Technical Factsheet on: LEAD

List of Contaminants

As part of the Drinking Water and Health pages, this fact sheet is part of a larger publication:
National Primary Drinking Water Regulations

Drinking Water Standards

MCLG: zero

Action Level: > 0.015 mg/L in more than 10 percent of tap water samples
HAL(child): none

Health Effects Summary

Acute: Lead can cause a variety of adverse health effects in humans. At relatively low levels of exposure,
these effects may include interference with red blood cell chemistry, delays in normal physical and mental
development in babies and young children, slight deficits in the attention span, hearing, and learning
abilities of children, and slight increases in the blood pressure of some adults. It appears that some of
these effects, particularly changes in the levels of certain blood enzymes and in aspects of children's
neurobehavioral development, may occur at blood lead levels so low as to be essentially without a
threshold.

Chronic: Chronic exposure to lead has been linked to cerebrovascular and kidney disease in humans.
Cancer: Lead has the potential to cause cancer from a lifetime exposure at levels above the action level.
Usage Patterns

Lead is the fifth most important metal in the USA economy in terms of consumption. Of this approximately
85% of the primary lead is produced domestically and 40-50% is recovered and recycled. Eighty eight
percent of the lead mined in the US comes from seven mines in the New Lead Belt in southeastern
Missouri; the rest coming from eight mines in Colorado, Idaho, and Utah. Three of the six USA lead
smelters are from this region, the others are located in Idaho, Montana, and Texas.

Release Patterns

Lead occurs in drinking water from two sources: (1) Lead in raw water supplies, i.e., source water or
distributed water, and (2) corrosion of plumbing materials in the water distribution system (corrosion by-
products). Most lead contamination is from corrosion by-products.

Occurrence in Source Water and Distributed Water. Based on a variety of water quality surveys, EPA now
estimates that approximately 600 groundwater systems and about 215 surface suppliers may have water
leaving the treatment plant with lead levels greater than 0.005 mg/L These two sources together indicate
that less than 1 percent of the public water systems in the United States have water entering the
distribution system with lead levels greater than 0.005 mg/L. These systems serve less than 3 percent of
people that receive their drinking water from public water systems.

From 1987 to 1993, according to the Toxics Release Inventory lead compound releases to land and water
totalled nearly 144 million lbs., almost all of which was to land. These releases were primarily from lead
and copper smelting industries. The largest releases occurred in Missouri, Arizona and Montana. The
largest direct releases to water occurred in Ohio.


-------
Occurrence as a Corrosion By-Product. Lead in drinking water results primarily from corrosion of
materials located throughout the distribution system containing lead and copper and from lead and
copper plumbing materials used to plumb public- and privately-owned structures connected to the
distribution system. The amount of lead in drinking water attributable to corrosion by-products depends on
a number of factors, including the amount and age of lead and copper bearing materials susceptible to
corrosion, how long the water is in contact with the lead containing surfaces, and how corrosive the water
in the system is toward these materials.

The potential sources of lead corrosion by-products found in drinking water can include: Water service
mains (rarely), lead goosenecks or pigtails, lead service lines and interior household pipes, lead solders
and fluxes used to connect copper pipes, alloys containing lead, including some faucets made of brass or
bronze.

Most public water systems serve at least some buildings with lead solder and/or lead service lines. EPA
estimates that there are about 10 million lead service lines/connections. About 20 percent of all public
water systems have some lead service lines/connections within their distribution system.

The amount of lead in drinking water depends heavily on the corrosivity of the water. All water is corrosive
to metal plumbing materials to some degree, even water termed noncorrosive or water treated to make it
less corrosive. The corrosivity of water to lead is influenced by water quality parameters such as pH, total
alkalinity, dissolved inorganic carbonate, calcium, and hardness. Galvanic corrosion of lead into water
also occurs with lead-soldered copper pipes, due to differences in the electrochemical potential of the two
metals. Grounding of household electrical systems to plumbing may also exacerbate galvanic corrosion.

Environmental Fate

Lead may enter the environment during its mining, ore processing, smelting, refining use, recycling or
disposal. The initial means of entry is via the atmosphere. Lead may also enter the atmosphere from the
weathering of soil and volcanos, but these sources are minor compared with anthropogenic ones.

Lead will be retained in the upper 2-5 cm of soil, especially soils with at least 5% organic matter or a pH 5
or above. Leaching is not important under normal conditions. It is expected to slowly undergo speciation
to the more insoluble sulfate, sulfide, oxide, and phosphate salts.

Lead enters water from atmospheric fallout, runoff or wastewater; little is transferred from natural ores.
Metallic lead is attacked by pure water in the presence of oxygen, but if the water contains carbonates
and silicates, protective films are formed preventing further attack. That which dissolves tends to form
ligands. Lead is effectively removed from the water column to the sediment by adsorption to organic
matter and clay minerals, precipitation as insoluble salt, and reaction with hydrous iron and manganese
oxide. Under most circumstances, adsorption predominates.

Lake sediment microorganisms are able to directly methylate certain inorganic lead compounds. Under
appropriate conditions, dissolution due to anaerobic microbial action may be significant in subsurface
environments. The mean percentage removal of lead during the activated sludge process was 82% and
was almost entirely due to the removal of the insoluble fraction by adsorption onto the sludge floe and to a
much lesser extent, precipitation.

The most stable form of lead in natural water is a function of the ions present, the pH, and the redox
potential. In oxidizing systems, the least soluble common forms are probably the carbonate, hydroxide,
and hydroxycarbonate. In reduced systems where sulfur is present, PbS is the stable solid. The solubility
of Pb is 10 ppb above pH 8, while near pH 6.5 the solubility can approach or exceed 100 ppb. Pb(0) and
Pb(+2) can be oxidatively methylated by naturally occurring compounds such as methyl iodide and
glycine betaine. This can result in the dissolution of lead already bound to sediment or particulate matter.


-------
Lead does not appear to bioconcentrate significantly in fish but does in some shellfish such as mussels.
Evidence suggests that lead uptake in fish is localized in the mucous on the epidermis, the dermis, and
scales so that the availability in edible portions do not pose a human health danger.

Chemical/Physical Properties

CAS Number: 7439-92-1

Color/ Form/Odor: Bluish-white, silvery, gray metal, lustrous when freshly cut.

Soil sorption coefficient: N/A; Low mobility in most soils, lowest at neutral pH and high organic matter.

Common Ores: sulfide-Galena; oxide-Lanarkite; carbonate-Cerrusite; sulfate-Anglesite

Bioconcentration Factor: Log BCFs for fish, 1.65; shellfish, 3.4

Solubilities:

acetate- 443 g/L at 20 deg C
arsenate- insoluble in cold water
carbonate- 0.0011 g/L at 20 deg C
chloride-10 g/L cold water
chromate- 0.2 mg/L
nitrate- 376.5 g/L at 0 deg C
oxide- 0.05 g/L at 20 deg C
dioxide- insoluble
phosphate- insoluble
sulfate- 0.4 g/L
sulfide- insoluble
tetraethyl- 0.29 mg/L at 25 deg C
thiocyanate- 0.5 g/L at 20 deg C
thiosulfate- 0.3 g/L cold water

Other Regulatory Information

Monitoring:

&$160;

Monitoring Period

Initial

After corrosion
control installation
Reduced monitoring

-	Conditional

-	Final

For Lead

At Home Taps

Every 6 months
Every 6 months

Once a year
Every 3 years

For Water Quality Parameters

Within the
Distribution
System

Every 6 months
Every 6 months

Every 6 months
Every 3 years

At Entry to the

Distribution

System

Every 6 months
Every 2 weeks

Every 2 weeks
Every 2 weeks

Analysis

Reference Source

EPA 800/4-83-043

Method Number

239.2; 200.8; 200.9

Treatment/Best Available Technologies

Source water: Ion exchange; lime softening; reverse osmosis; coagulation/filtration


-------
Corrosion Control: pH and alkalinity adjustment; calcium adjustment; silica- or phosphate-based
inhibition

Toxics Release Inventory - Water and Land Releases, 1987-93 (in pounds)



Water



Land



TOTALS

970,827



143,058,771



Top Twelve States *









MO

4,408

40,656,278





AZ

771

23,240,625





MT

0

20,822,517





UT

4,600

11,881,000





TX

1,988

11,515,211





OH

127,990

5,196,522





IN

62,894

4,851,940





TN

7,140

2,095,489





IL

26,601

1,930,000





Wl

1,310

1,350,960





MN

0

1,313,895





NM

0

1,060,880





Major Industries*









Lead smelting, refining



31,423



68,996,819

Copper smelting



5,371



34,942,505

Steelworks, blast furn.



379,849



18,149,696

Storage batteries



0



1,867,292

China plumbing fixtures



1,310



1,350,960

Iron foundries



10,021



1,274,777

Copper mining



0



1,240,000

* State/Industry totals only include facilities with releases greater than 100,000 lbs.
For Additional Information:

EPA can provide further regulatory and other general information:
EPA Safe Drinking Water Hotline - 800/426-4791

Other sources of toxicological and environmental fate data include:
Toxic Substance Control Act Information Line - 202/554-1404
Toxics Release Inventory, National Library of Medicine - 301/496-6531
Agency for Toxic Substances and Disease Registry - 404/639-6000


-------