June 1974
EPA-65Q/2-74-066
Environmental  Protection  Technology  Series

-------
                                            EPA-650/2-74-066
                     FIELD TESTING:
APPLICATION OF  COMBUSTION MODIFICATIONS
           TO  CONTROL NOX  EMISSIONS
               FROM  UTILITY BOILERS
                             by
              A. R. Crawford, E. H. Manny, andW. Bartok

               Exxon Research and Engineering Company
                  Government Research Laboratory
                         P. O. Box 8
                    Linden, New Jersey 07036
                     Contract No. 68-02-0227
                      ROAP No. 21ADG-AL
                    Program Element No. 1AB014
                 EPA Project Officer: Robert E. Hall

                    Control Systems Laboratory
                National Environmental Research Center
              Research Triangle Park, North Carolina 27711
                         Prepared for

               OFFICE OF RESEARCH AND DEVELOPMENT
              U.S. ENVIRONMENTAL PROTECTION AGENCY
                    WASHINGTON, D.C. 20460

                          June 1974

-------
This report has been reviewed by the Environmental Protection Agency
and approved for publication.  Approval  does not signify that the
contents necessarily reflect the views  and policies of the Agency,
nor does mention of trade names or commercial products constitute
endorsement or recommendation for use.
                                  11

-------
                                    -  ill  -
                               TABLE OF CONTENTS

                                                                      Page

    ACKNOWLEDGMENTS .................................................  xii

    SUMMARY [[[  xiii

1.  INTRODUCTION [[[    1

2 .  OVERALL CORRELATIONS AND CONCLUSIONS ............................    4

    2.1  NOX Emissions for Coal Fired Boilers .......................    5

    2.2  Particulate Mass Loading ...................................   16

    2 . 3  Furnace Corrosion Tes ting ..................................   17

    2.4  Effects of Combustion Modifications
         on Boiler Performance ......................................   19

    2.5  NOX Emissions for Boilers Converted
         from Coal to Oil Firing ....................................   19

3.  EFFECT OF ELECTROSTATIC
    PRECIPITATORS ON NOX FORMATION ..................................   24

4.  FIELD STUDY PLANNING AND PROCEDURES .............................   26

    4.1  Program Design .............................................   26

         4.1.1  Boiler Selection Criteria ...........................   26
         4.1.2  EPA/Exxon/Boiler Operators/
                Boiler Manufacturers Cooperation ....................   28
         4.1.3  Test Program Strategy ...............................   28

    4.2  Test Procedures ............................................   31

         4.2.1  Gaseous Sampling and Analysis .......................   31
         4.2.2  Particulate Sampling ................................   36
         4.2.3  Furnace Corrosion Rate Measurements .................   38

5.  COMBUSTION VARIABLES ............................................   43

    5.1  Load Reduction .............................................   43

    5 . 2  Low-Excess Air Firing ......................................   43

    5.3  Staged Combustion . . .................................. ......   44

    5.4  Flue Gas Recirculation .......... ......... . .................   45

    5 . 5  Burner Tilt ................................................   45


-------
                                      - XV -
                          TABLE OF CONTENTS  (Cont'd)

                                                                     Page

6.   FIELD TEST RESULTS 	    48

    6.1  Coal Fired Boilers  	    48

         6.1.1  Gaseous Emission Results  for
                Individual Coal Fired Boilers  	    48

                6.1.1.1  Gaseous Emissions  from
                         Front Wall Fired Boilers  	    48

                         6.1.1.1.1  Widows  Creek,  Boiler No. 6  	    50
                         6.1.1.1.2  Dave  Johnston, Boiler No. 2  ....    54
                         6.1.1.1.3  E.  D. Edwards, Boiler No. 2  ....    61
                         6.1.1.1.4  Crist Station, Boiler No. 6  ....    69

                6.1.1.2  Gaseous Emissions  from Horizontally
                         Opposed Coal Fired Boilers 	    72

                         6.1.1.2.1  Harllee Branch, Boiler No.  3  ...    72
                         6.1.1.2.2  Leland  Olds,  Boiler No. 1 	   75
                         6.1.1.2.3  Four  Corners,  Boiler No. 4  	   78

                6.1.1.3  Gaseous Emissions  from
                         Tangentially Fired Boilers 	   82

                         6.1.1.3.1  Barry,  Boiler  No.  3 	   82
                         6.1.1.3.2  Naughton,  Boiler No. 3 	   83
                         6.1.1.3.3  Barry,  Boiler  No.  4 	   91
                         6.1.1.3.4  Dave  Johnston, Boiler No. 4  	   95

                6.1.1.4  Gaseous Emissions  from
                         Turbo-Furnace  Boilers 	   96

                         6.1.1.4.1  Big Bend,  Boiler No. 2	   96

         6.1.2  Particulate  Emission Results 	 103

         6.1.3  Accelerated  Corrosion Probing  Results  	 105

         6.1.4  Boiler Performance Results  	 109

    6.2   Oil Fired Boilers Converted from Coal to  Oil  Firing	 113

         6.2.1  Front-Wall Fired Boilers  	 113

                6.2.1.1  Deepwater,  Boiler No.  3 	 113
                6.2.1.2  Deepwater,  Boiler No.  5 	 119
                6.2.1.3  Deepwater,  Boiler No.  8 	 121
                6.2.1.4  Deepwater,  Boiler No.  9 	 129

-------
                          TABLE OF CONTENTS (Cont'd)

                                                                      Page

         6.2.2  Cyclone Fired Boilers	 136

                6.2.2.1  B. L. England, Boiler No. 1	 136
                6.2.2.2  B. L. England, Boiler No. 2 	 138

7.  RECOMMENDATIONS FOR FURTHER FIELD TESTING 	 146

    7.1  Utility Boiler Testing 	 146

8.  REFERENCES 	 150

APPENDIX A - Operating and Gaseous Emission Data Summaries	 A-l

APPENDIX B - Coal Analyses 	 B-l

APPENDIX C - Cross Section Drawings of Typical Utility Boilers 	 C-l

APPENDIX D - Comments from Boiler Manufacturers	 D-l

APPENDIX E - Conversion Factors 	 E-l

-------
                                  -  vi  -


                             LIST OF FIGURES

No.                                                                        Page

2-1   PPM NO  vs  7o Stoichiometric Air Normal Firing  	   11
            X

2-2   Uncontrolled NO  Emissions vs  Gross  Load Per
      Furnace Firing Wall  	   13

2-3   Effect of Excess  Air on NO  Emissions
      Under Normal Operation 	   14

2-4   Effect of Excess  Air on NO  Emissions
      Under Mod if ied F iring Condit ions  	   15


4-1   Exxon Research Transportable Sampling and
      Analyt ica1  System	   32

4-2   NOX  Regression -  Beckman NO + NOo vs
      Chemiluminescence NOX Measurements  	   35

4-3   Relationship Between % C02 and %  02  Flue
      Gas  Measurements  (Widows Creek, Boiler No.  6)  	   37

4-4   Corrosion Probe Detail of 2-1/2"  IPS Extension
      Pipe and End Plate (Outside of Furnace)  	   41

4-5   Corrosion Probe Detail of Corrosion  Coupon
      As sembly (Ins ide  of  Furna ce) 	   42


6-1   PPM NOX (37. 02,  Dry)  vs % Stoichiometric Air
      To Active Burners (Widows Creek,  Boiler  No. 6)  	   51

6-2   PPM  NOX (37o 02, Dry)  vs Overall Stoichiometric Air
      (Widows  Creek,  Boiler No. 6) 	   52

6-3   PPM  NOX (3% 02, Dry)  vs 7» Stoichiometric Air
      to Active Burners for S^ and S^ Runs 	   56

6-4  PPM NOX  (3% 02, Dry) vs 7, Stoichiometric Air to
     Active Burners (Dave Johnston, Boiler No. 2)	  57

6-5  PPM NO  (37o  02, Dry)  vs Adjusted Average 7.
     Stoichiometric Air to Active Burners (Dave Johnston, Boiler No. 2)  ..  62

6-6  PPM NOX (3% 02, Dry) vs J0 Stoichiometric Air to
     Active Burners (E. D. Edwards, Boiler No. 2) 	  65

6-7  PPM NOX (37» 02, Dry) vs 7, Oxygen in Flue Gas
      (Run 9A, E.D. Edwards, Boiler No.  2)  	  67

-------
                                 - vii -



                       LIST OF FIGURES (Cont'd)

No.                                                                Page

6-8  PPM NOX vs % Oxygen in Flue Gas  (Run 7A,
     E. D. Edwards, Boiler No. 2) 	   68

6-9  PPM NOX (37, 02, Dry) vs % Stoichiometric
     Air to Active Burners (Crist,  Boiler No. 6)  	   70

6-10 Harllee Branch, Boiler No. 3 Pulverizer
     and Coal Pipe Layout 	   73

6-11 PPM NOX (3% 02, Dry) vs % Stoichiometric
     Air to Active Burners (Harllee Branch, Boiler No.  3)  	   74

6-12 PPM NOX (3% 02, Dry) vs % Stoichiometric
     Air to Active Burners (Leland Olds,  Boiler No. 1)  	   77

6-13 Four Corners Station, Boiler No. 4
     Pulverizer-Burner Configuration 	   79

6-14 PPM NOX (3% 02, Dry) vs % Stoichiometric
     Air to Active Burners (Four Corners, Boiler No. 4) 	   81

6-15 PPM N0x (3% 02, Dry) vs 7, Stoichiometric
     Air to Active Burners (Barry,  Boiler No. 3)	   85

6-16 Effect of Mill Fineness and Burner Tilt on NOX
     Emissions for Low Excess Air Staged Firing
     (Naughton, Boiler No. 3)  	   88

6-17 PPM N0x (3% 02, Dry) vs % Stoichiometric
     Air toXActive Burners (Naughton, Boiler No.  3)	,   90

6-18 % Oxygen Measured in Flue Gas Before
     and After Air Preheater (Barry,  Boiler No. 4) 	,	   93

6-19 PPM N0x (3% 02, Dry) vs % Stoichiometric
     Air to Active Burners (Barry,  Boiler No. 4)	   94

6-20 PPM NOX (3% 02, Dry) vs % Stoichiometric
     Air to Active Burners (Dave Johnston, Boiler No. 4)  ,	   98

6-21 PPM NOX (3% 02, Dry) vs % Stoichiometric
     Air to Active Burners (Big Bend, Boiler No.  2) 	  101

6-22 PPM NOX Emissions vs Probe Location (Big Bend,
     Boiler No. 2) 	  102

6-23 Furnace Corrosion Probe Locations	  106

6-24 PPM NOX vs % 02 Measured in Flue Gas  (Deepwater,
     Boiler No. 3) 	  116

6-25 PPM NOX vs % 02 in Flue Gas (Deepwater, Boiler No. 8)  	  122

-------
                                 - viii -



                         LIST OF  FIGURES (Cont'd)



No.                                                                         Page



6-26  PPM NO  vs 7, Oo in Flue Gas (Deepwater, Boiler No. 8)  	  123
            X


6-27  PPM NO  vs 7e, D£ Measured in Flue Gas (B. L. England,

      BoilerXNo. 9)  	  133



6-28  PPM NOx vs % Q£ Measured in Flue Gas (B. L. England,

      Boiler No. 1)  	  140

-------
                                  - ix -



                            LIST OF TABLES

No.                                                                Page

2-1  Summary of Coal Fired Boilers Tested	    6

2-2  Summary of NOX Emissions for Front Wall Fired Boilers ......    7

2-3  Summary of NOX Emissions for Opposed Wall Fired Boilers ....    8

2-4  Summary of NOX Emissions for Tangentially Fired Boilers ....    9

2-5  Atlantic City Electric Company
     Summary of Coal-to-Oil Converted Boilers Tested 	   21

2-6  Atlantic City Electric Company
     Summary of NOX Emissions for Coal-to-Oil Converted Boilers..   22
 3-1  NOX Emission Measurements Tests Across the Electrostatic
     Precipitator—Alabama Power Company,Barry, Boiler No. 4 ....   25
4-1   Test Program Experimental Design — Widows Creek, No. 6 ......   30

4-2   Continuous Analytical Instruments in Exxon Van .............   34

4-3   Summary  of Corrosion Probing Tests  ................... . .....   40


6-1   Summary  of Coal Fired Boilers  Tested ........ ......... ......   49

6-3   Calculation  of Expected  NOX Emissions  from
      % Stoichiometric  Air to  Active Burners .....................   55

6-4   Calculation  of Expected  NOX Emissions  from Average
      "Effective"  % Stoichiometric Air  to Active Burners  .........   55

 6-5   Experimental Design with %  02  and PPM  NOX  (3% 02, Dry)
      (Dave  Johnston, Boiler No.  2)  ..............................   58

 6-6   Summary  of Low Excess Air,  Staged Test Runs  ................   60

6-7   Experimental Design with PPM NOX  (3% 02,  Dry) and % Oo
      (E.  D. Edwards, Boiler No.  2)  ..............................   63

6-8   Test Program Experimental Design   (Crist, Boiler No.  6) .....   71

6-9   Experimental Design with Run No., % 0, and PPM NOX
      (Le land  Olds, Boiler No. 1)  ......... T ......................   76
 6-10  Experimental Design - % Oxygen  and  PPM N0   (3% 02, Dry)
      (Four Corners, Boiler No. 4)
                                              x
                                                                    80
6-11 Test Program Experimental Design  (Barry, Boiler No. 3) .....   84

6-12 Test Program Experimental Design  (Naughton, Boiler No. 3) ^   87

6-13 Pulverizer Screen Analyses (Naughton, Boiler No. 3) .........   89

-------
                                  -  x -
                         LIST OF TABLES (Cent M)

No,

6-14  Test Program Experimental Design (Barry,  Boiler  No.  4)  .............  92

6-15  Experimental Design with 7. 0,  and PPM NOX (3% 02,  Dry)
      (Dave Johnston,  Boiler No. 4)  ......................................  97

6-16  Experimental Design with % 02  and PPM N0x (3% 02,  Dry)
      (Big Bend,  Boiler No .  2)  ........................................... 100

6-17  Particulate Emission Test Results .................................. 104

6-18  Accelerated Corrosion  Rate Data  .................................... 107

6-19  ASME Test Form For Abbreviated Efficiency Test ..................... 110

6-20  ASME Test Form For Abbreviated Efficiency Test ..................... Ill

6-21  Summary of  Boiler Performance  Calculations ......................... 112

6-22  Summary of  Operating and Emission Data (Deepwater, Boiler No. 3)  ... 114

6-23  Experimental Design and Average  Emission  Measurements
      (Deepwater, Boiler No . 3)
6-24  Flue Gas Emission Measurements  and Temperatures (Deepwater,
      Boiler No.  3)  ............................. ........................ H8

6-25  Summary of  Operating and Emission Data
      (Deepwater,  Boiler No.  5)  .......................................... 12°

6-26  Flue Gas Emission Measurements  and Temperatures
      (Deepwater,  Boiler No .  5)  .......................................... 124

6-27  Summary of  Operating and Emission Data (Deepwater, Boiler No. 8)  .... 125

6-28  Experimental Design and Average Emission Measurements
      (Deepwater,  Boiler No.  8)  .......................................... I26

6-29  Firing Patterns Used During NOX Testing
      (Deepwater,  Boiler No.  8 )   ......................... • .............. 127

6-30  Flue Gas Emission Measurements  and Temperatures
      (Deepwater,  Boiler No.  8)  .......................................... I30

6-31  Summary of  Operating and Emission Data (Deepwater, Boiler No. 8)  ---- 131

6-32  Experimental Design and Average Emission Measurements
      (Deepwater, Boiler No .9) ...........................................
6-33  Flue Gas Emission Measurements and Temperatures
      (Deepwater, Boiler No. 9)

-------
                                  - xi -
                        LIST OF TABLES (Cont'd)

No.

6-34  Summary of Operating and Emission Data (B.  L. England,
      Boiler No. 1) 	   137

6-35  Experimental Design and Average Emission Measurements
      (B. L. England, Boiler No. 1 )  	   139

6-36  Flue Gas Measurements and Temperatures (B.  L. England,
      Boiler No. 1)  	   141

6-37  Summary of Operating and Emission Data (B.  L. England,
      Boiler No. 2)  	   143

6-38  Experimental Design and Average Emission Measurements
      (B. L. England, Boiler No. 2)  	   144

6-39  Flue Gas Measurements and Temperatures (B.  L. England,
      Boiler No. 2)  	   145
7-1   Number and Type of Utility Boilers to be
      Tested in Future Field Test Programs 	   146

-------
                                  - xii -
                             ACKNOWLEDGMENTS
           The authors wish to acknowledge  the  constructive participation
 of  Mr.  R.  E.  Hall,  EPA  Project Officer,  in planning the field test
 programs and  providing  coordination with boiler operators and manufacturers,
 The helpful cooperation,  participation and advice of the major U.S.
 utility boiler manufacturers, Babcock and  Wilcox, Combustion Engineering
 Inc.,  Foster  Wheeler Corp. and Riley-Stoker Corp. were essential  to
 selecting representative  boilers for  field testing and conducting the
 program.  The voluntary participation of electric utility boiler  operators
 in  making  their boilers available is  gratefully acknowledged.  These
 boiler  operators  included the Alabama Power Company, Arizona Public
 Service  Company, Atlantic  City Electric  Company, Basin Electric Power
 Cooperative,  Central Illinois Power and  Light  Company, Georgia Power
 Company, Gulf Power Company,  Pacific  Power and Light Company, Tampa
 Electric Company, the Tennessee Valley Authority, and Utah Power  and
 Light Company.  Special thanks are  due to  Combustion Engineering  for
 supplying  their basic corrosion probe design which was adapted to
 furnace  corrosion probing  tests in  this  study.  The authors also
 express  their appreciation for the  extensive coal analyses services
 provided by Exxon Research's  Coal Analysis Laboratory at Baytown, Texas
 and  to Messrs. A. A. Ubbens and E.  C.  Winegartner for their contributions
 and  advice on coal related matters.   The invaluable assistance of
Messrs.  L. W.  Blanken, R.  Campbell, R. W.  Kochanczyk, R. W. Schroeder,
 and A. J. Smith, and Mrs.  M.  V.  Thompson in these field studies is also
 acknowledged.

-------
                                 - xiii -
                                 SUMMARY


           Exxon Research  and Engineering  Company has been  conducting
 field studies  on  utility  boilers under EPA  sponsorship  to  develop NO
 and  other  pollutant  control technology through  the modification of
 combustion operating conditions.  Under the present contract on this
 problem, Exxon's  mobile sampling-analytical system has  been used to test
 12 pulverized  coal-fired  boilers of cooperating electric utilities.
 These boilers, including  wall, tangentially, and turbo-furnace fired
 units, had been recommended by the utility  boiler manufacturers as
 being representative of their current design practices. Also, combustion
 modifications  for NOX control were tested for six oil-fired boilers
 which had  been converted  from coal firing service.

           In addition to  gaseous emission measurements, particulate emis-
 sions and  accelerated furnace corrosion rates also have been determined
 in a number of cases  for  coal-fired boilers.  The test  design used con-
 sisted of  three phases.   First, statistically designed  short-term runs
 were made,  to  define  the  optimum "low NOX"  conditions within the con-
 straints imposed  by boiler operability and  safety, slagging, unburned
 combustible emissions and other undesirable side effects.  Second, the
 boilers were usually  operated for about two days under  the "low NOX"
 conditions defined in the first phase, to check operability on a sus-
 tained basis.  Third, several boilers were  operated under both baseline
 and  "low NOx"  conditions  for about 300 hours, with carbon steel corrosion
 coupons mounted on air-cooled probes exposed near the water walls of the
 furnaces,  to obtain  relative corrosion tendencies at accelerated rates.

           Analysis of the gaseous emission  data obtained shows that com-
 bustion operating modifications, chiefly  low excess air firing coupled
 with staged burner patterns, can reduce NOX emissions from the coal fired
 boilers tested by 25  to 60%, depending on the unit and  its flexibility
 for  modifications.  The NOX emissions measured have been successfully
 correlated for both normal and modified firing conditions with the per-
 cent stoichiometric air supplied to the burners.

           For  dry particulate mass loadings, the differences observed
 under baseline and "low NOX" operating conditions have been found to be
 relatively minor.  However, unburned carbon in the fly-ash seems to
 increase for "low NOX" firing in front wall and horizontally opposed
 fired boilers, and to decrease for tangentially fired units.   The potential
 debits in  overall performance based on these limited data for front wall
and horizontally opposed fired boilers have been shown to be offset by
improved efficiencies realized through lower excess air operation in "low
NOX" firing.

          Boiler efficiency calculations  comparing  baseline and modified
"low NOX"  operations  indicate  essentially  no efficiency  penalty for  the
implementation of combustion modifications to  control NOX emissions.

-------
                                 - xiv -
          Significantly, the accelerated corrosion tests have not
revealed major differences in corrosion rates measured under normal and
staged firing operating conditions.  More tests and long term runs, with
particular emphasis on corrosion and slagging problems, are needed to
demonstrate the promising leads uncovered in this study.

-------
                                  - 1 -
                           1.  INTRODUCTION
          In continuing studies sponsored by EPA, Exxon Research and
Engineering Company  (Exxon) is involved in the development of nitrogen
oxides  (NOX) emission control techniques for stationary sources.  Our
"Systems Study of Nitrogen Oxide Control Methods for Stationary Sources"
(1-3) characterized  the nature and magnitude of the stationary NOX
emission problem, assessed existing and potential control technology
based on technical feasibility and cost-effectiveness, developed a first-
generation model of NOX formation in combustion processes, and prepared
a set of comprehensive 5-year R&D plan recommendations for the Government
with priority rankings.

          Fossil fuel fired electric utility boilers were identified by the
above study as the largest single stationary NOX emission sector, responsible
for about 40% of all stationary NOX.  Consequently,  as part of Phase II of our
"Systems Study of Nitrogen Oxide Control Methods for Stationary Sources",
Exxon conducted a systematic field study of NOX control methods for
utility boilers (4-6).  The objectives of this field study were to determine
new or improved NOX  emission factors according to fossil fuel type and
boiler design type,  and to explore the application of combustion modifica-
tion techniques to control NOX emissions from such installations.

          Exxon provided a specially designed mobile sampling-analytical
van for the above field testing.  This van was equipped with gas sample,
thermocouple, and velocity probes, with associated sample treating equip-
ment, and continuous monitoring instrumentation for measuring NO, N02, CO,
^<")2' ^2' ^?» anc^ hydrocarbons.

          Gas, oil,  and coal fired utility boilers representative of the
U.S. boiler population were tested.  Combustion modifications were
implemented in cooperation with utility owner-operators (and with major
boiler manufacturer  subcontractors for three of the coal fired boilers
tested), and emission data were obtained in a statistically designed
field program.  The  17 boilers (25 boiler-fuel combinations) tested
included wall-fired, tangentially-fired, cyclone-fired, and vertically-
fired units ranging in size between 66 and 820 MW generating capacity.

          Major combustion operating parameters investigated consisted of
the variation of gross boiler load, excess air level,  staged firing patterns
flue gas recirculation, burner tilt, primary/secondary air ratio, and air
preheat temperature.  Operation under reduced load conditions reduced the NO
emissions, but only  for gas firing was the percent NOX reduction greater than
the percent load reduction.  Base-line emissions were correlated in a
statistically significant manner with the MW generated per "equivalent" furnace
firing wall.  In general, unburned combustible emissions, i.e.  CO and
hydrocarbons were found to be negligibly small under base-line conditions
and acceptably iow even with NOX control combustion modifications.  The NO-
portion of the flue gas was always five percent or less of the total NO  emitted

-------
                                  - 2 -
           The effectiveness of combustion modifications  was  found to  vary
 with individual boiler characteristics for each fuel.  For gas fired
 boilers, NOX emissions could be reduced on the average by about 60% at
 full load, even though in large, gas fired boilers  limited by heat transfer
 surface, NOX emission levels as high as 1000 ppm prevailed in the absence
 of combustion modifications.  Uncontrolled emissions  from fuel-oil fired
 boilers averaged lower values than for gas firing,  but combustion modifica-
 tions could be less readily implemented.  With coal firing,  only two  of
 the seven boilers tested (one a tangential unit, the  other a front wall
 fired boiler) could be operated in a manner conducive to reducing NOx
 emissions.  This operation consisted of firing the  operating burners  in
 the lower burner rows or levels with substoichiometric quantities of  air,
 and supplying the additional air required for the burn-out of combustibles
 (keeping overall excess air as low as possible) through  the air registers
 of the uppermost row or level.  In these short-term,  exploratory tests,
 NOX emissions were reduced by over 50% compared with  the standard firing
 mode.  In one set of boiler tests, this was demonstrated to be possible
 without decreasing thermal efficiency or increasing the  amount of unburned
 carbon in the fly-ash.  Due to stopping the pulverizer mill supplying coal
 to the top level of burners, the amount of fuel that  could be fired was
 reduced, resulting in a decrease of about 15% from  maximum rated capacity.
 The NOX reductions achieved were not affected by this reduction in load,
 as normal and modified combustion operations were compared at the same
 boiler load.

           While the exploratory data obtained in the  above study on con-
 trolling NOx and other pollutant emissions from utility  boilers by com-
 bustion modifications showed good potential, a number of critical questions
 had remained to be answered.   Thus,  for  coal fired  utility boilers, potential
 problems of slagging,  corrosion,  flame  instability  and impingement,
 increased carbon in the fly-ash,  the  actual  particulate  loadings  and
 potential decreases in boiler  efficiency which could  result  from  the
 modified combustion operations  still  needed  to be assessed in sustained
 test runs.

           The purpose of Exxon's  present  field testing program, sponsored
 by EPA under Contract No.  68-02-0227, has  been to obtain more detailed
 information primarily on the application of  combustion modification
 technqiues to coal fired utility  boilers,  in cooperative efforts  with
 boiler operators and manufacturers coordinated by EPA.  U.S.  utility
 boiler manufacturers (Babcock and Wilcox,  Combustion Engineering,  Foster
 Wheeler,  and Riley-Stoker)  have recommended  boilers characteristic of
 their current design practices.   They have provided their help in making
 arrangements for testing with  the cooperating  boiler owner/operators,
 and  in a  number  of cases assigned representatives to participate  in
Exxon's field tests.

-------
                                 - 3 -
          In addition to the continuous monitoring instrumentation
described above, four EPA-type particulate sampling trains have been
added to Exxon's system.  These trains and other equipment have been
transported to the testing sites in an auxiliary van.

          The approach used for field testing coal-fired boilers in
this study has been first, to define the optimum operating conditions
for NOX emission control without apparent unfavorable side effects,
in short-term, statistically design test programs.  Second, the boiler
was operated for 1-3 days under the "low NOX" conditions determined during
the optimization phase, for assessing boiler operability problems.  Finally,
where possible, sustained 300-hour runs were made under both baseline
and modified combustion ("low NOX") operating conditions.  During this
period, air-cooled carbon steel coupons mounted on corrosion probes were
exposed in the vicinity of furnace water tubes, to determine through
accelerated corrosion tests whether operating the boiler under the reducing
conditions associated with staged firing results in increased fire-side
water tube corrosion rates.  Particulate samples were obtained under both
baseline and "low NOX" conditions, and engineering information on boiler
operability, e.g., on slagging problems, and on boiler performance were
also obtained.  For the coal-to-oil converted boilers tested, gaseous
emission measurements were made in the same manner as for the coal-fired
units.

-------
                                 - 4 -
                   2.   OVERALL CORRELATIONS  AND CONCLUSIONS

           This section of the report presents the  overall correlations  and
 conclusions based on the results obtained  in a field program  conducted  on
 twelve representative coal-fired utility boilers.  Also, our  conclusions
 on the results of six boilers converted from coal  to oil service  are  pre-
 sented.  Because of the emphasis in this study on  the  control of  NOX
 emissions by combustion modifications, the  gaseous emission measurements
 obtained without adverse side-effects during short-term optimization  runs
 are analyzed in depth in the section that  follows.

           Baseline NOX emissions from the  boilers  tested under normal
 operating conditions, usually at full rated boiler capacity,  have been
 successfully correlated with excess air (or percent  stoichiometric air
to the  active burners) and boiler load.  Also,  the percent  reduction from
baseline  levels  in NOX emissions resulting from the application of staged
firing  has been  correlated with  the percent stoichiometric  air supplied
to the  active burners.

          Particulate measurements have been made under both baseline and
modified  combustion ("low NOx") conditions  for  several  of the  boilers tested.
The objective was to assess the  relative changes  in total  flue gas particu-
late loadings and in the unburned carbon content  of the flyash that may be
due to  the application of combustion modification techniques,  chiefly
staged  firing of burners with low overall levels  of excess  air.  No major
differences  in particulate loadings have been  found,  but the unburned carbon
content of flyash appears to be  somewhat affected by  combustion modifica-
tions.

          In a similar manner, the potential of increased furnace water-
tube corrosion rates resulting from reducing conditions created by sub-
stoichiometric air  supply to  the burners has been explored.   For this
purpose,  accelerated corrosion tests have been made under both baseline
and modified combustion  conditions for  300-hour sustained periods.  The
objective of these  corrosion  probing studies was to establish whether the
application  of staged  firing with low overall excess air supply could cause
severe  corrosion problems in  the furnace.   As will be discussed further,
comparison of  the corrosion rates measured  under baseline and modified
firing  conditions indicates that the reducing environment in  the  furnace
does not  appear  to  cause severe  corrosion problems.

          The  overall  correlations and  conclusions discussed  in this  section
will be followed by subsequent sections  of  this report containing our re-
commendations  for boiler operators and  manufacturers on NOX   emission con-
trol, details  of the  field tests, results on each individual boiler tested,
and recommendations on future emission  field studies.

-------
                                 - 5 -
2.1 NO  Emissions for Coal Fired Boilers
    —x—	
          In this section the results obtained for all coal-fired boilers
tested will be analyzed.   Individual boiler test data are summarized in
Section 6 of this report  and further details on gaseous emissions are presen-
ted in Appendix A.  Typical boiler cross-sectional diagrams for wall,
tangential, and turbo-furnace fired boilers are shown in Appendix C.

           The design and  operating  features of  the  twelve  coal-fired
boilers  tested are  summarized in Table  2-1, listed  in the  sequence  of  the
individual tests.   Of  the twelve boilers,  seven were wall  fired units
 (four front wall  and three  horizontally opposed fired units,  ranging in
size  from 100 MW  to 800 MW), four were  tangentially fired,  ranging  in  size
from  250 MW to 350  MW) and  one  was  a  turbo-furnace  boiler  (with maximum
rated design capacity  of  450 MW, but  tested only  at 370  MW) .   These
boilers  are representative  of current design practices,  and have been
selected for field  studies  at the recommendation  of their  respective
manufacturers as  discussed  in Section 4.1.

          Tables 2-2, 2-3, and 2^-4 summarize the NOX emission levels
measured  from single wall-fired, horizontally opposed wall-fired, and
tangentially-fired  (plus  a  turbo-furnace) boilers, respectively.  "Low
NOx"  operation at essentially full load reduced NOX emission reductions
of 55  to  64% compared  to  full load, baseline emission levels.

           Comparison of the NOX emission data in Table 2-4 with those in
Tables 2-2  and 2-3  reveals  that baseline NOx emission levels from tan-
gentially fired boilers are lower than  those from wall fired boilers.
(The  turbo-furnace  boiler was tested at 370 MW, due to operating
problems  at the time of our test, compared  with design full load of
450 MW,  and hence,  additional testing is needed to measure baseline,
full  load NOX emission levels.)  Combustion modifications for "low NOX"
staged firing operation with 15-20% load reduction enabled these tan-
gentially fired boilers to  further decrease NOX emissions.  "Low NOX"
operation with further load reduction resulted  in NOX reductions of  55
to 64% compared to  full load, baseline  emission levels.

           As will be discussed  in Section  6 of  this  report, it  should be
recognized  that these  results were  obtained during  short-term  test  periods
and that  long-term  testing  is needed  to study  slagging,  corrosion and other
operating conditions.  It is expected that  slagging  problems in some boilers
can be largely overcome by  increasing slag  blower steam  pressures,  increasing
the use  of  slag blowers and perhaps the addition of  slag blowers at  trouble-
some  locations.   Lower NOX  emissions would  also be  expected in  many  boilers
from  improved furnace maintenance,  so that  air-to-fuel ratios are as uniform
as practical across the furnace.  Research  at extremely  low levels  of
stoichiometric air  to  the active burners (less  than  75%) with staged
firing may  yield significantly  improved NOX emission  levels with
decreased  slagging, because of  lower temperatures.  Also, the addition
of secondary air-ports (frequently termed "NO-ports" or "overtired air-
ports") would probably allow most boilers to reduce NOX emissions
significantly during full-load  operation with all burners firing coal.

-------
                                           TABLE 2-1
SUMMARY OF COAL FIRED BOILERS TESTED

Boiler Operator
Tennessee Valley
Authority
Gulf Power
Georgia Power

Arizona Public Service
Utah Power and Light
Alabama Power
Alabama Power
Tampa Electric
Central Illinois Light
Basin Electric
Pacific Power and Light
Pacific Power and Light

Station and
Boiler No.
Widows Creek
Crist
Harllee
Branch
Four Corners
Naught on
Barry
Barry
Big Bend
E.D. Edwards
Leland Olds
Dave Johnston
Dave Johnston
(a) B&W - Babcock and Wilcox
CE - Combustion Engineering
F-W - Foster Wheeler
RS - Riley Stoker

Boiler
Mfr.(a>
6(c) B&W
6<"> F-W
3*c^$iw

4(C) (ilw
3(c) %
4(°)(&
3 CE
2 RS
2 RS
1 B&W
2 B&W
4 RS
(b) FW -
HO -
T -
Turbo -

Type of M
Firing fl" £
FW
FW
HO

HO
T
T
T
Turbo
FW
HO
FW


CR No. of
MW) Burners
125
320
480

800
330
350
250
350
256
218
105
T 348
Front Wall
Horizontally Opposed
Tangential
Turbo -Furnace
16
16
40

54
20
20
48
24
16
20
18
28

Test
Variables
4
4
4

5
6
7
4
4
4
3
3
7
No. of
Test
Runs
41
22
51

26
26
46
8
14
19
13
14
6
236
(c)   Particulate tests performed on these boilers.
(d)   Corrosion probe tests performed on these units.

-------
                                        TABLE 2-2
SUMMARY OF NOX EMISSIONS
FOR FRONT WALL FIRED BOILERS
(COAL FIRING)
NOX Emissions
Boiler
Dave Johnston No. 2
Widows Creek No. 6
E. D. Edwards No. 2
Crist No. 6
Operating
(Gross Load
Baseline
"Low NOX I
Baseline
"Low NOX I
"Low NOX II
Baseline
"Low NOX I
"Low NOX II
Baseline
"Low NO I
"Low NO* II
Mode
- MW)
(101)
" (99)
(125)
" (123)
" (100)
(253)
" (256)
" (221)
(350)
" (320)
" (260)
7.0.
.... £_
5.0
5.2
3.4
2.0
2.7
3.5
1.6
3.0
3.3
2.2
3.5
ppm
(3% 00)
454
214
634
379
295
703
359
295
832
550
526
Lb.
106 BTU *
0.60
0.28
0.84
0.50
0.39
0.93
0.48
0.39
1.11
0.73
0.70
gm.
100 cal *
1.08
0.50
1.51
1.90
0.70
1.67
0.86
0.70
2.00
1.31
1.26
ppm CO
(3% 00)
112
962
258
665
818
42
172
26
22
196
217
                               X
*  Calculated as NO,

-------
                                        TABLE 2-3
                                SUMMARY OF NOX EMISSIONS
                             FOR OPPOSED WALL FIRED BOILERS

                                       (COAL FIRING)
                                                          NOX Emissions
                                                              — .	
Operating Mode
Boiler
Leland Olds No. 1


Harllee Branch No. 3


Four Corners No. 4


(Gross Load •
Baseline
"Low NOX
"Low NOX
Baseline
"Low NOx
"Low NOX
Baseline
"Low NOX
"Low NOX

I"
II"

I"
II"

I"
II"
• MW)
(219)
(218)
(185)
(490)
(473)
(400)
(800)
(794)
(600)
%00
3
2
2
3
1
1
5
3
3
.9
.8
.2
.5
.4
.6
.0
.2
.0
ppm
(VI n 1
(. J /o U,, )
569
375
260
711
463
359
935
488
452
Lb . gm .
106
0.
0.
0.
0.
0.
0.
1.
0.
0.
BTU * 10°
76
50
34
95
62
48
24
65
60
1.
0.
0.
1.
1.
0.
2.
1.
1.
ppm GI
Cal * (37, 0,
37
90
61
71
12
86
23
17
08
24
231
518
27
152
316
18
172
33
                                                                                                         I
                                                                                                        oo
                                                                                                         I
*  Calculated as NO.-

-------
                                        TABLE  2-4
SUMMARY OF NOx EMISSIONS
FOR TANGENTIALLY FIRED BOILERS
(COAL FIRING)
NOX Emissions
Boiler
Barry No. 3
Naught on No. 3
Barry No. 4
Dave Johnston No. 4
Operating Mode
(Gross Load - MW) 7o00
Baseline
"Low NOx
Baseline
"Low NOX
"Low NOX
Baseline
"Low NOX
"Low NOX
Baseline
"Low NOX
(250)
I" (248)
(334)
I" (310)
II" (256)
(350)
I" (300)
II" (186)
(306)
" (304)
£.
3.1
1.3
4.2
2.3
3.0
4.4
2.4
2.2
4.2
3.3
TURBO - FURNACE
Big Bend No. 2
Baseline
"Low NOX
"Low NOX
(370)
I" (370)
II" (300)
2.8
1.4
1.8
ppm
Lb.
Gm/100
(3% 00) 10*" BTU * Cal *
410
310
531
219
197
415
273
189
434
384
BOILER
600
398
341
0.55
0.41
0.71
0.29
0.26
0.55
0.36
0.25
0.53
0.51

0.80
0.53
0.45
0.99
0.74
1.28
0.52
0.47
0.99
0.65
0.45
1.04
0.92

1.44
0.95
0.81
ppm CO
61
100
27
499
376
24
113
281
19
99

28
319
87
*  Calculated as N0r

-------
                                  -  10 -
          The  ranges  of  NOX  emissions measured as a function of % stoichio-
metric air  without  staging during  the short term optimization phases of
the  individual field  test programs are presented graphically in Figure 2-1.
In this  figure,  and in subsequent  graphica] presentations, the power
generating  stations and  boilers  are coded by the following letters (for
clarity,  the boiler numbers  appear in these figures only for stations
where more  than one boiler was tested) :


         Code Letters               Station             Boiler No.
          WC    6              Widows Creek                6
          HB    3              Harllee Branch              3
          FC    4              Four Corners                4
          N     3              Naughton                    3
          B     3              Barry                       3
          B     4              Barry                       4
          BB    2              Big Bend                    2
          E     2              E. D. Edwards               2
          0     1              Leland Olds                 1
          J     2              Dave Johnston               2
          J     4              Dave Johnston               4
          C     6              Crist                       6

          The  absolute  levels of NOx emissions shown in Figure 2-1 are
clearly  related to  the  level of excess air (or % stoichiometric air) for
each boiler tested.   In fact, the slopes of the NOx vs- ^ stoichiometric
air lines exhibit a rather small variability, which is remarkable in view
of the fact that  the data have been obtained on different boiler and burner
types and sizes,  fired  with different types of coal.  The very strong
dependence of  NOx emission levels on available oxygen will be discussed
further.

          As in our "Systematic Field Study", the uncontrolled baseline
NOX emissions  have  been correlated with the load generated per equivalent
furnace  firing wall.  The earlier data ( 4 ) have been recalculated using
the same set of assumptions as for the result of the study i.e., that  the
number of equivalent firing walls is 1, 2, and 4 for front wall, horizontally
opposed, and tangentiaily fired boilers, respectively.  For boilers having
twin furnaces,  this number has been doubled.  However, in contrast to  the
earlier  correlations (4), the above factor of 2 was not used to account for
the presence of a division wall in the furnace, because the heat absorbing
effect of a division wall is smaller than that of furnace side waxxa.
Also, the data for  two  wet-bottom (one of them cyclone fired) boilers
tested previously (4 )  have been omitted from the correlations, because
of the uncharacteristically long residence time at high temperatures in
these two units.

-------
                                  - 11 -

                              FIGURE 2-1

                    PPM NOx VS % STOICHIOMETRIC
                         Am NORMAL FIRING	

                        (COAL FIRED BOILERS)
1000
 900  -
                                        Q  Front Wall Fired


                                            Opposed Wall Fired

                                            Tangentially ^ired

                                              I          I
200
                                  120        125

                               STOICHIOMETRIC AIR
                                                                 135

-------
                                  -  12 -
          As a  first approximation, the above type of correlation takes
into account the relationship of furnace heat release rate to the heat
absorption  rate.  Figure 2-2 presents the correlation of baseline NOx
emission  levels (ppm at 3%  02, dry basis) vs. gross load per furnace firing
wall.  The  dashed line labeled "Present Study" is the least squares regres-
sion of the 12  data points  corresponding to the 12 boilers tested in the pre-
sent program.   The dotted line in Figure 2-2 is calculated from
our "Systematic Field Study"  (_4_), while the solid line is the regression
for all boilers.  There appears to be a very good correlation on this
basis, as the correlation coefficient is 0.9, and the standard error on
the estimate is 70 ppm NOX.  It should be noted that individual boilers
of unusual  furnace or burner design may produce emission rates outside
of the expected range calculated for the relationship shown in Figure 2.2.
Our sample  of 12 boilers plus 5 out of 7 for the 1971 field study is a
relatively  small sample of  the highly diverse populations of boilers
operating in the United States.  The regression intercept of 390 ppm NOX
at zero load corresponds to a conversion of about 20% of the average fuel
nitrogen  content of 1.3 wt. % of the coal types fired in this study.  This
observation is  a strong indication of the significant contribution of
bound fuel  nitrogen to NOx  emissions from coal fired boilers.  On an
absolute  scale,  this contribution would account for over 50% of the total
NOX emitted for the majority of the coal-fired boilers  tested, which is
in agreement with laboratory results (7 ) on this problem.  Substoichio-
metric air  supply to the active burners is expected to  reduce both the
fixation  of molecular N£, and the oxidation of fuel nitrogen, based on
independent laboratory data (8 ) .

          Figures 2-3 and 2-4 have been prepared  to show the overall
correlations of NOx emissions vs overall  %  stoichiometric air and %
stoichiometric  air supplied to the active burners.  Figure 2-3 is a plot
of "normalized" NOx emissions, expressed  as  the  % of baseline NOx emis-
sions  (full load and  20%  excess air) vs.  %  overall  stoichiometric air
(or % stoichiometric air to active burners under normal firing conditions).
The solid lines shown for each boiler are based on least-squares linear
regression  analysis of all  test runs made uner normal (all burners
firing coal), full load firing conditions.  With the exception of the
turbo-furnace boiler, all of these regressions show very good agreement
with about  a 20% reduction  in NOx at 110% vs. 120% stoichiometric air.
The three tangentially fired boilers show especially good agreement
in this significant correlation of NOX emission levels  with excess air
levels.

          Figure 2-4 is a plot of "normalized" NOx emissions expressed
as the %  of baseline NOx emissions (full load and 20% overall excess air)
vs. % stoichiometric air to the active burners under staged firing con-
ditions.  Thus,  the ordinates are identical in Figures  2-3 and 2-4.
However,  the least squares  regression lines of Figure 2-4 do not neces-
sairly pass through the 100% normalized NOx point at 120% stoichiometric
air to the  active burners,  as they must, by definition, in Figure 2-3.

          Figure 2-4 indicates the importance of low excess air firing
on NOx emissions, as well as the further benefits of staged firing and
additional  firing modifications.  The opposed wall fired boilers (Harllee
Branch No.  3, and Four Corners No. 4 boilers) showed excellent agreement, as

-------
                                             FIGURE 2-2
   1000
 fi
 w
 u
 X
 w
   800
   600
(3s?
CO
   400
  x
g
PL*
   200
                                   UNCONTROLLED NOx EMISSIONS VS

                               GROSS LOAD PER FURNACE FIRING WALL


                                       (COAL FIRED BOILERS)
                                              T
                                            ~~1	T

                                             ALL BOILERS
1971 FIELD STUDY (4 )
                                                     V^PRESENI

                                                          STUDY  -

                                                       fpcl
                                                               FRONT WALL FIRED
                                                               OPPOSED WALL FIRED
                                                               TANGENTIAL FIRED
                                                      "2W"
                                            "35IT
                                                                                                   u>

                                                                                                   I
"550
                             GROSS LOAD PER FURNACE FIRING WALL - MW

-------
i
esi
CQ

fc
O
   140
    120
fi
<
CQ   100
CO
W

><
W
    80
60
    40
    20
                                       FIGURE 2-3


                                EFFECT OF EXCESS AIR ON NOX

                             EMISSIONS UNDER NORMAL OPERATION


                                  (COAL FIRED BOILERS)
                A-^   «9VX
O   Front Wall Fired



n   Opposed Wall Fired



/\   Tangentially Fired
                                                   1
           104
                 108       112         116       120        124


                         \VERAGE % STOICHIOMETRIC AIR
                128
                                                                                132
136

-------
                                             FIGURE 2-4
i

I
<
OT
03
w
o
X
w
W
w

<:

PQ

fe

O
   100
    80  -
    60  _
     40  -
    20  ~
     0
                               EFFECT OF EXCESS AIR ON NOX EMISSIONS

                                 UNDER MODIFIED FIRING CONDITIONS	
                                        (COAL FIRED BOILERS)
                                                                     Front Wall Fired
                                                                     Opposed Wall Fired
                                                               /\   Tangentially Fired
                                                                                                        Ul


                                                                                                        I
                         AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                                  - 16 -
would be  expected,  since both of them represent modern design practices
of Babcock and Wilcox with their cell-type  burners.  Leland Olds No. 1
representing a t,ouiewhat different type of design  shows more of a deviation
from this behavior.  The tangentially fired boilers, Barry No. 4 and
Naughton  No. 3, that employed staged  firing showed  similar trends, with
Naughton  No. 4 producing lower NQx emissions because it  was  tested at
lower  % stoichiometric air levels.  Of the  tront  wail-fired  units, Widows
Creek  No. 6 boiler showed consistently larger reductions in  normalized
NOX under normal operating conditions than the other front wall  fired units
at the same %  stoichiometric air levels.  However,  under modified  firing
conditions  all front wall fired boilers gave similar results.   Boiler para-
meters such as size, coal type fired, pulverizer  conditions,  and other
design and  operating variables undoubtedly contributed to the differences
 found.

 2.2  Particulate Mass  Loading

           As  described in detail in Section 4 of  this  report, four
 Research Appliance Company EPA-type particulate sampling trains were
 used in  this  program.   The design of this equipment follows the guidelines
 of EPA Method No.  5  (9).  Many difficulties occur in actual operation,  as
 is inherent to particulate testing.  Care must be taken to assure that
 the probes  and test boxes are at specified temperatures.  Even so,
 especially  in cold weather, moisture in the flue gases condensing in the
 apparatus can quickly  plug filters which results  in aborting the test.
 Tests for leaks in each train prior to testing is also needed if meaningful
 data are to be obtained.  Plugging of sampling probes on occasion also
 occurs,  and can present difficulties in boilers with high particulate
 loadings.

           The boilers  tested proved to be another source of recurrent
 problems.  Most boilers were not equipped with suitable testing facilities.
 Sample test ports  are  often located too close to bends in the flue ducts
 where particulate  concentrations, due to centrifugal action, are strongly
 stratified.   Interferences of the probes with supports inside the flue
 ducts and of the  test  apparatus with other obstructions near test loca-
 tions outside the  boiler contribute to the difficulty of running par-
 ticulate loading  tests.  Last but not least, the EPA-type test train is
 built for horizontal probing, while most boiler test locations require
 vertical probing.   Our equipment has been modified for vertical probing,
 so that  usually the construction of scaffolding was necessary for access
 to the ducting.

           Despite  the  problems of conducting particulate tests,  the
 results  obtained  in this program, summarized in Table  6-17,  are consistent
 and appear  to be  reliable within  the limitations of this type of testing.
 The objective of  our work was to develop information on potential "side
 effects" of "low  NOX"  firing techniques on total particulate loadings and
 on the  carbon content of the flyash  produced.  Although strict adherence
 to EPA recommended sampling  procedures was not possible, due to the
 limited  availability of sample port locations and interferences with

-------
                                 - 17 -
building and boiler structures, the same procedures were used under both
baseline and "low NOX" conditions.  Therefore, the differences observed
in the results on particulate emissions and particulate carbon content
are felt to be representative of the relative effects of combustion
modifications on particulate emissions.

          As expected, some side effects did develop under "low NOX" firing
conditions.  Total quantities of particulates tend to increase but not
significantly and the consequences appear to be relatively minor.  This
trend would have an adverse effect on the required collection efficiency
of electrostatic precipitators to meet present Federal emission standards,
but the increases required in precipitator efficiency appear to be quite
small based on these limited tests.

          Another potentially adverse side effect of "low NOX" operation
with staged firing is that of increased carbon content of flyash.  The
carbon content of the particulates with "low NOX" operation, according
to the results of the study, in some cases increased on front wall fired
boilers by as much as from 6 to 10.5% on the average and from 5 to 8% on
horizontally opposed fired boilers.  However, the data are quite scattered,
and these increases do not appear  to be directly related to the change in
emissions with "low NOX" firing techniques, or other boiler operating
variables.  In the limited test data obtained, the debit due to increased
carbon on particulates, as discussed in Section 6.1.4 is offset at least
in part by the improved boiler efficiency due to the lower excess air
operation at "low NOX" conditions.  Surprisingly, there is some evidence
that "low NOX" firing techniques for tangentially fired boilers decrease
carbon losses by about 25 to 40%.  If this finding can be substantiated for
other tangentially fired boilers,  a net credit may be applied to "low
NOx" operation of these units.  Also it appears that "low NOX" firing
may decrease carbon losses for boilers fired with Western coals.  Such
improvements, however, would not be substantial since unburned combustible
losses with the easy-to-burn Western coals are already low.

          More data are needed on  all types of boilers to substantiate
these findings.  It is important to note, however, that no major adverse
side effects on particulate emissions appear  to result from the application
of staged  combustion and low excess air levels for NOX emission control
for the coal fired boilers tested.

2.3  Furnace Corrosion Testing

           Corrosion of furnace sidewall tubes caused problems in the
early days of the development of pulverized coal firing in utility boilers.
A considerable level of effort was devoted to the solution of this problem
through actual field trials and in laboratory experiments to determine
the corrosion mechanism.  Eventually practical solutions to the furnace
tube corrosion problem were found by increasing the level of excess air
and improving the fineness of pulverization so that oxidation of the
pyrites in the coal was complete before these ash particles could impinge
on the sidewall tubes.  As practical solutions to this problem became
available, very little information on this subject was documented in
publications.

-------
                                  - 18 -
          For the purpose of reducing nitrogen oxide emissions from
boilers, decreasing the level of excess air has been practical as one
of the principal combustion modification techniques.  The potential use
of this approach has resulted in a considerable amount of speculation and
apprehension that furnace sidewall corrosion problems might again be
encountered in coal fired installations.  Consequently, boiler owners
have been reluctant to subject their units to long term tests to determine
potential corrosion problems associated with low excess air firing without
some evidence that the risks are not grave, particularly for staged firing
that produces a net reducing environment in some portions of the furnace.

          For the above reasons, part of the current program was devoted
to obtaining "measurable" corrosion rates on probes exposed to actual
furnace conditions.  The objective of this effort was to obtain data on
potential effects of "low NOX" firing conditions on furnace wall tube
corrosion rates.  The approach used in obtaining these data was to
deliberately accelerate the rate of corrosion of coupons exposed to
temperatures in excess of normal tube metal temperatures of about 600°F.
It was decided that exposure for 300 hours at 875°F in susceptible furnace
areas would be sufficient to show major differences in corrosion rates
between coupons exposed to "low NOx" firing conditions and those exposed
under normal conditions.

          Although there was some scatter in the data obtained, the
results showed some consistent trends.   A major finding was that no major
differences in accelerated corrosion rates were observed between coupons
exposed to "low NOx", reducing conditions and those exposed under normal
boiler operating conditions.  In fact,  in some of the tests, the corrosion
rates were found to be lower under modified combustion operation than under
baseline conditions.

          Since corrosion was deliberately accelerated for these corrosion
tests in order to develop "measurable"  corrosion rates in a short time
period, the measured rates were much higher than normal tube wastage
experienced in actual furnace walls.  In future tests, the coupons should
not be acid pickled prior to exposure in the furnace to remove oxide
coatings, and coupon temperatures should be reduced to obtain corrosion
rates more closely simulating actual tube wastage rates.

          More information is required  for assessing the importance of
furnace tube corrosion problems that may result from firing coal with
substoichiometric quantities of air. The data obtained in this program
helps provide evidence that furnace tube corrosion may not necessarily be
a severe side effect of combustion modification techniques for NOX emission
control.  Long term "low NOX" tests using corrosion probes and the direct
determination of actual furnace wall tube corrosion rates by measuring
tube wall thicknesses are needed for a  thorough assessment of the problem.

-------
                                  - 19 -
 2.4  Effects of Combustion Modifications
     on Boiler Performance	

          Modifications of the combustion process for minimizing NOX
 emissions in general tend to result in less intense combustion conditions,
 Lowering the level of excess air supply increases flame  temperatures
 which aids combustion, but tends to limit the amount of  oxygen available
 for the combustion process.  Thus, this factor directionally increases
 the probability of burnout problems.  Similarly, staged  combustion burner
 patterns, in which some burners are operated at substoichiometric
 conditions, and the remaining burners are used as secondary or overfire
 "air-ports" to complete the combustion of the fuel, can  produce major
 changes.  These consist of further limiting the supply of available
 oxygen in the initial combustion phase, lengthening the  flames, and
 slower diffusive mixing of air and fuel.  Thus, this mode of operation
 potentially increases unburned combustibles and, in turn, could have
 an adverse effect on boiler efficiency.

          During each major test at baseline and "low NOX" firing
 conditions particulate dust loading data were obtained in accordance
 with EPA recommended procedures.  The particulate samples were analyzed
 for carbon content (uncombustibles) and the differences  in results from
 tests at baseline and "low NOX" conditions provide an indication of
 potential adverse side-effects.  In addition, critical control room
 board data and other information pertinent to boiler performance cal-
 culations were recorded.  Boiler efficiency was calculated for each
 test following the ASME Abbreviated Efficiency Test heat loss method
 using this information.  The results are discussed in Section 6.1.4.

          The conclusion reached from these performance  data is that
 there are no major performance debits with regard to boiler efficiency
 when operating a boiler under "low NOX" emission conditions.  Differences
 discerned in boiler efficiency, if any, with "low NOX" firing were
 negligible.  This shows that, with proper controls, the problems discussed
 above can be minimized or eliminated.

 2.5  NOX Emissions for Boilers Converted
     from Coal to Oil Firing	

          Very little information is available on the level and potential
 control of NOX emissions for utility boilers converted from coal to oil
 firing.  For this reason, short-term emission tests were made on several
 units of this type.

          This section summarizes the emission field tests conducted on
 utility boilers converted from coal to oil firing.  Six  units of this
 type were tested, four of them at Atlantic City Electric Company's
Deepwater Station, and the other two boilers at that company's B.  L.
England Station.

-------
                                 - 20 -
          Design and operating features of these six oil-fired boilers
tested are summarized in Table 2-5.  All of the boilers tested at the
Deepwater Station are front-wall fired units having maximum continuous
ratings ranging between 23 MW and 83 MW gross load.  The two cyclone-
fired boilers tested at the B. L. England Station have full load ratings
of 136 MW and 168 MW, respectively.

          Table 2-6 summarizes the NOX emissions measured from these
coal-to-oil  converted boilers tested.

          In general, low NOX levels were measured even under normal,
baseline conditions.  Thus, the baseline NOX emissions measured from
Deepwater Boilers No. 3 and 5 were found to be lower than the EPA new
source emission standard of 0.3 Ib NOX per million Btu fired, which is
equivalent to about 225 ppm, corrected to 3% 02, on a dry basis.  For
Deepwater Boilers No. 8 and 9, the baseline NOX emissions were found
to be slightly above the 0.3 Ib/lO^ Btu level, but staged firing of
these boilers reduced the emissions from these boilers well below the
level of 0.3 lb/106 Btu.

          As expected, the cyclone fired coal-to-oil converted Boilers No.
1 and 2 at ACE's B.L. England Station produced significantly higher NOX
emissions than the wall-fired units tested at Deepwater.  In the case of
B.L. England No. 1, the baseline level was 441 ppm NOX (corrected to 3%
02, on a dry basis), compared with the 225 ppm equivalent of the 0.3
Ib/lO^ Btu recommended EPA standard.  Similarly, the baseline NOX emissions
level from B.L. England Boiler No. 2 was 361 ppm, corrected to 3% 02 on a
dry basis.   This is in line with the expected effect of the high temperature
environment  prevailing in cyclone fired boilers, which are conducive to
relatively high NOX emission levels.

          Staged firing of  front wall fired Boilers No. 8 and 9 at the
Deepwater Station produced NOX emission levels well below the 0.3 Ib/lO^ Btu
level, even  at full boiler  load.  Lowering the excess air level was
effective in all boilers  tested  (including the cyclone boilers), for
reducing NOX emissions, particularly in combination with staged firing.

          The relative contribution of atmospheric nitrogen fixation and
chemically bound nitrogen oxidation NOX emissions can be estimated based
on the data  of Turner et al., obtained in a modified packaged boiler  (8).
The fuel oils fired at Deepwater averaged about 0.13 wt. % N content.
According to the fuel nitrogen conversion data, about 70% of the nitrogen
in the fuel  is expected to be converted into NOX.  Thus, roughly 130-140
ppm NOX would be predicted to be produced through the oxidation of fuel
nitrogen.  When comparing this prediction with the actual NOX levels
measured, it appears that in all cases fuel nitrogen oxidation accounts
for significant portions, and in some cases, the bulk of the NOX emission.
Similar arguments can be made about the cyclone fired boilers at the B.L.

-------
TABLE 2-5
ATLANTIC CITY ELECTRIC COMPANY
SUMMARY OF COAL-TO-OIL CONVERTED BOILERS TESTED
Station
Deepwater
Deepwater
Deepwater
Deepwater
B. L. England
B. L. England
Blr No.
3
5
8
9
1
2
Blr Mfr.
B&W
B&W
B&W
CE
B&W
B&W
Type of
Firing
FW
FW
FW
FW
Cyc.
Cyc.
MCR
(MW)
57
56
83
22.8
133
168
No. of
Burners
6
6
16
6
3
4
Test No. of
Variables Test Runs
5 8
4 4
14 25
6 7
4 7
2 2

-------
TABLE  2-6
ATLANTIC CITY ELECTRIC COMPANY
SUMMARY OF NOX EMISSIONS
FOR COAL-TO-OIL CONVERTED BOILERS
NOX Emissions

Boiler
Depwater No. 3
Deepwater No. 5
Deepwater No. 8
Deepwater No. 9
B.
B.
L. England No. 1
L. England No. 2
Operating Mode
(Gross Load-MW) %
Baseline
"Low NO "
X
Baseline
"Low NO "
X
Baseline
"Low NO "
X
Baseline
"Low NO "
X
Baseline
"Low NO "
X
Baseline
"Low NO "
(57)
(57)
(56)
(56)
(83)
(81)
(23)
(21)
(133)
(132)
(167)
(167)
6
5
4
2
4
4
1
2
1
0
2
1
_°2.
.1
.0
.2
.8
.5
.4
.8
.6
.5
.5
.2
.6
ppm
(3% 02)
142
118
221
209
246
123
286
101
441
313
361
303
Ib
10b
-
0.
0.
0.
0.
0.
0.
0.
0.
0.
0.
Btu
-
29
28
33
16
38
13
59
42
48
42
Gr/106 Cal
-
0.
0.
0.
0.
0.
0.
1.
0.
0.
0.
-
52
50
59
29
68
23
06
76
86
76
CO
ppm
(3% 02)
67
81
55
84
49
64
44
64
57
1523
85
231
                                                                    N3
                                                                    NJ

-------
                                 - 23 -
England Station, where fuel nitrogen contribution to NOX emissions is
expected to be significant, but proportionately less because of the more
intense combustion conditions.  Therefore, the use of combustion modifica-
tion techniques, if possible on cyclone fired installations might become
necessary if high nitrogen content fuel oils or other liquid fuels (such
as coal liquids or shale oil) are fired in such boilers.

          In conclusion, much valuable information has been obtained in
this test program on the levels of NOX emissions and their potential
control in boilers converted from coal to oil firing.  Although further
emission data are needed for establishing broad generalizations for this
type of equipment, it may be concluded that the NOX response of such
units to combustion modifications is similar to that of boilers designed
for oil firing.  In fact, the furnace characteristics of coal-fired boilers
converted to oil firing are expected to favor the control of NOX emissions
through combustion modifications, because of the more liberal sizing of
coal fired furnaces, which should result in higher heat removal rates
when firing oil.

-------
                                 - 24 -
                       3.   EFFECT OF ELECTROSTATIC
                        PRECIPITATORS ON NOX FORMATION
          Electrostatic precipitators  are used extensively for reducing
particulate emissions for coal fired,  steam-electric plants.   High
voltages across electrodes in this  equipment create  a corona discharge
that ionizes gas molecules and electrically charges  particles passing
through the field.   The charged particles are attracted to oppositely
charged surfaces where they can be  removed from the  flue gas.

          The effect of electrostatic  precipitation  on NOX formation is
not clear.  It is possible that the corona discharge (or perhaps arcing)
forms ozone and atomic oxygen, which form nitrogen oxides through reactions
with nitrogen..  However,  data reported to date have  not resolved this
question since both increases and decreases of NOX have been found (I) .

          As part of the present field test program, emission measurements
were made upstream  and downstream of the precipitator in the A and B flue
gas ducts of Boiler No. 4 at the Barry Power Station of the Alabama Power
Company, in an attempt to shed more light on this  potential problem.  The
precipitators of Boiler No. 4 at the Barry Station are well suited to such
tests, as the ash removal system at present is incapable of removing the
flyash collected in the precipitator collection hoppers sufficiently rapid.
This results in a build-up to a point  where the plates are shorted and
arcing occurs.  It  has been expected that this condition may promote the
formation of NOX, if any occurs.

          Table 3-1 summarizes gas  analyses taken  before and after the
Barry A and B precipitators with the precipitators on and off.  All data
reported have been  corrected to 3%  G£  in the flue  gas for comparison
purposes.  Analysis of the data shows  that there are no statistically
significant differences in NOX values  measured upstream and downstream
of the precipitators on either the  A or B sides.  It is concluded from
these tests that either the conditions required for  the formation of
NOX in precipitators were not present  in these tests, or more likely,
that there is no net production of  NOX from the precipitators.  Additional
research, over a variety of both corona discharge  as well as arcing opera-
tions is needed to  better quantify  the effect of electrostatic precipitators
on NOX formation in flue gas from coal fired boilers.

              As reported  earlier in our "Systems Study"  (1) , electric
discharge precipitation has been successfully used  to  remove NO  from
manufactured  gas (10).  However, it appears  that  unsaturated hydrocarbons
are  essential for NO  removal  (11) by this method.   Since  power plant flue
gases  contain negligible  amounts of unsaturates,  such  compounds   would
have to be added at  prohibitively high  costs  to use such  a proposed method
 (12)  for power  plant  NOX  emission  control.

-------
 - 25  -
TABLE 3-1
NOx EMISSION MEASUREMENTS TESTS ACROSS THE ELECTROSTATIC PRECIPITATOR
ALABAMA POWER COMPANY BARRY, BOILER NO. 4
(NOX
Avg.
Avg.
Avg.
Avg.
Avg.
Avg.
Concentrations in ppm, Corrected to 3% 0~, Dry Basis)
I. Precipitator Off - A Side
Before
Probe
414
401
407
407
Before
Probe
428
431
436
432
Before
Probe
389
400
405
398
*> 	
Before
Precipitator
1 Probe 2
388
380
381
383
	 ^ 	 J
395
II. Precipitator
Precipitator
1 Probe 2
417
424
416
	 4J9
426
III. Precipitator
Precipitator
1 Probe 2
371
387
399
386
•— • *~^._ ,*^*™ ^^f
372
IV. Precipitator
Precipitator
Probe 1 Probe 2
Avg.
Avg.
411
411
413
412
404
464
406
405
— •v -'
408
After Precipitator
Port a Port b
Short 386 401
Medium 373 414
Long 376 422
Ave. ^378 412,
Avg. 395
On - A Side
After Precipitator
Port a Port b
Short 420 416
Medium 421 416
Long 429 427
Ave. ^423 	 420^,
Avg. 422
Off - B Side
After Precipitator
Port a Port b
Short 373 383
Medium 404 392
Long 392 393
Ave. V390 	 389V
Avg. 394
On - B Side
After Precipitator
Port a Port b
Short 398 379
Medium 400 387
Long 403 394
Ave. ^400 38J
Avg. 394

-------
                                    - 26 -
                  4.   FIELD STUDY  PLANNING AND PROCEDURES


           This section discusses  the major  steps involved in field study
planning and the test procedures  used to obtain emission and corrosion
measurements.   Field study planning steps included developing boiler
selection criteria,  establishing  EPA/Exxon/Boiler Operators/Boiler
Manufacturers cooperation, and designing an effective test program strategy.
Testing  procedures included gaseous sampling and analyses, particulate
sampling and corrosion probing.   Methods of gaseous emission testing
were quite similar to those used in Exxon's "Systematic Field Study"  (4-6) •
Particulate loadings of the flue gas  stream, and the carbon content of the
particulates were also determined to  identify potentially adverse side-
effects.  In addition, corrosion probes were designed, and acclerated cor-
rosion test measurements were conducted under baseline and low NOX operations.

4.1   Program Design

           As discussed earlier in this  report, the major problem area in
reducing NOX emissions by combustion modification is to apply such
techniques to coal fired boilers. Coal fired utility boilers are the
largest  single source of stationary NQx emissions in the United States,
i.e.,  3  million tons NOX estimated for  1970, compared to 0.5 million tons
for  gas, and 0.3 million tons for oil firing (1) .  The operating flexibility
of coal  fired boilers is generally less than that of oil or gas fired
boilers.  This section will discuss the criteria developed and the coopera-
tive efforts required for selecting representative coal fired boilers, as
well as  the broad testing program strategy  developed for efficiently
measuring gaseous emissions, particulate emissions, and accelerated cor-
rosion rates.

      4.1.1  Boiler Selection Criteria

           Criteria recommended for selection of coal fired boilers were
classified into five groups which are discussed in turn below:   (1)  boiler
design factors, (2)  boiler operating flexibility, (3) boiler measurement
and  control capability,  (4) boiler operating management policy concerning
research and operating practices  and  (5) logistic and scheduling considerations,

           Boilers representing the current  design practices of the
utility  boiler manufacturers (Babcock and Wilcox, Combustion Engineering,
Foster Wheeler and Riley-Stoker)  were desired.  Design factors such as
size (150 MW or larger), type of  firing (wall tangential,  turbo-furnace
and  possibly cyclone), furnace loading  (normal, not extreme),  burner con-
figuration (size, number and spacing),  draft system (both balanced draft
and  pressurized), and furnace bottom design (wet and dry bottom) were
considered.

-------
                                  - 27 -
           Boiler operating flexibility was a prime consideration in
 selecting boilers.  Specific variables  (with the desired operating
 ranges listed ln parentheses) were:  excess air level (5-30%), furnace load
 with all burners firing (60 to 100% of maximum continuous rating),
 staged firing (individual burners or rows of burners on air only, or
 biased firing of individual burners), air register settings (20% to
 100% open),  combustion air preheat temperature (100°F variation),
 wind box pressure (low to high, over wide ranges of furnace load'and
 excess air  levels),  fuel burned (coal types characteristic of major
 U.S.  regions),  flue  gas recirculation (location of injection point
 and amount  recirculated) and independent steam temperature controls
 (attemperation  water,  burner tilt, air register flexibility, adequate
 soot blower  capacity,  etc.).

           Boilers vary considerably with regard to their operating
 parameters,  and measurement and control capabilities.  These capabilities
 are needed  to assure accurate,  quantative measurements representing
 each operating  condition, and to maintain stable operations during
 each test run.   Key  measurements needed are fuel,  air and water tem-
 peratures and feed rates;  steam temperatures,  pressures  and flow rates;
 and flue  gas component  measurements of oxygen,  combustibles, smoke,
 and temperatures.  In addition,  furnace viewing ports should be avail-
 able for  visual  inspection of furnace conditions such as burner flames
 and slag  buildup, in order to monitor potential problem  areas during
 each test run.   Also, ports are  needed for sampling coal supplied to or
 from the  pulverizers, sampling  the flue gas before air preheaters,
 sampling  particulates before  precipitators,  and for inserting corrosion
 probes  in furnace sidewalls.

          The attitude  of  the utility station  operating  management
 towards research programs,  and  their operating practices are other key
 elements  affecting the  productivity of field programs.  Operating
 management support includes providing  the  necessary technical,  super-
 visory  and^ operating personnel for  both planning and  conducting the  test
 program.  "Research-mindedness" means  support  for  exploiting the  full
 range of  boiler operating flexibility  in the test program.   A willingness
 to  schedule boiler load changes, to  provide expert  help  in  pre-test
 boiler  checkout, including the calibration of key boiler instruments,
 and  to  use experienced plant people  for  coal sampling and analysis is
 the result of a constructive management  policy  towards research programs.

          The criteria discussed above are extremely  useful,in  selecting
 candidate boilers for testing.  Individual boilers  can then  be  selected
 to provide maximum overall program effectiveness and  efficiency by
 taking  into account total schedule and logistic considerations.  Thus,
 utilities and stations should be so  selected that they would offer a
number  of boilers suitable for testing to minimize  travel and set-up
 time, and provide flexibility in case of unplanned boiler shutdowns,
with appropriate availability and load range.

-------
                                  - 28  -
     4.1.2  EPA/Exxon/Boiler Operators/
            Boiler Manufacturers Cooperation

          This  cooperative program of field testing utility boilers was
conducted by Exxon Research with the cooperation of utility boiler opera-
tors and manufacturers under the coordination of EPA.  The proper selection
of boilers  representing  current design practices for this program was
the result  of a cooperative planning effort.  Exxon Research developed
the comprehensive list of selection criteria discussed above to assist
EPA and boiler  manufacturers in preparing a list of potential boiler
candidates.  Each boiler manufacturer submitted a list of suggested
boilers to  EPA  for review and screening.  After consideration of such
factors as  design variables, operating flexibility, fuel type, geographic
location and logistics,  a tentative list of boilers was selected by EPA
and Exxon.  Field meetings were then held at power stations to confirm
the validity of the  boilers selected and to obtain necessary boiler
operating and design data.

          The field  meetings were attended by representatives of EPA,
Exxon  Research, boiler manufacturers and utility boiler operating manage-
ment.  EPA  described the background and need for developing emission
control technology for coal fired boilers, and how this fits into the
overall EPA program. Exxon Research presented a broad summary of pre-
vious  findings, and  an outline of the three-phase program to be run at
each boiler.  This led to the discussion aimed at developing the informa-
tion necessary  to  construct a detailed program plan.  These discussions
produced a  mutually  agreeable list of combustion operating variables, the
specific levels to be tested, estimated ease and length of time to change
from one level  to  another, how the variables were interrelated, and what
operating limitations or restrictions might be encountered.  In addition,
the proper  number  and specific location of sampling ports for gaseous,
particulate, and corrosion probes were also agreed upon.  If existing
sampling ports  were  not  adequate, new ports were installed by the
utility.  Tentative  testing dates were scheduled with provisions made
for possible segregation of coal types, scheduling of pre-test boiler
inspection, calibration  of measuring instruments and controls, scheduled
maintenance, and other preparatory steps.

          The excellent  support and cooperation provided by boiler
manufacturers and  utility boiler operators contributed significantly
to the success  of  this program.

     4.1.3  Test Program Strategy

          The up-to-date, comprehensive information obtained in field
meetings provided  the necessary data for Exxon to develop detailed,
run-by-run, proposed test program plans for review by all interested
parties.  Each  test  program, tailored to take full advantage of the

-------
                                  - 29 -
particular combustion control flexibility of each boiler, was comprised
of three phases:   (1) short test-period runs,  (2) a 1-3 day  sustained
"low NOx" run and  (3) 300-hour sustained "low NOX" and normal operation
runs.  Thus the strategy used for field testing coal-fired boLlers  consisted
first, of defining the optimum operating conditions for NOx  emission con-
trol, without apparent unfavorable side effects in short-term statistically
designed test programs.   Second,  the boiler was operated for 1-3 days under
the "low NOx" conditions determined during the optimization  phase,  for
assessing boiler operability problems.  Finally, where possible, sustained
300-hour runs were made under both baseline and modified ("low NOX")
operating conditions.  During this period, air-cooled carbon steel  coupons
were exposed on corrosion probes in the vicinity of furnace  water tubes,
to determine through accelerated corrosion tests whether operating  the
boiler under the reducing conditions associated with staged  firing
results in increased furnace water tube corrosion, rates.  Particulate
samples were obtained under both baseline and "low NOY" conditions.
                                                     A.
Engineering information on boiler operability, e.g.,  on slagging problems,
and data related to boiler performance were also obtained.

          Statistical principles (as discussed in more detail in our
"Systematic Field Study" (4)) provided practical guidance in planning
the Phase 1 test programs, i.e., how many, and which test runs to conduct,
as well as the proper order in which they should be run.  These procedures
allow valid conclusions to be drawn from analysis of data on only a small
fraction of the total possible number of different test runs that could
have been made.  Table 4-1 will be used to illustrate briefly these principles
applied to a front-wall fired boiler, TVA's Widows Creek Boiler No. 6.
(Tangentially fired boilers present a more complex problem in experimental
planning, since there are additional operating variables such as burner
tilt and secondary air register settings, that should be included in the
experimental design.   However, the same statistical principles apply.
In this example, there are four operating variables:   (1)  load,  (2)
excess air level,  (3) secondary air register settings, and (4) burner
firing pattern.  Assuming three levels of each of the first  three
variables, and eight different firing patterns available at each load,
there are 216 different  operating modes.  However,  only the  33 test runs
shown, i.e., 15% of the  potential maximum, provided the required informa-
tion on this boiler to define practical "low NOX" operating  conditions.

          Test run No. 10 operating conditions were chosen for the  second
phase of the experimental program, while test run No. 26 operating  condi-
tions are recommended for "low NOX" operation under reduced  load condi-
tions.  Test run No.  10 conditions could be selected with considerable
confidence, since examination of the data indicates that each of the 83
firing pattern runs produced lower NOX levels than did the corresponding
82 firing pattern.  The effects of day-to-day variables, such as coal
type variability, etc. not under study were balanced between the two
firing patterns, since runs No.  5,  6,  7 and 8 were made on one day,
while runs No. 9,  10, 11 and 12 were run on another day.   It should also

-------
                                                   TABLE 4-1

                            TEST  PROGRAM EXPERIMENTAL  DESIGN - WIDOWS  CREEK,  NO.  6

                       (Run  No.,  Average  %  0~ and Average PPM NO  Emissions  (3% 00, Dry))
                                           ^                   x                 i.

Tjjj-j^econdary
Pattern -Air^
Si - 16 Coal
0 Air Only
S2 - 14 Coal
D]^D4 Air
S3 - 14 Coal
A^A^ Air
84 - 12 Coal
A1A3A3A4
S5 - 12 Coal
A1A4B2B3
85 - 12 Coal
A1A4B1B4
S? - 12 Coal
A1A4°1D4
Sg - 12 Coal
B1B2B3B4
1^ - Rill Load (125 MW)
A. - Normal Air
20%
Open
(3) 2.8%
610
(11) 3.8%
632
(7) 4.5%
532





60%
Open
(1) 3.2%
577
(5) 4.0%
558
(9) 4.1%
518





A~ - Low Air
20%
Open
(4) 1.9%
505
(6) 2.0%
372
(10)* 1.7%
345





60%
Open
(2) 2.0%
491
(12) 1.5%
406
(8) 2.7%
368





L2 - Reduced Load (80 - 110 MW)
A. - Normal
20%
Open
(31) 4.9%
681


(24) 4.5%
399
(27) 4.9%
496
(15) 5.2%
471
(18) 4.3%
418

60%
Open
(29) 4.8%
629


(13) 4.5%
460
(17) 4.4%
480
(21) 6.1%
550
(25) 4.5%
495

A- - Low Air
20%
Open
(32) 2.8%
464


(26)** 2.7%
297
(22) 3.4%
306
(19) 3.1%
301
(16) 2.9%
329

60%
Open
(30) 2.7%
450


(20) 3.0%
345
(14) 2.6%
342
(28) 4.5%
438
(23) 3.9%
438
(20A) 2.2%
*** 371
                                                                                                                   w
                                                                                                                   o
 **
***
"Low NOX" operation selected for sustained run.
"Low NOx" operation at reduced load
Unplanned run 20A was conducted to obtain additional
information when pulverizer B was down due to
mechanical problems.
Pulverizer— Burner
Configuration
Mill Burner No.

A-Top
B-2nd
C-3rd
D-Bot

Row
Row
Row
, Rov
1
0
0
0
0
2
0
0
0
0
3
0
0
0
0
4
0
0
0
0

-------
                                   -  31  -
 be noted that each day's runs completed a one-half replicate of the
 complete factorial accomplished by two days of testing.  Thus, the
 main effects of each factor and interactions between factors could
 be estimated independently of each other, with maximum precision.
 Repeat test runs under test run 10 conditions, during a two-day
 sustained period, were used to validate these results and to obtain
 an independent estimate of experimental error.

 4.2  Test Procedures

           This section of the report describes the procedures used
 for performing field tests on utility boilers.  Flue gases were
 sampled and analyzed for gaseous species in each of the boiler test
 programs.  To assess potentially adverse side-effects of combustion
 modification techniques on particulate emissions (including carbon
 losses in the flyash) and on furnace water-wall corrosion rates,
 particulate measurements and accelerated corrosion rate determinations
 were also made for a number of boilers tested in this study.

      4-2.1   Gaseous  Sampling  and Analysis

           The objective of obtaining reliable gaseous emission data in  field
 testing boilers  requires a sophisticated sampling system.  The sampling and
 analytical system used in this program has already been described in detail
 in the Esso Research and Engineering Company Report, "Systematic Field  Study
 of NOX Emission  Control Methods for Utility Boilers" (4).

           For the present study,  further capabilities were added to the
 analytical instrument train by installing a Thermo-Electron chemiluminescent
 analyzer to provide measurements  of NO and NOX in addition to those obtained
 with  the Beckman NO and N02 spectroscopic monitors.  Figure 4-1 is a
 schematic diagram of  the configuration of the gaseous sampling and
 analytical system used in the present study.

           Since  samples  are taken  from zones of "equal areas" in the flue
 gas ducts,  gas sampling  probes are "tailor-made" for each individual boiler
 tested.   Three stainless  steel sampling tubes (short,  medium,  and long) are
 fabricated on the test-site, and installed in quick-disconnect mounting probe
 assemblies, along with a thermocouple located at the mid-point of the duct
 for gas temperature measurement.  At least two probes of this type are installed
 in each  flue  gas duct, or a minimum of  four are used when there is  only one
 large  flue duct on  the boiler.  Thus,  a minimum of  6 sample  points  per duct,
 or 12 per boiler are provided, assuring representative gas samples.   All
 connections between the Esso Analytical Van and the probes are of the
 quick-disconnect type for ease of assembly and assurance of leak-proof
 joints.

          In running field tests,  the gas samples are withdrawn from  the
boiler under vacuum, through the stainless steel probes  to  heated  filters
where the particulate matter is removed.   These filters  are maintained

-------
PROBE (4 EACH)



          THERMOCOUPLE
               FIGURE 4-1

EXXON RESEARCH TRANSPORTABLE SAMPLING
        AND ANALYTICAL SYSTEM
BOILER
DUCT
800°F
                   PITOT TU BE
                   500°F

                   PARTICULATE FILTERS (HEATED)
                             ROTAMETERS
                                           35 F
          HEATED
          LINES
             CO
 HYDROCARBONS
       NO  & NO  [
                               REFRIGERATOR
                                                                    200 FT
                                         SOLENOID
                                         VALVE
                                                       SAMPLING
                                                          VAN
                                                          I
                                                                                         UJ
                                                                                         N3
                                                                           ->V5 PSI RELIEF
                                                                               VALVE

-------
                                  -  33  -
 at 300-500°F.   The  gases  then pass  through  rotameters, which  are  followed
 by a packed  glass wool  column for 803  removal.   Initially,  gas  tempera-
 tures are  kept  as high  as possible  to  minimize  condensation in  the par-
 ticulate filters.   After  leaving  the packed column at  250-300°F,  the
 gas samples  pass at temperatures  above the dew-point through heated Teflon
 lines to the vacuum/pressure pumps.  The sample is then refrigerated to a
 35 F dew-point  before being sent  to the van for analysis.  Usually, the van
 is located 100  to  200 feet from this point and the gas stream flows through
 Teflon lines throughout this distance.

           As in our previous studies  (4-6),  our analytical  van was equipped
 with Beckman non-dispersive infrared analyzers to measure NO, CO, C02 and S02,
 a non-dispersive ultraviolet analyzer for N02 measurement, a polarographic 02
 analyzer and a  flame ionization detector for hydrocarbon analysis.  The
 Thermo-Electron chemiluminescent  instrument, as indicated above, was added
 to provide improved capabilities  for NO and NOX measurements.  The measuring
 ranges of  these continuous monitors are listed in Table  4-2.

           A  complete  range  of  calibration gas cylinders in  appropriate
 concentrations with N2  carrier  gas  for each  analyzer is installed in
 the  system.  Instruments  are  calibrated daily before each test, and
 in-between tests if necessary,  assuring reliable,  accurate analyses.

           Boiler flue gas samples are pumped continuously to the
 analytical van  through  four probes, each of which  combines the effluent
 of  three individual sampling tubes.  While one  sample is being analyzed,
 the  other  three are being vented.   Switching to a  new sample requires
 only the flushing of a very short section of sample line before reliable
 readings may be obtained.  Four duplicate sets of  analyses from each probe
 can  be obtained in less  than 32 minutes, thus speeding up the task of
 obtaining  reliable gaseous emissions, and/or avoiding the need to hold
 the  boiler too long at steady state conditions.

          The validity of using the Thermo-Electron chemiluminescent NO/NO
analyzer as the primary  NOX monitoring instrument  was  checked during the
 first series  of tests conducted in this program, on TVA's Widows Creek  Boiler
No.  6.  As  shown in Figure 4-2, the  NOX data measured with the chemiluminescent
analyzer were correlated with the  sum of NO plus N02 data measured with the
Beckman non-dispersive infrared NO and non-dispersive ultraviolet N02
instruments.   As seen from the regression in Figure 4-2,  excellent agreement
was  obtained  between the chemiluminescent monitor was validated  against  the
spectroscopic instruments, which in  turn had been validated against  a variety
of other technqiues, including the wet chemical phenoldisulfonic acid method
in previous Exxon field  studies (4-6).


         Our instrumental measurement  technique for flue  gas  02  and  COo
analyses were validated  periodically by checking against  Orsat determina-
tions made  on samples taken from the same points.   Measured 02 vs.  C02
x

-------
                                - 34 -
                               TABLE 4-2

                         CONTINUOUS ANALYTICAL
                       INSTRUMENTS IN EXXON VAN
    Beckman
  Instruments

NO
         Technique
 2

co2

CO


so2


Hydrocarbons
Non-dispersive Infrared


Non-dispersive ultraviolet


Polarographic


Non-dispersive infrared

Non-dispersive infrared



Non-dispersive infrared


Flame ionization  detection
  Measuring
    Range

0-400 ppm
0-2000 ppm

0-100 ppm
0-400 ppm

0-5%
0-25%

0-20%

0-200 ppm
0-1000 ppm
0-23,600 ppm

0-600 ppm
0-3000 ppm

0-10 ppm
0-100 ppm
0-1000 ppm
 Thermo Electron

 NO/NO
 Chemiluminescent
 0-2.5 ppm
 0-10.0 ppm
 0-25 ppm
 0-100 ppm
 0-250 ppm
 0-1000 ppm
 0-2500 ppm
 0-10,000 ppm

-------
                                              FIGURE 4-2
>l
II
ra
tf
w
 CM
g
i
O
W
CQ

CQ
      700
      600
      500
      400
      300
      200
      100
           Z
                               NOx REGRESSION - BECKMAN NO + NO2 VS
                               CHEMILUMINESCENCE NOx MEASUREMENTS
                               /
                                                         y= 0.42 + 1.0172X
                                                         r = 0. 985
                                                         Sy(est) = 19 ppm NO
                                                                                                     i
                                                                                                     OJ
                                                         ALL READINGS EXPRESSED AS
                                                         PPM NOx, CORRECTED TO 3%
                                                         O, DRY BASIS.
                   100
                           200
300
400
500
600
700
800
                              PPM NO  BY CHEMILUMINESCENT ANALYZER (X)
                                     X

-------
                                   - 36  -
 relationships were also compared with those calculated from the
 analysis of the actual fuel fired and different  excess air levels.   In
 addition frequent cross checks of flue gas Q£  content  were also  made
 with a portable polarographic (Beckman)  instrument  to  make certain  that
 van instrument measurements were accurate and  reliable.

           The comparison of measured to calculated 02 vs. CC>2 relationships
 is shown in Figure 4-3, based on data obtained in testing TVA's Widows
 Creek No. 6 Boiler.  As can be seen from Figure 4-3, the agreement  between
 the regressions based on measurements and calculations is very good over
 the range of actual measurements.

      4.2.2  Particulate Sampling

           Modifications of the combustion process for  minimizing NOX
 emissions in general tend to result in less intense combustion conditions.
 Lowering the level of excess air supply increases flame temperatures which
 aids combustion, but tends to limit the amount of oxygen available  for
 the  combustion process.   Thus,  this factor directionally increases  the
 probability of burnout  problems.   Similarly, staged combustion burner
 patterns,  in which some burners  are operated at  sub-stoichiometric  con-
 ditions,  and the remaining burners are used as secondary or overfire
 "air-ports"  to complete the combustion of the  fuel,  can  produce  major
 changes.   These  consist of further limiting the  supply of  available  oxygen
 in the  initial combustion phase,  lengthening the flames, and slower  dif-
 fusive  mixing  of air and fuel.   Thus,  this mode  of  operation potentially
 increases  unburned combustibles.   Also,  the actual amount  and  character
 of particulate matter in the flue gases  may be affected by modified  com-
 bustion operation.   Therefore,  it appeared necessary to take into account
 that combustion  modifications applied  for minimizing NOX emissions could
 potentially  increase particulate  emissions from  pulverized coal-fired
 boilers.

           To satisfy the need for this type of information, this field
 test program on coal fired boilers included measurement of  particulate
 emissions.   The  objective of this effort was to  obtain sufficient par-
 ticulate loading information to  determine the  potential  adverse  side effects
 of "low NOX" combustion modifications  on particulate emissions by comparing
 measurements of  total quantities and per cent  unburned carbon  with
 similar data obtained under normal or  baseline operating conditions.
 Other information,  such as changes in  particle size distribution or
 in flyash  resistivity which could affect electrostatic precipitator
 collection  efficiency is also needed.  However,  measurements of  this
 type were beyond the scope of the present  program.

          Four Research Appliance Company  EPA-type particulate sampling
 trains  designed  in accordance with  EPA Method  5  (9), including four  sample
boxes,  probes, and two  sets of isokinetic  pumping systems were used  for
obtaining particulate loading data  on  six  pulverized coal  fired  utility

-------
   18
                                    - 37 -
                                 FIGURE 4-3

                     RELATIONSHIP BETWEEN % CC>2 AND
                       % O2 FLUE GAS MEASUREMENTS

                      (WIDOWS CREEK, BOILER NO. 6-1B)
>H
II
S   16
ro
^
PQ
    14
O
w
£3
 Psl
O
0
    12
                                            CALCULATED FROM
                                            COAL ANALYSIS
                                            (Y- 18. 5-0. 88% O0)
CALCULATED FROM FLUE GAS ANALYSIS
        (Y= 18.4-0. 95% 09)
      0
                        % O2 IN FLUE GAS (DRY BASIS)

-------
                                  -  38 -
 boilers.  The names of the utilities and details of the boilers tested
 for particulate emissions are indicated in Table 2-1.  Except for tests at
 Utah Power & Light Company's Naughton Station, Boiler No. 3, all particulate
 mass data for dry, filterable solids loadings were obtained in the
 ducting at convenient locations downstream of the air-heaters.  At the
 Naughton Station particulate testing was done upstream of the air-heaters,
 due to the inaccessibility of sampling locations downstream of the air
 heaters.  Furthermore, at Alabama Power Company's Barry Station Boiler No. 4
 particulate sampling was carried out downstream of the precipitator (with
 the precipitator shut off), in a location immediately before entering the
 stack.  For all tests, two duct traverses were made with one probe assembly
 in each duct, in accordance with the procedures of Method 5 (9).   However,
 strict adherence to EPA-recommended test method was not always possible
 due to the limited availability of sample port locations, interferences
 with building and boiler appurtenances,  and the limited time and  manpower
 available for these tests.   However, it  should be remembered that the
 objective of these tests was not to measure absolute values of  particulate
 emissions,  but to determine relative changes between normal and modified
 firing operations.  Therefore,  it  was felt that information obtained  on
 relative changes in particulate emissions under normal and modified boiler
 operating conditions would  suffice for determining  potential side-effects
 of  combustion modification  techniques.

      A.2.3   Furnace Corrosion Rate Measurements

          Pulverized coal fired  boilers  are  subject  to wastage  of  the
 furnace wall  tubes.   Normally,  this type of  corrosion  is  experienced  in
 areas where  localized reducing  environments  might exist adjacent  to the
 midpoint  of  furnace  sidewalls near  burner  elevations where flame  impinge-
 ment could occur.   To  counteract such  effects,  normal  practice  is  to increase
 the excess air level so  that an oxidizing atmosphere prevails at  these
 locations, and to increase  the  fineness  of pulverization,  so that  the
 oxidation of the pyrites in the coal is  completed before  these  species
 can come  into  contact with  the  furnace wall  tubes.   For new boilers,
 a design  improvement consists of increasing  the separation between the
 burners and  the  sidewalls,  for minizing  potential  impingement problems.
 Several mechanisms have  been postulated  for  this type  of  corrosion which
 appears  to be  associated  with the  formation  of  pyrosulfates  from  the
 coal ash  (at  600-900°F),  and iron  sulfide, or  S03  from the pyrites.

          Combustion modifications  for NOX emission  control  are generally
 most effective at  low  excess air or substoichiometric  air  supply condi-
 tions in  the flame  zone,  i.e., under conditions  that are  potentially
 conducive to furnace  tube wall corrosion.  Our  prior field tests of
 coal-fired boilers have been of short duration,  allowing no  time to
 assess such side-effects.  However,  the need for evaluating  the effects
 of modified firing operations on furnace tube wall corrosion has been
recognized (13).  Discussions with  boiler manufacturers and operators
indicated that this potential problem was one of their major concerns.

-------
                                   -  39  -
 Also it became evident that accelerated corrosion rate testing would be
 necessary to establish that staged combustion could be used in coal-
 fired boilers without creating corrosion problems, because of the
 reluctance to operate on a long-term basis using the boiler as a test
 medium.

           Accordingly,  a third aspect of our  field testing was to design
 and  construct corrosion probes,  for exposure  under controlled conditions
 to define the extent  of the potential corrosion problem.   The objective
 of our furnace corrosion probing runs was to  obtain "measurable" cor-
 rosion rate data to determine  potential side  effects of "low NOX" firing
 conditions on furnace wall tubes.

           The approach used for  obtaining corrosion rate  data was to
 expose corrosion probes inserted into available openings  located at
 "vulnerable"  areas of the  furnace  under both  baseline and staged firing
 conditions.   Based on general  corrosion probing experiments,  it was
 concluded that exposure for approximately 300 hours at  elevated coupon
 metals temperatures (above normal  furnace tube  metal temperatures of
 about  600°F)  to accelerate corrosion,  would produce "measurable" rates
 of corrosion  on SA-192  carbon  steel  coupon material,  used for the manu-
 facture of furnace water tubes.  Since our objective was  to show relative
 differences in corrosion,  between  baseline and  "low NOX"  firing,  exposure
 temperatures  at  both  conditions were  set  at approximately 875OF.   Compared
 with normal tube wall  temperatures this was sufficiently  high  to accelerate
 the rate  of corrosion.   At  the same  time,  the comparison  temperature was
 kept below the 900°F  limit  above which  pyrosulfates  apparently  are not
 formed.

           Figures 4-4  and  4-5  show details of the  corrosion probes
 developed  for  this study based on  a design supplied  by  Combustion Engineering.
 Essentially,  this design consists  of  a  "pipe within  a pipe", where the
 cooling air from the plant  air supply  is  admitted  to  the  ring-shaped
 coupons exposed  to furnace  atmospheres  at  one end  of  the  probe,  through
 a 3/4-inch stainless steel  tube roughly centered inside of  the  coupons.
 The amount of  cooling air is automatically controlled to maintain the
 desired set-point temperature of 875°F  for the  coupons.  The cooling air
 supply  tube is axially  adjustable with respect  to  the corrosion  coupons
 so that temperatures of both coupons may be balanced.  To simplify the
 presentation,  thermocouples mounted in each coupon are not shown  in
Figures 4-4 and  4-5.   Normally, one thermocouple is used for controlling
and the other  one for recording temperatures.   The cooling air  travels
backwards  along  the 2-1/2-inch extension pipe and discharges outside of
 the furnace.   Thus, the cooling air and the furnace atmosphere do not mix
at the coupon  location.

          A 1/4-inch stainless steel tube is provided in the probe
assembly (Figures 4-4  and 4-5)  with an opening on the furnace side in
 the vicinity of  the furnace wall tubes and corrosion coupons.  Furnace

-------
                                        -  40  -
      gases may be drawn through  this  sampling  tube  for  analysis to determine
      the type of atmosphere  (reducing or  oxidizing) prevailing at the coupon
      location.   Sampling at  the  various probes during corrosion testing always
      showed a net excess of  oxygen.   Normally  the CO levels measured at
      these locations were low but in  a few  cases they exceeded the upper
      range of the CO instrument  (23,000 ppm).   This happened  (as  expected)
      when measured 02  concentrations  (0.1-0.2%) were very low.  Therefore,  in
      these isolated instances the atmosphere was net reducing because of the
      net excess  of CO  over oxygen.

               Sustained,  300-hour corrosion probe tests were run on boilers
      of  four  utility companies,  as shown  in Table 4-3.

                                    TABLE 4-3

                       SUMMARY OF CORROSION PROBING TESTS
          Utility
Georgia Power Co.

Utah Power & Light Co.

Arizona Public Service Co.

Alabama Power Co.
    Station
Harllee Branch

Naughton

Four Corners

Barry
 Boiler Number
Base  "Low NOY"
  4       3
  3

  5

  4
4

4
   Type of Firing
Horizontally Opposed

Tangential

Horizontally Opposed

Tangential

-------
                                           FIGURE 4-4

                                        CORROSION PROBE
                       DETAIL OF 2-1/2" IPS EXTENSION PIPE AND END PLATE
                                     (OUTSIDE OF FURNACE)
      DRILLED AND TAPPED FOR 1/8'HPT THREAD
(SWAGELOCK FITTINGS - FOR THERMOCOUPLES)
               \
               s—XfD
               /      \TO ACCEBT
               (       /1/2" SS ABR
               V     /SUPPLY
                ^	TUBING
     2-1/2" I.P.S. PIPE
        EXTENSION
                                                                       1/16" THERMOCOUPLES (2)
  AIR SUPPLY
(3/4" SS TUBING)
                                                   1/4" GAS SAMPT.TNH TURING (S
                                                     SEAL
                                                     WELD
   HOLE FOR 1/4" SS       END PLATE
   GAS SAMPLING TUBE
                           SWAGELOCK FITTING DRILLED FOR 1/2" SS AIR
                           SUPPLY TUBE (THREADS CUT OFF AND FITTING
                           WELDED OR SILVER SOLDERED TO END PLATE)
              WELD
                                                                          AIR DISCHARGE
                                                         1-1/4" COUPLING

-------
                                FIGURE 4-5

                             CORROSION PROBE

                   DETAIL OF CORROSION COUPON ASSEMBLY
                            (INSIDE OF FURNACE)
   2-1/2" PIPE EXTENSION

               \
1/4" S.S. GAS
SAMPLING TUBE
                     3/4" S.S. COOLING AIR SUPPLY TUBE
                   THERMOCOUPLE SOCKETS
                                                                     END CAP
CORROSION
COUPONS
                                                                                ho

                                                                                I
                       FACE OF FURNACE WALL TUBES

-------
                                  - 43 -
                         5.  COMBUSTION VARIABLES


          Our Systematic Field Study of NOX Emission Control Methods
for Utility Boilers  (1) was designed to explore the broad  limits of short-
term applicability of combustion modification on a representative  sample
of gas, oil and coal fired boilers.  The major combustion  operating
variables explored were:   (1) load reduction, (2) low excess air firing,
(3) staged combustion,  (A) flue gas recirculation, (5) air preheat
temperature, (6) burner tilt, (7) auxiliary to coal air damper settings,
and (8) secondary air register settings.   In our current field test pro-
gram, prime interest centered on coal fired boilers; first, to determine
the optimum combination of combustion variables, as listed above,  for
NOX emission reduction in short-period tests and second, to determine  if
slagging, corrosion or other operating problems were experienced in
extended period tests under "low NOX" operation.  Other emissions  (CO,
hydrocarbons, and particulates) were also  measured to determine whether
they were adversely affected.

          In this section, the major combustion variables  investigated
are discussed in general terms, while the  details of the results obtained
from each boiler tested are given in Section 6.

5.1  Load Reduction

          Since load reduction is an economically unattractive method
for reducing NOX emissions, the major emphasis in this program was to
determine the NOx reduction capability of  boilers at full  or maximum
possible load levels using combustion modifications for effective  NOX
emission control.   However, as shown by our overall correlations of
gross load per furnace firing-wall and by  the individual boiler results,
reducing load in coal fired boilers generally reduced NOx  emissions by
a lower percentage than the percentage reduction in load.  Reduced load
operation reduces the heat release per unit of furnace area or volume,
lowers effective peak flame temperatures and thus lowers the thermal
fixation of nitrogen in the furnace.   In addition,  low loads generally
require operation at higher excess air levels than at full load and the
increased availability of oxygen in the flame tends to increase NOX
emissions.

5.2  Low-Excess Air Firing

          Low excess air firing is an effective  method for NOX emission
control of coal fired boilers,  alone  and in combination with other com-
bustion variables such as staged firing.   This relationship is shown most
clearly by expressing the excess air  level as %  stoichiometric air to
active burners.  Reducing excess air  reduces NO  formation,  due to the
lack of availability of oxygen,  which preferentially  combines  with carbon,
hydrogen and sulfur rather than nitrogen.

-------
          The minimum practical level of excess air that can be reached
by each boiler depends upon a number of variables, such as load (lower
loads require higher excess air levels), uniformity of air to fuel ratio
for the operating burners,  (greater uniformity permits lower excess air),
slagging potential, furnace design  (cyclone furnace requires relatively
high excess  air), burner  tilt  (lower excess air for down-tilt than for up
tilt on tangentially fired boilers), secondary air register settings
(closed-down registers allow lower  excess air without violating minimum
wind-box to  furnace pressure differentials), steam temperature control
flexibility, coal quality variation, and fuel and air control lags during
load swings.  With coal fired boilers, under ideal conditions, 4 to 5%
excess air levels can be  reached without exceeding 200 ppm CO emissions.
More typical minimum excess air levels for coal firing in U.S. utility
boilers are  8 to 12% while in some  cases excess air levels below 15 to
18% present  operating problems.

5.3  Staged  Combustion

          Staged combustion (with low excess air) has so far proven in
short period tests to be  the most effective method of combustion control
for reducing nitrogen oxide emissions from coal fired boilers.  Although
coal fired boilers designed for two-stage combustion are just now coming
on line, a modified type  of two-stage combustion using some coal burners
on air only  has been successfully tested on a number of pulverized coal
fired boilers  (4).  Staged  combustion is effective in reducing both thermal
and fuel NOX emissions  (JJ)  due to limitation of oxygen and lower flame
temperatures in  the primary combustion zone, and lower effective temp-
eratures in  the  secondary,  air-rich combustion zone.

          Both practical  and theoretical considerations were  involved
in conducting  staged combustion test  runs.  The lowest practical air-to-
fuel ratios  were applied  to operating burners with maximum separation of
"air only burners" from operating burners to provide for cooling between
primary and  secondary combustion zones.  However, practical design and
operating constraints often limited the modified staged combustion effec-
tiveness for the  following  reasons:

          •  The  number and location of burners that could be operated
             on  an "air only"  basis depends upon the pulverizer - burner
             configuration  and the  maximum increase of coal supply
             to  active  burners under  full load conditions.  Otherwise,
             modified staged combustion generally resulted in a reduction
             in  load.   Fortunately, some boilers do have the  capacity
             to  operate at  full load with one or more pulverizers off,
             and  thus have  more staging flexibility.

          •  Some boilers do not have the capability of closing off
             individual coal burners from a pulverizer.  Thus, all
             burners fed  by a pulverizer are either on "active"   '
             or on "air only" operation.

-------
                                    - 45 -
          •   In some  boilers,  division wall tube temperature limita-
             tions, or  suspected side wall corrosion problems prevent
             the use  of ideal  "air-only" burner patterns.

          •   Steam temperature control problems can also prevent
             the use  of ideal  burner patterns.

          •   Furnace  slagging  tendencies may prevent the use of
             optimum  burner staging configuration.   For example,
             attempts to minimize air-to-fuel ratios in the bottom
             levels of  a tangentially fired boiler with down-tilt
             burners  were not  successful because of excessive
             slag build-up on  bottom side-walls and slopes of the
             furnace.

          •   The option to decrease secondary air register openings
             on active  burners to optimum settings while simultaneously
             operating  with wide open settings on "air only" burners
             to achieve maximum NOX emission reduction is not available
             on all boilers.   Most boilers with cell-type burners (2 or
             3 burners  in one  assembly) must operate all burners within
             each cell  at a common register setting, even though one or
             two burners are operated with air only.  In some boilers
             secondary  air register settings are tied in with controls
             in such  a  manner  that they can only be operated in completely
             open,  or fully closed modes.  Other boilers have fixed
             secondary  air register settings.  Many boilers have broken,
             non-operable register mechanical linkages or inaccurate
             register setting  indicators.

5.4  Flue Gas Recirculation

          Flue gas recirculation into the windbox or secondary air ducts
of the furnace combustion has  been shown to be an effective method of
reducing NOX emissions  from gas and oil fired boilers (_4-_6).  One boiler
selected for this test  program, in part because of its flue gas recir-
culation capability,  unfortunately could not be operated in this mode
because of fan blade  erosion during our test period.  Based on theoretical
grounds (_!)  as well as  on actual experience with pulverized coal fired
test rigs (_7), flue gas recirculation is expected to be effective pri-
marily for reducing thermal NOX, and affect fuel NOX formation to a
minor extent only, in  coal-fired utility boilers.

5.5  Burner Tilt

          Tangentially fired boilers are designed with tilting burners
(plus or minus  30° from horizontal) for  superheat steam temperature and
combustion flexibility.  Other generally available operating variables
that can assist  in steam temperature control  are superheat and reheat

-------
                                  - 46 -
 attemperation water sprays,  excess air  level, pulverizer loading patterns,
 secondary air register settings and soot-blower operation.  Thus, burner
 tilt can often be used (within limits)  to  reduce NOX emission levels
 without losing adequate steam temperature  control, although operators
 must be aware of potentially aggravated  slag problems.

           Raising burner tilts above the horizontal (on up fired boilers)
 tends to enlarge the effective furnace  combustion zone, to lower combustion
 intensity,  and lower effective high temperature residence time resulting
 in  reduced NOX emission levels for a given excess air level.  Down-tilt
 tends to reduce the furnace  combustion  zone, increases combustion
 intensity,  and increases effective high  temperature residence time, result-
 ing  in increasing NOX emissions levels  for a given excess air level.  The
 usefulness  of burner tilt as a NOx emission control variable is partly
 offset by the higher excess  air levels  generally necessary with up-tilt
 burner operation.   This higher excess air  is needed to allow for the
 greater flue  gas stratification observed with up-tilt burner operation
 caused by shorter times for  complete mixing and combustion prior to the
 flue  gases  reaching the furnace arch, and  dividing into two streams.  Of
 course,  potential slagging problems, and less flexible steam temperature
 control systems also limit the usefulness  of burner tilt for NOX emission
 control.  From a NOX emission standpoint,  firing with the burners in a
 horizontal or slightly upward tilt appears to give the best results.

 5. 6   Other  Combustion Variables

           The importance of  secondary air  register settings and its rela-
 tionship to the use of other combustion  variables have been discussed
 above in the  low excess air  and staged  combustion sections.  Lowering
 air  preheat temperatures can lower thermal NOx emission within rather
 narrow limits in existing boilers with major steam side redesign required
 for  effecting large changes  in air preheat temperatures.   Pulverized coal
 fineness showed only a minor effect on NOX emissions in the limited
 testing performed on this variable.

          While it  was recognized that other combustion variables such
as burner design and configuration, coal nitrogen content,  and primary
 to secondary  air ratios could have an important effect on NOX emission,
systematic  testing  of these  factors was beyond the scope of the present
study.

          Detailed  results of the field test program are presented in
the following sections of this report.  It should be noted that the
selection of  combustion variables was guided by known theoretical
considerations of  the formation of NOX in combustion processes.   However,
boiler  design and  practical  operating limitations and restrictions
determined  the actual,  detailed program plan for each boiler tested.

-------
                                  - 47 -
5.7  Combinations of Combustion Modifications

          As discussed in considerable detail in earlier Esso studies
on NOX emission control (_l-6), combinations of combustion modification
techniques can be used effectively for this purpose.  Undoubtedly, the
most powerful of these combinations is the use of staged burner firing
patterns in conjunction with low overall excess air for all fossil fuel
types.  This mode of operation results in the combustion of the bulk of
the fuel under reducing conditions, which affects the formation of both
"thermal" and "fuel" NOX.

          Flue gas recirculation into the burner zone is a technique
that by itself suffers from the limitation for coal firing that it
appears to have little effect on "fuel" NOX (_1, _7, &) » because its
principal effect is to reduce the combustion temperature.  Thus, the
relatively temperature-insensitive oxidation of chemically bound nitrogen
is not reduced significantly using this technique.  These comments also
apply to other means of reducing combustion temperature, such as
steam or water injection, or reducing air preheat temperature.  However,
for applications where "trimming" of NOX emissions already controlled
through other techniques is desirable, the use of flue gas recirculation
and steam or water injection should be kept in mind, as they are expected
to have an additive effect on NOX reduction in such cases.  Furthermore,
these techniques can be beneficial for improving boiler operability,
e.g., steam temperature control.  However, steam or water injection of  large
quantities of H20 (on the order of 0.5:1 to 1:1 mass ratio to fuel fired)
reduces boiler efficiency by 4-6%.  For similar reasons of reduction in
boiler efficiency, the use of reducing air preheat temperature is usually
not felt to be attractive for utility boiler applications.

          "Minor" combustion variables (from the standpoint of NOX
emission control) have to be adjusted and optimized for each individual
boiler, based on the broad experience gained with different types of
boilers having different sizes, and fired with the large variety of
coal and other fuel types in the U.S.

-------
                                  - 48 -
                          6.   FIELD TEST RESULTS
          The field  test  results obtained on individual coal fired boilers
under a variety of operating  conditions are presented in four parts.  These
parts consist of gaseous  emission measurements, flue gas particulate
loadings measured upstream of particulate collector equipment,  corrosion
probing data obtained  in  accelerated furnace fire-side water-tube corrosion
tests, and estimated boiler performance.  Gaseous emission data and most of
the particulate emission  data were obtained under normal,  as well as staged
firing conditions.   As discussed before, particulate loadings of the tiue
gas were determined  only  under  conditions corresponding to baseline and
"low NOX" operation,  for  purposes of_comparison on the relative effect of
modified combustion  operation on flue  gas particulate loadings in coal
combustion.  Similar considerations apply to the sustained, 300-hour
corrosion tests, which had as their objective the determination of whether
staged firing of coal  accelerates furnace water tube corrosion rates.

          The gaseous emission  data obtained under baseline and staged
firing conditions  at various  load levels are presented first.  Throughout
this  report, NOX  concentrations are expressed as ppm, adjusted to three
per cent 02  in  the flue gas,  on a dry  basis.

          In addition to  the  results obtained in tests coal fired boilers,
this  section also  presents  the  gaseous emission data on oil-fired units
converted from  coal.

6.1   Coal Fired Boilers

          Test  programs were  conducted on 12 coal fired boilers consisting
of four front-wall fired, three opposed-wall fired, four tangentially fired
and one turbo-furnace  boiler.   Typical cross-sectional diagrams for these
types of boilers are shown in Appendix C.  Table 6-1 lists each boiler by
station and number,  boiler manufacturer, type of firing, full load MW
rating, number  of burners and number of burner levels.  In addition, the
number of operating  test  variables included in each test program and the
number of completed  test  runs are shown.

     6.1.1  Gaseous  Emission  Results for
             Individual Coal Fired Boilers

          The data obtained from the 12 boilers tested are grouped
according to boiler  design type, i.e., front-wall fired, opposed-wall
fired, tangentially  fired and turbo-furnace boilers.

          6.1.1.1  Gaseous Emissions from
                   Front Wall Fired Boilers

          Boilers 1, 2, 3 and 4 are front-wall fired boilers varying in
size from 105 to 320 MW.  Dave Johnston No.  2 and Widows Creek  No.  6 were
designed by Babcock  and Wilcox, while E.  D.  Edwards No.  2  was designed by

-------
                                             TABLE 6-1
SUMMARY OF COAL FIRED BOILERS TESTED


1
2
3
4
5
6
7
8
9
10
11
12


Station and
Boiler No.
Dave Johnston
Widows Creek
E. D. Edwards
Crist
Leland Olds
Harllee Branch
Four Corners
Barry
Naughton
Barry
Dave Johnston
Big Bend



2
6
2
6
1
3
4
3
3
4
4
2


Boiler
MFG.
B&W
B&W
R-S
FW
B&W
B&W
B&W
C-E
C-E
C-E
FW
R-S


Type of
Firing
FW
FW
FW
FW
HO
HO
HO
T
T
T
T
Turbo


MCR
(MW)
105
125
256
320
218
480
800
250
330
350
348
350


No. of
Burners
18
16
16
16
20
40
53
48
20
20
28
24

No. of
Burner
Levels
4
4
4
4
3
4*
6**
6
5
5
7
1


Test
Variables
3
4
4
4
3
4
5
4
6
7
7
4

No. of
Test
Runs
14
41
19
22
13
51
26
8
26
46
6
14
286
 *  Two levels of burner cells with two burners per cell.
**  Two levels of burner cells with three burners per cell.

-------
                                  - 50 -
Riley-Stoker, and Crist No. 6 was designed by Foster Wheeler.  All four
of these boilers have  four levels of burners.  Widows Creek No. 6 boiler
will be discussed first since it was tested in most detail being the
first boiler  studied in this program.

                6.1.1.1.1  Widows Creek, Boiler No.  6

          Tennessee Valley Authority's Boiler No. 6 at the Widows Creek
Station was the first  boiler tested in our present study.  Thirty-two
short-term  test runs were made  in a statistically design optimization
program, to minimize NOX emissions.  These tests were followed by two
sustained runs, one at full load, the  other one at reduced load, with the
optimum staging patterns.  The  sustained corrosion probing run was
deferred at TVA's request, until high  sulfur coal could be fired, and
other data  become available to  show that staged firing would not cause
abnormally  high furnace corrosion rates.

          Widows Creek Unit No. 6 is a 125 MW, 16-burner, front-wall,
pulverized  coal fired  Babcock and Wilcox boiler.  It has a single dry-
bottom furnace  with a  division  wall, and the 16 burners are arranged
with  four burners in each of four rows.  Each row is fed with coal by
a  separate  pulverizer.

          The statistical test  design  shown in Table 4-1 for this boiler
has been discussed  in  Section 4.1.3.   The detailed operating and emission
data  are listed in Table 1 of Appendix A.  The NOX emission data,
expressed as  ppm NOX corrected  to three per cent oxygen in the flue gas
(dry basis) obtained with the various  firing patterns tested are sum-
marized in  Figures 6-1 and 6-2.  In Figure 6-1, the measured emissions are
plotted vs. per cent of stoichiometric air to the active burners.
Figure 6-2  shows the same emission data, but plotted as a function of the
overall per cent stoichiometric air.  Least squares regression lines have
been fitted to  the data points  corresponding to various firing patterns
designated  as "S".

          Actual baseline NQx emissions  (full load, normal firing with
60% open secondary  air registers) averaged 634 ppm at 18% excess air.
(For  comparison purposes  it should be  noted that the baseline NOx emis-
sion  level  at 120%  stoichiometric air  calculated from all normal firing,
full  load runs  is equal  to 666  ppm.)   Each of the four operating variables
included in the experimental plan, i.e., excess air level, load, firing
pattern and secondary  air register setting had a significant effect on
NOX emission  levels, and  are discussed in turn below.

          Low excess air operations consistently reduced NOx emission
levels as shown by  the least sqaure regression lines plotted in  figures 6-1
and 6-2.  A 10% reduction in stoichiometric air to active burners
reduced NOx emissions  by  25% under full  or reduced  load, normal  firing

-------
                                     - 51 -
                                 FIGURE 6-1


                 PPM N0x (3% Oo, DRY) VS % STOICHIOMETRIC
                 	AIR TO ACTIVE BURNERS	

                       (WIDOWS CP*:EK, BOILER NO. 6)
                          I	
                                   T
                     T
   700
	1	

- 125 MW
                                                            - 110 MW
   600
         S. , (80 - 110 MW)
          4-7
£2
CQ
   500
8

 eg
O


G-
 i

O*
fc
   400
   300
   200
   100
' a2 3 ~
_

1 1 1
Symbol
O
A
A
D
B

firing
Pattern
(Active /Air)
Sj (16/0)
S, (14/2)
So (H/2)
83 (14/2)
S5_7 (12/4)
S4" (12/4)
1
Gross
Load
125
110
125
125
110
110
J 	


	 1 	
     80
               90
100
                                  110
                                            120
                             130
                                                               140
            AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                                       - 52 -
                                  FIGURE 6-2



                            PPM NOx (3% O2, DRY) VS

                          OVERALL STOICHIOMETRIC AIR


                          (WIDOWS CREEK ,  BOILER NO. 6)
£2
CQ
O

eP
oo
i
    700
    600
n  500

g
400
    300
                                              S., - 125 MW
                                             O
                                                         25 MW
                                          O
                                                           sl- no
                                                   .83 - 125 MW
                                                             S4_? - 110 MW
    200
     100
      0
        80
Symbol






O
•
A
A
D
•
Firing
Pattern
Sl
Sl
S2
S3
S5-7
S4
— ... 1
Gross
Load - M\
125
110
125
125
110
110
             90
100
110
120
130
140
                           OVERALL STOICHIOMETRIC AIR

-------
                                  - 53 -
operation.  The same percentage reduction  in stoichmetric air under staged
firing reduced NOx emissions by an average of 24% at full load and 28%
at reduced load.  The lowest practical  level of excess air was dictated
by acceptable CO emissions and stack appearance.

          Reducing load from 125 to 110 MW (12% reduction) with normal,
16 burner firing resulted in little change in NOX emission levels since
the average excess air level was raised during low load operation.
However, when operating at equal excess air levels (say 20% overall
excess air) a 12% reduction in load resulted in a 20% reduction in NOX
emission levels under normal firing as well as under staged firing
conditions.

          Staged firing had a statistically significant effect on NOX emis-
sion levels under both full load  (14% NOX  reduction) and reduced load operation
(27% NOX reduction).   At full load, staging pattern 83 (top row wing
burners on air only)  consistently produced lower NOX emission levels
than staging pattern S2 (bottom row wing burners on air only) as shown
by their least square regression lines of Figure 6-2.  At reduced load,
staging pattern 84 (top row of burners on air only) resulted in the
lowest NOX emission levels.  The combination of low excess air and
staged firing reduced NOX emissions by 40% at full load, and from 33 to
50% at reduced load.   The optimum combination of operating variables
reduced NOX by 46% at full load and by 53% at reduced load compared to
full load, baseline emission levels.

          Opening the secondary air registers resulted in a small (5%)
but statistically significant reduction in NOX emissions when firing
coal in all burners.   When firing at full load with two burners on air
only, no significant  change in average NOX emissions resulted from changing
secondary air registers.   However, closed down secondary air registers
consistantly resulted in lower NOx emissions (average of 14%) during staged
firing operation with four burners on air only.  This improvement can be
explained by improved mixing of fuel and air with less CO formed as well
as less air to active burners since a higher proportion of air will be
diverted to the open  top burners.

          The data shown in Figure 6-1 call attention to an apparent
anomaly.  A cursory inspection of the data would indicate, that while
as expected NOx levels decrease with decreasing air supply to the active
burners, staging the  burners could result in higher NOX emissions than
normal operation at the same burner air/fuel ratio.  A refined method for
estimating the actual air/fuel ratio at each burner for each staged firing
pattern can explain this anomaly.  Since this method applies to other wall
fired boilers, a specific example will be used here to briefly explain the
method.

          Staged firing pattern,  84,  (top row of 4 burners on air  only
and the bottom 3 rows firing coal)  at 20% overall excess air results
in an average % stoichiometric air to each of the 12  active  burners  of

-------
                                   - 54 -
90%  i.e., air  to  coal = 120/16  to  100/12.   (Since 120% air is divided
^o'ng  16 burners  while 100% of  the coal  is  divided among the 12 active
burners.)   However,  some of the air from the  inactive top row of burners
mixes  with  the partially unburned  coal/air  mixture from row B (less  than
5  feet below)  raising the actual % stoichiometric air ratio above  the
90%  for the bottom two rows (12 and 17 feet below) .  Based on visual
observation of flame patterns during staged firing and simplified
calculations it appears that a one-third mixing efficiency for the top
row  air with the coal-air mixture  is a reasonable estimate.  Table 6-3
presents the calculations to bring actual NOX emission data in agreement
with those  calculated by extrapolating from unstaged levels.

           Figure 6-3 presents the  least  squares regression lines cal-
culated for the six test runs (shown as  circles) made at full load with
normal firing, as well as for the  six test  runs  (shown as squares) made
using staged firing pattern 84.  The actual ppm NOX emissions for  the
six  S4 runs are also plotted (as hexagons)  vs. the "effective" % stoichio-
metric air.  Run No. 24 NOx results fall 13%  below their "expected"  value
due  largely to the low load (89 MW vs.  the  104 MW average of other five
runs)  for this run.  It should also be noted  that each of the "expected
ppm  NOx" points plotted against the "effective" % stoichiometric air
would fall on, or very close to the extrapolated Si regression line.
Thus,  we can estimate the maximum NOX reduction if NO-ports were added
to this boiler (at a sufficiently high  elevation so that very little air
would be mixed with the primary flame front). At 120% overall excess
air  Si produces 667 ppm NOX, 84 produces 370  ppm, while  true  2-stage
combustion would approach 222 ppm NOX emissions.

                6.1.1.1.2  Dave Johnston, Boiler No.  2

           Boiler number 2 of the Dave Johnston Station of the Pacific
Power and Light Company is a Babcock and Wilcox designed, front wall
fired, single furnace boiler with a maximum continuous rating of 102 MW
gross load.  Six pulverizers feed 18 burners  arranged in four rows with
3 burners in the top row and 5 burners  in each of the other  three  rows.
 (Figure 6-4 shows the mill-burner configuration.)  The 18 burners  in this
unit are of the circular register type which  imparts a spinning action  to
 the  secondary air stream.

           Detailed operating and emission data are summarized in
Table 2 of Appendix A.  Table 6-5 indicates the experimental design  of
operating variables with average flue gas measurements of % oxygen and
ppm NOX (3% 02, dry basis) shown for each of  the 14 runs completed on
 this boiler.  Operating variables were  firing pattern, secondary air
register settings on coal mills not firing coal, and excess air level.
Gross load was maintained near full load for  all test runs due  to  a
 tight load demand during the test period.  Number 12 mill feeding  the

-------
                                  - 55 -
                                TABLE 6-3

               CALCULATION OF EXPECTED NOX EMISSIONS FROM
                 % STOICHIOMETRIC AIR TO ACTIVE BURNERS

Burner
Row

A (Top)
B
C
D
TOTAL

Coal
%

0
33.33
33.33
33.33
99.99

Air
%

28. si
30. 5j
30.5
30.5
120 ^

A/C
%

[1]
120
91.5
91.5
100.7[4]
Expected
NOX, ppm
(E)
[2]

667
222
222
370
Actual
NOX, ppm
(A)
[3]




369

%
Difference

i
A - E
i nn
A


-0.3%
[1]  Assumes 1/3 of air from Row A mixes with Row B.
[2]  Calculated from S;L Regression Equation:  PPM NOX = -1205 + 15.6
     (% Stoichiometric Air).
[3]  Calculated from 84 Regression Euqation:  PPM NO  = -1026 + 15 5
     (% Stoichiometric Air).                        X
[4]  Average "Effective" % Stoichiometric air to active burners.
[5]  Assumes 5% primary air and 95% secondary air.
          Similar calculations have been made for each run with staged
firing pattern 84.   The results are listed in Table 6-4, and plotted
in Figure 6-3.
                                TABLE 6-4

           CALCULATION OF  EXPECTED NOX EMISSIONS FROM AVERAGE
           "EFFECTIVE" % STOICHIOMETRIC  AIR TO ACTIVE BURNERS

Run
No.
13
20
24
26
26Ai
26A3
% Stoichiometric Air
Overall
126
116
126
114
115
113
To Active
Burners
94
87
94
86
86
85

"Effective"
106
98
106
96
97
95

Expected
PPM NOX
449
319
449
297
308
277

Actual
PPM NOX
460
345
399
297
299
290
% Diff.
( A - E\
V A )
+3
+8
-13
+9
-3
+4
Gross
Load
(MW)
110
108
89
99
99
103

-------
                                      - 56 -
                                  FIGURE 6-3

              PPM NO  (3% O2, DRY BASIS) VS % STOICHIOME TRIG AIR
                       ACTIVE BURNERS FOR Si AND 84 RUNS
   800
   700
   600
03
i-^
02
g
 CM
o
   500
   400
i
                 I
84 - Regression Line
 (y= -1026+ 15.50x)
   300
   200
   100
                                                     S1 - 125 MW Regression Lin
                                                    /(y = -1205 + 15.59x)
Firing
Symbol Pattern
A
D
O
si
S4
S4
% Stoichiometric
Air to Burners
Actual
Actual
"Effective"
       80
      90
100
110
120
130
140
              AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                     FIGURE 6-4
500
CO
OT
« 400
g
CT
65 30°
£2-
0*
& 200
100
0
8
PPM NOx (3% O2, DRY) VS % STOIC HIOME TRIG
AIR TO ACTIVE BURNERS
(DAVE JOHNSTON, BOILER NO. 2)
1 1 1 1 1 1
Normal Firing:
~~ 15 Burners Fir
12 Burners Firing /

ing-

S r(Tr
Staged Firing: ft m'®(^ *2 Burners FirinS
— Under and Over Ss^ Ju ^
^** Fire Air ^ /©
H©_^^S© a ^ t 	 ,
J2^"^ ® H^ Air Only
-H^ .It © 1 Coal + Air
BS(£) ^ ^
^ ,_ i ^H No Coal or
^^ (2) 51^ ^^*
uX- uver I ire Air vjniy Mi^| _ p1irnpr
~* Xffe") Configuration
© © ©
(jo) (T) (\o) (?)
© © ® ©
(?) (9) (iT) (7)
1 1 1 1 1 ^ | ^ 	 ^-^ | ^ 	
0 90 100 110 120 130 140
Air

©
©
©

AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                                  - 58 -








                                 TABLE 6-5




          EXPERIMENTAL DESIGN WITH % 02 AND PPM NOX (3% 02 BASIS)




                       (Dave  Johnston,  Boiler No. 2)
Firing Pattern
FI - No.
12 Pulverizer
Off
15 Burners
Firing
F2 - No.
11 and
12 Pulverizers
Off
12 Burners
Firing Coal
F~ - No. 12 &
10 Pulverizers
Off 12 Burners
Firing ~oal
Secondary Air
Registers
No. 12 Pulv.
Closed
No. 12 Pulv.
Open
Nos. 11 & 12
Closed
No. 11 Closed
No. 12 Wide Open
No. 11 Open
No. 12 Closed
No. 11 Open
No. 12 Open
No. 10 & 12
Closed
No. 10 Closed
No. 12 Open
No. 10 Open
No. 12 Closed
No. 10 Open
No. 12 Open
Staged
Pattern
Si
S2
Sl
S3
S4
S5
Sl
S6
S7
S8
Load: 98 to 106 MW
A^-Normal
Excess Mr
(3)*
U; 5.0% 02
454 ppm NOx
(11)
<*> 4.3
450
(8) 4.6
347
(9)
(10) 4.6%
358
(13) 5.2%
438



A2~Low
Excess Air
(4) 4.3
409
(12)4.1
314
(7) 3.7
413
(2) 4.2
284
(6) 3.3
362
(5) 4.0
311

(14) 4.7
270
(15) 5.3
326
(16) 5>2
214
*  Numbers  in parentheses are test run numbers.

-------
                                  - 59 -
top row of burners was down during the entire test period due to mechanical
problems.  Special advantage was taken of the wide range of firing pat-
terns available at full load by testing 10 different combinations of coal
mills off, with open or closed secondary air registers.

          Figure 6-4 is a plot of ppm NOx vs average % stoichiometric
air to the active burners.  The data points have been plotted as symbols
indicating visually the various firing patterns tested.  Solid lines
have been drawn through the data points with similar operation to show
the strong influence of excess air level.

          Five test runs were conducted at about full load without staged
air admission, except the small amount going through the secondary air
registers to cool the "off" burners.  Runs 1 and 7 were operated with
mills 11 and 12 off; run  3 and 4 were operated with number  12 mill off
and run 12 was conducted  with mills  10 and 12 off.  NOX emission levels
(corrected for excess air level) were highest for runs 1 and 7,
intermediate for runs 3 and 4 and lowest  for run 13.  These results
are in agreement with past operating experience and theory.  Runs 1 and
7 were conducted with only 12 active burners (therefore at a higher firing
rate of coal per burner)  compared to 15 active burners in runs 3 and 4.
Of more importance, runs  1 and 7 had cooling air flowing through burners
at a lower elevation, counter balancing the beneficial effect of adding
cooling air through 3 top burners, and in run 13, cooling air was added
through 6 top burners to aid in reducing NOX emission levels.  Actual
full-load baseline, NOx emissions were 454 ppm.

          Seven different staged firing patterns were tested with very
instructive results.  The five staging patterns operated with secondary
air admitted through top burners listed in the order of decreasing NOX
reduction efficiency were:  SQ top two mills on air only (214 ppm); S/-,
top mill on air only, bottom mill off (284 ppm); $2 top mill on air only
(314 ppm); and Sy, top mill off with cooling air and next to top mill on
air only  (326 ppm).  The two staging patterns with secondary air admitted
through both top and bottom burners were:  85, top and next to bottom
mills on air only (311 ppm)  and 85,   top mill off with cooling air only
and next  to bottom mill on air only  (362) .  Table 6-6 lists these low
excess air, staged runs with ppm NOX, % 02 and average % stoichiometric
air to active burners (calculated and adjusted bases) to allow comparisons.
These results clearly demonstrate the importance of maximizing secondary
air admission through top burners, providing minimum % stoichiometric air
to active burners and minimizing the additon of secondary air through
inactive bottom burners.  (In other words, "overfire" air staged operation
is preferred to "underfire"  air firing modes.)

          Analysis of these results  are greatly simplified  (as shown by
Figure 6-5) when  the calculated average % stoichiometric air is made more
realistic by adjusting directionally for  the "cooling" air  that enters
the furnace through  the "closed"  secondary registers of burners of "off-
mills".   If the closed registers are within the top  two burner rows

-------
                                 - 60 -
                                TABLE  6-6
               SUMMARY  OF LOW EXCESS AIR, STAGED TEST RUNS
Staged Firing Pattern
Mills Off and Secondary
Air Register Position
Overfire Air
S0 - 12 Open, 10 Open
o
S& - 12 Open, 10 Closed
S3 - 12 Open, 11 Closed
S - 12 Open
S7 - 12 Closed, 10 Open
Over & Under- Fire Air
S - 12 Open, 11 Open
S, - 12 Closed, 11 Open
Run
No.
16
14
2
12
15
5
6
N0x
PPM
214
270
284
314
326
311
362
°2
%
5.2
4.7
4.2
4.1
5.3
4.0
3.3
i
% Stoichiometric Air
To Active Burners
Calculated
[1]
88
102
99
102
106
82
94
Adjusted
[2]
88
99
102
102
103
82
91
ri]  Calculated  as:   %  Total Air x No- of Burners Firing Coal	
                      No.  of Burners Firing Coal plus No. of Burners on Air Onl]


[2]  Adjusted for estimated "cooling" air.  Deduct 3% from calculated
     % Stoichiometric air for overfire "cooling" air and/or add 3%
     for underfire "cooling" air.

-------
                                  - 61 -
("overfire" cooling air) the calculated % stoichiometric air is reduced
by 3%.  For underfire air (No. 11 mill off) the adjusted % stoichiometric
air is obtained by adding 3% to the calculated % stoichiometric air.
Figure 6-5 shows that all of the test run data are closely clustered around
three least-squares regression lines:  normal firing, 7 = -82 + 4.95x; and
staged "overfire" air, y = -436 + 7.30x.  Each of these three operating
methods reveals a strong (64 to 88%) relationship of excess air level with
ppm NOX emissions after adjusting for "cooling" air.  The displacement of
the staged firing regression lines from the extrapolated normal firing line
can be accounted for by the mixing of "overfire" (or "underfire" air) into
the burning air cool mixture from the next level of burners as shown for
the Widows Creek No. 6 boiler.  For example, the average "effective"
stoichiometric air levels in test runs No. 5 and 12 are 107.4% and 107.3%,
respectively, which produce expected NOX emission of 317 ppm  (from normal
firing equation:  y = -422 + 7.07x) compared to actual emissions of 311 and
314 ppm, respectively.

          To summarize the results from this boiler, emphasis was placed
upon the use of a wide variety of full load, staged firing combinations.
From baseline NOX emissions of 454 ppm, low excess air, staged operation
reduced NOx to as low as 216 ppm with a slightly darkened stack plume.
Other staged firing patterns resulted in 275 to 320 ppm NOX with no
degradation of the plume.  Excess air levels showed a strong  influence
on NOX emission levels in general agreement with previous experience on
wall fired boilers.

               6.1.1.1.3  E.  D. Edwards,  Boiler No,  2

          Boiler No. 2 at the E. D. Edwards station is a Riley Stoker
Corporation, front-wall fired, pressurized, single furnace boiler.  It
was designed for a maximum continuous rating of 1,870,000 pounds of
steam per hour with a superheater steam outlet pressure of 2600 psig
at 1005°F.  The furnace is fired with 16 burners (4 rows of 4 burners)
and has dimension of 46 feet width, 30 feet depth, a furnace volume of
155,600 cubic feet and a furnace envelop of 37,700 square feet effective
projected radiant surface.

          A summary of the operating and emission data for each test
run is  contained in Table 3 of Appendix A.  Table 6-7 below indicates
the experimental design of operating variables with average flue gas
measurements of % 02 and ppm NOx  (3% 02, dry basis) shown for  each
short-period test run.  Almost all of the  planned test runs shown were
completed.  Runs 21 and 22, peak load runs, could not be achieved during
the hot summer  testing period.  Two special, long-period fluctuating
load  (load  determined by industrial demand) runs were made under the
operating conditions specified for runs 7  and  9.  These runs,  identified
as  7A and 9A, were conducted  in order to determine how NOX emissions
produced  during varying load  conditions would  compare with the emission
data  obtained under steady-state  short-period  test runs.  The  analysis
of  the short-period test run  results will  be discussed first,  followed
by  that of  results  from the two special runs.

-------
                       - 62 -
                   FIGURE 6-5
PPM NOx (3% O2, DRY) VS ADJUSTED* AVERAGE
% STOICHIOMETRIC AIR TO ACTIVE BURNERS
(DAVE
sni
1 1
^
HH
<; Staged
JOHNSTON, BOILER NO. 2)
1 1 1 1
* Normal
(TXi) Firine
Firing: xV^J
•H AM Under + Over Fire Air J2)©
tf
Q x
£a Q^X^^
- 300- ^©
o*
s >
^ 20(_ ® /
IOC-


C 1 1
70 bO 90
^ S
^
Over Fire Air /
(i\X S
sffl /-\fR\m 5 and Run 12
/^ / Calculated from _
(J4) 0 "Effective" Stoich. Air
X^x
—
* + or - 3% Adjustment for
"Underfire" or "Overfire" ~
Cooling Air
1 1 1 J
100 110 120 130 14
                                                           0
ADJUSTED % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                            EXPERIMENTAL DESIGN WITH PPM NOy  (3% 02 BASIS) AND  %  02
                                         (E. D. Edwards, Boiler No. 2)
Burner
Firing
Pattern
sr
Normal
Firing
Pattern
S2-
AOOA
0000
0000
0000
S3-
OAAO
0000
0000
0000
AAAA
0000
0000
0000
S5-
AOOA
OAAO
0000
0000
Secondary
Air
Register
Setting
R1 - 50%
Open
R2 - 20%
Open
R-L - 50%
Open
R2 - 20%
Open
RX - 50%
Open
R2 - 20%
Open
^ - 50%
Open
R2 - 30%
Open
R-L - 50%
Open
R2 - 30%
L -280 MW
A^-Nor .
Air
(21)









A2~Low
Air
(22)









L2-260 MW
A^-Nor .
Air
(1) 670
3.2% 02
(3) 770
3.1% 02
(5) 644
3.8% 02
(9) 625
*3.9% 02
(11) 609
3.8% 02
(7) 401
7.5% 02




A2-Low
Air
<2) 556
1.5% 02
(4) 692
1.8% 02
(10) 474
2.0% 02
(6) 359
1.6% 02
(8) 524
2.7% 02
<12) 382
*2.1% 02




L3-220-240 MW
A^-Nor .
Air






(13)535
4.9% 02
(17)
(19)
(15)
A2-Low
Air






(18)386
3.5% 02
(14)310
4.4% 02
<16)336
2.8% 02
(20)295
3.0% 02
L.-210 MW
A^-Nor .
Air
(23) 667
4.2% 02









A2-Low
Excess Air
(24) 516
1.6% 02









                                                                                                                    CO
                                                                                                                     I
*  Secondary air registers 30% Open.

-------
                                  - 64 -
          Table 3 Appendix A contains a summary of operating and emission
data for the 20 short-period test runs completed on this boiler.  Operating
variables were gross  load, excess air level, firing pattern and secondary
air register setting.  The maximum gross load tested was 256 MW (vs full
load of 260 MW) with  normal and staged firing, while the minimum load
tested was 204 MW using  a normal firing pattern.  Excess air levels
were set at normal  operating levels or at the minimum level as established
by maximum acceptable CO measurements in the flue gas.  Five firing
patterns were tested; normal firing with all 16 burners in operation, two
staged firing patterns with two burners on air only, and two staged
firing patterns with  4 burners on air only.  Secondary air registers were
set normally  (45-50%  open) or closed down to a 20 or 30% open position.

          Each of the four operating variables showed a significant
independent effect  on NOX emission rates and some significant two variable
interaction effects were also apparent.  Figure 6-6, a plot of average
ppm NOx vs %  stoichiometric air to active burners (all short period test
runs) has been prepared  to show the relationship between NOx emissions
and excess air levels for various load, staged firing, and secondary air
register setting test conditions.

           Full load,  baseline NOx  emissions were  703  ppm.   Reducing  load
 to 212 MW (16% reduction)  resulted in a NOx emission  reduction of  5%
 (to 668 ppm).

          Reducing  excess air levels while holding other variables con-
stant  consistently  resulted in lowering NOX emissions, as shown by the
least  squares  regression lines drawn through data points representing
similar  types  of  operation in Figure 6-6.  The change in ppm NOX emission
with a 10% stoichiometric air reduction varied between 130 and 200 ppm
and agrees well with  other wall type boilers tested.

           Secondary air  register settings also showed a strong  influence
on NOx  emission  levels.  During normal firing of all burners, closing
down dampers  (20%  open instead of  50%) increased NOX  emissions by  116 ppm
 (664 to  780)  or  about 17% when firing with 3% 02 in the flue gas.  This
increase  in NOx  emissions  is  to be expected due to the greater  turbulance
and higher peak  flame temperatures associated with increased secondary
air velocity  at  the burner.   However during staged operation,  closed
down dampers  consistently produced lower NOx emissions than operation
with normal  damper  positions.  With  closed down dampers during  staged
firing  it was generally possible to  reduce excess air levels to  a  lower
level without  exceeding the maximum  permissible CO levels,  and  thus,  lower
NOX levels were  reached  with  this  type of operation.  Another explanation
for this phenomenon is that a lower percent of stoichiometric air is
introduced to  the  fuel rich burners when the air registers are pinched
to  20-30% open because the flow restriction upsets the balance to each
burner.  Therefore  a  boiler operating at 0.9 stoichiometric ratio with
all registers  at  50%  open may actually reach 0.85% stoichiometric ratio
when the registers  are closed to 20% open.

           Staged firing operation  resulted  in  lowered NOx emissions,  and
as  previously experienced,  the  combination  of  low excess  air and staged
firing showed further improvement.   The  average ppm NOx emissions  for
the four  test  runs  each with  normal  firing,  staged  firing  82,  and

-------
                                       - 65 -

                                  FIGURE 6-6

                  PPM NOx (3% O2, DRY) VS % STOICHIOMETRIG
                 	AIR TO ACTIVE BURNERS	

                 (E. D. EDWARDS, BOILER NO. 2,  FIRING COAL)
               T
  800
  700
2 600
s
  500
  400
  300
  200
  100 -
    0
                 	1	1	
                 Normal Firing
                   % Open Secondary Air - Gross
                   Load   20% - 255 MW
                     .  50% - 250 MW
                     /
                                                        50% - 210 MW
                                     20% - 250 MW
          (je) 50% - 220
                   (—.30% 230 MW
          30% - 220 MW
   Burner
Configuration
                           o
             0
                                      ©
.firing Pattern
Symbol Burners - Air Onl
OS1
AS2
VS3
DS4
0S5
None
1,4
2,3
1,2,3,4
1,4,6,7
               J.
     80        90       100        110       120        130        140

            AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                                  - 66 -
 staged firing 83, were 670, 526, and 479, respectively, indicating an
 average emission of reduction of 22% using 82 (top wing burners off) and
 29% using 83 (top middle burners off) compared to normal firing conditions,

          As mentioned before, test runs 9A and 7A were conducted in
 order to obtain a comparison of NOx emissions levels under normal, load
 varying conditions to steady state conditions.  Run 9A operating condi-
 tions were similar to steady state run 9, i.e., normal excess air, staged
 pattern 2 (top wing burners on air only) and secondary air registers
 closed down to 30% open; however, the load was allowed to follow its
 normal industrial pattern.

          Figure 6-7 is a plot of ppm NOX emissions vs % 02 measured in
 the flue gas for individual measurements of probe 2 and 3, or 1 and  4
 gas composites taken during test run 9A.  Also shown is the average NOX
 and 02 measurements of run 9.  During most of the four and one-half
 hour period of this run the load was steady at 255 MW with two short
 periods at 230 to 235 MW.  Thus, the NOX emissions compared very well
 with the results of test run 9 obtained 7 days earlier.

          Test run 7A operating conditions were similar those of  run 7,
 except that the secondary registers were only closed to 30% open  (vs
 20% open for run 7) and in addition the load was allowed to vary with
 industrial load demand from 200 to 260 MW.  Figure 6-8 is a plot of
 individual NOx vs 02 measurements for run 7A.  For comparison purposes,
 average results obtained under similar staged firing pattern 3  (middle
 top row burners on air only) are also shown as circled run numbers.
This plot indicates that the variation of NOX emissions during run 9A
were largely (77%)  related to changes in excess air level as shown by
 the solid least-squares line.   Test runs 8 and 11,  (operated with 50%
open secondary air  registers)  are above the regression line, while test
run 7 operated with 20% open secondary registers is considerably below
 the regression line indicating the importance of register settings.

          To sum up,  four operating variables were included in the
experimental test program of 20 short-period test runs completed on
boiler No.  2 at the E.  D.  Edwards Station.   Changes in gross load,
excess air level, firing pattern and secondary air  registers produced
 significant changes in NOx emission levels.  Base line emission levels
 of about 703 ppm NOX were reduced to between 360 and 380 ppm under low
 excess air, staged  operation with closed down secondary air registers
 at about full load.  Reduced load, low excess air - staged operation
with closed down secondary air registers resulted in further reductions
 to about 300 ppm.  Two normal excess air staged firing runs with gross
 load varied according to load demand produced NOx emission levels close
 to those predicted  from steady-state test runs, with most of the
 variation in NOx emissions due to changes in excess air level variation.

-------
500
                                - 67 -
                            FIGURE 6-7

          PPM NOX (3% O2 BASIS) VS % OXYGEN IN FLUE GAS
              (RUN 9A, E. D. EDWARDS, BOILER NO. 2)
CO
I—I




tf


 e-;
O

CO
400
300
200
O
100
  0
    0
                   % O2 MEASURED IN FLUE GAS

-------
                                     - 68 -
                               FIGURE 6-8

                    PPM NOx VS % OXYGEN IN FLUE GAS
                  (RUN 7A, E. D. EDWARDS, BOILER NO. 2)
500
                                                      Probes Sampled
                                                         1 and 4
                                                         2 and 3
                                                         land 2
                                                         3 and 4
                                                Circled Numbers
                                                Indicate Run No. Averages
  0
                                                              6
                            OXYGEN IN FLUE GAS

-------
                                     - 69 -
                6.1.1.1.4   Crist  Station,  Boiler No.  6^

           Crist Station Boiler number  6  is  a Foster  Wheeler  designed,
 front wall fired single furnace  boiler,  with a maximum continuous  rating
 of  320 MW  gross load.   The pressurized furnace has 16 burners  arranged
 in  four  rows of four burners  each.   Superheat and reheat  steam temperatures
 are 1000°F at pressures of 2484  psi  and  569 psi respectively during  full
 load operation.

           A cooperative test  program by  Gulf Power,  Foster Wheeler and
 Exxon, coordinated by EPA,  was planned for  this unit.   Plans included
 short-term firing pattern optimization runs for  minimizing NOX emission,
 accompanied by  boiler performance tests  by Foster  Wheeler,  followed  by
 boiler operability check-out  at  "low NOX",  then  a  sustained  300-hour
 test under low NOx" and  baseline operating conditions for assessing
 corrosion  problems, and an optional  long-term test period of about 6 months
 for determining actual  furnace water tube wastage.   Because  of load
 demands  on this  boilei., however,  it  has  been possible only to  explore
 firing patterns  in short-term runs only  for minimizing  NOX.

           Table  4 of Appendix A  contains  a  summary of the operating
 and emission data subdivided  into  the  "A" and "B" sides of the boiler.
 The flue gas stream leaving the  furnace  is  split into two ducting  paths,
 and although the boiler operator  and manufacturer could at times achieve
 02  balance  in the two sides,  the NOx levels measured were clearly  higher
 for the "A" side than the  "B" side,  with  all firing  patterns tested.   The
 reason for  this  difference  is not  completely understood at present,
 although it may be related  to differences  in air flow,  and uncertainties
 of  the air damper settings on the two  sides  of the boiler.*

           To simplify the presentation and  to facilitate  comparison
 with other boilers,  Hgure 6-9 is based on  the average  of duct A and duct B
 results.   Table 6-8  presents the experimental! design with %  oxygen and
 ppm NOX for each test run on duct A, duct B  and the  ooiler average.
 Operating variables  tested were load,  excess  air level  and firing patterns.

          Reducing load  from 320  to 270 MW  (16%  reduction) resulted in
 lowering NOX from 845 to 794 ppm (6% reduction)  for  normal firing operation.
 Reducing excess  air levels had a significant effect  on  NOX emission  levels
 under both normal and staged combustion operation as shown by  the  least
squares  regression lines of Figure 6-9.  Staged  firing also resulted  in
 significant reduction in NOX from the  832 ppm experienced during baseline,
 full load  operation.   The 320 MW staging pattern S3  (middle  top row burners
   Foster Wheeler has indicated a possible cause of the side to side
   differences as attributable to three burner-register assemblies which
   were replaced on the "A"  side prior to the test series.   These registers
   have a different register assembly which might have resulted  in different
   air flow characteristics.

-------
                                         - 70 -
                                   FIGURE 6-9




                   PPM NOx (3% O2, DRY) VS % STOICHIOME TRIG

                   	AIR TO ACTIVE BURNERS	




                              (CRIST, BOILER NO. 6)
    900
 en 800
 i—i
 OT


 CQ




 1
o

££>
  -
   600
PH
                                                5 MW
                                 ,S1 - 315 - 350 MW
                       MW
500


400,

300
D / A
/S4 - 270 MW




1 1
Symbol
O S1
• Sl
A S2
A S3
D S4
•S5
1
Burners
On Air
Only
None
None
1, 4
2,3
1, 2, 3, 4
2, 3, 5, 6
1
(jross
Load
(MW)
315-350
270
320
•620
270
270
1



_

1
      80
90
100
110
120
130
140
              AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                                                     TABLE 6-8
                              TEST PROGRAM EXPERIMENTAL DESIGN - CRIST. BOILER NO. 6
                  (Run No., Average % Oxygen and PPM KOX (3% 02,  Dry Basis)  Measured in Flue Gas)

le>--^ Fir±ng
£rW<«5»
Operating
70%
Open
Idle
0%
Open
70%
Open
L -350
MW
A^Nor.
Exc Air
sr
(26)
3.4-898
2.9-743
3.2-820
(26B)
3.2-888
3.5-801
3.4-844

L2 - 315 - 320 MW
A -Normal Excess Air
sr
(i)
3.6-902
3.6-799
3.6-850
(1R)
3.4-916
3.0-765
3.2-840

V

(2)
4.7-946
4. 7-872
4.7-909
(3)
2.3-724
3.4-631
2.8-678
S3-

(5A)
3.1-728
3.6-657
3.4-692
A--Low Excess Air
sr
(6)
2.4-804
2.4-630
2.4-717
(6R)
2.6-862
2.1-660
2.4-761

V

(7)
2.0-788
2.6-565
2.3-676
(8)
1.9-772
4.5-591
3.2-682
(8R)
3.1-738
2.2-526
2.6-632
S3-

(4)
1.4-516
4.0-546
2.7-531
(5)
0.9-532
3.2-620
2.0-576
(10)
1.8-566
2.2-522
2.0-544
(10R)
3.5-802
3.0-593
3.2-698
L3 - 270 MW
Ai-Nor.
Exc Air
sr
U1R)
3.7-840
3.9-748
3.8-794

A^-Low Excess Air
V
(14R)
2.0-754
2.2-640
2.1-697

V
(15A)
2.6-643
2.3-416
3.0-530
(16)
3.8-661
3.7-411
3.8-536
(16R)
1.8-560
4.5-472
3.2-516
V

(25R)
3.1-647
3.1-484
3.1-566
Code for Data in Cells
                       (26) - Test Run Number
                            3.4% 02 - 898 ppm NOX - A Duct
                            2.9% 02 - 743 ppm NOX - B Duct
                            3.2% 02 - 820 ppm NOx - Average

-------
                                  - 72 -
on air only) produced better results (reduction to 526 ppm NOX)  than staging
pattern S2  (outside  top row burners on air only) .  With the further reduced
load of 270 MW,  staging pattern 84  (top row of burner on air only) produced
lower NOX results  than staging pattern 85 (top row wing burners and next
to top row middle  burners on air only) .

           It  is hoped that  eventually an opportunity may arise for com-
pleting  the planned program on this unit.

           6.1.1.2  Gaseous  Emissions  from Horizontally
                    Opposed  Coal Fired Boilers	

           Three Babcock and Wilcox designed opposed firing  boilers were
tested  in this program;   Leland Olds  No. 1, 216 MW; Harllee Branch
Number  3, 480 MW; and Four  Corners No.  4, 800 MW  full load  rating.
Since the Harllee Branch boiler was tested first  and most extensively,
it will  be discussed first,  followed  by the Four  Corners and Leland
Olds boilers.

                6.1.1.2.1 Harllee  Branch, Boiler No. 3

           Harllee Branch unit No.  3 with a full  load  rated  capacity of
480  MW  gross  load, is a single furnace, pulverized  coal  fired  Babcock
and  Wilcox boiler.  It has 40 burners arranged  in twenty burner  cells of
two  burners each, with two rows of five burner  cells  located in  both the
front and rear walls of the furnace.  The burner  configuration and
pulverizer layout are shown in Figure 6-10.

           Table 5 of Appendix A provides a summary  of the  operating and
emission data from each of the 51  test  runs completed on this  boiler.
Operating variables included in the test program were load, excess  air
level,  secondary air register setting and staged  firing  pattern.

           Figure 6-11 contains individual data points and least  squares,
regression lines for the NOx vs. average % stoichiometric  air  to active
burners for normal and staged firing.

           Baseline NOx emission levels  at full load averaged about  711  ppm.
Lowering the  level of excess air was  possible both under normal  and
staged  operating conditions down to flue gas 0£ concentrations of about
1.5% or  even  lower, without apparent  undesirable  side effects.   The  steep
effect  of reducing the per  cent of stoichiometric air to the active  bur-
ners on  decreasing NOX emissions is shown by the  least squares regressions
of the  data in Figure 6-11.   A 10% reduction in excess air  reduced NOX
emissions by  about 100 ppm under normal firing, and by 118  ppm under
staged  firing conditions.

           Interestingly, by operating four to six top burner cell row
burners  on air only, it was possible to maintain  boiler  load at  480  MW,
and  reduce the NOX emission levels to about 488 ppm.  This  level corresponds
to a reduction in NOX of about one-third, compared with  the baseline level.
Usually, wing burners of the top rows of front  and  rear  walls  were  operated
on air  only,  but the NOX emission  levels were not particularly sensitive
to  the  exact  location of the inactive burners in the  top row.  Twenty
different firing patterns were tested.

-------
                         - 73 -
                      FIGURE 6-10

            HARLLEE BRANCH,  BOILER NO. 3
          PULVERIZER AND COAL PIPE LAYOUT
            Two-Burner Cell.

         Pulverizer Letter

            Burner Number  .
                          B
                          J
                         (D
                    I
                   '«_*•
                    D
J
4s
B
*•—-

C
o
 G
 •^—>
 I
 E
"3s
                                      K
                                      •-^>
                                       I
                                             K
                                     FACING REAR FACE
H
-—>
I
 F
 <•—>
      O
       F
H
     FACING FRONT FACE

-------
                                   FIGURE 6-11
w
*—i
CO
H
g
 (M
CO,
i*
         600
                   PPM NOx (3% 02, DRY) VS % STOICHIOMETRIC
                      .	AIR TO ACTIVE BURNERS	
                       (HARLLEE BRANCH, BOILER NO. 3)
         500
400
         300
        200
        100
          0
                      T
                       T
                             T
T
                           Staged Firing
                           465 - 485 MW
Staged Firing    /
R . _ - 400 MW
                                                                    Normal Firing
                                                                    470 - 500 MW
                                                      Normal Firing
                                                         400 MW
     S
   l_s4-6
                       ./
                                y
                          ^   Staged Firing
                          / Slg - 275 MW
                                           _L
                                                J_
            70        80        90        100       110       120

               AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS
                                                               130

-------
                                  -  75 -
          With only 30 active burners, i.e., 10 top row burners on air
only, it was possible to reduce NOx emissions to about 354 ppm at low
levels of excess air, or a reduction of over 50% from the baseline level.
However, load was also reduced by 17% from 480 MW to 400 MW using this
staging pattern.

          Secondary air register setting had only a small effect on NOx
emission levels.  Wide open registers produced lower NOX than the 50%
open position under normal firing, while there were no significant dif-
ferences observed during staged firing operation.

          Reducing gross load from 480 MW to 400 MW (17% reduction in
load) resulted in 672 ppm vs. 537 ppm NOX (20% reduction in NOX) at the
same excess air level under normal firing conditions.  As discussed
above, larger reductions in NOX emissions resulted from staged firing
with low excess air.

               6.1.1.2.2  Leland Olds, Boiler No. 1

          Leland Olds unit number 1 has a full load rated capacity of
216 MW gross  load.   At  the time of its first operation  in 1966,  it
was the largest lignite fueled boiler in the Western Hemisphere.  This
Babcock and Wilcox designed boiler has a single  furnace with opposed
wall firing.  Ten pulverizers feed 20 burners, arranged in three rows
of four burners each in the front wall, and two  rows of 4 burners each
in the rear wall.
           Table 6 of Appendix A contains a summary of the operating and
 emission data obtained from the 13 test  runs completed on this boiler.
 Table 6-9 presents the experimental design with run number,  % oxygen and
 ppm NOX shown for each test  run.   Operating variables tested were gross
 load,  excess air level and firing pattern.

           Figure 6-12 shows  a plot of ppm NOX vs.  average % stoichiometric
 air to the active burners.   Full load baseline NOX emissions were 569 ppm.
 The least squares regression lines indicate the strong influence of excess
 air on NOX emission levels for both normal firing and staged firing.   With
 normal firing of all burners, low excess air operation reduced NOX emissions
.by 21% to 447 ppm.   Low excess air,  staged firing at full load (one mill
 on air only)  reduced NOX emission by as  much as 34% to 375  ppm.  Low
'excess air,  staged firing at 15% reduced load (two mills on air only)
 reduced NOX emissions by 54% to 260 ppm using the most effective staged
 firing pattern, 84 (top row front wall burners on air only).
          The lignite coal fired at this station has a moisture content
of around 34  to 39 percent (Appendix B, Table 9).  It was expected that
the high moisture would have  a significant effect on baseline NOX emis-
sions.  However, this boiler  also has an abnormally high air preheat
temperature 100 to 150°F higher than normal designs thought  to be necessary
for proper coal pulverization.  The potential effect of the high coal
moisture  content apparently was cancelled out in our tests by the high
air preheat temperature.   Future lignite fired boilers would not require
abnormally high air  preheat  temperatures and NOX emissions, accordingly,
would be  expected  to be significantly lower.

-------
                                  - 76 -


                                 TABLE 6-9

          EXPERIMENTAL DESIGN WITH RUN NO., 7, 02 AND PPM NOx

                        (Leland Olds,  Boiler No.  1)

S, All Burners
Firing
S2 F Mill On
Air Only
S3 F & K Mills
Air Only
S, A & F Mills
Air Only
S A & H Mills
Air Only
S, A & K Mills
Air Only
LI - 218 MW
Gross Load
AI - Normal
Excess Air
(1) 3.97o-569
(1A) 3.6%- 5 64
(3) 4.27»-560




A2 - Low
Excess Air
(2) 2.17o-447
(4) 2.87o-375




L2 - 180 - 192 MW
Gross Load
f^l - Normal
Excess Air



(6) 4.97»-428


S7 A Mill (4A) 2.67.-418
Air Only (4B) 2 .7Z-401
(4C) 3.1%-475
A£ ~ Low
Excess Air


(5) 3.57o-342
(7) 2.27o-260
(9) 2.67o-329
(11) 3.57»-356

Runs 4A, 4B and  4C
conducted at  205 MW.
                                                 ©  ©  ;  ©  ©
                                                     Rear Wall
(c)
^™^
                                                               c
                                                               ®
                                                    Front Wall

                                                   Mill-Burner
                                                   Configuration

-------
                            - 77 -
                          FIGURE 6-12
           PPM NO* (3% O2, DRY) VS % STOIC HKME TRIG
           _ AIR TO ACTIVE BURNERS _

                 (LE LAND OLDS,  BOILER NO.  1)
600
22
CO
ffl
I"
§
 e\
O
CO,

i
500
                          STAGED
                          FIRING
400
300
200
100
  0
   70
                   80
90
100
110
120
130
      AVERAGE % STOICHIOMETRIG AIR TO ACTIVE BURNERS

-------
                                   - 78 -
                6.1.1.2.3  Four Corners, Boiler No.  4

           Arizona Public Service's No. 4 Boiler at  their Four  Corners
Station was also tested according to our planned test program  design,
except  that continuous electricity demand on the station prevented
testing at low loads, and the currently inoperative flue gas recirculation
system  could not be utilized due to erosion problems.  This unit, with
a maximum rated capacity of 800 MW gross load, is a single furnace
 (with division wall), pulverized coal  fired Babcock and Wilcox boiler.
 It is fired with low sulfur, high ash  Western coal.  Boiler No. 5 at
the Four Corners Station is a "sister"-unit of similar size and design.
The latter was used for determining accelerated furnace water-tube
corrosion rates under baseline operating conditions.

           In each of these two boilers, nine pulverizers feed 54 burners,
arranged in 18 cells of three burners  each, as shown in  ELgure 6-13.  The
 front wall has ten burner cells, while eight burner cells are located in
the rear wall of the furnace.  Each boiler can maintain the full load
capacity of 800 MW with eight or nine  pulverizers in operation when good
quality coal is fired, and all equipment is in good operating  condition.

           Operating variables during the short-term optimization phase of
 the tests were boiler load, burner firing pattern,  excess air  level,
secondary air register setting, and water injection (used for  improving
precipitator efficiency).  Our gaseous sampling system was modified to
allow sampling from 18, instead of the usual 12 duct positions, with two
 three-probe assemblies each in the north, middle, and south ducts between
 the economizer and the air heaters.

           Table 7, Appendix A contains a summary of the operating and
emission data from the 26 test runs completed on this boiler.   Table 6-10
below,  indicates the experimental design with run number, % oxygen  and
ppm NOX.

           The NOX emission data measured are summarized in Figure 6-14.
Baseline NOX emissions under normal operating conditions averaged a high
level of about 935 ppm, which is consistent with that expected from a
large,  horizontally opposed, coal-fired boiler.  Reducing the  per cent
stoichiometric air to the active burners consistently reduced  NOx emis-
sions for both normal and staged firing as shown by the least  squares
regression line of Figure 6-14.  The expected reductions in NOx for a 10%
reduction in % stoichiometric air calculated from least squares regression
analysis were 147, 184, 147, 159 and 166 ppm for firing patterns Si through
85,  respectively.

           Through staged firing, the average % stoichiometric  air to the
active  burners could be reduced considerably below the minimum level of
110% reached for normal firing, thus producing lower NOx emission levels.
Four staged firing patterns were tested:  (1) 82 - top 8 burners on air
only, (2)  83-2 top burners of 4 cells on air only to produce a
"tangential" effect, (3) 84 - top 12 burners on air only and (4)  85 - cells
fed  from pulverizers 5 and 9 on air only to produce a "tangential"  effect.
Full load operation was maintained with 83 and 84 firing, while gross load
was  reduced to about 730 MW (9% reduction) during 82 firing and reduced
to 600 MW during 84 type operation.   NOx emissions  under full  load,  low

-------
                                 - 79 -
                              FIGURE 6-13

                  FOUR CORNERS STATION, BOILER NO. 4
                  PULVERIZER-BURNER CONFIGURATION
                                       REAR WALL (EAST)
      NORTH
       WALL






(M)
©
43N
0
o
o

L




»6N
©
®
®
44N
0
o
o



471
O
o
o



i




43S
0
o
o

L




i5S
O
o
0
44S
O
o
o






46£
O
o
0
47S
0
o
o






                                                       SOUTH WALL
                  FRONT WALL (WEST)

9 PULVERIZERS NUMBERED 41 THROUGH 49.
18 BURNER CELLS NUMBERED WITH PULV. NO. "N" OR "S" FOR NORTH OR SOUTH
 QTT TYnrrsTryM WA.LT_.-.
54 BURNERS DESIGNATED "T", "M" OR "B" FOR TOP, MIDDLE OR BOTTOM OF
 OF EACH CELL.
E.G., 45NT IS TOP LEFT BURNER IN FRONT WALL OF NO. 4 BOILER
            TOP BURNER OF CELL
            NORTH SIDE OF DIVISION WALL
            ^NO. 5 PULVERIZER
            *NO. 4 BOILER

-------
                                                                   TABLE 6-10
                                         EXPERIMENTAL DESIGN - % OXYGEN AND PPM NOX  (3% 02. DRY BASIS)


                                                           (Four Corners,  Boiler No.  4)

S. - Normal
Firing
54 Burners
Firing Coal
S2 - 8 Top
Burners
On Air
Only
S~ - Simulated
Tangential
8 Burn on Air
S4 - 12 Top
Burners
On Air Only
S - No. 5 & 9
Mill
Burners
On Air Only
Lt - 710 - 810 MW Gross Load
AI - Normal
Excess Air
DI - Open
Sec. Air
(1A) 5.6-982
(1) 4.6-848
(IB) 5.1-965
(1C) 4.5-843
(ID) 5.2-949
(IE) 3.4-741*
(IF) 3.1-715*
(7) 4.7-754
(9) 4.6-685
(15) 5.5-709

D2 - 1/2 Open
Sec. Air
(5) 5.0-932
(3) 4.6-695



A2 - Low
Excess Air
DI - Open
Sec. Air
(6A) 2.3-641
(6) 2.0-630
(4) 2.2-482
(12B) 3.7-458*
(12C) 2.8-473*
(14) 2.3-494
(12) 3.2-488

D2 - 1/2 Open
Sec. Air
(2) 2.5-659
(2B) 2.8-748
(8) 3.3-609



L2 - 590 - 600 MW Gross Load
AI - Normal
Excess Air
AI - Open
Sec. Air




(19) 6.5-816
(20) 6.4-801
D2 - 1/2 Open
Sec. Air





A2 - Low
Excess Air
D! - Open
Sec. Air




(21) 3.0-452
D2 - 1/2 Open
Sec. Air





                                                                                                                                                 I

                                                                                                                                                 OT
                                                                                                                                                 O
*  100-200 gal. water/hour injected into furnace.

-------
                                     -  81 -
    900
    800
I   700

m
 CM

O
    600
    500-
                                 FIGURE 6-14

                          PPM NOx (3% O2, DRY) VS %
                   STOICHIOMETRIC AIR TO ACTIVE BURNERS
                  I          I           I          I           I    ^    T
                        (FOUR CORNERS, BOILER NO. 4)      _   OA)
                                                            (IB)
                                                             [ID)
                               •^-^

                             yNormal wiring

                            /710 - 800 MW
                     /
                       //
                              Staged (S9) Firing - 730 MW
                                °
    400-
                 Staged Firing - S4 and S& - 600-800 MW
    300-
    200-
                  I
Symbol
Sl
s2
S3
S4
S5
O
n
A
V
O
BUI
Firing
Coal
54
46
46
42
42
'Hers
Air
Only
0
8
8
12
12
Gross Loac
750-800 MW
730 MW
794-800 MW
725-805 MW
590-600 MV
I
I
I
       80        90        100       110        120       130

             AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS
                                        140

-------
                                    - 82 -
excess air, staged operation  (83 and 84) were reduced to about  490  ppm or
by  about 48% from baseline operation.  Operation with firing pattern  82
at  730 MW produced 482 ppm NOX  (458 to 473 with water injection), while
firing pattern 85 at about 600 MW produced 452 ppm NOX emissions.

           Wide open secondary air register settings could reduce NOX  emis-
sions  by a small amount compared with closed settings (presumably because
of  reduced combustion intensity) , but only in combination with  low  excess
air firing.  As before, the effect of damper settings on NOX emissions
was significant, but second-order with respect to the main effects  of
reduced excess air and staging.

           Data from test  runs numbered 12C and 12B were obtained with
 staged firing  (8 burners  on air only) while the boiler operator used
water injection to help improve precipitator efficiency for particulate
 removal.  The reduction in NOX of about  80 ppm from the expected level
 of about 543 ppm is not altogether surprising, based on our estimate  of
 0.2 Ib. H20 injected/lb.  coal fired.  This quantity of water injection
 should reduce flame temperatures sufficiently to allow for the  above
 degree in NOX emission reduction.
           6.1.1.3  Gaseous Emissions from
                    Tangentially Fired Boilers

           Four Combustion Engineering designed, tangentially fired,
 pulverized coal boilers were tested:  Barry No. 3,  250 MW; Naughton No. 3,
 325  MW;  Dave Johnston No. 4, 348 MW; and Barry No.  4 rated at 350 MW
 gross load.   The number of burners and burner levels were 20 and 5 for
 Naughton No. 3 and Barry No. 4, 48 and 6 for Barry  No. 3, and 28 burners
 arranged in 7 levels for Dave Johnston No. 4.  The  Naughton and Dave
 Johnston boilers were fired with Western coals, while the two Barry
 boilers  tested were fired with Alabama coal.

                6.1.1.3.1   Barry, Boiler No. 3

           Alabama Power Company's Boiler No. 3 at their Barry Station
was  tested at the boiler operator's request for gaseous emissions only
 in a  short-term optimization program.

           This unit is a 250 MW maximum continuous  rating, twin furnace
tangential,  pulverized coal fired Combustion Engineering boiler.  It has
a separated  furnace arrangement, with radiant and horizontal superheater
surfaces  in  both furnaces.  The pendant and platen  sections constitute
the superheat surface in one furance, and reheat surface in the other one.
Six pulverizers feed 24 tangential burners (six levels of four burners)
in each of the two furnaces.                                          —

-------
                                 - 83 -
          This boiler was of special interest, because cf the small value of
31.25 MW per "equivalent furnace firing wall".  Our correlation based on
previously obtained data for coal fired boilers (4_) would predict a
baseline (20% excess air) NOx emission level of 412 ppm for this parameter.
Actual measurements for run 1 baseline operation resulted in a NOX value
of 410 ppm, in good agreement with the correlation.

          Table number 8 of Appendix A contains a summary of operating
and emission data for the 8 test runs completed on this boiler.  Table 6-11
shows the experimental design with average % oxygen and ppm NOX for each
run.

          Operating variables included in the test program were excess
air level, air damper settings, and pulverizer mill fineness setting.
Planned reduced load and staged firing tests could not be implemented,
because mechanical problems with a condenser water valve prevented such
operation, despite all the efforts of the plant personnel to correct this
problem.

          As expected, excess air level exerted a major effect on NOX
emissions.  These results are shown in the least squares regression line
of Figure 6-15.  From a baseline level of about 412 ppm at 117% stoichio-
metric air to the burners, NOX emissions were reduced by about 24% to
310 ppm at 106% stoichiometric air.  The effect of damper settings was
very small, 7%, and that of mill fineness was negligible.  The normal
practice of 100% open auxiliary dampers and 40% open coal dampers pro-
duced lower NOX emissions than the reverse damper settings.

               6.1.1.3.2  Naughton, Boiler No. 3

          Utah Power and Light's No. 3 boiler at their Naughton Station
was one of two modern, 320 to 350 MW maximum rated single furnace, pul-
verized coal fired, Combustion Engineering boilers tested.  The other
one was Alabama Power's No.  4 Boiler at their Barry Station.  Both boilers
have five levels of four corner burners each.  Gaseous emission results
obtained in testing the latter unit will be presented in a subsequent
section of this report.

          Naughton unit No.  3 was designed to fire a sub-bituminous, low
heat content (9,500 Btu/lb.  HHV), low sulfur, high moisture content,
Western coal.  The boiler was designed for a larger turbine-generator
than the one actually installed.  This factor, in combination with the
lack of "seasoning" of the superheat and reheat surfaces, and the type
of coal fired in this new unit has resulted in a steam temperature control
problem.  The use of tilting burners and atfemperation water are the means
available for controlling steam temperatures.  To the date of our tests
it had been necessary at load levels exceeding 280 MW to tilt the burners

-------
                           - 84 -
                        TABLE 6-11
TEST PROGRAM  EXPERIMENTAL DESIGN - BARRY, BOILER NO. 3
 (Run No., Average % Oxygen,  and ppm NOX  (3% 0_ Dry Basis)
                    Measured in  Flue Gas)

Dl
Secondary
Air
Dampers
100% Aux.
30% Coal
D2
Secondary
Air
Dampers
40% Aux.
100% Coal
Fl
Normal
Mill
Fineness
F2
Coarse
Mill
Fineness
Fl
Normal
Mill
Fineness
Coarse
Mill
Fineness
LX 250 MW
Si All Mills
Firing Coal
AI Normal
Excess
Air
(1)
3.1 - 410
(7)
3.5 - 402
(3)
3.2 - 425
(6)
3.5 - 420
A« Low
Excess
Air
(2)
1.3-310
(8)
1.4-312
(4)
1.9-350
(5)
2.0-350

-------
                                   - 85 -
                               FIGURE 6-15



                      PPM NOx (3% O2 DRY BASIS) VS %

                 STOICHIOMETRIC AIR TO ACTIVE BURNERS



                          (BARRY, BOILER NO. 3)
   500
§
CO
•
   400
 *
0
fc

s
Pk
   300
                                                      Normal

                                                      Firing
   200
       80
90
100
110
120
130
           AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                                    - 86 -
 down, add  attemperation water, lower excess air,  and use furnace soot
 blowers  almost continuously.  It may be necessary, according  to Combustion
 Engineering representatives, to reduce the reheat surface  area to overcome
 this control problem.

            Other operating problems encountered in this  test program were
 furnace  slagging (particularly at high loads, with low  excess air and
 tilting  burners down) even under normal operating conditions, and the high
 silica content of the boiler feed-water, caused by pin-hole leaks in
 the condenser tubing.

            The above problems were taken into account for the design of the
 statistical test program.   Except for base line tests, our short-term NOX
 optimization phase was conducted at less than full load levels, to avoid
 the limited flexibility associated with operating problems.  The six
 operating  variables studied in the short term optimization tests were
 gross boiler load, burner firing pattern, excess  air level, burner tilt,
 secondary  air damper setting, and coal pulverizer fineness setting.
 Because  of the above-mentioned operating problems with this new boiler,
 the 300-hour accelerated corrosion test was performed only under normal
 operating  conditions, as will be discussed later.

            Table number 9 of Appendix A is a summary  of the  operating
 and emission data  obtained from  the 26 test runs  completed  on  this
 boiler.  Table 6-12  presents the test program experimental  design with
 average %  oxygen and ppm NOX for each test  run.

            Baseline NOX emissions at full  load  measured 531  ppm.  Reducing
 load from  334  MW to  200 MW (by 40%)  reduced NOX emissions by 73 ppm
 (from 531  to  458 ppm)  or only about 14%.   Coarse mill fineness had  a
 detrimental  effect of increasing NOX emissions by about  40  ppm (17%)  during
 the low excess  air,  staged operation compared  to normal  fineness as shown
 in Figure  6-16.  Table 6-13 presents the  change in coal  fineness measured
 on samples  from four mills.

           The  emission data obtained in testing this boiler.are shown  by
 the least squares regressions of  Figure 6-17.  Significant  reductions  in
 NOX emissions were achieved  from  the  baseline  level of about 530 ppm
 (which  is relatively  low for  a coal  fired boiler of this size, but  typical
 of  tangentially fired  units  from  the  standpoint of NOX emissions) .  With
 normal  firing,  quite  a  steep  decrease was found by reducing the percent
 stoichiometric  air to  the  active burners  to 110%,  resulting in a reduction
 of  about  30% to 380  ppm.   Staged  firing in  combination with low overall
 excess  air  (less than  stoichiometric  air/fuel ratio in the  active burners)
 at  90%  of full  load resulted  in NOX  levels  as low as 219 ppm,  or a
 reduction of about 60%  from the baseline NOX level.  These highest
 reductions  in NOX (311 ppm), were achieved with "abnormal" air register
 settings  (coal-air 30% open, and auxiliary air 20% open).  Additional small
 reductions  in NOX emissions could be obtained through the use of optimum
burner  tilt positions, and pulverizer mill fineness,  each contributing about
 10%  to  the  NOX emission reduction achieved.

-------
                                                                    TABLE 6-12
                                              TEST PROGRAM EXPERIMENTAL DESIGN - NAUGHTON, BOILER NO. 3
(Run No.,  Average
                                                      Oxygen and ppm N(X_  (3% 00 , Dry Basis) Measured  In  Hue  Gas)
                                                                       "      Z

~~ — L4J_Secondary
Cl
Normal
Mill
Fine-
ness

C2
Coarse
Mill
fine-
ness
Horiz .
Burner
Tilt
T2 -
Down
Burner
Tilt
T3 - Up
Tilt
T -Hor.
Tilt
T2 -
Down
T -Up
Tilt
L - 328 - 340 MW
A! - All
Pulv. Firing
Ai-Nor.
Exc . Air
V
(18) 3.9
494
(26) 4.4
568





A2 -
Lea
Dr
(19) 2.0
379





L2
sr
A! -
Nea
Dl-

(24) 3.6
569
(25) 4.2
549




- 300 - 315 MW
S2 - Top Pulv.
Air Only
A2 - Low
Excess Air
V
(20) 2.7
236





V
(21) 2.3
219





L3 - 250 - 275 MW
sr
Ai-
Nea
V
(1) 4.9
537
(23) 3.6
510




S, - Top Pulv.
Air Only
Al -
Nea
Dl-
(2) 4.9
304
(22)*3.1
331





A2 - Low
Excess Air
V
(3) 3.6
265
(4) 3.7
266
(6) 3.1
216
(5) 3.6
284

(9) 3.1
245

V
(10) 3.0
197
(7) 3.0
213
(11) 3.5
216
(13) 3.7
235
(8) 3.2
251
(12) 3.7
273
L^ - 200 MW
V
Al -
Nea
Dr
(14) 4.2
458





S3 - 2 Pulv. Off,
Top Pulv. Air Only
A! -
Nea
Dr
(15) 4.5
169





A2 - Low
Excess Air
Dr
(16) 3.2
182





V
(17) 4.2
176





i
00
*-J
1
*  Top pulverizer off with 2nd air registers partly open.

[1]  Secondary air registers:  DI - 20% auxiliary air, 80% coal air;  D2  - 60% auxiliary air,  20%  coal  air.

-------
                                  FIGURE 6-16

               EFFECT OF MILL FINENESS AND BURNER TILT ON
                 EMISSIONS FOR LOW EXCESS AIR STAGED FIRING

                          (NAUGHTON, BOILER NO. 3)
    30O
S
cT
e«
CO
i
25C-
    20C-
                                                            ,21 Coarse
                                                              Mill Fineness
                                                                     Normal
                                                                  ill Mill Fineness
                                                                                       oo
                                                                                       00
    150.
               -30
                     -20
-10
0
+ 10
+20
+30
                      BURNER TILT (° FROM HORIZONTAL)

-------
                                             TABLE 6-13

                                     PULVERIZER SCREEN ANALYSES
                                       NAUGHTONf  BOILER NO.  3
                                (Normal vs. Coarse Classifier Setting*)


Kill No.
1
2
3
4


Averages


% Passing Through
48 Mesh Screen
Norr.r.l Ccc.roc
99.2 97.2
99.6 98.2
95. 0 96.6
99.4 97.3


99.3 97.4


Diff. % 1
2.0
1.4
2.4
1.8


1.9
t = 9,1

% Passing Through
100 Mesh Screen
Normal Cor.rse
88.4 32.0
95.2 87.6
89. 6 84.1
90.8 83.6


91.0 84.3


% Passing Through
200 Mesh Screen
fliff. % i Normal Course j Diff. %
6.4
7.6
5.5
7.2


6.7
t » 14.4

76.7 60.9
75.4 64.6
65.1 61.6
69.3 64.8


71.6 63.0


15.8
10.8
3.5
4.5
i

8.6
t = 3.0

                                                                                                               I
                                                                                                              oo
*  The classifier can be set  from  0  (very  coarse)  to 4 (very fine).
   For these tests the classifier  vas  set  at:  2.1 normally and at 1.0
   for the coarse test runs.

-------
                                     - 90 -

                                 FIGURE 6-17
                          PPM NOX (3% O2, DRY) VS %
   550
   500
   450
g  400
<
PQ
><
§
 * 350
T	1	\	1	r
  STOICHIOMETRIC AIR TO ACTIVE BURNERS

         (NAUGHTON, BOILER NO. 3)
Firing Pattern Symbol
Sj - NORMAL O
S - TOP PULVER-Q
IZER ON AIR ONLY
S - 2 PULVER- A
3 IZER OFF
LrFOSS^
Load
2"50-340
250-315
200
                                                           Burners
                                                           Tilted
                                                           Down
                                            Normal Firing
                                            (Horizontal Tilt)
   300
PM
   250
   200  -
    150
                                 Itaged Firing
                               (Horizontal Tilt)
    100
I
I
i
       60        70        80        90        100       110       IzO

               AVERAGE % STOICHIOMETHIC AEP TO ACTIVE BURNERS
                                                           ~IBO

-------
                               - 91 -
               6.1.1.3.3  Barry, Boiler No. 4

          Alabama Power's Boiler No. 4 at their Barry Station was tested
successfully through all three phases of our test program design.
Representatives of Combustion Engineering actively participated in this
series of tests.  As mentioned before, this new 350 MW maximum rated
capacity, single furnace, pulverized coal fired Combustion Engineering
boiler is similar to Naughton unit No. 3.  Both are representative of
that manufacturer's current design practices.  In Barry No. 4, five
pulverizers feed 20 burners that are corner-mounted at five levels of
the furnace.  This boiler is designed for firing Eastern bituminous coal
having a HHV of 12,000 Btu/lb.

          Table Number 11, Appendix A contains a summary of the operating
and emission data obtained from the 46 test runs completed on this boiler.
Table 6-14  shows the test program experimental design with % oxygen and
ppm NOX  listed for each  test run.  For this boiler, flue gas samples were
taken from  ducts after the air preheater.  Regression analysis of simul-
taneous  measurements of  the Q£ concentration upstream and downstream of
the air  preheater in several test runs provided a basis (see Figure 6-18)
for estimating the excess air supplied to the furnace.

          Seven operating variables were varied independently in  the
short period NOX optimization phase of the test program.  Gaseous emission
data obtained from this  phase are presented in the least squares  correla-
tions of Figure 6-19.  As discussed below, the most important variables
from the standpoint of NOX emission control were excess air level, staged
firing,  and burner tilt.  Boiler load, secondary air register settings,
type of  coal and coal fineness were less important.

          Baseline NOx emissions at full load were only 423 ppm  due  in
part to  the relatively low level of excess air  (15%),  and  to  the
tangential  mode of firing.  Excess  air level was the most  important
variables as shown by the regression  lines of Figure 6-19.  Under normal
firing  operation with horizontal burner  tilt an eight  %  reduction of
excess  air  (from 15%  to  7%)  reduced NOX  to 350  ppm,  or by 17%.

            Burner tilt also had an important effect on NOX emission rates.
 Down tilt  operation increased NC^ emission by an average of 53 ppm  (14%)
 under normal firing, and by 5% under staged firing compared to horizontal
 burner  tilt.  Up tilt gave a small further improvement but caused steam
 temperature control problems and increased oxygen stratification between
 flue gas ducts.

           Staged firing (top pulverizer off) at 280 to 325 MW resulted in
 lowering NOx emissions  by about 34% (to about 280 ppm) when operating
 with 90% stoichiometric air to active burners.   Staged firing with the
 top two pulverizers off at 185 MW produced less than 200 ppm NOX under low
 excess  air firing.

-------
                                                                                             - 92 -
                                                                                           TABLE 6-14

                                                                     TEST PROGRAM EXPERIMENTAL PESIGN - BARRY. BOILER NO.  4

                                                         (Run Ho. Average 7.  Oxygen and  PPM NC  (37, 0,, Dry Basis) Measured  in  Flue Gas)
(1)
cl Fl -
Normal
Alabama Mill
Coal Fineness
With
C Pulv.
Firing
Petr.
Coarse
Mill
Fineness
2 1 Normal
Alabama Mill
Coal Fineness
On
All
Pulv.
S Fi -
Normal
Midwest Mill
Coal + Fineness
C. Pulv.
Firing
Coke
T -Horiz
Tilt
T.-DoVm
Tilt
T,-Up
Tilt
T, -Horiz
Tilt
T?-Down
Tilt
T -Horiz
Tilt
T.-Down
Tilt
T,-Up
Tilt
T. -Horiz,
X Tilt
T2~Down
Tilt
Lj - 325 - 360 »I (Gross Load)
ST - All 5 Pulv. Firing Coal
Aj-Nor.
Exc. Air
Di-Nor.
Setting
(1) 4.4-415
(33) 4.37.
497



(13) 4.7-420
(13A) 3.8-415


(17) 5.17,
441

A2~Low Excess
Air
Di-Nor.
Setting
(2) 3.9-398
(42)* 3.9-396
(43)* 2.7-349
(34) 3.17.
445
(3) 3.67.
349


(29) 2.87.
336

(30) 3.67.
336


D2'Rev.
Setting
(35) 3.8-409
(37) 3.9-441
(4) 2.57.
364




(31) 2.87.
398



L2 - 28C - 325 fW (Gross Load)
Si - 4 Pulv.
Firing
Ai-Nor.
Exc. Air
Dl-Nor.
Setting
(50)* 4.47.
436







(42A) 5.0-396
(42B) 4.5-370

S2 - Top Pulverizer on Air Only
A- -Nor.
E:c. Air
D -Nor.
Setting
(51 5.47.
313




(14) 5.17.
309


(18) 6.37.
334

A2-LOW Excess
Air
Dj-Nor.
Setting
(6) 4.87.
286
(10) 3.07.
289
(7) 4.47.
294

(11) 2.97.
299
(15) 3.67.
245


(19) 4.9-283
(19A) 4.4-308
(19E) 4.0-275

D2-Rev.
Setting
(9) 4.47.
295
(8) 2.4T.
257

(12) 4.3%
297


(16) 3.37.
264

(32) 5.77.
282
(20) 3.17.
273
Lj - 180 - 210 MW (Gross Load)
Sl -
A,-Nor.
Exc. Air
D,-Nor.
Setting








(25) 6.07.
440

83 - Top 2 Pulv. o£f;
Top Pulv. Air Only
Al-Nor.
Exc. Air
Dl-Nor.
Setting








(27) 7.17.
260

A2~tow Excess
Air
Dl-Nor.
Setting








(26) 3,77.
189

D2-Rev.
Setting









(28) 4.37.
232
S, - Top Pulv. Air
Cray; C Mill Off
Aj-Nor.
Exc. Air
Di-Nor.
Setting








(40) 7.77.
338

A] -Nor.
Exc. Air
Di-Nor.
Setting








(41) 3.97.
200

(1)   Secondary air register settings:  normal, auxiliary 100% open and coal  50%  open;  reversed,  auxiliary 507D open,  coal 100% open.
  *   Secondary air registers:  Auxil. - 40% open, Coal - 507D open.

-------
>H
 I

05
W
ffi
g   4
W
g
PK
w
ffl
                                   FIGURE 6-18

                     % OXYGEN MEASURED IN FLUE GAS BEFORE
                            AND AFTER AIR PREHEATER	

                                (BARRY,  BOILER NO. 4)
                       A

                   Duct B
                                                             y= 0.77 + O.SOx
                                                                                        u>
                                                                                        I
      0
                             % O2 - AFTER AIR HEATER - X

-------
                                    - 94 -

                                FIGURE 6-19


                         PPM NOx (3% O2, DRY) VS %
                  STOICHIOMETRIC AIR TO ACTIVE BURNERS

                           (BARRY, BOILER NO. 4)
   500
   450
   400
en
i— i
w
<
m
><

g

  ca
O

eP
CO
   350
   300
ft
   250
   200
   150
                           T
                                         S.. - Down Tilt
                                                S, - Horizontal Tilt
                                                 O
s9 ou
^ '
Down


1 1

Symbol
O
O
D
D
B! =
S2 =
i

Firing Burner Gross
Pattern Tilt Load
S.. Horiz. 340
Sj Down 340
S2 Horiz. 295
S2 Down 295
All burners firing coal
Top row burners on
air only
1 1



1
       80
                 90
100
110
120
130
140
             AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                                  - 95 -
           The effect of secondary air registers settings on NOX emissions
 depended upon the burner tilt position.  With horizontal burner tilt,
 normal damper settings (auxiliary 100% open and coal 50% open) produced
 about 7% less NOX than reversed settings.  However, with burners tilted
 down, reversed damper settings generally produced lower NOX emissions
 than did normal settings.

           Boiler load, coal type and coal fineness were minor operating
 variables from the standpoint of NOX emission control.   Reducing load
 by 12% reduced NOX levels  by about 9% which is in line  with our results
 obtained on other coal fired boilers.  Coal source had  a small, but
 satistically significant effect on NOX emission levels.  Alabama coal
 test runs produced about 23 ppm higher NOX emissions than did Midwest
 coal after  allowing  for  differences  in  excess  air  levels.  This difference
 is  possibly explained  by the  slightly higher nitrogen content  of the
 Alabama  coal.   Pulverizer  coal  fineness was changed  to  coarse  in only two
 test runs,  and  NOX results  obtained  did not show statistically  significant
 differences.

          Petroleum  coke was  fired through the middle level burners
 (Pulverizer  "C") on most test runs.   Comparison of the eight test runs
 conducted with Alabama coal fed to all pulverizers with similar runs firing
 petroleum coke or petroleum coke/coal mixtures indicated no statistically
 significant  differences in NOX emission levels.

               6.1.1.3.4  Dave Johnston, Boiler No. 4

           Boiler No. 4 at  the Dave Johnston  Station of  Pacific Power  and
 Light is a Combustion Engineering Company designed,  tangentially fired,
 single furnace boiler with a  maximum continuous  rating  of 2,450,000
 pounds of primary steam generated per hour or  about  348 MW gross  load.
 Seven pulverizers  feed coal to  28 tilting tangential burners  located
 at  the corners of  7  elevations.   The furnace  is  50 feet wide  and  42 feet
 deep with a volume of  280,000 cubic  feet.  Design  operating conditions
 at  maximum continuous  rating  include steam temperatures of 1005°F  leaving
 the superheater  and  the  reheater  turbine  throttle  pressure of  1890 psig
 and reheat  to  the boiler of 475  psig and  670°F.

          Table  10 of  Appendix A  contains  a summary  of  operating and
 emission data  for the  six  test runs  completed  on this boiler.   Maximum
 load was limited by  ID fan  capacity  due to plugging  of  the air  preheaters.
 Therefore,  our  test  runs were made at a reduced load of  303-312 MW
 instead  of  345-350 MW  full  load.  Normally, this boiler  can operate at
 full load with one or  two pulverizers off.  During our  test period  it
was  not  possible to  remove  the top mill without reducing  load  since
 there were always two other mills off, due either  to mechanical problems
or  to necessary, scheduled maintenance.  Thus, no  staged  firing tests
were possible.  Operating variables  included in the experimental program
were mills off, excess air level, burner tilt and primary air flow rate.
The  variation in primary air  (coal transport air) flow rate was made in
order to achieve higher loads without increasing ID fan output.

-------
                                   - 96 -
           Table 6-15 indicates the experimental design of operating
variables with average flue gas measurements of % 02  and ppm NOx (3%
02,  dry basis) shown for each test run.  Figure 6-20  is a plot of ppm
NOX  vs  % stoichiometric for the data collected during our test runs.

           Analysis of the flue gas emission data indicated a consistent
difference in flue gas measurements from duct "A" (probes 1 and 2) and
duct "B" (probes 3 and 4) generally characteristic of tangentially fired
boilers.  Duct "A" averaged about 2.3% oxygen and 20  ppm NOX, respectively,
less than the corresponding measurements from "B" duct.  This difference
in oxygen levels may be attributed to different burning rates prevailing
due  to  he centrifugal separation of larger coal particles arriving to the
furnace arch, before the flue gas stream is split into two ducts.

           Baseline NOX emission rates at partly reduced load  (12%
from full load) were 434 ppm  (3% 02, dry basis).  Reducing excess air
from 124 to 113% of stoichiometric reduced NOX emissions  to 384 ppm, or
by  12%.  Operating with burners tilted down resulted  in raising NOX
emissions by 40 ppm, or about 10%.  Test runs No. 10  and  17 were con-
ducted  with increased primary air damper openings so  that more coal would
be  transported with the same fan settings as used in  previous test runs,
and  consequently the load would be at increased levels.  NOX emissions
rates were about 13% lower in these test runs than corresponding earlier
test runs.  Horizontal burner tilt operation  produced less NOX emissions
than down tilt burner operation.   Additional experiments are needed to
verify  these results.

           6.1.1.4  Gaseous Emissions from
                    Turbo-Furnace Boilers
                6.1.1.4.1  Big Bend.  Boiler No. 2

           Tampa Electric Company's Boiler No. 2  at  their Big Bend Station
has been  the  only Riley-Stoker turbo—furnace unit  tested by Esso under
EPA sponsorship.   This pulverized coal fired, 450 MW maximum continuous
rating, single furnace boiler is fed by three pulverizer mills.  Altogether,
24 Riley  directional flame burners are fired normally, with one row of
12 burners in the front wall, and another row of 12 burners in the rear
wall.

           Maximum load was limited to 375 MW, due  to steam temperature,
potential  slagging,  and other operating problems not related to our test
program.   (It  is  our understanding that until the  time of our test, gross
load on this unit had never exceeded 400 MW.) Excess air was set at
normal operating  levels, or at the minimum level dictated by maximum
acceptable CO  levels measured in the flue gas, and  in the slag catcher
at the bottom  of  the furnace.  Other operating variables included in the
statistically  designed short-term phase (this was  the only phase of our
overall program design performed at Big Bend) were  operating with fly-
ash reinjection (practiced to improve carbon burn-out efficiency and
slagging characteristics)  or without it, and positioning of the

-------
                                          - 97 -
                                      TABLE  6-15

                 EXPERIMENTAL DESIGN WITH % Q£ AND PPM NOX (3% 02.BASIS)

                           (Dave Johnston Station, Boiler No. 4)

^x>»». *Primary
Burner~s'NVAir
Tilt ^\
Tl
Horizontal
T2
-10° Down
T3
+16° Up
S;L Normal Firing Pattern
(Mills 17 & 20 Off)
AI Normal
Excess Air
Pl
(1)
4.2-434


P2
(10)
3.9-362
(17)
3.9-380

A2 Low
Excess Air
Pl
(2)
3.2-386
(3)
3.2-414
(4)
3.4-381
P2
(16)


S2 Staged Firing
Top Mill - Air Only**
AI Normal
Excess Air
Pl
(5)


P2
(12)


A£ Low
Excess Air
Pl
(6)
(7)
(8)
P2
(13)
(14)
(15)
 *  Primary Air:  P  Normal  Primary  Air  Flow
                 P~ High Primary Air  Flow

**  Pulverizer mechanical problems and maintenance
   schedules prevented  the  running  of these tests.

-------
                            FIGURE 6-20

                       PPM NOx (3% Oo, DRY) VS %
                STOICHIOMETRIC AIR TO ACTIVE BURNERS

                (DAVE JOHNSTON STATION, BOILER No. 4)
    500
g
 CM
o
s
_x
    400
    300
1 1 1 	 1
Down Tilt >
/ >
© /
/ /
/ ©0©
/ @
i i i i
80 90 100 110 120
1 1
/Horizontal and
, , Up Tilt
(i)

Down Tilt Increased
Primary
) Horizontal Tilt Air
130 140
VO
00
            AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                                  - 99 -
directional air vanes.  Normal position is 15° below horizontal for the
air vanes.  During our tests baseline data were taken with the dampers in
the normal position and "low NOX" emission data were obtained with the
dampers aligned either 15° below the normal position, in both front and
rear burners, or the front directional vanes were set at 15° below the
normal position, and the rear directional vanes 15° above it.  Simulated
"staged" firing, at reduced load levels, was attempted by opening up the
secondary air registers on selected burners, so that the active burners
were supplied with 80% of stoichiometric air.

          Table 12, Appendix A contains a summary of the operating and
emission data obtained from the 14  test runs completed in Big Bend No. 2
boiler.  The experimental design with average % oxygen and ppm NOX data
for each run is shown in Table 6-16.  A diagram of  the mill-burner con-
figeration is also shown at the bottom of table to  aid in visualizing
the "simulated" staged firing patterns.

          The NOX emission results  obtained are shown in the least squares
regression of Figure 6-21.  Reducing the air to the burners from  the
normal level of 115% of stoichiometric to 107% decreased NOX emissions
from about 600 ppm at 370 MW to about 400 ppm, or a reduction of  about
one third.  This decrease in NOX with reducing excessing air is steeper
than that generally observed in wall and tangentially fired units.  On
the other hand, it should be noted  that the "baseline" NOjc emission was
determined at a load reduction of 18%, compared with maximum continuous
rating.  Further load reduction produced, as expected, further decreases
in NOX.

          "Staged" firing, which in this instance was quite different from
the normal pattern of staging burners, produced only a 10% reduction in
NOX at the low load of 230 MW, as shown in  Figure 6-21.  It was interesting
to note that NOx levels were consistently lower at  the ends of the
furnace compared to its middle as shown in Figure 6-22.

          The best NOX reductions were obtained with front wall direc-
tional air vanes tilted 15° down, and rear vanes tilted 15° up from
their normal alignment.  Flyash reinjection had no  significant effect
on NOX emissions.

          Further testing is required with coal-fired turbo-furnace
boilers to define optimum operation for NOX control, taking into  account
steam temperature control, slagging, and potential  furnace water-tube
corrosion problems.

-------
                                            TABLE  6-16

                       EXPERIMENTAL DESIGN WITH % 0? AND PPM NOX (3% 0? BASIS)

                                 (Big Bend  Station,  Boiler No.  2)

TI Directional
Vanes
Front - 15°
Rear - 15°
T2 Directional
Vanes
Front - 15°
Rear - 15°


1^ 370 - 385 MW
AI Normal
Excess Air
(1) Ash On
2.8-614
(2) Ash Off
2.8-587
(4 A) Ash On
2.8-547
(4B) Ash Off
2.9-558


A2 Low
Excess Air

(3) Ash Off
2,0-464

(5) Ash Off
1.4-398


L2 300 MW
Aj Normal
Excess Air

(11) Ash Off
2.5-397

(9) Ash Off
2.9-378


A2 Low
Excess Air

(12) Ash Off
2.1-362

(10) Ash Off
1.8-341


L3 225 - 230 MW
AI Normal
Excess Air


(6) Ash On
3.4-370
(20)* Ash Off
3.4-350


A2 Low
Excess Air



(21)** Ash Off
3.5-312
(22)*** Ash Off
3.5-312
                                                                                                             o
                                                                                                             o
  *  Run 20 B mill off, secondary air dampers closed on idle burners.
 **  Run 21 B mill off, secondary air dampers open on 1/2 idle burners.
***  Run 22 B mill off, secondary air dampers open on all idle burners.
         **  Mill Burner
             Configuration
             Air Only Burners
             Shown by Arrows
         Rear Wall Burners
ABCBACCABCBA
ABCBACCABC
        Front Wall Burners
B  A

-------
                                       - 101 -

                                    FIGURE 6-21
                             PPM NO* (3% 02, DRY) VS %
                      STOICHIOMETRIG AIR TO ACTIVE BURNERS
                        	1	1	1
                        (BIG BEND STATION, BOILER NO. 2)
    600
    500
§
 CM
O
eP
in
i
    400
    300
                             Staged" Firing
                               225 MW
                                          Symbol
                                                           370-380 MW
                                                                225 MW
                                   Flyash
                                 Reinjection
                                  	DLl'. VatifeS Beg.
                                   From Normal Positic i
                                  	Front/Rear
                                            O
                                            O
                                            D
                                            D
                                     Off

                                     On
                                     Off

                                     On
                                         -15/-15

                                         -15/-15
                                         -15/+15

                                         -15/+15
    200
                                                    _L
        70
80
90
100
110
                                                           120
                                                    130
               AVERAGE % STOICHIOMETRIC AIR TO ACTIVE BURNERS

-------
                                     FIGURE 6-22
    500
                        PPM NOx EMISSIONS VS PROBE LOCATION


                          (BIG BEND STATION, BOILER NO. 2)
CO
<
n
    40°
Q   300


 CM

O
_
g   200
    100
Directional
Vanes
Front/Rear
) -15% 15°
) -15% 15°
J -15° A 15°
3 -15V+150
\ -15°/-15°
1 -15°A15°
Excess
Air
Level
Normal
Normal
Normal
Low
Low
Fly Ash
Re injection
Yes
No
Yes
No
No
                                             o
                                             I-O
     0
        Left
4  Right (Facing Front of Boiler)
                                    PROBE NUMBER

-------
                                 -  103  -
     6.1.2  Particulate Emission Results

          The results of the particulate emission tests obtained on this
program, summarized in Table 6-17, are internally consistent and appear
to be reliable within the limitations of this type of testing.  As men-
tioned in section 4.2.2, the objective of this work was to obtain sufficient
particulate loading information to determine the potential adverse side
effects of "low NO " firing techniques on particulate emissions by com-
paring measurements of total quantities and percent unburned carbon with
similar data obtained under normal or baseline operating conditions.   The
differences in emission values and particulate carbon content between
baseline and "low NOX" operation summarized in Table 6-17 afford an
assessment of the adverse affect of "low NOX" firing on a given boiler.

          Not unexpectedly, some "side effects" did develop with "low NO "
firing.  Total quantities of particulate tend to increase but not signifi-
cantly and the consequences appear to be relatively minor.  This trend
would have an adverse effect on the required collection efficiency of
electrostatic precipitators to meet present Federal emission standards,
but the increases in efficiency indicated by these limited tests appear
to be quite small.

          Another side-effect of "low NO " operation is that on carbon
losses.  Carbon content of the particulates with "low NO " operation are
shown in Table 6-17 to increase significantly for front wall and horizon-
tally opposed fired boilers.  The data are quite scattered, and these
increases do not appear to be directly related to the change in emissions
with "low NOX" firing technqiues or other boiler oper?ting variables.
For example, the tests on boiler No. 4 at the Four Corners Station of
Arizona Public Service Company, a horizontally opposed fired boiler burn-
ing western coal, showed marginal decreases in particulate carbon content.
Surprisingly, there is some evidence that "low NO " firing techniques for
tangentially fired boilers may decrease carbon losses significantly.   It
also appears that "low NO " operation may decrease carbon losses for boilers
fired with Western coals.  Such improvements, however,  would not be substan-
tial since unburned combustible losses with these coals are already low.
The effect of these changes in combustibles on boiler efficiency is dis-
cusssed in Section 6.1.4 and are shown to be relatively insignificant.

          It is important to note that no major adverse side effects appear
to result from "low NO " firing with regard to particulate emissions.
Additional test data on a variety of boiler types are required to firm up
on these conclusions.  It would also be desirable to include investigation
into potential changes in particle size distribution and the resultant
effect on precipitator collection efficiency in the scope of future tests.
Potential changes in fly ash resistivity with respect to precipitator per-
formance is another area for investigation.

-------
                                                         TABLE 6-17
    Utility
TVA
Georgia
Power
Cojnpany
Arizona
Public
Service Co.
Alabama
Power
Company
Utah Power
& Light Co.


Gulf Power Co.
Test No.

  1A
  IB
 10-C-l
 10-C-3
 26-A-l

  1C
  ID
  IE
  1G
  1H
 52D
 52E

  IE
  IF
 12A
 12B

 42A
 42B
 19A
 19B

 23
 23
 25
 26

  1
 26B
PARTICIPATE EMISSION TEST RESULTS


Firing
Condition
Base
Base
Low NOX
Low NOX
Low NOX
Base
Base
Base
Low NOX
Low NO
Low NOX
Low NOY
A
Base
Base
Low NO
Low NOX
Base
Base
Low NOX
Low NOX
Base
Base
Base
Base
Base
Low NOY
Av.
Gr/SCF
@ Std.
Cond.
2.68
4.62
2.32
3.36
3.13
1.83
1.86
2.26
2.47
2.60
2.00
2.65
4.52
5.36
4.87
3.26
1.17
3.08
3.31
3.32
0.448
0.301
0.752
0.800
2.54
3.82


lb./106
BTU
4.65
7.89
3.84
5.62
5.10
3.03
3.20
3.84
3.71
3.92
3.12
4.14
7.65
8.91
8.38
5.59
2.00
5.14
5.57
5.49
0.76
0.51
0.44
1.48
4.34
6.45


Grams/
106 cal.
8.37
14.20
6.91
10.12
9.18
5.45
5.76
6.91
6.68
7.06
5.62
7.45
13.77
16.04
15.08
10.06
3.60
9.25
10.03
9.88
1.37
0.92
0.81
2.59
7.81
11.61
Reqd.
Efficiency
To Meet
0.1 lb/
106 BTU
97.85
98.73
97.40
98.22
98.04
96.70
96.88
97.40
97.30
97.45
86.79
97.58
98.69
98.88
98.81
98.21
95.00
98.05
98.20
98.18
86.91
80.55
77.73
93.04
97.70
98.45

%
Carbon on
Particulate
6.29
5.90
10.55
8.46
12.40
5.50
3.17
2.80
6.73
11.82
9.98
7.41
0.69
0.53
0.18
0.46
24.23
25.83
14.75
18.77
22.62
22.62
4.44
1.80
5.08
8.15

Coal
Ash
Wet. %
15.87
18.39
11.50
14.38
15.39
12.05
9.72
8.58
11.28
8.43
10.3
11.86
21.92
21.96
23.13
21.12
4.89
4.86
10.68
8.82
8.16
8.16
6.78
8.10
10.20
12.04

HHV
BTU/lb.
Wet
11,452
11,477
11,918
11,231
10,961
12,310
12,589
12,121
12,200
12,574
11,178
11,887 i
i— '
8,821 °
8,811 i
8,913
8,915
12,706
12,641
11,918
12,720
10,293
10,293
10,273
9,992
11,186
11,282

-------
                                   - 105 -
     6.1.3  Accelerated Corrosion Probing Results

          As mentioned in Section 4.2.3, corrosion probes were installed
in the furnaces of the boilers tested by inserting them through avail-
able openings closest to the areas of the furnace susceptible to corrosion.
Probe locations are indicated in Figure 6-23.  Prior to installing the
probes in the test furnace, the probes were preapred by mild acid pickling,
pre-weighing the coupons, and screwing them onto the probes along with
the necessary thermocouples.  Each probe was then exposed to the furnace
atmosphere prevailing for the particular type of operation desired for
approximately 300 hours at  coupon temperatures of about 875°F in order to
accelerate corrosion.  After exposure, furnace slag was cleaned off and
saved for future analyses,  and the coupons were carefully removed from the
probes.  In the laboratory  the coupons were cleaned ultrasonically with
fine glass beads to the base metal, and re-weighed to determine the weight
loss.

          Total weight loss data were converted to corrosion rates on a mils
per year basis, using the combined inner and outer coupon areas, coupon
material density, and exposure time.  Wastage was found to have occurred
on the internal surfaces of some of the coupons, possibly because of the
oxidation of the hot metal  by the cooling air.  Attempts were made to
determine "internal" and "external" corrosion rates by selective cleaning
and weight loss determinations, but the results were found to be more
consistent and reliable on  an overall basis.

          Corrosion rates have been determined for 40 coupons installed
on 20 probes (2 coupons/probe), in boilers at four different generating
stations as listed in section 4.2.3.  Corrosion data obtained are tabulated
in Table 6-18.

          Although there is some scatter in the data obtained, as shown
in Table 6-18, most of the  information is quite consistent.  A major
finding of these tests is that no major differences in corrosion rates have
been observed for coupons exposed to "low NOX" conditions compared to
those subjected to normal operation.  In fact, for some probes the corrosion
rates were found to be even lower than for "low NO " exposure.

          Since corrosion rates have been deliberately accelerated in
this study in order to develope "measurable" corrosion rates in a short
time period, measured rates, as expected, are much higher than the normal
wastage of actual furnace wall tubes.  In future tests, coupons should
not be acid-pickled to remove oxide coatings, and coupon exposure temper-
atures should be maintained lower for a closer approximation of actual
tube wastage.

-------
Georgia Power
Harllee Branch Station
Boilers No. 3 & 4
£
I
1

F.W.
Burners
Arizor
Four Corn*
Sla.3- 1

B lower • • ' — —
Elev. 6-8'
Top 4
Burner 1
Elev.
F. W. X
Burners
Slag Slag
Blower Blower
^o. 9 No. 3 &
•>fr
Probe Prot ej
3B 3 A, B
4A, , B
4B ^
V
Side View
ia Public Service
srs Station - Boil
Slag Blowers
-.'-. V
Probe
Locations
(Both Sides)
- 106 -
FIGURE 6-23
FURNACE CORROSION
PROBE LOCATIONS


Utah Power and Light Company
] Naughton Station Boiler No. 3
s
i 8
Slag
I x Blower
*—/ Elev.
8*
I ^ Top Burner
.W. Elev.
urners -
(
Alabz
Company Barry
ers No. 4 & 5

I
11'


Lower
Burner
Elev.
I'll
ir
— K Slag J 	
R.W. ?;°wer
/ Burners Elev"
Probe
No. 2
-0 0 D
Ins
Doc
u.
Probe
No. 4
; Probe
No. 1
D J1
P-
Drs
Probe
No. 3
'


-

Front Elevation
Corner Burners)
ima Power Company
Station - Boiler No. 4
Slag Blowers
No. 18 & 26
V m
i
Probes 1
Probes 1
o • • *
, \
\Slag Bl
No.

^Tos. 3&4
sfos. 1&2
s, „ J*k .
f *
owers /
3&11 /




I »IH -
Side Elev.
  Side Elev.
(Corner Burners)

-------
                                              TABLE 6-18
                                    ACCELERATED CORROSION RATE DATA
                  Boiler
Georgia Power, Harllee Branch No. 4
Georgia Power, Harllee Branch No. 4
Georgia Power, Harllee Branch No. 3
Georgia Power, Harllee Branch No. 3
Utah P&L, Naughton No. 3
Utah P&L, Naughton No. 3
Utah P&L, Naughton No. 3
Utah P&L, Naughton No. 3
Arizona Public Service,  Four Corners No.  4
Arizona Public Service, Four Corners No.  4
Arizona Public Service,  Four Corners No.  5
Arizona Public Service,  Four Corners No.  5
Firing Condition
Corrosion Rate,*
     Mils/Yr
Baseline

Baseline


Low NO
X
Low NO
X
Baseline

Baseline

Baseline
Baseline
Baseline
Baseline
Low NO
X
Low NO
X
f75
I72
f26
\ 48
r 28
J122.
r6
l155
/124
65
r '
/ 43 M
[47 3
f 16 '
1 24
T25
(157
I59
r5
f«

|160
f25
i 24

-------
                  Boiler
Alabama Power, Barry No. 4
Alabama Power, Barry No. 4
Alabama Power, Barry No. 4
Alabama Power, Barry No. 4
Alabama Power, Barry No. 4
Alabama Power, Barry No. 4
Alabama Power, Barry No. 4
Alabama Power, Barry No. 4
                                          TABLE 6-18 (Cont'd)

                                    ACCELERATED CORROSION RATE DATA
                                                        Firing Condition


                                                            Baseline


                                                            Baseline


                                                            Baseline


                                                            Baseline

                                                            Low NO
                                                                  X
                                                            Low NO
                                                            Low NO
                                                            Low NO
Corrosion Rate*,
     Mils/Yr
                                                                                                               o
                                                                                                               c»
*  Paired corrosion rate values obtained on
   two coupons exposed on the same probe.

-------
                                  - 109 -
           Much more data are obviously  required  to  resolve  the question
 of  furnace tube corrosion under  "low NO "  firing conditions.  The limited
 data obtained  in this  study should be helpful  in providing  evidence that
 furnace tube corrosion may not necessarily be  a  severe adverse side-effect
 of  low N0x firing.   Long term "low NO " tests  using corrosion probes and
 the measurement of  actual furnace wall  tube  corrosion rates are needed to
 answer these questions.

      6.1.4 Boiler  Performance Results

           The  side  effects of "low NO " combustion  modifications on boiler
 performance were investigated and evaluated  for  each major  test where par-
 ticulate runs  were  made  under full load baseline and optimum "low NO "
 conditions.  Pertinent control room  board  data and  other informationX
 representing each test run were recorded and boiler efficiency was cal-
 culated in accordance  with the ASME  Steam  Generating Units, Power Test
 Codes  using the Abbreviated Efficiency  Test, heat loss method.  Calcula-
 tions  were based on the  assumption that  combustibles in the bottom ash
 slag was zero  and unmeasured  losses  were 0.5 percent.  An example of
 typical performance  data and  the calculations made  are shown in the ASME
 test forms  of  Tables 6-19  and 6-20.

           The  boiler efficiency calculated for each test is tabulated in
 Table  6-21 along with  other pertinent boiler performance information.
 Differences in calculated  boiler efficiency between baseline and "low NO "
 tests  provide  a comparison of any debit  or credit accruing to "low NO " X
 emission combustion operations.  However,  such comparisons are confounded
 by other factors  such  as boiler load during the  test run, the percent
 ash  of the coal  fired  during  the test and  the carbon content of the parti-
 culate.  In general, boiler efficiency increases with load and decreases
 with increases  in coal ash  or unburned combustible  content of the parti-
 culate emissions.  As discussed in section 6.1.2, particulate carbon
 content tends  to increase  under "low NO  " operation for front wall and
 horizontally opposed fired boilers.  The data,  however, are quite scattered
 and  these  increases do not  appear directly related  to the change in
 emissions with  "low N0x" firing techniques.  For example, the tests at
 the  Four Corners Station, unit No.  4  (a horizontally opposed boiler fired
with Western coal) showed marginal decreases in particulate carbon content
at the same relative load and coal ash content.

          The overall conclusion from these performance data is that only
negligible differences in boiler efficiency occur with "low NO " firing
compared to baseline operation.   Stated  another way, it appears that there
are no significant performance debits with regard to boiler efficiency
under "low NO" emission operation.   More performance data are needed on
all  types of boilers to substantiate these important preliminary findings.

-------
                                           - 110 -
SUMMARY SHEET
FOR
          TABLE  6-19

    ASME  TEST  FORM
ABBREVIATED EFFICIENCY
                               TEST
PTC 4.1-a(1964)
TEST NO. 1A BOILER NO. 6
OWNER OF PLANT TVA LOCATION Widows Creek
DATE 4-18-72

TEST CONDUCTED BY Esso Research & Engineering Co. OBJECTIVE OF TEST Boiler PerformanceuRATiONA Hrs.
BOILER, MAKE 8. TYPE B&W Radiant RATED CAPACITY 125 MW
STOKER, TYPE & SIZE
PULVERIZER, TYPE & SIZE Ty?e E BURNER, TYPE
FUEL USED Bituminous Coal MINE COUNTY STATE
& SIZE
SIZE AS FIRED
PRESSURES & TEMPERATURES FUEL DATA
1
2
3
4
S
6
7
8
9
10
11
12
13
14
STEAM PRESSURE IN BOILER DRUM
STEAM PRESSURE AT S. H. OUTLET
STEAM PRESSURE AT R. H. INLET
STEAM PRESSURE AT R. H. OUTLET
STEAM TEMPERATURE AT S. H. OUTLET
STEAM TEMPERATURE AT R.H. INLET
STEAM TEMPERATURE AT R.H. OUTLET
WATER TEMP. ENTERING (ECON.MBOILER)
STEAM QUALITY% MOISTURE OR P. P.M.
AIR TEMP. AROUND BOILER (AMBIENT)
TEMP. AIR FOR COMBUSTION
TEMPERATURE OF FUEL
GAS TEMP. LEAVING (Boiler) (Econ.) (Air Htr.)
GAS TEMP. ENTERING AH (If conditions to be
psio
psio
psio
psia
F
F
F
F

F
F
F
F
F










r) ID
/) Q

^7 &

UNIT QUANTITIES
15
16
17
18
19
20
21
22
23
24
25
ENTHALPY OF SAT. LIQUID (TOTAL HEAT)
ENTHALPY OF (SATURATED) (SUPERHEATED)
STM.
ENTHALPY OF SAT. FEED TO (BOILER)
(ECON.)
ENTHALPY OF REHEATED STEAM R.H. INLET
ENTHALPY OF REHEATED STEAM R. H.
OUTLET
HEAT ABS/LB OF STEAM (ITEM 16-ITEM 17)
HEAT ABS/LB R.H. STEAM(ITEM 19-ITEM 18)
DRY REFUSE (ASH PIT + FLY ASH) PER LB
AS FIRED FUEL
Btu PER LB IN REFUSE (WEIGHTED AVERAGE)
CARBON BURNED PER LB AS FIRED FUEL
DRY GAS PER LB AS FIRED FUEL BURNED
Btu/lb
Btu/lb
Btu/lb
Btu/lb
Btu/lb
Btu/lb
Btu/lb
Ib/lb
Btu/lb
Ib/lb
Ib/lb
HOURLY QUANTITIES
26
27
28
29
30
31
ACTUAL WATER EVAPORATED
REHEAT STEAM FLOW
RATE OF FUEL FIRING (AS FIRED wt)
TOTAL HEAT INPUT (Item 28 X Item 41)
1000
HEAT OUTPUT IN BLOW-DOWN WATER
J° J*L (Item 26xltem 20)+(ltem 27x1 tern 21 ) t|trir -jn
OUTPUT 1000
Ib/hr
Ib/hr
Ib/hr
kB/hr
kB/hr
kB/hr







lS.81
J/7J

/ 1,1*







FLUE CAS ANAL. (BOILERMECON) (AIR HTR) OUTLET
32
33
34
35
36
coa
0,
CO
Nj (BY DIFFERENCE)
EXCESS AIR
% VOL
% VOL
% VOL
% VOL
%
l+.H-
3.3
L>tM
tf&JJc

COAL AS FIRED
PROX. ANALYSIS
37
38
39
40
MOISTURE
VOL MATTER
FIXED CARBON
ASH
TOTAL
41
42
Btu per Ib AS FIRED
ASH SOFT TEMP.*
ASTM METHOD
% wt
-^V




/ju.^2.

COAL OR OIL AS FIRED
ULTIMATE ANALYSIS
43
44
45
46
47
40
37
CARBON
HYDROGEN
OXYGEN
NITROGEN
SULPHUR
ASH
MOISTURE
TOTAL
Ml
v-.tf


0,71



COAL PULVERIZATION
48
49
50
64
GRINDABILITY
INDEX*
FINENESS %THRU
50 M*
FINENESS %THRU
200 M*



INPUT-OUTPUT
EFFICIENCY OF UNIT %

51
52
53
44
41
OIL
FLASH
Sp. Grav
POINT F*
ity Deg. API*


VISCOSITY AT SSU*
BURNER SSF
TOTAL
% wt
Btu per
HYDROGEN
Ib

GAS
54
55
56
5;
58
59
60
61
CO
CH, METHANE
C,H, ACETYLENE
C2H4 ETHYLENE
C,H6 ETHANE
HaS
CO,
Hj
HYDROGEN
TOTAL

62
63
41
TOTAL
% wt
HYDROGEN



%VOL










DENSITY 68 F
ATM. PRESS.
Btu PER CU FT
Btu PER LB


ITEM 31 « 100
ITEM 29
HEAT LOSS EFFICIENCY
65
66
67
68
69
70
71
72
HEAT LOSS DUE TO DRY GAS
HEAT LOSS DUE TO MOISTURE IN FUEL
HEAT LOSS DUE TO H20 FROM COMB.OFH,
HEAT LOSS DUE TO COMBUST. IN REFUSE
HEAT LOSS DUE TO RADIATION
UNMEASURED LOSSES
Btu/lb
A. F. FUEL






TOTAL
EFFICIENCY = (100 - Item 71)
* Not Required for Efficiency Testing
% of A. F
FUEL
6/?o
ft,1}1)
3R3
// 2&
0tC02
c.f
I2>>IL
£6,34-

t For Point of Measurement See Par. 7.2.8.1-PTC 4.1-1964

-------
                                                    -  Ill -
 CALCULATION SHEET
                                                   TABLE  6-20
                                              ASME   TEST   FORM
                                FOR   ABBREVIATED  EFFICIENCY   TEST
    PTC4.1-b (1964)

Revised September, 1965
OWNER OF PLANT XVA
30
24
25
36

65
66
67
68
69
70
71
72
HEAT OUTPUT IN BOILER BLOW-DOWN
If impractical to weigh refuse, this
item can be esf/mafed as follows
DRY REFUSE PER LB OF AS FIRED FUE
ITEM 43
CARBON BURNED L>'~]i $7
FUEL )0°
TEST NO. 1A BOILER NO. g DATE4-X8-7
ITEM 15 ITEM 13
WATER =LB OF WATER BL OW.nOWN PFB HP y 	 — 	
1000
% ASH IN AS FIRED COAL
100 - % COMB. IN REFUSE SAMPLE D1T ,,.-.-, ...
r 1 1 K t r Ubl
|— — i IN COMBUST
ITEM^2 ITEM 23 1 SHOULD BE
A./-^ ~ (tr,$ ' ° - 7  ITEM 11)] = /jl-SZf,5~.. .
HEAT LOSS DUE TO ITEM 22 ITEM 23 o
COMBUSTIBLE IN REFUSE = Oj^RI X ^/^ / " lif-Lf->6
HEAT LOSS DUE TO TOTAL BTU RADIATION LOSS PER HR
RADIATION* LB AS FIRED FUEL - ITEM 28
UNMEASURED LOSSES **
TOTAL
EFFICIENCY = (100 -ITEM 71)
kB/hr

LUE DUST & ASH
I DIFFER MATERIALLY
riBLE CONTENT, THEY
ESTIMATED
Y. SEE SECTION 7,
ONS.
LtJ_S,
ITEM 47
267 J


Btu/lb
AS FIRED
FUEL
71o
63,3
tftf
/^.8

0.1.






LOSS x
HHV
100 =
65
	 X 1 00 =
41
— X 100 =
41
67
	 X100 =
41
68
— X100 =
41
69
41
2°- x ,00 =
41









LOSS
63o
o&

zst?

AZ6

0.MZS
0^.
13, i '6

3*6.^

t For rigo
* If lossc
            dele
                       of.
                          xcess air se« Appendix 9.2 - PTC 4.1-1964
                     ed, use ABMA Standard Radiation Loss Chart, Fig. 8, PTC 4,1-1964
** Unmeasured losses listed in PTC 4.1 but not tabulated above may by provided for by assigning a mutually
  agreed upon value for Item 70.

-------
TABLE 6-21
SUMMARY OF BOILER PERFORMANCE CALCULATIONS
Company,
Station,
Boiler No.
Tennessee
Valley
Authority
Widows Creek,
No. 6

Georgia
Power
Harllee
Branch, No. 3




Arizona Public
Service
Four Corners,
No. 4

Alabama Power
Companv
Barry, No. 4


Gulf Power
Crist, "o. 6


Firing
Mode
Baseline
Baseline

Low NOX
Low NOX
Low NOV
A
Baseline
Baseline
Baseline

Low NOX
Low NOX
Low NOX
Low NOX
Baseline
Baseline

Low NOX
Low NOX
Baseline
Baseline

Low NOX
Low NOX
Baseline

Low NOX

Test
No.
1A
IB

10-C-l
10-C-3
26-A-l
1C
ID
IE

1G
1H
52D
52E
IE
IF

12A
12B
42A
42B

19A
19B
1

26B

Load,
MW
125
128

120
125
97
490
488
483

478
463
475
465
755
775

725
704
293
283

283
255
320

350


% 02
3.3
3.6

3.0
3.3
2.8
3.0
3.7
3.0

1.2
1.3
1.9
2.0
3.4
3.1

4.3
3.7
5.0
4.5

4.6
4.3
3.6

3.2

NOX, ppm
(3% 02)
669
656

343
397
299
688
711
745


472
582
565
741
715

560
458
396
370

347
288
902

888

Coal,
% Ash
15.87
18.39

11.32
14.38
15.39
12.05
9.72
8.58

11.28
8.43
10.30
11.87
21.92
21.96

23.13
21.12
4.78
4.85

10.69
8.84
10.2

10.2

% Carbon on
Particulate
6.29
5.9

10.55
8.46
12.40
5.5
3.17
2.8

6.73
11.82
9.98
7.41
.69
.53

.18
.46
24.23
25.83

14.75
18.77
5.08

8.15

Boiler
Efficiency
86.8
86.2

86.7
86.5
85.9
90.0
90.2
90.4

90.2
90.0
88.7
89.5
88.2
88.6

88.8
89.1
88.4
88.6

88.8
88.3
88.5

88.1

-------
                                 - 113 -
6.2  Oil Fired Boilers Converted
     from Coal to Oil Firing

          As discussed in Section 2,  short-term tests  were made  on  six
coal-to-oil converted boilers.  The emission results obtained  are presented
in this section.

     6.2.1  Front-Wall Fired Boilers

          6.2.1.1   Deepwater,  Boiler  No.  3

          Boiler No. 3 of Deepwater Station is a Babcock and Wilcox designed,
front wall fired, single furnace boiler, with a maximum continuous  rating
of 313.000 pounds of steam per hour at 1350°F and 725 pounds per square inch
pressure.  It was installed in 1928 to fire pulverized coal, but has re-
cently been converted to oil firing.  There are six mechanically atomizing
burners firing in a single row across the front wall of the furnace.

          Table 6-22 summarizes operating and emission data for  the eight
tear runs-, conducted on this boiler.  Operating variables  were  gross load and
excess air level.  Gross load (includes turbine generators 3H  and 3L which
run on steam from both No. 3 and No.  5 boilers) was varied  from full load
of 57 MW down to 19 MW.  Excess air was varied from normal  operating level
down to the lowest level that could be reached without excessive CO emis-
sions (greater than 200 ppm), or a visible plume showing  from the  stack.
It should be noted that the plume from the stack under normal excess air
operation is almost invisible.  Under low excess air  test operation, the
plume would show slight "efficiency"  haze or occasional gray wisps of smoke.
Average NOX measurements are listed on both ppm NOX (3% 02, dry basis)  and
pounds NOX  (calculated as N02) per 106 Btu.  Average  % oxygen measurements
are also shown for each test run.  Each of the six sampling probes contained
two gas sampling tubes that were positioned to provide samples from the
centers of  four equal areas of each of the three ducts between the economizer
and air preheaters.  During the test  runs, one or two of  the probes con-
sistently produced 1 to 2% higher oxygen readings (lower  C02 and NOX
readings) than did the other probes,  indicating a possible  5 to 10% air
leakage into the sampling system prior to sample pumps.   Although  inspec-
tion and checking of the complete sampling system from probes to pumps  re-
vealed no leaks, the consistency of the measurements  taken  from the other
four or five probes, and the agreement of the NOX measurements from all
probes on a 3% 02, dry basis does indicate that one and sometimes  two probes
were probably leaking.  Therefore, the average % oxygen for each test run
includes data from the four or  five consistent probes, while the average
ppm NOX  (3% 02, dry basis) for each run is the average dilution-corrected
NO  measurement from all six probes.
  x

-------
                                                   TABLE 6-22
                                     SUMMARY OF OPERATING AND EMISSION DATA
                                             Atlantic City Elactric
                                        (Deepwater Station, Boiler No. 3)
                                                   Oil Firing

Test
Run

1
2
3
4
5
6
7
8
Boiler Operating Conditions
Gross (3)
Load
(MW)
56.5
57
39
39
19
19
32
32
Excess
Air

Normal
Low
Normal
Low
Normal
Low
Normal
Low
Burner No.
Firing Oil

All
All
2, 3, 4 & 5
2, 3, 4 & 5
2 and 5
2 and 5
2, 3 & 5
2, 3 & 5
Flue Gas Measurements
Smoke
Meter

0.95
1.0
0.8
1.0
0.8
0.9
0.8
1.1
%o2
(2)

6.1
5.0
5.9
5.0
9.2
8.5
7.2
6.3
PPM NOX
(3%02, Dry Basis)

142
118
133
102
143
108
135
96
POUNDS NOY ...
Per 106 Bfu(4)

0.19
0.16
0.18
0.1.4
0.19
0.14
0.18
0.13
(1)   Average of three 2-minute gas composites from 2 sample tubes per probe with 2 probes per  duct  and
     3 ducts per boiler.
(2)   Average boiler % oxygen calculated from probes 1, 2, 4 and 5 for test runs 1 and  2, and  from
     probes 2 through 6 for test runs 3 through 8.  ppm NO., calculated from all 6 probes.
(3)   Boilers No. 3 and 5 provide steam to two turbines.  Gross load data represents  the
     combined gross load of both turbines.
 (4)  Calculated as N02<

-------
                                  - 115 -
          Table 6-23 indicates the experimental design of operating variables,
with average flue gas measurements of % oxygen and ppm NOX (3% 02,  dry
basis) shown for each test run.  Figure 6-24 is a plot of ppm NOX emissions
vs. % oxygen in the flue gas for the four' gross load conditions tested,  at
normal and low excess air levels, respectively.

          Baseline operation (test run No. 1), at full load with all six
burners firing oil, produced a relatively low average emission level of
142 ppm HOX (3% 02, dry basis) or 0.19 pounds per 106 Btu.  Reducing ex-
cess air by about 5% (to 5% 02 in the flue gas from 6.1% 02) resulted in a
17% reduction in NOx emissions to 118 ppm (3% 02, dry basis).  At reduced
loads, very similar results were achieved.  At 39 MW gross load (four burn-
ers firing), normal excess air operation resulted in 133 ppm NOX, and low
excess air operation produced 102 ppm NOX, or a reduction of 23%.  At 33
MW gross load (three burners firing), normal excess air operation resulted
in 135 ppm NOX, while low excess air operation produced a 24% reduction in
NO  emissions to 96 ppm.  At the minimum gross load of 19 MW, normal excess
air operation (two burners firing),  resulted in 143 ppm NOX, while low
excess air operation at this load produced 108 ppm NOX emissions or a re-
duction of 29%.

          Although the constant, relatively low NOX emission levels over
the wide range of total loads from full load to one-third load might appear
to be inconsistent with normal experience on oil fired boilers, we believe
they can be logically explained for  this boiler.  The heat released per
square foot of heating surface at full load is relatively low in this old
boiler installed in 1928, while the  steam rate was only about 255,000 pounds
per hour, or 80% of the full load designed rate of 313,000 pounds per hour.
The fuel rate at each of the six firing burners was a relatively low 348
gallon per hour at full load  (Boiler No.  9,  for  comparison,  fired  about
820 gallons of fuel oil per hour  to give  286  ppm  NOX  emissions  at full load).
As the load was reduced, the number  of firing  burners was  proportionately
decreased so that at 39, 32 and  19 MW  the fuel rates  per  firing burner  was
maintained relatively constant at 386, 380 and 392 gallons  per  hour,
respectively.  Also at the highest fuel  rate  per burner  at  19  MW load,  the
distance between firing burners  increased to  three  times  normal firing
operation and the distance between furnance  side walls and  firing  burners
was double that for full load operating  distances.

          Table 6-24 summarizes the  average flue gas component and tem-
perature measurement for each of the eight test runs completed on Deepwater
Station, Boiler No. 3.  This unit had a baseline NOX emission level of
only 142 ppm (3% 02, dry basis) at full load.  Reduced load operation at
normal excess air resulted in maintaining NOX emission levels between 133
and 143 ppm.  The fact that load had negligible effect on the NOX emissions
strongly suggests that the bulk of the NOX was formed through the oxidation
of fuel nitrogen.

-------
                                                FIGURE 6-24
                                 PPM NOx VS % O2 MEASURED IN FLUE GAS
                                            Atlantic City Electric
                                      (Deepwater Station, Boiler  No. 3)
                                                 Oil Firing
    200
g
CO
• I-H
CO
rt
S  15°
 «  100
                                       T
           Runs 1, 3,  5 and 7 are Normal Excess Air Runs
           Runs 2, 4, 6 and 8 are Low Excess Air Runs
                                                                                   19 MW
    50
                                                 J	.	L
                                                                                  I     i	L
                                                                                                      10
                                            % Oxygen in Flue Gas

-------
                                        - 117 -
                                    TABLE 6-23
               EXPERIMENTAL DESIGN AND AVERAGE EMISSION MEASUREMENTS
                              Atlantic City Electric
                         (Deepwater Station,  Boiler No. 3)
                                    Oil Firing

AI - Normal
Excess Air
A? - Low
Excess Air
Gross Load (Boilers 3 and 5) and Number of Burners Firing
L! - 57 MW
(6 Burners)
(1) 6.1% 02 *
142 ppm NOX
(2) 5.0% 02
118 ppm NO
X
L2 - 39 MW
(4 Burners)
(3) 5.9% 02
133 ppm NOX
(4) 5.0% 02
102 ppm NO
*v x
L3 - 33 MW
(3 Burners)
(7) 7.2% 02
135 ppm NO
(8) 6.3% 02
96 ppm NOX
L^ - 19 MW
(2 Burners)
(5) 9.2% 02
143 ppm NOX
(6) 8.5% 02
108 ppm NO
*  Each cell gives test run number, average  %  oxygen and
   ppm IK)  (3% 00, dry basis).
         x      2.

-------
                                 -  118  -
                               TABLE 6-24
             FLUE GAS  EMISSION MEASUREMENTS AND TEMPERATURES
                         Atlantic  City  Electric
                    (Deepwater Station,  Boiler No. 3)
                               Oil Firing
TEST
RUN
NO.

1
2
3
4
5
6
7
8
(2)
GROSS
LOAD
(MW)
56.5
57
39
39
19
19
32
32

0?

%
6.1
5.0
5.9
5.0
9.2
8.5
7.2
6.3
FT.ITE
C09

%
9.9
10.5
9.5
10.1
7.2
7.4
8.7
9.3
GAS MKASTTRTflEJflS/^
NOy | CO
PPM $ 1 ppM y
3%02
142
118
133
102
143
108
135
96
3%02
67
81
56
349
53
74
55
141
HC
PPM G
3%02

—
1
1
1
2
1
1
Temp.

°F
601
616
491
477
417
399
454
448
(1)  Average of  three  2-minute gas composites from two  sample  tubes
     from each of 6 probes.
(2)  Boilers No. 3 and 5  provide  steam to two turbines.   Gross
     load data represents the  combined gross load of  both turbines.

-------
                                  -  119  -
          Low excess air operation successfully reduced NOX emissions  by
17 to 29%.  These low emission levels are likely to be due to the relatively
low heat release per unit volume of this furnace.   Under all conditions
tested, the NOX emission levels were significantly below the EPA new source
emission standard of about 225 ppm NOX for oil fired boilers or 0.3  pounds
NOX per 106 Btu heat input.

          6.2.1.2  Deepwater,  Boiler No.  5

          Boiler No. 5 of Deepwater  Station is a  Babcock  and Wilcox designed,
front wall fired, single furnace boiler,  with a maximum continuous rating
of 290,000 pounds of steam per hour  at 1350°F and  725  pounds per square inch
pressure.  Installed in 1928  to fire pulverized coal,  it  has recently been
converted to oil firing.  The burner arrangement  is similar  to  Boiler No. 3,
with six mechanically atomizing oil  burners arranged  in a single row across
the front wall of the furnance.

          Boilers No. 3 and 5 feed main  steam to high  pressure  Turbine
Generator 3H (12 MW capacity).  Boiler No. 5 reheats  the  exhaust steam  from
Turbine Generator 3H and feeds Turbine Generator  3L  (42 MW capacity).   Pres-
ent operating practice results in firing  boiler No. 5  with about 133% of
the fuel burned in No. 3 boiler, resulting in Boiler No.  5 having a much
higher heat release per unit  furnace volume than No. 3.

          Table 6-25 contains a summary of operating and emission data for
the four test runs conducted on Boiler No. 5.   In light of the low NOX
emission levels on sister unit No. 3, only baseline, normal and low  excess
air test runs 1 and 2 were planned for Boiler  No.  5.  However,  test  runs 1
and 2 produced NOx emission levels close to the EPA new source standard  of
225 ppm NOx for oil fired boilers, and consequently, test runs 3 and 4 were
conducted in an attempt to obtain lower NOX emissions under full load
operation.

          Baseline NOX emissions  (test run No. 1)  were 221 ppm  (3% 02,  dry
basis) or 0.29 pounds NOX per 10^ Btu under normal excess air,  full load
operation.  Low excess air operation run No. 2 resulted in a 5% reduction
in NOX emission levels to 209 ppm.   Fuel  rates in  gallons per hour per
burner were about 33% higher  (465 vs. 350) than baseline  operation on
sister unit No. 3, with its lower NOX emission rate of 142 ppm.  Test run
No. 3 was conducted while firing with five burners equipped with large
capacity tips, and with the air registers wide open on the idle burner
(No. 3) to simulate low excess air,  staged firing.  However, the higher
fuel firing rate per burner (540 vs. 465  gallons  per hour),  and single  row
of burner configuration resulted in  an essentially baseline NOX emission
level of 225 ppm for test run No. 3.  The last test run,  No. 4,  conducted
at a 22% reduced oil firing rate of  365  vs. 465 gallons per burner-hour
produced a 21% lowered NOX emission  level of 175  ppm,  compared  to the base-
line emission level of 221 ppm.  The steam rate on Boilar No. 3 was in-
creased by about 40,000 pounds per hour  to make up for the lowered steam
rate of No. 5 boiler on run No. 4.

-------
                                              TABLE 6-25
                                 SUMMARY OF OPERATING AND EMISSION DATA
                                        Atlantic City Electric
                                    (Deepwater Station, Boiler No. 5)
                                              Oil Firing
Boiler Operating Conditions
Test
Run

1
2
3
4
Gross
Load
(MW)
56
56
56
53
Excess Air
Level

Normal
Low
Low
Low
No. of Burners
Firing Oil

6
6
5<2>
6<2>
Flue Gas Measurements
Smoke
Meter

0.62
0.65
0.70
0.60
%o2

4.2
2.8
4.3
4.0
PPM NOjj
(3%02, Dry Basis)

221
209
225
175
POUNDS,NO..
PER 10 BTU

0.29
0.28
0.30
0.23
                                                                                                              ISJ
                                                                                                              O
(1)   Average boiler % oxygen .calculated for probes 2, 3, 4 and  5.   Ppm  NO.,
     (3%0o,.dry basis) calculated as arthmetric average of data for all 6 probes.
(2)   Large capacity burner tips were used on test runs 3 and 4.

-------
                                  - 121
          Boilers No. 3 and 5 utilize the same stack and there is some
flexibility in adjusting the firing rate of the two boilers at full load.
Consequently, there is probably a minimum stack NOX emission rate obtained
by judiciously balancing the heat load of the two boilers.

          Table 6-26 contains average flue gas component measurements  and
temperatures for each of the four runs completed on Deepwater  Station  No. 5
boiler.  Flue gas temperature,  percent 0-, percent CO-,  ppm NO  and  ppm CO
are shown.  All data in ppm have all been corrected to a common 3% 0~, dry
basis.  Since the hydrocarbon instrument was inoperable during the test
period, no HC measurements were obtained.

          6.2.1.3  Deepwater, Boiler No. 8

          Boiler No. 8 at the Deepwater  Station is a Babcock and Wilcox
designed, front wall fired, single furnace boiler, with a maximum continuous
rating of 560,000 Ib. steam per hour at  1005/1005°F superheat and reheat
temperatures and 1520 psi design pressure.  Installed in 1954 to fire
pulverized coal, it has recently been converted to oil firing.  The unit  is
of balanced draft construction with 16 burners arranged four high and  three
wide.  Each burner is fired by a mechanical pressure atomizing oil gun of
the return flow type.

          Table 6-27 contains a summary of operating and emission data for the
25 test runs conducted on Boiler No. 8.  Operating variables were gross  load
(data were collected at six different loads), excess  air level,  and firing
pattern  (seven different firing patterns were explored).   Excess  air  was
varied from normal operating level down  to  the  lowest  level that  could be
reached without excessive CO emissions  (greater than  200 ppm),  smoke  meter
indications greater than 1.0, or producing  more than  slightly visible stack
plumes with periodic wisps of gray smoke.   Under  normal  excess  air  opera-
tion, the stack plume is practically invisible.   Under  low excess air test
operation, the plume often would show slight  "efficiency"  haze  or occasional
gray wisps of smoke.  Boiler No. 8 is also  limited in  fan  capacity  and
superheat and reheat control, making it  difficult  to  operate at  desired
levels to achieve optimum low NO  emissions with various staging patterns.
Average ppm NO  measurements (3% 02, dry basis), pounds NO  per 10&  Btu and
average % Q£ measurements are shown in Table 6-27 for each test run.  Each...
of the four proBes contained short, medium, and long  gas sampling tubes
that were positioned to provide samples  from  the  centers of twelve  equal
duct areas located between the economizer and the  air preheater  inlet.
Flue gas composition was remarkably uniform across the  duct.

          Table 6-28 summarizes the experimental design of  operating vari-
ables, with average flue gas measurements of % oxygen and ppm NOX (3%  02,
dry basis) shown for each run.   Table 6-29 details the firing  patterns
employed during the NOX tests,  and is helpful in visualizing potential
effects of the various firing configurations.  Figure 6-25 is  a plot of ppm
NOx vs. % oxygen in the flue gas for the seven firing patterns investigated
under full load operations.  Figure 6-26 is a plot of ppm NOX  vs. %  02 in
the flue gas for intermediate and low loads.

-------
                                         - 122 -
PPM
                                     FIGURE 6-25

                                     VS % O2 IN FLUE GAS
                                 Atlantic City Electric
                           (Deepwater Station, Boiler No.  8)
                                       Full Load
                                       Oil Firing
                                        T
    250
                                    Full Load
                                    Normal Firing
                                    Pattern I
 CO
 5  200
 CQ
    150
CO
                                  O
                                             Full Load
                                             Staged Firing
                                             Pattern IV
                                                                  Load
                                                              Staged Firing
                                                              Patterns
                                           Full Load
                                           Staged Firing
                                           Pattern II
pj  100
    50
      0
                                 % O2 In Flue Gases

-------
                                     - 123 -
                                   FIGURE 6-26

                          PPM NOx VS % O2 IN FLUE GAS

                               Atlantic City Electric

                         (Deepwater Station, Boiler No. 8)

                           Intermediate and Low Leads

                                    Oil Firing
   250
w
d
ffl
 CM
o
e£
co
   200
   150
   100
    50
     0
                                                             Low Load Normal
                                                             Firing Pattern I
Intermediate Load
(68 MW) - Normal
Firing Pattern I
           Intermediate Load
           (67 MW) - Staged
          Firing Pattern n
                                     Intermediate Load
                                     (66 MW) - Staged
                                     Firing Pattern in
                                                    Low Load Staged
                                                    Firing Pattern n
            11 - 52 MW- Normal Air
            12 & 16 - 52 & 50 MW - Staged Firing Patterns
            13 - Only 5 of Top Burners Firing - Others Off -
                Normal Firing Pattern I
            26 - All Burners Operating with Small Oil Guns
                 Normal Firing Pattern I
                            I
                                       3          4

                                   % O2 in Flue Gas

-------
                      - 124 -
                  TABLE 6-26
FLUE GAS EMISSION MEASUREMENTS AND TEMPERATURES
            Atlantic City Electric
       (Deepwater Station, Boiler No. 5)
                  Oil Firing

TEST
RUN
NO.

1
2
: 3
; 4

GRUob
LOAD
(MW)

56
56
56
53
AVERAGE FLUE GAS MEASUREMENTS
0,

%
4.2
2.8
4.3
4.0
CO,

%
11.9
12.5
11.7
11.8
NO
Fra
(3%02)
221
209
225
175
CO
WH
(3%02)
55
84
79
83
Temp.

°F
569
547
561
527

-------
SUMMARY OF OPERATING AND EMISSION DATA
        Atlantic City Electric
   (Deepwater Station, Boiler No. 8)
              Oil Firing

Date


5/16

5/17



5/19




5/20

5/24





5/26






Test
Run
No.
1
2
1A
4
6A
5A
7
8
9
10
11
12
16
14
13
17
18
19
20
21
22
23
24
25
26
Boiler Operating conditions
Gross
Load
MW
83
81
82.5
81
82
83
68
66
66
67
52
52
50
22
22
83
82
82
81
47
31
29.5
22
23
23
Excess
Air
Level
Normal
Low
Normal
Low
Low
Normal
Normal
Low
Low
Low
Normal
Low
Low
Low
Normal
Low
Low
Low
Low
Normal
Low
Low
Low
Low
Normal
Firing Pattern
(Burners on
Air Only)
Normal (None)
Normal (None)
Normal (None)
Staged (84 Row)
Staged (84S,84N,82C)
Staged (84S,84N,82C)
Normal (None)
Normal (None)
Staged (84 Row)
Staged (84C,83S,83N)
Normal (None)
Staged (84S.84N)
Staged (83S.83N)
Staged (84S.84N)
Normal (None)
Staged (83 Row)
Staged (84C.83S.83N)
Staged (83S.83N.82C)
Staged (83C.82S.82N)
Normal (None)
Staged (83 Row)
Staged (83S,83N,82C)
Staged (83S.83N.82C)
Staged (83 Row)
Normal (None)
Flue Gas Measurements

Smoke
Meter
0.75
1.0
0.7
0.8
0.8
0.75
0.75
0.9
0.8
0.9
0.75
1.0
0.9
0.8
•0.75
0.7
0.7
0.7
0.65
0.65
0.60
0.60
0.60
0.60
0.60
%02


4. .5
2.3
4.1
5.2
4.4
5.3
5.5
2.6
4.9
5.0
6.9
4.7
4.6
12.9
12.1
4.4
4.5
4.7
4.4
7.1
9.4
9.5
10.7
10.0
10.2
PPM NO
(3%02, Dry)

246
188
208
136
165
192
204
172
124
160
181
94
124
158
191
132
124
142
123
197
157
162
172
162
155
POUNDS NOx
PER 10 BTU

0.33
0.25
0.28
0.18
0.22
0.25
0.27
0.23
0.16
0.21
0.24
0.13
0.16
0.21
0.25
0.18
0.16
0.19
0.16
0.26
0.21
0.22
0-23
0.22
0.21
                                                                                 SJ
                                                                                 Ln

-------
                                                       TABLE  6-28
                               EXPERIMENTAL DESIGN  AND AVERAGE EMISSION MEASUREMENTS
                                                Atlantic City  Electric
                                           (Deepwater Station,  Boiler No. 8)
                                                       Oil Firing


sl
Normal
Firing
Pattern I
S2
Staged
Firing
Pattern II
3 Staged
Firing
Pattern III
A Staged
Firing
Pattern IV
ss
Staged
Firing
Pattern
s6
Staged
Firing
Pattern
7 Staged
Firing
Pattern

Al
©
4.5% 02
246 PPM
NOx


5.37. 02
192 PPM
NOx



Full Load
Lt - 82 MW
A1-A
©
4. IX 02
208 PPM
HOx






A2
®
2.3% 02
188 PPM
NOx
©
5.2% 02
136 PPM
NOx
0)
4.4% 02
132 PPM
NOx
@
^..4% 02
165 PPM
NOx
®
4.57. 02
124 PPM
NOx
©
*.7% 02
142 PPM
NOx
©
4.4% 02
123 PPM
NOX
Intermediate Load
L2 - 68 MW
Al
®
5.5% 02
204 PPM
NO,






A2
2.6% 02
172 PPM
NOx
®
4.9% 02
124 PPM
NOX
©
5.0% 02
160 PPM
NOx




Inter. Load
L3 - 52 MW
Al
O
6.9Z 02
181 PPM
NOX






A2

4.7% 02
94 PPM
NOX
©
4.647, 0?
124 PPM
NOx




Inter. Load
L^ - 47 MW
Al
7.17. 02
197 PPM
NO,






Inter. Load
L5 - 30 MW
A2

Q*
T.4% 02
157 PPM
NOx
©*
T.57. 02
162 PPM
NOx




Low Load
t6 - 22 MW
Al
0
12.1% 02
191 PPM NOX
©
TO. 27. 02
155 PPM NOx






A2

©
12.97. 02
158 PPM
NOx
©*
10.77. 02
172 PPM
NOx
© *
in o2
162 PPM
NOx


J
Small Oil Guns in Operating Burners
NOTE:  Figures in boxes gives test run number,  average 7. Oxygen and PPM NOx  (3X °2. Dry Basis)

-------
                                                       TABLE 6-29
                                        FIRING  PATTERNS USED DURING NOX  TESTING
                                                 Atlantic City Electric
                                            (Deepwater Station, Boiler No.  8)
                                                       Oil Firing
Full Load 82 MW
Sl
Run 1 & 2
000
000
000
too
Sl
Run 1A
000
000
000
0»0
S2
Run 4
AM
000
000
000
S3
Run 17
000
AAA
000
000
S4
Run 5A, 6A
AOA
000
OAO
000
S5
Run 18
OAO
AOA
000
000
S6
Run 19
000
AOA
OAO
000
S7
Run 20
000
OAO
AOA
000
Intermediate Load 68 MW
Sl
Run 7 & 8
000
000
000
•0«
S2
"Run 9
AAA
000
000
000
S3
Run 10
OAO
AOA
000
000
Intermediate Load
52 MW
Sl
Run 11
000
000
0«0
•••
S2
Run 12
AOA
000
000
•09
S3
Run 16
000
AOA
000
«()•
                                                                                                                          S3
                                                                                                                          •vl
Burner Arrangement
       si >-i si
       •U 0) 4J
        3 -U M
        o c o
        
-------
                                  - 128 -


          Baseline operation at  full load (test run No.  1)  conducted with
all burners operating normally,  except burner 81 south off, produced average
flue gas NO  concentrations of 246 ppm (3% 0_, dry basis) at 4.5 % 0^  in
the flue gas.  This is  the only  measurement recorded which exceeds trie
EPA-recommended emission  standard of about 225 ppm for oil fired boilers.
Reducing the excess air level to that corresponding to 2.3 % 02 in the flue
gas resulted in an average level of 188 ppm NO  (3% 0^  dry basis), or a
decrease of 23.5% from  baseline  conditions.  Other staging patterns (tests
4, 5A, 6A, 17, 18, 19 and 20) achieved further reductions in N0x emissions
to as low as 123 ppm NO  (50% reduction) , but operating conditions were
sometimes marginal.  AsXindicated by the results in the attached tables,
it is possible to operate at significantly reduced N0x emission levels at
all loads.  However,  these reductions  were  achieved  at  the expense of  re-
duced superheat and reheat temperatures.   Superheat  temperatures  were  as
much as 35°F low and  55°F on  reheat  during  some tests at full  load.  At
lower loads decreases as  much  as 140°F in  superheat  and 185°F  in  reheat
resulted.  Superheat  and  reheat  surface  would have to be added if the  unit
were to be operated full  time  at low NOX emission conditions.

          Carbon monoxide emission levels were generally lower than 100 ppm
(well within the arbitrary  limitation of 200 ppm criteria) but occasional
wisps of gray stack emissions were observed during some tests,  which may not
be entirely acceptable.  Smoke indicator readings during some  of  the  "low
NO " tests were slightly  higher  than normal but by no means exorbitant.
If low NO  emission firing  conditions were  to be employed  full time,  a
thorough investigation  of combustion  conditions would be warranted since bad
or worn sprayer plates  on individual  (single) burners could account for
these undesirable visible emissions.

          With some firing  configurations,  fans were operated  at  or near
their maximum output.   Fortunately,  this did not occur  at  optimum NOX
reduction conditions  but  fan capacity limitations under some conditions of
"low NOX" operation might be a problem.

          Baseline operation at  the intermediate load of 68 MW (test  No.  7)
with all burners operating  in the normal manner,  and wing burners 81S and
81N off, produced average flue gas concentrations of 204 ppm NOX (3%  02,
dry basis) at 5.5 % 0?  in the  flue gas.  Reducing  the excess air  to a
level of 2.6 % 0- in  flue gas, reduced NO   emissions  to an average of  172
ppm, i.e., a reduction  of about  16%.   Other staging patterns (tests No. 9
and 10) made further  reductions  in N0x emissions  to a low  of 124  ppm;  a 40%
reduction.

          At 52 MW  baseline NO   emission  at 6.9  5 0- in the flue gas  was
 181 ppm (test No. 11).  This was reduced to 124 ppm NO   (31% reduction) by
 staging and reducing  average excess air to a level of $.6% 02  in  the  flue
 gas.

           At  low load  (22 MW)  with large oil guns (test No. 13),  the  baseline
 NO  emissions  was  191 ppm NO  at 12.1% 0  in the flue gas.  Replacing the
 large sprayer  plates  with smaller ones and firing all 12 burners  produced a

-------
                                   - 129  -
baseline NOX emission  (test No.  26)  of  155 ppm at the 10.2% oxygen level.
Applying staged firing  techniques  (test No.  14),  reduced the baseline NOX
emission of 191 ppm down  to 158  ppm,  but,  interestingly enough,  staging
patterns in comparable  tests  (tests  No. 24 and 25 with small atomizers)
produced higher emissions  (172 and 162  ppm)  than  the 155 ppm baseline NOX
emission (test No. 26).   Evidently,  with the high excess air levels employed
during these tests, the air/fuel ratio  in the operating burners  was too high
for staging to be effective for  NOX  emission control.

          Table 6-30 contains average flue gas component emission measure-
ments and flue gas temperatures.  Percent  02» percent CO™, ppm NO  , ppm CO
are listed.  The ppm data  have been  corrected to  a 3% 0_, dry basis.

          To sum up, baseline NOX emissions  on Boiler No. 8 of 246 ppm are
slightly higher than the  new source  standard of about 225 ppm for oil
fired boilers.  Baseline  emissions at other  loads are normally below 200
ppm NOX  (3% 02, dry basis).  Staged  firing was effective at all loads in
reducing NOX emission  levels, except in two  cases at  low load, with high
levels of excess air.   The NOX emission levels obtained with staged firing
are all well below the  EPA standard  for new  oil fired boilers.  Because of
fan and steam temperature  control limitations, however,  the NOX emission
reductions obtained were  not always  made at  acceptable operating conditions.
Both superheat and reheat  steam  temperatures during "low NOX" emission con-
ditions were low at all loads which  seriously effect  overall plant efficiency.
Full time "low NOX" operation would  require  the addition of superheat and
reheat surface to overcome this  undesirable  deficiency.  Also, under some
conditions, visible grayish wisps were  emitted from the  stack, which could
be attributed to damaged  or worn sprayer plates on individual (single)
burners.  Long term operation at "low NO " conditions, therefore,  should be
preceded by a thorough revamping of  the combustion system (including con-
trols) to eliminate these undesirable visible emissions.

          6.2.1.4  Deefrwater, Boiler No. 9

          Boiler No. 9  at  Deepwater  Station is a  Combustion Engineering
designed front wall fired, single furnace boiler, with  a maximum continuous
rating of 550,000 pounds  of steam per hour.   It was  installed in 1957  to
fire pulverized coal and has been recently converted  to oil firing.  The
furnace width is 24 feet  3 inches and the furnace volume is 33,000 cubic
feet with a heating surface of 8,625 square feet. Main  steam operating
pressure is 1325 pounds per square inch at a temperature of 765°F.   There
are six mechanical atomizing burners arranged in  three  rows of two burners
each.

          Table 6-31 lists operating and emissions data  for the seven test
runs conducted on  this boiler.   Operating variables  were excess  air level
(normal  and low)  and burner  firing  patterns (normal  firing  plus  three staged
firing patterns).   Gross  load was  maintained at about full  rated capacity
(20.8  to 22.8 MW).  Low excess air was  defined as the minimum excess air
that produced only  a slight visible  plume with periodic wisps  of gray smoke.

-------
                  TABLE 6-30
FLUE GAS EMISSION MEASUREMENTS AND TEMPERATURES

            Atlantic City Electric

       (Deepwater Station, Boiler No. 8)

                  Oil Firing
TEST
RUN
N 1
1
2
1A
A
6A
5A
7
8
9
10
11
12
16
14
13
17
18
19
20
21
22
23
24
25
26
GROSS
LOAD
(M 6)
83
81
82.5
81
82
83
68
66
66
67
52
52
50
22
22
83
82
82
81
47
31
29.5
22
23
23
AVERAGE FLUE GAS MEASUREMENTS
°2
%

4.5
2.3
A.I
5.2
A. A
5.3
5.5
2.6
4.9
5.0
6.9
A. 7
4.6
12.9
12.1
A. 4
4.5
4.7
4. A
7.1
9. A
9.5
10.7
10.0
10.2
co2
%

11.6
13.0
11.5
10.5
11.9
11.3
10.6
12.4
11.2
11.3
9.6
11.2
11.0
4.8
5.5
11.6
11.9
11.6
11.8
9.4
7.5
7.1
6.5
6.5
6.7
NO
X
PPM
(3% 02)
246
188
208
136
165
192
204
172
12A
160
181
9A
12A
158
191
132
12A
1A2
123
197
157
162
172
162
155
CO
PPM
(3% 02)
49
10A
56
83
7A
7A
62
65
59
60
6A
6A
6A
10A
80
78
8A
70
6A
63
72
70
66
64
66
TEMP.
°F

620
579
615
608
608
615
607
547
570
607
593
517
521
495
522
609
590
600
595
560
520
505
498
490
495
                                                                                     OJ
                                                                                     o

-------
                                             TABLE 6-31
                               SUMMARY OF OPERATING AND EMISSION  DATA

                                       Atlantic City Electric

                                  (Deepwater  Station,  Boiler No.  8)

                                             Oil Firing
Boiler Operating Conditions
Test
Run
No.
1
2
3
4
5
6
7
Gross
Load
(MW)
22.8
22.8
21.7
21.4
20.8
20.8
21.9
Excess
Air
Level
Nor
Low
Nor.
Low
Low
Nor.
Low
Firing Pattern
(Burners on (~^
Air only)
Nor. -(None)
Nor. -(None)
Staged-(l,4)-I
Staged-(l,4)-I
Staged-(l,5)-II
Staged-(l,5)-II
Staged-(2,5)-III
Flue Gas Measurements

%o2

1.8
1.0
3.8
2.6
4.2
4.8
2.6
" PPM NOX I POUNDS£NOY
(3%02, Dry)

286
253
122
101
150
152
123
PER 10°BTU

0.38
0.34
0.16
0.13
0.20
0.20
0.16
                                                                                                              u>
                                                                                                              M
                                                                                                              I
(1)   Flue gas measurements made on gas smaples from 12 individual sampling tubes.
     Measurements shown are averages of 2 analyses from each of three sampling tubes  (short,
     medium and long) per probe.
(2)   Burner configuration
                           Top
                           Middle
                           Bottom
Q) ©
G ©

-------
                                   - 132  -
 Average ppm NOX measurements  (3% 02, dry basis),pounds NOX per 10^ Btu and
 average % 02 measurements are shown for each test run.  Each of the four
 probes contained short, medium and long gas sampling tubes that were posi-
 tioned to provide samples from the centers of twelve equal duct areas
 located between the economizer and air preheaters.  Flue gas composition
 was uniform across the duct except for the staggered, staged-firing pattern
 II, as discussed below.

           Table 6-32 indicates the experimental design of operating variables
 with average flue gas measurements of  % oxygen and ppm NOX (3%  02, dry
 basis) shown for each run.  A simplified furnace burner diagram is shown
 at the bottom of Table 6-32 to aid in  visualizing the  firing  configurations
 used in the three different staged firing patterns.  Figure 6-27 is a plot
 of ppm NOX emission vs % oxygen in the flue gas  for  the four  firing patterns
 investigated.

           Baseline operations (test run No. 1) conducted with all six
 burners firing oil, produced average flue gas concentrations of 286  ppm NOX
 (3% 02, dry basis) or 0.38 pounds N0x  per 106 Btu heat input  at 1.8%
 oxygen.  Reducing the excess air level to that corresponding to 1.0%  oxygen
 in the flue gas, resulted in an average level of 253 ppm NOX (3% 02,  dry
 basis) or a decrease of 12% from baseline conditions.   Staged firing  pat-
 tern I (top row of burners on air only) operation resulted, as  expected,
 in significant reductions in NOX emission levels; 122  ppm at  3.8% oxygen
 and 101 ppm at 2.6% 02-   It should be  noted that only  about 80% of  the  air
 required for complete combustion of the fuel oil entered the  active burners
 in run No.  3,  and only about 75% of stoichiometrically required air entered
 the active burners in run No.  4.

           Staged firing pattern II (Burners 1 and 5 on air only) operation
 did not produce as much NOX emission reduction as staged firing pattern I,
 as shown by test runs 5 and 6, compared to runs 3 and  4.  Staged firing
 pattern II produced an air-fuel imbalance with the left half  of the
 furnace having a higher excess air level than the right half  of the
 furnace.   This resulted in raising the minimum excess  air level of  2.5%
 02 in the flue gas achieved  using staged  firing  pattern I,  to 4.2% 0, when
 using staged pattern  II.                                            L

           Run  No.  7 made with  low excess air and staged firing  pattern  III
was  conducted  in an attempt  to achieve low NOX emissions with increased
 superheat  temperatures.   The NOX level of 123 ppm obtained in run No.  7
was  not  as  low as  staged pattern I operation,  but superheat temperature
 increased  by about  5°F (760°F  vs  755°F as measured at  the turbine
 throttle,  point  12).

          Table 6-33 lists average flue gas component measurements and
temperatures for each of the seven test runs completed—Deepwater Station
Boiler No. 9.  Percent 02, percent CO-, ppm NO , ppm CO and "F temperatures
are shown.

-------
                                        - 133 -

                                     FIGURE 6-27
                      PPM NOx VS % O2 MEASURED IN FLUE GAS
                                 Atlantic City Electric
                             (B. L. England, Boiler No. 9)
                                      Oil Firing
                         i     ,	•—   |    -f     |	,	p-
M
.1-1
%
n
    300
    250
                                       Normal Firing Pattern
 eq  200
O

    15°
   100
                                  Firing
                            Pattern II

   Staged Firring Pattern in
                   Staged Firing Pattern I
    50
See Table 14 for Staged Firing Patterns
Boiler Gross Load = 21-23 MW
     0
   1
        0
  3         4
% 02 in Flue Gas

-------
                                - 134 -
                              TABLE 6-32
         EXPERIMENTAL DESIGN AND AVERAGE EMISSION MEASUREMENTS
                        Atlantic City Electric
                   (Deepwater Station,  Boiler No.  9)
                              Oil Firing

S, -Normal
Firing
Pattern:
S2-Staged
Firing
Pattern-I:
S3~Staged
Firing
Pattern-II:
S4-Staged
Firing
Pattern-Ill:
Oil in 00
All 00
Burners 00
Air Only AA
In Top 00
Burners 00
Air Only AO
in Burners OA
No. 1 & 5 00
Air Only 00
in Middle AA
Burners 00
Full Load
(21 - 23 MW Gross)
A^-Normal
Excess Air
(1) 1.8% 02 *
286 ppm NOX
(3) 3.8% 02
122 ppm NOX
(6) 4.8% 02
152 ppm NOX

A2-Low
Excess Air
(2) 1.0% 02
253 ppm NOX
(4) 2.6% 02
101 ppm NOX
(5) 4.2% 02
150 ppm NOX
(7) 2.6% 02
123 ppm NOX
*  Each cell gives test run number, average % oxygen and ppm  NOX
   (3% 02, dry basis).
                        Top Row
                        Middle Row
                        Bottom Row
         Furnace Front:
         Burner
         Configuration

-------
                   - 135 -
                  TABLE 6-33
FLUE GAS EMISSION MEASUREMENTS AND TEMPERATURES
            Atlantic City Electric
       (Deepwater Station, Boiler No. 9)
                  Oil Firing

TEST
RUN
NO.

1
2
3
4
5
6
7

GROSS
LOAD

(MW)
22.8
22.8
21.7
21.4
20.8
20.8
21.0
FLUE GAS MEASUREMENTS

09

%
1.8
1.0
3.8
2.6
4.2
4.8
2.6
CO?

%
13.5
14.0
11.5
12.6
11.4
10.9
12.4
NOy
PPM
(3%02)
286
253
122
101
150
152
123
CO
PPM
(3%02)
44
97
45
64
60
48
53
HC
PPM
(3%02)

—
—
—
—
—

Temp.

°F
739
717
734
717
717
726
703

-------
                                   - 136 -
            To sum up,  this boiler  has baseline NO  emissions of 286 ppm.
  Low excess air plus staged firing operation  resulted in a significant
  lowering of NO  emissions, as  shown in Figure 6-27.  Three different
  staged firing patterns  were effective with staged pattern I (top burners
  on air only) producing  the lowest average NO emission level of 101 ppm
  (3% 02, dry basis).  The NO emission levels reached with staged firing
  are all well below the  EPA recommended standards for  oil fired boilers.
  It was possible to reduce NO  emissions to these levels for this boiler
  without any adverse effects such  as significantly increased smoke and
  unburned combustible  emissions, and reduced  boiler operability.

      6.2.2   Cyclone Fired  Boilers

           6.2.2.1  B.  L. England,  Boiler No.  1

           Boiler No.  1  at  the  B.L. England Station is a Babcock & Wilcox
 Company, cyclone fired  pressurized boiler with  a maximum continuous  rating
 of 930,000  Ib.  steam/hour.   It was installed in 1957, and has recently  been
 converted to crude  oil  firing.  Design pressure is 1815 psi, and electricity
 output  is 136 MW gross  (127  MW net) at steam and reheat temperatures  of
 1000/1000°F.  The boiler is  fired by single, mechanical atomizing oil burn-
 ers in  each  of  the  three cyclones, which are arranged with two of them  on
 one level, with the third  one elevated between  them in a triangular  fashion
 on the  front wall of  the furnace.

           Table 6-34 lists operating and emissions data for the seven  test
 runs conducted on this boiler.   Operating  variables were excess air  (normal,
 intermediate, and low) and load (full,  intermediate,  and low).   Gross load
 was maintained at about full rated capacity on crude oil firing (132-133 MW)
 at normal,  intermediate, and low excess  air firing conditions.   Tests were
 also made at three similar excess  air  levels  at intermediate loads of 103-
 105 MW.  Emission data were also obtained  at  normal excess air  conditions
 at "minimum" load (62 MW).   Low excess air at full load was defined as
 1.1% 02 on the control board oxygen meter  (0.5%  avg. 0- measured by the
 Exxon van).   At these  levels, smoke density on ACE's smoke meter was normal
 (30), and no visible emissions  were apparent  from the stack.   Carbon monoxide
 emissions as measured  by the Esso  van, however,  were  excessive  and,  there-
 fore, operation at  such  low level  of excess air would not  be  recommended.
 Low excess  air for  the intermediate load of about 103 gross IIW's was de-
 fined as the minimum excess air that produced only a  slightly visible stack
 plume,  no appreciable  increase  in  smoke density indication, and reasonable
(about 200 ppm max.)  CO emissions.  Average ppm NO  measurements (3% 0
 dry basis)  pounds  N0x/10b Btu and  average % 02 measurements are shown2for
 each test run.  Each of the four probes  contained short,  medium,  and long
 gas sampling tubes  which were positioned  to provide samples from the centers
 of twelve equal duct areas located between the economizer  and  the  air pre-
 heaters.

-------
                                           TABLE 6-34
                             SUMMARY OF OPERATING AND  EMISSION DATA
                                     Atlantic  City Electric
                                  (B.  L.  England,  Boiler No.  1)
                                           Oil Firing

Test
Run
No.
1
2
3
4

5
6
7
Boiler Operating Conditions
Gross
Load
MW
133
133
132
62

105
105
103
Excess
Air
Level
Normal
Inter.
Low(2)
Normal

Normal
Inter.
Low

Firing
Pattern
All Cyc. On
All Cyc. On
All Cyc. On
Middle Cyc.
Off
All Cyc. On
All Cyc. On
All Cyc. On
Average Flue Gas Measurements

Smoke
Density
30
30*
30
24

26
26
25

%o2
1.5
1.1
0.5
4.2

2.7
2.4
1.0

PPM NOx
(3%02, Dry)
441
396
313
261

404
364
241

POUND S6NOX
PER 10 BTU
0.59
0.53
0.42
0.35

0.54
0.48
0.32
(1)   Flue  gas  measurements made on composite gas samples from 3 individual  sampling tubes.
     Measurements shown are averages of 3 analyses from three sampling tubes  (short,  medium,
     and long) for each of 4 probes.
(2)   Excessively high CO emissions at this condition.

-------
                                 - 138 -
           Table  6-35  indicates the experimental design of operating variables
 with average flue gas measurements  of % oxygen and ppm NO  (3% 02,  dry basis)
 shown for each run.   Normal firing  patterns with all three cyclones firing
 were employed for all, except low load operation.   In the latter case, the
 middle or upper  cyclone was taken out  of service-  Figure  6-28  is a  plot of
 ppm  NOX emission vs.  % oxygen in the  flue gas for  the three loads tested.

           Baseline operations (test  run No.  1)  conducted  with  all  three
 cyclones operated normally, produced  average flue  gas concentrations  of 441
 ppm  NOX (3%  02,  dry basis)  at 1.5% oxygen.   Reducing the  excess air level
 to 1.1 and 0.5%  oxygen in the flue gas resulted in a reduction in  average
 emission levels  at this  load to  396  and 313  ppm NOX (3% 02,  dry basis),
 respectively.  Baseline  operation at  105 MW output produced  404 ppm NOX
 (3%  02,  dry  basis) at the level  of 2.7% 02  in the  flue gas.  Reducing excess
 air  to 2.4 and 1.0% 02 in the flue gas reduced  NOX emissions to 364 and  241
 ppm,  respectively, at the intermediate load.  At the minimum load of  62 MW,
 a baseline emission level of 261 ppm  NOX  (3% 02, dry basis)  was measured at
 4.2% oxygen.   This level  is about the same  as the  emissions  at the  inter-
 mediate load level of 105 MW at  low excess air  conditions, indicating the
 particularly significant  contribution of fuel nitrogen oxidation to NO
 emission at  intermediate  to low  load  levels,  i.e.,  at lowered  combustion
 intensity conditions.

           Decreasing  excess air  levels at both  full and intermediate  loads
 had  a substantial effect  on reducing  NOX emission  levels.  With cyclone
 operation, at  least at present,  staged firing patterns which might  effect
 further reductions are not  possible.

           Table  6-36  lists  average flue gas component measurements  and
 temperatures for each  test  run.  Percent 0 , percent C0?,  ppm NO ,  ppm
 CO and  temperatures are shown.  The ppm data have been correctedXto a 3%
 02,  dry basis.

           To sum up,  this boiler has baseline NOX  emissions of  441 ppm
which are  higher than the original recommended new  source emission standards
 of about  225 ppm for  oil  fired boilers.  Low excess  air operation at full
 and  intermediate loads resulted in significant  lowering of NOX  emissions
 as shown  in Figure 6-28.  However, decreases in load and reductions in
 excess  air levels could not  reduce emissions below  the recommended standards
 for  new boilers  which are subject to reassessment  at present by EPA).

           6.2.2.2   B. L.  England, Boiler N0. 2

           Boiler  No.  2 at ACE's B.L. England Station is a Babcock & Wilcox
Company, cyclone  fired, pressurized boiler with a maximum continuous rating
of 1,250,000 Ib.  of steam per hour.   The unit was  installed in  1964, and has
recently been converted to  crude oil firing.  Electricity output is 168 MW
gross  (160 MW net) at  design pressure  of 1815 psi, with 1000/1000°F super-
heat  and reheat  temperatures.  Each of  the four cyclones are fired by a
single mechanical pressure,  atomizing  oil gun.  The  four cyclones are
arranged in a square  pattern in the front wall of  the boiler,  two at each
 elevation  as detailed  in Table 6-38.

-------
                                                    TABLE 6-35
                               EXPERIMENTAL DESIGN AND AVERAGE EMISSION MEASUREMENTS
                                              Atlantic City Electric
                                           (B. L. England, Boiler No. 1)
                                                    Oil Firing





S. Normal (^
Firing ^<
Pattern ( ) ( )
Cyclone
Arrangement

Full Load 133 MW
A.
Norma 1
Air
^ 1.5% 02
441 PPM
NO
X

A
Inter
Air
(2> 1.1% 02
396 PPM
NO
X

A
Low
Air
*2) 0.5% o2
313 PPM
NO
X


Intermediate Load 105 MW
Al
Norma I
Air
^ 2.7% 02
404 PPM
NO
X

A
Inter
Air
© 2.4% 02
364 PPM
NO
X

A
Low
Air
1.0% 02
241 PPM
NO
X

Low Load
62 MW
Al
Normal
Air
® f.2Z 02
261 PPM
NO
X

                                                                                                                        UJ
                                                                                                                        VO
*  B Cyclone  Off

-------
                                   - 140 -
                                Figure 6-28
                   PPM NOx VS O2 MEASURED IN FLUE GAS
                             Atlantic City Electric
                          (B. L. England, Boiler No.  1)
                                  Oil Firing
                                              I
450
400
350
300
                        Full Load - Normal Firing Pattern
Intermediate Load -
Normal Firing Pattern
250
                                                    Low Load
200
150
100
    0
                                   in Flue Gas

-------
              TABLE 6-36
FLUE GAS MEASUREMENTS AND TEMPERATURES
        Atlantic City Electric
     (B. L. England, Boiler No. 1)
              Oil Firing
TEST
RUN
NO.
1
2
3
4
5
6
7
GROSS
LOAD
MW
133
133
132
62
105
105
103
AVERAGE FLUE GAS MEASUREMENTS
°2
%
1.5
1.1
0.5
4.2
2.7
2.4
1.0
co2
%
13.1
13.1
13.2
11.9
12.7
12.9
13.8
NO
X
ppm
(3% 02)
441
396
313
261
404
364
241
CO
ppm
(3% 02)
57
74
1523
54
59
53
68
TEMP.
°F
762
760
748
626
727
715
697

-------
                                  - 142 -
           Table 6-37  lists operating and emission data for the two test runs
 conducted on this  boiler.  As  agreed upon with  ACE,  the  only  operating
 variable during these tests  was  excess  air.   Low excess  air was  defined as
 the  minimum excess air that  produced only a  slight visible plume with
 periodic wisps  of  gray smoke,  no appreciable increase  in smoke meter indica-
 tions,  and reasonable increases  in CO emission  levels  (i.e.,  <200 ppm).
 Average ppm NOX measurements (3% 02, dry basis)  pounds NOX/10° Btu and
 average % 02 measurements are  shown in Table 6-37 for each test run.   Each of
 the  four probes  contained short,  medium, and  long gas sampling tubes that
 were positioned  to provide samples  from the  centers  of equal  areas across
 the  width of the duct at each  probe.  Gas sampling probes were located
 between the economizers and  the  air preheater.   Flue gas composition, ex-
 cept for probe No.  1  located on  the left hand side of the boiler, was
 fairly  uniform.  Unbalanced  gas  flow was experienced on  the unit with
 the  major part of  the flow concentrated on the left hand  side  at  probe
 No.  1.

           Table  6-38  shows the operating variables, excess air, with  average
 flue gas measurements of  % oxygen and ppm NOX (3% 00,  dry basis) for each
 run.  The cyclone  configuration  is  shown at the bottom of Table 6-38.

           Baseline operations  (test run No.  1)  conducted at  full load  with
 all  four cyclones  firing  crude oil, produced average flue gas NOX concen-
 trations of 361 ppm (3% 02,  dry  basis)  at 2.2%  oxygen.   Reducing the excess
 air  level to that  corresponding  to 1.6% oxygen  in the  flue gas resulted in
 an average level of 303 ppm  NOX  (3% 02, dry  basis),  or a decrease of 16%
 from baseline conditions.

           Table  6-39  lists average flue gas  comporert measurements and  tem-
 peratures for each  test run.   Percent  0_,  percent C02,  ppm NO  , ppm CO and
 temperatures are shown.  The ppm data are listed on  a  3% 0   dry basis.

           To sum up,  this boiler  has baseline NOX  emissions of 361 ppm  NO
which are higher than the original  EPA  recommended standards  of  about 225X
 ppm  for new oil  fired boilers.   Low excess air operation  resulted in a 16%
reduction in NOX emissions,  but  could not reduce them below recommended
standard  levels.   This reduction  in NO  emissions was achieved without  any
adverse  effects, such as significantly  increased smoke,  unburned combustible
emissions,  or reduced operability.

-------
                                         TABLE 6-37
                           SUMMARY OF OPERATING AND EMISSION DATA

                                   Atlantic City Electric
                                (B. L. England, Boiler No.  2)

                                         Oil Firing
Boiler Operating Conditions

Test
No.
1(2>

2(2)
Gross
Load
MW
167

167
Excess
Air
Level
Normal

Low

Firing
Pattern
All Burners
On
ii
Flue Gas Measurements

Smoke
Meter
24

24

%o2
2.2

1.6

PPM NOX
(3%02, Dry)
361

303

POUND S,NOx
PER 10 BTU
0.48

0.42
                                                                                                         to
                                                                                                         I
(1)   Flue gas measurements are averages of three composite flue
     gas samples taken from each of 4 probes.

-------
                         - 144  -
                        TABLE  6-38
   EXPERIMENTAL DESIGN AND AVERAGE  EMISSION MEASUREMENTS
                  Atlantic City Electric
               (B. L.  England, Boiler No.  2)
                        Oil Firing





S^ Normal
Firing
Pattern


Full Load
167 MV
AI Normal
Excess
Air

2.2% 02

361 PPM
NOV
A.
A2 Low
Excess
Air

1.6% 0
L

303 PPM
NOV
A.
                         O   O
                                      Top Row
Bottom Row
                       Cyclone Configuration
NOTE:  Each run number gives average % oxygen and ppm NO
       (3% 02 dry basis).

-------
                                        TABLE 6-39
                      FLUE GAS EMISSION MEASUREMENTS AND TEMPERATURES
                                  Atlantic City Electric
                               (B. L. England, Boiler No. 2)
                                        Oil Firing

DATE



5/8/73


TEST
RUN
NO .



1
2
GROSS
LOAD
MW



167
167
FLUE GAS MEASUREMENTS (1)
°2


%

2.2
1.6
co2


%

13.5
13.5
NO
x

ppm @
3% 02

361
303
CO

ppm @
3% 02

85
231

TEMPERATURES


°F

701
698
(1)   Average of three 2-minute gas composites from each of four probes.

-------
                                   -  146 -
                          7.   RECOMMENDATIONS  FOR
                             FURTHER FIELD  TESTING
           As discussed  in  Section 2, major  problem areas  and  potential
 limitations  of  combustion  control techniques  for  NOX reduction that  remain
 for  coal  fired  boilers  have been  well  defined.  Primary emphasis  in
 further field test  programs should be  placed  on the  longer period, dif-
 ficult operating problems  of coal fired  boilers under "low NOX" combustion
 control as detailed below.   In addition,  gas  turbines and stationary
 internal  combustion engines should be  field tested because of their
 expanding number and importance in electric power generation.  This  factor
 is directly  related to  the contribution  of  equipment categories to the
 overall NOX  emission problem for  stationary sources.

 7.1  Utility Boiler Testing

           Table 7-1 summarizes the number of  boilers by fuel  and  type of
 firing recommended  for  future field testing based on the  results  of  the
 present work and prior Esso field studies (4-6) .

                                TABLE  7-1

                 NUMBER  AND TYPE OF UTILITY  BOILERS TO BE
                    TESTED  IN FUTURE FIELD TEST PROGRAMS
                              Fuel Fired:
                                    Mixed      Waste      Expected
         Type of  Firing      Coal     Fuels       Fuel        Total

         Wall (FW + HO)        3         1          1            5

         Tangential           311            5

         Cyclone               1                               1

         Turbo Furnace         1^        _          _           1

         Expected Total        822           12
Major emphasis should be placed on coal fired boilers.  However, mixed
fuels (combinations of coal, gas and oil) and waste-fired fuels should
also be tested.  Wall fired  (front wall and horizontally opposed) and
tangentially fired boilers should be given about equal emphasis.  One or
two cyclone furnace boilers  and a turbo furnace boiler should be tested
if sufficiently  flexible boilers can be located and arrangements with
boiler operators can be made.

           The coal types  to  be included in future  testing should encom-
pass Western low-sulfur bituminous  and sub-bituminous, lignite, Midwestern
bituminous and Eastern bituminous and  sub-bituminous  coals.  Because of

-------
                                 - 147  -
their increasing performance as national energy resources, priority should
be given to Western coals and lignite.  Simultaneously fired fuels should
include combinations of coal and oil, coal and gas, and oil and gas.
The waste fuel fired boiler could be either waste alone, or  a combination
of waste and fossil fuel fired.

          The basis for selecting specific boilers for testing within
each of the four types of firing groups includes an evaluation of
all pertinent operating factors in addition to being representative of
current design practices of major boiler manufacturers.

          Operating flexibility is the prime selection criteria.  Boilers
designed to operate with "NO-ports" or "overfire" air-ports and/or flue gas
recirculation into the windbox should be especially sought out for inclusion into
future test programs.  In addition, the operator's ability and willingness
to fire with low excess air, to employ staged combustion, to utilize
water injection, to control air and fuel to individual burners and to
reduce loads are highly important.  Obviously, the boilers selected must
be in good repair  and have the proper instrumentation and controls so
that good data for fuel usage, combustion and steam-side analysis can
be obtained.  Also, the boiler operator's willingness to cooperate by
providing proper sampling ports, assistance in obtaining fuel and ash
samples, good supervision for  the required safe changes in operation,
research-mindedness and experience in NOX control should be  taken into
account.  The boiler selection process will be greatly assisted with the
continued cooperation of boiler manufacturers and boiler operators
experienced in our present and previous field study programs.

          The cooperative planning effort of the current field test pro-
gram provides a recommended framework for future test programs.   Exxon
Research developed a comprehensive list of selection criteria  to  assist
EPA and boiler manufacturers in preparing a list of potential  boiler
candidates.  Each  boiler manufacturer submitted  a  list  of  suggested
boilers to EPA for review and  screening.  After  consideration  of  such
factors as design  variables, operating  flexibility, fuel  type, geographic
location and logistics, a tenative list of boilers was  selected  by  EPA
and Exxon. Field meetings were then  held  at power  stations  to  confirm
the validity of  the boilers selected and  to obtain necessary boiler
operating  and design data.

           Since  it is  desirable  to test representative  types of  coal and
mixed fuels  that are  fired  in  different geographic regions of  the United
States, it will  be desirable  to minimize  travel  time by utilizing the
concept of cluster sampling.   Consideration should be  given to testing
in  fringe  areas  where  different  fuel types can be  supplied to the same
boilers.

-------
                                - 148 -
          The scope and order of work to be performed on each boiler
can be described in terms of an expanded version of our current three
stage program.  First, a statistically designed program of short-period
test runs should be conducted, incorporating all available combustion
control variables, to determine the optimum and near optimum operating
conditions for NOX emission control under both full load and reduced
load operation.  Second, the boiler should be operated for 1 to 3 days
under sustained low NOX conditions, to validate optimum NOX emission
reduction conditions, and to assess potential boiler operability
problems such as slagging and steam temperature control.  Third, sustained
300-hour runs should be made under both baseline and "low NOX" operation.
During these periods, air-cooled carbon steel coupons will be exposed to
combustion gases in the vicinity of furnace water tubes, to determine
through corrosion tests whether operating the boiler under the reducing
conditions associated with low excess air and  staged  firing results  in
increased fire-side water— tube corrosion rates.  Particulate samples
should also be obtained under both baseline and "low NOX" operations to
determine if  increased amounts of unburned carbon on fly ash result; also to
determine if  fly  ash  loadings increase under "low NOX" operations. The samples
should be analyzed for trace constituents.  Boiler operating data should
be recorded in order to determine boiler efficiency, and operating
observations  should be recorded to assess operating problems, such as
excessive furnace slagging or steam temperature problems.

          Several additional work items should be included in the
enlarged three stage testing program in future boiler tests.

          •   The  300-hour sustained runs on selected boilers should
              be extended to a six-month period.  A representative
              sample of tube wall thickness measurements should be
              made under  normal  conditions and  before  and  after  the
              sustained  run to compare with  coupon  corrosion measurements-

          •   Precipitator performance tests should be made during
              both baseline and "low NOx" operations.
             Particle  size  distribution  and  conductivity  tests
             should  be made on  fly ash samples ,and  flue gas
             803 measurements obtained in  conjunction with per
             formance  test  so that cause-effect  relationships
             may be  established.

             Flue  gas  particulate measurements should be  made
             both  upstream  and  downstream  of electrostatic
             precipitators,  to  assess the  effect of combustion
             modifications  on precipitator performance.

-------
                        - 149 -
•  The particulates collected should be analyzed
   for potentially hazardous trace constituents,
   such as Hg, Cd, Be and Cd.  Special attention
   should be paid to the effects of combustion
   modifications on the potential segregation of
   such constituents into different particle size
   ranges •

•  Furnace slagging observations should be quantified
   as far as practical and related to changes in fuel
   composition and boiler operation.  Representative
   samples of raw coal, furnace slag, fly ash and
   bottom ash as well as flue gas should be taken
   during both sustained baseline and "low NOX"
   operations.  These samples should be analyzed so
   that changes in slag observations can be correlated
   with coal quality (heating value, % ash, ash com-
   position, ash viscosity, ash softening point, ash
   melting point etc.) and other operating parameters
   affecting combustion.  Mill performance (coal fineness),
   fuel distribution (burner to burner), air distribution
   (uniformity of secondary air register openings from
   burner to burner, or side to side variation due to
   plugged air heaters on unbalance in forced or induced
   draft fans), flame shape  (coal spreader condition and
   setting, air register setting, coal nozzle setting,
   burner head distribution vane setting) burner line
   velocities, staged firing pattern, and excess air
   level are  some of the operating variables that
   should be  observed and recorded for rigorous
   regression analysis with  slagging observations.  This
   systematic approach is necessary  for  solving the
   slagging problems that had been identified, but
   were beyond the scope of  the present  and past field
   test program.

-------
                                   -  150 -
                             8.   REFERENCES
1.  W. Bartok,  A.  R.  Crawford, A. R.  Cunningham,  H-  J.  Hall,  E.  H.  Manny
    and A. Skopp,  "Systems Study of Nitrogen Oxide Control  Methods  for
    Stationary Sources," Esso Research and Engineering  Company Final
    Report GR-2-NOS-69,  Contract No.  PH 22-68-55  (PB 192  789)  November,
    1969.

2.  W. Bartok,  A.  R.  Crawford, A. R.  Cunningham,  H.  J.  Hall,  E.  H.  Manny
    and A. Skopp,  "Stationary Sources and Control of Nitrogen Oxide
    Emissions," in "Proceedings of the Second International Clean Air
    Congress",  H-  M.  England and W. T. Beery, editors,  pp.  801-818,
    Academic Press, New York, 1971.

3.  W. Bartok,  A.  R.  Crawford and A.  Skopp, "Control of NOX Emissions
    from Stationary Sources", Chem. Eng. Prog. 67,  64 (1971).

4.  W. Bartok, A.  R.  Crawford and G.  J. Piegari,  "Systematic Field
    Study of NOX Emission Control Methods for Utility Boilers,"  Esso
    Research and Engineering Company Final Report No. GRU-4G.NOS.71,
    NTIS Report No. PB 210-739, December 1971.

5.  W. Bartok, A.  R.  Crawford and G-  J. Piegari,  "Systematic Investigation
    of Nitrogen Oxide Emissions and Combustion Control  Methods for
    Utility Boilers," in "Air Pollution and Its Control," AIChE  Symposium
    Series 68.  (126),  66 (1972).

6.  W. Bartok, A.  R. Crawford and G- J. Piegari,  "Reduction of Nitrogen
    Oxide Emissions from Electric Utility Boilers by Modified Combustion
    Operation," presented at Fourteenth International Symposium on
    Combustion, The Pennyslvania State University,  August 1972.

7.  D- W. Pershing, G. B. Martin and E. E. Berkau,  "Influence of Burner
    Design Variables On The Production of NOX and Other Pollutants,"
    Paper No.  22C, AIChE 66th Annual Meeting, Philadelphia, Pa.,
    November 11-15, 1973.

8.  D. W. Turner,  R. L. Andrews and C. W. Siegmund,  "Influence of
    Combustion Modification and Fuel Nitrogen Content On Nitrogen
    Oxide Emissions From Fuel Oil Combustion" in Air Pollution and
    Its  Control,  AIChE Symposium Series, Vol. 68 (196),  55 (1973).

9.  Environmental Protection Agency,"Standards of Performance for New
    Stationary Sources," Method 5, Published in the Federal Register,
    December 23,  1971, Vol. 36, Number 247, p. 24888-

-------
                                    - 151  -
10.  Shively, W. L.,  and Harlow, E. V., "The Koppers Electrical Process
     for the Prevention of Nitrogenous Gases in Distributed Gas",
     American Gas Journal, 144(6), 9, (1936).

11.  Ehnert, W., "Behavior of Nitric Oxides During Electrostatic Gas
     Purification", Bremstoff-Chem. 9(7),  2, (1936).

12.  Baum, W. H., Crest, J. G. and Nagee,  E. V., "Process for Removing
     Nitric Oxide from Gaseous Mixtures",  Patent:  U.S.  3,428,414
     Filed June 2, 1966.

13.  A. R. Crawford,  E. H. Manny and W. Bartok, "NOX Emission Control
     for Coal Fired Utility Boilers," Presented at the  "Coal Combustion
     Seminar," Environmental Protection Agency, Research Triangle
     Park, N.C., June 19-20, 1973; pp. 215-283 of  Proceedings,  Environmental
     Protection Technology Series, EPA-650/2-73-021, September, 1973.

-------
                                  A-l

                                APPENDIX A

                           OPERATING AND GASEOUS
                          EMISSION DATA SUMMARIES
           This section of the report contains 12 tables summarizing
 the operating and gaseous emission data by test run for each of the
 12 coal fired boilers tested.
                     Table                 Boilers
                       1            Widows Creek No. 6
                       2            Dave Johnston No. 2
                       3            E. D. Edwards No. 2
                       4            Crist No. 6
                       5            Harllee Branch No. 2
                       6            Leland Olds No. 1
                       7            Rmr Corners No. 4
                       8            Barry No. 3
                       9            Naughton No. 3
                      10            Dave Johnston No. 4
                      11            Barry No. 4
                      12            Big Bend No. 2
          Hydrocarbon and S02 measurements made in this study are not
included in the tables of  Appendix A  for the following reasons-  In
all cases, the volatile hydrocarbon emission levels were negligible.
in line with our previous experience in field testing coal-fired boilers
(4-6)•  While S02 emissions were measured, it is felt that in general
these results are not reliable because of instrument calibration problems.
This will be corrected for future field testing studies so that the effect
of combustion modifications on flue gas SO-/SO  ratios can be determined.
* The initial S02 concentration of fresh calibration gas cylinders has
  been found to decrease with time (presumably due to the adsorption of
  SOo on the walls of the gas cylinder).  This problem will be eliminated
  in future studies by frequent re-checking of the certified calibration
  gases.

-------
                                                       A-2

                                                     TABLE 1

                       SUMMARY Of OPERATING AI.D EMISSION DATA - WIDOWS  CREEK. BOILER NO.  6
                                   (125 MW, Front  Wall, Pulverized  Coal Fired)
                                                                   Average Gaseous Emissions and Temperatures
Firing Pattern

Date and
Run No.
4/12/72
1
2
3
4
4/17/72
5
6
7
8
4/18/72
20A
9
10
11
12
1A
4/19/72
13
14
15
4/20/72
18
16
19
17
20
4/21/72
IB
4/24/72
21
23
22
24
4/25/72
25
28
27
26
4/26/72
31
32
29
30
4/27/72
lOAl
5/1/72
10 /Ci
5/2/72
10/C3
5/3/72
10 /C 5
26Ai
5/4/72
26A3
Gross
Load
(MW)

125
125
125
125

126
119
122
120

115
125
125
125
121
125

110
110
112

110
110
110
112
108

128

80
83
88
89

110
100
103
99

112
106
110
106

120

120

125

123
97

103
Burners

Code

sl
Si
sl
Sl

S2
S2
S3
S3

S8
Si
S3
S2
S7
.£
Sl

S4
S5
S6

S7
s?
Sfi
O
s5
S4

Sl

S6
S7
S5
S4

s?
S6
S5
S4

Sl
Sl
sl
Sl

S3

S3

S3

S3
S4

S4
No. on
Coal

16
16
16
16

14
14
14
14

12
14
14
14
14
16

12
12
12

12
12
12
12
12

16

12
12
12
12

12
12
12
12

16
16
16
16

14

14

14

14
12

12
On Air
Only






D1D4
DlD4
A1A4
AlA4

B1B2B3B4
XA?
AX
DX
DM
1 4

1 7 x A
A1A?B9Bt
A1A4B2B3
A1A4B1B4

AA.DnD.
A1AXDA
A!AXBt
AWB?
AXA2A3A4



A^A B B
wX
A!AXBt
A1A\2A3
1234

A A D D
A1AXB4
AlAXBt
.1.4.2.3
1234






A1A4

A1A4

A1A4

A1A4
A1A2A3A4

A1A2A3A4
Secondary
Air
Registers
(% Open)

60
60
20
20

60
20
20
60

60
60
20
20
60
60

60
60
20

20
20
20
60
60

60

60
60
20
20

60
60
20
20

20
20
60
60

20

20

20

20
20

20
Exc. Air
Level -
% Stoic.
Act. Bur.

Nor-117
Min-110
Nor-115
Min-109

Nor-108
Min-96
Nor-110
Min-100

Min
Nor-lQ7
Min-94
Nor-106
Min-94
Nor-118

Nor-94
Min-86
Nor-99

Nor-94
Min-86
Min-88
Nor-94
Min-87

Nor-120

Nor-105
Min-92
Min-89
Nor-94

Nor-94
Min-94
Nor-97
Min-86

Nor-129
Min-115
Nor-129
Min-114

Min-105

Min-102

Min-103

Min-102
Min-86

Min-85
NOX
PPM
(3% 02,
Dry)

577
491
610
505

558
372
532
368

371
518
345
632
406
669

460
342
471

418
329
301
480
345

656

550
438
306
399

495
438
496
297

681
464
629
450

409

343

397

403
299

290
Pounds
Per
106 BTU

0.77
0.65
0.81
0.67

0.74
0.49
0.71
0.49

0.49
0.69
0.46
0.85
0.54
0.89

0.61
0.45
0.63

0.56
0.44
0.40
0.64
0.46

0.87

0.73
0.58
0.41
0.53

0.66
0.58
0.66
0.40

0.91
0.62
0.84
0.60

0.54

0.46

0.53

0.54
0.40

0.39
_0Z


%

3.2
2.0
2.8
1.9

4.0
2.0
4.5
2.7

2.2
4.1
1.7
3.8
1.5
3.3

4.5
2.6
5.2

4.3
2.9
3.1
4.4
3.0

3.6

6.1
3.9
3.4
4.5

4.5
4.5
4.9
2.7

4.9
2.8
4.8
2.7

3.6

3.0

3.3

3.2
2.8

2.5
C02


%

15.4
16.2
15.4
16.2

14.1
16.0
13.9
15.0

16.4
14.5
16.3
14.2
15.5
14.4

14.3
15.2
12.5

14.6
15.4
14.9
14.0
15.0

15.1

12.3
13.8
13.9
13.0

14.0
13.6
13.4
14.8

12.7
14.6
14.1
15.9

14.7

14.8

15.0

15.2
15.1

15.9
CO HC**
PPM PPM
3% 02 3% 02
Dry Dry

329
814
247
523

359
1049
491
833

899
383 4
1027 3
415 3
976 3
394 2

773 1
594
176

1110*
3090* -
3180*
167
1920*

52

40
292*
572*
141*

210* -
389* -
83
840*

61
407
52
530

650

867

414*

366
748

867
Temp.


°F

699
691
701
691

716
686
707
692

672
703
681
711
683
700

678
672
706

694
685
688
704
696

-

684
668
672
681

696
682
695
668

707
680
702
678

696

690

698

696
680

685
 *  High variation in CO measurements between probes.
**  Hydrocarbons were measured on each test but values were negligible except where indicated.

-------
                                                   TABLE 2

                      SUMMARY OF OPERATING AND EMISSION DATA - DAVE JOHNSTON,  BOILER  NO.  2

                                  (105 MW, Front  Wall Pulverized Coal  Fired)
Date and
Run No.
7/27/73
3
4
7/30/73
1
6
5
2
7/31/73
8
10
7
8/1/73
12
14
16
15
13

Gross
Load
MW

101
101

102
102
102
102

103
103
101

106
102
99
98
99
Boiler Operating Conditions
Firing
Pattern :
Mills
Off

12
12

11,12
11,12
11,12
11,12

11,12
11,12
11,12

12
10,12
10,12
10,12
10,12
Secondary Air
Register
Settings on
Off Mills

Closed
Closed

Closed
11 Op., 12 Cl.
Partly Open
11 Cl., 12 Op.

11 Cl. , 12 Op.
Open
Closed

Open
10 Cl., 12 Op.
Open
10 Op. , 12 Cl.
Closed
Excess Air
Target

Nor.
Low

Nor.
Low
Low
Low

Nor.
Nor.
Low

Low
Low
Low
Low
Nor.
% Stoic.
To Act.
Burners

130
125

125
94
82
99

102
85
120

102
102
88
106
132
Average Gaseous Emissions
N
PPM
(3% 02,
Dry)

454
409

450
362
311
284

347
358
413

314
270
214
326
438
Ox
Pounds
Per
106 BTU

0.60
0.54

0.60
0.48
0.41
0.38

0.46
0.48
0.55

0.42
0.36
0.28
0.43
0.58
02
%

5.0
4.3

4.3
3.3
4.0
4.2

4.6
4.6
3.7

4.1
4.7
5.2
5.3
5.2
CO?
%

14.3
14.6

15.3
16.4
16.3
16.0

14.4
14.8
15.2

15.1
14.5
13.4
13.4
13.4
CO
PPM
(3% 02,
Dry)

112
731

28
112
308
277

370
96
117

918
1054
962
620
420
NOTE:  Hydrocarbons were measured on each test but values
       were negligible except where indicated.

-------
                                                     TABLE 3

                        SUMMARY OF  OPERATING AND EMISSIONDATA -  E.D.  EDWARDS,  BOILER  NO.  2




(260
MW, Front
Wall, Pulverized Coal Fired)
Boiler Operating Conditions
Firing Pattern

Date and
Run No.
6/11/63
1
2
6/12/63
5
6
3
4
6/13/63
23
24
13
18
8
7
6/14/63
14
10
11
12
9
6/15/63
16
20
1A
Gross
Load
(MW)

256
251

255
256
254
255

212
204
238
238
250
250

229
243
250
249
252

221
221
250
Burners

Code

Sl
sl

S2
S2

sl

Sl
sl
S4

S3
S3

S4
S2
S3
S3
S2

S5
S5
Sl
No. On
Coal

16
16

14
14
16
16

16
16
12
12
14
14

12
14
14
14
14

12
12
16
On Air
Only

None
None

1,4
1,4
None
None

None
None
1,2,3,4
1,2,3,4
2,3
2,3

1,2,3,4
1,4
2,3
2,3
1,4

1,4,6,7
1,4,6,7
None
Secondary
Air
Registers
(% Open)

45-50
45-50

45-50
20
20
20

50
50
50
50
50
20

30
50
50
30
30

50
30
50
Excess Air


Target

Nor.
Low

Nor.
Low
Nor.
Low

Nor.
Low
Nor.
Low
Low
Nor.

Low
Low
Nor.
Low
Nor.

Low
Low
Nor.
% Stoic.
To Active
Burners

117
107

106
94
117
109

124
108
97
89
100
108

94
96
106
96
107

86
87
121
Average Gaseous Measurements
NOV
PPM
(3% 02,
Dry)

670
556

644
359
770
692

668
516
535
386
524
401

310
474
609
382
625

336
295
736
Pounds
Per
106 BTU

0.89
0.74

0.86
0.48
1.02
0.92

0.89
0.69
0.71
0.51
0.70
0.53

0.41
0.63
0.81
0.51
0.83

0.45
0.39
0.98
02


%.

3.2
1.5

3.8
1.6
3.1
1.8

4.2
1.6
4.9
3.5
2.7
4.0

4.4
2.0
3.8
2.1
3.9

2.8
3.0
3.8
C02


%

14.8
16.0

14.6
16.2
14.4
15.4

14.1
16.3
13.2
14.1
14.3
13.3

13.3
16.6
14.4
15.7
14.4

15.0
14.6
14.2
CO
PPM
(3% 02,
Dry)

69
93

18
172
16
29

17
54
23
234*
117
28

215*
200*
19
333
22

257
26
16
Temp.


°F

644
622

649
642
644
637

620
597
647
633
636
640

627
630
647
474
633

613
610
647
                                NOTE:   Hydrocarbons  were measured on each test but
                                       values were negligible except where indicated.
*  Average values increased due to high CO measurements with one of 4 probes.

-------
                                                                                                A-5
                                                                                              TABLE 4
SUMMARY OF OPERATING
Boiler Operating Conditions
AND EMISSION DATA - CRIST. BOILER NO. 6
(340 MW, Front Wall, Pulverized Coal
Fired)
Flue Gas Emission Measurements
Excess Air
Firing P£

Date and
Run No.
12/6/72
3
2
12/7/72
26
12/8/72
4
5
12/9/72
ISA
12/11/72
1
5A
10
12/12/72
26B
12/13/72
6
7
8
12/14/72
16
3/19/73
14R
11R
16R
25R
3/20/73
1R
6R
8R
10R
Gross
Load
(MH)

315
318

350

318
320

270

320
320
320

350

320
310
314

250

272
272
272
272

315
320
321
320
i ttern
Burners

Code

S
S2

Sl

S3
S3

S4

S,
S3
S3

S!

S,
S
2

S4

S,
Sl
/
S5

S,
,,1
S

No. on
Coal

14
14

16

14
14

12

16
14
14

16

16
14
14

12

16
16
12
12

16
16
14
14
On Air
Only

1,4
1,4

None

2,3
2,3

1,2,3,4

None
2,3
2,3

None

None
1,4
1,4

1,2,3,4

None
None
1,2,3,4
2,3,5,8

None
None
1 ,4
2,3
Secondary
Air
Registers
(7. Open)
(Oper/Idle)
70/70
70/0*

101-

70/0*
70/70

70/0

101-
70/70
70/70

101-

101-
70/0*
70/70

70/70

70/70
70/70
70/70
TO/10

70/70
70/70
70/70
70/70
7, Stoic.
Air
To Active
Burners
Target
(1)
N
N

N

N
N

L

N
N
L

N

L
L
L

L

L
N
L
L

N
L
L
L
A

98
112

119

94
91

86

120
102
109

117

112
96
96

91

110
120
82
88

119
114
102
104
B

104
112

115

108
102

89

120
105
97

119

112
100
110

90

100
122
94
88

116
110
97
102
NOx 09
PPM
(37. 02)

724
946

898

516
532

643

902
728
566

888

804
788
772

661

754
840
560
647

916
862
738
802
Pounds/
106 BTU

0.96
1.26

1.20

0.69
0.71

0.86

1.20
0.97
0.75

1.18

1.07
1.05
1.03

0.88

1.01
1.12
0.75
0.86

1.22
1.15
0.98
1.07

"L

2.3
4.7

3.4

1.4
0.9

2.6

3.6
3.1
1.8

3.2

2,4
2.0
1.9

3.8

2.0
3.7
1.8
3.1

3.4
2.6
3.1
3.5
Duct A
C02

7,

-_
13.5

15.0

15.9
17.0

16.2

16.0
15.0
15.3

14.8

15.8
15.8
15.2

14.2

15.7
14.3
15.5
13.8

15.0
15.7
15.2
14.9

CO
PPM
(37. 02)

38
26

24

44
900

59

22
32
75

19

80
47
29

29

44
45
396
372

56
66
87
66

HC Temp.
PPM
37, 02 °F

653
619

-

648
651

640

2 659
659
1 651

4 671

651
650
658

600

616
617
611
-

647
638
643
643


NOx
PPM
37. 02

631
872

743

546
620

415

799
565
522

801

630
565
591

411

640
748
472
484

765
660
526
593
Pounds/
106 BTU

0.84
1.16

0.99

0.73
0.83

0.55

1.07
0.88
0.70

1.06

0.84
0.75
0.79

0.55

0.85
1.00
0.63
0.65

1.02
0.88
0.70
0.79

02

7.

3.4
4.7

2.9

4.0
3.2

3.3

3.6
3.6
2.2

3.5

2.4
2.5
4.5

3.7

2.2
3.9
4.5
3.1

3.0
2. 1
2.2
3.0
Duct B
C02

7.

-~
13.4

15.3

13.6
15.0

15.6

15.6
14.5
14.9

14.4

15.6
15.2
13.3

14. 1

15.6
14.1
13.1
13.9

15.3
16.0
15.9
15.1

CO
PPM
(37. 02)

42
32

27

36
28

173

23
34
90

19

140
220
32

94

175
46
131
372

60
230
902
218

HC** Temp.
PPM
(37, 02.) °F

685
662

704

671
-

-

2 696
688
1 680

4 703

_
_
-

643

661
663
653
651

682
676
683
681
(1)   Excess air target:   N-Normal,  L-Low Excess Air.
 *    Position of  idle  registeew  was  uncertain.
 **   Hydrocarbons were measured  on each  test but
     values were negligible except where  Indicated.

-------
                                                   TABLE 5
SUMMARY OF OPERATING AND EMISSION DATA - HARLLEE BRANCH, BOILER NO. 3
(480 MW, Horizontal Opposed Wall, Pulverized Coal Fired)
Boiler Operating Conditions Average Gaseous
Firing Pattern

Date and
Run No.
5/22/72
1
2
5/23/72
3
4
5
6
7
8
5/24/72
9
10
11
12
1A
5/31/72
20
14
28
23
IB
6/1/72
40
41
42
29
1C

6/12/72
ID
6/13/72
43
6/14/72
44
45
46
47
IE
6/15/72
48
49
6/19/72
50
51
52
6/27/72
16
6/28/72
1H
7/5/72
52 A
7/11/72
52B
7/12/72
52C
7/13/72
52D
7/14/72
52E
7/17/72
53A
7/18/72
53B
7/24/72
52T
7/25/72
526
7/26/72
53D
7/27/72
1J
IK
7/28/72
421
Gross
Load
(MW)

478
480

480
478
480
477
480
478

485
479
480
478
500

398
400
398
397
500

392
399
400
399
490


488

445

481
480
485
482
483

275
155

475
472
471

477

465

482

467

475

475

465

450

450

477

465

465

455
455

478
Burners
Code

sl


S
s1
s^
s2
5^
S3

S,
s
S,
s2
S2

S,
S*
s3
s°
sl

SB
S10
s
s"
sj
1

Sj

=14

s,,
s
sJi
s"
s^

s
s16

SIR
SIQ
S

S20

S20

S20

S20

S20

S20

S20

S21

S21

S20

S20

S21

S,,
'22

Sll
No. on
Coal

40
40

40
40
36
36
36
36

36
36
36
36
40

30
30
30
30
40

34
34
34
40
40


40

35

35
36
36
35
40

32
20

36
35
34

34

34

34

34

34

34

34

35

35

34

34

35

39
39

34
No. on
Air

0
0

0
0
4
4
4
4

4
4
4
4
0

10
10
10
10
0

6
6
6
0
0


0

5

5
4
4
5
0

8
8

4
5
6

6

6

6

6

6

6

6

5

5

6

6

5

1
1

6
Secondary
Air
Registers

100
100

50
50
100
50
50
100

100
50
50
100
100

100
100
100
100
100

100
100
100
100
100


100

100

100
100
100
100
100

100
100

100
100
100

100

100

100

100

100

100

100

100

100

100

100

100

100
100

100
Excess Air

T t

Nor.
Lou

Nor.
Lou
Nor.
Lou
Nor.
Lou

Nor.
Lou
Nor.
Lou
Nor.

Low
Low
Low
Low
Nor.

Low
Low
Lou
Nor.
Nor.


Nor.

Low

Low
Lou
Lou
Lou
Nor.

Lou
Lou

Lou
Lou
Lou

Lou

Low

Lou

Lou

Lou

Lou

Lou

Lou

Low

Lou

Lou

Lou

Nor.
Nor.

Lou
% Stoic.
To Act.

119
107

120
110
105
98
107
99

104
95
108
97
120

81
80
80
79
123

92
93
94
116
116


120

94

94
95
96
95
116

92
67

96
94
91

90

90

91

91

91

93

94

94

94

89

91

96

112
113

92
NOX
PPH
(32 02,
Dry)

747
549

735
667
613
569
734
578

680
568
624
493
688

372
334
392
256
707

363
339
360
537
668


711

491

576
594
624
589
745

287
148

486
493
466

463

472

517

520

466

582

565

552

592

403

407

556

608
639

498
Pounds
Per
106 BTU

0.99
0.73

0.98
0.89
0.82
0.76
0.98
0.77

0.90
0.75
0.83
0.66
0.92

0.49
0.44
0.52
0.47
0.94

0.48
0.45
0.47
0.71
0.89


0.95

0.65

0.77
0.79
0.83
0.78
0.99

0.38
0.20

0.65
0.65
0.62

0.62

0.63

0.69

0.69

0.62

0.77

0.75

0.73

0.79

0.54

0.54

0.74

0.81
0.85

0.66
02

%

3.5
1.4

3.7
2.0
3.1
1.9
3.4
2.0

2.9
1.3
3.6
1.7
3.6

1.6
1.5
1.4
1.1
4.1

1.7
1.9
2.0
3.0
3.0


3.7

1.5

1.4
1.2
1.4
1.8
3.0

2.9
2.4

1.4
1.5
1.4

1.2

1.3

1.4

1.5

1.5

1.9

2.0

1.7

1.6

1.1

1.5

2.1

2.8
3.0

1.6
Emissions and Temperatures
C02

%

14.1
16.6

14.8
16.3
14.8
15.9
15.3
16.7

15.6
17.0
14.7
16.9
15.4

16.6
15.5
15.6
16.3
14.5

16.4
16.2
15.8
15.0
15.2


14.3

16.4

17.2
17.0
17.1
16.4
15.4

15.9
16.2

17.1
16.9
16.8

17.3.

17.2

17.4

17.1

17.1

16.0

16.4

17.3

16.6

17.3

16.6

16.5

16.4
15.5

16.1
CO
PPM
(3% 02,
Dry)

21
81

13
26
26
30
24
45

18
38
24
52
27

178
924
92
562
32

159
75
225
28
47


14

96

280
187
147
172
23

417
306

618
321
357

127

24

158

45

45

122

101

20

28

288

47

52

20
26

48
HC* Temp.
PPM
(3% 02,
Dry) °F

604
1 595

0 613
596
600
596
610
1 596

1 610
593
2 614
595
619

567
551
560
558
620

554
560
558
565
606


624

590

601
595
598
593
609

524
460

600
596
592

613

611

614

2 611

0 605

3.1 610

1.2 606

1.2 597

2 591

3 603

1.9 604

2.1 607

2.5 603
2.1 605

1.9 603
* Hydrocarbons uere measured on each test but values  were negligible except uhere  indicated.

-------
                             TABLE 6

 SUMMARY OF OPERATING AND EMISSIONS DATA - LELAND OLDS. BOILER NO. 1

  (218 MW, Horizontally Opposed, Pulverized Coal Fired Boiler)
Boiler Operating Conditions
Average Gaseous Emissions and Temperatures
Firing Pattern
Date and
Run No.
7/6/73
1
2
7/9/73
3
4
5
7/10/73
6
7
9
11
1A
7/11/73
4A
4B
7/12/73
4C
Gross
Load
MW

219
218

218
216
192

187
185
185
180
214

205
205

205
Code
[1]

Si
Si

S2
S2
S3

S4
S4
S5
S6
sl

S7
S7

s?
Firing

20
20

18
18
16

16
16
16
16
20

18
18

18
Air
Only

0
0

2
2
4

4
4
4
4
0

2
2

2
Excess Air
Target

Nor.
Low

Nor.
Low
Low

Nor.
Low
Low
Low
Nor.

Low
Low

Low
% Stoic.
To Act.
Burners

122
110

112
104
95

103
89
91
95
120

103
103

105
NOX
PPM
(3% 02,
Dry)

569
447

560
375
342

428
260
329
256
564

418
401

475
Pounds
Per
106 BTU

0.74
0.58

0.74
0.50
0.45

0.57
0.35
0.44
0.47
0.75

0.56
0.53

0.63
_2z


3.9
2.1

4.2
2.8
3.5

4.9
2.2
2.6
3.5
3.6

2.6
2.7

3.1
CO?
7

15.7
16.9

14.9
16.3
15.9

14.4
16.8
15.9
15.9
15.6

16.3
16.4

16.0
CO
PPM
(3% 02
Dry)

24
283

23
231
139

21
518
226
153
21

50
51

25
Temp.
°F

954
948

945
937 >
883 --J

910
981
922
880
947

935
990

918
      NOTE:  Hydrocarbons were measured on each  test but
             values were negligible except where indicated.

-------
                                                     A-8


                                                   TABLE 7

                     SUMMARY OF OPERATING AND EMISSION DATA - FOUR CORNERS, BOILER  NO.  4

                            (800 MW, Horizontally Opposed, Pulverized Coal Fired)
                        Boiler Operating Conditions
Firing Pattern

Date and
Run No.
11/2/72
19
20
21
11/3/72
1A
6A
11/5/72
1
2
3
4
11/7/72
5
2B
8
7
11/8/72
6
IB
11/9/72
1C
ID
11/10/72
9
14
15
12
11/14/72
IE*
11/15/72
IF*
11/18/72
12A
11/20/72
12B*
11/21/72
12C*
Gross
Load
(MW)

600
600
590

750
755

740
710
730
730

760
750
730
730

754
768

810
796

801
794
806
794

755

775

725

704

735
Burners
Code
Jll

S5
S5
S5

sl
sl

sl

S2
S2

sl
Sl
S2
S2

sl
Sl

Sl
Sl

S3
S3
S4
S4

sl

Sl

S4

S2

S2

Firing

42
42
42

54
54

54
54
46
46

54
54
46
46

54
54

54
54

46
46
42
42

54

54

42

44

46
Air
Only

0
12
12

0
0

0
0
8
8

0
0
8
8

0
0

0
0

8
8
12
12

0

0

12

8

8
Second.
Air
Registers
% Open

100
100
100

100
100

100
50
50
100

50
50
50
100

100
100

100
100

100
100
100
100

100

100

100

100

100
Excess Air


Target

Nor.
Nor.
Low

High
Low

Nor.
Low
Nor.
Low

Nor.
Low
Low
Nor.

Low
Nor.

Nor.
Nor.

Nor.
Low
Nor.
Low

Nor.

Nor.

Nor.

Low

Low
% Stoic.
To Act.
Burners

112
111
90

135
112

127
113
108
95

130
115
101
108

110
131

126
132

108
95
105
91

119

117

97

98

98
NOX
PPM
(3% 02,
Dry)

816
801
452

982
641

848
659
695
482

932
748
609
754

630
965

843
949

685
494
709
488

741

715

560

458

473
Pounds
Per
10b BTU

1.08
1.07
0.60

1.31
0.85

1.13
0.88
0.92
0.64

1.24
0.99
0.81
1.00

0.84
1.28

1.12
1.26

0.91
0.66
0.94
0.65

0.99

0.95

0.74

0.61

0.63
02


%

6.5
6.4
3.0

5.6
2.3

4.6
2.5
4.6
2.2

5.0
2.8
3.3
4.7

2.0
5.1

4.5
5.2

4.6
2.3
5.5
3.2

3.4

3.1

4.3

3.7

2.8
C02


%

11.0
11.0
14.3

11.7
14.6

13.8
14.6
12.5
14.4

13.5
15.0
13.1
13.8

15.9
13.5

13.5
12.6

13.9
15.6
12.6
14.6

14.8

15.3

13.9

14.4

15.0
CO
PPM
(3% 02,
Dry)

17
13
33

24
156

18
110
24
260

14
60
113
19

423
15

19
13

48
453
21
172

21

14

40

40

195
Temp.


°F

_
544
514

472
560

582
554

551

588
592
564
578

552
578

576
585

580
550
590
560

587

575

558

540

563
[1]   Firing Pattern:

      Symbols
      Si     O
      S2     D
      S3     A
      S4     V
      s,     O
Burners on Air Only
None
INT, 9NT, 1ST, 9ST, 5NT, 6NT, 5ST, and 6ST.
INT, 1NM, 9ST, 9SM, 6NT, 6NM, 5ST, and 5SM.
INT, 9NT, 1ST, 9ST, 8NT, 2ST, 5NT, 6NT, 5ST, 6ST, 7NT and 3ST.
Burners fed by pulverizers 5 and 9.
  100-200 gal./hour water injection into furnace.
                            NOTE:   Hydrocarbons were measured on each test but
                                   values were negligible except where indicated.

-------
                                                        TABLE 8

                                SUMMARY OF OPERATING AND EMISSION DATA - BARRY.  BOILER NO.  3
(250 MW, Pulverized
Boiler Operating Conditions*
Firing Pattern
Gross
Date and Load
Run No. (MW)
3/23/73
1 250
2 248
3 248
4 248
5 250
6 250
7 251
8 248
Burners
Code
**

sl
Si
Sl
Sl
Sl
Sl
sl
si
No. on
Coal

48
48
48
48
48
48
48
48
No. on
Air

0
0
0
0
0
0
0
0
Secondary
Air Re£.
Aux/Coal
(% Open)

100/30
100/30
40/100
40/100
40/100
40/100
100/30
100/30
Coal, Tangentially
Excess Air

Mill
Fineness

Nor.
Nor.
Nor.
Nor.
Coarse
Coarse
Coarse
Coarse

Target

Nor.
Low
Nor.
Low
Low
Nor.
Nor.
Low
% Stoic.
To Act.
Burners

117
106
117
109
110
119
119
107
Fired)
Average Gaseous Emissions & Temp.
NOX
PPM
(3% 02,
Dry)

410
310
425
350
350
420
416
512
Pounds
Per
106 BTU

0.54
0.41
0.56
0.46
0.46
0.56
0.55
0.41
o?

%

3.1
1.3
3.2
1.9
2.0
3.5
3.5
1.4
CO?

%

14.8
16.2
14.2
15.2
14.9
13.3
13.1
14.4
CO
PPM
(3% 03,
Dry)

61
100
60
115
130
64
77
129
Temp.

°F

662
646
666
648
654
666
663
645








T
VD


 *  Tilts welded into fixed position.
**  Only normal firing runs because of mechanical problems.
                                   NOTE:   Hydrocarbons were measured  on each  test but
                                          values were negligible  except where indicated.

-------
                                                       A-10

                                                      TABLE 9

                          SUMMARY OF OPERATING AND EMISSION DATA - NAUGHTON,  BOILER NO.  3
                                (330 MW, Tangential, Pulverized Coal Fired Boiler)
Boiler Operating Conditions
                                                                       Average Gaseous  Emissions  and  Temperature
Firing Pattern
Date and
Run No.
9/13/72
1
9/14/72
2
3
4
5
9/18/72
6
7
8
9
9/19/72
10
11
12
13
9/20/72
14
15
16
17
9/21/72
18
19
20
21
9/27/72
22
10/4/72
23
10/6/72
24
10/9/72
25
10/10/72
26
Gross
Load
(MW)

256

260
265
254
260

250
262
260
262

256
259
260
260

199
198
200
199

328
328
308
310

275

283

300

315

340
Burners
Code

Si

S2
s2
S2
S2

S2
S2
S2


S2
S2

S

Si
Sj
S3


Si
Si
s2
s2

S2

Si

Si

Si

Si
No. on
Coal

20

16
16
16
16

16
16
16*
16*

16
16
16*
16*

16
12
12
12

20
20
16
16

16

20

20

20

20
No. on
Air

0

4
4
4
4

4
4
4
4

4
4
4
4

0
4
4
4

0
0
4
4

4

0

0

0

0
Secondary
Air
Registers
Aux./coal
(% Open)
20-80

20-80
20-80
20-80
20-80

20-90
70-25
70-25
15-90

60-20
60-20
60-20
60-20

20-80
20-80
20-80
70-30

20-80
20-80
20-80
70-30

20-80

20-70

20-80

20-80

20-80
Burner
Tilt
(° From
Horiz.)

0

0
0
-30
+10

-30
-30
-30
-30

0
+22
+20
0

0
0
0
0

0
0
0
0

0

-30

-30

-30

0
Excess Air
Target

Nor.

Nor.
Low
Low
Low

Low
Low
Low
Low

Low
Low
Low
Low

Nor.
Nor.
Low
Low

Nor.
Low
Low
Low

Nor.

Nor.

Nor.

Nor.

Nor.
% Stoic.
To Act.
Burners
**
127

99
91
92
92

91
92
93
92

88
90
90
91

118
78
74
65

121
109
88
77

105

120

120

124

125
NOX 02 C02
PPM
(3% 02,
Dry)

537

304
265
266
284

216
213
251
245

197
216
273
235

458
169
182
176

494
379
236
219

331

510

569

549

568
Lbs.
Per
106 BTU % %

4.9 12.9

4.9 13.5
3.6 14.2
3.7 14.0
3.6 13.7

3.1 14.5
3.0 16.0
3.2 15.9
3.1 16.4

3.0 16.8
3.5 16.4
3.7 15.9
3.7 16.0

4.2 14.6
4.5 13.4
3.2 13.7
4.2 12.7

3.9 14.7
2.1 15.8
2.7 14.5
2.3 14.8

3.1 15.2

3.6 15.3

3.6 15.3

4.2 14.0

4.4 14.2
HC*** CO
PPM
(3% 02,
Dry)

-

1
1
1
1

1
1
1
1

1
1
1
1

-
-
-
-

-
-
-
-

-

-

-

-

-
PPM
(3% 02,
Dry)

30

14
62
28
23

210
78
82
91

376
354
306
208

20
27
56
102

30
225
44
499

185

21

19

18

24
Temp.
°F

694

693
673
666
672

666
504
666
682

670
673
674
672

626
631
622
636

755
732
715
714

686

702

721

763

757
  *  Mill  fineness set to coarse (1 vs. 2.1)
 **  Calculated by combustion engineering from air register openings and  total  air.
***  Hydrocarbons were measured on each test but values were negligible except  where indicated.

-------
                             TABLE 10

SUMMARY OF OPERATING AND EMISSION DATA - DAVE JOHNSTON,  BOILER NO.  4
(340 MW, Pulverized Coal, Tangentially Fired)
Boiler Operating Conditions Average Gaseous Emissions & Temp.
Firing Pattern
Date and
Run No.
8/8/73
1
2
3
4
8/9/73
10
17
Gross
Load
(MW)
306
303
303
305

310
312
Excess Air
Burners
Pulv.
Off

17 &
17 &
17 &
17 &

17 6,
17 &

20
20
20
20

21
21
No. on
Coal

20
20
20
20

20
20
No. on
Air

0
0
0
0

0
0
Target
Nor.
Low
Low
Low

Nor.
Nor.
% Stoic.
To Act.
Burners

124
117
117
119

122
122
Burner
Tilt
(° From
Horiz.)

0°
0°
-10°
+16°

0°
-10°
NOX
Primary
Air
Level

Low
Low
Low
Low

+10%
+10%
PPM
(3% 02
Dry)
434
386
414
381

362
380
Pounds
Per
10 6 BTU

0.58
0.51
0.55
0.51

0.48
0.50
02_
%

4.2
3.2
3.2
3.4

3.9
3.9
C02
%

14.6
16.2
16.0
15.6

12.3
13.3
CO
PPM
(3% 02
Dry)
19
56
28
142

41
40
Temp.
°F

780
700
750
765

775
780
        NOTE:   Hydrocarbons were measured  on  each  test but
               values  were negligible  except  where indicated.

-------
                                                        A-12

                                                      TABLE 11

                              SUMMARY OF  OPERATING AND EMISSION DATA -  BARRY.  BOILER NO.  4

                                     (360 MW, Tangential, Pulverized Coal  Fired)
Boiler Operating Conditions
Firing Pattern

Date and
Run No .
1/19/73
13
29
30
31
1/22/73
17
18
19
20
32
1/23/73
1
2
3
4
5
6
7
8
1/24/73
33
34
35
37
9
10
11
12
2/4/73
40
41
25
26
27
28
2/5/73
13A
14
15
16
2/7/73
42
43
2/9/73
50
2/13/73
19A
2/14/73
19B
2/21/73
19C
19D
19 E
19F
2/22/73
42A
2/23/73
42B
Gross
Load
(MW)

325
328
330
330

290
295
292
281
286

348
348
344
334
299
298
294
294

346
345
360
348
322
297
311
304

186
180
210
186
184
180

343
292
284
283

320
325

323

283

255

282
280
289
288

293

283

Burners
No. on
Code Coal

ASi
ASi
ASi
AS1

BCS!
BCS2
BCS2
BCS2
BCS2

ACS.
ACS*

ACS*
ACS,
ACS,
ACS,
ACSj

ACS.
ACS.
ACS:
ACS:
ACS,
ACS,
ACS,
ACSj

BS.
BS3
BCS^
BCS,
BCS
BCS*

AS1

AS0
2

ACSi


ACSj

BCS2

BCS2

BCS2
BCS
BCS,
BCS^

BCSl

BCS2

20
20
20
20

20
16
16
16
16

20
20
20
20
16
16
16
16

20
20
20
20
16
16
16*
16*

12
12
20
12
12
12

20
16
16
16

20
20

16

16

16

16
16
16
16

16

16
No. on
Air

0
0
0
0

0
4
4
4
4

0
0
0
0
4
4
4
4

0
0
0
0
4
4
4
4

4
4
0
4
4
4

0
4
4
4

0
0

0

4

4

4
4
4
4

0

0
Secondary
Air Reg.
Burner
Tilt
Aux./Coal (" From
(% Open) Horiz.)

100/50
100/50
100/50
50/100

100/50
100/50
100/50
50/100
50/100

100/50
100/50
100/50
50/100
100/50
100/50
100/50
50/100

100/50
100/50
100/50
100/20
50/100
100/50
100/50
50/100

100/50
100/50
50/100
100/50
100/50
100/50

100/50
100/50
100/50
50/100

32/50
32/50

40/50

100/50

100/50

100/50
100/50
30/50
50/20

100/50

100/50

0
0
+20
-30

0
0
0
-30
0

0
0
+15
-25
0
0
+15
-30

-30
-30
0
0
0
-30
-30
0

0
0
0
0
0
-30

0
0
0
-15

-8
-8

-8

-8

-8

-8
-8
-8
-8

-8

-8
Excess Air
% Stoic.
Target

Nor.
Low
Low
Low

Nor.
Nor.
Low
Low
Low

Nor.
Low
Low
Low
Nor.
Low
Low
Low

Nor.
Low
Low
Low
Low
Low
Low
Low

Nor.
Low
Nor.
Low
Nor.
Low

Nor.
Nor.
Low
Low

Nor.
Nor.

Nor.

Low

Low

Low
Low
Low
Low

Nor.

Nor.
To Act.
Burners

115
107
110
107

118
100
94
86
94

115
112
110
106
96
94
92
85

114
108
112
112
92
86
86
91

100
84
123
83
97
86

112
90
88
87

112
107

115

92

91

95
87
90
91

117

115
Average
Gaseous
NOx
PPM
(37. 02,
Dry)

420
336
364
398

441
334
288
273
282

415
398
349
364
313
286
294
257

497
445
409
441
295
289
299
297

338
200
440
189
261
232

415
309
245
264

396
349

436

347

288

338
258
276
274

396

370
Pounds
Per
106 BTU

0.56
0.45
0.48
0.53

0.59
0.44
0.38
0.36
0.51

0.55
0.53
0.46
0.48
0.42
0.38
0.39
0.34

0.64
0.59
0.54
0.59
0.39
0.38
0.40
0.40

0.45
0.27
0.58
0.25
0.35
0.31

0.55
0.41
0.33
0.35

0.53.
0.46

0.58

0.46

0.38

0.45
0.34
0.37
0.36

0.53

0.49
Emissions and Temperature
J02

C02

CO
PPM
Temp.

(K U2,

4.7
2.8
3.6
2.8

5.1
6.3
4.9
3.1
5.0

4.4
3.9
3.6
2.5
5.4
4.8
4.4
2.4

4.3
3.1
3.8
3.9
4.4
3.0
2.9
4.3

7.7
3.9
6.0
3.7
7.1
4.3

3.8
5.1
3.6
3.3

3.8
2.7

4.4

4.6

4.3

5.2
3.3
3.9
4.2

5.0

4.5

13.4
15.4
14.5
15.2

11.5
12.3
12.5
13.3
11.9

13.8
13.8
13.8
14.0
11.5
12.2
12.1
15.9

14.4
15.4
14.0
13.7
13.0
14.1
14.5
13.3

10.5
14.1
11.6
13.7
10.6
13.1

14.6
13.1
14.0
14.5

13.4
14.0

14.6

15.9

14.1

12.7
13.5
13.0
12.6

13.2

14.2

20
227
37
41

19
33
50
43
50

24
115
100
96
26
63
98
107

27
24
169
58
97
113
114
189

22
211
27
281
30
43

25
25
201
58

56
395

37

48

49

21
177
130
69

36

47

308
311
310
312

305
295
295
289
292

305
290
295
291
281
280
288
284

308
308
310
309
291
286
288
285

273
254
266
249
255
250

315
298
290
277

305
303

291

283

290

293
281
282
280

280

215
*  Coarse mill setting.
                                  NOTE:
Hydrocarbons were measured on each test but
values were negligible except where indicated.

-------
                                                     TABLE 12


                          SUMMARY OF OPERATING AND EMISSION DATA - BIG BEND. BOILER NO.  2

                                  (450 MW,  Turbo-Rirnace,  Pulverized Coal Fired)
                           Boiler Operating Conditions
                                                                    Average Gaseous Emissions and Temperature


Date and
Run No.
3/5/73
6
4A
4B
3/6/73
2
1
3
5
3/7/73
20*
21**
22***
3/12/73
9
10
11
12

Gross
Load
(MW)

225
375
380

370
370
370
370

230
230
230

300
300
300
300

Direct
Vanes
Front/Rear

-15/+15
-15/+15
-15/+15

-15/-15
-15/-15
-15/-15
-15/+15

-15/+15
-15/+15
-15/+15

-15/+15
-15/+15
-15/+15
-15/+15

Firing
Pattern
Excess Air
Burners
Ash
Inject.

Yes
Yes
No

No
Yes
No
No

No
No
No

No
No
No
No
No. on
Coal

24
24
24

24
24
24
24

16
16
16

24
24
24
24
No. on
Air

0
0
0

0
0
0
0

0
4
8

0
0
0
0

Target

Nor.
Nor.
Nor.

Nor.
Nor.
Low
Low

Nor.
Low
Low

Nor.
Low
Nor.
Low
% Stoic.
To Act.
Burners

119
115
115

115
115
110
107

119
99
79

115
109
113
110
NOV
PPM
(3%, 02
Dry)

370
547
558

587
614
464
398

350
347
312

378
341
397
362
Pounds
Per
106 BTU

0.49
0.73
0.74

0.78
0.82
0.62
0.53

0.46
0.46
0.41

0.50
0.45
0.53
0.48
02


%

3.4
2.8
2.9

2.8
2.8
2.0
1.4

3.4
3.4
3.5

2.9
1.8
2.5
2.1
C02


%

15.0
15.4
15.2

15.3
15.3
15.9
16.2

15.0
14.9
14.6

14.6
15.1
14.2
14.4
CO
PPM
(3% 02,
Dry)

19
24
23

30
25
32
319

21
24
199

24
87
53
376
Temp.


°F

596
672
659

703
724
672
665

587
587
590

633
608
635
632
  *
 **
***
B mill off - secondary air dampers closed on idle burners.

B mill off - secondary air dampers open on 1/2 of idle burners.

B mill off - secondary air dampers open on all idle burners.


                           NOTE:  Hydrocarbons were measured on each test but
                                  values were negligible except where indicated.

-------
                                 B-l
                              APPENDIX B
                             Coal Analyses

          Representative coal samples were taken for each major test under
baseline and "low NO " operating conditions.  The samples were submitted
to the Exxon Research and Engineering Company's Coal Analysis Laboratory
at Baytown, Texas for analysis.  Ultimate analysis determinations, which
were of most importance to the study, were made on all samples as indicated
in the following tables for each boiler tested.  Proximate analyses informa-
tion are also tabulated, where available.  Ash fusion temperature deter-
minations under reducing and oxidizing conditions and analyses for critical
coal ash elements were obtained on coal samples taken during certain impor-
tant tests in an attempt to shed more light on potential slagging or foul-
ing side effects of "low NO " firing techniques.
                           x
             All coal analyses data, which were used for making various
calculations in this report, are tabulated in Tables 1-10 of Appendix B.

-------
                                                        APPENDIX B

                                                          TABLE 1

                                                       COAL ANALYSES

                                              TENNESSEE VALLEY AUTHORITY
                                           WIDOWS CREEK STATION - UNIT NO. 6
Run No.
                                       1A
10
10-A-l   10-C-l   10-C-3   10-C-5
                                                                                                1-B     26-A-l    26-A-3
Proximate Analysis
Moisture
Ash
Voaltiles
Fixed Carbon
Sulfur
BTU/LB.
Ultimate Analysis
C - % Dry
H - % Dry
S - % Dry
N - % Dry
Cl - % Dry
0 - % Dry
Ash - % Dry
BTU/LB. - % Dry
Ash Fusion Temperature
Reducing
Int.
H=W
H=W/2
Fl.
Oxidizing
Int.
H=W
H=W/2
Fl.
6.3






66.06
4.13
0.82
1.29

5.82
21.88
11,739


2450
2700
2700
2700

2475
2700
2700
2700
                                       5.4
                                      71.11
                                       4.54
                                       0.81
                                       1.40

                                       5.36
                                      16.78
                                     12,106
                                      2350
                                      2600
                                      2625
                                      2680
                                      2400
                                      2700
                                      2700
                                      2700
5.6
  8.7
7.2
7.7
8.5
71.22
4.46
0.96
1.39
5.88
16.08
12,689
2460
2675
2700
2700
2500
2700
2700
2700
66.22
4.60
4.04
1.31
7.56
16.28
12,068
1975
2035
2055
2140
2360
2500
2510
2515
69.01
4.97
4.00
1.43
8.39
12.20
12,646
2000
2070
2130
2300
2340
2515
2525
2545
67.27
4.63
3.09
1.37
8.06
15.58
12,168
2085
2160
2190
2250
2450
2535
2560
2570
65.68
4.48
3.70
1.33
7.29
17.53
11,919
2025
2110
2125
2165
2225
2500
2520
2525
5.1
8.8
67.48
4.36
1.36
1.35
6.05
19.38
12,094
2450
2660
2700
2700
2500
2700
2700
2700
66.28
4.55
3.36
1.36
7.58
16.87
12,019
2025
2120
2140
2200
2450
2500
2525
2590
7.5
                                                              67.79
                                                                 46
                                                                 40
                                                                 72
                                                               6.37
                                                              17.27
                                                             12,218
                                                              2130
                                                              2400
                                                              2430
                                                              2460
                                                              2590
                                                              2635
                                                              2665
                                                              2670

-------
                                                                APPENDIX B

                                                                  TABLE 2

                                                               COAL ANALYSES

                                                            GEORGIA POWER COMPANY
                                                     HARLLEE BRANCH STATION - UNIT NO.  3
Run No.
                                    1-A      1-C      1-D      1-E      1-G      1-H      52      52-A     52-B     52-C     52-D     52-E
Proximate Analysis

 Moisture
 Ash
 Volatiles
 Fixed Carbon
 Sulfur
 BTU/LB.

Ultimate Analysis
7.9       6.31     5.1      5.82     7.86      6.92      7.58      7.4      5.07     5.86     6.98    13.92     7.01
c —
H
S
N
Cl
0
Ash
BTU/LB. -
Ash Fusion
Reducing
Int.
H=W
H=W/2
Fl
Oxidizing
Int.
H=W
H=W/2
Fl.
% Dry
% Dry
% Dry
% Dry
% Dry
% Dry
7. Dry
% Dry
Temperature










72.15
4.78
1.12
1.71

8.23
12.02
12,874


2175
2625
2700
2700

2550
2700
2700
2700
73.27
4.89
1.16
1.76

7.63
11.30
13,147


2300
2450
2475
2600

2500
2700
2700
2700
71.69
4.93
1.65
1.71

7.34
12.70
12,972


2140
2400
2415
2450

2375
2660
2675
2685
74.17
5.01
1.27
1.84

7.39
10.32
13,367


2150
2425
2450
2600

2275
2690
2700
2700
73.94
4.89
1.12
1.78

8.97
9.31
13,155


2475
2500
2520
2530

2520
2700
2700
2700
72.53
4.93
1.51
1.81

7.10
12.12
13,108


2250
2450
2470
2500

2615
2656
2685
2700
'5.39
5.06
1.41
1.93
7.09
9.12
i,605
73.96
4.96
1.61
1.87
6.53
11.07
13,309
75.37
5.07
1.08
1.82
7.29
9.44
13,576
73.89
4.97
1.25
1.77
7.18
10.94
13,315
73.34
4.96
1.09
1.77
7.79
11.05
13,185
72.40
4.85
1.24
1.74
7.81
11.96
12,986
71.50
4.77
1.32
1.40
8.26
12.76
12,783

W
1
u>




                                                                                2400
                                                                                2500
                                                                                2515
                                                                                2570
                                                                               2525
                                                                               2700
                                                                               2700
                                                                               2700
                                                              2200
                                                              2400
                                                              2450
                                                              2475
                                                              2420
                                                              2640
                                                              2670
                                                              2690
2350
2450
2465
2550
2575
2700
2700
2700
2325
2480
2525
2600
2595
2700
2700
2700
2330
2490
2510
2540
2600
2700
2700
2700
2270
2475
2500
2530
2700
2700
2700
2700
2360
2600
2630
2695
2700
2700
2700
2700

-------
B-4
APPENDIX B
TABLE 3
GOAL ANA.LYSKS
UTAH POWER AND LIGHT CO.
NAUGHTON STATION, BOILER NO.
Run Number
Date - 1972
Raw Coal Sample
Moisture, %
Tin w> J «w>mvvn f~* -^ •* i-fc J n Vs. -! 1 -S 4-<>v
Hardgrove Gnndability
Pulverized Coal Sample
Proximate Analysis
Moisture
Ash
Volatiles
Fixed Carbon
Btu/lb
Ultimate Analysis
C, % Dry
H, % Dry
S, % Dry
N, % Dry
Cl, % Dry
0, % Dry
Ash, % Dry
18
9-21





12.23
5.47
39.12
43.18
10,566

70.06
4.89
0.49
1.47
0.01
16.47
6.23
19
9-21

- 23.55
r o /
_> J.4

10.97
5.78
39.57
43.68
10,688

69.86
4.88
0.48
1.57
0.01
16.42
6.49
20
9-21





13.38
6.19
38.23
42.20
10,326

69.37
4.85
0.51
1.58
0.01
16.30
7.15
21
9-21





13.57
6.39
38.04
42.00
10,276

69.19
4.83
0.59
1.53
0.01
16.26
7.39
3
22
9-27

—


14.35
8.80
36.53
40.32
9,866

67.04
4.68
0.55
1.60
0.01
15.76
10.27

23
—

24.41
/ f\ C
49.5

11.55
8.16
38.78
41.51
10,293

67.62
4.71
0.68
1.64
.01
16.11
9.23

25
10-9

22.98
54.9

13.40
6.78
37.75
42.07
10,273

69.14
4.83
0.63
1.65
0.01
15.91
7.83

26
10-10

22.91
51.6

13.99
8.10
36.61
41.30
9,992

67.61
4.75
0.63
1.57
0.01
16.01
9.42

-------
                                              APPENDIX B
                                                TABLE 4

                                             COAL ANALYSES
                                      ARIZONA PUBLIC SERVICE CO.
                                 FOUR CORNERS STATION, BOILER NO.
Run No.
Lab.  No.
Date, 1972

Pulverized Coal
 12A
1-14B
11-18
621B
1-15A
11-8
1C&1D
1-15A
11-9
1A&6A
1-17A
11-3
19,20,21
  1-18A
  11-2
1,2,3,4
 1-18A
  11-5
  IE
1-19A
11-14
 12B
1-23B
11-21
Ultimate Analysis
c,
H,
s,
N,
Cl,
o,
Ash,
% Dry
% Dry
% Dry
% Dry
% Dry
% Dry
% Dry
  IF
1-16B
11-15
Proximate Analysis
Moisture, %
Ash
Volatiles
Fixed Carbon
Btu/lb.

11.71
23.13
31.47
33.69
8,913

12.70
21.35
31.35
34.60
8',947

12.88
21.86
31.02
34.24
8,801

13.97
21.01
30.91
34.11
8,763

14.05
21.18
30.79
33.98
8,787

13.29
20.61
31.42
34.68
8,944

12.91
21.92
30.88
34.29
8,821

13.10
21.12
31.21
34.57
8,915

12.79
21.96
30.68
34.57
8,811
56.95
4.34
0.75
1.23
0.01
10.53
26.19
58.05
4.35
0.79
1.23
—
11.11
24.46
57.51
4.25
0.75
1.31
—
11.10
25.09
58.67
4.26
0.85
1.24
—
11.16
24.42
57.69
4.32
0.80
1.26
—
11.04
24.93
58.43
4.34
0.70
1.29
—
11.47
23.77
57.50
4.30
0.76
1.26
0.01
11.00
25.17
58.15
4.31
0.81
1.24
0.01
11.18
24.30
57.28
4.27
0.67
1.29
0.01
11.30
25.18
                                                                                           I
                                                                                           Ui

-------
B-6
APPENDIX B
TABLE 5
COAL ANALYSES*
GULF POWER COMPANY

Laboratory No
Run No
Date
PROXIMATE ANALYSIS
Moisture
Ash
Volatiles
Fixed Carbon
Sulfur
BRU/Lb .
ULTIMATE ANALYSIS
C - % Dry
H - % Dry
S - % Dry
N - % Dry
Cl- 7. Dry
0 - % Dry
Ash % Dry
BTU/
Lb.% Dry
ASH ELEMENTS
so3
MgO
Si02
A12°3
Fe2°3
CaO
^0
Ti02
P2°5
Total
ASH FUSION TEMPERATURES
Reducing - ID
- H=W
- H=W/2
- Fluid
Oxidizing- ID
- H=W
- H=W/2
- Fluid
CRIST STATION,
M15901
2&3
Dec 6-72

9.24
8.50
36.76
45.5
-
11,855

72.19
5.05
3.32
1.38
-
8.69
9.37
13,060


6.0
0.8
41.9
20.0
24.8
5.9
1.8
1.0
<0.1
102.2
°F
2020
2120
2270
2340
2360
2420
2540
2580
BOILER NO.
M15898
26
Dec 7-72

10.47
12.04
33.06
44.43
_
11,282

69.99
4.81
3.48
1.33
-
6.94
13.45
12,602


9.7
0.7
41.4
14.5
24.6
8.4
1.9
0.9
0.5
102.6

2030
2070
2140
2280
2280
2350
2430
2520
6
M15903
4&5
Dec 8-72

8.13
8.49
37.57
45.81
_
11,920

72.15
5.09
3.62
1.43
-
8.47
9.24
12,974


3.9
0.8
41.7
20.8
27.7
3.4
1.9
1.1
<0.1
101.3

1980
2040
2280
2330
2400
2480
2530
2580

M15691
1,5A,10&26B
Dec 11-12,72

9.6
10.2
-
-
_
11,186

69.23
4.93
4.80
1.33
-
8.43
11.28
12 ,374


0.6
0.6
37.5
20.5
40.6
0.7
1.9
1.0
<0.1
103.4

2000
2040
2080
2130
2530
2570
2610
2650
* Analyses furnished through the courtesy of Foster Wheeler Corporation.

-------
           APPENDIX B
             TABLE 6



COAL AND PETROLEUM COKE ANALYSES
ALABAMA POWER COMPANY
BARRY STATION, BOILER NO. 4
Run No .
Laboratory No.
Sample Identification*
Sample Date
Raw Coal Sample
Proximate Analysis
Moisture
Ash
Volatiles
Fixed Carbon
Btu/lb
Ultimate Analysis
C - % Dry
H - % Dry
S - % Dry
N - % Dry
Cl - % Dry
0 - % Dry
Ash - % Dry
% Used
Ash Elements
P205
Si02
Fe203
A12°3
Ti02
CuO
MgO
so3
K20
Na20
Total
Ash Fusion - Reducing
I.D.
H=W
H=1/2W
Fluid
- Oxidizing
I.D.
H=W
H=1/2W
Fluid
1
6076
1-A,B,D,E
1-23-73


7.72
12.11
31.73
48.44
11,877

71.39
4.75
2.73
1.52
0.09
6.40
13.12
80.2

0.37
45.62
19.01
24.06
1.10
2.57
0.89
3.31
2.09
0.31
99.33

2100
2135
2150
2180

2485
2525
2550
2560
2
6077 6078
1-C 2-A,B,D,E
1-23 1-23


6.40 6.99
2.22 11.86
14.67 32.12
76.71 49.03
14,020 12,022

85.11 71.69
4.01 4.77
3.97 2.65
1.20 1.55
0.0
3.34 6.59
2.37 12.75
19.8 80.3

0.38
45.91
16.93
21.91
1.08
4.36
1.09
4.28
2.04
0.03
98.28

	
—
—
—

—
—
—
—
6
6079 6080
2-C 6-B.D.E
1-23 1-23


5.69 7.25
2.37 10.89
14.76 32.40
77.18 49.46
14,106 12,127

84.99 72.52
4.00 4.83
3.98 2.61
1.08 1.59
—
3.44 6.71
2.51 11.74
19.7 75.6












* Note:
• Letters
• Samples
• Samples
coal and





6081
6-C
1023


5.76
1.93
14.82
77.49
14,163

85.39
4.02
4.03
1.22
—
3.29
2.05
24.4













8
6082
8-B.D.E
1023


6.09
9.95
33.23
50.73

6083
8-C
1023


6.33
2.79
14.59
76.29
12,438 13,943

73.47
4.89
2.68
1.59
—
6.78
10.59
75.8














84.58
3.98
3.81
1.25
—
3.40
2.98
24.2













13
6084
13-A,B,D,E
1-19


8.17
12.76
31.29
47.78

6085
13-C
1-19


8.13
13.14
31.16
47.57
11,714 11,664

70.76
4.71
2.40
1.52
—
6.72
13.89
81.4














70.42
4.69
1.92
1.45
—
7.22
14.30
18.6













13A
6086 6087
13-A,B,D,E 13-C
2-5 2-5-73


2.10 8.09
10.03 9.71
34.78 32.53
53.09 49.67
13,017 12,178

73.75 73.49
4.91 4.89
3.38 3.15
1.43 1.39
—
6.28 6.52
10.25 10.56
77.7 22.3













refer to pulverisers.
marked "A,
marked "C"
petroleum





B, D, E"
are 100%
coal
are petroleum coke or mixtures
coke.


















of















-------
           APPENDIX B
       TABLE 6 (Continued)
COAL AND PETROLEUM COKE ANALYSES
ALABAMA POWER COMPANY
BARRY STATION, BOILER NO. 4
Run No. 20
Laboratory No. 6097
Sample Identification* 20-A,B,D,E
Sample Date 1-22
Conditions 	
Raw Coal Sample
Proximate Analysis
Moisture 10.38
Ash 9.36
Volatiles 31.76
Fixed Carbon 48.50
Btu/lb 11,890
Ultimate Analysis
C - % Dry 73.59
H - % Dry 4.90
S - % Dry 3.38
N - 7. Dry 1.50
Cl - % Dry
0 - % Dry 6.19
Ash - % Dry 10.44
% Used 76.5
Ash Elements
P205
Si02
Fe203

Ti02
CaO
MgO
S03
K20
Na20
Total
Ash Fusion - Reducing
I.D.
H=W
H-1/2W
Fluid
- Oxidizing
I.D.
H=W
H=1/2W
Fluid

6098
20-C
1-22


6.37
2.55
14.62
76.46
13,974

84.80
4.00
4.04
1.19
—
3.25
2.72
23.5







*
29
6099
29-A,B,D,E
1-19


9.16
13.24
30.71
46.89
11,496

70.19
4.67
2.05
1.51
—
7.00
14.58
81.4







Note:
30 31
6100
29-C
1-19


8.47
10.86
18.83
61.84
11,394

75.74
4.47
2.39
1.47
—
4.07
11.86
18.6








6101
30-A,B,D,E
1-19


7.21
9.08
33.13
50.58
12,401

74.13
4.93
2.58
1.30
—
7.27
9.79
81.2








6102 6103 6104
30-C 31-A,B,D,E 31-C
1-19 1-19 1-19


8.03 8.76 6.98
11.20 12.71 9.43
18.86 31.08 19.51
61.91 47.45 64.08
12,410 11,634 12,843

75.46 70.22 77.22
4.45 4.71 4.55
2.45 2.06 2.18
1.51 1.49 1.34
—
3.95 7.09 4.57
12.18 13.93 10.14
18.8 81.3 18.7








• Letters refer to pulverizers
• Samples marked "A, B,
D, E" are
100% coal
• Samples marked "C" are petroleum coke or
mixtures of coal and petroleum coke.


















































42A
6106
42A-B.D.E
2-22


10.05
6.85
36.76
46.34
11,929

73.13
5.22
3.18
1.44
.061
9.35
7.62
69.3

.23
45.30
23.95
22.58
1.17
1.50
0.60
1.67
1.95
0.14
99.09

2070
2100
2120
2140

2535
2560
2570
2600
42B
6-107 6108 6109
42A-C 42B-B,D,E, 42B-C
2-22 2-23 2-23


6.74 10.01 6.18
0.11 6.99 0.11
12.03 36.72 12.10
81.12 46.28 81.61
14,382 11,915 14,468

86.42 73.01 86.43
3.86 5.21 3.86
4.52 3.29 4.59
1.13 1.38 1.14
—
4.07 9.34 3.87 ?
0.12 7.77 .114 °°
30.7 69.0 31.0

.39
26.15
20.15
14.29
1.42
3.69
0.98
3.25
2.31
0.49
73.18

—
—
—
—

—
—
—
—

-------
                                                  APPENDIX B
Run No.
Laboratory No.
Sample Identification*
Sample Date
Conditions
Proximate Analysis
  Moisture
  Ash
  Volatiles
  Fixed Carbon
  Btu/Lb
Ultimate Analysis
  C
  H
  S
  N
  Cl
  0
  Ash
  7, Used
% Dry
% Dry
% Dry
% Dry
% Dry
% Dry
  Dry
Ash Elements

  P205
  Si02
  Fe203
  A1203
  Ti02
  CuO

  S03
  K20
  Na20
  Total
Ash Fusion - Reducing
  I.D.
  H-W
  H-1/2W
  Fluid
           - Oxidizing
  I.D.
  H=W
  H-1/2W
  Fluid
TABLE 6 (Continued)
COAL AND PETROLEUM COKE ANALYSES
ALABAMA POWER COMPANY
BARRY STATION, BOILER NO. 4

6088
17-A,B,D
1-22
10.33
10.17
31.46
48.04
11,778
72.85
4.85
3.63
1.48
—
5.85
11.34
79.7




















17
6089
,E 17-C
1-22
6.42
2.47
14.63
76.48
13,979
84.87
4.00
3.98
1.20
—
3.31
2.64
20.3











* Note:
• Letters
• Samples
• Samples
mixtures




18
6090
19 19A
6091
18-B.D.E 19-B,D,E
1-22
10.58
8.17
32.16
49.09
12,037
74.66
4.97
3.56
1.52
—
6.15
9.14
100.0












re fer to
marked "A
marked "C
of coal




1-22
8.42
9.41
32.52
49.65
12,173
73.73
4.91
3.51
1.50
—
6.08
10.28
77.0












pulverizers
, B, D, E"
6092 6093
19-C 19A-B,D,E
1-22 2-13
6.40 8.05
2.42 11.33
14.64 33.37
76.54 47.25
13,989 11,665
84.92 70.32
4.00 4.88
4.14 2.90
1.17 1.40
—
3.18 8.18
2.59 12.32
23 69.8













are 1007= coal
6094
19A-C
2-13
9.42
9.21
19.00
62.37
12,502
77.19
4.55
3.16
1.32
—
3.61
10.17
30.2














" are petroleum coke or
and petroleum coke.












19B
6095
19B-B.D.E
2-14
9.84
7.67
34.14
48.35
11,936
73.38
5.09
3.29
1.44
0.073
8.23
8.50
69.6
0.40
44.50
22.21
22.49
1.17
1.99
0.88
2.17
2.38
0.32
98.50

2050
2100
2115
2130
2450
2500
2525
2535
6096
19B-C
2-14
6.93
11.51
19.04
62.52
12,531
75.30
4.44
2.81
1.41
—
3.67
12.37
30.4
.81
48.08
13.85
27.47
1.45
2.00
1.10
2.09
2.39
0.28
99.52

—
—
—
	
__
—
—
—

-------
B-10
APPENDIX B


TABLE 7



COAL ANALYSES

TAMPA
ELECTRIC
CO.
BIG BEND STATION, BOILER NO.
Laboratory No.
Run No .
Date
Time
Proximate Analysis
Moisture - %
Ash - %
Volatiles - %
Fixed C - %
Sulfur - %
BTU/lb - %
Ultimate Analysis
C - % Dry
H - % Dry
S - % Dry
N - % Dry
Cl - % Dry
0 - % Dry
Ash - % Dry
BTU/lb - % Dry
Ash Elements
P205
Si02
Fe203
A1203
Ti02
CaO
MgO
S03
K20
Na20
Total
Ash Fusion Temperatures °F
Reducing - I.D.
- H=W
- H=W/2
- Fluid
Oxidizing - I.D.
- H=W
- H=W/2
- Fluid
96135
4
3-5-73
1730

10.63
13.13
34.16
42.08
3.48
10,682

66.49
4.71
3.89
1.26
.03
8.96
14.69
11,952





















96136
2
3-6-73
0930

11.66
14.07
32.60
42.21
3.19
10,585

65.75
4.65
3.61
1.39
0.10
9.21
15.93
11,982

0.31
44.86
22.90
17.83
.80
4.87
0.86
6.16
2.11
0.21
100.89

2000
2015
2035
2045
2340
2370
2450
2475
96137
3
3-6-73
1445

10.75
13.78
34.54
40.93
3.44
19,576

66.02
4.59
3.86
1.41
0.10
8.68
15.44
11,849

0.26
45.21
20.28
17.66
0.87
4.91
0.83
6.85
2.00
0.22
99.10

2000
2040
2050
2075
2320
2380
2450
2470

2
96138
10
3-12-73
1230

10.85
13.52
33.88
41.75
3.66
10,780

66.86
4.71
4.11
1.39
	
7.77
15.16
12,092























96139
20
3-7-73
0830

10.98
13.85
33.68
41.75
3.72
10,505

65.86
4.56
4.18
1.38
	 —
8.47
15.55
11,801






















-------
B-ll
APPENDIX B
TABLE 8









COAL
ANALYSES
CENTRAL ILLINOIS LIGHT COMPANY
E. D. EDWARDS STATION, BOILER NO. 2
Laboratory Ho.
Run No.
Mills
Date
Proximate Analysis
Moisture
Ash
Volatiles
Fixed Carbon
Sulfur
BTU/LB.
Hardgrove Grind.
Ultimate Analysis
C - 7. Dry
H - "1, Dry
S - % Dry
N - 7. Dry
Cl - % Dry
0 - % Dry
Ash - '/, Dry
BTU/LB. - % Dry
96168
1
ABCD
6-11-73

15.97
9.94
32.81
41.28
3.07
10,433


68.96
4.96
3.66
1.25
0.02
9.32
11.829
12,416
96169
2
ABCD
6-11-73

15.65
9.38
33.20
41.77
2.90
10,557


69.51
5.00
3.44
1.27
0.02
9.64
11.12
12,516
96170
3
ABCD
6-12-73

16.77
9.83
32.50
40.90
2.94
10,335


68.97
4.97
3.53
1.25
0.02
9.45
11.81
12,417
96171
4
ABCD
6-12-73

16.02
9.34
31.91
42.73
3.00
10,530
54.5

69.66
4.99
3.57
1.26
0.02
9.38
11.12
12,539
96172
5
ABCD
6-12-73

17.07
10.61
32.02
40.29
2.66
10,183


68.21
4.91
3.21
1.20
0.02
9.66
12.79
12,279
96173
6
ABCD
6-12-73

17.26
14.07
30.41
38.26
2.56
10,170


64.91
4.67
3.09
1.19
0.02
9.11
17.01
12,292
96174
7
ABC
6-13-73

17.40
9.68
32.29
40.63
2.69
10,268


69.04
4.97
3.26
1.24
0.02
9.75
11.72
12,431
96175
8
ABC
6-13-73

18.07
9.53
32.06
40.34
2.80
10,195


69.11
4.98
3.41
1.25
0.02
9.60
11.63
12,444
96176
23
ABCD
6-13-73

15.94
9.33
33.28
46.45
2.88
10,576
54.5

69.851
4.993
3.429
1.236
0.022
9.37
11.10
12,582
96177
24
ABCD
6-13-73

16.04
8.89
33.24
41.83
2,98
10,571


69.93
5.03
3.55
1.25
0.02
9.63
10.59
12,591
96178
13
ABC
6-13-73

17.37
9.27
32.48
40.88
2.80
10,330


69.43
5.00
3.39
1.24
0.02
9.70
11.22
12,502
96179
18
ABC
6-13-73

17.65
8.66
32.63
41.06
2.46
10,376


69.98
5.04
2.99
1.25
0.02
10.20
10.52
12,600
96180
14
ABC
6-14-73

17.12
9.90
32.32
40.66
2.80
10,276


68.87
4.96
3.37
1.18
0.02
9.66
11.94
12,399
96181
10
ABC
6-14-73

16.55
9.22
32.87
41.36
2.82
19,452


69.57
5.01
3.38
1.26
0.02
9.71
11.05
12,525
96182
11
ABC
6-14-73

16.29
9.55
32.84
41.32
2.91
10,442


69.29
4.99
3.47
1.26
0.02
9.56
11.41
12,474
96183
12
ABC
6-14-73

15.40
9.59
34.17
40.84
3.10
10,488
55.9

68.86
5.01
3.66
1.32
0.03
9.78
11.34
12,397
96184
9
ABC
6-14-73

15.37
9.37
33.33
41.93
2.93
10,597


69.55
5.01
3.47
1.28
0.02
9.60
11.07
12,522
96185
16
ABCD
6-15-73

14.89
9.17
33.63
42.32
30.1
10,695


69.79
5.02
3.53
1.23
0.02
9.64
10.77
12,565
96186
20
ABC
6-15-73

15.27
9.29
33.40
42.04
3.05
10,623


69.64
5.01
3.60
1.23
0.02
9.54
10.96
12,537
96187
1A
ABCD
6-15-73

13.72
8.24
34.56
43.48
1.97
10,989


70.78
5.10
2.29
1.42
0.02
10.89
9.50
12,670

-------
APPENDIX B
TABLE 9
COAL ANALYSES
BASIN ELECTRIC POWER COOPERATIVE
STANTON, NORTH DAKOTA, BOILER NO. 1
Base
Laboratory No.
Run No.
Source
Date
Proximate Analysis
Moisture
Ash
Volatiles
Fixed Carbon
Sulfur
Btu/Lb
Hardgrove Grind.
Ultimate Analysis
C - % Dry
H - % Dry
S - % Dry
N - % Dry
Cl - % Dry
0 - % Dry
Ash - % Dry
Btu/Lb - Dry
Ash Elements
P2<>5
Si02
Fe203
A1203
Ti02
CaO
MgO
S03
K20
Na20
Total
Ash Fusion Temperatures
Reducing - I.D.
- H-W
- H=W/2
- Fluid
Oxidizing - I.D.
- H=W
- H=W/2
- Fluid
96189
1
Storage
7/6/73

36.44
7.61
28.01
27.70
0.41
6704


62.81
4.27
0.64
1.04
0.08
19.17
11.97
10548





















96190
1A
Mine
7/10/73

38.71
5.90
27.02
28.36
0.53
6643
29.5

64.44
4.43
0.87
1.08
0.07
19.55
9.63
10838

0.08
23.81
9.72
9.69
0.51
19.00
4.10
22.35
0.68
7.90
97.83

2220
2230
2240
2250
2250
2270
2275
2280
96191
3 & 4
Storage
7/9/73

34.42
6.16
29.75
29.41
0.43
7120


64.66
4.39
0.66
1.03
0.08
19.73
9.39
10858





















96192
4A & B
—
7/11/73

38.36
5.55
29.19
26.91
0.46
6710
27.3

65.03
4.39
0.47
1.09
0.08
19.76
9.00
10886

0.06
20.79
9.32
9.13
0.47
20.44
4.69
23.58
0.48
7.68
96.63

1990
2120
2150
2240
2200
2275
2280
2290
96193
4C
Mine
7/12/73

37.59
6.30
27.72
28.39
0.34
6728
27.3

64.11
4.35
0.55
1.12
0.08
19.78
10.09
10781

0.07
28.63
8.17
10.07
0.52
18.70
4.40
21.10
0.74
5.20
97.61

2090
2140
2145
2150
2190
2210
2220
2225
Low NOx
96194
5
Storage
7/9/73

36.94
5.29
28.93
28.60
0.35
6922


65.37
4.44
0.55
1.08
0.08
19.95
8.39
10977





















96195
6
Mine
7/10/73

37.95
6.03
28.05
27.73
0.43
6712


64.42
4.38
0.69
1.05
0.08
19.66
9.72
10817





















96916
7
Mine
7/10/73

39.21
5.92
27.47
27.16
0.38
6575


64.42
4.38
0.62
1.05
0.08
19.66
9.73
10816





















96197
9
Mine
7/10/73

38.11
8.54
26.71
26.41
1.11
6392


61.51
4.18
1.37
1.11
0.08
18.77
13.80
10328





















96198
11
Mine
7/10/73

37.66
6.11
28.15
27.83
0.46
6737


64.36
4.37
0.74
1.07
0.08
19.64
9.81
10807






















-------
                                                               APPENDIX B
                                                                TABLE 10
                                                               COAL ANALYSES

                                              PACIFIC POWER AND LIGHT CO., GLEN  ROCK, WYOMING

                                                          DAVE JOHNSTON STATION
Laboratory No.
Run No.
Boiler No.
Date
Proximate Analysis
  Moisture
  Ash
  Volatiles
  Fixed Carbon
  Sulfur
  Btu/Lb
  Hardgrove Grind.
Ultimate Analysis
  C
  H
  S
  N
  Cl
  0
  Ash
  Btu/Lb -
% Dry
% Dry
% Dry
% Dry
% Dry
% Dry
% Dry
% Dry
Ash Elements
  P205
  Si02
  Fe203
  A1203
  TiO
  CaO
  MgO
  S03
  K20
  Na20
  Total
Aah Fusion Temperatures
Reducing



Oxidizing



- I.D.
- H=W
- H=W/2
- Fluid
- I.D.
- H=W
- H=W/2
- Fluid
               96203    96204    96205    96206    96207    96208    96209    96210    96211   96212   96213   96214   96215
                 3        4        1        2        5        6        7        8        10      13      16       24
                 2222222222244
              7/27/73  7/27/72  7/30/73  7/30/73  7/30/73  7/30/73  7/31/73  7/31/73  7/31/73  8/1/73  8/1/73  8/8/73  8/8/73
26.05
13.80
30.67
29.48
0.51
7334

58.41
4.23
0.69
0.77
0.05
17.38
18.66
9918



















27.25
11.31
31.33
30.11
0.55
7491

60.65
4.39
0.76
0.79
0.05
18.05
15.54
10298



















28.86
7.55
32.42
31.17
0.45
7754

64.19
4.65
0.63
0.83
0.05
19.10
10.61
10899



















28.27
7.07
32.97
31.69
0.46
7884
28.7
64.73
4.69
0.64
0.82
0.05
19.26
9.86
10991
0.54
30.56
4.99
15.21
1.11
26.12
3.29
12.37
0.49
0.55
95.24
2125
2145
2150
2155
2170
2190
2200
2210
28.21
7.71
32.67
31.41
0.48
7813

64.01
4.64
0.66
0.82
0.05
19.07
10.74
10883



















28.26
7.63
32.69
31.42
0.53
7817

64.17
4.65
0.74
0.86
0.05
19.10
10.64
10896



















28.58
7.77
32.46
31.19
0.46
7761

64.00
4.63
0.64
0.83
0.05
19.04
10.88
10866



















28.85
7.31
32.55
31.29
0.49
7784

64.44
4.67
0.69
0.81
0.05
19.18
10.27
10941



















29.31
7.22
32.36
31.11
0.56
7739

64.47
4.67
0.79
0.83
0.05
19.19
10.22
10947



















29.28
6.43
32.78
31.51
0.49
7839

65.28
4.73
0.69
0.81
0.05
19.43
9.09
11085



















27.54
7.58
33.08
31.80
0.56
7911

64.30
4.66
0.77
0.84
0.05
19.13
10.46
10918



















16.51
13.67
35.55
34.26
0.63
8464

59.36
4.33
0.75
0.75
0.06
18.44
16.38
10138
0.31
42.91
4.24
18.77
0.97
15.67
2.48
10.01
1.09
0.47
96.93
2190
2250
2270
2300
2335
2375
2380
2390
15.32
16.29
34.82
33.56
0.57
8291

57.33
4.18
0.68
0.76
0.05
17.81
19.24
9791



















                                                                                                                                 60
                                                                                                                                 I

-------
                                 C-l
                              APPENDIX C

          CROSS SECTION DRAWINGS OF TYPICAL UTILITY BOILERS
          Typical utility boiler designs representative of the types of
boilers tested in this program are shown in the cross sectional drawings
in Figures 1 through 6 of Appendix C.  Typical front wall and horizontally
opposed fired boilers are shown in Figures 1, 2 and 3,  respectively, a
tangentially fired boiler is shown in Figure 4, and Figures 5 and 6 are
typical of turbo furnace and cyclone fired units.

-------
                                     C-2
                                  APPENDIX C
                                   FIGURE 1
                         TYPICAL  FRONT WALL FIRED BOILER
/         \ /  LY ASM   I       // ff\ I  /S I  -r r- t	       I \   gTFTU^^Bp
      /:.. V^^°" | LJI^-^f^LkAl-.^ _jj--r^-r,5M  Llny/C^   I.B
^^rJ^'Kv-^.v v- "'^ >V;. "*-'• :.'s:5fe'" < fe5>''-^^P?r.* *-:'-^ •• '-:::-^\
                                              ^"'•'*:      -^
           -27'-0"-
                       -32'-0"-
                                      -44'-0"-
                                                      -32'-0"-
                                                                   -30'-0"-
                     DRAWING FURNISHED THROUGH THE COURTESY OF
                         THE BABCOCK AND WILCOX COMPANY

-------
                           C-3
                         APPENDIX C
                          FIGURE 2
               TYPICAL FRONT WALL FIRED  BOILER
                                                           EL. l724'-6"
£L. l708'-6"
           eo'i.o.    J_  SPRAT CONTROL HEADER
            ^J --B „=.! -  El L
                                       HEATER OUTLET
                                                           TER
            DRAWING FURNISHED THROUGH THE COURTESY OF
                   THE FOSTER WHEELER CORPORATION

-------
                                         C-4
                                       APPENDIX C

                                        FIGURE  3

                        TYPICAL HORIZONTALLY OPPOSED FIRED BOILER
223-0"
                       DRAWING FURNISHED THROUGH THE COURTESY OF
                            THE BABCOCK AND WILCOX COMPANY

-------
                  C-5
               APPENDIX C

                FIGURE 4

    TYPICAL TANGENTIALLY FIRED BOILER
DRAWING FURNISHED THROUGH THE COURTESY OF
      COMBUSTION ENGINEERING, INC.

-------
                 C-6

               APPENDIX C

                FIGURE 5
   TYPICAL TURBO FURNACE FIRED BOILER
DRAWING FURNISHED THROUGH THE COURTESY
    OF THE RILEY STOKER CORPORATION

-------
                                C-7

                          APPENDIX  C

                            FIGURE 6

                TYPICAL  CYCLONE FIRED BOILER
                                       ATTEMPERATOR
                                               I!
                                         IJ,	PRIMARY SUPERHEATER
SECONDARY SUPERHEATER
    INLET
                                                          ECONOMIZER
                                                         OUTLET HEADER
                                                       - ECONOMIZER
                                                      >— ECONOMIZER
                                                         INLET HEADER
             DRAWING FURNISHED  THROUGH  THE COURTESY
                  OF THE  BABCOCK & WILCOX COMPANY

-------
                                  D-l
                               APPENDIX D
                   COMMENTS FROM BOILER MANUFACTURERS
          At the request of the EPA Project Officer, the boiler
manufacturers have reviewed this report.  Written comments were
received from Foster Wheeler Corporation and Riley Stoker Corporation
which are included in Appendix D.  These comments, plus verbal comments
received from the Bab cock and Wilcox Company, have been taken into
account in revising the Final Report.  Combustion Engineering, Inc.
accepted the report as written.

          The Riley Stoker Corporation in their comments, item 2,
suggest that the correlation of NOX emissions against megawatts per
equivalent furnace firing wall should be changed to NOX emissions
versus boiler load in pounds of steam per hour.  This is a valid comment
but the suggested adjustment is within the limits of error of the current
relationship.  More data is needed in order to add this refinement.  Riley
also points out that the correlation does not take into account differences
in fuel nitrogen content in the fuels fired.  The authors agree that fuel
nitrogen content is important.  However, the factors influencing the
quantitative conversion of fuel nitrogen to NOX emissions in coal fired
utility boilers have not yet been established.  Therefore, a correlation
of NOX emissions with fuel nitrogen content is not yet possible.  As more
data are developed, the refinements in the correlations, as pointed out
by Riley Stoker Corporation to be desirable, will be possible.

          The authors of the report wish to thank the reviewers for their
very constructive comments.

-------
                               D-2
                        APPENDIX   D
                             COMMENTS
                                TO
                           FINAL REPORT
                               FOR
                    EPA CONTRACT NO.  68-02-02227
      FIELD TESTING:  APPLICATION OF  COMBUSTION MODIFICATIONS
         TO CONTROL NOX EMISSIONS FOR LARGE UTILITY  BOILERS
FOSTER  WHEELER  CORPORATION
           110  SOUTH  OKANGK AVKNUK. LIVINGSTON. N. .1.
                     Prepared by:
                     R. E. Sommerlad,  Manager
                     Development Contract  Operations Dept.
                     Research Division

-------
                                   D-3
 INTRODUCTION




     Foster Wheeler Corporation  and  its client, Gulf Power Company, were




 pleased  to participate with  the  Environmental Protection Agency and its




 contractor, Esso Research and Engineering Company, in a program entitled




 "Field Testing: Application  of Combustion Modifications to Control NOV
                                                                     X.



 Emissions for Large Utility  Boilers".  The purpose of this appendix is to




 relate the efforts by the various participants in this program and to




 correlate the results found  with similar test programs by Foster Wheeler.




 TEST PROGRAM




     The program was conducted as described in Sections 4.1.1-4.1.3 and




 6.1.1.1.4 of the report and  included an agreement among the participants.




 The test program  included  specific  tests requested by FW as well as those




 requested by ERE.  New  test  connections were installed by Gulf.  ERE




 and FW test crews arrived in early December and data were taken through




 Dec. 14, 1972.  Due to anticipated load demands and ERE vacation schedules




 the test crews re-assembled  in January 1973 to renew testing.  During the




 interim period FW Service Engineers re-aligned registers and pulverizers to




 attempt  to correct side-to-side  unbalances as indicated by the flue gas




 composition.  The January period also proved fruitless due to operating




 demands.  All parties had previously agreed that load demand would have




 the highest priority.  As might  be expected this period of time coincided




with unseasonable cold weather requiring peak power almost constantly.  In




 order to keep other commitments  ERE had to go on to other plants.   ERE




 returned in March for two days.  FW resident service staff assisted but




FW test crews had been committed to other assignments.

-------
                                  D-4
PERFORMANCE TESTS




     In addition to  the  resident  start-up  crew FW provided  a  performance




test crew comprising five  engineers  and  the  district  service  manager.




Complete performance test  data were  obtained for  five runs  and included,




complete control data*,  tube metal temperatures,  fan  and  pulverizer power




input*, local steam  and  water pressures  and  temperatures, local air and gas




temperatures and pressures*, atmospheric ambient  conditions,  flue gas  com-




position from an array of  multiple points, air register and damper positions*,




ash coverage diagrams, and coal,  bottom  ash  and  fly ash samples for chemical




analyses.  Partial sets  of data*  were obtained during the eight runs.   Two




runs were attempted  but  then aborted due to  lack of stabilization time. FW




was concerned the firing unbalance from  side-to-side  which  was evident by




local 02, NOX and CO data  as measured.   This concern  was  later shown by




chemical analyses of bottom ash  and  fly  ash  which averaged  10.8 and 24.8%




combustible.



     As mentioned previously FW  spent considerable time  adjusting firing




equipment in late December with  the  hope that the December  tests could be




repeated with more meaningful results.   FW had run performance tests




previously on this unit  and NOX  tests on an identical unit  and therefore




could anticipate the results. Unfortunately the results  of these endeavors




were not realized in January.  During ERE's tests in March the results of




the above endeavors  were apparent by the consistency of  02 readings by ERE




as shown in Table 4, Appendix A.  However, the NOX data appear to confirm a











*Partial set includes items  from complete set marked with asterisks.

-------
                                  D-5
suspicion FW had formulated during the December tests as described below.




GASEOUS EMISSION TESTS




     In addition to the FW test crews mentioned earlier, FW also provided




an emission test crew comprising five engineers and technicians.  This in-




cluded FW's Mobile Pollution Monitoring Laboratory which housed continuous




analyzers for 02, NOX, and S02.  FW also brought in a trailer, the apparatus




to conduct wet chemical analyses and specified by EPA in the Test Methods




for the Standards of Performance.  FW probes were installed alongside ERE




probes.  The results of these efforts indicated that emission measuring by




FW's continuous analyzers were the same as ERE's analyzers and in addition




were confirmed by the EPA wet chemical procedures.  Members of the emission




test crew also aided ERE in particulate testing.




DISCUSSION OF RESULTS




     As indicated previously FW has hopes of participating in this program




to achieve meaningful results during the short test-period runs as had




been achieved by FW on an identical unit.  For this reason both performance




and emission test crews were committed to this test program.  It was also




anticipated that FW would oversee the 1-3 day sustained "low NOX" run and




the 300-hr sustained "low NOX" and normal operation runs.  Due to the un-




expected results of the short test-period and the unavailability of the unit




for re-testing, FW felt the performance test results were not indicative of




good commercial operation and declined to submit same in detail.




     On an identical unit FW data were the same as the ERE data for "Low NOX




I", S3 (Burners 2 & 3 on Air only).  However for "Low NOX II, 34 (Burners  1,




2, 3 & 4 on Air only) and S6 (Burners 5,  6,  7 & 8 on Air only)  the NOX

-------
                                  D-6
 reduction as % Baseline (20% Excess Air) NC)  was 33.3 where the % Stoichio-
                                           A



 metric Air to Active Burners calculated by FW was 88.0 which is in agreement




 with ERE's analysis as shown in Figure 2-4.




     During the December tests there was some confusion about register




 settings and rotation on three of the burners on the "A" side (Burner No. 3,




 4 and 7).  Prior to the test program these burner-register assemblies had




 been damaged and had been replaced with three assemblies from Unit No. 7




 under construction at the time.  The new assemblies were similar to the old




 assemblies and were fitted quite easily.  However, the new assemblies had




 a reversible register assembly.  To reverse the assembly is normally a shop




 setting.  These registers had to be rotated in the field requiring that




 the motor drives be reversed, hence the confusion.  Morever, the number of




 register blades and the shape of each individual blade is different.  Even




 though all assemblies were realigned in late December 1972 resulting in a




 better side-to-side Q£ balance as observed by ERE in March 1973, it is felt




 that the individual air flow rate and possibly the flow characteristics




 of the new assembly are different than the old assembly and effect swirl




and firing characteristics.   It is felt by some that the NOX formation occurs




within 1 or 2 feet of the throat and this could serve to explain the high




NOY on the "A" side.
  A.

-------
                               D-7
RILEY
         POST  OFFICE  BOX  547
 WORCESTER,  MASSACHUSETTS  O1613
STEAM GENERATING
AND FUEL BURNING
    EQUIPMENT
 "Field  Testing - Application of Combustion Modifications to
        Control NOX Emissions from Large Utility Boilers"
        by W. Bartok, A.R. Crawford, E.H. Manny, L. Berko-
        witz, and R.E. Hall
Review:
       Speaking for those of us at Riley who had the privi-
lege of working with the Esso "Tigers" test crew during the
planning and execution of their test program, the writer is
pleased to have the opportunity to commend these people for
their excellent work.  The subject report illuminates Esso's
experience in reducing nitrogen oxides (NOX) emissions from
coal fired utility boilers.
       Our comments and criticisms of this report are few.
It is perhaps the most accurate and fully documented study
of two-staged combustion yet to be published.  It was grati-
fying to us that the results of this study corroborate the
results of our own test program which investigated the two-
staged combustion of coal.  We also found that there is a
direct relationship between the air/fuel ratio at the fuel-
rich burners and the reduction of NOY emissions from all
                                    J\.
utility boilers.  Our own data,  when plotted against % of
stoichiometric air to active burners, fit right on top of

-------
                              D-8
the data In Figure  2-4 of this  report.  We  also  liked  the



way Esso addressed  iteslf to  the potential  operating problems



involved with combustion modification.  Their corrosion probe



results, although not conclusive,  do  indicate that the tube



wastage during two-staged combustion  may  be an overrated fear.



       The following are our  criticisms of  the report:



       1. On page 99, where the report  describes the  test



          conditions at Tampa Electric's  Big Bend No.  2 unit,



          we would  like to make a  few clarifications.   At the



          time of the test, the unit  was  limited to 375 M W



          due to superheater  slagging (from an isolated ship-



          ment of troublesome coal) and a steam  temperature



          problem which has been corrected after an extensive



          research  program.  This  unit has been  running for



          quite some time at  a load of 3,000,000 Ib/HR of



          steam (after all, a boiler produces steam,  not



          megawatts) which is above the maximum continuous



          rating of 2,856,000 Ib/HR.   However, the unit



          still has not exceeded 410-420 M W at this  steam



          flow due  to problems inherent in the turbine.







        2. The above point brings up one of the weaknesses



          of Esso's method of correlating NO  emissions
                                            J\~


          with the quantity  "M ¥ per equivalent furnace



          firing wall."  This correlation does not consider



          the efficiency of  the turbine which is  completely



          unrelated  to boiler operation.  Thus units  such



          as Big Bend 2, whose turbines are  less  efficient,



          are unduly penalized in  the correlation.

-------
                               D-9

         The other main weakness  of  the  correlation  is  the
         fact  that differences in fuel nitrogen  content are
         ignored.  In  this  study, the chemically "bound  nitro-
         gen ranged  from  0.75$ at Leland Olds  to 1.93$  at
         Harllee Branch.   Certainly, M W per firing  wall,
         which is proportional to bulk flame temperature,
         does  not reflect fuel nitrogen  conversion which
         has been shown to be essentially independent of
         temperature.  We would suggest  a correlation based
         on steam flow or heat input per firing  wall, with
         a correction  factor to "normalize" the  data to a
         common fuel nitrogen content  (say, 1.3$).


         3. On page  65,  the report indicates that closing
         the air registers to the fuel-rich burners  maxi-
         mized NOY  reductions because  the minimum allowable
                  J\.
          excess air was  reduced.  We feel that it is just as
          important  to  note that in addition, a lower $ of
          stoichiometric  air is introduced to the fuel rich
         burners when the air registers are pinched to 20-30$
          open because  the flow restriction upsets the balance
of air flow to each burner.  Therefore a boiler operating at
          a .9 stoichiometric  ratio with all registers at 50$
          open may actually reach a  .85 stoichiometric ratio
          when the registers are  closed to 20$ open.

-------
                               D-10





          4. In several instances  the report  states  that



          baseline NO  emissions level out at low loads
                     J\.


          because a larger percentage of the  total NOY is
                                                     J\*


          produced from the fuel nitrogen.  This is  certainly



          true, but no mention is made of the amount of ex-



          cess air, which may double at low loads.   Increased



          oxygen in the flame increases both  thermal NO,, for-
                                                       J\.


          mation and fuel nitrogen conversion in diffusion



          flames (in premixed flames, thermal NOX decreases



          with high excess air due to overall cooling of the



          flame).   In cases where fuel NOX is dominant at



          low loads,  we have observed total NOX emissions to



          increase as load decreases.





               In conclusion,  we are glad to see that this



final report does not mark the end of Esso's involvement



with EPA and NOX testing.   There certainly is much more to



learn by extended operation of utility boilers under low



NOX conditions.   Such a program as outlined in section 7 of



this report  would  greatly  benefit the utilities, the boiler



manufacturers,  and, most of all,  the environment.



                               A. H. Rawdon - Director of R & D



                               S.A. Johnson - Chemical Research



                                              Engineer



                               Riley Stoker Corporation

-------
                                   E-l
 To Convert From




Btu




Btu/pound




Cubic feet/day




Feet




Gallons/minute




Inches




Pounds




Pounds/Btu




Btu/Pound




Pounds/hour




Pounds/square inch




Tons




Tons/Day
      APPENDIX E




  CONVERSION FACTORS




ENGLISH TO METRIC UNITS







	    To	




Calories, kg




Calories, kg/kilogram




Cubic meters/day




Meters




Cubic meters/minute




Centimeters




Kilograms




Kilograms/calorie, kg




Kcal/Kg




Kilograms/hour




Kilograms/square centimeter




Metric tons




Metric tons/day
Multiply By




 0.25198




 0.55552




 0.028317




 0.30480




 0.0037854




 2.5400




 0.45359




 1.8001




 0.555




 0.45359




 0.070307




 0.90719




 0.90719

-------
                         	F-l	

                                TECHNICAL REPORT DATA
                          (Please read Instructions on the reverse before completing)
  REPORT NO.
    EPA-650/2-74-066
                           2.
                                   3. RECIPIENT'S ACCESSION-NO.
 4. TITLE AND SUBTITLE
 Field Testing: Application of Combustion Modifications
  to Control NOx Emissions from Utility Boilers
                                   5. REPORT DATE
                                    June 1974
                                   6. PERFORMING ORGANIZATION CODE
 7. AUTHOR(S)
                                                      8. PERFORMING ORGANIZATION REPORT NO.
 A.R.  Crawford, E.H. Manny, and W. Bartok
                                    GRU.1DJAF.74
9. PERFORMING ORG '\NIZATION NAME AND ADDRESS
 Exxon Research and Engineering Company
 Government Research Laboratory
 P.O.  Box 8, Linden, New Jersey 07036
                                   10. PROGRAM ELEMENT NO.
                                    1AB014; ROAP 21ADG-AL
                                   11. CONTRACT/GRANT NO.
                                    68-02-0227
 12. SPONSORING AGENCY NAME AND ADDRESS
 EPA, Office of Research and Development
 NERC-RTP, Control Systems Laboratory
 Research Triangle Park, NC 27711
                                   13. TYPE OF REPORT AND PERIOD COVERED

                                    Final	
                                   14. SPONSORING AGENCY CODE
 15. SUPPLEMENTARY NOTES
           The report describes field studies on utility boilers to develop NOx and
 other pollutant control technology by modifying combustion operating conditions.
 Tests were made on 12 pulverized-coal-fired boilers , including wall, tangentially,
 and turbo-furnace fired units representative of utility boiler manufacturers' current
 design practices. Six oil-fired boilers, converted from  coal-firing, were also tested
 with combustion modifications for NOx control.  Particulate emissions and acceler-
 ated furnace corrosion rates were also determined in some cases for coal-fired
 boilers.  The tests consisted of three phases: short-term runs to define the optimum
 low NOx conditions within the constraints imposed by boiler operability and safety;
 boiler operation for 2 days  (under low NOx conditions defined in the first phase) to
 check operability on a sustained basis; and operation of several boilers under base-
 line  and  low NOx conditions for about 300 hours (with air-cooled carbon steel cor-
 rosion coupons exposed near the furnace water walls) to obtain relative corrosion
 tendencies at accelerated rates. Analysis indicated that combustion modifications,
 chiefly low excess air firing coupled with staged burner patterns , can reduce NOx
 emissions from the tested coal-fired boilers by 25-60%, depending on the unit and
 its flexibility. NOx.emissions were, successfully correlated for normal and modified
 firing condmons with the percent stoicniometnc air supplied to the burners.	
 16. ABSTRACT
 7.
                             KEY WORDS AND DOCUMENT ANALYSIS
                 DESCRIPTORS
                                          b.lDENTIFIERS/OPEN ENDED TERMS
                                               c. COSATI Field/Gioup
 Air Pollution
 Combustion
 Nitrogen Oxides
 Boilers
 Emission
 Coal
 Fuel Oil	
Fouling
Corrosion
Burners
Slagging
Air Heaters
Hydrocarbons
Air Pollution Control
Stationary Sources
Combustion Modification
Utility Boilers
Excess Air
Staged Firing
Emission Factors
13B
21B
07B
13A, 13H

21D, 07C
 8. DISTRIBUTION STATEMENT

 Unlimited
                       19. SECURITY CLASS (This Report!
                       Unclassified	
                        21. NO. OF PAGES
                             209
                                          20. SECURITY CLASS (Thispage)
                                          Unclassified
                                                                   22. PRICE
EPA Form 2220-1 (9-73)

-------