A PHA United Slates

p	Environmental Protection

^1	Agsncy

Mandatory Greenhouse Gas
Reporting Rule: EPA's
Response to Public Comments

Subpart DD: Electric Transmission
and Distribution Equipment Use


-------
FOREWORD

This document provides responses to public comments on the U.S. Environmental Protection Agency's
(EPA's) Proposed Mandatory Greenhouse Gas Reporting Rule: Additional Sources of Fluorinated GHGs:
Subpart DD, Electric Transmission and Distribution Equipment Use. EPA published a Notice of Proposed
Rulemaking in the Federal Register (FR) on April 12, 2010 (75 FR 18652). EPA received comments on
this proposed rule via mail, e-mail, and at a public hearing held in Washington D.C. on April 20, 2010.
Copies of all comments submitted are available at the EPA Docket Center Public Reading Room.
Comments letters and transcripts of the public hearings are also available electronically through
http://www.requlations.gov by searching Docket ID EPA-HQ-OAR-2009-0927.

EPA prepared this document in multiple sections, with each section focusing on a different broad
category of comments on the rule. In light of the large number of comments received and the significant
overlap between many comments, this document does not respond to each comment individually. Rather,
EPA summarized and provided a single response to each significant argument, assertion, and question
contained within the totality of comments. Within each comment summary, EPA provides in parentheses
one or more lists of Docket ID numbers for commenters who raised particular issues; however, these lists
are not meant to be exhaustive, and EPA does not individually identify each and every commenter who
made a certain point in all instances, particularly in cases where multiple commenters expressed
essentially identical arguments.

EPA's responses to comments are generally provided immediately following each comment summary. In
some cases, EPA provided responses to specific comments or groups of similar comments in the
preamble to the final rulemaking. Rather than repeating those responses in this document, EPA has
referenced the preamble.

Comments were assigned to specific section of this document based on an assessment of the principal
subject of the comment; however, some comments inevitably overlap multiple subject areas.

November 8, 2010

Subpart DD—Response to Comment Document

2


-------
Table of Contents

1.	Definition of the Source Category	4

1.1	Definition of a Facility—Track 1	4

1.2	Definition of a Facility—Track 2	4

1.3	All-in Provision and Boundary between Electricity Generation Facility and T&D
Facility—Track 1	10

1.4	All-in Provision and Boundary between Electricity Generation Facility and T&D
Facility—Track 2	11

1.5	Installation of Electrical Equipment at Electric Power Systems—Track 2	13

1.6	De Minimis Exemption for Sealed-pressure Equipment—Track 1	13

1.7	De Minimis Exemption for Sealed-pressure Equipment—Track 2	14

1.8	Other (Definition of Source Category)	16

2.	Reporting Threshold	17

2.1	Threshold Analysis—Track 1	17

2.2	Other (Reporting Threshold)	18

3.	GHGs to Report—Track 1 	19

4.	Detailed GHG Emission Calculation Procedures/Equations	20

5.	Monitoring and QA/QC Requirements	21

5.1	Frequency of Weighing Cylinders—Track 1	21

5.2	Frequency of Weighing Cylinders—Track 2	22

5.3	Accuracy and Precision of Scales—Track 1	23

5.4	Accuracy and Precision of Scales—Track 2	24

5.5	Frequency of Scale Calibration	25

5.6	Other (Monitoring and QA/QC Requirements)—Track 1	25

6.	Data Reporting Requirements—Track 1	26

7.	Other Subpart DD Comments - Track 1	28

8.	Other Subpart DD Comments - Track 2	29

Appendix A - List of Commenters Sorted by Submission Number	30

November 8, 2010

Subpart DD—Response to Comment Document

3


-------
1. Definition of the Source Category

1.1 Definition of a Facility—Track 1

Relevant Bin Number 4.1.1

Comment Summary 1.1 -a: Two commenters (0407 and 0639) supported the concept of a reporting
facility as an entire transmission and distribution system rather than an individual building, such as a gas-
insulated substation.

Response 1.1-a: EPA appreciates the commenters' support of the proposed definition of a facility.

Comment Summary 1.1-b: One commenter (0608) sought clarification on how to determine the
boundary of a facility if numerous electric power retail companies have a common owner. The
commenter asked if the common owner should be considered one facility, or whether each individual
electric power retail company should be considered a separate facility.

Response 1.1-b: The final rule clarifies that the facility boundary is based on a physical collection of
equipment that functions as an integrated unit between two specified points: (1) the point(s) at which
electric energy is obtained by the facility from an electricity generating unit or a different electric power
transmission or distribution entity that does not have a common owner and (2) the point(s) at which the
customer(s) or another electric power transmission or distribution entity that does not have a common
owner receives the electric energy. Therefore, numerous electric power retail companies would only be
considered one reporting facility if they are electrically linked through transmission and distribution lines
in a continuous manner without being separated by electric power entities with a different owner.

It should also be noted that for purposes of the reporting threshold, if distinct facilities have a common
owner and the total nameplate capacity of all the facilities with the common owner exceeds 17,820
pounds, then each facility must report emissions even if the nameplate capacity of an individual facility is
less than 17,820 pounds.

Comment Summary 1.1-c: Commenters 0624, 1021, and 1080 stated that reporting should be
corporate-level to ensure that the largest potential emitters of SF6 are covered by the rule as well as to
ensure accurate reporting. The commenters argued that corporate-level reporting will minimize the
burden among owners and operators of electric power systems in determining what collections of
electrical equipment constitute each electric power system.

Response 1.1-c: See the Subpart DD Final Preamble, Section III, "Summary of Comments and
Responses" for EPA's response on corporate-level reporting.

1.2 Definition of a Facility—Track 2

Relevant Bin Number 4.1.1

Comment Summary 1.2-a: EPA requested comment on whether it would be appropriate to use the
Regional Greenhouse Gas Initiative (RGGI) definition of a transmission and/or distribution entity for
assistance in defining an electric power system facility. RGGI defines a transmission and/or distribution
entity as "the assets and equipment used to transmit and distribute electricity from an electric generator
to the electrical load of a customer. Includes all related assets and equipment located within the service
territory of the entity, defined as the service territory of a load-servicing entity specified by the applicable
state regulatory agency." Commenters 0075, 0086, 0088, 0109, and 0133 did not think the RGGI
definition is appropriate for use in the definition of a facility for Subpart DD. Commenter 0075 considered
the EPA definition more "specific and definitive." Commenter 0088 considered EPA's proposed definition
to be generally more consistent with national industry standards than the RGGI definition.

November 8, 2010

Subpart DD—Response to Comment Document

4


-------
Response 1.2-a: EPA appreciates the comments regarding the appropriateness of the RGGI definition of
a transmission and/or distribution entity. EPA did not incorporate the RGGI definition into the definition of
a facility for this subpart due to the ambiguity involved with the definition and the lack of support of the
RGGI definition among commenters.

Comment Summary 1.2-b: Six commenters (0075, 0088, 0097, 0098, 0115, 0128) generally agreed
with the system-wide facility concept contained in EPA's proposed definition of an electric power system
facility. Commenter 0075 noted that it is reflective of the way the commenter has reported emissions
under EPA's SF6 Emission Reduction Partnership for Electric Power Systems.

Response 1.2-b: EPA has retained the system-wide facility concept as part of the facility definition for
this subpart.

Comment Summary 1.2-c: EPA proposed the following as part of the language relating to the definition
of a facility: "Reporting by the electric power system would comprise all gas-insulated equipment located
between the point of generation and the point at which the ultimate customer receives the electricity."
Commenters 0075 and 0088 requested that the reference to "ultimate" customer be removed from the
language since many utilities and electric power providers do not provide electric power directly to the
ultimate consumer, but rather to a different utility or electric power provider. Commenter 0075 explained
that removing the word "ultimate" from the physical description of an electric power system would clarify
that there might be numerous distinct facilities from the point at which electric power is generated to the
point at which electric power is provided to the ultimate consumer.

Response 1.2-c: EPA acknowledges that the proposed language would not be appropriate for cases in
which an electric power entity provides electricity to another electric power entity rather than the ultimate
retail customer. EPA has removed reference to the "ultimate customer" in the final rule and has clarified
that the downstream boundary of the facility is "the point(s) at which the customers) or another electric
power transmission or distribution entity that does not have a common owner receives the electric
energy."

Comment Summary 1.2-d: Commenter 0083 stated that the proposed language describing electric
power systems as equipment "operated as an integrated unit by one electric power entity or several
entities that have a single owner" could be interpreted to mean that one parent company would have to
report emissions for all its subsidiaries, which would not be desirable for the commenter given its
ownership structure. The commenter explained that it is a subsidiary company with its own board of
directors that is distinct from its parent company's other subsidiaries, and thereby thought each
subsidiary should be allowed to report separately.

Response 1.2-d: : The final rule clarifies that the facility boundary is based on a physical collection of
equipment that functions as an integrated unit between two specified points: (1) the point(s) at which
electric energy is obtained by the facility from an electricity generating unit or a different electric power
transmission or distribution entity that does not have a common owner and (2) the point(s) at which the
customers) or another electric power transmission or distribution entity that does not have a common
owner receives the electric energy. Therefore, numerous subsidiaries would only be considered one
reporting facility if they are electrically linked through transmission and distribution lines in a continuous
manner without being separated by electric power entities with a different owner.

. See Subpart DD Final Preamble, Section III, "Summary of Comments and Responses" for EPA's
additional discussion of the final Definition of a Facility language.

Comment Summary 1.2-e: Seven commenters (0083, 0087, 0097, 0098, 0101, 0127, 0133) argued that
reporting should be based on the ownership of equipment (frequently referred to in comments as
corporate-level reporting) to ensure accurate reporting, reduce ambiguity regarding what collections of
equipment constitute facilities, and reduce the overall burden of reporting. Commenters 0083, 0087, and

November 8, 2010

Subpart DD—Response to Comment Document

5


-------
0133 considered the term "operated as" in the proposed definition of a facility to be ambiguous since the
operation of electrical equipment can mean many different things. Commenter 0083 thought that
"operated as" could be interpreted to mean the performance of maintenance activities and argued that
the entity responsible for performing maintenance activities on equipment should not be responsible for
reporting emissions from that equipment since the entity has no power to make decisions regarding the
purchase or replacement of the equipment.

Commenter 0087 acknowledged that corporate-1 eve I reporting can lead to ambiguities if there are
multiple owners of equipment. To avoid this potential ambiguity in multiple-owner situations, commenters
0087 and 0101 suggested that reporting be based on whichever owner is responsible for the
maintenance of the equipment.

Commenter 0133 stated that "corporate reporting would allow an entity to determine quickly and
accurately what equipment should be counted toward the reporting threshold (that which it owns) and
then report fully the emissions related to that equipment (based on service and maintenance records). It
also would eliminate any confusion that may be caused by introducing operational relationships into the
definition of 'electric power system'."

Commenter 0133 agreed with EPA that the entity responsible for equipment service and maintenance
activities is most capable of accurate data collection and compiling, but the commenter argued this notion
supports reporting based on ownership since the owners have the obligation to service and maintain their
equipment.

Response 1.2-e: See the Subpart DD Final Preamble, Section III, "Summary of Comments and
Responses" for EPA's response on corporate-level reporting. To avoid confusion, EPA has removed the
term "operated as" from the definition of facility. The definition of facility in the final rule refers to
equipment that "is owned, serviced, or maintained by a single electric power transmission of distribution
entity (or multiple entities with a common owner)." The phrase "owned, serviced, or maintained" as used
in the definition of facility is not intended to allow or suggest segmenting portions of a system for the
purpose of avoiding General Provisions (40 CFR 98.2 - 98.4), the reporting requirements that are
applicable to all owners and operators associated with the facility.

Comment Summary 1.2f: Commenters 0127 and 0133 interpreted the definition of a facility proposed by
EPA to mean that a single facility constitutes all generation, transmission, or distribution assets that are
operated as an integrated unit even if different companies are responsible for the generation,
transmission, and distribution of the electricity. The commenters expressed concern that the proposed
facility definition will lead to confusion and inaccurate emission reports if numerous companies have to
share data in order to calculate emissions.

Response 1.2-f: To avoid confusion, EPA has removed the term "operated as" from the definition of
facility. Instead, the definition refers to equipment that "functions as" an integrated unit, and that is
owned, serviced, or maintained by a single electric power transmission or distribution entity. The final
rule clarifies that the facility boundary is based on a physical collection of equipment that functions as an
integrated unit, that is owned, serviced or maintained by a single electric power transmission or
distribution entity (or multiple entities with a common owner), and that is located between two specified
points: (1) the point(s) at which electric energy is obtained by the facility from an electricity generating
unit or a different electric power transmission or distribution entity that does not have a common owner
and (2) the point(s) at which the customer(s) or another electric power transmission or distribution entity
that does not have a common owner receives the electric energy. Therefore, numerous electric power
retail companies would only be considered one reporting facility if they are electrically linked through
transmission and distribution lines in a continuous manner without being separated by electric power
entities with a different owner.

Comment Summary 1.2-g: Commenter 0096 requested that reporting be required by whichever entity
directly owns and operates a collection of equipment. The commenter elaborated as follows, "For
example, at a power plant where most of the switchyard is owned by a local distribution company (LDG),
the LDG would report on the equipment that it operates as part of its overall T&D system SF6 reporting.

November 8, 2010

Subpart DD—Response to Comment Document

6


-------
To the extent that the power plant operator manages any SF6 containing equipment at the same power
plant, the power plant operator would report SF6 emissions from any equipment that it manages at the
facility as part of its power plant facility-level reporting. However, the power plant operator would only
report SF6 emissions for equipment it owns as part of its facility report if the facility would otherwise
exceed the 25,000 tonne Mandatory Reporting Rule (MRR) reporting threshold for the facility."

Response 1.2-g: The commenter's proposal may be suitable for certain ownership and operational
relationships. However, the definition of a facility for this subpart must be applicable to scenarios in which
there are multiple owners or complex ownership and operational relationships involved with specific
pieces equipment. EPA's final definition of a facility is based on a physical collection of equipment
located between two specified points, where the equipment is owned, serviced, or maintained by a single
electric power entity (or multiple entities with a common owner). Per the General Provisions (40 CFR
98.2 - 98.4), the reporting requirements are applicable to all owners and operators associated with the
facility. See Subpart DD Final Preamble, Section III, "Summary of Comments and Responses" for
additional discussion of the final Definition of a Facility language.

Comment Summary 1.2-h: Commenter 0098 recommended the following edits to EPA's proposed
facility definition:

EPA proposes to define the facility as follows: For purposes of this subpart, "facility" means an
electric power system. Electric power system means the collection of SF6- and PFC-insulated
equipment linked through electric power transmission or distribution lines and operated as an
integrated unit by one electric power entity or several entities that have a single owner.

The commenter did not indicate why this edit should be made.

Response 1.2-h: One of EPA's intentions of the proposed language was to avoid situations where a
parent company divides several subsidiary companies into separate facilities even though the subsidiary
companies are located next to each other and operate electrical equipment that is interconnected by
lines. Therefore, EPA used language to clarify that in this scenario, the electrical equipment throughout
the subsidiary companies would be considered as part of a single facility. See Subpart DD Final
Preamble, Section III, "Summary of Comments and Responses" for additional discussion of the final
Definition of a Facility language.

Comment Summary 1.2-i: Commenter 0101 indicated that EPA assumed a single electric power
company always owns and operates all transmission and distribution equipment from the point of
generation to the point at which customers ultimately receive electricity. The commenter noted that in
some cases the owner of a piece of equipment is different from the operator of that piece of equipment,
and the commenter is concerned that under the proposed definition of a facility, double-counting of
emissions might occur from both the owners and operators of a piece of equipment reporting SF6
emissions from the equipment.

Response 1.2-i: EPA acknowledges that the transmission and distribution equipment from the point of
generation to the point at which customers ultimately receive electricity is not always owned and
operated by a single electric power entity. EPA has clarified the boundaries of a Subpart DD facility in the
final rule, and notes that there may be more than one distinct electric power system facility located from
the point at which electricity is generated to the point at which the ultimate customer receives the
electricity. See Subpart DD Final Preamble, Section III, "Summary of Comments and Responses" for
additional discussion of the final Definition of a Facility language and clarification of reporting obligations.

Comment Summary 1.2-j: Commenter 0101 argued that the following activities listed in the Monitoring
and QA/QC requirements of 40 CFR §98.304 are not possible for an owner that does not operate or
maintain a substation to conduct: (1) Ensure purchases from bulk gas distributors, Original Equipment
Manufacturers, and off-site recycling are accounted for, (2) Ensure all cylinders are consistently weighed
on certified scales, and (3) Provide proof that all scales are certified using NIST-traceable standards.

November 8, 2010

Subpart DD—Response to Comment Document

7


-------
Response 1.2-j: Per the General Provisions (40 CFR 98.2 - 98.4), the reporting requirements are
applicable to all owners and operators of a facility, but is up to the owners and operators to designate a
representative who will be responsible for certifying, signing, and submitting GHG reports to EPA. This
means that the owner, operator, or some combination of the two can conduct the monitoring and QA/QC
measures listed in 40 CFR §98.304 for the facility.

Comment Summary 1.2-k: Commenter 0109 supported the "operation" differentiation between electric
power systems in the definition of a facility proposed by EPA and noted that it will be reporting on an
"operation basis" under other subparts of the rule.

Response 1.2-k: EPA appreciates the commenter's support of the proposed definition of a facility. EPA
did propose defining the facility boundaries on the basis of operation. However, due to the myriad
relationships and operational structures among owners and operators of electric power systems as well
as other issues raised by commenters, it was necessary to revise the facility definition to no longer
differentiate facility boundaries solely on the basis of equipment operation. The definition now refers to
equipment that is "owned, serviced, or maintained by" a single entity. To avoid confusion, EPA has
removed the term "operated as" from the definition of facility. The definition of facility in the final rule
refers to equipment that "is owned, serviced, or maintained by a single electric power transmission of
distribution entity (or multiple entities with a common owner)." The phrase "owned, serviced, or
maintained" as used in the definition of facility is not intended to allow or suggest segmenting portions of
a system for the purpose of avoiding General Provisions (40 CFR 98.2 - 98.4), the reporting requirements
that are applicable to all owners and operators associated with the facility. See Subpart DD Final
Preamble, Section III, "Summary of Comments and Responses" for additional discussion of the final
Definition of a Facility language.

Comment Summary 1.2-1: Commenter 0115 requested flexibility in the EPA proposed definition of a
facility "with respect to ownership, geographic service territories and business structure." The commenter
explained that there are multiple transmission assets located geographically within the boundaries of its
service territories that it operates and maintains but does not own. The commenter would like the
definition to "allow for segregation of assets by ownership or by operating entity in the event future
operating practices and agreements with these third parties provide for a mechanism to segregate the
affects these third-party assets have on [the commenter's] overall emissions."

Response 1.2-1: EPA acknowledges that flexibility in the definition of an electric power system facility to
segregate electrical equipment based on either ownership or operational control might provide
convenience to certain SF6 equipment users under certain conditions. However, it is essential that the
definition of a facility for this subpart clearly identify which collections of equipment constitute a facility
and the points at which a facility begins and ends. This is essential because given the complex owner
and operator relationships in the industry, allowing flexibility to define a facility differently depending on
the situation encountered would greatly increase the risk of double-counting, underreporting, and/or
confusion regarding the boundaries of a facility. To avoid confusion, EPA has removed the term
"operated as" from the definition of facility. The definition of facility in the final rule refers to equipment
that "is owned, serviced, or maintained by a single electric power transmission of distribution entity (or
multiple entities with a common owner)." The phrase "owned, serviced, or maintained" as used in the
definition of facility is not intended to allow or suggest segmenting portions of a system for the purpose of
avoiding General Provisions (40 CFR 98.2 - 98.4), the reporting requirements that are applicable to all
owners and operators associated with the facility. See Subpart DD Final Preamble, Section III,
"Summary of Comments and Responses" for additional discussion of the final Definition of a Facility
language.

Comment Summary 1.2-m: Commenter 0119 suggested that "EPA clarify the applicability of the rule to
clarify that 'electric power systems' are owned by electric distribution companies and that these
companies would be responsible for reporting any emissions."

November 8, 2010

Subpart DD—Response to Comment Document

8


-------
Response 1.2-m: Per the General Provisions (40 CFR 98.2 - 98.4), the reporting requirements are
applicable to all owners and operators of a facility, and it is up to the owners and operators to designate a
representative who will be responsible for certifying, signing, and submitting GHG reports to EPA.
Furthermore, the owners of electric power system facilities are not limited to electric distribution
companies; there are myriad types of entities that can own an electric power system facility. For more
information on the types of entities that can be considered owners of electric power system facilities as
well as which entities are responsible for reporting emissions, please see Subpart DD Final Preamble,
Section III, "Summary of Comments and Responses."

Comment Summary 1.2-n: Commenter 0120 suggested that the system boundary in the final rule
include all equipment operated by a single owner, regardless of whether or not the equipment is
electrically linked through lines. The commenter noted that it currently has a single unified information
collection protocol for the three "affiliates" it operates even though the "affiliates" are not linked through
lines. The commenter stated that having to report emissions for the three affiliates separately would be
an incremental burden since it would necessitate establishing multiple information collection systems.

Response 1.2-n: EPA acknowledges that in certain cases, it may be more convenient for affiliate
companies to compile a single set of emission estimates and submit one report to EPA through a
common owner. However, EPA examined a variety of reporting levels for Subpart DD and concluded that
the facility definition must be based on a physical collection of equipment to avoid issues associated with
corporate-level reporting (or reporting based solely on a common ownership). These issues include the
complexity of corporate ownership structures, the potential for double-counting emissions when there are
multiple owners associated with an electric power system, and the challenges of tracking and monitoring
emissions for a facility overtime if there are changes in the ownership. For more information on the
EPA's examination of options for defining a facility for Subpart DD, see Subpart DD Final Preamble,
Section III, "Summary of Comments and Responses" as well as the TSD, located here:
www.epa.gov/climatechange/emissins/ghgrulemaking.html

Comment Summary 1.2-o: Commenter 0133 argued that the joint obligation for reporting between
owners and operators in §98.3 will be confusing in practice if applied to Subpart DD since owners and
operates are not equally capable of measuring emissions or defining clear facility boundaries for the
source category. The commenter stated that in order to avoid confusion and inaccurate emission reports,
EPA needs to clarify "how this joint reporting obligation would be structured."

Response 1.2-o: The details of the joint reporting obligation between owners and operators are provided
in the General Provisions (40 CFR 98.2 - 98.4). According to the General Provisions, the reporting
requirements are applicable to all owners and operators of a facility. But it is up to the owners and
operators to designate a representative who will be responsible for certifying, signing, and submitting
GHG reports to EPA. Therefore, the owners and operators of a facility can coordinate in measuring
emissions and confirming the facility boundary if they are indeed "not equally capable of measuring
emissions from a facility or defining clear facility boundaries."

Comment Summary 1.2-p: Commenter 0088 was supportive of how EPA's proposed definition of a
facility recognized the physical interconnection and operational interdependence of system components,
but was concerned about EPA's assertion that "regardless of the role that operation or ownership plays in
the final source category definition, the obligation to report will apply to both owners and operators." The
commenter thought this could lead to double-counting of emissions. Commenter TRANS-DC-04 (2010)
also expressed concern that holding both owners and operators of electric power systems responsible for
SF6 may lead to double-counting of emissions."

Response 1.2-p: The details of the joint reporting obligation between owners and operators are provided
in the General Provisions (40 CFR 98.2 - 98.4). According to the General Provisions, the reporting
requirements are applicable to all owners and operators of a facility. But it is up to the owners and
operators to designate a representative who will be responsible for certifying, signing, and submitting
GHG reports to EPA. Since the designated representative is selected by an agreement binding on all the

November 8, 2010

Subpart DD—Response to Comment Document

9


-------
owners and operators of the facility, then the designated representative should be fully capable of
ensuring that the facility emissions were measured properly and that emissions were not double-counted.

Comment Summary 1.2-q: CommenterTRANS-DC-04 (2010) thought that in certain cases, the myriad
of ownership and operational relationships for electric power systems across regions and companies
might not be "amenable" to reporting at the system-wide level.

Response 1.2-q: The mass-balance monitoring methods for subpart DD, which are based on the IPCC
Tier 3 method of measuring emissions from electric power systems, require monitoring of emissions for
an entire electric power system and are not conducive for measuring emissions for a specific piece of
equipment or single substation within a larger electric power system. Given the myriad ownership and
operational relationships in the electric power system industry, EPA acknowledges that coordination
might be required among distinct owners and operators in order to ensure that emissions are measured
accurately and reliably. For more information on EPA's rationale for system-wide reporting, please see
the TSD located here: www.epa.gov/climatechange/emissins/ghgrulemaking.html

1.3 All-in Provision and Boundary between Electricity Generation Facility and T&D
Facility—Track 1

Relevant Bin Number 4.1.1.1

Comment Summary 1.3-a: Twelve commenters (0407, 0455, 0584, 0597, 0618, 0624, 0661, 0725,
1021, 1080, 1566, 1741) requested clarification and/or expressed concern over the general reporting
requirement located in §98.2(a)(2) that any subpart D electric generating unit facility above the reporting
threshold would be required to report emissions for all source categories that are located at the facility,
including SF6 emissions under subpart DD.

Five commenters (0407, 0584, 1021, 1080, 1741) stated that including SF6 emissions from electric
equipment in subpart D facility emission reports could lead to double-counting of emissions since
facilities in subpart DD might encompass electrical equipment that is located at a subpart D facility.

Response 1.3-a: Based on the concerns expressed by commenters, EPA has made alterations to the
Reporting Threshold language in §98.301 so that a subpart D electric generating unit facility would only
be required to report emissions associated with the Electrical Transmission and Distribution Equipment
Use source category if the amount of SF6 and PFC-insulated equipment within the subpart D facility
exceeds the reporting threshold for subpart DD, which is 17,820 lbs of SF6 and PFC nameplate capacity.
EPA expects that in general, the subpart D facility will not independently meet this threshold and thus is
unlikely to incur the reporting obligation and the risk of double-counting emissions. For more information,
please see the Subpart DD Final Preamble, Section III, "Summary of Comments and Responses."

Comment Summary 1.3-b: Seven commenters (0407, 0455, 0597, 0624, 1021, 1080, 1741) argued that
it would be very difficult to accurately measure SF6 emissions from only electrical equipment at a electric
generating unit that is part of an integrated utility since the SF6 stocks that services this equipment are
often stored and tracked in a central storage area for the integrated utility. In this scenario, the SF6 stored
at the central storage areas would be used to service equipment throughout the integrated transmission
and distribution system, not just a single electric generating unit. These commenters noted that the mass-
balance is only an efficient and effective method for measuring emissions at the system-level and not for
a single physical location such as an electric generating unit facility.

Response 1.3-b: As explained in section §98.301-Reporting Threshold of the final rule, Subpart DD
emissions occurring at an electric generating unit (EGU) facility would only need to be reported if the
nameplate capacity of the SF6 and PFC insulated equipment at the facility exceeds the subpart DD
threshold of 17,820 pounds of nameplate capacity. EPA does not expect that many EGU facilities will
have this much SF6 and PFC-insulated equipment. If an EGU does exceed the subpart DD threshold,

November 8, 2010

Subpart DD—Response to Comment Document

10


-------
then conducting mass-balance emissions monitoring at this facility, as required by subpart DD, should be
a similar process and similar burden as conducting the mass-balance monitoring methods for non-EGU
facilities. For more information, please see the Subpart DD Final Preamble, Section III, "Summary of
Comments and Responses."

Comment Summary 1.3-c: Commenters 0624, 1021, and 1741 specifically requested clarification on
reporting responsibilities between different owners in certain cases where substations are "co-located"
with electricity generation facilities. As explained by commenter 0624, "If co-located substations and
other supporting infrastructure included SF6-containing equipment owned by the same electric generating
facility owner, then it appears that the proposed rule would require any SF6 emissions to be included in
the reporting by the generating facility owner. However, if the substation and other supporting
infrastructure is owned by another entity (i.e., not the owner of the generating facility), it is unclear who
would be responsible for reporting any SF6 emissions emanating from the co-located substations and
other supporting structure, the owner of the generating facility or the owner of the SF6 -containing
equipment."

Response 1.3-c: According to the General Provisions (40 CFR 98.2 - 98.4), the reporting requirements
are applicable to all owners and operators of a facility (although the actual emission report is certified,
signed, and submitted to EPA by the representative designated by the owners and operators of the
facility). If the SF6 insulated equipment co-located at an electricity generating unit is part of a subpart DD
electric power system facility, then the owners and operators of the electric power system facility would
report emissions for that equipment. In the case of an electricity generating unit that must report subpart
DD emissions for SF6 -insulated equipment co-located at the facility (note that this would only be required
if the EGU had more than 17,820 pounds of SF6 and PFC insulating equipment located within its facility),
the emissions report for the EGU facility would need to include emissions for any SF6 insulated
equipment located within the facility, regardless of whether the owners and operators of the EGU are the
same as the owners and operators of the SF6-insulated equipment. See subpart A §98.2-98.4 and
subpart D §98.301 for more information.

Comment Summary 1.3-d: Commenters 0624, 0479, and 0547 sought clarification on whether a
Subpart DD facility that falls above the threshold would be required to report emissions from a source
category that is located at the same site as the Subpart DD facility. Commenters 0624 and 0479 asked
whether a Subpart DD facility would be required to report emissions from combustion sources on site if
under the same ownership control and, if so, whether there would be any emissions or heat input size
threshold for determining applicability. Commenters 0624, 0479, and 0547 recommended that portable
equipment or generating units designated as emergency generators should be exempted from Subpart
DD facility emission reports.

Response 1.3-d: The facility definition for subpart DD (see 40 CFR §98.307) is unique from the definition
of a facility used in other subparts (see General Provisions, 40 CFR 98.2 - 98.4) in that the electric power
system facility only encompasses electric transmission and distribution equipment and servicing
inventory insulated with or containing SF6 or PFCs. The electric power system facility does not include
co-located emission sources. However, per General Provisions 40 CFR 98.2 - 98.4, the facility must
report for all applicable source categories listed in Table A—3 and Table A—4 of subpart A that are
triggered by the facility..

1.4 All-in Provision and Boundary between Electricity Generation Facility and T&D
Facility—Track 2

Relevant Bin Number 4.1.1.1

Comment Summary 1.4-a: Seven commenters (0088, 0096, 0097, 0126, 0127, 0133, TRANS-DC-04
(2010)) requested clarification and/or expressed concern over the general reporting requirement located
in § 98.2(a)(2) that any subpart D electric generating unit facility above the reporting threshold would be

November 8, 2010

Subpart DD—Response to Comment Document

11


-------
required to report emissions for all source categories that are located at the facility, including SF6
emissions under Subpart DD. The commenters argued that this would lead to ambiguities in reporting
responsibilities and impose an unreasonable burden while only capturing a relatively small amount of
emissions.

Commenters 0096 and 0126 requested a de minimis exception for SF6 -insulated equipment for electric
generating unit emission reports. Commenter 0096 stated "in the case of power plants, that a de minimis
exemption from SF6 reporting should be explicitly allowed for the power plant facility since the vast
majority of SF6 is typically used in T&O applications that will be reported on by LOCs as part of their
system-wide reporting of SF6. As an alternative, simplified engineering estimation techniques should be
allowed at facilities with de minimis SF6 emissions. Overall, in the context of the magnitude of C02
emissions from power plants, SF6 emissions are negligible. As an example, we estimate that SF6
emissions at the largest fossil plant operated by [the commenter] that SF6 emissions were less than 0.1%
of the facility's total GHG emissions in 2008." Commenter 0126 recommended either a complete de
minimis exception or a separate threshold of 17,820 lbs of SF6 nameplate capacity at the electric
generating facility to trigger SF6 emissions reporting.

Commenter 0097 cited the complexity of electric generation and electricity transmission ownership
structures as a major impediment to accounting for SF6 emissions from switchyards at electricity
generation facilities and recommends the following: "1. Require transmission and distribution entities to
report SF6 emissions for the equipment that it owns within the switchyard, and 2. Require electric
generation facility entities to report SF6 emissions for the equipment that it owns within the switchyard.
However, EPA should identify SF6 emissions as de minimis compared to stationary combustion
greenhouse gas emissions on site, and permit the use of alternative calculation methodologies (such as
engineering calculations) to estimate the emissions of SF6 containing equipment rather than the mass
balance methodology."

Commenter 0098 supported the general recommendations from commenter 0097, but offered slightly
different recommendations: "1. Require transmission/distribution and electric generating entities to
separately report SF6 emissions for the equipment that they own within the switchyard, and 2. Allow
electric generation facility entities to report SF6 emissions for the equipment that it owns within the
switchyard/contiguous power block with utilization of alternative calculation methodologies (such as
engineering calculations) to estimate the emissions of SF6 containing equipment rather than the mass
balance methodology. EPA should identify SF6 emissions as de minimis compared to stationary
combustion greenhouse gas emissions on-site. (Also, keep the 17,820 pound minimum by reporting
entity.) Reporters should be allowed the option to report per mass balance where the incoming inventory
and the returning bottles are weight certified by the suppliers/recyclers. Suppliers of equipment or bottles
must supply certified gas weight to the purchaser 3. Electric generation facilities and T&D entities that are
owned by the same parent company but operated as distinct companies should be allowed to report at
the distinct company level."

Response 1.4-a: EPA agrees that reporting subpart DD emissions as part of subpart D facility emission
reports would, in most cases, only capture emissions that are minor and/or already captured as part of a
subpart DD facility emission report. However, in some cases there might be considerable SF6 emissions
that occur at an EGU facility that would not be accounted for if subpart D facilities were not required to
report any subpart DD emissions that occur. To balance the risk of unaccounted emissions with the
burden associated with reporting subpart DD emissions for distinct EGU facilities, EPA is only requiring
that subpart D facilities include subpart DD emissions in their emission reports if the total nameplate
capacity of SF6 and PFC containing equipment located within that facility exceeds 17,820 pounds.

In terms of the reporting responsibility for SF6 -insulated equipment located at an EGU facility, the
General Provisions (40 CFR 98.2 - 98.4) dictate that the reporting requirements are applicable to all
owners and operators of a facility (although the actual emission report is certified, signed, and submitted
to EPA by the representative designated by the owners and operators of the facility). If the SF6 insulated
equipment co-located at an electricity generating unit is part of a subpart DD electric power system
facility, then the owners and operators of the electric power system facility would report emissions for that
equipment. In the case of an electricity generating unit that must report subpart DD emissions for SF6 -

November 8, 2010

Subpart DD—Response to Comment Document

12


-------
insulated equipment co-located at the facility (i.e., an EGU with more than 17,820 pounds of SF6 and
PFC insulating equipment located within its facility), the emissions report for the EGU facility would need
to include emissions for any SF6 insulated equipment located within the facility, regardless of whether the
owners and operators of the EGU are the same as the owners and operators of the SF6 -insulated
equipment. See subpart A §98.2-98.4 and subpart D §98.301 for more information.

1.5	Installation of Electrical Equipment at Electric Power Systems—Track 2

Relevant Bin Number 4.1.3

Comment Summary 1.5-a: Five commenters (0081, 0094, 0096, 0097, 0125) recommended that a
Subpart DD facility should not be responsible for emissions from new equipment being installed at the
Subpart DD facility until the equipment has been transferred to the equipment user by the electrical
equipment manufacturer. Commenter 0081 recommended that the point of transfer be when the
equipment has been "received, inspected, and accepted by the utility and the title has been transferred."
Commenter 0096 stated that "regarding GIS equipment assembled on-site by a manufacturer, [the
commenter] requests that the manufacturer be responsible for any SF6 reporting up until the point in time
that the end user takes final acceptance of the equipment (i.e., at the point in time when the end user
confirms that all contract agreements have been met and takes "final delivery" of the completed GIS
equipment). For shipped, pre-assembled GIS equipment, the end user should take responsibility for SF6
reporting at the point in time at which the title for the equipment transfers to the end user." Commenter
0125 recommends the point of transfer be defined as "the point when the equipment warranty is activated
or when the title is transferred or another such point described in the contract between the customer and
the equipment manufacturer or third party."

Response 1.5-a: EPA has confirmed that some equipment is not installed by the purchaser of the
equipment. For example gas insulated substations are typically assembled by the manufacturer onsite
and it can take several months to complete assembly, inspection, and final acceptance and
commissioning. For this reason, gas accounting is best done by the entity that is commissioning the
equipment and handling the gas that will be installed into the equipment.EPA agrees with the
commenters that the Subpart DD facilities should not be responsible for reporting emissions from new
equipment being installed (or from the installation process itself) at the Subpart DD facility until the title to
the equipment has been transferred to the equipment user by the electrical equipment manufacturer.
EPA has included the following language in Subpart DD §98.302—GHGs to report: "For acquisitions of
equipment containing or insulated with SF6 or PFCs, you must report emissions from the equipment after
the title to the equipment is transferred to the electric power transmission or distribution entity."

1.6	De Minimis Exemption for Sealed-pressure Equipment—Track 1

Relevant Bin Number 4.1.4

Comment Summary 1.6-a: Eight commenters (0407, 0479, 0547, 0624, 1021, 1080, 1569, 1741)
requested clarification on whether there is a de minimis exception for hermetically sealed-pressure
equipment that is not intended to be serviced during its lifetime. Seven commenters (0407, 0479, 0547,
0624, 1021, 1080, 1741) specifically argued for a de minimis exception in the context of the Data
Reporting Requirement Nameplate capacity of equipment containing SF6. Commenters 0407 and 1741
noted that a de minimis exception only for the total system-wide nameplate capacity reporting
requirement would not exclude hermetically sealed-pressure equipment from being captured in the mass-
balance emissions monitoring method since the system-wide nameplate capacity is not an input to the
mass-balance equation.

Commenter 1569 argued for a general de minimis exception throughout Subpart DD. In addition to
arguing for a de minimis exception for hermetically sealed-pressure equipment, commenter 1569 also
argued that any equipment with less than 15 pounds of nameplate capacity should be exempted from all
Subpart DD inventory and emission reporting requirements.

Commenter 1741 suggested that if there is no de minimis exception for hermetically sealed-pressure
equipment, there should be an option for facilities to estimate the internal volume for a typical piece of

November 8, 2010

Subpart DD—Response to Comment Document

13


-------
sealed-pressure equipment within different equipment categories, and then use the internal volumes to
assume a maximum nameplate capacity amount for equipment within each category.

Response 1.6-a: EPA concurs that the burden associated with performing a bottom-up assessment to
determine the nameplate capacity of each piece of sealed-pressure equipment within an electric power
transmission and distribution facility is high when compared to the benefits of performing such an
assessment. As a result, EPA has excluded sealed-pressure equipment from the data reporting
requirement for total facility-wide nameplate capacity existing as of the beginning of the year. However,
the potential for emissions from sealed-pressure equipment due to catastrophic events or equipment
disposal still makes it important to document emissions from sealed-pressure equipment, especially for
facilities that specialize in electricity distribution. EPA has clarified that SF6 arriving inside newly acquired
sealed-pressure equipment must still be included as part of the SF6 acquisitions input of the mass-
balance equation, and sealed-pressure equipment that is new or retired must still be considered as a
change to the nameplate capacity in the mass-balance equation.

For the purpose of determining which equipment must be included in the overall nameplate capacity
threshold, EPA considers it more appropriate to distinguish equipment based on whether it is hermetically
sealed rather than whether it is above or below a specified nameplate capacity threshold (such as 15
pounds as suggested by commenter 1569). This is because it can be burdensome to obtain the exact
nameplate capacity of relatively small distribution equipment whereas it is generally straightforward to
determine whether the equipment is sealed-pressure equipment. Distinguishing equipment based on
whether it is sealed-pressure or closed-pressure reduces the potential error associated with determining
whether a piece of equipment should be included in the system-wide nameplate capacity estimate.

Sealed pressure equipment generally contains anywhere from a few ounces to 15 pounds of SF6.

1.7 De Minimis Exemption for Sealed-pressure Equipment—Track 2

Relevant Bin Number 4.1.4

Comment Summary 1.7-a: Ten commenters (0075, 0083, 0086, 0096, 0097, 0098, 0109, 0120, 0126,
0133) recommended a de minimis exception for hermetically sealed-pressure equipment in the Subpart
DD source category. Commenters 0075 and 0083 noted that emissions from this type of equipment are
very low—except in the case of catastrophic failure—and that the equipment does not typically require
servicing or recharging of SF6 over its operational lifetime.

Commenter 0075 asserted that "including this equipment in the definition of a 'facility' simply complicates
reporting and verification with essentially no added benefit or value to the reporting rule or the
compilation of total SF6 emissions."

Since hermetically sealed-pressure equipment is non-serviceable, Commenter 0083 recommended
excluding the equipment by using the following language in §98.302—GHGs to Report: "You must report
total SF6 and PFC emissions (including emissions from fugitive equipment leaks, installation, servicing,
equipment decommissioning and disposal, and from storage cylinders) from the following types of
serviceable equipment: (a) Gas-insulated substations (b) Circuit breakers (c) Switchgear (d) Gas-
insulated lines (e) Electrical transformers."

Commenter 0086 recommended three options for reducing the burden associated with inventorying
hermetically sealed-pressure equipment for the §98.302 Data Reporting Requirement for system-wide
nameplate capacity of equipment containing SF6. The three recommended options provided by
commenter 0086 were as follows: "(1) establish a de-minimus capacity for specific equipment below
which the equipment would be exempt from the inventory requirements, (2) clarify that, after an initial
inventory, smaller pieces of equipment do not need to be included in annual inventories, or (3) for smaller
equipment, such as switches, allow affected entities the option of estimating the volume of small
equipment and assuming a maximum nameplate amount of SF6 for each one."

Commenters 0094 and 0096 recommended excluding "small distribution equipment, containing less than
35 pounds of SF6" from reporting. Commenter 0094 did not think that tracking small equipment is

November 8, 2010

Subpart DD—Response to Comment Document

14


-------
efficient, and notes that while approximately 43% of its circuit breakers have less than 35 lbs of SF6,
distribution equipment accounts for only 2% of its total SF6 emissions.

Commenter 0120 recommended a de minimis exception for equipment containing less than 15 pounds,
or a complete reporting exception for all distribution equipment. Commenter 0133 recommended a de
minimis exception for sealed-pressure equipment in the context of the §98.302 Data Reporting
Requirement for system-wide nameplate capacity of equipment containing SF6, and noted that this would
not exclude hermetically sealed-pressure equipment from being captured in the mass-balance emissions
monitoring method since the system-wide nameplate capacity is not an input to the mass-balance
equation.

Response 1.7-a: Comments regarding the inclusion of sealed-pressure equipment in reporting
requirements that were received after EPA's second Subpart DD proposal in 2010 were very similar to
the comments received in EPA's first Subpart DD proposal from 2009. Please see Response 1,6-a or
Subpart DD Final Preamble, Section III, "Summary of Comments and Responses" for EPA's response.

Comment Summary 1.7-b: Commenter 0096 thought that tracking of SF6 from hermetically sealed-
pressure equipment "would be better performed by upstream reporting of SF6 by original equipment
manufacturers (OEMs) where it would be much easier for OEMs to report a complete picture of small
sealed equipment sold in the United States." Commenter 0097 supports this notion by stating that
hermetically sealed-pressure equipment is a case where "upstream regulation of SF6 is more effective,
specifically at the original equipment manufacturer."

Response 1.7-b: Under Subpart SS—Electrical Equipment Manufacture and Refurbishment and
Manufacturing of Electrical Components, OEMs must monitor emissions that occur from the manufacture
of sealed-pressure as well as include sealed-pressure equipment in their data reporting requirements.
However, this does not render the inclusion of sealed-pressure equipment in subpart DD reporting
requirements unnecessary. The potential for emissions from sealed-pressure equipment due to
catastrophic events or equipment disposal still makes it important for electrical equipment users to
document emissions from sealed-pressure equipment, especially for Subpart DD facilities that are highly
involved in electricity distribution. While emissions from sealed-pressure equipment must be monitored
by Subpart DD facilities, EPA has removed the requirement for including sealed-pressure equipment as
part of the data reporting requirement for total facility-wide nameplate capacity existing as of the
beginning of the year.

Comment Summary 1.7-c: Commenter 0109 provided separate recommendations for three different
types of sealed pressure equipment: transmission, distribution—SF6 gas insulated, and distribution—SF6
gas insulated/interrupting. The commenter thought it was reasonable for sealed-pressure transmission
equipment to be included in reporting since the typical mass of SF6 in each piece is between 5 and 18
pounds, and "there are facilities with a good quantity of devices (typically identified as circuit switchers)
yielding significant nameplate capacity." The commenter stated that the "interrupting type" used in
distribution applications has not been available in the U.S. for many years, and should only be included in
reporting if this type of equipment represents more than 0.5% of total nameplate capacity. Lastly, the
commenter stated that reporting on "distribution equipment with SF6 as an insulating gas at very low
pressure (typically less than 1 atmosphere)" would be a significant issue since this equipment holds such
small amounts of SF6 and the "administrative burden of estimating the nameplate capacity and tracking
this distributed distribution equipment is extremely high."

Response 1.7-c: EPA appreciates the commenter's detailed delineation of the various types of sealed-
pressure equipment as well as the commenter's thoughts on the appropriateness of including each type
of sealed-pressure equipment in the Subpart DD reporting requirements. Due to the need for simplicity in
knowing when to include a piece of equipment in the reporting requirements as well as the potential for
emissions from sealed-pressure equipment used for electricity distribution, EPA is requiring that SF6
arriving inside all types of newly acquired sealed-pressure equipment must still be considered as part of
the SF6 acquisitions input of the mass-balance equation, and all types of sealed-pressure equipment that
is new or retired must be considered as a change to the nameplate capacity in the mass-balance
equation. But in an effort to reduce the overall burden for affected entities, EPA has excluded all types of

November 8, 2010

Subpart DD—Response to Comment Document

15


-------
sealed-pressure equipment from the data reporting requirement for total facility-wide nameplate capacity
existing as of the beginning of the year.

1.8 Other (Definition of Source Category)

Relevant Bin Number: 4.1
Track 1

Comment Summary 1.8-a: Two commenters (0612,1741) requested clarification on exactly what
equipment is included in the Subpart DD source category. Commenter 0612 specifically requested
clarification on whether scientific research equipment that contains SF6 would be included in the electrical
equipment regulated in Subpart DD. Commenter 1741 sought clarification on whether processes that use
SF6 as a testing gas would be regulated in Subpart DD.

Response 1.8-a: The Subpart DD source category includes all SF6 and PFC insulated equipment and
servicing inventory that is used within an electric power system. For a definition of the electric power
system facility, see Subpart DD §98.307-Definitions. If the SF6-insulated equipment and servicing
inventory discussed by the commenters are used within an electric power system, then the equipment
and servicing inventory would be covered under Subpart DD even if the equipment is not listed in
§98.307-Definition of the Source Category.

The subpart A General Provisions (40 CFR 98.2 - 98.4) do exclude research and development activities
from being covered by the source categories provided in the rule. Research and development activities
are defined in subpart A as those activities conducted in process units or at laboratory bench-scale
settings whose purpose is to conduct research and development for new processes, technologies, or
products and whose purpose is not for the manufacture of products for commercial sale, except in a de
minimis manner.

Track 2

Comment Summary 1.8-b: Commenter 0109 explained that the use of SF6 in transformers is not
widespread due to largely unsuccessful experimental trials using SF6 insulated transformers. The
commenter recommended that due to the high administrative burden for tracking and reporting this non-
switchgear equipment, EPA establish "a minimum threshold on quantity to trigger reporting (i.e. 2 or more
transformers)."

Response 1.8-b: Although the use of SF6 in electric power transformers might not be as widespread as
SF6 use in other types of electrical equipment, there is still the potential forSF6 emissions from SF6-
insulated transformers that are actively in use in the United States today. Furthermore, SF6-insulated
transformers are marketed to electrical equipment users in the United States, and it is unclear how much
of this equipment will be utilized in the future. Due to the potential for emissions from electric power
transformers currently in use as well as the potential for an increase in the use of these transformers,
EPA is not providing reporting exceptions for SF6-insulated transformers in the Subpart DD source
category.

November 8, 2010

Subpart DD—Response to Comment Document

16


-------
2. Reporting Threshold

Relevant Bin Number 4.2
Track 1

Comment Summary 2-a: Commenter 0413 questioned why EPA "appears to be requiring reporting of
very minor SF6 gas emissions when nameplate capacity exceeds 17,820 pounds, while a larger emission
from electrical equipment with lower SF6 nameplate capacity equipment will be unreported."

Response 2-a: The 17,820 pound threshold was developed as a nameplate-based approximate of the
25,000 metric tons of C02 equivalent threshold. The nameplate capacity equivalent to a 25,000 metric
ton of C02 equivalent was estimated using data reported by Partners in EPA's SF6 Emission Reduction
Partnership for Electric Power Systems. EPA's threshold analysis showed that the 17,820 pound
nameplate capacity threshold would cover a small percentage of the total electric utilities in the United
States (approximately 10%) while covering a large percentage of annual SF6 emissions from electric
power systems in the United States (approximately 83 percent). A nameplate capacity-based threshold
was chosen because it allows potential sources to determine whether they are above or below the
threshold much quicker than if the sources had to measuring emissions for this determination, thereby
reducing the burden for the industry as a whole. While it is possible that a facility with less than 17,820
pounds of nameplate capacity has greater SF6 emissions than a facility with greater than 17,820 pounds
of nameplate capacity, EPA's analysis concluded that nameplate capacity is strongly correlated with SF6
emissions, more so than other parameters like high-voltage transmission miles. For more information on
EPA's threshold analysis, please see the TSD located here:
www.epa.gov/climatechange/emissins/ghgrulemaking.html

Comment Summary 2-b: Commenters 0551, 0479, and 0547 agreed with the 17,820 pounds of SF6
nameplate capacity threshold proposed by EPA for subpart DD. Commenters 0479 and 0547 noted that it
allows potential sources to quickly determine whether they are covered.

Response 2-b: EPA appreciates the commenters' support of the reporting threshold.

2.1 Threshold Analysis—Track 1

Relevant Bin Number 4.2.1

Comment Summary 2.1 -a: Commenter 0413 stated that "no peer review scientific evidence exists to link
nameplate capacity with actual SF6 gas emissions or leakage." The commenter disagreed with EPA's
method for calculating the 17,280 pounds of SF6 nameplate capacity threshold for subpart DD.
Specifically, the commenter considered the use of 1999 weighted utility leak rates of SF6 to be inaccurate
since utilities currently emit SF6 at lower rates than they did in 1999. The commenter thought a "more
rational assumption would be leakage rates well below 1% annually."

Response 2.1-a: The relationship between nameplate capacity (how much SF6 equipment contains
when full) and the amount of SF6 emissions that occur from equipment is not perfect; other factors such
as equipment age and geographic location can have an impact on emissions. Nonetheless, EPA's
analysis showed that nameplate capacity is a strong correlate to SF6 emissions and stronger than other
potential correlates such as high-voltage transmission miles. EPA used 1999 weighted leak rates from 42
Partners of EPA's SF6 Emission Reduction Partnership for Electric Power Systems (1999 was the first
year that the Partnership received data) because it is assumed that utilities who have not participated in
the Partnership activities have not achieved the emission reductions from 1999-2008 that have been
achieved by Partners, and it was essential that a non-emissions based threshold be conservative enough
to ensure that sources emitting more than 25,000 metric tons of C02 equivalent were covered by the
threshold. EPA does not consider the leakage rates of "well below 1% annually" to be a rational
assumption since the average Partnership leak rates have never been below 4% since the inception of
the Partnership.

November 8, 2010

Subpart DD—Response to Comment Document

17


-------
2.2 Other (Reporting Threshold)

Relevant Bin Number 4.2.2

Track 1

Comment Summary 2.2-a: Commenter 0547 stated that "EPA should recognize that nameplate
capacity inventory of in-service power systems is achievable for distinct facilities such as substation sites
but would be virtually impossible for most power systems in the transmission and distribution lines
system."

Response 2.2-a: EPA is assuming the commenter is stating that it would be virtually impossible for an
entity that transmits and distributes electricity to determine the entire system-wide nameplate capacity of
all equipment within its electric transmission and distribution system. Contrary to the opinion of the
commenter, many electric power entities in EPA's SF6 Emission Reduction Partnership for Electric Power
Systems have provided system-wide nameplate capacity estimates to EPA for all SF6-insulated
equipment within the system except sealed-pressure equipment used for electricity distribution.

Comment Summary 2.2-b: Commenter 1569 remarked that "There are some pieces of electrical
equipment that do not list the capacity of SF6 in pounds on the nameplate, but rather give the pressure of
SF6 in the system in pounds per square inch (psig). It is our recommendation that the EPA establish a set
protocol to use to calculate the weight of SF6 in the equipment based on a set pressure and temperature
when the weight is not explicitly listed on the nameplate."

Response 2.2-b: EPA understands that in some cases the capacity of a piece of equipment is not clearly
affixed to the equipment itself. In these cases, EPA recommends contacting the original manufacturer of
the equipment, who should be able to provide the nameplate capacity of the equipment.

Track 2

Comment Summary 2.2-c: Commenter 0126 stated that "EPA is proposing to add electric power
systems to the list of "all-in" source categories in 40 CFR 98.2(a)(1). The reason for EPA's proposal is
that electric power systems have a production capacity or gas consumption threshold rather than a C02e
emission threshold. Sources in the "all-in" category must report emissions from all source categories for
which calculation methodologies are provided in any subpart of the rule." The commenter questions why
EPA would abandon the concept of a C02e emission threshold for SF6 and PFC that existed in 2009 (for
the initial proposal) and instead "consider in its current proposal a production capacity or a gas
consumption threshold."

Response 2.2-c: The 17,820 pound nameplate capacity threshold for Subpart DD proposed in 2010 was
the same threshold as proposed in 2009. The reason EPA is listing Subpart DD as an "all-in" category is
because the threshold for Subpart DD is capacity-based rather than a C02e emission threshold. EPA
notes that if a facility contains either an "all-in" source category listed in §98.2(a)(1) or a source category
listed in §98.2(a)(2) that triggers the 25,000 metric ton of C02e threshold, the facility must report for all
applicable source categories listed in Table A—3 and Table A—4 of subpart A that are triggered by the
facility. But EPA also notes that an electric power system facility (as specifically defined in subpart DD)
only encompasses electric transmission and distribution equipment and servicing inventory insulated with
or containing SF6 or PFCs; as such, the electric power system facility boundaries do not extend to
emission sources other than the electric transmission and distribution equipment and servicing inventory.

November 8, 2010

Subpart DD—Response to Comment Document

18


-------
3. GHGs to Report—Track 1

Relevant Bin Number 4.3

Comment Summary 3-a: Commenter 0661 asked "EPA to clarify whether PFCs are based on
nameplates or whether mass balances can be used to assess PFC emissions."

Response 3-a: PFC emissions must be measured in the exact same manner as SF6 emissions using the
mass balance monitoring methods provided in §98.302.

Comment Summary 3-b: Commenter 1569 noted that sometimes SF6 is emitted or destroyed due to a
lightning strike or fire, and recommended that EPA exempt emissions of SF6 from a force majeure event,
or at least establish a separate reporting section for those cases.

Response 3-b: Emissions of SF6 that occur from a force majeure event are not exempted from the
Subpart DD reporting requirements. The mass-balance monitoring methods required for Subpart DD are
designed for a system-wide emissions measurement and are not conducive for use in measuring
emissions occurring from specific events affecting specific pieces of equipment. The commenter should
note that the purpose of the Mandatory Reporting Rule is to collect emissions data; the rule does not
penalize facilities based on the quantity of their emissions.

November 8, 2010	Subpart DD—Response to Comment Document

19


-------
4. Detailed GHG Emission Calculation Procedures/Equations

Relevant Bin Number 4.4
Track 1

Comment Summary 4-a: Commenter 0096 requested that EPA allow for flexibility for "higher quality,
direct measurement data when available" in place of the proposed mass-balance method. The
commenter stated that the objective of EPA's proposed regulation can be "best accomplished by looking
at the amount of SF6 added to equipment which would equate to loss of SF6 as emissions. For example,
a company may have the actual weight of SF6 added to equipment during the year based on actual SF6
use which is a far better measure that simply looking at a mass balance for that year. The use of SF6
may be determined by the weight difference between the amount SF6 purchased (full bottle) and the
remaining amount of SF6 in an empty bottle of SF6. In other cases a company may actually weigh the
amount of SF6 gas added to each piece of equipment."

Response 4-a: The monitoring methods required by Subpart DD to measure SF6 emissions are based
on the IPCC Tier 3 method provided in the peer-reviewed 2006IPCC Guidelines for National
Greenhouse Gas Inventories. The Tier 3 mass balance method is considered by IPCC to be the most
accurate method for measuring SF6 emissions from electric power systems. Observing the amount of SF6
that is charged into leaky equipment might be a useful tool for estimating emissions from a specific piece
of equipment, but this direct measurement completely overlooks potential emissions that can occur
elsewhere within an electric power system. For example, if a circuit breaker is decommissioned from the
electric power system and the SF6 within the breakers is vented into the atmosphere, the direct
measurement method described by the commenter would not capture these emissions. Another example
of emissions that would not be captured using the commenter's method would be emissions that occur
from a faulty cylinder valve.

Track 2

Comment Summary 4-b: Commenter 0096 argued that the mass-balance formula should not include
annual nameplate capacity changes since these changes have "no bearing on the amount of SF6 used
during the year." The commenter stated that instead of using the annual change in nameplate capacity,
"a single system capacity value, such as the start of the year capacity, should be used in the SF6 leak
rate formula."

Response 4-b: The annual nameplate capacity change is essential to include in the mass-balance
monitoring methods for Subpart DD in order to measure emissions accurately. The mass-balance
method works by systematically accounting for all SF6 uses within the system. The amount of SF6 that
cannot be accounted for by the electric power system is equal to the emissions during the year since the
unaccounted for SF6 was not recorded as being used in a non-emissions context (such as the SF6 being
sent offsite for recycling or added to the storage inventory). Assessing the changes in nameplate capacity
plays an integral role in accounting for SF6 gas uses. For example, if new equipment is purchased during
the year and the equipment is filled with SF6 stocks from the user's storage inventory, then the nameplate
capacity of the new equipment must be used to reconcile the amount of SF6 that was withdrawn from
inventory, otherwise the amount of gas withdrawn from the storage inventory would register as an
emission.

November 8, 2010

Subpart DD—Response to Comment Document

20


-------
5. Monitoring and QA/QC Requirements

Relevant Bin Numbers: Section 4.5

Track 1

Comment Summary 5-a: Commenter 0608 stated that it is very difficult to weigh the amount of SF6 in
gas carts with on board storage vessels to an accuracy of 1 percent. This commenter's current practice is
to estimate the weight of gas carts with onboard storage vessels using engineering calculations.
Commenter 0608 noted that the "weighing method is based on a pivoting table single point measuring
system and removal of individual cylinders from the gas carts is difficult." The commenter also explained
that large carts are also used that have non-removable tanks on trailers; the proposed rule would require
the weighing of the entire trailer, which would not yield an accurate measurement of gas because of
"other materials such as compressor fluid and filter material which vary overtime." The commenter
requested "a more pragmatic approach that tracks its current business practice: (1) cylinders should be
weighed at the beginning and end of each reporting period; 2) the weight of SF6 in gas carts with onboard
storage vessels may be calculated using the current methodology; and (3) the manufactured supplied
and installed weighing system in gas carts with onboard SF6 cylinders should be permitted. By allowing
[the commenter] to continue its current practices, US EPA would reduce the reporting burden and still
achieve its aim of gathering emissions data." Commenter 0608 also explained that this approach is
consistent with methods provided for under the Climate Registry Protocol for reporting SF6 emissions
from Electricity Transmission and Distribution systems.

Response 5-a: After assessing concerns among numerous reporters about the proposed scale accuracy
requirements, EPA eased the scale accuracy requirement from a relative requirement of 1% of true
weight to an absolute requirement of+/- 2 pounds of true weight. In addition, EPA has removed the
proposed requirement in §98.306 (b)(2) for weighing storage cylinders as they enter and leave the
storage inventory and clarified that the QA/QC requirements for scale accuracy and calibration apply only
to cylinders returned to the gas supplier and cylinders weighed at the beginning and end of each year for
the beginning and end-of-year storage inventory. EPA also examined the use of engineering calculations
and alternative techniques other than scale weighing for determining SF6 weight. Due to the unreliability
of the most commonly used engineering calculations for weighing gas, such as using temperature and
pressure readings, EPA determined that such methods are not suitable for the Subpart DD mass-balance
monitoring methods, which rely on highly accurate inputs. For more information on the potential issues
with using engineering calculations to determine the weight of SF6, see comment response 5.1-b. For
more information on the necessity for highly accurate mass-balance inputs, see comment response 5.2-
a.

5.1 Frequency of Weighing Cylinders—Track 1

Relevant Bin Numbers: Section 4.5, 4.5.1, and 4.5.3

Comment Summary 5.1-a: Ten commenters (0455, 1021, 0608, 0624, 0618, 1566, 0902, 0479, 0547,
1645) disfavored EPA's proposed requirement of weighing gas cylinders each time they leave and enter
storage. Commenter 1021 noted that EPA does not explain what purpose weighing cylinders leaving and
entering storage in addition to the weighing of cylinders at the beginning and the end of every year would
serve.

Commenter 0455 asserted that "weighing cylinders twice each time they are used, 'as they are leaving
and entering storage,' would result in a significant increase in worker hours." Commenters 0455, 0624,
0618, and 1566 suggested that SF6 cylinders could be monitored by taking initial measurement of SF6
stored in containers, combined with the submission of records tracking subsequent SF6. This approach,
they stated, would be less costly than monitoring requirement proposed in §98.304(b)(2).

Commenters 0479 and 0547 are concerned about the potential administrative burden and health and
safety issues associated with frequent cylinder weighing by substation personnel, and preferred a
standardized approach that relies on SF6 vendors and recyclers to provide weighing services of the
delivered cylinders and residual gas upon return of the cylinder. These commenters believed that SF6
November 8, 2010	Subpart DD—Response to Comment Document	21


-------
vendors and recyclers are better prepared to report this information, as they already employ procedures
to weigh cylinders using scales that are routinely maintained and calibrated.

Commenter 0902 noted that the "rule as written will require employees to manually lift and weigh each
tank of SF6 in order to gather the information needed in the reporting process. Because a full tank of SF6
weighs over 200 lbs., increased handling of cylinders could increase risk of worker injury." Commenter
0902 favored the use of alternate methods of information gathering, stating that, "although current
technology requires weighing gas cylinders to obtain an accurate measurement of SF6 usage, future
reporting need not be limited to this inherently unsafe method of information gathering. An alternate
method of data collection that meets the stated accuracy requirements will allow reporting methods to
keep pace with advances in technology."

Commenters 1645 and 0608 favored the approach used under the existing voluntary program between
electric power systems and EPA. Commenter 1645 noted that, "although the interim weighing of cylinders
as they are used, handled, and relocated may have internal inventory value to the user, this information
is not necessary for accurate annual reporting, and can add significantly and unnecessarily to an
organization's labor burden and bookkeeping requirements, if mandated by the reporting rule."
Commenter 0608 asserted that individual cylinder weighing is impractical and questionably cost effective
given that at each facility, cylinders may leave and enter storage 20 times per year.

Response 5.1-a: EPA agrees that the benefit of weighing SF6 gas cylinders as they enter and leave
inventory does not justify the costs of performing this activity. EPA has removed this requirement from §
98.306 (b)(2) and clarified that the QA/QC requirements for scale accuracy and calibration apply to
cylinders returned to the gas supplier and cylinders weighed at the beginning and end of each year for
the beginning and end-of-year storage inventory.

Comment Summary 5.1-b: Commenter 1566 suggested that instead of weighing cylinders to track the
quantity of contained SF6, the pressure of the gas could be measured using a standard pressure gauge
and the mass calculated using the ideal gas law. Commenter 1566 noted, "considering the relatively de
minimis greenhouse gas emissions resulting from use and handling of SF6, this method of tracking the
SF6 content in cylinders in lieu of weighing cylinders should be sufficient."

Response 5.1-b: Measuring the amount of SF6 in cylinders using temperature and pressure calculations
is not an adequate method for weighing SF6 cylinders in the context of mandatory reporting since SF6 in
a cylinder can be in both a gaseous and liquefied state, thereby making pressure readings unreliable. For
example, in cases where gas extraction from the cylinder has cooled the temperature of SF6 liquid in the
cylinder to the point where it will no longer vaporize, a zero PSIG pressure reading could be read from
the cylinder when there is still SF6 remaining as a heel in the cylinder.

5.2 Frequency of Weighing Cylinders—Track 2

Relevant Bin Numbers: Section 4.5, 4.5.1, and 4.5.3

Comment Summary 5.2-a: Four commenters (0133, 0097, 0098, 0083) disfavored EPA's proposed
requirement of weighing gas cylinders each time they leave and enter storage. Commenters 0133 noted
that EPA does not explain what purpose weighing cylinders leaving and entering storage in addition to
the weighing of cylinders at the beginning and the end of every year would serve.

Commenters 0097 and 0098 were concerned about the potential administrative burden and health and
safety issues associated with frequent cylinder weighing by substation personnel, and preferred a
standardized approach that relies on SF6 vendors and recyclers to provide weighing services of the
delivered cylinders and residual gas upon return of the cylinder. These commenters believed that SF6
vendors and recyclers are better prepared to report this information, as they already employ procedures
to weigh cylinders using scales that are routinely maintained and calibrated.

In regards to administrative burden, Commenter 0083 explained that while a spreadsheet maintained by
one person may be appropriate for smaller or densely developed utilities, it is not feasible for a company

November 8, 2010

Subpart DD—Response to Comment Document

22


-------
with transmission operations spanning large geographic areas, which would instead require expensive
software upgrades that can take months or years to install.

Response 5.2-a: EPA agrees that the benefit of weighing SF6 gas cylinders as they enter and leave
inventory does not justify the costs of performing this activity. EPA has removed this requirement from §
98.306 (b)(2) and clarified that the QA/QC requirements for scale accuracy and calibration apply to
cylinders returned to the gas supplier and cylinders weighed at the beginning and end of each year for
the beginning and end-of-year storage inventory.

Comment Summary 5.2-b: Commenters 0097 and 0098 were in favor of EPA permitting the use of best
available estimation methodologies in the first reporting year to limit the administrative burden on industry
to weigh each SF6 cylinder, which would allow facilities flexibility in reporting using a combination of
internal engineering calculations and/or purchase records.

Response 5.2-b: EPA understands that it might be difficult for some entities to employ the monitoring,
data reporting, and QA/QC requirements by the beginning of 2011. Therefore, facilities may use best
available monitoring methods during 2011 to the extent provided in §98.3(d)(1) through (d)(2), with the
date changes specified in the final rule. For more information, see §98.303(a) of the final rule.

5.3 Accuracy and Precision of Scales—Track 1

Relevant Bin Numbers: Section 4.5.2

Comment Summary 5.3-a: Six commenters (0902, 1021, 0618, 0624, 1566, 0608) disagreed with the
proposed scale accuracy language at §98.304(b)(1), that states, "cylinders returned to the gas supplier
are consistently weighed on a scale that is certified to be accurate and precise to within 1 percent of the
true weight", and "If the gas supplier weighs the residual gas, obtain from the gas supplier a detailed
monthly accounting, within 1 percent, of residual gas amounts in the cylinders returned to the gas
supplier" and at §98.304(b)(2), that states, "Cylinders shall be weighed on a scale that is certified to be
accurate within 1 percent of the true weight."

Commenters were concerned about the cost of scales requiring this level of accuracy and the need to
purchase several of them for each site where cylinders are stored. Commenter 0902 stated that they will
have to purchase multiple scales at each location, which span thousands of transmission miles. This
commenter was concerned about the cost of a scale of this accuracy, which is around $1,200 and the
need for several scales, which would result in the expenditure of thousands of dollars."

Commenter 1012 remarked that given the expense of highly accurate scales and the associated worker-
hours with repeated weighing and scale recalibration, EPA should explain "why its chosen
methodology—the mass balance approach—does not provide sufficient information for reporting
purposes such that the additional burden of frequent, highly accurate weighing is justified."

Commenters 0618, 0624, and 1566 were also concerned about the need to purchase and maintain
numerous high-accuracy scales at each facility storing SF6 cylinders, which is costly for monitoring "what
translates to 'de minimis' quantities of GHG emissions."

Commenter 0902 appreciated the necessity for accurate reporting but believed that a one percent
accuracy requirement is arbitrary and unnecessarily burdensome on the industry. Commenter 0902
explained that a one percent requirement will vary greatly within the reporting process. "A scale that is
one percent accurate for a full 220 pound tank of SF6 will not be one percent accurate for a tank
containing only a couple pounds of residual gas being returned to the supplier." Commenter 0902
suggested a maximum variance in pounds rather than a percentage of the true weight. "A requirement
that scales be accurate within two pounds, which is one percent of a full SF6 tank, will reduce the
financial burden on affected companies while still providing accurate reporting." This commenter
explained that "designating a variance in terms of pounds establishes a clearly defined limit, and will
result in more consistent and accurate reporting."

Response 5.3-a: The 1 percent accuracy requirement was proposed by EPA because the mass-balance
method for measuring emissions requires accurate inputs, and the overall uncertainty of the emission

November 8, 2010

Subpart DD—Response to Comment Document

23


-------
estimate rises significantly as the potential inaccuracy of each input increases. However, EPA also
recognizes that the price of scales does increase as the accuracy of the scale increases and that many
electric power entities do not currently use scales that are accurate to within 1 percent of the true weight.

In order to balance the reporting burden with the need for accurate mass-balance inputs, this Final Rule
requires the accuracy and precision of scales used to weigh cylinders to be based on pounds, within +/- 2
pounds of true weight.

EPA deemed the +/- 2 pound accuracy requirement to be an appropriate accuracy level based on a
sensitivity analysis using mass-balance emission estimate data from four different size Partners from
EPA's SF6 Emission Reduction Partnership for Electric Power Systems. The sensitivity analysis involved
testing the effect of five different scale accuracies on the relative uncertainty of the emissions estimates
(on a 95% confidence interval). The five scale accuracies tested included: 1% (relative), 2% (relative), 1
pound (absolute), 2 pounds (absolute), and 1% of full scale at 330 pounds (absolute). Assuming 2%
uncertainty in the nameplate capacity parameters of the mass-balance formula (which are not measured
using scales), the 2 pound scale accuracy requirement resulted in a range of relative uncertainties
among Partners between 1% and 4.4%. The analysis also showed that the 1% relative scale accuracy
resulted in a range of relative uncertainties between 0.5% and 4.1%, and the 5% relative scale accuracy
resulted in a range of relative uncertainties between 2.6% and 6.5%. The complete sensitivity analysis
can be found here: www.epa.gov/climatechange/emissins/ghgrulemaking.html

5.4 Accuracy and Precision of Scales—Track 2

Relevant Bin Numbers: Section 4.5.2

Comment summary 5.4-a: Commenter 0083 stated that they will have to purchase multiple scales at
each location, which span thousands of transmission miles. This commenter was concerned about the
cost of a scale of this accuracy, which is around $2,000 and the need for several scales, which would
result in the expenditure of thousands of dollars. The commenter appreciated the necessity for accurate
reporting but believed that a one percent accuracy requirement is arbitrary and unnecessarily
burdensome on the industry. Commenter 0083 recommended amending §98.304(b)(1) and (2) as
follows:

"(1) Ensure that cylinders returned to the gas supplier are consistently measured by a method certified to
be accurate and precise within 2 pounds, and are recalibrated per the manufacturer's specifications.
Either measure residual gas (the amount of gas remaining in returned cylinders) or have the gas supplier
measure it. If the gas supplier measures the residual gas, obtain from the gas supplier a detailed monthly
accounting, within 2 pounds, of residual gas amounts in each cylinder returned to the gas supplier.

(2) Ensure that procedures are in place to measure all cylinders as they are leaving and entering the
electric power system. Cylinders shall be measured by a method certified to be accurate and precise
within 2 pounds and shall be recalibrated at the frequency specified by the manufacturer."

Commenter 0902 explained that a one percent requirement will vary greatly within the reporting process.
"A scale that is one percent accurate for a full 220 pound tank of SF6 will not be one percent accurate for
a tank containing only a couple pounds of residual gas being returned to the supplier." Commenter 0902
suggests a maximum variance in pounds rather than a percentage of the true weight. "A requirement that
scales be accurate within two pounds, which is one percent of a full SF6 tank, will reduce the financial
burden on affected companies while still providing accurate reporting." This commenter explains that
"designating a variance in terms of pounds establishes a clearly defined limit, and will result in more
consistent and accurate reporting."

Commenter 0133 remarked that given the expense of highly accurate scales and the associated worker-
hours with repeated weighing and scale recalibration, EPA should explain "why its chosen
methodology—the mass balance approach—does not provide sufficient information for reporting
purposes such that the additional burden of frequent, highly accurate weighing is justified."

Response 5.4-a: Please see Response 5.3a for EPA's response to this comment.

November 8, 2010	Subpart DD—Response to Comment Document	24


-------
5.5 Frequency of Scale Calibration

Relevant Bin Numbers: Section 4.5.1 and 4.5.2
Track 1

Comment Summary 5.5-a: Three commenters (0568, Email-034-1, and 1645) did not support a
calibration frequency that requires annual recalibration or the minimum frequency specified by the
manufacturer, whichever is more frequent. Commenter 0568 advocated removing the phrase,

"whichever is more frequent" found at § 98.304(b)(2) because removing this phrase "will allow for the
purchase of a higher quality scale that may not require recalibration as often as once a year, and will not
provide an incentive for the regulated entity to purchase a lower quality scale and replace it yearly." This
commenter stated that "the current wording of the Proposal encourages this practice because the cost of
replacement for scales can be less than the cost in time and money of recalibrating scales." Commenter
Email-034-1 recommended this change because the calibration cycle of the scales they intend to
purchase is every 3 years.

Response 5.5-a: EPA agrees that scale recalibration in accordance with manufacturer specifications is
sufficient and that the incremental costs associated with annual recalibration (when the manufacturer's
specified calibration is less frequent) are not justified. EPA has retained the requirement that recalibration
occur in accordance with manufacturer specifications but removed the requirement for a minimum of
annual recalibration.

Track 2

Comment Summary 5.5-b: Three commenters (0083, 0109, 0115) did not support a calibration
frequency that requires annual recalibration or the minimum frequency specified by the manufacturer,
whichever is more frequent because of cost and logistical reasons. Commenter 0083 stated that "the
manufacturer of the scale is better equipped than the EPA to determine the minimum maintenance
requirements for their own product. Annual certification is costly, time consuming, and most notably
unnecessary."

Response 5.5-b: Please see Response 5.5-a for EPA's response to this comment.

5.6 Other (Monitoring and QA/QC Requirements)—Track 1

Relevant Bin Numbers: Section 4.5.3

Comment Summary 5.6-a: Commenter 1062 "supports the Tier 3 mass-balance protocol as being
adequate as long as good QA/QC procedures are utilized. It is important that reporting methods and
verification be consistent nationally."

Response 5.6-a: EPA appreciates the support of the commenter. §98.303 and §98.305 of Subpart DD
provide numerous QA/QC and data reporting requirements to ensure that data reported to EPA is
accurate and complete.

November 8, 2010

Subpart DD—Response to Comment Document

25


-------
6. Data Reporting Requirements—Track 1

Relevant Bin Numbers: Section 4.7

Comment Summary 6-a: Commenter 0413 said that "EPA is seeking excessively detailed and
redundant information regarding electrical equipment containing SF6 gas." The commenter states that
"the amount of information sought creates a reporting requirement for use of SF6 gas not its emissions
into the atmosphere. This new regulation of'use' is unauthorized and unnecessary as EPA's data
showing significant reduction in SF6 emissions from 1990 to 2007. Congress only authorized reporting of
SF6 gas emission and did not authorize a complex regulatory system for regulating the use of SF6 gas."

Response 6-a: The system-level mass-balance monitoring methods required by Subpart DD are
considered the most accurate and complete method for measuring SF6 emissions for an electric power
system because the method captures emissions that occur anywhere within the system by tracking
system-level SF6 use. This comprehensive monitoring method is important because an electric power
system can span thousands of miles, and emissions can occur from a wide variety of causes throughout
the electric power system including improper gas handling, leaky equipment, and faulty cylinder valves.
While facilities are required to track and document SF6 gas use within the system to yield accurate inputs
for the mass-balance formula, EPA is not regulating how or when SF6 can be used by the facility. For
more information on the selection of monitoring methods for Subpart DD, please see the TSD located
here: www.epa.gov/climatechange/emissins/ghgrulemaking.html For a further detailed response on the
amount of information required to be reported on U.S. greenhouse gas emissions, please see the 2009
Response to Comments Volume 13 - Content of the Annual Report document, comment EPA-HQ-OAR-
2008-0508-0604.1 excerpt 5 (p. 1-2).

Comment Summary 6-b: Commenter 0413 stated that due to the amount of data reporting requirements
required for Subpart DD, "EPA is seeking to create a significant amount of paperwork for utilities, which
have successfully and significantly reduced SF6 emissions" from 1990 to 2007.

Response 6-b: Through the mandatory reporting rule, EPA is seeking to collect accurate and
comprehensive greenhouse gas emissions data to inform policymaking. EPA values the progress made
under the Partnership in reducing emissions, but this does not obviate the need for mandatory reporting.
There are large electric power systems that have not participated in the voluntary Partnership, and the
emissions estimated through the voluntary Partnership have not undergone the QA/QC requirements
necessary to ensure they are reliable enough to inform policymaking. While compiling and reporting
emission data does involve a burden to affected entities, EPA has attempted to minimize the burden as
much as possible while still insuring that emissions data is accurate, complete, and verifiable.

Comment Summary 6-c: Commenter 0413 stated that the reporting requirement for total system-wide
nameplate capacity is excessively detailed because "there should be no need to report if the equipment
is no longer in service."

Response 6-c: The data reporting requirements for Subpart DD require reporting the nameplate capacity
of equipment containing SF6 and the nameplate capacity of equipment containing PFC existing at the
beginning of the year (not including hermetically sealed-pressure switchgear). For purposes of compiling
the system-wide nameplate capacity value, facilities should only include equipment that is energized.
Equipment that is not in service but still contains SF6 should be treated as a part of the storage inventory.

Comment Summary 6-d: Commenters 0902 and 0568 requested clarification on whether the SF6 inside
partially-filled electrical equipment that has been purchased but not yet installed should be considered as
part of the mass-balance input §98.306(h) "SF6 with or inside new equipment purchased in the year" or
the input §98.306(g) "SF6 stored in containers at the beginning and end of the year." Commenter 0568
also requested clarification regarding whether the nameplate capacity of this equipment should be
recorded as new nameplate capacity acquired during the year (if the equipment is not yet installed at the
end of the year).

November 8, 2010

Subpart DD—Response to Comment Document

26


-------
Response 6-d: SF6 that is inside partially-filled electrical equipment that has been purchased by the
facility (i.e., the title has been transferred to the facility) but is not yet installed should be counted as part
of the mass balance input §98.306(h) "SF6 with or inside new equipment purchased in the year" as well
as the mass-balance input §98.306(g) "SF6 stored in containers at the beginning and end of the year"
(assuming the equipment still has not been installed by the end of the year).

Comment Summary 6-e: Commenter 1645 argued that the number of transmission miles for a facility,
as requested in the data reporting requirements of Subpart DD, is not a good metric for correlating with
nameplate capacity and SF6 emissions. The commenter thought a better metric for evaluating "SF6
emission intensity" would be the number of SF6 breakers within an electric power system facility. The
commenter noted that the amount of SF6 emissions associated with transmission miles is largely
dependent on the geographic region of the country and whether the transmission miles are located in
rural or urban areas within specific geographic regions.

Response 6-e: EPA acknowledges that the amount of SF6 used per transmission mile varies depending
on the geographic region where the transmission lines occur. However, EPA's analysis indicated that
transmission miles still correlates strongly with nameplate capacity and SF6 emissions, albeit not as
strongly as the correlation between nameplate capacity and SF6 emissions, and therefore EPA is
requiring transmission miles as a data reporting requirement. (For more information on EPA's threshold
analysis, please see the TSD located here: www.epa.gov/climatechange/emissins/ghgrulemaking.html.)

The number of SF6 breakers within an electric power system facility could also provide useful information.
However, due to the wide-variety of circuit breaker sizes and vintages, which can hold drastically different
amounts of SF6, there is limited usefulness to simply knowing the total number of breakers within an
electric power system facility. Therefore, EPA is not requiring this value as a data reporting requirement.

November 8, 2010

Subpart DD—Response to Comment Document

27


-------
7. Other Subpart DD Comments - Track 1

Relevant Bin Numbers: Section 4.10

Comment Summary 7-a: Commenter 0212 stated that the nameplate capacity approach for Subpart DD
does allow utilities to quickly determine whether they must report, but does not allow utilities to get credit
for reduced emissions, which may be possible even as nameplate capacity increases. The commenter
asked whether EPA has a mechanism to address this going forward. Commenter 0902 suggested that
"EPA adopt an incentive program to encourage continued emission reductions and to offset the additional
reporting costs under the mandatory reporting rule. Utilization of tax or other financial incentives will
provide a business case for companies to aggressively pursue reduction of SF6 emissions."

Response 7-a: The purpose of the Mandatory Reporting Rule is to collect accurate and comprehensive
data on the amount of greenhouse gases emissions from various sources to help inform policymaking.
EPA does not have a mechanism for providing financial incentives for greenhouse gas emission
reductions through the Mandatory Reporting Rule because such incentives would be outside the scope of
the rule.

Comment Summary 7-b: Commenter 0555, after reviewing the mechanisms for the use of SF6 in
electrical equipment, "applaud[s] EPA for a substantial document, and agree that the general
methodology for SF6 emissions from electric power systems is feasible."

Response 7-b: EPA appreciates the support from the commenter.

Comment Summary 7-c: Commenter 1569 agreed that greenhouse gas emission reports for Subpart
DD should be submitted on an annual basis since more frequent reporting using the mass-balance
emission measurement methods could result in errors.

Response 7-c: EPA appreciates commenter's support of annual reporting.

November 8, 2010

Subpart DD—Response to Comment Document

28


-------
8. Other Subpart DD Comments - Track 2

Relevant Bin Numbers: Section 4.10

Comment Summary 8-a: Commenter 0075 noted that "the proposed rule does not address the small
quantities of SF6 used as a tracer for leak detection in pressurized systems, such as nuclear power plant
boiler tubes."

Response 8-a: EPA appreciates the commenter's concern about other uses of SF6 that are not covered
by the rule. The purpose of the Mandatory Reporting Rule is to collect greenhouse gas emissions data
from significant sources without subjecting small sources to a reporting burden. EPA is not currently
aware of significant SF6 emissions occurring from its use as a tracer gas for leak detection in pressurized
systems, but will continue to examine whether significant greenhouse gas emissions occur from sources
not currently covered by the Mandatory Reporting Rule.

Comment Summary 8-b: Commenter 0128 supported EPA's inclusion of fluorinated greenhouse gas
reporting provisions for electric transmission and distribution use and thought it will enhance the overall
accuracy of EPA's greenhouse gas reporting rule and help the agency move towards a "truly
comprehensive inventory of national GHG emissions."

Response 8-b: EPA appreciates the support from the commenter.

November 8, 2010

Subpart DD—Response to Comment Document

29


-------
Appendix A - List of Commenters Sorted by Submission Number

Submission No.

Commenter

Organization

EPA-HQ-OAR-2009-0927-0075

Kenneth Boyd

Southern Company

EPA-HQ-OAR-2009-0927-0081

Kenneth Boyd

Southern Company

EPA-HQ-OAR-2009-0927-0083

Deborah Boyle

Oncor





Dominion Resource

EPA-HQ-OAR-2009-0927-0086

Pamela F. Faggert

Services, Inc.





Western Business

EPA-HQ-OAR-2009-0927-0087

Holly Propst

Roundtable





National Rural Electric

EPA-HQ-OAR-2009-0927-0088

Carol Whitman

Cooperative Association

EPA-HQ-OAR-2009-0927-0094

Alexander G. Taft

National Grid

EPA-HQ-OAR-2009-0927-0096

Bruce D. Alexander

Exelon Corporation

EPA-HQ-OAR-2009-0927-0097

Michael Bradley

The Clean Energy Group

EPA-HQ-OAR-2009-0927-0098

Rayburn L. Butts

Nextera Energy, Inc.

EPA-HQ-OAR-2009-0927-0101

Scott Davis

Arizona Public Service

EPA-HQ-OAR-2009-0927-0109

McCabe

American Electric Power

EPA-HQ-OAR-2009-0927-0115

Michael B. McNulty

ITC Holdings





The Dow Chemical

EPA-HQ-OAR-2009-0927-0119

Rob Rouse

Company

EPA-HQ-OAR-2009-0927-0120

Ruthanne Calabrese

Northeast Utilities

EPA-HQ-OAR-2009-0927-0125

Eric Hsieh

National Electric Managers
Association

EPA-HQ-OAR-2009-0927-0126

Wesley McNealy

Pepco Holdings, Inc.

EPA-HQ-OAR-2009-0927-0127

Gregory Ryan

DTE, Energy





Environmental Defense

EPA-HQ-OAR-2009-0927-0128

Pamela Campos

Fund

EPA-HQ-OAR-2009-0927-0133

Quinlan Shea

Edison Electric Institute

EPA-HQ-OAR-2008-0508-0212

Emily Fisher

Edison Electric Institute

EPA-HQ-OAR-2008-0508-0407

Michael Stroben

Duke Energy Corporation,





Environmental Task Force





of the Northwest Public

EPA-HQ-OAR-2008-0508-0413



Power Association

EPA-HQ-OAR-2008-0508-0455

Debra Jezouit

Class of'85 Regulatory
Response Group

EPA-HQ-OAR-2008-0508-0479

Michael Bradley

The Clean Energy Group

EPA-HQ-OAR-2008-0508-0547

Wesley McNealy

Pepco Holdings, Inc.

EPA-HQ-OAR-2008-0508-0551

Delaine Shane

Metropolitan Water District
of Southern California,

EPA-HQ-OAR-2008-0508-0555

Kyle Pistor

NEMA





American Transmission

EPA-HQ-OAR-2008-0508-0568

Rita Hayen

Company LLC

EPA-HQ-OAR-2008-0508-0584

Nicole Mcintosh

Consumers Energy

EPA-HQ-OAR-2008-0508-0597

Angila Retherford

Vectren

EPA-HQ-OAR-2008-0508-0608

Linda Sullivan

National Grid

EPA-HQ-OAR-2008-0508-0612

Andrew Lawrence

Department of Energy

EPA-HQ-OAR-2008-0508-0618

Vincent Brisini

RRI Energy, Inc.

EPA-HQ-OAR-2008-0508-0624

Joseph Miakisz

FPL Group





Arizona Public Service

EPA-HQ-OAR-2008-0508-0639

Scott Davis

Company

EPA-HQ-OAR-2008-0508-0661

J.P. Blackford

American Public Power

November 8, 2010

Subpart DD—Response to Comment Document

30


-------
Submission No.

Commenter

Organization





Association

EPA-HQ-OAR-2008-0508-0685

Helen A. Howes

Exelon Corporation

EPA-HQ-OAR-2008-0508-0725

John McManus

American Electric Power

EPA-HQ-OAR-2008-0508-0902

Deborah Boyle

Oncor Electric Delivery

EPA-HQ-OAR-2008-0508-1021

Quinlan Shea

Edison Electric Institute

EPA-HQ-OAR-2008-0508-1062

Matthew Frank

State of Wisconsin

EPA-HQ-OAR-2008-0508-1080

Kelly Carmichael

NiSource

EPA-HQ-OAR-2008-0508-1566

Robbie LaBorde

Cleco Corporation

EPA-HQ-OAR-2008-0508-1569

Patricia Meehan

New York Power Authority

EPA-HQ-OAR-2008-0508-1645



Southern Company

EPA-HQ-OAR-2008-0508-1741

Pamela Faggert

Dominion





Bonneville Power

EMAIL-034

Steve Lowder

Administration

Trans-DC-04

Dan Chartier

Edison Electric Institute

November 8, 2010

Subpart DD—Response to Comment Document

31


-------