EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
Tank-Type High-Efficiency Toilet Specification
1.0 Scope and Objective
This specification establishes the criteria for a tank-type high-efficiency toilet (MET) under the
U.S. Environmental Protection Agency WaterSense® program. It is applicable to:
• Single flush, tank-type gravity toilets;
• Dual flush, tank-type gravity toilets;
• Dual flush, tank-type flushometer tank (pressure-assist) toilets;
• Tank-type, flushometer tank (pressure-assist) toilets;
• Tank-type electrohydraulic toilets; and
• Any other technologies that meet these performance specifications.
The specification is designed to ensure both sustainable, efficient water use and a high level of
user satisfaction with flushing performance.
2.0 Summary of Criteria
Toilets must meet criteria in three areas:
• Effective flush volume shall not exceed 1.28 gallons1 (4.8 liters), as specified in
Section 3.0;
• Solid waste removal must be 350 grams2 or greater, as specified in Section 4.0;
and
• The toilet must conform to the adjustability and other supplementary
requirements specified in Section 5.0.
3.0 Water Efficiency Criteria
3.1 Single Flush Toilets - The effective flush volume shall not exceed 1.28 gallons
(4.8 liters). The effective flush volume is the average flush volume when tested in
accordance with ASME A112.19.23.
3.2 Dual Flush Toilets - The effective flush volume shall not exceed 1.28 gallons (4.8
liters). The effective flush volume is defined as the composite, average flush
volume of two reduced flushes and one full flush. Flush volumes will be tested in
accordance with ASME A112.19.2 and ASME A112.19.14.
1 The effective flush volume has been established as 1.28 gallons, which is a 20 percent reduction from the 1.6 gallons per flush
standard that became mandatory pursuant to the 1992 EPAct.
2 A qualified MET must provide superior flushing performance while saving significant volumes of water. Based on data contained in
the medical study Variability of colonic function in healthy subjects, 1978, J.B. Wyman, K.W. Heaton, A.P. Manning, and A.C.B.
Wicks of the University Department of Medicine, Bristol Royal Infirmary, the greatest single 'loading' of the 20 study participants was
approximately 450g, and the 99.5 percent confidence level of the men in the study equates to a loading of approximately 350g.
3 References to this and other ASME standards apply to the most current version of that standard.
Version 1.0 1 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
4.0 Flush Performance Criteria
4.1 Toilet model performance is identified as either a Pass or Fail depending upon
whether it can successfully and completely clear all test media from the fixture in
a single flush in at least four of five attempts. Only toilet models that Pass qualify
for the EPA WaterSense label. Flush performance testing shall be conducted in
accordance with the test protocol provided in Appendix A.
4.2 Test media consists of seven test specimens, 50 ± 4 grams each, consisting of
soybean paste forming a 'sausage' approximately 4 ± 0.5 inch (100 ± 13 mm) in
length and 1 ± 0.25 inch (25 ± 6 mm) in diameter and four loosely crumbled balls
of toilet paper as defined in Appendix A.
4.3 The flush performance criteria apply to single flush toilets, and to the full flush
option of dual flush toilets. No solid waste removal requirement applies to the
reduced flush option on dual flush toilets.
5.0 Supplementary Requirements for Flush Volume Adjustability
5.1 All single flush toilets must conform to ASM EA112.19.2 and all dual flush toilets
must conform to ASME A112.19.14.
5.2 The criteria in this section apply to tank-type gravity toilets.
5.2.1 MustconformtoASMEA112.19.5.
5.2.2 Fill Valve
The fill valve shall be the pilot valve type only, or, alternatively, the fill
valve shall meet the performance requirements of the fill valve test
protocol in Appendix B. All fill valves must conform to ANSI/ASSE 1002.
5.2.3 Tank Capacity
5.2.3.1 Any barrier, bucket, dam, displacement device, or similar fixture
used in a toilet tank to affect flush volume shall be tamper-
resistant and permanently affixed to the tank. Any device that
can be tampered with or removed such that the toilet can be
made to flush with greater than the maximum flush volumes
specified in Section 5.2.3.2 shall be deemed noncompliant.
5.2.3.2 The maximum volume of water that may be discharged by the
toilet, when field adjustment of the tank trim is set at its
maximum water use setting, shall not exceed the following
amounts:
• For single flush fixtures: 1.68 gallons (6.4 liters) per flush4
• For dual flush fixtures: 1.40 gallons (5.3 liters) per flush5 in
reduced flush mode and 2.00 gallons (7.6 liters) per flush6
in full flush mode.
4 Value based on a maximum effective flush volume of 1.28 gallons (4.8 liters) per flush, with no more than 0.40 gallon (1.6 liter)
increase with tank trim adjusted to maximum water use settings.
5 Value based on the reduced flush requirement in ASME A112.19.14-2001.
Version 1.0 2 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
• The maximum volume of water discharged, using both
original equipment tank trim and using after market closure
seals, shall be tested according to the protocol in Appendix
C.
6.0 Effective Date
This specification is effective on January 24, 2007.
7.0 Future Specification Revisions
EPA reserves the right to revise this specification should technological and/or market changes
affect its usefulness to consumers, industry, or the environment. Revisions to the specification
would be made following discussions with industry partners and other interested stakeholders.
8.0 Definitions
Definitions within ASME A112.19.2 and ASME A112.19.14 are included by reference.
• Electrohydraulic toilet: A toilet fixture of siphonic or washdown design that uses
a motor, pump, and controller to assist flushing action.
• Pressure-assist toilet: A flushometer tank toilet as defined in ASME A112.19.2.
• Rated flush volume: The stated flush volume of the toilet, as certified.
Value based on the requirement in the Los Angeles Department of Water and Power Supplementary Purchase Specification,
adopted in 2000 and as amended in 2005.
Version 1.0 3 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
Appendix A: MET Fixture Performance Testing Protocol7
1.0 Scope of Testing
1.1 Toilet model performance is identified as either a Pass or a Fail depending upon
whether the test fixture can successfully and completely clear all media (350
grams) from the fixture in a single flush in at least four of five attempts.
1.2 Tests where toilet sample clogs, plugs, or fails to restore a minimum of a 2 inch
(50 mm) trap seal following each flushing test will be deemed a failed test.
1.3 Test media is comprised of the following:
1.3.1 Seven test specimens at 50 ± 4 grams per test specimen ("test
specimen") consisting of soybean paste forming a "sausage"
approximately 4 ± 0.5 inch (100 ± 13 mm) in length and 1 ± 0.25 inch (25
± 6mm) in diameter. The total mass of test media used for each test shall
be 350 ± 10 grams.
1.3.2 Four loosely crumpled balls of toilet paper ("paper").
2.0 Testing Protocol
2.1 Fixture Model Selection
The product sample tested to these requirements shall be selected according to
the procedure provided in Section A4 of ASM EA112.19.2, Nonmandatory
Appendix A, Demonstrating Compliance to ASME A112.19.2.
2.2 Set-Up
2.2.1 Samples shall be assembled according to manufacturer's written
instructions as contained within the product packaging, and placed on test
rig, ensuring tank and bowl are level.
2.2.2 Tank water level shall be adjusted to the level specified by manufacturer
in the manufacturer's instructions (e.g., set to waterline) where applicable.
2.2.3 Static water supply pressure shall be set to 50 ± 3 PSIG.
2.2.4 Inlet water temperature shall be 65 to SOT (18 to 27 °C).
2.2.5 Flush sample a minimum of three times prior to commencement of
testing.
2.2.6 Re-adjust tank water level to proper level if required.
2.3 Flush Volume Measurement
2.3.1 Measure and record flush volume of sample (sample set-up as outlined in
Section 2.2). Repeat the test two additional times and record the results
and the average of the three test replicates. A receiving vessel may be
used, either calibrated in increments not exceeding 0.025 gallon (0.1 L) or
7 Testing protocol based on Maximum Performance (MaP) Testing Protocol, Version 3, January 2006, by Bill Gauley, Veritec
Consulting, Inc., and John Koeller, Koeller and Company.
Version 1.0 A-1 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
placed on a load cell with a readout in increments not exceeding 0.025
gallon (0.1 L). Other methods capable of measuring volumes to within in
0.025 gallon (0.1 L) shall be acceptable.
2.3.2 Samples with average flush volumes in excess of 0.10 gallon (0.4 L)
greater than their rated flush volume shall be deemed to fail testing
requirements due to excessive flush volume8.
2.3.3 Samples with average flush volumes less than 0.10 gallon (0.4 L) greater
than their rated flush volume shall be adjusted, if possible, to their rated
flush volume prior to performance testing.
2.3.4 Samples with average flush volumes less than their rated flush volume
shall be tested at measured volume and this volume shall be recorded on
test report.
2.4 Waste Extraction Test
2.4.1 Test specimens shall be formed such that they are roughly cylindrical in
shape and uniform in diameter.
2.4.2 A test specimen drop guide shall be placed across the top of the bowl,
with the centerline of a 2 inch (50 mm) diameter opening 6 inches (15 cm)
in front of the center of the seat post holes, equidistance from each hole.
Drop guide may be made of plastic or other rigid material, to be no more
than 0.5 inch (12 mm) thick, and be of sufficient length to span top of
toilet bowl.
2.4.3 Seven (7) test specimens (350g) shall be freely dropped in a vertical
orientation through opening in drop guide into bowl.
2.4.4 Immediately remove drop guide and freely and randomly drop four balls
of crumpled toilet paper over center of bowl sump.
2.4.5 Wait 10 ± 1 seconds.
2.4.6 Flush sample.
2.4.7 Record test as Pass or Fail (test is a Fail if any waste remains in the
bowl or trap, or if minimum 2 inch (50 mm) trap seal has not been
restored).
2.4.8 Flush sample to clean bowl and trapway and fully restore trap seal.
2.4.9 Repeat testing until toilet sample either (i) achieves four Pass grades or
(ii) achieves two Fail grades.
2.4.10 Models must Pass at least four of five attempts to qualify for the EPA
WaterSense Program.
3.0 Test Media Specifications
3.1 Soybean Paste Nominal Specifications:
35.5 percent water, 33.8 percent soybean, 18.5 percent rice, and 12.2 percent
salt, and having a density of 1.15 ± 0.10 g/mL (i.e., density greater than that of
water).
3.2 Test Specimens:
For example, fixtures rated at 1.28 gallons per flush (the MET maximum) but flushing at greater than 1.38 gallons (5.2 L) when
adjusted to water line shall be deemed to have "failed" the requirements of this specification.
Version 1.0 A-2 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
Each test specimen shall have a mass of 50 ± 4 grams.
3.3 Toilet Paper Specifications:
Each ball of paper is comprised of six sheets of single-ply toilet paper conforming
to ASMEA112.19.14, section 3.2.5.1.2.
Version 1.0 A-3 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
Appendix B: MET Fill Valve Integrity Test Protocol9
1.0 Scope of Testing
This requirement shall apply to all fill valves that are not otherwise classified as pilot valves.
Samples must conform to both Sections 2.0 and 3.0 of this appendix.
2.0 Consistent Water Level
2.1 Purpose of Test: To determine whether or not the fill valve shuts off at a
consistent water level in a toilet tank independent of any change in inlet water
supply pressure.
2.2 Test Procedure
2.2.1 Install the fill valve in the toilet tank provided, install the tank on a leveled
test stand, and adjust the water level per the manufacturer's
recommendation at an inlet water pressure of 20 ± 2 PSIG or at the
manufacturer's recommended minimum pressure as noted in the product
literature and product packaging.
2.2.2 Flush the tank to verify and mark water level after completed refill.
2.2.3 Increase the inlet water pressure to 60 ± 2 PSIG.
2.2.4 Flush the tank.
2.2.5 Measure any difference in water level after completed refill.
2.2.6 Repeat steps 2.2.3 to 2.2.5 utilizing 80 ± 2 PSIG inlet water pressure.
2.3 Performance Requirement: The fill valve shall shut off at the same water level ±
0.5 inch (± 12 mm) for all three inlet water pressures. In addition, water shall not
enter the overflow tube or flow out of the tank at any of the three tested inlet
pressures.
3.0 Shutoff Integrity with Increased Water Pressure
3.1 Purpose of Test: To determine whether or not the fill valve shuts off at a
consistent water level in a toilet tank independent of changes in inlet water
supply pressure.
3.2 Test Procedure
3.2.1 Install the fill valve in a toilet tank and adjust the water level per the
manufacturer's recommendation at an inlet water pressure of 20 ± 2 PSIG
or at the manufacturer's recommended minimum pressure as noted in the
product literature and product packaging.
3.2.2 Flush the tank to verify and mark water level after completed refill.
9 Testing protocol based on Appendix B to Los Angeles Department of Water and Power Supplementary Purchase Specification,
November 16, 2005 version.
Version 1.0 B-1 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
3.2.3 Increase the inlet pressure to the fill valve from 20 (or recommended
minimum pressure) to 60 PSIG, then to 80 PSIG at a rate of less than 10
PSIG per second.
3.3 Performance Requirement: The water level shall remain at the initial mark ± 0.5
inch (±12 mm). In addition, water shall not enter the overflow tube or flow out of
the tank.
Version 1.0 B-2 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
Appendix C: Tank Trim Adjustability Testing Protocol10
1.0 Scope of Testing
All tank-type gravity toilet fixtures must conform to the requirements of Section 2.0 of this
appendix, which address the adjustability of original equipment tank trim and the resulting flush
volume of the toilet fixture. All tank-type gravity toilet fixtures with flush seals must conform to
the requirements in Section 3.0 of this appendix, which address the flush volume resulting from
the replacement of original equipment seals with seals available in the after market.
2.0 Tank-Type Gravity Toilets With Original Equipment
2.1 Purpose of Test
The objective of this tank trim adjustability test is to determine the upper limit to
the volume of water that may be discharged by the field adjustment of tank trim
components. The maximum volume of water that may be discharged by the
toilet, when field adjustment of original equipment tank trim is set at its maximum
water-use setting, shall not exceed the following amounts:
For single flush fixtures - 1.68 gallons (6.4 liters) per flush
For dual flush fixtures:
Reduced flush ("short flush") mode - 1.40 gallons (5.3 liters) per
flush
Full flush mode - 2.00 gallons (7.6 liters) per flush
The following test procedure shall be used to verify that the toilet sample meets
these requirements.
2.2 Test Procedure
Test shall be conducted per section 8.4 of ASME A112.19.2 with the following
modifications:
2.2.1 The toilet shall be installed on a leveled test stand and all adjustable tank
trim components (any field adjustment features in the tank that might
increase the toilet flush volume) shall be adjusted to the maximum water
use setting, while taking care not to damage or alter the parts.
2.2.2 The water level in the tank shall be set to 0.25 ± 0.06 inch (6 ± 2 mm)
below the top of the overflow tube. Where the tank utilizes an internal
containment vessel and does not possess an overflow tube, the vessel
shall be filled to a level 0.25 ± 0.06 inch (6 ± 2 mm) below the top rim of
the vessel or to the manufacturer's designated water line, whichever is
higher.
2.2.3 The static pressure of the water supply shall be adjusted to 80 ± 2 PSIG.
2.2.4 The toilet shall be flushed maintaining the activator in the flushing position
for a period of one (1) second, the water being drained into a container.
2.2.5 After the flush cycle is complete, the total flush volume shall be observed
and recorded.
10 Testing protocol based on Los Angeles Department of Water and Power Supplementary Purchase Specification, 16 November
2005 version, modified to reflect the deletion of certain trim durability and marking requirements incorporated into ASME A112 19.5.
Version 1.0 C-1 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
2.2.6 This procedure shall be repeated until five (5) sets of data are obtained.
2.2.7 The static pressure of the water supply shall be adjusted to 20 ± 2 PSIG
or at the manufacturer's recommended minimum pressure as noted in the
product literature and product packaging, and test procedure steps 2.2.4
to 2.2.6 shall be repeated.
2.2.8 For dual-flush toilet fixtures, this test shall be conducted at both full flush
and reduced flush modes.
2.3 Report: The five (5) individual flush volumes and the average of the five (5) runs
shall be reported for each of the two static water supply pressures specified.
2.4 Performance Requirement: The average total flush volume for five (5) test runs
for each of the two static water supply pressures shall not exceed the following:
For single-flush fixtures - 1.68 gallons (6.4 liters) per flush
For dual-flush fixtures:
Reduced flush ("short flush") mode - 1.40 gallons (5.3 liters) per
flush
Full flush mode - 2.00 gallons (7.6 liters) per flush
The volume of water may be determined visually using a graduated container or
by weight calculated as a unit to volume unit.
3.0 Tank-Type Gravity Toilets With After-Market Closure Seals
3.1 Purpose of Test
The objective of this tank trim adjustability and after-market seal test is to
determine the upper limit to the volume of water that may be discharged when an
off-the-shelf replacement flush valve seal/flapper is installed on the toilet. The
maximum volume of water that may be discharged by the toilet, when the original
equipment flush valve seal (flapper or other sealing device) is replaced with a
standard (buoyant) seal available in home improvement centers and hardware
stores, and the field adjustment of tank trim is set at its maximum water-use
setting, shall not exceed the following amounts:
For single flush fixtures - 1.68 gallons (6.4 liters) per flush
For dual flush fixtures:
Reduced flush ("short flush") mode - 1.40 (5.3 liters) gallons per
flush
Full flush mode - 2.00 gallons (7.6 liters) per flush
The following test procedure shall be used to verify that the toilet sample meets
these requirements.
3.2 Test Procedure
Test shall be conducted per section 8.4 of ASME A112.19.2 with the following
modification:
3.2.1 The toilet shall be installed on a leveled test stand and all adjustable tank
trim components (any field adjustment features in the tank that might
increase the toilet flush volume) shall be adjusted for maximum water
use, while taking care not to damage or alter the parts.
Version 1.0 C-2 January 24, 2007
-------
EPA Tank-Type High-Efficiency
AA/atCTSCTISC Toilet Specification
3.2.2 Remove the original equipment flush valve seal and replace it with a
standard (buoyant) non-adjustable after-market seal/flapper for that toilet
where possible. In the case of a standard configuration 2-inch flush
valve, a Fluidmaster Bullseye Super flapper (part no. 501) or a Coast
Foundry Ultra Blue flapper shall be used. For non-standard flush valves,
including 3-inch flush valves, one or more replacement seals available at
hardware, plumbing supply, and building supply stores or from the
manufacturer or other recognized source shall be used11.
3.2.3 The water level in the tank shall be set to 0.25 ± 0.06 inch (6 ± 2 mm)
below the top of the overflow tube. Where the tank utilizes an internal
containment vessel and does not possess an overflow tube, the vessel
shall be filled to a level 0.25 ± 0.06 inch (6 ± 2 mm) below the top rim of
the vessel or to the manufacturer's designated water line, whichever is
higher.
3.2.4 The static pressure of the water supply shall be adjusted to 80 ± 2 PSIG.
3.2.5 The toilet shall be flushed maintaining the activator in the flushing position
for a period of one (1) second maximum, the water being drained into a
container.
3.2.6 After the flush cycle is complete, the total flush volume shall be observed
and recorded.
3.2.7 This procedure shall be repeated until five (5) sets of data are obtained.
3.2.8 The static pressure of the water supply shall be adjusted to 20 ± 2 PSIG
or at the manufacturer's recommended minimum pressure as noted in the
product literature and product packaging, and test procedure steps 3.2.5
to 3.2.7. shall be repeated.
3.2.9 For dual-flush toilet fixtures, this test shall be conducted at both flush
modes (full flush and reduced flush).
3.3 Report: The five (5) individual flush volumes and the average of the five (5) runs
shall be reported for each of the two static water supply pressures specified.
3.4 Performance Requirement: The average total flush volume for five (5) test runs
for each of the two static water supply pressures shall not exceed the following:
For single-flush fixtures - 1.68 gallons (6.4 liters) per flush
For dual-flush fixtures:
Reduced flush ("short flush") mode - 1.40 gallons (5.3 liters) per
flush
Full flush mode - 2.00 gallons (7.6 liters) per flush
The volume of water may be determined visually using a graduated container or
by weight calculated as a unit to volume unit.
11 Where neither the Fluidmaster Bullseye Super flapper nor the Coast Foundry Ultra Blue flapper fit the flush valve, where a 3-inch
flush valve is employed, or in the case of a toilet fixture with a non-standard flush valve seal, the testing laboratory shall have
discretion as to which after-market flapper or seal shall be used in the test.
Version 1.0 C-3 January 24, 2007
-------
EPA Tank-Type High-Efficiency
WaterSdlSe Toilet Specification
Appendix D: Informative Annex for WaterSense Labeling
The following requirements must be met for products to be marked with the WaterSense label.
1.0 WaterSense Partnership
The manufacturer of the product must have a signed partnership agreement in place with EPA.
2.0 Conformity Assessment
Conformance to this specification must be certified by a body either accredited by ANSI in
accordance with the WaterSense certification scheme, or otherwise approved for that purpose
by EPA.
3.0 Prior Testing
Products previousl
under this specification.
Products previously tested under the predecessor UNAR specification12 must still be certified
12 Uniform North American Requirements (UNAR) for toilet fixtures, a supplementary specification developed in 2005 for water
utilities.
Version 1.0 D-1 January 24, 2007
------- |