating, to
     determine whether inadequate  suc-
     tion field extension might be respon-
     sible for  the residual  indoor radon
     levels.
     Measurement of the re-entrainment
     into the house of high-radon exhaust
     gas  from the  ASD system, using
     tracer gases, and tests of modifica-
     tions to the ASD exhaust, to deter-
     mine the contribution from  re-en-
     trainment.
 •   Installation of temporary charcoal
     water treatment  units on incoming
     well  water in  selected houses, to
     permit measurement of the contribu-
     tion of radon in the well water to the
     residual airborne radon in the house.
As part of this effort,  sub-slab communica-
tion measurements were conducted using
an industrial vacuum cleaner to induce the
suction, to assess  how effectively such
pre-mitigation diagnostic testing might aid
a mitigator in immediately achieving < 2
pCi/L in difficult houses such as these.
   Testing addressing element 2, above,
to reduce system installation and/or oper-
ating costs, included:
 • ,  Modifications to selected  ASD  sys-
     tems, including reducing the number
     of sub-slab depressurization  (SSD)
     pipes or reducing the fan suction, to
     determine  whether scaled-down
     systems would provide adequate re-
     ductions. (This effort also included
     evaluation of vacuum cleaner com-
     munication testing to assess the ex-
     tent to which such pre-mitigation di-
     agnostic testing might aid in prevent-
     ing inadvertent system over-design).
 •   Assessment of when block-wall de-
     pressurization (BWD) is required, in
     addition to or instead of SSD, in order
     to adequately treat difficult basement
     houses. BWD systems would typically
     be expected to exhaust much more
     treated house air, increasing system
     operating costs. In selected houses
     where the original installation  was
     entirely a BWD system,  temporary
     SSD systems were installed TO pro-
     vide suction beneath the entire slab.
     The  independent BWD  and  SSD
     systems were each operated  alone,
     to indicate whether the SSD system
     by itself could equal or surpass the
     performance  of  the  original  BWD
     system.
 •   Measurement of the amount of base-
     ment air in selected ASD system ex-
     hausts, using tracer gases, to permit
     enhanced estimates of the operating
     costs of ASD systems in these types
     of houses.

Results and Conclusions

Durability of the Mitigation
Systems
   The durability of the 2- to 4-year-old
mitigation systems in  the  38 accessible
study houses was evaluated through further
analysis of the previously collected winter-
quarter and annual ATD radon measure-
ments, through measurements of mitigation
system flows and suctions, and through
system inspections. All of these houses
have a basement, in some cases with an
adjoining slab-on-grade  or paved crawl-
space  wing. All but two  of these houses
had  pre-mitigation  radon concentrations
above 20 pCi/L, and several had pre-miti-
gation levels well above 200 pCi/L.
   The following conclusions are based
on this effort:
 1.  Based on analysis of the ATD mea-
     surements since  1986, the systems
     in these 38 houses have not experi-
     enced any significant degradation in
     their ability to treat the radon entry
     routes, except where the fan has
     failed or where the homeowner has
     turned the system  off. Considering
     the standard  deviation  in  the ATD
     measurements, resulting from quan-
     tified uncertainty in the measurement
     method and from natural variations
     in indoor levels, the winter-quarter
     ATD measurements over the years
     have generally  remained  constant
     within two times this standard devia-
     tion (i.e., within the 95% confidence
     interval).  In the  11 houses where
     individual results varied  by greater
     than twice  the standard deviation,
     this variation can almost always be
     attributed to causes otherthan failure
     of the system to treat the soil gas
     entry routes. (Re-entrainment of ex-
     haust gas from soil depressurization
     systems, or airborne radon resulting
     from radon in  well water, have been
     shown to be the likely causes of these
     variations  in  most  of  these  11
     houses.)
 2.  Based upon further analysis of the
     ATD data, and of other data obtained
     during this project,  essentially all  of

-------
     the still-elevated study houses hav-
     ing sub-slab depressurization (SSD)
     or drain tile depressurization (DTD)
     systems could be reduced below 4
 t   pCi/L (and probably below 2 pCi/L)
     by redesigning the mitigation system
     exhaust and/or by treating the well
     water. That is, the elevated residual
     (post-mitigation)  levels in  these
     houses are not due to failure of the
     SSD and DTD systems to treat the
     soil gas entry routes. However, the
     elevated  residual  levels in  houses
     having block-wall pressurization and
     block-wall depressurization  (BWD)
     systems are probably indicating that
     wall treatment alone  sometimes
     cannot consistently  treat all  entry
     routes adequately in these highly-
     elevated houses, at least not during
     cold weather.  Elevated residual lev-
     els in houses having heat recovery
     ventilators (HRVs) are consistent with
     the  moderate reductions expected
     with HRVs.
3.   Based upon further  analysis of the
     ATD data, the annual average radon
     levels in the living area are equal to
     the winter-quarter levels, within ±1.0
     pCi/L,  in  the  large majority of the
     houses (21 out of 28 in which reliable
     annual results were successfully ob-
     tained). Of those houses where the
     difference was greater than 1.0 pCi/
     L, the annual average  was higher
     than the winter-quarter value in  more
     than half of them, the reverse of what
     would  have been  expected. Thus,
     winter measurements do not neces-
     sarily ensure worst-case results. Re-
     entrainment of mitigation system ex-
     haust gases, and unreported occa-
     sions where the homeowners might
     have turned off the  system during
     mild weather  during the annual
     measurement, might be contributing
    to the  annual  measurements being
     relatively higher than expected.
4.   Measurements of  flows,  suctions/
    pressures, and radon concentrations
    in mitigation  system piping during
    this project indicate that, within the
     range of uncertainty in the measure-
    ment techniques, these parameters
    have remained very consistent over
    the years. There has been no ap-
    parent degradation  in the perfor-
    mance of the 38 systems, in terms of
    these operating parameters.
5.  Of the 34 active soil ventilation fans
    operating in this project, 6 have failed
    over the 2 to 4 years that these sys-
    tems have been operating. Five of
    these six failures have been the result
     of failure of an electrolytic capacitor
     in the fan  circuitry;  an increased
     number of failures might be expected
     in the near future, as more fans sur-
     pass the 4.5-year operating lifetime
     thought to apply to the capacitors in
     many of the fans. Recent experience
     has shown  that the fans commonly
     used on this project can continue to
     operate for a year or more, at dra-
     matically reduced performance, after
     the capacitor fails; this observation
     underscores the need for  flow- or
     pressure-actuated alarms or gauges
     on soil depressurization systems.
6.   One of the  three HRVs installed in
     the original project has had to  be
     repaired  since installation,  due to
     seizure of the bearings in the motor.
7.   The silicone caulk used to seal SSD
     pipes into slab holes is continuing to
     provide generally intact seals after 2
     to 4 years, although the caulk often
     was no longer adhering to the con-
     crete slab. In some cases, air move-
     ment induced by the operating system
     as the caulk originally set created
     small openings in the seal. The PVC
     cement used to connect segments of
     piping  continued to  provide good
     seals except where sections of poly-
     ethylene (PE) piping had inadvertently
     become mixed with the PVC piping
     generally  used. The  PVC cement
     could not bond to the PE piping; in
    this project, silicone  adhesive was
    found to be an effective sealant for
     PE piping joints.
8.  Of the two granular activated char-
    coal (GAC) units installed to remove
     radon from well water, the unit con-
    taining a charcoal specifically  se-
     lected for radon removal has contin-
     ued to provide removals greater than
    95% since installation 3 years earlier.
    However, the unit containing a gen-
    erally-available charcoal not specifi-
    cally selected for radon removal has
    exhibited a continued deterioration in
    performance, from 95% removal im-
    mediately after installation in  1986,
    to 38% removal in December 1989.
9.  Homeowner intervention in system
    operation,  usually in the form  of
    turning the  system off, has been a
    common experience (reported in eight
    of the  houses).  Fans were usually
    turned off: during mild weather (when
    windows were  commonly open);
    when the owners were away; or as
    the result of fan noise. In these high-
    radon houses,  opening windows of-
    ten did not compensate for the sys-
    tem being off, since the annual ATD
      measurements often1 showed radon
      levels increasing having increased
      over  winter-quarter readings where
      the fan was known to have  been
      turned off. In two houses, the owners
      modified the systems, relocating the
      fan or installing a fan power control-
      ler.
  10.  Turning off these systems after sev-
      eral years of operation resulted in a
      relatively rapid return to the original
      pre-mitigation  indoor levels (over 1
      to 3 days), confirming that the source
      term is "durable". This rapid recovery
      suggests that large amounts of radon
      are being generated in the soil rela-
      tively near to the houses, and/or that
      soil gas movement through the soil is
      relatively rapid, so that there is a
      ready supply of radon.

 Testing to Improve System
 Performance
   The residual  radon concentrations in
 these  study  houses suggest  a  greater-
 than-average difficulty in achieving EPA's
 original 4 pCi/L guideline, and a  possible
 problem in reliably achieving the goal of
 near-ambient indoor radon concentrations
 specified in the U.S. Indoor Radon Abate-
 ment Act of 1988. Half of the houses were
 above 4 pCi/L in the basement according
 to the average of the winter-quarter ATD
 results; about one-quarter, were above 4
 pCi/L on an annual average in the living
 area, and about half were above  2 pCi/L.
 Accordingly, in  this  project, testing was
 undertaken to assess to  what extent the
 residual radon levels are due to: inadequate
treatment of soil gas entry routes; re-en-
trainment of exhaust from ASD systems;
well water usage; ambient radon infiltrating
from outdoors; and emanation from build-
 ing materials.
   The following  conclusions are based
 upon this effort:
 1.  Sub-slab depressurizations being
     maintained by the ASD systems were
     measured. Of the houses with  SSD
     systems (and the one with an interior
     DTD system), only in House 39 does
     it clearly appear  that the elevated
     residual radon  levels are'due to un-
     even  and inadequate distribution  of
     the suction field under the basement
     slab.  Exterior DTD  systems gener-
     ally produce lower sub-slab  depres-
   _ surizations than do SSD systems,  as
     expected; however, in those exterior
     DTD houses having elevated  residual
     radon, other testing conducted 'in this
     project indicates that the residual ra-
     don is largely due to re-entrainment
     and/or radon in well water, not  to

-------
    inadequate slab treatment. Houses
    with  BWD systems generally have
    only marginal sub-slab depressuriza-
    tions, and this  might be partly re-
    sponsible for the elevated  residual
    radon levels in many of these houses.
2.  The exhaust configuration was modi-
    fied in nine houses having a SSD or
    DTD system where exhaust re-en-
    trainment was suspected of being a
    problem, to assess the possible effect
    of re-entrainment on indoor levels.
    No significant  reductions in indoor
    levels were  achieved by converting
    from  horizontal exhausts at grade
    (directed 90° away from the house)
    to vertical discharges  above  the
    eaves.  Thus,  re-entrainment from
    these two  configurations appears
    generally comparable; horizontal ex-
    haust at grade might be  acceptable,
    especially when the radon concen-
    trations  in the exhaust are not high,
    as long as the exhaust is directed
    90° away from the house. However,
    where the exhaust at  grade was
    vertical  immediately  beside  the
    house—or where it is horizontal and
    is directed parallel to the house—
    converting  to  vertical  above-eave
    discharge, or to discharge at grade
    directed  away from the house, re-
    sulted in significant reductions in in-
    door  levels. Thus,  the  vertical-at-
    grade and horizontal/parallel at grade
    configurations were clearly causing
    significant re-entrainment in these
    houses, and should be avoided. At-
    tempts to quantify the actual re-en-
    trainment using PFT tracer gases in
    some of these nine houses did not
    give meaningful results.  Exhaust re-
    entrainment is thought to be the pre-
    dominant contributor to residual radon
    levels in a number of the houses.
3.  Temporary GAG well water treatment
    units were installed in four houses
    where well water was suspected of
    being a  major contributor to residual
    airborne levels, and the effects on
    the indoor airborne concentrations
    were measured. The data were also
    reviewed from the two houses which
    had received permanent GAG units
    3 years before. In four of these six
    houses, removal of radon from the
    water caused a  reduction in airborne
    levels consistent with the 10,000:1
    rule-of-thumb (i.e., 10,000 pCi/L in
    the water contributes an average of
    approximately 1 pCi/L to the airborne
    concentrations).  In the fifth house,
    the airborne reduction was about half
    that which would have been predicted
     from the rule-of-thumb. The results
     from the sixth house are not mean-
     ingful. These results confirm that well
     water is an important, though gener-
     ally not the sole, contributor to the
     residual airborne levels in a number
     of the study houses.
 4.  Outdoor radon concentrations in the
     study area were not unduly contrib-
     uting  to indoor  concentrations. Of
     ambient measurements in seven lo-
     cations, six gave readings below the
     estimated national average of 0.5 pCi/
     L. The seventh location yielded 0.8
     pCi/L.
 5.  Radon  flux  measurements from
     uncracked  concrete  in one house
     suggested that the slab and poured
     concrete foundation walls in this
     house  were  contributing  less  than
     0.2 pCi/L to  the  indoor concentra-
     tions. Thus,  as  expected,  building
     materials do not appear to be a sig-
     nificant residual source  in these
     houses.
   In summary, based upon the measure-
ments  made  in this project, it is believed
that the reasons  are now understood why
all of the study houses still above 2 pCi/L
are above that level. Commonly, more than
one of the first three contributors discussed
above  are contributing to the residual lev-
els.

Testing to Reduce System
Installation and  Operating Costs
   Tests were conducted in  a number of
the houses to obtain a better understand-
ing of mitigation installation and operating
costs, and to  explore ways in which these
costs might be reduced. These tests in-
cluded: investigation of whether the num-
ber of SSD suction pipes might be reduced
in  some cases where the SSD system
appears to be over-designed, including an
assessment of whether appropriate pre-
mitigation diagnostic testing might have
been cost-effective  in identifying the desir-
able  number and location of suction pipes;
investigation of the  effects of  reducing fan
capacity, where the system seems over-
designed based  upon diagnostic testing;
assessment of when BWD is required, in
addition to or instead of, SSD (since BWD
might be expected to have a greater oper-
ating cost, in view of the significant amount
of  house air  expected  to be exhausted);
and measurement of the amount of house
air in ASD exhaust.
   The following conclusions are based
on this testing:
 1.  Pre-mitigation suction field extension
     measurements  using a  vacuum
     cleaner  can give general guidance
    regarding how bad or  how uneven
    sub-slab communication is,  when
    communication is not good. But such
    testing cannot give quantitative di-
    rection regarding the  number and
    location of suction pipes for optimum
    design in such poor-communication
    houses, since the diagnostics tend to
    over-predict the number of SSD pipes
    required. For example,  in one study
    house, seven SSD pipes proved more
    than  adequate  to  treat the slab,
    whereas  the vacuum cleaner diag-
    nostics would have predicted that 17
    pipes would have been  needed. And
    where there is a good layer of aggre-
    gate and  communication is thus very
    good, the vacuum cleaner diagnos-
    tics will provide no information beyond
    that which would be obtained by vi-
    sual inspection of the aggregate.
2.  The  SSD systems  in  five  houses,
    each initially having four to six suction
    pipes through the  slabs, were re-
    duced to  two pipes each. In the two
    houses  having  excellent sub-slab
    suction field extension, where  the
    original system appeared to be'over-
    . designed, the reduction in the number
    of pipes had no significant effect on
    indoor radon levels, as would have
    been predicted by the diagnostics. In
    another two houses having interme-
    diate suction field extension, reduc-
    tion in the number of pipes again had
    no significant impact on indoor levels.
    However, in the  fifth house—where
    the diagnostics  had suggested that
    the original six-pipe SSD  system
    should have been marginal in treating
    the entire  slab—reduction of  the
    number of pipes  did indeed result in
    a significant increase in indoor con-
    centrations,  from 0.7 to  6.3 pCi/L.
    These results confirm that the diag-
    nostics can give general guidance
    regarding the number  of pipes re-
    quired.
3.  In three houses having  intermediate
    to excellent sub-slab suction field ex-
    tension and system flows well below
    the capacity of the SSD fan, the fan
    capacity  was reduced  by reducing
    power to  the fan. The power reduc-
    tions reduced system suction to 25
    to 40% of  full suction.  In all three
    houses—despite the suggestion by
    the diagnostics that the  tested re-
    ductions in fan power still should have
    provided  adequate slab treatment—
    the reduction of fan suction resulted
    in a significant  increase in  indoor
    levels, by 44 to 250%. While insuffi-
    cient testing was carried out to deter-

-------
    mine why the reduced fan capacity
    resulted In the increased indoor lev-
    els, h is clear that good  sub-slab
    depressurizatfons and  low system
    flows do not automatically mean that
    significant reductions in fan capacity
    are going to be possible. Perhaps a
    lesser reduction in fan power would
    have been possible without increas-
    ing indoor levels.
4.  To assess whether the  BWD sys-
    tems in some of these study houses
    might be effectively replaced with
    state-of-the-art SSD systems, tem-
    porary SSD systems were installed
    in three houses where: 1) the original
    system was entirely or predominantly
    BWD; and 2) sub-slab communica-
    tion is very good. Despite  effective
    deprassurizatfon of the sub-slab by
    the temporary SSD systems, the
    BWD systems were far more effec-
    tive in reducing radon concentrations
    in the basements and living areas of
    all three houses (giving residual ra-
    don levels half or less of the residual
    levels with SSD). This result con-
    firms that block walls can sometimes
    be important  sources that are not
    adequately treated despite effective
    depressurizatton of the sub-slab. Ad-
    ditional SSD pipes, near to the walls,
    might have improved the performance
    of the SSD systems.
5.  Through  measurements  of tracer
    gases in the ASD exhausts in seven
    houses, it was determined that be-
    tween 6 and 42% of the exhaust gas
    consisted of basement air. This is at
    the low end of the range reported by
    other investigators for houses having
    SSD systems  (21 to 90%). The two
    houses in this testing having exterior
    DTD  systems showed  the least
    basement air in the exhaust (6  and
15%), as  would be expected.  The
one  house having a BWD system,
where the percentage of basement
air in the exhaust would be expected
to be the highest, had 34% base-
ment air in the exhaust; this is not the
highest  percentage among  the
houses tested here, and is at the low
end  of the range reported by other
investigators for houses having SSD
systems. Of the four houses tested
here having SSD systems, the two
with  block foundation walls had gen-
erally higher percentages (26  and
42%) than did the two with poured
concrete foundation walls (15  and
32%). These relatively low percent-
ages might be suggesting that the
slabs in these houses are relatively
tight, consistent  with the excellent
suction field  extensions observed in
some houses.
                                                                           u. S. GOVERNMENT PRINTING OFFICE: 1991/548-028/20223

-------

-------
 W.O. FIndlay, A. Robertson, and A. G. Scott are with Acres International Corpora-
  tion, Amherst, NY 14228-1180.
 D.B. Henschel Is the EPA Project Officer (see below).
 The complete report, entitled "Follow-up Durability Measurements and Mitigation
  Performance Improvement Tests in 38 Eastern Pennsylvania Houses Having
  Indoor Radon Reduction Systems," (Order No. PB91-171389/AS; Cost: $45.00,
  subject to change)  will be available only from:
        National Technical Information Service
        5285 Port Royal Road
        Springfield, VA 22161
        Telephone: 703-487-4650
 The EPA Project Officer can be contacted at:
        Air and Energy Engineering Research Laboratory
        U.S. Environmental Protection Agency
        Research Triangle Park, NC 27711
United States
Environmental Protection
Agency
Center for Environmental Research
Information
Cincinnati, OH 45268
      BULK RATE
POSTAGE & FEES PAID
 EPA PERMIT NO. G-35
Official Business
Penalty for Private Use $300
EPA/600/S8-91/010

-------