EPA                                                                  Tank-Type High-Efficiency
AA/atCTSCTISC                                                          Toilet Specification
                 Tank-Type High-Efficiency Toilet Specification

 1.0 Scope and Objective

 This specification establishes the criteria for a tank-type high-efficiency toilet (MET) under the
 U.S. Environmental Protection Agency WaterSense® program. It is applicable to:

        •      Single flush, tank-type gravity toilets;
        •      Dual flush, tank-type gravity toilets;
        •      Dual flush, tank-type flushometer tank (pressure-assist) toilets;
        •      Tank-type, flushometer tank (pressure-assist) toilets;
        •      Tank-type  electrohydraulic toilets; and
        •      Any other technologies that meet these performance specifications.

 The specification is designed to ensure both sustainable, efficient water use and a high level of
 user satisfaction with flushing performance.

 2.0 Summary of Criteria

 Toilets must meet criteria in three areas:

        •      Effective flush volume shall not exceed  1.28 gallons1 (4.8 liters), as specified in
               Section 3.0;
        •      Solid waste removal must be 350 grams2 or greater, as specified in Section 4.0;
               and
        •      The toilet must conform to the adjustability and other supplementary
               requirements  specified in Section 5.0.

 3.0 Water Efficiency Criteria

        3.1     Single Flush Toilets - The effective flush volume shall not exceed  1.28 gallons
               (4.8 liters). The effective flush volume is the average flush volume when tested in
               accordance with ASME A112.19.23.

        3.2    Dual Flush Toilets - The effective flush volume shall not exceed 1.28 gallons  (4.8
               liters). The effective flush volume is defined as the composite, average flush
               volume of two reduced flushes and one full flush. Flush volumes will be tested in
               accordance with ASME A112.19.2 and ASME A112.19.14.
 1 The effective flush volume has been established as 1.28 gallons, which is a 20 percent reduction from the 1.6 gallons per flush
 standard that became mandatory pursuant to the 1992 EPAct.
 2 A qualified MET must provide superior flushing performance while saving significant volumes of water. Based on data contained in
 the medical study Variability of colonic function in healthy subjects, 1978, J.B. Wyman, K.W. Heaton, A.P. Manning, and A.C.B.
 Wicks of the University Department of Medicine, Bristol Royal Infirmary, the greatest single 'loading' of the 20 study participants was
 approximately 450g, and the 99.5 percent confidence level of the men in the study equates to a loading of approximately 350g.
 3 References to this and other ASME standards apply to the most current version of that standard.
 Version 1.0                                   1                                       January 24, 2007

-------
EPA                                                               Tank-Type High-Efficiency
AA/atCTSCTISC                                                       Toilet Specification
 4.0 Flush Performance Criteria

       4.1    Toilet model performance is identified as either a Pass or Fail depending upon
              whether it can successfully and completely clear all test media from the fixture in
              a single flush in at least four of five attempts. Only toilet models that Pass qualify
              for the EPA WaterSense  label. Flush performance testing shall be conducted in
              accordance with the test protocol provided in Appendix A.

       4.2    Test media consists of seven test specimens, 50 ± 4 grams each, consisting of
              soybean paste forming a  'sausage' approximately 4 ± 0.5 inch (100 ± 13 mm) in
              length and 1 ± 0.25 inch (25 ± 6 mm) in diameter and four loosely crumbled balls
              of toilet paper as defined  in Appendix A.

       4.3    The flush performance criteria apply to single flush toilets, and to the full flush
              option of dual flush toilets. No solid waste removal requirement applies to the
              reduced flush option on dual flush toilets.

 5.0 Supplementary Requirements for  Flush Volume Adjustability

       5.1    All single flush toilets must conform to ASM EA112.19.2 and all dual flush toilets
              must conform to ASME A112.19.14.

       5.2    The criteria in this section apply to tank-type gravity toilets.
              5.2.1   MustconformtoASMEA112.19.5.
              5.2.2  Fill Valve
                     The fill valve shall be the pilot valve type only, or, alternatively, the fill
                     valve shall meet the performance requirements of the fill valve test
                     protocol in Appendix B. All fill valves must conform to ANSI/ASSE 1002.
              5.2.3  Tank Capacity
                     5.2.3.1  Any barrier, bucket, dam, displacement device, or similar fixture
                             used  in a toilet tank to affect flush volume shall be tamper-
                             resistant and permanently affixed to the tank. Any device that
                             can be tampered with or removed such that the toilet can be
                             made to  flush with greater than the maximum flush volumes
                             specified in Section 5.2.3.2 shall be deemed noncompliant.
                     5.2.3.2  The maximum volume of water that may be discharged  by the
                             toilet, when field adjustment of the tank trim is set at its
                             maximum water use setting, shall not exceed the following
                             amounts:
                             •     For single flush fixtures: 1.68 gallons (6.4 liters) per flush4
                             •     For dual flush fixtures: 1.40 gallons (5.3 liters) per flush5 in
                                   reduced flush mode and 2.00 gallons (7.6 liters) per flush6
                                   in full flush mode.
 4 Value based on a maximum effective flush volume of 1.28 gallons (4.8 liters) per flush, with no more than 0.40 gallon (1.6 liter)
 increase with tank trim adjusted to maximum water use settings.
 5 Value based on the reduced flush requirement in ASME A112.19.14-2001.
Version 1.0                                 2                                   January 24, 2007

-------
EPA                                                                Tank-Type High-Efficiency
AA/atCTSCTISC                                                       Toilet Specification
                              •     The maximum volume of water discharged, using both
                                   original equipment tank trim and using after market closure
                                   seals, shall be tested according to the protocol in Appendix
                                   C.

 6.0 Effective Date

 This specification is effective on January 24, 2007.

 7.0 Future Specification Revisions

 EPA reserves the right to revise this specification should technological and/or market changes
 affect its usefulness to consumers, industry, or the environment. Revisions to the specification
 would be made following discussions with industry partners and other interested stakeholders.

 8.0 Definitions

 Definitions within ASME A112.19.2 and ASME A112.19.14 are included by reference.

       •       Electrohydraulic toilet: A toilet fixture of siphonic or washdown  design that uses
               a motor,  pump, and controller to assist flushing action.
       •       Pressure-assist toilet: A flushometer tank toilet as defined in ASME A112.19.2.
       •       Rated flush volume: The stated flush volume of the toilet, as certified.
 Value based on the requirement in the Los Angeles Department of Water and Power Supplementary Purchase Specification,
 adopted in 2000 and as amended in 2005.
Version 1.0                                 3                                    January 24, 2007

-------
EPA                                                              Tank-Type High-Efficiency
AA/atCTSCTISC                                                      Toilet Specification
          Appendix A: MET Fixture Performance Testing Protocol7

 1.0 Scope of Testing

       1.1    Toilet model performance is identified as either a Pass or a Fail depending upon
              whether the test fixture can successfully and completely clear all media (350
              grams) from the fixture in a single flush  in at least four of five attempts.

       1.2    Tests where toilet sample clogs, plugs, or fails to restore a minimum of a 2 inch
              (50 mm) trap seal following each flushing test will be deemed a failed test.

       1.3    Test  media is comprised of the following:
              1.3.1   Seven test specimens at 50 ± 4  grams per test specimen ("test
                     specimen") consisting of soybean paste forming a "sausage"
                     approximately 4 ± 0.5 inch (100  ± 13 mm) in length and 1 ± 0.25 inch (25
                     ± 6mm) in diameter. The total mass of test media used for each test shall
                     be 350 ± 10 grams.
              1.3.2   Four loosely crumpled balls of toilet paper ("paper").

 2.0 Testing Protocol

       2.1    Fixture Model Selection
              The product sample tested to these requirements shall be selected according to
              the procedure provided in Section A4 of ASM EA112.19.2, Nonmandatory
              Appendix A, Demonstrating Compliance to ASME A112.19.2.

       2.2    Set-Up
              2.2.1   Samples shall be assembled according to manufacturer's written
                     instructions  as contained within the product packaging, and placed on test
                     rig, ensuring tank and bowl are level.
              2.2.2   Tank water level shall be adjusted to the level specified by manufacturer
                     in the manufacturer's instructions (e.g., set to waterline) where applicable.
              2.2.3   Static water supply pressure shall be set to 50 ± 3 PSIG.
              2.2.4   Inlet water temperature shall be  65 to SOT (18 to 27 °C).
              2.2.5   Flush sample a minimum  of three times prior to commencement of
                     testing.
              2.2.6   Re-adjust tank water level to proper level if required.

       2.3    Flush Volume Measurement
              2.3.1   Measure and record flush volume of sample (sample set-up as outlined in
                     Section 2.2). Repeat the test two additional times and record the results
                     and the average of the three test replicates. A receiving vessel may be
                     used, either calibrated in increments not exceeding 0.025 gallon (0.1 L) or
 7 Testing protocol based on Maximum Performance (MaP) Testing Protocol, Version 3, January 2006, by Bill Gauley, Veritec
 Consulting, Inc., and John Koeller, Koeller and Company.
Version 1.0                               A-1                                   January 24, 2007

-------
EPA                                                               Tank-Type High-Efficiency
AA/atCTSCTISC                                                       Toilet Specification
                     placed on a load cell with a readout in increments not exceeding 0.025
                     gallon (0.1 L). Other methods capable of measuring volumes to within in
                     0.025 gallon (0.1 L) shall be acceptable.
              2.3.2   Samples with average flush volumes in excess of 0.10 gallon (0.4 L)
                     greater than their rated flush volume shall be deemed to fail testing
                     requirements due to excessive flush volume8.
              2.3.3   Samples with average flush volumes less than 0.10 gallon (0.4 L) greater
                     than their rated flush volume shall be adjusted, if possible, to their rated
                     flush volume prior to performance testing.
              2.3.4   Samples with average flush volumes less than their rated flush volume
                     shall be tested at measured volume and this volume shall be recorded on
                     test report.

       2.4    Waste Extraction Test
              2.4.1   Test specimens shall be formed such that they are roughly cylindrical in
                     shape and uniform in diameter.
              2.4.2   A test specimen drop guide shall be placed across the top of the bowl,
                     with the centerline of a 2 inch (50 mm) diameter opening 6 inches (15 cm)
                     in front of the center of the seat post holes, equidistance from each hole.
                     Drop guide may be made of plastic or other rigid material, to be no more
                     than 0.5 inch (12 mm) thick, and be of sufficient length to span  top of
                     toilet bowl.
              2.4.3   Seven (7) test specimens (350g) shall be freely dropped in a vertical
                     orientation through opening in drop guide into bowl.
              2.4.4   Immediately remove drop guide and freely and randomly drop four balls
                     of crumpled toilet paper over center of bowl sump.
              2.4.5   Wait 10 ± 1 seconds.
              2.4.6   Flush sample.
              2.4.7   Record test as Pass or Fail (test is a Fail if any waste remains in the
                     bowl or trap, or if minimum 2 inch (50 mm) trap seal has not been
                     restored).
              2.4.8   Flush sample to clean bowl and trapway  and fully restore trap seal.
              2.4.9   Repeat testing until toilet sample either (i) achieves four Pass grades or
                     (ii) achieves two Fail grades.
              2.4.10 Models must Pass at least four of five attempts to qualify for the EPA
                     WaterSense Program.

 3.0 Test Media Specifications

       3.1    Soybean Paste Nominal Specifications:
              35.5 percent water, 33.8 percent soybean, 18.5 percent rice, and 12.2  percent
              salt, and having a density of 1.15 ± 0.10 g/mL (i.e., density greater than that of
              water).

       3.2    Test Specimens:
  For example, fixtures rated at 1.28 gallons per flush (the MET maximum) but flushing at greater than 1.38 gallons (5.2 L) when
 adjusted to water line shall be deemed to have "failed" the requirements of this specification.
Version 1.0                                A-2                                   January 24, 2007

-------
EPA                                                               Tank-Type High-Efficiency
AA/atCTSCTISC                                                       Toilet Specification
              Each test specimen shall have a mass of 50 ± 4 grams.

       3.3    Toilet Paper Specifications:
              Each ball of paper is comprised of six sheets of single-ply toilet paper conforming
              to ASMEA112.19.14, section 3.2.5.1.2.
Version 1.0                                A-3                                   January 24, 2007

-------
EPA                                                               Tank-Type High-Efficiency
AA/atCTSCTISC                                                       Toilet Specification
             Appendix B: MET Fill Valve Integrity Test Protocol9

 1.0 Scope of Testing

 This requirement shall apply to all fill valves that are not otherwise classified as pilot valves.
 Samples must conform to both Sections 2.0 and 3.0 of this appendix.

 2.0 Consistent Water Level

       2.1    Purpose of Test: To determine whether or not the fill valve shuts off at a
              consistent water level in a toilet tank independent of any change in inlet water
              supply pressure.

       2.2    Test Procedure
              2.2.1   Install the fill valve in the toilet tank provided, install the tank on a leveled
                    test stand, and adjust the water level per the manufacturer's
                     recommendation at an inlet water pressure of 20 ± 2  PSIG or at the
                     manufacturer's recommended minimum pressure as  noted in the product
                     literature and product packaging.
              2.2.2   Flush the tank to verify and mark water level after completed refill.
              2.2.3   Increase the inlet water pressure to 60 ± 2 PSIG.
              2.2.4   Flush the tank.
              2.2.5   Measure any difference in water level after completed refill.
              2.2.6   Repeat steps 2.2.3 to 2.2.5 utilizing 80 ± 2 PSIG inlet water pressure.

       2.3    Performance Requirement: The fill valve shall shut off at the same water level ±
              0.5 inch (± 12 mm) for all three inlet water pressures.  In addition, water shall not
              enter the overflow tube or flow out of the tank at any of the three tested inlet
              pressures.

 3.0 Shutoff Integrity with Increased Water Pressure

       3.1    Purpose of Test: To determine whether or not the fill valve shuts off at a
              consistent water level in a toilet tank independent of changes in inlet water
              supply pressure.

       3.2    Test Procedure
              3.2.1   Install the fill valve in a toilet tank and adjust the water level per the
                     manufacturer's recommendation at an inlet water pressure of 20 ± 2 PSIG
                    or at the manufacturer's recommended minimum pressure as  noted in the
                     product  literature and product packaging.
              3.2.2   Flush the tank to verify and mark water level after completed refill.
 9 Testing protocol based on Appendix B to Los Angeles Department of Water and Power Supplementary Purchase Specification,
 November 16, 2005 version.
Version 1.0                                B-1                                   January 24, 2007

-------
EPA                                                               Tank-Type High-Efficiency
AA/atCTSCTISC                                                      Toilet Specification
              3.2.3   Increase the inlet pressure to the fill valve from 20 (or recommended
                     minimum pressure) to 60 PSIG, then to 80 PSIG at a rate of less than 10
                     PSIG per second.
       3.3    Performance Requirement: The water level shall remain at the initial mark ± 0.5
              inch (±12 mm).  In addition, water shall not enter the overflow tube or flow out of
              the tank.
Version 1.0                                B-2                                  January 24, 2007

-------
EPA                                                                Tank-Type High-Efficiency
AA/atCTSCTISC                                                        Toilet Specification
           Appendix C:  Tank Trim Adjustability Testing Protocol10

 1.0 Scope of Testing

 All tank-type gravity toilet fixtures must conform to the requirements of Section 2.0 of this
 appendix, which address the adjustability of original equipment tank trim and the resulting flush
 volume of the toilet fixture. All tank-type gravity toilet fixtures with flush seals must conform to
 the requirements in Section  3.0 of this appendix, which address the flush volume resulting from
 the replacement of original equipment seals with seals available in the after market.

 2.0 Tank-Type Gravity Toilets With Original Equipment

       2.1    Purpose of Test
              The objective of this tank trim adjustability test is to determine the upper limit to
              the volume of water that may be discharged by the field adjustment of tank trim
              components.  The maximum volume of water that may be discharged by the
              toilet, when field adjustment of original equipment tank trim is set at its maximum
              water-use setting, shall not exceed the  following amounts:
                     For single flush fixtures - 1.68 gallons (6.4 liters) per flush
                     For dual flush fixtures:
                            Reduced flush ("short flush") mode - 1.40 gallons (5.3 liters) per
                                  flush
                            Full flush mode - 2.00 gallons (7.6 liters) per flush
              The following test procedure shall be used to verify that the toilet sample meets
              these requirements.

       2.2    Test Procedure
              Test shall be  conducted per section 8.4 of ASME A112.19.2 with the following
              modifications:
              2.2.1   The toilet shall be installed on a leveled test stand and all adjustable tank
                     trim components (any field adjustment features in the tank that might
                     increase the toilet flush volume) shall  be adjusted to the maximum water
                     use setting, while taking care not to damage or alter the parts.
              2.2.2  The water level in the tank shall be set to 0.25 ± 0.06  inch (6 ± 2 mm)
                     below the top of the overflow tube.  Where the tank utilizes  an internal
                     containment vessel and does not possess an overflow tube, the vessel
                     shall be filled to a level 0.25 ± 0.06  inch (6 ± 2 mm) below the top rim of
                     the vessel or to the manufacturer's  designated water line, whichever is
                     higher.
              2.2.3  The static pressure of the water supply shall be adjusted to 80 ± 2 PSIG.
              2.2.4  The toilet shall be flushed maintaining the activator in the flushing position
                     for a period of one  (1) second, the water being drained into a container.
              2.2.5  After the flush cycle is complete, the total flush volume shall be observed
                     and recorded.
 10 Testing protocol based on Los Angeles Department of Water and Power Supplementary Purchase Specification, 16 November
 2005 version, modified to reflect the deletion of certain trim durability and marking requirements incorporated into ASME A112 19.5.
Version 1.0                                C-1                                   January 24, 2007

-------
EPA                                                               Tank-Type High-Efficiency
AA/atCTSCTISC                                                       Toilet Specification
              2.2.6   This procedure shall be repeated until five (5) sets of data are obtained.
              2.2.7   The static pressure of the water supply shall be adjusted to 20 ± 2 PSIG
                     or at the manufacturer's recommended minimum pressure as noted in the
                     product literature and product packaging, and test procedure steps 2.2.4
                     to 2.2.6 shall be repeated.
              2.2.8   For dual-flush toilet fixtures, this test shall be conducted at both full flush
                     and reduced flush modes.

       2.3    Report: The five (5) individual flush volumes and the average of the five (5) runs
              shall be reported for each of the two static water supply pressures specified.

       2.4    Performance Requirement: The average total flush volume for five (5) test runs
              for each of the two static water supply pressures shall not exceed the following:
                     For single-flush fixtures - 1.68 gallons (6.4 liters) per flush
                     For dual-flush fixtures:
                            Reduced flush ("short flush") mode - 1.40 gallons (5.3 liters) per
                                  flush
                            Full flush mode - 2.00 gallons (7.6 liters) per flush
              The volume of water may be determined visually using a graduated container or
              by weight calculated as a unit to volume unit.

 3.0 Tank-Type Gravity Toilets With After-Market Closure Seals

       3.1     Purpose  of Test
              The objective of this tank trim adjustability and after-market seal test is to
              determine the upper limit to the volume of water that may be discharged when an
              off-the-shelf replacement flush valve seal/flapper is installed on the toilet. The
              maximum volume of water that may be discharged by the toilet, when the original
              equipment flush valve seal (flapper or other sealing device) is replaced with a
              standard (buoyant) seal available in home improvement centers and hardware
              stores, and the field adjustment of tank trim is set at its maximum water-use
              setting, shall not exceed the following amounts:
                     For single flush fixtures - 1.68 gallons (6.4 liters) per flush
                     For dual flush fixtures:
                            Reduced flush ("short flush") mode - 1.40 (5.3 liters) gallons per
                                  flush
                            Full flush mode - 2.00 gallons (7.6 liters) per flush
              The following test procedure shall be used to verify that the toilet sample meets
              these requirements.

       3.2    Test Procedure
              Test shall be conducted per section 8.4 of ASME A112.19.2 with the following
              modification:
              3.2.1   The toilet shall be installed on a leveled test stand and all adjustable tank
                     trim components (any field adjustment features in the tank that might
                     increase the toilet flush volume) shall be adjusted for maximum water
                     use, while taking care not to damage or alter the parts.
Version 1.0                                C-2                                   January 24, 2007

-------
EPA                                                                 Tank-Type High-Efficiency
AA/atCTSCTISC                                                        Toilet Specification
              3.2.2   Remove the original equipment flush valve seal and replace it with a
                      standard (buoyant) non-adjustable after-market seal/flapper for that toilet
                      where possible. In the case of a standard configuration 2-inch flush
                      valve, a Fluidmaster Bullseye Super flapper (part no. 501) or a Coast
                      Foundry Ultra Blue flapper shall be used. For non-standard flush valves,
                      including 3-inch flush valves, one or more replacement seals available at
                      hardware,  plumbing supply, and building supply stores or from the
                      manufacturer or other recognized  source shall  be used11.
              3.2.3   The water  level in the tank shall be set to 0.25 ± 0.06 inch (6 ± 2 mm)
                      below the top of the overflow tube. Where the tank utilizes an internal
                      containment vessel and does not possess an overflow tube, the vessel
                      shall be filled to a  level 0.25 ± 0.06 inch (6 ± 2 mm) below the top rim of
                      the vessel  or to the manufacturer's designated  water line, whichever is
                      higher.
              3.2.4   The static pressure of the water supply shall  be adjusted to 80 ± 2 PSIG.
              3.2.5   The toilet shall be flushed maintaining the activator in the flushing position
                      for a period of one (1) second maximum, the water being drained into a
                      container.
              3.2.6   After the flush cycle is complete, the total flush volume shall be observed
                      and recorded.
              3.2.7   This procedure shall be repeated until five (5) sets of data are obtained.
              3.2.8   The static pressure of the water supply shall  be adjusted to 20 ± 2 PSIG
                      or at the manufacturer's recommended minimum pressure as noted in the
                      product literature and product packaging, and test procedure steps 3.2.5
                      to 3.2.7. shall be repeated.
              3.2.9   For  dual-flush toilet fixtures, this test shall be conducted at both flush
                      modes (full flush and reduced flush).

        3.3    Report: The five (5) individual flush volumes and the average of the five (5) runs
              shall be reported for each of the two static water supply pressures specified.

        3.4    Performance Requirement: The average total flush volume for five (5) test runs
              for each of the two static water supply pressures shall  not exceed the following:
                      For  single-flush fixtures - 1.68 gallons (6.4 liters) per flush
                      For  dual-flush fixtures:
                             Reduced flush ("short flush") mode -  1.40 gallons (5.3 liters) per
                                   flush
                             Full flush mode - 2.00 gallons (7.6 liters) per flush
              The volume of water may be determined visually using a graduated container or
              by weight calculated as a unit to volume unit.
 11 Where neither the Fluidmaster Bullseye Super flapper nor the Coast Foundry Ultra Blue flapper fit the flush valve, where a 3-inch
 flush valve is employed, or in the case of a toilet fixture with a non-standard flush valve seal, the testing laboratory shall have
 discretion as to which after-market flapper or seal shall be used in the test.
Version 1.0                                 C-3                                    January 24, 2007

-------
EPA                                                             Tank-Type High-Efficiency
WaterSdlSe                                                     Toilet Specification
          Appendix D: Informative Annex for WaterSense Labeling

 The following requirements must be met for products to be marked with the WaterSense label.

 1.0 WaterSense Partnership

 The manufacturer of the product must have a signed partnership agreement in place with EPA.

 2.0 Conformity Assessment

 Conformance to this specification must be certified by a body either accredited by ANSI in
 accordance with the WaterSense certification scheme, or otherwise approved for that purpose
 by EPA.
 3.0 Prior Testing

 Products previousl
 under this specification.
Products previously tested under the predecessor UNAR specification12 must still be certified
 12 Uniform North American Requirements (UNAR) for toilet fixtures, a supplementary specification developed in 2005 for water
 utilities.
Version 1.0                               D-1                                  January 24, 2007

-------