ENERGYSTAR
                       ENERGY STAR® Program Requirements for
                                 Residential Light Fixtures
                              Eligibility Criteria - Version 4.2
Section 1: Definitions
                                  Table of Contents
Section 2: Qualifying Products
V
Section 3: Energy Efficiency Specifications for Qualifying Products
V
Section 4: Qualification Process, Testing Facilities, Standards & Documentation
 V
Section 5: Additional Quality Assurance Requirements
VIM
Section 6: Effective Date
 IX
Section 7: Future Specification Revisions
X
Annex A:
       Table 1: Indoor Fixtures
       Table 1A: Additional Requirements for Indoor Recessed Downlight Retrofit Kits
       Table 2A: Outdoor Fixtures: Compliance Through Efficient Light Source
       Table 2B: Outdoor Fixtures: Compliance Through Reduced Operating Time
       Table 3: GU-24 Based Integrated Fluorescent Lamps
       Table 4: Indoor & Outdoor Fixtures Employing LED Light Engines for Primary
             Illumination
 1
 13
 16
 21
 24

 35
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
 ENERGY STAR
ENERGY STAR® Program Requirements for
           Residential Light Fixtures

        Eligibility Criteria -Version 4.2
Below is the product specification (Version 4.2) for ENERGY STAR qualified residential light fixtures and
replacement GU-24 base integrated lamps. A product must meet all of the identified criteria if it is to be
labeled as ENERGY STAR by its manufacturer.

The intent of ENERGY STAR for Residential Light Fixtures is to move consumers from traditional
incandescent fixtures to fixtures that use high-quality fluorescent lamps, light emitting diodes, or other
energy-efficient technologies, including motion-sensors and daylight-sensors for outdoor fixtures.


1) Definitions: Below is a brief definition of a light fixture and other related terms as relevant to ENERGY
   STAR:

   A.    ALA: American Lighting Association.

   B.    ANSI: American National Standards Institute.

   C.    APLAC: Asia Pacific Laboratory Accreditation Cooperation (NVLAP MRA Signatory).

   D.    Automatic Daylight Shutoff: A photosensor device that automatically prevents operation of a fixture
         during daylight hours.

   E.    Ballast: A device used with an electric-discharge lamp to obtain the necessary circuit conditions
         (voltage, current, and waveform) for starting and operating.

   F.    Ballast  Frequency: The frequency at which the ballast operates the lamp, measured in Hertz (Hz)
         orKilohertz(kHz).

   G.    CIE: Commission Internationale de I'Eclairage.

   H.    Color Rendering: The effect that the spectral characteristics of the light emitted by the lamp has on
         the color appearance of the objects illuminated by the lamp. Color Rendering Index is measured
         on a scale of zero to 100, and is defined in terms of a comparison of the spectral tri-stimulus
         values of the objects under test illumination and a reference or standard illumination according to
         the recommendations of CIE Publication No. 13.3.

   I.     Compact Fluorescent Lamp: A single based fluorescent lamp with a plug-in lamp base, including
         multi-tube, multibend, spiral, and circline types.

   J.    Correlated Color Temperature (CCT): The actual color of the lamp is called the color temperature
         and is defined in terms of the spectral tri-stimulus values (color coordinates) according to the
         recommendations of IESNA LM-16. For color coordinates near the Black Body  loci, the correlated
         color temperature, measured in Kelvin  (K), is used.

   K.    Covered Lamp: A lamp with an integral ballast and a translucent cover over the bare fluorescent
         glass tube.

   L.    Electronic Ballast: A ballast that uses semi-conductor components to increase the frequency of
         fluorescent lamp operation.  Fluorescent system efficiency is increased due to the higher
         frequency.

   M.    GU-24  Based  Integrated Lamp: A lamp unit that integrates the lamp and its ballast. It does not
         include any replaceable or interchangeable parts, and utilizes the GU-24 base type.
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
    N.    GU-24 Based Two-Piece Lamp: A term for a lamp-ballast unit that includes a ballast with the GU-
         24 base type paired with a standard pin based lamp. The ballast and lamp are separable, with the
         ballast designed to accept replacement pin based lamps.

    O.    IEC: International Electrotechnical Commission.

    P.    IESNA: Illuminating Engineering Society of North America.

    Q.    I LAC: International Laboratory Accreditation Cooperation (NVLAP MRA Signatory).

    R.    Input Power: The actual total power used by all lamp(s) and ballast(s) of the light fixture during
         operation, as measured in watts (MM).

    S.    Lamp: A generic term for a man-made source of light. By extension, the term is also used to
         denote sources that radiate in regions of the spectrum adjacent to the visible. In lighting parlance,
         the lamp is the replaceable light-generating component of a luminaire, usually a standardized
         element with a standard base, such as a screw base, pin base,  or bayonet base, for mechanical
         and electrical coupling. [From IEEE Dictionary]

    T.    Lamp Ballast Platform: A pairing of one ballast with one or more lamps that can operate
         simultaneously on that ballast. A unique platform is defined by the manufacturer and model
         number of the ballast and lamp(s)  and the quantity of lamps that operate on the ballast. A lamp
         ballast platform also may refer to a lamp with an integral ballast.

    U.    Lamp Current Crest Factor: For 60Hz operation, the ratio of peak lamp current to the root mean
         square (RMS) lamp current. For high-frequency (HF) operation, the highest peak lamp current of
         the modulation envelope (when evaluated over a full line voltage cycle) to the root mean square
         (RMS) of the lamp current.

    V.    Lampholder: A component of a fixture, which supplies power to  the lamp and also holds the lamp
         in place.

    W.   Light Emitting Diode (LED): A pn junction semiconductor device that emits incoherent optical
         radiation when biased in the forward direction. The output is a function of its physical construction,
         material used, and exciting current and may be in the ultraviolet, the visible, or in the infrared
         regions of the spectrum (from IESNA RP-16-05 Addendum a).

    X.    LED Array: An assembly of LED packages, or dies on a printed  circuit board or substrate, possibly
         with optical elements and additional thermal, mechanical, and electrical interfaces that are
         connected to the load side of LED driver.  The LED array does not contain a power source, does
         not include an ANSI standardized  base, and is not connected directly to the branch circuit [from
         IESNA RP-16-05 revision draft, March 2008].

    Y.    LED Control Circuitry: Electronic components located between the power source and the LED
         package (or LED array, LED module) designed to limit voltage and current, to dim, to switch, or
         otherwise control the electrical energy to the LED package (or LED array, LED module).  The
         circuitry does not include a power  source [from IESNA RP-16-05 revision draft, March 2008].

    Z.    LED Driver: A power source with integral  LED control circuitry designed to meet the specific
         requirements of an LED package,  or an LED array, or an LED module, or an LED lamp [from
         IESNA RP-16-05 revision draft, March 2008].

    AA.  LED Light Engine: A subsystem of an LED luminaire that includes one or more LED packages, or
         an LED array, or an LED  module;  an LED driver;  electrical and mechanical interfaces; and an
         integral heat sink to provide thermal dissipation. An LED light engine may be designed to accept
         additional components that provide aesthetic, optical, and environmental control (other than
         thermal dissipation). An LED light  engine  is designed to connect to the branch circuit, [from IESNA
         RP-16-05 revision draft, March 2008].

    BB.  LED Luminaire: A complete LED lighting unit consisting of a light source and driver together with
         parts to distribute light, to position  and protect the light source, and to connect the light source to a
         branch circuit. The light source itself may be an LED package, an LED array, an LED module, or
         an LED lamp. The LED luminaire  is intended  to connect directly to a branch circuit [from IESNA
         RP-16-05 revision draft, March 2008].
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
    CC.  LED Package: An assembly of one or more LED dies that contains wire bond or other type of
         electrical connections, possibly with an optical element and thermal, mechanical, and electrical
         interfaces.  The device does not include a power source, does not include an ANSI standardized
         base, and is not connected directly to the branch circuit. LED package can also be referred to as
         LED component [from IESNA RP-16-05 revision draft, March 2008].

    DD.  LED Platform: (see LED Light Engine definition above)

    EE.  Light Fixture (Luminaire): A complete lighting unit consisting of a lamp or lamps and ballasting
         (when applicable) together with the parts designed to distribute the light, position and protect the
         lamps, and connect the lamps to the power supply.

    FF.  Linear Fluorescent Lamp: A double based fluorescent lamp with a plug-in  lamp base, including
         straight shaped or U-bent types.

    GG.  Magnetic Ballast: A ballast that uses a magnetic core and copper winding  and operates at the
         frequency of the line voltage.

    HH.  MRA: Mutual Recognition Arrangement.

    II.    NAG LA: National Cooperation for Laboratory Accreditation (NVLAP MRA Signatory).

    JJ.   NEMA: National Electrical Manufacturers Association.

    KK.  NFPA: The National Fire Protection Association (United States), which develops the National
         Electrical Code (NEC).

    LL.  NRTL: Nationally Recognized Testing Laboratory as recognized by OSHA's NRTL Program, which
         is a part of OSHA's Directorate of Technical Support.

    MM.  NVLAP: National Voluntary Laboratory Accreditation Program.

    NN.  Optics: Include reflectors, baffles, lenses and/or diffusers, all of which control the light distribution
         and the appearance of the lighted fixture.

    OO.  OSHA: Occupational Safety & Health Administration.

    PP.  Pigtail: A short piece of cable with two connectors on each end for converting between one
         connector type and another; also referred to as a screw-based adapter and socket adapter.

    QQ.  Power Factor: The active power divided by the apparent power (i.e., the product of the rms input
         voltage and rms input current of a ballast).

    RR.  Power Source: A transformer,  power supply, battery, or other device capable of providing current,
         voltage, or power within its design limits. This device contains no additional control capabilities
         [from IESNA RP-16-05 Addendum a].

    SS.  Recessed Downlight Retrofit Kit: A non-linear lighting unit consisting of lamp(s), ballasting,  optics,
         trim, and power supply connection designed to convert an incandescent or halogen type Insulated
         Ceiling (1C) or non-IC recessed downlight into an air-tight fixture that uses an energy-efficient light
         source.

    TT.  Run-up Time: The time needed after switching on the electrical supply for the lamp to reach 80.0%
         of its stabilized luminous flux.

    UU.  Standardized Color Ellipse: An elliptical region of chromaticity coordinates that is defined using a
         centroid, a tilt angle relative to a horizontal  axis, and a defined level of variance. Such a region
         defines what chromaticity coordinates can be acceptably associated with a target Correlated Color
         Temperature. For this specification, standardized color ellipses are defined using centroids based
         upon objective chromaticities (x,y) and tilt angles (e) specified in Table 1 and 2 of ANSI C78.376-
         2001, and a defined variance of seven steps.

    VV.  Trim: Trim is the part of the downlight that covers the ragged edge of the ceiling cut-out. The trim
         may be a separate ring, or trim ring, or it may be integrated with the optics (i.e., a self-flanged
         reflector). Airtight or non-airtight.

    WW. UL: Underwriters Laboratories.
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2                                  IV

-------
2)  Qualifying Products: The ENERGY STAR Residential Light Fixture specification covers the requirements
    for indoor and outdoor light fixtures, recessed downlight retrofit kits and replacement GU-24 base
    integrated lamps intended  primarily for residential type applications. For the purposes of this ENERGY
    STAR specification, residential applications include single-family and multi-family dwellings (such as
    houses and apartments), dormitories, public or military housing, assisted-living facilities, motels and
    hotels, and some light commercial applications.

    Exclusion of magnetic ballasts: Indoor fluorescent fixtures that use magnetic ballasts cannot be
    ENERGY STAR qualified under this Version 4.2 specification. Only outdoor fixtures that use high
    intensity discharge (HID) lamps, such as metal halide and high pressure sodium, may continue to use
    magnetic ballasts.

    Inclusion of decorative LEDs (LED Hybrid Fixtures): LEDs used only as decorative  lighting elements
    in residential lighting fixtures and ceiling fan  light kits are allowed as long as the total wattage of the
    LEDs does not exceed five (5) watts, the average LED system (LED and driver) efficacy is at least 20
    lumens per watt, and the LED is used to supplement a primary light source that meets all  of the
    applicable performance  characteristics outlined in the Eligibility Criteria. This requirement applies to LED
    "hybrid" fixtures. For documentation requirements, please send an email request to RLF@icfi.com.


3)  Energy-Efficiency Specifications for Qualifying Products: Only those products listed in Section 2 that
    meet the criteria provided in Annex A may qualify as ENERGY STAR. Specifications for qualifying
    indoor fixtures can be found in Table 1. Additional specifications for qualifying recessed  downlight
    retrofit kits can be found in Table 1A. Specifications for qualifying outdoor fixtures can be found in
    either  Table 2A - Outdoor Fixtures: Compliance Through Efficient Light Source or Table 2B - Outdoor
    Fixtures: Compliance Through Reduced Operating Time. Specifications for GU-24  based integrated
    lamps used in ENERGY STAR fixtures can  be found in Table 3.  Specifications for  Indoor &  Outdoor
    Fixtures Employing  LED Light Engines for Primary Illumination can be found in Table 4.
4)  Qualification Process, Acceptable Sources of Documentation, Reference Standards & Required
    Documentation :
    The following section describes the steps required to qualify residential light fixtures and replacement
    GU-24 base integrated lamps as  ENERGY STAR, provides information about acceptable sources of
    documentation, and states the testing standards and documentation required for performance
    characteristics.

    Qualification Process:
    To qualify a residential lighting fixture as ENERGY STAR, it must be tested according to the protocol
    outlined below. Note:  EPA reserves the right to require additional documentation, at any time, in
    order to determine compliance with all performance characteristics.

    A. Partner must test qualifying products and obtain required documentation to meet the performance
       characteristics referenced in Annex A of this specification. Refer to the appropriate columns in Tables
       1 through 4 to determine the reference  standard and required documentation applicable to each
       performance characteristic.

       The following stipulations apply:

       •    For multiple fixture models that use the same lamp/ballast combination  or LED  light engine, only
           one set of test results is required. For example, two fixtures that use the same lamp and ballast
           combination or LED light  engine, but have different trim, lens and/or finish need only be tested
           once.
1 EPA may on occasion modify submittal procedures and format. Partners will be notified at the time of these
modifications. For the most current instructions on submitting fixtures to ENERGY STAR, reference the Residential Light
Fixtures Partner Resources page on the ENERGY STAR Web site.
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
      •    For fluorescent fixture models that may use different ballasts (either in terms of the type of
           ballast or manufacturer), each lamp/ballast combination must undergo testing and the test
           results must be submitted for qualification. For example, if a residential light fixture partner plans
           to use ballasts from several manufacturers in any one fixture, the fixture must be tested with
           each manufacturer's ballast.

      •    For fluorescent fixture models with one ballast type that can work with multiple fluorescent lamp
           types, the fixtures need only be tested with one lamp type. The lamp type must either be the one
           supplied with the fixture at shipment or, if a lamp is not supplied, one of the lamp types listed on
           the packaging. Please note that EPA expects all lamps listed on the packaging to comply with
           the specification when operating on the fixture's ballast. To ease the burden on the
           manufacturer, however, test data need be submitted for only one lamp type operating on the
           fixture's ballast.

    B. Electronically submit a completed copy of the ENERGY STAR Residential Light Fixture Qualified
      Product Information (QPI) form, along with required documentation  in the Supplemental Information
      Reporting (SIR) form, to the address listed on the QPI form. To obtain the current version of the QPI
      and SIR forms, visit the "Lighting" section of the ENERGY STAR Web site at
      www.enerqystar.qov/partners, select "Manufacturers," and click on "Qualifying Product Information."

   Acceptable Sources of Documentation:
    A.  A variety of acceptable sources of documentation are referenced for each performance
       characteristic within Tables 1 through 4. For clarity, these sources  are summarized below:

       •   A test report from a laboratory accredited by NVLAP or one of its MRA signatories - Both
           public and  private accredited laboratories may be used. NVLAP's MRA signatory partners
           include ILAC, APLAC, and NACLA. Note that if the laboratory used for the lumen output, CRI,
           CCT, or lamp life test is accredited by NVLAP or one of its MRA signatories, it must also have  a
           scope of accreditation that includes the method of measurement reference standard for this
           performance characteristic. Partners should obtain from the laboratory both its certificate of
           accreditation and  its scope of accreditation and submit them to ENERGY STAR.


       •   An EPA-approved Platform Letter of Approval - These letters are provided from EPA to
           manufacturers who have pre-approved specific performance characteristics for their lamp and/or
           ballast. When using this type of documentation, Partners should  obtain a copy of the  applicable
           letter from the manufacturer and include it with the ENERGY STAR submittal.


       •   EPA-approved documentation from an industry association - In certain instances, EPA has
           approved documentation from industry associations who take responsibility for specific
           performance characteristics of lamps and/or ballasts. When using this type of documentation,
           Partners should contact the industry association to obtain the EPA-approved documentation that
           is required for use with ENERGY STAR submittals. Note: Partners may use the NEMA-ALA
           Lamp and Ballast Matrices as a source for obtaining required information to qualify fixtures using
           compact fluorescent lamps. These matrices can be found at
           http://www.nema.orq/lampballastmatrix/.

       •   A test report from an OSHA NRTL laboratory - Documentation for safety requirements must
           come from an OSHA NRTL laboratory. OSHA NRTL laboratories may also be used to obtain
           certain additional  performance characteristics, as specified in Tables 1 through 4.


       •   Manufacturer documentation - Documentation for certain performance characteristics (such
           as product packaging requirements) may come directly from the  original equipment
           manufacturer.
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2                                 VI

-------
    B.  The information below may be used to locate an accredited testing facility:

       •   For a list of NVLAP accredited laboratories, visit the NVLAP Web site at
           http://www.nist.gov/nvlap or call (301) 975-4016.

       •   For a list of signatories to the ILAC MRA, visit the ILAC Web site at www.ilac.org.

       •   For a list of signatories to the APLAC MRA, visit the APLAC Web site at http://www.aplac.org.

       •   For a list of signatories to the NACLA MRA, visit the NACLA Web site at www.nacla.net.

       •   For a list of accredited OSHA NRTL laboratories, visit http://www.osha.gov/dts/otpca/nrtl/ or call
           (202)693-2110.
       •   For a list of laboratories trained by a representative of the Lighting Research Center (RPI) to
           perform ASSIST Recommends testing procedures, contact EPA.
       •   For a list of laboratories qualified and participating  in the CALiPER program, visit
           http://www.netl.doe.gov/ssl/comm_testing.htm

    C.  Documentation Notes: The list of Documentation Conditions below is referenced in appropriate
       sections of the Annexes.

           [1]  Laboratory test results must be produced  using the specific lamp and ballast that will
               operate in the fixture.

           [2]  Note: If the laboratory used for this test is accredited by NVLAP or one of its MRA
               signatories it must also have a scope of accreditation that includes the method of
               measurement reference standard for this performance characteristic.

           [3]  Laboratory test results must be produced  using the specific lamp that will operate in the
               fixture and either the ballast that will operate in the fixture or a commercially-available ballast
               that meets the applicable ANSI ballast requirements, if applicable, for the light source being
               tested.

           [4]  Manufacturers may obtain ENERGY STAR conditional  qualification for their fixture if all of
               the following items are provided:
                1.  A letter on letterhead from a NVLAP laboratory, one of its MRA signatories, or an ISO
                   9000 registered facility demonstrating lamp life testing has begun.
                2.  A laboratory report proving that testing has been completed for at least 40% of rated
                   life.
                3.  The date for testing completion.

               Conditional approval will only be granted for a  period of no longer than 325 days.
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2                                 VII

-------
           [5]   It is also intended that the fluorescent lamp manufacturer will meet the following quality
               requirements during the production runs of each lamp model:
                1.   The lamp manufacturer is required to maintain color control such that a minimum of
                   90% of the ongoing production (as represented by samples tested from each
                   production shift for the same color and when typically evaluated over 12 month period)
                   will fall within the 7 step Mac Adam color ellipse associated with the designated
                   (manufacturer declared) target color.
                2.   For the purposes of meeting color control, the lamp manufacturer must maintain testing
                   equipment calibrated to international practices and standards and must compile the
                   ongoing color control data in a manner such that it can be easily reviewed upon EPA
                   request.
                3.   At a minimum,  the manufacturer's color quality control program must maintain the
                   following information for a 3-year period:
                   a. Test dates and sample size (minimum of two lamps per production shift)
                   b. Test results (x,y) for each sample lamp measured
                   c. Test results (all x,y data) for sample lamps plotted graphically against the
                      designated 7 step color ellipse  and available for review at least on a quarterly basis
                   d. Records to substantiate that 90 percent of the (x,y) data points fall within the
                      applicable 7 step Mac Adam ellipse.  Manufacturers are  encouraged to exceed this
                      target.

           [6]   Laboratory test results must be produced using the specific ballast that will operate in the
               fixture.

           [7]   A laboratory test report must be submitted upon EPA request.

           [8]   Note: A laboratory test report proving the fixture is dimmable from 100% to 30% must be
               submitted upon EPA request.

           [9]   Manufacturers may  obtain ENERGY STAR conditional qualification if at 40% of rated life, 8
               or more lamps are operational.
               •   Two sample failures, acceptable.
               •   Three sample failures, does not qualify.
               In addition, manufacturers must supply a letter on letterhead from a NVLAP accredited
               laboratory, one of its MRA signatories, or an  ISO 9000 registered facility demonstrating lamp
               life testing has begun and the date of testing completion.  Conditional approval will be
               granted fora period  of no longer than 325 days. Interim and final average rated lifetime tests
               must use the same samples.

           [10]  1,000 hour lumen maintenance and lumen maintenance at 40% of rated life tests must use
               the same samples.

           [11]  Partners must specify if their product contains amalgam mercury during the qualification
               submission process to be eligible for this requirement.

           [12]  Laboratory test results must be produced using each specific fixture that will be qualified.

5)  Additional Quality Assurance Requirements: The following requirements outline a  manufacturer-financed
    quality assurance system that allows for independent evaluation of ENERGY STAR qualified fixtures.
    These requirements went into effect with the Version 4.0 effective date of October 1, 2005. EPA may
    request manufacturers to submit products for quality assurance testing as described below. EPA
    reserves the right to modify these procedures based on experience gained in their implementation. The
    Procedures Manual for this program is available on the ENERGY STAR RLF Partner Resources page
    at: http://www.energystar.gov/index.cfm?c=manuf_res.pt_lighting
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2                                VIM

-------
    For current information on this program and guidelines, reference the most recent version of this Manual
    on the Residential Light Fixtures Partner Resources page on the ENERGY STAR website.


    A.  Quality Assurance Testing (QA4): EPA will select fixtures, platforms, and/or replacement lamps
       each year for quality assurance testing. The manufacturer of each selected product will  be required
       to commission third-party testing of the specified fixture, lamp, or platform by a manufacturer-
       independent testing lab. The testing lab will procure three (3) samples of each fixture or ten (10)
       samples of each platform or replacement lamp on the open market (if possible). Specific testing
       details are outlined in the Procedures Manual.

       Schedule Requirements:
       The manufacturer must retain a qualified third-party testing lab within fourteen (14) business days of
       EPA notification. The laboratory must complete all initial testing (except lumen maintenance, which
       should be started but cannot be completed) within 19 calendar days  of notification of test start date
       to EPA. For fixtures, testing on the first sample must be completed within 311 days of initial
       notification by EPA. If the second and third samples need to be tested, testing needs to  be
       completed within 240 days of failure of the first sample. For platforms or lamps, testing on all ten
       samples must be completed within 311 days of initial notification by EPA.

       For fixtures, if more than one sample fails to meet the same performance parameter of the ENERGY
       STAR specification, the fixture will be addressed under EPA's delisting protocol. For platforms or
       replacement lamps, if more than two out often samples fail to meet the same performance
       parameter of the ENERGY STAR specification, the platform or replacement lamps will be addressed
       under EPA's Standard Operating Procedure (SOP) for Underperforming Components (Lamps,
       Ballasts, or Drivers).

       Note: EPA will select no more than two (2) fixtures, lamp ballast platforms or replacement lamps
       from any given manufacturer per year. Having selected the platform  or replacement lamp, EPA will
       then  proceed with  testing one specific fixture that contains each platform or replacement lamp; or
       initiate the Quality Assurance process on the items.

    B.  Third-Party Complaint Process: Any party who believes that a non-compliant fixture is using the
       ENERGY STAR mark may request that EPA investigate the fixture's compliance. This request must
       be accompanied by laboratory test reports or other evidence indicating that the product  does not
       meet ENERGY STAR requirements. The third-party making the complaint shall remain anonymous
       in all communications between EPA and the manufacturer whose  product is in question.

       EPA will review the materials from the third-party; will notify the manufacturer of the complaint; and,
       if necessary, request a corrective action plan be submitted within seven (7) calendar days. Upon
       receipt and review of the corrective action plan, EPA will take one of the following actions:
         •  Determine that the fixture is eligible to meet the ENERGY STAR requirements, or
         •  Determine that the fixture is not qualified or not eligible to be qualified and either request
            additional information or take steps to remove the fixture from the  ENERGY STAR  Qualified
            Product List for a minimum of six months and/or ensure the manufacturer ceases use of the
            ENERGY STAR mark.

       EPA reserves the  right to terminate any partnership agreements with a manufacturer whose
       products repeatedly violate the specification
6)  Effective Date: The ENERGY STAR Version 4.2 Eligibility Criteria (a.k.a. Specification) for Residential
    Light Fixtures, which represents the addition of test procedures and performance metrics for LED-based
    fixtures shall go into effect on June 2, 2008. Note: as previously announced, requirements specific
    to GU-24 based integrated lamps and the fixtures employing them take effect on August 1, 2008.
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2                                 IX

-------
    A.  Qualifying and Labeling Products under the Version 4.2 Specification: All products, including models
       originally qualified under Versions 4.0 or 4.1 with a date of manufacture on or after June 2, 2008,
       must meet the new Version 4.2 requirements in order to use the ENERGY STAR mark on the
       product, in product literature, on Partner promotional materials, on the Partner's website, or through
       Partner sales channels.  (Note: products qualified under Version 4.1 automatically qualify under
       Version 4.2.)  The date of manufacture  is specific to each unit and is the date (i.e.. month and year)
       on which a unit is considered to be completely assembled.

    B.  Elimination of Automatic Grandfatherinq: EPA does not allow grandfathering under this Version 4.2
       specification.  Therefore,  any product sold, marketed, or identified by the manufacturing partner as
       ENERGY STAR  must meet the current  specification in  effect at that time.

7)  Future Specification  Revisions: ENERGY STAR reserves the right to change the specification should
    technological and/or  market changes affect its usefulness to consumers, industry, or the environment. In
    keeping with current  policy, revisions to the specification will be arrived at through industry discussions.

    While this document  currently refers to test  procedures for fluorescent and compact fluorescent
    technologies, as new technologies emerge that have equal or better performance to the levels proposed
    here, consistent with  a technology neutral approach, EPA may amend the program requirements by
    adding additional  test procedures.

    Expiration of ENERGY STAR Qualification: During future specification revisions EPA may choose to
    require complete  new test data (i.e., test data that has been obtained within the six months prior to
    submitting the fixture for re-qualification) and documentation for all performance characteristics in order
    for a fixture to remain ENERGY STAR qualified. New test data may be required for new, revised and/or
    existing ENERGY STAR performance characteristics.
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                       ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                      Required Documentation
Note: Only electronic ballasts may be used to meet the requirements of this table.  In addition, fixtures that utilize compact fluorescent lamps that do not have a plug-in base (i.e
use a mogul, medium, or other screw base) are not eligible to earn the ENERGY STAR.
Combined Lamp & Ballast Requirements:
System Efficacy

Per Lamp Ballast
Platform in Lumens
Per Watt (LPW)
> 50 LPW for all lamp types below 30
total listed lamp watts.

> 60 LPW for all lamp types that are <
24 inches and > 30 total listed lamp
watts.

> 70 LPW for all lamp types that are >
24 inches and > 30 total listed lamp
watts.
Lamp Requirements:
Lamp Life
For lamps shipped with the fixtures, the
average rated life of the lamp must be >
10,000 hours.

If the lamp is not shipped with the
fixture, product packaging must meet
the requirements set forth in the
"Product Packaging for Consumer
Awareness" section of this Table.
IESNA LM-9; LM-66;
ANSI C82.2
                                                         IESNA LM-40-01; LM-65-01;
                                                         IEC 60091; IEC 60901;
                                                         ANSI C82.1; ANSI C82.11
 Provide:
 1.  a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
 2.  an EPA approved Platform Letter of Qualification that lists the
    lamp/ballast combination used in the fixture and the test result for this
    performance characteristic; or
 3.  EPA-approved documentation from an industry association, such as
    the NEMA/ALA matrices.

 Sample Size: > 3 lamp/ballast combination samples must be tested.

 Passing Test: Two of the three samples must pass in order to qualify for
 ENERGY STAR.

 Conditions: [11, [21
^m
 Provide:
 1.  a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
 2.  an EPA approved Platform Letter of Qualification that lists the
    lamp/ballast combination used in the fixture and the test result for this
    performance characteristic; or
 3.  EPA-approved documentation from an industry association, such as
    the NEMA/ALA matrices; or
 4.  a test report from an  ISO 9000 registered facility.

 Sample Size: > 10 lamps must be tested.

 Passing Test: 50% of the sample set must be functioning at the lifetime
 requirement in order to qualify for ENERGY STAR.

 Conditions: [2], [3], [4]	
         2 Efficacy shall be determined by the following equation:
             Efficacy [Lumens per Watt]  = Measured Lamp Lumens [Lumens]
                                       Measured Input Power [Watts]

             Lamp Lumens: Lamp lumens must be measured using the lamp and ballast that are shipped with the fixture.
             Input Power: Input power must be measured with the lamp and ballast that are shipped with the fixture.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Lumen
Maintenance
For lamps indicated on the fixture
packaging or shipped with the fixtures,
the lamp shall have an average rated
lumen maintenance of at least 80% of
initial lamp lumens at 40% (4,000 hours
minimum) rated lamp life.
IESNALM-40-01; IESNA LM-9-
99; IESNA LM-65-01; IESNA
LM-66-00; ANSI C78.5
Provide:
1.   a test report from a laboratory accredited by NVLAP, one of its MRA
    signatories; or
2.   an EPA approved  Platform Letter of Qualification that lists the
    lamp/ballast combination used in the fixture and the test result for this
    performance characteristic; or
3.   EPA-approved documentation from an industry association, such as
    the NEMA/ALA matrices; or
4.   a test report from an ISO 9000 registered facility.

Sample Size: > 10 lamps must be tested.

Passing Test: > 80%  of the samples must achieve the required lumen
maintenance value in order to qualify for ENERGY STAR.

Conditions: [3]	
Color Rendering
Index
For lamps shipped with the fixtures, the
color rendering index must meet the
following requirements:

> 80 for compact fluorescent lamps.
> 75 for linear fluorescent lamps.

If the lamp is not shipped with the
fixture, product packaging must meet
the requirements set forth in the
"Product Packaging  for Consumer
Awareness" section  of this Table.
IESNA LM-58; CIE 13.3
Provide:
1.   a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
2.   an EPA approved Platform Letter of Qualification that lists the
    lamp/ballast combination used in the fixture and the test result for this
    performance characteristic; or
3.   EPA-approved documentation from an industry association, such as
    the NEMA/ALA matrices.

Sample Size: > 10 lamps must be tested.

Passing Test: > 80% of the samples must achieve the required color
rendering index value in order to qualify for ENERGY STAR.

Conditions: [2],  [3]
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
   Performance
  Characteristic
    ENERGY STAR Requirements
  Methods of Measurement
    Reference Standards
                     Required Documentation
Correlated Color
Temperature
For lamps shipped with the fixtures, the
lamps must have one of the following
designated correlated color
temperatures (CCT): 2700K, 3000K,
3500K, 4100K, 5000K, or6500K.

If the lamp is not shipped with the
fixture, product packaging must meet
the requirements set forth in the
"Product Packaging for Consumer
Awareness" section of this Table.
IESNA LM-58; LM-16
Provide:
1.   a test report from a laboratory accredited by NVLAP, one of its MRA
    signatories; or
2.   an EPA approved  Platform Letter of Qualification that lists the
    lamp/ballast combination used in the fixture and the test result for this
    performance characteristic; or
3.   EPA-approved documentation from an industry association, such as
    the NEMA/ALA matrices; or
4.   a test report from an ISO 9000 registered facility.

Sample Size: > 10 lamps must be tested.

Passing Test: > 90% of the lamps tested fall within a 7-step ANSI Mac
Adam ellipse for the designated CCT in order to qualify for ENERGY STAR.

Conditions: [3],  [5]	
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
   Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Lamp/
Lampholder
Compatibility
For lamps indicated on the fixture
packaging or shipped with the fixtures,
lamps must utilize an ANSI/IEC
standardized lamp base configuration,
as defined by ANSI C81.61 and IEC
60061-1.

The lampholder must be designed to
accept lamps with ANSI/IEC
standardized lamp base configurations
for all applicable wattages. For
example, if the ballast can operate
lamps with multiple wattages (e.g., an
18W, 26W, or 32W lamp) then the
lampholder must be designed to accept
lamps with ANSI/IEC standardized
lamp base configurations for all three
applicable wattages.

In addition, lamps shall either:
    •   Meet the requirements of an
       ANSI/IEC standardized lamp
        specification sheet, as defined
        byANSIC78.901-2001 and
        IEC 60901 (for compact
       fluorescent lamps) or ANSI
        C78.81-2001 and IEC 60081
        (for  linear lamps) if an
        applicable standard exists, or,
    •   If no ANSI/IEC lamp standard
        exists (e.g., a spiral compact
       fluorescent lamp), a custom
        lamp specification sheet must
        be provided at the time of
        submittal. Specific lamp
        characteristics that should be
        included in the lamp
        specification sheet are
        detailed in the Required
        Documentation column.
Lamp Base Configuration:
ANSIC81.61; IEC 60061-1

Lamps Compliant with an ANSI-
IEC Standard (for lamp
dimensions and electrical
parameters):
ANSI C78.901-2001; ANSI
C78.81-2001; IEC 60901; IEC
60081

Lamps Not Compliant with an
ANSI-IEC Standard (for lamp
dimensions and electrical
parameters):
ANSI C78.901-2001; ANSI
C78.81-2001  (used as a
reference for the format and type
of information required on a
custom lamp  specification sheet)
Lamp Base Configuration:
Provide manufacturer data indicating the lamp base type used.

Lamps Compliant with an ANSI-IEC Standard (for lamp dimensions and
electrical parameters): Provide manufacturer data indicating applicable
ANSI-IEC lamp data sheet number.

Lamps Not Compliant with an ANSI-IEC Standard (for lamp dimensions and
electrical parameters): Provide a manufacturer lamp specification sheet that
describes the following (use the ANSI lamp data sheets found in ANSI
C78.901 and C78.81 as a reference for the format and type of information
requested):

1.   Lamp Description, including:
        •  Lamp Model Number
        •  Nominal Wattage
        •  Bulb Designation / Lamp Size (i.e., T4, T5, T8, etc.)
        •  Lamp Base Type as  defined by ANSI C81.61 or IEC 60061-
           1(i.e.,2G13, GR10q, etc.)
        •  Starting Circuit Application (i.e., rapid start, preheat, etc.)
2.   Dimensional Characteristics, including diagram
3.   Lamp Operating Characteristics, including:
        •  Approximate wattage (W)
        •  Voltage( V)
        •  Current (A)
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
  Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Lamp Labeling      For lamps shipped with fixtures, a
Requirement       manufacturer designation that
                   encompasses the lamp manufacturer
                   name, wattage, correlated color
                   temperature, and color rendering index
                   must be labeled on the lamp or lamp
                   base.
Electronic Ballast Requirements
(Note: Magnetic Ballasts May Not Be Used in Indoor Fixtures):
                                     No Standard Available
                                     (Use manufacturer protocol)
                               Provide:
                               A copy of the actual language that will be included on the base of the lamp.
General
Per ANSI C82.11 Section 5 except
paragraph 5.3.1.
ANSIC82.11
No supplemental documentation is required.
Lamp Start Time
The time needed after switching on the
lamp to start continuously and remain
illuminated must be an average of one
second or less.
ANSI C82.11-5.2
Provide:
1.   a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
2.   an EPA approved  Platform Letter of Qualification that lists the
    lamp/ballast combination used in the fixture and the test result for this
    performance characteristic; or
3.   EPA-approved documentation from an industry association, such as
    the NEMA/ALA matrices; or
4.   a test report from an OSHA NRTL laboratory.

Sample Size: > 3 lamp/ballast combination samples must be tested.

Passing Test: Two of the three samples must pass in order to qualify for
ENERGY STAR.

Conditions: [1]	
Power Factor
                    "0.5
                                    ANSIC82.11-3.3.1
                               Provide:
                               1.   a test report from a laboratory accredited by NVLAP or one of its MRA
                                   signatories; or
                               2.   an EPA approved Platform Letter of Qualification that lists the
                                   lamp/ballast combination used in the fixture and the test result for this
                                   performance characteristic; or
                               3.   EPA-approved documentation from an industry association, such as
                                   the NEMA/ALA matrices; or
                               4.   a test report from the manufacturer

                               Sample Size:  > 3 ballast samples must be tested.

                               Passing Test: Two of the three samples must pass in order to qualify for
                               ENERGY STAR.

                               Conditions: [6]	
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
  Performance
  Characteristic
ENERGY STAR Requirements
Methods of Measurement
  Reference Standards
Required Documentation
Lamp Current
Crest Factor
                                 ANSI C82.11-3.3.3 and 5.6
                                 ANSI C82.1-5.6.1
                            Provide:
                            1.   a test report from a laboratory accredited by NVLAP or one of its MRA
                                signatories; or
                            2.   an EPA approved Platform Letter of Qualification that lists the
                                lamp/ballast combination used in the fixture and the test result for this
                                performance characteristic; or
                            3.   EPA-approved documentation from an industry association, such as
                                the NEMA/ALA matrices; or
                            4.   a test report from an OSHA NRTL laboratory.

                            Sample Size:  > 3 ballast samples must be tested.

                            Passing Test: Two of the three samples must pass in order to qualify for
                            ENERGY STAR.

                            Conditions: [6]	
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
Performance
Characteristic
Maximum
Measured Ballast
Case
Temperature
During Normal
Operation Inside
Fixture(s)










Electromagnetic
and Radio
Frequency
Interference
ENERGY STAR Requirements
Not to exceed the ballast manufacturer
maximum recommended ballast case
temperature during normal operation
inside a fixture.

Note: This performance characteristic
is separate and distinct from thermal
requirements established by UL, which
governs safety rather than longevity of
the ballast. All qualified fixtures are
expected to meet this requirement,
including linear, suspended, close-to-
ceiling, 1C, ICAT and Non-IC recessed
canisters, etc. as well as those fixtures
that may be exempt from UL1598.








Ballast must meet FCC requirements
for consumer use (FCC 47 CFR Part 18
Consumer Emission Limits).

Methods of Measurement
Reference Standards
UL1598, Section 11
(Acceptable when the
thermocouple is placed at the
hot-spot location indicated by the
ballast manufacturer.)
-OR-
Lighting Research Center (LRC)
"Proposed Durability Testing
Method: Temperature" available
at
dl
http://www.lrc.rpi.edu/proqrams/li
qhtinqTransformation/pdf/durabili
tvTestinqFinalReport.pdf

Note: All qualified fixtures are
expected to meet the Measured
Maximum Ballast Case
Temperature During Normal
Operation Inside Fixture(s)
requirement. This includes every
qualified fixture including linear,
suspended, close-to-ceiling, 1C,
ICAT and Non-IC recessed
canisters, etc. as well as those
fixtures that may be exempt from
UL1598.
Consumer Limits Per FCC 47
CFR Part 18.305 and 18.307


Required Documentation
Provide: A Temperature Test Report containing all of the following
information:
• Fixture model(s) tested
• Lamp model(s) and ballast model(s) tested
• Measured maximum ballast case temperatures
• Ambient temperature
• Test procedure, including description of fixture installation,
thermocouple location(s), and time that elapsed before readings
were taken.
• Ballast Manufacturer Maximum Recommended Case Temperature
During Normal Operation Inside the Fixture(s)
• Ballast Hot Spot Location Diagram from the ballast manufacturer
The test report may be from:
1. a laboratory accredited by NVLAP or one of its MRA signatories; or
2. an OSHA NRTL laboratory; or
3. the fixture or ballast manufacturer.

Sample Size: 1 fixture must be tested.

Passing Test: Measured temperature at the appropriate ballast case test
point must be less than the manufacturer recommended maximum.

Conditions: Laboratory test results must be produced using the fixture with
the highest operating temperature among all fixtures being qualified, the
specific ballast that will operate in the fixture, and a lamp with the same
wattage and lamp type (e.g., triple-tube, quad tube, spiral) that will operate
in the fixture.
Provide:
No supplemental documentation required.


     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
   Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Ballast Frequency
20 to 33 kHz or > 40 kHz
Oscilloscope instruction manual
Provide:
1.   a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
2.   an EPA approved Platform Letter of Qualification that lists the
    lamp/ballast combination used in the fixture and the test result for this
    performance characteristic; or
3.   EPA-approved documentation from an industry association, such as
    the NEMA/ALA matrices; or
4.   a test report from the manufacturer

Sample Size: > 3 ballast samples must be tested.

Passing Test: Two of the three samples  must pass in order to qualify for
ENERGY STAR.

Conditions: [6]	
Transient
Protection
Per ANSI C82.11b, paragraph 5.10.1
(100kHz Ring Wave, 2.5kV, both
common mode and differential mode, 7
strikes)
ANSI C82.11b, paragraph 5.10.1
Provide:
1.   a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
2.   an EPA approved Platform Letter of Qualification that lists the
    lamp/ballast combination used in the fixture and the test result for this
    performance characteristic; or
3.   EPA-approved documentation from an industry association, such as
    the NEMA/ALA matrices; or
4.   a test report from the manufacturer

Sample Size: > 3 ballast samples must be tested.

Passing Test: AN samples must pass in order to qualify for ENERGY
STAR.

Conditions: [6]	
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                       ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                      Required Documentation
End of Life
Protection
All ballasts that operate lamps sized T5
and smaller must contain an end of life
protection circuit. For ballasts that
operate multiple lamps and are
required to have end of life protection,
the ballast must shut down no more
than two lamps when one of the lamps
has reached end of life.  For example, a
fixture with one ballast and five lamps
must not shut down more than the lamp
that has reached end of life plus one
additional lamp.
IEC 61347-2-3 Amendment 1 to
Edition 1 2004-06 (or ANSI
C82.11-2005, upon its release)
Provide:
For all ballasts that that operate T4 and/or T5 sized lamps, demonstrate that
the ballast is in compliance with the referenced standards by providing:
    1.   a test report from a laboratory accredited by NVLAP or one of its
        MRA signatories; or
    2.   an EPA approved Platform Letter of Qualification that lists the
        lamp/ballast combination used in the fixture and the test result for
        this performance characteristic; or
    3.   EPA-approved documentation from an industry association, such
        as the NEMA/ALA matrices; or
    4.   a test report from the ballast manufacturer

For all ballasts that operate T3 and smaller sized lamps, provide from the
ballast manufacturer a circuit diagram and an accompanying engineering
description outlining the scheme that is used to achieve the end of life
function within the ballast.

Sample Size: > 1 ballast  sample must be tested.

Passing Test: All samples must pass in order to qualify for ENERGY
STAR.

Conditions: [6]	
Dimming
Torchiere style portable fixtures shall
be dimmable from 100% to 30%, or
less, of maximum light output, or be
switchable to three levels of brightness,
not including the off position.

Other fixture types that utilize dimmable
ballasts shall be dimmable from 100%
to 30%, or less, of maximum light
output, or be switchable to three levels
of brightness, not including the off
position.
                                                         No Standard Available
                                                         (Use manufacturer protocol)
                                Provide:
                                A laboratory test report proving the fixture is dimmable from 100% to 30%
                                must be submitted upon EPA request.
Safety - Ballasts
and "Non-Edison
base Fluorescent
Adapters"
The cover page of a safety test report
or a general coverage statement must
be provided to demonstrate compliance
with ANSI/UL 935 or UL 1993, as
appropriate.
ANSI/UL 935 or UL 1993
Provide:
A cover page of a safety test report or a general coverage statement from
an OSHA NRTL laboratory.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                       ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
   Performance
  Characteristic
Fixture Requirements:
    ENERGY STAR Requirements
Fixture Warranty
A written warranty must be included
with fixture packaging at the time of
shipment, which covers repair or
replacement of defective parts of the
fixture housing, optics, trim and
electronics (excluding the lamp) for a
minimum of two years from the date of
purchase.
   Methods of Measurement
     Reference Standards
                                                          No Standard Available
                                                          (Use manufacturer protocol)
                      Required Documentation
                                Provide:
                                A copy of the actual two-year fixture manufacturer written warranty that is
                                included with product packaging.
Noise
Class A sound rating for electronic
ballasts within the fixture, not to exceed
a measured level of 24 dBA (audible)
when the ballast is installed in the
fixture.
Class A sound rating for
electronic ballasts within the
fixture, not to exceed a
measured  level of 24 dBA
(audible) when the ballast is
installed in the fixture and is
measured  using a sound  meter
(similar in performance to B&K
type 2209) where the
microphone is located 12 inches
from the fixture in any direction.
Provide:
Test report upon EPA request.
Lamp Shipment
Requirement
All indoor fixtures must be shipped with
a lamp, except for the following
fluorescent fixture types:
1.   Recessed downlight fixtures and
    recessed downlight retrofit kits
2.   Fixtures using linear fluorescent
    lamps	
No Standard Available
(Use manufacturer protocol)
                                None
Replaceable
Ballast
Ballasts in all fixtures (including
portables) must be accessible and
removable by an electrician without the
cutting of wires and without damage to
the fixture housing, trim, decorative
elements or the carpentry (e.g., ceiling
drywall) to which the fixture is attached.
No Standard Available
(Use manufacturer protocol)
Provide:
A copy of the language that includes guidance on ballast replacement and
states that the ballast is replaceable with the use of a "qualified electrician."
Safety - Portable
Fixtures
The cover page of a safety test report
or a general coverage statement must
be provided to demonstrate compliance
with ANSI/UL 153.
ANSI/UL153
Provide:
The cover page of a safety test report or a general coverage statement from
an OSHA NRTL laboratory.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Safety -
Hardwired
Fixtures
The cover page of a safety test report
or a general coverage statement must
be provided to demonstrate compliance
with UL 1598.
UL1598
Provide:
The cover page of a safety test report or a general coverage statement from
an OSHA NRTL laboratory.
Recessed
Downlight
Fixtures-
Insulation
Contact (IC)-
Rated
Recessed downlight fixtures that are
either IC-Rated for direct contact with
insulation or non IC-Rated may qualify
as ENERGY STAR. For fixtures to be
considered IC-Rated they must be
approved for zero clearance insulation
cover (1C) by an OSHA NRTL
laboratory. Recessed downlight
fixtures that are IC-Rated must also
meet the requirements for air tight
fixtures, listed below.	
Approved for zero clearance
insulation cover (1C) by an
OSHA NRTL laboratory
None
Recessed
Downlight
Fixtures-Air Tight
For Restricted Air
Movement
Recessed downlight fixtures that are
either air tight or not air tight may
qualify as ENERGY STAR. For fixtures
to be considered airtight, the housing
or certified/listed accessory must have
leakage less than 2.0 cubic feet per
minute (CFM) at 75 Pascals (or 1.57
Ibs/ft2) when tested in accordance with
ASTM E283 and shall be sealed with a
gasket or caulk.

For recessed downlight fixtures that are
airtight, the following measures must
be taken to  ensure that fixtures can be
properly installed and inspected:
1.  Product packaging must meet the
    requirements set forth in the
    "Product Packaging for Consumer
    Awareness Requirements" section
    below.
2.  The fixture itself must include a
    label certifying "airtight", or similar
    designation, to show air leakage
    less than 2.0 CFM  at 75  Pascals
    when tested in accordance with
    ASTM E283. The label must be
    clearly visible to a building
    inspector.	
ASTM E283
None
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                       ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                      Required Documentation
                    3.   Installation instructions must be
                        included listing all components of
                        the assembly that will be
                        necessary to ensure an airtight
                        installation and how the
                        components should be properly
                        installed.  For example, depending
                        on the method used to achieve air-
                        tight operation, the instructions
                        should alternatively show how a
                        gasket is to be attached, what type
                        of caulk to use and how it should
                        be applied, or which certified
                        airtight trim kits are designed to be
                        installed with the luminaire
                        housing.	
Product
Packaging for
Consumer
Awareness
Requirements
For fixtures that are not shipped with
lamps, product packaging must include
a list of lamps types that would ensure
ENERGY STAR quality and
performance when paired with the
qualifying fixture. This list must be
clearly visible to the consumer on the
fixture packaging.

Manufacturers are not required to
provide specific lamp manufacturer
names and model numbers on the
packaging. Rather, generic lamp
listings, such as the NEMA or ANSI
generic descriptions including a color
designation (e.g., F32T8/830 or
CFQ26W/G24q/827), will suffice.  In
addition, packaging should suggest that
consumers select a lamp with a rated
life of 10,000 hours or more.  Note:
only recessed downlight fixtures,
recessed downlight retrofit kits, and
fixtures using linear lamps may ship
without a lamp.

For fixtures that are shipped with
lamps, product packaging language is
required that clearly describes the	
No Standard Available
(Use manufacturer protocol)
Provide:
A written copy or a PDF graphic of the language that will be displayed on
product packaging and within the packaging, as required (i.e., installation
instructions for air-tight rated fixtures).
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 1: Indoor Fixtures
  Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
    Reference Standards
                     Required Documentation
                   nominal color designation of the lamp in
                   units of Kelvin (i.e., 2700K, 3000K,
                   3500K, 4100K, 5000K, or6500K).

                   For recessed downliqht fixtures that are
                   IC-Rated, product packaging must
                   clearly state this rating. The language
                   must be clearly visible on the product
                   packaging. The IC-Rated designation
                   will also be included in the fixture
                   description included in the Qualified
                   Product list posted on the ENERGY
                   STAR Web site.  Sample language:
                   "IC-Rated for direct contact with
                   insulation".

                   For recessed downliqht fixtures that are
                   Air-Tight (AT) rated, product packaging
                   must clearly show that the fixture
                   produces less air leakage than 2.0
                   CFM at 75 Pascals when tested in
                   accordance with ASTM E283. The
                   language must be clearly visible on the
                   product packaging. The "airtight", or
                   similar, designation will also be
                   included  in the fixture description
                   included  in the Qualified Product list
                   posted on the ENERGY STAR Web
                   site.  Sample language: "Certified Air
                   Tight per ASTM E283."
Table 1A: Additional Requirements for Indoor Recessed Down light Retrofit Kits
  Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
    Reference Standards
                     Required Documentation
Note: The following ENERGY STAR performance requirements must be met by recessed downlight retrofit kits in addition to those listed in Table 1 - Indoor Fixtures, above.
Combined Lamp & Ballast Requirements:
Reflectors
Reflectors must be included to
maximize fixture efficiency.
No Standard Available
(Use manufacturer protocol)
No supplemental documentation required.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 1A: Additional Requirements for Indoor Recessed Down light Retrofit Kits	
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Aperture
Maximum 7.0"
No Standard Available
(Use manufacturer protocol)
No supplemental documentation required.
Air Tight For
Restricted Air
Movement
Only recessed downlight retrofit kits
that are air tight may qualify as
ENERGY STAR.  For fixtures to be
considered airtight, the housing or
certified/listed accessory must have
leakage less than 2.0 cubic feet per
minute (CFM) at 75 Pascals (or 1.57
Ibs/ft2) when tested in accordance with
ASTM E283 and shall be sealed with a
gasket or caulk.

For recessed downlight retrofit fixtures,
the following measures must be taken
to ensure that fixtures can be properly
installed and inspected:
1.   Product packaging must meet the
    requirements set forth in the
    "Product Packaging for Consumer
    Awareness" section within this
    table, below.
2.   The fixture itself must include a
    label certifying airtight or similar
    designation to show air leakage
    less than 2.0 CFM at 75 Pascals
    when tested in accordance with
    ASTM E283. The label must be
    clearly visible to a building
    inspector.
3.   Installation instructions must be
    included listing all components of
    the assembly that will be
    necessary to ensure an airtight
    installation and how the
    components should be properly
    installed. For example, depending
    on the method used to achieve air-
    tight operation, the instructions
    should alternatively show how a
    gasket is to be attached, what type
    of caulk to use and how it should
    be applied, or which certified	
ASTM E283
Provide:
A test report from:
1.   a laboratory accredited by NVLAP or one of its MRA signatories; or
2.   an OSHA NRTL laboratory; or
3.   the fixture manufacturer.

Sample Size: > 1 sample must be tested.

Passing Test: The sample tested must meet the requirement.

Conditions: [12]
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                       ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 1A: Additional Requirements for Indoor Recessed Down light Retrofit Kits	
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
                        airtight trim kits are designed to be
                        installed with the luminaire
                        housing.
Electrical
Connections
Edison lamp socket with wire "pigtail" to
the ballast.
No Standard Available
(Use manufacturer protocol)
Provide:
An engineering description and/or schematic.
Safety- Fixture
Conversions,
Retrofits
Fixtures must be tested and listed by
an OSHA NRTL laboratory as
acceptable for compliance with NFPA
70, National Electrical Code (NEC).

The cover page of a safety test report
or a general coverage statement must
be provided to demonstrate compliance
with UL 1598 and UL1598B.
UL 1598 and UL1598B
Provide:
The cover page of a safety test report or a general coverage statement from
an OSHA NRTL laboratory.
Product Packaging
for Consumer
Awareness
Requirements
Recessed downlight retrofit kit
packaging and instructions must clearly
indicate:
1.   What fixture model numbers the
    recessed downlight retrofit kits are
    compatible with.
2.   Whether or not the product is
    dimmable. If dimmable, user
    instructions must clearly indicate
    what type of dimming circuit it can
    be used on.
3.   Any known incompatibility with
    photo controls, dimmers or timing
    devices.
4.   Airtight or similar designation to
    show air leakage less than 2.0
    CFM at 75 Pascals when tested in
    accordance with ASTM E283.  The
    language must be clearly visible on
    the product packaging. The "air
    tight," or similar, designation will
    also be included in the fixture
    description included in the
    Qualified Product list posted on the
    ENERGY STAR Web site.  Sample
    language: "Certified Air Tight per
    ASTM E283."
No Standard Available
(Use manufacturer protocol)
Provide:
A written copy or a PDF graphic of the language that will be displayed on
product packaging and within the packaging, as required (i.e., installation
instructions for air-tight rated fixtures).
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 2A: Outdoor Fixtures: Compliance Through Efficient Light Source
   Performance
  Characteristic
   ENERGY STAR Requirements
  Methods of Measurement
    Reference Standards
                     Required Documentation
Note: Only electronic ballasts may be used to meet the requirements of this table with the exception of high intensity discharge lamps, such as metal halide or high pressure
sodium lamps.  In these cases magnetic ballasts can still be used. In addition, fixtures that utilize compact fluorescent lamps that do not have a plug-in base (i.e., use a mogul,
medium, or other screw base) are not eligible to earn the ENERGY STAR. For example, a screw-based compact fluorescent lamp may not be used, though a metal halide lamp
may be used.
 Combined Lamp & Ballast Requirements:
System Efficacy

Per Lamp Ballast
Platform in Lumens
Per Watt (LPW)
> 40 LPW for all lamp types below 15
total listed lamp watts.

> 50 LPW for all lamp types over 15
total listed lamp watts up to 30 total
listed lamp watts

>_60 LPW for all lamp types over 30
total listed lamp watts
Lamp Life
IESNA LM-9; LM-66;
ANSI C82.2
 Lamp Requirements:
For lamps shipped with the fixtures,
the average rated life of the lamp must
be >10,000 hours.

If the lamp is not shipped with the
fixture, product packaging must meet
the requirements set forth in the
"Product Packaging for Consumer
Awareness" section of this Table.
IESNA LM-40-01; LM-65-01;
IEC 60091; IEC 60901; ANSI
C82.1; ANSIC82.11
Provide:
    1.  a test report from a laboratory accredited by NVLAP or one of its
       MRA signatories; or
    2.  an EPA approved Platform Letter of Qualification that lists the
       lamp/ballast combination used in the fixture and the test result for
       this performance characteristic; or
    3.  EPA-approved documentation from an industry association, such
       as the NEMA/ALA matrices.

Sample Size: >  3 lamp/ballast combination samples must be tested.

Passing Test: Two of the three samples must pass in order to qualify for
ENERGY STAR.

 Conditions: [1], [2]
^m
Provide:
    1.  a test report from a laboratory accredited by NVLAP or one of its
       MRA signatories; or
    2.  an EPA approved Platform Letter of Qualification that lists the
       lamp/ballast combination used in the fixture and the test result for
       this performance characteristic; or
    3.  EPA-approved documentation from an industry association, such
       as the NEMA/ALA matrices; or
    4.  a test report from an ISO 9000 registered facility.

Sample Size: >  10 lamps must be tested.

Passing Test: 50% of the sample set must be functioning at the lifetime
requirement in order to qualify for ENERGY STAR.

 Conditions: [2], [3], [4]	
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 2A: Outdoor Fixtures: Compliance Through Efficient Light Source	
  Performance
  Characteristic
  ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
 Lamp/
 Lampholder
 Compatibility
For lamps indicated on the fixture
packaging or shipped with the fixtures,
lamps must utilize an ANSI/IEC
standardized lamp base configuration,
as defined by ANSI C81.61  and IEC
60061-1.

The lampholder must be designed to
accept lamps with ANSI/IEC
standardized lamp base configurations
for all applicable wattages.  For
example, if the ballast can operate
lamps with multiple wattages (e.g., an
18W, 26W, or 32W lamp) then the
lampholder must be designed to
accept lamps with ANSI/IEC
standardized lamp base configurations
for all three applicable wattages.

In addition, lamps shall either:
   •    Meet the requirements of an
       ANSI/IEC standardized lamp
       specification sheet,  as defined
       byANSIC78.901-2001 and
       IEC 60901 (for compact
       fluorescent lamps) or ANSI
       C78.81-2001 and IEC 60081
       (for linear lamps) if an
       applicable standard exists, or,
•   If no ANSI-IEC lamp standard
    exists (e.g., a spiral compact
    fluorescent lamp), a custom lamp
    specification sheet must be
    provided at the time of  submittal.
    Specific lamp and lamp base
    characteristics that should be
    included in the lamp specification
    sheet are detailed in the Required
    Documentation column.
 Ballast Requirements:
 Electromagnetic
 and Radio
 Frequency
 Interference
Ballast must be FCC rated for
consumer use (FCC 47 CFR Part 18
Consumer Emission Limits).
Lamp Base Configuration:
ANSIC81.61; IEC 60061-1

Lamps Compliant with an ANSI-
IEC Standard (for lamp
dimensions and electrical
parameters):
ANSI C78.901-2001; ANSI
C78.81-2001; IEC 60901;  IEC
60081

Lamps Not Compliant with an
ANSI-IEC Standard (for lamp
dimensions and electrical
parameters):
ANSI C78.901-2001; ANSI
C78.81-2001 (used as a
reference for the format and type
of information required on  a
custom lamp specification  sheet)
 Consumer Limits Per FCC 47
 CFR Part 18.305 and 18.307
Lamp Base Configuration:
Provide manufacturer data indicating the lamp base type used.

Lamps Compliant with an ANSI-IEC Standard (for lamp dimensions and
electrical parameters): Provide manufacturer data indicating applicable
ANSI-IEC lamp data sheet number.

Lamps Not Compliant with an ANSI-IEC Standard (for lamp dimensions and
electrical parameters): Provide a manufacturer lamp specification sheet that
describes the following (use the ANSI lamp data sheets found in ANSI
C78.901 and C78.81 as a reference for the format and type of information
requested):

1.   Lamp Description, including:
    •   Lamp Model Number
    •   Nominal Wattage
    •   Bulb Designation / Lamp Size  (i.e., T4, T5, T8, etc.)
    •   Lamp Base Type as defined by ANSI C81.61  or IEC 60061-1(1.e.,
           2G13, GR10q,  etc.)
    •   Starting Circuit Application (i.e., rapid start, preheat, etc.)
2.   Dimensional Characteristics, including diagram
3.   Lamp Operating Characteristics, including:
    •   Approximate wattage (W)
    •   Voltage( V)
    •   Current (A)
Provide:
No supplemental documentation required.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                       ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 2A: Outdoor Fixtures: Compliance Through Efficient Light Source	
   Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                      Required Documentation
End of Life (EOL)
Protection
All ballasts that operate lamps sized
T5 and smaller must contain an end of
life protection circuit, per ANSI/IEC
requirements. For ballasts that
operate multiple lamps and are
required to have end of life protection,
the ballast must shut down no more
than two lamps when one of the lamps
has reached end of life.  For example,
a fixture with one ballast and five
lamps must not shut down more than
the lamp that has reached end of life
plus one additional lamp.
IEC 61347-2-3 Amendment 1 to
Edition 1 2004-06 (or ANSI
C82.11-2005, upon its release)
Provide:
For all ballasts that that operate T4 and/or T5 sized lamps, demonstrate that
the ballast is in compliance with the referenced standards by providing:
    1.   a test report from a laboratory accredited by NVLAP or one of its
        MRA signatories; or
    2.   an EPA approved Platform Letter of Qualification that lists the
        lamp/ballast combination used in the fixture and the test result for
        this performance characteristic; or
    3.   EPA-approved documentation from an industry association, such
        as the NEMA/ALA matrices; or
    4.   a test report from the ballast manufacturer

For all ballasts that operate T3 and smaller sized lamps, provide from the
ballast manufacturer a circuit diagram and an accompanying engineering
description outlining the scheme that is used to achieve the end of life
function within the ballast.

Sample Size: > 1 ballast  sample must be tested.

Passing Test: All samples must pass in order to qualify for ENERGY
STAR.

Conditions: [6]
 Fixture Requirements:
 Maximum Input
 Power
150 watts
 Automatic
 Daylight Shutoff
The fixture must contain an integrated
photosensor that automatically
prevents operation during daylight
hours.  In addition, the control must
automatically reactivate within 24
hours of a manual override or testing
operation.
 No Standard Available
 (Use manufacturer protocol)
 Provide:
 Applicable sections of fixture manual(s) that demonstrate controls exist for
 each fixture being submitted.

 Conditions: [6]
 Fixture Warranty
A written warranty must be included
with fixture packaging at shipment,
which covers repair or replacement of
defective parts of the fixture housing
or electronics (excluding the lamp) for
a minimum of two years from the date
of purchase.	
 No Standard Available
 (Use manufacturer protocol)
 Provide:
 A copy of the actual two-year fixture manufacturer written warranty that is
 included with product packaging.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 2A: Outdoor Fixtures: Compliance Through Efficient Light Source	
  Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Replaceable
Ballast
Ballasts must be accessible to and
removable by an electrician without the
cutting of wires and without damage to
the fixture housing, trim, decorative
elements or the carpentry (e.g. ceiling
drywall) to which the fixture is attached.
No Standard Available
(Use manufacturer protocol)
Provide:
A copy of the language that includes guidance on ballast replacement and
states that the ballast is replaceable with the use of a "qualified electrician."
 Safety
 Fixtures must be compliant with NFPA
 70, the National Electrical Code
 (NEC), including requirements for wet
 or damp locations (Articles 410-4a and
 Article 100).
 NFPA 70, the National
 Electrical Code (NEC),
 including requirements for wet
 locations when applicable
 (Articles 410-4a and Article
 100)	
 Provide:
 The cover page of a safety test report or a general coverage statement
 from an OSHA NRTL laboratory.  Include evidence of a Rain Test for Wet
 Locations, when applicable.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 2A: Outdoor Fixtures: Compliance Through Efficient Light Source
  Performance
  Characteristic
   ENERGY STAR Requirements
  Methods of Measurement
    Reference Standards
                     Required Documentation
 Product
 Packaging for
 Consumer
 Awareness
 Requirements
For fixtures that are not shipped with
lamps, product packaging must
include a list of lamp types that would
provide ENERGY STAR quality and
performance when paired with the
qualifying fixtures. This list must be
clearly visible to the consumer on the
fixture packaging.

Manufacturers are not required to
provide specific lamp manufacturer
names and model numbers on the
packaging. Rather, generic lamp
listings, such as the NEMA or ANSI
generic descriptions including a color
designation (e.g., F32T8/830 or
CFQ26W/G24q/827), will suffice. In
addition, consumers should be
directed to select a lamp with a rated
life of 10,000 hours or more.

Product packaging must indicate the
minimum (lowest) starting temperature
for the lamp and ballast platform of the
fixture.

If the automatic daylight shutoff control
can be adjusted such that the fixture
can operate during full daylight, or
automatic reactivation will not occur
within 24 hours of a manual override
or testing operation, additional
packaging language is required that
provides a range of settings that will
result in the fixture complying with the
specification. The language must be
clearly visible to the consumer on the
fixture packaging and in the fixture
manual. Sample language: "To meet
ENERGY STAR requirements the
photosensor control knob must be set
to x, y, orz to prevent operation during
full daylight."
No Standard Available
(Use manufacturer protocol)
Provide:
A written copy or a PDF graphic of the language that will be displayed on
product packaging and within the packaging, as required (i.e., installation
instructions for air-tight rated fixtures).
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                       ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 2B: Outdoor Fixtures: Compliance Through Reduced Operating Time
   Performance
  Characteristic
   ENERGY STAR Requirements
  Methods of Measurement
    Reference Standards
                     Required Documentation
 Note: All lamp types (fluorescent, incandescent, etc.) may be used to meet the requirements set forth in this table.
Fixture Requirements:
 Maximum Input
 Power
250 watts
 Automatic
 Daylight Shutoff
The fixture must contain an integrated
photosensor that automatically
prevents operation during daylight
hours.  In addition, the control must
automatically reactivate within 24
hours of a manual override or testing
operation.
No Standard Available
(Use manufacturer protocol)
Provide:
Applicable sections of fixture manual(s) that demonstrate controls exist for
each fixture being submitted.

Conditions: [6]
 Motion Control
The fixture must contain an integrated
motion sensor that employs infrared
sensing technology.
The sensor must:
     •   allow automatic shut-off of
         the lamp within 15 minutes
         of being manually activated
         by a switch or automatically
         activated by the sensor, and
     •   automatically reset to
         sensing mode within 24
         hours of a manual override
         or testing operation.
 The fixture must:
     •   have an indicator that visibly
         or audibly informs the device
         operator that the motion
         sensor is operating properly,
         or that it has failed or
         malfunctioned.
No Standard Available
(Use manufacturer protocol)
Provide:
Applicable sections of fixture manual(s) that demonstrate controls exist for
each fixture being submitted.

Conditions: [6]
 Fixture Warranty
A written warranty must be included
with fixture packaging at shipment,
which covers repair or replacement of
defective parts of the fixture housing
or electronics (excluding the lamp) for
a minimum of two years from the date
of purchase.	
No Standard Available
(Use manufacturer protocol)
Provide:
A copy of the actual two-year fixture manufacturer written warranty that is
included with product packaging.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 2B: Outdoor Fixtures: Compliance Through Reduced Operating Time	
  Performance
  Characteristic
   ENERGY STAR Requirements
  Methods of Measurement
    Reference Standards
                    Required Documentation
 Replaceable
 Ballast
If a ballast is present in the fixture, it
must be accessible to and removable
by an electrician without the cutting of
wires and without damage to the
fixture housing, trim, decorative
elements  or the carpentry (e.g., ceiling
drywall) to which the fixture is
attached.
No Standard Available
(Use manufacturer protocol)
Provide:
A copy of the language that includes guidance on ballast replacement and
states that the ballast is replaceable with the use of a "qualified electrician."
 Safety
                    Fixtures must be compliant with NFPA
                    70, the National Electrical Code
                    (NEC), including requirements for wet
                    or damp locations (Articles
                    410-4a and Article 100).	
                                     NFPA 70, the National
                                     Electrical Code (NEC),
                                     including requirements for wet
                                     locations when applicable
                                     (Articles 410-4a and Article
                                     100)	
                               Provide:
                               The cover page of a safety test report or a general coverage statement
                               from an OSHA NRTL laboratory.  Include evidence of a Rain Test for Wet
                               Locations, when applicable.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 2B: Outdoor Fixtures: Compliance Through Reduced Operating Time	
  Performance
  Characteristic
   ENERGY STAR Requirements
  Methods of Measurement
    Reference Standards
                     Required Documentation
 Product
 Packaging for
 Consumer
 Awareness
 Requirements
If the automatic daylight shutoff control
can be adjusted such that the fixture
can operate during full daylight, or
automatic reactivation will not occur
within 24 hours of a manual override
or testing operation, product
packaging  language is required that
provides a range of settings that will
result in the fixture complying with the
specification.  The language must be
clearly visible to the consumer on the
fixture packaging and in the fixture
manual. Sample language: "To meet
ENERGY STAR requirements the
photosensor control knob must be set
to x, y, orz to prevent operation during
full daylight."

If the integrated motion sensor can be
adjusted such that shut-off will not
occur within 15 minutes or automatic
reset to sensing mode will not occur
within 24 hours of a manual override
or testing operation, product
packaging  must provide a range of
settings that will resulting the fixture
complying  with the specification.  The
language must be clearly visible to the
consumer on the fixture packaging
and in the  fixture manual.  Sample
language: "To meet ENERGY STAR
requirements, the motion sensor
control knob must be set to x, y, or z to
allow automatic reset of the sensor". In
addition, the fixture must include
instructions within the packaging that
outlines step-by-step calibration
instructions for the motion sensor.
No Standard Available
(Use manufacturer protocol)
Provide:
A written copy or a PDF graphic of the language that will be displayed on
product packaging and within the packaging, as required (i.e., installation
instructions for air-tight rated fixtures).
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                       ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
Table 3 - GU-24 Based Integrated Fluorescent Lamps
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Note: These requirements supersede requirements in preceding
                                     tables, only for fixtures using GU-24 based integrated lamps.
System Efficacy'

Per Integrated
Lamp in Lumens
Per Watt (LPW)
Bare Lamps:
> 50 LPW for all lamp types below 30
total listed lamp watts.

> 60 LPW for all lamp types that are >
30 total listed lamp watts.
                    Covered, Reflector, and Dimmable
                    Lamps:
                    > 40 LPW for all lamp types and
                    wattages
LM-66-00; ANSI C78.5
Provide:
    1.   a test report from a laboratory accredited by NVLAP or one of its
        MRA signatories; or
    2.   EPA-approved documentation from an industry association.

Sample Size: > 10 samples must be tested for each testing orientation
selected for the submittal.

Passing Test: > 80% of the samples  must achieve the required System
Efficacy value.

Conditions: [2]
Average Rated
Lamp Life
Bare Lamps:
The average rated life of the lamp must
be > 10,000 hours.
                    Covered. Reflector, and Dimmable
                    Lamps:
                    The average rated life of the lamp must
                    be >8,000 hours.
IESNA LM-65-01; ANSI C78.5
Provide:
    1.   a test report from a laboratory accredited by NVLAP or one of its
        MRA signatories; or
    2.   EPA-approved documentation from an industry association; or
    3.   a test report from an ISO 9000 registered facility.

Sample Size: > 10 samples must be tested for each testing orientation
selected for the submittal.

Passing Test: > 50% of the samples  must be functioning at the lifetime
requirement.

Conditions: [2], [9]
1,000-hour Lumen
Maintenance
Must be greater than 90.0% of initial
(100-hour) lumen output at 1,000 hours
of rated life.
IESNA LM-65-01; IESNA LM-66-
00; ANSI C78.5 Section 4.10
Provide:
    1.   a test report from a laboratory accredited by NVLAP or one of its
        MRA signatories; or
    2.   EPA-approved documentation from an industry association; or
      Take performance and electrical measurements at the end of the 100-hour aging period according to ANSI C78.5. The lamp efficacy shall be the average of the total sample size for
     each testing orientation selected for the submittal. Use wattages placed on packaging, not measured wattage, to select proper efficacy category in this table.

     Efficacies are based on measured values for lumens and wattages from pertinent test data. Wattages and lumens placed on packages may not be used in calculation and are not
     governed by this criterion.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 3 - GU-24 Based Integrated Fluorescent Lamps	
   Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
    Reference Standards
                     Required Documentation
Lumen
Maintenance
at 40% of Rated
Life
Must be greater than 80.0% of initial
(100-hour) lumen output at 40% of
rated life.
                                  1.   a test report from an ISO 9000 registered facility.

                              Sample Size: > 10 samples must be tested for each Testing Orientation
                              selected for the submittal.

                              Passing Test: > 80% of the samples must achieve the required lumen
                              maintenance value.

                              Conditions: [2], [10]
Accelerated
Cycling, Thermal,
and Voltage
(ACTV) stress
test
GU-24 must remain functional for
2,880 cycles @ 60°C or 720 cycles at
80 °C
Lighting Research Center (LRC)
Test Method
Laboratory requirements have been determined by LRC and
replication of the equipment and methods is necessary in order to
repeat the tests outside of LRC - this transitional process is
underway.

Sample Size: 5 ^ 10 samples must be tested for each testing orientation
selected for the submittal.

Passing Test: If a sample size of 5 is chosen, then ALL 5 samples must
remain functional for the duration of the test. If a sample size of 10 is used
then 1 sample failure is permitted.
Color Rendering
Index
>80
IESNALM-58; CIE 13.3
Provide:
    1.  a test report from a laboratory accredited by NVLAP or one of its
       MRA signatories; or
    2.  EPA-approved documentation from an industry association.

Sample Size: > 10 samples must be tested for each testing orientation
selected for the submittal.

Passing Test:  > 80% of the samples  must achieve the required color
rendering index value.

Conditions: [2]
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 3 - GU-24 Based Integrated Fluorescent Lamps	
   Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Correlated Color
Temperature
Lamps must have one of the following
designated correlated color
temperatures (CCT): 2700K, 3000K,
3500K, 4100K, 5000K, or6500K.
IESNA LM-58; LM-16
Provide:
    1.  a test report from a laboratory accredited by NVLAP or one of its
       MRA signatories; or
    2.  EPA-approved documentation from an industry association; or
    3.  a test report from an ISO 9000 registered facility.

Sample Size: > 10 samples must be tested for each testing orientation
selected for the submittal.

Passing Test:  > 90% of the samples tested fall within a 7-step ANSI Mac
Adam ellipse for the designated CCT.

Conditions: [5]	
Lamp Base
Lamp Base configuration must utilize
the GU-24 base.
For details see:
http://www.lrc.rpi.edu/qu-24.asp
 (or ANSI GU-24 standard, upon
its release)	
No supplemental documentation is required.
Maximum
Mercury Content
GU-24 Based Integrated Lamps less
than 25 watts:
< 5 milligrams (mg) per lamp

GU-24 Based Integrated Lamps 25 to
40 watts:
< 6 milligrams (mg) per lamp

Partners must ensure that GU-24
based integrated lamps are listed with
NEMA. Lamp manufacturers of GU-24
based integrated lamps seeking
Platform Letters of Approval are
responsible for listing lamps with
NEMA.
NEMA Voluntary Industry
Commitment to Limit Mercury
Content in Self-Ballasted CFLs
Sold in  the U.S.


www.cfl-mercurv.org
Provide:
Reference to lamp manufacturer's commitment form on file with NEMA. In
addition, the product may not be present on the manufacturer's list of non-
conforming products.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 3 - GU-24 Based Integrated Fluorescent Lamps	
   Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Labeling for
Replacement GU-
24 Lamps

(language printed
on integrated lamp
base)
Required lamp labeling language for
consumer replacement must include a
manufacturer designation that
encompasses the following:

    •   lamp manufacturer name
    •   lamp wattage
    •   correlated color temperature
    •   color rendering index

Additional packaging requirements for
mercury content are included in the
Product Packaging and Lamp
Labeling for Consumer Awareness
Requirements, below.
No Standard Available
(Use manufacturer protocol -
optionally, manufacturer may
use the NEMA or ANSI generic
lamp description).
Provide:
A copy of the actual language that is included on the base of the GU-24
product.
General Ballast
Requirement
Integrated lamps are required to meet
the general requirement of ANSI C78.5,
in addition to the specific requirements
listed below.
ANSI C78.5
No supplemental documentation is required.
Lamp Start Time
The time needed after switching on the
lamp to start continuously and remain
illuminated must be one second or less.
ANSI C78.5 Section 4.7, for test
conditions and methodology
Provide:
      1.

      2.
      3.
                                                                                               a test report from a laboratory accredited by NVLAP or one of its
                                                                                               MRA signatories; or
                                                                                               EPA-approved documentation from an industry association; or
                                                                                               a test report from an OSHA NRTL laboratory.
                                                                                      Sample Size:  > 10 samples must be tested for each testing orientation
                                                                                      selected for the submittal.

                                                                                      Passing Test: > 80% of the samples tested must meet the required lamp
                                                                                      start time.
Run-up Time
Non-amalgam:
Average of 10 samples tested must be
less than 1.0 minute per ANSI C78.5,
Section 3.11 and 4.8.
ANSIC78.5, Section 3.11 and
4.8
                   Amalgam:
                   Average of 10 samples tested must be
                   less than 3.0 minutes per ANSI C78.5,
                   clause 3.11 and 4.8.
Provide:
    1.  a test report from a laboratory accredited by NVLAP or one of its
       MRA signatories; or
    2.  EPA-approved documentation from an industry association.

Sample Size: > 10 samples must be tested for each testing orientation
selected for the submittal.

Passing Test:  > 80% of the samples tested must achieve the required run-
up time.

Conditions: [2], [11]
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 3 - GU-24 Based Integrated Fluorescent Lamps	
   Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Power Factor
>0.50
ANSI C82.11-3.3.1
Provide:
1.   a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
2.   EPA-approved documentation from an industry association; or
3.   a test report from the manufacturer.

Sample Size:  > 10 samples must be tested.

Passing Test: > 80% of the samples tested must achieve the required
power factor.	
Electromagnetic
and Radio
Frequency
Interference
Integrated Lamp must meet FCC
requirements for consumer use, FCC
47 CFR Part 2 (Equipment
Authorization) and Part 18 (Consumer
Emission Limits)
FCC 47 CFR Part 2 and Part 18
Provide:
1.   a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
2.   EPA-approved documentation from an industry association; or
3.   a test report from the manufacturer.

Sample Size: 1 samp\e must be tested.

Passing Test: The sample tested must meet the requirement.
Ballast Frequency
20 to 33 kHz or > 40 kHz
Oscilloscope instruction manual
Provide:
1.   a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
2.   EPA-approved documentation from an industry association; or
3.   a test report from the manufacturer.

Sample Size:  > 10 samples must be tested.

Passing Test: > 80% of the samples tested must achieve the required
ballast frequency.	
Transient
Protection
Per ANSI C82.11b, paragraph 5.10.1
(100kHz Ring Wave, 2.5kV, both
common mode and differential mode, 7
strikes)
ANSI C82.11b, paragraph 5.10.1
Provide:
1.   a test report from a laboratory accredited by NVLAP or one of its MRA
    signatories; or
2.   EPA-approved documentation from an industry association; or
3.   a test report from the manufacturer.

Sample Size:  > 5 samples must be tested.

Passing Test: > 90% of the samples tested must meet the 7 strike test
requirement.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 3 - GU-24 Based Integrated Fluorescent Lamps	
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                                                    Required Documentation
End of Life
Protection
All integrated lamps sized T5 and
smaller must provide end-of-life
protection either in the ballast or the
discharge tube itself.
Applicable portions of IEC
61347-2-3 Amendment 1 to
Edition 1 2004-06 or alternate
EPA-approved standard

(Note that upon the inclusion of
integrated CFL lamps in
published UL1993 standards,
EPA will likely approve this
standard for use as a reference)
                               Provide:
                               For all T4 and/or T5 sized integrated lamps, demonstrate that the integrated
                               lamp is in compliance with the referenced standards by providing:

                               1.   a test report from a laboratory accredited by NVLAP or one of its MRA
                                   signatories; or
                               2.   EPA-approved documentation from an industry association; or
                               3.   a test report from the manufacturer.

                               ForT3 and smaller sized integrated lamps, provide from the integrated lamp
                               manufacturer a circuit diagram and an accompanying engineering
                               description outlining the scheme that is used to achieve the end of life
                               function within the integrated lamp.

                               For all lamps, upon release of UL 1993 2nd Edition: A cover page of a safety
                               test report or a general coverage statement from an OSHA NRTL laboratory
                               demonstrating that the integrated lamp is in compliance UL 1993 End of Life
                               testing requirements.

                               Sample Size (for T4 or T5): > 3 samples must be tested.

                               Passing Test (for T4 or T5): All samples must pass.
Safety
Product must comply with the most
current revision of UL1993
UL 1993 (most current revision)
                               Provide:
                               File number for the respective product as listed by the appropriate OSHA
                               NRTL laboratory and one of the following:

                               1.   Letter or statement from an OSHA NRTL facility indicating that the
                                   product meets the requirements of the most current revision of UL1993.
                               2.   Web Link to the manufacturer's listed product at the OSHA NRTL
                                   laboratory that carried out the safety tests.
                               3.   Print out of the OSHA NRTL website showing the listed product.	
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 3 - GU-24 Based Integrated Fluorescent Lamps	
   Performance
  Characteristic
   ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Testing
Orientation
When applying for Platform Letters of
Approval, GU-24 manufacturers must
declare the orientation used for each of
the following requirements:
1.    System Efficacy
2.    Average Rated Lamp Life
3.    1,000-hour Lumen Maintenance
4.    Lumen Maintenance at 40% of
     Rated Life
5.    ACTV Test
6.    Color Rendering Index
7.    Correlated Color Temperature
8.    Lamp Start Time
9.    Run-up Time
The following options will be
presented on Platform Letters of
Approval:
 1.   Base Up
 2.   Base Down
 3.   50% Base Up, 50% Base
     Down
 4.   Horizontal Operation
Provide:
No supplemental documentation required, but a response is mandatory
when submitting a product.

Conditions: [7]
Lamp Warranty
Warranty or limited warranty statement
must cover at least a minimum of 24
months, or 2 years, from date of
purchase based on no less than 3 hour
per day of use.
                                                       No Standard Available
                                                       (Use manufacturer protocol)
                               Provide:
                               A copy of the actual two-year manufacturer written warranty.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 3 - GU-24 Based Integrated Fluorescent Lamps	
   Performance
  Characteristic
    ENERGY STAR Requirements
   Methods of Measurement
     Reference Standards
                     Required Documentation
Product
Packaging and
Lamp Labeling
for Consumer
Awareness
Requirements
Required lamp labeling language for
mercury content must include one (1) of
the following :

    •   the symbol "Hg" within a circle
    •   "Contains Mercury"

Additional information may also be
printed as required by applicable state
laws.
                   Required fixture and fixture packaging
                   language for mercury content must
                   include the following:

                       •   www.epa.gov/bulbrecycling

                   Alternatively, www.lamprecvcle.org
                   may be printed in place of
                   www.epa.gov/bulbrecvcling , so long as
                   a prominent hyperlink to the EPA's web
                   site is maintained on the alternate's
                   home page.
                   Reguired lamp product packaging
                   language for mercury content when
                   lamp is not included with a light fixture
                   must include the following:

                       •   the symbol "Hg" within a circle
                       •   "Contains Mercury"
                       •   www.epa.gov/bulbrecycling

                   Alternatively, www.lamprecycle.org
                   may be printed in place of
                   www.epa.gov/bulbrecvcling , so long as
                   a prominent hyperlink to the EPA's web
                   site is maintained on the alternate's
                   home page.	
No Standard Available
(Use manufacturer protocol)
Provide:
A written copy or a PDF graphic of the language that will be displayed on
lamps and product packaging.
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                      ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 3 - GU-24 Based Integrated Fluorescent Lamps	
  Performance
  Characteristic
ENERGY STAR Requirements
Methods of Measurement
  Reference Standards
Required Documentation
                   Required lamp product packaging
                   language for warranty when lamp is not
                   included with a light fixture:

                   Product packaging must state
                   "Warranty" or "Limited Warranty" and
                   have one of the following for consumer
                   complaint resolution (as applicable):

                       •   A company phone number; or
                       •   mailing address; or
                       •   web site address.
                                 No Standard Available
                                 (Use manufacturer protocol)
                   Reguired lamp product packaging
                   language for FTC labeling reguirements
                   when lamp is not included with a light
                   fixture:

                   ENERGY STAR qualified compact
                   fluorescent lamps and lamp systems
                   must comply with the labeling
                   requirements of the U.S. Federal Trade
                   Commission Packaging Laws - FTC
                   16CFRPart305.1-.19.
                                 FTC 16CFR Part 305.1-.19
                   Reguired lamp product packaging
                   language for starting temperature when
                   lamp is not included with a light fixture:

                   Package must state the minimum
                   starting temperatures or geographic
                   zone of use and any other conditions
                   for reliable starting to meet the starting
                   time requirements of ANSI C78.5,
                   clause 4.8.
                                 ANSI C78.5 clause 4.8
                   Reguired lamp product packaging
                   language for control compatibility when
                   lamp is not included with a light fixture:

                   Lamp package must clearly state any
                   known incompatibility with photo
                   controls, dimmers or timing devices.  In
                   addition, packaging should state
                   specific application exceptions.
                                 No Standard Available
                                 (Use manufacturer protocol)
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                                    ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A

Table 3 - GU-24 Based Integrated Fluorescent Lamps	
  Performance
  Characteristic
ENERGY STAR Requirements
Methods of Measurement
  Reference Standards
Required Documentation
                  Packaging language requirement:

                  Packaging and lamp labeling language
                  must be in English or English with
                  additional languages.

                  For products that will be sold in
                  Canada, packaging must include both
                  English & French.
                                No Standard Available
                                (Use manufacturer protocol)
     ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2

-------
                               ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
                                      This page left intentionally blank for two-sided printing.
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2                                                           34

-------
  ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
         Table 4 - Indoor & Outdoor Fixtures Employing LED Light Engines for Primary Illumination
Performance
Characteristic
ENERGY STAR Requirements
Methods of Measurement
Reference Standards
Note: These requirements apply only to fixtures to be qualified using LED light engines. Recessed canister
fixtures using LED Light Engines are not eligible to earn the ENERGY STAR using these test procedures.
LED Light Engine Requirements
LED Light Engine
Efficacy
Per LED light
engine in lumens
per watt (LPW)
LED Light Engine
Color Rendering
Index (CRI)
Required for indoor
fixtures only.
LED Light Engine
Correlated Color
Temperature
(CCT)
Required for indoor
fixtures only.
LED Light Engine
Maximum
Measured
Driver/Driver
Case
Temperature
(During in situ
Operation)
Lumen
Maintenance
Color Stability
Power Factor
1 ASSIST, May 2008: /
2 Note: EPA understaru
of Solid-State Lighting F
reference LM-79 in futu
3 ASSIST, rev. August
revised2007.pdf.
Note: EPA understant
Sources") to be under d
> 50 LPW for uncovered LED light
engines
> 40 LPM for covered LED light
engines (engines featuring integral
secondary optics)
>75
Light output must meet one of the
following nominal correlated color
temperature (CCT) values: 2700K,
3000K, 3500K, 4000K, 4500K, 5000K,
5700K, 6500K.
Tc not to exceed the LED driver
manufacturer maximum recommended
case temperature when measured
during in situ operation.
Note: This performance characteristic is
separate and distinct from safety
requirements.
Indoor fixtures: > 25,000 hours to
70% Lumen Maintenance (L/o)
Outdoor fixtures: > 35,000 hours to
70% Lumen Maintenance (L/o)
Chromaticity shift for LED packages
overtime shall not exceed 0.007 on the
CIE 1976 (u', v') diagram (corresponds
with a 7-step MacAdam ellipse).
>0.7
ASSIST Recommends:
Recommendations for Testing and
Evaluating White LED Light Engines and
Integrated LED Lamps Used in Decorative
Lighting Luminaires. Vol 4, Issue 1, May
2008. (ASSIST, May 2008) 1'2
ASSIST, May 2008; ANSI C78.377-2008
ASSIST, May 2008; ANSI C78.377-2008
ASSIST, May 2008 (See page 8)
ASSIST Recommends:
LED Life for General Lighting Vol. 1,
February 2005, rev. August 2007 (ASSIST,
rev. August 2007) 3'4
ANSI C82.77
\vailable at httcV/www. Ire. rDi.edu/Droarams/solidstate/assist/Ddf/AR-LEDLiahtEnaine-Mav2008.Ddf.
ds that IESNA LM-79 ("IESNA Approved Method for the Electrical and Photometric Measurements
'roducts") may in the future incorporate LED light engine test procedures; as such EPA may
e revisions of this specification.
2007: Available at httD://www.lrc.rDi.edu/Droarams/solidstate/assist/Ddf/ASSIST-LEDLife-
ds IESNA LM-80 ("/ESAM Approved Method For Measuring Lumen Maintenance of LED Light
eveloDment as of June 2008, and may reference LM-80 in future revisions of this SDecification.
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2
                                                                                                 35

-------
   ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
           Table 4 - Indoor & Outdoor Fixtures Employing LED Light Engines for Primary Illumination
             Performance
             Characteristic
   ENERGY STAR Requirements
       Methods of Measurement
         Reference Standards
           Output Operating
           Frequency
> 120 Hz

Note: This performance characteristic
addresses problems with visible
flicker due to low frequency operation
and applies to steady-state as
well as dimmed operation. Dimming
operation shall meet the
requirement at all light output levels.
Oscilloscope instruction manual
           Noise
Class A sound rating for power supplies
within the fixture, not to exceed a
measured level of 24 dBA (audible)
when the power supplies are installed
in the fixture.
Class A sound rating for power supplies
within the fixture, not to exceed a measured
level of 24 dBA (audible) when the power
supplies are installed in the fixture and are
measured using a sound meter (similar in
performance to B&K type 2209) where the
microphone is located 12 inches from the
fixture in any direction.	
           Transient
           Protection
Power supply shall comply with
ANSI/IEEE C62.41, Class A operation.
The line transient shall consist of seven
strikes of a 100 kHz ring wave,
2.5 kV level, for both common mode
and differential mode.
ANSI/IEEE C62.41
           Electromagnetic
           and Radio
           Frequency
           Interference
Power supplies must meet FCC
requirements for consumer use (FCC
47 CFR Part 15/18 Consumer Emission
Limits)
Consumer Limits per FCC 47 CFR Part
15/18
           Off State Power
           Consumption
Fixtures using integral occupancy
sensors, motion sensors, or
photosensors, or portable fixtures, shall
consume no more than 0.5 watts in the
off state.

All other fixtures shall not consume
power in the off state.

Note:  EPA encourages manufacturers
to comply with requirements outlined in
the ENERGY STAR Program
Requirements for Single Voltage AC-
AC and AC-DC External Power
Supplies.
                                               Fixture Requirements
No Standard Available
(Use manufacturer protocol)
           Minimum
           Operating
           Temperature

           Required for
           Outdoor Fixtures
           Only.	
Fixture shall have a minimum operating
temperature of-20°C or below.
No Standard Available
(Use manufacturer protocol)
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2
                                                                                                                36

-------
   ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
           Table 4 - Indoor & Outdoor Fixtures Employing LED Light Engines for Primary Illumination
             Performance
             Characteristic
           Warranty
           Additional
           Requirements for
           Indoor Fixtures
           Additional
           Requirements for
           Outdoor Fixtures
           Product
           Packaging for
           Consumer
           Awareness
    ENERGY STAR Requirements
A written warranty must be included
with fixture packaging at the time of
shipment, covering repair or
replacement of replaceable defective
electrical parts:

Indoor fixtures: fora minimum of three
years from the date of purchase.

Outdoor fixtures: for a minimum of
four years from the date of purchase.
Indoor fixtures must also meet the
following performance characteristics
outlined in table 1:
    •   Safety - Portable Fixtures
    •   Safety - Hard-Wired Fixtures
Outdoor fixtures must also meet the
following performance characteristics
outlined in table 2A:
    •   Maximum Input Power
    •   Safety
    •   Automatic Daylight Shutoff
        (fixtures >13 watts only)
CCT Labeling:
Product packaging language is required
that clearly describes the nominal color
designation of the LED light engine in
units of Kelvin.

Dimming Capability and Compatibility:
External packaging must state any
known incompatibilities with dimmers,
occupancy or vacancy sensors, timing
devices or any other external lighting
controls. For LED fixtures that are
dimmable, external packaging must
clearly state the percentage range of
dimming,

Minimum Operating Temperature
(outdoor fixtures only):
Product packaging must indicate the
minimum (lowest) starting temperature
of the fixture.
       Methods of Measurement
         Reference Standards
                                                                   No Standard Available
                                                                   (Use manufacturer protocol)
Refer to table 1.
Refer to table 2A.
No Standard Available
(Use manufacturer protocol)
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2
                                                                                                                 37

-------
   ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
           Table 4 - Indoor & Outdoor Fixtures Employing LED Light Engines for Primary Illumination
             Performance
            Characteristic
   ENERGY STAR Requirements
       Methods of Measurement
         Reference Standards
           Product
           Packaging for
           Consumer
           Awareness (con't)
Incandescent Equivalency:
Fixtures incorporating LED light
engines generating < 800 lumens must
clearly state on product packaging the
incandescent light output equivalency
of the LED light engine based on the
table below:
                             Luminous Flux
                             (Lumens)	
                             >40
                             >70
                             >250
                             >450
                  Incandescent
                  Equivalency (W)
                  10
                  25
                  40
                             Example packaging declaration:
                             "This fixture produces light equivalent
                             to a 25 watt incandescent bulb."
No Standard Available
(Use manufacturer protocol)

Note:  EPA seeks to ensure that qualified
fixtures meet consumer expectations for
light output.  Consumer preference for light
output varies widely, and the same is true
for fixture design intent. Therefore it is
impractical to prescribe lumen values for
various residential lighting fixture
applications. This consumer awareness
requirement is intended to help  consumers
understand the limitations of LED  light
engines producing less than 800 lumens
(equivalent to 60 watts incandescent).
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2
                                                                                                               38

-------
   ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2 - ANNEX A
            Table 4 - Indoor & Outdoor Fixtures Employing LED Light Engines for Primary Illumination
             Performance
             Characteristic
                          Required Documentation
             Efficacy
             Color
             Rendering
             Index (CRI)
             Correlated
             Color
             Temperature
             (CCT)
 Provide:
 A test report from a laboratory:
    •   trained by a representative of the Lighting Research Center (RPI) on behalf of
        the Alliance for Solid-State Illumination Systems and Technologies (ASSIST);
        or
    •   qualified to participate in the Department of Energy's CALiPER program.

 Note: Upon availability of NVLAP accreditation for LED test methods, EPA will
 investigate test procedures under the proposed NVLAP scope and evaluate for
 inclusion here as an additional test report option.

 Sample Size:
    •   1 complete fixture sample (light engine installed); and
    •   2 additional light engine samples external to fixture;  and
    •   Any components and/or materials required to install  additional LED light
	engines in fixture.	
            • Lumen
             Maintenance
            • Color Stability
 Provide:
        Lumen maintenance and color stability data declared by LED package
        manufacturer, in accordance with ASSIST Sample Data Sheet for High-Power
        LEDs (Issue 4); or
        LED package datasheets conforming to IESNA LM-80 protocols, once the
        metric is available.
              Maximum
              Measured
              Driver/Driver
              Case
              Temperature
              Power Factor
              Transient
              Protection
 Provide:
    •   Laboratory test report

 Sample Size:
    •   One light engine sample must be tested.
           Warranty
 Provide:
 A copy of the actual fixture manufacturer written warranty that is included with product
 packaging.	
           Additional
           Requirements for
           Indoor Fixtures
 Refer to table 1.
           Additional
           Requirements for
           Outdoor Fixtures
 Refer to table 2A.
           Product
           Packaging for
           Consumer
           Awareness
 Provide:
 A written copy or a PDF graphic of the language that will be displayed on product
 packaging, and within the packaging as required (e.g., installation instructions for air-
 tight rated fixtures).

 If product is marketed as dimmable, a copy of the language that includes dimming
 range and known lighting control incompatibilities.	
ENERGY STAR Program Requirements for Residential Light Fixtures: Version 4.2
                                                                                                                 39

-------