United States
Environmental Protection
Agency
National Risk Management
Research Laboratory
Research Triangle Park, NC 27711
Research and Development
EPA/600/SR-98/029  April 1998
Project Summary
Heat  Transfer Evaluation of
HFC-236fa  In Condensation  and
Evaporation
S.-M. Tzuoo and M.B. Pate
   The shell-side heat transfer perfor-
mance of  hydrofluorocarbon (HFC)-
236fa, which is considered to be a po-
tential substitute for  chlorofluorocar-
bon (CFC)-114 in Navy shipboard chill-
ers, was evaluated in this study for
both  conventional finned  [1024- and
1575-fpm (fins-per-meter)] tubes and
high performance enhanced (Turbo-CII,
-B, and -Bll) tubes.
   Condensation of oil-free HFC-236fa
was conducted on 1024- and 1575-fpm,
and  Turbo-CII tubes. Pool boiling on
four tube types (1024- and 1575-fpm,
and Turbo-B  and -Bll) was tested not
only  for pure HFC-236fa  but also for
HFC-236fa mixed with 1 and 3%  lubri-
cant  by weight. The polyolester  lubri-
cant  used has a viscosity  340 SSU at
37.8°C (100°F) and the trade name of
Castrol Icematic SW-68.  The  above
tubes, which  have nominal outside di-
ameters of 19.1 mm (3/4-in.), were evalu-
ated at a saturation temperature of 40 C
for condensation and 2 C for pool boil-
ing over the heat flux range of 15 to 40
kW/m2.
   Heat transfer was improved for
HFC-236fa  by using the  high perfor-
mance enhanced tubes. Specifically, the
Turbo-CII tube  performed  better than
the two conventional  finned  tubes in
condensation testing,  while the perfor-
mance of the Turbo-B and -Bll tubes
was superior to the two conventional
finned tubes in pool boiling testing.
   The maximum increase in heat
transfer coefficient for the Turbo-CII
tube was 80% relative to the 1024-fpm
tube  and 70% relative to the 1575-fpm
tube, while  for the Turbo-B tube, it was
0.7 and 1.2 times greater than for the
1024-and 1575-fpm tubes, respectively.
 In addition, the Turbo-BII tube gave boil-
 ing heat transfer coefficients up to 80%
 larger than those of the Turbo-B tube.
    The heat transfer  performance of
 HFC-236fa was compared with the CFC-
 114 and  HFC-236ea data  obtained in
 earlier studies using the same test fa-
 cility.  For all tube types tested, except
 the Turbo-CII  tube, the heat  transfer
 results showed that  HFC-236fa  per-
 formed better than CFC-114 and HFC-
 236ea during both shell-side  conden-
 sation and pool boiling. The heat trans-
 fer  coefficients for HFC-236fa during
 condensation were up to 40% larger
 than those for CFC-114 and up to 30%
 larger than those for HFC-236ea, while
 the pool boiling coefficients were up to
 80% higher for HFC-236fa compared
 with CFC-114  and up to  70% higher
 compared with HFC-236ea. The  con-
 densation heat transfer coefficients for
 the Turbo-CII tube were similar for both
 HFC-236fa and -236ea; the deviation
 was within  10%. The  effects  of com-
 pressor oil on heat transfer  perfor-
 mance during pool boiling were inves-
 tigated. The presence  of up to 3% oil
 (by weight) in HFC-236fa  affected the
 boiling performance by less than a 10%
 deviation from the pure HFC-236fa re-
 sults for all but one of the tubes tested.
 The Turbo-BII tube, the only exception,
 showed  an increase in boiling coeffi-
 cients of up to 30% over  the pure-re-
 frigerant values for the testing with 1%
 oil and up to 15%  with 3% oil.
    This report was submitted by  Iowa
 State University under the sponsorship
 of the U.S. Environmental Protection
 Agency  (EPA)  with funding from the
 EPA/Department of Defense/Department
 of Energy Strategic Environmental Re-

-------
search and  Development Program
(SERDP).
    This Project Summary was devel-
oped by EPA's National Risk Manage-
ment Research Laboratory, Research
Triangle Park, NC,  to announce  key
findings of the research project that is
fully documented in a separate report
of the same  title (see Project Report
ordering information at back).

Introduction
    This research evaluated  the  heat
transfer coefficients for HFC-236fa during
condensation and  pool boiling on the out-
side  of a  single  horizontal tube with a
nominal outside diameter of 19.1 mm (3/
4-in.). Two types of integral finned (1024-
and 1575-fpm) tubes and three types of
high  performance  enhanced (Turbo-CII, -
B, and -Bll) tubes were tested for the heat
transfer performance of HFC-236fa. Inte-
gral finned tubes tested are presently used
in Navy shipboard heat exchangers to en-
hance heat transfer, while three high  per-
formance enhanced tubes, which were pro-
duced  by advanced manufacturing tech-
niques, were tested to evaluate their po-
tential for improving the heat transfer per-
formance of chillers but have not yet been
used in shipboard chillers.
    Saturated  pool boiling was also in-
vestigated for  HFC-236fa  mixed with 1
and  3%  oil  by weight.  A  miscible
polyolester oil with a viscosity of 340 SSU
at 37.8°C  was added to HFC-236fa, in
order to assess the  effects  of the  oil's
presence on the boiling heat transfer per-
formance.
    In addition, the comparative  heat
transfer performance of HFC-236fa and -
236ea, and CFC-114 was made in order
to evaluate the possibility of replacing CFC-
114 with HFC-236fa. The first two  refrig-
erants  are  non-ozone depleting alterna-
tives for CFC-114.  Both CFC-114  and
HFC-236ea were tested earlier in the cur-
rent test facility.

Objectives and Scope
    This study not only evaluated  the
shell-side heat transfer coefficients of an
environmentally  safe  refrigerant,  HFC-
236fa, during condensation and pool boil-
ing for two integral finned (1024- and 1575-
fpm) tubes and three high performance
enhanced (Turbo-CII, -B, and  -Bll) tubes
but also compared the heat transfer  per-
formance of the tubes tested  with HFC-
236fa.  In addition, the comparison  of the
heat transfer coefficients for HFC-236fa
and -236ea and CFC-114 was also an
important objective, where HFC-236fa and
HFC-236ea are  potential alternative  re-
frigerants for CFC-114.
    Using the same test facility which al-
lows analysis of condensation and pool
boiling, measurements were conducted on
a single-tube configuration at a saturation
temperature of 2°C for pool boiling and at
40°C for condensation over the heat flux
range of 15 to 40 kW/m2.
    Two integral finned (1024- and 1575-
fpm) tubes were tested for both shell-side
condensation  and  pool  boiling.  In  addi-
tion, the Turbo-CII  tube, designed to en-
hance  condensation, was  tested during
shell-side  condensation while  the en-
hanced  boiling  Turbo-B and  -Bll  tubes
were tested in pool boiling.
    The comparative heat transfer perfor-
mance of the high  performance enhanced
tubes  with the conventional finned tubes
was made  for HFC-236fa  in  this study.
Heat transfer results for CFC-114  and
HFC-236ea and -236fa  were also  com-
pared with each other. CFC-114 and HFC-
236ea were tested previously in the same
test facility. In addition, the effects of oil in
the refrigerant on the heat transfer perfor-
mance during pool  boiling were assessed
for HFC-236fa in this research.
    The heat transfer coefficients for the
integral finned  tubes were  used  as  a
baseline for comparing the  heat transfer
performance of the high  performance en-
hanced tubes. All the tubes compared had
the same  tube outside diameter of 19.1
mm (3/4-in.).

Experimental Apparatus
    Even though the same test rig was
used in all the experiments, different ex-
perimental arrangements were required for
testing condensation and pool boiling. The
main components  of the test facility  in-
cluded  the test section, tubes  under test,
closed water loop,  closed refrigerant loop,
glycol/water chiller,  and  data  acquisition
system.
    The heat transfer experiments  were
performed in a cylindrical, stainless  steel
chamber. On  the top of the test section
are two ports which are passageways for
vapor. The test section also has two  other
ports on the  bottom to serve as  liquid
paths.
    The closed water loop consists mainly
of a storage tank,  two triplex diaphragm
pumps, a flowmeter, an immersion heater,
and a  dual-tube  heat exchanger. The
heater and heat exchanger were used to
control the water temperature.
    The glycol/water mixture was pumped
through a  chiller with a  105-kW (30-ton)
cooling  capacity and could be  supplied
through manifolds to the dual-tube heat
exchanger, two   condensers,  and  a
subcooler.
    During condensation tests,  a stain-
less  steel boiler was used to vaporize
refrigerant before it reached the test sec-
tion.  For evaporation tests, a subcooler
and two condensers were utilized to con-
dense refrigerant after it was boiled in the
test section.

Condensation Results
    Heat  transfer coefficients were  ob-
tained for condensation of HFC-236fa on
three tube types— 1024- and 1575-fpm,
and Turbo-CII tubes. A comparison of re-
sults for these tubes with the previously
obtained  results of  CFC-114  and HFC-
236ea was made.
    The  best heat transfer performance
with HFC-236fa was provided by the high
performance Turbo-CII tube, indicating an
increase  in  heat transfer coefficients of
around 20 to  80%  with  respect to  the
1024-fpm tube, and about 40 to 70% with
respect to the 1575-fpm tube.
    The HFC-236fa performed better than
CFC-114 and HFC-236ea during conden-
sation for all the tube types tested except
the Turbo-CII tube. The HFC-236fa yielded
a maximum  increase of 40% compared
with  CFC-114  and 30%  compared with
HFC-236ea. The condensation heat trans-
fer coefficients produced by the Turbo-CII
tube were similar for both HFC-236fa  and
-236ea. Data were not taken on the Turbo-
CII tube with CFC-114.

Pool Boiling Results
    Heat transfer coefficients on four tube
types (1024- and 1575-fpm, and Turbo-B
and -Bll) were determined for pool boiling
of HFC-236fa  as well  as HFC-236fa/oil
mixtures. The effects of oil and tube types
on the  boiling  heat transfer performance
of HFC-236fa were assessed. In addition,
comparison was also made for these  test
tubes with the previous results of CFC-
114 and HFC-236ea in  order to evaluate
the effects of refrigerant type on the boil-
ing performance.
    The  best heat transfer performance
with HFC-236fa was provided by the high
performance  Turbo-BII  tube  with  heat
transfer coefficients  of  around  2  to  2.9,
2.4 to 3.8, and 1.2 to 1.8 times the values
for the  1024- and 1575-fpm, and Turbo-B
tubes, respectively.
    The HFC-236fa performed better than
CFC-114 and HFC-236ea during pool boil-
ing for all the tube types tested. The HFC-
236fa provided a maximum heat transfer
coefficient increase of 80% compared with
CFC-114 and 70% compared with HFC-
236ea.
    The  small amount  of oil, up to  3%
concentration, present during pool boiling
was found to affect the heat transfer per-

-------
formance by less than 10% relative to the
pure HFC-236fa results for all but one of
the tubes tested. The exception was the
Turbo-BII tube.  As noted, the Turbo-BII
tube showed the largest increase in per-
formance with a 30% enhancement at 1%
oil and  a  15% enhancement at 3%  oil
over the pure refrigerant value.

Summary
    The heat transfer coefficients of HFC-
236fa, proposed as a CFC-114 substitute,
were measured for 1024- and 1575-fpm
conventional finned tubes and Turbo-CII,
-B,  and  -Bll  high performance enhanced
tubes during shell-side condensation and
pool boiling  on the outside  of  a  single
horizontal  tube.  The high  performance
enhanced tubes were found to effectively
increase heat transfer and produced higher
heat  transfer  coefficients  than the
conventional finned tubes.
    The Turbo-CII tube produced notice-
ably higher  heat transfer coefficients in
condensation than  the  1024-  and  1575-
fpm tubes, and yielded  around 1.2 to 1.8
times the  values  of the  1024-fpm tube
and 1.4 to  1.7 times those of the 1575-
fpm tube.
    The pool boiling results for both pure
HFC-236fa  and HFC-236fa with  oil show
that the tube performance  in descending
order  was Turbo-BII  and -B,  and 1024-
and 1575-fpm tubes.  Heat transfer coeffi-
cients for pure HFC-236fa provided by the
Turbo-B tube are 1.6 to 1.7 and 1.9 to 2.2
times  those  by the 1024-  and 1575-fpm
tubes,  respectively.  The Turbo-BII  tube
outperformed the other tubes tested and
produced 1.2 to 1.8 times the heat trans-
fer coefficients of the  Turbo-B tube.
    For the pool  boiling testing, a mis-
cible polyolester oil with a viscosity of 340
SSU at 37.8°C was added  to HFC-236fa.
The oil concentrations in the HFC-236fa
were 1 and 3% by weight. The oil effects
on HFC-236fa caused the  boiling coeffi-
cients to deviate less than 10% from those
for the pure HFC-236fa tested with all the
tubes tested except the Turbo-BII tube.
    Although the high performance Turbo-
BII tube produced the highest heat trans-
fer coefficients of all  the tubes tested,  it
showed larger changes in pool boiling per-
formance with the addition of oil. Specifi-
cally, the Turbo-BII tube had a 10 to 30%
increase at the 1% oil concentration over
the results for pure HFC-236fa and a 10%
decrease to 15%  increase at the 3% oil
concentration.
    A comparison of shell-side heat trans-
fer coefficients was  made for  CFC-114
and its two proposed alternative refriger-
ants; i.e., HFC-236fa  and -236ea. In gen-
eral, HFC-236fa was found to have better
heat transfer performance than CFC-114
and HFC-236ea during both shell-side con-
densation and pool boiling. For condensa-
tion,  HFC-236fa yielded a maximum  in-
crease of 40% compared with  CFC-114
and 30% compared with HFC-236ea. For
pool boiling, HFC-236fa provided a maxi-
mum increase of 80%  compared with CFC-
114 and 70% compared with HFC-236ea.
    Replacing CFC-114 with HFC-236fa
is desirable in terms  of the heat transfer
performance based on the comparison of
CFC-114,  and  HFC-236ea and -236fa
made in this study. In addition, the high
performance  enhanced  tubes outper-
formed the finned  tubes at all the testing
conditions in this research.

-------
   S.-M. Tzuoo and M. B. Pate are with Iowa State University, Ames, IA 50011.
   Theodore G. Brna is the EPA Project Officer (see below).
   The complete report, entitled "Heat Transfer Evaluation ofHFC-236fa in Conden-
     sation and Evaporation," (Order No. PB98-136203; Cost: $27.00, subject to
     change) will be available only from:
           National Technical Information Service
           5285 Port Royal Road
           Springfield,  VA 22161
           Telephone:  703-605-6000
   The EPA Project Officer can be contacted at:
           National Risk Management Research Laboratory
           U.S. Environmental Protection Agency
           Research Triangle Park, NC 27711
United States
Environmental Protection Agency
Center for Environmental Research Information
Cincinnati, OH 45268

Official Business
Penalty for Private Use $300
     BULK RATE
POSTAGE & FEES PAID
         EPA
   PERMIT NO. G-35
EPA/600/SR-98/029

-------