United States
                Environmental Protection
                Agency
National Risk Management
Research Laboratory
Research Triangle Park, NC 27711
                Research and Development
EPA/600/SR-97/058
July 1997
SEPA      Project  Summary

                Comparison of CFC-114  and
                HFC-236ea  Performance  in
                Shipboard  Vapor Compression
                Systems
                D. T. Ray, M. B. Pate, and H. N. Shapiro
                 In compliance with the Montreal Pro-
               tocol and Department of Defense di-
               rectives, alternatives to the refrigerant
               1,2-dichloro-tetrafluoroethane (CFC-114)
               are being investigated by the U.S. Navy
               and the U.S. EPA for use in shipboard
               chillers. The  refrigerant 1,1,1,2,3,3-
               hexafluoropropane (HFC-236ea) has
               emerged as a candidate for drop-in re-
               placement.
                 A computer model was developed for
               comparing these two refrigerants in a
               simulated 440-kW centrifugal chiller
               system.  Equations for modeling each
               system component were developed and
               solved using the Newton-Raphson
               method for multiple equations and un-
               knowns. Correlations were developed
               for CFC-114 and HFC-236ea boiling and
               condensing  coefficients taken at the
               Iowa State Heat Transfer Test Facility.
               The model was tested for a range of
               inlet condenser water temperatures and
               evaporator loads. The results are pre-
               sented  and  compared with  data pro-
               vided by the  Naval Surface Warfare
               Center (NSWC) in Annapolis, MD.
                 The experimental data provided by
               the NSWC  sufficiently validate the
               model, and the simulation model pre-
               dicts that HFC-236ea would perform fa-
               vorably as a drop-in substitute for CFC-
               114.
                 Several recommendations are dis-
               cussed which may further improve the
               performance of HFC-236ea in Navy chill-
               ers. Recommendations include adjust-
               ing the load of the evaporator to achieve
               positive gage pressure, use of a purge
               device, use  of a variable speed com-
               pressor, further testing with azeotropic
               mixtures, and use of high performance
               tubes in the  heat exchangers.
  The work represented by the report
 was funded by the  Department  of
 Defense's Strategic Environmental Re-
 search and Development  Program
 (SERDP).
  This Project Summary was developed
 by  EPA's National Risk Management
 Research Laboratory's Air Pollution
 Prevention and Control Division, Re-
 search Triangle Park, NC, to announce
 key findings of the research project
 that is fully documented in a  separate
 report of the same title (see Project
 Report ordering information at back).

 Introduction

 Background
  Fully halogenated chlorofluorocarbons
 (CFCs) are manufactured chemicals with
 properties that make them useful for such
 applications as aerosol  propellents,  foam
 blowing agents, solvents, and refrigerants
 for  automotive, residential, and  commer-
 cial applications. CFCs became popular
 in part because they  were chemically
 stable, nonflammable, and  nontoxic.
 Ironically, the chemical  stability of CFCs
 is the cause for their present perceived
 threat to the environment. Scientific evi-
 dence suggests that the harmful alterations
 of the Earth' s atmosphere occurring from
 the  use of CFCs are of regional and glo-
 bal  proportions. As early as 1974, con-
 cerns about the potential harmful environ-
 mental effects associated with the use of
 CFCs were raised when it was suggested
 that the chlorine from these compounds
 could  efficiently destroy stratospheric
 ozone. Additionally, there is a growing con-
 sensus among scientists that CFCs may
 contribute to global warming.

-------
  CFC-114 has been in use on Navy ships
since 1969 and has demonstrated excel-
lent  reliability.  However,  design  improve-
ments have often lagged behind  commer-
cial  advancements  in compressor tech-
nology,  advanced  heat  transfer surface
technology, and intelligent control system
technology. Trichlorofluoromethane (CFC-
11), used extensively on commercial ships,
was found to be unsatisfactory to the Navy
because of  problems  unique to surface
craft and submarine applications. For ex-
ample, CFC-11 decomposes at high tem-
peratures causing  toxicity  problems on
submarines as the  air  is  recycled in high-
temperature air purification equipment. In
contrast, CFC-114  remains stable at high
temperatures.
  Other requirements  unique to  the Navy
include the need for small inventory and
small components due to  space con-
straints. Energy efficiency has been a low
priority in the past,  but with shrinking  de-
fense budgets, it has  become more  im-
portant. Additionally, surface craft and sub-
marines need to operate  silently in tactical
situations, and recycle  air in living spaces.
Cooling  systems must be able to operate
at as low as 10%  of  maximum capacity
during  normal peacetime operations  yet
handle dramatic increases in load when
firing weapons in combat or training situa-
tions. Fully halogenated refrigerants, such
as CFC-114,  generally  exhibit  the  best
compatibility and impose the  least  restric-
tion in choice  of materials; a suitable re-
placement must  display similar material
compatibility. Other  requirements  for a suit-
able replacement include meeting safety
and  environmental  standards for toxicity,
flammability,  ozone  depletion potential, and
global warming potential.
  A  need exists for a suitable near-term
replacement for existing  equipment using
CFC-114 . Because industry attention has
been focused on CFC-11 and dichlorodif-
luoromethane (CFC-12) replacements, the
Navy must devote  substantial resources
to address the CFC-114  problem. Current
potential alternatives for  CFC-114 are not
well  developed, and significant  modifica-
tions to system equipment will  likely be
necessary in order to accommodate them.
   At  one time,  1,1,1-trifluoro-2,2-
dichloroethane (HCFC-123) and 1,1,1,2-
tetrafluoro-2-chloroethane  (HCFC-124)
were leading alternatives for  CFC-11 and
CFC-114, respectively. When it became
apparent that these HCFCs would also be
phased out as  environmentally unsuitable,
the EPA began investigating  "backup" al-
ternatives. As a result, a series of  propanes
have emerged as candidate replacements
for CFC-114.
  HFC-236ea  is a  promising  candidate
for replacing CFC-114 for several reasons.
First,  a commercial  production route is
available for large quantities through  the
use of hexafluoropropylene.  Second,  ini-
tial modeling conditions appear favorable
as a drop-in substitute, with modeled per-
formance  being  within 1%  of CFC-114
and operating  capacities, pressures, and
temperatures matching closely. Flamma-
bility tests, materials compatibility  tests,
and oil miscibility tests  appear favorable.
Acute inhalation test results indicate lower
acute  toxicity than CFC-114. In addition,
estimates  predict that HFC-236ea has a
short atmospheric lifetime.

Objective
  The objective of this work is to evaluate
HFC-236ea  as a potential near-term re-
placement for CFC-114 in shipboard chill-
ers  using  a computer-simulated  system
with data from the Iowa State  University
Heat Transfer Test Facility and also using
data provided by the  NSWC. With  the
information gathered, appropriate design
recommendations to accommodate the use
of HFC-236ea  in shipboard chillers  are
offered.

Scope
  A computer program has  been devel-
oped that simulates the performance of a
440-kW capacity, single-stage, centrifugal,
chilled-water  air-conditioning  plant. The
design conditions shown in  Table  1  are
based on the design of a typical air-condi-
tioning plant in use on Navy surface craft
and submarines.
  Given the  entering and leaving tem-
peratures of the chilled water, the enter-
ing temperature  of the  condenser water,
and the flowrates of the chilled water and
condenser water, the model predicts  the
required compressor power  and  the  re-
frigerant saturation temperatures  in  the
heat exchangers. With knowledge of fluid
properties and tube geometries, the per-
formance of the system with different re-
frigerants and enhanced surface tubes can
be compared under similar operating con-
ditions. For this study, the model is used
to compare  refrigerants  CFC-114 and
HFC-236ea using  10.23 fins per centime-
ter (fpc) tubes in the condenser and evapo-
rator. The results  are presented with de-
sign  recommendations.

Model and Experimental
Results Comparison
  The NSWC, in cooperation with the U.S.
EPA, has tested CFC-114 and HFC-236ea
in a  440-kW laboratory centrifugal chiller
representative of those used in the U.S.
Navy's fleet of surface  craft and subma-
rines. The laboratory chiller is fully instru-
mented.
  Modeled and  measured performance
values were  compared for both refriger-
ants.  The measured compressor  power
provided  by  the NSWC  was  calculated
from measurements of torque and angu-
lar velocity of the compressor shaft. The
modeled  value  of compressor  power  is
the rate of work performed directly on the
fluid  and does not include the mechanical
or heat losses as the power is transferred
from the compressor shaft to the impeller
and  ultimately to the working fluid.  A lin-
ear  relationship was found to exist be-
tween the shaft power and the power trans-
ferred to the working fluid for the  data
provided  by the  NSWC.  The correlation
was  applied to the results of the model as
an assumed mechanical  efficiency.
  Even with  an efficiency factor applied,
the  model  underpredicts the  amount  of
compressor  power required to meet the
specified  load by 6 to 26%. This could be
related to the use of inlet guide vanes  to
the compressor which are not modeled  in
this study.
    Table 1. Simulated Design Conditions

    Component              Design Condition
                        Value
Evaporator
Evaporator
Evaporator
Condenser
Condenser
Chilled Water Flowrate
Entering Chilled Water Temperature
Leaving Chilled Water Temperature
Water Flowrate
Entering Water Temperature
28.4 L/s
10.7°C
7.0°C
31 .5 L/s
31 .4°C

-------
  A comparison of the system coefficient
of performance calculated using  NSWC's
measurements and that predicted using
the model developed in this study shows
that the model overpredicts the coefficient
of performance for HFC-236ea by as much
as 38%. The result is consistent with what
one would expect when  comparing mod-
eled with measured results. Since models
often  make  use of simplifying  assump-
tions,  the results tend to be idealized.
One would expect to see  the actual  re-
sults to be less favorable  than  modeled
results.
  A comparison of modeled  and mea-
sured  refrigerant temperatures in the con-
denser shows that the model  predictions
compare  well with CFC-114 data;  how-
ever, it underpredicts the condenser tem-
perature for most  HFC-236ea data by as
much  as 9°C. This difference could  be
caused, in part, by poor heat transfer in
the condenser with HFC-236ea. If this were
the case, it would take a higher condenser
temperature to overcome whatever ther-
mal resistance is present. More compres-
sor power would  be  required  to  provide
this additional temperature lift, resulting in
lower  system performance.  Because the
refrigerant temperature  in the  condenser
is  closely tied to  the condensing coeffi-
cient by use of the log mean temperature
difference equation for heat transfer in the
condenser, one would also expect to see
a difference in a comparison of the mea-
sured   and  modeled  condensing coeffi-
cients.  As the condensing temperature in-
creases while entering and leaving,  cool-
ing water temperatures  remain  constant
and the log mean temperature difference
increases. This would result in a  modeled
decrease in the condensing coefficient.
  An  example of when conditions may
exist in the condenser that hamper heat
transfer is when  noncondensable gases,
left unpurged, accumulate in  the upper
vapor space of the condenser. This is a
plausible explanation for the differences
in condenser  saturation temperatures ob-
served. For  HFC-236ea,  both the mea-
sured  and modeled evaporator tempera-
tures  are  near  2°C.  The corresponding
saturation pressures for these saturation
temperatures  are  less than atmospheric
pressure. This could cause nonconden-
sable  gases to  leak into the  evaporator
due to negative gage  pressure. These
gases  would  migrate and  collect in the
condenser and could significantly degrade
the performance of the condenser and the
entire  system. If air, in fact, was  present
in the condenser,  it would drive  the out-
side heat transfer coefficient down, result-
ing in  a  high condenser saturation tem-
perature.
  A  comparison of modeled and  mea-
sured cooling water temperatures leaving
the condenser shows that modeled val-
ues are within 0.2°C of measured values.
This  is consistent with trends observed for
condenser capacity. This is expected,
since the  rate of heat transfer and the
temperature of the water leaving the con-
denser are the two variables in the water-
side  heat  transfer equation for the con-
denser.
  A  comparison of modeled and  mea-
sured evaporator temperature shows that
modeled and measured boiling coefficients
compare well despite some variance. One
would therefore expect to see a variance
in a comparison of boiling coefficients since
these variables must balance in  the  log
mean temperature difference  equation for
the heat transfer in the evaporator.
  A  comparison of modeled and  mea-
sured evaporator capacity shows that the
values match because the capacity is cal-
culated based  on three  common inputs:
entering and leaving evaporator water tem-
peratures,  and evaporator water flowrate.
Thus, the  evaporator capacity remains
fixed as long as these three  input values
are held constant.
  A  comparison of modeled and  mea-
sured refrigerant flowrate shows that the
model  consistently  predicts the flowrate
for both refrigerants within +5%. This sug-
gests that the enthalpy  differences also
compare favorably since the  rate of heat
transfer in  the evaporator is constant and
is equal to the  refrigerant mass flowrate
times the  enthalpy  difference across the
evaporator.

Comparison of CFC-114 and
HFC-236ea Performance
  The model is used to predict the perfor-
mance of both refrigerants, CFC-114 and
HFC-236ea, through a range  of operating
conditions. This is done by using the fleet
design point as the default  and  varying
one parameter at a time over  an appropri-
ate range  to see the effects  on the sys-
tem.  The results yield additional insight as
to  the  possible suitability of  HFC-236ea
as a  drop-in substitute for CFC-114.

Entering Condenser Water
Temperature
  As the Navy operates  its fleet around
the world,  ships encounter a wide range
of condenser water temperatures because
sea  water  is used  directly  in the heat
exchanger to remove heat from the work-
ing fluid. Chillers for Navy ships  are de-
signed for  a condenser water  temperature
of 31.4°C;  however, temperatures encoun-
tered may range from -1.3 to 35.3°C de-
pending on where the ship is operating.
Since heat transfer  in the condenser  is
driven by the temperature difference be-
tween heat transfer fluids, a  condenser
water temperature that is too  high could
hamper the performance of the condenser
and subsequently the entire refrigeration
cycle. Thus, the entering condenser water
temperature is  significant  to the perfor-
mance of the overall system.
  The predicted power required to drive
the compressor more than doubles for
both refrigerants as the water tempera-
ture entering the condenser increases from
16 to 38°C. The trend is  expected since
better heat transfer occurs as the tem-
perature of the cooling water entering the
condenser  decreases. The efficiency  of
the refrigeration cycle should thereby im-
prove,  resulting  in  less  power input re-
quired to the compressor. Additionally, the
model predicts that HFC-236ea used as a
drop-in substitute for CFC-114 may result
in  energy savings. At the design point  of
operation, the predicted power required  to
drive the compressor using HFC-236ea  is
91.4% of the power required  using CFC-
114. The model predicts that, for any cool-
ing water temperature, the power required
for a refrigeration cycle using HFC-236ea
as a drop-in will be significantly less than
the same  cycle using  CFC-114 as the
working  fluid.  The predicted  savings  in
power consumption by using  HFC-236ea
at  the  design  point of operation is  550
kW.
  The  NSWC data for CFC-114 show
nearly constant compressor  power over
the range of entering  condenser water
temperatures.  The data for  HFC-236ea
show significant scatter. Both the CFC-
114 and HFC-236ea measured values  of
required compressor power are above the
predicted values for the range  of entering
condenser water temperatures.
  The coefficient of performance is pre-
dicted to decrease as the inlet condenser
water temperature increases. Additionally,
at  the  design  point of 31.4°C,  the pre-
dicted coefficient of performance for HFC-
236ea is 4.25 compared to 3.91 for CFC-
114. The  model predicts  better perfor-
mance using HFC-236ea over the range
of  condenser water temperatures simu-
lated.
  The measured values of coefficient  of
performance for both CFC-114 and HFC-
236ea are less than predicted  values. As
the entering condenser water temperature
increases,  the  measured  and  predicted
values of the coefficient of performance
move toward better agreement.

-------
  Modeled trends predict that both perfor-
mance indicators—compressor power re-
quirement and coefficient of performance—
improve as the inlet condenser water tem-
perature decreases from 38 to 16°C since
the required power consumption decreases
and  the  coefficient of performance  in-
creases. These are expected trends since
lower condenser water temperatures pro-
vide  a higher temperature difference  be-
tween the heat transfer fluids,  resulting in
increased cooling  potential in the con-
denser. HFC-236ea is  also predicted to
outperform CFC-114 over a range of inlet
condenser water temperatures, partly  be-
cause measured heat transfer coefficients
for HFC-236ea were found to be greater
than  those of CFC-114.
  The predicted values for CFC-114 and
HFC-236ea saturation temperature in  the
condenser for  a given temperature of  the
cooling water entering the condenser  are
nearly identical. The measured values of
condenser saturation temperature for CFC-
114 agree with the predicted values, while
the HFC-236ea data show the same trend
but are generally higher than predicted.
  The predicted saturation temperature for
HFC-236ea in  the evaporator as a func-
tion of the entering condenser water tem-
perature is higher than predicted for CFC-
114 over the range of entering condenser
water temperatures. The HFC-236ea data
compare well with predicted values, while
there appears  to be less agreement  be-
tween measured and modeled values for
CFC-114.
  The evaporator capacity is compared
with the temperature of the water entering
the condenser. Since the evaporator  ca-
pacity is  fixed  by holding the water-side
conditions constant, the predicted  capac-
ity values for  HFC-236ea and CFC-114
are identical. Scatter is shown in the mea-
sured values  of  HFC-236ea, while  the
measured values of CFC-114 agree well
with  predicted values.
  The condenser capacity  is also com-
pared with the entering condenser water
temperature. Predicted  values for CFC-
114 and HFC-236ea are nearly equal.  For
both  CFC-114  and HFC-236ea, measured
capacity values are higher than predicted,
with  significant scatter observed  in  the
HFC-236ea data.
  The refrigerant mass flowrate  is com-
pared with the temperature of the water
entering  the condenser.  The measured
and  predicted  values  for CFC-114 are in
close agreement, while there is significant
scatter in the data for the flowrate of HFC-
236ea. As condensing water temperature
increases, an increasing trend is predicted
in refrigerant mass flowrate.
Entering Evaporator Water
Temperature
  In this situation, the evaporator load is
defined by a constant chilled water flowrate
of 28.4 L/s, a chilled water inlet tempera-
ture of 7°C, and a chilled water exit tem-
perature ranging from 9.2 to 12.6°C. Addi-
tionally, the temperature of the water  en-
tering the condenser is  held constant at
31.4°C, and the flowrate  of the condenser
water is held constant at 31.5 L/s. As  the
cooling load is  systematically varied,  the
effect on various performance indicators
may be observed.
  As the temperature of the chilled water
returning from the load and  entering  the
evaporator increases while  other design
operating conditions remain constant, in-
creasing  power  is  required to drive  the
compressor. This is an  expected trend
because, as the water temperature enter-
ing  the evaporator increases, the load is
increased in the evaporator.  In order to
accommodate this increased load, either
the  refrigerant mass flowrate must increase
or the enthalpy difference  across  the
evaporator must increase in order to pro-
vide enough heat transfer to maintain a
constant  chilled  water exit  temperature.
The result is the need for more power to
drive the  compressor. A comparison of
HFC-236ea and CFC-114 shows that, for
the  compared range of chilled water tem-
peratures  entering the evaporator, HFC-
236ea always required  less  compressor
power than CFC-114  when  modeled as
the  working fluid.
  A comparison of the coefficient of per-
formance  as  a function  of chilled water
temperature entering the evaporator shows
that as the temperature increases the  co-
efficient of performance  decreases. This
means that as temperature increases,  the
rate of increase of power required  by  the
compressor is greater than the increase
in cooling capacity. Additionally, the coef-
ficient of performance for HFC-236ea is
higher than that for CFC-114 for the range
of temperatures modeled.

Design Recommendations
  One way to improve the performance of
the  fleet's  440-kW  chiller and allow  the
use of HFC-236ea as an alternative work-
ing  fluid  is to  reduce the  load  on  the
evaporator by increasing the temperatures
of the chilled  water  entering  and leaving
the  evaporator  by  a few degrees. This
would allow the refrigerant temperature in
the  evaporator  to rise slightly, which, in
turn, would result in an  evaporator pres-
sure that is above atmospheric pressure.
With a positive gage pressure in the evapo-
rator,  there  is  less  possibility   of
noncondensable  gases and contaminants
leaking into  the  system where they can
accumulate in the condenser and reduce
performance. The low evaporator tempera-
tures and high condenser temperatures
reported by the NSWC suggest the possi-
bility of this occurrence. This solution
avoids the cost of redesigning system com-
ponents.
  A purge device at the high point of the
condenser  would  allow purging   of
noncondensable  gases that might accu-
mulate there. If  noncondensables are a
persistent problem, the purge unit may be
malfunctioning  or the system may have
an air leak larger than the purge unit can
handle.
  A variable-speed  compressor would
eliminate the need for hot gas by-pass  or
the extensive use of inlet guide vanes  in
the compressor to control the refrigerant
flow. A variable-speed chiller would allow
maximum system performance to  be real-
ized over a broad range of operating con-
ditions, resulting  in maximum energy sav-
ings.
  Another possible improvement might be
to mix HFC-236ea  with  other non-CFC
refrigerants to form an azeotropic mixture
with properties that allow the  saturation
point in the evaporator to  stay above at-
mospheric pressure. The mixture could
be chosen so as to maintain the  desired
properties of HFC-236ea.
  Additionally,  better performance in the
Navy's fleet air-conditioning  units could
be  realized by investing in commercially
available high performance heat exchanger
tubes. While not reported in  this study,
Turbo B tubes were simulated with CFC-
114  and  HFC-236ea under fleet design
conditions and were predicted to  perform
significantly better than  10.23 fpc tubes in
both the evaporator and the condenser.
  Finally, the model predicts  that HFC-
236ea  used as  a drop-in substitute  for
CFC-114 without any design modifications
may result in energy savings.  The model
predicts that, for any set of conditions, the
power  required for  a refrigeration  cycle
using HFC-236ea as a drop-in will be sig-
nificantly  less than the  same cycle using
CFC-114 as the working fluid. The  pre-
dicted savings in power consumption by
using HFC-236ea at the  design point  of
operation is 8.6%. If  HFC-236ea is to be
used only as a near-term replacement, it
may be appropriate to use it without mak-
ing any significant design changes to the
system.

-------
Conclusion
  The  Montreal Protocol  began a world-
wide drive to eliminate the  production of
CFCs  and other chemicals  which  are
thought to be harmful to the environment.
As  a result of the  restrictive  legislation
that followed, there is an immediate need
to replace CFC-114 which is used exten-
sively in U.S.  Navy surface craft and sub-
marines.  Preliminary research conducted
by the EPA  suggested that HFC-236ea
might perform suitably as a near-term drop-
in replacement for CFC-114.  However, at
the  time  of this study,  heat transfer data
for HFC-236ea were not available.
  For this reason, a computer model was
developed  for comparing CFC-114 and
HFC-236ea in a simulated 440-kW labo-
ratory centrifugal chiller system represen-
tative of those found in the U.S. fleet. The
model  is  semi-empirical, combining ther-
modynamic and  heat transfer theory, as
well as boiling and condensing heat trans-
fer coefficient data measured at the Iowa
State University Heat Transfer Test Facil-
ity.
  The NSWC in Annapolis, MD, also pro-
vided data for this study. A 440-kW labo-
ratory centrifugal air-conditioning plant and
HFC-236ea were used for the data collec-
tion.  The experimental data  provided by
the NSWC were compared with the mod-
eled  results.
  The model was tested for a range of
inlet  condenser water temperatures,  en-
tering and leaving chilled water tempera-
tures, and evaporator and condenser wa-
ter flowrates. The  simulation model  pre-
dicts that HFC-236ea would perform fa-
vorably  as  a drop-in substitute for CFC-
114 .
  Additionally,  several  recommendations
were  provided  for improved performance
using HFC-236ea in centrifugal chiller sys-
tems. Design recommendations discussed
in  this  study  include  manipulating  the
evaporator load to achieve  positive gage
pressure in the evaporator, ensuring the
absence of noncondensable gases in the
system, using a variable-speed compres-
sor with a fixed inlet guide vane angle to
the impeller, conducting further research
using azeotropic mixtures with HFC-236ea
as  the  major component,  and  installing
high-performance enhanced surface tubes
in both the evaporator and the condenser.
  In summary, the simulation developed
in this study provides results that are con-
sistent with the expected  behavior  of a
440-kW refrigeration system. The results
provided by the NSWC sufficiently  vali-
date the model. Finally, the results  sug-
gest that HFC-236ea would perform well
in  existing  CFC-114 centrifugal chillers,
although design modifications should be
considered for optimal  performance.

-------
   D. T. Ray, M. B. Pate, and H. N. Shapiro are with Iowa State University, Ames, IA
     50011.
   Theodore G. Brna is the EPA Project Officer (see below).
   The complete report, entitled "Comparison of CFC-114 and HFC-236ea Perfor-
     mance in Shipboard Vapor Compression Systems," (Order No. PB97-178735;
     Cost: $25.00, subject to change) will be available only from:
           National Technical Information Service
           5285 Port Royal Road
           Springfield, VA22161
           Telephone: 703-487-4650
   The EPA Project Officer can be contacted at:
           Air Pollution Prevention and Control Division
           National Risk Management Research Laboratory
           U.S. Environmental Protection Agency
           Research Triangle Park, NC 27711
United States
Environmental Protection Agency
Center for Environmental Research Information
Cincinnati, OH 45268

Official Business
Penalty for Private Use $300
     BULK RATE
POSTAGE & FEES PAID
         EPA
   PERMIT NO. G-35
EPA/600/SR-97/058

-------