^£D S5%
£
a	INSPECTION, TEST AND MAINTENANCE GUIDANCE
FOR FIRE SAFETY SYSTEMS
% pro^
Environmental Protection Agency
Safety, Health and Environmental Management Division
June 1994

-------
TABLE OF CONTENTS
PAGE
INTRODUCTION 		1
FIRE SAFETY SYSTEM COMPONENTS		 .	2
MATER SUPPLY SYSTEMS 		3
AUTOMATIC SPRINKLER SYSTEMS 		4
STANDPIPE AND HOSE SYSTEMS 		7
FIRE PUMPS	11
FIXED EXTINGUISHING SYSTEMS 		11
PORTABLE FIRE EXTINGUISHERS 		12
FIRE JUARM SYSTEMS	12
POWER SUPPLY	15
MISCELLANEQUS WIRE SAFETY COMPONENTS	15
HOUSEKEEPING PRACTICES 		16
FIRE SAFETY SYSTEMS CHECKLIST 		17
ATTACHMENT A) EXAMPLES OF RECORD SHEETS 	 A-l
- i -

-------
INSPECTION, TEST AMD MAINTENANCE GUIDANCE
FOR FIRE SAFETY SYSTEMS
INTRODUCTION
Fire safety systems fi ling fire suppression, detection and alarm) are crucial to
defend against fire. However, they are rendered useless if no routine maintenance or
testing is provided to assure their operation when needed. This document provides limited
guidance for periodic inspection, testing, and maintenance of fire safety systems commonly
found at EPA laboratory facilities. The document is intended as a starting point to help
safety personnel focus on key aspects of fire safety systems maintenance. The user will
need to evaluate their facilities to determine other specific system maintenance
requirements.
The document is divided in two portions. The first portion describes fire safety
components and their functions. The second portion is a Checklist of inspection, testing
and maintenance requirements of specific components. The Checklist, can be used
independently to ensure that fire protection components are evaluated on a regular
scheduling basis, or it may be integrated into a facility preventive maintenance program.
It can be useful in developing a fire prevention plan for the facility. The following
systems and components are discussed: water supply, automatic sprinklers, standpipe and
hose, fire pumps, fixed and portable extinguishers, fire alarm, fire doors, dampers and
emergency lighting.
Records o£ all testing, maintenance and inspection activities should be kept on file for
periodic review. Atr.aehment A provides examples of how inspection activities can be
recorded.
Although facility personnel can visually inspect various system components, many of the
testing and maintenance and some of the inspection procedures require handling of the
equipment or component. Those procedures requiring handling should be performed by
qualified fire protection contractors. Any test or maintenance procedure having a direct
connection to a centra 1	or fire department should b<~. made only after proper notice
is given to the signal receiving station. Fire protection systems are required to be
acceptance tested upon their installation. This document does not address acceptance
testing of new systems.
- 1 -
DRAFT - JUNE 1994

-------
EPA policy requires that facilities follow the National Fire Protection Association (NFPA)
standards. This document was developed using the latest NFPA standards. Requirements
that are imposed by other local author it'should also be observed. At. the end of each
fire^safety component discussion, the reader is directed to the applicable NFPA
publications which the user will need to perform complete inspections, Ft r rol lowed.
FXRE SAFETY SYSTEM COMPONENTS
Each fire safety system component performs one or more functions of detection, suppres-
sion, or life safety. The water supply system is vital to fire suppression. Water which
may come from tlis-: city water system or water storage tanks, supplies automatic sprinklers,
standpipe and hose systems, and fire hydrants. A properly designed and maintained fire
alarm system will help limit loss of property and life by providing ea?. ty warning. Life
safety features such as fire walls and enclosed stairways are normally designed into the
building construction. Several components of life safety systems need to be inspected and
maintained to ensure that people can escape a building safely. This portion of the
document describes key fire safety components and their operation.
- 2 -
draft - mmm is§4

-------
WATER SUPPLY SYSTEMS
Water for fire protection is conveyed to a facility by various methods, including water
storage tanks, public water mains, dedicated fire mains and puhli. vettn hyd^-tnts. At EPA
facilities, lei if- commonly supplied through storage tanks and public fire raains. Fire
hydrants are norma 11y puhUcH owned and the local jurisdiction is responsible for their
upkeep. Fire hydrants axe used in emergencies to obtain water from the public water
supply. The most common type of hydrant is the dry barrel? it is used in locations
susceptible to freezing. Wet barrel hydrants are used where there is no danger of
freezing. Different portions of hydrants (e.g., piping, monitor nozzles, hose, hydrant
house) require routine inspection, test, and maintenance.
Water storage tanks hold a specified amount of water to augment water supply to the
facility or serve as the primary water source in remote areas. Tanks typically are
provided with control valves, check valves (which direct the flow of water), heaters fin
freezing climates), fire department connections, ladders, drain outlets, water level
alarms, and level indicators. Fire department connections, commonly referred to as
"Siamese connections," usually consist of a dual 2 1/2-inch outlet outside the building.
The fire department connections are interconnected to standpipes or automatic sprinkler
systems. The fire department attaches hose lines to these connections to boost the water
capacity, during a fire emergency,
Refer to NFPA 25, Standard for the Inspection, Testing and Maintenance of Water Based Fire
Prevention Systems, Chapter 6: Water Storage Tanks and Chapter 7: Private Fire Mains for
more detail.
AUTOMATIC SPRINKLER SYSTEMS
A sprinkler system is an integrated system of small discharge nozzles (sprinklers), an
automatic water supply, and underground and overhead piping, The system is usually
activated when the heat from a fire fuses a metal alloy in the sprinkler. The water
within the system then discharges over the fire area.
The vertical piping which connects the overhead piping and the underground water supply is
called the system riser. The riser is usually between 4 ^and 8 inches in diameter and
normally painted red. System components or function indicators which need to be inspected
- 3 -
DRAFT - JUNK 1994

-------
or tested {such as water control valves, alarms, pressure gauges! are normally located
close to or on the system riser. Figure 1 shows a layout of a typical sprinkler system.
Sprinkler systems and other systems directing water supply require valves at strategic
locations and intervals which control the flow	\ They may be needed to shut off
systems after	operations, or to isolate portions of the system for repair or
maintenance. Valves (including control valves, Outside Screw and Yoke (OS&Y) or Post
Indicator Valve {PIV)) have a system to indicate whether the valve is closed or open.
Check valves are installed to isolate separate sources of water supp iy; they direct the
flow of water toward the system. Alarm check valves generate an alarm when water flows
through the system. Gate valves are normally found on both sides of a check valve and are
used to isolate check valves for maintenance operations.
Other system connections and drains are provided to test water supply. Water flow test
connections are provided at specific locations te jm low flow tests of water suppl ies.
These test connections verify the operation of the water flow alarm devices such as water-
motor gong, pressure switch or flow switch. They also indicate the amount of time for
water to flow to the sprinkler. The fire department can pump water into the sprinkler
system through the fire department connection. These connections are used to supplement
the water supply. Drains are needed for maintenance operations such as flushing the
system.
The main types of sprinkler systems found at EPA facilities are discussed below. They are
wet pipe, dr> pipe, and pre-action. Each type of system has unique function indicators or
components which requite Ji t1event treatments and frequencies for inspection or testing.
For additional information on automatic sprinkler systems refer to NFPA. 'J5, Chapter 2:
Sprinkler Systems, NFPA 13, Installation of Sprinkler Systems,
Wmt Pipm Spxi nklmr Syattaag
Met pipe sprinkler systems have their piping filled with water and the sprinklers are
closed. When the sprinklers reach their operating temperature, they open and waf ex-
discharges immediately. Met pipe sprinkler systems are used only in heated buildings.
Some buildings may have small unheated areas, such as a cold room or walk-in freezer and
so an nantifreeze loop" or dry pendant sprinkler is selected. Figure 2 shows features of
a wet sprinkler control valve. Figure 3 shows more detail on the sprinkler riser.
_ 4 _
DRAFT - JUNE 1994

-------
CROSS MAIN-
BRANCH
LINES '
BULK MAIN
(RISER!
INSPECTORS
TEST
CONNECTION
AUTOMAT if!
SPRiNKi.EBS
WATER
MOTOR"
ALARM
ALARM VALVE
FIRE —	-u
DEPT. V
CONNECTION
O. S. Si Y, GATE VALVE
TO CONTROL WATER
SUPPLY TO SYSTEM
MAIN
DRAIN
CONNECTION
WATER SUPPLY
figure 1:
Typical Automatic Wei Pipe Sprinkler System (Reprinted by permission of NIT A)

-------
RISER
2" MAIN
DRAIN VALVE
WATER
MAIN WATER CLAPPER
WATER PRESSURE GAUGES
2" MAIN
DRAIN
ALARM CONTROL
VALVE
'WATER
TO RETARDING
CHAMBER
PRESSURE SWITCH
AND WATER MOTOR
ALARM
c wwml
AUXILIARY ALARM CLAPPER
MAIN WATFR CONTROL VALVE
WATER SUPPLY PIPE
NOTT VALVES NOS 18, 2 NORMALLY OPEN	CLOSE NO. 1 TO SHUT OFF WATER.
>	CLOSE NO. 2 TO SILENCE ALARM.
VALVE NO 3 NORMALLY CLOSED OPEN TO DRAIN SYSTEM
Figure 2: Schematic of Wet Pipe Sprinkler Valve
(Reprinted by permission of NFI'A)
SPRINKLER RISER
INCOMING
WATER
PRESSURE
GAUGE
PRESSURE
SWITCH
WATER
MOTOR
GONG
SYSTEM
WATER
PRESSURE
GAUGE
RETARD
CHAMBER
2" MAIN
DRAIN
INCOMING
WATER SUPPLY
Figure 3: Photograph of Wet Pipe Valve
(Reprinted by permission of NFI'A)

-------
Dry Pipe Sprinkler 83mtmas
Unheat, ed ^ bu i It 11ngs which are subject to freezing have dry pipe sprinkler systems instead
of wo'	ijyjbterns. However, the enclosure which houses the valves for dry pipe systems
must be heated. Dry pipe systems have their piping filled with air or nitrogen under
pressure. When the heat from a fire causes the sprinkler to open, the air pressure is
released. This permits the water pressure to push open the dry pipe valve. Water then
flows into the piping system and out the opened sprinkler. Dry pipe systems are often
less reliable than wet pipe systems due to additional maintenance requirements. Iignr^s 4
and 5 show details of a dry pipe sprinkler and valve. Figure 6 is a schematic of a dry
pipe system.
Delugm System*
In this system, the sprinklers are open; the water is held back by a deluge valve on the
system riser. When the fire detection system in the protected area activates, it trips
the deluge valve. This causes water to flow through all the sprinklers. These systems
are used in small areas such as cooling towers where water damage is not a concern.
fre-acfelon Systmnm
Pre-action systems are similar to deluge systems, except that the sprinklers are closed.
If water damage is a concern, as in computer rooms, a pre-action system is employed.
When the fire detection system trips the deluge valve, water enters the sprinkler piping.
However, water only discharges through the sprinklers which opened.
It is imperative to keep all records of sprinkler system evaluations on fx1p< Records of
testing, if compared over a few years, will help determine if the system capacity has
diminished. Attachment A is an example of inspection activities that should be recorded.
STANDPIPR AND HOSE SYSTEMS
Standpipe systems are a network of risers, piping, hose connections, and valves that allow
the Eire department or trained personnel to manual iy extinguish a fire. Water suppJy to
the stan.1p.ipo system can be automatic through water mains or provided by the fire
department. See Figure 7 for a drawing of a fire department connection. Components such
as hoses, cabinets, and nozzles must be routinely inspected. Consult NF	Care, Use
and Service rnstn] luti ;n of Fire Hose Including Coupling and Nozzles, NFPA 25, Chapter 3:
- 7 -
rwyrT - mm is 94

-------
ACCEl FRATOH
TO SPRINKl ERS
PRESSURE SWITCH
PRIMING FUNNEL
UPPER PRIMING VALVE
CHECK VA1 VF
MM PRESSURE GAUGE
<\ND low air pressure
¦Wl ICR
I O WA1 ER
motor gonc;
•	PRIMING chamber
lower priming valve
M ARM DRAIN
At ARM TEST COCK
PRIMING WATF R
?" MAIN DRAIN
FIRE DEPARTMENT
CONNECTION ——*
WATFR PRESSURE
CHECK VALVE W/BALL
DRIP. PIPE BALL DRIP
TO OUTSIDE
?•- DRAIN VALVE —
-TAMPER SWITCH
rim, re I: Schematic of Dry Pipe Spri"^r
(Reprinted by permission of Nt I A»
PRIMING WATEI
FILL CUP
SYSTEM AIR
PRESSURE
GAUGE
PRESSURE
SWITCH
WATER —1
SUPPLY
PRESSURE
GAUGE
2" "MAIN
DRAIN
figure 5:
Photograph of Dry Pipe Valve
(Reprinted hy permission of NF PA)

-------

1
(I I { (3) (4^
1
ITEM
DESCRIPTION
ITEM
Of? sen IP BON
ITEM
DESCRIPTION
1
City main
1?
Dry p«pp vr»lvp
23
O S ft Y. m!*(P trtptinn.it)
2
Pumps??-type fut> hyd*3"»
13
Anli-Uoori fS*?v«CR fopimnaH
24
Cher* vsslvp
3
UnrffMqrnunif lire mam
14
Accfilffalor {optional)
25
Rtw? to tpmsUm
4
K r>y valve »wi road box
15
Water mofm alarm «|tam
26
Thfusi Work
5
Post sndftaio? vaivi*
16
Wnlffi moim miasm
27
Drain vnivn jmrl phirj
6
Mam drain
17
Cross mam
28
Dfum drip
7
Rltil ririp
18
Dsy pips? valve hmiw
29
Uprtqhj tpimfelpr
8
firf fl'-psMmpnt rannpciipn
19
WalPi moirjt al;vm 'inp
39
Dry ppnifi'iit sprmkln
9
Check vaivp
20
Ptpssurr? swiirh
31
Inspectors lost vntve
to
Drain cup
21
Alarm line 5tr»inri
3?
fnsps'r.tnr '$ tns 1 rfr.im
f i
Main thmn vslvr
??
Alarm IPs! valve


Figure 6: Typical Dry Pipe Sprinkler System (Reprinted by permission o( NFPA)

-------
FIRE DEPARTMENT
SIAMESE CONNECTION
WATERPROOF MASTIC
C.IIFCK VAI.VE
11 FMIOH F IRF.	
1(1! FCTION PIPING
AUTOMATIC BAl L DRIP
Figure 7: Typical Fire Department Siamese Connection
(Reprinted by permission of NFFA)
Fhotograph of Fire Hose Cabinet
(Reprinted by permission of NFFA)

-------
Standpipe and Hose Systems for con	dance. Figure 8 illustrates a' fire hose
cabinet,
FIRE PUMPS
Fire pumps are provided to fire protection systems to boost the pressure of an existing
water supply. Fire pumps are designed to operate at various flows and pressures; rated
pressure (pump design), churn pressure (no flow), and overflow pressure (!50% of designed
flow). When the fire pumps are tested, performance at these flow rates is observed.
The pump may be housed in a cut-off room in the facility, or in a detached pump house.
The engine for operating the pump is typically a diesel engine or an electric motor.
Pumps can operate manually, as well as automatically if provided with pump controllers.
Pumps which provide primary protection for the facility normally start automatically.
A preventive maintenance program which complies with the manufacturer's recommendations
must be established and implemented. Maintain records on all work performed on the pump,
engine, controller, and auxiliary equipment. A routine review of test records can provide
clues to water supply or pump deficiencies. Refer to NFPA 20, Standard for the
Installation of Centrifugal Fire Pumps and NFPA 25, Chapter 5; Fire Pumps for additional
informati on.
FIXED EXTINGUISHING SYSTEMS
Many types of automatic extinguishing systems other than sprinklers are availabie for f :i re
suppre n. They are typically selected based on the hazard type that will be protected.
For protection of electronic equipment, EPA normaliy selects C02 extinguishing systems and
pre-action sprinkler systems. Foam water systems are selected to protect areas using
large amounts of flamm	ids. •
Carbon Dloxid9 Extiagul ehirtgr fly stoma (C03)
COj systems have C02 agent under pressure in cylinders and tanks. The tanks are accessed
through hoses to nozzles in the protected area. The systems apply C02 gas to fill an
entire room (total flooding systems), or to a specific area (local application).
- 11 -
DRAFT - JUNK 1994

-------
Additional information on these system can be obtained from NFPA 12, Carbon Dioxide
Extinguishing Systems, Figure 9 shows a typical C02 extinguishing system.
Foam-Wmtmr Systems
Fire fighting foam is used to combat fires involving flamn>ab!e and combust 1 b1 e liquids.
Foam is a mixture of air, water and a concentrated foaming agent. Aqueous Film Forming
Foam (AFFF) is the most popular type of extinguisher used at £f"\ id •, ^tiss. When AFFF is
discharged, it forms a blanket over the surface of the liquid, which smothers the fire.
Refer to NFPA 16, Chapter 8: Deluge Foam-Water Sprinkler and Foam-Water Spray Systems and
NFPA 25, Chapter 8: Foam-Water Sprinkler Systems for more information.
PORTABLE WISE EXTINGUISHERS
Portable fire extinguishers are required in most EPA facilities. Portable extinguishers
are selected according to the hazard they protect. The multipurpose dry chemical and
carbon dioxide extinguishers are most common at EPA facilities. The multipurpose dry
chemical can normally protect against most types of fires including electrical, ordinary
combustibles and flammable materials. C0a extinguishers are effective on electrical and
flammable liquid fires. The label on the extinguisher cylinder indicates what types of
fires it can extinguish.
FIRE ALARM SYSTEMS
A building fire alarm system provides audible and/or visual alarm signals when alarm
initiating devices such as a manual pull station, sprinkler* control valve, water flow
switch, or smoke detector operates, The alarm i	rig devices are connected to the
fire alarm control panel, which continuously monitors these devices. Refer to NFPA 10,
Portable Fire Extinguishers for more detail.
A common fire alarm arrangement is one where an alarm initiating device operates and a
general alarm sounds. All alarm indicating devices, such as bells, horns arid lights
operate. Additionally, alarms sound at the alarm control panel. The alarm control panel
can be used to dea^twafce alarms during testing and maintenance operations. The alarm
annunciator panel indicates the location or type of device which activated, EPA
facilities usually have their fire alarm systems monitored by a central station. The
- 12 -
DRAFT - JUNK 1994

-------
WIRE AND CONDUIT TO DETECTORS
DISCHARGE
NOZZLE
CONTROL PANEL

PIPING
CYLINDER
CONTROL HEAD
ACTUATION LINE
DISCHARGE CONTROL
VALVE
NAMPPL ATF; WITH
SYSTEM DATA
CYLINDER
Jy»—WALL MOUNTING
BRACKET
Figure 9: Typical Carbon Dioxide High Pressure System	«	. .
5 leisure system (Keprinted by permission of NF PA)

-------
central station, upon receiving ar, alarm	will make atlfciipts to verify the alarm.
If 31 cannot verify a false alarm, the Fire Department responds to the mstail ation. Fire
alarm systems are connected to emergency power supplies, which must be inspected and
maintained, as well.
Smokm Bmtmctors
Fires produce detect ~ ~ lantities of smoke before any significant rise in heat. Smoke
detection devices respond when smoke particles enter the units. Duct smoke detectors
cause the air handJing systems of a buildings ventilation system to shut down, thereby
preventing the .recirculation of smoke within the building. Magnete ri catxficial smoke
can be used to test smoke detectors. It is recommended t	smoke be applied
from a distance of at least 12 feet to avoid damage to the unit.
The following documents provide additional information: NFPA 10.1, Life Safety Code; NFPA
72 H, Guide for Testing-.
Jfaafe DmtBctora
A heat detector works when the fusible elements within, the unit melt or when air or metal
in the unit expands in response to a predetermined heat level. Heat detectors are
provided on the initiating device circuits. SPA facilities have fixed temperature, rate-
of-rise, or rate compensation heat detectors. Fixed temperature heat detectors must be
replaced if they are tested using heat. Other restorable detectors can be safely tested
with a hair-dryer, or shielded heat lamp. Rate-of-rise and rate compensation detectors
can reset themselves after testing, Any detectors which fail to operate during tests must
be properly replaced. Records for testing, inspection, and maintenance must be kept on
file.
Manna. 1 Stations, Bella, and Horna
Basically, manual stations are electrical switches housed in a red-colored box. They
operate upon breakii	11ing a lever, or using a key. Bells and horns generate
loud noises to indicate emergencies. Sometimes visual signals such as strobes and lights
are provided.
- 14' -
DRAFT - JTJOT! 1994

-------
POMSR SUPPLY
Power supply to the alarm system can be provided by either commercial it and power
supply or an engine-driven, generator. Secondary power suj	te alarm system must be
provided. It can cc	>rage battery and charger, or an engine-driven generator.
Secondary power supplies normally support other systems as well, including fire pumps,
exhaust hoods and emergency lighting. Ml power supplies, including uninterrupted power
supplies {UPS!, have inspection, test and maintenance requirements. Jk routine maintenance
and operational testing program must be developed and implemented based on manuf .i-"t mer's
recommendat ions.
NFPA 110, Emergency and Standby Power Supply and NFPA 72, National Electrical Code discuss
power supply requirements in detail.
MISCELLANEOUS FIRE SAFETY COMPONENTS
Firm Doora
Fire doors are used to protect openings in fire-rated walls and partitions. They are
required to be sell -closing or automatic closing (i.e., close upon activation of detection
systems). It is imperative that fire doors are not kept open with wood jambs or door
chocks. Doing so compromises fire safety and the design flow rates of ventilation
systems. NFPA 80, Standard on Doors and Windows provides details on door t«sting.
Daunpora
Fire dampers are provided on some air distribution systems to limit the migration of heat
or flame across a fire barrier. They close automatically when they detect excessive heat
in the air distribution duct. Smoke dampers restrict the movement of smoke.
NFPA 90A, Installation of Air Conditioning and Ventilating Systems and NFPA 101, Life
Safety Code discuss fire and smoke dampers.
Emergency Lights
Emergency lighting is required at most EPA facilities. Laboratory work units require at
least 10 candles of illumination on the face of the hood during emergencies. Emergency
lighting must operate automatically in the event of any interruption of normal lighting.
- 18 -
DRAFT - JUNK 1994

-------
A secondary source of power is required. This can be storage batteries or emergency
generators.
Refer to NFPA 10.1, Chapters 5 and 31 for more information. Written records of testing
must be kept on file.
HOUHERKEPIIJ^ PRACTICES
Good housekeeping is a continuous eft ort by management and staff to control sources of
ignition and to facilitate emergency evacuation. Managers must ensure safe storage and
handling of" materials. A lack of facilities to store materials can result in blocked exit
waysi sprinklers, and fire extinguishers. In addition to adding to the fire load, the
accumulation of combustibles (outside the building as we11 as inside the building) may
hinder safe evacuation. The safe handling and storage practices for combustible and
f lammabJ liquids must be observed.
There is no required evaluation schedule per se. However, individuals performing
inspections should keep good housekeeping practices in mind. Further information can be
found in the Fire Protection Handbook, 17 th Edition, Section 2, Chapter 34.
- is -
DRAFT - JUNK 1994

-------
FIRE SAFETY SYSTEMS CHECKLIST
hydrant
semi-annually ft after each
operation: Check all hydrants
near the facility for signs of
damage or obstructions. Verify
thai private hydrants are
visible and accessible and that
caps are in place. Wet hydrants
require annual inspection.
annually: Fully open and
close private hydrants to
ensure water flows
properly.
annually:
lubricate private
hydrants and
provide other
services according
to manufacturer.
hydrant
piping
annuallyt Inspect exposed
piping for leaks, damage, or
corrosion.
5 yearst Perform flow
tests; determine
deterioration.

hose/hydrant
house
monthlyi Inspect for
accessibility, physical damage,
and missing equipment.
Test hoses per NFPA 1962.
annuallyt Ensure
all fire hose and
other components
are in usable
condition.
hydrant
monitor
nozzle
semi-annuallyt Check for
leakage, physical damage,
corrosion.
annually* Test similarly
to hydrants.
semi-annuallyt Oscillate
and move nozzles through
ill range.
annuallyt
Lubricate to
ensure proper
operation,
- If -
DRAFT - JUNE IS §4

-------
fire
department
connection
monthly: Ensure connection is
acco,?iMr and visible. Check
that caps or plugs are in place;
threads are clean, undamaged and
lightly lubricated.
control valve
waakly: Verify that sealed
control valves are open,
monthly: Verify that locked
valves or valves with tamper
switches are open.
5 years: . Inspect internally.
Verify components operate
properly and move freely.
other water
supply
valves,
including
post
indicator and
roadway valve
weekly:
- 18 -
Clean, repair or
replace per
manufacturer' s
instructions.
annually:
Exercise post
indicator and
outside screw and
yoke (OS&Y)
valves. Fully
close and reopen
each valve.
DRAFT - JUNK 1994

-------
water storage
tank
monthly: Check that the proper
water level and condition are
maintained. Ensure that:
heating devices are kept in
order; the tank roof is kept
tight and in good repair,* ice
does not form on the tank
surfaces; no dirt or rubbish is
piled near the base of the
column. During freezing
weather, check water
temperature. Ensure that water
is maintained above 40°F.
5 years t inspect interior of
tank for corrosion.
monthly: Verify that valves are
secured in the open position.
weeklyt Inspect sealed valves.
~ 19 -
Maintain tank at
full or designed
water level.
semi-annually:
Drain or flush
sediments from
tank.
annually: Clean
tank vents. Fully
open and close
tank drain valve.
annually:
Lubricate all
valve stems on the
control	is.
DRAFT - JUNK 1994

-------
sprinklers
annually: Ensure sprinklers are
free of corrosion, foreign
materials, paint and physical
damage,
monthly: Vet. if y that
obstructions such as stock pile
racks are at least 18" below the
sprinklers.
5 years: Test "Extra
High" sprinklers.
10 years: Retest fast
response sprinklers.
50 years: Replace
sprinklers or send
representative samples to
laboratory for
operational testing.

supply of
spare
sprinklers
monthly; Verify the proper type
and number of sprinklers and
that a sprinkler wrench is
avail,iJol g.


piping
annually: Veri fy that piping is
free of mechanical damage,
leakage, corrosion and
misalignment. External loa'd
should not be applied to
sprinkler piping.


seismic
braces and
hangers
annually: Ensure that loose
braces and hangers are securely
fastened.


alarm devices
monthly: Verify that alarm
devices are not physically
damaged and that all electrical
connections are in place.
quarterly, Verify all
devices generate audible
and visual signals.

- 20 -
DRAFT - JUNE 1954

-------




hydraulic
nameplar.e
quarterly - Ensure that
namep 1 a;•>¦? i .3 ^ and that it
is attached securely to
sprinkler riser.


water
pressure
gauge
monthly: Ensure that normal
water supply pressure is
provided. Verify condition of
gauge.
5 years: Replace with
new or recalibrated
gauges.

main drain
______ 	

quarterly; Open the 2"
main drain valve to
verify the flow of water.
Determine if the normal
water supply as indicated
on hydraulic dataplate is
available. Check for the
presence of closed valves
or other obstructions.

antifreeze
loop

annually: Check the
freezing point of the
antifreeze solution;
adjust if necessarv.

water flow
alalHl
monthly: Verify that alarm
devices are not physically /
damaged and that all electripal
connections are intact, \
quarterly: Open the
inspector's test
connection to assure the
sounding of alarms.
')

- 21 -

DRAFT - ormns 1994

-------
annually: Before the onset of
freezing weather, verify that
sprinkler piping will not. be
exposed to'freezing and that
adequate heat will be provided.
priming water
level test
valve

quarterly: Slowly open
the priming water 1 ove1
test valve to determine
the priming water level.
Add or drain priming
water,
¦
air pressure
gauge
weakly: Verify that the system
is supp1]ed with air or nitrogen
at the required pressure.
Normal pressure should be
verified initially with the
sprinkler contractor. A
pressure loss of more than 10%
should be investigated.
5 years: Replace with
new or recalibrated
gauge.

building
heating
- 22
DRAFT - JUNE 1994

-------
low air
pressure
alarm

quarterly: Verify the
transi :m
when test valve is
opened. Close water
supply valve, slowly
release air from the
system by gently opening
the inspector's test
valve.

dry pipe
valve
weekly: Ensure that the valve
is free of physical damage.
Ensure all trim valves are in
the appropriate (open or closed)
position.
annually: Inspect interior
during annual trip test.
annually: During the
spring, trip test dry
pipe valve with control
valve partially open.
every 3 years: Perform a
full flow trip test with
the supply control valve
annually: Clean
the interior and
replace or repair
parts during
annual trip test.
valve
enclosure
daily: Inspect enclosure
heating equipment d< ig
cold weather. Maintain
temper-it ure to at 1®asl 40°F.
Inspect weekly if low
temperature alarms are present.


water . flow
alarm

quarterlyi Open the alarm
by-pass valve to assure
the sounding of the
alarm; do not use the
inspector's test
connection.

- 23 -
DRAFT - iTUNC 1994

-------

low point
drains

annually (Fall): Drain
all low point drains to
remove any water buildup
in the sprinkler lines.

pre-action
valve
weekly: Ensure that the valve
is free of physical damage and
that all trim valves are in the
appropriate (open or closed)
position. Check: that electrical
components are in service.
annually: Inspect interior
during annual trip test.
<*nnually: During the
spring, trip test dry
pipe valve with control
valve partially open,
every 3 years: Perform a
full flow trip test with
the supply control valve
fully open.
annually: Clean
the interior and
replace or repair
parts during
annual trip test.
valve
enclosure
daily: Inspect enclosure
heating equipment dally during
cold weather. Maintain
temperature to at least 40°F.
weeklyt Inspect if low
temperature alarms are present.


detection
systems

semi-annuallyt Test fire
detection associated with
the sprinkler system for
proper operation.

- 24 -
DRRFT - JUNK 1994

-------




water flow
alarm

quarterly: Open the alarm
by-pass valve to assure
the sounding of the
alarm; do not use the
inspector's test
connection.

air pressure
gauge
weakly: Verify that the normal
air and water pressures are
provided. (See dry pipe
system.)
5 years: Replace with
new or recalibrated
gauge.

hose
monthlyt Inspect hose rack,
reels and nozzle for damage."
Ensure that hose is properly-
racked in cabinet and that
nozzle is attached.

annuallyt Remove
and rerack hose.
Lubricate swing-
out hose racks.
hose cabinets
monthlyt Ensure that cabinet is
equipped with hose and nozzle.
Inspect cabinet signs; ensure
they are conspicuous and
appropriate.

monthlyt As
needed.
hose nozzle
annuallyt Confirm that nozzles
can be easily opened and closed.
monthly» Verify that
nozzles operate smoothly.
Repair or replace.

- 25 -
DRAFT - JUNE 1394

-------
standpipe
system
monthlyi If standpipe does not
require a hose, ensure that the
2-1/2" valve is not damaged and
readily aoceoRi M c,
5 yearsi Perform
hydrostatic and flow
tests of hydraulically 1
remote location. 1
alarm devices

quarterly: Test water
flow alarm and
* «* »

pump house
weekly: Ensure that the pump
house is kept clean, dry and
free of condensate. Verify
adequate heat and ventilation.
Ensure that environmental
conditions (ventilation, heating
and illumination) are adequate.


pump system
weekly: Inspect the condition
of the pump components such as
bearings, st ig boxes,
suction pipe strainers, power
supply, storage batteries,
lubr.i nation system.


pump
controller
weekly: Ensure that the pump
controller is in the automatic
startin; 1.


- 26 -
DRAFT - JUNE 1994

-------
electrical
system
weeklys Ensure all pilot lights
are illuminated, Check oil
level in sight glass.
weekly: Operate pump for
10 minutes without
flowing water.
annually: Perform flow
test at different loads.
Compare with
manufacturer's
specifications.
annually:
Lubricate
mechanical moving
parts, calibrate
pressure switches
I grease motor
bearings.
diesel engine
system
weakly: Ensure tank is two-
thirds full. Check battery
readings. Check oil and cooling
water levels. Check tightness
of packing gland.
		
weekly: Operate pump for
at least 30 minutes. Do
i j water,
annually: Perform pump
performance test, Verify
pump speeds at each flow.
Verify setting of relief
valves.
annually; Keep
engine clean, dry,
and well
lubricated.
Maintain the
proper oil level
in the crankcase.
NFPA 25 contains
other significant
details.
Frequencies vary.
extinguishing
iders
weekly: Check liquid 1eve1
gauges.
monthly: Check for signs of
leakaye and phys i dl damage.
semi-annually: Weigh
cylinders. Operate
cylinder control head.

nozzles
weekly: Check for physical
damage.



- 27 -

DRAFT - mm 1994

-------
system
weekly; Inspect entire system
for physical damage.
annually} Perform
actuating test of system.
12 ysarsi Perform
discharge test.
mmmmmwmmmmmmmmmmmsiim
5 yearat Perform
hydrostatic test |
on hoses, i
12 years t Perform
hydrostatic test
on system, hoses,
cy1inders.
general
requirements
general
requirements
monthlyt Confirm that
extinguisher is in its proper
tee and that it appears in
operating condition. Confirm
that extinguisher is visible and
accessible and that seals and
tamper indicators are intact.
Verify that pressure gauge is in
the normal range. Note any
physical damage. Initial and
monthly: Ensure that all
equipment is in place and in
good condition. Determine if
|components are free of
1 corrosion, foreign materials,
jtampering, or physical damage.
5 years t Perform
hydrostatic test.
12 yearst Perform
hydrostatic test on dry
mical type.
annuallyt Examine
mechanical parts
thoroughly.
- 28 -
DRAFT - OTffl IS§4

-------




fire alarm
control
equipment,
including
fuses and
light
emitting
diodes
(LEDs).
annually: Inspect fire alarm
equipment for damage or
operability. Check illumination
of fire alarm and enunciator
panels.
annuallyt Test
supervisory device
circuits; check primary
and secondary power
supplies. Test lamps and
LEDs on annunc .iat ing and
fire alarm control
panels. Check initiating
and signaling device
cuits.
semi-annuallys
Remove fuses and
check ratings.
smoke
UctcCtOIo
semi-annua1ly: Check all smoke
detectors for obstruction or
damage. Ensure the detectors
are properly located.
annually: Veri fy
sensitivity range of
device. Test device for
alarm response.
Remove
.-n>:umuiation of
dust and dirt.
Clean devices per
manufacturer's
speciCications.
heat
defectors
¦ami-annually: Check all heat
detectors for obstruction or
damage. Ensure the detectors
are properly located.
annually: Laboratory
test and replace 2% of
fixed temperature
detectors. Heat test
lers.

duct detector
semi-annually: Ensure that
device will sample the air
stream.
annually; Verify that
device will sample the
air stream. Verify
sensitivity range of
device. Test device for
alarm response.

- 29 -
DRAFT - JUNE 1994

-------
audible/
visible
devices
¦cnoi-annually: Determine if
bells and horns appear
operational.
annuallyt Measure sound
1pvels through out
protected areas.

batteries
monthly: Inspect for corrosion
and leakage. Ensure tightness
of connection. Certain battery
types require less frequent
inspections.
monthly; Perform
discharge, charger and
load voltage tests. Some
batteries require less
frequent testing.

manual
stations
requirement
¦«m±~annuallyt Determine if
manual stations appear
operational.
annually: Activate t he
station. Determine if
bells and horns are
audible in all portions
of the building.

annually: Test primary
arid secondary power
supplies.

emergency-
power supply
systems
weaklyc follow manufacturers
instructions.
monthlyi Exercise under
load. Follow
manufacturer1s
instructions.

automatic
t.i ans f er
switch
waeklys Inspect for evidence of
overheating,
monthly: Operate transfer
switch from normal
position and return.
Remove dust and dirt.
Replace contact when
rpmn
tf&W «&«¦ saW. S
Follow
manu' s
instruct ions,
NFPA 110 contains
significant
details.
- 30 -
DRAFT - JUNK 1994

-------
doors
'annually? Ensure that fire
doors are not blocked open.
Verify that the door is not
damaged and that it closes
completely and catches.
_~
as neededt
Lubricate door
guides and
bearings. Operate
automati^ tlosing
devic
Fire dampers
annually: Verify hinges and
other moving parts appear
operable.

annuallyt Operate
damper, lubricate
moving parts.
Emergency
lighting
monthlyt Perform a functional
test. Operate unit for 30
seconds.
Initial and date tags attached
to unit.
annuallyt Test for 1 1/2
h O VI2T S •

- 31 -
DRAFT - JUNE 1994

-------
Monthly Inspection Record Sheet
System/ Component:	Automatic Sprinkler System, No. 1
Description; This is a wet pipe sprinkler system which serves the office portion of the building. The system capacity is
650 fpra at 45psi. System has 100 sprinklers.
date
inspector
(initials)
control
valve
sprinkler
alarm
device
water
pressure
gauge
water
flow
alarm
sprinkler
supply
















Quarterly Inspection & Test Record Sheet
System/ Component: .	Automatic Sprinkler System, No. 1
Description: This is a wet pipe sprinkler system which serves the office portion of the building. The system capacity is
650 gpni at 45psi. System has 100 sprinklers.
date
inspector
(initials)
hydraulic
name plate
test of alarm
devices
test of 2"
main drain
test water flow
alarm












Annually Inspection Record Sheet
System/ Component:	Automatic Sprinkler System, No. 1
Description: This Is a wet pipe sprinkler system which serves the office portion of the building. The system capacity is
Attatchment A

-------
650 gpin at 45psi, System has 100 sprinklers.
date
inspector(initials)
piping
sprinkler seismic braces
building heat


















Attatchment A

-------