EPA TEST NUMBER 73-TRB-2 SAN DIEGO GAS AND ELECTRIC COMPANY KEARNY MESA GAS TURBINES SAN DIEGO, CALIFORNIA EPA LIBRARY SERVICES RTP NC EPA-EMB-73-TRB-2 TECHNICAL DOCUMENT COLLECTION ------- EPA TEST NUMBER 73-TRB-2 SAN DIEGO GAS AND ELECTRIC COMPANY KEARNY MESA GAS TURBINES SAN DIEGO, CALIFORNIA SUBMITTED TO Environmental Protection Agency Office of Air Programs Contract No. 68-02-0225 Task No. 14 BY ENGINEERING-SCIENCE, INC, 7903 Westpark Drive McLean, Virginia 22101 March 1973 ------- PREFACE The work reported herein was conducted by Engineering-Science, Inc. pursuant to Task Order No. 14 dated November 11, 1972 issued by the Envi- ronmental Protection Agency under the terms of EPA Contract No. 68-02-0225. APPROVED FOR ENGINEERING-SCIENCE, INC. Terrence A. Li Puma, Director Air Pollution Control Department 28 March 1973 ------- SECTION I TABLE OF CONTENTS SECTION II III IV V VI APPENDIX A B D E F G H I TITLE INTRODUCTION DISCUSSION AND SUMMARY OF RESULTS PROCESS DESCRIPTION LOCATION OF SAMPLING POINTS SAMPLING AND ANALYTICAL PROCEDURES COMPLETE PARTICULATE RESULTS WITH EXAMPLE CALCULATIONS COMPLETE GASEOUS RESULTS WITH EXAMPLE CALCULATIONS COMPLETE OPERATION RESULTS WITH EXAMPLE CALCULATIONS FIELD DATA SAMPLING PROCEDURE LABORATORY REPORT TEST LOG PROJECT PARTICPANTS OPERATING DATA LOG PAGE 1 3 23 28 30 ------- ! SECTION II ! INTRODUCTION i Source emission tests were conducted on the exhaust gases from two gas turbine power generators at the Kearny Mesa plant of the San Diego Gas and Electric Company, San Diego, California. The tests were con- ducted to aijd in the establishment of federal emission standards for sources in this category. The two identical units tested were manufac- tured by the General Electric Company and have a peak load rating of 17.2 Mw. Th'e units were equipped with a water injection system designed to reduce oxides of nitrogen emissions. A series of nine successful test runs were completed during the period January 10 - 12, 1973. Continuous samples were taken for the determination of hydrocarbons, oxygen, carbon monoxide, and oxides of nitrogen. In addition, oxides of nitrogen were also measured using grab samples. All samples were taken from the turbine exit stack according to the recommended source test procedures of the i Office of Air Programs, Environmental Protection Agency. Some modifica- tions of standard procedures were necessary due to the unique character- istics of tHese facilities. This test was also of an experimental nature in that extensive comparison of test methods was conducted. Subsequent sections of this report include a summary of the analyses i performed and a brief narrative of the entire project; the location of sampling ports; the sampling and analytical procedures; the process descrip- tion; and the process operation. The appendices contain the analysis of the data and experimental procedures in addition to all the raw data collected during the tests. This report is written without specific views i of the test team regarding emission rates, compliance with air pollution regulations or control techniques. ------- Mr. Robert M. Martin, Office of Air Programs, Environmental Pro- tection Agency, coordinated the tests, arranged for sampling ports, elec- tricity, and other test facilities. In addition, he provided valuable guidance and technical advice on the actual conduct of the tests. Mr. James Eddinger, Industrial Studies Branch, Environmental Protection Agency, scheduled the tests and arranged for the desired operating conditions. Mr. Tom Logan, Environmental Protection Agency, conducted oxides of nitro- gen sampling using the PbOp method. Mr. Stanley Spruiell, Environmental Protection Agency, assisted with the velocity, temperature, and paramagnetic oxygen determinations. Mr. James Kelly, Environmental Protection Agency, conducted the laboratory analyses of one-half of the PDS oxides of nitro- gen samples. The remainder of the testing and analyses were performed by Messers. Michael E. Lukey and Burke Bell of-Engineering-Science, Inc.; Mr. C. McComis of Ultrasystems, Inc.; and Messers. John Chehaske, Daniel Whimpey, and Douglas Epps of Commonwealth Laboratory, Inc. ------- SECTION III DISCUSSION AND SUMMARY OF RESULTS The test team arrived in San Diego the night of Sunday, January 7, 1973. Monday morning was spent transporting the sampling equipment from the Chula Vista plant and from the airport to the Kearny Mesa plant. Monday afternoon and part of Tuesday morning were spent setting up and calibrating! the sampling equipment. High humidity and occasional rain showers forced cancellation of tests planned for Tuesday afternoon because of the humidity effect on the formation of oxides of nitrogen and the safety problem of working on the wet sloping metal roof of the turbine. Testing'commenced on Wednesday, January 10, 1973 and terminated on Friday afternoon, January 12, 1973. During this time, three tests (Runs 1 - 3) were conducted on turbine #GT-2A and six tests (Runs 4-9) were conducted on turbine #GT-2B. i Test runs 1 - 5 were complete stack traverses (7 rows of 7 points each) conducted at 16.2 + 0.2 Mw load. Test runs 6-9 were single-point runs conducted at 18.5 Mw, 15 Mw, 10 Mw and 5 Mw, respectively. All traverses were made in the same horizontal plane just upstream from the silencing baffles. Three 3/8 inch stainless steel sampling tubes, an S-type pitot tube, and a ceramic sheathed thermocouple were encased in a 2 inch pipe to form the sampling probe assembly. One of the sampling tubes was connected to i the EPA Paramagnetic oxygen analyzer with approximately 50 feet of Teflon tubing. The second sampling tube was utilized for the oxides of nitrogen determinations using the PDS method. The evacuated PDS flasks were connec- ted directly to the sampling tube thus eliminating a long sample line. ------- The third sampling tube was used for all the remaining sampling instruments except the PbO~ which used a separate, nontraversing sampling probe. Stack gases were drawn from this third tube through a heated teflon line by a teflon lined diaphram pump and were fed via a glass manifold to the following instruments: i ' CO - NDIR (Ultrasysterns) i HC - FID (ES) NO - Chemiluminescence (Ultrasystems) NO - Electrochemical (ES) ! /\ $2 ~ Polarographic (Ultrasysterns) All original field data and observations are contained in Appendix D. Tables III-l through III-6 summarize this data by test run and in addition provide oxides of nitrogen values normalized for excess air to both 3% and i 15% oxygen. The normalized NO values can be directly compared to existing /\ regulations1and proposed standards. (The current San Diego County Regula- tions are based on 3% 0^, while the proposed EPA standards are based on 15% 02.) Tables III-l through III-5 list the results of the first five tests. These were complete traverse tests requiring approximately three hours each.I Table 111-6 lists the results of the four single point tests, numbers 6 through 9; these tests were of 10 minutes duration. The tabulated PDS results are the average of two samples taken at each selected point. i The two samples were taken one immediately after the other; the analyses of one sample was performed by the EPA and the second sample was analyzed by Commonwealth Laboratory. Results of the Pb09 sampling runs are shown with i *• arrows to indicate the duration of each individual sample. The remaining determinations are listed point by point for each of the 49 points comprising a complete stack traverse. The stack temperature throughout the entire stack was relatively con- stant for each test; maximum variation observed was 150°F during test 2. ------- TABLE III-I KEARNY MESA, SAN 1)1 V.GO, CALIFORNIA Summary of Results Tost Run No. 1 - J.iiiunrv 10. 1973 A B C D E F G Snmi>] inf. Point s % 02 Correction ppm) Electro Clicm PbO, 1C (ppm) 0, (%) CO (ppm) Temp. (°F) Vol. (fpn) NOX 1'DS 'ppm) Electro Chcm Pb02 1C (ppm) 02 (%) CO (ppm) Temp. (°F) Vo.l. (fps) NOX PDS ppm) Electro Chem Pb°2 1C (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PBS !ppm) Electro Chem . Pb02 HC (ppra) 02 (%) CO (ppm) Temp.(°F) Vel. (fps) NOX PUS [ppm) Electro Chem phri HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm) Electro Chem "oi'.2 I1C (ppm) 02 (%) CO (ppm) rcmp.(°K) Vel. (fps) N0v PDS (ppm) Electro Glicm VfoOy 1C (ppm) )2 (%) CO (ppm) I'omp. (°K) VH . (fps) JNC 53 44 1 1 1.5 47 51 1 1 26 47 54 1 1 23 50 55 1 1 12 54 58 1 1 2C 52 54 1 1 21 54 56 ] . ?.( 1 3 177 148 5.6 • 37 020 4.4 146 158 1.3 5.2 20 060 4.5 154 177 2.3 5.5 25 075 4.0 164 181 1.2 5.5 25 0.75 6.1 174 185 0.8 5.4 22 085 0.0 170 177 0.8 5.5 27 065 9.7 170 1.77 L5.3 27 060 >9.1 15 59 49 49 53 51 59 54 60 58 62 57 59 57 59 INC 53 44 1 1 13 \> 52 53 1 It 6' 54 57 1 1 9 56 52 56 1 1 14 54 57 1 1 26 58 54 54 1 1 10 54 55 1 1 1.4 2 3 177 147 3.6 30 320 5.8 97 159 162 1.2 5.1 30 )65 'i.2 177 186 L.5 5.5 25 360 3.5 182 170 182 L.I 5.5 22 )45 7.1 174 183 1.0 5.4 22 075 5.8 185 174 174 0.8 5.4 27 065 2.6 170 174 0.7 5.3 27 . 065 8. 1 15 59 49 33 53 54 59 62 61 57 60 58 61 62 58 58 57 58 UNC 50 45 1 1 13 53 55 1 1 6 58 54 58 1 1 4 53 56 1 1 56 55 56 1 1 2f 55 54 1 ] l 52 54 J 1. 3 3 164 1.46 5.5 30 030 7.3 164 172 1.4 5.2 30 055 6.0 190 177' 189 1.3 5.5 25 080 2.1 174 183 1.1 5.5 22 065 0 178 177 180 1.3 5.4 25 060 6.1 174 170 1.0 5.3 27 L075 2.0 164 170 0.8 5.3 27 070 L4.9 15 54 49 55 57 63 59 63 58 61 60 59 60 58 57 55* 57 NC 50 46 02 52 54 52 59 32 53 57 54 54 57 53 55 A A 52 53 4 3 IG/i 152 1.' is.: 2< 10 2( 130.. 194 161 167 i.; is.; 3. 105f 93. ^ 170 193 l.C 15.1 25 108C 163. C 104 170 184 2.5 15.-! 22 10 7( lll.C 174 174 1. 15. 25 106( 162. ( 177 164 171 l A C 15. 27 106 0 1.64 171 0. 15. 27 107 94. 15 54 50 ) ) bb 54 56 > 57 64 ) ) ) 34 57 61 ) ) 58 58 1 4 D 3 59 55 57 Aft i 55 57 3 • 3 5 J UNC 50 47 1 1 19 50 54 1 1 12 54 50 . 61 1 1 14 54 56 1 1 14 60 53 53 1 1 52 55 1 1 51 52 1 1 .1C 5 3 161 152 1.5 5.4 25 033 6.6 167 181 2.4 5.6 60 075 6.1 175 164 200 1.0 5;5 25 050 7.4 174 182 5.4 22 050 7.4 193 170 170 5.4 27 055 0 157 168 5.1 27 075 0 L64 168 0.8 5.4 27 080 3.1 15 54 51 56 60 58 55 66 58 60 64 57 57 • 53 56 55 56 UNC 47 48 2 2i> 50 54 1 60 1 54 51 59 • 51 55 53 51 53 50 50 1 6 3 151 153 1.3 15.4 25 1020 51.0 84 167 180 2.0 L5.6 35 L060 47.8 196. .5.5 25 L050 L4.1 175 164 190 L5.4 22 L065 59.2 161 174 15.3 27 1060 0 167 161 167 0.5 15.3 27 1070 72.7 16 4 16 A 0.5 15.5 27 1070 87.7 15 50 5.1 U 56 60 65 58 55 63 54 58 56 54 56 54 54 UNC 40 46 1 1 29 46 52 1 1 25 48 42 1 1 3C 48 53 1 1 25 47 50 1 1 6 48 53 1 ] 2; 47 50 1 3( 7 3 126 1.46 1.3 .5.3 25 020 9.0 153 173 2.7 5.6 37 045 4.8 157 138 1.2 5.5 25 060 3.0 154 171 0.5 5.4 22 045 9.8 163 173 0.8 5.8 27 .045 5.8 152 .1.67 0.6 .5.3 27 075 0.4 1.51 167 0.5 5.4 27 070 )2.f> 15 42 48 51 58 52 46 51 57 54 58 50 56 50 5f> *S;impli: continued an iulilltJ.oii.il 7 mlnuti'S. ------- TABLE II1-2 KKAKNY IICSA, SAN 1)1 KGO, CALIFORNIA Summary of Results Test Run No. 2 - January 10, 1973 G F E D c- B A Sampling Points % o2 Correction NOX PDS [ppm)Electro Che.m PbO, 1C (ppm) 02 (%) CO (ppm) Temp. (°F) Vol. (fps) NOX PDS [ppm) Electro Chem Pb02 1C ' (ppm) 0, (%)' CO (ppm) Temp. (°F) Vel. (fps) NOX PDS [ppm) Electro Chem Pb02 1C (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm)Electro Chem ' Pb02 ' 1C (ppm) Oo <*> CO (ppm) Cemp. (°F) Vfil. (fps) NOX PDS (ppm) Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm)Electro Chem Pb02 HC (ppm) o2 m CO (ppm) Temp. (°F) Vol. (fps) NOX PDS (ppm) Electro Chem , PbO-) HC (ppm) 02 (%) CO (ppm) Tomp. (°F) Vt;1. (fps) 1 UNC 49 46 3 163 157 .15 54 52 0.5 15.6 - 22 1045 190.9 47 54 157 183 52 61 1.1 15.6 22 910 198.7 48 49 163 166 54 56 15.7 27 930 179.0 52 - 177 - 59 15.7 30 9-25 126.3 47 - 163 - 54 15.8 30 925 213.8 47 50 163 173 54 58 15.8 30-31 915 259.5 47 47 160 160 53 53 0.6 15.7 33 905 143.0 2 UNC 50 47 3 167 157 15 56 52 0.8 15.6 22 920 149.2 54 49 52 179 163 173 60 54, 58 1.1 15.6 22 925 109.4 48 50 163 170 54 57 0.6 15.7 27 930 228.2 53 50 180 170 60 57 15.7 30 915 154.2 - 49 - 170 - 56 15.8 30 925 101.9 54 49 50 183 166 170 61 56 57 15.7 30-31 925 79.9 47 47 163 163 54 54 0.5 15.8 33 920 1 .9 . 6 3 IMC 49 47 3 163 157 15 54 52 0.6 15.6 22 920 97.7 49 52 163 173 54 58 1.0 15.6 22 930 63.3 52 49 48 176 166 163 59 56 54 0.8 15.7 27 940 246.0 - 49 - 170 - 56 0.7 15.8 30 925 109.4 - 49 - 170 - 56 0.5 15.8 • 30 930 63.3 50 51 170 173 57 58 0.4 15.7 33 925 56.5 48 46 169 162 56 54 0.5 15.9 33 920 97.7 4 UNC 49 48 3 163 160 15 54 53 0.6 15.6 . 22 920 63.1 53 47 50 179 160 170 60 53 57 0.9 15.7 22 925 0 48 47 163 160 54 53 0.8 15.7 30 920 166.8 52 49 180 170 60 56 0.7 15.8 30 925 178.7 56 49 194 170 65 56 0.5 15.8 30 925 63.2 55 51 51 187 173 173 62 58 58 0.5 15.7 33 925 109.4 46 48 166 173 55 58 0.3 16.0 33 920 1 26 . 1 5 UNC 48 49 3 160 163 15 53 54 15.6 22 910 62.8 45 5.3 153 180 51 60 0.8 15.7 22-23 915 0 53 47 46 181 160 156 60 53 52 0.8 15.7 30 915 0 - 51 - 176 - 59 0.7 • 15.8 30 920 126.1 58 53 50 109 184 173 56 61 58 0.5 15.8 30 910 125.6 50 50 170 170 57 57 0.6 15.7 33 915 109.0 46 45 169 165 56 55 0.2 - 16.1 - 33 905 177.4 6 UNC 46 50 3 153 167 15 51 . 56 0.9 15.6 22 910 1.40 . 5 44 46 49 151 156 167 50 52 56 0.8 15.7 25 925 • o- 46 48 156 163 52 54 0.8 15.7 30 910 0 50 50 173 173 58 58 0.6 15.8 30 910 0 52 50 181 172 60 57 0.5 15.8 30 915 109.0 29 50 50 98 170 170 33 57 57 0.6 15.7 33 920 135.2 45 43 169 161 56 54 0.2 16.2 34 895 202.0 7 UNC 43 48 3 143 160 15 48 53 1.0 15.6 22 900 280.0 47 .7 160 160 53 53 15.7 25 915 188.8 44 46 149 160 50 53 0.8 15.7 30 915 188.8 - 47 - 163 - 54 0.6 15.8 30 890 187.1 44 48 152 170 51 56 0.5 15.8 30-31 910 251. 3 46 46 156 160 52 53 0.6 15.7 33 895 237.1 42 41 161 157 54 52 0.2 16.3 32 880 29 1 . 4 ------- TANLK Til-3 KEAKNY MKSA, SAN IUKCO, CALIFORNIA Summary of Rt.'iHil.ta Test Run No. 3 - January 11, 1973 Port A B ' D E - ' F G Samp] ing Points % 02 Correction NOX I'DS (ppm) Electro Chcra PbO? 1C (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm) Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS , (ppm)Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm) Electro Chem . Pb02 IIC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) N0x PDS (ppm)Electro Chem Pb62 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm) Electro Chem Pb02 IIC (ppm) 02 (%) • CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm)Elcctro Chem , Pb02 IIC (ppm) 02 (%) CO (ppm) ; Temp. (°F) , Vol. (fps) 1 UNC 53 46 3 74 154 15 58 51 0.8 15.5- 20 925 112.7 50 48 167 160 56 53 0.5 15.6 22 950 220.2 50 51 164 167 54 56 0.10 15.5 27 960 168.7 52 54 167 174 56 58 0.6 15.4 30 910 125.3 54 58 170 183 57 61 0.4 15.3 32 955 170.8 51 56 164 180 55 60 0.5 15.4 31-32 950 220.2 58 183 61 15.3 32 9.85 182.0 2 JNC 52 47 3 170 1.54 15 57 51 0.4 15.5 20 925 97.6 51 51 49 171 L70 1.63 57 57 54 0.5 15.6 25 910 62.7 51 52 L64 167 55 56 0.15 15.4 27 965 70.0 56 52 55 180 167 177 60 56 59 0.7 15.4 30 915 186.2 53 59 167 186 56 62 0.4 15.3 32 965 239.1 34 51 56 108 164 180 36 55 60 0.5 15.4 32 950 89.9 57 180 60 0.7 15.3 32 975 99.3 3 UNC 51 48 3 If. 7 157 15 56 52 0.5 15.5 20 935 56.6 53 51 174 167 58 56 0.3 15.5 25 930 56.5 56 54 52 180 174 167 60 58 56 15.4 27 935 40.0 52 54 167 177 56 59 0.8 15.4 30 935 97.9 56 54 55 177 170 174 59 57 58 0.5 15.3 ' 32 955 231.3 50 56 161 183 54 61 0.7 15.4 32 915 39.7 57 180 60 15.3 32 950 80.4 4 UNC 52 48 3 173 163 15 58 54 0.6 15.6 20 950 127.1 52 53 51 49 170 174 167 160 57 58 56 53 0.3 15.5 25 920 119.3 54 52 174 170 58 57 .15.4 27 960 139.7 63 53 56 202 170 180 67 57 60 0.8 15.4 30 955 180.1 52 53 164 167 55 56 0.5 15.3 32 945 106.2 58 52 57 53 182 1.64 1.80 170 61 55 60 57 0.8 15.3 32 960 0 56 183 61 15.4 32 930 69.1 5 . UNC 56 48 3 187 160 15 62 53 0.6 15.6 20 950 196.9 52 52 170 170 57 57 0.2 15.5 25 920 108.9 58 53 54 186 170 174 62 57 58 0.20 15.4 27 930 126.2 53 56 167 177 56 59 0.8 15.3 30 960 127.6 58 51 54 183 161 170 61 54 57 0.5 15.3 32 935 0 53 56 167 177 56 59 0.8 15.3 32 900 0 58 1.86 62 15.4 32 905 108.3 6 INC 45 45 3 150 150 15 50 50 0.6 15.6 20 930 252.4 54 51 50 177 167 167 59 56 56 0.2 15.5 25 940 138.8 51 52 164 170 55 57 15.4 27 955 113.9 56 52 56 177 164 177 59 55 59 0.9 15.3 30 960 0 50 52 161 167 54 56 0.5 15.4 32 930 0 56 52 56 177 164 177 59 55 59 0.7 15.3 32 865 77.9 57 186 1 62 15.5 32 890 175.9 7 UNC 42 43 3 180 143 15 47 48 0.6 15.6 20 930 296.0 46 48 150 157 50 52 0.2 15.5 27 935 256.0 47 49 1.51 158 50 52 15.4 30 935 296.5 49 49 155 155 52 52 15.3 30 960 180.4 48 51 154 164 51 55 0.6 15.4 32 935 260.6 49 54 155 1.70 52 57 0.9 15.3 32 905 137.2 57 1.86 62 15.5 32 910 306.9 ------- TA1ILE 1IT-4 KEARNY MKSA, SAN WECO, CALIFORNIA Summary of Results Test Run No. 4, January 11, 1973 A B. c D E- F G Sampling Points % 02 Correction NCx PDS (ppm) Electro Chcm Pb02 11C (ppm) o2 (%) CO (ppm) Temp. (°F) Vol. (fps) NOX PUS (ppm) Electro Chcm Pb02 HC (ppm) 0, (%) CO (ppm) Temp. (°F) Vol. (fps) NOX PDS (ppm)Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppra) Electro Cliem Pb02' HC (ppm) o2 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm)Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fns) NOX PDS (ppm)Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm)Klcctro Chcm, PbOi HC (ppm) 02 <%) , CO (ppm) Temp. (°F) Vc'l. (fprO 1 INC 51 50 3 167 164 15 56 54 0.5 15.5- 38 980 40.7 45 45 145 145 48 48 0.6 15.4 35 965 212.1 45 47 140 146 47 49 0.5 15.2 37 960 189.4 46 49 143 152 48 51 0.5 15.2 37 965 169.3 47 143 48 15.1 32 965 247.3 47 50 143 156 48 52 0.4 15.1 38 970 239.8 47 50 143 152 48 51 0.6 15.1 38 %0 H2.H 2 UNC 51 49 3 164 158 15 55 52 15.4 38 990 0 52 162 54 15.2 32 965 0 46 47 143 146 48 49 0.4 15.2 37 960 80.8 50 46 49 153 143 152 51 48 51 0.5 15.2 37-38 970 192.2 47 46 143 140 48 47 15.1 38 970 151.6 51 48 50 155 146 152 52 49 51 0.4 15.1 38 970 70.2 46 50 140 1.52 47 51 0.5 15.1 38 965 70.1 3 INC 50 50 3 158 161. 15 53 54 0.4 15.3 38 990 0 44 46 137 143 46 48 0.4 15.2 ' 37 965 0 48 46 48 149 143 149 50 48 50 0.4 15.2 37 960 40.4 49 152 51 15.2 38 970 128.0 48 47 49 146 143 150 49 48 50 15.1 " 38 970 169.5 48 50 146 152 49 51 0.4 15.1 38 965 0 47 50 143 152 48 51 0.5 15.1 38 965 40.5 4 UNC 49 50 3 152 .55 1.5 5V 52 0.5 15.2 38 990 152.7 54 47 46 47 168 146 143 148 56 49 47 49 0.3 15.2 37 970 99.3 M7 48 146 149 49 50 0.5 15.2 37 965 99.1 - - - 15.2 970 181.2 47 50 143 152 48 51 0.3 15.1 38 965 145.9 52 48 49 39 158 146 L50 11.4 53 49 50 40 0.4 15.1 38 960 0 46 50 140 1.52 47 51 0.5 15.1 38 905 57.2 5 INC 48 50 3 152 158 15 50 53 0.5 15.3 38 990 215.9 47 46 146 143 49 48 0.4 15.2 37 970 134 . 4 54 47 48' 168 146 149 56 49 50 0.5 15.2 '37 970 169.5 52 46 49 160 140 150 53 47 50 0.6 15.1 38 157.0 46 47 50 140 143 152 47 48 51 0.3 15.1 38 965 , 57.2 49 49 150 150 50 50 0.4 15.1 38 965 0 45 50 1.37 152 46 51 0.6 15.1 38 970 57.3 6 UNC 48 50 3 157 164 15 52 .5'' 0.5 15.5 38 985 237.5 42 46 47 132 143 146 44 48 49 0.4 15.2 37 960 191.6 47 49 146 152 49 51 0.5 15.2 37 970 157.0 49 47 50 150 143 152 50 48 51 15.1 38 975 111.2 50 152 51 0.4 15.1 38 ' 965 80.9 54 49 50 165 150 152 55 50 51 0.5 15.1 38 970 114.6 43 50 33 155 44 52 0.6 15.2 38 970 107.2 7 UNf: 4.1 45 3 139 153 15 46 51 0.6 15.7 38 930 246.3 45 47 131 146 47 49 0.4 15.2 37 940 • 246.3 46 48 143 '149 48 50 0.5 15.2 37 950 284.5 47 51 143 156 48 52 15.1 38 970 239.8 50 156 52 0.4 15.1 38 965 259.0 49 50 150 J.54 50 51 0.5 15.1 38 960 255.4 44 50 139 158 46 53 0.6 15.3 38 960 180.6 Sample continued an ailJitlnn.il 16 minute!!. ------- TABLE III-5 KEARNY MESA, SAN DIF.fiO, CALIFORNIA Summary of Results Test Run No. 5, January 12, 1973 G F E D C B A Sampling Points % 02 Correction NOX PDS (ppm) Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vcl. (fps) NOx PDS (ppm)Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX' PDS (ppm) Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vcl. (fps) NOX PDS (ppm) Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm)Electro Chem Pb02 HC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm) Electro Chem Pb02 UC (ppm) 02 (%) CO (ppm) Temp. (°F) Vel. (fps) NOX PDS (ppm)Elcctro Chem' Pb02 UC (ppm) 02 (%) CO (pnm) Temp. (kK) Vol. (fps^ 1 UNC 51 47 3 161 148 15 54 50 0.8 15.3 26 975 128.3 51 46 158 146 53 49 0.8 15.2 26 985 240.9 49 50 152 158 51 53 15.2 28 985 232.1 48 50 146 152 49 51 15.1 30 970 0 48 51 144 153 48 51 15.0 30 985 203.6 48 51 142 150 47 50 14.9 30 985 244.3 48 48 144 144 48 48 0.4 15.0 32 955 08.7 2 UNC 52 50 3 164 161 15 55 54 0.8 15.3 26 985 128.8 88 50 48 278 158 152 93 53 50 0.8 15.3 26 985 91.0 49 50 150 152 50 51 15.1 28 980 257.1 48 49 51 L46 147 153 48 49 51 15.0 30 980 157.4 48 49 L44 L47 48 49 15.0 30 985 64.4 44 49 51 129 145 150 43 48 50 0.1 14.9 30 975 40.6 48 50 144 150 48 50 0.4 15.0 32 970 114.6 3 UNC 55 50 3 171 158 1.5 57 53 0.8 15.2 26 1010 41.1 50 48 158 152 53 50 0.8 15.3 ' 26 980 0 42 49 50 124 147 150 42 49 50 0.4 15.0 28 980 213.2 48 49 142 144 47 48 14.9 30 975 111.1 42 49 50 124 145 148 41 48 49 14.9 30 980 40.7 48 52 142 153 47 51 0.1 14.9 30 970 40.5 49 50 147 150 49 50 0.4 15.0 • 32 960 133.9 4 UNC 54 50 3 171 161 15 57 54 0.8 15.3 26 1015 108.8 42 50 48 45 135 161 154 140 45 54 51 47 0.7 15.3 26 985 0 49 50 L47 150 49 50 0.5 15.0 28 975 128.3 47 49 49 142 147 147 47 49 49 0.4 15.0 30 980 J.92.8 49 50 L45 L50 48 50 14.9 30 980 26.7 42 49 50 126 145 148 42 48 49 0.2 14.9 30 980 81.3 48 50 42 144 150 127 48 50 42 0.4 15.0 32 960 189.3 5 UNC 54 50 3 174 161 15 58 54 0.8 15.4 26 1010 224.9 49 47 158 151 52 50 0.8 15.4 26-27 980 0 45 49' 49 135 147 147 45 49 49 0.6 15.0 30 980 0 49 50 147 153 49 51 0.5 15.0 30 980 134.8 52 49 50 148 145 153 49 43 51 14.9 30 , 995 144.5 50 50 150 150 50 50 0.4 15.0 30 980 107.5 48 50 144 ISO 48 50 0.4 15.0 32 960 231.9 6 UNC 47 48 3 157 160 15 52 .53 0.8 15.6 970 239.6 48 48 47 156 157 154 52 52 51 0.8 15.5 28 985 128.8 48 50 146 152 49 51 0.7 15.1 30 985 64.4 41 48 50 124 144 150 41 48 50 0.4 15.0 30 980 70.4 49 52 147 153 49 51 15.0 30 975 157.2 43. 50 50 132 152 152 44 51 51 0.3 15.1 30 • 970 169.4 47 48 148 155 50 52 0.4 15.3 32 945 290.9 7 UNC 45 42 3 156 145 15 52 49 0.8 15.8 26 940 245.4 48 49 163 166 54 56 0.9 15.7 28 980 257.1 48 50 149 155 50 52 0.3 15.2 30 980 250.6 48 50 144 150 48 50 0.4 15.0 30 980 215.1 48 50 149 155 50 52 0.2 15.2 30 965 293.0 49 47 152 146 51 49 0.3 15.2 32 950 257.5 46 48 150 157 50 51' ; • .• 1 0.4 15.5 32 940 283.4 Sample continued nn .•ulilltion.il /I nil nut i-f I ------- TABLE II1-6 KEARNY MESA. SAN DIEGO, CALIFORNIA Summary of Results Test Runs 6 through 9, January 12, 1973 Test No. 1 6 % 02 Correction NOX (ppm) Electro Chem HC (ppm) o2 (%) CO (ppm) Temp (°F) Velocity (fps) Load (Mw) ' 1 UNC | 3% ; _ . 60 163 161 166 15% 54 56 2.5 i 14.4 20 1050 174 ! 18 7 UNC 45 52 3% 162 187 15% 54 62 3.0 16.0 32 1050 — 15 8 UNC 31 39 3% 130 163 15% 43 54 7.5 16.7 75 — — 10 9 UNC 3% 26 134 32 165 15% 45 55 9.5 17.5 235 625 27 5 All samples taken from traverse point number D-4. 10 ------- As expected,; velocity varied widely from point to point, ranging from 0 at some points to just over 300 fps at other points. The highest veloci- ties were encountered near the stack wall which contained the sampling ports. Since the stack static pressure was slightly higher than ambient pressure there was no problem of stack gas dilution at the sampling ports. Hydrocarbon results were uniformly low with most values less than 1 ppm (as i propane) at normal operating loads. As the load was dropped, the hydrocarbon content increased, reaching a maximum steady state value of approximately 10 ppm at the 5 Mw load. During the 5 minutes or so required to shut down the turbine, the hydrocarbon concentration increased rapidly to over 500 ppm. Carbon monoxide concentrations, like the hydrocarbon values, were low and reasonably constant from point to point and from test to test. Values ranged from;20 ppm to 38 ppm for the normal load tests. At low load levels CO concentration increased, reaching 235 ppm at the 5 Mw load. The various methods of determining NO concentration did not yield X identical values, but did show the NO concentration to be uniform through- A out the stack and relatively constant with time. The NO concentration i i varied in direct proportion with the load -- approximately 60 ppm at 18 Mw and approximately 30 ppm at 5 Mw with no water injection. A general comparison of the NO methods used shows the following trends: : X 1. PDS yields the highest values but results are frequently erratic. ' Mean values range from essentially equal with electrochemical values to 10% higher than electrochemical. 2. Electrochemical and Chemiluminescence yield results that are nearly identical and are very stable. 3. PbOp yields the lowest values with somewhat more variability than I the continuous analyzers but not as much variability as the PDS. Results ranged from essentially equal to the electrochemical to approximately 10% lower than the electrochemical. 11 ------- In order to obtain a more definite comparison of the NOV methods used, A statistical analyses were performed on the PDS, electrochemical, and chemi- luminescence results from tests 1 through 5. For the purpose of these analyses, all NO values were corrected to 15% oxygen. No allowances were A made for deviant data points since the resulting correlations would reflect the ability of the data analyst rather than the precision of the test method. Table II1-7 shows the numerical difference in the results obtained by the electrochemical and the chemiluminescence methods and also the electro- chemical and PDS methods. The differences are given for each individual point at which comparative data were taken. The electrochemical method was used as the comparison standard because it yielded the most consistent stan- dard deviation results of the methods used. PDS values used were the average of the EPA and Commonwealth Laboratory results. The arithmetic means and standard deviations of the temperature, velo- city, and NO measurements are shown in Table III-8. Two additional types of A statistical analyses were performed on the NO data—the F test and the t test. A The F test compares the standard deviation or variance of each of the data sets and determines if differences in the standard deviations can be attributed to chance fluctuations or to a real difference in the standard deviations. The t test compares means or averages of all the data recorded by each test pro- cedure. Accounting for the standard deviations and an arbitrary confidence level (in this case 95%), the t test determines whether the difference in means between the two methods falls within the accuracy of the tests or if a systematic difference exists. In actuality, this is a comparison of the assumed normal population of one sampling procedure with the normal population of another procedure. The mean and standard deviation define one population. We then compare the mean 12 ------- TABLE III-7 COMPARISON BY DIFFERENCE (PPM) OF NO,, RESULTS CORRECTED TO 15% OXYGEN . A A-l 2 3 4 5 6 7 B-l 2 3 4 5 6 7 C-l 2 3 4 5 6 7 Test 1 E-C E-PDS 10 10 5 4 . ... 3 -1 -6 -4 -1 -13 -2 -2 -11 -4 -4 28 -7 -8 -3 -4 -4 -7 -11 -3 - 6 Test 2 E-C E-PDS 0 0 2 -3 - 1 2 2 -4 -1 -5 -1 0 -4 0 0 22 -1 - - - - 3 -5 3 -5 Test 3 E-C E-PDS 7 6 4 . 4 5 0 -1 3 3 0 2 2 1 0 0 -4 -2 -2 -1 2 -2 1 -1 -6 -2 -2 Test 4 E-C E-PDS 2 3 -1 -1 -3 -2 -5 0 - -2 2 0 1 -1 4 » -2 -2 -1 -2 -7 -1 -1 -6 -2 -2 Test E-C 0 -2 -2 -2 -2 -2 -2 -3 -2 -4 -1 o- 0 2 -3 -1 -1 -2 -3 -2 -2 5 E-PDS - - - - - - - - 5 - 6 - 7 - - - 6 - -2 • .- • — ------- TABLE III-7 (cont'd) D-l 2 3 4 5 6 7 E-l 2 3 4 5 6 7 F-l 2 3 4 5 6 7 Test E-C -6 -3 -3 -4 -2 -8 -6 -4 -3 -1 0 0 -4 -4 -2 0 1 -2 -3 -2 -6 1 E-PDS - -4 - 23 - -3 - - - -1 - -7 - - - -4 - -4 - -2 — Test 2 E-C E-PDS - - - - - - - -2 -3 -2 -4 1 1 -7 -2 -3 -9 -4 -6 -4 -4 -7 -9 -4 2 0 Test E-C -2 -3 -3 -3 -3 -4 0 -4 -6 , -1 -1 .-3. . -2 -4 -5 -5 -7 -5 -3 -4 -2 3 E-PDS - -4 - -11 - -5 - - - -3 - -8 * - - - 19 - -6 - -5 _ Test E-C -3 -3 - - -3 -3 -4 - 1 -2 -3 . -3 - - -4 -2 -2 -2 0 -1 -1 4 E-PDS - -3 - - -6 -3 - - - 1 - 2 - - - -5 - -6 - -5 _ Test E-C -2 -2 -1 0 -2 -2 -2 -2 -1 -1 -1 0 -2 -2 4 3 3 3 2 1 -2 5 E-PDS - -1 - 2 - 7 - - 7 - 4 - - - -40 - 9 - 6 _ ------- TABLE III-7 (cont'd) Test 1 E-C E-PDS G-l -2 - 2 -1 - 3 -2 - 4 -2 - 5 -1 - 60- 7 -6 - Test 2 Test 3 E-C E-PDS E-C E-PDS 2 - - - 4 _ 2 1 - - - _! _ _5 _ -5 - Test 4 E-C E-PDS -3 -4 -3 -4 — 5 — -8 -7 Test E-C 4 1 4 4 4 -1 -3 5 E-PDS - - - - - - - NOTE: E-C represents electrochemical vs chemiluminescent result. E-PDS represents electrochemical vs phenoldisulfonic acid result (where there were both PDS and Electro data points). ------- If" TABLE III-8 SAN DIEGO GAS AND ELECTRIC MEANS AND STANDARD DEVIATIONS OF NO,, TEMPERATURE'AND VELOCITY n A (NO values are corrected to 15% oxygen) Test PDSEPA (ppm) PDS Commonweal tt (ppm) ELEC (ppm) CHEM (ppm) ELEC where both PDS & ELEC data pts. exist (ppm) Temperature (°F) Velocity (fps) Test 1 Mean 51.77 52.12 54.75 56.73 55.55 1058.5 147.9 Stand 15.87 22.09 3.29 5.39 2.41 17.74 83.66 Test 2 Mean 54.15. 54.14 54.34 55.62 55.87 919.3 133.7 Stand 3.58 15.14 2.65 2.20 2.85 21.51 78.99 Test 3 |1 Test 4 Mean 56.62 56.28 55.05 56.91 55.88 936.6 133.7 Stand 1.89 14.5 2.74 3.54 1.34 23.28 82.73 Mean 47.62 54.45 48.40 50.46 48.13 967.1 131.1 Stand 4.37 4.86 2.18 1.73 0.80 11.00 84.62 Test 5 Mean 48.83 48.35 50.25 50.86 49.71 976.7 144.4 Stand 13.50 13.90 2.69 1.57 1.96 15.12 89.60 16 ------- and standard deviation to another population to see if they are the same. If, through the t test and the F test, we accept the hypotheses, then we can easily conclude that the sampling methods are identical. Table III-9 is a summary of the F tests performed. The "Hypothesis" i column shows which methods are being compared (PDS is Commonwealth Labora- tory PDS data; PDSERA is EPA PDS data; ELE is electrochemical data; CHEM is chemiluminescence data). Entries in the "Findings" column indicate whether the standard deviations were equal as hypothesized (accept) or not equal (reject). Results of .the t tests are shown in Table 111-10. Again, the two methods being compared are listed in the Hypothesis column, (col. 2), and the results of the comparison test are listed in the Findings column, (col 7). The two right hand columns (cols. 8 & 9) are included to show the results of the corresponding F tests. As ah example, the first line of Table 111-10 provides the following information: the methods being compared were the PDS data generated by the EPA for Test 1 to the PDS data generated by Commonwealth Laboratory for Test 1; the t test was accepted (col. 7); the F test was accepted (col. 8); therefore, the results obtained with these two methods for Test 1 can be considered equal within the accuracy of the method. The effect of standard deviation on the t test is very important and must not be overlooked. As the standard deviations decrease, the t test's acceptability range also decreases. Thus, if two methods each have a small standard deviation the t test becomes much more stringent and small systematic differences in methods can be detected. This is most dramatically shown by the data from Test 1. Comparison of EPA PDS data to electrochemical data was accepted as equal within the accuracy of the methods. The numerical 17 ------- difference in the means was 2.98 ppm. Similar comparison of chemilumi- nescence data to electrochemical data was rejected even though the means differed by only 2.02 ppm. In summary, the electrochemical method produced the lowest average standard deviation (2.71 ppm) followed closely by the chemiluminescence method (2.88 ppm). These low standard deviations indicate both methods have good precision. The electrochemical and chemiluminescence methods yielded nearly I identical results, the difference averaging only 2.8 ppm. This difference was shown to be a real systematic difference. The PDS results from the two laboratories compared favorably with each other and with the electrochemical method. The standard deviations, however, were erratic ranging from a low of 1.89 to a high of 22.09 ppm. If the extremely low PDS values are discarded as deviant data points, the standard deviations would decrease and the means would increase. 18 ------- TABLE III-9 F-TEST COMPARISON OF TEST METHODS FOR DETERMINATION OF NO,, CONCENTRATION L " X .05 95% Confidence Test 1 2 3 4 .. . 5 1 2 3 4 5 1 2 3 4 5 Hypothesis .o2PDS = a2ELE * 2 2 CT PDS = o ELE * a2PDS = a2ELE * 2 2 a PDS = a ELE * a PDS = a ELE * 2 2 o ELE = cr PDS * 2 2 o ELE = a PDS * 2 2 a ELE = a PDS . * a 2ELE = a 2PDS * 2 2 a ELE = a PDS * a 2ELE = a 2CHEM 2 2 a^ELE = a CHEM a 2ELE = a 2CHEM a ELE = a CHEM 2 2 a ELE = a CHEM F Calculated 84.01 28.22 117.04 36.9 50.29 43.36 1.579 1.999 29.83 47.46 .373 1.451 .599 1.588 2.936 Degrees of Freedom Vl 12 8 12 11 12 12 8 12 11 12 50 50 50 50 50 V2 12 8 12 11 12 12 8 12 11 12. 50 50 50 50 50 F Book Fl (1"a/2) 3.28 4.43 3.28 3.47 3.28 3.28 4.43 3.28 3.47 3.28" 1.77 1.77 1.77 1.77 1.77 F2 (a/2) .305 .226 .305 .288 .305 .305 .226 .305 .288 .305 .568 .568 .568 .568 .568 Findings** Reject Reject Reject Reject Reject Reject Accept Accept Reject Reject Reject Accept Accept Accept Reject * Where both points exist. ** Reject HQ if F calc £ F (a/2, V^ V2) or if F calc >. F[(l - a/2), ------- TABLE III-9 (CONT'D) ro o Test 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 Hypothesis a2ELE = a PDS 2 2 a ELE = a PDS a2ELE = a2PDS a2ELE = a2PDS a2ELE » a2PDS 2 2 a ELE = a PDS p. 2 2 a ELE = a PDS 2 2 a ELE = a PDS p «> t*T f — • *» TOT^O 0 £jj_i£j = (J; rUo 2 2 0 ELE — 0' P DS—,-. a2PDS__. = a2PDS EPA a PDS = a PDS a2PDS£pA = a2PDS a2pDSEPA = °2pDS *2pDSEPA = °2PDS F Calculated .0221 .0306 .0357 .2012 .0374 .0429 .5483 2.0915 .2489 .0396 1.9374 17.898 58.57 1.2577 1.0596 Degrees of Freedom Vl 50 50 50 50 50 50 50 50 50 50 12 8 12 11 12 V2 12 8 12 11 12 12 8 12 11 12 12 8 12 11 12 F Book Fl (1"a/2) 2.87 3.81 2.87 3.03 2.87 2.87 3.81 2.87 3.03 2.87 3.28 4.43 3.28 3.47 3.28 F2 (a/2) .450 .407 .450 .442 .450 .450 .407 .450 .442 .450 .305 .226 .305 .288 .305 Findings** Reject Reject Reject Reject Reject Reject Accept Accept Reject Reject Accept Reject Reject Accept Accept ** Reject H if F calc <_ F (a/2, V.^ V£) or if F calc >_ F[(l - a/2), V.^ V ------- TABLE III-10 T-TEST COMPARISON OF TEST METHODS FOR DETERMINATION OF NO CONCENTRATION . . Test 1 ; 2 ;3 * ;5 ii •2 • ;3 i4 5 1 2 3 4 5 Hypothesis yPDSEpA = yPDS yPDSEpA = yPDS yPDSEpA = yPDS yPDS PA = yPDS yPDS£pA = yPDS yPDS = yELE * yPDS = yELE * yPDS = yELE * yPDS = yELE * yPDS = yELE * yPDSEpA = yELE * yPDSEpA = yELE * yPDSEpA = yELE * yPDSEpA = yELE'* yPDSEpA = yELE * t Calculated .00445 .0018 .0805 -3.466 .0858 -0.5347 -0.3176 0.0951 4.2557 -0.3356 -.8159 -1.0631 1.1064 -.3807 -.2234 Degrees c Vl 12 8 12 11 12 12 8 12 11 - 12 . 12 8 12 11 12 >f Freedom V2 12 8 12 11 12 12 8 12 11 12 12 8 12 11 12 . . t Book 2.074 2.3060 2.1784 2.086 2.074 2.2009 2.365 2.2009 2.2298 2.2009 2.1790 2.145 2.074 2.2009 2.1790 Findings** Accept Accept Accept Reject Accept Accept Accept Accept Reject Accept Accept Accept Accept Accept Accept .• 2 2 CT^ - a* / / / / / a2 t a2 ' ' / / / / / / ' 7 * Where both data points exist. ** Reject if |t calc| > t (Book). ------- TABLE 111-10 (CONT'D) Test 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 Hypothesis yELE = yCHEM yELE = yCHEM yELE = yCHEM yELE = yCHEM yELE = yCHEM yELE = yPDS yELE = yPDS yELE = yPDS yELE = yPDS yELE = yPDS yELE = yPDSppA yELE = yPDS yELE = yPDS yELE = yPDSEpA yELE = yPDS t Calculated -2.1723 -2.574 -2.8786 -5.1282 -0.9564 0.4112 0.0372 -0.2925 -4.0367 0.4713 -.6472 -.1784 1.8707 -.5757 -.3625 Degrees of Freedom Vl 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 V2 48 48 48 48 48 12 8 12 11 12 12 8 12 11 12 t Book 2.0079 1.987 1.987 1.987 2.0079 2.199 2.3631 2.1992 2.2183 2.1992 2.0098 2.000" 2.000 2.0184 2.0096 Findings** Reject Reject Reject Reject Accept Accept Accept Accept Reject Accept Accept Accept Accept Accept Accept 02 » 02 / / / / / 02,02 / / / / / / / / ' / ro ro ** Reject if |t calc| >^ t (Book) ------- SECTION IV PROCESS DESCRIPTION The gas turbines located at the Kearny Mesa site were installed in 1969 with the water injection system being installed in 1972. These turbines were manufactured by General Electric Company and are their Model LA-PG 5211. This model has at peak load a rating of 17.2 Mw and a heat rate of 13,950 BTU/Kw (LHV). The base rating and heat rate are 14.6 Mw and 14,500 BTU/Kw (LHV), respectively. These gas turbines consist of a single shaft, two stage impulse turbine driving a sixteen stage axial flow compressor with an electric generator at the exhaust end of the turbine. The sixteen stage axial compressor draws in air, and compresses it, thereby providing a con- tinuous stream of high pressure air to the multiple (10) combustion chambers where fuel is added and burned in an oxygen-rich atmosphere. The resultant hot gases expand through the two stages of the turbine, developing power to drive the axial compressor and to produce useful shaft output for electrical generation. The turbines are started by bringing them up to starting speed with the use of a starting device which for these turbines were diesel engines. The units are also equipped with an atomizing air fuel injection system, which can operate on either distillate oil or natural gas. These turbines are constant speed gas turbines, that is, the speed of the turbine, compressor and generator are constant throughout the load range. The load is varied, however, by changing the generator's electrical field. This requires the fuel flow to also change in order to compensate for this load change and maintain the unit's speed. 23 ------- ro AIR DEMINERALIZED WATER COMBUSTION CHAMBER COMPRESSED AIR .. COMPRESSOR FUEL HOT GASES EXHAUST TURBINE ELECTRIC GENERATOR FIGURE IV-1. SCHEMATIC DIAGRAM OF A SIMPLE CYCLE - SINGLE SHAFT GAS TURBINE ------- The atomizing air system was installed to improve the combustion process. The atomizing air system receives the air from the discharge of the turbine axial compressor and increases it to a pressure level required to obtain the proper energy for atomizing the liquid fuel. The air from the atomizing air system is used to cool and purge the fuel nozzle passages when gaseous fuel is burned. Air atomization has been installed to reduce the opacity of the gas turbine exhaust. Although during startup and shutdown a plume was slightly visible, the opacity was less than 20 percent. There was, however, no plume visible during operation at the various loads, but there was a heavy plume opacity, up to 100 percent, during cutback on load when the control of the turbine was switched from the control room at the site to the main dispatcher. The water injection system was provided to reduce oxides of nitrogen emissions. This system receives water from a water storage tank and forwards it to the turbine at a pressure of up to 200 psig and a flow rate of up to 15 gallons per minute depending on load. The water, when injected, is evenly distributed through a specially con- structed fuel nozzle directly into the reaction zone of the flame. To control the water consumption rate for various loads the injection system is modulated using the turbine exhaust temperature as the parameter for the control of the quantity of water injected. The water is first treated, however, by a demineralizing technique before it is pumped into the storage tank. The quality of the water injected into the gas turbine, as reported.by San Diego Gas and Electric Company, is as follows: 25 ------- Total Dissolved Solids <5 ppm Sodium <1 ppm Potassium <1 ppm Vanadium <1 ppm Lead <1 ppm Modifications were made to the combustion chambers to reduce N0> by increasing the local air flow and extending flame profile. During each test, the operating parameters (load, fuel flow, water flow, etc.) of the turbine were held constant. The turbine was operated at the same load for the first 5 tests. The load was chanaed, however, for tests 6, 8, and 9 to determine its effect on emissions. The water was injected at the same water-fuel ratio throughout the tests except when the turbine was operated at 5 Mw because the water injection automatically shuts off below 7.5 Mw. The control panel meters were monitored throughout the testing program. Table IV-1 summarizes this data. 26 ------- TABLE IV-1 SUMMARY OF OPERATING DATA Unit GT-2A GT-2A GT-2A GT-2B GT-2B GT-2B GT-2B GT-2B Test 1 2 3 4 5 6 8 9 Output (Mw) 16.2 16.0 16.4 16.1 16.16 18.5 10 5 Water Rate (gpm) 11.4 10.8 11.7 11.5 11.6 12.3 - 0 Fuel Flow (gpm) 31.0 30.0 31.3 31.6 31.1 33.8 19.0 15.0 Water-Fuel Ratio (W1b/F.lb) 0.43 0.42 0.43 0.42 0.43 0.42 - 0 Ambient Temperature ( F) 60 64 62 62 66 69 69 69 These turbines were operated on No. 2 distillate oil during all of the tests since natural gas was not available during any portion of the tests. NOTE: No data available for Test 7. 27 ------- SECTION V LOCATION OF SAMPLING POINTS Seven 3" sampling ports were located along one side of the tapered rectangular stack. The ports were approximately 18 inches above the enclosure housing the turbine generator. At the horizontal plane of the sampling ports, the stack inside dimensions were 103" x 129". The double- wall insulated stack terminated approximately twenty feet above the sampling ports. The EPA project officer selected a 49 point traverse for these tests. Figure V-l is a line sketch of the turbine generator enclosure and stack, showing the location and configuration of the sampling ports and points. The ports were labeled A through G from left to right and the points were numbered 1 through 7, the first point located furthest from each port. 28 ------- •^5 r • rf^w ^ s* \ ^K g ! BAFFLES >r 1 i j BAFFLES j / |l 1 \ A JTT^ /^ t 2i i r 18" I J. 1 'X-T-X ^ ^ \ r""A — j \^ V*]^!^ t=~ -y-----JGENERATORj ^iiw*> ' ' . mJL. SIDE VIEW J 12 1 9" 111 A iii A r i ' * * ^ i < i A r 1 ' I V | i A FA) i ' ' i**i Ilk A POINTS 1 THRU 7 • A A A ( • Irfhl A fi~| | 1 A fA~l A " 1 i 1 A fil A 1 1 • l*J • ' i • fail A fAl < • A A A 1 7 / >_- 7 / >- - 7 >-- 7 / k_ _ 1 dG dc dB ^1 u _^ n SECTION A-A npoints where PDS Were Taken FIGURE V-l. LOCATION OF SAMPLE POINTS 29 ------- SECTION VI SAMPLING AND ANALYTICAL PROCEDURES A line diagram of the test apparatus used to draw representative samples of the gas turbine exhaust gases to the various monitors is shown in Figure VI-1. The stainless steel probes, S-type pitot tube, and thermo- couple assembly were field constructed to obtain a tight fit in the ports, j* • thus reducing the amount of stack gases escaping or dilution air entering. The Teflon tubing (1/4 inch) and Teflon-lined pump were used to prevent the sample gases from reacting and changing their chemical characteristics. The inline condensers were used to remove moisture from the sample gases and prevent interference in the various monitors. Three minute representative samples were drawn at each of the 49 test points during the first three test runs but changed to a 2 minute period during tests 4 and 5 to expedite the program. The last four tests (6 through 9) were conducted at a single sample point in the center of the stack. Four methods were used for NO analyses: the grab sample phenoldisulfonic (PDS) A method from Method 7 of December 23, 1971 Federal Register; an experimental integrated lead dioxide (Pb02) method; a continuous electrochemical analy- zer; and a continuous chemiluminescent analyzer. Hydrocarbon emissions were determined with a total hydrocarbon analyzer equipped with a flame ioniza- tion detector (FID). Both a polarographic and a paramagnetic type oxygen sensor were used to monitor 0~ emissions. Carbon monoxide was determined using a double beam infrared analyzer. Calibrations were performed on each of the continuous analyzers prior to and during sampling. For the NO analyses, 204.0 ppm NO and 98.5 ppm N0? were used. The calibrations " ^ . of the FID hydrocarbon analyzer were performed with 459 ppm propane. Cali- brations of the oxygen analyzers were accomplished by exposing the sensors 30 ------- STACK 2" DIA. SHEATH 1/4" STAINLESS TUBING TO SEPARATE PROBE NOX (FbO,) -1/4" HEATED TEFLON TUBING (50 ft) WASTE 0.75 acfm TEFLON LINED PUMP GLASS MANIFOLD NOX (CHEM) KE> HC (FID) NOX (ELECT) STAINLESS STEEL PUMP •1/4" HEATED TEFLON TUBING (16 ft) ICE FIGURE VI-1. DIAGRAM OF TEST APPARATUS CONDENSER ------- to clean, dry ambient air which contains 20.95% oxygen by volume, regard- less of barometric pressure. The infrared CO analyzer was calibrated with 207 ppm CO. All calibrations were performed in accordance with instru- ment instructions. The 98.5 ppm N02 calibration gas was also used to check the PDS method by drawing the calibration gas instead of sample gas into one of the flasks. The resulting analysis yielded 70 ppm versus the actual 98.5 ppm. In addition to these analyses, exhaust gas flow rate and temperature were monitored with an S-type pi tot tube and thermocouple, respectively. For additional information concerning the analyses used in this test program, refer to Appendix E of this report. 32 ------- |