orvallis EVAPORATION FROM POPLAR RIVER COOLING RESERVOIR Mostafa A. Shirazi CERL - 033 April 1977 nvironmental gjesearch ^laboratory % ------- EVAPORATION FROM POPLAR RIVER COOLING RESERVOIR Mostafa A. Shirazi CERL - 033 April 1977 Prepared for EPA Region VIII Dennis Nelson, Project Officer CORVALLIS ENVIRONMENTAL RESEARCH LABORATORY OFFICE OF RESEARCH AND DEVELOPMENT U.S. ENVIRONMENTAL PROTECTION AGENCY CORVALLIS, OREGON 97330 ------- I. Introduction An electric generation project proposed by the Saskatchewan Power Corporation impounds the East Branch of Poplar River to form a cooling reservoir. Since this is an international river and the proposed dam would be located within five miles of the United States-Canada border, the project raises water quality concerns to the State of Montana and to Environmental Protection Agency Region VIII. The impoundment of the river and the use of the reservior for cooling within the Canadian border is subject to certain water apportionment agreements as well as maintaining acceptable water quality. Evaporative water losses provide a first order link between water quantity and quality. It is important, therefore, to establish an estimate of such loss at the outset. The purpose of this report is to provide estimates of water loss by evaporation under specific conditions of power generation. Adequate details are outlined in this report to enable assessment of assumptions and comparison with other methods. II. Meteorological data Saskatchewan Power Authority supplies (a) dew point tempera- ture, (b) solar radiation, (c) natural water surface temperature and (d) wind speed for Coronach, Province of Saskatchewan, corre- sponding to the geographical location of the proposed reservoir within the Canadian border. These data are listed in Table 1 and will be used for all calculations in this report. III. Engineering data There are four coal-operated units, each generating 300 mega- watts of electric power. They totally reject 5.89 billion Btu/hr 1 ------- at 11.67°C (21°F) condenser aT. The volume flow rate of cooling water is 34.4m3s_1. The reservoir when flooded to its highest elevation is nearly 1800 acres (728 ha). Calculations are performed for a reservior area as small as 700 acres (283 ha). The distance between intake and discharge, measured along the river bed, is about 5 km. The discharge is a rectangular, open end conduit 3X5 meters with an invert elevation of 739 m. There is no skimmer wall con- sidered at the intake end of the reservoir. IV. Intermediate Calculations Table 2 shows a list of items that are common to all forth- coming calculations. These items are explained below: A) Wind speed function f(M)--Heat loss by evaporation and by conduction from the water surface are strong functions of ambient air flow. The greater the wind speed, the greater would be both losses. The functional form of wind speed for evaporation losses is not well known. Numerous wind functions have been compared by Edinger and Brady (1974). For example, fj (W) = 9.2 + 0.46 W2 Wnf2 rrenHg"1 where W is wind speed in ms"1 and fi(W) is expressed in Watts (W) per m2 per mmHg . For the range of wind speed used in this work, the above wind function yields low values. Higher, but realistic values of wind speed function were obtained from visual inspection of upper bound of data presented in Reference 2 and identified by f2 (W) in Table 2. Both quantities will be used in our cal- 2 ------- culations, yielding conservative and more liberal evaporation estimates for the purpose of comparison. B) Humidity ratio w--This is defined as the ratio of mass of vapor per unit mass of dry air. It was obtained from a stand- ard psychrometric chart, from the intersection of the dew point temperature and saturated vapor line. C) Ambient air vapor pressure e --This was obtained from the a definition of humidity ratio for a mixture of water vapor at e3 and air water vapor mixture at a standard pressure e = a 760 mmHg, i.e., w Rs 760 = (85^6° = 1222w mmHg Q Os5 • j where R, and Rp are, respectively, the universal gas constants a S for air and for steam. V. Natural evaporation Heat loss by evaporation per unit area can be calculated from: He = e(Ts - Td) f (W), Wnf2 p = .35 + .015 Tm + .0012 Tm2, (mmHg/°C) Tm = (Ts + V/2' °C T$ = Surface water temperature, °C Td = Dew point temperature, °C For total natural evaporation, Hg is multiplied by the surface area either of the reservoir or the area of the 5 km stretch of the river without impoundment. The heat loss Hg can also be calculated more directly from 3 ------- He =¦ (es - efl) f (W), Wm"2 where e$ is the saturated vapor pressure at the surface water temperature; eg is found from the standard steam tables. A graph of this function is shown plotted in Figure 1. Also on the same figure, one finds a graph of the slope of e$ with temperature. The latter will be needed in the calculations of forced evaporation. A listing of heat lost from water surfaces under natural conditions can be found in Table 3. In order to calculate the equivalent rate of water volume escaping from the surface in the form of vapor, we need to multiply He by the conversion factors .0408 and .0699, respectively, for the 700 acre and 1200 acre ponds. The results are thus expressed in cubic feet per second which are pro-rated for the entire year even though water loss by evaporation occurs only from April through October. Under natural conditions, surface ice is present from November through March. VI. Forced evaporation Induced heating of the water results in excess evaporation above the natural evaporation by a magnitude that is proportional to the change in the vapor pressure. An estimate of the vapor pressure above a heated reservoir can be obtained from the knowledge of the effective surface temperature Tg of the reservoir. We shall assume for the purpose of these calculations that Ts is an average temperature between the intake temperature T. and the discharge temperature (aT + T^) i.e., T. . T, ~ T,) S ~1 where AT is the temperature differential across the condenser taken to be 11.67°C. 4 ------- The intake temperature is an important parameter. It must be calculated from meteorological and engineering data. Ideally, details of temperature distribution from intake to discharge must be predicted to account for the reservoir geometry, discharge condition, and induced flow circulation. Since this is very dif- ficult to do, simplifing assumptions that are typical for these problems are made to find an estimate of the temperature. Accord- ingly, it is assumed that the temperature decays exponentially from discharge to intake, i.e., there exist no vertical and lateral temperature gradients in any cross section along the reservoir. Temperature gradient exists only along the length of the reservoir, decreasing from discharge to the intake. This longitudinal temperature decay depends on the equilibrium temperature T , the flow rate Q, the surface area A, the heat exchange coefficient K, water denisity p and its specific heat Cp. Thus, VTe -r vr6 where r = K^/p^pQ and Tq = T^ + AT Using.approximate expressions for K and Tg given in Reference 2, we have de K = 4.5 + .05 T$ + f(W)(^ + .47) and Te = Td + VK where Td is the dew point temperature and Hs the solar radiation. ------- Calculations are straightforward except for the fact that K is dependent on Ts which can't be calculated without the unknown For this reason initial estimates must be made of Tg and inserted in the equations for K. Corresponding initial estimates are then obtained for the equilibrium temperature Tg and the intake temper- ature Ti. The latter will be used to obtain better values of T$ and K. In this manner, iterations continue until convergence is obtained. Results of such calculations for 700 and 1200 acre ponds are presented respectively in Tables 4 and 5. Lower values of wind speed function [i.e., f^w)] were used in these tables. To compare similar results obtained with the higher value of wind speed function, f2(w), Tables 6 and 7 were prepared. The Sunmary of all results are presented in the next section. VII. Summary and discussion of results 1. The average natural evaporation during seven months, April through October, is 8.1 cfs for a 1200 acre impoundment and 4.7 cfs for a 700 acre impoundment. These translate to 3360 and 1960 acre-feet per year respectively, for 1200 and 700 acre impoundments. If there were no impoundments at all, the average loss for the same period is 0.6 cfs or 250 acre-foot per year. The yearly average is less than the seven month average by a factor of 1.7. See Table 3. 2. The average yearly total evaporation for a 1200 acre impound- ment is at least 12.8 cfs or 9120 acre-foot. See Table 5. 3. The average yearly total evaporation for a 700 acre impound- ment is at least 10.8 cfs or 7730 acre-foot. See Table 4. 6 ------- 4. More conservative estimates of the total evaporation using appropriate wind functions [i.e. f2(w)] are: 11,300 acre-foot (15.8 cfs) and 8500 acre-foot (11.9 cfs) respectively, for 1200 acre and 700 acre reservoirs. These values were obtained indirectly from Tables 7 and 6. Since partial calculations were made in these tables, comparisons were made with corre- sponding months in Tables 5 and 6 and average yearly evapor- ation from these tables was increased proportionally. 5. The above do not include effects of recirculation. It is difficult to say, but recirculation of uncooled water is unlikely to become a problem with the given design. Recircu- lation, if it occurs, will increase evaporation, however. 6. The estimates presented in this report are lower than those presented in Reference 1, making the latter estimates ade- quately conservative. No calculations were performed for sites B and C at this time. 7. Reference 1 did not present documentation of the method used. In this report, such documentation is presented for the method used. Additional calculations can be made, of course, to check new conditions. Detailed water quality models, if available, will provide further refinements of temperature distribution in the reservoir. Considerably more effort is required to achieve a relatively small improvement in the accuracy of the estimates. 7 ------- References 1. Sheppard T. Powell Consultants Limited, C. W., Systems Study for Saskatchewan Power Corporation, Appendix I, undated. 2. Edinger, John E. and Derek K. Brady. 1974. Heat exchange and transport in the environment. Report No. 14, The Johns Hopkins University. ------- Table 1. Meteredogical Data for Coronach, Site A, Data Obtained from Reference 1. January February March April May June July August September October November Dew point °C -16.94 -13.61 -8.06 -2.50 2.78 8.33 11.39 9.72 4.72 0 -7.5 (°F) (1.5) (7.5) (17.5) (27.5) (37) (47) (52.5) (49.5) (40.5) (32) (18.5) Solar radiation Langleys, Hs 128 213 350 425 500 550 600 490 355 227 125 Wind Speed Mph 14.8 14.3 14 14.3 14.4 13 12 12 14 14 14.6 m/s 3.31 3.2 3.13 3.2 3.22 2.91 2.68 2.68 3.13 3.13 3.27 Natural water temperature O C -14.17 -9.72 -3.17 3.61 9.44 15.28 19.17 17.18 12.11 5.56 -3.06 (°F) 6.49 14.50 26.29 38.50 48.99 59.50 66.51 62.92 53.80 42.00 26.49 ------- January fjtW) W^rrmHg"1 14.24 f2(W) W^nmHg"1 27.50 w .0008 e, mmHg .98 a Table 2. Intermediate February March April May 13.91 13.71 15.50 13.97 27.00 26.00 27.00 27.50 .00115 .00185 .003 .0046 1.41 2.26 3.67 5.62 Ca I culations. June July August 13.10 12.05 12.05 25.00 28.00 28.00 .0068 .0082 .0075 8.25 10.02 9.17 September October November 13.71 13.71 14.12 26.00 26.00 27.00 .0053 .0037 .002 6.42 4.75 2.44 ------- Table 3a. Heat loss He* from Water Surface Under Natural Conditions. es mmHg 6.0 9.10 13.30 17.00 15.20 10.90 6.40 He, Wnf2 33.96 45.26 63.19 83.60 78.92 56.84 30.56 '1 ;2 V HeoWnf2 62.91 95.70 126.30 196.40 168.80 116.50 42.90 Table 3b. Yearly Averaged Water Loss CFS.** No Reservoir 700 Acre 1200 Acre 1800 Acre Qe] Qe2 Qe1 Qe2 Qe] Qe2 Qe] Qe2 .18 .35 1.42 2.75 2.44 4.72 3.65 7.08 ~Indices 1 and 2 refer to different methods of calculation as explained in this section. ~~Evaporation rates during seven months are higher than indicated for the yearly average by a factor of 12 * 7 = 1.71. Note that 35.31 CFS = lm^s"^ 1 acre-foot/year = 1.401 x 10~3 CFS ------- Table 4. Calculations for Site A, 700 Acres with Low Values of Wind Speed Function. Wms"^ f^(w) Wm mmHg Hs Wm~^ Td °C w rrmHg T$ °C des/dT mmHgc"^ T °C e T1. °C K Wm"2c_1 e$ mmHg He^ Wm~2 Qe-j CFS January February March April May June July August September October November 3.31 3.20 3.13 3.20 3.22 2.91 2.68 2.68 3.13 3.13 3.27 14.24 13.91 13.71 15.50 13.97 13.10 12.05 12.05 13.71 13.71 14.12 62.00 103.00 169.40 205.70 242.0 266.2 290.4 237.20 171 .80 109.90 60.50 -16.94 -13.61 -8.06 -2.50 2.78 8.33 11.39 9.72 4.72 0 -7.50 .0008 .00115 .00185 .003 .0046 .0068 .0082 .0075 .0053 .0037 .002 .98 1 .41 2.26 3.67 5.62 8.25 10.02 9.17 6.42 4.75 2.44 13.01 15.37 20.33 22.63 27.22 31.45 34.43 34.35 27.32 23.69 17.92 .76 .86 1.12 1.26 1.61 1.98 2.30 2.31 1 .64 1.34 .985 -14.20 -9.28 -1.86 3.84 9.71 15.30 18.72 18.70 9.66 3.60 -5.17 6.49 10.23 14.49 16.86 21.48 25.70 28.58 28.52 21.49 17.75 12.30 22.67 23.77 27.32 32.45 34.92 38.17 39.60 39.72 34.79 30.50 25.94 11.40 13.30 18.00 20.50 27.30 35.00 41.50 41.30 27.50 22.00 15.80 148.38 165.39 215.80 260.87 302.87 350.43 379.33 387.17 289.01 236.50 188.64 6.05 6.75 8.80 10.64 12.36 14.30 15.48 15.80 11.79 9.65 7.70 ------- Table 5. Calculations for Site A, 1200 Acre and Low Values of Wind Speed Function January February March April May June July August September October November Wms-^ 3.31 3.20 3.13 3.20 3.22 2.91 2.68 2.68 3.13 3.13 3.27 f-|Cw) Wm"2mmHg 14.24 13.91 13.71 15.50 13.97 13,10 12.05 12.05 13.71 13.71 14.12 Hs.W/m2 62.00 103.00 169.40 205.70 242.0 266.20 290.40 237.20 171.80 109.90 60.50 T °C .d L -16.94 -13.61 -8.06 -2.50 2.78 8.33 11.39 9.72 4.72 0 -7.50 w .0008 .00115 .00185 .003 .0046 .0068 .0082 .0075 .0053 .0037 .002 mmHg .98 1.41 2.26 3.67 S.62 8.25 10.02 9.17 6.42 4.52 2.44 Tsc °C (1DnH9"'c 5.70 9.45 14.93 18.00 23.08 27.71 30.75 28.65 22.96 18.53 11 .97 des/dT .49 .61 .835 .99 1.30 1.64 1.92 1.73 1.28 1.02 .705 t °r 'd L -13.58 -8.46 -.74 4.84 10.75 16.27 19.73 17.03 10.46 4.27 -4.70 Ti °C -.12 3.62 9.09 12.22 17.25 21.81 24.92 22.88 17.13 12.70 6.13 K WnfV1 18.47 20.00 23.14 28.03 30.38 33.53 34.84 32.44 29.92 25.71 21.62 es mmHg 6.80 8.90 13.00 16.00 21.00 28.00 33.50 30.00 21.00 16.50 10.50 He Wm 2 82.88 104.20 147.25 191.12 214.86 258.73 282.93 251.00 199.89 165.25 113.81 Qe CFS. 5.74 7.28 10.29 13.36 15.06 18.08 19.78 17.55 13.97 11.48 7.96 ------- Table 6. Calculations for Site A, 700 Acre at Highest Values of Wind Speed Function. January February March April June August September October f(W)^ Wm 2mmHg 27.50 27.00 26.00 27.00 25.00 28.00 26.00 26.00 Ts °C 4.91 8.25 13.00 16.86 25.23 24.95 21.39 17.30 des/dT mmHgc"^ .47 .56 .76 .925 T .46 1.42 1.18 .96 Te °C -14.91 -10.46 -3.53 2.28 13.26 13.76 8.26 2.58 Ti °C .83 2.41 7.17 11.02 19.39 19.11 15.55 11.46 K Wm"2c_1 30.60 32.72 37.40 43.01 54.01 58.67 48.47 42.54 esmmHg 6.55 8.15 11.50 14.70 24.50 24.00 19.30 15.30 He Wm'2 153.20 182.00 240.20 297.90 406.25 415.24 334.88 280.28 Qe CFS 6.25 7.42 9.80 12.15 16.97 16.94 13.66 11.43 ------- Table 7. Calculations for Site A, 1200 Acre at Values of Wind Speed Function. High May f^(w) Wm ^mniHg 27.50 T °C s 17.41 des/dT mmHgc"^ .96 T °C e 8.23 T. °C 11.57 -2 -1 K Wm C 44.42 es mmHg 15.30 He^ Wm ^ 266.20 Qe2 CFS 18.61 July November 28.00 27.00 24.22 6.37 1.38 .51 16.44 -5.58 18.39 .54 57.51 31.55 23.00 7.16 363.44 127.44 25.40 8.91 ------- 2.0 1 -8 - 1.6 - 1 - 1.2 - 1 O C_J o> - .8 - .6 - .4 - .2 > 0> "O -40 -30 -20 -10 0 10 20 T = temperature C° dt Figure 1: Saturated vapor pressure es and its gradient 37^- as a function of temperature ------- |