WATER POLLUTION CONTROL RESEARCH SERIES
DAST-13
         Design of a Combined
        Sewer Fluidic Regulator
J.S. DEPARTMENT OF THE INTERIOR • FEDERAL WATER POLLUTION CONTROL ADMINISTRATION

-------
             Design of a  Combined

           Sewer Flu/die Regulator
      The Development of Basic Configurations
        and Design Criteria for Applications
          of Fluidics in Sewer Regulators
FEDERAL WATER POLLUTION CONTROL ADMINISTRATION
           DEPARTMENT OF THE INTERIOR
                        by

           Bowles Engineering Corporation
                 9347 Fraser Street
            Silver Spring, Maryland 20910
              Program No. 11024 DGZ
              Contract No.  14-12-486
                   October 1969

-------
               FWPCA Review Notice

This report has been reviewed by the Federal Water
Pollution Control Administration and approved for
publication.  Approval does not signify that the con-
tents necessarily reflect the views and policies  of
the Federal Water Pollution Control Administration.
                         ii

-------
                           ABSTRACT
      The objective of this program was to demonstrate feasibility, and
to develop a workable configuration for a combined sewer Fluidic regulator,
whose purpose is to minimize combined sewer discharge while protecting
interceptor sewers from overloading during storm flows.  A second objective
•was to develop design procedures and criteria for the general application
of this concept to municipal sewer diversion requirements, including pre-
liminary investigations  of construction methods, costs,  and  maintenance
requirements. A third objective was to establish a plan and  location for
an operational demonstration of the concept with a  cooperating municipality.

      All objectives were successfully met.  A generic Fluidic Regulator
configuration was evolved which diverts 0 to 75% of the combined sewer
flow away from the  interceptor as a function of water level sensed in the
interceptor sewer, or combined sewer, in either an analog or digital
operational mode.  Application design criteria were evolved  for a range
of small to medium  sized municipal sewers,  in terms of a few basic
parameters.  Projected  installation costs  are only slightly more than for
conventional diversion  structures; while the anticipated construction and
maintenance requirements are simple and  minimal.

      The City of Philadelphia was established as  the demonstration site,
and a demonstration unit should become operational in late 1970.  Recom-
mendations were made for experimental activity to  improve regulation
linearity; expand application  size limit, and to better definitize con-
struction methods and costs.

      This report is submitted in fulfillment of Contract 14-12-486,
between the Federal Water Pollution Control Administration and the
Bowles Engineering Corporation.
                                 iii

-------
CONTENTS
ction
1
2
3
4

5
6
7
8
9
10
L Title
CONCLUSIONS AND RECOMMENDATIONS 	
INTRODUCTION 	
APPLICATION OF FLUIDIC REGULATORS 	
EXPERIMENT CONSTRUCTION AND
MEASUREMENTS 	
DISCUSSION 	 	
DEMONSTRATION PLANNING AND LIAISON 	
ACKNOWLEDGEMENTS 	
REFERENCES AND PUBLICATIONS 	
GLOSSARY OF TERMS AND ABBREVIATIONS 	
APPENDICES 	 	
Page
1
3
19

39
44
90
97
99
100
102

-------
                           FIGURES
Figure
                                                           Page
   1     Final Sewer Regulator Geometry with
         Blunt Splitter Nozzle 2" x 4"	
         Fluidic Sewer Regulator Switching Action 100%
         Diversion to Interceptor Sewer No Aspiration ..
   3     Fluidic Sewer Regulator Switching Action Diversion
         Toward Interceptor Sewer Slight Aspiration	     8

   4     Fluidic Sewer Regulator Switching Action 50-50
         Diversion, Aspiration at Both Controls	     10

   5     Fluidic Sewer Regulator Switching Action Maximum
         Diversion to Combined Sewer No Aspiration	     10

   6     Typical Existing Diversion Structure	     11

   7     Schematic Arrangement - Fluidic Sewer Regulator ..     12

   8     Fluidic Automated Irrigation System	     15

   9     Fluidic  Irrigation Diverter Installed at Washington
         State University Experimental Farm	     15

   10     Flow vs Supply Head vs Orifice Coefficient for
                                                              20
11
12
13


1 C
10
1 C
Discharge Coefficient vs Supply Head for Fluidic
Fluidic Sewer Regulator Geometry Dimensions 	
Control Line Diameter vs Line Length vs Nozzle



Pni-nm;»r« ctroAt Rtruo.turfi . Washinaton. D. C 	
21
23

26
27
27
29
                                 vii

-------
                      FIGURES (Continued)


Figure                                                     Pa9e

  1 7     Potomac Street Structure Details
         Washington, D.  C .............................    30

  18     Railroad Avenue  Structure, Washington, D. C .....    31

  19     Railroad Avenue  Structure Details
         Washington, D.  C .............................    32

  20     Intercepting Sewer in Cobbs Creek Park Slot
         Regulator Installation, City of Philadelphia .......    33

  21     Potomac  Street Structure No. 43 a Fluidic
         Regulator Installation, Washington, D. C ........    34

  22     Anacostia Main  Interceptor Structure No.  7
         Fluidic Regulator Installation, Washington, D. C..    35

  23     Intercepting Sewer in Cobbs Creek Park Fluidic
         Regulator Installation, City of Philadelphia .......    36

  24     Fluidic Sewer Regulator Test Layout ..............    40

  25     Test Installation Showing Head Box ..............    41

  26     Test Installation Showing Sewers and Regulator
         Insert ........................................    41
  27     Sewer Regulator Test Insert .....................     43

  28     Fluidic Irrigation Diverter 1/2" x 1/2" Nozzle
         Used in Predictive Analysis Tests ...............     45

  29     Fluidic Irrigation Diverter 1/2" x 1/2" Nozzle
         Operating at 1 00% Diversion ....................     45

  30     Minimum Head vs Nozzle Height for 100% Diversion
         of Fluidic Irrigation Diverters ...................     47

  31     Bias Orifice Test Circuit  .......................     48
                                 viii

-------
                      FIGURES  (Continued)


Figure                                                    Page

  32     Sensor Control Orifice Area vs Diversion
         for Fluidic Sewer Regulators	    49

  33     Irrigation Diverter Exhibiting Analog Control	    50

  34     Irrigation Diverter in State of 100% Diversion	    50

  35     Changes in Setback Geometry	    52

  36     Changes in Splitter Geometry	    52

  37     Geometric Bias Test Configuration	    53

  38     Model Test Configuration Showing Combined and
         Interceptor Sewers and Element Insert	    55

  39     Model Test Configuration Showing Combined and
         Interceptor Sewers and Element Insert	    55

  40     Basic Irrigation Test Model with 2" x  1" Nozzle ...    56

  41     Large Control Pockets on Irrigation Geometry
         Nozzle 2" x 1"	    56

  42     Cutaway Sidewalls on Irrigation Geometry
         Nozzle 2" x 1"	    58

  43     Short Sidewalls with Cutaway Nozzle  2" x 1"	    58

  44     Rounded Sidewalls with Cutaway Nozzle 2" x 1"...    59

  45     Short Sidewalls with Splitter Upstream
         Nozzle 2" x 1"	    59

  46     Short Sidewalls Rounded Splitter Nozzle 2" x 1" ...    60

  47     Short Sidewalls Rounded Splitter Less  Downstream
         Setback Nozzle 2" x 1"  .	    60
                               ix

-------
                      FIGURES (Continued)


Figure                                                    Page

  48    Analog Sewer Regulator Geometry Nozzle 2" x 4" ..     61

  49    Analog Geometry with Larger Control Pockets and
        Upstream Splitter Nozzle 2" x 4"	     61

  50    Analog Geometry with Long Nozzle, Pointed
        Splitter Nozzle 4" x 4"	     62

  51    Final Analog Sewer Regulator Geometry
        Nozzle 2" x 4"	     62

  52    Final Geometry with Pointed Splitter
        Nozzle 2" x 4"	     63

  53    Maximum Diversion vs Supply Head for Fluidic
        Sewer Regulators	     65

  54    Interceptor Slot.Configurations	„.     66

  55    Minimum-Maximum Diversion From Interceptor
        vs Combined and Interceptor Weir Settings for
        Fluidic Sewer Regulators	     68

  56    Maximum Diversion vs Combined Weir Height	     69

  57    Float Valve  Mechanical Sensor	     70

  58    Float Valve  Test Installation	     70

  59    Float Valve  Sensor Test Setup .... „	     71

  60    Float Valve  Sensor Areas	     72

  61    Diversion vs Interceptor Water Level for Fluidic
        Sewer Regulator  2 "  x 4 " Nozzle	     73

  62    Diversion vs Sensor Area Change 2" x 4" Nozzle
        Supply Head = 13.0"	     75

-------
                      FIGURES (Continued)


Figure                                                     Pa9e

  63     Diversion vs Sensor Area Change 4" x 4" Nozzle
         Supply Head =13.0" ....................... o...     76

  64     Diversion vs Interceptor Level for Fluidic Sewer
         Regulators Aspect Ratio =0.5 Nozzle 2" x 4" .....     77

  65     Diversion vs Sensor Area for Fluidic Sewer
         Regulators Aspect Ratio = 0.5 Nozzle 2" x 4" .....     78

  66     No-Moving-Part Sensor Test Setup ...... „ ........     79

  67     No-Moving-Part Sensor Push-Pull Bottles .........     81

  68     No-Moving-Part Bottles Installation .............     81

  69     Diversion vs Control for  No-Moving-Parts
         Push-Pull Sensor Nozzle 2" x 4" ................     82

  70     Air Water Flow Ratio vs Diversion ...............     82

  71     Multiple Sensor Test Setup .....................     84

  72     Diversion vs Supply Head for Multiple Sensor
         Control of Fluidic Sewer  Regulator ...............    85

  73     Diversion vs Supply Head for Multiple Sensor
         Control of Fluidic Sewer Regulator ...............    86

  74     Shrouded Discharge Low Velocity Flow
         Interference ..................................    & 7

  75     Shrouded Discharge Low Velocity Longer Shroud
         No Interference ...............................    87
   76     Basic Irrigation Test Model 2" x 3" Nozzle  .......    88

   77     Simulated Debris , Fouling Test ..................    88

   78     Preliminary Demonstration Plan ..................    96
                                 xi

-------
                      FIGURES (Continued)
Figure
                                                         Page
 B-l     Relationship of Discharge to the Differential Head
         Across the Diverter.  Fluidic Irrigation Diverter
         8" x 8" Nozzle	   m

 B-2     Discharge Coefficient vs Head Fluidic Irrigation
         Diverter Test on 8" Diverter - Ft. Collins	   112

 B-3     Flow vs Normalized Inlet Head 1/2" x 1/2" Nozzle
         12.5% Setback Blocked Port on Non-Control Side
         of Regulator Orifice on Other Control	   113

 B-4     Flow vs Head for Fluidic Sewer Regulators	   114

 C-l     Percent Diversion as  a  Function of  Bias Orifices
         1/2" x 1/2" Irrigation Element Supply Head = 6 hn ..   117

 C-2     Percent Diversion as  a Function of  Bias Orifices
         1/2" x 1/2" Irrigation Element Supply Head = 15hn.   118

 C-3     Maximum Diversion vs Supply Head	   H9

 C-4     Maximum Diversion vs Combined Weir Height
         Element 710-1 Nozzle 2" x 4" Interceptor Exit
         Area= 12.2 in2	   120

 C-5     Minimum-Maximum Diversion vs Combined and
         Interceptor Weir Settings Element 829-1 Nozzle
         2" x 4" Supply Head  =  10.25"		   121

 C-6     Minimum-Maximum Diversion vs Combined and
         Interceptor Weir Settings Element 818-1 Nozzle
         4" x 4" Supply Head  = 13.0"	   122

 C-7    Minimum-Maximum Diversion vs Combined and
         Interceptor Weir Settings Element 818-1 Nozzle
         4" x 4" Supply Head  = 17.0"	   123

 C-8    Minimum-Maximum Diversion vs Combined and
         Interceptor Weir Settings Element 818-1 Nozzle
         4" x 4" Supply Head  = 17.0"	   124
                                xii

-------
                      FIGURES (Continued)
Figure                                                     Page

 C-9    Diversion vs Height in Interceptor Element 710-1
        Nozzle 2" 4" Sensor 2M Weirs Set for Maximum
        Diversion ....................................   126

 C-10   Diversion vs Sensor Area Element 710-1 Nozzle
        2" x 4" Sensor 2M Weirs Set for Maximum
        Diversion ....................................   127

 C-ll   Low Diversion, Low Interceptor Water Level
        Float Valve Control ............................   128

 C-12   High  Diversion, Loaded Interceptor Float Valve
        Control ......................................   128
 C-13   Area of Sensor Orifices vs Height of H£O Interceptor
        Sensor 2M ....................................    129

 C-14   Flow Ratio vs Diversion Optimum Sensor and
        Weir Settings .................................    130

 E-l    Air Flow Through Orifice. „ ......................    135

 E-2    Air Pressure Drop Nomograph ....................    137
                               Xlll

-------
                            SECTION 1

             CONCLUSIONS AND RECOMMENDATIONS
 Conclusions*

       1.  The concept of a Combined Sewer Fluidic Regulator was found
 feasible and practical, based on a  series of scale model tests in which
 the scale factor varied from about 1:6 to 1:20 of a "typical" municipal
 diversion sewer. Of the three basic fluidic arrangements tested, (geometric
 bias, fixed orifice bias, and variable orifice bias) only the variable orifice
 bias provided complete,  predictable analog flow diversion.  The fixed
 orifice bias provided good partial analog, or fully digital flow diversion,
 which may  be quite satisfactory for many system applications.  The geo-
 metric bias arrangement was  abandoned early in the test program.  While
 mechanically simplest,  it proved to be overly sensitive to dimensional
 tolerances, and provided a significantly poorer range of flow diversion
 performance.

       2.  A basic Fluidic element geometry was developed which reliably
 diverts  from 0 to greater than 75% of the combined flow from the interceptor
 to the receiving waters outlet as either a digital or proportional function
 of water level variation in either interceptor or combined sewer.  This
 characteristic has been demonstrated over a  considerable range of inlet
 heads.  At  low inlet heads (corresponding basically to dry weather flow),
 all the flow enters the interceptor.  The unit's performance remains rela-
 tively unaffected by variations in inlet height-width ratio that would be
 encountered in adapting to the normal range of municipal installations.

       3.  A design rationale has been evolved for establishing  the
 principal Fluidic Element geometric parameters to correspond to the
 normal range of municipal combined sewer regulator requirements.

       4.  A preliminary analysis has shown  that the installation of a
 Combined Sewer Fluidic Regulator is similar in nature and overal com-
 plexity  to a conventional leaping weir,  or side flow diversion structure.
 It is estimated that the use of a Fluidic regulator would not increase the
 cost of  a large diversion structure, and would add only about 20% to the
 cost of  a small diversion structure.  It is estimated that the modification
 of an existing structure for a Fluidic Regulator would cost 20 to 50% of the
 original installation cost,  depending on size and degree of rework required.
*Terminology related to Fluidic technology is described in the Glossary.

-------
      5.  A simulated fouling test has shown a very low susceptibility
to fouling by solid or soft sheet-like debris in the water flow. It is
concluded that fluidic sewer regulators will require  significantly less
maintenance and/or surveillance to assure proper operation in municipal
service.

Recommendations

      1.  It is recommended that a full scale pilot model of a Combined
Sewer Fluidic Regulator be constructed, tested and evaluated in a typical
municipal diversion point, or equivalent, based on the design criteria
developed in the subject program.  The unit should be operated on typical
combined sewer flows, incorporating both normal dry weather and storm
flows.  The installation should be adequately instrumented to provide
real time and  recorded readings of all pertinent levels, flows, and control/
sensor  pressures. The unit should be evaluated over a period of at least
one year to properly assess the combined effects of dry and wet weather
flows,  including seasonal variations in each.  This program should also
serve as a basis for establishing  the nature and frequency of maintenance
or other services to keep  this type of sewer regulator operable.

      2.  It  is recommended that additional larger scale model testing
be performed to improve the accuracy of the performance prediction
criteria, when applying these criteria to the design  of sewer regulator
structures with regulator inlet areas in excess of about 4 square  feet.

      3.  It  is recommended that additional design  and testing be
performed to  improve  the linearity and predictability of the flow diversion
vs interceptor water level change characteristic for  the no-moving-part
push-pull sensor. This will be highly desirable in those applications
where a network of sewer regulators is to be controlled from a central
municipal command center.

      4.  It is recommended that study and experimentation be performed
to evaluate the relative cost effectiveness of three suggested methods
of construction:  plastic interaction region insert; cast concrete inter-
action region insert using a plastic reusable mold; cast concrete insert
using a disposable mold.

-------
                          SECTION 2

                       INTRODUCTION


 The Combined Sewer Overflow Problem

      The general problem which has prompted this program is the pollution
 of natural water resources by overflows from combined sewers.  According
 to the American Public Works Association, roughly three-fourths of all
 combined sewerage system overflows in the United States have their
 sources in combined outfalls1.  For this reason, existing combined  sewers
 are regarded as one of the most troublesome  sources of pollution in  this
 country today.

      The problem is materially aggravated by the distribution of these
 combined sewerage systems. Serving more than one-fourth of the sewered
 populace of the country, combined sewers are especially prevalent in
 cities having populations in  excess of 100,000.  Such cities have gen-
 erally been long established and their streets are underlain by such a
 complex of sewage,  water,  transportation, electric, steam  and telephone
 lines that a separate sewer system is totally impractical.  Beyond this,
 of course, the time, the inconvenience and particularly the cost of con-
 version to a separate system, even in many communities where conversion
 could still be considered, also render this approach unacceptable so long
 as any other solution is available.

      For this reason, the Federal Water  Pollution Control Administration
 is currently investigating a number of alternate approaches  to the problem
 of reducing the substantial pollution problem of existing combined sewer
 installations.  Among the potential solutions  being examined is that of
 storing all overflows,  either in the existing system or else  in large
 lagoons or underground reservoirs, and providing the capability of pumping
 the stored waste water back into sewage  treatment plants.  By such means,
 the treatment plants can be kept operating near full capacity at all times
 with the combination of normal dry-weather (sanitary) flows and pump-
 back flows.  Study programs are either now in progress or have recently
 been completed under FWPCA sponsorship to evaluate this type of in-
 stallation for a number of cities.
^-''Report on Problems of Combined Sewer Facilities and Overflows, 1967,"
 prepared by APWA under Contract No.  14-12-65, sponsored by the FWPCA.

-------
      A necessary part of the storage concept is that of regulating the
flow of sewage into the treatment plant during heavy storms.  Regulation
is required to prevent overloading of the interceptor sewers and/or the
treatment plant, itself, during heavy storm flows. Regulation also
assures that 100% of the dry weather flow is diverted to the interceptor
sewers, thus minimizing the required capacity and running costs of any
pumpback facility and reducing the tendency for sanitary solids to be
deposited in the storage reservoirs or low-use portions of the system.

      Conventional  regulation devices presently used in combined sewers
for regulating flow to adjacent interceptors range from several types of
manually-, float- or flow-operated gate valves to orifices, siphons, and
a variety of weir configurations.  Such devices all suffer from a reliability
problem.   This problem is  caused by the environmental conditions which
prevail in sewers  and by the characteristics of the sewage, itself.  High
humidity  coupled with acidic gases forms  a corrosive atmosphere  which
attacks most materials not actually immersed in the liquid.  The flow,
itself, is both corrosive and charged with debris, including sticks,
leaves, newspapers,  sand,  stones and other solids.  The result is  that
the regulator devices tend to deteriorate rapidly, due to corrosion,  to
physical  damage, or to the fouling and jamming action of debris.

      The moving-part devices are especially susceptible to these types
of damage.  Although their performance can be excellent,  such performance
can be secured only through frequent, periodic and expensive preventive
maintenance.  Such no-moving part devices as weirs and orifices  are,
of course, less susceptible to damage.  They suffer, however, from the
fact that  they are  inherently very poor regulators even when operating
perfectly. There is, therefore, a definite need for a simple regulator
device which combines the superior reliability of no moving parts  with
the improved performance available from properly functioning conventional
valves and gates.

The  Regulator Problem

      The problem of providing regulators  that are accurate,  reliable,
and  easily maintained is unfortunately a problem that has  largely  eluded
solution thus far.  There are, of course,  passive regulator devices  that
are relatively dependable.  Such devices as weirs and orifices, for
example,  have no moving parts and thus represent two of the more reliable
methods for flow regulation.

      Such devices are also relatively poor in their performance as
regulators.  Orifices, for example, regulate only to the extent that flow
is proportional to the square root of the combined sewer head increase.
Weir flow is  proportional to the 3/2 power of  the fluid head over the

-------
crest of the weir, for a rectangular weir installation.  Other notch shapes
yield other relationships between weir head and flow (e.g. ,  a triangular
notch having  the apex of the triangle down allows flow proportional to
the 5/2 power of weir head). Actual regulation,  however, is usually in
terms of combined sewer head rather than interceptor sewer level for most
regulator configurations involving orifices or weirs.  Hence, even if the
orifices or weirs offered appropriate accuracy, they could still not regu-
late in terms  of the required control parameter which is the level of flow
in the interceptor sewer.

      Other regulatory devices are available which offer substantially
improved accuracy and, in some cases, capability of control in accordance
with interceptor rather than combined sewer level.  Fairly simple examples
of such devices include float-operated gate valves and tipping
gates used in small-size regulators. The former are gate valves actuated
by floats measuring the  flow level in the interceptor.  The latter consist
of gates having a pivot point below their center lines; excessive upstream
flow causes them to be closed, while low flow rates permit them to fall
completely open.  Both of these devices could be made to regulate very
well if the regulated fluid were clean and non-corrosive.

      Unfortunately, the atmosphere within the sewer is typically wet
and corrosive. The flow, itself, in addition to being corrosive is charged
with solids ranging from fecal matter to earth,  sticks, stones, leaves,
rags, paper,  and a whole variety of other objects.  These solids produce
jamming of gates and fouling of mechanisms, while corrosion results in
rapid deterioration of mechanical parts.  The result is that these other-
wise satisfactory simple regulators have proven short-lived  and unreliable
in service.

      Still other types of moving  parts regulators  have been  developed
for large-scale regulation.  For very large sewers, electrically- or
hydra ulically-opera ted sluice gates driven by interceptor level sensor
signals may be used. These large, complex and expensive installations
are capable of exceptional performance  as regulators.  Unfortunately,
they are also  subject to the identical operating life and maintenance
problems that plague the float-operated and tipping-gate  valves.  Fre-
quent inspections and maintenance are required to keep the large devices
operational.   Unfortunately, the jamming  or stalling of a  gate during a
severe storm is usually irreparable until the waters have  receded to a
point where the installation may be safely entered by men.  Hence,
although they do offer greater performance, this performance cannot be
obtained reliably without costly inspection and maintenance.

-------
The Use of Fluidics for Sewer Regulation

      In seeking a regulation device or technique that combines the
reliability of weirs, orifices and other no-moving-parts devices with
the regulatory capability of moving-part valves, fluidics certainly
appears promising.

      Concerning the reliability requirement, the majority of fluidic
devices have as one of their most obvious characteristics the elimin-
ation of moving mechanical parts.  In effect, the fluid through its own
internal flow dynamics performs those functions which normally require
moving parts.  As a result, most of the problems of moving parts in
fluid systems are eliminated.  Such problems as wear,  backlash and
slop, friction and binding, and the need for lubrication and seals, for
example, all disappear when moving parts are absent.  Replacing the
moving parts are contoured flow channels constructed of materials re-
quiring only structural integrity and chemical compatibility with the
fluid involved.   Hence, fluidic devices are  obvious candidates for
sewerage system use from the  standpoint of potential reliability.

      In addition to their simplicity, however, fluidic devices also
offer a  performance capability  either duplicating or closely approximating
that of conventional moving parts valves for regulation of systems where
fluid flow is the principal controlled output. This occurs because most
of the sensors, transducers, interface devices and activators are re-
placed  by simple flow channels through which the fluid itself supplies
control signals, feedbacks and power outputs in the form of such funda-
mental  parameters as  flow and pressure. In many applications, additional
simplification is possible because the energy which provides the control
signals is obtained directly from the main power source, thus eliminating
any need for auxiliary energy sources.  Inasmuch as sewage regulation
is an example of such an application, the second criterion for considering
fluidic  devices  as potential regulators is also obviously met.

      Basic operation of the Fluidic sewer regulator as shown in Figure 1
is as follows:  When the  interceptor control port of the Fluidic sewer
regulator is closed off, the jet stream is directed along the corresponding
sidewall shown in Figure 2. In this  condition the interceptor control
registers a partial vacuum indicating a tendency to aspirate air as a
result of the venturi effect.  In this state the combined  control port is
open, allowing  ample  air to be aspirated which helps keep the jet stream
attached to the  interceptor sidewall.  As the interceptor control is opened
slightly, air is  aspirated and the jet stream begins to pull away from  the
sidewall as shown in Figure 3. In this state some flow begins to be
diverted into the combined discharge.  As the interceptor control

-------
      INTERCEPTOR
         EXIT
COMBINED
 OUTFALL
                                                          COMBINED
                                                            SEWER
                                                          CONTROL
       INTERCEPTOR
          SEWER
         CONTROL
                                     VENTURI
                                      NOZZLE
Figure 1.   Final Sewer Regulator Geometry with Blunt Splitter
          Nozzle 2" x 4"

-------
Figure 2.  Fluidic Sewer Regulator Switching Action
          100% Diversion to Interceptor Sewer
          No Aspiration
Figure 3.  Fluidic Sewer Regulator Switching Action
          Diversion Toward Interceptor Sewer
          Slight Aspiration

-------
is opened farther, more air is aspirated and the jet stream gradually
swings away from the interceptor sidewall until it is in the center of
the diverter, when the control is fully open, giving 50-50 diversion,
see Figure 4.  In a like manner, if the combined control is gradually
closed the aspiration will be restricted and the jet stream will be drawn
by the resulting pressure differential until, when the control is fully
closed, almost all the flow will be directed out of the combined dis-
charge, see Figure 5.

      Fluidic devices can be considered to combine the best features
of both of the two types  of conventional flow  regulators.  They have
the no-moving parts reliability of orifices and weirs.  Yet they are  also
capable of performance and installation flexibility entirely comparable
to that of servo-controlled valves or gates.   Both first costs and mainte-
nance costs can be greatly reduced, in addition, while  overall operational
reliability can be greatly improved.

      Consider  the problem of flow regulation at an existing diversion
structure.  The  diversion structure may presently utilize as  simple  a
regulator device as the leaping  weir shown schematically in Figure 6.
Conversely, it may be equipped with a completely automatic sluice gate,
servo-opera ted, which limits flow diverted to the interceptor in accord-
ance with the remaining capacity of the  interceptor line.

      Figure 7 shows a possible arrangement for a fluidic flow regulator
which occupies the same diversion structure  volume. The concept  con-
 sists basically  of embedding  a fluidic flow regulator element into the
weir of a conventional dammed-weir installation.  One exit of the regu-
lator leads to the interceptor portion of the installation while the other
 exit leads to the receiving waters.  A small exit weir provided in the
 interceptor exit of the diverter is significantly lower than a similar weir
 in the combined sewer exit.   Hence, normal low-velocity dry-weather
flow passes through the near side of the regulator and into the interceptor
line.  Flow passages would be less  than full under these conditions  and
no flow would go over the  outfall weir.

      The fluidic regulator is designed for control by a  balance between
 pressures applied at control ports on either side of its intake nozzle.
 One of these ports, shown on the near side of the regulator in Figure 7,
 consists of a fixed area orifice through which air is aspirated into  the
 flowing  stream. The opposite port is shown  connected  to a level sensor
 located  in the interceptor  sewer.  Under conditions of low interceptor
 flow the  area through which  air is aspirated from the interceptor is larger
 than the  fixed area orifice.  Hence, pressure on the far side of the flow
 stream is greater than that on the near side and this AP maintains flow

-------
Figure 4.  Fluidic Sewer Regulator Switching Action
          50-50 Diversion, Aspiration at Both Controls
Figure 5.  Fluidic Sewer Regulator Switching Action
          Maximum Diversion to Combined Sewer
          No Aspiration
                       10

-------
                                                   COMBINED
                                                    SEWER
      INTERCEPTOR
         SEWER
Figure 6.  Typical Existing Diversion Structure
                      11

-------
                  Control Port
     Elevated Exit Weir
Combined
  Sewer
  Outfall
                                                                                   Combined Flow
                                                                                Weir
                                                                            Communication Lines

                                                                            Fixed Area Orifice
                                                                      Simple Level Sensor

                                                                      Air Slot
Interceptor Flow
                 Figure 7.  Schematic Arrangement - Fluidic Sewer Regulator

-------
into the interceptor.  As interceptor flow increases, however,  the aspiration
area at the level sensor is reduced.  This change in area produces a cor-
responding change in the AP, resulting in flow modulation to the combined
sewer outfall of the regulator as the level of liquid in the interceptor sewer
increases, see Figures  2 to 5.

      The foregoing description of a fluidic regulator is intended primarily
to illustrate the operating principles of a  system utilizing such devices.
Clearly, variations in geometry and size from that shown are possible.
Likewise, different forms and arrangements of sensors are also possible
including, for example, lead or anticipation sensors in the upstream com-
bined sewer, and in the upstream interceptor line.  One element of design
which has not been discussed directly heretofore is the question of analog
versus digital operation.  Both types of operation are  possible, of course,
and the question of type is therefore best answered by simultaneously
considering both the needs of the installation and the design parameters
yielding a given level of performance for each type of regulator.

      By nature, the properties of a fluidic regulator are a function of
the geometry of its internal flow passages.  The basic requirement for
construction material, therefore, is simply that its geometry should  be
unaffected by either the operating environment or the fluid passing through
it. Since this  requirement is basically identical to that for the sewer,
itself, it follows that the materials  and techniques normally used for
sewer construction should be equally applicable to fluidic sewer elements.
Hence, concrete,  brick and stone should be entirely adequate in most
installations.  The exception is in the narrow venturi  section of the
inlet nozzle where relatively high fluid velocities occur.  In a few in-
stallations where  sustained high velocity flow occurs, a local "armoring"
may be necessary using a tough, smooth,  non-corrosive material,  such
as corrosion resistant steel, high quality plastic, or fiberglass.

      In the construction of these elements dimensional tolerances can
be relaxed to as much as ± 5%  except in the immediate vicinity of  the
inlet nozzle and sidewalls where a ± 2% tolerance is necessary.  For
reference, the latter  is  roughly equivalent to a tolerance of ± 1/4 inch
for a  one-foot nozzle width. Construction  of small flow control elements
can probably be done in concrete on a prefabricated basis. Large elements
can either be poured directly on site or else built up of prefabricated
subassemblies.

Program Approach

      The technical approach for the subject sewer regulator program is
based on the work conducted by the Bowles Engineering Corporation  toward
the development of a proprietary Fluidic automatic agricultural irrigation

                                13

-------
system.  The irrigation system requirement is similar in many ways to
the sewer regulator system requirement described in the previous section.
Both handle relatively large water flows, operating  at quite low gravity
heads.  Both may handle water heavily charged with solid particles, and
on occasion, debris.  Both are faced with significant environmental
corrosion problems;  both require high reiliability with a minimum of
maintenance and monitoring.  It is highly desirable that both systems
operate without external or auxiliary energy sources, other than the
main water flow, and both systems should be economical both in terms
of initial and operational costs.

      A schematic arrangement for a Fluidic automatic irrigation system
is shown in Figure 8.  This system is currently the  subject of a U. S.
patent application.  It is under consideration by the Hawaiian Sugar
Planter's Association for the automated irrigation of sugar cane,  and a
similar system is  currently being demonstrated at the Washington State
University Experimental Farm at Othello, Washington, for general
automated farm irrigation as  shown in Figure 9.  This system will
automatically irrigate a number of growing areas to  the  desired water
depth whenever water is applied.

      The  system  consists of a number of large fluidic diverters connected
in series downslope.  Water reaching the first diverter is directly initially
to the adjacent growing area, then switched downslope to the next di-
verter. Associated  with each diverter is a water level sensor, which
senses a  predetermined water depth in a  typical furrow, and provides a
signal to  the diverter to switch.

      In operation,  each diverter acts as a digital logic flip-flop.  In
order to eliminate the need for positive pressure control flows, the
pressure in the diverter adjacent is reduced below atmospheric ambient
by narrowing the inlet nozzle in the manner of a venturi meter.  Ambient
air is thus aspirated into the control ports to provide control flow.  In
its  simplest form the diverter flow is thus controlled by capping off as-
pirated air flow on the side of the diverter when water flow is desired,
and  opening the opposite side.   In the case of the irrigation diverters,
this arrangement is modified such that switching occurs when one control
port aspirates air  continuously through a small orifice, while the opposite
port is either capped, or opened wide.  Control flow air is allowed  into
the diverter through  the level sensor,  and interconnecting line.  The
level sensor consists  simply of an inverted  cup, whose open end is  set
at the desired maximum water level in the furrow.  When the water level
rises to the cup, air cannot enter, hence the first diverter switches  its
flow to the next downslope diverter.  A saucer  is generally placed under
the cup so that the diverter will remain switched downslope if the water
in the furrow recedes before all the fields have been irrigated.
                                14

-------
                       Lateral
                       Distribution
                       Ditch
                                                    Furrows
 Diverters
    Crop Areas
         Figure 8.  Fluidic Automated Irrigation System
Figure 9.  Fluidic Irrigation Diverter Installed at
          Washington State University Experimental Farm

                               15

-------
Program Procedure

      The procedure followed on the subject program has been to utilize
the above described technology and practice as a starting point.  Of
specific use was the Fluidic element, sensor, and communication line
configuration data.

      The program was planned to include a number of phases:  a predictive
performance analysis; the construction of a test setup; the construction,
testing, and evaluation of a number of experimental Fluidic Regulator
models; the generation of an application design rationale for applying the
test results to practical municipal design requirements; a preliminary
configuration and cost analysis; and a planning and liaison effort for
evaluating a full scale pilot model under operational conditions.

      A major technical objective in the course of the program was the
modification of a number  of characteristics of the irrigation element con-
figuration.  These are described below.

      The principal  modification was the need for proportional flow
diversion as well as the  on-off, or digital type, diversion characteristic
of the irrigation  systems.

      A second modification concerned adding the capability to operate
with a considerable difference in elevation between the outlet to the
interceptor, and  the outlet to the receiving waters.  The interceptor
outlet must be lower in order that normal dry-weather, or sanitary flows,
be  allowed  to flow with minimum impedance to the interceptor,  and then
onto the treatment plant.  On the other hand,  the outlet to the receiving
waters  must be elevated  to prevent  the dry weather flow from entering
the receiving waters, except under  storm  flow conditions when the inter-
ceptor is running near or  at its capacity.

      A third modification involved  the redesign of the overflow structure
so that very heavy storm  flows can  flow over, or around the regulator
without causing  significant changes in its regulation  performance.

      Another possible modification, which is desirable for future sewer
systems, is the capability for remote control from a centrally located
command center.  Remote regulator  control is  currently the subject of
experiments in several large municipalities,  and in time will probably
be used in most large, and many smaller cities.  However, due to its
futuristic nature, this requirement was not investigated during the initial
phases  of the subject program covered by this report; nevertheless,  it
appears promising based  on Fluidic  irrigation  experience.
                                 16

-------
Program Implementation and History

      On February 4,  1969, the U. S. Department of Interior, through the
Federal Water Pollution Control Administration,  entered into a contract
with the Bowles Engineering Corporation to conduct an initial research
and development activity.  The purpose of this activity has been to establish
design and performance criteria for general application of fluidic devices
to a representative range of sewer sizes and locations as a potential means
for reducing or controlling  combined sewer overflows.

      The program was conducted under the personal supervision of Mr.
Peter A. Freeman, Principal Engineer and Manager of the Water Manage-
ment Group at Bowles Engineering Corporation.  A total of four tasks were
involved in addition to the preparation of reports.  These tasks and their
completion dates are  summarized below:

      Task I - Predictive Analysis.  The purpose of this task was the
analytical establishment of general design criteria for an interceptor
sewer junction flow control based on fluidic technology.   This task was
started on February 4, 1969, and completed  May 15, 1969.

      Task II - Design  and Fabrication of Scale Model Junction.  Task II
had the goal of preparing to substantiate the general design criteria de-
veloped in Task I by designing, fabricating, and assembling a scale
model junction suitable for test.   This task was started about February 15,
 1969, and was completed May 24, 1969.

       Task III - Testing.   The purpose of Task III was to perform  a complete
 series  of tests of the model constructed under the preceding task.  Specific
 objectives of the  tests  were as follows:

       o    Substantiate basic design criteria.

       o    Perform flow and blockage tests using both small (sand,  silt
            and pebbles) and large  (newspaper pulp, rags, confetti,  lint
            and tree  limbs) contaminants.

       o    Generate preliminary cost estimates for installations of
            various sizes.

       o    Test to determine the maximum  practical lengths of air
            aspirator lines.

       o    Study the effects of reduction of air aspirator line cross-
            sectional area due to clogging or foreign material buildup.

       o    Determine the preferred material(s) for air aspirator lines.

                                 17

-------
This task was started on May 5,  1969,  and completed September 9,
1969.

      Task IV - Liaison and Planning.  The purpose of Task IV was to
establish liaison with one or more municipalities desiring to work toward
the design and installation of an interceptor junction with a fluidic flow
control.  Once liaison was established, a Phase II plan covering the
design of a demonstration combined sewer flow regulator installation
was to be completed jointly by the cooperating municipality and EEC and
included in the Phase I final engineering report.  This task was started
on July 8,  1969,  and was completed September 3, 1969, with the agree-
ment by the City of Philadelphia  to request a FWPCA Demonstration Grant
to evaluate a Fluidic Sewer Regulator.

      This contract has been the first phase of a planned four-phase
program.  The overall program purpose is to develop, build, install and
demonstrate  a fluidic sewer regulator.  As cited above, the purpose of
the Phase I contract reported on herein has been to establish design and
performance  criteria on the application of fluidic devices to the problem
of reducing or controlling combined sewer overflows.

      Succeeding phases of the program cover respectively the design,
construction and evaluation of a test system at an actual sewer site of
the cooperating  municipality.  Phase II provides for detailed design of
the test  system  including device design by EEC and A&E services by the
municipality. Phase III covers the construction and installation of the
test system.  Phase IV provides  for demonstration and evaluation of the
test system over a twelve-month time period.

      As described later in Section 6, it is expected that Phase II through
IV will start  early in 1970, and will continue through 1971.
                                18

-------
                          SECTION 3

             APPLICATION OF FLUIDIC REGULATORS
      The intent of this section is to discuss the application of Fluidic
Regulators to practical municipal combined sewer requirements.  This
section will include  specific design criteria and procedures, suggested
installations in typical municipal combined sewers, rough cost esti-
mates,  and suggested  approaches to the maintenance and service of
Fluidic Regulators.

      It should be noted that the  information here presented must be
considered experimental and preliminary at this time.  It is expected
that refinements and improvements in the design and cost criteria and
procedures will occur in the course of forthcoming testing  to be con-
ducted  under a FWPCA Demonstration Grant.

Water Channel Sizing

      The principal parameter affecting the water channel  size is the
maximum desired flow into the diversion channel from  the  combined
sewer, before flow begins to bypass  (over or around) the diversion
structure. Also to be determined is the desired inlet head at which
this flow occurs.  The inlet head is established by the weir or dam
height  at the regulator inlet nozzle.  The inlet nozzle  area is computed,
using the nomograph shown in Figure 10. (Note that the discharge co-
efficient, CD, is a function of the relative magnitude  of the inlet head
as compared to the nozzle height.  This relationship is shown in Figure
 11.  For first approximation purposes,  a value of 1.0  is suggested.)

      When the nozzle area, AN, is determined, the values of nozzle
height and width must be chosen, so that the best overall diversion
 performance can be realized. A number of considerations  affect this
choice.

       1.    Based on the program test results, a greater range of flow
       diversion is obtained with higher aspect ratio nozzles; i.e. , hn*
       large compared with wn*.  Note that flow diversion represents
       that part of the flow which does not enter the interceptor.
*hn is the height of the regulator supply nozzle.
 wn is the width of the regulator supply nozzle.
                                 19

-------
  t:
  50

  40

  30  -


  20
|
>- 10
(0
Q
7.0 -


5.0



3.0
 :
 -  1.0


I   .7
    .5 -
    .3 -
    .1


    .07-


    .05-
                                                                           s  Orifice Coefficient
                                                                                CD =.90        |=_
                                                                                CD = i.oo
                                                                                cD-i.10
                                                                                CD=1.20




                                                                                ssaEgs^;:3F3H:n^a_ 3 p
                                                                                                     7.0

                                                   f-j	•-••;—!—*-— -;	

                         -
                                                                                                       I
                                                                                                       -
                                                                                                      _
                                                                                                         g
                                                                                                         --
                                                                                                         *"
                                                                                                         B
                                                                                                         U
                                                                                                          -
                                                                                                         BC

                                                                                                          -
                                                                                                       -
                                                                                                       ,
                                                                                                       sc
                                                                                                       '
                                                                                                       c
                                                                                                       o
                                                                                                       -
                                                                                                       .
                                                                                                       5C
                                                                                                          B
                                                                                                          _
                                                                                                          -
                                                                                                  _  1.0
                               Figure 10.  Flow vs Supply Head vs Orifice Coefficient
                                         for Fluidic Sewer Regulators
                                                  20

-------
    1.20
K
_ J
nlet '
jpaH hf i

1 h 	
\
ft
K/






Fluidic Regulator




                                                                                   Discharge Head
    0.85 '
                                        Nozzle Height
    0.80
+
              1.0     2.0    3.0    4.0    5.0    6.0    7.0    8.0    9.0    10.0

                   SUPPLY HEAD RATIO - INLET HEAD MINUS DISCHARGE HEAD \~ h(i
                                                                            hn
              Figure 11.  Discharge Coefficient vs Supply Head for Fluidic Regulators

-------
      2.    Flow diversion is also strongly affected by the ratio of
      inlet water head to hn.  For ratios less than about  2, the range
      of flow diversion drops off  sharply.

      3.    A limiting value of undiverted flow must be determined
      from the interceptor sewer flow handling  capabilities, in that
      the  interceptor must be able to accept this amount  of undiverted
      flow when the combined sewer is running full.  If the inter-
      ceptor cannot accept this amount of flow, then the regulator
      inlet nozzle area must be reduced, or the nozzle weir lowered.

      It can be seen that the achievement of the best diversion charac-
 teristics within the above indicated restraints may require several "trial"
 designs.  When wn is established, then the horizontal plane  geometry
 of the regulator can be established,  using wn-based parameters  shown
 in Figure 12.  Note that considerable flexibility is possible in the con-
 figuring of both flow passages from a point downstream of the splitter
 to the interceptor inlet orifice, or the outfall weir.  A good working
 value of the outfall weir height has been determined as (1.4)  hn.  A
 good working value of the interceptor orifice width has been determined
 as 1.4  wn, assuming  a vertical dimension of hn.

 Air Channel Sizing

      Two procedures for air channel sizing can be  used, depending
 on the mode of regulation desired.  Digital, or "on-off" action similar
 to that  used in irrigation systems, can be obtained  with a small fixed
 bias air orifice on the interceptor side; a larger fixed orifice will pro-
 duce a  hybrid type of  action in which a limited degree of proportional
 diversion  occurs in the vicinity of the maximum diversion range (toward
 the  outfall).  Below this range maximum flow into the interceptor occurs.
 Complete  analog action requires a variable bias orifice,  such as the
 push-pull  sensor arrangement described later.  Considerations for sizing
 air channels for both modes of operation are described below.

      1.    Digital Action.  The bias orifice (interceptor side) should
      have an opening equal to .0015 AJJ, where A^j is the nozzle area.
      The  sensor orifice area should be . 004 AJJ.

      The  communication lines should be sized so that they produce
less than 10% of the pressure drop across either the bias, or  control
orifices, when each is passing maximum airflow.  As a guide to sizing
these lines,  the static pressure at the bias port when the regulator is
switched to the interceptor side is -.3h, where h is the water head at
the inlet.  (This is the maximum airflow condition.) Also the static
                                22

-------
asw
                                                                  SIDEWALL
                                                               	 SETBACK
                                                                  CONTROL
                                                                  POCKET
                                     VENTURI NOZZLE
         Figure 12.  Fluidic Sewer Regulator Geometry Dimensions
                                   23

-------
pressure at the control port under the same conditions is about -. Ih
the water head at the inlet.  This also corresponds to a maximum steady
airflow condition.

      In a practical installation, the control orifice should be located
well above the interceptor sewer water line, so that sewage cannot be
drawn or "percolated" into it when the regulator is operating at high
head  conditions.

      2.    Analog Action.   For analog operation, the push-pull  control
      arrangement is recommended.  The dip tube sensor located in the
      interceptor sewer should have a maximum orifice area = . 02 AJJ.
      The  orifice should be shaped in the form of a vertical slot, or
      alternately, a series of holes.  The vertical distribution of the
      orifice area is a function of range of interceptor water level over
      which flow regulation is desired.  Experiment has shown that a
      linear variation of regulator diversion with interceptor water depth
      will require a tapered area distribution,  with the largest slot
      width (or hole diameters) at the bottom of the dip tube.

      In the experiments to date, a linear taper of the orifice slot has
been used. This has resulted  in a rather non-linear diversion vs water
depth calibration, however. The reason for this is attributed to the fact
that the  fluidic element's capability to aspirate airflow into a control
port drops off sharply as the main flow stream is diverted away from
that side of the element; thus, a relatively large decrease in area of
the control side sensor was necessary to produce a significant lowering
of pressure in that part, which would allow flow to start entering the
bias port.  It is expected that  a non-linear tapered slot, which widens
sharply near the bottom of water depth range,  can be formulated  to pro-
duce  a much improved degree of linearity.  Such a contour could be
formed by  the area between a vertical line and a parabola.  This can
be described by the formula:
      ws  =  a (1 -1
                    T   -^
                                   where ws =   sensor slot width
                                                  along contour
                                          a   =   slot width at the
                                                  lower water level
                                                  limit
                                          hs  =   slot height along
                                                  contour
                                          D   =   maximum depth of
                                                  slot
                                24

-------
by simple integration, the area of the slot can be shown to be = 1/3 Da.
Additional testing will be required to fully evaluate the above or other
improved linearity contours.

      A second dip tube sensor is required in the open side of the push-
pull controller.  Its orifice should be constructed with the same distri-
bution of aiea as a function of variation in liquid depth, except that the
depth will be determined by the maximum control pressure difference
expected, the density of the controller  liquid, and the relative cross
section areas  of the open and closed sides.   The most desirable choice
of the controller liquid is still open to experimentation.   It appears that
the most significant requirements for the liquid are good chemical
stability, relatively low vapor pressure, low toxicity, and low surface
tension and/or viscosity.  These requirements reflect the fact the liquid
must evaporate at a minimum rate; and when the regulator is called on
to operate, the ambient air can bubble through it with minimum restraint,
foaming, or chemical reaction.

       Sizing of the communication lines can be accomplished by the
relationship shown in Figure 13.   This graph shows the inside diameter
of the line as a function of line length and inlet nozzle area. In general,
pressure drops along the communication line of a  Fluidic regulator oper-
ating in the analog mode will cause errors in the desired degree of
diversion.  The maximum error will occur at  the maximum airflow con-
dition which has been shown to occur near the 50% diversion point.  In
formulating Figure 13, a maximum allowable error in diversion of 10%
has been assumed as a function of increased flow impedance from the
sensor orifice.  The curves show the trade off of line I.D. (I.D. =
inside diameter) vs length,  in order to remain within the  tolerable im-
pedance increase limit.  These relationships hold for variations in inlet
head (assuming a maximum value of discharge coefficient, CD) .

       It is recommended that  all  dip tube sensors be relatively large in
diameter, as compared to the communication lines, to minimize the
chance of "percolating"  sewage, or controller liquid into the communication
lines.  It is recommended that communication lines  and sensors be con-
structed from  plastic pipe, in view of the very low operating pressures,
need for corrosion resistance, and low cost. It appears  that several
types of plastic material would be equally satisfactory, including PVC,
ABS, PE, or possibly polypropylene. The sensor installations in the
interceptor (or combined) sewer should provide for deflectors to prevent
occlusion of the orifice  slot by soft debris such as rags or newspapers.
A preferred location would be against a  sidewall as shown in Figure 14.
If a sidewall installation is otherwise unsuitable, a midflow installation
could be made per Figure 15. In this arrangement, soft debris could be
caught by the sensor pipe,  but the side deflectors and the downstream
location of the orifice slot would prevent interference with the basic level
sensing function.

                                 25

-------
to
en
         4-
     w
     tc
     U
     a
      w
      O
      u

      O

      p  1
                     25
50
 75         100         125        150


LENGTH OF CONTROL LINE IN FEET
175
200
                              Figure 13.  Control Line Diameter vs Line Lengtn vs Nozzle Area

                                        for Fluidic Sewer Regulators

-------
                     DEFLECTOR
COMMUNICATION
      LINE
    SENSOR
     SLOT
    ORIFICE
 INTERCEPTOR
<^ FLOW
                                                   WALL LOCATION
                      Figure 14.  Sensor Installation
                                                MIDSTREAM LOCATION
                       Figure 15.  Sensor Installation
                                     27

-------
 Installation

       Description.  In order to gain insight into the task of adapting
 a Fluidic Regulator into a typical municipal diversion location, con-
 struction layout drawings were obtained for several existing diversion
 structures in the City of Washington, D. C., and Philadelphia,
 Pennsylvania.  These are shown in Figures 16 through 20.   These
 structures have been modified as shown in Figures 21, 22 and 23 to
 outline possible arrangements and locations for Fluidic regulators,
 including sensors, and control equipment.  In each case the sizing
 is only approximate, since the drawings  are too limited in detail for
 precise  scaling.  The upstream weir shown is higher than that for the
 existing  structure, since it is presumed that the Fluidic unit would be
 sized to  handle a considerably greater flow before bypass flow would
 go over  the regulator.  This would permit a much greater flow to enter
 the interceptor if the latter can accept it, thereby greatly reducing the
 sewage  flow  into the receiving waters even during significant storm
 flows.

       Construction.  The construction of the Fluidic regulators is not
 shown in detail; however, the layouts are based on the assumption
 that the Fluidic element interaction region would be  constructed of
 precast  concrete shells, sealed against a concrete slab. This type
 of construction minimizes the likelihood  of air leaking into the element
 interaction region.  An alternate method of element construction would
 be the insertion of a heavy molded plastic shell of the element inter-
 action region, secured around the edges  with concrete or other masonry
 structure.  Hard Polyethylene, or PVC, would be promising plastic
 materials.  These units could be fabricated by rotational casting.  A
 second alternate method would be the in-place casting of the element
 in concrete around a disposable core  contoured to the element's internal
 geometry.  For example, the  core could be made of a plastic foam that
 could be  easily burned away, steamed away, or dissolved away with
 solvents. A third alternative would be the on-site casting of the
 element  in concrete with reusable heavy  plastic molding forms.  It is
 anticipated that the construction approach will be studied in detail
 during the design task to be performed as part of the Demonstration
 Grant activity.

      Cost Estimates.  At the time of writing of this report a detailed
 cost estimate for a complete Fluidic Regulator Structure has  not been
 made, since such an estimate would require a detailed design for a
 specific  site, which will not  be available until the next phase of the
 program.  The subject has been discussed with the responsible planning
 and construction engineers in Washington, D. C.  and  Philadelphia to
obtain rough cost estimates of Diversion  Structures with Fluidic Regu-
lators.  The following responses were obtained.
                                 28

-------
                 .c_4=_/i_/y
               SCALE : /'=2O'
Figure 16.  Potomac Street Structure
           Washington, D. C.
                29

-------
                                   _jeii^
                  ''
                4'-0S -
                    4.17
                  ^15*5, Inv. ~6.82(0vtrf/

                   /53s
     6.29-
                                            -6.29
    !2aS/uice Gate
4.19
                                          - Dam
    I2'S-
(Overflow)
                                       -6.89
                                DETAIL
                                i'= 10'-o'
                                                         Too of Dam
                                                         El. 8.30
                                                               . =6.8
                 Figure 17.  Potomac Street Structure Details
                           Washington, D. C.
                                  30

-------
                  PLAN
                SCALE:l"-IOo'
Figure 18.  Railroad Avenue Structure
          Washington, D. C.
               31

-------
                                  70S
•Sluice Gate
                                       f  S/u/ce Gate
                                          '3.O3 lO'S
                                             -3.32 (Dam)
                              DETAIL
Figure 19.  Railroad Avenue Structure Details
          Washington, D. C.
                    32

-------
cm
co
                                     2'-0" PIPE
                                .	
                             \^\'.V..!;A'.;V :r.;-;.vT


                                                                                                   OVERFLOW
                                                                                          10" PIPE
                                                 TO INTERCEPTOR

                                                      SEWER
                                                        Figure 20.  Intercepting Sewer in Cobbs Creek Park

                                                                   Slot Regulator Installation

                                                                   City of Philadelphia

-------
                                           SHROUD
                                                                   CONTROL LINES
       (OVERFLOW)
                                                       FLUIDIC REGULATOR
             NO-MOVING-PARTS
                  SENSOR
             (OVERFLOW)

                   rmrm.
  •4'-0"S

FOULING COVER
Figure 21.  Potomac Street Structure No. 43a
          Fluidic Regulator Installation
          Washington, D. C.

-------
(OVERFLOW)
                                      FLUIDIC
                                     REGULATOR
 NO-MOVING-PARTS
      SENSOR
      INTERCEPTOR
          WEIR
CONTROL LINES
                                             REGULATOR
                                             OVERFLOW
                                             CHANNEL
                                                                DIP TUBE
                                                                  FOULING
                                                                  COVER
         Figure 22.  Anacostia Main Interceptor Structure No. 7
                   Fluidic Regulator Installation, Washington, D.C.
                                 35

-------
00
OJ
                                     2'-0" Dia.  PIPE
                                                  DAM

.'." '. '•'. •'•.'•
X-
• XJ
'. '. ','*"' '',



ll"
t
^
; ,';'','•",
>

,' "A
'* .'• •


1
k
•


^jjjj
~

, 4,' • •
. . ' <
•'.*: -'
;•>.;;
"•'•.*'
V


^T

^





• ' i '
***
-^^
^
^S
-|
>' ;


y
'j|&
|
• A'
\
•'• 4
I
*N
.'.'A

!
/
/
|;
'*
»'.
'A
V
1
„• J^-jT
i

•.-•«'
i

X
/•s
..''.'I'- ',".'.".*'
/
1
•'/•>:'••*.



HROUD
/^ OVERFLOW
'/
>




                                                                                          10" Dia. PIPE
                                         TO INTERCEPTOR SEWER
                                    FLUID 1C REGULATOR
                                                          Figure 23.  Intercepting Sewer in Cobbs Creek Park
                                                                     Fluidic Regulator Installation
                                                                     City of Philadelphia

-------
1.    It was estimated that the cost of a diversion structure using
a Fluidic Regulator would range from equivalent, to approximately
25% greater than for a conventional (weir and side pipe) diversion
structure, depending on the size,  and overall complexity of the
structure.  For a large structure, with such features as a wet well,
leaping v;oir,  elaborate manhole or other servicing access arrange-
ments, the incorporation of a Fluidic Regulator would add a
negligible fraction to the cost.  For smaller structures,  such as
the "slot" arrangement in use in Philadelphia, a modest increase
in cost would  be required to incorporate a Fluidic Regulator.  The
initial costs of Conventional Diversion Structure costs would
range from about $15,000 for the small, easily excavated instal-
lations, to over $50,000 for the larger, deeper, or more complex
installations.  Thus the minimum cost for a Fluidic Regulator
installation might approach $20,000 while the maximum cost
would not be appreciably different from current practice.

2.    The City of Washington, D. C.  provided a rough cost
estimate for the modification of the current conventional structure
shown in Figure 17 to that indicated in Figure 21.  The original
structure cost, at current prices,  is estimated between $20,000
and $25,000.  The cost of modification for a Fluidic Regulator
was estimated at $15,000.  In this case the modification was
rather extensive, since the original sewer bottom would have to
be lowered to  receive the Fluidic Regulator.   In contrast, for the
projected modification of Figure 19, the Fluidic element could
be mounted completely within the  existing combined sewer  walls,
necessitating  only a small hole for the diverted flow line.  This
modification could probably be accomplished for significantly
less than $3,000.

3.    The cost of Fluidic Regulator and auxiliaries is relatively
modest.  Based on cost projections for large plastic irrigation
elements,  a plastic insert of the element interaction region would
range in cost  between $50 and $150, depending on size. The
cost of in-place cast concrete regulator structures is dependent
on many factors such as element size, concrete costs,  labor
costs, etc. As an example,  an element with a nozzle opening
of 1' x 1.5' will contain about 12  cubic feet, assuming  a 3" shell
thickness. Assuming a concrete cost of $25/cubic yard, the shell
material cost  would be around $13.  The cost of construction labor
@ $4/hour would be around $20, and molding form rental would
probably be on the order of $50.  Thus the total cost of the in-
stalled regulator,  using either type of construction, less auxiliary
equipment, would be less  than $100.
                          37

-------
      4.    The sensor, auxiliary controls equipment, and communication
      lines would range in cost from $25 to $50 depending on size,  This
      equipment would be constructed of a high grade plastic material,
      such as ABS, or PVC.

      Service and Maintenance Procedures.  Service and maintenance
requirements for Fluidic Sewer Regulators should  be extremely straight-
forward.  Since there are no moving parts, there are no requirements for
typical mechanism maintenance procedures,  such as cleaning,  lubrication,
replacement of moving seals, adjustment for wear, corrosion removal,
etc.  The foreseeable situations requiring maintenance, or service,  are
described as follows:

       1.    Cleanout.  Removable cleanout hatches would be provided
       in each outlet at a point abreast of the element splitter.  These
      would facilitate the removal of very large pieces of debris, or
       occasional periodic flushing of accumulated solids  and sediments
       after long periods of only dry weather  flow, if necessary.  (Note,
       experience on irrigation elements has  shown that the increased
       flow velocity through the nozzle, even under moderate flows should
       minimize the sediment buildup in the element interaction region.
       For example, irrigation elements that have been completely
       "silted in" when  the water is turned off, completely clear within
       a few seconds  when the water  is again turned on.)

       2.    Auxiliary Equipment.  For those  installations  using the
       analog mode of operation,  the  fluid in the U-tube should be
       checked for level at several month intervals.  For analog or
       digital mode operation all communication lines  should be checked
       periodically to prevent air leakage through seals, or joints.

       It  may be desirable to flush, or blow out communication  lines
       occasionally.  This can be facilitated by installing fittings in
       easily accessible locations, and flushing with potable water,
       or compressed  air.
                                38

-------
                         SECTION 4

        EXPERIMENT CONSTRUCTION AND MEASUREMENTS
Test Setup

      The performance of the subject program required a test setup suitable
for both the development of a satisfactory Fluidic Regulator element geometry
and its evaluation under simulated system conditions.  Accordingly, a test
setup was designed to operate  on an existing steel water test tank in the
EEC  laboratory.  This unit is shown in Figure 24. It consists of a large
wooden head tank which flows  water into two closed conduits; one conduit
represents a combined sewer,  the other an interceptor sewer.  The latter
makes a 90° bend and runs across and under the combined sewer.  The
Fluidic element fits at the junction so that one of its outlets discharges
back into the combined sewer, while the  other outlet discharges into the
interceptor sewer.  Both sewers discharge flow into the tank, from where
it is returned to the head tank  through a large irrigation pump.  The head
tank is equipped with bypass disc valves to control water head, while the
discharge from each sewer is controlled with a Bowles  Engineering Cor-
poration proprietary flexible roller curtain gate.  Photographs of the
completed unit are shown in Figures  25 and 26.

      The test setup pump furnishes  a total flow of about 1700 gpm.  The
pump support structure has been designed to  support two additional pumps
of the same type, thus giving  the test setup the potential flow capacity
of about 5000 gpm.   With one  pump, each conduit can  flow about 1/2 full
at a flow velocity of about 1. 7 feet/sec.  If a scale factor of 10:1 were
assumed, a flow velocity of 17 feet/sec  would be simulated.  If all the
available flow passes through  one conduit, the simulated velocity can
be doubled to  34 feet/sec, which can adequately simulate a flood flow
condition.

Experimental Fluidic Element Construction

      The test setup is  arranged so that the experimental  Fluidic element
under test slides into place through the side of the  combined sewer in
the manner of a desk drawer for easy removal and adjustment between
tests.  Both combined and interceptor sewers are fitted with Plexiglas
sides in the vicinity of the element for visual observation of the element
performance.

      The test elements were  constructed of  a stack of 1/2" marine ply-
wood laminations,  a plywood  floor,  and  a Plexiglas top, through which
                                39

-------
HEAD ADJUSTMENT    0   (.i      (T\
    CONTROL
                                                                      WATER TANK (EXISTING)
                                                                      WATER BOX
                                                                      12 IN x 12 IN INTERCEPTOR DUCT
                                                                      12 IN x 12 IN REGULATED DUCT
                                                                      TEST ELEMENT BLOCK
                                                                      ADJUSTABLE GATE
                                                                      CIRCULATING FUMP
                       FLOW STRAIGHTENER
                       (AS REQUIRED)
                           Figure 24.  Fluidic Sewer Regulator Test Layout

-------
        Figure 25.  Test Installation Showing Head Box
Figure 26.  Test Installation Showing Sewers and Regulator Insert
                             41

-------
the aspiration control airflow was passed.  The plywood laminations
were cut out to accommodate the maximum width dimensions anticipated
during the test program.  A "basic" maximum nozzle width of 5" was
thus obtained.  Element depths from 1/2" to 4" were obtained by adding
or subtracting plywood laminations.  The basic element test insert is
shown in Figure 27.  In the course of testing, internal geometry was
changed by  bending strips of aluminum flashing to the desired contours
and anchoring these strips to the element floor and cover with strips of
caulking putty.

      The combined sewer discharge weir was constructed of an aluminum
sheet, which was pivoted at the sewer floor to adjust the weir height.
The weir was sealed along the sewer sides with putty. The  interceptor
discharge gate was designed initially to provide a narrow, full depth
passage to pass simulated dry weather flow without any head backup.
The gate height increased to full element depth along a diagonal.  The
gate was vertically adjusted to vary the exit area.

Measurements

      Water flow measurements were made  by timing the interval required
to fill a 18. 7 gallon bucket.  This provided a measurement accuracy
within 2%, except for timing intervals less than 10 seconds, where the
accuracies were on the order of 5%.

      Water heads and weir settings were measured directly using scales
against the  transparent Plexiglas sides of the test sections.

      Control  port pressures were measured using conventional water
manometers.

      Control  port airflows were established by measuring the pressure
differential  across various sized, precision sharp edged orifice plates.
An inclined  manometer was used for very small differential pressure
measurements.
                               42

-------
                    CONTROL LINE
 COMBINED SEWER
       SUPPLY
LOW
FLO
           HEAD SCALE
              \
                                                     OUTFALL WEIR
                                                             WEIR SCALE
                       ff      INTERCEPTOR SEWER
                                 EXIT ADJUSTMENT
                          PLEXIGLAS TOP     \
                          Z
                 TEST REGULATOR
                     INSERT
                                                        ADJUSTABLE CURTAIN
                                                              GATE
                                                     INTERCEPTOR SEWER
              TEST REGULATOR
                  INSERT
                                                       INTERCEPTOR EXIT

                                                        INTERCEPTOR EXIT
                                                             SCALE
          PLEXIGLAS VIEW PLATE

                Figure 27.  Fluidic Regulator Test Insert
                              43

-------
                           SECTION 5

                           DISCUSSION
 Predictive Analysis

       The purpose of the predictive analysis was to obtain design criteria
 from the established irrigation element configuration which would provide
 a theoretical basis for the design of larger size model sewer regulators.
 It was found  after an initial effort,  however, that a purely analytical
 approach would have been prohibitive  in time and cost, due to the general
 mathematic complexity in handling two-phase flow field phenomena.
 Consequently, it was decided that existing performance data available
 from the testing  of several large irrigation diverters,  plus additional data
 to be taken on a small diverter, could adequately provide the basis  for
 performance predictions of fluidic sewer regulator elements.

       The test setup shown in Figures 28 and 29  utilizes a 1/2" x 1/2"
 nozzle size irrigation diverter.  Test data was  taken to obtain mathe-
 matical relationships for:  Flow as a function of head, diversion as  a
 function of control orifice size, control pressure and flow as a function
 of diversion  and head, and geometrical modifications vs analog control
 range.  The results of the tests were graphically analyzed and compared
 to theoretical predictions as well as actual data  taken on large  scale
 models of the irrigation configuration.  See Appendix A for log of tests.

       Flow vs Head Analysis.  In an effort to obtain design data to
 predict the flow through water regulators  for a  range of supply heads
 and nozzle sizes, flow data over a wide range of supply heads were
 taken for a 1/2" x 1/2" nozzle diverter as part of the task 1 testing.
 Additional flow vs head data were obtained from  an 8" x 8"  nozzle di-
 verter from tests conducted by the Agricultural Research Service at the
 Engineering Research Center, Fort Collins, Colorado.  The data from
 these two size diverters were used with the orifice equation to determine
 the relationship of orifice discharge coefficient to  the supply head as
 shown in Figure 11.   For the purpose of this study  it was assumed that
 the orifice coefficient did not change  with aspect ratio*; however, for
 aspect ratios much less than or greater than 1  this variable must be
 considered.  See Appendix B for a discussion of the orifice equation,
 graphical data,  and calculations of orifice coefficient.  The orifice
           .      height of supply nozzle  _  nn
*Aspect Ratio =  width Qf supply nozzle   -  ^
                                 44

-------
Figure 28.  Fluidic Irrigation Diverter 1/2"  x 1/2"  Nozzle
           Used in Predictive Analysis Tests
Figure 29.  Fluidic Irrigation Diverter 1/2" x 1/2" Nozzle
           Operating at 100% Diversion
                          45

-------
equation was then used along with the values of orifice coefficient
obtained from the report of test results from the Fort Collins irrigation
diverter to produce a nomograph of supply head vs flow through diverters
as a function of the nozzle areas and orifice coefficients.  See Figure 10.
The head vs flow characteristic of the 1/2" x 1/2" irrigation diverter
tested was compared to the nomograph data and was found to closely
agree, even though the scale factor between the two diverters  compared
was over 250:1.  Also, head vs flow data were obtained in testing model
sewer regulators with 2" x 1", 2" x 4", and 4" x 4" nozzle sizes. A
comparison with the nomograph predicted flow values showed agreement
to within five (5) percent.

      Testing of the small size diverter used for the predictive analysis
also yielded a graph of minimum supply head vs nozzle height  for 100
percent diversion performance of the diverter.  Comparison of this data
with the 8" x 8" Fort Collins diverter and the various size model sewer
regulators  tested showed good agreement.  This graph is  shown in Figure
30 for diverters having square nozzles,  or aspect ratio 1. Although this
curve applies specifically to  the 100% diversion condition, it  indicates
the relative ability of small elements vs large elements to provide flow
diversion for various head/nozzle height ratios. Accordingly,  this
curve is useful in interpreting experimental test results taken on small
elements,  on the effect of nozzle aspect ratio on diversion performance.
This will be described later.

      Biasing Orifices.  In order to obtain scaling information  for control
orifice size the small 1/2" x  1/2"  nozzle irrigation diverter was  tested
with a fixed orifice of specific diameter on one control port and a range
of orifices on the opposite control as shown in Figure  31. The results
of the biasing orifice testing  are shown graphically in Figure 32.  See
Appendix C for actual data curves.  Results showed that the bias  orifice
for maximum diversion performance had to be 0.12  (10~2) AN/ where
AJJ =  nozzle area; and the control orifice had to vary from nearly closed
to ten (10) times the area or approximately three times the diameter of
the bias  orifice to provide maximum diversion control.  The validity of
this data for reliable scaling was confirmed by its agreement with the
required  control port sizes used on the 8"  x 8" nozzle diverter tested
by the Agricultural  Research Service at Fort Collins.  Even though bias
orifice tests were performed on an irrigation configuration designed
primarily for digital operation, an analog control region was observed
which provided diversion control between 30 and 70 percent.   See
Figure 32.  Bias orifice control of irrigation diverters is shown producing
proportional diversion in Figure 33 and total diversion in  Figure 34.
The bias  control data were useful in designing a dip tube sensor con-
figuration to be used in the scale model test program and investigating
analog control.

                                46

-------
o


PS
  o
  o
a,

P
CO
                                   7        8


h, NOZZLE HEIGHT,  IN INCHES (ASPECT RATIO = 1)
                                                                                              10
                          Figure 30.  Minimum Head vs Nozzle Height for 100% Diversion

                                     of Fluidic Irrigation Diverters

-------
                     TO
                  INTERCEPTOR
                    SEWER
   TO
COMBINED
DISCHARGE
ASPIRATED
AIR FLOW
     FIXED BIAS
      ORIFICE
                                             ASPIRATED
                                             AIR FLOW
              VARIABLE
              CONTROL
              ORIFICE
                                                          DIP TUBE SENSOR
                                                     PROVIDES VARIABLE CONTROL
                                                      FROM RISING INTERCEPTOR
                                                           WATER LEVEL
                   Figure 31. Bias Orifice Test Circuit
                                  48

-------
(O
     O
          1.2
          1.0 ••
IN*
c
•l-l
O
•pH
M-l
§
1
a
O
u
lu
0
10

-------
Figure 33.  Irrigation Diverter Exhibiting Analog Control
Figure 34.  Irrigation Diverter in State of 100% Diversion
                          50

-------
      As pointed out above, bias orifice tests showed that a region of
analog control existed in the performance of the digital irrigation diverter
tested.  In order to gain some insight into the results of changes on
geometry to analog performance two basic modifications were tried on
the 1/2" x 1/2" nozzle diverter. The normal 12.5% setback of the side-
walls was changed to zero and 21%,  and diversion performance data
taken, see Figure  35.  Decreasing  setback to zero reduced  the diversion
considerably, whereas increasing setback to 21% had little effect.  The
distance of the splitter downstream was changed by one nozzle width
with little effect in performance, see Figure 36.   Because of poor access
to the internal geometry of the small size regulator, modifications were
limited.  Since no improvement  in analog  performance was observed as
a result of these modifications, additional changes were  planned for the
larger size scale model tests.

      As a result of test data taken from the standard  1/2" x 1/2" nozzle
irrigation diverter and comparisons made with the 8" x 8" irrigation di-
verter, several significant and reliable scaling parameters were determined
as follows:

      1.     Flow through regulators vs  supply head for any  size regulator
      nozzles, Figure 10.

      2.     Orifice coefficient vs supply head for any size  regulator
      nozzles, Figure 11.

      3.     Supply head vs nozzle  height required for maximum diversion
      performance, Figure  30.

      4.     Diversion vs control orifice area for fixed bias  orifice areas,
      Figure 32.

The testing  carried out in this portion of the program also provided insight
into a test procedure and element design for the scale model testing.
The predictive analysis made from  the tests provided a good foundation
for the starting of larger size regulator tests, particularly in choosing
supply heads and control sizes.

Sewer Regulator Model Development

      Regulator configurations  similar to that shown in Figure 37 having
a geometrical bias were tested for  single  control analog operation.  In
such a configuration the water stream would normally attach to the left
sidewall and flow  into the  interceptor as long as the control sensor in
the interceptor was open to permit maximum aspiration.  When aspiration
was reduced by interceptor flow level on the dip tube sensor, the water
stream would be pulled away from the left sidewall in proportion to the

                                51

-------
         SETBACK
         12.5%W


         W
                               FILLER
        SETBACK = 0
         SETBACK 21%W

          W
        FILLER
IRRIGATION
GEOMETRY
MODIFIED
GEOMETRY
MODIFIED
GEOMETRY
       Figure 35. Changes in Setback Geometry
          IRRIGATION
          GEOMETRY
                                         W
           MODIFIED
           GEOMETRY
       Figure 36.  Changes in Splitter Geometry
                          52

-------
INTERCEPTOR
  OUTLET
COMBINED
DISCHARGE
             LARGE SETBACK
                                                SMALL SETBACK
                                                CONTROL TO
                                                INTERCEPTOR
                                                DIP TUBE SENSOR
        Figure 37.  Geometric Bias Test Configuration
                       53

-------
aspirated flow change until the jet was attached to the right sidewall
and all flow was directed to the combined discharge.  Tests of this
geometry showed that geometrically biased elements could be made to
perform as described above; however, the geometry was extremely
critical.  The maximum diversion performance was generally less than
60% into the combined discharge.  Also,  in the course of testing biased
configurations, it was not possible to duplicate any of the acceptable
designs.  AE a result of this critical geometry problem this  approach
was dropped as impractical and no further investigations were made.

Irrigation Configuration Modifications

      In an effort to develop an analog diverter controlled by air aspiration,
a 2" x 3" nozzle size irrigation configuration was made  to adopt to the
sewer simulation test setup shown in Figures 38 and 39.  The basic
irrigation geometry shown in Figure 40 was tested with bias orifice control
as described above.  In an attempt to obtain better analog performance,
tests were made with several splitter variations, including  pointed, round,
flat,  and  concave shapes;  and  several weir settings.  Results showed no
improvement in analog performance over the digital irrigation diverter.
The nozzle  size was then changed to 2"  x 1"  (aspect ratio = 2) to  provide
a greater range of flexible geometry variations.  Variations  were then
made in control pocket size, setback, cutaway of sidewall, sidewall
length, sidewall curvature, downstream  sidewall setback, and splitter
bluntness and downstream location.   See Log of Sewer Regulator Tests,
Appendix A, for a detailed account of these tests. -As a result of the
testing, a 2" x 1" element configuration and sensor were developed
having linear analog aspiration control over a 0 to 90 percent diversion
range.  The results of the control parameters tested  were as follows.

      The size of the control pockets were varied from 0.875W to  3W,
see Figures 40 and 41 (W = width of nozzles, see Figure 12). As  the
pocket size is  increased above W the diversion control is reduced until
at 3W there is  no aspiration control.

      The setback of the regulator sidewalls was varied from 1/2W to
zero, see Figure 35.  As the setback approached zero, control rapidly
deteriorated until at zero setback there was no control.  As  setback
increased above 1/4W total diversion decreased slightly and control
became more digital.

      The difference in linearity and control range of rounded vs pointed
splitters was not significant; however, splitter location  downstream of
the nozzle did cause considerable effect on analog performance and
linearity.  Moving the splitter  closer to the nozzle as  shown in Figure 36
                                54

-------
Figure 38.  Model Test Configuration Showing Combined and
           Interceptor Sewers and Element Insert
Figure 39.  Model Test Configuration Showing Combined and
           Interceptor Sewers and Element Insert
                         55

-------
Figure 40.  Basic Irrigation Test Model with 2" x 1" Nozzle
  Figure 41.  Large Control Pockets on Irrigation Geometry
              Nozzle 2" x 1"
                           56

-------
Increases the total diversion range and improves linearity.  If the splitter
is rounded as shown in Figure 46, performance is not degraded.  A very
blunt splitter as shown in Figure  37 does degrade performance.

      If the  sidewall is cut away at the control cavity as shown in Figure
42, the water stream cannot be diverted significantly in either a digital
or analog fashion, regardless of other variations in geometry.  If a  short
sidewall is left downstream of the controls and then cutback as  shown
in Figures 43 and 45 analog performance can be obtained with good  total
diversion characteristics.  As the length of the sidewall is made longer
than W,  operation becomes more  digital.  As the length of the sidewall
is made  shorter than W the diversion  range is shortened.  Rounded side-
walls as shown in Figure 44 did not improve performance.  The setback
downstream of  the sidewalls was also found to effect performance.  A
setback  of 1/8W produced better total diversion than did larger setbacks.
See Figures 46  and 47.

      During the tests of geometrical variations on analog diversion
performance several sensors were tested to obtain best analog control.
A mechanical float valve was found to be  best and was used for testing
the other parameters discussed above.  A discussion of sensor tests
and designs follows.

      A long neck nozzle was tried, see Figure 50;  however, this was
found to reduce the venturi effect of the nozzle and  consequently de-
graded diversion performance. Nozzle variations also showed that
performance was not affected by  minor changes in the nozzle centerline
relative  to the  element splitter.

      The best 2"  x 1" nozzle configuration as shown in Figure 47 was
scaled to form  2" x 4" and 4" x 4" nozzle size regulator elements to
test geometry at different aspect ratios.  Basic variations were made
in control pockets, see Figures 48 and  49,  and splitters, see Figures
51 and 52.  The regulator performance varied as a result of these changes
in the same manner as the 2" x 1" nozzle configuration.  It was there-
fore assumed that an acceptable  final geometry had been obtained.   See
Figure 12.

Performance Tests - Final Configuration

      After the final geometry was obtained as a result of the extensive
testing of numerous configurations as described above,  the final con-
figuration was  then tested in 2" x 1", 2"  x 4", and 4" x 4" nozzle
regulator elements.  The purpose of this testing was to obtain performance
design curves  which could be used to design a sewer regulator for any
particular installation when given the requirements  of the installation.
                                57

-------
Figure 42.  Cutaway Sidewalls on Irrigation Geometry
           Nozzle 2" x 1"
      Figure 43.  Short Sidewalls with Cutaway
                Nozzle 2" x 1"
                       58

-------
 Figure 44.  Rounded Sidewalls with Cutaway
            Nozzle 2" x 1"
Figure 45.  Short Sidewalls with Splitter Upstream
           Nozzle 2" x 1"
                     59

-------
  Figure 46. Short Sidewalls  Rounded Splitter
            Nozzle 2" x 1"
Figure 47.  Short Sidewalls Rounded Splitter Less
           Downstream Setback Nozzle 2" x 1"
                     60

-------
     Figure 48. Analog Sewer Regulator Geometry
                Nozzle 2" x  4"
Figure 49.  Analog Geometry with Larger Control Pockets
           and Upstream Splitter Nozzle 2" x 4"
                         61

-------
Figure 50.  Analog Geometry with Long Nozzle, Pointed Splitter
           Nozzle 4" x 4"
    Figure 51.  Final Analog Sewer Regulator Geometry
               Nozzle 2" x 4"
                            62

-------
Figure 52.  Final Geometry with Pointed Splitter
           Nozzle 2" x 4"
                  63

-------
      Diversion Performance vs Supply Head.  The difference aspect
ratio nozzles were tested at numerous supply heads from 6" to 18" and
the maximum and minimum flows were measured to obtain the diversion
range. All regulators tested were adjusted such that with the bias port
completely blocked as much flow as possible was directed to the inter-
ceptor.  This was accomplished by  adjusting the interceptor slot opening
and combined exit weir height.  Design curves derived from this data
are shown in Figure 53.  See Appendix C for actual data.  These curves
show  that regulators with nozzles of higher aspect ratios require less
head to obtain the same diversion.  It is believed that the use of these
curves will result in conservative estimates of maximum diversion per-
formance, particularly for large  sewers  with very low aspect ratio nozzles.
This belief stems from the fact that data for the 0.25 and  0.5 aspect
ratio curves were taken from tests on elements with 1 and 2 inch nozzle
heights respectively, whereas the 1.0 aspect ratio curve was taken
with a 4 inch nozzle element.   Figure 30 shows a significant increase
in head in terms of h,  to achieve 100% diversion for small values of h.
Note that  a relatively large change  in required head occurs between
h = 1" and h = 4".  This  would indicate that the a = 0.25, and a = 0.5
curves of  Figure 53 would have lain closer to  the a =  1.0  curve had the
tests  been made on elements with h = 4" for all aspect ratios.  Referring
again to Figure 30, the decrease in required head from 4" up is quite
small, hence the diversion performance predicted from Figure 53 for
nozzle aspect ratios = 1  should  be fairly accurate.  With the testing
of large, low aspect ratio nozzle regulators, it is  expected that the
accuracy of the lower aspect ratio curves of Figure 53 can be appreciably
improved.

      Total flow through the regulator was measured for all nozzle sizes
at all heads to obtain head flow data.  This was compared to the nomo-
graph obtained from the predictive analysis,  see Figure 10 and Appendix B.
Agreement was within ± 5 percent for all nozzle sizes.

      Weir Settings;  Interceptor Exit Design.  Several configurations of
the interceptor weir were investigated to obtain the most simple design
with the best performance, see Figure 54.  Design #1 was a conventional
weir with  a cut off corner that allowed low flow to pass without  restriction.
The discharge area in this design was distributed across the channel and
provided an opening subject to fouling.   Design #2 provided a larger
opening by shaping the exit area into a  full depth rectangular slot along
the splitter wall where the high velocity stream would have a low im-
pedance path to the interceptor.  This design  exhibited basic functional
response problems in switching the flow to the interceptor by forming an
air pocket, see Figure 54. Proper performance was obtained with this
weir design by moving the opening  next to the sidewall side of the element
as shown  by Design #3 in Figure 54.

                                64

-------
en
       O
       CM
       ffi
       CO
       w
       ffi
       u
       CO
       U
       I— I
       w
       ffi
       N
       N
       O
          6h "
       s
       I—I

       9 2h
       w
       ffi
       o.
       p
       co
a =  aspect ratio =
                    w
                     n
                             20
            30       40      50       60       70

             PERCENT DIVERSION FROM INTERCEPTOR
80
90
100
                     Figure 53.  Maximum Diversion vs Supply Head for Fluidic Sewer Regulators

-------
                        AIR
                      POCKET
ADJUSTMENT
                            ADJUSTMENT
   WEIR
                                      SPLITTER
                        WEIR
ADJUSTMENT
                                                                   ^
                                                             "\>J" IV*^
                                                                  SPLITTER
                               #2
      WEIR

     #3
               Figure 54.  Interceptor Slot Configurations
                               66

-------
      In order to obtain design data concerning the proper interceptor
exit area settings,  the combined weir was  set at various fixed levels,
and maximum-minimum diversion data were taken for a complete range
of interceptor exit area settings and inlet heads.  These data are shown
in Figures 55 and 56 in dimensionless  parameters based on nozzle size
and area. These characteristics proved independent of supply heads.
Using Figure 56 we see that the optimum height of the combined weir
is 1.4 hn (hn = nozzle height).  Using Figure 55  we see that the optimum
area of the interceptor discharge is 1.2 AN (AN = nozzle area).  See
Appendix C for actual data curves  used to  obtain these design curves.)

      Sensor Characteristics.  The predictive analysis yielded bias
orifice criteria as discussed above.  These data were found to hold for
using single dip tube sensors and a bias control orifice to effect digital
type control; however,  it was found that the  analog operation of the
regulator could best be obtained by a sensor which would operate inde-
pendently on each control and thus obtain  maximum linearity. This type
of control also required a sensor with very different area relationships
than the bias orifice type.  The development of the analog area ratios
and sensor schemes are presented in the following detailed discussion.

      In order to determine the sensor area relationship required for
linear analog control as described above,  a  float valve was  placed in
the interceptor line as  shown in Figures 57 and 58 to provide control.
The schematic of the float valve test setup,  Figure 59,  shows how
regulator control was effected by  interceptor water level.  When the
water level is at the desired minimum point, float valve area #2 is
closed by the rubber flapper and all the flow through the regulator is
directed to  the interceptor.  When the interceptor is  filled to the desired
maximum level, area #1 is closed and all  flow is diverted away from
the interceptor to the combined discharge.

       Three  sensor area configurations tested in this  setup are  shown
in Figure 60 and performance data from these sensors are shown in
Figure 61.  Sensor 1  consisted of small areas on the order of the  bias
orifice areas recommended by the predictive analysis.  Performance
with  this size area was purely digital; that is,  the interceptor water
level had to raise  to its maximum height to close off the sensor area
#1 before any change  in diversion occurred.  At this point complete
 switching of the stream occurred  with no analog control.  Sensor #2
 incorporated areas five (5) times  as large as the areas in sensor #1.
 Performance with sensor #2 was still  digital; however,  a range of analog
 control was  observed, as shown  in Figure 61.  As a result of numerous
 tests and observations with sensor #2, it was determined that maximum
 sensor area is needed when the areas are equal and  the regulator is
                                 67

-------
CD
OO
      X
      w
Q
0)
O

0)
.I-J
c
      (0
      0)
        0
        'N
        N
        O
        (0
        0
           1.6
           1.2 -'
0.8 "
                                                                                      Combined Weir Height
                                                                                         Nozzle Height
     0.4 --
                                                                         -4-
                      10
20      30       40      50      60       70

         PERCENT DIVERSION FROM INTERCEPTOR
                                                                           80
                                                                               90
100
                       Figure 55.  Minimum-Maximum Diversion From Interceptor vs Combined and
                                  Interceptor Weir Settings for Fluidic Sewer Regulators

-------
01
ID
           2.4 -
           2.0 -
       
N
O
1.2 -
                                  3. Oh
                        Area of Interceptor Exit
                            Area of Nozzle
                                      = 1.5
                                                              4.Oh
                                                                   n
                                                                    5.0hn 6.Oh
                                                                                       n
                                                                                             Supply Head
                       10
                      20
                                 30      40       50      60       70

                                  PERCENT DIVERSION FROM INTERCEPTOR
                                                                      80
90
—I—•
 100
                                Figure 56.  Maximum Diversion vs Combined Weir Height

-------
Figure 57.  Float Valve Mechanical Sensor
 Figure 58.  Float Valve Test Installation
                   70

-------
GATE
                       fO        TO
                    COMBINED  INTERCEPTOR
                                   INTERCEPTOR
                 Figure 59.  Float Valve Sensor Test Setup
                                      71

-------
                       L
                                      AREA =  0.012 in?
                                              ~Z-~ RUBBER FLAP
                                            ,

                                          /    TOTAL AREA = 0. 033 in2
                  SENSOR 1
                                        0.05 in2
\
|^»	.55 	«J
                                                  RUBBER FLAP
/   TOTAL AREA =0.16
                  SENSOR 2
                                           AREA = 0.16 in2
\
                                                  RUBBER FLAP
                                          V
                  SENSOR 2M




           Figure 60.  Float Valve Sensor Areas




                          72

-------
00
        100
     w
     j
     K
     O
     H
     Qu
     U
     U
PH
O
w
O
     O
     H
     W
     U
     w
       1
     g   80--
                              SENSOR 1,  A  =  0.033  in2
                                     30       40       50       60       70

                                       PERCENT DIVERSION FROM INTERCEPTOR
                                                                          80
90      100
                     Figure 61.  Diversion vs Interceptor Water Level for Fluidic Sewer Regulator
                                2" x 4" Nozzle

-------
dividing the flow evenly between the interceptor and combined sewers.
By gradually opening up the areas at the 50-50 operating diversion point
the optimum area designated as  sewer #2M was established and per-
formance data recorded, see Figures 60 and 61.

      Percent diversion vs change in sensor area was then taken for the
2" x 4" and 4" x 4" nozzle regulators, see Figures 62 and 63. Area
change was recorded as a ratio of sensor area change to regulator nozzle
area, as referenced from the condition where the interceptor control area
is fully closed and all flow is diverted to the interceptor.  The ratio
corresponding to maximum diversion is then twice the area of the sensor
opening used for each  control.   Test results from both 2" x 4" and  4" x 4"
nozzle regulators yielded the same ratio of 40  (10~3) as the proper ratio
for linear analog control.

      It follows, then, that the  optimum control orifice area for analog
operation is 20  (10~3)  AN, (AN = nozzle  area).  Digital operation is
obtained by using orifice areas equal to  one quarter of the analog area.
Tests at numerous supply heads showed  diversion performance vs area
change or interceptor level change was linear, over a complete range
of heads, as shown in Figures 64 and 65.  (See Appendix C for actual
data curves.)

No-Moving-Part Sensors

      Principles of Operation.  In the course of this program a new design
for a no-moving-part sensor was investigated which could provide linear
analog control without the need  for a mechanical float valve.  A schematic
of the  arrangement is shown in Figure 66.  The system uses a control dip
tube in the interceptor sewer which is connected to the combined control
of the  regulator and a  sealed bottle. A second dip tube is connected to
the interceptor control and placed in a second  bottle which is vented and
has a common fluid connection at its base with the sealed bottle.  The
two bottles and connection operate in the manner of a U-tube manometer.
As the interceptor dip  tube sensor is covered by rising water level, as-
piration through the combined control is  reduced causing  an increase in
vacuum.  This increase in vacuum acts on the  sealed bottle to raise its
fluid level.  Since the two bottles have  a common connection and the
dip tube bottle is vented, a  change in fluid level between the two bottles
results.  The change in fluid level of the bottles produces a change in
the exposed area of the vented bottle dip tube, which in turn  controls
aspiration to the interceptor control. Therefore, an interceptor level
increase will increase the aspiration to  the interceptor control by in-
creasing the opening of the dip tube slot through the bottle and decrease
the aspiration to the combined control directly. The jet stream will be
switched in a push-pull manner.


                                 74

-------
Cn
       ro
        I
        O
            40 --
          
-------
          20
30      40      50     60       70



 PERCENT DIVERSION FROM INTERCEPTOR
80
90
100
Figure 63. Diversion vs Sensor Area Change 4" x 4" Nozzle Supply Head = 13.0"

-------
-vl
co
w
K
U
    K
    o
    e
    w
    U
    ex
       Limit
         10.0
      8.0"
           6.0--
W


I
PLH
O
E-t
sc
o
    g  Limit
           4.0 •-
           2.0
                    2h
                      n
                      10
H	,	,	,	1	1	
 20       30      40      50       60       70

          PERCENT DIVERSION FROM INTERCEPTOR
                                                                             80
90
100
                         Figure 64.  Diversion vs Interceptor Level for Fluidic Sewer Regulators
                                    Aspect Ratio =0.5 Nozzle 2" x 4"

-------
     oo
     I
     o
                                                                                             n
         40
00
     to
     0)
     o
     w
     G
     O
     CO
     c
     (0
     .c
     u
        CD

       13
        g30
          20  ••
0)
75
N
S,  10
       (D
                             20
                               30       40      50      60       70


                                 PERCENT DIVERSION FROM INTERCEPTOR
80
90
100
                           Figure 65.  Diversion vs Sensor Area for Fluidic Sewer Regulators

                                      Aspect Ratio = 0.5 Nozzle 2" x 4"

-------
                        INTERCEPTOR
                         CONTROL
    COMBINED
     CONTROL
                                              TO
                                          INTERCEPTOR
                                            SEWER
                                                         TO
                                                      COMBINED
                                                       SEWER
                                                      DISCHARGE
                                   VENTED  BOTTLE
                                     DIP TUBE
1
       INTERCEPTOR
        DIP TUBE
        SENSOR
              COMMON CONNECTION
INTERCEPTOR
       Figure 66.  No-Moving-Part Sensor Test Setup
                            79

-------
      Push-Pull Sensor Tests.  Several tests were made to investigate
the no-moving-part bottle sensor with different dip tubes and bottles,
see Figures 67 and 68.  It was found that equal size bottles with equally
distributed dip tube areas did not provide enough gain and control was
very non-linear.  A sealed bottle of twice the area  of the vented bottle
was tried to increase sensor gain; however, this was only partially
successful.  Control with the push-pull bottles as  a function of inter-
ceptor water level did not affect diversion until the dip tube sensor was
over 50% closed; however, after diversion control started a reasonably
linear control  range was observed,  see Figure  69.  In  order to expand
the control range the interceptor dip tube was shaped similar to Sensor
#1 shown in Figure 60; however, no noticeable improvement in per-
formance was  observed.

      After testing of model sewer regulators was completed and aspirated
air flow data analyzed it was found,  as shown in Figure 70, that the
aspirated air flow is high at the midpoint  in diversion  (see Appendix C
for actual data curve) and drops sharply as diversion approaches its
maximum value.  Thus, only a low  aspiration capability is available
to produce the initial change in the fluid levels of  the push-pull sensor
bottle to  obtain linear analog control.  From a  controls system stand-
point, this characteristic represents a region of very low gain.  There-
fore, to  provide linearity,  this low gain region must be compensated by
a high gain in some other part of the system.   The  two-bottle, or U-tube
concept  offers several approaches to provide such  a localized,  high
gain characteristic.

       1.    The dip tube orifices can be shaped so that a small change
       in liquid level effects a large change in total orifice area.  This
      requires a non-linear tapered slot,  which widens abruptly near
      the bottom of its range.

      2.    The relative bottle diameters  can be shaped.  The increase
       in vacuum on the combined port as the interceptor sensor is  covered
       causes  a  corresponding differential change in the liquid level
      between the U-tube branches.  Since only a  fixed amount of liquid
       is involved, the relative fluid level rise in the closed branch, as
       compared to the level drop in the vented branch, is proportional
       to the inverse ratio of the branch cross section areas.  Thus if
       the vented branch is necked  down opposite the bottom end of the
      dip tube slot, a relatively large change is liquid level will result
       from a small increase in vacuum.

       It  was not possible to fully explore the above possibilities within
the scope of this  initial program phase; however, it appears certain that
good diversion linearity can be achieved through one or both, so that proper
sewer regulation without moving mechanical parts is achieved.


                                80

-------
Figure 67.  No-Moving-Part Sensor Push-Pull Bottles
   Figure 68.  No-Moving-Part Bottles Installation
                         81

-------
o
O>

(0
K
O
U
 en



CO

 C
•rH

 

O
                     20         40          60         80


                    PERCENT DIVERSION FROM INTERCEPTOR
                                                                   100
              Figure 70. Air Water Flow Ratio vs Diversion
                              82

-------
Multiple Sensors

      In an effort to determine whether two fluid levels could be monitored
with dip tube sensors and added to provide control from a single control
port, the sensor combination shown in Figure 71 was tested.  In this setup
one dip tube sensor was put upstream of the  regulator nozzle in the com-
bined sewer and a second sensor was placed in the interceptor sewer.
Both sensors were then connected to the combined control to provide
diversion control.  With the knowledge of the optimum area for analog
control as discussed above the total area of  both sensors was selected
having an area ratio of about 3:1.  The diversion performance of the
multiple sensors was measured as a function of supply head.  Curve  1
of Figure 72 shows the change in diversion vs head over the full range
of the combined sensor with the interceptor level constant. Curve 2  of
Figure 72 shows the change in diversion resulting from change in head
without the combined sewer sensor connected to the control.  The sig-
nificant difference between these curves shows that both sensors  are
contributing to the diversion.  Figure 73 consists of a similar pair of
curves taken at a different interceptor water  level.  Results of these
tests showed that the  knowledge of control areas obtained from regulator
tests could be applied to multiple dip  tubes  as well as single ones.

Flow-Over Discharge

      Diversion performance of the sewer regulator was tested for the
simulated condition of large upstream  heads, caused by storm  flows,
causing flow over the  regulator and thus over the discharge. When the
head of water flowing  over the discharge exceeds about fifteen (15)
percent of the upstream head the fluidic regulator flow is biased to the
interceptor and diversion performance  is seriously reduced.  In an effort
to avoid this problem, shrouded discharge tests were made to isolate
the two  flows and provide an air-water mixing region, see Figures 74
and  75.  For large  flows over the regulator a short shroud will  act like
a leaping weir; however, at low  flows a short shroud produced interference,
see  Figure 74, and effected diversion  noticeably.  A longer shroud as
shown in Figure 75 solved this problem.

       From these tests it is concluded that for installations where the
outfall communicates to tidal waters or back water conditions exist to
produce a head at the outfall the fluidic regulator performance will show
significant degradation as the discharge head builds to about fifteen (15)
percent of the supply  head regardless  of shrouding.
                                 83

-------
  COMBINED SEWER
X    DIP TUBE
      1
COMBINED
  SEWER
      % Closed
                             "OPEN"
                          INTERCEPTOR
                           CONTROL
                           COMBINED
                           CONTROL
                                       TO
                                  INTERCEPTOR
                                     SEWER


                                     TO
                                  COMBINED
                                    SEWER
                                  DISCHARGE
                            INTERCEPTOR
                             DIP TUBE
                            INTERCEPTOR SEWER
                       % Closed
        Figure 71.  Multiple Sensor Test Setup
                           84

-------
            100
CD
cn
                                         CURVE 1
                        COMBINED & INTERCEPTOR
                         SENSORS w/ INTERCEPTOR
                        SENSOR SET @ 83% CLOSED
                                                         CURVE 2
                                             INTERCEPTOR SENSOR
                                           ONLY,SET @ 85% CLOSED
                                                                                 70
                                                                                            9.0
                               PERCENT DIVERSION FROM INTERCEPTOR
                      Figure 72.  Diversion vs Supply Head for Multiple Sensor Control
                                 of Fluidic Sewer Regulator

-------
oo
01
                          CURVE 1
  COMBINED & INTERCEPTOR SENSORS
w/ INTERCEPTOR SENSOR 100% CLOSED
                                                                        CURVE 2
                                                             INTERCEPTOR SENSOR
                                                             ONLY, 100% CLOSED
                                                                                        ••12.0
                                                                                        -• 10.0
                                                                                           9.0
                                          60        65          70          75

                                      PERCENT DIVERSION FROM INTERCEPTOR
                                                                                                 O
                                                                                                 CM
                                                                                                 CO
                                                                                                 B
                                                                                        -•ii.o   3
                        Figure 73.  Diversion vs Supply Head for Multiple Sensor Control
                                  of Fluidic Sewer Regulator

-------
Figure 74.  Shrouded Discharge Low Velocity Flow Interference
    Figure 75.  Shrouded Discharge Low Velocity Longer Shroud
               No Interference
                              87

-------
Fouling Analysis

      In order to determine a Fluidic regulator's susceptibility to fouling,
tests were conducted with small branches of various sizes and shapes.
Maximum dimensions of branches ranged from 1.1 to 4 times the nozzle
height (hn), as shown in Figure 77.  The channel upstream of the nozzle
was 6 hn  square so branches could approach in any orientation.  The
regulator  used for testing is shown in Figure 76.   Ten runs were  made
with each of eight branches giving a total of 80 runs. Six cases of
lodged branches occurred, three on the converging section of the nozzle
and three on the splitter. The splitter in this case was relatively sharp
making it more susceptible to fouling by the forked sticks than other
regulator  splitter geometries having the same functional characteristics;
see Appendix D for fouling data.  In addition to tests with branches,
tests were run with pieces of paper to give some insight into the fouling
caused by large soft objects such as newspapers.  No problems  were
experienced except with a very large, 5 hn x 8 hn piece which caught
2 of 6 times on the pointed splitter.  Later  tests  showed that regulators
with blunted splitters  could be designed to perform as well as pointed
splitter types, therefore actual hardware utilizing blunted splitter designs
will be less subject to fouling.

      Fouling tests showed that the Fluidic sewer regulator without an
upstream trap of any sort was relatively free of fouling.  On the occasions
when fouling occurred, the fouling objects  had a linear dimension of four
(4) or more times the nozzle height.  A sharp splitter is more susceptible
to fouling than a blunt one, and that sharp corners near the regulator
nozzle should be well beveled, or rounded.

      It is anticipated that field tests to be conducted  as part of the
demonstration grant will resolve the fouling problems associated with
fluidic sewer regulators under actual conditions.
                                 88

-------
Figure 76.  Basic Irrigation Test Model
            2"  x 3" Nozzle
Figure 77.  Simulated Debris,  Fouling Test
                   89

-------
                          SECTION 6

           DEMONSTRATION PLANNING AND LIAISON
General

      One of the specific objectives of the subject program was to assist
the FWPCA in planning and establishing the succeeding phases of the
program; namely, the design, construction, operation, and evaluation
of the Fluidic Sewer Regulator concept in a typical metropolitan diversion
location.  It is the  FWPCA1 s intent that the work should be done by a
large municipality,  under a FWPCA Demonstration Grant.  Because of
the preponderance of combined sewers in the eastern USA and the relative
convenience in performing engineering liaison from both EEC and the
FWPCA, it was decided that candidate cities should be New York,  Chicago,
Washington, D. C. , Philadelphia, and  Baltimore.

      Accordingly,  a series of visits were arranged with the various
municipal sewer engineering chiefs as follows:
 New York City,  N.Y.
 Chicago, Illinois
 Baltimore, Maryland
 Philadelphia, Pa.
 Washington, D. C,
Official & Title

Mr. Joseph Cunetta
Deputy Director,  Plants
Bureau of Water Pollution
 Control
City of New York

Mr. Clint Keifer
Chief, Water & Sewer
Design Engr'g, Dept. of
  Public Works
City of Chicago

Mr. John Prussing
Principal Engineer
Sewer Construction

Mr.  Carmen Guarino
Deputy Water Commissioner
City of Philadelphia

Mr.  James Robertson
Associate Director
Engr'g & Construction
Dept. Sanitary Engr'g
District  of Columbia
July 14, 1969
July 25,  1969
July 28,  1969
                                                       August 5, 1969
                                 90

-------
Questionnaire

      A brief questionnaire was presented at each meeting to assist in
defining each city's capability and interest in seeking and performing
the subject Fluidic regulator demonstration uder a FWPCA Demonstration
Grant.  The questionnaire contained the following:

      1.    Are relatively small diversion points available within the
      municipal area for installing a small pilot model Fluidic sewer
      regulator?

      2.    Is municipal funding available in keeping with the FWPCA1 s
      75% -  25% funding policy?

      3.    Are there difficulties,  or unusual conditions required to
      secure the commitment of municipal funds to support 25% of the
      program cost?

      4.    Would serious scheduling delays exist in the installation
      of the demonstration program due to prior commitment, or un-
      availability of engineering or construction manpower,  or facilities?

      5.    Would the municipality consider the use of A&E contract
      assistance in conducting the demonstration program?

      6.    Would the municipality encounter procurement difficulties
      in contracting for sole source goods or services in view of BEC's
      proprietary position in the Fluidic  field in general, and in water
      management devices in particular?

      7.     Has the municipality had prior experience in conducting
      programs under FWPCA Research, or Demonstration Grants?

      8.     Would officials  of the municipality be interested in visiting
      BEC's laboratory and watching a demonstration of the experimental
      model?

 Visit Discussion

      The results of each visit are summarized:

      New York  City.  Mr. Cunetta and  his staff showed strong technical
 interest in the program concept, and test results. Questions were raised
 on the  effect of  regulator diversion performance away from interceptor
 when tide gates are backloaded with high tides; Answer - regulator would
 work fairly well until tide level exceeded 25% of inlet head level.  In
 response to questionnaire items:

                                  91

-------
      1.    Location for small regulators probably available, but some
      study needed.

      2.    Funds could be made available, with approval of Board of
      Estimates.

      3.    No specific approval difficulties - this type of program has
      been approved in the past.

      4.    A starting delay from 18-24 months would be necessary due
      to engineering work backlog.

      5.    NYC would consider A&E assistance; they suggest that BEG
      should contract this effort directly, rather than NYC.

      6.    No specific problem procuring sole source, proprietary
      equipment or services if good reason is present.

      7.    NYC is currently evaluating the "Ponsar" regulator concept
      under FWPCA Demonstration Grant.

      Summary — New York City has the technical interest,  and financial
capability, but engineering  capability would not  be available for 1-2 years
- Good possibility for a Demonstration Grant  program later, poor possi-
bility in near future.

      Chicago, Illinois.  Mr. Keifer showed moderate technical interest
in concept, but indicated that Chicago's  system  of sewers did not include
many small diversion points that needed regulation (most regulation is
done with very large electric motor driven gate structures), and foresaw
difficulty in getting  approval to install a regulator in a currently non-
regulated diversion point.   In response to questionnaire items:

      1.    Small diversion points available, but currently do not need
      regulation (see above).

      2.     Present bond improvement funds very low - more bonds require
      voter approval before a new program could  be committed.

      3.    No particular difficulty in funding programs of this magnitude
      if funds are available.

      4.    No particular difficulty in getting approval, if funds are
      available.
                                92

-------
      5.    Chicago would probably not use A&E assistance for basic
      hydraulic design - only for detailed  structures once specifications
      are established.

      6.    No difficulty in sole source,  proprietary procurement of
      equipment, or services, if good reason is present.

      7.    Chicago currently has several FWPCA Demonstration Grant
      programs in progress.

      Summary -- Chicago has an excellent technical capability for
the subject program, but currently no firm requirements for this device;
is very limited in available funds - poor immediate  possibility for the
subject Demonstration Grant program.


      Baltimore.  Maryland.  Mr. Prussing showed technical interest
but indicated  that Baltimore had virtually no combined sewers.  He
indicated that requirements for storm water diversion existed, if the
device could be adapted to this requirement (Answer - it could). In
response to the questionnaire:

      1.     Except for a few storm water diversion  points, very few
      diversion points are available.

      2.     Municipal funding is available.

      3.     No particular difficulties  in obtaining approval of Board
      of Estimates.

      4.    Baltimore has  a significant engineering work backlog.
      Consequently, considerable delay  in starting would  be anticipated.

       5.    A&E  contract assistance would be a strong probability.

       6.    No difficulty in procurement of proprietary, sole source
       equipment, or services if justification shown.

       7.    Baltimore currently has a FWPCA Demonstration Grant program
       in progress at the Back River Sewage Treatment Facility.

       Summary -- Baltimore has minimum requirements for subject device,
 except possibly  for storm  water  handling.  Despite general technical
 interest, this city has a considerable engineering work backlog, and thus
 could not consider the subject demonstration program for a considerable
 period of time -  poor possibility for the near future.
                                 93

-------
      Philadelphia, Pennsylvania.  Mr. Guarino showed strong interest
both in the technical progress made to date,  and,  the possibility of
evaluating the concept.  Philadelphia has at present approximately 70
small mechanical float-operated regulators, in addition to a number of
large hydraulically operated units.  The small units require at least
twice-a-week surveillance and close monitoring during storm conditions
to keep them operating.  With this background, Mr. Guarino indicated
he was quite interested in evaluating approaches which might require
less monitoring.  With respect to the questionnaire items:

      1.    Philadelphia has a considerable number of mechanical
      regulators, also many "slot" diverters, which are basically
      equivalent to the standard diversion dam and interceptor side
      flow line arrangement.

      2.    Municipal funding is readily available for experimental
      purposes upon the approval of the Water Commissioner.

      3.    Funding approval  can be made directly by the Water
      Commissioner.

      4.    Philadelphia has an experienced engineering staff who
      would be available on short notice to undertake the subject
      program.

      5.    A&E support would be considered, but is probably not
       specifically required.

      6.    There would be no procurement difficulty for sole source,
      or proprietary equipment or services,  if sufficient justification
      is present.

       7.    Philadelphia is currently active on a FWPCA Demonstration
      Grant concerning microstrainers for combined sewer overflows.

      Summary — Philadelphia appears to have strong interest, and
excellent capability for performing the subject Demonstration Program
- A top possibility.

      Washington, D. C. Mr. Moorehead, acting for Mr.  Robertson,
indicated a strong interest in the Fluidic concept, having accepted an
invitation to view the experimental model at EEC's laboratory in the
D.C. area where a pilot Fluidic regulator could be demonstrated.   How-
ever, he cited local government  policy which forbade any new construction,
or improvements to be made on existing combined sewers, since the city
                                94

-------
was embarked on a long term program to replace these with separate
sewers.  Consequently, although the city would be willing to offer a
location for a demonstration model, it would not agree to conduct the
actual demonstration program under a FWPCA grant.

      Summary — Despite a strong technical interest in the subject
concept, and a very cooperative attitude in offering to provide facilities
and other assistance to such a demonstration program, Washington,
D. C. could not be considered for the subject program.

Second Round Meeting

      Following the initial series of meetings,  Mr. Guarino and his
staff visited EEC on September 3 and  viewed the experimental laboratory
model.  Mr.  Guarino confirmed the City of Philadelphia's desire to
participate in the subject Demonstration Grant program. At the time
of writing of this report, the Demonstration Grant Request is  in prepa-
ration by his staff.

Demonstration Program Schedule

      A preliminary Demonstration Program Schedule spanning 24 months
is shown in Figure 78.  This plan would establish a 4 month design
phase, a 4 month construction phase, a 2 month checkout phase, and
a 12 month operational evaluation  phase, and a  2 month reporting phase.
This plan will be finalized when the Demonstration Grant Request is
submitted to the  FWPCA.
                                95

-------
                                               1970
                                                                      1971
(£>
cn
DESIGN



CONSTRUCTION




CHECKOUT



EVALUATION
         REPORT
               DRAFT
               FINAL
I FMAMT T ASOND




~3

[


1
d
Hi
1

J FMAMT I ASOND










I
=•
                                      Figure 78.  Preliminary Demonstration Plan

-------
                          SECTION 7

                     ACKNOWLEDGEMENTS
      Acknowledgement is made to the following chiefs of Sewer Engineering,
and their respective staffs,  for their interest and the time taken in the con-
ducting of the interviews necessary for the Demonstration and Planning phase
of the subject program, as described in Section 6.

               Mr. Joseph Cunetta
               Deputy Director, Plants
               Bureau of Water Pollution Control
               City of New  York

               Mr. Clint Keifer
               Chief, Water & Sewer
               Design Engr'g Dept. of Public Works
               City of Chicago

               Mr. John Prussing
               Principal Engineer
               Sewer Construction
               Baltimore, Maryland

               Mr. Carmen Guarino
               Deputy Water Commissioner
               City of Philadelphia

               Mr. James Robertson
               Associate Director
               Engr'g & Construction
               Dept. of Sanitary Engr'g
               District of Columbia

      Acknowledgement is  made to Mr. George A. Moorehead, Chief of
 Systems and Planning, Department of  Sanitary Engineering, District of
 Columbia, Washington, D. C. , and to Mr. Carmen Guarino,  Deputy
 Water Commissioner, City  of Philadelphia, for furnishing typical diversion
 structure drawings, and the generation of preliminary diversion structure
 cost estimates, as described previously  in Section 3.

      Acknowledgement is made to Mr. William Rosenkranz, Chief of the
 Storm and Combined Sewer  Pollution Control Branch,  FWPCA;  and to Mr.
 Darwin Wright, Program Project Officer,  of the same organization.   These
                                 97

-------
individuals have provided valuable guidance and background information
in the course of conducting the subject program.

      Acknowledgement is made to members of the Bowles Engineering
Corporation staff as follows:

            P. A. Freeman                     Program Director
            R.  Bean                            Research Engineer
            J. Zaloudek                        Research Engineer
            P. Cain                            Test Technician
            P. Senes                           Test Technician
            A. Freiling                         Model Shop
                                98

-------
                    SECTION 8

           REFERENCES AND PUBLICATIONS
1.    Report:  "Problems of Combined Sewer Facilities and Over-
flows - 1967," prepared by the APWA under contract 14-12-65,
sponsored by the FWPCA.

2.    Paper:  "Performance and Operating Characteristics of a
Fluidic Irrigation Diverter," prepared byDrs. Howard R. Haise
and E. Gordon Kruse, of the ARS, SWC, USDA,  Ft. Collins,
Colorado.

3.    Article:  "Air Pressure Drop Nomograph,"  F.  Kaplan, Kaiser
Engineers, appearing in the April 1967 issue of Controls Engineering^
Magazine.
                           99

-------
                          SECTION 9

            GLOSSARY OF TERMS AND ABBREVIATIONS
Fluidic Element Nomenclature

      Nozzle - opening where fluid (water in this case) enters the fluidic
element having a geometry similar to a venturi throat.

      Control  Ports - openings immediately downstream from the nozzle,
where fluid  (gas or liquid) is admitted to influence the direction of nozzle
flow.

      Interaction Area - the volume of the  element immediately down-
stream of the control ports and upstream of the splitter,  containing the
attachment walls.

      Splitter - a wall which divides the fluidic element exit area into
two (or sometimes more) sections.

      Attachment Walls - wall of element immediately downstream of
the control  pockets to which the water jet attaches by the coanda effect.

      Coanda Effect - wall attachment phenomenon of a jet stream close
to a wall which provides  a pressure differential to act on the jet stream
as  a result  of entrainment at the wall, producing a low pressure area.

      Venturi  - a constriction in a flow channel which produces increased
velocity and decreased pressure or suction at the constriction.

      Aspiration  - drawing of fluid (air in  this case) into diverter inter-
action region  by  suction caused by the venturi action of nozzle.

      Setback - offset of one portion of geometry to another measured
away from centerline of nozzle.

      Aspect Ratio - ratio of height of diverter nozzle to  its width.

      Digital  Switching - having only two functional states,  either maximum
or minimum diversion.

      Analog Switching - having a continuous range of diversion values
between maximum and minimum levels.
                                 100

-------
Abbreviations



      PVC - Polyvinylchloride




      ABS - Acrylonitrile - Butadiene - Styrene




      PE - Polyethylene




      hn - height of regulator nozzle




      hi - height of inlet head




      hd - height of discharge




      wn - width of regulator nozzle




      a - aspect ratio




      A  - area of nozzle
                                   101

-------
                    SECTION 10




                   APPENDICES






                                               Page




A.    Log of Sewer Regulator Element Tests         104




B.    Orifice Equation                            110




C.    Performance Design Data                    116




D.    Fouling Analysis                            132




E.    Control Line Sizes                          134
                          102

-------
                          APPENDIX A
Log of Sewer Regulator Element Tests

      The test program was begun with tests of the 1/2" x 1/2" nozzle
irrigation diverter as part of the task 1 predictive analysis listed on the
first page.  Testing was then continued on model sewer regulator vari-
ations starting from the basic irrigation geometry, and culminating in the
final analog regulator configuration.  These tests are listed from June 20
to July 25.  Several final configurations were then tested to investigate
minor changes in geometry and obtain performance curves and design
data (see tests from August 15 to September 4).   Tests listed in the log
were for regulator elements for which test data were recorded and  a
definite variable was tested.  In many cases numerous  testing was done
by visual observation with many variables and  formal data were not
recorded.
                                 103

-------
Log of Sewer Regulator Element Test&
Test
Date
4-4

4-7

4-9

4-17

4-17

4-17

4-18

4-18

4-18

4-24

4-24

4-28

4-28


Test
No.
1

1

1

1

2

3

1

2

3

1

2

1

2


Config.
No.
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element
Irrigation
Element

Nozzle
Size
1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2

1/2x1/2


Sensor
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices
Bias
Orifices

Parameter
Tested
Supply
Flow vs Head
Control Flow
vs Supply Flow
Control Bias.es

Head = 3.0"
Control Biases
Head =5.0"
Control Biases
Head = 7.5"
Control Biases
Head = 3.0"
Zero set back
Head = 4.0"

Head = 7.5"

Control
Airflows
Control
Pressures
Setback

Control
Airflow
104
Results of Tests
Useful productive data

Useful productive data

Some analog control
possible
Digital operation

More analog range

Same as 5.0" head

No control

No control

No control

Airflow vs % div.
obtained
Pressure diff. vs.
Diversion obtained
Curve obtained low
scatter of data
Airflow vs % div. showed
wide scatter

Diversion
Range
0-100

0-100

50-100

0-70

0-95

0-90

95-98

95-100

95-100

0-95

0-95

0-100

0-95



-------
Log of Sewer Regulator Element Tests (Continued)
Test
Date
5-14


5-14

5-14

5-15

5-16

5-16

5-23

5-26

5-29

6-16

6-16

6-17

6-17

6-18


6-18


6-18

6-18


6-19

6-19
6-19


Test
No.
1


2

3

1

1

2

1

1

1

1

2

1

2

1


2


3

4


1

2
3


Config.
No.
513-1


513-1

514-1

515-1

516-1

516-2

516-2

516-2

527-1

616-1

616-2

617-1

617-2

618-1


618-2


618-3

618-4


618-4

618-4
618-4


Mozzle
Size
2x3


2x3

2x3

2x3

2x2-1/2

2x3-1/4

2x3-1/4

2x3-1/4

2x3-1/4

2x1

2x1

2x1

2x1

2x1


2x1


2x1

2x1


2x1

2x1
2x1


Sensor
Bias
Orifice

Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice
Bias
Orifice

Bias
Orifice

Bias
Orifice
Bias
Orifice

Float
Valve
Bottles
Bias
Orifice

Parameter
Tested
Single control
geometrical
bias
Weir setting

Cusp on split-
ter
Cusp - smaller

irrigation
Geometry
Wider nozzle
pointed splitter
Weir setting

Lower head

Fouling tests

Higher aspect
ratio
Smaller control
pockets
Vortex pockets
1-1/2"
Vortex pockets
2"
Increased set-
back decreased
wall angle
Splitter posi-
tion 1 " down-
stream
Vortex pockets
3"
New profile
cutaway side-
walls
Sensor

Sensor
Sensor

105
Results of Tests
Poor control range


Poor control range

Improved diversion
range
Reduced operating
range
Strickly bistable
operation
Improved diversion
range
Good range - still
bistable
Reduced range

Low percent fouling

Comparable to previous
tests
Strickly bistable

Some intermediate
values
Poor control

Reduced operating
range

Same as 618-1


No control

Nearly bistable


Small analog range

Sames as Test 1 above
Reduced operating
range

Diversion
Range
25-45


16-36

19-73

27-39

8-100

20-79

15-94

23-88

18-87

18-80

18-79

0-100

30-78

26-64


27-68


50-50

15-74


30-91

30-100
30-68



-------
Log of Sewer Regulator Element Tests (Continued)
Test
Date
6-20

6-20

6-20

6-20

6-20
6-23

6-23

6-23

6-24

6-24

6-24

6-24

6-25

6-25

6-26

6-26

6-26


6-26

6-27


7-1

7-1



Test
No.
1

2

3

4

5
2

3

4

1

2

3

4

1

2

1

2

4


5

1


2

3



Config .
No.
620-1

620-2

620-3

620-4

620-5
623-1

623-3

623-4

624-1

624-1

624-1

624-1

625-1

625-2

626-1

626-2

626-4


626-5

627-1


71-1

71-1



Nozzle
Size
2x1

2x1

2x1

2x1

2x1
2x1

2x1

2x1

2x1

2x1

2x1

2x1

2x1

2x1

2x1

2x1

2x1


2x1

2x1


2x4

2x4



Sensor
Bias
Orifice
Bias
Orifice
Float
Valve
Float
Valve
Bottles
Float
Valve
Float
Valve
Float
Valve
Float
Valve
Float
Valve
Float
Valve
Float
Valve
Float
Valve
Float
Valve
Float
Valve
Float
Valve
Float
Valve

Float
Valve
Float
Valve

Float
Valve
Float
Valve


Parameter
Tested
Setback = 0

Splitted moved
upstream
Setback
increased
Short sidewalk
added
Short sidewalls
Wall length
1,2"
Wall length
3.2"
Splitter moved
2" downstream
Curved side-
walls 1.2"
Control orifice
shade
Larger area
triangle
One half size
triangle
Pointed splitter
upstream
Blunt splitter

Splitter moved
downstream
Sharp splitter

Sidewall cut-
back shortened
1/2"
Rounded
splitter
Sidewall cut-
back shortened
1/8"
Nozzle

Combined
weir raised
106

Results of Tests
Not enough setback to
deflect jet
Same as Test 1 above

Same as Test 1 above

Improved analog control
range
Pour range - surging
Poor range

Improved range

Reduced operating
range
No significant improve-
ment
Slightly improved
linearity
Most linear performance

Much more digital
performance
Improved range

Reduced range

Improved range

Suring - splitter very
close
Not surging


Reduced range

Improved range


Did not match 2x1
performance
Improved range



Diversion
Range
50-50

50-50

50-50

0-77

0-81
11-52

19-100

8-71

11-83

15-86

12-83

13-75

11-79

10-45

6-73

7-100

11-91


19-81

0-86


4-68

7-81




-------
Log of Sewer Regulator Element Tests (Continued)
Test
Date
7-8

7-8

7-8

7-9

7-9

7-9

7-9

7-10

7-10

7-10

7-10

7-11

7-11

7-11

7-11

7-11

7-14

7-15

7-15

7-15

7-15


Test
No.
1

2

3

1

2

4

5

1

2

3

4

1

2

3

4

5

1

1

2

3

4


Config.
No.
74-1

74-1

74-1

78-1

78-1

78-1

78-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1


Nozzle
Size
2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4


Sensor
Float
Valve 1
Float
Valve 1
Float
Valve 1
Float
Valve 1
Float
Valve 1
Float
Valve 1
Float
Valve 1
Float
Valve 1
Float
Valve 1
Float
Valve 1
Float
Valve 1
Float
Valve 2
Float
Valve 2
Float
Valve 2
Float
Valve 2
Float
Valve 3
Float
Valve 2M
Float
Valve 2M
Float
Valve 2M
Float
Valve 2M
Float
Valve 2M

'arameter
Tested
ensor low
lead
nterceptor
weir lower
ncreased
head 10"
nterceptor
weir higher
ncreased
head 13"
Lower head
8.5"
Low head
60"
Head 8.5"

Head 10.0"

Head 12.0

Head 6.0

Sensor head
10.0"
Lower com-
bined weir
ncreased
head 13.0
Head 7.5"

Sensor head
10.0"
Sensor head
8.5"
Head 11.0"

Head 14.0"

Raised com-
bined weir
Reduced head
11.0"
107
Results of Tests
Poor control

Slight increase in range
- digital
Improved range -
digital
Improved range -
digital
Slightly improved -
digital
Reduced range - digital

Further Reduced range

Still digital

Same as 8.5" head

Same as 8.5" head

Greatly reduced range

Increased analog range

Reduced range

Sames as 8.5" head

Reduced range

Analog performance

Linear analog
performance
Increased range

Reduced range

Range restored

Reduced range


Diversion
Range
35-54

3-40

4-61

5-70

1-69

3-55

2-47

1-78

1-75

1-78

1-38

2-76

5-58

2-79

0-60

0-74

3-69

2-81

3-47

3-81

1-69



-------
Log of Sewer Regulator Element Tests (Continued)
Test
Date
•••j^- i —
7-16

7-16

7-16

7-16

7-16

7-18

7-18

7-18

7-18

7-23

7-23

7-23

7-24

7-24

7-24

7-24

7-25

7-25

8-15

8-15


Test.
No.
1

2

3

5

6

1
i
2

3

4

1

2

3

1

2

3

4

1

2

1

2


3onfig. ]
No.
710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

710-1

813-1

813-1


Nozzle
Size
2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

2x4

1x4

1x4

1x4

1x4

1x4

1x4

4x4

4x4


1
Sensor
Float ]
Valve 2M
Float
Valve 2M
Float
Valve 2M
Float
Valve 2M
Float
Valve 2M
Multiple
Dip tubes
Single
Dip tube
Multiple
Dip Tubes
Multiple
Dip Tubes
Plugged
controls
Plugged
controls
Plugged
controls
Float
Valve 2M
Float
Valve 2M
Float
Valve 2M
Float
Valve 2M
Float
Valve 21V
Half
area 2M
Float
Valve 4
Float
Valve 4

Parameter
Tested 1
Bead 10.0

Head 13.0

Head 6.5

Head 6.0

Head 7.0

Sensors

Sensor

Sensor areas

Head

Combined
weir
Higher heads

Higher heads

Head

Head 12.0"

Head 8.0"

Head 10.0"

Diversion

Sensor

Weir settings

High com-
bined weir
108
1
Results of Tests
	 __ 	
Linear

Increased range

Reduced range

Greatly reduced range

Increased range

Poor control range

Wide linear control

Good range - linear

Good control - 2 sensor;
w/head
Fine adj for optimum
setting
Higher max. diversion
range
Maximum range

Very short range -
still linear
Won't attach on inter-
ceptor side
Lower range - attach-
ment problem
Same switching problem

Best control range

No improvement

Not as good range as
211 A II
x4
No control switching


Diversion
Range
3-77

3-81

8-53

4-8

5-53

5-26

1-76

0-78

41-82

29-68

49-83

47-83

4-9

39-84

21-49

30-75

36-84

36-81

8-64

50-50



-------
Loq of Sewer Regulator Element Tests (Continued)
Test
Date
8-15

8-15

8-15

8-15

8-19

8-20

8-20

8-20

8-21

8-29

9-3

9-4

9-4

9-4

9-4


Test
No.
3

4

5

6

2

1

2

3

1

1

1

1

2

3

4


Config.
No.
813-1

813-1

813-1

813-1

818-1

818-1

818-1

818-1

818-1

829-1

829-1

829-1

829-1

829-1

829-1


Nozzle
Size
4x4

4x4

4x4

4x4

4x4

4x4

4x4

4x4

4x4

2x4

2x4

2x4

2x4

2x4

2x4


Sensor
Float
Valve 4
Float
Valve 4
Float
Valve 4
Float
Valve 4
Float
Valve 4-5
Float
Valve 6
Float
Valve 6
Float
Valve 6
Float
Valve 6
Float
Valve 2M
Bottles

Float
Valve 2M
Float
Valve 2M
Float
Valve 2M
Float
Valve 2M

'arameter
Tested
..ower head
.0"
Low combined
weir
Head 17.0

High combined
weir
Sensors

Sensors

Head 9.0"

Head 17.0

Flow over
discharge
Diversion

Sensor

Weir settings

Higher head
16.0
Lower head
8.0
Shrouded
discharge
109
Results of Tests
Narrow control range

Increased control range

Increase range

Increase range

Improved linearity
with area
Greater area - improved
linearity
Slightly improved
range
Slightly improved range

Greatly effects
performance
Performance matches
early 2x4
Narrow control range
- not linear
Affect performance
significantly
Slightly improved
control ranges
Lower control ranges

Large shroud need to
separate flows

Diversion
Range
40-50

10-50

18-71

8-69

11-62

12-60

12-64

12-71

4-30

0-80

0-63

2-75

2-82

0-52

43-66



-------
                          APPENDIX B
Orifice Equation

      Q =
                  2gAh

           Q   =  Flow through orifice in cubic feet per second (CFS)

           CD =  Orifice discharge coefficient (non-dimensional)

           A   =  Area of orifice in square feet

           g   =  Gravity constant 32.2 ft/sec/sec

           Ah  =  Differential head in feet across orifice, i.e.,
                  upstream head minus downstream

      In order to accurately use the orifice equation to calculate the
flow through an orifice the head and orifice coefficient must be known.
Test data  taken from a fluidic irrigation water diverter by the Engineering
Research  Service, at Fort Collins,  Colorado, provide flow vs supply
head data for a known nozzle size diverter,  see Figure B-l.

      These data were used with the orifice  equation to obtain the values
of discharge coefficient vs differential head, see Figure B-2.

      The experimental curve of discharge coefficient vs supply head
was then  used with the orifice equation to form the nomograph of Figure
10 covering a nozzle area range from 0.1 to  10 square feet,  a head
range from 1.0 to  100 feet and orifice  coefficients from  0.8 to 1.2.

      The nomograph obtained from the orifice equation  and irrigation
diverter (8" x 8")  test data were  then compared to the data from the
1/2" x 1/2" irrigation diverter used in the predictive analysis and the
2" x 4" fluidic sewer diverter,  see Figures  B-3 and B-4 with the  fol-
lowing results.

Comparison of Test Data

      1/2" x 1/2" Nozzle Irrigation Diverter, Figure B-3

            A = 1.73 (10-3) sq  ft  Ah  = .455 ft CD =  1.2  hi/hn = 12
                                110

-------
              90-95%  96-1007]
                                  Original romp length
                                  l"  ramp extension
                                  3"  romp retraction
                                  6"  ramp retraction
 M
<«-
 -o
<
O
    4.0
     3.0

Figure B-l.   Relationship of Discharge to the Differential Head
             Across  the Diverter.   Fluidic Irrigation Diverter
             8" x 8" Nozzle
                             111

-------

-------
•

-------
114

-------
      Flow from Figure B-3 measured

           Q  = 5 gpm = 1.11 (10~2) cfs

      Flow from nomograph Figure 10

           Q  = 1.1 (10-2) Cfs

Agreement of flows was as good as the reading accuracy of the nomograph
or approximately 1%.

      2' x 4" Nozzle Sewer Regulator, Figure B-4

           A  = 5.5 (10-2) sq ft  Ah = .915 ft  CD  =  1.2

      Flow from Figure B-4 measured

            Q = 228 gpm  =  . 507 cfs

      Flow from nomograph Figure  10

            Q -  .51 cfs

Agreement better than 1% indicating the nomograph of Figure 10 is a
reliable source of design data for fluidic  sewer regulators.
                                115

-------
                         APPENDIX C
Performance Design Data

      Diversion vs control orifice areas for various bias orifice areas
were taken from the 1/2" x 1/2" nozzle irrigation diverter at various
supply heads, see Figures C-l and C-2.

      Diversion vs supply head data were taken for sewer regulator
geometries having nozzle and aspect ratios as follows:

            Aspect Ratio                     Nozzle Size

                2                              2" x 1"
                1                              4"x4"
               .5                              2"x4"
               .25                             1" x 4"

      Actual data from test of these model regulators are shown in
Figure C-3.  Inconsistencies in the data curves resulted from minor
variations in the geometries of the regulators tested.  The misplace-
ment of the  data points from the 4" x 4" nozzle regulator were caused
by a long nozzle which reduced the venturi effect, see Figure 50.

      Diversion vs height of the combined discharge weir were measured
over a complete range of weir settings and supply heads as shown in
Figure C-4.  The  test data show that raising the combined weir increases
its resistance and diverts more flow to the interceptor.  As the combined
weir is lowered diversion increases until the weir gets so low that an
air pocket forms along the top of the element and destroys the wall attach-
ment effect  by equalizing control pressures and permitting direct com-
munication from ambient air to the interceptor control port. The water
flow is supercritical in this case.  The combined weir tests were  taken
for an  interceptor weir exit area of 12.2 in^ which was within the operating
zone of the  regulator.  Figures C-5, C-6, C-7, and C-8 show data taken
for maximum and minimum diversion as a function of the interceptor weir
area which produces a loading effect somewhat like that of the combined
weir.  If the interceptor area is too great the coanda effect won't  form as
a result of supercritical flow conditions.  Too small an area affects
maximum dry weather flow diversion to the interceptor, so that some
flow goes over the combined weir.  Data were taken for two nozzle sizes
and three supply heads,  see graphs.
                                116

-------
a .O*K>' D'd
                         PERCENT DIVERSION AS A
                                 OF  BIAS
                       H+milMIIMIIIIIIIIIM

-------
CO

-------


-------
ro
o

-------

PERCENT DIVERSION F*OM

-------
I  I
I  ,

-------
!
                               HEIGHT of NoT.-Z.Le
                           PERCENT DIVERSION) FROM

-------
I.       I

-------
      Percent diversion vs the height of water in the interceptor data
were taken for the best analog geometry with the most linear sensor to
determine diversion range and linearity over a wide range of heads,
see Figure C-9.  Results showed that linearity was good over the oper-
ational head  range; however, diversion performance dropped sharply
for supply heads  below 3.5hn (hn = nozzle height).  Diversion performance
showed improvement with head until a head of 5 hn was reached at which
point best performance is reached.  Figures C-ll and C-12 show the
combined interceptor sewer test setup with the float valve, used to obtain
the diversion data discussed above.

      In order to  represent the change in interceptor level  as a more meaningful
parameter, the sensor  float valve calibration was expressed as area change
of sensor over area of  regulator nozzle as follows:  (see Figures C-10 and
C-13)
      Sensor Area Change Ratio = - - - —   (10 3)
                                     AN
            AA^  =  Change in combined control area
            AA2  =  Change in interceptor control area
            AN   =  Area of nozzle

      Reference Point

            Flow diverted  100% to interceptor
            AA,  = 0  AA9  =  0
               1          £.*
      As the interceptor water level increases area AA2 (interceptor control
 area) is opened until the 50-50 diversion point is reached.  As the inter-
 ceptor level continues to change AA]_ (combined control area) is closed until
 at 100% diversion from  the interceptor, AAi is fully closed and AA2 is  fully
 opened giving a sensor area change ratio of:
            AC  + AC  =  -- , Ac =  Area of control orifice
              AN        AN

      Air flow through the control ports of a fluidic sewer regulator as a
 function of the percent diversion was plotted as an air/water ratio for a
 2" x 4" and 4" x 4" sewer regulator being controlled by a mechanical float
 valve,  see Figure C-14.  Test observations and data confirmed the air flow
                                 125

-------
r .
• i,
                                                                                      wer/es SET pae MAX/MUM

-------
I
  I

-------
Figure C-ll. Low Diversion,  Low Interceptor Water Level
             Float Valve Control
     Figure C-12.  High Diversion, Loaded Interceptor
                   Float Valve Control
                          128

-------
f  I

-------
w
o

-------
characteristic as shown.  As the control port is opened from a maximum
diversion setting aspiration begins and increases until the 50-50 diversion
point is reached when the port is fully open.  Sensor tests showed that
further increase in sensor area has no effect; that is, the regulator is
getting all the air it needs.  As the diversion increases above the  50 per-
cent level, the aspiration in the open control line actually drops as a result
of the decreased venturi effect when the jet stream is directed away from
the control pocket.
                                  131

-------
                          APPENDIX D
Fouling Analysis

      The table shown on the following page is the test data taken as
part of the fouling analysis.  The test configuration used, see Figure 76,
had a very pointed splitter which was much more susceptible to fouling
than more rounded types which were found to have the same diversion
performance.  Half of the fouling hang up caused by the twigs were caused
by the forks snagging the pointed splitter.  The remainder of the hang ups
caused by twigs resulted in the long (10") twig lodging crosswise at the
nozzle.  It is  quite possible that under actual conditions where a reasonably
long approach line supplies the regulator, long objects such as twigs and
rolls of paper  will align themselves in the water stream with their longest
dimension in the direction of the stream, allowing them to pass through the
regulator rather than hang up crosswise.
                                132

-------
                              Fouling Test Data
Regulator Element Nozzle Size 2" x 3-1/4"
Supply Head  9-1/4"
Interceptor Weir  Open
Code
Letter
Fig.
4-16
A
B
C
D
E
F
G
H
-
-
-
-
Subject
Length
Twig- 6. 5"
Twig- 3.0"
Twig- 6.0"
Twig- 6. 5"
Twig- 4.5 "
Twig- 3. 5"
Twig- 4.0"
Twig- 10.0"
Paper- 2 "x3"
Paper- 4 "x5"
Paper- 2 "x6"
Paper-10"xl6"
Number
of
Forks
2
0
2
0
2
1
1
1
-
•
-
-
Total
Passes
10
10
10
10
10
10
10
10
10
10
10
10
Passed
Through
5
10
8
9
9
10
10
5
10
10
10
8
Hung Up
Then
Passed
Through
3
0
1
1
1
0
0
2
0
0
0
0
Hung
Up
2
0
1
0
0
0
0
3
0
0
0
2
Remarks
Fork caught splitter

Large fork caught
pointed splitter




Caught in neck of
nozzle



Hung up on splitter
                                   TOTAL HANG UPS
                                    133

-------
                          APPENDIX E
Control Line Sizes

The control line I.D.  vs length vs regulator nozzle area data as shown
in Figure 13 was derived with the following considerations.

The maximum airflow through the control port occurs at the 50-50 diversion
point,  see Figure 70.

The maximum airflow for fluidic sewer regulators is 5 x 10~2 times the
water flow through the regulator,  see Figure 70.

The optimum sensor area for linear analog control of a sewer regulator
is 20 (10~3) AJJ (A}j  = area of nozzle -in2), see Figures 62 and 63.
Knowing the maximum area and maximum airflow we can calculate the
pressure drop across the sensor orifice with zero control line length,
using Figure E-l.

Using the sensor area vs diversion characteristic for linear analog control
shown in Figures 62 and 63, it was assumed that a degradation in di-
version performance of 10% would be tolerated as a result of the control
line length to be added to the  sensor control orifice.

The area change corresponding to a 10% degradation in diversion per-
formance, from Figures  62  and 63, is 5 (10~3) AJJ  (A^  = area of nozzle).
It was then assumed that the same maximum control airflow would pass
through an orifice with new area equal to the optimum sensor area minus
the area change corresponding to the 10% degradation in diversion per-
formance:
            New area  = [20 (1Q-3) - 5 (10~3) j

                      =   15 (10~3)  Ajsj (AN  =  area of nozzle)
Using the maximum airflow and this new area the pressure drop across the
new area is obtained from Figure E-l.

The difference in pressure drops (AP) between the pressure drop across
the optimum sensor orifice area  and the sensor orifice area which would
provide a diversion change of 10 percent is then the tolerable pressure
drop in the control lines when the  control orifice is fully open and airflow
is at its maximum value.

                                134

-------
10.0


0.
                         0.01                 0.1                 1.0
                        FLOW (Q) IN CUBIC FEET PER SECOND (CFS)
10.0
                    Figure E-l.  Air Flow Through Orifice

-------
 The pressure drop (AP) was then used with the nomograph showing Figure
 E-2* to determine the minimum I.D. (internal diameter) of a  100 foot
 control line.  By using  various scale factors of AP with the nomograph
 of Figure E-2, a family of curves of control line I.D. vs length of control
 line vs regulator nozzle area was obtained.  (See Figure 13.)  The  air
 pressure drop nomograph (see Figure E-2) used to obtain the control pipe
 size is demonstrated through the following example:

            The temperature of the fluid on the "t" scale  is connected
      with the exhaust pressure of the pipe on the P scale intersecting
      index A at point a.

            P  = 0 psig, t  = 700p

            Point a is then connected to the flow rate through  the pipe
      as shown on the  "V" scale and intersecting index B at point b.

            V = 1.0 scfs  = 60.0 scfm

            Point b is then used with  the allowable pressure drop for
       100 foot of control pipe from scale &PIQO am* ^e intersection of
      a line through  these two parameters  gives  the minimum required
      control line size.

            AP =  .04  psig

            Minimum I.D.  = 2.9 inches
*This figure is based on an article "Air Pressure Drop Nomograph," by
 F. Kaplan, Kaiser Engineers, appearing in the April, 1967, issue of
 Controls Engineering Magazine.
                                 136

-------
Figure E-2.  Air Pressure Drop Nomograph
      Pressure - PSIG
      Pressure Line Drop/100 Feet = PSIG
      Flow Through Line - SCFM
      Temperature of Fluid - deg F
      I.D. of Tubing - inches
                                               3o—
                                              /   :
Inda* Index /
r« '
\
\
\
-5 \
\

— 10 \

— IS
— 20


—30

—40
— 50

— 60
— 70
— 80
— 90
— \oo

j— ISO
\

-2oo

— 250


— 3oo
P In
,
*?;n

J50—
40 —
30 —
2P —

^_^
\IO=:
\~
x-
4—
3 —

o
o

!f-/.o —
&.^1-
-1 W —
*) f\^ 	
^
0.2—

al —
.05 —
,04 —
.03 —
D2 —


jo\ —
.ooe —
^)06 —
ex-aW—
\
i







-^— ^
^ ^~ ^.
^^7
\ /
\»
1
\ ,
\
\ 1
\ i
V
/\
/ \
/ \
/ \
/ \
/ \
/
/
»-P>?essuRE DROP
PEPMlTTCO IN
CONTROL UH£
PC* 100'





In
' V
1000 —

7*o —
500 —
400 -j
3oo f-
1
20O —
1
• 100 —
b-76^
50 —
AO —
30-
"320 —
Ul
to"
u. —
7 -
5 -
4 —

3 —
\ ^ _

\
' "V
05 -
04 ~
0.3-
0.2 -


0.1 -
01 —
Jex job-
r, 2M-
-500 —

/ 1.6-
—
15 —

^ 0/3 —
El
— • —
—
— o
— -10
	 20
0./9 ^
	 30 p.j8 —















.e
Q"
M
Ol
C
-a















/" 
-------
         BIBLIOGRAPHIC:  The Bowles Engineering Corporation.  Design of a Combined.
           Sewer Fluldic Regulator FWPCA Publication No. DAST-13 October 1969.

         ABSTI&CT: The objective ot this program was to demonstrate feasibility,  and
           to develop a workable configuration for a Combined Sewer Fluidtc Regulator,
           whose purpose Is to minimize combined sewer discharge while protecting
           interceptor sewers from overloading during storm  flows.  A second objective
           was to develop design procedures and criteria for the general  application  of
           this concept to municipal sewer diversion requirements, including preliminary
           Investigations of construction methods,, costs, and maintenance require-
           ments. A third objective was to establish a plan and location for an oper-
           ational demonstration of the concept with a cooperating municipality.  All
           objectives were successfully met.  A generic Fluldic Regulator configuration
           was evolved which diverts 0 to 75% of the combined sewer flow away from
           the Interceptor as a function of water level sensed in the Interceptor sewer,
           or combined sewer, In either an analog  or digital operational mode.  Appli-
           cation design criteria were evolved for a range of small to medium sized
           municipal sewers, in terms of a few basic parameters.  Projected installation
           costs  are only slightly more than for conventional diversion structures; while
           the anticipated construction and maintenance requirements are simple and
           minimal.  The City of Philadelphia was established as a potential demon-
           stration site,  and a demonstration unit should become operational In late
           1970.  Recommendations were made for experimental activity to improve
           regulation linearity; expand application size limit,  and to better definitive
           construction methods and costs.  This report is submitted In fulfillment of
           Contract 14-12-486,  between the Federal Water Pollution Control Adminis-
           tration and the Bowles Engineering Corporation.
ACCESSION NO:

KEY WORDS

   Combined Sewers

   Low Cost

   Low Maintenance

   Fluldic

   Regulator

   Variable Diversion

   No-Moving-Parts
u
         BIBLIOGRAPHIC:  The Bowles Engineering Corporation.  Design of a Combined
           Sewer Fluldic Regulator rWPCA Publication No. DAST-13 October 1969.

         ABSTRACT:  The objective of this program was to demonstrate feasibility,  and
           to develop a workable configuration for a Combined Sewer Fluldic Regulator.
           whose purpose Is to minimize combined sewer discharge while protecting
           Interceptor sewers from overloading during storm  flows.  A second objective
           was to develop design procedures and criteria for the general  application  of
           this concept to municipal sewer diversion requirements. Including preliminary
           Investigations of construction methods, costs, and maintenance require-
           ments. A third objective was to establish a plan and location for an oper-
           ational demonstration of the concept with a cooperating municipality.  All
           objectives were successfully met.  A generic Fluldic Regulator configuration
           was evolved which diverts 0 to 7596 of the combined sewer flow away from
           the Interceptor as a  function of water level sensed In the Interceptor sewer,
           or combined sewer.  In either an analog or digital operational mode.  Appli-
           cation design criteria were evolved for a range of small to  medium sized
           municipal seweis, In terms of a few basic parameters.  Projected Installation
           costs are only slightly more than for conventional diversion structures; while
           the anticipated construction and maintenance requirements are simple and
           minimal.  The City of Philadelphia was established as a potential demon-
           stration site,  and a  demonstration unit should become operational In late
           1970. Recommendations were made for experimental activity to Improve
           regulation linearity: expand application size limit, and to better definitive
           construction methods and costs.  This report Is submitted In fulfillment of
           Contract U-12-486, between the Federal Water Pollution Control Adminis-
           tration and the Bowles Engineering Corporation.
         BIBLIOGRAPHIC: The Bowles Engineering Corporation.  Design of a Combined
            Sewer Fluldlc Regulator FWPCA Publication No.  DAST-13 October 1969.

         ABSTRACT:  The objective of this program was to demonstrate feasibility,  and
            to develop a workable configuration for a Combined Sewer Fluldic Regulator,
            whose purpose Is to minimize combined sewer discharge while protecting
            interceptor sewers from overloading during storm flows.  A second objective
            was to develop design procedures and criteria for the general  application of
            this concept to municipal sewer diversion requirements, including preliminary
            investigations of construction methods,  costs, and maintenance require-
            ments. A third objective was to establish a  plan and location for an oper-
            ational demonstration of the concept with a cooperating municipality.  All
            objectives were successfully met.  A generic Fluldic Regulator configuration
            was evolved which diverts 0 to 75% of the combined sewer flow away from
            the Interceptor as a  function of water level sensed in the Interceptor sewer,
            or combined  sewer.  In either an analog or digital operational mode.  Appli-
            cation design criteria were evolved for a range of small to medium sized
            municipal sewers. In terms of a few basic parameters.  Projected Installation
            costs are only slightly more than for conventional diversion structures; while
            the anticipated construction and maintenance requirements are simple and
            minimal.  The City of Philadelphia was established as a potential demon-
            stration site, and a  demonstration unit should become operational in late
            1970.  Recommendations were made for experimental activity to Improve
            regulation linearity;  expand application size limit, ami to better deflnltlze
            construction methods and costs.  This report Is  submitted In fulfillment of
            Contract 14-12-486, between the Federal Water Pollution Control Adminis-
            tration and the Bowles Engineering Corporation.
ACCESSION NO:

KEYWORDS

   Combined Sawers
   Low Cost
   Low Maintenance

   Fluldic

   Regulator
   Variable Diversion
   No-Moving-Parts
ACCESSION NO:

KEYWORDS

   Combined Sawers

   Low Cost
   Low Maintenance
   Fluldic
   Regulator
   Variable Diversion
   No-Moving-Farts

-------