SRI/USEPA-GHG-VR-34
                                September 2006
Environmental Technology
Verification Report


ECR Technologies, Inc.
EarthLinked® Ground-Source Heat Pump
Water Heating System
                 Prepared by:
         Greenhouse Gas Technology Center
           Southern Research Institute
           Under a Cooperative Agreement With
        U.S. Environmental Protection Agency

-------
                                      EPA REVIEW NOTICE

This report has been peer and administratively reviewed by the U.S. Environmental Protection Agency, and
approved for publication.  Mention of trade names or commercial products does not constitute endorsement or
recommendation for use.

-------
                                                                        SRI/USEPA-GHG-VR-34
                                                                               September 2006
           THE ENVIRONMENTAL TECHNOLOGY VERIFICATION PROGRAM
       «EFA
                                                                    SOUTHERN RESEARCH
                                                                      INSTITUTE
    U.S. Environmental Protection Agency

                    ETV Joint Verification  Statement
      TECHNOLOGY TYPE:       Ground-Source Heat Pump Water Heating System

      APPLICATION:             Water Heating

      TECHNOLOGY NAME:      EarthLinked® Water Heating System

      COMPANY:                 ECR Technologies, Inc.

      ADDRESS:                  3536 DMG Drive
                                  Lakeland, FL 33811

      E-MAIL:                    info(S>ecrtech.com
The  U.S. Environmental  Protection  Agency  (EPA)  has created  the Environmental Technology
Verification  (ETV) program  to facilitate the  deployment of innovative or improved environmental
technologies through performance verification and dissemination of information.  The goal of the ETV
program is to further environmental protection by accelerating the acceptance and use of improved and
cost-effective technologies.  ETV seeks to achieve this goal by providing high-quality, peer-reviewed data
on technology performance  to those involved in the purchase, design, distribution, financing, permitting,
and use of environmental technologies

ETV works in partnership with recognized standards and testing organizations, stakeholder groups that
consist of buyers, vendor organizations, and permitters, and with the  full participation of individual
technology developers. The  program evaluates the performance of technologies by developing test plans
that are responsive to the  needs of stakeholders, conducting field or laboratory tests, collecting and
analyzing data, and preparing peer-reviewed reports. All evaluations are conducted in accordance with
rigorous quality assurance protocols to ensure that data of known and adequate quality are generated and
that the results are defensible.

The Greenhouse Gas Technology Center (GHG Center), one of six verification organizations under the
ETV program, is operated  by Southern Research  Institute in cooperation with EPA's National Risk
Management Research Laboratory.  GHG Center  stakeholders are  particularly  interested in building
heating and cooling technologies, including technologies used primarily to heat domestic hot water, with
the potential to improve efficiency and reduce concomitant GHG and criteria pollutant emissions.

The GHG Center collaborated with ECR Technologies, Inc. (ECR) to evaluate their EarthLinked Ground-
Source Heat Pump Water Heating System's performance as installed in a commercial setting. The system
incorporates a ground-sourced heat pump into a  building's water heating system.  ECR  states that the
                                            S-l

-------
                                                                           SRI/USEPA-GHG-VR-34
                                                                                   September 2006

EarthLinked system may provide up to 70% reduction in power consumption when compared to electric
water heating  systems of equivalent capacity.  This reduced energy consumption would also  reduce
emissions from the electric power system's generators or natural gas combustion in direct-fired systems.
Broad utilization of such technologies could have a significant beneficial impact on GHG and pollutant
emissions.

TECHNOLOGY DESCRIPTION

The following technology  description is based on information provided by ECR and does not represent
verified information. The  EarthLinked system typically consists of two or more 50- or 100-foot  copper
refrigerant loops (earth loops) installed in the ground, a compressor, a heat exchanger, refrigerant liquid
flow controls,  and an  active charge control.  The earth loops can be installed in horizontal, vertical, or
diagonal configurations.  The EarthLinked system circulates non-ozone depleting refrigerant (R-407c)
through the copper earth loops.  The manufacturer claims that the system's direct heat transfer from the
earth to the refrigerant is intended to improve heat transfer efficiency.

The liquid refrigerant absorbs heat from the ground,  which is typically at a constant temperature year
round (40-80 °F, depending on location), and vaporizes. A compressor raises the refrigerant pressure and
routes it to a heat exchanger.  There, the vapor condenses and  yields the latent heat of vaporization to
domestic water passing through a heat exchanger and circulating back to the hot water tanks.  Refrigerant
is then returned to the earth loops via a patented refrigerant flow control device.

The EarthLinked system consumes power in the compressor and hot water circulation pump, and has no
direct emissions.  ECR  states  that typical  EarthLinked  heating systems will  focus on commercial
applications that require a minimum of 2,000 gallons per day such as restaurants and laundries.

The reader is encouraged to note that this is a heat pump water heater and performance results cannot be
directly compared with those of conventional heating, ventilation, and air conditioning heat pumps.

The test plan  defines  the  EarthLinked heat pump as  the device under test (DUT).  The DUT  and its
integration into the host facility are known as the system under test  (SUT).

HOST FACILITY and INSTALLED SYSTEM DESCRIPTION

The Lake Towers Retirement Community, located in Sun City Center, Florida, served as the host facility.
Tests  occurred at the  Sun Terrace, a one-story building with two residential wings for assisted living.
Each wing has 15 rooms, each with a small vanity sink. Other domestic hot water (DFiW) uses include
two shower rooms, one bathtub, two utility closets, four nurses' stations, and a kitchen.

The system has four 100-ft copper earth loops installed at a depth of 100-ft and in a vertical configuration.
The facility's DFiW source consists  of two 15 kilowatt (kW), 480 V electric water heaters operating in
parallel.  Each water heater has two electric elements controlled by a single theremostat.  One element
port in each heater was removed and is used for the heated water return from the DUT. As hot water at
the site is used, cold city water enters the tanks.  ECR claims that the EarthLinked system operates most
efficiently when heating cold water.  For this installation, the average return temperature to the heat pump
was 94 °F. Table S-l lists the specifications for the EarthLinked unit installed at the site.
                                              S-2

-------
                                                                          SRI/USEPA-GHG-VR-34
                                                                                 September 2006
                              Table S-l. EarthLinked Specifications
                                 (Source: ECR Technologies, Inc.)
Model Number
Rated Performance
Rated Coefficient of Performance
Heating Capacity
Width
Depth
Height
HC-036-3A
36,000 Btu
3.7
60 gal/hra
24.375"
12.375"
26.5"
a rated at 90 °F water temperature rise
A recirculation pump continuously cycles hot water from Tanks #1 and #2 through the building's DHW
piping and back to the tanks.  The circulation loop ensures the immediate availability of hot water at each
tap throughout the facility. Thermal losses due to this loop can be substantial. For the purposes of this
test, thermal losses due to the recirculation loop are considered as part of the total site load.

VERIFICATION DESCRIPTION

A series of short-term tests and a long-term  monitoring period  were conducted to determine the
performance of the EarthLinked system as  compared to the baseline electric resistance-type hot water
heaters.

Short-term testing was conducted on May  26, 2005.  Industry-accepted American National Standards
Institute  (ANSI)  /  American  Society of Heating,  Refrigerating  and Air-Conditioning  Engineers
(ASHRAE) Type V heat pump water heater test methods formed the basis for the short-term tests.

Short-term test verification parameters were:

       •   DUT  water  heating  capacity  while raising  the  lowest achievable  city water
           temperature (likely to  be approximately 72 °F in Florida in May) 20 °F or to whatever
           temperature can be achieved over a 60-minute period (whichever occurs first), British
           thermal units per hour (Btu/h)
       •   DUT water heating capacity while raising the water temperature from  110 to 130 °F
           or over a 60-minute period (whichever occurs first), Btu/h
       •   DUT coefficient  of performance  (COP) at the lower and elevated  temperatures,
           dimensionless
       •   DUT standby  heat loss rate, Btu/h, while operating with the  EarthLinked system at
           120 ± 5 °F

Long-term monitoring began  on May 25, 2006 and continued through July 12, 2006.  The goal of the
long-term testing was to characterize the SUT performance in normal  daily use.  As such, the
ANSI/ASHRAE test method was not  valid for long-term testing.   The  ANSI/ASHRAE  method is
performed under controlled conditions over a specific temperature range and does not  characterize in-use
operations.

Long-term monitoring results allowed the assessment of:

       •   difference between  SUT  electrical  power consumption with  and  without  the
           EarthLinked system, kW
                                             S-3

-------
                                                                             SRI/USEPA-GHG-VR-34
                                                                                    September 2006

        •   hot water usage and parasitic losses, kW
        •   operational COP of the DUT, dimensionless
        •   estimated EarthLinked carbon dioxide (CO2) and oxides of nitrogen (NOX) emission
           changes as compared to the baseline electric water heater, Ib/year
        •   estimated simple cost savings based on the price of electricity saved, $/year

Rationale  for  the  experimental  design,  determination of verification parameters, detailed testing
procedures, test log forms, and quality assurance/quality control (QA/QC) procedures can be found in the
test and quality assurance plan titled Test and Quality Assurance Plan  - ECR Technologies, Inc.
EarthLinked Ground-Source Heat Pump Water Heating System (Southern Research Institute, 2005), and
the addendum to the test plan, titled Addendum to Test and Quality Assurance Plan - ECR Technologies,
Inc. EarthLinked Ground-Source Heat Pump Water Heating System (Southern Research Institute, 2006).

VERIFICATION OF PERFORMANCE
Results of the verification are representative of the EarthLinked system's performance as installed at the
Lake Towers Retirement Community.  Quality assurance (QA) oversight of the verification testing was
provided following specifications in the ETV Quality Management Plan.  This verification was supported
by an audit of data quality (ADQ) conducted by the GHG Center QA manager.  During the ADQ, the QA
manager randomly selected data supporting each of the primary verification parameters and followed the
data through the analysis and data processing system. The ADQ confirmed that no systematic errors were
introduced during data handling and processing.

Short-Term Tests

Short-term tests first measured water heating capacity and COP. Water heating capacity assesses the heat
pump's ability  to generate hot water.  COP is a dimensionless ratio  of water heating energy  output to
input energy. The short-term tests consisted of three low temperature  and three elevated temperature test
runs, as per the ANSI/ASHRAE test method for Type V water heaters. The system was configured such
that Tank #1 operated on the EarthLinked system and it was completely isolated from the facility's DHW.
The results of the test runs are shown in Table S-2.

         Table S-2. Water Heating Capacity and Coefficient of Performance for Short-Term Tests

Runl
Run 2
Run 3
Average
Low Temperature Tests3
Water Heating
Capacity (Btu/h)
35700 ± 1200
35000 ± 1200
34600 ± 1200
35100 ± 1300
COP
3.61 ±0.12
3.57 ±0.12
3.55 ±0.12
3.58 ±0.12
Elevated Temperature Testsb
Water Heating
Capacity (Btu/h)
32800 ±1100
32300 ±1100
3 1900 ±1100
32300 ±1100
COP
2.78 ±0.10
2.63 ±0.09
2.65 ±0.09
2.69 ±0.10
          For the low temperature tests, the average initial tank temperature was 82.1 ± 0.6 °F and the average final tank
         temperature was 102.3 ± 0.6 °F
         b For the high temperature tests, the average initial tank temperature was 97.6 ± 0.6 °F and the average final tank
         temperature was 120.7 ± 0.6 °F	
Standby heat loss, a measure of the heat loss  rate for the water heater, was also calculated during the
short-term  testing.  Three  standby heat loss test runs  were conducted with the system in the same
configuration as for the water heating capacity  and COP tests.  That is, the heat loss includes the
EarthLinked system, Tank #1, and the  connecting pipes.  As per the ANSI/ASHRAE test method and the
test plan, data were collected for three complete heating and cooling cycles and were used to calculate
average standby heat loss.  The results  of the test runs are shown in Table S-3.
                                               S-4

-------
                                                                           SRI/USEPA-GHG-VR-34
                                                                                   September 2006
                                   Table S-3. Standby Heat Loss

Cycle 1
Cycle 2
Cycle 3
Average
Heat Loss Rate (Btu/h)
490 ± 90
520 ± 90
450 ± 90
490 ± 90
Table S-3 shows that the average standby heat loss was calculated as 490 ± 90 Btu/h. The high heat loss
indicates that piping in the system may not be adequately insulated.

Long-Term Monitoring

During the long-term monitoring period,  the power meter monitored electricity consumption for both
tanks and the DUT.  System operators alternated between EarthLinked and resistive element heating on a
weekly schedule. A weekly schedule was chosen because GHG Center personnel predicted that day-to-
day variations in the data would likely follow  a weekly pattern.  All  electric heating elements in both
tanks were disabled when the system was under EarthLinked operation. The thermostats for Tanks #1
and #2 were set to 110 °F during both EarthLinked  and resistive element operations. This set point was
required by site management.

Analysts calculated power consumption  separately as overall  mean  real power consumption  while
operating from the EarthLinked system and from the heating elements. These measurements were then
normalized in terms of "efficiency" or mean  energy consumption over the period divided by  mean
thermal energy delivered to the site.  The change in normalized electrical power consumption (AZkw) was
calculated by subtracting the mean normalized power consumption for the SUT during the three weeks of
EarthLinked operations (Zkw EarthLmked) from  the mean normalized power  consumption for both  tanks
during the three weeks of resistive element heating (ZkWEiements).  Table S-4 summarizes the results.

                              Table S-4. Electrical Power Consumption
ZkW,EarthLinked (kW)
0.58 ±0.03
ZkWEiements (kW)
2.33±0.11
AZkw(kW)
1.75 ±0.11
% Difference
75 ± 6%
At this site, the load was substantially below the recommended range for the equipment.  Parasitic thermal
losses from the recirculation loop represent 39 ± 8% of the total load.

The average system efficiency (r\) is equal to the average rate of thermal energy delivered to the site loads
divided by the average  system input power consumption expressed in common units.  The efficiency
provides a measure of the energy delivered to site loads versus the total input energy.  It characterizes the
performance  of  the  installation, rather than simply  the  performance  of the DUT by  itself.   The
improvement in  efficiency was calculated as an average improvement  comparing the three weeks of
operation using the DUT (r|EarthLmked) to three  weeks of operation using  the heating  elements (r|Eiements).
Table S-5  summarizes these values.  The efficiency of the electric elements (r|Eiements)  was expected to be
1.00 and this result was achieved within the confidence limits.
                                              S-5

-------
                                                                            SRI/USEPA-GHG-VR-34
                                                                                   September 2006
                               Table S-5. Average System Efficiency
T|EarthLinked
4.01 ±0.07
^Elements
1.005 ±0.018
At]
3.00 ±0.07
The  operational  COP of the DUT was also calculated.   Operational COP differs from the efficiency
reported  in Table  S-5.   COP  looks  at the performance  of only the DUT and is  commonly used to
characterize heat pump technologies.  The efficiency characterizes the performance of the whole system
installation, not just the DUT. Operational COP was calculated as the rate of energy delivered by the
DUT to the site (Zkw DUT ) versus the rate of energy consumed by the DUT (Zkw EarthLmked) during actual
operating conditions. This is distinct from the COP measured in the short-term tests. The short-term tests
were performed under controlled conditions for a specific temperature range. This calculation of COP is
performed during actual operating conditions. Table S-6 summarizes the results.

                     Table S-6. Operational Coefficient of Performance of the DUT
ZkW,DUT(kW)
2.59 ±0.19
ZkW, EarthLinked (kW)
0.58 ±0.03
COP
4.43+0.09, -0.3
The average COP of the DUT during the in-use monitoring was higher than the average COP observed in
the short-term testing (refer to Table S-2).  Calculation of COP for the short-term tests was conducted
following the  ANSI/ASHRAE tests for Type V heat pump water heaters.  Analysts found that this
procedure, however useful for comparison between different pieces of equipment of the same class under
controlled circumstances, may not provide results that are directly representative  of in-service operating
conditions. Calculation of COP for the long-term tests was based on the ratio of thermal energy delivered
by the device and the electrical energy consumed by the DUT.

The procedure used for estimating SUT emission reductions correlates the estimated annual electricity
savings in megawatt-hours per year (MWh/year) with Florida  and  nationwide  electric power system
emission rates in pounds per megawatt-hour (Ib/MWh).  For this verification, analysts assumed that the
EarthLinked system operates continuously throughout the year with electric power savings as measured
during the long-term monitoring period (refer to Table S-4). Emission data from the EPA's "EGRID"
database were used to estimate state and nationwide emission rates. Table S-7 summarizes the estimated
yearly emission reductions.
                          Table S-7. Estimated Yearly Emissions Reductions

Pollutant
EREPS,i (Ib/MWh)
MWhDUT,Ann (MWh/year)
Emission Offset (Ib/year)
Florida
CO2
1420.42
NOx
3.36
Nationwide
CO2
1392.49
NOx
2.96
15 ±1
21,700 ±1,400
51±3
21,300 ±1,300
45 ±3
The procedure for estimating SUT simple cost savings is based on the Florida and nationwide prices for retail
electricity at "commercial" rates. Varying prices for retail electricity can be found in many resources. This
methodology of estimating simple cost savings uses the prices found in the Energy Information Agency's
Table 5.6.A. Average Retail Price of Electricity to Ultimate Customers by End-Use Sector, by State. Similar
to emissions reductions, analysts assumed that the EarthLinked system operates continuously throughout the
year with electric power savings as measured during the long-term monitoring period.  The EarthLinked
                                              S-6

-------
                                                                                  SRI/USEPA-GHG-VR-34
                                                                                          September 2006

system does not use auxiliary fuel, nor is it intended as a power source, so their potential costs or revenues are
not considered for this verification. Table S-8 summarizes the estimated yearly cost savings.

                               Table S-8. Estimated Yearly Cost Savings*

MWhDUT,Ann (MWh/year)
RPeiec (cents/kWh)
Simple Cost Savings (dollars/year)
Florida
Nationwide
15 ±1
9.88
1,500 ±100
9.2
1,410 ±90
                 * Based on approximately 630 gallons per day average consumption on site. The
                 intended load for this product is 2,000 gallons per day.	

Details on the verification test design, measurement test procedures, and QA/QC procedures can be found in
the test plan, titled Test and Quality Assurance Plan - ECR Technologies, Inc. EarthLinked Ground-Source
Heat Pump Water Heating System (Southern  Research Institute 2005), and the test plan addendum, titled
Addendum to Test and Quality Assurance Plan - ECR Technologies, Inc. EarthLinked Ground-Source Heat
Pump  Water Heating System (Southern  Research Institute  2006).  Detailed results of the verification  are
presented in the final report, titled Environmental Technology Verification Report for ECR Technologies, Inc.
EarthLinked Ground-Source Heat Pump Water  Heating System (Southern Research Institute 2006).  Both
can be downloaded from the  GHG Center's web-site (www.sri-rtp.com)  or the  ETV Program web-site
(www.epa.gov/etv).
 Signed by Sally Gutierrez 09/27/06	         Signed by Richard Adamson 09/20/06

Sally Gutierrez                                        Richard Adamson
Director                                               Director
National Risk Management Research Laboratory        Greenhouse Gas Technology Center
Office of Research and Development                   Southern Research Institute
       Notice:  GHG Center verifications are based on an evaluation of technology performance under specific,
       predetermined criteria and the appropriate quality assurance procedures.  The EPA and Southern Research
       Institute make no expressed or implied warranties as to the performance of the technology and do not certify
       that a technology will always operate at the levels verified. The end user is solely responsible for complying
       with any and all applicable Federal, State, and Local requirements. Mention of commercial product names does
       not imply endorsement or recommendation.	
                                           EPA Review Notice
        This report has been peer and administratively reviewed by the U.S. Environmental Protection Agency, and
        approved for publication. Mention of trade names or commercial products does not constitute endorsement or
        recommendation for use.
                                                  S-7

-------
                                             SRI/USEPA-GHG-VR-34
                                                     September 2006
(this page intentionally left blank)
              S-8

-------
                                                     SRI/USEPA-GHG-VR-34
                                                           September 2006
 Greenhouse Gas Technology Center
A U.S. EPA Sponsored Environmental Technology Verification ( ETV ) Organization
     Environmental Technology Verification Report

                  ECR Technologies, Inc.
       EarthLinked® Ground-Source Heat Pump
                  Water Heating System
                          Prepared By:
                  Greenhouse Gas Technology Center
                     Southern Research Institute
                         PO Box 13825
                Research Triangle Park, NC 27709 USA
                     Telephone: 919/806-3456

                  Under EPA Cooperative Agreement

                 U.S. Environmental Protection Agency
                  Office of Research and Development
             National Risk Management Research Laboratory
              Air Pollution Prevention and Control Division
               Research Triangle Park, NC 27711   USA

               EPA Project Officer:  David A. Kirchgessner

-------
                                              SRI/USEPA-GHG-VR-34
                                                     September 2006
(this page intentionally left blank.)

-------
                                                              SRI/USEPA-GHG-VR-34
                                                                    September 2006

                             TABLE OF CONTENTS

                                                                              Page

LIST OF FIGURES	ii
LIST OF TABLES	ii
DISTRIBUTION LIST	iii
ACKNOWLEDGEMENTS	iv
ABBREVIATIONS AND ACRONYMS	v

1.0   INTRODUCTION	1-1
     1.1   BACKGROUND	1-1
     1.2   EARTHLINKED TECHNOLOGY DESCRIPTION	1-2
     1.3   HOST FACILITY AND INSTALLED SYSTEM INTEGRATION	1-3
     1.4   PERFORMANCE VERIFICATION OVERVIEW	1-6

2.0   VERIFICATION RESULTS	2-1
     2.1   SHORT-TERM TEST RESULTS	2-1
          2.1.1   Water Heating Capacity and COP	2-1
          2.1.2   Standby Heat Loss	2-3
     2.2   LONG-TERM MONITORING RESULTS	2-4
          2.2.1   Electrical Power Consumption	2-4
          2.2.2   Parasitic Losses	2-5
          2.2.3   Average System Efficiency	2-8
          2.2.4   Operational COP of the OUT	2-9
          2.2.5   Estimated Emissions  Reductions	2-10
          2.2.6   Estimated Simple Cost Savings	2-11

3.0   DATA QUALITY ASSESSMENT	3-1
     3.1   DATA QUALITY OBJECTIVES	3-1
     3.2   RECONCILIATION OF DQOS AND DQIS	3-1
     3.3   AUDITS	3-4

4.0   TECHNICAL AND PERFORMANCE DATA SUPPLIED BY ECR
     TECHNOLOGIES	4-1

5.0   REFERENCES	5-1

-------
                                                                          SRI/USEPA-GHG-VR-34
                                                                                 September 2006
                                     LIST OF FIGURES
                                                                                   Page
Figure 1-1.  Plumbing Schematic and Sensor Locations	1-4
Figure 1-2.  System Electrical Schematic and Power Meter Location	1-4
Figure 1-3.  Lake Towers Installation	1-5
Figure 1-4.  EarthLinked Water Heating System Compressor Unit	1-6
Figure 2-1.  Parasitic Losses and Site Load for One Week	2-6
Figure 2-2.  Thermal Load Duration Curve over the Long-Term Monitoring	2-7
Figure 2-3.  Electrical Load Duration Curve for the Heat Pump and Electric Elements	2-8
                                     LIST OF TABLES
                                                                                   Page
Table 1-1. EarthLinked Specifications	1-3
Table 2-1. Heat Pump Water Heating Capacity and Coefficient of Performance for
          Short-Term Tests	2-2
Table 2-2. Standby Heat Loss	2-4
Table 2-3. Electrical Power Consumption	2-5
Table 2-4. Average  System Efficiency	2-9
Table 2-5. Operational COP of the OUT	2-10
Table 2-6. Estimated Yearly Emissions Reductions	2-11
Table 2-7. Estimated Yearly Simple Cost Savings*	2-11
Table 3-1. Instrument and Accuracy Specifications	3-2
Table 3-2. QA/QC Checks	3-3
Table 3-3. Crosscheck between Type V and Type IV Test Methods	3-3

-------
                                                                        SRI/USEPA-GHG-VR-34
                                                                               September 2006
                                  DISTRIBUTION LIST
U.S. EPA
       David Kirchgessner
       Robert Wright

Southern Research Institute
       Richard Adamson
       Bill Chatterton

ECR Technologies, Inc.
       Joe Parsons

Johnson Research, LLC
       Russ Johnson

CANMET Energy Technology Centre
       Chris Snoek
                                            in

-------
                                                                           SRI/USEPA-GHG-VR-34
                                                                                  September 2006
                                  ACKNOWLEDGEMENTS
The Greenhouse Gas Technology Center wishes to thank Joe Parsons, Russ Bath, and Shan Shevade of
ECR Technologies for their assistance with this verification. Thanks are also extended to Russ Johnson,
editor of the "In Hot Water" newsletter, and Chris Snoek of CANMET Energy Technology Centre for
their inputs to this Verification Report.  Finally, thanks go to the staff at the Lake Towers Retirement
Community for their assistance with field activities.
                                              IV

-------
                                                                         SRI/USEPA-GHG-VR-34
                                                                                September 2006
                            ABBREVIATIONS AND ACRONYMS
ADQ         audit of data quality
ANSI         American National Standards Institute
ASHRAE     American Society of Heating, Refrigerating, and Air-Conditioning Engineers
Btu/h         British thermal units per hour
CO           carbon monoxide
CO2          carbon dioxide
COP          coefficient of performance
DHW         domestic hot water
DQI          data quality indicator
DQO         data quality objective
DUT         device under test
ECR          ECR Technologies, Inc.
EPA          U.S. Environmental Protection Agency
ETV          Environmental Technology Verification
GHG Center   Greenhouse Gas Technology Center
kW           kilowatt
kWh          kilowatt-hour
lb/ft3          pounds per cubic foot
Ib/MWh       pounds per megawatt-hour
MWh         megawatt-hour
NOx          oxides of nitrogen
QA/QC       quality assurance / quality control
QMP         quality management plan
Southern      Southern Research Institute
SUT          system under test

-------
                                             SRI/USEPA-GHG-VR-34
                                                     September 2006
(this page intentionally left blank)
               VI

-------
                                                                            SRI/USEPA-GHG-VR-34
                                                                                   September 2006
                                     1.0  INTRODUCTION
     1.1     BACKGROUND

The  U.S. Environmental Protection Agency's (EPA) Office of Research and Development operates the
Environmental  Technology  Verification  (ETV)  program  to  facilitate the  deployment  of innovative
technologies. The program's goal is to further environmental protection by accelerating the acceptance
and  use of these  technologies.  Primary  ETV activities are independent performance verification and
information dissemination. Congress funds ETV in response to the belief that many viable environmental
technologies exist that are not being used for the lack of credible third-party  performance data.  With
performance data developed under this program, technology buyers, financiers, and permitters will be
better equipped to make informed decisions regarding new technology purchases and use.

The  Greenhouse Gas Technology Center (GHG Center) is one of several ETV organizations.  EPA's ETV
partner, Southern Research Institute (Southern), manages the GHG Center.  The GHG Center conducts
independent verification of promising energy  efficiency,  GHG mitigation, and GHG  monitoring
technologies. It develops verification Test and Quality Assurance Plans (test plans),  conducts field tests,
collects and interprets field and other data, obtains independent peer-review input, reports findings, and
publicizes verifications through numerous outreach efforts.  The GHG Center conducts verifications
according to the externally reviewed test plans and recognized quality assurance/quality control (QA/QC)
protocols.

Volunteer stakeholder  groups guide the GHG Center's ETV activities.  These stakeholders advise on
appropriate technologies for testing, help disseminate results, and review test plans and reports. National
and  international environmental policy,  technology, and  regulatory experts  participate in the GHG
Center's Executive Stakeholder Group. The  group includes industry trade organizations, environmental
technology finance groups, governmental organizations,  and other interested parties.  Industry-specific
stakeholders provide testing strategy guidance within their expertise and peer-review key documents
prepared by the GHG Center.

GHG Center stakeholders are  particularly  interested in building heating  and  cooling technologies,
including technologies used primarily to heat  domestic hot water, with the potential to improve efficiency
and  reduce concomitant GHG and criteria pollutant emissions.  The Energy Information Administration
reports that in 1999 approximately 3.1 million commercial  facilities in the U.S. consumed about 4.8 x
1012  British thermal units per year (Btu/y). The portion of this energy consumption that is attributable to
water heating varies significantly by facility type, but it averages about 11%, or 5.3 x 1011 Btu/y.

ECR Technologies, Inc. (ECR) has addressed  this issue with their EarthLinked water heating system.  The
system incorporates a ground-sourced heat pump into a building's water heating system. ECR states that
the EarthLinked system may provide  up to  70% reduction in power consumption when compared to
electric water heating  systems of equivalent capacity.   This  reduced energy  consumption would  also
reduce emissions  from the electric power system's generators or natural gas combustion  in direct-fired
systems. Broad utilization of such technologies could have a significant beneficial impact on GHG and
pollutant emissions.

The  GHG Center conducted  a performance evaluation of the EarthLinked water heating system installed
at a retirement community in Sun City Center, Florida. Testing began in May 2005 with a series of short-
term tests to determine the EarthLinked heat pump's performance.  A four-week long-term  monitoring
                                              1-1

-------
                                                                            SRI/USEPA-GHG-VR-34
                                                                                   September 2006

period followed.  In the course of performing the testing and analysis in accordance with the initial test
plan, it was determined that the installation was not representative of what could be considered a 'typical'
retro-fit installation for the subject technology. As the installation was originally configured, the heat
pump did not contribute energy to the overall site load unless there was hot water usage.  The heat pump
did not contribute energy to supporting the parasitic loads in the system. Further, it was determined that
the data collected was inadequate to credibly and accurately reflect the performance  of a  'typical'
installation.  With that conclusion, it was determined that:

    1) the data collected during the short-term testing performed under the original test plan is reflective
       of the performance of the 'device under test' (DUT) under controlled circumstances,  but may not
       be under in-service operating conditions;
    2) the integration with the site, which constitutes the 'system under test' (SUT), should  be modified
       to be more reflective of a typical retrofit installation; and
    3) data generated during the original long-term testing is invalid and testing should be repeated with
       a suitably modified instrumentation arrangement to correspond to the new configuration.

The modified system configuration is shown in Figure 1-1.  In this configuration the heat pump supports
the site's parasitic loads, even in the absence of hot water usage.

Details on the verification test design, measurement test procedures, and QA/QC procedures can be found
in the test plan, titled Test and Quality Assurance Plan - ECR Technologies, Inc.  EarthLinked Ground-
Source Heat Pump Water Heating System [1], and the test plan addendum, titled Addendum to  Test and
Quality Assurance  Plan - ECR  Technologies, Inc.  EarthLinked Ground-Source Heat Pump  Water
Heating System [2]. They can be downloaded from the GHG Center's website (www.sri-rtp.com) or the
ETV  program  website (www.epa.gov/etv).    The test plan describes  the DUT,  the  SUT, project
participants, original test procedures, site specific instrumentation and measurements, and verification
specific QA/QC goals.  The test plan addendum documents the adjustments to  the instrumentation and
analysis  corresponding to the new system configuration.  Both documents were  reviewed  and revised
based on comments received from ECR Technologies and the EPA Quality Assurance Team.  The test
plan and test plan addendum meet the requirements of the GHG Center's Quality  Management Plan
(QMP) and satisfy the ETV QMP requirements.

The remainder  of Section 1.0 describes the EarthLinked water heating system  technology  and the test
facility, and outlines the performance verification procedures that were followed.  Section  2.0 presents
test results, and Section 3.0 assesses  the quality of the data obtained.  Section 4.0, submitted by ECR
Technologies, presents additional information regarding the system. Information provided in Section 4.0
has not been independently verified by the GHG Center.
     1.2     EARTHLINKED TECHNOLOGY DESCRIPTION

The  following technology description is based on information provided by ECR and does not represent
verified information. The EarthLinked system typically consists of two or more 50- or 100-foot copper
refrigerant loops (earth loops) installed in the  ground, a compressor, a heat exchanger, refrigerant liquid
flow controls, and an active charge control.  The earth loops can be installed in horizontal, vertical, or
diagonal configurations.  The EarthLinked system  circulates non-ozone  depleting refrigerant (R-407c)
through the copper earth loops.  The manufacturer claims that the system's direct heat transfer from the
earth to the refrigerant is intended to improve heat transfer efficiency.
                                              1-2

-------
                                                                           SRI/USEPA-GHG-VR-34
                                                                                   September 2006

The liquid refrigerant absorbs heat from the ground, which is typically at a constant temperature year
round (40-80 °F, depending on location), and vaporizes. A compressor raises the refrigerant pressure and
routes it to a heat exchanger. There, the vapor condenses and yields the latent heat of vaporization to
domestic water passing through a heat exchanger and circulating back to the hot water tanks. Refrigerant
is then returned to the earth loops via a patented refrigerant flow control device.

The EarthLinked system consumes power in the compressor and hot water circulation pump, and has no
direct emissions.   ECR  states  that typical  EarthLinked heating  systems  will  focus on commercial
applications that require a minimum of 2,000 gallons per day such as restaurants and laundries.

The reader is encouraged to note that this is a heat pump water heater and performance results cannot be
directly compared with those of conventional heating, ventilation, and air conditioning heat pumps.

The test plan defines the EarthLinked heat pump as the DUT. The DUT and its integration into the host
facility are known as the SUT. Figure 1-1 shows DUT and SUT boundaries.
     1.3     HOST FACILITY AND INSTALLED SYSTEM INTEGRATION

The Lake Towers Retirement Community, located in Sun City Center, Florida, served as the host facility.
Tests occurred at the Sun Terrace, a one-story building with two residential wings for assisted living.
Each wing has 15 rooms, each with a small vanity sink. Other domestic hot water (DFiW) uses include
two shower rooms, one bathtub, two utility closets, four nurses' stations, and a kitchen.

The system has four 100-ft copper earth loops installed at a depth of 100-ft and in a vertical configuration.
The facility's DFiW source consists of two 15 kilowatt (kW), 480 V electric water heaters operating in
parallel.  Each water heater has two electric elements controlled by a single theremostat.  One  element
port in each heater was removed and is used for the heated water return from the DUT. As hot water at
the site is used, cold city water enters the tanks.  ECR claims that the EarthLinked system operates most
efficiently when heating cold water. For this installation, the average return temperature to the heat pump
(T2 in Figure 1-1)  was  94 °F.  Table 1-1 lists the specifications for the EarthLinked unit installed at the
site.
                               Table 1-1. EarthLinked Specifications
                                  (Source: ECR Technologies, Inc.)
Model Number
Rated Performance
Rated Coefficient of Performance
Heating Capacity
Width
Depth
Height
HC-036-3A
36,000 Btu
3.7
60 gal/hra
24.375"
12.375"
26.5"
a rated at 90 °F water temperature rise
Figure 1-1 shows the plumbing schematic and sensor locations for the installation. It also shows the DUT
and SUT boundaries. Figure 1-2 shows the system electrical schematic and power meter location.
                                              1-3

-------
                                                                                      SRI/USEPA-GHG-VR-34
                                                                                               September 2006
                                                                                                       SUT
   TO SINK,
SHOWERS, ETC.
                                                                                                      OUT
    WATER METER
     TOTALIZER
    CITY WATER IN
CONNECT
AT 1.5" '
3UNGHOLE
:TER
1RN
XT \
f I \DRAIN
VALVE

CONNECT
AT 1.5" '
BUNGHOLE
XT \
' I \DRAIN
VALVE
/
                                                                                    FLOW
                                                                                   METER
                                                                                   BYPASS
                                   T4
                          Figure 1-1. Plumbing Schematic and Sensor Locations
                                                                       Earthlinked Geothermal Heat Pump
                           Note: One element port for each otthe two tanks is used torthe heated water return ports from the OUT.


                    Figure 1-2. System Electrical Schematic and Power Meter Location
                                                    1-4

-------
                                                                              SRI/USEPA-GHG-VR-34
                                                                                     September 2006

A recirculation pump continuously cycles hot water from Tanks #1 and #2 through the building's DHW
piping and back to the tanks.  The circulation loop ensures the immediate availability of hot water at each
tap  throughout the facility. Thermal losses due to this loop can be substantial.  For the purposes of this
test, thermal losses due to the recirculation loop are considered as part of the total site load.

Figure 1-3 shows the Lake Towers installation and  Figure  1-4  shows the EarthLinked water heating
system compressor unit.
                                Figure 1-3. Lake Towers Installation
                                               1-5

-------
                                                                           SRI/USEPA-GHG-VR-34
                                                                                  September 2006
                   Figure 1-4. EarthLinked Water Heating System Compressor Unit
     1.4     PERFORMANCE VERIFICATION OVERVIEW

A series of short-term  tests  and a long-term monitoring period were  conducted to determine the
performance of the EarthLinked system as compared to the baseline electric resistance-type hot water
heaters.

Short-term testing was conducted on May 26, 2005.  Industry-accepted American  National Standards
Institute  (ANSI)  /  American  Society of Heating,  Refrigerating and  Air-Conditioning  Engineers
(ASHRAE) Type V heat pump water heater test methods [3]  formed the basis for the short-term tests.
This is a quasi-steady-state test that measures the change in temperature of the storage tank over time.
The  short-term tests were conducted with the system in its original piping configuration, as described in
the test plan  [1]. A diagram of the original piping configuration is also in the test plan.

Short-term test verification parameters were:

       •   DUT  water heating  capacity while  raising the lowest  achievable  city  water
           temperature (likely to be approximately 72 °F in Florida in May) 20 °F or to whatever
           temperature can be achieved over a 60-minute period (whichever occurs first), British
           thermal units per hour (Btu/h)
       •   DUT water heating capacity while raising the water temperature from 110 to 130 °F
           or over a 60-minute period (whichever occurs first), Btu/h
       •   DUT coefficient of performance (COP) at  the lower and elevated temperatures,
           dimensionless
       •   DUT standby heat loss rate, Btu/h, while operating with the EarthLinked system at
           120 ± 5 °F

Long-term monitoring began on May 25, 2006  and continued through July 12, 2006. The goal of the
long-term testing was to  characterize the SUT  performance  in normal daily use.   As such, the
ANSI/ASHRAE test method  was not valid  for  long-term testing.  The  ANSI/ASHRAE  method is
performed under controlled conditions over a specific temperature range and does not characterize in-use
operations.
                                              1-6

-------
                                                                            SRI/USEPA-GHG-VR-34
                                                                                   September 2006

Long-term monitoring occurred with the system in the modified piping configuration, depicted in Figure
1-1.  Monitoring began with the tanks operating on the EarthLinked water heating system and the electric
elements disabled.  After a period of one week, ECR operators set the controls for the tanks to operate on
the electric heating elements and disabled the EarthLinked system for one week. This pattern continued
for six weeks. A weekly schedule was chosen because GHG Center personnel predicted that day-to-day
variations in the data would  likely  follow a weekly pattern.  GHG Center personnel periodically
downloaded test data from the local data acquisition system by telephone modem.

Long-term monitoring results allowed the assessment of:

       •   difference between SUT electrical  power consumption  with and without  the
           EarthLinked system, kW
       •   hot water usage and parasitic losses, kW
       •   operational COP of the DUT, dimensionless
       •   estimated EarthLinked carbon dioxide  (CO2) and oxides of nitrogen (NOx) emission
           changes as compared to the baseline electric water heater, Ib/year
       •   estimated simple cost savings based on the price of electricity saved, dollars/year

Circulating flow rate through the  DUT, as  measured by Flow Meter 1 in Figure 1-1, and the
change in temperature across the DUT, measured at Tl and T2, provide a measure of the thermal
energy delivered to the hot water tanks.  Flow Meter 3 and the differential temperature between
T3 and T5 provide a measure of the parasitic thermal energy lost in the recirculation loop.  The
difference between the flow measurement at Flow Meter 2 and  Flow Meter 3 and the differential
temperature measured across T4 and  T3 provides a measure of the thermal energy delivered to
the intended loads.  That is, the  total thermal  energy delivered to the site less the parasitic losses.
                                              1-7

-------
                                             SRI/USEPA-GHG-VR-34
                                                     September 2006
(this page intentionally left blank)

-------
                                                                           SRI/USEPA-GHG-VR-34
                                                                                  September 2006
                               2.0  VERIFICATION RESULTS

Results of the verification are representative of the EarthLinked system's performance as installed at the
Lake  Towers Retirement  Community.  Performance  of ground-source heat pumps is known to be
dependent on sub-soil temperatures. Results obtained in different geographic areas may differ from those
obtained at this site in Florida.
2.1   SHORT-TERM TEST RESULTS
2.1.1   Water Heating Capacity and COP

Short-term testing measured water heating capacity and COP.  Water heating capacity assesses the heat
pump's ability to generate hot water.  COP is a dimensionless ratio  of water heating energy output to
input energy.

The short-term tests consisted of three low temperature and three elevated temperature test runs, as per
the ANSI/ASHRAE test method for Type V water heaters.   ECR personnel installed the EarthLinked
system on Tank #1,  with provisions to operate either the tank's  electric  heating  elements  or the
EarthLinked system.  GHG Center personnel isolated Tank #1 from the facility's DFiW during the short-
term tests, with the  site operating  solely on Tank #2  during the  test period.  A summary  of the
ANSI/ASHRAE test procedure for the short-term testing follows:

    1.  Completely drain Tank # 1 and refill with the coldest possible city water.  Enable data logging.
   2.  Disable Tank #1 heating  elements, record the  mean tank temperature,  Tmho, and enable the
       EarthLinked system.
   3.  Continue the test until T^ has increased by 20 °F or until 60  minutes have elapsed.  Record the
       final mean tank temperature, Tmhf, and actual elapsed time for the final T^f reading.
   4.  Repeat steps 1 through 3 until three valid test runs are completed.
   5.  Raise the mean Tank #1 temperature, either with the heat pump or heating elements, to 110 °F.
   6.  Disable Tank #1 heating elements, record the initial mean tank temperature, T^o, and enable the
       EarthLinked system. Enable data logging.
   7.  Continue the test until Tmh has increased by 20 °F or until 60  minutes have elapsed.  Record the
       final mean tank temperature, T^f, and actual elapsed time for the final T^f reading.
   8.  Admit cold water into the tank while discharging heated water  until T^ is less than 110 °F. Raise
       the mean tank temperature back to 110 °F.
   9.  Repeat  steps 5  through 8 until three valid test  runs are completed at the  elevated
       temperature.

Water heating capacity (§10.3.2 of [3]) is calculated as:
Vx
n -
' cp ]
•,CI,XV)
X\*-mhf -*-mhO/
+ n
                                                    hs
                                                                         Eqn. 2-1
                                              2-1

-------
        where:
                                                                               SRI/USEPA-GHG-VR-34
                                                                                       September 2006
               Qh = Water heating capacity, Btu/h
               V =  Storage tank capacity, gal (116.3 for this test series)
               Cp =  Specific heat of water at the mean of Tmhf and Tmho (from [4]), Btu/lb °F
               Cfg = Volume conversion factor, 7.48055 gal/ft3
               v  = Specific volume of water at the mean system pressure (from [5]), ft3/lb
               Tmhf =  Final mean tank temperature (as the average of 6 in-tank sensors), °F
               Tmho  = Initial mean tank temperature (as the average of 6 in-tank sensors), °F
               tm =  Final time stamp, h
               toh = Initial time stamp, h
               Qhs = Mean storage tank heat loss rate as calculated in Equation 2-5, Btu/h or as
                      estimated from manufacturer's data  (341.2 Btu/h for this test series)
Electric power usage is:
                Qhe =
                       CgexZh
Eqn. 2-2
        where:
COP is:
               Qhe  = Electric power consumption as Btu/h
               Cge  = Power conversion factor, 3412 Btu/kV
               Zh = Electric energy consumption, kWh
                COPh =
                         Q
Eqn. 2-3
                           he
The results of the test runs are shown in Table  2-1.  The average water heating capacity for the low
temperature tests was 35,100 ± 1,300 Btu/h.  This yields an average COP of 3.58 ± 0.12.  The average
water heating capacity for the elevated  temperature tests was  32,300 ±  1,100 Btu/h.   This yields an
average COP of 2.69 ±0.10.
    Table 2-1. Heat Pump Water Heating Capacity and Coefficient of Performance for Short-Term Tests

Runl
Run 2
Run 3
Average
Low Temperature Tests"
Water Heating
Capacity (Btu/h)
35700 ± 1200
35000 ± 1200
34600 ± 1200
35100 ± 1300
COP
3.61 ±0.12
3.57 ±0.12
3.55 ±0.12
3.58 ±0.12
Elevated Temperature Tests*
Water Heating
Capacity (Btu/h)
32800 ±1100
32300 ±1100
3 1900 ±1100
32300 ±1100
COP
2.78 ±0.10
2.63 ±0.09
2.65 ±0.09
2.69 ±0.10
         " For the low temperature tests, the average initial tank temperature was 82.1 ± 0.6 °F and the average final tank
         temperature was 102.3 ± 0.6 °F
         b For the high temperature tests, the average initial tank temperature was 97.6 ± 0.6 °F and the average final tank
         temperature was 120.7 ± 0.6 °F	
                                                2-2

-------
                                                                             SRI/USEPA-GHG-VR-34
                                                                                     September 2006
2.1.2    Standby Heat Loss
Standby heat loss, a measure of the heat loss rate for the water heater, was also calculated during the
short-term  testing.   Three standby heat loss test runs were conducted with the system in the same
configuration as for the water heating capacity and COP tests (see  §2.1.1).  That is, the heat loss includes
the EarthLinked system, Tank #1, and the connecting pipes. As per the ANSI/ASHRAE test method and
the test plan, data were collected for three complete heating and cooling cycles and were used to calculate
average standby heat loss. The tank heat loss parameter for each complete cooling / heating cycle is:
                                     ' t-Ohs
                                            Cf XV
                                            —	                               Eqn. 2-4
       where:
               Lhs = Heat loss parameter, Btu/h.°F
               Tmhsf = Final mean tank temperature (as the average of 6 in-tank sensors), °F
               Tahsf = Final test room dry bulb temperature, °F
               Tmhso = Initial mean tank temperature (as the average of 6 in-tank sensors), °F
               Tahso = Initial test room dry bulb temperature, °F
               V = Storage tank capacity, gal
               Cp =  Specific heat of water at the mean of Tmhf and Tmho (from [4]), Btu/lb °F
               Cfg = Volume conversion factor, 7.48055 gal/ft3
               v =  Specific volume of water at the mean of Tmhf and Tmho (from [5]), ft3/lb
               tfhS = Final time stamp for the individual cooling / heating cycle, h
               t0hs = Initial time stamp for the individual cooling / heating cycle, h

Analysts calculated the mean heat loss parameter as the average of the three individual results from the
monitored cooling / heating cycles.

The tank's heat loss rate is:

                               Cx   -T  )+(T   -T  )
                             ,, \  mhO    ahO /  \ mhf     ahf /                         TJ	„  o c
               Qhs  =

       where:
               Qhs = Heat loss rate, Btu/h
               Lhs,mean =  Mean heat loss parameter, Btu/h °F
               Tmho = Initial mean tank temperature (as the average of 6 in-tank sensors), °F
               Taho  = Initial test room dry bulb temperature, °F
               Tmhf = Final mean tank temperature (as the average of 6 in-tank sensors), °F
               Tahf  = Final test room dry bulb temperature, °F
The results of the test runs are shown in Table 2-2. The average standby heat loss was calculated as 490 ±
90 Btu/h.  The high heat loss indicates that piping in the system may not be adequately insulated.
                                               2-3

-------
                                                                          SRI/USEPA-GHG-VR-34
                                                                                  September 2006
                                  Table 2-2. Standby Heat Loss

Cycle 1
Cycle 2
Cycle 3
Average
Heat Loss Rate (Btu/h)
490 ± 90
520 ± 90
450 ± 90
490 ± 90
2.2   LONG-TERM MONITORING RESULTS

During the long-term monitoring period, the power meter monitored electricity consumption for both
tanks and the DUT.  System operators alternated between EarthLinked and resistive element heating on a
weekly schedule.  All electric heating elements in both tanks were disabled when the system was under
EarthLinked operation.  The thermostats for Tanks #1 and #2 were set to 110 °F during both EarthLinked
and resistive element operations. This set point was required by site management.

Long-term monitoring began with the tanks operating on the EarthLinked system. The system operated in
this configuration for one week before it was switched to operate on the electric heating elements. This
configuration pattern began on May 25, 2006 and continued for six weeks, with the completion of long-
term monitoring on July 12, 2006.
2.2.1   Electrical Power Consumption

Analysts calculated power consumption separately as overall  mean  real power consumption while
operating from the EarthLinked system and from the heating elements.  These measurements were then
normalized in terms  of "efficiency" or mean energy consumption over the period divided by mean
thermal energy delivered to the site. Normalized power consumption for each week was calculated as
follows:
       where:
              Zkw,i,N = normalized power consumption for week "i", kW
              Zs = mean rate of energy delivered to site over all 6 weeks of monitoring, kW
              ZS1 = mean rate of energy delivered to the site during week "i", kW
              Zkw j = mean power consumption during week "i", kW

The mean rate of energy delivered to the site, Zs, was calculated as the sum of the rate of energy delivered
to loads such as showers and sinks, ZL, and the rate of parasitic losses in the recirculation loop, ZP.  The
equations are as follows:

              ZL=(F2-F3)x(T4-T3)xCpxp                        Eqn. 2-7


              Zp=(T5-T3)xF3xC  xp                                Equ. 2-8
                                             2-4

-------
                                                                            SRI/USEPA-GHG-VR-34
                                                                                   September 2006

               Zs = ZL + ZP                                             Eqn. 2-9

       where:
               F2 = water flow rate measured by Flow Meter #2
               F3 = water flow rate measured by Flow Meter #3
               T3, T4, T5 = temperatures measured at locations on Figure 1-1
               Cp = the heat capacity of water and is a function of temperature and pressure;
               p = the density of water, also a function of temperature and pressure.

The change in normalized electrical power consumption (AZkw) was calculated by subtracting the mean
normalized power consumption for the  SUT during the  three weeks  of EarthLinked  operations
(Zkw,EarthLinked) from the mean normalized power consumption for both tanks during the three weeks of
resistive element heating (ZkWEiements).  Table 2-3 summarizes  the results.   The average difference in
power consumption for the two heating systems was 1.75 ± 0.11 kW.   This is a 75 ± 6% decrease in
power consumption with the EarthLinked system.

                              Table 2-3. Electrical Power Consumption
ZkW,EarthLinked (kW)
0.58 ±0.03
ZkWEiements (kW)
2.33±0.11
AZkW(kW)
1.75 ±0.11
% Difference
75 ± 6%
2.2.2   Parasitic Losses

The site's recirculation pump continuously circulates water through the hot water system and back to the
heating tanks.  This ensures a minimum delay at the tap when a resident calls for hot water.  Depending
on the flow rate and insulation on the supply and return piping, thermal losses due to this circulation can
be substantial.  These losses are defined  as the parasitic losses for this system.  Figure 2-1 shows the
average rate of thermal energy delivered to the site (Zs)  and the parasitic loss rate (ZP) due to the
recirculation loop  during one week in the  monitoring period.  The chart depicts a two-hour rolling
average, which smoothes out fluctuations in the data to show the trends more clearly.
                                              2-5

-------
                                                                            SRI/USEPA-GHG-VR-34
                                                                                   September 2006
                                               1 week

                       Figure 2-1. Parasitic Losses and Site Load for One Week

The parasitic load was fairly constant throughout the week. This is typical of all weeks in the monitoring
period.  Overall, the average rate of thermal energy delivered to the site (Zs) for the monitoring period
was 2.34 ± 0.17 kW. The average rate of thermal energy delivered to loads such as sinks and showers (ZL)
was  1.43 ±  0.03  kW.  The average parasitic loss rate for the six-week period was 0.91 ± 0.03 kW,
accounting for 39 ± 8% of the average rate of thermal energy delivered to the site.

Figure 2-2 shows a load duration curve for the rate of thermal energy delivered to the site (Zs) over the
six-week monitoring period in 15-minute demands.  The chart  shows that both the heat pump and the
water heaters were oversized for this installation.
                                              2-6

-------
                                                                             SRI/USEPA-GHG-VR-34
                                                                                    September 2006
    35 n
    30
    25
    20
    15
    10
         coLOcot-coc0a)t-^rr^a)CNLO
                t-t-t-t-CNCNCNCNCOCO
                                                                ss  ss ss ss  ss
                                                                r^  o rsi in  co
                                                                              ss  ss ss ss  ss ss
               Figure 2-2. Thermal Load Duration Curve over the Long-Term Monitoring


Figure 2-3 shows an electrical load duration curve in 15-minute  demands for the  three weeks of
EarthLinked heat pump operations and the three weeks of resistive element operations. The chart shows
that the EarthLinked unit reduced the overall energy usage and peak power demand. The shape of the
plots also shows that the heat pump tends to cycle at a lower frequency than the electric elements, which
lowers peaks.
                                               2-7

-------
                                                                             SRI/USEPA-GHG-VR-34
                                                                                     September 2006
           Figure 2-3. Electrical Load Duration Curve for the Heat Pump and Electric Elements
2.2.3   Average System Efficiency

The average system efficiency (r\) is equal to the average rate of thermal energy delivered to the site loads
divided by the average system input power consumption expressed in common units.  The efficiency
provides a measure of the energy delivered to site loads versus the total input energy.  It characterizes the
performance of the installation, rather than simply the performance of the DUT by itself.  Efficiency is
calculated as:
                                                                   Eqn. 2-10
Thus, for the resistive elements case:
                I elements
And for the DUT case:
                                                                   Eqn. 2-11
                             ,elements
                                               2-8

-------
                                                                             SRI/USEPA-GHG-VR-34
                                                                                    September 2006
                                s                                 Eqn. 2-12
                           JkW,Earthlmked
The improvement in efficiency was calculated as an average improvement comparing the three weeks of
operation using the DUT (r|EarthLmked) to three weeks  of operation using the heating elements  (TjEiements).
Table 2-4 summarizes these values.
                                Table 2-4. Average System Efficiency
T|EarthLinked
4.01 ±0.07
T|Elements
1.005 ±0.018
At]
3.00 ±0.07
The efficiency of the electric elements (r|Eiements) was expected to be 1.00 and this result was achieved
within the confidence limits.
2.2.4   Operational COP of the DUT

The operational COP of the DUT was also calculated.  The operational COP differs from the efficiency
reported in Table 2-4. COP looks at the performance of only the DUT and is commonly used to
characterize heat pump technologies.  The efficiency characterizes the performance of the whole system
installation, not just the DUT.

Operational COP is calculated as the ratio of the rate of energy delivered by the DUT to the site (Zkw DUT)
versus the rate of energy consumed by the DUT (Zkw EanhLmked) during actual operating conditions. This
is distinct from the COP measured in the short-term tests. The short-term tests were performed under
controlled conditions for a specific temperature range.  This calculation of COP is performed during
actual operating conditions. It was calculated as:

               Zkw,DUT =  (Ti - T2) x Fi x Cp x P
               r^r^n        .                                              „    ,  , .
               COP =          =•                                        Eqn. 2-14
                       7
                       •^kW.Earthlmked

       where:
               Zkw,ouT = from Eqn. 2-13
               Zkw,EarthLinked from Table 2-3
               F] = water flow rate measured by Flow Meter #1 (see Figure 1-1)
               TI and T2 = temperatures measured at the heat pump inlet and outlet
               Cp = the heat capacity of water and is a function of temperature and pressure
               p = the density of water, also a function of temperature and pressure.

Table 2-5 summarizes the results.
                                               2-9

-------
                                                                           SRI/USEPA-GHG-VR-34
                                                                                  September 2006
                              Table 2-5. Operational COP of the BUT
Zkw,Dur(kW)
2.59 ±0.19
ZkW, EarthLinked (kW)
0.58 ±0.03
COP
4.43+0.09, -0.3
The reader is encouraged to note that this technology is a heat pump water heater and the performance
results cannot be directly compared with those of conventional heating, ventilation, and air conditioning
heat pumps.

It should be noted that the COP has asymmetric error.  During post-test equipment calibration checks,
GHG Center personnel discovered that the Hedland flow meter (Fi in Figure 1-1) was over-reporting flow
by approximately 6%.  The  meter was  calibrated  prior to  testing and was  found to be within its
specification  of ±1% at that time.  Flow  readings from the meter were consistent throughout the test
period, so this led analysts to conclude that something occurred in shipping either before or after testing
that caused the meter to be out of spec.  If the assumption is made that the meter over-reported flow
throughout the test, this would result in an  over-reported  COP.  As such, the lower error limit  was
modified to include the effect of the 6% bias.

The average COP of the DUT during the in-use monitoring was higher than the average COP observed in
the  short-term testing (refer to Table 2-1).  Calculation of COP for the short-term tests was conducted
following the ANSI/ASHRAE tests for Type V heat  pump  water heaters.  Analysts found  that this
procedure, however useful for comparison between different pieces of equipment of the same class under
controlled circumstances, may not provide results that are directly representative of in-service operating
conditions. Calculation of COP for the long-term tests was based on the ratio of thermal energy delivered
by the device and the electrical energy consumed by the DUT.
2.2.5   Estimated Emissions Reductions

The procedure used for estimating  SUT emission reductions correlates the estimated annual electricity
savings in megawatt-hours per year (MWh/year) with Florida and nationwide electric power system
emission rates in pounds per megawatt-hour (Ib/MWh).  For this verification, analysts assumed that the
EarthLinked system operates continuously throughout the year with electric power savings as measured
during the long-term monitoring period.  Emission data from the EPA's "EGRID" database [6] were used
to estimate state and nationwide emission rates.  The test plan specified that carbon monoxide (CO), CO2,
and NOx emissions reductions would be estimated.  EGRID does not supply emission information for
CO, so it is not considered here. Potential emissions reductions were calculated as:

               Reduction,  =  EREPS>i x MWhDUT Ann                        Eqn. 2-15

       where:
              Reduction; = annual reduction for pollutant "i", Ib/year
              EREPS.I  = electric power system emission rate for pollutant "i" from EGRID, Ib/MWh
              MWhDUT Ann  =  annual estimated device-based power savings, MWh/year

MWhDUT Ann comes from the change in  normalized electrical power consumption between EarthLinked
and electric elements operations (AZkw) reported in Table 2-3 and then converted to MWh.  Table 2-6
summarizes the estimated yearly emission reductions.
                                             2-10

-------
                                                                             SRI/USEPA-GHG-VR-34
                                                                                    September 2006
                          Table 2-6. Estimated Yearly Emissions Reductions

Pollutant
EREPS,i (Ib/MWh)
MWhDUT.Ann (MWh/year)
Emission Offset (Ib/year)
Florida
CO2
1420.42
NOx
3.36
Nationwide
CO2
1392.49
NOx
2.96
15 ±1
21,700 ±1,400
51±3
21,300 ±1,300
45 ±3
2.2.6   Estimated Simple Cost Savings

The procedure for estimating SUT simple cost savings is based on the Florida and nationwide prices for
retail  electricity at  "commercial" rates.   Similar to emissions  reductions,  analysts assumed that  the
EarthLinked system operates continuously throughout the year with electric power savings as measured
during the long-term monitoring period.  The  EarthLinked system  does not use auxiliary fuel, nor is it
intended as a power source, so their potential  costs  or revenues are not considered for this verification.
The simple cost savings is the annual estimated device-based power savings multiplied by the average
retail price of electricity:
                                      MWhnTIT,   xRP,   xlO3
               Simple Cost Savings =	_——	                  Eqn. 2-16
                                                 100
       where:
               Simple Cost Savings = estimated annual device-based cost savings, dollars/year
               MWhDUT,Ann = annual estimated device-based power savings, MWh/year
               RPeiec = average retail price of commercial electricity, cents/kWh
               103 = conversion factor from MWh to kWh
               100 = conversion factor from cents to dollars

MWhDUT,Ann comes from the change in normalized  electrical power consumption between EarthLinked
and electric elements operations (AZkw)  reported in Table 2-3 and then converted to MWh.  Varying
values for RPeiec can be found in many resources.  This methodology of estimating simple cost savings
uses the Energy  Information Agency's Table  5.6.A. Average Retail Price of Electricity  to  Ultimate
Customers by End-Use Sector, by State [7] to find RPeiec

Table 2-7 summarizes the estimated yearly cost savings.
                          Table 2-7. Estimated Yearly Simple Cost Savings*
MWhDUT.Ann (MWh/year)
RPeiec (cents/kWh)
Simple Cost Savings (dollars/year)
15
9.88
1,500 ± 100
±1
9.2
1,410 ±90
                                                              Florida
Nationwide
           * Based on approximately 630 gallons per day average consumption on site. The intended load for
           this product is 2,000 gallons per day. Increasing the load may be expected to improve savings.
                                              2-11

-------
                                             SRI/USEPA-GHG-VR-34
                                                     September 2006
(this page intentionally left blank)
              2-12

-------
                                                                          SRI/USEPA-GHG-VR-34
                                                                                  September 2006
                             3.0  DATA QUALITY ASSESSMENT
3.1   DATA QUALITY OBJECTIVES

The GHG Center selects test methods and instruments for all verifications to ensure a stated level of data
quality in the reported results.  The  test plan  described the data quality  objectives  (DQOs) for this
verification.  The test plan also listed contributing measurements, their accuracy requirements, QA/QC
checks, and other data quality indicators (DQIs) that, if met, would ensure achievement of the DQOs.

The following activities and procedures supported the achievement of this verification's objectives:

       •   on-site QA/QC checks to reconcile the achieved DQIs with the DQOs
       •   audit of data quality (ADQ)
       •   on-site performance evaluation

The test plan defined the following DQOs for this test:

       •   determine EarthLinked water heating capacity and COP to within ±5%
       •   determine the power consumed by  the  baseline and EarthLinked systems (during
           long-term monitoring) to within ± 0.4%

The first DQO was  met for the EarthLinked water heating capacity tests at both low and elevated
temperatures, as well as for the EarthLinked COP  at low  and elevated temperatures.  Water heating
capacity was determined to ± 3.6% and COP was determined to ± 3.8%. The second DQO was met for
both the baseline  and EarthLinked  systems.   Power  consumed  during  long-term  monitoring was
determined to ± 0.3%.

The following subsections describe  reconciliation of the DQIs with the DQOs, the QA/QC checks, and
data quality audits.
3.2   RECONCILIATION OF DQOS AND DQIS

A fundamental component of all ETV verifications is the reconciliation of the collected data and their
DQIs with the DQOs.  Achievement of these DQIs implies that the DQOs were met.  The following
tables show the DQI data for the test campaign.
                                             3-1

-------
                                                                             SRI/USEPA-GHG-VR-34
                                                                                    September 2006
                          Table 3-1. Instrument and Accuracy Specifications
Measurement Variable
EarthL inked system water flow
Facility supply water flow
Recirculation loop water flow
System temperature
measurements
Test room temperature
System pressure
kW
Current transformers (for kW)
Tank #1 volume, gal
Observed
Operating
Range
10-12gpm
1.7-8gpm
1 - 3 gpm
59-120°F
57-89°F
20 - 40 psig
0-31kW
0-18A
120, nominal
Instrument Range
0-55 gpm
2. 5 -29 gpm
0.75 - 5 gpm
0-250°F
0 - 60 psig
0 - 125 kW
0-150A
n/a
Accuracy
Specification"1
+ 1%
+ 0.5%
+ 0.5%
+ 0.6 °F
+ 3%
+ 0.15%
+ 0.3%
+ 3.3%
How Verified /
Determined
NIST-traceable
calibration within
2 years
NIST-traceable
calibration within
6 years; pretest
crosscheck
Manufacturer's
certificate
Gravimetrically as
part of statistical
process control
Result
Achieved
Meets
spec.
Does not
meet spec.
Meets
spec.
Meets
spec.
Meets
spec.
Does not
meet spec.
Meets
spec.
Meets
spec.
Meets
spec.
  "Accuracy is % of reading unless stated as absolute units
All instrument and accuracy specifications in Table 3-1 were met with the exception of the facility supply
water flow and the system pressure measurements.

The observed operating range for the facility supply flow was outside the lower limit of the flow meter.
GHG Center personnel performed a low flow calibration of the meter at approximately 1.7 gpm against a
coriolis mass flow meter after the completion of testing to determine the accuracy effects of being below
the meter range.  The calibration showed that the meter accuracy outside the meter range is ±1%.  As
such,  this accuracy was applied to all calculations. The accuracy change  did not have any effect on the
confidence limits of reported findings.

A NIST-traceable  calibration for the pressure  gauge used in testing could not be located.  The system
pressure that was recorded during field testing was 72 psig. If the gauge had been so out of specification
as to read 0 psig, the change in pressure would result in a change in density of 0.016 lb/ft3. This change is
negligible and it was therefore deemed unnecessary to recalibrate the pressure gauge to verify that it is
within the stated accuracy specification.

Power meters, flow meters, and temperature sensors were cross-checked to confirm performance within
expected limits before being shipped to the field (pre-mobilization) and after returning from the field (de-
mobilization) in accordance with Southern Research Standard Operating Procedures.

Table 3-2 summarizes QA/QC checks which the field team leader performed before and during testing.
                                               3-2

-------
                                                                               SRI/USEPA-GHG-VR-34
                                                                                      September 2006
                                       Table 3-2. QA/QC Checks
System or
Parameter
QA/QC Check
When
Performed
Expected or Allowable Result
Result Achieved
Short-Term Testing
EarthL inked system
flow rate
Tank #1 and Tank
#2 real power
consumption
Temperature sensors
Water heating
capacity
Zero check
Full flow check
Voltage and current field
reasonableness checks with
Fluke 335 clamp meter
Laboratory cross checks
between power meters
Ambient cross check
Cross check between Type
V (tank) and Type IV
(flow) test method
Immediately prior
to first test run
Prior to testing
Prior to
installation
After each short-
term test run
Ogpm
9-11 gpm
Voltage within + 2 %
Current within + 3 %
kW readings within + 1 % of
each other
All within +1. 5 °F of each
other
Result within + 6.4 % of each
other
0 gpm
9.4 gpm
Voltage: 0.08 %
Current: 2.44 %
Readings within + 1% of
each other
All within +1. 2 °F of
each other
Failed: All results were
within + 14.8% of each
other
Long-Term Testing
Flow meters
Power Consumption
Temperature sensors
Zero Check
Full flow check
Voltage and current
reasonableness checks
Laboratory cross check
between power meters
Ambient cross checks
Ice-bath checks
Immediately prior
to testing
Prior to testing
Prior to
installation
Prior to
installation
Pre-mobilization
Ogpm
Fl: 9-12 gpm
F2: 1-4 gpm
F3: F2 must be greater than F3
Voltage within + 2 %
Current within + 3 %
All within + 1 % of each other
All within +1. 5 °F of each
other
Each pair within 0.5 °F of each
other
0 gpm on all meters
Fl: 10.5 gpm
F2: 2.8 gpm
F3: 1.6 gpm
All voltage readings
within + 0.7 %
All current readings
within + 2.2 %
All within 0.1% of each
other
All readings within 0.2 °F
of each other
Each pair within 0.4 °F of
each other
   All QA/QC checks were met with the exception of the cross check between the Type V and Type IV test
   methods.  This verification was based on the ANSI/ASHRAE test method for Type V heat pump water
   heaters which incorporate  a storage tank. Analysts did, however, collect sufficient data to quantify the
   water heating performance for Type IV systems, or, as if the water heater did not have a storage tank.
   While the Type IV determination's accuracy does not meet the ANSI/ASHRAE test specifications, the
   results served as a cross check against the Type V determinations.  The expected result (within ± 6.4% of
   each other) was not achieved for any of the test runs. The achieved results appear in Table 3-3.
                      Table 3-3. Crosscheck between Type V and Type IV Test Methods

Result Achieved
Low Temperature Tests
Runl
7.57%
Run 2
7.75%
Run 3
7.32%
Elevated Temperature Tests
Runl
14.45%
Run 2
14.37%
Run 3
12.76%
   This cross check failed and resulted in a deviation from the test plan.  The expected result of ± 6.4% was
   based on expected instrument errors and assumptions about the expected data. Southern assumed that the
   Type IV and Type  V determinations should give comparable results; however, at  least in these field
   conditions, this was an incorrect assumption and resulted in a consistent bias error. Rather than ± 6.4%,
   the expected result should have been  closer to the achieved results in Table 3-3, and  the crosscheck was
   therefore deemed invalid.
                                                 3-3

-------
                                                                          SRI/USEPA-GHG-VR-34
                                                                                 September 2006
3.3   AUDITS
This verification was supported by an ADQ conducted by the GHG Center QA manager.  During the
ADQ, the QA manager randomly selected data supporting each of the primary verification parameters and
followed the  data through the analysis and  data processing system.   The ADQ confirmed that no
systematic errors were introduced during data handling and processing.
                                             3-4

-------
                                                                            SRI/USEPA-GHG-VR-34
                                                                                   September 2006
    4.0  TECHNICAL AND PERFORMANCE DATA SUPPLIED BY ECR TECHNOLOGIES
Note: This section provides  an opportunity for ECR  Technologies  to provide  additional comments
concerning the EarthLinked  Water Heating System and its features not addressed elsewhere in  this
report. The GHG Center has not independently verified the statements made in this section.

Simultaneous with the system testing at Sun City Center, monitoring was conducted in a condominium
building in Claremont, NH under the direction of Public Service Company of New Hampshire. In  that
test, 48 °F supply water was pre-heated to 110 °F by the EarthLinked unit, then the resistive elements of
five traditional water heater tanks raised the water temperature to 125 °F and maintained that level within
±5 degrees. The documented energy savings ranged from 65% to 72%, even though the electrical circuit
being monitored  also served common area lighting.  The  short cost recovery period  shown by the
monitored results caused the building owner to install five additional units in other locations.

Pre-heating of low temperature water for a large bank of traditional water heater tanks demonstrates the
energy saving capability of the EarthLinked system, the highest return on investment and the greatest
environmental savings from a single unit. That arrangement also  provides redundancy, which is necessary
to provide assurance to commercial  and institutional customers that the addition of technology that is new
to them will not diminish the reliability of their water heating system.

The cabinet  design of  the EarthLinked unit encloses  the heat pump, the refrigerant-to-water heat
exchanger, and the water circulating pump within one unit for a small foot print (21x17 inches) and ease
of access.

Because of high efficiency thermal exchange with its heat source in the earth, only 100 feet of earth loop
per ton of heat pump capacity is needed, and a three inch diameter bore hole is optimal. Therefore, the
system is  easily adapted to new construction or retrofit applications. The earth loops can be installed
vertically, diagonally, or horizontally by trenching, drilling, excavation, or directional boring even under a
parking lot.
                                              4-1

-------
                                             SRI/USEPA-GHG-VR-34
                                                     September 2006
(this page intentionally left blank)
              4-2

-------
                                                                           SRI/USEPA-GHG-VR-34
                                                                                  September 2006
                                     5.0  REFERENCES

[1]  Southern Research Institute, Test and Quality Assurance Plan - ECR Technologies, Inc. EarthLinked
Ground-Source Heat Pump  Water Heating System, SRI/USEPA-GHG-QAP-34,  www.sri-rtp.com.
Greenhouse  Gas Technology  Center, Southern Research Institute,  Research Triangle Park, NC. May
2005.

[2]  Southern Research Institute, Addendum to Test and Quality Assurance Plan - ECR  Technologies, Inc.
EarthLinked Ground-Source Heat Pump Water Heating System, SRI/USEPA-GHG-QAP-34A, www.sri-
rtp.com. Greenhouse  Gas Technology Center, Southern Research Institute, Research Triangle Park, NC.
May 2006.

[3]  ANSI/ASHRAE Standard 118.1-2003: Methodof Testing for Rating Commercial Gas, Electric, and
Oil Service Water Heating Equipment, American Society of Heating,  Refrigerating and  Air-Conditioning
Engineers, Inc. Atlanta, GA.  2003

[4]  Handbook of Chemistry and Physics, 60th Edition, "Specific Heat of Water", page D-174,  CRC Press.
Boca Raton,  FL.  1980

[5]  Handbook of Chemistry and Physics, 60th Edition, "Steam Tables—Properties of Saturated Steam and
Saturated Water", page E-18, CRC Press. Boca Raton, FL. 1980

[6] U.S. Environmental Protection Agency, Emissions & Generation Resource Integrated Database
(eGRID) Version 2.01, available from < http://www.epa.gov/cleanrgy/egrid/index.htm>. accessed on
09/06/2006.

[7] Energy Information Agency, Table 5.6.A. Average Retail Price of Electricity to Ultimate Customers
by End-Use Sector, by State available from , accessed on 09/05/2006.