-------
11.
iii.
iv.
VI.
_MGD
MGD
Estimated fire flow demand?
Sum of i + ii =
What is estimated nominal minimum
daily storage on the distribution system? .,,.
gallons
What is estimated rate of flow from
distribution storage for the required fire
flow duration [iv x storage factor from
Table D-l, Appendix D] ? _MGD
Required capacity of arterial mains is
iii - v =
MGD
b.
Area
Served
vii. What is ratio of installed arterial
capacity to required capacity?
With respect to secondary feeder mains, size
*
according to area served 40 years after installation.
Use same method as A. 3 above, but apply to areas
served. UNKNOWN
Ratio
Estimated Required Installed Installed:
Population Capacity Capacity Required
E-3
-------
c. Length of installed mains and pipes of all
sizes? 77 miles
d. Number and miles of alternate or duplicate
mains to supply each area in case of a main
or pipe break? -No. , 6 7 miles
Number of mains or pipes having no duplicate
supply? -JSfo. - , IO miles
e. Are pressures recorded at hours of peak
demand where pressures are expected to be
lowest? Yes
f. Do records show pressures at least 20 psi
at critical points at hours of peak demand? Yes
If no, how many hours per year is pressure
less than 20 psi? O hours
g. What is the shortest life expectancy of any
• segment of the system? unsown years
h. What is expected life of material generally
used for mains? SO years
i. What is number of dead ends in system? \6
Are dead ends provided with protected
blow-off valves for flushing? V«s — P»re
Is a flushing procedure followed? Yes
j. Are mains looped to form a grid and avoid
dead ends? ~§ °* •J>Ys*em '**
k. Are all mains isolatable to small areas for
repair purposes without interrupting flow to
more than one block? ~Q °-F -sys¥ev~ is
1. What percentage of the system has the
following life expectancy? 10 to 34years
35 to 49years
50 to 100 years 9O
E-4
-------
m. For mains 3 inches and smaller, what is the number
of customers served? Do they fall within Table E-l?
Indicate in Table. C?lc
n. Is a proper disinfection, flushing, and bacteriological
testing procedure followed following repairs, alter-
ations, or installations? Such a procedure should
consist of: Yes--~^we ^ps'^s tvea+ed u \s
a• t:«ste<) av\d ?>Uov" UtRKS -
p. Is there a code prohibiting cross-connections
to lesser or unknown quality water or other
liquids? pVuvwbi.^ Codle
q. Is there an active program to inspect for and
eliminate cross-connections in the system? Qr>\y
nevt pluw^ing, i»\s^aMa*'>ows o*- pluv^ivyi, a\-te»-a-Viov\!Jf; '
How many cross-connections are found and
eliminated per year (average)? "72
r. Is a valve (including hydrants) maintenance
program practiced to ensure proper valve
operation and good condition? Yes
s. Is chlorine residual maintained throughout
distribution system? See paragraph f, ,
page D-5.
E-5
-------
TABLE E-l. MAXIMUM NUMBER OF CUSTOMERS
DESIRABLE ON SMALL MAINS
Pipe Length
Diameter of Main
(inches) (feet)
1" 50
100
150
1-1/2 100
200
H
o> 30°
2" 100
250
500
3" 200
500
1,000
Desirable Number of Actual Number of
Customers Customers
Pressure at Pressure at
Start of Main (psi) Start of Main (psi)
26 30 40 50 26 30 40 50
1 2 4
, o N0(v) 6
i &
i
1.3 10 15
1 5 8 |Vj O fO C.
1 3 5
2 10 15 15
1 4 10 10
266
7 15 2570 Feet O-
1 2- cw.S'tow\e \r-s ,
3 10
1 5
NOTES: a) Table is based on dead end pipelines; number of customers may be doubled
for 2" and 3" circulating pipelines only.
b) Table is based on metered customers.
Ratios
Desirable: Actual
Pressure at
Start at Main (psi)
26 30 40 50
-------
4. Storage of treated water
a. Are ground level or subsurface tanks used ?
Are they sealed?
Are they always full?
Does a test program exist to test them
for leaks ?
Are vents inverted and protected from
admitting insects, animals, etc. ?
Is tank at high point of surrounding area
to provide surface drainage away from
tank ?
b. Are elevated tanks used? Yes
Where are they located with respect
to pump units?
i. At pump unit?
ii. At far end of area served? u^-""
iii. In middle of area served?
Are tanks sealed and protected from
intrusion of insects, birds, rainwater? Yes
Are vents inverted and screened? Yes
Are open reservoirs used?
Are they protected from intrusion by
humans and other animals?
Is chlorine residual maintained?
Is treatment provided to prevent growth
of algae and other plankton which are odor
and taste formers?
Is water chlorinated at discharge and at
least 0.4 mg/ i residual maintained not
less than 30 minutes prior to reaching
customer? See paragraph f, page D-5.
E-7
-------
5. Capacity Rating
a. lias water system ever discontinued or curtailed
service to customers due to lack of adequate dis-
tribution capacity and pressure? NO
i. Times per year (average) Q
ii. Days per time (average) —•
iii. Percentage of distribution system
per time (average) —
iv. Historical distribution capability
' ... ~ i
x U1 - '-
365
b. Consider ratios of 3, a. vii and 3.b above.
B. Distribution Reliability
1. Model the distribution system using Figure E-l and detail
each operation following the procedures in Appendix A.
Enter A. 5. a. iv into the reliability evaluation as historical
reliability for the subsystem. See pages E-15 through E-21
for demonstration system.
2. Consider pumps and standbys from A. 1 and A. 2 above.
3. Consider one and two direction supply areas in the model
from A. 3. d. Use Figure E-2 for reliability.
4. Calculate the probability of pressure loss due to peak
demand load using data from A. 3. f as follows:
p , [8760-Hrs of Pres. Loss 1 x / % of system
f.L,: - i-
r8760- Q 1 s
"I 8760 J X/
C. Distribution Design and Maintenance Adequacy
1. Portion of system (from A. 3. 1) having 35-year or
greater life expectancy 90 %
E-8
-------
M
co
13 DISTRIBUTE TREATED-
WATER
-131 CONVEY TREATED WATER
L-132 STORE TREATED WATER-
-C
311 CONVEY TO STORAGE -
1312 CONVEY TO DEMAND-
-1321 STORE IN TANKS-
-1322 STORE IN RESERVOIRS-
-C
41
j-,3:
T— 13:
13112 PUMP FEED TO STORAGE
13121 GRAVITY FEED TO DEMAND
13122 PUMP FEED TO DEMAND
13211 ELEVATED TANKS
13212 GROUND-LEVEL TANKS
13221 LINED RESERVOIR
1222 EARTHEN RESERVOIR
Figure E-l. Structure and Matrix for Distribution of Treated Water, Subsystem 13
-------
10000
5000
Use for Dead
End Mains
(Not Looped)
0 0.1 0.2 0.
0.4
0.5 0.6 0.7 0.8
Inherent Reliability
0.9 1.0
Figure E-2. Distribution Main Reliability
with Respect to Installed Length
E-10
-------
2. Number of miles of pipe with dead ends = Q .Adequacy = 1 - Ratio = \ .Q
3. Number of flow interruptions involving more than
one block £-S
Ratio of interruptions involving more than one
block to total blocks served
6 4 43V = .QI3& . Adequacy = 1 - Ratio = Q.9662.
4. Adequacy of mains 3 inches and smaller and number
of customers. Total number of connections exceeding
desirable number (from A. 3. m) divided by total
number of connections.
O 4 = Q . Adequacy = Ratio = \»O
5. Number of repairs utilizing proper disinfection,
flushing, and testing divided by total system repairs
(average per year), see A. 3.n. \ 5 4- i S =
l.Q - repair disinfection adequacy.
6. Leak repair adequacy = number of leaks repaired
per year divided by total number discovered (from
A. 3.o) = \5€> -s- ise = i.Q
7. Using distribution reliability model from B, model
probability of not having a cross-connection con-
tamination as follows:
Using reliability for distribution from Appendix Aj
raise the subsystem reliability (R^ x R2) to the
power of the number of cross-connections found
per year (from A. 3. q), cross-connection
potential = ( ,566£ ) (Z^ = O.3677
E-ll
-------
if the nature of the cross-connection hazard
is identified, compute the probability of not
exceeding the constituent limits of the drinking
water standards and multiply by the cross-con-
nection potential to obtain the probability of not
contaminating the subsystem. Enter the result
into the Appendix A and B analyses for the
distribution subsystem.
8. Adequacy of valve maintenance program is the number of
times per year (average) that interruptions of excessive
areas (over one block) were required divided by total
number of interruptions = 6 4- ISC = «0384
Adequacy = 1 - Result = \ - .038H *• 0.9616
9. Refer to the failure modes and effects analysis in
Appendix I, Figure 1-6, to determine effects of failure
on system reliability. The effects should be considered
when modeling the system for reliability analysis.
D. Quality Surveillance of the Distribution System
1. Calculate the probability that distributed water exceeds
the constituent limits of the drinking water standards
and the water quality rating using the procedures of
Appendix B. See pages E-22 through E-26 for the
demonstration system.
2. Using the same methods (Appendix B), calculate the
following control analysis probabilities.
a. Aluminum - probability of exceeding 0. 05 mg/£
b. Chlorine residual - probability of exceeding
0.4 mg/ i
c. Hardness - probability of exceeding 80 mg/i,
d. pH - probability of falling outside of range from
5. 6 to 9. 5 (use same technique as for flouride
content).
E-12
-------
3. Does bacteriological sampling conform to the minimum
required by the drinking water standards (see Figure E-4)?
Required number per month - Yc S
Number taken per month = 52.
52. ftire -takev^ b -H,e ^a^er
are
by
E-13
-------
DRINKING WATEB 8TANDABD8, 188J
MINIMUM NUMBER OF SAMPLES PER MONTH
1.000
10.0»
° 100.000
1.000.000
10.000.000
The minimum number of samples to be collected from
the distribution system and examined each month should
be in accordance with the number on the graph for the.
population served by the system. For the purpose of
uniformity and simplicity in application, the number
determined from the graph should be in accordance
with the following: for a population of 25, 000 and
under— to the nearest 1; 25, 001 to 100, 000 — to the
nearest 5; and over 100, 000 - to the nearest 10.
In determining the number of samples examined month-
ly, the following samples may be included, provided
all results are assembled and available for inspection
and the laboratory methods and technical competence
of the laboratory personnel are approved by the
Reporting Agency and the Certifying Authority:
(a) Samples examined by the Reporting Agency
(b) Samples examined by local government
laboratories
(c) Samples examined by the water works
authority
(d) Samples examined by commercial laboratories
The laboratories in which these examinations are made
and the methods used in making them shall be subject
to inspection at any time by the designated repre-
sentative of the Certifying Authority and the Reporting
Agency. Compliance with the specified procedures and
the results obtained shall be used as a basis for certi-
fication of the supply.
Daily samples collected following a bacteriologically
unsatisfactory sample shall be considered as special
samples and shall not be included in the total number
of samples examined. Neither shall such special
samples be used as a basis for prohibiting the supply,
provided that: (1) when waters of unknown quality are
being examined, simultaneous tests are made on
multiple portions of a geometric series to determine a
definitive coliform content; (2) immediate and active
efforts are made to locate the cause of pollution; (3)
immediate action is taken to eliminate the cause; and
(4) samples taken following such remedial action are
satisfactory.
Figure E-4. Sampling Rate for Bacteriological Analysis
-------
DISTRIBUTE TREATED)
WATER
r!31 CONVEY TREATED WATE
ifr-r
Ur
L-I32 STORE TREATED WATER
CONVEY TO STORAGy-
312 CONVEY TO DEMANJ^-
.1321 STORE IN TANKS
1322 STORE IN RESERVOIRS-
3111 GRAVITY FEED TO STORAGp
3112 PUMP FEED TOSTORAGT^^
13212 GROUND-LEVEL TANKS
13221 LINED RESERVOIR
13222 EARTHEN RESERVOIR
Figure E-l. Structure and Matrix for Distribution of Treated Water, Subsystem 13
-------
TABLE A-1. UNIT Ql-ERAT1ON RL LIABIL1TY
Operation Description:
Stage Identification Number:
(1)
FgedL 'bo C Lg^>rt*3f-
mber: I 3 1 11
!2) (3)
(4)
(5)
(6)
(7)
Component Name
PlPfc
Afcnu.a/ Values
Quantity
Installed
N
1
4
Quantity
Required
n
J
¥
Quantity
Standby
S
O
0
Reliability, R, No Standbys, n=N
R (from Fig. F-2)
.99,39
.9999
RW
.99^9
.9996
Series Components Reliability = Product of i'UN .= HI = .99S
Standby Components Reliability = Product of ll\ - R? ~
Unit Operation Reliability,
Reliability, R,
where standbys
are installed:
n + s = N; R
(from Fig. F-2)
.
.
J = Product of RI x H?. =.991" x — • = . 99£
Enter R in Column (5) of Table F-2.
H
-------
TABLE A-l. UNIT OPERATION RELIABILITY
Operation Description: ^y
Feeai
LVLZK
Stage Identification Number: i3lli-f
(1) (2) (3)
l 2. \ 3l
(4)
(5)
(6)
(7)
Component Name
Quantity
Installed
N
Quantity
Required
n
Quantity
Standby
S
Reliability, R, No Standby s, n=N
R (from Fig. F-2)
Reliability, R,
where standbys
are installed:
n •*• s = N; R
(from Fig. F-2)
ttM.»fL Wf.V Lr-f t-
I
Valve
1 —
M
i
.96
9939
9991
s
o
99 ea
'*!*<*
999l>
*&/•£?
- 99A
999J
Series Components Reliability = Product of
I = Rj
99S9
. 99&9
Standby Components Reliability = Product of R[ = R2 =
R = Product of
Unit Operation Reliability,
Enter R in Column (5) of Table F-2.
x R2 =
-------
TABLE A-1. UNIT OPERATION REI.IABIL.iTY
Operation Description
Stage Identification Number: i3ltl. /3//Z. 73/22. 131
/ i /
(1)
(2)
(3)
(4)
CCO/V 77A^«
(5)
(6)
(7)
Component Name
Quantity
Installed
N
Quantity
Required
n
Quantity
Standby
S
Reliability, R, No Standbys, n=N
R (from Fig.F-2)
Reliability, R,
where standbys
are installed:
n + s = N; R
(from Fig.F-2)
.9999
i
i—«
oo
J&_
.99 &9
Zoyi
Xoapeal
i
-_L-
-4-
._
t
, 99?ff
«...
-
Series Components Reliability - Product of Rj - R.j -
Standby Components Reliability = Product of R^ - llv -
Unit Operation Reliabiirt'yT"^. ~- Product of RYx~R~2 r/735~;;
Enter R in Column (5) of Table F-2,
-------
TABLE A-1. UNIT OPERATION RELIABILITY
Operation Description:^
Stage Identification Number: 133.11
(1) (2) (3)
(4)
(5)
(6)
(7)
Component Name
.SatM^ as
Quantity
Installed
N
0*a/W;r
Quantity
Required
n
{fr'344*
d
Quantity
Standby
S
re /="-3>.»
Reliability, R, No Standby s, n=N
R (from Fig. F-2)
RN
.9*70
Series Components Reliability = Product of RiN = RI = . 99"7£>
Standby Components Reliability = Product of R^ = R2 =
Reliability, R,
where standby s
are installed:
n + s = N; R
(from Fig; F-2)
Unit Operation Reliability, R = Product of RI x R2 = x = «997^
Enter R in Column (5) of Table F-2.
-------
TABLE A-2. SUBSYSTEM RELIABILITY
Subsystem Description:
UJft4eir
Stage Identification Number: i 3
(7)
(1)
Operation
Identi-
fication
Number
13111
iSlitjOiiX;
l3inT |3«^1
k
(32JI
(2)
Quantity
Installed
N
1
1
2.
(3)
Quantity
Required
n
1
1
2
(4)
Quantity
Standby
S
£>
O
O
(5)
Unit Operation
Reliability
Ri
.995
.704
.9970
(6)
If
n=N,
Compute
RiN
.?3T
.704
.991
Series Operations Reliability = Product of Ri = Rj = »694*
Standby Operations Reliability =Product of R^ = R0 =
If n + s = N, enter Ri on
curve RI in Fig. F-l, move
horizontally to right, and
read from R2 or R3 as
appropriate for number
of standbys
— .
-
Subsystem Reliability = Product of R| x R2 -',&& x . — • = .699. - Rss
Subsystem Historical Water Supply Capability -fy^i<. = BBS
Subsystem Ability to Furnish Water = Rss x Bss &94- _ x ,^b^> = *€>&$•
H
i
-------
TABLE A-5. OPERATION RELATIVE FAILURE EFFECT
m
Operation
Numher
(l-rnm Table K-2)
/3tH
yJ/zz.
13*11
APfi. £.
C.t.
C.3
c.¥
C.5
6.6
C.7
c,9
n
Summation, 2 Fj
i'l
.AM 4£Mrvj
(2)
Failure Lffecl
Weightinq
Factor. F
(From Tahli' !•-•)>
63A>Vd00
U&&BL
TASfefiflB
2ffAO
VlD
140
220
10
JAO
V05W)
/AO
stf' SttTmm
(3)
Operation
Weight Factor
Fraction
l-dy^F,)
.99f
.trr
.99?
.999
.999
,999
.199
.999
.199
.119
.999
(4)
Actual
Operation
Reliability. H;
(From Table F-2)
,995
.764
.931
l.oo
.9K
Loo
hOO
1,00
,367
•m
JO.O/
J5|£» System Failure Ef
(5)
Highest
Artuevablf
Kehahility. Hh
.999
.999
.HI
LOO
A 00
t*o
1.00
1.00
t.OQ
1,00
1.00
af9/
(M
Actual
Operation
Effect
CO k U)
,1**
,69f
.1X1
f999
,999
,9!S
J99
,999
.199
3*7
.%o
Eft 6) * (7)]j
ect Hating i^i — =
1 7)
Lowus.l
Operation
Effurt
CO X (SI
.197
,1X1
.197
,999
.199
,999
,999
,999
.999
.199
.999
.oi
*1I_
E-21
-------
(sheet 1 of 2)
WATER CONSTITUENT DATA
w
DO
to
Use Certified Laboratory Sources Only
Data Sources: Treatment Laboratory
Water Supply System: Name
Location
County Health Department _
State Health Department
Data for: Raw Water
Treated Water
Distributed Water
Constituent
Nonremovables:
Alkyl Benzene
Sulfonate. ABS
Arsenic, As
Barium, Ba
Cadmium, Cd
Chromiurn, Hexava-
lent. Cr+«
Chloride^ Cl
Copper, Cu
Carbon Chloroform
Extract. CCE
Cyanide. CN
Lead, pb
Nitrate_, NO3
Selenium, Se
Silver, Ag
Sulfate, SO4
Zinc. Zn
Radium -"•>
Strontium- »u
Removables:
Coliform
Color
Public Health Service
Drinking Wate
Recommended
Limit. Xi
0.5 mg/t
0.01
250.
1.0
0.2
0.01
45.
250.
5.
- Standards
Mandatory
Limit. X2
0. 05 mgj I
1.0
0.01
0.05
0.2
0.05
0.01
0.05
3uuc/ t
lOuMC/l
alXlorXj: 10% + /month
using 10 ml portions
b) >3-*(usinglOmlportions)
in 2 consecutive samples
in>l sample when <20 sam
pies/month. or>57(, when
>20 samples/month
c) 1/100 ml avg/mo. ; or
>3/50 ml. >4/100 ml
7/200 ml. 13/500 ml
15 units
Laboratory Water Test Results Z-Score Values
X
tie an
•7#
tSRi
Deviation
,1V
.wn+
N.
No. of
Tests
/O
W}
95T< Confid
*••**#
• 9^
A029
?nce Limits
x" - x &
X "X *W
x,-x-
^ffi
(&2ta
x,-x
^
XL-S"
_>1
"c
o
o
^
u
o
3
u.
L.
O
u.
*!-*'
ff
"c
"D
t,
3
£_
Probability of
Evceedina
Recon.mended
Limit
•32
0*
D\VS:
Monda:crv
Limit
Figure B -3. Calculations for Probability of Exceeding
the Drinking Water Standards
-------
(sheet 2 of 2)
H
N>
OO
Constituent
Removables (Cont'd
Fluoride, F
Iron, Fe (f~ftj P /-f|
Manganese. Mn
Odor, Threshold
Number
Phenols
Tastes
Total Dissolved
Solids. TDS
Turbidity
Public Health Service
Drinking Water Standards
Recommended
Limit, Xi
Mandatory
Limit, X2
Avg. Temp. F(LWR) F (Uppe
X
50. 0-53. 7°F 0
9 1 7
53. B-58. 3uh 0. 8 1.5
58. 4-63. 8°F 0.8 1.3
63. 9-70. 6°F 0. 7 12
70. 7-79. 2°F 0.7 1.0
79^3-90. 5°F 0.6 0.8
ti&ZDtl I
0.5 nTg/i
3
0.001 mg.1 1
Not obiectionable
500. mg/ I
5 units
Laboratory Water Test Results
X
Mean
k
t^j
Deviation
.09
alX 9 £*
N,
No. of
Tests
3V
/ if
-' - &
"TT
9*
m¥f
-,, - 2S1
"* -SIT
.93
Z-Score Values
X,-X'
—.SI
X2 - X '
e
,33
X - X'
7.9
Probability of
Exceeding DWS:
Recommended
Limit
_=j^r
mil
Mandatory
Limit
In 2 consecutive samples, or in >\ sample when <20 samples/month, or in >5% of samples when >20 samples/month.
Control Characteristics Measurement (Treated and Distributed Water)
Aluminum
Chlorine Residual
Hardness
Ph
0.05 me.1 1
0.4 me/ 1 •»•
80 mull
XL Xu
5. 6 9. 5
/&S" -t.
launi
p/V£p>
^«-
*fC/A/
-------
(sheet 1 of 2)
WATER CONSTITUENT DATA
M
i
to
Use Certified Laboratory Sources Only
Data Sources: Treatment Laboratory _
Water Supply System: Name
Location
County Health Department
State Health Department
Data for: Raw Water
Treated Water
Distributed Water.
Constituent
Nonremovables:
Alkyl Benzene
Sulfonate. ABS
Arsenic. As
Barium, Ba
Cadmium, Cd
Chromium, Hexava-
lent. Cr+B
Chloride, Cl
Copper, Cu
Carbon Chloroform
Extract, CCE
Cyanide, CN
Lead, j>b
Nit rate j NO 3
Selenium. Se
Silver, Afi
Sulfate. SO4
Zinc. Zn
Radium -226
Strontium-3U
Removables:
Coliform
Color
Public Health Service
Drinkine Wate
Recommended
Limit. Xi
0.5 mg/t
0.01
250.
1.0
0.2
0.01
45.
250.
5.
- Standards
Mandatory
Limit. X2
0. 05 meJ I
1.0
0.01
0.05
0.2
0.05
0.01
0.05
3uuc/i
lOuu c/t
a) XlorX2: 10% + /month
using 10 ml portions
b) >3 + (using 10ml portions)
in 2 consecutive samples
in>l sample when <20 sam
pies/month. or>57(. when
>20 samples/month
c) 1/100 ml avg/mo. ; or
>3/50 ml. >4/100 ml.
7/200 ml. 13/500 ml*
1 5 units
Laboratory Water Test Results
X
Mean
~T"r
n
Deviation
rf-S f
N,
No. of
Tests
JtObUi
//¥-
95* Confid
S'^.M
ry/3 -T&
\ L 7K,
^^f^ ^. .
snce Limits
*••*-£
*rr Xff*
Z-Score Values
Xj-X1
>«7C
l**5f
x,-S
>
-a*-
•^-s"
c
u
-o
i,
o
D
O
u,
/
/'*
x..;x'
a
c
-3
t,
3
L.
rs
Probability of
Exceeding
Recorr mended
Limit
0
,OOfr-7
. * j
nws:
Mandatorv
Limit
* "«•»/ * m ' ••• •
Figure B-3. Calculations for Probability of Exceeding
the Drinking Water Standards
-------
(sheet 2 of 2)
to
01
In 2 consecutive samples, or in >1 sample when <20 samples/month, or in >5% of sannples when >20 samples/month.
Control Characteristics Measurement (Treated and Distributed Water)
Constituent
Removables (Cont'd
Fluoride. F
Iron, Fe
Manganese^ Mn
Ddor, Threshold
Number
Phenols
Tastes
Total Dissolved
Solids^TDS
Turbidity
Public Health Service
Drinking Water Standards
Recommended
Limit, Xi
Mandatory
Limit, X2
Avg. Temp. F(LWR) F(Uppe
XL Xu
53.8-381. 3up ftT'ft- 1 . 5
58. 4-63. 8°F 0.8 1.3
63. 9-70. 6°F 0. 7 12
70.7-79.2°F 0.7 1.0
79. 3-90. 5°F 0.6 0.8
0.3 mg/jt
0.5 mg/i
3
0.001 mfi/i
Not oblectionable
500. mg/i
5 units
Laboratory Water Test Results
X
Wean
*)
*n
t*4
2.9
ۥ
Deviation
.«
&.3
N,
No. of
Tests
h
x' - x + ^
x - xVjf
A 33
/Wt
3.*-
- ?«•
X"=X-^
.4r
Z-Score Values
Xj X
y.^7
AVfc
X2- X'
XLX"
4^
•N L^A
.a^
Probability of
Exceeding DWS:
Recommended
Limit
.i2-
^99**
o
.Of
Mandatory
Limit
service
prev»{e»Tfvt
-------
(1)
Constituent
bacteria:
Coliform
3hysical:
Turbidity
Color
Threshold Odor
Taste
Chemical,
Recommended:
ABS
As
Cl
Cu
CCK
CN
Ke
Mil
NO:!
Phenols
S04
TDS
Zn
Chemical,
Mandatory:
As
Ba
Cd
Cr+6
CN
F
Pb
Se
Ag
Radioactivity:
Ra22«
Sr90
(2)
Weight
Fartor
10
9
9
9
9
9
9
a
o— •
9
9
-8-
9
9
9
JJ.
9
10
10
10
10
10
10
10
10
10
10
(3)
1-PU DWS)
P(; DWS) from Fie. c;-3
&.9031-
6.0-7
& t°t<.t
&,OQ
e>.33
o.~?\
o.oo
o.oo
(4)
(2) x (3)
0.032.
0.6J
/» W
o.oo
*. 97
6.39
o.oo
o.oo
74 .^."M-ii.**
_,,,..., n
PiSTv»Wte* watev _s|<2>x<3>i -^
T^^ft T *H. ft, ** n
O ^<2>i
(5)
n
£1(21 x (3) :
(2)x(3)+i = l'
n
S(2)i
i • 1
O.Z.O
3,9V
i/*n
o.oo
/ ?. Sfe
39*94.
o.oo
o.co
Figure B-6. Rating of System Ability to Meet Constituent
Limits of Public Health Service Drinking Water Standards
of 1962
E-26
-------
Water Quality
Surveillance
-------
APPENDIX F
SURVEY OF WATER QUALITY SURVEILLANCE
A. Sampling and Testing Covered in Appendices B, C, D, and E.
B. Laboratory — Subjectively rate on 0. 0 to 1. 0 scale considering
the following:
1. Is laboratory certified ?
2. Are services procured from a certified laboratory?
3. Are tests performed in accordance with Standard
Methods for the Examination of Water and Waste-
water? Ves
4. Is laboratory orderly and clean?
5. Is there any significant difference between water-
laboratory test results and health department or
other test results? .
•*"CUcvMV\e Residua)
6. Are samples from the distribution system taken
at random from the entire system or from pre-
determined locations?
7. Are laboratory chemists or technicians properly
trained and experienced in the performance of
water analysis ?
8. The structure of tests is shown in Figure F-l.
9. Refer to the failure modes and effects analysis, Appendix I,
Figure 1-8,. for guidelines in failure modes and effects.
RATING - CX85
C. Control of treatment is structured in Figure G-l; however, the
constituent tests for control are given in Subsection D of
Appendix E.
D. See pages F-3, F-4, and F-5 for the demonstration system.
F-l
-------
I
DO
14 PROVIDE WATER
QUALITY SURVEILLANCE —
TEST TREATED WATER FOR
BACTERIA
-142 TEST TREATED WATER FOR
CHEMICAL CON TENT
-143 TEST TREATED WATER FOR -
PHYSICAL AND AESTHETIC
CHARACTERISTICS
-1411
TEST TREATED WATER FOR BACTERI-
OLOGICAL CONTENT
-1421 TE3T FOR MINERAL CONTENT-
L144
-1422 TEST FOR ORGANIC CONTENI-
-1431
TEST FOR TASTE, ODOR,
TURBIDITY, AND COLOR"
r-1441 TEST FOR RADIOACTIVITY-
TEST TREATED WATER FOR
OTHER CONSTITUENTS—
L1442 TEST TO MAINTAIN CONTROL
OF TREATMENT
14111 SAMPLE FOR BACTERIA TEST
14112 TEST FOR BACTERIAL CONTENT
-14211 SAMPLE FOR MINERAL CONTENT TESTS
-14212 TEST FOR MINERAL CONTENT
-14221 SAMPLE FOR ORGANIC CONTENT TESTS
-14222 TEST FOR ORGANIC CONTENT
1431! SAMPLE FOR PHYSICAL AND AESTHETIC
CHARACTERISTICS
14312 TEST FOR PHYSICAL AND AESTHETIC
CHARACTERISTICS
14411 SAMPLE FOR RADIOACTIVITY TEST
14412 TEST FOR RADIOACTIVITY CONTENT
-14421 TEST FOR CHLORINE RESIDUAL
-14422 TEST FOR HARDNESS
14423 MEASURE PH
L14424 MEASURE TEMPERATURE
Figure F-l. Structure and Matrix of the Water Quality Surveillance Subsystem
-------
I
OO
PROVIDE WATER
QUALITY SURVEILLANO
,/MI TES1
V>—«JAJ
TEST TREATED WATER
•CTERIA
R FOy—-f\'
^411 1EST TREATED WATER FOR BACTERI-
OLOGICAL CONTENT
42 TEST TREATED WATER FOR
-CHFM|f-Al CDNTENX
143 TEST TREATED WATER FOR
PHYSICAL AND AESTHETIC
CHARACTERISTICS
144 TEST TREATED WATER FOR j
. OTHER CONSTITUENTS-
SL5
421 TEST FOR MINERAL CONTENT^
1422 TEST FOR ORGANIC CONTENI
1431 TEST FOR TASTE, ODOR,
TURBIDITY. AND COLOR
-1441 TEST FOR RADIOACTIVITY-
Mill SAMPLE FOR 8ACIEKIA
GI42^IS
.T4212T
1 M
14212 TEST FOR MINERAL CONTENT^J
TESTSJ}
14221
J4222 TEST FOR ORGANIC CONTENT
43!! SAMPLE FOR PHYSIC
_. CHARACTERISTICS
\l AND AESTHE
-c
[14312 TEST FOR PHYSICAL AND AESTHETIC")
_ CHARACTERISTIC^ ^^
14411 SAMPLE FOR RADIOACTIVITY TEST
14412 TEST FOR RADIOACTIVITY CONTENT
"l442 TEST TO MAINTAIN CONTROL\
k^ OF TREATMENT -^
^14421 TEST FOR CHLORINE RESIDUAL^
•C4422 TEST FOR HARDNESp
^4423 MEASURE pH~^
\14424 MEASURE ItMPbRATuRrj
our
Figure F-l. Structure and Matrix of the Water Quality Surveillance Subsystem
-------
TABLE .A-2. SUBSYSTEM RELIABILITY
Subsystem Description: \Jj) a"t*gy~
: fr
Stage Identification Number: |
y
(7)
(1)
Operation
Identi-
fication
Number
/v//
J ^J 4%^
i *J •
J^Stf
(2)
Quantity
Installed
N
P(±l>uis
P&PLAS
j?f
j&ajrx ,if~
^a^x-SSV^
(6)
If
n=N,
Compete
.996.8
'^^•^
.&4O
Series Operations Reliability = Product of Ri = R| = "sJutk
Standby Operations Reliability =Product of Rj = R0 =
If n + s = N, enter Ri on
curve RI in Fig. F-l, move
horizontally to right, and
read from H2 or R3 as
appropriate for number
of standbys
.
Subsystem Reliability = Product of R] xR9'=' x =.oZ2Z = RSS
Subsystem Historical Water Supply Capability = - BQS
Subsystem Ability to Furnish Water =
rXooXXjoo X ~*
on f.
-------
TABLE A-5. OPERATION RELATIVE FAILURE EFFECT
&*rr/i
Optiraiion
Number
'(.m TahU- h
Failure liffecl
Factor. F
( 1- rom THhlt- (• -4)
Oporatinn
Wmght Factor
FructKin
/Vat
£2£££_
_^21
Actual
Operation
Huhahility, R.
From Tiihle K - 2)
366
Highest
f ^fration
A-hievabii-
Keliahllity, H
(b)
Actual
Operation
Failure
t-Jffent
(4)
'h :. '._
ADO
LoO
f.OO
SAO
.237
(71
Li-wt-.l
Optiruln>n
Failuru
Efli^rl
CO « (5)
.1*9
Operation
Z.&S'*. _
Summation,
• System Failure Effect Rating
F-5
-------
Susfe-r: Services
-------
APPENDIX G
SURVEY OF SYSTEM SERVICES
The structure of system services is shown in Figure G-l. Failure
modes and effects are given in Appendix I, Figure I-10 for consideration
in modeling and in rating the subsystem. Model the system and compute
reliability and failure effects using methods of Appendix A. See pages
G-7 through G-14 for the demonstration system.
A. Utilities
1. Two independent power supplies with switch gear for
each should be furnished where electrical power is
required such as for intakes, treatment facility, all
pump stations, and controls. Ov>\y ov\e pvov'idea.
2. Model the power supply and determine reliability and
failure effects using Appendix A.
3. A special note is that auxiliary power supplies should
be capable of being placed on-line before water storage
is depleted or risk of contamination increases.
b. Sanitary and Habitability Items
1. Sanitary facilities such as toilets, drains, and other
sanitary sources of contamination should be so in-
stalled to prevent any possible contamination of treated
water. If such facilities are so located that contami-
nation may be possible, treat as common walls, and
compute reliability as follows:
a. Determine number of toilets, drains, and other
sanitary sources of contamination Q
b. Enter quantity into Figure D-3 and read reli-
ability from abscissa. Reliability should be
entered into calculations in Appendix A.
2. Habitability items such as heat, air conditioning, ven-
tilation, safety, and emergency equipment should
G-l
-------
function properly. Safety and emergency equipment should
be properly located for easy access by personnel. Enter
human engineering items into the reliability analysis of
Appendix A. Check safety and emergency equipment for
proper, locations.
a. Breathing apparatus, gloves, goggles within easy
reach of chlorine equipment and storage.
b. Fire fighting equipment should be located near
hypochlorite and sodium chlorite storage and feed
equipment. Sodium chlorite burns and is explosive.
c. Eye flushing fixtures should be located near chemical
equipment.
Human engineering should be evident in plant design, layout,
and equipment installation. Inspection points include cleanli-
ness, location of controls within easy reach, room to move
about, standard controls, safety devices, alarms, fail-safe
devices, and in general an environment that fosters effective
procedures, work patterns, and personnel safety and that
minimizes discomfort, distractions, and other factors which
degrade human performance.
Subjectively rate safety equipment location and suitability on
a 0.0 to 1. 0 scale with 0. 25 as poor, 0. 50 below average,
\0_. Tjy average, and 1. 0 excellent. Enter this rating as a
series reliability item in the services analysis in Appendix A.
C. Preventive Maintenance Program
1. Schedule — A schedule for assigning and recording the per-
formance of preventive maintenance should be maintained.
The schedule should describe tasks to be accomplished,
intervals between accomplishment, and assigned personnel.
Lost
G-2
-------
Labor— Maintenance should be performed by skilled person-
nel having knowledge, experience, and training in the proper
methods of performing water system maintenance including
disinfection practices, operation of equipment in the water
in the water system, and particular skills as required for
maintaining mechanical and electrical equipment.
3. Instructions — Personnel should have available, easy to
read step by step procedures for performing maintenance.
The instructions should be in a form suitable for use on the
job. These instructions should state required personnel
skill levels for the detailed maintenance task.
4. Subjectively rate preventive maintenance on the basis of:
a. Training and experience of personnel in water
system maintenance and principles. ScVooleJ teX
cKesapeake Sect,;CM ot ftvs/WA.
b. Adequacy of schedules and instructions.
Rate on basis of 0. 0 to 1.0 scale and enter as a series
reliability into the reliability analysis of services in
Appendix F. , 85
D. Corrective Maintenance — Subjectively evaluate the same as
C. 2, 3, and 4 above. Enter as a series item in reliability
analysis.
E. Operate the Equipment
1. Controls — Model the system using Figure E- 1 and enter
reliabilities in accordance with Appendix F.
2. Monitoring Equipment and Instrumentation— Model using
Figure E- 1 arid enter reliability in accordance with
Appendix F.
3. Alarm System — An annunciator and alarm system should
provide indicators of operating equipment and alarms for
chlorination, chemical feed, capacity, main pressure,
G-3
-------
r!51 PROVIDE UTILITIES-
15 PROVIDE SERVICES-
O
I
1511 PROVIDE POWER -
1512 PROVIDE SANITARY AND HABIT-
ABILITY ITEMS
r
15111 PRIMARY POWFR
15112 AUXILIARY POWER
15121 SANITARY EQUIPMENT
15122 HABI1ABILITY ITEMS
15211 PREVENTIVE MAINTENANCE SCHEDULE
152 OPERATE AND MAINTAIN
EQUIPMENT
-1521 PERFORM PREVENTIVE MAINTENANCE-j-15212 PREVENTIVE MAINTENANCE LABOR
L-15213 PREVENTIVE MAINTENANCE INSTRUCTIONS
I-15221 CORRECTIVE MAINTENANCE LABOR
1522 PERFORM CORRECTIVE MAINTENANCE-L,5222 CORRECT|VE MAINTENANCE INSTRUCTIONS
L1523 OPERATE EQUIPMENT
-15231 CONTROL EQUIPMENT
15232 MONITORING EQUIPMENT
-15233 ALARM SYSTEM
- 15234 OPERATING SCHEDULE
-15235 OPERATING LABOR
-15236 OPERATING INSTRUCTIONS
Figure G-l. Structure and Matrix of Services Subsystem
-------
power, reservoir levels, fire. Enter reliability using
Figure E- 1 in accordance with Appendix F.
4. Operating Schedule — This schedule provides a record of
equipment operation, rotation, and a sequence for system
loadings such as equipment required to operate at minimum
load, normal load, full capacity, maximum load. Sub-
jectively rate on 0. 0 to 1. 0 scale and enter as a reliability
in accordance with Appendix F.
5. Labor — Subjectively rate on 0. 0 to 1. 0 scale and enter
reliability in accordance with Appendix F. Consider the
following:
a. Are operators trained in physical, chemical,
and bacteriological properties of water treat-
ment? »<> ^ vs
IO **-e
b. Are operators certified by state? s ftre NO-\-
c. • Are operators experienced in water sys-
tem operation? Yes
6. Instructions — Subjectively rate on 0. 0 to 1.0 scale and
enter as reliability in accordance with Appendix F. Con-
sider the following:
a. Are easy to follow equipment operating
principles and instructions posted at
operating stations and equipment? No
b. Are system operating instructions available
to chief operator at his duty station? Ho
G-5
-------
PROVIDE SERVICES'
15111 PRIMARY
PROVIDE POWER^
15112 AUXILIARY POWER
lSl PROVIDE UTILITIES
5i?i SANITARY EQUIPMENT
512 PROVIDE SANITARY AND HABIT-
ABILITY ITEMS
S122 HABIIABILIIY II
•^^•w
i^MMB
PREVENTIVE MAINTENANCE SCHEDUI
521 PERFORM PREVENTIVE MAINTENANCE
^_______^..^^
-gg22 PERFORM CORRECTIVE MAINTENANC
152 OPERATE AND MAINTAI
EQUIPMENT
CORRECTIVE MAINTENANCE INSTRUCTIONLSP
5231 CONTROL EQUIPMEN
\1S232 MONITORING EQUIPMENTI3
OPERATE EQUIPMEN
Q5233 ALARM SYSTEM_3
5234 OPERATING SCHEDULE
gap«—
OPERATING LA
15236 OPERATING INSTRUCTIONS
Figure G-l. Structure and Matrix of Services Subsystem
-------
TABLE A-1. UNIT OPERATION RELIABILITY
Operation Description:
Stage Identification Number: I S 11
(1) (2) (3)
(4)
(5)
(6)
(7)
Component Name
£Jec,-f trie. &t*e»~
Quantity
Installed
N
/
Quantity
Required
n
/
Quantity
Standby
S
0
Reliability, R, No Standby s, n=N
R (from Fig. F-2)
.99?J
'
R^
f?99/
Series Components Reliability = Product of RiN = Rj. = «99P/
Standby Components Reliability = Product of R^ = R? =
Reliability, R,
where standby s
are installed:
n + s = N; R
(from Fig; F-2)
. ,
Unit Operation Reliability, R = Product of RI x K2 =SRH x — • = ,9997
Enter R in Column (5) of Table F-2.
o
-------
TABLE A-l.UNIT OPERATION RELIABILITY
Operation Description: ij&
Stage Identification Number:_
(1) (2) (3)
(4)
(5)
(6)
(7)
Component Name
Jfe&rfM* &Qui£3.
3 Z> f
Quantity
Installed
N
/
Quantity
Required
n
/
Quantity
Standby
S
O
Reliability, R, No Standbys, n=N
R (from Fig. F-2)
. 9903
RN
.9903
Series Components Reliability = Product of RI = R! = » 97Q-&
Standby Components Reliability = Product of R^ = R2 =
Reliability, R,
where standby s
are installed:
n + s = N; R
(from Fig. F-2)
•
Unit Operation Reliability, R = Product of RI x R% = 9flB x — = ~9Q«L9
Enter R in Column (5) of Table F-2.
Q
i
CD
-------
TABLE A-1. UNIT OPERATION RELIABILITY
Operation Description
Stage Identification Number:
(1) (2)
(3)
(4)
(5)
(6)
(7)
Component Name
£o»hv/ fli'^Sys,
' fr*
Quantity
Installed
N
/
Quantity
Required
n
f
Quantity
Standby
S
o
Reliability, R, No Standbys, n=N
R (from Fig. F-2)
- 9955
Rw
.waa
Series Components Reliability = Product of RiN = RI = . 993&
Standby Components Reliability = Product of R^ = R2 =
Reliability, R,
where standbys
are installed:
n + s - N; R
(from Fig. F-2)
- —
Unit Operation Reliability, R = Product of RI x K2 =i99S»x *— = . 99&B
Enter R in Column (5) of Table F-2.
I
I-1
o
-------
TABLE .A-l.UNIT OPERATION RELIABILITY
Operation Description:
Stage Identification Number:_
(1) (2)
(3)
(4)
(5)
(6)
(7)
Component Name
£&*h+l JflottlJor-s
Vecareiers
7>/a/ TW/Aa^*.^
Quantity
Installed
N
/
¥
V
Quantity
Required
n
/
^
V
Quantity
Standby
S
O
0
&
Reliability, R, No Standbys, n=N
R (from Fie. F-2)
.99&&
. 99&B
, 999?
RN
.^95 A
*96/
- 999t>
Series Components Reliability = Product of RiN = RI = .939
Standby Components Reliability = Product of Rj^ = R? =
Reliability, R,
where standby s
are installed:
n + s = N; R
(from Fig. F-2)
.
. .
__
Unit Operation Reliability, R = Product of RI x R? --#£9 x — -.VS?
Enter R in Column (5) of Table F-2.
O
I
-------
TABLE A-1.UNIT OPERATION RELIABILITY
Operation Description:
Stage Identification Number:
(1)
mber: 15-233
2) (3)
(4)
(5)
(6)
(7)
Component Name
nff4tiMe.ia.4op Sy£-
w
Quantity
Installed
N
/
Quantity
Required
n
/
Quantity
Standby
S
-o
Reliability, R, No Standbys, n=N
R (from Fig. F-2)
- 0996
RW
. 999^>
Series Components Reliability = Product of RiN = RI = . 9^9&
Standby Components Reliability = Product of R[ - R2 =
Reliability, R,
where standby s
are installed:
n + s - N; R
(from Fig. F-2)
__
Unit Operation Reliability, R = Product of RI x R? ^999fex — • = .999£»
Enter R in Column (5) of Table F-2.
Q
-------
TABLE A-2. SUBSYSTEM RELIABILITY
Subsystem Description^
Stage Identification Number:
(7)
(1)
Operation
Identi-
fication
Number
(2)
Quantity
Installed
N
(3)
Quantity
Required
(4)
Quantity
Standby
S
(5)
Unit Operation
Reliability
Ri
(6)
If
n=N.
Compute
RiN
If n + s = N, enter Ri on
curve RI in Fig. F-l, move
horizontally to right, and
read from R2 or R3 as
appropriate for number
of standbys
• 999y*
/5V2/
-9gy
o
I
)—^
O5
/S2U-HS2J3
.939*
Series Operations Reliability = Product of Ri
R-2
Standby Operations Reliability =Product of
Subsystem Reliability = Product of R j" x R2 = _
Subsystem Historical Water Supply Capability =
.3fc^=.3l3
= R
ss
Subsystem Ability to Furnish Water = Rss x Bss
" BSS
x
-------
TABLE A-5. OPERATION RELATIVE FAILURE EFFECT
O|it;rMion
NiimhiT
1 r.-ni T.-ihli- K-2)
/r///
yr/z;
Kartoi , I-
( h com T;«hlf I -4'
\\ t-iRht Kactor
Frurtinn
I-IF.&F.)
1-1
.99*
All
(4)
/ictual
Operation
Reliahility. K;
(From Table F-2)
.9991
MO_
(4)
Highebt
Operation
llehahility, K
(6)
Anu.l
Operation
Failure
Kff.:cl
. 11 > (4)
.9999
/.oo
• 991
1.00
1.00
,999
LI.WI •••
Op til-ill K.I!
r'ailuru
KM. vl
I 1) X (S)
.999
,99?
.77*
.9/1
Opcr^l inn
H.IIIMI;
/.OO
/.oe
.9*
^372000
.99^
9999
,997
.999
.999
.959
.999
£27266
.999
,9996
.499
•
1.06
/sa.34
42.720
.999
a2£
1,00
01P_
15*35
.9/1
1.00
.77*/
,76
.999
/.oo
/T.
Summation, 2 Fj
> System Failure Effect Rating
.2^(6) + (7)].
G-14
-------
Composite Rating
-------
APPENDIX H
WATER SYSTEM COMPOSITE RATING AND
DETERMINATION OF CRITICAL OPERATIONS
AND COMPONENTS
COMPOSITE RATING
The water supply system rating is a composite of the reliability rating,
failure effect rating, ability to meet drinking water standards, and the
system design adequacy. An average of the four gives the system
rating.
System Reliability Rating, From Page H-2 = Q.S4
Water Quality Rating, From Appendix E,
Page E-23 = 0
Failure Effect Rating, From Page H-9 =
System Design Adequacy, From Page B-10 = Q.
Sum = 3./3
System Rating = (sum>4x 10° =
System Composite Rating
The. rating is expressed as a two-digit number having a value between
0 and 100 with a maximum value of 100.
IDENTIFICATION OF CRITICAL OPERATIONS AND COMPONENTS
Critical operations and components are identified in each of the four
rating areas; reliability, ability to meet standards, failure effect,
and design adequacy.
Water system reliability. Operation and component criticality with
respect to reliability is determined by subtracting the subsystem reli-
ability from one and dividing by one minus the system reliability. The
result when multiplied by 100 is the percent contributed by the subsystem
to the unreliability (unreliability = 1- reliability) of the system. Like-
H-l
-------
Equipment Reliability
Subsystem 11, Obtain Raw Water (Appendix C)
Subsystem 12, Treat Raw Water (Appendix D)'
R12 = £«^*8*J0 x $z(#**)* e>,mx .9z/
Subsystem 13, Distribute Treated Water (Appendix E)
R13 = 0»fc?V
Subsystem 14, Provide Water Quality Surveillance (Appendix F)
Subsystem 15, Provide Services (Appendix G)
R15 = 0,$20
Water System Reliability = R = Product of subsystem reliabilities:
R,, =/
Highest Attainable Reliability for the System (Appendix A, Page A- 13)
R + (0. 999/)N =
HE
Water System Reliability Rating (Appendix A, Page A- 17)
rj
System Rating = «-i = . *' S/6» a O* **
RHE ^
Figure H-l. Water System Reliability Study
H-2
-------
wise, operation unreliability divided by subsystem unreliability gives
operation contribution to subsystem unreliability, and component un-
reliability divided by operation unreliability gives component contri-
bution to operation unreliability. Criticality is defined as the subsys-
tems, operations, and components contributing the greatest unrelia-
bility to the system.
The subsystem criticality calculations are made using Table H-l.
Operations criticalities are evaluated using Table H-2. Components
criticalities are evaluated using Table H-3. Data are obtained from
Appendices C, D, E, and G for the reliability criticality analysis.
Critical subsystems, operations, and components should be evaluated
to determine the best approach to increasing reliability. See pages H-10
through H-17 for the demonstration system.
Water Quality. The identification of constituents which are critical
to the ability of the system to meet the drinking water standards is
determined by the relative contribution of each constituent rating to the
rating of system ability. The relative contribution is obtained from
column (5) of Figure B-6, Appendix B, (used in Appendices C, D,
and E), for the distribution subsystem.
Failure Effects. Operation failure effect criticality is defined as those
operations that, if failed, would cause the greatest effect on the ability
of the water system to furnish water meeting drinking water standards.
Those operations having a low rating in the failure effect computation
are critical. The operations would be those having a rating of less than
one from column (8) of Table A-5, Appendix A (used in each Appendix).
Relative criticality is determined by the lowness of the rating in
column (8h a 1. 00 rating is the highest and 0 the smallest. Critical
operations should be evaluated to determine the best approach to in-
crease reliability and decrease potential failure effects.
Design Adequacy. The design adequacy measures the ability of the sys-
tem to remove excess concentrations of constituents or determine if
the subsystems are contaminating the water. Criticality is based on the
design adequacy of the treatment and distribution subsystems relative to
H-3
-------
TABLE H-l. SUBSYSTEM CRITICALITY COMPUTATION
System Name
System Unreliability = 1-RS = 1-
Subsystem
Identification
Subsystem
Reliability
Rxx
Subsystem
Unreliability
1-Rxx
Criticality
1-Rxx
1-Rs
Remarks
H-4
-------
TABLE H-2. OPERATIONS CRITICALITY COMPUTATION
Subsystem Name
Subsystem Identification Number
Subsystem Unreliability = 1-Rxx = 1-
Operation
Identification
Operation
Reliability
Rxxxxx
Operation
Unreliability
1 - Rxxxxx
Criticality
1 - Rxxxxx
1 - Rxx
Remarks
H-5
-------
excess constituent concentrations. The evaluation should be correlated
with water quality data to determine if the excess constituents are pres-
ent in raw water, if satisfactory treatment is provided to remove the con-
stituents (if removable by treatment methods), and if the constituent is
added during treatment and distribution.
Cn'ticality .Analysis. Evaluating the various crihcal subsystems, opera-
tions, and components should lead to recommendations for improving
system design, reliability, operation, and control. The analysis should
result in recommendations to increase the ability of the water system to
meet the constituent limits of the drinking water standards.
H-7
-------
TABLE A-5. OPERATION RELATIVE FAILURE EFFECT
H-9
-------
TABLE H-I. SUBSYSTEM CRITICALITY COMPUTATION
System Name Demon
Sys.-h
ewv
System Unreliability = 1-RS = 1-^5^ = .46
Subsystem
Identification
H
12.
13
15
^ Trea
IX <
Subsystem
Reliability
Rxx
M**A8**
.96
.9K«.W«
• 55
• 68
.92.
•f'ruC^'vt" ^*>
ivx<^ 13) av
Subsystem
Unreliability
1-Rxx
.0*
. 15
.3Z
.08
rf di^.'t.
-C MO^T" Cri
Criticality
1-Rxx
1-Rs
.09
. 33^
,70^
• 17
4-' /^" 1
,rior\ (^Sut
•Koa. 1 s u le>
Remarks
•
H-10
-------
TABLE H-2. OPERATIONS CRITICALITY COMPUTATION
Subsystem Name TVea.-h *Ra\x/
Subsystem Identification Number \
Subsystem Unreliability = 1-Rxx = l-.g5 = »\S
Operation
Identification
/2/Z2-
/*22.
/z^3/
/2iV2-
/233/
/*33Z.
River -Source."
/*///
/3/Z.z.
~
/ 27.31
112*2
/232I
/*33*
/ O«?^^9
/ ^S ^^^w
Operation
Reliability
Rxxxxx
• 9 96
.?£&
-9<£s-
.999
.992.
.996
,996
.997
.973
.997
.995
.99z
.99V
.*Cri*
Operation
Unreliability
1 - Rxxxxx
,00V
,£>/^
-f>J$~
.col
.ooB
.oof-
• . oo ¥
.003
. ooz.
.ooS
. 006
oal ix.v»;-V Of
Criticality
1 - Rxxxxx
1-Rxx
.oaf
. o93 "*"
-^
— —^^^^£^ l/Vl
J^^^^TT^ 9 j ww
,ooG
.tfS3
,03.7
.0^7
,0X0
.0*0
.01 3
.053
.0*>
era Vf o*us
Remarks
f
H-ll
-------
TABLE H-3. COMPONENTS CRITICALITY COMPUTATION
Operation Name
Operation Identification Number
al* /&f iJ. Mi> floagula-fe f
'
I 2.2.2 — C »-
Operation Unreliability = 1-Rxxxxx =1-
Component
Identification
M** Feed
Aluv*» Feed
C-3vbov» Pteai
"Dv-aiw Va-H^e^
Mfxivtd tattle
5e<*i.*evcta*u>H
*&^SlVl
S^lufce C^aier
Component
Reliability
Re
.9963
.9999
.9999
. 9998
.9933
.393
.9996
•
Component
. Unreliability
1-RC
. 0037
, ooot
, oool
, ooot.
.0017
* 007
,000^
a I Co*^f«VV
Criticality
1-Rc
1 - Rxxxxx
.W*
. 001
. 007
,0 I1/
• 1 *• L
500"^
-°a9
Remarks
•
H-12
-------
TABLE H-3. COMPONENTS CRITICALITY COMPUTATION
Operation Name F;|-
(^v>avi-K, p;
Operation Identification Number I Z Z 3»l
Operation Unreliability = 1-Rxxxxx = 1 - «9<£?5 = • O\S
Component
Identification
Pi H"ev»jp
Aie^C3
Was k«*»atev
VaJves
Pfpe
£O»HMU>M CW^Iiy
Component
Reliability
Re
I-
,9996
.992.
.99*
.99fl9
.-999
Component
. Unreliability
1-Rc
0
. ooov-
. 008
« 006
,<9H
. 00 1
COVVN •pov^€v\"fc
Criticality
1-Rc
1-Rxxxxx
O
• 0X7
.5*33^
.«00*
.733^
L$"
Remarks
•
H-.l 3
-------
TABLE H-3. COMPONENTS CRITICALITY COMPUTATION
Operation NameAddl
S«sti'te~-
Operation Identification Number 1 32, 2.
Operation Unreliability = 1-Rxxxxx = 1-^9^5 = »
Component
Identification
AUwv Peeot
Mftuio Feeoi
Agi-te4o*r Mi^er
Af/x ISasi'vx
Floccttla'Voir
5eff/i^ Sas?iw
«f«
Component
Reliability
Re
. 9919
.99)9
.99^^
.^«3
.9691
.996
.9959
"*Cri*?<
Component
. Unreliability
I-RC
.00^1
-oofll
,0013
.6017
,0^09
,00+
00011
:al Ce>~vpo<
Criticality
1-Rc
1 - Rxxxxx
.33I-*
.3131^
,oJ7
,oV9
, »W*
.//^
.<»3l
^«vcty
Remarks
•
H-14
-------
TABLE H-3. COMPONFNTS CRITICALITY COMPUTATION
Operation Name Pi j-f&r mt
if Fil4*e>~ —
Operation Identification Number |"2.2-S I — River
Operation Unreliability = 1-Rxxxxx = 1 - ,9*7.3 = .
Component
Identification
FH-fcKs
Filter Sleeps
e>a3m
Cem-tvol VfelVe*
Rate CovftVoikr
/tShuaJ Vy /Vej
U/dfh t^fif^f- ftu*f>s
Pt/ye
Component
Reliability
Re
.99^
.992.
.996
.996
.9996
'999?
,996
,993?
.999*
Component
. Unreliability
1-RC
.00*
.008
-oo*
,oot
.000^
• ooo/
.00*
.oW/
,0003-
Criticality
1-Rc
1 - Rxxxxx
.148*
.llfa*"
1 tfSt ^
. \*9*
,o/s
• 0 Q't
.1*9*
.0*1
.oo7
rfcs
Remarks
•
H-15
-------
TABLE H-2. OPERATIONS CRITICALITY COMPUTATION
Subsystem Name
osej! o-P 1"
Operation
Unreliability
1 - Rxxxxx
, DOS
^ f*-r *
Criticality
1- Rxxxxx
1-Rxx
. O2,
.03
\A ^>-e
Remarks
•
H-16
-------
TABLE H-3. COMPONENTS CRITICALITY COMPUTATION
Operation Name £Vayi'4y aw^ fLt*r
_ > . /. . r
-rtve
.
Operation Identification Number / j///.
ovt
/3/2.a..
Operation Unreliability = 1-Rxxxxx =1- ,7Q = ,3O
Component
Identification
f?u**vp^ ; H fc v l*K*f
N/alveSj Manual
\raiVCi GKCjt-fc-
^« 1?
EAecb-ic Power
Recordte r".r
Valve^jCowcHx)!
^68«.^E*w.
^Vl^liw^
Pflre Viyci**dKV3f
f^UtK^s (ooo«"t^r
Component
Reliability
Re
1-
^\ A +} /
* ^?7*O^^
.9967
.9971
31*\
.W8
, S89
.9996
Component
. Unreliability
1-RC
o
.107*
9 Oo3 3
« GO?**
.0111
0002.
In,
a cwr-
Criticality
1-Rc
1 - Rxxxxx
0
'ot*
.01
.01
.04
.01
.37*
a
Remarks
••
H-17
-------
Failure Modes &
Effects Analysis
-------
APPENDIX I
WATER SYSTEM FAILURE MODES AND EFFECTS ANALYSIS
A failure modes and effects analysis was performed to define all physi-
cal, operational, and surveillance components of urban water systems
that have, or may have, an effect on the ability of the total water supply
system to produce water of a given quality. A failure modes and effects
analysis is a systematic method of determining the consequences of unit
operation failure with respect to system operation. The analysis re-
sults in the identification of components which are critical to satis-
factory system performance.
The failure modes and effects analysis is performed for each unit
operation of each subsystem in the water system. Unit operations in
water systems were structured by subsystems. A matrix is provided
to insure examination of all components of water systems. The follow-
ing definitions apply to column headings used in the failure modes and
effects analysis:
1. Component and number - Name and identification
number of components and unit operations
2. Component function - Description of design function
to be performed by the component or unit operation
3. Failure mode - Description of failures which occur
to component or unit operation
4. Failure effect - Identification of effect on system and
water quality caused by the failure mode of the com-
ponent or unit operation
5. Detection means - Description of methods which can
be used to identify the possible occurrence of the
failure
6. Remarks - Comments and other considerations re-
lated to component or unit operation design, installa-
tion, inspection;, operation, and maintenance
1-1
-------
The failure modes and effects analysis defines design, operation,
maintenance, and surveillance criteria which should be considered
in evaluating and rating water supply systems. It is provided to assist
in identification of water system characteristics which are critical to
the ability of a water system to consistently supply water meeting the
constituent limits of Federal Drinking Water Standards.
The failure modes and effects analyses are included for each sub-
system on the following figures and pages:
Subsystem 11 - Obtain raw. water, Figures 1-1 and 1-2,
Pages 1-3 through 1-22
Subsystem 12 - Treat raw water, Figures 1-3 and 1-4,
Pages 1-23 through 1-40
Subsystem 13 - Distribute treated water, Figures 1-5 and
1-6, Pages 1-41 through 1-47
Subsystem 14 - Provide water quality surveillance,
Figures 1-7 and 1-8, Pages 1-48 through 1-50
Subsystem 15 - Provide services, Figures 1-9 and I-10,
Pages 1-51 through 1-57
1-2
-------
11 OBTAIN RAWWATER-
i
CO
-111 PROVIDE SOURCE-
-112 CONVEY RAW WATER-
STORE RAW WATER -
rl 111 OBTAIN FROM GROUND WATER•
Ll 112 OBTAIN FROM SURFACE WATER-
-1121 CONVEY TO STORAGE-
1122 CONVEY TO TREATMENT -
•1131 STORE IN TANKS
L1132 STORE IN RESERVOIR-
t
•c
11111 OBTAIN FROM WELLS
11112 OBTAIN FROM SPRINGS
11121 OBTAIN USING IMPOUNDMENTS
11122 OBTAIN DIRECTLY FROM STREAM
11211 GRAVITY FEED TO STORAGE
11212 PUMP TO STORAGE
11221 GRAVITY FEED TO TREATMENT
11222 PUMP TO TREATMENT
11311 STORE IN ELEVATED TANK
11312 STORE IN GROUND-LEVEL TANK
11321 STORE IN LINED BASIN RESERVOIR
11322 STORE IN EARTHEN RESERVOIR
Figure 1-1. Structure and Matrix of Water Source
-------
(sheet 1 of 19)
Operation Name: Supply Raw Water From Wells
Operation Number: 11111000
Subfunction: Supply From Groundwater 11110000 Function:
11100000
Provide Raw Water Source
11000000
Subsystem: Obtain Raw Water
Component
& Number
Well Screen
11111001
Well Casing
or Pit
11111002
Component
Function
Screen out sand and
other solids from
water.
Prevent intrusion of
contaminated higher
level water into aquifer.
Provide casing into
which drop pipe is
lowered for removing
water. Casing should
be sealed to imperme-
able layer.
Failure
Mode
Collapse of screen.
Clogging by bacteria
growth or mineral
buildup.
Leakage of contam-
inated water into
well.
Failure
Effect
Sand/solids in water
prevent flow from
well and possible
screen callapse.
Increased bacteri-
ological or chemical
contamination of
water and aquifer.
Detection
Means
Increased turbidity
of raw water
increased sand/
solids in raw water.
Testing raw water
for increased bacte-
ria and chemical
constituents. Pres-
sure testing of well.
Remarks
Screens should be re-
placed at failure.
Bacterial contami-
nation most prevalent.
Well location has bearing
on contamination. Consi-
derations include:
1. Well at high point of
land.
2. Located at least the
maximum distance
from pollution sources
that economics, land
ownership, geology,
topography will permit.
3. Survey location with
respect to caves, sink
holes, abandoned wells/
bores, fissures, faults,
over the aquifer.
Figure 1-2. Component Failure Modes and Effects Analysis
-------
(sheet 2 of 19)
Operation Name: Supply Raw Water From Wells
Operation Number: 11111000
11100000
11000000
Subfunction: Supply From Groundwater 11110000 Function: Provide Raw Water Source Subsystem: Obtain Raw Water
Component
&' Number
Component
Function
Failure
Mode
Failure
Effect
Detection
Means
Remarks
Well Cap Seal casing to prevent Leakage of contami-
11111003 surface contamination nated water into well.
and to drain surface Vent flooded and con-
contamination away taminates well.
from well head. Cap
provided with vent to
maintain atmospheric
pressure in casing.
Pipe Constrain water and Leakage of contami-
11111004 convey from aquifer to nation into water. Re-
surface. Prevents intru- quires loss of pres-
sion of contamination sure in pipe. Leakage
from external sources, reduces quantity
supplied.
Check Valve Prevent loss of pump Failed to open.
or Foot Valve prime and drop in water Shattering due to back
1111005 column in drop pipe. pressure.
Prevent backflow to
well.
Increased bacteri-
ological or chemical
contamination of
water and aquifer.
Increased bacteria
contamination of
water. Loss of
water.
Testing raw water
source for bacteria
and chemical consti-
tuents changes/
increases. Pressure
testing of well.
Pressure drop in
source supply pipe.
Decreased flow from
well. Test for increased
bacteria concentration.
Possible loss of
pump prime. Back
flow to well and loss
of pressure. Possi-
ble contamination of
aquifer if water in
pipe is contaminated.
Back flow through pump
and well. Loss of pres-
sure from well supply.
Figure 1-2. (Continued)
-------
(sheet 3 of 19)
Operation Name: Supply Raw Water From Wells
Operation Number: 11111000
Subfunction: Supply From Groundwater 11110000 Function: Provide Raw Water Source
11100000
11000000
Subsystem: Obtain Raw Water
Component
& Number
Flow Meter
11111006
Component
Function
Measure output.
Line Stop Valves
11111007
i
05
Normally open. Used
to manually isolate
well from system.
Pump Withdraw water from
11111008 aquifer and supply
under pressure to
system.
Failure
Mode
No indication or record
of output.
Leakage. Failed to
open.
Pump or driver failure.
Failure
Effect
Loss of output record.
No effect to water
quality.
Negligible loss of
ability to isolate well.
No water quality
effects.
Loss of pressure. No
water quality effects.'
Detection
Means
Recorder or indicator
not functioning. No
quality effects.
Manual check of
valve operation.
Pressure drop.
Remarks
In cases where
meter is part of
control circuit, other
sources might be
started.
Alarms should be
used for pressure
loss.
Figure .1-2. (Continued)
-------
(sheet 4 of 19)
Operation Name: Supply Raw Water From Springs or From Infiltration Galleries
Operation Number: 11112000
Subfunction: Supply From Groundwater 11110000 Function: Provide Raw Water Source 11100000 Subsystem:
11000000
Obtain Raw Water
Component
& Number
Spring Box
11112001
Air Vent
11112002
Spring Screen
11112003
Flow Meter
11112004
Check Valve
11112005
Component
Function
Collection of gravity
spring water or
artesian water and
protection from sur-
face contamination.
Failure
Mode
Inflow of contami-
nated water.
Failure
Effect
Contamination of water
supply.
Flooding.
Collapse of screen.
Clogging of screen.
Maintain atmospheric
pressure in spring box.
Prevent intake of sand
and other solids.
See 11111006
Prevent back flow to Failed to open.
spring.
Contamination of water.
Sand and other solids
are taken into system
clogging and stopping
flow.
Back flow to spring.
Detection
Means
Testing raw water
for chemical and
bacterial content.
Testing raw water
for bacterial con-
tent.
Increase in solids
in water. Loss
of flow.
Pressure loss.
Remarks
Artesian sources are
at higher head than
surface and are less
subject to contami-
nation than gravity
springs which occur
from water table
outflow. The water
source (recharge
point) for springs must
be surveyed and pro-
tected from contami-
nation.
Vent should be inverted,
screened (#24 mesh), and
18 inches above surface.
Figure 1-2.. (Continued)
-------
(sheet 5 of 19)
Operation Name: Supply Raw Water From Springs or From Infiltration Galleries
Operation Number: 11112000
11000000
Subfunction: Supply From Groundwater 11110000 Function: Provide Raw Water Source 11100000 Subsystem; Obtain Raw Water
i
oo
Component
& Number
Line Stop Valve
11112006
Pipe
11112007
Component
Function
Normally open, used
to isolate part of sys-
tem or for manual flow
control.
See 11111004
Failure
Mode
Leakage.
Failed open.
Failure
Effect
Negligible loss of ability
to isolate part of system
or to manually control
flow.
Detection
Means
Manual check of
valve operation.
Remarks
Figure 1-2. (Continued)
-------
(sheet 6 of 19)
Operation Name: Supply Raw Water From Impoundment
Operation Number: 11121000
Subfunction: Supply From Surface Water 11120000 Function: Provide Raw Water Source 11100000 Subsystem:
11000000
Obtain Raw Water
Component
& Number
Line Stop Valve
11121001
CD
Control Valve
11121002
Component
Function
Opened or closed to
allow intake of water
at various heights in
the reservoir due to
water level or turbi-
dity.
Control flow of raw
water from reservoir
usually from remote
point such as the fil-
ter plant.
Failure
Mode
Seizure.
Leakage.
Erratic Control.
Seizure.
Leakage.
Failure
Effect
Seizure causes inability
to adjust valve or open
or close. Leakage pre-
vents complete close off
of an intake. Either
mode may cause diffi-
culty in controlling
intake of turbidity or
surface contamination
in the reservoir.
Controls or actuator
failure, seizure pre-
vents movement of
valve. Either mode
prevents flow control
and inability to shut off
supply if necessary to
prevent intake of
excessively contami-
nated water.
Detection
Means
Manually check valve
operation. Close and
check for leakage.
Remarks
Periodic calibration
and verification.
Operate valve through
open to close positions
on a periodic basis.
Figure 1-2. (Continued)
-------
(sheet 7 of 19)
Operation Name: Supply Raw Water From Impoundment
Operation Number: 11121000
Subfunction: Supply From Surface Water 11120000 Function: Provide Raw Water Source 11100000
11000000 •
Subsystem: Obtain Ra\v Water
I
i—'
O
Component
& Number
Reservoir
11121003
Component
Function
Failure
Mode
Failure
_ Kffect
Detection
Means
Remarks
Dike or Darn
11121004
Pipe
11121005
Store raw water and Contamination from
protect it. from further external sources such
contamination, and pro- as industry, sewage,
vide excess storage for habitation, waste-
periods of low rainfall.
runoff, and collection.
water. Contamination
from internal sources
such as recreation.
overgrowth in aquatic
vegetation, reduced
oxygen content.
Contain water in the lireak in dam.
impoundment and pro-
vide structure for yate-
house and overflow.
Confine water and Leakage or rupture.
transport it through dam Contamination by
to point of conveyance trace metals.
to treatment.
K>:cessive contamination
of impoundment which
may overload treatment
arid disinfection. Taste
and odor arc detrimen-
tally affected.
Loss of water supply.
Loss of water and
possible serious damage
to dam. Contamination
of water.
Water sampling Reservoirs provide excess
and testing of all storage to provide water to
source areas of source during low flow
impoundment con- periods. Raw water reserviors
lamination. Survey are particularly subject to
of impoundment. algal buildups requiring
Control and legal copper sulfate treatment.
authority required Note that water may be
to prevent con- purchased from external
tamination from reservoir owner.
external sources.
Storm control of
water level by
prior warning.
Inspection of dam
to assure integrity.
Pipe inspection
periodically, use
of proper materials'
prevents contami-
nation by trace
metals.
Figure 1-2. (Continued)
-------
(sheet 8 of 19)
Operation Name: Supply Raw Water From Impoundment
Operation Number: 11121000 . 11000000
Subfunction: Supply From Surface Water 11120000 Function: Provide Raw Water Source 11100000 Subsystem: Obtain Raw Water
Component Component Failure Failure Detection
&: Number Function Mode Effect • Means Remarks
Screen, Bar Prevent intake of de- Break in screen, dis- Intake of debris- Inspection and
11121006 bris from impound- lodging, clogging- Loss of water supply cleaning of screens-
ment.
Figure 1-2. (Continued)
-------
(sheet 9 of 19)
Operation Name: Supply Raw Water From Streams
Operation Number: 11122000
Subfunction: Supply From Surface Water 11120000 Function: Provide Raw \Vater Source 11100000
11000000 •
Subsystem: Obtain Raw Water
I
i—'
CO
Component
& Number
Cross or Side
Intake Weir
11122001
Fixed Screen
11122002
Traveling
Screen
11122003
Intake pipe or
Tunnel
11122004
Component
Function
Failure
Mode
Funnel or channel water Break
to an intake location and
provide a source of low
velocity with sufficient
depth.
Prevent intake of large
debris such as logs.
Break or dislodge-
ment of screen.
Clogging.
Remove fine debris such Break in screen.
as vegetation, leaves. Clogging of screen
fish. due to excess debris
or vegetation.
Confine water and con- Break or leakage.
vey it through intake Contamination of
structure. water by trace
metal in pipe.
Failure
Effect
Loss of source of low
velocity which may
increase turbidity and
susceptibility of intake
of debris.
Possible intake of large
debris which would dam-
age other intake com-
ponents. Clogging pre-
vents passage of water.
Possible intake of de-
bris which would trouble
treatment processes.
Loss of water supply
until screen is cleaned.
Damage to intake struc-
ture. Loss of water
supply. Contamination
of water.
Detection
Means
Periodic inspection
of weir.
Inspection of screen.
Inspection of screen
operation.
Inspection of pipe
periodically.
Proper choice of
materials prevents
contamination by'
trace metals.
Remarks
Washwater flow adjust-
ment is critical to
removal of debris.
Figure 1-2. (Continued)
-------
(sheet 10 of 19)
Operation Name: Supply Raw Water From Streams
Operation Number: 11122000
Subfunction: Supply From Surface Water 11120000 Function: Provide Raw Water Source 11100000
11000000 •
Subsystem: Obtain Raw Water
I
h-»
CO
Component
&: Number
Line Stop Valve,
Intake Gate
11122005
Check Valve
11122006
Screen Wash-
water Pump
11122007
Stream
11122008
Component
Function
Isolate intake from
source. Manual con-
trol of intake flow in
emergencies.
Prevent back flow of
water.
Provide water to wash
debris from screens.
Source of supply.
Failure
Mode
Seizure.
Leakage.
Fail open.
Loss of pressure.
Failure
Effect
Seizure prevents valve
operation and loss of
ability to control intake
in emergencies.
Leakage prevents
isolation of intake from
source.
Detection
Means
Periodically open
and shut valve to
check operation.
Check for leakage.
Remarks
Back flow may cause loss Periodically check
of water supply. valve operation.
Clogging of screens.
nonremoval of debris,
debris taken into system.
supply
Contamination of source.
Excess contamination Contamination of water.
by bacteria, vegetation Low flow causes loss of
(taste and odor).
Chemicals, low flow.
Transportation
accidents (autos,
trains) which may
cause source con-
tamination.
Alarms. Periodically Provide standby pumps.
inspect pump
operation.
Test water. Survey
stream and control
sources of contami-
nation. Set up early
warning system to
prevent intake of
waterwhich is beyond
capability of removal
by treatment.
Transportation safety
system. Water utility
should be on the list
of those to be notified
in case of accident in
the watershed.
Control of industrial and
other contamination is
necessary.
Figure 1-2'. (Continued)
-------
(sheet 11 of 19)
Operation Name: Convey Raw Water to Storage by Gravity
Operation Number: 11211000
Subfunction: Convey to Storage 11210000
Function: Convey Raw Water 11200000
11000000
Subsystem: Obtain Raw Water
Component
& Number
Pipe or Conduit
11211001
Component
Function
Confine and direct
raw water flow.
Line Stop Valves Isolate portions of
11211002 pipe for repair or
testing. Emergency
flow control.
Control Valves
11211003
Flow Meter
11211004
Control flow from
remote station.
Indicate water flow
for control of flow to
meet water demand.
Outflow Structure Provide connection
11211005 to pipe.
Failure
Mode
Rupture.
Leakage.
Contamination by
trace metals.
Fail open by seizure.
Leakage.
Improper response
to signal.
Seizure.
Leakage.
Nonindication of flow.
Leakage.
Failure
Effect
Loss of water. Trace
metal contamination
may cause failure of
water system.
Loss of isolation capa-
bility. Leakage causes
loss of water.
Loss of control.
Loss of visual means to
measure flow.
Loss of water leakage
into structure may
possibly contaminate
water.
Detection
Means'
Remarks
Periodically in-
spect pipe. Test
water for trace
metal contamination.
Proper design and
materials should
prevent contamination.
Pressure test for leaks.
Manually operate valves
periodically. Pressure
test for leaks.
Calibrate and verify
valve operation. Pres-
sure test pipe and valves.
Visual. Compare various
flow meters. Inspect and
calibrate.
Inspection of surfaces.
Figure 1-2. (Continued)
-------
(sheet 12 of 19)
Operation Name: Convey Ra-.T Water to Storage by Pumping
Operation Number: 11212000
Subfunction: Convey to Storage 11210000
Function: Convey Raw Water 1120000
11000000
Subsystem: Obtain Raw Water
Component
& Number •.
Check Valve
11212001
Line Stop
Valves
11212002
Pumps
11212003
Housing
Structure
11212004
Control Valves
11212005
Flow Meter
11212006
Component
Function
Prevent Back, flow to
pump.
Isolate pump from
pipe.
Provide energy to
move water.
Protect pumps from
elements and provide
foundation for pumps.
Provide flow control
from remote station.
Same as 11211004
Pipe or Conduit Same as 11211001
11212007
Outflow Structure Same as 11211005
11212008
Failure
Mode
Fail open.
Leakage.
Fail open.
Leakage.
Loss of capacity
through pump
failure.
Leakage.
Error response.
Leakage.
Seizure.
Failure
Effect
Loss of pressure when
pump not operating.
Back Flow of water.
Loss of capability to
isolate pump if check
valve also fails. A
safety hazard would
occur if only the check
valve were allowed to
hold pipe pressure.
Detection
Means
Periodically check
operation.
Periodically open and
shut valves and check
operation. Pressure
test for leaks.
Remarks
Loss of capacity and Periodically inspect
pressure (if all pumps pumps. Pump failure
fail). Loss of pressure indicated by annunciator
allows inflow of possible system.
contamination in system.
Loss of protection to
pumps, if severe
exposure results.
Control loss of positive
shut-off ability. Loss
of operation.
Inspection of housing
structure.
Calibration and testing
of valve operation.
Pressure test for
leakage.
Figure .1-2. (Continued)
-------
Operation Name: Convey Raw Water to Treatment bv Gravity
Ooeration Number: 11221000
Subfunction: Convey to Treatment 11220000
Function: Convey Raw Water 11200000
(sheet 13 of 19)
110000CO
Subsystem: Obtain Raw Water
Component
A- N-.;rr,ber
Pipe or Conduit
11221001
Line Stop
Valves
11221002
Control Valve
11221003
Flow Meter
11221004
Component
Function
Same as 11211001
Same as 11211002
Same as .11211003
Same as 11211004
Failure
Mode
Failure
Efioct
Detection
Means
Remarks
Figure 1-2. (Continued)
-------
(sheet 14 of 19)
Operation Name: Convey Haw Water to Treatment by Pumping
Operation Number: 11222000
Subiunction: Convey to Treatment 11220000
Function: Convey Raw Water 11200000
11000000
_ Subsystem: Obtain Raw \Vator
Component
&•. Number
Check Valve
11222001
Line Stop
Valves
11222002
Pumps
11222003
Housing
Structure
11222004
Component
Function
Same as 11212001
Same as 11212002
Same as 11212003
Same as 11212004
Control Valve Same as 11212005
11222005
Flow Meter
11222006
Same as 11211004
Pipe or Conduit Same as 11211001
11222007
Failure
Mode
Failure
Effect
Detection
Means
Remarks
Figure 1-2.' (Continued)
-------
Operation Name: Store Raw Water in Elevated Tanks
Operation Number: 11311000
Subfunction: Store in Tanks 11310000
Function: Store Raw Water 11300000
(sheet 15 of 19)
11000000
Subsystem: Obtain Raw Water
i
h-^
oo
Component
& Number
Pipe, Inflow
11311001
Tank
11311002
Level Recorder
11311003
Line Stop
Valves
11311004
Control Valve,
Altitude Valve
11311005
Component
Function
Same as 11211001
Confine and store raw
water. Storage also
provides some plain
settling. Storage gives
excess supply to meet
demand when source
flow is low.
Provide visual display
of stored water volume
and control feed.
Isolate fill pipe or tank
for inspection or repair
and for emergency flow
control.
Control amount of
stored water by head
pressure.
Failure
Mode
Rupture of tank. Leak-
age. Contamination bv
dissolving trace metals
from tank materials.
Algal growth can be a
problem in an open
tank.
Failure
Effect
Detection
Means
Remarks
Failure to record or
to properly regulate
water level.
Fail open by seizure.
Leakage.
Improper response to
control signal. <
Seizure.
Leakage.
Loss of stored water.
Possible loss of supply
if tank is not bypassed.
Contamination of water
may cause system to
fall below trace metal
standards.
Taste and odor.
Loss of visual display.
Possible under- or over-
filling with water.
Under-filling may re-
sult in loss of excess
supply or even loss of
supply.
Loss of isolation
capability.
Loss of level control
(automatic).
Periodic inspection, pres-
sure testing, and coating of
tank with noncontaminating
coating. Proper materials
and construction should
prevent contamination by
trace metals. Contamination
detected by testing water.
Comparison of level recorder
readings with equivalent head
or pressure indicators.
Inspection, calibration, and
verification of proper operation
should be periodically per-
formed.
Manually operate valves
periodically. Pressure
test for leaks.
Calibrate and verify proper
operation. Pressure test
for leaks.
Figure 1-2. (Continued)
-------
(sheet 16 of 19)
i.
i—*
CD
Operation Name: Store Raw Water in Elevated Tanks
Operation Number: 11311000
Subfunction: Store in Tanks 11310000
Function: Store Raw Water 11300000
11000000
Subsystem: Obtain Raw Water
Component
& Number
Level
Controller
11311006
Component
Function
Control signals to alti-
tude valve to preset
conditions of water
level.
Failure
Mode
Improper setting or
malfunction of signal
circuit.
Failure
rffcct
Loss of automatic level
control.
Detection
Means
Calibrate and verify
proper operation and
setting of controls.
Remarks
Figure 1-2. (Continued)
-------
I
CO
o
Operation Name: Store Raw Water in Ground Level Tanks
Operation Number: 11312000
(sheet 17 of 19)
Subfunction: Store in Tanks 11310000
Component
& Number
Pipe, Inflow
11312001
Tank
11312002
Level
Recorder
11312003
Line Stop
Valves
11312004
Control Valve
11312005
Level
Controller
11312006
Component
Function
Same as 11211001
Same as 11311002
Same as 11311003
Same as 11311004
Same as 11311005
Same as 11311006
Function: Store Raw Water 11300000
11000000
Subsystem: Obtain Raw Water
Failure
Modes
Failure
Effect
Detection
Means
Remarks
Figure 1-2". (Continued)
-------
(sheet 18 of 19)
Operation Name:
Operation Number: 11321000
Store Raw Water in Lined Reservoir
Subfunction: Store in Reservoir 11320000
Function: Store Raw Water 11300000
1100000
Subsystem: Obtain Raw Water
Component
&. Number
Reservoir,
Covered
11321001
Lined.
Line Stop Valves
11321002
i
CO
Component
Function
Confine and store raw
water. Provide excess
supply when source
flow is low. Provides
some plain settling.
Isolate reservoir for
inspection, cleaning,
and repair. Emergency
flow control.
Failure
Mode
Break in reservoir.
Contamination from
external source.
Sedimentation
buildup.
Fail open by seizure.
Leakage.
Failure
Effect
Loss of water. Exces-
sive contamination of
raw water. Loss of
storage capacity.
Loss of isolation
capability.
Detection
Means
Inspection. Test water.
Inspect sediment depth.
Ownership and protection
of area surrounding
reservoir is necessary.
Manually operate valves
periodically. Pressure
test for leaks.
Remarks
Control Valve,
Altitude Valve
11321003
Same as 11311005
Level Recorder
11321004
Same as 11311003
Pipe, Inflow
11321C05
Same as 11311001
Level Controller
11321006
Same as 11311006
Figure 1-2. (Continued)
-------
Operation Name: Store Raw Water in Earthen Reservoir
Operation Number: 11322000
(sheet 19 of 19)
11000000
Subfunction: Store in Reservoir 11320000 Function; Store Raw Water 11300000 Subsystem: Obtain Raw Water
IS3
to
Component
& Number
Reservoir, Earthen
11322001
Line Stop Valves
11322002
Control Valves,
Altitude Valve
11322004
Level Recorder
11322004
Pipe, Inflow
11322005
Level Recorder
11322006
Component
Function
Same as 11321001
Same as 11321002
Same as 11311005
Same as 11311003
Same as 11311001
Same as 11311006
Failure
Mode
Failure
Effect
Detection
Means
Remarks
Figure 1-2. (Continued)
-------
DO
oo
12 TREAT RAW WATER
F 12111 COARSE SCREEN RAW WAT El?
-1212 PRED1SINFECT RAW WATER
-1222 COAGULATE, FLOCCULATE,
-1231 SPECIAL DISINFECTION TREATMENT
-12113 MICRO-STRAIN RAW WATER
-12121 PREDISINFECT DIRECTLY WITH Clj GAS
-12122 PREDISINFECT WITH Clj GAS SOLUTION FE5D
-12123 PREDISINFECT WITH LIQUID Clj EVAPORATOR
-12124 PREDISINFECT WITH DRY HYPOCHLORITE
-12125 PREDISINFECT WITH HYPOCHLORITE SOLUTION
-12126 PREDISINFECT WITH CHLORINE DIOXIDE
-12141 SPRAY AERATE RAW WATER
-12142 AERATE WITH MULTIPLE TRAYS
-12144 AERATE WITH DIFFUSION AERATOR
-12145 AERATE WITH MECHANICAL AERATOR
-12212 SOFTEN WITH ION EXCHANGE
-12221 ADD CHEMICALS AND RAPID MIX
-12222 COAGULATE AND FLOCCULATE
H2223 SETTLE FLOCCED PARTICLES
C2231 FILTER WITH GRAVITY FILTER
.2232 FILTER WITH PRESSURE FILTER
-12241 DIRECTLY AND CHLORINE GAS FEED
-12242 CHLORINE GAS SOLUTION FEED
-12243 LIQUID CHLORINE GAS EVAPORATOR FEED
-12244 DRY HYPOCHLORITE FEED
-12245 HYPOCHLORIT5 SOLUTION FEED
-12246 CHLORINE DIOXIDE FEED
-12312 OZONATE WATER
TASTES AND ODORS
irn nonvinr r.ncriAl TB'ATUFfjT . 17331 ARD FLUORIDE TO WATER
F
r
L
122112 ADD CHEMICALS AND MIX,
COAGULATE AND FLOC-
CULATE, SETTLE FLOCCED
PARTICLES
12311 AERATION
123112 ADD REDUCING CHEMICALS
123113 ACTIVATED CARBON
Figure 1-3. Structure and Matrix for Raw Water Treatment, Subsystem 12
-------
Operation Name: Coarse Screen Raw Water
Operation Number: 12111000
Subfunction: Screen Raw Water 12110000
Function: Prctreat Raw Water 12100000
(sheet 1 of 17)
. Subsystem: Treat Raw Water 12000000
Component
& Number
Intake and Outflow
Structure
12111001
Fixed Screen, Bar
Grille
12111002
Component
Function
Confine raw water to flow-
ing through screen.
Failure .
Mode
Break or leak in
structure.
Remove debris from water. Clogged deterioration
or breakthrough.
Failure
Kffect
Detection
Means
Remarks
Loss of water screening. Inspection.
Loss of screening capa-
bility. Clogging causes
loss of water supply.
Taste and color prob-
lems might occur if
leaves or other vege-
tation decompose in
sufficient quantity.
Inspection of reservoir
and screens.
I
to
Figure 1-4. . Component Failure Modes and Effects Analysis
-------
(sheet 2 of 17)
Operation Name: Fine Screen Raw Water
I
to
cn
Operation Number: 12112000
Subfur.ction: Screen Raw Water 12110000
Component
& Number
Intake and Outflow
Structure
12112001
Traveling Screen
12112002
Washwater Pump
12112003
Check Valve
12112004
Line Stop Valves
12112005
Washwater Jets
and Pipe
12112006
Control Valves
12112007
Component
Function
Same as 12111001
Remove fine debris such
as vegetation, leaves.
Same as 11122007
Same as 11212001
Same as 11212002
Spray water to remove
debris from screen
Same as 11212005
Function: Prctrcat Raw Water 12100000
. Subsystem: Treat Raw Water 12000000
Failure .
Mode
Same as 11122003
Failure
Effect
Detection
Means
Remarks
Clogged jeta or pipe-
Clogged screen. In-
creased turbidity.
Inspection. Test of
water.
Figure 1-4. (Continued)
-------
Operation Name: Micro-Strain Raw Water
Operation Number: 12113000
Subfunction: Screen Raw Water 1211000
(sheet 3 of 17)
Function: Prctrent Rnw Water 12100000
. Subsystem: Treat Raw Water 12000000
I
to
O3
Component
& Number
Intake and Outflow
Structure
12113001
Traveling, Drum,
or Band Strainer
12113002
Washwater Pump
12113003
Check Valve
12113004
Line Stop Valves
12113005
Washwater Jets,
Piping
12113006
Control Valves
12113007
Drains
12113008
Sludge Removal
Pump
12113009
Component
Function
Same as 12111001
Same as 12112002
Same as 11122007
Same as 11212001
Same as 11212002
Same as 12112006
Same as 11212005
Drain Water from debris
removal area.
Remove sludge from wash
area-
Failure
Mode
Failure
Effect
Detection
Means
Remarks
Clogged.
Loss of sludge removal.
Flooding of structure.
Buildup of sludge in
debris removal area.
Inspection.
Inspection.
Provide standby sludge
pump.
Figure 1-4. (Continued)
-------
(sheet 4 of 17)
Operation Name: Predisinfect Directly Using Chlorir.e Feeder
Operation Number: 12121000
Subfunction: Prodis infect Raw Water 12120000 Function: Parent Haw \Vai.cr 12100000
Subsystem: Treat Raw Water 12000000
I
to
Component
?•-, >.' u r.i h e r
Chlorine Feeder
12121001
Component
Function
Feed chlorine gas directly
into pipeline or conduit, or
main, or channel.
Failure .
Mode
High water pressure
above R= 20 psi.
Inadequate mixing with
water.
Insufficient fired rate
for water quantity.
Freeze-up due to rapid
evaporation.
Failure
Kffect
Detection
Means
Flooding and failure of Pressure monitoring.
ft.'cdt-r to properly
diffuse C12-
Incomplete disinfection. Water analysis for
bacteria and chlorine
residual.
Inadequate disinfection.
Loss of chlorination.
Loss of chlorine residual Possible contamination
or increase in chlorine of water has occured.
demand..
Water analysis for
bacteria and chlorine
residual.
Feed indicator drop
in feed rate.
Monitor chlorine
residual.
Chlorine Storage Same as 12123002
Tank and Connection
12121002
Note: (1) Direct feed chlorine equipment should be considered as emergency equipment and for small
installations where a suitable supply of water is unavailable for operation of solution feeders.
(2) Safety equipment and emergency procedures should be available where chlorine storage and
equipment are installed so that hazards to personnel are minimized.
(3) Records should be maintained showing:
(a) Amount of water treated each 24-hour period (rate & flow)
(b) Chlorine used (weight)
(c) Applied dosage
(>'} Chlorinator settings
(e) Time and location of sampling and results of testing for chlorine residual.
Remarks
Maximum pressure
from Clo bottle.
20 psi
Diffuser should be within
25 ft of feeder ahead of
pump, valves, or similar
equipment-
Maximum feed rate is about
7ft Ib per 2-4 hours to a pipe-
line or main and about 300 Ib
per 24 hours to an open tank
or channel.
Feed at proper rates
depending upon ambient
temperatures.
The presence of chlorine
residual indicates safe
water.
Figure 1-4. (Continued)
-------
(sheet 5 of 17)
Operation Name: Predisinfect Raw Water With Chlorine Gas Solution Feeder
Operation Number: 12122000
Subfunction: Predisinfect Raw Water 12120000 Function: Pretrent Raw Water 12100000
. Subsystem: Treat Raw Water 12000000
Component
& Number
Chlorine Solution
Feeder
12122001
Component
Function
Feed chlorine in concen-
trated solution with water
into pipe, main, conduit,
•channel, or tank.
Failure .
Mode
Loss of water pres-
sure.
Loss of power.
Hazardous mani-
folding of tanks to
obtain desired feed
rate.
I
to
00
Freeze-up (relique-
faction).
Proper feed rate.
Failure Detection
Effect Means
Loss of vacuum and
chlorine feed.
Loss of chlorine feeder.
Loss of chlorine flow.
Loss of disinfection.
Loss of chlorine flow.
Loss of disinfection.
Personnel hazard and Inspection.
danger to losing supply
because of large number -
of tanks required.
Remarks
An injector water supply
is needed of 25 to 300 psi.
Electric power needed to
operate feeder and other
accessories.
Solution feeders can feed
up to 8000 !h per 24 hr
but discharge rate is
determined by tank pres-
sures and capacities.
Solution feeders generally
are coupled to chlorine
evaporators when required
for chlorine exceed about
2000 to 3000 tb per 24 hr
(see 12123000).
Flow loss.
Inadequate dosage.
Over-dosage giving taste
from chloramines.
Monitor flow and
alarms.
Monitor chlorine residual
and combined total chlorine.
Chlorine Storage Same as 12123002
Tank and Connections
12122002
See Note (2) Under 12121000.
Figure 1-4. (Continued)
-------
(sheet 6 of 17)
I
to
CO
Operation Name: Predisinfect Raw Water With Chlorine Feeder Using Evaporator
Operation Number: 12123000
Subfunction: Predisinfect Raw Water 12120000 Function: I'retrcat Raw Water 12100000
Subsystem: Treat Raw Water 12000000
Component
& Number
Chlorinator
12123001
Chlorine Storage
Tank and Con-
nections
12123002
Component Failure .
Function Mode
Same as 12122001
Provide chlorine supply on Leakage of gas.
a continuous basis. Scale
provide check on tank
usage and dosage rates.
Failure
Effect
Loss of chlorine and a
hazard to personnel
safety.
Detection
Means
Monitor tank
indicator for
loss rate.
weight
unusual
Chlorine Evaporator Provide controlled evapo-
12123003 ration of chlorine so that
proper mixing with water
is achieved. Superheats
chlorine gas for high use
rates (over 2000 Ib pc-r
24 hr).
Intermittent flow when
changing tanks.
Freeze-up due to rapid
evaporation from tank.
Insufficient number of
tanks for continuous
flow.
Loss of power.
Kt-liquefaction of
chlorine gas due to
pressure.
Evaporator leak.
Loss of disinfection
during tank changeover.
Loss of flow.
Loss of disinfection
because of lack of
chlorine'.
Loss of heat source and
possible loss of chlorine
feed.
Improper control of
mixing and feed into
water.
Loss of chlorine feed
and a hazard to
personnel.
Remarks
More than one source of
chlorine is desirable at
all times to insure not
depleting the tanks con-
nected and spares.
Proper mainifold de-
sign for chlorine tanks.
Flow indicators regis-
ter low flow.
Records showing tanks Keep adequate spare tanks
in use and number of on hand (some connected
'spares. to manifold) at all times
(30 day minimum supply).
Power failure.
Drop in chlorine
residual. Flow indi-
cator changes on
chlorinator. Causes
improper chlorinator
feed.
Loss of chlorination.
An alternate power source
or possible steam heat
source may be required.
A pressure-reducing valve
should be installed to pre-
vent reliquefaction.
An evaporator should be
provided for each chlori-
nator when used including
standby chlorinators.
See Note (2) under 12121000
Figure 1-4. (Continued)
-------
(sheet 7 of 17)
Operation Name: Predisinfect With Dry Hypochlorite
Ooeration Number: 12124000
Subfunction: Predisinfect Raw Water 12120000 Function: Pretrc-at Raw Water 12100000
Subsystem: Treat Raw Water 12000000
I
GO
o
Component Component
& Number Function
Dry Hypochlorite Provide container for
Basket or Bag Feeder hypochlorite to gradually
Using Hypochlorite dissolve and feed chlorine
Tablets into water stream.
12124001
Hypochlorite
Storage
12124002
Provide excess capacity
for feeder.
Failure .
Mode
Failure
Effect
Basket or bag failure Loss of feed and chlori-
nation.
Dissolving away of all Loss of disinfection.
hypochlorite.
Absorption of moisture
and fire hazard.
Corrosion of tank-
Loss of chlorine and
possible fire.
Deterioration and loss
of storage capacity-
Detection
Means
Inspection.
Water tests.
Water test; frequent
refilling of basket/
bag-
Moisture content in
storage area.
Inspection and pre-
ventive maintenance.'
Remarks
This is a manual operation
requiring personnel
monitoring and filling of
baskets. Hypochlorite feed
is limited to smaller water
supply systems.
Hypochlorites are
hygroscopic (slightly). .
Use corrosion resistant
materials.
Figure 1-4. (Continued)
-------
(sheet 8 of 17)
Operation Name: Predisinfeet With Hypochlorite Solution Feeder
Opera-.ion Number: 12125000
Subfunction: Predisinfect Raw Writer 12120000 Function: Prctrrat H.-v.v Water 12100000
Subsystem: Treat Raw Water 12QOOOOQ
I
oo
Component
& Number
Hypochlorite
Storage Tank
12125001
Solution Prepara-
tion Tank
12125002
Agitator
12125003
Solution Feeder
12125004
Component Failure
Function Mode
Same as 12124002
Same as 12124002
Mix hypochlorite solution Power loss.
and maintain solution form.
Breakage due to
deterioration.
Failure
Kffect
Detection
Means
Remarks
Proportional feed hypo-
chlorite solution into
water.
Power loss .
Feeder failure.
Loss of mixer.
Loss of mixer.
Loss of disinfection.
Loss of disinfection.
Power failure.
Inspection and pre-
ventive maintenance.
Power loss. Power may be electric,
mechanical (shaft), water
power, pheumatic, or
auxiliary (gas engine).
Inspection and water Hypochlorites are
tests. corrosive and materials
must be chosen accord-
ingly.
Figure 1-4, (Continued)
-------
(sheet 9 of 17)
Operation Name: Predisinfeet With Chlorine Dioxide
Operation Number: 12126000
Subfunction: Predisinfeet Raw Water 12120000 Function: Pretrcat Raw Water 12100000
Subsystem: Treat Raw Water 12000000
GO
tS3
Component
& Number
Sodium Chlorite
."Storage Tank .
12126001
Ceramic Packed
Glass Chlorine
Dioxide Generator
12126002
Chlorine Solution
Feeder
12126003
Component
Function
Same as 12124002
Mix chlorine solution with
sodium chlorite and
generate chlorine dioxide.
Feed 500 ppm chlorine
solution to generator.
Failure
Alode
Improper mixing.
Same as 12122001
Failure
Effect
Decrease in generation
of chlorine dioxide and
loss of disinfection.
Detection
Means
Water tests •
Monitoring Operation
of generator.
Remarks
Sodium chlorite is
explosive creating
storage and handling
problem.
Chlorine dioxide
Feeder
12126004
Feed chlorine dioxide to
raw water through diffuser.
Same as 12122001
This treatment is good for
removing phenols because
of high reaction rates.
See Note (2) under 12121000
Figure 1-4. (Continued)
-------
Item Name: Pretreat Raw Water - Function
(sheet 10 of 17)
Item Number: 12100000
12130000 Plain Settle Raw Water
I
CO
CO
Item Name
& Number
Plain Settle Flaw
Water
12130000
Component
Function
Reduce heavy sediment
loads prior to subsequent
treatment processes such
as coagulation.
Failure Failure
Mode Effect
Design and installation Overloading of subse-
such that flow is too fast, qucnt treatment pro-
turbulent, or length of cossi-s with heavy
settling basin too short to sediment loads.
allow proper settling.
Operating at too high flow Same.
rates to achieve settling'
Algae growth in basin or Taste and odor prob-
reservoir. lems are created.
Detection
Means
Flow rate measurement
through basin. Look for
turbulent flow. Samples
show heavy sediment
content in effluent.
Same.
Visual plus testing.
Remarks
Allow sufficient space between
influent, even flow (settling),
and effluent sections of basin.
It is better to have redundant
basins so that peak loads will
not exceed settling rates. This
also facilitates cleaning and
maintenance.
Figure 1-4. (Continued)
-------
Item Name: Pretreat Raw Water - Function
Item Number: 12100000
12140000 Aerate Raw Water
(sheet 11 of 17)
Item Name
&• Number
Aerate Raw Water-
Subfunction
12140000
Component
Function
Reduce CC>2.
Reduce taste and odor
producing substances,
remove substances that
interfere with subse-
quent treatment processes.
Oxidiv.p iron manganese,
hydrogen sulfide, and
organic matter.
Failure Failure
?.1oi;!e Kfl'ect
Kquipment failure.
Short circuit of water
flow around aeration
process.
Contamination from
airborne matter.
Excessive aeration may
cause adverse effects on
iron and manganese
removal if low pH is
created.
Increased dissolved
oxygun content in water.
Overload process either Loss of function due
because of failure, deg- to overload.
radation or- peak demand.
Loss of oxygen contact
time.
Detection
Means
Increased corrosive- Water test. Proper
ni-ss. Loss of function design. Inspection and
and exceed water prevention of channel
quality criteria. failure •
Contamination of
water supply.
Loss of function if
removing iron and
manganese.
Increased corrosion.
Proper design. Cover
over process. Use
filtered supply.
Dissolved oxygen con-
tent analysis of water.
Dissolved oxygen con-
tent analysis of water.
Monitor demand and load
on system.
Remarks
No common wall boundaries
or direct overflow to finished
water.
Chlorinate prior to aeration
to aid oxidation; however
this creates loss of chlorine
and increases costs.
Provide standby redundant
equipment in order to meet
overloads, shutdown for
maintenance or repair.
Figure 1-4. (Continued)
-------
Item Name: Soften Water
Item Number: 12210000
Treat Water 12200000. Treat Raw Water 12000000
(sheet 12 of 17)
Item Name
& N'urr.b°r
Lime-Soda-Ash
Softening
12211000
I
W
01
Ion Exchange
12212000
Component
Function
Add CaO to remove COg
as CaCO;j and to oxidize
and precipitate iron and
manganese in raw water
Operation involves lime
feed, rapid mix, floccu-
lation, sludge removal
(rapid sand filtration and
stabilization would follow).
Failure
Mode
Failure
Effect
Trace elements in lime. Water contamination.
Lime feeder clogged.
Sludge removal equip-
ment failure.
Improper floe mix and
formation.
Remove CaCO3 and other Clogging.
ions by displacement.
Loss of lime feed.
Failure of operation.
Loss of operation.
Decreased sedi-
mentation effective-
ness and increased
clogging of filter.
Frequent flushing
requiring more
off-line (down) time.
Detection
Means
Analysis of lime to
check quality.
Periodically inspect and
clean lime feed equip-
ment.
Loss of equipment
operation.
Visual inspection can
confirm proper floe
formation. Jar tests
should be performed
for proper chemical
dosage.
Increase in loss of head
across resin bed.
Remarks
Use turbidimeter to check
variance in raw water
turbidity, then perform
jar tests and correlate
to determine proper
chemical dosage control-
A standby unit is required
for operation during
regeneration.
Figure 1-4: (Continued)
-------
Item Name: Coagulate. Flocculate, and Sediment
Item Number: 12220000
Treat Water 12200000. Treat Raw Water 12000000
(sheet 13 of 17)
Item Name
& Number
Add chemicals and
Rapid Mix
12221000
I
co
Oi
Coagulate and
Flocculate
12222000
Sedimentation
12223000
Component
Function
Attain full mixing and
contact of suspended
solids with flocculant
agent.
Failure
Mode
Failure
Effect
Attain complete envelop-
ment of suspended
particles within floe.
Reduce amount of settle-
able solids.
Flocculent feeder failure. Failure of operation.
Raffled mixing basin
having wide flow vari-
ations •
Mechanical mixer
failure.
Excess alum.
Flocculator failure-
Baffle failure.
Flow control.
Sludge removal equip-
ment failure.
Sludge accumulation.
Not suitable for
mixing. Reduced
efficiency.
Loss of operation.
Destroys floe and
carries into finished
water.
Loss of agitation and
coalescence of parti-
cles.
Velocity flow occurs
which shears floe and
prevents coalescence.
Insufficient time for
settling-
Shutdown of basin for
cleaning.
Take basin out of
service for cleaning-
Detection
Means
Alarm; inspection of
feeder.
Flow measurement.
Inspection.
Remarks
Standby feeder necessary •
for continuous operation.
Baffled basins not suitable
where flow varies widely.
Install over capacity so that
standby, mixing capacity is
available.
Monitor aluminum
content in finished water.
Perform jar tests and
monitor turbidity to
control alum dosage
rate.
Visual inspection. A
proper floe can be seen
in the water.
Visual inspection. A
proper floe can be seen
in the water.
Flow monitoring.
Operations; visual )
inspection. >
Measure sludge depth.)
Paddle wheel flocculators
are used Cor agitation.
Care must be taken in
design to prevent this.
Standby equipment is
required in order to
remove a basin from
service-
Figure 1-42 (Continued)
-------
(sheet 14 of 17)
Item Name: Filter Water
Item Number: 12230000
Treat Water 12200000. Treat Raw Water 12000000
Item Name
& Number
Gravity Filter
12231000
Component
Function
Separate suspended and
colloidal impurities from
water by passing through
a porous medium-
I
Oi
-3
Pressure Filter
12232000
Same as 12231000 above
Failure
Mode
Clogging.
Breakthrough.
Media disruption due
to high backwash rate-
Controls failure such
as control of flow
(flow controlled).
Filter breakthrough
at corners.
Failure
Effect
More frequent back-
washing.
Failure and passage
of contaminated
water.
Disruption of filter
bod and filter must
be removed from
service and restored.
Detection
Means
High loss of head through
filter.
Loss in head. Increased
alum in water and
increased chlorine
demand.
Media dislodgement
during backwash. Care
must be exercised when '
backwashing. Could
lead to breakthrough.
Filter must be Operation of filter.
removed from service Loss of head •
until controls restored.
Loss of filtration.
• Buildup of floe or
surface coating in
corners of filter.
Notes: Filtration is probably the single most important process in treating water sources of
poor quality. When coupled with pretreatment, filtration removes over 99 percent of
bacteria (post chlorination controls remainder); over 98 percent of polio virus removed
by flocculation and filtration, turbidity reduced to less than 0.2 Jackson Units by
filtration; color iron, manganese are easily removed with proper pretreatment; large
microorganisms readily removed.
Remarks
.Standby filter
capacity is
necessary to
provide redun-
dancy for
removing a
filter from
Media should be
periodically removed,
underdrains cleaned.
and media restored.
Figure 1-4. (Continued)
-------
co
oo
(sheet 15 of 17)
Item Name: Post Disinfect Water
Item Number: 12230000
Treat Water 12200000. Treat Raw Water 12000000
Item Name
& Number
12241000
through
12246000
Component
Function
Failure
Mode
Failure
Effect
Detection
Means
Remarks
Same as 12121000 through 12126000
Figure 1-4^ (Continued)
-------
(sheet 16 of 17)
Item Name: Provide Special Treatment
Item Number: 12300000
Treat Raw Water 12000000
I
00
CO
Item Name
& Number
Dechlorinate Water
12311000
Component
Function
Ozonate Water
12312000
Treat with
Carbon
12321000
Add Fluoride to
Water
12331000
Failure
Mode
Failure of treatment.
Remove excess chlorine
following treatment having
super chtorination to
render the water more
palatable. Methods
include adding 50%, aera- Overdosage.
tion, treatment using
activated carbon.
Diffuse in water to
disinfect.
Add activated carbon
to remove tastes and
odors, phenolic com-
pounds, toxic chemicals
excess chlorine.
Additive to fight tooth
decay-
Failure
Effect
Detection
Means
Remarks
Super chlorinated water Monitor treatment pro-
enters distribution sys- cess. Test finished
tern. It can irritate eyes water. Monitor Cl2
and be unpalatable. residual.
Loss of ozone generating
equipment due to failure
or to power loss.
Reduced (or loss)
chlorine residual.
Loss of disinfection.
Failure of feed equipment. Loss of control.
Possible contamination
of water.
Fluoride below or above
limits deleterious to
dental health due to flow
proportioner failure.
Exceed limits causing
dental deterioration.
Monitor chlorine residual.
Alarm should be pro-
vided. Test water.
Alarm and monitoring
system. Test water.
Alarm and monitoring
system. Test water
Colorimetric tests.
Notes: Records should be maintained for all chemical additions:
(a) Flow and volume of water treated
(b) Amount of chemical used
(c) Theoretical dosage
(d) Machine setting and actual dosage
(e) Chemicals on hand and ready for use
(f) Concentration of chemicals
Figure I-4.i (Continued)
-------
(sheet 17 of 17)
Item Name: Treat Raw Water
Item Number: 12000000
Item Name
& Number
Special
Considerations
12000000
Component
Function
Design.
Failure
Mode
Failure
Kffect
Detection
Means
i
£>•
O
Failure of common walls Contamination of water. Visual examination
where higher qviality
water could be contami-
nated by lower quality
water.
Bypass of treatment
plant.
Treatment facilities
contaminated by air-
borne pollutants.
Sanitary (toilets, etc.)
equipment failure.
Piping failure of low
quality water.
Loss of treatment,
possible distribution
of contaminated water.
Water contamination.
Water contamination.
Water contamination
if tow quality main
could fail and damage
higher quality main or
dump water into higher
quality water.
Proper design should
preclude occurence.
Increased chlorine
demand or loss of
residual.
Visual examination.
Loss of chlorine
residual.
Air monitoring.
Increased chlorine
demand or loss of
residual.
Visual inspection.
Increased chlorine
demand or loss of
residual.
Visual inspection.
Loss of chlorine
residual.
Remarks
High quality water should '
be above lower quality
water where common
divisions occur.
Common walls should
not be allowed in
proper design.
Proper design and main-
tenance should preclude
existence in plants where
raw water must be treated
to meet standards.
Proper design should have
covered facilities.
Proper design should isolate
sanitary equipment from
treatment processes and
water so that failure would
not cause contamination of
water.
If low quality and high
quality mains must be
routed through same
area, route high quality
above low quality with
maximum separation.
Never route low quality
water over higher quality
water.
Figure .1-4. (Continued)
-------
13 DISTRIBUTE TREATED -
WATER
-131 CONVEY TREATED WATER
L132 STORE TREATED WATER-
-c
311 CONVEY TO STORAGE -
1312 CONVEY TO DEMAND-
-1321 STORE IN TANKS-
-1322 STORE IN RESERVOIRS-
-C
-C
-C
41
13112 PUMP FEED TO STORAGE
1312) GRAVITY FEED TO DEMAND
13122 PUMP FEED TO DEMAND
13211 ELEVATED TANKS
13212 GROUND-LEVEL TANKS
13221 LINED RESERVOIR
13222 EARTHEN RESERVOIR
Figure 1-5.. Structure and Matrix for Distribution of Treated Water, Subsystem 13
-------
(sheet 1 of 6)
Item Name: Distribute Treated Water
Item Number: 13000000
I
^
to
Item Name
& Number
Convey Treated
Water to Storage
by Gravity
13111000
Component
Function
Transport treated water to
storage under gravitational
force to maintain pressure.
Failure
Mode
Failure
Effect
Conduit or pipe leakage Inflow of contaminated
or failure. Valve failure water.
Draft such as fire pump
causing loss of pressure.
Loss of control. Possible
contamination during
repair. Also, backflow
could occur if check
valve failed.
Detection
Means
Inspection and pressure
testing of conduit or
pipe. Excess leakage
should not be allowed.
Periodically check
valves for proper
operation.
Sludge in pipe or con-
duit from settling of
solids out of water.
Contamination or slime
in pipe or conduit.
Flooding.
Corrosion.
Loss of flow. Inspection.
Bacterial contamination,
odors, and tastes.
Contamination.
Equipment failure, added
metal content to water
(may contaminate).
Monitor chlorine resid-
ual. Test water.
Pipe or conduit should
be installed above flood
levels to prevent back-
flow.
Monitoring pH,
alkalinity, and inspec-
tion results. Test
water.
Remarks
Proper design should not '
have treated water passing
below lower quality water
or in adjacent walls where
contamination might flow
into finished water if
failure occurred. Sewers
to be 10 away. Repairs
should have flushing and
disinfection procedures to
prevent contamination. Use
proper materials. Do not
use materials that support
the growth of pathogenic
organisms. Materials should
meet AWWA specs.
Periodic flushing necessary to
remove settled sludge.
Provide chlorine residual in
water. Minimum is 4 mg/1
for 30 min.
Proper design should have
excess pressure in pipe or
conduit to prevent flooding
and back flow.
Proper material selection,
proper pH and control of
alkalinity should prevent.
Prevent the occurrence of
dead water pockets.
Figure 1-6, Failure Modes and Effects Analysis
-------
(sheet 2 of 6)
Item Name: Distribute Treated Water
Item Number: i ?nnnnnn
I
t^
GO
Item Name
& Number .
Pump Treated
Water to Storage
13112000
Convey to Demand
by Gravity
13121000"
Component
Function
Pump water to achieve head
required to reach storage
head and supply water.
Furnish water by gravity
using storage head to
maintain pressure*
Failure
Mode
All in 13111000
Pump failure.
Controls failure to turn
pump on at low storage.
Failure
Effect
Loss of pressure.
Loss of pressure.
All shown in 13111000
Note: The rate of failure of distribution mains
depends upon length of installed pipe.
Backflo'.v in low pres- Contamination of supply-
sure area.
Dead ends.
(Continued)
Stagnation and con-
tamination of supply.
Detection
Means
Alarm. Monitoring
operation.
Alarm. Monitoring
operation.
Cross-connection sur-
vey program and pres-
sure test programs for
minimizing the chance
of backflow and low
pressure occurrence.
Remarks
Sufficient standby pump
capacity should be provided.
Sufficient displays should
be provided for monitoring
the operation.
Proper system design
should preclude low
pressure which might
suck (or siphon) con-
tamination into distri-
bution system. This
use of vacuum breakers
at consumer connections,
back pressure valves,
and check valves would
lessen chances of
occurrence.
A flushing procedure
should be followed to
periodically flush dead
ends and test water
quality-
Figure 1-6. (Continued)
-------
(sheet 3 of 6)
Item Name: Distribute Treated Water
Item Number: 13000000
Item Name
& Numb°r
Component
Function
13121000 (Continued)
Failure
Mode
Clogging.
Failure
Effect
Loss of capacity and
higher susceptibility
to low pressure
occurrence.
Detection
Means
Increased head pres-
sure in a main.
boss of pressure.
Remarks
Proper chemical controls '
and flushing program should
be followed.
Note: (1) A plumbing code should prohibit connections which might
allow discharge or suction of unknown or questionable
liquids into the water supply. Blow-off connections to
s'ewers or sewer manholes should be prohibited.
(2) A system should be provided with sufficient bypass and
blow-off valves to make necessary repairs without undue
interruption of service over any appreciable area.
Pump Water to
Demand
13122000
Pump water to achieve
head and volume to
supply demands.
All in 13121000
Note: (1) A plumbing code should prohibit connections which
might allow discharge or suction of unknown or
questionable liquids into the water supply. Blow-off
connections to sewers or sewer manholes should be
prohibited.
The rate of failure of distribution mains depends upon
the length of installed pipe.
Pump failure.
Controls failure to
turn pump on to meet
demand.
(Continued)
Loss of pressure and
capacity.
Loss of pressure and
capacity.
Alarm. Monitoring
operation.
Alarm. Monitoring
operation.
Sufficient standby pump
capacity should be provided.
Sufficient display information
provides operator with
monitoring instrumentation
to display problem occurrence.
Figure 1-6. (Continued)
-------
(sheet 4 of 6)
Item Name: Distribute Treated Water
Item Number: 13000000
Item Name
& Number
Component
' Function
Failure
Mode
Failure
Effect
Detection
Means
Remarks
13122000 (Continued)
Backflow in low pres-
sure area.
Possible contamination
of supply.
I
(^
01
Dead ends.
Clogging.
Same as 13121000.
Same as 13121000.
Store Treated
Water in Elevated
Tanks
13211000
Provide storage capacity
for treated water at
sufficient height to pro-
vide head sufficient to
maintain system pres-
sure at 20 psi minimum.
Tank rupture (freezing Loss of water.
of riser or failure)
Corrosion.
Contamination of water
by corrosion products.
Cross-connection sur-
vey program and pres-
sure test programs for
minimizing the chance
of backflow and low
pressure occurrence.
Proper system design should
preclude low pressure which
might suck (or siphon) con-
tamination into the distribution
system. The use of vacuum
breakers at consumer con-
nections, back pressure valves.
and chetk valves would lessen
chances of occurrence.
Proper inspection prevents
rupture. Means to prevent
freezing should be installed
where freezing temperatures
of sufficient lowness and
duration occur.
Control pH, dissolved Proper material selection,
oxygen, monitor proper construction, proper
inspection results. Test maintenance, proper controls
water. will prevent failure. A
periodic tank cleaning and
coating is required.
Inspection and testing.
Figure 1-6. (Continued)
-------
Item Name: Distribute treated water
Item Number: 13000000
(sheet 5 of 6)
Item Name
& Number
Component
Function
13211000 (Continued)
Failure
Mode
Level controls failure.
Bacteria in water.
Failure
Kffcct
Maintain improper tank
level control. Possible
loss of reserve (excess)
water storage.
Contamination of water.
Store Treated
Water in Ground
Level Tanks
13212000
Store Treated
Water in Lined
Reservoir
13221000
Same as 13211000
Provide storage capacity
for treated water at
sufficient head to main-
tain system pressure at
20 psi minimum .
Note: A good maintenance
program is required for
clearwells and other lined
reservoirs for finished
water.
Reservoir rupture.
Bacteria in water.
Loss of water.
Water contamination.
Level controls failure. Possible loss of water.
Contamination.
Water failure.
Note (2)
Detection
Means
Remarks
Compare head pressure Level controls are usually'
and level control connected to controller for
actuation points. Peri- pump that fills tank.
odically inspect controls
and calibrate.
Water tests for bacteria
and chlorine residual.
Booster chlorination is
required where bacteria
occur in stored finished
water. Chlorine residual
is 0. 4 mg// for 30 min
minimum.
Inspection and testing.
Test water for bacteria
and chlorine residual.
Note (1) below
Booster chlorination may
be required. Chlorine residual
should be 0. 4 mg/1 for
30 min minimum.
Reservoir should be covered.
Compare head, pres- Level controls are usually
sure,and level control connected to controller for
actuation points. Peri- pump that fills reservoir.
odically inspect controls
and calibrate.
No sewer within 50 feet
with a below-ground
floor. Ten feet all others.
Figure I~6. (Continued)
-------
(sheet 6 of 6)
Hem Name: Distribute Treated Water
Item Number: 130000'00
Itom Name
& Kumber
13221000 (Continued)
Component
Function
Failure
Mode
Slime or sediment in
reservoir.
Failure
Effect
Tastes and odor.
Detection
Means
Visual inspection.
Remarks
Chlorine residual should
minimize occurrence.
Periodic cleaning is
required.
Store Treated
Water in Earthen
Reservoir
13222000
Same as 13221000 above
plus:
Aquatic vegetation
growth.
Taste and odors.
Visual inspection.
Chlorine residual should
minimize. Periodic treat-
ment with copper sulfate
and cleaning is required.
Note: (1) Open finished water reservoirs should not be permitted. In event
they are used, chlorine residuals must be maintained or booster
chlorination facilities are required to insure complete disinfection
before distribution to the first customer.
(2) The surface should be graded to drain surface water away from the
reservoir and the area should be secured from public or animal
access by fencing. Manholes should be elevated and have a water-
tight cover. Vents should be inverted and screened (No. 24 mesh)
to prevent rain, insects, or animals from entering.
General notes for distribution subsystems:
Bacteriological quality hazards
a. Insufficient treatment at point of production
b. Cross-connections
c. Improperly protected distribution system storage
d. Inadequate disinfection of mains
e. Unsatisfactory construction of mains, including improper joint-packing material
f. Close proximity of sewer and water mains
g. Improperly constructed, maintained, or located blow-off, vacuum, and air relief valves
h. Negative pressures in the distribution system
i. Dead ends in distribution mains
Figure 1-6^ (Continued)
-------
I
rf^
oo
14 PROVIDE WATER
QUALITY SURVEILLANCE—
r-141 TEST TREATED WATER FOR
BACTERIA
-142 TEST TREATED WATER FOR
CHEMICAL CONTENT
-143 TEST TREATED WATER FOR -
PHYSICAL AND AESTHETIC
CHARACTERISTICS
M44
TEST TREATED WATER FOR
OTHER CONSTITUENTS-
-1411
UST TREATED WATER FOR BACTERI-
OLOGICAL CONTENT
-1421 TEST FOR MINERAL CONTENT-
-1422 TEST FOR ORGANIC CONTENf-
-1431
TEST FOR TASTE, ODOR,
TURBIDITY, AND COLOR"
-1441 TEST FOR RADIOACTIVITY-
-1442
TEST TO MAINTAIN CONTROL
OF TREATMENT
14111 SAMPLE FOR BACTEKIA TEST
14112 TEST FOR BACTERIAL CONTENT
-14211 SAMPLE FOR MINERAL CONTENT TESTS
-14212 TEST FOR MINERAL CONTENT
-14221 SAMPLE FOR ORGANIC CONTENT TESTS
-14222 TEST FOR ORGANIC CONTENT
{
14311
SAMPLE FOR PHYSICAL AND AESTHETIC
CHARACTERISTICS
-c
14312 TEST FOR PHYSICAL AND AESTHETIC
CHARACTERISTICS
14411 SAMPLE FOR RADIOACTIVITY TEST
14412 TEST FOR RADIOACTIVITY CONTENT
-14421 TEST FOR CHLORINE RESIDUAL
-14422 TEST FOR HARDNESS
14423 MEASURE PH
L14424 MEASURE TEMPERATURE
Figure 1-7.. Structure and Matrix of the Water Quality Surveillance Subsystem
-------
(sheet 1 of 2)
Item Name: Provide Water Quality Surveillance
Item Number: 14000000
CD
Item Name
& Number
Sample for Bacteria
Test
14111000
Test for Bacteria
Content in Samples
1411200C
Sample and Test
Water for Chemical
(Mineral & Organic)
Content
14200000
Component
Function
Provide adequate sampling
to statisticallv provide
assurance of not exceeding
drinking \vater standards
in the entire distribution
system.
Failure
Mode
Samples taken too close
to treatment.
Failure
Effect
Detection
Means
Remarks
Entire distribution SYS- Independent survey of
tcm not covered
meaning far points in
system may not meet
bacteriological limits.
Sampling container not Contamination of
properly cleaned, sample sample resulting in
insufficiently protected, erroneous analytical
sample not tested ns soon results.
as possible.
Insufficient number of Possibility that statis-
samples per month. Lack tical assurance of good
of random sampling and quality cannot be made.
sampling by Public
lie." 1th Service or other
service organi/ations.
Comparison of sample
results with previous
test results and re-
sample for retesting.
Monitor sampling to
insure correct num-
ber are taken. Check
Perform test for bacteria Test procedures which
in accordance with standard are not as rigorous as
methods. Laboratory should standard methods.
be certified
good coverage of system. Also.l'HS requirements population frequently
to insure correct
number specified.
Survey of laboratory
procedures, media,
other chemicals, and
comparison with
standard methods.
are not met.
Possible nonidenti-
fication of bacteria
when water is contami-
nated .
Test water at sufficient Insufficient sampling and
intervals to ensure meeting testing to statistically
the drinking water standards, ensure water quality.
Sampling and testing not
in accordance with stan-
dard methods.
Possible water contami- Statistical analysis of
nation. all test results.
Possible erroneous
results.
Survey of laboratory
methods and proce-
dures.
If bacteria are found
in water In varying
numbers, it becomes
very important to
assure meeting
requirements.
Laboratory should be
certified.
Each test result should
be compared with pre-
vious results to see if
quality is deteriorating.
Laboratory should be
certified.
Figure 1-8. Failure Modes and Effects Analysis
-------
Item Name: Provide Water Quality Surveillance
Item Number: 14000000
(sheet 2 of 2)
Item Name
& Number
Component
Function
Test Water for Test for turbidity, taste.
Physical and Aesthetic odor, and color.
Properties
14300000
Test tor Other
Constituents
14400000
Test for radioactivity.
Test to maintain control
of treatment-and distri-
bution.
I
CJi
O
Insufficient sampling and
testing to statistically
ensure water quality.
Insufficient sampling and
testing to statistically
ensure water quality.
Failure to adjust treat-
ment to meet variations
in raw water; failure to
monitor treatment to
ensure all processes are
functioning properly from
raw water intake to the
farthest point in the dis-
tribution.
Failure
Effect
Possible water
contamination.
Possible water
contamination.
Inadequate treatment
inefficient treatment,
contamination by over-
treating.
Detection
Means
Statistical analysis
of all test results.
Statistical analysis
of all test results.
Operational control
tests are for:
alkalinity, aluminum
chloride, chlorine
residual, color,
fluoride, hardness,
iron, jar tests, man-
ganese, pH, taste and
odor, turbidity.
Remarks
Instruments are
available for continuous
monitoring of turbidity.
Instruments are
available to measure
radioactivity.
Frequency of tests
should be such to assure
proper treatment of
water as its 4uality
varies and to ensure
proper control of the
water system.
Figure I-8. (Continued)
-------
-151 PROVIDE UTILITIES-
15 PROVIDE SERVICES-
I
Or
1511 PROVIDE POWER-
-c
15111 PRIMARY POWFR
15112 AUXILIARY POWER
15121 SANITARY EQUIPMENT
r
-L 15122 HABIIABILITY ITEMS
152 OPERATE AND MAINTAIN
EQUIPMENT
1512 PROVIDE SANITARY AND HABIT-
ABILITY ITEMS
r-15211 PREVENTIVE MAINTENANCE SCHEDULE
1-1521 PERFORM PREVENTIVE MAINTENANCE-j-15212 PREVENTIVE MAINTENANCE LABOR
L-15213 PREVENTIVE MAINTENANCE INSTRUCTIONS
15221 CORRECTIVE MAINTENANCE LABOR
15222 CORRECTIVE MAINTENANCE INSTRUCTIONS
- 1522 PERFORM CORRECTIVE MAINTENANCE
-c:
L1523 OPERATE EQUIPMENT
-15231 CONTROL EQUIPMENT
15232 MONITORING EQUIPMENT
-15233 ALARM SYSTEM
- 15234 OPERATING SCHEDULE
-15235 OPERATING LABOR
-15236 OPERATING INSTRUCTIONS
Figure 1-9. Structure and Matrix of Services Subsystem
-------
(sheet 1 of 6)
Item Name: Provide Utilities
Item Number: 15100000
ISflOOOOQ
Item Name
& Number
Provide Power
15110000
Component
Function
Supply primary electrical
power.
Supply auxiliary electrical
power.
Failure
Mode
Power loss unless
secondary or auxiliary
power supply is provided.
Power loss of primary
and auxiliary power
sources.
Failure
Effect
Loss of electrical
equipment.
Loss of electrical
equipment.
Detection
Means Remarks
None for power failures.
Interruptions for service
maintenance can be fore-
cast.
None for power failures.
Interruptions for service
maintenance can be fore-
cast .
I
Oi
CO
Figure I-10. Failure Modes and Effects Analysis
-------
Item Name: Provide'Sanitary and Habitabilitv Items
Item Number: 15120000
Provide Utilities 1510000, Provide Services 15000000
(sheet 2 of 6)
01
CO
Item Name Component Failure
& Number Function . Mode
Sanitary Equip- Provide facilities for dis- Overflowing or pipe
ment posing waste and sewage failure.
151210000 for personnel and opera-
tions such as laboratories,
cleaning operations,
drains.
Human Provide work environments Conditions hindering
Engineering which foster effective proce- human performance.
15122000 • dures, work patterns, and
personnel safety and which
minimize discomfort,
distraction, and any other
factors which degrade human
performance or increase
error. The design should
minimize personnel and
training requirements within
limits of time, costs, and
performance trade-offs.
Failure
Effect
Contamination of water
unless located so as to
prevent contamination.
Inefficient operation
and possible safety
hazards.
Detection
Means
Inspection to check
flow paths and dis-
tance removed from
.system operations.
Inspection of facilities
to assure space and
environment suitable
for man to work in.
Standardization of con-
trols, labeling, and
arrangement are com-
mon functions '.o look
for. Alarm systems.
Fail-safe devices for
hazardous operations.
Location and arrange-
ment suitable for man
to work in to maintain
the system.
Remarks .
Proper design dictates
that sanitary facilities
be designed so that
failures will not cause
water contamination.
Many s.ubjective attributes
can be used to measure the
human engineering aspects
of a system: clearances,
location of controls within
easy reach and with room
to operate, standard controls,
safety devices, alarms,
fail-safe devices, etc.
Figure I-10.(Continued)
-------
(sheet 3 of 6)
Item Name: Perform Preventive Maintenance
Item Number: 15210000
Operate and Maintain Equipment 15200000, Provide Services 15000000
Oi
Item Name Component
& Number Function
Schedule Provide a checklist for
15211000 guiding, planning, and
following the performance
of maintenance designed
to prevent equipment
failure and enhance
efficient system operation.
Labor Personnel to perform pre-
15212000 ventive maintenance tasks.
This may be determined
by the makeup of plant
equipment and the require-
ments for maintaining
equipment.
Instructions Provide easy to read step
15213000 by step procedures for per-
forming maintenance in a
form usable and available
to personnel. The instruc-
tions should state person-
nel skill levels required
to perform the maintenance
tasks.
Failure
Mode
No schedule or records
to provide check of main-
tenance performed.
Lack of training and
experience with equip-
ment. Lack of certi-
fication.
Instructions not avail-
able, not easy to follow,
not easily handled when
performing maintenance.
Failure
Effect
Detection
Means
Possible neglect to per- Check for schedule and
form all maintenance record keeping to
which should be done ensure all maintenance
resulting in higher prob- is being performed.
abilities of system
degradation and failure.
Possibility of poor
maintenance and
induced equipment
failures.
Possible neglect to
perform maintenance
in correct manner
leading to higher
probability of system
degradation and failure.
The possibility of
creating safety hazards
exists.
Check length of
experience of main-
tenance personnel,
amount of training
received, and skill
levels achieved.
Remarks
This is subjective
since the adequacy
of a preventive
maintenance pro-
gram must also be
examined.
The skill titles may
be those listed in the
U. S. Department of
Labor Dictionary of
Occupational Titles.
Check for availability
of instructions, intelligi-
bility, and ease of using
when performing main-
tenance. Are equipment
manuals available?
Figure I-l'O.(ContinUed)
-------
i
en
01
Iterr. Name: Perform Corrective Maintenance
Item Number: 15220000
Operate and Maintain Equipment 15200000, Provide Services 15000000
Item Name
& Number
Labor
15221000
Instructions
15222000
Component
Function
Personnel to perform
corrective maintenance.
This may be determined
by the makeup of plant
equipment, probability
of failure, and equipment
complexity.
Same as 15213000
Failure
Mode
Lack of training,
experience, or skills to
perform maintenance.
Lack of certification-
Failure
Ki'fcct
Possibility of poor
maintenance leading to
recurring and induced
equipment failure.
Detection
Means
(sheet 4 of 6)
Remarks
Check experience and
skill levels of person-
nel. Are they sent to
training schools?
What amount of training Titles.
received and skill
levels achieved?
The skill titles may be
those used in the U.S.
Department of Labor
Dictionary of Occupational
Figure I-10 (Continued)
-------
Item Name: Operate Equipment
Item Number: 15230000
Operate and Maintain Equipment 15200000. Provide Services 15000000
(sheet 5 of 6)
i
Ol
Item Name
& Number
Control Equip-
ment
15231000
Monitoring
Equipment
15232000
Alarm System
15233000
Operating
Schedule
15234000
Component
Function
Provide control system
motive power (pneumatic,
hydraulic, electrical).
Provide control and
monitoring displays for
operating the system:
dial indicators, record-
ers, lights, meters,
gages, etc.
Provide alarms for
critical and hazardous
operations to alert
operators to occurrence
of failure or ha/.ard.
Such areas include
chlorine room monitoring,
Cl2 tank weight, fluoride
monitoring, tank levels,
power source, fire, etc.
Provide sequence of
operation of system (e.g.,
minimum load, avg load,
full capacity), rotation
of equipment, correlation
to preventive maintenance
requirements.
Failure
Mode
Failure of control of
motive power.
Failure Detection
Effect Means
Failure of remote Alarms.
controls, manual con-
trol becomes necessary.
Failure of instrumentation
may cause operator to
make a control error.
Lack of alarms.
Lack of schedule.
Mnloperation of system; Comparative Instru-
loss in water treatment mentation to check
capacity. instrument perfor-
mance.
fla/.ards to water
contamination and to
personnel safety.
Remarks
Control systems should
have redundancies built in
for high failure rate equip-
ment.
Operating instructions should
provide for procedures to com-
pare various process readings
which would provide check on
instrument performance.
Inspection of system
to determine hazardous
areas and presence or
absence of alarms.
Operation of system in Doea schedule exist ?
an inefficient manner or Are records kept?
possible early degrada-
tion of portion of system
due to over-operation and
under-maintenance.
'Proper sequential operation
and rotation of equipment
leads to equipment
longevity.
Figure I-10 (Continued)
-------
Item Name: Operate Equipment
Item Number: 15230000
Operate and Maintain Equipment 15200000, Provide Services 15000000
(sheet 6 of 6)
Item Name
& Number
Operating Labor
15235000
I
Ul
Operating
Instructions
15236000
Component
Function
Failure
Moile
Personnel to operate sys- Lack of training, experi-
tem. Determine by system encc, skills, or certi-
clesign and requirements in fication'of operators.
emergencies.
Provide easy to read step
by step procedures for
operating the system in
all operating modes from
low capacity to full
capacity and emergency
control.
Instructions not avail-
able, not posted, not
easily obtained when
needed.
Failure
Effect
Possible maloperation
of system. Possible
poor operation leading
to early wearout and
induced equipment
failure.
Possible failure of
water system to meet
quality and demand
requirements.
Detection
Means
Check experience,
skills, certification.
Are operators sent
to specialized
training? What
training and experi-
ence achieved ?
Are operating instruc-
tions available to
operators? Are they
simple and straight-
forward? Are they
within the operators
watch station? Do they
cover all operational
modes including
emergency procedures ?
Remarks
The skill titles may
be those used by the
U. S. Department of
Labor Dictionary
of Occupational Titles.
An evaluation of plant
operation in relation
to operator training
and experience may be
required to rate this.
A qualitative evaluation
may be necessary to
determine if the
instructions are
followed if available.
Figure I--10 (Continued)
-------