PROJECT NO. 75-CCL-7
                AIR  POLLUTION
                EMISSION  TEST
 O
•Jm
   FINAL REPORT
WESTMORELAND COAL COMPANY
     QUINWOOD
   WEST VIRGINIA
                       MAY 25 1976
          UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
                Office of Air and Waste Management
              Office of Air Quality Planning and Standards
                  Emission Measurement Branch
               Research Triangle Park. North Carolina

-------
                 FINAL REPORT
                       on
   COAL CLEANING PREPARATION PLANT EMISSIONS
         AT WESTMORELAND COAL COMPANY,
            QUINWOOD, WEST VIRGINIA
                       to

         ENVIRONMENTAL PROTECTION AGENCY




                May 14, 1976
                       by

P. R. Webb, J. M. Pilcher, and J. A. Gieseke
                    BATTELLE
              Columbus Laboratories
                 505 King Avenue
              Columbus, Ohio  43201

-------
                        TABLE OF CONTENTS

                                                            Page

INTRODUCTION	   1

SUMMARY AND DISCUSSION OF SAMPLING RESULTS	   5

     Particle Size Results	   5

          Process Coal Sieve Results.	   5
          Particulate Collected by the Scrubber 	   7
          Cyclone Catch Analyses	17
          Scrubber Inlet Measurement Results	24
          Scrubber Outlet Results 	  24
          Total Solids in Scrubber Outlet Water 	  29

     Opacity Measurements 	  30

     Data Applicable to All Five Runs	39

     Trace Metal Results	41

LOCATION OF SAMPLING POINTS 	  41
          Inlet to Venturi Scrubber . .	  41
          Outlet of Mist Eliminator	44

PROCESS DESCRIPTION AND OPERATION 	  47
          Process Description 	  47
          Emission Control Equipment	49
          Process Operation 	  49

SAMPLING AND ANALYTICAL PROCEDURES	51

     Coal Sample Collection Method	 .  51
     Scrubber Water Collection	53
     Particle Sizing Methodology	55

          Distribution Change Due to Drying 	  56
          Effect of Ultrasonic Dispersion Compared With
            Mechanical Dispersion 	  56
          Ultrasonic Cleaning of Alundum Thimble	59
          Relative Comparison—Particle Concentration ...  62
          Representative Aliquots From Large
            Electrolyte Volumes 	  63
          Coal Particle Solubility	  63

REFERENCES	  65

-------
                         TABLE OF CONTENTS
                            (Continued)


                                                                  Page

                            APPENDIX A

COMPLETE PARTICULATE RESULTS 	   A-l
     Sample Calculations—Outlet Run No.  4	   A-6

                            APPENDIX Bl

VISIBLE EMISSIONS OBSERVATIONS DURING PARTICULATE  SAMPLING  ...   Bl-1
     Summary and Discussion of Visible Emissions  	   Bl-1
     Method 9 Report	   Bl-3

                            APPENDIX B2

TOTAL VISIBLE EMISSION DATA	   B2-1

                            APPENDIX C

FIELD AND LABORATORY DATA RELATED TO PARTICULATE  SAMPLING   ...   C-l
     Preliminary Data	   C-l
     Sample Run Data   	   C-7
     Molecular Weight Calculations 	   C-28
     Field Analytical Data	   C-34
     Sample Drying Data	   C-46
     Visible Emission Field Data	   C-75
     Cyclone Field Data	   C-166

                            APPENDIX D

SAMPLE COLLECTION LOG  	   D-l
     Sampling Task Log	   D-4

                            APPENDIX E

PROCESS OPERATION FIELD DATA 	   E-l

                            APPENDIX F

SAMPLE IDENTIFICATION LOG	   F-l

                            APPENDIX G
CYCLONE SAMPLE LOG AND ANALYTICAL RESULTS	   G-l

                            APPENDIX H

DIAGRAM OF SAMPLE EQUIPMENT SERIES CYCLONES INCLUDING
  CALIBRATION DATA	   H-l

                            APPENDIX I

DETAILED STANDARD SAMPLING AND ANALYTICAL PROCEDURES  	   1-1
     Particle Size Analysis by Mine Safety
       Appliance Particle Size Analyzer   	   1-4
                                ii

-------
                  TABLE  OF CONTENTS
                      (Continued)
                        APPENDIX  J.

PROJECT PARTICIPANTS AND TITLES	   J-l
                     LIST  OF TABLES

Table 1.   Sieve Analyses of Coal Samples From West-
           moreland Coal Company	      5

Table 2.   Subsieve Particle Distribution of Westmoreland
           Coal Company Samples by MSA Particle
           Size Analyzer	      8

Table 3.   Size Distribution Comparison of Thimble
           Catches and Scrubber Water Suspension by Coulter
           Counter From Westmoreland Coal Company	     16

Table 4.   Test Data	     18

Table 5. .  Analytical Data For Particle Size Runs With
           Multiple-Cyclone Sampler. .__. .  . . ._	     19

Table 6.   Summary of Results of Particle Size Runs	     20

Table 7.   Inlet Measurement Results Summary (English Units)     25

Table 8.   Inlet Measurement Results Summary (Metric Units).     26

Table 9.   Outlet Measurement Summary Results
             (English Units) 	     27

Table 10.  Outlet Measurement Results Summary (Metric Units)     28

Table 11.  Scrubber Water Analysis 	     29

Table 12.  Frequency Observation Averages Exceeding Stated
           Opacity for Particulate Sampling Only 	     31

Table 13.  Frequency Observation Averages Exceeding Stated
           Opacity for Total Opacity Data	     3~2

Table 14.  Opacity Observation Summary  	     40

Table 15.  Optical Emission Spectroscopy Analysis for
           Trace Metals (Run No. 4)	     42

Table 16.  Traverse Port Locations—Inlet	     45

Table 17.  Traverse Port Locations—Outlet	     46

-------
                      LIST  OF  TABLES
                         (Continued)

                                                                Page

Table 18.  Production Rates (June 25, 1975) ..........   50

Table 19.  Particles Generated From Ultrasonic Thimble
           Cleaning, Coulter Counter Analyses .........   61

Table A-l. Inlet Results ...................   A-l

Table A-2. Outlet Results ...................   A-3

Table A-3. Orsat Gas Composition Measured at Outlet Stack —
           Westmoreland Coal Company, Quinwood, West Virginia.   A- 5



                      LIST  OF  FIGURES

Figure 1.   Process Coal Sieve Analysis ............    6

Figure 2.   Subsieve Size Distribution of Process Coal by
            Coulter Counter ..... .............    9

Figure 3.   Subsieve Size Distribution of Process Coal by
            Mine Safety Appliance Particle Size Analyzer ...   10

Figure 4.   Comparison of Run 2 Thimble Catch and
            Associated Scrubber Water Suspension, Coulter
            Counter Analyses .................   12

Figure 5.   Comparison of Run 4 Thimble Catch and
            Associated Scrubber Water Suspension, Coulter
            Counter Analyses .................   13

Figure 6.   Comparison of Run 5 Thimble Catch and
            Associated Scrubber Water Suspension, Coulter
            Counter Analyses .................   14

Figure 7.   Comparison of Run 6 Thimble Catch and
            Associated Scrubber Water Suspension, Coulter
            Counter Analyses .................   15
Figure 8.   Particle Size Distributions of Cyclone Catches
            Coulter Counter Analyses .............     22

Figure 9.   Sample Point Location ...............     23

Figure 10.  Opacity Observation Sites .............     33

Figure 11. -Run No. 1 Opacity Results as a Function of
            Time of Day ....................     34
                               iv

-------
                      LIST  OF FIGURES
                         (Continued)

                                                               Page

Figure 12.  Run No. 2 Opacity Results as a Function of
            Time of Day	35

Figure 13.  Run No. 3 Opacity Results as a Function of
            Time of Day	36

Figure 14.  Run No. 4 Opacity Results as a Function of
            Time of Day	37

Figure 15.  Run No. 5 Opacity Results as a Function of
            Time of Day	   3£

Figure 16.  Inlet Stack Special Adapter With Gate Valve
            Showing Position of Alundum Thimble Prior
            to Sampling	43

Figure 17.  Inlet Stack Geometry Showing Sampling Location
            and Sample Point Configuration 	   45

Figure 18.  Outlet Stack Geometry Showing Sampling Location
            and Sample Point Configuration 	   46

Figure 19.  Exhausting-Type Fluidized-Bed Thermal Coal Dryer,
            Showing Component Parts and Flow of Coal and
            Drying Gases, Westmoreland Coal Company, Imperial
            Smokeless Division, Quiiiwodd, West Virginia  ...   48

Figure 20.  Coal Sample Collection Method	52

Figure 21.  Schematic of Venturi Scrubber Water Flow System.  .   54

Figure 22.  Distribution of Dried and Undried Coal Samples
            From a Thimble Catch, Coulter Counter Analyses .  .   57

Figure 23.  Comparison Distribution of Wet and Dry Sieved
            Process Coal Samples	   58

Figure 24.  Comparison of Ultrasonic and Medicine Dropper
            Dispersion Techniques, Coulter Counter Analyzer.  .   60

Figure 25.  Representative Aliquot Check of Large Solution
            Volume Having High-Particle Density, Coulter
            Counter Analyses 	   64

Figure H-l. Series Cyclone Sampling Apparatus Block
            Diagram	   H-l

-------
                      LIST OF FIGURES
                        (Continued)
Figure H-2.   Cut-off Point Versus Flow Rate Calibration
             Curves for EPA Series Cyclone	    H-2

Figure H-3.   Cyclone Collection Efficiency Calibration
             Data	    H-3
                             VI

-------
             COAL CLEANING PREPARATION PLANT EMISSIONS
                   AT WESTMORELAND COAL COMPANY,
                      QUINWOOD, WEST VIRGINIA
                                by
          P. R. Webb, J. H. Pilcher, and J. A. Gieseke
                           INTRODUCTION

          In accordance with Section 111 of the Clean Air Act of 1970,
the Environmental Protection Agency is charged with the responsibility
of developing standards of performance for emissions from new stationary-
sources (New Source Performance Standards) which may contribute signi-
ficantly to air pollution.   A standard of performance developed under
the Act for emissions of air pollutants must be based on the "best emission
reduction systems that have been adequately demonstrated, taking into
account economic considerations.
          The development of standards of performance utilizes emissions
data for pollutant sources in the particular industry being studied.  In
response to comments on the proposed emission standards by the coal clean-
ing industry, the emission control systems (venturi scrubbers) of the
Westmoreland Coal Company, Quinwood, West Virginia, were selected by
EPA for an emission testing program to provide test data by which the
effectiveness of that emission control system could be compared with other
facilities previously tested.
          The Westmoreland Coal Company contested the proposed standards
as a result of their preliminary tests which indicated that their specific
type of coal could present an emissions control problem not previously
considered by EPA.  The Westmoreland data implied that the particle size
of the particulate matter entering the venturi scrubber device was finer
than had previously been acknowledged.  The data indicated that one type
of coal (Sewell) processed at the Quinwood plant presented different size
characteristics than coal on which the proposed standards were based.

-------
In order to adequately evaluate these allegations, EPA decided to conduct
an extensive test program at the Quinwood facility.
    Goal delivered to the plant is crushed to a variety of sizes and then
washed, screened, and separated by both water and concentration tables.
The coal washing occurs in a continuous process which reduces ash content .
from 16 to 3 percent.  The 0 x 3/8-inch size of coal of interest in this
study is dewatered by vacuum discs, then dried in a fluidized bed.  Coal
drying is accomplished by use of flue gas (produced by a coal-fired
furnace) reduced in temperature by dilution air.  The fluidized bed is
contained in a chamber loaded with 40 or more multiclones which separate
the coal from the fine dusts.  Dust particles pass from the multiclones
of the dryer through a high-pressure blower to a venturi scrubber, then to
a large mist eliminator, and finally out an 81-inch-diameter stack.
    EPA requested Battelie-Columbus to: sample particulate and gas-
eous emissions from the inlet and outlet stacks of the venturi scrubber
control device at the Westmoreland Coal Company, Quinwood, West Virginia.
The test program was conducted from June 18, through June 25, 1975
during the times the plant was processing Sewell coal.  High mass loading
at the inlet required the use of an in-stack Alundum* thimble (in con-
junction with an EPA Method 5 train).  Tests  for particle  size
distribution of the inlet particulate were made by EPA utilizing a special
multilpe-cyclone sampler.  Grab samples of the process coal and ven-
turi scrubber water were taken simultaneously with the particulate and
gaseous measurements.  The purpose of the aforementioned measurements
is to provide EPA with additional data for support of their standards
development efforts.
    In order to evaluate the effect of particle size on the venturi
scrubber equipment it was necessary to determine the particle size dis-
tribution of the particulate matter entering the scrubber for each type
coal.  Particle size comparison by sieve analysis was conducted on both
types of process coal (Sewell and Pocahontas).  Particle sizes of the sus-
pended particulate at the scrubber inlet, suspended particulate in the
* Mention of trade names does not constitute endorsement or recommendation
  for use by the Environmental Protection Agency.

-------
scrubber water, and <325 mesh process coal from the sieve analysis were
                             (I)*
determined by Coulter Counterv ' .  A Mine Safety Appliance Particle Size
        (2}
Analyzer    was also used to determine the particle size of the <325 mesh
particulate in an effort to substantiate the test results as determined
by Coulter Counter.  Particle size data, as presented in the figures
throughout this report , were determined from one aliquot per sample unless
otherwise noted.
     Since the effectiveness of the venturi scrubber was in question rel-
ative to the process coal particle size, additional effort was placed on
determining venturi inlet particulate size distribution.  A special EPA
series cyclone was used to futher evaluate the size cut of the inlet
particles.
     Trace metals in Run No. 4 outlet emission samples were determined by
optical emission spectroscopy.
     Present opacity of the outlet stack emissions was monitored by two
 certified observers during the particulate sampling.  The test program
 was conducted  to determine mass concentration levels and size distribu-
 tions of particulate emissions during normal plant operation.  Process
 conditions were carefully observed and tests were performed only when the
 process operations appeared to be operating normally.  Process and/or
 scrubber malfunctions occurred during Runs 2, 3, and 5 at which time the
 particulate sampling was terminated.  Opacity readings continued through-
 out the entire period including times when high values were observed
 because of scrubber malfunction.
     A total of five outlet and six inlet runs were made for particulate
 loading.  Run No. 1 inlet was voided due to incorrect  (Pocahontas) coal
 being processed.  Run No. 2 outlet was not considered valid due to an open
 circuit in the probe heater and a leak in the filter which allowed some
 particulate to pass through into the impinger catch.  Run No. 3 inlet was
 voided due to nonrepresentative sampling caused by incorrect placement of
 the sampling nozzle and, therefore, incorrect sampling point location.
 Inlet Runs No. 4, 5, and 6 and outlet Runs 3, 4, and 5 were essentially
  *
   References are given on page 65.

-------
simultaneous and considered valid.   The following  sections  of  this  report
cover the summary of results,  process description  and  operation,  location
of sampling points, and sampling and analytical procedures.

-------
                 SUMMARY AND DISCUSSION OF SAMPLING RESULTS

                            Particle Size Results

    Process  Coal Sieve Results

         The  effectiveness of a venturi scrubber is, among other factors,
    related  to the particle size of the effluent to be  scrubbed.   To better
    understand and evaluate the final outlet emission results  of this study
    it  is  pertinent to obtain a size distribution of the bulk  process coal.
    Figure 1 graphically depicts the sieve analysis results  of two types  of
    coal processed by the Westmoreland Coal Company.   (Run No. 1 is probably
    an  unknown composite of both Sewell and Pocahontas  types of coal.) The
    size distributions of the Sewell process coal used  during  outlet Runs 3,
    4,  and 5 show very good agreement.  As indicated, the Sewell coal has a
    mass mean diameter of 1000 pm with approximately 3  to 4  percent being less
    than 325 mesh (44 pjn).  The Pocahontas coal, as indicated  in Figure 1,
    is  relatively smaller than the Sewell coal having a mass mean diameter
    of  250 um, but with approximately 4 percent being smaller  than 325 mesh.
    Table  1 is a tabular summary of the Sewell and Pocahontas  sieve analysis
    data.
                     TABLE 1.  SIEVE ANALYSES OF COAL SAMPLES FROM
                             WESTMORELAND COAL COMPANY
Sieve Size
U.S. Sieve Screen Opening,
Number \m
4
8
16
30
50
100
200
325
Pan (-325)
4,760
2,380
1,190
590
297
149
74
44
<44
Particle Size
Range Collected
per Stage, yjn
>4760
2380-4760
1190-2380
590-1190
297-590
149-297
74-149
44-74
<44
Accumulative Weight-
Percent Retained per
Stage and Smaller Stages
Run 1
100.0
90.3
72.5
54.0
38.5
25.2
fl 16.7
10.8
3.7
Run 3
100.0
92.9
75.8
57.5
41.7
27.9
17.9
11.6
3.1
Run 4
100.0
91.0
72.4
53.4
38.2
25.7
17.1
11.3
2.9
Run 5
99.9
91.5
73.1
53.9
38.3
25.2
16.4
10.5
3.9
Pocahontas
100.0
97.8
92.5
84.2
. 72.2
54.9
36.4
21.8
4.0
    ^  Run No. 2 discarded  _.      	
(a)  Sample size approximately" 900 grama (2~ Ib)

-------
y»
98
95
90
80
? 70
o>
* 60
>.
* 50
*-
§ 40
I 30
 on
V- ^u
o
1 10
O
5
2
1
0.5
0.2
O.I
2




























•*
/
f














L
¥














/
*
X















X
X














ft
'















x
t*















X
X













^
^
^
^












J.
^

^












_^
V\


H















^
















T

^
^1









kx
?












X


X













X*


X












fX



X


I
(
i
\






_fS
^

/
&





-tlS^

JT"






^

X






>
^
^






3 Pocohantusi
3 Run 1 Composite
^ Run 3-1
\. Run 4 	 Sewell -
^ Run 5-J
















0 30 40 60 80 100 200 300 400 600 800 1000 2000 3000 50(
       Particle Diameter, micrometers
FIGURE 1.   PROCESS COAL SIEVE ANALYSIS

-------
     In order to evaluate the proportion of ultrafines (<2 |jjn) that is
of primary importance relative to venturi scrubber effectiveness, Coulter
Counter analyses of the subsieve fraction (<325 mesh) were performed for
the indicated runs.  The results are shown in Figure 2.  Again the size
distribution for the Sewell coal for outlet Runs 3, 4, and 5 show good
agreement, the mass mean diameter being approximately 17 pm and approxi-
mately 1 to 2 percent being less than 2 pm.  The Pocahontas coal has
more fines than the Sewell coal, with a mass mean diameter of approximately
12 p,m and approximately 2.5 to 3 percent being less than 2 pjn.  Therefore,
with all other factors equal, the Sewell coal emissions are no more dif-
ficult to collect with venturi scrubber equipment than the Pocahontas coal
emissions.
     The Mine Safety Appliance Particle Size Analyzer results as depicted
in Figure 3 essentially substantiate the Coulter Counter results for the
Sewell samples but shows the Pocahontas and Sewell with essentially an
equal size distribution except in the relatively smaller size fractions
where scatter in the data occurs.  If one averages the MSA data in the
smaller size fraction, 2 to-3 percent of the size distribution is less
than 2 am; this agrees with the Coulter Counter data of Figure 2.  Table
2 is a tabular summary of the Sewell and Pocahontas results for size
measurements with the MSA Particle Size Analyzer.

Particulate Collected by the Scrubber

     It is to be expected that the venturi scrubber used to clean partic-
ulate from the effluent gas stream will remove large particles more
efficiently than smaller particles.  To directly measure such effects,
mass concentrations and size distributions are required for particles in
the gas stream entering the scrubber and in the scrubber water.  Because
of the time averaging effect of scrubber water recirculation, a direct
measurement of particulate mass collected in the water over the inlet
gas sampling time was not possible.  The scrubber water samples were col-
lected over a very short time interval and, hence, a time averaged value
for the particulate collected by the water prior to the sampling time
was determined.

-------
                              TABLE 2.   SUBSIEVE PARTICLE  SIZE  DISTRIBUTION OF WESTMORELAND
                                        COAL COMPANY  SAMPLES  BY MSA PARTICLE SIZE
                                        ANALYZER(a)
Particle
Size, \m
60
50
40
35
25
20
15
12
10
8
6
4
2
1
0.8
Weight Percent of
Run 1
•• «
100.0
98.1
97.1
79.2
63.3
43.7
33.1
26.8
18.5
12.2
5.3
1.3
0
—
Run 3
— —
100.0
97.6
95.3
79.2
63.4
46.7
31.9
25.8
22.5
15.5
6.4
0.7
0
--
Run 4
« ••
100.0
97.1
94.9
76.1
62.5
47.5
39.1
29.4
21.3
12.9
9.2
5.9
0
--
<44 \m Portion(b)
Run 5
— —
--
100.0
97.2
78.3
65.0
48.3
38.5
30.8
21.7
14.0
8.4
4.9
0.7
0
Pocahontas
100
97
93
91
73
57
42
32
25
17
9
4
1
0
-
.0
.5
.7
.2
.3
.5
.9
.9
.0
.1
.6
.6
.3

-
Weight Percent of Total Sample^)
Run 1
— .
3.70
3.63
3.59
2.93
2.34
1.62
1.22
0.99
0.68
0.45
0.20
0.05
0
--
Run 3
__
3.10
3.03
2.95
2.46
1.97
1.45
0.99
0.80
0.70
0.48
0.20
0.02
0
--
Run 4
•. M
2.90
2.82
2.75
2.21
1.81
1.38
1.13
0.85
0.62
0.37
0.27
0.17
0
--
Run 5
— «•
--
3.90
3.79
3.05
2.54
1.88
1.50
1.20
0.85
0.55
0.33
0.19
0.03
--
Pocahontas
4.00
3.90
3.75
3.65
2.93
2.30
1.72
1.32
1.00
0.68
0.38
0.18
0.05
0
--
Note:  Run No. 2 discarded.
(a)  Sedimentation liquid—isopropyl alcohol;  feed liquid--50 percent  isopropyl  alcohol,  50 percent heptane.
(b)  Data are reported as less than indicated  size.
                                                                                                                  00

-------
.c
 *
C
0)
u
^
(U .
a.
0)
3
E
3
o
99.9
99.8

99.5
  99
  98

  95

  90

  80
  70
  60
  50
  40
  30

  20

   10
      2
       I
    0.5
    0.2
     O.I
O Run 1
£ Run 3—
QRun 4
-J- Run 5-
   Pocahontas
       0.6  0.8   I
                                  4      6   8   10         20
                            Particle Diameter, micrometers
                    40    60
                    FIGURE"2.'  SUBSIEVE"SIZE DISTRIBUTION OF PROCESS COAL
                               BY COULTER COUNTER

-------
                                        10
o»
"55
c
0>
u
k.
«
a.

0>
 £
 3
o
)9.8
9.5
99
98
95
90
80
70
60
50
40
30
20
10
5
2
1
0.5
0.2
O 1

























































.^



















£
















m
\
/£
^ L
















»-
1
3
\
















\
^A
/ I


















r
j

















j
' i


















Y
J

















c
'I


















t>
J

















^
i















S

*

/'
^

j«






x
1
r
]



Q Run 1
/^ Run 3-,
•^
V
a i
Run 4
Run 5-
Pocahoi







/


i
\


r













Composite
— SewelT
atas






























       0.6  0.8
      4      6   8   10          20

Particle  Diameter, micrometers
40
60
              FIGURE  3.   SUBSIEVE SIZE DISTRIBUTION OF PROCESS~~COAL BY"

              	MINE SAFETY APPLIANCE PARTICLE SIZE ANALYZER

-------
                                  11
However, the samples were collected to determine if any differences be-
tween inlet suspended particulate and scrubber water particulate existed.
These differences could lead to significant inferences regarding scrubber
collection efficiency as dependent on particle size.
     The size distribution curves given in Figures 4, 5, 6,  and 7 allow
comparisons between suspended inlet particulate and scrubber collected
particulate for Runs 2, 4, 5, and 6, respectively.  Inlet Runs 1 and 3 were
voided as explained in the Introduction.  The results may appear to be
inconclusive because of the data in Figures 4 and 5» which show less partic-
ulate below about 2 \m in the scrubber water than in the inlet gas, and
Figures 6 and 7, which show the reverse.   Table 3 is a tabulation of these
data.  Within the error of the particle sizing methods, the  data show
that the particle size distribution in the scrubber water is practically
the same as the distribution at the scrubber inlet.  This result could
be predicted when the scrubber collects essentially all of the particulate
matter.  Data of this type cannot be used to obtain size dependent col-
lection, efficiencies.  Any major impact on control effectiveness would
occur only if a sufficiently large fraction of the particulate material
had sizes too small for efficient collection.  Size distributions for the
suspended inlet particulate indicate that only about 5 percent of the particles
have sizes below about 2 pm.  This low fraction in the small size range
makes comparison impractical since the small sizes constitute a nearly
negligible portion of the particulate for measurement purposes.  If, how-
ever, the differences between the curves are attributable to normal
scatter in the experimental data, as is likely, it can be concluded that
the overall efficiency is not sensitive to low collection efficiency for
these small sizes.  This is because such a small fraction of the total
entering particles are smaller than the size where efficiency drops off.
Therefore, valid conclusions that can be drawn from these data are that
the venturi scrubber essentially collects all sizes of particulate in
excess of 2 yjn.  The amount of particulate matter less than  2 micrometers
that reduces the scrubber's collection efficiency is not significantly
different for Sewell coal as compared with Pocahontas coal.

-------
                                 12
                                                     TH-2

                                                     Scrubber Water
0.6 0.8  I
      4     6    8  10         20
Particle Diameter, micrometers
40    60
             FIGURE 4.  COMPARISON OF RUN 2 THIMBLE  CATCH
                        AND ASSOCIATED SCRUBBER WATER SUSPENSION,
                        COULTER COUNTER ANALYSES

-------
                                 13
                                                     TH-4
                                                     Scrubber  Water
0.6 0.8  I
      4      6    8  10         20
Particle Diameter, micrometers
40    60
           FIGURE 5.   COMPARISON OF RUN 4 THIMBLE CATCH AND
                      ASSOCIATED SCRUBBER WATER SUSPENSION,
                      COULTER COUNTER ANALYSES

-------
                                14
0.6 0.8  I
      4      6   8   10         20
Particle Diameter, micrometers
40    60
          FIGURE 6.  COMPARISON OF RUN 5 THIMBLE CATCH AND
                     ASSOCIATED SCRUBBER WATER SUSPENSION,
                     COULTER COUNTER ANALYSES

-------
                                15
                                                    TH-6

                                                    Scrubber Water
0.6 0.8
      4     6    8  10         20
Particle Diameter, micrometers
40    60
           FIGURE  7.  COMPARISON OF RUN 6 THIMBLE CATCH AND
                     ASSOCIATED SCRUBBER WATER SUSPENSION,
                     COULTER COUNTER ANALYSES

-------
                    TABLE 3.  SIZE DISTRIBUTION COMPARISON OF  PARTICLES  ENTERING
                              THE SCRUBBER AND PARTICLES  CAUGHT  BY  THE SCRUBBER
                              WATER(a),  FROM WESTMORELAND COAL COMPANY
                                    (Percent less than indicated size)
Particle
Size, (j,m
44.2
35.1
27.8
22.1
17.5
13.9
11.1
8.8
7.0
5.5
4.4
3.5
2.8
2.2
Run
Thimble
Catch
_-
--
--
100.0
91.87
91.13
81.52
70.98
63.11
53.00
41.33
28.89
17.68
9.48
2
Scrubber
Water
--
100.0
94.81
94.29
89.61
85.58
78.11
70.02
60.80
50.43
46.38
29.87
17.67
7.57
Run
Thimble
Catch
--
100.0
98.89
98.34
95.43
91.20
83.37
75.48
66.11
53.83
40.70
26.95
14.82
9.53
4
Scrubber
Water
100.0
97.88
96.82
94.70
91.25
85.94
79.47
70.03
60.75
51.00
38.41
26.71
14.15
5.93
Run
Thimble
Catch
--
—
100.00
98.27
97.11
92.78
86.78
79.04
69.67
57.55
40.95
24.51
12.36
5.54
5
Scrubber
Water
--
—
—
100.00
98.33
93.13
86.47
80.63
71.78
60.53
48.15
34.07
20.47
10.02
Run
Thimble
Catch
--
100.0
97.12
94.26
92.79
85.58
78.42
71.14
61.73
44.97
29.89
16.54
9.03
4.90
6
Scrubber
Water
--
100.0
98.96
93.24
90.90
81.54
74.45
67.52
58.60
48.65
38.03
27.83
14.83
7.61
(a)  Size distribution of thimble particle catch and scrubber water particle suspension determined
    by Coulter Counter using an aperture diameter of 100 pjn, and a manometer volume of 500 y&.

-------
                                  17
Cyclone Catch Analyses

     Tests were conducted using a sample train consisting of two aluminum
cyclones followed by a glass fiber filter.  The purpose of the tests was
to determine the mass loading of particulates less than 2.5 \ua in diam-
eter.  All tests were conducted at the inlet to the scrubber.  The testing
cyclones were developed by an independent contractor for the Environmental
Protection Agency.  Since the equipment had not been previously used by
the tester, numerous problems were encountered until a sampling technique
was established.  A total of 13 runs was conducted.  During the first six
runs, problems were encountered with the testing; Runs 7-13 were valid
tests.  However, during Runs 8, 10, and 12, the process was operating under
a light load.  Furthermore, Run 13 was conducted when Type 7 Sewell sur-
face-mined coal was being processed.
     Tables 4 and 5 summarize the test data and analytical data.  Table 6
summarizes the test results.  The tests were conducted at a nominal flow
rate of 1 acfm, yielding cut-off points of 2.5 and 1.0 \aa for the first
and second cyclones, respectively.  Therefore, the particulate less than
2.5-p,m diameter was calculated as the total mass minus the mass collected
in the first cyclone.
     Two tests with a cascade impactor were attempted, but were not suc-
cessful.  In one case, the stages were overloaded, and in the other case,
the collection substrates were knocked ajar.
     Table 6 summarizes the test results.  As previously noted, Tests 7-13
were considered the best tests as far as sampling procedures are concerned.
In performing the calculations, an average stack gas moisture (9.9 percent)
                                       fUitA-
calculated from the five Alundum thimble/flwas used.  The results presented in
Table 6 show a reasonable correlation between the Alundum thimble and cyclone
methods for determining particulate concentration of particles less than
2.5 ym diameter.  For cyclone Runs 7-13 the mass percent less than 2.5 ym
ranged from 11.6 to 17.6 percent with an average of 14.5 percent.   For
the Alundum thimble Runs 2, .4, 5, and 6, the mass percent less than 2.5 ym
ranged from 7 to 15 percent with an average value of 11.5 percent.

-------
                                 TABLE 4.   TEST DATA FOR PARTICLE  SIZE  RUNS  WITH MULTIPLE-CYCLONE SAMPLER
Run
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
Dace
6/18
6/19
6/19
6/20
6/20
6/23
6/23
6/25
6/25
6/26
6/26
6/26
6/26
Sample
Start Port Period
Time Identification (minutes)
1800
1415
1715
1115
1445
1700
2000
1005
1255
1650
1225
1420
1550
S
S
S
E
E
E
E
E
E
S
S
E
S
22
10
11
11
11
11
11
11
11
11
11
11
11
Meter
Volume
(acf)
22.345
8.000
10.520
7.230
9.050
8.675
8.600
8.520
8.525
—
7.895
8.600
8.715
Stack
Temp.
(F)
190
190
170
170
170
200
200
155
150
170
180
180
180
Nozzle
Diameter
(inches)
0.4375
0.4375
0.4375
0.4375
0.4375
0.1875
0.1875
0.1875
0.1875
0.1875
0.1875
0.1875
0.1875
Absolute
Stack
Pressure
(in. Hg)
29.68
29.80
29.80
29.80
29.80
29.81
29.81
29.74
29.74
29.74
29.63
29.63
29.63
Volume
Sampled
(dscf)
20.16
7.24
9.52
6.54
8.20
7.84
7.75
7.68
7.68
—
7.08
7.72
7.82
Sample
Rate , .
(acfm)(a)
1.3
1.0
1.1
0.8
1.0
1.0
0.9
0.9
0.9
—
0.9
1.0
1.0
Percent
Isokinetic
(b)
(b)
(b)
(b)
(b)
(b)
77.8
78.5
78.5
—
85.2
78.1
77.0
(a)   Stack conditions.
(b)   Used incorrect sample  nozzle.
                                                                                                                                           00

-------
                                  TABLE 5.  ANALYTICAL DATA FOR PARTICLE SIZE RUNS
                                            WITH MULTIPLE-CYCLONE SAMPLER^)
Test
1
2
3
4
5
6
7
8
9
10
11
12
13
First
Cyclone
__
0.3349
1.7575
3.9237
3.6606
1.3006
1.1888
0.5013
1.2658
0.6590
1.6196
1.0512
0.5947
Second
Cyclone
__
N/A
N/A
N/A
2.2320
0.1659
0.1346
0.0535
0.1166
0.0752
0.2217
0.1151
0.0771
Filter
._
0.0620
0.1144
0.1266
0.0229
--
0.0450
0.0278
0.0383
0.0234
0.109
0.000
0.0386
First
Cyclone
Wash
__
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0.0060
0.0035
0.0081
0.0059
0.0048
Second
Cyclone
Wash
__
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0.0076
0.0062
0.0089
0.0172
0.0098
Filter
Assembly
Wash
_ _
N/A
N/A
N/A
0.0085
--
0.0073
0.0048
0.0048
0.0040
0.0086
0.0070
0.0028
First
Cyclone
Total
__
0.3349
1.7575
3.9237
3.6606
1.3006
1.1888
0.5013
1.2718
0.6625
1.6277
1.0571
0.5995
Second
Cyclone
Total
__
N/A
N/A
N/A
2.2320
0.1659
0.1346
0.0535
0.1242
0.0814
0.2306
0.1323
0.0869
Filter
Total
__
0.0620
0.1144
0.1266
0.0314
—
0.0523
0.0326
0.0431
0.0274
0.1176
0.0070
0.0414
Total
_-
0.3969
1.8719
4.0503
5.9241
--
1.3757
0.5874
1.4391
0.7713
1.9759
1.1964
0.7278
(a)  All masses are reported in grams.
N/A Not Applicable.

-------
                                   20
                     TABLE 6.  SUMMARY OF RESULTS OF
                               PARTICLE SIZE RUNS-
Run Number
Cyclones:
1
2
3
4
5
6
7
8
9
10
11
12
13
Alundum Thimbles:
1
2
4
5
6
Mass
Total

---
.84
3.02
9.54
11.13
--
2.73
1.18
2.90
--
4.30
2.39
1.43

2.73
1.79
2.89
3.23
2.67
Loading, gr/scf
Less than
2.5 nm(a>

--
0.14
0.19
0.30
4.25
--
0.37
0.17
0.34
'
0.76
0.28
0.25

--
0.27
0.35
0.39
0.19
*Mass Less
than 2.5 pm,
percent

«• «
15.6
6.1
3.1
38.2
--
13.6
14.7
11.6
--
17.6
11.6
17.6

--
15
12
12
7
                                                                         (a)
(a)   Total mass, less mass collected in first cyclone.

-------
                                  21
     Figures 8 presents the particle size distribution of the cyclone
catches which were analyzed by electronic counter.  Field data sheets are
presented in Appendix C.  Cyclone sample identification and analytical
results are presented in Appendix G.
     Figure 9 indicates the location of the sampling points.  Because of
the design of the equipment only the first 22 points on each traverse
could be sampled.  Each test (Runs 6-13) was conducted using two cyclones
in series with a back-up filter.  The sampling rate was kept constant
during each test at a nominal flow of 1 acfm.  Each test was conducted
across only one traverse and was only 11 minutes in duration.  It was
necessary to limit each test to only one traverse because of the capaci-
ties of the cyclone collection cups.
     Prior to each test the sample train was checked for leaks and then
inserted into the stack (with nozzle plugged) in order to allow the cyclones
to heat to stack temperature.  After a 20-minute pre heat, the cyclones
were removed, the nozzle unplugged, the cyclones reinserted, and the test
begun.
     The sample train was constructed so that the nozzle was inserted
directly into the first cyclone.  The first cyclone was immediately fol-
lowed by the second cyclone and a back-up filter connected to the probe.
During sampling, both cyclones and filter were in-stack.  A flexible hose
was used to connect the probe to a silica gel impinger, vacuum pump, and
dry gas meter, in that order.  Figure H-l of Appendix H is a block diagram
of the cyclone and filter assembly.  Figure H-2 shows the calibration
curves for the cyclones.  Figure H-3 shows the calibration curves for each
cyclone and relates the particle cut-off size, |j,m, as a. function of flow
rate.
     The particulate catch of each cyclone was emptied from the collection
cup into a weighing vessel.  All residual material was brushed into these
vessels using a camel hair brush.  In addition, for Runs 9-13, acetone
rinses were conducted on the cyclones and filter holder.

-------
60.0
                   First cyclone
              Run 2
              Run 7    •
              Run 9    A
              Run II    «
                   Second cyclone
              Run 8
              Run 7    o
              Run 9
              Run II    a
                                                                                                   K)
                                                                                                   to
   0.01
O.I
0.5  I   2
10   20  30 40 50 60 70 80   90
  Percent Mass Less Than D
95  98 99
99.9    99.99
             FIGURE 8.  PARTICLE SIZE  DISTRIBUTIONS OF CYCLONE CATCHES,
                       COULTER COUNTER ANALYSES

-------
                                   23
        South
        Port
Traverse points:
1
2
3
4
5
6
7
8
9
10
11
12
1 inch
2.25
4
5.75
7.5
9.5
11.5
14
16.5
19.5
23.25
28.75
[
13
14
15
16
17
18
19
20
21
22
*23
*24
East
Port
43.25
48.75
52.5
55.5
58
60.5
62.5
64.5
66.25
68
69.75
71
                                                                        •X
    *Not Sampled,
                     FIGURE 9 .  SAMPLE POINT LOCATION

-------
                                  24
     For several cyclone catches, the particle size distribution of
the collected material was determined using an electronic counter.  The
sizing procedures used were the same as those employed for the Alundum
thimble particulate catches.

Scrubber Inlet Measurement Results

          Tables 7 and 8 show computer output tabular summaries (in English
and metric units, respectively) of results of Runs 1 through 6, Run 3 being
aborted because of operator error.  Runs 1 and 2 are not considered representa-
tive relative to outlet comparison but are being presented only as support
data to aid in ascertaining a better understanding of inlet sampling conditions.
Weight concentration for Runs 4, 5, and 6 ranged from 2.68 to 3.23 gr/dscf
(6144 to 7407 mg/Nm3 ) resulting in a mean of 2.93 gr/dscf (6728 mg/Nm3 ).
Isokinetic sampling for Runs 4 to 6 varied from 100 to 106 percent, in spite
of the undesirable working conditions encountered, which is well within the
desired limits of 100 _ 10 percent for producing valid data.

Scrubber Outlet Results

          Tables 9 and 10 show summarized data by computer  (in English and metric
units, respectively) obtained at the outlet stack of the Westmoreland Coal
Company.  Runs 1 and 2, as previously mentioned, are not considered representative
because of plant and/or BCL operator error, but have been presented as
additional support data.
          For Runs 3 to 5, the dry catch (probe and filter) weight con-
centration results are 0.037, 0.059, and 0.035 gr/dscf (86.1, 134.5, and
80.6  mg/Nm3  , respectively.  The impinger catch results for Runs 3 to 5
increased the weight concentrations an average of 25 percent, the total
catch  (probe, filter, and impingers) being 0.054, 0.072, and 0.049 gr/dscf
 (123.2, 164.6,  and  112.9  mg/Nm3 ) , respectively.

-------
TABLE 7.  INLET MEASUREMENT RESULTS  SUMMARY  (ENGLISH UNITS)
WESTMORELAND COAL COMPANY INLET RESULTS
RUN NO. ^
TEST DATE

VOLUME OE GAS SAMPLED, DSCF^'
PERCENT MOISTJRE BY VOLUME
AVERAGE STACK TEMPERATURE, E
STACK VOLUMETRIC FLOW RATE, DSCFM(C)
STACK VOLUMETRIC FLOW RATE, ACFM(d>
PERCENT ISOKINETIC
PERCENT EXCESS AIR
PERCENT OPACITY
FEED RATE, TONS/HR

PARTICULATES - PROBE, CYC, FILTER CATCH
MG
GR/nSCF -
GR/ACF -
LR/HR -
LB/TON FEED


	 	 __1 	
6/ifl

ua.i
It. 2
166
136913
183212
98.6
1072
NA
ND


181t»i*.0
2.729
2.018
3201. 3
ND


	 2 	
6/19

88.8
7.0
16«»
l«»8680
191155
9«».6
1785
NA
ND


9271.0 1
1.785
1. 387
2273.3
ND

ND - No Data (a) Run No> 3 aborted<
(b) Dry standard cubic feet at 70° F, 29.92 in. Hg.
(c) Dry standard cubic feet per minute at 70° F, 29,
(d) Actual cubic feet per minute.
(e) Average includes only Runs 4, 5, and 6.

	 J» _
6/20

90. t«
9.1
171
1<*(«0<»1
190091*
100.0
2«»11
NA
ND


5368.0
2.888
2.187
356<».l
ND

.92 in. Hg

5
6/23

li»0.0
10.7
202
138019
193875
106.1
2267
NA
ND


26167.0
3.225
2.29**
3812.9
ND ..

NA - Not
•

6
6/25
126.6
12.1
181
135899
1880Q(*
99.7
1595
NA
ND


20087.0
2.675
1.932
311U.2
ND

Applicable
(e\
Average v '
119.0
10.6
185
137986
190657
101.9
2091
NA
ND
20540.0
2.929
2.138
3497
ND

                                                                                          Ul

-------
                             TABLE  8.   INLET MEASUREMENT RESULTS  SUMMARY (METRIC UNITS)
WESTMORELAND COAL COMPANY
RUN NO.
TEST DATE

VOLUME OF GAS SAMPLED, NCM
PERCENT MOISTURE RY VOLUME
AVERAGE STACK TEMPERATURE,
STACK VOLUMETRIC FLOW RATE
STACK VOLUMETRIC FLOW RATE
PERCENT ISOKINETIC
PERCENT EXCESS AIR
PERCENT OPACITY
FEED RATE, MTON/HR

PARTICULATES - PROBE, CYC, F
MG
MG/NCM -
MG/CM -
KG/HR -
KG /MTON FEED 	
INLET RESULTS
124
6/18 6/19 6/20

(a) 3.3 2.5 2.6
11.2 7.0 9.1
C 74 73 77
/v \ _ .. _ . _ .
, NCMMV ' 3862 4194 4063
, CMM(C) 5168 5392 5362
98.6 94.5 100.0
1072 1786 2411
NA NA NA
ND ND ND

ILTER CATCH
18144.0 9271.0 15368.0
6269.3 ff099.4 5634.4
	 U 680 .7 	 1185^7 	 5022.5
1452.1 1031.2 1616.7
ND ND ND

5
6/23

3.9
10.7
94
3893
5469
106.1
2267
NA
ND


26167. 0
7407.2
	 5268^2
1729.5
ND

6
6/25 Average

3.6 3.4
12.1 10.6
82 84
3833 3930
5303 5378
99.7 101.9
1595 2091
NA NA
ND ND


20087.0 20540
6144.3 6728.6
4437.2 4909.3
1412.6 1586.3
ND ND
ND - No  Data.
(a)   Normal cubic meter (dry)  20.0 C,  760 mm Hg.
(b)   Normal cubic meter per minute (dry)  at 20.0  C,  760 mm Hg.
(c)   Actual cubic meters per minute.
NA = Not Applicable
                                                                                                                      CT>

-------
                                           27
                   TABLE  9.   OUTLET MEASUREMENT  SUMMARY RESULTS  (ENGLISH UNITS)
HFSTKnPFLftMn. rOAL rOSPAMY flUTl FT O^SULTS
SUN NO. 1 2 •*
TEST TATE 6/18 6/19 6/?0
VOLUME OF GAS SAHPLFD, nSCF(b) 109.5 100.5 106.7
PERCENT MOIST'JRF BY VOLUME It. 8 1 1 . l« 11. 1.
avF^aGE srac< TEMPEPATU°E, F us IDS . no
STACK VOLU^ET = IC FLOW RATE, QSCFn(c> "~ 1325U3 125531. ~ 139320
STACK VOLUMFT°IC FLOW RATE, &CcM 20 ?5
FEFO P!\TE, TOf.'S/HP ND ND ND

PflPTICULATES - PROnF, CYC, FILTER CATCH
M3 . .. ._ 	 	 	 _._. 2 '».'*.'« 	 32_P.l 	 239.6
G9/1SCF - .. 	 O.Q"?8 0.055 0.037
GP/ACF - 	 	 	 	 	 	 ..Q.JJ.29 	 O..0.if_2 	 n.0?9
LR/TON CEEH ND ND ND

PARTICIPATES - TOTAL CATCH

HG 299.7 Ui.a.2 31.2.9
GR/'JS'CP - O.di.7 0.076 0.051.
GP/ftCF - 0.035 0.058 O.Qi.1
LB/H9 - 5?. 9 81.5 6<*.0
LR/TON Fprr) ND jjp ND

PFDCFNT TMPTN:E° CATCH 18.5 26. a 30.1

«. 5
6/23 6/?5
109.2 10«..0
13.2 11.9
116 112
135983 137815
181.17? 182969
103. R 97.1
2?67 15^5
13 20
ND ND

_376.9 ..21 1». 2
0.05C> 0.035
0.0d3 P..026
68.2 Ul. if
ND !!D



'•fSl.if 300.2
0.07? O.DI.O
0.053 0.037
83.5 58.0
ND ND

18.3 28.6


Average
106.6
12.2
113.3
137629
183457
100.6
2091
19
ND

276.9
0.044
0.033
51.4
ND



36S.2
0.058
0.044
68.5
ND

" 25.7
ND - No Data.
(a)   Dry standard cubic feet at 70° F,  29.92 in.  Hg.
(b)   Dry standard cubic feet per minute at 70° F, 29.92 in.  Hg.
(c)   Actual cubic feet per minute.
(d)   Average includes only Runs 3,  4,  and 5.
(e)   Opacity measured only during portion of run.

-------
                                           28
                  TABLE 10.   OUTLET MEASUREMENT-RESULTS' SUMMARY (METRIC UNITS)
WESTMORELAND CO<'«L COMPANY OUTLET .". 30.1

1* 5
'" "6/23 " ~ ' 6V?5 " Average
"3.1 ~2.9 " 3.0
13.2 11.9 12.2
46 I* 1. 44
3836 38fl7 3S84
5195 5161 5171
103.8 97.1 100.6
2267 1595 2091
13 20 19
' ND ND ND


376.9 211*. 2 276.9
131*. 5 flO.6 100.4
99.2 60.6 75.1
30.9 13.8 23.3
ND ND ND



1.61.1* 300.2 368.2
16i*. 6 112.9 133.6
121.'. 85.0 100.1
37.9 26.3 31.1
ND ND ND

IB. 3 28.6
ND - No Data.
 (a)   Normal cubic meter (dry)  at 20.0 C,  760 mm Hg.
 (b)   Normal cubic meters  per minute  (dry)  at 20.0  C,  760 mm Hg.
 (c)   Actual cubic meters  per minute.

-------
                                   29
          Inlet and outlet volumetric flow rates compare reasonably well
when considering the relatively poor inlet sampling location.   Insufficient
downstream stack diameters from the inlet sampling location did not allow
sufficient time to establish a uniform flow profile; the end result being
a poor velocity profile which could be a reasonable explanation for the
inlet and outlet volumetric flow rate difference.
          Moisture condensation in the outlet stack and reentrainment of water
droplets resulted in the effluent gases being supersaturated and, thus, the
stack gas moisture content of the gases was greater than the moisture cor-
responding to the dew point.
          Complete particulate results by computer, which include additional
operational data, and sample calculations for outlet Run No. 4 can be seen in
Appendix A.

Total Solids in Scrubber Outlet Water

         Solids in the scrubber water samples were determined by passing
a 50-ml aliquot of the scrubber water through a tared 45-mtn glass fiber filter.
The sample was then dried to a constant weight.  Table 11 shows the results
for the indicated runs.

                TABLE 11.  SCRUBBER WATER ANALYSIS
Outlet
Run No.
2
3
4
5
Total Solids,
percent
7.64
8.69
7.74
6.94

-------
                                   30
                          Opacity Measurements

           Visible emissions were observed by two BCL certified smoke
 readers simultaneous with particulate sampling.   During the five runs,
 opacity values ranged from 10-30 percent.  Particulate sampling was
 terminated during periods of time when the venturi scrubber was malfun-
 tioning.  Opacity readings for the most part were taken during all periods.
 A complete summary of the data is presented in Appendix B-l and B-2. Tables
12 and 13 are computer summaries of Appendices B-l and B-2  and list the
frequency each observer exceeded the stated opacities.
           In order to make it easier to interpret this large amount  of
 data a graphic presentation of each run has been prepared  and is presented
 in Figures 11 through 15.  Each graph shows the  percent opacity as a
 function of time of day for the total reading period for each test.   Runs
 3 and 5 have been divided into A and B sections  because of relatively long
 interruptions in opacity observations and also to facilitiate computer
 data reduction.  Also shown on the graphs, by means of horizontal arrows,
 are the time periods during which "Particulate Sampling" occurred.  These
 graphs make it possible to quickly determine the ranges of visible emissions
 during particulate sampling times for each of the five test runs. Because
 opacity readings were continued when scrubber malfunctions occurred, abnormal
 values of visible emissions may have been observed.  Emphasis should be
 placed only on the visible emission data obtained during particulate sampling.
 Figure 11 shows the relative positions of the observation  sites with respect
 to the outlet stack and adjacent structures.  Site B was used for opacity
 reading in the mornings and Site A in the afternoons.

-------
TABLE 12.  FREQUENCY OBSERVATION AVERAGES EXCEEDING STATED
           OPACITY FOR PARTICULATE SAMPLING ONLY

F^£r
~~uX I
30 X
25X
' 2CX
~ i ex
1CX
5X
OX
FRSO
Run No. 1
)U£NCY OBSERVE? AV,_°2GE
CUOS STATtO 0°ACITYI
PLCH"? SNYOP
0 u
S j
C 2
3 5
6 7
7 7
7 7
Run No. A
USSCY OiiScRVE0. AV-:RAGr
IfXCEKOS STfiTf H 0°ACITYI

"~3 0 X "
25X
" 2 OX"
16X
1CX
5X
ax
PLCHR SMYOR
" o ' ' " 3
0 Q
	 o i" "
f 7
21 20
21 22
21 22
Run No. 2 Run No. 3A Run No> 3B
F'JlHENcr r->s;^vr? AV'^AOC FI-^UCNCY rnr>i?vtR AV^^AGF FFraur,NCY ns'^v^' AVERAGE
t X E 10 2tX It 3 25X C 0
2CX 8 1*. 	 20X " 17 17 " 	 2cy. 	 0 	 3 	
15X 17 20 15X ifl 19 15X 5 i.
1C/. Z< M . IPX 18 20 iOX 5 U
i"< 22 22 5>X 18 20 5 X 5 t
OX 22 22 fX 18 20 " OX 5 <.
U>
l-1
Run No. 5A Run No. 5B
FRrQOfNCY OBSrPV"=> AU^PflGP FPcQUENCY ris:?v£.^ Ayc^AGt >
CXCiTLOS STATLn 0PACITYJ LXCc.c.OS STATED OPACITY!
PLCHP ' "st.-YO* PLCH^ SNYOR"
3QX 0 0 30X 0 0
20X 0 0 25 X 1 5
2 ax 01 20 x 6 ii
ItX 0 tt 15X 9 13
IOX 3 10 1CX 10 13
5X S 10 " 5X ~" 10' 13" 	
OX 6 10 OX 10 13

-------
TABLE 13.  FREQUENCY OBSERVATION AVERAGES EXCEEDING
           STATED OPACITY FOR.TOTAL OPACITY DATA
_ 	
Run No. 1
FHECUENCY OBSErtvEH AVERAGE
EXCEEDS sTAtto OPACITY:
PLCHC SNYDH
30* 00
• "255 	 0 0
20% 0 2
15% 35
10% 6 7
5% 7 7
0% 7 7
Run No. A
FHECUE^CY OHSEHVER AVERAGE.
EXCEEDS STATED OPACITYI
PUC^R SNYDH
30% 3 0
20% 3 2
15% 4 9
10% 19 23
5» 3* 35
0% 35 35
Run No. 2
FHEUUENCY TOBSEHVEH AVERAGE
EXCEEDS STATED OPACITY:
PLCHR SNYDH
30% 2 6
25% 6 11
20% 9 17
15% 22 24
10% 27 26
5% 27 .26
0% 27 26
Run No. 5A
_jF£iQ«l- NCY Pjr-'PUF? AV^=?AG£
t XC-
3 OX
25X
2 1 X
1SX
10 X
5X
OX
•::os sia
fLCHr
c"
2
1<»
2ST
*9
29
29
T:J OPACITY:
SNVQR
i
c
25
26
30
30
30
Run No. 3A Run No> 3B
crIO"-iCY r^:r:v'= AVE^AG^ F^OU-.NCY r->s--^vfp Av^ar.f
f.xjrr..i5 s-u-:o CFACITYI LXJ.^OS STUID CFACITY:
^LCH-^ SMYOR PLCHR SNvnp

30 X 11 0 30 X 0 0
25X 15 i» 25X 0 o
2&X 23 19 20 X 6 ' 5

15'. ^s <;^ 15 x 
Run No. 5B
FxcE^ns STATTH OPACITY:
PLC^? SNYDK
30 X 2 2
2 5 X 3 2
2CX "1 V
15X 6 7
10X 15 l«t
5X 15 1*«
C X 15 1 <,

-------
                                        33
Observation
     •Site A
 Hillside
                        400
                                       76-8"
                                                          120
5
^
0'
f i
i
f>r

k

1
41
1
Observation
      Site'B
                                                                          Hillside
                            Cross-Sectional View
  2
  3
Coal preparation;
 cleaning and drying
 process area
Venturi scrubber inlet stack
Effluent outlet stack
                                                                      Observation
                                                                          Site  B
                                 Top View
                    FIGURE 10.   OPACITY OBSERVATION SITES

-------
                              34
    50
   40
§   30
o>
CL
(J
o
Q.
O
20
    10
                                                      Run No. I
             Particulate  sampling
                       Sundown - no further readings
                       of visible emissions
      18
              19
20          21
Time of Day, hours
22
23
 FIGURE 11.   RUN NO.  1 OPACITY  RESULTS AS A FUNCTION OF TIME OF DAY

-------
                              35
        50
        40
        30
     0)
     Q.
     O
     o
     O.
         20
         10
                                                        Run No. 2
                 Particulate sampling
          15
                                          •((Run started at 14:48)
16
   17          18

Time of Day, hours
19
FIGURE 12.  RUN NO. 2 OPACITY RESULTS AS A FUNCTION OF TIME OF DAY

-------
    50
    40
§  30
i_
0)
ex
o
o

O  2°
    10
Particulate

 samplings
                        Run  No. 3A data
                                                     I
                                                                                       Run  No. 3
                                   Particulate

                                    sampling
                                                   Run No.  3B data
                  10
   II
12          13          14

     Time of. Day, hours
15
16
17
           FIGURE 13.   RUN NO.  3 OPACITY RESULTS AS A FUNCTION OF TIME OF DAY

-------
                             37
    50
    40
u
i_
0)
a.
    30
o
o
£  20
     10
      15
16
                           Particulate samplings
                              _L
 17           18
Time of Day, hours
                                                      Run No. 4
19
20
 FIGURE 14.  RUN NO. 4 OPACITY RESULTS AS A FUNCTION OF TIME OF DAY

-------
    50
   40
   30
o>
Q.
O

Q-  20
O
    10
J
      10
                        Run 5A
                        Particulate
                      /samplings

                    KH
                                        i
                                                  Run No. 5
           II
12
                                                                Run5B
13          14          15

    Time of Day, hours
                                                                   Particulate
                                                                   •          i
                                                                    sampling
16
17
                                                                                                    00
18
               FIGURE  15.  RUN NO.  5  OPACITY RESULTS AS A FUNCTION OF TIME OF DAY

-------
                                  39


                Data Applicable to All Five Runs


          The following data, required by the EPA "Guidelines for Pre-

paring Summary of Visible Emissions", apply to all five of the test runs.

              Type of Plant;  Coal cleaning

              Type of Discharge;  Emissions from thermal dryer

              Location of Discharge;  Stack above dryer

              Height of Point of Discharge;  76 feet, 8 inches
                                             above ground level

              Distance from Observer to Discharge Point;

                ' Site A:   400 ft northwest of stack
                 Site B:   120 ft southeast of stack
              Height of Observation Point;

                 Site A:   50 ft above base of stack
                 Site B:   40 ft above base of stack
              Direction of Observer from Discharge Point;

                 Site A:   northwest of stack (in afternoon)
                 Site B:   southeast of stack (in morning)

          The remaining data called for in the EPA guidelines are different

for each run and are presented in Table 14.  An examination of Figures 11
through 15 show the opacity ranges as follows.

          Test Run 1   -  Opacity ranged from about 8 to 18 percent
                          during the 50 minutes of observations prior
                          to sundown.
          Test Run 2   -  Opacity ranged from about 14 to 31 percent
                          during time of particulate sampling which
                          extended from 1448 to 1736 hours.

          Test Run 3A  -  Opacity ranged from 22 to 31 percent.
          Test Run 3B  -  Opacity ranged from 15 to 20 percent.

          Test Run 4   -  Opacity ranged from about 7 to 18 percent
                          during the times of particulate sampling
                          which were 1552 to 1655 hours and 1811 to
                          1917 hours.
          Test Run 5A  -  Opacity ranged from about 17 to 25 percent
                          during the first two particulate sampling
                          periods .

          Test Run 5B  -  Opacity ranged about 12 percent at the
                          start of the third particulate sampling
                          period.

-------
                                            TABLE  14.  OPACITY  OBSERVATION  SUMMARY
                                      Description  Description             Wind
Run    Date   24 Hr.  Clock Observation    of           of       Wind     Velocity,
No.   (1975)      Time        Site    Background      Sky      Direction   mph      Color of Plume
                                                                  Comments
                                                                          Duration of
                                                                          Observation
      1/18/75   1809-1859
Sky
20% clouds  from NNW
2     6/19/75   1510-1850       A
3A    6/20/75   0940-1300       B
3B    6/20/75   1504-1628       A
4     6/23/75   1530-1930       A
5A    6/25/75   1004-1400
5B    6/25/75   1430-1715
                                          Sky
         50% clouds  from SW
                                          Sky      Overcast    from NE
                                                (100% clouds)
                                          Sky      Overcast    from NE
                                                (100% clouds)
                                                                            0-5     Black with steam
                                                                                   plume near stack
                         5-10    Black with steam
                                plume near stack
                                 0-5
                                 0-5
                                          Sky      Overcast    from NW      0-5
                                                (100% Clouds)   but  variable
Sky  Slightly over-   from NE      0-5
     cast
      (107. clouds)  .
Sky  Slightly over-   from NE      0-5
     cast
      (10% clouds)
                                Black with steam
                                plume attached
                                to stack

                                Black with steam
                                plume attached
                                to stack
                                         Black with steam
                                         plume attached
                                         to stack
                                Black with steam
                                plume attached
                                to stack
                                Black with steam
                                plume attached
                                to stack
Black plume obscured
by attached steam
plume sometimes ex-
tending 200 ft above
stack

Black plume obscured
by attached steam
plume up to 75 ft
above stack

Black plume obscured
by attached steam
plume extending 100
to 200 ft above stack

Black plume obscured
by attached steam
plume extending 50
to 100 ft above stack

Black plume obscured
by attached steam
plume extending 75
to 250 ft above stack

Steam plume extended
50 to 125 ft above
stack

Steam plume extended
50 to 125 ft above
stack
                                                                                                                             50 rain;
                                                                                                                             discontinued
                                                                                                                             at sundown
                                                                                                                             (7:00 p.m.)
                                                                                                                             3 hrs, 40 mia
                                                                                                                             3 hrs, 20 min
                                                                                                                             1 hr, 24 min
                                                                          4 hrs
                                                                                                                             3 hrs, 56 min
                                                                                                                             2 hrs, 45 min
 (a)  Moved to Site A at 1310 hours.

-------
                                   41
                        Trace Metal Results

           The  catch  from  Run No.  4 was  analyzed  for  trace metals  and the
 results  are  shown in Table  15.  For the most part  these data are  considered
 to  be  representative of what one  might  expect  from coal.  The results must
 be  interpreted with  consideration of mass  for  each sample.  The ppm values,
 as  presented,  tend to be  misleading if  one does  not  relate the indicated
 ppm values to  the associated sample mass(as presented at the bottom of the
 table) to obtain  the  mass  per sample of  each element.  The major constituents
 based  on the mass collected on probe and filter  catch are iron, potassium,
 sodium,  and  zinc. Relatively small amounts of other elemental constituents
 were picked  up in the acetone rinse of  the impingers but are insignificant
 when considering their relative mass.   Silicon,  being the predominant metal,
 is  most  likely present due  to its occurrence in  coal ash.  However, some
 portion  of the silicon may  represent fragments of  filter picked up during
 the probe-and-filter-holder acetone rinse.
                      LOCATION OF SAMPLING POINTS
Inlet to Ventu'ri Scrubber

     Particulate samples were collected from the scrubber inlet gases
using an Alundum thimble in conjunction with a standard EPA Method 5
rig.  A rather large port consisting of a 6-inch-diameter nipple was
necessary to accept the special EPA series cyclone used to classify par-
ticle size.  The cyclone had an overall height of 5-1/2 inches.  Due to
the high pressure drop across the scrubber (30 inches water pressure),
it was necessary to fabricate a sealed holding chamber and sliding gate
valve assembly (Figure 16) so that the sampling probe could be inserted
into the stack against the high static pressure.  The relatively large
holding chamber would not allow complete traversing of one stack diameter

-------
                         42
    TABLE 15. OPTICAL EMISSION SPECTROSCOPY ANALYSIS
              FOR TRACE METALS  (RUN NO.  4),  PPM


Element -441(1)
Hg
Be
Cd
As
V
Mn
Ni
Sb
Cr
Zn
Ca
Pb
Se
B
F
Li
Ag
Sn
Fe
Sr
Na
K
Ca
Si
Mg
Ba
(a)


--
1
<200
<200
30
10
50
<50
50
1,000
300
50
—
100
—
<600
<1
10
3,000
50
2,000
3,000
500
--
300
50
Descriptions of
Blank Nos. -493


-441(2)
—
1
<200
<200
30
10
50
<50
50
1,000
300
50
—
.200
—
<600
<1
10
3,000
20
2,000
3,000
500
--
300
50
Samples (a»
-442
—
<1
<200
<200
30
200
100
<50
300
300
50
<20
—
200
'
<600
150
<10
6,000
100
2,000
2,000
1,000
15,000
600
100
b)
-443
--
<1
<10
<10
<3
<3
<3
<10
<3
<20
<3
40
--
<3
--
<25
10
115
<3
10
115
45
370
100
45
3
Sample Nos. S75-001-441
through

-496 are as






























-444
—
<1
<170
<170
<60
10
<60
<170
<60
600
<60
120
—
170
--
<570
30
570
400
<15
570
860
<60
1,700
<60
60

-445
--
<1
<285
<285
<95
70
190
<285
95
950
1,900
190
—
280
—
<950
50
1,900
570
70
2,900
2,400
1,900
1,900
1,600
285
through -445 and
follows:

Wt

(Solid) ,

-441
-442
-443
-4A4
-445
-493
-494

-495
-496


Glass fiber filters (2
Acetone, wash
Itnpinger catch
of front

each)
half

54

and water rinse
Chloroform/ether extraction
Final acetone
rinse of
Glass fiber filter (3
Acetone blank,
Lot #7150
Oemineralized
Burdick

back half
each)
and Jackson





me

Vol
(Liquid) ,
ml
.3/54.1
268
87
3
2
0
0

double distilled water, OSU 1
Chloroform/ether, Baker A.R.
1
.8
.0
.5
.1

.4

.6
.9
160
815
150
325
__
200

200
150 .
(b)  Background Subtracted.

-------
                            43
                          6'
FIGURE 16.  INLET STACK SPECIAL ADAPTER WITH GATE VALVE SHOWING
           POSITION OF ALUNDUM THIMBLE PRIOR TO SAMPLING

-------
                                  44
due to insufficient probe length; therefore, the second half of the stack
was traversed without the holding chamber.  Working conditions were very
undesirable because of the hot exhaust gases (180-200 F) escaping through
the 6-inch-diameter nipple at approximately 300 cfm.  During the second
half of each of the two stack traverses, the gate valve was opened, the
probe was inserted into the stack against the flow of hot exhaust gases,
the 6-inch pipe reducing coupling was threaded into the valve assembly,
and traversing continued.
          Figure 17 shows the inlet stack geometry relative to sampling
                                                                (3)
locations.  According to the December 23, 1971, Federal Register   ,
Method 1, sampling two diameters upstream and less than one diameter
downstream from a disturbance requires at least 48 sampling points, 24 on
a diameter as indicated on Figures 16 and 17.  Specific distances for traverse
points are given in Table 16.

Outlet of Mist Eliminator

          Particulate and gaseous emissions were sampled at the outlet
of the mist eliminator.  Figure 18 shows the geometry relative to the
sampling locations.  According to the December 23, 1971, Federal Register,
Method 1, 22 sampling points per stack diameter were required relative to
the associated upstream and downstream stack diameters.  Table 17 shows
specific distances for traverse point locations.
          Prior to outlet particulate sampling, it was necessary to
install straightening vanes to reduce the cyclonic swirl caused by the
mist eliminator.  This was accomplished by the insertion of two 8-foot
lengths of metal at right angles to each other as depicted in Figure 18.

-------
                                          45
                                             TABLE 16.  TRAVERSE  PORT LOCATIONS—INLET
Sample
location
                 Flow
                 o
                                12
Point
1
2
3
4
5
6
7
8
9
10
11
12
Percent
of
Diameter
1.1
3.2
5.5
7.9
10.5
13.2
16.1
19.4
23.0
27.2
32.3
39^8
Distance from
Outside of Sam-
ple Port (a), in.
41
42-1/8
44
45-3/4
47-5/8
49-1/2
51-5/8
54
56-5/3
59-5/8
63-1/4
68-5/8 '
Point
13
14
15
16
17.
18
• 19
20
21
22
23
24
Percent
of
Diameter
60.2 •
67.7
72.8
77.0
80.6
83.9
86.8
89.5
. 92.1
94.5
96.8
98.9
Distance from
Outside of Sam-
ple Port(b), in.
57-3/8
61-3/4
65-3/8
68-1/2
69
73-3/8
75-1/2
77-1/2
79-1/4
81
82-3/4
84
                                       (a)  Using "holding chamber".
                                       (b)  Using "short nipple".
                              'Venturi
                               scrubber
          FIGURE 17. INLET STACK GEOMETRY SHOWING  SAilPLING LOCATION AND
                     SAMPLE POINT CONFIGURATION

-------
                                      46
          6-9
          Mist

        eliminator
                               •Straightening
                               vanes
                                         TABLE  17.  TRAVERSE  POINT LOCATIONS —OUTLET
22-9'
Point
1
2
3
4
5
6
7
8
9
10
11
Percent
of
Diameter
1.1
3.5
6.0
8.7
11.6
14.6
18.0
21.8
26.1
31.5
39.3
Distance from
Outside o£
Sample Port, in.
6
7-7/8
9-7/8
12
14-3/8
16-3/4
19-1/2
22-5/8
26-1/8
30-1/2
36-3/4
Point
12
13
14
15
16
17
18
19
20
21
22
Percent
of
. Diameter
60.7
68.5
73.9
78.2
82.0
85 .4
88.4
91.3
94.0
96.5
98.9
Distance from
Outside of
Sanple Port, in.
54
60-3/8
64-3/4
68-1/4
71-1/4
74
76-1/2
78-3/4
81
83
84-3/4
FIGURE  18.  OUTLET STACK GEOMETRY SHOWING SAMPLING LOCATION
            AND SAMPLE POINT CONFIGURATION

-------
                                 47

                 PROCESS DESCRIPTION AND OPERATION

          The Westmoreland Coal Company installation near Quinwood,  West
Virginia in Nicholas County thermally dries Pocahontas No. 3 Sewell  and
Dorchester-Imboden coal.  The demand for thermal drying is due to freight
rate savings, the elimination of handling problems due to freezing,  and
the needs of the customer's process (coke ovens must control bulk density
and power plants must control plugging of pulverizers).  A venturi scrub-
ber is used to control particulate emissions from the thermal dryer.
Tests for particulate emissions were conducted on the thermal dryer ex-
haust only during periods of typical plant operations.

                       Process Description

          Coal is delivered to the plant and is crushed to a variety of
sizes.  It is then washed, screened and separated by both water tables
and concentration tables.  The coal washing is a continuous process  and
reduces ash content from 16 percent to 3 percent.
          The coal that is thermally dried, the 3/8 x 0-inch coal or the
slack  is dewatered by shaker tables and vacuum discs and then dried to
2.0 percent to 3.5 percent surface moisture in a thermal dryer.  Coal
drying is accomplished by use of flue gas (produced by a coal-fired furnace)
reduced in temperature by dilution air.  The emissions from the fluidized
bed thermal dryer are exhausted to a chamber loaded with 40 or more multi-
clones which separate  much of the fine dust from the emissions.  The  finer
dust particles pass from the multiclones of the dryer through a high pres-
sure blower to a venturi scrubber and a demister where over 95 percent of
the particles are collected.  The emissions to the atmosphere are ducted via
an 81-inch diameter stack.  Figure 19 is a sketch of the thermal dryer
system.  The design capacity of the thermal dryer is 270 ton/hr of coal at
approximately 250 F.  The plant is usually operated at two-thirds to
three-fourths of this rate because of the moisture level.  The actual
operating capacity of the dryer is limited by the tons of water evaporated
per hour rather than the amount of coal being processed.  The plant  runs
on a schedule of two 8-hour shifts and is typically closed on weekends.

-------
  Denxister
           A
           I
           I
                                                  Explosion Vent
                                       KEY

                                   -*• —— Gas flow
                                   *C —— • Coalf low
          ischarge\
           Gate, -  v
 Rotary
Discharge
                                                                                               O O
                                                                                              Control
                                                                                              . Panel
                                                                                   Note: Sampling point
                                                                                     located at Dryer
                                                                                     feed conveyor belt
                                                        ^X	ru _     »v!
                                                      ,  vrr^
                                        Feeder :  •
                                              Bedplate 'I
                                                                    CD
                                                           Furnace
                                                                       Tempering
                                                                        Louvers
                                                                         A  exhaust temperature and  fan
                                                                           pressure
                                                                         +  drying chamber pressure  and
                                                                           temperature
                                                                         •  bed pressure
                                                                         a inlet pressure
FIGURE 19..  EXHAUSTING-TYPE FLUIDIZED-BED THERMAL COAL DRYER,  SHOWING COMPONENT PARTS AND
           FLOW OF COAL AND DRYING GASES, WESTMORELAND COAL COMPANY, IMPERIAL SMOKELESS
           DIVISION, QUINWOOD,  WEST VIRGINIA

-------
                                  49
                      Emission Control Equipment


          The thermal dryer exhausts into a cyclone separator where the

large particles are removed.  Next, the exhaust is blown into the venturi

scrubber where the fine particles are impacted upon water droplets which

are removed from the effluent gases by the mist eliminator.  From there,

the exhaust gases exit the mist eliminator and go out the stack.  The

fan volume is rated at 134,000 cfm for the maximum design capacity of
270 ton/hr.  The pressure drop across the venturi scrubber is 32 in. H20,
3 to 4 in. H20 attributable to the mist eliminator.


                        Process Operation


          Samples were collected from the inlet and outlet gases to the

venturi scrubber control equipment.  Opacity observations and dryer feed
                                                                          *
samples were gathered concurrently.  Each test run is described as follows.

  June 18, 1975 - Refer Appendix E  Run 1

            Test went well with only one interruption that occurred
  due to low feed.  Also, Sewell No. 3 strip mined coal was used
  for the majority of the time instead of Sewell deep-mined coal.
  Though the data are not suitable for evaluation of Sewell No. 7,
  they do provide an interesting comparison between the two coal
  mining methods.

  June 19, 1975 -  Refer Appendix E  Run 2

          The test had only two interruptions but process operations
  were unsteady.  Feed to thermal dryer was discontinued, problems
  with the water supply to the venturi scrubber were suspected, and
  the supply of raw coal to the plant was inconsistent. These data
  are not typical of routine operation.  Repairs were made to the
  venturi scrubber water supply system prior to commencing the next
  test.

  June 20, 1975 - Refer Appendix E  Run 3

          The test was very good, even though it was necessary to
  temporarily suspend sampling twice due to process malfunctions.
  Process on the whole operated very smoothly, and during actual
  testing was very consistent.  The test data are representative
  of typical operations.
  *Run numbers are relative to outlet.

-------
                                  50
  June 23, 1975 - Refer Appendix E  Run 4

          Test was very good with no delays at all.  High drying
  chamber temperatures occurred for one-half hour from 4:45 to
  5:20 p.m. but were not extreme.

  June 24, 1975
          Process shut down every half hour due to broken equip-
  ment.  There was no continuity to process whatsoever.  Testing
  was cancelled for the day.

  June 25, 1975 - Refer Appendix E  Run 5
          Test very good.  Sampling was interrupted briefly during
  two short process delays.   Drying chamber temperatures were a
  bit high from 12:30 p.m. to 1:05 p.m. and from 4:40 p.m. to 5:03
  p.m. but were not abnormal.

  June 26, 1975 - Refer Appendix E

          Several special inlet tests were done by Roy Neulicht.
  The first and second tests were good with no problems.  The
  third and fourth tests had high but not normal drying chamber
  temperatures.  All tests were conducted during the processing
  of Sewell No. 7 deep-mined coal except the fourth test which
  was Park Sewell or Sewell No. 3 strip-mined coal.


          The production for the second half of Test No. 5 (June 25,  1975)
was determined to be 180  ton/hr.  The  average process  rate for  that day,

 however,  was  only  137.7  ton/hr-because of production stoppages  (see Table 18).

 The rate  during  actual sampling was higher.  The reason for this inconsistency

 is  that testing  was never done during  process malfunctions or slow ups be-
cause of the abnormally high drying chamber temperatures that occur.   The
emission tests were conducted only during periods when conditions were
typical of routine operation and the data, therefore,  are representative

 of  normal production.


                       TABLE 18..  PRODUCTION RATES
                                 (June 25, 1975)
Recorder
Westmoreland Coal Co.
EPA
EPA
EPA
Amount Time
Time Period minutes
Both shifts
10:00 to 11:18
14:55 to 16:18
16:18 to 17:18
1035
438
83
60
Process
, Rate ,
ton /he
137.7
158.9
187.9
180.0

-------
                                   51
                    SAMPLING AND ANALYTICAL  PROCEDURES

            Plant operations, by necessity, were monitored by EPA personnel
  prior to and during all sampling to ensure the validity of the measure-
  ments being presented in.  this report.
            Standard EPA sampling methods, as reported in the December 23,
  1971, Federal Register, were followed to obtain samples of gaseous
  emissions for C0~, CO, and 02•  Samples of scrubber water and process
  coal were taken under the direction of the EPA Project Officer.  Sample
  times are reported in the Sample Collection Log presented in Appendix D.'
            A temporary on-site lab facility was set up for equipment clean-
  up.  Due to the nature of the process, it was important to isolate, as
  much as possible, the cleanup and analytical area from plant operations.
            Analytical balances were set up in the temporary lab and mass
  determination of BCL inlet and outlet samples and for the EPA cyclone catches
  were determined on site after each run.  All calculations pertinent to
  isokinetic sampling were  determined after each run to ensure results
  were within EPA guidelines.
                     Coal Sample Collection Method

          Representative samples of the process coal were collected for
sieve analysis during each run.  Figure 20 depicts the process feed
system used at the Westmoreland Coal Company and also gives a pictorial
diagram of how coal sample aliquots were collected.
          The conveyor pushes the coal into a large hopper where it is
fed into the dryer.  The bulk or large mass of the coal falls into the
hopper just as it passes the end of a stationary^ inclined ramp.  As the
conveyor reaches the end of its travel and starts its return, additional
coal which has adhered to the conveyor surface is thrown off and appears
in the hopper as relatively fine particles.

-------
                 52
                                  Coal samples
FIGURE 20.   COAL SAMPLE COLLECTION METHOD

-------
                                      53
        The hopper outlet coal samples were collected from each of four
quadrants as depicted in Figure 20.  The sample collector, fabricated ac-
cording to ASTM standards^ , was inverted and placed behind the stream-of
coal as in Position 1.  The collector was then turned upright and moved into
and through the stream of coal as in Positions 2, 3, and 4.  The sample
collector was emptied into a sample container and the collection method was
repeated for each of the other quadrants to obtain one composite sample.
Three samples were collected each 15 minutes during the entire particulate
sample run.  The coal samples for each run were combined and a fraction was
removed for sieve analysis according to ASTM Standards   .
                        Scrubber Water Collection

           To develop a better understanding of the operation and effective-
 ness of the venturi scrubber, samples of water which had passed through
•the venturi were collected at Che outlet of the scrubber sump.   Figure 21
 is a simple schematic depicting the basic flow pattern of the scrubber
 system.  As indicated, about 80 percent of the scrubber sump water is
 recirculated back to the ventari for reuse while the other 20 percent is
 sent to a static thickner where the particles collected in the  scrubber
 water settle by gravitational forces.  The scrubber water sample to be used
 for size distribution of the collected particles was taken from the 20
 percent by-pass line as indicated.  It is assumed that sufficient water
 flow is maintained in the recirculation system to allow a representative
 water sample to be collected relative to the associated outlet  emission
 sampling.  If this assumption is valid then a comparison can be made of
 the inlet particle size distribution and the associated particle size
 measured in the scrubber water.  However, it should be noted that the
 particles collected in the scrubber water represent a time-averaged
 representation of the particles removed from the gas stream.  The volume
 of the scrubber sump relative to the 20 percent discharge volume flow
 would indicate the extent of time averaging involved relative to the gas
 sampling time.  Only if there exist steady-state scrubber operation and

-------
        Straightening
           vanes
      Level
      control

Makeup  water
20% clarified
    Scrubber sump
                                  Overflow
                                  to thick-
                                  ener
                                                    80% recirculated  water
                                                        About 20% of scrubber water flow
                    Water pump
                                                                                                            Ui
Scrubber
water sample
                                                                               To static thickener

                          FIGURE  21.  SCHEMATIC OF VENTURI SCRUBBER WATER  FLOW SYSTEM

-------
                                   55
an unchanging gas borne participate feed to the scrubber can the parti-
cles found in the scrubber be directly compared with gas samples for
evaluating scrubber performance.
                    Particle Sizing Methodology

          Particulate samples were collected by sampling the venturi scrub-
ber inlet stack gases at an isokinetic rate into an Alundum thimble.  During
sampling, the thimble was  located in the stack and was at stack gas temperatures,
thereby minimizing condensation.  Size distribution for particles collected
in the thimbles,  in a cyclone sampler, and from bulk coal samples were de-
termined with a Coulter Counter'  .  A Mine Safety Appliance  (MSA) Particle
Size Analyzer' '  complemented Coulter Counter data relative to <325 mesh
samples.  The following questions were considered relative to analysis tech-
niques which, if  not applied properly, could alter the reported particle
size distribution:

          (1)  What effect would sample drying have on the particle
               size distribution?
          (2)  Would particle dispersion by ultrasonic vibration
               alter the particle size distribution?
          (3)  What particle concentrations would be "generated" from
               thimble breakup during ultrasonic cleaning?
          (4)  If ultrasonic thimble cleaning were feasible because
               of insignificant thimble particle concentration,  would
               it be possible to obtain a representative aliquot
               from a relatively large electrolyte volume?
          (5)  Since the MSA particle size analyzer utilizes various
               fluids to determine particle size from settling
               velocity, might the coal particles be soluble enough
               in the fluids to affect their sizes?

  Experimental efforts were undertaken  to  answer these  questions  so  that a
  valid experimental  procedure  for size distribution measurements  could be
  established.  The following particle  size distribution  results  are an
  average  of three runs  per aliquot, which  is  a  routine procedure  for Coulter
  Counter  analyses.   One aliquot  per  sample was  taken for Coulter  Counter
  analyses and one aliquot  per  sample was  taken  for analyses by  the  Mine
  Safety Appliance Particle Size  Analyzer.

-------
                                      56
   Distribution  Change  Due  to  Drying
                                    (a)
             It was  determined  by  desiccator  drying  of  samples  collected
   in  thimbles at  the  scrubber  inlet  that  they  contained <1.0  percent  mois-
   ture;  therefore,  particle  size  change due  to drying  was  expected  to be
   insignificant.  This was verified  by Coulter Counter size analyses  as
   shown  in  Figure 22. Only  slight differences between the particle size
   distribution  curves of "undried" or "dried"  samples  are  seen,   these differences
   are considered  to be within  experimental error  and,  hence,  no  effect of
   coal sample drying  was found.
             The  bulk  process coal samples were wet  when  collected and,
   therefore, a  change in particle size distribution due  to drying was
   considered.   An extra  bulk feed coal sample  was divided  into two  equal
   portions  according  to  ASTM standards'^.   One half was dried at 100 F
   and sieved dry.  The other half was sieved wet  to determine if. the  size
   distribution would  show a  difference.   Figure 23  shows the  results  of
   these  measurements  which  indicate  essentially no  difference except  in  the
   pan catch (<325 mesh or <44  M-m) which shows  a slightly higher  catch for
   the wet sieving.  This could be attributed to experimental  error  or
   possibly  the  loss of the relatively fine catch  during  the drying  process.

   Effect of Ultrasonic Dispersion
   Compared  with Mechanical Dispersion

             Before  particle  dispersion by ultrasonic techniques  could be
   utilized, it was  necessary to determine to what extent the  particle size
   distribution would  be  altered by ultrasonic  dispersion techniques and
   what procedures were sufficient to assure  adequate dispersion.  A sample
(a)   The effects  of  drying on size  distribution were  determined with  coal
     samples  which may not have  been representative aliquots  and,  therefore,
     the data can only be  considered relative with respect  to size distri-
     bution and are  valid  only for  evaluating drying  effects.

-------
                               57
99.9
99.8
99.5
99
98
95
90
•21 80
>s 70
c 60
0)
Sf 50

-------
33
98
95
90
80
4—
.? 70
o>
$ 60
^ 50
§ 40
I 30

-------
                                   59
aliquot of a thimbl6 catch was placed in a dram vial containing the
wetting agent and electrolyte solution.   Mixing was accomplished by
repeated filling and emptying of a medicine dropper (the usual technique
for dispersing particles prior to Coulter Counter sizing).  A size dis-
tribution then was determined for an aliquot of this dispersion.  The
dispersion was then subjected to ultrasonic vibration ; another aliquot
was removed, and a size distribution determined.  Figure 24 depicts the
results of the two dispersion methods.  Although slight differences
can be seen, the differences are within experimental error and it can be
concluded that either method of dispersion could be used without sub-
stantial error.  (This conclusion applies only to the specific samples
of this task.  Other materials could possibly respond differently depend-
ing on their morphology and wetting properties.)  Particles from the
solutions used in the analysis by the Coulter Counter were collected on a
silver membrane filter and observed by means of a scanning electron
microscope for possible size differences in an additional  effort to
verify that ultrasonic dispersion did not modify the particle size.
Electron photomicrographs were taken of  representative  areas of the
filters and it was observed from these photos that the particles are
essentially the same in number and size  with and without ultrasonic
dispersion.

Ultrasonic Cleaning  of Alundum Thimble

           To determine the extent and nature of particle  release  from an
unused thimble,  a new Alundum thimble was  placed in 825 cc of 4.0 percent
 sodium chloride  (Coulter Counter electrolyte)  and cleaned by ultrasonic
vibration for 30 minutes at a nominal frequency of 28 kHz  + 1.5 kHz.   This
procedure was repeated three times,  each time using the same thimble  in
clean electrolyte to determine if any change would occur  in the rate  of
particle generation.  A size distribution  by Coulter Counter was  determined
 from each 825-cc volume.  Table  19  compares  the total number of particles
 generated each time by ultrasonic cleaning.

-------
                       60
99
98
95
90
80
70
i, so
'o>
$ 50
.0 40
1 30
0
& 20
o>
>
| 10
I '5
2
1
0.5
0.2
O.I
0.05
0.01






























































































































X:
6
j
















4
»
^















,Ss
•<*?
'/















1
//
&










fc/
T









/
/











/
«»










/











^











/
1










y
L
/










^
/
y









/\ Ultrasonic Dispersed
^^ Medicine Dropper Dispersed -



























).2 0.3 0.4 0.6 0.8 2 3 4 6 8 10 2C
             Particle Diameter,  micrometers
FIGURE 24.  COMPARISON  OF  ULTRASONIC AND MEDICINE
            DROPPER DISPERSION TECHNIQUES , COULTER
            COUNTER ANALYZER

-------
                       61
TABLE  19. PARTICLES GENERATED FROM ULTRASONIC
          THIMBLE CLEANING, COULTER COUNTER ANALYSES
Size,
M-m
22.0
17.5
14.0
11.0
8.8
7.0
5.5
4.4
3.5
2.8
2.2
1.7
Accumulative Number of
Than Indicated Size
Run 1
0
0
0
13
83
173
233
488
1,023
1,922
3,235
10,213
Run 2
2
3
16
38
51
130
231
393
690
904
1,548
3,765
Particles Larger
, x 10-3
Run 3
0
3
5
3
25
61
125
229
338
546
843
2,020

-------
                                   62
          It appears that the number of particles generated decreases with
each successive cleaning and begins to level off to some extent.   One can
conclude from these data that thimble cleaning prior to use may reduce
error in the size-distribution data where relatively small sample catches
are expected.

Relative Comparison--
Particle Concentration

          The importance of the relative concentration of thimble-generated
particles compared with collected coal particles in the particle population
being sized was determined.  Sample contamination due to ultrasonic thimble
cleaning was found to be insignificant when determining size distribution if
a sufficient sample mass was collected.  Table 20 shows the total number of
particles generated during initial thimble cleaning is of the order of 10 x
10  and is significantly reduced with successive cleanings.  For comparison,
it has been determined, during this study, that the total number of particles
in a measured aliquot of 2.16 mg of coal is of the order of 12 x 10 .  During
this study, the thimble sample catch range was from 9,271 mg to 26,167 mg
(see Table 7).  By ratio (9,271 mg:2.16 mg), the thimble sample particle
population is greater by at least a factor of the order of 4,000.  Therefore,
it can be concluded that the relative number of particles generated by thimble
cleaning is insignificant by comparison with the mass contained in any of
the thimble samples collected during this study.  As previously mentioned,
if one expects a relatively small thimble catch it would be advisable to
preclean the thimble several times before use to eliminate the possiblity of
a significant background particle contribution.

-------
                                     63
Representative Aliquots From
Large Electrolyte Volumes
        Thimble cleaning and particle dispersion were both accomplished
via ultrasonic vibration.  The thimble contents were emptied into a beaker
containing 825 cc of isopropyl alcohol, the alcohol being used because of
its wetting characteristics.  The thimble was then placed into the alcohol
bath and ultrasonically vibrated at a nominal frequency of 28 kHz - 1.5
kHz for 30 minutes.  Obtaining a aliquot from three different beaker levels
while the particles are in suspension would give some identification of
possible stratification due to nonuniform mixing and check the representa-
tive nature of aliquot collection for analysis.  Figure 25 depicts the
size distribution indicating that a representative aliquot can be selected
from a relatively large volume of solution with a very dense particle con-
centration if the suspension is maintained by ultrasonic mixing.   A further
conclusion from these results is that the measurement technique is repeat-
able and random errors are small.

Coal Particle Solubility

        Solubility of coal particles in the solutions used with the Mine
Safety Appliance Particle Size Analyzer was found to be negligible.  The
operating principle of this device is essentially to measure the  particle
sedimentation rate as a function of time in an appropriate liquid media.
The particles need to be thoroughly wetted and are placed in a feed liquid
prior to being placed in the sedimentation liquid.  The feed liquid consisted
of 50 percent isopropyl alcohol and 50 percent heptane.  A solubility check
for coal particles in this mixture was made by measuring weight loss during
the washing of a coal sample with a large excess of the solution.  A weight
loss of 0.08 percent was found which is considered to be insignificant.

-------
                               64
0.6 0.8  I
      4     6    8  10         20
Particle Diameter, micrometer
40    60
        FIGURE 25.  REPRESENTATIVE ALIQUOT CHECK OF LARGE
                    SOLUTION VOLUME HAVING HIGH-PARTICLE DENSITY,
                    COULTER COUNTER ANALYSES

-------
                                  65

                             REFERENCES
(1)   Coulter Counter Industrial  Model  B Instruction Manual,  Coulter
     Counter Industrial  Division,  Franklin Park,  Illinois   60131.

(2)   Whitby, K.  T.,  "A Rapid General  Purpose  Centrifuge  Sedimentation
     Method for  Measurement of Size Distribution  of Small  Particles",
     Mechanical  Engineering Department, University of Minnesota,  1955;
     presented at the 61st Annual  Meeting of  ASHRAE, Philadelphia,
     Pennsylvania,  January, 1955.
(3)   Federal Register.  December 23,  1971,  Vol.  32,  No.  247.
(4)   1974 Annual  Book of  ASTM Standards.  Part  26,  "Gaseous  Fuels;
     Coal and Coke,  Atmospheric Analysis",  American Society for
     Testing and  Materials,  Philadelphia,  Pennsylvania  19103,  1974.
(5)  Federal Register. November 12, 1974, Vol. 39, No. 219.

-------