EPA-330/9-7 4-001 J|,b
            NATIONAL WASTE TREATMENT CENTER
                     CINCINNATI
         OPERATIONAL CONTROL PROCEDURES
                       for the
             ACTIVATED SLUDGE PROCESS
            PART  I - OBSERVATIONS
            PART II - CONTROL TESTS
                     MAY 1974
       UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
           OFFICE OF WATER PROGRAM OPERATIONS

-------
 NATIONAL WASTE TREATMENT CENTER - CINCINNATI
        OPERATIONAL CONTROL PROCEDURES
                   FOR THE
           ACTIVATED SLUDGE PROCESS
     PART  I  -  OBSERVATIONS
   PART  II  -  CONTROL  TESTS
                     by
             Alfred W. West, P.E.

   Director, National Waste Treatment Center
(formerly Waste Treatment Branch, National Field
     Investigations Center - Cincinnati)
                   MAY  1974
             (Revised Nov.,1975)
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY

      OFFICE OF WATER PROGRAM OPERATIONS

-------
                          FOREWORD
    The National  Waste  Treatment  Center  (Cincinnati)  is
developing  a  series  of  pamphlets  describing Operational
Control Procedures for the Activated Sludge  Process.   This
series,  describing the "NWTC Procedures", will include Part
I OBSERVATIONS, Part II CONTROL TESTS, Part III  CALCULATION
PROCEDURES,  Part  IV SLUDGE QUALITY, Part V PROCESS CONTROL
and an APPENDIX.  Each of these  individual  parts  will  be
released for distribution as soon as it is completed, though
not  necessarily in numerical order.  The original five-part
series raay then be expanded to include  case  histories  and
refined process evaluation and control techniques.

    This  pamphlet  has  been  developed  as a reference for
Activated Sludge Plant Control lectures I have presented  at
training  sessions, symposia, and workshops.  It is based on
my  personal  conclusions  reached   while   directing   the
operation  of  dozens  of different activated sludge plants.
This  pamphlet  is  not   necessarily   an   expression   of
Environmental Protection Agency policy or requirements.

    Parts  I  and  II  were  originally  printed as separate
pamphlets dated April 1973.  The May 1974 printing  combines
the two Parts which includes some revision concerning use of
the centrifuge and dilution settlometer tests.

    The  mention  of  trade  names or commercial products in
this pamphlet is for  illustrative  purposes  and  does  not
constitute  endorsement  or  recommendation  for  use by the
Environmental Protection Agency.
                             Alfred W. West

-------
                       PART I



                 OBSERVATIONS




                   TABLE OF CONTENTS


                                              PAGE NO.

OBJECTIVES 	  1


INTRODUCTION  	  1


AERATION TANKS  	  1

    Turbulence 	  1
    Surface  Foam and Scum 	  3
    Sludge Color and Odor 	  6


FINAL CLARIFIERS 	  6

    Final Effluent Appearance 	  6
    Final Clarifier Surface Appearance 	  7

-------
                        OBJECTIVES

     Aeration tanks and final clarifiers are studied  percep-
tively for informative physical  characteristics   that   help
identify  sludge  quality  and  process  status.    They   are
scrutinized for clues that  indicate  the  kind  of  control
adjustments  needed  to  achieve  optimum plant performance.
The  inferences  of  such  physical  findings  are used  to
supplement  the results of other more specific  control tests
that dictate the direction and magnitude  of  the  essential
control adjustments.
                       INTRODUCTION

     Much  can be learned from simple but perceptive  sensory
observation of process features such as the type,  color,  and
extent of foam on the aeration tank surface and  the presence
or lack of scums and rising  floe  particles  in  the  final
clarifiers.   From  such  observations,  a  skilled operator
usually can determine the basic phase his process  is  moving
towards  or is locked into.  Such observations will make  him
aware of more generalized long-term requirements.  They will
help him reach proper conclusions from the results of  other
more  specific  control  tests  that  are  used  to calculate
process demands and to determine  the  type  and  extent   of
control adjustments that are actually needed.

     The entire series of physical observations  described in
this  section  should  be made each time the routine  control
tests are performed.  The appearance of the  final effluent
and  the  aeration  and  clarifier  tank  contents should be
examined at least once  during  each  operator's  eight-hour
shift.


                     AERATION TANKS

                        TURBULENCE
     The  operator  should  observe the entire aeration tank
surface for turbulence.  Though some of his conclusions will
be subjective and based on past experience,  the  extent  of
surface  turbulence will indicate whether or not all  sewage,
return  sludge,  and  mixed  liquor  are  thoroughly    mixed
throughout  the  entire  aeration  tank.  Observable  surface

-------

COMPRESSED AIR - SPIRAL FLOW
     Showing Diffuser Socks
COMPRESSED AIR -  CROSS ROLL
     Showing Diffuser Socks
COMPRESSED AIR - SPIRAL FLOW
             In Use
                                                                        >• .r==^a~j=~-^.~p|



                                                 ~~*~~
 COMPRESSED AIR -  CROSS ROLL
             In Use

-------
characteristics  will  imply  whether  or  not dead spots or
insufficiently  mixed  core  areas  may  exist  within   the
aeration  tanks.  The operator should maintain, increase, or
decrease air discharge rates according to the conclusions he
reaches from the  results  of  such  observations  and  from
supplementary dissolved oxygen determinations.

     He  should  reproportion  air  flow  through headers or
individual subheaders to correct any dead spots, unequal air
distribution, or  inadequately  tapered  aeration  intensity
that may have been observed.

     If   serious   mixing   deficiencies   prevail  despite
corrective air distribution adjustments, he  should  attempt
to   determine   which   structural,  mechanical  or  design
deficiencies may be responsible for  the  difficulties.   If
normal  air  balancing  procedures  fail  to correct evident
defects, he should be prepared to recommend the  maintenance
or modification procedure that may be necessary to eliminate
the problems.

     In  many  cases, aeration deficiencies can be corrected
by  routine  diffuser  cleaning  or  by  replacing  existing
diffusers  with  more  effective maintenance free units.  In
some cases, major mechanical alterations may be required  to
relocate  and  increase  the  number of diffusers to mix and
aerate  the  tank  contents  thoroughly.   Overall   process
performance  has  been  improved at some plants by replacing
the single run of diffusers that  extended  along  one  side
wall  with  multiple  parallel  runs  of diffusers extending
either longitudinally or across the tank bottom.


                   SURFACE FOAM AND SCUM
     The type of foam or scum, if any, accumulated over  the
aeration  tank surface, and to a lesser extent, the color of
the mixed liquor sludge reveal process status  and  indicate
generalized long-term sludge wasting requirements.

Fresh Crisp White Foam

     Only  a modest accumulation of white, or at least light
colored, crisp appearing foam is usually evident on aeration
tank surfaces when an excellent final effluent  is  produced
by a properly balanced activated sludge process.  Under such
circumstances  the  operator  should continue his successful

-------
                                                        A
                                              •',,•••-
BILLOWY WHITE FOAM
    (Young Sludge)
THICK DARK TANK FOAM
       (Old Sludge)
                          DARK FOAM, BAD ODOR
                               (Septic Sludge)

-------
control policies until the physical characteristics  or  the
results of other control tests diverge from optimum.

Excessive Billowing White Foam

     If  the  aeration tanks are covered by thick voluminous
billows of white sudsy  foam,  the  operator  can  be  quite
certain  that  the  sludge  is too young and that sludge age
should be increased by reducing the sludge wasting rate.

     Sludge age, which is controlled by the  sludge  wasting
rate,  indicates  the  approximate  number  of days that the
activated  sludge  remains  in  the  system   before   being
discarded.   Prolonged  excessive sludge wasting will reduce
sludge age by increasing the proportionate amount  of  newly
developed  floe  in  the  system.   Conversely,  unduly  low
wasting rates will increase the number of days the sludge is
retained in the system and will increase  the  proportionate
amount of older sludge.

     Sludge wasting rates should be decreased only gradually
on  a day-to-day basis to correct the process imbalance that
was revealed by the excessive white foam.  Best results  are
usually  obtained by reducing the wasting rate approximately
twenty percent on each successive day until all observations
and  tests  reveal  an  improving  trend.    When   positive
improvement  is  noted,  the  operator  should  maintain the
lowered wasting rate for about three  more  days  while  the
improving  trends  are  confirmed.   He  should,  of course,
continue to plot and review  process  control  and  response
trends which will alert him to subsequent control adjustment
policy  that  may  become necessary.  As implied previously,
wasting  usually  should  not  be  discontinued  completely-
Exceptionally  low sludge settling rates and classic bulking
that can accompany this  type  of  foam  generation  may  be
corrected by reducing air discharge rates to lower the mixed
liquor dissolved oxygen concentration to the 0.5 to 1.0 mg/1
range.

Thick, Scummy, Dark Tan Foam

     At  the  other extreme, the operator may observe a more
dense and somewhat greasy scummy layer of deep tan to  brown
foam covering the entire aeration tank surface.  Such a foam
almost  always  indicates  that  the  sludge  is too old and
possibly over oxidized.  The obvious answer is  to  increase
sludge  wasting  rates.  Here again, the sludge wasting rate
should  usually  be  increased  modestly,  possibly   twenty
percent per day, on a day-to-day basis while observing trend

-------
lines  to  determine the maximum wasting rate that should be
maintained until  the  difficulties  are  overcome  and  the
process is restored to proper balance.


                   SLUDGE COLOR AND ODOR

     At  times  a  poor quality extremely dark brown-colored
sludge, sometimes almost black, releasing  hydrogen  sulfide
odors,  may  be observed in the aeration tanks.  It does not
take  much  experience  to  recognize  this  problem.   Most
operators  would  logically  increase  air  discharge  rates
immediately to provide 2-3 mg/1  DO  throughout  the  tank
contents.   In  severe  cases,  when  such  color  and  odor
persists,  despite  proper  control  measures,  they  should
question  the  adequacy of the aeration devices installed at
their plants.  Under such circumstances, the operator should
clean  or  replace  the  existing  diffusers  and  recommend
appropriate  mechanical  modifications  as  discussed in the
section on turbulence and mixing.
     The operator should also observe the final effluent and
the clarifier water surface critically for additional  clues
to indicate process phase and balance, and to supplement the
results  of  other control tests to determine sludge wasting
and air control requirements.


                 FINAL EFFLUENT APPEARANCE

     If the final effluent appears clear and attractive,  or
is  improving  day  by  day,  obviously  the operator should
continue  his  present  control  policy   if   all   control
measurements are in the proper range.

     Conversely, if it appears turbid or contains noticeable
solids,  he  should  modify his operational control policies
and procedures.  Though observation of poor effluent quality
alone will not  reveal  specific  control  requirements,  it
signals  the  need  for  judicious  review  of  control  and
response  trends  and  for   revised   operating   policies.
Specific control adjustments will be dictated by the results
of other control tests.

-------
            FINAL CLARIFIER SURFACE APPEARANCE

Sludge Bulking

     Operators  who  have  experienced  true  classic sludge
bulking find it all too easy to remember and identify.  Such
conditions are evidenced by a homogeneous  appearing  sludge
blanket  that  extends  throughout the entire clarifier, and
can be observed at the water surface while the mixed  liquor
solids  pour  out  over the final effluent weirs.  Though at
times induced by shock loadings, and aided  and  abetted  by
ineffective aeration devices, classic sludge bulking usually
is  caused  by  improper  operational control rather than by
inadequate plant capacity.  Furthermore,  impending  bulking
usually  can  be recognized from the trend charts  (Appendix)
and by judicious use of  the  sludge  depth  blanket  finder
(Part II Control Tests) many days before it actually occurs.

     This  type  of  bulking,  which  is  practically always
associated with young sludge, usually can be  eliminated  by
reducing sludge wasting rates, increasing return sludge flow
rates,  and reducing air discharge down to the minimum rates
that will maintain aerobic conditions in the aeration tanks.
Where appropriate flexibility has been designed into plants,
bulking has also been eliminated  by  changing  the  process
mode from conventional plug flow to step flow by introducing
the  primary  effluent  into  the second or third bay of the
aeration tank.

     In some  cases  where  such  control  adjustments  have
failed,  emergency  chemical  treatment  has  cured  classic
sludge bulking.  Some operators  have  successfully  applied
polymers  and  ferric  chloride  or alum to the mixed liquor
entering the final clarifier  without  destroying  desirable
sludge  characteristics.   Laboratory  jar  tests  should be
performed to indicate the type of chemical, the dosage rate,
and the pH range  that  will  be  most  effective.   If  the
chemical  additives  do not cure actual bulking in the final
clarifiers, even  though  the  sludge  samples  settled  and
compacted  in the laboratory jar tests, the chemicals should
be added at different points between the aeration tanks  and
the final clarifiers until best results are obtained.  It is
usually  best  to apply chemicals to the wet well preceding,
or the pipe line leading to, the final clarifier.

Sludge Solids Washout

     Excessive sludge washout over the final effluent weirs,
when the upper surface of the sludge blanket  is  more  than

-------
CLASSIC SLUDGE BULKING
     RISING CLUMPS
                                                    SOLIDS WASH OUT
                                                      FLOATING ASH

-------
three feet below the clarifier water surface and when sludge
settles  properly  in the laboratory, should not be confused
with classic sludge bulking.  At times this type  of  severe
effluent degradation has been observed while the settlometer
test  revealed  excellent  sludge quality.  In many multiple
clarifier plants this  has  been  caused  by  unequal  mixed
liquor  flow into, or by unequal return sludge removal from,
individual  final  clarifiers.   Under  such  circumstances,
where  excessive velocity currents are induced, every effort
should be  made  to  balance  flows  into  and  out  of  the
clarifiers.

     Solids  washout  has  also  been  caused  by  hydraulic
overloading, by improper clarifier inlet port  arrangements,
and by faulty final effluent weir locations.  Differing from
classic  sludge  bulking,  this  type  of  problem  is  more
frequently caused by hydraulic  overloads  or  inappropriate
final  clarifier  design  rather than by operational control
procedures.

Clumping and Ashing

     At times, large masses of sludge, possibly as large  as
one foot in diameter, may be seen rising, then bursting, and
finally  spreading  over  the  clarifier  surface.  This has
sometimes been called "clumping".  At other  times,  smaller
sludge  particles,  usually deep brown to gray in color, may
rise and then spread over the tank surface.  Some  operators
call this "ashing".  This problem usually occurs when sludge
age  has  been  permitted  to  increase  beyond  the optimum
equilibrium requirement of the  process  cycle  and  it  can
usually  be  eliminated  by increasing sludge wasting rates.
Reducing air discharge rates to the minimum levels that will
still maintain aerobic conditions in the aeration tanks  has
also been helpful.

Straggler Floe

     At times, small, almost transparent, very light fluffy,
buoyant  sludge particles (one-eighth to one-quarter inch in
diameter) may be observed rising to  the  clarifier  surface
near   the   outlet   weirs.    This  condition  is  usually
intensified in a shallow clarifier  and  may  be  especially
noticeable at high return sludge flow rates.  When this type
of  straggler  floe  is observed while the final effluent is
otherwise  exceptionally  clear,  and  particularly  if   it
prevailed even during relatively low surface overflow rates,
it  implies  that  sludge age should be increased moderately
towards optimum.   Since this type of straggler floe  usually

-------
occurs  at relatively low mixed liquor solids concentrations
and is usually intensified during the early  morning  hours,
it  is  believed that these particles are fresh, low density
portions of new sludge that have been built up  over  night.
Straggler  floe  formation  can  be  minimized,  by reducing
sludge wasting rates moderately to increase sludge age while
return sludge and air discharge rates are controlled to meet
process demands  that  are  calculated  from  other  control
tests.

Pin Floe

     At  other  times,  very small compact pin floe, usually
less than one-thirty-second of an inch in diameter,  may  be
observed   suspended   throughout  moderately  turbid  final
clarifier tank contents.   This is a strong  indication  that
sludge  age  has  been  increased unduly, and the sludge has
become  overoxidized.   This  will  be  confirmed   by   the
settlometer   test   if  rapidly  settling  discrete  sludge
particles  appear  granular  rather  than  flocculant,   and
accumulate  rather  than compact while forming a settlometer
sludge blanket.  In essence, granular sludge particles  were
falling  through  a turbid liquor rather than compacting and
squeezing out a clear final effluent.

     When  these   final   clarifier   characteristics   are
confirmed  by  the settlometer test, the sludge wasting rate
should be increased while return sludge flow is adjusted  to
meet other control test demands.
                            10

-------
                       PART II







                 CONTROL  TESTS









                   TABLE OF CONTENTS





                                               PAGE NO,



OBJECTIVES 	 13





INTRODUCTION 	 13





METER READINGS 	 14





DEPTH OF SLUDGE BLANKET 	 16





SAMPLE COLLECTION  	 19





SETTLOMETER TESTS  	 20





CENTRIFUGE TESTS 	 24





EFFLUENT TURBIDITY TESTS 	 26





DISSOLVED OXYGEN TESTS 	 27
                          11

-------
                        OBJECTIVES
     Control  tests, that can be run as frequently as needed
throughout  each  24-hour  cycle,  reveal  sludge   quality,
process status, and final effluent quality.

     Results   of  the  settlometer,  centrifuge  and  final
clarifier sludge blanket level tests are used  to  calculate
solids  distribution  ratios  between the aeration tanks and
the final clarifiers, sludge detention  time  in  the  final
clarifiers    and    other   factors   influencing   process
performance.

     The  coordinated  results  of  the  full  test  series,
including flow records, turbidity, and dissolved oxygen test
data,  are  ultimately  used  to determine the return sludge
flow, excess sludge wasting and air discharge  rates  needed
to maintain or restore excellent final effluent quality.



                       INTRODUCTION

     Practically  all  information  needed  to define sludge
quality  and  process  status  and  to   calculate   control
adjustment  requirements  can be determined from the results
of a few relatively simple  tests.   The  entire  series  of
settlometer,  centrifuge,  sludge  blanket  depth,  effluent
turbidity and dissolved oxygen tests  can  be  completed  in
about   ninety   minutes  and  can,  therefore,  be  run  as
frequently as needed throughout  each  24-hour  cycle.   The
complete  test  series  should  be  run  at least once every
eight-hour operating shift.   The  sludge  blanket  and  the
fifteen   minute   centrifuge   tests  should  be  run  more
frequently whenever rapidly changing process characteristics
demand more critical scrutiny and control.   Though  simple,
informative,  and  too frequently neglected, these tests are
neither new nor difficult.  They were, in fact, proposed  by
E.  B.  Mallory  more  than  thirty  years  ago.  Though the
testing  techniques  and  some  of   the   data   processing
methodology   includes   that   proposed   by  Mallory,  the
procedures  and   calculations   for   determining   control
adjustment  requirements,  as  discussed in these pamphlets,
were developed by me.

     These discussions include only those control tests that
are used directly to identify  process  performance  and  to
                            13

-------
dictate   process   control  adjustments.    Other  important
monitoring type tests, such  as  BOD,  COD,  etc.,  are  not
included in these discussions.


                     METER READINGS

     Each  control  test series should be  started by reading
plant  meters  to  record  flow  data  that  are  needed  to
determine process requirements.

     Flow  records  specifically  related   to control of the
activated sludge process include:

     AERATION TANKS

        Total influent waste water flow to aeration tanks
        Return sludge flow to aeration tanks
        Total air to aeration tanks
     FINAL CLARIFIERS

        Mixed liquor flow to clarifiers
        Sludge removed from clarifiers
     EXCESS SLUDGE TO WASTE

        Mixed liquor wasted
        Return sludge wasted

     The extent of additional flow data needed  to  evaluate
and  control total plant performance will vary from plant to
plant.  Other waste streams that  should  also  be  measured
could include:

        Raw sewage flow
        Plant drainage recycled to primaries
        Primary sludge flow
        Sludge thickener flows
        Sludge filtrate flows
        Digester supernatant flow
        Sludge removed from plant
        Plant drainage recycled to aeration tanks
        Final effluent reuse
        Final effluent flow
                            14

-------
    - The following discussion is limited specifically to the
activated  sludge  portion  of  the  treatment  plant.   For
multiple tank plants, having three aeration tanks and  three
final  clarifiers,  for  example,  the  operator should also
routinely maintain equal hydraulic loading to  each  of  the
parallel operating units.

     The  following  flow  rates should be determined during
each test period and the 24-hour  totalized  value  of  each
should be recorded every day.

SEWAGE FLOW INTO EACH AERATION TANK

     Frequently  overall  treatment is impeded when aeration
tank loadings cannot  be,  or  are  not,  balanced  properly
between  the  parallel aeration tanks.  The better treatment
provided by an underloaded tank  unit  will  not  compensate
fully  for  the  poorer treatment provided by the overloaded
unit.

RETURN SLUDGE FLOW INTO EACH AERATION TANK

     Maldistribution of return sludge flow, especially  when
coupled  with  unequal  sewage flow loading between parallel
aeration  tanks,  can  further  distort  the   proportionate
purification   pressures  (mixed  liquor  concentration  and
detention times) and reduce treatment capability.

AIR DISCHARGE TO EACH AERATION TANK

     Here, again, unequal distribution as well as inadequate
or excessive total air flow can degrade sludge  quality  and
purification.    The   basic   indicating,   recording,  and
totalizing meters should be used to measure and control  air
flow to each aeration tank.  Simple indicating meters should
be  observed  to  assure proper air distribution to the main
air headers feeding each bay or  compartment  of  individual
aeration tanks.

MIXED LIQUOR FLOW INTO EACH FINAL CLARIFIER

     The   influent   flow   to  each  clarifier  should  be
determined during each  test  period  so  that  the  surface
overflow  rates  and  the solids loadings can be distributed
properly to each clarifier.  This  is  especially  important
during  troublesome  times  when rising sludge blankets warn
that classic sludge bulking may be imminent.
                            15

-------
     If the clarifier flows are  not  balanced  properly  at
such  times,  mixed liquor sludge can be forced out over the
final weirs of the overloaded clarifier,  while  the  sludge
blankets  in  the  other clarifiers may remain low enough to
produce a clear effluent.   Unfortunately,  this  may  occur
when  proper flow distribution could otherwise have held the
sludge blankets  safely  below  the  water  surface  of  all
clarifiers.

SLUDGE REMOVED FROM EACH CLARIFIER

     These meters, one for each tank, should also be read at
each  test period and the totalized value should be recorded
each day.  Here again, the need to  balance  sludge  removal
from  all clarifiers to maintain proper sludge blanket level
control is obvious.

EXCESS SLUDGE FLOW TO WASTE

     This meter, or meters, should be  read  at  every  test
period and whenever the wasting rate is changed.

     Procedures  to  use  flow  data  and other control test
results to determine return sludge, waste sludge, and  other
process  requirements  will  be  discussed in other parts of
this pamphlet series.


                DEPTH  OF SLUDGE BLANKET

     After checking the  meters,  an  operator  following  a
logical  test  schedule  should  move  on to determine final
clarifier characteristics.  He should determine the depth of
the sludge blanket that has accumulated within the clarifier
and observe conditions at and near the water surface.

     Various types of sludge blanket depth finders are used.
The type described in the Appendix can be constructed simply
and used conveniently; and when handled properly, it becomes
a valuable, reliable operational control tool.  At least two
sludge  blanket  finders  should  be  provided   to   assure
continuity  of  test  results,  especially when one is being
repaired.  One should be  long  enough  to  reach  from  the
bridge  to  the  tank  bottom.  The other shorter one should
only be long enough to extend about half way down  into  the
tank.

     Two  other  types  of  blanket  finders  are wands with
photo-electric cell actuated buzzers and a series  of  small
                            16

-------
SLUDGE BLANKET FINDER
LIGHT AND SIGHT GLASS
                                                    OPERATOR STARTING
                                                  DEPTH OF BLANKET TEST

-------
airlift  pumps  extending  down to different measured depths
within the final clarifier.  The  operator  should  use  the
type  he finds most convenient, but it is suggested that the
reliable pipe and sight glass type be provided, at least  as
a back-up instrument.

     It  takes  a  little  practice for an operator to use a
blanket finder, or, more exactly, to know what he is looking
for, but after the first few diligent attempts  he  will  be
surprised at how accurately and easily blanket depths can be
determined.

     A   cross  section  of  most  clarifiers  containing  a
reasonably  good  sludge  solids  distribution  balance  may
reveal  a zone of discrete straggler floe particles settling
down to form the blanket.  Somewhat  farther  than  half-way
down  into  the tank, there will usually be a distinct plane
of  demarcation  between  the  individual  settling   sludge
particles  and  the  relatively thin, but quite homogeneous,
upper surface of the accumulated sludge blanket.   Then  the
concentration  of  this sludge blanket will usually increase
in density down to the zone of  maximum  compaction  at  the
very bottom of the tank.

     Here  are two precautions - which will only be resolved
by practice.  Do not  stop  the  downward  movement  of  the
blanket finder when the individual discrete sludge particles
are  observed.   Secondly,  do  not force the blanket finder
down to the point where the denser sludge within the blanket
actually obscures the  light.   Instead,  move  the  blanket
finder down at a rather rapid uniform rate through the clear
liquor,  then  continue  down  through  the  zone containing
individual floe particles, and finally stop when  the  upper
surface of the definite homogeneous sludge mass is observed.
Take  your reading at this point; you have reached the upper
surface of the sludge blanket.

     The blanket reading station  should  be  located  at  a
point  where  the  single  measurement  will approximate the
average depth of the entire sludge blanket.   A  station  on
the  final  clarifier  bridge,  about  one-third of the tank
radius in from the outer tank  wall,  will  usually  satisfy
this  requirement.  The selected station should be marked so
that  blanket  depths  are  always  measured  at  the   same
location.
                            18

-------
                    SAMPLE COLLECTION

     Samples for the control tests and other laboratory work
must be collected on time, from appropriate  locations,  and
according to approved procedures; and they certainly must be
representative.   These  elementary  principles  can  not be
violated without cost.

CENTRIFUGE TEST SAMPLES

     After observing the clarifiers, return  sludge  samples
should  be  collected for the centrifuge test.   Selection of
the sampling  station  for  collecting  samples  that  truly
represent  the actual quality of the entire return and waste
sludge flow is most important.  It is best  to   collect  the
sample  from  the  point  where  the thoroughly mixed return
sludge from all clarifiers enters the  aeration  tanks.   If
such  location  is  inaccessible, the sample should be taken
from a tap off the return sludge pump discharge header.  The
sample pipe  should  obviously  be  flushed  out  thoroughly
before  each  sample  is  collected.   Since mixing  may be
inadequate, sampling from deep wet wells should  be  avoided
if at all possible.

     In  addition  to  the  sample collected for basic plant
control,  individual  return  sludge   samples    should   be
collected  from  each final clarifier to check  or to balance
multi-tank performance.

     At times, samples should be collected from each of  the
individual  sludge  draw-off  tubes in each final clarifier.
This series of samples need be collected only as  frequently
as  required  to  assure  uniform sludge withdrawal from the
entire clarifier floor area.  Ordinarily, such   "trim  spin"
samples are collected about once each week.

     The  samples  collected  for  the  settlometer test, as
described in a following  section,  will  also   be  used  to
determine  the centrifuged concentration of the mixed liquor
solids.

TURBIDITY TEST SAMPLES

     Special samples should also be collected from the final
clarifier to determine the turbidity of the  treated  waste.
These samples for turbidity should be collected deliberately
from  the clearest area of the final clarifier  water surface
                            19

-------
that contains the least surface sludge or scum that  may  be
present.   When collected in this manner, these samples will
indicate  specific  process  performance,   undistorted   by
clarifier   or   other   equipment  defects  that  may  need
correction.  Other 24-hour composite samples  collected  for
plant  monitoring  (BOD,   COD,   TSS,   etc.)  will be used to
determine net process performance.

SETTLOMETER TEST SAMPLES

     The mixed liquor sample for the settlometer test should
be  collected  last  of  all.    This  sample,   which  should
represent  the  average  quality of all mixed liquor flowing
out of all aeration tanks, will also be  used  to  determine
solids  concentration  both  by  centrifuge  and  by weight.
Preferably, this sample should  be collected from the  common
discharge  flume that contains  all mixed liquor flowing from
the outlet of all active   aeration  tanks.    If  the  common
discharge  header  is  inaccessible,   equal volumes of mixed
liquor should be collected  from  the  outlet  end  of  each
aeration  tank  and  composited into a single representative
sample for the settleability and solids concentration tests.

     The necessity for collecting mixed  liquor  samples  in
wide-mouthed   containers,   rushing   the   samples  to  the
laboratory, and starting  the settlometer  test  immediately,
can  not  be over emphasized.   After collection, the samples
should be  subjected  to   the  absolute  minimum  amount  of
agitation  and  aeration.  Improper sample  handling, such as
violent shaking or splashing, or unwarranted  delay  between
the  time  that  the  sample is collected and the time it is
poured into  the  settlometer,   can  alter   sludge  settling
characteristics   and   induce   erroneous  settlometer  test
results.

                   SETTLOMETER TESTS

     Preferably, mixed  liquor   sludge  settleability  tests
should be determined in a clear glass cylinder with a larger
diameter  and  a  lesser   depth  than  the  standard 1,000 cc
graduated cylinder that is frequently used  for this test.  A
glass cylinder shaped  similar   to  the  standard  two-liter
beaker,  but with better  graduations and without the rounded
bottom edge, would  be  satisfactory.   Many  operators  now
prefer  the  five  inch  diameter, six inch graduated depth,
two-liter Mallory settlometer that is  graduated  in  tenths
and  hundredths  of  the   settlometer  volume.  Satisfactory
settlometers can also be  fabricated from five inch  diameter
clear plexiglass cylinders.
                            20

-------
•MM
         TEST SET-UP
5 MINUTE READING
      1 HOUR APPEARANCE                               1 HOUR READING
                              SETTLOMETER TEST

-------
     The  mixed  liquor  sludge sample should be stirred and
then poured into the settlometer carefully and  rapidly  and
with  the  least  possible  amount of additional aeration or
disturbance.   The  settlometer  contents  should  then   be
stirred  gently to assure thorough mixing; then all swirling
should be dampened immediately with a wide paddle  (four inch
sheet aluminum works well) before the timer is started.

     The volume  of  the  settlometer  occupied  by  settled
sludge  should  be  read  and  recorded at every five-minute
interval for the first thirty minutes and  then  every  ten-
minute  interval  for  the  second thirty minutes of the one
hour settlometer test.  This is the standard test duration.

     When sludge settles extremely  slow,  or  when  bulking
actually  occurs,  the  settlometer  test  period  should be
extended beyond the  one  hour  reading.    By  returning  to
observe the settled sludge volume after 2, 3, 4, etc.  hours,
the  operator  will  be  able  to  determine ultimate sludge
compaction for a more thorough process evaluation.

     Running  simultaneous  multiple  settlometer  tests  on
diluted  specimens  of slowly settling mixed liquor can help
the operator decide whether  to  increase  or  decrease  the
sludge wasting rate.  At least two dilutions should be made.
One  settlometer  should contain undiluted mixed liquor, one
should contain about 75% mixed liquor diluted with 25% final
effluent, and a third settlometer should contain half  mixed
liquor and half final effluent.

     Though this expanded multiple dilution test need be run
only  once per day while the slow settling problem persists,
it should follow the previously stated standard  procedures.
If  confirmed  by other control test results, these multiple
settlometer test results can reveal  the  following  control
adjustment needs.

     If  the  diluted  samples settle much more rapidly than
the  undiluted  sample  (especially  during  the  first   10
minutes),  the system contains too many fair to good quality
mixed liquor solids and sludge wasting should most  probably
be increased.

     If the diluted samples settle at the same rate, or only
slightly  faster  than  the  undiluted  mixed  liquor sample
(especially during the first 10 minutes), the  mixed  liquor
sludge  is  truly bulky.  This has been caused frequently by
excessively heavy wasting which reduced sludge age way below
the optimum.  Sludge wasting should usually be reduced  (but
                            22

-------
not  down to zero) modestly, day by day, to develop a sludge
that can concentrate more.

     Operators who set up a test cylinder,  walk  away,  and
then  return  for  only  one single observation after thirty
minutes, miss most of the information that actually  defines
sludge  quality.   A single thirty-minute test, to determine
SVI, is somewhat like a five-day BOD,  in  that  it  reveals
only  one  point  in  a progressive reaction and it will not
help an evaluator who is really interested in reaction rates
and the full impact of ultimate demands.

     The first five-minute reading is one of  the  two  most
important  observations  for  this  test.  During this first
five minutes  the  conscientious  operator  will  critically
observe  how  the sludge particles agglomerate while forming
the blanket.  He will see whether the sludge compacts slowly
and uniformly while squeezing clear liquid from  the  sludge
mass  or whether tightly knotted sludge particles are simply
falling down  through  a  turbid  effluent.   He  will  also
observe  how  much  and what type of straggler floe, if any,
remains in the supernatant  liquor  above  the  main  sludge
mass.

     The importance of conscientious, perceptive observation
during  the  first  five minutes can not be over emphasized.
During these first five minutes the  operator  will  acquire
additional  insight  into  sludge character and quality, and
will be in a much  better  position  to  evaluate  what  the
settlometer test reveals.

     The  sixty-minute  reading is the second most important
observation.  It provides a check on final clarifier  sludge
blanket  characteristics  and  is  used  to  compute process
equilibrium  indices  and  operational  control   adjustment
requirements.

     After  the tests are completed, the settlometers should
remain undisturbed for at least four  hours.   The  time  at
which  previously  compacted sludge starts to swell and rise
to the surface is  another  important  indicator  of  sludge
quality-  Settled sludge should not remain down forever, any
more than it should gasify and pop to the surface during the
sixty-minute   test   cycle.    Well-oxidized   sludge  will
frequently begin to swell somewhat after ninety minutes  and
will  usually  float to the surface within two to four hours
after the test was started.
                            23

-------
     A portion of the sample collected for  the  settlometer
test should be saved for solids determinations.


                    CENTRIFUGE TESTS

     The  centrifuge  permits  rapid  determination of mixed
liquor and return sludge solids concentrations for immediate
use in calculating  solids  distribution  ratios,   effective
return   sludge  percentages,  solids   concentration  rates,
clarifier sludge  detention  times,   and  a  host   of  other
process  relationships used to determine operational control
demands.

     The use of 12.5 ml API (American   Petroleum  Institute)
centrifuge  tubes in a clinical centrifuge, with a six place
horizontal head, revolving at full speed (position 7 on  the
International   No.    428,   for  example)   has been  found
convenient and appropriate for sewage  plant control testing.
The mixed liquor  and  return  sludge   specimens  should  be
centrifuged  for  a   standardized fifteen minute interval to
assure consistent compaction and to  avoid discrepancies that
can be introduced by slight variations in testing  time  when
shorter  intervals (say from one to  three minutes)  are used.
Shorter time intervals may be  used   for  "trim  spins"  and
other  special  tests when many specimens are centrifuged to
determine the solids balance in multiple aeration   tanks  or
clarifiers.

     The  centrifuge is an exceedingly useful and  convenient
tool for searching out and correcting  unbalanced  sewage  or
return  sludge  flow  distribution  as well as unequal mixed
liquor and return sludge solids concentrations  in  multiple
tank plants.  It has also been used  effectively to determine
return  sludge  percentages  in the  all too many cases where
flow meters have been  missing  or  were  in  error.   Mixed
liquor  and  return  sludge concentration data frequently are
plugged into the mixing formulas, described  in  Part  IIIA.
It is then possible  to determine either the primary effluent
flow  rate  into the aeration tanks  or the sludge  withdrawal
rate from the final  clarifiers when  either of the  meters for
these two locations  is missing or inoperative.

     Some operators  question the use of the  centrifuge  for
sludge   concentration   determination  because  such  tests
results can not always be correlated with  suspended  solids
determinations  by the laboratory balance.  The variation in
the ratio of mixed  liquor  suspended  solids  concentration
determined  by  the  laboratory balance to that determined by
                            24

-------
PROPER SAMPLE HANDLING
   FOR TURBIDITY TEST
  CENTRIFUGED
SLUDGE SAMPLES
                      TURBIDITY READING

-------
the centrifuge is affected by sludge age and  oxidation  and
is,  therefore,  one  of the virtues of the centrifuge test;
not a defect.   Furthermore,  the  centrifuge  test  result,
because  it  is  influenced  by the specific gravity and the
surface area  of  the  sludge  mass,  provides  a  realistic
measure of effective sludge concentration.


               EFFLUENT TURBIDITY  TESTS

     Two  turbidity  determinations  should  be  made on the
sample collected from the final clarifier.   A photo-electric
activated readout type turbidimeter with  results  expressed
in Jackson Turbidity Units (JTU)  or Formazin Turbidity Units
(FTU)  is  recommended.    The  turbidity  of excellent final
effluents usually ranges between 1.0  and  3.0  JTU.    Final
effluent  turbidities greater than 3.0, and especially those
exceeding 10.0 JTU,  indicate  that  the  full  purification
capability  of  the  activated  sludge  process has not been
achieved.

     The  first  turbidity  determination  should  be   made
shortly after the settlometer and centrifuge tests have been
started.   The  sample should be stirred (only for the first
test) before it is poured into the turbidimeter  test  vial.
The  vial  exterior  should  always  be  wiped clean and dry
before insertion into  the  turbidimeter.   This  precaution
will protect the internal components and enhance accuracy.

     The  final effluent sample should then be put aside for
a one-hour settling period to permit gravity  separation  of
extraneous floatable scums and settleable solids that may be
attributed   to   flow   overloads  or  inappropriate  final
clarifier features.  At the end of this time  interval,  the
turbidity  of  the  subnatant  liquor  in  the settled final
effluent sample should be determined.

     Special additional precautions should be observed while
pouring the "settled" specimens into the  turbidimeter  test
vial.   The  specimen  container  should be carefully lifted
from the work bench and any accumulated surface scum  should
be  poured to waste before the settled liquid (free from any
sludge that may have settled to the bottom of the container)
is poured into the test vial.  The pouring operation must be
gradual and continuous to avoid creating air bubbles and  to
eliminate   surface  scums  or  settled  solids  that  might
otherwise  cause  erroneous  interpretation  of   the   test
results.
                            26

-------
            When   performed  properly,   the  turbidity  test  will
       reflect process performance.   If  the final effluent contains
       excessive suspended solids,  for example,  differences in  the
       turbidity  test results on settled versus unsettled effluent
       specimens will indicate whether the problem was  created  by
       improper   process   control,    hydraulic  overloads  or  by
       defective final clarifiers.   In other words,  if  the  final
       clarifiers   lack   scum   baffles   and  skimmers  or  have
       inappropriately placed final  effluent launders,  or  if  the
       tank  geometry  induces  unnecessary  velocity currents, the
       turbidity of the  settled  specimen  will  reveal  the  true
       effect  of control adjustments on sludge characteristics and
       process equilibrium.   Many times  the final effluent produced
       by  good  sludge  at   proper   process  equilibrium  contains
       unnecessarily   high    concentrations  of  solids  that  are
       needlessly forced out of the  clarifiers by inappropriate  or
       malfunctioning equipment.  The object of this turbidity test
       is  to  define  process  response  and  control requirements
       rather  than  to  document   built-in,   and   usually   not
       immediately correctable, plant defects.

            Turbidimeter   calibration   and   use   should  follow
       manufacturer's  instructions.    Where   multiple   turbidity
       standards  are supplied with  the equipment, the turbidimeter
       should be  calibrated  with  the  standard  closest  to  the
       anticipated effluent  turbidity.  If, for example, 1.0, 10.0,
       and 100.0 FTU standards were  provided, and the equipment had
       been  calibrated with the 100  FTU standard, but the effluent
       turbidity read out at less than 10 FTU; the meter should  be
       recalibrated with the 10 FTU  standard and reread.
                       DISSOLVED OXYGEN TESTS

            At  least once per day, and preferably once during each
       eight hour shift, dissolved oxygen concentrations should  be
       determined  at  the  inlet  and  at  the outlet ends of each
       "pass"  or  compartmented  area  of  the   aeration   tanks.
       Additional  dissolved  oxygen  determinations should be made
       more  frequently  at  "one"  or  "a  single"  aeration  tank
       sampling  station  to  reveal  dissolved  oxygen  variations
       throughout  each  24-hour  cycle.   These  additional  tests
       usually  are  run  once  every  four  hours  and  should  be
       scheduled to  include  the  intervals  when  influent  loads
       increase  in  the  early afternoon and decrease in the early
       morning hours.  A battery-operated  dissolved  oxygen  field
       probe  is  much  more  convenient  to  use and provides more
       accurate mixed liquor DO values  than  the  Winkler  Method.
S. GOVERNMENT PRINTING OFFICE: 1975/657-695/5351 Region No. 5-I I     27

-------