&EPA

United States
Environmental Protection
Agency

Office of Water (4601M)

Office of Ground Water and Drinking Water

Total Coliform Rule White Paper

Causes of Total Coliform-Positive Occurrences in
Distribution Systems

DECEMBER 2006


-------
PREPARED FOR:

U.S. Environmental Protection Agency
Office of Ground Water and Drinking Water
Standards and Risk Management Division
1200 Pennsylvania Ave., NW
Washington DC 20004

Background and Disclaimer

The USEPA is revising the Total Coliform Rule (TCR) and is considering new possible
distribution system requirements as part of these revisions. As part of this process, the
USEPA is publishing a series of issue papers to present available information on topics
relevant to possible TCR revisions. This paper was developed as part of that effort.

The objective of the "white papers" is to review the available data, information and
research regarding the potential public health risks associated with the distribution
system issues, and where relevant, identify areas in which additional research may be
warranted. The white papers will serve as background material for EPA, expert and
stakeholder discussions. The papers only present available information and do not
represent Agency policy. Some of the papers were prepared by parties outside of EPA;
EPA does not endorse those papers, but is providing them for information and review.

Additional Information

The paper is available at the TCR web site at:

http://www.epa.gov/safewater/disinfection/tcr/requlation revisions.html

Questions or comments regarding this paper may be directed to TCR@epa.gov.


-------
[This page intentionally left blank]


-------
Table of Contents

1.	Overview

1.1	Purpose and Scope

1.2	Definitions

2.	Information Sources

2.1	Contamination Events and Data from the United States and Other Developed Countries

2.2	Waterborne Disease Outbreak Reports

2.3	Total Coliform-Positive Events

3.	Data Limitations

3.1	Distribution System Monitoring and Data Interpretation

3.2	Correlating Illness to Distribution System Total Coliform Positive Events

3.3	Recording and Archiving Total Coliform Positive Events

4.	Possible Causes of Total Coliform Occurrences

4.1	Sources of Total Coliform Bacteria

4.1.1	Soil and Water Surrounding Pipes

4.1.2	Biofilms and Microbial Growth

4.1.3	Corrosion Tubercles

4.1.4	W eather-Rel ated Events

4.1.5	Customer Connections

4.1.6	Materi al s Added to the Di stributi on Sy stem

4.1.7	Sediments

4.2	Pathways for Total Coliform Bacteria to Enter Distribution Systems

4.2.1	Finished Water Storage Facilities

4.2.2	Cross Connections and Backflow

4.2.3	Intrusion and Main Breaks

4.2.4	Treatment Breakthrough

4.3	Mechanisms that Allow Total Coliform Bacteria to Enter or Proliferate in Distribution

Systems

4.3.1

Hydraulic Conditions

4.3.2

Operations

4.3.3

Maintenance Practices

4.3.4

Retention Time

4.3.5

Presence of Nutrients

5. Summary



6. References



- 1 -

April 2007


-------
1. Overview

1.1 Purpose and Scope

As discussed in the paper "Total Coliform Rule and Distribution System Issue Papers
Overview," EPA in 2003 announced its plans to assess the effectiveness of the current Total
Coliform Rule (TCR) and to consider revisions to the TCR with new requirements for ensuring
the integrity of the distribution system. Part of this assessment entails reviewing total coliform
positive events and MCL violations to determine the extent of events that are captured by the
existing TCR monitoring.

This paper on the causes of total coliform-positive occurrences in distribution systems
reviews existing literature, research, and information on public water supply distribution system
occurrences of total coliform bacteria and the circumstances and deficiencies identified as
having caused those events. These occurrences include documented waterborne disease
outbreaks where total coliform was detected; positive total coliform sample results; and acute
violations of the Total Coliform Rule (TCR) (40 CFR Sections 141.21 and 141.63). This paper
compiles causes of positive total coliform events, identifies commonalities between different
events, and describes potential causes that may not have been reported in available event
summaries for the purpose of highlighting potential strategies for control or prevention of the
total coliform occurrence.

The scope of this paper includes appurtenances owned and operated by private customers
(such as service lines), that are typically not considered the responsibility of the public water
system purveyor since these appurtenances sometimes serve as a pathway to the distribution
system or a source of contaminants. This paper does not provide a comprehensive listing of all
documented total coliform occurrences or a statistical representation of the number or relative
frequency of each cause of an event. Contamination events involving disinfectants, disinfection
byproducts, lead, copper, and other chemicals found in the distribution system are only
mentioned where total coliforms were also detected, or where the case study illustrates a
pathway or mechanism important to total coliform occurrence. This paper does not address
source water or water treatment deficiencies that result in a distribution system occurrence of
total coliforms.

The majority of the contamination events described in this paper occurred in community
water system distribution piping or finished water storage facilities. Community water systems
typically have more extensive distribution piping, storage, and pressure complexities in
comparison to non-community water systems. This distribution system complexity creates
more opportunity for circumstances to create a contamination event. In addition, public health
outcomes related to contamination events may more likely be detected in these types of systems
since larger populations are potentially affected; consumer complaints are more likely from
residential customers than transient populations; and residents are more apt to notice if
something about their drinking water is abnormal. Several case studies from non-community
water systems have been included for contamination events where the configuration of the
distribution system is similar to a community water system (i.e., not just interior plumbing) and
therefore the circumstances of the contamination could also occur in community systems.

April 2007

-2 -


-------
1.2 Definitions

Causes are the specific failure mechanisms, pathways, and sources of contaminants that
contribute to the occurrence of total coliforms.

Community water system is a public water system which serves at least 15 service
connections used by year-round residents or regularly serve at least 25 year-round residents (40
CFR Section 141.2).

Contamination event is defined as the combination of circumstances that allows an undesirable
microbial (e.g. coliforms) and/or chemical substances in the distribution system. Contamination
occurs when a source of contaminants is present (e.g., untreated sewage in soil external to
pipeline), a pathway to the distribution system exists (e.g., open pipeline for repair, point of
leakage, or faulty seal), and a mechanism that allows the contaminant to travel through the
pathway to the distribution system (e.g., pressure conditions). Contamination events can be
chronic, intermittent or short-term occurrences. They are not restricted to documented
waterborne disease outbreaks or violations of National Primary Drinking Water Regulations
(NPDWRs).

Distribution system is defined as a system of conveyances that distributes potable water
including all pipes, storage tanks, pipe laterals, and appurtenances that comprise the delivery
system.

Non-community water system is a public water system that is not a community water system.
A non-community water system is either a transient non-community water system or non-
transient non-community water system (40 CFR Section 141.2).

Pathway is an entry point to the distribution system or mechanism that allows contaminants to
enter the distribution system. Examples include physical openings in the pipes or storage
facilities such as faulty seals, leakage points, unprotected vents or pipe openings for repairs.

Public water system (PWS) is a system for the provision to the public of water for human
consumption through pipes or, after August 5, 1998, other constructed conveyances, if such
system has at least 15 service connections or regularly serves an average of at least 25
individuals daily at least 60 days out of the year (40 CFR Section 141.2).

Waterborne disease outbreak is the occurrence of two or more individuals experiencing a
similar illness after exposure to water and epidemiological evidence implicates water as the
probable source of illness. If water quality data indicate chemical contamination or laboratory-
confirmed primary amebic meningoencephalitis, a single case of illness is considered a
waterborne disease outbreak. Outbreaks that are attributed to the contamination of drinking
water at its point of use (e.g., a contaminated water faucet or serving container) are not
classified as waterborne disease outbreaks by the CDC (Lee et al., 2002).

April 2007


-------
2. Information Sources

Sources used to obtain information on total coliform occurrences within the distribution
system are discussed in Section 2.1. Data from waterborne disease outbreak reports are
discussed in Section 2.2. Information regarding total coliform-positive events is detailed in
Section 2.3.

2.1	Contamination Events and Data from the United States and Other Developed
Countries

Research reports published in peer-reviewed journals and other literature specifically
addressing distribution system water quality provide actual and potential contamination
scenarios. Anecdotal reports from newspapers and e-based periodicals were used where the
cause of a contamination event was clearly established as having been distribution system-
related. EPA regional offices were also contacted to verify information on events and to
describe additional events, where possible.

Additional data sources include the following:

•	Safe Drinking Water Information System (SDWIS). The SDWIS database was queried
for events that indicated bacterial contamination to verify if TCR violations coincided
with the event (described in more detail in Section 2.3).

•	Consumer Confidence Reports (CCR) database. CCRs were obtained, where available,
to further expand on events and verify causes.

•	Surveys. Surveys conducted by national organizations, such as American Water Works
Association (A WW A), were investigated to obtain statistics on industry practices that
may highlight causes of events.

•	National Oceanic and Atmospheric Administration (NOAA). The NOAA database was
queried to determine if significant weather during or near an event may have contributed
to the contamination event. Correlations were found with catastrophic events but a
thorough analysis of more typical events was not completed.

2.2	Waterborne Disease Outbreak Reports

Contamination events that result in illnesses may be recognized by local public health
officials or others, and in some instances, reported to the Centers for Disease Control and
Prevention (CDC). CDC's investigation will determine if the contamination event meets the
criteria of a waterborne disease outbreak, and therefore will be included on the CDC report.

Since 1971, EPA, the CDC, and the Council of State and Territorial Epidemiologists have
maintained a collaborative surveillance system for collecting and reporting data on the
occurrences and causes of waterborne disease outbreaks in community and non-community
public water systems. Where CDC has determined a waterborne disease outbreak has occurred,
details on the cause(s) of the waterborne disease outbreak are often recorded and made publicly
available by CDC. The investigative work for these types of outbreaks is focused on
determining the circumstances leading to the outbreak.

April 2007

-4 -


-------
The primary responsibility for detecting and investigating waterborne disease outbreaks falls
with state, territorial, and local public health agencies. The results of the investigations are
voluntarily reported to CDC on a standard form. The form is used to record the following:

•	Data related to characteristics of the outbreak.

•	Results from epidemiological studies.

•	Specimen and water sample testing.

•	Factors contributing to the outbreak, including environmental factors, water distribution,
and disinfection concerns.

CDC obtains additional needed information from the state's drinking water agency, which
are analyzed and included in their disease outbreak reports and summaries.

Craun and Calderon (2001) analyzed the causes of waterborne disease outbreaks associated
with chemical and microbial contaminants entering the distribution system or storage facilities,
and water that was corrosive to plumbing systems within buildings or homes for the period
1971 to 1998. CDC reports (Lee et al., 2002; Blackburn et al., 2004) provide additional
information on outbreaks that occurred from 1999 through 2002, as well as outbreaks
previously unreported in 1995 and 1997. Among these summaries, data are provided for
distribution system-related outbreaks from 1971 to 2002. The data show outbreaks occurred in
both community and non-community public water systems. In this time period, 126 of 689
(approximately 18 percent) of the reported waterborne disease outbreaks were caused by
distribution system deficiencies.

Exhibit 1 summarizes the findings regarding outbreaks in community and non-community
water systems caused by distribution system deficiencies from 1971 through 2000. Specific
examples of some of these outbreaks are also included later in this paper under the discussion of
contaminant pathways and causes of contamination events.

2.3 Total Coliform-Positive Events

SDWIS database and information provided by EPA regional offices were used to determine
if coliform-positive events or TCR violations coincided with microbial contamination events
presented in this paper. According to the USEPA, more than 9,000 TCR maximum
contaminant level (MCL) violations occurred each year from 2000 through 2004
(http://www.epa.gov/safewater/data/getdata.html).

An association between waterborne disease outbreaks and coliform-positive events was
studied by Craun et al. (1997). This study reviewed epidemiologic investigative reports of
waterborne disease outbreaks and available coliform data. The evaluation included waterborne
disease outbreaks reported during 1983-1992. The authors found that water samples from 52
percent of the community water systems and 87 percent of the non-community water systems
showed the presence of coliform organisms during the outbreaks. In community systems,

April 2007


-------
Exhibit 1. Distribution System Deficiencies Causing Outbreaks in Community and Non-
community Water Systems 1971-2000

Deficiency Causing Distribution System-Related
Outbreaks

Number of Distribution
System-Related Outbreaks

Percentage of
Distribution-Related
Outbreaks by
Deficiency

CWS*

NCWS**

Total

Cross-connection/backsiphonage

49

15

64

53.3

Corrosion/leaching of metals

12

1

13

10.8

Broken or leaking water mains

11

0

11

9.2

Contamination during storage

9

6

15

12.5

Contamination of mains during construction/repair

5

1

6

5.0

Contamination of household plumbing

9

1

10

8.3

Inadequate separation of water main and sewer

1

0

1

0.8

Total

96

24

120



* Community water system
**Non-community water system

Sources of data: Craun and Calderon (2001); Lee et al. (2002).

coliforms were detected in 63 percent of the outbreaks attributed to distribution system
deficiencies or unidentified deficiencies. The authors noted increased sampling for coliform
organisms, above that required for compliance monitoring, may have occurred during the
outbreaks. Coliform-positive water samples were also reported in the several months before an
outbreak in 26 (54 percent) of 48 public water systems with available information, but data were
limited and the authors could not rule out the influence of random error.

Where available, information is provided on coliform sampling and TCR violations for case
studies presented in Section 4.

3. Data Limitations

Certain causes of events are identified more frequently due to the magnitude of their impact
(e.g., on a large number of people), the ease by which they are recognized by consumers and
trigger a response (e.g., taste, odor, or appearance of the water), and/or the conditions under
which they occur (e.g., large scale impact for long term). For an event to be detected through
distribution system monitoring, the monitoring program must include the affected area of the
system at the same time and location that the indicator or contaminant are detectable.

Subsequent investigation of the cause of such an event may be delayed by the time required for
sample analysis, and the circumstances resulting in the initial event may no longer be
detectable.

April 2007

-6-


-------
Data on the causes of distribution system contamination events are limited for several
reasons:

•	Limitations in distribution system monitoring and data interpretation.

•	Limitations with correlating illness to distribution system occurrences.

•	Difficulty with reporting and archiving contamination events.

The effect these limitations have on the availability of historical contamination events data,
and the uncertainty inherent in reported data, is further described below.

3.1	Distribution System Monitoring and Data Interpretation

Most distribution system monitoring for coliform bacteria involves taking samples at
specific times and locations within the distribution system. These samples reflect water quality
at discrete points and times, not on a continuous or universal basis. Craun and Calderon noted
that analysis of water quality data collected during outbreaks indicated most reported
distribution system outbreaks were caused by significant or continuing contamination (Craun
and Calderon, 2001). Contamination events that are of a larger magnitude and longer duration
are more likely to be detected than short-term or intermittent events, such as many distribution
system contamination events. Furthermore, the TCR requires monitoring at points that are
"representative" of the distribution system. Many different interpretations of what is considered
"representative" exist, which results in varying criteria specified by different States. This
presents challenges to the interpretation of the monitoring information on a national basis.

One factor affecting a water system's ability to identify a distribution system contamination
event are the limitations associated with the use of total coliforms as indicators of fecal
contamination to a water distribution system. While the presence of total coliform bacteria in a
water sample may be the direct result of fecal contamination, total coliforms can also originate
from environmental sources (e.g., soil) or from biofilms. Many of these environmental total
coliform species are not known to pose a threat to public health. Total coliforms can also be
present due to a number of contamination pathways such as treatment breakthrough, cross-
connections, and intrusion (Craun and Calderon, 2001). These pathways can introduce fecal
pathogens to the distribution system.

High levels of heterotrophic bacteria can interfere with total coliform analysis in lactose-
based culture methods such as membrane filter (Geldreich et al., 1972). Experimental studies
have also shown that HPC bacteria will out-compete coliform organisms for low levels of
nutrients (LeChevallier and McFeters, 1985).

3.2	Correlating Illness to Distribution System Total Coliform Positive Events

Another issue in identifying contamination events is limitations associated with correlating
an illness to the distribution system. Even if many illnesses result from contamination events, it
is difficult to establish a link between the illnesses and the event because a very small volume of
the distributed water is sampled, and the system would have to monitor in the right place at the
right time. In addition, it is difficult to attribute symptoms of illness to drinking water
contamination. Many other barriers exist in attributing illness to drinking water, such as the

April 2007

-7-


-------
customers not seeking health care and lack of physician reporting results to the health agency.
Unless a confirmed case of illness triggers a report to health agencies (with subsequent
investigative follow-up by the health agencies and the water utility), an incident of
contamination may not be identified. The time interval required for ingestion, development of
symptoms, medical diagnosis and treatment, and investigation of the source of the disease may
be weeks or months. For instance, it can take 14 to 24 days between ingestion and reporting of
an outbreak associated with Cryptosporidium (see Exhibit 3). By the time a water sample is
collected, days or weeks may have lapsed and the contaminant may no longer be present. If
contamination of the distribution system was temporary or intermittent, subsequent
investigative sampling may not identify any contamination or recover the causative agent of
disease. In addition, the illness may be thought to be caused by another source, such as
foodborne contamination or by person-to-person contact. Exhibit 3 presents the numerous steps
that typically occur before a waterborne disease outbreak is recognized.

Exhibit 3. Chronology of Illness Reporting (Adapted from Frost et al., 1996) and
Typical Timeline for Cryptosporidium Outbreak and Reporting (Juranek, 1997)

Typical Timeline for
Cryptosporidium
Outbreak

1 Contaminant enters the distribution system through a pathway

9-14 days

2-3 days

3-7 days

<

Total: 14-24 days

April 2007

2 Does the contaminant reach the customer's tap?

NO

(depends on fate and transport in the distribution system)

CO
LU

>-

NO

3	Does the person seek medical care?

co I

4	Did the physician order the appropriate clinical test?

co I

LLJ I

NO

5 Did the patient comply?

NO

CO
LU
>-

6 Was the laboratory proficient?

NO

co

LU

>¦

NO (False Negative)

7	Was the clinical test positive?

co I

8	Did the physician or laboratory report the results NO
to the health agency?

to I

9	Did the health agency correctly determine that no
drinking water was the probable cause?

to I

10	Did the health agency report the incident and NO
illnesses to CDC?

to I

11	Did CDC find the data sufficient to include in reports?

Illness is NOT
Reported

_r

NO

I

Illness is Reported


-------
Four full-scale epidemiology studies (household intervention studies) designed to measure
endemic waterborne illness demonstrate the difficulties with identifying cases of illness
associated with drinking water and/or distribution system contamination. These studies were
conducted in communities served by surface water systems in the United States, Canada, and
Australia (Payment et al., 1991; Payment et al., 1997; Hellard et al., 2001; Colford et al., 2002).
Each of the household intervention studies measured differences in the incidence of
gastroenteritis symptoms (e.g., diarrhea, vomiting) reported by persons in participating
households that had been randomly assigned to one of a number of different household drinking
water interventions (e.g., point-of-use treatment of tap water) or to the "no treatment" option
(regular tap water, or a placebo treatment device in the case of a blinded study).

Two studies were unable to detect illness attributable to drinking water (Colford et al., 2002;
Hellard et al., 2001). Neither of these studies was designed specifically to differentiate between
illness caused by contamination resulting from inadequacy of water treatment before entry to
the distribution system and contamination originating in the distribution system.

The two studies by Payment et al. (1991 and 1997) indicate gastrointestinal illnesses due to
consumption of tap water may be more common-place than typically recognized. The first study
by Payment et al. (1991) compared the illness patterns among 300 households that drank from
reverse osmosis (RO) point-of-use treatment devices installed at the kitchen tap and 300
households that drank normal tap water. This study was conducted for a 15-month period and
reported a 35 percent lower rate of gastrointestinal illness in the group that drank RO filtered
water than in the group that drank tap water. The rate of gastrointestinal illness was also
compared by zones in the distribution system. People living at the end of the distribution
system had rates of illness twice as high as people living near the treatment plant or close to the
rechlorination sub-station. The authors concluded that the observed excess illness was not
epidemic in nature because the illnesses were distributed throughout the year and not clustered
in specific areas at specific times. They also concluded that sporadic problems at the treatment
plant were not the source of the effect because the excess risk increased, rather than decreased,
with distance from the plant. There was no correlation observed between the incidence of
gastrointestinal symptoms and total or fecal coliforms.

The study by Payment et al. (1997) was conducted in the same community following major
treatment improvements at the treatment plant and higher disinfectant residual entering the
distribution system. The study was comprised of 1400 families who were divided into four
groups. One group drank tap water, one group drank tap water from a continuously purged tap,
one group drank bottled water taken from the treatment plant, and another group drank purified
bottled water (spring water or water treated with RO). It was theorized that the water from the
continuously purged tap would be representative of water in the distribution system. The group
drinking purified bottled water was used as a baseline for comparison. Participants were asked
to keep health diaries and complete questionnaires related to their health and water consumption
for the duration of the study (up to 16 months).

The results of the study showed that among participants drinking regular tap water, 14
percent of gastrointestinal illnesses were attributable to consumption of the tap water. Among
individuals drinking water from the continuously purged tap, 19 percent of gastrointestinal

April 2007

-9-


-------
illnesses were attributable to drinking that water. Incidence rates among children 2 to 5 years
old were higher (up to 40 percent). There was no significant difference in the incidence of
gastrointestinal illness between participants who drank bottled plant water and those that drank
bottled purified water. The significantly higher incidence of illness among participants of both
groups assigned to drinking tap water (compared to the incidence among those assigned to
drinking bottled water) suggests that the distribution system might be the main source of the
observed difference; however, the authors concluded that it was not possible to conclusively
establish the contribution of the distribution system and household plumbing to the observed
higher incidence of illness. The fact that the bottled treated plant water was only collected at
the plant during periods of optimal filtration means the study did not measure the incidence of
drinking water attributable illness during periods when it would have been more prevalent,
thereby underestimating the rate of illness due to treatment deficiencies and overestimating the
risk due to distribution system problems. Also contributing to the higher incidence rate among
those assigned to continuously purged tap group could be higher levels of pathogens in the
distribution system surviving disinfection because of the shorter disinfectant contact time. The
authors conclude that the high rate of illness among participants of the continuously purged tap
group pointed to the distribution system as a major source of the unknown etiologic agents
responsible for the reported illnesses.

The results of the two household intervention studies by Payment et al. (1991 and 1997)
suggest that distribution system contamination may be responsible for a substantial fraction of
endemic waterborne illness, but the authors were not able to quantify the fraction.

3.3 Reporting and Archiving Total Coliform Positive Events

Reporting of waterborne illnesses to CDC is currently voluntary. It is estimated as few as
10 to 30 percent of waterborne disease outbreaks in the United States are reported (Craun and
Calderon, 2001). This under-reporting of waterborne disease outbreaks does not include those
waterborne illnesses that fail to meet the definition of an outbreak, such as endemic illnesses or
waterborne illnesses where an association with water was not established. Therefore,
contamination events within the distribution system may be significantly higher than those
reported and documented. Because the majority of contamination episodes are not reported or
documented, it is difficult to derive a statistically accurate representation of the different types
of contamination events and associated causes.

In addition, there is no existing national database or central archive for reporting or storing
distribution system contamination events. These two factors further limit the availability of
information on distribution system contamination events data.

4. Possible Causes of Total Coliform Occurrence

Similar to other contamination events, the occurrence of total coliform bacteria in the
distribution system requires three factors to be present: a source of total coliform bacteria; a
pathway into the distribution system or a breach in the system's physical integrity; and a
mechanism that allows the bacteria to be carried on this pathway into the distribution system.
For example, a cross connection is a pathway whereby a piping connection exists between a

April 2007

- 10-


-------
private water system and the public water system. Backflow through this cross connection is
the mechanism that allows untreated water containing the bacteria to enter the water distribution
system. As stated in Section 1.1, this paper does not address water treatment breakthrough as a
mechanism for total coliform occurrence. The paper also does not include total coliform
occurrence from untreated source waters. Although there are often multiple causes to total
coliform positive events, in the following sections, case study examples are organized according
to their primary cause.

4.1 Sources of Total Coliform Bacteria

Reported sources of total coliform bacteria in the distribution system include the following:

•	Soil and Water Surrounding Pipes

•	Biofilms and Microbial Growth

•	Corrosion Tubercles

•	Weather-Related Events

•	Customer Connections

•	Materials Added to the Distribution System

•	Sediments

4.1.1 Soil and Water Surrounding Pipes

A list of potential sources of microbiological contamination at water main repair sites was
compiled by Pierson et al. (2001). Prior to the repair, contaminant sources may include
soil/sediment; animal or human waste; dead animals; unsanitary human contact; incidental dirty
water; or trash. During the repair, contaminant sources may include soil/sediment; animal
wastes; unsanitary human contact; groundwater or sewage in the repair trench; or agricultural
runoff in trench.

Besner et al. (2005) studied the occurrence of microbial intrusion into distribution systems
by collecting and analyzing soil and water samples at water main repair sites, customer houses
and adjacent hydrants. For example, at one repair site, microbiological analyses conducted on
soil and water samples detected aerobic spore formers, actinomycetes, total coliforms, and
Clostridium perfringens, an indicator of fecal contamination. After the repair was complete, the
water main was flushed from a nearby hydrant. Microbiological analyses of the flushed water
detected aerobic spore forming bacteria, E. coli, total coliforms, and actinomycetes. This repair
site was the only one of 14 repair sites where E. coli was detected in the flushed water. No
positive samples were collected from customer houses after flushing was complete.

Besner et al. (2004) also studied possible sources of microbiological contamination at water
main repair sites. Of nine soil samples and six water samples collected from the immediate
vicinity of excavated mains, E. coli was detected in one soil sample but the water sample from
that repair site was too dirty to allow analysis. Clostridium perfringens was detected in two of
the six water samples and three of the nine soil samples.

April 2007

- 11 -


-------
Kirmeyer et al. (2001) conducted microbial analyses of soil and water samples at water
main repair sites and found evidence of fecal pollution. Total coliforms were detected in 58
percent of water samples and 70 percent of soil samples. Fecal coliforms were detected in 43
percent of water samples and 50 percent of soil samples. A total of 65 samples were collected
(32 water samples and 33 soil samples) from eight utilities in six states.

When pipes are stored at the construction site without protective caps, they are easily
contaminated with dirt, mud, debris, and dirty water. These conditions may lead to water
quality problems such as high turbidity, high heterotrophic bacteria counts, and coliform
bacteria occurrence (Korntreger and O'Donnell 1998). As reported by Haas et al. (1998),

"Clark et al. (1982) used coliform tests to evaluate new mains for bacterial
contamination. They found that new mains contained species of Enterobacter,
Klebsiella, Escherichia, and Citrobacter as well as Aeromonas hydrophila, an
opportunistic pathogen.. .Citrobacterfreundii is commonly found in soil and
suggests the soil contamination of new mains."

Besner et al. (2005) also identified a possible source of bacteria during a main repair when a
replacement valve was placed onto fecally-contaminated soil and installed without proper
disinfection.

As reported in Haas et al. (1998), Harris (1959) investigated the bacterial loading of
trenches and found the largest bacterial densities in trench bottoms next to existing pipe.

"Moisture content increased bacterial counts substantially (up to 100-fold).

Thus, damp soil near a leaking main is a potential source of massive bacterial
contamination during repairs. (Haas et al. 1998)"

In Cabool, Missouri, from 1989-1990, E. coli 0157: H7 were introduced at or near the sites
of two large water main breaks and numerous service meter breaks. The water main and service
meter breaks were attributed to extremely cold weather. Sewage overflow from manholes of a
nearby deteriorating sewer collection system during heavy rains was thought to be the source of
contamination (Geldreich et al., 1992).

4.1.2 Biofilms and Microbial Growth

Biofilms are defined as a complex mixture of microbes, organic, and inorganic material
accumulated amidst a microbially-produced organic polymer matrix attached to the inner
surface of the distribution system (USEPA, 2002). Contaminants, including total coliforms and
some pathogens, may attach to or become enmeshed in biofilms on pipe walls in distribution
systems. Many pathogens have been found to survive and sometimes increase in number in
these pipe biofilms where they are protected from disinfectants. Over time, these pathogens
may detach or slough from biofilms, causing persistent detections and even waterborne disease.
Biofilm can result in total coliform-positive and other contamination events if disturbed, such as
during a sudden change in flow. More detailed background information is provided in the
USEPA (2002) white paper including the potential public health risks of biofilms,

April 2007

- 12-


-------
characteristics of specific microbes, and factors that influence pathogen survival and growth.
The following case study gives a specific example of coliform occurrence linked to biofilms.

Biofilms on gate valves with rubber-coated wedges were identified as a cause of coliform
contamination of drinking water without disinfectant residual (Bendinger et al., 2004).
Coliforms were detected in water samples 12 months after new piping was installed. Nine gate
valves were removed from this piping and examined. On visual inspection, all rubber-coated
wedges were covered by excessive biofilms. Bacterial testing found coliform bacteria on all
rubber surfaces but no E. coli. Since coliforms of the same species were found in the drinking
water and the rubber surfaces, it was assumed that the coliform bacteria entered the drinking
water from the biofilm.

4.1.3	Corrosion Tubercles

Friedman et al. (2003) summarized technical literature documenting cases of coliform
bacteria present within corrosion tubercles. LeChevallier et al. (1987) identified E. coli within
tubercles collected from bituminous-coated, cement-lined cast iron pipe. Emde et al. (1992)
found that total coliforms were present in greater numbers in corrosion deposits than in the
untreated water supply. The authors examined corrosion tubercles from exhumed pipes and
found 22 types of bacteria, including coli and Klebsiella spp.

4.1.4	Weather-Related Events

A range of different weather-related events can contribute to the occurrence of total
coliforms, and sometimes fecal indicators, in drinking water distribution systems. In some
cases, the indicators may increase in the source waters, while in other cases they may enter the
distribution system more directly. The types of weather-related events that have been
contributed to indicator positive samples include significant rainfall events, droughts, and
excessively warm or cold weather. Significant rainfall was suggested as a possible cause of
total coliform positive samples in Bristol, Connecticut in 2005 (The Bristol Press, 2005), and
Yamhill County, Oregon in 2006 (Oregon Department of Health Services, 2006). Snowmelt
was suggested as a possible cause of total coliform positive samples in East Providence, Rhode
Island in 2003 (East Bay Newspapers, 2003) and in White Lake Township, Michigan in 2005
(The Daily Oakland Press, 2005), as well as the possible cause of E. coli occurrence in Lisbon,
New Hampshire in 2005 (Littleton Courier, 2005). High temperatures may have also
contributed to total coliform positive samples in Rockdale County Georgia in 2003 (Gwinnett
Daily Post, 2003).

4.1.5	Customer Connections

Customer connections can be the source of total coliform bacteria when a backflow
event has occurred. In Norridgewock, Maine in 1991 backsiphonage from a failure of a
restaurant's septic system led to the presence of total and fecal coliforms (EPA Region 1, 1991).
Coliform bacteria were also detected in samples in Goodyear, Arizona in 1988. The suspected
cause was backflow contamination from a construction site (EPA Region 9, 1988). In April

April 2007

- 13 -


-------
1991 in San Antonio, Texas, total coliform bacteria entered the distribution system from a
heating and cooling system in an Air Force base (EPA Region 9, 1991).

4.1.6	Materials Added to the Distribution System

In some instances materials added to the distribution system can result in the presence of
total coliforms. These can result from the materials themselves being contaminated, and from
materials that can support the growth of coliforms by providing nutrients for microbial growth.
E. coli contamination was detected in the Woodburn, Oregon drinking water supply in 2005.
Contamination due to construction activity was mentioned as one possible cause (Statesman
Journal, 2005). Similarly, construction activity was mentioned as a possible cause of total
coliform contamination of the Lacey, Washington distribution system in 2004 (The Olympian,
2004). Some construction materials, such as rubber, silicon, polyvinyl chloride, and bituminous
coatings can stimulate microbial growth (USEPA, 1992).

4.1.7	Sediments

Sediment accumulation can provide a habitat for microbial growth in a distribution
system (USEPA, 1992). Furthermore, the sediments can provide the microbes protection from
disinfectants. Besner et al. (2001) identified sediment accumulation in a low-flow main as a
possible source of total coliforms in a sampling point on "B Street" in the Montreal distribution
system.

4.2 Pathways for Total Coliform Bacteria to Enter Distribution Systems

This section focuses on the pathways that allow contaminants to enter the distribution
system from the sources described in Section 4.1. According to the National Academy of
Sciences report Drinking Water Distribution Systems: Assessing and Reducing Risks, physical
integrity determines: ".. .the ability of the distribution system to act as a physical barrier that
prevents external contamination from affecting the quality of the internal, drinking water
supply." (National Research Council, 2006). Total coliforms and pathogens can be introduced
to the distribution system through a variety of pathways, including:

•	Finished Water Storage Facilities

•	Cross Connections and Backflow

•	Intrusion and Main Breaks

•	Treatment Breakthrough

Kirmeyer et al., 2001 also held an expert panel workshop to prioritize the pathogen routes of
entry into distribution systems that had been identified in a literature review. High priority
pathways included cross connections, water main repair sites, and transitory contamination due
to pressure transients. Uncovered storage facilities were classified as a medium priority
pathway. Covered storage facilities and bacteria growth/resuspension were considered low
priority pathways.

April 2007

- 14-


-------
These pathways are described in more detail in the following section using case study
examples. Further background information can be found in the distribution system white papers
(http://www.epa.gov/safewater/disinfection/tcr/regulation revisions.html).

4.2.1 Finished Water Storage Facilities

Storage tank deficiencies, such as vents without screens, inadequate hatches, access hatches
that are not locked, physical openings in storage tank roofs, and lack of a cover, can result in the
entry of contaminants. Microorganisms can also be introduced into ground storage facilities
from surface water or groundwater infiltration or runoff.

"Although they may suffer from structural failures, storage facilities are most
susceptible to external contamination due to the absence or failure of an essential
component, such as a cover, vent, hatch, etc. The complete absence of a cover or
vent on a storage facility can allow birds access to the tank and subsequently
introduce microbial pathogens such as bacteria..(National Research Council
2006)"

A finished water storage facility was identified as the pathway for Salmonella typhimurium
that caused a community outbreak of salmonellosis in Gideon, Missouri, in 1993 (Clark et al.,
1994). It was estimated that the outbreak caused 650 people to become ill and caused seven
deaths. The system's covered storage tanks were not properly maintained and holes in the roof
of one tank allowed bird droppings and feathers to enter. Pigeons were found roosting on the
tanks. S. typhimurium was detected in the sediment from one of the storage tanks. The
sediment was upset when the water in the storage tank became unstratified due to temperature
changes. Subsequent flushing performed in response to taste and odor complaints carried the
sediment throughout the distribution system. The system did not have full-time chlorination
when the outbreak occurred, but installed full-time chlorination shortly after the outbreak.
Routine TCR monitoring did not indicate a problem, but water samples collected after the
system became aware of the outbreak were positive for fecal coliforms.

From January 1991 through May 1994, the Missouri Department of Natural Resources
(MDNR) found that 18 of 51 (35 percent) boil water orders in water systems with elevated tanks
were due to contamination of the tanks. Deficiencies noted included defects in the hatch, vent,
overflow, and in the joint between the wall and roof overhang, and holes that tank painting
contractors did not repair subsequent to hanging internal rigging (Atkinson, 1995). Birds and
related debris were identified as the contaminants. The boil water orders were triggered by
detection of fecal coliform-positive water samples and acute MCL violations. The MDNR was
also aware of an additional 15 situations where an acute MCL violation did not occur despite
subsequent discovery of contamination in the tanks. MDNR theorized that full-time
disinfection of the water supplies might have masked the presence of fecal coliforms in the
contaminated tanks.

An acute TCR violation caused by E. coli contamination of the Point Evans, Washington
water system in November 2003 was attributed to a storage tank. A system inspection showed
no signs of vandalism or unauthorized entry, but heavy rains may have caused water that

April 2007

- 15 -


-------
normally runs safely off the roof of one tank to seep into a second tank near an overflow vent,
according to a water company bulletin (Sherman, 2004). The hatch was found to have a
deficient seal, possibly serving as an entry point for contaminants. The system did not practice
full-time disinfection at the time of this event (Ryding, 2004). The Washington Department of
Health issued a boil order.

In 1995, a water district in Maine traced a total coliform bacteria occurrence in the
distribution system to two old steel tanks with wooden roofs (Hunt, 2002). Inspection of the
tanks revealed missing roof shingles and large gaps in the tank roofs were present. The tanks
were drained and an interior inspection found two feet of accumulated sediment, widespread
coating failure on the tank sidewalls, and evidence of human entry. The tanks were cleaned and
the distribution system was flushed and disinfected. A boil water order was in place until
system water quality was restored.

Finished water reservoirs with floating covers may become contaminated if the cover is
damaged; allowing accumulated untreated water on the cover to mix with the finished water. At
Philadelphia's Oak Lane Reservoir, surface water collected on the floating cover was found to
contain fecal coliform bacteria counts as high as 13,000 per mL (Kirmeyer et al., 1999).

Although the City of Woodburn, Oregon could not definitively determine the cause of the E.
coli found in one sample at the new Parr Road reservoir in May 2005, several small holes were
found around seals and wire entry points on the reservoir's cathodic protection system and the
reservoir exhaust system (http://www.ci.woodburn.or.us/publicworks/water/CCR%20-
%202005%20-Eng.pdf). On the same day, a sample from the country club reservoir tested
positive for total coliform bacteria. Further testing resulted in three positive total coliform
samples which triggered a boil-water advisory.

A city in Massachusetts detected fecal coliform bacteria in several samples at one of their
six finished water storage facilities (Correia, 2002). The tank inspector discovered an open
access hatch and other signs of vandalism on one of the tanks. This tank was drained and
cleaned to remove several inches of accumulated sediment. Three other finished water storage
facilities were cleaned in 2001 without being drained and removed from service. The tank
closest to the filtration plant was found to contain two to three inches of sediment and the tanks
in outlying areas contained four to six inches of sediment. Shortly after the tanks were cleaned,
the city experienced widespread total coliform occurrences in the distribution system. The
city's immediate response was to boost the free chlorine residual in the distribution system and
tank outlets to 4.0 mg/L. Also, the distribution system was flushed continuously for two days to
remove contaminated water. These measures resolved the coliform bacteria problem. A boil
order was not required. (Friedman et al., 2002b.)

4.2.2 Cross Connections

A cross connection can be defined as "any unprotected actual or potential connection or
structural arrangement between a public or private potable water system, and any other source
or system through which it is possible to introduce into any part of the potable water system any
used water, industrial fluids, gas, or substance other than the intended potable water with which

April 2007

- 16-


-------
the potable system is supplied" (USC-FCCCHR, 1993). Some common examples of cross
connections include potable water system connections to industrial or commercial processes,
carbon dioxide beverage dispensers, a leaking hydrant foot valve, garden hose sprayers, cooling
systems, irrigation systems and fire sprinkler systems.

The EPA Distribution System White Paper (http://www.epa.gov/safewater/tcr/pdf/ccrwhite.pdf)
provides additional background information on cross connections and possible health impacts.
Two case studies that link total coliform or E. coli occurrence to a cross connection are
summarized below.

A cross connection was determined to be the probable cause of an E. coli outbreak in
August, 2000, at a county fair in Ohio (Lee et al., 2002). Twenty-nine persons who had
attended the county fair had confirmed cases of E. coli. Consumption of food and beverages
purchased from vendors within a particular area of the fairgrounds was found to be a substantial
risk factor. An investigation found a cross-connection between the branch of the water
distribution system supplying those vendors and an animal show barn. Spigots connecting
hoses to both the animal areas and the concession stands did not have backflow prevention
devices. Backsiphonage from the hoses in the animal areas was determined to be the probable
cause of the outbreak.

In June 2001, an employee of the Mauriceville Special Utility District in Texas incorrectly
assumed that a discolored water line was a sewer line and connected a sewer line to it (U.S.
Water News Online, 2001). As a result, sewage contaminated the drinking water supply for
about 20 days before customer complaints about particles in the water prompted the utility
district to conduct sampling. The samples came back positive for fecal coliform bacteria and
resulted in an acute TCR violation. About 2,000 customers were affected by the contamination
and had to boil their drinking water or use bottled water.

4.2.3 Intrusion and Main Breaks

Intrusions through leaks, as well as main breaks, can provide a pathway for contaminants
outside of the pipe to enter the distribution system during low and negative pressure events.
Points through which intrusions can occur also include pipeline fracture cracks, leaking joints,
leaking adapters and deteriorating seals (Kirmeyer et al., 2001).

On March 28, 2004, a boil-water advisory was issued for residents of a seven-block section
of Pacific, Missouri after a water distribution system sample tested positive for coliform
bacteria, resulting in a TCR violation (Masson 2004). The sample tested negative for E. coli.
The contamination was suspected to be related to a recent water main break. Another sample
taken three days earlier had tested negative for bacteria, but was reported to have an odd smell.
This prompted water system personnel to test additional samples from that area, including the
sample in which the unknown bacteria were found. As a precaution, the water system crews
also opened three fire hydrants to flush the affected area of the distribution system.

Besner et al. (2001) identified that the source of total coliform bacteria for a sampling point
on "B Street" in the Montreal distribution system was likely due to a series of water main
breaks on a nearby 14-inch main. The authors also showed that flow reversals in summer

April 2007

- 17-


-------
months could bring water containing low chlorine residual past this 14-inch main toward the
sampling point.

In the Cabool, Missouri outbreak, Swerdlow et al. hypothesized a "pocket" of contamination
may have been able to enter the distribution system during main and service meter breaks or on
a long-term, minor flow rate basis (through seepage into the system) (Swerdlow et al., 1992,
Craun et al., 2001). Hyperchlorination was not part of the main repair process or of meter
replacements. The water system also did not use full-time disinfection. Routine coliform
monitoring did not indicate a problem and the water system did not have any coliform
violations during this time period. This outbreak resulted in four deaths, 32 hospitalizations, and
a total of 243 documented cases of diarrhea.

4.2.4 Treatment Breakthrough

One current objective of total coliform monitoring is to indicate the effectiveness of
treatment. Therefore, total coliforms have broken through the treatment barriers; they may be
detected in samples collected in the distribution system. Failure of the treatment barrier was
noted in Aurora, Illinois when elevated levels of ammonia decreased the ability of chlorine to
disinfect. E. coli was detected in the distribution system (City of Aurora, 2004). Mechanical
problems at a water treatment plant led a water plant in Bandon, Oregon to distribute water
potentially containing fecal coliforms and E. coli from the source water in 2005
(theWorldlink.com, 2006). Low chlorine levels were a possible contributor to the detection of
E. coli in Warren County, Mississippi in 2007 (Vicksburg Post, 2007). In addition, even in
systems that provide treatment and are in compliance, the distributed water is not sterile. As
such, some total coliforms have the potential to enter the distribution system, even in well-
treated systems.

4.3 Mechanisms that Allow Total Coliform Bacteria to Enter or Proliferate in
Distribution Systems

This section addresses the driving forces that may allow for total coliforms or fecal
indicators to enter or proliferate in a distribution system if a source of contaminants and/or a
pathway exist. The mechanisms discussed in the paper are:

•	Hydraulic Conditions

•	Operations

•	Maintenance Practices

•	Retention Times

•	Presence of Nutrients

4.3.1 Hydraulic Conditions

The operating pressure in a water distribution system fluctuates over time and location,
depending on several factors such as pipe elevation, operating setpoints for booster pumps and
system valves, storage tank water levels, and water demand variations. Pressure losses can
occur in the distribution system as a result of certain events including flushing, main breaks,

April 2007

- 18 -


-------
power outages, service line breaks, and fire events (ABPA 2000). Pressure transients (also
called pressure surges or water hammer) can occur when an abrupt change in water velocity
occurs, due to a sudden valve closure, pump shutdown, or loss of power (Friedman et al. 2004).
The resulting pressure wave, with alternating low and high pressures, travels back and forth
through the distribution system until the pressure is stabilized.

LeChevallier et al. (2002) and Friedman et al. (2004) have documented occurrences of low
and negative pressures within distribution systems during transient pressure events. Many of
the causes of pressure transients are a part of regular water distribution system operations and
therefore, pressure transients may occur frequently in certain water distribution systems, as
demonstrated by Friedman et al. (2004). Further information on pressure transients are
discussed in the Distribution System White Paper
(http://www.epa.gov/safewater/tcr/pdf/intrusion.pdf).

Besner et al. (2002) summarized an investigation by McMath and Casey (2000) who
measured subatmospheric pressures at one distribution system point during surges. This point
was an air valve chamber that flooded with dirty water during wet weather. The authors
identified intrusion of dirty water through the air valve chamber during low pressure conditions
as a possible cause of the high coliform detection rate in distribution system water samples
collected near this point.

Contaminant intrusion may occur if a very low or negative pressure occurs within the pipe
at a leakage point or other gap in the piping system where the external pressure is higher
(LeChevallier et al., 2002). One example of high water pressure external to the pipe is a high
ground water table. A source of contaminants in the soil and water outside the pipe must also
be present to allow contaminant intrusion to occur.

Low pressure conditions in the distribution system can allow a flow reversal or backflow of
non-potable water to enter the system from a cross connection or other source. Backflow can
also occur when an outside source is pressurized by air or gas, creating a higher pressure in the
outside source than in the distribution system. From 1971 through 1998,

"... chemical and microbial contamination from cross-connections and
backsiphonage were responsible for most distribution system outbreaks.

Outbreaks could be traced to backflow prevention devices that were needed but
not installed, had been inappropriately installed, or had been inadequately
maintained (Craun and Calderon, 2001)."

For example, in July 1997, 123 persons who had visited a New Mexico country club became
ill with gastroenteritis. E. coli 086:H11 was isolated from 11 ill individuals and Giardia was
isolated from one ill individual (Barwick et al., 2000). A heavy rainstorm caused a power
outage at the country club two weeks before the gastroenteritis outbreak. It is believed that
during the power outage, contaminated water may have siphoned back into the country club's
water system due to low pressures. No backflow prevention device was present (Craun and
Calderon, 2001).

April 2007

- 19-


-------
Pressure transients can also create hydraulic disturbances that allow biofilm material on pipe
surfaces or sediments to enter the bulk water. This phenomenon was observed during a major
fire in a Texas city (Geldreich, 1996). The water demand for fire fighting resulted in reduced
pressure in the water line. After the fire hydrant valve was closed and normal pressures were
being restored in the water line, a significant water hammer was created in the pipe. Biofilm
shearing occurred that released 125 to 200 Pseudomonas aeruginosa per milliliter to the
finished water over a 24-hour period before subsiding to non-detectable levels.

4.3.2	Operations

If the distribution system is fed by multiple sources with varying water quality, the release
of biofilms, scales, or sediments may occur at the interface between the sources. The City of
Tulsa, Oklahoma, derives its water from two major surface water supplies that are located at
opposite ends of the distribution system, creating three water quality zones: one for each plant
and one at the interface zone in the distribution system where water from each plant mixes. For
two years, the majority of positive coliform samples have occurred at the interface between the
two treated waters in the distribution system (Kirmeyer et al., 2000). Although coliform data
appeared to be linked to the interface area, the city was uncertain of the cause. Red or brownish
water complaints were occurring at the interface, but subsided when the city held the production
ratio near constant at each facility. The fluctuations in production likely caused loosening or
dissolution of scale material due to changing water quality in the interface zone. Water quality
changes consisted primarily of an increase in conductivity that may have resulted from low-
flow conditions within the interface zone.

4.3.3	Maintenance Practices

Water main flushing and cleaning are routine maintenance practices often conducted within
the distribution system. Line cleaning methods include air and water scouring, swabbing,
pigging, and chemical and mechanical cleaning. Flushing and line cleaning practices can affect
the distribution system water quality in a negative manner if not conducted properly. Improper
flushing can result in moving a contaminant further into the distribution system.

Loose deposits are susceptible to entrainment and suspension under normal hydraulic
scenarios, such as flow reversals and velocity changes (Friedman et al., 2003). Sudden flow
increases (USEPA, 1992) or hydraulic disturbances (Characklis, 1988) can cause accumulated
biofilm, scales, sediment, or tubercles to shear or slough, resulting in release to the water
column. These disturbances can occur due to many factors, including flushing operations.

Flushing and disinfection following water main repair may not be sufficient to remove
sources of contamination. Besner et al. (2004) investigated total coliform occurrence associated
with water main repair sites. After repairs were complete, coliform were detected in flushed
water samples and house samples collected near three repair sites. The authors hypothesized
that increased water velocity in the main during flushing led to biofilm sloughing or sediment
resuspension that contained coliforms. LeChevallier (1999) noted that the flushing velocity
used in a repaired main is often too low to remove contaminants. Gauthier et al. (2001)

April 2007

-20-


-------
illustrated how coliform bacteria counts at the "B Street" sampling point in the Montreal
distribution system increased after it was flushed, drawing water from the 14-inch main.

Besner et al. (2002a) identified distribution system work, including pipe flushing, valve
operations, hydrant operations and low distribution system pressures, as highly probable causes
of 15 positive total coliform samples in the Laval, Quebec system. Seven samples were
collected from two sampling points in the same pressure zones where unidirectional flushing
was performed during the same time period. Five samples collected from three sampling points
were linked to localized low distribution system pressures that were related to construction
work. Two samples were collected from a sampling point near the construction work after three
valves were operated, causing flow reversals and low pressure conditions. One sample was
linked to nearby hydrant operations that may have caused hydraulic disturbances such as
sediment resuspension.

Mechanical cleaning and relining of pipes, as well as new main installation were identified
as possible causes of a total coliform occurrence in the Moncton, New Brunswick distribution
system (Besner et al., 2003). The authors used customer complaint calls and turbidity data for
distribution system samples to establish approximate dates for distribution system maintenance
work since maintenance records were not available. A positive coliform sample was obtained
in the vicinity of this work during the same time period.

Incomplete curing of new paint and residual solvents leaching from the paint caused
biological growth on interior surfaces of two finished water standpipes at Lakehaven Utility
District (Kirmeyer et al., 2000). Visual inspection of the tank interiors revealed an extreme
microbial growth and slimy surfaces. During the fall of 1989, these tanks had been cleaned,
painted, and disinfected prior to returning to service. During the first eight months following
the painting, only one incident of coliform bacteria was detected from tank water samples, but
HPC levels began to show an increase. Customer complaints of a strange musty and fishy odor
in their water also began to occur during this time period. On five occasions, the tanks were
taken off-line and shock-chlorinated only to have a substantial increase in heterotrophic bacteria
return within a short period. Historically, samples collected from these tanks produced HPCs
levels in the range of 1 to 50 colony forming units (CFU)/mL. During the eight-month time
period, samples from the tanks produced HPC levels in the range of 0 CFU/mL (after shock-
chlorination) to 4,300 CFU/mL within about a four-week period.

4.3.4 Retention Time

Long retention time in the distribution system can reduce the water's disinfectant residual
and allows the deposition and accumulation of sediment. Stagnant water can occur in dead-end
pipes, fire protection storage tanks or finished water storage facilities that are over-sized or have
periods of limited use. Stagnant water provides an opportunity for suspended particulates to
settle into pipe sediments, for biofilm to develop, and for biologically mediated corrosion to
accelerate (Brandt et al., 2004). An EPA Distribution System White Paper discusses
(http://www.epa.gov/safewater/tcr/pdf/waterage.pdf) the effects of water age on distribution
system water quality.

April 2007

-21 -


-------
Gauthier et al. (2001) identified a possible cause of a total coliform occurrence in a
distribution system with a retention time issue. The authors studied total coliform occurrences
in a portion of the Montreal, Quebec, Canada distribution system to evaluate possible causes.
For the 1997 to 2000 period, total coliform occurrence at one sampling point was thought to be
initially caused by closure of a valve between two pressure zones that created dead-end
conditions near the sampling point. After the valve closure, the water's chlorine residual
dropped immediately to zero and total coliforms were detected one month later.

4.3.5 Presence of Nutrients

Some materials or system operations can introduce nutrients to the distribution system that
may support growth of total coliform bacteria. For instance, if proper lubricants are not used in
pumps, microbial growth may be supported. Also, some treatment operations (e.g., ozonation,
chlorination) may lead to the production of available nutrients that may support growth. The
effects of nutrients are described in more detail in the EPA paper on biofilms (USEPA, 2002).
and on treatment and nutrients (USEPA, 2006).

5. Summary

The purpose of this paper is to review existing literature, research, and information on
public water supply distribution system occurrences of total coliform bacteria and the
circumstances and deficiencies identified as having caused those events. Total coliform
bacteria may be present in the distribution system if three conditions simultaneously occur: a
source of total coliform bacteria; a pathway into the distribution system; and a mechanism that
allows the bacteria to be carried on this pathway into the distribution system or that allows
bacteria within biofilms, corrosion tubercles or sediment to enter the water.

Sources of total coliform bacteria include the following:

•	Soil and Water Surrounding Pipes

•	Biofilms and Microbial Growth

•	Corrosion Tubercles

•	Weather-Related Events

•	Customer Connections

•	Materials Added to the Distribution System

•	Sediments

Pathways through which total coliform bacteria can enter the distribution system include the
following:

•	Finished Water Storage Facilities

•	Cross Connections and Backflow

•	Intrusion and Main Breaks

•	Treatment Breakthrough

April 2007

-22-


-------
Mechanisms that allow coliform bacteria to enter the distribution system (assuming a source
of contaminants and a pathway are present) or that allow bacteria to proliferate in the
distribution system include the following:

•	Hydraulic Conditions

•	Operations

•	Maintenance Practices

•	Retention Times

•	Presence of Nutrients

April 2007

-23 -


-------
6. References

ABPA. 2000. 2000 Survey of State and Public Water System Cross-Connection Control
Programs.

Arnold, H. 2003. College, County Seek Source of Water Contamination. October 12, 2003.
Daily Freeman, Kingston, NY.

Atkinson, R. A Matter of Public Health: Contamination of Water Storage Tanks. Missouri
Municipal Review. June, 1995. Pgs 22-23.

Aurora, City of. 2004. Important Information about Your Drinking Water: February Tests
ShowedE. coli and Total Coliform Bacteria in Aurora Water. March, 5, 2004.

AWWA. 1999. Water Quality and Treatment, Fifth Edition. McGraw Hill. New York, NY.

AWWAPNWS. 1995. AWWA Pacific Northwest Section. 1995. Summary ofBackflow
Incidents, Fourth Edition. December, 1995.

Bach, A. 2003. Issaquah to Add Chlorine After Cases of Coliform Keep Showing Up. November
18, 2003. Seattle, WA: The Seattle Times.

Barwick, R., D. Levy, G. Craun, M. Beach, R. Calderon. 2000. Surveillance for Waterborne-
Disease Outbreaks - United States, 1997-1998. Morbidity and Mortality Weekly Rept., 49:(SS-
4):l-36.

Bendinger, B., B. Schultheis, and I. Wagner. 2004. Biofilms on Rubber Material as Cause of
Coliform Contamination of Drinking Water. In Proc. of the AWWA WQTC Conference. Denver,
Colo.: AWWA.

Berend, K. and T. Trouwborst. 1999. Cement-Mortar Pipes as a Source of Aluminum. Journal
AWWA, 91(7):91-100.

Besner, M.-C., C. Cartier, C. Morissette, A. Aubin, P. Payment, and M. Prevost. 2005. Water
Quality Variations During Repairs of Pipe Leaks. In Proc. of the AWWA WQTC Conference.
Denver, Colo.: AWWA.

Besner, M.-C., C. Cartier, C. Morissette, B. Karney, P. Payment, and M. Prevost. 2004. Do
Routine Distribution System Operations Have an Impact on Water Quality? In Proc. of the
AWWA WQTC Conference. Denver, Colo.: AWWA.

Besner, M-C., V. Gauthier, B. Barbeau, R. Millette, R. Chapleau, and M. Prevost. 2001.
Understanding Distribution System Water Quality. JAWWA, 93(7): 101-114.

April 2007

-24-


-------
Besner, M-C., V. Gauthier, C. Morissette, and M. Prevost. 2002a. Identification of the Main
Causes of Total Coliforms in a Distribution System. In Proc. of the AWWA WQTC Conference.
Denver, Colo.: AWWA.

Besner, M-C., V. Gauthier, P. Servais, and A. Camper. 2002b. Explaining the Occurrence of
Coliforms in Distribution Systems. Journal AWWA, 94:8:95-109.

Besner, M-C., V. Gauthier, M. Trepanier, E. Nicholson, and R. Desjardins. 2003. Study of Water
Quality Variations in the Moncton (New Brunswick) Distribution System Using an Integrated
Approach. In Proc. of the 8th Environmental and Sustainable Engineering Specialty Conference
of the Canadian Society for Civil Engineering.

Bluemink, E. 2004. Official: Radium Settling in Pipes. Pensacola News Journal. March 12, 2004.

Brandt, M., J. Clement, J. Powell, R. Casey, D. Holt, N. Harris, and C. Ta. 2004. Managing
Distribution Retention Time to Improve Water Quality - Phase I. AWWARF. Denver, CO.

Bristol Press. 2005. City Looks to Lift 'No Drink' Order. Bristol, Connecticut. September 24,
2005.

Carter, C., M. Cohen, and A. Hilliard. 2001. Detective Story: The Airborne Solvent that
Contaminated a Water Supply. Opflow, 27(9): 8-10, 21.

Characklis, W. 1988. Bacterial Regrowth in Distribution Systems. AWWARF. Denver, CO.

Clark, R., E. Geldreich, K. Fox, E. Rice, C. Johnson, J. Goodrich, and J. Barnick. 1994. A
Waterborne Salmonella serovar typhimurium Outbreak in Gideon, Missouri: Results from a Field
Investigation. US EPA. Cincinnati, Ohio.

Colford Jr., J., J. Rees, T. Wade, A. Khalakdina, J.Filton, I. Ergas, S. Burns, A. Benker, C. Ma,
C. Bowen, D. Mills, D. Vugia, D. Juranek, and D. Levy. 2002. Participant Blinding and
Gastrointestinal Illness in a Randomized, Controlled Trial of an In-Home Drinking Water
Intervention. Emerging Infectious Diseases, 8:1.

Correia, L. 2002. City of Fall River, Massachusetts. Personal Communications.

Craun, G. F., P. S. Berger, and R. L. Calderon. 1997. Coliform Bacteria and Waterborne Disease
Outbreaks. Journal AWWA 89 (3):96-104.

Craun, G., and R. Calderon, 2001. Waterborne Disease Outbreaks Caused by Distribution
System Deficiencies. Journal AWWA, 93:9:64-75.

Crozes, G. F., and R. S. Cushing. 2000. Evaluating Biological Regrowth in Distribution Systems.
Water Quality Technology Conference. Denver, CO.

April 2007

-25 -


-------
Current, W. 1986. Cryptosporidium: Its biology and potential for environmental transmission.
Crit. Rev. in Env. Control. 17:1:21-51.

Daily Oakland Press. 2005. District Trying to Solve Water Contamination Problem. January
29, 2005.

Deb, A., F. Grablutz, Y. Hasit, and K. Momberger. 2000. Guidance for Management of
Distribution System Operation and Maintenance. AWWARF. Denver, CO.

DWI0772. December 1997. Permeation of Benzene, Trichloroethene and Tetrachlorethene
through Plastic Pipes: An Assessment for Drinking Water Inspectorate. FWR.

East Bay Newspapers. 2003. East Providence Calls Drinking Water Safe After Two E. coli
Scares. February, 2003.

Edberg, S. C., J. E. Patterson, and D. B. Smith. 1994. Differentiation of Distribution Systems,
Source Water and Clinical Coliforms by DNA Analysis. Journal of Clinical Microbiology 32(1):
139-142.

Emde, K.M., D.W. Smith, and R. Facey. 1992. Initial Investigation of Microbially Influenced
Corrosion (MIC) in a Low Temperature Water Distribution System. Water Research, 26(2): 169-
175.

Fayer, R., and B. Ungar. 1986. Cryptosporidium spp. and cryptosporidiosis. Microbial Review.
50(4):458-483.

Field, W., E. Fisher, R. Valentin, and B. Kross. 1995. Radium-Bearing Pipe Scale Deposits:
Implications for National Waterborne Radon Sampling Methods. American Journal of Public
Health, 85:4:567.

Flemming, H. and G. Geesey, editors. 1990. Biofouling and Biocorrosion in Industrial Water
Systems. Springer Verlag. New York.

Flournoy, R., D. Monroe, N. Chestnut, and V. Kumar. 1999. Health Effects from Vinyl Chloride
Monomer Leaching from pre-1977 PVC Pipe. 1999 AWWA Annual Conference Proceedings.

Flicker, C.R., M. Pryor, R.M. Powell, D. Mooren, and P. Warden. 2006. Investigating the source
of coliforms in Water Distribution Systems. In Proc. Of the AWWA Annual Conference. Denver,
Colo.: AWWA.

Friedman, M., A. Hill, and S. Via. 2002a. Permeation and Leaching.
http://www.epa.gov/safewater/tcr/pdf/permleach.pdf

Friedman, M., K. Martel, A. Hill, D. Holt, S. Smith, T. Ta., C. Sherwin, D. Hilterbrand, P.
Pommerenk, Z. Hinedi, and A. Camper. 2003. Establishing Site-Specific Flushing Velocities.
Denver, Colo.: AwwaRF.

April 2007

-26 -


-------
Friedman, M., K. Martel, and S. Via. 2002b. Finished Water Storage Facilities.
http://www.epa. gov/ safewater/tcr/pdf/storage, pdf

Friedman, M., L. Radder, S. Harrison, D. Howie, M. Britton, G. Boyd, H. Want, R. Gullick, M.
LeChevallier, D. Wood, and J. Funk. 2004. Verification and Control of Pressure Transients and
Intrusion in Distribution Systems. Denver, Colo.: AwwaRF.

Frost, F., G. Craun, andR. Calderon. 1996. Waterborne Disease Surveillance. Journal AWWA
88(9):66-75.

Gauthier, V., M.-C. Besner, M. Trepanier, R. Millette, and M. Prevost. 2001. Tracking the
Source for Microbial Contamination in Distribution Systems Using an Integrated Approach. In
Proc. Of the AWWA WQTC Conference. Denver, Colo.: AWWA.

Geldreich, E., K. Fox, J. Goodrich, E. Rice, R. Clark, and D. Swerdlow. 1992. Searching for a
Water Supply Connection in the Cabool, Missouri Disease Outbreak of Escherichiea coli
0157:H7. Water Research Journal. Vol. 26, No. 8, August 1992.

Geldreich, E. 1996. Microbial Quality of Water Supply in Distribution Systems. Lewis
Publishers. Boca Raton, FL.

Geldreich, E.E., and S. Shaw. 1993. New York City Water Supply Microbial Crisis. U.S.
Environmental Protection Agency.

Geldreich, Edwin E. 1990. Microbiological Quality Control in Distribution Systems. In Water
Quality and Treatment. Edited by Frederick W. Pontius, American Water Works Association.
New York, Ny.: McGraw-Hill, Inc.

Goodfellow, F., S. Ouki, and V. Murray. 2002. Permeation of Organic Chemicals through Plastic
Water-Supply Pipes. J. CIWEM, Vol. 16, pp. 85-89.

Gwinnett Daily Post. 2003. Weather Blamed in Rockdale Water Contamination. October,

2003.

Haas, C.N., R.B. Chitluru, M. Gupta, W.O. Pipes, and G.A. Burlingame. 1998. Development of
Disinfection Guidelines for the Installation and Replacement of Water Mains. Denver, Colo.:
AwwaRF and AWWA.

Hellard, M. E., M. I. Sinclair, A. B. Forbes, and C. K. Fairley. 2001. A Randomized, Blinded,
Controlled Trial Investigating the Gastrointestinal Health Effects of Drinking Water Quality.
Environ. Health Perspect, 109:773-778.

Hess, Alan F., D.B. Smith, and G.R. Iwan. 1993. Laboratory Role in Obtaining and Complying
With a Total Coliform MCL Variance. In Proc. of the Twenty-First Annual AWWA Water
Quality Technology Conference. Denver, Colo.: AWWA.

April 2007

-27 -


-------
Holsen, T., J. Park, D. Jenkins, and R. Selleck. 1991. Contamination of Potable Water by
Permeation of Plastic Pipe. Journal AWWA. Vol 83, No. 8.

Hunt, T. 2002. Personal Communications with K. Martel.

Jackson, A., S. Arunagiri, R. Tock, T. Anderson, and K. Rainwater. 2004. Technical Note:
Electrochemical Generation of Perchlorate in Municipal Drinking Water Systems. Journal
AWWA, 96:7:103-108.

Juranek, D. 1997. Waterborne Disease Workshop. Centers for Disease Control and Prevention.
October 9-10, 1997.

Kirmeyer, G., M. Friedman, J. Clement, A. Sandvig, P. Noran, K. Martel, D. Smith, M.
LeChevallier, C. Volk, E. Antoun, D. Hiltebrand, J. Dyksen, and R. Cushing. 2000. Guidance
Manual for Maintaining Distribution System Water Quality: CD-ROM. AWWA Research
Foundation. Denver, CO.

Kirmeyer, G.J., M. Friedman, K. Martel, D. Howie, M. LeChevallier, M. Abbaszadegan, M.
Karim, J. Funk and J. Harbour. 2001. Pathogen Intrusion Into the Distribution System. Denver,
Colo.: AWWARF and AWWA.

Kirmeyer, G.J., L. Kirby, B.M. Murphy, P.F. Noran, K. Martel, T.W. Lund, J.L. Anderson, and
R. Medhurst. 1999. Maintaining and Operating Finished Water Storage Facilities to Prevent
Water Quality Deterioration. Denver, Colo.: AWWARF and AWWA.

Kornteger, G. and L. O'Donnell. 1998. Utility's Innovation Keeps New Mains Cleaner.
OPFLOW, 24(9): 12-13.

Kramer, M., B. Herwaldt, G. Craun, R. Calderon, and D. Juranek. 1996a. Surveillance for
Waterborne-Disease Outbreaks - United States, 1993-1994. Morbidity and Mortality Weekly
Rept., 45:(SS-l):l-33.

Kramer, M., B. Herwaldt, G. Craun, R. Calderon, and D. Juranek. 1996b. Waterborne Disease:
1993 and 1994. Journal AWWA, 88:3:66-80.

Krouse, M. 2001. Sheilding Your Water Supply Backflow Incident Sparks Improvements.
Opflow, 27:2:1-14.

LeChevallier, M.W. 1999. The Case for Maintaining a Disinfectant Residual. Jour. AWWA,
91:1:86.

LeChevallier, M., W. Norton, and T. Atherholt. 1997. Protozoa in Open Reservoirs. J. AWWA.
89(9):84-96.

April 2007

-28 -


-------
LeChevallier, M.W., T.M. Babcock, and R.G. Lee. 1987. Examination and Characterization of
Distribution System Biofilms. Applied and Environmental Microbiology, 53(12):2714-2724.

LeChevallier, M., Gullick, R., and Karim, M. 2002. The Potential for Health Risks from
Instrusion of Contaminants into the Distribution System from Pressure Transients.
http://www.epa.gov/safewater/tcr/pdf/intrusion.pdf

Lee, S., D. Levy, G. Craun, M. Beach, and R. Calderon. 2002. Surveillance for Waterborne-
Disease Outbreaks - United States, 1999-2000. Morbidity and Mortality Weekly Rept., 51 :(SS-

8).

Levy, D., M. Bens, G. Craun, R. Calderon, and B. Herwaldt. 1998. Surveillance for Waterborne-
Disease Outbreaks - United States, 1995-1996. Morbidity and Mortality Weekly Rept., 47:(SS-
5): 1-29.

Littleton Courier. 2005. Lisbon Residents Boil Water After E. coli Discovery. February, 2005.
Logston, M. 2004. Personal communication.

Mac Kenzie, W., N. Hoxie, M. Proctor, M. Gradus, K. Blair, D. Peterson, J. Kazmierczak, D.
Addiss, K. Fox, J. Rose, and J. Davis. 1994. The New England Journal of Medicine, 331:3:161-
167.

Masson, P. 2004. Pacific Residents Get Notice to Boil Water for 72 Hours After Sample Tests
Positive for Bacteria. March 31, 2004. The Missourian, Washington, Missouri.

McMath, S. and R. Casey. 2000. The Use of Network Modeling Techniques to Resolve Water
Quality Issues in Distribution Systems. In Proc. of the AWWA WQTC Conference. Denver,

Colo.: AWWA.

National Research Council. 2006. Drinking Water Distribution Systems: Assessing and Reducing
Risks. Prepublication Copy. Washington D.C.: The National Academies Press.

Nilson, J. 2004. Washington Department of Health. Personal communication.

O'Neill, J. G., and O. T. Parry. 1997. The Operational Significance of Coliform Species in
Treated Water. Coliforms and E. coli: Problem or Solution? 249. Royal Society of Chemistry.
Cambridge, UK.

Olympian. 2004. Lacey Drains Reservoir, Treats Wells after Bacteria Discovered. March 2,
2004.

Oregon Department of Human Services. 2006. Drinking Water Found to be Likely Camp
Yamhill Disease Source. Oregon Department of Human Services Press Release.

April 2007

-29 -


-------
Payment, P., L. Richardson, J. Siemiatycki, R. Dewar, M. Edwardes, and E. Franco. 1991. A
Randomized Trial to Evaluate the Risk of Gastrointestinal Disease due to Consumption of
Drinking Water meeting Current Microbiological Standards. American Journal of Public Health,
81(6)703-708.

Payment, P., J. Siemiatycki, L. Richardson, G. Renaud, E. Franco, and M. Prevost. 9 1997. A
Prospective Epidemiological Study of Gastrointestinal Health Effects Due to the Consumption of
Drinking Water.

Peterson, K. 2001. Minnesota Department of Natural Resources. Personal communication.

Pierson, G.L., G. Burlingame, and K. Martin. 2002. Distribution Systems Establishing a
Tradition of Contamination Prevention. Opflow, 28:7:6-11.

Pierson, G., K. Martel, A. Hill, G. Burlingame, and A. Godfree. 2001. Practices to Prevent
Microbiological Contamination of Water Mains. Denver, Colo.: AwwaRF.

Prevost, M., A. Rompr3, H. Baribeau, J. Coallier, and P. Lafrance. 1997. Service Lines: Their
Effect on Microbiological Quality. Journal AWWA, 89:7:78-91.

Principe, Michael A., Freud, Salome and Lu, Lin. 1995. Designing a Sampling Strategy for the
Detection of Coliform Bacteria Within a Large Distribution System. In Proc. of the 1995 Water
Quality Technical Conference. Denver, Colo.: AWWA.

Reiber, S., G. Dostal, L. Onnen, J. McCafferty, W. Sund, andL. Andreasen. 1997b. Groundwater
Disinfection and Arsenic Concentration in the Fremont Distribution System. Final Report, HDR
Engineering, Inc.

Reiber, S., S. Poulsom, S. Perry, M. Edward, S. Patel, and D. Dodrill. 1997a. A General
Framework of Corrosion Control Based on Utility Experience. AwwaRF. Denver, Colo.

Robb, J. 2004. $1.2 Million Settlement Reached Over Contaminated Drinking Water. March 3,
2004. The Town Talk, Alexandria, Louisiana.

Ruane, D. 2004. Cape Penalized for Water Mix-Up. February 14, 2004. News-press.com.

Ryding, J. 2004. Washington Department of Health. Personal communication.

Salmon, R. 2004. Code Blue Murrieta Closer to Solving Neighborhood's Mysterious Water
Problem. June 27, 2004. The Press-Enterprise.

Sherman, K. 2004. Boil Water If You Live at Point Evans. November 12, 2003. The News
Tribune. Tacoma, WA.

Statesman Journal. 2005. Woodburn Residents Urged to Boil Water after E. coli Found. May
26, 2005.

April 2007

-30-


-------
Stevens, M. and N. Miles. 2001. Total Coliforms - Water Quality Indicator or Compliance
Headache? In Proc. of the AWWA Water Quality Technology Conference. Denver, Colo.:
AWWA.

Swerdlow, D., B. Woodruff, R. Brady, P. Griffin, S. Tippen, H. Donnell Jr., E. Geldreich, B.
Payne, A. Meyer Jr., J. Wells, K. Greene, M. Bright, N. Bean, and P. Blake. 1992. A Waterborne
Outbreak in Missouri of Escherichia coli 0157:H7 associated with bloody diarrhea and death.
Ann. Internal Med., 117:812-819.

Symons, J., L. Bradley, Jr., and T. Cleveland, Editors. 2000. The Drinking Water Dictionary.
AWWA. Denver, CO.

USEPA. 2002. Health Risks From Microbial Growth and Biofilms in Drinking Water
Distribution Systems, http://www.epa.gov/safewater/tcr/pdf/biofilms.pdf

USEPA. 1992. Control of Biofilm Growth in Drinking Water Distribution Systems. EPA/625/R-
92/001. Washington, D.C.

USEPA Region 1. 1991. Personal Communication.

USEPA Region 9. 1988. Personal Communication.

USEPA Region 9. 1991. Personal Communication.

USC-FCCCHR (University of Southern California Foundation for Cross-Connection Control and
Hydraulic Research). 1993. Manual of Cross-Connection Control, Ninth Edition. University of
Southern California, Los Angeles, California.

U.S. Water News Online. 2001. Mistake by Rookie Employee Cited as Cause of Water
Contamination. June 2001.

Vicksburg Post. 2007. E. coli found in Water for Fisher Ferry. April 7, 2007.

Wims, M. 2003. Police Blame Landscaper for Water Contamination. October 19, 2003. The
Providence Journal, Providence, RI.

Worldlink.com. 2006. Bandon Residents Warned to Boil Water. January 6, 2006.