EPA R2-73084b
June 1973 Environmental Protection Technology Series
Field Investigation of Emissions
from Combustion Equipment
for Space Heating
(Data Supplement)
\
UJ
0
American Petroleum Institute Office of Research and Monitoring
1801 K Street. NW U.S. Environmental Protection Agency
Washington. D.C. 20006 Washington. D.C. 20460
-------
EPA-R2-73-084b
Field Investigation of Emissions
from Combustion Equipment
for Space Heating
(Data Supplement)
by
R.E. Barrett, S.E. Miller,
and D.W. Locklin
Battelle - Columbus Laboratories
505 King Avenue
Columbus, Ohio 43201
Contract No. 68-02-0251
Program Element No. 1A2015
EPA Project Officer: Robert E. Hall
Control Systems Laboratory
National Environmental Research Center
Research Triangle Park, North Carolina 27711
Prepared for
AMERICAN PETROLEUM INSTITUTE
1801 K STREET, NW
WASHINGTON, D.C. 20006
and
OFFICE OF RESEARCH AND MONITORING
U.S. ENVIRONMENTAL PROTECTION AGENCY
WASHINGTON, D.C. 20460
June 1973
-------
This report has been reviewed by the Environmental Protection Agency and
approved for publication. Approval does not signify that the contents
necessarily reflect the views and policies of the Agency, nor does
mention of trade names or commercial products constitute endorsement
or recommendation for use.
n
-------
FIELD INVESTIGATION OF EMISSIONS
FROM COMBUSTION EQUIPMENT
FOR SPACE HEATING
(Data Supplement)
FOREWORD TO DATA SUPPLEMENT VOLUME
The purpose of this Data Supplement Volume is to record individual data points and
plots in greater detail than is practical in the main report volume. It is intended for use in
conjunction with the main report volume by researchers who wish to refer to individual data
points.
Readers are referred to the main report for information as to objectives, selection of
units, measurement procedures, data averages, and interpretations.
This volume contains the emissions data, plots of emissions versus CO2, computed
emission factors, and emission concentrations corrected to 3 percent O2 in the flue gas. The
material is arranged as follows:
Appendix G - Data for Residential Units (pages G-l through G-66)
Appendix H - Data for Commercial Boilers (pages H-l through H-110)
Appendix I - Calculated Emission Factors for Residential Units (pages 1-1 through 1-20)
Appendix J — Calculated Emission Factors for Commercial Boilers, (pages J-l through J-24)
Details necessary for interpretation of these data and results are presented below.
Appendix G. Data for Residential Units (Pages G-l Through G-66)
Appendix G contains data on Phase II Residential Units 23 through 35 for the "as-
found", "tuned", and "reference fuel" conditions for the cyclic and varied-air runs.
For both cyclic iruns and varied-air runs, data are presented to define the combustion
conditions (Bacharach smoke number, CO2, and O2) and corrected gaseous emissions* (CO, HC,
NO, and NOX). For the cyclic runs, participate emission loadings of the flue gas are presented
*Corrections for interferences were made as follows:
True CO (ppm) = NO measured with NDIR (ppm) -1 25-CO2 (%) - 0.8
CO2 (%)
True NO (ppm) = NO measured with NDIR (ppm) —
C02(%)
True NOX (ppm) = NOX measured with NDIR and converter (ppm) =
No correction was necessary when measuring NOX with electrochemical fuel cells (first and second
visits to residential units).
-------
based on measurements using the EPA particulate sampling procedure2. Particulate loadings are
presented for "filterable" particulate (the probe and filter catch) and "total" particulate (includ-
ing the impinger catch). Where available, gas temperatures at the sampling point are reported for
the varied-air runs.
Plots of gaseous emissions as a function of CO2 are also presented for the varied-air runs.
Appendix H. Data for Commercial Boilers (Pages H-l Through H-110)
Appendix H contains data for the Phase II commercial boilers. Data are given for runs
with each of the fuels fired in each boiler and for each load at which the boiler was operated.
Data are presented to define combustion conditions (Bacharach smoke numbers, CO2,
and O2), gas temperatures at the sampling point, corrected gaseous emissions* (CO, HC, NO,
;NOX, and SO2), and "filterable" and "total" particulate loadings based on the EPA procedure2.
Plots of gaseous emissions as a function of CO2 are also presented for each boiler, fuel,
and load.
Appendix I. Calculated Emission Factors for
Residential Units (Pages 1-1 Through 1-20)
Appendix I consists of computer printouts of calculated emission factors (pounds of
pollutant emitted per 1000 gal of oil fired) for gaseous pollutants and "filterable" particulate
and "total" * particulate for both cyclic and varied-air runs on the residential units. Also shown
are the calculated excess-air values and volumes of flue gas generated per pound of fuel. Gaseous
emission concentrations calculated at 3 percent oxygen are shown in the second part of this
appendix.
Appendix J. Calculated Emission Factors for
Commercial Boilers (Pages J-l Through J-24)
Appendix J consists of computer printouts of calculated emission factors (lb/1000 gal of
fuel fired for oil firing and lb/106 cu ft of natural gas for gas firing) for gaseous pollutants for
each boiler, fuel, and load. Also shown are the calculated excess-air values and volumes of flue
gas generated per pound of fuel. Gaseous emission concentrations calculated at 3 percent oxygen
are shown in the second part of this appendix.
"Standards of Performance for New Stationary Sources", Federal Register, Vol 36 No 139 Part II DD 15704
15722, August 17, 1971. ' ' ' ' '
*See footnote, page 1, for interference-correction formulas.
-------
G-l
APPENDIX G
DATA FOR RESIDENTIAL UNITS
-------
Residential Unit
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
! ' '
1 Combustion Conditions
Unit Condition Fuel |smokeNo.la)
As found j HPUK II '
Tuneti j " [Mr.' f0.5j
Second vii" House . 0 . 1 fO. t)
1 Referent j # j fa 2\
co,,x(b'|o,,%
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit 23
Unit Co: -ci.tirn
As foun 1
j
j
Tuned
Tuned
Fuel
House
1
!
House
Reference
Combustion Conditions
Smoke. No.
0. 6
0.3
V.3
7S
\
\
0.3
0,3
0.3
C.H
3.7
8.9
B.i
0.3
0.3
0.0
U
8.7
co2, *
8.1
9.3
9.V
9.7
9.5"
9.9
10. 1
/o.3
xo.5-
/D.6
/O.I
9.3
9.3
9.9
/./
/O.2.
oz.%
9.7
t.l
8.i
8.5-
83
8.7
es
8.*
8.0
7-7
7.6
ff.3
8.3
7.r
7.i
7.3
Stack
Tern para £ure,
F
Gaseous Emissions, ppm
CO
/.
2.
8.
13.
3.
3.
H.
H.
28.
266.
!(,.
3.
f.
H.
1.
89.
HC
3.r
+ o
2.o
2.o
2.3
2.2
2.2
2.2
l.o
/.?
o.f
A3
l.o
/.o
A3
t.o
NO
60.
£9.
$7.
&.
71.
73.
73.
71.
68.
VS.
?8.
73.
7S.
81.
73.
f».
NOX
7y
93.
99.
/07.
9^
/o2.
/of.
107.
91.
/oV.
f07.
78.
80.
67.
80.
70.
9
-------
G-5
Residential Unit _
Condition AS
23
o
o
en
u
a
u
o
to
• Smoke
o CO
I
8 9
C02, percent
10
X HC
A
34- -170
32
30
28- -140
26
24
22
20- -
E
a.
S '"
16
14
12
10
8
6
160
150
•130
120
110
100 E
a.
a
- - 90
4- 80
7O
60
5O
40
30
z
•o
"I
u
4-- 20
2- - 10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-6
9
8
7
6
6
f5
CO
£
O
CO
3
2
1
O
R«>idan«iol Unit 23 _ "mofe
Condition Tv/ltd F...I //«
-------
G-7
8
7
6
.
•
* 5
o
E
o" '® "
I
16-
| 14-
12-
10-
3
6-
4-
we
1
-170
-160
-150
-140
-130
-120
-1 10
-IOO E
a.
a.
- 90 o*
z
•o
- 80 °
o
o
- 70
60
- 5O
- 4O
- 30
- 2O
- 10
0
5
8 9
C02, percent
10
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
Residential Unit
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
/
UP it Condition
As found
Tunas
Second v;i>;
Third vis «
Fuel
Haute
Referents
House
Reference
House
Reference
Combustion Conditions
Smoke No.(a)
O.I (0.3}
0.7 (0.7)
Q.B (t.J)
0.2. (03}
o.l a'o.i-}
0.2/0-5}
d. 7 (0.7)
co?,%«w
71
£9
9.2
ff.8
5.0
7.3
8.1,
or%(b>
12.C
9-0
£S
9.0
3.3
SO.?
9.2
Gaseous Emissions, ppm
CO
222.
H.I
9S
2o.. t
/B.3
W4
/?.?
HC
I2.-Z
3.1
V?
573
//7
28.?
z/.o
NO
39.
7A
69,
5-9.
^2.
«.
o-y.
N0x
78.
76.
71.
3(c)
Partkulate Loading, mg^m
Probe + Filter
3.2
(3.7
12.5-
60. II —
^V. -
5-5. —
(f/. 1 77
Total
n.o
V/0
2A9
—
—
—
Z&.6
fe> Xlr 9-minute point of 4th cycle (5th minute smoke no. shown in parentheses).
(bl Average for "on" period of cycles.
(cl Based on sample collected during six 10-minute cycles.
o
oo
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit 2V
Unit Condition
As found
Tuned
Tuned
Fuel
House
Hou«
Reference
Combustion Conditions
Smoke .No.
0.6
O.H
l.o
£3
0,0
0.0
0.0
/.8
519
aV
o.H
oS
LO
7.0
co2, %
5:9
6.2
79
tf.e
r.9
4.)
t.y
9.3
/a/
5". 5
(>.o
*y
9.Z
/o.6
o2.%
'3.3
12.8
X».3
9./
I2.<$
tz.s
12.1
8.0
7.2
S3.o
12.8
/o.7
8.2.
6.Z
Stack
Temperature,
F
Gacaous Emissions, ppm
CO
toSZ.
vy/.
yJ
3.
37^.
/y*.
39.
0
y.
762.
y*z.
r.
3.
/?.
HC
yo.
/5To
/.o
0.5-
3,0
<£J.5"
O.T
/.o
2.o
35.
S3.o
/•o
/.y
2.o
NO
/£
25:
w.
56.
/6.
35:
38.
72.
73.
17.
/9,
*o.
75:
79.
NOK
82.
88.
76.
78.
5-1.
53.
5-y.
eo.
ffA
y?.
y*.
5*9.
7y.
77.
9
CD
-------
G-10
Residential Unit 2V
Condition As found
Fuel
CO
o
a
o
CO
8 9
COg, percent
• Smoke X HC
O CO A
IO
II
34'
32
30
28- -140
26
24
22
20
E
a.
J '8
z
16
14-
12'
10
8
170
160
ISO
ISO
120
110
100 E
a
a
k
90 o*
- - 80
i
70
60
50
40
30
6- -
4- - 20
2-1- 10
0
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-ll
Residential Unit ^ >
Condition
• Smoke X HC
O CO A NO.
8 9
CO.J,percent
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-12
Residential Unit
Condition
2H
o
to
U
a
o
o
CD
Fuel
• Smoke X HC
O CO A NO*
34
32-
30
28
26
24
22
20
E
a.
16
14
12
10
170
160
150
140
130
120
I IO
100 E
a.
a.
90 o*
z
•o
c
o
O
O
- - 80
70
60
50
8- - 40
6- - 30
4- - 2O
2- - 10
8 9
, percent
10
II
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Residential Unit 25"
Unit Condition
Astound
Tumid
Second visrt
Third visit
Fuel
JHouw?
Safaranco
House
Referanca
House
Rafaranca
Combustion Conditions
Smoke No ia!
1.0 ('I)
1.7 (1 ft}
2.~ {0.7)
o*i fry)
O.I (6.1)
V./ (1.1}
S.Q (r.7)
co?.%
B.H
9.V
ffS
/o.B
/o.?
9J
10. 1
or%'b>
9.o
73
8.8
i*
6.5
8.H
7.o
Gaseous Emissions, ppm
CO
10. 6
&.&
12. t
trs
H7
1 03
11.8
HC
M
5.9
5".7
8.i
5.9
22.7
22.0
NO
V2.
V7.
y4<
*9.
5-V.
3^.
37.
NO^
56.
H7.
<*9.
V7.
V8.
36.
39.
3
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit
25-
Unit Conditi >r
As found
Tuned
Tuned
,_
HOLS?
riotise
Reference
Combustion Conditions
Smcke.No.
os
0.6
21
3.7
6V
O.H
0.6
I.B
/.3
H.o
U
OS
0.7
/.9
2.0
/.v
H.I
co2. %
7.7
7.8
9.5-
/o.6
//v
9./
?.3
9.5-
9.7
/o.i
I I.I
ff.6
8.<)
9-V
9,6
9.9
/I.I
Q2. %
9.S
9.6
7.1
5:^
V.3
^.o
7S
7.5-
7o
*.o
y.2
tf.3
79
7.1
6.7
6.3
*r
Stack
Tern pars ture,
F
Gaseous Emissions, ppm
CO
?.
r.
V.
7.
//.
/.
/.
A
3.
2.
/*
7
7.
0.
£
9.
/£.
HC
/•°
o.r
o.S
o.S-
/.o
C.8
A 2
2.2
0.3
0.7
/2
/.o
J.o
/o
0.7
/.*
/r
NO
Vo.
yo.
r/.
^.
&.
ft.
vs.
18.
51.
V9.
18.
W.
V9.
5*2.
«.
52.
49.
N0x
52.
52.
66.
76.
75.
So.
*9.
V5>
S"/
VA
V5.
V9.
V9.
5"o.
5*>.
51.
55.
O
I
-------
G-15
Residential Unit
Condition - . As found
o
CO
o
o
I
u
o
CD
House.
• Smoke x HC
O CO A NOX
34
32
30
28- -
16- -
170
•160
ISO
140
ISO
120
110
100 £
a.
a
90 o*
z
o
14- - 70
12- - 6O
10- - 5O
8-- 40
6- - 3O
10
12
SMOKE AND GASEOUS EMiSSJONS FOR RESIDENT8AL UNITS AS FUNCTION OF CO,
-------
G-16
Residential Unit '*-->
Condition
O
o
at
F..«I
• Smoke x HC
o CO & NOX
34- -170
32
3O
I
160
150
- -140
130
120
110
IOO E
a.
a
90 O
z
•o
c
o
O
o
- - 80
- - 70
12- - 60
10- - 50
8- - 4O
6- - 30
20
10
8 9
C02, percent
iO
II
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-17
Residentiol Unit 2 3
Condition Tuned
o
o
V)
o
a
u
o
CD
Fuel
• Smoto x HC
O CO A NOX
8 9
COj, percent
10
II
34
32
30
28
26
24
22- -I 10
20- -
E
a.
16
14
12
10
8
6
4
2
•170
•160
•150
140
ISO
I2O
100 E
o.
a
90 o*
z
•o
-4-80°
u
- - 70
60
50
40
30
2O
10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
Residential Unit
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Unit Condition
As found
Tuned
Second visit
Third visit
Fuel
Hours,
:
^stai&TXa
House
Hafaronca
House
Reference
Combustion Conditions
Smoke No.
0.fM
O.H fo.l}
o.r fo.f]
0.2/0.2)
0.2 fo.2]
oSfo-S)
Oti ('0.3}
co^.%<«
7.1
8.7
8.8
9.Y
9-V
9.2
7.o
o2,%(b>
//.;
9.1
8.3
8.7.
8.0
8.2.
8.i
Gaseous Emissions, ppm
CO
5".5"
£.0
fo.~?
^
7.0
5S
2.2.
HC
5-J
4.0
y.y
1.8
6.1
7.8
7.2.
NO
54
68.
17.
&.
61.
£6.
66.
NO,
61.
7f.
72.
yM
'articulate Loading, mgfcm
Probe + Filter
^./
6.7
6.0
7* I '
73.
(8.
67. \ H.6
Total
27.i
yV.5-
L U-°
^.
—
—
A.y
Q
i
1—1
CO
lal At 9-minute point of 4th cycle (5th minute smoka no. shown in parentheses).
(b) Average for "on" period of cycles.
let Based on sample collected during six 10-minute cycles.
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit
Unit Condition
As found
Tuneci
Tuned
Fuel
House
HOJ^'
Reference
Combustion Condition!
Smoke.No.
0.3
0.3
I.I
0.3
0.3
33
y.ff
/.v
J.O
0.6
0.7
0.8
2.1
5.7
Of/
t ^
0.3
O.I
2.r
y.5"
co2.%
(.8
7-X
7.7
e.o
8.8
to.9
// 2.
7.3
7.6
8.3
9.1
9.7
/o.6
//y
7.3
7.7
9.3
/e>.8
//y
o2,%
//r
//./
/o.Z
9.7
5.3
y.a
//3
/o.6
9.f
8.5
7.5
6.2.
y.7
//2
/O.i
8.1
6.0
y.8
Stack
Temperature,
F
Gataous Emisstoru, ppm
CO
12.
e.
5!
y.
3.
2.
y
9.
V.
3.
2.
V.
6.
JJo.
/V.
.12.
It.
II.
HC
/.2
I.Z
X3
/2
/3
/3
/y
/.o
/.o
/2
/2
/z
/3
/3
X.2
/./
//
/.I
/3
NO
H7.
52.
57.
62.
67.
go.
83.
S5.
63.
70.
76.
79.
85.
—
St.
60.
71,
77.
81.
N0x
68.
7o.
75.
78.
S3.
///,
/Zo.
66.
69.
73.
75.
77.
79.
—
66.
7f.
86.
96.
/o8.
Q
i
H-'
CO
-------
G-20
Residential Unit
Condition As
• Smoke x HC
O CO A NO.
8 9
CO-,, percent
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-21
Residential Unit
Condition Tuned
o
at
o
a
• Smoka X HC
o CO A NOX
34
32
30
28
170
160
150
140
130
120
MO
100 E
Q.
a
90 d*
z
- - 80
u
7O
6O
IO-- 50
8- - 40
30
4- - 20
2- - 10
8 9
C02, percent
10
II
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-22
Residentiol Unit
Condition
• Smok« X HC
O CO A
8 9
C02, percent
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Residential Unit Z "7
Ur>:t O">f)'?ion
As four.:*
Tuned
Second visit
Third visit
Fuel
House
Reference
House
Reference
House
Haferenca
Combustion Conditions
Smoke No '"'
1.0 (1,1)
0.V (O.H±
o.'$ f'o.H)
co,,%!bl
9./
8.2.
LAL
0?.%
8.1
9.V
9.5-
Gaseous Emissions, ppm
CO
fU
12. 5"
I/J
HC
33
V.V
73
NO
U.
£8.
62. .
NOX
86.
78.
&.
3
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit 2,7
Unit Condition
As fou«-J
Tuned
Tuned
Fuel
House
House
Reference
Combustion Conditions
Smoke. No,
0.5
0-i
I*
1.7
5.0
0.2.
0.3
0.3
OS
I.I
H.o
0.3
o.H
0.7
V.3
*?.y
co2, %
7.1
8.(,
9.o
9.3
/o.y
7.6
8.2.
g.6
83
9.3
/o.H
7.2.
77
8.0
8.6
9.7
o2.%
11.2.
9.3
ff.6
8.0
£.8
/0.6
9.7
9.3
87
8.0
1.7
10.8
9.8
?.y
8.7
7.o
Stack
Temperature,
F
Gaseous Emissions, ppm
CO
190.
17.
9.
9.
e.
\
HI.
/•y.
t2.
i2.
10.
10.
26.
10.
9.
7.
/9.
HC
tl.o
3.o
/5"
2.f
/.7
f.O
3.2.
2.V
/r
/.i
/.o
H.o
2.2
1.1
—
_
NO
V.2.
72,
76.
78.
78.
tt
63.
70.
79.
89.
9V.
Y4.
5*9.
it.
75.
83.
NOX
79.
9o.
67.
92.
89.
if.
70.
7f.
St.
92.
95!
58.
66.
73.
8+
9V.
I
CO
-------
G-25
27
Residential Unit
Condition As found
o
E
-------
G-26
27
Residential Unit.
Condition TZtnetf
u
a
5
o
CD
• Smoke x HC
o CO A NOX
8 9
C0g5 percent
IO
34- -170
32
30
28
26
24
22
20
e
a.
- 18 - -
16
14
12
8
6
4. .
2- -
160
150
140
130
120
no
100 E
a
a
»
90 o*
z
TJ
C
O
- - 80
I
70
60
10- - 50
40
30
20
10
0
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
27
Residentiol Unit.
Condition Tuned
5 5
o
o
a
O
O
CD
Fuel
G-27
/Reference
• Smoke X HC
o CO A NOX
8 9
COg, percent
10
34- -170
32- -160
30- -ISO
28- -140
26
24
22- -I 10
20- -
E
a
16
14
12
10
8 - -
130
120
100 E
a.
a
- - 90 o
- - 80
- - 70
5O
4O
6--30
2O
h 10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Residential Unit 2,&
Unit Condition
As, found
Tunad
Second visit
Third visit
Ftinl
House
..
Rsfarariee
<-k>use
Rsterence
House
totem.
Combustion Conditions
SmokaNj.
W°A.
*.'j fr.v)
CQ0.,%(b>
I A
7.4
L7.7
Q,.%'b)
* »* 7
/as
9.8
Gaseous Emissions, ppm
CO
>a.
&*> O
if Q
HC
/3./
,_ Afl
¥7
NO
"31,
&.
tl.
N0x
79.
^2.
7^.
Paniculate Loading, mg^m
Probe + Filter
9.7
7. a
—
Total
33. £
I3.5~
-
9
CO
co
M Xlt 9-minute point of 4th cycle ISth minute smoke no. shown in parentheses!.
Ibl Average for "on" period of cycles.
(c) Based on sample collected during six 10-minute cycles.
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit
Unit Condition
As found
Tuned
Tuned
Fuel
House
House
Reference
Combustion Conditions
Smoke. No.
ay
0.3
C.3
7.6
| o.o
O.o
0.0
0.0
0.2
—
l.o
o.o
0.0
o.o
0.3
0.3
o.o
0*
co2. %
5,7
I.I
6.?
7.H
7.3
76
7.8
7.9
8.1
*.y
8.7
7.1
73
73
7.6
7.6
79
8.0
o2. %
12.8
/2.3
H.B
10.2.
10.6
/o.o
9.5-
9.5T
9.0
8.7
ay
/a.?
10.1
10.2.
9.8
9.7
9.3
9.3
Stack
Temperature,
F
595
L2Z
£2f
6ZS
62?
tzc
£o5
62°
tlo
Wo
Wo
63a
Si?
6ZO
Gaseous Emissions, ppm
CO
>/2V0.
712.
122.
/ST.
12.
£
y.
s.
7.
7.
7.
/9.
8.
8.
7.
8.
7.
7.
HC
/2T.
2V.o
17.0
I3.a
j.y
3.2
3.Z
3.2
3.o
3.Z
3.2.
*o
3S
2.5
2.3
2.3
2.3
2.3
NO
9.
2.2.
30.
55.
39.
5Y.
&/.
£2.
Ll.
.
67.
69.
6B.
N0x
^2.9.
ize.
//&.
tie.
so.
58.
65.
66.
68.
70.
72.
iH.
69.
70.
80.
BO.
S3.
83.
o
I
to
-------
G-30
28
Residential Unit
Condition As -found
Fuel
2
®
Jt
O
E
u
a
o
a
OB
I
• Smoke x HC
O CO £ NOX
E
d
a.
o"
I
34
32
30
28
26
24
22- -
20- -
18- -
170
160
150
- -140
I3O
120
I 10
16
14
12
10
8
6
100 E
a
a
90 o"
z
- - 80
70
60
50
40
30
o
O
4- - 2O
2- - 10
8 9
COg, percent
10
II
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-31
o
OT
o
a
a
ID
9
8
7
6
5
4
3
2
1
0
O Q [
Raftidential Unit X. O -CLirur
• Smoke x nc
Condition Tuned Fliei Hous^. n en A wo
34-
- 32-
3O-
- 28-
26-
- 24-
22-
-- 20-
E
Q.
* 18-
r
— 16-
J^~-^- ,4-
/
/ IO-
— 8-
^ 6-
0
— >V ^V
^X .— / O
i I . r cii^ \ i i
-170
-I6O
-150
-140
-130
-120
-MO
-100 E
CL
CL
- 9O 0*
T3
- 80 °
O
O
- 70
- 60
- 50
- 40
- 30
- 20
- 10
0
8 9
COj,, percent
10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-32
o
E
en
o
a
9
8
7
6
5
«
3
2
1
0
Rfteirientinl lini* £- " ur
condition Tuned. Flie, Ke-ference wo
34-
— 32-
30-
- 28-
26-
- 24-
22-
- 20-
E
a
5 l8-
i
— /^^ I6~
/ '4
- / 12-
IO-
-
6-
ffx,- ^ *'
j 'S^ , *'
-170
-160
-150^
-140
-I3O
-120
-1 1 0
-100 E
a.
- 90 o*
z
TJ
-*°o
o
- 70
- 60
- 50
- 4O
- 30
- 20
- 10
O
6 9
CO2, percent
10
II
12
SMOKE AND GASEOUS EMISSIONS f Oh RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
SMOKE A\
Residential Unit 29
EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Unit r«-.ditLon
As founH
Tuned
' """'
Second visn
Third visit
I. tt
\
Fuel
Combustion Conditiom Gaseous Emissions, ppm
Smoks No.(a)
House \\$0&J>)
»
C02,5i(b)
9.V
i A5"(o.7)\ 7.9
toiwu. ,j 0.3 fr.0
•*>». |~~
fc-iarsnc*
House
(totem*
77
o2r%(bl
7J
97
?.!
CO
2*7
/2.3
HC
y.y
y.2
2S:a
NO
ff/.
«.
try.
NO
83.
65,
?y.
Participate Loading, mgkm
Probe -I- Filter
/y.y
3£.3
-
Total
76.0
56.B
CO
co
(a) At 9-minute point of 4th cycle (Sth minute smoke no. shown in parentheses).
Ibl Average for "on" period of cycles.
(cl Based on sample collected during six 10-minute cycles.
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit
29
Unit Condition
As found
Tuned
Tuned
Fu
1
Ho i ™. j
i
1
i
Hots-
Reference
Combustion Conditions
Smoke. No.
1
1 ""
!_ o.i
t_ *> J
j "*
j £7.6
j 0,7
1,0
O.7
0.6
o.i
c.sr
2.6
6.0
0.5
o.i
0.1
c.1
0.1
o.i
2.8
3.2
co2, %
i.B
*~ HJ
5.1
W
L &
$.*>
i3
6.Z
6.i
6.7
7.1
8J
8.6
6.0
6.2.
6.1
6.7
6.9
7.Z
7.8
8.0
o2, %
/3.8
/3.7
X3.5"
/J.2
l^.o
/*.¥
S/.B
/2.3
/t.8
//.3
10.6
9.0
e.1
I2..I
n.e
IIS
n.o
xo.V
9.8
8.7
a.*
Stack
Temparature,
Gaseous Emissions, ppm
CO
>/2VO.
683.
173.
5o.
33.
2.1.
/2.
20.
9.
7.
f.
8.
Zl.
39.
28.
27.
26.
21.
/8.
22.
^6.
HC
>IOQ.
?S
3.o
3.o
3.1
3.2
3.7
2.2
Z.2
2.2
3.3
/AS"
/3.0
6.6
9.0
/v.r
2
-------
G-35
Residential Unit
Condition
Fuel
Hou.se.
e 9
C02, percent
• Smoke x HC
O CO A NOX
10
34- -
32
30
28- -140
26
24
22
20- -
E
ex
a.
*.
O
r
16
14
12
10
8
170
I6O
150
130
120
I IO
100 e
a
ex
18- - 90
- - 80
70
60
50
40
•o
c.
o
O
O
6- - 30
4+20
10
12
SMOKE AND GASEOUS EM)SS!3!S!S FOR RESIDENTIAL UN8TS AS FUNCTION OF C02
-------
G-36
Residential Unit.
Condition Tuned
• Smoke x HC
O CO A NO.
C02, percent
SMOKE AND GASEOUS EMISSIONS FOR HF,$9D£NTiAL UNITS AS FUNCTION OF CO2
-------
G-37
Residentiol Unit _
Condition TuneJ.
Fuel
•* 5
o
E
CO
u
a
u
o
CD
1.
• Smoke X HC
o CO A NOX
E
o.
a.
*>•
O
X
34--
32
30
28
26
24-
22
20--
18
16
14-
12-
IO
170
•160
•150
•140
I3O
120
I 10
100 E
a.
a
90 o"
- - 80
i
70
60
50
40
6-j- 3O
4- - 2O
2-j" 10
0
8 9
COH,p*rcenf
10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTSAL UNITS AS FUNCTION OF CO2
-------
Residential Unit
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
3o
Unit Cofidiiiwfi
As fous d
TuneS
Second visrt
Third visit
Fuel
Housa
••
reference
House
Reference
House
Reference
Combustion Conditions
SmckaNs.'91
co2yw
a 2/o.2)| 75-
0.6 (/./)
o3 ft.H)
7.1
6V
V*'
10.3
II.)
//.
1 Gaseous Emissions, ppm
! CO
//.7
/70WJ
2oofM
,
1
is
HC
j?.2
9.V
Xfl.7
NO
^
W,
37.
NO,,
7?:
^s:
5».
Paniculate Loading, mg&m
Probe 4 Filter
f.e
t.i
—
Total
29.r
27.8
—
Q
i
CO
00
(a) At 9-minute point of 4th cycle (5th minute smoke no. shown in parentheses).
(bl Average for "on" period of cycles.
Id Based on sample collected during six 10-minute cycles.
(J) "On »M W*f, eUfeJti,
-------
Residential Unit
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
30
Unit Condi ".ion
As found
i
i
Tuned
Tuned
Fuel 1
Huu..- j
i
|
HOL- .
Refeience
Combu
Smoke. No.
1
L_ '-3
P «T<-
i '-
1 Y.2
i 7.5"
1
_
,¥
oM
aV
a?
7.5"
0.Z
as
0.3
c.
0.Y
ai
a?
6.3
*!ion Condition
C02. K
7.7
79
S.2
8.3
^ 8,7
r.9
&/
6.7
6.9
8.7
ZS
5.7
6.1
6.5-
6.9
7.3
7.3
7S
«
o2, %
9.8
9.7
r~9.v i
9./
S5
/2.S"
IZ.I
yy.3
ll.o
8.2
12.8
/2.3
/A 9
il.H
/Q.8
S0.2.
IO.Z
9.5-
Stack
Temperature,
F
CO
0.
7
1 6.
7.
H.
H7.
HS.
/&.
tz.
23.
302.
i2.
22.
6.
2.
3.
A
0.
Gaseous Em
HC
-------
G-40
3o
Residential Unit
Condition A* TQ<*n*
Fue|
o
Z
to
U
a
ffl
0
<*
//C
8 9
C02, percent
• Smoke X HC
O CO A NOX
10
II
34'
32
30
28- -140
26
24
22
20
E
a.
S "'
16
14
12
IO- -
8- -
170
160
150
130
120
110
100 E
a
a
90 o"
2
- - 80
70
60
50
4O
6- - 30
4-- 20
2- - 10
0
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-41
3o
Residential Unit
Condition Tuned
o
E
V)
o
a
u
o
CO
8 9
C0.fi percent
• Smoke
o CO
10
X HC
A NOX
34
32
30
28
26
24
22
170
160
I5O
- -140
130
120
I 10
20- -
E
a
S "
14-
12
10
100 e
Q.
Q.
- - 90
z
•o
16- - 80
O
o
70
60
50
8- - 40
6- - 30
4- - 2O
2- - 10
12
SMOKE AND GASEOUS EMISSIONS FOB RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
Residentiol Unit
Condition T
3o
G-42
Fuel
S. 5
o
E
CO
u
a
4ta
O
•5 4
as
8 9
CO},, percent
• Smoke x HC
o CO A NOX
!O
34
32
30
28- -140
26
24
22
20- -
E
a.
8""
170
160
150
130
120
110
100 £
a
a.
»
90 o"
z
•o
c
o
O
o
16- - 80
14- - 70
12-- 60
10- - 50
8- - 40
6- - 30
4- - 20
-|- 10
0
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Residential Unit 3/
Unit Condition
As found
; Tuned
"
Second visit
Third visit
i
i
Combustion Conditions
Fue! |iS>moke No.'a)
Mouse j! &' C '° °)
cc2,%'b'jo2.y.(b)
1
|| 0.2. /&.2.)j 9.9 i ?.<$
Reference j, A2*b.'3,)
House
Referance
House
Rafwence
i
i
9.6 i «o
•••• •
Gaseous Emissions, ppm
CO
36J
^.v
V.7
HC
3.8
Z.H
2.V
NO
61.
S3.
es;
NO
te.
87.
89.
3
-------
Residential Ursl
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Unit Condition
As foun-i
Tuned
Tuned
Fuel
House
HCL"-:>
Reference
|
Combustion Conditions
Smoke. N.,
0.2
O.Z
—
o3
O.Z.
1,5
22.
0.3
0.2
0.3
0.3
_
<3.3
/.¥
£3
0.2.
O.I
O.Z
03
0.2.
c.6
£&
CO2, '- '.-
7-0
7.3
7,# I
0.2
~8.7
u. 9.7
11.2.
74
7.7
ff.3
9.a
9.3
9.6
/o,6
/;.3
73
7.6
S.H
8.7
9.5T
/O.I
H3
o2,%
113
//.v
/atf _|
/o.V
9.6
&3
'6.3
11.2.
to.7
9.9
8.6
8*
7.9
6.7
5T7
;/.V
/o.S
9.8
9.0
B.I
7.2
£3-
Stack
Temperalure.
F
Gacaous Emissions, ppm
CO
ye.
'/A
t/ft
^^
;7.
L-^
5-2.
i
3.
v.
3.
V.
v.
3.
V.
22.
s:
£
V.
s:
V.
£
3,2.
HC
3.2
2.9
zr
2.8
2.7
2.7
3.o
3.7
3.3
3./
3.o
2.6
2.9
2.5
3.2
2.0
1.8
1.7
1.7
1.7
t.7
2.3
NO
50.
60.
77. |
6 A
7V.
77.
76.
55.
62..
73.
8£
W.
86.
S3.
82.
r3.
63.
77.
9V.
Sff.
es».
88.
N0x
57.
^3.
75:
71.
75.
77.
7V.
5-fi.
(>7.
•78.
89.
92.
9o.
ss.
82.
55.
6V.
So.
95-.
9/. !
9/.
9A
Q
-------
G-45
Residential Unit
Condition
• Smoke x HC
O CO A NO*
8 9
C02, percent
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
Residential Unit
Condition
• Smoke x HC
O CO A NOX
8 9
C02, percent
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-47
Residentiol Unit _
Condition Tuned
o
W
u
o
ffi
• Smoke X HC
O CO A NOX
34- -
32
30
28--
26
24
22
20--
170
160
150
140
130
120
•I I 0
100 E
a.
a.
90 o*
z
-- 80
70
6O
50
- - 40
G- - 30
4-- 20
2- - I 0
8 9
CO2, pa-rent
10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Residential Unit
32.
Unit Condition
As found
Tunad
Second vis'!
Third visit
u *»
Fuui
Htjusn
Hefarar?se
House
R«fero?»ca
House
Reference
Combustion Conditions
Snnok., rJo.!a)
0, 2 So. /)
O.I (&.>}
£>.! /'»./)
r-n w(W
t-2—
7.o
8.7
L&6
c y(b|
C2'r"
//v
9.y
9.3
Gaseous Emissions, ppm
CO
292.
90.
vv. J
HC
12.5
2.8
*-L
NO
3/
63,
12
NO
73.
^9.
6-7
Particulate Loading, rngfcm
Probe + Filter
53
/oS
Total
V2.9
373
oo
(a) At 9-minute point of 4th cycle (5th minute smoke no. shown in parentheses!.
Ibl Average for "on" period of cycles.
Id Based on sample collected during six 10-minute cycles.
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit 3Z
Unit Condition
As found
Tuned
Tuned
Fuel
Hjuse
House
Reference
Combustion Conditions
S:oke,,.,
0.1
rii —
o.i
O.I
O.I
2.6 1
y.r
0.0
OJ
0.1
O.I
0.3
/.O
1.3
s.r
O.I
O.I
O.I
OJ
O.I
/z
co2.%
5.8
6.3
. ts
7.2
7.5
8.H
8.7
6.t
6.9
7.3
8.0
9./
/o. 2
/0.6
//.?
6.2.
7.1
8.0
8.7
9.1
9.7
11.3
.£"
a. 5
0.5-
0.9
9.0
1.7
1.3
I.I
—
1.0
I AV
NO
28.
29.
37.
yc
i9.
5"o.
v&
y/s
16.
55.
62.
61.
6+
6t.
62.
6s:
33.
60.
65.
61.
65^
57.
61.
N0x
72.
71.
66.
60.
58.
56.
57.
5o.
82.
7V.
76.
70.
70.
60.
66.
69.
82.
70.
67.
58.
62.
55.
5-5:
Q
i
£t
CD
-------
Residentiol Unit
Condition A* fov.*JL
G-50
Fuel
I5
«c
u
a
o
o
8 9
CO2, percent
• Smoke
O CO
10
X HC
A NOX
34- -170
32
30
28--I40
26
24
22
20- -
E
ci
'8
16
14
12
I6O
ISO
130
120
I 10
100 e
a
Q.
90 a"
- - 80
70
GO
C
O
O
O
10- - 50
8- - 4O
6- - 3O
4-- 20
2- - I 0
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-51
Residential Unit _
Condition 7un«et
Fuel
o
o
E
tn
.e
u
a
o
CQ
• Smoke x HC
o CO A NOX
8 9
C02, percent
10
II
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
Residential Unit
Condition
32-
o
o
E
to
o
a
o
o
CO
O
G-52
Fuel
• Smoke x HC
o CO A NOX
B 9
C0?1 percent
IO
34- -170
32
30
28+140
130
120
I I O
4- -
2 - ~
160
150
100 e
o.
o.
90 o
z
•o
o
O
o
- - 80
7O
6O
5O
40
30
20
10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Residential Unit 33
Unit Condition
As found
Tuned
Second visit
Third visit
ruei
House
Reference
Combustion Conditions
SmoSca No.(al
/5-<*.«S
A* 4$
CO ,«tbl
&l
I2K.
>I2HO.
>12HO.
HC
-
211.
IU.
NO
9,
2o.
22.
NO
X
87.
/oZ
97.
3 skoveJ fijm oi ^k^ae
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit
33
Unit Condition
A"; found
Turpi
Tuned
Fuel
HoUiE
Houv
Reference
Combustion Conditions
Smoke. to.
3,0 <*>
/.v &>
U (*j
r.o (a) j
/..? '*)
5".o (a;'
13 ia)
£.9 ral
0.8 &
—
/.2'a)
/. 2. ( a}
2.6 fai
*/3 ^
A/ 'a)
O.fl W
0.7 w
aV fa;
2Sfa}
3.6 (a)
cor%
3.g
5^2
^.0
^.S 1
^.7
7.6
H.3
,5.9
^.7
^.g
7.6
7.7
8.2
9.1
V.7
5:9
6.7
^,9
S.I
9.3
o2.*
15.1
^33
X2.5-
y/.^ j
If 7
/O.3
H.H
13.2
12.2
//.5"
//,/
11.2,
lo.H
9,0
/W
/3.o
//,9
n.2.
1 0.0
8.1
Stack
Temperature,
F
6oZ
62.0
(>1o
£32.
4/6
62.g
t,o<)
581
570
(3.0
6/9
600
563
Gaseous Emissions, ppm
CO
>I2HO.
? I2HO.
? IZVo.
? I2HO.
> I2HO.
6HO.
>12HO.
>I2HO.
>I2HO.
990.
760.
S8o.
3&o.
/68.
>1210.
> 1210.
?/2Vo.
650.
280.
fl8.
HC
360O.
*j5o.
62..
2.QO.
zs.
/5".
WSO.
120.
/S~0.
37.
65.
32.
V3.
35.
1700.
26o.
90.
29.
33.
28.
NO
25.
12.
11.
IB.
22.
30.
H.
/o.
10.
28.
21.
30.
33.
Vtf.
X6.
/3 -
25".
3V.
V5".
5-9.
NOX
^
73.
80.
—
80.
go.
CA)
>IOO.
>/«o.w
« / 90. rtj
«r /V6*. rt)
» /fi<, fb>
< y?r rt)
< 170. '*>
< /42. ^
> /5"o. f6^
aisi. {t>)
«-//8. ^
-------
G-55
Residential Unit
Condition A*
33
8 9
C02,percent
• Smoke X HC
o CO A NOX
10
34- -
32
30
28
26
24
22
- -140
130
I2O
I 10
20- -
14
12
10
170
160
150
100 e
a.
a.
E
a.
j 18+ 90 6
r
16 - - 80
TJ
C
O
O
u
70
60
50
3- - 40
6 - - 30
4- - 20
2- - IO
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-56
Residential Unit
Condition
o
E
to
.c
u
a
u
o
OS
0
Fuel
• Smoke x HC
O CO & NOX
8 9
CQg, percent
IO
II
34--
32
30- -150
28--I40
26
24
22
20--
£
a
16
14
12 •
IO
170
160
•130
120
I I 0
100 E
a.
o.
90 o"
z
T>
80°
O
7O
60
50
4O
6- - 3O
20
10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-57
Residential Unit _
Condition Tuned
Fuel
/?efi
•* 5
o
E
u
a
o
o
CD
• Smoke X HC
O CO A NOX
I
8 9
CO2, percent
IO
34- -
32
3O
28- -
26
24
22
2O- -
14- .
12
10
I7O
160
150
140
130
120
I 10
100 E
a.
a.
E
a
18-1-90 o
16- - 80
7O
60
50
8- - 4O
6- - 30
4- - 20
2- - 10
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
Residential Unit
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Unit Condition
As found
Tuned
Second Visit
Third visit
Fuel
House
.--
Reference
House
Reference
House
Reference
Combustion Conditions
Smoke No.'"'
2.7 fat)
/.o O.s}
A 9 ^.6)
co.,.%""
9.V
9-8
10. 1
0;!,%(b>
7V
e.o
L^3
Gaseous Emissions, ppm
CO
/9.6
H.B
I S3. 2
HC
5:y
3.9
S.I
NO
62.
58.
t>3.
NOX
U.
tt.
i2.
3
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit
Unit Condition
As found
Tuned
Tuned
Fuel
House
Hour:
Reference
Combustion Conditions
Smoke .No.
O.I
0.3
1.0
/,v
3-6
5.1
o.H
0.6
0.6
0.6
0.6
2.8
—
0.2.
1.8
24
Z.5
B.I
co2, %
0.6
L&7
8.7
9.0
9./
9.5
5.9
9.3
9.3
9.4
9.7
lo.6
9,6
9.8
10.0
/0.3
10.3
11.3
o2,%
6.H
8.0
7.6
7.1
7.1
6.i
8.5
8.2.
8.0
7.8
7.6
6.7
7.8
7.5
7.2
72
7.1
f.i
Stack
Temperature,
F
V57>
V8<>
V8o
48°
*j8o
17t>
505-
5"cJ9
508
f°t
5*1
H8o
5"oo
V8o
foo
its'
%OO
V95"
Gaseous Emissions, ppm
CO
12.
12.
15.
15.
29.
V3.
9.
9.
9,
/0.
//.
Hi.
19.
12.
15.
39.
16.
n 25".
HC
/.v
A3
o.a
l.o
i.7
^ 2.3
1.7
/.6
U
1.6
2.7
2.9
/.2
2.2
/•9
2.7
1.7
35.
NO
5^.
61.
68.
11.
62.
62.
58.
63.
66.
70.
66.
68.
72.
61.
o3.
56.
66.
VV.
NOX
60.
6H.
63.
67.
65".
6s:
61.
68.
71.
75:
72.
73.
70.
60.
6H.
56.
66.
13.
Q
OI
<£>
-------
G-bU
Residentiol Unit
Condition ATS -fount*.
o
£
en
o
a
o
o
a
Fue|
• Smoke x HC
O CO A NO*
8 9
C02, percent
IO
II
34- -
32
30
28- -140
26
24
22
20- -
16
14
12
10
4- -
2- -
170
160
150
130
120
I 10
100 e
a.
a
E
a
I8-|- 90 O
- - 80
70
6O
50
•o
c
o
O
O
8- - 40
6- - 30
20
10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-61
Residential Unit
Condition
S. 5
o
E
u
a
u
o
a>
Fuel
• Smoke x HC
O CO a NOX
_L
8 9
C02, percent
10
34
32
30
170
- -160
- -150
28- -140
26
24
22
20- -
E
a
S""
16
14
12
10
•130
120
I I 0
100 £
a.
a.
90 a"
z
•c
c.
o
O
O
- - 80
7O
- - 60
- - 50
40
6- - 30
4- - 20
2- - 10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF 2
-------
Residential Unit
Condition
o
tn
-------
Residential Unit
SMOKE AND EMISSIONS DATA FOR RESIDENTIAL UNITS
FOR CYCLIC RUNS
Unit Condition
As found
Tuned
Second visit
Third visit
Fuel
House
..
Reference
House
Reference
HOURS
Reference
Combustion Conditions
Smoke No.fa)
—
C. 2 ft. 2)
0.2. fo ^2)
co2.%<»>
—
8.8
9.3
0?.%lb>
• —
8.7
7.5-
Gaseous Emissions, ppm
CO
—
2.5"
3.e
HC
~
5:^
9.i
NO
77.
8V.
N0,
S5~.
9A
Paniculate Loading, mgfsm
Probe + Filter
—
+ 1
2,9
Total
S5.2-
^7,6
Q
i
O5
CO
la) At 9-minute point of 4th cycle 15th minute smoke no. shown in parentheses!.
(b) Average for "on" period of cycles.
fcl Based on sample collected during six 10-minute cycles.
-------
SMOKE AND GASEOUS EMISSIONS DATA FOR RESIDENTIAL UNITS
AS FUNCTION OF CO2
Residential Unit
35-
Unit Condition
As found
Tuned
Tuned
Fuel
House
House
Reference
Combustion Conditions
Smoke .No.
0.2.
0.2.
0.3
o.i
1.0
0.3
0.1
0.2.
0.2.
a?
OS
OS
0.8
i.o
co2. %
7.1
7.8
83
9./
9.7
IOS
7.6
8.0
8.2
8.5
8.7
8.1
9.1
10 J
Q2. *
lt.3
10. 1
8.7
8.1
7V
&.Z
10.2.
9.r
9./
8.7
8.1
7.8
76
i.H
Stack
Temperature,
F
5~o o
foo
H75
Hie
1*0
*3o
&?
SZt
S<8
SH»
$00
v?r
186
Viz.
Gaseous Emissions, ppm
CO
2.
3.
2.
2.
/.
y.
3.
V.
-------
G-65
Residential Unit
3r
2 5
o
E
£
O
a
o
o
00
He
8 9
C02, percent
• Smoke
o CO
X HC
A NOX
IO
34- -
32
30
28--
26
24
22
20- -
o
16
14
12
10
4_.
2--
170
160
150
140
•130
120
I I 0
100 E
CL
a.
90 o*
Z
-- 80
7O
6O
50
8- - 40
6- - 30
20
10
12
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
G-66
35-
Residential Unit
Condition Tuned
• Smoke x HC
o CO A N0«
8 9
C02, percent
SMOKE AND GASEOUS EMISSIONS FOR RESIDENTIAL UNITS AS FUNCTION OF CO2
-------
H-l
APPENDIX H
DATA FOR COMMERCIAL BOILERS
-------
Boiler C2.00I
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel fJo.TL
Load,
percent
99.
go.
60.
Firing
Rate,
a*
//r
93
7.o
Fuel
Temperature,
F
—
Combustion Condition!
Smoke No.
0.2
0.1
1.8
7.1
/.5~
/.y
x.v
2.1
2.1
7.8
oA
0.1
0.1
s.z
3.Z
2.B
8.1
CO,,*
11.6
12.1
/3.o
13.*
9.3
^P
/o.$
12.1
/2.z
(3.1
9.3
9.9
A>.?
//y
/2.0
/i.o
/3.o
o2. %
y?
7.S
2.7
1.9
0.y
^y
^.2
y.y
1.1
2.e
7.1
&.<>
5.2.
y.r
?•?
75"
2.3
Stack
Temperature,
F
73o
720
710
700
680
i?o
£55
ad
£5-0
izo
565-
SS3
5V2
• —
5-J0
530
5-/Z
Gaseous Emissions, ppm
CO
&
f.
?/.
«*.
/32.
78.
11,
/y.
/3.
22.
zyy
79.
/3.
7.
z
f.
19.
HC
0.1
0.7
0.9
80.
19.5
9.3
yr
/r
/.$•
/2
yo.
9.0
2.0
/.*"
/.7
A 7
y.a
NO
?8.
f8.
&.
$7,
5o.
51.
f9.
6i.
&0.
U.
37.
It.
ft.
V9.
17.
17.
15.
N°x
58.
5Q.
57.
57.
5V.
f3.
59.
62.
V.
60.
12.
y*.
yft
18.
5f.
5o.
It.
so2
/3l.
n&.
SfO.
/«.
/<»*
/tl.
fZZ.
J12.
/w
/St.
/OO.
//£.
/21.
12-9.
'36,
132.
J1%-
Particulate Loading, mg/sm
>roba + filter
—
—
—
^
_
-
—
*6
—
—
—
-
-
—
—
9.2
—
Total
—
—
—
—
-
-
—
y5".y
—
—
—
-
—
—
—
22.7
_
a
-------
H-4
B.i..,_CZOO/_
//
I
I
• Srnok*
o co
X HC
A NO,
180
10 II
CO2,ptrc«nt
12
13
14
340- -I7O
320- -160
300- -150
280- -140
260- -130
240- -120
220- -110
200- -100
,
180- - 90
I6O- • 80
140- - 70
120- - 60
IOO- - 50
SO- - 40
€0- - 30
40- • 20
20- - 10
O
15
36
34
32
30
28
26
24
22
20
t
16
14
12
10
- 8
6
4
2
0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-5
ff2%
IO II
C02,P*rc*nt
• Smok*
O CO
x MC
A NO,
14
I
ISO
340- -170
32O- -160
500- -ISO
280- -I4O
260- -ISO
24O- -120
22O- -110
2OO- -IOO
I
ISO- • 90 *
°
"
160- - 80
140- - 70
120- - 60
100- - 50
80- - 40
60- - 3O
4O- - 20
20- - 10
• 0
15
-36
-34
-32
-30
-28
-26
24
-22
-20
I
'8c
]
16
14
12
IO
8
- 6
4
- 2
0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-6
•».... C2QQI
• Smok*
O CO
10 II
C0*,ptrc«nt
12
XNC
A NO.
340- -I7O
320- -160
300- -ISO
2BO- -I4O
260- -ISO
240- -120
220- -110
20O- -100
So.
. I8O+ 90"*
it
O
ISO
14
160- • 80
140- • 70
120- • 60
IOO- • 50
BO- - 40
60- • SO
40- • 20
20-t- 10
0
15
-36
•34
-32
-30
-26
-26
24
-22
-20
'«,
16
" 14
12
10
a
• e
- 4
- 2
0
a.
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler C 2001
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel
Load.
percent
102.
ei.
45;
Firing
Rite,
cfh
/600.
/260.
1010.
Fuel
Temperature,
F
—
—
_
Combustion Conditions
Smoke No.
0.2
c.2.
0.)
0.1
0.)
O.I
O.I
0.)
0.2.
o.o
O.Z
0.3
o.3
o.H
03
O.I
co2. %
7.5
7.9
8.f
9./
9.9
7.3
7.6
&¥
?./
l.i
/o.3
6.1
?./
7.7
8.H
9J
o2, %
7.7
6.8
£.Z
Zo
3.H
8J
7.3
6.2
?.o
IS
3.0
9.5
e,z
7.0
6.0
V.3
Stack
F
75«
75o
?vr
7^9
739
712.
7*9
700
700
7oo
660
US'
625-
6/0
&8
set
Gatooin EmiKions, ppm
CO
270.
H9.
80.
22.
3o.
330.
260.
/23.
St.
13.
35^.
JfT/.
290.
232.
176.
vr.
HC
t/o.
5Si
5b.
V5:
/r
2S-5-
/^
53C
35
37.
2
-------
H-8
C2.001
/Ol
1
• Srnok*
O CO
XHC
A NO.
IO M
C02,S>*rc«nt
12
IS
14
540-
32O-
300-
280-
260-
24O-
220-
20O-
I
a. (80-
o:
Z 160-
140-
120-
100-
80
60-
40-
20-
I8O
ITO
I6O
150
140
ISO
I2O
•HO
•IOO
8
8O
7O
60
50
40
30
20
IO
0
36
34
-32
-30
-28
-26
-24
•22
20
i
i
i
" 5
16
14
12
10
8
6
4
- 2
0
E
'o-
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-9
C200I
i s
i4
8
•79%
• Smoh*
O CO
1—•»-
IO H
C0},ptre«n»
12
13
X HC
A NO*
14
340- -I7O
320- -160
300- -ISO
290- -140
260- -130
240- -120
22O- -110
200
too
leo- - 90*
o
O
160 4- SO
140- - 70
120- -6O
IOO- • 50
8O- - 40
60- - 3O
40- - 20
2O-i- IO
0
15
36
-34
32
•30
-28
-26
-24
-22
-20
-18
- 18
14
12
- 10
- a
- 6
- 4
- 2
0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-10
• Smok*
O CO
K HC
a NO,
!'
34O- -I7O
32O- -ISO
300- -ISO
2BO- -I4O
260- -ISO
240- -I2O
220- -MO
ZOO- -IOO
ISO
IO II
CQj.ptrctnt
12
13
14
a
180- • 90*
O
o
160+ 8O
140- • 70
120- • 60
100- • 50
80- - 40
6O- - 30
40- - 20
20-4- IO
O
IS
36
-34
-32
-30
-28
26
-24
-22
-20
I
i
:
16
14
12
- IO
- 8
- 6
- 4
- 2
•0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
Boiler C2002
Fuel
AS FUNCTION OF CO
. Z
Load.
percent
99.
1 78-
!
' ,-
71.
59.
Firing
Rate,
Z7.2.
Zt.b
_J9.Z.
/6.3
Fuel
Temperature,
F
—
—
—
—
Combustion Conditions
Smoke No.
O.I
0.1
0.2
2.0
7.7
/Z3a.
1
ji
£26
£/8
592
5"y<»
5to
600
555
5VC
£32.
V6o
fto
MS
f*5
V98
HSS"
ws-
2.
2.
/.
V5".
$g
7
6.
6.
/A
>/230.
/.
O
O
O
0
12.
HC
.
/».
70.
75L
£2.
so2
/20.
/28.
/Vo
t&i.
196,
too.
lot,,
IZO.
/to.
/SO.
151.
92.,
/20.
/3Z.
/y*.
/9£.
00.
9/.
/o«.
/37.
/y5T
Paniculate Loading, mg/sm
Probe + filter
_
_
— .
-
—
~
-
_
9.6
_
—
__
—
—
—
—
—
—
—
—
—
—
Total
_
—
—
—
~
—
-
_
2 o.o
_
—
_
—
—
_
—
—
—
_
—
—
~-
ffi
-------
H-12
3«
S4
-32
30
28
26
24
22
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-13
st
I-34
•32
-30
-28
•26
24
22
-20
10 II
COg.pcrctnl
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-14
totter.
CZOQ2-
xA* ^
/W ! ••
I
S
• Smofct
O CO
KHC
A NO.
IO II
COg.ptrecnt
12
13
14
a
340
320
3OO
28O-
260-
240
220
200
180- -
ISO
140
120
100
eo
60
40
20
180
ITO
I6O
ISO
140
130
•I2O
•MO
IOO
8O
TO
6O
SO
40
SO
20
10
O
36
34
32
30
28
26
24
22
20
I
•••;
16
14
12
IO
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-15
•oil*r.
CZ002.
• Smoke
O CO
X HC
A NOi
340-
520-
3OO-
28O-
26O-
240-
220-
200-
•
M 80- -
'
I6O
I4O
120
100
8O
60
40
20
10 II
COg,P*rc«nt
180
I7O
•160
•ISO
140
ISO
120
•110
•IOO
3
SO
70
6O
50
4O
30
80
10
0
-34
-32
-30
28
-26
-24
-22
-20
-'•
- 16
14
12
I- IO
8
- 6
- 4
- 2
- O
a
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler C20O2
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel M>. V
Load.
parcant
9*
78.
69.
57.
Firing
Rat*.
gph
26.o
20.6
/B.2.
)S.)
Fual
F
—
—
,_
—
Combunion Conditioni
Smoka No.
0.8
0.3
a.*
I.I
/*-
7.t
0,5-
0.8
/.6
2.3
2.3
8.8
I.I
f.O
l.IO
5-95
Uo
600
572.
55$
JVe
S3S
SBo
$55
53o
5V3
-W2
r^a
V92
Hlo
W7
V2i
r
GotoiK Emwiom, ppm
CO
H.
3.
3.
2.
/.
6o7.
o
o
O I
o
2.
^/23o.
;.
o
/.
o
>/230.
2V.
3.
2.
/.
>/Z3o.
HC
NO
139.
/79.
2V<.
27*.
ZSo.
ZVo.
IZl,
2/2.
238.
2*3.
2t7,
202.
/^S.
2o3.
Z".
2/6.
/*9.
/oy.
/72.
2M.
2//.
X69.
N0x
/39.
/*?
2VA
276.
28
-------
H-17
C2.00Z
10 II
C0j,p«re«nt
r36
34
-32
-30
28
26
24
-22
20
I
»;
16
14
12
10
a
6
4
2
0
E
'5
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-18
Bai... C2002.
P.... A/». */
•79%
I-
• Srnck*
o co
X HC
A N0«
ISO
10 II
C0j,p»re»nt
14
340- -170
320- -160
3OO- -150
280- -140
260- -130
240- -120
220- -IIO
20O- -IOO
180- -
(
(
160- • BO
140- - 70
120- - 60
IOO- - 5O
8O- - 40
6O- - 30
40- - 2O
20- - 10
O
15
36
34
32
30
-28
26
24
22
20
i
16
14
- 12
10
- a
- 6
- 4
- 2
- O
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-19
Bon«. C 2-002.
A/e. *y
• Smofc*
O CO
X HC
A NO*
180
36
34
32
30
-28
26
-24
-22
20
I
i
i
]
I- IS
14
12
- 10
- 8
- 6
340- -170
320- -160
SOO- -150
280- -140
260- -190
24O- -I2O
220- -MO
2OO- -IOO
I8O- • 90
3
160- - 80
140- - TO
120 - 60
100- - 50
80- - 40
60- - 30
4O- - 2O
20- - 10
IO
ti
12
13
14
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-20
C20Q2.
ieo
36
34
-32
-30
-28
-26
-24
-22
•2O
-18,
IO II
C0g,p*rc*nt
14
15
SMOKE AND GASEOUS EMISSIONS FOB COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Boiler C20O2.
Fuel
CR
Load,
percent
99.
78.
69.
58.
Firing
R««,
gph
26.0
ZO.H
I8.O
is:i
Fuel
Tamparatura,
F
X95-
155
2 03
2oo
Combuttion Condition*
Smoke No.
x.v
/.5
2.Z
3.2.
8.0
i.B
J.8
/•«_j
32
3.o
7.Y
2-9
A9
2.1
Z.2.
2.9
5:9
9,o
/.e
A9
2-0
3./
7.2-
co2, x
9.0
10,0
/.o
12 J
/2,l
7.6
8.7
10. 1
11.7
>2J
I2.B
oz.x
5.2
i,8
5T6
V.2-
?.6
/^3
9.0
522
^y
?f2.
T32.
^20
5"ffO
512.
P/8
S3o
f2S
S7S
532
£08
V92
H30
flo
GaMout Emiwoni, ppm
CO
O
0
O
0
780.
O
0
O
0
O
7.
I.
o
O
o
o
2.
r.
/.
0
o
o
S3.
HC
NO
228.
273.
Z83.
286.
if/.
tat.
2/9.
2VS.
260.
T.S7
237.
IfZ.
in.
2/t.
2Z8.
2V/.
222.
/2S-.
/9a.
2«2.
23.2.
228.
2oo,
N0*
232.
28o.
3oo.
288,
ZH7.
188.
223.
Z5o.
211.
257
2*2.
159.
/90.
2/V.
23V.
2Vo,
227
/29.
/9o.
2o7.
222.
22ft
2<>2.
so2
370.
V3o.
Vtfc.
5"3o,
55o.
320.
370.
vzo.
Soo.
520.
511.
270.
15°.
Voo.
Ht>o.
foo.
fYo.
2VO.
36o.
390.
ilt>.
foo.
SSo.
Paniculat* Loading, me/tin
Probe + filtar
—
„
—
—
_
^^
_
_
-
/o3.
—
—
—
—
—
—
—
-
—
—
—
~~
Tout
_
-
-
—
—
-
-
-
—
117.
—
—
—
—
—
—
~
—
—
—
—
—
_
a
i
to
-------
H-22
BoiUr.
C20Q2.
CK
IOO%
I
t
12
x HC
A NO.
14
ISO
34O- -170
320- -160
3OO- -ISO
280- -I4O
280- -130
240- -I2O
220- -110
200- -IOO
E
| ISO- • 90"*
1 - 16
14
- 12
- 10
e
I- 6
- 4
- 2
0
o.
a
'o
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-23
Soil*?.
CZ002
CK
re
O
• Smok*
o co
10 II
COj, percent
X HC
A NO,
ISO- -
- - 40
- - 30
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-24
•«.... C 2.002.
F....
• Smok*
O CO
I
10 It
C02,ptre«n*
12
13
X HC
A NO,
14
E
a
180
340- -ITO
320- -ICO
300- -150
280- -140
260- -130
240- -120
220- -110
20O- -!OO
C
I8O- - 90C
C
160- - 80
140- - 7O
120- - 60
100- • 5O
80- - 4O
60- - 30
40- - 20
2O- - 10
0
15
34
-32
30
-28
-26
-24
-22
20
I
i
:
- 16
14
- 12
- 10
- e
- 6
- 4
- 2
0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-25
„,.., C200Z
180
IO II
C02, percent
13
14
15
36
32
30
28
26
24
22
20
I
t
<
1
16
14
12
10
8
6
• 4
2
•0
o
z
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF C02
-------
Boiler C2002
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel
Load.
percent
99.
1
r
! 82.
Firing
Rite.
} O.o
! ; i
:
7/.
67.
2650,
2.180.
„
—
O.I \
0.1
O.D
coz. %
76
8.H
It
9-9
7.8
o2. %
7<
4.3
V-8
J.3i
75"
8.6 j 6.1
/".o ^
/o.o
3.3
3-i
O. o
o.o
0.0
O.o
0.0
o.o
O.o
7V
8.6
_?£
O
£.3
9./
99
7o
rf
?.°
9.o
6.3
V.5-
3.z
Stack
Tamparatura.
F
6/^r
tzr
62-)
£20
n*
*90
^fff
578
S30
f'8
STo8
jToo
H9Z
ter
H8o
Gataoin Emissions, ppm
CO
3.
l.
3.
3.
o
o
/.
/.
o
c
o
i.
0
o
i.
HC
0.6
/.5-
0.6
i.i
0.6
o.3
0.3
/3
A/
A 2
Z.o
IS
/.6
iS
J.S"
NO
80.
63.
85.
9J.
59.
77.
93.
9A
63.
78.
89.
19.
71.
69.
68.
N0x
77.
83.
86.
91.
62.
77.
91.
92.
63.
78.
9/.
V9.
76.
89.
69.
soz
o
o
0
o
0
o
o
o
o
0
o
0
o
o
&
Paniculate Loading, mg/wn
'robe + filter
—
—
-
—
_
—
2J
-
_
—
—
—
—
—
~
Total
—
—
— .
—
-
_
/AY
-
_
_
—
—
—
_
—
K
to
OS
-------
H-27
a
fafi Lra,t i Mrf 9° "» « <•" * xOj
340-
320-
30O-
280-
260-
240-
220-
_ 2OO-
a
a 130-
o"
- Z 160-
I4O-
120-
K! o I0°
^~^*~~~~^~~^
60-
— 40-
x jjc^u >»*U
! ^K=r^f==::ii^^=^fj^ till
-iao
-I7O
•160
•ISO
•140
•I3O
•120
•110
•too
E
- 90*
O
o
- 80
- 7O
- 60
- 50
- 40
- 3O
- 20
- 10
-36
-34
-32
•30
-28
•26
•24
•22
•20
E
a
a.
' IB 0
I
- 16
• 14
- 12
- 10
- 8
- 6
• 4
- 'e.
• O
II
C0z,p»rc»nt
13
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-28
9
8
7
6
i 5
!
IA
Soehoroch :
*
3
2
•
0
.oi,., C200Z . w
- /£__ « >?/} ^/
340-
320-
300-
280-
260-
240-
220-
20O-
€
S 180-
M
O
- Z 160-
140-
120-
_ !00-
^tf^^^"^ 80-
S#^ 60-
40-
CO i.5H>°^ 20.
WC ^ _x
-ISO
-I7O
-160
-ISO
-140
•130
-120
-110
-IOO
E
a
• 90^
O
o
-eo
- 70
• 6O
•50
- 40
- 30
- 20
- IO
•36
-34
-32
-30
-28
-26
-24
-22
-20
- 16
- 16
- 14
- 12
- 10
- 8
- 6
- 4
- 2
•0
a
10 II
C02,P*rc«nt
12
13
14
IS
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-29
•
e
7
6
i *
£
U
Bochorc
»
3
2
•
0
«
Boil.r C 2.0 O2. ,. g(r).i.t v ur
34O-
- 320-
300-
- 280-
260-
240-
220-
_ 2OO-
E
a
a ISO-
2
- 160-
140-
- 120-
100-
*^^*^*" 8°"
-^r**^ 60-
40-
tfC__*- 20-
i H. i ''L i co '^f"*^* i i t i
i 7 8 9 IO II 12 13 14 1
CO(,P*rc«nt
-ISO
-170
-160
•150
•I4O
•130
•120
•110
•IOO
E
a
• 90^;
0
o
-80
- 70
- 60
• SO
• 40
- 30
- 20
- 10
1°
•36
-34
-32
-30
-26
•26
•24
•22
•20
-IB
• 16
• 14
• 12
• 10
• 8
- 6
• 4
- 2
• 0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF C02
-------
H-30
i*U
Boit.r CZOOZ •-mau. }t HC
F...I CrtLS. LMd 6 b /O _ _„ fl N0
340-
- 320-
300-
— 280-
260-
- 240-
220-
20O-
a
* 180-
o"
- * 160-
I4O-
- 120-
IOO-
K|OlC_ ^
J^*S-^*'^ T*->.
^^^ 80-
^ — 60-
40-
o
„ ^ HC „ 3 "-
_..... L i^^-^*iS"«ote | | i i
6 7 8 9 10 II 12 13 14 1
-180
-170
-l«0
-ISO
-140
-ISO
-120
-no
-100
E
a.
- 90*
0
o
- 80
- 7O
-6O
• 50
- 40
- 30
- 20
- 10
J°
-36
•34
•32
•3O
-28
-26
-24
-22
-20
a.
••»:-
• 16
• 14
- 12
- IO
- 8
• 6
- 4
- 2
• 0
COj,P«re«nl
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler C20Q?>
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel Are. 2,
fwrcant
10).
1
I
go.
j_
&.
3Z
Firing
Rat*.
»*
—2°-5
7/.S-
V£3
3l.o
Fuel
Tamparatura,
F
IIS
86
78
78
Combustion Condition!
Smoke No.
/9
7J
/.fl j
r>y 1
co2, %
yj.2.
,*.*•
/0.3
11.2.
2./ 1 /2.i
2.0 t
3.0
V.9
V./
Zo
/.2
/. 6
V.5"
2-9
3.r
3.2.
3.2L
V.o
6.0
12.1
13,3
/3.9
o2.%
3.Z
/6
77
6.0
?.o
1.9
33
2.4
1
76
9.Z
/o.r
/'•9
13.1
i.k
7.5
9.7
I2.o
/2.6
/3.o
/0.9
&.J
<.5T
V.V
2.9
H.8
it>.<)
7.6
V.3
3.e
3.0
Stack
T«nper«tur«,
F
388
382.
365-
3F8
3So
351.
3SC
317
320
3o?
3oS
3oo
298
28/
278
zse
26*
2f$
2&o
GBSOOUJ Emioions, ppm
CO
o
//.
0
O
O
o
0
0
o
o
o
o
o
7
A
o
o
o
o
HC
AS"
Y.0
3.0
2.5-
2.5
3.0
3.0
3.0
2.5-
2.3
2,2
2.0
2.0
Z.o
6.0
7.0
«.s
9.0
6.0
NO
8f.
86.
*Y.
4S
70.
70.
7/.
7o.
vv.
Jo.
rv.
5&
^ff.
36.
V/.
^9.
rv.
rv.
55.
N0x
5^.
^s:
^.
67
7/,
70.
7J.
73.
Hi.
SI.
Si.
59.
61.
V3.
11.
So.
5$,
Sb.
56.
soz
92.
/o5T
70.
7V.
So.
0<.
fffi>.
9V.
5V.
6V.
72.
83.
92.
«.
5Z
70.
^
8V.
92-
Paniculate Loading, mg/tm
>rob« + filter
_-
^^
_
_
_^.
//.z
—
—
—
—
—
—
_
_
—
-
—
—
Total
—
—
—
—
—
22.2
—
-
_
—
—
—
—
—
-
—
—
-
—
CO
-------
H-32
. 2
M
?4
I
180
IO
12
13
15
34
32
30
28
26
24
22
20
I
i
:
16
14
12
10
8
6
4
2
O
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-33
BoiUr.
C2.003
fumi No. Z.
20%
• Smok*
o CO
X HC
A NO»
180
170
160
'ISO
140
130
120
110
•100
E
a
90a.
O
u
80
70
60
50
40
30
• 20
10
0
-36
-34
-32
30
28
26
24
22
20
E
•ij
16
14
12
10
8
6
4
2
0
//c
CO
4O
20
IO II
CO^.pcrcont
12
13
14
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF C02
-------
H-34
Boiltr.
C2QQ3
A/o. Z.
%
• Smok*
o CO
X HC
A NO,
I BO
(TO
•160
•ISO
140
130
120
•HO
IOO
a.
901
O
o
80
70
60
SO
4O
30
20
IO
O
-36
34
i-32
-30
-28
-26
-24
-22
-20
-x-
I ^
Co ^i
E
a
340
320
30O
28 O
260
24O
220
ZOO
I8O- -
160
140
120
too-
8O
60
40
20
IO II
COj,P«rc»nt
12
13
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H~35
9
8
7
6
! 9
to
u
i4
S
at
3
2
1
0
e
Boil*? C2LOO3 * Smoht w ur
Fiul N*. 2. Land 35 /c, « rn A MO.
340-
_ 320-
300-
— 280-
260-
- L 240-
/ 22O-
_ / 200-
/ E
/ » ISO-
/ °*
L * I6O-
« . / 140-
5/woAe. -/
120-
IOO-
X
^^ 80
— *-"~ ' AlOi ? G°-
- -— — — "~*~~~
I1 — 1 i ^L J _l 1 ^ i. 1
7 8 9 IO II 12 13 14 1
•180
•I7O
-160
-ISO
-140
-130
•I2O
•110
-IOO
E
a
O
U
- 80
- 70
- 6O
- 50
- 4O
- 3O
- 20
- IO
J°
-36
•34
-32
•30
•28
•26
-24
•22
•20
E
a
X
• 16
- 14
• 12
- 10
- e
- 6
- 4
- 2
• 0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler C2003
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel CR
Load.
percent
97
77.
5-0.
33.
Firing
R.t«,
gph
83.0
^6Lo
V3.o
2ft 2
Full
Temperature,
F
/Vo
tH3
Ho
t3?
Combustion Condition
Smoke No.
Z.i
v./
2.9
2.7
3.2
F,2
co2>%
/2.2
/2.7
9.5
ic.8
n.o
13*
!
!
2.9
2.2
2.6
3.3
£7
V./
3.7
3.S
3.9
*.¥
7.V
9.0
9,9
//,9
<3.fc
^.2
72
a*
9.3
//.e
o2.%
V-2
2.5"
a/
^.2
V.5"
2.e
M3
9.Z
7.JT
V.9
2.6
/2.V
;/.3
?.y
g.3
5"./
Stack
F
36Z
•378
3c»
3fz
3V8
svr
3/r
3so
3'S
291
29Z.
28o
27?
Z?o
2.
117,
12+
IH8.
Ho.
/go.
I8H.
9Z
112.
m.
138.
iSo.
NOx
2o3.
2/5".
/6/.
173.
190.
/97.
/26,
/V«.
;B2.
iBo.
>85
99.
ni.
131.
HI.
M*
so,
«o.
fflo.
Voo.
vw,
5-20.
set.
2%.
370.
HIO.
Sao.
570.
236.
260.
3i°.
390.
S~oa.
Particulaw Loading, mg/sm
•robe + filter
—
—
—
286.
—
—
—
—
—
—
—
_
—
-
Total
—
—
—
—
3o5.
—
—
—
-
—
_
—
—
-
—
a
i
co
OJ
-------
H-37
...... CZ003
FU.I Reference. CR
100%,
I
o co
10 II
CO^.ptrcinl
12
13
X HC
A NO,
340- -170
320- -160
30O- -150
28O- -I4O
260- -ISO
240- -120
220-'MO
200- -IOO
Q.
14
tt 180+ 9°*
O
160--80
I4O- • 70
120- -60
100- • 50
80- • 40
60- - 30
40- • 20
20+ 10
• 0
•180
15
36
34
32
-30
26
24
22
20
{
I
16
14
12
10
8
6
4
2
0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF C02
-------
H-38
Boiler.
C20Q3
Reference C.R tnait 8O%
i
t
• Smoke
O CO
X HC
A NO,
CO
180
10 II
COg, percent
12
13
340- -170
320- -160
300- -ISO
280- -140
260- -130
240- -120
220- -110
20O- -IOO
E
L a
' ISO- - 90"i
• s
160- • 80
140- - 70
120-- 60
IOO- - 50
80- - 40
6O- - 30
40- - 20
2O- - IO
0
36
34
-32
-3O
-28
-26
-24
-22
-2O
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-39
FU.I
CfZ
52. %
• Smofc*
O CO
X HC
A NO,
180
•I7O
•160
•ISO
•I4O
130
•120
•HO
•IOO
E
a
90 *i
O
o
80
70
60
50
34O
320
3OO
280
260
240
220
200
• 180- -
i
160
I4O
120
100
80- - 40
6O- - 30
IO II
COg, percent
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-40
in
1.
C2003
fZe-fereAce, CK.
• Smoke
O CO
X HC
6 NO*
180
IO
13
14
340- -170
320- -ISO
300- -150
280- -140
260- -ISO
24O- -120
220- -110
2OO- -IOO
I
I8O- - SO'i
o
"
leo- - so
140- - 70
120- - 60
100- - 50
80- - 40
60- - 3O
4O- - 20
20- - 10
O
96
34
-32
-30
-28
-26
-24
-22
-20
15
SMOKE AND GASEOUS EMISSIONS FOR
BO9LERS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO-
Boiler
C2003
Fuel
Load,
percent
foo.
79.
S^.
3V.
Firing
Rita,
gph
83.0
6ZS-
V3.o
26.0
Fuel
Temperature.
f
Zo8
2o8
2ot>
199
Combustion Conditions
Smokfl No.
317
3.7
V2
y.r
16
V.3
y.3
y.2
y.z
57
z*
2. a
3.o
3.Z
3.3
3.7
y.r
£3
V./
y.y
V.O
y.7
577
V*
7.r
coz, x
//.s-
//.*
;3.o
/3.V
9.2
A>. 3
//.o
//.9
/2.T
X3.3
7.2
*./
9.0
9.7
y/3
/2.o
/2.3
/3.fi
6.7
73
ff.2
9.3
/o.9
X/2
/i'.S'
o2, %
5:2
V-8
?.Z
2.8
ff.7
7/
(£.2
£o
v.z
3.Z
//2
/o./
9./
75
s:g
r.o
V.6
2.7
I2.o
//.2
9,7
ff.3
£.1
*3
y.o
Stack
Tamp*r«tura,
F
378
36o
37*
3£F
3/3?
3So
35o
3fS
•350
3fO
33Z
330
3*0
32i
3/r
3'8
3'5~
3'0
3/o
32i
311
3oo
295"
292
2fff
Guooui Emiuions, ppm
CO
It,
10.
8,
n.
/3.
//.
to.
9.
10.
to.
13.
e.
7.
6.
y.
3.
3.
S1.
29.
23.
2.0.
IB.
/6.
/7.
2Z,
HC
/.y
A3
y.y
2.o
2-2
2.2
2.2
3.2
2.3
2.r
0.9
0.9
o.9
o.9
0.7
/.r
0.9
y.o
*.e
£.8
<5.9
7./
7.o
73
7.3
NO
26/.
2<3.
279.
2*v.
Zol.
2Z3.
23V.
zro.
25-5:
2io.
/y/.
fto.
177.
/9o.
209.
aoa.
2/A
2/3.
/39.
xr/.
y/,
soz
//yo.
/I to.
12 to.
t3io.
880.
96o.
/O&O.
//5"o.
//So.
/2^
430.
720.
000,
ff?0.
Io30.
/O.
112.0.
I2ia.
600.
&Q.
76o.
860.
—
//oo.
—
Paniculate Loading. mg/nn
Probe + filter
_
_
—
_
—
_
—
72.Z.
_
—
—
—
—
—
—
—
—
—
—
-
—
—
2.07.
—
Total
—
—
—
~
—
-
—
7W
_
—
—
—
_
—
—
_
—
—
—
-
—
-
30*:.
_
—
a
-------
H-42
Bail., C2OO3 •-mom tt HC
A/«.6 u^ 1 00% ,„ ftf|Ca
340-
320-
3OO-
H^Q* A_<%^ 280-
'"^ 260-
240-
220-
_ 200-
o.
•^ * 180-
<2£*S^ * 160-
140-
- I2O-
100-
- 80-
60-
40-
^^~===^==^' 2°
1 1 1 1 1 1 ^ 1 1
-180
-I7O
-160
-150
-140
-I3O
•120
-MO
-too
a
- 90 «i
0
o
- 80
- 70
- 60
- 50
- 4O
- 30
- 20
- IO
-36
•34
•32
-30
-28
-26
•24
-22
-20
-,.
- 16
• 14
- 12
- 10
- 8
- 6
- 4
- 2
- 0
tt
10 II
C0z,p«re«nl
12
13
14
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-43
»Bi... C 2.0 03
i s
!
a>
I
• Smoke
o CO
X HC
A NO«
IO II
C02,P«rc«nt
12
13
ieo
14
340- -170
320- -160
300- -ISO
280- -140
260- -130
240- -120
220- -MO
200- -IOO
^
: ISO- - 90"i
; s
I6O- - 80
I4O- - 70
120- - 60
100- - 50
8O- - 40
60- - 5O
40- - 20
20- - 10
0
-36
-34
32
30
-28
26
24
-22
20
ie!
16
- 14
12
IO
- 8
- 6
' o
z
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-44
Boiler.
C2003
F...I Mo. 6
• Smofc*
o CO
x HC
A NO,
180
IO II
C0j,ptre«n)
12
14
34O- -I7O
320- -160
3OO- -150
280- -140
260- -130
240- -I2O
220- -HO
20O- -100
E
Q.
• 180- - 90"i
' 8
I6O- • 80
I4O- - 70
120- - 60
IOO- • 5O
80- • 40
60- - 30
40- - 20
20- - 10
O
36
34
-32
30
-28
-26
-24
-22
-2O
-18,
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-45
Boll«r.
I4
8
C2003
AA.. 6
• Smoke
o CO
ric
-* X-
-tt-
X HC
A NO,
ISO
10 II
C02,p«rc»nt
12
14
340- -170
320- -160
300- -150
280- 140
260- 130
240- -120
220- -MO
20O- -IOO
' 180- 90«i
r 8
160- - 80
140- • 70
120- • 60
100- • 50
80- - 40
6O- - 30
40 - 20
2O- - IO
O
36
34
32
30
28
26
24
22
20
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler C2003
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel
Load,
percent
XX.
83.
Firing
Rat*,
Cfh
J2>HOQ.
10,000.
1
1
52.
35:
Fuel
Temp«rituri,
F
—
-
Combustion Conditiom
Smoka No.
0.0
a.o
0.0
0.0
0.0
o.o
0.0
O.o
li °-z
. • ii
6Z80.
V25"0.
—
-
o.o
O.O
0.9,
75-
0,0
o.o
0.0
0.0
S.O
co2, %
9.4
IO.O
n.i
//.v
7.6
9.0
^97
/0.0
//./
7V
*-9
LJ°-/_|
/o.7
«.f
ff.3
9-2
/O.O
&£—
o2.%
V.o
313
y.2
0.6
7.9
5-J
3.6
3.1
/.2
8.2
S.I
3.2
<5.V
/0.2
6.6
V.9
3-3
0.7
Stack
Tamparatur*.
F
390
365
18?
361
370
36o
3f0
358
3?S
3/5T
3/<»
303.
29;
ZGI
261
217
263
2to
Gateout Emotions, ppm
CO
/.
/.
9.
/ozs:
2.
i.
A
£
8.
2..
2.
2.
>IZHO.
5.
B.
7.
7.
30*.
HC
x.z
rolw + filter
—
—
_
_
—
—
_
H.o
_
—
—
—
—
_
—
—
_
Total
—
—
_
— .
_
—
_
IH.7
_
~
_
_
—
—
_
—
—
_
a
i
^
03
-------
H-47
•
B
r
6
i 5
!
Boehoraeh !
w *
2
1
0
Be,,., C20O3
PU.I 6rA& tMt 99%
• Small* * HC
0 CO A NOi
34O-
_ 320-
300-
_ 280-
-
tf°* J
A^"- A^
/
-
260-
240-
220-
2OO-
E
a ISO-
M
o
Z 160-
140-
120-
100-
80
6O
4O-
^ / >^c oV
, , ^^e -:^^>^>U^ , , ,
-180
•I7O
-160
•150
140
•130
•120
•110
•IOO
0.
• 90 »
O
u
• 80
- 70
- 60
• 30
• 40
- 30
- 2O
- 10
-36
-34
•32
-SO
-28
-26
•24
•22
•20
a
•'•5
X
• 16
• 14
• 12
- 10
• B
- 6
- 4
::
10 U
C02,P*re«nl
12
13
14
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-48
ftall.r
i 9
o
i
• Smok*
10 II
C0z,ptre*nl
12
13
X HC
14
40-
180
340- -I7O
320- -160
300- -190
280- -140
260- -130
240- -I2O
220- -MO
200- -100
E
' ISO- - 90*
• 8
160- - 80
I4O- - TO
120- - 6O
IOO- • SO
80- - 40
60- - 30
20
56
-34
32
-3O
-28
26
i-24
-22
20
"o-
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-49
C2003
2
f
in
-*-
5o%
• SrnoK*
O CO
10 II
C02,p*re*n<
12
X HC
A NO,
I
160
14
340- -170
320- -I6O
300- -ISO
280- -I4O
260- -130
240- -120
22O- -110
20O- -100
I
ISO- • 90*!;
S
ISO- - 80
I4O- • 7O
120- - «0
IOO- - 50
80- - 40
60- - 3O
40- - 20
20- - 10
• O
36
-34
32
-30
IS
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-50
Boiltr.
C 2.00 3
ISO
10 II
COz,P»rcont
36
34
-32
30
28
26
-24
•22
•20
I
i
i
3
16
14
- 12
- 10
8
6
4
2
0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Boiler C2QOV
Fuel
. 2-
Load,
percent
99.
8L
Firing
Rate,
»pr»
23.V
,
/9,2
i
\
63.
Y6.
/y.s
/0
I.B i soo
,_ 2./ 1
ff.6
ll.o 6-1
I2.o
\I2,T
J3.i\
H.o
7.1
8-f,
/o.o
10.8
12.0
12.8
11.8
t.s
7.9
$.0
/O.6
II.S
•y.f
V.3
3.a
//,3
9./
!_ 7./
6.1
y.s-
3.7
A 2.
/A7
lo.i
8.7
1.3
5.1
171
V?o
vv/
Hz8
H2B
y/z
Voa
y)8
Vo2.
386
379
Jfff
338
200
3<5"
jfo
33i
32 Z
Gacaous Emissions, ppm
CO
0
O
a
0
3o.
o
o
o
o
o
VY.
M.
o
o
o
o
o
29.
/2s;
0
o
o
o
HC
3.2.
3.2
38
3.8
3.8
3.Z
3.3
A 8
5-7
3.r
3.6
570
2.i
2.7
2.7
2,5"
2.8
V.o
/o.o
/.8
/7
2.3
/.S"
-*-
NO
90,
//o.
yo9.
/oV.
gtf.
loo.
Io3.
1 00.
lo2.
99.
y«.
68.
78.
8H.
91,
97.
99,
VX
6H.
71.
957
M.
N0x
too.
106.
III.
112.
loS.
86.
lot.
/oY.
/o/.
;oj.
99,
Y8.
£8.
78.
8£
9V,
97.
99,
Y3.
61.
71.
9Y,
88.
so,
97
/oV.
/o7.
/26.
79,
94.
loz.
107.
lib.
/2Y.
r*;.
72.
8Y.
92.
/o2.
108.
128.
5b.
71.
8°.
?*,
/o2.
Paniculate Loading, mg/sm
•robe + filter
—
__
—
—
—
—
_
9.3
—
—
—
—
—
_
—
—
—
—
—
—
-
6.5-
-
Total
_
—
—
—
—
—
-
/&.£
—
—
~
_
_
_
—
_
~
—
_
-
—
2512.
—
a
Ul
-------
H-52
Fu.1
8
I
• Smofc*
o CO
X HC
A N0a
10 M
C0z,ptre»nt
12
13
14
180
170
16O
ISO
140
130
•I2O
•110
IOO
E
o"
o
80
70
• 60
• 50
• 40
• 30
• 2O
• 10
• 0
36
34
32
-30
28
-26
-24
22
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-53
B.II.. C 3.00V
FiMl.
Ma.2.
Load.
81 %
i 5
I
i'
8
to
• Smoke
o co
X HC
A NO*
ieo
I7O
- -160
•150
140
ISO
120
no
100
E
a
90^
O
o
80
70
60
50
4O
30
20
10
-36
-34
-32
-30
-28
26
-24
-22
20
o
I
IO II
C02,p*re«nl
12
13
14
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF C02
-------
H-54
36
34
32
30
-28
26
-24
-22
-20
10 II
COg.ptrccnt
14
IS
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-55
BOIL,
• Srnok*
O CO
X HC
A NO*
10
12
13
14
340
320
300
Z8O
260
240
220
200
180
160
!40
I2O
100
eo
6O
40
20
180
•170
•160
•150
I4O
130
120
•110
100
3
80
70
6O
50
40
3O
20
10
0
36
•32
•30
•28
26
24
22
20
a
' IB J
Z
16
14
12
IO
8
6
• 4
2
O
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Boiler C2.0OH
Fuel
CR
Load,
percent
IOO.
82.
60.
«8.
Firing
Rate.
gpn
22.3
18.3
/3-V
/a 7
Fuel
Temperature,
F
//6
—
//9
//9
Combustion Condition*
Smoke No.
3,6
3.o
3.1
3.3
3.V
2.S-
2.9
3.r
6.7
3.r
2.9
3.1
3.Z
*3
£.7
*3
?.«
3.6
y.5"
5.o
7.V
8*
$.0
/o.r
/2.3L
pl.o
y.7
£3
B.o
/o.o
//9
o2, %
6.0
f.f
V-2
3.3
9
3W
383
Ito
3V0
38L
3*8
3?o
33o
316
GaMOin Emixtionl, ppm
CO
O
O
O
O
/.
0
O
0
V7.
£•.
/.
o
O
o
3.
So.
i.
e>
0
2.
HC
6.2
i.3
o.
380.
110.
tffo.
5(0.
I5&.
260.
320.
Vos.
5"o«.
Paniculate Loading, mg/tm
>robe + filter
—
—
_
—
—
—
^7.r<
—
—
—
-
—
-
—
—
—
—
-
-
Total
—
—
-
—
-
—
JO*
—
—
—
—
—
-
—
_
_
-
-
—
a
•
en
01
-------
H-57
Bail*, C^2,OO/ T5r-"- v ur
8
7
6
f S
I
(/»
£
U
j4
m
3
2
,
O
340-
_ 320-
300-
- 280-
260-
^^J^J^3^^
220-
_ 200-
E
a |8o-
K
O
- Z 160-
< ^tf, ««•-
- ^V— •^^^"^ I2O-
100-
80-
-_r it "^ «
* * '» * 60.
40-
20-
1 1 1 1 ^ _U 1- C° -1 1
-170
•160
•150
•140
•130
•120
•no
•100
E
a
• 90 °:
O
u
• 60
- 70
- 60
- 50
• 40
- 30
- 20
- 10
-34
-32
-30
•26
•26
-24
•22
•20
a
a
I
• 16
• 14
• 12
- 10
i- B
• 6
• 4
• 2
. n
6 7 8 9 10 II 12 13 14 15
CQZ, percent
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-58
36
34
32
-30
-28
26
-24
22
2O
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-59
•»...,
180
•36
-34
-32
-30
-28
-26
-24
-22
20
I
i
18,'
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-60
C2QQH
v>
CO
• Smoke
o co
X HC
A NO.
340- -I7O
320- -160
300- -150
2BOH
ISO
-I4O
26O- -I3O
240- -120
220- -110
200- -IOO
E
: ISO- - 9OC
' S
160- - 80
140- - 70
i20- - 6O
IOO- - 50
80- - 40
60- - 30
4O- - 2O
20- - !O
36
34
-32
-30
-26
26
24
-22
20
I
i
i
- 16
14
12
10
- 8
10
12
14
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler C2OOJ
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel V». 5~
Load,
percent
to*
85.
(,i.
50.
Firing
Rate.
OP"
22.5-
I$.H
13.8
tO.Q
Fuel
Temperature,
F
HB
12.0
12.0
12.0
Combustion Conditions
Smoke Mo.
V.7
V.V
6.2.
v.*
5.o
y.9
5.o
5.7
£3
3.2.
3.3
3.9
5.1
6.5
f.H
V.9
(>.o
co2, %
//.3
12.0
I3.S
\^—
/o.o
L/0.8J
12. 0
/3.G
75"
8.7
9.?
10.7
I Z.I
5:9
<-9
8.1
12.0
oz.%
5.5
vs-
2.3
S.^
73
iS.z
V.5
J.V
L_/<3.5"
\&&
7.1
63
V.3
/3./
//.£
9./
V.6
Stack
Temperature^
F
V73
V<{3
fft>
V5S-
KS
HiB
Ht8
Hoo
V27
y/y
y»r
395
55o
37Z
-?*-*
3W
319
Gaseous Emissions, ppm
CO
/.
O
1.
2.
O
0
0
o
II.
/.
O
o
o
?02.
lt>.
3.
2.
HC
V.3
Y.'
3.8
3-5"
?.•/
3.3
7.7
*3
V.8
V.S
r.o
V.8
V.fl
/Z.o
V-2
2
V.Z
NO
27«.
293.
307.
2/9.
2W.
2«.
29/.
30S.
Aft
2«>A
2^ft
25o,
294
/o/.
/Vft
/9i.
2«/.
N0x
280.
29fl.
?IO.
223.
2HL.
2.68.
295".
3^7.
/7/,
2o£
2/7.
2Vfl.
295:
/o9.
/5"Y.
/99»
2SV.
soz
iuo.
1180.
/350.
8?o
97o-
/o5"o.
Hto.
1270.
7iO,
850.
930.
1050.
1210.
5HO.
6t*.
&50,
1200.
Paniculate Loading, mg/sm
Probe + filter
—
—
—
—
—
_-
/3^
—
—
—
_
—
—
_
—
_
—
Total
—
—
—
—
—
—
202.
—
—
—
-
—
—
—
_
_
—
a
-------
H-62
Bail.r
C200H
w%
• Smoke
O CO
2
o
8
o>
X HC
A NO,
ISO
IO .11
COZ,Percent
<2
13
14
340- -170
320- -160
3OO- -ISO
28O- -I4O
26O- -I3O
240- -120
22O- -HO
200- -100
E
a
' ISO- - 90 *
' s
160- - 80
140- - 70
I2O- - 60
IOO- - 50
8O- - 4O
60- - 30
40- • 2O
20-- iO
0
15
36
34
-32
-30
-28
-26
24
-22
-20
I
i
i
- 16
- 14
12
- IO
8
6
- 4
• 2
- 0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-63
B.il.r C20QV
F...I M».5"
0)
I4
%
• Smoke
O CO
-x-
X HC
A NO,
(0
12
13
14
340- -170
320- -160
300- -150
280- -140
260- -130
240--120
220- -110
ZOO- -IOO
E
a
a. (SO- - 9O
o:
Z 160- - 80
I4O- - 70
120- - 6O
IOO- - 50
SO- - 40
60- - 3O
40- - 20
20-- 10
O
180
-36
-34
-32
-30
-2B
-26
-24
-22
-20
I
-IB.1
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-64
•...-
F...I
Lood.
i 5
•
1
in
8
CD
• Smoh«
O CO
-K-
X HC
A NO,
a
340
320
300
280
260
24O- -
220
200
180- -
160
140'
120
100
SO
60
40
20
10 li
COj» ptrcent
13
14
180
•170
•160
•ISO
140
•130
120
MO
100
E
a
90 «i
O
O
80
7O
60
SO
40
30
20
IO
0
36
-34
-32
3O
-28
-26
-24
-22
•20
a
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-65
B«H., CZOOH
FU.I M>. 5"
E
in
I
• Smok«
o co
X HC
A NO,
10 II
COj, percent
12
13
14
340
320
300
280
260
240
220
200
180
iro
- -I6O
•I5O
140
130
120
110
100
180- -
160
140^
120
100
80
60
40
20
80
7O
6O
SO
40
30
20
10
-36
-34
-32
-30
-28
26
-24
22
20
'8
16
14
- 12
- 10
8
- 6
4
- 2
0
a
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF C02
-------
Boiler
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel
Laid,
(MTCHIt
96.
,
76.
Firing
Rite.
c-fH
3030.
2*/«5C.
\ ..
.
'
I
FM
F
—
Combuition Coniiitiom
Smoki Ko.
o.;
*e
COy %
3.5
o.,? ! /o.y
ftc ;*7
ii
||
ii
«i.Z
!l 0,0 j 70
ll O.o
\
o.c
^
\ 0.3 i //.i
«v*
^.S"
5.3
3-3
2.3
,'f.C
5.2.
£*
3.6
StMk
F
Hil
Vi£
W?
ViS
V2Z
if o<)
tj0$
'.' . i
1 \ I
57,
3r.
/8OO.
1100.
ii
— i 6.0
—
^* o
^. o
^. o
0.y
.o
ao
<3.O
O.o
nw.
HC
2.8
2.8
6.0
/&.0
3.1
2.9
2-7
?.&
gfo.
70.
x.e
2.0
30.
2oo.
J200.
toSo.
>3o.
V.f
t.7
i.6
V.o
370.
NO
fb.
5).
5"V.
5-V.
v/.
5-0,
*f7.
*t5.
s.
21.
VS.
VV-
Vft
3.
2.
3.
/A
5V.
V8.
V».
36.
*>»
«-
?3.
5-9
V3.
Y9.
52.
5"o.
SI.
21.
3L
f8.
¥7
Zf.
12.
/f.
16.
3),
J2.
H8.
H&.
1L
*°2
o
c
c
9
O
O
O
0
25:
o
0
o
o
/8.
o
0
0
o
0
o
o
/<>•
Pinicutau Loading, mg/im
Vote + filMr
—
—
—
.^
—
—
_
2.2
—
—
—
—
—
_
„
—
-
_
—
-
—
Total
—
—
—
—
—
—
-
£.2.
—
-^
—
~
—
•
_
—
—
-
—
~
—
a
i
O5
O5
-------
H-67
Boll.r
C200V
teo
36
34
32
30
28
26
24
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-68
• SmaM
0 CO
W
i'
i
12
13
X HC
A NO,
14
340- -I7O
32O- -160
300- -ISO
280- -140
26O- -I3O
24O- -120
220- -HO
200- -IOO
E E
£ ISO- - 90*
; o
o o
* i60- - BO
I4O- - 70
120- • «0
IOO- • 50
80- - 40
60- - 3O
40- • 20
20- - 10
O
180
34
-S2
30
^-28
-26
-24
22
-20
I
i
""«
- 1C
14
12
- 10
- a
6
4
2
a
IS
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-69
Boiler.
I-
I
ID II
COj.psrcmt
• Smak*
O CO
13
X HC
A NO,
14
I
180
340- 170
32O- -160
3OO- -150
Z8O- -140
260- 130
24O- -120
22O- -110
200- -IOO
I
ISO- • 90*
8
ICO- • 80
I4O- - 70
120- • 60
tOO- • 50
80 - 40
6O- - 30
40- - 20
20- - 10
O
3«
34
32
30
26
26
24
22
20
E
•5
(5
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-70
Boiltr.
-------
Boiler
C2005-
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel A/*. 2.
Load.
peccant
99.
j
Firing
Rate,
W>
30.6 1
j
i
i
_._?*.
1 ... _.
I
t-
i
So.
\
|
I
•
i_ 2*.
.
23.4
u
15.1
Fu«l
Termwatura,
as
Combuition Condrttona
Smoke No.
i_a* J
[ A3
3.fc
!
ii
i;
I*
«9.T
L . _•
i O.o
~1 *-e
co2. r.
i2J
12.^
9.6
-'H*
o2.*
V3
?.7
2.7
75"
Stack
F
333
330
32&
3*8
4'.? ?oJ
5;y i jo*
I O.P i /,2,e> i V-3 I ^OO
l! /.7 1 /3.3 \ 2.i i 29i
#3
i
79 81
7.1 \ /V.0 j A'3
0.0
C.o
0.0
l_ 0-0
o.o
7.1
0.0
i 0.6
\
I] & ®
1 ^•7
j
ii
i!
8.2.
9.5"
/o.7
/2.o
/2-9
^v./
«r
9.7
|_7.9
<.i
y.3
J.o
//.7
/O.O
/2.o 73
/3.6 2.5"
. 1
2&)
279
27V
2ta
2tV
262
2*6
237
23/
22V
^ 2ZO
GaMout Emotions, ppm
CO
3.
n.
127.
o
o
0
o
IB.
o
o
o
o
o
> 12.30.
o
o
o
>ll$o.
1
i
1
1 «
HC
2.5"
2.5
2.8
2.3
2.3
2.3
2>i
2.r
7.5"
IS
/.&
2.0
y.o
3,2.
3.7
y.2.
v.3
NO
/33.
(28.
/23.
//ft
/23.
/2V.
12.5.
122-
//9.
/»S.
/26.
/39.
Hi>.
/V8,
/y?.
/25".
/«.
t?9.
t3o.
«>x
/3A
/3o.
/27.
/20.
/25T
/26.
127.
125,
/22.
//O.
/29.
/y/.
iUfk
/5o»
117.
127.
15$
IBt-
i3i.
so2
/90.
X95:
205:
/V3.
/55.
/<9.
/^.
Zoo.
235.
/•$!.
152.
/89.
23o.
Paniculata Loading, mg/tm
-------
H-72
......
C200fT
Load.
loo
i-
• Smok*
OCO
.Ate,
XHC
* NOs
IO
II
12
19
94O- -I7O
920- -ISO
300- -ISO
26O- -I4O
260- •ISO
240- -120
220- -110
2OO- -100
* I
» 180- • »0C
o S
* i«o- • to
I4O- - 70
120- • «O
100- • SO
80- - 40
60- • 3O
40- • 20
20- • 10
•0
100
3«
34
92
30
28
2«
•24
22
20
I
i
i
'"«
J
16
14
12
to
• a
• e
- 4
a
•rf
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-73
Boil«r.
r~, M>.2.
Lood.
7^
!«
if
• Smoke
o CO
XHC
A NOi
,^-f
IO
II
12
13
ISO
I7O
(60
ISO
I4O
ISO
120
110
100
E
90*
O
u
••0
• 70
• CO
•90
• 40
•30
• 20
• 10
:0
3«
34
32
30
28
2C
24
22
20
I
••;
16
14
12
10
8
6
4
2
0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-74
Bclltf.
.....
C2005*
/Vo. 2.
I
• Smoke
o CO
K HC
A NO!
180
I7O
•160
•ISO
I4O
ISO
•120
•MO
•IOO
E
a
90*
O
u
• 80
• 7O
• «O
•SO
• 4O
• 3O
• 20
• IO
IO
12
13
14
IS
36
34
-32
-30
28
-26
-24
22
-2O
I
i
•'•t
3
- 16
• 14
• 12
- IO
e
6
4
- 2
-O
c
•5
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-75
•oilw.
02005"
i to
15
3C
34
32
3O
28
2C
24
22
20
I
i
<
:
1C
14
12
10
8
• 4
2
0
a
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler C ZOOS'
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel
Lo*d.
fMTGMll
... ?«-...
j: •/*_,
SI.
2V.
Firing
R«t«,
B*
2*8
FlMl
Timp«ntura,
F
/o9
Combuttion Conditioiw
Smoke No.
2.V
V./
fZ<-i
coyx
//.?
/2.V
/3.9
i
i
i
^~ ; • !
\2?S\ Ho
&.r*
7.1
2* 1
1 2'°
L 2.Z
?s
6.8
in
/09
9J
%G
or%
V.7
2«5
/fl
8.S
75
/t.Z J5:<5
/2.i • ¥.f
/3.9 £.P
\ 1
•
3.3
2-V
/.8
2.1
2.5"
1.1
3.6
i.9
^.VH
\U
LI 3-V
7.oJ
^.v
73
^.a
//./
/i./
^3.8
5". 9
7.9
8.3
/o.3
IZ.I
13.7
\_l.
0.
0.
rotaa + filter
—
_
—
—
—
—
*V.*
_
—
_
—
—
—
..
—
—
^.
—
—
—
Tom
—
—
—
—
—
—
*rf.r
—
.^
—
_
—
—
—
—
—
_
_,
_
—
a
Oi
-------
H-77
...... C20Q5-
r^.. Reference CR .
• Srnok*
O CO
X HC
A NOi
HC
34O
320
3OO
280'
260-
240
220
20O
:ISO-•
I6O
I4O
120
100
80
60
4O
20
160
•170
•160
•ISO
140
ISO
120
110
IOO
a
90°;
o
o
80
70
60
50
- - 40
30
20
10
IO II
COz,p»'C»nt
12
13
14
IS
36
34
-32
30
26
26
24
-22
20
C
<
16
14
12
10
8
6
4
2
0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF C02
-------
H-78
•oiler.
C2005"
Re-ference.
78 K
• Smok*
O CO
XHC
A NOi
a
340
320
300
280
260
240
220
200
I8O- -
160
I4O
I2O
IOO
80
60
20- -
•O
II
12
13
14
180
170
160
ISO
140
ISO
I2O
•IIO
IOO
a
90*
O
o
80
ro
60
so
40
30
20
10
O
36
34
32
30
28
26
24
2O
I
i
18.
\
16
14
12
8
6
• 4
2
0
o
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-79
».»., C200S
e.. CR.
• Smok*
oco
I4
X HC
A NO,
a
340
320
3OO
28O-
260
24O
22O
200
ISO- •
160
I4O
ISO
IOO
60
60
40
20
100
I7O
160
ISO
140
ISO
•I2O
•MO
IOO
o
o
60
70
6O
30
40
30
2O
10
36
34
32
30
28
26
-24
-22
20
16
16
14
• 12
- 10
IO
II
12
13
14
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-80
Beil*r
C20Q5"
Reference. CR
I »
v>
\.
i
• Smoke
O CO
XHC
A NO*
I8O
340- -170
320- -160
$00- -ISO
280- -140
260- -ISO
24O- -120
220- -IIO
200- -100
180- -
10 II
C0z,p*re*nt
19
8
ISO- -80
I4O- - 7O
120 SO
100- • SO
80- - 40
6O - 3O
4O • 2O
SO- • 10
0
3«
34
32
30
28
28
-24
22
20
i
a
•tS
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel A/o. 6
Loid.
parcint
99.
77.
5V.
2V.
Firing
R«ta,
gph
Z79
2/0
/y.y
*-9
FlMl
Ttmporatur*,
F
2 06
20<
2o5-
2.00
Combuition Condition*
Smok.No.
¥3
y.7
7.i
3.6,
2.9
2.5-
3.6
76
£$•
£3
3.2.
2.2.
3-2
y.3
£5
5TZ
?.y
2*-
3.V
4.6
coz. x
/2.0
/2-0
/y.7
9.3
/0.3
y//
/2.>
/V.7
^./
f.9
tf.2.
/«.3
V2J
/3LZ
£.>
7.i
$3
,eS
n.o
/3.3
o2.%
$:/
v-/
/-<
8.7
7.5
*.*
£3
A 8
/?./
//a
93
7o
V.7
?-V
/?.o
/o.*
^.8
<-7
H-7
•J.i
Stock
Twnpmtur*,
F
32V
3/0
3o7
317
3/1
3t>9
3o£
2<)l
290
zee
28 Z
275
27o
2*r
2V3
ZVo
2?9
i?i
i?o
2i9
Gawoui EmWora, ppm
CO
8.
9.
75.
8.
57
V.
5.
58.
yy.
/3.
^.
/.
/.
y
//
2.
o
o
o
o
HC
2.2
IS
1.2.
A/
1.0
1.0
l.o
/.o
3.B
3.V
?.p
?.y
2.S
2.S
/V
/3
,y
o.9
0.9
.?
^____
NO
3//
3/2.
3/tf.
263.
274.
208.
293.
29V.
/.
297.
Hi,
*2A
2«.
3/A
38o.
Y'7
«>,
?/<.
3/2.
J/A
2<3.
2W.
29A
30).
2«57
/72.
2o3.
230
279.
293.
?oo.
/72.
2i6.
272.
321.
38V.
f*o.
so2
9flO.
9to.
/szo.
(,80.
75o.
820.
930.
//20.
H20.
V90.
S8o.
7ft.
9oo.
980.
V3o.
f&.
(50.
78V,
9e»o.
/020.
Pirticulat* Loading, mg/tm
•rob* + fittvr
—
_
_
—
—
—
1 02.
..
—
—
~
—
—
—
_
_
-
—
•ioA
Total
—
—
—
_
—
—
J*6.
—
—
_
_
^
-
—
„
—
_
—
81.3
_
a
i
oo
-------
H-82
C2005*
Load.
100%
36
34
32
-30
28
-26
-24
-22
20
10 II
COt,P*re«nl
12
13
14
IS
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-83
Boiler.
fu.1 M>. i
-7B%
• Smoke
O CO
X HC
4k NO.
10 II
CCS.i»*rr,»h»
12
14
ISO
I7O
160
ISO
I4O
130
12O
no
too
a
90*
O
u
80
• TO
• 60
50
• 4O
• 30
• 20
• IO
0
36
34
-32
-30
28
26
24
22
20
!•;
- 16
14
- 12
- 10
i- 8
- 6
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-84
B«il*r.
C2005"
iao
170
IS
3«
34
32
30
28
26
22
20
I
i
IS
14
12
10
a
6
4
2
0
a
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-85
Boil«r
i
I
• Smok*
o co
HC
X HC
A NO,
180
II
COj.peresM
14
3404-ITO
320- -160
3OO- -150
280- -140
260- 130
240- -120
220- -110
ZOO- -100
; E
i a
1 ISO- 90*
r s
1 160- -80
140- • ro
120- -6O
100- 50
80- • 40
60- • 30
40- 20
20- • IO
O
36
34
32
30
28
26
24
2Z
20
I
"s
16
14
12
10
8
6
15
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF C02
-------
Boiler C200Z
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel fras
Load,
fMTCWlt
loo.
77. J
Firing
Rat*.
cfh
V/VO.
32 /C.,
i
| 1
Fuel
Tcmpcralur*.
F
—
-
~
Comlxntion Conditions
Smok* No.
O.'S
C.I
C.3
1.1
L *-''® -
COyX
6.6
u_?-°
/O.O
oz.x
6" 7
V.7
?.9
0.7
6.7
79
';[ 0.0 ' <).?
!i o.i /o.o
9.3
6.B
Stack
F
32?
327
29V
290
1-1 £84
3.0 \ 27/
GMOU> EmoHom. ppm
CO
/9.
20.
33.
> /2V0.
22.
20.
2,1.
&7.
! i i ii 3.6 ' to-8 i /•£ i 26° ii >/2V».
52.
2H.
2»70.
990.
:~
':
—
—
i
0.0
c.o
0.0
o,7
$3
O.O
O.O
o.3
6.V
7.V
93
/O.i
/O.i
H.8
6.6
8.^
/O.O
ii
ii
j
JO.f
7.7
V.2.
2.6
O.9
/2.Z
g>,5
5".V
2-?
2.7Z
2*0
242.
2,!2tO.
63.
o
0
/I/O.
HC
-
—
/V
38.O
—
—
...
.~
_
-
—
7e>
Voo.
7-S"
3,5-
Y.o
22.0
NO
67.
70.
7*
6i-
?2.
£e>.
&.
63.
62.
73.
71.
iS.
62.
S*
36.
81.
66,
it.
NO,
68.
7/
75:
73.
5^3
69.
66.
6£
66.
75.
7A
6t'.
6V.
t'A
H5:
ffjf.
56.
67.
so2
V.
V.
7.
6/.
0
o
o
o
O
O
O
o
o
3o.
o
o
o
o
PwtteulM* Loading, mo/tm3
>rolw » f ilMr
—
—
—
—
—
_
2.7
_
_
_
—
—
—
—
^
—
—
Tout
—
—
—
_
—
—
—
lt>.7
_
-
—
—
—
_
_
_
-
—
ffl
I
CO
O)
-------
H-87
„-»., CZO05
F.-I G-AS Land IOI %
• Smoke X HC
o CO A NOi
-
-
~
-
\
,0
340-
320-
30O-
280-
260-
240-
220-
20O-
£
S 180-
T * I6O
i 140-
i I2O-
| too-
f 80
"*" c^^n-
j*****r^ i 1 ? 40-
1 If K
1 1 \
J / 2O-
1 1 ^+^ i/ . 1 1 J
6 7 8 9 to li 12 13 14 1
ISO
•I7O
•160
•ISO
•I4O
130
•I2O
•110
•IOO
E
O
o
- 80
- TO
- 60
- 50
- 40
- 30
- 20
- IO
3 °
36
34
-32
-30
-28
26
•24
•22
•20
• 18
• 16
• 14
• 12
• IO
• 8
• 6
• 4
- 2
•0
E
a
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-88
I s-
».!,.. CZ005 B3ju XM
340-
320-
soo-
280-
i
1 280-
1 240-
1
1 1 200-
l"°
1
T I
1 /
/ / 100-
/ /
Aj'0x /X / 8°-
x^ *y y~
cL co y J
• - •- n «,.
jf
- i -i i *^*C i i i i
1 7 • 9 10 II 12 13 14 I
•(•0
•I7O
-I6O
-ISO
•140
•ISO
-I2O
•no
•100
a
'*°8*
-•0
• 70
-6O
• 30
- 40
- 30
- 20
• IO
»°
•34
-32
-30
•28
26
-24
-22
•20
•
NC.ppm
• 16
• 14
- 12
• 10
- 8
- 6
- 4
- t
•0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-89
*.»., C2005"
F..I
« Sntok* X HC
0 CO A N0>
340-
320-
3OO-
-
-
•
_
I
1
I
jj
^ ^y^ I •
— ft-- — J t 1
>- CO ^x^/ /
^y
280-
260-
240-
220-
2OO-
a
a 190-
o"
Z ISO-
I4O
120
too-
60-
-*.... 6O
40-
20
1^1 i ^*- t i i i i
•ISO
•iro
•160
•ISO
140
130
•120
•110
•100
a
• 90*
o
0
• 80
•70
•«0
•50
- 40
• 3O
• 20
• 10
3«
•34
•32
•30
•28
•26
•24
•22
•20
•16
• 16
• 14
•12
• 10
• 6
- 6
- 4
• 2
-0
'o
;o
12
13
14
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-90
•.».. C2oo$
F«»l_
• Smok*
o CO
X HC
A NO,
340-
320-
3OO-
280-
260-
240-
220
200-
ISO-
I6O
I4O'
120-
100-
80-
6O
40-
20
10 I
CCj pt'Ctnl
12
13
14
180
I7O
ISO
ISO
140
130
120
•110
100
E
a
• 90*
O
o
80
70
60
50
• 40
30
• 20
• 10
• 0
36
34
32
30
28
26
24
22
20
••„-
X
16
14
12
IO
8
6
4
2
O
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler C2OOL
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel rVo. 2.
Load,
percent
/OO.
Firing
KM,
gpr,
/79.
t !
j ;
i
i i
. 7JL.
i-
H2.
Fu»l
T«npw«tura,
F
7C
7o
•
f ' ; |
' ; ;
! I
5-2.
34,
i
9V.
6H.
70
7o
--
Combustion Condition*
Smok»No.
0.7
X.3
7./
0,1
co2. %
/Z.O
L/2.JLJ
/3.7
o2.%
3S
2.o
l.o
Stack
TvniMraturc,
F
HH8
«/33
116
I
fOJ
c.y i ;/.2.
e.V i //.9
1,0 [_'*?d
8.* /V.o
j
o.o
o.o
<5,0
o.;
__Z,ff
9.0
0.0
0.0
o.9
2.V
e.-j
9.7
/^3_
/A9
/3.Z
/3.^
9.7
//.Z
/2./
/2S
6S
f.o
3-8
/.&
&?
y*a
Hli
Hio
39f
362
8.1
7.o
S.i
17
1.1
l.o
£.5"
y.3
7.2
2.7
3f5
?Vtf
31i
32*-
3/2
*ofi
affo
Z?o
2<«
262.
GIMU* EtniMJom, ppm
CO
O
0
222.
O
O
o
o
^;zjio.
o
o
o
o
o
JS30.
O
o
o
o
HC
2.;
2.6
?.V
3.9
V.o
4.7
v./
5!5"
y?
y.?
5To
/:/
j:a
/«./
V.<
v./
V.o
3.2-
NO
//7
;/5T
//2.
//3.
/'«
/2V.
/26.
;z4.
95;
/o3.
//V.
//9.
IIS,
loB.
96.
toH.
98-
9V.
WM
//ft
/'5:
//v.
//2.
"9.
/23.
'2fe.
/27.
95
y*3.
//V.
//«.
//6.
110,
9<.
/o3.
100.
95.
«°a
9/.
loo.
>o7.
72.
*o.
d<.
9^.
//3,
<7
7V.
03.
9/.
yo2.
/o«.
7V.
es.
94.
9a.
Pwtlculit* Lowfinc. mg/tffl3
Prob* <• filtw
.» _
.^
_
—
__
3.3
_
—
—
—
—
—
—
—
_
_
_
—
Tout
_
—
—
—
_
17.8
—
—
—
—
—
—
-
—
_
-
—
—
a
i
CD
-------
H-92
^u, CZoo6
FiMl
. 2.
i
• Smoke
O CO
X HC
A NOi
Z
340-
320-
300-
260-
260-
240-
220-
2OO-
ISO- •
160-
I4O-
I2O-
IOO
80-
60
40
20
!O li
CO2 p«rc»nt
12
IS
14
no
170
160
ISO
140
ISO
I2O
HO
•IOO
e
90?
o
u
80
TO
60
50
40
30
20
10
0
38
34
32
30
-28
28
•24
•22
-20
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-93
•»».,
CZ006
yS/o. 2.
• Smoke
O CO
X HC
A NO*
iao
170
160
ISO
140
130
120
no
IOO
a
901;
o
u
80
TO
60
SO
• 4O
• 30
• 20
- 10
• 0
36
34
32
30
28
26
24
22
20
16
14
12
10
8
6
• 4
• 2
•0
10 II
COz,P«re«nt
12
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-94
IO II
C02,p«'C»M
3C
34
82
30
20
26
24
22
2O
I
I
:
is
14
12
10
- e
• 6
4
2
0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-95
BOH., C2LOO(> T.mm
34O-
320-
3OO-
280-
260-
240-
220-
2OO-
E
cf
* I6O-
140-
120-
^>— — ~* — -*--JL
/ 80-
/ 6O-
_^ HC /
,5£r, , :
-iao
•170
•160
•ISO
•140
•ISO
•I2O
•110
•100
a
• 90*
u
•80
- 70
- 60
• SO
- 40
- 30
- 2O
- 1C
-36
-34
-32
•30
-28
•26
-24
•22
•2O
a
a
z
• 16
• 14
• 12
• 10
- 8
- 6
• 4
- 2
- O
II
C02,p*re*nt
12
13
IS
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler CZ006
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel
Lo.d.
pvrcont
101.
8*
51.
37.
Firing
R«W,
gph
171.
m.
St.
>
&,
FlMl
Tcmpmtura,
F
/39.
127
/yo
/yy
Combust
SmolnNo.
3.7
J.Y
5.9
ff.
10
2}
?.«,
H.6
8.0
j
2S
2.8
33
f.2.
f.6
3.8
—
S. I
an Condii
COy*
//.7
12 J
12.9
/t.o
93
//./
12.0
/3.1
Ho
9-7
to*
/2.0
/3.a
/3.6
//.^
//.9
/3.S
ion*
Oj.%
V.3
38
2V
.a
^.7
T2.
¥.0
2.0
o.fi
7.0
5:a
3.7
2. a
A3
Y,V
y./
AY
Slack
TMnpmtur*,
F
v«r
Hio
fo9
3*B
Vtt
VoS
398
&sr
373
33S
32f
3U
3*S
3oo
27*
Z?o
2*8
"•
CO
o
6
O
66.
O
O
O
o
78.
o
o
o
o
2.
o
o
//3.
Sj
Qiwoui
HC
Y.8
1.8
ZZ
5.1
5.8
i.J
t-t-
6.1
6V
8S
$.S
8.S"
8.1
8.7
8.7
8S
ff.f
Em Wont.
NO
Z03.
ZoS.
2/3.
2/0.
190,
tol.
2>0.
ZI7.
zto.
Zo3.
222.
23V.
Z38.
238.
23/.
213.
/9Z
ppm
NOX
203.
2 08.
2/0.
-210.
18$.
J98.
2o8.
2/5T
2o?
203.
222.
23*
237
235!
2 as.
233.
/fJC
so2
f?o.
jyo.
55o.
tf3o.
y?«.
V9o.
5T20.
59o.
620.
y20.
y7<».
$2.0.
ft*.
£90.
Wo.
Sio.
Sto.
Pirtictriau La
Prab* + filter
—
—
~
—
—
—
ttt.i
^
_
_
_
—
-
«.
~
-
—
tdlng. mg/im3
ToM
_
—
—
—
—
_
93.7
—
—
_
_
_
-
«.
-
_
—
K
CD
as
-------
H-97
••iltr.
Load.
J00%
1-
I
i eo
10 M
C02,p«re«nl
IS
-36
•34
32
-30
28
26
24
22
20
"!
16
14
12
10
8
- 6
4
- 2
•0
•!
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-98
Boil«r.
C2O06
.0 II
COj, ptrc«nt
36
34
32
30
28
26
22
2O
16
14
12
10
8
• 6
• 4
• 2
• O
a
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-99
C 200 6
CR.
5-0%
• Smofc*
O CO
X HC
A NO,
I41
34O
32O
30O
260
260-
£4O-
22O-
200
I
a I8o
o;
Z I6O-
|4O
120
100-
80-
60
40
20
IO
180
170
ISO
ISO
140
130
120
IIO
100
E
a.
90*
o
u
ao
7O
60
50
40
SO
2O
10
• 0
38
34
32
30
-28
26
24
-22
-20
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-100
Boil«r.
r...i /Sp^grgAce CR
37 X
I 5
• Smoke
o CO
X HC
A NOa
COf
-J_
H
- -K
12
13
14
180
!7O
160
•ISO
140
130
120
•no
•IOO
E
a
• 90*
O
o
•80
• 70
• 60
SO
• 4O
• 30
20
• 10
• 0
36
34
32
SO
28
24
22
20
I
i
i
16
14
12
IO
8
6
• 4
2
0
|
a
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CP2
Boiler C 2OQ&
Fuel
Load.
p«rc«nt
/OO.
8*
Firing
R««,
•PH
US.
/39L_,
!- ~\ —
FlMt
T*mp«ritu»,
F
2/2.
2/2
Combunion Condition*
Smelt* No.
V.7
£.1
*-*'*
2.7
COj.*,
/2.2
/3.7
/0.3
r //.o
ji H.I \ li.l
j f
i
i
50.
i
37
02.
tl.
Z/o
Zio
! T "7
y.f
£ S?
y. *
L/2-7
/3L7
3,7 ^
2.3
AS
1.7
z.t
5.2,
*i2
f.Z.
£.2
o2,%
3.7
l.i
Sock
T*mp«rttuf*,
F
W3
V22.
\
6.1
s-s
H.t
3.2.
1.7
v/3
y«5"
3^3
J9
38o
i
GMMHH Embtiom, ppm
CO
2.
6.
o
a
o
O
2.
L
i ii
<.f
9-f
9.''
M3
I/.9
13.1
II.B
/2./
/*Z
it.i
8.7
6.8
V.7
y.o
/.7
5:/
7-8
2.8
ji
3^5
3V4
336
32*
3/9
3oB
278
269
26o
25;
s.
o
0
o
o
O
0
2.
HC
?.S
3.6
3.8
3.8
f.i
3.6
3.8
H.6
H.5
3.8
3.8
3.8
3.8
H.B
i.8
H.B
NO
Zit
272.
2VA
Z«>.
2*3.
27a
27ft
'72.
2/V.
2V«
2«.
29A
2V.
ZW.
2fio.
Z<7.
«.
2
-------
H-102
9
8
7
6
I S
9
in
?4
1
2
3
2
,
0
*,»„ CZOO6
34O-
320-
3OO-
A!^— -- MO"
""*" y/ 26O-
- / 240-
/jP/ 820-
- y/ 200"
V^ E
y* a
/ » 180-
0*
- * I6O-
140-
- 120-
IOO-
- 80-
60-
)t HC w- *o
I I I 1 1 I""1*"" " f t
L_i*n _. »*
-170
-160
-ISO
•140
•130
-120
-110
-IOO
E
&
O
o
- 80
- 7O
- 60
- SO
• 40
- 3O
- 20
• 10
^v
-34
•32
•30
•28
•26
•24
•22
•20
a
a
•'•„-
- 16
• 14
• 12
- 10
- B
• 6
• 4
• 2
• ft
6 7 8 9 10 II 12 13 14 IS
C0(,p*re*nt
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-103
•„„.,
CZ006
• Smok*
O CO
XMC
A NO.
* 5
I4
,-...#,,„
-*-
340
320
3OO
260
240
22O
200
i 180- -
«
160
I4O
I2O
IOO
80
60
40
20
180
170
160
ISO
I4O
ISO
!2O
no
100
90?
o
u
14
80
70
6O
SO
4O
30
2O
IO
0
36
34
32
-3O
28
26
24
22
-20
I
i
<
16
14
12
10
- 8
- 6
4
- 2
•O
E
a
SMOKE AND GASEOUS EMISSIONS FOR CO^¥.£ft£iAL BOILERS AS FUNCTION OF CO2
-------
H-104
•»»« C2OO6
• Samtk*
O CO
X HC
A N0(
i
e
540
920
300
26O
260
240
220
200
ISO
140
I2O
IOO
60
6O
40
20
ISO
I7O
I6O
ISO
I4O
ISO
120
no
IOO
12
13
O
O
•0
7O
60
50
40
3O
2O
IO
0
36
34
32
SO
28
26
24
22
20
' o
14
12
10
e
6
4
2
0
SMOKE AMD GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF O02
-------
H-105
9
8
7
6
i 3
1
1 4
«
3
2
,
0
«
B.il« CZOOi T5r-T-T -"'•
ru.i Vo. I i,^^ 37 ^o « rn A MO.
340-
320-
3OO-
-*^-<4&
^^ 260-
VCjX^^ 240-
7/ 220-
/ 200-
/ 1
/ * I8O-
' * 160-
140-
120-
IOO-
80-
6O-
I- 40-
20-
1 1 1 | ! -Unr— <~e^-*- \
7 B 9 iO H 12 13 14 1
00z,p»'««nt
•ISO
-170
-160
•ISO
-I4O
•130
-120
•no
•IOO
a
• 90*
o
u
-60
- 70
-60
- SO
- 40
- 30
- 20
- 10
1°
•36
-34
•32
•30
-28
•26
•24
•22
-20
E
•••5
• 16
• 14
12
• 10
• 8
• 6
• 4
• 2
•0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
Boiler C2006
SMOKE AND EMISSIONS DATA FOR COMMERCIAL BOILERS
AS FUNCTION OF CO2
Fuel &-«.$
!
LoMl,
ptrcwn
99.
§3.
!
i
5V.
37.
Fifing
R«*.
•*
23.800.
20,'OQ,
72,300.
89VO.
Furi
F
—
1
—
—
Combun
Smok* No.
0.3
o.3
0.6 ,
e».5"
1
i
tf.o
[. C.-.0
«T>. O
| 0.0
j o.o
i
!
0.0
43.0
O.O
0.0
0.0
o.o
o.o
on Condi
COyX
ff.3
AT
*'
/d.y
73
8.Z
?.o_
9.8
/o.S"
79
g.7
9./
£.2
73
AS"
9./
ions
Oj.%
5".i
$:a
y.o
/.a.
.75"
5:7
v.^
^.y
r ^>
/-*i*
«.v
v.^
V.'
9.9
7*
r./
V.o
Suck
F
y?<
4tt$
^3
v/s-
yaf
39?
38B
38V
381
3J8
3/o
3oS
Z8o
273
2«-y
Jf9
CO
O
o
o
73(.
O
o
o
o
toZ.
0
o
o
o
o
o
o
Gmout
HC
3.V
T3
3,Z
3?
3.o
?.o
5,5"
5^
5-7
Z.9
3.2.
2-9
Ao
/7
2.5"
?.y
EmWora.
NO
7«
79.
92
tfO.
St.
75.
<*).
9^;
too.
55.
(+
73.
36.
yv.
?7.
^/.
ppm
»«>«
7^.
7A
9f.
//2.
5"V.
75".
90.
95;
lot.
55.
63.
72.
34.
yy.
P.
^/.
•°i
o
o
3.
/o.
o
o
o
2.
2.
o
o
e
o
0
o
o
Pmteutott La
Vote + filMr
_-
«. .
—
—
—
—
*r
—
—
—
—
—
-
—
—
-
•ding, mfl/«m3
Toul
—
—
—
—
—
—
//./
—
—
—
—
—
_
_
_
_
ffi
i—i
o
-------
H-107
•
e
r
6
I 5
|
in
I4
*
3
2
1
0
...» czoof T,^T
340-
320-
3OO-
280-
260-
240-
220-
_ 20O-
E
a ISO-
* ISO-
1
1 140-
\ 120-
^^T*>^* 100-
^< \ 8°-
J I
— J( — |f -|f- i I, , f V
^sM-*^ -r "* 8°-
1 J_ ^ „ [f ^/ I ! I 1 1
-ISO
I7O
•160
•ISO
140
•ISO
•120
-HO
-too
E
9O"i
0
o
• 80
• TO
• 6O
• SO
- 4O
- 30
- 20
- IO
r-36
•34
-32
30
•28
•26
•24
•22
•2O
•16
- 14
• 12
- 10
• 8
• 6
- 4
- 2
• 0
II
Oz,p*re»nt
12
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-108
•altar
C20Q6
• Smoke
O CO
i 3
X HC
so
180
340- -170
320- -160
300 -150
280- -I4O
260- -130
240- 12O
200- -IOO
E
o.
180- • SO*
o
o
1604- eo
140: • 70
120- - 60
100- • 50
- 4O
30
- 20
- IO
10
13
-34
-32
30
28
26
24
22
20
a.
-iS
16
14
12
IO
8
6
- 2
-0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF CO2
-------
H-109
Boilu
C.2OO6
• Zmok*. t CO
A NO.
-i:.,..^
!!
•ISO
12
13
14
340- -I7O
320- -160
3OO- -ISO
280- -I4O
260- -ISO
240- -120
220- -110
2OO- -IOO
1 ISO- • 90*
r 8
1 160- • 80
I4O- • TO
I2O- • 60
100- • SO
SO- - 40
60- - 30
40- - 20
20- - 10
O
•36
-34
-32
-SO
-28
-26
24
22
20
18
16
14
12
10
IS
4
• 2
•0
SMOKE AND GASEOUS EMISSIONS FOR COMMERCIAL BOILERS AS FUNCTION OF C02
-------
H-110
»»»« C2OO6
340-
320-
300-
280-
260-
240-
220-
200-
a
» IflO-
-------
1-1
APPENDIX I
CALCULATED EMISSION FACTORS
FOR RESIDENTIAL UNITS
-------
EMISSION FACTORS LBS/1000-GAL FUEL
EXCESS DRY
UNIT CONO C02, AIR FLUE GAS,
PERCENT PERCENT SCF/L6 FUEL
23.0
23. l"
23.2
24.0
24.1
24.2
25.0
25.1
25.2
26.0
26.1
26.2
27.3
A
T
R
A
R
A
R
A
T
R
A
R
A
R
A
T
n
A
R
A
R
A
T
R
A
R
A
R-
A
T
R
9.2
9.9
9.4
8.9
8.4
8.7
8.8
7.1
8.9
9.2
8.8
9.0
7.8
8.6
8.4
9.4
8.5
10.8
10.9
9.1
10.1
7.1
8.7
8.3
9.4
9.4
9.2
9.3
9.1
8.2
8.1
68.3
54.5
6C.8
72.4
77.8
73.0
70.7
119.6
71.1
65.1
72.3
65.9
94.8
75.6
75.3
55.9
73.0
41.7
40.6
63.7
48.1
108.6
72.9
69.9
62.2
61.0
61.5
65.8
63.7
81.2
83.0
320.0
293.7
305.6
327.0
337.3
327.6
323.2
415.7
323.7
312.3
325.7
312.6
368.5
332.1
333.3
296.2
328.8
270.1
268.0
312.8
282.7
397.0
328.8
323.0
305.9
303.7
308.8
317.0
309.4
342.6
346.1
CO
0.61
1.17
0.41
1.20
1.5i4
0.78
0.
-------
EMISSION FACTORS L8S/1000-GAL FUEL
UNIT
28.0
29.0
30.0
31.0
32.0
33.0
34.0
35.0
EXCESS
COND C02, AIR
A 6.6
T 7.4
R 7.7
9. 4
7.9
7.7
7.5
7.1
6.9
A 7.9
T 9.9
R 9.6
7.0
8.7
8.6
6.1
6.5
6.6
A 9.I»
T 9.8
R 10.1
8.8
9.3
125.5
97.3
89.3
54.7
85.7
83.7
95. 4
108.3
114.4
93.7
56.1
59.0
113.7
75.5
75.7
11*3.2
130.5
187.5
54.9
55.1
49.1
69.6
58.0
JE GAS.
r/LB FUEL CO
428.6
374.7
359.5
294.0
353.1.
31.9.6
372. it
397.2
1.08.8
366.1
294.8
300.3
405.8
332.9
333.1.
463.2
1.38.9
1.33.2
296.7
297.2
285.5
321.7
299.5
36.23
1.E8
1.67
3.78
2.26
2.1.7
2.26
3it. 95
1.2.33
6.97
1.00
0.71.
62.63
15.81.
7.75
^300.59
>284.82
>281.15
2.96
2.2<4
2.61.
0.1.2
0.59
HC
1.68
0.2C
0.50
0.39
0.1*1.
2.60
0.91
1.11
1.30
O.i»2
0.21
0.22
1.5".
0.28
O.i«2
27.71
21.53
0.1.7
0.3<>
0.1.2
0.53
0.85
MO
7.1.3
12.57
12.26
13.27
12.1.1
12.1.7
li.. 05
9.69
8.39
12.62
13.83
li.. 1.3
7.12
11.88
11.71
2.3<>
4.92
5.31.
1C. 03
9.1.0
9.80
13.77
13.99
N02
17.63
0.61.
4.62
0.50
0.60
2.99
3.1.8
7.09
7.30
2.22
1.02
1.04
li». 80
1.73
1.1.5
31.06
32.07
27.93
0.00
0.00
0.00
2.19
1.79
PARTICIPATES^**
NOX FILTERABLE TOTAL
29.02
19.92
23.1.2
20.85
19.63
22.11
25.02
21.95
20.17
21.58
22.23
23.17
25.72
19.95
19. MO
3<».e
-------
EMISSION FACTORS LBS/1000-GAL FUEL
UNIT
23.0
EXCESS
COND C02, AIR
24.0
A 8.9
A 9.3
A 9.4
A 9.7
T
T
T
T
T
T
T
R
R
R
R
R
A
A
A
A
T
T
T
T
T
R
R
R
R
R
9.5
9.9
10.1
10.3
1C.5
1C.6
10.6
9.3
9.3
9.9
10.1
10.2
5.9
6.2
7.9
6.8
5.9
6.1
6.4
9.3
1C.1
5.3
6.0
7.4
9.2
10.6
75.3
67.4
62.0
60.2
60. 0
57.2
54.6
51. t
91.6
72.8
152.9
li»3.1
133.5
61.2
50.6
156.6
Ht9.l|
131.5
63.3
1*2.3
UKY
JE GAS,
F/LB FUEL
333.5
318.lt
306.0
304.6
312.6
304.1
298.9
293.8
287.8
283.3
284.it
308.4
306.4
290.5
286.7
264.3
491.2
464.6
362.6
326.8
479.1
460.4
442.1
304.9
284.6
486.1
472.3
381.4
308.6
268.9
CO
0.17
0.33
1.27
2.05
0.48
0.47
0.62
0.61
4.17
38.97
2.35
0.48
0.80
0.60
0.59
13.08
270.27
107.21
0.76
0.51
93.22
35.16
9.02
0.00
o.eo
193.74
104.25
1.00
0.43
2.67
HC
0.35
0.38
0.18
0.18
0.21
0.20
0.19
0.19
0.09
0.13
0.04
0.12
0.09
0.09
0.11
0.08
5.68
2.09
0.11
0.05
0.43
0.07
0.07
0.09
0.17
5.10
1.84
0.11
0.13
0.16
NO
11.09
12.17
9.72
9.96
12.30
12.30
12.09
11.56
10.84
7.53
9.14
12.47
12.81
13.04
11.59
9.14
4.13
6.51
10.97
10.26
4.30
9.03
9.41
12.30
11.64
4.63
5.03
12.82
12.96
11.90
N02
3.97
6.49
10.99
12.42
6.90
7.49
8.12
8.98
6.36
13.47
11.84
1.31
1.31
1.46
1.70
2.90
28.27
25.16
6.85
6.18
14.41
7.12
6.08
2.10
1.71
13.36
11.77
0.00
0.00
0.00
NOX
20.97
25.15
25.90
27.68
25.76
26.35
26.66
26.71
22.98
25.03
25.85
20.43
20.96
21.47
19.48
16.91
34.61
35.14
23.68
21.90
20.99
20.97
20.51
20.96
19.56
20.47
19.48
19.66
19.90
18.25
-------
EMISSION FACTORS LBS/1000-GAL FUEL
UNIT
25.0
EXCESS DRY
CONO COZ, AIR FLUE GAS,
PERCENT PERCENT SCF/L8 FUEL
26. 0
7.7
7.3
9.5
10.6
11. i*
9.1
9.3
9.5
9.7
10.6
11.6
8.6
8.9
9.1»
9.6
9.9
11.1
6.8
7.1
7.7
8.0
8.*»
10 .9
11.2
7.3
7.6
8.3
9.1
9.7
10.6
11.1.
7.3
7.7
9.3
10.8
11. <•
89.1
86. t
51*.0
39.1
29.3
62.3
59.1.
56.1
51.9
<.0.8
27.9
68.8
63.5
5*4.8
51.2
1.7.1
31.8
117.3
108.6
92.2
si*.e
68.0
35.9
32.2
107.8
97.0
79.8
65.2
51..<*
<*1.6
30.7
106. 8
95.8
61.1
39.5
31.0
359.7
35
-------
EMISSION FACTORS LBS/1000-GAL FUEL
UNIT
27.0
EXCESS
COND COS, AIR
28.0
A
A
A
A
T
T
T
T
T
T
R
R
a
R
R
A
a
A
A
T
T
T
T
T
T
T
R
R
R
R
R
R
R
7.1
8.6
9.3
9.3
10.1.
7.6
8.2
8.6
8.9
9.3
10 .if
7.2
7.7
8.9
8.6
9.7
5.7
6.1
6.5
7.it
7.3
7.6
7.8
7.9
8.1
8.1»
8.7
7.1
7.3
7.3
7.6
7.6
7.9
8.0
110.8
76.3
67.7
61.3
<»6.5
98.1
83.1.
76.3
69.2
61.3
1*6.0
105.1.
90.1
83. 4
72.1
52.6
155.0
139.6
126.1
96.4
101.3
92.2
85.8
84. 6
78.7
73.5
68.6
103.2
97.8
97.8
90.6
89.8
63.1
82. 0
UN T
;E GAS,
:/LB FUEL
398.8
333.2
317.0
304.9
276.8
374.7
346.9
333.2
319.9
304.9
275.9
388.5
359.4
346.8
325.4
288.4
484.8 ;
455.5
429.6
373.1
382.4
365.0
352.8
350.5
339.3
329.4
320.0
386.1
375.7
375.7
361.9
360.4
347.7
345.5
CO
39.93
2.99
1.50
1.45
1.17
8.10
2.56
2.11
2.02
1.61
1.45
5.32
1.89
1.64
1.20
2.89
»313.69
169.23
27.35
2.92
2.39
0.95
0.74
0.91
1.24
1.20
1.17
3.83
1.57
1.57
1.32
1.50
1.27
1.26
HC
1.93
0.30
0.14
0.23
0.14
0.57
0.33
0.24
0.14
0.11
0.08
0.47
0.24
0.15
__
—
19.11
3.27
2.18
1.45
0.39
0.35
0.34
0.34
0.30
0.31
0.31
0.46
0.39
0.28
0.25
0.25
0.24
0.24
NO
9.46
13.55
13.60
13.43
12.19
11.64
12.34
13.17
14.27
15.32
14.64
10.09
11.97
12.53
13.78
13.52
2.44
5.60
7.21
12.10
8.34
11.02
12.03
12.15
11.57
11.78
11.63
9.71
11.76
13.23
13.35
13.50
13.41
13.14
N02
12.77
5.19
3.02
3.70
2.64
3.24
2.10
1.44
1.38
0.79
0.24
4.04
2.18
2.70
2.54
2.75
49.87
41.39
31.67
19.19
3.61
1.25
1.21
1.20
2.04
1.69
1.92
6.29
4.19
2.25
4.34
4.02
4.17
4.44
NOX
27.27
25.96
23.87
24.29
21.33
21.09
21.02
21.64
23.26
24.29
22.69
19.51
20.54
21.92
23.66
23.47
53.61
49.98
42.72
37.74
16.39
18.15
19.66
19.83
19.78
19.76
19.75
21.18
22.22
22.54
24.82
24.72
24.74
24.56
-------
EMISSION FACTORS IBS/1000-GAL FUEL
UNIT
29.0
EXCESS
CONO CO?, AIR
30.0
A
A
A
A
A
A
A
T
T
T
T
T
T
R
R
R
R
R
R
R
R
R
A
A
A
A
A
T
T
T
T
T
R
R
R
ft
R
R
R
R
i*.8
1..9
5.1
E.«*
5.5
5.9
6.3
6.2
6.1*
6.7
7.1
8.1
6.6
6.0
6.2
6,<»
6.7
6.9
7.2
7.8
3,3
8.2
7.7
7.9
8.2
8.3
8.7
5.9
6.1
6.7
6.9
B.7
5.5
5.7
6.1
6.5
6.9
7.3
7.3
7.8
195.2
190.2
180.7
167.7
162.1
l«**i. 5
129.1
137.2
127.3
116.7
103.7
78.1*
69.2
138.5
131.0
123.9
113,6
10 it. 9
95.5
79. 8
75.6
69,8
88.8
85.6
80.0
76.8
68.8
136. ii
116.5
110.3
66.9
158.9
11*7.3
133.9
120.9
10B.lt
97.2
97.2
85.3
UK I
IE GAS,
VLB FUEL
562.8
553.2
535.1
510.2
1(99.5
1*65.8
i»36.<»
451.9
1.33.0
i<12.6
387.8
339.3
321.8
1*51.. i*
<*i«Q.O
1*26.5
1*06.8
390.0
372.1
31.2.1
33363.02
196.57
1*8.16
13.27
8.57
5.09
2.72
i*.70
2. 03
1.5D
1.01
1.1*1
3.52
9.22
6.1*1
5.99
5.50
1..26
3.<<8
3.92
<*.52
7.73
1.1*9
1.28
1.06
1.22
2.33
35.66
10.53
3.1*2
2.1*9
3.78
77.23
15.11*
5.08
1.31
0.1*1
0.58
0.19
O.DO
HC
>16.76
0.58
0.1*8
0.1*6
0.1*6
0.1* i»
0.1*8
0.30
0.28
0.27
0.38
1.16
1.25
0.89
1.18
l.Bi*
2.1*2
2.i«i«
2.11
1.22
0.80
0.53
0.51
0.52
0.53
0.1*8
0.50
0.76
o.eo
0.78
0.62
1.22
0.59
0.1*5
0.1.3
0.1.0
0.38
0.31
0.36
0.33
NO
2.20
2.78
5.67
9.10
10.58
12.20
12.89
10.07
11.10
12.65
13.18
12.1.8
12.38
9.12
9.81
10.70
11.56
12.17
12.1*<*
12.20
12.1.7
12.78
15.16
11*. 71
13.88
11.. 19
13.72
6.76
8.50
11.22
12.01
9.87
1.92
5.23
7.92
1C. 05
11.90
12.30
13.31.
13.31
N02
18.75
17.02
10.98
3.92
2.13
0.00
0.00
2.32
1.1*8
0.35
0.33
0.87
0.27
3.88
3.76
2.92
1.39
1.67
1.27
1.17
0.86
1.10
6.12
6.31
5.51*
7.16
10.38
11.95
9.20
6.67
lt.77
(..59
19.32
12.81*
7.59
5.02
3.72
2.88
2.88
2.70
NOX
22.12
21.27
19.66
17.88
18.35
18.71
19.77
17.76
18.50
19.75
20.55
20.01
19.25
17.86
18.80
\19.32
19.12
20.33
20.35
19.88
19.98
20.70
29.37
28.87
26.82
28.92
31.1(2
22.32
22.21*
23.87
23.19
19.73
22.26
20.86
19.73
20.1.2
21.96
21.71.
23.33
23.11
I
CO
-------
EMISSION FACTORS LBS/1000-GAI FUEL
UNIT
31.3
EXCESS
COND C02» AIR
32.0
T
T
T
T
T
T
T
T
R
R
R
R
R
R
R
A
A
A
A
A
A
A
A
T
T
T
T
T
T
T
T
R
R
R
R
R
R
R
7.0
7.3
7.8
8.2
8.7
9.7
11.2
7.7
ft. 3
9.2
9.3
9.6
10.6
11.3
7.3
7.6
e.<«
8.7
9.5
10.1
11.3
5.8
6.3
6.5
6.9
7.2
7.5
8.14
8.7
6.1.
6.9
7.3
8.0
9.1
10.2
1C. 6
11.5
6.2
7.1
8.0
8.7
9.1
9.7
11.3
12G.3
110.2
97.7
89.<«
77.7
60.0
39.2
106.8
98.0
8«*.l
66.0
63.9
58. i«
41*. 8
36.0
110.2
100.2
82.2
73.3
fit.*
50.8
35.2
153.0
li*0.1
127.it
116.3
106.7
96.8
78.5
72.0
11.5.7
119.7
10 8 . 3
89.2
66.9
1.9.5
32.3
110.1
86.7
72.6
65.0
5
-------
EMISSION FACTORS LBS/1COO-GAL FUEL
UNIT
33.0
EXCESS
COND C02, AIR
34.0
A
A
A
A
A
A
T
T
T
T
T
T
T
T
R
R
R
R
R
R
A
A
A
A
A
A
T
T
T
T
T
T
R
R
R
R
R
R
3.9
5.2
6.0
6.5
6.7
7.6
4.8
5.9
6.7
6.8
7.6
7.7
8.2
9.1
4.7
5.9
6.7
6.9
8.1
9.3
8.6
8.7
8.7
9.0
9.1
9.5
6.9
9.3
9.3
9.6
9.7
1C.6
9.6
9.8
10.0
10.3
10.3
11.3
265. 5
17 If. 6
11*3.8
123.3
121.1
94.3
207.7
156.3
127.1
117.3
101.8
101.5
88.2
66.5
211.0
153.1
123.it
112.5
85.9
61.0
67. 7
64.3
62.1
58.3
56.3
5C.1
65.5
60.2
59.0
55.5
53.6
1.2.7
55.5
52.3
49.3
47.2
46.7
33.6
-E GAS,
=/LB FUEL CO
697.1
523.2
464.3
1)25.1
452.43
>339.56
>301.3i|
>275.92
>273.17
123.83
>380.69
>316.87
?280.67
21<». 29
152.72
116.1.2
67.44
28.17
>384.70
>312.93
^276.07
137.61
51.81
18.90
1.96
1.92
2.37
2.31
4.42
6.29
l.<<5
1.1.1
1.1.0
1.52
1.65
6.39
2.88
1.78
2.18
5.59
2.29
11.6.33
HC
793.96
70.57
8. 63
25.1.8
3.15
1.66
25*. 92
61. 46
19.44
4.59
7.1.8
3.68
4.ei
3.36
302.02
37.57
11.47
3.52
3.50
2.57
0.13
0.12
0.07
0.09
0.15
G.19
0.16
O.lt4
0.1<«
O.li.
0.23
0.23
0.10
0.19
0.16
0.22
0.14
2.61
NO
9.77
3.52
3.65
4.29
5.19
6.22
4.60
2. 74
2.1.3
6.49
4.52
6.45
6.62
8.62
5.32
3.52
5.96
7.71
8.92
10.13
9.81
10.47
11.52
10.58
10.12
9.71
10.03
10.54
10.96
11.37
10.91
10.13
11.69
9.70
9.82
8.60
1C. 10
6.13
N02
*-w
27.44
26.35
— —
20.99
15.89
>43.37
>62.96
SS66.92
<42.67
* 54.47
<41.21
< 42.16
< 31.39
> 24.46
>56.79
*47.18
V29.21
< 28.88
4, 18.16
1.07
0.79
0.26
0.76
0.75
0.72
1.59
1.28
1.27
1.24
0.98
1.14
0.00
0.00
0.24
0.00
0.00
0.00
NOX
32.84
31.94
—
28.95
25.43
250.43
>67.16
SS70.64
<52.62
3:61.40
<51.11
<52.31
•<44.62
>32.62
>62.ia
= 56.32
«41.04
<42.55
« 33.68
16.12
16.85
17.92
16.58
16.27
15.61
16.97
17.45
18.09
18.67
17.71
16.67
17.93
14.88
15.29
13.19
15.49
S.40
I
5
-------
EMISSION FACTORS LBS/1000-GAI FUEL
EXCESS DRV —...—.... —... .........
UNIT CONO C02, AIR FLUE GAS,
PERCENT PERCENT SCF/LS FUEL CO HC NO N02 NOX
35.0
T
T
T
T
T
T
R
R
R
R
R
R
R
R
R
7.1
7.8
8.9
9.1
9.7
10.5
7.6
8.0
8.2
8.5
8.7
8.9
9.1
10.1
11.4
11 1 . 1
90.6
68.7
63.7
54.2
42.6
93.9
83.5
78.4
72.5
68. n
63.2
6C.3
46.2
30.2
400.7
361.7
319.9
310. 4
292.3
270.1
368.0
3f*8.2
338. >t
327.2
318.7
309.4
303.9
277.1
2«>6.5
0.1*2
0.56
C.33
0.32
0.15
0.56
0.57
0.72
0.70
O.E8
C.66
0.80
O.E3
0.58
2.91
0.39
0.35
0.31
0.30
0.27
0.27
0.1.9
0.38
0.37
0.39
0.45
0.60
0.47
0.5G
0.
-------
PPM AT 3 PERCENT OXYGEN
uni l
23.0
23.1
23.2
2«*.Q
2(*. 1
2<*.2
25.0
25.1
25.2
26.0
26.1
26.2
27.0
L> unu
A
T
R
A
R
A
R
A
T
R
A
R
A
R
A
T
R
A
R
A
R
A
T
R
A
R
A
R
A
T
R
i/uc.
PERCENT
9.2
9.9
8.3
8.1*
8.7
8.8
7.1
8.9
9.2
8.8
9.0
7.8
8.6
8.1*
8.5
10.8
10.9
9.1
10.1
7.1
8.7
8.8
9.1*
9.4
9.2
9.0
9.1
8.2
a.i
CO
5.1,0
10.31
3.E2
10.1,6
13.1,1
6.75
<*.29
1*22.80
6.08
13.59
3C.OO
26.29
69.90
33.28
16.12
11. E2
18.15
19.03
17.91
11*. 63
15.15
9.96
9.00
15.77
9.69
9.76
7.71
7.1.8
19!62
17.60
HC
12.11
7.63
(*.<,6
10.16
11.87
7.10
23.21,
1..60
6.1.1.
7.91
16.81
1*8.1.6
31.95
8.21
7.97
8.55
10. 5&
7.19
32.25
28.21*
9.23
6. CO
£.1.8
9.55
8.50
10.93
10.36
<<. 68
6.91
11.58
NC
97.76
109.80
101.. 52
128.53
117.15
127.1*5
131*. 61
71*. 28
105.27
98.71
88.05
89.07
91,. 55
97.37
63.86
63.1*9
65.99
6C.16
65.79
53.99
1*7.50
97.77
101.96
98.72
96.91
96.19
92.51
91,. 95
93.57
91.05
98.33
N02
26.26
9.37
5.57
0.00
1.51,
0.00
8.88
71.. 28
7.1,1
2.86
1.1,9
2.87
3.38
0.00
21.29
0.00
7.50
0.00
0.00
0.00
2.57
18.10
<*.50
7.37
7.02
5.58
2.80
1.1*1,
28.35
31.1,0
11.10
NOX
121,. 03
119.18
110.09
128.53
118.70
127.1*5
li*3.i«8
11,8.55
112.68
101.57
89.5«*
91.91*
97,93
97.37
85.15
63.1,9
73.1,9
60.16
65.79
53.99
50.07
115.87
106.1,6
106.08
103.93
101.77
95.32
96.39
121.92
122. «»5
109.1*3
CO
-------
PPM AT 3 PERCENT OXYGEN
UNIT CONO
28.0
29.0
30.0
31.0
32.0
T 8.7 136.91 1..26 95.81. 9.13 102619.E2
>2<«82.18
> 2<»50.1i»
26.31.
19.52
23.51)
3. €8
5.20
HC
25.65
3.08
7.72
5.90
6.77
39.65
13.91
17.01
19.93
6.38
3.2<«
3.30
23.18
i|.26
e.<
-------
PPM AT 3 PERCENT OXYGEN
23. D
2
-------
PPM AT 3 PERCENT OXYGEN
UNIT COND C02,
PERCENT
25.0 A 7.7
A 7.8
ft 9.5
A 1C.6
A ll.i.
T 9.1
T 9.3
T 9.5
T 9.7
T 10.6
T 11.6
R 6.6
R B.9
R 9.It
R 9.6
R 9.9
R 11.1
A 7.1
A 7.7
A 6.0
A 8.8
A 10.9
A 11.2
T 7.3
T 7.6
T 8.3
T 9.1
T 9.7
T 10.6
T ll.i*
R 7.3
R 7.7
R 9.3
R 10.8
R ll.<*
CO
8.20
8.08
5.31,
8.M3
12.31
l.iil
1.38
1.35
3.95
2.
i».30
2.68
i*. 91
6.79
35.90
23.78
16.75
13.29
12.48
HC
1.61.
C .81
0.67
0.60
1.12
1.13
1.66
2.98
0.39
o.es
1.33
1.1*6
1.1.2
1.3<<
0.92
1.27
1.71
2.26
2.17
t.17
1.92
1.89
1.53
1.60
1.80
1.71
1.87
1.72
1.61
1.59
1.1.7
2.15
1.87
1.5>*
1.1.5
l.<»7
NO
65.63
61.. 67
68.07
67.1.7
61.56
70.35
66.3l«
61.. 95
67.1i»
59.77
53.12
70.2i»
69.1.7
69.78
68.11*
66.25
55.89
88.67
9I..15
95.08
99.32
97.58
91..15
91.. 98
99.21
107.71
109.19
106.88
105.73
10ii.27
0.00
96.92
101.93
99.13
93.01
91.89
N02
19.69
19.1.0
20.02
2i*. 10
22.39
0.00
1.38
1.35
0.00
0.00
0.00
1.1.6
D.OO
0.00
0.00
0.00
6.31*
39.62
32.59
30.03
25.63
23.30
36.1.8
1.2. 3<*
l°.8i*
10.26
I..68
0.00
0.00
0.00
0.00
25.13
23.78
20.91*
22.95
30.63
NOX
85.32
BI.. 07
88.09
91.57
83.95
70.35
67.72
66.30
67.11*
59.77
53.12
71.71
69.1.7
69.78
68.11.
66.25
62.73
128.29
126.73
125.11
121.. 95
120.86
130.61*
137.32
119.06
117.97
113.87
103.88
105.73
101*. 27
O.DC
122.05
125.71
120.08
115.96
122.52
-------
PPH AT 3 PERCENT OXYGEN
UNIT COND
27.0
nu
A
A
A
A
A
T
T
T
T
T
T
R
R
R
R
R
A
A
A
A
T
T
T
T
T
T
T
R
R
R
R
R
R
R
LU27l»5.66
1«.81.3<*
239. 1(0
25.56
20.96
8.33
6.1,5
8.01
10.85
10.53
10.23
33.50
13.73
13.73
11.57
13.17
11.12
11.05
HC
29.21*
i*.5B
2.18
3.(.9
2.16
8.59
5.09
3.67
2.20
1.68
1.26
7.12
3. 62
2.23
—
—
276.80
1*9.93
33.36
22.15
5.91*
5.33
5.16
5.12
14.65
l*.61
<*.66
7.C5
6.C1
l«.29
3.80
3.79
3.65
3.63
NO
76.75
109.95
110.38
109.00
98.95
9<*.i*5
100.li*
106.90
115.82
12i«.37
118.81*
81.90
97.18
101.72
111.81*
109.70
19.93
1*5.77
58.87
98.81*
68.12
90.02
98.30
99.27
9<». 55
96.28
95.00
79.35
96.09
108.11
109.10
110.29
109.59
107.32
N02
67.61
27.1*9
15.98
19.56
13.95
17.17
11.13
7.6i*
7.33
i*.19
1.26
21.36
11.53
Hi. 30
13.1*2
li». 5i«
265.73
220.51*
168.76
102.25
19.21
6.67
6.1*5
e.<»o
10.85
9.03
10.23
33.50
22.31
12.01
23.11*
21.1*0
22.21*
23.67
NOX
11.1*. 37
137,«*i»
126.36
128.56
112.90
111.62
111.27
111*. 53
123.15
128.56
120.11
103.26
108.71
116.03
125.26
121*. 2i«
285.66
266.31
22V.63
201.09
87.33
96.68
104. 71,
105.67
105.1*0
105.30
105.23
112.86
118. i*t
120.12
132.21.
131.69
131.83
130.99
28. 0
bs
-------
PFM AT 3 PERCENT OXYGEN
29.0
30.0
NU l,Ul«
PERCENT
A 4.8
A 4.9
A
A
A
A
A
T
T
T
T
T
T
R
R
R
R
R
R
R
R
R
A
A
A
A
A
T
T
T
T
T
R
R
R
R
R
R
R
R
5.1
5.4
5.5
5.9
6.3
6.2
6.4
6.7
7.1
8.1
8.6
6.0
6.2
6.4
6.7
6.9
7.2
7.8
8.0
8.2
7.7
7.9
8.2
8.3
8.7
5.9
6.1
6.7
6.9
8.7
5.5
5.7
6.1
6.5
6.9
7.3
7.3
7.8
CO HC
>3181.94 >256.61
r 1722. 94 8.83
422.15
116.33
75.16
44.60
23.63
41.20
17.77
13.17
8.84
12.38
30.82
60.81
56.18
52.51
48.22
37.35
30.54
34.32
39.59
67.73
13.11
11.27
9.37
10.73
20.49
313.78
92.41
30 .09
21.92
33.29
679.50
1J3.24
44.71
11.51
3.E2
5.14
1.71
0.00
7.32
6.98
7.G6
6.80
7.36
4.53
4.34
4.14
5.83
17.79
19.08
13.68
18. C6
26.20
37.10
37.35
32.23
18.72
12.18
6.10
7.86
8.C5
8.12
7.36
7.61
11.74
12.32
12.03
9.50
18.82
9.00
6.68
6.50
6.14
5.79
4.79
5.48
5.14
NO
17.96
22.70
46.36
74.45
86.55
95.82
105.47
82.41
90.82
133.48
107.86
102.11
101.25
74.59
80.25
87.51
94.59
99.60
101.79
99.83
102.03
104.54
124.51
120.80
113.99
116.54
112.70
55.50
69.82
92.14
96.62
81.06
15.75
42.98
65.03
82.51
97.71
101.01
139.57
109.32
N02
100.08
90. SI
58.56
20.94
11.39
0.00
0.00
12.36
7.90
1.88
1.77
4.64
1.47
20.72
20.06
15.56
7.42
8.89
6.79
6.24
4.57
5.89
32.77
33.82
29.67
38.34
55.62
64.04
49.29
35.73
25.57
24.61
1D3.50
68.77
40.65
26.86
19.90
15.41
15.41
14.47
NOX
118.04
113.52
104.93
95.39
97.93
99.82
105.47
94.77
98.71
105.36
109.63
, 106.76
102.72
95.32
100.31
103.07
102.01
1D8.49
108.56
106.07
106.60
110.43
157.28
154.62
143.66
154.88
168.31
119.53
119.11
127.87
124.19
105.66
119.25
111.73
105.68
109.38
117.61
116.42
124.98
123.79
-------
PFM AT 3 PERCENT OXYGEN
31.0
JN!)
A
A
A
A
A
A
A
T
T
T
T
T
T
T
T
R
R
R
R
R
R
R
A
A
A
A
A
A
A
A
T
T
T
T
T
T
T
T
R
R
R
R
R
R
R
uuz,
PERCENT
7.0
7.3
7.9
6.Z
8.7
9.7
11.2
7.1,
7.7
8.3
9.2
9.3
9.6
10.6
11.3
7.3
7.6
8.1,
8.7
9.5
10.1
11.3
5.8
6.3
6.5
6.9
7.2
7.5
B.I.
8.7
6,1,
6.9
7.3
8.0
9.1
10.2
10.6
11.5
6.2
7.1
6.0
8.7
9.1
9.7
11.3
CO
3<».37
32.80
30.81,
27.90
26.16
26.33
62.65
5.38
6.66
i».79
5.75
5.68
4.12
5.01
25.89
9.11
8.67
6.32
7.51
5.56
6.53
37.1*3
1783.<48
919.03
260.51*
88.21
50.20
31.Qt»
35.59
1*1.71,
1*92.76
66.73
30.73
18.05
8.68
10.36
13.70
1.0.09
1060.57
58. 3d
22.66
19.1,5
15.73
17.37
57.59
NC
6.11
5.28
I..28
<«.60
i*.16
3.M
3.61
6.63
5.66
8
3.97
3.56
3.1*3
4.27
2.67
2.17
0.82
0.72
0.65
0.62
1.03
19.01
3.10
2.10
1.65
0.00
1.3
-------
UNIT CONO
33.0
PPM AT 3 PERCENT OXYGEN
34.0
nu iiuc*
PERCENT
T
T
T
T
T
T
T
T
R
R
a
H
R
R
A
A
A
A
A
A
T
T
T
T
T
T
R
R
R
R
R
R
3
5
6
6
6
7
4
5
6
6
7
7
8
9
It
5
6
6
e
9
6
8
8
9
9
9
8
9
9
9
9
10
9
9
10
ID
IB
11
.8
.2
.0
.5
.7
.6
.8
.9
.7
.8
.6
.7
.2
.1
.7
.9
.7
.9
.1
.3
.6
.7
.7
.0
.1
.5
.9
.3
.3
.6
.7
.6
.6
.8
.0
.3
.3
.3
CO
>3942
>2959
>2626
,> 2404
>238fl
1079
>3317
>2761
>2445
1867
1333
1014
587
245
>3352
>2727
>2405
1199
451
16<4
17
17
21
23
39
55
12
12
12
13
lit
56
25
15
19
1.9
20
13C2
HC
.8212U82
.20
.17
.58
.ei
.16
.El
.50
.•=7
.50
.57
.59
.73
.<<&
.55
.17
.89
.27
.52
.73
.1*8
.12
.11
.61
.35
.98
.°4
.52
.'.2
.••9
.£6
.93
.€4
.86
.ti2
.79
.35
.77
1C73
131
387
48
25
3879
«35
295
6S
113
55
70
51
4596
671
171.
53
53
39
2
1
1
1
2
2
2
2
2
2
3
3
1
2
2
3
2
i.O
.83
.90
.31
.81.
.00
.29
.M6
.35
.88
.80
.83
.98
.20
. 1".
,Zk
.83
.62
.51
.22
.09
.C<*
.86
.13
.37
.31
.99
.<<<•
.23
.21
.16
.60
.59
.62
.91
.46
.45
.16
.53
NO
79.230
>334
S355
<226
«288
<218
<2Z3
<166
>129
>301
»250
*154
<153
< 96
5
4
1
4
4
3
8
6
6
e
5
6
0
0
1
0
0
0
.57
.78
.35
.31
.09
.05
.06
.36
.96
.66
.66
.56
.78
.31
.29
.98
.20
.32
.83
.28
.41
.12
.07
.91
.62
.95
.90
.75
.33
.19
.00
.00
.29
.00
.00
.00
NOX
174
169
153
134
>267
>356
K374
<279
*325
<271
<277
<236
>173
>329
«298
• 217
<225
•(178
87
91
97
92
88
84
91
94
98
101
95
90
.21
.43
.59
.89
.55
.32
.79
.18
.74
.14
.54
.69
.03
.90
.80
.71
.76
.69
.38
.32
.09
.04
.20
.62
.99
.58
.01
.20
.97
.35
97.16
80
82
71
83
50
.62
.87
.49
.96
.95
-------
PPM AT 3 PERCENT OXYGEN
UNIT CONO C02,
PERCENT
35.0 T 7.1
T 7.8
T 8.9
T 9.1
T 9.7
T 10.5
R 7.6
R 8.0
R 8.2
R 8.5
R 8.7
R 8.9
R 9.1
R 10.1
R 11. <•
CO
3.E6
<».96
2.92
2.81.
1.3i*
i».9i(
5.05
6.37
6.19
5.98
5.83
7.07
5.55
5.07
2i».79
HC
E.C
-------
J-l
APPENDIX J
CALCULATED EMISSION FACTORS
FOR COMMERCIAL BOILERS
-------
EMISSION FACTORS L8S/1COO-GAL FV=L
UNIT CO NO
co2,
C.AUC.ii
«IR
PERCENT PERCENT
^02001 R
No. 2 oil R
R
R
H
H
H
H
H
H
L
L
L
L
L
L
L
11.6
i?.i
13.0
13.5
9.3
9.9
10.9
12.1
12.2
13.4
9.3
9.9
10.9
11.4
12. Q
12.0
13.0
27.9
23.6
16.0
11.4
52.5
52.1
39.5
2?. 6
24.8
14.6
56.8
46.0
35.2
29.7
24.4
23.1
14.8
UKT
FLUE GAS,
SCF/LB FUEL
2i»2.9"
234.7
220.1
211.3
309.3
289.2
265.1
238,6
237.0
217.5
298.3
281.5
257.0
246.4
236.3
233.7
217.9
CO
"0.75
0.61
3.52
61.IT+
21.06
11.64
5.61
1.72
1.59
2.«*7
37.55
11.47
1.72
0.89
0.61
0.60
5.51
HC
0.03
0.05
0 .06
4.99
1.78
0.79
0.35
3. 11
0 .11
0 . 08
3.52
0.75
0.15
0.11
0 .12
0 . 12
0.27
MO
7.79
7.52
6.81
[.56
8.55
6.63
8.64
6.04
7.86
7.33
6.10
e.38
6.53
6.67
6.14
6.07
E.4?
N02
b.oo~ ""
0.00
0.19
0.00
0.26
0.00
0.00
0.20
0.20
0.00
1.26
1.19
0 . 44
0.00
0.80
0.59
0.18
EMISSION FACTORS LBS/MILLION-
C2001~ R "~
Gas R
R
R
R
H
H
H
H
H
H
L
L
L
L
L
7.5
7.9
8.5
9.1
9.9
7.3
7.6
' 8.4
9.1
9.2
10.3
6.4
7.1
7.7
3.4
9.1
51.7
43.6
3t. 2
27.3
17.3
5E.fi
48.7
37.0
27.3
24.9
14.0
74.9
58.5"
1,6.3
36.1
24.9
329.3
311.0
29<».l
273.8
250.9
338.8
322.5
295.8
273.8
2S8.3
243.5
382.3
3<*i».7
317.1
293.8
268.2
296.11
154.29
78. 34
20.06
25.07
372.26
279.23
121.14
46.50
42.89
288.65
446.81
332.88
244.97
17<*.15
4J.19
69. 08
32.61
28. 04
23.50
0.72
164.73
" 101.47
31.02
18.28
18.93
11.14
342.61
200.49
108. 84
72.84
34.78
56.40
66.. 57
77.64
67.41
69.83
6C.43
66.74"
72.81
69.36
68.93
53.86
49.10
61.49"
67.88
66.14
67.94
12.61
5.10
1.61
0.00
4.12
11.12
10.58
3.24
5.99
0.00
6.66
18.82
"15.0 8
8.67
9.64
2.93
NOX S02
11.94~~~
11.53
10.63
10.21
13.37
13.24
13.25
12.54
12.25
11.24
10.62
10.97
"10.45
10.23
10.21
9.90
8.49
01 FT
99. 09
107. 17
120.65
103.36
111.19
103.78
112.91
114.87
112.35
105.69
89.24
94.10
109.37""
112.75
114.12
107.10
38 . 40
38. 20
38.95
41.38
37.95
38.22
38.15 ~"~ "
39.97 Baseline
38.56
40.02
35.19
37.20
37.60
37.49
37.91
36.40
38.30
•
;-
Baseline
C-l
I
co
-------
EMISSION FACTORS LBS/1000-GAL FUEL
UNIT COND
C02,
AIR FLUE GAS,
PERCENT PERCENT SCF/Lb FUEL CO
C2002 R
No. 2 oil R
R
R
R
H
H
H
H
H
H
M
"" M"
M
M
M
L
_ L
L
L
L
L
C2002 R
No. 4 oil R
R
R •
3
R
H
H
H
H
H
H
M
M
M
M
M
L
L
L
U
L
10.5
11.3
12.3
13.2
13.8
8.6
9.1
10.2
11. -i
12.7
12.9
8. 3
10. r "/
11.0
12.0
13.3
7.6
ft. 3
9.4 '""
11.0
12.1
12.7
7.3
fi.7
9.9
11.2
12.1
13.5
8.2
9.1
10.3
11.3
12.3
12.8
8.0
9.9
10.9
12.0
13.3
5.S
6.3
10.1
11.9
13.0
i»3. 8
38.1)
26.9
15.4
10.2
74.9
&e .a
1*9.4
30.0
22.1
20. 5
91.8
50.6 """
38. 4
27.2
15.0
97.5
B3.3
S3. 0
39.3
34.3
2C.7
96.5
77.5
54.8
36.9
26.5
14.6
79.7
61 .9
38.4
31.1
25.1
15.6
BE .5
5?.l
39.5
26.6
11.6
153.8
79.3
48.1
Z ( •-. 1
14.2
273.5
262.2
241.0
219.1
209.1
333.0
317.5
284.1
247.1
231.8
228.8
365.4
.286.5
263.1
241.7
218.3
376.3
349.2
310.2
264.8
293.5
229.2
367.3
331.5
289.1
255.4
236.0
213.8
335.7 '
302.4
258.4
244.7
233.5
215.6
348.3
284.0
260.5
236.3
208.1
474.5
335.0
276.5
235.3
213.0
0.00 ""
0. 00
0.00
9,27
>132.65
0.34
C.33
0.15
0.51
5.38
11.57
1.32
"0.89 """
0. 81
1.37
>138.48
0.19
0.00
0. 00
0. 00
0. 00
1.42
0.81 "
0.55
0.46
0.28
0.13
71.73
0.00
• 0. 00
0.00
0.00
0.26
>146.62
0. 19
0.00
0.14
0.00
>141.51
6.3G
0.56
0.31
0.13
>144.80
HC
< 0 . 0 8
<0 . 08
< 0.07
<0.06
0.62
^0.10
< 0. 09
< 0.08
0 . 04
0.89
0 .47
40.11
0.10
0. 16
0.23
6.45
-------
EMISSION FACTORS LBS/1000-GAL FUEL
EXCESS CRY ..........
UNIT COND C02, AIR FLUE GAS,
PERCENT PERCENT SCF/L8 FUEL CO
C2002 . R
CR R
R
R
R
H
H
H
H
H
H
M
M
M
M
:1
M
L
L
L
L
L
L
9.3
10.0
11.0
12.1
12.6
7.6
8.7
10. 1
11.7
12.1
12.8
6.9
B.7
9.7
10.9
12.1
13.0
6.2
8.5
9.6
10.8
11.9
13.4
54.3
46.6
36.5
25.2
20.8
94.4
72.2
48.4
2fi.3
2S..1
18.6
112. 6
72.2
57.3
40 .2
27.3
17.7
lit 6. 9
8 6, . 9
61.7
i*3.7
30,7
15.7
309. 7
279.9
257.1
235.6
227.2
366.7
324.8
279.5
21*1.5
236.9
223.1
1*01.3
324.8
296. iT
26i». 1
239.7
221.1*
469.9
352.5
3QI».8"
270.6
246.1
217.7
0.00
0.00
0.00
0.00
97.97
0. 00
0.00
0.00
0. 00
0. 00
0. 86
0.22
0.00
0.00
0. 00
0.00
0.24
1.30
0.19
0. 00
0.00
0.00
6.38
HC
i
—
—
—
—
—
—
•••
—
—
—
—
—
—
"~ —
—
—
—
—
—
~ — " ~
—
—
-™ •
NO
41.82
45.26
43.09
39.90
32.43
39. 31
42.12
41.05
37.19
3fc. 06
31.31
36.12
37. 70
37.04
3S.66
34.21
29.11
34.79
39.67
36.^7
35.58
33.23
25.78
N02
1.12
1.78
3.97
O.i*3
1.21*
2.33
1.18
0.51
1.32
0.00
1.01
2.55
0.59
0.81
!.!»<.
0.00
1.01
1.71
0.00
1.35
0.00
0.00
0.1*0
NOX
65.25
71.18
70.05
61.61
50.96
62.61
65.77
"&3.*»6
58. 3«*
55.29
i*9. 03
57.91*
58.39
57.60
56.11
52.i*6
i»5.6i*
55.05
60. 82
57.30 '
5i*. 56
50.95
39.93
S02
li*i». 87
152.18
156.03
157.85
157.98
148.35
151.91
11*8.1*1
152.66
155.75 Baseline
159.63
136.96
11*3.70
11+9.88 "" "
153.56
151.52
151.16
1<*2.58
160 . i+3
150.30
157.39
155.51*
151.34
EMISSION FACTORS LdS/HILLION-CU FT
C2002 R
Gas 3
R
R
H
H
H
H
M
M
M
L
L
L
L
7.6
8.4
9.1
9.9
7.3
8.6
10.0
10.0
7.4
8.6
9.9
6.9
8.3
9.1
9.9
5C .3
37.4
2f . 6
17.0
47.9
35.5
16.it
16.1
52.1
32.6
16.1
55.5
38.2
25.5
16.7
326.0
296.7
272.2
250.2
320.8
292.4
249.0
2<*8.3
330.3
285.9
21*8.2
360.3
298.5
269.8
249.6
3.26
0.99
2.72
2.50
0.00
0.00
0. 83
a. 83
0.00
G.OO
0. 00
1.20
0.00
0.00
4.99
0.37
0.85
0.31
0.52
0. 37
0.17
0 .14
0.62
0.69
0.65
0.95
1. 03
0.91
0.77
0.71
93.05
87.37
82.54
81.24
67.52
80.33
82.62
80.63
74.24
79.55
78.81
63.08
8C.93
35.66
78.35
0. 00
0.00
l.«*9
0.00
5.26
0.00
1.36
1.36
0.00
0.00
2.72
0.00
0.00
0.00
1.37
11*2. 68
13<*. 71*
128.05
12«*.57
108.80
123. 17
128.05
12<*.98
113.31*
121.98
123.56
96.72
121*. 09
131.3(»
121.50
Baseline
I
Wl
-------
EMISSION FACTORS LBS/1000-GAL FUEL
cv r c c c
UNIT SOND
C02, MR
PERCENT PERCENT
cz6o3~ R
:. No. 2 oil R
"~ " H
H
H
H
H
H
M
M
M
M
M
L
L
L
L
L
L
C2003 R
CR R
H
H
H
H
M
M
"1
M
1
L
L
L
L
L
13.2
14.5
10.0
11.2
12.1
12.1
13. 3
13.9
7.6
9.3
13.5
11.9
13.1
6.6
7.5
9.7
12.0
1?. 6
13.0
12.2
12.7
9.5
10. 4
12.3
13.4
7.4
' 9.0
9.9
11.9
13.6
6.2
7.2
8.6
9.3
11.8
16.
7.
52.
36.
27.
27.
16.
11.
99.
51.
!*3.
26.
16.
123.
IOC.
54.
25.
21.
16.
24.
16.
59.
40.
26.
14.
10 E.
7t.
52.
28.
13.
138.
109.
76.
&2.
30.
5
0
7
6
7
3
i*
9
1
7
2
5
0
1
4
4
6
0
7
7
9
4
if
7
2
5
8
9
7
4
7
3
1
3
0
FLUE GAS,
SCF/LB
221
203
291
260
243
242
221
212
380
308
272
240
220
426
382
294
239
230
222
234
220
300
264
238
214
339
322
288
242
213
t50
394
332
305
244
FUEL
. 5
.3
.2
.2
.1
.3
.3
.8
.2
.4
.8
.7
.6
.3
.7
.4
.1
.3
.0
.6
.0
.5
. i*
.6
.8
.7
.1
.2
.3
.3
.6
.9
.0
.9
.8
..CO
0.00
1.15
0.03
0.00
0.00
0. 00
0.00
0.00
0. 00
0.00
0.00
0.00
0.00
1.54
0.20
0.00
0.00
0.00
0.00
0. 39
0.49
0 . 66
0. 44
0. 26
(j. 36
1.72
C.89
a. 64
U.40
C.59
6.23
1.96
1.10
1.01
0.95
HC
0.10
0 .24
0.26
0 .19
0.18
0 .21
0.20
0.19
0. 28
0.21
0.18
0.14
0.13
0.63
0 .68
0.61
0.32
0 .61
0.39
0.23
0. 19
0 . 11
0. 1C,
0. 09
0 . 08
0 . 11
0 . 09
0 . 39
0.09
0.03
0.06
0.07
3.09
0.12
0.12
MO
10.27
9.65
1C. 29
9.33
9.39
9.36
6.67
8.22
9.23
8.51
8.13
7.71
7.06
8.47
8.66
7.96
7.13
6.86
e.74
27.65
27.62
27.7o
26.77
26. 7U
2S.06
26.62
28.23
27.31
2?. 83
23.24
2E.35
26.19
25. 76
2&* QC
21.75
- N°2
0.37
0.00
0.49
0.44
0.21
0.00
0. 37
0.54
0.64
0.26
0.46
0.20
0.56
2.53
0.97
0.25
0.20
0.39
0.19
0.85
0.60
1.36
0.48
3.22
0 .CO
0.71
0.00
0.52
O.CC
0.19
1.64
0.72
0.00
0.83
0.89
_. NOX
16.13
14.80
16.27
14.75
14. 61
14.36
13.66
13.15
14.80
13.31
12.93
12.02
11.39
15.52
14.25
12.46
11.13
10.91
10.52
43.26
42.95
43.93
41. 53
41.16
38.43
44. 59
43.29
42.39
39.61
35.84
40.51
40. 88
39.49
39.17
34.23
S02
24.02
25.16
24.02
22.69
22.91
24.56 Baseline
22.95
23.57
24.19
23.26
23. 14
23.54
23.91
21. 10
23.45
24.28
24.23
22.79
24.06
154.25
161.29
151.96
155. 08
136.82 Baseline
158. 61
145.82
150 .67
149.37
153.18
153.71
134.43
139.78
151.09
15G. 83
154.73
C-l
a*
-------
EMISSION FACTORS LBS/lOO0-GA.L. FUEL_
UNIT COND
C02, ft IR FLUE GAS.
PERCENT PERCENT SCF/LB FUEL CO
C2003 R
-No. 6 oil R
R
R
H
H
H
H
H
H
M
M
H
rt
4
M
M
M
L
L
L
L
L
L
L
C2003 R
Gas R
R
R
H
H
M
H
H
M
M
M
M
L
L
L
L
L
11.5
11.8
13.0
13.4
9.2
10.3
11.0
11.9
12.5
13.3
7.2
8.1
9.0
9.7
11.3
12.0
12.3
13.3
6.7
7.3
8.3
9.2
10.9
11.2
12.5
" 9.5
10.0
11.2
11.4
7.6
9.3
9.7
1!J. T
11.1
7.4
8.9
10.1
10.7
6.5
8.3
9.2
10.9
11.4
32.8
29.6
18.4
IE. 4
66.7
46.9
40.0
29.9
23.9
17.1
109. 7
38.0
71.2
57.1
36.4
29.4
26.3
13.5
126.3
108.2
82.6
64.2
40.1
34.9
23.3
~ 20.8"
16.4
5.1
2.9
3 1". 9
26.4
19.0
16.1
5.6
55.4
30.9
15.6
5.5
79.0
39.5
26.3
16.4
3.1
246.0
240.1
219,2
213.8
309.0
275.9
259.3
240.6
229.6
216.8
388.7
348.5
317.4
291.1
252.7
239.6
234.0
210.2
419.7
386.1
338.5
304.3
259.6
250.0
228.3
1.56
1.38
1.01
1.35
2.31
1.75
1.49
1.25
1.32
1.25
2.91
1.61
1.28
1.01
0.58
0.41
0.40
C.61
7. 01
5.11
3.90
3.15
2.39
2.45
2.39
HC
0.11
0.10
0.10
0.14
0.22
0.20
0.19
0 . 25
0.17
0.18
0.12
0.10
0.09
0.09
0.06
0. 12
0.07
0.28
0.94
0. 87
0.77
0.71
0.60
0.60
0.55
NO
39.62
38.96
37.73
37.45
39.27
39.65
37.44
37.10
36.11
34.78
33.81
34.40
34.66
34.13
32.59
30.75
30.46
27.63
35.99
35.97
3^.66
34.36
33.64
31.31
29.15
N02
1.16
1.14
0.62
0.00
1.46
0.00
0.98
0.00
1.09
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
2.38
1.46
1.60
0.86
1.23
0.71
0.86
NOX
61.91
60.88
58.47
57.43
61.68
60.80
58.38
56.89
56.46
53.32
51.85
52.75
53. 14
52.33
49.97
47.14
46.71
42.36
57.56
56.61
54.75
53.54
52.81
48.71
45.56
S02
369.37
366.82
363.70
368.77
358.12
356.02
362.00
364.33 Baseline
356.72
365.45
322 . 49
330.47
334.36
333.55
342.83
334.47
345.15
348.85
331.60
330.49
338.75
344.65
—
362.12
—
- EMISSION FACTORS LBS/MILLION-CU FT
"" 259.0
249.0
223.2
218.2
329.7
276.1
254.8
248.3
224.2
337.8
282.0
247.1
224.1
391.5
301.5
271.6
249.0
218.7
0.66
0.83
6.69
744.65
2.20
0.92
0.85
4.13
5.97
2.25
1.88
1.65
925.17
6.52
8.03
6.33
5.80
222.11
0.59
<0.47
<0.43
<0.42
0.75
0.63
0.58
0.47
0.51
0.64
0.54
0.47
10.68
^0.75
<0.57
<0.52
<0.47
1.67
97.96
103.06
97.97
98.85
81.16
96.55
99.10
IOC. 12
92.79
89.19
95.59
91.70
75.14
89.40
92.51
68.16
83.51
65.54
0.00
9.53
4.88
0.00
3.61
4.53
1.39
4.08
7.36
0.00
0.00
5.41
0.00
2.14
0.00
1.49
0.00
. 5.93
15 0 . 21
167.56
155.10
151.57
128.06
152.58
153.35
157.59
149.64
136.76
146.57
146.02
115.22
139.22
141.85
136.67
128.05
106.47
.....
Baseline
-------
EMISSION FACTORS LBS/1000-GAL FUEL
UNIT COND
C02,
PERCENT
C2004 R
No. 2 oil R
R
R
R
H
H
H
H
H
H
M
M
M
M
M
••1
M
L
L
L
L
L
~ C2004~~ R
CR R
R
R
H
H
H
H
H
M
M
M
M
M
M
L
L
L
L
L
11.0
11. 4
12. 1
12.2
14.1
9.1
11.0
12.0
12.1
13.1
14.0
7.1
8.6
13.0
10.6
12.3
12. 8
lu. 3
6.5
7.9
9.3
10. &
11.5 "'
10.6 ~
11. 1
12.1
12.9
10.0
10.9
12. 1
13.2
15.3
7. 4
8.5
9.6
10.5
12.2
14, 3
4.7
6.5
3.0
10.0
11.9
HIR FLUE GASi
PERCENT SCF/LB FUEL CO
45. 0
37.7
24.7
2 6 • 4
9.7
&5.2
38.1
26.3
25.1
16.2
9.5
139.7
73. 2
49.5
39.4
^6.3
19.7
4.9
123.5
38. 2
66.7
41.5
31.1
4 C . 8
35.5
25.2
ie .4
48. 1
36.2
25.2
15.9
3.6
90.6
S9.1
51.6
41.4
24.3
9.4
23 8 . 1
134.6
37.1
5 C . 6
2 e. . 9
276.3
262.2
237.3
240.5
208.5
315.1
263.1
240.3
238.0
221.0
208.2
400.6
330.4
284.9
265.5
240.3
227.8
199.3
427.1
359.3
318.0
269.6
249.7
265.1
255.2
235.6
222.8
279.0
260.2
235.6
218.1
194.8
359.5
318.7
285.7
266.3
234.0
205.7
633.9
44?. 9
352.8
283.8
238.8
0. 00
0.00
0. 00
0.00
3.19
0.00
0.00
0.00
0.00
c.oo
4.67
2. 36
0.00
0.03
G. 00
0. 00
Q . 0 0
2. 95
27.24
0. 00
0.00
C. 30
0.00
0.00
0. 00
0. 00
0. 00
0.15
0.00
0.00
Q. 30
5. 06
0. 99
0.18
0.03
G. 00
0.00
0.34
17.66
0.24
0.00
3.00
0.26
HC
0.26
0 . 25
0.26
0 .27
0 .23
0. 29
0.25
0 . 13
0 . 26
0. 23
0 .22
0.59
0.25
0 . 22
0 .21
3. IB
0 . 19
3 . 23
1. 25
0 . 19
0.16
0. 18
" 0.11
" 0 . 52
0 .51
0.47
0.44
0.<»7
0 .44
0 . 40
0 . 38
0.34
0.59
0.53
0.48
0.46
4 0. 44
0.40
1.11
0.57
0. 48
0 .40
0.38
NO
14.80
14.91
14.27
14.33
11.86
14.82
1^.39
13.53
13.01
12.33
11.27
1C. 08
12.28
12.15
12.19
12. 35
12.08
1C. 79
9.57
12.57
12.87
14.00
12.01
36.42
35.07
33.21
33.79
35. 03
35.45
35.02
31.90
28.03
31.08
32.28
34.01
"" 34.70
35.20
31.67
38.97
43.28
42.00
40.50
36.78
N02
0.46
0.<*4
0 .20
0.60
0.17
0.00
0.22
0.20
0.20
0.19
0.00
0 .67
0.03
0.30
0 .22
0.00
" " 0 . 0 0
O.UO
0.72
0.00
0.30
0.00
0.00
o'ltio"
0.46
0.00
0.00
0.00
0.00
0.00
1. 19
2.30
0.00
0.00
0.00
0.73
0.85
0.56
1.16
0.00
1.28
1.03
0.00
NOX
23.16
23.30
22.08
22.58
18.35
22.72
22.28
20.95
20.15
19. 09
17.28
16.12
18.33
16.63
18.92
18.94
18.52 "
16. 54
15. 4C
19.28
19.73
21.47
18.42 "
'~"55.85~
54.23
50.92
51.80
53.72
54.35
53. 70
50.10
45.28
47.66
49.50
52.15
53.94
54.82
49.12
6C.92
66.36
65.69
63.13
56.39
S02
31.28
31.21
28.80
30. 04
30.66
29.05
29.48
28.61 Baseline
29.72
29.92
30.13
26.18
27. 76
27. 93
28.50
28.61
23. 71
29. 77
24.92
29.77
29.69
29. 89
29.72
140 .76
145. 18
145.93
146.49
141.10
141.47
148.91 " " Baseline
146.12
150.21
131.78
124.92
137.25
138.05
11*1.99
145.61
121.15
145.56
142.7*
143.50
150.97
oo
-------
.EMISSION FACTORS LBS/1000-GAL FOIL
UNIT CONO
C02,
cxut
MR
FLUE GAS,
PERCENT PERCENT SCF/LB FUEL CO
C200A R
No. 5 oil R
R
H
H
H
H
H
M
M
M
M
M
L
L
L
L
11.3
12.0
13.8
9.1
10. 0
10.8
12.0
13.0
7.5
8.7
9.5
10.7
12.3
5.9
6.9
8.6
12.0
36.
26.
13.
58.
53.
42.
29.
2f.
100.
72.
59.
43.
26 .
159.
12 C.
?e.
29.
5
7
4
7
6
6
8
1
9
5
2
7
it
5
8
9
1
251.3
237.0
208.8
310.5
282.8
262.5
239.0
221.1
369.8
317.5
293.1
264.6
232.8
477.5
4G6.3
325.6
237.6
0.15
0.00
0.12
0. 36
0.00
0.00
0.00
0.00
2.35
0.18
0. 00
0.00
0. 00
83.42
3.76
0.57
0. 27
HC
0.36
0.32
0.26
0.36
0.32
0.29
0.29
0.24
0.59
0.50
0 .49
0 .42
0.37
1.90
0.57
0.4*
0 .33
NO
43.30
43.03
39.74
42.15
42.76
43.29
43.11
42.22
38.51
39.56
39.96
41.00
41.85
29.89
37.52
39.55
41.39
N02
0.48
1.13
0.60
1.18
0.54
0.50
0.91
0.00
1.05
1.21
0.00
0.00
1.11
3.63
1.93
0.93
0.68
NOX
66. 87
67.11
61.53
65.81
66. 11
66.87
67.01
64.73
60.10
61.86
61.28
62.87
65. 27
49.46
59.47
~ 61.58
6fc. 14
S02
371.
369.
373.
357.
362.
364.
366.
371.
347.
357.
360.
367.
372.
341.
354.
366.
377.
03
95
01
41
89
74
83 Baseline
58
37
09 "
60
58
71
15
81
15
29
EMISSION FACTORS LBS/MILLICN-CU FT
C2004 R
Gas R
R
R
H
H
H
H
H
M
M
M
M
L
L
L
L
L
L
L
L
8.5
9.1
10.1
10.7
6.2
7.0
9.3
10. 3
11. 2
4. 7
5.4
6.9
10.1
10.6
2.3
3.5
4.6
5.7
7.8
9.1
9.8
11.2
37.
27.
IE.
1C.
89.
SE.
30.
17.
4.
137.
13 u.
51.
15.
10.
296.
213.
144.
97.
47.
27.
19.
5.
5
3
9
1
9
8
3
4
4
9
5
8
6
1
4
8
8
4
4
7
1
1
297.1
273.8
247.8
234.6
416.4
361.4
280.5
251.1
221.6
525.3
449.6
352.3
247.1
234.5
886.7
698.7
541.4
433.5
319.6
274.7
255.0
223.2
0.00
0.00
32.18
16C.96
2.77
0.00
0.00
6.69
> 915.12
1278.10
62.88
0.00
125.09
795.54
>3661.30
2559.20
600.29
118. 36
0.00
6.40
33.97
> 921. 81
1.59
1.46
2.84
7.16
2.46
2.00
1.44
1.44
274.70
70.18
1.54
1.34
14.14
89.43
5410.71
1398.92
134. 20
3.72
'1.04
0.94
1.95
157.51
52.99
49.32
47.75
45.21
60.92
61.89
50.04
42. 11
35.58
9.38
41.71
60.33
36.80
4C.16
9.49
I-.99
5.79
27.84
58.15
47.04
41.85
30.27
3.25
3.00
2.71
6.42
4.56
'"" 1.98
3.07
4.12
7.27
54.64
12.30
0.00
4.06
3.85
43. 65
49.68
38.49
30.82
1.75
0.00
2.79
9.77
84.51
79. 39
75.92
75.73
97.96
"96.87
79.80
68.68
61.83
69.02
76.25
92.51
63.54
65.42
58.20
57.33
47.38
73.51
90.92
72.13
66.96
56.16
Baseline
CH
CD
-------
.EMISSION FACTORS L8S/1000-GAL FUEL
UNIT CONO
C02, QIR FLUt GAS«
PERCENT PERCENT SCF/L3 FUEL CO
C2005 R
- No. 2 oil «
R
H
H
H
H
H
H
M
H
<•)
M
M
M
L
L
L
L
C2005 R
CR R
R
H
H
H
H
H
1
M
M
M
M
M
L
L
L
, L
L
L
L
12.1
12.5
13.2
9.6
10.3
11.2
12.0
13.3
14.0
a. 2
9.5
10.7
12. 0
12,9
14.1
8.5
9.7
12.0
13.6
11.9
13.4
13.9
9.1
9.8
11.2
12.1
13.9
6.4
7.3
9.2
11.1
12,1
13.8
5.9
7,0
3.3
10.3
12.1
13.7
14.0
25.0
21.1
l^.g
54.5
45.3
34.0
25.5
14.2
7.9
BC.8
57.5
4D.4
25.5
17.0
6.8
97.3
7C .4
36.4
12.7
28.0
14.2
1C. 0
55. 3
53.7
35.4
26.2
1C. 6
136.3
105.8
52.5
35.9
2 5 . 5 -
10.4
153.3
110.1
78.4
43.6
23.8
10.0
5.2
237.7
230.1
218.2
294.3
276.7
254.9
238.6
216.9
204.9
344.8
300.1
267.2
238.6
222.4
202.8
376.4
324.7
263.4
214.0
240.9
214.8
206.9
311.5
289.6
254.9
237.6
207.9
446.2
338.3
306.4
256.0
236.2
207.6
478.3
396.5
336.4
270.6
233.0
206.8
197.8
0.37
1.30
14.23
0.00
0.00
0. 00
0.00
2.00
>129.39
j. 00
0.00
0.00
0.00
3. 00
>128.04
0,00
0. 00
0.00
>135.15
0.00
0.24
2.63
0.00
0.00
0. 00
0. 00
4.25
1.48
0.00
0.00
0.00
0.00
U.80
1.32
0.00
0.00
0.00
a. oo
0.00
69.99
HC
0.17
0.17
0 .18
0.20
0.19
0 . 17
0 .18
0 . 16
0 .45
0 . 00
o.oc
0.12
0.13
0.13
0.24
0.35
0.35
0 .33
0.27
0.07
0 . 06
0.06
—
0.18
0 . 14
0 . 08
0.10
1.41
1.23
0.97
0.81
0.75
0.66
0.96
0.86
0.80
0.73
0 .48
0.36
—
MO
17.39
16.20
14.76
19.10
18.72
17.38
16.41
14.55
13.41
20.48
20.80
20.43
19.16
16.10
15.95
25.88
27.15
25.93
15.30
35.38
32.83
31.86
38.38
37.56
35.17
33.49
29.18
38.84
39.33
37.74
33.81
31.62
27.30
35.41
39.21
40.65
4G.22
43.19
36.22
—
N02
1.00
0.39
0.74
0.50
0.47
0.43
0 .40
0.55
0.52
0.58
0.76
0.45
0.60
0.38
0 .68
0.63
0.82
0.44
0.72
0. 44
0.39
0.75
1.41
1.05
1.16
1.08
0.57
0.00
2.12
0.83
1.16
0.86
0.94
3.04
2.52
1.83
2.21
0.00
0.56
—
NOX
27.66
25.23
23.38
29.79
29.17
27.08
25.56
22.86
21.08
31.99
32.65
31.77
29.99
28.14
25. 14
40. 31
42.45
40.21
24.19
54.69
50.72
49.60
60.26
58.65
55. 09
52.43
45.31
59.56
62.42
58,70
53.00
49.34
42.80
57.33
62.64
64.16
63.89
66.23
59.17
—
S02
53.02
52.68
52.53
49. 42
50.35
50.57
50 . 43 Baseline
50 . 93
51.72
50. 20
51.10
52. 08
52.11
52. 22
55.95
57.89
57.95
58.45
57.80
161.42
165 . 67
167.39
157.54
161.09
164.33
165.21 Baseline
165.59
152.30
157.10
154.93
161.81
161 . 28
162.72
139. 07
145.35
148.86
150.51
153.17
156.89
—
e-i
H-1
o
-------
EMISSION FACTORS LBS/10QO-GAL FUEL
UNIT CONO
C02, AIR FLUE GAS»
PERCENT PERCENT SCF/LB FUEL CO
C2005 R
- No. 6 oit R
R
H
H
H
H
H
M
M
M
H
M~ "
M
L
L
L
L
L "
L
12.0
12.3
14.7
9.3
10. 3
11.1
12.1
14.7
6.1
6.9
8.2
10.3
12.1
13.2
6.1
7.6
6.9
10.5
12.3
13.3
3C.
23.
8.
57.
52.
l»2.
~~ "31.
f .
155.
122.
87.
49.
26.
19.
153.
102.
71.
4b.
29.
17.
9
3
1
if
4
0
1
6
0
9
0
7
8
1
5
2
7
8
3
8
2 it 1.6
227.5
199.5
309.0
281.2
262.1
21.2.1
200.5
470.7
411. it
345.2
276.4
237.8
219.9
467.8
373.2
317.0
271.1
238.3
217.4
1.13
1.20
8.77
1.45
0.82
0.61
"0.71
6.82
12.14
3.13
1.21
0.16
0.14
0.52
3.02
C.44
0.00
0.00
0.00
0.00
HC
™"b". is"
0.11
0.08
0.11
0.09
0.09
"0.08
0.07
0.60
0.47
0.35
0.29
0.22
0. 21
0.22
0.16
0.10
0 . 08
0.07
0.07
NO
47.18 "
44.57
39.84
51.03
48.74
47.40
44.54 "
37.01
48.47
50.63
50.29
47.20
43.15
41.01
48.76
51.79
53.34
54.12
56.97 "
56.92
N02
i.is"
0.00
0.00
0.00
1.35
0.76
1.86 "
0.58
3.63
2.77
1.99
1.86
0.92
0.64
2.70
1.80
1.22
2.09
0.92
0.63
NOX
""73.50
68.35
61.08
78.24
76.08
73.44
70.16
57.33
77.95
80.40
79.10
74.24
67.08
63.52
77.47
81.21
83. 00
85. 08
" 88.27
87.90
S02
291.
292.
299.
281.
282.
288.
'" 301.
300.
264.
270 .
268.
277.
286.
288.
269.
275.
276.
284.
288.
297.
43
76
50
64
70
09
78 Baseline
98
98
17
36
83
87
87
61
12
14
83
02
20
EMISSION FACTORS IBS/MILLION- CU FT
C2005 R~~
Gas R
R
R
H
H
H"
H
H
M
M
M
M
M
L
L
L
L
8.6
9.0
10.0
10.5
6.7
7.9
9.5
10. 0
10.3
6.3
7.1*
9.3
10.1
10.6
4.8
6.6
8.1*
10.0
33.
26.
16.
7.
59.
43.
21.
15.
6.
37.
52.
23.
13.
7.
127.
88.
33.
13.
4
9
3
1
8
6
7
6
9
4
7
3
9
1
7
4
7
6
287.7
272.8
253.3
227.7
370.6
311.0
261.1
247.0
227.2
410.7
331.5
264.6
243.2"
227.7
502.5
367.3
288.3
242.5
18.20
18.17
27.83
940. 38
27.15
20.71
18.26 ""'
55.11
933. 25
30.09
20.97
17.62
61.55
940. 26
138.88
0.00
0.30
896.45
-_
—
0.68
16.50
—
—
— .
3.77
_
«_
—
—
324.64
173.69
7.19
2.45
2.20
10.17
68.76
68.14 •
66.87
53.63
68.76
76.55
59.62 "
55.52
50.26
10E.97
83.98
61.36
""" 53.80
46,31
64.54
106.14
88.46
52,78
1.57
1.49
1.39
8.72
2.03
0.00
2.86 "
2.70
7.46
0.00
0.00
1.45
"" 2.66
4.98
24.74
4.02
0.00
7.96
107. 01
105.97
103.92
90.95
107.46
117.38
94.27
87. 83
84.53
164.02
128.76
95.53
' 85.15'
75.99
123.70
166.77
135.64
88.89
Baseline
-------
EMISSION FACTORS LBS'lOOO-GAL FUEL,
UNIT COND
C02,
iKL;:
AIR
j,sj UKT _.._._-_ . . --
FLUE GAS,
PERCENT PERCENT SCF/LB FUEL CO
C2006 R
No. 2 oil R
R
H
H
H
H
H
M
H
M
M
M
M
L
L
L
L
C2006 R
CR ^
R
R
H
H
H
H
H
M
M
M
M
M
L
L
L
13.0
12.9
13.7
10.1
11.2
11.9
13.2
14.0
8.9
9.7
10.9
11.9
13. 2
13.6
9.7
11.2
12.1
12.5
11. 7
12,1
12.9
14. a
9.9
11.1
1?. 'J
13.3
14. 3
9.7
10.9
12. a
13. a
13.6
11.6
ii.9
13.8
23.
14.
e.
1*6.
3?.
24.
12.
6.
E>4.
51 .
34.
24.
12.
8.
'+9.
30.
21.
18.
2 7 .
23.
15.
7.
48.
34.
25.
12.
7.
51.
35.
24.
14.
9.
28.
25.
9.
0
4
5
0
6
5
6
2
2
4
8
2
0
9
0
0
6
2
6
B
8
1
8
3
0
o
1
8
5
0
8
9
5
8
4
233.9
217.3
206.0
276.0
252.3
236.7
213.8
201.5
312.8
288.4
256.4
236.1
212.8
206.8
283.7
247.3
231.1
224.5
240.2
233.0
217.7
201.4
280.4
252.9
235.2
212.4
201.4
286.1
255.2
233.3
215.8
206.6
241.8
236.8
205.6
0.
0.
23.
0.
0.
0.
0.
>126.
0.
0.
Q.
0.
0.
87.
0.
0.
0.
.0*
0.
0.
0.
7.
0.
0.
c.
0.
6.
0.
0.
0.
0.
0.
0.
0.
12.
00
00
37
00
00
00
00
65
00
00
00
00
00
68
00
00
00
00
00
00
00
57
00
00
00
00
68
00
00
00
00
23
00
00
84
HC
0.14
0.18
0.20
0 . 32
0.30
0 . 33
0 . 26
0 . 32
0 . 43
Q . 41
0. 38
0.35
0 . 32
0.61
0 . 38
0.30
0.27
0. 21
0.36
0 . 35
0 . 36
0 . 34
0.51
0 .50
0 .46
0 . 42
0 .43
0.77
0.69
Q .63
0.59
0.57
0.67
0.64
0.55
NO
14.98
13.68
12.63
17.20
16.43
16. 07
14.75
13.90
ie.26
16.26
16.00
15.38
13.39
12.22
14.91
14. 08
12.40
11.55
28.87
28.7Q
27.47
25.04
31.55
3C.11
29.25
27.30
25.04
34.40
33.55
32.33
3C. 42
29.12
33.09
32.68
23.75
N02
0.20
0.00
0.35
0.00
0.00
0.00
0.00
0.17
0.00
O.OG
0.00
0.00
0 .18
0.35
0.00
0.00
0.39
0.19
0.00
0. 00
o.uo
0.00
0.00
0.00
o.oc
o.uo
0.00
0.00
0.00
0.00
0.00
0 .00
0.00
0.00
0.00
NOX
23.16
20.97
19.71
26.37
25. 20
24.64
22.61
21.48
24.94
24.93
24.54
23.58
20.72
19.09
22.86
21.59
19.40
17. 9C
" "44.27
44.01
42.12
38.40
48. 38
46. 16
44. 86
41.85
36.40
52.74
51.45
49.58
46.65
44.65
50.73
50.11
36.41
S02
24.87
25.39
25.76
23. 39
23.58
23 . 79 Baseline
23.73
26.61
24.49
24.93
24. 87
25.11
25. 36
26. 09
24, 53
25.43
25.92
25.71
~ 160.91
159.06
159.65
160 .37
152.44
156.67
154.63 Baseline
158.42
157. 83
151.91
151.63
153.38
152.81
154.11
149.81
152.70
153.37
-------
EMISSION FACTORS LBS/1000-GAL FUEL
UNIT CONO coe.
C2006 R
U No. 6 oil R
H
H
H
H
H"
M
M
M
>1
H
rt
L
L
L
PERCENT
12.2
13.7
ID. 3
11.0
12.1
12.7
13.7
6.9
8.5
9.7
11.3
11.9
13. i*
11.8
12.1
13.2
CAl/C.33
AIR
PERCENT
24.8
11.8
4B.8
36.2
26.6
ZC. 7
12.1
lie. 3
75. G
53.2
33,2
27,3
13.3
31.9
25.6
17.2
UK I
FLUE GAS,
SCF/LB FUEL CO
231.3
207.3
272.1
256.2
23(». 8
223.8
207.8
404.8
324.5
284.1
247.0
236.1
210.1
2i*i*. 6
232.9
217.1*
0.27
0.72
0.00
0. 00
0.00
0.00
0.24
5.84
0. 94
0. 00
0. 00
G.OO
0. 00
0. 00
0. 00
0.25
HC
0.29
0 . 26
0.34
0 .32
0. 33
0. 28
0.26
0.64
0 .48
0 .36
0 .31
0.30
0.26
0.39
0 .37
0 .35
NO
37.73
3^.88
4C.57
39.62
38.20
37.38
35.86
43.07
42.95
43.58
43.24
42.35
38.59
42.82
40. 34
35.91
N02
~o.ob
0.39
0.52
0.49
0 .67
0 .42
' " 0.00
5.76
1.85
Q .81
0 .00
0 .90
0.00
0.70
1.33
0.00
NOX
57.
53.
62.
61.
59.
57.
54.
71.
67.
67.
66.
65.
59.
66.
63.
55.
EMISSION FACTORS LBS/MILL ION-CU
C2006 R
Gas R
R
R
H
H
H
H
H
M
M
M
L
L
L
L
8.3
8.5
9. 1
10.-+
7.3
8.2
9.0
9.6
10.5
7.9
8. 7
9.1
6.2
7.3
8.5
9.1
35.2
32.2
23.9
8.8
52.6
36.1*
25.2
1^.9
e . 3
'41.8
29.6
2 4 . 2
30.6
53.1
31.8
23.9
291.8
284.9
265.9
231.5
331. U
294.5
268.9
21,5.6
230. tt
306.8
279.1
266.7
395.1
332.5
284.0
265.9
O.OD
0.00
0. 00
567.41
0. 00
0. 00
0. 00
0. 00
78. 26
0.00
0. 00
0.00
0.00
0.00
0.00
0.00
1. 89
1.79
1.62
1 . 46
1 .90
1.68
1.79
1 .50
1. 63
1.70
1.70
~ 1.47
0.75
1. 08
1.35
1.57
81.21
80.29
92.03
90.86
66.20
78.80
87.30
83.24
82. 21
60.21
63. 72
69.45
5C.74
52.20
57.76
57.87
0.00
0.00
0.00
2.53
0.00
0.00
0.00
0. OC
i.26
0.00
O.OQ
0.00
0.00
0.00
0.00
0.00
124.
123.
141.
141.
101.
120.
133.
127,
127.
92.
97.
" 106.
77.
80.
86.
88.
93
87
73
23
24
7b
98
80
71
63
30
84
17
35
16
05
FT
52
11
11
85
51
83
86
64
31
31
71
50
81
04
56
74
S02
204.
208.
201.
202.
204.
206.
205.
192.
197.
198.
202.
202.
208.
200.
199.
200.
66
01
24
97
62 Baseline
89
76
42
09
82
20
64
02
23
89
94
Baseline
CO
-------
PFH AT 3 PERCENT OXYGEN
UH1 |
-------
PPM «T 3 PERCENT OXYGEN
unj 1 U
C2002
No. 2 oil
C2002
No. 4 oil
UNU
R
R
R
R
R
H
H
H
H
H
H
M
M
M
M
M
I
L
L
L
L
L
R
R
R
R
R
R
H
H
H
H
H
H
M
K
M
H
M
L
L
L
L
L
1>U£«
PERCENT
10.5
11.0
12.3
13.2
13.8
8.6
9.1
10.2
11.9
12.7
12.9
8.0
1C.1
11.0
12.0
13.3
7.6
8.3
9.1*
11.0
12.1
12.7
7.8
8.7
9.9
11.2
12.1
13.5
8.2
9.1
1C. 8
11.3
12.3
12.8
8.3
9.9
10.9
12.0
13.3
5.8
8.3
10.1
11.9
13.0
CO
0.00
3.00
0.00
81.85
>1171.85
3.Ci»
2.89
1.29
<*.50
47.51*
102.18
11.65
7.83
7.19
12.11
^1223.33
1.71
0.00
0.00
0.00
0.00
12.53
6.81
1..61
1..02
2.37
1.09
601.37
0.00
O.CO
0.00
O.CC
2.16
^1229.26
1.61
O.CO
1.21
0.30
?1186. 121^4. 01
HC
<1.25
<1.19
<1.10
<1.00
9.62
<1.52
-------
UNIT COND
C2002
CR
PPM AT 3 PERCENT OXYGEN
Gas
unu
R
R
R
R
R
H
H
H
H
H
H
H
M
K
M
M
f<
L
L
L
I
I
I
R
R
R
R
H
H
H
H
K
M
M
L
L
I
I
liU£f
PERCENT
9.0
10.0
11. 0
12.1
12.6
7.6
8.7
10 .1
11.7
12.1
12.8
6.9
8.7
9.7
10.9
12.1
13.0
6.2
8,5
9.6
10 .8
11.9
13. it
7.6
6.4
9.1
9.9
7.8
fl.6
10. u
1G .3
7.1*
8.6
9.9
6.9
8.3
9.1
9.9
CO
0
0
0
a
814
0
0
0
0
0
7
1
0
0
0
0
2
10
J
JL
0
0
0
53
3
1
3
3
0
0
1
1
0
0
0
1
0
0
6
.00
.to
.GO
.00
.66
.00
.00
.00
.CD
,30
.18
.84
.00
.CO
.00
.CO
.04
.80
.62
.00
. DC
.00
.03
.98
.21
.32
.06
.00
.00
.01
.01
.00
.00
.00
.".7
.00
.CO
.1C
HC
---
—
—
—
—
_
—
—
—
—
— -
—
—
_
_
_
—
_
T-
—
«•!••
T-
~
C.8G
1.81
0.66
1.12
0.78
0.36
0.30
1.31
1.48
1.40
2.C2
2.20
1.914
1.65
1.52
NO
324.
351.
334.
309.
251.
305.
326.
318.
288.
279.
243.
283.
292.
287.
276.
265.
225.
270.
307.
283.
276.
257.
200.
106.
100.
94.
92.
77.
91.
9<«.
91.
84.
90.
89.
71.
92.
97.
89.
60
31
48
71
71
11
93
6<»
6<4
89
C3
36
60
<»7
7«»
5i»
56
01
88
05
18
88
11
18
26
18
70
0<4
66
27
99
71
77
93
98
3<4
73
-------
PPM AT 3 PERCENT OXYGEN
urn i u unu
C2003 R
No. 2 oil R
H
K
H
H
H
H
M
M
M
M
f
I
L
L
L
L
L
C2003 R
CR R
H
H
H
H
K
H
H
M
M
L
L
L
L
L
UU£«
PERCENT
13.2
14.5
1C.Q
11.3
13. 1
12.1
13.3
13.9
7.6
9.3
10 .5
11.9
13.1
6.6
7.5
9.7
12.0
12.6
13.3
12.2
12.7
9.5
10.8
12.0
13. 4
7.1*
9.0
9.9
11.9
13.6
6.2
7.2
8.6
9.3
11.8
CO
0
10
0
0
a
a
a
0
a
0
0
a
0
13
1
0
0
3
0
3
4
5
3
2
2
l>t
7
5
3
4
51
16
9
0
7
.00
.17
.00
.00
.CO
.00
.00
.CO
.CO
.00
.00
.00
,00
.57
,7k
.CO
.DO
.GO
.CO
.24
.04
.53
.65
.19
.96
.33
.40
.20
.34
.90
.78
.34
.16
.44
.68
HC
1.51
3.70
3.97
2.96
2.76
3.31
3.02
2.90
4.32
3.23
2.73
2.19
2. 01
9.69
10 .44
9.37
4.69
9.42
€.06
3.34
2.B3
1.66
1.46
1.32
1.19
1.61
1.33
1.32
1.34
0.49
0.83
1.C9
1.37
1.69
1.80
NO
84
79
84
76
77
77
71
67
76
70
67
63
58
69
71
65
58
56
55
214
214
215
237
207
194
222
219
211
200
180
196
203
199
194
168
.63
.53
.76
.91
.38
.15
.47
.74
.09
.13
.GO
.50
.19
.80
.36
.61
.71
.55
.53
.64
.36
.49
.80
.25
.54
.12
.14
.95
.51
.42
.76
.30
.91
.06
.78
N02
2.02
0.00
2.65
2.37
1.11
0.00
2.01
2.90
3.46
1.40
2.48
1.09
3.01
13.57
5.22
1.34
1.09
2.09
1.01
4.31
3.03
6.91
2.43
1.13
0.00
3.58
0.00
2.65
0.00
0.98
8.28
3.63
0.00
4.22
4.50
NO
86
79
87
79
78
77
73
70
79
71
69
64
61
83
76
66
59
58
56
218
217
222
210
208
194
225
219
214
200
181
205
206
199
198
173
X
.65
.53
.41
.28
.49
.15
.49
.64
.55
.53
.48
.59
.20
.37
.58
.95
.80
.64
.54
.96
.39
.39
.24
.35
.54
.70
.14
.59
.51
.40
.05
.93
.91
.27
.28
S02
92.
97.
92.
87.
88.
94.
88.
90.
93.
89.
89.
90.
92.
31.
90.
93.
93.
87.
92.
560.
586.
552.
563.
570.
576.
530.
547.
543.
556.
558.
488.
508.
549.
548.
562.
70
10
71
56
44
78 Baseline
59
96
38
76
33
87
29
43
50
74
51
97
88
87
44
53
87
22 Baseline
70
23
84
11
98
90
80
24
38
42
60
-------
PPM AT 3 PERCENT OXYGEN
vmj. i o imu
C2003 R
No. 6 oil R
R
R
H
H
H
H
H
H
M
M
M
M
M
M
M
M
L
L
L
L
L
L
L
C2003 R
Gas R
R
R
H
H
H
H
H
M
M
M
M
L
L
L
L
L
UU£»
PERCENT
11.5
11.8
13. a
13. 4
9.2
10.3
11.0
11.9
12.5
13.3
7.2
8.1
9.3
9.7
11.3
12.0
12,3
13.8
6.7
7.3
8.3
9.2
10.9
11.2
12.5
9.6
10.0
11.2
11.4
7.6
9.3
9.7
1C .0
11. i
7.<»
8.9
10.1
11; .7
6.5
8.3
9.2
10.0
11. i.
CO
12
11
8
10
IS
14
12
10
13
10
23
13
10
8
4
3
3
4
56
41
31
25
19
19
23
1
1
8
910
2
1
1
5
7
2
2
2
1131
7
9
7
7
271
.63
.21
.13
.97
.75
.16
.10
.11
.71
.12
.58
.01
.37
.15
.72
.35
.28
.91
.80
.45
.59
.57
.39
.83
.44
.05
.01
.18
.32
.68
.12
.01*
.05
.30
.75
.30
.01
.CO
.97
.82
.74
.10
.52
HC
1.61
1.46
1.43
2. CO
3.17
2.83
2.66
3.59
2.46
2.53
1.63
1.46
1.33
1.22
0.63
1.68
0.98
3.93
13.32
12.25
10.90
10. C8
8.48
8.52
7.78
1.27
<1.0i
<0.91
<0.89
1.61
1.35
1.24
1.C1
1.10
1.38
1.15
1.C1
22.60
<1.59
<1.23
<1.11
o.ci
3.56
NO
299
294
285
283
297
299
283
280
273
263
255
260
262
258
246
232
230
239
272
272
262
259
254
236
220
111
117
111
112
92
110
113
114
105
101
109
104
85
102
105
100
95
74
.71
.76
.42
.35
,12
.99
.23
.70
.21
.09
.80
.27
.19
.17
.5*4
.61
.1*6
.01
.26
.10
.23
.92
.48
.B<»
.54
.78
.59
.78
.79
.61
.16
.08
.24
.88
.77
.07
.63
.7i»
.00
.56
.60
.29
.76
N02
5.74
5.60
3.07
0.00
7.21
0.00
4.84
0.00
5.36
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
11.75
7.21
7.90
4.26
6.06
3.50
4.26
0.00
7.10
3.64
0.00
2.68
3.37
1.04
3.03
5.48
0.00
0.00
4.02
0.00
1.59
0.00
1.11
0.00
4.45
NOX
305.
300.
288.
283.
304.
299.
288.
280.
278.
263.
255.
260.
262.
£58.
246.
232.
230.
209.
284.
279.
270.
264.
260.
240.
224.
111.
124.
115.
112.
95.
113.
114.
117.
111.
101.
109.
108.
85.
103.
105.
101.
95.
79.
46
36
49
35
33
99
07
70
57
09
80
27
19
17
54
61
46
01
01
31
13
18
54
34
80
78
69
42
79
29
54
11
27
35
77
07
66
74
60
56
70
29
23
302
1309.
1300.
1288.
1306.
1269.
1261.
1282.
1291.
1264.
1295.
1142.
1171.
1185.
1182.
1215.
1185.
1223.
1236.
1175.
1171.
1200.
1221.
—
1283.
—
10
07
99
99
24
78
99
23 Baseline
27
21
94
22
03
14
02
42
27
39
22
29
57
48
39
Baseline
oo
-------
PPM AT 3 PERCENT OXYGEN
uwii isunu
C2004 R
No. 2 oil R
R
R
R
H
H
H
H
H
H
M
H
M
M
H
M
M
L
L
L
L
L
C2004 R
CR R
R
R
H
H
H
H
H
H
M
M
H
H
N
L
L
L
L
L
bUd t
PERCENT
11.3
11.4
12.1
12.2
14.1
9.1
11.0
12.0
12.1
13.1
14.0
7.1
8.6
10.0
10.8
12.0
12.8
114.8
6.5
7.9
9.3
10.6
11.5
10.6
11.1
12.1
12.9
10. a
10.8
12.1
13.2
15.0
7.4
8.5
9.6
10.5
12.2
i4.o
4.7
6.5
8.0
10.0
11.9
C
0
0
0
0
28
0
0
0
0
0
41
25
0
0
0
0
0
26
242
0
0
0
0
0
0
0
0
1
0
0
0
42
8
1
0
0
0
2
11.6
2
0
0
2
0
.00
.00
.00
.00
.45
.00
.00
.00
.00
.00
.66
.51
.00
.00
.00
.00
.CO
.29
.83
.00
.00
.00
.00
.00
.00
.00
.DO
.28
.00
.00
.00
.08
.26
.'47
.00
.00
.00
.e<«
.84
.04
.00
.00
.20
HC
(4.02
3.82
-------
PPM flT 3 PERCENT OXYGEN
UNI i uunu
C2004 R
No. 5 oil R
R
H
H
H
H
H
H
M
M
M
M
L
L
L
L
C2004 R
Gas *
R
R
H
H
H
H
H
M
M
M
M
M
L
L
L
L
L
L
L
L
l*U£f
PERCENT
11.3
12.0
13.8
9.1
10.0
10.8
12.0
13.0
7.5
8.7
9.5
10.7
12.3
5.9
6.9
3.6
12.0
8.5
9.1
10. i
1C .7
6.2
7.0
9. a
10.0
11.2
4.7
5 .4
6.9
10.1
10.6
2.8
3.5
4.6
5.7
7.8
9.1
9.8
11.2
CO
1
0
0
2
0
0
0
1)
19
1
0
0
0
676
30
4
2
0
3
39
196
3
0
0
8
} 11 IS
1562
76
0
152
960
.18
.00
.98
.91
.GO
.00
.CO
.00
.08
.49
.00
.00
.00
.53
.50
.58
.23
.00
.00
.35
.77
.39
.CO
.00
.18
.72
.46
.87
.00
.92
.31
HC
5.C7
4.56
3.72
5.10
4 .51
4.C6
4.15
3.42
8.33
7.15
6.87
5.96
5.24
26.88
8.01
6.42
4.68
3.39
3.12
6.C5
15.28
5.26
4 .21
3.C3
3.C7
586.43
14?. 82
3.29
2.87
30.18
190.92
>4475. 8711550 .62
3123
733
144
0
7
41
>1126
.57
.84
.70
.00
.83
.52
.89
2986.36
286.48
7.94
2.21
2.01
4.15
336.26
NO
327
325
300
319
323
327
326
319
291
299
302
310
316
226
284
299
313
60
56
54
51
69
70
57
48
40
10
47
68
44
45
10
5
6
31
66
53
47
34
.72
.73
.78
.01
.68
.64
.30
.53
.45
.42
.47
.33
. 74
.26
.112
.38
.28
.47
.85
. 48
.58
.51
.61
.10
.04
.60
.70
.59
.84
.27
.82
.83
.69
.61
.76
.35
.67
.75
.53
N02
2.36
5.56
2.94
5.83
2.65
2 .46
4.49
0.00
5.20
5.96
0.00
G.OO
5.46
17.92
9.53
4.53
3.34
2.42
2.23
2.02
4.78
3.39
1.47
2.28
3.07
5.41
40.67
9.15
0.00
3.02
2.96
32.49
36.97
28.65
22.94
1.30
0.00
2.08
7.27
NOX
330
331
303
324
326
330
330
J19
296
305
302
310
322
244
293
303
316
62
59
56
56
72
72
59
51
46
51
56
68
47
48
43
42
35
54
67
53
49
41
.08
.28
.72
.84
.33
.1C
.79
.53
.66
.37
.47
.33
.20
.18
.56
.96
.62
.88
.08
.50
.36
.90
.09
.38
.11
.Ul
.37
. 74
.84
.29
.68
.31
.66
.26
.70
.65
.67
.83
.80
S02
1315.
1311.
1322.
1267.
1286.
1293.
1300.
1317.
1231.
1266.
1278.
1303.
1321.
1209.
1258.
1298.
1337.
61
80
64
32
75
32
72 Baseline
55
73
19
64
38
59
68
10
31
83
Baseline
to
o
-------
PPM AT 3 PERCENT OXYGEN
uni i uvinu
C2005 R
NO. 2 Oil R
R
H
H
H
H
H
H
M
M
H
H
H
M
L
L
L
L
C200S R
CR R
R
H
H
H
H
H
H
H
M
M
M
M
L
L
L
L
L
L
L
bUlv
PERCEN'
12.1
12.5
13.2
9.6
10.3
11.2
12.0
13.3
li*. &
8.2
9.5
10.7
12.0
12.9
Kt.l
8.5
9.7
12.0
13.6
11.9
13.1.
13.9
9.1
9.8
11.2
12.1
13.9
6.1*
7.3
9.2
11.1
12.1
13.8
5.9
7.0
8.3
10.3
12.1
13.7
1<*.0
r co
3
11
126
3
0
0
Q
17
>11<*7
0
0
0
Q
0
>1135
0
0
3
>119B
0
1
21
Q
0
D
Q
35
12
0
0
0
0
6
ia
Q
Q
Q
0
0
582
.25
.52
.18
.00
.00
.CO
.00
.77
.dO
.CO
.00
.no
.CO
.00
.<<2
.00
.00
.CO
.52
.00
.98
.87
.00
.00
.CO
.GO
.36
.31
.00
.00
.00
• tiO
.68
.99
.00
.00
.00
.00
.00
.02
HC
2
2
2
3
2
2
2
2
7
0
0
1
1
2
3
P
5
5
<.
1
G
0
2
1
1
1
<2G
<17
<1<*
<11
<10
< 9
!«•
12
11
10
6
5
.71
.62
.78
.08
.90
.67
.82
.W
.CO
.00
.CO
.82
.96
,C2
.69
.1.8
.<*7
.01*
.19
.00
.89
.86
—
.66
.99
.C9
.1*3
.51
.85
.C8
.77
.86
.51*
.29
.76
.60
.57
.96
.23
—
NO
li»3.91
13
-------
PPM AT 3 PERCENT OXYGEN
UI14I IrlinU
C2005 R
No. 6 oil R
R
M
H
H
M
H
M
M
H
M
M
H
L
L
L
L
t
L
C2005 R
Gas *
R
R
H
H
H
H
H
M
M
M
M
H
L
L
t
L
UUC t
PERCENT
12.0
12.8
lit. 7
9.3
10.3
11.1
12.1
li*. 7
6.1
6.9
8.2
10.3
12.1
13.2
6.1
7.6
8.9
10 .5
12.3
13.3
8.6
9.0
10.0
10.5
6.7
7.9
9.5
10.0
1" .8
6.0
7.1*
9.3
10.1
10.6
l*.8
6.6
e.<*
10.0
CO
9.C5
9.58
70.03
11.57
6.58
i*.91
5. 67
5i» .1.2
96.93
25. C3
9.69
1.29
1.11
i*.12
2<*.C6
3.1.9
G.OO
0.00
O.DO
0.00
22.25
22.21
31*. C2
111*9.60
33.19
25.32
22.32
67.37
11«»7.QO
36.78
25.6««
21.51*
75.21*
11^9. 1*5
169,78
0.00
0.00
1095.89
HC
2
1
1
1
1
1
1
0
6
6
i*
<«
3
2
3
2
1
1
1
0
;
35
a
693
370
15
5
l«
21
.<*9
.60
.12
.59
.32
.23
.13
.9
-------
PPM AT 3 PERCENT OXYGEN
uni i u '
C2006
No. 2 oil
C2006
CR
unu
R
R
R
H
H
H
H
H
H
H
M
H
M
M
L
L
L
L
R
R
R
R
H
H
H
H
H
H
M
M
H
H
L
L
L
UU£«
PERCENT
12.Q
12.9
13.7
10.1
11.2
11.9
13.2
11*. 0
8.9
9.7
10.9
11.9
13.2
13.6
9.7
11.2
12.1
12.5
11.7
12.1
12.9
lit. 0
9.9
11.1
12. Q
13.3
li«. 0
9.7
10 .9
12.0
13.0
13.6
11.6
11.9
13.8
r cc
0.00
0.00
208.20
0.00
0.30
0.00
0.00
^1128.1.5
0.00
O.CO
0.00
0.00
o.no
781.21
0.00
0.00
O.GO
O.CO
O.GO
O.GO
0.00
62.°
-------
J-2b
BIBLIOGRAPHIC DATA
SHEET
'• ReP°« N°-
EPA-R2-73-084b
3. Recipient's Accession No.
4. Title and Subtitle
Field Investigation of Emissions from Combustion
Equipment for Space Heating (Data Supplement)
5. Report Date
June 197.3
6.
7. Author(s)
R.E.Barrett, S.E. Miller, and D.W.Locklin
8- Performing Organization Kept.
No.
9. Performing Organization Name and Address
Battelle - Columbus Laboratories
505 King Avenue
Columbus , Ohio 43201
10. Project/Task/Work Unit No.
11. Contract /Grant No.
68-02-0251
12. Sponsoring Organization Name and Address
EPA, Office of Research and Development
NERC-RTP, Control Systems Laboratory
Research Triangle Park, North Carolina 27711
13. Type of Report & Period
Covered
Final
14.
IS. Supplementary Notes
16. Abstracts -phfe "Data Supplement" volume records individual data points and plots in
greater detail than is practical in the main volume of the report. It is intended for
use by researchers who wish to refer to individual data points. Data is included
from the 13 residential units and 6 commercial boilers investigated in Phase n of the
program under different combustion conditions. This volume contains the emissions
data, plots of emissions versus CO2, computed emission factors, and
emission concentrations calculated at 3% O2. Additional details , including
descriptions of individual units and sampling and measurement procedures, are
contained in the main body of the report.
17. Key Words and Document Analysis
Air Pollution
Space Heating
Residential Buildings
Commercial Buildings
Combustion
Emission
Burners
Boilers
Furnaces
17b. Identifiers/Open-Ended Terms
Air Pollution Control
Stationary Sources
Emission Factors
No. 2 Oil
No. 4 Oil
17a. Pcscriptors
Nitrogen Oxides Sulfur Trioxide
Nitrogen Oxide (NO) Natural Gas
Nitrogen Dioxide Fuel Oil
Particulate Composites
Smoke
Carbon Monoxide
Hydrocarbons
Sulfur Oxides
Sulfur Dioxide
No. 5 Oil
No. 6 Oil
17e. COSATI Field/Group 13B , 7C
IB. Availability Statement
Unlimited
19. Security Class (This
Report)
UNCLASSIFIED
20. Security Class (This
Page
UNCLASSIFIED
21. No. of Pages
225
22. Price
FORM NT1S-35 (REV. 3-721
USCOMM-OC MOS2-P72
------- |