INTRODUCTION
The ENERGY STAR® Upgrade Manual for Buildings is a guide for planning and
implementing profitable upgrades that will improve the energy performance of your
facilities. The Manual is a guide for developing a comprehensive energy management
strategy and an integrated approach to upgrading existing buildings. It also provides
information on proven energy-efficient technologies that can produce energy savings
of 35% or greater by following the staged process outlined in the manual.
ENERGY STAR Overview
ENERGY STAR is a dynamic voluntary government and industry partnership that
makes it easy for businesses and consumers to save money and protect the
environment. In 1991, the US Environmental Protection Agency introduced the
Green Lights program, a voluntary program that encouraged organizations to
upgrade their lighting to energy efficiency lighting systems and controls. The labeling
program was launched the following year and the ENERGY STAR brand was
introduced. The ENERGY STAR brand identifies energy-efficient products and
promotes energy performance that saves energy and protects the environment. In
1996, EPA partnered with Department of Energy to increase the product offerings
of the ENERGY STAR label. The label was expanded to include new homes,
commercial and institutional buildings, residential heating and cooling equipment,
major appliances, office equipment, lighting, and consumer electronics. Green Lights,
ClimateWise, and all labeled products have been consolidated under one umbrella;
ENERGY STAR. Now, the suite of products and offerings all bear the ENERGY STAR
logo. From labeled buildings and homes to labeled products, the ENERGY STAR logo
makes it easier for businesses and consumers to recognize the symbol for exemplary
energy performance, saving money and pollution prevention.
You Can Make A Difference
With ENERGY STAR, money isn't all you'll save! Whether your business is education,
retail, manufacturing, or healthcare, you can profit from a new source of value by
adopting energy management best practices that promotes exemplary energy
performance in your buildings. If all US consumers and businesses were to choose
ENERGY STAR products and building upgrade strategies over the next decade, the
national annual energy bill would be reduced by about $200 billion. Consumers and
businesses would not only save money but would also make a huge reduction in air
pollution and contribute to protecting the earth's atmosphere for future generations.
ENERGY STAR has contributed to 6.4 million metric tons of carbon reductions and
31.6 billion kWh savings since the inception of its flagship program.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Upgrading Your Buildings
Energy efficiency prevents pollution and is good for your bottom line as well as the
environment. Your organization will save the money that was previously spent on
energy-wasting equipment and technologies. Reductions in energy consumption also
enable you to deliver products and services at a lower cost and increase profits,
which means being more competitive. The potential savings from an integrated
approach to energy-efficient upgrades can be 35% or greater. For example, energy
bills for existing US commercial space (approximately 78 billion square feet) total
$110 billion annually. EPA estimates that increasing the energy efficiency of this
space could save more than $25 billion. In addition to dollar savings, there are
several other benefits for incorporating energy efficiency into your business strategy:
• ENERGY STAR upgrades offer superior returns at a lower risk than many other
investments (see Figure 1).
• Improvements in energy performance and employee comfort can increase
productivity in your upgraded buildings; in fact, revenue generated from
increased productivity can be 10 times as high as the energy cost savings
received from performing upgrades.
• Every dollar invested in an energy-efficient upgrade can produce between $2 and
$3 in increased asset value, which can make commercial properties more
attractive to buyers and lenders.
Figure 1: Risk vs. Return
Sf
— 15 -
E?
S1 10 -
1
5 .
ENERGY STAR Buildings participation
in energy efficiency upgrades
« (Average IRR)
Latin American stock composite
NYSE composite
Long-term government bonds » »» s&p 50° composite
S&P high technology
composite
Short-term municipal bonds
0.8
1 1.5
Risk (Coefficient of variation)
2.5
Improving energy performance offers long-term, low-risk returns, reductions in
energy consumption and costs, increases in worker productivity, and improved asset
value, few other investments can do all that. And each day that you delay your
decision to upgrade, you lose those potential savings forever.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
An Integrated Upgrade Approach
An integrated upgrade approach is a formula for success that includes the following
factors:
• Involving the right people in your organization — EPA encourages top
management commitment and targets top level executives in promoting energy
performance and pollution prevention.
• Benchmarking energy performance — EPA advocates benchmarking energy
performance (EPA's portfolio manger) to optimize energy use and achieve
maximum energy and cost savings, and using proven energy-efficient
technologies and an integrated approach for building upgrades.
• Communicating results —EPA recognizes participants' successes to increase
public awareness on the benefits of energy performance. Nothing is more
convincing than success!
The rationale and approach to energy efficiency upgrades introduced below are
designed to maximize your rate of return for energy-efficient investments.
Underlying the integrated approach for building upgrades is a basic understanding of
how to improve energy performance. Figure 2 illustrates how heat and energy flow
in a building. Heat is given off by lights, people, and other supplemental loads; such
as office equipment requires space cooling. Solar radiation and hot outside air
temperatures can also impact space cooling needs. Conversely, cold outside air
temperatures create the need for heating. Even when it is cold outside, your building
may still require some cooling to remove excess heat given off by lights, people and
equipment.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figure 2: Heat Flow
o
PLANT
LOADS
Heat Flow In Buildings: Building Systems Interactions
Figure 2 shows the interaction of heating, cooling, and electrical loads with the HVAC
equipment. Arrows indicate heat flow pathways. Reducing heating, cooling, and
electrical loads reduces the demand on HVAC equipment, thus saving energy.
The staged approach synthesizes these interactions into a systematic method for
planning upgrades that enables you to maximize energy savings. The stages are:
• Recommissioning: Periodically examine building equipment, systems, and
maintenance procedures as compared to design intent and current operational
needs.
• Lighting: Install energy-efficient lighting systems and controls that improve
light quality and reduce heat gain.
• Supplemental Load Reductions: Purchase ENERGY STAR labeled office
equipment, install window films and add insulation or reflective roof coating to
reduce energy consumption of supplemental load sources.
• Fan Systems Upgrades: Properly size fan systems, adding variable speed
drives, and converting to a variable-air-volume system.
• Heating And Cooling System Upgrades: Replace chlorofluorocarbon
chillers, retrofit or install energy-efficient models to meet the building's
reduced cooling loads, upgrade boilers and other central plant systems to
energy-efficient standards.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
When the staged approach is performed sequentially, each stage includes changes that
will affect the upgrades performed in subsequent stages, thus maximizing energy and
cost savings. The first three stages, Recommissioning, Lighting, and Supplemental
Load Reductions, address reducing heating, cooling, and electrical loads. Once these
loads are reduced, you can upgrade HVAC equipment to meet the current loads and
optimize its performance. By implementing the load reduction strategies first, the
savings from fans and HVAC systems will be greater because these systems can be
properly sized to handle the reduced loads.
Build Your Building Right
After many requests from our participants to help them achieve ENERGY STAR for
new building projects, EPA has expanded its experience in energy performance for
existing buildings to the new buildings arena. It has been documented that when high
performance buildings are designed from the start, they are generally more efficient
and cost less than upgrading after the fact. Buildings systems and materials can be
designed as integral network that will improve energy performance.
ENERGY STAR provides guidance for design teams and building owners on new
building design strategies to enhance energy performance. The New Building Design
initiative is web based and will walk you through the design process and provide tools
to help you make informed decisions about energy performance on new design
projects. It starts with setting goals and ends with achieving the ENERGY STAR label
for your building. It also address all other design phases from pre-design to
construction and bid documents. Energy performance is the driving element in the
discussion at each phase. It will help you identify or ask the question, "How will this
design decision effect the energy performance of the building?"
Target Finder, a web based energy performance calculator, will help you set a target
early in the process. You can also measure your progress along the way by comparing
your simulated energy consumption to your target. The difference between the
simulated and target can assist in determining relative efficiency, identifying gaps and
making improvements to energy performance strategies. The benefit is that energy
strategies are incorporated as an integral part of the design and can be compared to
industry benchmarks to monitor progress toward reaching your energy performance
goals.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Get Started Now
You can become an ENERGY STAR partner and receive the benefits of membership!
Your organization signs a Partnership Agreement stating that they are committed to
improving energy performance by:
1. Measuring, tracking, and benchmarking energy performance using tools such as
those offered by ENERGY STAR,
2. Developing and implementing a plan to improve energy performance in your
facilities and operations by adopting the strategy provided by ENERGY STAR,
3. Educating your company and community about your achievements and
partnership with ENERGY STAR.
EPA will provide you with resources and assistance; such as analytical software tools,
publications, and technical guidance to assist you with achieving exemplary energy
performance goals. You can learn more about the obtaining the suite of offerings
from:
ENERGY STAR on the Web
ENERGY STAR Hotline
. energystar.gov
1-888-STAR YES
(1-888-782-7937)
ENERGY STAR® BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
BUSINESS ANALYSIS
Overview
Energy performance can increase the value of an organization by improving the
bottom line. The bottom line in business is net income or earnings; reduced energy
costs can be reflected in increased earnings and earnings per share. Every dollar of
increased earnings can be valued at the prevailing market earnings multiple, or the
Price Earnings Ratio. This approach to valuation is common practice among
analysts, who routinely relate market prices for shares of stock to multiples of
earnings. You can also use this approach to determine the value of energy
performance for your business— that is, increased market capitalization. ENERGY
STAR provides tools that quantify, justify and communicate the impact of energy
performance to a company's worth.
The process to improved energy performance requires that the financial merits of
opportunities be carefully evaluated. All organizations employ basic financial
analysis tools to examine the value, risk, and liquidity impacts of investment
opportunities competing for limited capital resources. To successfully compete against
other business investments, energy performance should be evaluated on the same
basis. Understanding basic financial concepts and using simple analysis tools can
facilitate an informed decision.
This chapter explains the tools necessary to evaluate profitability, cash flow, and
liquidity and presents a framework for using these tools to analyze building upgrade
investments to improve energy performance.
Capital Budgeting Basics
Both for-profit and not-for-profit organizations evaluate potential investments based
on net income (bottom line). To evaluate net income, an organizations use financial
analyses to identify whether an investment exceeds a predetermined hurdle rate while
maintaining acceptable first cost and liquidity requirements. Profitability is measured
by whether a project's internal rate of return passes the investment hurdle rate. Cash
flow and liquidity are evaluated by first cost and payback.
• First cost is the up-front cost that is incurred before the investment generates any
savings. Large first costs put stress on an organization's balance sheet and may
cause an investment to be rejected, even if it is profitable in the long run.
• Net present value (NPV) is the total net cash flow that a project generates over its
lifetime, including first costs, with discounting applied to cash flows that occur in
the future. NPV indicates what a project's lifetime cash flow is worth today.
e payback is the amount of time, in years, necessary for future cash flows to
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
return the original investment. Payback is an indicator of liquidity because it
measures the speed with which an investment can be converted into cash.
Payback is also used as an indicator of risk. As a general rule, short-term events
can be predicted more precisely than events in the distant future. Therefore,
assuming everything else is constant, projects with a shorter payback period are
generally considered less risky.
Internal rate of return (IRR) is the interest rate that equates the present value of
expected future cash flows to the initial cost of the project. Expressed as a
percentage, IRR can be easily compared with loan or hurdle rates to determine
an investment's profitability.
Hurdle rate is the accept/reject criterion for determining if an investment passes
the profitability test. If the IRR is higher than the hurdle rate, the investment is
profitable. Hurdle rates are the marginal cost of capital, adjusted for a project's
risk. The higher the cost of capital and risk, the higher the required hurdle rate.
Capital Budgeting Glossary
Cost of capital The discount rate that is used in the capital budgeting process.
Discount rate The interest rate used to discount future revenue streams.
Hurdle rate The minimum acceptable internal rate of return for a project.
Internal rate The interest rate that equates the present value of expected
of return future cash flows to the initial cost of the project.
Net present The present value of the expected net cash flows of an
value investment, discounted at an appropriate percentage rate,
minus the initial cost outlay of the project.
Simple payback The number of years required to return the original investment
from net cash flows.
Time value Money received today is valued more highly than money
of money received at a future date.
Net Income Analysis
Evaluating investment in long-term building projects requires tools that consider cash
flow over the life of a project and account for the time value of money. Simple
payback, although frequently used in the energy management industry, is not a good
indicator of profitability because it does not consider returns beyond the payback
period and ignores the time value of money. The most common tools to evaluate
investments are IRR and NPV. IRR is used to compare a project's return against a
hurdle rate to determine whether it meets financial criteria and worth pursuing. NPV
is useful for comparing and prioritizing amongst competing projects. Together, they
provide a comprehensive evaluation of a project's contribution to the bottom line.
In addition to evaluating investment returns, determining the financial value of
energy performance investments and its effect on the bottom line is equally
important. While NPV can be used to demonstrate today's value of an investment
and future returns, understanding how energy performance can impact key financial
and profitability metrics such as profit margin, earnings per share, net reserve, and
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
market capitalization should be considered in capital decision making. Valuing the
incremental earnings that result from improved energy performance is a way to
capture the true worth to an organization. ENERGY STAR has developed a financial
value calculator (fvc) to analyze how energy performance projects can improve an
organization's net income and corporate value. Visit ENERGY STAR Web site at
www.energvstar.gov.
Financial Evaluation
ENERGY STAR encourages using energy performance measurement and/or
equipment upgrades to maximize energy savings while improving building comfort
and indoor air quality. The following framework provides a systematic approach to
evaluating energy performance investments and can be applied to comprehensive
building upgrades or new designs.
1. Prepare a cash flow analysis for each upgrade or design option.
2. Calculate IRR for each option. Determine each option's profitability against the
hurdle rate.
3. Compare competing options and prioritize options within a package using NPV.
4. Maximize energy efficiency by packaging upgrade options or carefully
integrating systems where appropriate.
Business Analysis Process
Cash Flow Analysis
Evaluating profitability with IRR and NPV requires the preparation of a cash flow
analysis. A simple cash flow estimate (see Table 1) should be prepared for each
potential energy-performance option suggested by an energy audit. Cash flow
analysis can also be used to compare the theoretical performance of an efficient
building design to that of a conventional design. This analysis lists the year-to-year
costs and savings for all implementation, operation, maintenance, and disposal costs,
and energy and demand savings, over the life of the equipment or building. For this
demonstration the investment is evaluated over a period of 10 years. Each option
generally has a first cost and a stream of cost savings. In our example, the first cost
is the installation cost, which occurs in year zero. In the unusual case that the retrofit
is planned over multiple years, provide an estimate of the cost for each year in which
the work will be completed. Be sure to document the projected schedule in the list of
key assumptions.
Project energy cost savings. Typically, an energy audit report converts your energy and
demand savings into monetary savings based on your current energy rates and
operating schedules. Similarly, computer energy simulation can estimate annual
savings associated with an efficient design. If you anticipate energy price changes,
you may want to adjust the amount of savings in future years. Also, for a multiyear
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
project, you will need to phase in the energy savings over the first few years as
appropriate. Be sure to document the energy rates that are used for the calculation
and the planned operating schedules in the list of key assumptions. In our example,
the energy prices and operating schedules will remain constant over the 10-year life
of the equipment.
Table 1:
Year
0
1
2
3
4
5
6
7
8
9
10
Cash Flow Analysis For LED
Retrofit
Cost
$ 3,250
0
0
0
0
0
0
0
0
0
0
Key Assumptions:
1. Retrofit will be completed in 3
Energy &
Savings
$ 0
2,181
2,181
2,181
2,181
2,181
2,181
2,181
2,181
2,181
2,181
months.
Exit Signs
Maintenance
Savings
$ 0
200
200
200
200
200
200
200
200
200
200
Omitted Risk
Savings Level
Neutral Neutral
2. LED exit signs have a 10-year life expectancy.
3. Energy savings are based on the current average energy rate of $0.078/kWh.
4. No changes in energy rates will occur during the 10-year period.
5. Maintenance savings are realized because lamps are changed less frequently.
Estimate the annual savings in maintenance costs. In our example, we are replacing
incandescent exit signs with LED signs, and can thus realize substantial savings in
labor and materials over the life of the equipment. In some cases, an energy-efficient
retrofit can require more maintenance than before, resulting in a negative
maintenance savings entry. Document all key assumptions regarding maintenance
savings.
Provide qualitative guidance. Additional savings or costs can be difficult to quantify.
Potential savings that are hard to measure include worker productivity gains,
increased sales attributable to the upgrade, and enhanced corporate image. Omitted
savings/costs should simply be classified as having a negative, neutral, or positive
influence on the net annual cash flow For all six of the lighting options in the
example, omitted costs/savings are neutral, even though evidence suggests that office
lighting retrofits can increase worker productivity.
Classifying the risk level of the project can also be difficult. Because of uncertainty
about future events (for example, future prices of electricity), anticipated cash flows
may be difficult to estimate. However, compared with other investments that a
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
company may make, such as new product development, energy efficiency projects
are still considered a low risk. If you do not know the risk levels of other
investments your organization is considering, you may want to classify the risk of
energy-efficient investments as neutral to be conservative.
Cash flow analyses for most options will follow this simple example, in which the
initial cost occurs in year zero, savings estimates are constant over the life of the
project, and risk and omitted cost/savings are neutral.
Cash Flow Assumptions
Estimating cash flow is the most difficult part of any financial analysis. While initial
retrofitting or construction costs can be estimated based on experience, estimates of
energy savings and operation and maintenance costs savings are based on more
extensive assumptions that may be affected by numerous variables. Because future
events may not occur as anticipated in your assumptions, the IRR realized for the
project may vary considerably from your original estimate. Recognizing this
uncertainty, you should explicitly list the assumptions underlying your cash flow
estimates, and reach a consensus with other staff that these assumptions are
reasonable. At a minimum, assumptions that should be documented are the future
prices of energy and your basic operating conditions.
Taxes can also affect your cash flow estimates. Increasing depreciation, decreasing
energy and maintenance expenses, and, if your project is debt financed, increasing
the amount of your interest deduction can affect an organization's tax liability. If you
are unfamiliar with these tax implications, simply omit them from your analysis and
express your results in pre-tax terms.
Profitability Test
If all the options being considered have a single-payment first cost, cash flows that
are uniform for the entire time horizon, and equal-length life spans, you can easily
determine IRR using a calculator and Table 2.Using the table, a 20% IRR hurdle rate
would result in a simple payback of 4.2 years, options with less than a 4.2-year
simple payback would be considered profitable.
Calculate the IRR for each project, and simply compare it to your hurdle rate. If the
option exceeds the established hurdle rate, that project would be considered
profitable and should be pursued. IRR should be used to determine profitability for
each project. It should not be used to compare or prioritize projects; this approach
can minimizes first cost rather than maximizing energy performance and long-term
savings.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Table 2: Project IRR After Simple Payback
Payback
(yeafs) Time Horizon (yeafs)
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
12345678 9
0.0% 61.8% 83.9% 92.8% 96.6% 98.4% 99.2% 99.6% 99.8%
21.5% 44.6% 55.2% 60.4% 63.1% 64.6% 65.5% 66.0%
0.0% 23.4% 34.9% 41.0% 44.5% 46.6% 47.8% 48.6%
9.7% 21.9% 28.6% 32.7% 35.1% 36.7% 37.8%
0.0% 12.6% 19.9% 24.3% 27.1% 29.0% 30.2%
5.6% 13.2% 18.0% 21.1% 23.2% 24.6%
0.0% 7.9% 13.0% 16.3% 18.6% 20.2%
3.6% 8.9% 12.4% 14.9% 16.7%
0.0% 5.5% 9.2% 11.8% 13.7%
2.5% 6.4% 9.2% 11.2%
0.0% 4.0% 6.9% 9.0%
1.9% 4.9% 7.1%
0.0% 3.1% 5.3%
1.5% 3.8%
0.0% 2.4%
1.2%
0.0%
10
99.9%
66.3%
49.1%
38.5%
31.1%
25.7%
21.4%
18.0%
15.1%
12.7%
10.6%
8.7%
7.1%
5.6%
4.3%
3.1%
2.0%
0.9%
0.0%
11
100.0%
66.4%
49.4%
38.9%
31.7%
26.4%
22.3%
18.9%
16.1%
13.8%
11.8%
10.0%
8.4%
7.0%
5.7%
4.6%
3.5%
2.5%
1.6%
12
100.0%
66.5%
49.6%
39.2%
32.2%
26.9%
22.9%
19.6%
16.9%
14.7%
12.7%
11.0%
9.5%
8.1%
6.9%
5.7%
4.7%
3.8%
2.9%
13
100.0%
66.6%
49.7%
39.5%
32.5%
27.3%
23.4%
20.2%
17.6%
15.3%
13.4%
11.8%
10.3%
9.0%
7.8%
6.7%
5.7%
4.8%
4.0%
14
100.0%
66.6%
49.8%
39.6%
32.7%
27.6%
23.7%
20.6%
18.0%
15.9%
14.0%
12.4%
11.0%
9.7%
8.5%
7.5%
6.5%
5.6%
4.8%
15
100.0%
66.6%
49.9%
39.7%
32.9%
27.9%
24.0%
20.9%
18.4%
16.3%
14.5%
12.9%
11.5%
10.2%
9.1%
8.1%
7.2%
6.3%
5.6%
Prioritise Options
To compare two competing options or to prioritize options, a net present value (NPV) analysis should
be used. NPV discounts the future total net cash flow over a project's life, and tells you what a
project's future cash flow is worth in today's dollars. As with IRR, NPV is calculated by using a
financial calculator or spreadsheet Note that IRR and NPV are related, a negative NPV indicates that
the option generates less than the established rate of return.
For example, you have the option of controlling lighting with a Central Time clock or individual
occupancy sensors. Table 3, illustrates that the time clock has a higher IRR and quicker payback, but
NPV analysis suggest that occupancy sensors would increase energy savings and net worth of your
organization. Similarly, NPV can be used to prioritize and rank the value of options within a package
of upgrades (see Table 4).
Bundle Upgrades
What about options that are considered marginally profitable, but can still contribute to maximizing
the energy efficiency of a project? In our example, improving office task lighting, when evaluated
individually, does not meet our required hurdle rate. However, when task lighting is packaged with the
other more profitable aspects of lighting upgrades, the combined project IRR still exceeds the hurdle
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
rate. By using an integrated approach, the task lighting can be included in the upgrade
package and still meet investment criteria.
Table 3: Comparing The Profitability Of Upgrade Options
Year
Initial
0 $ 42
1
2
3
4
5
6
7
8
9
10
Over Ten Years
Simple Payback
IRR
NPV
Upgrade Option 1A
Occupancy Sensors
Cost S
,000
0
0
0
0
0
0
0
0
0
0
ji'itigs Generated
$ 0
12,200
12,200
12,200
12,200
12,200
12,200
12,200
12,200
12,200
12,200
Cumulative
% 122,000
3.4 years
26%
$ 7,623
Upgrade
Central
Initial Cost
% 9,000
0
0
0
0
0
0
0
0
0
0
Savings
Option 1B
Timeclock
^aiings Generated
$ 0
3,550
3,550
3,550
3,550
3,550
3,550
3,550
3,550
3,550
3,550
$ 35,500
2.5 years
38%
$ 4,903
In another example, including a daylight dimming option would not be pursued,
because it is not profitable both when evaluated on its own and as part of the overall
upgrade package. Incremental costs alone should not dissuade the specifier from
including an option that is marginally profitable. Options can be quantified in terms
other than cost, particularly if the option can significantly improve aesthetics or
lighting quality, or provide other non-tangible benefits.
Other Considerations
Remember that these financial calculations are based on key assumptions. If any of
your assumptions change, analyze all of the options again before going forward with
a proposed package of options. Another important factor that may affect the
decision to pursue an energy-performance investment is the manner in which the
project is financed. Financing options affect the balance sheet in different ways and
can be a determining factor on whether to accept an investment proposal. See the
Financing chapter in this manual for more information on loans, leasing,
performance contracting, and other financing alternatives.
ENERGY STAR® BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Table 4: Assemble A Profitable Package
Stage Two
Lighting Options
la Install Occupancy
Sensors
Ib Install Central
Timeclock
2 Install LED
Exit Signs
3 Improve Corridor
Lighting
4 Improve Office
Lighting
5 Upgrade Task
Lighting
6 Install Daylighting
Controls
Options la-4
Options la-5
Options la-6
NPV
$7,623
4,902
5,606
5,106
4,751
(929)
(26,524)
$23,091
$22,161
$(4,363)
First
IRR
26%
38%
73%
38%
23%
16%
2%
27%
26%
19%
Annual
Net
Cost
$42,000
9,000
3,250
9,490
57,605
9,500
59,080
Package Resa/ts
$112,345
$121,845
$180,925
Cash Omitted
Flow Savings Risk
$12,200 Neutral
3,550 Neutral
2,380 Neutral
3,725 Neutral
15,100 Neutral
2,000 Neutral
6,500 Neutral
$33,405
$35,405
$39,905
Neutral
Neutral
Neutral
Neutral
Neutral
Neutral
Neutral
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
FINANCING
Overview
Energy performance projects may be different from many other business
investments in that they provide an immediate and predictable positive cash flow
resulting from lower energy bills. This feature allows them to be financed with both
familiar and unconventional financing products.
Regardless of your organizational requirements or constraints, there is a financing
option available to help you realize the profitability of energy performance
improvements.
Financing section discusses payment and financing options and suggests evaluation
criteria to help you select the option that is right for your organization, whether you
are in the private or public sector. While the right financing option will depend upon
many factors such as debt capacity, in-house expertise, and risk tolerance, there are
viable options for virtually any type of organization. The following table
summarizes financing options traditionally used in the public and private sectors.
Public
Purchasing 1
Cash 1
Loan
Private
1
1
1
Leasing
Capital Lease
Tax-Exempt Lease
Operating Lease
1
1
1
Performance Contracting
Shared Savings 1
Paid from Savings 1
1
1
Payment and Financing Options
The payment and financing options discussed below include:
• Purchasing equipment and services
• Leasing
• Performance contracting
• Public and Institutional Options
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Purchasing Equipment and Services
Cash
A cash purchase is the simplest method for financing energy performance
improvements. A cash purchase makes sense if your organization has cash reserves
and a strong balance sheet. The advantage of a cash purchase is that all cost savings
realized from the upgrade are immediately available to your organization. Additionally,
the depreciation of the equipment becomes a tax deduction. The disadvantage of a
cash purchase is the loss of opportunities associated with not having that capital
available for other investments.
Generally, relatively inexpensive, simple efficiency measures that are likely to pay for
themselves in about a year are purchased with cash. Large complex projects are often
financed differently.
Cash Purchase
On balance sheet?
Initial payment
Payments
Ownership
Tax deductions
Performance risk
yes
100%
none
owner
depreciation
owner
Loan
Lenders may require up to a 40 percent down payment on loans for energy projects.
Generally, a high-risk loan will have less leverage (ratio of debt to equity for the
project), a higher interest rate, and a shorter term of debt. As a borrower, you may
put up business or personal assets as security for the loan. Your borrowing ability will
depend on your organization's current debt load and credit worthiness. Loan payments
may be structured to be equal to or slightly lower than projected energy savings. In
this financing arrangement, you bear all the risks of the project and receive all the
benefits.
Including high performance features during new building design is simpler to justify,
since energy efficiency depends on the selection and combination of components that
will be purchased regardless of performance goals. Rightsizing lighting and HVAC
equipment may eliminate incremental first cost increases. As a result, many of these
projects need no additional funding or a slight increase for extended architectural and
engineering services and commissioning.
ENERGY STAR? BatldingManaal
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Loan
On balance sheet?
Initial payment
Payments
Ownership
Tax deductions
Performance risk
yes
downp ayment
fixed
owner
depreciation,
interest
owner
Leasing
You may procure your energy performance upgrade through leasing to spread out the
term of payments. Lease payments are usually lower than loan payments. Laws and
regulations for equipment leasing are complex and change frequently, so be sure to
consult your financial executive, attorney, or auditor before entering into a lease
agreement.
Capital Lease
Capital leases are installment purchases of equipment. Little or no initial capital outlay
is required. With a capital lease, you eventually own the equipment and may take
deductions for depreciation and for the interest portion of payments. A capital asset
and associated liability will be recorded on your organization's balance sheet.
Based on the criteria defined by the Financial Accounting Standards Board (FASB)
Statement No. 13, a lease meeting one or more of the following criteria qualifies as a
capital lease:
• The lease transfers ownership of property to the customer at end of the lease
term.
• The lease contains a bargain purchase option.
• The lease term covers 75 percent or more of the estimated economic life of the
equipment.
• The value of the lease equals or exceeds 90 percent of the fair market value of
the equipment at the beginning of the lease.
If you work for a governmental organization, you may be eligible for a tax-exempt
capital lease. Because the lessor does not pay taxes on the interest from these leases,
the rates are lower than typical market rates. For municipal organizations that can
undertake new debt, tax-exempt capital leases can be very attractive.
Tax-Exempt Lease
A tax-exempt lease purchase agreement, also known as a municipal lease, is closer to
an installment purchase agreement than a rental agreement. You will own the
equipment after the financing term is over. A benefit of the lease purchase
agreement is that the lessee's (borrower's) payment obligation usually terminates if
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
the lessee fails to appropriate funds to make lease payments. Because of this
provision, neither the lease nor the lease payments are considered debt, and payments
can be made from the energy savings in your operating budget. Unlike bond issues,
tax-exempt lease purchase financing usually does not require a voter referendum
because it is considered an operating rather than capital expenditure due to this non-
appropriation language. However, lenders will want to know that the assets being
financed are of essential use, which will minimize the risk of non-appropriation. In
fact, your organization may already be leasing equipment, and it may be surprisingly
easy to add your energy project to the existing lease agreement, especially if your
organization has a Master Lease in place with a lending institution.
Capital Lease
On balance sheet?
Initial payment
Payments
Ownership
Tax deductions
Performance risk
yes
none
fixed
owner
depreciation,
interest
owner
Operating Lease
Under an operating lease, the lessor owns the equipment. It is, in effect, "rented"
(leased) to your organization for a fixed monthly fee during the contract period. The
lessor claims any tax benefits associated with the depreciation of the equipment. At
the end of the contract term, you can purchase the equipment at fair market value
(or at a predetermined amount), renegotiate the lease, or have the equipment
removed.
To meet the FASB definition of an operating lease, the lease term must be less than
75 percent of the equipment's economic life, and the total value of the lease
payments must be less than 90 percent of the fair market value of the equipment at
the start of the lease. If the equipment has residual value as used equipment, it may
be eligible for an operating lease.
Discuss the project's qualifications with a financial decision-maker before entering
into an operating lease for energy-efficient equipment.
Operating Lease
On balance sheet?
Initial payment:
Payments:
Ownership:
Tax deductions:
Performance risk:
no
none
fixed
lessor
lessor
lessor
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Performance Contracting
As you research financing options for your project, you will certainly hear about
performance contracting. A performance contract may be the preferred financing
option if your organization wants to keep the upgrade project off its balance sheet.
This type of contracting can be complex, but it is becoming increasingly common.
A performance contract is one in which payment for a project is contingent upon its
successful operation (see Figure 1). For an energy performance upgrade, services are
rendered in exchange for a share of the future profits from the project.
A performance contract can be undertaken with no up-front cost to the building
owner and is paid for out of energy savings. The service provider obtains financing
and assumes the performance risks associated with the project. The financing
organization owns the upgraded equipment during the term of the contract, and the
equipment asset and debt do not appear on your balance sheet. Financing for
performance contracts relies little on the financial strength of the building owner, but
it is based on the cost savings potential of the project.
Through performance contracting, any of the financing options discussed above can
be negotiated to guarantee that, as the customer, you receive the estimated cost
savings from the energy performance upgrade. Performance contracting can be
applied to purchases or leases.
Figure 1: Performance Contract
$
Old
Energy
Bill
Cash
Flow
ESCO
Payment
New
Energy
Bill
]
v Savings
In a performance contract, an outside party provides a services package. This
package can range from a simple audit, installation, and monitoring to full operation
of a facility's energy systems. The service provider typically conducts an energy audit,
designs the cost-effective projects, obtains bids, manages the construction, guarantees
energy savings, obtains financing, and maintains the energy-saving capital
improvements. You use resulting energy savings to pay for the improvements.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Performance contracts are sometimes referred to as "shared savings" or "paid from
savings" contracts. These terms refer to the manner in which payment is made for
the upgrade.
Performance Contracting
On balance sheet?
Initial payment:
Payments:
Ownership:
Tax deductions:
Performance risk:
no.
none.
variable or fixed.
contractor.
contractor.
contractor.
The service provider pays the energy bill and retains the difference between your
payment and the actual bill (for example, the actual bill may be only 60 percent of the
expected bill). In this case, if there is an increase in energy usage, the service provider
must make up the difference between your payment and the actual bill.
Shared Savings
With shared savings, the dollar value of the measured savings is divided between you
and the service provider (see Figure 2). If there are no cost savings, you pay the
energy bill and owe the contractor nothing for that period. The percentage
distribution of the savings between the service provider and the customer is agreed
upon in advance and documented in the performance contract. At the end of the
contract, ownership transfers to the building owner as specified in the contract. You
either may purchase the equipment at fair market value or simply assume ownership
of the equipment paid for during the contract term.
t'isyffc 2: Shared Sai'ings
o o
Total Savings
Customer Share
Time
ENERGY STAR® EuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figures 2 and 3 illustrate the distribution of the cost savings under two
scenarios. The specific payment arrangements between you and the service provider
are specified in your contract.
Paid from Savings
Almost all energy performance projects are paid for from the savings created by
reduced energy usage. Thus, the term "paid from savings" can be used for several
different types of energy-upgrade contracts. Here it is being used to refer to another
performance contract payment whereby you pay the service provider a
predetermined amount each period (for example, an amount equal to 80 percent of
the expected energy bill before the upgrade—see Figure 3).
Figure 5: Paid From Savings
o o
Total Savings
Customer Share
Time
Performance contracts can be complex and take a long time to negotiate and
implement. The contracts usually:
• Specify detailed work for individual facilities
• Involve large sums of capital
• Cover a wide range of contingencies
• Require significant expertise in law, engineering and finance
For a service provider and financier to make a commitment to an energy efficiency
project, the potential for savings must be substantial. Performance contracts are
usually arranged for facilities with annual energy costs over $150,000. However,
smaller projects may be good candidates depending on the project specifics.
Entering into a performance contract is like forming a partnership with a service
provider. You are arranging a complex, long-term relationship through a contractual
agreement. It is important for you to remain in close communication with the service
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
provider during contract negotiations and project implementation. Build contingencies
into the contract for any issues you can anticipate. For example, an operations change
such as adding a piece of manufacturing equipment or changing operating hours can
have a significant impact on energy use. By incorporating responses to likely changes
up front, you can avert major operational or contractual problems down the road.
A performance contract is a major commitment for you and the service provider. As
a financing tool, it offers the benefits of low-risk capital improvements off the
balance sheet. Although there are no initial payments to the contractor, you should
expect to spend time and resources providing data the service provider will need to
perform the audit and establish a baseline from which to estimate energy savings. If
you wish to select a service provider through a competitive procurement, you will
have to prepare requests for qualifications or proposals and evaluate the submittals.
Defining all the terms and conditions of the contract can be a lengthy process and
may require hiring independent engineers or other professionals to review the
contract on your behalf. The business of performance contracting is growing, so
there is an expanding pool of competent and capable service providers available to
you. Although the contracting process is complex, it creates an opportunity for
organizations with limited debt capacity or capital resources to undertake profitable
energy performance projects that would otherwise not be implemented.
Guaranteed Savings Insurance
Guaranteed savings insurance is a method of reducing your risk. This option
guarantees that energy cost savings will exceed an established minimum dollar value.
Typically, this guaranteed minimum equals the financing payment for the same period
to ensure a positive cash flow during the financing term.
Like any insurance policy, you'll pay a premium that compensates the guarantor for
the performance risk and covers monitoring costs. This premium is added to your
loan or lease payment and the guarantor will maintain and monitor the performance
of your upgrade. The supplier, installer, or service provider selling the upgrade
usually offers this guarantee.
Public and Institutional Financing Options
The two most common public sector mechanisms are tax-exempt lease purchase
agreements and performance contracts. A performance contract can be considered a
finance mechanism because it bundles together with performance guarantees one or
more of the following components: financing, equipment, energy costs, and
maintenance. Both mechanisms are effective alternatives to traditional debt
financing, and both may allow you to pay for energy efficiency upgrades by using
money that is already in your utility operating budget. By spending only operating
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
budget dollars, you may avoid the cumbersome capital budget process altogether.
Both mechanisms will allow you to draw on dollars saved from future energy bills to
pay for new, energy-efficient equipment today.
Evaluation Factors
Finding the right financing vehicle for your project requires a thorough evaluation of
your options. The following factors will help define your organization's business
profile and will enable you to select the financing option that best meets your
organization's objectives.
• Balance sheet
• Initial payment
• Payments
• Ownership
• Tax deductions
• Performance risk
A brief description of each follows.
Balance Sheet
If your organization is near the level of debt permitted by your lenders, you may not
be able to undertake additional debt without violating certain covenants. There are,
however, methods that enable a company that cannot assume more debt to proceed
with an upgrade and take advantage of the financial benefits.
Initial Payment
A large initial capital outlay may be an obstacle for some organizations planning
energy performance upgrades. If you have large capital reserves or are planning a
small project, it makes sense to pay for the project with cash. Then all the cost
savings from the project will be immediately available to you to offset the original
investment. There are financing options that can move a project forward with no
initial capital outlay from you, the customer. If capital resources are tight, you may
want to consider a performance contract.
Payments
Your goal is to obtain financing at a minimum cost to your organization. However,
benefits such as off-balance sheet financing may justify paying more for your
borrowed money. The general advantage of energy performance investments is that
even with performance contracts, which tend to be more costly because of the
amount of monitoring and verification involved, you are guaranteed to receive
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Table 1: Financing Options
Cash
Interest Rates N/A
Financing Term N/A
Other Costs N/A
Approval Internal
Process
Approval Time Current budget
period
Funding N/A
Flexibility
Budget Used Either
Largest Benefit Direct access if
Largest Hurdle Never seems to
be enough
money available
for projects
Bonds
Lowest
May be 20
years of more
Underwriting
legal opinion,
insurance, etc.
May have to be
approved by tax
payers or public
referendum
May be lengthy
- process may
take years
Very difficult to
go above the
dollar ceiling
Capital
Low interest
rate because it
is a general
obligation of the
public entity
Very time
consuming
Municipal Lease
Low tax-exempt
rate
Up to 10 years
is common and
up to 12-15
years is possible
for large
projects
None
Internal
approvals
needed. Simple
attorney letter
required
Generally within
one day
Can set up a
Master Lease,
which allows
you to draw
down funds as
needed
Operating
Allows you to
buy capital
equipment using
operating dollars
Identifying the
project to be
financed
Performance
Contracts
Can be taxable
or tax-exempt
tax-exempt rate
Typically up to
10 years but
may be as long
as 15 years
May have to pay
engineering
costs if contract
not executed
RFP usually
required, internal
approvals
needed
Generally within
2-3 days once
the award is
made
Relatively
flexible. An
underlying
Municipal Lease
is often used
Operating
Provides
performance
guarantees
which help
approval
process
Identifying the
project to be
financed and
selecting the
ESCO
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
financial benefits immediately upon completion of the project. At the end of the
contract term, those savings are yours.
Ownership
If you own your energy performance upgrade equipment, you are entitled to tax
deductions for depreciation or interest payments and other benefits. You are also
liable for any performance risk associated with the equipment.
Tax Deductions
As an equipment owner, your business is entitled to potential tax benefits such as
depreciation and deductions for loan interest. If you finance your upgrade off the
balance sheet, you will not be eligible for tax benefits.
Performance Risk
There is risk associated with any investment. Energy performance upgrades can be
low-risk investments because they apply proven technologies with long records of
performance. However, the financing option you choose will affect who bears the
risk of performance failure.
Performance risk of energy upgrades depends on the accuracy of the assumptions
concerning maintenance, cost of energy, occupancy, and other factors. Lighting
upgrades are typically considered a lower risk investment than HVAC investments,
because it is easier to predict energy savings from lighting upgrades.
More Savings Opportunities
When you begin your search for project capital, begin by bargain hunting for special
programs that support energy performance. Every organization planning an energy
performance upgrade should investigate the availability of utility incentives, state
assistance, and other cost-reducing measures.
Utility Incentives
Utilities often provide financial incentives for energy performance upgrades through
rebates, fuel switching incentives, low-interest loans, and energy audits. Check with
your local utility to learn what programs are available.
State Assistance
Some states offer financial assistance to nonprofit organization or small businesses
for operating improvement upgrades. Contact the state agency that monitors the type
of service provided by your organization to inquire about these opportunities. For
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
example, Florida's Energy Loan Program was created to motivate small business
owners to evaluate their total energy usage and implement energy conservation
measures. Funding may be available through the State Energy Programs, energy
conservation programs supported by the US Department of Energy.
Summary of Options
Whether your energy performance project involves small improvements or a
complete system upgrade, there is a suitable financing option for you. A simple cash
purchase yields immediate benefits to the customer and is a straightforward
transaction. It is well suited for small or low-risk upgrades. Performance contracting,
the most complex type of arrangement, offers the customer the benefit of risk
protection. It is also the most costly financing option because of the amount of
monitoring and verification required. However, even this more expensive alternative
yields a positive cash flow for the customer immediately upon installation. Regardless
of your organizational requirements or constraints, there is a financing option
available to help you realize the profitability of energy performance improvements.
Table 2: Summary Of Options
Evaluation
Factor
Balance
sheet
Initial
payment
Payments
Ownership
Tax
Cash
Purchase
on
100%
none
owner
depreciation
Loan
on
do wnp ayment
fixed
owner
depreciation,
Capital
Lease
on
none
fixed
owner
depreciation,
Operating
Lease
off
none
fixed
lessor
lessor
Performance
Contract
off
none
variable or
fixed
contractor
contractor
deductions interest interest
Performance owner owner owner lessor contractor
risk
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
RECOMMISSIONING
Overview
Recommissioning is essentially the same process as commissioning, but applied to
existing building's HVAC, controls, and electrical systems. When standardized
maintenance and energy management procedures fail to fix chronic building
problems, recommissioning provides a systematic approach for discovering and
solving them. Recommsioning entails the examination of actual building equipment
systems operation and maintenance procedures for comparison to intended or design
operation and maintenance procedures.
The heat flow diagram (Figure 1) illustrates the interaction of all buildings systems
and activities. Recommissioning capitalize on heating, cooling, and electrical load
reductions by continually monitoring energy consumption to optimize energy
performance and savings. Recommisioning can be a cost-effective retrofit in itself,
sometimes generating more savings than the cost of the retrofit measure. This can
result in additional savings other than direct energy cost reductions. For example, a
recommissioning may help avoid the need to install new or additional equipment,
resulting in capital savings. In the recommissioning phase, you will continue to
implement numerous cost-effective strategies to reduce your heating, cooling, and
electrical loads, and your overall energy consumption, while improving occupant
comfort.
Previously referred to as Building Tune-Up, the recommissioning chapter will help
you understand if the building is operating as intended and if current operational
needs are being met. It will help you identify improper equipment performance,
opportunities for saving energy and money, and strategies for improving
performance of the various building systems. "Best Ways to Save" and "Take
Action" are checklists of typical opportunities to tune-up equipment and how to
approach funding recommissioning
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figure 1: Heat Flow In Suit
PLANT
LOADS
Heat Flow In Buildings: Building Systems Interactions
Figure 2 shows the interaction of heating, cooling, and electrical loads with the HVAC
equipment. Arrows indicate heat flow pathways. Reducing heating, cooling, and
electrical loads reduces the demand on HVAC equipment, thus saving energy.
The Best Ways To Save
• Calibrate building controls such as thermostats and occupancy sensors.
• Adjust operating schedules to ensure equipment is on only when necessary.
• Check for leaking or improperly functioning steam traps.
• Clean heat exchanger tubes in the condenser, evaporator, and boiler to maintain
optimal efficiency.
Take Action!
• Recognize building tune-up as an opportunity to reduce energy costs and regain
or improve comfort.
• Allocate time and funding to a building tune-up separately from your ongoing
maintenance budget.
• Explore available financing options if in-house funds are not available.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Understanding Recommisioning Process
Making low-cost or no-cost adjustments to your building systems will not only
minimize your current operating costs but will also lower future maintenance costs.
Furthermore, performing a recommissioning will help you understand your building's
current operational needs, how it is intended to operate, and how you can improve
the current level of performance in the other stages.
Commis sioning
Commissioning is a quality assurance process that ensures design intent and operational needs
are met for new buildings or major rehabilitation. Ideally, commissioning takes place during
the construction process and continues through occupancy.
Maintenance
Maintenance is an ongoing process to ensure that equipment operates at peak performance. It
should take place following the initial system tune-up and should be routinely scheduled for
the life of the equipment.
Unlike the other four stages of an integrated upgrade approach recommissioning
does not necessarily require purchasing and installing new equipment or technology.
However, both time and budget should be set aside expressly for a building
recommissiong Savings, though often surprising, can be harder to estimate in
advance; yet, because recommissioning plays an integral role in the process of
identifying potential upgrade opportunities to be implemented in the other stages, it
should be viewed, planned, and funded as a process separate from standard
maintenance.
Financing can be a limiting factor, especially if a recommissioning is mistakenly
lumped into the maintenance budget. Financing options are often available. See
Financing Your Energy-Efficient Upgrade chapter.
Performing a Successful Recommisioning Project
The key to a successful recommissioning process is the commitment of the
commissioning team. The commitment may be express through a written contract
defining the responsibilities and contractual relationship of team members, and the
specific tasks to be performed by each team member according to area of expertise.
One major task in the process is for the owner's design professionals and contractors
to set realistic contract agreements and assign appropriate responsibilities.
Communication among the recommissioning team and facility staff is paramount for
uncovering building systems problems and opportunities.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
A successful re commissioning effort also depends not only on a deep understanding
of building systems but also a firm grasp on how people interact to operate the
building systems from day to day. This helps the recommissioning team to collect
accurate data and propose cost-effective and energy savings solutions.
Recommissioning may be performed by in-house staff or by outside contractors. A
decision to obtain outside expertise should not be viewed as "pointing the finger" at
maintenance staff for previous oversights but instead as an opportunity to get a non-
bias assessment of building systems operation and maintenance procedures.
Facility staff that are trying to fix these problems work under a variety of
constraints, including limited labor force, limited budgets, and limited access to
monitoring equipment. Sometimes, facility maangement lack technical expertise or
staff to perform diagnostic tests and repair problems.
However, recommissioning will affect the building's future maintenance and
operations program, facility staff should be updated on revised maintenance and
operations procedures. In addition, facility staff should undergo regular training to
learn how to effectively operate and maintain building's systems.
Recommissioning Strategy and Savings Potential
The strategy for recommissioning is a series of building recommissioning that build
upon one another in a staged approach. By following the order suggested below, you
can capitalize on the benefits of a comprehensive systems upgrade approach.
When recommissioning your building, you should keep in mind the primary goal,
does the building operate as intended and are operational needs being met. For
example, occupant comfort is paramount in the operational needs assessment.
Occupants mil modify their personal space to achieve comfort. This often results in
tampering with thermostats and sensor calibrations, using inefficient portable lighting
or space heaters, or even blocking vents, all of which will further increase energy
use.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Potential Savings
Building Recommissioning Offer Surprising Paybacks
A detailed assessment of the costs and benefits of tuning up buildings was conducted based
on a survey of results from more than 40 tune-up projects. Results from the study confirmed
that recommissioning can typically translate into energy savings of 5 to 15 percent. Although
it is difficult to pinpoint exactly which tune-up procedures generate the greatest savings, a
study performed by the Energy Systems Laboratory of Texas A&M University showed that
about 80 percent of all savings from recommissioning come from optimizing building control
systems. Improving operations and maintenance accounts for nearly all remaining savings.
Financing the tune-up of a building may require spending funds up front, although parts are
generally inexpensive and expenses are minimal. However, you should plan on incurring addi-
tional labor costs. If your building's maintenance staff does not have the skills to perform
tune-up procedures, or, if your staff is simply too busy, look into outside consultants such as
energy service companies or utility companies. Energy service companies have offered tune-up
services for years as part of shared-savings contracts. Some utilities continue to conduct re-
commissioning on a fee-for-service basis.
Source: "Commissioning Existing Buildings/' E SOURCE Tech Update (TU-97-3; March 1997).
Recommissioning will assist you with systematically assessing building performance
and effects of occupants and equipment loads on performance. The
recommissioning process consist of a series of strategically ordered building
recommissioning should be implemented in the following order:
Building Tune-Up Strategy
• Lighting + Supplemental Loads.
• Building Envelope.
• Controls.
• Testing, Adjusting, and Balancing.
• Heat Exchange Equipment.
• Heating and Cooling System.
Lighting
The lighting systems within a building are an integral part of a comfortable working
environment. Over the course of its life, all lighting systems become gradually less
efficient. Certain efficiency losses are unavoidable, such as reduction in light output
are due to the aging of lighting equipment. However, other efficiency losses, such
as improperly functioning controls, or dirt accumulation on fixture lenses and
housings and lamp lumen depreciation can be avoided by regularly scheduled lighting
maintenance.
Insufficient lighting can have a negative impact on energy performance of the
building. Without adequate lighting, occupants will bring in less efficient fixtures, thus
increasing the lighting and cooling loads in the building.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Lighting Tune-Up
A lighting system tune-up should be performed in the following order:
1. Follow a strategic lighting maintenance plan of scheduled group relamping and
fixture cleaning.
2. Measure and ensure proper light levels.
3. Calibrate lighting controls.
(see Lighting chapter for lighting system specifications and details)
Periodically cleaning the existing fixtures and replacing burned-out lamps and ballasts
can considerably increase fixture light output. This simple and cost-effective tune-up
item can restore light levels in a building close to their initial design specifications.
After the fixtures have been cleaned and group relamping has taken place, the next
step is to measure existing light levels to ensure that proper illuminance levels are
provided for the tasks being performed in the space. As space use and furnishings
may change over time, it is important to match the lighting level to the current
occupant requirements. The Illuminating Engineering Society of North America
issues recommended illuminance levels depending on the job or activity performed.
Overlighted or underlighted areas should be corrected. Lighting uniformity should
also be assessed, as relocation of furniture and even walls may have altered lighting
distribution.
Once the proper light levels and uniformity have been achieved in the space,
examine the automatic lighting controls. Many buildings use a variety of automatic
controls for time-based, occupancy-based, and lighting level-based strategies. These
controls may have never been properly calibrated during installation or may have
been subsequently tampered with by occupants. Adjusting these controls and
associated sensors now will reduce occupant complaints, maintain safety, and ensure
maximum energy savings.
Many buildings utilize energy management systems, time clocks, and electronic
wallbox timers to control lighting automatically based on a predictable time schedule.
These systems need to be programmed correctly to ensure that lights are only
operating when the building is occupied, and that overrides are operational where
required. Exterior lighting schedules must also be changed throughout the year
according to the season.
The performance of occupancy or motion sensors depends on customizing the
sensitivity and time-delay settings to the requirements of each individual space. The
sensor's installed position should also be checked to ensure adequate coverage of the
occupied area. Also, keep all furnishings from obstructing the sensor's line of sight. A
sample commissioning protocol is available to guide your staff or contractor to
commission occupancy sensors properly (call the ENERGY STAR hotline at l-£
STAR YES for more information).
ENERGY STAR® BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Any indoor and outdoor photocells should also be checked at this time to ensure the
desired daylight dimming or daylight switching response. Set-points should be
adjusted so that the desired light levels are maintained. Photocells and dimming
ballasts are also used to save energy in non-daylight areas through lumen
maintenance control, a strategy to adjust system output to compensate for aging
lamps and dirt accumulation on luminaries. To maintain continued energy savings in
lumen maintenance control strategies, you will need to tune the set-point manually to
reduce the light level by 25 to 30 percent (the expected light level depreciation over
the maintenance cycle) each time fixtures are periodically cleaned and re-lamped.
This will allow the ballast to increase the system output over time to maintain the
illuminance set-point.
Savings
Although the savings associated with performing a lighting tune-up will vary
depending on the quality and performance of the current lighting system, they can
be significant. For example, cleaning alone may boost fixture light output from 10
percent in enclosed fixtures in clean environments to more than 60 percent in open
fixtures located in dirty areas. Simple calibration of occupancy sensors and photocells
can restore correct operation, reducing the energy used by the lighting system in
those areas by 50 percent or more.
Considerations
• Is a scheduled lighting maintenance policy in place?
• Are spaces provided with the proper light levels?
• Have all automatic controls been calibrated?
Supplemental Loads
The area of supplemental loads is also an opportunity for recommissioning In the
business world, office equipment constitutes the fastest growing portion of electrical
loads. However, much of this energy is wasted because equipment is left on when
not in use throughout the workday, at night, and on weekends. Electrical loads from
office equipment can be reduced by the use of ENERGY STAR labeled office
equipment and/or enabling power management features.
Supplemental Loads Tune-up
For existing office equipment models, check to see if they have power management
or other energy-saving features and that these features are enabled. Whether or not
they may not meet the ENERGY STAR specifications, these features will provide some
energy savings if activated.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Educate employees so that they understand what power management is and why it is
important. Here are some examples of issues that you should focus on:
•/ Sleeping equipment still draws some electricity; so turn it off when not in
use for long periods of time.
•/ Heat is a leading cause of equipment failure. When the power-management
feature is used, the computer generates less heat, so it may last longer and
have improved reliability.
•/ If screen savers are used in the office, be sure to choose those that will
display images for a predetermined period of time and then enter the sleep
mode. Graphical screen savers are primarily for entertainment and are not
energy-efficient features.
Savings
Energy-efficient equipment with the ENERGY STAR label cost the same as comparable
non- labeled equipment. However, the savings are greater for labeled equipment.
Products that meet ENERGY STAR specifications use about half as much electricity as
conventional equipment. ENERGY STAR labeled and non-labeled equipment produce
less heat when powered down or not in use, which results in reduced cooling loads,
and energy costs.
Considerations
• Is your organization purchasing office equipment with the ENERGY STAR label?
• Are energy saving features enabled on office equipment?
Building Envelope
The next step of a building tune-up is to reduce air infiltration through the building
envelope to enhance occupant comfort. Outside air can penetrate a building through
a variety of places, most commonly through the windows, doors, walls, and roof.
Drafts created by improperly sealed windows and doors can cause cold hands and
feet in the winter and discomfort in the summer.
In general, a building envelope should meet recommended infiltration standards. For
commercial buildings, the National Association of Architectural Metal
Manufacturers recommends infiltration rates per unit of exterior wall not to exceed
0.06 cubic feet per minute per square foot (cfm/sf) at a pressure difference of 0.3
in. of water (ASHRAE Fundamentals Handbook, 2001, 26.24).
A frequent result of infiltration problems, other than general occupant complaints, is
an increase in building heating, cooling, and/or electrical loads (when, for example,
occupants bring in space heaters or fans). In addition, the escape of conditioned air
forces the air handling system to work longer and harder to provide the required
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
space temperature. Thus, tuning up the envelope of a building can reduce HVAC
costs while greatly improving occupant comfort.
Tune-Up
The first step in reducing air infiltration is to tighten the existing building by locating
all air leaks in the windows, doors, walls, and roofs. Once you have detected the air
leaks, seal them with appropriate materials and techniques such as weather-stripping
on doors, sealing and caulking on windows, and proper insulation distribution in walls,
ceilings, and roofing.
If your building is equipped with revolving doors, you should encourage their use.
Revolving doors significantly reduce drafts and conditioned air loss. Automatic doors
should be calibrated to minimize air loss from the building envelope.
Savings
Reducing infiltration will result in a reduction in heating and cooling loads. Savings
will depend on many factors, including the existing condition of the building; the
building surface area-to-volume ratio; construction type; geographical location; and
the internal heating, cooling, and electrical loads. Typical savings for a large office
building range up to 5 percent of heating and cooling costs.
Considerations
• Are any areas particularly drafty?
• Are any areas routinely serviced?
• Do the windows and doors close and seal properly?
• Are the windows and door frames adequately caulked?
• Is weather stripping installed on windows and doorways?
• Is there any wet or deteriorating insulation that needs to be replaced?
Controls
The energy management system and controls within a building play a crucial role in
providing a comfortable building environment. Over time, temperature sensors or
thermostats often become out of tune. Wall thermostats are frequently adjusted by
occupants, throwing off controls and causing unintended energy consumption within
a building.
Poorly calibrated sensors cause increased heating and cooling loads and occupant
discomfort. As with envelope infiltration problems, occupants are likely to take
matters into their own hands if they are consistently experiencing heating or cooling
problems. By integrating mechanical and control recommissioning within each system,
you are more likely to improve occupant comfort.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Tune-Up
The first step in tuning up controls is to calibrate the indoor and outdoor building
sensors. Calibration of room thermostats, duct thermostats, humidistats, and
pressure and temperature sensors should be in accordance with the original design
specifications. Calibrating these controls may require specialized skills or equipment,
such as computer software. Thus, you should seriously consider the use of outside
expertise for this tune-up item.
In addition to calibrating the sensors, damper and valve controls should be inspected
to make sure they are functioning properly. Check pneumatically controlled dampers
for leaks in the compressed air hose lines. Also examine dampers to ensure they open
and close properly. Stiff dampers can cause improper modulation of the amount of
outside air being used in the supply air stream. In some cases, dampers may have
actually be wired in a single position or disconnected entirely, violating minimum
outside air requirements (for a more detailed explanation, see Supplemental Load
Reductions).
As part of tuning up controls, be sure to review building operating schedules. Often,
while control schedules remain constant, occupancy schedules change frequently over
the life of a building. This results in discomfort at the beginning and end of each day.
HVAC controls must be adjusted to heat and cool the building properly during
occupied hours. For example, operating schedules should be adjusted to reflect
Daylight Savings Time.
When the building is unoccupied, set the temperature back to save some heating or
cooling energy. Keep in mind that some minimum heating and cooling may be
required when the building is unoccupied. In cold climates, for example, heating may
be needed to keep water pipes from freezing.
In addition to the building's operation schedule, review the utility rate schedule.
Utilities typically charge on-peak and off-peak times within a rate, which can
dramatically affect the amount of your electric bills. If possible, equipment should
run during the less expensive off-peak hours. For certain buildings, precooling and/or
preheating strategies may be called for. (See also Supplemental Load Reductions,
Night Precooling, p. 14.)
Savings
The main savings associated with tuning controls result from reductions in charges
for heating and cooling energy (and possibly demand). Because savings are heavily
dependent on the existing condition of the controls, it is difficult to estimate the
actual savings that will result from a tune-up. Savings will depend on many factors
related to the building including heating and cooling system types; construction;
geographical location; and internal heating, cooling, and electrical loads. Typical
savings can range up to 30 percent of annual heating and cooling costs.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Considerations
• Are building sensors, such as thermostats and humidistats, calibrated and
operating properly?
• Are damper and valve controls functioning properly?
• Are there any leaks present in the pneumatic control systems?
Do equipment schedules reflect occupancy schedules and seasonal changes?
Can certain equipment be scheduled to operate during utility off-peak hours?
Can temperatures be set-back during unoccupied times?
Testing, Adjusting, And Balancing
Proper air and water distribution in an HVAC system is critical to create comfortable
conditions within a given space. Excessive room air temperature fluctuations,
excessive draft, and improper air distributions will lead to occupants' discomfort and
can increase energy consumption.
Testing, adjusting, and balancing (TAB) involves investigating the current state of a
system and making adjustments to bring the HVAC system back into balance and
close to its original design specifications. As we mentioned before, over time,
occupancy levels and space utilization may change dramatically. The TAB process
will help identify and make necessary adjustments to fit these changes, thereby
improving occupant comfort and saving energy costs.
A qualified TAB contractor should:
• Verify the current state of the system.
• Identify and correct any problems with the system.
• Ensure the system provides proper indoor air quality.
Testing, Adjusting, And Balancing
Testing, Adjusting, and Balancing (TAB) is the process of adjusting HVAC system components to
supply air and water flows to match load requirements.
TAB generally includes:
Testing. The process of evaluating the performance of the equipment in its current state and
making recommendations for improvements.
Adjusting. The process of regulating flow rates of air or water for the purpose of balancing the
system.
Balancing. The process of proportioning the air or water flows throughout a building to match
the loads.
Perform TAB analysis on a building whenever you think that the air or water
distribution system is not functioning as designed. Indicators that TAB is needed
include frequent complaints from occupants about hot or cold spots in a building, the
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
renovation of spaces for different uses and occupancy, and the frequent adjustment
of HVAC components to maintain comfort.
Tune-Up
A TAB analysis usually includes a complete review of a building's design
documentation. Typical HVAC system components and parameters to investigate may
include:
• Air system flow rates, including supply, return, exhaust, and outside airflow.
Flows include main ducts, branches, and supply diffusers that lead to specific
spaces in a building.
• Water system flow rates for chillers, condensers, boilers, and primary and/or
secondary heating and cooling coils.
• Temperatures of heating and cooling delivery systems (air side and water side).
• Positions and functioning of flow control devices for air and water delivery
systems.
• Control settings and operation.
• Fan and pump speeds and pressures.
The TAB contractor will provide a test and balance report with a complete record of
the design specifications, preliminary measurements, and final test data. All
discrepancies between the design and test data should be outlined along with an
analysis. The report should also include recommended and completed adjustments.
Savings
The savings associated with TAB come from the reductions in the energy used by
the heating and cooling system. Because savings are heavily dependent on the
building's condition, it is difficult to estimate the actual savings that will result from
TAB. Savings will differ depending on many factors related to the building including
heating and cooling system types, construction, geographical location, and internal
heating, cooling, and electrical loads. Savings can range up to 10 percent of heating
and cooling costs.
Considerations
• Are occupants frequently complaining about the temperature, humidity, etc., in
the building?
• Have HVAC system components been replaced or modified?
• Has any building space been renovated?
• Can the HVAC system satisfy comfort requirements during very hot or very
cold days?
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
renovation of spaces for different uses and occupancy, and the frequent adjustment
of HVAC components to maintain comfort.
Tune-Up
A TAB analysis usually includes a complete review of a building's design
documentation. Typical HVAC system components and parameters to investigate may
include:
• Air system flow rates, including supply, return, exhaust, and outside airflow.
Flows include main ducts, branches, and supply diffusers that lead to specific
spaces in a building.
• Water system flow rates for chillers, condensers, boilers, and primary and/or
secondary heating and cooling coils.
• Temperatures of heating and cooling delivery systems (air side and water side).
• Positions and functioning of flow control devices for air and water delivery
systems.
• Control settings and operation.
• Fan and pump speeds and pressures.
The TAB contractor will provide a test and balance report with a complete record of
the design specifications, preliminary measurements, and final test data. All
discrepancies between the design and test data should be outlined along with an
analysis. The report should also include recommended and completed adjustments.
Savings
The savings associated with TAB come from the reductions in the energy used by
the heating and cooling system. Because savings are heavily dependent on the
building's condition, it is difficult to estimate the actual savings that will result from
TAB. Savings will differ depending on many factors related to the building including
heating and cooling system types, construction, geographical location, and internal
heating, cooling, and electrical loads. Savings can range up to 10 percent of heating
and cooling costs.
Considerations
• Are occupants frequently complaining about the temperature, humidity, etc., in
the building?
• Have HVAC system components been replaced or modified?
• Has any building space been renovated?
• Can the HVAC system satisfy comfort requirements during very hot or very
cold days?
ENERGY STAR? BatldingManaal
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Heat Exchange Equipment
The next steps in building tune-up focus on the heat exchange equipment that cools
and heats the air that ultimately reaches building spaces. This equipment usually
consists of heating and cooling coils installed in air handlers, fan coil terminal units,
or baseboard radiators. These units are typically supplied with chilled water and hot
water from a central plant. The heating and cooling coils can also be part of a
packaged unit such as a rooftop air conditioning unit or central station air handling
unit.
As with other tune-up items, tuning up your heat exchange equipment has the
potential not only to save energy costs but also to increase your building occupants'
comfort.
Although many of the tune-up recommendations presented below should be
performed as normally scheduled maintenance, they are included in Supplemental
Load Reductions because of the potential for resultant energy cost savings.
The controls and flow issues for heat exchange equipment were addressed in the
previous controls and TAB sections. The remaining action is to ensure that all
surfaces and filters are clean. Dirty surfaces reduce heat transfer, increase pressure
loss, and increase energy use.
Tune-Up
Clean the air side of heating and cooling coils, whether in an air handler or in a
rooftop unit, to reduce deposit buildup. Methods for cleaning may include
compressed air, dust rags/brushes, and power washes. Check baseboard heating
systems for dust build up and clean if necessary.
The water side of heating and cooling systems is generally inaccessible for
mechanical cleaning. Chemical treatments are often the best solution to clean these
surfaces. Ongoing water treatment and filtering of the water side is recommended to
reduce dirt, biological, and mineral scale buildup. Filters for both air side and water
side systems should be cleaned and replaced as necessary.
Avoid covering or blocking terminal fan coil units and baseboards with books, boxes,
or file cabinets. Besides creating a fire hazard (in the case of radiators), blocking the
units prevents proper air circulation and renders heating and cooling inefficient.
Savings
The savings you will see from a tune-up of your heat exchange equipment are highly
dependent upon the existing conditions of the equipment. In general, the more you
can improve the heat transfer of surfaces, the more you will save. Additionally,
cleaning coils and filters may reduce the pressure drop across the coil and reduce fan
or pump energy consumption.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Savings will differ depending on many factors related to the building, including
heating and cooling system types; construction; geographical location; and internal
heating, cooling, and electrical loads. Typical heating and cooling system cost savings
can range up to 10 percent.
Considerations
• Are the heating and cooling surfaces clean?
• Are air and water filters changed regularly?
• Are heating or cooling terminal units and baseboards blocked by furniture or
debris?
Heating and Cooling System
Following the framework of the integrated approach, the final step is to tune up the
heating and cooling system. The heating and cooling system, generally a central plant,
supplies all of the heating and cooling to make building spaces comfortable. Some
buildings may have distributed heating and cooling units or a combination of both
instead of a designated central plant.
The information gathered during the previous sections may become useful in
determining any potential operational changes to the central plant. Additionally,
recommissioning conducted on the HVAC and lighting systems should reduce the
amount of energy the central plant consumes.
Some of the following tune-up items should be performed as part of normal
scheduled maintenance. They are included here because of their potential for
resultant energy cost savings. Specially trained and qualified personnel should
perform all of these tune-up procedures.
Chiller Tune-Up
Chillers are similar to air conditioners found in any home, except that chillers supply
cool water and home air conditioners supply cool air. The cool water from a chiller is
eventually pumped through a heat exchanger (i.e., cooling coil), which cools the
building's air. (For more information on specific types of chiller equipment, see
Heating And Cooling System Upgrades.)
Chilled Water And Condenser Water Temperature Reset — A chiller's operating
efficiency can be increased by raising the chilled water temperature and/or by
decreasing the temperature of the condenser water. Chilled water reset is the practice
of modifying the chilled water temperature and/or condenser water temperature in
order to reduce chiller energy consumption.
If you decide to undertake chilled water reset, be careful that all of the
considerations are taken into account. Although raising the chilled water will reduce
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
chiller energy consumption, it may increase supply fan energy consumption.
Reducing the condenser water temperature may increase the cooling tower fan
energy consumption as well. Be sure to consult experts who can analyze all the
effects of chilled water reset. If in doubt, using the intended design temperatures is
your safest bet (E SOURCE, Space Cooling Atlas^).
Chiller Tube Cleaning And Water Treatment — Optimum heat transfer relies on
clean surfaces on both the refrigerant and water side of the chiller tubes. Typically,
the water side of the condenser needs the most attention because evaporative
cooling towers have an open loop and new water is introduced continuously. Thus,
water treatment is needed to keep surfaces clean and reduce biological films and
mineral scale. Similar treatments may be needed for the chilled water loop.
As part of the tune-up, clean the condenser and evaporator tubes to remove any
scale or buildup of biological film. To do this, the surfaces usually have to be
physically scrubbed and sometimes treated with chemicals.
Reciprocating Compressor Unloading - Reciprocating compressors are typically
used for smaller chillers. Many of these compressors utilize multiple stages (that is,
more than one piston for the compressor) of cooling to allow for more efficient
part-load performance and reduced cycling of the compressor motor.
At part-load performance, one or more of the stages are unloaded. If the controls
of the system fail to unload the cooling stage, then the system may cycle
unnecessarily during low cooling loads. Because starting and stopping is inherently
inefficient, cycling decreases the efficiency of the cooling system. Additionally,
increased cycling can lead to compressor and/or electrical failures (E SOURCE, Space
Cooling Atlas).
Consult manufacturer's maintenance information to check for proper cooling stage
unloading. Unloading may be controlled by a pressure sensor that is set for a specific
evaporator pressure. This sensor, and the controls dependent upon it, can fall out of
calibration or fail.
Boiler Tune-Up
In many buildings, the boiler is the heart of the heating system. Steam or hot-water
boilers are present in approximately 42 percent of heated commercial floor space
(CBECS, 1995).
When considering a tune-up for a boiler, always make sure that you and the
maintenance staff or contractor know and fully understand all safety precautions.
Also, always follow manufacturer's information on maintenance and local safety or
environmental codes. ENERGY STAR recommends you consider obtaining specialized
expertise for boiler tune-up items.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Boiler System Steam Traps — Steam heating systems use mechanical devices called
steam traps to remove condensate and air from the system. Steam traps frequently
become stuck in the open or closed position. When a trap is stuck open, steam can
escape through the condensate return lines to the atmosphere, and the resulting
energy loss can be significant. Check steam traps for leaks frequently and make
repairs as needed. Because special tools and experience are required, you should
consider the use of outside expertise.
Combustion Air — More air is typically supplied for combustion than is needed.
Excess air helps prevent incomplete combustion, which contributes to associated
hazards such as smoke and carbon monoxide buildup. If too much air is introduced,
some of the fuel is wasted heating this excess air. A tune-up of combustion air
consists of adjusting combustion air intake until measured oxygen levels in the flue
gas reach a safe minimum. (This tune-up measure does not apply to electric boilers.)
Boiler Tube Cleaning And Water Treatment — Optimum heat transfer relies on
clean surfaces on both the boiler's combustion and water or steam side. Surfaces that
are dirtied with fouling (see sidebar) will ultimately increase the energy consumption
of the heating system. A tune-up consists of removing fouling buildup from both the
fire side and water side of the boiler tubes by physically scrubbing the surfaces and
sometimes by applying a chemical treatment.
Additionally, treating the heating water may be a good option to reduce the further
deterioration of your boiler tubes.
Fouling
Fouling is the buildup of a film thatD
reduces heat transfer. Soot, ash, or other particles can build up on the fire side surfaces of aD
boiler. Mineral deposits or other materials can build up on the water or steam side surfaces.D
Heating and Cooling Equipment Savings
The savings associated with central plant re commissioning are derived from reducing
the energy consumption of the heating and cooling system. Savings are highly
dependent on the existing condition of the equipment. Other related factors include
the heating and cooling system types; construction type; geographical location; and
internal heating, cooling, and electrical loads.
Savings for most of the central plant recommissioning are listed below. When all
recommissioning are taken together, heating and cooling cost savings can reach
upwards of 15 percent.
Chilled Water and Condenser Water Temperature Reset — The savings
associated with a water temperature reset will vary, depending on equipment type and
system interactions. Because temperature reset does not require the purchase of new
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
equipment, it can often be inexpensive. The complexity of reset, however, could
result in incorrect implementation, instead increasing your energy use. Therefore, a
professional consultant should be contacted who will be able to estimate the savings
potential.
Chiller Tube Cleaning and Water Treatment — The savings achieved by cleaning
tube surfaces are highly dependent on the current state of the tubes. Savings can be
estimated by looking at what the temperature change through the evaporator or
condenser should be and comparing it to the actual temperature change. Contact an
HVAC consultant or a chiller specialist for a savings estimate.
Boiler System Steam Traps — The savings achieved by fixing steam trap leaks is
highly dependent on the size of the leak and the pressure of the system. Table 1
compares orifice size with the estimated steam leaked per month and the resulting
costs.
Table 1: Steam Trap Leaks
Si^e of
Orifice
(in.)
1/2
7/16
Steam Leak
per month
(Ib.)
835,000
637,000
Total Cost
per month
(f)
2,480
1,892
3/8 470,000 1,396
Based on: 100 psi, boiler efficiency of 80 percent, energy cost of $2 per million Btu.
Source: Wayne C. Turner. Hner
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Table 2: Boiler Combustion Fouling
Soot layer on Increase in fuel
heating surface consumption
(in.) (%)
1/32
1/16
1/8
2.5
4.4
8.5
Table 3: Boiler Water Side Fouling
Thickness of scale Increase in fuel
(soft carbonate scale) consumption
(in.) ' (%)
1/32
1/16
1/11
7.0
12.5
15.0
Considerations
Chillers
• Have you consulted an expert to determine the implications of chilled water
temperature reset on supply fan energy consumption?
• How dirty are your evaporator and condenser tubes?
• Are reciprocating compressor cylinders unloading at part load?
Boilers
• Have the steam traps been inspected for leaks?
• Has combustion air been checked in the last year?
• Have the combustion and water or steam side heat transfer surfaces been
cleaned recently?
Summary
To recap, your strategy for recommissioning should follow the framework an
integrated staged approach. Keep in mind that the overriding concern in performing
recommissioning is to ensure that the building operates as intended and meets
current operational needs.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Building tune-up strategies should be implemented in the following order:
• Lighting + Supplemental Loads
• Building Envelope
• Controls
• Testing, Adjusting, And Balancing
• Heat Exchange Equipment
• Heating And Cooling System
Next Steps
• Make certain that facility staff receive training so that they are familiar with
tuning and maintaining building systems.
• Use the information learned in recommissiomng to identify and implement other
energy performance strategies and savings opportunities in throughout the entire
building and its systems.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
LlGHTINGD
Overview
Lighting consumes 25 — 30% of energy in commercial buildings, and is a primary
source of heat gain and waste heat. Excess heat and energy can be reduced by
implementing an energy-efficient lighting system. Upgraded lighting systems can also
improve lighting quality to increase occupant comfort and productivity.
Figure 1 illustrates how heat from the lighting system effects cooling loads in the
building. Comprehensive lighting upgrades create opportunities to improve the
efficiency of electrical distribution and HVAC systems by reducing these loads. The
additional energy savings from lighting upgrades are discussed in subsequent stages
of the upgrade process.
Benefits of a comprehensive lighting upgrade:
• Highly profitable energy savings and low-risk investment.
• Maximize energy savings opportunities for subsequent building systems upgrades.
•D Successful lighting upgrades can increase management and occupant acceptance of other
energy-efficiency projects.
This chapter will identify opportunities and strategies to improve the efficiency of lighting systems.
"Best Ways to Save" and "Take Action" are checklists to perform a quality lighting upgrade and
maximize energy savings.
Figure 1 : Heat Flow
LOADS
Heat Flow In Buildings: Building Systems Interactions
Figure 2 shows the interaction of heating, cooling, and electrical loads with the HVAC
equipment. Arrows indicate heat flow pathways. Reducing heating, cooling, and
electrical loads reduces the demand on HVAC equipment, thus saving energy.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Best Ways to Save
• Design light quantity and quality for the task and occupants' needs.
• Maximize lamp and ballast efficiency.
• Maximize system efficiency, not just the components.
• Use automatic controls to turn lights off or dim lights in daylit spaces.
• Establish maintenance schedule for group relamping and fixture cleaning.
• Use ENERGY STAR Labeled exit signs.
• Establish responsible disposal practices.
Take Action!
• Develop an implementation plan and budget for lighting upgrade projects.
• Communicate project objectives and process to occupants.
• Perform trial installations to assess light levels, occupants acceptance, and energy
use.
The Importance of Lighting
Lighting and The Environment
Lighting consumes a tremendous amount of energy and financial resources. Lighting
accounts for approximately 17 percent of all electricity sold in the United States (see
Figure 2, E SOURCE 1994, Lighting Technology Atlas, Ch. 4).
ENERGY STAR estimates that if efficient lighting were used in all locations where it has
been shown to be profitable throughout the country, the nation's demand for
electricity would be cut by more than 10 percent. This could save nearly $17 billion
in ratepayer bills and result in the following annual pollution reductions:
• 202 million metric tons of carbon dioxide, the primary cause of global climate
change. This would be the equivalent of taking 15 million cars off the road.
• More than 1.3 million metric tons of sulfur dioxide, which contributes to acid
rain.
• 600,000 metric tons of nitrogen oxides, which contribute to smog.
Table 1 illustrates potential lighting energy savings.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figure 2: Lieiiini Share Of All TLled^ic l::,!terin Use
o o o J &>
Other Industrial
30%
Other Residential
27%
Other Commercial
19%
Miscellaneous
7%
Lighting
17%
Table 1: Potential Lighting Energy Savings
Lamps and Ballasts 20 to 40 %
New Fixtures 30 to 50 %
Task/ Ambient Lighting 40 to 60 %
Outside Lighting 30 to 50 %
Green Ugbts l^h/1^^ v^'/ii^s save ft percent itf d ^i/
Source: EPA Green Lights Prop-ram.
i mergy
Lighting And Your Business
Lighting is also a significant expense in operating buildings. Lighting is the largest cost
component of a commercial building's electricity bill (see Figure 3) and a significant
portion of its total energy bill.
Lighting and Your Building
Reduce Heat Gain
In addition to visible light, all lighting systems produce heat. Lighting is typically the
largest source of waste heat, often called "heat gain," inside commercial buildings.
Improving lighting efficiency reduces heat gain, which affects your buildings in two
ways.
Waste heat is a useful supplement when the building requires heat, it must be
removed by the HVAC system when the building needs to be cooled. The impact of
this tradeoff—the penalty for increased heating costs versus the bonus for reduced
cooling costs—depends on your building type, its geographic location, and its HVAC
system. Although heating costs may rise, they will rarely exceed the resultant cooling
savings, even in buildings in northern climates that use electric resistance heat.
ENERGY ST^AE? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
By reducing internal heat gain, efficient lighting also reduces your building's cooling
requirements. Consequently, your existing cooling system may be able to serve future
Figure 3: Lighting Share Of Office Building Electricity Use
Cooling
Space Heating
29%
Other
10%
Ventilation
11%
Water Heating
4%
Office
Eguipment
13%
ihting
2%
Refrigeration
3%
Cooking
1%
added loads, or may be appropriate for "rightsizing". Given the large impact lighting
upgrades can have on your HVAC system requirements and the high cost of cooling
equipment, you should always quantify HVAC and lighting interactions. There are
simplified methods available for calculating the impacts of lighting upgrades on
heating and cooling systems. (See EPRI Lighting Bulletin, no. 6, April 1994.)
Improve Power Quality
Lighting also affects the power quality of your building's electrical distribution
system. Poor power quality is a concern because it wastes energy, reduces electrical
capacity, and can harm equipment and the electrical distribution system itself.
Upgrading to lighting equipment with clean power quality (high power factor and low
harmonic distortion) can improve the power quality in your building's electrical
system. Furthermore, upgrading with higher efficiency and higher power factor
lighting equipment can also free up valuable electrical capacity. This benefit alone
may justify the cost of a lighting upgrade.
ENERGY STAR® EuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Lighting and People
A lighting upgrade is an investment not only in reducing electricity consumption but
also in improving the performance of the building in supporting its occupants. A
building's lighting directly affects the comfort, mood, productivity, health, and safety
of its occupants. Moreover, as the most visible building system, it also directly affects
the aesthetics and image of the building and your business. Successful lighting
upgrades take into account the impact of energy performance choices on the
building occupants and seek to marry efficiency with improved lighting quality and
architectural aesthetics wherever possible.
Productivity
The relationship of lighting to task performance and visibility is well understood.
Improved lighting enhances visual comfort, reduces eye fatigue, and improves
performance on visual tasks. Well-designed lighting is likely to improve performance,
increase productivity, and reduce absenteeism. Because costs associated with your
employees greatly outweigh the other building costs (see Figure 4), any lighting
changes that improve your occupants' workspaces are worth investigating.
Figure 4: Annual Operating Costs Per Square Foot, Typical Office Space
Services & Furniture &
Supplies 5% Equipment 3%
Lighting 1%
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Safety
Lighting also contributes to the safety of occupants and the security of buildings.
Emergency lighting must be available during power outages, and minimum levels of
light must be available at night when most lighting is turned off. In addition, safety
codes require exit signs to highlight escape routes during fires or other emergencies.
Outside lighting and indoor night lighting deters crime by exposing intruders'
movements and permitting occupants to move safely through the building or to cars.
Although such effects are difficult to quantify, comfort, mood, productivity, health,
safety, and other impacts on people should be considered as part of every lighting
upgrade.
Maximizing Efficiency and Quality
A comprehensive lighting upgrade achieves your qualitative lighting objectives while
maximizing efficiency and profitability. With rewards beyond the sum of its parts,
this process integrates equipment replacement with deliberate design, operation,
maintenance, and disposal practices. This whole-system approach takes what is
frequently regarded as a complex system of individual decisions and unites them into
a strategic approach that ensures that each opportunity is addressed and balanced
with other objectives (see Figure 5).
Figure 5: Comprehensive Lighting Upgrade Strateg
Avoid implementing only the easiest and quickest payback opportunities. While this
may seem appealing, you will forgo quality-enhancing and savings opportunities that
result from comprehensive upgrades. A simplified upgrade may yield faster payback,
but you will sacrifice long term energy savings over the life of the system.
Table 2 illustrates the economic impacts of pursuing incrementally more aggressive
upgrades while maintaining pro Stability and lighting quality and quantity. (See E
SOURCE, Lighting Technology Atlas, Chapter 3, for more detail.)
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Lighting Design
Successful lighting design begins with an assessment of several design issues to meet
the occupants' lighting needs, which depend on the tasks performed in the
workspace. The lighting system should be designed to provide the quantity and
quality of light responsive to those requirements. Chapter 10, "Quality of the Visual
Environment," of the IESNA Lighting Handbook 9th edition, identifies several issues
such as color, daylight availability, glare and, light distribution that should be
considered. Retrofits that skip this assessment may perpetuate designs that have
become inadequate because of workspace rearrangements or changing tasks (for
example, paper-based to computer-based tasks).
Table 2: Performance Comparison of Fluorescent Retrofit Options
Base ease: "Energy T8 T8 lampst Same as
Tl 2 L^amps saving' lamps, electronic ballasts, Case 4 +
n>l magnetic T12 electronic reflector lens, occupancy
ballasts lamps ballasts + 50% delamping sensors
Case 1 Case 2 Case 3 Case 4- Case 5
Avg
maintained
footcandles
(fc) 28 25 30 27 27
Input watts
per fixture 184 156.4 120 60 60
Total kW 2.208 1.877 1.440 0.720 0.720
Annual energy
use (kWh) 8;832 7,507 5;760 2,880 1,800
.'; • -;,::;/•
Case 5 +
maintenance
Case 6
27
50
0.600
1,500
Costs
Energy
savings (%) N/A 15% 35% 67% 80%
Annual
operating
cost for
energy ($) 883.70 750.74 576.00 288.00 212.40
Upgrade
cost ($) N/A 312 1,440 1;620 1;970
83%
177.00
1,970
****
Energy
savings (%) N/A 15% 35% 67% 80%
Operating
cost
savings (%) N/A 15% 35% 67% 76%
Simple payback
(years) N/A 2.4 4.7 2.7 2.9
Internal Rate
of Return
(1 0 -year) N /A 41% 17% 35% 32%
Source: Adapted from E SOURCE., ~Ljigbis\\ \ . ?bno o^y Atlas, Table 3.1.
83%o
80%
2.8
34%
It is important to recognize that people do not see absolute levels of illuminance, the
amount of light shining on a surface. They see differences in luminance or
brightness—the amount of light reflected back from the surface. The fundamental
relationship between lighting and occupant tasks makes it essential that the lighting,
task, and surrounding area be evaluated together. Although lighting retrofits are
ENERGY ST^AE? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
generally limited to the lighting equipment, good design should evaluate and modify
work environments where appropriate. For example, a lighting redesign may reorient
computer monitors away from windows or increase the contrast between tasks and
their backgrounds.
Room dimensions and finishes also affect the required light output and thus the
energy consumption of all interior lighting systems. As much as one-third of the
energy use of a lighting system depends upon the surrounding interior features, such
as the ceiling height, windows, and color and reflectivity of room surfaces and
furnishings. Where possible, the lighting designer should work with both the architect
and interior designer to ensure that features that significantly enhance lighting levels,
such as large windows and light-colored finishes, are utilized wherever possible. This
helps minimize the required light output and therefore the energy consumption of
the lighting system.
The same principals and guidance that apply to interior lighting are applicable to
exterior lighting as well. Outdoor lighting that is designed and implemented properly
should be cost effective, control light by directing it where needed; reduce glare and
distribute illumination evenly; and reduce light trespass.
The Right Quantity of Light
A common misperception contributing to the proliferation of ineffective and
inefficient lighting is that more light equals higher quality light. Lighting-level
requirements have evolved with the changes in our workplaces and our knowledge
of visual science. The Illuminating Engineering Society of North America (IESNA)
has developed consensus-based guidelines to select appropriate illuminance levels for
hundreds of indoor and outdoor activities. These recommendations, some of which
are listed in Table 3, are starting points, suggesting a range of values based on design
issues, locations, and tasks. Listed below are several design issues outlined by
IESNA:
• Appearance of Space and Luminaires
• Color Appearance (and Color Contrast)
• Daylighting Integration and Control
• Direct Glare
• Flicker (and Strobe)
• Light Distribution on Surfaces
• Light Distribution on Task Plane (Uniformity)
• Luminances of Room Surfaces
• Modeling of Faces and Objects
• Point(s) of Interest
• Reflected Glare
• Shadows
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
• Source/Task/Eye Geometry
• Sparkle/Desirable Reflected Highlights
• Surface Characteristics
• System Control and Flexibility
Table 3: Recommended Light Levels (fbotcandles)D
Average Reading
and Writing 50 fc
Offices with
Computer Screens
Task Lighting 25 fc
Ambient Lighting 25 fc
Hallways 10 fc
Stockroom Storage 30 fc
Loading and Unloading 10 fc
High-Volume Retail 100 fc
Low-Volume Retail 30 fc
Roadway Lighting .3 — 1.6 fc
Parking Lots .8 - 3.6 fc
Building Entrance 5 fc
Source: IE5'_\_ ' 7 ::-:-:''MV Handbook.
It is important to note that these are average maintained target levels for the task
and should not necessarily be applied uniformly as the ambient light level for the
entire space. Lighting levels should be customized through the use of supplemental
task lighting in areas requiring higher localized levels. Target lighting levels should be
the sum of the ambient and task lighting levels. This task and ambient lighting design
approach creates flexibility to accommodate individual tasks or worker requirements,
creates visual interest, and can save considerable energy in comparison to a uniform
ambient level approach.
The Right Quality of Light
Of equal importance to the quantity of light is the quality of light. The quality of
light is dependent on both the properties of the light and how that light is delivered
to the space. The fundamental quality issues include all of the IESNA "design issues"
listed above with special consideration given to:
• Glare
• Uniformity of luminance
• Color temperature and color rendition
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
The eye does not see absolute levels of illuminance; the amount of light shining on a
surface. It sees differences in luminance, the amount of light reflected back from the
surface. Eyestrain and fatigue are caused when the eye is forced to adapt continually
to different luminances. Therefore, it is important not only to provide the right level
of light but also to ensure that light is evenly distributed across the task area.
Balancing light levels also ensures that task lighting levels will be adequate throughout
the space. Uniformity on vertical surfaces should also be maintained to avoid a
gloomy, cavelike atmosphere.
IESNA recommends as good design practice an average luminance ratio of no
more than 3 to 1 for close objects and 10 to 1 for distant objects and outdoor
applications (IESNA Lighting Handbook, Sect. 11—Office Lighting). In other words,
the difference in light level between the task area and the background should be less
than a factor of three. While some designers use illuminance variation as an
organizing theme, such as defining hallways leading to open offices, or as a
highlighting strategy, such as in retail and merchandising locations, large footcandle
variations within a workspace should be avoided.
Glare is the most important quality factor. Glare results when luminance levels or the
differences in luminance levels are too high, and objects appear too bright. Because
glare creates discomfort, loss of visual performance, and impaired visibility, it should
be minimized wherever possible.
The two types of glare you will encounter are direct glare and reflected glare. Direct
glare occurs when light from a bright object enters the eye directly. It can be
controlled through the use of luminaire lenses, louvers, and window blinds, all of
which block the direct viewing of sources.
Reflected glare is produced when reflected light creates a shining or veiling
reflection, which reduces or washes out task contrast. This commonly occurs on
shiny, light-colored surfaces and computer screens. Although veiling reflections are
more difficult to control, they can be minimized by moving the light source,
reorienting the task, and installing reflectors, lenses, or louvers on luminaires. Good
general practices to minimize glare include the use of lower ambient light levels, task
lighting, indirect lighting, and luminaires with a high visual comfort probability
(VCP) rating. The VCP index provides an indication of the percentage of people in a
given space that would find the glare from a fixture to be acceptable. You should
ensure a minimum VCP rating of 70 for commercial interiors and 80 for computer
areas.
The color mix of a light source is described by the terms color rendering and color
temperature. The ability of a light source to accurately reveal the true colors of
objects is measured by its color rendering index (CRT), which ranges between 0 and
100 (see Table 4). Lamps with a higher CRI make people and objects appear more
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
natural and bright. Because high CRI lamps improve visual clarity and aesthetics, use
the highest CRI lamps economically practical.
The color temperature of lamps, measured in degrees Kelvin (° K), refers
to the relative warmth or coolness of their light color. The higher the color
temperature, the cooler the light source. Lamps with a color temperature of 3500° K
are generally considered neutral (see Figure 6).
Table 4: Typical CRI Values For Selected Light Sources
Source Typical CRI Value
Incandescent/Halogen
Fluorescent
Cool White T12
Warm White T12
High Lumen T12
T8
T10
Compact
Mercury Vapor (clear/coated)
Metal Halide (clear/coated)
High-Pressure Sodium
Standard
Deluxe
White HPS
Low-Pressure Sodium
98+
62
53
73-85
75-98
80-85
80-85
15/50
65/70
22
65
85
0
While color temperature is largely an architectural choice, it also relates to design
lighting levels. While warmer sources, with a temperature below 3500° K, are
generally preferred in lower illuminance environments, cooler sources, with a
temperature above 3500° K, are preferred in higher illuminance environments.
Maximize Source Efficiency
Too often, lighting retrofits start and finish with the objective of pairing lamps with
ballasts to turn electricity into visible light most efficiently. While the majority of
energy savings potential often resides here, pursuit of high efficiency alone may lead
to compromises in light quality and controllability and higher system installation and
maintenance costs. Lamp and ballast specification should seek to optimize efficiency
while maintaining a balance with these other considerations.
ENERGY
uildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figure 6: Color Temperatures of Various LJgbt Sources
Lamp Type
Incandescent
Halogen
Compact
Fluorescent
Full-SJze
Fluorescent
Mercury Vapor
Metal Halide
High-Pressure
Sodium
Low-Pressure
Sodium
Color Temperature (° K)
• 2800
"^ ~~^ (lower when dimmed)
• 3000 "*"
2700 3000
• •
3000
•
"warm-white"
•
2100 2700 31°°
• •
standard white HPS
• 1740
1500 2000 2500 3000
Table 5: Lamp Characteristics
Standard Full-Si^
i n, ..•'•'. :.?.:< !'it Fluorescent
Wattages 3-1,500 4-215
System
Efficacy (Im/W) 4-24 49-89
Average Rated
Life (hrs) 750-2,000 7,500-24,000
Color Rendering
Index ' 98+ 49-85
Life Cycle Cost High Low
Source Optics Point Diffuse
Start-to-Full
Brightness Immediate 0—5 Seconds
Restrike Time Immediate Immediate
Lumen Good/ Fair/
Maintenance Excellent Excellent
3500 4100 5000
• • •
3500 4100 5000
• • •
"white" "cool-white"
• 4400 (coated) •
• •
4100 5000
3500 4000 4500 5000 5500
Memory Metal
Vapor Halide
40-1,250 32-2,000
19^3 38-86
24,000+ 6,000-20,000
15-50 65-70
Moderate Moderate
Point Point
3-9 Minutes 3-5 Minutes
10-20 4-20
Minutes Minutes
Poor/Fair Good
6500
•
6500
•
5700 (clear)
6000 6500
High -Pressure
... odivm
35-1,000
22-115
16;000-24;000
22-85
Low
Point
3—4 Minutes
1 Minute
Good/
Excellent
While a wide range of light sources are available, the predominant types used in
commercial and industrial spaces are fluorescent and high-intensity discharge (HID).
Historically, fluorescent lighting has been used for high-quality, general-purpose
indoor diffuse lighting. HID has been used for industrial and outside lighting.
However, technical advances and a flood of new products have increased the use of
HID in interiors.
Although fluorescent sources are still limited by their inability to function in very hot
or cold environments or as spotlights, advances in physical size, thermal
performance, and light quality are allowing wider application in industrial,
manufacturing, and residential environments. Likewise, in the past, HIDs have
ENERGY STAR® EuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
typically been limited by their high light output and their inability to render color
accurately or to be switched on and off frequently or dimmed. Today, however, HID
lamps are used indoors in some applications where light quality is critical and where
dimming and lower light outputs are necessary. While practical limitations still exist,
now, more than ever, specifiers need to research lamp capabilities and understand the
tradeoffs between efficiency and performance. For example, linear T5 lamps, which
have recently been introduced, are becoming popular in direct/indirect pendent
mounted systems, cove lighting and retail display lighting. But should not be used in
retrofit applications because of the following limitations.
• Available only in metric lengths
• Lamp holder design is different that T8 and T12
• Higher tube luminance, which will cause glare problems in existing lighting
equipment.
Ballast selection is integral to lamp performance. All fluorescent and HID lamps
require a ballast to provide the necessary starting voltage and regulate lamp current
and power quality. Ballasts determine the lamp's light output, life, and control
capabilities. Similar to advances in lamp technology, electronics advances have greatly
expanded ballast capabilities and selection.
The three types of fluorescent ballasts are magnetic, electronic, and hybrid ballasts.
Magnetic ballasts, also known as electromagnetic ballasts, have improved from the
standard-efficiency, core-coil ballasts last made in 1989 to higher efficiency models.
Electronic ballasts have been developed for almost all fluorescent lighting
applications to replace their conventional magnetic counterparts directly. Electronic
ballasts operate fluorescent lamps at a higher frequency, which improves system
efficiency by about 30 percent when used in conjunction with T8 lamps to replace
T12 lamps and standard magnetic ballasts. Electronic ballasts also offer these
advantages:
• Less audible noise and virtually no lamp flicker.
• Dimming capability (with specific ballast models).
• Ability to power up to four lamps, increasing energy efficiency by an additional 8
percent, while reducing first cost and maintenance costs.
Hybrid ballasts, which combine features of magnetic and electronic ballasts, are also
available. Although these ballasts offer the same efficiency benefits as electronic
ballasts, they cannot power more than three lamps.
Instant-start circuitry offers an additional 5 percent efficiency compared with rapid-
start electronic ballasts. However, if lamps are frequently switched on and off,
additional lamp and maintenance costs may exceed energy savings.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Programmed-start ballasts offer increased lamp life compared to instant or rapid
start ballasts. Programmed-start ballasts are designed to soft start the lamp, which
decreases lamp cathode damage. These ballasts are an excellent choice when
luminaires are switched on and off frequently, such as in spaces controlled by an
occupancy sensor.
Selecting ballasts for HID lamps involves matching a ballast type to the electrical
distribution system in your building to control the lamp light output when line voltage
varies. The level of this control is then balanced against ballast losses, power factor,
lamp life, and cost. Electronic ballasts are also available for most types of HID
lamps, these ballasts are becoming more popular because of their smaller size,
weight, decreased lamp color shifting, and increased compatibility with lighting
controls Nominal efficiency improvements of only 5 to 7 percent make retrofits
difficult to justify on energy savings alone. Linear reactor circuit ballasts have been
developed which, when used with matched, pulse-start, metal halide lamps, can cut
ballast losses in half and offer a 20-percent improvement in efficiency.
Maximize Lwninaire Efficiency
A luminaire, or light fixture, is a system of components designed to direct light
efficiently while providing a high level of visual comfort (see Figure 7).
Getting a large percentage of light to exit the fixture while controlling its distribution
usually requires a compromise. Generally, the most efficient fixtures have the poorest
visual comfort. Conversely, fixtures with excellent glare control are the least efficient.
Figure 7: Luminaire Components
Housmg/Reflector
Lamps
\ \ \ \ \ \
Lumens from Fixture
When installing new fixtures, the lighting designer will determine the best compromise
between fixture efficiency and visual performance and specify optimized fixtures that
fit into the architectural design objectives. When retrofitting fixtures, however, lamps
are repositioned, and reflectors and shielding materials are added to balance these
objectives.
Reflectors are inserts designed to reduce the internal light loss in fixtures by
using highly reflective surfaces to redirect light out of the fixture. They can be used
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
in new fixtures or installed in existing fixtures as part of an energy savings retrofit
strategy. In retrofits, reflectors improve fixture efficiency by improving the internal
surface reflectance by up to 17 percent in new fixtures and more if fixture surfaces
are old or deteriorating (see Ughting Upgrade Technologies, p. 10, EPA 430-B-95-008).
By modifying the light distribution of the fixture, reflectors can also facilitate
additional energy savings when reducing lighting levels through delamping or
relamping
Reflector performance is largely determined by specific design and installation rather
than material selection. As reflector retrofits usually accompany a redesign of lighting
quantity and quality in the space, evaluate changes in fixture appearance, target light
levels, uniformity, and glare through trial installations.
Most indoor commercial fixtures use some type of diffuser, lens, or louver over the
face of the fixture to block direct view of the lamp or to diffuse or redirect light.
Although these shielding media improve visual comfort, each one has strengths and
weaknesses with regard to visual performance, efficiency, and appearance (see Table
6).
In general, diffusers are simply semitranslucent plastic sheets that hide lamp images
and diffuse light evenly across the face of the fixture. Because they spread light in all
directions and absorb a large amount of light, diffusers are not only inefficient but
also ineffective at controlling glare. By using clear plastic lenses with small prismatic
surface patterns instead of diffusers, one can improve efficiency and the distribution
of light.
Table 6: Shielding
Shielding
Material
Standard
Clear Lens
Low-Glare
Clear Lens
Deep-Cell
Parabolic Louver
Translucent
Diffuser
White Metal
Louver
Small-Cell
Parabolic Louver
; Media Options
Luminaire
Efficiency
Range (%)
60-80
60-80
50-90
40-60
35-45
40-65
VCP
Range (%)
50-70
75-85
75-99
40-50
65-85
99
Louver retrofits, depending on cell size and depth, can provide a better balance
between superior light control and energy efficiency. Avoid small paracube louvers
(cells less than 1 inch) whenever possible; although they provide excellent glare
control, they are quite inefficient. Larger "deep cell" louvers provide high efficiency
ENERGY ST^AE? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
and excellent light control and are available for retrofit into many existing fixtures.
New parabolic lowered fixtures are now designed to combine high efficiency (90
percent) with very high VCP ratings above 90. When retrofitting shielding media,
evaluate changes in light output, distribution, and fixture appearance using trial
installations.
The best type of lighting system for glare control and visual comfort is a direct/
indirect pendent mounted system. By providing some up-light against the ceiling and
a direct component to the work surface, direct/indirect lighting minimizes the
extreme brightness between the ceiling surface and the fixture. Installing pendent
mounted systems is usually only cost effective during complete renovations and new
construction. However, these systems continue to come down in price and some
contractors have experienced that the installed cost of a pendent mounted system is
nearly the same as the installed cost of a new lay-in parabolic troffer, and their
clients usually like the direct/indirect lighting system better.
Automatically Control Lighting
Reducing the connected load (wattage) of the lighting system represents only half of
the potential for maximizing energy savings. The other half is minimizing the use of
that load through automatic controls. Automatic controls switch or dim lighting based
on time, occupancy, lighting-level strategies, or a combination of all three. In
situations where lighting may be on longer than needed, left on in unoccupied areas,
or used when sufficient daylight exists, you should consider installing automatic
controls as a supplement or replacement for manual controls.
Time-Based Controls
The most basic controlling strategies involve time-based controls, best suited for
spaces where lighting needs are predictable and predetermined. Time-based controls
can be used in both indoor and outdoor situations. Common outdoor applications
include automatically switching parking lot or security lighting based on the sunset
and sunrise times. Typical indoor situations include switching lighting in production,
manufacturing, and retail facilities that operate on fixed, predefined operating
schedules. Time-based control systems for indoor lighting typically include a manual
override option for situations when lighting is needed beyond the scheduled period.
Simple equipment, such as mechanical and electronic timeclocks and
electromechanical and electronic photocells, can be independent or part of a larger
centralized energy-management system.
Occupancy-Based Controls
Occupancy-based strategies are best suited to spaces that have highly variable and
unpredictable occupancy patterns. Occupancy or motion sensors are used to detect
occupant motion, lighting the space only when it is occupied. For both initial and
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
sustained success in using occupancy sensors, the sensor must be able to see the
range of motion in the entire space while avoiding either on or off false triggering.
This requires proper product selection, positioning, and testing.
Occupancy sensors should first be selected based on the range of body motion
expected to occur throughout the entire lighted space. Controls for hallways, for
example, need only be sensitive to a person walking down a narrow area, while
sensors for offices need to detect smaller upper body motion, such as typing or
reaching for a telephone. Once sensitivity and coverage area is established, sensors
are selected from two predominant technology types.
Passive infrared sensors detect the motion of heat between vertical and horizontal
fan pattern detection zones. This technology requires a direct line of sight and is
more sensitive to lateral motion, but it requires larger motion as distance from the
sensor increases. The coverage pattern and field of view can also be precisely
controlled (see Figure 8). It typically finds its best application in smaller spaces with a
direct line of sight, warehouses, and aisles.
Figure 8: Infrared Sensor Coverage Patterns
Ultrasonic sensors detect movement by sensing disturbances in high-frequency
ultrasonic patterns. Because this technology emits ultrasonic waves that are reflected
around the room surfaces, it does not require a direct line of sight, is more sensitive
to motion toward and away from the sensor, and its sensitivity decreases relative to
its distance from the sensor (see Figure 9). It also does not have a definable coverage
pattern or field of view. These characteristics make it suitable for use in larger
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
enclosed areas that may have cabinets, shelving, partitions, or other obstructions. If
necessary, these technologies can also be combined into one product to improve
detection and reduce the likelihood of false on or off triggering.
To achieve cost-effective, user-friendly occupancy sensor installations, both types of
technologies need to be carefully commissioned at installation to make sure that their
position, time delay, and sensitivity are properly adjusted for the space and tasks.
To ensure proper performance, the position of both wall- and ceiling-mounted
sensors needs to be evaluated carefully. Ultrasonic sensors, for example will respond
to strong air movement and need to be located away from ventilation diffusers.
Infrared sensors should have their line of sight checked to ensure that it is not
blocked by room furnishings. Both types of technologies should be positioned and
adjusted so that their coverage area is not allowed to stray outside of the intended
control area. See Table 7 for appropriate occupancy sensor applications.
All sensors have an adjustable time delay to prevent the lights from switching off
when the space is occupied but there is little activity. Some infrared and all ultrasonic
sensors also have an adjustable sensitivity setting. Customizing these settings to the
application is necessary to balance energy savings with occupant satisfaction.
Figure 9: Ultrasonic Sensor Coverage Patterns
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Table 7: Occupancy Sensor Applications
Ultrasonic
Wall Switch 3
Ultrasonic
Ceiling Mount 3
Infrared Wall
Mount
Infrared
Ceiling Mount 3
Ultrasonic
Narrow View
Infrared
High-Mount
Narrow V tew
Corner-Mount
Wide-View
Technology
Although increasing time delays will reduce the possibility of the lighting being
switched off while the space is occupied, it will also reduce the energy savings.
Setting the sensitivity too high may turn the lighting on when the room is unoccupied,
wasting energy. Similarly, setting the sensitivity too low will create occupant
complaints, as the lighting may turn off when the room is occupied. Evaluating the
potential savings from an occupancy sensor installation should, and can, go beyond
guesswork or speculation. Although sensors primarily affect energy use, they also
affect energy demand, load on HVAC system, and lamp life. Evaluating the economic
feasibility of an installation is best done by monitoring lighting and occupancy
patterns. The use of inexpensive loggers will indicate the total amount of time the
lights are on when the space is vacant, the time of day the savings take place, and the
frequency of lamp cycling. This information will help you make an informed
decision on the economic feasibility of potential occupancy-control opportunities.
lighting Level-Based Controls
Lighting level-based strategies take advantage of any available daylight and supply
only the necessary amount of electric light to provide target lighting levels. In
addition to saving energy, lighting level controls can minimize overlighting and glare
and help reduce electricity demand charges. The two main strategies for controlling
perimeter fixtures in daylighted areas are daylight switching or daylight
dimming.
Daylight switching involves switching fixtures off when the target lighting levels can
be achieved by utilizing daylight. To avoid frequent cycling of the lamps and to
minimize distraction to occupants, a time delay, provided by a deadband, is necessary.
Several levels of switching are commonly used to provide for flexibility and a
smooth transition between natural and electric lighting.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Daylight dimming involves continuously varying the electric lighting level to maintain
a constant target level of illumination. Dimming systems save energy by dimming
fluorescent lights down to as low as 10 to 20 percent of full output, with the added
benefit of maintaining consistent lighting levels. Because HID sources cannot be
frequently switched on and off, they are instead dimmed for time, occupancy, and
lighting level-based control strategies.
Build In an Operations And Maintenance Plan
A lighting upgrade does not end with the installation of efficient equipment. Many
cost-effective opportunities for reducing energy and maintenance costs and
improving occupant satisfaction are frequently missed simply because operations and
maintenance issues are ignored or addressed in an ad hoc fashion after the upgrade.
The following decisions need to be integrated into your upgrade design from the
beginning
All lighting systems experience a decrease in light output and efficiency over time
from three factors:
• Lamp light output decreases (lamp lumen depreciation).
• Dirt accumulates on fixtures (luminaire dirt depreciation).
• Lamps burn out.
Over time, these factors can degrade a system's efficiency by up to 60 percent (see
Figure 10), wasting energy and maintenance costs and compromising safety,
productivity, and building aesthetics. A planned maintenance program of group
relamping and fixture cleaning at a scheduled interval minimizes this waste and
maximizes system performance.
Figure 10: Efficiency Loss Over Time
Energy
Input
Light
Output
Time
ENERGY STAR® EuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Integrating a planned maintenance program into your lighting upgrade saves money
in two ways. First, you will not have to overcompensate with higher initial lighting
levels to ensure adequate lighting over time. The lighting system can be rightsized,
saving on annual energy use and material first costs.
Second, while replacing lamps as they burn out on a spot basis may seem like a cost-
effective practice, it actually wastes valuable labor. Group relamping times the
replacement of lamps at their maximum economic value, generally at about 70
percent of their calendar life. Although it means replacing lamps before they expire,
group relamping dramatically reduces the time spent replacing each lamp (not to
mention the time spent responding to service calls and complaints), which can reduce
your overall lighting maintenance budget by more than 25 percent. In addition,
planned maintenance reduces the cost of lamps through bulk-purchase discounts, the
storage space needs for replacement lamps, and disruptions in the workplace.
To sustain an efficient, high-performance lighting upgrade, assemble an operations
and maintenance (O&M) manual. Use it as both the lighting management policy and
a central operating reference for building management and maintenance staff. This
manual should include the following information:
• Facility blueprints.
• Fixture and controls schedule.
• Equipment specifications, including product cut sheets.
• Equipment and service provider sources and contacts (include utility contacts).
• Fixture cleaning and relamping schedule with service tracking log.
• Procedures for relamping, reballasting, and cleaning fixtures.
• Procedures for the adjustment of photosensors and occupancy sensors.
• Procedures for proper lamp and ballast disposal.
Review the O&M manual with the staff responsible for lighting maintenance. Make
training mandatory for all new maintenance personnel. Correct operation and
maintenance should be built into job descriptions and should become part of all
annual performance reviews.
Exterior Lighting
The three main considerations for exterior lighting are energy waste, glare, and light
trespass. Energy waste and glare are discussed earlier in this chapter.
Light trespass, also known as spill light, is light that strays from its intended target and
becomes an annoyance or nuisance. Maximizing the utilization of light output where
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
and when it is needed will reduce light trespass. IES recommended light levels makes
good economic sense and will minimize adverse environmental impacts associated
with light trespass.
Strategies for Exterior lighting
1. Use lighting fixture with directional control.
2. Direct and control light output to locations where it is needed.
3. Use time controls/dimmers to turn lights on and off and reduce light levels.
4. Design and install lighting to minimize glare.
5. Use the right amount of light for the task
6. Use energy efficient light sources and fixtures.
Environmental Effects
Exterior lighting can also have effects on the environment, excessive lighting near
wildlife areas can adversely impact migrating bird life, nocturnal insects and other
species. State and local ordinances have been established to protect natural wildlife
from light pollution.
Outdoor lighting ordinances and codes encourage better quality lighting, which
reduces glare, light trespass, and energy waste. Many codes are now including the
concept of E-zones to distinguish between different types of lighting areas. For
example, near national or state parks, wildlife refuges, or astronomical observatories
lighting levels should be much lower than in city centers. The ordinances and
community standards vary and local zoning departments should be contacted before
implementing an outdoor lighting project.
Disposal
A lighting upgrade will most likely require the removal and disposal of lamps and
ballasts. Group relamping every several years, and occasional spot relamping as
necessary, will also create additional lamp waste. Some of this waste may be
hazardous. As the waste generator, you must manage it according to applicable
federal, state, and local requirements. While your specific requirements and your
selected disposal options will determine the expense, it is important to note that
disposal costs are rarely a "deal breaker" in a lighting upgrade. Typically, disposal
costs constitute a very small percentage of the overall life-cycle costs of operating a
lighting system (see Figure 11). Investigate and budget for these disposal costs both
as a first cost during the upgrade and as an ongoing operation and maintenance
expense.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figure 11: Fluorescent Lamp Life Cycle Cost
Assumptions:
(2)T832-Wlamps
62-W system wattage (w/electronic ballast)
Electricity at 7f!/kWh
Lamps at $2.65 each
Relamp labor at $1.50 each (group relamping)
Lamp life at 20,000
Lamp recycling at $0.50 each
Contact & Resource Information at a glance
Name
Activity
Pur./icjtions/Contact
Resource Conservation
and Recovery Act
(RCRA)
National Electrical
Manufacturer's
Association (NEMA)
Toxic Substances
Control Act (TSCA)
Lamp Disposal
Lamp Recycling
Disposal of Ballasts
with PCBs
www.epa.gov/rcraonline/
Publication: Some Used Lamps
are Universal Wastes
RCRA Hotline 1.800.424.9346
(DC Metro Area 703.412.9810)
www.lamprecycle.org
www.epa.gov/pcb
TSCA Hotline (202) 554-1401
E-mail tsc a-hotline(ffl!ep a.gov
Many lamps contain mercury, and are therefore considered hazardous waste under
the Resource Conservation and Recovery Act (RCRA). In 1999, EPA added
hazardous waste lamps to the universal waste program. Examples of common
universal waste lamps include fluorescent, high intensity discharge, neon, mercury
vapor, high pressure sodium, and metal halide lamps. Visit EPA's online RCRA Web
site at www.epa.gov/rcraonline/ for more details. Recycling spent mercury-containing
lamps is an alternative disposal method. The National Electrical Manufacturer's
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Association (NEMA) encourages this practice and offers information on a website
www.lamprecycle.org designed specifically to address lamp recycling issues.
The proper method for disposing of used ballasts depends on several factors, such
as the type and condition of the ballasts. Generally, ballasts manufactured after 1978
contain the statement "No PCBs" and have not been found to contain PCBs. The
disposal of Polychlorinated biphenyls (PCBs) is regulated under the Toxic Substances
Control Act (TSCA). Information regarding the disposal of PCBs can be found on
the PCB Home Page at www.epa.gov/pcb. Additional information can be obtained
from the TSCA Hotline, which is reachable by phone at (202) 554-1401 or by e-mail
at tsca-hotline@epa.gov. Other factors controlling the disposal of ballasts will
depend on the regulations and recommendations in effect in the state(s) where you
remove or discard them. Because disposal requirements vary from state to state,
check with regional, state or local authorities for all applicable regulations in your
area.
If you generated lighting material wastes, you are responsible for managing its
disposal according to federal, state, and local laws or requirements.
Summary
Lighting has described opportunities for upgrading your building's lighting system at a
profit. Keep the following strategies in mind as you upgrade your lighting system.
• Design light quantity and quality tailored to the task and occupants' needs.
• Maximize lamp and ballast efficiency.
• Maximize fixture efficiency.
• Use automatic controls to turn lights off or down when not needed.
Reduce light pollution from exterior lighting
• Establish operation, maintenance, and disposal practices.
Next Steps
' Assess whether the existing lighting system meets occupant requirements.
• Communicate the lighting upgrade's objectives and process to all staff and
occupants.
• Specify equipment that maximizes system efficiency, not just component efficiency.
• Perform trial installations to assess energy use and user acceptance.
• Move forward with lighting upgrades.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
SUPPLEMENTAL LOAD REDUCTIONS
Overview
Supplemental load sources are secondary load contributors to energy consumption in
buildings. Some typical supplemental load sources are people, computers, lights and
the building itself. These loads can adversely effect heating, cooling and electrical
loads. However, the effect of supplemental loads can be controlled and reduced
through strategic planning and implementing energy efficient upgrades.
The heat flow diagram (Figurel) illustrates how supplemental load sources effect the
heating, ventilation, and air-conditioning (HVAC) system. With careful analysis of
these sources and their interaction with HVAC systems, you can reduce equipment
size and cost associated with upgrades. These upgrades can increase HVAC energy
savings and reduce wasted energy.
Supplemental Load Reductions section will help you identify these load sources and
provide strategies to mitigate their negative impact on energy performance. "Best
Ways to Save" and "Take Action", will provide you with checklists for reducing
supplemental loads. "Load Reduction Strategy", will discuss various technologies,
equipment and activities that provide opportunities for reducing supplement loads.
Figure 1: Heat Flow In Buildings
PLANT
LOADS
Heat Flow In Buildings: Building Systems Interactions
Figure 2 shows the interaction of heating, cooling, and electrical loads with the HVAC
equipment. Arrows indicate heat flow pathways. Reducing heating, cooling, and
electrical loads reduces the demand on HVAC equipment, thus saving energy.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Supplemental Load Reductions Strategy
• Reduce heating, cooling, and electrical loads to allow the installation of smaller and lower
first-cost HVAC equipment in Fan Systems and Heating and Cooling Systems.
• If possible, delay the installation of HVAC equipment until all loads are reduced and the im-
pacts on HVAC systems can be measured directly.
• If HVAC equipment installation cannot be delayed, take the time to predict the magnitude of
load reductions from upgrade projects.
The Best Ways To Save
• Ventilation Upgrades
— Control ventilation rates to meet minimum requirements
— Install air side cooling economizer cycle
— Utilize energy recovery equipment (i.e., heat pipes and heat wheels)
• Equipment Upgrades
— ENERGY STAR® labeled office equipment
• Building Envelope Upgrades
— Window films and/or shading
— Roof insulation
Take Action!
1. Assess supplemental load sources in your building to determine reduction
opportunities.
2. Contact vendors, contractors, or an engineering consultant to specify upgrades
for supplemental load sources.
3. Install energy efficient upgrades to reduce the effect of supplemental load
sources on heating, cooling, and electrical systems.
Load Sources
In the first stage of the upgrade process, Recommissioning, you had an opportunity
to assess, plan and perform some reductions to the primary and secondary energy
loads in buildings. The next step completing high-efficiency lighting upgrades, you
achieved even more significant cooling and electrical load reductions. The third step
in the process is Supplemental Load Reductions, which explores and identifies
additional load reductions that can not only save energy and money, but will further
increase savings when upgrading equipment for Fan Systems and Heating and
Cooling Systems.
We have briefly introduced the three primary types of loads in all buildings and the
benefits of reducing them. Next we discuss the supplemental load sources—that is,
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
the individual characteristics that contribute to heating, cooling, and electrical loads.
The magnitude of the effect on heating, cooling and electrical loads is determined by
the following load sources:
• Lighting
• Occupants
• Ventilation Systems
• Equipment
• Building Envelope
Supplemental load sources affect more than one primary load type. Windows, for
example, affect your cooling and heating loads. Lighting affects all three.
Lighting
Typically, 70 to 80 percent of the electrical energy used by lighting ends up in the
conditioned space as heat. Upgrading to energy efficient lighting can reduce
electrical and cooling loads, by eliminating heat generated by the lighting system; an
inefficient and expensive form of heating.
The electrical load of lighting systems in office space ranges from 1 watt per square
foot (W/sf) or less for efficient lighting to more than 2 W/sf for older systems. The
Lighting stage seeks to reduce both the connected electrical load (kW) and energy
consumption (kWh) of lighting equipment. Proven technologies provide equal light
output with reduced electrical input and better color rendition. Lighting controls can
significantly reduce operating hours and costs by turning off lighting when spaces are
unoccupied. (For further detail, see Lighting Chapter, Automatically Control Lighting.)
Sample Calculation: Cooling Bonus
Replacing standard fluorescent lights with T8 lamps and electronic ballasts and adding occupancy
sensors could save 300,000 kWh per year of electricity in a typical 100,000-sf office building.
Furthermore, the cooling system removes less heat from the lights, and the additional cooling
energy savings is approximately 41,000 kWh per year for a cooling bonus of 14 percent.
(Assumptions: 1 W/sf savings, 3;000 lighting operating hours per year, cooling efficiency
of 0.6 kW/ton; 80% of lighting waste heat removed by cooling system)
Occupants
You have undoubtedly noticed that when a small room is filled with people, it tends
to become warmer. People emit heat primarily through breathing, perspiration, and,
to a lesser extent, through radiation. An average adult will generate 400 to 600 Btu
of heat per hour. This heat generates a load on your cooling system.
It is difficult to change the contribution occupants make to the energy balance in a
building. Nevertheless, it is important to assess this contribution accurately and
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
recognize that improvements to distribution systems and space conditioning
equipment will lessen its effect on cooling loads and associated costs, while still
maintaining or improving occupant comfort.
Ventilation Systems
Buildings with mechanical cooling-air distribution systems generally mix a portion
of outdoor air with return air from the space to maintain an acceptable level of
indoor air quality (see Figure 2). Outside air requirements for maintaining occupant
health and comfort vary depending on the type of facility, the level of occupancy,
and other factors. (Consult local building codes for outside air requirements; many
locations have adopted ASHRAE Standard 62-1989 as part of their code for
ventilation and some are beginning to consider ASHRAE Standard 62-1999.) In the
summer, hot and humid ventilation air increases cooling loads. In the winter, cold
ventilation air increases heating loads.
Many buildings require air-conditioning although the outside air is relatively cool
and dry, due to internal or supplemental loads. An economizer cycle can be used to
increase amounts of outside air to reduce mechanical cooling load.
.!: "iffire 2: G;»/M/ Air System
Exhaust
Air
Outside
Air
Return
Air
Supply
Air
Humidifier
Heating Coil
Cooling Coil
Fan
Equipment
Equipment powered by electricity will, of course, affect your electrical loads. It is
important to remember, however, that for many types of equipment, much of the
electrical use in a space will ultimately end up in that space as heat. Thus, improving
the efficiency of your electrical equipment not only reduces your electrical loads
but also reduces your cooling load and, as with lighting, allows you the opportunity
ENERGY STAR® BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
to replace that heat more efficiently, when needed, with gas heat or electric heat
pumps.
Office Equipment
Office equipment (whether mechanical, electrical, or electronic) that consumes
energy generates heat in the conditioned space. A typical non-ENERGY STAR labeled
computer and color monitor draw a continuous electrical load of 120 watts or more
(User Guide to Power Management for PCs and Monitors, Lawrence Berkeley National
Laboratory, January 1997). Moreover, the heat they generate can be provided to the
space more efficiently when needed.
Example: Computer Load Reduction
Typical load reduction (for 10 ENERGY STAR labeled PCs and monitors): 1;000 watts
Replacing 10 PCs with ENERGY STAR labeled models represents a reduction of 3,413
Btu/h no longer lost to the conditioned space. So, at $0.08 per kWh, 8 hr. per day, the heating
cost was $0.64 per day.
Assuming gas costs $0.80 per therm and contains 100,000 Btu/therm, with a heating efficiency
of 75%, the new heating cost is $0.29 per day.
Heating Cost Savings: 54%
Kitchens
Most commercial buildings have small kitchen areas for occupants to prepare coffee,
lunch, or snacks. Microwave ovens, coffee machines, and refrigerators are common
in these areas. Microwave ovens and stoves generally consume energy in direct
proportion to the need for warming foods, whereas refrigerators run continuously,
and coffee machines may be left on longer than necessary. Vending machines are
typically lighted and often refrigerated continuously, consuming energy 24 hours a
day. Because this equipment is located within conditioned space, its electricity usage
leads to heat generated in the space.
Domestic Hot Water
Small domestic hot water tanks are often located in bathrooms or cabinets within the
conditioned space. Larger units may be located in mechanical rooms where some of
the heat generated by mechanical room equipment may reach the space conditioning
system. Heat loss from tanks occurs 24 hours a day.
Building Envelope
Building envelope components include windows, doors, walls, the roof, and
the foundation. Heat flows from the warmer side of the building shell to the colder
side. The most commonly discussed parameters of heat flow through the building
envelope, in or out, are conduction, infiltration, and solar radiation. Insulation,
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
building design and materials, and maintenance (such as caulking and weather-
stripping—see Recommissioning) all determine the levels of these heat flows.
Ventilation rates determine the magnitude of the ventilation load as discussed
previously. Mechanical heating and cooling are used to make up the heat lost (or
gained) through conduction, infiltration, and solar radiation.
Heat Transfer Basics
How does heat travel? As you know from experience, heat will always move from warm to cold.
You may not, however, recognize the three ways in which heat travels.
Conduction is heat flow through a material from hot to cold. This phenomenon explains why
the handle on a stove pot becomes hot. It also explains why we add insulation to walls.
Infiltration, a form of convection, is heat flow by movement of air. This phenomenon
explains why we feel cold when the door is open on a winter day. It also explains why we fill
small cracks around windows with caulking.
Radiation is heat flow over a distance from hot to cold. This phenomenon explains how the
sun's warmth reaches earth. It also explains why we use window shades in summer.
Conduction (Roofs, Walls, And Windows)
The materials used in the building shell determine the level of conductivity.
Insulation slows, but does not stop, the flow of heat through walls and roofs. R-value
is a measure of insulation that demonstrates the relative resistance to heat flow
through a solid. The larger the R-value, the more insulation the wall or roof
provides and the less heat that flows through that wall or roof by conduction in a
given time. Similarly, storm windows or double-pane windows rely on an insulating air
space between the panes of glass (see Figure 3) to achieve their increase in R-value.
Infiltration
It is likely in older buildings that heat will leak through breaks in insulation or around
windows. This kind of air leakage, called infiltration, can greatly reduce the
effectiveness of insulation. Thus, R-values alone do not fully describe the energy
efficiency of a wall or roof.
All buildings allow some level of uncontrolled airflow through the building envelope.
Infiltration paths include seals around operable windows, cracks or seams in exterior
panels, doorjambs, and shell penetrations such as holes for wiring or roof curbs for
HVAC equipment. Air flowing into or out of these leakage paths is driven by
pressure differences caused by HVAC equipment between the inside and outside of
the building, between windward and leeward sides of the building, and between upper
and lower floors (natural convection, most commonly called the chimney effect) of
the building. In buildings with mechanical ventilation systems, it is desirable to
minimize uncontrolled air leakage to reduce cooling loads.
Solar Radiation
The sun's influence on the heating of a building is a concept that has been
recognized for a long time.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figure 3: Window Heat Flow
Solar Radiation
Infiltration
Noiv, in houses with a south aspect, the sun's rays penetrate into the porticoes in winter, but in
summer, the path of the sun is right above the roof so that there is shade. If, then, this is the
best arrangement, we should build the south side loftier to get the winter sun, and the north
side lower to keep out the cold winds.
Socrates, 360 B.C.
Solar radiation can have an enormous influence on the heating and cooling required
in a space. The sun often makes perimeter spaces uncomfortably hot, and it also
creates glare and fades fabrics. Reducing solar gain (heating caused by solar radiation)
offers very profitable opportunities for cooling-load reductions and energy savings.
Heat can also be radiated out of the building through the windows in winter if
outdoor temperatures are much lower than room temperature. Yet, the amount of
heat lost through radiation is far less significant than that of other types of heat gain
or loss.
Supplemental Load Reduction Opportunities
As the heat flow diagram (Figure 1) illustrates, load reductions made in this stage can
significantly and positively affect equipment modifications that will be made in the
remaining stages.
ENERGY STAR
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Fan System Upgrades addresses fan systems, which can usually be right-sized to a
smaller capacity or operated more efficiently as a result of load reductions.
Sample Calculation: Chiller Cost Reduction
Looking again at the chiller energy savings in a 100,000-sf building,
the 1 W/sf reduction in lighting load would allow a chiller capacity reduction of
approximately 23 tons (assuming that 80 percent of the waste heat reaches the conditioned
space). If you assume a typical chiller cost of $450 per ton, then you could figure on reducing
the first cost of a new chiller by more than $10,000 based on the 23-ton reduction. Other
load reductions would further reduce the chiller size requirement.
Heating and Cooling System Upgrades address equipment that also can be right-
sized, usually to a smaller capacity, and/or operated more efficiently as a result of
load reductions.
Upgrades that effect load reductions have the potential for both future energy
savings and lower first costs in Fan Systems and HVAC Systems. A analysis done on
supplemental load reductions will pay back more than once.
Distribution System Benefits
Distribution system motor size may be reduced with smaller cooling loads. The first cost on a
fan motor, for example, would be $26 less for every ton of reduced cooling load. (Assump-
tions: motor cost @ $65/hp x 1 hp/1,000 cfm x 400 cfm/ton = $26/ton)
Load Reduction Strategy:
ENERGY STAR Labeled Office Equipment
In the business world, office equipment constitutes the fastest growing portion of
electrical loads. However, much of this energy is wasted because equipment is left on
when not in use throughout the workday, at night, and on weekends.
Electrical loads from office equipment, as well as cooling loads, can be reduced by
the use of ENERGY STAR labeled office equipment. Virtually all office equipment
manufacturers offer a wide range of ENERGY STAR labeled models, including copiers,
printers (and some mailing machines), fax machines, monitors, computers and
workstations, scanners, and multifunction devices. Office equipment with the
ENERGY STAR label saves energy and money by powering down and entering "sleep"
mode or off mode when not in use. Products that meet the ENERGY STAR
specifications use about half as much electricity as conventional equipment.
Energy-efficient equipment with the ENERGY STAR label cost the same as comparable
non- labeled equipment. However, the savings are greater for labeled equipment, as
shown in Table 2. The estimated savings below are per unit and can be multiplied to
estimate savings for an office with hundreds of energy-efficient products.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Table 2: ENERGY STAR Labeled Office Equipment Savings
Product
Estimated Annual
Savings/ Unit
Large Copier $130
(plus J650 if double-sided
copying feature is used)
Printer $40
Computer and Monitor $20
Fax $15
Source: Lawrence Berkeley Laboratories.
ENERGY STAR labeled equipment produce less heat by powering down when not in
use. This reduces cooling load, and energy costs of air-conditioning and contributes
to a cooler and more comfortable workspace. In addition, building occupants can do
their part to minimize loads and costs by turning off equipment (including ENERGY
STAR labeled models) at night and on weekends.
Managing Your Office Equipment
Here are four steps organizations should take to ensure that they realize the benefits
offered by ENERGY STAR labeled office equipment.
Check Equipment Specifications — Look for and request the ENERGY STAR label
when purchasing new equipment. It may appear on the product itself, in
advertisements and promotional materials, or on the packaging. If the label isn't
visible, ask the manufacturer, or retailer if the model meets the ENERGY STAR
specifications.
For existing models in the office, check to see if they have power management or
other energy-saving features. Although they may not meet the ENERGY STAR
specifications, these features will provide some energy savings if activated. In
addition, control devices are available for non-ENERGY STAR labeled computers,
monitors, and printers. These external hardware units are designed to reduce the
energy consumption of older equipment by turning them off when not in use. To
request a list of control device manufacturers and their products, call the ENERGY
STAR hotline at 1-888-STAR YES.
Ensure Proper Equipment Setup - Confirm information systems or support staff
that the equipment is installed properly with the power-management features enabled.
Each employee has different work habits and should be encouraged to adjust the
time settings to accommodate individual work patterns. If the computer power-
management feature is not compatible with the network environment, disable the
feature on computers, but continue to use it on all of the monitors. Monitors
consume 80 percent of the energy used by the two components.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Set a Corporate Policy — Inform employees through regular training and other
internal materials, that ENERGY STAR is an organizational policy. E-mail and voicemail
messages can be sent to employees providing them with ENERGY STAR information as
well as updates on the air pollution reductions resulting from their using energy-
efficient equipment. Displaying ENERGY STAR posters in copy rooms, lounges, and
other areas can also help to remind employees to use the energy-saving features and
to turn off their equipment at the end of the day.
Educate Employees — Educate employees so that they understand what power
management is and why it is important. Here are some examples of issues that you
should focus on:
Ic "Sleep" the same as "Off?"No. Sleeping equipment still draws some electricity; so
turn it off when not in use for long periods of time.
Will the power-management feature shorten the lifetime of my computer or monitor? No. Heat is
a leading cause of equipment failure. When the power-management feature is used,
the computer generates less heat, so it may last longer and have improved reliability.
In addition, manufacturers have increased the reliability of components, such as hard
drives and microprocessors, that "cycle" when power management is used.
Does a screen saver help save energy? No, but there are screen savers available that won't
interfere with the power-management features. If screen savers are used in the
office, be sure to choose those that will display images for a predetermined period of
time and then enter the sleep mode. Graphical screen savers are primarily for
entertainment and are not energy-efficient features.
Table 3: ENERGY STAR Labeled Office Equipment
Equipment ENERGY STAP^ Specifications
Computers
Copiers
Fax Machines
Monitors
Multifunc tion
Devices
Printers
Scanners
in use.
Automatically enter a low-power sleep mode after a period of inactivity.
Efficiency specifications based on power supply.
Depending on copier speed, automatic power-down and shutoff to 5—
20 watts or less after 30—90 minutes of inactivity. Separate specifica-
tions available for large format copier models. Recommended automatic
double-sided copying on medium- and high-speed models.
Automatically power down to 15—45 watts after 5—15 minutes of inac-
tivity, depending on fax speed.
Automatically enter two successive low-power modes of 15 watts and 8
watts after 15—30 minutes of inactivity.
Automatically power down to 5—105 watts after 15—120
minutes of inactivity, depending on equipment speed.
Automatic double-sided copying on machines that copy at
44 pages or faster per minute.
Automatically power down to 15—45 watts, depending on print speed.
Automatically power down to 12 watts or less when not
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
ENERGY STAR Specification^
Computers — ENERGY STAR labeled computers automatically enter a low-power sleep
mode after a period of inactivity. The newest ENERGY STAR specifications allow
workstations to qualify for the ENERGY STAR label. Most ENERGY STAR labeled
computers are compatible with the primary network environments (for example,
Novell NetWare, Banyan Vines, and LAN Manager). Consult with the manufacturer
before purchasing a computer to ensure it is designed to be compatible with your
particular network environment.
Monitors — As of January 1998, ENERGY STAR labeled monitors automatically enter
two successive low-power modes of 15 watts and 8 watts. In addition to reducing
wasted energy, ENERGY STAR labeled monitors emit fewer electromagnetic fields
when sleeping because most of their electronic components are turned off.
Printers/Fax Machines — Typically, printers and fax machines are left on 24 hours
a day, although they are active for only a small percentage of that time. To conserve
energy, ENERGY STAR labeled printers and fax machines, after a period of inactivity,
automatically enter a low-power mode of 15 to 45 watts, depending on product
speed. Approximately 95 percent of the printers and fax machines available in the
United States meet the ENERGY STAR criteria. When purchasing new equipment,
consider a combination printer/fax machine, which consumes half as much energy
when idle as two stand-alone products.
Copiers — ENERGY STAR labeled copiers include a low-power mode and an
off mode. About 70 percent of US black-and-white copier models carry the ENERGY
STAR label. Even if a copier is used frequently during business hours, the auto-off
feature will save energy by turning off the copier at night and on weekends. The
average office worker uses 10,000 sheets of copy paper each year. Selecting the
double-sided copying (or duplexing) feature will reduce waste, save paper, and cut
mailing and storage costs.
Scanners — Scanners that qualify for the ENERGY STAR label automatically enter a
low-power mode of 12 watts or less when not in use. When the user wants to scan
another image, the machine will "wake up" and resume activity.
Multifunction Devices — ENERGY STAR labeled multifunction devices offer copying
as well as printing, faxing, scanning, and/or other capabilities. To reduce wasted
energy, they automatically enter a sleep mode of 5 to 105 watts (depending on
output speed) after a period of inactivity. High-speed multifunction devices also
include an automatic double-sided copying feature.
Load Reduction Strategy: Control Ventilation Rates To Minimum
Requirements
If your building was designed and built before the mid-1970s and there have been
no substantial modifications of equipment or controls, the chances are good that
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
energy savings can be achieved not only through improved equipment efficiency but
also by improving the control of outside air. This can be done by controlling outside
air to the minimum required for health and comfort when outside air is an energy
burden and by increasing outside air delivery when outside air can provide free
cooling or nighttime precooling In most cases, any opportunity to save energy by
increasing the delivery of outside air will also tend to improve the building's air
quality.
A testing, adjusting, and balancing contractor (see Fan System Upgrades) can be
engaged to determine the quantities of outdoor air provided by your air-handling
units at both full-load and part-load conditions. These quantities can be compared to
occupancy levels to determine the recommended ventilation rates per occupant. If
they exceed ASHRAE Standard 62-1989, which is 15 cfm per occupant for office
spaces without significant sources of pollution (see Load Sources), reducing the rates
to the minimum required, particularly during occupied hours in the summer, could
result in substantial energy savings.
CO2 Sensors and Time Clocks
Because occupants are most often the primary source of CO2 in buildings, CO2 is
sometimes used as a surrogate for determining levels of occupant-related
contaminants. Accordingly, there is some interest in using CO2 sensors to control
outdoor air ventilation. When CO2 levels are low, outdoor air ventilation rates are
reduced to save energy, and, when CO2 levels are high, outdoor air rates are
increased to reduce occupant-related contaminants. Because demand-controlled
ventilation using CO2 sensors does not account for other sources of pollution, it is
important to be aware of other sources that may create indoor air quality problems.
Although the opportunities to reduce cooling and heating loads with CO2monitoring
can be significant, the risk of causing occupant discomfort is also significant. Thus,
ENERGY STAR recommends obtaining outside expertise to implement this load
reduction strategy.
Time clocks that automatically reduce ventilation rates during unoccupied periods
can greatly reduce the energy load in buildings. If your building does not currently
have nighttime setback of the ventilation system, consider investing in time clocks.
Load Reduction Strategy: Air Side Cooling Economizer Cycle
There are times when increasing outside air beyond ASHRAE 62-1989 requirements
will lower cooling loads.
It is often possible, through the use of an economizer, to use outside air to cool a
space either totally or partially. An economizer consists of local controls and dampers
capable of delivering 100 percent outside air. Air-side economizers come in two
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
types: dry-bulb and wet-bulb economizers. A dry-bulb economizer is activated by
outdoor air temperature. When the temperature is below a certain set-point, the
outside air damper opens to its maximum aperture to allow 100 percent outside air
in. A wet-bulb economizer operates in the same manner; its only difference is that
both temperature and relative humidity are measured. If you are familiar with the
saying "it's not the heat, it's the humidity," you can understand why relative humidity
is important.
Table 4: Economizer Savings
Climate Savings i
Humid-climate
commercial buildings
Temperate-climate
commercial buildings
Desert-climate small
commercial buildings
Arid-climate small
commercial buildings
Temperate/coastal-climate
small commercial
buildings
Los Angeles
commercial buildings
San Francisco
commercial buildings
Fresno commercial
buildings
Source: E SOURCE, Space Cooling Ted
25
50
12-20
30-40
>70
15-65
40-80
30-45
mology Atlas, Sec. 6.3.1.
In a practical sense, it is difficult to measure relative humidity accurately over a long
period. For this reason, dry-bulb economizers, which measure temperature alone, are
common.
Do not assume a building uses outside air economizing just because dampers,
temperature sensors, and controls are installed. Outside air dampers, along with
sensors, are prone to malfunctioning. Again, underscoring the importance of the
ENERGY STAR Approach, Building Tune-Up is designed to identify and fix equipment
problems so that systems such as outside air economizers work properly.
Load Reduction Strategy: Night Precooling
Night precooling, another ventilation control strategy, is an energy-efficient way of
cooling your building in lieu of mechanical refrigeration cooling. Night ventilation is
an effective means of cooling in regions where nighttime temperature is low and
daytime cooling loads are significant (Passive Solar Journal, vol. 2, no. 2). This strategy
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
can be considered as a flushing method, whereby cold outdoor air is introduced
during the night to flush internally generated heat out of a building.
Night precooling can save significant energy. Studies have shown that cost savings
range from 5 percent in Phoenix, Arizona, to 18 percent in Denver, Colorado, for a
typical office building. Additionally, peak demand reduction can also be achieved
through night precooling. Simulation analyses have shown that precooling a 100,000-
sf 3-story building in Sacramento, California, would save up to 12.6 percent in
energy and cause a peak demand reduction of 31.3 percent (E SOURCE, Space Cooling
Technology Atlas, Section 6.3.1).
Load Reduction Strategy: Minimize Kitchen Equipment Loads
When buying kitchen equipment such as refrigerators, buy the most energy-
efficient model available in your size. If you have vending machines, they are
typically lit continuously, consuming energy 24 hours a day. If possible, put such
lighting on timers or replace them with more efficient lights. With some vending
machines, it is possible to put the entire machine on a timer.
Load Reduction Strategy: Reduce Domestic Hot Water Heat Loss
Heat loss from domestic hot water tanks occurs 24 hours a day. Reducing heat loss
from the tanks with either added insulation or installation of a higher efficiency unit
also reduces the load on air-conditioning systems. For electric hot water tanks, an
insulation wrap is both easy to install and pays for itself quickly. Another option is
point-of-use heaters that have no tank and therefore no standby losses.
Load Reduction Strategy: Window Films
Window films can be retrofitted to existing windows to reduce heat gain due to solar
radiation and provide a low-cost cooling load reduction (see Figure 4).
Window films are thin layers of polyester, metallic coatings, and adhesives that save
energy by limiting both the amount of solar radiation passing through the windows
and the amount of internal heat escaping through windows. They can be applied
directly to the interior surfaces of all types of glass and generally last 7 to 12 years.
Typically, in the heating season, more heat escapes from most windows than comes in
from the sun (on a 24-hour basis); the extent depends on the local climate and the R-
value of the window. Window films can help reduce this costly heat loss by reflecting
indoor radiant heat back into the room. In the cooling season, even when drapes and
blinds are closed, much of the sun's heat passes through the glass into the room.
Window films address this problem by reducing solar heat gain at the window.
In short, window films save energy by reducing radiation and other forms of heat
transfer through windows, by allowing better balance in heating and cooling systems
and by providing opportunities for HVAC downsizing.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figure 4 • )i: indoiv Films
Glass
Release Liner.
Polyester Film
(Clear/ •
U-V Inhibitors)
Optional
Reflective •
Layer
Adhesive
Scratch
• Resistant
Coating
Window Films: Cost Effective For Your Building?
Apply the following criteria to your building. The more criteria your building meets, the more
profitable window films can be.
• The amount of window space on the building is large compared to the total surface area
(that is, greater than 25 percent of the surface area).
• The building is in a sunny location with little natural shade.
• Windows on the south and west sides of the building receive direct sunlight.
• Windows have single-pane glass. (Note: Even buildings with better insulated, double-pane
windows may profit from window films.)
• Windows are clear; they have no tint, color, or reflective coating.
• The building is in a geographical area that has many sunny days.
Fan systems and cooling equipment can be downsized following peak cooling load reductions.
There are several economic considerations in regard to window film installations. For
old, drafty single-pane windows, complete window replacement is another option.
Although this option is more expensive than window film installation, it may be more
appropriate depending on your window condition. It may be most cost effective to
install window films only on the south and west sides of the building. Window films
typically cost between $1.35 and $3 per square foot, installed. Improperly installed
films can, however, bubble, crack, peel, or even cause the glass to crack, so it is
worthwhile to buy films with a material and installation guarantee of 5 to 10 years.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Load Reduction Strategy: Window Shading
Other ways to reduce the solar cooling load imposed by windows involve physical
shading. Exterior and interior shading are among the best ways to keep the sun's heat
out of a building. In warm climates, buildings in sunny areas can benefit greatly from
a variety of shading techniques (see Figure 5).
Interior Shading
Venetian blinds and other operable shades are a low-cost and effective solution for
keeping out the sun. More sophisticated systems, sometimes even located between
two panes of window glazing, automatically open and close shades in response to the
cooling load imposed by the sun.
Law emissiuty coatings
Low-emissivity (low-e) coatings provide better insulation, while letting in as much
solar heat gain as possible. These coatings are now typically offered on many
window systems.
Exterior Shading
Properly applied, overhangs and awnings can be particularly beneficial. During
winter, when the sun is low in the sky, sunlight is beneficial for heating and lighting
the inside of a space while the windows are not shaded. During summer, when the
sun is high in the sky, overhangs or awnings keep sunlight off the window.
Figure 5: Shading Strategies
o o o
Summer Sun
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Exterior shading techniques are also an excellent way of reducing glare produced
when sunlight strikes glass directly.
Awnings are popular exterior shading devices on low-rise commercial buildings.
Fiberglass or metal shade screens are often cost effective for low-rise commercial
applications and are capable of reducing solar heat gain up to 80 percent in
comparison to unshaded clear glass. Air space between exterior shades and windows
helps carry away heat absorbed by the shade before it can be transferred through the
window.
Exterior roller blinds are one effective method of exterior shading. Exterior roller
blinds are a series of slats, typically horizontally oriented, made of wood, steel,
aluminum, or vinyl. Like interior shades, they can be raised or lowered as needed to
control the amount of sunlight entering a building space. In warm temperatures
during sunny hours, they can be lowered to function as an insulating barrier, limiting
incoming sunlight and reducing heat gain. Similarly, they can be raised in cold
temperatures during sunny hours for desirable heat gain. Partially raising the blinds
allows some daylight and air to enter between the slats. Experimentation has shown
that these blinds can improve the R-value of the window area from the standard
0.88 for uncovered single glass to 1.75 with a lowered blind. However, this shading
technique can be expensive, and it alters the exterior appearance of a building.
When selecting shading system colors, be sure to remember that light colors are
better at reflecting solar radiation. A darker awning may require venting to allow heat
dissipation.
Shading With Vegetation
Finally, deciduous trees are also very effective at providing shade: During the winter
they are bare, allowing sunlight to pass through, but during summer they shade the
building.
Load Reduction Strategy: Roof Insulation
A significant portion of a building's heat loss and heat gain occurs through its roof.
Energy efficiency measures that slow the rate of energy transfer through the roof
therefore provide opportunities for significant energy savings. The most effective
means of reducing the heat transfer rate through the roof is to maximize R-value by
adding thermal insulation.
In buildings undergoing roof replacement, it is always a good idea to incorporate
roof insulation as part of the renovation. Rigid board insulation, typically two inches
thick, can be applied to the exterior surface of the roof prior to the application of
the new roof covering. This technique works well with new roof construction as well.
However, it is generally not cost effective to apply insulation to the outside surface
of an existing roof unless the roof itself is being replaced.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Where there is an attic or crawlspace below the roof, there are other options. Roof
insulation types used in such applications include fiberglass blanket or "batt"
insulation; blowing insulation, typically a spray-on urethane or fiberglass foam; or
blown-in loose cellulose or fiberglass. In most cases, roof insulation for buildings
withvented attic spaces is applied to the attic floor, in the form of either fiberglass
batts or blown-in loose insulation.
Layers
Outside Air
Roof Covering
Roof Membrane
Roof Insulation
Vapor Retarder
Base Insulation
Steel Deck
Still Air
Ceiling Board
Inside Air Film
For buildings with unvented attics or no attic, or in buildings where foot traffic might
damage attic floor insulation, apply insulation to the inside roof surface, using either
rigid board or spray-on foam insulation. Attic floor insulation is also inappropriate in
the presence of any type of water pipe in the attic space. Because the insulation
reduces the heat flow from the occupied spaces upward to the attic, the attic space is
at a lower temperature, increasing the likelihood that your pipes may freeze and burst
during the heating season.
In well-insulated buildings, the relative significance of heat loss through uninsulated
structural members, particularly those made of metal, increases. This effect reduces
the effectiveness of the insulation by as much as 20 percent. It is important to
consider insulating these structural members (see Figure 6) as well as the building
ENERGY ST^AE? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
envelope components, unless, as with flat roofs, the roof insulation is on the exterior
of the building.
Load Reduction Strategy: ENERGY STAR Labeled Roof Products
A significant portion of a building's heat loss and heat gain occurs through its roof.
Energy efficiency measures that slow the rate of energy transfer through the roof
therefore provide opportunities for significant energy savings. As with insulation, an
effective means of reducing the heat transfer rate through the roof is to minimize
the amount of heat conducted through the roof. ENERGY STAR labeled roof products
use reflectivity to lower the roof surface temperature by up to 100 °F, thereby
decreasing the amount of heat transferred into a building's interior.
Benefits of ENERGY STAR labeled roof products include:
• Downsized A/C equipment. A reflective roof can reduce peak cooling demand
by 15%. The home or building owner may be able to purchase a smaller, less-
expensive cooling system.
• Extended roof life. Roofs undergo significant expansion and contraction as they
heat and cool throughout the day. Heat absorbed by the roof can also accelerate
degradation by ultraviolet rays and water. A reflective roof can reduce the
amount of thermal shock that occurs on the roof surface and make the roof
last longer.
• Reduced Heat Island Effect. Roofs made of non-reflective products cause the
temperature of the air passing over them to rise, resulting in an increase in the
overall temperature of the area, also known as a "heat island effect." The
elevated temperature leads to increased building and vehicle air conditioning
demand, increased levels of smog, and the associated increased incidence of
heat- and smog-related health problems.
Energy savings from installing ENERGY STAR labeled roof products will depend on the
geographic location and climate where it is installed, existing insulation levels in the
building, the type of roof it replaces, the type of roof installed, and how well it is
kept clean and maintained. In general, cooling energy savings can be as high as 50%.
Additionally, a reflective roof can reduce peak cooling demand by 10 to 15%. As a
result, building owners may be able to purchase smaller, less expensive HVAC
systems.
Additional Strategies
There are many additional strategies for reducing loads. Some are only cost effective,
however, when viewed as part of the incremental costs of replacing old equipment
for reasons unrelated to energy efficiency. Other technologies are emerging and may
become more cost effective in the future.
ENERGY STAR® BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Load Reduction Strategy: High-Performance Windows
Windows almost always represent the largest source of unwanted heat loss and heat
gain in buildings. This is because even the best windows provide less insulation (lower
R-value) than the worst walls or roofs, and because windows represent a common
source of air leakage. Windows also admit solar radiation. Of course, we neither
want nor need to eliminate windows.
While improvements such as films, shading, and weather-stripping have already been
discussed, replacing the complete window offers some additional benefit and is
economically feasible in some situations, particularly as part of an extensive
renovation.
Many window or glazing systems of buildings built in the 1960s and 1970s are
beginning to fail. Often, these failing systems are single-pane glass, as found in 68
percent of commercial space and 52 percent of office space in the United States. If
your building has windows needing replacement, this presents an excellent
opportunity to use the latest in advanced window designs, which offer paybacks in
only a few years.
Here are some new technologies to look for:
• Spectrally selective glasses can maximize or minimize solar gain and shading
depending on the product chosen.
• New double-glazed systems with layers of low-e film stretched across the
interior air space have become available, which offer R-values as high as 8.
— Gas filled windows, using argon or krypton gas, minimizes the convection
currents within the space, conduction through the gas is reduced, and the
overall transfer of heat between the inside and outside is reduced.
Architects and facility planners now have a vast selection of new window types
available that not only meet stringent energy performance requirements but also
satisfy aesthetic concerns.
Load Reduction Strategy: Energy Recovery Strategies
Heat recovery is one of the most beneficial ways of optimizing energy efficiency
during building operations. Exhaust air from HVAC systems is a primary source of
useful waste heat. During most of the year, energy is consumed to heat, cool,
humidify, or dehumidify the air supply. Exchanging the energy between the outdoor
air introduced into the building and the air exhausted from the building reduces the
energy required to condition the outdoor air. Several heat recovery technologies are
available, including rotary heat wheels, plate and frame heat exchangers, runaround
coils, and heat pipes.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Each of these technologies is suited to specific applications. Consult vendors and
engineers to determine the best match for your building. Depending on the
application and technology type, these systems can recover 50 to 80 percent of the
energy used to heat or cool ventilation air brought into the building.
Load Reduction Strategy: Desiccant Dehumidification
As new building codes require more outside air to be circulated into buildings, the
amount of humidity that an air-conditioning system must remove has increased
substantially. Conventional cooling systems consume more and more energy
removing moisture, often overcooling the air below its dew point just to get the water
out.
Recently, new desiccant-based cooling systems have emerged on the market.
Desiccants are materials that absorb moisture from their surrounding space. Most
people know them as small, usually white, packets found in the packaging of
electronics and dried foods. Desiccant materials used in building applications can be
regenerated. In other words, the moisture is driven out of them by the application of
heat, whereupon they can be reused to absorb more water from the air. The heat is
generally derived from gas, steam, or waste heat from the building.
The best applications for desiccant cooling systems are buildings with large
dehumidification loads, long hours, and those in warm and humid climates—for
example, hospitals, swimming pools, or supermarket fresh-produce areas. The cost
of gas or waste heat used for regeneration is typically much lower than the cost of
electricity used for conventional dehumidification.
Load Reduction Strategy: Building Integrated Photovoltaics
Photovoltaic (PV) panels generate electricity while absorbing solar radiation and
reducing solar heat gain through the roof. A newly emerging Building Integrated PV
(BIPV) technology is the use of PV roofing materials that can be installed much like
traditional shingles or flat roof membranes, and involve little or no unusual
engineering design.
Recently, buildings have incorporated PV cells mounted on clear building materials
both to generate power and allow some light transmission through the panels to
provide daylight to the space below. Such a system was installed at the Olympic
Natatorium, built for the 1996 Olympic Games, at Georgia Institute of Technology.
With PV materials becoming available for roofs and walls, as well as other products
that allow through some visible light, a large proportion of a building's exterior
surface area has the potential to provide power generation of approximately 0.5 to 1
kW peak for every 10 square meters, depending on construction and orientation. In
addition to reducing solar heat gain through the shell, BIPV technologies offer the
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
advantage of providing the greatest power generation capacity coincident with the
time of day when space-cooling needs are greatest.
Load Reduction Strategy: Daylighting And Light Pipes
Once the most efficient electric lighting sources are implemented, reduce lighting
operating hours for additional energy savings. The use of daylight sensors is the first
step toward eliminating or reducing electric lighting operation when there is enough
available daylight from windows along building perimeters during occupied hours.
It is often possible to shade windows enough to reduce heat gain and glare
substantially (see shading discussion above) while still providing enough daylight to
eliminate electric light usage for much of the workday. Exterior light shelves can be
used to reflect light onto the ceiling of the space without absorbing much solar heat.
Lighting in parts of the space away from the window or light source can be increased
using reflective surfaces or louvers.
What about interior building spaces, particularly those below the top floor where
skylights are not feasible? Emerging and experimental technologies offer the potential
to "pipe" light from roof- or wall-mounted collectors to interior spaces that do not
have windows. One advantage of piping light is the potential to use either the daylight
collector or a high-efficacy light source to light the whole system depending on
daylight availability.
Load Reduction Strategy: Solar Windows (Chromogenic Glazings)
Research is currently under way to develop glazings that change automatically in
response to changing temperature and/or light level conditions—similar, for example,
to sunglasses that darken in sunlight. One technology being investigated is a
treatment that turns glass cloudy as temperatures rise. Another technology uses an
electrical current to alter the spectral selectivity of the glass. Strategically selected and
positioned sensors thus control what the window is doing at any given time. A third
effort is focusing on the embedding of thin-film amorphous PV material into glass
while retaining light transmission so that the window becomes a miniature electric
power plant.
None of these chromogenic technologies is commercially available at this time, but
all are showing promise. In just a few years, window technology may indeed be vastly
different from today's.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Summary
Other Load Reductions identifies numerous opportunities for further reducing your
loads and allowing the installation of smaller, lower first-cost equipment in fan and
HVAC Systems. To recap, here are your best savings opportunities:
• Ventilation Upgrades
— Control ventilation rates to minimum requirements
— Install air-side cooling economizer cycle
— Install energy recovery technologies
• Equipment Upgrades
— Use ENERGY STAR labeled office equipment
• Building Envelope Upgrades
— Add window films and/or shading
— Upgrade roof insulation
Next Steps
• Assess your load sources to determine where loads can be reduced.
• Implement upgrades to reduce loads and allow the installation of smaller
equipment in fan and HVAC systems.
• If possible, delay the installation of HVAC equipment until all loads can be
reduced and the impacts on HVAC systems can be measured directly.
Appendix: History Of Ventilation Requirements
Building codes require minimum ventilation rates. Code requirements have changed
significantly over the years in response to the impact of outside air quantities on
energy consumption, occupant comfort and health.
The American Society of Heating, Refrigerating, and Air-Conditioning Engineers
(ASHRAE) has updated its recommended ventilation rates periodically. Prior to
1973, ASHRAE recommended a standard of 15 to 25 cubic feet per minute (cfm)
of outside air per person. After the oil crisis of the mid-1970s, a new awareness of
the energy costs for treating outside air led to ASHRAE Standard 62-1981.
ASHRAE Standard 62-1981 defined ventilation air requirements and allowable
contaminant levels. Striking a compromise between indoor air quality concerns and
energy consumption concerns, Standard 62-1981 recommended a minimum of 5
cfm of outside air per person in a nonsmoking environment and 20 to 35 cfm of
outside air per person in a smoking environment. At times, the reduction in outside
air requirements for nonsmoking spaces led to an increase in indoor air quality
complaints. ASHRAE Ventilation Standard 62-1989 required at least 15 cfm of
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
outside air per person (and more for many types of spaces) and a maximum CO2
concentration of 1,000 ppm.
Partly because of lower ventilation rates set in ASHRAE Standard 62-1981,
complaints of discomfort and poor health, phenomena now referred to as Sick
Building Syndrome and Building Related Illnesses, increased. This led ASHRAE to
raise its ventilation requirements closer to its previous levels. Depending on space
use, ASHRAE Standard 62-1989 requires minimum outside ventilation rates of 15 to
25 cfm per occupant. The new standard defines acceptable air quality as "air in
which there are no known contaminants at harmful concentrations as determined by
cognizant authorities . . ." Since the 1989 publication of the Standard, several
cognizant authorities have determined that tobacco smoke is harmful to human
health. These authorities include, among others, the U.S. Environmental Protection
Agency, World Health Organization, American Medical Association, American Lung
Association, National Institutes of Occupational Safety and Health Administration,
and the Office of the U.S. Surgeon General, while smoking lounges still require 60
cfm of outside air per occupant.
The current ASHRAE Ventilation Standard 62-1999 requires at least 15 cfm of
outside air per person (and more for many types of spaces) and modifies the criteria
for maximum CO2 concentration to 700 ppm above the outdoor air concentration.
In addition, language has been added more clearly describing the CO concentrations
as a useful indicator of the concentration of human bioeffluents. Finally, Standard
62-1999 removes references that the ventilation rates (in Table 2 of the Standard)
will accommodate a moderate amount of smoking. Please see Standard 62-1999 for
further details regarding smoking and ventilation. (Table 1 summarizes the history of
ventilation requirements.)
Table 1: Historical Outside Air Requirements
Outside air per personcfm
Industry Standard 1973 15-25
ASHRAE Standard 62-1981 > 5
ASHRAE Standard 62-1989 > 15
ASHRAE Standard 62-1999 >15
With the increased use of chemical-based products, building materials, and
furnishings that contribute to indoor pollution, health and comfort complaints,
ASHRAE has concurrently tried to address contaminants not produced by occupants
in its ventilation requirements. The current Standard 62-1999 allows the user to
establish ventilation requirements based on a separate procedure that analyzes
specific contaminants.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
FAN SYSTEM UPGRADES
Overview
Fan Systems, also know as air-handling systems, are the conduit for getting
conditioned air (heating and cooling) to people occupying a building, and therefore
directly impacting occupant comfort. Fan systems can be upgraded and adjusted to
optimize the delivery of air in the most energy efficient way.
The heat flow diagram (Figure 1) illustrates how, in Fan System Upgrades, you can
take advantage of the load reductions you have realized in other stages of an
integrated approach. The resultant opportunities for reducing your air-handling
system's energy consumption are now tremendous. Continuing with the integrated
approach, you can realize a 50 to 85 percent reduction in fan power consumption.
Fan System Upgrades section will help you identify which components of your fan
systems are most inefficient. "Best Ways to Save" and "Take Action", will provide
you with checklists for improving the operation of fan systems. "Best Opportunities"
and "Additional Considerations" discuss the opportunities for improving energy
performance of your fan systems through technology as well as operations. The
appendix Fan System Survey provides instructions for recording the loads associated
with your fan system.
Figure 1: Heat Flow In Buildings
ENERGY STAR? BuildingManual
PLANT
LOADS
Heat Flow In Buildings: Building Systems Interactions
Figure 2 shows the interaction of heating, cooling, and electrical loads with the HVAC
equipment. Arrows indicate heat flow pathways. Reducing heating, cooling, and
electrical loads reduces the demand on HVAC equipment, thus saving energy.
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Fan Systems Strategy
• Rightsize your cooling system to match reduced loads.
• Take advantage of improvements in air-handling technology.
• Install equipment that allows for more efficient operation, lower first cost, and lower mainte-
nance costs.
The Best Ways To Save
• Fan system rightsizing
• Variable-speed drives
• Improved controls
• Energy-efficient motors
• Energy-efficient belts
If you are already planning to purchase replacement equipment, installing smaller
components is less costly than replacing with larger equipment.
Potential Savings
Potential energy savings from rightsizing, energy-efficient motors, and variable speed drives: 50—
85%
Source: Variable Air Volume Systems:
Maximize Energy Efficiency and Profits,
EPA 430-R-95-002.
An Easy Target
The fans that move the heated and cooled air through your building constitute eleven
percent of the total energy consumed by your facility, as shown in Figure 2. Any
reductions in their consumption can result in significant savings for you. A recent
EPA study found that almost 60 percent of building fan systems were oversized by
at least 10 percent, with an average oversizing of 60 percent. By rightsizing, you can
save an average of 50 percent in fan system energy. Moreover, these savings are
independent of any other improvements, such as installing energy-efficient motors.
Take Action!
1. Use the Fan System Survey at the end of this chapter to determine the
operating characteristics of your current fan system.
2. Enter survey data into a fan system software package to estimate potential
savings and economic benefits.
3. Upgrade your fan system and begin saving money and energy, immediately.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figure 2: Typical Electrical Energy Consumption
Space Heating
29%
Other
10%
Office
Equipment
13%
Refrigeration
3% Cooking
1%
Cooling
7%
Ventilation
11%
Water
Heating
4%
Lighting
'2%
Source: U.S. Department of Energy, Energy Information Administration, Energy End Use Inten-
sities in Commercial Buildings, Sept. 1994. DOE/EIA-05555(94)/2.
Air-Handling Components
The major components in an air-handling system (AHS) are fans, coils, ducts, and
dampers. These components must function well individually and together in order to
ensure efficient operation as well as occupant comfort.
Each component performs a task critical to the proper operation of your system.
Fans circulate the air and provide the pressure required to push it through ducts and
across heating and /or cooling coils. Ducts convey the conditioned air throughout
your building, distributing the air from the AHS to occupants and then returning it to
the AHS to be conditioned and circulated again. Dampers control the flow and mix
of returned and outside air through the ducts to the various parts of the building.
Fans
Fans are the heart of your building's air-handling system. Like a heart that pumps
blood through a body, they distribute throughout the building the conditioned (heated
or cooled) air, that your occupants need. There are two main types of fans,
centrifugal and axial.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Centrifugal fans (see Figure 3) are by far the most prevalent type of fan used in
the HVAC industry today. They are usually cheaper than axial fans and simpler in
construction, but generally do not achieve the same efficiency. Centrifugal fans
consist of a rotating wheel, or impeller, mounted eccentrically inside a round housing.
The impeller is electrically driven by a motor, which is usually connected via a belt
drive.
Figure 3: Centrifugal Fan
Air
In
Axial fans (see Figure 4) consist of a cylindrical housing with the impeller mounted
inside along the axis of the housing. In an axial fan, the impeller consists of blades
mounted around a central hub similar to an airplane propeller. As with an airplane,
the spinning blades force the air through the fan. Typically, axial fans are more
efficient than centrifugal fans.
Figure 4: Axial Fan
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Axial fan motors can be mounted externally as on a centrifugal fan. They can also be
belt driven. However, they are often driven by a motor directly coupled to the
impeller mounted within the central hub.
Ducts
like the arteries and veins in your body, ducts convey the conditioned air from the air
handling unit out through the building and return it back to be conditioned again. They are
usually constructed of sheet metal, and are insulated
Ductwork can either be round or rectangular. Rectangular duct is cheaper and more
common than round duct, as it is generally easier to route, design, and install. Round
duct, on the other hand, uses much less material, as it is the most efficient shape for
a given cross-sectional area. It is also naturally stiffer than a rectangular duct having
the same cross-sectional area. Round duct also creates less resistance as the air
moves through it, reducing fan power requirements.
Duct insulation helps prevent the warming of your chilled air and the cooling of
your heated air as it passes through the ducts. Ducts must be properly insulated to
prevent excessive energy loss. Commercial building codes typically require 1 inch of
insulation for ducts carrying hot or cold air. This requirement varies by jurisdiction,
please consult your local energy and / or mechanical codes. Proper choice of
insulation can also help reduce the transmission of fan and motor noise from your
HVAC system to the working spaces inside your building.
Dampers
Dampers serve to modulate the flow of air through the ducts to the various parts of
the building, reducing or increasing the flow of air depending upon conditions.
Dampers also serve to regulate the quantities of outside air allowed to enter the air
handling unit and mix with return air for ventilation purposes. Dampers can be
difficult to maintain and can affect occupant comfort as the space requirements
change and as the air-handling system ages.
Air-Handling System Types
Depending on the age and design requirements of your building, you might have one
or more of the following systems:
• Constant volume systems
— Reheat system
— Dual-duct system
— Multizone system
• VAV systems
ENERGY STAR? BatldingManaal
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Compared to older systems, current air-handling systems offer much more efficient
designs than may have originally been installed in your building. Today's VAV systems
can handle changing load requirements by varying the amount of air circulated, as
well as regulating the amount of cooled or heated air, to more accurately tailor
energy consumption to the actual climate control needs of the building's occupants.
Constant Volume Systems
Constant volume, also referred to as constant air volume, systems are installed in a
large number of buildings. The simplest of all the systems discussed, they circulate a
constant volume of conditioned air.
Reheat Systems
In a reheat system, a constant amount of air is cooled and recirculated (see Figure
5). This amount of air is designed to be able to cool all parts of the building at peak
cooling load. To cool at lighter loads or to heat the building, the circulated air, which is
\ cooled, is reheated before being distributed to the various zones.
Reheat systems are very inefficient because the same air is being cooled and then
reheated before it even reaches building occupants.
Dual-Duct Systems
Often found in buildings constructed during the 1960s and 1970s, dual-duct systems
are a relatively effective means of maintaining comfort, yet an extremely inefficient
method of conditioning air.
Figure 5: Constant Volume System With Reheat
Outside
Air
Reheat Coil (On)—!
Return
High Cooling Load
In this example, the room with the moderate cooling load is reheating its air from 55° to 60° F.
ENERGY ST^AE? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Dual-duct systems consist of two independent systems, one warm and one cool,
which circulate air in parallel sets of ducts through all sections of the building. Hot
and cold air are mixed in local mixing boxes in each zone or room and then fed into
that area. Depending on the temperature needs of the area, the mixture of hot and
cold air is adjusted until the desired temperature is reached. Unfortunately, with a
dual-duct system, you must pay to cool, heat, and circulate a volume of air that is
typically much larger than the actual volume required by your building.
Multizone Systems
Multizone systems are similar to dual-duct systems in that two streams of hot and
cold air are mixed to produce a desired temperature. But, whereas dual-duct systems
mix the air in individual boxes located at each area or room, multizone systems mix
air in large mixing boxes near the fans. This conditioned air is then fed to each zone,
with each zone, depending on its load, receiving air at a different temperature. As
with dual-duct and reheat systems, multizone systems are quite inefficient because
you must pay to heat and cool air simultaneously.
Variable Air Volume Systems
VAV systems vary the amount of circulated air in response to varying heating or
cooling loads. This reduces fan power requirements, which saves energy and costs.
VAV systems work either by opening or closing dampers or by modulating the airflow
through VAV fan-powered mixing boxes as loads in various zones of the building
change (see Figure 6). If, for example, more cooling in an area is required, the
damper to that area is opened wider, increasing the flow of cold air until the desired
temperature is reached. Conversely in this same example, if an area is too cool, the
damper is slowly closed, reducing the flow of cold air. Used in combination with
VSDs, this reduction in flow results in a reduction in the fan power needed, saving
energy. Because retrofitting an existing constant volume system to a VAV system
allows your system to turn itself down in response to changing demand, it is a
popular option for many building owners. Proper conversions to VAV systems include
the removal of constant volume dampers and typically reduce fan horsepower
requirements by 40 to 60 percent.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
i'ffare 6: VAV System
Flter
Outside
Air i
t
Supply Fan
/
©
55° C>
\ .X *\
Cooling f \——
Return coil
Air A
%. *
High Load
In a VAV system, dampers control the flow of chilled air to respond to changes in cooling load.
Thermally Powered VAVs
Thermally powered VAV systems, like standard VAV systems, regulate the volume of
air that a space (usually a room) receives based upon its temperature.
Thermally powered VAVs are ceiling-mounted diffusers, each with its own damper,
that replace standard diffusers. With an internal "thermostat" and a small damper,
they enhance the process of reducing airflow to a certain conditioned space when its
temperature is below the setpoint and increasing airflow when the temperature in that
space is too warm. In addition, thermally powered VAVs are now being produced
with individual controls, a feature that provides a level of control comparable to that
of a standard VAV system.
Thermally powered VAV systems also:
• Provide more comfort at less cost.
• Are a viable alternative to VAV fan-powered mixing boxes in terms of costs,
benefits, and lessened disruption during retrofit construction.
Best Opportunities
Comparison: VAV Systems Vs. Constant Volume Systems
The conversion of your older constant volume reheat, multizone, or dual-duct
system to a modern, energy-efficient variable air volume system is a task to be
undertaken with serious consideration and expert analysis. This would normally
require the services of an engineering firm.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
As discussed earlier, VAV systems are more energy-efficient than constant volume
systems as VAV systems can reduce airflow in response to decreasing demand. You
are also cooling only the amount of air that is required to meet demand, rather than
meeting demand by simultaneously heating and cooling large volumes of air.
Are Your Fans Oversized?
If your fans are oversized, fan rightsizing can be profitable. It can be implemented
separately or in combination with energy-efficient motors and VSDs. In general,
rightsizing with an energy-efficient motor, energy-efficient belts, and a VSD is the
best alternative.
Advantages Of A Rightsized System
A rightsized system saves you energy costs; however, there are other advantages to a
rightsized system that you might not have thought of:
• Lower First Costs
As the capacity required from your fan system is reduced, your system can be
more accurately tailored to the new air flow requirements. By installing smaller,
more energy-efficient equipment that meets these requirements, first costs are
also reduced.
• Comfort
If your fan system supplies too much air to your occupants, not only are you
wasting energy, but you could also be affecting their comfort. Too much air can
result in disturbing drafts, increased humidity, and noise.
• Equipment Life
Prolonged operation of an oversized motor with a VSD at very low speeds can
reduce the useful life of motors and other equipment. Properly sized, smaller
capacity equipment will be more suited to operation at reduced capacities.
Rightsizing Your Fan System
When rightsizing your fan system, the type of system in use-
VAV—will slightly affect the methods you use.
constant volume or
Regardless of whether you have a constant volume system or a VAV system, when
reducing your fan airflows, make sure that you maintain the proper amount of
outside air to ensure occupant health and comfort (see Stage Three—Other Load
Reductions, Load Sources). Consult your local building codes for information about
required outside air quantities.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
VAV Systems
While VAV systems are more energy-efficient than constant volume systems, the
potential for rightsizing may still exist. Your building engineer may be able to
determine if your VAV fans are oversized by using one of three methods: measuring
the fan motor current draw (amperage), checking the fan control vanes and dampers,
or measuring fan system static pressure.
Measuring Amperage
1. Measure the fan motor amperage. For a VAV system, measure the amperage
when your cooling system is operating under a peak load (a hot, humid day, for
example).
2. Read the full-load amperage off the motor's nameplate or from the Operations
& Maintenance manual.
3. Compare these two numbers. If the measured amperage is lower than 75
percent of the full-load amperage, the motor is oversized.
Checking Vanes and Dampers — Check the position of the fan control vanes or
dampers when the cooling system is operating under a peak load (a hot, humid day,
for example). If the vanes or dampers are closed more than 20 percent, the fan is
oversized.
Measuring Static Pressure
1. Measure the static pressure of the main supply fan system on a hot, humid day.
Make sure that all fan vanes and dampers are fully open, and that all VAV boxes
are fully open.
2. Compare your static pressure reading with the static pressure setpoint. If the
static pressure reading is less than the setpoint and the space in your building is
sufficiently comfortable, the setpoint can be adjusted to the lower static pressure.
Constant Volume Systems — If it is not economically feasible to replace your
constant volume system with a VAV, rightsizing your constant volume system is
generally a profitable choice. However, in determining the potential for rightsizing,
your building's engineer is typically limited to just one method—measuring fan system
static pressure.
Measuring Static Pressure
1. Measure the main supply fan system static pressure on a hot, humid day. Make
sure that all fan vanes and dampers are 100-percent open.
2. If the measured static pressure is greater than the design pressure (found in
your building's mechanical drawings), your fan is probably supplying too much air
and is a good candidate for rightsizing.
ENERGY ST^AE? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Three Ways To Rightsize - If you have assessed that your VAV or constant
volume system is oversized, you can now rightsize it to match your building's actual
flow requirements. Rightsizing your fan system can be accomplished by installing
larger pulleys (sheaves), adjusting static pressure, and/or replacing the fan's motor
with a smaller, energy-efficient motor.
• Smaller, Energy-Efficient Motors
Once you have rightsized the fan flow rate, your existing motor is probably too
big for the brake horsepower required. Replace the existing, oversized motor
with a smaller, energy-efficient motor that matches the load. For example,
rightsizing a 75-hp standard efficiency motor to a 50-hp energy-efficient motor
will reduce your motor energy consumption by about 33 percent.
• Larger Pulleys
Replacing an existing belt-driven pulley with a larger one will reduce its speed,
saving energy costs. Reducing a fan's speed by 20 percent reduces its energy
consumption by 50 percent.
Note: The new pulky should operate the fan at a reduced speed that matches peak had
requirements.
• Static Pressure Adjustment (VAV Systems Only)
Reducing static pressure in your VAV system reduces the fan horsepower
consumption. By gradually reducing the static pressure setpoint to a level low
enough to keep occupants comfortable, you will reduce energy consumption.
Example: VAV System Static Pressure Reduction
A VAV fan system currently operating at a static pressure of 6 inches of water (gauge) is found
to operate satisfactorily at 4 inches. This 33 percent reduction in static pressure with its ac-
companying reduction in flow will result in an energy savings of approximately 45 percent.
Estimating Potential Savings
You can estimate the expected benefits of rightsizing by collecting data listed in the
Fan Survey (see Appendix) and calculating savings from right-sizing your fan systems
using a commercially available fan analysis software program.
Project Management Considerations
The first consideration in rightsizing your fan system is to determine which
components will be involved in the process. You have the choice of replacing pulleys,
adjusting static pressure, installing smaller energy-efficient motors, or a combination
of these.
Note: Changes to one of these components mil affect the others! Be sure to perform an analysis of
the options and their effects on the system before proceeding to ensure an effective reduction.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
The engineer verifying the rightsizing potential will need the information you
collected in the Fan Survey, as well as the types and efficiencies of the air-handling
units, fans, and pulleys in your building.
If your company does not have a qualified engineer on staff, hire a consulting
engineering firm to verify your choices.
Once the potential for rightsizing is verified, qualified personnel should implement
the changes—a controls technician should adjust static pressure, an electrician should
replace motors and drives, and HVAC technicians should replace fan pulleys and
belts.
Variable-Speed Drives
Variable-speed drives (VSDs) are an efficient and economical retrofit option and
should be considered for all VAV systems. VSDs allow the motor speed of your
equipment to vary depending on actual operating conditions, rather than operating at
one speed. Varying the speed of your fans allows them to match more closely the
actual load required. As indicated in Figure 7, reducing a fan's speed by 20 percent
can reduce its energy requirements by nearly 50 percent. Installing a VSD on your
fan motor allows the fan to automatically match this reduced capacity, slowing down
in response to reduced demand, thereby saving energy.
A VSD is not actually a motor, but rather an electronic device that varies the
frequency of the electricity to the motor. It is installed "upstream" of the motor,
between the transformer and the motor.
A recent EPA study (Variable Air Volume Systems Maximize Energy Efficiency and Profits,
EPA 430-R-95-002) showed that VSDs can greatly reduce the energy used by the
same fan operating under similar airflow volumes and static pressure conditions.
Overall, the study indicated that VSDs provided an average energy savings of 52
percent.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Figure 7: VSDs Induce Maximum Tower Input
100
3
Q.
C
- 80
8
o>
o
Q.
E
3
'><
(0
C
0)
§ 20
Q.
Reduces Required Power 50%
Reduces
Speed 20%
10 20 30 40 50 60 70
Percent Speed
80 90 100
Source: Electric Power Research Institute.
VSDs make economic sense when installed on motors that operate many hours per
year at fluctuating loads, and especially on larger motors.
Table 1: VSDs: Installed Cost For Various Size Motors
hp Installed Cost
5
7.5
10
15
20
30
40
50
60
75
100
Source:
$2,975
$3,400
$3,575
$4,225
$4,925
$7,225
$8,625
$11,100
$13,200
$17,700
$19,400
Adapted from R.S. Means, Electrical Cost Data — 1997 Edition.
Controls
Modifying the way your system operates, not just the system itself or its components,
can also save energy. By taking advantage of such concepts as economizer cooling
and night precooling, you can significantly reduce your cooling costs.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Optimized Scheduling
An optimum start and stop procedure for your system is a common-sense control
philosophy that can result in significant energy savings. Normally, your system is set
to automatically turn itself on and off based upon the expected occupant working
hours.
For example, your cooling might come on at 6 A.M. and shut off at 7 P.M. Adjusting
these times for varying seasons will reduce your energy costs. In the spring and fall
seasons, where cooling is required but the peak temperatures are typically lower than
the summer temperatures, you can set your system to come on later in the morning
and shut off earlier in the day. Of course, you can also shut down your system on
weekends.
Pressure Reset
If you have installed a VSD on your fan system, pressure reset is a method by which
you can increase your system's energy savings. Pressure and flow are related.
Reducing pressure supplied by your fans also reduces the flow supplied, in turn
reducing the power required. By reducing the duct pressure level when less air is
required, instantaneous fan energy savings of 50 percent can be achieved above and
beyond the application of a VSD. The desired setpoint can be found by gradually
reducing the fan speed each day until the pressure is as low as possible, but occupant
space is still comfortable. It is possible to have two or more pressure settings; for
example, one for daytime and one for evening or one for summer and one for
winter.
Case Study: Economizer Cooling
The majority of conventional air-handling units are enabled to provide 100-percent outside air.
However, at one 200,000-sf office building in a Boston suburb, it was noticed that air condi-
tioning compressors in the rooftop units operated on sunny days even when outside air tem-
perature was as low as 35° F. The reason was that solar-heated interior air had no way to
escape from the building, so that the rooftop units, even with outside air dampers wide open,
could not provide enough outside air to cool the building without mechanical refrigeration.
The solution was found by installing power exhausts in the rooftop units, which exhausted all
indoor air outside when the building was in economizer cooling mode. Roughly 1,000 hours
per year were found to have proper conditions for free cooling. After installation of the
power exhausts, cooling compressors only operated when outside air temperature was above
55° F. The installation cost $75,000 and paid for itself in under 4 years.
Economizer Cooling
As discussed in Other Load Reductions, air-side economizers consist of a set of
dampers, filters, and sometimes a fan on the supply air side of the air-handling
system. The damper is controlled so that when outside air is cooler than return air,
the outside-air damper opens, allowing the outside air to be drawn into the building.
When it is hotter and more humid outside than the return air, the economizer
damper closes to its minimum setting, which is the minimum amount of fresh air
required according to ASHRAE standards (see Stage Three, Load Sources).
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Demand Ventilation
Standard ventilation specifications are based on a certain volume of outside air in
cubic feet per minute (cfm). ASHRAE 62-1999 specifies a minimum of 15 cfm per
occupant. Tlhis ventilation level, however, should be understood as an average value
to be applied to a whole building. In other words, if your building holds 3,000 people,
your air-handling system should provide 15 cfm/person x 3,000 people = 45,000
cfm of outside air. This assumes that the occupants of your building are also equally
distributed.
In some areas, such as cafeterias, auditoriums, conference rooms, and gymnasiums,
the area could be empty during some portions of the day but full at others to the
point that indoor air quality would suffer. For example, in a cafeteria at lunchtime,
the air-handling system might not supply enough outside air to meet demand;
conversely, for most of the day, the air-handling system is supplying outside air to an
area with no people.
The solution to this problem is demand ventilation. By only supplying outside air
when and where it is needed, you can ensure proper air quality while not wasting
energy supplying the area with outside air during other parts of the day. A popular
way to do this is by monitoring the concentration of CO2 in the area. As mentioned
before, CO2 concentration is a good indicator of an area's population. As more
people exhale, the concentration of CO2 increases. By controlling the quantity of
outside air based on a CO2setpoint, you can ventilate an area on a demand basis.
When CO2 concentration rises, dampers are opened and more outside air is allowed
to flow into the area until the concentration decreases to acceptable levels. Keep in
mind that CO2 concentration rates do not indicate the levels of other potential VOCs
contained within the space and that additional ventilation may be required in order to
satisfy the acceptable indoor air quality requirements (consult your local building
codes for proper ventilation rates).
Energy-Efficient Motors
Depending on their size, typical electrical motors are 75 percent to 95 percent
efficient, with larger motors being more efficient than smaller ones. The remaining 5
percent to 25 percent of the wasted power is lost as heat to the surrounding area.
Energy-efficient motors are designed to convert a greater amount of electrical
energy into useful work. After completing the other stages, you will have reduced the
heating and cooling loads in your building, allowing for the installation of smaller
motors that better match the reduced power requirements. By installing motors that
are smaller and mote efficient, you can save further energy costs.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Table 2: Comparison Of Standard Efficiency Motors And
Energy-Efficient Motors
(1,800 RPM Totally Enclosed Fan-Cooled Motor)
Standafd- Energy-
Efficiency Efficient
hp Motor Motor
5
7.5
10
15
20
30
40
50
60
75
100
83.3
85.2
86.0
86.3
88.3
89.5
90.3
91.0
91.7
91.6
92.1
90.2
91.7
91.7
93.0
93.6
94.5
94.5
95.0
95.4
95.4
95.4
Note: Older standard-efficiency models have even lower efficiencies than those shown in this
table.
Source: Adapted from California Energy Commission, Washington State Energy Office, U.S. De-
partment of Energy, and E SOURCE, Space Cooling Technology Atlas.
Economic Benefits
The savings realized by installing energy-efficient motors can be particularly
attractive for equipment motors that run most or all of the day and have a higher
capacity, such as a fan motor.
Energy-efficient motors achieve their efficiencies from improved internals (windings,
stators, etc.). Higher efficiency means less waste heat is generated. While excessive
heat shortens motor life over time, less heat prolongs lubricant life. Also, the higher
thermal mass of energy-efficient motors allows them to tolerate heat better than
standard motors. Altogether, energy-efficient motors generally last longer and require
less maintenance than standard motors.
Considerations
Repair (Rewind) Vs. Replacement
Occasionally, like any type of equipment under constant use, motors fail. When they
do, many people make the assumption that they should replace the unit immediately
rather than repair it. Although it is generally more economical to replace, rather than
repair, a failed motor, this is not always the case. Rewinding a failed motor can be
more cost effective if one or more of the following situations applies:
• The motor is larger than 125 hp.
• The motor operates less than 2,000 hours per year.
• The failed motor is an energy-efficient motor.
ENERGY STAR® BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Premium Efficiency Vs. High Efficiency
Many motor manufacturers have three lines of motors—standard efficiency, high
efficiency, and premium efficiency. Adding to the confusion, many other
manufacturers offer just two lines of motors, calling their standard efficiency motors
"high efficiency" and their energy-efficient motors "premium efficiency."
Understanding this practice will help you choose the combination of motor efficiency
and cost that best suits your specific needs.
Shaft Alignment
In typical fan system configurations, the motor and the fan each have shafts, which
are connected with a belt or belts and two pulleys. If the pulley faces are not square
with each other, then the belt and shafts are not in alignment. Improperly aligned
shafts can not only result in poor efficiency and higher operating costs, but also can
lead to premature failure and increased maintenance costs. Whenever you replace or
rewind a motor, be sure to pay close attention to the shaft alignment.
Energy-Efficient Belt Drives
Belts are often used to transfer power from the motor to the fan system being
driven. Standard V-belt drives can be found in the majority of belt applications. They
are the lowest cost option of the belt family. The tradeoff, as usual, is reduced
energy efficiency.
• V-belts, when new, can typically achieve efficiencies in the 90 to 95 percent
range. A worn belt, however, can considerably reduce the efficiency by slippage
caused by slackening and worn grip surfaces.
• Cogged V-belts are similar to standard V-belts, except that the normally flat
underside has longitudinal grooves in it, allowing better grip and less slip than
standard V-belts. They typically offer a 2 percent to 5 percent efficiency bonus.
• Synchronous belts combine toothed belts with grooved pulleys, minimizing slip
and improving efficiency to a range of 97 percent to 99 percent.
Economic Benefits
Drive belts should be a standard replacement part in your building's maintenance
program, requiring replacement every few months. Energy-efficient belts can easily
be incorporated into your standard maintenance program, and the savings generated
greatly outweigh the slight increase in cost per belt.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Additional Considerations
Ventilation Requirements
As discussed in Other Load Reductions, building codes based on standards set by
ASHRAE dictate minimum ventilation rates. Code-mandated rates have changed
significantly over the years in response to events and new understanding about the
impact of outside air, energy consumption, and occupant comfort.
Testing, Adjusting, and Balancing Firms
One issue to consider: After implementing some of the modifications outlined,
your HVAC system will most likely exhibit different operating characteristics than
before. Normally, the engineer or contractor who performed the work will be
responsible for what is called the testing, adjusting, and balancing, or TAB, of the
modified or new system. TAB involves analyzing the various flows of air, chilled
water, hot water, steam, etc., and ensuring that distribution of heating and cooling
throughout the building meets the required specifications as outlined in the contract
documents. Recent developments in the building heating and cooling industry have
led to the introduction of independent TAB firms. Under contract to the building
manager, they serve as a third party to ensure accuracy of the TAB measurements
and are worth retaining if further oversight is desired.
Upgrading Of Fan System
]C Penney
Atlanta, GA
The air distribution for one of JC Penney's 155,000-sf stores was provided by five air-han-
dling units located in a penthouse equipment room. Two return fans, also located in the
penthouse, vented air from the first and second floors through ductwork and back to the
air-handling units. The air-handling units supplied conditioned air through ductwork to dif-
fusers throughout the building. The fans operated at two speeds, high and low, each manu-
ally controlled with selector switches as well as on-off automatic-function switches. The
fans usually operated at the high-speed setting, although they were cycled occasionally to
conserve electricity. In an effort to reduce energy consumption, tests were conducted to de-
termine the airflow from each of the fans while operating at high speed. Data collected in-
dicated that the actual airflow for each air-handling unit was less than the design airflow;
therefore the fans were larger than necessary for this facility. The testing also revealed that
an accumulation of dirt on the cooling coils in air-handling units 1 and 2 was restricting air
flow and wasting fan energy. The QuikFan software developed by EPA was used to estimate
the energy savings potential of the various Stage Four upgrade options. Measurements of
each fan motor indicated that the maximum load was less than the horsepower rating.
Another potential energy saver was minimization of the outside air brought into the building
for ventilation. This air had to be heated or cooled, which required energy. By monitoring
carbon dioxide levels in the building it was felt that the air intake could be safely reduced to
the minimum quantity necessary.
JC Penney decided to install variable-speed drives on the supply-air and return-air fans in the
building to bring the fan capacity nearer the actual load and to install carbon dioxide sensors
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
that would enable the system to minimize the intake of air. The large open areas in the store
made it impractical to install variable air volume boxes that control the speed of the fan mo-
tors with pressure sensors. Space thermostats were therefore used to regulate fan speeds di-
rectly. Before installation of the variable-speed drives, the fans cycled on at maximum
electrical consumption and then cycled off regularly. The variable-speed drives eliminated this
inefficient constant cycling. Peak power use was therefore less than the maximum, with pro-
jected electric demand savings of 36 kW per month.
The total cost of installation of the variable-speed drives and the carbon dioxide sensors was
$17,000, which is projected to save 138,833 kWh of electricity at an annual savings of
$9,726. The payback for this upgrade of the fan system is 1.75 years, and the internal rate of
return is 56.6 percent. JC Penney was therefore able to realize substantial annual savings with
a relatively low investment, and the savings continue year after year.
Summary
Fan Systems illustrates the many options that are available to you to save on your
building's energy costs. To recap:
• Measure your loads.
• Rightsize your fan system to match actual loads.
• Install rightsized, energy-efficient motors where possible.
• Install VSDs where practical.
• Install energy-efficient belts.
• Investigate options available for improving the control of your fan system.
Next Steps
1. Using the Fan System Survey provided in the Appendix, record information on
your various fan systems and measure your loads.
2. Enter this data into a commercial fan sizing software program to estimate what
you could save.
3. Using a qualified engineering firm, perform a more detailed assessment of your
system to investigate further savings.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
FanSysten Suivey
FacfliyName
FanSystHn Bfoimatbn
Name
OD)
Fan
System
Type
Operati-
ng
Schedufe
FanFbw
Contol
System
Duty
Cyde
Motor Bfoimatbn
Namepbte
Hoisapow-
er
EfEcmcy
Hoisepower
@ 1001 cii
Date
0 paatbnal Bfoim atbn
ftstaM
Capacity
CoiLcad
@ Peak
(tons)
Fan Fbw @
Peak
(cfin)
ENERGY ST.AR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
HEATING AND COOLING SYSTEM UPGRADES
Overview
Heating and cooling systems are the largest single consumers of energy in buildings.
These systems condition the air within a building so that occupants are comfortable.
Heating and cooling systems consist mainly of chillers, boilers, cooling towers, and
pumps. There are central heating and cooling systems, and unitary systems that
combine heating and cooling. Opportunities exist for improvement to both central
and unitary systems.
The heat flow diagram (Figure 1) illustrates how, you can capitalize on the heating,
cooling, and electrical load reductions you have realized through your upgrades in the
other stages of an integrated approach. The cumulative effect of these various load
reductions now allows you to install heating and cooling systems that are both more
energy efficient and properly sized to accommodate appropriate loads.
Heating and Cooling System Upgrades chapter will help you identify the
opportunities for improving the performance of your heating and cooling system
based on the type of system that you have in place. "Best Ways to Save" and "Take
Action" provide checklists for cooling and heating upgrade opportunities and
benefits. The Heating and Cooling Survey Appendix will assist you with evaluating
the current condition of your systems and opportunities for improvement.
Heating and Cooling System Strategy
Measure your heating and cooling loads.
Rightsize your heating and cooling systems.
Replace your chillers with new, more energy-efficient, non-chlorofluorocarbon (CFC) models.
Upgrade your heating and cooling system components.
Install variable-speed drives (VSDs) on your pumps and cooling tower fans.
• Optimize operation of your heating and cooling systems.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Figure 1: Heat Flow In Buildings
PLANT
LOADS
Heat Flow In Buildings: Building Systems Interactions
Figure 2 shows the interaction of heating, cooling, and electrical loads with the HVAC
equipment. Arrows indicate heat flow pathways. Reducing heating, cooling, and
electrical loads reduces the demand on HVAC equipment, thus saving energy.
The Best Ways To Save
• Cooling System Upgrades
— High Efficiency Components
— Cooling Tower Improvements
— Free Cooling
— VSD Pumping
— Controls
• Heating System Upgrades
— High Efficiency Components
— Controls
Table 1: Potential Cooling and Heating Energy Savings
System Typical Saivii/
Cooling
Central Chiller
Unitary A/C
Heating
Boiler
Furnace
Adapted from: E SOURCE, Sfiacc
15-35%
20-35%
10-30%
5-25%
~,g Technology Atlai, and E SOURCE., $pa>?s
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Use An Integrated System Approach
The conventional approach to upgrading a heating and cooling system is to address
each component of the system individually. However, addressing the interaction
between the components using an integrated system approach ultimately results in
a more energy-efficient system. In addition, compared with assessing components
individually, assessing upgrade opportunities for whole systems consumes less time,
and therefore less money, in the long term. Heating and cooling system components,
particularly in central systems, interact with each other extensively. For example,
chillers operate more efficiently if they receive cooler condenser water. However, the
cooling tower fans consume more energy to provide cooler condenser water.
Optimizing the energy use of the cooling tower/chiller system is one example of
using an integrated system approach that can improve your energy performance and
save money.
Heating and Cooling System Energy Use
Cooling may use as much as a third of the electricity consumed in a typical building.
Heating systems use natural gas or oil as the primary fuel, but may also use
electricity. Heating and cooling systems condition the air within a building so that
occupants are comfortable. These systems consist mainly of chillers, boilers, cooling
towers, and pumps. Cooling systems generally have higher space conditioning
capacities than heating systems, because a large portion of the building's heating
requirements is supplied by waste heat from the people, lighting, and office
equipment. The proper design and operation of these systems can translate into
significant savings. If you have followed the steps outlined in the other stages, your
cooling load may now be low enough to justify retrofitting or rightsizing your cooling
system.
Advantages Of A Rightsized System
In addition to reducing energy consumption and costs, heating and cooling upgrades
will:
• Reduce noise.
• Lower first costs for equipment.
• Reduce equipment footprint.
• Eliminate CFCs.
• Optimize equipment operation
Take Action!
1. Measure your existing heating and cooling loads. To begin, see the Heating and
Cooling Survey (Appendix). Contact an engineering services firm for the more
complex load measurement tasks.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
2. Total the reduction in cooling load achieved by your efforts from the previous
stages. Calculate the proper size for your chiller. See the Heating and Cooling
Survey (Appendix).
3. Use the information from the Heating and Cooling Survey to investigate options
for upgrading your chiller plant.
4. Contact vendors and/or an engineering consultant who can recommend specific
components and design upgrades for your heating and cooling system.
Central Cooling Systems: Best Opportunities
Cooling systems consist of various components that must work together to operate
at highest efficiency while ensuring proper occupant comfort. Improvements to any
system must, of course, incorporate improvements to its individual pieces of
equipment. However, these changes must be viewed as part of an integrated system
approach. To improve your building's overall efficiency, modifications in the design
or operation of one set of components will affect, the operation of other equipment
within the system.
There are four types of mechanical compression chillers—centrifugal, screw, scroll,
and reciprocating, different applications call for different chiller types. Generally,
older chillers have efficiencies ranging from 0.8 to 1.0 kW/ton; they often consume
approximately twice the energy of newer, more efficient chillers. Today, centrifugal
chillers have efficiencies as low as 0.45 kW/ton. Table 2 shows the efficiency ranges
in which these chiller technologies.
Eliminating CFCs:
Headache Or Opportunity?
• CFC refrigerant production was phased out by law in 1996. As existing stock of CFCs
dwindle and become more expensive, conversion to or replacement with non-CFC chillers is
becoming more cost effective.
• Existing, relatively new chillers may be cost effective to retrofit for non-CFC operation.
• Replacing an older chiller with a new, non-CFC chiller is an excellent opportunity to invest in
a high efficiency unit. First cost for the installation will be reduced by installing a smaller
chiller made possible by the implementation of all upgrade stages.
Chiller Retrofit
If the existing chiller is less than 10 years old, retrofitting the chiller to operate on
non-CFC refrigerants at the newly reduced loads will probably be your most
profitable option. This postpones investing in a new chiller. When you are replacing
refrigerant, use HCFC-123 in place of R-ll and HFC-134a in place of R-12.
Retrofitting may involve replacing orifice plates, impellers, gaskets, or even the
compressor. The specifics of the retrofit depend on the type of chiller and its
manufacturer. Many manufacturers offer retrofit kits for their chillers. Contact the
manufacturer of your chiller to determine its requirements.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Due to their inherent properties, non-CFC refrigerants are not as efficient and thus
will affect the chiller efficiency by reducing its cooling tonnage at current or even
increased levels of energy consumption. However, the reduced cooling loads
obtained through performing a comprehensive upgrade will offset this loss.
Table 2: Common Chiller Types and Efficiencies
Chiller
Type
Full-load
Efficiency
(kW/ton)
Centrifugal
Screw
water-cooled
air-cooled
Reciprocating
water-cooled
air-cooled
100-1,500+
40-1,100
1-400
0.45-0.68
CFCs Are On The Way Out
Eighty percent of today's existing chillers are centrifugal chillers that use R-ll as refrigerant.
The newer, non-CFC alternative to R-ll is HCFC-123. Some centrifugal chillers use R-12; its
non-CFC alternative is HFC-134a. Unitary A/C units typically use R-22, which will be phased
out in the future.
Phase-Out Dates
1996
2010
2020
2030
2030
Source :ASHRAE Fund amen
Refrigerants
R-ll, R-12,
R-500,HCFC-152A,
CFC-114
HCFC-22
HCFC-123
HCFC-22
HCFC-123
talsliandbook,2001..
Action
Production of these refrigerants
has stopped. Equipment
using these refrigerants is no
longer manufactured.
Manufacture of equipment
using this refrigerant has stopped
Manufacture of equipment
using this refrigerant has stopped
Production of this refrigerant
has stopped.
Production of this refrigerant
has stopped.
Chiller Rightsi^ing
Depending on the upgrades implemented in the previous stages, loads on your
cooling system (see Figure 2) likely have been reduced by at least 10 percent, and
perhaps by as much as 40 percent. Even if you haven't implemented upgrades,
design loads and actual building demand rarely match.
Chillers are frequently oversized, and those in poor condition suffer downtime and
significantly increased operating and maintenance costs. A new efficient and reliable
chiller may be more cost effective. Thus, you may want to consider rightsizing your
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
existing chiller with a new, smaller, energy-efficient one that matches the newly
reduced loads and uses compliant non-CFC refrigerants. This option is most
profitable when your existing chiller is more than 10 years old.
Figure 2: Typical Water-Cooled Chiller System
Condenser
Water
Pump
Chilled
Water
Pump
When you decide to replace an existing chiller with an energy efficient unit, be sure
to evaluate the initial operating and maintenance costs, size, and weight of the new
unit. Keep in mind that the energy consumption of a new high efficiency chiller
could range from 15 percent to more than 50 percent less than that of the existing
chiller.
While the new chiller must be sized for peak loads, be sure that it operates
efficiently at part-load conditions, because it is at part load that the chiller operates
most of the time. Many chiller manufacturers provide electronic copies of their
equipment specifications catalogs on CD-ROM. This information can be used to
identify the appropriate chiller for your facility, once you have analyzed the
building's peak load profile. An energy services professional or consulting engineer
can develop the new peak load profile.
To analyze the profitability of chiller upgrades, you will need to identify the
relationship between outdoor air temperature and the cooling load that the chillers
must meet. Consult the chiller manufacturer's specifications to prepare a load
profile for your building gathered using the Heating and Cooling survey
(Appendix).
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
To evaluate the chiller project, gather data about existing chillers, operating schedules,
utility rate schedules, cooling tower parameters, and water reset temperatures for the
condenser and evaporator.
Chiller Rightsizing Case Study: An ENERGY STAR Showcase Building
Mobil Corporation's 340,000-sf research and development building in Dallas, Texas, was up-
graded over a 1-year period as an ENERGY STAR Showcase Building. The original cooling capac.
ity of the building's chiller plant was 1,760 tons. During the first 10 years, the building's
cooling load had been projected to increase to 1,805 tons primarily from heat generated by the
increasing number of personal computers and related equipment. Prior to the Showcase
project, Mobil was planning to replace its three R-ll chillers with larger R-123 chillers, sized
to provide the additional cooling capacity. Using the ENERGY STAR Approach, Mobil identified
profitable opportunities to reduce the building's cooling loads. Upgrades in the five stages pro.
vided a total cooling load reduction of 212 tons—more than enough to eliminate the need for
larger chillers
Existing Cooling Capacity
Pre-Upgrade Calculated Peak Cooling Load
Upgrades Implemented
Lighting retrofit
Peak air flow to labs reduced 10 percent
ENERGY STAR computers, monitor shutoff devices,
window films
Variable-speed drives
Post-Upgrade Projected Peak Cooling Load
1,760 tons
1,805 tons
Reductions
45 tons
115 tons
38 tons
14 tons
1,593 tons
By committing to ENERGY STAR, Mobil was able to rightsize the three chillers with chillers that
were smaller than originally planned. Mobil thus saved money on the first cost of the chillers
and is reaping significant energy savings over the life of the chillers. The total cost of the
chiller plant upgrades was $641,000. This investment resulted in an annual cost savings of
$110,000, an annual energy savings of 10.4 percent, with an internal rate of return of 16.5
percent.
Mobil purchased the chillers before the tune-up and conversion of the return air system for lab
spaces. In hindsight, had it waited to purchase the chillers last, as prescribed by the ENERGY
STAR Approach, the lab return air conversion and tune-up would have reduced the peak cool.
ing load by up to 120 tons and 250 tons respectively.
Mobil's experience in upgrading its R&D facility confirmed one of the basic premises of ENERGY
STAR: systematically reducing cooling loads where profitable from tune-ups through fan sys.
terns generates opportunities to profitably install rightsized, high efficiency chillers.
Upgrading Chiller Components
Numerous components of a chiller system can be upgraded to improve system
efficiency and increase cooling cost savings.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Cooling Tower Improvements
Central cooling systems generate heat that must be rejected outside the building, a
cooling tower is commonly used for this purpose. All cooling towers function as large
heat exchangers, transferring heat from the condenser side of the chiller to the
outside air by spraying the hot water through a flow of outside air. This flow of
outside air is created with centrifugal or axial fans mounted at the lower end of the
tower in the forced-draft tower.
A more common type of tower, the induced-draft tower, utilizes a propeller fan at
the top of the tower to pull air up through the tower. The induced-draft tower offers
better aerodynamics and is generally more efficient than a forced-draft tower. The
forced-draft tower is generally quieter and requires less space than an induced-draft
tower, but operates at a lower efficiency. Both forced-draft and induced-draft cooling
towers (Figure 3) employ a surface contact medium or fill to increase contact surface
and improve the transfer of heat between hot water from the chiller and the outside
air.
Figure 3: Cooling Tomer
Forced Draft Tower Induced Draft Tower
Scaling, corrosion, and biological growth all impede tower efficiency and increase
maintenance costs from the resultant condenser fouling and loss of heat transfer.
Chemical treatment is generally used to mitigate these problems. However, new, non-
chemical water treatment technologies, such as ozone generators, magnetic systems,
and ultraviolet irradiation, are available. Ozone is a powerful oxidant and biocide that
can replace chemicals completely in some cases. Magnetic systems are designed to
cause scale-forming minerals to precipitate in a low-temperature area away from heat
exchanger surfaces, thus producing non-adherent particles. The precipitated particles
can then be removed by blowdown, mechanical means or physical flushing. The
effectiveness of a magnetic system can be diminished by a low ratio of dissolved
calcium to silica, by the presence of excessive iron in the water, or if it is installed in
close proximity to high-voltage power lines.
Two-speed fan motors in combination with fan cycling provide an improvement in
control and efficiency over fan cycling alone. VSDs provide the most efficient
method of control. Cooling tower fans offer similar energy-saving opportunities. Fan
power is proportional to the cube of the airflow rate; thus, a reduction of 20 percent
in fan airflow (and speed) will correspond to a reduction of 49 percent in fan power.
ENERGY STAR® EuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Free Cooling (Water Side Economizer)
Under the right conditions, free cooling or a water side economizer system can
generate significant energy savings. In cooler, drier climates, water side economizers
can provide over 75 percent of the cooling requirements; in warmer climates they
may provide only 20 percent. Although air side economizers, as discussed in Stages
Three and Four, are typically less expensive, you should also consider using a water
side economizer.
Several methods of free cooling are available. The most common method is a type
of indirect free cooling that uses a separate heat exchanger, typically of the plate-
and-frame type. It allows for a total bypass of the chiller, transferring heat directly
from the chilled water circuit to the condenser water loop (see Figure 4).
A less common method is direct free cooling, in which the condenser and chilled
water circuits are linked directly without the use of a separate heat exchanger. A
disadvantage of using direct free cooling is that bacteria present in the cooling tower
water system (described above) may contaminate your chilled water circuit. You can,
however, install filtration systems or strainers to minimize this risk.
Facilities that require year-round cooling from high sensible heat gains would most
likely benefit from direct free cooling. A large computer room or data center cooled
with a central chilled water system would be a promising application.
When ambient outdoor conditions are ideal (that is, when the wet-bulb temperature is
low enough), the chiller can be shut off and the cooling load may be served
exclusively by the cooling tower without the energy-intensive mechanical
refrigeration. The resulting reduction in energy consumption can be dramatic.
••:•, Indirect Water Side
Condenser
Water
Pump
Plate And Frame Heat Exchanger
Chilled
Water
Pump
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Pumping System Upgrades
In buildings that use pumps to transport chilled water or condenser water, an
integrated system approach can reduce pumping system energy by 50 percent or
more. You can make your pumping systems more energy-efficient by:
• Replacing oversized impellers, pumps, and motors with rightsized pumps and
smaller, energy-efficient motors.
• Installing VSDs on pump motors.
• Converting single-loop configurations to primary-secondary loop configurations.
Hdghtsi^ing
Rightsizing pumps to accommodate lower maximum loads can result in energy
savings of up to 70 percent. The most cost-effective method is often trimming or
replacing an oversized impeller in an existing centrifugal pump. When pump
rightsizing, maximum design capacity of the new impeller or pump must be greater
than the measured maximum load for the system. Be certain that the new motor is
an energy-efficient model, sized to meet the maximum load, and recognize that
pump motors, like fan motors, come in incremental sizes (5 hp, 7.5 hp, 10 hp, etc.).
Calculate your energy savings from rightsizing by comparing rated energy curves at
various loads for old and new pump and motor sizes. Contact the pump
manufacturer or an engineering consultant for further assistance.
Variable-Speed Drives
Installation of VSDs will ensure that your pumps are performing at maximum
efficiency at part-load conditions. (See page 10 for an example of VSD savings
potential.) Similar to the fan systems, the power required to operate a pump motor is
proportional to the cube of the speed. For example, in a pump system with a VSD, a
load reduction that results in a 10-percent reduction in motor speed reduces energy
consumption by 27 percent [1 — (0.9)3 = 0.27].
ENERGY STAR? BatldingManaal
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Estimating Savings From Installing VSDs On Pumps
To estimate the annual energy savings you can gain from installing VSDs on pumps, you will need
to estimate run times for all part-load conditions, based either on monitoring or load calculaD
tions. Compare the motor horsepower of the existing motor with the motor horsepower of
the motor with a VSD installed under the part-load conditions. The difference in horsepower
(converted to kW) multiplied by the operating hours for the range of load percentages will
give you the expected energy savings in kWh.
Example:
A 30-hp VSD is installed on a chilled-water pump. The existing flow rate is 1,040 gallons per
minute (GPM), existing operating hours are 3,300 per year, and the pump's energy consumpD
tion is 66,900 kWh per year. The initial cost of the VSD is $7,175.
The VSD reduces average flow to 700 GPM.
Estimated new annual energy consumption:
(66,900)(700 - 1,040)3 =
20,400 kWh per year.
Estimated annual energy savings:
(66,900 - 20,400)($0.08/kWh) =
$3,720 per year.
Simple payback =
$7,175 - $3,720 = 1.9 years.
When installing VSDs, be sure to:
• Complete harmonic, power factor, and torsional analyses before installation.
• Conduct a coast-down test to compare mechanical resonance with speed
response.
• Ensure that maximum and minimum flow rates through the chiller can be met
with chiller pump upgrades.
Single-Loop Conversions
The rated minimum flow for chilled water through the chiller is typically 70 percent
of maximum, which also applies to VSD flow reductions. However, a primary-
secondary loop configuration, also known as a production-distribution configuration,
can allow for greater energy savings without compromising your chiller performance.
With the primary-secondary loop configuration (see Figure 5), chillers are equipped
with smaller chilled-water pumps, or primary pumps. These are constant-flow pumps
that operate with a lower pressure drop than in a single-loop configuration. Variable-
flow secondary pumps then distribute the chilled water through your building's end-
use air-handling devices and have the capability of reducing their speed at part-load
conditions.
When converting from a single-loop configuration to a primary-secondary
configuration, be sure to:
• Pipe the lower velocity chiller bypass water on the production side to flow into
the higher velocity chilled water return on the distribution side and not vice
versa.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
• Replace three-way valves at air-handling unit coils with two-way valves.
• Maintain maximum and minimum flow rates through the chiller.
Figure 5: Primary I Secondary Pumping Loop
Central Heating Systems: Best Opportunities
Boiler System Upgrades
Approximately 40 percent of all commercial buildings use boilers for space heating
(see Figure 6). Of these, roughly 65 percent are gas fired, 28 percent are oil fired,
and 7 percent are electric. The combustion efficiency of older boilers is generally
between 65 percent and 75 percent, although inefficient boilers can have efficiencies
between 40 percent and 60 percent. Energy-efficient gas- or oil-fired boiler systems
can have efficiencies between 85 and 95 percent.
Figure 6: toiler Components
Combustion Gas
Fire
Tubes
Burner
Furnace
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Boiler system energy consumption can be reduced by 10 to 30 percent. Improve
your boiler system's efficiency by either:
• Replacing your existing boiler system with a new, rightsized, more energy-
efficient boiler system.
• Retrofitting your boiler so that it can perform more efficiently.
Boiler
The best opportunities for energy savings come with replacing an old or inefficient
boiler with a more efficient boiler system. Energy-efficient boilers have increased
heating surface areas and improved controls for fuel and airflow over the range of
load conditions. Before replacing your boiler:
• Determine your building's heating load and rightsize your boiler
accordingly.
• Plan to rightsize your boiler with an energy-efficient model.
• Determine the applicability of converting from a single-boiler system to a staged
system of smaller, energy-efficient boilers operating in combination.
To determine whether you should replace your boiler system, you need to
understand your building's heating load and your existing boiler's efficiency. Calculate
the energy savings from replacing a boiler by comparing rated energy consumption
at various loads for the old and new boiler systems. Contact the boiler manufacturer
or an engineering consultant for further assistance.
Boiler Retrofit
Retrofitting existing boilers can dramatically improve the peak- and part-load
efficiency of your boiler and extend the useful life of your heating systems. Your
best options include:
• New Burners — Efficient burners improve fuel combustion and reduce
emissions of nitrogen oxide.
• Temperature/Pressure Reset —
Temperature and pressure reset controls provide significant energy savings by
minimizing fuel waste. Reset controls match the supply of steam with the
demand for heat instead of supplying steam at a higher pressure than is needed.
The system water temperature is reset based on the outdoor temperature. If
outdoor temperature increases, the system water temperature is lowered.
• Boiler Economizer — A boiler economizer captures waste heat in the exhaust
flue gases and uses it to preheat the boiler feedwater. When natural gas fuels the
boiler, it is important to maintain the stack temperature at a minimum of 250° F
to avoid condensation of the water vapor in the flue gases. The figure below
shows the percentage of fuel saved as a function of the percentage of excess air
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
for different stack temperatures from a gas-fired boiler. For example, with the use
of an economizer, a boiler operating at a stack temperature of 500° F and 80
percent excess air would realize a 7 percent fuel savings (see Figure 7).
• Baffle Inserts—Baffle inserts induce combustion gases to flow in a turbulent
spiral pattern, which increases the efficiency of heat transfer.
Figure 7: Boiler Economizer Fuel
25 -
20
in
D>
| 15
to
C/5
ffl
3
10
800° F
20 40 60 80 100 120
Excess Air (%)
140 160 180
Source: Turner, E •• •:•.. ':'• ':- j^f^^il- Handbook, 2nd ed.
As discussed in Recommissioning, improved operation and maintenance are
important parts of your overall strategy and can provide significant energy savings.
An annual tune-up, improved water treatment, and a preventative maintenance
program can reduce boiler energy waste by as much as 15 percent.
Furnace Upgrades
Furnaces are heating plants that produce heat for the purpose of providing thermal
comfort for your building. The heat source can be fuel oil, natural gas, electricity,
coal, or wood. The main components of a warm-air furnace are the heat exchanger,
fuel burner, blower or fan, controls, and housing.
An integrated system approach can reduce your furnace energy consumption 5
percent to 25 percent. You can make your furnace energy-efficient by:
• Replacing your existing furnace with a new, rightsized, energy-efficient furnace.
• Retrofitting your furnace with additional controls so that it can perform more
efficiently.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Furnace 'Bdghtsi^ing
Standard combustion furnaces have a steady-state efficiency of about 80 percent.
High efficiency furnaces built with condensing heat exchangers have a steady-state
efficiency as high as 94 percent. If your furnace is more than 10 years old, you
should:
• Measure your heating loads.
• Evaluate your existing furnace in terms of efficiency and capacity.
• Determine the benefits of installing a new, rightsized energy-efficient model.
Furnace Retrofit
Retrofitting existing furnaces can significantly increase your energy savings. Your best
options are to:
• Install new burners—Efficient burners improve fuel combustion and reduce
emissions of nitrogen oxide.
• Install two-stage setback controls—In electrically heated spaces where the
temperature is reduced during unoccupied periods, the electric demand needed
to bring the space back to its original temperature can be significant. In this case,
if your electric rate structure includes demand charges, install a two-stage
setback thermostat with staged supplemental heat and a programmable demand
limiter to prevent demand peaks in the morning. Consider alternatives to
resistance heating to reduce heating costs and overall impact on the environment.
As discussed in Recommissioning, improved operation and maintenance of your
systems save energy—often in significant amounts. As with boiler systems, an annual
tune-up and a preventative maintenance program are crucial to achieving and
sustaining these savings.
Unitary Systems: Best Opportunities
Unitary systems are factory-assembled cooling, or combined heating and cooling,
systems. Cabinet- or skid-mounted for easy installation, typical units generally consist
of an evaporator, blower, compressor, condenser, and, if a combined system, a
heating section. The size of the units ranges from approximately 1.5 to 130 tons.
Typical unitary systems are single-packaged units, split-system packaged units, heat
pump systems, and water-source heat pump systems. Compared to central chiller
plants, unitary systems do not last as long (only 12 to 15 years) and are less efficient.
Unitary systems are generally used in one-, two-, or three-story buildings that have
small cooling loads, such as retail spaces, small office buildings, and classrooms.
Generally speaking, it is not feasible to convert a building from packaged units to
central chilling. However, it is not always necessary to replace in kind. (See the heat
pump and additional strategies sections for conversion options, pages 18 and 19.)
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Whether your building uses unitary systems for cooling, heating, or both, you can
benefit from an integrated system approach. Depending on the upgrades you have
implemented in tune-ups through fan systems, cooling load requirements have
probably been reduced between 10 percent and 40 percent.
As with chillers, existing unitary systems are, in many cases, oversized. Likewise,
unitary systems that are in poor condition suffer downtime and significantly increased
operating and maintenance costs. A new and more reliable unitary system may be
more cost effective. If your unitary systems are 10 years old or older, you can
realize energy savings by replacing unitary systems with rightsized, energy-efficient
models.
Rightsizing your unitary systems to maximize the benefits of the cooling and heating
load reductions can result in significant energy savings. When determining the
rightsizing potential of your unitary system, be sure to measure your cooling and
heating loads first. By knowing what your cooling and heating loads are, you will be
better able to rightsize your new unitary system to meet maximum loads.
To estimate your energy savings from rightsizing, first measure your cooling and
heating loads. Then, using the seasonal energy efficiency ratio (SEER) for your
old and new systems, compare their respective energy consumption. Contact your
equipment manufacturer or an engineering consultant for further assistance.
Typically, commercial buildings use unitary systems with cooling capacities greater
than 5 tons. In some cases, however, due to space requirements, physical limitations,
or small additions, residential-sized unitary systems are used. In these cases, be sure
to look for the ENERGY STAR label. The ENERGY STAR label is found on various high
efficiency heating, cooling, and control products and can help you differentiate
between these and standard efficiency products. To determine what products may
meet your needs, visit the ENERGY STAR Web site at http : / /www. energystar.gov/
products/
The information about the technologies listed below will help you better understand
your unitary system and recent technological advances that may increase its
rightsizing p o tential .
• Packaged or rooftop units
• Vertical packaged units
• Split-system packaged units
• Air-source heat pumps
• Water-loop heat pump systems
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Packaged Or Rooftop Units
Packaged units are packaged HVAC units that are usually mounted on the roof,
freeing up valuable indoor floor space. They can also be installed on a concrete pad
at ground level. Because they are self-contained, manufactured units, installation
costs are low.
Single-package units consist of a blower section, filter bank, evaporator coil,
at least one compressor (larger units typically have multiple compressors to improve
load matching), and an air-cooled condenser section (see Figure 8). Units may also
come equipped with a heating section.
Heating is accomplished using either natural gas or electricity; however, natural gas is
generally less expensive, depending on the region. Heat pump systems can be used in
situations where electricity is the only source of energy. Unitary heat pump units
typically range in size from 1.5 to 20 tons. Heat pump systems are discussed further
below.
As packaged units age and deteriorate, their efficiency often decreases while the need
for maintenance increases. Upgrading your packaged units to high efficiency models
will result in substantial long-term energy savings.
Figure 8: S* elf-ContainedPackaged AC Unit
Supply Duct
Blower
Fan Motor
Return
Duct*.
Condenser
Fan
Evaporator
Compressor
Condenser Air In
Condenser
Air Out
Condenser
In the last 10 to 15 years, manufacturers have made significant improvements to the
efficiency of packaged units. The efficiency of heat transfer at both the evaporator
and condenser coils has been improved; high efficiency motors are now standard;
ENERGY STAR® BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
and blower and compressor designs have improved in high efficiency packaged units.
Scroll compressors are now commonplace on medium-sized (20- to 60-ton) rooftop
units. Energy efficiencies of newer units have a SEER in the range of 9.50 to 13.0.
It is not uncommon to find older units operating at efficiencies as low as 6.0, and
most operate at less than 9.0. Gas-fired heating sections typically have an annual
fuel utilization efficiency (AFUE) of about 80 percent.
Case Study: Installing High Efficiency Packaged Units Can
Cut Energy Costs
For a typical 100,000-sf office building that has 10 standard 25-ton packaged units with a
SEER rating of 9 and 80 percent electric heat efficiency, electricity costs would be about
$71,300 per year ($53,300 for cooling and $18,000 for heating, at $0.08 per kWh).
Installing a new energy-efficient unit with a cooling energy efficiency rating of 13 would result
in cooling mode electricity costs of about $36,900 annually—a savings of $16,400 per year. If
the heating component of the system was improved to 90 percent efficiency, the heating sav-
ings would be $2,000 per year. The combined annual savings of $18,400 equals a reduction in
energy costs of more than 25 percent.
(The cooling units are assumed to operate for 2,000 hours per year, while the heating units are
assumed to run for 1,000 hours per year.)
All newer packaged rooftop units are equipped with factory-installed microprocessor
controls. These controls make maintaining equipment easier and improve the energy
efficiency of both the unit and the overall HVAC system. Control features include
temperature setback and on/off scheduling. Large systems have variable air volume
capability, as discussed in Fan System Upgrades. Also, most units have an optional
communication interface for connection to an EMS system.
Vertical Packaged Units
Other unitary systems, if upgraded to high efficiency systems, offer much the same
potential for energy savings. Vertical packaged units (see Figure 9), which are a
variation on the packaged unit, are typically designed for indoor installation. Most
units have a water-cooled condenser, which can be fed from a cooling tower and/or
city water. Other components are mounted in the package. Ductwork can be
connected to the unit to distribute the air.
Split-System Packaged Units
Split-system packaged units (see Figure 10) have an outdoor pad or rooftop-
mounted air-cooled condenser. Refrigerant piping connects the compressor section to
an indoor air-handling unit and evaporator coil.
Unless they are heat pump type units, they cannot provide heat to the space. Heating
coils can be installed in the air-handling section, particularly if there is a central
source of heat such as hot water or steam from a boiler.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Figure 9: Vertical Packaged Units
o o
Supply Air Outlets
Evaporator
Coil
Section
Access
Panel
\
- Fan
Section
Return Air Filters
Compressor Section
Figure 10: Split-System Packaged Units
Compressor Condensor
\x v
Space
Blower
Evaporator
Refrigerant Lines
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Air-Source Heat PumpsK
Air-source heat pump systems are typically rooftop units, packaged either.
complete or as split systems. During cooling mode, the unit operates as a typical air-.
conditioning system. During heating mode, the cooling system is reversed completely.
to extract heat from the outside air and to provide it to the space. The size of.
unitary heat pump systems ranges from approximately 1.5 tons to 20 tons. In some.
cases, existing packaged cooling units with electric resistance heat can be upgraded to.
heat pumps for improved energy efficiency..
Heat pump applications are best suited to relatively warm climates, such as the.
Southeastern United States, and to areas where the availability of natural gas for.
heating is low. . When temperatures are low, the coefficient of performance (COP).
of the heat pump falls dramatically. A 7.5-ton rooftop heat pump unit that has a.
high-temperature COP of 3.0 can have a low-temperature COP of 2.0 or less..
Moreover, when the temperature drops further, heat pumps require supplemental.
heat, typically electric resistance; thus, effective heating efficiencies become even.
lower. More recently, dual-fuel heat pumps have become available in areas where.
natural gas can be used as the supplemental heating source..
Split-package heat pumps are designed with an air-handling unit located inside the.
conditioned space, and both the condenser and compressor are packaged in units for.
outdoor installation on a pad or on the roof.
Due to their improved annual efficiency, air-source heat pumps are good candidates.
for replacing packaged cooling units with electric-resistance heating coils..
Water-Loop Heat Pump SystemsK
Water-loop, or water-source, heat pump systems use water instead of air to.
transfer heat. In an air-to-air heat pump system, heat is removed from indoor air and.
rejected to outside air during the cooling cycle. The reverse happens during the.
heating cycle. However, in a water-loop heat pump, water replaces the outdoor air as.
the source or sink for heat, depending on the cycle in use..
In hot weather, a cooling tower removes heat from the water loop; in cooler weather,.
a central boiler heats the water..
As shown in Figure 11, water-loop heat pump systems allow for simultaneous heating.
and cooling by multiple separate and distinct units, and thus increase individual.
comfort. Furthermore, recovering heat from cooled areas and recycling it into other.
areas adds to the system's efficiency..
The size of water-source heat pumps ranges from approximately 0.5 tons to 25 tons..
Efficiencies of water-source units are generally higher than their air-to-air.
counterparts, where a SEER of 11.0 and COP of 3.8 to 4.0 are not uncommon..
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
High efficiency water-source heat pumps have a SEER as high as 14.0 to 15.0 and a
COP as high as 4.4.
Figure 11: Water-Loop Heat Pump System
WSHP
Cooling
WSHP
Cooling
"" -^- -4 -*- ~>
Additional Strategies: Best Opportunities
In addition to the strategies outlined in previous sections, other worthwhile
technological strategies warrant further attention for some applications. Whether or
not these strategies are viable for your building depends upon various conditions (for
example, size, location, types of business onsite, utility rate structures). These
strategies include the following:
Heating and Cooling Strategies
• Geothermal heat pumps
• District heating and cooling
• Radiant heating and cooling
Cooling Strategies
• Cool storage.
• High temperature difference distribution.
• Evaporative cooling.
• Non-electric cooling.
ENERGY ST^AE? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Geothermal Heat Pumps
An additional strategy for improving the efficiency of your HVAC equipment is the
geothermal heat pump. Geothermal heat pumps take advantage of the natural heat
stored underground to provide space conditioning heating, cooling, and humidity
control. Rather than converting chemical energy to heat, as in a furnace,
geothermal heat pumps work by moving heat. During the heating season, a
geothermal heat pump can move heat taken from the ground and apply it to a
building. In the cooling season, this process is reversed, as the building's excess heat
is moved back to the ground to provide air conditioning. (See A Short Primer and
Environmental Guidance for Geothermal Heat Pumps, EPA 430-K-97-007, available from
1-888-STAR YES).
Due to the relative stability of ground temperature, geothermal heat pump systems
are inherently more efficient than air-source heat pumps, which rely on outside air
as the medium which receives heat from the heat pump or from which heat is
extracted by the heat pump. Geothermal heat pump systems provide the highest
efficiencies in both cooling and heating seasons, as well as in heating water.
Information on geothermal heat pump systems is available from the ENERGY STAR
Web site at http: //www.energystar.gov/products /, under the Heating and Cooling
for your home. For additional information, visit the Geothermal Heat Pump
Consortium Web site at http://www.ghpc.org/home.htm.
District Heating and Cooling
District cooling is a shift in the generation location of chilled water from inside a
facility to a local chilled-water producer. As a district cooling customer, your facility
would purchase chilled water from a generation plant just as you purchase power
from a local utility company. Chilled-water plants supply water to a number of
customers within the plant district territory, usually encompassing a radius of three
to five city blocks.
There are several advantages to district cooling:
•OMost district cooling plants are modern facilities that use energy-efficient
generation methods.
•OThe need for buildings to own and use refrigerants is eliminated along with
refrigerant compliance responsibilities, handling regulations, rising replacement
costs, and capacity-loss issues.
•Dice can be generated at off-peak hours (when utility demand and rates are
lowest) and used at peak cooling periods to supplement chilled-water
production, yielding a lower chilled-water temperature. This lower temperature
means that high temperature-difference distribution may be viable, as discussed
below.
ENERGY ST^AE? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
•OChilled water can be purchased without the expense of installing, operating, or
maintaining one's own chiller.
This strategy is applicable for some facilities in cities, campuses, or industrial parks.
District heating and cooling eliminates central heating and/or cooling equipment.
Also, because district cooling suppliers use modern, non-CFC chillers, CFG chiller
equipment in your building can be retired.
Radiant Heating And Cooling
Radiant heating and cooling, also called hydronic heating and cooling, differs from
standard HVAC design in that it uses water distribution instead of air distribution to
meet a building's heating and cooling needs.
In a radiant cooling system, cold water is pumped through special panels or grids
of tubing mounted in the walls, ceilings, or floors. These panels absorb heat from
the building and bring it back to the HVAC plant to be removed from the building.
As discussed in load reductions and fan systems, the amount of outdoor air
required to ventilate your building is actually much smaller than the amount of air
that must be circulated through cooling coils to handle cooling load. Radiant
systems cool the space directly, reducing your ventilation system to the size
required to bring in outside air. This requirement is about 20 percent of the total
air recirculation capacity of the average building. As water has a much higher
capacity to store heat or cold than air, a much smaller volume of water can be
circulated, further reducing costs. Radiant cooling can supply the same cooling
capacity as other systems but at levels of energy consumption that are typically
about 75 percent of those for air-based systems.
Cool Storage
Cool storage is a means of using less expensive off-peak power to produce cooling
for the building. Cool storage is based upon the principle that a storage medium can
be cooled while chiller operating cost is low, and the storage can be discharged
when chiller operating cost is high. Furthermore, chillers tend to be most
economical to operate at night, when building cooling loads are low, electric rates
may be lower, and lower outdoor temperatures allow the chiller to reject heat more
efficiently. Cooling energy is stored in tanks of water, ice and water, or water
circulating around chemical modules that freeze and thaw. This last system, as well
as an ice-based system, has the advantage of taking up less space than chilled-water
storage because the freezing process can naturally store much more "cold" in a
given volume.
Generally, the most cost effective type of cool-storage design and operating
strategy is the partial-storage system shown in Figure 12. A partial storage system
reduces a building's maximum electrical demand by shifting a portion of the
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
cooling load from daytime to nighttime. The total chiller capacity required for the
building is also less than that of a standard system.
The cost effectiveness of cool-storage systems varies considerably depending on the
specific application. However, high electric-utility peak-demand charges, which
generally coincide with the peak cooling period in the afternoon, and a time-of-use
rate with a low nighttime kWh charge are factors that make it favorable to shift
cooling equipment operation away from the utility peak period. A cool storage system
is most cost effective when its capital cost is viewed as an incremental cost compared
to replacing or constructing a new chilled-water system.
Figure 12: Partial-Storage Strategy
o o &/
Load
Chiller Capacity
Chiller Charging Storage
Chiller Meets Load Directly
Storage Meets Load
24-Hour Period
High Temperature-Difference Distribution
Designing or modifying the chilled water distribution system to have a lower supply
temperature and a higher return temperature than normal provides more cooling
capacity for the same amount of chilled water flow. Increasing the difference
between the supply and return temperatures by a certain percentage reduces the
required water flow by the same percentage. Such a reduction in chilled-water flow
can substantially reduce required pumping energy.
Because a chiller operates less efficiently as it supplies colder chilled water, high
temperature-difference distribution systems are most appropriate when combined
with cool-storage systems, as discussed above. To reduce the required tank size, cool-
storage tanks containing ice or water are generally at lower-than-standard supply
temperature.
High temperature difference distribution systems are most cost effective in new
construction, because reduced chilled water flow requirements reduce the capital cost
of pumps, piping, and heat exchangers.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Evaporative Cooling
The process of evaporating water or another fluid absorbs heat, just as a kettle must
be heated before the water must boil. This is the basis for many types of mechanical
cooling. A much simpler and more economical variation can be used in some
climates. Cooling is produced by passing a flow of dry air over a wet surface. As the
water evaporates from the surface, the air stream is cooled. Although evaporative
cooling systems are most effective in dry climates, where the air has a large capacity
to absorb evaporating water, they can also be used elsewhere to reduce the annual
cooling load on mechanical refrigeration equipment.
There are both direct and indirect types of evaporative coolers and systems used in
conjunction with mechanical refrigeration. Direct evaporation systems evaporate
water directly into the supply air stream, whereas indirect systems cool one air stream
that in turn cools the supply air stream through a heat exchanger. Although indirect
systems are more costly, they avoid increasing the humidity of supply air.
Evaporative cooling can also be used to precool air to reduce the load on a
mechanical refrigeration system. Mechanical refrigeration can be used to increase the
evaporative cooling capacity by cooling the water used for evaporation.
Compared with standard unitary air-conditioning equipment, indirect evaporative
coolers have been shown to use 70 percent less electricity seasonally. While
evaporative cooling equipment generally offers reduced cooling capacity compared to
mechanical refrigeration, indirect evaporative preceding can supply half of the
annual cooling load in many areas (ASHRAE, 1999, Applications Handbook, Chapter
50).
Nonelectric Cooling
While the most common cooling plants use an electric motor to drive a refrigerant
compressor, there are nonelectric alternatives, such as engine-driven, steam turbinel
driven, and absorption chillers. While nonelectric cooling systems are often less
expensive to operate, their first cost is higher than that of electric systems, and they
come with increased equipment size and maintenance costs.
Gas engine-driven chillers are a cost-effective option for producing chilled water
in areas where gas rates are lower than electric rates. Gas engine-driven chillers are
much like electric chillers, except that they contain an engine rather than a motor.
Where there is a need for heating during the cooling season, heat recovery from both
the exhaust and cooling water can improve the efficiency of these systems. Gas
engine-driven chillers have average operating COPs of 1.7 to 1.9. If heat recovery
from the exhaust and water jacket are implemented, their efficiency can increase to
2.3 COP. While the efficiency of gas engine-driven chillers is much lower than that
of electric chillers, total fuel use and pollution emissions can be comparable when
considering electric power plant operations. The centrifugal or screw chiller driven by
the engine uses an HCFC or HFC refrigerant, much like an electric chiller.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Absorption chillers do not use the vapor compression cycle that most mechanical
refrigeration uses; instead, they are "driven" by heat, not by a mechanical drive input.
Moreover, they use water as a refrigerant in conjunction with lithium bromide as the
absorption chemical (or ammonia and water) such that there is no ozone-depletion
potential from the system. Although the system has fewer moving parts than a
centrifugal chiller, it is technically complex.
There are single- and double-effect absorption systems, and they may be fired
directly with a gas burner or indirectly with steam generated by separate equipment.
Single-effect systems have a COP of 0.5 to 0.7. Double-effect systems are more
efficient, with a COP of 1.0 to 1.1. Triple-effect absorbers are also under
development and promise still better efficiency. In addition, chiller-heaters, which use
absorption technology to provide cooling, heating, or both cooling and heating as
required, are available.
Steam turbines can be used to drive centrifugal compressors. The chilled medium is
usually water or brine, with a halogenated hydrocarbon refrigerant. Other refrigerants
such as ammonia, butane, or propane are also used in industrial processes.
Summary
This section has described numerous opportunities for optimizing both the size and
efficiency of your building's heating and cooling systems. Before undertaking any of
these strategies, you should measure your building's heating and cooling loads. Having
done so, retrofit or rightsize your heating and cooling equipment based on the load
reductions implemented in tune-up s through fan systems.
To find the most efficient equipment for your building's cooling and heating systems,
consult the American Council for an Energy-Efficient Economy's (ACEEE's) Guide
To Energy-Efficient Commercial Equipment, 2"1 edition.
Next Steps
Measure your cooling and heating loads and complete the Heating and Cooling
Survey at the end of this document.
ing Systems
Estimate your savings by conducting a Heating and Cooling survey and working
with an engineer (on-staff or consultant) to calculate savings potential.
Rightsize your cooling system to take advantage of load reductions.
OElimmate CFC refrigerants from your chiller system by retrofitting or replacing
your chiller.
OOlder chillers represent an investment opportunity. Install new high efficiency
chillers to reduce operating costs and match equipment size to cooling load.
ENERGY STAR? BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
• Improve cooling towers and install VSD controls with rightsized pumps.
• Implement cooling system efficiency strategies such as free cooling.
Heating Systems
•OReplace older boilers and furnaces or upgrade components and controls of
existing units.
Unitary Systems
• Replace older unitary equipment with high efficiency equivalents or heat pumps.
Additional Strategies
•OWhen evaluating your upgrade options, assess whether your building's specific
characteristics lend themselves to:
— Geothermal heat pumps
— District heating and cooling
— Radiant heating and cooling
— Cool storage
— High temperature-difference distribution
— Evaporative cooling
— Nonelectric cooling
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
APPENDIX: HEATINGQ\ND COOLING SURVEYD
Measure Heating and Cooling Loads To Rightsize Systems
This survey will familiarize you with the condition of your heating and cooling
systems and enable you to determine whether your heating and cooling equipment
needs replacing with rightsized, energy-efficient equipment.
To prepare to rightsize your heating and cooling systems, compile basic information
and measurements about the systems and your facility. Next, calculate the required
cooling and heating loads for your building.
To get started, recruit a survey team including a building engineer, HVAC technician,
boiler operator, and electrician. You will need to evaluate your available staff
resources and staff capabilities. If you do not have the means of taking these
measurements, you may want to contact an independent testing, adjusting and
balancing (TAB) firm or seek outside engineering services.
Before You Begin
You will need the following items to complete your survey:
• The latest specifications for the heating and cooling equipment in your building.
• The TAB report for your building's pumping systems.
• "As built" mechanical drawings.
•OOperations and maintenance manuals for the boiler, chiller, or unitary system
equipment.
•OThe system logs showing hot and chilled water supply and chilled-water return
temperatures and flow rates (if you have an energy management system).
• A data logger (note: for unitary systems only).
• A calculator.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Chiller Systems Survey
Collect the following information:
Chiller Type
Manufacturer
Type of Refrigerant
D Air-cooled centrifugal
D Water-cooled centrifugal
D Reciprocating
D Helical rotary/screw
D Steam absorption
D Hot-water absorption
D Direct-fired absorption
D Engine-driven
Efficiency (kW/ton)
Size or Capacity (in tons)
(12,000 Btu/hr = 1 ton)
Calculate the maximum cooling load for jour building using the following procedure:
What is the maximum cooling load for the building (in tons)? This load will be
compared with the chiller capacity recorded above. To determine maximum cooling
load, take the following measurements in the afternoon on a typical hot summer day
to capture peak load effects on your system. Note: An energy management system may
also log these measurements.
•OTemperature of the chilled-water supply (CHWS). A temperature gauge should
be found on the pipe at the chiller's supply outlet.
•OTemperature of the chilled-water return (CHWR). A temperature gauge should
be found on the pipe at the chiller's return inlet.
•OFlow rate (GPM) of the chilled water supply. A flow rate gauge should be found
on the supply pipe. If a gauge is not available, the design flowrate from as-built
drawings may be used.
Chilled Water System
Measurements
Temperature of CHWS_
Temperature of CHWR
Flow rate (GPM) of CHWS_
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Now, using the measurements, do the following calculations:
CHWR - CHWS = AT:
AT x 500 x (GPM - 12,000) =
Load (in tons):
Load x 1.1 = Maximum Cooling Load
How much of your existing chiller capacity does your building currently need? To
answer this, do the following calculation:
Maximum Cooling Load ^
Chiller Capacity =
Percentage of Chiller Capacity Needed
If the required capacity of the chiller is 30 percent less than the installed capacity of
your existing chiller, you should seriously consider replacing the chiller. The efficiency
of the chiller decreases sharply below 70 percent loading. Also, remember that the
chiller is operating most of the time at part-load conditions with your newly reduced
loads, which increases your rightsizing potential even further.
Boiler Systems Survey
Collect the following information:
Heating Plant Central hot water
Type boiler
Manufacturer
Fuel (gas, oil, electric)
Efficiency (percent)
Size or Capacity
(in MBtu/hr)
Calculate the maximum heating load for jour building using the following procedure:
What is the maximum heating load for the building (in MBtu/hr)? This load will be
compared with the heating system capacity recorded above. To determine maximum
heating load, take the following measurements in the morning on a typical cold winter
day to capture peak load effects on your system. Note: An energy management system
may also log these measurements. The folio wing procedure is tailored to typical central hot
water boiler systems.
•OTemperature of the hot water supply (HWS). A temperature gauge should be
found on the pipe at the boiler's supply outlet.
ENERGY ST^AE? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
•OTemperature of the hot water return (HWR). A temperature gauge should be
found on the pipe at the boiler's return inlet.
•OFlow rate (GPM) of the hot water supply. A flow rate gauge should be found on
the supply pipe. If a gauge is not available, the design flow rate from as-built
drawings may be used.
Boiler System Measurements
Temperature of HWS _
Temperature of HWR _
Flow rate (GPM) of HWS
Now, using the measurements, do the following calculations:
HWR - HWS = AT
AT x 500 x GPM/1,000 = Load
(in MBtu/hr)
Load x 1.1 = Maximum Heating Load
How much of your existing boiler capacity does your building currently need?
Maximum Heating Load ^
Heating Plant Capacity =
Percentage of Heating Capacity Needed
For other types of heating systems, there are other ways of measuring maximum
heating load.
•OFor systems such as forced-air furnaces and heat pumps that respond to
thermostats by cycling on and off, a simple runtime meter will show how much
of the time the unit cycles on. Supply-temperature data logged every few
minutes by an EMCS or other data logger can also be analyzed to determine
how much of the time the unit is cycled on. The percentage of heating capacity
needed is the time the unit operates divided by the total time during a high
heating load period.
•OMeasuring steam boiler loading is similar, but more complicated than for a hot
water boiler. Instead of the water flow rate, the steam flow rate must be
measured. Instead of multiplying a temperature difference by a factor
accounting for the heat content of each GPM, the temperature and pressure
properties of the supply steam must be recorded from gauges on the supply line
and used to determine the heat content of each pound of steam using a steam
table.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Other strategies for measuring heating loads include:
• Periodic gas meter readings.
• Oil tank gauge readings or oil deliveries.
• On/off cycle times for systems that operate intermittently.
Unitary Systems Survey
Collect the following information for each type of unit installed in jour
Boiler System Measurements
Unitary System Type D Packaged rooftop unit
(choose onej^\ D Split system
D Vertical packaged unit
D Heat pump
Manufacturer
Htg Fuel (gas, oil, elec.)
Unit Age
Cooling Efficiency (%)
Heating Efficiency (%)
Size or Capacity (cooling)
(in tons)
Size or Capacity (heating)
(in MBtu/hr)
Calculate the maximum cooling and heating loads for jour building using the following
steps:
What are the maximum heating and cooling loads for the building (in MBtu/hr)?
These loads will be compared with the cooling and heating capacities recorded above.
To determine maximum heating or cooling load use the procedure described in the
heating section for small systems that cycle on and off.
Time cycled on ^ Total time = Percentage of Capacity Needed
A data logger can be used to determine how much of the time the unit is cycled on.
ENERGY ST^AE? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
GLOSSARY
Recommissioning
air side systems
Equipment used to heat, cool, and transport air within building HVAC systems.
ASHRAE
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
Process of measuring and adjusting equipment to obtain desired flows. Applies to both air
side and water side systems.
Pressure vessel designed to transfer heat (produced by combustion) or electric resistance to a
fluid. In most boilers, the fluid is water in the form of liquid or steam.
British thermal unit (Btu)
A unit of energy equivalent to the amount of heat required to raise the temperature of 1
pound of water 1 degree Fahrenheit.
BUD
See British thermal unit.
calibration
Process of adjusting equipment to ensure that operation is within design parameters.
carom mtitioxule
Colorless, odorless, poisonous gas formed during incomplete combustion of fuel.
central plant
Centrally located equipment that satisfies a building's cooling and heating loads.
CFCsD
See chlorofluorocarbons.
cfm
Cubic feet per minute.
Mechanical device that generates cold liquid, which is circulated through cooling coils to cool
the air supplied to a building.
chlorofluorocarbons
Chemical compounds consisting of carbon, hydrogen, chlorine, and fluorine, once used
widely as aerosol propellants and refrigerants. Believed to deplete the atmospheric ozone
layer.
coil, condenser
A heat exchanger used to condense refrigerant from a gas to a liquid.
coil, cooling
Heat exchanger used to cool air under forced convection with or without dehumidification.
May consist of a single coil section or several coil sections assembled into a bank.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
coil, fan
A device that combines a heat exchanger and a fan in a single unit that conditions air by
forced convection.
coil, heating
Heat exchanger that heats air under forced convection. May consist of a single coil section or
several coil sections assembled into a bank.
combustion air
Air that supplies the oxygen required to burn fuel.
commissioning
The quality assurance process that ensures
design intent is met for new facilities or major rehabilitation.
condenser
Heat exchanger in a refrigeration system that expels building heat absorbed in the evaporator.
conditioned air
Air that serves a space and that has had its temperature and/or humidity altered to meet de-
sign specifications.
controls
An instrument or set of instructions for operating or regulating building systems.
control, pneumatic
A control that utilizes air pressure to vary equipment operation.
control, set back
The practice of reducing the thermostat setpoint during unoccupied times.
cooling tower
Device that dissipates heat from water-cooled systems through a combination of heat and
mass transfer, whereby the water to be cooled is distributed in the tower and exposed to cir-
culated ambient air.
The noncontinuous operation of equipment.
dampers
Single- or multiple-blade devices, either manually or automatically opened or closed, that
control the flow of air.
demand charges
Fees levied by a utility company for electric
demand.
demand, electric
Electrical power delivered to a system at a given time or averaged over a designated period.
Expressed in kilowatts.
diffuser, UVAC
A device that distributes conditioned air to a space.
d
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
energy maxasfr/Knt system (EMS)
The control system that monitors the environment and energy usage in a building and alters
equipment operation to conserve energy while providing occupant comfort.
envelope, building
The outer shell of a building, including walls, roof, windows, and doors.
evaporator
Heat exchanger in a refrigeration system that absorbs heat from chilled water or building air,
thus reducing the supply temperature.
The buildup of a film that reduces heat transfer.
heat exchanger
A device that transfers heat from one fluid to another.
humidistat
A device that responds to humidity changes and controls equipment by seeking a setpoint.
UVAC
Heating, ventilating, and air-conditioning.
kilowatt(kW)
Unit of power equal to 1,000 watts.
kilowatt-hour (kWh)
Unit of electric consumption equal to the work done by 1 kilowatt acting for 1 hour.
kW
See kilowatt.
kWh
See kilowatt-hour.
The demand upon the operating resources of a system. In the case of energy loads in build-
ings, the word generally refers to heating, cooling, and electrical (or demand) loads.
maintenance
An ongoing process to ensure equipment operates at peak performance.
occupancy sensor
A device that detects heat (passive infrared) or a shift in the frequency of reflected ultrasonic
sound waves, to control operation of lights or equipment accordingly.
off-peak
Refers to a utility rate schedule that designates the time of day when energy and demand
costs are typically less expensive.
on-peak
Refers to a utility rate schedule that designates the time of day when energy and demand
costs are typically more expensive.
packaged unit
A self-contained HVAC unit that provides heating and/or cooling to a building space.
part-load
Condition when equipment operates at less than full capacity to meet the demand placed
upon it.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
part-load performance
Equipment efficiency at less than full capacity.
pressure drop
The loss in pressure experienced by flowing water or air due to friction and obstructions.
radiator
Device that provides warmth to a space through radiant or convective heat provided by either
steam or hot water.
Recommissioning ensures system functionality. It is an inclusive and systematic process in-
tended not only to optimize how equipment and systems operate, but also to optimize how
the systems function together.
refrigerant
Substance, such as CFCs, HCFCs, HFCs, air, ammonia, water, or carbon dioxide, used to
provide cooling by evaporation and condensation.
reset, chilled water
The practice of increasing chilled water temperature to obtain higher chiller efficiency.
reset, condenser mater
The practice of decreasing condenser water temperature to obtain higher chiller efficiency.
rooftop uniO
Air-handling equipment such as packaged units located on the roof.
scaling
schedule
A control sequence that turns equipment on and off.
setpoint
Desired temperature, humidity, or pressure in a space, duct, etc.
shell, bailiKtiji
See envelope, building.
space
The distinct area to which conditioned air is
delivered.
steam trap
A device that separates air and condensed water from steam.
E-ffiG
See testing, adjusting, and balancing.
testing, adjusting, and balancing (TAB)
The process of adjusting HVAC system components to supply air and water flows at design
or revised specifications.
thermostat
A device that responds to temperature changes and controls equipment by seeking a setpoint
accordingly.
ton
Unit of cooling capacity equal to 12,000 Btu/hr.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
tubes, condenser
Heat exchanger tubes through which condenser water is pumped to allow heat transfer be-
tween the condenser water and the refrigerant.
tubes, evaporator
Heat exchanger tubes through which chilled water is pumped to allow heat transfer between
the chilled water and the refrigerant.
tune-up, building
The purposeful sequence of maintenance and operational improvements, undertaken at a
specific point in time, designed to reduce energy use, heating loads, and cooling loads of ex-
isting facilities.
variable air volume
A type of air-handling system that provides air at a constant temperature and varies the air
quantity to each zone to match the variation in room load.
See variable air volume.
water side systems
Equipment used to heat, cool, and transport water to building HVAC systems.
Lighting
ballast
Power-regulating device that modifies input voltage and controls current to provide the elec-
trical conditions necessary to start and operate gaseous discharge lamps.
carbon dioxide
Colorless, odorless, incombustible gas formed during respiration, combustion, and organic
decomposition. Increasing amounts of carbon dioxide in the atmosphere are believed to
contribute to the global warming phenomenon.
CERCLA
Comprehensive Environmental Response, Compensation and Liability Act (1980) an EPA
regulation. Also known as the Superfund law.
color ren/iis'!f!f[ ttidex (CRI)
A measure ranging from 0 to 100 of the accuracy with which a light source renders different
colors in comparison to natural light, which has a measure of 100.
controls
An instrument or set of instructions for operating or regulating building systems.
CRJD
See c
The noncontinuous operation of equipment.
deadband
A setting in the lighting control that provides a time delay, signaling the lights to switch off
only if the light level is somewhat above the setting, or on only if the level is somewhat below
the setting.
DEHP
Di (2-ethylhexyl) phthalate, an insulator used to replace PCBs in ballast capacitors starting in
1979. DEHP is listed as a hazardous waste in its pure form, but, according to RCRA, it is no
longer considered hazardous once used in a lighting ballast.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
(If'Hand charges
Fees levied by a utility company for electric demand.
demand, electric
Electrical power delivered to a system at a given time or averaged over a designated period.
Expressed in kilowatts.
diffuser, HVAC
A device that distributes conditioned air to
a space.
diffuser, lighting
A device that distributes light produced by lamps into a space.
efficacy
The ratio of lamp lumen output to total lamp power input expressed in lumens per watt.
efficiency
Ratio of power output to power input.
EMSD
See energy management system.
energy /naKoinntnt system (EMS)
The control system that monitors the environment and energy usage in a building and alters
equipment operation to conserve energy while providing occupant comfort.
footcandle ffc)
Unit of illuminance equal to 1 lumen per square foot.
The rate at which heat enters or is generated within a space at a given instant.
HID
High-intensity discharge.
HVAC
Heating, ventilating, and air-conditioning.
Indoor air quality.
IBS
Illuminating Engineering Society.
illuminance
Commonly called light level, the light intensity arriving on a surface measured in footcandles.
internal rate of return
Compound interest rate at which the total discounted benefits equal total discounted costs
for a particular investment.
IRBD
See internal rate of return.
kilowatt (kW)
Unit of power equal to 1,000 watts.
kilowatt-hour (kWh)
Unit of electric consumption equal to the work done by 1 kilowatt acting for 1 hour.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
See kilowatt.
kWh
See kilowatt-hour.
load
The demand upon the operating resources of a system. In the case of energy loads in build-
ings, the word generally refers to heating, cooling, and electrical (or demand) loads.
Unit measurement of the rate at which a light source produces light per unit time.
li'fnmaire
Complete lighting unit, consisting of one or more lamps together with a housing, the opti-
cal components to distribute the light from the lamps, and the electrical components (ballast,
starters, etc.) necessary to operate the lamps.
Commonly referred to as brightness, the light leaving a surface measured in footlamberts. It
considers both illuminance on the surface and reflectance of the surface.
luminance ratitO
The ratio between the luminances of any two
areas in the visual field. This is a measure of the uniformity of luminance.
maintenance
An ongoing process to ensure equipment operates at peak performance.
Chemical compounds that contain nitrogen
and oxygen. They react with volatile organic compounds in the presence of heat and sunlight
to form ozone and are a major precursor to acid rain.
occupancy sensor
A device that detects heat (passive infrared) or a shift in the frequency of reflected ultrasonic
sound waves, to control operation of lights or equipment accordingly.
packaged unit
A self-contained HVAC unit that provides heating and/or cooling to a building space.
payback
See payback, simple.
payback, simple^}
Also known as payback. Measurement of the elapsed time between an initial investment and
the point at which accumulated savings are sufficient to offset the initial investment.
PCS
Polychlorinated biphenyl. A substance used as an insulator in the capacitor of fluorescent and
HID magnetic ballasts prior to 1970. PCBs have been labeled as carcinogenic and can cause
skin, liver, and reproductive disorders.
A device that responds electrically to the presence of light.
power factor
Ratio of real power to total apparent power.
power quality
The degree to which voltage and current wave forms conform to a sinusoidal shape and are
in synchronous phase with one another. Poor power quality can have negative impacts on
electrical equipment.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
RCRA
Resource Conservation and Recovery Act, an EPA Regulation.
ref/ectotO
A device installed in lumnaires used to direct light from a source via specular or diffuse reflec-
tion.
rightsisjng
The process of correctly sizing equipment to the peak load.
rooftop uniO
Air-handling equipment such as packaged units located on the roof.
schedule
A control sequence that turns equipment on and off.
sulfur dioxide
A heavy, colorless, pungent air pollutant formed primarily by the combustion of fossil fuels
such as coal. It is a respiratory irritant and a precursor to the formation of acid rain.
See vi.
visual comfort probability (VCP)
A rating given to lighting systems expressed as the percentage of people who will find light
output acceptable in terms of glare due to direct light from luminaires.
voltage, volts
International system unit of electric potential or the amount of electrical flow, also referred to
as electromotive force.
Supplemental Load Reductions
AHLD
air-handling unit (AHU)
Equipment used to distribute conditioned air to a space. Includes heating and cooling coils,
fans, ducts, and filters.
air side systems
Equipment used to heat, cool, and transport air within building HVAC systems.
ASHSAE
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
Process of measuring and adjusting equipment to obtain desired flows. Applies to both air
side and water side systems.
ballast
Power-regulating device that modifies input voltage and controls current to provide the elec-
trical conditions necessary to start and operate gaseous discharge lamps.
British thermal unit (Btu)
A unit of energy equivalent to the amount of heat required to raise the temperature of 1
pound of water 1 degree Fahrenheit.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
Bun
See British thermal unit.
calibration
Process of adjusting equipment to ensure that operation is within design parameters.
carbon dioxide
Colorless, odorless, incombustible gas formed during respiration, combustion, and organic
decomposition. Increasing amounts of carbon dioxide in the atmosphere are believed to
contribute to the global warming phenomenon.
See chlorofluorocarbons.
Cubic feet per minute.
Mechanical device that generates cold liquid, which is circulated through cooling coils to cool
the air supplied to a building.
chlorofluorocarbons
Chemical compounds consisting of carbon,
hydrogen, chlorine, and fluorine, once used widely as aerosol propellants and refrigerants. Be-
lieved to cause depletion of the atmospheric ozone layer.
coil, condenser
A heat exchanger used to condense refrigerant from a gas to a liquid.
coil, cooling
Heat exchanger used to cool air under forced convection, with or without dehumidification.
May consist of a single coil section or several coil sections assembled into a bank.
coil, fan
A device that combines a heat exchanger and
a fan in a single unit that conditions air by forced convection.
coil, heating
Heat exchanger that heats air under forced
convection. May consist of a single coil section or several coil sections assembled into a bank.
controls
An instrument or set of instructions for operating or regulating building systems.
dampers
Single- or multiple-blade devices, either manually or automatically opened or closed, that
control the flow of air.
DEHP
Di (2-ethylhexyl) phthalate, an insulator used
to replace PCBs in ballast capacitors starting in 1979. DEHP is listed as a hazardous waste in
its pure form, but, according to RCRA, it is no longer considered hazardous once used in a
lighting ballast.
demand charges
Fees levied by a utility company for electric
demand.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
demand, electric
Electrical power delivered to a system at a given time or averaged over a designated period.
Expressed in kilowatts.
demand ventilation
Method of controlling the amount of outdoor air intake based on carbon dioxide levels in
a space.
desiccant
A material that absorbs moisture from its surrounding environment.
domestic hot mater
All hot water consumed in a building that is used for purposes other than heating a space.
efficacy
The ratio of lamp lumen output to total lamp power input expressed in lumens per watt.
efficiency
Ratio of power output to power input.
ENERGY STAR label
EPA's trademark symbolizing excellence in energy efficiency.
envelope, building
The outer shell of a building, including walls, roof, windows, and doors.
exhaust air
Air removed from a building and not reused.
glaring
Glass set or made to be set in frames.
glaring system
A configuration of materials with a transparent or translucent element designed to admit
sunlight.
GPM
Gallons per minute. A measure of water flow rate.
Deal e>, cnant
A device that transfers heat from one fluid to another.
heat, latent
The heat required to change the state of matter from a liquid to gas or gas to liquid.
heat pump
Heat pump utilize the vapor compression refrigeration cycle the same that a DX unit or
chiller does. The difference is that a heat pump can reverse the direction of heat flow which
naturally flows from warmer to cooler areas.
heat, sensible
The heat required to change temperature without changing state of matter. This temperature
change can occur by exposure to radiation, friction between two objects, chemical reaction, or
contact with a hotter object.
Horsepower. A unit of mechanical power.
HVAC
Heating, ventilating, and air-conditioning.
Indoor air quality.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
infiltration
Air that leaks into a building through the
building shell.
kilowatt (kW)
Unit of power equal to 1,000 watts.
kilowatt-hour (kWh)
Unit of electric consumption equal to the work done by 1 kilowatt acting for 1 hour.
kW
See
kWh
load
The demand upon the operating resources of a system. In the case of energy loads in build-
ings, the word generally refers to heating, cooling, and electrical (or demand) loads.
maintenance
An ongoing process to ensure equipment operates at peak performance.
nitrogen oxides
Chemical compounds that contain nitrogen and oxygen. They react with volatile organic com-
pounds in the presence of heat and sunlight to form ozone and are a major precursor to acid
rain.
occupancy sensor
A device that detects heat (passive infrared) or a shift in the frequency of reflected ultrasonic
sound waves, to control operation of lights or equipment accordingly.
Sttpayback, simple.
payback, simple^}
Also known as payback. Measurement of the elapsed time between an initial investment and
the point at which accumulated savings are sufficient to offset the initial investment.
PPM
Parts per million. A unit of concentration.
roof curb
A raised and reinforced area on a roof for mounting equipment.
setpoint
Desired temperature, humidity, or pressure in a space, duct, etc.
space
The distinct area to which conditioned air is
delivered.
time clock
The control device used to turn equipment on and off at set times of the day.
ton
Unit of cooling capacity equal to 12,000 Btu/hr.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
transformer
A device that reduces the incoming line voltage, usually to a standard level, so that it may be
used to operate electrical equipment in a building.
tune-up, building
The purposeful sequence of maintenance and operational improvements, undertaken at a
specific point in time, designed to reduce
energy use, heating loads, and cooling loads
o f exis ting facilitie s.
W/sf
Watts per square foot.
Fans
AHU3
air-handling unit (AHU)
Equipment used to distribute conditioned air to a space. Includes heating and cooling coils,
fans, ducts, and filters.
air side systems
Equipment used to heat, cool, and transport air within building HVAC systems.
ASHRAE
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
Process of measuring and adjusting equipment to obtain desired flows. Applies to both air
side and water side systems.
Pressure vessel designed to transfer heat produced by combustion or electric resistance to a
fluid. In most boilers, the fluid is water in the form of liquid or steam.
British thermal unit (Btu)
A unit of energy equivalent to the amount of heat required to raise the temperature of 1
pound of water 1 degree Fahrenheit.
BtiD
See British thermal unit.
See constant volume.
CFCsD
See chlarofluoro carbons.
cjm
Cubic feet per minute.
Mechanical device that generates cold liquid, which is circulated through cooling coils to cool
the air supplied to a building.
chlorofluorocarbons
Chemical compounds consisting of carbon, hydrogen, chlorine, and fluorine, once used
widely as aerosol propellants and refrigerants. Believed to cause depletion of the atmospheric
ozone layer.
ENERGY ST^AE? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
of performance (COP)
A measure of efficiency in which a higher value designates a more efficient system.
coil, condenser
A heat exchanger used to condense refrigerant from a gas to a liquid.
coil, cooling
Heat exchanger used to cool air under forced convection, with or without dehumidification.
May consist of a single coil section or several coil sections assembled into a bank.
coil, fan
A device that combines a heat exchanger and a fan in a single unit that conditions air by
forced convection.
coil, heating
Heat exchanger that heats air under forced convection. May consist of a single coil section or
several coil sections assembled into a bank.
condenser
Heat exchanger used to expel building heat absorbed in the evaporator of a refrigeration sys-
tem.
Air that serves a space that has had its
temperature and/or humidity altered to meet design specifications.
constant volume (CAV, constant air volume)
Type of air-handling system that supplies the conditioned space at a constant air flow and
modulate heating and cooling by varying the air temperature.
controls
An instrument or set of instructions for operating or regulating building systems.
Device that dissipates heat from water-cooled systems through a combination of heat and
mass transfer, whereby the water to be cooled
is distributed in the tower and exposed to
circulated ambient air.
com
See coefficient of performance.
The noncontinuous operation of equipment.
df-nand charges
Fees levied by a utility company for electric
demand.
demand, electric
Electrical power delivered to a system at a given time or averaged over a designated period.
Expressed in kilowatts.
downsizing
Process of reducing the size (capacity) of equipment so that it operates efficiently at design
load conditions.
ductwork
The distribution system for air in HVAC systems. It is usually made of sheet metal
or fiberglass.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
ejfieitney
Ratio of power output to power input.
EMSD
See energy management system.
energy management system (EMS)
The control system that monitors the environment and energy usage in a building and alters
equipment operation to conserve energy while providing occupant comfort.
evaporator
Heat exchanger in a refrigeration system that absorbs heat from chilled water or building air,
thus reducing the supply temperature.
The buildup of a film that reduces heat transfer.
gasket
Material used to seal a joint against leakage.
GPM
Gallons per minute. A measure of water flow rate.
heat exchanger
A device that transfers heat from one fluid to another.
heat, latent
The heat required to change the state of matter from a liquid to gas or gas to liquid.
heat pump
Heat pump utilize the vapor compression refrigeration cycle the same that a DX unit or
chiller does. The difference is that a heat pump can reverse the direction of heat flow which
naturally flows from warmer to cooler areas.
heat, sensible
The heat required to change temperature without changing state of matter. This temperature
change can occur by exposure to radiation, friction between two objects, chemical reaction, or
contact with a hotter object.
hp
Horsepower. A unit of mechanical power.
HVAC
Heating, ventilating, and air-conditioning.
impeller
The rotating element of a fan or pump used to circulate the air or water.
internal rate of return
Compound interest rate at which the total discounted benefits become equal to total dis-
counted costs for a particular investment.
IRBD
See internal rate of return.
kilowatt (kW)
Unit of power equal to 1,000 watts.
kilowatt-hour (kWh)
Unit of electric consumption equal to the work done by 1 kilowatt acting for 1 hour.
kW
See kilowatt.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
kWh
See kilowatt-hour.
load
The demand upon the operating resources of a system. In the case of energy loads in build-
ings, the word generally refers to heating, cooling, and electrical (or demand) loads.
maintenance
An ongoing process to ensure equipment operates at peak performance.
A device used to measure and display or record data.
nitrogen oxides
Chemical compounds that contain nitrogen and oxygen. They react with volatile organic com-
pounds in the presence of heat and sunlight to form ozone and are a major precursor to acid
rain.
Refers to a utility rate schedule that designates the time of day when energy and demand
costs are typically less expensive.
on-peak
Refers to a utility rate schedule that designates the time of day when energy and demand
costs are typically more expensive.
packaged unit
A self-contained HVAC unit that provides heating and/or cooling to a building space.
part-load
Condition when equipment operates at less than full capacity to meet the demand placed
upon it.
Sttpayback, simple.
payback, simple^}
Also known as payback. Measurement of the elapsed time between an initial investment and
the point at which accumulated savings are sufficient to offset the initial investment.
power factor
Ratio of real power to total apparent power.
pressure drop
The loss in pressure experienced by flowing water or air due to friction and obstructions.
refrigerant
Substance, such as CFCs, HCFCs, HFCs, air, ammonia, water, or carbon dioxide, used to
provide cooling by evaporation and condensation.
reset, chilled mater
The practice of increasing chilled water temperature to obtain higher chiller efficiency.
reset, condenser water
The practice of decreasing condenser water temperature to obtain higher chiller efficiency.
rightsizing
The process of correctly sizing equipment to operate efficiently at design load conditions.
rooftop uniO
Air-handling equipment such as packaged units located on the roof.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
sealing
schedule
A control sequence that turns equipment on and off.
seasonal energy-efficiency ratio (SEER)
Cooling capacity (Btu/hr) divided by total input power (watts) requirement where both
seasonal averages.
SEESD
See seasonal energy-efficiency ratio.
sheave
(Pronounced shiv.) Pulley.
space
The distinct area to which conditioned air is
delivered.
thermostat
A device that responds to temperature changes and controls equipment by seeking a setpoint
accordingly.
timeclock
The control device used to turn equipment on and off at set times of the day.
ton
Unit of cooling capacity equal to 12,000
Btu/hr.
tune-up, building
The purposeful sequence of maintenance and operational improvements, undertaken at a
specific point in time, designed to reduce
energy use, heating loads, and cooling loads
of existing facilities.
variable air /eh/me (VAV)
A type of air-handling system that provides air at a constant temperature and varies the ai
quantity to each zone to match the variation in room load.
air
See variabk air volume.
vsrn
See variable-speed drive.
variable-speed drive (VSD)
A device used to adjust the speed of an AC
motor to match load requirements.
Heating and Cooling
See air-
unit
air-handling unit (AHU)
Equipment used to distribute conditioned air to a space. Includes heating and cooling coils,
fans, ducts, and filters.
ENERGY ST^AE? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
air side systems
Equipment used to heat, cool, and transport air within building HVAC systems.
ARI
Air-Conditioning and Refrigeration Institute.
ASHRAE
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
ASME
American Society of Mechanical Engineers.
Pressure vessel designed to transfer heat produced by combustion or electric resistance to a
fluid. In most boilers, the fluid is usually water in the form of liquid or steam.
calibration
Process of adjusting equipment to ensure that operation is within design parameters.
carbon dioxide
Colorless, odorless, incombustible gas formed during respiration, combustion, and organic
decomposition. Increasing amounts of carbon dioxide in the atmosphere are believed to
contribute to the global warming phenomenon.
See constant volume.
CFCsD
See chlarofluoro carbons.
Mechanical device that generates cold liquid, which is circulated through cooling coils to cool
the air supplied to a building.
chlorofluorocarbons
Chemical compounds consisting of carbon, hydrogen, chlorine, and fluorine, once used
widely as aerosol propellants and refrigerants. Believed to cause depletion of the atmospheric
ozone layer.
coefficient of performance (COP)
A measure of efficiency in which a higher value designates a more efficient system. For ex-
ample, Chiller efficiency measured in Btu output (cooling) divided by Btu input (electric
power), measured at full or part load.
coil, condenser
A heat exchanger used to condense refrigerant from a gas to a liquid.
coil, cooling
Heat exchanger used to cool air under forced convection, with or without dehumidification.
May consist of a single coil section or several coil sections assembled into a bank.
coil, heating
Heat exchanger that heats air under forced convection. May consist of a single coil section or
several coil sections assembled into a bank.
condenser
Heat exchanger used to expel building heat absorbed in the evaporator of a refrigeration sys-
tem.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
constant volume (CAV, constant air volume).
Type of air-handling system that supplies the conditioned space at a constant air flow and
modulate heating and cooling by varying the air temperature.
controls
An instrument or set of instructions for operating or regulating building systems.
cooling tower
Device that dissipates heat from water-cooled systems through a combination of heat and
mass transfer, whereby the water to be cooled is distributed in the tower and exposed to cir-
culated ambient air.
com
See coefficient of performance.
dampers
Single- or multiple-blade devices, either manually or automatically opened or closed, that con-
trol the flow of air.
ik»i-md charges
Fees levied by a utility company for electric demand.
direct expansion system
Cooling system in which the refrigerant runs in the cooling coil to cool the air directly; that is,
there is no water loop between the refrigerant and the air to be cooled.
downsizing
Process of reducing the size (capacity) of equipment so that it operates efficiently at design
load conditions.
EER
Energy Efficiency Ratio. Cooling capacity
(Btu/hr) divided by total input power (watts)
requirement.
efficiency
Ratio of power output to power input.
EMSD
See energy management system.
energy management system (EMS)
The control system that monitors the environment and energy usage in a building and alters
equipment operation to conserve energy while providing occupant comfort.
fan, cooling tower
Fans that are used to draw air through the cooling tower to carry away water vapor.
gasket
Material used to seal a joint against leakage.
GPM
Gallons per minute. A measure of water flow rate.
heat-exchange area
Area where heat is transferred from one medium to another.
heat pump
Heat pump utilize the vapor compression refrigeration cycle the same that a DX unit or
chiller does. The difference is that a heat pump can reverse the direction of heat flow which
naturally flows from warmer to cooler areas.
ENERGY STAR? BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
HVAC
Heating, ventilating, and air-conditioning.
IEEE
Institute of Electrical and Electronic Engineers.
internal rate of return
Compound interest rate at which the total discounted benefits become equal to total dis-
counted costs for a particular investment.
ZRBD
See internal rate of return.
kilowatt (kW)
Unit of power equal to 1,000 watts.
kilowatt-hour (kWh)
Unit of electric consumption equal to the work done by one kilowatt acting for one hour.
kW
See kilowatt.
YWh
See kilowatt-hour.
load, cooling
Cooling (typically measured in Btu/hr or
tons) required to maintain an indoor design temperature.
part-load conditions
Time when equipment is operating at less than design loads; represents the majority of the
time equipment is operating.
payback
See payback, simple.
payback, simple^
Also known as payback. Measurement of the elapsed time between an initial investment and
the point at which accumulated savings are sufficient to offset the initial investment.
peak (cooling) load
Maximum cooling required to maintain an indoor design temperature under the most ad-
verse summertime outdoor air conditions.
pump, chilled-mater
Device that circulates chilled water.
pump, condenser-water
Device that circulates condenser water.
refrigerant^
Substance, such as CFCs, HCFCs, HFCs, air, ammonia, water, or carbon dioxide, used to
provide cooling by evaporation and condensation.
seasonal energy-efficiency ratio (SEER)
Cooling capacity (Btu/hr) divided by total input power (watts) requirement where both
are seasonal averages.
SEEFD
See seasonal energy-efficiency ratio.
ENERGY STAR® BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
setpoint
Desired temperature, humidity, or pressure in a space, duct, etc.
space
The distinct area to which conditioned air is
delivered.
strainer screen
Filtering device used in water side systems to protect equipment from dirt, rust, and other
particles.
See testing, adjusting, and balancing.
ton
Unit of cooling capacity equal to 12,000 Btu/hr.
variable air volume (VAV)
A type of air-handling system that provides air at a constant temperature and varies the air
quantity to each zone to match the variation in room load.
variable-speed drive (VSD)
A device used to adjust the speed of an AC motor to match load requirements.
See variabk air volume.
See variable speed drive.
mater side systems
Equipment used to supply heating and cooling for air side systems. Includes pumps, chillers,
boilers, and other devices.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
BIBLIOGRAPHY ORGANIZED BY CHAPTER
Recommissioning
American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc.
(ASHRAE). Fundamentals Handbook. Atlanta: ASHRAE, 2001.
American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc.
HVACApplications Handbook. Atlanta: ASHRAE, 1995.
American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc.
Hl/ACApplications Handbook. Atlanta: ASHRAE, 1996.
ildings. TechnicalUpdate. Boulder: E SOURCE, 1997.
E SOURCE.
E SOURCE. Space Cooling Atlas.
Boulder: E SOURCE, 1997.
E SOURCE. Space HeatingAtlas.
Boulder: E SOURCE, 1996.
Turner, Wayne C. Energy Management Handbook. 2nd ed.
Lilburn, GA: The Fairmont Press Inc., 1993.
US Environmental Protection Agency ENERGY STAR program. 430-B-97-002.
; Your Energy-Efficiency Upgrade. Washington, DC: GPO, 1997.
US Environmental Protection Agency ENERGY STAR program. 430-R-97-004.
Introducing Your Company's Newest Profit Center. Washington, DC: GPO, 1997.
US Department of Energy - Energy Information Administration Office of Energy Markets
and End Use. DOE/EIA-0625(95) A 'Look at Commercial Buildings in 1995: Characteristics, En-
ergy Consumption, and Energy ExLighting
E SOURCE. Lighting Technology Atlas.
Boulder: E SOURCE, 1994.
Electric Power Research Institute. LightingBulletin,no. 6. April 1994.
Illuminating Engineering Society of North America. Lighting Handbook: Reference &
Application, 8™ ed. New York: Illuminating Engineering Society of North America, 1993.
Illuminating Engineering Society of North America. Lighting Handbook: Reference e>
Application, 9th ed. New York: Illuminating Engineering Society of North America, 2000.
Illuminating Engineering Society of North America. The Advanced Lighting Guidelines:2001
Edition. White Salmon, Washington: New Buildings Institute, Inc., 2001.
National Electrical Manufacturers Association. The Management of Spent Electric Lamps Con-
y. Washington, DC: National Electrical Manufacturers Association, 1992.
US Department of Energy. CommercialBuildingEnergy Consumption Survey.
Washington, DC: GPO, 1994.
US Environmental Protection Agency. 430-B-95-004. Lighting Waste Disposal.
Washington, DC: GPO, 1997.
ENERGY STAR® BuildingManual
-------
CHANGE R3R THE
BETTER Will I
ENERGY STAR
US Environmental Protection Agency. 430-B-95-008. Lighting Upgrade Technologies.
Washington, DC: GPO, 1997.
Electric Power Research Institute, Inc., Electric Power Research Institute, Inc., Office Com-
plexes Guidebook., Boulder: E4 Incorporated, 1997.
Portland Energy Conservation, Inc. (PECI) and Oak Ridge national Laboratory (ORNL).
ORNL/TM-1999/34. A Practical Guide for Commissioning Existing Buildings. Portland:
PECI, Oak Ridge, ORNL, 1999.
Fans
ASHRAE. HVAC Systems and Equipment Handbook. Atlanta: ASHRAE, 2000.
ASHRAE. HVACApplications Handbook. Atlanta: ASHRAE, 1999.
Bonneville Power Administration. Adjustable Speed Drive Guide Book. Olympia, WA:
Bonneville Power Administration, 1992.
California Energy Commission. Guide to Preparing Feasibility Studies for Energy Efficiency
Projects. P400-00-002. Sacramento, CA: California Energy Commission, 2000.
Englander, S.L. and L.K. Norford. "Saving Fan Energy in VAV Systems, Part 1: Analysis of a
Variable Speed Retrofit," ASHRAE Transactions 1992a: 98.
Englander, S.L. and L.K. Norford. "Saving Fan Energy in VAV Systems, Part 2: Supply Fan
Control for Static Pressurization Minimization Using DDC Zone Feedback," ASHRAE
Transactions 1992b: 98.
Lorenzetti, D., and L.K. Norford. "Measured Energy Consumption of Variable Air Volume
Fans under Inlet Vane and Variable Speed Drive Control," ASHRAE Transactions 1992.
Washington State Energy Office. Motor Master software program. Olympia, WA: 1993.
Heating and Cooling
ACEEE. Guide To Energy-Efficient Commercial Equipment, 2™1 edition. Washington, DC: The
American Council For An Energy-Efficient Economy, 2000.
ASHRAE. HVAC Applications Handbook. Atlanta: ASHRAE, 1999.
ASHRAE. HVAC Systems And Equipment Handbook. Atlanta: ASHRAE, 2000.
Cleaver Brooks. The Boiler Book, Systems Fundamentals. Milwaukee, WI: Cleaver Brooks Divi-
sion, Aqua-Chem, Inc., 1995.
E SOURCE. Commercial Space Cooling Technology Atlas. Boulder, CO: E SOURCE, 1997.
E SOURCE. Space Heating Technology Atlas. Boulder, CO: E SOURCE, 1996.
Turner, Wayne C. Energy Management Handbook. 2nd ed. Lilburn, GA: The Fairmont Press
Inc., 1993.
US Environmental Protection Agency. ENERGY STAR Web site: www.energystar.go/products.
penditures. Washington, DC: 1998.1nc., 1993.
ENERGY STAR® BuildingManual
-------
CHANGE FDR THE
BETTER WITH
ENERGY STAR
Supplemental Loads
ASHRAE journal, Sept., 1991.
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. ASHRAE
Standard 62-81. Atianta: ASHRAE, 1981.
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. ASHRAE
Standard 62-1989. Atlanta: ASHRAE, 1989.
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. ASHRAE
Standard 62-1999. Atlanta: ASHRAE, 1999.
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
Fundamentals Handbook. Atianta: ASHRAE, 1993.
US Environmental Protection Agency ENERGY STAR labeled products.
www.energystar.gov/products.
E SOURCE. Space Cooling Technology Atlas.
Boulder, CO: E SOURCE, 1995.
Means, RS. Building Construction Cost Data. Kingston, MA: R.S. Means Company, Inc.,
1996.