United States
    Environmental Protection
    Agency
EPA/600/R-15/326
January 2016
www.epa.gov/water-research
TESTING AND PERFORMANCE
EVALUATION OF AN INNOVATIVE
INTERNAL PIPE SEALING SYSTEM FOR
WASTEWATER MAIN REHABILITATION
    Office of Research and Developemnt
    Water Supply and Water Resources Division

-------
TESTING AND PERFORMANCE EVALUATION OF AN INNOVATIVE INTERNAL PIPE
         SEALING SYSTEM FOR WASTEWATER MAIN REHABILITATION
                                      by
             John C. Matthews, Ph.D., Wendy Condit, P.E., and Ryan Stowe
                            Battelle Memorial Institute

                              Shaurav Alam, Ph.D.
                    Louisiana Tech Trenchless Technology Center
                          EPA Contract No. EP-C-11-038
                               Task Order No. 01
                        Ariamalar Selvakumar, Ph.D., P.E.
                              Task Order Manager
                       U.S. Environmental Protection Agency
                  National Risk Management Research Laboratory
                     Water Supply and Water Resources Division
                       Urban Watershed Management Branch
                        2890 Woodbridge Avenue (MS-104)
                                Edison, NJ 08837
                  National Risk Management Research Laboratory
                        Office of Research and Development
                       U.S. Environmental Protection Agency
                              Cincinnati, Ohio 45268
                                 January 2016

-------
                                       DISCLAIMER
The U.S. Environmental Protection Agency (EPA), through its Office of Research and Development,
funded and managed the research described herein under Task Order (TO) 01 of Contract No. EP-C-11 -
038 to Battelle.  It has been subjected to the Agency's peer and administrative review and has been
approved for publication. Any opinions expressed in this report are those of the authors and do not
necessarily reflect the views of the Agency, therefore, no official endorsement should be inferred.  Any
mention of trade names or commercial products does not constitute endorsement or recommendation for
use.  The quality of secondary data referenced in this document was not independently evaluated by EPA
and Battelle.

-------
                                          ABSTRACT
Many utilities are seeking emerging and innovative rehabilitation technologies to extend the service life
of their infrastructure systems. This report describes the testing and performance evaluation of an internal
pipe sealing system, which provides a permanent physical seal for the spot rehabilitation of cracks, leaks,
corrosion, and other defects. The system tested was Pipe-Seal-Fix® from Pipe-Robo-Tec USA. The Pipe-
Seal-Fix® system consists of a stainless steel sleeve and an ethylene propylene diene monomer (EPDM)
rubber seal or gasket that span over a damaged spot in a sewer main. The sleeve and seal are installed
together via a robotic closed circuit television (CCTV) camera and packer arrangement.  The Pipe-Seal-
Fix® system is designed for use in storm and sanitary sewer pipe rehabilitation applications in diameter
ranges of 8 to 24 inches (200 to 610 mm). Field demonstrations were attempted on a 10-inch sewer main
in Santa Fe, Texas and an 8-inch sewer main in Baltimore, Maryland. Both locations had previously been
lined with cured-in-place pipe (CIPP), but had significant defects allowing infiltration or exfiltration of
the  sewer flow.  The system could not be installed at the Santa Fe, Texas location due to sagging and the
ovality of the defective CIPP liner that prevented the system from reaching the repair site.  The repair
sleeve  was successfully installed in Baltimore, Maryland. However, the repair was performed manually
due to  access issues that prevented the installation packer from moving through the pipe to the repair site.
The post-lining  inspection via CCTV showed the repaired section to be sealed, with no signs of
exfiltration. The system was also tested via external hydraulic testing in the laboratory on three 8-inch
steel pipes.  The laboratory testing showed the seals were leak free for 2.5 hours above 15 pounds per
square inch (psi), which is approximately twice the external hydraulic design pressure of 7.25 psi (0.5
bar). The material cost for the Baltimore, Maryland spot repair of an 8-inch sewer main was $756 and the
installation occurred over approximately three hours. The project had a negligible carbon footprint as the
equipment required for the installation was minimal.  The technology shows promise as a low-cost and
rapid trenchless repair approach.  Access requirements should be assessed based upon site-specific
conditions to ensure feasibility of the robotic-assisted installation, especially in previously  lined pipes.

-------
                                   ACKNOWLEDGMENTS
This report has been prepared with input from the research team, which includes Battelle and the
Trenchless Technology Center (TTC) at Louisiana Tech University, and Dr. Ray Sterling. The technical
direction and coordination for this project were provided by Dr. Ariamalar Selvakumar of the Urban
Watershed Management Branch. The project team would like to acknowledge several key contributors to
this report in addition to the authors listed on the title page. The demonstration would not have been
possible without the cooperation of the City of Baltimore. Cooperation from Pipe-Robo-Tec USA and
others was crucial for this project and the authors would like to thank Luke Keenan and others from Pipe-
Robo-Tec USA and the Savin Engineers field crew for their assistance on this project. Key contributors
from the TTC included Ben Curry, Lane Elien, and Urso Adrian Campos for the experimental  work.
                                              in

-------
                                   EXECUTIVE SUMMARY
Many utilities are seeking emerging and innovative rehabilitation technologies to extend the service life
of their infrastructure systems.  However, information on new technologies is not always readily available
and not easy to obtain.  To help to provide this information, the U.S. Environmental Protection Agency
(EPA) developed an innovative technology demonstration program to evaluate technologies that have the
potential to reduce costs and increase the effectiveness of the operation, maintenance, and renewal of
aging water distribution and wastewater collection systems. The intent of this program is to make the
technologies' capabilities better known to the water and wastewater industries.

This report describes the testing and performance evaluation of an internal pipe sealing system, which
provides a permanent physical  seal  for the spot rehabilitation of cracks, leaks, corrosion, and other
defects. The system tested was Pipe-Seal-Fix® from Pipe-Robo-Tec USA.  This method is most
applicable when only one or two defective areas require repair, while the remaining host pipe is in
acceptable condition. The  Pipe-Seal-Fix® system consists of a stainless steel sleeve and an ethylene
propylene diene monomer  (EPDM) rubber seal or gasket that span over a damaged spot in a sewer main.
The sleeve and seal are installed together via a robotic closed circuit television (CCTV) camera and
packer arrangement. The packer inflation forces the seal against the pipe wall and permanently locks the
sleeve in place.  The Pipe-Seal-Fix® system is designed for use in storm and sanitary sewer pipe
rehabilitation applications in diameter ranges of 8 to 24 inches (200 to 610 mm). Field demonstrations
were attempted on a 10-inch sewer  main in Santa Fe, Texas and an 8-inch sewer main in Baltimore,
Maryland.  Both locations had previously been lined with cured-in-place pipe (CIPP), but had significant
defects allowing infiltration or  exfiltration of the sewer flow. The system was also tested in the laboratory
on three 8-inch steel pipes to determine the maximum external water pressure it could withstand.

The system could not be installed at the Santa Fe, Texas site due to sagging and the ovality of the
defective CIPP liner. The system was successfully installed manually in the field at the Baltimore,
Maryland site, but the robotic installation feature was not able to be fully demonstrated.  The challenging
pipe conditions leading to a manual installation included the pipe entering the manhole at eye level (i.e., a
drop connection), plus the manhole was not a standard 48-inch diameter (i.e.,  it was only 28-inches in
diameter). Despite these conditions, the post-lining inspection via CCTV showed the spot repaired
section to be sealed, with no signs of exfiltration.  These installations can only be confirmed visually, so
laboratory testing was also conducted.  The laboratory testing of three 8-inch steel pipes  showed the seals
were leak free for 2.5 hours above 15 pounds per square inch (psi), which is approximately twice the
external hydraulic design pressure of 7.25 psi (0.5 bar).

In terms of quality assurance/quality control (QA/QC) procedures, two post-installation checks were
conducted including confirmation that the required inflation pressure was used on the packer and then a
visual check with the CCTV camera of the overall position and fit.  It is recommended that additional
QA/QC measures be developed to ensure that the seal is properly installed.  It would be advantageous to
develop a field test for QA/QC to ensure that each seal is set and water tight.

The material cost for the Baltimore  installation was $756 for the spot repair of an 8-inch sewer main.  The
installation was completed in approximately three hours from site preparation to final CCTV inspection.
The project had a negligible carbon footprint as the equipment required for the installation was minimal.
The technology shows promise as a low-cost and rapid trenchless repair approach.  However, access
requirements should be assessed based upon site-specific conditions to ensure feasibility of the robotic-
assisted installation, especially in previously lined pipes. If possible, the initial CCTV inspection should
be completed with the packer assembly and/or a simulated pig of similar dimensions to ensure that bends
and offsets can be successfully navigated.
                                               IV

-------
                                TABLE OF CONTENTS
DISCLAIMER	i
ABSTRACT	ii
ACKNOWLEDGMENTS	iii
EXECUTIVE SUMMARY	iv
TABLE OF CONTENTS	v
ABBREVIATIONS AND ACRONYMS	vii

Section 1.0: INTRODUCTION	1
       1.1    Project Background	1
       1.2    Project Objectives	2
       1.3    Report Outline	2

Section 2.0: DEMONSTRATION APPROACH	3
      2.1    General Approach	3
      2.2    Technology Selection Approach	5
             2.2.1   Overview of Innovative Sewer Main Repair Approaches	6
             2.2.2   Overview of Internal Pipe Sealing System	6
             2.2.3   Design of Internal Pipe Sealing System	9
             2.2.4   Installation of Internal Pipe Sealing System	9
             2.2.5   QA/QC of Internal Pipe Sealing System	10
      2.3    Site Selection Approach	11
             2.3.1   Site Selection Factors	11
             2.3.2   Site Descriptions	12

Section 3.0: INTERNAL SEALING DEMONSTRATION AND TESTING	13
      3.1    Site 1: Santa Fe, Texas	13
      3.2    Site 2: Baltimore, Maryland	15

Section 4.0: DEMONSTRATION RESULTS	19
      4.1    Technology Maturity	19
      4.2    Technology Feasibility	19
      4.3    Technology Complexity	19
      4.4    Technology Performance	19
      4.5    Technology Cost	24
      4.6    Technology Environmental Impact	25

Section 5.0: CONCLUSIONS  AND RECOMMENDATIONS	27

Section 6.0: REFERENCES	29

-------
                                          FIGURES

Figure 2-1. Stainless Steel Sleeve and Rubber Gasket	7
Figure 2-2. Schematic of Overall Locking Mechanism	7
Figure 2-3. Detailed Photos of the Teeth, Locking Mechanism, and Hold-Down Plate	8
Figure 2-4. Installation via a Robotic CCTV Camera and Installation Packer Assembly	9
Figure 2-5. CIPP Liner Failure at Santa Fe, Texas Site	12
Figure 3-1. Site Preparation and CCTV Inspection	13
Figure 3-2. Seal Preparation	13
Figure 3-3. Pipe-Seal-Fix® Placed on the Packer	14
Figure 3-4. Robotic Camera	14
Figure 3-5. Upstream Manhole	15
Figure 3-6. Initial CCTV Inspection	16
Figure 3-7. Downstream Manhole	17
Figure 3-8. Manual Inflation	17
Figure 3-9. Final CCTV Inspection of Seal Placement	18
Figure 4-1. Measurement Orientation (left) and Measurement (right)	20
Figure 4-2. Pipe-Seal-Fix® Sleeve with and without Elastomer Seal and Bladder System	20
Figure 4-3. Positioning of the Seal on the Sleeve (left) and Sleeve on the Bladder (right)	21
Figure 4-4. Positioning of the Bladder System Inside the Tube (left) and Rubber Seal from the Outside
           Prior to Inflation (right)	21
Figure 4-5. Finished Sealing System from Inside (left) and from Outside (right)	21
Figure 4-6. Test Setup - Positioning the Sample and Tube Inside a Larger Diameter Pipe	22
Figure 4-7. Testing of the Specimen	22
Figure 4-8. Sample Prepared for the Capacity Test	22
Figure 4-9. Change of Pressure Over Time during External Hydraulic Testing	23
Figure 4-10. Burst Pressure of the Specimen #2	24
Figure 4-11. Capacity Testing of the Specimen (left) and Seal Broke at around 65 psi (right)	24
Figure 4-12. Inputs for e-Calc forthe Pipe Sealing Project in Baltimore	25
                                           TABLES

Table 2-1. Framework of Technology Metrics to be Evaluated	4
Table 2-2. Selected Innovative Rehabilitation Technologies	5
Table 2-3. Material Properties of Pipe-Seal-Fix®	6
Table 4-1. Measurement of the Annular Gaps	20
Table 4-2. Results from e-Calc forthe Pipe Sealing Project	26
Table 5-1. Technology Evaluation Metrics Conclusion	27
                                              VI

-------
                            ABBREVIATIONS AND ACRONYMS
CCTV        closed circuit television
CIP           cast iron pipe
CIPP         cured-in-place pipe

DIP           ductile iron pipe
DIN          Deutsches Institut Fur Normung (German National Standards)

EPA          United States Environmental Protection Agency
EPDM        ethylene propylene diene monomer

GFRP         glass fiber reinforced plastic

HOPE        high density polyethylene

NRMRL      National Risk Management Research Laboratory

psi            pounds per square inch
PVC          polyvinyl chloride

QA/QC       quality assurance/quality control
QAPP        Quality Assurance Project Plan

RCP          reinforced concrete pipe

SOT          state-of-technology
STREAMS    Scientific, Technical, Research, Engineering, and Modeling Support

TO           task order
TTC          Trenchless Technology Center

VCP          vitrified clay pipe
                                             vn

-------
                                 Section 1.0: INTRODUCTION
1.1        Project Background

Many utilities are seeking emerging and innovative rehabilitation technologies to extend the service life
of their infrastructure systems.  However, information on new technologies is not always readily available
and easy to obtain. To help to provide this information, research is being conducted as part of the U.S.
Environmental Protection Agency's (EPA's) Innovation and Research for Water Infrastructure for the
21st Century research program to evaluate promising innovative technologies that can reduce costs and
improve the effectiveness of the operation, maintenance, and renewal of aging drinking water distribution
and wastewater collection systems. This research includes field demonstration studies of emerging and
innovative rehabilitation technologies, which is intended to make  the capability of these technologies
better known to the water and wastewater industries.  The specific technology metrics evaluated under
this program include technology maturity, feasibility, complexity, performance, cost, and environmental
impact.

Several emerging and innovative technologies were identified by  EPA based upon industry experience
and extensive state-of-technology (SOT) reports (EPA, 2010a; 201 Ob; 2013). A successful demonstration
project provides substantial value to utilities, manufacturers, technology developers, consultants, service
providers, and contractors.  The benefits of a technology demonstration program to these various groups
are summarized below:

  Benefits to Utilities
    •  Reduced risk of experimenting with new technologies and new materials on their own
    •  Increased awareness of innovative and emerging technologies and their capabilities
    •  Assistance in setting up strategic and tactical rehabilitation plans
    •  Understanding of technology environmental impact and social cost
    •  Identification of design and quality assurance/quality control (QA/QC) issues

  Benefits to Manufacturers/Technology Developers
    •  Opportunity to advance technology development and commercialization
    •  Opportunity to accelerate the adoption of new technologies in the U.S.
    •  Opportunity to better understand the needs of utilities

  Benefits to Consultants
    •  Opportunity to compare performance and cost of similar products in a consistent manner
    •  Access  to standards and specifications for new technologies
    •  Education of best practices on pre- and post-installation procedures and testing

  Benefits to Contractors and Service Providers
    •  Identification of successfully implemented QA/QC protocols
    •  Identification of successfully implemented installation procedures including surface preparations
    •  Understanding of regulations related to the use of new renewal technologies

This report provides an assessment of the effectiveness, expected  range of applications, and cost of the
demonstrated technology to assist utilities in better decision-making on whether rehabilitation or
replacement is more cost-effective in selecting rehabilitation technologies for use. The field
demonstration described in this report resulted in the installation of an internal pipe sealing system for
spot repair of an 8-inch wastewater collection main that had been  previously lined with cured-in-place

-------
pipe (CIPP) in Baltimore, Maryland. The system was also pressure tested in the laboratory on three
unlined, steel pipe test segments and all three held well above 15 pounds per square inch (psi).  The
activities involved with sealing system installation, which included pipe inspection, installation activities,
and post-installation activities such as visual inspection and laboratory testing, are presented in this report.
This report conducts a preliminary evaluation based upon both field and laboratory demonstration results.

1.2        Project Objectives

The project objectives are to:

    •  Evaluate, under laboratory and field conditions, the performance and cost of an innovative
       internal pipe sealing system used for spot repair of wastewater collection mains.

    •  Document the results of the demonstration and testing, and provide recommendations related to
       product installation and QA/QC measures.

This research was conducted for the EPA National Risk Management Research Laboratory (NRMRL)
under Task Order (TO) No. 01 titled Field Demonstration and Retrospective Evaluation of Rehabilitation
Technologies for Wastewater Collection and Water Distribution Systems of the Scientific, Technical,
Research, Engineering, and Modeling Support II (STREAMS II) Contract No. EP-C-11-038. The report
describes data collection, analyses, and project documentation in accordance with EPA NRMRL's
Quality Assurance Project Plan (QAPP)  Requirements for Measured Projects (EPA, 2008) and the
project-specific QAPPs (Battelle, 2012)  and QAPP Amendment (Battelle, 2015).

1.3        Report Outline

The report is organized into the following sections:

    •  Section 2.0 Demonstration Approach. Discussion of the demonstration program approach
       including an overview of the innovative rehabilitation technology.

    •  Section 3.0 Internal Sealing Demonstration and Testing.  Documentation of the field
       demonstration including site preparation, installation, and QA/QC procedures, as well as
       laboratory testing.

    •  Section 4.0 Demonstration Results.  Discussion of the demonstration results and assessment of
       the technology based on comparison with the outlined evaluation metrics.

    •  Section 5.0 Conclusions  and Recommendations.  Summary of the demonstration including
       effectiveness of the demonstrated technology and recommendations for areas needing further
       examination.

-------
                         Section 2.0: DEMONSTRATION APPROACH
This section outlines the overall approach to the field demonstration and provides an overview of the
innovative rehabilitation technology and site selection for this task.

2.1        General Approach

The demonstration of innovative technologies requires clear and repeatable testing criteria if the
technologies are to be understood and accepted. A protocol was developed to provide a consistent
approach and a guide for conducting field demonstrations in a manner that encourages acceptance of the
outcomes and results by wastewater utilities. The demonstration protocol addressed issues involved in
gaining the approval for the use of innovative technologies by:

    •  Providing for independent verification of the claims of technology developers
    •  Sharing information about new technologies among peer user groups
    •  Supporting utilities and technology developers in bringing new products to a geographically and
       organizationally diverse market.

A QAPP was developed to outline the approach to plan, coordinate, and execute the field demonstration
protocol with the specific objectives of evaluating, under field and laboratory conditions, the performance
and cost of an innovative internal pipe sealing system for wastewater main rehabilitation.

The QAPP described the overall objectives and approach to the  EPA's field demonstration program, the
technology and site selection factors considered, and the features, capabilities, and limitations of the
selected technology, which are summarized below (Battelle, 2012).  The demonstration protocol was
executed by completing the following steps:

    •  Prepared and obtained EPA approval for the QAPP;

    •  Gathered relevant data for demonstration opportunities meeting the selection criteria;

    •  Secured a commitment from the technology developer and contractor to use one of their projects
       as the demonstration study;

    •  Documented and conducted the field demonstration as outlined in the demonstration protocol;

    •  Processed and analyzed the results of the field demonstration and laboratory testing; and

    •  Prepared a report and peer reviewed article  summarizing the results.


This demonstration report not only records the use of the internal pipe sealing system technology, but also
provides a documented case study of the technology selection process, QA/QC procedures, and the
preparation for life-cycle management of the asset.  In performing the field demonstration, the technical
and QA/QC procedures specified in the QAPP were followed unless otherwise stated.  Special aspects of
the EPA demonstration program which were aimed at adding value to the wastewater rehabilitation
industry are described below.

    •  Consistent Design Methodology. An important role of this task is to identify design parameters
       and specifications for the selected technologies and to document the application of a consistent
       design methodology based on the vendor recommendations or industry defined standards.

-------
  QA/QC Procedures.  The success of a rehabilitation project depends largely on proper
  installation controls and post-installation inspection and assessment. The level of qualification
  testing and QA requirements typically vary by technology without a clear quality standard. This
  task provided an opportunity to examine current QA practices and identify areas for
  improvement. For technologies lacking an industry quality standard, QA/QC procedures
  recommended by the vendor and utility should be reviewed and adopted (as appropriate).

  Technology Range of Applications.  The demonstration provides an assessment of the short-
  term effectiveness and cost of the selected technologies in comparison with the respective vendor
  specifications and identifies conditions under which each technology can be best applied.  This
  effort also provides suggestions on necessary improvements for the technology itself, the
  installation procedures, and QA/QC procedures. Several metrics that can be used to evaluate and
  document rehabilitation technology application, performance,  and cost are identified (Table 2-1).

  Life-Cycle Performance. Long-term performance data for rehabilitation systems is needed.
  These data will enable decision makers to make better cost-benefit decisions.  This report will
  assist utilities in developing life-cycle plans for the ongoing evaluation of rehabilitation
  technology performance.
              Table 2-1. Framework of Technology Metrics to be Evaluated
                              Technology Maturity Metrics
Maturity is innovative (recently commercialized), emerging (not widely used in the U.S.), or conventional.
Availability of supporting performance data and patent citation (if applicable).
Comments and feedback from utility owners and consultants with experience from previous pilot studies.
                               Technology Feasibility Metrics
Applicability of the technology in meeting the rehabilitation requirements.
Suitability of the technology to the operating conditions of the host pipe.
Consideration of failure modes and documentation of design procedures.
                              Technology Complexity Metrics
Adaptability to and widespread benefit for small- to medium-sized utilities.
Level of training required, pre- and post-installation requirements, and maintenance requirements.
Time and labor requirements for the overall rehabilitation project.
Evaluation of the installation process, procedures, and problems encountered.
Documentation of the efficiency of the reinstatement of laterals, etc.
                             Technology Performance Metrics
Evaluation of manufacturer-stated performance versus actual performance.
Expected visual appearance and geometric uniformity after installation.
Ability to achieve design specifications.
Ability to withstand typical sewer cleaning operations.
                                 Technology Cost Metrics
Document costs including design, capital, operation and maintenance, traffic and surface footprint, and
calculate a unit cost.
Estimate an average level of social disruption (although social cost calculation is beyond the project scope).
                       Technology Environmental and Social Metrics
Assess utilization of chemicals or waste byproducts that have an unintended impact on the environment.
Assess quantity of waste byproducts produced (e.g., wastewater volume, soil requiring off-site disposal).
Evaluate the overall "carbon footprint" of the technology compared to open cut.

-------
2.2
Technology Selection Approach
Several emerging and innovative technologies were identified by EPA based upon industry experience
and extensive SOT reports (EPA, 2010a; 2010b; 2013). From these resources, the Battelle team identified
innovative technologies that have the potential to be demonstrated and that would provide a benefit to
advance the SOT (see Table 2-2). This report focuses on the field demonstration of one of these
technologies, Pipe-Seal-Fix®, which is an innovative robotic internal pipe sealing system for wastewater
pipes.

                   Table 2-2. Selected Innovative Rehabilitation Technologies
Technology
(Vendor)
Technology Description
Rationale for
Demonstration
Wastewater Rehabilitation
3S Panels
(National Liner)
Geo Spray™
(Milliken)
Pipe-Seal-Fix®
(Pipe-Robo-Tec USA )
Composite pipe consists of 3S
segmental panels, host pipe, and
3 S grout. Panels are made of
transparent polyvinyl chloride,
allowing visual confirmation of
uniform grouting.
Fiber reinforced geopolymer
mortar designed for spray
applications. Designed to adhere
to the surface to build thickness.
Internal pipe sealing system
comprised of a stainless steel
sleeve with a unique locking
system and rubber gasket, which
are described in Section 2.2.2.
Circular or noncircular; visual
confirmation of uniform
grouting; used where bypassing
is not feasible, large diameter.
Fast return to service; high
durability; near-zero porosity;
high resistance to acid; green
material.
Innovative internal pipe sealing
system for spot repair. Includes
robotic installation feature,
which is described in Section
2.2.4.
Water Main Rehabilitation
Melt-in-place pipe
(Aqualiner)
Automated Leak Repair
(Curapipe)
Pipe Armor
(Quest Inspar)
Thin thermoplastic polymer
composite liner for 6 inch to 12
inch diameters. Glass fiber
reinforced polypropylene and a
woven tube. Heated with a pig
that melts the thermoplastic.
Pig train contains curing
substances under pressure that
plug leaks as the pigs travel
down the main. The substances
harden to plug leaks.
High build polyurea lining
material that can be spray
applied. Fast curing can
potentially allow for fast return
to service.
Performs as a Class IV liner
capable of independently
handling internal pressure and
external loads.
Innovative technique for leak
repair; can be deployed through
hydrants.
Can be applied to a Class IV
lining level capable of
independently handling internal
pressure and external loads.
The technology selection criteria identified by the project team follow the general guidelines below:

    •   Maturity.  Novel and emerging technologies that are commercially available are desired.
       Technologies should be truly novel and more than an incremental improvement over conventional
       methods (EPA, 2009).

-------
    •  Feasibility. The potential of the proposed technology as a compliance strategy for the site-
       specific conditions should be identified. The nature of the problem faced in the pipe will
       ultimately drive technology selection.
    •  Complexity. Technology adaptability to and widespread benefit for small- to medium-sized
       utilities is desired (EPA, 2009). The complexity refers to the level of training required for the
       installer, pre- and post-installation requirements, and maintenance requirements.
    •  Performance.  This criterion is evaluated based on the capabilities and limitations of the
       technology and investigation of potential advances over  existing and competing technologies.
       Vendor performance claims will be compared to actual performance in the field.
    •  Cost.  The direct installation cost on a per-unit basis will be provided. Additional costs are site-
       specific and may include pre-installation setup, pre-and post-installation inspection, cleaning,
       traffic control, and sewage bypass.  Warranties or guarantees on performance should be provided.
    •  Environmental.  Technologies may use chemicals or produce waste byproducts  that have an
       unintended impact on the environment or water quality.  Technologies that reduce the overall
       carbon footprint of the project compared to open cut are  desired (EPA, 2009).

2.2.1      Overview of Innovative Sewer Main Repair Approaches.  Sewer main repairs are carried
out to restore the sewer to an operating condition and to deal with localized deterioration. Typically, spot
repairs will be made if there are only one or two sections requiring repair within a mainline segment,
otherwise it may be advisable to replace or re line the entire segment from manhole to manhole.  Open cut
repair is the conventional approach used for spot repair of sewer mains where it is feasible and cost-
effective. Other repair approaches include external repair clamps and joint sleeves, cured-in-place pipe
(CIPP) spot repair with short liners, and internal joint seals and mechanical spot repairs (EPA, 201 Ob).
Battelle received an agreement from Pipe-Robo-Tec USA, which developed Pipe-Seal-Fix® (see Table 2-
2), to participate in the EPA demonstration opportunity under this project. This repair technology, which
is designed for gravity sanitary and storm sewers, is  described below.

2.2.2      Overview of Internal Pipe Sealing System.  Pipe-Robo-Tec USA's Pipe-Seal-Fix® system
is composed of a stainless steel sleeve and an ethylene propylene diene monomer (EPDM) rubber seal or
gasket that  span over a damaged spot in a sewer main (see Figure 2-1). The Pipe-Seal-Fix® system is
designed for use in storm and sanitary sewer pipe repair applications in diameter ranges of 8 to 24 inches
(200 to 610 mm). The physical properties for Pipe-Seal-Fix® are shown in Table 2-3. The materials used
(i.e., stainless steel and rubber) have been verified to be corrosion resistant under sewer conditions (see
Section 2.2.5). The stainless steel  sleeve and elastomer seal are installed via a robotic closed circuit
television (CCTV) camera and packer arrangement as described  in Section 2.2.4. These seals can be
installed quickly in low flow conditions, eliminating the need to  bypass pump. The seals are also
relatively easy to install and do not require highly specialized knowledge or equipment (Pipe-Robo-Tec,
2015).

                         Table 2-3. Material Properties of Pipe-Seal-Fix®
Property
External Design Pressure
Temperature Range
Value
7.25 psi (0.5 bar)
Stability up to 266°F

-------
                       Figure 2-1. Stainless Steel Sleeve and Rubber Gasket

The AISI 316Lor316Ti stainless steel sleeve is used for its resistance to sewage conditions (see Section
2.2.5). The corrosion-resistant sleeve has a unique locking system that cannot unlock once expanded into
place inside the pipe (see Figure 2-2 for an illustration and photo of the overall locking system).  Pipe-
Seal-Fix® does not require any curing; instead the packer used to expand the sleeve in place just needs to
be pressurized to 40 psi to ensure the locks are fully expanded.  The locking mechanism is described here
briefly and in more detail in the Pipe-Seal-Fix® manual for additional information. There are two rows of
teeth punched into each sleeve, which provide for two locks to hold the repair in place. The teeth help to
guide the pinions (i.e., gears) of the locking mechanism.  Detailed photos of the teeth, locking
mechanism, and hold-down plate are shown in Figure 2-3. The  locking mechanism consists of a pinion
for guiding and a spring-loaded pinion for locking. The interlocking pinions are arranged so that the
sleeve can only move in one direction for a forward expansion.  After expansion of the seal, the spring
element loses its function.  The hold-down plate  is there to uniformly press the expanding sleeve sheet
and fixes the pinons in place (Pipe-Robo-Tec, 2015).  The locking mechanism is made of titanium which
had a high resistance to corrosion. The Pipe-Seal-Fix® system has been tested for corrosion resistance
and high pressure flushing resistance as summarized in Section  2.2.5 below.
                                   LOCK
                                   (connected with
                                   the stainless steel
                                   sleeve behind)
                                   SERRATED LINE
                                   (In front of the pipe section)
                                                                                         Figure
                                                                                           2-2.
              Schematic of Overall Locking Mechanism (Courtesy of Pipe-Robo-Tec)

-------
Figure 2-3. Detailed Photos of the Teeth, Locking Mechanism, and Hold-Down Plate
               (From top to bottom; Courtesy of Pipe-Robo-Tec)

-------
Main Benefits Claimed
    •   Addresses longitudinal and other cracks

    •   Reinforces pipe joints

    •   Installed in non-accessible pipes

    •   Adapts to nearly all pipe materials including reinforced concrete pipe (RCP), vitrified clay pipe
       (VCP), ductile iron pipe (DIP), cast iron pipe (CIP), glass fiber reinforced plastic (GFRP),
       polyvinyl chloride (PVC), and high density polyethylene (HDPE)

    •   Installed quickly with minimal equipment

    •   Trenchless process with minimal access requirements

Main Limitations Cited
    •   Bends and offsets above  10% can cause difficulty as the sleeves are rigid

    •   Manholes must be large enough (> 30-inch diameter) to insert camera and packer equipment
       (typical manholes are 48-inches in diameter)

    •   Temporary stoppage of flow or bypass may be required in high flow pipes

    •   Proper access within the pipe is required and obstructions must be removed such as root
       penetrations

    •   Temporary stoppage of flow or bypass may be required in high flow pipes

    •   Not applicable to corrugated pipe and appropriate precautions must be taken to avoid cracking
       VCP.


2.2.3       Design of Internal Pipe Sealing System. There is no design standard for this technology.
The seals come in standard diameter ranges depending on the internal diameter of the host pipe to be
repaired.

2.2.4       Installation of Internal Pipe Sealing System.  The Pipe-Seal-Fix® system is installed via a
robotic CCTV camera and installation packer assembly as shown in Figure 2-4. The robotic CCTV
camera unit is outfitted with an adapter that connects it to a coupling rod that both moves and supplies
compressed air to the installation packer unit.
   Figure 2-4. Installation via a Robotic CCTV Camera (Left) and Installation Packer Assembly
                              (Right) (Courtesy of Pipe-Robo-Tec)

-------
The following is a brief overview of the major steps involved in the application of the internal pipe seal:

    •   Conduct a pre-installation CCTV to assess that pipe conditions and access requirements are met
    •   Remove any obstructions from the host pipe
    •   Block and/or divert upstream flow in pipe (low flow allowable)
    •   Inspect stainless  steel sleeve for damage and remove all adhesive strips
    •   Apply talcum powder to the inside of the EPDM rubber seal and slide seal over the sleeve
    •   Cut rubber seal on each end with  a sharp knife so the seal is 0.2 to 0.4 inches shorter than the
       sleeve
    •   Adhere EPDM rubber seal to stainless steel sleeve using superglue applied to a maximum of four
       points at each end
    •   Attach the installation packer to the robotic CCTV camera via a coupling rod
    •   Position the Pipe-Seal-Fix®  sleeve with the EPDM seal onto the installation packer
    •   Rotate the sleeve on the installation packer so that the locking mechanism is at 12 o'clock and
       open the air valve just enough to hold the sleeve in position on the packer
    •   Close the air valve and disconnect the coupling rod from the packer
    •   Move the packer to the pipe entrance and then reattach the coupling rod and open the air valve.  If
       the sleeve is flanged, the flanging must be installed in the direction opposite of the flow
    •   Use the robotic CCTV camera to  push the installation packer to the damaged section of the pipe
    •   The sleeve and EPDM rubber seal should be positioned in the center of the damage
    •   Build up pressure in the packer to the prescribed final contact pressure (40 psi for 8-inch sleeve)
    •   Inspect installation using CCTV to determine if a re-tightening of the sleeve is needed
    •   If the post-installation CCTV inspection reveals a misfit sleeve  or other issues, the internal pipe
       sealing system can be removed, but it will be permanently destroyed in the process. The locking
       mechanism must be cut in order to remove the sleeve.  This is accomplished with a milling robot
       equipped with a  common flex disc for metals. Each lock is cut, which allows the EPDM rubber
       seal to contract and become loose so that the entire  sealing system can be removed from the pipe
       (Pipe-Robo-Tec, 2015).

2.2.5       QA/QC of Internal Pipe Sealing System.  The Pipe-Seal-Fix® system  has been subjected to
several laboratory-based  QA/QC testing procedures as summarized below. The 50-year estimated design
life is based upon the stainless steel  and EPDM material testing.  These  tests are based on ASTM  and
German National Standards (or Deutsches Institut Fur Normung  [DIN]) and include:

    •   Testing the material identity of the elastomer sealants according to ASTM D5576;
    •   Proving the steel quality as to  its resistance to sewage water according to DIN 1986-3;
    •   Testing high pressure flushing resistance according to DIN 19523;
    •   Testing the water tightness for external pressure of 7.25 psi (0.5 bar);
                                               10

-------
    •   Testing the water tightness under heavy load, deformation and bending according to DIN 4060

    •   Drinking water test according to DIN DVGW W270; and

    •   Elastomer directive of the German Federal Environment Agency (Pipe-Robo-Tec, 2015).

The field QA/QC regimen is less involved. Only a few visual QA/QC procedures are recommended by
the manufacturer. First, the seal should be centered on the defect, which is confirmed visually with the
CCTV camera. After full pressure has been applied (40 psi is recommend for an 8-inch sleeve), the
sleeve is inspected via CCTV to ensure the locks have been expanded. However, this procedure is not
optimal because the locks may not be able to open as wide on each end and it is difficult to see visually
whether or not the sleeve can expand any more. This is why the minimum expansion pressure must be
met. The main conclusion of this study is the need to improve field QA/QC procedures to ensure that a
good seal is obtained, especially for CIPP lined pipes, pipes with significant ovality, and/or pipes with
rough surfaces. In addition to the visual examination, it would be advisable to develop a means to inspect
the seals to determine if there is a good fit (especially at either end of the seal).  In addition, the ability of
the packer to force the sleeve outward to make a tight seal between the sleeve and CIPP liner or between
CIPP liner and pipe wall may need to be further studied. This would involve tests on various types of
CIPP with various types of defects that are beyond the scope of this preliminary field demonstration.

2.3        Site Selection Approach

To ensure that the field demonstration results are acceptable and useful to the user community, the field
demonstration site and the condition of the selected test pipe had to be representative of typical
applications for the internal seals. Therefore, the operational conditions (e.g., pipe type, structural
integrity, etc.) and environmental conditions (i.e., subsurface conditions) of potential host sites had to be
appropriate for the technology. Another important consideration in site selection was the wastewater
utilities' willingness to participate in the study.

2.3.1      Site Selection Factors.  Site selection was largely dependent on the utilities' rehabilitation
needs, the availability of time and resources to contribute to the study, and  a strong motivation to advance
the state of emerging and innovative technologies. The following factors were considered in the site
selection process for the demonstration program:

    •   Utility Commitment.  Is the utility willing to use an emerging rehabilitation technology and to
        provide the  required time and resource commitments to the project?

    •   Perceived Value.  What is the number of interested utility participants? Is the technology and/or
        test pipe rehabilitation need of national-scale versus regional-scale interest?

    •   Regulatory/Stakeholder Climate.  Are local/state officials willing to work with the utility
        concerning requirements to permit use of an emerging technique?

    •   Test Pipe and Site Conditions. Are the test pipe operating and environmental site conditions
        suitable when compared to the technology's application limitations?

    •   Site Access and Safety.  Are site conditions (i.e., site access, space requirements,  etc.) suitable
        for a safe and secure field demonstration?

The site selection process for this demonstration involved employing a collaborative approach with the
technology developer and installer in an effort to identify candidate sites for the planned demonstration
study.  As part of this process, a dialogue with Pipe-Robo-Tec USA was initiated and they indicated
                                               11

-------
multiple sites being planned for projects including Santa Fe, Texas and Baltimore, Maryland. The overall
responsibilities of the technology vendor (Pipe-Robo-Tec USA) were defined as follows:

    •  Provide vendor specifications, design, and installation information for the technology
    •  Provide the technology for evaluation during the field demonstration
    •  Provide equipment and labor needed for the duration of the demonstration
    •  Provide data from the field demonstration to verify performance and cost of the technology

2.3.2      Site Descriptions.  Two field installation events of Pipe-Seal-Fix® were observed including a
10-inch pipe in the City of Santa Fe, Texas and an 8-inch VCP in Baltimore, Maryland. Both field sites
had pipes that had been previously lined with CIPP that had defects requiring repair.  The Santa Fe, Texas
pipe was located 10 ft below ground surface and had a liner failure at the joint allowing a large volume of
groundwater to infiltrate the pipe (see Figure 2-5). The Baltimore, Maryland pipe was an 8-inch VCP
lined with 290 ft of CIPP, which had a defect near a downstream manhole that was allowing sanitary flow
to exfiltrate the pipe.  A CCTV scan of the defect was not available for the Baltimore site.
        Figure 2-5. CIPP Liner Failure at Santa Fe, Texas Site (Courtesy of Pipe-Robo-Tec)
                                               12

-------
            Section 3.0: INTERNAL SEALING DEMONSTRATION AND TESTING
This section outlines the activities involved with the Pipe-Seal-Fix® field demonstrations in Santa Fe,
Texas and Baltimore, Maryland, including site preparation, technology application, and post-
demonstration field verifications.
3.1
Site 1: Santa Fe, Texas
The first demonstration took place on April 22, 2015, in Santa Fe, Texas, on a 10-inch pipe that had
previously been lined with CIPP, but ruptured at one location.  Site preparation included placing a plug to
minimize flow and the initial CCTV inspection. Battelle had one staff member in the field. Personal
protective equipment included hard hats, safety glasses, steel-toed shoes, and safety vests. After arriving
on site, the contractor placed the plug to allow for the CCTV inspection (Figure 3-1).
                       Figure 3-1. Site Preparation and CCTV Inspection

Next, dye tests were conducted to determine if infiltration was taking place from any of the nearby
laterals. No lateral defects were noted that required repair. The location of the liner failure was observed
at 223 ft from the upstream manhole. However, the contractor subsequently decided to approach the
repair of the CIPP liner defect from the downstream manhole due to jagged pieces of the failed liner near
the upstream manhole. All equipment was moved to the next downstream manhole located at the
intersection of 11th Street and Main Street. The rubber seal was slid on the metal locking sleeve and blue
hydrophilic tape was put on the Pipe-Seal-Fix® to add increased sealing ability due to a slight
misalignment in the  pipe observed by the robotic camera (Figure 3-2).
                                  Figure 3-2. Seal Preparation
                                               13

-------
Next, the vacuum truck arrived and was prepared to water jet the line. After cleaning, the camera was
lowered into the line and the liner failure was located at 223 ft upstream of the manhole.  Next, the Pipe-
Seal-Fix® was placed on the packer and secured by inflating the packer just enough to hold the seal in
place. The packer was accidentally over-inflated causing the seal to expand to a diameter larger than the
inner diameter of the pipe.  A new seal was assembled and placed on the packer (Figure 3-3).
                         Figure 3-3. Pipe-Seal-Fix® Placed on the Packer
The robotic camera was outfitted with an adapter that connected it to the push rod, which was connected
to the packer (Figure 3-4).  The packer with the seal was lowered into the manhole to be placed into the
line. Due to the size of the original wheels on the packer, the seal would not fit into the pipe. The packer
was raised up and smaller wheels were put on. The packer with the seal was then lowered back into the
manhole and still did not fit. The pipe coming into the manhole was found to be non-circular, which
prevented the seal from fitting into the pipe. The decision was made to try the repair from the next
upstream manhole.
         sam
                                  Figure 3-4. Robotic Camera
                                              14

-------
Pipe-Robo-Tec decided to try the same size (i.e., 10-inch) Pipe-Seal-Fix® without the hydrophilic tape
and to also try a size smaller (i.e., 8-inch) Pipe-Seal-Fix®. Both sizes had to be picked up from their
warehouse approximately 30 minutes from the site. Pipe-Robo-Tec returned to the site with an 8-inch
and a 10-inch Pipe-Seal-Fix®. Prior to returning, the plug was removed. The backed-up water in the line
caused the water level in the manhole to rise above the top of the pipe.  Pumping upstream of the current
location was started to lower the water level.  Once the water level was low enough to allow entry into the
manhole by personnel wearing hip waders, the 10-inch Pipe-Seal-Fix® without the hydrophilic tape was
tried first. They were unable to fit the 10-inch Pipe-Seal-Fix® into the pipe due to a slight sag in the pipe
that was not originally observed by the robotic camera.  Next, the contractor attempted to insert the 8-inch
Pipe-Seal-Fix®, but it was too small even when fully expanded. Finally, it was determined that due to the
presence of the sagging CIPP liner and the contour/geometry of the pipe that Pipe-Seal-Fix® was not able
to be used in this situation.  The leak would have to be dug up and repaired at a later date.

3.2        Site 2: Baltimore, Maryland

The second demonstration took place on May 20, 2015 in Baltimore, Maryland on an 8-inch pipe that had
previously been lined with CIPP, but failed at one location.  The defect was approximately 4 inches in
length and a 16.5-inch sleeve was installed for the repair.  Site preparation included a CCTV inspection to
locate the  defect.  Bypass pumping was not required as there was little flow in the main during
installation.  Traffic control was not required as the manholes were located in backyards. The
demonstration took place over the course of approximately three hours from initial CCTV inspection to
final CCTV check of the installation.  Battelle had one staff member in the field. Personal protective
equipment included hard hats, safety glasses, steel-toed shoes, and safety vests.

A local crew from Savin Engineers was hired by the City to  facilitate the sewer main inspection and
repair process. Pipe-Robo-Tec supplied the Pipe-Seal-Fix®  for Savin Engineers to install. The two-
person crew from Savin Engineers arrived on site at 8:00 am on May 20, 2015.  Savin began by CCTV
videoing from the upstream manhole (Figure 3-5) located in an open field in a backyard. The CCTV
showed that the flow was not significant enough to require an upstream plug  or bypass (Figure 3-6).
From this  initial location, the contractor videoed downstream 90 ft before encountering an offset in the
pipe, which did not allow inspection to the defect that was located nearly 290 ft downstream. The
contractor determined that an 8-inch camera and packer system would not fit through the offset to inspect
the pipe and install the seal, which prevented the installation of the technology from the  upstream
manhole.
                                 Figure 3-5. Upstream Manhole
                                               15

-------
                              Figure 3-6. Initial CCTV Inspection

Savin moved to the downstream manhole, which was also located in a backyard (Figure 3-7, left). The
manhole was 28 inches in diameter, which is smaller than atypical manhole (i.e., 48 inches in diameter)
and the pipe was a drop connection (i.e., the pipe was not at the manhole bench, but approximately 4 ft
above the bench). This made it difficult to launch the equipment from the surface since the installation
packer was longer than 28 inches.  Since the packer would not fit in the manhole, a tripod was set up
above the manhole, which allowed the seal to be inserted manually and installed using a typical 4-inch
plug (instead of the normal packer). This was only possible because the defect was within arm's reach of
the manhole (approximately 5 ft inside of the pipe). The vendor said this was the first time they had tried
this type of install, but they were comfortable with the idea since the plug could expand the seal similar to
the packer. There were two other small piped drop connections in the manhole, which made it difficult to
maneuver while in the manhole. One was cutout and reattached after the installation.

Since the plug expands like a balloon (round), it had to first expand on one end and then on the other end
of the seal. The plug was manually placed at the downstream end of the seal (Figure 3-7,  right) and
slowly inflated to 20 psi from the surface with a portable air compressor. Then the installer from Savin
got out of the manhole and the pressure was increased to 40 psi, which is the required pressure to expand
the seal  locks (Figure 3-8). The plug was repositioned at the upstream end of the seal and again slowly
inflated to 20 psi. Again the laborer got out of the  manhole and the pressure was increased to 43 psi,
which is beyond the required pressure to expand the seal locks and the maximum pressure recommended
for the plug being used. This entire installation took less than 30 minutes. After the seal was installed
and the plug was removed, the flow coming out of the main increased significantly as the  flow had
previously been exiting the pipe through the defect.
                                               16

-------
Figure 3-7. Downstream Manhole
  Figure 3-8. Manual Inflation
              17

-------
The CCTV camera was re-launched to inspect the installation, which was deemed successful by the City
representative and the installer based on visual evidence of stoppage of the exfiltration (Figure 3-9). A
CCTV scan of the original defect was not available for the Baltimore site for comparison. Upon
examination of the post-installation CCTV, it appeared  as if the upstream end of the seal expanded
slightly more than the downstream end. This could be due to the 3 psi difference in pressure used or a
slight change in diameter in the host pipe. The installation took approximately three hours from site
preparation through the final CCTV inspection.
                      Figure 3-9. Final CCTV Inspection of Seal Placement
                                              18

-------
                          Section 4.0:  DEMONSTRATION RESULTS
This section presents the results of the field demonstration and laboratory testing including an assessment
of the technology based on the evaluation metrics defined in Section 2.1 and Table 2-1. The specific
metrics that were used to evaluate and document the application of the Pipe-Seal-Fix® product for spot
repair are described below.

4.1         Technology Maturity

While internal pipe seals are classified as conventional, the Pipe-Seal-Fix® system is classified as
emerging in terms of maturity based on its design and use of the robotic installation method.  The product
was released on the U.S. market in January 2015 and has been applied at more than 10 sites.  However,
the results of those additional installations are not published.  Representatives from the City of Baltimore
were expected to use the product more in the future.

4.2         Technology Feasibility

The Pipe-Seal-Fix® system was designed to provide a permanent physical seal for the spot rehabilitation
of cracks, leaks, corrosion, etc. While the robotic portion of the installation process could not be fully
evaluated due to site-specific challenges, the system was found to be a viable option when remote access
to the host pipe and defect is possible. Significant offsets that limit access of the CCTV camera and
packer installation system can prevent the robotic installation of the pipe seal, but  if the packer can fit, the
installation can be completed.  Other limitations include the need for flow bypass and removal of
obstructions such as root penetrations. However, flow control was not required for the Baltimore
demonstration due to low flow conditions, but typically some form of bypass or diversion would be
required.

4.3         Technology Complexity

The internal pipe sealing process is not a complex procedure; therefore, it is conceivable that contractors
or wastewater utility personnel could be trained to install this product. A typical two-person CCTV
inspection crew could be trained to install the seals. The packer easily connects to a CCTV camera and
the seal is loaded on the packer. If for some reason the seal was to be locked in place and needed to be
removed, it would have to be cut out using a milling robot equipped with a common flex disc for metals.
In terms of QA/QC, the only checks performed are  that the required pressure is used on the packer and
then a visual check is conducted with the CCTV  camera to confirm position and fit.

4.4         Technology Performance

The technology performance was assessed in the laboratory through the  ability of the  seal to resist
external hydrostatic pressure on three test pipes consisting of 8-inch diameter, unlined steel. The tests
conducted did not simulate applying the sleeve over a defect in CIPP lined pipe, which could be a
consideration for further study. Steel mechanical tubes were cut into 12-inch by 8-inch pieces. Later, the
steel tubes were tack welded simulating  a crack or defect that spanned the circumference of the pipe. The
resulting gaps were measured around the circumference of the pipe using a Vernier Caliper (see Figure 4-
1). The measured gaps are presented in  Table 4-1.  The annular gaps in the simulated defects were 0.25,
0.32, and 0.34 inches for pipes 1, 2, and 3, respectively. The Pipe-Seal-Flex® repair was then performed
on each of the three pipes and subjected to external hydraulic testing up to 15 psi.  In addition, one
specimen was taken to failure to observe the maximum external pressure that could be withstood.
                                               19

-------
               Figure 4-1. Measurement Orientation (left) and Measurement (right)

                          Table 4-1. Measurement of the Annular Gaps
Specimen
ID
1 (Pieces
1&2)
2 (Pieces
3&4)
3 (Pieces
5&6)
Gap at Different Clock Position (inch)
1
0.19
0.30
0.31
2
0.22
0.29
0.37
3
0.27
0.29
0.34
4
0.29
0.30
0.38
5
0.29
0.32
0.29
6
0.29
0.33
0.30
7
0.23
0.33
0.31
8
0.25
0.34
0.33
9
0.27
0.34
0.40
10
0.20
0.33
0.41
11
0.23
0.33
0.31
12
0.21
0.32
0.35
Average
(inch)
0.25
0.32
0.34
Next, the annular gaps in each sample were sealed using the Pipe-Seal-Fix®.  The Pipe-Seal-Fix® is a
rolled stainless steel sleeve, containing an elastomer seal on the outer surface, which can be pressed and
spanned over a damaged spot. The sleeve is expanded using a bladder system against the inside of the
damaged pipe and locked in place (see Figure 4-2). The sleeve is manufactured in a way that the seal will
permanently interlock within the defected pipe wall (see Section 2.2.2 for an explanation of the locking
mechanism).
      Figure 4-2. Pipe-Seal-Fix® Sleeve with and without Elastomer Seal and Bladder System
                                              20

-------
The samples first were checked for any uneven sharp weld spots and removed where found using a
handheld grinder or a file. This was necessary to protect the EPDM rubber seal surrounding the stainless
steel sleeve. Next, the sleeve was outfitted with the rubber seal and positioned on the bladder system,
which was then pushed inside the steel tubes and inflated at 43 psi (see Figures 4-3 through 4-5).
      Figure 4-3. Positioning of the Seal on the Sleeve (left) and Sleeve on the Bladder (right)
   Figure 4-4. Positioning of the Bladder System Inside the Tube (left) and Rubber Seal from the
                                Outside Prior to Inflation (right)
          Figure 4-5. Finished Sealing System from Inside (left) and from Outside (right)

The tests were performed by applying external pressure on the outer surface of the samples.  First, the
samples were positioned inside a larger diameter pipe and both ends along the annular space were sealed
                                              21

-------
using circular inflatable tubes encapsulated using two steel plates (see Figures 4-6 and 4-7). Next, the
annular space was filled with water and pressurized at 5 psi, 10 psi, and 15 psi for 30 minutes (see Figure
4-7) for each of the three specimens.  In another test, one of the specimens was taken to failure.  First, the
specimen was positioned inside a steel pipe and two prepared steel washers were welded at both ends.
The sample was then pressurized to reach its highest capacity (see Figure 4-8).
     Figure 4-6. Test Setup - Positioning the Sample and Tube Inside a Larger Diameter Pipe
                               Figure 4-7. Testing of the Specimen
                        Figure 4-8. Sample Prepared for the Capacity Test

Water pressure was applied on the specimens using the main supply line.  The Pipe-Seal-Fix® specimens
were found to hold 15 psi pressure (which is twice the design pressure) for approximately 150 minutes
                                               22

-------
each with no leaks observed. For Specimens #1 and #2, minor leaks were found around the inflatable
tubes that were part of the testing apparatus, which were regulated by increasing the water supply
pressure. No leaks were observed in the inflatable tubes for the Specimen #3 trial indicating optimization
of the test setup (see the constant pressure achieved in Specimen 3 in Figure 4-9).  Next, Specimen #2
was prepared for an external hydraulic test that would take the seal to failure conditions in order to
determine the maximum external hydraulic pressure. The seal broke at approximately 65 psi, although
they were designed for 7.25 psi (see Figures 4-10 and 4-11).
                                Pressure Vs  Duration
                                                                           Specimen 1

                                                                           Specimen 2

                                                                           Specimen 3
              0
20
40
60
80
100
120
140
160
                                            Duration, Min
           Figure 4-9. Change of Pressure Over Time during External Hydraulic Testing
                                             23

-------
                               Pressure Vs Duration
60
50
Q.
.- 4°
1 BO
£
20
10
n




£L

\
I



















































Pressure, psi
                                                     8
10
12
14
                                          Duration, Min
                        Figure 4-10. Burst Pressure of the Specimen #2

    Figure 4-11. Capacity Testing of the Specimen (left) and Seal Broke at around 65 psi (right)


4.5       Technology Cost

The material cost was $756 for the 8-inch VCP spot repair in Baltimore, Maryland.  This excludes
equipment and labor. The cost to conduct a spot repair is dependent on a wide variety of variables. These
common variables include: pipe diameter, length of pipe/number of repairs, the amount of cleaning and/or
bypass required, and location of access points.  Remote sites that require equipment and personnel to
travel long distances can also impact pricing.
                                            24

-------
4.6
Technology Environmental Impact
To estimate the carbon footprint, the tool known as e-Calc was used (Sihabbudin and Ariaratnam, 2009).
The e-Calc inputs for the air compressor and CCTV truck are shown in Figure 4-12. The primary
equipment was the air compressor which was used for less than one hour. The contractor also had the
CCTV trucks mobilized for the day. Additional carbon impacts would be realized if cleaning and/or
bypass pumping are required.  However, in this field demonstration, an upstream plug or bypass pumping
was not required due to the low flow conditions in the sewer main. The e-Calc outputs are shown in
Table 4-2. The Baltimore project resulted in a carbon footprint of approximately 0.03 short tons (or 60
Ibs) of CO2 equivalents from the use of the air compressor and CCTV truck. Because open cut repair is
the conventional approach when feasible, the Pipe-Seal-Fix® footprint is compared to an equivalent open
cut repair project, which would generate 2,000 Ibs of CO2 equivalents per day based on previous studies
(EPA, 2012).
Equipment Details
Power Model Engine Useful
Name Model (hp) Year Tech, Hours
Porter Cable Air | C2002 | 1 | 2010
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
r r r r
Tier 2 _^j| 5000 |
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
3i r
| Fuel Details
Cum. Mrs Sulfur
Used Type (%)
10 | Diesel jj| 0,33
1 dl
1 dl
1 dl
1 dl
1 dl
1 dl
1 dl
1 dl
1 dl
1 dl
F ~3I~
1

jdl
dl
dl
dl
dl
dl
dl
dl
dl
dl
31
dl
Project Details |
Power
Representative Used e
Equipment Cyde /„/ 1 (hrs)
Other Construction Equipment^] ] 90 | 1
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
dl 1
~3F F
| Transport Details
Gross Vehide
Name Make Ef Weight (GVW)
Year flte.)
| CCTV Truck | Aries
1 1
2000 | 33,001-60,000 -r\\
r r 73T
1 1 1 1 dl
1 1
1 1
I |
1 dl
1 dl
73T
| Fuel Details
Mileage
W
10000 | Diesel T|[
1 dl
1 dl
1 dl
1 dl
731"
i
Sulfur
(%)
0.05 •*
dl
dl
dl
dl
dl
Project Details |
Oneway Return
Altitude t? Distance Distance
ofTnps (mi) rmi)
Low T|| 1
dl
dl
dl
dl
73F
10





10





             Figure 4-12. Inputs for e-Calc for the Pipe Sealing Project in Baltimore
                                             25

-------
             Table 4-2. Results from e-Calc for the Pipe Sealing Project
Category
Equipment
Porter Cable Air Compressor
Transport
CCTV Truck
Total
Emissions
HC
(Ibs)
0
HC
(Ibs)
0.03
0.03
CO
(Ibs)
0.01
CO
(Ibs)
0.13
0.14
NOX
(Ibs)
0.01
NOX
(Ibs)
0.45
0.46
PM
(Ibs)
0
PM
(Ibs)
0.01
0.01
CO2
(S/T)
0
CO2
(S/T)
0.03
0.03
SOx
(Ibs)
0
SOx
(Ibs)
0.02
0.02
Note: S/T is short ton, 2,000 Ibs
                                        26

-------
                   Section 5.0:  CONCLUSIONS AND RECOMMENDATIONS
The laboratory evaluation of the internal pipe sealing system verified an external pressure of 15 psi was
withstood with no leaks (approximately twice the design pressure of 7.25 psi) over 2.5 hours. The field
demonstrations of the internal pipe sealing system encountered challenges associated with the robotic
pipe installation methodology, which prevented the robotic installation aspect of the technology from
being fully observed. The issues were primarily related to access issues for the packer system in CIPP
lined pipes. In Santa Fe, Texas, the seal was not able to be installed due to access restrictions from a non-
circular pipe due to sagging and/or ovality of the CIPP liner. In Baltimore, both an offset in the CIPP-
lined host pipe downstream and the limited size of the manhole upstream resulted in the need for the seal
to be manually placed.

Table 5-1 summarizes the overall conclusions for each metric used to evaluate the technology. In terms
of QA/QC procedures, two post-installation checks are available including confirming that the required
pressure is used on the packer and then a visual check with the CCTV camera of the overall  position and
fit.  It is recommended that additional QA/QC measures be developed to ensure that the seal is properly
installed. The field QA/QC measures should be improved to be more quantitative in nature and not rely
solely upon visual observation.  It would be advantageous to develop a field test to ensure that each seal is
set and watertight. The technology shows promise as a low-cost and rapid trenchless repair  approach.
However, access requirements should be assessed  based upon site-specific conditions to ensure feasibility
of the robotic-assisted installation, especially in previously lined pipes.  It is possible that the initial
CCTV inspection should be completed with a packer or simulated pig of similar dimensions to ensure that
bends and offsets can be  successfully navigated.

                       Table 5-1. Technology Evaluation Metrics Conclusion
                                     Technology Maturity Metrics
  •   Emerging technology installed using robotic installation methodology.
  •   Corrosive resistance was not validated, but stainless steel has been proven.
  •   Some third-party data are available, but long-term testing is needed.	
                                    Technology Feasibility Metrics
     One demonstration met the owner's expectation to eliminate exfiltration from the damaged area, while the
     other installation was not successfully installed.
     The seal was manually installed in one difficult to access pipe, but it could not be installed in the other
     difficult to access pipe. In both situations, installation via the robotic CCTV camera and packer arrangement
     was not achieved due to access issues in entering the pipe and/or within the pipe itself.
     The technology may face challenges in previously lined or rehabilitated pipes (e.g., CIPP) which reduce the
     inner diameter and may cause access issues.
     Careful review of design drawings, manhole sizes, and/or pre-installation CCTV may identify access issues
     ahead of time.  However, some issues cannot be anticipated until the full CCTV and packer assembly is
     deployed in the field.	
                                   Technology Complexity Metrics
  •   May be favorable in mainline segments with only one or two defects requiring repair, which would be more
     economical than a full-length liner depending on site-specific considerations.
  •   The process is not complex; therefore, contractors or utility personnel could be trained to install this product.
                                                 27

-------
	Table 5-1. Technology Evaluation Metrics Conclusion (Continued)	
	Technology Performance Metrics	
 •   The post-lining inspection via CCTV showed the seal to be secure in place.
 •   Laboratory results showed the seals can withstand 15 psi for over two hours (approximately twice the design
     pressure of 7.25 psi).
 •   Ability to withstand typical sewer cleaning operations was not evaluated in this study, but has been
     addressed by the vendor through testing the seal's high pressure flushing resistance according to DIN 19523
 •   The durability of the individual repair versus a full length line is a factor to be considered, but has not been
     addressed in this preliminary technology evaluation. The technology is estimated to have a design life of 50
     years based on manufacturer's testing.	
	Technology Cost Metrics	
 •  The material cost was $756 for the Pipe-Seal-Fix® repair of the 8-inch VCP project. This includes cost for
    the sleeve and excludes costs for labor and equipment including site mobilization and pre- and post-
    installation CCTV inspection.
 •  Specific costs for comparison to other spot repair technologies are not readily available (EPA, 2010b).  It is
    likely to be faster and less expensive than a CIPP sleeve or carbon fiber-reinforced polymer (CFRP) wrap.
    Other mechanical joint seals are available on the market that may be comparable in terms of speed and costs.
	Technology Environmental and Social Metrics	
 •   Social disruption was minimal since traffic control was not required.
 •   An estimated 60 Ibs of CCh equivalents were emitted from on-site operations.
 •   An open cut repair project, considered the conventional repair approach where feasible, would emit
     approximately 2,000 Ibs of CCh equivalents.	
                                                  28

-------
                                  Section 6.0: REFERENCES
Battelle. 2012. Quality Assurance Project Plan for the Demonstration of GeoTree Technologies
GeoSpray™ Fiber Reinforced Geopolymer Spray Applied Mortar. October.

Battelle. 2015. Quality Assurance Project Plan Amendment for Pipe-Robo-Tec Pipe-Seal-Fix®. May.

Environmental Protection Agency (EPA). 2008. EPA NRMRL QAPP Requirements for Measurement
Projects, U.S. EPA, Office of Environmental Information, Washington, B.C.

Environmental Protection Agency (EPA). 2009. Rehabilitation ofWastewater Collection and Water
Distribution Systems: White Paper.  EPA/600/R-09/048, U.S. EPA, Office of Research and Development,
Cincinnati, OH, May, 91 pp., http://nepis.epa.gov/Adobe/PDF/P10044GX.pdf.

Environmental Protection Agency (EPA). 2010a. State of Technology Report for Force Main
Rehabilitation. EPA/600/R-10/044, U.S. EPA, Office of Research and Development, Cincinnati, OH,
Mar., 175 pp., http://nepis.epa.gov/Adobe/PDF/P100785F.pdf.

Environmental Protection Agency (EPA). 201 Ob. State of Technology for Rehabilitation ofWastewater
Collection Systems. EPA/600/R-10/078, U.S. EPA, Office of Research and Development, Cincinnati, OH,
Jul., 325 pp., http://nepis.epa.gov/Adobe/PDF/P1008C45.pdf.

Environmental Protection Agency (EPA). 2013. State of Technology for Rehabilitation of Water
Distribution Systems. EPA/600/R-13/036. U.S. EPA, Office of Research and Development, Cincinnati,
OH, Mar., 212 pp. http://nepis.epa.gov/Adobe/PDF/P100GDZH.pdf.

Pipe-Robo-Tec USA. 2015. Pipe-Seal-Fix and Pipe-Seal-Flex Installation Manual. Available at
http://www.piperobotecusa.com/assets/fix-flex_installation_manual_final.pdf. June.

Sihabbudin, S. and S. Ariaratnam. 2009. "Methodology for estimating emissions in underground utility
construction projects." Journal of Engineering Design and Technology, 7(1), 37-64.
                                             29

-------