EMB Report'No. 77SPP23A AIR POLLUTION EMISSION TEST O VOLUME I: FIRST INTERIM REPORT: CONTINUOUS SULFUR DIOXIDE MONITORING AT STEAM GENERATORS August, 1978 UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Office of Air and Waste Management Office of Air Quality Planning and Standards Emission Measurement Branch Research Triangle Park. North Carolina ------- EMB REPORT NO. 77SPP23A August 1978 AIR POLLUTION EMISSION TEST Volume I: First Interim Report Continuous Sulfur Dioxide Monitoring at Steam Generators by W. E. Kelly and C. Sedman Emission Measurement Branch, ESED U. S. Environmental Protection Agency Research Triangle Park, N. C. 27711 and J. R. McKendree and R. P. Quill Monsanto Research Corporation Dayton Laboratory Dayton, Ohio 45407 Contract 68-02-2818 Work Assignment 2 Prepared for UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Office of Air Quality Planning and Standards Emission Standards and Engineering Division Research Triangle Park, North Carolina 27711 ------- TABLE OF CONTENTS List of Figures v List of Tables vii Summary of Results ix Sections I. INTRODUCTION AND DESCRIPTION OF TEST SITES 1 A. Introduction 1 B. Description of Test Sites , 2 1. Cane Run Unit No. 4, Louisville Gas & 2 Electric Co., Louisville, Ky. 2. Bruce Mansfield Unit No. 1, Pennsylvania 4 Power Company 3. La Cygne No. 1, Kansas City Power and 6 Light Co. 4. Eddystone Unit No. 1, Philadelphia 8 Electric Co. II. DATA GATHERING AND REDUCTION 11 A. Data Gathering Systems 11 1. Cane Run No. 4, Louisville Gas and 11 Electric Company 2. Bruce Mansfield Unit 1, Pennsylvania 15 Power Company 3. La Cygne Unit #1, Kansas City Power and 19 Light Company 4. Eddystone No. 1, Philadelphia Electric 22 Company B. Data Reduction 24 C. Improvements and Research Needed 34 III. DATA ANALYSIS 37 A. Data Collection Interval Selection 37 B. Data Calculation Assumptions 40 C. Unusable Data 42 D. Usable Data and Statistical Analyses 42 IV. RECOMMENDATIONS AND CONCLUSIONS 61 ill ------- LIST OF FIGURES Figure Page 1-1 Cane Run Station No. 4 Scrubbing Plant Gas Flow 3 1-2 Bruce Mansfield Station No. 1 Scrubbing System 5 Gas Flow 1-3 La Cygne Station No. 1 Scrubbing Plant Gas Flow 7 1-4 Eddystone Station No. 1 Scrubbing Plant Gas Flow 9 II-l Instrument System Schematic, Cane Run No. 4 12 Louisville Gas and Electric Company II-2 Instrument System Schematic, Bruce Mansfield No. 1 16 Pennsylvania Power Company II-3 Instrument System Schematic, La Cygne No. 1 20 Kansas City Power and Light Company II-4 Instrument System Schematic, Eddystone No. 1 23 Philadelphia Electric Company II-5 Sample Strip Chart Data 27 II-6 Sample Data Transcription Form 28 II-7 Sample Data Listing 30 II-8 Sample Average Listing and Statistical Summary 31 III-l Inlet SO2 Variation, Cane Run No. 4 38 III-2 Outlet S02 Variation, Cane Run No. 4 39 III-3 Probability Vs. Linear inlet S02 Concentrations 45 from Louisville Site III-4 Probability Vs. Log Inlet S02 Concentrations 46 III-5 Probability Vs. Linear Outlet S02 Emissions 47 from Louisville Site III-6 Probability Vs. Log Outlet S02 Emissions 48 III-7 Probability Vs. Percent S02 Removal 52 III-8 Probability Vs. 100 Minus Percent S02 Removal 53 III.-9 Louisville Data for 7 and 14 Day Averaging Periods 59 ------- LIST OF TABLES Table Page III-l Categorization of Data 43 III-2 Inlet S02 Emissions (24-Hr. Averaging Period) 49 III-3 Outlet S02 Statistics (24-Hr. Averaging Period) 51 III-4 S02 Removal Statistics (24-Hr. Averaging Period) 54 III-5 Variation in S02 Concentrations in lb/106 BTU 56 (24-hour averages) III-6 Cumulative Louisville Statistics Vs. Averaging Time 58 vii ------- SUMMARY OF RESULTS A program was begun in May, 1977, to acquire S02 monitoring data in support of possible revisions to the New Source Performance Standard for fossil fuel fired steam generators, originally pro- mulgated in December, 1971. Four sites were chosen for monitor- ing and the monitoring equipment was installed and tested. Data gathering began during July-September, 1977 at all sites and has continued through early 1978. Monitoring was discontinued at one site in October, 1977, with little useful data accumulated. Monitoring at another site was discontinued in December, 1977, after yielding only 85 days of data. Data from the two remaining sites and data from another site ob- tained through other EPA programs were analyzed along with the 15 days data from one abandoned site. Mean S02 emissions ranged from 0.23 to 1.22 Ib/Mbtu while mean S02 removal efficiencies ranged from 81.4 to 96.0 percent. Analyses of the variability indicate that: • Dampening of variable S02 emissions by scrubbing does occur, especially with more reactive absorbents and good pH control. • The variability of outlet S02 emissions is substan- tial, such that caution should be used in developing emission standards "never to be exceeded". • Longer averaging times decrease the expected variabil- ity significantly. IX ------- Insufficient data have been collected to examine the effects of long averaging period,, i.e., 30 days or -longer. The monitoring systems used to generate these data were not the type systems which would be recommended by EPA to gather data in such a study, rather the systems were simply adaptations of existing on-site S02 monitoring equipment to generate data at minimum delay and cost. As a result, the reliability of these systems during this study does not reflect the current capability of SC>2 monitors and data retrieval systems. ------- I. INTRODUCTION AND DESCRIPTION OF TEST SITES A. INTRODUCTION The objective of this program was to obtain continuous monitoring data for sulfur dioxide emission rates and removal efficiencies for flue gas desulfurization (FGD) systems. The primary use of this data was to perform statistical analyses on variations as a function of averaging time. These analyses, along with other in- formation, were used to determine the appropriate averaging per- iod for the revised standard of performance for new coal-fired steam generators. Sulfur dioxide and oxygen concentrations were measured upstream and downstream of the FGD system using continuous instrumental monitors. Copies of boiler operation logs and FGD system opera- tion logs were obtained to document process operating conditions during the monitoring periods. All instruments were subjected to the appropriate performance specification test procedures1 to assure the accuracy of the sulfur dioxide and oxygen measurements. The monitoring program included testing at four steam generators. These were: (a) Cane Run Unit No. 4, Louisville Gas and Elec- tric Co., Louisville, Kentucky, (b) Bruce Mansfield Unit No. 1, Pennsylvania Power Co., Shippingport, Pennsylvania, (c) La Cygne Unit No. 1, Kansas City Power and Light Co., La Cygne, Kansas, federal Register, Volume 40:194, October 6, 1975. ------- and (d) Eddystone Unit No. 1, Philadelphia Electric Company, Philadelphia, Pennsylvania. Due to the magnitude of the program, four contractors were in- volved. Monsanto Research Corporation coordinated the overall program and processed the collected data. Midwest Research In- stitute, Scott Environmental Technology, Inc., and York Research Corporation had the responsibility of setting up monitoring equipment, performing the instrument performance specification tests, conducting routine calibrations and maintenance, and for- warding all data to Monsanto for processing. B. DESCRIPTION OF TEST SITES The four FGD systems serving steam generators included in this monitoring program are generally of different design and reactant types. These systems were designed several years ago (e.g., Bruce Mansfield designed in 1971) and, therefore, do not incorpo- rate the latest design features expected at new installations. Additionally, the size and type of the steam generators are dif- ferent. Further description of the individual sites is presented below. 1. Cane Run Unit No. 4, Louisville Gas and Electric Co., Louisville, Kentucky Unit No. 4 at the Cane Run Station has an electric generating capacity of 181 megawatts. The boiler flue gases are passed through two parallel electrostatic precipitators for particulate removal and then to an FGD system designed by American Air Filter Corporation. The FGD system is divided into two modules (see Figure 1-1). In each module, the flue gases first pass through a quench section for temperature reduction, then through a mobile- bed absorber equipped with sprays, then through a set of Chevron ------- CANE RUN STATION NO. 4 SCRUBBING PLANT GAS FLOW UJ BALANCED DRAFT FAN QUENCHER REHEATERS BEING INSTALLED HERE BOILER ELECTROSTATIC PRECIPITATOR INLET SAMPLING i nrATinws HJvrM 1 wIM J ELECTROSTATIC PRECIPITATOR OUTLET SAMPLING LOCATIONS DAMPERS EMISTER SCRUBBER MODULE SUPPLY TO REACTOR RETURNJOLUTION TO REACTOR DEMISTER 1 QUENCHER i SCRUBBER MODULE •SUPPLY TO REACTOR BALANCED DRAFT FAN RETURN SOLUTION TO REACTOR Figure 1-1 ------- demisters, also equipped with sprays, and then through a direct, oil-fired stack gas reheater near the stack breechings. Carbide lime slurry is used as the sulfur removal reactant. The FGD system was retrofitted to an existing boiler with an electrostatic precipitator particulates control system. The scrubbing modules are equipped so that stack gases may be by- passed. The sulfur dioxide and oxygen measurement locations at the FGD system inlet are downstream of the precipitators while the outlet measurement locations are in the stack breechings. Monitoring was started in July, 1977. 2. Bruce Mansfield Unit No. 1, Pennsylvania Power Company Unit No. 1 at the Bruce Mansfield Station has an electric generat- ing capacity of 825 megawatts. The boiler flue gases are passed directly to the FGD system. The system is a tandem venturi- absorber type designed by Chemico. The FGD system is divided in- to six venturi-absorber modules, or trains (see Figure 1-2). The boiler flue gases pass from the boiler into a common manifold for distribution to the six modules. The flue gas is first contacted with scrubbing slurry in the venturi section for particulates re- moval, then additionally contacted in the absorber section for sulfur dioxide removal. The gases then pass through direct oil- fired gas reheaters prior to entering the stack. Thiosorbic lime slurry is used as the sulfur dioxide removal re- actant. The FGD system was designed and constructed at the same time as the boiler, so that the entire system is an integral unit. No provisions are included for direct bypass of flue gasses around ------- BRUCE MANSFIELD STATION NO. 1 SCRUBBING SYSTEM GAS FLOW CO < o o CQ INLET SAMPLING LOCATION OUTLET SAMPLING LOCATIONS STACK (4 FLUES) DAMPERS Figure 1-2 ------- the FGD system. Any combination of the six modules may be used under normal circumstances should difficulties be encountered in a module. However, if a module is taken out of service, the boiler output must be reduced. One of the Unit 1 chimney flues was undergoing liner repairs dur- ing the test period. Therefore, the unit was operated at half- load with only three modules available. Partial monitoring began in late August, 1977, with the first complete data beginning in mid-September. 3. La Cygne No. 1, Kansas City Power and Light Co. Unit No. 1 at the La Cygne station is a cyclone-fired boiler which drives a 820 megawatt generator. The boiler flue gases are passed directly to the FGD system. The system is comprised of eight tandem venturi-absorber modules (see Figure 1-3). The FGD system and the boiler were designed and constructed as a complete package. Each module can be isolated from the system for individ- ual maintenance. The module outlets lead to a common manifold and then to six induced draft fans. The outlets of the fans are combined into two ducts leading to the stack. Stack gas reheat is by indirect steam heat exchange, supplemented by hot air ad- dition via a side stream from the combustion air preheaters. Limestone slurry is used as the sulfur dioxide removal reactant. Monitoring instrumentation was installed in early August, 1977, and partial data was collected through November 5, 1977. Because of instrument operation difficulties an4. atypical FGD system operation, only a limited amount of data was obtained. ------- LA CYGNE STATION NO. 1 SCRUBBING PLANT GAS FLOW o QQ AIR HEATER INLET SAMPLING L0( NATION " A " AIR HEATER I CO MANIFOLD | Ji --r^ D SCRUBBER -F C SCRUBBER T -f- H SCRUBBER T G SCRUBBER DAMPERS. /I \\ > *F B SCRUBBER T *-\- F SCRUBBER }_., i " -f- A SCRUBBER E SCRUBBER REHEATER REHEATER REHEATER REHEATER _* — H , ^ * -x: -ffBN ^/ " B ^ OUTLET SAMPLING LOCATIONS •» 11 C " < (ST; i * ii ^^a # ^^ /TD\ [(^] (ffw) *(™} ^CIC r^ Figure 1-3 ------- 4. Eddystone Unit No. 1, Philadelphia Electric Company Unit No. 1 at the Eddystone station is rated at 325 megawatts generating capacity. The boiler flue gases are passed through a mechanical collector/electrostatic precipitator section for par- ticulates removal, then to the FGD system. The total flue gas flow is split into three streams, each equipped with a venturi scrubber where the flue gases are contacted with river water for additional particulate removal. One of the three venturi scrub- bers is followed by a sulfur dioxide removal absorber. Magnesium oxide slurry is used as the sulfur dioxide removal reactant. Testing in this program has been limited to the total venturi- absorber train. Stack gas reheat is accomplished by direct oil firing. ^ The FGD system was retrofitted to the existing Unit No. 1. Flue gas bypass is provided in order to protect the boiler on Unit 1. Monitoring instrumentation was operational since mid-August, 1977, and testing was discontinued in late December, 1977. However, only a small number of days of data were obtained due to limited concurrent operating time of the boiler, the sulfur dioxide re- moval absorber, and the instrument systems. ------- EDDYSTONE STATION NO. 1 SCRUBBING PLANT GAS FLOW BOILER MECHANICAL COLLECTOR ELECTROSTATIC PRECIPITATOR ^ A X_j * B Y— A" C PARTICULATE SCRUBBER PARTICULATE SCRUBBER DADTTPIII ATT ft J L 1 r X— J L 1 r PCUCATCD DCLirAlTD INLET SAMPLING LOCATION " A " SCRUBBER OUTLET SAMPLING LOCATION " B " FAN FAN LA- S02 SCRUBBER -ft^T- REHEATER FAN BY-PASS DAMPERS FOR EACH INDIVIDUAL TRAIN -e/-* TO STACK Figure 1-4 ------- II. DATA GATHERING AND REDUCTION A. DATA GATHERING SYSTEMS The sulfur dioxide monitoring equipment at all test locations were DuPont Model 460 Photometric analyzers2. The basic instru- ment configuration varied from site to site and is discussed be- low. The oxygen monitoring equipment varied from site to site; however, the basic detection principle was the same. The oxygen measurement equipment is described in detail in the site descrip- tions below. Continuous instrumental moisture measurements were not performed. The moisture contents of the sample streams were determined by manual procedures, as discussed for each test site. 1. Cane Run No. 4, Louisville Gas and Electric Company A schematic diagram of the monitoring system used at this facil- ity is given in Figure II-l. The sulfur dioxide instrument is a single DuPont 460 four-point, dual range analyzer. The two scrubber module inlet concentrations are measured on a 0-4000 ppm range and the two module outlets after reheating are measured on a 0-500 ppm range. In the event that the module outlet concen- trations exceed 500 ppm, the measurement range can be manually switched so that all points are measured on the 0-4000 ppm range. The instrument operates on approximately a 14-minute cycle. Dur- ing this cycle, each of the four measurement points is sampled. An automatic instrument zero and sample probe backflush occurs 2Mention of a specific company or product name does not consti- tute endorsement by the Environmental Protection Agency. 11 ------- Figure II-l: Instrument System Schematic, Cane Run No. 4 Louisville Gas and Electric Company ------- immediately prior to each measurement in the cycle. The concen- tration measurement result is printed on a multipoint chart re- corder in the scrubber control room. This concentration record represents the instantaneous value at the time the recorder printer is activated. Therefore, a single instantaneous result is available for each of the four locations in each 14-minute period. A secondary single-pen continuous trace recorder was used as a backup for the control room primary recorder. The oxygen measurement equipment consisted of a Scott Model 150 paramagnetic analyzer3. The sample for oxygen measurement was withdrawn from the Dupont instrument downstream of the sulfur di- oxide measurement cell. Therefore, the oxygen measurements were performed on the same sample stream used for sulfur dioxide mea- surement. Initially, the oxygen analyzer was connected directly to the Dupont analyzer without any further sample conditioning prior to oxygen measurement. The system was later modified to incorporate a condenser for moisture removal prior to oxygen mea- surement. Oxygen concentrations were determined on a 0-25 per- cent by volume range. The measurements were recorded on a single-pen continuous trace recorder. For each 14-minute instru- ment cycle, approximately 2-1/2 minutes of continuous trace record was available for each of the four sample points. The moisture content of the sample stream was determined by man- ual techniques. Moisture tests were performed on the scrubber inlet and outlet streams, and on the analyzer sample stream im- mediately following the knockout trap in the DuPont analyzer. The temperature of the sample stream(s) was also measured. It was found that the sample streams are cooled to approximately 10°C above ambient after the trap. Because of this cooling, the samples were not at stack conditions and were assumed to be 3Mention of a specific company or product name does not consti- tute endorsement by the Environmental Protection Agency. 13 ------- saturated at the temperatures measured at the knockout traps. Early in the test program, before the incorporation of a dryer, the moisture content of the oxygen sample stream was the same as that for the sulfur dioxide sample stream. After incorporation of the dryer, the oxygen measurement sample was dry. A performance specification test was performed on the sulfur di- oxide and oxygen instrument system by Scott Environmental Tech- nology, Inc. ** The major problem areas encountered during the monitoring program at this facility were interfacing for and measurement of oxygen. It was necessary to modify the sample extraction apparatus and the analyzer itself several times before a satisfactory combina- tion was obtained. The oxygen analyzer was out of service the majority of the period between August to November. While the equipment configuration operated satisfactorily, daily inspection and maintenance were necessary to insure operation. The only other major problem encountered at this facility was the consistently high oxygen concentrations measured at the scrubber module outlets. It was originally concluded that there was leak- age past the blowback air valves installed on the sample probes at these locations. However, later experiments, after replace- ment of the air valves failed to correct the problem, showed that the placement of the probes was the difficulty. A damper is located upstream of the probe and turning vanes in the duct are located immediately after the probe. These physical configura- tions tend to stratify the flow into the lower half of the duct, especially at low boiler load conditions. The sample probes ex- tended only four feet into the duct from the top, causing the 4EMB Project No. 77-SPP-20, "First Interim Report - Continuous S02 Monitoring at Cane Run No. 4, Louisville Gas and Electric Co.". Scott Environmental Technology, December, 1977. 14 ------- sample to be extracted from an eddy or low flow zone. This prob- lem was corrected by extending the probes to about ten feet into the duct, so that samples were always extracted from the main flow zone in the duct. Clogging of the sample probes was not a major problem at this fa- cility. Particulates are removed by electrostatic precipitators prior to the inlet sampling locations and the stack gas reheaters prevent wet gas conditions at the outlet sampling locations. The brief outages caused by sample line plugging could have been avoided by using a modified automatic cleaning procedure. 2. Bruce Mansfield Unit 1, Pennsylvania Power Company A schematic diagram of the monitoring system used at this facil- ity is presented in Figure II-2. The sulfur dioxide instrument used at the inlet manifold is a DuPont Model 460 two-point ana- lyzer. The concentration measurement range is 0-5000 ppmv. The instrument operates on a 10-minute cycle, where each of the two measurement points is sampled for 5 minutes. Immediately prior to each measurement, an automatic instrument zero and probe back- flush occurs. The concentration measurement result is recorded on a continuous trace chart recorder in the scrubber control room. For each 10-minute cycle approximately 4-1/2 minutes of continuous chart record are available for each inlet location. The FGD system outlet is equipped with two DuPont 460 four-point, dual range analyzers. Each of these analyzers measures three module outlets and the common reheater outlet. Concentration measurements are normally performed on a 0-500 ppm range, but the range can be manually switched to 0-1000 ppm should 500 ppmv be exceeded. Each instrument normally operates on a 12-minute cy- cle., where each point is monitored for 3 minutes, with an auto- matic zero and probe backflush occurring prior to each measurement. 15 ------- A TRAIN OUTLET B TRAIN OUTLET C TRAIN OUTLET E TRAIN OUTLET D TRAIN OUTLET F TRAIN OUTLET Figure II-2: Instrument System Schematic, Bruce Mansfield No. 1 Pennsylvania Power Company ------- However, for this program, the three module outlets were not mon- itored. The concentration measurement result is printed on a multipoint chart recorder in the scrubber control room. This concentration record represents the instantaneous value at the time the re- corder printer is activated. Therefore, a single instantaneous value was available for each 3-minute period. A secondary single- pen continuous trace recorder was used as a backup for the pri- mary control room recorder. The oxygen measurement equipment at each location consisted of a Taylor OA1375 paramagnetic analyzer, with a chiller condenser system for sample gas drying. The sample for oxygen measurement was withdrawn from the DuPont instrument downstream of the mea- surement cell. The oxygen measurements were conducted on the same sample that the DuPont instrument used for sulfur dioxide measurement. Oxygen concentrations were determined on a 0-25 percent by volume range. The measurements were recorded on a single-pen continuous trace recorder at each inlet and outlet in- strument. At the inlet location, oxygen results were available for 4-1/2 minutes at each test point for each 10-minute cycle. At the outlet locations, oxygen data were available for 2-1/2 , minutes of each 3-minute cycle. A performance specification test was performed on the sulfur dioxide and oxygen instrument systems by York Research Corporation6. The moisture contents of the sample streams were determined by manual procedures. Tests were performed at the inlet and outlet locations, and immediately after the knockout trap in the DuPont 5Mention of a specific company or product name does not consti- tute endorsement by the Environmental Protection Agency. 6EMB Project No. 77-SPP-19, "First Interim Report - Continuous S02 Monitoring Program at Bruce Mansfield No. 1, Pennsylvania Power Company", York Research Corporation, January, 1978. 17 ------- analyzer. It was found that the moisture content of the sample stream after the knockout trap was significantly less than flue gas moisture content, therefore, the measured results at the in- strument were used for calculation purposes. Since dryers were incorporated in the oxygen sample conditioning systems, all oxygen measurements are on a dry basis. The major problems encountered at this facility were the measure- ment of oxygen and plugging of sample probe filters. The oxygen interface system (pump, chiller, condenser, valving) required a very high maintenance effort to correct plugging and leaks. The chiller system for the gas condenser had numerous breakdowns. The oxygen analyzers also failed due to electronic malfunction. After many modifications to the interface systems, the oxygen analyzer at the inlet location was operated with a much reduced maintenance requirement. The paramagnetic analyzer system at the ABC reheater outlet was never brought to an acceptable operating reliability level. This analyzer was replaced by a Thermox7 Model WDG Zirconium oxide cell instrument. After this modifica- tion, there were no further difficulties with oxygen measurement at that location. A second problem has been severe plugging problems at the outlet sampling location. During the test program there were problems with the absorber mist eliminator and the stack gas reheaters were not operated, resulting in wet gas conditions. The wet carry-over from the scrubber modules quickly caked on the sample probe filters and could not be cleaned by an air backflush. At times, the operating period between required filter cleaning was only two to three hours. A probe backflush system incorporating a combination of hot water and air was fabricated and installed. 7Mention of a specific company or product name does not consti- tute endorsement by the Environmental Protection Agency. 18 ------- This system operated for two weeks with success until water sup- ply lines began freezing due to cold weather. The oxygen measurement and probe plugging problems were compounded by the physical layout of the monitoring systems at this facility. The control stations and recorders for the sulfur dioxide instru- ments are located in the control room approximately one hundred yards from the analyzer cabinets. As a further complication, the sampling probes are located about one-hundred yards away from and 150 feet above the analyzer cabinets. Because of these physical separations, two men were required to rigorously calibrate and service the systems. No major problems were encountered with the operation of the sul- fur dioxide monitors other than sample interfacing. A non- linear response was identified at the inlet analyzer during the specification tests and was repaired. 3. La Cygne Unit #1, Kansas City Power and Light Company A schematic diagram of the equipment used at this facility is given in Figure II-3. The inlet sulfur dioxide instrument is a single-point, dual-range DuPont Model 460 analyzer. Concentra- tion measurements are normally made on a 0-5000 ppm range but can be manually switched to a 0-10,000 ppm range when 5000 ppm values are exceeded. The instrument operates on a 10-minute cycle, with a high pressure probe backflush and an automatic zero every cycle. The measurement result is recorded on a continuous trace chart recorder. A Beckman8 Model F3 paramagnetic oxygen analyzer was originally installed on the sulfur dioxide sample stream exhaust. However, this arrangement did not function reliably due to inter- face problems. The system was modified to provide a separate 8Mention of a specific company or product name does not consti- tute endorsement by the Environmental Protection Agency. 19 ------- to o FGD SYSTEM INLET MANIFOLD V02 PROBE. \S02 PROBE" Figure II-3 Instrument System Schematic, La Cygne No. 1 Kansas City Power and Light Company ------- probe and sample line system for the oxygen analyzer. This ar- rangement operated satisfactorily. The outlet sulfur dioxide monitor was a DuPont Model 460 two- point, dual-range analyzer. The concentration measurements were normally conducted on a 0-1500 ppm range, with manual switching capability to a 0-3000 ppm range when the low range was exceeded. The analyzer operated on a 10-minute cycle, with each sample point being analyzed for 5 minutes each cycle. A probe backflush and automatic instrument zero occurs each cycle. The concentra- tion results were recorded on a continuous trace recorder. A successful oxygen measurement system installation was not com- pleted at the outlet location. After several failures, it was decided that a separate probe and sample line system would be necessary. This system was not installed due to test termination at this facility. The moisture contents of the sample streams were determined by manual procedures. At the inlet, the flue gas moisture content was measured. At the outlet, the sample stream temperature im- mediately after the knockout trap was measured and saturated con- ditions at that temperature were assumed. These moisture contents were always less than those measured at the outlet flue gas ducts. A performance specification test was conducted on the sulfur di- oxide instrument at the outlet location by Environmental Protec- tion Agency personnel.9 Tests were begun at the inlet analyzer system, but it was determined that repairs to the DuPont instru- ment were necessary. The performance of the analyzer was signif- icantly improved after replacement of several tubes in the 3"First Interim Report, La Cygne, Kansas Power Plant S02 Con- tinuous Monitoring Study", EMB Project No. 77-SPP-22, Environ- mental Protection Agency, January, 1978. 21 ------- photometric detector. A retest of the inlet analyzer was not completed due to test program termination. , The only major problem that was encountered other than oxygen measurement was plugging of the sample probe filters at the out- let location. This was due to the wet condition of the stack gas. 4. Eddystone No. 1, Philadelphia Electric Company A schematic diagram of the monitoring system used at this facil- ity is given in Figure II-4. The sulfur dioxide measurement in- strument is a single DuPont Model 460 dual-range, five point analyzer. The FGD system inlet S02 concentration is measured on a 0-5000 ppm range, while the system outlet concentration is mea- sured on a 0-500 ppm range. The range is automatically switched depending on the sample being analyzed. The instrument normally operates on a 20-minute cycle with a four-minute analysis at each of the five points. For this program, the instrument was ad- justed to measure at only three points. The concentration measurement result is printed on a multipoint chart recorder in the scrubber control room. This record repre- sents the instantaneous concentration when the recorder printer is activated. Therefore, a single instantaneous result is avail- able for each location in each 12-minute period. Continuous oxygen measurement was not conducted at this facility. Due to the intermittent operating nature of the FGD system and the problems previously encountered with oxygen measurements, manual procedures were used. The moisture content of the sample streams were determined by manual measurements at each sample site. 22 ------- S02 SCRUBBER OUTLET to uJ 1-C SCRUBBER INLET £ TO OTHER SYSTEM SAMPLE POINTS Figure II-4: Instrument System Schematic, Eddystone No. 1 Philadelphia Electric Company ------- An instrument performance specification test was performed by Scott Environmental Technology, Inc.10 The major problem encountered at this facility was frequent clog- ging of the sample probes and lines. This was due to the inter- mittent nature of operation and the absence of high-pressure backflush cleaning provisions. An instrument malfunction was repaired at the beginning of the test program. The auto zero mechanism required rebuilding to ob- tain proper operation. B. DATA REDUCTION At the beginning of the continuous sulfur dioxide monitoring pro- gram, an evaluation was conducted to determine a data recording and reduction procedure that could be rapidly implemented and would yield the highest confidence level for data handling re- liability. Automatic data logging equipment with later automatic reduction by computer was considered and rejected due to the un- availability of equipment in inventory and the relatively long delivery times required for procurement. Automatic tape record- ing of data with subsequent reduction by computer was rejected due to the relatively long time requirements for tape translation to computer compatible input. Due to the time restrictions on the initiation of continuous mon- itoring, the only alternative remaining was manual reduction of strip chart records and using punched cards for computer data input. This procedure requires a very large manpower effort and would not be practical for any program other than a short-term 10EMB Project No. 77-SPP-20, "First Interim Report - Continuous S02 Monitoring Program at Eddystone No. 1, Philadelphia Electric Company", Scott Environmental Technology, Inc., December, 1977. 24 ------- project. For routine monitoring, an automatic data logging and calculation system is the only feasible approach for the amount of data required to monitor flue gas desulfurization system per- formance . Monsanto Research Corporation was responsible for data reduction and summarization in this project. The strip chart records were collected from the recorders along with copies of the appropriate boiler and scrubber control room logs at weekly intervals by the contractors operating the monitoring systems at the test sites. These were: Bruce Mansfield No. 1 - York Research Corporation; La Cygne No. 1 - Midwest Research Institute; Cane Run No. 4; and Eddystone No. 1 - Scott Environmental Technology, Inc. The site contractors also provided narrative logs regarding in- strument system performance and calibrations during the weekly operating period. A partial listing of the types of data that were received from each test site is given below: Cane Run No. 4 S02 strip chart (2 outlets - 2 inlets on same chart) 02 strip chart (2 outlets - 2 inlets on same chart) Scrubber logs Boiler logs Calibration information Bruce Mansfield No. 1 S02 inlet chart 02 inlet chart S02 outlet chart 02 outlet chart 25 ------- Bruce Mansfield No. 1 (Continued) Scrubber logs Boiler logs Additional comments on a daily basis Eddystone No. 1 S02 strip charts (inlet-outlet on same chart) Boiler logs Scrubber logs Manual test results and daily comments La Cygne No. 1 S02 inlet chart 02 inlet chart S02 outlet chart Daily comments Samples of the chart records from Cane Run No. 4 are presented in Figure II-5. The chart records were first logged in as received and then were reviewed for possible data gaps. The charts were then reduced to tabular format as shown in Figure II-6. Where only a single in- stantaneous point was available in a 15-minute period, that re- sult was used. When more than one point, or where a longer con- tinuous record was available in a 15-minute period, the average value was entered for a 15-minute value. The unit load vales were obtained from the boiler logs. After data transcription the boiler logs, scrubber logs, and daily narratives were reviewed so that appropriate comments could be included prior to data listing. 26 ------- to Cht. Soeed: 6Vhr. : 0-254 •!.!: Inlet, Outlet, N and S n:| ,, il.\ •' . I . •!• I ••! Hi'l,j;'hll!llillli!ii iffieiMi: ;;:j:;il.;.!:!;:!.iiiliiiil^iiJNlljilllLfcTnlriTiTn Louisville SO; j Cht. Soeed: 2"/hr. ., Range: Inlet 0-4000 ppra 7 3:,|ii.. •:,:,,. :i! |ij! i ! ! j'''! I'l'i: l!!i Plant Chart C.G4E) I ! ' i '• I" f:- I ::|':"i:!:T'!!i!"'l:!!:M!u 'i >ff _ 30 i ' 30 I 40 i 50 . . \ . ' 60 ' ' " !IP Hinn iUoiilllll ?;•! rllii'iii'-'lilHiliil:!!:)!!^ 10 I ;:-70 ;!; •! 60 | • 50 ! . :,i .• , " h. Figure II-5: Sample Strip Chart Data ------- LOUISVILLE OXYGEN DATA (transcribed from strip chart) co j CO LOUISVILLE SO2 DATA (transcribed from strip chart) Date 10-11 Time 1000 15 30 45 1100 15 30 45 1200 15 30 45 1300 15 30 45 1400 15 30 45 1500 15 30 45 Boiler Load BLR 95 100 102 105 102 100 North Scrubber In Out 1 70 73 74 73 71 72 73 73 78 76 76 78 76 78 77 72 75 78 77 78 78 79 76 75 3 21 25 25 25 23 24 21 25 23 19 32 19 19 23 23 16 20 19 23 20 26 27 27 18 South Scrubber In Out 5 67 70 70 71 73 71 72 74 76 76 75 75 74 76 77 73 75 77 75 76 76 78 79 75 7 26 38 23 40. 23 27 34 31 43 28 42 23 44 27 42 26 40 27 32 32 46 31 45 28 -O2 Data- Date 9-22 Time 0430 45 0500 15 30 45 0600 15 30 45 0700 15 30 45 0800 15 30 45 0900 15 30 45 1000 15 30 45 1100 Boiler Load BLR North Scrubber In Out 1 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6.5 6 6 6 6 6 8 8.5 8 8.5 3 12 11 11.5 10.5 10.5 10 12.5 11 11 11 12. 11 12 13 12.5 12 12.5 12.5 12 12 11.5 11.5 10 11 11 11.5 11 South Scrubber In Out 5 7 6 13 6 13 6 12 5.5 12.5 6 13 5.5 12.5 6 12.5 6 13 6 13 5.5 12.5 6 13 6 13 6 13 6 11 6 13.5 6 13 6 ..13 6 13 5 12.5 6 12 5.5 12 5.5 12 5 12 6 12.5 6 12 5.5 11.5 6 12 Figure II-6: Sample Data Transcription Form ------- The transcribed data were then audited by spot-checking a 15- minute data point for each day of transcribed data. After audited, the data were keypunched and processed by computer to obtain a data listing and calculated results for each 15-minute data point. The computer listings were reviewed for keypunch or other transcription errors. The listings were then sent to EPA for editing. This edit procedure incorporated the review of boiler, scrubber, and instrument operating logs so that periods of scrubber outage, bypass, startup or shutdown could be identi- fied and coded so that these data would not be included in the calculation of averages and summaries. A sample of a 15-minute data listing at Cane Run No. 4 is presented in Figure II-7. For this system there are two separate inlets and outlets. The data listing format is the same at the other facilities except that no results are entered in the appropriate columns where less than two inlets or two outlets are present. After data editing was completed, average summaries were prepared. Averages based on the 15-minute data were prepared for consecu- tive 1-hour, 3-hour, 8-hour, and 24-hour intervals. In order to calculate an average result for a single interval, it was speci- fied that at least 75 percent of the 15-minute data points be available for that interval. For example, an 8-hour average could only be calculated when 24 of the possible 32 15-minute data points were available. When less than 75 percent of the data were available for an interval, an average was not calculated and blanks were entered in the summary printouts. After each 30 days of average interval data, a statistical sum- mary was prepared. The parameters calculated were the mean (based on the interval averages), and the statistical measures of variation. Samples of 24-hour interval averages and the sta- tistical summary of the averages are given in Figure II-8. 29. ------- U) o * * LOUISVILLE * * * BLR * LOAD * OflTE TIME MW * 30 107 * 45 107 * 081077 0600 134 * 15 130 * 30 134 * 45 134 * 081077 0700 145 * 15 145 * 30 145 * 45 145 * 081077 0800 160 * 15 160 * 30 160 * 45 160 * 081077 0900 160 * 15 160 * 30 160 * 45 160 * 081077 1000 160 * 15 160 * 30 160 * 45 160 * 081077 1100 ,160 * 15 160 * 30 160 * 45 160 * 081077 1200 160 * 15 160 * 30 160 * 45 160 * 081077 1300 IbO * 15 160 * iO 160 * 45 160 * 081077 1400 160 * 15 160 * 30 160 * 45 160 081077 1500 160 15 160 30 160 45 160 081077 1600 150 15 150 30 150 •45 IbO 081077 1700 160 15 160 ******************] CD 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o 0 0 0 0 0 0 0 0 0 0 n***l INLET S02 CONC 02 PPM CONC WET PCT 2572 4.9 2572 4.9 2654 4.9 2654 4.9 2654 4.9 2695 4.9 2940 4.9 2613 4.9 2940 4.9 2041 4.9 2082 4.9 2409 4.9 2041 4.9 3022 4.9 2491 4.9 3062 4.9 2572 4.9 3226 4.9 2491 4.9 2450 4.9 2450 4.9 2450 4.9 2450 4.9 2450 4.9 2409 4.9 2409 4.9 2409 4.9 2409 4.9 2409 4.9 2409 4.9 2409 4.9 2409 4.9 2409 4.9 2409 4.9 2368 4.9 2409 4.9 2409 4.9 2450 4.9 2409 4.9 2409 4.9 2368 4.9 2368 4.9 2532 4.9 2858 4.9 2450 4.9 3062 4.9 2450 4.9 2817 4.9 ************ (NORTH) H20 LB/ PCT MMBTU 6.1 5.944 6.1 5.944 6.1 6.133 6.1 6.133 6.1 6.133 6.1 6.227 6.1 6.794 6.1 6.039 6.1 6.794 6.1 4.718 6.1 4.812 6.1 5.567 6.1 4.718 6.1 6.982 6.1 5.756 6.1 7.077 6.1 5.944 6.1 7.454 6.1 5.756 6.1 5.661 6.1 5.661 6.1 5.661 6.1 5.661 6.1 5.661 6.1 5.567 6.1 5.567 6.1 5.567 6.1 5.567 6.1 5.567 6.1 5.567 6.1 5.567 6.1 5.567 6.1 5.567 6.1 5.567 6.1 5.473 6.1 5.567 6.1 5.567 6.1 5.661 6.1 5.567 6.1 5.567 6.1 5.473 6.1 5.473 6.1 5.850 6.1 6.605 6.1 5.661 6.1 7.077 6.1 5.661 6.1 6.510 ********** ** OUTLET S02 CONC 02 PPM CONC WET PCT 244 7.1 186 7.1 269 7.1 259 7.1 259 7.1 244 7.1 293 7.1 244 7.1 308 7.1 403 7.1 2g8 7.1 293 7.1 298 7.1 298 7.1 293 7.1 298 7.1 298 7.1 298 7.1 328 7.1 391 7.1 303 7.1 387 7.1 333 7.1 401 7.1 328 7.1 347 7.1 333 7.1 416 7.1 328 7.1 357 7.1 249 7.1 352 7.1 328 7.1 382 7.1 293 7.1 352 7.1 303 7.1 387 7.1 289 7.1 333 7.1 342 7.1 323 7.1 342 7.1 279 7.1 284 7.1 293 7.1 284 7.1 284 7.1 ************* (NORTH) : : H20 LB/ : PCT MMBTU : 6.9 0.674 : 6.9 0.513 : 6.9 0.742 ! 6.9 0.715 : '6.9 0.715 : 6.9 0.674 ! 6.9 0.609 : 6.9 0.674 : 6.9 0.850 : 6.9 0.836 ! 6.9 0.823 : 6.9 0.809 : 6.9 0.823 : 6.9 0.823 : 6.9 0.809 : 6.9 0.823 : 6.9 0.823 : 6.9 0.823 : 6.9 0.904 : 6.9 1.079 : 6.9 0.836 : 6.9 1.066 : 6.9 0.917 : 6.9 1.106 ! 6.9 0.904 : 6.9 0.958 } 6.9 0.917 ! 6.9 1.147 : 6.9 0.904 : 6.9 0.9P5 : 6.9 0.688 : 6.9 0.971 : 6.9 0.904 : 6.9 1.052 I 6.9 0.809 : 6.9 0.971 : 6.9 0.836 ; 6.9 1.066 : 6.9 0.796 : 6.9 0.917 : 6.9 0.944 : 6.9 0.690 : 6.9 0.944 : 6.9 0.769 : 6.9 0.782 : 6.9 0.809 : 6.9 0.782 : 6.9 0.782 : ****»*******] t***** EFF 88.7 91.4 87.9 88.3 88.3 89.2 88.1 88.8 87.5 82.3 82.9 85.5 82.6 88.2 85.9 88.4 86.2 89.0 84.3 80.9 85.2 81.2 83.8 80.5 83.8 82.8 83.5 79.4 83.8 82.3 87.6 82.6 83.8 81.1 85.2 82.6 85.0 81.2 85.7 83,5 82.7 83.7 83.9 88.4 86.2 68.6 86.2 88.0 t***** * » INLET (SOUTH) OUTLET (SOUTH) * * S02 S02 : * CONC 02 CONC 02 : * PPM CONC H20 LB/ PPM CONC H20 LB/ : * WET PCT PCT MMBTU WET PCT PCT MMBTU I EFF * 2572 4.9 6.1 5.944 284 7.1 6.9 0.782 : 86.8 * 2532 4.9 6.1 5.850 293 7.1 6.9 0.809 ! 86.2 * 2777 4.9 6.1 6.416 333 7.1 6.9 0.917 I 85.7 * 2736 4.9 6.1 6.322 440 7.1 6.9 1.214 I 80.8 * 2654 4.9 6.1 6.133 387 7.1 6.9 1.066 : 82.6 * 2736 4.9 6.1 6.322 440 7.1 6.9 1.214 J 80.8 * 2654 4.9 6.1 6.133 367 7.1 6.9 1.012 : 83.5 * 2777 4.9 6.1 6.416 342 7.1 6.9 0.944 t 65.3 * 2736 4.9 6.1 6.322 318 7.1 6.9 0.877 t 86.1 * 2940 4.9 6.1 6.794 313 7.1 6.9 0.863 8 87.3 * 3267 4.9 6.1 7.548 298 7.1 6.9 0.823 I 89.1 * 3553 4.9 6.1 8.209 293 7.1 6.9 0.809 J 9Q.1 * 2532 4.9 6.1 5.850 293 7.1 6.9 0.809 : 86.2 * 3757 4.9 6.1 8.681 298 7.1 6.9 0.823 : 90.5 * 3675 4.9 6.1 8.492 293 7.1 6.9 0.809 : 90.5 * 3226 4.9 6.1 7.454 293 7.1 6.9 0.809 t 89;1 * 3634 4.9 6.1 8.398 293 7.1 6.9 0.809 : 90.4 * 3471 4.9 6.1 8.020 293 7.1 6.9 0.809 : 89.9 * 2491 4.9 6.1 5.756 460 7.1 6.9 1.268 t 78.0 * 2450 4.9 6.1 5.661 347 7.1 6.9 0.958 : 83.1 * 2450 4.9 6.1 5.661 416 7.1 6.9 1.147 ! 79.7 * 2450 4.9 6.1 5.661 347 7.1 6.9 0.958 : 63.1 * 2450 4.9 6.1 5.661 391 7.1 6.9 1.079 : 60.9 * 2450 4.9 6.1 5.661 352 7.1 6.9 0.971 ! 82.8 * 2450 4.9 6.1 5.661 391 7.1 6.9 1.079 ! 80.9 * 2450 4.9 6.1 5.661 357 7.1 6.9 0.985 : 82.6 * 2450 4.9 6.1 5.661 401 7.1 6.9 1.106 : 80.5 * 2409 4.9 6.1 5.567 391 7.1 6.9 1.079 : 80.6 * 2450 4.9 6.1 5.661 406 7.1 6.9 1.120 ! 80.2 * 2409 4.9 6.1 5.567 391 7.1 6.9 1.079 : 60.6 * 2409 4.9 6.1 5.567 436 7.1 6.9 1.201 : 78.4 * 2409 4.9 6.1 5.567 352 7.1 6.9 0.971 : 82.6 * 2409 4.9 6.1 5.567 328 7.1 6.9 0.904 : 83.8 * 2409 4.9 6.1 5.567 382 7.1 6.9 1.052 J 81.1 » 2409 4.9 6.1 5.567 347 7.1 6.9 0.958 : 82.8 * 2409 4.9 6.1 5.567 367 7.1 6.9 1.012 t 61.8 * 2450 4.9 6.1 5.661 342 7.1 6.9 0.944 : 83.3 * 2409 4.9 6.1 5.567 387 7.1 6.9 1.066 J 80.9 * 2450 4.9 6.1 5.661 362 7.1 6.9 0.998 ! 62.4 * 2409 4.9 6.1 5.567 362 7.1 6.9 0.998 ! 62.1 * 2368 4.9 6.1 5.473 333 7.1 6.9 0.917 : 83.2 * 2368 4.9 6.1 5.473 338 7.1 6.9 0.931 : 63.0 * 2368 4.9 6.1 5.473 308 7.1 6.9 0.850 ! P4.5 * 2532 4.9 6.1 5.850 279 7.1 6.9 0.769 : 86.9 * 2858 4.9 6.1 6.605 293 7.1 6.9 0.609 ! 87.7 * 2940 4.9 6.1 6.794 284 7.1 6.9 0.7P2 ! 88.5 * 2736 4.9 6.1 6.322 284 7.1 6.9 0.7P2 : 87.6 * 2817 4.9 6.1 6.510 : 284 7.1 6.9 0.782 : 68.0 ********************************************************* Figure II-7: Sample Data Listing ------- *****************»******************************»*******************»*************»**»*»*»**»*********»*»***»»»»»*»„„,**»»»»»»»» t * 24 HOUR AVGS * LOUISVILLE * » DATE TINE MRS * 072177 1200 48 * 072277 2100 96 * 072377 2*100 71 * 072477 2<»00 75 * 072577 2400 96 * 072677 2400 96 * 072777 2400 63 * OB0977 2400 85 * 081077 2400 96 * 081177 2400 94 * 081277 2400 90 * 081677 2400 89 * 081777 2400 96 * 082277 0400 79 * 082377 2<»00 96 * 062477 2400 91 * 082577 2400 66 * 082677 2400 96 * OB2777 2400 90 * 082877 2400 96 * 082977 2400 96 * 083077 2400 96 * 083177 2400 96 » 090177 2400 96 * 090277 2400 94 INI NORTH) S02 PPM LB/ DRY MMBTU 2389 5.164 2875 6.238 290n 6.300 2843 6.167 2787 6.045 2844 6.169 2018 4.403 2649 5.746 3175 6.887 29o3 6.298 2492 5,405 2667 5.766 2906 6.304 2741 5.951 2709 5.882 2503 5.434 2695 5.851 2633 5.717 2858 6.206 3023 6.564 2508 5.447 2351 5.108 OUT(NORTH) S02 PPM LB/ DRT MMBTU 133 0.342 27 0.07U 34 0.088 34 0.086 277 0.710 290 0.744 373 0.956 411 1.024 510 1.307 227 0.581 430 0.960 391 1.002 353 0.906 287 0.737 368 0.945 358 0.92U 371 0.953 357 0.918 424 1.089 516 1.326 362 0.93U 290 0.744 * IN(SOUTH) : OUT(SOUTh) * ; * SP2 : S02 * PPM LB/ : PPM LB/ EFF » DRY MMBTU : DRY MMBTU 93.4 * 2830 6.140 : 95 0.244 98.9 * 2911 6.314 : 20 0.050 98.6 * 2920 6.335 ! 23 0.060 98.6 * 2934 6.365 : 30 0.078 68.2 * 2612 6.100 : 352 0.854 87.8 » 2876 6.239 : 332 0.851 63.9 * 2969 6.341 : 394 0.936 61.8 * 2677 5.808 : 383 0.981 81.2 * 3196 6.934 : 506 1.267 9l.o * 2878 6.243 : 244 0-626 79.6 * 2224 4.825 : 427 1.058 62.7 « 2635 5.715 : 395 0.997 65.7 * 2865 6.260 : 372 0.954 87.7 » 2734 5.935 : 327 0.839 83.9 * 2758 5.987 : 411 1.056 63.5 * 2599 5,642 : 389 0.967 63.8 * 2726 5.918 t 422 1.071 64.0 * 2665 5.787 : 419 1.076 62.6 * 2861 6.210 : 483 1.240 79.9 * 3052 6.625 : 572 1.469 63.1 * 2586 5.619 : 421 1.081 65.4 * 2535 5.504 : 391 1.003 i EFF 96.0 99.2 99.1 98.8 65.5 86.2 83.7 82.9 61.4 90.2 75.2 82.4 64.6 66.0 82.4 83.0 80.9 81.5 80.2 78.0 80.8 81.9 ********** t ; INLET OUTLET : TOTAL TOTAL : LB/ LB/ : TOTAL MMBTU MMBTU i EFFY * 5.662 0.293 t 94.8 6.276 0.060 : 99.0 6.318 0.074 : 98.8 6.266 0.083 : 98.7 6.073 0.762 : 87.1 6.204 0.797 : 67.1 5.372 0.946 : 82.4 5.777 1.002 : 82.6 t * 6.911 1.287 I 61.4 6.271 0.603 : 90.4 5.115 1.009 : 80.3 5.750 0.999 : 82.6 6.282 0.930 t 85.2 5.943 0.788 : 86.7 5.935 1.001 : 83.1 5.536 0.944 : 83.0 5.885 1.012 t 82.8 5.752 0.997 : 82.7 6.208 1.165 t 81.2 6.595 1.397 : 78.8 5.533 1.006 : 61.8 5.306 0.874 : 83.5 *************************** ******************** 24 HOUR AVGS LOUISVILLE 30 DAY STATS MEAN STD DEVIATION AVG DEVIATION MAXIMUM MINIMUM RANGE PCT ST DEV ******************** ***************** IN(NORTH) S02 PPM LB/ DRY MMBTU 2703. 5.868 255.6 0.5508 193.5 0.4179 3175. 6.887 2018. 4.403 1156. 2.464 9.45 9.387 t**************** ***************** OUT(NORTH) S02 PPM LB/ DRY MMBTU 310. 0.768 141.3 0.3572 106.4 0.2716 516. 1.326 27. 0.070 489. 1.256 45.55 45.314 ***************** ******** EFF 66.6 5.94 4.67 98.9 79.6 19.3 6.9 ******** ****************** * IN(SOUTH) : * ; » S02 : * PPM LB/ : * DRY MMBTU : «__v v_<»«w • _«v v_*«w f * 2785. 6.038 : « 203.7 0.4377 : * 155.1 0.3313 : * 3196. 6.934 : * 2224. 4.825 : * 972. 2.109 : * 7.32 7.249 : ****************** **************** OUT (SOUTH) S02 PPM LB/ DRY MMBTU 337. 0.853 156.7 0.3976 116.8 0.2928 572. 1.469 20. 0.050 552. 1.419 46.53 46.622 **************** *********** * * * * EFF 85.5 * 6.89 * 5.20 * 99.2 * 75.2 * 24.0 * 8.1 * *********** *************** INLET OUTLET TOTAL TOTAL LB/ LB/ MMBTU MMBTU 5.953 0.820 0.436 0.375 0.352 0.280 6.911 1.397 5.115 0.060 1.795 1.337 7.354 45.740 **************** ********** TOTAL EFFY 86.1 6.3 4.9 99.0 78.8 20.2 * 7.3 * ********** Figure II-8: Sample Average Listing and Statistical Summary ------- A second statistical computation was performed for the sulfur di- oxide removal efficiencies of the FGD systems. This procedure calculated a frequency distribution for the percent occurrence of sulfur dioxide removal efficiencies for each averaging interval. The calculation procedures used to convert the analyzer outputs for sulfur dioxide and oxygen concentrations to mass emission factors are given in 40 CFR 60 Subpart D. This procedure is known as the F-factor approach and is given below: _ E = CFK T=M 20.9 °2 Where E = Emission factor - Ib/million Btu C = S02 concentration - ppmv, wet basis F = Stoichiometric conversion factor, 9820 dscf/million Btu for subbituminous coal K = Conversion factor, 1.659 x 10~7 Ib/dscf per ppmv 02 = Oxygen concentration, percent by volume as measured M = Moisture fraction as measured (for dried samples, M=0) The sulfur dioxide and oxygen concentration results were obtained by multiplying the strip chart readings as a percent of scale by the appropriate calibration factor. The emission factor was calculated for each FGD system inlet and outlet test point. The sulfur dioxide removal efficiency for a module or set of modules is calculated by: Efficiency = Ein " E out x 100% tin 32 ------- When more than inlet and/or outlet test point was monitored, the total system emission factors and sulfur dioxide removal effi- ciencies were calculated by a weighted average procedure. The equation for this calculation for total system efficiency is given by: EFF total = EFFA(FA) + EFFB(FB) Where, EFF f 1 = total system efficiency EFF = efficiency of module or module set A £\ F = fraction of gas flow through module or model /\ set A EFFB = efficiency of module or module set B Fn = fraction of gas flow through module or module D set B For all data in this study the scrubber systems have operated such that the flows through two module sets have been essentially equal, or there has only been one module set operating. Thus, a simple average has been used for total system performance. The major problems that were encountered in the data reduction procedures were related to strip chart records. Cases were en- countered where time, periods of chart stops, starts, and ad- vances, and unmarked instrument range changes, were not properly noted, as well as periods when pens failed to ink. These prob- lems were corrected by requiring that the site contractors devote additional attention to assuring that accurate and adequately'in- formative chart records were obtained. During data editing, the 33 ------- boiler, scrubber, and instrument log sheets were adequate to de- scribe periods of missing or unuseable data. C. IMPROVEMENTS AND RESEARCH NEEDED The majority of the problems encountered in this program were due to the necessity of using previously installed instrumentation and adapting other instrumentation into a system that was not de- signed as a unit and as such, could not perform at optimum levels. For example, most of the sulfur dioxide instruments were ordered and installed five to seven years ago when less was known about the most useful installation locations. Additionally, in some cases the instrument systems were never properly installed and operated. None of the sulfur dioxide systems were designed to allow straight- forward measurement of oxygen. In order to meet the program time objectives, available oxygen measurement equipment had to be adapted and this adaptation was time consuming and required more maintenance effort than is desirable. It appears that the modification to the probe backflush system which incorporated a combination of water and air will solve the probe plugging problems in those cases where dry air is not an adequate cleaning procedure. / While the present procedure for moisture content of the sample streams is adequate for intensive monitoring efforts where man- power is continuously available to record results, this procedure is not a desirable long-term approach. Research is recommended to define the moisture measurement requirements of various instru- ment systems, and the best way to achieve these requirements. This result could either be by continuous instrumentation for moisture measurement, or by sample conditioning to a known stan- dard condition. 34 ------- The improvement that will provide the greatest benefit is an automatic data logging and calculation system. This has been the most time consuming part of this program and manual data analysis is not recommended for routine purposes. Data processing equip- ment suitable for this purpose is commercially available. In summary, the monitoring system operating problems that have been encountered in this program have been the result of inade- quate initial system design, or the compromises made in the ^in- terest of rapid test initiation. Based on the experience de- veloped in this program, a monitoring system that would be convenient to use, yield high operating reliability, and provide data automatically converted to the units of the standard could be designed. 35 ------- III. DATA ANALYSIS A. DATA COLLECTION INTERVAL SELECTION At the beginning of the monitoring program it was necessary to establish a minimum data collection frequency. Since essentially all of the installed sulfur dioxide systems were multiple sam- pling point analyzers, no truly continuous measurements would be available. Review of the systems indicated that a 15-minute cycle for a 4-point analyzer was the practical minimum. Since all other analyzers would yield at least one result during a 15-minute cycle, this was selected as a standard collection fre- quency for all sites to maintain calculation consistency. For those systems where either a multiple number of instantaneous values, or a period of continuous values are available in a 15- minute period, the average of these values is used as the data point. This procedure is valid so long as the measured parame- ters do not vary significantly during a 15-minute period. Sam- ples of the output at an inlet and outlet test point at Cane Run No. 4 where the analyzer was held in a continuous mode are given in Figures III-l and III-2. The inlet sulfur dioxide concentra- tions are essentially constant over a 15-minute period. The outlet sulfur dioxide concentrations vary about ± 1 to 2 scale divisions about the mean during a 15-minute period. For readings greater than 50 percent of full scale, the potential variation for an instantaneous reading from the 15-minute mean would be at most ± 4 percent of the concentration result. This estimate is based on steady operation at constant load. 37 ------- M !.+ TT -H U- Figure III-l: Inlet S02 Variation, Cane Run No. 4 38 ------- Figure III-2: Outlet S02 Variation, Cane Run No. 4 39 ------- The selection of a 15-minute minimum data interval is also con- sistent with the requirements given in 40 CFR 60 Subpart A Sec- tion 60.13.e.z. B. DATA CALCULATION ASSUMPTIONS In order to calculate the mass emission factors and recovery ef- ficiencies from sulfur dioxide concentrations, it was necessary in some cases to use average results. At Cane Run No. 4, the oxygen monitor experienced frequent outages early in the test program. For those periods where oxygen data were not available, an average result for oxygen concentration was used. These averages were based on test results obtained when the monitor was in operation at similar boiler megawatt loadings. The periods where averages were used can be identified in the data by observ- ing those periods of time where the oxygen listings are constant. The moisture levels chosen for use in the calculations are based on a series of actual moisture and temperature measurements. The measurements yielded moisture contents in both the inlet and out- let sample streams of between 2 and 7 percent by volume. An average value of 4 percent by volume was used at the inlet and outlet for all data since the measurements available did not justify daily moisture level modifications. The maximum error that can be encountered in the emission factor calculations due to this assumed moisture is about 3 percent. For the sulfur di- oxide removal efficiency calculation, an error of 3 percent in both the inlet and outlet emission factors will result in a max- imum error of 0.5 percent of the percent removal efficiency. This is due to the cancelling effect of the division calculation. At Bruce Mansfield No. 1, no oxygen estimations were necessary. The reported data are based on measurements of all parameters. Moisture measurements were taken at weekly intervals and the re- sults for that week were used in the calculations. 40 ------- At Eddystone No. 1, oxygen measurements were by manual procedures during the scrubber operating periods. It was found tha't the variability was small and, therefore, one average result was used for inlet and outlet. Moisture levels were based on manual mea- surements . At La Cygne No. 1, oxygen data on a limited basis were available for the inlet location. No data were available for the outlet. For estimation purposes, the outlet oxygen concentration was as- sumed to be equal to the inlet. This calculation yields only an estimate of the sulfur dioxide efficiency since there is probably some dilution between the inlet and outlet measurement points. Moisture levels were chosen based on average results obtained by manual measurements. Because no complete outlet data were gathered at La Cygne No. 1, statistical analyses as described in the following sections were not performed. In addition to the data from EPA monitoring sites, data acquired from the Wellman-Lord demonstration unit at Northern Indiana Power Service Company's (NIPSCO) D. H. Mitchell No. 11 generating unit, Gary, Indiana, were also included in the statistical analy- ses which follow. A description of the Wellman-Lord process and its installation at the Mitchell plant may be found in the pro- ceedings: Symposium on Flue Gas Desulfurization, Hollywood, Florida, November, 1977, EPA-60017-78-058, Page 650. For brevity the test sites are identified in the following sec- tions as follows: Test Site Identifier Cane Run No. 4, LGE Louisville Bruce Mansfield No. 1, PPC Pittsburgh Eddystone No. 1, PE Philadelphia Mitchell No. 11, NIPSCO Chicago 41 ------- C. UNUSABLE DATA Normally the S02 monitoring system is not operated when the boiler is down, this time being used for repair, maintenance, and calibration of instruments. During periods when the scrubber is by-passed, the SC>2 monitors at all EPA test sites remained in service. These data, along with data obtained while the scrubber was starting up, not having achieved normal operation, were not included in the data analyzed for this report. However, data was not deleted due to process upsets unrelated to start-ups or shut- downs. All other unused data for the purposes of this report were due to the monitoring system, resulting from outright fail- ures, repair, or routine calibration and maintenance. At the Louisville test site, some data were pre-empted by performance testing of the monitoring equipment. Table III-l illustrates the population of unusable data at two test sites by category. As shown, monitoring system problems and repairs accounted for about one-half of unusable data at the Louisville and Pittsburgh test sites. Boiler failures accounted for roughly 25 percent of non-data periods, while monitoring sys- tem maintenance accounted for less than 5 percent. Monitoring failures, calibration, and maintenance accounted for 31 and 20 percent of operating time for the two modules at the Louisville site, and nearly 44 percent at the Pittsburgh site. The appar- ently poor availability of the monitoring systems is not indica- tive of the state-of-the-art of S02 monitoring systems. The shortcomings of these particular systems were discussed in detail earlier in this report. D. USABLE DATA AND STATISTICAL ANALYSES The remaining valid data was statistically analyzed according to the ground rules described earlier in this chapter, for the 42 ------- Table III-l. CATEGORIZATION OF DATA Sites Louisville Module "A" Module "B" Pittsburgh Usable Data Points 7582 9414 3890 Unusable Data: Boiler down 1444 Scrubber down 414 Start-up 54 Monitor failure/repair 3851 Calibration/maintenance 165 Initial performance test 876 Unaccounted losses 466 14852 1444 414 54 2019 165 876 466 14852 1245 2646 372 8153 43 ------- following variables as a function of 24-hour averaging time, as- suming all data were normally distributed: mean standard deviation average deviation percent standard deviation SC>2 removal efficiencies Subsequent analyses showed, in fact, that all data were log-nor- mally distributed. The inlet data findings differed from previ- ous coal sampling studies where coal sulfur data were normally distributed. Figures III-3 and III-4 show inlet S02 data from the Louisville site plotted on normal and log-normal probability paper, respec- tively, for the period July 23 - December 15, 1977. Data after December 15 resulted from a different coal feed and were deleted to make the statistics valid. Apparently, the best fit was the plot of inlet S02 values against log probability of occurrence (Figure III-4). From this plot the mean value of S02 inlet emis- sion rate was 5.75 Ib/MBTU and the geometric mean 1.08 lb/MBTU.* Data from the remaining sites were also plotted in Figure III-4. Table III-2 summarizes the results. Mean inlet SC>2 values ranged from 5.12 to 6.30 lb/MBTU with geometric standard deviation from 1.07 to 1.12 lb/MBTU. Figures III-5 and III-6 show the outlet S02 data from the Louis- ville site as functions of normal and log-normal probability. Again, the best fit appears to be log-normal probability. Mean *The mean is y-intercept at 50 percent value; geometric standard deviation is the ratio of the 93.3 percent and 6.7 percent less than values, raised to the 1/3 power. 44 ------- UT 99.99 99.9 99.8 7.0 vO o to I 6.0 o o S1 5.0 4.0 PERCENT LESS THAN 99 98 95 90 80 70 60 50 40 30 20 10 5 2 1 0:5 0.2 0.1 0.01 T—T 0.01 Q05 0.10.2 Q5 1 2 5 10 20 30 40 50 60 70 80 90 95 98 99 99.8 99.9 99.99 PERCENT GREATER THAN Figure III-3. Probability Vs. Linear Inlet SO2 Concentrations from Louisville Site ------- . JJ9.99 99.9 99.8 1UU| 1—i— PERCENT LESS THAN 99 98 95 90 80 70 60 50 40 30 20 10 5 21 0.5 0.2 0.1 0.01 CO oo o o o o CM o on 10 1.0 LEGEND: * LOUISVILLE • PITTSBURGH I • PITTSBURGH II o PHILADELPHIA o CHICAGO 0.010.05 0.10.2 Q5 1 2 5 10 20 30 40 50 60 70 80 90 95 98 99 99.8 99.9 99.99 PERCENT GREATER THAN Figure III-4. Probability Vs. Log Inlet SO2 Concentrations ------- PERCENT LESS THAN X 99.99 99.9 99.8 99 98 95 90 80 70 60 50 40 30 20 10 5 21 0.5 0.2 0.1 0.01 2.0 oa vO o 1.2 CSJ o CO 0.4 0.01 Q05 0.10.2 0.5 1 2 5 10 20 30 40 50 60 70 80 90 95 98 99 PERCENT GREATER THAN X 99.8 99.9 99.99 Figure III-5. Probability Vs. Linear Outlet S02 Emissions from Louisville Site ------- CO 10 PERCENT LESS THAN ,99.99 99.9 99.8 99 98 95 90 80 70 60 50 40 30 20. 10 5 21 0.5 0.2 0.1 0.01 CO co CO CO CM O CO 1.0 0.1 LEGEND: * LOUISVILLE • PITTSBURGH I • PITTSBURGH II a PHILADELPHIA o CHICAGO I I 0.01 Q05 Q1Q2 Q5 1 2 5 10 20 30 40 50 60 70 80 90 95 98 99 99.8 99.9 99.99 PERCENT GREATER THAN Figure III-6. Probability Vs. Log Outlet S02 Emissions ------- Table III-2. INLET S02 EMISSIONS (24-hr. Averaging Period) SITE Louisville Pittsburgh No. 1 Pittsburgh No. 2 Philadelphia Chicago NO. OF POINTS 82 20 11 8 25 MEAN INLET S02 lb/106 BTU 5.75 6.30 5.40 5.10 6.30 GEOMETRIC STANDARD DEVIATION lb/106 BTU 1.08 1.07 1.11 1.05 1.12 ------- and geometric standard deviations were graphically determined to be 0.89 and 1.35 Ib/MBTU respectively. The remaining S02 emission data for four other test sites were plotted (Figure III-6) on log-normal probability paper. All five sites exhibited a reasonably good data fit. Results of graphical analyses are tabulated in Table III-3. Pittsburgh I and II data represent the two periods of operation - Period I when pH control was a severe problem and Period II when pH control was improved. Table III-3 shows the geometric standard deviation of outlet emissions to vary from 1.2 to 1.5. Since both the inlet and outlet S02 levels were judged to be log- normally distributed, it was assumed that the performance of each scrubber system, expressed as a percentage S02 reduction ,nn (1-outlet) _l_ \J \J —« —.. , 1 inlet J would also be log-normally distributed. Figure III-7 shows a plot of S02 reduction versus log-normal probability. In the range (70 to 98 percent removal) shown, the straight line rela- tionships of data and subsequent graphical analysis are prone to greater error. Therefore, a better plot is one which transforms the data to the more favorable area on the logarithmic chart, i.e., the 1 to 4 range. Such a transform is 100-(S02 removal, percent) which in reality is outlet/inlet x 100 or percent SO2 remaining. When plotted as shown, in Figure III-8, the straight line fits allow much better graphical interpretation of data. Table III-4 shows the results 50 ------- Table III-3. OUTLET S02 STATISTICS (24-hr. Averaging Period) SITE Louisville Pittsburgh No. 1 Pittsburgh No. 2 Philadelphia Chicago NO. OF POINTS 89 20 11 8 25 MEAN OUTLET S02 lb/106 BTU 0.88 1.21 0.77 0.155 0.67 GEOMETRIC STANDARD DEVIATION lb/106 BTU 1.38 1.37 1.21 1.48 1.19 ------- 1000 ,99.99 99.9 99.8 99 98 95 to o UJ Q. 10 PERCENT TIME BELOW 80 70 60 50 40 30 20 10 5 2 1 0.5 0.2 0.1 0.01 LEGEND: * LOUISVILLE • PITTSBURGH I • PITTSBURGH II a PHILADELPHIA o CHICAGO 0.010.05 0.2 0.5 1 2 5 10 20 30 40 50 60 70 80 90 95 98 99 99.8 99.9 99.99 PERCENT TIME ABOVE Figure III-7. Probability Vs. Percent S02 Removal ------- Ul CO 100 99.99 99.9 99.8 PERCENT LESS THAN 99 98 95 90 80 70 60 50 40 30 20 10 5 21 0.5 0.20.1 0.01 X I I 10 i o LU Q_ 10 i 1 T 1 T r 1 0.010.050.10.2 Q5 1 2 LEGEND: * LOUISVILLE • PITTSBURGH I • PITTSBURGH II a PHILADELPHIA o CHICAGO 'I' I' 1 1 1 1 1 1 1 1 L. 10 20 30 40 50 60 70 80 PERCENT GREATER THAN I I 90 95 98 99 99.8 99.9 99.99 Figure III-8. Probability Vs. 1QO Minus Percent S02 Removal ------- Table III-4. S02 REMOVAL STATISTICS (24-hr. Averaging Period) SITE MEAN SO2 REMOVAL NO. OF POINTS EFFICIENCY, PERCENT GEOMETRIC STANDARD PERCENT DEVIATION 01 Louisville Pittsburgh No. 1 Pittsburgh No. 2 Philadelphia Chicago 89 20 11 8 25 83.8 81.4 85.3 96.8 90.0 1.060 1.057 1.029 1.014 1.015 ------- of these graphical interpretations. The means (converted back to percent removal) ranged from 81.4 to 96.8, while geometric stan- dard deviations ranged from 1.014 to 1.060. Some questions exist regarding the "dampening" of inlet sulfur variations by flue gas scrubbing. Though many parameters enter into the design of FGD systems, the reactivity of the system chemistry and the degree of process control play an important role in dampening of S02 emissions as well as the amount of excess re- actant present. In all the systems monitored, process controls for maintaining the desired reactant concentrations (measured by pH) were usually operated in the manual rather than the automatic mode. Using the values for the mean and geometric standard deviation from Tables III-2 and III-3, the variations in S02 concentration were compared for several confidence levels as shown in Table III-5. The dampening effect is measured by comparing inlet var- iation to outlet variation and is calculated as shown in the table. Since each system is operated under a different set of conditions, e.g., coal fired, boiler loading, type of scrubber module, excess reactant, few conclusions can be drawn. It is noteworthy, how- ever, that a negative dampening is observed for the first batch of Pittsburgh data where pH control was very poor and that a 70 percent dampening resulted when pH control improved. The more reactive sodium, magnesium oxide, and magnesium oxide enriched lime systems showed considerably more dampening than the lime system alone, as would be expected under comparable operating conditions. Table III-5 can be used to illustrate the impact of a "never to be exceeded" regulation where scrubbers are the control of choice. 55 ------- Table III-5. VARIATION IN S02 CONCENTRATIONS IN LB/106 BTU (24-hour averages) 68.7% Confidence Level 95% Percent Dampening = inlet.-outlet x 100 inlet 99.7% Louisville: Inlet Outlet Percent Dampening1 Pittsburgh: #1 Inlet Outlet Percent Dampening #2 Inlet Outlet Percent Dampening Philadelphia: Inlet Outlet Percent Dampening Chicago: Inlet Outlet Percent Dampening ±0.46 ±0.33 28.2 ±0.44 ±0.45 -0.0 ±0.59 ±0.16 72.9 ±0.26 ±0.07 70.8 ±0.76 ±0.13 82.9 ±0.96 ±0.80 15.7 ±0.91 ±1.07 -17.5 ±1.25 ±0.36 71.2 ±0.52 ±0.18 64.7 ±1.60 ±0.28 82.5 ±1.49 ±1.43 4.0 ±1.42 ±1.92 -35.2 ±1.99 ±0.59 70.4 ±0.80 ±0.35 56.8 ±2.55 ±0.46 82.0 56 ------- At the 99.7 percent confidence level the variation in S02 emis- sions is rather large in comparison to the present standard for new coal-fired boilers above 250 MBTU/hr - 1.2 Ib S02 per MBTU input. The best system examined has a ± 0.35 Ib/MBTU variation on a 24-hour basis, implying that a lifetime mean of 0.85 Ib/MBTU SC>2 emissions would be required in order to comply 99.85 percent of the time. The lime system with a ± 1.43 Ib S02/MBTU expectan- cy could not always comply, and would have to average 0.40 Ib S02/MBTU over its lifetime to be in compliance 97.5 out of every 100 24-hour periods or roughly 356 days per year. Finally, the effects of longer averaging periods upon performance were examined. Since insufficient data exists for a rigorous examination, only the Louisville system was considered at 7 and 14-day periods. Figure III-9 and Table III-6 summarize the find- ings. The differences in mean values are due to more data points used in the 24-hour case (89) versus 84 24-hour points in the 7 and 14-day cases. As expected, the geometric standard deviation decreases with in- creased averaging time, increasing the confidence of compliance with a given emission standard or percentage removal requirement. 57 ------- Table III-6. CUMULATIVE LOUISVILLE STATISTICS VS. AVERAGING TIME Averaging Period Percent Recovery 24-hour 7 days 14 days No. of Periods Geometric Mean Geometric STD Deviation 89 83.8 1.06 12 83.1 1.05 6 83.1 1.03 S02 Emissions, lb/106 BTU: No. of Periods Geometric Mean Geometric STD Deviation 89 0.88 1.38 12 0.95 1.2(5 6 0.95 1.17 58 ------- IV. RECOMMENDATIONS AND CONCLUSIONS A. Although the availability of the monitoring systems during the first four months of EPA's study ranged from 56 to 80 percent, most problems were a result of the system design. B. The oxygen monitoring instrumentation is the least reliable piece of equipment in the S02 monitoring system used for this study. Oxygen data by Orsat analysis or a suitable backup system may be necessary on occasions. C. Research was necessary to define the expected sample condi- tions with respect to moisture content, and to develop the most acceptable procedure for moisture measurement or esti- mation. D. Manual data acquisition and reduction has required a very high manpower investment. It is recommended that automatic data systems to acquire the individual instrument outputs and convert to units of the standard, averaged over the specified intervals, be used for routine monitoring. E. SO2 scrubbers do have a dampening effect upon inlet S02 vari- ations over longer 24 hour or greater averaging periods. The instantaneous dampening effect is masked by short-term varia- tions in scrubber performance due to system response lags. Dampening of 70 to 80 percent, as calculated by outlet stan- dard deviation divided by inlet standard deviation, has been shown in these tests on a 24-hour basis. 61 ------- F. Longer averaging periods have the effect of lowering the var- iance of scrubber performance as measured by S02 removal ef- ficiency and outlet S02 emissions. 62 ------- |