United States
Environmental Protection
Agency
Office of Air Quality
Planning and Standards
Research Triangle Park NC 27711
EMB Report 85-CHM-4
August 1985
Air
Neshap Screening
Study
Chromium

Emission Test
Report
Burlington
Industries
Raleigh,
North Carolina

-------
             EMISSION TEST REPORT
            BURLINGTON INDUSTRIES
           RALEIGH,  NORTH CAROLINA
                  ESED 85/02
                      by

       Entropy Environmentalists, Inc.
            Post Office Box 12291
Research Triangle Park, North Carolina   27709
           Contract No. 68-02-3852
            Work Assignment No. 18
                  PN:   3018
               EPA Task Manager
                  Dan Bivins
    U. S. ENVIRONMENTAL PROTECTION AGENCY
         EMISSION MEASUREMENT BRANCH
 EMISSION STANDARDS AND ENGINEERING DIVISION
RESEARCH TRIANGLE PARK, NORTH CAROLINA  27711
                 October 1985

-------
                                    CONTENTS
Figures                                                                    iv

Tables                                                                     v

1.0  INTRODUCTION                                                          1-1

2.0  PROCESS OPERATION                                                     2-1

     2.1  Process Description                                              2-1
     2.2  Air Pollution Control                                            2-1
     2.3  Process Conditions During Testing                                2-1

3.0  SUMMARY OF RESULTS                                                    3-1

     3.1  Particulate Matter, Hexavalent Chromium,  and Total  Chrcmiun       3-3
          3.1.1  Double Mechancial Collector Inlet  at 50%
                  Boiler Capacity                                          3-4
          3.1.2  Double Mechanical Collector Outlet at 50%
                  Boiler Capacity                                          3-8
          3.1.3  Double Mechanical Collector Inlet  at 80%
                  Boiler Capacity                                          3-9
          3.1.4  Double Mechanical Collector Outlet at 80%
                  Boiler Capacity                                          3-13
     3.2  Sunmary of Emissions in Units of Process  Rate and
           Collection Efficiency                                           3-15
          3.2.1  Emissions at 50% Boiler Capacity                          3-17
          3.2.2  Emissions at 80% Boiler Capacity                          3-17
          3.2.3  Conclusions                                               3-17
     3.3  Particle Size Distribution                                       3-18
          3.3.1  Particle Size Distribution at 50%  Boiler Capacity         3-18
          3.3.2  Particle Size Distribution at 80%  Boiler Capacity         3-21
          3.3.3  Conclusions                                               3-21
     3.4  Visible Emissions Observation Data                               3-21
     3.5  Svmmary of Analytical Results for Hexavalent and Total  Chrcmiun   3-22
     3.6  Coal Sample Analysis for F Factor Calculation                    3-28

4.0  SAMPLING LOCATIONS AND TEST METHODS                                   4-1

     4.1  Double Mechanical Collector Inlet
            (Sampling Locations B and C)                                   4-1
     4.2  Double Mechanical Collector Outlet (Sampling Location F)          4-6
     4.3  Coal Feed (Sampling Location A)                                  4-8
     4.4  Primary and Secondary Multiclone Hoppers
            (Sampling Locations D and E)                                   4-8
     4.5  Bottom Ash (Sampling Location G)                                 4-8
     4.6  Velocity and Gas Temperature                                     4-8
     4.7  Molecular Weight                                                 4-9
     4.8  Particulate Matter                                               4-9
     4.9  Particle Size Distribution                                       4-10
     4.10 Hexavalent Chrcmiun Content                                      4-10
     4.11 Total Chrcmiun Content                                           4-11
     4.12 Visible Emissions                                                4-11

5.0  QUALITY ASSURANCE                                                     5-1
                                         ii

-------
                              CONTENTS (Continued)
APPENDICES
     A   TEST RESULTS AND EXAMPLE CALCULATIONS                             A-1
         Particulate, Hexavalent Chromium and Total Chromium               A-3
         Example Particulate Test Calculations                             A-9
         Particle Size for Total Particulate, Hexavalent Chromium          A-42
           and Total Chromium
         Summary of Hexavalent Chromium Particle Sizing                    A-90
         Summary of Total Chromium Particle Sizing                         A-92
         Total Chromium Analysis Calculation                               A-94
         Explanation of Total Chromium Analysis Calculation Table          A-97

     B   FIELD AND ANALYTICAL DATA                                         B-1
         Particulate Matter                                                B-3
         Particle Size Distribution                                        B-49
         Inlet Flow Angle Data                                             B-74
         Total Particulate Analysis                                        B-76
         Particle Size Distribution Analysis                               B-88
         Coal Analysis                                                     B-97
         Hexavalent Chromium Analysis                                      B-99
         Total Chromium Analysis                                           B-107

     C   VISIBLE EMISSIONS OBSERVATION DATA                                C-1

     D   SAMPLING AND ANALYTICAL PROCEDURES                                D-1
         Determination of Total Particulate Emissions                      D-3
         Determination of Hexavalent Chromium Emissions                    D-8
         Determination of Particle Size Distribution                       D-23
         Determination of Total Chromium Content                           D-15
         Grab Samples                                                      D-29

     E   CALIBRATION AND QUALITY ASSURANCE DATA                            E-1

     F   MRI PROCESS DATA                                                  F-1

     G   TEST PARTICIPANTS AND OBSERVERS                                   G-1
                                         iii

-------
                                    FIGURES

Nunber                                                                   Page

2-1  Schematic Representation of Boiler No. 4                             2-3

4-1  Simplified Process Air Flow Diagram of Boiler No.  4  and Emission
       Control Eqiupment at Burlington Industries  Wake  Finishing Plant     4-2

4-2  Double Mechanical Collector Inlet (Sampling Locations B and C)        4-4

4-3  Double Mechanical Collector Outlet (Sampling  Location F)              4-7
                                       iv

-------
                                     TABLES

Number                                                                   Page

2.1  Process Operating Conditions,  Run 1a, February  12,  1985               2-4

2.2  Process Operating Conditions,  Run 2a, February  13,  1985               2-5

2.3  Process Operating Conditions,  Run 3a, February  14,  1985               2-6

2.4  Process Operation Conditions,  Run 1b, February  15,  1985               2-7

2.5  Process Operating Conditions,  Run 2b, February  18,  1985               2-8

2.6  Process Operating Conditions,  Run 3b, February  19,  1985               2-9

3.1  Testing Schedule for Burlington Industries                            3-2

3.2  Summary of Flue Gas Conditions for 50% Boiler Capacity                3-5

3.3  Summary of Particulate,  Hexavalent Chromiun, and Total
       Chromium Emissions for 50% Boiler  Capacity                          3-7

3.4  Summary of Flue Gas Conditions for 80% Boiler Capacity                3-10

3.5  Summary of Particulate,  Hexavalent Chromiun, and Total Chromium
       Emissions for 80% Boiler Capacity                                   3-12

3.6  Sunmary of Emission Rates in Units of Process Rate  and
       Efficiency                                                         3-16

3.7  Sunmary of Particle Size Distribution at 50% Boiler Capacity          3-19

3.8  Summary of Particle Size Distribution at 80% Boiler Capacity          3-20

3.9  Summary of Visible Emissions Data for All Runs  Boiler No. 4
       Mechanical Collector Outlet                                         3-23

3.10 Summary of Analytical Results  for Hexavalent and Total
       Chromium at 50% Boiler Capacity                                  '  3-24

3.11 Summary of Analytical Results  for Hexavalent and Total
       Chromiun at 80% Boiler Capacity                                    3-26

3.12 Summary of Analytical Results  for Hexavalent and Total
       Chromiun Quality Assurance Samples                                 3-29

3.13 Coal Analysis                                                        3-30

4.1  Sampling Plan for Burlington Industries                               4-3

5.1  Field Equipment Calibration                                          5-2

5.2  Particle Size Blank Filter and Reactivity Filter Analysis             5-5

5.3  Audit Report Chromiun Analysis                                       5-6

-------
                               1.0  INTRODUCTION


     During the weeks of February 11 and 18, 1985,  Entropy Environmentalists,

Inc. conducted an emission measurement program at Burlington Industries'  Wake

Finishing Plant located in Raleigh,  North Carolina.  The purpose of this

program was to provide data for a screening study to determine the quantity and

form of chromium emissions associated with combustion of coal in industrial

boilers.

     Comprehensive testing was conducted on a coal-fired traveling-grate

spreader stoker industrial boiler whose emissions are controlled by a double

mechanical collector (two multiclones in series).  Tests were performed at both

50 percent and 80 percent of the boiler capacity.

     The double mechanical collector at this plant was selected for source-

testing for the following reasons:


     o    Spreader stokers are typical of coal-fired industrial
          boilers producing less than 250 x 10  Btu/hour.  Spreader
          stokers account for approximately 34 percent of bituminous coal
          consumption sources (see Table 1-1).  Dry-bottom pulverized
          units account for approximately 49 percent of bituminous
          combustion, but are more prevalent in boilers producing greater
          than 250 x 106 Btu/h.

     o    The particulate emission control technology and its removal
          efficiency are representative of those found on other coal-fired
          industrial boilers producing less than 250 x 10  Btu/h.

     o    Inlet and outlet sampling ports are already available.

     o    Chromium content of coal burned at this plant is typical of
          eastern U. S. coal (15-20 ppm Cr).
                                      1-1

-------
TABLE 1.1.  ESTIMATED INDUSTRIAL COAL  USED  BY  COMBUSTION SYSTEM
                                       Fuel  used,
        Fuel  type                        PJ/yr
        Coal                              1,540

          Bituminous                     1,490
            Pulverized, dry                730
            Pulverized, wet                150
            Cyclone                         40
            Spreader stokers               510
            Other stokers                   60

          Anthracite                        10
            All stokers                     10

          Lignite                           40
            Spreader stokers                40
                              1-2

-------
     Particulate concentrations and mass emission rates were measured at the




double mechanical collector inlet and outlet using U. S. Environmental




Protection Agency (EPA) Reference Method 5.*  Total chromium concentrations and




hexavalent chromium concentrations were measured at the same locations by




further analysis of the Method 5 samples using the alternate sample preparation




and analytical procedures as described in Appendix D.  Flue gas flow rates,




temperature, moisture content, and composition [oxygen (02), carbon dioxide




(CO,), and carbon monoxide (CO)] were measured in conjunction with the




particulate tests.  In addition, the particle size distribution of particulate




matter entering and exiting the double mechanical collector was determined




along with hexavalent and total chromium distribution by particle size.




Visible emission observations were made on the exit stack  after the collector




using EPA Reference Method 9.*




     Representative samples of (1) the coal used to fire the boiler, (2)




multiclone hopper ash, and (3) bottom ash were collected during the particulate




tests for determination of hexavalent and total chromium content.




     Mr. Dwight Atkinson  [Midwest Research Institute (MRI)] monitored process




operation throughout the test period.  Mr. Dan Bivins (EPA Task Manager) of the




Emission Measurement Branch (EMB) and Mr. Ron Myers of the Industrial Studies




Branch (ISB) observed the test program.  Mr. Gene Swift, Plant Engineer, and




Mr. Glee Nowell, served as the contacts for Burlington Industries.




     This report is organized into several sections addressing various aspects




of the testing program.  Immediately following this introduction is the




"Process Operation" section which includes a description of the process.and




control device tested.  Following this is the "Summary of  Results" section
    40 CFR 60, Appendix A, Reference Methods 5, 9 July  1,  1981.
                                       1-3

-------
which presents table summaries of the test data and discusses these results.




The next section, "Sampling Locations and Test Methods" describes and




illustrates the sampling locations for emissions testing and grab sampling and




then explains the sampling strategies used.  The final section, "Quality




Assurance," notes the procedures used to ensure the integrity of the sampling




program.  The Appendices present the complete Test Results and Example




Calculations (Appendix A); Field and Analytical Data (Appendix B);  Control




Device Collection Data (Appendix C); Sampling and Analytical Procedures




(Appendix D); Calibration Data (Appendix E);  MRI Process Data (Appendix F);  and




Test Participants and Observers (Appendix G).
                                      1-4

-------
2.0  PROCESS OPERATION
2.1  PROCESS DESCRIPTION
     Burlington Industries boiler No. 4 1s a traveling-grate,
spreader-stoker, coal-fired Industrial boiler (see Figure 2-1).  The
traveling-grate stoker was manufactured by the Detroit Rotostoker Company,
and Its boiler was manufactured by the Zurn Corporation.  They were both
Installed 1n 1977.
     The traveling-grate boiler has a rated steam production capacity of
68,000 kilograms per hour (kg/h) (150,000 pounds per hour [lb/h]) and
typically produces 29,000 kg/h (64,000 Ib/h) of steam.  It operates
24 hours per day, 5 to 6 days per week.
     The traveling-grate boiler 1s fueled by coal from the Island Creek
Mine 1n Kentucky.  This coal has an ash content of 5.5 to 7.5 percent.
2.2  AIR POLLUTION CONTROL
     Exhaust gases from the traveling-grate boiler are routed through an
economizer for heat recovery prior to entering a series of two
multlclones, collectively referred to as a double mechanical collector,
for particle removal.  The first and second multlclones typically operate
at pressure drops of 0.62 kllopascals (kPa) (2.5 Inches of water column
[1n. w.c.J) and 0.75 kPa (3.0 1n. w.c.), respectively.  The double
mechanical collector was manufactured by Zurn Corporation.
2.3  PROCESS CONDITIONS DURING TESTING
     All processes were operated normally during emission testing.  The
following parameters were monitored and recorded every 15 minutes during
testing:  steam flow, steam pressure, undergrate air flow return water
pressure, return water temperature, undergrate air pressure, furnace
pressure, boiler draft, air heater outdraft, outlet draft on collectors
No. 1 and No. 2, overfire air, air heater differential pressure grate
temperature, and coal consumption.  Tables 2-1 through 2-6 present the
process parameters monitored and operating conditions during the tests.  A
log of the actual steamflow rate (k lb/h) during each test is included in
Appendix p.
     A total of six test runs were conducted, Nos. 1A, 2A, and 3A at
50 percent boiler capacity and Nos. IB, 2B, and 3B at 80 percent boiler
                                    2-1

-------
capacity.  Test run Nos. 1A, 2A, and 3A were approximately 4 hours 1n
length per run.  Two Interruptions and one delay were noted during run
Nos. 1A and 3A.  During run No. 1A, the use of a toaster oven by a plant
employee caused a 30 second power outage due to an overloaded circuit.
Run No. 3A was delayed for about 30 minutes due to a test equipment
leak.  A 20 percent drop 1n steam flowrate was noted approximately
45 minutes after Run 3A started due to an unexpected production shutdown
1n the plant.  Steam production returned to approximately 50 percent of
capacity within 15 minutes and testing was not halted.
     There were no Interruptions 1n run Nos. IB, 28, and 38, which were at
80 percent capacity.  These runs were each approximately 2 hours 1n
length.  However, during run No. 28, initial erratic flowrate readings
caused the run to be delayed 1 hour and 20 minutes.
     During all six runs, boiler No. 4 operated entirely on coal mined
from the Island Creek Mine in Kentucky.
                                    2-2

-------
ro

CO
                                                         Economizer
                                                                                 Stack
                                                        f Air Heater

                                                        B and  C
                                                        Primary
                                                       Multiclone
Secondary
Multiclone
                                                                                  Fan
                           Figure 2-1.   Schematic representation of  Boiler No.  4.

-------
TABLE 2-1.  PROCESS OPERATING CONDITIONS, RUN 1A, FEBRUARY 12, 1985


Tine
09:50
10:00
10:15
10:30
10:45
10:55
11:00
11:15
11:30
11:45
12:00
12:15
ro 12:3°
i 12:45
•** 13:00
13:15
13:30
13:45
14:00
14:15
14:18
14:35
Stean Steam
flow, pressure,
K Ib/h PSI
Under- Uider-
grate grate
air Return Return air
flow, water water pressure.
no pressure, temp.
units
PSI 'f
in. of
water
Furnace
pressure.
in. of
water
Boiler
draft.
in. of
water
Air
heater
out
draft.
in. of
water
Outlet
draft
No. 1
collector,
in. of
water
Collector
No. 1
P.
in. of
water
Outlet
draft
No. 2
collect.
in. of
water
Col lector
No. 2
P.
in. of
water
finished cleaning hoppers
82 130
80 130
86 ' 130
78 130
toaster causes
85 130
80 131
80 130
80 130
80 131
80 130
82 130
80 131
80 131
84 130
79 131
85 128
78 129
74 129
end Method 5
80 131
82
77
83
78
power loss
82
77
77
78
79
78
79
77
78
79
77
83
80
72

75
287 222
293 222
280 222
285 222
appro* inat el y
292 222
287 222
291 222
290 222
287 222
288 222
290 222
291 222
289 222
287 222
287 222
290 222
290 222
288 222

287 222
1.4
1.3
1.3
1.3
30 s
1.3
1.2
1.2
1.3
1.2
1.2
1.2
1.3
1.2
1.3
1.2
1.4
1.2
1.2

1.2
-0.03
-0.02
-0.03
-0.03

-0.02
-0.02
-0.02
-0.02
-0.02
-0.02
-0.02
-0.02
-0.02
-0.02
-0.02
-0.02
-0.02
-0.02

-6.02
-0.6
-0.6
-0.6
-0.6

-0.6
-0.6
-0.6
-0.6
-0.6
-0.6
-0.6
-0.6
-0.5
-0.6
-0.6
-0.6
-0.6
-0.5

-0.5
-1.2
-1.2
-1.2
-1.2

-1.2
-1.2
-1.1
_,-!.!
-1.0
-1.2
-1.1
-1.1
-1.0
-1.0
-1.1
-1.1
-1.1
-1.0

-1.2
-3.0
-3.0
-3.0
-3.0

-3.2
-3.0
-2.8
-2.8
-2.8
-3.0
-2.8
-3.0
-3.0
-3.0
-3.0
-3.1
-3.0
-2.6

-2.5
1.8
1.8
1.8
1.8

2.0
1.8
1.7
1.7
1.8
1.8
1.7
1.9
2.0
2.0
1.9
2.0
1.9
1.6

1.3
-5.0
-4.9
-4.9
-4.5

-5.0
-4.9
-4.5
-4.8
-4.2
-4.6
-4.5
-4.8
-4.6
-4.6
-4.8
-5.0
-4.2
-4.4

-4.5
2.0
1.9
1.9
1.5

1.8
1.9
1.7
2.0
1.4
.6
.7
.6
.6
.6
.8
.9
.2
1.8

2.0
Over-
fire
air.
in.
of
water
\
15
15
15
17

18
17
16
17
16
18
17
17
17
17
17
18
16
16

17
Air
heater
differ-
ential.
in. of
water

0.5
0.5
0.5
0.5

0.6
0.5
0.5
0.5
0.5
0.5
0.5
0.6
0.5
0.5
0.5
0.6
0.5
0.5

0.5
Grate
te«p. .
•F

300
302
303
303

318
298
305
304
305
305
305
305
305
305
310
304
305
305

305
Coal
feed
Ib/h,
xlO

13.6

13.6


16

16

16

15.2

14.4

14.4

19.2


16

-------
                         TABLE 2-2.  PROCESS OPERATING CONDITIONS, RUN 2a, FEBRUARY  13,  1985
ro
i
en



Stean
flow.
Tine K Ib/h
Under-
grate
air
Stean flow.
pressure, no
PSI units


Return
water
pressure.
PSI
Under-
grate
Return air
water pressure.
te«p. , in. of
°F water


Furnace
pressure.
in. of
water


Boi ler
draft.
in. of
water
Air
heater
out
draft.
in. of
water
Out let
Outlet
draft Collector draft
No. 1 Ho. 1 No. 2
collector,
P. collect.
in. of in. of in. of
water water water

Col lector
No. 2
P.
in. of
water
Over- Air
fire heater
air. differ-
in, ential.
of in. of
water water
\


Coal
Grate feed
leap.. ID/h.
•F xlO
09:45 finished cleaning hoppers
10:00 79
10:15 80
10:30 84
10:45 80
11:00 82
11:15 78
11:30 80
11:45 80
12:00 80
12:15 80
12:30 80
12:45 80
13:00 80
13:15 81
13:30 80
13:45 80
14:00 80
14:15 83
14:30 75
14:45 83
129 80
130 82
' 130 85
132 80
132 85
130 80
130 80
130 80
130 80
130 80
130 80
130 80
135 79
130 79
130 79
130 80
130 80
130 82
130 78
130 80
287
286
286
275
273
272
272
265
255
255
250
250
250
250
250
245
250
250
240
240
222 .1
222 .1
222 .2
222 .0
222 .1
222 .1
222 .1
222 .1
222 .1
222 .1
222 .1
222 .1
222 .1
222 .1
222 .2
222 .1
222 .2
222 .2
222 .1
222 .1
-0.1
-0.2
-0.1
-0.1
-0.1
-0.1
-0.1
-0.15
-0.15
-0.1
-0.05
-0.05
-0.05
-0.05
-0.05
-0.05
-0.05
-0.05
-0.05
-0.1
-0.6
-0.6
-0.6
-0.6
-0.6
-0.6
-0.6
-0.6
-0.6
-0.5
-0.5
-0.5
-0.5
-0.5
-0.6
-0.6
-0.6
-0.6
-0.6
-0.6
-1.2
-1.2
- .1
- .1
- .2
- .1
- .1
- .2
- .2
- .1
- .1
- .0
- .0
- .0
- .0
- .0
- .2
- .0
- .0
- .0
-3.0
-3.0
-3.0
-3.0
-3.5
-3.0
-3.0
-3.0
-3.0
-3.0
.8 -5.0
.8 -5.0
.9 -5.0
.9 -5.0
.3 -5.0
.9 -4.5
.9 -5.0
.8 -5.0
.8 -5.0
.9 -5.0
-3.0 1.9 -5.0
-3.0 2.0 -4.5
-3.0 2.0 -4.5
-3.0 2.0 -4.5
-3.0 2.0 -5.0
-2.5
-3.0
1.5 -4.5
1.8 -4.5
-3.0 2.0 -5.0
-3.0 2.0 -4.5
-3.0 2.0 -4.5
2.0
2.0
2.0
2.0
1.5
1.5
2.0
2.0
2.0
2.0
2.0
1.5
1.5
1.5
2.0
2.0
1.5
2.0
1.5
l.S
17 0.5
18 0.5
19 0.6
18 0.6
19 0.6
18 0.5
18 0.6
17 0.6
17 0.55
18 0. 55
18 0.6
18 0. 55
18 0. 55
18 0.55
18 0.60
17 0.55
17 0.6
18 0.6
17 0.55
17 0.50
305 13.6
306
309 15.2
309
311 16
310
312 13.6
310
311 16.8
312
308 14.4
311
312 15.2
310
310 16
311
312 14.4
310
311 16
311
14:45 end Method 5
15:00 80
130 80
265
222 1.1
-0.1
0.6
-1.0
-3.0 2.0 -4.5
1.5
15 0.50
310 16

-------
                        TABLE 2-3.   PROCESS  OPERATING CONDITIONS,  RUN 3a,  FEBRUARY 14, 1985
o>





Tine
09:45
10:00
10:15
Due to
10:30
10:45
11:00
11:15
11:15
11:30
11:45
12:00
12:15
12:30
12:45
13:00
13:15
13:30
13:45
14:00
14:15
14:30
14:45
15:00
15:05
15:10
15:15
15:25
Under-
grate
air Return
Stean Stean flow. water
flow, pressure, no pressure.
K Ib/h PSI units PSI
finished cleaning ash hoppers
79 129 80 26S
82 . 129 81 265
problem with leak will start at 10:
80 127 80 260
74 130 75 260
78 130 78 255
drastic drop in flow rate due to
70 130 73 260
83 130 82 250
80 130 81 255
80 130 80 245
77 130 80 250
82 130 80 255
81 130 80 255
82 130 81 255
82 130 82 255
80 130 78 255
80 130 82 250
78 130 80 250
83 130 85 250
81 128 80 245
77 128 77 245
80 130 80 250
end Method 5 testing
particle size sample destroyed.
83 130 82 245
test cooplete
Uhder-
grate
Return air
water pressure
tenp. , in. of
°F water

222 .0
222 .0
30
222 .0
222 .0
222 .0
shut off in lant
222 .0
222 .2
222 .2
222 .2
222 .0
222
222
222
222
222
222
222
222 . 5
222
222
222



Furnace
, pressure.
in. of
water

-0.1
-0.1

-0.1
-0.05
-0.05
(niniaun at
-0.1
-0.05
-0.05
-0.05
-0.05
-0.05
-0.05
-0.05
-0.05
-0.05
--0.05
-0.05
-0.05
-0.05
-0.05
-0.05

Air
heater
Boiler out
draft. draft.
In. of in. of
water water

-0.6 -1.0
-0.6 -1.0

-0.6 - .0
-0.6 - .0
-0.6 - .0
11:05 (65)) ste n off
-0.55 - .0
-0.6 - .0
-0.6 - .0
-0.6 - .0
-0.55 - .0
-0.6 - .0
-0.6 - .0
-0.6 - .0
-0.6 - .0
-0.6 - .0
-0.6 - .0
-0.55 - .0
-0.55 - .1
-0.55 - .1
-0.55 - .1
-0.55 - .1

Outlet

draft Collector
No. 1
collector,
in. of
water

-3.0
-3.2

-3.0
-2.6
-3.0
in nain plant
-2.8
-3.0
-3.0
-3.0
-3.0
-3.0
-3.0
-3.0
-3.0 •
-3.X)
-3.0
-3.0
-3.0
-3.0
-3.0
-3.0

No. 1
P.
in. of
water

2.0
2.2

2.0
1.6
2.0

1.8
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9

Outlet
Over-
draft Collector fire
No. 2 No. 2 air.
collect.
P. in.
in. of in. of of
water water water


-5.0 2.0 17
-5.0

-5.0 i
-4.5
-4.5

-4.2
.8 17

'.0 16
.9 15
.5 17

.4 17
-5.0 2.0 17
-5.0 2.0 17
-5.0 2.0 17
• -4.5
-4.5
-4.5
-4.5
-4.5
-4.5
-4.5
-4.5
-5.0
-4.5
-4.2
-4.5

.5 16
.5 16
.5 18
.5 18
.5 18
.5 18
.5 17
.5 18
.0 18
.5 18
.2 17
.5 18

Air
heater
differ-
ential.
in. of
water

0.6
0.6

0.55
0.5
0.55

0.5
0.6
0.6
0.6
0.55
0.55
0.55
0.55
0.6
0.6
0.55
0.6
0.6
0.6
0.5
0.6




Grate
te.p..
•F

299
302

306
309
309

309
308
308
308
309
309
309
309
309
309
309
308
307
307
306
308



Coal
feed
Ib/h,
xlO

14.4


15.2

14.4


15.2

16

15.2

15.2

15.2

14.4

15.2

15.2

Retake- -will finish at 15:20
222 1.1

-0.05

-0.3 -1.2

-3.0

1.8

-4.5

1.5 17

0.55

309




-------
TABLE 2-4.  PROCESS OPERATING CONDITIONS, RUN Ib. FEBRUARY 15. 1985





Tine
09:30
09:30
10:00
10:15
10:30
10:45
11:00
11:15
11:30
11:45
11:45
12:00
12:15
ro i2:2o
Under-
grate
air Return
Steaa Steaa flow, water
flow, pressure, no pressure.
K Ib/h PSI units PSI
finished cleaning ash hoppers
prelininary test beginning
128 . 130 128 230
128 130 128 230
130 130 133 230
132 130 133 228
128 130 130 228
132 130 134 225
135 130 135 222
133 130 135 222
testing cooplete "Method 5"
133 130 133 222
130 130 130 222
end of testing


Return
water
teap..
•F


222
222
222
222
222
222
222
222

222
222

Uhder-
grate
air
pressure.
in. of
water


2.2
2.2
2.2
2.3
2.2
2.4
2.4
2.4

2.4
2.4



Furnace Boi ler
pressure, draft.
in. of in. of
water water


-0.05 - .2
-0.05 - .2
-0.07 - .2
-0.05 - .2
-0.05 - .2
-0.07 - .2
-0.05 - .2
-0.05 - .2

-0.05 - .2
-0.05 - .2

Air
heater
out
draft.
in. of
water


-2.5
-2.5
-2.5
-2.5
-7.5
-2.5
-2.5
-2.5

-2.5
-2.2

Outlet
draft
No. 1
collector,
in. of
water


-7.0
-7.0
-6.0
-7.0
-7.0
-6.5
-7.0
-7.0

-7.0
-6.5


Collector
No. 1
P.
in. of
water


4.5
4.5
3.5
4.5
4.5
4.0
4.5
4.5

4.5
4.3

Outlet
draft
No. 2
collect.
In. of
water


-11
-11
-11
-11
-11
-11
-11
-11

-11
-11


Col lector
No. 2
P.
in. of
water


4.0
4.0
5.0
4.0
4.0
4.5
4.0
4.0

4.0
4.5

Over- Air
fire heater
air. differ-
in, ential.
of In. of
water water


25 .5
25 .5
24 .5
24 .5
24 .5
25 .5
25 .5
25 .5

25 1.5
24 1.5



Coal
Orate feed
teap. , Ib/h.
•F xlO


330 23.2
332
332 23.2
334
335 23.2
335
336 25.6
337

337 24.0
337


-------
TABLE 2-5.  PROCESS OPERATING CONDITIONS, RUN 2b, FEBRUARY 18, 1985
Under-
grate

air Return Return
Stean Stean flow. water
water
flow, pressure, no pressure, teip. ,
Ti«e K Ib/h PSI units PSI
•F
Under-
grate
air
pressure.
in. of
water

Furnace
pressure.
in. of
water

Boi ler
draft.
in. of
water-
Air
heater
out
draft.
In. of
water
Outlet
draft Collector
No. 1
collector.
in. of
water
No. 1
P.
in. of
water
Outlet
draft Col lector
Ho. 2
collect.
in. of
water
No. 2
P.
in. of
water
Over-
fire
air.
in.
of
water
Air
heater
differ-
ential.
in. of
water


Grate
te»p..
•F

Coal
feed
In/h.
xlO
09:45 finished cleaning ash out of hoppers
10:00 144 130 129 230
10:15 144 ' 130 134 175
Can't start test on tine. Flowrate too
10:30 148 137 145 180
10:45 146 130 145 160
11:00 138 130 135 180
11:15 128 130 130 195
11:20 start Method 5 testing
11:30 130 130 128 195
11:45 135 130 133 185
12:00 128 130 135 195
12:15 138 130 135 190
"J° 12:25 flowrate capacity at 149
00 12:30 149 130 133 175
12:40 flowrate capacity at 118
12:45 126 130 126 205
12:50 120 127 124 195
12:50 end Method 5 testing
219
220
erratic.
219
224
221
219

221
220
221
221

218

220
222

2.2
2.5

2.4
2.3
2.3
2.3

2.3
2.4
2.2
2.2

2.2

2.2
2.2

-0.05
-0.1

-0.05
-0.05
-0.1
-0.1

-0.05
-0.05
-0.05
-0.03

0.0

-0.03
-0.05

-1.2
-1.4

-1.3
-1.2
-1.2
-1.2

-1.2
-1.2
-1.2
-1.2

-1.2

-1.2
-1.1

-2.5
-2.5

-2.5
-2.4
-2.3
-2.2

-2.0
-2.5
-2.5
-2.2

-2.2

-2.2
-2.0

-6.5
-7.5

-7.0
-6.5
-6.5
-6.5

-6.5
-6.5
-6.5
-6.7

-6.5

-6.5
-6.2

4.0
5.0

4.5
4.1
4.2
4.2

4.5
4.0
4.0
4.5

4.3

4.3
4.2

-12
-12

-12
-12
-12
-11

-10
-11
-11
-11

-11

-10
-10

5.5
4.5

5.0
5.5
S.S
4.5

3.5
4.5
4.5
4.3

4.5

3.5
3.8

23
23

22
24
23
23

22
23
24
24

22

24.5
22

1.45
1.65

1.5
1.45
1.45
1.45

1.4
1.4
1.4
1.5

1.5

1.4
1.35

320
326

331
335
338
340

339
340
340
342

343

346
346

23.2


28.8

24.8


34

25.6


20.8


20.0


-------
                         TABLE 2-6.  PROCESS OPERATING CONDITIONS, RUN 3b. FEBRUARY 19,  1985
ro
i
UD





Tine
09:45
10:00
10:15
10:30
10:45
11:00
11:15
11:20
11:20
11:30
11:45
Testing
Under-
grate
air Return
Stean Stean flow, water
flow, pressure, no pressure.
K Ib/h PSI units PSI


Return
water
leap. ,
•F
Uhder-
grate
air
pressure.
in. of
water


Furnace Boiler
pressure. draft.
in. of in. of
water water
Air
heater
out
draft.
in. of
water
Outlet
draft
No. 1
collector.
in. of
water

Collector
No. 1
P.
in. of
water
Outlet
draft
No. 2
collect.
in. of
water

Col lector
No. 2
P.
in. of
water
Over- Air
fire heater
air. differ-
in, ential.
of In. of
water water


Coal
Grate feed
top. . Ib/h.
•F xUT
finished cleaning ash out of hoppers
126 130 130 230
128 • 130 127 200
126 130 129 230
130 130 131 230
129 130 128 230
128 130 128 225
stop Method 5 testing
128 130 128 220
126 130 128 210
128 130 128 220
couplete February 19, 1985
219
221
222
221
219
221

222
222
222

2.0
2.0
2.1
2.2
2.2
2.2

2.2
2.2
2.2

-0.05 - .2
-0.05 - .2
-0.05 - .2
-0.1 - .2
0.0 - .2
-0.05 - .2

-0.05 - .2
-0.05 - .2
-0.05 - .1

-2.1
-2.0
-2.2
-2.2
-2.1
-2.2

-2.2
-2.1
-2.1

-6.2
-6.0
-6.5
-6.5
-6.5
-6.2

-6.2
-6.5
-6.5

4.1
4.0
4.3
4.3
.4
.0

.0
.1
.1

-10
-10
-10.5
-11
-10
-10.5

-10
-10
-10

3.8
4.0
4.0
4.5
3.5
4.3

3.8
3.5
3.5

22 .35
23 .35
29 .40
30 .45
21 .45
22 .45

20 .45
20 .45
21 .45

330 24.0
333
335 25.6
340
340 24.0
338

337
337 24.0
337


-------
                            3.0  SUMMARY OF  RESULTS








     Particulate matter and particle size distribution  tests were conducted at




the double mechanical collector inlet (boiler outlet) and  the double mechanical




collector outlet (stack exit or emissions discharge)  at 50 percent and 80




percent boiler capacity.  Table 3.1  summarizes the testing schedule.




     In brief, the uncontrolled emissions from the boiler  averaged 415 pounds




per hour of particulate matter (4.7  pounds per million  Btu), 0.00024 pounds per




hour of hexavalent chromium, and 0.075 pounds per hour  of  total  chromium at 50%




of boiler capacity.  The controlled  emissions averaged  30  pounds per hour of




particulate matter (0.35 pounds per  million  Btu),  0.00017  pounds per hour of




hexavalent chromium, and 0.01 pounds per hour of total  chromium  at 50% of




boiler capacity.  The resulting collection efficiency of the double mechanical




collector was 92.7% for particulate  matter,  25.9% for hexavalent chromium, and




86.5% for total chromium.




     At 80% of boiler capacity, the  uncontrolled emissions averaged 1370 pounds




per hour of particulate matter (8.9  pounds per million  Btu), 0.00062 pounds per




hour of hexavalent chromium, and 0.21 pounds per hour of total chromium.  The




controlled emissions averaged 64 pounds per  hour of  particulate  matter (0.49




pounds per million Btu), 0.00062 pounds per  hour of  hexavalent chromium, and




0.034 pounds per hour of total chromium.  The resulting collection efficiency




of the double mechanical collector was 94.5% for particulate matter, no  removal




for hexavalent chromium, and 80.3% for total chromium.




     Based on the coal data, the emissions from the  boiler were  greater  than




expected, with uncontrolled emissions of 4.7 and 8.9 pounds per  million  Btu at




50% and 80% boiler capacity, respectively.   The double mechanical collector




exhibited a typical collection efficiency for particulate  matter of 93 and




95 percent at the two boiler capacities.  The particle  size distribution
                                      3-1

-------
                                         TABLE  3.1.   TESTING SCHEDULE FOR BURLINGTON INDUSTRIES
U)



NJ
Date
(1985)
2/12
2/13
2/14
2/15
2/18
2/19
Sample Type
Participate
Particle size
Particle size
Participate
Particle size
Particle size
Particle size
reactivity
Participate
Particle size
Particle size
Participate
Particle size
Particle size
Participate
Particle size
Particle size
Participate
Particle size
Particle size
Mechanical Collector
Inlet - East
Run
No.
IB
SIB
28
S2B
3B
S3B
4B
S4B
5B
S5B
6B
S6B
Test Time
24 h clock
1000-1223
1323-1328
1000-1241
1319-1323:30
1250-1505
1520-1525
1030-1143
1209-1211:45
1120-1235
1247-1250:15
1000-1112
1119-1122:55
Mechanical Collector
Inlet - West
Run
No.
1C
SIC
2C
S2C
3C
S3C
4C
S4C
5C
S5C
6C
S6C
Test Time
24 h clock
1200-1409
1138-1143
1200-1409
1111-1116
1030-1243
1139-1344
1030-1140
1222-1225
1120-1228
1233-1236
1000-1108
1114-1117
Mechanical Collector
Outlet
Run
No.
IF
S1F1
S1F2
IF
S2F1
S2F2
S2FR
3F
S3F1
S3F2
4F
S4F1
S4F2
5F
S5F1
S5F2
6F
S6F1
S6F2
Test Time
24 h clock
1000-1418
1254-1318
1356-1420
1000-1415
1115-1135
1324-1344
1220-1240
1030-1451
1140-1200
1252-1312
1031-1144
1032-1052
1126-1146
1120-1228
1120-1140
1212-1232
1000-1105
1006-1026
1052-1112

-------
results were also typical for an industrial boiler and demonstrated that the




double mechanical collector collected the majority of all particles greater




than 10 ym in diameter and only about one third of the particles less than 5 Pm




in diameter.  As a result of the size-specific control efficiency, the




hexavalent chromium collection efficiency was very low (less than 25 percent).




This would be expected since the majority of the hexavalent chromium was in the




particle size range of 5 vm or less.  The collection efficiency and particle




size distribution for total chromium were similar to that for the particulate




matter, but showed some dependency towards the smaller particles.  This




dependency is most likely due to the fact that the larger particles consist




mostly of unburned combustibles and that in all particles the total chromium to




ash ratio should remain consistent (both being noncombustible)  with only the




amount of combustibles present changing.  The dependency, then, has little or




nothing to do with the fact that total chromium would form in the smaller size




range.  And, thus, no particle size dependency would be expected in a




pulverized coal firing situation where almost all of the combustibles would be




utilized.




     In the following sections, the results addressed above and additional




results are presented and discussed in detail according to the emission type




and sampling location.  The computer printouts of the emission calculations can




be found in Appendix A.  The original field data sheets and the analytical data




are located in Appendix B.








3.1  PARTICULATE MATTER, HEXAVALENT CHROMIUM, AND TOTAL CHROMIUM




     Particulate matter tests (EPA Method 5) along with the determination of




the associated flue gas flow rate were conducted at both the mechanical




collector outlet and inlet (boiler outlet).  Due to the configuration of the




double mechanical collector inlet (boiler outlet) sampling location and the




heavy particulate emissions loading, it was decided that a separate run would
                                      3-3

-------
be conducted at each half of the duct and then the results  combined.  The




particulate matter samples were initally analyzed using gravimetric techniques




to determine the mass of particulate matter.   Then the samples  were further




analyzed for hexavalent and total chromium.   Complete descriptions  of each




sampling location and the sampling and analytical procedures are given  in




Chapter 4.







3.1.1  Double Mechanical Collector Inlet at 50% Boiler Capacity




     The double mechanical collector inlet represents the uncontrolled




emissions from the boiler.  Separate particulate matter runs were made  on the




east half and west half of the duct.  Two-hour inlet runs were  conducted




sequentially to correspond with the one four-hour outlet test run.




     Flue Gas Conditions and Isokinetic Sampling Rate - A summary of the flue




gas conditions at the boiler outlet (collector inlet) for 50% boiler capacity




is presented in Table 3.2.  The volumetric flow rate conditions were




significantly different for the west and east halves of the duct.  This was a




result of the flow distribution in the duct.   The flow rate at  the  inlet, when




corrected for the dilution air drawn in at the induced draft fan, was very




consistent with the outlet flow rate.  The inlet volumetric flow rate




(composite of the East and West Inlets) averaged 60,200 actual  cubic meters per




hour  (2,130,000 actual cubic feet per hour) with a flue gas temperature of




159°C (318°F), a moisture content of 4.9%, O2 content of 7.6%,  C02




content of 11.6%, and an excess air value of 55%.  The volumetric flow  rate at




standard conditions averaged 38,200 dry standard cubic meters per hour




(1,340,000 dry standard cubic feet per hour).  Standard conditions  are  20°C




(68°F), 760 mm Hg  (29.92 in. Hg), and dry.




     The average inlet and outlet standard volumetric flow rates corrected to




zero percent excess air were 865,000 and 867,000 dry standard cubic feet per
                                      3-4

-------
                                                  TABLE 3.2.   SUMM/KY OF FLUE GAS CONDITIONS F(R  50% BOILER  CAPACITY
CO
en
Run
No.
Date
(1985)
Test Time
24 h clock
Vo 1 umetr I c F 1 ow R ate
Actual3
acmh
x 103
acfh
x 106
Standard15
dscmh
x 103
dscfh
x tO6
Stack
Temperature
°C
°F
Moisture
%
°2
co2
%
EA
%
Isoklnettc
%
                                                            Double Mechanical Collector Inlet East (B)
IB
2B
3B
2/12
2/13
2/14
1000-1223
1000-1214
1250-1505
Average
53.2
53.3
52.0
52.8
1.88
1.88
1.84
1.87
33.5
33.2
32.9
33.2
1.18
1.17
1.16
1.17
153
162
161
159
308
324
321
318
5.9
5.7
5.1
5.6
7.2
8.2
7.5
7.6
12.0
11.5
11.5
11.7
51.0
63.1
54.0
56.0
106.4
106.5
109.8

                                                            Double Mechanical Collector Inlet West (C)
1C
2C
3C
2/12
2/13
2/14
1200-1409
1200-1409
1030-1243
Average
63.8
72.1
67.1
67.7
2.25
2.55
2.37
2.39
40.6
45.5
43.1
43.1
1.43
1.61
1.52
1.52
158
159
159
159
317
319
318
318
3.8
5.0
3.9
4.2
7.3
7.4
7.8
7.5
11.9
11.5
11.2
11.5
52.0
52.8
57.4
54.1
103.0
102.2
102.7

                                                                  Inlet East and West (B and C)
Average
60.2
2.13
38.2
1.34
159
318
4.9
7.6
11.6
55.0

                                                              Double Mechanical Collector Outlet (F)
IF
2F
3F
2/12
2/13
2/14
1000-1418
1000-1415
1030-1451
Average
65.2
66.1
66.3
65.9
2.30
2.33
2.34
' 2.32
42.1
42.6
43.1
42.6
1.49
1.50
1.52
1.50
145
150
150
148
293
302
302
299
5.5
5.4
5.1
5.3
8.6
9.3
9.1
9.0
10.8
10.0
9.9
10.2
67.8
77.5
74.1
73.1
100.6
100.3
100.8

                Volumetric flow rate In actual  cubic meters per hour (acmh) and actual cubic feet per hour (acfh) at stack conditions.
                Volumetric flow rate In dry standard cubic meters per hour (dscmh) and dry standard cubic feet per hour (dscfh).

-------
hour, respectively.  The comparison of -the mathematically adjusted values




indicates that the inlet flow rate measurements were very accurate (1)  despite




the poor sampling location, and (2) that the difference between the inlet  and




outlet flow rate is equivalent to the amount of dilution air drawn in by the




induced draft fan.  The isokinetic sampling rate was within the allowable  range




for all six sample runs.




     Particulate Emissions - The particulate emissions from the boiler  (see




Table 3.3) were fairly consistent when the east and west runs were combined to




provide a value for the four-hour run.  For a run-by-run comparison of  the




inlet with the outlet run, runs 1B and 1C, 2B and 2C, and 3B and 3C would  be




combined to correspond to the outlet runs 1F, 2F, and 3F, respectively.




However, in this data presentation each of the three sets of runs (i.e., 1B,




2B, and 3B) were averaged and then the averages of the inlet runs were  combined




to obtain an inlet value.  The particulate emissions for the combined inlet




runs at 50% boiler capacity averaged 4970 milligrams per dry standard cubic




meter (2.18 grains per dry standard cubic foot) and 188 kilograms per hour




(415 pounds per hour).  These emissions have a corresponding emission rate of




4.74 pounds per million Btu.




     Hexavalent Chromium Emissions - The hexavalent chromium emissions  for each




test run (see Table 3.3) were very consistent with the corresponding particu-




late run.  They averaged 0.53, 0.64, 0.55, 0.58, 0.61, and 0.54 micrograms of




hexavalent chromium per gram of particulate emissions for runs 1B, 2B,  3B, 1C,




2C, and 3C, respectively.  The hexavalent chromium emissions for both inlet




tests at 50% boiler capacity averaged 2.84 micrograms per dry standard cubic




meter (0.0000012 grains per dry standard cubic foot) and 0.00010 kilograms per




hour (0.00024 pounds per hour).




     Total Chromium Emissions - The total chromium emissions for each test run




(see Table 3.3) were fairly consistent with the corresponding particulate  run.




They averaged 208, 202, 167, 190,  159, and 173 micrograms of total chromium per
                                      3-6

-------
                                       TABLE 3.3.  SUMMARY OF PARTICULATE,  HEXAVALENT CHROMIUM, AND  TOTAL CHROMIUM EMISSIONS

                                                                      FCR  50$ BOILER  CAPACITY
Run
No.
Date
(1985)
Part leu late
concentration
mg/dscm
gr/dscf
mass emissions
kg/h
Ib/h
Hexavalent Chromium
concentration
y g/dscm
gr/dscf
x 10~3
mass emissions
kg/h
Ib/h
Total Chromium
concentration
y g/dscm
gr/dscf
x 10~3
mass emissions
kg/h
Ib/h
                                                        Double Mechanical  Collector Inlet East (B)
IB
2B
3B
2/12
2/13
2/14
Average
5917
3937
6127
5330
2.59
1.72
2.68
2.33
198
131
201
177
437
288
444
390
3.11
2.53
3.36
3.00
0.0014
0.0011
0.0015
0.0013
0.00010
0. 00008
0.00011
0.00010
0.00023
0.00018
0.00024
0.00022
1229
795
1022
1020
0.5370
0.3471
0. 4466
0.444
0.0411
0.0263
0.0336
0.0337
0.0907
0.0581
0.0741
0.0743
                                                        Double Mechanical  Collector Inlet West (C)
1C
2C
3C
2/12
2/13
2/14
Average
3992
5000
4872
4620
1.74
2.19
2.13
2.02
162
227
210
200
357
501
463
440
2.30
3.06
2.65
2.67
0.0010
0.0013
0.0012
0.0012
0. 00009
0.00014
0.00011
0.00011
0.00021
0.00031
0.00025
0.00026
757
796
843
799
0. 3309
0. 3479
0.3682
0.349
0.0307
0.0362
0.0364
0.0344
0.0677
0.0798
0.0801
0.0759
u>
I
                                                               Inlet East and West (B and C)
Average
4970
2.18
188
415
2.84
0.0012
0.00010
0.00024
907
0.396
0.0340
0.0751
                                                          Double Mechanical  Collector Outlet (F)
IF
2F
3F
2/12
2/13
2/14
Average
327.3
327.3
320.4
325.0
0.143
0.143
0.140
0.142
13.8
•13.9
13.8
13.8
30.4
30.7
30.4
30.5
2.93
0.98
1.70
1.87
0.0013
0. 0004
0.0007
0. 0008
0.00012
0.00004
0.00007
0.00008
0.00027
0.00009
0.00016
0.00017
148.5
98.5
81.5
109.5
0.0649
0.0430
0.0356
0.0478
0.0063
0. 0042
0. 0035
0.0047
0.0138
0.0092
0.0077
0.0102

-------
gram of particulate emissions for runs •IB,  2B,  3B,  1C,  2C,  and 3C,  respect-




ively.  The total chromium emissions for both inlet tests at 50%  boiler




capacity averaged 907 micrograms per dry standard cubic meter (0.00040  grains




per dry standard cubic foot) and 0.034 kilograms per hour (0.075  pounds per




hour).







3.1.2  Double Mechanical Collector Outlet at 50% Boiler Capacity




     The double mechancial collector outlet represents  the controlled emissions




discharge to the atmosphere.  All three runs at the outlet at 50% of boiler




capacity were conducted for four hours in an effort to  obtain a quantifiable




amount of hexavalent chromium.




     Flue Gas Conditions and Isokinetic Sampling Rate - A summary of flue gas




conditions at the outlet for 50% boiler capacity is presented in  Table 3.2.




The volumetric flow rates for the three runs were consistent with the measured




inlet flow rate when the dilution air drawn in by the induced draft fan was




taken into consideration.  The outlet volumetric flow rate averaged 65,900




actual cubic meters per hour  (2,320,000 actual cubic feet per hour) with a flue




gas temperature of 148°C (299°F), a moisture content of 5.3%, an  0,




concentration of 9.0%, a CC^ concentration of 10.2%, and an excess air value




of 73.1%.  The volumetric flow rate at standard conditions averaged 42,600 dry




standard cubic meters per hour (1,500,000 dry standard cubic- feet per hour).




Standard conditions are 20°C  (68°F), 760 mm Hg  (29.92 in. Hg), and dry.




     The isokinetic sampling  rates were all well within the allowable range  for




all  runs.




     Particulate Emissions  - The particulate emissions from the control




equipment to the atmosphere were very consistent at 50% boiler capacity (see




Table 3.3).  The particulate  emissions averaged 325 milligrams per dry standard




cubic meter (0.14 grains per  dry standard cubic foot) and 13.8 kilograms per
                                      3-8

-------
hour (30.5 pounds per hour) with a corresponding emission rate of  0.35  pounds




per million Btu.




     Hexavalent Chromium Emissions - The hexavalent chromium emissions  were not




as consistent with their corresponding particulate run (see Table  3.3).  They




averaged 9.0, 3.0, and 5.3 micrograms of hexavalent chromium per gram of




particulate emissions for runs 1F, 2F, and 3F, respectively.  The  hexavalent




chromium emissions averaged 1.87 micrograms per dry standard cubic meter




(0.0000008 grains per dry standard cubic feet) and 0.00008 kilograms per hour




(0.00017 pounds per hour).




     Total Chromium Emissions - The total chromium emissions were  consistent




with their corresponding particulate run (see Table 3.3).  They averaged 454,




301, and 255 micrograms per gram of particulate emissions for runs 1F,  2F,  and.




3F, respectively.  The higher concentration of total chromium in the outlet




samples compared to the inlet samples is likely due to the higher  amount of




combustible material in the inlet samples.  The total chromium emissions




averaged 110 micrograms per dry standard cubic meter (0.000048 grains per dry




standard cubic foot) and 0.0047 kilograms per hour (0.0102 pounds  per hour).








3.1.3  Double Mechanical Collector Inlet at 80% Capacity




     The test time for the inlet and outlet runs were reduced in length for the




runs at 80% of boiler capacity.  The reduction in testing time was based on an




analysis of one of the 50% load emission samples and the plant's request to




reduce the testing time, since the test required that excess steam above plant




demand be vented to the atmosphere.  The two inlet runs were conducted




concurrently with the corresponding outlet test run which was also shortened.




     Flue Gas Conditions and Isokinetic Sampling Rate - A summary  of the flue




gas conditions at the double mechanical collector inlet (boiler outlet) at 80%




of boiler capacity is presented in Table 3.4.  The volumetric flow rate




conditions were slightly different on the west and east half of the duct.  This
                                      3-9

-------
                                              TABLE 3.4.  SUMM/RY OF FLUE GAS CONDITIONS FCR 80$ BOILER CAPACITY
GJ

M
O
Run
No.
Date
(1985)
Test Time
24 h clock
Volumetric Flow Rate
Actual8
acmh
x 103
acfh
x 106
Standard5
dscmh
x 103
dscfh
x 106
Stack
Temperature
°C
°F
Moisture
%
°2
co2
EA
%
1 sok I net I c
%
Double Mechanical Collector Inlet East (B)
48
5B
6B
2/15
2/18
2/19
1030-1143
1120-1235
1000-1112
Average
93.8
108.6
93.1
98.5
3.31
3.84
3.29
3.48
54.3
64.1
58.4
58.9
1.92
2.26
2.06
2.08
194
194
167
185
381
382
332
365
6.3
5.9
5.2
5.8
6.7
6.3
6.8
6.6
12.4
12.7
12.0
12.4
45.7
41.8
46.5
44.7
106.1
102.0
105.0

Double Mechanical Collector Inlet West (C)
4C
5C
6C
2/15
2/18
2/19
1030-1140
1120-1228
1000-1108
Average
106.7
105.5
108.2
106.8
3.77
3.72
3.82
3.77
64.2
63.8
64.6
64.2

Average
102.6
3.62
61.6
2.27
2.25
2.28
2.27
186
189
190
188
367
372
374
371
4.2
4.7
5.1
4.7
7.4
6.0
5.3
6.2
11.8
12.7
13.2
12.6
53.1
38.8
32.7
41.5
101.9
102.6
102.5

nlet East and West (B and C)
2.18
186
368
5.2
6.4
12.5
43.1

                                                         Double Mechanical Collector Outlet (F)
4F
5F
6F
2/15
2/18
2/19
1031-1144
1120-1228
1000-1105
Average
111.6
107.4
103.5
107.5
3.94
3.79
3.66
'3.80
67.1
65.3
63.1
65.2
2.37
2.31
2.23
2.30
182
183
179
181
359
361
355
358
5.6
5.9
5.7
5.7
10.2
8.8
8.4
9.1
9.4
10.5
10.3
10.1
92.5
70.4
64.3
75.7
102.0
103.1
101.5

           Volumetric flow rate In actual cubic meters per hour (acmh) and actual cubic feet per hour (acfh) at stack conditions.
           Volumetric flow rate In dry standard cubic meters per hour (dscmh) and dry standard cubic feet per hour (dscfh).

-------
was a result of the flow distribution in the duct.   The flow rate at the inlet




for the combined runs at the east and west half were fairly consistent,  and




when corrected for the dilution air drawn in at the induced draft fan,  it was




consistent with the outlet flow rate.  The first run, when the plant was not




operating, had an excess air value above what would be considered to be




optimum.




    The inlet volumetric flow rate (composite of the east and west inlets)




averaged 102,600 actual cubic meters per hour (3,620,000 actual cubic feet per




hour) with a flue gas temperature of 186°C (368°F), a moisture content of 5.2%,




an 02 concentration of 6.4%, a CC^ concentration of 12.5%, and an excess air




value of 43.1%.  The volumetric flow rate at standard conditions averaged




61,600 dry standard cubic meters per hour (2,180,000 dry standard cubic feet




per hour).  Standard conditions are 20°C (68°F), 760 mm Hg (29.92 in. Hg), and




dry.  The average inlet and outlet standard volumetric flow rate and outlet




standard volumetric flow rate corrected to zero percent excess air were




1,523,000 and 1,309,000 dry standard cubic feet per hour, respectively.  This




comparison of the mathematically adjusted values indicate that the inlet flow




rate measurements were fairly accurate despite the poor sampling location, and




that the difference between the inlet and outlet flow rate can be mainly




accounted for the dilution air drawn in by the induced draft fan.




    The isokinetic sampling rates were within the allowable range for all




sample  runs.




    Particulate Emissions - The particulate emissions from the boiler were




fairly  consistent for the combined inlet runs (see Table 3.5).  However, the




emissions were significantly higher  in the west half of the duct compared to




the east half of the duct.  Also, the emissions were approximately two times as




high at 80% boiler capacity as at 50% boiler capacity.  Based on the coal




analysis  (see Appendix B) and the type of boiler, these results indicate that




adjustments of the overfire and underfire air would probably reduce the




emissions from the boiler.



                                     3-11

-------
TABLE 3.5.  SUMMARY OF PARTICULATE,  HEXAVALENT OftCMIUM,  AND TOTAL CWOMIUM EMISSIONS
                               FOR  80? BOILER CAPACITY
Run
No.
Date
(1985)
Part leu late
concentration
mg/dscm
gr/dscf
mass emissions
kg/h
Ib/h
Hexavalent Chromium
concentration
y g/dscm
gr/dscf
x 10~3
mass emissions
kg/h
Ib/h
Total Chromium
concentrat 1 on
y g/dscm
gr/dscf
x 10~3
mass emissions
kg/h
Ib/h
                 Double Mechanical  Collector Inlet East (B)
4B
5B
6B
2/15
2/18
2/19
Average
14718
12165
6882
11260
6.43
5.32
3.01
4.92
800
780
402
661
1762
1720
886
1460
3.97
2.40
3.15
3.17
0.0017
0.0011
0.0014
0.0014
0.00022
0.00015
0.00018
0.00018
0.00048
0.00034
0.00041
0.00041
1713
1786
1145
1550
0. 7485
0.7807
0. 5003
0.676
0.0930
0.1146
0.0669
0.0915
0. 2050
0.2525
0.1474
0.202
Double Mechanical Collector Inlet West (C)
4C
5C

2/15
2/18
2/19
Average
7149
10237
9801
9060
3.12
4.47
4.28
3.96
459
653
634
582
1012
1439
1396
1280
6.24
5.71
5.43
5.79
0.0027
0.0025
0. 0024
0.0025
0.00040
0.00036
0. 00035
0.00037
0.00088
0.00080
0.00077
0.00082
1232
1556
1636
1470
0.5385
0.6799
0.7150
0.644
0.0791
0.0992
0.1058
0.0947
' 0. 1 744
0.2188
0.2332
0.209
Inlet East and West (B and C)
Average
10160
4.44
622
1370
4.48
0. 0020
0.00028
0.00062
1510
0.660
0.0931
0.205
                   Double Mechanical Collector Outlet (F)
4F
5F
6F
2/15
2/18
2/19
Average
515
411
410
445
0.225
0.180
0.179
0.195
34.5
•26.9
25.9
29.1
76.1
59.4
57.0
64.2
4.52
1.65
6.75
4.31
0.0020
0.0007
0.0029
0.0019
0.00030
0.00011
0. 00043
0.00028
0.00067
0.00024
0.00094
0.00062
219
263
235
239
0.096
0.115
0.103
0.105
0.0147
0.0172
0.0148
0.0156
0.0324
0.0378
0.0327
0.0343

-------
     The particulate emissions averaged 10160  milligrams  per dry standard cubic




meter (4.44 grains per dry standard cubic feet)  and 622 kilograms per hour




(1370 pounds per hour) with a corresponding emission rate of 8.89 pounds per




million Btu.




     Hexavalent Chromium Emissions - The hexavalent chromium emissions  for  each




test run at 80% of boiler capacity (see Table  3.5)  were not as  consistent as




the 50% boiler capacity runs.  The emissions averaged 0.27,  0.20, 0.46,  0.87,




0.56, and 0.55 grams of hexavalent chromium per gram of particulate emissions




for runs 4B, 5B, 6B, 4C, and 6C, respectively.  The hexavalent  chromium




emissions averaged 4.48 micrograms per dry standard cubic meter (0.000002




grains per dry standard cubic foot) and 0.00028 kilograms per hour  (0.00062




pounds per hour).




     Total Chromium Emissions - The total chromium emissions for each run at




80% boiler capacity (see Table 3.5) were consistent with  their  corresponding




particulate run.  They averaged 116, 147, 166, 172, 152,  and 167 micrograms per




gram of particulate emissions for runs 4B, 5B, 6B,  4C, 5C, and  6C,  respec-




tively.  The concentrations were lower than the 50% boiler capacity run which




was probably a result of poor combustion, and thus, more  combustible material




being present in the particulate emissions.  The total chromium emissions




averaged 1510 micrograms per dry standard cubic meter (0.00066  grams per dry




standard cubic foot) and 0.093 kilograms per hour (0.21 pounds  per  hour).







3.1.4  Double Mechanical Collector Outlet at 80% Capacity




     The test time for the outlet runs was reduced based  on the analysis of the




sample from the first run at 50% of boiler capacity.  This reduced  sampling




time still allowed collection of a quantifiable amount of hexavalent chromium,




and it reduced the amount of time the plant had to vent the excess  steam not




needed for plant production.
                                      3-13

-------
     Flue Gas Conditions and Isokinetic Sampling Rate - A summary of  the  flue




gas conditions at the double mechnical collector outlet (emissions discharged




to the atmosphere) at the 80% boiler load is presented in Table 3.4.   The flow




rates were fairly consistent, with the exception that the first run conducted




while the plant was not operating appeared to be at a rate above the  optimum




excess air.  The volumetric flow rate averaged 107,500 actual cubic meters per




hour (3,800,000 actual cubic feet per hour)  with a flue gas temperature of




181°C (358°F), a moisture content of 5.7%, an 02 concentration of 9.1%, a




CO2 concentration of 10.1%, and excess air value of 75.7%.  The volumetric




flow rate at standard conditions averaged 65,200 dry standard cubic meters per




hour (2,300,000 dry standard cubic feet per hour).  Standard conditions are




20°C (68°F), 760 mm Hg (29.92 in. Hg), and dry.




     The isokinetic sampling rates were within the allowable range for all




sample runs.




     Particulate Emissions - On a mass emission basis, the particulate




emissions at the double mechanical collector outlet at 80% boiler capacity (see




Table 3.5) were twice that of the emissions at 50% boiler capacity.  Also, the




emissions for the first run were significantly higher than the other two  runs.




This higher emission rate for the first run was likely a result of the fact




that the plant was not in operation and that too much excess air was  used.  The




overall higher emission concentration is probably due to improper adjustment of




the boiler overfire and underfire air.  Also, the emissions measured  on oneside




of the mechanical collector inlet duct were twice as high as those measured on




the other side.  The particulate emissions averaged 445 milligrams per dry




standard cubic meter (0.195 grains per dry standard cubic foot) and 29.1




kilograms per hour (64.2 pounds per hour) with a corresponding emission rate of




0.486 pounds per million Btu.




     Hexavalent Chromium Emissions - The hexavalent chromium emissions measured




were not very consistent from run to run, averaging 8.8, 4.0, and 16.5 micro-
                                      3-14

-------
grams of hexavalent chromium per gram of particulate emissions  (see Table  3.5).




These inconsistencies are due to the small amount of hexavalent chromium




actually analyzed and the resulting analytical error.  The hexavalent chromiun




emissions averaged 4.3 micrograms per dry standard cubic meter (0.0000019




grains per dry standard cubic foot) and 0.00028 kilograms per hour (0.00062




pounds per hour).




     Total Chromiun Emissions - The total chromium emissions  at the 80% boiler




capacity (see Table 3.5) were not as consistent as at the 50% boiler capacity




and were much higher in concentration.  They averaged 425,  640, and 573 micro-




grams per gram of particulate emission for runs 4F, 5F, and 6F, respectively.




The concentrations were greater than the inlet runs mainly due to the greater




amount of combustible material present in the inlet samples.   The reason for




the chromiun concentrations for the outlet runs at 80% boiler capacity being




greater than those at 50% boiler capacity is not known.  The  total chromium




emissions averaged 239 micrograms per dry standard cubic meter (0.00011 grains




per dry standard cubic foot) and 0.016 kilograms per hour (0.034 pounds per




hour).








3.2  SUMMARY OF EMISSIONS IN UNITS OF PROCESS RATE AND COLLECTION EFFICIENCY




     The emission rates in units of the process rate are expressed in term's  of




pounds of pollutant per million Btu's of heat released and are presented in




Table 3.6.  These values were determined using the F factor calculation and  do




not account for unburned combustibles.  No process operating  parameters were




actually used to perform these calculations. To determine the collection




efficiency of the double mechanical collector, the uncontrolled and controlled




measured emissions were used.  No actual measurements were made on the mass




removal rates from the double mechanical collector.
                                      3-15

-------
                                          TABLE 3.6.  SUMMARY OF EMISSION RATES IN UNITS OF PRXESS RATE AND EFFICIENCY
Date
(1985)
Run Nos.
Uncontrolled Emissions
partlcul ate
lbs/l06Btu
hex av a lent
chromium
lbs/106Btu
total
chromium
lbs/106Btu
Controlled Emissions
partlcul ate
lbs/106Btu
hexavalent
chromium
lbs/106Btu
total
chrom 1 um
lbs/106Btu
Collection Efficiency
partlcul ate
%
hexavalent
chromium
%
total
chromium
%
                                                                        50? Boiler Capacity
2/12
2/13
2/14
IB, 1C, IF
2B, 2C, 2F
38, 3C, 3F
Average
4.614
4.328
5.274
4.739
2.5 x 10~6
2.7 x 10~6
2.9 x 10~6
2.7 x 10~6
0.92 x 10~3
0.78 x 10~3
0.89 x 10~3
0.86 x 10"3
0.338
0.359
0.345
0.347
3.0 x 10~6
1.1 x 10~6
1.8 x 10~6
2.0 x 10~6
0.154 x 10~3
0.108 x 10~3
0.088 x 10~3
0.12 x 10~3
92.7
91.7
93.5
92.7
<0
59.3
37.9
25.9
83.3
86.2
90.1
86.5
                                                                        80? Boiler Capacity
2/15
2/18
2/19
4B, 4C, 4F
5B, 5C, 5F
6B, 6C, 6F
Average
9.934
9.644
7.082
8.887
4.7 x 10~6
3.5 x 10~6
3.6 x 10~6
3.9 x 10~6
1.34 x 10~3
1.44 x 10~3
1.18 x 10~3
1.32 x 10~3
0.610
. 0.432
0.416
0.486
5.4 x 10~6
1.7 x 10~6
6.8 x 10~6
4.6 x 10~6
0.26 x 10~3
0.28 x 10~3
0.24 x 10~3
0.26 x 10~3
93.9
95.5
94.1
94.5
<0
51.4
<0
<0
80.6
80.6
79.7
80.3
CJ
I

-------
3.2.1  Emissions at 50% Boiler Capacity



     The uncontrolled particulate emissions averaged 4.74 pounds  per million




Btu, and the controlled emissions averaged 0.347 pounds per million Btu,  with a




resulting collection efficiency of 92.7% by weight.   The uncontrolled




hexavalent chromium emissions averaged 2.7 x 10   pounds per million Btu, and



                                          — 6
the controlled emissions averaged 2.0 x 10   pounds  per million Btu/ with a




resulting collection efficiency of 25.9% by weight.   The uncontrolled total




chromium emissions averaged 860 x 10   pounds per million Btu,  and the




controlled emissions averaged 120 x 10   pounds per million Btu,  with a



resulting control efficiency of 86.5% by weight.
3.2.2  Emissions at 80% Boiler Capacity




     The uncontrolled particulate emissions averaged 8.89 pounds per million



Btu and the controlled emissions averaged 0.49 pounds per million Btu, with a

                                                 «


resulting collection efficiency of 94.5% by weight.  The uncontrolled




hexavalent chromium emissions averaged 3.9 x 10~6 pounds per million Btu and



the controlled emissions averaged 4.6 x 10   pounds per million Btu, with a




resulting collection efficiency of less than zero.   The negative collection




efficiency is a result of the small amount of hexavalent chromium analyzed and



the resulting analytical error.  The uncontrolled total chromium emissions




averaged 1320 x 10   pounds per million Btu and the controlled emissions



averaged 260 x 10~6 pounds per million Btu, with a resulting control



efficiency of 80.3% by weight.







3.2.3  Conclusions




     The double mechanical collector's removal of particulate emissions was



slightly less than typical.  This slightly lower collection efficiency may be




due to the poor distribution of emissions to be collected.  The double



mechanical collector has a very low collection efficiency for the hexavalent
                                      3-17

-------
chromium emissions, which is due to the fact that these emissions are mainly in




the particle size range of less than 5 Urn.  The collection efficiency for total




chromium was slightly lower than that for the particulate emissions,  however,




this is due mainly to the fact that the larger particles consist of a greater




percentage of combustible material.








3.3  PARTICLE SIZE DISTRIBUTION




     Six particle size runs were made at the outlet and both of the inlet




locations at each of the two boiler loads.  After the initial gravimetric




determination was made, the six runs were combined at the inlet and outlet in




an effort to obtain a quantifiable amount of hexavalent chromium.  Computer




printouts of the emission calculations and graphs presenting plot particle size




versus percent weight are included in Appendix A.  A summary of the particle




size distributions are presented in Table 3.7 for the 50% boiler capacity runs




and in Table 3.8 for the 80% boiler capacity runs.








3.3.1  Particle Size Distribution at 50% Capacity




     Emissions from the boiler were mainly composed of large particles with




only 15% of the weight in particles greater than 10 ym in diameter.  The double




mechanical collector did a good job of collecting most of the particles in the




10 ym range, but only collected approximately half of the particles less than




10 ym in diameter.  The emissions at the collector outlet were approximately




50% by weight less than 10 ym in diameter.  Since the mechanical collector did




a  relatively poor  job of collecting .the smaller particles, very little of the




hexavalent chromium particles were collected, since approximately three-fourths




of all the hexavalent chromium particulate matter is less than 5 ym in




diameter.  The particle size distribution results for hexavalent chromium is




not believed to be extremely accurate due to the very small amount of




hexavalent chromium being analyzed.  The particle size distribution for total
                                      3-18

-------
                                               TABLE 3.7.  SUMM/RY OF RETICLE SIZE DISTRIBUTION AT 50$ BOILER CAPACITY
Run
No.
Date
(1985)
Test Time
24 h clock
Partlcul ate
wt. less than size, %
1 y m | 5 ym
10 ym
Hexavalent Chromium
wt. less than size, %
1 ym
5ym
10 ym
Total Chromium
wt. less than size, %
1 ym
5 ym
10y m
I
I-"
VO
                                                     Double Mechanical Collector  Inlet East
SIB
S2B
S3B
2/12
2/13
2/14
1323-1328
1319-1323:30
1520-1525
Average
1.2
0.3
10
4
2
0.5
25
9
3
2
54
20
























Double Mechanical Collector Inlet West
SIC
S2C
S3C
2/12
2/13
2/14
1138-1 143
1111-1 116
1139-1344
Average
4.8
4.8
2.4
4
7
5
4
5
10
8
8
9
























                                                                Inlet East  and  West
Average
4
7
15
31*
68*
79*
a
a
a
                                                       Double Mechanical Collector Outlet
S1F1
S1F2
S2F1
S2F2
S3F1
S3F2
2/12
2/12
2/13
2/13
2/14
2/14
1254-1318
1356-1420
1115-1135
1324-1344
1140-1200
1252-1312
Average
1.6
2
4.5
9
7
8
5
11
9
24
54
46
48
32
18
13
35
85
74
69
49






3*






71*






95*






25*






58*






72*
                   Composite.


                  aNo particle size  distribution  curves  for the  inlet  due  to  a

                   fractions during  inlet  particle  size  testing.
lack of  a  significant  catch  in  smaller

-------
                                             TABLE 3.8.  SLMM/>RY OF RETICLE SIZE DISTRIBUTION AT 80? BOILER CAPACITY
Run
No.
Date
(1985)
Test Time
24 h clock
Part icu late
wt. less than size, %
1 y m
5 ym | 10'ym
Hexavalent Chromium
wt. less than size, %
lym
5 ym 1 10 ym
Total Chromium
wt. less than size, %
lym | 5ymj10ym
to
o
Double Mechanical Collector Inlet East
S4B
S5B
S6B
2/15
2/18
2/19
1209-1211:45
1247-1250:15
1119-1122:55
Average
0.1
0
0
0.03
0.1
0.5
0
0.2
0.1
1.3
0.4
0.6












Double Mechanical Collector Inlet West
S4C
S5C
S6C
2/15
2/18
2/19
1222-1225
1233-1236
1114-1117
Average
4.5
15
5
8
16
19
10
15
18
30
24
24












                                                                 Inlet East  and West
Average
4
8
12
20*
60»
76»
a
a
a
                                                        Double Mechanical Collector Outlet
S4F1
S4F2
S5F1
S5F2
S6F1
S6F2
2/15
2/15
2/18
2/18
2/19
2/19
1032-1052
1126-1146
1120-1140
1212-1232
1006-1026
1052-1112
Average
8
14
10
14
12
12
12
42
50
60
60
53
55
53
70
83
84
88
75
83
81






8*






28*






38*






2*






5*






7*
                    Composite.


                    No particle size  distribution curves for the  Inlet due to a  lack of a significant catch  In smaller

                    fractions during  Inlet particle size testing.

-------
chromium could not be determined due to the extremely high blank levels  in the




large number of filters required to collect the sample.   However, based  on




previously discussed results, total chromium would most likely be found  in




greater concentration in the smaller particles due to the greater proportion of




combustibles present in the larger particles.








3.3.2  Particle Size Distribution at 80% Boiler Capacity




     The particle size distribution for the tests conducted at 80% of boiler




capacity is similar to that for the tests conducted at 50% of capacity.   The




particle size results for the outlet emissions of hexavalent chromium appear to




be invalid and are therefore not used for any of the conclusions.









3.3.3  Conclusions




     Based on the emissions data and particle size data, the particle size




distribution for particulate emissions appears to be typical for both




controlled and uncontrolled particulate emissions.  The particle size




distribution data for hexavalent chromium includes some analytical error due to




the small amount of hexavalent chromium analyzed.  However, the results  clearly




show that the hexavalent chromium emissions for industrial boilers are particle




size dependent and that the majority of all hexavalent chromium emissions are




less than 5 ura in size.  The total chromium particle size distribution could




not be accurately determined due to the extremely high blank levels in the




large number of filters required to collect the sample.  As noted earlier, the




particle size distribution would probably be the same as that for the




particulate emissions if all combustibles were elminiated from the samples.








3.4  VISIBLE EMISSIONS OBSERVATION DATA




     Visible emissions determinations were made at both boiler operating




capacities.  The data sheets and calculations for each run are presented in
                                      3-21

-------
Appendix C.  A summary of the visible emissions data is  presented in Table




3.9.  The opacity of the visible emissions were fairly consistent for all




runs.  Opacity versus mass was 0.093, 0.092,  0.091,  0.135,  0.110,  and 0.109




grains per actual cubic foot compared to 14.55, 10.57, 10.35,  10.60,  8.47, and




10.54 percent opacity, respectively.  Both the actual stack gas  pollutant




concentration and the percent opacity were fairly constant for all runs.  Some




of the variability in the visible emission data is more  likely due to poor




background conditions and high winds.




    After the concentration of the hexavalent chromium emissions is estab-




lished through testing with the total emissions, visible emissions would likely




be a good indicator of hexavalent chromium emissions as  long as the percent




chromium in the coal remains about the same.




    For facilities with efficient fuel combustion, the opacity-mass




relationship for total chromium and opacity would be the same as that for the




particulate emissions.  The concentration of total chromium in the fuel would




also be included in the relationship.








3.5  SUMMARY OF ANALYTICAL RESULTS FOR HEXAVALENT AND TOTAL CHROMIUM




    The summaries of results for the hexavalent chromium and total chromium




analyses of samples collected are presented in Table 3.10 for the 50% boiler




capacity tests and in Table 3.11 for the 80% boiler capacity tests.  The




analytical data sheets are contained in Appendix B.  The analytical results




shown in Tables 3.10 and 3.11 for hexavalent and total chromium are the results




obtained by the EPA tentative method for  "Determination of Hexavalent Chromium




Emissions  from Stationary Sources" and the "EPA Protocol for Emissions Sampling




for Both Hexavalent and Total Chromium" (see Appendix D).  When for total




chromium analysis the table indicates that the sample "residue" was analyzed,




then the values presented for total chromium are a sum of (1) the hexavalent




chromium in the sample filtrate from the  extraction of the sample and (2) the
                                      3-22

-------
TABLE 3.9. SUMMARY OF VJSIBLE  EMISSIONS DATA FOR ALL RUNS
         BOILER NO.  4 MECHANICAL  COLLECTOR OUTLET
               Run No.  1  - 50% Capacity
Date
Before
2/12 During
After
Time
1000-1439

Range
5-20

Avg. % Opacity
14.55


14.55

                 Run No.  2 -  50% Capacity
Date
Before
2/13 During
After
Time
0930-0959
1000-1417
1418-1429
Range
10-20
5-20
5-15
Avg. % Opacity
14.77
10.57
9.79

10.57

Average
opacity
during
50% load
test runs
 = 11.82
                 Run No.  3 -  50% Capacity
Date
Before
2/14 During
After
Time
0930-1029
1030-1521
Range
5-15
5-20
Avg. % Opacity
9.83
10.35
10.35

                 Run No.  4 -  80% Capacity
Date
Before
2/15 During
After
Time
0930-1029
1030-1229
Range
10-20
5-20
Avg. % Opacity
16.25
10.60
10.60

                 Run No.  5 - 80% Capacity
Date
Before
2/18 During
After
Time
0930-1025
1030-1253
1254-1259
Range
5-25
0-15
5-10
Avg. % Opacity
11.21
8.47
7.08

8.47

Average
opacity
during
80% load
test runs
 =  9.87
                 Run No.  6 - 80% Capacity
Date
Before
2/19 During
After
Time
0930-0959
1000-1123
1124-1145
Range
5-20
5-20
5-10
Avg. % Opacity
11.14
10.54
7.92

10.54

                             3-23

-------
                       TABLE 3.10.  SUMMARY OF ANALYTICAL RESULTS FCR HEXAVALENT AND TOTAL CHROMIUM AT 50? BOILER CAPACITY
Run
No.
Samp 1 e
Type
Samp 1 e
No.
Analyzed
Amount of
Samp 1 e
mg or ml
Hex aval en t Chromium
Results
VI9
Concentrat 1 on
yg/g
Amount of
Samp 1 e
Analyzed
Total Chromium
Results
yg
Concentration
yg/g
Samp 1 e
Prep
Method9
                                                         Double Mechanical Collector Inlet East
IB
IB
2B
38
Part leu late Front Half
Implnger Contents
Part leu late Front Half
Part leu late Front Half
C-98
C-111
C-99
C-100
5,897
Total
3,890
4,380
3.1
	
2.5
2.4
0.53
0.1
0.64
0.55
Residue
4 of 44 ml
Residue
Residue
1224
157.9
785.0
730.6
207.7
26. 7b
201.8
166.8
2
5
2
2
Double Mechanical Collector Inlet West
1C
1C
2C
3C
Part leu late Front Half
Implnger Contents
Part leu late Front Half
Part leu late Front Half
C-104
C-117
C-105
C-106
4,694
Total
6,540
6,072
2.7
	
4.0
3.3
0.58
<0.1
0.61
0.54
Residue
4 of 27 ml
Residue
Residue
890.2
62.2
1041
1050
189.7.
13.3b
159.2
172.9
2
5
2
2
'Double Mechanical Collector Inlet East and West Particle Sizing
S1-3
SI -3
S1-3
Particle Size, large
Particle Size, medium
Particle SI ze, smal 1
C-160
C-161
C-162
1,128
46.4
26.4
0.12
0.22
0.31
0.11
4.74
11.74
Residue
Residue
Residue
615.3
c
c
545.5
c
c
3
3
3
                                                           Double Mechanical Collector Outlet
IF
IF
2F
3F
S1-3F
S1-3F
S1-3F
Part leu late Front Half
Implnger Contents
Part leu late Front Half
Part leu late Front Half
Particle Size, large
Particle Size, medium
Particle Size, smal 1
C-92
C-123
C-93
C-94
C-154
C-155
C-156
1,462
Total
1,473
1,465
516
143
131
13.1
	
4.4
7.8
0.02
0.26
0.11
8.96
O.I
2.99
5.32
0.04
1.82
0.84
Residue
4 of 51ml
Residue
Residue
Residue
Residue
Residue
663.7
8.2
443.2
373.3
171.2
60.7
72.7
454.0.
5.61 b
300.9
254.8
331.8
424.5
555.0
1
5
1
1
1
1
1
                                                                      Grab Samples
1A
ID
IE
16
2A
2D
2E
26
3A
3D
3E
36
Coal Feed
1° Multlclone Hopper Ash
2° Multlclone Hopper Ash
Bottom Ash
Coal Feed
1 Multlclone Hopper Ash
2° Multlclone Hopper Ash
Bottom Ash
Coa 1 Feed
1 Multlclone Hopper Ash
2° Multlclone Hopper Ash
Bottom Ash
C-148
C-142
C-136
C-130
C-149
C-143
C-137
C-131
C-150
C-144
C-138
C-132
___
	
	
	
	
	
	
	
	
	
	
— • -—
	 _
	
	
	
	
	
	
	
	
	
	
»_
0.5
O.5
2.5
O.5
O.5
O.5
1.8
0.5
O.5
0.5
1.4
O.5
309. 8mg
151. Img
155.9mg
155.9mg
304. 6mg
168.0mg
151. 4mg
188.9mg
310.5mg
158.0mg
149.9mg
152.3mg
6.155
36.12
35.94
23.39
6.541
29.88
33.29
39.03
7.050
31.88
49.43
27.33
19.9
239.0
230.5
150.0
21.5
177.9
219.9
206.6
22.7
201.8
329.8
179.4
4
4
4
4
4
4
4
4
4
4
4
4
aSample preparation methods are as follows:

     1  = For the Method 5 filters collected at the outlet location:  jjlgxavalent chromium was extracted from the filter and acetone
         rinse and the filtrate from this process was analyzed for Cr  •  The residue from the extraction was analyzed for total
         chromium.  Total chromium results reported (yg) are the sum of both measurements (blank corrected).
(continued)

-------
                                                                  TABLE 3.10.   (continued)


               2 = For -the Method 5 filters collected at the inlet locations:   One weighed  portion of the filter catch was taken for hexavalent
                   chromium analysis and another weighed portion was taken for total  chromium analysis.

               3 = For particle sizing:  Because of the relatively small  catches,  sets.of equivalent Impactor stages and/or filters from 6 corres-
                   ponding runs (e.g.. Runs SIB, S2B, S3B,  SIC,  S2C,  and S3C)  were combined into single samples.  Analysis for Cr   Involved
                   extraction of the catch and analysis of  the filtrate.   All  Cr   results  were below the detection level  of the method
                   (Insignificant).  Therefore, the total  chromium results reported (yg)  Include only the total  chromium In the extraction residue
                   detected by NAA.

               4 = For solid process samples:   One weighed  portion was taken for hexavalent chromium analysis and another weighed portion was
                   taken for total chromium analysis.

               5 = For Implnger contents:  The  liquid samples were concentrated; one measured aliquot was taken for hexavalent chromium analysis
                   and one measured aliquot taken for total chromium analysis.  Total chromium concentrations are expressed as yg Cr per g of
                   partlculate matter catch.
           Expressed in yg Cr per g of particulate matter catch In the front half.

          cSubtraction of blank value from total chromium catch for this fraction resulted In a negative number.
u>
10
Ul

-------
                       TABLE 3.11.  SUMMARY OF ANALYTICAL RESULTS FCR  HEXAVALENT AND TOTAL CWOMIUM AT 80$ BOILER CAPACITY
Run
No.
Samp 1 e
- Type
Samp 1 e
No.
Analyzed
Amount of
Samp 1 e
mg or ml
Hexavalent Chromium
Results
yg
Concentration
yg/g
Amount of
Sample
Analyzed
Total Chromium
Resu 1 ts
yg
Concentration
yg/g
Samp 1 e
Prep
Method8
                                                         Double Mechanical  Collector Inlet East
4B
58
6B
Partlculate Front Half
Partlculate Front Half
Partlculate Front Half
C-101
C-102
C-103
11,860
11,138
5,907
3.2
2.2
2.7
0.27
0.20
0.46
Residue
Residue
Residue
1380
1636
982.7
116.4
146.9
166.4
2
2
2
Double Mechanical Collector Inlet West
4C
5C
6C
Parti cut ate Front Half
Partlculate Front Half
Partlculate Front Half
C-107
C-108
C-109
6,758
9,680
9,388
5.9
5.4
5.2
0.87
0.56
0.55
Residue
Residue
Residue
1164.8
1471.4
1567.3
172.4
152.0
167.0
2
2
2
Double Mechanical Collector Inlet East and West Particle Sizing
S4-6
S4-6
S4-6
Particle Size, large '
Particle Size, medium
Particle Size, smal 1
C-163
C-164
C-165
1,371
27.7
7.6
0.2
0.5
0.2
0.13
17.69
30.26
Residue
Residue
Residue
203.7
b
b
148.6
b
b
3
3
3
                                                           Double Mechanical  Collector Outlet
4F
5F
6F
S4-6F
S4-6F
S4-6F
Partlculate Front Half
Partlculate Front Half
Partlculate Front Half
Particle Size, large
Particle Size, medium
Particle Size, smal 1
C-95
C-96
C-97
C-157
C-158
C-159
603
475
450
66
220
216
5.3
1.9
7.4
0.39
0.16
0.12
8.79
4.00
16.44
5.91
0.73
0.56
Residue
Residue
Residue
Residue
Residue
Residue
256.4
302.9
257.7
531.6
85.5
63.7
425.2
637.7
572.7
8054
388.6
294.9
1
1
1
3
3
3
                                                                      Grab Samples
4A
4D
4E
46
5A
5D
5E
5G
6A
60
6E
6G
Coal Feed
1° Multlclone Hopper Ash
2° Multlclone Hopper Ash
Bottom Ash
Cga 1 Feed
1 Multlclone Hopper Ash
2° Multlclone Hopper Ash
Bottom Ash
Coal Feed
1° Multlclone Hopper Ash
2° Multlclone Hopper Ash
Bottom Ash
C-151
C-145
C-139
C-133
C-152
C-146
C-140
C-134
C-153
C-147
C-141
C-135
	
	
. 	
	
	
	
	
	
	
	
	
	
— .—
	
	
	
	
	
	
	
	
	
	
— -
<0.5
<0.5
1.7
<0.5
O.5
<0.5
1.1
<0.5
O.5
O.5
0.74
O.5
333. Omg
151. Img
154.8mg
163. Omg
304. 6mg
151.9mg
151.9mg
162. 5mg
306. 7mg
153.2mg
153.7mg
156.3mg
6.714
38.91
38.70
29.21
5.934
28.96
34.90
35.92
5.936
50.27
37.07
24.15
20.2
257.5
250.0
179.2
19.5
190.7
229.8
221.0
19.4
328.1
241.2
154.5
4
4
4
4
4
4
4
4
4
4
4
4
                                                                      BIank Samp Ies






Acetone 4 M-5 Filter Blank
Distilled H20 Blank
Outlet BlanR Medium, Andersen
Outlet Blank Small, Andersen
Inlet Blank Medium, Flow Sensor
Inlet Blank Small, Flow Sensor
C-110
C-129
C-166
C-167
C-168
C-169

200




<0.20
___
1.0
1.0
0.9
0.6












_«—
5.3
123.8
165.1
164.8
138.7












(continued)

-------
                                                             TABLE  3.11.   (continued)
       Sample preparation methods are as follows:
           1  = For the Method 5 filters collected  at the outlet  location:  Hexavalent chromium was extracted from the filter and acetone  rinse
                                                                     t£
               and the filtrate from this process  was analyzed  for  Q-   .  The residue from the extraction was analyzed  for total chromium.
               Total  chromium results reported  (yg)  are the sum  of  both measurements (blank corrected).

           2  = For the Method 5 filters collected  at the Inlet  locations:  One weighed  portion of the  filter catch was  taken for hexavalent
               chromium analysis and another weighed portion was taken  for total  chromium analysis.

           3  = For particle sizing:   Because of the relatively  small catches, sets of equivalent  Impactor stages and/or filters from 6 corres-
               ponding runs (e.g., Runs SIB, S2B,  S3B,  SIC,  S2C,  and S3C) were combined Into  single  samples.  Analysis  for Q-   Involved
               extraction of the catch and analysis of the filtrate.  All Or    results  were below the  detection  level of the method
               (Insignificant).  Therefore,  the total  chromium  results  reported (yg)  Include  only the  total chromium  In the extraction residue
               detected by NAA.

           4  = For solid process samples:   One  weighed portion  was  taken  for  hexavalent chromium  analysts and another weighed  portion was
               taken for total chromium analysis.


       Subtraction of blank value from total chromium catch for  this  fraction resulted  In a negative number.
U)
CO

-------
chromium in the residue from the extraction measured by Neutron Activation




Analysis.  When the table indicates that the "total" sample was analyzed,  then




the values presented for total chromium content are from the direct analysis  of




the total sample for total chromium by Neutron Activation Analysis.  A table




showing the total chromium calculations and references to the applicable data




forms can be found at the end of Appendix A of this report.




    For this testing program, there is some sample analysis variability due to




the small amount of hexavalent chromium present.  However, the average values




for the runs are believed to be representative.




    One set of impinger contents (or back half particulate catch)  was analyzed




for each location sampled at 50% boiler capacity.  The purpose of  this analysis




was to reconfirm the fact, established by the method development and evaluation




study, that a significant amount of hexavalent chromium and/or total chromium




does not pass through the front half.  The analytical results for  the impinger




contents for Runs 1B, 1C, and 1F show that the amount of hexavalent and total




chromium passing through the filter was negligible (see Table 3.10).




    Quality assurance audit samples were analyzed for total chromium.  As  shown




in Table 3.12, no bias was present and the results are considered  acceptable.








3.6  COAL SAMPLE ANALYSIS FOR F FACTOR CALCULATIONS




    Coal samples were taken to represent each set of test runs. A portion




ofthe coal samples were combined for the 50% boiler capacity and for the 80%




boiler capacity for a proximate and ultimate analysis.  The results of these




analyses are presented in Table 3.13.  They indicate that the coal was of good




quality, which is typical for use in a spreader stoker boiler.  The calculated




F factor was 9750 for the coal used at 50% boiler load and 9724 for that used




at 80% boiler load.
                                       3-28

-------
                  TABLE 3.12.  SUMM/RY OF ANALYTICAL RESULTS FCR HEXAVALENT AND TOTAL CWOMIUM QUALITY ASSURANCE SABLES
U)
to

Run
No.

Samp 1 e
Type

Sample
No.

True
Value
Hexavalent Chromium
Results
yg/ml
%
Oev.
Total Chromium
Results
yg
%
Dev.
Qual Ity Assurance Samples
—
—
—
—
— ~
Qual ity Assurance
Qual Ity Assurance
Qual Ity Assurance
Qual Ity Assurance
Qual Ity Assurance
• QA-7
QA-8
QA-9
QA-10
QA-11
5 yg Cr
10 yg Cr
66.33 yg Cr
132.7 yg Cr
199 yg Cr
—
—
—
—
— —
	
	
—
	
— —
4.501
6.675
79.45
131.9
145.1
10.0
33.3
19.8
0.6
27.1

-------
TABLE 3.13.  COAL ANALYSIS

Moisture, %
Ash, % dry basis
Volatile, % dry basis
Fixed carbon, % dry basis
Sulfur, % dry basis
Carbon, % dry basis
Hydrogen, % dry basis
Nitrogen, % dry basis
Oxygen, % dry basis
Btu/lb
Boiler Capacity
80%
6.04
5.14
37.63
57.23
0.66
78.20
5.26
1.51
9.23
13,897
50%
6.62
5.98
39.32
54.70
0.75
77.75
5.53
1.51
8.48
13,931
              3-30

-------
                    4.0  SAMPLING LOCATIONS AND TEST METHODS








     This section describes the sampling locations and test methods used to




characterize emissions from Boiler No. 4 at Burlington Industries Wake




Finishing Plant in Raleigh, North Carolina.  Seven sampling locations were used




in the emission testing program.  At three sampling locations (two at the




boiler mechanical collector inlet and one at the collector outlet), emissions




testing was conducted for particulate matter, total chromium content,




hexavalent chromium content, particle size distribution, and chromium




distribution with respect to particle size distribution.  At the collector




outlet location (boiler stack exit) visible emissions observations were




conducted to determine the opacity of emissions.  At the coal hopper, two




multiclone hoppers, and bottom ash hopper, grab samples of the coal feed,




hopper ash, and bottom ash were collected for hexavalent and total chromium




analysis.  The relative positions and the type of testing conducted at each




location are shown in the simplified process flow diagram (see Figure 4-1) and




accompanying Table 4.1.  The subsections which follow further describe each




sampling location and applicable test methods.








4.1  DOUBLE MECHANICAL COLLECTOR INLET (SAMPLING LOCATIONS B AND C)




     Particulate matter, hexavalent chromium, total chromium, particle size




distribution, and chromium distribution with respect to particle size




distribution were measured at the inlet to the double mechanical collector




controlling Boiler No. 4 as shown in Figure 4-2.  Four sampling ports were




installed on opposite sides in the vertical rectangular duct (39" by 192")




along the 39 inch width.  The east side of the duct is referred to as location
                                      4-1

-------
 Sampling Location F
  Sampling Locations
        B and C
           Coal Feed

 Sampling Location A
                                 To atmoshpere
                                     Stack
                                    I. D. Fan
                                   Secondary
                                  Multiclone
                                    Primary
                                  Multiclone
                                      Air
                                   Preheater
                                  Economizer
Boiler
 No. 4
                      Sampling Location E

                             Ash
                                                           JSampling Location D
                    -•^-Hopper Ash
Bottom Ash
                       Sampling Location G
Figure 4-1.  Simplified Process Air Flow Diagram of Boiler No. 4 and Emission
             Control Equipment at Burlington Industries Wake Finishing Plant.
                                    4-2

-------
                 TABLE 4.1.   SAMPLING  PLAN  FOR  BURLINGTON  INDUSTRIES
Sample Type
P articulate matter
Hexavalent chromium
Total chromium
Particle size distribution
Hexavalent and total chromium
distribution by particle size
Stack opacity
Hexavalent chromium, total
chromium
Sampling
Locations
B, C, F
B, C, F
B, C, F
B, C, F
B, C, F
F
A, D, E, G
Number ^
of Samples
3 (50%)
3 (80%)
3 (50%)
3 (80%)
3 (50%)
3 (80%)
**
**
3 (50%)
3 (80%)
3 composite
grab (50%)
3 composite
grab (80%)
Methods
EPA Method 5
EPA 5 using Tentative
EPA Method for Hexavalent
Chromium
EPA 5 using EPA Protocol
for Total Chromium
Impactor (Andersen,
Flow Sensor)
Impactor using Tentative
EPA Method for
Hexavalent Chromium
and EPA Protocol
for Total Chromium
EPA Method 9 -
Gravimetric, Tentative
EPA Method for
Hexavalent Chromium
EPA Protocol for
Total Chromium
**
"50%" indicates at 50% boiler capacity.
"80%" indicates at 80% boiler capacity.

Sampling Locations B and C = 3 (50%)  and 3  (80%),
Sampling Location F = 6 (50%) and 6  (80%).
                                         4-3

-------
   West
A
B  C
C  1=
D

• 1 •
1 .
i . i .
I . I .
• i
i
• 1 .
i
1 . 1 . 1 . 1 . 1
1 1 1
! /
1 . .
1 1
i
— • 	 O"
=1 D
=1 C
=1 B
ZI A
f
39"
I
                            8 Half Axes
                            3 Points/Half Axis
                           24 Total Points
                                  Section S-S
       39" —
     o o o o
     A B C D


     West
                Air Preheater
          To
         Multiclones
 Side Elevation View
                          58"
                   12"
                                                 From Boiler
                                               To Multiclones
                                              Sampling Ports
Figure 4-2.  Double Mechanical Collector Inlet (Sampling Locations B and C)
                                     4-4

-------
B, and the west side as location C.  These ports were located 12 inches (0.185




duct diameters) upstream of the entrance to the primary mechanical collector




and 10 inches (0.15 duct diameters) downstream from the air preheater.  Because




of the close proximity of potential flow disturbances, this location did not




meet EPA Method 1 sampling requirements; however, there was no other location




available for inlet testing.  To check for the degree of flow disturbance at




this location, the angle of flow misalignment was measured at each sampling




point using an S-type pitot and an angle indicator.  The average of the angles




measured at the inlet east (C) was 13.9 degrees; at the inlet west (C), the




average was 15.4 degrees.




     For the Method 5 testing (used for particulate matter, hexavalent




chromium, and total chromium determinations), a 3 x 8 sample point matrix (as




per Method 1 ) was used.  As a result of the design of the inlet sampling




location, two Method 5 sample trains were run on opposite sides of the duct,




each sampling a 3 x 4 sample point matrix.  At 50% boiler capacity, each of the




points was sampled for 10 minutes for a total of 120 minutes of sampling per




train; the trains were run sequentially to coincide with the 240 minutes of




sampling at the mechanical collector outlet sampling location.  At.80% boiler




capacity, each of the points was sampled for 5 minutes for a total of 60




minutes of sampling per train; in this case, the trains were run simultaneously




to correspond with the 60 minutes of sampling at the outlet.




     For the particle size testing (including hexavalent and total chromium




distribution by particle size), separate particle sizing trains were used to




sample both the east and west sides of the duct.  Three runs each were con-




ducted at both 50% and 80% boiler capacity.  The first run of each three run




series was conducted at a point of average velocity.  To ensure consistent
                                      4-5

-------
cut-sizes on the impactor plates, the second and third runs were conducted at




points having the same velocity.  Runs in both series were 4 1/2 to 5 minutes




in length.




4.2  DOUBLE MECHANICAL COLLECTOR OUTLET (SAMPLING LOCATION F)




     Particulate matter, hexavalent chromium, total chromium, particle size




distribution, and hexavalent and total chromium distribution with respect to




particle size were measured at the outlet to the double mechanical collector as




shown in Figure 4-3.  Four sampling ports were installed 90° apart on the




59 1/4" diameter stack and were located about 49 1/2" (0.84 duct diameters)




upstream from the stack exit and 160 inches (2.7 duct diameters) downstream




from the fan exit.




     For the EPA Method 5 sampling (used for particulate matter, hexavalent




chromium, and total chromium determinations), a total of 24 points, as per




Method 1, were sampled.  At 50% boiler capacity, each point was sampled for




10 minutes for a total sampling time of 240 minutes.  At 80% boiler capacity,




each point was sampled for 2.5 minutes for a total of 60 minutes.




     For the particle size tests (including hexavalent and total chromium




distribution by particle size) six runs each were conducted at both 50% and 80%




boiler capacity.  The first run of each six-run series was conducted at a




sampling point representing the average velocity in the stack.  To ensure




consistent cut-sizes on the-impactor plates, the remaining five runs at that




boiler load were conducted at points having the same velocity as the first




run.  The six particle size runs at 50% boiler capacity ranged from 4.5 to 5.0




minutes in duration.  The six runs at 80% boiler capacity ranged from 2.. 75 to




3.25 minutes in duration.




     Visible emissions observations were performed at the double mechanical




collector stack exit as specified by EPA Reference Method 9.  Observations were




conducted simultaneously with the Method 5 and particle size testing when




suitable conditions existed for valid observation.




                                      4-6

-------
                                N
            2 Axes
           12 Points/Axis
           24 Total Points
59.25" DIA
                             CH	V-   	3 A
                                          —  —5.5'
                                      D
                                    Section R-R
                59.25"
                  -O-
                   D
                                         Sampling Port
                                 49.5"
                                 48"
                                 112"
                                                    Roof Line
               From Fan
                                 Elevation View
Figure 4-3.  Double Mechanical Collector Outlet (Sampling Location F)
                                    4-7

-------
4.3  COAL FEED (SAMPLING LOCATION A)




    Grab samples representative of the coal feed to the boiler were taken at




the inlet to the coal hopper two times for each day's test run series.  Because




it takes approximately one hour for the coal to move from the inlet to the




hopper to the boiler, samples were taken approximately one hour before testing




was to begin (9:00 a.m.) and one hour before the last run of the day was to




end.  The two grab samples for each day were combined into a single sample for




analysis of hexavalent and total chromium content.








4.4  PRIMARY AND SECONDARY MDLTICLONE HOPPERS  (SAMPLING LOCATIONS D AND E)




    Grab samples of the flyash from (1) the primary multiclone hopper and (2)




the secondary multiclone hopper were collected two times during each day's test




run series: at the beginning of the first test run and at the end of the last




test run.  The two samples for each day from each hopper were combined into




single samples for analysis of hexavalent and total chromium content.








4.5  BOTTOM ASH (SAMPLING LOCATION G)




    Grab samples of the bottom ash from the boiler were collected two times




during each day's test run series, at the same time as the multiclone hopper




samples.  The two bottom ash samples for each day were also combined into a.




single sample for analysis of hexavalent and total chromium content.








4.6  VELOCITY AND GAS TEMPERATURE




    A type S pitot tube and an inclined draft  gauge manometer or two




differential pressure gauges in-parallel were used to measure the gas velocity




pressure (AP)«  Velocity pressures were measured at each sampling point across
                                      4-8

-------
the duct to determine an average value according to the procedures outlined in




Method 2 of the Federal Register.*  The temperature at each sampling point was




measured using a thermocouple and digital readout.








4.7  MOLECULAR WEIGHT




     Flue gas composition was determined utilizing procedures described in




Method 3 of the Federal Register.*  A bag sample was collected during each




particulate test run.  The bag contents were analyzed using an Orsat Gas




Analyzer.








4.8  PARTICULATE MATTER




     Method 5, as described in the Federal Register,* was used to measure




particulate grain loading at locations B, C, and F.  All tests were conducted




isokinetically by traversing the cross-sectional area of the stack and




regulating the sample flow rate relative to the flue gas flow rate as measured




by the pitot tube attached to the sample probe.  A sampling train consisting of




a heated, glass-lined probe, a heated 87 mm (3.4 inches) diameter glass fiber




filter (Gelman A/E), and a series of Greenburg-Smith impingers was employed for




each test.  An acetone rinse of the nozzle, probe, and filter holder portions




of the sample train was made at the end of each test.  The acetone rinse and




the particulate caught on the filter media were dried at room temperature,




desiccated to a constant weight, and weighed on an analytical balance.  Total




filterable particulate matter was determined by adding these two values.  See




Appendix D for detailed sampling procedures.
* 40 CFR 60, Appendix A, Reference Methods 2, 3, and 5, July 1, 1980,
                                      4-9

-------
4.9  PARTICLE SIZE DISTRIBUTION




     Particle size samples were obtained using Andersen Mark III and Flow




Sensor Cascade Impactors.  These in-stack, multistage cascade impactors have a




total of eight and seven stages, respectively, followed by a back-up filter




stage and particle size cut-offs ranging nominally from 0.5 to 15 microns.The




Flow Sensor includes a built-in preimpactor stage, in addition.  Substrates




were glass fiber filters, 64 mm in diameter for the Andersen impactors and 69




mm in diameter for the Flow Sensor impactors.  A constant sampling rate was




maintained through the test period.  Sampling rates were set for isokinetic




sampling as long as the sampling rate did not exceed the recommended flow rate




for the impactor.  See Appendix D for detailed sampling procedures.




     Three impactor runs each were conducted at 50% and 80% boiler capacity at




both the inlet east and the inlet west locations.  Six runs each were conducted




at 50% and 80% boiler capacity at the double mechanical collector outlet.  At




the locations sampled, a point of average velocity was sampled.  With the




exception of selection of the sampling point locations, the procedures used




followed those recommended in the "Procedures Manual for Inhalable Particulate




Sampler Operation" developed for EPA by the Southern Research Institute.*








4.10 HEXAVALENT CHROMIUM CONTENT




     Hexavalent chromium content was determined utilizing procedures described




in the tentative EPA Method "Determination of Hexavalent Chromium Emissions




from Stationary Sources" (see Appendix D).  The Method 5 filter catch collected




and weighed for each Method 5 run was taken and analyzed for hexavalent




chromium content using this method.  If was also used to determine the




hexavalent chromium content of representative portions the scrubber water




samples and the ESP and dust collector dust samples.
*Prepared for EPA under Contract No. 68-02-3118, November 1979.




                                      4-10

-------
4.11 TOTAL CHROMIUM CONTENT




     Total chromium content was determined using procedures described in the




"EMB Prototcol for Sample Preparation and Emission Calculation of Field Samples




for Total Chromium" in combination with Neutron Activation Analysis (NAA) (see




Appendix D).  Samples collected during Method 5 runs and first submitted to




analysis for hexavalent chromium were then analyzed for total chromium using




this method.  The total chromium content of the scrubber water samples and the




ESP and dust collector dust samples were also determined using these procedures




using a representative portion of the sample.








4.12 VISIBLE EMISSIONS




     Visible emission observations were performed by use of procedures




described in EPA Method 9.*  A certified visible emission reader was utilized.
*40 CFR 60, Appendix A, Reference Method 9, July 1, 1981.
                                      4-11

-------
                             5.0  QUALITY ASSURANCE


     Because the end product of testing is to produce representative emission

results, quality assurance is one of the main facets of stack sampling.

Quality assurance guidelines provide the detailed procedures and actions

necessary for defining and producing acceptable data.  Two such documents were

used in this test program to ensure the collection of acceptable data and to

provide a definition of unacceptable data.  These documents are:  the EPA

Quality Assurance Handbook Volume III, EPA-600/4-77-027 and Entropy's "Quality

Assurance Program Plan" which has been approved by the U. S. EPA, EMB.

     Relative to this test program, the following steps were taken to ensure

that the testing and analytical procedures produce quality data.


     o   Calibration of field sampling equipment.  (Appendix E describes
         calibration guidelines in more detail.)

     o   Checks of train configuration and on calculations.

     o   On-site quality assurance checks such as sampling train, pitot
         tube, and Orsat line leak checks, and quality assurance checks of
         all test equipment prior to use.

     o   Use of designated analytical equipment and sampling reagents.

     Table 5.1 summarizes the on-site audit data sheets for the sampling

equipment used for particulate testing at each sampling location, including

deviation limits.  In addition to the pre- and post-test calibration audits, a

field audit was performed on the meter boxes used for sampling.  Entropy used

the procedures described in the December 14, 1983 Federal Register (48FR55670).

In addition, the analytical balance used for filter weighing was audited with

Class "S" weights.  Appendix E includes the audit run data sheets for each dry

gas meter used for particulate testing and audit data sheets for the other

sampling equipment.
                                       5-1

-------
                      TABLE  5.1.   FIELD  EQUIPMENT  CALIBRATION
Equipment
Reference
Allowable
Error
Ac tual
Error
Within
Allowable
Limits
Double Mechanical Collector Inlet East
Meter box (N-3)
Meter box thermometer
Impinger thermometer
Stack thermometer
Orsat analyzer
Trip balance
Analytical balance
Wet test meter
ASTM-3F at ambient
temperature
ASTM-3F at ambient
temperature
ASTM-3F at stack
temperature
% 02 in ambient air
IOLM standard weight
Class "S" standard
weight
Y ^O.OSY
5°F
2°F
7°F
0.7%
0.5 grams
0.1 mg
1.007
-2°
-2°
+2°
OK
0
0
^^
^^^
^
^
Double Mechanical Collector Inlet West
Meter box (N-12)
Meter box thermometer
Impinger thermometer
Stack thermometer
Orsat analyzer
Trip balance
Analytical balance
Wet test meter
ASTM-3F at ambient
temperature
ASTM-3F at ambient
temperature
ASTM-3F at ambient
temperature
% $2 in ambient air
IOLM standard weight
Class "S" standard
weight
Y + 0.03Y
5°F
2°F
7°F
0.7%
0.5 grams
0.1 mg
0.993
+2°
+1°
-2°
OK
0
0
^
^
"^
^
(continued on next page)
                                        5-2

-------
TABLE 5.1.  FIELD EQUIPMENT CALIBRATION (continued)
Equipment
Reference
Allowable
Error
Actual
Error
Within
Allowable
Limits
Double Mechanical Collector Outlet
Meter box (N-6)
Meter box (N-7)
Meter box thermometer
Impinger thermometer
Stack thermocouple
Orsat analyzer
Trip balance
Analytical balance
Wet test meter
Wet test meter
ASTM-3F at ambient
temperature
ASTM-3F at ambient
temperature
ASTM-3F at stack
temperature
% 02 in ambient air
IOLM standard weight
Class "S" standard
weight
Y + 0.03Y
Y +_ 0.03Y
5°F
2°F
11°F
0.7%
0.5 grams
0.1 mg
1.012
0.988
-2°
0°
-5°
OK
0
0
^
-
^
^
^
^
^
^
                        5-3

-------
     As a check on the reliability of the method used to analyze the filters




for particle size tests, sets of filters that had been preweighed in the lab




were resubmitted for replicate analysis.  Table 5.2 summarizes these results.




     Audit solutions prepared by the EPA were used to check the analytical




procedures of the laboratories conducting the hexavalent and total chromium




analyses.  Table 5.3 presents the results of these analytical audits.  The




audit tests show that the analytical techniques were good.




     The sampling equipment, reagents, and analytical procedures for this test




series were in compliance with all necessary guidelines set forth for accurate




test results as described in Volume III of the Quality Assurance Handbook.
                                      5-4

-------
TABLE 5.2.  PARTICLE SIZE BLANK FILTER AND REACTIVITY FILTER ANALYSIS
Sample type
Particle size
blank run filters
B256
A256
B257
A257
B258
A258
B259
A259
SF138
Particle size
reactivity run
filters
B212
A212
B213
A213
B214
A214
B215
A215
SF128
Original tare
weight, mg


162.64
147.37
162.80
146.23
163.06
147.12
162.64
146.43
270.53



156.01
138.58
156.39
138.47
156.00
137.93
156.30
137.98
267.03
Blank weight,
mg


162.68
147.42
162.76
146.23
163.01
147.09
162.65
146.47
270.53



156.00
138.59
156.40
138.49
156.09
137.91
156.19
137.83
267.13
Net weight,
mg


+0.04
+0.05
-0.04
0.00
-0.05
-0.03
+0.01
+0.04
-0.03



-0.01
+0.01
+0.01
+0.02
+0.09
-0.02
-0.11
-0.15
+0.10
                                 5-5

-------
                   TABLE 5.3.   AUDIT REPORT CHROMIUM ANALYSIS
Plant:
Date samples received:
Sample analyzed by:_
Reviewed by:	
                                                   Task No.:    301
                                                   Date analyzed:
                                                   Date of review:
Sample
Number
QA -7-
Qfi-3
QA- °i
Qk-td
Q*-H


ug/ml
Cr+o or Cr
5^j Cr
[o jj-q ^
(,(,.33/A$ ^
132.1-^3 C
-------