THE ENVIRONMENTAL TECHNOLOGY VERIFICATION
                                    PROGRAM
  &ER/V
HOI
INTERNATIONAL
  U.S. Environmental Protection Agency                               NSF International

                                    turning knowledge into practice
                      ETV Joint Verification Statement
    TECHNOLOGY TYPE:   Infrastructure Rehabilitation Technologies
    APPLICATION:        Grouts for Wastewater Collection Systems
    TECHNOLOGY NAME:  Warren Environmental M-301 Epoxy Trowel On Mastic Systems
    TEST LOCATION:      University of Houston, CIGMAT
    COMPANY:           Warren Environmental, Inc.
    ADDRESS:            P.O. Box 1206             PHONE:   508-4947-8539
                         Carver, MA 02330         FAX:     508-947-3220
    WEB SITE:            http://www.warrenenviro.com
    EMAIL:               http://www.warrenenviro.com/contact_us.html
The U.S. Environmental Protection Agency (EPA) created the Environmental Technology Verification
(ETV) Program to facilitate the deployment of innovative or improved environmental technologies
through performance verification and dissemination of information. The program's goal is to further
environmental protection by accelerating the acceptance and use of improved and more cost-effective
technologies. ETV  seeks to  achieve this goal by providing high  quality, peer-reviewed data  on
technology performance to those involved in the design, distribution, permitting, purchase, and use of
environmental technologies.
ETV works in partnership with recognized standards and testing organizations; stakeholder groups,
which consist of buyers, vendor organizations, and permitters; and with the full participation of
individual technology developers. The program evaluates the performance  of innovative technologies
by developing test plans that are responsive to the needs of stakeholders, conducting field or laboratory
tests as appropriate,  collecting  and  analyzing  data,  and  preparing peer-reviewed reports.  All
evaluations are conducted in accordance with rigorous quality assurance protocols to ensure that data
of known and adequate quality are generated and that the results are defensible.
NSF International (NSF), in  cooperation with EPA, operates the Water  Quality Protection Center
(WQPC), one of six centers under  the ETV Program.  This evaluation of the performance of the
Warren Environmental, Inc. M-301  Epoxy Trowel-On Mastic Grout for wastewater infrastructure
rehabilitation was  completed under  a  contract (No. EP-C-05-060) between EPA's  Office  of
Research  and Development and RTI International. The testing was performed by the University of
Houston's  Center  for  Innovative  Grouting  Materials   and  Technology  (CIGMAT),  with
subcontract  support by NSF  International.

-------
TECHNOLOGY DESCRIPTION
The following description of the M-301 Epoxy Trowel On Mastic System (M-301) was provided by the vendor
and does not represent verified information.

The M-301 Epoxy can be used for sealing leaks in sewer pipe joints, and can also be used to control water
seepage in cracks and joints in subgrade concrete structures. The grout was formulated with special additives
and modifiers to enhance water and chemical resistance, and bond strength to a variety of substrates, as well as
its own internal strength. The  high thixotropic index allows for build-ups  of up  to %" on vertical surfaces
without sag. It has been designed to be applied to a clean surface free of standing water with a notched (toothed)
trowel  similar  to stucco. Alternately,  it  may  be applied  using  heated  tanks,  heated   lines,  and
Warren Environmental Inc.'s patented meter, mix, and spray equipment. This Epoxy system utilizes a 2 parts
base-to-1 part activator mix ratio by volume. This product is sold and installed only by technicians specifically
trained and licensed in the manufacturer's patented techniques.

VERIFICATION TESTING DESCRIPTION - METHODS AND PROCEDURES
Verification  testing was conducted to evaluate M-301 Epoxy used in wastewater collection  and treatment
systems to control leaks into the systems.  Specific testing objectives were (1) to evaluate the grout for working
properties (setting  (gel) time),  physical and mechanical properties (unit weight, water absorption, shrinkage,
permeability and compressive strength), durability and environmental properties (wet-dry  cycle and chemical
resistance), (2) evaluate grout-substrate interactions, under both wet and wet-dry conditions, and (3) determine
the effectiveness of the grout in controlling leakage in cracked concrete using a model test.
There are no relevant  American  Society for Testing and Materials (ASTM)  methods,  so the  testing  was
conducted following methods developed by CIGMAT, including CIGMAT(1) GR 1-04, GR 3-04, GR 7-04, GR
2-04, GR 3-04,  CH 2-04 and CT 3-00.  Product characterization tests were conducted on specimens of M-301
created  for the  purpose, and the uncoated concrete specimens used in the grout-substrate interaction tests to
assure uniformity prior to their use in the bonding strength tests. Warren Environmental representatives were
responsible for coating the concrete specimens and completing the repair of the concrete crack simulations in the
model test, under the guidance  of CIGMAT staff members.  The  coated specimens were evaluated over the
course of six months.

PERFORMANCE VERIFICATION
Grout Material Evaluation
(a) Working properties
Setting time was determined by the elapsed time from grout preparation until the grout no longer flowed from a
plastic cup or beaker inclined slowly (so that if the cup/beaker were filled with liquid, the surface of the liquid
would remain level) to  45  degrees. Observations made at periodic intervals  determined if the grout exhibited
liquid-flow properties,  or if the grout sample had gelled  and the specimen could  no  longer flow from  the
container. Six replicates of grout were observed, with times varying from 38 to 40 minutes, with an average of
39 minutes.

(b) Physical and mechanical properties
Grout test specimens prepared for physical and mechanical tests consisted of cylinders approximately 4.5 inches
(in.) high  with a diameter of approximately 1.5 in. with a resin-to-water ratio of 9:1.  Specimens were cured
under ambient room temperature and humidity conditions.  Cured specimens were removed from the mold and
stored in labeled, sealed plastic bags for identification, protection, and to prevent moisture loss.

(i) Unit weight - Unit weight was determined for three  specimens by taking the  weight of the specimens
   divided by the  volume.  The unit weight measurements ranged from 0.91 to 1.09 g/cm3, with an average of
    l.OOg/cm3.
                                                 m

-------
(ii) Water absorption - Three grout specimens were immersed in tap water (initial pH approximately 7), and
   changes in the  weight and volume (determined by measuring specimen diameter and  height) of the
   specimens were  recorded daily over a 4-day period. The weight change of the three specimens varied from
   0.09% to 0.17%, with an average of 0.14%.  The volume change in the specimen varied  from 0.03% to
   0.06%, with a mean of 0.04%.

(iii)Shrinkage - Three grout specimens were placed in sealed bags and held for 28 days at 23°C  ± 2°C and
   relative humidity (RH) of 90%+ 5%. The weight and dimensions of the specimens were measured before
   and after the test.  It was found that the weight change varied from 0 to  0.09%, with an average value of
   0.06%, and the volume change varied from 0 to 0.04%, with an average of 0.01%.

(iv)Permeability - Three grout specimens were prepared in 1.5-in. diameter Plexiglas/glass cylinders and cured
   for a period of 7 days under room conditions. The cured specimens were  permeated with water under a
   hydraulic gradient of 100 over a period of 72 hours.  There was no observed discharge from  any of the
   specimens indicating the permeability of the grout to be zero.

(v) Compressive strength - Compression tests on specimens cured over periods of 3,  7 and 28  days using a
   screw-type machine.  Collected  data included the compressive strength, modulus (determined from the
   initial slope of the stress/strain relationship), and failure strain (the maximum strain before the specimen
   failed). A total of 11 specimens were tested. The average strength, failure strain, and initial modulus after 3
   days of curing were 6591 psi, 9%, and 225,000 psi, respectively; the  average strength, failure  strain, and
   initial modulus after 7 days  of curing were  6402 psi, 5%,  and 225,000 psi, respectively; and the average
   strength,  failure  strain, and  initial modulus  after 28 days  of curing were 6180 psi, 5%, and 195,000 psi,
   respectively.

(c) Durability properties
(i) Wet-dry cycles - This test was designed to determine the impact of repeated wetting  and drying on the
   performance of grouts. Three replicate specimens were subjected to 10 wet/dry cycles for a total test time of
   140 days, or until failure (specimen completely deteriorated). One wet/dry cycle was  14 days in duration,
   consisting of 7  days  of water exposure in tap water (pH approximately 7) followed  by 7 days of dry
   conditions at room temperature and humidity (23 ± 2°C and 50% ± 5% RH). Changes in length, diameter,
   weight, and volume of the  specimens were measured  daily. At the  end  of the 10 wet/dry cycles, the
   specimens were tested to determine the compressive strength of the grout.  After the first wet-dry cycle, the
   average change in weight, length, diameter, and volume was 0.04%, -0.25%, 0%, and -0.25%, respectively.
   The unit weight of the specimens increased over time, while the length of the specimens decreased. After
   the tenth wet-dry cycle, the  average change in weight, length, diameter, and volume was  0.25%, -0.41%,
   0%, and -0.41%, respectively. The unit weight of the specimens increased.  The average strength of the grout
   after 10 wet-dry  cycles was also determined and found to be an average of 6,531 psi, approximately equal to
   the 3-day compressive strength of the grout.

(ii) Chemical resistance  - This  test evaluates the resistance of grouts when exposed to  chemical  conditions
   representing various environmental applications and will help when selecting suitable grouts  for use in
   various chemical environments. A total of nine  grout specimens were prepared, and  the initial weight,
   dimensions, color, and surface appearance of the specimens were recorded. Three specimens at each pH
   were fully immersed in solutions, with pH 2, 7, and 10 maintained at room temperature  (23 ± 2°C) for the
   entire exposure period. The  solutions consisted of tap water, with hydrochloric acid or sodium hydroxide
   added to achieve the pH required for the  tests. The weight and volume  change were determined and
   recorded for three specimens at each pH after 30, 90, and 180 days, with the following results:
   pH= 2 solution: After 30 days, the average change in weight, volume, and unit weight was 0.32%, 0.59%,
   and -0.27%, respectively. After 180 days, the average change in  weight,  volume, and unit weight was
   1.38%, 1.70%, and -0.31%, respectively. The weight and volume increased over the 180 days period.
   pH= 7 (tap water): After one month, the average change  in weight, volume, and unit weight was 0.29%,
   0.11%, and 0.18%, respectively After 180 days, the average change in weight, volume, and unit weight was

                                                 iv

-------
    1.24%, 0.47%, and 0.77%, respectively. The weight and volume increased over the  180 day period, as did
    the unit weight.

    pH= 10 solution: After 30 days, the average change in weight, volume, and unit weight was 0.42%, -0.06%,
    and 0.48%, respectively After 180 days, the average change in weight, volume, and unit weight was 1.24%,
    0.47%, and 0.79%, respectively. The weight and volume increased over the 180 day period, as did the unit
    weight.

(d) Environmental properties
Potential contaminant leaching from solidified grout was determined by analyzing water exposed to the grout
for total organic carbon (TOC).  Three test replicates, using cylindrical grout specimens of equal volumes and
approximate equal weights, were  exposed to tap water in  individual  exposure jars for 7 days.  One  blank
container containing only the exposure water was prepared and held under the same conditions as the specimen
exposure jars.  The test was  conducted with three grout specimens and water volume so that  there was an
adequate volume exposed to water to conduct the required analyses. A  liquid-to-solid ratio of 1:1 (by volume)
was used. The  results found from 0.057 to 0.185 g of TOC/L, which translated to 0.0007 to 0.0023 g TOC/L/g
grout, with a  mean of 0.0017 g/L/g.   These data should  be considered  estimated values  because  of data
uncertainty arising from incomplete QA/QC, as discussed in the QA/QC  section of this statement.

Grout-Substrate Interaction

Interaction between the grout and a concrete substrate was evaluated by  testing the bonding strength and type of
failure (i.e., bonding failure, substrate failure, or a combination) of prepared  concrete  bricks to which grout was
applied under different service conditions. The test sandwich specimens  were formed by applying grout material
to an area of one concrete brick, then overlapping a second brick in a perpendicular direction to the first to allow
the grout to form a filling between the overlap areas, as shown in Figure  1.

                         ••LSB^—^^—^

                                                                   Concrete
                                                                     Brick

                                                                    Epoxy
                                                                     Grout

                        Figure 1. Formation of sandwich specimens.

Grout/concrete substrate specimens were exposed to (1) wet conditions and (2)  a wet/dry cycle test.  Four
sandwich specimens were evaluated at each of 30, 90 and 180 days following water curing, and three were
evaluated after 180 days of wet-dry cycle curing. The cured specimens were tested on a load frame to determine
the break strength of the grout-brick bond. The break type was evaluated to determine where the failure occurred
as described in Table 1.  The results of the testing are summarized in Table 2.  The failures observed in the
specimens were all either Type 1 or Type 4, without a significant change in the break strength over the 180 day
period, averages ranging from 257 to 280 psi.  The specimens exposed to the wet/dry cycle showed lower break
strengths, averaging 233 psi.

-------
                             Table 1.  Bonding Failure Types
          Failure Type
      Description
Sandwich Test
             Type 1
   Substrate Failure
             Type 4
Bonding and Substrate
        Failure
                                                              Concrete Brick
 ?te Bri(
 X
Table
                               Summary of Bonding Strength Tests
Exposure
Time
(days)
30
90
180

Exposure
Conditions
Water
Water
Water
Wet-Dry
Cycles
Failure Type 1
1 2
O
2
3
3
- Number of Failures Failure Strength (psi)
345 Range Average
1 228-288
2 247-304
1 204-329
204-278
260
280
257
233
1  See Table 1.

Model Test Evaluation

For this study, Warren Environmental, Inc. selected the model test related to leak control in cracked concrete.
The  model test uses  10-inch.  (25-cm) diameter circular concrete disks with six-inch (15-cm) openings at the
center  (each disk is donut-shaped) to  simulate a leak in a concrete structure.  The two disks were placed one-
inch apart and the opening was grouted by the vendor, as shown in Figure 2. After the vendor-specified curing
period, the grouted joint was  placed  in a Plexiglas chamber (Figure 3), which was sealed to allow water to
completely surround the  grouted joint. Hydrostatic pressures of 3, 4, and 5 psi were applied through the inlet to
the Plexiglas enclosure for 5  minutes at each pressure, and the  water leaking through the grouted joint was
collected and recorded. After two wet-dry cycles, the hydrostatic pressure tests were repeated.

Two replicate model tests were completed.  As shown in Table 3,  the model tests showed that the grouting with
M-301 was effective in significantly reducing or eliminating the leak volume in the cracked concrete (0 to 19.3
gallons/day at 5 psi water pressure) immediately after grouting and after two wet and dry cycles over period of
one month (0 to 16.2 gallons/day at 5 psi water pressure).
                                                 VI

-------
     Figure 2.  Repaired cracked concrete.                       Figure 3. Model test setup.

                        Table 3. Model Test 4 Leak Rate Results (gallons/day)
Hydrostatic
Pressure (psi)
3
4
5
Replicate 1
Initial Wet-Dry Cycle
Condition Condition
11.5
13.9
19.3
7.6
12.6
16.2
Replicate 2
Initial Wet-Dry Cycle
Condition Condition
0.0
0.0
0.0
0.0
0.0
0.0
Summary of Verification Results
The tests resulted in the following conclusions for Warren Environmental's M-301Epoxy Mastic Grout:

    •   The setting time of the grout at room temperature (70°F) varied from 38 to 40 minutes, and the average
       unit weight of the solid grout was 62.6 pcf.

    •   During the water absorption test (under saturated conditions), the weight change in the specimens varied
       from 0.09% to 0.17%,  with an average  of 0.14%. The volume change  in the specimen varied from
       0.03% to 0.05%, with a mean of 0.04%.

    •   The shrinkage at 23°C and 90% RH after 28 days of testing resulted in an average weight and volume
       change of 0.03% and 0.01%, respectively.

    •   The permeability of the  grout was zero (impermeable) under a hydraulic gradient of 100 held for 4 days.

    •   The average strength, failure strain, and initial modulus after 3  days of curing were 6,591 psi, 9%, and
       225,000 psi,  respectively. The average strength,  failure strain, and initial modulus after 28  days  of
       curing were 6,180 psi, 5%, and 195,000 psi, respectively.

    •   After ten  wet-dry cycles, the  average change in weight, length, diameter and volume was 0.25%,
       - 0.41%, 0%, and -0.41%, respectively.  The unit weight of the  specimens increased by 0.99%. The
       average strength  of the  grout after 10 wet-dry cycles was 6,531 psi; hence, the specimen strength was
       not affected after 10 wet-dry cycles.

    •   After 180 days in a pH =2 solution (acid), the average change  in unit weight and volume was -0.31%
       and 1.70%, respectively. After 180 days in a pH =7 solution (water), the average change in unit weight
       and volume was 0.77% and 0.47%, respectively. After 180 days  in a pH =10 solution (base), the average
       change in unit weight and volume was 0.79% and 0.47%, respectively.
                                                 VII

-------
    •   The average total organic content (TOC) in the leaching water was 0.0017 g/L/g of grout; however,
        because of incomplete QA/QC, these results should only be considered estimated values.

    •   The bonding strength for water cured grout-concrete specimens did not vary significantly over a 180
        day exposure period,  with average strengths ranging from 257 to 280 psi; most of the specimen failures
        were Type 1 (substrate), with others being Type 4 (substrate failure with the grout intact).

    •   After 180 days of the grout-substrate test, following 10 wet-dry cycles, the average bonding strength
        was 233 psi, and all (100%) of the failures were Type 1.

    •   Model tests  showed that grouting with M-301 significantly reduced or eliminated the leak in a simulated
        one-inch concrete crack (0 to  19.3 gallons/day at 5 psi water pressure) immediately after grouting, and
        after two wet and dry cycles over period of 30 days (0 to 16.2 gallons/day at 5 psi water pressure). Prior
        to grouting all of the water leaked out of the open pipe joint.

Quality Assurance/Quality Control
A technical systems audit prior to the  start of testing to ensure that CIGMAT was equipped to comply with the
test plan, along with a data  quality audit of at least  10%  of the  test data to ensure that  the  reported data
represented the  data generated during testing.  The documentation submitted by  CIGMAT for the  working
properties, physical  and mechanical properties, and durability properties support the findings as described in this
report.  The documentation provided by  CIGMAT for the TOC analyses  showed  that the laboratory did not
produce sufficient QC documentation to provide traceability to back  up the TOC analytical results.  Overall, the
TOC data does not  have the  QA/QC  support to validate or refute the reported values.  Further explanation is
provided in the verification report.
      Original Signed by                                    Original Signed by
      Cynthia Sonich-Mullin                5/14/2013       Thomas J. Bruursema        3/19/2013
       Cynthia Sonich-Mullin               Date              Thomas J. Bruusema         Date
       Director                                               Director
       National Risk Management Research Laboratory         Sustainability
       Office of Research and Development                    NSF International
       United States Environmental Protection Agency
    NOTICE: Verifications are based on an evaluation of technology performance under specific, predetermined criteria and the
    appropriate quality assurance procedures. EPA and NSF make no expressed or implied warranties as to the performance of the
    technology and do not certify that a technology will always operate as verified. The end user is solely responsible for
    complying with any and all applicable federal, state, and local requirements. Mention of corporate names, trade names, or
    commercial products does not constitute endorsement or recommendation for use of specific products. This report is not an
    NSF Certification of the specific product mentioned herein.
        Availability of Supporting Documents
        Referenced Documents:
        1)   CIGMAT Laboratory Methods for Evaluating Grout and Coating Materials, available from the University of
            Houston, Center for Innovative Grouting Materials and Technology, Houston, TX.
        Copies of the Test Plan for Verification of Warren Environmental Inc. Mastic 301-04 for Infrastructure
        Rehabilitation (September 2009), the verification statement, and the verification report (NSF Report
        Number 10/34/WQPC-SWP) are available from:
            ETV Water Quality Protection Center Program Manager (hard copy)
            NSF International
            P.O. Box 130140
            Ann Arbor, Michigan 48113-0140
        NSF website: http://www.nsf.org/etv (electronic copy)
        EPA website: http://www.epa.gov/erv (electronic  copy)
                                                    Vlll

-------