v>EPA
                       United States
                       Environmental Protection
                       Agency
                      Office of Water
                      Washington, D.C.
EPA 832-F-99-041
September 1999
Combined  Sewer Overflow
Management  Fact  Sheet
Sewer  Separation
DESCRIPTION

Sewer systems that convey both sanitary sewage
and storm water through a single pipe are referred
to as combined sewer systems (CSSs).  In dry
weather and during light to moderate rainfall, the
CSS is able to convey all flows to the wastewater
treatment facility. During periods of heavy rainfall,
however, the capacity of the CSS may be exceeded,
often causing untreated combined sewage and storm
water to back up into basements and to overflow
from manholes onto surface streets.  Traditionally,
CSS outfalls were designed to discharge directly
into receiving  waters during  combined  sewer
overflows (CSOs).  This was done to prevent the
excessive combined flows from directly impacting
public health via basement and street flooding.

In addition to flooding problems, CSOs can cause
problems in receiving water bodies.  CSOs can
contain  untreated   domestic,  industrial,   and
commercial wastes,  as well as storm water runoff.
Contaminants contributed by these sources include
potentially high concentrations of suspended solids,
biochemical oxygen demand (BOD), oils and grease,
toxics,  nutrients,  floatables,  pathogenic
microorganisms,  and  other  pollutants.    CSO
pollution has caused many receiving  waters to
exceed water quality standards, resulting in threats
to public health, aquatic species, or aquatic habitat.
CSO pollutants have impaired receiving water body
uses and have contributed to restrictions on shellfish
harvesting,  occasional  fish kills,  and  numerous
beach closures. Potential odors and solids deposits
in the receiving water body can also compromise
aesthetics and limit recreational  uses of the water
body.
                     Many communities have studied and evaluated CSO
                     control strategies that would effectively reduce, if
                     not necessarily eliminate, CSOs and their associated
                     health and ecological risks.  One of the strategies
                     often considered is sewer separation.

                     Sewer separation is  the practice of separating the
                     combined, single pipe system into separate sewers
                     for sanitary and storm water flows.  In a separate
                     system, storm water is conveyed to a storm water
                     outfall for  discharge directly into the receiving
                     water.  Based on a comprehensive  review of a
                     community's sewer system, separating part or all of
                     its combined systems into distinct storm and sanitary
                     sewer systems may be feasible.  Communities that
                     elect for partial separation typically use other CSO
                     controls in the areas that are not  separated.

                     APPLICABILITY

                     Sewer separation can be considered wherever there
                     is  a CSS.  However,  an  evaluation  of the most
                     appropriate CSO control should be performed prior
                     to selecting sewer separation or any other measure.
                     Sewer separation has  often been the appropriate
                     technology  in areas where one or more of the
                     following conditions exist:

                     •     Most sewers are already separated;

                     •     Siting constraints and costs prohibit the use
                           of other structural measures;

                           The uses and the assimilative  capacities of
                           receiving waters prohibit the  use of other
                           CSO controls;

-------
•      Other  CSO  strategies  are not  publicly
       acceptable;

       Additional  infrastructure  improvements,
       such as road repaying, are also required;

•      The combined system is undersized;

•      Elimination of CSOs is desired; and/or

•      Other CSO measures are not able to achieve
       the community's goals.

Sewer separation has been used effectively in many
communities.  Most of the approximately 1,000
communities that are served by CSSs are located in
the  Northeast and  the  Great  Lakes  region.
Complete or  partial  separation  of CSSs  has
occurred in many of these areas, as well as in several
locations in the West. Cities that have completely
or partially separated CSSs include: Minneapolis,
St.  Paul, and South St. Paul,  MN; the  metro
Detroit, MI, area; the metro Boston, MA, area;
Salem and Portland, OR; the metro Seattle, WA,
area; Lynchburg,  VA; Bangor, ME; Hartford and
Norwich, CT; and Remington, IN. Columbus, OH,
has recently elected to separate its CSS as well.

One  of  the largest sewer separation  projects
occurred in  Minneapolis, St. Paul, and  South St.
Paul, MN. The project involved pipe separation in
more than 21,000 acres of drainage area.  By
December 1996,  189 miles of storm sewers and
11.9 miles of sanitary sewers had been installed.
This program was needed to reduce the number of
overflows that were estimated to occur an average
of once  every three days  (American  City  and
County., 1996). Overflows have been significantly
reduced by this separation project.

ADVANTAGES AND DISADVANTAGES

Positive impacts resulting from  sewer  separation
include:  reduction or elimination of basement and
street flooding; reduction or elimination of sanitary
discharges to receiving waters; decreased impacts to
aquatic species and habitat; decreased contact risk
with pathogens and bacteria from domestic sewage
in the receiving water; and relief from  CSO
regulations.  In addition, incidental infrastructure
work (e.g.,  road repaving  and  the repair or
replacement of miscellaneous utilities, such as water
and  cable lines)  could be conducted more  cost
effectively  if it  were  to coincide  with  sewer
separation.  For example, as a result  of the CSO
program in the  City of St. Paul, MN,  streets were
paved and handicap ramps were added to sidewalks,
gas and water mains were installed, gas services
were renewed  or replaced,  lead water  service
connections were replaced, and street lights were
installed.

Separating CSSs may contribute to improvements to
water quality due to the reduction or elimination of
sanitary  discharges to  receiving  water  bodies.
However, the increased storm water discharges
resulting from sewer separation could decrease the
positive  impacts  of the separation unless storm
water discharges are mitigated. Without mitigation,
increased loads of storm water pollutants, including
heavy metals, sediments, and nutrients, may run off
into  local water bodies.  For  example, in Atlanta,
GA,  sewer  separation  was predicted to increase
pollution to local creeks (AMSA, 1994) as polluted
storm water previously reaching the treatment plants
now is  discharged directly into receiving  waters.
However, in many cases, separating sewers reduces
pollution to receiving waters, as described above for
St. Paul, MN.  A second example  of  successfully
reducing pollution to receiving water bodies has
occurred in  Juneau, AK. It has been reported that
in Juneau, where there is in excess  of 70 inches of
precipitation a year, the storm water concentrations
conveyed through the  recently  separated storm
water sewers are rather dilute. This has also been
attributed to large quantities of clean groundwater
that infiltrate into the storm sewer, relatively clean
activities  within  the   watershed,  and   several
non-point source pollution control programs within
the City (City of Juneau, 1997). Existing and future
storm water impacts to the receiving water body
should be evaluated prior to  implementing sewer
separation.

Negative impacts associated with sewer separation
include  extensive  construction and construction
related   impacts   (e.g.,  noise,   dust,  erosion),
disruption to residents  and  businesses, possible
disruptions in sewer service, and the need for storm
water controls or best management practices.

-------
In addition, complete separation  of sanitary  and
storm water flows can  be hard to  accomplish
whether the combined sewer is converted to a storm
sewer or to a sanitary sewer. Complete separation
of a CSS would involve disconnection of all storm
water drainage structures, sump pumps, and roof
and footer drains.  Disconnection of footer drains is
often not cost effective.   Some communities have
offered  financial  incentives to  homeowners  and
businesses  for voluntarily disconnecting  some of
these  storm water sources from sanitary sewers.
Many communities have  also passed ordinances
requiring   the  disconnection.    Despite  these
provisions, there is still  potential  for some storm
water flows to remain connected to sanitary sewers.
Likewise, complete disconnection of sanitary flows
from a converted storm water sewer may be difficult
to accomplish, but is usually more successful than
eliminating  all  storm  flow  connections  from
connected sanitary sewers.

KEY PROGRAM COMPONENTS

Decisions for a CSO control strategy should be
made on a site-by-site basis utilizing drainage area
data, receiving water use and water quality data, and
sewer system data.  Sewer system information can
be obtained from review of sewer plans, television
inspection, and flooding records.  Communities may
consider performing house to house  inventories of
house connections to the combined system (i.e.,
sanitary and roof drains). This was successfully done
in parts of the metropolitan Boston area. Modeling
and Geographical Information Systems (GIS) may
be useful data analysis and prediction tools.

Using these data,  communities should determine
what CSO controls, or combination of controls, will
meet  performance  goals  established  by  the
community.    Other  factors,   such  as  cost
effectiveness, natural and urban topography and soil
types, siting constraints,  location of current  and
future utilities, land use and cover, existing sewer
capacity, layout, and condition, pump and treatment
plant  capacities,  and   requirement  for  other
infrastructure work in the same area, should be
considered before finalizing project plans.   For
example,   sewer   separation  was   selected  in
Minneapolis, South St. Paul, and St. Paul, MN, due
to local needs for eliminating sewage backups into
basements,   reducing   street  flooding,  and
reconstructing aging portions of the sewer system
(MWCC, 1984).

Sewer separation can  be accomplished  through
installing new storm or sanitary sewers to be used in
conjunction with the existing sewer. Economics,
capacity, condition, and  layout of the combined
sewer are the typical factors used in deciding the
existing line's post-separation use.

An advantage of converting the combined sewer to
a sanitary sewer (referred to as a converted sanitary
sewer in this document) is that all sanitary flows are
already  connected to the converted sanitary sewer.
Using the existing combined sewer as the sanitary
sewer and installing a new storm sewer would likely
require  that any overflow weirs, gates, or other
regulating devices  remaining  in  the  converted
sanitary system be bulkheaded or otherwise disabled
to eliminate the potential for sewage to overflow.
In addition, storm water drainage structures, sump
pumps,  and roof drains  must  be disconnected from
the converted sanitary system and connected to the
new storm water sewer.  This will  provide more
capacity in the converted sanitary sewer and will
reduce the possibility of overflows. Building footer
drains, however, are often left connected to the
existing combined system and do consume some of
the   converted   sanitary    sewer   capacity.
Rehabilitation or relining of the converted sanitary
system,  storage tanks,  and/or equalization basins
may be required if infiltration is a  significant
problem due to cracks  or inadequate construction
materials (e.g., brick sewers). In some cases, such
as in Juneau, AK, the existing combined sewer may
be in such poor condition that new sanitary  sewers,
as well as new storm sewers, are constructed.

There are some circumstances that may make the
conversion of the combined sewer to a storm sewer
(referred to  as a  converted  storm  sewer  in this
document)   more  appropriate.    For instance,
combined sewers that have  a large diameter and
have little slope (less than 3 percent) would not
have the flushing velocity required of a  sanitary
sewer. In cases such as this,  the existing CSS may
be more appropriately converted to a storm sewer,
provided that the sewer has sufficient capacity for
safe  conveyance of the  local design storm.   A

-------
smaller  sewer should be appropriately designed,
sized, and constructed to convey the sanitary flows.
Storm,  roof,  and  footer  drains, as  well  as
catchbasins  could   remain  connected  to  the
converted storm  sewer.    Sanitary connections,
however,  would  need to  be disconnected  and
conveyed to the new sanitary line. Any remaining
sanitary lines  connected  to the  converted storm
sewer will cause direct discharges of sanitary flows
to the  receiving water  body.   Post-separation
sampling and monitoring of the converted storm
sewer is typically  required to  confirm  that  all
sanitary  flows have been removed  from  the
converted storm  sewer and redirected into the
sanitary sewer.  Conversion of the combined sewer
to a  storm  sewer  would  also  require that the
interceptor connection at the regulating device (e.g.,
weir or gate) be plugged,  and may potentially
require  modifications  to  prevent water from
stagnating upstream of the regulator.

Consideration  should be  given to coordinating
sewer  separation with improvements  to other
utilities, as this enhances the cost-effectiveness of
both/all  projects and minimizes  disruption to the
public.

IMPLEMENTATION

Sewer separation reduces and  often  eliminates
untreated sanitary discharges from discharging into
receiving water bodies, and therefore positively
impacts receiving water quality. Sewer separation,
however, greatly increases untreated storm water
discharges to the receiving water body. In a CSS,
at least some of the storm water flows are treated at
the treatment plant. The performance achieved with
sewer separation will vary depending on the existing
storm water pollutant loading and the  existing
sanitary pollutant loading.  For example, a study
performed   for  North  Dorchester  Bay, MA,
estimated that the overall  fecal coliform removal
potentially achieved by sewer separation was only
45 percent (Metcalf & Eddy, 1994).  This was
attributed to the increase in storm water discharges
to the receiving water body, and the corresponding
increase in non-point runoff pollutants.

Actual fecal coliform  removal  rates  have been
determined for several sites where sewer separation
has been implemented.  Water quality monitoring
data collected in St. Paul and Minneapolis from
1976   to  1996   indicated  a  fecal  coliform
concentration reduction of 70 percent. One of the
four sites where data was collected reduced fecal
coliform concentrations  from an average  of  500
organisms per 100 mL to 150 organisms per  100
mL. At another site, fecal coliforms were reduced
from 489 organisms per  100 mL to 143 organisms
per 100 mL (Richman, 1996).  This reduction has
been attributed to  sewer separation  and to  the
reduction in the number of overflows occurring
every year.

Sewer  separation may also result in other related
improvements to water quality. In stretches of the
Mississippi, water quality improvements attributed
to sewer separation projects have  resulted in the
return of the pollution-sensitive Hexagenia mayfly
after a 30 year absence; the return of Bald Eagles to
the area; and the recovery of fish populations  and
diversity from 3 species to over 25 species (Cities of
Minneapolis, et. al., 1996).

Monitoring  the  performance of  CSO  control
strategies at the  Rouge  River   Demonstration
Program has been underway since  the summer of
1997. Part of the monitoring program will identify
the effectiveness of sewer  separation  in terms of
improvements  to  water  quality.     Instream
monitoring  is also occurring in Portland, OR.   The
supplemental data will add to the performance data
collected in Minnesota (70 percent fecal coliform
reduction)  and  estimated for  Massachusetts  (45
percent fecal coliform reduction).

OPERATIONS AND MAINTENANCE

The  Operations   and   Maintenance   (O&M
requirements of separated sewers are generally the
same as those of other sewer systems. Maintenance
must be conducted on pump  stations (including
routinely cleaning  wet wells,  testing for adequate
pumping capacity, and  exercising  pumps   and
stand-by generators), sewer lines, and catchbasins
and grit chambers. Catchbasins and grit chambers
located in the sanitary or storm sewer system  will
require routine cleaning to prevent accumulation of
sediment.   Jet spray  cleaning,   pumping,   and

-------
vacuuming  are  common methods for cleaning
catchbasins and grit chambers.

In addition, all sewer lines, and in particular sewers
that  were  previously  combined,  need  to  be
monitored  to verify  hydraulic  capacity and to
identify infiltration and inflow.  Basement or street
flooding is a likely indication of hydraulic capacity
or gradient problems in the sewer and may require
maj or repairs. Excessive infiltration into a converted
sanitary sewer may require rehabilitation of the
sewer system. Methods for assessing the condition
of the sewers include modeling, smoke testing, and
television  inspection.   Monitoring will identify
cracked and collapsed sewers that will need to be
repaired.  In addition, monitoring can identify the
location and cause of sewer blockages. To prevent
blockages, lodged debris, sediment, and grit must be
removed on a regular basis.

Post-separation monitoring and sampling may be
required to ensure that no sanitary flows are still
connected to the storm  sewer and being directly
discharged   to   the   receiving  water  body.
Alternatively, simple dye studies can be employed to
verify separation.

COSTS

Separation costs vary considerably due  to the
location and layout of existing sewers; the location
of other utilities that will have to be avoided during
construction; other infrastructure work that may be
required; land uses and costs; and the construction
method used (e.g., open cut verses microtunneling).
Communities  that  have   other   infrastructure
requirements (such  as road repairs) in addition to
sewer  separation may  find  that  upgrading the
facilities simultaneously can result in a much lower
cost relative to upgrading  them  independently.
Construction occurring  in  existing right-of-ways
would  probably not require land acquisition, and
thus would not  add to the project  cost. Project
costs could increase depending on the land use. For
example,  project  construction occurring in  an
industrial area that contained hazardous materials or
wastes would  likely  increase the project  cost.
Methods of construction, such as the need to tunnel
or bore versus open cutting,  can also add to the
cost.  Project costs  could also  increase if sanitary
equalization basins are required as part of the
separation   project  or  if  storm  water  best
management practices are required to control the
increased storm water discharges to the receiving
water body.

Actual construction costs are available from the St.
Paul sewer  separation  project.   For that project,
sewer  separation costs  ranged  from $8,350/acre
to$40,060/acre,   with  an  average   cost  of
$15,400/acre  (all costs  are  in 1984  dollars).
Estimates from the City of Portland and Detroit are
$18,000/acre and $67,800/acre, respectively.

The Rouge River project has also generated  good
cost data  for sewer  separation.    Costs  were
approximately    $377,000   for   separating
approximately 600 meters  of  pipe on  a  small
residential street (CSO Area 42, Windsor Avenue),
which  included  costs  for  removing  existing
pavement, laying a new sewer line,  and re-paving
and re-sodding. A second project (CSO Area uing
cost $1.3 million to separate approximately 2,600
meters of pipe.  All costs are presented in  1995
dollars.

The cost of operation and maintenance (O&M) of
the separated sewer system is difficult to predict.
Factors contributing to the O&M costs include the
age and the condition of the previously combined
sewer, the length and diameter  of the sewers, the
frequency and the amount of sand and grit removed,
and the size of drainage areas.

Sewer separation can reduce treatment and O&M
costs at the receiving treatment plant by potentially
eliminating storm water flows to the plant.  Energy
costs for transporting flows to the treatment  plant
could also be reduced  due to  the  reduced  flow
volume.
REFERENCES

1.      American City and County, 1996.  "CSO
       Control   Revitalizes   Stretch   of  the
       Mississippi,"  pp. 31-32.

-------
       Association  of Metropolitan  Sewerage
       Agencies  (AMSA), 1994.  Approaches to
       Combined  Sewer   Overflow  Program
       Development. Washington, D.C.

       City and Borough of Juneau, Alaska, 1997.
       Personal Communication with Ernie Mueller
       with the City and Borough of Juneau, Public
       Works.

       Metcalf  &  Eddy,   1994.    Final  CSO
       Conceptual Plan and System Master Plan:
       Part II CSO  Strategies. Prepared for the
       Massachusetts Water Resources Authority.
       Wakefield, MA.

       Metropolitan Waste Control Commission
       (MWCC),   1984.   MWCC  Metro   201
       Facilities Plan. St. Paul, MN.

       Cities of Minneapolis, Saint Paul, South St.
       Paul,   and    Metropolitan  Council
       Environmental Services, 1996. Separating
       Combined Sewers to Improve and Protect
       Mississippi River  Water  Quality:   A
       Ten-Year Commitment. Annual Progress
       Report  to  the  Public  -   Year   Ten.
       Minneapolis,  St. Paul, South St. Paul, MN.

       City of Portland, Oregon, 1997. Personal
       communication with Lester Lee, City of
       Portland.

       Richman, M.,  1996.   "Sewer Separation
       Lowers  Fecal  Coliform  Levels  in  the
       Mississippi River".  Water Environment &
       Technology, Vol. 8, No. 11, pp 20-22.

       Wade-Trim, 1997. Personal communication
       with Laura Crane, Wade-Trim.
Borough and City of Juneau, Alaska
Ernie Mueller
Department of Public Works
5433 Shaune Dr.
Juneau, AK 99801

Michigan City, Indiana, Sanitary District
Tim Haus
532 Franklin Street
Michigan City, IN 463 61

City of New Haven, Connecticut
Raymond Smedberg
Water Pollution Control Authority
345 East Shore Parkway
New Haven, CT 06510

City of Portland, Oregon
Lester Lee
City of Portland Bureau of Environmental Services
1211 Southwest 5th Avenue, Suite 800
Portland, OR  97204

Rouge River Demonstration Project
Vyto Kaunelis
Wayne County Department of Environment
415 Clifford Street, 7th Floor
Detroit, MI 48226

City of Saco, Maine
Larry Nadeau
Department of Public Works
300 Main Street
Saco, ME 04072

City of St. Paul, Minnesota
Mike Kassan
Sewer Utility, Department of Public Works
1000 City Hall Annex
St. Paul, MN  55102
ADDITIONAL INFORMATION

City of Columbus, Ohio
Laurie Mehl
Public Utilities, Division of Sewerage and Drainage
910 Dublin Road, Room 32
Columbus, OH 43215

-------
The mention of trade names or commercial products
does not constitute endorsement or recommendation
for the use by the U.S. Environmental Protection
Agency.
                                                          For more information contact:

                                                          Municipal Technology Branch
                                                          U.S. EPA
                                                          Mail Code 4204
                                                          401 M St., S.W.
                                                         IMTB
                                                         Excelence fh compliance through optimal technical soLtrons^
                                                         MUNICIPAL TECHNOLOGY

-------