Version 1, August 17, 2006
               Environmental Technology Verification

           Test/QA Plan for Biological and Aerosol Testing
                  of General Ventilation Air Cleaners
                     EPA Cooperative Agreement R-83191101
                     Research Triangle Institute Project 09309
                                Prepared by:

                     Air Pollution Control Technology Center
                          Research Triangle Institute
                          Research Triangle Park, NC
Approved by:

APCT Center Director:	Signed by Andrew Trenholm, August 21, 2006
Andrew Trenholm

APCT Center Quality Manager:    Signed by Gary Eaton, August 21, 2006
W. Gary Eaton

EPA Project Officer: 	Signed by Michael Kosusko, August 30, 2006
Michael Kosusko

EPA Quality Manager:      Signed by Paul Groff, August 30. 2006	
Paul Groff
                                                          KRTI
                                                          INTERNATIONAL

-------
Research Triangle Institute                                                             Page ii
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
This document serves as the Test and Quality Assurance (QA) Plan for the verification of
general ventilation air cleaners that reduce aerosols and bioaerosols. This document was
developed under Cooperative Agreement R-83191101 between EPA and the Research Triangle
Institute for implementation of the air pollution control technology center of the environmental
technology verification program. The quality management plan under which this work is
conducted is the Quality Management Plan for Verification Testing of Air Pollution Control
Technology, Revision 2.2, June 2005.

-------
Research Triangle Institute                                                          Page iii
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
                               TABLE OF CONTENTS



Al: Title and Approval Sheet	i

A2: Table of Contents	iii

List of Figures	v

List of Tables	v

A3: Distribution List	vi

List of Acronyms/Abbreviations/Definitions	vii

SECTION A: PROJECT MANAGEMENT	1

A4: Project/Task Organization	1
      A4.1:  Management Responsibilities	1
             A4.1.1:  EPA Project Officer	1
             A4.1.2:  APCT Center Director	2
             A4.1.3:  RTI Task Leader	2
      A4.2:  Quality Assurance Responsibilities	3
             A4.2.1:  EPA Quality Manager	3
             A4.2.2:  APCT Center Quality Manager	3

A5: Problem Definition/Background Information	3

A6: Task Description and Schedule	5
      A6.1:  Task Description	5
             A6.1.1:  Identification and Acquisition of Devices	5
             A6.1.2:  Performance of ASHRAE 52.2-1999 Test	5
             A6.1.3:  Performance of Culturable Bioaerosol Testing	6
             A6.1.4:  Performance of Inert Particle Testing	6
             A6.1.5:  Preparation of Report	7
      A6.2:  Schedule	7

A7: Data Quality Objectives and Criteria for Measurement Data	7

A8: Special Training Requirements/Certification	8

A9: Documentation and Records	8
      A9.1:  Laboratory Documentation	9
             A9.1.1:  ASHRAE 52.2-1999 and Inert Aerosol Tests	9

-------
Research Triangle Institute                                                         Page iv
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

             A9.1.2: Bioaerosol Tests	9
      A9.2: QA Reports	9
      A9.3: Reporting	10
      A9.4: Verification Reports and Verification Statements	10

SECTION B: MEASUREMENT/DATA ACQUISITION	11

Bl: Test Design	11
      Bl.l: ASHRAE 52.2-1999 and Inert Testing	11
             Bl.1.1: Particle Counters	11
             Bl.l.2: Inert Aerosol Generation	12
             B1.1.3: Inert Conditioning Procedure for Devices with Media Under Test
                   Options 2 and 3	12
      B1.2: Culturable Bioaerosol Testing	12
             B 1.2.1: Test Organisms	13
             Bl.2.2: Bioaerosol Preparation and Generation	14

B2: Sampling Methods Requirements	15

B3: Sample Handling and Custody Requirements	15

B4: Analytical Methods Requirements	15

B5: Quality Control Requirements	15

B6: Instrument/Equipment Testing, Inspection, and Maintenance Requirements	15

B7: Instrument Calibration  and Frequency	15

B8: Inspect!on/Acceptance  Requirements for Supplies and Consumables	15

B9: Data Acquisition Requirements (Non-direct measurements)	16

BIO: Data Management	16
      B10.1:  Data Recording	16
      BIO.2:  Data Analysis	16
             BIO.2.1: Inert Aerosol Data	16
             B10.2.2: Bioaerosol Data	17
      B10.3:  Data Storage and Retrieval	18

SECTION C: ASSESSMENT/OVERSIGHT	19

Cl: Assessments and Response Actions	19
      Cl.l: Audits	19
      C1.2: Corrective Actions	19

-------
Research Triangle Institute                                                           Page v
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

C2: Reports to Management	20

SECTION D: DATA VALIDATION AND USABILITY	21

Dl: Data Review, Validation, and Verification Requirements	21

D2: Validation and Verification Methods	21

D3: Reconciliation with Data Quality Objectives	21

References	22

Appendix A:  Test Specifications	24

Appendix B: Inert Aerosol Run Sheet	30

Appendix C: Bioaerosol Run Sheet	32


                                  LIST OF FIGURES


Figure 1. Organization chart	2

Figure Al.  Schematic of test duct (top view) used for device testing	24


                                   LIST OF TABLES

Table 1. DQOs for Inert Aerosol Tests	7

Table 2. DQOs for Filtration Efficiency for Culturable Bioaerosol	8

Table 3 RTT's FTV Assessments                                                      19
_I_ Ck,\JL\J *J . .L\- -L _L iJ ' > _I_ V  .Tl.kJkJ^'kJkJlll^'llLkJ 	_L .s

Table Al.  Quality Control Parameters for Inert Aerosol Tests	25

Table A2.  Quality Control Parameters Associated with Scanning Mobility Particle Sizer (SMPS)
          and Conditioning Aerosol	27

Table A3.  Quality Control Parameters for Bioaerosols	28

Table A4.  Quality Control Parameters for the Test Duct	29

-------
Research Triangle Institute                                                           Page vi
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

A3: Distribution List

EPA
Mr. Michael Kosusko
Mr. Paul Groff

Research Triangle Institute
Mr. Clint Clayton
Dr. W. Cary Eaton
Ms. Karin Foarde
Ms. Deborah Franke
Mr. Michael Herman
Mr. James Hanley
Ms. Kathleen Owen
Ms. Lauren Pugh
Dr. C. E.  Tatsch
Mr. Andrew Trenholm
Ms. Tricia Webber

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

List of Acronyms/Abbreviations/Definitions
Page vii
ADQs
AGI
ANSI
ASHRAE
ASME
cm3
CPU
cfm
cm
CPC
culturable
CV
dso
DQO
EI, ฃ2, ฃ3
electret
EPA
Eq.
ETV
g
HEPA
in.
ISO
KC1
Kr
L
m3
MERV
min
min.
ML
m
mL
mm
MSDS
MS2
audits of data quality
all glass impinger
American National Standards Institute
American Society of Heating, Refrigerating, and Air-conditioning
Engineers
American Society of Mechanical Engineers
cubic centimeter(s)
colony forming unit
cubic feet per minute
centimeter(s)
condensation particle counter
able to be grown on microbiological media
coefficient of variance
50% cut point on Andersen sampler
data quality objective
average minimum particle-size efficiency designator of ASHRAE
a filter comprised of fibers that contain an embedded electrostatic
52.2
charge
U.S. Environmental Protection Agency
equation
Environmental Technology Verification Program
gram(s)
high efficiency particulate air
inch(es)
International Organization for Standardization
potassium chloride
Krypton
liter(s)
cubic meter(s)
minimum efficiency reporting value of ASHRAE 52.2
minimum
minute(s)
microbiology laboratory
meter(s)
milliliter(s)
millimeter(s)
material safety data sheet
bacterial virus or bacteriophage

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Page viii
OPC
PCO
PEs
PFU
PSE
psig
PSL
QA
QC
QM
QMP
RH
RTI
sec
SMPS
SOP
t
T/QAP
TSAs
//m
optical particle counter
photocatalytic oxidation
performance evaluations
plaque forming unit
particle size (removal) efficiency
pounds per square inch gauge
polystyrene-latex
quality assurance
quality control
quality manager
quality management plan
relative humidity
Research Triangle Institute
second(s)
scanning mobility particle counter
standard operating procedure
temperature
test/quality assurance plan
technical system audits
micrometer

-------
Research Triangle Institute                                                            Page 1
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

SECTION A: PROJECT MANAGEMENT

A4:  Project/Task Organization
The U.S. Environmental Protection Agency (EPA) established the Environmental Technology
Verification Program (ETV) to accelerate the development and commercialization of improved
environmental technology through third party verification and reporting of performance. Under a
cooperative agreement with EPA, Research Triangle Institute (RTI) operates the Air Pollution
Control Technology Center (APCT). RTI will verify the filtration efficiency and bioaerosol
inactivation efficiency of heating, ventilation and air conditioning (HVAC) air cleaners for
culturable bioaerosol and aerosol challenges. RTI will perform the testing, evaluate the data, and
prepare the verification reports and the verification statements.

The scope of this test/quality assurance (QA) plan (T/QAP) covers in-duct air cleaners based on
filtration, ultraviolet (UV) illumination, photocatalytic oxidation (PCO) and combinations of
those technologies, however the focus is on filters. The T/QAP with addendum for specific
technology can be used for UV, PCO and other technologies if they are compatible with the test
facilities and procedures of the T/QAP. It is anticipated that the devices tested will be compatible
with a nominal 24" x 24" test duct cross  section.

This T/QAP is based on previous work for three ETV-related projects. Stakeholder groups were
convened under these projects to provide input into the selection of technologies and into the
development of protocols and  T/QAPs.
•  Under the ETV Indoor Air Pilot, a test protocol1 and test plan2 were developed and validated
   for general ventilation media devices.
•  As part of the ETV Safe Buildings for homeland security, a test protocol3 and test plan4
   developed which included  bioaerosol testing.
•  Recently, the EPA Technology Testing and Evaluation Program (TTEP) developed a test
   method for testing UV light systems used in ventilation ducts for bioaerosols5.
The methods and procedures in these documents were supplemented based on RTFs experience
conducting testing for commercial clients for bioaerosols and testing based on American
National Standards Institute (ANSI)/American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc. (ASHRAE) Standard 52.2-19996, Method of Testing General
Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size (ASHRAE 52.2-1999).

The various QA and management responsibilities are divided between EPA and RTI key project
personnel as defined below. The lines of authority between key personnel for this project are
shown on the project organization chart in Figure 1.

A4.1:  Management Responsibilities
Project management responsibilities are divided among the EPA and RTI personnel as listed
below.

A4.1.1: EPA Project Officer
The EPA center project officer (EPA PO), Mr. Michael Kosusko, monitors and guides the
progress of the APCT Center.  The EPA PO has overall EPA ETV Program responsibility for the
quality of verification tests conducted by the center.  The EPA PO is responsible for coordinating

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Page 2
EPA QA and technical peer reviews and EPA approval of generic verification protocol (GVP)
revisions, test/QA plans (T/QAPs), and verification reports and statements. The EPA PO
recommends the resources necessary to meet project objectives and requirements.



EPA Project Manager
M. Kosusko


APCT Center Director
A. Trenholm


RTI Task Leader
D. Franke



Bioaerosol
K. Foarde, lead


_____



EPA Quality Manager
P. Groff

APCT Center
Quality Manager
W. C. Eaton



Inert Aerosols
J. Hanley, co-lead
K. Owen, co-lead


        Figure 1. Organization chart. Dotted lines indicate organizational independence.

A4.1.2: APCT Center Director
The APCT Center director, Mr. Andrew Trenholm, has overall responsibility for APCT Center
activities, which includes oversight of all verification test planning, execution, and reporting.
The director maintains communication with EPA to assure mutual understanding and
conformance with EPA quality procedures and expectations and ETV policies and procedures,
develops T/QAPs in cooperation with technology developer/vendors, ensures that all
subcontractors [i.e., testing organizations (TOs)] and analytical labs conform to the requirements
of this GVP and resulting T/QAPs, and reviews and approves internal QA reviews and
assessment reports and initiates corrective actions. The director also develops agreements for
verification tests with technology developers/vendors and other collaborators, including cost-
sharing agreements, monitors and directs each test's task leader, directs subcontractor efforts,
and coordinates with  the EPA PO.  The director oversees preparation and internal review  and
approvals of GVP revisions, T/QAPs, and verification reports and statements.  The director
submits these documents to the EPA PO for review and approval.

A4.1.3: RTI Task Leader
The RTI task leader, Deborah Franke has responsibility for the task, including defining task
objectives and developing a detailed work plan schedule.  She will work with vendors and
stakeholders, review work progress to ensure that task budgets  and schedules are met, and
prepare verification reports and verification statements.

-------
Research Triangle Institute                                                             Page 3
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Ms. Karin Foarde, the bioaerosol technical lead, will have responsibility for the technical
oversight required for the bioaerosol testing. She will be assisted by Tricia Webber,
Microbiology Laboratories Supervisor.  James Hanley and MKathleen Owen will be
co-technical leads for the inert aerosol tests.  These technical leaders will review the results for
consistency based on their experience with the respective components of the tests.

The technical leaders will assist the RTI task leader with the work plan schedule, review/prepare
operating procedures applicable to the testing and review test apparatus and procedures prior to
commencement of testing. They will oversee testing of the ventilation devices, review test data
/results for attainment of DQOs and reasonableness, and submit test results to RTI task leader. If
needed they will initiate corrective actions.

A4.2: Quality Assurance Responsibilities
QA responsibilities are divided among the EPA personnel and RTI personnel as listed below.

A4.2.1:  EPA Quality Manager
The EPA quality manager (EPA QM), Mr. Paul Groff, communicates ETV quality system
requirements, quality procedures, and quality issues to the EPA PO and APCT Center director
and quality manager. He reviews and approves GVP revisions, T/QAPs, verification reports and
statements, and QA reports prepared by the center, including QA evaluations and audits.  He
performs independent technical systems audits (TSAs) and performance evaluation audits
(PEAs) of verification tests, as  appropriate, to verify conformance to the quality requirements of
the applicable T/QAP.  He provides assistance to APCT Center personnel in resolving QA
issues.

A4.2.2:  APCT Center Quality Manager
•  The APCT Center quality manager (QM), Dr. W. Gary Eaton, assists the director in revisions
   of this GVP and preparation of subsequent T/QAPs.  The QM is free from personal and
   external barriers to independence, is organizationally independent from data collection
   activities, and is able to maintain an independent attitude and appearance. The QM is
   responsible for ensuring that QA/quality control (QC) procedures described in this GVP are
   followed. The QM communicates directly with the EPA QM and with TO-QMs on quality-
   related issues, providing technical assistance to TOs regarding EPA quality requirements.
   The QM prepares the QA section of each verification report. The  QM reviews and approves
   T/QAPs, verification reports and statements, verification test results, and associated quality
   records.  The QM communicates directly with TO-QMs on quality-related issues. The QM is
   also responsible for conducting independent assessments of the quality systems of TOs and
   independent technical assessments (i.e., technical systems audits [TSAs] and performance
   evaluation audits [PEAs]) of verification tests in cooperation with the EPA QM.  The QM
   performs and documents audits of data quality (ADQs) on 10% of test data. The QM is
   responsible for determining and documenting the effectiveness of corrective actions
   implemented in response to independent assessment findings.

-------
Research Triangle Institute                                                             Page 4
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

A5:  Problem Definition/Background Information
This ETV T/QAP for Biological and Aerosol Testing of General Ventilation Air Cleaners
describes the test and QA procedures that will be used to provide data on the removal efficiency
of bioaerosols and inert aerosols by general ventilation air cleaners.

While data and methods are available for measuring single-pass inert particle removal
efficiencies of air cleaners and filters, no standard method exists for evaluating culturable
bioaerosol reduction by these devices. RTI has developed a test method for measuring culturable
bioaerosol filtration efficiencies of devices ranging from  a room air cleaner to duct-mounted
ventilation filters to vacuum cleaner filters7'8'9. Additionally, the method was used in a previous
ETV project for Biological Testing of General Ventilation Filters (EPA Contract No.
GS10F0283K-BPA-1; Task Order 1101. Research Triangle Institute Project 08787.001)4.

The methods discussed in the previous paragraph are the basis for the bioaerosol test and the sub-
0.3 |im inert particle tests in this T/QAP.  Inert particle efficiency tests are used also as a point of
comparison for QA/QC of the culturable bioaerosol results and will be used as a "self-
consistency" check within the QA framework for the bioaerosol tests.

Under this T/QAP, the following tests may be performed:
1.  A complete ASHRAE 52.2-1999 test.
2.  Bioaerosol test with four culturable microorganisms.
3.  Inert particle tests, using potassium chloride (KC1) aerosol:
   a.  0.3 - 10 jim, with optical particle counter (OPC) measurement,
   b.  0.03 -  0.3 |im, with scanning mobility particle counter (SMPS) measurement, and
   c.  0.03-  10 |im, with combined SMPS and OPC measurements.

The above tests will be performed on clean, conditioned and dust-loaded devices as defined in
this paragraph. For options 2 and 3, conditioning with the sub-micron aerosol and dust loading
with ASHRAE dust will be required for all devices that incorporate filter media. Filter media is
the fibrous material  used in air filters  and other air cleaners to remove particles via filtration.
Examples include microglass and polypropylene fibers. Filter media is typically assembled in
the form of a flat panel, pleated or bag configuration. The bioaerosol test includes inert testing,
as applicable, for QA/QC and reporting purposes.

All of these tests will be performed in a fully qualified ASHRAE 52.2-1999 test duct. This test
duct operates at positive pressure to minimize infiltration of room air or bioaerosol. The KC1
aerosol used for the ASHRAE 52.2-1999 and other inert  aerosol tests and the bioaerosols are
injected upstream of a mixing baffle to provide aerosol mixing with the airstream. Bioaerosol
and inert aerosol concentrations are measured both upstream and downstream of the test section
where the air cleaner is installed to obtain the challenge and penetrating concentrations,
respectively.

Both conditioning and dust loading are done so that the testing better represents what happens
when filters are used in real life. Most media filters increase in efficiency as they are used and
dust collects on the  media. Electret filters have an electrostatic charge applied during
manufacturing. These filters may decrease in efficiency at the start of their use cycle and,

-------
Research Triangle Institute                                                            Page 5
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

possibly, throughout the use cycle if the filters are replaced before significant loading (dust
accumulation) occurs. For ASHRAE 52.2-1999, the conditioning step (also called the first
dustload) challenges the filter with ASHRAE dust (a mixture of carbon black, cotton linters, and
Arizona road dust) until either a pressure drop increase of 10 Pa is achieved or 30 g of dust is
fed, whichever one comes first. Relative to the 25%, 50%, 75% and 100% dust load steps used in
the ASHRAE 52.2-1999 test, this is a very low dust challenge intended to simulate dust loading
during the early states of the filter's use.  The dust  loading with ASHRAE dust is used to
simulate the changes that  can occur as a media filter accumulates dust; this usually results in an
increase in efficiency, but can lead to an efficiency  decrease if the filter sheds the dust instead of
retaining it.

The recommended submicron conditioning step was recently developed as a way to more closely
mimic the actual drop-off in efficiency as seen for electret media. Where the ASHRAE 52.2-
1999 conditioning step  may show a decrease in efficiency for these filters, it is usually much less
than that shown in situ and is unlikely to show a drop-off for the larger particle sizes even though
many media filters do drop-off in efficiency across  the entire particle size range. Thus this step
is needed to simulate real  use efficiencies.

An addendum may be added to this test plan when testing UV, PCO or other devices to cover
device-specific handling or additional measurements.

A6:  Task Description and Schedule
The task consists of the steps summarized below:
1.  Procuring the general  ventilation devices for testing from participating manufacturers,
2.  Subjecting each  air  cleaner to the tests  chosen by the manufacturer as listed in A5,
3.  Preparing verification reports and statements.

A6.1: Task Description
A6.1.1:  Identification and Acquisition of Devices
Devices will be selected by the manufacturers and shipped to RTI. The full name and description
of the product will also be provided. If a media device, a separate filter (or device) will be
provided for each ASHRAE 52.2-1999 test; the bioaerosol tests and inert test may be performed
on the same filter if desired. For devices with filters, each manufacturer should provide a backup
filter to be used if, for example, the other filters are damaged in transit.  Kathleen Owen will be
the custodian of the  devices and will be responsible for storage, labeling, etc. of the devices. For
non-media devices, which tests are appropriate and how many units are needed will need to be
determined on an individual basis in consultation between the manufacturer and the testing
personnel.

A6.1.2:  Performance of ASHRAE 52.2-1999 Test
The ASHRAE 52.2-1999  test will be performed per the standard and will establish the minimum
efficiency reporting value (MERV) and other parameters as required in the standard. ASHRAE
designed the MERV to  represent a filter's minimum performance over multiple particle sizes. In
general, a higher MERV indicates higher filter efficiency. Most commercial filters and high end
residential filters are now  marketed using the  MERV. The filtration efficiencies (average of the
minimum composite efficiency) are presented by particle size groupings: El, 0.3 to 1.0 //m; E2,

-------
Research Triangle Institute                                                            Page 6
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

1.0 to 3.0 //m; and E3, 3.0 //m to 10 //m. If other tests are performed on the same model of
device, performing the ASHRAE 52.2-1999 test in RTFs laboratory will yield a consistent set of
MERV, inert efficiency and bioaerosol efficiency measurements for a device type.

A6.1.3: Performance of Culturable Bioaerosol Testing
Biological testing will be performed using four different bioaerosols and one inert aerosol . If
ASHRAE 52.2-1999 testing is also performed, a second device will be used for the bioaerosol
testing if the device contains media. First, the initial efficiency will be determined using both the
biological and the inert aerosols. The inert testing will cover the typical ASFFRAE 52.2-1999
particle size range of 0.3-10 jam. If the device contains media, the initial efficiencies will be
followed by
•  Submicrometer conditioning (if applicable,  see A5) and the biological efficiency will be
   determined after conditioning,
•  The device will then be loaded with ASFFRAE test dust (if applicable, see A5) to obtain the
   final pressure drop as appropriate based on the MERV estimated by the inert particles or as
   chosen by the manufacturer. The bioaerosol efficiencies after dust-loading will be
   determined.  Table 12-1 of the ASHRAE 52.2-1999 standard provides information on the
   minimum final resistance to be used for each MERV value.
The specifics of the testing will be discussed in further detail in Section B1.2.

The use of microorganisms as the challenge aerosol requires that a number of technical issues be
addressed either in this document or in device-specific addenda. These issues include:
•  Maintaining the survivability and culturability of the organisms through the aerosol
   generation and collection process,
•  Determining whether the test organisms are being aerosolized  as singlets (or single
   organisms) with a narrow size distribution,
•  Generating the bioaerosol challenge in sufficient concentration to maintain the sampling
   duration within the sample time limits of the bioaerosol sampler,
•  Establishing  the generation protocol for the test organisms.
While all of these issues have been addressed in earlier RTI work, they will be readdressed as
needed based on the specific organisms used and the technologies being tested. An addendum
will be added to the test/QA plan for specific technologies to identify any variances from this
plan.

A6.1.4 Performance of Inert Particle Testing
Inert testing will be  performed using KC1 aerosol on the device when (1) clean and, if applicable
(see A5), (2) conditioned and (3) fully dust-loaded. The device is fully dust-loaded when the
minimum final resistance is reached as specified in Table 12-1 of the standard.  If ASHRAE
52.2-1999 testing is performed, a different device will be used for this testing if the device
contains media.  If the bioaerosol testing is performed, this testing may be interspersed with that
testing.  First, the initial  efficiency will be determined using KC1 generated by the ASHRAE 52.2
method and by a Collison nebulizer. The standard generation method will be used with testing
with the OPC covering 0.3-10 jim; the nebulizer will be used with the SMPS to cover the particle
size range of 0.03-0.3 i^m. If applicable (see A5), the initial efficiencies will be followed by:

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
                                                                   Page?
 •  Submicrometer conditioning with  the inert efficiency to be determined after conditioning
    and between conditioning steps,
 •  The device will be loaded with ASHRAE test dust to obtain the final pressure drop as
    appropriate based on the MERV estimated by the inert particles (Table 12-1 of the standard)
    or as chosen by the manufacturer;  the inert efficiencies after dust-loading will be
    determined.
 The specifics of the testing will be discussed in further detail in Section Bl.l.

A6.1.5: Preparation of Report
The final step is to complete the verification report and verification statement for each product
and test performed and submit them to the EPA.

A6.2:  Schedule
If multiple products of a given type are submitted for verification, the products could be run as a
batch and the report for each product issued at the same time. It is expected that in general
products will be tested individually and the report issued when approved by EPA.

A7: Data Quality Objectives and Criteria for Measurement Data
Data quality objectives (DQOs) are qualitative and quantitative statements designed to ensure
that the type, quality, and quantity  of data used are appropriate for the intended application. The
DQOs for the critical measurements are found in Tables 1 and 2.  The test specifications are
found in Appendix A.

Table 1. DQOs for Inert Aerosol Tests
      Parameter
Frequency and
description
                       DQO
 OPC (optical particle
 counter): Penetration
 error limit for OPC
 data
Each test. Statistical check of
data quality. Expected to be
achieved on tests of clean air
cleaners. May not always be
achieved with dust-loaded air
cleaners if the air cleaner sheds a
significant amount of the
collected dust.
Per definitions and procedures of ASHRAE 52.2
Section 10.6.46

&—;= ^ 0.07P or 0.05 whichever is greater for 0.3 — 3 fjm
                                                      ^ 0.15P or 0.05 -whichever is greater for 3 - 5.5 /um
                                                a— -~ < 0.20P or 0.05 whichever is greater for 5.5 — 10 /jm
                                                T = T-distribution variable, n = number of samples,
                                                P = penetration (fraction), o = standard deviation

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

Table 2. DQOs for Filtration Efficiency for Culturable Bioaerosol
PageS
Parameter
Minimum upstream counts for
samplers
Maximum counts for samplers
100% Penetration
(correlation test)
Upstream CPUs
Upstream PFUs
Frequency and description
Each efficiency test.
Each efficiency test.
Performed at least once per
test sequence per organism.
Each test. Statistical check of
data quality.
Each test. Statistical check of
data quality.
Control Limits
Minimum of 10 CFUVplate or
PFUb/plate
Maximum of 500 CFU/plate or 800
PFUb/plate
Test Acceptable
Organism Penetration Range
B. atrophaeus 0.85 to 1.15
S. marcescens 0.80 to 1.20
MS2 0.75 to 1.25
cv1: < 0.25
CVC<0.35
a CFU  =  colony forming units
b PFU  =  plaque forming unit
0 CV   =  coefficient of variance

All data will be reviewed for accuracy (correctness) and reasonableness. If the results are
deemed unreasonable by the technical leaders (e.g., internally inconsistent), they will be
discarded, the procedures reviewed, and the test repeated if necessary. Occasional data points
within a test are obvious outliers and will be discarded based on the statistical tests described in
and/or referenced by ASTM Standard Practice E 178-02, Standard Practice for Dealing with
Outlying Observations10 without requiring the entire test to be repeated.  While exact agreement
is not expected (due to the different measurements devices) similar results are expected.

A8:  Special Training Requirements/Certification
There are no specialized certification requirements specified for these tests. The RTI technical
leads will be responsible for overseeing all work and ensuring that all personnel are fully trained
in each  operation and procedure for the testing.

The method chosen for analysis of the inert aerosol particle size efficiency of ventilation devices
in the laboratory is restricted to use by, or under the supervision of, personnel experienced in the
use of an OPC and skilled in the interpretation of raw count data.

In addition, for the bioaerosol tests, all of RTFs Microbiology Department staff will have
completed at least one formal microbiology course (college or professional/society sanctioned)
and gone through extensive informal laboratory training in the microbiology techniques needed
for this task.
A9:  Documentation and Records
This section identifies the documents and reports to be generated as part of the verification
program and the information to be included in the verification reports and verification
statements.  A description of the data management system established for this task is presented in
Section BIO.

-------
Research Triangle Institute                                                            Page 9
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Requirements for record keeping and data management for the overall program are found in the
U.S. EPA, Environmental Technology Verification Program Quality Management Plan11. All
SOPs are maintained on file at RTI. Access to these files is permitted on-site at RTI.

A9.1: Laboratory Documentation
A9.1.1:  ASHRAE 52.2-1999 and Inert Aerosol Tests
The test operator for the inert aerosol test will record the test data and run notes on test run sheets
prepared specifically for these tests (An example is presented in Appendix B.) The sheets will be
kept in a labeled three-ring binder.  The run sheets are designed to prompt the test operator for all
required test information:
•   Testing date, time, and operator;
•   Manufacturer and model number of device;
•   Physical description of the device;
•   QA checks on the equipment and data; and
•   Test conditions (temperature, relative humidity, atmospheric pressure, air flow rate, device
    pressure drop).

The particle count data generated by the OPC are recorded by the computer.  The file will be
saved to the hard drive and later copied to a floppy disk or shared directory for backup.

A9.1.2:  Bioaerosol Tests
The bioaerosol test operator will record the test data and notes on a bioaerosol test run sheet
(presented in Appendix C).  The sheets are kept in a labeled three-ring binder. The run sheets are
patterned from the inert aerosol run sheets and designed to prompt the test operator for all
required test information:
•   Device and run number;
•   Testing date and operator;
•   Test conditions (t, RH, ambient pressure, air flow rate, pressure drop across ASME nozzle;
•   Biological suspension information (test organism, suspension preparation, drying air,
    nebulizer pressure, initial volume, and time on);
•   Biological sampling scheme (time run begins, sample length, and media); and
•   Rotameter readings showing the flow rate through the bioaerosol sampler.

The organism counts are entered in the project notebook or recorded by a computer.  If recorded
to a computer, the file will be saved to the hard drive and later copied to a floppy disk or  shared
directory for backup.

A9.2: QA Reports
The RTI QM will perform a system audit based on the approved T/QAP during the first month of
testing; this is considered suitable since this testing program is using well-known measurement
systems components. A report will be prepared for the task leader within 15 days of completion
of the audit.

RTI will cooperate with audits performed by the EPA project officer, EPA QM, or their
designee.

-------
Research Triangle Institute                                                            Page 10
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
A9.3: Reporting
After the completion of verification tests, the control test data, sample inventory logs, calibration
records, and certificates of calibration will be stored. Calibration records will include such
information as the instrument being calibrated, raw calibration data, calibration equations,
analyzer identifications, calibration dates, calibration standards used and their traceabilities,
identification of calibration equipment used, and the staff conducting the calibration. Final
reports of self-assessments and independent assessments (i.e., technical systems audits,
performance evaluations, and audits of data quality — TSAs, PEs, and ADQs — will be
retained. Each verification report and verification statement will contain a QA section, which
will describe the extent that verification test data comply with DQOs.

A9.4: Verification Reports and Verification Statements
Verification reports and verification statements will be prepared by the task leader and reviewed
by the APCT Center director and the APCT Center quality manager prior to submittal to the EPA
project officer for approval. Procedures for the preparation, review, and dissemination of
verification reports and verification statements are described in the U.S. EPA, Environmental
Technology Verification Program Quality Management Plan11.

It is anticipated that the verification reports and statements will include the filtration efficiency of
the tested device for the challenges used for the clean and dust-loaded device.

The following information will be included in the verification reports and verification
statements, depending on which test(s) were performed:
•  The fractional filtration efficiency of the air device over the 0.03 - 10 i^m size range for the
   device when (1) clean, and if applicable (see A5) (2) conditioned and (3) fully dust-loaded;
•  The efficiency for the four bioaerosols;
•  The pressure drop across the  clean and (if applicable, see A5), fully dust-loaded device;
•  The test air flow rate;
•  The measured MERV and the associated El, E2, and E3 values of the ASHRAE 52.2-1999
   test;
•  A complete ASHRAE 52.2 report, and
•  A description and photograph of the device tested.

-------
Research Triangle Institute                                                           Page 11
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

SECTION B: MEASUREMENT/DATA ACQUISITION

Bl:  Test Design
Under this T/QAP, the following tests may be performed:
1.  A complete ASHRAE 52.2-1999 test,
2.  Bioaerosol test with four culturable microorganisms,
3.  Inert particle tests, using KC1 aerosol:
   a.  0.3 - 10 jam, with OPC measurement,
   b.  0.03 - 0.3 |im, with SMPS measurement, and
   c.  0.03- 10 jam, with combined  SMPS and OPC measurements.

The above tests will be performed on clean, conditioned and dust-loaded devices as applicable.
Conditioning with the sub-micron aerosol and dust loading will be required for all devices that
incorporate filter media. All tests will be performed on devices at an air flow rate acceptable
under ASHRAE 52.2-1999.

Bl.l: ASHRAE 52.2-1999 and Inert Testing
The ASHRAE 52.2-1999 test will be run in accordance with the ASHRAE 52.2-1999 test
method. A second device will use modified ASHRAE 52.2-1999 procedures to extend the
measurements to smaller particle sizes and to condition electret media.  All the inert aerosol tests
will use laboratory-generated KC1 particles  dispersed into the airstream as the test aerosol. A
particle counter will measure and count the  particles in a series of size ranges both upstream and
downstream of the test devices for its efficiency determinations. To simulate the effects of dust
accumulation on the devices, the devices will be tested when clean and, if applicable (see A5),
when conditioned and when fully dust-loaded.  The dust-loading will follow ASHRAE 52.2-
1999 procedures as applicable.

Bl.1.1: Particle Counters
For the inert aerosol filtration efficiency measurements, the particle sizing measurements will be
made with two particle counting instruments: a Climet Model 500 spectrometer (OPC) covering
the particle diameter size range from 0.3 - 10 //m in 12 particle sizing channels and a TSI SMPS
to  cover the range from 0.03 - 0.3 //m. For the conditioning aerosol, a TSI condensation particle
counter (CPC) (model 3022A or similar) will be used to monitor the upstream  concentration.
The CPC will function to monitor the concentration of the submicrometer-sized particles used
for conditioning; it will not aid in measuring the efficiency of the devices.

The OPC uses a laser-light illumination  source and has a wide collection angle for the scattered
light. The OPC's sampling rate is 7.1 L/min. (0.25 cfm).  The OPC is equipped to provide a
contact closure at the end of each sample and also provides a 15 sec. delay in particle counting
after each sample. The contact closure is used to control the operation of electromechanical
valve actuators in the upstream and downstream sample lines.  The 15 sec. delay allows time for
the new sample to be acquired. The SMPS consists of a TSI Model  3080 electrostatic classifier
and a TSI Model 3010 or 3022 CPC.

Depending upon the quality of the data from any individual test, the SMPS can sometimes
reliably quantify particles even smaller than 0.03 //m, and when this is the case, those smaller

-------
Research Triangle Institute                                                           Page 12
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

sizes are reported. The ability to quantify sizes smaller than 0.03 //m is determined as defined in
Table A2. A data control parameter for the SMPS requires that the coefficient of variance (CV)
on upstream counts be computed for each efficiency test based on the upstream particle counts
and that the CV be less than 0.30 before the data is used. The lower size ranges for the SMPS are
included in the verification report only if they meet the data control parameter. Particle sizes
above 0.3  jim will be measured and reported when there are particle counts that meet the data
specifications; however, the aerosol generation system necessary to meet our data standards
often does not achieve sufficient particle counts for the larger particles.

Bl.1.2: Inert Aerosol Generation
Three aerosol generators will be used for the tests as applicable. These generators are needed to
cover the range of particle sizes needed; one for the 0.03 - 0.3 //m tests, one for the 0.3 - 10 //m
tests, and one to generate the submicrometer conditioning aerosol. All of the aerosols will be
generated from KC1 in aqueous solution. The concentrations of KC1 will vary as will the
generation technique to give particles in the needed size ranges.

For the 0.3-10 //m efficiency tests, the KC1 solution will be nebulized using a two-fluid (air and
liquid) atomizing nozzle (Spray Systems 1/4 J siphon spray nozzle). The full description of the
test duct is in Appendix A.  The nozzle is positioned at the top of a 0.30 m  (12 in.)-diameter, 1.3
m (51 in.)-tall transparent acrylic spray tower. The tower serves two purposes. It allows the salt
droplets to dry by providing an approximately 40 sec. mean residence  time, and it allows larger
particles to fall out from the aerosol. After generation, the aerosol passes through a TSI Model
3054 aerosol neutralizer (Krypton-85 radioactive source) to neutralize any  electrostatic charge on
the aerosol (electrostatic charging is an unavoidable consequence of most aerosol-generation
methods). The KC1 solution is fed to the atomizing nozzle at 1.2 mL/min.  by a pump.  Varying
the operating air pressure of the generator allows control of the output aerosol concentration.

For the 0.03 - 0.3 //m tests, the KC1 solution will be nebulized with a Collison nebulizer or
Laskin nozzle generator. Both of these devices generate smaller particles than the spray nozzle.

Bl.1.3: Inert Conditioning Procedure for Devices with Media Under Test Options 2 and 3
For the conditioning required for devices with filter media if tested under options 2 or 3, the
conditioning aerosol will be produced using a bank of Laskin generators nebulizing a 0.1% KC1
aqueous solution (1 g KC1 to 1 L of water).  This is a refinement of procedures developed by
RTI on earlier EPA-supported research7 and under ASFIRAE research  project 1190-RP.
Previous measurements have indicated that the resultant aerosol is < 0.1 //m in mean diameter.
Periodically during the conditioning portion of the test, the device's efficiency will be measured
(0.3  - 10 //m) to determine if the efficiency has fallen to its minimum condition. Once the
efficiency is at or near its minimum, the conditioning will cease. The  duration of conditioning
and the concentration  of the conditioning aerosol will be monitored during the test.

B1.2:  Culturable  Bioaerosol Testing
The bioaerosol testing is based on the inert methodology and uses the  same test rig as the inert
aerosol. The methodology is described in ML SOP #038* (SOP for the Determination of the
Filtration Efficiency of Bioaerosols).  Two primary differences from the inert aerosol
methodology are that the bioaerosol is generated from a suspension of the test organism and the

 * All SOPs are maintained on file at RTI indefinitely. Access to these files is permitted onsite at RTI.

-------
Research Triangle Institute                                                            Page 13
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

sampling is achieved using bioaerosol samplers.  The use of microorganisms as the challenge
aerosol requires that a number of technical issues be addressed. These include:
•  Measuring the survivability and culturability of the organisms through the aerosol generation
   and collection process;
•  Determining whether the test organisms are being aerosolized as singlets with a narrow size
   distribution;
•  Generating the bioaerosol challenge in sufficient concentration to maintain the sampling
   duration within the sample time limits of the bioaerosol sampler; and
•  Establishing the generation protocol for the test organisms.
While all of these issues have been addressed in earlier RTI work, they may need to be
readdressed based on the specific organisms used and the technologies being tested.

Bl.2.1:  Test Organisms
The size and shape of the organisms selected for testing are important because the organisms are
aerosolized and their filtration efficiency determined. These organisms naturally vary in both
their sizes and shapes.  Therefore, there is the need to select organisms that reflect that natural
diversity.

The bioaerosol tests will be conducted using four organisms: one fungal spore, one spore-
forming bacterium, one vegetative bacterium, and one virus. The fungal spore (2-3.5 jim
spheres), Aspergillus versicolor,  is frequently reported as a causative  agent of hypersensitivity
pneumonitis and has been isolated from a number of problem buildings. The spore form of the
bacteria Bacillus atrophaeus (formerly B. subtilis var niger) is elliptically  shaped with
dimensions of 0.7 - 0.8 x 1 - 1.5 jim.  The organism is a ubiquitous environmental bacterium
found at high levels in soil and highly associated with indoor dust. Staphylococcus epidermidis
is a common gram-positive 0.5 - 1.5 |im spheres organism and will be the  representative
vegetative bacterium.

Human viruses are thought to be spread by airborne or droplet transmission. Because human
viruses can be expensive and cumbersome to work with, the bacterial virus (bactedophage) MS2
(0.02 - 0.03 //m), having approximately the same aerosol characteristics as a human virus, will
serve as a surrogate for the viruses of similar and larger size and shape.

Although the individual virus particles are in the submicrometer size range, the test particle size
planned for the virus tests will span a range of sizes (polydispersed bioaerosol). This test is not
designed to study the removal  efficiencies for single individual virus particles; rather, it is
designed to determine the removal efficiencies for virus particles as they are commonly found
indoors.  A representative challenge would be a polydispersed aerosol containing the phage
because:
•  The aerosols created from sneezing and coughing vary in size from < 1 to 20 //m12, but the
   largest particles  settle out and  only the smaller sizes remain in the  air for extended periods for
   potential removal by an air cleaner;
•  For some viruses (i.e., Coxsackie virus), few viruses have been found associated with the
   smallest particles13; and
•  Nearly all 1 - 2 //m particles are deposited in the respiratory tract, while larger particles may
   not be respired.

-------
Research Triangle Institute                                                            Page 14
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Bl.2.2: Bioaerosol Preparation and Generation
Bacteria suspension preparation for the aerosolization process requires that the specific test
organism be grown in the laboratory and the suspension prepared for aerosol generation in the
test rig following ML SOP #012 (SOP for the Quantitation of Viable Microorganisms in
Suspension). The microbial challenge suspensions are prepared by inoculating the test organism
on solid or liquid media, incubating the culture until mature, wiping organisms from the surface
of the pure culture (if solid media), and eluting them into sterile nebulizing fluid to a known
concentration, corresponding to a concentration of approximately 1 x 107 CPUs (colony forming
units)/mL. Trypticase soy agar will be used for the the bacteria. Sabourauds Dextrose Agar will
be used for the fungus.

The phage challenge will be prepared by inoculating a logarithmic phase broth culture of the host
bacteria with phage  and allowing it to multiply overnight or until the majority of the host bacteria
are  lysed. The mixture is processed to collect and concentrate the phage. Then, the phage stock is
filter sterilized (0.2//m) to remove the bacteria. The phage stock will be used as the challenge
aerosol. The concentration of the phage stock will be approximately 1 x 1012 or higher plaque
forming units (PFU)/mL.

The challenge organism suspensions will be aerosolized using a Collison nebulizer (BGI,
Waltham, MA) at 15 psi air pressure. The Collison nebulizer generates droplets with an
approximate volume mean diameter of 2 //m. The particle diameter after the water evaporates
depends on the solids content of the suspension.  Particle size is determined by the size of the
suspended particles  (if singlets).

Upstream and downstream sampling of the bacteria and fungus will be accomplished using a
one-stage Andersen viable bioaerosol sampler.  The one-stage Andersen sampler is a 400-hole
multiple-jet  impactor operating at 28 L/min. The dso (50% cut point on Andersen sampler) is
0.65 //m. After sampling, the petri dishes will be removed from the sampler and incubated at
appropriate times and temperatures for the test organism being used. CPUs are  then enumerated
and their identity confirmed.

The phage will be collected in all glass impingers (AGIs).  The AGI is a high velocity liquid
impinger operating at a flow rate of 12.3 - 12.6 L/min. The dso is approximately 0.3 //m.  The
AGI is the sampler against which the other commonly used bioaerosol samplers are often
compared. The AGI (containing collection fluid) will be used for the MS2 sampling.

The experimental conditions and sampling times will be adjusted so that these samplers will be
used within their upper and lower sampling limits.

To quantify  the microbial counts, the plates are incubated at the appropriate temperature and
time for the  test organism (overnight to a week). Colonies or plaques are counted. A "positive-
hole" correction  is applied14 to the one-stage Andersen data to correct for undercounting at high
concentrations.

-------
Research Triangle Institute                                                          Page 15
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

B2: Sampling Methods Requirements
Inert aerosol sampling method requirements and critical dimensions and configurations of the
test apparatus are specified in ASHRAE 52.2-1999. Bioaerosol sampling methodology will
comply where appropriate. Bioaerosol samplers are operated according to the manufacturer's
specifications.  The vacuum pumps required for operating the samplers are calibrated following
ML SOP #029 (SOP for Calibrating Pump Flows Using a Dry Gas Meter).

B3: Sample Handling and Custody Requirements
Sampling methods and laboratory procedures are described in specific laboratory SOPs. These
SOPS address any anticipated failures and the methods that will be employed to overcome these
failures. Most of the methods are well-known sampling methods; therefore, sampling failures
are not anticipated. Any additional project-specific considerations will be addressed by the RTI
technical leads and included in an updated SOP. Supporting measurements, such as temperature,
relative humidity or atmospheric pressure, will be recorded in laboratory data logs, run sheets or
notebooks.

Upon receipt of the test devices, each will be serially numbered using a permanent marker (or
other means as appropriate). All devices for this study will be stored in a single indoor, air
conditioned common area (Bay 1).

B4: Analytical Methods Requirements
The analytical method requirements for the inert aerosol testing are described in ASHRAE 52.2-
1999. The requirements for biological testing are described in the appropriate ML SOPs.

B5: Quality Control Requirements
The apparatus will be tested to verify that the test rig and sampling procedures are capable of
providing quantitatively reliable particle size measurements. Appendix A contains quality
control information for inert aerosols (Table Al), the scanning mobility particle sizer (Table A2)
and bioaerosols  (Table A3).

B6: Instrument/Equipment Testing, Inspection, and Maintenance Requirements
Qualification tests will be conducted as required by the table shown in Appendix A.  Typically,
these tests are run as part of each test run, monthly, biannually, or after a change that may alter
performance.

B7: Instrument Calibration and Frequency
Calibration will  be performed in accordance with the manufacturer's recommendations or
annually. Recommended instrument calibration frequencies are provided in the respective SOPs
and manufacturer's manuals.  Pipettes will be calibrated gravimetrically following ML SOP
#013 (SOP  for Pipet Calibration).

B8: Inspection/Acceptance Requirements for Supplies and Consumables
Chemicals,  supplies, and other consumables will be purchased from sources that have provided
high quality products to the laboratory in the past.  Materials such as growth media will be
purchased from  a single source to help ensure uniformity throughout the duration of the project.

-------
Research Triangle Institute                                                           Page 16
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

All supplies will be inspected by the lab personnel. RTFs purchasing department will assist with
the return of any equipment or materials that do not meet project requirements.

B9:  Data Acquisition Requirements (Non-direct measurements)
Non-measurement sources such as computer databases, programs, literature files, or historical
databases  will not be used for data acquisition.

Manual methods of primary data acquisition (e.g., visual CPU counting) are described in ML's
SOPs, while automated data acquisition equipment (e.g., balances and environmental  controls) is
checked using procedures recommended by the manufacturer. Procedures for screening and
verifying manually entered data are used to reduce input errors to a minimum through double
checking each other.  Non-experimental data, such as an MSDS, will be included in the project
notebook and a copy maintained in the RTI Technical Leader's project file.

BIO: Data Management
The work performed using this T/QAP will conform to the quality management plan for the
APCT Center15.

Guidelines for data management in the ML include the description, location, format, and
organization of all types of records. The technical leaders will oversee all data management
activities.  This section identifies the activities and processes planned for documenting the
traceability of the data, calibrations, and information in the verification report.

B10.1:  Data Recording
Data for this task will be collected either by computer or by manual (handwritten) entries.
Observations and records (e.g., sample description and collection information) will  be recorded
manually in lab notebooks kept exclusively for this task. Output data generated by  the OPC
instruments will be transferred directly to a computer file and stored as a spreadsheet; printed
output will be taped into the lab notebook.

B10.2:  Data Analysis
B10.2.1: Inert Aerosol Data
The computation of inert aerosol filtration efficiency is based on the ratio of the downstream-to-
upstream particle concentrations corrected on a channel-by-channel basis for:
•   Background counts (i.e., upstream and downstream counts observed when the aerosol
    generator is off) and
•   For the correlation ratio measured at the start of the test sequence.
A minimum of two background and six upstream and six downstream counts will be taken.
These data will  be used for determining filtration efficiency by computing the observed
penetration (Pobserved) (Eq. 1):
                                          (D-D,)
                                                t> '
                                       _  _
                                observed     (TT  TT \
                                          \U ~U b)


where:
       D  =  Downstream particle count,
                                                                                    -:
                                                                                    *

-------
   Research Triangle Institute                                                           Page 17
   ETV Test/Quality Assurance Plan
   Biological and Aerosol Testing of General Ventilation Air Cleaners

          Db =  Downstream background count,
          U  =  Upstream count, and
          Ub =  Upstream background count.

   To remove system bias, the observed penetration is corrected by the correlation ratio (R) (the
   Pobserved measured during a blank control test for which no device is installed in the duct) (Eq. 2).

                                 corrected ~  observed                               Eq. 2

The inactivation efficiency is then computed (Eq.  3).

                      Inactivation Efficiency (%) = 1 00 (1 - Pcorrected )                    Eq . 3


   B10.2.2:  Bioaerosol Data
   Data analysis will be performed using commercially available software (Microsoft Excel16) to
   enter the raw data into a spreadsheet and calculate results from a series of equations.

   Samples will be collected simultaneously using multiple samplers. A minimum  of six, usually
   twelve, replicates will be collected for each efficiency determination.

   The mean upstream and downstream  CPUs will be calculated as (Eq. 4):
                     n                                        n
                                                        _
                    *'=!                  and             j) = *'=!                     Eq. 4
                     n                                        n
   where:
          D;  =  Downstream count of the ith sample and n is the number of replicate samples
                 collected and
          U;  =  Upstream count of the ith sample and n is the number of replicate samples
                 collected.

   The calculation of the penetration is based on the ratio of the downstream to upstream culturable
   counts.  The penetration with the device installed in the test rig (Pmeasured) is shown in the
   following equation (Eq. 5):
                                P        =   -
                                 measured   /U                                       Eq. 5
   where:
                 D  =  Mean downstream count with a device installed in the test rig and
                 U  =  Mean upstream count with a device installed in the test rig.

-------
Research Triangle Institute                                                            Page 18
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

The PIOO (no device installed in the test rig) is calculated as the Pmeasured but using the results of
the no device tests (Eq. 6).
                                        ^100
where:
Dwo   =  Mean downstream count with no device in the test rig and

Uloo   =  Mean upstream count with no device in the test rig.

To remove system bias, the Pmeasured is corrected by the penetration of a blank "no device" test for
which no air cleaner is installed in the duct (Pioo) (Eq. 7).
                                         P         /
                              p        =  measured/
                               corrected          /P                                Eq. 7
                                                /   100


The inactivation efficiency is then calculated as shown in Eq. 8.

                Inactivation Efficiency (%) = 100 (1 - Pcomcted )                         Eq  8

The precision DQO for bioaerosol inactivation efficiency will be calculated based as ฑ one
standard deviation of penetration computed from the coefficient  of variance of upstream and
downstream culturable counts as shown in Eq.  9.
               Std. Deviation = Pmeasured (^CFj + CFD2)                              Eq. 9

where:
       Pmeasured = Penetration calculated from the upstream and downstream culturable counts,
       CVu    = Coefficient of variance for the upstream counts, and
       CVo    = Coefficient of variance for the downstream counts.

B10.3: Data Storage and Retrieval
Laboratory notebooks containing manually recorded information and data output generated from
instrumentation will be stored in the custody of the appropriate technical lead for the duration of
the project.

Spreadsheet files including raw and calculated data will be stored on computers.  The files will
be downloaded to a network server backed up nightly on magnetic tape.

Following policy at RTI, as well as ETV policy, project files will be archived offsite at a secure
facility for a minimum of 7 years following the end of the project.

-------
Research Triangle Institute                                                           Page 19
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

 SECTION C:  ASSESSMENT/OVERSIGHT

Cl:  Assessments and Response Actions
Cl.l: Audits
RTI will be subject to both external and internal audits as specified in the APCT Center Quality
Management Plan (QMP)17 (Table 3) and the ETV QMP11 (Table 9-1), ETV Assessments. A
subset of those tables is shown below, Table 3. Audits based on this test/QA plan include
Technical  System Audits (TSAs) and Performance Evaluation Audits (PEAs). The raw and
summary data is subject to Audits of Data Quality (ADQs). An external audit may be conducted
by EPA or a designated representative. The auditor(s) will document their findings and note
where corrective actions are necessary. The auditor(s) will distribute audit reports to those listed
in Section A3 as well as to the supervisor whose laboratory was audited.

                            Table 3. RTI's ETV Assessments
Assessment Tool
Technical
Systems Audits
Performance
Evaluation Audits
Audits of Data
Quality
Assessors
Self
RTI QAM
Independent
EPA QAM
Self
RTI QAM
Independent
EPA QAM
Self
RTI QAM
Independent
EPA QAM
Subject of
Assessment
Test/QA plan
Test/QA plan
Raw data and
summary data
Minimum
Frequency
Self
Once per test or
batch of tests
Independent
Once per year
Sen"
Each test or batch of
tests
Independent
Each test or batch of
tests
Self
At least 10% of the
data in each test
Independent
Each test
Reason for
Assessment
Assess
technical
quality of
evaluations
Assess
measurement
performance
Assess data
calculations
and reporting
Report Reviewed by
EPA Project Officer
APCT Center Director
Task Leader
EPA Project Officer
APCT Center Director
Task Leader
EPA Project Officer
APCT Center Director
Task Leader
C1.2: Corrective Actions
Technical personnel will have the direct responsibility for ensuring that the T/QAP plan is
implemented, that the operating parameters are within acceptable limits as specified in Appendix
A, and that corrective actions are taken when appropriate. Corrective action will be taken
whenever measurement accuracy or bias is outside the limits of objectives for the critical
measurements.  If procedures are found to be faulty, corrective action will also be taken.
Corrective actions include:
•  Problem identification;
•  Attempting to find the cause;
•  Attempting immediate repairs (if possible);
•  Reporting or documenting the problem;
•  Planning for corrective action (if major repairs are needed);

-------
Research Triangle Institute                                                            Page 20
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

•  Checking that problem was corrected;
•  Documenting the corrective actions taken; and
•  Recommending changes to instruments, SOPs, etc. to avoid similar future occurrences.

The RTI QM, task leader, and the technical leaders will be jointly responsible for proper
documentation of corrective actions. Minor corrective actions are to be recorded in the
laboratory notebooks. Major problems will be addressed as outlined above. All corrective
actions will be noted in the test report.  Depending on the time and expense involved with
necessary corrective actions, it will be necessary to consult the EPA project officer or the
sponsor before implementing any changes in the planned activities.

C2:  Reports to Management
The task leader will notify the APCT Center director and EPA project officer when testing under
this project is being conducted. The task leader will submit verification reports and verification
statements, as well as data, to the RTI QM. After technical assessments, the task leader will
submit the assessment report to the APCT Center director. The APCT Center director will
submit verification reports and verification statements to the EPA project officer and will submit
assessment reports to the EPA project officer for informational purposes.

Audit reports will be sent to all those on the distribution list for the T/QAP.

-------
Research Triangle Institute                                                            Page 21
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

SECTION D: DATA VALIDATION AND USABILITY

Dl:  Data Review, Validation, and Verification Requirements
The test is acceptable if all the measured parameters fall within the DQO limits described in
Table 2.  The test operator and analyst are responsible for checking that all measured parameters
fall within prescribed limits before continuing testing.

D2:  Validation and Verification Methods
The test analysis will verify that the test data have been correctly entered and processed by
double checking each other.  Newly-developed or modified software, including spreadsheets,
will be checked for correctness before being used to process project data. All manual
calculations will be double- checked.

Each verification report will be reviewed by the RTI QM for compliance with the applicable
method and for the quality of the data reported.

The RTI QM will check for the following:
•  Data completeness,
•  Initial and continuing calibrations, and
•  QC reference and internal standards.

D3:  Reconciliation with Data Quality  Objectives
Each ETV verification  statement will summarize testing conditions and will state test results.
Each ETV test report will present the critical and relevant ancillary measurements.

Actual data quality will be compared with the DQOs specified in Section A7; if the data quality
meets or exceeds the objectives and test specifications have been met, the test data will be
considered acceptable.  If exceptions are identified, the issues will be investigated for impact on
the credibility of the data, the EPA QM will be consulted, and the test results disposed of on the
basis of this careful consideration; the verification statement will note the except!on(s) and their
potential impact on the utility of results.

-------
Research Triangle Institute                                                           Page 22
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

                                       References

1.  RTI. 1999. Environmental Technology Verification Test Protocol for General Ventilation
   Filters. Research Triangle Park, NC. http://www.epa.gov/etv/pdfs/vp/07_vp_filters.pdf

2.  RTI. 1999. Environmental Technology  Verification Test Plan for General Ventilation Filters.
   Research  Triangle Park, NC.
   http://www.epa. gov/etv/pdfs/testplan/07_tp_093099_general.pdf

3.  RTI. 2004. Environmental Technology  Verification Protocol for Measuring Efficiency for
   Biological or Chemical Challenges of Technologies for Cleaning Building Ventilation Air.
   Research  Triangle Park, NC. Available from RTI.

4.  RTI. 2003. Environmental Technology Verification Test Plan for Biological Testing of
   General Ventilation Filters. Research Triangle Park, NC.
   http://www.epa.gov/etv/pdfs/testplan/10_tp_bio.pdf

5.  RTI. 2005. Technology Testing and Evaluation Program,  Test/QA Plan for Bioaerosol
   Inactivation Efficiency by HVAC In-Duct Ultraviolet Light Air Cleaners.  Research Triangle
   Park, NC. Available from RTI.

6.  ANSI/ASHRAE (American National Standards Institute/American Society of Heating,
   Refrigerating and Air-Conditioning Engineers). 1999. ANSI/ASHRAE Standard 52.2-1999,
   Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by
   Particle Size, Atlanta, GA.

7.  Foarde, K.K. and J.T. Hanley. 2001. Determine the Efficacy of Antimicrobial Treatments of
   Fibrous Air Filters. ASHRAE Transactions. Volume 107, Part 1. 156-170.

8.  Foarde, K.K. and J.T. Hanley. 1999. A New Laboratory Method for Measuring the
   Bioaerosol Filtration Efficiency of Air Cleaners. Proceedings: 1999 Air Filtration
   Conference: Fall Topical Conference pp. 47-54.

9.  Foarde, K.K., J.T. Hanley, D.S. Ensor, and P.F. Roessler.  1999. Development of a Method
   for Measuring Single-Pass Bioaerosol Removal Efficiencies of a Room Air Cleaner. Aerosol
   Science and Technology. 30: 223-234.

10. ASTM. 2003. E178-02 Standard Practice for Dealing With Outlying Observations. American
   Society for Testing and Materials. West Conshohocken, PA.

11. U.S. EPA. 2002.  Environmental Technology Verification Program  Quality Management
   Plan, EPA/600/R-03/021, U.S. EPA, Cincinnati, OH, 2002.
   http://www.epa.gov/etv/pdfs/qmp/ETV 02 QMP.pdf

12. RTI. 1999. Environmental Technology Verification Test  Method, General Ventilation
   Filters, Research Triangle Park, NC. http://etv.rti.org/iap/documents.cfm.

-------
Research Triangle Institute                                                           Page 23
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
13. Knight, V. 1973.  Viral and Mycoplasmal Infections of the Respiratory Tract, Lea & Febiger,
   Philadelphia, PA.

14. Buckland, F.E., and Tyrell, D.A.S. 1962. Loss of Infectivity on Drying Various Viruses,
   Nature 195: 1063-1064.

15. Macher, J.M. 1989. Positive Hole Correction of Multiple-jet Impactors for Collecting Viable
   Microorganisms, American Industrial Hygiene Association Journal. 50: 561-568.

16. Microsoft Corporation. Microsoft Excelฎ 2000. Redmond, WA.

17.RTI (Research Triangle Institute). 2005. Quality Management Plan for Verification Testing
   of Air Pollution Control Technology, Revision 2.2, Research Triangle Park, NC.
   http://etv.rti.org/apct/pdf/apctqmp.pdf
                            ML SOPs Used in this Document

    1.  ML SOP #012, SOP for the Quantitation of Viable Microorganisms in Suspension.
    2.  ML SOP #013, SOP for Pipet Calibration.
    3.  ML SOP #029, SOP for Calibrating Pump Flows Using a Dry Gas Meter.
    4.  ML SOP #038, SOP for the Determination of the Filtration Efficiency of Bioaerosols.

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Page 24
Appendix A:  Test Specifications
Test specifications for the inert aerosol tests are defined in ASHRAE 52.2-1999 and shown in
Table Al. These will be used for both the ASHRAE 52.2-1999 testing and the inert aerosol
component of the bioaerosol test. The test specifications associated with the SMPS and the
conditioning aerosol are found in Table A2.  Table A3 shows the test specifications for the
bioaerosol test. The test duct performance specifications applicable to all testing are found in
Table A4.

Test Duct /System
A schematic of the test duct is shown in Figure Al.  The drawing is approximately to scale.  The
test duct is a 610 mm (24 in.) x 610 mm (24 in.) square. The locations of the major components,
including the sampling probes, test section (device holder), the aerosol generator (site of aerosol
injection) are shown.

There are presently no standards available to directly "calibrate" the test system for penetration.
However, a number of parameters can be checked to verify proper performance.  0%  and 100%
penetration measurements are made by using a HEPA filter and an empty (no device) test
section, respectively, using the optical particle counter (OPC) and KC1 as the inert particulate.
Separate tests with the bioaerosol will be done using the test bioaerosol and the bioaerosol
samplers.

The flow rate will be measured via the pressure drop across an ASME long radius flow nozzle
(i.e., nozzle size 8V2 in.) mounted in the center of the duct downstream of the device.  It will be
the primary standard for the laboratory.  Prior to use, the nozzle is visually inspected to be free
from defects. The  installation of the nozzle in the duct will be inspected to confirm that it is
seated in place.
Exhaust
to Roorr
Room 1
Air " —
1 "—
H_


^
t \
\ 1
Blower \
Flow Contro
Valve
ASME Nozzle
Outlet Filter Bank 9
1 ||


1 | 0(l *• —
nlet Filter / upstream Mixer
Bank Aerosol Bl
Generator Sc
Biological
Sampling Downstream Mixer
P ^
ง <- ^
. )J

,Device Backup Filter
; Section.. . , ,,,.,,,.
1 Holder (Used When
^ Dust-Loading)
^logical
^mpling
Figure Al.  Schematic of test duct (top view) used for filter testing. Drawing is
approximately to scale with the duct being 610x610 mm2 (24 x 24 in.2) and shows the
location of aerosol injection, mixing baffles, test section, ASME flow nozzle, and OPC
sampling probes.

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Page 25
The pressure drop across the device will be measured with an inclined manometer and/or a
digital micromanometer. The zero and level of the manometer will be confirmed and connecting
tubing inspected for integrity.

Measurements of the in-duct temperature and relative humidity (RH) and room atmospheric
pressure will be made. These measurements are not critical to the program and are being
collected simply to document the general test environment. A wet and dry bulb psychrometer
will be used for determination of temperature and relative humidity and an aneroid barometer for
atmospheric pressure (periodically compared to a mercury barometer in an adjoining lab). For
the bioaerosol, the RH goal is 20 - 70%.  No specific quality control checks on these instruments
are planned other than an inspection of the instruments for mechanical faults (e.g., mercury
separation in the thermometers, poor tubing connections), and inspection of the data for
reasonableness.

Table Al. Quality Control Parameters For Inert Aerosol Tests
Parameter
Minimum counts per
OPCa channel for
challenge aerosol
Maximum total OPC
count per sample
100% Efficiency test
(0% Penetration)
100% Penetration
(correlation test)
Penetration error limit
for OPC data
OPC calibration:
primary calibration
Frequency and
description
For each efficiency test, the total
number of particles counted per
OPC sizing channel for the
upstream challenge aerosol is
computed.
Each efficiency test.
Monthly. A HEP A filter is used
for the test device.
A 100% penetration test
performed at least once per week
during testing.
Each test. Statistical check of
data quality. Expected to be
achieved on tests of clean air
cleaners. May not always be
achieved with dust-loaded air
cleaners if the air cleaner sheds a
significant amount of the
collected dust.
Primary calibration performed by
manufacturer at manufacturer-
specified intervals; but at least
annually.
Control Limits
Minimum total of 500 particle counts per channel.
Not to exceed maximum challenge aerosol concentration
determined in the OPC upper concentration limit test
referenced in Table A4.
Measured penetration must be <1%.
Particle Acceptable
Size range Penetration Range:
0.3tol|im: 0.90 to 1.10
Ito3|im: 0.80 to 1.20
3tolO|im: 0.70 to 1.30
Per definitions and procedures of ASEQIAE 52.2 Section
10.6.46
&—;= ^ 0.07 P or 0.05 -whichever is greater for 0.3 - 3 /urn
vซ
&—j= ^ 0.15P or 0.05 whichever is greater for 3 - 5.5 /u
vซ
T
Manufacturer provides certificate of calibration.

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Page 26
Parameter
Minimum counts per
OPCa channel for
challenge aerosol
OPC sizing accuracy
check:
polystyrene latex
spheres (PSL)
OPC reference filter
check
OPC zero count
Background count rate
Pressure drop across
empty test section
Pressure drop across
the air cleaner
Pressure drop across
the ASME flow
nozzle used for
measurement of
airflow
Aerosol charge
neutralizer
Filter weight
Weight of ASHRAE
dust fed into the test
duct
Frequency and
description
For each efficiency test, the total
number of particles counted per
OPC sizing channel for the
upstream challenge aerosol is
computed.
Daily. Sample aerosolized PSL
spheres.
A filtration efficiency test is
performed on a reference filter
monthly during testing.
Each correlation and initial
efficiency test.
Measured during correlation and
clean device tests.
Each correlation test.
Annual. Compare to reference
manometer.
Annual. Compare to reference
manometer.
Monthly. Confirm activity of
radioactive charge neutralizers.
Confirm balance of corona
discharge neutralizers.
Filters will be weighed before
and after completion of dust
loading.
Each test based on the change in
weight of the dust on the dust-
loading tray.
Control Limits
Minimum total of 500 particle counts per channel.
Peak of distribution should be in correct OPC channel.
Efficiency must be consistent with reference filter
measurements made after OPC's primary calibration;
efficiency within ฑ 10 percentage points.
Less than 10 counts per sample.
Upper 95% confidence limit on background counts must
be less than 5% of challenge counts.
Measured pressure drop must be < 0.03 in. H2O.
Inclined fluid manometer or digital manometer readable to
within ฑ0.01 in. H2O. 10% or better accuracy.
Inclined fluid manometer or digital manometer readable to
within ฑ0.01 in. H2O. 10% or better accuracy.
Activity must be detected in radioactive neutralizers.
Corona discharge neutralizers must be in balance.
Electronic balance with 0.1 g resolution, 10% accuracy or
better, calibrated annually.
Electronic balance with 0.1 g resolution, 10% accuracy or
better, calibrated annually.
       a OPC = optical particle counter

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Page 27
Table A2.  Quality Control Parameters Associated with Scanning Mobility Particle Sizer
(SMPS) and Conditioning Aerosol
Parameter
0% Efficiency test
(100% Penetration)
SMPS: CVon
upstream counts
Conditioning aerosol
concentration
SMPS operational
checks:
sizing accuracy check
instrument flow rates
instrument zero —
filtered inlet
instrument zero — 0
volt setting
inlet impactor
photodetector
Reference flow meter
Reference manometer
Frequency and description
At least once every five efficiency
tests. A 100% penetration test is
performed with no device in the test
section.
Computed for each efficiency test
based on the upstream particle
counts.
Measured with a condensation
particle counter (CPC).
At start of project and at least
monthly during testing, sample
aerosolized monodisperse PSL
spheres.
Confirmed prior to test program
using reference flow meter.
Checked at start of project and
weekly during testing.
Checked at start of project and
weekly during testing.
Visually confirm impactor orifice is
free of debris and that the impactor
plate is greased. Daily.
Check at start of program. Filter on
CPC inlet and/or sample pump off.
Bios International Model DryCal
DC1 Primary Air Flow Meter
(soapless piston-type cell) or the
Gilabrator (good for lower
flowrates). Used to confirm SMPS
flow rates at beginning of program.
TSI Model 8702/8704 digital
manometer
and/or Meriam Model 50MH10-8
inclined fluid manometer.
Control Limit
Particle Acceptable
Size range Penetration Range:
0.01- 1.0 |im 0.70 to 1.30
<0.30
Concentration will not exceed instrument's
specified concentration limit.
A relative peak in the number distribution is
observed within 20% of the PSL particle diameter
Flows should be within 10% of set points.
< 0. 1 particle/cm3 a counted by CPC.
< 0.1 particles/cm3 counted by CPC.
Orifice clear of visible obstructions. Impactor has
very thin film of vacuum grease.
0 ฑ 0.05 volts
Based on the fundamental nature of this positive
displacement piston flow meter, the
manufacturer's accuracy claim is accepted. The
unit is visually inspected for proper operation prior
to use.
Digital manometer to receive primary calibration
by manufacturer within prior 12 months. Fluid
manometer inspected for zero and level.
       a cm = cubic centimeter

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Page 28
Table A3. Quality Control Parameters for Bioaerosols
Parameter
Minimum upstream counts for
samplers
Maximum counts for samplers
100% Penetration
(correlation test)
Upstream CPUs
Upstream PFUs
Frequency and description
Each efficiency test.
Each efficiency test.
Performed at least once per test
sequence per organism
Each test. Statistical check of data
Each test. Statistical check of data
Control Limits
Minimum of 10 CFUVplate or
PFUb/plate
Maximum of 400 CFU/plate or 800
PFUb/plate
Test Acceptable
Organism Penetration Range:
B.subtilis 0.85 to 1.1 5
S. epidermidis 0. 80 to 1 .20
MS2 0.80 to 1.20
A. versicolor 0.85 to 1.15
CVC < 0.20
CVC< 0.35
        a CPU =  colony forming units
        b PFU =  plaque forming unit
        0 CV =  coefficient of variance

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

         Table A4.  Quality Control Parameters for the Test Duct
Page 29
Parameter
Air velocity uniformity based on traverse measurements over a nine-point
cross-sectional grid at the test flow rate. Performed upstream of the test
section using a TSI Model 8345 digital thermal anemometer.
Inert aerosol uniformity based on traverse measurements over a nine-point
cross-sectional grid at the test flow rate. Performed upstream of the test
section.
Inert downstream mixing based on nine-point perimeter injection grid at the
test section and center-of-duct readings at the downstream probe locations.
100% Efficiency test based on HEPA filter test.
100% Penetration (correlation test)
OPCb upper concentration limit based on limiting the concentration to below
the level corresponding to the onset of coincidence error.
Aerosol generator response time
Duct leakage
Ratio of leak rate to test flow rate.
Determined by sealing the duct at inlet HEPA filter bank and at the ASME
flow nozzle locations followed by metering in air to achieve a steady duct
pressure. The flow rate of the metering air (equal to the leakage flow) is
measured for a range of duct pressures.
OPC zero count check
OPC sizing accuracy check based on sampling aerosolized monodisperse
PSL spheres of known size.
Aerosol neutralizer activity (if radioactive source is used)
Dust feeder air flow rate as function of discharge pressure based on
measuring the required dust feeder air gauge pressure to achieve 425 L/min.
(15 cfm) airflow.
Final device efficiency
Based on injecting 100 g of dust and computing weight change of the filter.
Control Limits
CV < 10%
CV<15%
CV<10%
Efficiency > 99%
Particle Acceptable
Size range Penetration Range:
0.3tol|im: 0.90 to 1.10
Ito3|im: 0.80 to 1.20
3tolO|im: 0.70 to 1.30
No predetermined level, but must be
established prior to testing.
No predetermined level.
Ratio < 1.0%
< 10 counts per sample
Relative maximum must appear in
the appropriate sizing channel.
Radioactivity must be detected.
No predetermined value.
100 ฑ 2 g of dust captured for 100 g
injected.
       ' CV  =  coefficient of variance
       ' OPC =  optical particle counter

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
                                                                                          Page 30
Appendix B:  Inert Aerosol Run Sheet
Date:
                         Test Operator:
Staple photo to back of page 2.
                                        _Charge Number:
Physical Description of Device:
Test Requested by:	
Manufacturer:   	
Product Name:                           	
Model:
Condition:      New or From Field     No damage or Slight frame damage and/or Media damage   (Circle
all that apply)
Other/describe damage:  	
Product type:
Other Attributes:

Height

Width

Thickness

Media Type (if applicable)


Media Color (if
applicable)


Correlation Test: (use 3/3 -10/9 - 3/3 sampling)
Date:                     Time:
Flow rate manometer zeroed and level:
                                           Device pressure drop manometer zeroed and level:
OPC clock correct:
                                           Valve switch on:
OPC: (Set for 0.10 ft3 samples with 15 second purge; use 3/3 -10/9 - 3/3 sampling)
20 min
warm
up

/


Flow is
0.25
cfm

/


CI-226
switch
"Low"
/ or
n/a


Zero Check < 10 total / sample
enter actual count



HEPA capsule or In-duct



Daily PSL check
(Enter size when
performed or / if done
earlier today)


File Name
c:\climet\rpmmddyyss
RP MM DD YY SS









  must meet <10 criteria at least once per ASHRAE 52.2 test.
Notify project manager if limit is exceeded.
                                                           ** Save daily check to disk using file name.
                                                              RPMMDDYY-HEPA-PSL.TXT

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

Test Conditions:
                           Page 31
Flow rate
(cfm)++

Flow
Manometer
(inchH2O)

Dry Bulb
Temp. (F)
Limits = 50-100 ฐF

Wet Bulb
Temp.
(ฐF)

RH
Limits =
20-65%

Arm Pressure
(inches Hg)
XX. XX

   Is flowrate MERV eligible for this size device?  Y or N (see page 3)
Aerosol Generator: JNo-Device Pressure Dro
Aerosol
Type
KCL

Pump
setting
1.2cc/
min
Drying
Air
4 cfm
240 cfh
Nozzle
air
pressure
(psi)


Nozzle
air
flowmt.


p
Upper
Concentration
Target *
enter Ch 1 count

Lower
Concentration
target **
enter Ch 1 5 cnt

At start
of test
x.xx(x)
must be < 0.03"

At end of
test
x.xx(x)
must be < 0.03"

    Channel 1 targets:  CI-500 = 3,000; Cl-Spectro = 3,000; CI-226 = 5,000                Channel 15 target: 72
-150 counts per sample desired range.             Notify project manager if these targets are not met.
Using "Correlation" graph in spreadsheet, does data look reasonable?
yes
no  (Should be near 1.0)

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners

Appendix C: Bioaerosol Run Sheet
                                                                 Page 32
Device #:_
Date:
Run#:
Test Operator:	
Climet Filename:
Test Conditions:
Test Flow Rate
CFM
ASME Nozzle
Pressure Drop
in. H2O
Temperature
ฐF
RH
%
Ambient Atm
Pressure
in. Hg
Biological Suspension:
Organism:	
Suspension Prep:_
Drying Air:	
Nebulizer Pressure:
Initial Volume:	
Time On:
Biological Sampling:
 Sample #
    Time Run Begins
Sample Length    (min.)  Media
 Ul, U2, U3
 D1,D2, D3
 D4, D5, D6
 U4, U5, U6
 U7, U8, U9

-------
Research Triangle Institute
ETV Test/Quality Assurance Plan
Biological and Aerosol Testing of General Ventilation Air Cleaners
Page 33
 D7, D8, D9
 D10,D11,D12
 U10,U11,U12
U; = upstream sample ;'
D; = downstream sample ;'

Rotometer/Vac #1 Reading:
Rotometer/Vac #2 Reading:
Rotometer/Vac #3 Reading:

-------