Evaluation of Savings from the Application
of Adsil™ in the NC/SC Charlotte Area
                        EPA

-------

-------
                                                 EPA-453/R-05-003
                                                    November 2004
          Evaluation of Savings from the
           Application of Adsil™ in the
              NC/SC Charlotte Area
                      By:
                   MACTEC
                  Prepared By
              404 SW 140th Terrace
               Gainesville, Florida
                  Prepared for:
               Melissa McCullough
    Office of Air Quality Planning and Standards
           Contract No. 4D-6453-NTLX
       U.S. Environmental Protection Agency
Information Transfer and Program Integration Division
    Office of Air Quality Planning and Standards
                    RTF, NC

-------

-------
                                                     Application ofAdsil in the NC/SC Charlotte Area
                               Table of Contents

1. Introduction and Project Objectives	1-1
2. Description of Tasks	2-1
3. EER Measurement Procedures	3-1
    3.1  Spreadsheet Calculation	3-1
    3.2  Condenser Measurement	3-3
    3.3  Service Assistant Measurements	3-3
4. Testing Procedure Repeatability and Accuracy	4-1
5. Measurements in EER	5-1
6. Projected Energy Savings	5-1
7. Estimated Degradation in HVAC Performance	7-1
8. Statistical Significance	8-1
9. Summary of Results and Conclusions	9-1
10. Recommendations	10-1
List of Appendices

Appendix A   List of Facilities for Adsil Application
Appendix B   Residential Five-Ton Split-System Results
Appendix C   Commercial Five-Ton Heat Pump Results
Appendix D   Eckerd's Study
Appendix E   Service Assistant Information
Appendix F   EER Test Data from Units in SEQL Area
Appendix G   Energy Savings Calculations
Appendix H   Spreadsheet Prediction of Degradation
Appendix I    Statistical Model
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                                                             MACTEC

-------
                                                     Application ofAdsil in the NC/SC Charlotte Area
                         Table of Contents (continued)
List of Tables
Table 4-1.     Unit 1 Baseline Study
              Generic Compressor Test Summary-All Temperatures	4-6
Table 4-2.     Unit 1 Baseline Study
              Generic Compressor Test Summary at Ambient 85 Degrees or Higher	4-7
Table 4-3.     Unit 1 Baseline Study
              Copeland Compressor Test Summary-All Temperatures	4-12
Table 4-4.     Unit 1 Baseline Study
              Copeland Compressor Test Summary at Ambient 85 Degrees or Higher	4-15
Table 4-5.     Unit 2 Baseline Study
              Generic Compressor Test Summary All Temperatures	4-26
Table 5-1.     Summary of All Tests at All Temperatures	5-4
Table 5-2.     Summary of Valid Tests at All  Temperatures	5-5
Table 5-3.     Summary of Valid Tests at Literature Temperatures	5-6



List of Figures

Figure 3-1.    Pre-Adsil HVAC Spreadsheet	3-2
Figure 4-1.    Unit 1 Baseline Study
              HVAC Data Sheet and EER Calculation at ARI Conditions	4-2
Figure 4-2.    Unit 1 Baseline Study
              Power Consumption versus OAT, All Temperatures	4-4
Figure 4-3.    Unit 1 Baseline Study
              Power Consumption versus OAT, Temps above 85 Degrees	4-4
Figure 4-4.    Unit 1 Baseline Study
              Condenser EER versus OAT, All Temperatures	4-5
Figure 4-5.    Unit 1 Baseline Study
              Condenser EER versus OAT, Temps above 85 Degrees	4-5
Figure 4-6.    Unit 1 Baseline Study
              Generic Compressor EER versus OAT, All Temperatures	4-9
Figure 4-7.    Unit 1 Baseline Study
              Generic Compressor EER versus OAT at 85 Degrees or Higher	4-9
Figure 4-8.    Unit 1 Baseline Study
              Copeland Compressor EER versus OAT, All Temperatures	4-10
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                                                              MACTEC

-------
                                                       Application ofAdsil in the NC/SC Charlotte Area
                         Table of Contents (continued)

List of Figures (continued)

Figure 4-9.    Unit 1 Baseline Study
              Copeland Compressor EER versus OAT(SA) at 85 Degrees or Higher	4-10
Figure 4-10.   Unit 1 Baseline Study
              Change in EER after Adsil Treatment, All Temperatures	4-11
Figure 4-11.   Unit 1 Baseline Study
              Change in EER after Adsil Treatment, Temperatures Above 85 Degrees	4-11
Figure 4-12.   Unit 1 Baseline Study
              Efficiency Index versus OAT for Pre-Adsil Tests, All Temperatures	4-17
Figure 4-13.   Unit 1 Baseline Study
              Efficiency Index versus OAT for Post-Adsil Tests, All Temperatures	4-17
Figure 4-14.   Unit 1 Baseline Study
              Efficiency Index versus OAT for Pre-  & Post-Adsil Tests,
              Temps Above 85 F	4-18
Figure 4-15.   Unit 2 Baseline Study
              HVAC Data Sheet and EER Calculation at ARI Conditions	4-19
Figure 4-16.   Unit 2 Baseline Study
              Power Consumption versus OAT, All Temperatures	4-20
Figure 4-17.   Unit 2 Baseline Study
              Condenser EER Test versus OAT, All Temperatures	4-22
Figure 4-18.   Unit 2 Baseline Study
              Generic Compressor EER versus OAT, All Temperatures	4-22
Figure 4-19.   Unit 2 Baseline Study
              Change in EER after Adsil Treatment, All Temperatures	4-23
Figure 4-20.   Unit 2 Baseline Study
              Efficiency Index versus OAT for Pre-Adsil Tests, All Temperatures	4-23
Figure 5-1.    Service Assistant, Valid Tests at Literature Temperatures	5-8
Figure 6-1.    Energy Savings Projection Tool	6-2
Figure 7-1.    Degradation Prediction Tool	7-2
Figure 7-2.    Degradation of Units Compared with Age Weighted Average, Literature
              Valid Tests	7-4
Figure 7-3.    Visual versus Service Assistant Degradation, Literature Valid Tests	7-4
Figure 7-4.    Degradation of Unit versus Fin Condition Weighted Average, All Literature
              Valid Tests	7-5
Figure 7-5.    Degradation of Unit versus Dirt Factor Weighted Average, Literature
              Valid Tests	7-5
P:\EEGVEnergy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc     111                                    MACTEC

-------
                                                       Application ofAdsil in the NC/SC Charlotte Area
                          Table of Contents (continued)

List of Figures (continued)

Figure 7-6.     Degradation of Unit versus Corrosion Weighted Average, Literature
               Valid Tests	7-6
Figure 7-7.     Degradation of Unit versus Capacity Weighted Average, Literature
               Valid Tests	7-6
Figure 7-8.     Degradation of Unit versus Capacity Weighted Average, All Literature
               Valid Tests	7-5
List of Acronyms and Abbreviations

A/C       air conditioner
ASHRAE  American Society of Heating, Refrigeration, and Air-Conditioning Engineers
CDD       cooling degree days
cfm       cubic feet per minute
CO2       carbon dioxide
COG       Councils of Government
EER       energy efficiency ratio
El         efficiency index
EPA       United States Environmental Protection Agency
FLEOH    Full Load Equivalent Operating Hours
HVAC     heating, ventilating and air conditioning
kg/sec     kilogram per second
kWh       kilowatt-hours
MACTEC  MACTEC Engineering and Consulting, Inc.
NOAA     National Oceanic and Atmospheric Administration
NOx       nitrogen oxide
OAT       outdoor air temperature
PDA       personal digital assistant
SEQL     Sustainable Environment for Quality of Life
SO2       sulfur dioxide
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc      IV                                    MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
                                Executive Summary

The SEQL Project (Sustainable Environment for Quality of Life, www.seql.org ) is an integrated
environmental improvement project in a 15-county North Carolina/South Carolina region
surrounding Charlotte, NC. One aspect of this project is to explore using energy efficiency to
benefit air quality. The SEQL desired to evaluate a new coating, Adsil, which previous studies
have shown that, when applied to evaporators, condensers and fans of an air conditioner (A/C)
unit, can bring the efficiency of that unit virtually back to that of a new unit, as well as prevent
age-related efficiency loss due to the deterioration of heat transfer surfaces, saving both electrical
power and early replacement costs. The ability to model expected energy savings with
widespread use ofAdsil in various types of locations (in relation to corrosive and fouling
influences) would be beneficial and transferable to other communities nationwide.  Energy
savings reduce costs, limit the need for new generating capacity, and could under certain
circumstances benefit air quality.  However, quantifiable air quality benefits would depend on the
amount of energy savings and the extent to which, and where, fossil fuel-fired power plants
reduced emissions as a result of those energy savings.

In order to further evaluate this opportunity, the  United States Environmental Protection Agency
(EPA), working with SEQL, competitively selected an engineering firm, MACTEC Engineering
and Consulting, Inc. (MACTEC) to conduct a pilot program. This pilot was required to evaluate
the possible energy-related benefits of coating A/C units in the SEQL area with Adsil and to
provide a method to predict the energy savings from similar applications on a widespread basis
elsewhere. The total tonnage of air conditioning units included in this study is approximately
2,500 tons.

There were three primary objectives for this project:

    1.   Provide the EPA with a spreadsheet-based calculation methodology to accurately predict
        the degradation in energy efficiency ratio (EER) for air-cooled heating, ventilating and
        air conditioning (HVAC) equipment coils;
    2.   Document the EER improvement for air-cooled HVAC equipment cleaned and coated
        with Adsil cleansers and coatings; and
    3.   Provide a tool for estimating the energy savings for an HVAC unit cleaned and coated
        using this protocol.

MACTEC evaluated the impact ofAdsil application to 45 HVAC units in the SEQL area and to
three units outside the  SEQL area. The results of this evaluation show that the Adsil
treatment can be expected to improve the efficiency of existing HVAC units by
approximately 12% based on the ton-weighted average method used in this project.  The
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc      V                                    MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
data was statistically evaluated and determined to be significant at the 99% confidence
level.

Utility bill analysis was determined to be an inappropriate measurement tool for EER changes
and therefore actual efficiency measurements for each HVAC unit were performed.  Three tests
were used including a calculation method, a power and capacity measurement, and a refrigerant-
based measurement using the Service Assistant as available from Honeywell Controls.

Two baseline studies were conducted to establish the accuracy of each testing protocol and which
involved repeated tests on two units.  Repeatability in measurements was demonstrated in these
tests and it was determined that the Service Assistant instrument provided the most repeatable and
accurate measurements of HVAC EER. The generic compressor curve used for many of the
SEQL area tests was found to underestimate the actual savings demonstrated in the pilot baseline
study tests. The condenser test methodology was generally less accurate but showed greater
increases in EER as a result of the  Adsil treatment.

A degradation prediction tool for HVAC units was created in this pilot program.  This
spreadsheet-based tool was calibrated against actual EER measurements and was found to be very
accurate in predicting the EER degradation of a population of HVAC units in the SEQL area.

An energy savings projection tool was also created based on the results of this study. This tool
can be easily adapted by facility owners and operators to estimate their energy savings, dollar
savings, and avoided pollution emissions as a result of the application ofAdsil to air-cooled
HVAC equipment. This tool estimates that annual dollar savings for the 150 units coated  in the
SEQL area will exceed $37,000  based on a blended electric rate of $0.08 perkWh..

MACTEC believes that this product demonstrated significant savings  for air-cooled  HVAC
equipment.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc     VI                                     MACTEC

-------
                                                         Application ofAdsil in the NC/SC Charlotte Area
                    1.   Introduction and Project Objectives

The SEQL Project (Sustainable Environment for Quality of Life) is an integrated environmental
improvement project in the North Carolina/South Carolina region surrounding Charlotte, NC.
This project is led by the region's Councils of Government (COGs) —the Centralina COG on the
NC side of the border and the Catawba COG on the SC side. One aspect of this project is to use
energy efficiency to benefit air quality.
The SEQL desired to evaluate a new coating, Adsil, which when applied to evaporators,
condensers and fans of an air conditioner (A/C) unit, can bring the efficiency of that unit virtually
back to that of a new unit, as well as prevent age-related efficiency loss due to the deterioration of
heat transfer surfaces, saving both electrical power and early replacement costs. This coating has
been well tested for this benefit in other climactic areas, including the Naval Air Station in
Jacksonville, FL. The increases in unit efficiency in these tests has been well documented (this
documentation is available at www.adsil.com). The ability to model expected energy savings with
widespread use ofAdsil in various types of locations (in relation to corrosive and fouling
influences) would be beneficial and transferable to other communities nationwide. Energy
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                            1-1
                                                                                   MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
savings reduce costs, limit the need for new generating capacity, and could be used in some areas
to benefit air quality. However, quantifiable air quality benefits would depend on where and
what kind of plants changed power production as a result of energy savings.

In order to further evaluate this opportunity, the United States Environmental Protection Agency
(EPA), working with SEQL, competitively selected an engineering firm, MACTEC Engineering
and Consulting, Inc. (MACTEC) to conduct a pilot program. This pilot was required to evaluate
the possible energy-related benefits of coating A/C units in the SEQL area with Adsil and to
provide a method to predict the energy savings from similar applications on a widespread basis
elsewhere. To develop a prediction model, additional data was required to be collected to
supplement existing data. For example, to evaluate possible benefits, EPA required data to be
collected on the degradation curve of A/C units related to pollution and other corrosive or fouling
influences. This included data collection for units besides those being coated. This pilot, funded
by the US EPA, was to include as many as 30 buildings' units and be completed by September of
2004. The preliminary list of buildings/units is shown in Table A-l in Appendix A for
information purposes. The total tonnage of air conditioning units included in this study is
approximately 2,500 tons.

Project Objectives

There were three primary objectives for this project:

    1.  Provide the EPA with a spreadsheet-based calculation methodology to accurately predict
       the degradation in energy efficiency ratio (EER) for air-cooled heating, ventilating and
       air conditioning (HVAC) equipment coils;
    2.  Document the EER improvement  for air-cooled HVAC equipment cleaned and coated
       with Adsil cleansers and coatings; and
    3.  Provide a tool for estimating the energy savings for an HVAC unit cleaned and coated
       using this protocol.

An overview of the tasks used to provide data to  meet these objectives are provided in the next
section.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                           1-2                                     MACTEC

-------
                                                       Application ofAdsil in the NC/SC Charlotte Area
                             2.   Description of Tasks

A number of tasks were completed in order to ensure accurate and credible tools were created.
These tasks are described below:

Task 1: Baseline Testing
MACTEC selected two units in the Gainesville, Florida area as control tests.  One unit is a 1991
5-ton split-system air conditioner. The other unit is a 2001 split-system heat pump. The
efficiency of each of these units was measured between 10 and 20 times at various outdoor air
temperatures and differing indoor wet bulb temperatures to ensure that the testing processes were
repeatable and accurate.  Three methods were used (see Section 3 for description) to determine
the EER of these two pieces of equipment before  cleaning and coating with Adsil. Multiple tests
were conducted post-Adsil application and the results were compared for repeatability. These
results may be seen in Appendices B and C.

Task 2: Test Procedure Comparison with Traditional Data Logger Analysis
In order to further support the proposed testing process, MACTEC, in conjunction with the Adsil
company conducted a multi-week study at a commercial property near the west coast of Florida.
A 10-ton package heat pump was selected and sensors and data loggers were used to collect data
for two weeks prior to cleaning and coating.  Data was then collected for two weeks post-
cleaning. The units were then cleaned and coated per Adsil protocol. Data was then collected for
a final two weeks.  In conjunction with this test, MACTEC conducted our standard test procedure
using the spreadsheet, condenser heat rejection, and Service Assistant methodologies.  The results
of these tests and comparisons may be seen in Appendix D.

Task 3: Measure the Change in EER of HVAC Units in the SEQL Area
After establishing the protocol for measurement of HVAC efficiency in Tasks 1 and 2,
measurement of the EER of 45 HVAC units in the SEQL area was conducted pre- and post-
treatment. Prior to treatment MACTEC graded the units using our spreadsheet calculation.

Task 4: Develop a Tool for Prediction of HVAC Degradation
MACTEC developed a spreadsheet-based tool for predicting the degradation of HVAC
equipment based on objective data.  This spreadsheet can be used by a facility owner or operator
to estimate the degradation of air-cooled HVAC equipment based on objective data inputs. The
algorithms used in this spreadsheet were correlated to the actual measured change in efficiencies
of the HVAC units pre- and post-Adsil treatment.

Task 5: Utility Bill Verification of Savings
MACTEC determined that it would not be possible to use utility bills at the tested facilities for
determination of electric consumption savings. There were many reasons for this, including an
inability to collect utility bills for some of the facilities. Adding to this difficulty was the fact that

P:\EEG\Energy\EPAAdsilProject\FinalReport\EPAAdsilFinalReportwithedits -v2.doc     2~ 1                                    MACTEC

-------
                                                         Application ofAdsil in the NC/SC Charlotte Area
many of the facilities shared a common meter. Shared metering masks the effect of the efficiency
improvements since the savings would be attributed to facilities with units being treated as well
as facilities with no units being treated.

A third difficulty is attributed to an inability to collect a minimum of 12 months of bills post-
treatment. Application ofAdsil was completed in June of 2004, requiring collection of bills until
June of 2005 to acquire 12 months of usage; however, this was not feasible based on schedule
requirements of the project.  In many cases the units were coated in two phases several months
apart, rendering a meaningful comparison nearly impossible as 12 months of utility bills would
need to be collected prior to  any units being treated and requiring 12 months of bills to be
collected after the last unit was coated.  There would be 6-8 months of bills between events which
would have to be disregarded.

A fourth and final difficulty was that some facilities had only a small percentage of their total
tonnage cleaned and coated.  In these cases it would be impossible to measure savings on the
utility bills.

Even without the aforementioned difficulties, it would be difficult to use utility bill savings as a
significant measuring tool in an experiment such as this one. The reason is in our experience the
total amount of energy consumed by compressors and condensing units in the type of facilities in
this pilot typically account for approximately 30% of the total electricity consumption. Based on
measurements pre- and post-treatment, the typical energy savings with Adsil is around 10%.  This
HVAC savings would equate to an overall utility savings of 3%, a value very difficult to capture
in utility bill comparisons due to natural fluctuations of 10% to 20% from weather and usage
variations from one year to the next. Therefore, MACTEC used actual efficiency measurements
for the 45 units in the SEQL area and three units outside the SEQL area to create the tools and
form the conclusions presented in this report.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                            2-2                                     MACTEC

-------
                                                       Application ofAdsil in the NC/SC Charlotte Area
                       3.  EER Measurement Procedures

Initially there were 150 units included in the proposed SEQL area sample. In calendar year 2003,
prior to MACTEC's involvement, 75 of these units were coated with Adsil.  EPA and MACTEC
decided to determine the efficiency of as many of these remaining units as possible for the
allocated budget. Traditional efficiency measurements of HVAC units require multiple
temperature sensors, humidity sensors, kW sensors, and flow sensors to feed data to data loggers
over a period of time, typically 1-2 weeks, and then repeat the data collection post-HVAC
modification. Data is compared, analyzed, trended, and efficiency changes over a wide range of
operating temperatures (ambient and inside) are recorded and efficiency changes are determined.
It is easy to see why this methodology, while accurate, is expensive, and would have limited the
number of HVAC units being evaluated to a small percentage of the number being treated.

MACTEC proposed a different methodology requiring a one-time EER determination, pre- and
post-Adsil treatment, for each unit.  Three different methodologies were used, ranging from
simplest to most complex.  Results of the tests are provided in Section 5. A  description of each of
the procedures is provided below:

3.1   Spreadsheet Calculation

MACTEC developed a spreadsheet calculation to estimate the degradation of condenser coils.
The spreadsheet uses a compilation of objectively acquired data (see Figure  3-1) including coil
age, dirt accumulation, bent and smashed fins, degree of corrosion, presence of coil coating, and
fin-tube attachment to estimate the degradation in efficiency of coils.  Results were obtained from
this procedure on a total of 45 units and the ton-weighted average degradation was calculated.
Post-treatment, units were again evaluated and the EER degradation was compared to the pre-
treatment estimation. The difference in the values was recorded as the EER improvement. This
method is the easiest to use but was determined to be the least accurate. It fails to take into
account the effects of low refrigerant charge and other variables not visible in a site inspection.
Its accuracy is also dependent on the algorithms used to project the EER based on the input.
These were later refined, as described in Section 7 of this report.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                          3-1                                    MACTEC

-------
                                                                          Application ofAdsil in the NC/SC Charlotte Area
   Manufacturer:
   Model Number:
   Serial Number
   Equipment Type:
   Year Manufactured:
   Location
   Tag

   Compressor Data
   Running load Amps:
   Nameplate Voltage:
   Power factor:

   Condensing Fan Data
   Full load Amps:
   Nameplate Voltage:
   Adjust FLA to RLA:
                          FIGURE 3-1
                 Pre-Adsil HVAC Spreadsheet

Carrier                         Published EER:
50TJQ009-601                  Calculated EER:
4598G30510                    Nominal Capacity:
Package HP                    Age
1998                          Coil Condlton
Concord Admin                  Present Condition EER
RTU-5                         kW/ton
                                                      11.3
                                                      11.3
                                                      8.41
                                                       6
                                                      6%
                                                      10.5
                                                      1.14
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
    7.2
    460
    0.74
    0.70
    460
    0.70
   Evaporator fan data (If applicable)
   Full load Amps:               2.60
   Nameplate Voltage:           460
   Adjust FLA to RLA:            0.70

   Calculated compressor load:
   Calculated condensing fan load:
   Calculated evaporator fan load
   Total calculated load for equipment:
   Assumptions
   Condenser Coll Assessment
   Overall Unit Condition
                New
                Average
                Fair
                Poor
   Coil Cleanliness
                Coated
                Clean
                Dirty
                Clogged
                Plugged
   Fin Condition
                Like New
                Some Bent
                Smashed
                Dull/rough
                Corroded
                Pitted
                Flaking
   Fin-Tube Attachment
                Like New
                Corrosion
                Some Loose
                Many Loose
Amps              Power supply:
Volts               Phase adjustment:
                   Compressor quantity:
Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
            Amps              Power supply:
            Volts              Phase adjustment:
                              Fan quantity:

                        8.5    kW
                       0.45   kW
                       0.84   kW
                       8.93   kW - Condensing side only
              5.7%   Performance Degradation
3-phase
  1.73
   2
1-Phase
   1
   2
                                                    3-Phase
                                                      1.73
                                                       1
   Tubes
               Clean Cu
               Corrosion
               Pitting
               Leaks
    0.85
    0.15
    0.1
    0.05
    0.9
Source:  MACTEC,2004.
Prepared by :_TBL_
Checked by:  CDM
P:\EEGVEnergy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                         3-2
                                                                                                            MACTEC

-------
                                                       Application ofAdsil in the NC/SC Charlotte Area
3.2   Condenser Measurement

The second method used in EER calculation was a straight-forward condenser power
consumption and heat rejection calculation. For this method, a Fluke 41 meter was used to
measure actual power consumption of the condenser (total power of the condenser fan,
compressor(s), and blower motor if a package unit). Heat rejection of the condenser was
measured by determining the available flow area of the condenser, measuring the entry air
velocity into the condenser, and measuring the change in temperature of the air flow across the
condenser.  Inaccuracies in this procedure include a calculated air flow higher than actual due to
the coil restrictions, a measured air flow impacted by the presence of wind, and compressor heat
rejection being included in the EER calculation. As a result, the EERs of the equipment using
this methodology were on average almost twice what is expected (due in large part to the
inclusion of the coil and fin obstructions in the available air flow area). However, as the
compressor heat and available flow area were not germane to the comparison of before and after
EER values (they cancel one another out), no effort was made to determine the values of these
constants and subtract them from the equations. Every effort was made to minimize the impact of
wind, but in some cases the tests were thrown out because the wind velocity was sufficient to
impact our measurements.

Ambient temperatures, return air temperature, and return air humidity were also recorded.
Manufacturer's data was then used to "adjust" the measured EER at actual conditions to an EER
at ARI conditions of 95 degrees dry bulb (ambient temperature) and 67 degrees wet bulb
(evaporator temperature). In cases where the supply air cubic feet per minute (cfm) was not
available, MACTEC used the value most closely approximating a value of 400 cfm/ton in the
manufacturer's data.

3.3   Service Assistant Measurements

The third method used in EER determination was the employment of a Service Assistant as
available from Honeywell Controls. This tool has five  sensors for measuring the liquid pressure
(downstream of the condenser coil but upstream of the  expansion valve) or the discharge from the
compressor; the suction pressure before the compressor; the suction temperature before the
compressor; the liquid temperature after the condenser; and the ambient temperature. Supply air
temperature and humidity and return air humidity are measured via separate instrumentation (not
provided with the Service Assistant) and entered into a hand-held personal digital assistant (PDA)
which provides the interface. Software on the PDA includes input for Copeland compressor
models, or for the capacity and EER of the compressor for compressor models other than
Copeland. Using the  supplied input and the measured values, the efficiency index, capacity
index, and power index are determined by comparing inputs with compressor tables stored in the
proprietary software.  These values could be calculated manually but the software does it quickly
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc     J - J                                    MACTEC

-------
                                                          Application ofAdsil in the NC/SC Charlotte Area
and reliably with what MACTEC believes to be accurate results.  A detailed description of the
Service Assistant is provided in Appendix E.

MACTEC believes that this method provided the most reliable results. Disadvantages of this
method include disassembly of the HVAC units for access, thorough knowledge of HVAC
equipment and circuitry for proper location of sensors, and EPA certification in order to attach
refrigerant hoses to active HVAC equipment. Total instrumentation cost for methods 2 and 3 are
considered to be approximately similar.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                             3-4                                     MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
              4.   Testing Procedure Repeatability and Accuracy

Achieving repeatable and accurate results is integral to the success of the HVAC efficiency
measurement process. Many variables impact the measurement of the efficiency of an HVAC
unit. These variables include outdoor air temperature (typically an increase in outdoor air
temperature (OAT) decreases the efficiency); return air wet bulb temperature (generally higher
wet bulb temperatures result in higher efficiencies); blower air flow rate (constant for these
control tests); condenser air flow rate (increased after application ofAdsil and generally
decreases with air density increase); electrical measurements (power consumed is dependent on
voltage, current, load factor, and power factor); and the presence or absence of low temperature
ambient controls on individual units (simulate harsh conditions and decrease efficiency).  In
addition to these variables the instruments used are accurate to within a small error band with
additional error being potentially introduced by the reading of the  instruments.  Measuring the
capacity and power consumption of a dynamic piece of equipment involves professional
judgment at times in conjunction with the methodology being employed.

In order to minimize the magnitude of the errors associated with our protocol, MACTEC selected
two units to use in a baseline study. Unit 1 is a 14-year old Carrier 5-ton split-system considered
to be in good condition relative to its age. Unit 2 is a two-year old Carrier heat pump considered
to be in excellent condition.

Unit 1 Protocol
This unit was evaluated 17 times prior to the Adsil application and the initial assessment is shown
in Figure 4-1.  The ambient temperature ranged from 64 degrees to 92 degrees F and  the return air
wet bulb temperature varied from 53 degrees to 59 degrees F during the testing period from April
2004 through July 2004. The blower air flow was held constant and the condenser air flow was
observed to increase after Adsil treatment. The complete test results are presented in Appendix B.

Three testing procedures were used in each of the 17 evaluations.  The first procedure was the
condenser test measurement described in Section 3.2. The second and third tests compared the
compressor-specific Service Assistant test to the generic Service Assistant test. The generic test
uses a generic compressor curve to determine the operating efficiency of a condenser based on
the measurements described in Section 3.3.  The compressor-specific test uses the actual
compressor model of the identified piece of equipment to determine the operating efficiency. At
the time of our study, only Copeland compressor models were available in the software. As many
different compressor brands were encountered in our study it was  decided that it would be
necessary to compare the results of using a generic compressor with the results of the actual
compressor model.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                           4-1                                    MACTEC

-------
                                                                        Application ofAdsil in the NC/SC Charlotte Area
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
             Figure 4-1  Unit 1 Baseline Study
            HVAC Data Sheet and EER Calculation at ARI Conditions

Carrier                         Published EER:                    9.4
38TH060300                    Calculated EER:                   9.4
                               Nominal Capacity:                 4.96
Split system                     Age                              13
1991                           CoilConditon                     18%
Gainesville                      Present Condition EER             7.4
Toms Home unit                 kW/ton                           1.62
                                                           Btu/W-hr  (CUOnly)
                                                           Btu/W-hr  (CD Only)
                                                           tons
                                                           years
                                                           (% degraded)
                                                           Btu/W-hr
    30.8     Amps
    208     Volts
    0.96
    1.40
    208
    0.70
Amps
Volts
 Evaporator fan data (if applicable)
 Full load Amps:               7.10    Amps
 Nameplate Voltage:            122     Volts
 Adjust FLA to RLA:            0.77
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
                               Power supply:
                               Phase adjustment:
                               Fan quantity:
                               1-Phase
                                  1
                                  1
1-Phase
   1
   1
                                                  1-Phase
                                                     1
                                                     1
 Calculated compressor load:
 Calculated condensing fan load:
 Calculated evaporator fan load
 Total calculated load for equipment:
 Assumptions
 Present condition EER based on degradation of 2% per year after year 4
  plus additional degradation of condenser coil
                        6.1
                        0.20
                        0.67
                        6.32
                   kW             Published Total; System kW
                   kW             Condensing Unit kW at ARI conditons
                   kW             Capacity at ARI Conditions=
                   kW - Condensing side only
                                                      6.99
                                                      6.32
                                                      4.96
 Condenser Coil Assessment
 Overall Unit Condition	
              New
              Average
              Fair
              Poor
 Coil Cleanliness
              Coated
              Clean
              Dirty
              Clogged
              Plugged
 Fin Condition
              Like New
              Some Bent
              Smashed
              Dull/rough
              Corroded
              Pitted
              Flaking
 Fin-Tube Attachment
              Like New
              Corrosion
              Some Loose
              Many Loose
              18.2%  Performance Degradation
 Tubes
              Clean Cu
              Corrosion
              Pitting
              Leaks
    0.3
    0.2
    0.3
    0.2
    0.05
    0.95
Source: MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
P:\EEGVEnergy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                       4-2
                                                                                                         MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
This unit was cleaned with a garden hose prior to initiation of pre-Adsil testing. After completion
of pre-testing, the unit was cleaned and coated per Adsil protocol on August 3, 2004. Post-Adsil
testing began at this time and continued through August 23, 2004. Twelve tests were conducted
post-treatment and comparisons were made to the pre-treatment results.

Condenser Heat Rejection and Power Measurement
The protocol for this procedure is described in Section 3.2 of this report. Per this procedure, the
power consumption was observed to increase as temperature increased, as shown in Figure 4-2
and Figure 4-3.  It may also be seen in these two figures that the slope of the curve post-Adsil
treatment is steeper than the pre-treatment curve suggesting that power consumption on this
tested unit increased after treatment. The intercept for this phenomenon occurs at approximately
88 degrees F in  Figure 4-3.

A comparison of the measured EER values using this procedure shows great variation prior to
Adsil application. EER values ranged from 3.5 to 7.5 in the 70-95 degree temperature range.
This variation is due primarily to very inconsistent fan flow measurements prior to the Adsil
treatment, as may be seen in Table 4-1. The average flow rate was measured to be 0.66 kilogram
per second (kg/sec) with a range of 0.40 kg/sec to 0.94 kg/sec. Post-treatment the fan flow rate
averaged 1.13 kg/sec with a range between 1.11 kg/sec and 1.16 kg/sec. Flow post-treatment was
very consistent and uniform.

The average EER gain using this methodology was determined to be in excess of 70% as shown
in Table 4-1 for all temperatures and 49% for tests conducted at 85 degrees and higher. However,
the high variation of the flow rates pre-treatment may  invalidate the results of this protocol for
this unit. Figure 4-4 shows a very large increase in EER post-treatment with a trend of the EER
improvement to decrease post-treatment with increasing ambient temperatures.  Figure 4-5 also
shows a large increase in EER post-treatment with a trend of the EER to increase slightly post-
treatment (with  increasing ambient temperatures) when only tests 85 degrees and higher are
considered.

Service Assistant Test Description for Generic Compressor Model
The results for this procedure are  summarized in Table 4-2. The accuracy  and repeatability in the
tests improved with an increase in OAT using this procedure. At temperatures below 85 degrees,
the data had greater scatter. For instance, in the generic tests the range of achieved efficiency as a
percent of theoretical efficiency was between 80% and 102%. However, at temperatures of 85
degrees and higher, the range can be observed to be restricted to between 86% and 90% efficient.
Similarly, in the post-treatment tests the range is 86% to 99% at temperatures 73 and above.  At
temperatures 87 degrees and higher, the range is 89% to 99% efficient.  It was interesting to note
that the greatest efficiency improvements occurred at the harsher conditions and at lower ambient
temperatures there appeared to be little benefit from the treatment process.

P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc     4~3                                    MACTEC

-------
                                                          Application ofAdsil in the NC/SC Charlotte Area
                           Figure 4-2   Unit 1 Baseline Study
                    Power Consumption vs OAT, All Temperatures
       4.4 -F
           70
75
Source: MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
                              Figure 4-3 Unit 1 Baseline Study
                   Power Consumption vs OAT, Temps Above 85 Degrees
Source: MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                             4-4
                                                                                     MACTEC

-------
                                                             Application ofAdsil in the NC/SC Charlotte Area
1 O
1 1
1 n
•c- Q
^ y
*> Q
3
m 7

UJ

0
7
Figure 4-4 Unit 1 Baseline Study
Condenser EER Test vs OAT, All Temperatures

•
. 	
• "~" IT" 	 "~"~~


•
^
*. * ^^^*
^—~**~^*^
^ *
"**** •
0 75 80 85 90 9
OAT (F)





4Pre-Adsil EER
• Post-Adsil EER




5
Source: MACTEC,2004.
Prepared by :_TBL_
Checked by:  CDM
                          Figure 4-5  Unit 1 Baseline Study
                Condenser EER vs OAT, Temps Above 85 Degrees
»Pre-Adsil EER
• Post-Adsil EER
     OL
     UJ
                                                   90

                                                OAT (F)
Source: MACTEC,2004.
Prepared by :_TBL_
Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                               4-5
                                                                                          MACTEC

-------
                                                                                                                                      Application ofAdsil in the NC/SC Charlotte Area

TABLE 4-1
Unit 1 Baseline Study
Generic Compressor Test Summary-All Temperatures
EER at ARI Conditions 9.4 BTU/W-h
Condensing unit CFM 3000 CFM (Listed)
Capacity at ARI 4.96 tons
Coil Area 15 sq-ft
Predicted EER = 7.40
Test Date
April 12-G
April 14-G
April 12G
April 8G
July8-G
April 28G
July8-G
April 10G
April 28G
June 2-G3
July8G4
April 28G
JulySG
MaySG
MaySG
JulySG
MaySG


POSTADSIL
August 21 -G
August 20-G
August 23-G
August 20-G
August 20-G
August 20-G
August 10-G
August 21 -G
August 10-G 1
August 6-G
August 6-G1
August 18-G


HVAC Service Assistant

OAT
64
66
71
73
82
83
83
84
84
84
84
85
85
88
90
90
92
EWB
57
56
57
57
58
55
53
57
55
56
55
59
56
58
55
59
59
AVERAGES

OAT
73
81
82
83
85
85
85
86
87
89
91
90


EWB
59
59
63
60
60
65
57
59
58
60
60
65

AVERAGES
El
80%
102%
87%
79%
84%
85%
84%
86%
84%
87%
87%
88%
86%
89%
88%
90%
90%
86.8%

El
86%
87%
95%
88%
88%
88%
88%
88%
94%
93%
99%
94%

90.7%
Cl
73%
102%
82%
73%
83%
80%
82%
84%
80%
84%
86%
84%
88%
88%
88%
92%
90%
84.6%

Cl
81%
85%
95%
87%
85%
85%
85%
87%
90%
95%
97%
96%

89.0%
EER
9.9
12.4
10.0
8.8
8.5
8.5
8.4
8.5
8.3
8.6
8.6
8.7
8.4
8.5
8.1
8.4
8.5


EER
9.7
9.0
9.9
8.9
8.7
9.1
8.6
8.6
9.2
9.0
9.4
8.7


kW
5.7
4.9
6.6
5.5
4.7
4.7
5.1
5.2
4.8
6.3
5.1
4.9
4.9
5.0
5.0
4.8
5.0


kW
4.7
4.9
5.0
4.9
4.9
5.6
5.8
4.9
5.8
6.1
5.9
6.2


Physical Power and Capacity Measurements
Cond Air, deg F
inlet
66
66
71
73
85
83
85
84
84
84
82
85
86
86
90
90
95


inlet
72
79
82
83
84
82
84
85
82
89
89
90


exhaust
89
88
96
95
107
105
106
107
107
106
106
108
109
108
111
116
115


exhaust
96
102
106
107
107
108
107
108
105
114
115
115


Cond Air
DT(K)
12.8
12.2
13.9
12.2
12.2
12.2
11.7
12.8
12.8
12.2
13.3
12.8
12.8
12.2
11.7
14.4
11.1
12.55

DT(K)
13.3
12.8
13.3
13.3
12.8
14.4
12.8
12.8
12.8
13.9
14.4
13.9

13.38
kW
4.8
4.6
4.8
4.8
5.3
5.1
5.2
5.3
5.2
5.2
5.2
5.2
5.3
5.4
5.4
5.6
5.4


kW
4.8
5.1
5.3
5.2
5.3
5.4
5.2
5.3
5.2
5.5
5.6
5.6


(kg/sec)
1.06
1.76
1.06
1.06
2.16
1.42
2.10
1.06
1.81
1.08
2.10
1.81
2.04
2.19
2.30
2.22
2.47
1.75

(kg/sec)
2.96
2.94
2.92
2.99
2.92
2.98
3.01
2.98
3.06
2.93
3.02
2.99

2.97

tons
3.9
6.2
4.2
3.7
7.6
5.0
7.0
3.9
6.6
3.8
8.0
6.6
7.5
7.7
7.7
9.2
7.9


tons
11.31
10.74
11.12
11.39
10.66
12.32
11.01
10.88
11.17
11.62
12.49
11.87



EER
9.68
16.06
10.52
9.26
17.10
11.72
16.16
8.76
15.26
8.75
18.52
15.29
16.87
17.03
17.07
19.65
17.46
14.42

EER
28.27
25.28
25.18
26.29
24.14
27.38
25.41
24.63
25.77
25.35
26.77
25.43

25.83

cfm adj
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38

cfm adj
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38

0.38
Change 4.4% 5.1% 6.6% 70.1% 79.1% 0.0%
Source:  MACTEC, 2004.    Prepared by:  _TBL_
Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - vldi
                                                                                       4-6
                                                                                                                                                                         MACTEC

-------
                                                                                                                                      Application ofAdsil in the NC/SC Charlotte Area

TABLE 4-2
Unit 1 Baseline Study
Generic Compressor Test Summary at Ambient 85 Degrees or Higher
(Maximum of 1 Test per Temperature)
EER at ARI Conditions 9.4 BTU/W-h
Condensing unit CFM 3000 CFM (Listed)
Capacity at ARI 4.96 tons
Coil Area 15 sq-ft
Predicted EER = 7.40
Test Date
July 8G
MaySG
MaySG
MaySG


POST ADSIL
August 10-G
August 21 -G
August 10-G1
August 6-G
August 6-G1
August 18-G


HVAC Service Assistant

OAT
85
88
90
92
EWB
56
58
55
59
AVERAGES

OAT
85
86
87
89
91
90


EWB
57
59
58
60
60
65

AVERAGES
El
86%
89%
88%
90%
88.3%

El
88%
88%
94%
93%
99%
94%

92.7%
Cl
88%
88%
88%
90%
88.5%

Cl
85%
87%
90%
95%
97%
96%

91.7%
EER
8.4
8.5
8.1
8.5


EER
8.6
8.6
9.2
9.0
9.4
8.7


kW
4.9
5.0
5.0
5.0


kW
5.8
4.9
5.8
6.1
5.9
6.2


Physical Power and Capacity measurments
Cond Air, deg F
inlet
86
86
90
95


inlet
84
85
82
89
89
90


exhaust
109
108
111
115


exhaust
107
108
105
114
115
115


Cond Air
DT(K)
12.8
12.2
11.7
11.1
11.94

DT(K)
12.8
12.8
12.8
13.9
14.4
13.9

13.43
kW
5.3
5.4
5.4
5.4


kW
5.2
5.3
5.2
5.5
5.6
5.6


(kg/sec)
2.04
2.19
2.30
2.47
2.25

(kg/sec)
3.01
2.98
3.06
2.93
3.02
2.99

3.00

tons
7.5
7.7
7.7
7.9


tons
11.01
10.88
11.17
11.62
12.49
11.87



EER
16.87
17.03
17.07
17.46
17.11

EER
25.41
24.63
25.77
25.35
26.77
25.43

25.56

cfm adj
0.38
0.38
0.38
0.38


cfm adj
0.38
0.38
0.38
0.38
0.38
0.38


Change 5.0% 3.6% 12.4% 33.1% 49.4%
Source:  MACTEC, 2004.    Prepared by: _TBL_
Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                       4-7
                                                                                                                                                                         MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
Figure 4-6 shows the EER improvement associated with the Adsil process as measured with the
Service Assistant generic compressor over the temperature range from 73 to 92 degrees F. The
average EER improvement measured with this process is 4.4% and the average capacity increase
is seen to be 5.1% in Table 4-1. When temperatures 85 degrees and above are considered, the
improvement in EER is seen to be 5.0% but the capacity increase is less than before with a 3.6%
increase.  Table 4-2 and Figure 4-7 show these results.

Service Assistant Test Description for Copeland Compressor Model
The second test employs the actual Copeland compressor model currently in use on the unit.
Comparing these results in a similar manner as before, the EER as a percent of the theoretical
EER is seen to vary between 79% and 103%. The accuracy and repeatability in these tests also
increased with an increase in OAT.  At temperatures below 85 degrees, the data had greater
scatter. At temperatures of 85 degrees and higher, the range can be observed to be restricted to
between 81% and 85% efficient.  Similarly, in the post-treatment tests the range is 83% to 96% at
temperatures 73 and above.  At temperatures 87 degrees and higher, the range  is 92% to 96%
efficient. It was interesting to note that the greatest efficiency improvements occurred at the
harsher conditions and that at low ambient temperatures there appeared to be little benefit from
the treatment process.

Figure 4-8 shows the EER improvement associated with the Adsil process as measured with the
Service Assistant Copeland compressor over the temperature range from 73 to 92 degrees F.  The
average EER improvement measured with this process is 6.1% and the average capacity increase
is seen to be 6.0% in Table 4-3. When temperatures 85 degrees and above are considered, the
improvement in EER is seen to be 5.0% but the capacity increase is less than before with a 3.6%
increase.  Table 4-4 and Figure 4-9 show these results.

Summary of Test Results for Unit 1
All three test procedures showed a measurable increase in EER for Unit 1.  Figure 4-10 shows
change in EER after Adsil treatment for all three procedures.  Consistent trend lines are observed
when comparing the generic compressor curve test to the Copeland compressor test although the
generic test underestimates the Copeland test efficiency gains. The condenser test in this figure
shows a much larger increase in EER over the temperature range of 73 degrees to 92 degrees.
Figure 4-11 presents the results of tests at 85 degrees and higher. These three curves are
approximately parallel and indicate that the EER gains are higher for all three tests at higher
temperatures.  The condenser test continues to overestimate the gains because  of the poor
condenser air flow measurements during pre-treatment testing.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                           4-8                                   MACTEC

-------
                                                           Application ofAdsil in the NC/SC Charlotte Area
                              Figure 4-6  Unit 1 Baseline Study
                     Generic Compressor EER vs OAT, All Temperatures
                                                                            »Pre-Adsil EER

                                                                            • Post-Adisl EER
           70
95
Source: MACTEC,2004.
Prepared by :_TBL_
Checked by:  CDM
                              Figure 4-7  Unit 1 Baseline Study
                 Generic Compressor EER vs OAT at 85 Degrees and Higher
Source: MACTEC,2004.
Prepared by :_TBL_
Checked by: _CDM_
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                              4-9
                                                                                      MACTEC

-------
                                                            Application ofAdsil in the NC/SC Charlotte Area
                               Figure 4-8  Unit 1 Baseline Study
                    Copeland Compressor EER vs OAT, All Temperatures
   a:
                                                                              *Pre-Adsil EER

                                                                              • Post-Adsil EER
            70
Source: MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
                                Figure 4-9  Unit 1 Baseline Study
                     Copeland  EER vs OAT (SA) at 85 Degrees and Higher
        9.3 —
        9.1

        8.9

        8.7

        8.5

        8.3
»Pre-Adsil EER

• Post-Adsil EER
Source: MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                               4-10
                                                                                         MACTEC

-------
                                                                    Application ofAdsil in the NC/SC Charlotte Area
Figure 4-10 Unitl Baseline Study
Change in EER after Adsil Treatment
0.8 -i
0.7 -
UL
s °6
.E 0.5 -
o
j? 0.4 -
ra
o 0.3-
5s 0.2-
0.1 -
0 -
6
All Temperatures

\^
^\^
^\^^
^\^^
^^\




• Generic
• Copeland
Condenser test




5 75 85 95 105
OAT (F)
Source: MACTEC,2004.
Prepared by :_TBL_
Checked by:  CDM


0 35 -
0 3 -
o:
S 025 -


-------
                                                                                                                                                                                                                                                                                                       Application ofAdsil in the NC/SC Charlotte Area
TABLE 4-3
Unit 1 Baseline Study
Copeland Compressor Test Summary-All Temperatures
EER at ARI Conditions 9.4 BTU/W-h
Condensing unit CFM 3000 CFM (Listed)
Capacity at ARI 4.96 tons
Coil Area 15 sq-ft
Predicted EER = 7.40
Test Date
ApriM2-C
April 14-C
AprN12-C
July 8-C
April 28-C
July 8-C1
April 10-C1
April 28-C2
June 2-C3
July 8 C4
April 9-C1
April 28-C2
July 8-C3
May 08-C
May 08-C
May 08-C
May 08-C


POSTADSIL
August 21 -C
August 20-C
August 23-C
August 20-C
August 20-C
August 20-C
August 10-C
August 21 -C
August 10-C
August 6-C
August 6-C
August 1 8-C


HVAC Service Assistant

OAT
64
66
71
82
83
83
84
84
84
84
85
85
85
88
90
90
92


OAT
73
81
82
83
85
85
85
86
87
89
91
90


EWB
57
56
57
58
55
53
57
55
56
55
57
59
56
58
55
59
59


EWB
59
59
63
60
60
65
57
59
58
60
60
65


El
79%
103%
79%
81%
80%
80%
83%
81%
86%
84%
81%
83%
83%
83%
83%
85%
84%
83.4%

El
83%
84%
88%
84%
89%
89%
88%
85%
92%
92%
96%
92%

88.5%
Cl
72%
103%
71%
75%
72%
73%
76%
73%
78%
77%
72%
76%
78%
77%
77%
81%
78%
77.0%

Cl
74%
76%
84%
78%
81%
81%
79%
78%
82%
87%
91%
88%

81.6%
EER
9.8
12.5
9.0
8.2
8.0
8.0
8.2
8.0
8.5
8.3
7.9
8.2
8.1
7.9
7.6
8.0
7.9


EER
9.4
8.7
9.2
8.5
8.8
9.2
8.6
8.3
9.0
8.9
9.1
8.5


kW
4.6
5.0
4.6
4.7
4.7
4.7
4.7
4.6
5.5
4.7
5.5
4.7
4.8
4.7
4.7
4.8
4.7


kW
4.6
4.6
4.8
4.7
4.7
5.6
5.5
4.6
5.5
5.8
5.8
5.8


Change 6.1% 6.0%
Physical Power and Capacity Measurements
Cond Air, deg F
inlet
66
66
71
85
83
85
84
84
84
82
85
85
86
86
90
90
95


inlet
72
79
82
83
84
82
84
85
82
89
89
90

83.42


exhaust
89
88
96
107
105
106
107
107
106
106
108
108
109
108
111
116
115


exhaust
96
102
106
107
107
108
107
108
105
114
115
115

107.50
Cond Air
DT(K)
12.8
12.2
13.9
12.2
12.2
11.7
12.8
12.8
12.2
13.3
12.8
12.8
12.8
12.2
11.7
14.4
11.1
12.6

DT(K)
13.3
12.8
13.3
13.3
12.8
14.4
12.8
12.8
12.8
13.9
14.4
13.9

13.38
kW
4.8
4.6
4.8
5.3
5.1
5.2
5.3
5.2
5.2
5.2
5.2
5.2
5.3
5.4
5.4
5.6
5.4


kW
4.8
5.1
5.3
5.2
5.3
5.4
5.2
5.3
5.2
5.5
5.6
5.6

5.29
(kg/sec)
1.06
1.76
1.06
2.16
1.42
2.10
1.06
1.81
1.08
2.10
1.06
1.81
2.04
2.19
2.30
2.22
2.47
1.7

(kg/sec)
2.96
2.94
2.92
2.99
2.92
2.98
3.01
2.98
3.06
2.93
3.02
2.99

2.97

tons
3.87
6.16
4.21
7.55
4.98
7.00
3.87
6.61
3.79
8.0
3.87
6.62
7.5
7.66
7.68
9.17
7.86


tons
11.31
10.74
11.12
11.39
10.66
12.32
11.01
10.88
11.17
11.62
12.49
11.87

11.38

EER
9.68
16.06
10.52
17.10
11.72
16.16
8.76
15.26
8.75
18.52
8.93
15.29
16.87
17.03
17.07
19.65
17.46
14.4

EER
28.27
25.28
25.18
26.29
24.14
27.38
25.41
24.63
25.77
25.35
26.77
25.43

25.83
6.3% 70.1% 79.3%
P:\EEG\Energy\EPA Adsil PrqjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                                                                                                               4-12
                                                                                                                                                                                                                                                                                                                                               MACTEC

-------
                                                                                                                                                                                                                       Application ofAdsil in the NC/SC Charlotte Area
 Table 4-3. Unit 1 Baseline Study, Copeland Compressor Test Summary-All Temperatures (continued)
Condensing Unit Summary - Ambient Conditions | Condensing Unit Summary - ARI Conditions
OAT
64-C
66-C
71 -C
82-C
83-C
83-C1
84-C1
84-C2
84-C3
84-C3
85-C1
85-C2
85-C3
88-C
90-C
90-C1
92-C

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
4.6
3.61
9.8
5.0
5.12
12.5
4.6
3.45
9.0
4.7
3.50
8.2
4.7
3.26
8.0
4.7
3.30
8.0
4.7
3.48
8.23
4.6
3.29
7.97
5.5
3.54
8.46
4.7
3.47
8.26
5.5
3.28
7.94
4.7
3.52
8.20
4.8
3.53
8.11
4.7
3.49
7.91
4.7
3.38
7.65
4.8
3.66
7.95
4.7
3.49
7.91
CU
4.800
3.87
9.68
4.600
6.16
16.06
4.8
4.21
10.52
5.3
7.55
17.10
5.1
4.98
11.72
5.2
7.00
16.16
5.3
3.87
8.76
5.2
6.61
15.26
5.2
3.79
8.75
5.2
8.02
18.52
5.2
3.87
8.93
5.2
6.62
15.29
5.3
7.45
16.87
5.4
7.66
17.03
5.4
7.68
17.07
5.6
9.17
19.65
5.4
7.66
17.03
Lit
4.85
5.01
12.40
4.92
4.97
12.12
5.09
4.86
11.45
5.50
4.66
10.17
5.46
4.52
9.94
5.46
4.52
9.94
5.54
4.58
9.91
5.50
4.50
9.83
5.52
4.54
9.83
5.50
4.50
9.83
5.58
4.56
9.81
5.63
4.63
9.88
5.56
4.52
9.77
5.70
4.53
9.53
5.71
4.39
9.22
5.79
4.52
9.35
5.76
4.54
9.46
Percent Difference
SA/Lit
95%
72%
79%
102%
103%
103%
90%
71%
79%
85%
75%
81%
86%
72%
80%
86%
73%
80%
85%
76%
83%
84%
73%
81%
100%
78%
86%
86%
77%
84%
99%
72%
81%
84%
76%
83%
86%
78%
83%
82%
77%
83%
82%
77%
83%
83%
81%
85%
82%
77%
84%
CU/Lit
99%
77%
78%
93%
124%
133%
94%
87%
92%
96%
162%
168%
93%
110%
118%
95%
155%
163%
96%
85%
88%
95%
147%
155%
94%
83%
89%
95%
178%
188%
93%
85%
91%
92%
143%
155%
95%
165%
173%
95%
169%
179%
95%
175%
185%
97%
203%
210%
94%
169%
180%
SA/CU
96%
93%
101%
109%
83%
78%
96%
82%
86%
89%
46%
48%
92%
65%
68%
90%
47%
49%
89%
90%
94%
88%
50%
52%
106%
93%
97%
90%
43%
45%
106%
85%
89%
90%
53%
54%
91%
47%
48%
87%
46%
46%
87%
44%
45%
86%
40%
40%
87%
46%
46%
Test Data
SA
6.0
3.6
7.4
6.4
5.1
9.7
5.7
3.5
7.4
5.4
3.7
7.6
5.4
3.6
7.5
5.4
3.6
7.5
5.4
3.8
7.8
5.3
3.6
7.6
6.3
3.9
8.1
5.4
3.8
7.9
6.2
3.6
7.6
5.3
3.8
7.8
5.5
3.9
7.8
5.2
3.8
7.8
5.2
3.8
7.8
5.2
4.0
8.0
5.2
3.8
7.9
CU
6.2
3.8
7.4
5.9
6.1
12.5
6.0
4.3
8.7
6.1
8.0
15.8
5.9
5.5
11.1
6.0
7.7
15.3
6.0
4.2
8.3
6.0
7.3
14.6
6.0
4.1
8.4
6.0
8.8
17.7
5.9
4.2
8.6
5.8
7.1
14.6
6.0
8.2
16.3
6.0
8.4
16.8
6.0
8.7
17.4
6.1
10.1
19.8
5.9
8.4
17.0
Literature
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
Percent Difference
SA/Lit
95%
72%
79%
102%
103%
103%
90%
71%
79%
85%
75%
81%
86%
72%
80%
86%
73%
80%
85%
76%
83%
84%
73%
81%
100%
78%
86%
86%
77%
84%
99%
72%
81%
84%
76%
83%
86%
78%
83%
82%
77%
83%
82%
77%
83%
83%
81%
85%
82%
77%
84%
CU/Lit
99%
77%
78%
93%
124%
133%
94%
87%
92%
96%
162%
168%
93%
110%
118%
95%
155%
163%
96%
85%
88%
95%
147%
155%
94%
83%
89%
95%
178%
188%
93%
85%
91%
92%
143%
155%
95%
165%
173%
95%
169%
179%
95%
175%
185%
97%
203%
210%
94%
169%
180%
SA/CU
96%
93%
101%
109%
83%
78%
96%
82%
86%
89%
46%
48%
92%
65%
68%
90%
47%
49%
89%
90%
94%
88%
50%
52%
106%
93%
97%
90%
43%
45%
106%
85%
89%
90%
53%
54%
91%
47%
48%
87%
46%
46%
87%
44%
45%
86%
40%
40%
87%
46%
46%
Predicted/SA
-
-
99%
-
-
76%
-
-
99%
-
-
97%
-
-
98%
-
-
98%
-
-
95%
-
-
97%
-
-
91%
-
-
94%
-
-
97%
-
-
95%
-
-
95%
-
-
95%
-
-
95%
-
-
92%
-
-
94%
Predicted/CU
-
-
101%
-
-
59%
-
-
86%
-
-
47%
-
-
67%
-
-
48%
-
-
89%
-
-
51%
-
-
88%
-
-
42%
-
-
86%
-
-
51%
-
-
45%
-
-
44%
-
-
42%
-
-
37%
-
-
44%
P:\EEG\Energy\EPA Adsil PrqjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                                                                4-13
                                                                                                                                                                                                                                                     MACTEC

-------
                                                                                                                                                                                                             Application ofAdsil in the NC/SC Charlotte Area
 Table 4-3. Unit 1 Baseline Study, Copeland Compressor Test Summary-All Temperatures (continued)

73-C
81 -C
82-C
83-C
85-C
85-C1
85-C2
86-C
87-C
89-C
91 -C
90-C Clean
Evap
POST ADSIL
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER

4.6
3.64
9.37
4.6
3.59
8.68
4.8
4.14
9.20
4.7
3.68
8.52
4.7
3.78
8.83
5.6
4.09
9.19
5.5
3.60
8.63
4.6
3.60
8.31
5.5
3.74
9.02
5.8
3.96
8.86
5.8
4.16
9.11
5.8
3.98
8.54

4.8
11.31
28.27
5.1
10.74
25.28
5.3
11.12
25.18
5.2
11.39
26.29
5.3
10.66
24.14
5.4
12.32
27.38
5.2
11.01
25.41
5.3
10.88
24.63
5.2
11.17
25.77
5.5
11.62
25.35
5.6
12.49
26.77
5.6
11.87
25.43

5.23
4.92
11.29
5.49
4.73
10.33
5.66
4.93
10.45
5.58
4.72
10.14
5.65
4.67
9.92
5.87
5.05
10.33
5.58
4.56
9.81
5.66
4.61
9.77
5.58
4.56
9.81
5.67
4.55
9.63
5.78
4.57
9.49
5.85
4.52
9.28

88%
74%
83%
84%
76%
84%
85%
84%
88%
84%
78%
84%
83%
81%
89%
95%
81%
89%
99%
79%
88%
81%
78%
85%
99%
82%
92%
102%
87%
92%
100%
91%
96%
99%
88%
92%

92%
230%
250%
93%
227%
245%
94%
226%
241%
93%
241%
259%
94%
228%
243%
92%
244%
265%
93%
242%
259%
94%
236%
252%
93%
245%
263%
97%
255%
263%
97%
273%
282%
96%
262%
274%

96%
32%
33%
90%
33%
34%
91%
37%
37%
90%
32%
32%
89%
35%
37%
104%
33%
34%
106%
33%
34%
87%
33%
34%
106%
33%
35%
105%
34%
35%
104%
33%
34%
104%
34%
34%

5.6
3.7
7.8
5.3
3.8
7.9
5.4
4.2
8.3
5.3
3.9
7.9
5.3
4.0
8.4
6.0
4.0
8.4
6.2
3.9
8.3
5.1
3.9
8.0
6.2
4.1
8.7
6.5
4.3
8.7
6.3
4.5
9.0
6.3
4.4
8.7

5.8
11.4
23.6
5.9
11.3
23.1
5.9
11.2
22.7
5.9
12.0
24.4
5.9
11.3
22.9
5.8
12.1
25.0
5.9
12.0
24.4
5.9
11.7
23.7
5.9
12.1
24.8
6.1
12.7
24.8
6.1
13.5
26.6
6.1
13.0
25.8

6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42
6.32
4.96
9.42

88%
74%
83%
84%
76%
84%
85%
84%
88%
84%
78%
84%
83%
81%
89%
95%
81%
89%
99%
79%
88%
81%
78%
85%
99%
82%
92%
102%
87%
92%
100%
91%
96%
99%
88%
92%

92%
230%
250%
93%
227%
245%
94%
226%
241%
93%
241%
259%
94%
228%
243%
92%
244%
265%
93%
242%
259%
94%
236%
252%
93%
245%
263%
97%
255%
263%
97%
273%
282%
96%
262%
274%

96%
32%
33%
90%
33%
34%
91%
37%
37%
90%
32%
32%
89%
35%
37%
104%
33%
34%
106%
33%
34%
87%
33%
34%
106%
33%
35%
105%
34%
35%
104%
33%
34%
104%
34%
34%

-
-
95%
-
-
94%
-
-
89%
-
-
94%
-
-
88%
-
-
88%
-
-
89%
-
-
92%
-
-
85%
-
-
85%
-
-
82%
-
-
85%

-
-
31%
-
-
32%
-
-
33%
-
-
30%
-
-
32%
-
-
30%
-
-
30%
-
-
31%
-
-
30%
-
-
30%
-
-
28%
-
-
29%
Source: MACTEC, 2004.   Prepared by: _TBL_
Checked by:  CDM
P:\EEG\Energy\EPA Adsil PrqjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                                                          4-14
                                                                                                                                                                                                                                         MACTEC

-------
                                                                                                                                                     Application ofAdsil in the NC/SC Charlotte Area
             TABLE 4-4
             Unit 1  Baseline Study
             Copeland Compressor Test Summary at Ambient of 85 Degrees or Higher
             (Maximum of 1 Test Per Temperature)
 EER at ARI Conditions
 Condensing unit CFM
 Capacity at ARI
 Coil Area
 Predicted EER =
                     9.4 BTU/W-h
                   3000 CFM (Listed)
                    4.96 tons
                     15 sq-ft
                    7.40
Test Date
April 9-C1
May 08-C
May 08-C
May 08-C


POSTADSIL
August 20-C
August 20-C
August 21-C
August 10-C
August 6-C
August 6-C
August 18-C


HVAC Service Assistant

OAT
85
88
90
92


OAT
85
85
86
87
89
91
90


EWB
57
58
55
59


EWB
60
65
59
58
60
60
65


El
81%
83%
83%
84%
82.8%

El
89%
89%
85%
92%
92%
96%
92%

90.7%
Cl
72%
77%
77%
78%
76.0%

Cl
81%
81%
78%
82%
87%
91%
88%

84.0%
EER
0.0
0.0
0.0
0.0


EER
0.0
0.0
0.0
0.0
0.0
0.0
0.0


kW
5.5
4.7
4.7
4.7


kW
4.7
5.6
4.6
5.5
5.8
5.8
5.8


Physical Power and Capacity Measurements
Cond Air, deg F
inlet
85
86
90
95


inlet
84
82
85
82
89
89
90

85.86
exhaust
108
108
111
115


exhaust
107
108
108
105
114
115
115

110.29
Cond Air
DT(K)
12.8
12.2
11.7
11.1


DT(K)
12.8
14.4
12.8
12.8
13.9
14.4
13.9

13.57
kW
5.2
5.4
5.4
5.4


kW
5.3
5.4
5.3
5.2
5.5
5.6
5.6

5.41
(kg/sec)
1.06
2.19
2.30
2.47


(kg/sec)
2.92
2.98
2.98
3.06
2.93
3.02
2.99

2.98

tons
3.87
7.66
7.68
7.86


tons
10.66
12.32
10.88
11.17
11.62
12.49
11.87

11.57

EER
8.93
17.03
17.07
17.46


EER
24.14
27.38
24.63
25.77
25.35
26.77
25.43

25.64
Source: MACTEC, 2004.
Prepared by: _TBL_  Checked by: _CDM_
P:\EEG\Energy\EPA Adsil PrqjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                         4-15
                                                                                                                                                                         MACTEC

-------
                                                              Application ofAdsil in the NC/SC Charlotte Area
Figure 4-12 shows the variability in measuring the efficiency index of the unit pre-treatment over the
temperature range of 73 degrees to 92 degrees. Figure 4-13 shows the same indices for the post-
treatment unit. Results of this inspection show more uniform results after Adsil treatment. Figure 4-14
shows the indices for temperatures of 85 degrees or higher.  Inspection of these graphs indicate that the
efficiency index, a measure of the actual efficiency divided by the benchmark efficiency of the unit when
new, increases with increasing temperatures. This increase is observed to be more pronounced after the
Adsil application.

Unit 2 Protocol
This unit was evaluated eight times prior to the Adsil application. The ambient temperature ranged from
83 degrees to 92 degrees F and the return air wet bulb temperature varied from 54 degrees to 57 degrees
F during the testing period from May 2004 through August 2004. The blower air flow was held constant
and the average condenser air flow was observed to increase after Adsil treatment. The complete test
results are presented in Appendix C. Figure 4-15 provides the initial assessment of the unit prior to
Adsil treatment.

Two testing procedures were used in each of the eight evaluations.  The first procedure was the
condenser test measurement described in Section 3.2. The second test was the generic compressor
Service Assistant test.  The generic test uses a generic compressor curve to determine the operating
efficiency of a condenser based on the measurements described in Section 3.3.

This unit was not cleaned prior to initiation of pre-Adsil testing.  After completion of pre-testing, the unit
was cleaned and coated per Adsil protocol on August 3, 2004. Post-Adsil testing began at this time and
continued through August 31, 2004.  Seven tests were conducted post-treatment and comparisons were
made to the pre-test process.

Condenser Heat Rejection and Power Measurement
The protocol for this procedure is described in Section 3.2 of this report. Per this procedure the power
consumption was observed to increase as temperature increased, as shown in Figure 4-16 and Table 4-5.
It may also be seen in these two figures that the slope of the post-Adsil treatment curve is less than the
pre-treatment curve suggesting that power consumption on this tested unit decreased after treatment.
The intercept for this phenomenon occurs at approximately 84 degrees F.

A comparison of the measured EER using this procedure shows great variation prior to and after Adsil
application. EER values ranged from 7.6 to 11.2 for all temperature ranges before application and from
9.7 to 13.9 after application.  This variation is due primarily to very inconsistent fan flow measurements
as may be seen in Table 4-5.  The average pre-application flow rate was measured to be 3.91 kg/sec with
a range of 3.33 kg/sec to 4.63  kg/sec. Post-treatment the fan flow rate averaged 4.47 kg/sec with a range
between 4.07 kg/sec and 4.92  kg/sec.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                               4-16                                     MACTEC

-------
                                                                            Application ofAdsil in the NC/SC Charlotte Area
Figure 4-12 Unit 1 Baseline Study
Efficiency Index (El) vs OAT for Pre-ADSIL Tests, All Temperatures
<\
\
OQC
OQ
.y
DJ 0.85
00
.0
Oyc
07


A * * *

mm mmmm—~mmm^L^E' ^
*


*pre generic
pre copeland

. / i
70 80 90 100
OAT (F)
Source: MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
Figure 4-13 Unit 1 Baseline Study
Efficiency Index (El) vs OAT for Post-Adsil Tests, All Temperatures
-i
i
OOC:
.yo
On
.y
77", n KC,
Ul U.OO
00
.0
07£
. / 0
07


^^£5^
^^



• post generic
x post copeland

70 80 90 100
OAT (F)
Source: MACTEC,2004.
Prepared by :_TBL_
Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                         4-17
                                                                                                            MACTEC

-------
                                                                          Application ofAdsil in the NC/SC Charlotte Area
                                   Figure 4-14  Unit 1 Baseline Study
              Efficiency Index (El) vs OAT For Pre- & Post-Adsil Tests, Temps Above 85 F
       0.95
   w   0.9
       0.85
           85
   90
OAT (F)
95
Source:  MACTEC,2004.
Prepared by: _TBL_
Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                       4-18
                                                                                                        MACTEC

-------
                                                                                   Application ofAdsil in the NC/SC Charlotte Area
Figure 4-15 Unit 2 Baseline Study
HVAC Data Sheet and EER Calculation at ARI Conditions
Manufacturer: Carrier Published EER: 67.0
Model Number: 38YCC060 Calculated EER: 9.2
Serial Number Nominal Capacity: 4.64
Equipment Type: SS Heat pump Age 3
Year Manufactured: 2001 Coil Conditon 3%
Location MACTEC Hendrickson Present Condition EER 9.0
Tag HP-7 kW/ton 1.33
Compressor Data
Running load Amps: 17.0 Amps Power supply: 3-phase
Nameplate Voltage: 230 Volts Phase adjustment: 1.73
Power factor: 0.86 Compressor quantity: 1
Condensing Fan Data
Full load Amps: 1.40 Amps Power supply: 1-Phase
Nameplate Voltage: 230 Volts Phase adjustment: 1
Adjust FLA to RLA: 0.70 Fan quantity: 1
Evaporator fan data (if applicable)
Full load Amps: 5.40 Amps Power supply: 1-Phase
Nameplate Voltage: 230 Volts Phase adjustment: 1
Adjust FLA to RLA: 0.11 Fan quantity: 1
Calculated compressor load: 5.8 kW
Calculated condensing fan load: 0.23 kW
Calculated evaporator fan load 0.13 kW
Total calculated load for equipment: 6.04 kW - Condensing side only
Assumptions
Condenser Coil Assessment 3.2% Performance Degradation
Overall Unit Condition
New
Average X
Fair
Poor
Coil Cleanliness
Coated
Clean 0.9
Dirty 0.1
Clogged
Plugged
Fin Condition
Like New 1
Some Bent
Smashed
Dull/rough 0.5
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New x
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu x
Corrosion
Pitting
Leaks


Btu/W-hr (CU Only)
Btu/W-hr (CUOnly)
tons
years
(% degraded)
Btu/W-hr
Source:  MACTEC, 2004.
Prepared by :_TBL_
Checked by:  CDM
P:\EEGVEnergy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                              4-19
                                                                                                                     MACTEC

-------
                                                                                  Application ofAdsil in the NC/SC Charlotte Area
Figure 4-16 Unit 2 Baseline Study
Power Consumption vs OAT, All Temperatures
A Q
A £
A 7
A R
5 4=i -
> 4.5
4.4
A ^
4 9
A 1
•1

Pre Adsil \ ^^
J^, —
* *^.--J^^.- — *
^
*^l*fS^+ ^^~~~ Post Adsil
^— • t**'




*Pre-Adsil Fluke kW
• Post- Adsil Fluke kW

80 85 90 95
OAT (F)
Source:  MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                             4-20
                                                                                                                    MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
The average EER gain using this methodology was determined to be 17% for all tested
temperatures as shown in Table 4-5. The variations of the flow rates tend to invalidate the results
of this protocol for this unit. Figure 4-17 shows the trend of the EER to increase post-treatment
with increasing ambient temperatures.

Service Assistant Test Description for Generic Compressor Model
The results for this procedure are summarized in Table 4-5.  The Service Assistant test for Unit 2
showed an average operating efficiency of 96% for tests conducted prior to Adsil application.
For these tests the efficiency index (El) ranged from 95% to 98% and tended to increase with
increasing ambient temperature. After application, Unit 2 had an average operating El of 97%.
The post-treatment range varied from 94% to 99% and tended to increase with increasing  ambient
temperature. The EER for Unit 2 had an average increase of 1% over the range of ambient
conditions tested. Figure 4-18  shows the linear profile of the EER over this range and suggests
that the unit performance (for pre- and  post-Adsil applications) tends to converge around 83 F.

The average Service Assistant capacity for pre- and post-Adsil™ applications decreased from
4.18 to 4.16 tons of cooling over the range of tested ambient conditions. The capacity measured
tends to converge with increasing ambient temperature and has an average difference of negative
0.54%.  The Service Assistant capacity measurement results are presented in Table 4-5.

Summary of Test Results for Unit 2
Both test procedures showed a measurable increase in EER for Unit 2.  Figure 4-19 presents the
results of tests at all temperatures.  The results show an increase in EER % change for the Service
Assistant test with increasing ambient temperature, and a  decrease in % EER change for the
condenser test with increasing ambient temperatures.

Figure 4-20 shows the variability in measuring the efficiency index of the unit for pre- and post-
treatment over the tested temperature ranges. Inspection of these graphs indicate that the
efficiency index, a measure of the actual efficiency divided by the benchmark efficiency of the
unit when new, increases with increasing temperatures. This increase is observed to be more
pronounced after the Adsil application.

Conclusions-Units 1 and 2
Test results at temperatures of 85 degrees  or greater are considered to be more accurate and viable
for the process. The Service Assistant  methodology was determined to be the most accurate
method for measuring the EER of FfVAC  equipment.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                          4-21                                    MACTEC

-------
                                                                   Application ofAdsil in the NC/SC Charlotte Area
                                     Figure 4-17  Unit 2 Baseline Study
                               Condenser EER Test vs OAT, All Temperatures
                                                                      • Pre-Adsil Condenser EER
                                                                      • Post Adsil Condenser EER
                                               OAT (F)
Source:  MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
                                     Figure 4-18 Unit 2 Baseline Study
                             Generic Compressor EER vs OAT, All Temperatures
       10
   ;= 9.5
   a:
      8.5
                                                               Post-Adsil
                                                     Pre-Adsil
         80
85
90
                                             OAT (F)
95
Source:  MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                  4-22
                                                                                                 MACTEC

-------
                                                                     Application ofAdsil in the NC/SC Charlotte Area
                                       Figure 4-19  Unit 2 Baseline Study
                                     Change in EER after Adsil Treatment
                                               All Temperatures
       0.25
       0.23
       0.21
       0.19
       0.17
       0.15
       0.13
       0.11
       0.09
       0.07
       0.05
       0.03
       0.01
      -0.01
                                      85
                                                                  90
                                                                                             95
                                                  OAT (F)
Source: MACTEC,2004.
Prepared by: _TBL_
Checked by:  CDM
Figure 4-20 Unit 2 Baseline Study
Efficiency Index (El) vs OAT for Pre-ADSIL Tests, All Temperatures
n QQ
n Qft
n QT
n QR

n QA
n Q^

n CM
OQ
• ^-'**
Post-Adsil v .^'^
\. j^^ ^


^ — ^ * \Pre-Adsil
^^





»Pre-Adsil El
• Post-Adsil El

80 85 90 95
OAT (F)
Source: MACTEC,2004.
Prepared by: _TBL_
Checked by: _CDM_
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                    4-23
                                                                                                     MACTEC

-------
                                                       Application ofAdsil in the NC/SC Charlotte Area
Comparison with Data Logger Evaluation
Traditional measurements of HVAC efficiency have been conducted by collecting data over an
extended period of time. This method is believed to be the most accurate for measuring true
operating efficiency of HVAC equipment, if the equipment is instrumented properly and sensors
are accurate. Ideally, actual air flow and enthalpy changes across the evaporator will be collected
and compared to the true power required to produce this cold air flow.  Actual power
measurements require that the voltage, amperage, and power factor be measured.

In the comparison test performed at a commercial property in Clearwater near the Florida west
coast, a Carrier 12-1/2-ton, dual-compressor package unit was chosen.  Instrumentation of this
unit was performed by a third party and the analysis of the data was also performed by a third
party. This report is included as Appendix D in this report. The third party testing began on
April 27, 2004 with the unit, RTU-2, being instrumented. On May 5, 2004 the unit was cleaned
and coated per standard operating procedures of the owner. On May 19, 2004, the unit was
cleaned and coated per the Adsil process.

Data collection was conducted from April 27 through May 31, 2004. Unfortunately, the actual
power was not measured, only the amperage; constant values of 0.85 for power factor and 208
volts for the voltage were assumed and used to estimate the power. Capacity measurements were
not made although the data could be used to determine capacity if compressor curves and tables
were incorporated in the calculation procedure. The unit had dual compressors which further
complicated the measurement process since the cycling of the second compressor had significant
impacts to both the power consumption and the condenser efficiency.

Refrigerant temperature drop across the condenser, ambient temperature, and refrigerant low and
high side pressures were recorded; however, capacity measurements of the condenser were not
provided by the third party study. Consequently, EER values were not determined by this third
party study complicating the comparison process. The study did provide a multiple linear
regression model to determine the daily energy variation with ambient temperature for the unit
pre-and post-treatment. Based on the results of this comparison, the energy savings resulting
from the treatment process were 3.9%.

MACTEC performed our standard Service Assistant and condenser efficiency determinations for
this same unit.  By using jumper cables on the panel board we manually controlled the
compressor operation to energize both the first and second stage during our testing. We did pre-
treatment testing on May 13 (ambient temperature of 78 degrees) and post-treatment testing on
July 21 (ambient temperature of 88 degrees). The data and results of this test may be seen in
Appendix D. The Service Assistant test showed a 20.6% increase in EER and the  condenser test
showed a -5.9% change in efficiency.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                          4-24                                   MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
Conclusions
The low ambient temperature pre-test (78 degrees) during MACTEC's pre-treatment test has been
shown to have the potential to skew test data (see the Unit 1 Baseline Study in Section 4 of this
report).  For this reason MACTEC believes that the results of our Service Assistant test are not
reliable for this site. The condenser test was conducted on a roof where there were measurable
breezes present, compromising the integrity of the flow measurements.  The third party
evaluation predicted a 3.9% savings in energy consumption but used assumptions which, in
MACTEC's experience could skew the range of predicted savings by as much as 150%, giving a
potential range of between -2% and 10% as the bounds on savings.

MACTEC does not think that conclusive results regarding this comparison were obtained.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                           4-25                                    MACTEC

-------
                                                                                                                 Application ofAdsil in the NC/SC Charlotte Area
               TABLE 4-5
               Unit 2 Baseline Study
               Generic Compressor Test Summary-All Temperatures
      EER at ARI Conditions
      Condensing unitCFM
      Capacity at ARI
      Coil Area
      Predicted EER =
9.27 BTU/W-h
3300 CFM (Listed)
4.67 tons
  22 sq-ft
9.07 BTU/W-h
Test Date
PRE

POST
24-May
1-Jul
1-Jul
1-Jul
1-Jul
1-Jul
1-Jul
1-Jul

1 6-Aug
1 6-Aug
11-Auq
11-Aug
31-Aug
31-Aug
31-Aua
HVAC Service Assistant

OAT
92
89
88
88
87
86
84
b3
Averages
91
89
89
85
82
88
bb
EWB
57
55
55
54
54
56
54
bb

57
54
59
59
57
54
b/
El
98%
96%
97%
95%
96%
97%
95%
9b%
96%
99%
99%
98%
96%
94%
97%
9/%
Cl
98%
95%
97%
93%
94%
96%
93%
92%
95%
98%
96%
94%
95%
90%
93%
93%
EER
8.83
9.01
9.24
9.04
9.27
9.52
9.58
9./3

9.05
9.28
9.24
9.60
9.80
9.23
9.26
Cap
4.24
4.16
4.26
4.08
4.14
4.26
4.15
4.13
4.18
4.26
4.20
4.13
4.25
4.07
4.08
4.1U
kW
5.60
5.60
5.60
5.51
5.51
5.51
5.51
b.42

5.51
5.51
5.42
5.51
5.80
5.80
b.bU
Averages 97% 94% 4.16
Change 1.1% -0.64% -0.54%
Physical Power and Capacity measurments
Cond Air, deg F
inlet
94
90
87
88
87
86
86
82

90
87
87
86
84
90
b9
exhaust
110
105
103
102
103
100
100
99

105
103
105
101
99
105
1U4
Cond Air
Ul (K.)
8.9
8.3
8.9
7.8
8.9
7.8
7.8
9.4
8.47
8.3
8.9
10.0
8.3
8.3
8.3
b.3
kW
4.81
4.64
4.66
4.60
4.64
4.42
4.44
4.33

4.61
4.65
4.62
4.46
4.3
4.57
4.b/
(kg/sec)
4.63
4.20
3.90
3.75
3.94
3.33
3.70
3.b1
3.91
4.53
4.40
4.92
4.48
4.24
4.61
4.U/

tons
11.76
10.01
9.92
8.35
10.02
7.40
8.23
1U.29

10.81
11.20
14.09
10.67
10.10
10.98
9. /U

EER
29.35
25.89
25.55
21.78
25.90
20.09
22.23
28.52
24.92
28.13
28.90
36.59
28.72
28.18
28.84
ZD.4/

cfm adj
0.38
0.38
0.38
0.38
0.38
0.38
0.38
U.3b
0.38
0.38
0.38
0.38
0.38
0.38
0.38
U.3b
8.65 4.47 29.26 0.38
2.11% 14.29% 17.45%
Source: MACTEC, 2004.   Prepared by: _TBL_
        Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - vldi
                                                                        4-26
                                                                                                                                               MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
                            5.   Measurements in EER

The majority of the units evaluated in this study were under preventive maintenance programs.
As part of these programs, coils are reported to be regularly cleaned.  No specific cleaning of the
coils was performed by MACTEC or Adsil prior to commencement of pre-treatment testing.
Many of the units were graded out to be very clean according to MACTEC's site inspection,
supporting the claims for regular coil cleanings. The impact of cleaning alone on the
performance of these units is not addressed in this report.

In previous sections of this report it was determined that the Service Assistant testing
methodology was the most accurate and reliable form of instantaneous efficiency measurement
procedure.  This section of the report will address the results of EER measurement in the SEQL
area. Unless otherwise specified, results recorded here are based on the Service Assistant
methodology.

 Initially there  were  150 units included in the proposed SEQL area sample. In calendar year
2003, prior to MACTEC's involvement, 75 of these units were coated with Adsil, effectively
eliminating them from the subject population. MACTEC inspected each of the remaining  75
units and successfully completed testing on 45 of these units.  The reasons for not testing the
other 30 units included the size (either too large or too small for the instruments we were using);
lack of electrical power disconnect at the  unit; and inability to get the unit(s) to operate.

Many of these units  contained a single compressor and circuit. These units were the most
straight-forward to test and data was collected and analyzed as described in the baseline tests.

Other variations included multiple compressors with a common condenser, evaporator and power
source; dual compressors in a single package unit with each compressor having a dedicated
condenser but  sharing the same evaporator circuit and power; and dual compressors sharing a
common condenser, evaporator, and power disconnect. A description of how each of these types
of equipment was analyzed is presented below.

Multiple Compressors. Common Condenser Circuit
Many of the package Trane units encountered at York Technical College possessed this
configuration.  Two  or more compressors discharged into a common manifold which went into a
single condenser coil.  When only one stage was energized, the efficiency of this type of unit is
higher than when both compressors are energized. All power measurements were made at the
local disconnect and included all operating compressors and condenser fans as well as the  blower.
In most cases all compressors were energized during both pre- and post-treatment testing.  The
recorded tonnage was equal to the tonnage of the active compressors.  All pre- and post-treatment
tests were conducted with the same  compressor configuration operating. If conditions could not
P:\EEG\Energy\EPAAdsilProject\FinalReport\EPAAdsilFinalReportwithedits -v2.doc      5~ 1                                     MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
be replicated in the post-treatment test, the data was marked invalid and was not used in this
report.

Dual Compressors. Dedicated Condenser
Many of the York package units encountered at the Monroe Aquatic Center possessed this
configuration.  A single package unit contained two independent circuits housed in separate
compartments with individual condenser fans and condenser housings with an intertwined
evaporator circuit.  These units shared a single power source. In some cases both compressors
were energized and both circuits were independently measured and analyzed.  In other cases only
one circuit was energized. Pre- and post-treatment tests were conducted on the same number of
circuits so as to ensure reliability of test measurements. Recorded tonnage was the nameplate
value of the unit. In most cases both circuits were energized.

Multiple Compressors. Shared Condenser
Some of the units, including those at the York Technical College Library, had this configuration.
In the event that only one stage is energized the condenser may work more efficiently than  if both
compressors are energized since the rejected heat from one circuit is not partially absorbed  by the
2nd circuit as when both are energized.  Pre- and post-treatment tests were conducted identically
and in most cases both circuits were energized.

Results-All Tests
A total of 395 tons of HVAC equipment was tested in this sample of 45 units over a temperatures
range of 70 to 96 degrees. The average increase in EER is presented in Table 5-1. The most
significant number presented in the table is the increase in EER for the ton-weighted average.
This value is seen to be 9.9% with a standard error of 1.5%.

Results-Valid Tests at All Temperatures
The validity of 15 of the tests was questionable due to several changes in conditions which  were
considered to be significant. These included nine (9) units with low refrigerant charge; one (1)
unit which had refrigerant added after the first test; and five (5) tests with differing condenser and
compressor operation. After eliminating these conditions, 30 tests were deemed valid
representing a total of 287 tons of HVAC equipment tested over a temperatures range of 70 to 96
degrees. Table 5-2 summarizes the results of these 30 tests. The ton-weighted average EER
improvement was determined to be  11.3% with a standard error of 1.8%.

Results-Valid Tests at Literature Temperatures
The validity of 15 of the tests was questionable due to tests being conducted at temperatures
below those published in the performance data for the HVAC equipment. Different
manufacturers  rate their equipment over different temperature ranges with data being available
for all of the units at temperatures of 85 degrees and above.  Data was available at temperatures
above 75 degrees on only three of the units and at temperatures above 80 degrees on only four of

P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc     5 ~2                                    MACTEC

-------
                                                           Application ofAdsil in the NC/SC Charlotte Area
the units. The most rigorous presentation of results requires that the results of these tests be
eliminated since the determination of efficiency below the supplied data requires assumptions and
extrapolations which may or may not be accurate.  Additionally, test results in our baseline
testing indicate that results are more significant when ambient temperatures exceed 85 degrees.
After eliminating these conditions, 15 tests were deemed valid representing a total of 107 tons of
HVAC equipment tested over a temperatures range of 85 to 94 degrees. A summary of these test
results is provided in Table 5-3.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                             5-3                                       MACTEC

-------
                                                                                                                                                                                                               Application ofAdsil in the NC/SC Charlotte Area
 TABLE 5-1
 Summary of All Tests at All Temperatures
Site
Concord Admin

Concord City Hall







Granite Quarry


Iredell Health Center



Locust City Hall

Monroe Aquatic Center







Monroe Aquatic Center


YTC Bid D
YTC- Hood Center







YTC - Library
YTC - Library
YTC Student Center

YTC Student Services
YTC Truck School
Unit
RTU-5
RTU-7
RTU-1
RTU-2
RTU-3
SS-1
SS-2
SS-3
SS-4
SS-5
SS-1
SS-2
SS-3
RTU-1
RTU-1 3
RTU-1 4
RTU-3
SS-1
SS-2
RTU-2
RTU-2
RTU-4
RTU-5
RTU-6
RTU-8
RTU-9
RTU-1 0
RTU-1 3
RTU-1 5
RTU-1 6
RTU-1
RTU-1 0
RTU-5
RTU-6
RTU-7
RTU-8
RTU-9
HP-1
HP-2
Unit 1
Unit 2
Ground
RTU-25
HP-1
SS-1
Age
6
6
5
5
5
2
5
2
11
7
13
9
3
12
12
12
12
7
7
7
7
7
7
7
7
7
7
7
2
2
4
13
12
13
13
13
12
4
12
13
13
Un10
13
13
15
                      Per Unit
                      Ton-Weighted
Pre-test Post-test
OAT OAT
93 93
92 93
81 87
86 89
86 88
85 88
87 92
91 89
93 89
88 87
79 95
77 94
77 92
87 79
87 80
88 80
83 79
93 87
94 89
88 91
85 88
90 85
93 84
95 88
97 85
88 87
85 89
92 93
94 79
96 80
88 85
77 NA
80 77
84 78
70 85
76 78
76 90
79 82
77 74
75 85
77 88
81 84
84 86
74 83
85 86
Service Assistant
Tons
tested
8
9
5
5
5
5
6
4
2
3
5
5
5
3
5
6
3
3
3
7
7
5
5
5
21
12
8
21
7
5
4
24
24
29
24
18
23
3
5
17
17
24
5
7
9
Pre-Adsil
EER
11.76
10.19
11.76
11.76
11.88
11.30
9.45
10.67
7.61
9.06
8.47
7.95
9.11
9.70
9.20
NA
9.70
12.55
11.87
11.14
10.58
8.58
7.82
11.19
8.96
7.91
10.71
9.07
10.52
8.11
7.09
6.35
9.62
9.99
7.65
11.63
9.18
9.84
7.03
8.53
9.25
7.84
7.89
10.14
10.44
Post Adsil
EER
11.76
10.78
12.00
12.48
12.48
12.13
9.97
10.01
7.69
8.34
8.66
9.79
NA
10.17
9.79
10.76
9.89
12.98
12.51
11.03
11.14
9.23
8.91
10.75
10.24
9.12
11.87
11.63
10.92
8.57
9.55
NA
9.72
9.89
10.56
12.41
10.36
10.78
8.22
9.45
8.53
8.89
8.40
12.15
11.40
% Change
0.0%
5.8%
2.0%
6.1%
5.1%
7.3%
5.6%
-6.3%
1.1%
-7.9%
2.2%
23.2%
NA
4.9%
6.4%
NA
2.0%
3.4%
5.4%
-1.0%
5.3%
7.6%
13.9%
-3.9%
14.3%
15.3%
10.9%
28.2%
3.8%
5.6%
34.7%
NA
1.0%
-1 .0%
38.0%
6.7%
12.8%
9.5%
16.9%
10.7%
-7.7%
13.5%
6.6%
19.8%
9.2%
Ton
weighted
avg.
0.0%
54.1%
10.7%
32.0%
26.4%
40.0%
31 .7%
-23.9%
2.5%
-21 .8%
10.5%
115.9%
NA
14.5%
33.1%
NA
5.8%
10.2%
16.1%
-7.5%
39.4%
39.9%
73.0%
-20.4%
295.9%
182.2%
83.0%
584.8%
28.3%
29.3%
138.7%
NA
24.0%
-27.9%
922.9%
122.7%
291 .2%
27.1%
81 .4%
185.2%
-133.0%
325.9%
34.1%
146.4%
84.4%
Condensing
Tons
tested
8.41
9.31
5.23
5.23
5.23
5.48
5.71
3.83
2.35
2.75
4.78
5.00
5.00
2.97
5.19
6.30
2.97
3.00
3.00
7.49
7.49
5.25
5.25
5.25
20.71
11.88
7.63
20.71
7.44
5.21
4.00
23.98
23.98
28.74
24.30
18.41
22.67
2.84
4.82
17.29
17.29
24.17
5.19
7.40
9.19
Pre-Adsil
EER
17.45
47.97
NA
NA
NA
14.79
15.61
22.24
18.70
NA
NA
NA
NA
19.79
17.58
18.59
22.41
NA
NA
24.54
16.44
14.03
16.59
19.36
8.09
18.84
19.25
15.57
26.63
22.06
NA
11.72
21.13
NA
NA
19.76
13.15
15.47
NA
7.42
6.00
NA
NA
NA
10.91
Post Adsil
EER
36.04
56.62
NA
NA
NA
27.07
27.88
21.75
19.83
NA
NA
NA
NA
32.96
21.62
17.54
20.42
NA
NA
22.68
24.28
20.07
16.34
24.02
20.18
17.47
22.05
23.30
23.52
21.93
NA
9.32
16.08
NA
NA
17.04
24.74
25.34
NA
15.81
15.15
NA
NA
NA
14.82
% Change
106.6%
18.0%
NA
NA
NA
83.0%
78.6%
-2.2%
6.1%
NA
NA
NA
NA
66.6%
23.0%
-5.7%
-8.9%
NA
NA
-7.6%
47.6%
43.1%
-1.5%
24.0%
149.5%
-7.3%
14.5%
49.7%
-1 1 .6%
-0.6%
NA
-20.5%
-23.9%
NA
NA
-13.7%
88.1%
63.8%
NA
113.2%
152.3%
NA
NA
NA
35.9%
Ton
weighted
avg.
896.6%
167.9%
NA
NA
NA
455.2%
448.9%
-8.4%
14.3%
NA
NA
NA
NA
197.5%
119.1%
-35.7%
-26.3%
NA
NA
0.6%
18.8%
17.2%
-1.1%
-4.9%
442.3%
-13.2%
12.1%
290.4%
-3.3%
-0.2%
NA
-491.1%
-573.3%
NA
NA
-253.1%
1997.4%
181.2%
NA
1956.7%
2633.7%
NA
NA
NA
329.4%
Spreadshee
Pre-Adsil
EER
10.50
11.32
11.65
11.19
11.14
11.35
9.84
10.77
7.05
7.43
NA
NA
NA
8.00
8.51
9.18
8.06
11.65
11.65
10.74
10.74
10.39
10.17
10.17
9.35
9.39
10.70
9.98
10.19
9.25
8.04
8.59
8.85
7.96
8.08
7.81
9.21
8.93
8.76
8.82
9.08
7.19
9.10
9.57
9.13
Post Adsil
EER
11.08
11.62
11.88
11.88
11.88
12.01
10.39
11.32
7.49
8.70
NA
NA
NA
8.80
9.06
9.96
8.80
11.88
11.88
10.81
10.83
10.56
10.56
10.56
10.19
10.22
10.77
10.44
10.21
9.26
9.45
8.82
8.85
8.89
8.93
8.86
9.53
9.37
9.16
9.32
9.32
8.23
9.51
10.23
9.60
                           35.28  (tons not counted)
                          395.01                       8.02%

                                standard deviation        9.7%
                                             count       42
                                      standard error     1.5%
9.90%
137.83  (tons not counted)
292.46                       36.6%

      standard deviation       43.5%
                   count       29
            standard error     8.1%
30.0%
                                                                                                                                                   standard deviation
                                                                                                                                                                count
                                                                                                                                                         standard error
Source:  MACTEC, 2004.
Prepared by: _TBL_    Checked by: _CDM_
P:\EEG\Energy\EPA Adsil PrqjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                                                        5-4
                                                                                                                                                                                                                                           MACTEC

-------
                                                                                                                                                                                   Application ofAdsil in the NC/SC Charlotte Area
 Table 5-2
 Summary of Valid Tests at All Temperatures
           Site
         Concord Admin
        Concord City Hall
     Iredell Health Center
         Locust City Hall
   Monroe Aquatic Center
   Monroe Aquatic Center
              YTC Bid D
       YTC- Hood Center
            YTC - Library
     YTC Student Center
    YTC Student Services
       YTC Truck School

Unit
RTU-7
RTU-2
RTU-3
SS-1
SS-2
SS-4
SS-5
RTU-1
RTU-13
RTU-3
SS-2
RTU-1
RTU-2
RTU-9
RTU-1 0
RTU-13
RTU-1 5
RTU-1 6
RTU-1
RTU-5
RTU-6
RTU-7
RTU-8
RTU-9
HP-1
HP-2
Unitl
RTU-25
HP-1
SS-1

Age
6
5
5
2
5
11
7
12
12
12
7
7
7
7
7
7
2
2
4
12
13
13
13
12
4
12
13
13
13
15
P re-test
OAT
92
86
86
85
87
93
88
87
87
83
94
94
85
88
85
92
94
96
88
80
84
70
76
76
79
77
75
84
74
85
                         Per Unit
                         Ton-Weighted
Post-test
OAT
93
89
88
88
92
89
87
79
80
79
89
91
88
87
89
93
79
80
85
77
78
85
78
90
82
74
85
86
83
86
Service Assistant
Tons
tested
9
5
5
5
6
2
3
3
5
3
3
7
7
12
8
21
7
5
4
24
29
24
18
23
3
5
17
5
7
9
Pre-Adsil
EER
10.19
11.76
11.88
11.30
9.45
7.61
9.06
9.70
9.20
9.70
11.87
10.58
10.58
7.91
10.71
9.07
10.52
8.11
7.09
9.62
9.99
7.65
11.63
9.18
9.84
7.03
8.53
7.89
10.14
10.44
Post Adsil
EER
10.78
12.48
12.48
12.13
9.97
7.69
8.34
10.17
9.79
9.89
12.51
11.03
11.14
9.12
11.87
11.63
10.92
8.57
9.55
9.72
9.89
10.56
12.41
10.36
10.78
8.22
9.45
8.40
12.15
11.40
%
Change
5.8%
6.1%
5.1%
7.3%
5.6%
1.1%
-7.9%
4.9%
6.4%
2.0%
5.4%
4.2%
5.3%
15.3%
10.9%
28.2%
3.8%
5.6%
34.7%
1 .0%
-1 .0%
38.0%
6.7%
12.8%
9.5%
16.9%
10.7%
6.6%
19.8%
9.2%
Ton
weighted
avg.
54.1%
32.0%
26.4%
40.0%
31 .7%
2.5%
-21 .8%
14.5%
33.1%
5.8%
16.1%
31 .5%
39.4%
182.2%
83.0%
584.8%
28.3%
29.3%
138.7%
24.0%
-27.9%
922.9%
122.7%
291.2%
27.1%
81 .4%
185.2%
34.1%
146.4%
84.4%
Condensing
Tons
tested
9.31
5.23
5.23
5.48
5.71
2.35
2.75
2.97
5.19
2.97
3.00
7.49
7.49
11.88
7.63
20.71
7.44
5.21
4.00
23.98
28.74
24.30
18.41
22.67
2.84
4.82
17.29
5.19
7.40
9.19
Pre-Adsil
EER
47.97
NA
NA
14.79
15.61
18.70
NA
19.79
17.58
22.41
NA
17.50
16.44
18.84
19.25
15.57
26.63
22.06
NA
21.13
NA
NA
19.76
13.15
15.47
NA
7.42
NA
NA
10.91
Post Adsil
EER
56.62
NA
NA
27.07
27.88
19.83
NA
32.96
21.62
20.42
NA
22.68
24.28
17.47
22.05
23.30
23.52
21.93
NA
16.08
NA
NA
17.04
24.74
25.34
NA
15.81
NA
NA
14.82
%
Change
18.0%
NA
NA
83.0%
78.6%
6.1%
NA
66.6%
23.0%
-8.9%
NA
29.6%
47.6%
-7.3%
14.5%
49.7%
-1 1 .6%
-0.6%
NA
-23.9%
NA
NA
-13.7%
88.1%
63.8%
NA
113.2%
NA
NA
35.9%
Ton
weighted
avg.
167.9%
NA
NA
455.2%
448.9%
14.3%
NA
197.5%
119.1%
-26.3%
NA
9.3%
18.8%
-13.2%
12.1%
290.4%
-3.3%
-0.2%
NA
-573.3%
NA
NA
-253.1%
1997.4%
181.2%
NA
1956.7%
NA
NA
329.4%
Spreadshee
Pre-Adsil
EER
11.32
11.19
11.14
11.35
9.84
7.05
7.43
8.00
8.51
8.06
11.65
10.74
10.74
9.39
10.70
9.98
10.19
9.25
8.04
8.85
7.96
8.08
7.81
9.21
8.93
8.76
8.82
9.10
9.57
9.13
Post Adsil
EER
11.62
11.88
11.88
12.01
10.39
7.49
8.70
8.80
9.06
8.80
11.88
10.81
10.83
10.22
10.77
10.44
10.21
9.26
9.45
8.85
8.89
8.93
8.86
9.53
9.37
9.16
9.32
9.51
10.23
9.60
                                        0.00  (tons not counted)
                                      286.83                        9.33%

                                            standard deviation        9.7%
                                                          count        30
                                                  standard error      1.8%
11.31%
 90.65 (tons not counted)
196.18                       32.6%

       standard deviation       35.1%
                    count       20
             standard error     7.9%
27.2%
                                                                                                                                                              standard deviation
                                                                                                                                                                            count
                                                                                                                                                                    standard error
Source:  MACTEC, 2004.
Prepared by: _TBL_   Checked by: _CDM_
P:\EEG\Energy\EPA Adsil PrqjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                                        5-5
                                                                                                                                                                                                           MACTEC

-------
                                                                                                                                                                                  Application ofAdsil in the NC/SC Charlotte Area
 Table 5-3
 Summary of Valid Tests at Literature Temperatures
                                            P re-test
          Site              Unit      Age      OAT
         Concord Admin RTU-7    6               92
       Concord City Hall RTU-2    5               86
                        RTU-3    5               86
                        SS-1     2               85
                        SS-2     5               87
                        SS-4     11              93
                        SS-5     7               88
         Locust City Hall SS-2     7               94
  Monroe Aquatic Center RTU-1    7               94
                        RTU-2    7               85
                        RTU-9    7               88
                        RTU-10   7               85
                        RTU-13   7               92
             YTC Bid D RTU-1    4               88
      YTC Truck School SS-1     15              85
                        Per Unit
                        Ton-Weighted
Post-test
OAT
93
89
88
88
92
89
87
89
91
88
87
89
93
85
86
Service Assistant
Tons
tested
9
5
5
5
6
2
3
3
7
7
12
8
21
4
9
Pre-Adsil
EER
10.19
11.76
11.88
11.30
9.45
7.61
9.06
11.87
10.58
10.58
7.91
10.71
9.07
7.09
10.44
Post Adsil
EER
10.78
12.48
12.48
12.13
9.97
7.69
8.34
12.51
11.03
11.14
9.12
11.87
11.63
9.55
11.40
%
Change
5.8%
6.1%
5.1%
7.3%
5.6%
1.1%
-7.9%
5.4%
4.2%
5.3%
15.3%
10.9%
28.2%
34.7%
9.2%
Ton
weighted
avg.
54.1%
32.0%
26.4%
40.0%
31 .7%
2.5%
-21 .8%
16.1%
31 .5%
39.4%
182.2%
83.0%
584.8%
138.7%
84.4%
Condensing
Tons
tested
9.31
5.23
5.23
5.48
5.71
2.35
2.75
3.00
7.49
7.49
11.88
7.63
20.71
4.00
9.19
Pre-Adsil
EER
47.97
NA
NA
14.79
15.61
18.70
NA
NA
17.50
16.44
18.84
19.25
15.57
NA
10.91
Post Adsil
EER
56.62
NA
NA
27.07
27.88
19.83
NA
NA
22.68
24.28
17.47
22.05
23.30
NA
14.82
%
Change
18.0%
NA
NA
83.0%
78.6%
6.1%
NA
NA
29.6%
47.6%
-7.3%
14.5%
49.7%
NA
35.9%
Ton
weighted
avg.
167.9%
NA
NA
455.2%
448.9%
14.3%
NA
NA
9.3%
18.8%
-13.2%
12.1%
290.4%
NA
329.4%
Spreadshee
Pre-Adsil
EER
11.32
11.19
11.14
11.35
9.84
7.05
7.43
11.65
10.74
10.74
9.39
10.70
9.98
8.04
9.13
Post Adsil
EER
11.62
11.88
11.88
12.01
10.39
7.49
8.70
11.88
10.81
10.83
10.22
10.77
10.44
9.45
9.60
                                       0.00  (tons not counted)
                                     107.44                        9.07%

                                           standard deviation       10.1%
                                                         count        15
                                                 standard error      2.6%
12.33%
20.20 (tons not counted)
87.24                       35.6%

      standard deviation       28.5%
                   count       10
            standard error     9.0%
19.9%
                                                                                                                                                             standard deviation
                                                                                                                                                                          count
                                                                                                                                                                   standard error
Source:  MACTEC, 2004.
Prepared by: _TBL_   Checked by: _CDM_
P:\EEG\Energy\EPA Adsil PrqjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                                       5-6
                                                                                                                                                                                                           MACTEC

-------
                                                           Application ofAdsil in the NC/SC Charlotte Area
The increase in EER varied from a low of 9.9% in the Service Assistant test for all units to a high
of 30% using the condenser test methodology on the same sample. It is MACTEC's opinion that
the test results from the Service Assistant tests conducted within the range of manufacturer's
published EER values provide the most reliable prediction of energy savings. The increase in
efficiency of the units in this study is therefore estimated to be 12.3%.  Complete results are
provided in Appendix F.  Figure 5-1 graphically depicts the change in EER based on the Service
Assistant measurements on this sample.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                             5-7                                      MACTEC

-------
                                                                                                                                     Application ofAdsil in the NC/SC Charlotte Area
                                                                                     Figure 5-1
                                                              Service Assistant, Valid Tests at Literature Temperatures
            RTU-7        RTU-2
Source:  MACTEC,2004.
Prepared by: _TBL_
Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                               5-S
                                                                                                                                                                        MACTEC

-------
                                                       Application ofAdsil in the NC/SC Charlotte Area
                          6.   Projected Energy Savings

A total of 150 units in the SEQL area were cleaned and coated with Adsil representing a total of
2,545 tons of HVAC equipment.  Based on MACTEC's measurement of the change in EER, an
improvement in efficiency of 12.3% is expected in this population. Appendix G contains the
calculation details and assumptions but for convenience  the key elements are repeated.  The
National Oceanic and Atmospheric Administration (NOAA) lists the cooling degree days (CDD)
for the Charlotte area at 1,648.  This number represents the amount of time that the temperatures
are above 65 degrees with each degree above 65 being weighted heavier than the one before.
Twenty-four hours of a 66-degree temperature represent one CDD; conversely, one hour of 89
degree temperature also represents one  CDD. The American Society of Heating, Refrigeration,
and Air-Conditioning Engineers (ASHRAE) suggests that the number of Full Load Equivalent
Operating Hours (FLEOH) of apiece of equipment is roughly equal to 80% of the CDDs.

Using these inputs and others detailed in Appendix G, MACETC estimates that the application of
Adsil to this population will result in an annual energy savings of 461,400 kilowatt-hours (kWh)
and an annual cost savings in excess of $37,000.  These  energy savings result in lowered
production from power plants and should, consequently, result in decreased emissions.  However,
because of the complexities of the power transfers over the power grid, it is difficult to verify or
quantify pollution benefits and to do so is beyond the scope of this project.

A tool for projecting energy savings at an individual  facility or group of facilities is provided in
Figure 6-1. Required inputs are highlighted in yellow. Providing data to these fields will
automatically estimate annual energy and cost savings for a facility or facility group.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                           6-1                                    MACTEC

-------
                                                               Application ofAdsil in the NC/SC Charlotte Area
                        FIGURE 6-1 ENERGY SAVINGS PROJECTION TOOL
              Facility: Your Facility Name
                      Capacity of HVAC Units
         ECP Savings:      371.67 Electric Demand kW
                        $36,915   Electric Energy Cost Savings

    Total ECP Savings:   $36,915   Total Annual Cost Savings
            ECP Cost:   $165,425
             Payback:    4.48     yrs (excluding maint savings)
                             461,440  Electric Energy kWh
                              1,574   Electric Energy MMBtu

                              1,574   Total Annual MMBtu Savings
                                            Calculations

     Assumptions:     This recommendation is applied in the following instances:
                         1) New equipment
                         2) Existing equipment with evidence of minor environmental damage
                         3) Equipment with five years of useful life remaining
                      The protective corrosion inhibitor is MicroGuard (TM) product from Adsil (TM)
                      Charlotte area has 1644 cooling degree days (CDD) per NOAA
                      Full-load equivalent operating hours = FLEOH= 0.8*CDD
                      Decrease in EER is assumed to be both an increase in power consumption
                       and capacity degradation
                      Savings to heat pumps during the heating season are not included
                      Average EER=9.0
                      Average EER gain =12.3%
                      Nominal capacity is total tonnage at facility. Available from equipment nameplate data.
                       May be estimated by taking total facility square footage and dividing by 400.
                      CDD from website      http://lwf.ncdc.noaa.gov/oa/climate/online/ccd/nrmcdd.html
                          1644
                          1,315
                         $0.000
                        $0.08000
                        0.003412
                         12.3%
CDD     use website to get CDD for your city
FLEOH
Demand Cost per kW
Energy Cost per kWh
MMBtu/kWh
EER gain use default of 12.3% or value from degradation tool
  use blended electric rate
 HVAC System Data
 Condensing Unit Data from:
 Condensing Unit Consumption:
 Calculated EER:

 EER after coil application
 kW/ton after coil application
 Demand Consumption
SEQL Area
 3393.33 kW
   10.1   Btu/W-hr

  10.11
   1.19
 3021.67
     Nominal Capacity:
Present Condition EER:
           kW/ton=
2545.0  tons
  9.0    Btu/W-hr
 1.33
Source:  MACTEC, 2004.
Prepared by :_TBL_
Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportXEPA Adsil Final Report with edits - v2.doc
                                                6-2
                                                                                            MACTEC

-------
                                                               Application ofAdsil in the NC/SC Charlotte Area
                   FIGURE 6-1 ENERGY SAVINGS PROJECTION TOOL (continued)

              Facility: Your Facility Name
                      Capacity of HVAC Units
 Current Run-time Adjustment Factors
 Night Setback:             1.000    Note 1
 FLEOH Conversion:        0.800
 Proposed Run-time Adjustment Factors
 Night Setback:             1.000
 FLEOH Conversion:        0.800
Excess Capacity:
Weekend Setback:
Cooling Set Point:
Excess Capacity:
Weekend Setback:
Cooling Set Point:
 Run-time Estimates
 Current condensing unit:
 Proposed condensing unit:
1,242  hours - annually
1,242  hours - annually
                                     kW

                           Current 3393.333
                         Proposed 3021.668
                           Savings
                   kWh

                 4,212,989
                 3,751,548
                  461,440
                                          Installation Costs
 Nominal capacity:
 Cost associated to install coating (parts & labor):
                      Total project cost:
                                      1.000
                                      1.000   Note 2
                                      72.00   Degrees F
                                      1.000
                                      1.000
                                      72.00   Degrees F
                   2,545  tons
                    $65   per ton (total installed cost)
                          (vendor quotation)

                 $165,425
 Note 1: Use a night setback value of .95 if HAVC equipment does not run at night after 6:00 P.M. Use 1  if no
        setback is used.
 Note 2: Use a weekend setback value of .75 is HVAC is turned off for the weekend.  Use .875 if it is turned off
       for one day during the weekend.
Source: MACTEC, 2004.
Prepared by: _TBL_
Checked by: _CDM_
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                 6-3
                                                                                             MACTEC

-------

-------
                                                       Application ofAdsil in the NC/SC Charlotte Area
             7.   Estimated Degradation in HVAC Performance

The estimation of air conditioning condensing unit performance degradation was based on a
combination of objective input factors. The development of degradation prediction equations was
based on empirical data we collected from testing in this program. MACTEC has previously
found that degradation of HVAC equipment is influenced by many factors, including compressor
wear, evaporator coil fouling and deterioration (resulting primarily in increased equipment run
time and decreased capacity) and condenser coil degradation (resulting in a decrease in efficiency
and an increase in power consumption).  It is inherently difficult to predict equipment degradation
over time. This is due in part to the difficulty in conducting a statistically significant study that
controls or measures the large number of variables involved (compressor type, age and condition;
condenser coil coating and condition; evaporator coil condition; indoor temperature and humidity
conditions; under/overcharge of refrigerant; ambient weather conditions; and quality of
equipment installation to name a few).

To begin the process, nameplate data for each of 45 units being tested was field-collected and the
efficiency of the unit when new was determined from manufacturer's literature at a range of
ambient conditions. MACTEC then measured the efficiency of each HVAC unit and determined
the degradation in EER, compared with published data at the same conditions (ambient
temperature and entering wet-bulb temperature) when new.

A spreadsheet was developed which weighted various condenser conditions, including age, coil
cleanliness, fin condition, fin-tube attachment, and corrosion.  These categories are objectively
graded by algorithms contained in this degradation prediction tool, shown in Figure 7-1. The
results of the spreadsheet EER degradation prediction model was compared with the results of the
Service Assistant measurements for the two sample groups: Valid Test Results, and Valid Test
Results at Literature Temperatures.

The spreadsheet model predicted an EER degradation of 11.49% compared with a Service
Assistant degradation of 11.50% (ton-weighted average) and 10.31% (unit average).  These
results are presented in Appendix H. A second comparison was made with the results compiled
from the summary tests of the population of units contained in the tests performed within the
realm of literature published temperatures. In this case, the spreadsheet model predicted an EER
degradation of 10.45%. The  Service Assistant measurements  resulted in an EER degradation of
13.14% (ton-weighted average) and 11.00% (unit average). These results are also presented in
Appendix H.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                           7-1                                    MACTEC

-------
                                                                      Application ofAdsil in the NC/SC Charlotte Area
                               FIGURE 7-1  Degradation Prediction Tool
  Manufacturer:
  Model Number:
  Serial Number
  Equipment Type:
  Year Manufactured:
  Location
  Tag

  Compressor Data
  Running load Amps:
  Nameplate Voltage:
  Power factor:

  Condensing Fan Data
  Full load Amps:
  Nameplate Voltage:
  Adjust FLA to RLA:
Brand X
Big Guy 60
123456
Split-System
1999
ACME Warehouse
SS-2
   18.0   Amps
   208   Volts
   0.80
   1.40   Amps
   208   Volts
   0.70
Published EER:        10.2
Calculated EER:       10.8
Nominal Capacity:     5.00
Age                    5
Coil Conditon         12%
Present Condition E    9.6
kW/ton                1.25
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
Power supply:        3-phase
Phase adjustment:      1.73
Compressor quantity:     1
Power supply:        3-phase
Phase adjustment:      1.73
Fan quantity:            1
(=1.0 if single phase)
(=1.0 if single phase)
  Evaporator fan data (if applicable)
  Full load Amps:           NA   Amps
  Nameplate Voltage:        NA   Volts
  Adjust FLA to RLA:        0.70

  Calculated compressor load:
  Calculated condensing fan load:
  Calculated evaporator fan load
  Total calculated load for equipment:
  Assumptions
                             Power supply:
                             Phase adjustment:
                             Fan quantity:
                  1 or 3-phase
                    1 or 1.73
                      NA
                      5.2    kW
                      0.35    kW
                   #VALUE!  kW
                      5.53    kW - Condensing side only
 Condenser Coil Assessment
 Age of Unit            	
           New
           2-9 years
           10-14 years
           15 or more
 Coil Cleanliness
           Coated
           Clean
           Dirty
           Clogged
           Plugged
 Fin Condition
           Like New
           Some  Bent
           Smashed
           Dull/rough
           Corroded
           Pitted
           Flaking
 Fin-Tube Attachment
           Like New
           Corrosion
           Some  Loose
           Many Loose
 Tubes
           Clean Cu
           Corrosion
           Pitting
           Leaks
   0.7
   0.2
   0.1
   0.1
   0.05
   0.9
           12.3%   Performance Degradation

                             Put a "1" in the approf
                             correspond with the ai
Put a "1" if unit is currently coated
Place a percentage (.01-1) to represent
percentage of the fins that are considered
to be clean, dirty, clogged, or plugged.  These
must sum to 100%

Percentage in "like new" condition
Percentage "bent"
Percentage "smashed"
Percentage "dull/rough, corroded, pitted,
& flaking" plus percentage "like new",
must equal 100%.
                             Place a"1" in the appropriate cell
                             Place a"1" in the appropriate cell
Source: MACTEC, 2004.
Prepared by: _TBL_
Checked by: _CDM_
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.doc
                                                      7-2
                                                                                                       MACTEC

-------
                                                         Application ofAdsil in the NC/SC Charlotte Area
The impact of various factors on the degradation of the unit are included in Appendix H. It is of
interest to note that the age of the unit had little impact on the degradation of the coil (see
Figure 7-2). Figure 7-3 graphically depicts the comparison of spreadsheet predicted EER
degradation with actual measured degradation. This must be differentiated from the degradation
of the unit as a whole because the scope of this project was confined to the recoverable portion of
the EER due to Adsil treatment and did not address other contributing factors (compressor wear,
evaporator degradation, refrigerant charge, etc.)  which would not be impacted by condenser coil
restoration. The fin condition and the dirt factor were observed to have the greatest impact on the
decrease in performance, as shown in Figure 7-4 and Figure 7-5. Corrosion was observed to have
a negative impact on the degradation of these units (see Figure 7-6); however, this may be
misleading due to the almost complete lack of corrosion present in this population. Because the
corrosion  was minimal, other contributing factors controlled the degradation resulting in an
apparent increase  in EER when compared with corrosion factor as a stand-alone attribute. In
aggressive environments or corroded coil units, this attribute would be expected to contribute to
the decrease in performance.  A comparison was also done to compare the EER Degradation vs
capacity.  Figure 7-7 shows that the larger units had greater degradation.  This has a measurable
impact on the comparison of the unit average degradation as compared with the weighted-average
degradation. Further discussion on this issue will be presented in Section 8.

There is a large variance in the data which is shown by low correlation coefficients for each of
these comparisons.  This may result in a potentially large error when a single HVAC unit is
evaluated  using this spreadsheet. However, this error should be normalized when used in larger
populations resulting in a more accurate prediction of population EER degradation. This position
is supported by the close correlation in EER population degradations (Spreadsheet vs Service
Assistant methodologies) as discussed earlier.

The accuracy of this tool has not been tested in significantly different climactic areas and there
may be additional attributes which need to be considered in these cases.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                            7-3                                     MACTEC

-------
                                                                                                                                        Application ofAdsil in the NC/SC Charlotte Area
     ro
     T3
     ro
     D)
     tu
     T3
0.35

 0.3

0.25

 0.2

0.15

 0.1

0.05

    0
                                               Figure 7-2 Degradation of Units Compared with Age
                                                   Weighted Average, Literature Valid Tests
                                                                        10
                                                                            12
       14
16
                                                         Age of Unit
Source:  MACTEC, 2004.    Prepared by: _TBL_
                                                    Checked by:  CDM
                                                                                      Figure 7-3
                                                             Visual vs Service Assistant Degradation, Literature Valid Tests
           RTU-7      RTU-2      RTU-3
          Concord   Concord City
           Admin       Hall
                                                                        SS-2
                                                                      Locust City
                                                                        Hall
 RTU-1
Monroe
Aquatic
Center
 Unit
           RTU-10     RTU-13     RTU-1      SS-1
                             YTC Bid D  YTC Truck
                                         School
                                                                                                                                                                       Average
Source:  MACTEC, 2004.    Prepared by: _TBL_
                                                              Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                        7-4
                                                                                                                                                                           MACTEC

-------
                                                                                                                            Application ofAdsil in the NC/SC Charlotte Area






g
(D
05

'E
Z>




Figure 7-4 Degradation of Unit vs Fin Condition
Weighted Average, All Literature Valid Tests

0.35 -i
0.3 -

0.25 -
0.2 -
0.15 J
0.1 -

0.05 -
o -


» Fin Condition Factor vs
Degradation

^^^
^^^^
^^^^
^^^^
.^^^^
^
^~^^ +
' * •
1
•
iii
0 0.2 0.4 0.6 0.8 1
Fin Structural Condition Factor
















1.2

Source: MACTEC, 2004.   Prepared by:  _TBL_
Checked by:  CDM

adation
0)


Figure 7-5 Degradation of Unit vs Dirt Factor
0.35 -i
0.3
0.25
0.2
0.15
0.1 -
0.05 ;
0
C
Weighted Average, Literature Valid Tests
„

* Degrad
I
^^^^^
^ — r
^ » I
^^^^^
K »** •» I
• I
) 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
Dirt Factor


Factor vs
ation



Source: MACTEC, 2004.   Prepared by: _TBL_         Checked by: _CDM_
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                 7-5
                                                                                                                                                            MACTEC

-------
                                                                                                                                       Application ofAdsil in the NC/SC Charlotte Area
                    0.35 T
                                               Figure 7-6 Degradation of Unit vs Corrosion
                                                Weighted Average, Literature Valid Tests
                                       0.2
0.4
       0.6
Corrosion Factor
0.8
1.2
Source:  MACTEC, 2004.    Prepared by: _TBL_
      Checked by:  CDM
       0.35 1
        0.3
       0.25
io
        0.2
       0.15
        0.1
       0.05
                                              Figure 7-7 Degradation of Unit vs Capacity
                                             Weighted Average, All Literature Valid Tests
                                     10
                                                  15          20
                                                  Capacity of Unit
                                                                           25
                                                                                        30
                                                                                                    35
Source:  MACTEC, 2004.    Prepared by: _TBL_
      Checked by:  CDM
P:\EEG\Energy\EPA Adsil ProjectVFinal ReportVEPA Adsil Final Report with edits - v2.di
                                                                                        7-6
                                                                                                                                                                           MACTEC

-------
                                                        Application ofAdsil in the NC/SC Charlotte Area
                            8.   Statistical Significance

The results of the SEQL area testing were evaluated to determine the statistical significance of the
study.  This statistical testing was based on individual unit results; however, the EER
improvements realized for the ton-weighted average were greater than for the unit average.  A
clearly defensible statistical method for evaluating units on a ton-weighted average was not easily
discerned so it was decided to measure the significance based on a unit average and apply the
results to the ton-weighted average approach.

For each unit with both pre- and post-Adsil treatment EER results, the % difference in efficiency
{100 x (EER, post-treatment - EER, pre-treatment)/EER, pre-treatment} was tabulated. Thus a
positive change indicates an efficiency improvement. This data set (% Change in EER) was tested
to determine if it exhibited a normal distribution. Statistical tests were performed in SYSTAT  10
(SPSS, Inc. 2000), and the test for normality was Lilliefors and the level of significance selected
was 0.05 (indicating 95% confidence that the data were drawn from a normal population). If the
data passed the test of normality, then the 't' test was used to determine whether the average
improvement was significantly greater than zero. This procedure is equivalent to performing a
paired 't' test on the two (pre- and post-) data sets. The  significance was evaluated at a level of
0.05. In fact all data sets exhibited significant improvement with significance less than 0.01,
indicating 99% confidence that Adsil treatment resulted in an improvement in efficiency.

If the % Change in EER data sets did not follow a normal distribution, then the nonparametric
equivalent of a paired 't' test, the Wilcoxon signed rank test, was used to determine the effect of
Adsil treatment.

All data sets showed an improvement in EER post-Adsil treatment, when compared with
pre-treatment EER.  The model results are presented in  Appendix I.

The relationship between EER improvement and unit capacity (tons) was demonstrated in
Section 7 and shown in Figure 7-7; therefore ton-weighted averages are expected to exhibit
similar improvement as the results obtained from individual unit comparisons, and ton-weighted
improvements are also expected to be statistically significant.

After determining that each data set exhibited significant improvement, the average and standard
error for each data set was determined, as well as the upper and lower confidence intervals of the
average improvement. These results indicate typical improvements that may be expected in
various populations, as well as the range in potential improvements.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                           8-1                                    MACTEC

-------

-------
                                                       Application ofAdsil in the NC/SC Charlotte Area
                   9.  Summary of Results and Conclusions

MACTEC evaluated the impact ofAdsil application to 45 HVAC units in the SEQL area and to
three units outside the SEQL area.  The results of this evaluation show that the Adsil treatment
can be expected to improve the efficiency of existing HVAC units by approximately 12% based
on the ton-weighted average method used in this project. The data was statistically evaluated and
determined to be significant at the 99% confidence level.

Utility bill analysis was determined to be an inappropriate measurement tool for EER changes
and therefore actual efficiency measurements for each HVAC unit were performed.  Three tests
were used including a calculation method, a power and capacity measurement, and a refrigerant-
based measurement using the Service Assistant as available from Honeywell Controls.

Two baseline studies were conducted to establish the accuracy of each testing protocol and which
involved repeated tests on two units. Repeatability in measurements was demonstrated in these
tests and it was determined that the Service Assistant instrument provided the most repeatable and
accurate measurements of HVAC EER.  The generic compressor curve used for many of the
SEQL area tests was found to underestimate the actual savings demonstrated in the pilot baseline
study  tests.  The condenser test methodology was generally less accurate but showed greater
increases in EER as a result of the Adsil treatment.

A degradation prediction tool for HVAC units was created in this pilot program.  This
spreadsheet-based tool was calibrated against actual EER measurements and was found to be very
accurate in  predicting the EER degradation of a population of HVAC units in the SEQL area.

An energy savings projection tool was also created based on the results of this study.  This tool
can be easily adapted by facility owners and operators to estimate their energy savings, dollar
savings, and possibly avoided pollution emissions as a result of the application ofAdsil to air-
cooled HVAC equipment. This tool estimates that annual dollar savings for the 150 units coated
in the SEQL area will exceed $37,000 based on a blended electric rate of $0.08 per kWh.

MACTEC believes that this product demonstrated significant savings for air-cooled HVAC
equipment.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                          9-1                                    MACTEC

-------

-------
                                                         Application ofAdsil in the NC/SC Charlotte Area
                               10.   Recommendations
MACTEC recommends that the units in this study be evaluated for EER improvements on an
annual basis. The instantaneous results form the Adsil treatment indicated that the EER improved
12%. There is no data currently available to support or refute that these improvements will be
maintained. It would be very valuable to conclusively identify the long-term impact of the
product on HVAC efficiency.
P:\EEG\Energy\EPA Adsil Project\Final ReportVEPA Adsil Final Report with edits - v2.doc
                                           10-1                                    MACTEC

-------

-------
        Appendix A
Preliminary Application List

-------

-------
                                 APPENDIX A

                                    Table A-1

Preliminary Application List

      Building                                  Tons
      1      City of Concord Admin Building         83
      2      City of Concord - City Hall              58.5
      3      City of Monroe Rec Center               6
      4      City of Monroe Arts Building             9
      5      City of Monroe Recreation Buildings      183
      6      Town of Stallings Govt Office            9.5
      7      City of Salisbury - Rec Building          33
      8      Rowan County Office Building          80
      9      County of Anson Building "C"           20
      10     Town of Granite Quarry Town Hall       15
      11     Iredell County - Health Building          169
      12     Char/ Meek Samuel Billings Center       125
      13     Char/Meek Wallace Kuralt Center       550
      14     Gaston County Mental Health Home       8
      15     Town of Badin -Town Hall               9
      16     City of Locust Town Hall & Rec Bldg     12
      17     YTC Building "C"                     80
      18     YTC-Building "B"                     120
      19     YTC Building "D"                     42.5
      20     YTC-Building "F"                     11
      21     YTC - Maintenance Building             7
      22     YTC Student Services                  84
      23     YTC Truck Driving School               7.5
      24     YTC - Student Center                  39
      25     YTC - Library                         80
      26     YTC Building "A"                     155
      27     YTC - Science Building                270
      28     YTC Hood Center                     310.5

             Totals                             2576.5

-------

-------
        Appendix B
Residential Split System Tests

-------
                                   HVAC Datasheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                         Carrier
                         38TH060300
                         Split system
                         Gainesville
                         Toms Home unit
                            30.8    Amps
                            208    Volts
                            0.96
                            1.40    Amps
                            208    Volts
                            0.70
 Evaporator fan data (if applicable)
 Full load Amps:               7.10    Amps
 Nameplate Voltage:           122    Volts
 Adjust FLA to RLA:            0.77
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
Power supply:
Phase adjustment:
Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
Power supply:
Phase adjustment:
Fan quantity:
 9.4
 9.4
4.96
 13
18%
 7.4
1.62
Btu/W-hr   (CU Only)
Btu/W-hr   (CU Only)
tons
years
(% degraded)
Btu/W-hr
                                                                                         1
 Calculated compressor load:                       6.1
 Calculated condensing fan load:                   0.20
 Calculated evaporator fan load                    0.67
 Total calculated load for equipment:               6.32
 Assumptions
 Present condition EER based on degradation of 2% per year after year 4
  plus additional degradation of condenser coil
kW             Published Total; System kW
kW             Condensing Unit kWat ARI conditons
kW             Capacity at ARI Conditions=
kW- Condensing side only
                     6.32
                     4.96
 Condenser Coil Assessmei
 Overall Unit Condition
             New
             Average
             Fair
             Poor
 Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
 Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
 Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
 Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
                                      18.2%   Performance Degradation
FLUKE METER MEASUREMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Ass
nput SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Listed Fan CFM
244

20.8 4.6 0.92

slant Measurement
10
NA
NA
NA
NA

NA
NA
NA
NA
NA
F
F
%
%
%
%
Tons
F
kW
CU Capacity Estimates
67 F 293 K
89 F 305 K
73.5 in
28 in
15.0sq-ft
1115
Air Mass Flow 0.63 kg/sec |
                                                       Capacity
                                                       Efficiency
                                                       Efficiency
                          2.21 Tons
                          5.76 EER
                          2.08 kWfTon
 CU Fan CFM Calculation
Appendix B
Page 1 of 43
                                                                                                                    EPA Adsil Evaluation
                                                                                                            Residential Split System Tests

-------
Blower Data April 8
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

Average
2.7
3.5
3.3
3.9
3.7
3.5
3.5
3.1
3.3
3.1
3.7
3.5
3.5
2.7
2.9
2.9
2.5
2.5
3.1
3.9
4.1

3.281
1
2
3
4
5
6
7
8
9
Average
Area=
CFM=

3.1
2.9
2.1
2.7
2.5
2.5
3.5
3.7
3.3
2.922
1
175.3333
Total Blower CFM=
Published=
Error=
ft/sec

sq ft
1061.19
2000
47%
Area= 4.5 sq ft
CFM= 885.8571


1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

Average
Area=
CFM=
4.1
4.1
4.1
3.9
3.7
2.9
3.7
3.9
4.3
4.3
3.9
3.9
4.3
4.1
4.1
4.1
4.1
4.3
4.7
4.9
5.3

4.129
Blower Data April 10
Total Blower CFM- 11 33.293
Published= 2000
Error= 43%
ft/sec
4.575 sq ft
1133.293
Appendix B
Page 2 of 43
        EPA Adsil Evaluation
Residential Split System Tests

-------
Test at 90 Degrees
MayS, 2004 3:00 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

241
23.8
5.4
0.95
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
12
5

63
45
236
97
92
36
9
15
112
20

77
49
33%
85%

90%
90%
5














F
F
%
%

%
%
kW
12
5

63
45
236
97
92
36
9
15
112
20

77
49
33%
85%

84%
78%
4.7
;ti mates
95 F 308
115 F 319
in
in
15.0sq-ft
4365
2.47 kg/sec
Low
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
        7.86 Tons
       17.46 EER
        0.69 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
5.9
5.3
5.1
4.7
4.1
4.1
5.3
4.3
4.1
4.1
4.7
4.1
4.6
6.6
6.2
5.7
4.3
4.1
4.850
Appendix B
Page 3 of 43
                                                                                                             EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 92 Degrees
MayS, 2004 2:00 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
241
23.8
5.4
0.95
HVAC Service Assistant Measurement
Generic
12
5

63
45
236
97
92
36
9
15
112
20

77
49
33%
85%

90%
90%
5
Cope
F
F
%
%
%
%
kW
;timates
95 F
115 F
in
in
15.0sq-ft
4365
2.47 kg/sec
and 6CRN5-0500-PFV-270
12
5

63
45
231
97
92
36
9
14
112
19

77
49
33
85

84%
78%
4.7
Low
F
F
%
%
%
%
kW
308 K
319 K
             Capacity
             Efficiency
             Efficiency
        7.86 Tons
       17.46 EER
        0.69 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
5.9
5.3
5.1
4.7
4.1
4.1
5.3
4.3
4.1
4.1
4.7
4.1
4.6
6.6
6.2
5.7
4.3
4.1
4.850
Appendix B
Page 4 of 43
                                                                                                             EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 90 Degrees
July 8 2004 1:45 PM

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

240
24.4
5.6
0.95
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
12
5

66
46
231
97
90
38
7
16
112
21

79
50
29%
85%

90%
92%
4.8














F
F
%
%

%
%
kW
12
5

66
46
231
97
90
38
7
16
112
21

79
50
29%
85%

85%
81%
4.8
;ti mates
90 F 305
116F 320
in
in
15.0sq-ft
3920
2.22 kg/sec
Low
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
        9.17 Tons
       19.65 EER
        0.61 kW/Ton
  CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
5.1
5.3
5.5
4.7
3.7
3.1
5.5
4.7
3.7
4.1
4.3
4.1
3.5
4.7
4.3
4.3
3.7
4.1
4.356
Appendix B
Page 5 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 90 Degrees
MayS, 2004 3:00 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
241
23.8
5.4
0.95
HVAC Service Assistant Measurement
Generic
12
5

61
43
227
96
90
35
8
16
112
21

88
49
33%
85%

88%
88%
5
Cope
F
F
%
%
%
%
kW
timates
90 F
111 F
in
in
15.0sq-ft
4065
2.30 kg/sec
and 6CRN5-0500-PFV-270
12
5

62
43
234
97
91
36
7
16
112
21

88
49
33%
85%

83%
77%
4.7
305
317
Low
F
F
%
%
%
%
kW
K
K
              Capacity
              Efficiency
              Efficiency
        7.68 Tons
       17.07 EER
        0.70 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
5.7
4.7
4.3
4.5
3.7
3.9
4.3
4.1
4.1
3.7
3.5
3.7
5.1
6.4
6.1
5.7
4.3
3.5
4.517
Appendix B
Page 6 of 43
                                                                                                            EPA Adsil Evaluation
                                                                                                    Residential Split System Tests

-------
Test at 88 Degrees
MayS, 2004 6:30 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
243
21.5
5.4
0.94
HVAC Service Assistant Measurement
Generic
12
5

62
45
220
92
88
35
9
16
108
20

80
48
25%
85%

89%
88%
5
Cope
F
F
%
%
%
%
kW
;timates
86 F
108 F
in
in
15.0sq-ft
3870
2.19 kg/sec
and 6CRN5-0500-PFV-270
12
5

61
42
220
93
88
35
7
15
108
20

80
48
25%
85%

83%
77%
4.7
Low
F
F
%
%
%
%
kW
303 K
315 K
             Capacity
             Efficiency
             Efficiency
        7.66 Tons
       17.03 EER
        0.70 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
5.7
4.3
4.5
4.1
3.3
3.7
4.1
3.1
3.9
3.7
3.5
3.5
4.9
6.1
6.1
4.9
4.3
3.7
4.300
Appendix B
Page 7 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 85 Degrees
July 8 2004 2:40 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
241
23.4
5.3
0.95
HVAC Service Assistant Measurement
Generic
12
5

62
41
214
91
85
35
6
16
107
22

76
48
26%
85%

86%
88%
4.9
Cope
F
F
%
%
%
%
kW
timates
86 F
109 F
in
in
15.0sq-ft
3600
2.04 kg/sec
and 6CRN5-0500-PFV-270
12
5

62
41
214
91
85
35
6
16
107
22

76
48
0.26
0.85

83%
78%
4.8
303
316
Low
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
        7.45 Tons
       16.87 EER
        0.71 kW/Ton
  CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
3.3
2.7
3.9
3.3
2.7
2.5
4.3
4.3
3.7
4.9
4.1
3.5
5.3
5.9
5.5
5.1
3.5
3.5
4.000
Appendix B
Page 8 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 85 Degrees
April 9, 2004 4:45 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

241
23.1
5.2
0.94
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow




































F
F
%
%

%
%
kW














75
46
30
87

81%
72%
5.5
;ti mates
85 F 303
108 F 315
in
in
15.0sq-ft
1870
1.06 kg/sec
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
        3.87 Tons
        8.93 EER
        1.34 kW/Ton
  CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
4.7
2.7
4.7
4.9
3.1
0
4.5
3.5
2.5
2
1.8
1
2
0
0
0
0
0
2.078
                           Not Updated
Appendix B
Page 9 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                       Residential Split System Tests

-------
Test at 85 Degrees
April 28, 2004 3:00 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

243
23.1
5.2
0.94
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
12
5

60
51
212
91
85
34
17
13
104
20

77
48
33%
85%

88%
84%
4.9














F
F
%
%

%
%
kW
12
5

60
49
213
91
85
34
15
14
105
21

77
48
33
85

83%
76%
4.7
;ti mates
85 F 303
108 F 315
in
in
15.0sq-ft
3200
1.81 kg/sec
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
        6.62 Tons
       15.29 EER
        0.79 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
4.5
3.9
2.7
4.1
4.9
3.1
3.9
3.3
3.1
2.9
2.7
2.7
3.9
4.5
2.9
5.3
3.5
2.1
3.556
Appendix B
Page 10 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 84 Degrees
June 2, 2004 at 10:25 AW

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
243
22.6
5.2
0.94
HVAC Service Assistant Measurement
Generic
10
5

59
46
206
89
84
33
12
15
103
19

78
47
25%
85%

87%
84%
6.3
Cope
F
F
%
%
%
%
kW
;timates
84 F
106 F
in
in
15.0sq-ft
1915
1 .08 kg/sec
and 6CRN5-0500-PFV-270
10
5

59
46
206
89
84
33
12
15
103
19

78
47
25%
85%

86%
78%
5.5
Low
F
F
%
%
%
%
kW
302 K
314 K
             Capacity
             Efficiency
             Efficiency
        3.79 Tons
        8.75 EER
        1.37 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
3.5
2.7
0
2
0
0
3.1
5.5
4.5
2.9
1.8
0
2.7
2.7
1.4
3.5
2
0
2.128
Appendix B
Page 11  of 43
                                                                                                             EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 84 Degrees
April 28, 2004 4:00 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
243
22.8
5.2
0.94
HVAC Service Assistant Measurement
Generic
12
5

58
44
204
91
84
32
13
12
102
19

76
45
24%
85%

84%
80%
4.8
Cope
F
F
%
%
%
%
kW
timates
84 F
107 F
in
in
15.0sq-ft
3195
1.81 kg/sec
and 6CRN5-0500-PFV-270
12
5

58
44
207
91
84
32
12
13
104
20

77
45
24
85

81%
73%
4.6
302
315
Low
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
        6.61  Tons
       15.26 EER
        0.79 kW/Ton
  CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
4.5
3.9
3.1
4.1
3.9
3.1
3.7
3.3
2.7
1.8
1.8
2
4.9
5.3
3.3
5.7
4.5
2.3
3.550
Appendix B
Page 12 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 83 Degrees
July 8 2004 10:55 A.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

243
23
5.2
0.94
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
12
5

59
40
208
91
83
34
6
13
104
21

72
48
27%
85%

84%
82%
5.1














F
F
%
%

%
%
kW
12
5

59
40
208
91
83
34
6
13
104
21

72
48
27%
85%

80%
73%
4.7
;ti mates
85 F 303
106 F 314
in
in
15.0sq-ft
3705
2.10 kg/sec
Low
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
        7.00 Tons
       16.16 EER
        0.74 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
2.3
4
4.7
3.9
3.7
3.5
5.1
4.7
4.7
4.3
2.7
2.9
4.7
6.1
5.5
4.9
3.5
2.9
4.117
Appendix B
Page 13 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 84 Degrees
April 10, 2004 5:00 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
243
23.3
5.3
0.94
HVAC Service Assistant Measurement
Generic
12
5

60
49
214
90
84
34
15
16
106
21

75
46
30%
87%

86%
84%
5.2
Cope
F
F
%
%
%
%
kW
;timates
84 F
107 F
in
in
15.0sq-ft
1870
1 .06 kg/sec
and 6CRN5-0500-PFV-270
12
5

60
50
209
90
84
34
16
16
105
22

75
46
30
87

83%
76%
4.7
Low
F
F
%
%
%
%
kW
302 K
315 K
              Capacity
              Efficiency
              Efficiency
        3.87 Tons
        8.76 EER
        1.37 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
4.7
2.7
4.7
4.9
3.1
0
4.5
3.5
2.5
2
1.8
1
2
0
0
0
0
0
2.078
Appendix B
Page 14 of 43
                                                                                                             EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 83 Degrees
April 28, 2004 5:00 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
243
22.6
5.1
0.94
HVAC Service Assistant Measurement
Generic
12
5

57
43
201
90
83
31
12
11
102
18

74
44
25%
85%

85%
80%
4.7
Cope
F
F
%
%
%
%
kW
timates
83 F
105 F
in
in
15.0sq-ft
2515
1 .42 kg/sec
and 6CRN5-0500-PFV-270
12
5

56
43
201
89
83
31
12
12
102
20

74
44
25
85

80%
72%
4.6
301
314
Low
F
F
%
%
%
%
kW
K
K
              Capacity
              Efficiency
              Efficiency
        4.98 Tons
       11.72 EER
        1.02 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
4.1
3.5
2.5
3.1
2.9
2
2.5
2.3
2.1
1.8
2
0
4.9
5.1
2.1
5.3
4.1
0
2.794
Appendix B
Page 15 of 43
                                                                                                             EPA Adsil Evaluation
                                                                                                     Residential Split System Tests

-------
Test at 83 Degrees
July 8 2004 9:55 A.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

242
23.1
5.3
0.95
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
12
5

60
40
207
89
82
34
6
15
104
21

75
49
34%
85%

84%
83%
4.7














F
F
%
%

%
%
kW
12
5

60
40
207
89
82
34
6
15
104
21

75
49
34%
85%

81%
75%
4.7
;ti mates
85 F 303
107 F 315
in
in
15.0sq-ft
3815
2.16 kg/sec
Low
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
        7.55 Tons
       17.10 EER
        0.70 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
3.1
3.7
3.3
3.9
3.7
3.7
5.5
5.1
4.7
4.7
3.3
3.5
3.9
6.2
5.7
5.3
3.3
3.7
4.239
Appendix B
Page 16 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 73 Degrees
April 8, 2004 5:00 P.M. Generic Compressor Curve
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

244
21.5
4.8
0.92
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
10
5












NA
NA
NA
NA

79%
73%
5.5














F
F
%
%

%
%
kW
10
5












NA
NA
NA
NA

79
73
5.5
;ti mates
73 F
95 F
NA in
NA in
15.0sq-ft
1870
1.06 kg/sec
F
F
%
%
%
%
kW
             Capacity
             Efficiency
             Efficiency
        3.70 Tons
        9.26 EER
        1.30 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
4.7
2.7
4.7
4.9
3.1
0
4.5
3.5
2.5
2
1.8
1
2
0
0
0
0
0
2.078
Appendix B
Page 17 of 43
                                                                                                             EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 71 Degrees
April 12, 2004 7:30 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

244
21.5
4.8
0.92
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
12
5

58
69
177
74
71
32
37
19
93
23

75
46
30
87

87%
82%
6.6














F
F
%
%

%
%
kW
12
5

56
69
176
73
71
31
38
19
93
22

75
46
30
87

79%
71%
4.6
;ti mates
71 F
96 F
NA in
NA in
15.0sq-ft
1870
1.06 kg/sec
Low
High
F
F
%
%
%
%
kW
             Capacity
             Efficiency
             Efficiency
        4.21  Tons
       10.52 EER
        1.14 kW/Ton
  CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
4.7
2.7
4.7
4.9
3.1
0
4.5
3.5
2.5
2
1.8
1
2
0
0
0
0
0
2.078
                                       Fan Not Measured-Used previous numbers
Appendix B
Page 18 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                       Residential Split System Tests

-------
Test at 66 Degrees
April 14, 2004 6:30 P.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
244
20.6
4.6
0.92
HVAC Service Assistant Measurement
Generic
12
5

67
64
157
69
66
39
24
17
85
19

72
41
35
85

102%
102%
4.9
Cope
F
F
%
%
%
%
kW
and 6CRN5-0500-PFV-270
12
5

69
64
155
68
66
40
22
17
85
19

72
41
35
85

1 03%
1 03%
5
F
F
%
%
%
%
kW
;timates
66 F
88 F
NA in
NA in
15.0sq-ft
3110
1 .76 kg/sec
             Capacity
             Efficiency
             Efficiency
        6.16 Tons
       16.06 EER
        0.75 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
2.1
5.5
3.7
6.1
5.3
2.1
4.5
3.5
2.9
3.1
3.5
2.7
3.1
3.7
3.5
2.5
2.1
2.3
3.456
Appendix B
Page 19 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 64 Degrees
April 12, 2004 8:00 A.M.

Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
246
21.2
4.8
0.91
HVAC Service Assistant Measurement
Generic
12
5

53
64
162
68
64
28
36
19
87
24

75
46
30
87

80%
73%
5.7
Cope
F
F
%
%
%
%
kW
and 6CRN5-0500-PFV-270
12
5

52
64
160
69
64
28
37
18
87
22

75
46
30
87

79%
72%
4.6
Low
High
F
F
%
%
%
%
kW
;timates
66 F
89 F
NA in
NA in
15.0sq-ft
1870
1 .06 kg/sec
             Capacity
             Efficiency
             Efficiency
        3.87 Tons
        9.68 EER
        1.24 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
4.7
2.7
4.7
4.9
3.1
0
4.5
3.5
2.5
2
1.8
1
2
0
0
0
0
0
2.078
                                       Fan Not Measured-Used previous numbers
Appendix B
Page 20 of 43
                                                                                                              EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
Test at 84 Degrees
Juto 2004 3:45 PM- Cleaned Coil with Hose
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
243
22.9
5.2
0.94
HVAC Service Assistant Measurement
Generic
12
5

60
39
205
86
84
34
5
17
103
19

75
48
26%
85%

87%
86%
5.1
Cope
F
F
%
%
%
%
kW
timates
82 F
106 F
in
in
15.0sq-ft
3715
2.10 kg/sec
and 6CRN5-0500-PFV-270
12
5

60
39
205
86
84
34
5
17
103
19

75
48
0.26
0.85

84%
77%
4.7
301
314
Low
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
        8.02 Tons
       18.52 EER
        0.65 kW/Ton
  CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
3.9
4.7
5.5
4.1
2.7
2.7
4.5
3.9
3.3
3.5
4.1
3.9
6.2
5.5
4.3
3.9
3.9
3.7
4.128
Appendix B
Page 21  of 43
                                                                                                             EPA Adsil Evaluation
                                                                                                      Residential Split System Tests

-------
               TABLE 4-1
               Unit 1 Baseline Study
               Generic Compressor Test Summary-All Temperatures
    EER at ARI Conditions
    Condensing unitCFM
    Capacity at ARI
    Coil Area
    Predicted EER =
 9.4 BTU/W-h
3000 CFM (Listed)
4.96 tons
  15 sq-ft
7.40
Test Date
April 12-G
April 14-G
April 12G
April 8G
July 8-G
April 28G
July 8-G
April 10G
April 28G
June 2-G3
July8G4
April 28G
July 8G
MaySG
MaySG
July 8G
MaySG


POST ADSIL
August 21-G
August 20-G
August 23-G
August 20-G
August 20-G
August 20-G
August 10-G
August 21-G
August 10-G1
August 6-G
August 6-G1
August 1 8-G


HVAC Service Assistant

OAT
64
66
71
73
82
83
83
84
84
84
84
85
85
88
90
90
92
EWB
57
56
57
57
58
55
53
57
55
56
55
59
56
58
55
59
59
AVERAGES

OAT
73
81
82
83
85
85
85
86
87
89
91
90


EWB
59
59
63
60
60
65
57
59
58
60
60
65

AVERAGES
El
80%
102%
87%
79%
84%
85%
84%
86%
84%
87%
87%
88%
86%
89%
88%
90%
90%
86.8%

El
86%
87%
95%
88%
88%
88%
88%
88%
94%
93%
99%
94%

90.7%
Cl
73%
102%
82%
73%
83%
80%
82%
84%
80%
84%
86%
84%
88%
88%
88%
92%
90%
84.6%

Cl
81%
85%
95%
87%
85%
85%
85%
87%
90%
95%
97%
96%

89.0%
EER
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!


EER
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!


kW
5.7
4.9
6.6
5.5
4.7
4.7
5.1
5.2
4.8
6.3
5.1
4.9
4.9
5.0
5.0
4.8
5.0


kW
4.7
4.9
5.0
4.9
4.9
5.6
5.8
4.9
5.8
6.1
5.9
6.2


Physical Power and Capacity Measurements
Cond Air, deg F
inlet
66
66
71
73
85
83
85
84
84
84
82
85
86
86
90
90
95


inlet
72
79
82
83
84
82
84
85
82
89
89
90


exhaust
89
88
96
95
107
105
106
107
107
106
106
108
109
108
111
116
115


exhaust
96
102
106
107
107
108
107
108
105
114
115
115


Cond Air
DT(K)
12.8
12.2
13.9
12.2
12.2
12.2
11.7
12.8
12.8
12.2
13.3
12.8
12.8
12.2
11.7
14.4
11.1
12.55

DT(K)
13.3
12.8
13.3
13.3
12.8
14.4
12.8
12.8
12.8
13.9
14.4
13.9

13.38
kW
4.8
4.6
4.8
4.8
5.3
5.1
5.2
5.3
5.2
5.2
5.2
5.2
5.3
5.4
5.4
5.6
5.4


kW
4.8
5.1
5.3
5.2
5.3
5.4
5.2
5.3
5.2
5.5
5.6
5.6


(kg/sec)
1.06
1.76
1.06
1.06
2.16
1.42
2.10
1.06
1.81
1.08
2.10
1.81
2.04
2.19
2.30
2.22
2.47
1.75

(kg/sec)
2.96
2.94
2.92
2.99
2.92
2.98
3.01
2.98
3.06
2.93
3.02
2.99

2.97

tons
3.9
6.2
4.2
3.7
7.6
5.0
7.0
3.9
6.6
3.8
8.0
6.6
7.5
7.7
7.7
9.2
7.9


tons
11.31
10.74
11.12
11.39
10.66
12.32
11.01
10.88
11.17
11.62
12.49
11.87



EER
9.68
16.06
10.52
9.26
17.10
11.72
16.16
8.76
15.26
8.75
18.52
15.29
16.87
17.03
17.07
19.65
17.46
14.42

EER
28.27
25.28
25.18
26.29
24.14
27.38
25.41
24.63
25.77
25.35
26.77
25.43

25.83

cfm adj
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38

cfm adj
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38

0.38

EER, Adj
3.68
6.10
4.00
3.52
6.50
4.45
6.14
3.33
5.80
3.32
7.04
5.81
6.41
6.47
6.49
7.47
6.63
5.48

EER, Adj
10.74
9.61
9.57
9.99
9.17
10.40
9.66
9.36
9.79
9.63
10.17
9.66

9.81

kg/sec, adj
0.40
0.67
0.40
0.40
0.82
0.54
0.80
0.40
0.69
0.41
0.80
0.69
0.77
0.83
0.87
0.84
0.94
0.66

kg/sec, adj
1.13
1.12
1.11
1.14
1.11
1.13
1.14
1.13
1.16
1.11
1.15
1.14

1.13
                             Change   4.4%
                                               5.1%
                                                                                      6.6%
                                                                                                       70.1%
                                                                                                                        79.1%
                                                                                                                                  0.0%
                                                                                                                                             79.1%
                                                                                                                                                         70.1%
Appendix B
Page 22 of 43
                                                                                                               EPA Adsil Evaluation
                                                                                                        Residential Split System Tests

-------
Condensing Unit Summary - Ambient Conditions
OAT
64G
66G
71G
73G
82G
83G
83G1
84G1
84G2
84G3
84G4
85G
85G
88G
90G
90G1
92G

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
5.7
#REF!
#REF!
4.9
#REF!
#REF!
6.6
#REF!
#REF!
5.5
#REF!
#REF!
4.7
#REF!
#REF!
4.7
#REF!
#REF!
5.1
#REF!
#REF!
5.2
#REF!
#REF!
4.8
#REF!
#REF!
6.3
#REF!
#REF!
5.1
#REF!
#REF!
4.9
#REF!
#REF!
4.9
#REF!
#REF!
5.0
#REF!
#REF!
5.0
#REF!
#REF!
4.8
#REF!
#REF!
5.0
#REF!
#REF!
CU
4.8
3.87
9.68
4.6
6.16
16.06
4.8
4.21
10.52
4.8
3.70
9.26
5.3
7.55
17.10
5.1
4.98
11.72
5.2
7.00
16.16
5.3
3.87
8.76
5.2
6.61
15.26
5.2
3.79
8.75
5.2
8.02
18.52
5.2
6.62
15.29
5.3
7.45
16.87
5.4
7.66
17.03
5.4
7.68
17.07
5.6
9.17
19.65
5.4
7.66
17.03
Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Percent Difference
SA/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
SA/CU
119%
#REF!
#REF!
107%
#REF!
#REF!
138%
#REF!
#REF!
115%
#REF!
#REF!
89%
#REF!
#REF!
92%
#REF!
#REF!
98%
#REF!
#REF!
98%
#REF!
#REF!
92%
#REF!
#REF!
121%
#REF!
#REF!
98%
#REF!
#REF!
94%
#REF!
#REF!
92%
#REF!
#REF!
93%
#REF!
#REF!
93%
#REF!
#REF!
86%
#REF!
#REF!
93%
#REF!
#REF!
Condensing Unit Summary - ARI Conditions
Test Data
SA
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Literature
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Percent Difference
SA/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
SA/CU
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Predicted/SA

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!


#REF!


#REF!

-
#REF!


#REF!


#REF!


#REF!
-
-
#REF!
Predicted/CU

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!


#REF!


#REF!

-
#REF!


#REF!


#REF!


#REF!
-
-
#REF!
bstimatea
Degradation

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!

-
#REF!


#REF!


#REF!

-
#REF!


#REF!


#REF!


#REF!
-
-
#REF!
Appendix B
Page 23 of 43
        EPA Adsil Evaluation
Residential Split System Tests

-------

73-G
81-G
82-G
83-G
85-G
85-G1
85-G2
86-G
87-G
89-G
91-G
90-G Clean
Evap
POSTADSIL
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER

4.7
#REF!
#REF!
4.9
#REF!
#REF!
5.0
#REF!
#REF!
4.9
#REF!
#REF!
4.9
#REF!
#REF!
5.6
#REF!
#REF!
5.8
#REF!
#REF!
4.9
#REF!
#REF!
5.8
#REF!
#REF!
6.1
#REF!
#REF!
5.9
#REF!
#REF!
6.2
#REF!
#REF!

4.8
11.31
28.27
5.1
10.74
25.28
5.3
11.12
25.18
5.2
11.39
26.29
5.3
10.66
24.14
5.4
12.32
27.38
5.2
11.01
25.41
5.3
10.88
24.63
5.2
11.17
25.77
5.5
11.62
25.35
5.6
12.49
26.77
5.6
11.87
25.43

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

98%
#REF!
#REF!
96%
#REF!
#REF!
94%
#REF!
#REF!
94%
#REF!
#REF!
92%
#REF!
#REF!
104%
#REF!
#REF!
112%
#REF!
#REF!
92%
#REF!
#REF!
112%
#REF!
#REF!
111%
#REF!
#REF!
105%
#REF!
#REF!
111%
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
Appendix B
Page 24 of 43
        EPA Adsil Evaluation
Residential Split System Tests

-------
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Coil Area
    Predicted EER =
TABLE A-2
Generic Compressor Test Summary at Ambient 85 Degrees or Higher
(Maximum of 1 Test per Temperature)
                                     9.4 BTU/W-h
                                    3000 CFM (Listed)
                                    4.96 tons
                                      15 sq-ft
                                    7.40
Test Date
July 8G
May 8G
May 8G
May 8G


POST ADSIL
August 10-G
August 21 -G
August 10-G1
August 6-G
August 6-G1
August 18-G


HVAC Service Assistant

OAT
85
88
90
92
EWB
56
58
55
59
AVERAGES

OAT
85
86
87
89
91
90


EWB
57
59
58
60
60
65

AVERAGES
El
86%
89%
88%
90%
88.3%

El
88%
88%
94%
93%
99%
94%

92.7%
Cl
88%
88%
88%
90%
88.5%

Cl
85%
87%
90%
95%
97%
96%

91.7%
EER
#REF!
#REF!
#REF!
#REF!


EER
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!


kW
4.9
5.0
5.0
5.0


kW
5.8
4.9
5.8
6.1
5.9
6.2


Physical Power and Capacity measurments
Cond Air
inlet
86
86
90
95


inlet
84
85
82
89
89
90


deg F
exhaust
109
108
111
115


exhaust
107
108
105
114
115
115


Cond Air
DT(K)
12.8
12.2
11.7
11.1
11.94

DT(K)
12.8
12.8
12.8
13.9
14.4
13.9

13.43
kW
5.3
5.4
5.4
5.4


kW
5.2
5.3
5.2
5.5
5.6
5.6


(kg/sec)
2.04
2.19
2.30
2.47
2.25

(kg/sec)
3.01
2.98
3.06
2.93
3.02
2.99

3.00

tons
7.5
7.7
7.7
7.9


tons
11.01
10.88
11.17
11.62
12.49
11.87



EER
16.87
17.03
17.07
17.46
17.11

EER
25.41
24.63
25.77
25.35
26.77
25.43

25.56

cfm adj
0.38
0.38
0.38
0.38


cfm adj
0.38
0.38
0.38
0.38
0.38
0.38



EER, adj
6.41
6.47
6.49
6.63
6.50

EER, adj
9.66
9.36
9.79
9.63
10.17
9.66

9.71
                              Change   5.0%
                                                 3.6%
                                                                                         12.4%
                                                                                                          33.1%
                                                                                                                            49.4%
                                                                                                                                                  49.4%
Appendix B
Page 25 of 43
                                                                                                                                           EPA Adsil Evaluation
                                                                                                                                    Residential Split System Tests

-------
Condensing Unit Summary - Ambient Conditions
OAT
85G
88G
90G
92G

85-G2
86-G
87-G
89-G
91 -G
90-G Clean
Evap

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
POSTADSIL
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
4.9
#REF!
#REF!
5.0
#REF!
#REF!
5.0
#REF!
#REF!
5.0
#REF!
#REF!

5.8
#REF!
#REF!
4.9
#REF!
#REF!
5.8
#REF!
#REF!
6.1
#REF!
#REF!
5.9
#REF!
#REF!
6.2
#REF!
#REF!
CU
5.3
7.45
16.87
5.4
7.66
17.03
5.4
7.68
17.07
5.4
7.66
17.03

5.2
11.01
25.41
5.3
10.88
24.63
5.2
11.17
25.77
5.5
11.62
25.35
5.6
12.49
26.77
5.6
11.87
25.43
Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Percent Difference
SA/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
SA/CU
92%
#REF!
#REF!
93%
#REF!
#REF!
93%
#REF!
#REF!
93%
#REF!
#REF!

112%
#REF!
#REF!
92%
#REF!
#REF!
112%
#REF!
#REF!
111%
#REF!
#REF!
105%
#REF!
#REF!
111%
#REF!
#REF!
Condensing Unit Summary - ARI Conditions
Test Data
SA
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Literature
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Percent Difference
SA/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
SA/CU
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Predicted/SA


#REF!


#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
Predicted/CU


#REF!


#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
Estimated
Degradation


#REF!


#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
Appendix B
Page 26 of 43
        EPA Adsil Evaluation
Residential Split System Tests

-------
                 TABLE B-1
                 Copeland Compressor Test Summary-All Temperatures
      EERatARI Conditions
      Condensing unit CFM
      Capacity at ARI
      Coil Area
      Predicted EER =
 9.4 BTU/W-h
3000 CFM (Listed)
4.96 tons
  15 sq-ft
7.40
Test Date
April 12-C
April 14-C
April 12-C
July 8-C
April 28-C
July 8-C1
April 10-C1
April 28-C2
June 2-C3
July8C4
April 9-C1
April 28-C2
July 8-C3
May 08-C
May 08-C
May 08-C
May 08-C


POSTADSIL
August 21-C
August 20-C
August 23-C
August 20-C
August 20-C
August 20-C
August 10-C
August 21-C
August 10-C
August 6-C
August 6-C
August 18-C


HVAC Service Assistant

OAT
64
66
71
82
83
83
84
84
84
84
85
85
85
88
90
90
92


OAT
73
81
82
83
85
85
85
86
87
89
91
90


EWB
57
56
57
58
55
53
57
55
56
55
57
59
56
58
55
59
59


EWB
59
59
63
60
60
65
57
59
58
60
60
65


El
79%
103%
79%
81%
80%
80%
83%
81%
867o
84%
81%
83%
83%
83%
83%
85%
84%
83.4%

El
83%
84%
88%
84%
89%
89%
88%
85%
92%
92%
96%
92%

88.5%
Cl
72%
103%
71%
75%
72%
73%
76%
73%
787o
77%
72%
76%
78%
77%
77%
81%
78%
77.0%

Cl
74%
76%
84%
78%
81%
81%
79%
78%
82%
87%
91%
88%

81.6%
EER
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!


EER
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!


kW
4.6
5.0
4.6
4.7
4.7
4.7
4.7
4.6
5.5
4.7
5.5
4.7
4.8
4.7
4.7
4.8
4.7


kW
4.6
4.6
4.8
4.7
4.7
5.6
5.5
4.6
5.5
5.8
5.8
5.8


Physical Power and Capacity Measurements
Cond Air, deg F
inlet
66
66
71
85
83
85
84
84
84
82
85
85
86
86
90
90
95


inlet
72
79
82
83
84
82
84
85
82
89
89
90

83.42
exhaust
89
88
96
107
105
106
107
107
106
106
108
108
109
108
111
116
115


exhaust
96
102
106
107
107
108
107
108
105
114
115
115

107.50
Cond Air
DT(K)
12.8
12.2
13.9
12.2
12.2
11.7
12.8
12.8
12.2
13.3
12.8
12.8
12.8
12.2
11.7
14.4
11.1
12.6

DT(K)
13.3
12.8
13.3
13.3
12.8
14.4
12.8
12.8
12.8
13.9
14.4
13.9

13.38
kW
4.8
4.6
4.8
5.3
5.1
5.2
5.3
5.2
5.2
5.2
5.2
5.2
5.3
5.4
5.4
5.6
5.4


kW
4.8
5.1
5.3
5.2
5.3
5.4
5.2
5.3
5.2
5.5
5.6
5.6

5.29
(kg/sec)
1.06
1.76
1.06
2.16
1.42
2.10
.06
.81
.08
.10
.06
.81
2.04
2.19
2.30
2.22
2.47
1.7

(kg/sec)
2.96
2.94
2.92
2.99
2.92
2.98
3.01
2.98
3.06
2.93
3.02
2.99

2.97

tons
3.87
6.16
4.21
7.55
4.98
7.00
3.87
6.61
3.79
8.0
3.87
6.62
7.5
7.66
7.68
9.17
7.86


tons
11.31
10.74
11.12
11.39
10.66
12.32
11.01
10.88
11.17
11.62
12.49
11.87

11.38

EER
9.68
16.06
10.52
17.10
11.72
16.16
8.76
15.26
8.75
18.52
8.93
15.29
16.87
17.03
17.07
19.65
17.46
14.4

EER
28.27
25.28
25.18
26.29
24.14
27.38
25.41
24.63
25.77
25.35
26.77
25.43

25.83
                                   Change   6.1%
                                                      6.0%
                                                                                              6.3%
                                                                                                              70.1%
                                                                                                                               79.3%
Appendix B
Page 27 of 43
                                                                                                        EPA Adsil Evaluation
                                                                                                 Residential Split System Tests

-------
Condensing Unit Summary - Ambient Conditions | Condensing Unit Summary - ARI Conditions
OAT
64-C
66-C
71 -C
82-C
83-C
83-C1
84-C1
84-C2
84-C3
84-C3
85-C1
85-C2
85-C3
88-C
90-C
90-C1
92-C

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
4.6
#REF!
#REF!
5.0
#REF!
#REF!
4.6
#REF!
#REF!
4.7
#REF!
#REF!
4.7
#REF!
#REF!
4.7
#REF!
#REF!
4.7
#REF!
#REF!
4.6
#REF!
#REF!
5.5
#REF!
#REF!
4.7
#REF!
#REF!
5.5
#REF!
#REF!
4.7
#REF!
#REF!
4.8
#REF!
#REF!
4.7
#REF!
#REF!
4.7
#REF!
#REF!
4.8
#REF!
#REF!
4.7
#REF!
#REF!
CU
4.800
3.87
9.68
4.600
6.16
16.06
4.8
4.21
10.52
5.3
7.55
17.10
5.1
4.98
11.72
5.2
7.00
16.16
5.3
3.87
8.76
5.2
6.61
15.26
5.2
3.79
8.75
5.2
8.02
18.52
5.2
3.87
8.93
5.2
6.62
15.29
5.3
7.45
16.87
5.4
7.66
17.03
5.4
7.68
17.07
5.6
9.17
19.65
5.4
7.66
17.03
Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Percent Difference
SA/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
SA/CU
96%
#REF!
#REF!
109%
#REF!
#REF!
96%
#REF!
#REF!
89%
#REF!
#REF!
92%
#REF!
#REF!
90%
#REF!
#REF!
89%
#REF!
#REF!
88%
#REF!
#REF!
106%
#REF!
#REF!
90%
#REF!
#REF!
106%
#REF!
#REF!
90%
#REF!
#REF!
91%
#REF!
#REF!
87%
#REF!
#REF!
87%
#REF!
#REF!
86%
#REF!
#REF!
87%
#REF!
#REF!
Test Data
SA
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Literature
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Percent Difference
SA/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
SA/CU
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Predicted/SA
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
Predicted/CU
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
Estimated
Degradation
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
Appendix B
Page 28 of 43
        EPA Adsil Evaluation
Residential Split System Tests

-------

73-C
81 -C
82-C
83-C
85-C
85-C1
85-C2
86-C
87-C
89-C
91 -C
90-C Clean
Evap
POST ADSIL
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER

4.6
#REF!
#REF!
4.6
#REF!
#REF!
4.8
#REF!
#REF!
4.7
#REF!
#REF!
4.7
#REF!
#REF!
5.6
#REF!
#REF!
5.5
#REF!
#REF!
4.6
#REF!
#REF!
5.5
#REF!
#REF!
5.8
#REF!
#REF!
5.8
#REF!
#REF!
5.8
#REF!
#REF!

4.8
11.31
28.27
5.1
10.74
25.28
5.3
11.12
25.18
5.2
11.39
26.29
5.3
10.66
24.14
5.4
12.32
27.38
5.2
11.01
25.41
5.3
10.88
24.63
5.2
11.17
25.77
5.5
11.62
25.35
5.6
12.49
26.77
5.6
11.87
25.43

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

96%
#REF!
#REF!
90%
#REF!
#REF!
91%
#REF!
#REF!
90%
#REF!
#REF!
89%
#REF!
#REF!
104%
#REF!
#REF!
106%
#REF!
#REF!
87%
#REF!
#REF!
106%
#REF!
#REF!
105%
#REF!
#REF!
104%
#REF!
#REF!
104%
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
.
#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
.
#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
.
#REF!
-
-
#REF!
-
-
#REF!
Appendix B
Page 29 of 43
        EPA Adsil Evaluation
Residential Split System Tests

-------
                 TABLE B-2
                 Copeland Compressor Test Summary at Ambient of 85 Degrees or Higher
                 (Maximum of 1 Test Per Temperature)
      EER at ARI Conditions                                  9.4 BTU/W-h
      Condensing unit CFM                                  3000 CFM (Listed)
      Capacity at ARI                                       4.96 tons
      Coil Area                                             15 sq-ft
      Predicted EER =                                      7.40
Test Date
April 9-C1
May 08-C
May 08-C
May 08-C


POSTADSIL
August 20-C
August 20-C
August 21-C
August 10-C
August 6-C
August 6-C
August 18-C


HVAC Service Assistant

OAT
85
88
90
92


OAT
85
85
86
87
89
91
90


EWB
57
58
55
59


EWB
60
65
59
58
60
60
65


El
81%
83%
83%
84%
82.8%

El
89%
89%
85%
92%
92%
96%
92%

90.7%
Cl
72%
77%
77%
78%
76.0%

Cl
81%
81%
78%
82%
87%
91%
88%

84.0%
EER
#REF!
#REF!
#REF!
#REF!


EER
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!


kW
5.5
4.7
4.7
4.7


kW
4.7
5.6
4.6
5.5
5.8
5.8
5.8


Physical Power and Capacity Measurements
Cond Air, deg F
inlet
85
86
90
95


inlet
84
82
85
82
89
89
90

85.86
exhaust
108
108
111
115


exhaust
107
108
108
105
114
115
115

110.29
Cond Air
DT(K)
12.8
12.2
11.7
11.1


DT(K)
12.8
14.4
12.8
12.8
13.9
14.4
13.9

13.57
kW
5.2
5.4
5.4
5.4


kW
5.3
5.4
5.3
5.2
5.5
5.6
5.6

5.41
(kg/sec)
1.06
2.19
2.30
2.47


(kg/sec)
2.92
2.98
2.98
3.06
2.93
3.02
2.99

2.98

tons
3.87
7.66
7.68
7.86


tons
10.66
12.32
10.88
11.17
11.62
12.49
11.87

11.57

EER
8.93
17.03
17.07
17.46


EER
24.14
27.38
24.63
25.77
25.35
26.77
25.43

25.64
Appendix B
Page 30 of 43
       EPA Adsil Evaluation
Residential Split System Tests

-------
Condensing Unit Summary - Ambient Conditions | Condensing Unit Summary - ARI Conditions
OAT
85-C1
88-C
90-C
92-C

85-C
85-C1
86-C
87-C
89-C
91 -C
90-C Clean
Evap

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
POST ADSIL
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
5.5
#REF!
#REF!
4.7
#REF!
#REF!
4.7
#REF!
#REF!
4.7
#REF!
#REF!

4.7
#REF!
#REF!
5.6
#REF!
#REF!
4.6
#REF!
#REF!
5.5
#REF!
#REF!
5.8
#REF!
#REF!
5.8
#REF!
#REF!
5.8
#REF!
#REF!
CU
5.2
3.87
8.93
5.4
7.66
17.03
5.4
7.68
17.07
5.4
7.66
17.03

5.3
10.66
24.14
5.4
12.32
27.38
5.3
10.88
24.63
5.2
11.17
25.77
5.5
11.62
25.35
5.6
12.49
26.77
5.6
11.87
25.43
Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Percent Difference
SA/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
SA/CU
106%
#REF!
#REF!
87%
#REF!
#REF!
87%
#REF!
#REF!
87%
#REF!
#REF!

89%
#REF!
#REF!
104%
#REF!
#REF!
87%
#REF!
#REF!
106%
#REF!
#REF!
105%
#REF!
#REF!
104%
#REF!
#REF!
104%
#REF!
#REF!
Test Data
SA
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Literature
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Percent Difference
SA/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
CU/Lit
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
SA/CU
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
Predicted/SA
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
Predicted/CU
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
Estimated
Degradation
-
-
#REF!
.
.
#REF!
-
-
#REF!
-
-
#REF!

-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
-
-
#REF!
.
.
#REF!
-
-
#REF!
Appendix B
Page 31 of 43
        EPA Adsil Evaluation
Residential Split System Tests

-------
Test at 91 Degrees
August 6, 2004 3:00 P.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                               POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

242
24.5
5.6
0.95
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
10
5

62
79
221
95
91
36
40
14
109
18

80
55
30%
85%

99%
97%
5.9














F
F
%
%

%
%
kW
10
5

69
63
231
96
91
40
22
16
111
21

80
55
30%
85%

96%
91%
5.8
;ti mates
89 F 305
115 F 319
in
in
15.0sq-ft
5340
3.02 kg/sec
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
       12.49 Tons
       26.77 EER
        0.45 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.7
6.7
6.1
5.9
5.5
5.5
6.1
6.3
6.6
5.9
5.3
5.7
5.1
5.3
5.7
5.9
5.5
7
5.933
Appendix B
Page 32 of 43
                                                                                                        EPA Adsil Evaluation
                                                                                                 Residential Split System Tests

-------
Test at 90 Degrees
August 18, 2004 3:50 P.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
POSTADSIL, CLEAN  EVAP
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

241
24.5
5.6
0.95
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
10
5

67
49
226
94
89
39
11
16
109
20

82
53
40%
85%

94%
96%
6.2














F
F
%
%

%
%
kW
10
5

67
48
225
93
89
39
10
16
109
20

82
53
40%
85%

92%
88%
5.8
;ti mates
90 F 305
115 F 319
in
in
15.0sq-ft
5275
2.99 kg/sec
Low
F
F
%
%
%
%
kW
K
K
            Capacity
            Efficiency
            Efficiency
       11.87 Tons
       25.43 EER
        0.47 kW/Ton
  CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6
6
6.8
7.2
5.6
5.4
6.3
6.3
6.7
5.3
5
4.4
6.8
6.2
5.3
5.5
5.5
5.2
5.861
Appendix B
Page 33 of 43
                                                                                                    EPA Adsil Evaluation
                                                                                             Residential Split System Tests

-------
Test at 89 Degrees
August 6, 2004 3:30 P.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                               POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2

243
24
5.5
0.94
HVAC Service Assistant Measurement
Generic Copeland 6CRN5-0500-PFV-27C
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity Es
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
10
5

66
48
225
93
89
38
9
16
109
20

80
55
30%
85%

93%
95%
6.1














F
F
%
%

%
%
kW
10
5

66
48
225
93
89
38
9
16
109
20

80
55
30%
85%

92%
87%
5.8
;ti mates
89 F 305
114 F 319
in
in
15.0sq-ft
5165
2.93 kg/sec
Low
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
       11.62 Tons
       25.35 EER
        0.47 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.5
5.9
4.5
5.4
5.6
6.1
5.6
5.6
5.8
6.5
4.8
5
6.1
6.2
6.8
5.5
5.6
5.8
5.739
Appendix B
Page 34 of 43
                                                                                                        EPA Adsil Evaluation
                                                                                                 Residential Split System Tests

-------
Test at 87 Degrees
August-ID, 2004 10:50 A.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                               POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
244
23
5.2
0.94
HVAC Service Assistant Measurement
Generic
10
5

61
48
201
87
87
34
13
15
102
15

76
59
35%
85%

94%
90%
5.8
Cope
F
F
%
%
%
%
kW
timates
82 F
105 F
in
in
15.0sq-ft
5395
3.06 kg/sec
and 6CRN5-0500-PFV-270
10
5

60
44
204
88
88
34
10
15
103
15

76
59
35%
85%

92%
82%
5.5
301
314
Low
F
F
%
%
%
%
kW
K
K
             Capacity
             Efficiency
             Efficiency
       11.17 Tons
       25.77 EER
        0.47 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.6
6.8
5.5
6.1
5.5
5.5
6.2
6.1
5.9
5.7
5.3
5.1
6.8
6.6
7.2
6.2
5.5
5.3
5.994
Appendix B
Page 35 of 43
                                                                                                        EPA Adsil Evaluation
                                                                                                 Residential Split System Tests

-------
Test at 86 Degrees
August 21, 2004 11:40 A.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                                POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
241
23.4
5.3
0.95
HVAC Service Assistant Measurement
Generic
12
5

61
42
208
91
86
35
7
14
105
19

74
48
40%
85%

88%
87%
4.9
Cope
F
F
%
%
%
%
kW
timates
85 F
108 F
in
in
15.0sq-ft
5255
2.98 kg/sec
and 6CRN5-0500-PFV-270
12
5

61
42
208
91
86
35
7
14
105
19

74
48
40%
85%

85%
78%
4.6
303
315
F
F
%
%
%
%
kW
K
K
              Capacity
              Efficiency
              Efficiency
       10.88 Tons
       24.63 EER
        0.49 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.1
6.8
6
5.8
5.6
5.5
5.4
5.6
5.2
6.1
6.3
5.6
6.5
6.4
6.4
5.8
5.4
4.6
5.839
Appendix B
Page 36 of 43
                                                                                                       EPA Adsil Evaluation
                                                                                                Residential Split System Tests

-------
Test at 85 Degrees
August-ID, 2004 11:15 A.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                                 POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
244
22.9
5.2
0.94
HVAC Service Assistant Measurement
Generic
10
5

60
41
201
88
85
33
8
14
102
18

75
60
30%
85%

88%
85%
5.8
Cope
F
F
%
%
%
%
kW
timates
84 F
107 F
in
in
15.0sq-ft
5320
3.01 kg/sec
and 6CRN5-0500-PFV-270
10
5

60
41
201
88
85
33
8
14
102
18

75
60
30%
85%

88%
79%
5.5
302
315
Low
F
F
%
%
%
%
kW
K
K
              Capacity
              Efficiency
              Efficiency
       11.01 Tons
       25.41 EER
        0.47 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.8
7
5.7
5.9
5.9
6.1
5.7
5.9
6.1
6.2
4.9
5.1
6.8
6.4
4.9
5.3
5.5
6.2
5.911
Appendix B
Page 37 of 43
                                                                                                       EPA Adsil Evaluation
                                                                                                Residential Split System Tests

-------
Test at 85 Degrees
August 20, 2004 3:15 P.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                                 POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
242
23.5
5.4
0.95
HVAC Service Assistant Measurement
Generic
12
5

59
70
200
91
85
34
36
11
102
18

83
53
37%
85%

88%
85%
5.6
Cope
F
F
%
%
%
%
kW
timates
82 F
108 F
in
in
15.0sq-ft
5265
2.98 kg/sec
and 6CRN5-0500-PFV-270
12
5

63
69
207
90
85
36
32
14
104
19

83
53
37%
85%

89%
81%
5.6
301
315
F
F
%
%
%
%
kW
K
K
              Capacity
              Efficiency
              Efficiency
       12.32 Tons
       27.38 EER
        0.44 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
5.8
6.2
6.7
6.8
5.7
5.3
5.1
5.5
5.5
6.1
6.2
5.1
6.4
6.8
6.6
5.5
5.3
4.7
5.850
Appendix B
Page 38 of 43
                                                                                                       EPA Adsil Evaluation
                                                                                                Residential Split System Tests

-------
Test at 85 Degrees
August 20, 2004 5:15 P.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                                POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
241
23.1
5.3
0.95
HVAC Service Assistant Measurement
Generic
12
5

62
43
208
88
85
35
8
16
104
19

76
48
40%
85%

88%
85%
4.9
Cope
F
F
%
%
%
%
kW
timates
84 F
107 F
in
in
15.0sq-ft
5150
2.92 kg/sec
and 6CRN5-0500-PFV-270
12
5

62
43
208
88
85
35
8
16
104
19

76
48
40%
85%

89%
81%
4.7
302
315
F
F
%
%
%
%
kW
K
K
              Capacity
              Efficiency
              Efficiency
       10.66 Tons
       24.14 EER
        0.50 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.4
6.2
5.7
5.5
5.7
5.7
5.2
6.2
5.5
6.1
5.1
5.1
6.2
6.4
6.6
5.1
5.5
4.8
5.722
Appendix B
Page 39 of 43
                                                                                                       EPA Adsil Evaluation
                                                                                                Residential Split System Tests

-------
Test at 83 Degrees
August 20, 2004 5:30 P.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                                POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
242
22.9
5.2
0.94
HVAC Service Assistant Measurement
Generic
12
5

61
42
206
88
83
35
8
15
103
20

76
48
40%
85%

88%
87%
4.9
Cope
F
F
%
%
%
%
kW
timates
83 F
107 F
in
in
15.0sq-ft
5275
2.99 kg/sec
and 6CRN5-0500-PFV-270
12
5

61
42
206
88
83
35
8
15
103
20

76
48
40%
85%

84%
78%
4.7
301
315
F
F
%
%
%
%
kW
K
K
              Capacity
              Efficiency
              Efficiency
       11.39 Tons
       26.29 EER
        0.46 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.8
6.6
5.8
5.9
5.8
5.7
5.5
6
5.2
6.4
6.2
5.3
6.3
6.4
6.5
5.4
5.2
4.5
5.861
Appendix B
Page 40 of 43
                                                                                                       EPA Adsil Evaluation
                                                                                                Residential Split System Tests

-------
Test at 82 Degrees
August 23, 2004 5:30 P.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                                 POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
243
23.1
5.3
0.94
HVAC Service Assistant Measurement
Generic
12
5

66
57
203
84
82
38
18
18
102
21

80
52
40%
85%

95%
95%
5
Cope
F
F
%
%
%
%
kW
timates
82 F
106 F
in
in
15.0sq-ft
5150
2.92 kg/sec
and 6CRN5-0500-PFV-270
12
5

66
57
203
84
82
38
18
18
102
21

80
52
40%
85%

88%
84%
4.8
301
314
F
F
%
%
%
%
kW
K
K
              Capacity
              Efficiency
              Efficiency
       11.12 Tons
       25.18 EER
        0.48 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.4
6.8
6.2
5.7
5.5
5.7
5.3
6.2
5.1
5.1
5.1
5.5
6.2
6.2
6.4
5.4
5.1
5.1
5.722
Appendix B
Page 41 of 43
                                                                                                       EPA Adsil Evaluation
                                                                                                Residential Split System Tests

-------
Test at 81 Degrees
August 20, 2004 6:40 P.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                                 POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
242
22.4
5.1
0.94
HVAC Service Assistant Measurement
Generic
12
5

59
40
191
84
81
33
6
15
98
18

74
46
40%
85%

87%
85%
4.9
Cope
F
F
%
%
%
%
kW
timates
79 F
102 F
in
in
15.0sq-ft
5190
2.94 kg/sec
and 6CRN5-0500-PFV-270
12
5

59
40
191
84
81
33
6
15
98
18

74
46
40%
85%

84%
76%
4.6
F
F
%
%
%
%
kW
299 K
312 K
              Capacity
              Efficiency
              Efficiency
       10.74 Tons
       25.28 EER
        0.47 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.6
6.6
6.1
5.6
5.8
5.4
6.2
5.8
5.6
6
4.1
4.9
6.3
6.3
6.2
5.9
5.3
5.1
5.767
Appendix B
Page 42 of 43
                                                                                                       EPA Adsil Evaluation
                                                                                                Residential Split System Tests

-------
Test at 73 Degrees
August 21, 2004 3:00 P.M.
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag
                                                 POSTADSIL
Carrier
38TH060300

Split system
1991
Gainesville
Toms Home unit
Delta Measurement
Phase Volts Amps kW PF
1 to 2
Input SEER
Input Cap
SP
ST
LP
LT
OAT
ET
SH
SC
CT
COA
RAT
SAT
RAH
SAH
El
Cl
Predicted KW
CU Capacity E;
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Fan CFM
Air Mass Flow
245
21.4
4.8
0.92
HVAC Service Assistant Measurement
Generic
12
5

56
47
170
76
73
31
16
15
91
18

74
46
40%
85%

86%
81%
4.7
Cope
F
F
%
%
%
%
kW
timates
72 F
96 F
in
in
15.0sq-ft
5235
2.96 kg/sec
and 6CRN5-0500-PFV-270
12
5

56
47
170
76
73
31
16
15
91
18

74
46
40%
85%

83%
74%
4.6
F
F
%
%
%
%
kW
295 K
309 K
              Capacity
              Efficiency
              Efficiency
       11.31 Tons
       28.27 EER
        0.42 kW/Ton
   CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Average
ft/sec
6.3
7.2
6
5.9
5.7
5.5
6.2
6.3
6.6
5.5
5.3
4.3
5.6
6.2
6
5.6
5.2
5.3
5.817
Appendix B
Page 43 of 43
                                                                                                       EPA Adsil Evaluation
                                                                                                Residential Split System Tests

-------
           Appendix C
Commercial 5-Ton Split-system Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
  9.3
  9.3
  4.67
   3
  3%
  9.1
  1.32
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.9
0.1



1


0.5




X




X



Amps             Power supply:
Volts              Phase adjustment:
                  Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      3.2%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
4.6
5.5
5.4
5.0
5.1
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


212.0

15.7 4
kW Difference

5 0.78
0.17
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
211
212
tMeasurment
10
76
56
25
85

95%
92%
5
83
5.80
15.4 3
12.9 1.
2 0.99
13 0.41
4.33
F
F
%
%
Tons
F
kW
CU Capacity Estimates
82 F
99 F
90 in
35 n
22 sq-ft
6727
3.81 kg/sec
10.29 Tons
28.52 EER
301 K
310 K
Appendix C
Pagel of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  3%
  9.1
  1.32
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.9
0.1



1


0.5




X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      3.2%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
4.4
5.9
5.2
4.4
5.0
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


212.0

15.9 4
kW Difference

6 0.78
0.16
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
212
212
tMeasurment
10
73
53
24
85

95%
93%
5
84
5.90
15.8 3
13.05 1.
3 0.99
14 0.41
4.44
F
F
%
%
Tons
F
kW
CU Capacity Estimates
86 F
100 F
90 in
35 n
22 sq-ft
6530
3.70 kg/sec
8.23 Tons
22.23 EER
303 K
311 K
Appendix C
Page 2 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  3%
  9.1
  1.32
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.9
0.1



1


0.5




X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      3.2%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
4.3
5.4
3.8
4.4
4.5
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


215.0

15.9 4
kW Difference

6 0.78
0.18
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
214
215
tMeasurment
10
73
53
30
85

97%
96%
5
86
5.90
15.5 3
13.23 1.
3 0.99
12 0.40
4.42
F
F
%
%
Tons
F
kW
CU Capacity Estimates
86 F
100 F
90 in
35 n
22 sq-ft
5873
3.33 kg/sec
7.40 Tons
20.09 EER
303 K
311 K
Appendix C
Page 3 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  3%
  9.1
  1.32
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.9
0.1



1


0.5




X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      3.2%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.8
5.8
4.8
4.8
5.3
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


212.0

13.5 4
kW Difference

0 0.82
0.61
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
212
212
tMeasurment
10
74
54
24
85

96%
94%
5
87
5.90
16.1 3
13.6 1.
4 0.99
24 0.43
4.64
F
F
%
%
Tons
F
kW
CU Capacity Estimates
87 F
103 F
90 in
35 n
22 sq-ft
6956
3.94 kg/sec
10.02 Tons
25.90 EER
304 K
313 K
Appendix C
Page 4 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  3%
  9.1
  1.32
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.9
0.1



1


0.5




X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      3.2%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.4
5.4
4.4
5.0
5.1
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


213.0

13.7 4
kW Difference

0 0.80
0.6
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
212
213
tMeasurment
10
73
53
24
85

95%
93%
5
88
5.90
16.3 3
13.7 1
4 0.99
2 0.41
4.60
F
F
%
%
Tons
F
kW
CU Capacity Estimates
88 F
102 F
90 in
35 n
22 sq-ft
6628
3.75 kg/sec
8.35 Tons
21. 78 EER
304 K
312 K
Appendix C
Page 5 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  3%
  9.1
  1.32
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.9
0.1



1


0.5




X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      3.2%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.4
6.0
4.6
5.0
5.3
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


213.0

13.8 4
kW Difference

1 0.82
0.54
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
213
213
tMeasurment
10
74
54
28
85

97%
97%
5
88
6.00
16.15 3
13.8 1.
4 0.99
26 0.43
4.66
F
F
%
%
Tons
F
kW
CU Capacity Estimates
87 F
103 F
90 in
35 n
22 sq-ft
6891
3.90 kg/sec
9.92 Tons
25.55 EER
304 K
313 K
Appendix C
Page 6 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  3%
  9.1
  1.32
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.9
0.1



1


0.5




X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      3.2%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.6
6.1
4.9
6.0
5.7
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


213.0

16.4 4
kW Difference

8 0.79
0.16
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
214
214
tMeasurment
10
74
54
26
85

96%
95%
5
89
6.00
16.1 3
13.8 1.
4 0.99
24 0.42
4.64
F
F
%
%
Tons
F
kW
CU Capacity Estimates
90 F
105 F
90 in
35 n
22 sq-ft
7416
4.20 kg/sec
10.01 Tons
25.89 EER
305 K
314 K
Appendix C
Page 7 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  3%
  9.1
  1.32
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.9
0.1



1


0.5




X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      3.2%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.9
6.9
6.7
5.4
6.2
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


213.0


16.7 5


0 0.8

Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
212
212
tMeasurment
10
76
56
25
85

98%
98%
5
92
6.00
16.5 3
14.1 1.
F
F
%
%
Tons
F
kW
CU Capacity Estimates
94 F
110 F
90 in
35 n
22 sq-ft
8170
4.63 kg/sec
11. 76 Tons
29.35 EER
5 0.99
31 0.44
308 K
316 K
Appendix C
Page 8 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  0%
  9.4
  1.28
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1
0



1







X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      0.0%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
6.8
7.3
7.0
5.4
6.6
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


213.0

16.0 4
kW Difference

8 0.81
0.18
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
212
213
tMeasurment
10
76
56
34
85

98%
94%
5
89
5.80
16.1 3
13.9 1.
4 0.99
22 0.41
4.62
F
F
%
%
Tons
F
kW
CU Capacity Estimates
87 F
105 F
90 in
35 n
22 sq-ft
8695
4.92 kg/sec
14.09 Tons
36.59 EER
304 K
314 K
Appendix C
Page 9 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  0%
  9.4
  1.28
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1
0



1







X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      0.0%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.5
6.8
5.9
5.9
6.0
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


213.0

15.6 4
kW Difference

5 0.79
0.04
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
212
213
tMeasurment
10
74
54
40
85

96%
95%
5
85
5.90
15.6 3
13.3 1.
3 0.99
16 0.41
4.46
F
F
%
%
Tons
F
kW
CU Capacity Estimates
86 F
101 F
90 in
35 n
22 sq-ft
7908
4.48 kg/sec
10.67 Tons
28.72 EER
303 K
311 K
Appendix C
Page 10 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  0%
  9.4
  1.28
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1
0



1







X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      0.0%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.5
6.8
5.9
5.5
5.9
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


212.0

16.1 4
kW Difference

8 0.81
0.15
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
211
212
tMeasurment
10
73
53
28
85

99%
96%
5
89
5.90
16.2 3
13.8 1.
4 0.99
25 0.43
4.65
F
F
%
%
Tons
F
kW
CU Capacity Estimates
87 F
103 F
90 in
35 n
22 sq-ft
7777
4.40 kg/sec
11. 20 Tons
28.90 EER
304 K
313 K
Appendix C
Page 11  of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  0%
  9.4
  1.28
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1
0



1







X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      0.0%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.8
6.4
5.4
5.2
5.7
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


214.0

16.4 4
kW Difference

9 0.80
0.6
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
211
213
tMeasurment
10
76
56
29
85

94%
90%
5
82
5.80
15.1 3
12.7 1
2 0.99
1 0.41
4.30
F
F
%
%
Tons
F
kW
CU Capacity Estimates
84 F
99 F
90 in
35 n
22 sq-ft
7481
4.24 kg/sec
10. 10 Tons
28. 18 EER
302 K
310 K
Appendix C
Page 12 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  0%
  9.4
  1.28
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1
0



1







X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      0.0%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
6.2
7.1
6
5.1
6.1
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


214.0

16.4 4
kW Difference

9 0.80
0.29
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
213
214
tMeasurment
10
74
54
35
85

99%
98%
5
91
5.90
16.1 3
13.7 1.
4 0.99
21 0.41
4.61
F
F
%
%
Tons
F
kW
CU Capacity Estimates
90 F
105 F
90 in
35 n
22 sq-ft
8006
4.53 kg/sec
10.81 Tons
28. 13 EER
305 K
314 K
Appendix C
Page 13 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  0%
  9.4
  1.28
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1
0



1







X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      0.0%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
6.7
6.3
5.9
5.9
6.2
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


214.0

15.9 4
kW Difference

7 0.80
0.13
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
213
214
tMeasurment
10
76
56
21
85

97%
93%
5
88
5.80
15.9 3
13.22 1.
4 0.99
17 0.41
4.57
F
F
%
%
Tons
F
kW
CU Capacity Estimates
90 F
105 F
90 in
35 n
22 sq-ft
8138
4.61 kg/sec
10.98 Tons
28.84 EER
305 K
314 K
Appendix C
Page 14 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
                                    HVAC Data Sheet and EER Calculation
 Manufacturer:
 Model Number:
 Serial Number
 Equipment Type:
 Year Manufactured:
 Location
 Tag

 Compressor Data
 Running load Amps:
 Nameplate Voltage:
 Power factor:

 Condensing Fan Data
 Full load Amps:
 Nameplate Voltage:
 Adjust FLA to RLA:
Carrier
38YCC060

SS Heat pump
2001
MACTEC Hendrickson
HP-7
    17.0    Amps
    230    Volts
    0.86
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coil Conditon
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
  9.3
  9.3
  4.67
   3
  0%
  9.4
  1.28
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    1.40
    230
    0.70
Evaporator fan data (if applicable)
Full load Amps:               5.40
Nameplate Voltage:            230
Adjust FLA to RLA:            0.11

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1
0



1







X




X



Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                        5.8    kW
                       0.23   kW
                       0.13   kW
                       6.04   kW - Condensing side only
                                      0.0%   Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
4.9
5.0
6.5
5.5
5.5
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF

3-Phase


212.0

15.9 4
kW Difference

7 0.80
0.13
Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
212
212
tMeasurment
10
76
56
29
85

97%
93%
5
88
5.80
16 3
13.28 1.
4 0.99
17 0.41
4.57
F
F
%
%
Tons
F
kW
CU Capacity Estimates
89 F
104 F
90 in
35 n
22 sq-ft
7186
4.07 kg/sec
9.70 Tons
25.47 EER
305 K
313 K
Appendix C
Page 15 of 16
                                                                                                                                       EPA Adsil Evaluation
                                                                                                                             Commercial 5-Ton System Tests

-------
               TABLE 4-5
               Unit 2 Baseline Study
               Generic Compressor Test Summary-All Temperatures
      EERatARI Conditions
      Condensing unit CFM
      Capacity at ARI
      Coil Area
      Predicted EER =
9.27 BTU/W-h
3300 CFM (Listed)
4.67 tons
  22 sq-ft
9.07 BTU/W-h
Test Date
PRE

POST
24-May
1-Jul
1-Jul
1-Jul
1-Jul
1-Jul
1-Jul
1-Jul

1 6-Aug
1 6-Aug
11-Aug
11-Aug
31-Aug
31-Aug
31-Aug
HVAC Service Assistant

OAT
92
89
88
88
87
86
84
83
Averages
91
89
89
85
82
88
88
EWB
57
55
55
54
54
56
54
55

57
54
59
59
57
54
57
El
98%
96%
97%
95%
96%
97%
95%
95%
96%
99%
99%
98%
96%
94%
97%
97%
Cl
98%
95%
97%
93%
94%
96%
93%
92%
95%
98%
96%
94%
95%
90%
93%
93%
EER
8.83
9.01
9.24
9.04
9.27
9.52
9.58
9.73

9.05
9.28
9.24
9.60
9.80
9.23
9.26
Cap
4.24
4.16
4.26
4.08
4.14
4.26
4.15
4.13

4.26
4.20
4.13
4.25
4.07
4.08
4.10
kW
5.60
5.60
5.60
5.51
5.51
5.51
5.51
5.42

5.51
5.51
5.42
5.51
5.80
5.80
5.80
Averages 97% 94%
Change 1.1% -0.64%
Physical Power and Capacity measurments
Cond Air, deg F
inlet
94
90
87
88
87
86
86
82

90
87
87
86
84
90
89
exhaust
110
105
103
102
103
100
100
99

105
103
105
101
99
105
104
Cond Air
fll (K.)
8.9
8.3
8.9
7.8
8.9
7.8
7.8
9.4
8.47
8.3
8.9
10.0
8.3
8.3
8.3
8.3
kW
4.81
4.64
4.66
4.60
4.64
4.42
4.44
4.33

4.61
4.65
4.62
4.46
4.3
4.57
4.57
(kg/sec)
4.63
4.20
3.90
3.75
3.94
3.33
3.70
3.81
3.91
4.53
4.40
4.92
4.48
4.24
4.61
4.07

tons
11.76
10.01
9.92
8.35
10.02
7.40
8.23
10.29

10.81
11.20
14.09
10.67
10.10
10.98
9.70

EER
29.35
25.89
25.55
21.78
25.90
20.09
22.23
28.52
24.92
28.13
28.90
36.59
28.72
28.18
28.84
25.47

cfm adj
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38
0.38

EER Adj
11.15
9.84
9.71
8.28
9.84
7.63
8.45
10.84
9.47
10.69
10.98
13.90
10.91
10.71
10.96
9.68
8.65 4.47 29.26 0.38 11.12
2.11% 14.29% 17.45% 17.45%
Appendix C
Page 16 of 16
                                                                                                                   EPA Adsil Evaluation
                                                                                                          Commercial 5-Ton System Tests

-------

-------
     Appendix D
Eckerd's and MACTEC

-------
Eckerd Rooftop Units

Two rooftop units on an Eckerd drug store in Clearwater, Florida were instrumented by ADSIL, prior to a
routine condenser cleaning (per standard operating procedures), and followed later by cleaning and
coating using the Adsil treatment.  The testing/cleaning schedule for the units was as follows:
Date
April 27, 2004
May 5, 2004
(8:00 AM -4: 00PM)
May 19, 2004
(9:30 AM- 2:00 PM)
May 3 1,2004
Event
Units instrumented and data collection
begins
Condensers cleaned using standard
methods (per SOP)
Condensers cleaned and coated using
ADSIL treatment
Data collection ends
Eight data points were collected at 10-minute intervals for each unit.  Data collected included refrigerant
temperature entering and leaving the condenser, refrigerant suction and discharge pressures, ambient
temperature, and current for each of the three phases on the unit's main electrical service.  The current
measurements were converted to power (assuming a constant power factor of 0.85) by:
                         Power (kW) =
                                        208 x V3 x Avg(Ia,Ib,Ic) x 0.85
                                                     1000
Figure 1 displays the observed operating patterns of the two units during the monitoring period. The units
displayed two typical operating powers near 8 kW and 15 kW, corresponding to first and second stage
cooling operation. With the exception of a few hours where unit #2 operated the fan without any
cooling1, the units operated the first stage compressor nearly continuously. The second stage compressor
is observed to cycle  on during the afternoon hours, coincident with the peak cooling load.


The bottom plots are shade plots of the unit power.  On the shade plot each day is represented by a
vertical strip consisting of 144 10-minute data records. Periods of high power consumption are shown by
darker shades of grey.  Periods of missing  data (such as where the units were being cleaned and coated by
Adsil) are shown in  bright white. The shade plot reveals that unit #2 operated in second stage cooling
more  frequently than unit #1. Periods where unit #1 was observed  to be off (May 4-7 and May 27-30,
midnight to noon) are readily observed.
1 In mid-May there were several hours with an operating power of 3 kW for this unit, a typical value for the supply
fan on this size unit.
CDH Energy Corp.
June 23, 2004

-------
                    Eckerd Unit #1 Power
                                                                         Eckerd Unit #2 Power
    20
    15
    10
     o
        Baseline
                                       Adsil Coating
                                                         20
                                                         15
                                                         10
                                                         0
                                                                          Std. Cleaning
                                                                                            Adsil Coating
      26      3
      April  May
      2004
                      10
                               17
                                       24
                                                31
 26      3
 April  May
 2004
                                                                           10
                                                                                   17
                                                                                            24
                                                                                                    31
                Eckerd Unit#1 Operating Pattern
           Eckerd Unit #2 Operating Pattern
     2829301 2345678 910111213141516171819202122232425262728293031
      April  May
                   Day (MAX/MN=  17.45/ 0.00 kW)

Figure 1. Rooftop Unit Operating Patterns
2829301 2345678 910111213141516171819202122232425262728293031
 April May

              Day (MAWMN=  16.95/ 0.00 kW)
The following figure displays the observed condenser performance across the three periods. The data
were averaged to hourly values to reduce the amount of scatter. No significant difference was observed
between any of the periods. Most significant is the lack of any impact on either the saturated discharge
temperature or liquid temperature leaving the condenser.  These two parameters tend to have the largest
impact on any increase in efficiency from condenser treatment.

Also shown is the  saturated suction temperature variation with ambient.  Again, little change can be
observed between  the three periods, indicating that no change would have occurred in the supply air
temperature.
CDH Energy Corp.
                                 June 23, 2004

-------
    100


     95



  E  9°

  s>
  3
  2  85
  a
  E
  0
  I-  80



     75
     70 L_

      50
                                                 Eckerd Unit#1
              Refrigerant Temp Drop Across Condenser
                60
                          70        80        90

                      Ambient Temperature (F)
                                                               1201	
                                                          E
                                                          0
                                                          1-  SO
                                                        100
                                                             60L

                                                              50
                                                                           Refrigerant Leaving Condenser
                                                                           60
                                                                                  70        80

                                                                               Ambient Temperature (F)
                                                                                                         90
                                                                                                                  100
    135


    130



  E 125

  I
  1° 120
  0
    115
    110
    105L

      50
                  Saturated Discharge Temperature
                60
                          70        80        90

                      Ambient Temperature (F)
                                                                36
                                                             34
                                                           I
                                                           1° 32
                                                                30
                                                                28
                                                        100
                                                                 50
                                                                           60
                                                                                   Subcooling
                                                                                  70        80

                                                                               Ambient Temperature (F)
                                                                                                         90
                                                                                                                  100
  50





  45



0


H 40
0
Q.
E



  35





  30
      50
                   Saturated Suction Temperature
                                    A  -
                                    'V A ,
                                    ^  T v
                60        70        80        90

                      Ambient Temperature (F)
                                                        100
                                                                       + Baseline (Apr 28 - May 04)
                                                                       » Std Cleaning (May 06-May 18)
                                                                       A Adsil Coating (May 20 - May 31)
Figure 2.  Condenser Performance - Unit 1
CDH Energy Corp.
                                                                                                    June 23, 2004

-------
  80

£
5> 75
=3
2
a
I 70


  65
     60L
      50
                                                  Eckerd Unit #2
              Refrigerant Temp Drop Across Condenser
                60
                          70        80        90
                      Ambient Temperature (F)
                                                               •\2or~"
                                                               100
                                                             I-  80
                                                        100
                                                             60L
                                                               50
                                                                           Refrigerant Leaving Condenser
                                                                        60         70         80         90
                                                                               Ambient Temperature (F)
                                                                                                                   100
    140
    120
    100
     80^
      50
                  Saturated Discharge Temperature
             60         70        80         90
                    Ambient Temperature (F)
                                                                                    Subcooling
                                                        100
                                                             40

                                                             35

                                                            ; 30

                                                             25

                                                             20

                                                             15
                                                             ioL_
                                                               50
                                                                           60        70        80
                                                                                 Ambient Temperature (F)
                                                                                                         90
                                                                                                                   100
                   Saturated Suction Temperature
     50


     45
  £
   o
   £ 40
   £
   o
  \—
     35
     30l	i	i	i	i	
      50        60        70        80        90        100
                      Ambient Temperature (F)

Figure 3.  Condenser Performance - Unit 2
                                                                       Baseline (Apr 28 - May 04)
                                                                       Std Cleaning (May 06-May 18)
                                                                       Adsil Coating (May 20 - May 31)
CDH Energy Corp.
                                                                                                    June 23, 2004

-------
Figure 4 and Figure 5 displays the daily energy variation with ambient temperature for each unit. The
high degree of cycling operation between first and second stage cooling observed required summing the
power data collected to daily data for analysis purposes.

To assess the impact of the Adsil coating on the daily energy, a multiple linear regression (MLR) model
was developed.  The model incorporated a dummy variable to describe the impact of the coating (dummy
= 1 for the Adsil period, dummy = 0 for the baseline period).  Also shown on the plot are the t-ratios for
the regression coefficients. The t-ratio describes the statistical significance of each coefficient.
Coefficients with t-ratio with an absolute value greater than 2.0 indicate that the coefficients are
statistically significant at the 95% confidence interval.
                                          Eckerd Unit #1
    2000
    1500
 (0
 T3
 .*:

 D)
    1000
     500
            o

            A
Baseline (Apr 29 - May 03)
Std Cleaning (May 07 - May 18)
Adsil Coating (May 20 - May 31)
kWh/day = 3239.5 + 59.8 * TAO - 35.6 * DUMMY
t-ratios:-8.5, 12.4,-1.5
        70
       75                  80
                 Ambient Temperature (F)
85
90
Figure 4. Unit 1 Daily Energy Variation with Ambient
CDH Energy Corp.
                                                              June 23, 2004

-------
                                          Eckerd Unit #2
    2000
    1500
 (0
 T3
 .*:

 D)
    1000
     500
            o

            A
Baseline (Apr 28 - May 04)
Std Cleaning (May 06 - May 18)
Adsil Coating (May 20 - May 31)
kWh/day = 2863.7 + 56.8 * TAO - 46.8 * DUMMY
t-ratios: -5.4, 8.4, -1.2
        70
       75                  80
                 Ambient Temperature (F)
85
90
Figure 5. Unit 2 Daily Energy Variation with Ambient


The regression coefficients indicate that after the Adsil coating was applied, compared to the baseline, unit
#1 used 35.6 less kilowatt-hours per day and unit #2 used 46.8 less kilowatt-hours per day. Annual
savings were determined by applying the regression model to daily temperature data for Tampa, FL from
the Department of Energy typical meteorological year data set (TMY2).  Savings calculations assume no
cooling operation when the average daily temperature is less than 50°F (15 days/year).  Unfortunately, the
t-ratio for the dummy variable (the savings coefficient) was not greater than 2.0, indicating that the savings
were not statistically significant.


Table 1. Annual Impact From Adsil Coating
Unit
Unit#l
Unit #2
Baseline Energy
Use
(kWh/year)
384,402
439,142
Energy Use After
Adsil Coating
(kWh/year)
371,942
422,753
Savings
(kWh/vear / %)
12,460 / 3.2%
16,389 / 3.9%
Statistically
Significant
(t-ratio > 2.0)
No
No
A visual inspection of the daily energy data indicates that the standard cleaning had no impact on the
energy consumption of the units.  In fact, for unit #2 energy consumption appears to have slightly
increased.
CDH Energy Corp.
                                                              June 23, 2004

-------

-------
       Appendix E
Honeywell Service Assistant

-------
                      *•
           iagnostics
                                                            ASHRAE s Most Innovative
                                                                      Product of the Year 2003
HVAC Service Asistant
                                              HVAC Service Provider
                                              Multi-Unit Facility Manager
                                               HVAC Service Assistant
                                               Virtual Mechanic
   Honeywell
i IVAC Service Assistant
Highlights
    •   2003 AHR Expo Innovation Award Winner Use award winning technology to increase sales and improve productivity.
    •   First Efficiency Estimating Tool The Service Assistant's patented technology instantly displays the energy efficiency of a/c units. This revolutionary index identifies energy
        savings opportunities and provides objective documentation of the benefits.
    •   Honeywell provides worldwide distribution The Service Assistant complements a family of Honeywell products designed to reduce HVAC operating costs through energy
        savings in commercial buildings.

-------
Service Assistant Features

      •    Automated objective performance data collection
      •    Integrated fault detection (service needed? y/n) and diagnostics (what service?)
      •    Record and display the raw data and its interpretations on the PDA and its designated database
      •    Displays efficiency and capacity estimates with potential energy savings (more...)
      •    Estimates indoor air flow in cfm/ton
      •    Create customized task lists to standardize service procedures and field data collection
      •    Allows technicians to note required follow up work
      •    Technician can print for customer a UNIT REPORT CARD (see example) on site (optional printer required)
      •    Equipment applications include:
                 O    Packaged equipment (including rooftop units)
                 O    Split systems (including standard  residential a/c units)
                 O    Full diagnostics of cooling only and heat pumps operating in cooling mode
      •    ServiceAssistantOnline Web Service Communicate to clients, management, and end users recent service activity and resulting benefits (more...)
Features in Development
      •    Heat pump in heating mode diagnostics
      •    Diagnose units under cooler outdoor temperatures, helping to extend your cooling service/sales season
      •    Improve efficiency through sophisticated service recommendations when diagnostics indicates "No Faults Detected"
Accessories
           Single and two stage sensor arrays expand the Service Assistant's measurement capabilities.
Product Demonstrations

      •    Download the Service Assistant Palm application running in an emulator on your PC (7MB) Run a full featured demonstration on your PC with demo data.
      •    Inquire about a live Service Assistant demonstration
                 O    Visit our office for a demonstration of the Service Assistant directly for the development team!
                 O    Print this
                 O    Contact Field Diagnostic Services for help arranging for a product demonstration.
Free Downloads
      •    Download for FREE... SACalc - a refrigeration cycle analysis Palm Pilot application
                 O    Easily enter pressure and temperature measurements ...like using a hand calculator.
                 O    Performance indices are calculated including evaporating and condensing temperatures, condensing temperature over ambient, superheat and subcooling
                      based on integrated refrigerant property tables.
                 O    Superheat for fixed orifice units is evaluated based on entered data.

-------
More Information

     •    Honeywell Catalog page for the Service Assistant See Honeywell's presentation of Service Assistant benefits and features. Download cut sheets and instructions that are
           provided with the tool. Get list prices.
     •    American Express and Honeywell team up to provide leasing for the Service Assistant Easily achieve positive cash flow in the first month with the Service Assistant's
           leasing option.
     •    Honeywell HVAC  Service Assistant product cut sheet The cut sheet is a compact (2 sides of 1 page) full color description of the product.
     •    Refrigeration Cycle Diagnostics Overview This detailed document explains the technical underpinnings of how the Service Assistant analyzes data to provide diagnostics. It
           includes a discussion of the more challenging aspects of data interpretation.
     •    Estimating Efficiency and Capacity
           and capacity estimator technology.
     •    Technology  Report - /
           electric power demand and consumption. It is helpful for utility program managers and facility managers interested is applying the Service Assistant's patented technology
           to cost effectively  reduce utility bills.

     •    ServiceAssistantOnline web service helps all HVAC service stake holders better communicate.
     •    Before and After Report documents energy savings from strategically servicing  units on a big box retail store.
     •    Service  Assistant Wins 2003 AHR Expo Innovative Product Award The Service Assistant is the most innovative "Tool, Instrument, or Software" for 2003 in the HVAC
           Industry.
     •    Field Diagnostic Services Inc. is a leading edge developer of HVAC equipment  monitoring and diagnostic technology.

Purchasing the Service Assistant

     •    Contact your local Honeywell sales representative or distributor. Print this Honeywell cut sheet for a clear definition of the product and its Honeywell part numbers.
     •    Contact Field Diagnostic Services directly to learn how to purchase a Service Assistant.

-------
            Appendix F
EER Test Data from Units in SEQL Area

-------
                             Pre-Adsil  HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
38AE-012-500
T890439
Split System
1989
YTC Truck School
SS-1
    43.6     Amps
    208     Volts
    0.65
                           Published EER:
                           Calculated EER:
                           Nominal Capacity:
                           Age
                           Coil Conditon
                           Present Condition EER
                           kW/ton
                           Power supply:
                           Phase adjustment:
                           Compressor quantity:
  10.7
  10.7
  9.19
  15
  6%
  9.1
  1.31
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
0.50     Amps (Average of 2)   Power supply:
208     Volts               Phase adjustment:
0.70                        Fan quantity:
3-phase
  1.73
   1
                                                                1-Phase
                                                                   1
                                                                   2
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
it

1




0.75
0.25




0.1

0.75




X




X



            Amps              Power supply:
            Volts              Phase adjustment:
                              Fan quantity:

                        10.2   kW
                        0.15   kW
                        0.00   kW
                       10.34  kW-Condensing side only
                                      5.7%   Performance Degradation
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
4.3
4.1
3.9
4.3
3.7
4.9
4.2
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
208
208
t Measurment
10
77
57
33
85

98%
97%
10
85
11.80
24.0 6
30.4 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
89 F
104.5 F
133 in
31 in
28.6 sq-ft
7215
4.09 kg/sec
10.06 Tons
12.71 EER
0.94 kW/Ton
1 0.99
4 0.54
305 K
313 K
HVAC Data Sheet
Page 1 of 3
                                                                                                                EPA Adsil Evaluation
                                                                                                              York Technical College
                                                                                                                  Truck School SS-1

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                       Carrier                        Published EER:
                       38AE-012-500                  Calculated EER:
                       T890439                       Nominal Capacity:
                       Split System                    Age
                       1989                          CoilConditon
                       YTC Truck School               Present Condition EER
                       SS-1                          kW/ton
                           43.6    Amps              Power supply:
                           208    Volts              Phase adjustment:
                           0.65                      Compressor quantity:
                            0.5     Amps              Power supply:
                            208     Volts              Phase adjustment:
                            0.7                       Fan quantity:
  10.7
  10.7
  9.2
  15
  0%
  9.6
  1.25
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
            New
            Average
            Fair
            Poor
Coil Cleanliness
            Coated
            Clean
            Dirty
            Clogged
            Plugged
Fin Condition
            Like New
            Some Bent
            Smashed
            Dull/rough
            Corroded
            Pitted
            Flaking
Fin-Tube Attachment
            Like New
            Corrosion
            Some Loose
            Many Loose
                                   Amps             Power supply:
                                   Volts              Phase adjustment:
                                                     Fan quantity:

                                               10.2   kW
                                               0.15   kW
                                               0.00   kW
                                              10.34  kW - Condensing side only
                                     0.0%  Performance Degradation
3-phase
  1.73
   1
1-Phase
   1
   2
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
10.2
5.5
10.5
10.5
9.2
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
207
209
t Measurment
10
77
57
33
85

107%
1 03%
10
86
11.60
29.6 5
28.9 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
88 F
97 F
133 in
31 in
28.63 sq-ft
15762
8.93 kg/sec
12.77 Tons
17.21 EER
0.70 kW/Ton
7 0.99
2 0.56
304 K
309 K
HVAC Data Sheet
Page 2 of 3
                                                                                                                                     EPA Adsil Evaluation
                                                                                                                                    York Technical College
                                                                                                                                       Truck School SS-1

-------
    YTC Truck School
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-1     Summary
                10.7 BTU/W-h
               7215 CFM (Measured)
                9.19 tons
               10.00 tons
               28.63 sq-ft
                9.13 pre	9.60 post
Equipment age
15 years
Test Date
24-May

HVAC Service Assistant

OAT
85

Post Adsil Measurements
16-Jun

86

ST-SH
42


43

El
98%


107%

Cl
97%


103%

EER
12.2


13.2

kW
10.84


10.66

Physical Power and Capacity measurments
Cond Air, deg F
inlet
89


88

exhaust
104.5


97

Cond Air
AT(K)
8.6


5.0

kW
9.5


8.9

(kg/sec)
4.09


8.93


tons
10.06


12.77


EER
12.71


17.21

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
10.84
9.88
12.2
10.66
10.62
13.2
CU
9.5
10.06
12.71
8.9
12.77
17.21
Lit
9.85
10.19
12.42
10.00
10.31
12.38
Percent Difference
SA/Lit
110%
97%
98%
107%
103%
107%
CU/Lit
96%
99%
102%
89%
124%
139%
SS/Lit
100%
100%
85%
100%
100%
90%
Condensing Unit Summary - ARI Conditions
Test Data
SA
11.4
8.9
10.5
11.0
9.5
11.4
CU
9.9
9.1
10.9
9.2
11.4
14.9
Literature
10.31
9.19
10.69
10.31
9.19
10.69
Percent Difference
SA/Lit
110%
97%
98%
107%
103%
107%
CU/Lit
96%
99%
102%
89%
1 24%
1 39%
SA/CU
114%
98%
96%
120%
83%
77%
Predicted/SA


87%

-
80%
Predicted/CU


83%

-
61%
Predicted/
Original


85%

-
90%
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
12.2
13.2

10.4
11.4
9.2%
Condenser Test
12.71
17.21

10.91
14.82
35.9%
Spreadsheet
9.13
9.60

9.13
9.60
5.1%
            Weighted Average   91.8
                                                 358.6%
                                                                51.4%
HVAC Data Sheet
Page 3 of 3
                                                                                                                               EPA Adsil Evaluation
                                                                                                                             York Technical College
                                                                                                                                 Truck School SS-1

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
38ASQ008
1396G00194
Split Heat Pump
1991
YTC Student Services
HP-1

14.1 Amps
460 Volts
0.66

1.90 Amps
460 Volts
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Amps
Volts
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
       Power supply:
       Phase adjustment:
       Fan quantity:

7.4    kW
0.61    kW
0.00    kW
8.02    kW-Condensing side only
                                          11.1
                                          11.1
                                          7.40
                                           13
                                          7.5%
                                           9.6
                                          1.25
                                                            Btu/W-hr  (CU Only)
                                                            Btu/W-hr  (CU Only)
                                                            tons
                                                            years
                                                            (% degraded)
                                                            Btu/W-hr
                                        3-Phase
                                          1.73
                                           1
                                        1-Phase
                                           1
                                           1
Condenser Coil Assessment
Overall Unit Condition     _
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
                                      7.5%   Performance Degradation
             Corrosion
             Some Loose
             Many Loose

             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
.

.

.


FLUKE METER MEASUREMENTS
Y-measurment
Phase Volts Amps
1
2
3



kW PF



Delta Measurement
Phase Volts Amps
1 to 2
2 to 3
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP1
10





91%
82%
7.5
74
7.10
kW PF


F
F
Tons (Each)
kW

CU Capacity Estimates
F - K
F - K
in
in
sq-ft
(From Product Data)
kg/sec
Tons
EER
HVAC Data Sheet
Page 1 of 3
                                                                                             EPA Adsil Evaluation
                                                                                            York Technical College
                                                                                            Student Services HP-1

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
38ASQ008
1396G00194
Split Heat Pump
1991
YTC Student Services
HP-1
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
11.1
11.1
7.40
 13
0%
10.2
1.17
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    14.1    Amps              Power supply:
   460.0   Volts               Phase adjustment:
    0.7                       Compressor quantity:
    1.9    Amps              Power supply:
   460.0   Volts               Phase adjustment:
    0.7                       Fan quantity:
                                 3-Phase
                                   1.73
                                    1
                                 1-Phase
                                    1
                                    1
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1












X




X



           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                       7.4    kW
                       0.61    kW
                       0.00    kW
                       8.02    kW - Condensing side only
                                     0.0%   Performance Degradation
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
-
-



FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP 1
10

-
.


1 09%
101%
7.5
83
8.50


F
F
%
%
Tons
F
kW
CU Capacity Estimates
F - K
F - K
in
in
sq-ft
kg/sec
Tons
EER
HVAC Data Sheet
Page 2 of 3
                                                                                                             EPA Adsil Evaluation
                                                                                                           York Technical College
                                                                                                           Student Services HP-1

-------
    YTC Student Services
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
HP-1     Summary
                11.1 BTU/W-h
                NA CFM (Measured)
                7.40
                7.50 tons
                 NA sq-ft
                9.57 pre	10.23 post
Equipment age
13 years
Test Date
24-May
HVAC Service Assistant

OAT
74
EWB
60
El
91%
Cl
82%
EER
12.2
kW
7.01
Physical Power and Capacity measurments
Cond Air
inlet
NA
deg F
exhaust
NA
Cond Air
AT(K)
NA
kW
NA
(kg/sec)
NA

tons
NA

EER
NA

Post Adsil Measurements
14-Jun

83


60


109%


101%


13.1


8.39


NA


NA


NA


NA


NA


NA


NA

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
7.01
6.03
12.2
8.39
7.15
13.1
CU
NA
NA
NA
NA
NA
NA
Lit
6.59
7.35
13.39
7.07
7.08
12.02
Percent Difference
SA/Lit
106%
82%
91%
1 1 9%
101%
1 09%
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
101%
100%
86%
101%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
8.5
6.1
10.1
9.5
7.5
12.1
CU
NA
NA
NA
NA
NA
NA
Literature
7.97
7.40
11.15
7.97
7.40
11.15
Percent Difference
SA/Lit
106%
82%
91%
1 1 9%
101%
1 09%
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


94%


79%
Predicted/CU


NA


NA
Predicted/
Original


86%


92%
                                     EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
12.2
13.1

10.1
12.1
19.8%
Condenser Test
NA
NA

NA
NA
NA
Spreadsheet
9.57
10.23

9.57
10.23
6.9%
               Weighted Average  148.4%
                                                NA
                                                                  51.6%
HVAC Data Sheet
Page 3 of 3
                                                                                                                           EPA Adsil Evaluation
                                                                                                                          York Technical College
                                                                                                                          Student Services HP-1

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
48DJE006630
2891G07552
Package Cool
1991
YTC Student Center
RTU-25
7.8     Amps
460     Volts
0.87
                           1 .00
                           460
                           0.70
Evaporator fan data (if applicable)
Full load Amps:              3.00
Nameplate Voltage:           460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
           Amps
           Volts
Amps
Volts
                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    5.4    kW
                   0.56   kW
                   1.93   kW
                   5.96   kW-Condensing side only
                                                     10.4
                                                     10.4
                                                     5.19
                                                      13
                                                      5%
                                                      9.1
                                                     1.32
                                                                   Btu/W-hr  (CU Only)
                                                                   Btu/W-hr  (CU Only)
                                                                   tons
                                                                   years
                                                                   (% degraded)
                                                                   Btu/W-hr
                                                   3-Phase
                                                     1.73
                                                      1
                                                           3-Phase
                                                             1.73
                                                              1
                                                                                      3-Phase
                                                                                        1.73
                                                                                         2
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




1





0.5






X




X



                                     2.7%   Performance Degradation
CU Fan CFM Calculation
Measurement
Number
1
2
3
Average
ft/sec
NA
NA
NA
NA
FLUKE METER MEASUREMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
474
475
tMeasurment
COMP1
10
72
52
55
85

76%
82%
5
84
3.00
9 4
9 1
F
F
%
%
Tons
kW
CU Capacity Estimates
84 F
97 F
NAin
NAin
NA sq-ft
NA
NA kg/sec
NA Tons
NAEER
4 1
8 0.42
302 K
309 K
HVAC Data Sheet
Page 1 of 3
                                                                                                  EPA Adsil Evaluation
                                                                                                York Technical College
                                                                                                Student Center RTU-25

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
48DJE006630
2891G07552
Package Cool
1991
YTC Student Center
RTU-25
                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
10.4
10.4
5.19
 13
 0%
 9.5
1.26
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    7.8    Amps              Power supply:
   460.0   Volts               Phase adjustment:
    0.9                       Compressor quantity:
    1.0    Amps              Power supply:
   460.0   Volts               Phase adjustment:
    0.7                       Fan quantity:
Evaporator fan data (if applicable)
Full load Amps:               3.00     Amps
Nameplate Voltage:          460.00    Volts
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:

                                               5.4    kW
                                               0.56   kW
                                               1.93   kW
                                               5.96   kW-Condensing side only
                                                                                      3-Phase
                                                                                        1.73
                                                                                         1
                                                                                      3-Phase
                                                                                        1.73
                                                                                         1
                                                               3-Phase
                                                                1.73
                                                                2.00
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1





0.01






X




X



                                     0.1%   Performance Degradation
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
NA
NA
NA
NA
NA
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP 1
10





81%
88%
5
86
6.40


F
F
%
%
Tons
F
kW
CU Capacity Estimates
NA F NA K
NA F NA K
NA in
NA in
NA sq-ft
NA
NA kg/sec
NA Tons
NA EER
HVAC Data Sheet
Page 2 of 3
                                                                                                             EPA Adsil Evaluation
                                                                                                            York Technical College
                                                                                                           Student Center RTU-25

-------
    YTC Student Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-25  Summary
                10.4 BTU/W-h
                  -  CFM (Measured)
                5.19
                5.00 tons
                  - sq-ft
                9.10 Pre       9.51 Post
Equipment age
13 years
Test Date
24-May
HVAC Service Assistant

OAT
84
EWB
61
El
76%
Cl
82%
EER
8.4
kW
3.11
Physical Power and Capacity measurments
Cond Air
inlet
NA
deg F
exhaust
NA
Cond Air
AT(K)
NA
kW
NA
(kg/sec)
NA

tons
NA

EER
NA

Post Adsil Measurements


86


61


81%


88%


8.7


6.64


NA


NA


NA


NA


NA


NA


NA

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
3.11
4.02
8.4
6.64
4.27
8.7
CU
NA
NA
NA
NA
NA
NA
Lit
5.34
4.90
11.02
5.41
4.85
10.77
Percent Difference
SA/Lit
58%
82%
76%
123%
88%
81%
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
99%
100%
88%
99%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
3.5
4.3
7.9
7.4
4.6
8.4
CU
NA
NA
NA
NA
NA
NA
Literature
6.00
5.19
10.38
6.00
5.19
10.38
Percent Difference
SA/Lit
58%
82%
76%
123%
88%
81%
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


115%


108%
Predicted/CU


NA


NA
Predicted/
Original


88%


92%
                                     EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
8.4
8.7
7.9
8.4
6.6%
Condenser Test
NA
NA
NA
NA
NA
Spreadsheet
9.10
9.51
9.10
9.51
4.5%
               Weighted Average   32.9%
                                                NA
                                                                  22.7%
HVAC Data Sheet
Page 3 of 3
                                                                                                                           EPA Adsil Evaluation
                                                                                                                         York Technical College
                                                                                                                         Student Center RTU-25

-------
                             Pre-Adsil  HVAC  Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
38AD028610
A494368
Split System
1994
YTC Student Center
Ground Unit
    54.4     Amps
    460     Volts
    0.65
                           Published EER:
                           Calculated EER:
                           Nominal Capacity:
                           Age
                           Coil Conditon
                           Present Condition EER
                           kW/ton
                           Power supply:
                           Phase adjustment:
                           Compressor quantity:
 24.17
  10
  7.2
  1.67
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
3.00     Amps (Average of 2)   Power supply:
460     Volts               Phase adjustment:
0.70                        Fan quantity:
3-phase
  1.73
   1
                                                                3-Phase
                                                                  1.73
                                                                   3
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
it


1




0.5
0.1



0.1
0.25
0.65
0.1





X


X



            Amps              Power supply:
            Volts              Phase adjustment:
                              Fan quantity:

                        27.9   kW
                        5.01   kW
                        0.00   kW
                       32.94  kW-Condensing side only
                                      16.5%   Performance Degradation
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
NA
NA
NA
NA
NA
NA
NA
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
NA
NA
t Measurment
10
74
56
40
85

89%
70%
30
81
30.20
NA N
NA N
F
F
%
%
Tons
F
kW
A NA
A NA

CU Capacity Estimates
NA F
NA F
NA in
NA in
NA sq-ft
NA
NA kg/sec
NA Tons
NA EER
NA kW/Ton
HVAC Data Sheet
Page 1 of 3
                                                                                                                EPA Adsil Evaluation
                                                                                                              York Technical College
                                                                                                          Student Center Ground Unit

-------
                           Post-Ad si I  HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
38AD028610
A494368
Split System
1994
YTC Student Center
Ground Unit
54.4 Amps
460 Volts
0.65
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
 3      Amps              Power supply:
460     Volts              Phase adjustment:
0.7                       Fan quantity:
                                                             24.2
                                                              10
                                                              1%
                                                              8.2
                                                             1.46
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:             0
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
        Amps              Power supply:
        Volts              Phase adjustment:
                          Fan quantity:

                   27.9   kW
                   5.01   kW
                   0.00   kW
                   32.94   kW - Condensing side only
                                      1.0%  Performance Degradation
                                                            3-phase
                                                             1.73
                                                               1
3-Phase
  1.73
   3
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
NA
NA
NA
NA
NA
0.95
0.05
0.1
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
NA
NA
t Measurment
10
74
54
40
85

101%
91%
30
84
11.60
NA N
NA N
F
F
%
%
Tons
F
kW
A NA
A NA

CU Capacity Estimates
NA F
NA F
NA in
NA in
NA sq-ft
NA
NA kg/sec
NA Tons
NA EER
NA kW/Ton
HVAC Data Sheet
Page 2 of 3
                                                                                                          EPA Adsil Evaluation
                                                                                                         York Technical College
                                                                                                     Student Center Ground Unit

-------
    YTC Student Center
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
Ground Unit
     Summary
  8.8 BTU/W-h
  NA CFM (Measured)
24.17 tons
30.00 tons
  NA sq-ft
 7.19 pre	8.23 post
                                        Equipment age
10 years
Test Date
24-May

HVAC Service Assistant

OAT
81

Post Adsil Measurements
16-Jun

84

ST-SH
26


30

El
89%


101%

Cl
70%


91%

EER
7.9


9.0

kW
24.33


9.35

Physical Power and Capacity measurments
Cond Air, deg F
inlet
NA


NA

exhaust
NA


NA

Cond Air
AT(K)
NA


NA

kW
NA


NA

(kg/sec)
NA


NA


tons
NA


NA


EER
NA


NA

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
24.33
14.40
7.9
9.35
19.83
9.0
CU
NA
NA
NA
NA
NA
NA
Lit
27.92
20.57
8.84
29.49
21.79
8.87
Percent Difference
SA/Lit
87%
70%
89%
32%
91%
1 01 %
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
109%
120%
90%
109%
120%
103%
Condensing Unit Summary - ARI Conditions
Test Data
SA
26.4
14.1
7.1
9.6
18.4
8.1
CU
NA
NA
NA
NA
NA
NA
Literature
30.25
20.18
8.01
30.25
20.18
8.01
Percent Difference
SA/Lit
87%
70%
89%
32%
91%
1 01 %
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


101%

-
89%
Predicted/CU


NA

-
NA
Predicted/
Original


90%

-
103%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
7.9
9.0

7.8
8.9
Condenser Test
NA
NA

NA
NA
13.5% NA
Spreadsheet
7.19
8.23

7.19
8.23
14.5%
            Weighted Average  404.5%
                                                              434.8%
HVAC Data Sheet
Page 3 of 3
                                                                                                                             EPA Adsil Evaluation
                                                                                                                            York Technical College
                                                                                                                        Student Center Ground Unit

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Trane
YCH210B4
F1 4627920
RTU-Gas
1991
YTC - Library
Unit 2
14.5
460
0.74
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                   Amps              Power supply:
                                   Volts              Phase adjustment:
                                                     Compressor quantity:
3.00     Amps              Power supply:
460     Volts              Phase adjustment:
0.70                       Fan quantity:
                                                             10.2
                                                             10.2
                                                            17.29
                                                              13
                                                             3%
                                                             9.1
                                                             1.32
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
Evaporator fan data (if applicable)
Full load Amps:              7.60
Nameplate Voltage:           460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

1




0.95
0.05




0.1
0.1
0.2




1




1



        Amps              Power supply:
        Volts              Phase adjustment:
                          Fan quantity:

                   17.1   kW
                   3.34   kW
                   2.45   kW
                   20.42   kW - Condensing side only
                                     3.0%   Performance Degradation
                                                           3-phase
                                                             1.73
                                                              2
3-Phase
  1.73
   2
3-Phase
  1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
2.7
5.1
4.9
3.1
2.7
3.3
3.6
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
484
485
t Measurement
10
73
53
50
85
Circuit 1 (only)
91%
94%
10
77
12.40
22.2 1C
17.6 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
77 F
92 F
91 in
48 in
30.3 sq-ft
6613
3.74 kg/sec
8.93 Tons
7.54 EER
.7 1.0
5 0.41
298 K
306 K
HVAC Data Sheet
Page 1 of 3
                                                                                                          EPA Adsil Evaluation
                                                                                                        York Technical College
                                                                                                                Library Unit 2

-------
                           Post-Ad si I  HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Trane
YCH210B4
F1 4627920
RTU-Gas
1991
YTC - Library
Unit 2
14.5
460
0.74
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                   Amps              Power supply:
                                   Volts               Phase adjustment:
                                                      Compressor quantity:
 3     Amps              Power supply:
460    Volts               Phase adjustment:
0.7                       Fan quantity:
                                                             10.2
                                                             10.2
                                                             17.29
                                                              13
                                                             0%
                                                             9.3
                                                             1.29
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
Evaporator fan data (if applicable)
Full load Amps:               7.6
Nameplate Voltage:            460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
       Amps              Power supply:
       Volts               Phase adjustment:
                          Fan quantity:

                   17.1    kW
                   3.34    kW
                   2.45    kW
                   20.42   kW - Condensing side only
          0.0%   Performance Degradation
                                                           3-phase
                                                             1.73
                                                              2
3-Phase
  1.73
   2
3-Phase
  1.73
   1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
1.2
6.1
6.4
5.2
4.73
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
481
483
t Measurement
10
73
53
50
85
Circuit 1 (only)
84%
96%
10
88
13.40
21 1C
18.9 4
F
F
%
%
Tons
F
kW
CU Capacity Estimates
88 F
112 F
91 in
48 in
30.3 sq-ft
8600
4.87 kg/sec
18.57 Tons
15.59 EER
.1 1.0
2 0.45
304 K
318 K
HVAC Data Sheet
Page 2 of 3
                                                                                                          EPA Adsil Evaluation
                                                                                                        York Technical College
                                                                                                                 Library Unit 2

-------
    YTC - Library
    EER at ARI Conditions
    Condensing unit CFM
    Nominal  Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
Unit 2 Summary
                        10.2 BTU/W-h
                       6613 CFM (Measured)
                       17.29 tons
                       10.00 tons
                       30.33 sq-ft
                        9.08 pre	9.32 post
Equipment age
13 years
Test Date
24- May

HVAC Service Assistant

OAT
77

Post Adsil Measurements
14-Jun

88

EWB
61


61

El
91%


84%

Cl
94%


96%

EER
11.6


8.8

kW
10.72


11.58

Physical Power and Capacity measurments
Cond Air, deg F
inlet
77


88

exhaust
92


112

Cond Air
AT(K)
8.3


13.3

kW
14.2


14.3

(kg/sec)
3.74


4.87


tons
8.93


18.57


EER
7.54


15.59

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
10.72
8.27
11.6
11.58
7.86
8.8
CU
14.2
8.93
7.54
14.3
18.57
15.59
Lit
8.27
8.80
12.77
9.40
8.19
10.45
Percent Difference
SA/Lit
130%
94%
91%
123%
96%
84%
CU/Lit
172%
101%
59%
152%
227%
149%
SS/Lit
100%
100%
89%
100%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data
SA
13.2
8.1
9.2
12.6
8.3
8.5
CU
17.5
8.8
6.0
15.5
19.6
15.1
Literature
10.21
8.64
10.16
10.21
8.64
10.16
Percent Difference
SA/Lit
130%
94%
91%
123%
96%
84%
CU/Lit
172%
101%
59%
152%
227%
1 49%
SA/CU
75%
93%
154%
81%
42%
56%
Predicted/SA


98%

-
1 06%
Predicted/CU


151%

-
60%
Predicted/
Original


89%

-
92%
                                    EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.6
8.8

9.2
8.5
-7.7%
Condenser Test
7.54
15.59

6.00
15.15
152.3%
Spreadsheet
9.08
9.32

9.08
9.32
2.7%
             Weighted Average  -76.9%
                                                 1523.3%
                                                                  27.1%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                          EPA Adsil Evaluation
                                                                                                                                        York Technical College
                                                                                                                                                Library Unit 2

-------
                             Pre-Adsil  HVAC  Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCH210B4
F14627920
RTU-Gas
1991
YTC - Library
Unitl
    14.5     Amps
    460     Volts
    0.74
    3.00     Amps
    460     Volts
    0.70
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
Power supply:
Phase adjustment:
Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
  10.2
  10.2
 17.29
   13
                                                                  1.36
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
Evaporator fan data (if applicable)
Full load Amps:               7.60
Nameplate Voltage:            460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
it

1




0.9
0.1




0.4
0.1
0.5




1




1



            Amps              Power supply:
            Volts              Phase adjustment:
                              Fan quantity:

                        17.1   kW
                        3.34   kW
                        2.45   kW
                       20.42  kW-Condensing side only
                                      6.2%   Performance Degradation
3-phase
  1.73
   2
3-Phase
  1.73
   2
                                  3-Phase
                                    1.73
                                     1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
Average
ft/sec
5.9
6.1
4.5
3.9
2.3
3.4
2.7
4.1
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
484
485
t Measurement
10
73
53
50
85
Circuit 1 (only)
84%
90%
10
75
12.70
22.2 1C
17.6 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
75 F
92 F
91 in
48 in
30.3 sq-ft
7488
4.24 kg/sec
11.46 Tons
9.68 EER
.7 1.0
5 0.41
297 K
306 K
HVAC Data Sheet
Page 1 of 3
                                                                                                                EPA Adsil Evaluation
                                                                                                              York Technical College
                                                                                                                      Library Unit 1

-------
                           Post-Ad si I  HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Trane
YCH210B4
F1 4627920
RTU-Gas
1991
YTC - Library
Unitl
14.5
460
0.74
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                   Amps              Power supply:
                                   Volts               Phase adjustment:
                                                      Compressor quantity:
 3     Amps              Power supply:
460    Volts               Phase adjustment:
0.7                       Fan quantity:
                                                             10.2
                                                             10.2
                                                             17.29
                                                              13
                                                             0%
                                                             9.3
                                                             1.29
        Btu/W-hr
        Btu/W-hr
        tons
        years
        (% degraded)
        Btu/W-hr
(CU Only)
(CU Only)
Evaporator fan data (if applicable)
Full load Amps:               7.6
Nameplate Voltage:            460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
       Amps              Power supply:
       Volts               Phase adjustment:
                          Fan quantity:

                   17.1    kW
                   3.34    kW
                   2.45    kW
                   20.42   kW - Condensing side only
          0.0%   Performance Degradation
                                                           3-phase
                                                             1.73
                                                              2
3-Phase
  1.73
   2
3-Phase
  1.73
   1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
12.7
12.9
11.4
11.5
12.13
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
480
484
t Measurement
10
73
53
50
85
Circuit 1 (only)
93%
85%
10
85
11.10
20.2 9
14.8 2
F
F
%
%
Tons
F
kW
CU Capacity Estimates
86 F
95 F
91 in
48 in
30.3 sq-ft
22068
12.50 kg/sec
16.88 Tons
17.17 EER
6 0.99
2 0.30
303 K
308 K
HVAC Data Sheet
Page 2 of 3
                                                                                                          EPA Adsil Evaluation
                                                                                                         York Technical College
                                                                                                                 Library Unit 1

-------
    YTC - Library
    EER at ARI Conditions
    Condensing unit CFM
    Nominal  Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
Unit 1  Summary
                        10.2 BTU/W-h
                       7488 CFM (Measured)
                       17.29 tons
                       10.00 tons
                       30.33 sq-ft
                        8.82 pre	9.32 post
Equipment age
13 years
Test Date
24- May

HVAC Service Assistant

OAT
75

Post Adsil Measurements
14-Jun

85

EWB
61


61

El
84%


93%

Cl
90%


85%

EER
11.1


10.3

kW
10.98


9.60

Physical Power and Capacity measurments
Cond Air, deg F
inlet
75


86

exhaust
92


94.5

Cond Air
AT(K)
9.4


4.7

kW
14.2


11.8

(kg/sec)
4.24


12.50


tons
11.46


16.88


EER
9.68


17.17

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
10.98
8.02
11.1
9.60
7.10
10.3
cu
14.2
11.46
9.68
11.8
16.88
17.17
Lit
8.06
8.91
13.26
9.09
8.35
11.03
Percent Difference
SA/Lit
136%
90%
84%
106%
85%
93%
CU/Lit
176%
129%
73%
130%
202%
156%
SS/Lit
100%
100%
87%
100%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data
SA
13.9
7.8
8.5
10.8
7.3
9.4
CU
18.0
11.1
7.4
13.3
17.5
15.8
Literature
10.21
8.64
10.16
10.21
8.64
10.16
Percent Difference
SA/Lit
136%
90%
84%
106%
85%
93%
CU/Lit
176%
129%
73%
130%
202%
1 56%
SA/CU
77%
70%
115%
81%
42%
60%
Predicted/SA


103%

-
93%
Predicted/CU


119%

-
56%
Predicted/
Original


87%

-
92%
                                    EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.1
10.3

8.5
9.4
10.7%
Condenser Test
9.68
17.17

7.42
15.81
113.2%
Spreadsheet
8.82
9.32

8.82
9.32
5.7%
             Weighted Average  107.1 %
                                                 1131.7%
                                                                  56.9%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                          EPA Adsil Evaluation
                                                                                                                                        York Technical College
                                                                                                                                                Library Unit 1

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
American Standard
TWA060A400A2
G06289343
Split-System
1992
YTC Hood Center
HP-2
    9.1     Amps
    460    Volts
    0.77
    0.90    Amps
    460    Volts
    0.70
Evaporator fan data (If applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
           Amps
           Volts
       Published EER:
       Calculated EER:
       Nominal Capacity:
       Age
       Coll Condlton
       Present Condition EER
       kW/ton
       Power supply:
       Phase adjustment:
       Compressor quantity:
       Power supply:
       Phase adjustment:
       Fan quantity:
       Power supply:
       Phase adjustment:
       Fan quantity:

 5.6    kW
0.29    kW
0.00    kW
5.87    kW-Condensing side only
  9.9
  9.9
  4.82
  12
  5%
  8.8
  1.37
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
3-Phase
  1.73
   1
1-Phase
   1
   1
Condenser Coll Assessment
Overall Unit Condition     	
             New       '
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                                      NA    Brush Colls
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Number
1
2
3
4
Average
ft/sec





FLUKE METER MEASUREMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP 1
10
77
55
43
85

71%
44%
5
77
4.20


F
F
%
%
Tons
kW
CU Capacity Estimates
F - K
F - K
in
in
sq-ft
kg/sec
Tons
EER
HVAC Data Sheet
Page 1 of 3
                                                                                                        EPA Adsil Evaluation
                                                                                                      York Technical College
                                                                                                                    HP-2

-------
                            Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
American Standard
TWA060A400A2
G06289343
Split-System
1992
YTC Hood Center
HP-2
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coll Condlton
Present Condition EER
kW/ton
 9.9
 9.9
4.82
 12
 0%
 9.2
1.31
Btu/W-hr   (CU Only)
Btu/W-hr   (CU Only)
tons
years
(% degraded)
Btu/W-hr
    9.1      Amps               Power supply:
   460.0    Volts               Phase adjustment:
    0.8                         Compressor quantity:
    0.9     Amps               Power supply:
   460.0    Volts               Phase adjustment:
    0.7                        Fan quantity:
                                  3-Phase
                                    1.73
                                     1
                                  1-Phase
                                     1
                                     1
Evaporator fan data (If applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
            Amps               Power supply:
            Volts               Phase adjustment:
                               Fan quantity:

                        5.6    kW
                        0.29    kW
                        0.00    kW
                        5.87    kW - Condensing side only
              0.0%   Performance Degradation
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Number
1
2
3
4
Average
ft/sec





FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP1
10
72
52
50
85

83%
79%
5
74
5.80


F
F
%
%
Tons
F
kW
CU Capacity Estimates
F - K
F - K
in
in
sq-ft
kg/sec
Tons
EER
HVAC Data Sheet
Page 2 of 3
                                                                                                  EPA Adsil Evaluation
                                                                                                 York Technical College
                                                                                                               HP-2

-------
    YTC Hood Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
HP-2     Summary
                 9.9 BTU/W-h             Equipment age
                NA  CFM (Measured)
               4.82
                5.00 tons
                 NA sq-ft
                8.76 pre	9.16  post
12 years
Test Date
24-May
HVAC Service Assistant

OAT
77
EWB
62
El
71%
Cl
44%
EER
8.5
kW
4.05
Physical Power and Capacity measurments
Cond Air, deg F
inlet
NA
exhaust
NA
Cond Air
AT(K)
NA
kW
NA
(kg/sec)
NA

tons
NA

EER
NA

Post Adsil Measurements


74


62


83%


79%


10.4


5.59


NA


NA


NA


NA


NA


NA


NA

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
4.05
2.14
8.5
5.59
3.91
10.4
CU
NA
NA
NA
NA
NA
NA
Lit
4.88
4.87
11.98
4.75
4.95
12.49
Percent Difference
SA/Lit
83%
44%
71%
118%
79%
83%
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
101%
100%
89%
101%
100%
93%
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
4.8
2.1
7.0
6.9
3.8
8.2
CU
NA
NA
NA
NA
NA
NA
Literature
5.84
4.82
9.90
5.84
4.82
9.90
Percent Difference
SA/Lit
83%
44%
71%
118%
79%
83%
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


125%


107%
Predicted/CU






Predicted/
Original


88%


93%
                                       EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
8.5
10.4
7.0
8.2
16.9%
Condenser Test
NA
NA
NA
NA
NA
Spreadsheet
8.76
9.16
8.76
9.16
4.6%
               Weighted Average
                                   84.5%
                                                      NA
                                                                    23.1%
HVAC Data Sheet
Page 3 of 3
                                                                                                                         EPA Adsil Evaluation
                                                                                                                       York Technical College
                                                                                                                                     HP-2

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
38YCC036
3200E19247
Split System cool
2000
YTC Hood Center
HP-1
    11.1    Amps
    230    Volts
    0.77
    1.40
    230
    0.70
Evaporator fan data (If applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Amps
Volts
           Amps
           Volts
                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coll Condlton
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:

            3.4   kW
            0.23   kW
            0.11   kW
            3.63   kW-Condensing side only
                                   9.4
                                   9.4
                                   2.84
                                    4
                                   5%
                                   8.9
                                   1.34
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
                                 3-Phase
                                   1.73
                                    1
1-Phase
   1
   1
Condenser Coll Assessment
Overall Unit Condition     	
             New       '
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
              5.0%   Performance Degradation
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Number
1
2
3
4
Average
ft/sec
6.2
6.2
6.2
6.2
6.2
FLUKE METER MEASUREMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
202
205
t Measurment
COMP 1
10
72
55
50
85

105%
99%
3
79
3.50
9.4 1.92 1
8.23 0.75 0.43
F
F
%
%
Tons
kW
CU Capacity Estimates
79 F 299 K
87 F 304 K
90 in
23 in
14.4sq-ft
5,348
3.03 kg/sec
3.85 Tons
17.30 EER
HVAC Data Sheet
Page 1 of 3
                                                                                                        EPA Adsil Evaluation
                                                                                                      York Technical College
                                                                                                                    HP-1

-------
                            Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
38YCC036
3200E19247
Split System cool
2000
YTC Hood Center
HP-1
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coll Condlton
Present Condition EER
kW/ton
9.4
9.4
2.8
 4
0%
9.4
1.28
Btu/W-hr   (CU Only)
Btu/W-hr   (CU Only)
tons
years
(% degraded)
Btu/W-hr
    11.1     Amps               Power supply:
   230.0    Volts               Phase adjustment:
    0.77                        Compressor quantity:
    1.4     Amps               Power supply:
   230.0    Volts               Phase adjustment:
    0.7                        Fan quantity:
                                  3-Phase
                                     1.7
                                     1.0
                                  1-Phase
                                     1.0
                                     1.0
Evaporator fan data (If applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
            Amps               Power supply:
            Volts               Phase adjustment:
                               Fan quantity:

                        3.4    kW
                        0.23    kW
                        0.11    kW
                        3.63    kW - Condensing side only
              0.0%   Performance Degradation
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Number
1
2
3
4
Average
ft/sec
6.2
6.4
7.6
7.0
6.8
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
205
203
t Measurment
COMP1
10
72
52
50
85

115%
117%
3
82
3.60
7.8 0.
9.2 1.
F
F
%
%
Tons
F
kW
CU Capacity Estimates
76 F
87 F
90 in
23 in
14.4 sq-ft
5865
3.32 kg/sec
5.81 Tons
27.43 EER
58 0.44
36 1.00
298 K
304 K
HVAC Data Sheet
Page 2 of 3
                                                                                                  EPA Adsil Evaluation
                                                                                                 York Technical College
                                                                                                               HP-1

-------
    YTC Hood Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
HP-1     Summary
                 9.4 BTU/W-h
              5,348  CFM (Measured)
               2.84  tons
                3.00 tons
               14.38 sq-ft
                8.93 pre	9.37 post
Equipment age
4 years
Test Date
24-May
HVAC Service Assistant

OAT
79
EWB
60
El
105%
Cl
99%
EER
11.0
kW
3.32
Physical Power and Capacity measurments
Cond Air
inlet
79
deg F
exhaust
87
Cond Air
AT(K)
4.4
kW
2.67
(kg/sec)
3.03

tons
3.85

EER
17.30

Post Adsil Measurements
13-Jun

82


60


115%


117%


11.7


3.41


76


87


6.1


2.54


3.32


5.81


27.43

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
3.32
2.76
11.0
3.41
3.22
11.7
CU
2.67
3.85
17.30
2.54
5.81
27.43
Lit
3.19
2.79
10.48
3.25
2.75
10.15
Percent Difference
SA/Lit
104%
99%
105%
105%
1 1 7%
1 1 5%
CU/Lit
84%
138%
165%
78%
211%
270%
SS/Lit
100%
100%
95%
100%
1 00%
1 00%
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
3.8
2.8
9.8
3.8
3.3
10.8
CU
3.0
3.9
15.5
2.8
6.0
25.3
Literature
3.64
2.84
9.37
3.64
2.84
9.37
Percent Difference
SA/Lit
104%
99%
105%
105%
1 1 7%
1 1 5%
CU/Lit
84%
138%
165%
78%
21 1 %
270%
SA/CU
124%
72%
64%
134%
55%
43%
Predicted/SA


91%

-
83%
Predicted/CU


58%

-
35%
Predicted/
Original


95%

-
100%
                                     EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.0
11.7

9.8
10.8
9.5%
Condenser Test
17.30
27.43

15.47
25.34
63.8%
Spreadsheet
8.93
9.37

8.93
9.37
5.0%
               Weighted Average   28.6%
                                                    191.3%
                                                                   15.0%
HVAC Data Sheet
Page 3 of 3
                                                                                                                            EPA Adsil Evaluation
                                                                                                                          York Technical College
                                                                                                                                        HP-1

-------
                            Pre-Adsil  HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCH300B4
G071427640
RTU-Gas
1992
YTC - Hood Center
RTU-9
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
 10.3
 10.3
22.67
 12
 4%
 9.2
 1.30
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    17.7    Amps              Power supply:
    460    Volts               Phase adjustment:
    0.87                       Compressor quantity:
    3.00    Amps              Power supply:
    460    Volts               Phase adjustment:
    0.70                       Fan quantity:
Evaporator fan data (if applicable)
Full load Amps:              11.00    Amps
Nameplate Voltage:            460     Volts
Adjust FLA to RLA:             0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
                              Power supply:
                              Phase adjustment:
                              Fan quantity:

                       24.5   kW
                       1.93   kW
                       3.54   kW
                       26.44   kW - Condensing side only
                                 3-phase
                                   1.73
                                    2
                                 1-Phase
                                    1
                                    2
                                 3-Phase
                                   1.73
                                    1
Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                                     3.7%   Performance Degradation
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
3.9
2.9
10.2
10.2
2.7
3.3
5.5
    0.9
    0.1
    0.9
    0.1
    0.5
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3
Delta Measurement
Phase
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency



Volts
486
485
t Measurement
10
70
50
50
85
Circuit 1
88%
90%
12.5
76
15.30






Amps kW PF
40.4 1£
37.6 8
F
F
%
%
Circ


Tons
F
kW
CU Capacity Estimates
73 F
108. 5 F
109 in
48 in
36.3 sq-ft
12063
6.83 kg/sec
38.54 Tons
16.40 EER
.6 1
6 0.47

uit2
91%
91%
12.5 Tons
76 F
5.10 kW
296 K
316 K
HVAC Data Sheet
Page 1 of 3
                                                                                                              EPA Adsil Evaluation
                                                                                                            York Technical College
                                                                                                                         RTU-9

-------
                           Post-Adsil HVAC  Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCH300B4
G071 427640
RTU-Gas
1992
YTC - Hood Center
RTU-9

17.7 Amps
460 Volts
0.87

3 Amps
460 Volts
0.7
Evaporator fan data (if applicable)
Full load Amps:               11
Nameplate Voltage:            460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
       Power supply:
       Phase adjustment:
       Fan quantity:

 24.5   kW
 1 .93   kW
 3.54   kW
26.44   kW- Condensing side only
  0.0%   Performance Degradation
                                                      10.3
                                                      10.3
                                                     22.67
                                                      12
                                                      0%
                                                      9.5
                                                      1.26
                                                 Btu/W-hr
                                                 Btu/W-hr
                                                 tons
                                                 years
                                                 (% degraded)
                                                 Btu/W-hr
                  (CU Only)
                  (CU Only)
Amps
Volts
                                                    3-phase
                                                      1.73
                                                       2
                                                    1-Phase
                                                       1
                                                       2
3-Phase
  1.73
   1
             Corrosion
             Some Loose
             Many Loose

             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
Average
Ft/Sec
16.0
6.8
15.8
13.9
12.2
15.6
17.0
13.1
13.8
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
483
484
t Measurement
10
72
52
50
85
Circuit 1
102%
103%
12.5
90
15.20
38.2 1E
16.3 8
F
F
%
%
Circ


Tons
F
kW
CU Capacity Estimates
85 F
105 F
109 in
48 n
36.3 sq-ft
30084
17.04 kg/sec
54. 15 Tons
24.25 EER
.5 1
3 0.48

uit2
00%
00%
12.5 Tons
88 F
14.90 kW
303 K
314 K
HVAC Data Sheet
Page 2 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                       York Technical College
                                                                                                                    RTU-9

-------
    YTC - Hood Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-9   Summary
                10.3 BTU/W-h
              12063 CFM (Measured)
               22.67 tons
               25.00 tons
               36.33 sq-ft
                9.21 pre	9.53 post
Equipment age
12 years
Test Date
24- May

HVAC Service Assistant

OAT
76

Post Adsil Measurements
14-Jun

90

EWB
60


60

El
90%


101%

Cl
91%


91%

EER
11.4


10.2

kW
27.56


27.29

Physical Power and Capacity measurments
Cond Air, deg F
inlet
73


85

exhaust
108.5


105

Cond Air
AT(K)
19.7


11.1

kW
28.2


26.8

(kg/sec)
6.83


17.04


tons
38.54


54.15


EER
16.40


24.25

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
27.56
21.63
11.4
27.29
19.98
10.2
CU
28.2
38.54
16.40
26.8
54.15
24.25
Lit
22.42
23.90
12.79
26.35
22.08
10.05
Percent Difference
SA/Lit
123%
91%
90%
1 04%
91%
1 01 %
CU/Lit
126%
161%
128%
102%
245%
241 %
SS/Lit
94%
95%
90%
94%
95%
93%
Condensing Unit Summary - ARI Conditions
Test Data
SA
34.5
21.7
9.2
29.0
21.7
10.4
CU
35.3
38.7
13.2
28.5
58.8
24.7
Literature
28.05
23.98
10.26
28.05
23.98
10.26
Percent Difference
SA/Lit
123%
91%
90%
104%
91%
101%
CU/Lit
126%
161%
128%
102%
245%
241 %
SA/CU
98%
56%
70%
102%
37%
42%
Predicted/SA


100%

-
89%
Predicted/CU


70%

-
37%
Predicted/
Original


90%

-
93%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.4
10.2

9.2
10.4
12.8%
Condenser Test
16.40
24.25

13.15
24.74
88.1%
Spreadsheet
9.21
9.53

9.21
9.53
3.4%
             Weighted Average  321.2%
                                                2203.0%
                                                                85.6%
HVAC Data Sheet
Page 3 of 3
                                                                                                                              EPA Adsil Evaluation
                                                                                                                            York Technical College
                                                                                                                                         RTU-9

-------
                            Pre-Adsil  HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCH300B4
G071427640
RTU-Gas
1992
YTC - Hood Center
RTU-5
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
 9.6
 9.6
23.98
 12
 0%
 8.8
 1.36
Btu/W-hr
Btu/W-hr
tons
years
(% degraded)
Btu/W-hr
(CU Only)
(CU Only)
    17.7    Amps              Power supply:
    460    Volts               Phase adjustment:
    0.95                       Compressor quantity:
    3.00    Amps              Power supply:
    460    Volts               Phase adjustment:
    0.70                       Fan quantity:
Evaporator fan data (if applicable)
Full load Amps:              11.00    Amps
Nameplate Voltage:            460     Volts
Adjust FLA to RLA:             0.70
Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                              Power supply:
                              Phase adjustment:
                              Fan quantity:

                       26.8   kW
                       3.34   kW
                       3.54   kW
                       30.11   kW-Condensing side only
                                 3-phase
                                   1.73
                                    2
                                 3-Phase
                                   1.73
                                    2
                                 3-Phase
                                   1.73
                                    1
              0.0%   Performance Degradation
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
15.2
14.5
12.7
12.5
15.4
11.7
13.667
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
488
488
t Measurement
10
72
52
50
85
Circuit 1 (only)
1 00%
98%
15
80
17.80
22.7 1
18.9 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
80 F
91 F
109 in
48 in
36.3 sq-ft
29793
16.87 kg/sec
29.49 Tons
23.75 EER
1 1
9 0.42
300 K
306 K
HVAC Data Sheet
Page 1 of 3
                                                                                                              EPA Adsil Evaluation
                                                                                                            York Technical College
                                                                                                                         RTU-5

-------
                            Post-Adsil  HVAC  Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCH300B4
G071 427640
RTU-Gas
1992




YTC- Hood Center
RTU-5
17.7
460
0.95
3
460
0.7

Amps
Volts
Amps
Volts
Evaporator fan data (if applicable)
Full load Amps:                11
Nameplate Voltage:            460
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition      	
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                                                       Published EER:
                                                       Calculated EER:
                                                       Nominal Capacity:
                                                       Age
                                                       Coil Conditon
                                                       Present Condition EER
                                                       kWrton
                                                       Power supply:
                                                       Phase adjustment:
                                                       Compressor quantity:
                                                       Power supply:
                                                       Phase adjustment:
                                                       Fan quantity:
Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:

            26.8   kW
            3.34   kW
            3.54   kW
            30.11   kW - Condensing side only
  0.0%    Performance Degradation
                                                       9.6
                                                       9.6
                                                      23.98
                                                        12
                                                     3-phase
                                                       1.73
                                                        2
                                                     3-Phase
                                                       1.73
                                                        2
3-Phase
  1.73
   1
         Btu/W-hr  (CD Only)
         Btu/W-hr  (CD Only)
         tons
         years
         (% degraded)
         Btu/W-hr
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
Average
ft/sec
15.4
12.7
14.6
13.9
12.9
11.1
15.2
10.7
13.31
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
488
488
t Measurement
10
72
52
50
85
Circuit 1 (only)
101%
103%
15
77
18.30
23.4 11.1 0.99
19.1 3.7 0.40
F
F
%
%
Tons
F
kW
CU Capacity Estimates
78 F 299 K
87 F 304 K
109 in
48 n
36.3 sq-ft
29021
16.44 kg/sec
23.51 Tons
19.06 EER
HVAC Data Sheet
Page 2 of 3
                                                                                                           EPA Adsil Evaluation
                                                                                                          York Technical College
                                                                                                                       RTU-5

-------
    YTC - Hood Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-5   Summary
                 9.6 BTU/W-h
              29793 CFM (Measured)
               23.98 tons
               15.00 tons
               36.33 sq-ft
                8.85 pre	8.85 post
Equipment age
12 years
Test Date
24- May

HVAC Service Assistant

OAT
80

Post Adsil Measurements
14-Jun

77

EWB
60


60

El
100%


101%

Cl
98%


103%

EER
10.8


11.5

kW
14.23


14.63

Physical Power and Capacity measurments
Cond Air, deg F
inlet
80


78

exhaust
91


87

Cond Air
AT(K)
6.1


5.0

kW
14.9


14.8

(kg/sec)
16.87


16.44


tons
29.49


23.51


EER
23.75


19.06

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
14.23
11.46
10.8
14.63
12.24
11.5
CU
14.9
29.49
23.75
14.8
23.51
19.06
Lit
12.97
11.69
10.82
12.50
11.88
11.41
Percent Difference
SA/Lit
110%
98%
100%
117%
103%
1 01 %
CU/Lit
115%
252%
220%
118%
198%
167%
SS/Lit
101%
100%
92%
101%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data
SA
16.4
11.7
9.6
17.5
12.3
9.7
CU
17.2
30.2
21.1
17.7
23.7
16.1
Literature
14.95
11.99
9.62
14.95
11.99
9.62
Percent Difference
SA/Lit
110%
98%
100%
117%
103%
101%
CU/Lit
115%
252%
220%
118%
198%
1 67%
SA/CU
95%
39%
46%
99%
52%
60%
Predicted/SA


92%

-
91%
Predicted/CU


42%

-
55%
Predicted/
Original


92%

-
92%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
10.8
11.5

9.6
9.7
1 .0%
Condenser Test
23.75
19.06

21.13
16.08
-23.9%
Spreadsheet
8.85
8.85

8.85
8.85
0.0%
             Weighted Average   15.0%
                                                -358.7%
                                                                 0.0%
HVAC Data Sheet
Page 3 of 3
                                                                                                                              EPA Adsil Evaluation
                                                                                                                            York Technical College
                                                                                                                                         RTU-5

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
SFHD030
J97M72722
RTU-Gas
1991
YTC - Hood Center
RTU-6
    27.3    Amps
    460    Volts
    0.75
1.80
460
0.70
Evaporator fan data (If applicable)
Full load Amps:              10.80
Nameplate Voltage:           460
Adjust FLA to RLA:           0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                          Published EER:
                          Calculated EER:
                          Nominal Capacity:
                          Age
                          Coll Condlton
                          Present Condition EER
                          kW/ton
                          Power supply:
                          Phase adjustment:
                          Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
                             Power supply:
                             Phase adjustment:
                             Fan quantity:

                       32.6   kW
                       3.01   kW
                       3.48   kW
                      35.60  kW-Condensing side only
             12.7%   Performance Degradation
           Amps
           Volts
        Amps
        Volts
                                   9.7    Btu/W-hr  (CU Only)
                                   9.7    Btu/W-hr  (CU Only)
                                  28.74  tons
                                   13    years
                                   13%   (% degraded)
                                   8.0    Btu/W-hr
                                   1.51
                                 3-phase
                                   1.73
                                    2
3-Phase
  1.73
   3
                                 3-Phase
                                   1.73
                                    1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
Average
ft/sec
NA
NA
NA
NA
    0.5
    0.4
    0.1
    0.05
    0.75
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
NA
NA
t Measurement
10
72
52
50
85
Circuit 1
103%
98%
30
84
34.50
NA N
NA N
F
F
%
%
A NA
A NA

Two comp. on one circuit
Tons
F
kW

CU Capacity Estimates
NA F NA K
NA F NA K
NA in
NA in
NA sq-ft
NA
NA kg/sec
NA Tons
NA EER
HVAC Data Sheet
Page 1 of 3
                                                                                                        EPA Adsil Evaluation
                                                                                                       York Technical Center
                                                                                                                   RTU-6

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
SFHD030
J97M72722
RTU-Gas
1991
YTC - Hood Center
RTU-6
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
 9.7
 9.7
28.74
 13
 0%
 8.9
 1.35
Btu/W-hr
Btu/W-hr
tons
years
(% degraded)
Btu/W-hr
(CU Only)
(CU Only)
    27.3    Amps              Power supply:
    460    Volts               Phase adjustment:
    0.75                       Compressor quantity:
    1.8    Amps              Power supply:
    460    Volts               Phase adjustment:
    0.7                       Fan quantity:
Evaporator fan data (if applicable)
Full load Amps:              10.8
Nameplate Voltage:           460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                       32.6   kW
                       3.01   kW
                       3.48   kW
                       35.60   kW - Condensing side only
              0.0%   Performance Degradation
                                 3-phase
                                   1.73
                                    2
                                 3-Phase
                                   1.73
                                    3
                                 3-Phase
                                   1.73
                                    1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
NA
NA
NA
NA
NA
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurement
10
70
50
65
85
Circuit 1 (only)
102%
99%
30
78
35.00


F
F
%
%
Tons
F
kW
CU Capacity Estimates
NA F NA K
NA F NA K
NA in
NA in
NA sq-ft
NA
NA kg/sec
NA Tons
NA EER
HVAC Data Sheet
Page 2 of 3
                                                                                                             EPA Adsil Evaluation
                                                                                                             York Technical Center
                                                                                                                         RTU-6

-------
    YTC - Hood Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-6   Summary
                 9.7 BTU/W-h
             NA    CFM (Measured)
               28.74 tons
               30.00 tons
             NA    sq-ft
                7.96 pre	8.89 post
Equipment age
13 years
Test Date
24- May

HVAC Service Assistant

OAT
84

Post Adsil Measurements
14-Jun

78

EWB
60


59

El
103%


102%

Cl
98%


99%

EER
11.1


11.9

kW
33.05


33.53

Physical Power and Capacity measurments
Cond Air, deg F
inlet
NA


NA

exhaust
NA


NA

Cond Air
AT(K)
NA


NA

kW
NA


NA

(kg/sec)
NA


NA


tons
NA


NA


EER
NA


NA

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
33.05
26.31
11.1
33.53
26.72
11.9
CU
NA
NA
NA
NA
NA
NA
Lit
30.00
26.85
10.74
27.66
26.99
11.71
Percent Difference
SA/Lit
110%
98%
103%
121%
99%
102%
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
100%
100%
82%
100%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data
SA
39.2
28.2
10.0
43.1
28.5
9.9
CU
NA
NA
NA
NA
NA
NA
Literature
35.57
28.74
9.70
35.57
28.74
9.70
Percent Difference
SA/Lit
110%
98%
103%
121%
99%
102%
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


80%

-
81%
Predicted/CU


NA

-
NA
Predicted/
Original


82%

-
92%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.1
11.9

10.0
9.9
-1.0%
Condenser Test
NA
NA

NA
NA
NA
Spreadsheet
7.96
8.89

7.96
8.89
11.7%
            Weighted Average  -29.1%
                                             NA
                                                              349.5%
HVAC Data Sheet
Page 3 of 3
                                                                                                                              EPA Adsil Evaluation
                                                                                                                             York Technical Center
                                                                                                                                         RTU-6

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
SFHCC25
J91M72724
RTU-Gas
1991
YTC - Hood Center
RTU-7
    27.3    Amps
    460    Volts
    0.62
1.80
460
0.70
Evaporator fan data (If applicable)
Full load Amps:              7.30
Nameplate Voltage:           460
Adjust FLA to RLA:           0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                          Published EER:
                          Calculated EER:
                          Nominal Capacity:
                          Age
                          Coll Condlton
                          Present Condition EER
                          kW/ton
                          Power supply:
                          Phase adjustment:
                          Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
                             Power supply:
                             Phase adjustment:
                             Fan quantity:

                       26.9   kW
                       3.01   kW
                       2.35   kW
                      29.95  kW-Condensing side only
             11.5%  Performance Degradation
           Amps
           Volts
        Amps
        Volts
                                   9.7    Btu/W-hr  (CU Only)
                                   9.7    Btu/W-hr  (CU Only)
                                  24.30  tons
                                   13    years
                                   11%   (% degraded)
                                   8.1    Btu/W-hr
                                   1.48
                                 3-phase
                                   1.73
                                    2
3-Phase
  1.73
   3
                                 3-Phase
                                   1.73
                                    1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
Average
ft/sec
NA
NA
NA
NA
    0.5
    0.5
    0.75
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
NA
NA
t Measurement
10
70
50
55
85
Circuit 1
79%
82%
25
70
30.80
NA N
NA N
F
F
%
%
Tons
F
kW
A NA
A NA

CU Capacity Estimates
NA F NA K
NA F NA K
NA in
NA in
NA sq-ft
NA
NA kg/sec
NA Tons
NA EER
HVAC Data Sheet
Page 1 of 3
                                                                                                        EPA Adsil Evaluation
                                                                                                      York Technical College
                                                                                                                   RTU-7

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
SFHCC25
J91M72724
RTU-Gas
1991
YTC - Hood Center
RTU-7
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
 9.7
 9.7
24.30
 13
 0%
 8.9
 1.34
Btu/W-hr
Btu/W-hr
tons
years
(% degraded)
Btu/W-hr
(CU Only)
(CU Only)
    27.3    Amps              Power supply:
    460    Volts               Phase adjustment:
    0.62                       Compressor quantity:
    1.8    Amps              Power supply:
    460    Volts               Phase adjustment:
    0.7                       Fan quantity:
Evaporator fan data (if applicable)
Full load Amps:               7.3
Nameplate Voltage:            460
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
           Amps              Power supply:
           Volts               Phase adjustment:
                              Fan quantity:

                       26.9   kW
                       3.01   kW
                       2.35   kW
                       29.95   kW - Condensing side only
              0.0%   Performance Degradation
                                 3-phase
                                   1.73
                                    2
                                 3-Phase
                                   1.73
                                    3
                                 3-Phase
                                   1.73
                                    1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
NA
NA
NA
NA
NA
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurement
10
70
50
65
85
Circuit 1 (only)
109%
1 08%
25
85
29.60


F
F
%
%
Tons
F
kW
CU Capacity Estimates
NA F NA K
NA F NA K
NA in
NA in
NA sq-ft
NA
NA kg/sec
NA Tons
NA EER
HVAC Data Sheet
Page 2 of 3
                                                                                                             EPA Adsil Evaluation
                                                                                                            York Technical College
                                                                                                                         RTU-7

-------
    YTC - Hood Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-7   Summary
                 9.7 BTU/W-h
             NA    CFM (Measured)
               24.30 tons
               25.00 tons
             NA    sq-ft
                8.08 pre	8.93 post
Equipment age
13 years
Test Date
24- May

HVAC Service Assistant

OAT
70

Post Adsil Measurements
14-Jun

85

EWB
60


62

El
79%


109%

Cl
82%


108%

EER
10.2


11.4

kW
29.94


28.77

Physical Power and Capacity measurments
Cond Air, deg F
inlet
NA


NA

exhaust
NA


NA

Cond Air
AT(K)
NA


NA

kW
NA


NA

(kg/sec)
NA


NA


tons
NA


NA


EER
NA


NA

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
29.94
19.54
10.2
28.77
25.21
11.4
CU
NA
NA
NA
NA
NA
NA
Lit
22.25
23.83
12.85
26.83
23.34
10.44
Percent Difference
SA/Lit
135%
82%
79%
107%
108%
109%
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
99%
100%
83%
99%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data
SA
40.5
19.9
7.7
32.3
26.2
10.6
CU
NA
NA
NA
NA
NA
NA
Literature
30.11
24.30
9.69
30.11
24.30
9.69
Percent Difference
SA/Lit
135%
82%
79%
107%
108%
109%
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


106%

-
77%
Predicted/CU


NA

-
NA
Predicted/
Original


83%

-
92%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
10.2
11.4

7.7
10.6
38.0%
Condenser Test
NA
NA

NA
NA
NA
Spreadsheet
8.08
8.93

8.08
8.93
10.5%
            Weighted Average  949.4%
                                             NA
                                                              262.6%
HVAC Data Sheet
Page 3 of 3
                                                                                                                             EPA Adsil Evaluation
                                                                                                                            York Technical College
                                                                                                                                        RTU-7

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
SFHCC20
J91 M72723
RTU-Gas
1991





YTC - Hood Center
RTU-8

18.2
460
0.72

1.80
460
0.70


Amps
Volts


Amps
Volts

Evaporator fan data (if applicable)
Full load Amps:               7.30
Nameplate Voltage:            460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition     _
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
                                                      Published EER:*                     9.7   Btu/W-hr  (CU Only)
                                                      Calculated EER:                      9.7   Btu/W-hr  (CU Only)
                                                      Nominal Capacity:                   18.41   tons
                                                      Age                                13   years
                                                      Coil Conditon                        15%   (% degraded)
                                                      Present Condition EER                7.8   Btu/W-hr
                                                      kW/ton                              1.54
                                                      Power supply:                      3-phase
                                                      Phase adjustment:                     1.73
                                                      Compressor quantity:                    2
                                                      Power supply:                      3-Phase
                                                      Phase adjustment:                     1.73
                                                      Fan quantity:                          2
                                                      Power supply:                      3-Phase
                                                      Phase adjustment:                     1.73
                                                      Fan quantity:                          1

                                                20.9   kW
                                                2.01   kW
                                                2.35   kW
                                               22.86  kW-Condensing side only
                                      14.8%   Performance Degradation
Amps
Volts
             Corrosion
             Some Loose
             Many Loose

             Clean Cu
             Corrosion
             Pitting
             Leaks
                            0.25
                            0.75
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
12.3
10.9
10.9
12.1
10.9
9.6
11.1
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
490
490
t Measurement
10
70
50
60
85
Circuit 1
120%
116%
10
76
11.80
20.7 9
19.1 2
F
F
%
%
Tons
F
kW
CU Capacity Estimates
76 F
89 F
63 in
71 n
31.1 sq-ft
20719
11.73 kg/sec
24.24 Tons
24.24 EER
7 0.96
3 0.25
298 K
305 K
Note: * Published EER value from 25-ton Trane model YCH300B4. ARI efficiency data not available for this unit
HVAC Data Sheet
Page 1 of 3
                                                                                                                                             EPA Adsil Evaluation
                                                                                                                                           York Technical College
                                                                                                                                                         RTU-8

-------
                            Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
SFHCC20
J91 M72723
RTU-Gas
1991





YTC - Hood Center
RTU-8

18.2
460
0.72

1.8
460
0.7


Amps
Volts


Amps
Volts

Evaporator fan data (if applicable)
Full load Amps:               7.3
Nameplate Voltage:            460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
it
X





1




1







X




X



                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
Amps               Power supply:
Volts               Phase adjustment:
                   Fan quantity:

            20.9    kW
            2.01    kW
            2.35    kW
           22.86   kW-Condensing side only
                                      0.0%   Performance Degradation
                                                      9.7
                                                      9.7
                                                      18.41
                                                       13
                                                                                          1.35
        Btu/W-hr   (CU Only)
        Btu/W-hr   (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
                                                    3-phase
                                                      1.73
                                                       2
                                                    3-Phase
                                                      1.73
                                                       2
3-Phase
  1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
Ft/Sec
12.3
12.5
12.5
12.3
12.9
13.1
12.6
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
488
488
t Measurement
10
70
50
65
85
Circuit 1 (only)
128%
129%
10
78
12.10
23.4 11
19.1 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
79 F
91 F
63 in
71 in
31.1 sq-ft
23483
13.30 kg/sec
25.36 Tons
20.56 EER
.1 0.99
7 0.40
299 K
306 K
HVAC Data Sheet
Page 2 of 3
                                                                                                    EPA Adsil Evaluation
                                                                                                  York Technical College
                                                                                                                RTU-8

-------
    YTC - Hood Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-8   Summary
                 9.7 BTU/W-h
              20719 CFM (Measured)
               18.41 tons
               10.00 tons
               31.06 sq-ft
                7.81 pre	8.86 post
Equipment age
13 years
Test Date
24- May

HVAC Service Assistant

OAT
76

Post Adsil Measurements
14-Jun

78

EWB
61


62

El
120%


128%

Cl
116%


129%

EER
14.3


15.0

kW
10.86


11.14

Physical Power and Capacity measurments
Cond Air, deg F
inlet
76


79

exhaust
89


91

Cond Air
AT(K)
7.2


6.7

kW
12


14.8

(kg/sec)
11.73


13.30


tons
24.24


25.36


EER
24.24


20.56

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
10.86
10.47
14.3
11.14
11.75
15.0
CU
12
24.24
24.24
14.8
25.36
20.56
Lit
9.11
9.03
11.89
9.35
9.11
11.70
Percent Difference
SA/Lit
119%
116%
120%
119%
129%
128%
CU/Lit
132%
269%
204%
158%
278%
176%
SS/Lit
100%
100%
81%
100%
100%
91%
Condensing Unit Summary - ARI Conditions
Test Data
SA
13.6
10.7
11.6
13.6
11.9
12.4
CU
15.0
24.7
19.8
18.0
25.6
17.0
Literature
11.39
9.20
9.69
11.39
9.20
9.69
Percent Difference
SA/Lit
119%
116%
120%
119%
129%
128%
CU/Lit
132%
269%
204%
158%
278%
1 76%
SA/CU
91%
43%
59%
75%
46%
73%
Predicted/SA


67%

-
63%
Predicted/CU


40%

-
46%
Predicted/
Original


81%

-
91%
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
14.3
15.0

11.6
12.4
6.7%
Condenser Test
24.24
20.56

19.76
17.04
-13.7%
Spreadsheet
7.81
8.86

7.81
8.86
13.5%
             Weighted Average   66.7%
                                                -137.5%
                                                               135.3%
HVAC Data Sheet
Page 3 of 3
                                                                                                                              EPA Adsil Evaluation
                                                                                                                            York Technical College
                                                                                                                                         RTU-8

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCH240B4
F501 422580
RTU-Gas
1991





YTC- Hood Center
RTU-10

17.4
460
0.96

3.00
460
0.70


Amps
Volts


Amps
Volts

Evaporator fan data (if applicable)
Full load Amps:               11.00    Amps
Nameplate Voltage:           460    Volts
Adjust FLA to RLA:            0.70
Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition     _
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:

                                               26.6   kW
                                               3.34   kW
                                               3.54   kW
                                               29.93   kW-Condensing side only
                                      3.0%   Performance Degradation
                                                                                        23.98
                                                                                          13
                                                                                         3%
                                                                                         8.6
                                                                                         1.40
                                                                                                Btu/W-hr
                                                                                                Btu/W-hr
                                                                                                tons
                                                                                                years
                                                                                                (% degraded)
                                                                                                Btu/W-hr
                                                                                                         (CU Only)
                                                                                                         (CU Only)
                                                                                       3-phase
                                                                                         1.73
                                                                                          2
                                                                                       3-Phase
                                                                                         1.73
                                                                                          2
                                                                                       3-Phase
                                                                                         1.73
                                                                                          1
             Corrosion
             Some Loose
             Many Loose

             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
Average
ft/sec
4.1
5.7
5.9
3.1
5.5
3.7
4.7
4.9
4.7
                            0.85
                            0.15
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
480
480
t Measurement
10
72
52
55
85
Circuit 1 (only)
66%
74%
10
77
13.20
38.8 9
40.6 1£
F
F
%
%
Tons
F
kW
CU Capacity Estimates
77 F
115 F
99 in
48 n
33.0 sq-ft
9306
5.27 kg/sec
31. 82 Tons
13.17 EER
4 0.51
.6 1.00
298 K
319 K
HVAC Data Sheet
Page 1 of 3
                                                                                                                                            EPA Adsil Evaluation
                                                                                                                                           York Technical College
                                                                                                                                                       RTU-10

-------
                            Post-Adsil HVAC  Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCH240B4
F501 422580
RTU-Gas
1991




YTC- Hood Center
RTU-10
17.4
460
0.96
3
460
0.7

Amps
Volts
Amps
Volts
Evaporator fan data (if applicable)
Full load Amps:                11
Nameplate Voltage:            460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition      	
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                                                       Published EER:
                                                       Calculated EER:
                                                       Nominal Capacity:
                                                       Age
                                                       Coil Conditon
                                                       Present Condition EER
                                                       kWrton
                                                       Power supply:
                                                       Phase adjustment:
                                                       Compressor quantity:
                                                       Power supply:
                                                       Phase adjustment:
                                                       Fan quantity:
Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:

            26.6   kW
            3.34   kW
            3.54   kW
            29.93   kW - Condensing side only
  0.0%    Performance Degradation
                                                       9.6
                                                       9.6
                                                      23.98
                                                        13
                                                     3-phase
                                                       1.73
                                                        2
                                                     3-Phase
                                                       1.73
                                                        2
3-Phase
  1.73
   1
         Btu/W-hr  (CD Only)
         Btu/W-hr  (CD Only)
         tons
         years
         (% degraded)
         Btu/W-hr
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
Average
Ft/Sec
15.2
12.5
15.2
14.8
14.6
12.5
13.3
12.3
13.80
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
485
483
t Measurement





Circuit 1 (only)





34.7 16.7 0.99
32.3 7.35 0.47
F
F
%
%
Tons
F
kW
CU Capacity Estimates
78 F 299 K
87 F 304 K
99 in
48 n
33.0 sq-ft
27324
15.47 kg/sec
22. 13 Tons
11.04 EER
HVAC Data Sheet
Page 2 of 3
                                                                                                           EPA Adsil Evaluation
                                                                                                          York Technical College
                                                                                                                      RTU-10

-------
    YTC- Hood Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-10  Summary
                 9.6 BTU/W-h
               9306 CFM (Measured)
               23.98 tons
               10.00 tons
               33.00 sq-ft
               8.59 pre	8.82 post
Equipment age
13 years
Test Date
24- May

HVAC Service Assistant

OAT
77

Post Adsil Measurements
14-Jun

NA

EWB
60

El
66%

Cl
74%

EER
7.1

Could not douplicate pre-test conditions
NA

NA

NA

NA

kW
15.83


NA

Physical Power and Capacity measurments
Cond Air, deg F
inlet
77


78

exhaust
115


87

Cond Air
AT(K)
21.1


5.0

kW
29


24.05

(kg/sec)
5.27


15.47


tons
31.82


22.13


EER
13.17


11.04

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
15.83
8.65
7.1
NA
NA
NA
CU
29
31.82
13.17
24.05
22.13
11.04
Lit
12.97
11.69
10.82
12.50
11.88
11.41
Percent Difference
SA/Lit
122%
74%
66%
NA
NA
NA
CU/Lit
224%
272%
122%
192%
186%
97%
SS/Lit
100%
100%
89%
100%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data
SA
36.5
17.7
6.4
NA
NA
NA
CU
66.9
65.3
11.7
57.5
44.7
9.3
Literature
29.90
23.98
9.62
29.90
23.98
9.62
Percent Difference
SA/Lit
122%
74%
66%
NA
NA
NA
CU/Lit
224%
272%
122%
192%
186%
97%
SA/CU
55%
27%
54%
NA
NA
NA
Predicted/SA


135%

-
NA
Predicted/CU


73%

-
92%
Predicted/
Original


89%

-
92%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
7.1
NA

6.4
NA
NA
Condenser Test
13.17
11.04

11.72
9.32
-20.5%
Spreadsheet
8.59
8.82

8.59
8.82
2.7%
            Weighted Average
                                NA
                                                -204.8%
                                                               27.1%
HVAC Data Sheet
Page 3 of 3
                                                                                                                             EPA Adsil Evaluation
                                                                                                                            York Technical College
                                                                                                                                        RTU-10

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
NA
558CPX048000
NA
RTU-Gas
2000
YTC Bid D
RTU-1

15.7 Ar
208 Vc
0.85
Condensing Fan Data
Full load Amps:              1.90
Nameplate Voltage:           208
Adjust FLA to RLA:            0.70

Evaporator fan data (If applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coll Condlton
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                         Power supply:
                         Phase adjustment:
                         Fan quantity:
                         Power supply:
                         Phase adjustment:
                         Fan quantity:

                   4.8   kW
                   0.28   kW
                   0.00   kW
                   5.08   kW-Condensing side only
         21.4%  Performance Degradation
                                                             NA
                                                             9.5
                                                            4.00
                                                             4
                                                            21%
                                                             7.8
                                                            1.54
                                                            Btu/W-hr  (CU Only)
                                                            Btu/W-hr  (CU Only)
                                                            tons
                                                            years
                                                            (% degraded)
                                                            Btu/W-hr
Amps
Volts
Amps
Volts
                                                           3-phase
                                                            1.73
                                                             1
1-Phase
   1
   1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
0.8
CU Fan CFM Calculation
Measurement
Number
1
2
3
Average
ft/sec


-

FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
206
203
t Measurment
10





75%
83%
4
88
5.10
17.1 3
18.7 2
F
F
%
%
Tons
F
kW
5 0.98
1 0.56

CU Capacity Estimates
88 F
101 F
72 in
37 in
18.5sq-ft
NA
NA kg/sec
NA Tons
NA EER
HVAC Data Sheet
Page 1 of 3
                                                                                                    EPA Adsil Evaluation
                                                                                                  York Technical College
                                                                                                               RTU-1

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
NA

558CPX048000
NA
RTU-Gas
2000
YTC Bid D
RTU-1
15.7
208
0.85




Ar
Vc
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.9
208
0.7
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:             0

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                         Power supply:
                         Phase adjustment:
                         Fan quantity:

                   4.8   kW
                   0.28   kW
                   0.00   kW
                   5.08   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                             NA
                                                             9.5
                                                            4.00
                                                             4
                                                             0%
                                                             9.5
                                                            1.27
                                                                                              Btu/W-hr  (CU Only)
                                                                                              Btu/W-hr  (CU Only)
                                                                                              tons
                                                                                              years
                                                                                              (% degraded)
                                                                                              Btu/W-hr
Amps
Volts
                                   Amps
                                   Volts
                                                          3-phase
                                                            1.73
                                                             1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
Average
ft/sec
NA
NA
NA
NA
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
NA
NA
t Measurment
10
NA
NA
NA
NA

101%
90%
4
85
4.30
NA N
NA N
F
F
%
%
Tons
F
kW
A NA
A NA

CU Capacity Estimates
NAF
NAF
72 in
37 in
18.5sq-ft
NA
NA kg/sec
NA Tons
NAEER
HVAC Data Sheet
Page 2 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                       York Technical College
                                                                                                                    RTU-1

-------
                YTC Bid D   RTU-1 Summary
    EER at ARI Conditions
    Condensing unit CFM                           NA
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
  9.5 BTU/W-h
     CFM (Measured)
 4.00 tons
 4.00 tons
18.50 sq-ft
 7.79 pre	9.45 post
Equipment age
4 years
Test Date
24-May

HVAC Service Assistant

OAT
88

Post Adsil Measurements
16-Jun

85

EWB
61


61

El
75%


101%

Cl
83%


90%

EER
7.1


9.5

kW
5.10


4.30

Physical Power and Capacity measurments
Cond Air
inlet
88


NA

deg F
exhaust
101


NA

Cond Air
AT(K)
7.2


NA

kW
5.6


NA

(kg/sec)
NA


NA


tons
NA


NA


EER
NA


NA

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
5.10
NA
7.1
4.30
NA
9.5
CU
5.6
NA
NA
NA
NA
NA
Lit
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
NA
NA
NA
NA
NA
NA
Condensing Unit Summary - ARI Conditions
Test Data
SA
NA
NA
NA
NA
NA
NA
CU
NA
NA
NA
NA
NA
NA
Literature
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


NA


NA
Predicted/CU


NA


NA
Predicted/
Original


NA


NA
                                     EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
7.1
9.5
7.1
9.5
34.7%
Condenser Test
NA
NA
NA
NA
NA
Spreadsheet
7.79
9.45
7.79
9.45
21.4%
             Weighted Average    138.7%
                                                NA
                                                                  85.6%
HVAC Data Sheet
Page 3 of 3
                                                                                                               EPA Adsil Evaluation
                                                                                                             York Technical College
                                                                                                                          RTU-1

-------
                             Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCS060A4EMAOXD
236101276L
RTU-Gas
2002
Monroe Aquatic Center
RTU-16
9.5 Amps
460 Volts
0.86
1.20 Amps
460 Volts
0.70
Evaporator fan data (if applicable)
Full load Amps:               3.20
Nameplate Voltage:            460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition      	
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                                                       Published EER:
                                                       Calculated EER:
                                                       Nominal Capacity:
                                                       Age
                                                       Coil Conditon
                                                       Present Condition EER
                                                       kWrton
                                                       Power supply:
                                                       Phase adjustment:
                                                       Compressor quantity:
                                                       Power supply:
                                                       Phase adjustment:
                                                       Fan quantity:
Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:

             6.5    kW
            0.39    kW
            1.03    kW
            6.89    kW - Condensing side only
  0.1%    Performance Degradation
                                                       9.1
                                                       9.1
                                                       5.21
                                                        2
                                                       0%
                                                       9.3
                                                       1.30
                                                     3-phase
                                                       1.73
                                                        1
                                                     1-Phase
                                                        1
                                                        1
3-Phase
  1.73
   1
         Btu/W-hr  (CD Only)
         Btu/W-hr  (CD Only)
         tons
         years
         (% degraded)
         Btu/W-hr
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
ft/sec
10.7
10.9
10.8
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
480
480
t Measurement
10
72
52
50
85

89%
89%
5
96
6.00
11.8 5.6 0.99
8.6 1.5 0.37
F
F
%
%
Tons
F
kW
CU Capacity Estimates
92 F 306 K
114 F 319 K
47 in
28 n
9.1 sq-ft
5922
3.35 kg/sec
11. 72 Tons
19.82 EER
HVAC Data Sheet
Page 1 of 3
                                                                                                           EPA Adsil Evaluation
                                                                                                         Monroe Aquatics Center
                                                                                                                      RTU-16

-------
                          Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCS060A4EMAOXD
236101276L
RTU-Gas
2002
Monroe Aquatic Center
RTU-16
    9.5    Amps
    460    Volts
    1.2
    460
    0.7
Evaporator fan data (If applicable)
Full load Amps:               3.2
Nameplate Voltage:            460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coll Condlton
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                             Power supply:
                             Phase adjustment:
                             Fan quantity:

                       6.5   kW
                       0.39   kW
                       1.03   kW
                       6.89   kW-Condensing side only
             0.0%  Performance Degradation
                                                     9.1
                                                     9.1
                                                     5.21
                                                      2
                                                     0%
                                                     9.3
                                                     1.30
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
Amps
Volts
Amps
Volts
                                                   3-phase
                                                     1.73
                                                      1
1-Phase
   1
   1
                                                   3-Phase
                                                     1.73
                                                      1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
Average
Ft/Sec
10.7
11.1
12.7
11.5
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
487
485
t Measurement
10
72
52
50
85

94%
90%
5
80
5.80
10.5 4
7.2 0.
F
F
%
%
Tons
F
kW
CU Capacity Estimates
78 F
100 F
47 in
28 in
9.1 sq-ft
6306
3.57 kg/sec
12. 48 Tons
25.74 EER
9 0.96
92 0.26
299 K
311 K
HVAC Data Sheet
Page 2 of 3
                                                                                                       EPA Adsil Evaluation
                                                                                                     Monroe Aquatics Center
                                                                                                                  RTU-16

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-16  Summary
                9.1  BTU/W-h
               5922 CFM (Measured)
               5.21  tons
               5.00 tons
               9.14 sq-ft
               9.25 pre	9.26 post
Equipment age
2 years
Test Date
24- May

HVAC Service Assistant

OAT
96

Post Adsil Measurements
14-Jun

80

EWB
60


60

El
89%


94%

Cl
89%


90%

EER
7.3


10.1

kW
6.25


6.04

Physical Power and Capacity measurments
Cond Air, deg F
inlet
92


78

exhaust
114


100

Cond Air
AT(K)
12.2


12.2

kW
7.1


5.82

(kg/sec)
3.35


3.57


tons
11.72


12.48


EER
19.82


25.74

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
6.25
4.21
7.3
6.04
4.68
10.1
CU
7.1
11.72
19.82
5.82
12.48
25.74
Lit
6.86
4.73
8.19
5.76
5.20
10.70
Percent Difference
SA/Lit
91%
89%
89%
105%
90%
94%
CU/Lit
1 04%
248%
242%
101%
240%
241 %
SS/Lit
100%
100%
101%
100%
100%
102%
Condensing Unit Summary - ARI Conditions
Test Data
SA
6.3
4.6
8.1
7.2
4.7
8.6
CU
7.1
12.9
22.1
6.9
12.5
21.9
Literature
6.86
5.21
9.11
6.86
5.21
9.11
Percent Difference
SA/Lit
91%
89%
89%
105%
90%
94%
CU/Lit
104%
248%
242%
101%
240%
241 %
SA/CU
88%
36%
37%
104%
37%
39%
Predicted/SA


114%

-
108%
Predicted/CU


42%

-
42%
Predicted/
Original


101%

-
102%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
7.3
10.1

8.1
8.6
5.6%
Condenser Test
19.82
25.74

22.06
21.93
-0.6%
Spreadsheet
9.25
9.26

9.25
9.26
0.1%
            Weighted Average   28.1%
                                                  -3.0%
                                                                0.5%
HVAC Data Sheet
Page 3 of 3
                                                                                                                             EPA Adsil Evaluation
                                                                                                                           Monroe Aquatics Center
                                                                                                                                       RTU-16

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCS090A4ELAO
236101222L
RTU-Gas
2002
Monroe Aquatic Center
RTU-15
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coll Condlton
Present Condition EER
kW/ton
    13.6     Amps              Power supply:
    460     Volts              Phase adjustment:
    0.75                       Compressor quantity:
    2.50     Amps              Power supply:
    460     Volts              Phase adjustment:
    0.70                       Fan quantity:
Evaporator fan data (If applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coll Assessment
Overall Unit Condition     	
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
            Amps              Power supply:
            Volts              Phase adjustment:
                              Fan quantity:

                        8.1    kW
                       0.81   kW
                       0.00   kW
                       8.92   kW-Condensing side only
              0.1%   Performance Degradation
10.0    Btu/W-hr  (CUOnly)
10.0    Btu/W-hr  (CUOnly)
7.44    tons
 2     years
0%    (% degraded)
10.2    Btu/W-hr
1.18
                                  3-phase
                                   1.73
                                     1
                                  1-Phase
                                     1
                                     1
                                  3-Phase
                                   1.73
                                     1
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
ft/sec
7.6
10.7
9.2
    0.02
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
488
488
t Measurement
10
72
52
50
85

105%
103%
7.5
94
8.80
15.9 1.9 0.25
13.8 6.6 0.99
F
F
%
Tons
F
kW
CU Capacity Estimates
92 F 306 K
112 F 318 K
70 in
36 in
17.5 sq-ft
9608
5.44 kg/sec
17.29 Tons
24.41 EER
HVAC Data Sheet
Page 1 of 3
                                                                                                     EPA Adsil Evaluation
                                                                                                  Monroe Aquatics Center
                                                                                                                RTU-15

-------
                          Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Trane
YCS090A4ELAO
236101222L
RTU-Gas
2002
Monroe Aquatic Center
RTU-15
    13.6    Amps
    460    Volts
    0.75
    2.5    Amps
    460    Volts
    0.7
Evaporator fan data (If applicable)
Full load Amps:               0
Nameplate Voltage:            0
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coll Condlton
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                             Power supply:
                             Phase adjustment:
                             Fan quantity:

                       8.1   kW
                       0.81   kW
                       0.00   kW
                       8.92   kW-Condensing side only
             0.0%  Performance Degradation
Amps
Volts
  10.0   Btu/W-hr  (CUOnly)
  10.0   Btu/W-hr  (CUOnly)
  7.44   tons
   2    years
  0%    (% degraded)
  10.2   Btu/W-hr
  1.18
3-phase
  1.73
   1
1-Phase
   1
   1
3-Phase
  1.73
   1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
Average
ft/sec
8.2
8.6
12.3
9.7
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
487
484
t Measurement
10
72
52
50
85

109%
104%
7.5
79
8.70
11.6 5
13.1 2
F
F
%
%
Tons
F
kW
CU Capacity Estimates
77 F
96 F
70 in
36 in
17.5sq-ft
10185
5.77 kg/sec
17.42 Tons
27.86 EER
2 0.93
3 0.36
298 K
309 K
HVAC Data Sheet
Page 2 of 3
                                                                                                       EPA Adsil Evaluation
                                                                                                     Monroe Aquatics Center
                                                                                                                  RTU-15

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER  =
RTU-15  Summary
               10.0 BTU/W-h
               9608 CFM (Measured)
               7.44 tons
               7.50 tons
               17.50 sq-ft
               10.19 pre	10.21 post
Equipment age
2 years
Test Date
24- May

HVAC Service Assistant

OAT
94

Post Adsil Measurements
14-Jun

79

EWB
60


60

El
105%


109%

Cl
103%


1 04%

EER
9.6


12.9

kW
8.72


8.63

Physical Power and Capacity measurments
Cond Air, deg F
inlet
92


77

exhaust
112


96

Cond Air
AT(K)
11.1


10.6

kW
8.5


7.5

(kg/sec)
5.44


5.77


tons
17.29


17.42


EER
24.41


27.86

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
8.72
6.98
9.6
8.63
7.69
12.9
CU
8.5
17.29
24.41
7.5
17.42
27.86
Lit
8.73
6.78
9.19
7.39
7.40
11.87
Percent Difference
SA/Lit
100%
103%
105%
117%
1 04%
109%
CU/Lit
97%
255%
266%
101%
235%
235%
SS/Lit
100%
100%
102%
100%
100%
102%
Condensing Unit Summary - ARI Conditions
Test Data
SA
8.9
7.7
10.5
10.4
7.7
10.9
CU
8.7
19.0
26.6
9.0
17.5
23.5
Literature
8.91
7.44
10.02
8.91
7.44
10.02
Percent Difference
SA/Lit
100%
103%
105%
117%
104%
109%
CU/Lit
97%
255%
266%
101%
235%
235%
SA/CU
103%
40%
40%
115%
44%
46%
Predicted/SA


97%

-
93%
Predicted/CU


38%

-
43%
Predicted/
Original


102%

-
102%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
9.6
12.9

10.5
10.9
3.8%
Condenser Test
24.41
27.86

26.63
23.52
-11.6%
Spreadsheet
10.19
10.21

10.19
10.21
0.1%
            Weighted Average  28.6%
                                                 -87.3%
                                                                0.8%
HVAC Data Sheet
Page 3 of 3
                                                                                                                             EPA Adsil Evaluation
                                                                                                                          Monroe Aquatics Center
                                                                                                                                       RTU-15

-------
                             Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D2CG240N24046FDE
SNFHM080298
RTU-Gas
1997
Monroe Aquatic Center
RTU-13
    9.6     Amps
    460     Volts
    0.68
    2.10     Amps
    460     Volts
    0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
it

X




0.7
0.3



0.5
0.1

0.5
0
0
0

X




X



CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
6.1
6.2
4.1
7.6
5.3
4.3
5.6
                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coil Conditon
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                              Power supply:
                              Phase adjustment:
                              Fan quantity:

                        20.8   kW
                        2.34   kW
                        0.00   kW
                       23.12   kW-Condensing side only
                                      4.7%   Performance Degradation
  10.7
  10.7
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
 20.71   tons
   7
  5%
  10.0
  1.20
years
(% degraded)
Btu/W-hr
Amps
Volts
3-phase
  1.73
   4
3-Phase
 1.73
   2
3-Phase
 1.73
   1
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Coil Number
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
486
484
t Measurement
10
72
52
50
85

85%
94%
20
92
30.00
39.3 19 1
39.6 8.2 0.43
Measured circuit 1
F (compressors 1 &2)
F All compressors were
% running during the
% test.
nput capacty and
power projections
multiplied by 2
Tons
F
kW
CU Capacity Estimates
92 F 306 K
128.5 F 327 K
74 in
29 in
2
29.8 sq-ft
10015
5.67 kg/sec
32.90 Tons
14.51 EER
HVAC Data Sheet
Page 1 of 3
                                                                                                               EPA Adsil Evaluation
                                                                                                             Monroe Aquatics Center
                                                                                                                          RTU-13

-------
                           Post-Ad si I HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                       York
                       D2CG240N24046FDE
                       SNFHM080298
                       RTU-Gas
                       1997
                       Monroe Aquatic Center
                       RTU-13
                         Published EER:
                         Calculated EER:
                         Nominal Capacity:
                         Age
                         Coil Conditon
                         Present Condition EER
                         kW/ton
  10.7
  10.7
 20.71
   7
  0%
  10.4
  1.15
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
                           9.6    Amps             Power supply:
                           460    Volts              Phase adjustment:
                           0.68                      Compressor quantity:
2.1
460
0.7
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1





0
0

0
0
0

X




X



                                  Amps             Power supply:
                                  Volts              Phase adjustment:
                                                    Fan quantity:
       Amps             Power supply:
       Volts              Phase adjustment:
                         Fan quantity:

                   20.8   kW
                   2.34   kW
                   0.00   kW
                   23.12  kW - Condensing side only
                                     0.0%   Performance Degradation
                                                          3-phase
                                                            1.73
                                                             4
3-Phase
  1.73
   2
                                                                                      3-Phase
                                                                                       1.73
                                                                                         1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
11.5
11.7
10.5
10
10.4
9
10.5
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps
1
2
3



Delta Measurement
Phase Volts Amps
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
486 23.3
490 23.4
t Measurement
10
72 F
52 F
50%
85%

1 09%
1 06%
20 Tons
93 F
NAkW
CU Capacity Estimates
87 F
103 F
74 in
29 in
29.8 sq-ft
18807
10.65 kg/sec
27.08 Tons
21. 52 EER
kW PF



kW PF
3.9 0.37
11.2 0.98
Measured circuit 1
(compressors 1&2)
Compressors 38,4
shut off during
test.
I nput capacity and
power projections
multiplied by 2
304 K
313 K
HVAC Data Sheet
Page 2 of 3
                                                                                                                                   EPA Adsil Evaluation
                                                                                                                                 Monroe Aquatics Center
                                                                                                                                              RTU-13

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-13 Summary
               10.7 BTU/W-h
             10015 CFM (Measured)
              20.71 tons
              20.00 tons
              29.81 sq-ft
               9.98 pre	10.44 post
Equipment age
7 years
Test Date
27-May

HVAC Service Assistant

OAT
92

Post Adsil Measurements
17-Jun

93

EWB
60


60

El
85%


109%

Cl
94%


106%

EER
8.5


10.7

kW
31.07


NA

Physical Power and Capacity measurments
Cond Air, deg F
inlet
92


87

exhaust
128.5


103

Cond Air
AT(K)
20.3


8.9

kW
27.2


15.1

(kg/sec)
5.67


10.65


tons
32.90


27.08


EER
14.51


21.52

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
31.07
17.22
8.5
NA
19.34
10.7
CU
27.2
32.90
14.51
15.1
27.08
21.52
Lit
22.10
18.32
9.95
22.21
18.24
9.86
Percent Difference
SA/Lit
141%
94%
85%
NA
106%
109%
CU/Lit
123%
180%
146%
68%
148%
218%
SS/Lit
99%
100%
94%
99%
100%
98%
Condensing Unit Summary - ARI Conditions
Test Data
SA
32.7
19.5
9.1
NA
22.0
11.6
CU
28.7
37.2
15.6
15.8
30.7
23.3
Literature
23.29
20.71
10.67
23.29
20.71
10.67
Percent Difference
SA/Lit
141%
94%
85%
NA
106%
109%
CU/Lit
123%
180%
146%
68%
148%
218%
SA/CU
114%
52%
58%
NA
71%
50%
Predicted/SA


110%

-
86%
Predicted/CU


64%

-
43%
Predicted/
Original


94%

-
98%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
8.5
10.7

9.1
11.6
28.2%
Condenser Test
14.51
21.52

15.57
23.30
49.7%
Spreadsheet
9.98
10.44

9.98
10.44
4.6%
            Weighted Average  564.7%
                                                993.1%
                                                               91.3%
HVAC Data Sheet
Page 3 of 3
                                                                                                                            EPA Adsil Evaluation
                                                                                                                          Monroe Aquatics Center
                                                                                                                                       RTU-13

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
York
D3CG090N1304GG
NGFM090088
RTU-Gas
1997
Monroe Aquatic Center
RTU-10
7.1 Amps
460 Volts
0.66
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.30
460
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
0.9
0.1




1




0.9
0.1


0
0
0

X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    7.4    kW
                   0.84   kW
                   0.00   kW
                   8.25   kW - Condensing side only
                                     0.52%  Performance Degradation
                                                            11.1
                                                            11.1
                                                            7.63
                                                              7
                                                             1%
                                                            10.7
                                                            1.12
                                         Btu/W-hr  (CU Only)
                                         Btu/W-hr  (CU Only)
                                         tons
                                         years
                                         (% degraded)
                                         Btu/W-hr
                                  Amps
                                  Volts
                                   Amps
                                   Volts
                                                           3-phase
                                                            1.73
                                                              2
1-Phase
   1
   2
                                 3-Phase
                                   1.73
                                    1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
6.2
5.3
8
11.7
11.5
11.7
9.1
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3
Delta Measurement
Phase
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency



Volts
484
487
t Measurement
10
74
54
42
85
Circuit 1
90%
99%
3.5
85
4.50






Amps kW PF
16.2 3
14.2 6
F
F
%
%
1 0.4
6 0.94

Circuit 2


Tons
F
kW
CU Capacity Estimates
84.5 F
105. 5 F
41 in
29 in
16.5sq-ft
8984
5.09 kg/sec
16.98 Tons
21. 00 EER
03%
03%
3.5 Tons
86 F
4.20 kW
302 K
314 K
HVAC Data Sheet
Page 1 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                      Monroe Aquatics Center
                                                                                                                    RTU-10

-------
                            Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D3CG090N1304GG
NGFM090088
RTU-Gas
1997
Monroe Aquatic Center
RTU-10

7.1 Amps
460 Volts
0.656

1.3 Amps
460 Volts
0.7
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:             0
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
it
X





1





0
0

0
0
0

X




X



                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
Amps              Power supply:
Volts              Phase adjustment:
                  Fan quantity:

            7.4   kW
            0.84   kW
            0.00   kW
            8.25   kW-Condensing side only
                                      0.0%   Performance Degradation
                                                      11.1
                                                      11.1
                                                      7.63
                                                       7
                                                      0%
                                                      10.8
                                                      1.11
        Btu/W-hr   (CU Only)
        Btu/W-hr   (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
                                                    3-phase
                                                      1.73
                                                       2
                                                    1-Phase
                                                       1
                                                       2
3-Phase
 1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
11.1
11.1
9.6
12.5
12.5
12.5
11.6
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
481
485
t Measurement
10
74
54
42
85
Circuit 1
108%
110%
3.5
89
4.30
15.7
14 6.
F
F
%
%
3 0.4
35 0.93

Circuit 2


Tons
F
kW
CU Capacity Estimates
89 F
106 F
41 in
29 in
16.5 sq-ft
11444
6.48 kg/sec
17.51 Tons
22.47 EER
06%
08%
3.5 Tons
87 F
4.30 kW
305 K
314 K
HVAC Data Sheet
Page 2 of 3
                                                                                                    EPA Adsil Evaluation
                                                                                                 Monroe Aquatics Center
                                                                                                               RTU-10

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER  =
RTU-10 Summary
               11.1 BTU/W-h
              8984 CFM (Measured)
               7.63 tons
               7.00 tons
              16.51 sq-ft
              10.72 pre	10.77 post
Equipment age
7 years
Test Date
13-May

HVAC Service Assistant

OAT
85

Post Adsil Measurements
17-Jun

89

EWB
59


59

El
97%


107%

Cl
101%


109%

EER
11.7


12.1

kW
9.48


9.37

Physical Power and Capacity measurments
Cond Air, deg F
inlet
84.5


89

exhaust
105.5


106

Cond Air
AT(K)
11.7


9.4

kW
9.7


9.35

(kg/sec)
5.09


6.48


tons
16.98


17.51


EER
21.00


22.47

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
9.48
7.32
11.7
9.37
7.72
12.1
CU
9.7
16.98
21.00
9.35
17.51
22.47
Lit
7.18
7.25
12.11
7.52
7.08
11.31
Percent Difference
SA/Lit
132%
101%
97%
125%
109%
107%
CU/Lit
135%
234%
173%
1 24%
247%
199%
SS/Lit
102%
102%
96%
102%
102%
97%
Condensing Unit Summary - ARI Conditions
Test Data
SA
10.7
7.6
10.7
10.1
8.2
11.9
CU
10.9
17.5
19.3
10.0
18.5
22.1
Literature
8.08
7.49
11.12
8.08
7.49
11.12
Percent Difference
SA/Lit
132%
101%
97%
125%
109%
107%
CU/Lit
135%
234%
173%
124%
247%
1 99%
SA/CU
98%
43%
56%
100%
44%
54%
Predicted/SA


100%

-
90%
Predicted/CU


56%

-
48%
Predicted/
Original


96%

-
97%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.7
12.1

10.7
11.9
10.9%
Condenser Test
21.00
22.47

19.25
22.05
14.5%
Spreadsheet
10.72
10.77

10.72
10.77
0.5%
            Weighted Average   76.2%
                                                                3.5%
HVAC Data Sheet
Page 3 of 3
                                                                                                                            EPA Adsil Evaluation
                                                                                                                         Monroe Aquatics Center
                                                                                                                                      RTU-10

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                       York
                       D4CG150N20046JSC
                       NBFM022912
                       RTU-Gas
                       1997
                       Monroe Aquatic Center
                       RTU-9
                            460
                           0.78
                            0.70
Evaporator fan data (if applicable)
Full load Amps:               7.50
Nameplate Voltage:           460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coil Conditon
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:

                                               11.9    kW
                                               1.61    kW
                                               2.42    kW
                                               13.53   kW-Condensing side only
                                      9.2%    Performance Degradation
 10.5
 10.5
11.88
  7
 9%
 9.4
 1.28
Btu/W-hr
Btu/W-hr
tons
years
(% degraded)
Btu/W-hr
                                                                     (CU Only)
                                                                     (CU Only)
                                   Amps
                                   Volts
Amps
Volts
Amps
Volts
                                                    3-phase
                                                     1.73
                                                       2
                                                    1-Phase
                                                       1
                                                       2
                                                    3-Phase
                                                     1.73
                                                       1
             Corrosion
             Some Loose
             Many Loose

             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
Average
ft/sec
4.1
4.1
3.1
3.3
6.6
5.9
6.8
5.9
5.0
                            0.3
                            0.7
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
490
487
t Measurment
10
85
65
35
85
Circuit 1
73%
80%
6
88
7.70
26.9 1
27.8 4
F
F
%
%
3 1
6 0.34

Circuit 2


Tons
F
kW
CU Capacity Estimates
86 F
115 F
48 in
42 n
28.0 sq-ft
11424
6.47 kg/sec
29.81 Tons
20.33 EER
77%
80%
6 Tons
84 F
7.30 kW
303 K
319 K
HVAC Data Sheet
Page 1 of 3
                                                                                                                                           EPA Adsil Evaluation
                                                                                                                                         Monroe Aquatics Center
                                                                                                                                                       RTU-9

-------
                           Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                       York
                       D4CG150N20046JSC
                       NBFM022912
                       RTU-Gas
                       1997
                       Monroe Aquatic Center
                       RTU-9
                            460
                           0.78
                            0.7
Evaporator fan data (if applicable)
Full load Amps:                7.5
Nameplate Voltage:            460
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coil Conditon
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:

                                               11.9    kW
                                               1.61    kW
                                               2.42    kW
                                               13.53   kW-Condensing side only
                                      0.1%    Performance Degradation
 10.5
 10.5
11.88
  7
 0%
 10.2
 1.17
Btu/W-hr
Btu/W-hr
tons
years
(% degraded)
Btu/W-hr
                                                                     (CU Only)
                                                                     (CU Only)
                                   Amps
                                   Volts
Amps
Volts
Amps
Volts
                                                    3-phase
                                                     1.73
                                                       2
                                                    1-Phase
                                                       1
                                                       2
                                                    3-Phase
                                                     1.73
                                                       1
             Corrosion
             Some Loose
             Many Loose

             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
Average
ft/sec
10
9.8
8.4
8.8
9.8
9.2
8.8
6.8
9.0
                            0.98
                            0.02
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
482
484
t Measurment
10
87
67
45
85
Circuit 1
85%
78%
6
87
6.70
26.8 4
25.5 1;
F
F
%
%
6 0.35
.4 1.00

Circuit 2


Tons
F
kW
CU Capacity Estimates
87 F
110 F
48 in
42 n
28.0 sq-ft
15036
8.52 kg/sec
31. 12 Tons
21.97 EER
88%
84%
6 Tons
85 F
6.90 kW
304 K
316 K
HVAC Data Sheet
Page 2 of 3
                                                                                                                                           EPA Adsil Evaluation
                                                                                                                                         Monroe Aquatics Center
                                                                                                                                                       RTU-9

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER  =
RTU-9 Summary
              10.5 BTU/W-h
            11424 CFM (Measured)
             11.88 tons
             12.00 tons
             28.00 sq-ft
              9.39 pre	10.22 post
Equipment age
7 years
Test Date
13-May

HVAC Service Assistant

OAT
88

Post Adsil Measurements
16-Jun

87

EWB
65


70

El
75%


87%

Cl
80%


81%

EER
8.5


11.5

kW
14.85


13.46

Physical Power and Capacity measurments
Cond Air, deg F
inlet
86


87

exhaust
115


110

Cond Air
AT(K)
16.1


12.8

kW
17.6


17

(kg/sec)
6.47


8.52


tons
29.81


31.12


EER
20.33


21.97

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
14.85
9.75
8.5
13.46
10.67
11.5
CU
17.6
29.81
20.33
17.0
31.12
21.97
Lit
12.85
12.19
11.38
13.09
13.17
13.26
Percent Difference
SA/Lit
116%
80%
75%
103%
81%
87%
CU/Lit
137%
245%
179%
130%
236%
166%
SS/Lit
100%
100%
89%
100%
100%
97%
Condensing Unit Summary - ARI Conditions
Test Data
SA
15.6
9.5
7.9
13.9
9.6
9.1
CU
18.5
29.1
18.8
17.6
28.1
17.5
Literature
13.52
11.88
10.54
13.52
11.88
10.54
Percent Difference
SA/Lit
116%
80%
75%
103%
81%
87%
CU/Lit
137%
245%
179%
130%
236%
1 66%
SA/CU
84%
33%
42%
79%
34%
52%
Predicted/SA


119%

-
103%
Predicted/CU


50%

-
54%
Predicted/
Original


89%

-
97%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
8.5
11.5

7.9
9.1
15.3%
Condenser Test
20.33
21.97

18.84
17.47
-7.3%
Spreadsheet
9.39
10.22

9.39
10.22
8.8%
            Weighted Average  184.0%
                                                 -87.2%
                                                              105.9%
HVAC Data Sheet
Page 3 of 3
                                                                                                                           EPA Adsil Evaluation
                                                                                                                        Monroe Aquatics Center
                                                                                                                                      RTU-9

-------
                             Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D2CG240N24046FDE
NGFM089948
RTU-Gas
1997
Monroe Aquatic Center
RTU-8
    9.6     Amps
    460     Volts
    0.68
    2.10     Amps
    460     Volts
    0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
it

X





0.5
0.5


0.25
0.1

0.75
0
0
0

X




X



                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coil Conditon
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                              Power supply:
                              Phase adjustment:
                              Fan quantity:

                        20.8   kW
                        2.34   kW
                        0.00   kW
                       23.12   kW-Condensing side only
                                      12.0%   Performance Degradation
  10.7
  10.7
 20.71
   7
  12%
  9.4
  1.28
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
Amps
Volts
3-phase
  1.73
   4
3-Phase
 1.73
   2
3-Phase
 1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
3.9
3.3
4.5
4.1
3.3
2.1
3.5
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Coil Number
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
487
487
t Measurement
10
82
62
15
85

84%
96%
20
97
26.80
41.3 8.2 0.41
41.4 20 0.99
Measured circuit 2
F (compressors 3&4)
F All compressors were
% running during the
% test.
nput capacty and
power projections
multiplied by 2
Tons
F
kW
CU Capacity Estimates
98 F 310 K
128.5 F 327 K
74 in
29 in
2
29.8 sq-ft
6319
3.58 kg/sec
17.34 Tons
7.38 EER
HVAC Data Sheet
Page 1 of 3
                                                                                                               EPA Adsil Evaluation
                                                                                                             Monroe Aquatics Center
                                                                                                                           RTU-8

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D2CG240N24046FDE
NGFM089948
RTU-Gas
1997
Monroe Aquatic Center
RTU-8
9.6 Amps
460 Volts
0.68
2.1 Amps
460 Volts
0.7
Evaporator fan data (if applicable)
Full load Amps:               0
Nameplate Voltage:            0
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1

0.25



0
0

0
0
0

X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
Amps             Power supply:
Volts              Phase adjustment:
                  Fan quantity:

            20.8   kW
            2.34   kW
            0.00   kW
           23.12  kW - Condensing side only
                                     2.5%   Performance Degradation
  10.7
  10.7
 20.71
   7
  3%
  10.2
  1.18
                                                           Btu/W-hr  (CU Only)
                                                           Btu/W-hr  (CU Only)
                                                           tons
                                                           years
                                                           (% degraded)
                                                           Btu/W-hr
3-phase
  1.73
   4
3-Phase
  1.73
   2
3-Phase
  1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
9.2
9.8
12.3
10.8
9.2
9.4
10.1
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
483
485
t Measurement
10
82
62
15
85

96%
94%
10
85
23.60
36.7 6
37 1"

4 0.36
.8 0.98

Measured circuit 2
F (compressors 38,4)
F All compressors were
% running during the
% test.

I nput capacity and
power projections
multiplied by 2
Tons
F
kW
CU Capacity Estimates
85 F
110. 5 F
74 in
29 in
29.8 sq-ft
18092
10.25 kg/sec
41. 52 Tons
20.59 EER
303 K
317 K
HVAC Data Sheet
Page 2 of 3
                                              EPA Adsil Evaluation
                                            Monroe Aquatics Center
                                                          RTU-8

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-8 Summary
              10.7 BTU/W-h
             6319 CFM (Measured)
             20.71 tons
             20.00 tons
             29.81 sq-ft
              9.35 pre	10.19 post
Equipment age
7 years
Test Date
27-May

HVAC Service Assistant

OAT
97

Post Adsil Measurements
17-Jun

85

EWB
55


55

El
84%


96%

Cl
96%


94%

EER
8.2


10.5

kW
27.75


24.44

Physical Power and Capacity measurments
Cond Air, deg F
inlet
98


85

exhaust
128.5


110.5

Cond Air
AT(K)
16.9


14.2

kW
28.2


24.2

(kg/sec)
3.58


10.25


tons
17.34


41.52


EER
7.38


20.59

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
27.75
17.22
8.2
24.44
17.72
10.5
CU
28.2
17.34
7.38
24.2
41.52
20.59
Lit
22.10
17.94
9.74
20.78
18.86
10.89
Percent Difference
SA/Lit
126%
96%
84%
118%
94%
96%
CU/Lit
128%
97%
76%
116%
220%
189%
SS/Lit
99%
100%
88%
99%
100%
95%
Condensing Unit Summary - ARI Conditions
Test Data
SA
29.2
19.9
9.0
27.4
19.5
10.2
CU
29.7
20.0
8.1
27.1
45.6
20.2
Literature
23.29
20.71
10.67
23.29
20.71
10.67
Percent Difference
SA/Lit
126%
96%
84%
118%
94%
96%
CU/Lit
128%
97%
76%
116%
220%
1 89%
SA/CU
98%
99%
111%
101%
43%
51%
Predicted/SA


104%

-
91%
Predicted/CU


116%

-
46%
Predicted/
Original


88%

-
95%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
8.2
10.5

9.0
10.2
14.3%
Condenser Test
7.38
20.59

8.09
20.18
149.5%
Spreadsheet
9.35
10.19

9.35
10.19
9.0%
            Weighted Average  285.7%
                                               2989.8%
                                                              179.1%
HVAC Data Sheet
Page 3 of 3
                                                                                                                           EPA Adsil Evaluation
                                                                                                                         Monroe Aquatics Center
                                                                                                                                      RTU-8

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D7CG060N07946A
NGFM091009
RTU-Gas
1997
Monroe Aquatic Center
RTU-6
    8.0    Amps
    460    Volts
    0.87
    0.80    Amps
    460    Volts
    0.70
Evaporator fan data (if applicable)
Full load Amps:              3.30
Nameplate Voltage:           460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.75
0.25



0.75
0.25

0.25
0
0
0

X




X



                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coil Conditon
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                             Power supply:
                             Phase adjustment:
                             Fan quantity:

                       5.5   kW
                       0.26   kW
                       1.06   kW
                       5.80   kW - Condensing side only
                                     4.0%   Performance Degradation
  10.9
  10.9
  5.25
   7
  4%
  10.2
  1.18
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
Amps
Volts
3-phase
  1.73
   1
1-Phase
   1
   1
3-Phase
  1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
6.4
6.2
5.7
6.2
6.1
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
485
485
t Measurement
10
75
55
35
85

1 03%
98%
5
95
NA
11.6 0
10.75 5
F
F
%
%
Tons
F
kW
CU Capacity Estimates
95 F
114 F
74 in
29 in
14.9sq-ft
5477
3.10 kg/sec
9.36 Tons
19.05 EER
7 0.13
2 1.00
308 K
319 K
HVAC Data Sheet
Page 1 of 3
                                                                                                                                    EPA Adsil Evaluation
                                                                                                                                 Monroe Aquatics Center
                                                                                                                                               RTU-6

-------
                           Post-Ad si I HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D7CG060N07946A
NGFM091009
RTU-Gas
1997
Monroe Aquatic Center
RTU-6
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
10.9
10.9
5.25
 7
0%
10.6
1.14
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
     8     Amps             Power supply:
    460    Volts              Phase adjustment:
    0.87                      Compressor quantity:
    0.8    Amps             Power supply:
    460    Volts              Phase adjustment:
    0.7                      Fan quantity:
Evaporator fan data (if applicable)
Full load Amps:               3.3
Nameplate Voltage:           460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1





0
0

0
0
0

X




X



           Amps             Power supply:
           Volts              Phase adjustment:
                             Fan quantity:

                       5.5   kW
                       0.26   kW
                       1.06   kW
                       5.80   kW - Condensing side only
                                     0.0%   Performance Degradation
                                 3-phase
                                   1.73
                                    1
                                 1-Phase
                                    1
                                    1
                                 3-Phase
                                   1.73
                                    1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
7.2
7.4
7.5
7.6
7.425
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
483
485
t Measurement
10
75
55
35
85

99%
98%
5
88
6.00
11 0
11.7 5
F
F
%
%
Tons
F
kW
CU Capacity Estimates
87 F
108 F
74 in
29 in
14.9sq-ft
6639
3.76 kg/sec
12.55 Tons
25.96 EER
6 0.11
2 1.00
304 K
315 K
HVAC Data Sheet
Page 2 of 3
                                                                                                                                    EPA Adsil Evaluation
                                                                                                                                 Monroe Aquatics Center
                                                                                                                                               RTU-6

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-6 Summary
              10.9 BTU/W-h
             5477 CFM (Measured)
              5.25 tons
              5.00 tons
             14.90 sq-ft
             10.17 pre	10.56 post
Equipment age
7 years
Test Date
24- May

HVAC Service Assistant

OAT
95

Post Adsil Measurements
15-Jun

88

EWB
58


58

El
103%


99%

Cl
98%


98%

EER
11.0


11.6

kW
NA


6.30

Physical Power and Capacity measurments
Cond Air, deg F
inlet
95


87

exhaust
114


108

Cond Air
AT(K)
10.6


11.7

kW
5.9


5.8

(kg/sec)
3.10


3.76


tons
9.36


12.55


EER
19.05


25.96

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
NA
5.15
11.0
6.30
5.42
11.6
CU
5.9
9.36
19.05
5.8
12.55
25.96
Lit
5.90
5.25
10.68
5.65
5.53
11.74
Percent Difference
SA/Lit
NA
98%
103%
112%
98%
99%
CU/Lit
100%
178%
178%
103%
227%
221 %
SS/Lit
100%
100%
94%
100%
100%
97%
Condensing Unit Summary - ARI Conditions
Test Data
SA
NA
5.1
11.2
6.5
5.1
10.8
CU
5.8
9.4
19.4
6.0
11.9
24.0
Literature
5.80
5.25
10.86
5.80
5.25
10.86
Percent Difference
SA/Lit
NA
98%
103%
112%
98%
99%
CU/Lit
100%
178%
178%
103%
227%
221%
SA/CU
NA
55%
58%
109%
43%
45%
Predicted/SA


91%

-
95%
Predicted/CU


53%

-
42%
Predicted/
Original


94%

-
97%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.0
11.6

11.2
10.8
-3.9%
Condenser Test
19.05
25.96

19.36
24.02
24.0%
Spreadsheet
10.17
10.56

10.17
10.56
3.8%
            Weighted Average  -19.4%
                                                120.2%
                                                               19.2%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                                                EPA Adsil Evaluation
                                                                                                                                                              Monroe Aquatics Center
                                                                                                                                                                           RTU-6

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D7CG060N07946A
NGFM091011
RTU-Gas
1997
Monroe Aquatic Center
RTU-5
    8.0    Amps
    460    Volts
    0.87
    0.80    Amps
    460    Volts
    0.70
Evaporator fan data (if applicable)
Full load Amps:              3.30
Nameplate Voltage:           460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.75
0.25



0.75
0.25

0.25
0
0
0

X




X



                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coil Conditon
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                             Power supply:
                             Phase adjustment:
                             Fan quantity:

                       5.5   kW
                       0.26   kW
                       1.06   kW
                       5.80   kW - Condensing side only
                                     4.0%   Performance Degradation
  10.9
  10.9
  5.25
   7
  4%
  10.2
  1.18
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
Amps
Volts
3-phase
  1.73
   1
1-Phase
   1
   1
3-Phase
  1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
4.5
5.3
4.5
3.1
4.4
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
480
483
t Measurement
10
75
55
25
85

72%
68%
5
93
5.80
11.25 0
10.7 5
F
F
%
%
Tons
F
kW
CU Capacity Estimates
91 F
115 F
74 in
29 in
14.9sq-ft
3890
2.20 kg/sec
8.40 Tons
16.53 EER
9 0.17
2 1.00
306 K
319 K
HVAC Data Sheet
Page 1 of 3
                                                                                                            EPA Adsil Evaluation
                                                                                                          Monroe Aquatics Center
                                                                                                                        RTU-5

-------
                            Post-Adsil  HVAC  Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D7CG060N07946A
NGFM091011
RTU-Gas
1997
Monroe Aquatic Cenl
RTU-5
8 Amps
460 Volts
0.87
0.8 Amps
460 Volts
0.7
Evaporator fan data (if applicable)
Full load Amps:                3.3
Nameplate Voltage:             460
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition      	
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                                                       Published EER:
                                                       Calculated EER:
                                                       Nominal Capacity:
                                                       Age
                                                       Coil Conditon
                                                       Present Condition EER
                                                       kWrton
                                                       Power supply:
                                                       Phase adjustment:
                                                       Compressor quantity:
                                                       Power supply:
                                                       Phase adjustment:
                                                       Fan quantity:
Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:

             5.5    kW
            0.26    kW
            1.06    kW
            5.80    kW - Condensing side only
  0.0%    Performance Degradation
                                                       10.9
                                                       10.9
                                                       5.25
                                                        7
                                                       0%
                                                       10.6
                                                       1.14
                                                     3-phase
                                                       1.73
                                                        1
                                                     1-Phase
                                                        1
                                                        1
3-Phase
  1.73
   1
         Btu/W-hr  (CD Only)
         Btu/W-hr  (CD Only)
         tons
         years
         (% degraded)
         Btu/W-hr
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
6.1
6
5.7
6.1
6.0
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
485
489
t Measurement
10
68
48
50
85

82%
74%
5
84
5.50
10.5 0.3 0.07
10.3 5 1.00
F
F
%
%
Tons
F
kW
CU Capacity Estimates
84 F 302 K
101 F 311 K
74 in
29 n
14.9 sq-ft
5343
3.03 kg/sec
8. 17 Tons
18.51 EER
HVAC Data Sheet
Page 2 of 3
                                                                                                           EPA Adsil Evaluation
                                                                                                         Monroe Aquatics Center
                                                                                                                       RTU-5

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-5   Summary
                10.9 BTU/W-h
               3890 CFM (Measured)
                5.25 tons
                5.00 tons
               14.90 sq-ft
               10.17 pre	10.56 post
Equipment age
7 years
Test Date
24- May

HVAC Service Assistant

OAT
93

Post Adsil Measurements
15-Jun

84

EWB
55


57

El
72%


82%

Cl
68%


74%

EER
7.8


10.1

kW
6.09


6.09

Physical Power and Capacity measurments
Cond Air, deg F
inlet
91


84

exhaust
115


101

Cond Air
AT(K)
13.3


9.4

kW
6.1


5.3

(kg/sec)
2.20


3.03


tons
8.40


8.17


EER
16.53


18.51

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
6.09
3.62
7.8
6.09
4.21
10.1
CU
6.1
8.40
16.53
5.3
8.17
18.51
Lit
5.91
5.33
10.82
5.54
5.68
12.30
Percent Difference
SA/Lit
103%
68%
72%
110%
74%
82%
CU/Lit
103%
158%
153%
96%
1 44%
150%
SS/Lit
100%
100%
94%
100%
100%
97%
Condensing Unit Summary - ARI Conditions
Test Data
SA
6.0
3.6
7.8
6.4
3.9
8.9
CU
6.0
8.3
16.6
5.5
7.6
16.3
Literature
5.80
5.25
10.86
5.80
5.25
10.86
Percent Difference
SA/Lit
103%
68%
72%
110%
74%
82%
CU/Lit
103%
158%
153%
96%
1 44%
1 50%
SA/CU
100%
43%
47%
115%
51%
55%
Predicted/SA


130%

-
114%
Predicted/CU


61%

-
62%
Predicted/
Original


94%

-
97%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
7.8
10.1

7.8
8.9
13.9%
Condenser Test
16.53
18.51

16.59
16.34
-1.5%
Spreadsheet
10.17
10.56

10.17
10.56
3.8%
            Weighted Average  69.4%
                                                  -7.5%
                                                               19.2%
HVAC Data Sheet
Page 3 of 3
                                                                                                                             EPA Adsil Evaluation
                                                                                                                          Monroe Aquatics Center
                                                                                                                                        RTU-5

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D7CG060N07946A
NGFM091011
RTU-Gas
1997
Monroe Aquatic Center
RTU-4
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
10.9
10.9
5.25
 7
2%
10.4
1.16
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    8.0    Amps             Power supply:
    460    Volts              Phase adjustment:
    0.87                      Compressor quantity:
    0.80    Amps             Power supply:
    460    Volts              Phase adjustment:
    0.70                      Fan quantity:
Evaporator fan data (if applicable)
Full load Amps:               3.30
Nameplate Voltage:           460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

X




0.9
0.1



0.9
0.1

0.1
0
0
0

X




X



           Amps             Power supply:
           Volts              Phase adjustment:
                             Fan quantity:

                       5.5   kW
                       0.26   kW
                       1.06   kW
                       5.80   kW - Condensing side only
                                     1.7%   Performance Degradation
                                 3-phase
                                   1.73
                                    1
                                 1-Phase
                                    1
                                    1
                                 3-Phase
                                   1.73
                                    1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
4.9
6.8
5.5
5.5
5.675
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
480
480
t Measurment
10
68
48
50
85

79%
73%
5
90
5.70
10.5 5
10.8 0
F
F
%
%
Tons
F
kW
CU Capacity Estimates
90 F
105 F
74 in
29 in
14.9sq-ft
5074
2.87 kg/sec
6.85 Tons
14.68 EER
1 1
5 0.09
305 K
314 K
HVAC Data Sheet
Page 1 of 3
                                                                                                            EPA Adsil Evaluation
                                                                                                          Monroe Aquatics Center
                                                                                                                        RTU-4

-------
                           Post-Ad si I HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D7CG060N07946A
NGFM091011
RTU-Gas
1997
Monroe Aquatic Center
RTU-4
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coil Conditon
Present Condition EER
kW/ton
10.9
10.9
5.25
 7
0%
10.6
1.14
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
     8     Amps             Power supply:
    460    Volts              Phase adjustment:
    0.87                      Compressor quantity:
    0.8    Amps             Power supply:
    460    Volts              Phase adjustment:
    0.7                      Fan quantity:
Evaporator fan data (if applicable)
Full load Amps:                3.3
Nameplate Voltage:            460
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1





0
0

0
0
0

X




X



           Amps             Power supply:
           Volts              Phase adjustment:
                             Fan quantity:

                       5.5   kW
                       0.26   kW
                       1.06   kW
                       5.80   kW - Condensing side only
                                     0.0%   Performance Degradation
                                 3-phase
                                   1.73
                                    1
                                 1-Phase
                                    1
                                    1
                                 3-Phase
                                   1.73
                                    1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
7.0
7.0
7.2
7.2
7.1
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
484
486
t Measurment
10
68
48
50
85

85%
78%
5
85
5.70
10.7 0
10.5 5
F
F
%
%
Tons
F
kW
CU Capacity Estimates
86 F
104 F
74 in
29 in
14.9sq-ft
6349
3.60 kg/sec
10.28 Tons
22.44 EER
4 0.07
1 1.00
303 K
313 K
HVAC Data Sheet
Page 2 of 3
                                                                                                            EPA Adsil Evaluation
                                                                                                          Monroe Aquatics Center
                                                                                                                        RTU-4

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-4 Summary
              10.9 BTU/W-h
             5074 CFM (Measured)
              5.25 tons
              5.00 tons
             14.90 sq-ft
             10.39 pre	10.56 post
Equipment age
7 years
Test Date
24- May

HVAC Service Assistant

OAT
90

Post Adsil Measurements
15-Jun

85

EWB
57


57

El
79%


85%

Cl
73%


78%

EER
9.0


10.3

kW
5.99


5.99

Physical Power and Capacity measurments
Cond Air, deg F
inlet
90


86

exhaust
105


104

Cond Air
AT(K)
8.3


10.0

kW
5.6


5.5

(kg/sec)
2.87


3.60


tons
6.85


10.28


EER
14.68


22.44

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
5.99
3.98
9.0
5.99
4.40
10.3
CU
5.6
6.85
14.68
5.5
10.28
22.44
Lit
5.75
5.45
11.37
5.58
5.64
12.14
Percent Difference
SA/Lit
1 04%
73%
79%
107%
78%
85%
CU/Lit
97%
126%
129%
99%
182%
185%
SS/Lit
100%
100%
96%
100%
100%
97%
Condensing Unit Summary - ARI Conditions
Test Data
SA
6.0
3.8
8.6
6.2
4.1
9.2
CU
5.7
6.6
14.0
5.7
9.6
20.1
Literature
5.80
5.25
10.86
5.80
5.25
10.86
Percent Difference
SA/Lit
104%
73%
79%
107%
78%
85%
CU/Lit
97%
126%
129%
99%
1 82%
1 85%
SA/CU
107%
58%
61%
109%
43%
46%
Predicted/SA


121%

-
113%
Predicted/CU


74%

-
52%
Predicted/
Original


96%

-
97%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
9.0
10.3

8.6
9.2
7.6%
Condenser Test
14.68
22.44

14.03
20.07
43.1%
Spreadsheet
10.39
10.56

10.39
10.56
1.7%
            Weighted Average  38.0%
                                                215.5%
                                                                8.3%
HVAC Data Sheet
Page 3 of 3
                                                                                                                           EPA Adsil Evaluation
                                                                                                                        Monroe Aquatics Center
                                                                                                                                      RTU-4

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
York
D3CG090N1304GG
NGFM090091
RTU-Gas
1997
Monroe Aquatic Center
RTU-2
7.1 Amps
460 Volts
0.64
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.30
460
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
0.9
0.1




1





0.1


0
0
0

X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    7.2    kW
                   0.84   kW
                   0.00   kW
                   8.07   kW - Condensing side only
                                     0.52%  Performance Degradation
                                                            11.1
                                                            11.1
                                                            7.49
                                                              7
                                                             1%
                                                            10.8
                                                            1.12
                                         Btu/W-hr  (CU Only)
                                         Btu/W-hr  (CU Only)
                                         tons
                                         years
                                         (% degraded)
                                         Btu/W-hr
                                  Amps
                                  Volts
                                   Amps
                                   Volts
                                                           3-phase
                                                            1.73
                                                              2
1-Phase
   1
   2
                                 3-Phase
                                   1.73
                                    1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
FPM
7.2
8.2
5.3
4.9
7.8
5.5
6.483
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3
Delta Measurement
Phase
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency



Volts
480
480
t Measurement
10
70
50
28
85
Circuit 1
92%
93%
3.5
85
4.20






Amps kW PF
15.5
13.4 5
F
F
%
%
3 0.41
8 0.92

Circuit 2


Tons
F
kW
CU Capacity Estimates
83 F
105 F
41 in
29 in
16.5sq-ft
6424
3.64 kg/sec
12.72 Tons
17.34 EER
98%
96%
3.5 Tons
86 F
4.10 kW
301 K
314 K
HVAC Data Sheet
Page 1 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                       Monroe Aquatics Center
                                                                                                                    RTU-2

-------
                            Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
York
D3CG090N1304GG
NGFM090091
RTU-Gas
1997
Monroe Aquatic Center
RTU-2

7.1 Amps
460 Volts
0.64

1.3 Amps
460 Volts
0.7
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:             0
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kWrton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
                Power supply:
                Phase adjustment:
                Fan quantity:

          7.2    kW
          0.84   kW
          0.00   kW
          8.07   kW - Condensing side only
0.0%   Performance Degradation
                                                    11.1
                                                    11.2
                                                    7.50
                                                     7
                                                    0%
                                                    10.8
                                                    1.11
                                                             Btu/W-hr  (CD Only)
                                                             Btu/W-hr  (CD Only)
                                                             tons
                                                             years
                                                             (% degraded)
                                                             Btu/W-hr
Amps
Volts
                                                  3-phase
                                                   1.73
                                                     2
                                                  1-Phase
                                                     1
                                                     2
3-Phase
  1.73
   1
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
7
8
9
10
11
12
Average
FPM
11.5
11.7
11.9
12.5
11.5
11.5
14.3
13.9
11.1
14.6
13.5
13.5
12.625
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
480
485
t Measurement
10
70
50
30
85
Circuit 1
100%
99%
3.5
88
4.10
15.2 2
13.4
F
F
%
%
9 0.4
5 0.92

Circuit 2


Tons
F
kW
CU Capacity Estimates
88.5 F
104.5 F
41 in
29 in
16.5 sq-ft
12509
7.08 kg/sec
18.01 Tons
24.29 EER
00%
99%
3.5 Tons
89 F
4.20 kW
305 K
313 K
HVAC Data Sheet
Page 2 of 3
                                                                                                             EPA Adsil Evaluation
                                                                                                          Monroe Aquatics Center
                                                                                                                        RTU-2

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-2   Summary
                11.1  BTU/W-h
               6424 CFM (Measured)
                7.49 tons
                7.00 tons
               16.51  sq-ft
               10.76 pre	10.83 post
Equipment age
7 years
Test Date
24-May

HVAC Service Assistant

OAT
85

Post Adsil Measurements
16-Jun

88

EWB
53


53

El
95%


100%

Cl
95%


99%

EER
11.2


11.1

kW
8.88


8.88

Physical Power and Capacity measurments
Cond Air, deg F
inlet
83


88.5

exhaust
105


104.5

Cond Air
AT(K)
12.2


8.9

kW
8.8


8.9

(kg/sec)
3.64


7.08


tons
12.72


18.01


EER
17.34


24.29

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
8.88
6.70
11.2
8.88
6.91
11.1
CU
8.8
12.72
17.34
8.9
18.01
24.29
Lit
7.25
7.09
11.75
7.52
6.98
11.14
Percent Difference
SA/Lit
123%
95%
95%
118%
99%
100%
CU/Lit
121%
179%
148%
118%
258%
218%
SS/Lit
100%
100%
97%
100%
100%
97%
Condensing Unit Summary - ARI Conditions
Test Data
SA
9.9
7.1
10.6
9.5
7.4
11.1
CU
9.8
13.4
16.4
9.6
19.3
24.2
Literature
8.08
7.49
11.12
8.08
7.49
11.12
Percent Difference
SA/Lit
123%
95%
95%
118%
99%
100%
CU/Lit
121%
179%
148%
118%
258%
218%
SA/CU
101%
53%
64%
100%
38%
46%
Predicted/SA


102%

-
97%
Predicted/CU


66%

-
44%
Predicted/
Original


97%

-
97%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.2
11.1

10.6
11.1
5.3%
Condenser Test
17.34
24.29

16.44
24.28
47.6%
Spreadsheet
10.76
10.83

10.76
10.83
0.7%
            Weighted Average   36.8%
                                                333.4%
                                                                4.6%
HVAC Data Sheet
Page 3 of 3
                                                                                                                             EPA Adsil Evaluation
                                                                                                                          Monroe Aquatics Center
                                                                                                                                        RTU-2

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
York
D3CG090N1304GG
NGFM090089
RTU-Gas
1997
Monroe Aquatic Center
RTU-1
7.1 Amps
460 Volts
0.64
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.30
460
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
0.9
0.1




1





0.1


0
0
0

X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    7.2    kW
                   0.84   kW
                   0.00   kW
                   8.07   kW - Condensing side only
                                     0.52%  Performance Degradation
                                                            11.1
                                                            11.1
                                                            7.49
                                                              7
                                                             1%
                                                            10.8
                                                            1.12
                                         Btu/W-hr  (CU Only)
                                         Btu/W-hr  (CU Only)
                                         tons
                                         years
                                         (% degraded)
                                         Btu/W-hr
                                  Amps
                                  Volts
                                   Amps
                                   Volts
                                                           3-phase
                                                            1.73
                                                              2
1-Phase
   1
   2
                                 3-Phase
                                   1.73
                                    1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
4.7
12.7
6.4
14.3
9.525
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3
Delta Measurement
Phase
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency



Volts
477
481
t Measurement
10
74
54
50
85
Circuit 1
95%
1 02%
3.5
94
4.40






Amps kW PF
16.5 3
14.5 6
F
F
%
%
5 0.46
8 0.95

Circuit 2


Tons
F
kW
CU Capacity Estimates
95 F
112. 5 F
41 in
29 in
16.5sq-ft
9438
5.34 kg/sec
14.86 Tons
17.32 EER


Tons
F
kW
308 K
318 K
HVAC Data Sheet
Page 1 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                       Monroe Aquatics Center
                                                                                                                     RTU-1

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
York
D3CG090N1304GG
NGFM090089
RTU-Gas
1997
Monroe Aquatic Center
RTU-1
7.1 Amps
460 Volts
0.64
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1 .3
460
0.7
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1





0
0

0
0
0

X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                   Amps              Power supply:
                                   Volts               Phase adjustment:
                                                     Fan quantity:
       Amps             Power supply:
       Volts              Phase adjustment:
                         Fan quantity:

                   7.2   kW
                   0.84   kW
                   0.00   kW
                   8.07   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                                                        11.1
                                                                                        11.1
                                                                                        7.49
                                                                                         7
                                                                                        0%
                                                                                        10.8
                                                                                        1.11
                                                                   Btu/W-hr  (CU Only)
                                                                   Btu/W-hr  (CU Only)
                                                                   tons
                                                                   years
                                                                   (% degraded)
                                                                   Btu/W-hr
                                                                                      3-phase
                                                                                       1.73
                                                                                         2
1-Phase
   1
   2
                                                                                      3-Phase
                                                                                        1.73
                                                                                         1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
6
Average
ft/sec
12.4
11.8
12.6
13.4
13.7
12.4
12.717
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
476
483
t Measurment
10
74
54
50
85

99%
101%
3.5
91
4.30
15.6 3
14.1 6
F
F
%
%
Tons
F
kW
CU Capacity Estimates
90.5 F
106. 5 F
41 in
29 in
16.5sq-ft
12600
7.14 kg/sec
18. 14 Tons
22.44 EER
2 0.42
5 0.95
306 K
315 K
HVAC Data Sheet
Page 2 of 3
                                                                                                                                    EPA Adsil Evaluation
                                                                                                                                  Monroe Aquatics Center
                                                                                                                                                RTU-1

-------
    Monroe Aquatic Center
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER  =
RTU-1    Summary
               11.1  BTU/W-h
               9438 CFM (Measured)
               7.49 tons
               3.50 tons
               16.51  sq-ft
               10.76 pre	10.81 post
Equipment age
7 years
Test Date
24-May

HVAC Service Assistant

OAT
94

Post Adsil Measurements
16-Jun

91

EWB
61


61

El
95%


99%

Cl
102%


101%

EER
10.5


10.9

kW
9.41


9.20

Physical Power and Capacity measurments
Cond Air, deg F
inlet
95


90.5

exhaust
112.5


106.5

Cond Air
AT(K)
9.7


8.9

kW
10.3


9.7

(kg/sec)
5.34


7.14


tons
14.86


18.14


EER
17.32


22.44

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
9.41
7.07
10.5
9.20
7.13
10.9
CU
10.3
14.86
17.32
9.7
18.14
22.44
Lit
7.93
6.93
10.49
7.68
7.06
11.02
Percent Difference
SA/Lit
119%
102%
100%
120%
1 01 %
99%
CU/Lit
130%
214%
165%
126%
257%
204%
SS/Lit
100%
100%
97%
100%
100%
97%
Condensing Unit Summary - ARI Conditions
Test Data
SA
9.6
7.6
11.1
9.7
7.6
11.0
CU
10.5
16.1
18.4
10.2
19.3
22.7
Literature
8.08
7.49
11.12
8.08
7.49
11.12
Percent Difference
SA/Lit
119%
102%
100%
120%
101%
99%
CU/Lit
130%
214%
165%
126%
257%
204%
SA/CU
91%
48%
60%
95%
39%
49%
Predicted/SA


97%

-
98%
Predicted/CU


59%

-
47%
Predicted/
Original


97%

-
97%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
10.5
10.9

10.6
11.0
4.2%
Condenser Test
17.32
22.44

18.38
22.68
23.4%
Spreadsheet
10.76
10.81

10.76
10.81
0.5%
            Weighted Average   14.7%
                                                 82.0%
HVAC Data Sheet
Page 3 of 3
                                                                                                                             EPA Adsil Evaluation
                                                                                                                          Monroe Aquatics Center
                                                                                                                                        RTU-1

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Tempstar
CH9536VKB2
L970880635
Split Heat pump
1997
Locust City Hall
SS-2

16.0 An
208 Vc
0.96
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.30
208
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

1



1

0.1




0.05






X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                    Power supply:
                                                    Phase adjustment:
                                                    Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    3.2    kW
                   0.19    kW
                   0.00    kW
                   3.38    kW - Condensing side only
                                    5.95%  Performance Degradation
                                                            10.6
                                                            10.6
                                                            3.00
                                                             7
                                                            6%
                                                            9.8
                                                            1.23
                                                                                              Btu/W-hr  (CU Only)
                                                                                              Btu/W-hr  (CU Only)
                                                                                              tons
                                                                                              years
                                                                                              (% degraded)
                                                                                              Btu/W-hr
Amps
Volts
                                   Amps
                                   Volts
                                                           1-Phase
                                                             1
                                                             1
1-Phase
   1
   1
 CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
4.7
5.5
2.7
6.4
4.825
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
120
120
t Measurment






112%
1 09%
3
94
3.50
10.78 1.
10.56 1.
F
F
%
%
Tons
F
kW
CU Capacity Estimates
95 F
104 F
88 in
29 in
17.7sq-ft
5131
2.91 kg/sec
4. 16 Tons
21. 22 EER
17 0.91
18 0.93
308 K
313 K
HVAC Data Sheet
Page 1 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                 Locust, NC Police Department
                                                                                                                     HP-2

-------
                           Post-Ad si I HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Tempstar
CH9536VKB2
L970880635
Split Heat pump
1997
Locust City Hall
SS-2

16 An
208 Vc
0.96
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.3
208
0.7
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:             0

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                         Power supply:
                         Phase adjustment:
                         Fan quantity:

                   3.2   kW
                   0.19   kW
                   0.00   kW
                   3.38   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                            10.6
                                                            10.6
                                                            3.00
                                                             7
                                                            0%
                                                            10.3
                                                            1.16
                                                                                              Btu/W-hr  (CU Only)
                                                                                              Btu/W-hr  (CU Only)
                                                                                              tons
                                                                                              years
                                                                                              (% degraded)
                                                                                              Btu/W-hr
Amps
Volts
                                   Amps
                                   Volts
                                                          1-Phase
                                                             1
                                                             1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.5
6.8
6.6
6.4
6.325
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
118
118
t Measurment
10
74
54
50
85

118%
116%
3
89
3.60
10.48 1.
10.35 1.
F
F
%
%
Tons
F
kW
CU Capacity Estimates
89 F
100 F
88 in
29 in
17.7sq-ft
6726
3.81 kg/sec
6.66 Tons
35.20 EER
15 0.91
12 0.91
305 K
311 K
HVAC Data Sheet
Page 2 of 3
                                                                                                        EPA Adsil Evaluation
                                                                                                 Locust, NC Police Department
                                                                                                                     HP-2

-------
    Locust City Hall
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-2   Summary
                        10.6 BTU/W-h
                       5131 CFM (Measured)
                        3.00 tons
                        3.00 tons
                       17.72 sq-ft
                        9.76 pre	10.33 post
Equipment age
7 years
Test Date
24-May

HVAC Service Assistant

OAT
94

Post Adsil Measurements
16-Jun

89

EWB
NA


NA

El
1 1 2%


1 1 8%

Cl
109%


116%

EER
11.9


12.5

kW
3.50


3.60

Physical Power and Capacity measurments
Cond Air, deg F
inlet
95


89

exhaust
104


100

Cond Air
AT(K)
5.0


6.1

kW
2.35


2.27

(kg/sec)
2.91


3.81


tons
4.16


6.66


EER
21.22


35.20

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
3.50
NA
11.9
3.60
NA
12.5
CU
NA
NA
NA
NA
NA
NA
Lit
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit






SS/Lit
NA
NA
NA
NA
NA
NA
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
NA
NA
NA
NA
NA
NA
CU






Literature
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit






SA/CU






Predicted/SA


NA


NA
Predicted/CU






Predicted/
Original


NA


NA
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.9
12.5
11.9
12.5
5.4%
Condenser Test
NA
NA
NA
NA
NA
Spreadsheet
11.7
11.9
11.7
11.9
1.9%
             Weighted Average   16.1%
                                                  NA
                                                                 5.8%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                        EPA Adsil Evaluation
                                                                                                                                 Locust, NC Police Department
                                                                                                                                                    HP-2

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Tempstar
CH9536VKB2
L970880635
Split Heat pump
1997
Locust City Hall
SS-1

16.0 An
208 Vc
0.96
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.30
208
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

1



1
0.8
0.2




0.05

0.2




X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    3.2    kW
                   0.19   kW
                   0.00   kW
                   3.38   kW - Condensing side only
                                     7.2%   Performance Degradation
                                                            10.6
                                                            10.6
                                                            3.00
                                                             7
                                                            7%
                                                            9.7
                                                            1.24
                                                                                              Btu/W-hr  (CU Only)
                                                                                              Btu/W-hr  (CU Only)
                                                                                              tons
                                                                                              years
                                                                                              (% degraded)
                                                                                              Btu/W-hr
Amps
Volts
                                   Amps
                                   Volts
                                                           1-Phase
                                                              1
                                                              1
1-Phase
   1
   1
 CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
FPM
6.6
7.6
4.7
5.5
6.100
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
120
120
t Measurment
10
74
54
50
85

118%
114%
3
93
3.50
12.7 1.
11.7 1
F
F
%
%
Tons
F
kW
CU Capacity Estimates
93 F
105 F
88 in
29 in
17.7sq-ft
6486
3.67 kg/sec
7.00 Tons
31. 02 EER
41 0.98
3 0.56
307 K
314 K
HVAC Data Sheet
Page 1 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                          Locust, NC City Hall
                                                                                                                      HP-1

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Tempstar
CH9536VKB2
L970880635
Split Heat pump
1997
Locust City Hall
SS-1

16 An
208 Vc
0.96
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.3
208
0.7
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:             0

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                         Power supply:
                         Phase adjustment:
                         Fan quantity:

                   3.2   kW
                   0.19   kW
                   0.00   kW
                   3.38   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                            10.6
                                                            10.6
                                                            3.00
                                                             7
                                                            0%
                                                            10.3
                                                            1.16
                                                                                              Btu/W-hr  (CU Only)
                                                                                              Btu/W-hr  (CU Only)
                                                                                              tons
                                                                                              years
                                                                                              (% degraded)
                                                                                              Btu/W-hr
Amps
Volts
                                   Amps
                                   Volts
                                                          1-Phase
                                                             1
                                                             1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
FPM
7.2
8.2
8.6
6.6
7.650
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
120
120
t Measurment
10
74
54
50
85

122%
117%
3
87
3.50
11.5 1.
11.5 1.
F
F
%
%
Tons
F
kW
CU Capacity Estimates
87 F
101 F
88 in
29 in
17.7sq-ft
8135
4.61 kg/sec
10.25 Tons
49.00 EER
25 0.91
26 0.91
304 K
311 K
HVAC Data Sheet
Page 2 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                          Locust, NC City Hall
                                                                                                                      HP-1

-------
    Locust City Hall
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-1   Summary
                        10.6 BTU/W-h
                       6486 CFM (Measured)
                        3.00 tons
                        3.00 tons
                       17.72 sq-ft
                        9.65 pre	10.33 post
Equipment age
7 years
Test Date
24-May

HVAC Service Assistant

OAT
93

Post Adsil Measurements
16-Jun

87

EWB
62


62

El
1 1 8%


122%

Cl
114%


117%

EER
12.6


13.0

kW
3.50


3.50

Physical Power and Capacity measurments
Cond Air, deg F
inlet
93


87

exhaust
105


101

Cond Air
AT(K)
6.7


7.8

kW
2.71


2.51

(kg/sec)
3.67


4.61


tons
7.00


10.25


EER
31.02


49.00

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil
Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
3.50
NA
12.6
3.50
NA
13.0
CU
NA
NA
NA
NA
NA
NA
Lit
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit






SS/Lit
NA
NA
NA
NA
NA
NA
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
NA
NA
NA
NA
NA
NA
CU






Literature
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit






SA/CU






Predicted/SA


NA


NA
Predicted/CU






Predicted/
Original


NA


NA
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
12.6
13.0
12.6
13.0
3.4%
Condenser Test
NA
NA
NA
NA
NA
Spreadsheet
11.7
11.9
11.7
11.9
1.9%
             Weighted Average   10.2%
                                                 NA
                                                                 5.8%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                        EPA Adsil Evaluation
                                                                                                                                         Locust, NC City Hall
                                                                                                                                                    HP-1

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
48DJE004630
0292G64683
RTU-Gas
1992
Iredell Health Center
RTU-3

6.1 Amps
460 Volts
0.71
Condensing Fan Data
Full load Amps:                1.00
Nameplate Voltage:            460
Adjust FLA to RLA:             0.70

Evaporator fan data (If applicable)
Full load Amps:                1.50
Nameplate Voltage:            460
Adjust FLA to RLA:             0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coll Condlton
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:

                                                3.4   kW
                                                0.32   kW
                                                0.48   kW
                                                3.74   kW-Condensing side only
         10.0%   Performance Degradation
                                                              9.5
                                                              9.5
                                                             2.97
                                                              12
                                                             10%
                                                              8.1
                                                             1.49
        Btu/W-hr   (CU Only)
        Btu/W-hr   (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
       Amps
       Volts
       Amps
       Volts
                                                            3-phase
                                                              1.73
                                                               1
1-Phase
   1
   1
1-Phase
   1
   1
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
ft/sec
12.5
13.1
12.8
0.9
0.1
0.1
0.3
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
466
467
t Measurment
10
74
54
50
85
Circuit 1
102%
99%
4
83
3.53
5.7 1.2 0.45
5.4 2.5 0.99
F
F
%
Tons
F
kW
CU Capacity Estimates
85 F 303 K
94 F 308 K
62 in
28 in
12.1 sq-ft
9259
5.24 kg/sec
7.50 Tons
24.32 EER
HVAC Data Sheet
Page 1 of 3
                                                                                                 EPA Adsil Evaulation
                                                                                              Iredell Health Center, NC
                                                                                                             RTU-3

-------
                          Post-Adsil  HVAC  Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
48DJE004630
0292G64683
RTU-Gas
1992
Iredell Health Center
RTU-3
    6.1     Amps
    460    Volts
    0.71
     1      Amps
    460    Volts
    0.7
Evaporator fan data (If applicable)
Full load Amps:               1.5
Nameplate Voltage:            460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coll Condlton
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                             Power supply:
                             Phase adjustment:
                             Fan quantity:

                       3.4   kW
                       0.32   kW
                       0.48   kW
                       3.74   kW-Condensing side only
              0.0%   Performance Degradation
  9.5
  9.5
 2.97
  12
  0%
  8.8
 1.36
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
Amps
Volts
3-phase
  1.73
   1
1-Phase
   1
   1
1-Phase
   1
   1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
FPM
13.9
13.9
13.9
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
467
469
t Measurment
10
74
54
50
85

104%
100%
3
79
3.50
5.8 1
5.7 2
F
F
%
%
Tons
F
kW
CU Capacity Estimates
77 F
85 F
62 in
28 in
12.1 sq-ft
10054
5.69 kg/sec
7.24 Tons
23.48 EER
2 0.46
5 1.00
298 K
303 K
HVAC Data Sheet
Page 2 of 3
                                                                                                        EPA Adsil Evaulation
                                                                                                     Iredell Health Center, NC
                                                                                                                   RTU-3

-------
    Iredell Health Center
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-3   Summary
                 9.5 BTU/W-h
               9259 CFM (Measured)
                2.97 tons
                4.00 tons
               12.06 sq-ft
                8.06 pre	8.80 post
Equipment age
12 years
Test Date
24-May

HVAC Service Assistant

OAT
83

Post Adsil Measurements
16-Jun

79

EWB
62


62

El
102%


104%

Cl
99%


100%

EER
10.5


11.4

kW
2.61


2.60

Physical Power and Capacity measurments
Cond Air, deg F
inlet
85


77

exhaust
94


85

Cond Air
AT(K)
5.0


4.4

kW
3.7


3.7

(kg/sec)
5.24


5.69


tons
7.50


7.24


EER
24.32


23.48

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
NA
2.87
10.5
NA
2.99
11.4
CU
3.7
7.50
24.32
3.7
7.24
23.48
Lit
3.37
2.90
10.32
3.28
2.99
10.93
Percent Difference
SA/Lit
NA
99%
102%
NA
100%
1 04%
CU/Lit
110%
259%
236%
113%
242%
215%
SS/Lit
100%
100%
85%
100%
100%
93%
Condensing Unit Summary - ARI Conditions
Test Data
SA
NA
2.9
9.7
NA
3.0
9.9
CU
4.1
7.7
22.4
4.2
7.2
20.4
Literature
3.75
2.97
9.50
3.75
2.97
9.50
Percent Difference
SA/Lit
NA
99%
102%
NA
100%
104%
CU/Lit
110%
259%
236%
113%
242%
215%
SA/CU
NA
38%
43%
NA
41%
48%
Predicted/SA


83%

-
82%
Predicted/CU


36%

-
39%
Predicted/
Original


85%

-
93%
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
10.5
11.4

9.7
9.9
2.0%
Condenser Test
24.32
23.48

22.41
20.42
-8.9%
Spreadsheet
8.06
8.80

8.06
8.80
9.3%
            Weighted Average    7.8%
                                                 -35.5%
                                                                37.0%
HVAC Data Sheet
Page 3 of 3
                                                                                                                               EPA Adsil Evaulation
                                                                                                                            Iredell Health Center, NC
                                                                                                                                          RTU-3

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
48DJD007
5291G62648
RTU-Gas
1992
Iredell Health Center
RTU-14
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coll Condlton
                   Present Condition EER
                   kW/ton
  10.8
  10.8
  6.30
  12
  9%
  9.2
  1.30
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
    10.4     Amps              Power supply:
    460     Volts              Phase adjustment:
    0.81                       Compressor quantity:
    1.00
    460
    0.70
Evaporator fan data (If applicable)
Full load Amps:               1.80
Nameplate Voltage:            460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
Amps              Power supply:
Volts               Phase adjustment:
                   Fan quantity:
            Amps              Power supply:
            Volts              Phase adjustment:
                              Fan quantity:

                        6.7    kW
                       0.32   kW
                       0.58   kW
                       7.03   kW-Condensing side only
              8.6%   Performance Degradation
                                                    3-phase
                                                      1.73
                                                       1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
ft/sec
10.5
9.2
9.9
    0.5
    0.5
    0.9
    0.1
    0.25
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
464
465
t Measurment
10
74
54
50
85
Circuit 1
NA
NA
6
88
NA
12.8 2.
13.9 6.
F
F
%
Tons
F
kW
CU Capacity Estimates
88 F
109 F
62 in
28 in
12.1 sq-ft
7125
4.03 kg/sec
13.47 Tons
18.79 EER
25 0.39
35 0.98
304 K
316 K
HVAC Data Sheet
Page 1 of 3
                                                                                                     EPA Adsil Evaluation
                                                                                                  Iredell Health Center, NC
                                                                                                                RTU-14

-------
                          Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
48DJD007
5291G62648
RTU-Gas
1992
Iredell Health Center
RTU-14
    10.4    Amps
    460    Volts
    0.81
     1      Amps
    460    Volts
    0.7
Evaporator fan data (If applicable)
Full load Amps:               1.8
Nameplate Voltage:            460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coll Condlton
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                             Power supply:
                             Phase adjustment:
                             Fan quantity:

                       6.7   kW
                       0.32   kW
                       0.58   kW
                       7.03   kW-Condensing side only
             0.0%  Performance Degradation
Amps
Volts
  10.8   Btu/W-hr
  10.8   Btu/W-hr
  6.3    tons
  12    years
  0%    (% degraded)
  10.0   Btu/W-hr
  1.20
3-phase
  1.73
   1
1-Phase
   1
   1
1-Phase
   1
   1
(CU Only)
(CU Only)
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
ft/sec
12.1
11.1
11.6
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
465
466
t Measurment
10
74
54
50
85

100%
103%
5
80
6.10
12.3 1
13.5 6
F
F
%
%
Tons
F
kW
CU Capacity Estimates
79 F
96 F
62 in
28 in
12.1 sq-ft
8391
4.75 kg/sec
12. 84 Tons
19.50 EER
9 0.34
0 0.97
299 K
309 K
HVAC Data Sheet
Page 2 of 3
                                                                                                        EPA Adsil Evaluation
                                                                                                    Iredell Health Center, NC
                                                                                                                  RTU-14

-------
    Iredell Health Center
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-14  Summary
                10.8 BTU/W-h
               7125 CFM (Measured)
                6.30 tons
                6.00 tons
               12.06 sq-ft
                9.23 pre	9.96 post
Equipment age
12 years
Test Date
24-May

HVAC Service Assistant

OAT
88

Post Adsil Measurements
16-Jun

80

EWB
62


62

El
NA


100%

Cl
NA


103%

EER
NA


12.0

kW
NA


6.41

Physical Power and Capacity measurments
Cond Air, deg F
inlet
88


79

exhaust
109


96

Cond Air
AT(K)
11.7


9.4

kW
8.6


7.9

(kg/sec)
4.03


4.75


tons
13.47


12.84


EER
18.79


19.50

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
NA
NA
NA
6.41
6.38
12.0
CU
8.6
13.47
18.79
7.9
12.84
19.50
Lit
6.53
5.92
10.87
6.21
6.19
11.96
Percent Difference
SA/Lit
NA
NA
NA
103%
103%
100%
CU/Lit
132%
227%
173%
127%
207%
163%
SS/Lit
100%
100%
86%
100%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data
SA
NA
NA
NA
7.2
6.5
10.8
CU
9.2
14.3
18.6
8.9
13.1
17.6
Literature
7.02
6.30
10.78
7.02
6.30
10.78
Percent Difference
SA/Lit
NA
NA
NA
103%
103%
100%
CU/Lit
132%
227%
173%
127%
207%
1 63%
SA/CU
NA
NA
NA
81%
50%
61%
Predicted/SA


NA

-
86%
Predicted/CU


50%

-
53%
Predicted/
Original


86%

-
92%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
NA
12.0

NA
10.8
NA
Condenser Test
18.79
19.50

18.59
17.54
-5.7%
Spreadsheet
9.23
9.96

9.23
9.96
8.0%
            Weighted Average   NA
                                                 -34.0%
                                                                47.8
HVAC Data Sheet
Page 3 of 3
                                                                                                                               EPA Adsil Evaluation
                                                                                                                            Iredell Health Center, NC
                                                                                                                                         RTU-14

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
48DJD006
0492G68975
RTU-Gas
1992
Iredell Health Center
RTU-13
    9.6     Amps
    460     Volts
    0.79
    1.00
    460
    0.70
Evaporator fan data (If applicable)
Full load Amps:               1.80
Nameplate Voltage:            460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coll Condlton
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
                   Power supply:
                   Phase adjustment:
                   Fan quantity:
                              Power supply:
                              Phase adjustment:
                              Fan quantity:

                        6.0    kW
                       0.32   kW
                       0.58   kW
                       6.36   kW-Condensing side only
             6.35%   Performance Degradation
                                                      9.8
                                                      9.8
                                                      5.19
                                                       12
                                                      6%
                                                      8.6
                                                      1.40
        Btu/W-hr   (CU Only)
        Btu/W-hr   (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
Amps
Volts
Amps
Volts
                                                    3-phase
                                                      1.73
                                                       1
1-Phase
   1
   1
                                                    1-Phase
                                                       1
                                                       1
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
ft/sec
8.0
8.0
8.0
    0.5
    0.5
    0.15
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
460
460
t Measurment
10
74
54
50
85
Circuit 1
94%
97%
5
87
6.10
10 1.9 0.39
10.1 4.65 0.99
F
F
%
Tons
F
kW
CU Capacity Estimates
83 F 301 K
102 F 312 K
63 in
29 in
12.7 sq-ft
6090
3.45 kg/sec
10.41 Tons
19.08 EER
HVAC Data Sheet
Page 1 of 3
                                                                                                     EPA Adsil Evaluation
                                                                                                  Iredell Health Center, NC
                                                                                                                RTU-13

-------
                          Post-Adsil  HVAC  Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
48DJD006
0492G68975
RTU-Gas
1992
Iredell Health Center
RTU-13
    9.6    Amps
    460    Volts
    0.79
     1      Amps
    460    Volts
    0.7
Evaporator fan data (If applicable)
Full load Amps:               1.8
Nameplate Voltage:            460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                  Published EER:
                  Calculated EER:
                  Nominal Capacity:
                  Age
                  Coll Condlton
                  Present Condition EER
                  kW/ton
                  Power supply:
                  Phase adjustment:
                  Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                             Power supply:
                             Phase adjustment:
                             Fan quantity:

                       6.0   kW
                       0.32   kW
                       0.58   kW
                       6.36   kW-Condensing side only
              0.0%   Performance Degradation
  9.8
  9.8
  5.2
  12
  0%
  9.1
  1.32
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
Amps
Volts
3-phase
  1.73
   1
1-Phase
   1
   1
1-Phase
   1
   1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
ft/sec
12.5
10.0
11.3
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
^l
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
465
465
t Measurment
10
74
54
50
85

100%
103%
5
80
6.10
9.8 1
9.9 4
F
F
%
%
Tons
F
kW
CU Capacity Estimates
77 F
93 F
63 in
29 in
12.7 sq-ft
8564
4.85 kg/sec
12.33 Tons
24.26 EER
6 0.35
5 0.98
298 K
307 K
HVAC Data Sheet
Page 2 of 3
                                                                                                        EPA Adsil Evaluation
                                                                                                     Iredell Health Center, NC
                                                                                                                  RTU-13

-------
    Iredell Health Center
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-13  Summary
                 9.8 BTU/W-h
               6090 CFM (Measured)
                5.19 tons
                5.00 tons
               12.69 sq-ft
                8.56 pre	9.06 post
Equipment age
12 years
Test Date
24-May

HVAC Service Assistant

OAT
87

Post Adsil Measurements
16-Jun

80

EWB
62


62

El
94%


100%

Cl
97%


103%

EER
10.0


11.0

kW
6.33


6.33

Physical Power and Capacity measurments
Cond Air, deg F
inlet
83


77

exhaust
102


93

Cond Air
AT(K)
10.6


8.9

kW
6.55


6.1

(kg/sec)
3.45


4.85


tons
10.41


12.33


EER
19.08


24.26

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
6.33
4.87
10.0
6.33
5.25
11.0
CU
6.55
10.41
19.08
6.1
12.33
24.26
Lit
5.67
5.02
10.62
5.57
5.09
10.98
Percent Difference
SA/Lit
112%
97%
94%
114%
103%
100%
CU/Lit
116%
207%
180%
110%
242%
221 %
SS/Lit
101%
100%
87%
101%
100%
92%
Condensing Unit Summary - ARI Conditions
Test Data
SA
7.1
5.0
9.3
7.2
5.3
9.8
CU
7.3
10.8
17.7
6.9
12.6
21.7
Literature
6.32
5.19
9.85
6.32
5.19
9.85
Percent Difference
SA/Lit
112%
97%
94%
1 1 4%
103%
100%
CU/Lit
116%
207%
180%
110%
242%
221%
SA/CU
97%
47%
52%
104%
43%
45%
Predicted/SA


92%

-
87%
Predicted/CU


48%

-
39%
Predicted/
Original


87%

-
92%
                                  EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
10.0
11.0

9.2
9.8
6.4%
Condenser Test
19.08
24.26

17.58
21.62
23.0%
Spreadsheet
8.56
9.06

8.56
9.06
5.9%
            Weighted Average   31.9%
                                                 114.9%
                                                                29.4%
HVAC Data Sheet
Page 3 of 3
                                                                                                                              EPA Adsil Evaluation
                                                                                                                           Iredell Health Center, NC
                                                                                                                                         RTU-13

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
48DJE004630
0292G64667
RTU-Gas
1992
Iredell Health Center
RTU-1

6.1 Amps
460 Volts
0.71
Condensing Fan Data
Full load Amps:                1.00
Nameplate Voltage:            460
Adjust FLA to RLA:             0.70

Evaporator fan data (If applicable)
Full load Amps:                1.50
Nameplate Voltage:            460
Adjust FLA to RLA:             0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coll Condlton
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:

                                                3.4   kW
                                                0.32   kW
                                                0.48   kW
                                                3.74   kW-Condensing side only
          10.8%  Performance Degradation
                                                              9.5
                                                              9.5
                                                              2.97
                                                               12
                                                              11%
                                                              8.0
                                                              1.50
        Btu/W-hr   (CU Only)
        Btu/W-hr   (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
        Amps
        Volts
        Amps
        Volts
                                                            3-phase
                                                              1.73
                                                               1
1-Phase
   1
   1
1-Phase
   1
   1
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
ft/sec
11.5
12.5
12.0
0.8
0.2
0.25
0.25
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
467
466
t Measurment
10
74
54
50
85
Circuit 1
102%
97%
3
87
3.50
5.5 1.3 0.5
5.1 2.4 0.99
F
F
%
Tons
F
kW
CU Capacity Estimates
85 F 303 K
93 F 307 K
62 in
28 in
12.1 sq-ft
8680
4.92 kg/sec
6.25 Tons
20.27 EER
HVAC Data Sheet
Sheet 1 of 3
                                                                                                  EPA Adsil Evaluation
                                                                                              Iredell Health Center, NC
                                                                                                              RTU-1

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
48DJE004630
0292G64667
RTU-Gas
1992
Iredell Health Center
RTU-1
6.1 Amps
460 Volts
0.705
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
 1      Amps             Power supply:
460    Volts              Phase adjustment:
0.7                      Fan quantity:
                                                             9.5
                                                             9.5
                                                            2.97
                                                             12
                                                             0%
                                                             8.8
                                                            1.36
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
Evaporator fan data (if applicable)
Full load Amps:               1.5
Nameplate Voltage:            460
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



       Amps             Power supply:
       Volts              Phase adjustment:
                         Fan quantity:

                   3.4   kW
                   0.32   kW
                   0.48   kW
                   3.74   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                           3-phase
                                                            1.73
                                                              1
1-Phase
   1
   1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
Average
ft/sec
13.1
12.7
10.9
12.4
10.2
11.9
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
470
471
t Measurement
10
74
54
50
85

107%
1 04%
3
79
3.50
5.6 1
4.9 0
F
F
%
%
Tons
F
kW
CU Capacity Estimates
75 F
84 F
62 in
28 in
12.1 sq-ft
8579
4.86 kg/sec
6.95 Tons
37.90 EER
3 0.98
9 0.41
297 K
302 K
HVAC Data Sheet
Sheet 2 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                      Iredell Health Center, NC
                                                                                                                     RTU-1

-------
    Iredell Health Center
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-1 Summary
               9.5 BTU/W-h
             8680 CFM (Measured)
              2.97 tons
              3.00 tons
             12.06 sq-ft
              8.00 pre	8.80 post
Equipment age
12 years
Test Date
24-May

HVAC Service Assistant

OAT
87

Post Adsil Measurements
16-Jun

79

EWB
62


62

El
102%


107%

Cl
97%


1 04%

EER
9.9


11.7

kW
3.46


3.46

Physical Power and Capacity measurments
Cond Air, deg F
inlet
85


75

exhaust
93


84

Cond Air
AT(K)
4.4


5.0

kW
3.7


2.2

(kg/sec)
4.92


4.86


tons
6.25


6.95


EER
20.27


37.90

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
3.46
2.72
9.9
3.46
3.11
11.7
CU
3.7
6.25
20.27
2.2
6.95
37.90
Lit
3.46
2.80
9.74
3.28
2.99
10.93
Percent Difference
SA/Lit
100%
97%
102%
105%
1 04%
107%
CU/Lit
107%
223%
208%
67%
232%
347%
SS/Lit
100%
100%
84%
100%
100%
93%
Condensing Unit Summary - ARI Conditions
Test Data
SA
3.8
2.9
9.7
3.9
3.1
10.2
CU
4.0
6.6
19.8
2.5
6.9
32.9
Literature
3.75
2.97
9.50
3.75
2.97
9.50
Percent Difference
SA/Lit
100%
97%
102%
105%
104%
107%
CU/Lit
107%
223%
208%
67%
232%
347%
SA/CU
94%
44%
49%
157%
45%
31%
Predicted/SA


83%

-
79%
Predicted/CU


40%

-
24%
Predicted/
Original


84%

-
93%
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
9.9
11.7

9.7
10.2
4.9%
Condenser Test
20.27
37.90

19.79
32.96
66.6%
Spreadsheet
8.00
8.80

8.00
8.80
10.0%
             Weighted Average   14.7%
                                                 199.7%
                                                                29.9%
HVAC Data Sheet
Sheet 3 of 3
                                                                                                                             EPA Adsil Evaluation
                                                                                                                          Iredell Health Center, NC
                                                                                                                                        RTU-1

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Lennox
HS290609Y
S801M14822
SS
2001
Granite Quarry
SS-3
17.3 Al
208 V(
0.95
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.90
208
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
1




1

0.35



0.9
0.1

0.1




X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    5.9    kW
                   0.28    kW
                   0.00    kW
                   6.19    kW-Condensing side only
                                     7.3%   Performance Degradation
                                                             NA
                                                             9.7
                                                            5.00
                                                             3
                                                             7%
                                                             9.1
                                                            1.32
                                                                                              Btu/W-hr  (CU Only)
                                                                                              Btu/W-hr  (CU Only)
                                                                                              tons
                                                                                              years
                                                                                              (% degraded)
                                                                                              Btu/W-hr
       Amps
       Volts
Amps
Volts
                                   Amps
                                   Volts
                                                                                     3-Phase
                                                                                       1.73
                                                                                        1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
1.1
2.7
1.3
1.5
1.6
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
199
199
t Measurment
10
74
54
50
85

94%
87%
5
77
5.60
12.2 2
15.9 2
F
F
%
%
Tons
F
kW
CU Capacity Estimates
78 F
102 F
66 in
30 in
13.8sq-ft
1351
0.77 kg/sec
2.92 Tons
7.61 EER
4 0.99
2 0.70
299 K
312 K
HVAC Data Sheet
Page 1 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                          Granite Quarry, NC
                                                                                                                      SS-3

-------
                           Post-Ad si I HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Lennox
HS290609Y
S801M 14822
SS
2001
Granite Quarry
SS-3
17.3 Al
208 V(
0.95
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.9
208
0.7
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:             0

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                         Power supply:
                         Phase adjustment:
                         Fan quantity:

                   5.9   kW
                   0.28   kW
                   0.00   kW
                   6.19   kW-Condensing side only
                                     0.0%   Performance Degradation
                                                            NA
                                                            9.7
                                                            5.00
                                                             3
                                                            0%
                                                            9.8
                                                            1.23
                                                                                              Btu/W-hr  (CU Only)
                                                                                              Btu/W-hr  (CU Only)
                                                                                              tons
                                                                                              years
                                                                                              (% degraded)
                                                                                              Btu/W-hr
       Amps
       Volts
Amps
Volts
                                   Amps
                                   Volts
                                                                                     3-Phase
                                                                                       1.73
                                                                                        1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.9
6.2
6.8
5.6
6.1
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
197
200
t Measurment
10
70
50
50
85



5
92

13.7 2
18.5 2
F
F
%
%
Tons
F
kW
CU Capacity Estimates
92 F
121 F
66 in
30 in
13.8sq-ft
5053
2.86 kg/sec
13. 19 Tons
30.43 EER
6 0.97
6 0.70
306 K
323 K
HVAC Data Sheet
Page 2 of 3
                                                                                                        EPA Adsil Evaluation
                                                                                                          Granite Quarry, NC
                                                                                                                     SS-3

-------
    Granite Quarry
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-3   Summary
                         9.7 BTU/W-h
                       1351 CFM (Measured)
                        5.00 tons
                        5.00 tons
                       13.75 sq-ft
                        9.12 pre	9.79 post
Equipment age
3 years
Test Date
24-May

HVAC Service Assistant

OAT
77

Post Adsil Measurements
16-Jun

92

EWB
61


61

El
94%


NA

Cl
87%


NA

EER
9.1


NA

kW
5.60


NA

Physical Power and Capacity measurments
Cond Air, deg F
inlet
78


92

exhaust
102


121

Cond Air
AT(K)
13.3


16.1

kW
4.6


5.2

(kg/sec)
0.77


2.86


tons
2.92


13.19


EER
7.61


30.43

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
5.60
4.35
9.1
NA
NA
NA
CU
4.6
2.92
7.61
5.2
13.19
30.43
Lit
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
NA
NA
NA
NA
NA
NA
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
NA
NA
NA
NA
NA
NA
CU
NA
NA
NA
NA
NA
NA
Literature
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


NA


NA
Predicted/CU





-
Predicted/
Original


NA


NA
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
9.1
NA
NA
NA
NA
Condenser Test
7.61
30.43
NA
NA
75.0%
Spreadsheet
9.1
9.8
NA
NA
6.8%
             Weighted Average   NA
                                                374.9%
                                                                34.2%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                        EPA Adsil Evaluation
                                                                                                                                         Granite Quarry, NC
                                                                                                                                                    SS-3

-------
                           Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Lennox
HS29-653


5895D63302
SS
1995
Granite Qu;
SS-2
17.3
208
0.95

jrry
Ai
V(
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.90
208
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

1



1
0.5
0.5




0.05






X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    5.9    kW
                   0.28    kW
                   0.00    kW
                   6.19    kW-Condensing side only
                                     7.7%   Performance Degradation
                                                             NA
                                                             9.7
                                                            5.00
                                                             9
                                                                                       1.40
                                                                                              Btu/W-hr  (CU Only)
                                                                                              Btu/W-hr  (CU Only)
                                                                                              tons
                                                                                              years
                                                                                              (% degraded)
                                                                                              Btu/W-hr
       Amps
       Volts
Amps
Volts
                                   Amps
                                   Volts
                                                                                     3-Phase
                                                                                       1.73
                                                                                        1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
0.9
1.0
2.0
2.4
1.6
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
202
201
t Measurment
10
74
54
50
85

82%
76%
5
77
5.70
14.9 3
14.1 1
F
F
%
%
Tons
F
kW
CU Capacity Estimates
78 F
98 F
66 in
30 in
13.8sq-ft
1299
0.74 kg/sec
2.34 Tons
6.24 EER
0 0.99
5 0.53
299 K
310 K
HVAC Data Sheet
Page 1 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                              Granite Quarry
                                                                                                                      SS-2

-------
                           Post-Ad si I HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Lennox
HS29-653


5895D63302
SS
1995
Granite Qu;
SS-2
17.3
208
0.95

jrry
Ai
V(
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.9
208
0.7
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:             0

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                         Power supply:
                         Phase adjustment:
                         Fan quantity:

                   5.9   kW
                   0.28   kW
                   0.00   kW
                   6.19   kW-Condensing side only
                                     0.0%   Performance Degradation
                                                            NA
                                                            9.7
                                                            5.00
                                                             9
                                                            0%
                                                            9.2
                                                            1.30
                                                                                              Btu/W-hr  (CU Only)
                                                                                              Btu/W-hr  (CU Only)
                                                                                              tons
                                                                                              years
                                                                                              (% degraded)
                                                                                              Btu/W-hr
       Amps
       Volts
Amps
Volts
                                   Amps
                                   Volts
                                                                                     3-Phase
                                                                                       1.73
                                                                                        1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.7
6.1
7.7
7.5
6.8
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
198
200
t Measurment
10
70
50
50
85

101%
105%
5
94
6.20
17.1 3
17.6 2
F
F
%
%
Tons
F
kW
CU Capacity Estimates
94 F
120 F
66 in
30 in
13.8sq-ft
5569
3.15 kg/sec
13.03 Tons
28.96 EER
4 0.99
0 0.58
308 K
322 K
HVAC Data Sheet
Page 2 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                             Granite Quarry
                                                                                                                     SS-2

-------
    Granite Quarry
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-2   Summary
                         9.7 BTU/W-h
                       1299 CFM (Measured)
                        5.00 tons
                        5.00 tons
                       13.75 sq-ft
                        8.60 pre	9.23 post
Equipment age
9 years
Test Date
24-May

HVAC Service Assistant

OAT
77

Post Adsil Measurements
16-Jun

94

EWB
61


61

El
82%


101%

Cl
76%


105%

EER
7.9


9.8

kW
5.70


6.20

Physical Power and Capacity measurments
Cond Air, deg F
inlet
78


94

exhaust
98


120

Cond Air
AT(K)
11.1


14.4

kW
4.5


5.4

(kg/sec)
0.74


3.15


tons
2.34


13.03


EER
6.24


28.96

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
5.70
3.80
7.9
6.20
5.25
9.8
CU
4.5
2.34
6.24
5.4
13.03
28.96
Lit
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
NA
NA
NA
NA
NA
NA
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
NA
NA
NA
NA
NA
NA
CU
NA
NA
NA
NA
NA
NA
Literature
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU





-
Predicted/SA


NA


NA
Predicted/CU





-
Predicted/
Original


NA


NA
                          EER Changes (Ambient Condions)

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
7.9
9.8
7.9
9.8
18.8%
Condenser Test
6.24
28.96
NA
NA
78.5%
Spreadsheet
8.6
9.2
NA
NA
6.8%
             Weighted Average   94.1%
                                                 392.3%
                                                                 34.2%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                        EPA Adsil Evaluation
                                                                                                                                             Granite Quarry
                                                                                                                                                     SS-2

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Goodman
CPKE36-18
9712425279
SS
1997
Concord City Hall
SS-5
17.3 Am|
208 Volt
0.95
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1.80
208
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

0.8
0.2


1

0.7
0.3





1




X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    3.4    kW
                   0.26   kW
                   0.00   kW
                   3.68   kW-Condensing side only
                                     16.9%  Performance Degradation
                                                             9.0
                                                             9.0
                                                            2.75
                                                              7
                                                            17%
                                                             7.5
                                                            1.60
                                                           Btu/W-hr  (CU Only)
                                                           Btu/W-hr  (CU Only)
                                                           tons
                                                           years
                                                           (% degraded)
                                                           Btu/W-hr
Amps
Volts
Amps
Volts
                                                           1-Phase
                                                              1
                                                              1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.7
6.4
7.2
5.1
6.1
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
120
118
t Measurment
10
74
54
50
85

101%
93%
3
88
3.40
13.8 1.
14.1 1
F
F
%
%
Tons
F
kW
CU Capacity Estimates
89 F
101 F
86 in
23 in
13.7sq-ft
5027
2.85 kg/sec
5.43 Tons
23.44 EER
58 0.97
2 0.72
305 K
311 K
HVAC Data Sheet
Page 1 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                        Concord, NC City Hall
                                                                                                                      SS-5

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Goodman
CPKE36-18
9712425279
SS
1997
Concord City Hall
SS-5
17.3 Am|
208 Volt
0.95
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1 .8
208
0.7
Evaporator fan data (if applicable)
Full load Amps:               0
Nameplate Voltage:            0
Adjust FLA to RLA:             0

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
Amps             Power supply:
Volts              Phase adjustment:
                  Fan quantity:
Amps             Power supply:
Volts              Phase adjustment:
                  Fan quantity:

            3.4   kW
            0.26   kW
            0.00   kW
            3.68   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                     9.0
                                                     9.0
                                                     2.75
                                                      7
                                                     0%
                                                     8.7
                                                     1.38
                                                                   Btu/W-hr  (CU Only)
                                                                   Btu/W-hr  (CU Only)
                                                                   tons
                                                                   years
                                                                   (% degraded)
                                                                   Btu/W-hr
                                                   1-Phase
                                                      1
                                                      1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
7.6
6.6
8.0
7.6
7.5
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
120
119
t Measurment
10
74
54
50
85

93%
88%
3
87
3.40
14.3 1.
14.4 1.
F
F
%
%
Tons
F
kW
CU Capacity Estimates
87 F
99 F
86 in
23 in
13.7sq-ft
6140
3.48 kg/sec
6.63 Tons
27.72 EER
64 0.96
23 0.72
304 K
310 K
HVAC Data Sheet
Page 2 of 3
                                                                                                 EPA Adsil Evaluation
                                                                                                 Concord, NC City Hall
                                                                                                              SS-5

-------
    Concord City Hall
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-5 Summary
                       9.0 BTU/W-h
                      5027 CFM (Measured)
                      2.75 tons
                      3.00 tons
                     13.74sq-ft
                      7.48 pre	8.70 post
Equipment age
                                                                   7 Years
Test Date
24-May

HVAC Service Assistant

OAT
88

Post Adsil Measurements
16-Jun

87

EWB
61


61

El
101%


93%

Cl
93%


88%

EER
9.1


8.3

kW
3.12


3.12

Physical Power and Capacity measurments
Cond Air, deg F
inlet
89


87

exhaust
101


99

Cond Air
AT(K)
6.7


NA

kW
2.78


NA

(kg/sec)
2.85


3.48


tons
5.43


6.63


EER
NA


NA

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
3.12
2.56
9.1
3.12
2.42
8.3
CU
2.78
5.43
NA
NA
6.63
NA
Lit
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
NA
NA
NA
NA
NA
NA
Condensing Unit Summary - ARI Conditions
Test Data
SA
NA
NA
NA
NA
NA
NA
CU
NA
NA
NA
NA
NA
NA
Literature
NA
NA
NA
NA
NA
NA
Percent Difference
SA/Lit
NA
NA
NA
NA
NA
NA
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


NA


NA
Predicted/CU


NA


NA
Predicted/
Original


NA


NA
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
9.1
8.3
9.1
8.3
-7.9%
Condenser Test
NA
NA
NA
NA
NA
Spreadsheet
7.48
8.70
7.48
8.70
16.4%
             Weighted Average  -23.8%
                                              NA
                                                                49.1%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                      EPA Adsil Evaluation
                                                                                                                                     Concord, NC City Hall
                                                                                                                                                   SS-5

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
38CK036
3993E06985
Split System
1993
Concord City Hall
SS-4
8.9 Ami
230 Volt
0.93
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1 .40
230
0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
        Amps              Power supply:
        Volts              Phase adjustment:
                          Fan quantity:
        Amps              Power supply:
        Volts              Phase adjustment:
                          Fan quantity:

                    3.3    kW
                    0.23   kW
                    0.00   kW
                    3.52   kW - Condensing side only
                                      6.7%  Performance Degradation
                                                              8.0
                                                              8.0
                                                             2.35
                                                              11
                                                              7%
                                                              7.0
                                                             1.70
                                                                    Btu/W-hr  (CU Only)
                                                                    Btu/W-hr  (CU Only)
                                                                    tons
                                                                    years
                                                                    (% degraded)
                                                                    Btu/W-hr
                                                            3-phase
                                                             1.73
                                                               1
1-Phase
   1
   1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.5
5.5
5.5
7.6
6.0
0.95
0.05
0.8
0.05
0.2
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
204
206
t Measurment
10
74
54
50
85

95%
82%
3
93
3.20
7.5 0.
8.35 1.
F
F
%
%
Tons
F
kW
CU Capacity Estimates
90 F
102 F
62 in
26 in
11.2sq-ft
4047
2.29 kg/sec
4.37 Tons
19.86 EER
0.60 kW/Ton
89 0.58
75 1 .00
305 K
312 K
HVAC Data Sheet
Page 1 of 3
                                                                                                          EPA Adsil Evaluation
                                                                                                          Concord, NC City Hall
                                                                                                                        SS-4

-------
                           Post-Ad si I HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
38CK036
3993E06985
Split System
1993
Concord City Hall
SS-4
8.9 Ami
230 Volt
0.93
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                            1.4     Amps             Power supply:
                            230     Volts              Phase adjustment:
                            0.7                       Fan quantity:
                                                                                         8.0
                                                                                         8.0
                                                                                        2.35
                                                                                         11
                                                                                         0%
                                                                                         7.5
                                                                                        1.60
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
            New
            Average
            Fair
            Poor
Coil Cleanliness
            Coated
            Clean
            Dirty
            Clogged
            Plugged
Fin Condition
            Like New
            Some Bent
            Smashed
            Dull/rough
            Corroded
            Pitted
            Flaking
Fin-Tube Attachment
            Like New
            Corrosion
            Some Loose
            Many Loose
                                   Amps             Power supply:
                                   Volts              Phase adjustment:
                                                     Fan quantity:

                                               3.3   kW
                                               0.23   kW
                                               0.00   kW
                                               3.52   kW - Condensing side only
                                      0.0%  Performance Degradation
                                                                                       3-phase
                                                                                        1.73
                                                                                          1
1-Phase
   1
   1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
7.5
8.2
8.2
9.0
8.2
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
206
208
t Measurment
10
74
54
50
85

96%
84%
3
89
3.30
7.5 0
8.1 1
F
F
%
%
Tons
F
kW
CU Capacity Estimates
90 F
99 F
62 in
26 in
11.19sq-ft
5524
3.13 kg/sec
4.47 Tons
20.65 EER
0.58 kW/Ton
9 0.59
7 1.00
305 K
310 K
HVAC Data Sheet
Page 2 of 3
                                                                                                                                     EPA Adsil Evaluation
                                                                                                                                     Concord, NC City Hall
                                                                                                                                                   SS-4

-------
    Concord City Hall
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-4 Summary
                       8.0 BTU/W-h
                      4047 CFM (Measured)
                      2.35 tons
                      3.00 tons
                     11.19 sq-ft
                      7.05 pre	7.49 post
Equipment age
                                                                  11 Years
Test Date
24-May

HVAC Service Assistant

OAT
93

Post Adsil Measurements
16-Jun

89

ST-SH
37


31

El
95%


96%

Cl
82%


84%

EER
8.1


8.0

kW
2.51


2.58

Physical Power and Capacity measurments
Cond Air, deg F
inlet
90


90

exhaust
102


99

Cond Air
AT(K)
6.7


5.0

kW
2.64


2.6

(kg/sec)
2.29


3.13


tons
4.37


4.47


EER
19.86


20.65

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
2.51
2.03
8.1
2.58
1.90
8.0
CU
2.64
4.37
19.86
2.6
4.47
20.65
Lit
3.49
2.48
8.51
3.25
2.26
8.34
Percent Difference
SA/Lit
72%
82%
95%
80%
84%
96%
CU/Lit
76%
177%
233%
80%
198%
248%
SS/Lit
97%
91%
82%
97%
91%
87%
Condensing Unit Summary - ARI Conditions
Test Data
SA
2.6
2.1
8.2
2.9
2.2
8.2
CU
2.7
4.6
20.0
2.9
5.1
21.2
Literature
3.61
2.58
8.58
3.61
2.58
8.58
Percent Difference
SA/Lit
72%
82%
95%
80%
84%
96%
CU/Lit
76%
177%
233%
80%
1 98%
248%
SA/CU
95%
46%
41%
99%
42%
39%
Predicted/SA


86%

-
86%
Predicted/CU


35%

-
33%
Predicted/
Original


82%

-
87%
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
8.1
8.0

7.6
7.7
1.1%
Condenser Test
19.86
20.65

18.70
19.83
6.1%
Spreadsheet
7.05
7.49

7.05
7.49
6.3%
             Weighted Average    3.2%
                                                  18.3%
                                                                18.8%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                      EPA Adsil Evaluation
                                                                                                                                     Concord, NC City Hall
                                                                                                                                                   SS-4

-------
                              Pre-Adsil  HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
           Carrier                        Published EER:
           38CKC048-56                   Calculated EER:
           2802E15220                    Nominal Capacity:
           Split System                    Age
           2002                          Coil Conditon
           Concord City Hall                Present Condition EER
           SS-3                          kW/ton
               14.1    Amps              Power supply:
               208    Volts               Phase adjustment:
               0.78                       Compressor quantity:
               1.40    Amps              Power supply:
               208    Volts               Phase adjustment:
               0.70                       Fan quantity:
  11.1
  11.1
  3.83
   2
  5%
  10.8
  1.11
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
3-phase
  1.73
   1
1-Phase
   1
   1
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessment
Overall Unit Condition
                 New
Coil Cleanliness
Fin Condition
Average
Fair
Poor

Coated
Clean
Dirty
Clogged
Plugged
                 Like New
                 Some Bent
                 Smashed
                 Dull/rough
                 Corroded
                 Pitted
                 Flaking
Fin-Tube Attachment
                 Like New
                 Corrosion
                 Some Loose
                 Many Loose
Tubes
                 Clean Cu
                 Corrosion
                 Pitting
                 Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
6.4
6.8
6.1
5.7
6.250
                      Amps              Power supply:
                      Volts               Phase adjustment:
                                         Fan quantity:

                                   3.9    kW
                                  0.20   kW
                                  1.00   kW (From Product Data)
                                  4.14   kW - Condensing side only
                                         5.0%   Performance Degradation
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
207
208
t Measurment
10





96%
90%
4
91
4.60
11.1 1
12.6 2
F
F
%
%
Tons
F
kW
CU Capacity Estimates
91 F
109 F
61 in
25 in
10.6sq-ft
3971
2.25 kg/sec
6.43 Tons
21. 44 EER
1 0.48
5 1.00
306 K
316 K
HVAC Data Sheet
Page 1 of 3
                                                                                                                                     EPA Adsil Evaluation
                                                                                                                                     Concord, NC City Hall
                                                                                                                                                   SS-3

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
38CKC048-56
2802E15220
Split System
2002
Concord City Hall
SS-3
14.1 Ami
208 Volt
0.775
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
1 .4
208
0.7
Evaporator fan data (if applicable)
Full load Amps:               0
Nameplate Voltage:            0
Adjust FLA to RLA:             0

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1





0
0

0
0
0

X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
Amps             Power supply:
Volts              Phase adjustment:
                  Fan quantity:
Amps             Power supply:
Volts              Phase adjustment:
                  Fan quantity:

            3.9   kW
            0.20   kW
            1.00   kW (From Product Data)
            4.14   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                     11.1
                                                     11.1
                                                     3.83
                                                      2
                                                     0%
                                                     11.3
                                                     1.06
                                                                   Btu/W-hr  (CU Only)
                                                                   Btu/W-hr  (CU Only)
                                                                   tons
                                                                   years
                                                                   (% degraded)
                                                                   Btu/W-hr
                                                   3-phase
                                                     1.73
                                                      1
1-Phase
   1
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
6.8
7.2
7.0
5.8
6.7
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
208
206
t Measurment
10
74
54
50
85

90%
79%
3
89
4.27
10.6
11.8 2
F
F
%
%
Tons
F
kW
CU Capacity Estimates
90 F
106 F
61 in
25 in
10.6sq-ft
4257
2.41 kg/sec
6.13 Tons
21. 64 EER
0.45
4 0.99
305 K
314 K
HVAC Data Sheet
Page 2 of 3
                                                                                                                                    EPA Adsil Evaluation
                                                                                                                                    Concord, NC City Hall
                                                                                                                                                 SS-3

-------
    Concord City Hall
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-3 Summary
                     11.12 BTU/W-h
                      3971 CFM (Measured)
                      3.83 tons
                      4.00 tons
                     10.59 sq-ft
                     10.77
Equipment age
                                                                   2 Years
Test Date
24- May

HVAC Service Assistant

OAT
91

Post Adsil Measurements
15-Jun

89

EWB
57


57

El
96%


90%

Cl
90%


79%

EER
10.3


10.0

kW
4.40


4.08

Physical Power and Capacity measurments
Cond Air, deg F
inlet
91


90

exhaust
109


106

Cond Air
AT(K)
10.0


8.9

kW
3.6


3.4

(kg/sec)
2.25


2.41


tons
6.43


6.13


EER
21.44


21.64

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
4.40
3.07
10.3
4.08
2.72
10.0
cu
3.6
6.43
21.44
3.4
6.13
21.64
Lit
3.82
3.41
10.72
3.73
3.44
11.06
Percent Difference
SA/Lit
115%
90%
96%
109%
79%
90%
CU/Lit
94%
189%
200%
91%
178%
196%
SS/Lit
100%
100%
97%
100%
100%
102%
Condensing Unit Summary - ARI Conditions
Test Data
SA
4.8
3.4
10.7
4.5
3.0
10.0
CU
3.9
7.2
22.2
3.8
6.8
21.8
Literature
4.13
3.83
11.12
4.13
3.83
11.12
Percent Difference
SA/Lit
115%
90%
96%
109%
79%
90%
CU/Lit
94%
189%
200%
91%
178%
1 96%
SA/CU
122%
48%
48%
120%
44%
46%
Predicted/SA


101%

-
108%
Predicted/CU


48%

-
50%
Predicted/
Original


97%

-
102%
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
10.29
9.95

10.67
10.01
-6.3%
Condenser Test
21.44
21.64

22.24
21.75
-2.2%
Spreadsheet
10.77
11.32

10.77
11.32
5.1%
             Weighted Average  -25.0%
                                                                20.4%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                                                   EPA Adsil Evaluation
                                                                                                                                                                  Concord, NC City Hall
                                                                                                                                                                                SS-3

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
38AK007501
1099G00176
Split System
1999
Concord City Hall
SS-2
19.0 Am|
208 Volt
0.90
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      CoilConditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
2.80     Amps              Power supply:
208     Volts              Phase adjustment:
0.70                       Fan quantity:
                                                             10.5
                                                             10.5
                                                             5.71
                                                              5
                                                             6%
                                                             9.8
                                                             1.22
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
                                                            3-phase
                                                             1.73
                                                               1
1-Phase
   1
   1
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:           0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
        Amps              Power supply:
        Volts              Phase adjustment:
                          Fan quantity:

                    6.1    kW
                    0.41   kW
                    0.00   kW
                    6.53   kW - Condensing side only
                                      5.7%  Performance Degradation
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
5.0
5.0
5.7
5.7
5.35
0.9
0.1
0.95
0.05
0.05
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
205
207
t Measurment
10
74
54
50
85

90%
91%
6
87
7.30
17.8 2
18.9 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
89 F
112 F
64 in
28 in
12.4sq-ft
3995
2.26 kg/sec
8.27 Tons
17.11 EER
0.70 kW/Ton
0 0.55
8 0.99
305 K
318 K
HVAC Data Sheet
Page 1 of 3
                                                                                                                                      EPA Adsil Evaluation
                                                                                                                                     Concord, NC City Hall
                                                                                                                                                   SS-2

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
38AK007501
1099G00176
Split System
1999
Concord City Hall
SS-2
19 Ami
208 Volt
0.895
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     CoilConditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                            2.8     Amps              Power supply:
                            208     Volts              Phase adjustment:
                            0.7                       Fan quantity:
                                                                                        10.5
                                                                                        10.5
                                                                                        5.71
                                                                                         5
                                                                                        0%
                                                                                        10.4
                                                                                        1.15
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
            New
            Average
            Fair
            Poor
Coil Cleanliness
            Coated
            Clean
            Dirty
            Clogged
            Plugged
Fin Condition
            Like New
            Some Bent
            Smashed
            Dull/rough
            Corroded
            Pitted
            Flaking
Fin-Tube Attachment
            Like New
            Corrosion
            Some Loose
            Many Loose
                                   Amps             Power supply:
                                   Volts              Phase adjustment:
                                                     Fan quantity:

                                               6.1   kW
                                               0.41   kW
                                               0.00   kW
                                               6.53   kW - Condensing side only
                                     0.0%  Performance Degradation
                                                                                       3-phase
                                                                                        1.73
                                                                                          1
1-Phase
   1
   1
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
Average
ft/sec
10.0
10.2
10.1
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
205
207
t Measurment
10
74
54
50
85

95%
90%
6
92
6.90
17.4 2
18.8 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
91 F
112 F
64 in
28 in
12.44sq-ft
7541
4.27 kg/sec
14.25 Tons
28.99 EER
0.41 kW/Ton
0 0.55
9 0.99
306 K
318 K
HVAC Data Sheet
Page 2 of 3
                                                                                                                                      EPA Adsil Evaluation
                                                                                                                                     Concord, NC City Hall
                                                                                                                                                   SS-2

-------
    Concord City Hall
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-2 Summary
                      10.5 BTU/W-h
                      3995 CFM (Measured)
                      5.71 tons
                      6.00 tons
                     12.44 sq-ft
                      9.84 pre	10.39 post
Equipment age
                                                                   5 Years
Test Date
24-May

HVAC Service Assistant

OAT
87

Post Adsil Measurements
16-Jun

92

ST-SH
39


40

El
90%


95%

Cl
91%


90%

EER
10.4


10.4

kW
6.95


6.56

Physical Power and Capacity measurments
Cond Air, deg F
inlet
89


91

exhaust
112


112

Cond Air
AT(K)
12.8


11.7

kW
5.8


5.9

(kg/sec)
2.26


4.27


tons
8.27


14.25


EER
17.11


28.99

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
6.95
5.39
10.4
6.56
5.25
10.4
CU
5.8
8.27
17.11
5.9
14.25
28.99
Lit
6.17
5.92
11.50
6.42
5.83
10.91
Percent Difference
SA/Lit
112%
91%
90%
102%
90%
95%
CU/Lit
94%
140%
149%
92%
244%
266%
SS/Lit
100%
100%
94%
100%
100%
99%
Condensing Unit Summary - ARI Conditions
Test Data
SA
7.3
5.2
9.4
6.7
5.1
10.0
CU
6.1
8.0
15.6
6.0
13.9
27.8
Literature
6.53
5.71
10.48
6.53
5.71
10.48
Percent Difference
SA/Lit
112%
91%
90%
102%
90%
95%
CU/Lit
94%
140%
149%
92%
244%
266%
SA/CU
120%
65%
61%
111%
37%
36%
Predicted/SA


104%

-
99%
Predicted/CU


63%

-
35%
Predicted/
Original


94%

-
99%
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
10.4
10.4

9.4
10.0
5.6%
Condenser Test
17.11
28.99

15.61
27.88
78.6%
Spreadsheet
9.84
10.39

9.84
10.39
5.6%
             Weighted Average   33.3%
                                                                33.9%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                      EPA Adsil Evaluation
                                                                                                                                     Concord, NC City Hall
                                                                                                                                                   SS-2

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
38ARZ007-501
4302G30009
Split System
2002
Concord City Hall
SS-1
19.1 Ami
208 Volt
0.78
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                           0.90    Amps
                           208    Volts
                           0.70
Evaporator fan data (if applicable)
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
                                   Amps
                                   Volts
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

1




0.75
0.25




0.1

0.75




X




X



5.7%
0
1
5
12
25
0
25
50
100
0
25
50
25
35
45
60
0
10
25
50
                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
      Power supply:
      Phase adjustment:
      Fan quantity:
      Power supply:
      Phase adjustment:
      Fan quantity:

5.3   kW
0.26   kW
0.00   kW
5.59   kW - Condensing side only
                                            Performance Degradation
                                                                                       11.8
                                                                                       11.8
                                                                                       5.48
                                                                                         2
                                                                                        6%
                                                                                       11.4
                                                                                       1.06
                                                Btu/W-hr  (CU Only)
                                                Btu/W-hr  (CU Only)
                                                tons
                                                years
                                                (% degraded)
                                                Btu/W-hr
                                                                                      3-phase
                                                                                       1.73
                                                                                         1
1-Phase
   1
   2
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
6.1
3.7
4.1
4.9
4.700
0
1
0
0
0
0
0
6.25
0
0
0
0
2.5
0
18.75
0
0
0
0
0
0
0
0
0
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
208
204
t Measurment
10
74
54
50
85

96%
92%
6
85
6.90
18.1 1
16.4 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
87 F
96.5 F
in
in
29.2 sq-ft
8234
4.66 kg/sec
7.04 Tons
16.25 EER
0.74 kW/Ton
9 0.51
3 1.00
304 K
309 K
HVAC Data Sheet
Page 1 of 3
                                                                                                                                    EPA Adsil Evaluation
                                                                                                                                   Concord, NC City Hall
                                                                                                                                                 SS-1

-------
                           Post-Ad si I HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
38ARZ007-501
4302G30009
Split System
2002
Concord City Hall
SS-1
19.1 Ami
208 Volt
0.775
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                            0.9     Amps             Power supply:
                            208     Volts              Phase adjustment:
                            0.7                       Fan quantity:
                                                                                        11.8
                                                                                        11.8
                                                                                        5.48
                                                                                         2
                                                                                        0%
                                                                                        12.0
                                                                                        1.00
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
Evaporator fan data (if applicable)
Full load Amps:                0
Nameplate Voltage:            0
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coil Assessment
Overall Unit Condition
            New
            Average
            Fair
            Poor
Coil Cleanliness
            Coated
            Clean
            Dirty
            Clogged
            Plugged
Fin Condition
            Like New
            Some Bent
            Smashed
            Dull/rough
            Corroded
            Pitted
            Flaking
Fin-Tube Attachment
            Like New
            Corrosion
            Some Loose
            Many Loose
                                   Amps             Power supply:
                                   Volts              Phase adjustment:
                                                     Fan quantity:

                                               5.3   kW
                                               0.26   kW
                                               0.00   kW
                                               5.59   kW - Condensing side only
                                      0.0%  Performance Degradation
                                                                                       3-phase
                                                                                        1.73
                                                                                          1
1-Phase
   1
   2
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
6.6
7.2
6.8
6.8
6.9
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
Efficiency
209
206
t Measurment
10
74
54
50
85

103%
92%
6
88
6.50
17.3 1
15.5 3
F
F
%
%
Tons
F
kW
CU Capacity Estimates
89 F
100 F
0 in
0 in
29.20 sq-ft
12001
6.80 kg/sec
11. 88 Tons
29.09 EER
0.41 kW/Ton
7 0.48
2 1.00
305 K
311 K
HVAC Data Sheet
Page 2 of 3
                                                                                                                                     EPA Adsil Evaluation
                                                                                                                                    Concord,  NC City Hall
                                                                                                                                                   SS-1

-------
    Concord City Hall
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
SS-1 Summary
                      11.8 BTU/W-h
                      8234 CFM (Measured)
                      5.48 tons
                      6.00 tons
                     29.20 sq-ft
                     1135 pre	12.01 post
Equipment age
                                                                   2 Years
Test Date
24-May

HVAC Service Assistant

OAT
85

Post Adsil Measurements
16-Jun

88

ST-SH
35


37

El
96%


103%

Cl
92%


92%

EER
12.4


13.0

kW
6.31


5.94

Physical Power and Capacity measurments
Cond Air, deg F
inlet
87


89

exhaust
96.5


100

Cond Air
AT(K)
5.3


6.1

kW
5.2


4.9

(kg/sec)
4.66


6.80


tons
7.04


11.88


EER
16.25


29.09

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
6.31
4.86
12.4
5.94
4.96
13.0
CU
5.2
7.04
16.25
4.9
11.88
29.09
Lit
4.90
5.28
12.93
5.11
5.39
12.65
Percent Difference
SA/Lit
129%
92%
96%
116%
92%
103%
CU/Lit
106%
133%
126%
96%
220%
230%
SS/Lit
100%
100%
96%
100%
100%
102%
Condensing Unit Summary - ARI Conditions
Test Data
SA
7.2
5.0
11.3
6.5
5.0
12.1
CU
5.9
7.3
14.8
5.4
12.1
27.1
Literature
5.59
5.49
11.77
5.59
5.49
11.77
Percent Difference
SA/Lit
129%
92%
96%
116%
92%
103%
CU/Lit
106%
133%
126%
96%
220%
230%
SA/CU
121%
69%
76%
121%
42%
45%
Predicted/SA


100%

-
94%
Predicted/CU


77%

-
42%
Predicted/
Original


96%

-
102%
                                   EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
12.4
13.0

11.3
12.1
7.3%
Condenser Test
16.25
29.09

14.79
27.07
83.0%
Spreadsheet
11.35
12.01

11.35
12.01
5.8%
             Weighted Average   43.8%
                                                 498.1%
                                                                34.9%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                      EPA Adsil Evaluation
                                                                                                                                    Concord,  NC City Hall
                                                                                                                                                  SS-1

-------
                             Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
50TJQ006
1399G20943
Package Heat Pump
1999
Concord City Hall
RTU-3

15.4 Amps
230 Volts
0.81

1.50 Amps
230 Volts
0.70
Evaporator fan data (if applicable)
Full load Amps:               5.90
Nameplate Voltage:            208
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Amps
Volts
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
       Power supply:
       Phase adjustment:
       Fan quantity:

5.0    kW
0.24    kW
0.86    kW
5.20    kW-Condensing side only
                                                      12.0
                                                      12.0
                                                      5.23
                                                       5
                                                      7%
                                                      11.1
                                                      1.08
                                                 Btu/W-hr  (CU Only)
                                                 Btu/W-hr  (CU Only)
                                                 tons
                                                 years
                                                 (% degraded)
                                                 Btu/W-hr
                                                    3-Phase
                                                      1.73
                                                       1
                                                    1-Phase
                                                       1
                                                       1
1-Phase
   1
   1
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
it

X




0.8
0.2




0.1

1




X




X



                                      6.7%   Performance Degradation
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
Average
ft/sec






FLUKE METER MEASUREMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP1
10
74
54
50
85

99%
94%
5
86
5.80



F
F
%
%
Tons
kW
F
F
in
in
sq-ft
kg/sec
Tons
EER
HVAC Data Sheet
Page 1 of 3
                                                                                                    EPA Adsil Evaluation
                                                                                                   Concord, NC City Hall
                                                                                                                RTU-3

-------
                           Post-Ad si I HVAC Data Sheet and  EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
50TJQ006
1 399G20943
Package Heat Pump
1999
Concord City Hall
RTU-3
                          Published EER:
                          Calculated EER:
                          Nominal Capacity:
                          Age
                          CoilConditon
                          Present Condition EER
                          kW/ton
 12.00
 12.0
5.2261
   5
  0%
 11.9
 1.01
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
15.4     Amps              Power supply:
230     Volts              Phase adjustment:
0.81                       Compressor quantity:
    1 .5
    230
    0.7
Evaporator fan data (if applicable)
Full load Amps:               5.9
Nameplate Voltage:           208
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



        Amps              Power supply:
        Volts              Phase adjustment:
                          Fan quantity:
        Amps              Power supply:
        Volts              Phase adjustment:
                          Fan quantity:

                    5.0    kW
                   0.24   kW
                   0.86   kW
                   5.20   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                              3-Phase
                                                                1.73
                                                                 1
1-Phase
   1
   1
                                                              1-Phase
                                                                 1
                                                                 1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
-
-



FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP 1
10
74
54
50
85

104%
101%
5
88
5.60


F
F
%
%
Tons
F
kW
CU Capacity Estimates
F
F
in
in
sq-ft
kg/sec
Tons
EER
HVAC Data Sheet
Page 2 of 3
                                                                                                         EPA Adsil Evaluation
                                                                                                        Concord, NC City Hall
                                                                                                                    RTU-3

-------
    Concord City Hall
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-3 Summary
                        12.0 BTU/W-h
                          -  CFM (Measured)
                        5.23
                        5.00 tons
                          - sq-ft
                       11.14
Equipment age
                                                                    5 Years
Test Date
24-May
HVAC Service Assistant

OAT
86
EWB
62
El
99%
Cl
94%
EER
13.0
kW
6.06
Physical Power and Capacity measurments
Cond Air
inlet

deg F
exhaust

Cond Air
AT(K)

kW

(kg/sec)


tons


EER


Post Adsil Measurements
16-Jun

88


62


104%


101%


13.2


5.85






















Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
6.06
4.69
13.0
5.85
5.00
13.2
CU
NA
NA
NA
NA
NA
NA
Lit
4.58
4.99
13.08
4.69
4.95
12.66
Percent Difference
SA/Lit
132%
94%
99%
125%
101%
1 04%
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
100%
100%
93%
100%
100%
99%
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
6.9
4.9
11.9
6.5
5.3
12.5
CU
NA
NA
NA
NA
NA
NA
Literature
5.23
5.23
12.00
5.23
5.23
12.00
Percent Difference
SA/Lit
132%
94%
99%
125%
101%
1 04%
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


94%

-
89%
Predicted/CU




-

Predicted/
Original


93%

-
99%
                                     EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
13.0
13.2
11.9
12.5
5.1%
Condenser Test
NA
NA
NA
NA
NA
Spreadsheet
11.1
11.9
11.14
11.88
6.6%
               Weighted Average   25.3%
                                                NA
                                                                  33.2%
HVAC Data Sheet
Page 3 of 3
                                                                                                                                   EPA Adsil Evaluation
                                                                                                                                  Concord, NC City Hall
                                                                                                                                              RTU-3

-------
                             Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
50TJQ006
1399G20939
Package Heat Pump
1999
Concord City Hall
RTU-2

15.4 Amps
230 Volts
0.81

1.50 Amps
230 Volts
0.70
Evaporator fan data (if applicable)
Full load Amps:               5.90
Nameplate Voltage:            208
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Amps
Volts
                                                      Published EER:
                                                      Calculated EER:
                                                      Nominal Capacity:
                                                      Age
                                                      Coil Conditon
                                                      Present Condition EER
                                                      kW/ton
                                                      Power supply:
                                                      Phase adjustment:
                                                      Compressor quantity:
                                                      Power supply:
                                                      Phase adjustment:
                                                      Fan quantity:
       Power supply:
       Phase adjustment:
       Fan quantity:

5.0    kW
0.24    kW
0.86    kW
5.20    kW-Condensing side only
                                                      12.0
                                                      12.0
                                                      5.23
                                                       5
                                                      6%
                                                      11.2
                                                      1.07
                                                 Btu/W-hr  (CU Only)
                                                 Btu/W-hr  (CU Only)
                                                 tons
                                                 years
                                                 (% degraded)
                                                 Btu/W-hr
                                                    3-Phase
                                                      1.73
                                                       1
                                                    1-Phase
                                                       1
                                                       1
1-Phase
   1
   1
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
it

X



0.7
0.3




0.5


0.5




X




X



                                      6.2%   Performance Degradation
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
Average
ft/sec






FLUKE METER MEASUREMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP1
10
74
54
50
85

98%
91%
5
86
5.60



F
F
%
%
Tons
kW
F
F
in
in
sq-ft
kg/sec
Tons
EER
HVAC Data Sheet
Page 1 of 3
                                                                                                    EPA Adsil Evaluation
                                                                                                   Concord, NC City Hall
                                                                                                               RTU-2

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
                       Carrier
                       50TJQ006
                       1399G20939
                       Package Heat Pump
                       1999
                       Concord City Hall
                       RTU-2
                          Published EER:
                          Calculated EER:
                          Nominal Capacity:
                          Age
                          CoilConditon
                          Present Condition EER
                          kW/ton
12.0
12.0
5.23
 5
0%
11.9
1.01
Btu/W-hr  (CU Only)
Btu/W-hr  (CU Only)
tons
years
(% degraded)
Btu/W-hr
 15.4    Amps             Power supply:
230.0    Volts              Phase adjustment:
 0.8                       Compressor quantity:
 1.5     Amps             Power supply:
230.0    Volts              Phase adjustment:
 0.7                       Fan quantity:
Evaporator fan data (if applicable)
Full load Amps:               5.9    Amps
Nameplate Voltage:          208.0   Volts
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:

                                               5.0    kW
                                              0.24   kW
                                              0.86   kW
                                              5.20   kW-Condensing side only
                                                                                      3-Phase
                                                                                       1.73
                                                                                         1
                                                                                      1-Phase
                                                                                         1
                                                                                         1
                                                           1-Phase
                                                              1
                                                              1
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1












X




X



                                     0.0%   Performance Degradation
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
-
-



FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP 1
10
74
54
50
85

104%
98%
5
89
5.80


F
F
%
%
Tons
F
kW
CU Capacity Estimates
F
F
in
in
sq-ft
kg/sec
Tons
EER
HVAC Data Sheet
Page 2of 3
                                                                                                          EPA Adsil Evaluation
                                                                                                         Concord, NC City Hall
                                                                                                                     RTU-2

-------
    Concord City Hall
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
RTU-2 Summary
                        12.0 BTU/W-h
                          -  CFM (Measured)
                        5.23
                        5.00 tons
                          - sq-ft
                       11.19
Equipment age
                                                                    5 Years
Test Date
24-May
HVAC Service Assistant

OAT
86
EWB
62
El
98%
Cl
91%
EER
12.8
kW
5.85
Physical Power and Capacity measurments
Cond Air
inlet

deg F
exhaust

Cond Air
AT(K)

kW

(kg/sec)


tons


EER


Post Adsil Measurements

16-Jun
89


62


104%


98%


13.0


6.06






















Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
5.85
4.54
12.8
6.06
4.83
13.0
CU
NA
NA
NA
NA
NA
NA
Lit
4.58
4.99
13.08
4.75
4.93
12.45
Percent Difference
SA/Lit
128%
91%
98%
128%
98%
1 04%
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
100%
100%
93%
100%
100%
99%
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
6.7
4.8
11.8
6.7
5.1
12.5
CU
NA
NA
NA
NA
NA
NA
Literature
5.23
5.23
12.00
5.23
5.23
12.00
Percent Difference
SA/Lit
128%
91%
98%
128%
98%
1 04%
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA


95%

-
90%
Predicted/CU




-

Predicted/
Original


93%

-
99%
                                     EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
12.8
13.0
11.8
12.5
6.1%
Condenser Test
NA
NA
NA
NA
NA
Spreadsheet
11.2
11.9
11.2
11.9
6.1%
               Weighted Average   30.6%
                                                    NA
                                                                  30.7%
HVAC Data Sheet
Page 3of 3
                                                                                                                                   EPA Adsil Evaluation
                                                                                                                                  Concord, NC City Hall
                                                                                                                                              RTU-2

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
50TJQ006
NA
Package Heat Pump
1999
Concord City Hall
RTU-1
    15.4     Amps
    208     Volts
    0.90
    1.50
    208
    0.70
Evaporator fan data (If applicable)
Full load Amps:               5.90
Nameplate Voltage:            208
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Amps
Volts
            Amps
            Volts
                   Published EER:
                   Calculated EER:
                   Nominal Capacity:
                   Age
                   Coll Condlton
                   Present Condition EER
                   kW/ton
                   Power supply:
                   Phase adjustment:
                   Compressor quantity:
Power supply:
Phase adjustment:
Fan quantity:
                   Power supply:
                   Phase adjustment:
                   Fan quantity:

            5.0    kW
            0.22    kW
            0.86    kW
            5.21    kW-Condensing side only
                                   12.0
                                   12.0
                                   5.23
                                    5
                                    2%
                                   11.7
                                   1.03
        Btu/W-hr  (CU Only)
        Btu/W-hr  (CU Only)
        tons
        years
        (% degraded)
        Btu/W-hr
                                  3-Phase
                                   1.73
                                     1
1-Phase
   1
   1
                                  1-Phase
                                     1
                                     1
Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
              2.0%   Performance Degradation
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Number
1
2
3
4
5
Average
ft/sec


-


-
    0.9
    0.35
FLUKE METER MEASUREMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assistar
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP 1
10
74
54
50
85

98%
93%
5
81
5.80



F
F
Tons
kW
F
F
in
in
sq-ft
kg/sec
Tons
EER
HVAC Data Sheet
Page 1of 3
                                                                                                     EPA Adsil Evaluation
                                                                                                    Concord, NC City Hall
                                                                                                                 RTU-1

-------
                            Post-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag

Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:

Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
Carrier
50TJQ006
NA
Package Heat Pump
1999
Concord City Hall
RTU-1
    15.4     Amps
   208.0    Volts
    0.9
Published EER:
Calculated EER:
Nominal Capacity:
Age
Coll Condlton
Present Condition EER
kW/ton
Power supply:
Phase adjustment:
Compressor quantity:
    1.5     Amps               Power supply:
   208.0    Volts               Phase adjustment:
    0.7                        Fan quantity:
Evaporator fan data (If applicable)
Full load Amps:                5.9     Amps
Nameplate Voltage:            208.0    Volts
Adjust FLA to RLA:             0.7
Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions

Condenser Coll Assessment
Overall Unit Condition
             New
             Average
             Fair
             Poor
Coil Cleanliness
             Coated
             Clean
             Dirty
             Clogged
                               Power supply:
                               Phase adjustment:
                               Fan quantity:

                        5.0    kW
                        0.22    kW
                        0.86    kW
                        5.21    kW - Condensing side only
  12.0   Btu/W-hr  (CU Only)
  12.0   Btu/W-hr  (CU Only)
  5.23   tons
   5    years
  0%   (% degraded)
  11.9   Btu/W-hr
  1.01
3-Phase
  1.7
   1
                                  1-Phase
                                     1
                                     1
                                  1-Phase
                                     1.0
                                     1.0
              0.0%   Performance Degradation
             Plugged
Fin Condition
             Like New
             Some Bent
             Smashed
             Dull/rough
             Corroded
             Pitted
             Flaking
Fin-Tube Attachment
             Like New
             Corrosion
             Some Loose
             Many Loose
Tubes
             Clean Cu
             Corrosion
             Pitting
             Leaks
CU Fan CFM Calculation
Number
1
2
3
4
Average
ft/sec
-

-

-
FLUKE METER MEASURMENTS
Y-measurment
Phase Volts Amps kW PF
1
2
3






Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
HVAC Service Assistan
Input SEER
RAT
SAT
RAH
SAH
El
Cl
Input Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Wdth
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency


t Measurment
COMP1
10
74
54
50
85

100%
92%
5
87
5.60


F
F
%
%
Tons
F
kW
CU Capacity Estimates
F - K
F - K
in
in
sq-ft
kg/sec
Tons
EER
HVAC Data Sheet
Page 2of 3
                                                                                                  EPA Adsil Evaluation
                                                                                                  Concord, NC City Hall
                                                                                                              RTU-1

-------
          Concord City Hall  RTU-1 Summary
    EER at ARI Conditions
    Condensing unit CFM
    Nominal Unit Capacity
    Capacity used for SA
    Coil Area
    Predicted EER =
 12.0 BTU/W-h
   - CFM (Measured)
 5.23
 5.00 tons
    - sq-ft
11.65
Equipment age
                                              5 Years
Test Date
24-May
HVAC Service Assistant

OAT
81
EWB
62
El
98%
Cl
93%
EER
14.0
kW
6.06
Physical Power and Capacity measurments
Cond Air, deg F
inlet
NA
exhaust
NA
Cond Air
AT(K)
NA
kW
NA
(kg/sec)
NA

tons
NA

EER
NA

Post Adsil Measurements
16-Jun

87


62


100%


92%


12.9


5.85


NA


NA


NA


NA


NA


NA


NA

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data® Field Conditions
SA
6.06
4.74
14.0
5.85
4.57
12.9
CU
NA
NA
NA
NA
NA
NA
Lit
4.30
5.10
14.25
4.64
4.97
12.87
Percent Difference
SA/Lit
141%
93%
98%
126%
92%
100%
CU/Lit
NA
NA
NA
NA
NA
NA
SS/Lit
100%
100%
97%
100%
100%
99%
Condensing Unit Summary - ARI Conditions
Test Data @ARI
SA
7.4
4.9
11.8
6.6
4.8
12.0
CU
NA
NA
NA
NA
NA
NA
Literature
5.23
5.23
12.00
5.23
5.23
12.00
Percent Difference
SA/Lit
1 41 %
93%
98%
126%
92%
100%
CU/Lit
NA
NA
NA
NA
NA
NA
SA/CU
NA
NA
NA
NA
NA
NA
Predicted/SA
-

99%

-
97%
Predicted/CU
-

-

-

Predicted/
Original
-

97%

-
99%
                                       EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
14.0
12.9
11.8
12.0
2.0%
Condenser Test
NA
NA
NA
NA
NA
Spreadsheet
11.7
11.9
11.7
11.9
1.9%
                Weighted Average
                                   10.2%
                                                      NA
                                                                      9.7%
HVAC Data Sheet
Page 3of 3
                                                                                                            EPA Adsil Evaluation
                                                                                                            Concord, NC City Hall
                                                                                                                        RTU-1

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
50TJQ009-601
4598G30510
Package HP
1998
Concord Admin
RTU-5
7.2 Al
460 V(
0.74
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
0.70     Amps
460     Volts
0.70
Evaporator fan data (if applicable)
Full load Amps:              2.60
Nameplate Voltage:           460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

1




0.85
0.15



0.1
0.05

0.9




X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    8.5    kW
                   0.45   kW
                   0.84   kW
                   8.93   kW - Condensing side only
                                     5.7%   Performance Degradation
                                                     11.3
                                                     11.3
                                                     8.41
                                                      6
                                                     6%
                                                     10.5
                                                     1.14
                                                                   Btu/W-hr  (CU Only)
                                                                   Btu/W-hr  (CU Only)
                                                                   tons
                                                                   years
                                                                   (% degraded)
                                                                   Btu/W-hr
Amps
Volts
                                                   3-phase
                                                     1.73
                                                      2
1-Phase
   1
   2
3-Phase
  1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
5
Average
ft/sec
9.4
9.8
10.0
10.0
9.8
9.8
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
495
495
t Measurement
10
74
54
50
85
Circuit 1
104%
99%
3.5
93
4.00
13.6 3
12.9 6

1 0.46
4 1.00

4 compressors 2
F stages. All 4 on durring
F CU test; two on during
% SA test
%
Tons
F
kW
CU Capacity Estimates
96 F
103 F
72 in
36 in
36.0 sq-ft
21168
11. 99 kg/sec
13.33 Tons
16.84 EER
309 K
313 K
HVAC Data Sheet
Page 1 of 3
                                                                                                  EPA Adsil Evaluation
                                                                                            Concord, NC Admin Building
                                                                                                             RTU-5

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
50TJQ009-601
4598G30510
Package HP
1998
Concord Admin
RTU-5
7.2 Al
460 V(
0.74
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
0.7    Amps
460    Volts
0.7
Evaporator fan data (if applicable)
Full load Amps:               2.6
Nameplate Voltage:            460
Adjust FLA to RLA:             0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                  Power supply:
                  Phase adjustment:
                  Fan quantity:
                         Power supply:
                         Phase adjustment:
                         Fan quantity:

                   8.5   kW
                   0.45   kW
                   0.84   kW
                   8.93   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                     11.3
                                                     11.3
                                                     8.41
                                                      6
                                                     0%
                                                     11.1
                                                     1.08
                                                                   Btu/W-hr  (CU Only)
                                                                   Btu/W-hr  (CU Only)
                                                                   tons
                                                                   years
                                                                   (% degraded)
                                                                   Btu/W-hr
Amps
Volts
                                                   3-phase
                                                     1.73
                                                      2
1-Phase
   1
   2
3-Phase
  1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
10.7
11.5
10.7
10.7
10.9
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3









Delta Measurement
Phase Volts Amps kW PF
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency
495
495
t Measurement
10
74
54
50
85
Circuit 1
104%
96%
3.5
93
4.00
13.6 3
12.9 6

1 0.46
4 1.00

Both circuits on
F durring both tests
F
%
%
Tons
F
kW
CU Capacity Estimates
93 F
106 F
72 in
36 in
36.0 sq-ft
23544
13.33 kg/sec
27.54 Tons
34.79 EER
307 K
314 K
HVAC Data Sheet
Page 2 of 3
                                                                                                  EPA Adsil Evaluation
                                                                                            Concord, NC Admin Building
                                                                                                             RTU-5

-------
         Concord Admin  RTU-5 Summary
    EER at ARI Conditions
    Condensing unit CFM
    Capacity at ARI
    Capacity used for SA
    Coil Area
    Predicted EER =
 11.3 BTU/W-h
21168 CFM (Measured)
 8.41 tons
 3.50 tons
36.00 sq-ft
10.50 pre	11.08 post
Equipment Age
                                             6 Years
Test Date
13-May

HVAC Service Assistant

OAT
93

Post Adsil Measurement
17-Jun

93

EWB
62


62

El
104%


104%

Cl
99%


96%

EER
11.4


11.4

kW
9.62


9.62

Physical Power and Capacity measurments
Cond Air
inlet
96


93

deg F
exhaust
103


106

Cond Air
AT(K)
3.9


7.2

kW
9.5


9.5

(kg/sec)
11.99


13.33


tons
13.33


27.54


EER
16.84


34.79

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
9.62
7.46
11.4
9.62
7.24
11.4
CU
9.5
13.33
16.84
9.5
27.54
34.79
Lit
8.29
7.54
10.92
8.29
7.54
10.92
Percent Difference
SA/Lit
116%
99%
104%
116%
96%
1 04%
CU/Lit
115%
177%
154%
115%
365%
319%
SS/Lit
102%
102%
93%
102%
102%
98%
Condensing Unit Summary - ARI Conditions
Test Data
SA
10.2
8.2
11.7
10.2
7.9
11.7
CU
10.1
14.6
17.4
10.1
30.2
36.0
Literature
8.79
8.26
11.28
8.79
8.26
11.28
Percent Difference
SA/Lit
116%
99%
104%
116%
96%
104%
CU/Lit
1 1 5%
177%
154%
1 1 5%
365%
319%
SA/CU
101%
56%
67%
101%
26%
33%
Predicted/SA


89%

-
89%
Predicted/CU


60%

-
29%
Predicted/
Original


93%

-
98%
                                    EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
11.4
11.4

11.8
11.8
0.0%
Condenser Test
16.84
34.79

17.45
36.04
106.6%
Spreadsheet
10.50
11.08

10.50
11.08
5.6%
            Weighted Average
                                0.0%
                                                  373.0%
                                                                 19.6%
HVAC Data Sheet
Page 3 of 3
                                                                                                             EPA Adsil Evaluation
                                                                                                       Concord, NC Admin Building
                                                                                                                        RTU-5

-------
                            Pre-Adsil HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
50TJQ01 2-601
4598G30510
Package HP
1998
Concord Admin
RTU-7
8.6 Al
460 V(
0.66
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
0.70     Amps
460     Volts
0.70
Evaporator fan data (if applicable)
Full load Amps:               3.40
Nameplate Voltage:           460
Adjust FLA to RLA:            0.70

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt

1




0.8
0.2



1
0.05

0.25




X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                          Power supply:
                          Phase adjustment:
                          Fan quantity:

                    9.0    kW
                   0.45   kW
                   1.09   kW
                   9.43   kW - Condensing side only
                                     2.7%   Performance Degradation
                                                                                        10.6
                                                                                        11.8
                                                                                        9.31
                                                                                         6
                                                                                        3%
                                                                                        11.3
                                                                                        1.06
                                                                   Btu/W-hr  (CU Only)
                                                                   Btu/W-hr  (CU Only)
                                                                   tons
                                                                   years
                                                                   (% degraded)
                                                                   Btu/W-hr
                                   Amps
                                   Volts
                                                                                      3-phase
                                                                                        1.73
                                                                                         2
1-Phase
   1
   2
3-Phase
  1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
10.0
9.6
9.3
9.4
9.6
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3
Delta Measurement
Phase
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency



Volts
493
493
t Measurement
10
74
54
50
85
Circuit 1
82%
85%
5
92
6.20






Amps kW PF
19.4 2
18.4 8

0 0.21
9 0.98

4 compressors 2
F stages. All 4 on durring
F CU test; two on during
% SA test
%
Circu


Tons
F
kW
CU Capacity Estimates
92 F
112. 5 F
61 in
43 in
36.4 sq-ft
20929
11. 85 kg/sec
38.61 Tons
42.51 EER

t2
90%
89%
5 Tons
92 F
6.00 kW
306 K
318 K
HVAC Data Sheet
page 1 of 3
                                                                                                                                    EPA Adsil Evaluation
                                                                                                                              Concord, NC Admin Building
                                                                                                                                                RTU-6

-------
                           Post-Ad si I HVAC Data Sheet and EER Calculation
Manufacturer:
Model Number:
Serial Number
Equipment Type:
Year Manufactured:
Location
Tag
Compressor Data
Running load Amps:
Nameplate Voltage:
Power factor:
Carrier
50TJQ01 2-601
4598G30510
Package HP
1998
Concord Admin
RTU-7
8.6 Al
460 V(
0.656
Condensing Fan Data
Full load Amps:
Nameplate Voltage:
Adjust FLA to RLA:
0.7    Amps
460    Volts
0.7
Evaporator fan data (if applicable)
Full load Amps:               3.4
Nameplate Voltage:           460
Adjust FLA to RLA:            0.7

Calculated compressor load:
Calculated condensing fan load:
Calculated evaporator fan load
Total calculated load for equipment:
Assumptions
Condenser Coil Assessme
Overall Unit Condition
New
Average
Fair
Poor
Coil Cleanliness
Coated
Clean
Dirty
Clogged
Plugged
Fin Condition
Like New
Some Bent
Smashed
Dull/rough
Corroded
Pitted
Flaking
Fin-Tube Attachment
Like New
Corrosion
Some Loose
Many Loose
Tubes
Clean Cu
Corrosion
Pitting
Leaks
nt
X





1




1







X




X



                                                     Published EER:
                                                     Calculated EER:
                                                     Nominal Capacity:
                                                     Age
                                                     Coil Conditon
                                                     Present Condition EER
                                                     kW/ton
                                                     Power supply:
                                                     Phase adjustment:
                                                     Compressor quantity:
                                                     Power supply:
                                                     Phase adjustment:
                                                     Fan quantity:
                         Power supply:
                         Phase adjustment:
                         Fan quantity:

                   9.0   kW
                   0.45   kW
                   1.09   kW
                   9.43   kW - Condensing side only
                                     0.0%   Performance Degradation
                                                                                        10.6
                                                                                        11.8
                                                                                        9.31
                                                                                         6
                                                                                        0%
                                                                                        11.6
                                                                                        1.03
                                                                   Btu/W-hr  (CU Only)
                                                                   Btu/W-hr  (CU Only)
                                                                   tons
                                                                   years
                                                                   (% degraded)
                                                                   Btu/W-hr
                                   Amps
                                   Volts
                                                                                      3-phase
                                                                                        1.73
                                                                                         2
1-Phase
   1
   2
3-Phase
  1.73
   1
CU Fan CFM Calculation
Measurement
Number
1
2
3
4
Average
ft/sec
11.3
11.1
8.4
11.1
10.5
FLUKE METER MEASUREMENTS
Y-measurement
Phase Volts Amps kW PF
1
2
3
Delta Measurement
Phase
1 to 2
2 to 3
TOTAL
HVAC Service Assista
Input SEER
RAT
SAT
RAH
SAH
El
Cl
nput Cap
OAT
Predicted KW
Ambient
CU Exhaust
Coil Length
Coil Width
Area
Measured Fan CFM
Air Mass Flow
Capacity
Efficiency



Volts
495
495
t Measurement
10
74
54
50
85
Circuit 1
92%
92%
5
93
6.00






Amps kW PF
13.6 3
12.9 6

1 0.46
4 1.00

Both circuits on
F durring both tests
F
%
%
Circu


Tons
F
kW
CU Capacity Estimates
93 F
112 F
61 in
43 in
36.4 sq-ft
22897
12.97 kg/sec
39. 15 Tons
49.45 EER

t2
90%
89%
5 Tons
92 F
5.90 kW
307 K
318 K
HVAC Data Sheet
page 2 of 3
                                                                                                                                    EPA Adsil Evaluation
                                                                                                                              Concord, NC Admin Building
                                                                                                                                                RTU-6

-------
          Concord Admin
EER at ARI Conditions
Condensing unit CFM
Capacity at ARI
Capacity used for SA
Coil Area
Predicted EER =
                               RTU-7 Sumary
                                                      11.8 BTU/W-h
                                                    20929 CFM (Measured)
                                                      9.31 tons
                                                     10.00 tons
                                                     36.43 sq-ft
                                                     11.32 pre	11.62 post
Equipment Age
                                                                                                    6 Years
Test Date
13-May

HVAC Service Assistant

OAT
92

Post Adsil Measurement
17-Jun

93

EWB
62


62

El
86%


91%

Cl
87%


91%

EER
9.0


9.4

kW
11.36


11.08

Physical Power and Capacity measurments
Cond Air, deg F
inlet
92


93

exhaust
112.5


112

Cond Air
AT(K)
11.4


10.6

kW
10.9


9.5

(kg/sec)
11.85


12.97


tons
38.61


39.15


EER
42.51


49.45

Condensing Unit Summary - Ambient Conditions
OAT
Pre-Adsil
Post-Adsil

Power (kW)
Capacity (Tons)
EER
Power (kW)
Capacity (Tons)
EER
Test Data
SA
11.36
7.50
9.0
11.08
7.77
9.4
CU
10.9
38.61
42.51
9.5
39.15
49.45
Lit
9.85
8.62
10.50
9.95
8.58
10.35
Percent Difference
SA/Lit
115%
87%
86%
1 1 1 %
91%
91%
CU/Lit
111%
448%
405%
95%
456%
478%
SS/Lit
90%
100%
106%
90%
100%
109%
Condensing Unit Summary - ARI Conditions
Test Data
SA
12.1
8.1
9.1
11.7
8.4
9.7
CU
11.6
41.7
43.0
10.0
42.5
50.8
Literature
10.51
9.31
10.63
10.51
9.31
10.63
Percent Difference
SA/Lit
115%
87%
86%
1 1 1 %
91%
91%
CU/Lit
111%
448%
405%
95%
456%
478%
SA/CU
104%
19%
21%
117%
20%
19%
Predicted/SA


124%
-
-
117%
Predicted/CU


26%
-
-
22%
Predicted/
Original


106%
-
-
109%
                                    EER Changes

Pre-Adsil EER
Post Adsil EER
ARI Adjusted
Pre-Adsil EER
Post Adsil EER
Change
Service Assistant
9.0
9.4

10.2
10.8
5.8%
Condenser Test
42.51
49.45

47.97
56.62
18.0%
Spreadsheet
11.32
11.62

11.32
11.62
2.6%
             Weighted Average   58.1%
                                                   180.4%
                                                                   26.5%
HVAC Data Sheet
page 3 of 3
                                                                                                                                                                      EPA Adsil Evaluation
                                                                                                                                                               Concord, NC Admin Building
                                                                                                                                                                                 RTU-6

-------

-------
       Appendix G
Energy Savings Calculations

-------
Appendix G- Energy Savings Calculations

                         Increase the Life and Performance of Condenser Coils
   The outdoor environment can be harsh on heat transfer surfaces.  The application of the Adsil
   corrosion inhibitor will decrease the environmental damage to the condenser coils.  As such, the life
   and performance of the coils is increased. This protection is easily applied to equipment.

           Facility: SEQLArea
                   150 Units
      ECP Savings:
 Total ECP Savings:
         ECP Cost:
          Payback:
  371.67  Electric Demand kW
  0.00    Equivalent Demand kW
          Demand Cost Savings
          Steam System Therms
          Steam System Cost Savings
          Other Fuels Therms
          Water kgal
          Wastewater kgal
          Maintenance Cost Savings
$36,915
$165,425
  4.48
Total Annual Cost Savings

yrs  (including maint savings)
                              461,440
                               1,574
                              $36,915
        Electric Energy kWh
        Electric Energy MMBtu
        Electric Energy Cost Savings
        Steam System MMBtu
        Other Fuels MMBtu
        Other Fuels Cost Savings
        Water kgal Cost Savings
        Wastewater kgal Cost Savings
1,574   Total Annual MMBtu Savings

4.48    yrs (excluding maint savings)
                                            Calculations
   Assumptions:   This recommendation is applied in the following instances:
                       1) New equipment
                       2) Existing equipment with evidence of minor environmental damage
                       3) Equipment with five years of useful life remaining
                   Use blended utility rate of $0.08 per kWh
                   The protective corrosion inhibitor is MicroGuard (TM) product from Adsil (TM)
                   Charlotte area has 1644 cooling degree days (CDD) per NOAA
                   Full-load equivalent operating hours = FLEOH= 0.8*CDD
                   Decrease in EER is assumed to be both an increase in power consumption
                    and capacity degradation
                   Savings to heat pumps during the heating season are not included
                   Average EER=9.0
                   Average EER gain =12.3%
                      1644
                      1,315
                     $0.000
                    $0.08000
                       0%

 HVAC System Data
 Condensing Unit Data from:
 Condensing Unit Consumption:
 Calculated EER:
          CDD
          FLEOH
          Demand Cost per kW
          Energy Cost per kWh
          Demand Diversity
          SEQL Area
           3393.33   kW
             10.1     Btu/W-hr
                                 Nominal Capacity:   2545.0   tons
                            Present Condition EER:    9.0    Btu/W-hr
                                        kW/ton=      1.33
 EER after coil applications         10.11
 kW/ton after coil applications      1.19
 Demand Consumption=          3021.67
Appendix G
Page 1 of 2

-------
           Facility:
SEQL Area
150 Units
Current Run-time Adjustment Factors
Night Setback:         1.000
FLEOH Conversion:    0.800
 Proposed Run-time Adjustment Factors
 Night Setback:         1.000
 FLEOH Conversion:    0.800
                              Excess Capacity:
                              Weekend Setback:
                              Cooling Set Point:
                              Excess Capacity:
                              Weekend Setback:
                              Cooling Set Point:
                               1.000
                               1.000
                               72.00   Degrees F
                               1.000
                               1.000
                               72.00
                                                                                Degrees F
 Run-time Estimates
 Current condensing unit:
 Proposed condensing unit:
              1,242
              1,242

               kW
                       Current   3393.333
                     Proposed   3021.668
                       Savings ^^7~
hours - annually
hours - annually

           kWh

        4,212,989
        3,751,548
                               461,440
                                          Installation Costs
Nominal capacity:                                     2,545
Cost associated to install coating (parts & labor):           $65
                   Total project cost:                $165,425
                                         tons
                                         per ton (total installed cost)
                                         (vendor quotation)
Appendix G
Page 2 of 2

-------

-------
        Appendix H
Spreadsheet EER Degradation

-------
TABLE H-1  SPREADSHEET EER DEGRADATION COMPARED WITH SERVICE ASSISTANT FOR ALL VALID TESTS
           Site              Unit     Age
           Concord Admin RTU-7    6
         Concord City Hall RTU-2    5
                        RTU-3    5
                        SS-1     2
                        SS-2     5
                        SS-4     11

      Iredell Health Center RTU-1    12
                        RTU-13   12
                        RTU-14   12
                        RTU-3    7
           Locust City Hall SS-2     7
    Monroe Aquatic Center RTU-1    7
                        RTU-2    7
                        RTU-9    7
                        RTU-10   7
                        RTU-13   2
                        RTU-15   2
                        RTU-16   4
               YTC Bid D RTU-1    12
        YTC-Hood Center
                        RTU-6    13
                        RTU-7    13
                        RTU-8    12
                        RTU-9    4
                        HP-1     12
            YTC - Library Unit 1     13
       YTC Student Center RTU-25   13
     YTC Student Services HP-1     13
        YTC Truck School SS-1     15

                 Average
Capacity
9
5
5
5
6
2
3
3
5
3
3
7
7
12
8
21
7
5
4
24
29
24
18
23
3
5
17
5
7
9
Overall Unit Condition
New






























1-9 yrs
























1





10-1 5 yrs





1

1
1
1









1

1
1
1

1
1
1
1
1
>15 yrs






























Coil Cleanliness
Coated

0.7


0.9
1





1













1




Clean
0.8
0.3
0.8
0.75

0.95

0.8
1
0.9
0.9

1
1

1
0.7
1
1





0.9

0.9
1
1
0.75
Dirty
0.2

0.2
0.25
0.1
0.05

0.2

0.1
0.1
0.1


0.3

0.3


1

0.5
0.5
0.25
0.1

0.1


0.25
Clogged














0.7






0.4
0.5
0.75






Plugged





















0.1








Fin Condition
Like New
1
0.5


0.95
0.8








0.9
0.9
0.5





1

0.9
1




Some Ben
0.05

0.1
0.1
0.05
0.05

0.25
0.15

0.1
0.05
0.1
0.1

0.1
0.1
0.02
0.02
0.8

0.05


0.1

0.4
0.5
1
0.1
Smashed







0.25

0.25
0.3








0.2






0.1

0.25

Dull/rough
0.25
0.5
1
0.75
0.05
0.2

1
1
1
1



0.1

0.5




0.75
0.75
1
0.5

0.5


0.75
Corroded






























Pitted






























Flaking






























Overall Grade
7.00%
7.50%
9.00%
9.25%
9.60%
10.65%

15.25%
7.50%
1 1 .3%
9.00%
10.0%
4.00%
4.00%
21.70%
4.00%
9.50%
3.20%
3.20%
30.00%

24.00%
23.00%
24.75%
6.50%
9.00%
12.00%
9.00%
17.75%
10.25%
Service assistant
6% 0.541308
6% 32.0%
5% 26.4%
7% 40.0%
6% 31 .7%
1% 2.5%
0.0%
5% 14.5%
6% 33.1%
2% 5.8%
5% 16.1%
4% 31 .5%
5% 39.4%
15% 182.2%
11% 83.0%
28% 584.8%
4% 28.3%
6% 29.3%
35% 138.7%
1% 24.0%
0.0%
38% 922.9%
7% 122.7%
13% 291.2%
10% 27.1%
17% 81.4%
11% 185.2%
7% 34.1%
20% 146.4%
9% 84.4%
                                                                                                                                                                                                           11.49%   10.31%
Appendix H
Page 1 of 2
       EPA Adsil Evaluation
Spreadsheet EER Degradaion

-------
                                                                                        Visual vs Service Assistant Degradation Approximation (Valid Tests)
       5.00% --     —    —
Appendix H
Page 2 of 2
       EPAAdsil Evaluation
Spreadsheet EER Degradaion

-------
TABLE
                                                                 Overall Unit Condition
                                                                                                               Coil Cleanliness
Site
Concord Admin
Concord City Hall





Locust City Hall
Monroe Aquatic Center




YTC Bid D
YTC Truck School

Average
Unit
RTU-7
RTU-2
RTU-3
SS-1
SS-2


SS-2
RTU-1
RTU-2
RTU-9
RTU-1 0
RTU-1 3
RTU-1
SS-1


Capacity
9
5
5
5
6


3
7
7
12
8
21
4
9

102
Age
6
5
5
2
5


7
7
7
7
7
7
4
15


New

















1 -9 yrs
1
1
1
1
1


1
1
1
1
1
1
1



10-1 5 yrs

















>15 yrs














1


Coated

0.7


0.9


1









Clean
0.8
0.3
0.8
0.75




1
1

1
0.7

0.75


Dirty
0.2

0.2
0.25
0.1


0.1


0.3

0.3
1
0.25


Clogged










0.7






Plugged

















Like New
1
0.5


0.95





0.9
0.9
0.5




Some Ben
0.05

0.1
0.1
0.05


0.05
0.1
0.1

0.1
0.1
0.8
0.1


Smashed













0.2



Dull/rough
0.25
0.5
1
0.75
0.05





0.1

0.5

0.75


Overall Grade
7.00%
7.50%
9.00%
9.25%
9.60%


10.0%
4.00%
4.00%
21.70%
4.00%
9.50%
29.00%
11.25%

10.45%
Service assistant
5.8%
6.1%
5.1%
7.3%
5.6%


5.4%
4.2%
5.3%
15.3%
10.9%
28.2%
34.7%
9.2%

11.00%
54%
32%
26%
40%
32%


16%
32%
39%
182%
83%
585%
139%
84%

13.14%
Appendix H
Page 1 of 2
        EPA Adsil Evaluation
Spreadsheet EER Degradation

-------
                                                                             Visual vs Serice Assistant Degradation  (Literature Valid Tests)
             40.00%
             35.00%
             30.00%
             25.00%
          o
          'ra
             20.00%
             15.00%
             10.00%
              5.00% - -
              0.00%
                                                                                                   Unit
Appendix H
Page 2 of 2
        EPA Adsil Evaluation
Spreadsheet EER Degradation

-------

-------
   Appendix I
Statistical Model

-------
                                           File: EER Change Stat Results.doc


IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     42.000   0.160     0.009
IMPORT successfully completed.

 42 cases and 2 variables processed and saved.
SYSTAT Rectangular file P:\EAT\TUCKER\small projects\lowrey\EER Change\allsaprepost.SYD,
created Fri Sep 03, 2004 at 10:05:18, contains variables:

      PREADSILEE       POSTADSILE

SYSTAT Rectangular file P:\EAT\TUCKER\small projects\lowrey\EER Change\allsaprepost.SYD,
created Fri Sep 03, 2004 at 10:05:18, contains variables:

      PREADSILEE       POSTADSILE

Wilcoxon Signed Ranks Test Results

 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                  0                  6
      POSTADSILE _ 35 _ 0_

 Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ   °'

      POSTADSILE                 4                  °-
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than Pre for Service Assistant results.
Appendix I
Statistical Model
Page 1 of 10

-------
                                             File: EER Change Stat Results.doc
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
42
0.079
0.380
0.060
0.080
0.111
0.049
0.015
0.099
IMPORT successfully completed.
All condensing data

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERIMPROVEM    29.000    0.150      0.096
Data are normal. Use t test.

One-sample t test of EERIMPROVEM with 29 cases;  Ho:  Mean =    0.000

   Mean=     0.366        95.00% Cl  =    0.173 to   0.558
    SD=    0.505                   t=    3.898
                      df=  28  Prob=    0.001
Appendix I
Statistical Model
Page 2 of 10

-------
                                      File: EER Change Stat Results.doc
     o
    O
                    EERIMPROVEM
EERIMPROVEM
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev

0.
3
0
6
8
3
4
5
29
239
1.52
0.23
0.36
0.55
0.17
0.09
0.50
IMPORT successfully completed.
All Spreadsheet results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable   N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE   42.000   0.141    0.034
% Change results not normal. Use nonparametric test.
IMPORT successfully completed.
EXPORT successfully  completed.

Appendix I
Statistical Model
Page 3 of 10

-------
                                           File: EER Change Stat Results.doc
Wilcoxon Signed Ranks Test Results

 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                  0                  0
      POSTADSILE _ 41 _ 0_

 Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ    °'

      POSTADSILE
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than Pre.
IMPORT successfully completed.
EERCHANGE
N of cases

Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev

42
0.000
0.176
0.051
0.058
0.072
0.044
0.007
0.044
Use valid data only. All temperatures. Service Assistant results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     30.000   0.215     0.001
Data are not normal. Use nonparametric test.
IMPORT successfully completed.
IMPORT successfully completed.

Wilcoxon Signed Ranks Test Results
Appendix I
Statistical Model
Page 4 of 10

-------
                                           File: EER Change Stat Results.doc

 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                  0                 2
      POSTADSILE _ 28 _ 0_

  Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE        POSTADSILE

      PREADSILEE          OOQ    °'

      POSTADSILE                 4                 °-
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than Pre.
IMPORT successfully completed.
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
30
0.079
0.380
0.063
0.093
0.130
0.056
0.018
0.099
Valid tests, all temperatures, condensing results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     20.000    0.098     1.000
Data are normal. Use t test.

One-sample t test of EERCHANGE with 20 cases;  Ho: Mean =    0.000

   Mean=    0.326       95.00% Cl =   0.140 to   0.512
    SD=    0.397                 t=    3.670
                     df=  19   Prob=    0.002
Appendix I
Statistical Model
Page 5 of 10

-------
                                    File: EER Change Stat Results.doc
    O
    O
8
7
6
5
4
3
2
1
0
-0.5    0.0    0.5     1.0
          EERCHANGE
                       OOO O OO
                 OOIOOO OOP
                                               1.5
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
20
0.239
1.132
0.263
0.326
0.512
0.140
0.089
0.397
Valid tests, all temperatures, Spreadsheet results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

 EERCHANGE    30.000   0.165    0.036
Results not normally distributed. Use nonparametric test.
IMPORT successfully completed.

Appendix I
Statistical Model
Page 6 of 10

-------
                                           File: EER Change Stat Results.doc

IMPORT successfully completed.

Wilcoxon Signed Ranks Test Results

 Counts of differences (row variable greater than column)

                         PREADSILEE       POSTADSILE
      PREADSILEE                  0                  0
      POSTADSILE _ 29 _ 0_

 Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ   °'

      POSTADSILE                 4                  °-
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than Pre.
IMPORT successfully completed.
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
30
0.000
0.176
0.057
0.061
0.078
0.043
0.009
0.047
Valid results, temperatures previously tested in the literature. Service Assistant results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable   N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     15.000   0.235     0.026
Data are not normal. Use nonparametric test.
IMPORT successfully completed.
IMPORT successfully completed.

Wilcoxon Signed Ranks Test Results

Appendix I
Statistical Model
Page 7 of 10

-------
                                           File: EER Change Stat Results.doc
 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                  0                  1
      POSTADSILE _ 14 _ 0_

 Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ    °'

      POSTADSILE                 2                  °-
 Two-sided probabilities using normal approximation
                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ    1'

      POSTADSILE
Post Adsil EER significantly greater than pre.
IMPORT successfully completed.
EERCHANGE
N of cases

Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev

15
0.079
0.347
0.058
0.091
0.148
0.033
0.027
0.104
Valid results at temperatures previously tested in the literature. Condensing tests.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     10.000   0.126     1.000
% change data are normal. Use t test.

One-sample t test of EERCHANGE with 10 cases;  Ho: Mean =    0.000

   Mean=    0.356       95.00% Cl =   0.143 to   0.568
    SD=    0.297                  t=    3.788
                     df=   9  Prob=     0.004
Appendix I
Statistical Model
Page 8 of 10

-------
                                     File: EER Change Stat Results.doc
    O
    O
          5
          4
          1
          0
          -0.5
                          O
   0.0       0.5
EERCHANGE
1.0
Post Adsil improvement is statistically significant.
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
10
0.073
0.830
0.327
0.356
0.568
0.143
0.094
0.297
Valid results, temperatures previously tested in the literature. Spreadsheet results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable   N-of-Cases   MaxDif Lilliefors Probability (2-tail)

 EERCHANGE     15.000   0.254     0.010
Data not normal. Use nonparametric test.
IMPORT successfully completed.

Appendix I
Statistical Model
Page 9 of 10

-------
                                          File: EER Change Stat Results.doc
Wilcoxon Signed Ranks Test Results

 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                 0                 0
      POSTADSILE _ 15 _ 0_

  Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ   °'

      POSTADSILE
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than pre.
IMPORT successfully completed.

                       EERCHANGE

            N of cases          .,-
                              I 0
             Minimum           QQQ7

             Maximum           _ „_„
                               u.i /D
               Median           Q Q56

                Mean           Q06Q

          95% Cl Upper          Q Q8g

          95% Cl Lower          Q Q31

             Std. Error          Q^

          Standard Dev           Q^2
Appendix I
Statistical Model
Page 10 of 10

-------
                                           File: EER Change Stat Results.doc


IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     42.000   0.160     0.009
IMPORT successfully completed.

 42 cases and 2 variables processed and saved.
SYSTAT Rectangular file P:\EAT\TUCKER\small projects\lowrey\EER Change\allsaprepost.SYD,
created Fri Sep 03, 2004 at 10:05:18, contains variables:

      PREADSILEE       POSTADSILE

SYSTAT Rectangular file P:\EAT\TUCKER\small projects\lowrey\EER Change\allsaprepost.SYD,
created Fri Sep 03, 2004 at 10:05:18, contains variables:

      PREADSILEE       POSTADSILE

Wilcoxon Signed Ranks Test Results

 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                  0                  6
      POSTADSILE _ 35 _ 0_

 Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ   °'

      POSTADSILE                 4                  °-
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than Pre for Service Assistant results.
Appendix I
Statistical Model
Page 1 of 10

-------
                                             File: EER Change Stat Results.doc
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
42
0.079
0.380
0.060
0.080
0.111
0.049
0.015
0.099
IMPORT successfully completed.
All condensing data

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERIMPROVEM    29.000    0.150      0.096
Data are normal. Use t test.

One-sample t test of EERIMPROVEM with 29 cases;  Ho:  Mean =    0.000

   Mean=     0.366        95.00% Cl  =    0.173 to   0.558
    SD=    0.505                   t=    3.898
                      df=  28  Prob=    0.001
Appendix I
Statistical Model
Page 2 of 10

-------
                                      File: EER Change Stat Results.doc
     o
    O
                    EERIMPROVEM
EERIMPROVEM
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev

0.
3
0
6
8
3
4
5
29
239
1.52
0.23
0.36
0.55
0.17
0.09
0.50
IMPORT successfully completed.
All Spreadsheet results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable   N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE   42.000   0.141    0.034
% Change results not normal. Use nonparametric test.
IMPORT successfully completed.
EXPORT successfully  completed.

Appendix I
Statistical Model
Page 3 of 10

-------
                                           File: EER Change Stat Results.doc
Wilcoxon Signed Ranks Test Results

 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                  0                  0
      POSTADSILE _ 41 _ 0_

 Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ    °'

      POSTADSILE
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than Pre.
IMPORT successfully completed.
EERCHANGE
N of cases

Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev

42
0.000
0.176
0.051
0.058
0.072
0.044
0.007
0.044
Use valid data only. All temperatures. Service Assistant results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     30.000   0.215     0.001
Data are not normal. Use nonparametric test.
IMPORT successfully completed.
IMPORT successfully completed.

Wilcoxon Signed Ranks Test Results
Appendix I
Statistical Model
Page 4 of 10

-------
                                           File: EER Change Stat Results.doc

 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                  0                 2
      POSTADSILE _ 28 _ 0_

  Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE        POSTADSILE

      PREADSILEE          OOQ    °'

      POSTADSILE                 4                 °-
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than Pre.
IMPORT successfully completed.
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
30
0.079
0.380
0.063
0.093
0.130
0.056
0.018
0.099
Valid tests, all temperatures, condensing results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     20.000    0.098     1.000
Data are normal. Use t test.

One-sample t test of EERCHANGE with 20 cases;  Ho: Mean =    0.000

   Mean=    0.326       95.00% Cl =   0.140 to   0.512
    SD=    0.397                 t=    3.670
                     df=  19   Prob=    0.002
Appendix I
Statistical Model
Page 5 of 10

-------
                                    File: EER Change Stat Results.doc
    O
    O
8
7
6
5
4
3
2
1
0
-0.5    0.0    0.5     1.0
          EERCHANGE
                       OOO O OO
                 OOIOOO OOP
                                               1.5
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
20
0.239
1.132
0.263
0.326
0.512
0.140
0.089
0.397
Valid tests, all temperatures, Spreadsheet results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

 EERCHANGE    30.000   0.165    0.036
Results not normally distributed. Use nonparametric test.
IMPORT successfully completed.

Appendix I
Statistical Model
Page 6 of 10

-------
                                           File: EER Change Stat Results.doc

IMPORT successfully completed.

Wilcoxon Signed Ranks Test Results

 Counts of differences (row variable greater than column)

                         PREADSILEE       POSTADSILE
      PREADSILEE                  0                  0
      POSTADSILE _ 29 _ 0_

 Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ   °'

      POSTADSILE                 4                  °-
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than Pre.
IMPORT successfully completed.
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
30
0.000
0.176
0.057
0.061
0.078
0.043
0.009
0.047
Valid results, temperatures previously tested in the literature. Service Assistant results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable   N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     15.000   0.235     0.026
Data are not normal. Use nonparametric test.
IMPORT successfully completed.
IMPORT successfully completed.

Wilcoxon Signed Ranks Test Results

Appendix I
Statistical Model
Page 7 of 10

-------
                                           File: EER Change Stat Results.doc
 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                  0                  1
      POSTADSILE _ 14 _ 0_

 Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ    °'

      POSTADSILE                 2                  °-
 Two-sided probabilities using normal approximation
                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ    1'

      POSTADSILE
Post Adsil EER significantly greater than pre.
IMPORT successfully completed.
EERCHANGE
N of cases

Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev

15
0.079
0.347
0.058
0.091
0.148
0.033
0.027
0.104
Valid results at temperatures previously tested in the literature. Condensing tests.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable    N-of-Cases   MaxDif Lilliefors Probability (2-tail)

  EERCHANGE     10.000   0.126     1.000
% change data are normal. Use t test.

One-sample t test of EERCHANGE with 10 cases;  Ho: Mean =    0.000

   Mean=    0.356       95.00% Cl =   0.143 to   0.568
    SD=    0.297                  t=    3.788
                     df=   9  Prob=     0.004
Appendix I
Statistical Model
Page 8 of 10

-------
                                     File: EER Change Stat Results.doc
    O
    O
          5
          4
          1
          0
          -0.5
                          O
   0.0       0.5
EERCHANGE
1.0
Post Adsil improvement is statistically significant.
EERCHANGE
N of cases
Minimum
Maximum
Median
Mean
95% Cl Upper
95% Cl Lower
Std. Error
Standard Dev
10
0.073
0.830
0.327
0.356
0.568
0.143
0.094
0.297
Valid results, temperatures previously tested in the literature. Spreadsheet results.
IMPORT successfully completed.

Kolmogorov-Smirnov One Sample Test using Normal(0.00,1.00) distribution

 Variable   N-of-Cases   MaxDif Lilliefors Probability (2-tail)

 EERCHANGE     15.000   0.254     0.010
Data not normal. Use nonparametric test.
IMPORT successfully completed.

Appendix I
Statistical Model
Page 9 of 10

-------
                                          File: EER Change Stat Results.doc
Wilcoxon Signed Ranks Test Results

 Counts of differences (row variable greater than column)

                        PREADSILEE       POSTADSILE
      PREADSILEE                 0                 0
      POSTADSILE _ 15 _ 0_

  Z = (Sum of signed ranks )/square root(sum of squared ranks)

                   PREADSILEE       POSTADSILE

      PREADSILEE          OOQ   °'

      POSTADSILE
 Two-sided probabilities using normal approximation

                   PREADSILEE       POSTADSILE

      PREADSILEE

      POSTADSILE
Post Adsil EER significantly greater than pre.
IMPORT successfully completed.

                       EERCHANGE

            N of cases          .,-
                              I 0
             Minimum           QQQ7

             Maximum           _ „_„
                               u.i /D
               Median           Q Q56

                Mean           Q06Q

          95% Cl Upper          Q Q8g

          95% Cl Lower          Q Q31

             Std. Error          Q^

          Standard Dev           Q^2
Appendix I
Statistical Model
Page 10 of 10

-------

-------
 TECHNICAL REPORT DATA
 1. REPORT NO.
   EPA-453/R-05-003
                                                                        3. RECIPIENT'S ACCESSION NO.
 4. TITLE AND SUBTITLE
 Evaluation of Savings from the Application of
 Adsil in the NC/SC Charlotte Area
                   5. REPORT DATE
                     Nov. 5, 2004
                                                                        6. PERFORMING ORGANIZATION CODE
 7. AUTHOR(S)
 Tom Lowery, PE Principal
 Chris Melton,  PE Senior Engineer
                                                                        8. PERFORMING ORGANIZATION REPORT NO.
 9. PERFORMING ORGANIZATION NAME AND ADDRESS

                      Prepared for EPA by Mactec, 404 SW 140th Terrace, Newberry, FL
                                                                        10. PROGRAM ELEMENT NO.
                                                                        11. CONTRACT NO.
                                                                        4D-6453-NTLX
 12. SPONSORING AGENCY NAME AND ADDRESS
   Office of Air Quality Planning and Standards
   U.S. Environmental Protection Agency
   Research Triangle  Park, NC  27711
                   13. TYPE OF REPORT AND PERIOD COVERED
                   Technology evaluation
                   Nov. 2003 - Nov. 2004
                                                                        14. SPONSORING AGENCY CODE
                                                                        EPA/200/04
 15. SUPPLEMENTARY NOTES
 16. ABSTRACT
 This report contains the results of a study in the Charlotte, NC/Rock Hill, SC region to evaluate the benefits of a new coating called
 Adsil. It was conducted as part of the SEQL Project (Sustainable Environment for Quality of Life), an integrated environmental
 improvement project in the 15-county NC/SC region surrounding Charlotte, NC. Previous studies have shown that, when Adsil is
 applied to air conditioner units, it can bring the efficiency of that unit virtually back to that of a new unit, as well as prevent age-
 related efficiency loss, saving electrical power and early replacement costs.  The ability to model expected energy savings with
 Adsil is beneficial and transferable to other communities. Energy savings reduce costs, limit the need for new generating capacity,
 and could under certain circumstances benefit air quality.  The report includes two tools:

 1) A degradation prediction tool (spreadsheet-based) calibrated against actual EER measurements and found to be very accurate in
 predicting the EER degradation of a population of HVAC units in the SEQL area.
 2) An energy savings projection tool created based on the results of this study. This tool can be adapted by facility owners and
 operators to estimate their energy savings, dollar savings, and potentially avoided pollution emissions as a result of the application
 of Adsil to air-cooled HVAC equipment.	
 17.KEY WORDS AND DOCUMENT ANALYSIS
           DESCRIPTORS
                                                     b. IDENTIFIERS/OPEN ENDED TERMS
                                                                                             c. COSATI Field/Group
 Technology evaluation of energy efficiency
 technology
Energy efficiency
Air quality
Air conditioning
 18. DISTRIBUTION STATEMENT

    Release Unlimited
19. SECURITY CLASS (Report)
   Unclassified
                                                                                             21. NO. OF PAGES
61
                                                     20. SECURITY CLASS (Page)
                                                        Unclassified
                                                                                             22. PRICE
EPA Form 2220-1 (Rev. 4-77)   PREVIOUS EDITION IS OBSOLETE

-------
United States
Environmental Protection
Agency
Office of Air Quality Planning and Standards
Air Quality Strategies and Standards Division
        Research Triangle Park, NC
Publication No. EPA-453/R-05-003
                  November 2004
Postal information in this section where appropriate.

-------