Environmental Technology Verification

Test Report of Control of Bioaerosols in
HVAC Systems
AAF International
DriPak® 90/95%
              Prepared by
           Research Triangle Institute

          HRTI
          INTERNATIONAL
            Under a Contract with
         U.S. Environmental Protection Agency
          r&FPA
          mSK£ ^H I  f\
EIV EW  ET

-------
            THE ENVIRONMENTAL TECHNOLOGY VERIFICATION PROGRAM
  &EPA
U.S. Environmental Protection Agency
                                           HRTI
                                           INTERNATIONAL
                                          Research Triangle Institute
                        ETV Joint Verification Statement
        TECHNOLOGY TYPE:    VENTILATION MEDIA AIR FILTER
        APPLICATION:
FILTRATION EFFICIENCY OF BIOAEROSOLS IN
HVAC SYSTEMS
        TECHNOLOGY NAME:   DriPak® 90/95%
        COMPANY:

        DDRESS:

        WEB SITE:
        E-MAIL:
AAF International

PO Box 35690             PHONE:(502) 637-0340
Louisville, KY 40232-5690  FAX:   (502)637-0676
http://www.aafintl.com
Mmontague@aafintl.comm
     The U.S. Environmental Protection Agency (EPA) has created the Environmental Technology
     Verification (ETV) Program to facilitate the deployment of innovative or improved
     environmental technologies through performance verification and dissemination of information.
     The goal of the ETV Program is to further environmental protection by substantially accelerating
     the acceptance and use of improved and cost-effective technologies. ETV seeks to achieve this
     goal by providing high quality, peer-reviewed data on technology performance to those involved
     in the design, distribution, financing, permitting, purchase, and use of environmental
     technologies.

     ETV works with recognized standards and testing organizations; stakeholder groups which
     consist of buyers, vendor organizations, permitters, and other interested parties; and with the full
     participation of individual technology developers. The program evaluates  the performance of
     innovative and improved technologies by developing test plans that are responsive to the needs
     of stakeholders, conducting field or laboratory tests (as appropriate), collecting and analyzing
     data, and preparing peer-reviewed reports.  All evaluations are conducted in accordance with
     rigorous quality assurance protocols to ensure that data of known and adequate quality are
     generated and that the results are defensible.

     EPA's National Risk Management Research Laboratory contracted with the Research Triangle
     Institute (RTI) to establish a homeland-security-related ETV Program for products that clean
     ventilation air.  RTI evaluated the performance of ventilation air filters used in building heating,
     ventilation and air-conditioning (HVAC) systems. This verification statement provides a
     summary of the test results for the AAF International DriPak® 90/95% media air filter.
                                             S-l

-------
VERIFICATION TEST DESCRIPTION
All tests were performed in accordance with RTFs "Test/Quality Assurance Project Plan:
Biological Testing of General Ventilation Filters," which was approved by EPA. Tests were
performed for the following:
   •   Bioaerosol filtration efficiency tests of the clean and dust-loaded filter. Three bioaerosols
       were used in the testing:
          o  The spore form of the bacteria Bacillus atrophaeus (BG), a gram-positive spore-
             forming bacteria elliptically shaped with dimensions of 0.7 to 0.8 by 1 to 1.5 //m,
          o  Serratia marcescens, a rod-shaped gram-negative bacteria with a size of 0.5 to
             0.8 by 0.9 to 2.0 //m, and
          o  The bacterial virus (bacteriophage) MS2 dispersed as a micrometer-sized
             poly disperse aerosol.
   •   Inert aerosol filtration efficiency tests consisting of an American National Standards
       Institute (ANSI)/American Society of Heating, Refrigerating and Air-Conditioning
       Engineers (ASHRAE)  Standard 52.2-1999 type test (0.3 to 10 |im) and extended
       fractional efficiency measurements down to 0.02 jim particle diameter on both clean and
       dust-loaded filter.
   •   ASHRAE 52.2 test. This test provides filtration efficiency results (average of the
       minimum composite efficiency) given for three size ranges of particles: El, 0.3 to 1.0
       //m; E2, 1.0 to 3.0 //m; and E3, 3.0 //m to 10 //m.
VERIFIED TECHNOLOGY DESCRIPTION
As shown in Figure 1, the AAF International
DriPak® 90/95% media air filter is a extended
surface pocket filter with nominal dimensions of
0.61 xO.61 xO.31 m (24 x 24 x 30 in.). The filter
has an extended metal header and eight bags (or
pockets). The filter media color is yellow.  The
media is micro-glass. The part number is 729-
118-300.
VERIFICATION OF PERFORMANCE
                                                 Figure 1. Photograph of the AAF International
                                                        DriPak® 90/95% media filter.
Verification testing of the AAF International
DriPak® 90/95% media air filter began on
September 15, 2003 at the test facilities of RTI and was completed on October 16, 2003. The
results for the bioaerosol filtration efficiency tests are presented in Table 1 for the clean and dust-
loaded filter.  Table 2 presents the results of the ASHRAE 52.2 test. All tests were conducted at
an air flow of 0.93 nrVsec (1970 cfm).
                                           S-2

-------
                             Table 1. Bioaerosol Filtration Results

Clean
Dust loaded
Pressure Drop
Pa (in. H2O)
104 (0.64)
348(1.40)
Filtration
Efficiency for
Removal of
B. atrophaeus , %
99
99
Filtration
Efficiency for
Removal of
S. marcescens, %
99
99
Filtration
Efficiency for
Removal of
MS2 phage, %
95
99
                           Table 2. Summary of ASHRAE 52.2 Test

AAF International
DriPak® 90/95%
El
0.3 to 1.0 //m,
%
87
E2
1.0to3.0//m,
%
99
E3
3.0 to 10 //m,
%
99
Minimum Efficiency
Reporting Value
(MERV)
15 at 93 nrVsec
(1970 cfm)
The quality assurance officer reviewed the test results and the quality control data and concluded
that the data quality objectives given in the approved test/QA plan were attained.

This verification statement addresses two performance measures of media air filters: filtration
efficiency and pressure drop. Users of this technology may wish to consider other performance
parameters such as service life and cost when selecting a media air filter for bioaerosol control.
In accordance with the test/QA plan1, this verification statement is applicable to filters
manufactured from December 2003 through November 2006.
Original signed by E. Timothy Oppelt 12/8/2003
E. Timothy Oppelt                   Date
Director
National Homeland Security Research Center
Office of Research and Development
United States Environmental Protection Agency
Original signed by David S. Ensor 12/4/2003
David S. Ensor                    Date
Director
ETV-HS
Research Triangle Institute
   NOTICE: ETV verifications are based on an evaluation of technology performance under specific, predetermined
   criteria and the appropriate quality assurance procedures. EPA and RTI make no expressed or implied warranties
   as to the performance of the technology and do not certify that a technology will always operate as verified. The
   end user is solely responsible for complying with any and all applicable federal, state, and local requirements.
   Mention of commercial product names does not imply endorsement.
                                             S-3

-------
Environmental Technology Verification
     Test  Report of Filtration  Efficiency of
         Bioaerosols in HVAC Systems

            AAF International DriPak® 90/95%
          EPA Contract No. GS10F0283K-BPA-1, Task Order 1101
                    RTI Project No. 08787.001
                        Prepared by:

                    Research Triangle Institute
                   Engineering and Technology
                 Research Triangle Park, NC 27709
              GS10F0283K-BPA-1, EPA Task Order 1101
                    RTI Project No. 08787.001
                     EPA Project Manager:
                       Theodore G. Brna
              Air Pollution Prevention and Control Division
             National Risk Management Research Laboratory
                Office of Research and Development
                U.S. Environmental Protection Agency
                 Research Triangle Park, NC 27711
                       December 2003

-------
                                        Notice

This document was prepared by the Research Triangle Institute (RTI) with funding from the U.S.
Environmental Protection Agency (EPA) through the General Service Administration Contract
No. GS10F0283K per EPA's BPA-1, Task Order 1101. The document has undergone RTI and
EPA peer and administrative reviews and has been approved for publication. Mention of
corporation names, trade names, or commercial products does not constitute endorsement or
recommendation for use of specific products.

                                       Foreword

The Environmental Technology Verification (ETV) Program, established by the U.S.
Environmental Protection Agency (EPA), is designed to accelerate the development and
commercialization of new or improved environmental technologies through third-party
verification and reporting of performance.  The goal of the ETV Program is to verify the
performance of commercially ready environmental technologies through the evaluation of
objective and quality-assured data so that potential purchasers and permitters are provided with
an independent and credible assessment of the technology that they are buying or permitting.

EPA's National Risk Management Research Laboratory contracted with the Research Triangle
Institute (RTI) to establish a homeland-security related ETV Program for products that clean
ventilation air. RTI developed (and EPA approved) the "Test/Quality Assurance Plan for
Biological Testing of General Ventilation Filters1." The test described in this report was
conducted following this plan.
                                 Availability of Report

Copies of this verification report are available from

•      Research Triangle Institute
       Engineering and Technology Unit
       PO Box 12194
       Research Triangle Park, NC 27709-2194

•      U.S. Environmental Protection Agency
       Air Pollution Prevention and Control Division, E305-01
       109 T.W. Alexander Drive
       Research Triangle Park, NC 27711

Web sites:     http://www.epa.gov/etv/verifications
                                           11

-------
                                   Table of Contents

ETV Joint Verification Statement	S-l
Notice	ii
Foreword 	ii
Availability of Report	ii
Table of Contents	iii
Acronyms/Abbreviations	iv
Acknowledgments	v
1.0    Introduction	1
2.0    Product Description	1
3.0    Test Procedure	1
4.0    Test Results	4
5.0    Limitations and Applications	6
6.0    References	6
Appendix:  ASHRAE 52.2 Test Report	7
                                        Figures

Figure 1. Photograph of the AAF International DriPak® 90/95% Media Filter	1
Figure 2. Schematic of Test Duct	2
Figure 3. Summary of the Inert Aerosol Filtration Efficiency Data for the Clean and
       Dust-Loaded Filter, # 2 	5
Figure A-l. Filtration Efficiency and Flow Resistance for AAF International DriPak® 90/95%
       Media Filter	10
                                         Tables

Table 1. Numbers of Filters and Expected Utilization	4
Table 2. Bioaerosol Filtration Results for Filter # 2	4
Table 3. Summary of Removal Efficiency Using ASHRAE 52.2 Test for Filter # 1	4
Table 4. DQOs for Precision of Filtration Efficiency Measurements for Culturable Bioaerosol... 5
                                           in

-------
                               Acronymns/Abbreviations
ANSI         American National Standards Institute
ASHRAE     American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ASME        American Society of Mechanical Engineers
B             Bacillus
BG           Bacillus atrophaeus (formerly B. subtilis var niger and Bacillus globigif)
cfm           cubic feet per minute
CPU          colony forming unit
cm           centimeter
dso           median diameter (of particle)
DQO         data quality objective
EPA          U.S. Environmental Protection Agency
ETV          Environmental Technology Verification
F             Fahrenheit
fpm           feet per minute
HS           homeland security
in.            inch(es)
KC1           potassium chloride
kPa           kilopascal(s)
L             liter(s)
MERV        minimum efficiency reporting value
m             meter(s)
mm           millimeter(s)
mL           milliliter(s)
min           minute(s)
//m           micrometer(s)
NAFA        National Air Filtration Association
nm           nanometer(s)
OPC          optical particle counter
QA           quality assurance
QC           quality control
Pa            pascal(s)
PFU          plaque forming units
psig           pounds per square inch gauge
RTI           Research Triangle Institute
SAE          Society of Automotive Engineers
SMPS        scanning mobility particle sizer
                                           IV

-------
                                  Acknowledgments

The authors acknowledge the support of all of those who helped plan and conduct the
verification activities. In particular, we would like to thank Ted Brna, EPA's Project Manager,
and Paul Groff, EPA's Quality Assurance Manager, both of EPA's National Risk Management
Research Laboratory in Research Triangle Park, NC. We would also like to acknowledge the
assistance and participation of our stakeholder group for their input, as well as Al Veeck and the
National Air Filtration Association (NAFA), and Intertek ETL SEMKO, especially Theresa
Peck, for their help in acquiring the filters, and AAF International for donating the filters to be
tested.

For more information on the AAF International DriPak® 90/95% filter, contact

Michael Montague
AAF International
PO Box 35690
Louisville, KY 40232-5690
Telephone: (502) 637-0340, FAX (502) 637-0676
Email: Mmontague@aafintl.com
Web site: http://www.aafmtl.com

For more information on RTFs ETV program, contact

Debbie Franke
Research Triangle Institute
PO Box 12194
Research Triangle Park, NC 27709-2194
Telephone: (919) 541-6826
Email: dlf@rti.org

-------
1.0    Introduction
EPA's National Risk Management Research Laboratory contracted with the Research Triangle
Institute (RTI) to establish a homeland-security related ETV Program for products that clean
ventilation air. RTI convened a group of stakeholders representing government and industry
with knowledge and interest in the areas of homeland security and building ventilation.  The
group met in December 2002 and recommended technologies to be tested. RTI then developed
(and EPA approved) the "Test/Quality Assurance Plan for Biological Testing of General
Ventilation Filters1."  The first round of tests included ten types of filters.  The tests described in
this report were conducted following this plan.
2.0    Product Description
As shown in Figure 1, AAF International DriPak®
90/95% media air filter is an extended surface
pocket filter with nominal dimensions of 0.61 by
0.61 by 0.78 m (24 by 24 by 30 in.). The filter has
an extended metal header and eight bags (or
pockets). The filter media color is yellow. The
media is micro-glass. The part number is 729-118-
300.

3.0    Test Procedure
The test program measured the culturable bioaerosol
removal efficiency of general ventilation filters.
Three tests were required to accomplish this goal.
First, the American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc.
(ASHRAE) Standard 52.22 test was performed on one filter to determine the minimum efficiency
reporting value (MERV) of the filter.  After determining the MERV, the biological test using
three different bioaerosols and an inert aerosol test on both clean and fully dust-loaded filters
was performed on a second filter. All tests were at an air flow rate of 0.93 m3/sec (1970 cfm) to
conform to the conditions described in ASHRAE Standard 52.2.

All testing was performed in a test duct as specified in ASHRAE Standard 52.2. A schematic of
the test duct is shown in Figure 2. The test section of the duct is 610 mm (24 in.) by 610 mm (24
in.) square.  The locations of the major components, including the sampling probes, device
section (filter holder), and the aerosol generator (site of aerosol injection) are shown.

The inert testing and the ASHRAE Standard 52.2 test were performed using a potassium chloride
(KC1) aerosol. The filters were loaded using ASHRAE dust, composed of 72% Society of
Automotive Engineers (SAE) fine, 23% powdered carbon, and 5% cotton linters. The final
pressure drop was determined by the Standard's requirements.
Figure 1. Photograph of the AAF International
DriPak® 90/95% Media Filter.

-------
                  Exhaust
                    to
                   Room
Outlet Filter Bank
                 ASME
                 Nozzle
   Room
    Air
                    I.
      i            1
    ^n^f           _
Biological
Sampling
               Downstream Mixer
            X
           6
  Blower
£

i © ' ^
f F \
Fr5;
&
^
Inlet Filter / Upstream ^
Bank / Mivor i&

|
| Device Backup
i Section Filter
1 Holder
a (Used When
' "— ' Dust-loading)
Aerosol Bioloqical
Generator Sampling
            Flow Control
               Valve
        Figure 2.  Schematic of Test Duct. Filter is placed in device section.

The bioaerosol tests were conducted using three microorganisms,  two bacteria and one bacterial
virus.  The spore form of the bacteria Bacillus atrophaeus  (formerly B. subtilis var niger and
Bacillus globigii or BG) was used as the simulant for gram-positive spore-forming bacteria.  The
BG spore is elliptically shaped with dimensions of 0.7 to 0.8 by 1 to 1.5 //m. Serratia
marcescens was used as the surrogate for rod-shaped gram-negative bacteria. S. marcescens is
0. 5 to 0. 8 by 0.9 to 2.0 //m.

The bacterial virus (bacteriophage) MS2 (0.02 to 0.03 //m), having approximately the same
aerosol characteristics as a human virus, was used as a surrogate for the viruses of similar and
larger size and shape. Although the individual virus particles are in the submicrometer size
range, the test particle size planned for the virus tests will span a range of sizes (poly dispersed
bioaerosol). This test was not designed to study the removal efficiencies for single individual
virus particles; rather, it was designed to determine the removal efficiencies for virus particles as
they are commonly found indoors. A representative challenge would be a micrometer-sized,
polydispersed aerosol containing the phage because:
•   The aerosols created from sneezing and coughing vary in size from < 1 to > 20 //m, but the
    largest particles settle out and only the smaller  sizes remain in the air for extended periods for
    potential removal by  an air cleaner;
•   Few viruses have been found associated with particles less than 1  //m; and
•   Nearly all 1 to 2 //m particles are deposited in the respiratory tract, while larger particles may
    not be respired.

Bacteria suspension preparation for the aerosolization process required that the specific test
organism be grown in the laboratory and the suspension prepared for aerosol generation in the
test rig. The microbial challenge suspensions were prepared by inoculating the test organism on
solid or liquid media, incubating the culture until mature, wiping organisms from the surface of
the pure culture (if solid media), and eluting them into sterile diluent to a known concentration.

-------
The bacterial virus challenge was prepared by inoculating a logarithmic phase broth culture of
the host bacteria with phage and allowing it to multiply until the majority of the host bacteria
were lysed.  The mixture was centrifuged to remove the majority of the cell fragments. The
resultant supernatant was the phage stock and was used as the challenge aerosol. The
concentration of the phage stock was approximately 1 x 109 or higher plaque forming units per
milliliter, (PFU)/mL.

The challenge organism suspensions were aerosolized using a Collison nebulizer (BGI,
Waltham, MA) at 103.4 kPa (15 psig) air pressure. The nebulizer generates droplets with an
approximate volume mean diameter of 2 //m.  The particle diameter after the water evaporates
depends on the  solids content of the suspension. Particle size was determined by the size of the
suspended organism (if singlets).

Upstream and downstream sampling of the bacteria was accomplished using a one-stage
Andersen viable bioaerosol sampler. The one-stage Andersen sampler is a 400-hole multiple-jet
impactor operating at 28 L/min. The dso is 0.65 //m. After sampling, the petri dishes were
removed from the sampler and incubated at appropriate times and temperatures for the test
organism being used. Colony forming units (CPUs) were then enumerated and their identity
confirmed.

The microbial viruses were collected in AGI-30s.  The AGI-30 is a high velocity liquid impinger
operating at a flow rate of 12.3  to 12.6 L/min. The dso is approximately 0.3 //m.  The AGI-30 is
the sampler against which the other commonly used bioaerosol samplers are often compared.

For the inert aerosol filtration efficiency measurements, the particle sizing measurements were
made with two particle counting instruments: a Climet model 500 spectrometer/optical particle
counter (OPC) covering the particle diameter size range from 0.3 to 10 //m in 12 particle sizing
channels and a TSI scanning  mobility particle sizer (SMPS) to cover the range from 0.03 (or as
low as 16 nm) to 0.5 //m.  In  the test/QA plan there is a data control parameter for the SMPS that
states the standard deviation on upstream counts be computed for each efficiency test based on
the upstream particle counts and be less than 0.30 before the data is used. The lower size ranges
for the SMPS are included only if they meet the data control parameter. (Table A2 of test/QA
plan).

Quality Control (QC) procedures for running the test duct and the measuring equipment are
defined in the test/QA plan.

The product tested was collected by the Intertek ETL SEMKO on July 1, 2003 following the
NAFA Product Certification Program Procedural Guide3. RTI provided oversight into the
selection of representative filters. For each filter type,  a box or a minimum of four filters were
procured and sent to RTI. The  filters were used as shown in Table 1.

Full details of the test method can be found in RTFs test/QA plan1.

-------
                    Table 1.  Numbers of Filters and Expected Utilization
Tests
ASHRAE Standard 52.22test
Initial efficiency for an inert aerosol
Initial efficiency for three bioaerosols
Dust load to final pressure drop with ASHRAE dust
Efficiency for inert aerosol after dust-loading
Efficiency for three bioaerosols after dust-loading
Reserve filter*
Filter #
1
X






2

X
X
X
X
X

3






X
4






X
       *Filters # 3 and # 4 have been kept in reserve to be used if needed.

4.0    Test Results
The bioaerosol filtration efficiency results are found in Table 2.

                     Table 2.  Bioaerosol Filtration Results for Filter # 2
Filter
Condition
Clean
Dust-loaded
Pressure
Drop
Pa (in. H2O)
104 (0.64)
348(1.40)
Filtration
Efficiency for
Removal of
B. atrophaeus, %
99
99
Filtration
Efficiency for
Removal of
S. marcescens, %
99
99
Filtration
Efficiency for
Removal of
MS2 phage, %
95
99
The ASHRAE filtration efficiencies and the MERV are shown in Table 3. The filtration
efficiencies (average of the minimum composite efficiency) are presented by particle size
groupings: El, 0.3 to 1.0 //m; E2, 1.0 to 3.0 //m; and E3,  3.0 //m to 10 //m.  The full ASHRAE
52.2 test results are provided in the Appendix.

       Table 3. Summary of Removal Efficiency Using ASHRAE 52.2 Test for Filter # 1
Filter
AAF International
DriPak® 90/95%
El
0.3 to 1.0 //m, %
87
E2
1.0to3.0//m, %
99
E3
3.0 to 10 //m, %
99
MERV
15 at 93 mVsec
1970 cfm

-------
The filtration efficiency for inert particles is plotted so that the efficiencies for particles from
about 0.03 to 10 //m can be observed (Figure 3).  Note that this is a logarithmic base 10 scale on
the x axis. Two instruments were used to obtain the measurements.  The SMPS was used to
measure particles up to 0.5 //m and the OPC was used for particles from 16 nm to 10 //m.  These
measurements were made on a filter when clean and then when dust-loaded.

The quality assurance officer has reviewed the test results and the quality control data and has
concluded that the data quality objectives (DQOs) (Table 4) given in the approved test/QA plan
have been attained.

  Table 4. DQOs for Precision of Filtration Efficiency Measurements for Culturable Bioaerosol
Data quality objective
Precision of filtration
efficiency, %
Test organism
Spore-forming bacteria
(B. atrophaeus)
±8a
Vegetative bacteria
(S. marcescens)
± lla
Bacterial virus
(MS2 phage)
±13a
a Based on +/- one standard deviation of penetration computed from the coefficient of variance
upstream and downstream culturable counts.
                  100.
                    80.
                    60.
               c
               
-------
5.0    Limitations and Applications

This verification report addresses two performance measures of media air filters: filtration
efficiency and pressure drop. Users may wish to consider other performance parameters such as
service life and cost when selecting a general ventilation air filter for their application.

In accordance with the test/QA plan1, this verification statement is applicable to filters
manufactured from December 2003 through November 2006.

6.0    References

1.  RTI. 2003.  Test/QA Plan for Biological Testing of General Ventilation Filters. Research
   Triangle Institute, Research Triangle Park, NC.

2.  ANSI/ASHRAE Standard 52.2-1999, Method of Testing General Ventilation Air-Cleaning
   Devices for Removal Efficiency by Particle Size, American Society of Heating, Refrigerating
   and Air-Conditioning Engineers, Atlanta, GA.

3.  NAF A (National Air Filtration Association). 2001. Product Certification Program
   Procedural Guide Approved Version 1, Second Revision, February 2001. Virginia Beach,
   VA.

-------
      Appendix ASHRAE 52.2 Test Report

       For AAF International DriPak 90/95%
ASHRAE 52.2 TEST REPORT

Manufacturer:     AAF International
Product Name:     DriPak 90/95%
ETV ID Number:    AAF1-A

  RTI Report No.   AY09150302
         Test Laboratory:
              RTI
          919-541-6941
                  7

-------
                                                                                   Page 1 of 3
                    ASHRAE Std. 52.2 Air Cleaner Performance Report Summary
                    	This report applies to the tested device only.	
Laboratory Data
RTI Report No.
Test Laboratory
Operator
Particle Counter(s):

Device Manufacturer's Data
Manufacturer
Product Name
Product Model
Test requested by
Sample obtained from
Catalog rating:
Specified test conditions:
Device Description
Nominal Dimensions (in.):
Generic name
Amount and type of adhesive
Other attributes

Test Conditions
Airflow (cfm)
Face Velocity (fpm)
Test aerosol type:
Remarks

Resistance Test Results
Initial resistance (in. wg)
                                 AY09150302
                     Date
           9-15-03
                                 Research Triangle Institute
                                 Clayton	
                                 Brand
Climet
Supervisor  Owen/Hanley
Model                 500
                                 AAF International
                                 DriPak 90/95%
                                 Extended Surface Filter
                                 EPA	
                                 NAFA
                                 Airflow rate
                                 Airflow (cfm)
                                 Face Velocity (fpm)
                                 24x24x30
              NA
             1970
      Initial dP (in. wg)
      Final dP (in. wg)
            NA
           1.40
                                                          493
           (height x width x depth)
                                 bag filter
                      Media color   yellow
                                 NA
                                 8 pockets, external metal header
                                    1970
   Temperature (F)
    74
                                    493
   Final Pressure Drop (in. wg)
RH (%)
 1.40
48
                                     KCI
                                    0.70
           Final resistance (in. wg)
                  1.40
                                                87
Minimum Efficiency Reporting Data
Composite average efficiencies              E1	
Air cleaner average Arrestance per Std 52.1:
Minimum efficiency reporting value (MERV) for the device:
                                                 8
                  E2     99
                      E3
            99
                                                          NA
                                                                         15
                                      1970   cfm

-------
                     Report No.  AY09150302

                     Research Triangle Institute
         90

         80
           	i	
      S1
      I  60
      'o
      it  50
      111
         20

         10
         40	
         30--
                                               	
          Initial Efficiency


          After 1st loading


          After 2nd loading


          After 3rd loading


          After 4th loading


          After 5th loading
           0.1                    1                     10
                  Particle Diameter (micrometers)
      Minimum Composite Curve
    Particle Diameter (micrometers)
Resistance to Airflow
   for clean filter





'







J
20-
10-
n
i


i
i
i
i
i
i
i
i
i

i
	 i 	
i
	 i —
i
i



>










-
-


i
/
f










_
-

>













-
-

ff


i
i
i
i
i
i
i
i
i

i
_L
I
4-
I

*
I


I
I
I
I
I
I
I
I
I

I
_L
I
4
I















	
	

I


I
I
I
I
I
I
I
I
I

I
	 I _
I
	 1 -
I















-
-

I I


I I
I I
I I
I I
I I
I I
I I
I I
I I

I I
_l J_
I I
-I 4-
I I

I


I
I
I
I
I
I
I
I
I

I
J_
I
4-
I
1
1-



O U-8
107-






(0 u-4
CO n q
a
& 07-
0 1-
D n-












































S
/
S
s









s
/










/
/
/













                                              500    1000   1500   2000
                                                   Air Flow (cfm)
                                                                         2500
Figure A-1.  Filtration Efficiency and Flow Resistance Curves for

             AAF International DriPak 90/95% Filter.

-------
                                             TABULATED DATA SUMMARY
                                             Report No. AY09150302
                                             Research Triangle  Institute
Summary of Test Conditions:
Product Manufacturer
Product Name
Nominal Dimensions (in.)
Airflow (cfm)
Final Resistance (in. H2O)
OPC Channel Number
Min. Diam. (urn)
Max. Diam. (urn)
Geo. Mean Diam. (urn)
Initial efficiency
after first dust load
after second dust load
after third dust load
after fourth dust load
after fifth dust load
Minimum Composite Efficiency (%)
                     AAF International
                     DriPak 90/95%
                     24 x 24 x 30
                       1970
                       1.40
                                                   Efficiency (%) per Indicated Size Range
1
0.3
0.4
0.35
2
0.4
0.55
0.47
3
0.55
0.7
0.62
4
0.7
1
0.84
5
1
1.3
1.14
6
1.3
1.6
1.44
7
1.6
2.2
1.88
8
2.2
3
2.57
9
3
4
3.46
10
4
5.5
4.69
11
5.5
7
6.20
12
7
10
8.37
Run No.
AY091 50303
AY09 160301
AY09 160302
AY091 60303
AY09 170301
AY09 170302

81
73
80
80
87
93

89
84
89
88
92
100

94
95
98
99
99
100

97
98
99
99
99
100

99
99
99
99
99
100

99
99
100
99
99
100

99
99
100
99
99
100

99
99
99
100
100
100

99
99
100
100
99
100

99
99
99
100
100
100

99
99
99
100
100
100

99
100
99
100
100
100
                         73
                      84
    94
97
99
99
99
99
99
99
99
99
E1 =
E2 =
E3 =

MERV'
87
99
99

15
(E1  is the average of the minimum composite efficiency values for particle diameters from 0.3 to 1 urn.)
(E2 is the average of the minimum composite efficiency values for particle diameters from 1 to 3 urn.)
(E3 is the average of the minimum composite efficiency values for particle diameters from 3 to 10 urn.)
Resistance to Airflow for Clean Filter:
Airflow
    50
    75
   100
   125
   Airflow
    (m3/s)

    0.465
    0.697
    0.930
    1.162
            Airflow
             (cfm)

              985
             1478
             1970
             2463
Air Velocity   Air Velocity
  (fpm)          (m/s)
   246
   369
   493
   616
     1.251
     1.876
     2.502
     3.127
         Resistance
         (in. H2O)

           0.30
           0.49
           0.70
           0.95
                Resistance
                  (Pa)

                   73
                  122
                  174
                  235
Resistance to Airflow with Loading at 0.93 m3/s (1970 cfm)
Initial
After first dust load
After second dust load
After third dust load
After fourth dust load
After fifth dust load
                     Resistance
                     (in. H2O)

                        0.70
                        0.73
                        0.88
                        1.05
                        1.23
                        1.40
                         Resistance
                           (Pa)

                           174
                           180
                           218
                           261
                           305
                           348
Weight Gain of filter after completion of dust loading steps
                                                  300.3 g
                                                   10

-------