EPA-AA-CPSB-83-01
                            Technical Report
                         Humidity Calculations
                               Used For
                   Mobile  Source Emission Testing
                              Eric Zellin


                            February,  1983
                                NOTICE


Technical Reports  do  not  necessarily represent final  EPA   decisions
or  positions.   They  are intended to present technical analysis of
issues using data  which are currently available.  The purpose  in the
release of such  reports is to facilitate the exchange   of   technical
information and  to inform the public of technical developments which
may form the basis for  a  final EPA decision, position,  or  regulatory
action.

This document has been approved under the EPA peer review process and is available
for internal and  external distribution.
                 U.  S.  Environmental Protection Agency
                  Office of Air,  Noise, and Radiation
                       Office of  Mobile Sources
                        Certification Division
                Certification Policy and Support Branch
                          2565 Plymouth Road
                      Ann Arbor,  Michigan  48105

-------
    Humidity Calculations Used for Mobile Source Emission Testing
measurement  of  specific  humidity  in units of grains of water per
pound of dry air, grams of water per gram of dry air,  or  grams  of
water per kilogram of dry air.

The  measurement  of  percent  relative  humidity  is  required  for
analysis of carbon monoxide (CO) whenever water vapor  is  extracted
from  exhaust  gas  to  prevent  interference  in CO analyzers.  The
carbon monoxide analyzers used at the EPA laboratory  in  Ann  Arbor
are  essentially free of interference from water vapor, and for this
reason, CO measurements at MVEL are no longer corrected for relative
humidity; however,  the  correction  is  applied  at  other  testing
facilities that use equipment susceptible to interference.

Emission  measurements  for  1979-1983  model-year  engines  must be
converted from a dry to  a  wet  basis.   The  calculation  used  to
perform  the  conversion  includes a term for the water-vapor volume
concentration, on a dry basis, of the engine intake air.  The water-
vapor volume concentration  equals  the  specific  humidity  of  the
engine intake air multiplied by a constant.

Many  methods  exist  for  measuring  humidity and are classified as
primary and secondary.  Secondary  methods  must  be  calibrated  by
means  of  a primary method and are not ordinarily used for emission
testing because most secondary  methods  lack  sufficient  accuracy.
Primary  methods are used that provide good accuracy, are relatively
easy and economical to use, and are capable of providing a  repeated
(or  continuous) humidity measurement.  Two instruments that satisfy
these requirements, and are used for most emission testing, are  the
dew-point hygrometer and the wet-bulb psychrometer.

Dew-point   hygrometers   and   wet-bulb   psychrometers  both  have
acceptable accuracy, when properly calibrated and optimized, and are
capable of continuously measuring humidity.  In the past,  the  wet-
bulb  psychrometer  was the most common instrument in use because it
was easier and cheaper to use than the  hygrometer.   The  dew-point
hygrometer has always had the advantage of superior accuracy.

Within  the  last  ten years, improvements in the design of the dew-
point hygrometer have produced an instrument that is easier  to  use
for emission testing than the wet-bulb psychrometer and has superior
reliability,  as  well as better accuracy.  The dew-point hygrometer
is still more expensive than  the  wet-bulb  psychrometer;  however,
steady  cost  reduction,  plus  the  operational  superiority of the
hygrometer, are rapidly  making  it  the  preferred  instrument  -for
humidity measurement.
                                                      February, 1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing
    Humidity Calculations Used for Mobile Source Emission Testing
                              Abstract

This  reference document provides a summary of the calculations used
to determine relative and specific humidity of moisture  in  air  for
mobile  source  (motor vehicle and engine) emission and  fuel economy
testing at the U.S.  Environmental Protection Agency  Motor  Vehicle
Emissions Laboratory in Ann Arbor, Michigan.  The reference includes
calculations  required to determine the saturation vapor pressure of
water,  psychrometric  equations  used  to  calculate  the   partial
pressure  of  water  vapor for wet-bulb psychrometers, and equations
for the enhancement factor of water  and  ice.   Described  are  the
methods used from  1971 to 1983.


Purpose.   This  reference  provides a description of the procedures
used to calculate  humidity  at  the  EPA  Motor  Vehicle  Emissions
Laboratory  (MVEL).   Several  procedures have been used at MVEL for
different applications.  For heavy duty engine certification between
1979 and 1983, the humidity calculation procedure was defined  in the
Federal Register;  for light duty motor vehicles, the  procedure  was
determined ' by the testing laboratory from technical and operational
considerations, as  well  as  the  state  of  the  art   of  humidity
measurement.   Manufacturers,  EPA  contractors,  and  EPA employees
often need to  know  what  procedure  is,  has  been,  or,  in  some
instances,  should  be  used  to calculate humidity.  This reference
provides a  single  document  that  describes  the  procedures  used
historically  at  MVEL,  plus information about procedures that have
not been used, but which may be useful in the future.

Overview.  Humidity measurement  is  required  for  three  different
calculations used  in the analysis of mobile source emission and fuel
economy:  (1)  to  correct the measurement of oxides of  nitrogen for
the effect of moisture in engine intake  air,  (2)  to   correct  the
measurement  of  carbon  monoxide  (CO) when water is extracted from
exhaust gases., and (3) to convert heavy duty engine emissions  from a
dry to a wet basis.

The humidity of water in air has an effect  on  the  measurement  of
oxides  of  nitrogen.   As a result of a study made for  EPA by Scott
Research Laboratories Inc.  in 19701 * , EPA test procedures  correct
the  measurement   of oxides of nitrogen for the specific humidity of
water in air.  Several different correction equations have been used
historically to correct oxides of nitrogen for humidity.  These  can
be  found  in  various  editions of the Federal Register and are not
described  here;   however,  all  of  these  equations  required  the

                                                      February, 19~83

-------
    Humidity Calculations Used for Mobile Source Emission Testinq
Humidity measurements.   Three  measurements are required to measure
relative and specific humidity: barometric pressure,  ambient  (dry-
bulb)   temperature,  and  either  wet-bulb  temperature,  dew-point
temperature,  or  for   temperatures   below   freezing,   ice-point
temperature.    From   these   measurements,   several  intermediate
calculations are performed.  First, it is necessary to calculate the
saturation vapor pressure of  water  at  each  temperature;  several
different  equations have been used for this at MVEL.  Second, it is
necessary to calculate the partial pressure of water vapor.   For  a
dew-point  hygrometer this is a trivial calculation; however for the
wet-bulb  psychrometer  a  special   equation,   the   psychrometric
equation,  is  required.   Relative  and  -specific humidity are then
directly calculated from these values.  Each of  these  calculations
is described in detail below.

Experimental variables.   All  of  these  methods  are  similar  and
require the measurement of barometric pressure, ambient temperature,
and either dew-point  (ice-point) temperature measured  with  a  dew-
point  hygrometer  or  wet-bulb temperature measured with a wet-bulb
psychrometer.  In this article, the following symbols  are  used  to
represent  values  of  each measured variable for different units of
temperature and pressure.
    Tamb(K) =  ambient temperature
    Tamb(C) =  ambient temperature
    Tamb(F) =  ambient temperature
degrees Kelvin.
degrees Celsius.
degrees Fahrenheit.
    Twet(K) =. wet-bulb temperature
    Twet(C) =  wet-bulb temperature
    Twet(F) =  wet-bulb temperature
 degrees Kelvin.
 degrees Celsius.
 degrees Fahrenheit.
    Tdew(K) =  dew-point temperature
    Tdew(C) =  dew-point temperature
    Tdew(F> =  dew-point temperature
  degrees Kelvin.
  degrees Celsius.
  degrees Fahrenheit
    Tice(K) =  ice-point temperature — degrees Kelvin.


    Pbaro   =  barometric  pressure  —  same  pressure   units   as
    saturation vapor pressure.


Many  of  the  equations presented in this article are pressure unit
independent; that is, the equation is valid for any pressure unit as
long as all pressures are expressed in the same units, and  as  long
as the pressure of a perfect vacuum is defined to equal zero.
                                                      February, 1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing
Saturation vapor pressure.   Ambient  temperature  and  either  dew-
point,   ice-point,   or   wet-bulb   temperature    are    measured
experimentally  and  the saturation vapor pressure of water (or ice)
is calculated at each temperature.  The following variables are used
to represent saturation vapor pressure at different temperatures and
pressures:


    Pamb(Pa)   =  the  saturation  vapor  pressure  at  the  ambient
    temperature — Pascals.

    Pamb(InHg) =  the  saturation  vapor  pressure  at  the  ambient
    temperature — inches of mercury.


    Pwet(Pa)   =  the saturation  vapor  pressure  at  the  wet-bulb
    temperature — Pascals.

    Pwet(InHg) =  the  saturation  vapor  pressure  at  the wet-bulb
    temperature — inches of mercury.


    Pdew(Pa)   =  the saturation vapor  pressure  at  the  dew-point
    temperature — Pascals.

    Pdew(lnHg) =  the  saturation  vapor  pressure  at the dew-point
    temperature — inches of mercury.


    Pice(Pa)   =  the saturation vapor  pressure  at  the  ice-point
    temperature — Pascals.


Historically,  MVEL  has  used four different equations to calculate
saturation vapor pressure.  The actual difference between  equations
is  not large and the effect of differences is much less.significant
than other sources of error in vehicle emission testing.

The oldest equation used at MVEL is formula 2 of Smith,  Keyes,  and
Gerry3,  equation  (1)  below,  which  has  been used for light duty
vehicle testing to the present date (1983).  Equation (1) determines
saturation vapor pressure Psat (inches of  mercury)  at  temperature
T(K)  (degrees Kelvin ITS-26).  Pamb(InHg), Pdew(InHg), or Pwet(InHg)
can  be  determined by substituting Tamb(K), Tdew(K), or Twet(K) for
T(K)  in equation (1):
                                                      February,  1983

-------
    Humidity Calculations Used for Mobile Source Emission Testinq
       Psat(InHg)
(1)
where
               -[X / T(K)]  [A+BX+CX  ] / [1  + D X]
    29.92 PC 10

   Tc   =  647.27
   PC   =  218.167
   A    =  3.2437814
   B    =  5.86826E-3
   C    =  1.1702379E-8
   D    =  2.1878462E-3
   T(K) = .5555 [ T(F) -
   X    =  Tc - T(K)
   T(F) = temperature degrees
                                32 ] + 273.16
Formula 2 of Smith, Reyes, and Gerry
range of 10 to  150 degrees Celsius.
                                     Fahrenheit,
                               is  valid  for  a  temperature
In  1947  the  Goff-Gratch  formulation  for  the  saturation  vapor
pressure of water over water and ice, which is not  presented  here,
was  adopted  for international use in Resolution 164 of the Twelfth
Conference  of  Directors  of   the   International   Meteorological
Organization4.   The Goff-Gratch formulation, which is still used in
meteorology, was used at the  U.S.   National  Bureau  of  Standards
until  1971,  when  the  NBS developed a new equation.  The 1971 NBS
equation, equation  23  of  Wexler  and  Greenspan,  is  the  second
equation used at MVEL5.  This equation,  (2) below, has been used for
heavy   duty  engine  testing  from  1979  to  1983.   Equation  (2)
determines saturation vapor pressure Psat  (Pascals)  at  temperature
T(K)  (degrees Kelvin IPTS-68).  Pamb(Pa), Pdew(Pa), or Pwet(Pa) can
be determined by substituting Tamb(K), Tdew(K), or Twet(K) for  T(K)
in equation (2):
(2)
where
Psat(Pa)

   B
   F(0) '
   P(D '•
   F(2) ••
   F(3) :
   F(4) '
                       B In T(K)
•   exp

-1.21507990E+01
-8.49922000E+03
-7.42318650E+03
+9.61635147E+01
+2.49176460E-02
-1.31601190E-05
 9
 I
i=0
 F(5)
 F(6)
 F(7)
 F(8)
 F(9)
                                               i-2
                                    T(K)
                                           -1 . 14604540E-08
                                           +2.17012890E-11
                                           -3.61025800E-15
                                           +3.85045190E-18
                                           -1.43170000E-21
Equation  (2)  is valid  for a temperature range of 0 to  100 degrees C.
                                                      February,  1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing
In 1976 Wexler published a revision to the original saturation vapor
pressure  equation'.   Equation  15  from the revision, equation (3)
below, can be used  to  calculate  saturation  vapor  pressure  Psat
(Pascals)  at  temperature T(K) (degrees Kelvin IPTS-68).  Pamb(Pa),
Pdew(Pa), or Pwet(Pa) can be  determined  by  substituting  Tamb(K),
Tdew(K), or Twet(K) for t(K) in equation (3):
(3)    Psat(Pa)

where     F(0) =
                       F(7) In T(K)
                    exp
                                      6
                                    + I
                                     i=0
                                                  i-2
          F(2) =
          F(3) =
                  -0.2991272900E+04  F(4)
                  -0.6017012800E+04  F(5)
                  +0.1887643854E+02  F(6)
                  -0.2835472100E-01  F(7)
                                              T(K)
                                             +0.1783830100E-04
                                             -0.8415041700E-09
                                             +0.4441254300E-12
                                             +0.2858487000E+01
Equation
Celsius.
          (3)  is  valid for a temperature range of 0 to 100 degrees
In 1977 Wexler published a  third  equation
determine  the  saturation vapor pressure of
                equation
                (Pascals)
                                             that
                                             ice
this reference
pressure  Psat
                                                   can  be  used  to
                                                    Equation 54 from
                          (4)  below,  determines  saturation  vapor
                           at temperature T(K) (degrees Kelvin IPTS-
68).  Pwet(Pa) or Pice(Pa) is determined by substituting Twet(K)  or
Tice(K) for T(K) in equation (4):
(4)    Psat(Pa)

where     F(0) =

          F(2) =
                       F(5) In T(R)
                    exp
                                      4
                                      Z
                                     j-o
                                                  J-1
                  -0.58653696E+04  F(3)
                  +0.22241033E+02  F(4)
                  +0.13749042E-01  F(5)
                                              T(K)
                                           -0.34031775E-04
                                           +0.26967687E-07
                                           +0.69186510E+00
Equation  (4)  is  valid  for temperatures less than or equal to the
triple point of water, 0.1 degrees Celsius.

Equations (1)-(4) determine saturation vapor pressure of pure  water
or ice (without air).  The saturation vapor pressure of water in air
differs  from  the  vapor  pressure  of  pure  water or ice by small
amounts: about 1/2 percent at atmospheric temperature and  pressure.
A  correction,  the  enhancement  factor,  can be applied to correct
saturation vapor pressure for the effect of air—although Mr  Saburo
Hasegawa  of  the U.S.  National Bureau of Standards has stated that
the magnitude of this correction is usually much smaller than
sources of error in humidity measurement.8
                                                               other
Hyland  developed  equations  that  can  be  used  to  determine the
enhancement factor'.  Because these equations are difficult  to  use
for  computation, Buck developed simpler equations based on Hyland1s
                                                      February, 1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing
data10.  These equations are described  below  for  water,  equation
(5),  and  ice,  equation  (6).  Equations (5) and (6) determine the
enhancement factor of water, Fw5,  or  ice,  Fi5,  from  temperature
T(K),  degrees  Kelvin,  and barometric pressure Pbaro(Pa), Pascals.
Because Buck's original equations are based on  Celsius  temperature
and  millibar  pressure  units,  coefficients  B, C,  and E have been
modified for use with Kelvin temperature and Pascal pressure  units.
The equation for the enhancement factor of liquid water is given by:


(5)    Fw5  =  1 + A
                                                                 2
           + Pbaro(Pa) [B + C [ T(K) - 273.15 + D + E Pbaro(Pa) ]  3

where  A  =  4.1E-04
       B  =  3.48E-08
       C  =  7.4E-12
       D  =  30.6
       E  =  -3.8E-04

Equation  (5)  is valid for a temperature range of -20 to 50 degrees
Celsius.

The equation for the enhancement factor of ice is given by:


(6)    Fi5  =  1 + A
                                                                 2
           + Pbaro(Pa) [B + C [ T(K) - 273.15 + D + E Pbaro(Pa) ]  ]

where  A  =  4.8E-04
       B  =  3.47E-08
       C  =  5.9E-12
       D  =  23.8
       E  =  -3.1E-04

Equation (6) is valid  for a temperature range of -60  to  0  degrees
Celsius.

To   apply   the  enhancement   factor,  one  simply  multiplies  the
uncorrected saturation vapor pressure by the enhancement  factor  to
determine  the  corrected value as  illustrated in equation (7) below
for water and equation (8) for  ice:

       Pamb(corrected)  =  Fw5  Pamb(uncorrected), 50 C ^ T £ -20 C
(7)    Pdew(corrected)  =  Fw5  Pdew(uncorrected)
       Pwet(corrected)  =  Fw5  Pwet(uncorrected)

(8)    Pice(corrected)  =  Fi5  Pice(uncorrected),  0 C £ T £ -60 C

Equations  (7) and (8)  are valid for any consistent set  of  pressure
units.

MVEL   has  not  applied  an  enhancement  factor  correction  to any

                                                      February, 1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing
humidity measurement before 1983.

Partial pressure of water vapor.  Saturation vapor  pressure  values
are  used  to  determine the partial pressure of water vapor Pv.  If
dew-point  or  ice-point  temperatures  are  measured,  the  partial
pressure  of  water  vapor  is defined td.equal the saturation vapor
pressure, corrected for enhancement factor, at the dew-point or ice-
point temperature—equations (9) and (10)  below:

(9)    Pv  =  Pdew  or

(10)   Pv  =  Pice

If a wet-bulb psychrometer is  used  to  measure  humidity,  several
psychrometric  equations  are  available for calculating the partial
pressure  of  water  vapor  Pv.   Equation  (11)  is  based   on   a
thermodynamic model of wet-bulb behavior:

                   [Pbaro - Pwet]  [Tamb(F) - Twet(F)]
(1.1)   Pv = Pwet - 	:	
                           2831 - 1.43 Twet(F)


Pressure can have any consistent set of units in equation  (11).

Equation  (11)  is  included here because it is in fairly common use
and has been used by several automobile manufacturers  for  emission
testing.   In  addition, equations similar to (11) have been used to
prepare several published psychrometric charts.  The author does not
feel qualified to make a statement  about  the  merits  of  equation
(11);  however,  it  is  important  to  point out that there is poor
correlation between  results  calculated  using  equation  (11)  and
results calculated from the equations used at MVEL.

Although a thermodynamic model of wet-bulb behavior has been used to
prepare many psychrometric charts, it has been stated that classical
thermodynamics   does   not   provide   a   completely  satisfactory
description of  a  wet-bulb  system11 12 13 14.   Several  empirical
equations  have  been  developed which may be preferable to equation
(11) because they are based on experimental results.  Equations (12)
and (13) are equivalent forms of Ferrels equation4 14 1S 14 that can
be used to determine the partial pressure of water vapor.   Equation
(12)  determines  Pv  from ambient and wet-bulb temperature (degrees
Fahrenheit) and has been used at  MVEL  to  determine  humidity  for
light  duty  vehicle  testing  to 1983.  Equation (13) determines Pv
from temperature measured in degrees Kelvin and  has  been  used  at
MVEL to determine humidity for heavy duty engine testing.
                                                      February,  1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing
(12)   Pv  =  Pwet - [Tamb(F) - Twet(F)]

        .000367 Pbaro [Twet(F) + 1539] / 1571

(13)   Pv  =  Pwet - [Tamb(K) - Twet(K)]

        .000660 Pbaro [1 + .00115 [Twet(K) - 273.15]]

Equation (14), developed at the Japan Meteorology Agency, is similar
in  form to Ferrels equation, and appears to be superior for Assmann
psychrometers of the type used by the Japan Meteorology Agency17.

(14)   Pv  =  Pwet - [Tamb(K) - Twet(K)]

        .000700 Pbaro [1 - .00560 [Twet(K) - 273.15]]

Any consistent set of .pressure units may be used in equations   (12)-
(14).

Relative and specific humidity.   Equation (15) is used to determine
percent relative humidity R,

(15)   R  =  100 Pv / Pamb

for any consistent set of pressure units.

The specific humidity H (grains of water per pound of  dry  air)   is
used  to  correct  oxides  of nitrogen emission measurements for the
effect of humidity.  Equation (16) is used for  light  duty  vehicle
testing:

(16)   H  =  4347.8 Pv / [Pbaro - Pv]

for  any consistent set of pressure units.  In the Federal Register,
equation (16) is sometimes combined with equation  (15)andwritten
as:

(17)   H  =  43.478 R Pamb /  [Pbaro - R Pamb / 100]  .

It  can  be  seen  that  equations  (16)  and  (17)  are equivalent.
Equation  (16)  is  preferable  because  it  is  simpler  and   more
fundamental than (17).

Equation (18) is an alternative representation of equation (16) that
calculates specific humidity  in units of grams of water per kilogram
of dry air:

(18)   H  =   .0006211 Pv / [Pbaro - Pv]

A  slightly  different  version  of  equation  (16)  has  been  used
internally at MVEL to investigate humidity  calculation  procedures.
The constant 4347.8 can be expressed more accurately as


                                                      February,  1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing   10
       18.01534 (kg/mole water)
(19)   	 (7000 grains/lb) = 4353.484
        28.967  (kg/mole air)

Equation  (20)  has been published in internal documentation at MVEL
investigating humidity calculation procedures, but it has  not  been
used for official certification or fuel economy testing.

(20)   H  =  4353.484 Pv / [Pbaro - Pv]

for any consistent set of pressure units.

A  third  constant  has  been used for heavy duty engine testing for
model years  1979-1983.   The  constant  in  the  specific  humidity
equation can be expressed as

       18.01534 (kg/mole water)
(21)   	  = .62198 * .62200
        28.9645 (kg/mole air)

This  value has been used to calculate specific humidity in units of
grams of water per gram of dry air—equation (22) below:

(22)   H  =  .622 Pv / [Pbaro - Pv]

The same heavy duty test procedure calculates specific  humidity  in
units  of  grains  of  water  per pound of dry air by converting the
constant in equations  (21) and (22):

(23)   H  =  [453.59 gm/lb / .0648 gm/gr] .622 Pv / [Pbaro - Pv]

          =  4353.904 Pv / [Pbaro - Pv]

A third value, the water vapor volume concentration Y,  is calculated
from equation (22) to determine Pv / [Pbaro - Pv]—equation (24)

(24)   Y  =  [28.9645 / 18.01534] .622 Pv / [Pbaro - Pv]

          =  1.000032 Pv / [Pbaro - Pv]

For model years 1984 and  later,  the  equation  used   to  calculate
specific humidity for heavy duty engine testing is the  same as light
duty, namely, equations (16)-(18).

If a user wishes to use the most accurate specific humidity equation
available, equations (25) and  (26) can be used:

       18.01534 (kg/mole water)
(25)   	:	 (7000 grains/lb) = 4353.86
        28.9645  (kg/mole air)

(26)    H  =  4353.86 Pv / [Pbaro - Pv]

                                                      February,  1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing   n
Humidity measurement below freezing.    Although   MVEL   does   not
presently test manufacturer emission and fuel  economy  vehicles  at
temperatures  below  freezing, equations in this article can be used
at low temperatures.

At temperatures below 0°C, relative humidity  should  be  determined
with  respect  to  water,  that  is,  Pamb should be determined with
respect to the saturation vapor pressure  of  liquid  water  at  the
ambient  temperature4 14.   If  temperature  is  below  freezing and
saturation vapor pressure equation (1), (2), or (3) (for  water)  is
used, it is necessary to extrapolate below 0°C.

To  determine  Pv,  one can use a dew-point hygrometer or a wet-bulb
psychrometer.   For  dew-point  hygrometers,  it  is  necessary   to
determine  whether the hygrometer measures ice-point temperature, in
which case equations (4)  and  (6)  can  be  used,  or  whether  the
hygrometer  measures the dew-point temperature of supercooled water.
Equations (1)-(3) can be extrapolated  for  supercooled  water,  and
used with equation (5).

If  a photoelectric detector is used to maintain a mirror at the dew
point or frost point for  temperatures  below  0°C,  the  saturation
vapor  pressure  equation  for  ice  should  probably  be used.  For
photoelectric control, Wexler states "There can be  little  question
of  whether  the  liquid or solid phase is involved, for supercooled
liquid will not long last under such conditions without changing  to
ice"
If  a wet-bulb psychrometer is used, Ferrels equation is valid below
0°C and can be used.14 If the wet bulb wick is covered with ice, the
Pwet term in equation (12) or (13) should be calculated with respect
to ice.14 As mentioned above, however, the Pamb term would still  be
calculated  with  respect  to water.  If a bare bulb is covered with
ice, special corrections may be  required  that  are  not  described
here4.

Caution  is  required  for  any  attempt  to measure humidity at low
temperatures  with  a  wet-bulb  psychrometer.   Wexler  states  "At
temperatures below freezing, the psychrometer continues to function,
but  the  magnitude  of the depression is greatly reduced and proper
precautions  must  be  taken  to  obtain   reliable   data."1*   For
temperatures  below  freezing,  dew-point hygrometers appear to have
greater than ordinary advantages versus the wet-bulb psychrometer.

Summary.  This article describes several procedures for  calculating
humidity  that  have  been  of interest to MVEL, either because they
have been used for vehicle emission testing, or because they may  be
useful  in  the  future.  Equations (4), (6), and (14) have not been
used at MVEL in the past and there are presently (1983) no plans  to
use  them  for certification or fuel economy testing.  Nevertheless,
these equations are included here because they appear to be the best
equations  currently   available   for   testing   under   important
conditions:   cold   temperature   or  with  Assmann  psychrometers.

                                                      February, 1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing
Information about these equations may be important in the future.

Readers should not assume that humidity  calculation  procedures  in
use  elsewhere are unacceptable for emission or fuel economy testing
simply because they are  not  described  here.   Many  high  quality
equations  are  described  in  the  literature,  especially  for the
calculation of saturation vapor  pressure.   Most  saturation  vapor
pressure equations agree very closely with the ones presented here.

On   the   other   hand,   readers  should  carefully  evaluate  any
psychrometric equation used to calculate  the  partial  pressure  of
water  vapor  from ambient and wet-bulb temperature.  Wide variation
exists between results produced by different psychrometric equations
and a choice of  incompatible  psychrometric  equations  can  easily
cause correlation problems.

Appendix A contains a summary of the humidity equations used by MVEL
for  vehicle emission and fuel economy testing at different times in
history.
                                                      February,  1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing   13
                             References


1.  Effect of laboratory ambient conditions  on  exhaust  emissions.
Final  report to Nat'l Air Pollution Control Admin., Project CPA 22-
69-156, Scott Research Labs., Inc., April 24, 1970.

2.  Manos, M.  J., Bozek, J.   W.,  and  Huls,  T.   A.,  Effect  of
laboratory    ambient   conditions   on   exhaust   emissions,   SAE
Transactions, paper 720124,  (1972)

3.  Keenan, J.  H.  and Keyes, F.  G., Thermodynamic  Properties  o_f_
Steam, John Wiley and Sons, New York p.14,(1936).

4.  List,  Robert  J.   editor,  6th ed., Smithsonian Meteorological
Tables.  Smithsonian Institute Press.

5.  Wexler, A.  and Greenspan, L., Vapor pressure equation for water
in the range 0 to 100° C, J.  Res.  Nat.  Bur.  Stand.  (U.S.), 75A,
Phys.  and Chem., No.  3, 213-230  (1971).

6.  Wexler, A., Vapor pressure formulation for water in the range  0
to   100°  C—A Revision.  J.  Res.  Nat.  Bur.  Stand.  (U.S.), 80A,
Phys.  and Chem., No.  5 and 6, 775-785  (1976).

7.  Wexler, A., Vapor pressure formulation for ice.  J.  Res.   Nat.
Bur.  Stand.  (U.S.), 81A, Phys.   and Chem., No.   1, 775-785  (1977).

8.  Hasegawa,  S., Telephone conversation with Zellin, E., February,
1983.

9.  Hyland, R.  W., A correlation  for the second interaction  virial
coefficients  and enhancement factors for moist air.  J.  Res.  Nat.
Bur.  Stand.  (U.S.), 79A, Phys.   and Chem., No.  4, 551-560  (1975).

10.  Buck, A.  L., New equations for computing  vapor  pressure  and
enhancement factor.  J.  Appl.  Metero., 20,  1527-1532  (1981).

11.  Sherwood, T.  K.  and Comings, E.  W., An experimental study of
the  wet-bulb  hygrometer,   Trans.   Am  Insti.  Chem.  Eng.  28, 88
(1932).

12.  Arnold, J.  H., The theory of the psychrometer.  Physics 4, 255
(1933).

13.  Carrier, W.  H.  and Mackey,  C.   0.,  A  review  of  existing
psychrometric  data  in  relation  to practical engineering problems.
ASME Trans.  59, 32, and 528  (1937).

14.  Bindon, H.  H., A critical review of tables and charts used  in
psychrometry.   Humidity  and  Moisture;  Measurement and Control in
Science and Industry, vol  1, pp 3, Wexler, Arnold editor.

                                                      February, 1983

-------
    Humidity Calculations Used for Mobile Source Emission Testing   14.
15.  Wexler, A.   and  Brombacher,  W.   G.,   Methods  of  Measuring
Humidity and Testing Hygrometers, NBS Circular 512 (1951).

16.  Ferrel,  Annual  Report,  Chief, U.S.  Signal Officer, Appendix
24, 233-259 (1886).

17.  Yoshitake, M.  and Shimizu, I.,  Experimental  results  of  the
psychrometer  constant.   Humidity  and  Moisture;  Measurement  and
Control _in_  Science  and  Industry,  vol  1,  pp 70,  Wexler,  Arnold
editor.
                                                      February,  1983

-------
Appendix A -- Summary of Humidity Calculations Used at MVEL
April. 1983
.
Saturat ion
Vapor Pressure
Enhancement
Factor
Psychrometr ic
Equation
Specif ic
Humidity
Relative
Humidity
Water Vapor
Volume
Concentrat ion
Light
Vehicle
Tri
to
1983'
(1)
None
(12)
(17)
(15)
None
Duty
i And
jck
1983+'
(3)
(5)
(13)'
(16)
(15)
None
Heav>
to
1978'
(1)
None
(12)
(17)
(15)
None
/ Duty Enc
1979-
1983'
(2)
None
(13)
(22)
(23)
(15)
(24)
jine
1984+'
(3)
(5)
(13)1
(16)
(15)
None
Humii
to
1983'
<'>
None
(13)
(20)
(15)
None
dlty Evali
1983+'
(water)
(3)
(5)
(13)
(16)
(26)
(15)
None
jat ion
1983+'
(ice)
(4)
(6)
(13)
(16)
(26)
(15)
None
Numbers in parenthesis refer to equations in the body of the Technical  Report.
1.  Revised light duty humidity calculation procedures were implemented April  4,  1983.
2.  Model year.
3.  PsychrometrIc equation not required for dew-point hygrometers.

-------