THE ENVIRONMENTAL TECHNOLOGY VERIFICATION
                                      PROGRAM
       oEPA
    U.S. Environmental Protection Agency                                                NSF International
                      ETV Joint Verification Statement
    TECHNOLOGY TYPE:  ELECTROFLOCCULATION AND MEDIA FILTRATION
                           USED IN DRINKING WATER TREATMENT SYSTEMS
    APPLICATION:         REMOVAL OF ARSENIC IN DRINKING WATER
    TECHNOLOGY NAME:  ARS CFU-50 APC ELECTROFLOCCULATION AND
                           FILTRATION WATER TREATMENT SYSTEM

    COMPANY:            ARS USA, LLC
    ADDRESS:             PO Box 1170                       PHONE: (505)771-4344
                           Bernalillo, NM 87004               FAX:    (505) 771-4345
    WEB SITE:             www.arsusa.com
    EMAIL:                info@arsusa.com
The U.S. Environmental Protection Agency (EPA) supports the Environmental Technology Verification
(ETV)  Program to  facilitate the  deployment of innovative or improved environmental technologies
through performance verification and dissemination of information.  The goal of the ETV Program is to
further environmental  protection by accelerating the acceptance and use of improved and more cost-
effective technologies.  ETV seeks to achieve this goal by providing high-quality, peer-reviewed data on
technology performance to those  involved in the design, distribution, permitting, purchase, and use of
environmental technologies.
ETV works in partnership with  recognized standards  and testing  organizations,  stakeholder  groups
(consisting of buyers, vendor organizations, and permitters), and with the full participation of individual
technology developers.  The program evaluates the performance of innovative technologies by developing
test plans that are responsive to the needs  of  stakeholders, conducting field or laboratory tests  (as
appropriate), collecting and analyzing data,  and preparing peer-reviewed reports.  All evaluations  are
conducted in accordance with rigorous quality assurance protocols  to ensure that data of known and
adequate quality are generated and that the results are defensible.
NSF International (NSF), in  cooperation with the EPA, operates the Drinking Water Systems (DWS)
Center, one of six technology areas under the ETV  Program. The DWS Center recently evaluated  the
performance of an  electroflocculation and  media  filtration system for the removal of arsenic from
drinking water. This verification statement provides  a summary  of the test results for the ARS CFU-50
APC Electroflocculation and Filtration Water Treatment System (ARS CFU-50 APC). The NSF Drinking
Water Treatment Systems Laboratory (DWTS) was the  field testing  organization (FTO) that performed
the verification testing. The verification report contains a comprehensive description of the complete
verification test.
06/ARS1/EPADWCTR    The accompanying notice is an integral part of this verification statement.        September 2006

                                       VS-i

-------
ABSTRACT
Verification testing of the ARS CFU-50 APC Electroflocculation and Filtration Water Treatment System
(ARS CFU-50 APC) for arsenic removal was conducted at the Town of Bernalillo Well #3 site from April
18 through May 2, 2006.  The source water was chlorinated groundwater from two supply wells, and the
feed water for the verification test was withdrawn from the pressure tank at the site. Verification testing
was  conducted at the operating conditions specified by the manufacturer.  The feed water, with a pH in
the range of 7.6 to 7.9, was pumped into a reaction vessel where electricity is applied to aluminum and
graphite plates to create flocculent to which arsenic adsorbs.  When operated under the manufacturer's
specified conditions at this site, at  an average flow rate of 32.1 gallons per minute  (gpm), the ARS
CFU-50 APC reduced the total arsenic concentration from an average of 12 micrograms per liter ((ig/L)
in the feed (untreated) water to 6 (ig/L in the filtrate (treated) water.
TECHNOLOGY DESCRIPTION
The following technology description was provided by the manufacturer and has not been verified.
The  ARS  CFU-50 APC is a standard, full-scale,  modular system for the removal of arsenic and other
contaminants from water. The ARS CFU-50 APC is a self-contained, complete system that connects to a
water supply source. If the source is  not pressurized, a pump, supplied with the unit, is used to pump the
water through the treatment system.  The ARS CFU-50  APC requires a three-phase 480-volt AC electric
power source to operate  the reaction vessel,  programmable logic  controller (PLC), and  ancillary
equipment. The  system used for this test is  designed to treat flows up to a maximum flow rate  of
approximately 35 gpm (50,000 gallons per day [gpd]),  from either a pressurized or unpressurized water
source.
Untreated/contaminated water enters the unit through a regulated influent pipe. The flocculent generation
and decontamination process occurs in the reaction vessel in a continuous process. Flocculent particles in
the holding pipe/tank are subject to further growth and reaction after the electrolytic process. Sand filters
separate the flocculent from the treated water. The filter surfaces are cleaned by automatic backwashing,
and the flocculation sludge is flushed into the floe water reservoir tank. The  low volume, thickened
flocculation sludge accumulated in the floe water reservoir tank is pumped into the filter press by a pump,
where it is pressed into a filter cake. After the treated water passes through the filter press, it is stored in
the clean water tank for later use in filter backwashing and rinsing. As the clean water tank level reaches
its maximum level, it is pumped out of the unit through the filtrate water pipe.
The ARS CFU-50 APC treatment system is fully automated and programmed to control all aspects of the
treatment  and filter operation. The control system automatically initiates backwash cycles based on  an
inlet pressure level set by the operator.  The backwash  cycle time is a  fixed time duration that is
programmed in the PLC. The control system monitors data from the system operation. This information is
available to the on-site operator.
VERIFICATION TESTING DESCRIPTION
Test Site
The  Bernalillo Well #3 site is a fenced property that includes a building that houses the well pump and
chlorination equipment, a primary storage  tank (approximately 1,000,000 gallons [gal]), and a secondary
storage tank (approximately 200,000 gal).  Water pumped at the site is a mixture from two wells, both of
which pump water from the Rio Grande Group aquifer.  The  average daily water use for the Town of
Bernalillo  is approximately 2,000,000 gpd. Water quality data based on data collected between June 2002
and March 2004  shows total arsenic in the combined well water ranges from  14 to  68  (ig/L and the
primary arsenic  species is  arsenic (V).   The water has a total hardness  of approximately 70 to  90
milligrams per liter (mg/L) as CaCO3 and the pH is approximately 7.3.
06/ARS1/EPADWCTR    The accompanying notice is an integral part of this verification statement.         September 2006

                                         VS-ii

-------
Methods and Procedures

Operations, sampling, and analyses were performed in accordance with the Product Specific Test Plan
(PSTP) developed and approved for this verification test. The PSTP included a Quality Assurance Project
Plan (QAPP) to assure the quality of the data collected  and to provide an accurate evaluation of the
treatment system under field conditions. Testing included characterization of the feed water, an arsenic
loss test (no electricity supplied to the reaction vessel), and a 14-day verification test.
The verification test was performed from April 18, through May 1, 2006. The ARS CFU-50 APC was
operated for the 14-day verification test by using water supplied from the Town of Bernalillo. Flow rate,
production volume, water temperature, and system pressure were monitored and recorded daily. Feed and
filtrate (treated) water samples were analyzed on-site for pH, temperature, turbidity, free and total residual
chlorine, color, and dissolved oxygen (DO) by the field operator.  Grab samples were collected and
delivered to the NSF  Analytical  Laboratory  and were  analyzed  for alkalinity,  aluminum,  calcium,
magnesium, iron, manganese, sulfate, chloride, total organic carbon (TOC), total suspended solids (TSS),
and fluoride.  Samples for total  arsenic  were collected daily, plus 14  samples were collected during a
48-hour intensive survey.  In addition to the samples for total arsenic, arsenic samples were speciated
during the test to determine the soluble arsenic concentration and the concentrations of arsenic (III) and
the arsenic (V) present in the soluble fraction.
Complete descriptions of the verification testing results and quality assurance/quality control (QA/QC)
procedures are included in the verification report.
VERIFICATION OF PERFORMANCE
System Operation

ARS performed the system startup  and shakedown testing, which included optimization of the electrical
feed rates (30 amps) to the reaction vessel. The verification test was conducted under the manufacturer's
specified operating conditions. The backwash system was  set to backwash when the pressure differential
across the filter exceeded 15 pounds per square inch (psi).
System pressure was monitored at the filter influent and  filtrate.  Head loss fluctuated between 6.4 and
15.9 psi  during the  inspections.  The ARS  CFU-50 APC PLC was not programmed to  record pressure
differentials at the start  of backwash cycles, so the pressure differential  evaluation for this verification
was limited to whether the differential exceeded 15 psi during the time the FTO personnel inspected the
device.
During the test, there were a total of four incidences (April 20, 21, 28,  and 30) where a sensor triggered
the PLC to shut down operations.  During each incident,  the sensor indicated that either the floe water
reservoir tank had exceeded capacity  or the filter press alarm went off.  In each instance, the filter press
had clogged to a point where it  was prohibiting sufficient filtration to  maintain  the device's rated
throughput.  ARS personnel  recommended that the filter press be cleaned a minimum of once every  24
hours to prevent the ARS CFU-50 APC from automatically shutting down. After each shutdown incident,
FTO personnel cleaned the filter press and resumed operation in accordance with the startup procedures
outlined in the ARS Operations and Maintenance (O&M) manual.  As a  result of these incidents, the ARS
CFU-50 APC experienced approximately 36 hours of downtime during the 14-day verification test.
The filtrate flow rate was  32.1 gpm over the 14 days. The total filtrate volume produced each day was
also consistent, except for those days when operating time was lost due to the filter press alarm shutting
down the system.
Water Quality Results
The results of total  arsenic analyses are  shown in Figure VS-1.  The feed water total arsenic averaged
12 (ig/L with most of the arsenic as arsenic (III), but with some arsenic (V) also present. The filtrate water
total arsenic concentration averaged 6 (ig/L. The data collected during the 48-hour intensive survey were
06/ARS1/EPADWCTR   The accompanying notice is an integral part of this verification statement.         September 2006

                                          VS-iii

-------
consistent with the data collected each day during the verification test. There was no indication of any
transient or short time changes in the arsenic concentration or in any other monitored parameters.
                                                              ^    ^    ^    ^«
                                                              *>*5s   )"X-V   '"X-v    '"X-
                        *%.   -%
%
%
                                             Date
                                         •Feed —•—Filtrate
Figure VS-1. Total Arsenic Results.

The feed and filtrate water alkalinity averaged 130 mg/L as CaCO3, indicating that the treatment process
had no  impact  on the  alkalinity.   The pH of the feed and filtrate water had a median value of 7.7.
Aluminum was detected in four of the 14 feed water samples, at concentrations ranging from  13 to
84 (ig/L, while  the remaining ten feed water samples had aluminum concentrations below the 10 (ig/L
detection limit.  In the filtrate, the average aluminum concentration was 560 (ig/L, and ranged from 200 to
890 (ig/L. The average  filtrate aluminum concentration was 20 times greater than the feed water average
concentration and significantly higher than the National Secondary Drinking Water Regulation range of
50 to 200 (ig/L. Furthermore, operation of the ARS CFU-50 APC increased the turbidity levels in the
filtrate water. The feed water turbidity averaged 0.30 Nephelometric Turbidity Units (NTU), and ranged
from 0.20 to 0.45 NTU, while the filtrate water averaged 0.80 NTU, and ranged from 0.35 to 1.2 NTU.
Turbidity and aluminum data during the 48-hour intensive survey were similar to those during the 14-day
test.   The turbidity and aluminum data indicated that filtration mechanisms more efficient than those
currently utilized  in the ARS CFU-50 APC were required to bring these parameters closer to the feed
water concentrations or within the  EPA regulations. The ARS CFU-50 APC had little or no impact on
free chlorine, total chlorine, DO, chloride, sulfate, TOC, fluoride, calcium, or magnesium concentrations.
Manganese and iron concentrations were consistently below detection  limits in both the feed and filtrate
water.
Backwash was  initiated automatically based on pressure differential.   Backwash waste was treated by a
filter press designed to remove the solids  (floe) from the backwash water.  The filtrate from the filter
press was transferred back to the reaction vessel for re-treatment.  The backwash cycle was set for a fixed
time duration of 120 seconds for backwash and  30  seconds for rinsing.  The combined backwash and
rinsing resulted in approximately 250 gallons of waste per backwash sequence. Solids retained in the
filter press were removed manually during filter press maintenance. At the end of testing, approximately
572,550  gallons of water were treated, and approximately 1,425  pounds of solids  (wetted floe) was
created.  This calculates to an approximate suspended solids concentration of 300 mg/L.  The backwash
06/ARS1/EPADWCTR    The accompanying notice is an integral part of this verification statement.

                                          VS-iv
                                          September 2006

-------
solids were  not considered a hazardous waste, based on Toxicity Characteristic Leaching Procedure
(TCLP) metals  analyses, which were below the regulatory limits under the Resource Conservation and
Recovery Act (RCRA).
Operation and Maintenance Results

The ARS CFU-50 APC was found to be easy to operate and required little time for daily maintenance.
The field staff was on-site for two to three hours per day. Most of the time on-site was spent performing
field activities, including flow checks, calibrations, cleaning the filter press, and other verification-related
activities.
The ARS CFU-50 APC O&M manual provides a  detailed description of the system, appropriate safety
precautions,  and detailed descriptions of operating procedures, capability  and operation of the computer
control system, and specific instructions for utility operators. The maintenance section of the  manual
includes  some descriptions  of required maintenance, but refers the reader to the individual equipment
literature supplied by  the various pump and instrument manufacturers. A review of the O&M  manual
shows that the manual is well organized and easy to read.
The ARS CFU-50 APC was equipped with two sand filters, so that one filter could be in operation while
the other was  in backwash mode or  standby.  During the testing at this installation,  there were no
conditions where the pressure  differential across both sand filters required  that both filters backwashed at
the same time.  Issues regarding the efficacy of the filtration process, as shown in the  aluminum and
turbidity data, were noted during the verification test.
Backwash waste was treated by a filter press designed to remove the solids from the backwash water.
During the testing, when the flocculent caked in the filter press to a point where water would no longer
pass through it, the PLC shut down the entire system, as it was programmed to do. When this occurred,
field personnel  cleaned the filter  press and restarted the system. Verification testing substantiated the
importance of the filter press  and its appropriate maintenance as a critical aspect of the function of the
ARS CFU-50 APC.
The system PLC was designed to operate and monitor many of the operating functions of the device.  The
PLC readings were easy to use, but required an understanding of the PLC operating  keys to display the
readings. The PLC was not programmed to record data, so readouts on component performance,  such as
flow, pressure, and electrical settings had to be monitored and recorded manually. Because the PLC did
not record data, information regarding the duration of filter runs, frequency of backwash cycles,  and the
pressure differentials across the sand filters could not be accurately recorded. The PLC was designed to
shut the entire system  down in the event any sensor recorded a condition outside preset operating limits.
This condition was experienced four times during the verification.  The cause of each shutdown was the
filter press clogging to a point where water could not pass through it at the system's rated throughput.
During each shutdown condition, after the filter press was cleaned, the alarm conditions in the PLC were
cleared and the system was restarted without difficulty.
Electrical power consumption was estimated based  on the floe pump, clean water pump, backwash pump,
reaction vessel, waste pump,  and miscellaneous other devices (air compressor, PLC, lights, etc.). The
power consumption was estimated to be 4.2 kilowatt hours (KwH).
Quality Assurance/Quality Control
NSF provided technical and  QA  oversight of the verification testing  as described in the verification
report, including an audit of nearly 100% of the data. The NSF QA department conducted a technical
systems audit during testing to ensure the testing was in compliance with the test plan and performed a
QA review of the analytical data.  A complete description of the QA/QC procedures is provided in the
verification report.
06/ARS1/EPADWCTR    The accompanying notice is an integral part of this verification statement.        September 2006

                                          VS-v

-------
   Original signed by                                    Original signed by
   Sally Gutierrez	September 22, 2006         Robert Ferguson   September 12, 2006
    Sally Gutierrez                     Date            Robert Ferguson             Date
    Director                                           Vice President
    National Risk Management Research Laboratory       Water Systems
    Office of Research and Development                 NSF International
    United States Environmental Protection Agency
    NOTICE:  Verifications are based on an evaluation of technology performance under specific,
    predetermined criteria and the appropriate quality assurance procedures.  EPA and NSF make no
    expressed or implied warranties as to the performance of the technology and do not certify that a
    technology will always operate as verified.  The end-user is solely responsible for complying with
    any and all applicable federal, state, and local requirements.  Mention of corporate names, trade
    names, or commercial products does not constitute endorsement or recommendation for use of
    specific products.  This report is not an NSF Certification  of the specific product mentioned
    herein.
       Availability of Supporting Documents
       Copies of the ETV Protocol for Equipment Verification  Testing for Arsenic Removal
       dated September 2003, the product-specific test plan, the verification statement, and the
       verification  report  (NSF  Report  #06/ARS1/EPADWCTR)  are  available from  the
       following sources:
       (NOTE: Appendices are not included in the verification report.  Appendices are available
       from NSF upon request.)

       1.   ETV Drinking Water Systems Center Manager (order hard copy)
           NSF International
           P.O.  Box 130140
           Ann Arbor, Michigan 48113-0140
       2.   NSF web site: http://www.nsf.org/info/etv (electronic copy)
       3.   EPA web site: http://www.epa.gov/etv (electronic copy)
06/ARS1/EPADWCTR    The accompanying notice is an integral part of this verification statement.         September 2006

                                         VS-vi

-------