DRAFT

ECMPS Emissions
Check Specifications

United States Environmental Protection Agency
Office of Air and Radiation
Clean Air Markets Division

Ariel Rios Building
1200 Pennsylvania Avenue
Washington, DC 20460

September 17, 2014


-------

-------
Table of Contents

Appendix D and E Status	1

Daily Calibration Status	35

Daily Calibration Test	47

Daily Emissions Data	95

Daily Interference Status	111

Daily Test	118

Flow-to-Load Status	125

Hourly Aggregation	138

Hourly Appendix D	185

Hourly Appendix E	247

Hourly Apportionment	263

Hourly Calculated Data	280

Hourly Derived Data	338

Hourly General	404

Hourly Monitor Data	433

Hourly Operating Data	488

Leak Status	542

Linearity Status	551

LME	578

RATA Status	631


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Appendix D and E Status

Environmental Protection Agency

Page 1 of667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	ADESTAT-1

Check Name:	Determine Appendix E Status

Related Former Checks:

Applicability:

Description:

Validation Tables:

Fuel Code (Lookup Table)

Specifications:

Set PriorAppendixERecord = null.

Set InvalidAppendixERecord = null.

Set CurrentAppendixEStalus = null.

Set PriorAppendixEEventRecord = null.

Set SubsequentAppendixERecord = null
Set AppendixEMissingOpDalalnfo = null.

If (App E Op Code in set {N, W, X, Y, Z} ) AND AppENOXE System ID is not null)

Append AppE NOXE System ID to NOXE System ID Array.

Locate the most recent record in AppendixETestRecordsByLocationForQAStatus for the location where the SystemID is equal to
the AppE NOXE System ID and the TestResultCode is not equal to "INVALID" and the EndDate/Hour is prior to the
CurrentOperatingDate/Uour.

if (AppendixETestRecordsByLocationForQAStatus is found)

Set PriorAppendixERecord = the found record in AppendixETestRecordsByLocationForQAStatus.

Locate the most recent record in AppendixETestRecordsByLocationForQAStatus for the location where the SystemID is
equal to the AppENOXESystemID and the TestResultCode is equal to "INVALID" and the EndDate/Hour is prior to the
CurrentOperatingDate/Uour and the EndDate/Hour is greater than the I'riorAppendixIJRecord.\.nd\>dlc I lour.

if (AppendixETestRecordsByLocationForQAStatus is found)

Set InvalidAppendixERecord = the found record in AppendixETestRecordsByLocationForQAStatus.

else

Locate the most recent record in AppendixETestRecordsByLocationForQAStatus for the location where the SystemID is
equal to the AppE NOXE System ID and the TestResultCode is equal to "INVALID" and the EndDate/Hour is prior to the
CurrentOperatingDate/Uour.

if (AppendixETestRecordsByLocationForQAStatus is found)

Set InvalidAppendixERecord = the found record in AppendixETestRecordsByLocationForQAStatus.
if (PriorAppendixERecord is not null)

if {PriorAppendixERecord.QANeedsEvaluationFlag = "Y")

Set CurrentAppendixEStalus = "Prior Test Not Yet Evaluated",
else if (PriorAppendixERecord.TestResuitCode = null)

Set CurrentAppendixEStalus = "OOC-Prior Test Has Critical Errors".

Environmental Protection Agency

Page 2 of667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Set PriorTestExpirationDate = Prior. 1 ppendixERecord. Tc s t H \ p i rat i o n Da tc

if (PriorTestExpirationDate is null)

Set PriorTestExpirationDate = 5 years (20 calendar quarters) after the end of the quarter of the
I'riorAppendixERecord.I Indl )atc I lour.

if (CurrentOperatingDate/Hour is AFTER the PriorTestExpirationDate)

Set CurrentAppendixEStatus = "OOC-Expired".

Locate the most recent record in QACertificalionEventRecords where the SystemID is equal to the
AppENOXESystemID and the RequiredTestCode is equal to 75 and the QACertEventDate/Hour is prior to
the CurrentOperatingDate/Hour and theQACertEventDate/Hour is on or after the
I'riorAppendixE Record.I Indl )atc I lour

if (QACertificationEventRecords is found)

Set PriorAppendixEEventRecord = the found record in QACertificationEventRecords.

if (the number of calendar days ON OR AFTER the

Prior. ippendix/J^ventRecord.QACa l] .\cnll )dlc and ON OR BEFORE the
CurrentOperatingDate/Hour > 180)

Set CurrentAppendixEStatus = "OOC-Event".

else if (PriorAppendixEEventRecord .MinOpDaysPriorQuarter is null)
Set PriorAppendixEEventRecord MinOpDaysPriorQuarter = 0
Set PriorAppendixEEventRecord MaxOpDaysPriorQuarter = 0

for each quarter beginning with the quarter of the

PriorAppendixEEventRecord.QACertEventDate and continuing through the quarter
BEFORE the CurrentOperatingDate/Hour.

if (EarliestLocationReportDate <= the last day of the quarter being checked)

Locate the record in OperatingSuppDataRecordsbyLocation where the
OpTypeCode is equal to "OPDAYS" and the reporting period is equal to
the quarter being checked.

if (OperatingSuppDataRecordsbyLocation is not found)

else

Set P^iorAppendixEEventRecord.MinOpDaysPnorQuarter = -1
Set AppendixEMissingOpDatalnfo = "[YEAR] Q[QTR]"
(where [YEAR] is the year of the quarter being checked and
[QTR] is the number of the quarter being checked,
exit for.

else

If the quarter being checked is the quarter of the
PriorAppendixEEventRecord.QACertEventDate

If (OperatingSuppDataRecordsby Location. Op Va I uc

Environmental Protection Agency

Page 3 of667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

MINUS the number of calendar days in the quarter

being checked that are PRIOR to the

PriorAppendixEEventRecord.QACertEventDate > 0)

Set

Prior, {ppendixlilivent Record. Mi nOpI )avsI'rior

Quarter =

OperatingSuppDataRecordsby Locati on. ()p Va I

ue MINUS the number of calendar days in the
quarter being checked that are PRIOR to the
Prior. 1 ppendixlilivent Record. Q A C crtl vcn 11 )a t

e

If (OperatingSuppDataRecordsby Location. Op Va I lie is

less than the number of calendar days in the quarter
being checked that are ON OR AFTER the
Prior. {ppendixlilivent Record.QACcrl\:.\cnl\)dlc)

Set

PriorAppendixEEventRecord.yLaxOpDaysPrio
rQuarter =

OperatingSuppDataRecordsby Location. ()p Va I

ue.

else

Set

PriorAppendixEEventRecord.yLaxOpDaysPrio
rQuarter = the number of calendar days in the
quarter being checked that are ON OR AFTER
the

Prior. 1 ppendixlilivent Record. Q A C crtl vcn 11 )a t

e.

Set

Prior, {ppendixliliventRecord.Min()p\)c\\ %l'riorQucUlcr

Prior, {ppendixliliventRecord.Min()p\)c\\ %l'riorQucUlcr
+ OperatingSuppDataRecordsbyLocation. Op Value.

Set Prior, {ppendixliliventRecord.Md\()p\)d\ s
PriorQuarter =

Prior, {ppendixliliventRecord.Mc\x()p\)c\\ %l'riorQucUlcr
+ OperatingSuppDataRecordsbyLocation. Op Value.

If (CurrentAppendixEStatus does NOT begin with "OOC")

if (Rpt Period Op Time Accumulator Array for the Location == -1)

set CurrentAppendixEStatus = "Invalid Op Data"
elseif (Prior, {ppendixliliventRecord.Min()p\)c\\ %\'riorQuiulcr == -1)

set CurrentAppendixEStatus = "Missing Op Data"
else if (Prior, {ppendixliliventRecord. Min< )p\ )-d\ s\'norQui\rlcr + Rpt Period Op Days

Environmental Protection Agency

Page 4 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Accumulator Array for the Location > 30)

Set CurrentAppendixEStatus = "OOC-Event".

else if (PriorAppendixEEventRecord.MaxOpDaysPnorQuarter + Rpt Period Op Days
Accumulator Array for the Location > 30)

Set Current AppendixEStatus = "Undetermined-Event".

else

Set Current AppendixEStatus = "IC".

Set CurrentAppendixEStatus = "IC".

if (AppEFuelCode is not equal to "MIX")

Locate the earliest record in AppendixETestRecordsByLocationForQAStatus for the location where the SystemID
is equal to the AppENOXESystemID and the TestResultCode is not equal to "INVALID" and the EndDate/Hour is
on or after the CurrentOperatingDate/Hour

else

if (AppendixETestRecordsByLocationForQAStatus is found)

Set SubsequentAppendixERecord = the found record in
AppendixETestRecordsByLocationForQAStatus.

Locate the earliest record in AppendixETestRecordsByLocationForQAStatus for the location where the
SystemID is equal to the AppENOXESystemID and the TestResultCode is equal to "INVALID" and the
EndDate/Hour is on or after the CurrentOperatingDate/Hour and the EndDate/Hour is before the
SubsequentAppendixERecord.].nd\y<\lc I lour

if (AppendixETestRecordsByLocationForQAStatus is found)

Set InvalidAppendixERecord = the found record in
AppendixETestRecordsByLocationForQAStatus.

Locate the earliest record in OperatingSuppDataRecordsbyLocation where the FuelCode is equal to
AppEFuelCode and the OpTypeCode is equal to "OPHOURS"

If OperatingSuppDataRecordsbyLocation is found)

Set FuelOpSuppDataRecord = the found record in OperatingSuppDataRecordsbyLocation
Set DateFuelFirstCombusted = end date of quarter of the FuelOpSuppDataRecord .RptPeriodID -
int{{FuelOpSuppDataRecord .OpValue - l)/24) days

if (If OperatingSuppDataRecordsbyLocation is found AND DateFuelFirstCombusted is more than 180
calendar days before the CurrentOperatingDate/Hour)

Set CurrentAppendixEStatus = "OOC-No Prior Test"

else

Locate the record in the FuelCode lookup table where the FuelCode is equal to AppEFuelCode.
Locate the record in FuelRecordsByHourLocation for the hour and location where the FuelCode

Environmental Protection Agency

Page 5 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

is equal to the Fwe/CorfaUnitFuelCode

if (FuelRecordsByHourLocation is not found OR more than one FuelRecordsByHourLocation is
found)

Set CurrentAppendixEStalus = "Invalid Location Fuel"
else if (FuelRecordsByHourLocation.lndicatorCode is equal to "S",

if (Subsequent. [ppendixERecord.QhNccd'd.xix] nation Mag = "Y")

Set CurrentAppendixEStatus = "Subsequent Test Not Yet Evaluated",
else if (SubsequentAppendixERecord.TestResuitCode = null)

Set Current AppendixEStatus = "OOC-Subsequent Test Has Critical Errors".

else

Set Current AppendixEStatus = "IC"

Set PriorAppendixERecord = SubsequentAppendixERecord

else

Set CurrentAppendixEStalus = "OOC-No Prior Test"

else

Set CurrentAppendixEStatus = "OOC-No Prior Test"

Locate the earliest record in AppendixETestRecordsByLocationForQAStatus for the location where the
SystemID is equal to the AppENOXESystemID and the TestResultCode is equal to "INVALID" and the
EndDate/Hour is on or after the CurrentOperatingDate/Hour

if (AppendixETestRecordsByLocationForQAStatus is found)

Set InvalidAppendixERecord = the found record in
AppendixETestRecordsByLocationForQAStatus.

else

Set CurrentAppendixEStatus = "OOC-No Prior Test"
if (CurrentAppendixEStatus begins with "OOC")
if (InvalidAppendixERecord is not null)

Set CurrentAppendixEStatus = CurrentAppendixEStatus &

if (CurrentAppendixEStatus does not begin with "IC")

Return result CurrentAppendixEStatus.

Environmental Protection Agency

Page 6 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Invalid Location
Fuel

Invalid Monitor
System

Invalid Op Data

Missing Fuel Op
Data

Missing Op Data

OOC-Event
OOC-Event*

OOC-Expired

OOC-Expired*

OOC-No Prior
Test

OOC-No Prior
Test*

OOC-Prior Test
Has Critical
Errors

OOC-Prior Test
Has Critical
Errors*

OOC-Subsequent
Test Has Critical
Errors

OOC-Subsequent
Test Has Critical
Errors*

Prior Test Not
Yet Evaluated

Subsequent Test
Not Yet
Evaluated
Undetermined-Ev
ent

Response

The Appendix E test status for MonitoringSystemID [ID] could not be determined,
because you did not report a single, valid unit fuel record for FuelCode [unitfuel] that
was active during the current hour.

The Appendix E test status for MonitoringSystemID [ID] could not be determined,
because the Monitor System record for the NOXE system has a critical error.
The Appendix E test status for MonitoringSystemID [ID] could not be determined,
because the OperatingTime in at least one Hourly Operating Data records was missing
or invalid.

The Appendix E test status for MonitoringSystemID [ID] could not be determined,
because the Op Supp Data record for OPHOURS for FuelCode [fuel] is missing for one
or more previous reporting periods. If you have submitted emissions data for prior
quarters, you should be able to retrieve these records by logging on to the EPA host.
The Appendix E test status for MonitoringSystemID [ID] could not be determined,
because the Op Supp Data record for OPDAYS is missing for

[MISSINGOPDATAINFO] (and possibly other previous reporting periods). If you have
submitted emissions data for prior quarters, you should be able to retrieve these records
by logging on to the EPA host.

You reported a QA Certification Event record for QACertEventCode [code]
QACertEventDate [eventdate] for MonitoringSystemID [ID], but you did not perform a
subsequent Appendix E test within the specified timeframe.

You reported a QA Certification Event record for QACertEventCode [code]
QACertEventDate [eventdate] for MonitoringSystemID [ID], but you did not perform a
subsequent Appendix E test within the specified timeframe. An invalid Appendix E test
was ignored.

The prior Appendix E test TestNumber [testnum] for MonitoringSystemID [ID] has
expired.

The prior Appendix E test TestNumber [testnum] for MonitoringSystemID [ID] has
expired. An invalid prior Appendix E test TestNumber [invtestnum] was ignored.
You did not report a prior Appendix E test for MonitoringSystemID [ID],

You did not report a prior Appendix E test for MonitoringSystemID [ID], An invalid
prior Appendix E test Test Number [invtestnum] was ignored.

The applicable prior Appendix E test TestNumber [testnum] for MonitoringSystemID
[ID] has critical errors.

The prior Appendix E test TestNumber [testnum] for MonitoringSystemID [ID] has
critical errors. An invalid prior Appendix E test TestNumber [invtestnum] was ignored.

The subsequent recertification Appendix E test TestNumber [subtestnum] for
MonitoringSystemID [ID] has critical errors.

The subsequent recertification Appendix E test TestNumber [subtestnum] for
MonitoringSystemID [ID] has critical errors. An invalid Appendix E test TestNumber
[invtestnum] was ignored.

The Appendix E test status for MonitoringSystemID [ID] could not be determined,
because the applicable prior Appendix E test TestNumber [testnum] for the system has
not yet been evaluated.

The Appendix E test status for MonitoringSystemID [ID] could not be determined,
because the subsequent certification test TestNumber [subtestnum] for the system has
not yet been evaluated.

The software could not determine if the current hour was within the 30-operating day
window required to conduct another Appendix E test following QACertEventCode
[code] QACertEventDate [eventdate] for MonitoringSystemID [ID],

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 7 of667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1

2

3

Process/Category:	Emissions Data Evaluation Report — Hourly Configuration Evaluation

Conditions:	App E Checks Needed Equals true

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Conditions:	App E Constant Fuel Mix Equals true

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Conditions:	App E Constant Fuel Mix Equals false

Environmental Protection Agency

Page 8 of667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	ADESTAT-2

Check Name:	Locate Most Recent Prior Accuracy Test

Related Former Checks:

Applicability:

Description:

Specifications:

Set CurrentAccuracyStalus = null.

Set Prior Accuracy Record = null.

Set InvalidAccuracyRecord = null.

Set InappropriateTransmitterTransducerTest to false.

Locate the most recent record in Accuracy TestRecordsByLocationForQAStatus for the location where the ComponentID is equal to the
FuelFlowComponentRecordToCheck.ComponenUT) and the TestResult is not equal to "INVALID" and the EndDate/Hour is prior to the
CurrentOperatingDate/Hour

if (Accuracy TestRecordsByLocationForQAStalus is found)

Set PriorAccuracyRecord = the found record in AccuracyTestRecordsByLocalionForQAStatus .

if (PriorAccuracy Record.'\ c^l\ \ pcCo
-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Usage:

1

Set InvalidAccuracyRecord = the found record in AccuracyTestRecordsByLocationForQAStalus.

Response	Severity

Process/Category:	Emissions Data Evaluation Report	Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 10 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	ADESTAT-3

Check Name:	Locate Most Recent Prior Accuracy Event

Related Former Checks:

Applicability:

Description:

Specifications:

Set PriorAccuracyEventRecord= null.

If (CurrentAccuracy Status is null)

Locate the most recent record in QACertificalionEventRecords WHERE

a)	the ComponentID is equal to the FuelFlowComponentRecordToCheck.ComponentID AND

b)	FFACCRequired is equal to "Y" AND

c)	the QACertEventDate/Hour is prior to the CurrentOperatingDate/Hour AND

d)	the QACertEventDate/Hour is after the later of the PriorAccuracyRecord.EndDatefHour and the
PriorAccuracyRecord.ReinstaUationDate/Hour.

if (QACertificationEventRecords is found)

Set PriorAccuracyEventRecord = the found record in QACertificationEventRecords.

Set Current Accuracy Status = "OOC-Event".

else

Set PriorTestExpirationDate = 5 years (20 calendar quarters) after the end of the quarter of the
Prior. 1 ccuracy Record. H n d Da te Hour.

if (CurrentOperatingDate/Hour is AFTER the PriorTestExpirationDate)

Set CurrentAccuracy Status = "OOC-Accuracy Test Expired".

else

Set PriorTestExpirationDate = 4 quarters after the end of the quarter of the later of the
Prior. 1 ccuracyRecord. H nd Da te Hour and the Pr/oMccMracjifecorrf.ReinstallationDate/Hour.
Set Prior Accuracy Record. TestExpirationDate = PriorTestExpirationDate.

If (CurrentOperatingDate/Hour is ON OR BEFORE the PriorTestExpirationDate)

Set Current Accuracy Status = "IC".

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 11 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	ADESTAT-4

Check Name:	Determine Eligibility for Fuel Flow to Load Testing (Accuracy)

Related Former Checks:

Applicability:

Description:

Specifications:

Set FF2LAccuracyEligible = null.

Set FF2LAccuracyCheckDate = null.

if (CurrentAccuracy Status is null)

Locate any record in FF2LTestRecordsByLocalionForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the TestResult is equal to "PASSED", "EXC168H", "INPROG", or
"FAILED" and the quarter is prior to the quarter of the CurrentOperatingDate and the quarter is subsequent to the quarter of the
later of the PriorAccuracy Record. I jidDate and the /V/w.Iccm/y/cj'/^'c^/y/. Reinstallation Date.

if (FF2LTestRecordsByLocationForQAStalus is found)

Set FF2LAccuracyEligible = true.

Set FF2LAccuracyCheckDate = the later of the PriorAccuracy Record. I Indl )atc and the
PriorAccuracyRecord.ReinstaUationDate.

for each record in FuelFlowComponentRecords

if {FuelFlowComponentRecords.ComponentID is not equal to
FuelFlowComponentRecordToCheck. ComponentID)

Locate the latest record in AccuracyTestRecordsByLocationForQAStalus for the location where the
ComponentID is equal to the FuelFlowComponentRecords.ComponentID and the TestResult is equal to
"PASSED" and the quarter of the later of the EndDate and the ReinstallationDate is in the same or adjacent
quarter of the later of the PriorAccuracyRecord.EndDate and the
PriorAccuracyRecord.ReinstaUationDate.

if (Accuracy TestRecordsByLocationForQAStatus is not found)

Set FF2LAccuracyEligible = false, and exit this check.

else

Set FF2LAccuracyCheckDate = the later of FF2LAccuracyCheckDate and the
AccuracyTestRecordsByLocationForQAStatus.EndDate and the
AccuracyTest Records By Location l'orOAStatus.Rcinsld\\dUon\)dlc.

if (Accuracy TestRecordsByLocationForOAStatus.l call ypcCodc is equal to "FFACCTT")

Locate the latest record in PEITestRecordsByLocationForQAStatus for the location
where the ComponentID is equal to the FuelFlowComponentRecords ComponentID and
the TestResult is equal to "PASSED" and the quarter is in the same or adjacent quarter of
the later of the PriorAccuracy Record. I Indl )atc and the
Prior A ccuracyRecord.Kei nstallati onDate.

if (PEITestRecordsByLocationForQAStatus is not found)

Set FF2LAccuracyEligible = false, and exit this check.

else

Environmental Protection Agency

Page 12 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set FF2LAccuracyCheckDate = the later of FF2LAccuracyCheckDate and the
PEITestRecordsByLocalionForQAStatus. EndDate.

else if (PriorAccuracy Test Record. TcstTvpcCodc is equal to "FFACCTT")

Locate the latest record in PEITestRecordsByLocalionForQAStatus for the location where the
ComponentID is equal to the FuelFlowComponentRecords.ComponentID and the TestResult is equal to
"PASSED" and the quarter is in the same or adjacent quarter of the Prior AccuracyRecord.EndDate.

if (PEITestRecordsByLocationForQAStalus is not found)

Set FF2LAccuracyEligible = false, and exit this check.

else

Set FF2LAccuracyCheckDate = the later of FF2LAccuracyCheckDate and the
PEITestRecordsByLocationForQAStatus. EndDate.

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report

Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 13 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

ADESTAT-5

Check Name:

Evaluate Fuel Flow to Load Tests (Accuracy)

Related Former Checks:

Applicability:

Description:

Specifications:

Set FF2LAccuracyBeginYearQuarter = null.

Set FF2LAccuracyEndYearQuarter = null.

Set InvalidFF2LTestNumber = null.

Set MissingFF2LYearQuarter = null.

if (FF2LAccuracyEligible == true)

Locate any record in FF2LTestRecordsByLocalionForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the TestResult is equal to "FAILED" and the quarter is prior to the quarter of
the CurrentOperatingDate and the quarter is subsequent to the quarter of the later of the PriorAccuracy Record. I IndDate and the
PriorAccuracyRecord.ReinstaUationDate.

if (FF2LTestRecordsByLocationForQAStalus is found)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStalus. TestNumber
Set Current Accuracy Status = "OOC-Fuel Flow to Load Test Failed",
exit check.

Locate any record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the TestResult is NULL and the quarter is prior to the quarter of the
CurrentOperatingDate and the quarter is subsequent to the quarter of the later of the PriorAccuracy Record. I IndDate and the
PriorAccuracyRecord.ReinstaUationDate.

if (FF2LTestRecordsByLocationForQAStatus is found)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus. TestNumber
Set Current Accuracy Status = "OOC-Fuel Flow to Load Test Has Critical Errors",
exit check.

Locate any record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the QANeedsEvaluation flag is equal to "Y" and the quarter is prior to the
quarter of the CurrentOperatingDate and the quarter is subsequent to the quarter of the later of the PriorAccuracyRecord.EndDate
and the PriorAccuracyRecord.ReinstaUationDate.

if (FF2LTestRecordsByLocationForQAStatus is found)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus. TestNumber
Set Current Accuracy Status = "Fuel Flow to Load Test Has Not Yet Been Evaluated",
exit check.

Locate the earliest record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the TestResult is equal to "PASSED", "FEW168H", or "EXC168H" and the
quarter is prior to the quarter of the CurrentOperatingDate and the quarter is subsequent to the quarter of the later of the
PriorAccuracy Record. Hndl )atc and the PriorAccuracyRecord.ReinstaUationDate.

if (FF2LTestRecordsByLocationForQAStatus is found)

Set FF2LAccuracyBeginYearQuarter = FF2Test Records By Location ForO. 1 Status Yea r &
FF2LTestRecordsByLocationForQAStatus. Quarter.

Environmental Protection Agency

Page 14 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Set FF2LAccuracyBeginYearQuarter = null

Locate the latest record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the TestResult is equal to "INPROG" and the quarter is prior to the quarter of
the CurrentOperatingDate and the quarter is subsequent to the quarter of the later of the Prior Accuracy Record. I IndDate and the
PriorAccuracyRecord.ReinstaUationDate.

if (FF2LTestRecordsByLocationForQAStalus is found)

if (FF2LAccuracyBeginYearQuarter is not null AND FF2LTest Records By LocationForO. 1 Status Year Quartcr >
FF2LAccuracyBegin YearQuarter)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus. TestNumber
Set CurrentAccuracyStalus = "OOC-Invalid Fuel Flow to Load Test",
exit check.

else if (FF2LTestRecordsByLocationForQAStatus. Year/Quarter is more than 4 quarters after the quarter of the
FF2LA ccuracyCh eckDale)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus. TestNumber
Set CurrentAccuracyStalus = "Undetermined-Baseline Period Expired",
exit check.

Set FF2LAccuracyBeginYearQuarter = the quarter after the quarter of the FF2LAccuracyCheckDate.

Locate the latest record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the TestResult is equal to "PASSED", "EXC168H", "INPROG", or
"FEW168H", and the quarter is prior to the quarter of the CurrentOperatingDate and the quarter is subsequent to the quarter of the
later of the Prior Accuracy Record. I jidDatc and the PriorAccuracyRecord.ReinstaUationDate.

Set FF2LAccuracyEndYearQuarter = FF2LTestRecordsByLocationForQAStatusYeax &

FF2L Test Records By Location ForO. 1 Status. Q ua iter.

for each quarter between the FF2LAccuracyBeginYearQuarter and the FF2LAccuracyEndYearQuarter (inclusive)

Locate any record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck. SystemID and the quarter is equal to the quarter to check.

if (FF2LTestRecordsByLocationForQAStatus is found)

if (FF2LTestRecordsByLocationForQAStatus. TestResult = "FEW168H")

Locate a record in OperatingSuppDataRecordsby Location where the FuelCode is equal to
CurrentFuelFlowRecordVuelCode and the OpTypeCode is equal to "OPHOURS" or "OSHOURS" and
the quarter is equal to the quarter to check and the OpValue >= 168.

if {OperatingSuppDataRecordsbyLocation is found)

Locate any record in FF2LBaselineRecordsByLocationForQAStatus for the location where the
SystemID is equal to the FuelFlowComponentRecordToCheck.SystemID, and the EndDate is
within the quarter being checked.

If not found,

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus.TestNumber
Set CurrentAccuracyStatus = "OOC-Invalid Fuel Flow to Load Test".

Exit check.

Environmental Protection Agency

Page 15 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Locate a record in OperatingSuppDataRecordsbyLocation where the FuelCode is equal to
CurrentFuelFlmvRecordVueiCode and the OpTypeCode is equal to "OPHOURS" or "OSHOURS" and the
quarter is equal to the quarter to check and the Op Value >= 168.

if (OperatingSuppDataRecordsbyLocation is found)

Set MissingFF2LYearQuarter equal to the year/quarter to check.

Set Current Accuracy Status = "Undetermined-Missing Fuel Flow to Load Test".

Exit check.

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report

Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 16 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

ADESTAT-6

Check Name:

Determine Accuracy Test Expiration Date

Related Former Checks:

Applicability:

Description:

Specifications:

Set AccuracyMissingOpDatalnfo = null,
if (CurrentAccuracy Status is null)

Set PriorTestExpirationDate = Prior Accuracy Record a pi rati on I )atc.

for each quarter subsequent to the quarter of the later of the PriorAccuracyRecord.EndDate/Hour and the
Pr/oMccMracjifecorrf.ReinstallationDate/Hour and prior to the quarter of the CurrentOperalingDale/Hour

Set OSO Reporter to false.

Locate a LocalionReportingFrequency record for the test location where ReportingFrequencyCode = "OS", the
BeginQuarter is on or before the quarter being checked, and the EndQuarter is null or is on or after the quarter being
checked.

If found,

Set OSO Reporter to true.

if (OSO Reporter == false or the quarter to check is the 3rd quarter)

if (FF2LAccuracyEligible == true and the quarter to check is between the FF2LAccuracyBeginYearQuarter and
the FF2LAccuracyEndYearQuarter (inclusive))

Add 1 quarter to the PriorTestExpirationDate.

else

if (EarliestLocationReportDale > the last day of the quarter being checked)

Add 1 quarter to the PriorTestExpirationDate.

else

Locate the record in OperatingSuppDataRecordsbyLocation where the OpTypeCode is equal to
"OPHOURS" and the reporting period is equal to the quarter to check and the FuelCode is equal to
CurrentFuelFlowRecord F uelCode.

if (OperalingSuppDataRecordsbyLocation is not found)

Locate the record in OperatingSuppDalaRecordsbyLocation where the OpTypeCode is
equal to "OPHOURS" and the reporting period is equal to the quarter to check and the
FuelCode is null.

if (OperalingSuppDataRecordsbyLocation is not found)

Set AccuracyMissingOpDatalnfo = "[YEAR] Q[QTR]" (where [YEAR] is the
year of the quarter being checked and [QTR] is the number of the quarter being
checked).

else

Environmental Protection Agency

Page 17 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Add 1 quarter to the PriorTestExpirationDate.
else if (OperatingSuppDataRecordsby Location.OpN&hie <= 168)

Add 1 quarter to the PriorTestExpirationDate.

else

Locate a record in TestExtensionExemptionRecords for the location where the
ComponentID is equal to the FuelFlowComponentRecordToCheck.ComponentID, the
reporting period is equal to the quarter to check , AND the ExtensionExemptionCode is
equal to "NONQADB".

if (TestExtensionExemptionRecords is found)

Add 1 quarter to the PriorTestExpirationDate.

else if (OSO Reporter == true and the quarter to check is the 2nd quarter)

if (FF2LAccuracyEligible == true and the quarter to check is between the FF2LAccuracyBeginYearQuarter and
the FF2LAccuracyEndYearQuarter (inclusive))

Add 1 quarter to the PriorTestExpirationDate.

else

Locate a record in TestExtensionExemptionRecords for the location where the reporting period is equal to
the quarter to check , AND the ExtensionExemptionCode is equal to "NONQAOS" and the FuelCode is
equal to the CurrentVuelVlowRecord. I uclCode.

if (TestExtensionExemptionRecords is found)

Add 1 quarter to the PriorTestExpirationDate.

else

Locate a record in TestExtensionExemptionRecords for the location where the ComponentID is
equal to the FuelFlmvComponentRecordToCheck.ComponentID, the reporting period is equal to
the quarter to check , AND the ExtensionExemptionCode is equal to "NONQADB".

if (TestExtensionExemptionRecords is found)

Add 1 quarter to the PriorTestExpirationDate.

else if {OSO Reporter == true and the quarter to check is the 1st or 4th quarter)

if (FF2LAccuracyEligible == true and the 2nd quarter following the quarter being checked is between the
FF2LAccuracyBeginYearQuarter and the FF2LAccuracyEndYearQuarter (inclusive))

Add 1 quarter to the PriorTestExpirationDate.

else

Locate a record in TestExtensionExemptionRecords for the location where the reporting period is equal to
the quarter to check , AND the ExtensionExemptionCode is equal to "NONQAOS" and the FuelCode is
equal to the CurrentVuelVlowRecord. I ucl Code.

if (TestExtensionExemptionRecords is found)

Environmental Protection Agency

Page 18 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Add 1 quarter to the PriorTestExpirationDate.

else

Locate a record in TestExtensionExemptionRecords for the location where the ComponentID is
equal to the FuelFlmvComponentRecordToCheck.ComponentID, the reporting period is equal to
the quarter to check , AND the ExtensionExemptionCode is equal to "NONQADB".

if (TestExtensionExemptionRecords is found)

Add 1 quarter to the PriorTestExpirationDate.

if (CurrentOperatingDate/Hour > PriorTestExpirationDate)

if (AccuracyMissingOpDatalnfo is not null)

Set CurrentAccuracyStatus = "Missing Op Data"

Return result CurrentAccuracyStatus .

else if (FF2LAccuracyEligible == false)

Set CurrentAccuracyStatus = "OOC-Accuracy Test Expired-Fuel Flow To Load Test Ignored".

Return result CurrentAccuracyStatus .

else

Set CurrentAccuracyStatus = "OOC-Accuracy Test Expired"

else

Set CurrentAccuracyStatus = "IC-Extension"

If (CurrentAccuracyStatus does not begin with "IC" and is not null)

if (CurrentAccuracyStatus starts with "OOC" or "Undetermined" AND InvalidAccuracyRecordis not null)

Set CurrentAccuracyStatus = CurrentAccuracyStatus &

Return result CurrentAccuracyStatus.
else if (InapprorpriateTransmitterTransducerTest == true)

Return result "Inappropriate Transmitter Transducer Test" 11 do NOT set current accuracy status

Environmental Protection Agency

Page 19 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Accuracy Test
Not Yet
Evaluated
Fuel Flow to
Load Test Has
Not Yet Been
Evaluated
Inappropriate
Transmitter
Transducer Test

Missing Op Data

OOC-Accuracy
Test Aborted
OOC-Accuracy
Test Aborted*
OOC-Accuracy
Test Expired
OOC-Accuracy
Test Expired*
OOC-Accuracy
Test Expired-Fuel
Flow To Load
Test Ignored
OOC-Accuracy
Test Expired-Fuel
Flow To Load
Test Ignored*
OOC-Accuracy
Test Failed
OOC-Accuracy
Test Failed*
OOC-Accuracy
Test Has Critical
Errors

OOC-Accuracy
Test Has Critical
Errors*
OOC-Event

OOC-Event*

OOC-Fuel Flow
to Load Test
Failed

OOC-Fuel Flow
to Load Test
Failed*

OOC-Fuel Flow
to Load Test Has
Critical Errors

Response	Severity

The [testtype] status for [key] could not be determined, because the applicable prior	Critical Error Level 1

[testtype] with TestNumber [testnum] has not yet been evaluated.

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load	Critical Error Level 1

test for MonitoringSystemID [ID] with TestNumber [ffZltestnum] has not yet been

evaluated.

The prior [testtype] for [key] with TestNumber [testnum] is a transmitter/transducer	Critical Error Level 2

test], but this type of test is inappropriate for the SampleAcquisitionMethodCode for the
fuel flowmeter. A transmitter/transducer test can only be performed on a NOZ, VEN,
and ORF fuel flowmeter.

The [testtype] status for [key] could not be determined, because the Op Supp Data	Critical Error Level 1

record for OPHOURS, OSHOURS, or OPDAYS is missing for

[MISSINGOPDATAINFO] (and possibly other previous reporting periods). If you have
submitted emissions data for prior quarters, you should be able to retrieve these records
by logging on to the EPA host.

The applicable prior [testtype] for [key] with TestNumber [testnum] was aborted.	Critical Error Level 1

The prior [testtype] for [key] with TestNumber [testnum] was aborted. An invalid prior	Critical Error Level 1

[testtype] with TestNumber [invtestnum] was ignored.

The prior [testtype] for [key] with TestNumber [testnum] has expired.	Critical Error Level 1

The prior [testtype] for [key] with TestNumber [testnum] has expired. An invalid prior	Critical Error Level 1

[testtype] with TestNumber [invtestnum] was ignored.

The prior [testtype] for [key] with TestNumber [testnum] has expired. A prior	Critical Error Level 1

fuel-flow-to-load test for MonitoringSystemID [ID] was ignored.

The prior [testtype] for [key] with TestNumber [testnum] has expired. A prior
fuel-flow-to-load test for MonitoringSystemID [ID] was ignored. An invalid prior
[testtype] with TestNumber [invtestnum] was also ignored.

Critical Error Level 1

The applicable prior [testtype] for [key] with TestNumber [testnum] failed.

The prior [testtype] for [key] with TestNumber [testnum] failed. An invalid prior
[testtype] with TestNumber [invtestnum] was ignored.

The applicable prior [testtype] for [key] with TestNumber [testnum] has critical errors.

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

The prior [testtype] for [key] with TestNumber [testnum] has critical errors. An invalid	Critical Error Level 1

prior [testtype] with TestNumber [invtestnum] was ignored.

You reported a QA Certification Event record for QACertEventCode [code]	Critical Error Level 1

QACertEventDate [eventdate] for [key], but you did not perform a subsequent
[testtype].

You reported a QA Certification Event record for QACertEventCode [code]	Critical Error Level 1

QACertEventDate [eventdate] for [key], but you did not perform a subsequent
[testtype]. An invalid [testtype] was ignored.

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load	Critical Error Level 1

test for MonitoringSystemID [ID] with TestNumber [ffZltestnum] has failed.

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load	Critical Error Level 1

test for MonitoringSystemID [ID] with TestNumber [ffZltestnum] has failed. An invalid
[testtype] with TestNumber [invtestnum] was ignored.

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load	Critical Error Level 1

test for MonitoringSystemID [ID] with TestNumber [ffZltestnum] has critical errors.

Environmental Protection Agency

Page 20 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

OOC-Fuel Flow
to Load Test Has
Critical Errors*
OOC-Invalid
Fuel Flow to
Load Test

OOC-Invalid
Fuel Flow to
Load Test*

OOC-No Prior
Accuracy Test
OOC-No Prior
Accuracy Test*
Undetermined-Ba
seline Period
Expired

Undetermined-Mi
ssing Fuel Flow
to Load Test

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load
test for MonitoringSystemID [ID] with TestNumber [ffZltestnum] has critical errors. An
invalid [testtype] with TestNumber [invtestnum] was ignored.

The [testtype] status for [key] could not be determined, because one or more prior
fuel-flow-to-load tests, including the test for MonitoringSystemID [ID] with
TestNumber [ff21testnum], are invalid. These tests may be invaild because (1) the
TestResultCode indicates that baseline data collection is ongoing, yet you reported a
prior test indicating that baseline data collection was completed; or (2) the
TestResultCode indicates that there were fewer than 168 fuel QA operating hours in the
quarter, yet your emissions data for that quarter indicates otherwise.

The [testtype] status for [key] could not be determined, because one or more prior
fuel-flow-to-load tests, including the test for MonitoringSystemID [ID] with
TestNumber [ff21testnum], are invalid. These tests may be invaild because (1) the
TestResultCode indicates that baseline data collection is ongoing, yet you reported a
prior test indicating that baseline data collection was completed; or (2) the
TestResultCode indicates that there were fewer than 168 fuel QA operating hours in the
quarter, yet your emissions data for that quarter indicates otherwise. An invalid
[testtype] with TestNumber [invtestnum] was ignored.

You did not report a prior [testtype] for [key].

You did not report a valid prior [testtype] for [key]. An invalid [testtype] with
TestNumber [invtestnum] was ignored.

The [testtype] status for [key] could not be determined, because, according to the
fuel-flow-to-load test for MonitoringSystemID [ID] with TestNumber [ff21testnum],
baseline data was still being collected after the deadline.

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load
test for MonitoringSystemID [ID] was missing for [missingff21].

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 2

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 21 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

ADESTAT-7

Check Name:

Determine if Component Requires a PEI Test

Related Former Checks:

Applicability:

Description:

Specifications:

Set PEIRequired = false.

if (PriorAccuracyRecord is not null and PriorAccuracyRecord.TestTypeCode is equal to "FFACCTT")

Set PEIRequired = true.

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report

Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 22 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

ADESTAT-8

Check Name:

Locate Most Recent Prior PEI Test

Related Former Checks:

Applicability:

Description:

Specifications:

Set CurrentPEIStatus = null.

Set PriorPEIRecorcl = null.

if (PE! Required == true)

Locate the most recent record in PEITestRecordsByLocationForQAStatus for the location where the ComponentID is equal to the
FuelFlowComponentRecordToCheck.ComponentID and the EndDate/Hour is prior to the CurrentOperatingDate/Hour

if (PEITestRecordsByLocationForQAStalus is found)

Set PriorPEIRecord = the found record in PEITestRecordsByLocationForQAStatus .
if (Pr/orP£7ifecorrf.QANeedsEvaluationFlag = " Y")

Set CurrentPEIStatus = "PEI Test Not Yet Evaluated",
else if (PriorPEIRecord.TestKesuitCode is null)

Set CurrentPEIStatus = "OOC-PEI Test Has Critical Errors",
else if (PriorPEIRecord.TestResultCode = "FAILED")

Set CurrentPEIStatus = "OOC-PEI Test Failed",
else if (PriorPEIRecord.TestResultCode = "ABORTED")

Set CurrentPEIStatus = "OOC-PEI Test Aborted".

else

Set CurrentPEIStatus = "OOC-No Prior PEI Test".

if (CurrentPEIStatus is not null)

Return result CurrentPEIStatus.

Results:

Result

OOC-No Prior
PEI Test
OOC-PEI Test
Aborted
OOC-PEI Test
Failed

OOC-PEI Test
Has Critical
Errors

PEI Test Not Yet
Evaluated

Response

You did not report a prior [testtype] for [key].

The [testtype] status for [key] could not be determined, because the applicable prior
[testtype] with TestNumber [testnum] has not yet been evaluated.

The applicable prior [testtype] for [key] with TestNumber [testnum] has critical errors.

The applicable prior [testtype] for [key] with TestNumber [testnum] failed.

The applicable prior [testtype] for [key] with TestNumber [testnum] was aborted.

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Severity

Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 23 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 24 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks
Applicability:

Description:

Specifications:

Set PriorPEIEventRecord = null.

If (PEIRequirecl == true AND CurrentPEIStatus is null)

Locate the most recent record in QACertificalionEventRecords WHERE

a)	the ComponentID is equal to the FuelFlowComponentRecordToCheck.ComponentID AND

b)	PEIRequired is equal to "Y" AND

c)	the QACertEventDate/Hour is prior to the CurrentOperalingDale/Hour AND

d)	the QACertEventDate/Hour is after the PriorPEIRecord.EndDatefHour.

if (QACertificationEventRecords is found)

Set PriorPEIEventRecord = the found record in QACertificationEventRecords.

Set CurrentPEIStatus = "OOC-Event".

else

Set PriorTestExpirationDate = 5 years (20 calendar quarters) after the end of the quarter of the PriorPEIRecord.EndDate.
if (CurrentOperatingDate is AFTER the PriorTestExpirationDate)

Set CurrentPEIStatus = "OOC-PEI Test Expired".

else

Set PriorTestExpirationDate = 12 quarters after the end of the quarter of the PriorPEIRecord.EndDate.
Set PriorPEIRecord.TestExpimtionDate = PriorTestExpirationDate.

If (CurrentOperatingDate is ON OR BEFORE the PriorTestExpirationDate)

Set CurrentPEIStatus: = "IC".

If (CurrentPEIStatus starts with "OOC")

Return result CurrentPEIStatus.

Results:

Result
OOC-Event

OOC-PEI Test
Expired

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Fuel Flowmeter QA Status Evaluation

ADESTAT-9

Locate Most Recent Prior PEI Event

Response

You reported a QA Certification Event record for QACertEventCode [code]
QACertEventDate [eventdate] for [key], but you did not perform a subsequent
[testtype].

The prior [testtype] for [key] with TestNumber [testnum] has expired.

Severity

Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 25 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

ADESTAT-10

Check Name:

Determine Eligibility for Fuel Flow to Load Testing (PEI)

Related Former Checks:

Applicability:

Description:

Specifications:

Set FF2LPEIEligible = null
Set FF2LPEICheckDate = null.

if (PEIRequired == true AND CurrentPEIStatus is null)

Locate any record in FF2LTestRecordsByLocalionForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the CalculatedTestResult is equal to "PASSED", "FEW168H", "EXC168H",
"INPROG", or "FAILED" and the Year/Quarter is prior to the quarter of the CurrentOperatingDale and the Year/Quarter is
subsequent to the quarter of the PriorPEIRecord.EndDate.

if (FF2LTestRecordsByLocationForQAStalus is found)

Set FF2LPEIEligible = true.

Set FF2LPEICheckDate = PriorPFIRecord. I jidDatc.

for each record in FuelFlowComponentRecords

Locate the latest record in Accuracy TestRecordsByLocalionForQAStatus for the location where the ComponentID
is equal to the FuelFlowComponentRecords.ComponentID and the TestResult is equal to "PASSED" and the
Year/Quarter of the later of the EndDate and Reinstallation Date is in the same or adjacent quarter of the
PriorPEIRecord. EndDate.

if (Accuracy TestRecordsByLocationForQAStalus is not found)

Set FF2LPEIEligible = false, and exit check.

Set FF2LPEICheckDate = the later of FF2LPEICheckDate and the
AccuracyTestRecordsByLocationForQAStatus.EndD&te and the
Accuracy TestRecordsByLocationForQAStatus.ReinstaUationDate.

if (FuelFlowComponentRecords.ComponentID is not equal to
FuelFlowComponentRecordToCheck.ComponentID AND

AccuracyTestRecordsByLocationForQAStatus.IestlypeCode is equal to "FFACCTT")

Locate the latest record in PEITestRecordsByLocationForQAStalus for the location where the
ComponentID is equal to the FuelFlowComponentRecords.ComponentID and the TestResult is
equal to "PASSED" and the Year/Quarter is in the same or adjacent quarter of the
Prior PFfRecord. H n d I )a tc.

if (PEITestRecordsByLocalionForQAStatus is not found)

Set FF2LPEIEligible = false, and exit check.

else

Set FF2LPEICheckDate = the later of FF2LPEICheckDate and the
PEITestRecordsByLocationForQAStalus. EndDate.

else

Results:

Result

Response

Severity

Environmental Protection Agency

Page 26 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 27 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

ADESTAT-11

Check Name:

Evaluate Fuel Flow to Load Tests (PEI)

Related Former Checks:

Applicability:

Description:

Specifications:

Set FF2LPEIBeginYearQuarter = null.

Set FF2LPEIEndYearQuarter = null.

if {FF2LPEIEligible == true)

Locate any record in FF2LTestRecordsByLocalionForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemiT) and the TestResultCode is equal to "FAILED" and the Year/Quarter is prior to the
quarter of the CurrentOperatingDate and the Year/Quarter is subsequent to the quarter of the PriorPEIRecord.EndDate.

if (FF2LTestRecordsByLocationForQAStalus is found)

Locate a record in QACertificationEventRecords WHERE

a)	the ComponentID is equal to the FuelFlowComponentRecordToCheck.ComponentID AND

b)	the QACertEventCode is equal to "410"

c)	the RequiredTestCode is equal to "53"AND

d)	the QACertEventDate/Hour is after the EndDate/Hour and of the located failed
FF2LTestRecordsByLocationForQAStalus record.

e)	the QACertEventDate/Hour is prior to the CurrentOperalingDale/Hour

if (QACertificationEventRecords is not found)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus. TestNumber
Set CurrentPEIStalus = "OOC-Fuel Flow to Load Test Failed".

Return result CurrentPEIStatus.

Locate any record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck. SystemID and the TestResultCode is NULL and the Year/Quarter is prior to the quarter of
the CurrentOperatingDate and the Year/Quarter is subsequent to the quarter of the PriorPEIRecord.EndDate.

if (FF2LTestRecordsByLocationForQAStatus is found)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus. TestNumber
Set CurrentPEIStatus: = "OOC-Fuel Flow to Load Test Has Critical Errors".

Return result CurrentPEIStatus.

Locate any record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the QANeedsEvaluation flag is equal to "Y" and the Year/Quarter is prior to
the quarter of the CurrentOperatingDate and the Year/Quarter is subsequent to the quarter of the PriorPEIRecord.EndDate.

if (FF2LTestRecordsByLocationForQAStatus is found)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus. TestNumber
Set CurrentPEIStatus: = "Fuel Flow to Load Test Has Not Yet Been Evaluated".

Return result CurrentPEIStatus.

Locate the earliest record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the TestResultCode is equal to "PASSED", "FEW168H", or "EXC168H" and
the Year/Quarter is prior to the quarter of the CurrentOperatingDate and the Year/Quarter is subsequent to the quarter of the
I'ri or PHI Record L n d Da te.

Environmental Protection Agency

Page 28 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (FF2LTestRecordsByLocationForQAStalus is found)

Set FF2LPEIBeginYearQuarter = FF2LTestRecordsByLocationForQAStatus.Year &
FF2LTestRecordsByLocationForQAStalus. Quarter.

else

Set FF2LPEIBeginYearQuarter = null

Locate the latest record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the TestResultCode is equal to "INPROG" and the Year/Quarter is prior to the
quarter of the CurrentOperatingDate and the Year/Quarter is subsequent to the quarter of the PriorPEIRecord.EndDate.

if (FF2LTestRecordsByLocationForQAStalus is found)

if (Set FF2LPEIBeginYearQuarter is not null AND FF2LTestRecordsByLocationForQAStatus.Ye&r/Qu&rter >
FF2LPEIBegin YearQuarter)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus. TestNumber
Set CurrentPEIStalus = "OOC-Invalid Fuel Flow to Load Test".

Return result CurrentPEIStatus.

else if (FF2LTestRecordsByLocalionForQAStatus. Year/Quarter is more than 4 quarters after the quarter of the
FF2LPEICheckDale)

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus. TestNumber
Set CurrentPEIStatus = "Undetermined-Baseline Period Expired".

Return result CurrentPEIStatus.

Set FF2LPEIBeginYearQuarter to the quarter after the quarter of the FF2LPEICheckDate.

Locate the latest record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the TestResultCode is equal to "PASSED", "FEW168H", or "EXC168H" and
the Year/Quarter is prior to the quarter of the CurrentOperatingDate and the Year/Quarter is subsequent to the quarter of the
Prior 1'IJf Record.\.nd\)dlc.

Set FF2LPEIEndYearQuarter = FF2LTestRecordsByLocationForQAStatus. Year &

FF2L Test Records By Location ForO. 1 Status. Q ua iter.

for each quarter between the FF2LPEIBeginYearQuarter and the FF2LPEIEndYearQuarter (inclusive)

Locate any record in FF2LTestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
FuelFlowComponentRecordToCheck.SystemID and the Year/Quarter is equal to the year/quarter to check.

if (FF2LTestRecordsByLocationForQAStatus is found)

if (FF2LTestRecordsByLocalionForQAStatus.C&\cu\&tedTestResu\t = "FEW168H")

Locate a record in OperatingSuppDataRecordsbyLocation where the FuelCode is equal to
CurrentFuelFlowRecordVuelCode and the OpTypeCode is equal to "OPHOURS" or "OSHOURS" and
the Year/Quarter is equal to the year/quarter to check and the OpValue >= 168.

if (OperatingSuppDataRecordsbyLocation is found)

Locate any record in FF2LBaselineRecordsByLocationForQAStatus for the location where the
SystemID is equal to the FuelFlowComponentRecordToCheck.SystemID, and the EndDate is
within the quarter being checked.

Environmental Protection Agency

Page 29 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

If not found,

Set InvalidFF2LTestNumber = FF2LTestRecordsByLocationForQAStatus.TestNumber
Set CurrentPEIStatus = "OOC-Invalid Fuel Flow to Load Test".

Return result CurrentPEIStatus.

Locate a record in OperatingSuppDataRecordsbyLocation where the FuelCode is equal to
CurrentFuelFlmvRecordVueiCode and the OpTypeCode is equal to "OPHOURS" or "OSHOURS" and the
Year/Quarter is equal to the year/quarter to check and the OpValue >= 168.

if (OperatingSuppDataRecordsbyLocation is found)

Set MissingFF2LYearQuarter equal to the year/quarter to check.

Set CurrentPEIStatus = "Undetermined-Missing Fuel Flow to Load Test".

Return result CurrentPEIStatus.

Results:

Result

Fuel Flow to
Load Test Has
Not Yet Been
Evaluated
OOC-Fuel Flow
to Load Test
Failed

OOC-Fuel Flow
to Load Test Has
Critical Errors
OOC-Invalid
Fuel Flow to
Load Test

Undetermined-Ba
seline Period
Expired

Undetermined-Mi
ssing Fuel Flow
to Load Test

Response

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load
test for MonitoringSystemID [ID] with TestNumber [ffZltestnum] has not yet been
evaluated.

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load
test for MonitoringSystemID [ID] with TestNumber [ffZltestnum] has failed.

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load
test for MonitoringSystemID [ID] with TestNumber [ffZltestnum] has critical errors.

The [testtype] status for [key] could not be determined, because one or more prior
fuel-flow-to-load tests, including the test for MonitoringSystemID [ID] with
TestNumber [ff21testnum], are invalid. These tests may be invaild because (1) the
TestResultCode indicates that baseline data collection is ongoing, yet you reported a
prior test indicating that baseline data collection was completed; or (2) the
TestResultCode indicates that there were fewer than 168 fuel QA operating hours in the
quarter, yet your emissions data for that quarter indicates otherwise.

The [testtype] status for [key] could not be determined, because, according to the
fuel-flow-to-load test for MonitoringSystemID [ID] with TestNumber [ff21testnum],
baseline data was still being collected after the deadline.

The [testtype] status for [key] could not be determined, because a prior fuel-flow-to-load
test for MonitoringSystemID [ID] was missing for [missingff21].

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 2

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 30 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

ADESTAT-12

Check Name:

Determine PEI Test Expiration Date

Related Former Checks:

Applicability:

Description:

Specifications:

Set PEIMissingOpDalalnfo = null.

if (PEIRequirecl == true AND CurrentPEIStatus is null)

Set PriorTestExpirationDate = Prior PEIRecord.'Ycsl] a pi rati on Date.

for each quarter subsequent to the quarter of the PriorPEIRecord.EndDate and prior to the quarter of the CurrentOperatingDale

Set OSO Reporter to false.

Locate a LocalionReportingFrequency record for the test location where ReportingFrequencyCode = "OS", the
BeginQuarter is on or before the quarter being checked, and the EndQuarter is null or is on or after the quarter being
checked.

If found,

Set OSO Reporter to true.

if (OSO Reporter == false or the quarter to check is the 3rd quarter)

if (FF2LPEIEligible == true and the quarter to check is between the FF2LPEIBeginYearQuarter and the
FF2LPEIEndYearQuarter (inclusive))

else if (OSO Reporter == true and the quarter to check is the 2nd quarter)

if (FF2LPEIEligible == true and the quarter to check is between the FF2LPEIBeginYearQuarter and the
FF2LPEIEndYearQuarter (inclusive))

Add 3 quarters to the PriorTestExpirationDate.

if (CurrentOperatingDate > PriorTestExpirationDate)

if (PEIMissingOpDatalnfo is not null)

Set CurrentPEIStatus = "Missing Op Data"

else if {FF2LPEIEligible == false)

Set CurrentPEIStatus = "OOC-PEI Test Expired-Fuel Flow To Load Test Ignored"

Add 1 quarter to the PriorTestExpirationDate.

else

Set CurrentPEIStatus = "OOC-PEI Test Expired'

Return result CurrentPEIStatus.

else

Set CurrentPEIStatus = "IC-Extension'

Environmental Protection Agency

Page 31 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Missing Op Data

OOC-PEI Test
Expired
OOC-PEI Test
Expired-Fuel
Flow To Load
Test Ignored

Response

The [testtype] status for [key] could not be determined, because the Op Supp Data
record for OPHOURS, OSHOURS, or OPDAYS is missing for

[MISSINGOPDATAINFO] (and possibly other previous reporting periods). If you have
submitted emissions data for prior quarters, you should be able to retrieve these records
by logging on to the EPA host.

The prior [testtype] for [key] with TestNumber [testnum] has expired.

The prior [testtype] for [key] with TestNumber [testnum] has expired. A prior
fuel-flow-to-load test for MonitoringSystemID [ID] was ignored.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 32 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	ADESTAT-13

Check Name:	Determine System Appendix D Status

Related Former Checks:

Applicability:

Description:

Specifications:

if (CurrentAppendixDStatus == "OOC-Multiple Reasons" OR (CurrentAppendixDStatus starts with "OOC" and Current Accuracy Status
starts with "OOC" and CurrentAppendixDStatus o CurrentAccuracyStatus))

Set CurrentAppendixDStatus = "OOC-Multiple Reasons"

else it (CurrentAppendixDStatus starts with "OOC")

—do nothing

else if (CurrentAccuracyStatus starts with "OOC")

Set CurrentAppendixDStatus = CurrentAccuracyStatus.

else if ((CurrentAppendixDStatus is not null and does not start with "IC" or "Undetermined" and CurrentAppendixDStatus does not end
with "Not Yet Evaluated") and (CurrentAccuracyStatus does not start with "IC" or "Undetermined" and CurrentAccuracyStatus does not
end with "Not Yet Evaluated") and CurrentAppendixDStatus o CurrentAccuracyStatus)

Set CurrentAppendixDStatus = "Invalid Data".

else if (CurrentAppendixDStatus does not start with "IC" or "Undetermined" and CurrentAppendixDStatus does not end with "Not Yet
Evaluated" AND CurrentAppendixDStatus is not null)

— do nothing

else if (CurrentAccuracyStatus does not start with "IC" or "Undetermined" and CurrentAccuracyStatus does not end with "Not Yet
Evaluated")

Set CurrentAppendixDStatus = CurrentAccuracyStatus.
else if (CurrentAppendixDStatus ends with "Not Yet Evaluated" or CurrentAccuracyStatus ends with "Not Yet Evaluated")

Set CurrentAppendixDStatus = "Test Not Yet Evaluated"
else if (CurrentAppendixDStatus starts with "Undetermined" or CurrentAccuracyStatus starts with "Undetermined")

Set CurrentAppendixDStatus = "Undetermined"
else if (CurrentAppendixDStatus == "IC-Extension" or CurrentAccuracyStatus == "IC-Extension")

Set CurrentAppendixDStatus = "IC-Extension"

else

Set CurrentAppendixDStatus = "IC"
if (PEIRequired == true)

if (CurrentAppendixDStatus == "OOC-Multiple Reasons" OR (CurrentAppendixDStatus starts with "OOC" and
CurrentPEIStatus starts with "OOC" and CurrentAppendixDStatus o CurrentPEIStatus))

Set CurrentAppendixDStatus = "OOC-Multiple Reasons"

Environmental Protection Agency

Page 33 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else if (CurrentAppendixDStatus starts with "OOC")

—	do nothing

else if (CurrentPEIStalus starts with "OOC")

Set CurrentAppendixDStatus = CurrentPEIStatus.

else if ((CurrentAppendixDStatus is not null and does not start with "IC" or "Undetermined" and CurrentAppendixDStatus does
not end with "Not Yet Evaluated") and (CurrentPEIStatus does not start with "IC" or "Undetermined" and CurrentPEIStatus does
not end with "Not Yet Evaluated") and CurrentAppendixDStatus <> CurrentPEIStatus:)

Set CurrentAppendixDStatus = "Invalid Data".

else if (CurrentAppendixDStatus does not start with "IC" or "Undetermined" and CurrentAppendixDStatus does not end with
"Not Yet Evaluated" AND CurrentAppendixDStatus is not null)

—	do nothing

else if (CurrentPEIStatus does not start with "IC" or "Undetermined" and CurrentPEIStatus does not end with "Not Yet
Evaluated")

Set CurrentAppendixDStatus = CurrentPEIStatus.
else if (CurrentAppendixDStatus ends with "Not Yet Evaluated" or CurrentPEIStatus ends with "Not Yet Evaluated")

Set CurrentAppendixDStatus = "Test Not Yet Evaluated"
else if (CurrentAppendixDStatus starts with "Undetermined" or CurrentPEIStatus starts with "Undetermined")

Set CurrentAppendixDStatus = "Undetermined"
else if (CurrentAppendixDStatus == "IC-Extension" or CurrentPEIStatus == "IC-Extension")

Set CurrentAppendixDStatus = "IC-Extension"

else

Set CurrentAppendixDStatus = "IC"

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report

Fuel Flowmeter QA Status Evaluation

Environmental Protection Agency

Page 34 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Daily Calibration Status

Environmental Protection Agency

Page 35 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DCSTAT-1

Check Name:	Locate Most Recent Prior Daily Calibration Test

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Set PriorDailyCalRecord = null.

Set InvalidDailyCalRecord= null.

Locate the most recent record in DailyCalTestRecordsByLocationForQAStatus for the location where:

a)	ComponentID is equal to the ApplicableComponentID AND

b)	ValidFlag is equal to "Y" AND

c)	the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed
if (DailyCalTestRecordsByLocationForQAStalus is found)

Set PriorDailyCalRecord = the found record in DailyCalTestRecordsByLocationForQAStatus.

Locate the most recent record in DailyCalTestRecordsByLocationForQAStalus for the location where:

a)	the ComponentID is equal to the ApplicableComponentID AND

b)	ValidFlag is equal to "N" AND

c)	the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed

if (DailyCalTestRecordsByLocationForQAStatus is found AND EndDate/Hour/Min is greater than the
PriorI)ailyCalRecor{l.\ .nd\)dlc I lour Min)

Set InvalidDailyCalRecord = the found record in DailyCalTestRecordsByLocationForQAStatus.

else

Locate the most recent record in Daily CalTestRecordsByLocationForQAStatus for the location where:

a)	the ComponentID is equal to the ApplicableComponentID AND

b)	ValidFlag is equal to "N" AND

c)	the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed
if (DailyCalTestRecordsByLocationForQAStatus is found)

Set InvalidDailyCalRecord = the found record in DailyCalTestRecordsByLocationForQAStatus.

Results:

Result	Response	Severity

Environmental Protection Agency

Page 36 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:

2	Process/Category:

3	Process/Category:

4	Process/Category:

5	Process/Category:

6	Process/Category:

Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report

C02 Daily Calibration Status Evaluation
FLOW Daily Calibration Status Evaluation
NOX Daily Calibration Status Evaluation
02 Dry Daily Calibration Status Evaluation
02 Wet Daily Calibration Status Evaluation
S02 Daily Calibration Status Evaluation

Environmental Protection Agency

Page 37 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DCSTAT-2

Check Name:	Locate Most Recent Prior Event

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Set PriorDailyCalEventRecord= null.

Set CurrentDailyCalStatus = null.

Locate the most recent record in QACertificationEventRecords where:

a)	the ComponentID is equal to the ApplicableComponentID AND

b)	the QACertEventDate/Hour is on or prior to the CurrentMII] Record.\ )dlc I lour AND

AND either

a)	PriorDailyCalRecord is null AND the QACertEventDate/Hour is in the CurrentReportingPeriod OR

b)	QACertEventDate/Hour is after the PriorDailyCalRecord.EndDatefHour

AND either

a)	DualRangeStatus = false OR

b)	HighRangeComponentID o LowRangeComponentID OR

c)	QACertEventCode o 20, 25, 26, 30, or 172 and CurrentAnalyzerRangeUsed= "H" OR

d)	QACertEventCode <> 35 or 171 and CurrentAnalyzerRangeUsed= "L"

if (QACertificationEventRecords is found)

Set PriorDailyCalEventRecord = the found record in QACertificationEventRecords

If (PriorDailyCalEventRecord is null)

if (PriorDailyCalRecord is null)

if (the number of clock hours between the First Day of Operation/First Hour of Operation and the
CurrentMHVRecord.Date/Hour is less than 25)

Set CurrentDailyCalStatus = "IC-Undetermined".

else

Locate the latest record in HourlyOpData where the Date/Hour is ON OR PRIOR to the 24th clock hour following
the First Day of Operation/First Hour of Operation and OpTime is equal to zero.

if (HourlyOpData is found)

Locate the first record in HourlyOpData where the Date/Hour is after the Date/Hour in the HourlyOpData
record found above and ON OR PRIOR to the CurentMHVRecord.T)ate/Yk>ur and the OpTime is greater
than zero.

if (not found OR the number of clock hours between HourlyOpData.Date/Hour and the
CurrentMHVRecord.Date/Hour is less than 8)

Set CurrentDailyCalStatus = "IC-Undetermined".

else

Set CurrentDailyCalStatus = "OOC-No Prior Test".

Environmental Protection Agency

Page 38 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

else

else

Set CurrentDailyCalStatus = "OOC-No Prior Test".

if (PriorDailyCalRecord .TestResultCode = null)

Set CurrentDailyCalStatus = "OOC-Test Has Critical Errors",
else if (PriorDailyCalRecord .TestResultCode = "FAILED")

Set CurrentDailyCalStatus = "OOC-Test Failed",
else if (PriorDailyCalRecord .TestResultCode = "ABORTED")
Set CurrentDailyCalStatus = "OOC-Test Aborted".

Set CurrentDailyCalStatus = "OOC-Event".

if (InvalidDailyCalRecordis not null and InvalidDailyCalRecord.I jidDatc I lour is BEFORE the
PriorDailyCalEventRecord.QACertEverrtDate/Hour)

Results:

Result

Usage:

1

2

3

4

5

6

Set InvalidDailyCalRecord = null.

Response

Severity

Process/Category:	Emissions Data Evaluation Report	C02 Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	FLOW Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	NOX Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 Daily Calibration Status Evaluation

Environmental Protection Agency

Page 39 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DCSTAT-3

Check Name:	Determine Test Expiration Date for Most Recent Prior Daily Calibration Test

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Set OnlineDailyCalRecordto null.

if (CurrentDailyCalStatus is null)

if (PriorDailyCalRecord.OnUnelndicator == 1)

if (the number of clock hours between the I'riorDailyCalRecord.I lour and the CurrentMHVRecord.Date/Hour is less
than 26)

Set CurrentDailyCalStatus = "IC".

else

Locate the latest record in HourlyOpData where OpTime is equal to zero and the number of clock hours between
the Date/Hour and the PriorDailyCalRecord.T)ate/Yk>ur is less than or equal to 26.

if (HourlyOpData is found)

Locate the earliest record in HourlyOpData where the Date/Hour is after the Date/Hour in the
HourlyOpData record found above and OpTime is greater than zero.

if (the number of clock hours between the HourlyOpData.Date/Hour and the
CurrentMHVRecord.Date/Hour is greater than or equal to 8)

Set CurrentDailyCalStatus = "OOC-Expired".

else

Set CurrentDailyCalStatus = "IC-Grace".

else

Set CurrentDailyCalStatus = "OOC-Expired".

else

Locate the most recent record in DailyCalTestRecordsByLocationForQAStatus for the location where:

a)	ComponentID is equal to the ApplicableComponentlD AND

b)	ValidFlag is equal to "Y" AND

c)	the Onlinelndicator = 1 AND

d)	the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed
if (DailyCalTestRecordsByLocationForQAStatus is found

Set OnlineDailyCalRecord = the found record in DailyCalTestRecordsByLocationForQAStatus.
if (InvalidDailyCalRecordis null)

Locate the record in DailyCalTestRecordsByLocationForQAStatus for the location where:

Environmental Protection Agency

Page 40 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

a)	the ComponentID is equal to the ApplicableComponentID AND

b)	ValidFlag is equal to "N" AND

c)	the Onlinelndicator = 1 AND

d)	the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed

if (DailyCalTestRecordsByLocalionForQAStatus is found AND the EndDate/Hour is after the
OnlineDailyCalRecordEndDatefHour AND the EndDate/Hour is equal to or prior to the
PriorI)ailyCalRecord.\ )dlc I lour)

set InvalidDailyCalRecord = the found record in DailyCalTestRecordsByLocationForQAStatus.

if {OnlineDailyCalRecord .TestResultCode = null)

Set CurrentDailyCalStatus = "OOC-Prior Online Test Has Critical Errors".

else if (OnlineDailyCalRecord .TestResultCode = "FAILED")

Set CurrentDailyCalStatus = "OOC-Prior Online Test Failed".

else if (OnlineDailyCalRecord.TestResultCode = "ABORTED")

Set CurrentDailyCalStatus = "OOC-Prior Online Test Aborted".

else if (the number of OPERATING hours between the OnlineDailyCalRecord.Dsite/YLom and the
CurrentMII]'Record.I lour is less than 26 AND the number of clock hours between the
PriorI)ailyCalRecord.\)dlc I lour and the CurrentMHVRecord.Date/Hour is less than 26)

Set CurrentDailyCalStatus = "IC".

else

if (the number of clock hours between the OnlineDailyCalRecord.Dsite/YLom and the
CurrentMHVRecord.Date/Hour is less than 26)

Set CurrentDailyCalStatus = "IC".

else

Locate the latest record in HourlyOpData where OpTime is equal to zero and the number of clock
hours between the Date/Hour and the OnlineDailyCalRecord.Dsite/YLom is less than or equal to
26.

if (HourlyOpData is found)

Locate the earliest record in HourlyOpData where the Date/Hour is after the Date/Hour in
the HourlyOpData record found above and OpTime is greater than zero.

if (the number of clock hours between the HourlyOpDataDatefHour and the
CurrentMII]'Record.I lour is greater than or equal to 8)

Set CurrentDailyCalStatus = "OOC-Expired".

else

Set CurrentDailyCalStatus = "IC-Grace".

else

Environmental Protection Agency

Page 41 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Set CurrentDailyCalStatus = "OOC-Expired".

else

if (Rpt Period Op Hour Accumulator Array for the location is less than 26)

Set CurrentDailyCalStatus = "IC-Undetermined".

else

Set CurrentDailyCalStatus = "OOC-Expired".

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Daily Calibration Status Evaluation

2	Process/Category:	Emissions Data Evaluation Report	FLOW Daily Calibration Status Evaluation

3	Process/Category:	Emissions Data Evaluation Report	NOX Daily Calibration Status Evaluation

4	Process/Category:	Emissions Data Evaluation Report	02 Dry Daily Calibration Status Evaluation

5	Process/Category:	Emissions Data Evaluation Report	02 Wet Daily Calibration Status Evaluation

6	Process/Category:	Emissions Data Evaluation Report	S02 Daily Calibration Status Evaluation

Environmental Protection Agency

Page 42 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DCSTAT-4

Check Name:	Determine Final Daily Calibration Status

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Set AlternateDailyCalRecord= null.

if (CurrentDailyCalStatus begins with "OOC")

if (InvalidDailyCalRecord is not null)

Set CurrentDailyCalStatus = CurrentDailyCalStatus &

Return result CurrentDailyCalStatus.

else if (DualRangeStatus = true and CurrentDailyCalStatus begins with "IC")

if (CurrentAnalyzerRangeUsed = "H")

Set AlternateAnalyzerRange = "L".

Set AltemateComponentID = LowRangeComponentID.

else

Set AlternateAnalyzerRange = "H".

Set AltemateComponentID = HighRangeComponentlD.

Locate the most recent record in DailyCalTestRecordsByLocationForQAStatus for the location where:

a)	ComponentID is equal to the AltemateComponentID AND

b)	ValidFlag = "Y" AND

c)	SpanScaleCode is equal to the AlternateAnalyzerRange
if (DailyCalTestRecordsByLocationForQAStatus is found)

Set AlternateDailyCalRecord = the found record in DailyCalTestRecordsByLocationForQAStatus.
if (AlternateDailyCalRecord is not null)

if {AlternateDailyCalRecord.TestResultCode = null)

Set CurrentDailyCalStatus = "OOC-Alternate Range Test Has Critical Errors",
else if {AlternateDailyCalRecord. TestResultCode = "FAILED")

Set CurrentDailyCalStatus = "OOC-Alternate Range Test Failed",
else if {AlternateDailyCalRecord.TestResultCode = "ABORTED")

Set CurrentDailyCalStatus = "OOC-Alternate Range Test Aborted".

else

Locate the latest record in DailyCalTestRecordsByLocationForQAStatus for the location where:
a) ComponentID is equal to the AltemateComponentID AND

Environmental Protection Agency

Page 43 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

b)	the SpanScaleCode is equal to the AlternateAnalyzerRange

c)	the TestResultCode is equal to "FAILED" or "ABORTED"

if (DailyCalTestRecordsByLocationForQAStalus is found AND (either the PriorDailyCalRecord is null or
EndDate/Hour/Minute is after the PriorDailyCalRecord.EndDate/YLour/Minute))

Set CurrentDailyCalStatus = "OOC-No Passing Test After Alternate Range Failed Test".

(Report this status in the Evaluation Report under the PriorDailyCalRecord.TestDate/Hour.)

Else

Locate the latest record in DailyCalTestRecordsByLocationForQAStatus for the location where:

a)	ComponentID is equal to the ApplicableComponentID AND

b)	the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed

c)	the TestResultCode is equal to "FAILED" or "ABORTED"

if (DailyCalTestRecordsByLocalionForQAStatus is found AND EndDate/Hour/Minute is after the
AlternateDailyCalRecord.EndDate/Ykmr/Minute)

Set CurrentDailyCalStatus = "OOC-No Passing Alternate Range Test After Failed Test".
(Report this status in the Evaluation Report under the PriorDailyCalRecord.TestT)ate/Y{our.)

if (CurrentDailyCalStatus begins with "OOC")

if (InvalidDailyCalRecordis not null)

Set CurrentDailyCalStatus = CurrentDailyCalStatus &

Locate the most recent record in DailyCalTestRecordsByLocationForQAStatus for the location where:

a)	ComponentID is equal to the AlternateComponentID AND

b)	ValidFlag is equal to "N" AND

c)	the SpanScaleCode is equal to the AlternateAnalyzerRange

if (DailyCalTestRecordsByLocationForQAStatus is found AND the EndDate/Hour is after the
AlternateDailyCalRecord.I jidDatc I lour)

Set InvalidDailyCalRecord = the found record in DailyCalTestRecordsByLocationForQAStatus.
Set CurrentDailyCalStatus = CurrentDailyCalStatus &

Return result CurrentDailyCalStatus .

elseif (CurrentDailyCalStatus does not begin with "IC")

Return result CurrentDailyCalStatus .

Environmental Protection Agency

Page 44 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

OOC-Alternate
Range Test
Aborted
OOC-Alternate
Range Test
Aborted*
OOC-Alternate
Range Test
Failed

OOC-Alternate
Range Test
Failed*

OOC-Alternate
Range Test Ftas
Critical Errors
OOC-Alternate
Range Test Ftas
Critical Errors*
OOC-Event

OOC-Event*

OOC-Expired
OOC-Expired*

OOC-No Passing
Alternate Range
Test After Failed
Test

OOC-No Passing
Alternate Range
Test After Failed
Test*

OOC-No Passing
Test After
Alternate Range
Failed Test
OOC-No Passing
Test After
Alternate Range
Failed Test*

OOC-No Prior
Test

OOC-No Prior
Test*

OOC-No
Probationary
Calibration Test

Response

The prior daily calibration test for the alternate range [altscale] of [compkey], which was
completed on [altdate], was aborted.

The prior daily calibration test for the alternate range [altscale] of [compkey], which was
completed on [altdate], was aborted. An invalid daily calibration test completed on
[invdate] was ignored.

The prior daily calibration test for the alternate range [altscale] of [compkey], which was
completed on [altdate], failed.

The prior daily calibration test for the alternate range [altscale] of [compkey], which was
completed on [altdate], failed. An invalid daily calibration test completed on [invdate]
was ignored.

The prior daily calibration test for the alternate range [altscale] of [compkey], which was
completed on [altdate], has critical errors.

The prior daily calibration test for the alternate range [altscale] of [compkey], which was
completed on [altdate], has critical errors. An invalid daily calibration test completed on
[invdate] was ignored.

You reported a QA Certification Event record for QACertEventCode [code]
QACertEventDate [eventdate] for [compkey], but you did not perform a subsequent
daily calibration test.

You reported a QA Certification Event record for QACertEventCode [code]
QACertEventDate [eventdate] for [compkey], but you did not perform a subsequent
daily calibration test. An invalid daily calibration test completed on [invdate] was
ignored.

The prior daily calibration test for [compkey] completed on [date] has expired.

The prior daily calibration test for [compkey] completed on [date] has expired. An
invalid daily calibration test completed on [invdate] was ignored.

The prior daily calibration test for [compkey] was completed on [date], however a
subsequent passing test on [altscale] has not been completed. When a daily calibration
test is failed for a dual-range analyzer, you must complete a passing daily calibration test
on both ranges before the monitor is considered to be in-control. An invalid daily
calibration test completed on [invdate] was ignored.

The prior daily calibration test for [compkey] was completed on [date], however a
subsequent passing test on [altscale] has not been completed. When a daily calibration
test is failed for a dual-range analyzer, you must complete a passing daily calibration test
on both ranges before the monitor is considered to be in-control. An invalid daily
calibration test completed on [invdate] was ignored.

The prior daily calibration test for [compkey] was completed on [date], which is prior to
a failed or aborted test for the alternate range [altscale]. When a daily calibration test is
failed for a dual-range analyzer, you must complete a passing daily calibration test on
both ranges before the monitor is considered to be in-control.

The prior daily calibration test for [compkey] was completed on [date], which is prior to
a failed or aborted test for the alternate range [altscale]. When a daily calibration test is
failed for a dual-range analyzer, you must complete a passing daily calibration test on
both ranges before the monitor is considered to be in-control. An invalid daily
calibration test completed on [invdate] was ignored.

You did not report a prior daily calibration test for [compkey] during the reporting
period. Any daily calibration test that may have been completed in a prior reporting
period has expired.

You did not report a prior daily calibration test for [compkey] during the reporting
period. Any daily calibration test that may have been completed in a prior reporting
period has expired. An invalid daily calibration test completed on [invdate] was
ignored.

This check result is obsolete.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

No Errors

Environmental Protection Agency

Page 45 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

OOC-No

Probationary

Calibration Test*

OOC-Prior

Online Test

Aborted

OOC-Prior

Online Test

Aborted*

OOC-Prior

Online Test

Expired

OOC-Prior

Online Test

Expired*

OOC-Prior

Online Test

Failed

OOC-Prior

Online Test

Failed*

OOC-Prior

Online TestFtas

Critical Errors

OOC-Prior

Online TestFtas

Critical Errors*

OOC-Test

Aborted

OOC-Test

Aborted*

OOC-Test Failed

OOC-Test

Failed*

OOC-Test Ftas
Critical Errors
OOC-Test Ftas
Critical Errors*

This check result is obsolete.

The prior online daily calibration test for [compkey] completed on [ondate] was aborted.

The prior online daily calibration test for [compkey] completed on [ondate] was aborted.
An invalid daily calibration test completed on [invdate] was ignored.

The prior online daily calibration test for [compkey] completed on [ondate] has expired.

The prior online daily calibration test for [compkey] completed on [ondate] has expired.
An invalid daily calibration test completed on [invdate] was ignored.

The prior online daily calibration test for [compkey] completed on [ondate] failed.

The prior online daily calibration test for [compkey] completed on [ondate] failed. An
invalid daily calibration test completed on [invdate] was ignored.

The prior online daily calibration test for [compkey] completed on [ondate] has critical
errors.

The prior online daily calibration test for [compkey] completed on [ondate] has critical
errors. An invalid daily calibration test completed on [invdate] was ignored.

The prior daily calibration test for [compkey] completed on [date] was aborted.

The prior daily calibration test for [compkey] completed on [date] was aborted. An

invalid daily calibration test completed on [invdate] was ignored.

The prior daily calibration test for [compkey] completed on [date] failed.

The prior daily calibration test for [compkey] completed on [date] failed. An invalid

daily calibration test completed on [invdate] was ignored.

The prior daily calibration test for [compkey] completed on [date] has critical errors.

The prior daily calibration test for [compkey] completed on [date] has critical errors.
An invalid daily calibration test completed on [invdate] was ignored.

No Errors

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Usage:

1

2

3

4

5

6

Process/Category:	Emissions Data Evaluation Report	C02 Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	FLOW Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	NOX Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Daily Calibration Status Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 Daily Calibration Status Evaluation

Environmental Protection Agency

Page 46 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Daily Calibration Test

Environmental Protection Agency

Page 47 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAYCAL-1

Check Name:

Daily Calibration Test Component Type Check

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

For the daily calibration test:

Set Daily Cal Calc Result to null.

Set Daily Cal Fail Date and Daily Cal Fail Hour to null.

If the ComponentID is null,

set Daily Cal Component Type Valid to false, and return result A.

Otherwise,

If the ComponentTypeCode of the associated component is equal to "S02", "NOX", "C02", "02", or "FLOW",
set Daily Cal Component Type Valid to true.

Otherwise,

set Daily Cal Component Type Valid to false, and return result B.

If component is invalid, do not perform injection-based checks. Set the calculated values to null.

Results:

Result

A

B

Response

You did not provide [fieldname], which is required for [key].
The ComponentTypeCode in the monitoring plan is [comptype]. This type of
component does not require a calibration test. Only component types 'S02', 'NOX',
'C02', '02', or 'FLOW' may have a daily calibration test.

Severity
Fatal

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 48 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAYCAL-2

Check Name:

Aborted and Incomplete Daily Calibration Test Check

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

For the daily calibration test:

Set Evaluate Upscale Injection AND Evaluate Zero Injection to false.

If Daily Cal Component Type Valid is equal to true,

If the TestResultCode is equal to "ABORTED",

set Daily Cal Calc Result to "ABORTED", and return result A.

If the TestResultCode is equal to "INC",

set Daily Cal Calc Result to "INC".

If ZeroInjectionDate, ZeroInjectionHour, and ZeroMeasuredValue are not null,
set Evaluate Zero Injection to true.

If UpscalelnjectionDate, UpscalelnjectionHour, and UpscaleMeasuredValue are not null,
set Evaluate Upscale Injection to true.

Otherwise,

set Evaluate Upscale Injection AND Evaluate Zero Injection to true.

Results:

Result
A

Response

The TestResultCode indicates that the [type] test for [key] was aborted. If the test was
aborted for a reason not related to monitor performance, you should not report the test.

Severity

Informational Message

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 49 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-3

Check Name:	Online Offline Indicator Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For a daily calibration test:

Set Daily Cal Calc Online Ind to null.

If ZeroOpTime is equal to 0 OR UpscaleOpTime is equal to 0
set Daily Cal Calc Online Ind to 0

else if ZeroOpTime is equal to 1 AND UpscaleOpTime is equal to 1
set Daily Cal Calc Online Ind to 1

else

set Daily Cal Calc Online Ind to the OnlineOfflinelndicator.

If (OnlineOfflinelndicator is null)
return result A.

else

If (Daily Cal Calc Online Ind is equal to 0)

If (OnlineOfflinelndicator is equal to 1)
return result B.

else

Locate the latest OOC Test Record for the location where the ComponentID and SpanScaleCode is equal
to the ComponentID and SpanScaleCode in the current test and the EndDate/Hour is prior to the Date/Hour
of the current test.

If not found,

Set Ignored Daily Calibration Tests to true.

If (Daily Cal Calc Result <> "INVALID")

set Daily Cal Calc Result to "IGNORED"

Otherwise,

Locate an QA Certification Event Record for the location where the ComponentID is equal to the
ComponentID in the current test AND OOCRequired == " Y" AND the EventDate/Hour is after
the EndDate/Hour of the retrieved OOC test AND the EventDate/Hour is on or before the
EndDate/Hour of the current test AND EITHER

a)	SpanScaleCode in the current test is null OR

b)	SpanScaleCode in the current test == "H" and QACertEventCode o 20, 25, 26, 30, or 172 OR

c)	SpanScaleCode in the current test == "L" and QACertEventCode o 35 or 171

If found,

return result D.

Environmental Protection Agency

Page 50 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

A

B

C
D

Response

You did not provide [fieldname], which is required for [key].
The OnlineOfflinelndicator in the daily calibration test indicates that the test was
performed on-line, but OperatingTime in the Hourly Operating Data record is 0.

This check result is obsolete.

The test was peformed while the unit was not operating, but this is not valid, because
you reported an QA Certification Event record indicating that you needed to perform an
online-offline calibration demonstration allowing you to conduct off-line daily
calibration tests. However, you have not reported an online-offline calibration
demonstration subsequent to the EventDate and EventHour in the QA Certification
Event record.

Severity

Critical Error Level 1
Critical Error Level 1

No Errors

Critical Error Level 2

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 51 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAYCAL-4

Check Name:

Test Span Scale Valid

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

For a daily calibration test with a valid component:

Set Daily Cal Span Scale Valid to true.

If the ComponentTypeCode of the associated component is not equal to "FLOW",

If the SpanScaleCode is null,

set Daily Cal Span Scale Valid to false, and return result A.

If the SpanScaleCode is not equal to "H" or "L",

set Daily Cal Span Scale Valid to false, and return result B.

If the EM Test Date Valid AND EM Test Hour Valid are true,

If the SpanScaleCode is equal to "H"

Locate an Analyzer Range record for the component where the AnalyzerRangeCode is equal to "L", the
BeginDate and BeginHour is on or before the Date and Hour in the current test, and the EndDate is null or
the EndDate and EndHour is on or after the Date and Hour of the current test.

If found,

set Daily Cal Span Scale Valid to false, and return result C.

If the SpanScaleCode is equal to "L"

Locate an Analyzer Range record for the component where the AnalyzerRangeCode is equal to "H", the
BeginDate and BeginHour is on or before the Date and Hour of the current test, and the EndDate is null or
the EndDate and EndHour is on or after the Date and Hour of the current test.

If found,

set Daily Cal Span Scale Valid to false, and return result C.

Otherwise,

If the SpanScaleCode is not null,

set Daily Cal Span Scale Valid to false, and return result D.

Environmental Protection Agency

Page 52 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

A

B

C

D

Usage:

1

Response

You did not provide [fieldname], which is required for [key].

You reported the value [value], which is not in the list of valid values, in the field

[fieldname] for [key].

The active analyzer range for the component is inconsistent with the span scale [value]
reported for the [type] test for [key].

You reported a SpanScaleCode in the [type] test for [key], but this is not appropriate for
flow component.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 53 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-5

Check Name:	Determine Span Value

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For a daily calibration test:

Set Daily Cal Span Value to null.

If EM Test Date Valid, EM Test Hour Valid, and Daily Cal Span Scale Value are all true,

Locate the System Component records for the associated component with the earliest Begin Date.

If found,

If the BeginDate in the retrieved record is not null, the BeginHour in the retrieved record is between 0 and 23, and
the BeginDate and BeginHour is later than the Date and Hour of the test.

Locate a Span Record for the location where the ComponentTypeCode equal to the ComponentTypeCode
of the associated component, the SpanScaleCode is equal to the SpanScaleCode in the test, the Span Value
is greater than 0, the BeginDate and BeginHour is on or before the BeginDate and BeginHour of the
retrieved record, and the EndDate is null or the EndDate and EndHour is after the BeginDate and
BeginHour of the retrieved record.

Otherwise,

Locate a Span Record for the location where the ComponentTypeCode equal to the ComponentTypeCode
of the associated component, the SpanScaleCode is equal to the SpanScaleCode in the test, the Span Value
is greater than 0, the BeginDate and BeginHour is on or before the Date and Hour of the test, and the
EndDate is null or the EndDate and EndHour is after the Date and Hour of the test.

If not found,

return result A.

If more than one record is found,
return result B.

If one record is found,

set Daily Cal Span Value to the SpanValue in the retrieved span record.

else

return result C.

Environmental Protection Agency

Page 54 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

Usage:

1

Response

You have not reported a valid monitoring plan span record that was active during the
test for [key].

You reported more than one monitoring plan span record that was active during the test
for [key].

The component reported for [key] is not part of any monitoring system.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 55 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-6

Check Name:	Daily Calibration Test Upscale Gas Level Code Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

If the UpscaleGasCode is null,

set Daily Cal Upscale Gas Level Valid to false, and return result A.

If the UpscaleGasCode is not equal to "MID" or "HIGH",

set Daily Cal Upscale Gas Level Valid to false, and return result B.

If the ComponentTypeCode of the associated component is equal to "FLOW", and the UpscaleGasLevelCode is equal to "MID",
set Daily Cal Upscale Gas Level Valid to false, and return result C.

Otherwise,

set Daily Cal Upscale Gas Level Valid to true.

Results:

Result	Response	Severity

A	You did not provide [fieldname], which is required for [key].	Critical Error Level 1

B	You reported the value [value], which is not in the list of valid values, in the field	Critical Error Level 1

[fieldname] for [key],

C	You have reported a value of "MID" as the UpscaleGasCode. This value is not	Critical Error Level 1

appropriate for flow components.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 56 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-7

Check Name:	Reference Values Consistent with Calibration Gas Levels

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale and zero injection:

If ZeroReferenceValue greater than or equal to 0, UpscaleReferenceValue greater than 0, AND ZeroReferenceValue is greater than
or equal to UpscaleReferenceValue,

set Daily Cal Calc Result to "INVALID", and return result A.

Results:

Result	Response	Severity

A	The reference value is not consistent with the reported calibration gas levels in the daily	Critical Error Level 1

calibration test for [key]. The reference values of zero-level gas injection or reference
signals must be less than that of the upscale gas injection.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 57 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-8

Check Name:	Zero Measured Value Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with a zero injection:

If ZeroMeasuredValue is null,
return result A.

Results:

Result	Response	Severity

A	You did not provide [fieldname], which is required for [key].	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 58 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-9

Check Name:	Zero Reference Value Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with a zero injection:

If ZeroReferenceValue is null,
return result A.

If ZeroReferenceValue is less than 0,
return result B.

Results:

Severity

Critical Error Level 1
Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Result	Response

A	You did not provide [fieldname], which is required for [key],

B	The value [value] in the field [fieldname] for [key] is not within the range of valid

values. This value must be greater than or equal to zero.

Environmental Protection Agency

Page 59 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-10

Check Name:	Zero Calibration Error Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with a zero injection:

If the ZeroCalibrationError is null,
return result A.

If the ZeroCalibrationError is less than 0,
return result B.

Results:

Severity

Critical Error Level 1
Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Result	Response

A	You did not provide [fieldname], which is required for [key],

B	The value [value] in the field [fieldname] for [key] is not within the range of valid

values. This value must be greater than or equal to zero.

Environmental Protection Agency

Page 60 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-11

Check Name:	Zero APS Indicator Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with a zero injection:

If ZeroAPSIndicator is null,
return result A.

Results:

Result	Response	Severity

A	You did not provide [fieldname], which is required for [key].	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 61 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-12

Check Name:	Upscale Measured Value Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

If UpscaleMeasuredValue is null,
return result A.

Results:

Result	Response	Severity

A	You did not provide [fieldname], which is required for [key].	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 62 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-13

Check Name:	Upscale Reference Value Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

If UpscaleReferenceValue is null,
return result A.

If UpscaleReference Value is less than or equal to 0,
return result B.

Results:

Severity

Critical Error Level 1
Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Result	Response

A	You did not provide [fieldname], which is required for [key],

B	The value [value] in the field [fieldname] for [key] is not within the range of valid

values. This value must be greater than zero.

Environmental Protection Agency

Page 63 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-14

Check Name:	Upscale Calibration Error Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

If the UpscaleCalibrationError is null,
return result A.

If the UpscaleCalibrationError is less than 0,
return result B.

Results:

Severity

Critical Error Level 1
Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Result	Response

A	You did not provide [fieldname], which is required for [key],

B	The value [value] in the field [fieldname] for [key] is not within the range of valid

values. This value must be greater than or equal to zero.

Environmental Protection Agency

Page 64 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-15

Check Name:	Upscale APS Indicator Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

If UpscaleAPSIndicator is null,
return result A.

Results:

Result	Response	Severity

A	You did not provide [fieldname], which is required for [key].	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 65 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-16

Check Name:	Upscale Injection Time Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

If the UpscalelnjectionHour is not between 0 and 23, or the UpscalelnjectionMinute is null and Legacy Data Evaluation == false,
or the UpscalelnjectionMinute is not between 0 and 59,

set Daily Cal Upscale Injection Time Valid to false, and return result A.

Otherwise,

set Daily Cal Upscale Injection Time Valid to true.

Results:

Result	Response	Severity

A	The [type] date, hour, and/or minute for [key] is invalid.	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 66 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-17

Check Name:	Zero Injection Time Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with a zero injection:

If the ZeroInjectionHour is not between 0 and 23, or the ZeroInjectionMinute is null and Legacy Data Evaluation == false, or the
ZeroInjectionMinute is not between 0 and 59,

set Daily Cal Injection Times Valid to false, and return result A.

else if Legacy Data Evaluation == false, the UpscalelnjectionDate is not null, the UpscalelnjectionHour is between 0 and 23, the
UpscalelnjectionMinute is between 0 and 59, and the UpscalelnjectionDate, UpscalelnjectionHour, and UpscalelnjectionMinute are
equal to the ZeroInjectionDate, ZeroInjectionHour, and ZeroInjectionMinute, and the associated ComponentTypeCode is not equal
to "FLOW"

set Daily Cal Injection Times Valid to false, and return result B.

Otherwise,

set Daily Cal Injection Times Valid to Daily Cal Upscale Injection Time Valid.

Locate another Daily Calibration Test Record for the location where the ComponentID and SpanScale are equal to the
ComponentID and SpanScale in the current record, TestResultCode is not equal to "INC", and the EndDate/Hour/Minute is
between the UpscalelnjectionDate/Hour/Minute and ZeroInjectionDate/Hour/Minute of the current test.

If found,

return result C.

else

If the absolute value of the difference between the ZeroInjectionDate/Hour and the UpscalelnjectionDate/Hour in
the current test is greater than 1,
return result D.

Results:

Result

A

B

D

Response

The [type] date, hour, and/or minute for [key] is invalid.

You reported that the zero injection and upscale injection for [key] were performed at
the same time. This is invalid.

This [testtype] was conducted at the same time as another [testtype] for the same
component and range.

The zero and upscale injections for [key] were not performed in the same or adjacent
clock hours.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 2

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 67 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAYCAL-18

Check Name:

Zero Reference Value Consistent with Span

Related Former Checks:

Applicability:

CEM Check

Description:

Validation Tables:

Test Tolerances (Cross Check Table)

Specifications:

For the daily calibration test with a Daily Cal Span Value that is not null and a ZeroReferenceValue greater than or equal to 0:

Calculate Zero Reference Percent of Span = ZeroReferenceValue I Daily Cal Span Value * 100, and round to result to one decimal
place.

If Zero Reference Percent of Span is greater than 20.0,

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to "7DAY" and the FieldDescription is

equal to "GasPercentOfSpan".

If Zero Reference Percent of Span is greater than 20.0 + Tolerance in the cross-check record,
return result A.

Otherwise,

return result B.

Results:

Result
A

Response

The tag value of at least one Zero level reference signal or calibration gas for [key] is
[percent]%, which does not meet the performance specifications of 40 CFR Part 75.
The concentration of the zero reference signal or calibration gas must be less than or
equal to 20.0% of the span value. The test is invalid.

Severity

Critical Error Level 2

B

The tag value of at least one zero level reference signal or calibration gas for [key] is
[percent]%, which does not meet the performance specifications of 40 CFR Part 75.
The concentration of the zero reference signal or calibration gas must be less than or
equal to 20.0% of the span value.

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 68 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAYCAL-19

Check Name:

Upscale Reference Value Consistent with Span

Related Former Checks:

Applicability:

CEM Check

Description:

Validation Tables:

Test Tolerances (Cross Check Table)

Specifications:

For the daily calibration test with a Daily Cal Span Value that is not null and an UpscaleReferenceValue greater than 0:

Calculate Upscale Reference Percent of Span = UpscaleReferenceValue I Daily Cal Span Value * 100, and round to result to one
decimal place.

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to "7DAY" and the FieldDescription is equal to
"GasPercentOflSpan".

If UpscaleGasLevelCode is equal to "MID", and the ComponentTypeCode of the associated component is not equal to "FLOW",

If Upscale Reference Percent of Span is less than 50.0 or greater than 60.0,

If Upscale Reference Percent of Span is less than 50.0 - Tolerance in the cross-check record or Upscale Reference
Percent of Span greater than 60.0 + Tolerance in the cross-check record,
return result A.

If Upscale Reference Percent of Span is less than 50.0 - Tolerance in the cross-check record or Upscale
Reference Percent of Span greater than 70.0 + Tolerance in the cross-check record,
return result C.

Otherwise,

return result D.

Otherwise,

If Upscale Reference Percent of Span is greater than 100.0,
return result E

If Upscale Reference Percent of Span is less than 80.0,

If Upscale Reference Percent of Span is less than 80.0 - Tolerance in the cross-check record,
return result E.

Otherwise,

return result B.

If UpscaleGasLevelCode is equal to "HIGH",

If the ComponentTypeCode of the associated component is equal to "FLOW",

If Upscale Reference Percent of Span is less than 50.0 or greater than 70.0,

Otherwise,

return result F.

Environmental Protection Agency

Page 69 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B

D

Response

The tag value of at least one Mid level reference signal or calibration gas for [key] is
[percent]%, which does not meet the performance specifications of 40 CFR Part 75.
The concentration of the mid reference signal or calibration gas must be between 50.0%
and 60.0% of the span value. The test is invalid.

The tag value of at least one Mid level reference signal or calibration gas for [key] is
[percent]%, which does not meet the performance specifications of 40 CFR Part 75.
The concentration of the 'mid' reference signal or calibration gas must be between 50.0%
and 60.0% of the span value.

The tag value of at least one High level reference signal for [key] is [percent]%, which
does not meet the performance specifications of 40 CFR Part 75. The value of the high
reference signal for a flow component must be between 50.0% and 70.0% of the span
value. The test is invalid.

The tag value of at least one High level reference signal for [key] is [percent]%, which
does not meet the performance specifications of 40 CFR Part 75. The value of the 'high'
reference signal for a flow component must be between 50.0% and 70.0% of the span
value.

The tag value of at least one High level reference calibration gas for [key] is [percent]%,
which does not meet the performance specifications of 40 CFR Part 75. The
concentration of the high reference calibration gas must be between 80.0% and 100.0%
of the span value. The test is invalid.

The tag value of at least one High level reference calibration gas for [key] is [percent]%,
which does not meet the performance specifications of 40 CFR Part 75. The
concentration of the 'high' reference calibration gas must be between 80.0% and 100.0%
of the span value.

Severity

Critical Error Level 2

Non-Critical Error

Critical Error Level 2

Non-Critical Error

Critical Error Level 2

Non-Critical Error

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 70 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-20

Check Name:	Calculate Zero Gas Injection or Reference Signal Results

Related Former Checks:

Applicability:	CEM Check

Description:

Validation Tables:

Test Tolerances (Cross Check Table)

Specifications:

For the daily calibration test with a zero injection:

If (Daily Cal Span Value is null, or ZeroReferenceValue of the test is null or is less than zero, or ZeroMeasuredValue of the test is
null)

Set Daily Cal Calc Result to "INVALID", Daily Cal Zero Injection Calc Result to null, Daily Cal Zero Injection Calc
APS Indicator to null, and return result A.

Otherwise,

Calculate diff= abs(ZeroMeasuredValue - ZeroReferenceValue)

Set Daily Cal Zero Injection Calc APS Indicator to 0.

If (ComponentTypeCode of the associated component is equal to "C02" or "02")

Round diff to 1 decimal place.

Set Daily Cal Zero Injection Calc Result to diff.

If (Daily Cal Calc Result is not equal to "INVALID" or "IGNORED")

If (Daily Cal Zero Injection Calc Result is greater than 1.0)

If (ZeroCalibrationError is greater than or equal to 0 and less than or equal to 1.0)

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to
"7DAY" and the FieldDescription is equal to "DifferencePCT".

If (the absolute value of the difference between diff and ZeroCalibrationError is less than
or equal to the Tolerance in the cross-check record)

if (Daily Cal Calc Result is not equal to "INC" or "FAILED")
set Daily Cal Calc Result to "PASSED".

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
Zerolnj ectionDate/ZeroInj ectionHour)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour.

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

Environmental Protection Agency

Page 71 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
Zerolnj ectionDate/ZeroInj ectionHour)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour.

else if (Daily Cal Calc Result is not equal to "INC" or "FAILED")
set Daily Cal Calc Result to "PASSED".

If (ComponentTypeCode of the associated component is equal to "S02" or "NOX")

Calculate Daily Cal Zero Injection Calc Result = min(round(afr$rI Daily Cal Span
Round diff to 1 decimal places.

If (Daily Cal Zero Injection Calc Result is greater than 5 .0, AND (Daily Cal Span
50 AND diff is less than or equal to 5.0) OR (Daily Cal Span Value is greater than
is less than or equal to 200 AND diff is less than or equal to 10.0)))

set Daily Cal Zero Injection Calc Result to diff.
set Daily Cal Zero Injection Calc APS Indicator to 1.

If (Daily Cal Calc Result is not equal to "INVALID" or "FAILED" or "INC" or "IGNORED")
set Daily Cal Calc Result to "PASSAPS".

Otherwise,

If (Daily Cal Zero Injection Calc Result is greater than 5 .0)

If (Daily Cal Calc Result is not equal to "INVALID" or "IGNORED")

If (ZeroAPSIndicator is NOT equal to 1 and ZeroCalibrationError is greater than or equal
to 0 and less than or equal to 5.0)

Locate the Test Tolerance cross-check record where the TestTypeCode is equal
to "7DAY" and the FieldDescription is equal to "CalibrationError".

If (the absolute value of the difference between Daily Cal Zero Injection Calc
Result and ZeroCalibrationError is less than or equal to the Tolerance in the
cross-check record)

If (Daily Cal Calc Result is not equal to "PASSAPS" or "INC" or
"FAILED")

set Daily Cal Calc Result to "PASSED".

Otherwise,

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
Zerolnj ectionDate/ZeroInj ectionHour)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour.

Otherwise,

Value * 100, 1), 9999.9)

Value is less than or equal to
50 AND Daily Cal Span Value

Environmental Protection Agency

Page 72 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (ZeroAPSIndicator is equal to 1 and ZeroCalibrationError is greater than or
equal to 0, and (Daily Cal Span Value is less than or equal to 50 AND
ZeroCalibrationError is less than or equal to 5.0) OR (Daily Cal Span Value is
greater than 50 AND Daily Cal Span Value is less than or equal to 200 AND
ZeroCalibrationError is less than or equal to 10.0)))

Locate the Test Tolerance cross-check record where the TestTypeCode is
equal to "7DAY" and the FieldDescription is equal to "DifferencePPM".

If (the absolute value of the difference between diff and
ZeroCalibrationError is less than or equal to the Tolerance in the
cross-check record)

If (Daily Cal Calc Result is not equal to "INC" or "FAILED")
set Daily Cal Calc Result to "PASSAPS".

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is
greater than ZeroInjectionDate/ZeroInjectionHour)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour.

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
Zerolnj ectionDate/ZeroInj ectionHour)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour.

Otherwise,

If (Daily Cal Calc Result is not equal to "FAILED" or "INC" or "PASSAPS" or "IGNORED")
set Daily Cal Calc Result to "PASSED".

If (ComponentTypeCode of the associated component is equal to "FLOW")

Calculate Daily Cal Zero Injection Calc Result = min(round(diff I Daily Cal Span Value * 100, 1), 9999.9).

Round diff to 2 decimal places.

If (Daily Cal Zero Injection Calc Result is greater than 6.0, the SampleAcquisitionMethodCode of the associated
component is equal to "DP", and diff is less than or equal to 0.02)

set Daily Cal Zero Injection Calc Result to diff.
set Daily Cal Zero Injection Calc APS Indicator to 1.

If (Daily Cal Calc Result is not equal to "INVALID" or "FAILED" or "INC" or "IGNORED")
set Daily Cal Calc Result to "PASSAPS".

Otherwise,

Environmental Protection Agency

Page 73 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (Daily Cal Zero Injection Calc Result is greater than 6.0)

If (Daily Cal Calc Result is not equal to "INVALID" or "IGNORED")

If (ZeroAPSIndicator is NOT equal to 1 and ZeroCalibrationError is greater than or equal
to 0 and less than or equal to 6.0)

Locate the Test Tolerance cross-check record where the TestTypeCode is equal
to "7DAY" and the FieldDescription is equal to "CalibrationError".

If (the absolute value of the difference between Daily Cal Zero Injection Calc
Result and ZeroCalibrationError is less than or equal to the Tolerance in the
cross-check record)

If (Daily Cal Calc Result is not equal to "PASSAPS" or "INC" or
"FAILED")

set Daily Cal Calc Result to "PASSED".

Otherwise,

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
Zerolnj ectionDate/ZeroInj ectionHour)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour.

Otherwise,

If (ZeroAPSIndicator is equal to 1, the SampleAcquisitionMethodCode of the
associated component is equal to "DP", and ZeroCalibrationError is greater than
or equal to 0 and less than or equal to 0.02)

Locate the Test Tolerance cross-check record where the TestTypeCode is
equal to "7DAY" and the FieldDescription is equal to
"DifferenceINH20".

If (the absolute value of the difference between diff and
ZeroCalibrationError is less than or equal to the Tolerance in the
cross-check record)

If (Daily Cal Calc Result is not equal to "INC" or "FAILED")
set Daily Cal Calc Result to "PASSAPS".

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is
greater than ZerolnjectionDate/ZeroInjectionHour)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour.

Environmental Protection Agency

Page 74 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

set Daily Cal Calc Result to "FAILED".
If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
Zerolnj ectionDate/ZeroInj ectionHour)

set Daily Cal Fail Date to ZeroInjectionDate.
set Daily Cal Fail Hour to Zerolnjection Hour.

Otherwise,

If (Daily Cal Calc Result is not equal to "INC" or "FAILED", or "PASSAPS" or "IGNORED")
set Daily Cal Calc Result to "PASSED".

Results:

Result
A

Response

The software could not evaluate the [test] calculations reported for [key], because of the
errors listed above.

Severity

Informational Message

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 75 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-21

Check Name:	Calculate Upscale Gas Injection or Reference Signal Results

Related Former Checks:

Applicability:	CEM Check

Description:

Validation Tables:

Test Tolerances (Cross Check Table)

Specifications:

For the daily calibration test with an upscale injection:

If (Daily Cal Span Value is null, or Daily Cal Upscale Gas Level Valid is false, or UpscaleReferenceValue of the test is null or is
less than or equal to zero, or UpscaleMeasuredValue of the test is null)

Set Daily Cal Calc Result to "INVALID". Daily Cal Upscale Injection Calc Result to null, Daily Cal Upscale Injection
Calc APS Indicator to null, and return result A.

Otherwise,

Calculate diff= abs(UpscaleMeasuredValue - UpscaleReferenceValue)

Set Daily Cal Upscale Injection Calc APS Indicator to 0.

If (ComponentTypeCode of the associated component is equal to "C02" or "02")

Round diff to 1 decimal place.

Set Daily Cal Upscale Injection Calc Result to diff.

If (Daily Cal Calc Result is not equal to "INVALID" or "IGNORED")

If (Daily Cal Upscale Injection Calc Result is greater than 1.0)

If (UpscaleCalibrationError is greater than or equal to 0 and less than or equal to 1.0)

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to
"7DAY" and the FieldDescription is equal to "DifferencePCT".

If (the absolute value of the difference between diff and UpscaleCalibrationError is less
than or equal to the Tolerance in the cross-check record)

if (Daily Cal Calc Result is not equal to "INC" or "FAILED")
set Daily Cal Calc Result to "PASSED".

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
UpscalelnjectionDate/UpscalelnjectionHour)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour.

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

Environmental Protection Agency

Page 76 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
UpscalelnjectionDate/UpscalelnjectionHour)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour.

else if (Daily Cal Calc Result is not equal to "INC" or "FAILED" or "IGNORED")
set Daily Cal Calc Result to "PASSED".

If (ComponentTypeCode of the associated component is equal to "S02" or "NOX")

Calculate Daily Cal Upscale Injection Calc Result = minf rounds////'I Daily Cal Span Value * 100, 1), 9999.9)

Round diff to 1 decimal places.

If (Daily Cal Upscale Injection Calc Result is greater than 5.0, AND (Daily Cal Span Value is less than or equal
to 50 AND diff is less than or equal to 5.0) OR (Daily Cal Span Value is greater than 50 AND Daily Cal Span
Value is less than or equal to 200 AND diff is less than or equal to 10.0)))

set Daily Cal Upscale Injection Calc Result to diff.
set Daily Cal Upscale Injection Calc APS Indicator to 1.

If (Daily Cal Calc Result is not equal to "INVALID" or "FAILED" or "INC" or "IGNORED")
set Daily Cal Calc Result to "PASSAPS".

Otherwise,

If (Daily Cal Upscale Injection Calc Result is greater than 5.0)

If (Daily Cal Calc Result is not equal to "INVALID" or "IGNORED")

If (UpscaleAPSIndicator is NOT equal to 1 and UpscaleCalibrationError is greater than or
equal to 0 and less than or equal to 5.0)

Locate the Test Tolerance cross-check record where the TestTypeCode is equal
to "7DAY" and the FieldDescription is equal to "CalibrationError".

If (the absolute value of the difference between Daily Cal Upscale Injection Calc
Result and UpscaleCalibrationError is less than or equal to the Tolerance in the
cross-check record)

If (Daily Cal Calc Result is not equal to "PASSAPS" or "INC" or
"FAILED")

set Daily Cal Calc Result to "PASSED".

Otherwise,

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
UpscalelnjectionDate/UpscalelnjectionHour)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour.

Otherwise,

Environmental Protection Agency

Page 77 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (UpscaleAPSIndicator is equal to 1 and UpscaleCalibrationError is greater than
or equal to 0, and (Daily Cal Span Value is less than or equal to 50 AND
UpscaleCalibrationError is less than or equal to 5.0) OR (Daily Cal Span Value
is greater than 50 AND Daily Cal Span Value is less than or equal to 200 AND
UpscaleCalibrationError is less than or equal to 10.0)))

Locate the Test Tolerance cross-check record where the TestTypeCode is
equal to "7DAY" and the FieldDescription is equal to "DifferencePPM".

If (the absolute value of the difference between diff and
UpscaleCalibrationError is less than or equal to the Tolerance in the
cross-check record)

If (Daily Cal Calc Result is not equal to "INC" or "FAILED")
set Daily Cal Calc Result to "PASSAPS".

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to

UpscalelnjectionDate.

set Daily Cal Fail Hour to Upscalelnjection

Hour.

else if (Daily Cal Fail Date/Daily Cal Fail Hour is

greater than

UpscalelnjectionDate/UpscalelnjectionHour)
set Daily Cal Fail Date to
UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection
Hour.

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
UpscalelnjectionDate/UpscalelnjectionHour)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour.

Otherwise,

If (Daily Cal Calc Result is not equal to "FAILED" or "INC", or "PASSAPS" or "IGNORED")
set Daily Cal Calc Result to "PASSED".

If (ComponentTypeCode of the associated component is equal to "FLOW")

Calculate Daily Cal Upscale Injection Calc Result = min(round(diff I Daily Cal Span Value * 100, 1), 9999.9).

Round diff to 2 decimal places.

If (Daily Cal Upscale Injection Calc Result is greater than 6.0, the SampleAcquisitionMethodCode of the

associated component is equal to "DP", and diff is less than or equal to 0.02)

Environmental Protection Agency

Page 78 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

set Daily Cal Upscale Injection Calc Result to diff.
set Daily Cal Upscale Injection Calc APS Indicator to 1.

If (Daily Cal Calc Result is not equal to "INVALID" or "FAILED" or "INC" or "IGNORED")
set Daily Cal Calc Result to "PASSAPS".

Otherwise,

If (Daily Cal Upscale Injection Calc Result is greater than 6.0)

If (Daily Cal Calc Result is not equal to "INVALID" or "IGNORED")

If (UpscaleAPSIndicator is NOT equal to 1 and UpscaleCalibrationError is greater than or
equal to 0 and less than or equal to 6.0)

Locate the Test Tolerance cross-check record where the TestTypeCode is equal
to "7DAY" and the FieldDescription is equal to "CalibrationError".

If (the absolute value of the difference between Daily Cal Upscale Injection Calc
Result and UpscaleCalibrationError is less than or equal to the Tolerance in the
cross-check record)

If (Daily Cal Calc Result is not equal to "PASSAPS" or "INC" or
"FAILED")

set Daily Cal Calc Result to "PASSED".

Otherwise,

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
UpscalelnjectionDate/UpscalelnjectionHour)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour.

Otherwise,

If (UpscaleAPSIndicator is equal to 1, the SampleAcquisitionMethodCode of the
associated component is equal to "DP", and UpscaleCalibrationError is greater
than or equal to 0 and less than or equal to 0.02)

Locate the Test Tolerance cross-check record where the TestTypeCode is
equal to "7DAY" and the FieldDescription is equal to
"DifferenceINH20".

If (the absolute value of the difference between diff and
UpscaleCalibrationError is less than or equal to the Tolerance in the
cross-check record)

If (Daily Cal Calc Result is not equal to "INC" or "FAILED")
set Daily Cal Calc Result to "PASSAPS".

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

Environmental Protection Agency

Page 79 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

set Daily Cal Fail Date to

UpscalelnjectionDate.

set Daily Cal Fail Hour to Upscalelnjection

Hour.

else if (Daily Cal Fail Date/Daily Cal Fail Hour is

greater than

UpscalelnjectionDate/UpscalelnjectionHour)
set Daily Cal Fail Date to
UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection
Hour.

else

set Daily Cal Calc Result to "FAILED".

If (Daily Cal Injection Times Valid == true)

If (Daily Cal Fail Date is null)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour,
else if (Daily Cal Fail Date/Daily Cal Fail Hour is greater than
UpscalelnjectionDate/UpscalelnjectionHour)

set Daily Cal Fail Date to UpscalelnjectionDate.
set Daily Cal Fail Hour to Upscalelnjection Hour.

Otherwise,

If (Daily Cal Calc Result is not equal to "INC" or "FAILED", or "PASSAPS" or "IGNORED")
set Daily Cal Calc Result to "PASSED".

Results:

Result

Response

The software could not evaluate the [test] calculations reported for [key], because of the
errors listed above.

Severity

Informational Message

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 80 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAYCAL-22

Check Name:

Daily Calibration Test End Time Valid

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

For the daily calibration test with upscale and zero injections and a valid date, hour, and minute and injection times:

If Date, Hour, and Minute of the test does not equal the later of the ZeroInjectionDate, Hour, and Minute (if not null) and the
UpscalelnjectionDate, Hour, and Minute (if non-null),

return result A.

Results:

Result
A

Response

You reported a test Date, Hour, and Minute that is not the same as the Date, Hour, and
Minute of the last injection in the daily calibration test for [key].

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 81 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAYCAL-23

Check Name:

Reported Zero Injection Results Consistent with Recalculated Values

Related Former Checks:

Applicability:

CEM Check

Description:

Validation Tables:

Test Tolerances (Cross Check Table)

Specifications:

For the daily calibration test with a zero injection:

If the ZeroAPSIndicator is equal to 1, the ComponentTypeCode of the associated component is equal to "FLOW", and the
SampleAcquisitionMethodCode of the associated component is not equal to "DP",
return result A.

If the ZeroAPSIndicator is equal to 1, the ComponentTypeCode of the associated component is equal to "S02" or "NOX", and the
Daily Cal Span Value is greater than or equal to 200,
return result B.

If the ZeroAPSIndicator is equal to 1, the ComponentTypeCode of the associated component is equal to "C02" or "02",
return result C.

Otherwise,

If Daily Cal Zero Injection Calc Result is not null,

If the ZeroAPSIndicator in the current record is not equal to 1 and the Daily Cal Zero Injection Calc APS
Indicator is equal to 1,
return result D.

If the ZeroCalibrationError is greater than or equal to 0,

If the ComponentTypeCode of the associated component is equal to "C02" or "02"

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to "7DAY" and
the FieldDescription is equal to "DifferencePCT".

If the absolute value of the difference between the Daily Cal Zero Injection Calc Result and the
ZeroCalibrationError is greater than the Tolerance in the cross-check record,
return result E.

If the Daily Cal Zero Injection Calc APS Indicator is equal to 1,

If the ComponentTypeCode of the associated component is equal to "FLOW",

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to
"7DAY" and the FieldDescription is equal to "DifferencelNLQO".

If the absolute value of the difference between the Daily Cal Zero Injection Calc Result
and the ZeroCalibrationError is greater than the Tolerance in the cross-check record,
return result E.

Otherwise,

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to
"7DAY" and the FieldDescription is equal to "DifferencePPM".

Environmental Protection Agency

Page 82 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If the absolute value of the difference between the Daily Cal Zero Injection Calc Result
and the ZeroCalibrationError is greater than the Tolerance in the cross-check record,
return result E.

else if ZeroAPSIndicator is equal to 0,

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to "7DAY" and
the FieldDescription is equal to "CalibrationError".

If the absolute value of the difference between the Daily Cal Zero Injection Calc Result and the
ZeroCalibrationError is greater than the Tolerance in the cross-check record,
return result F.

Results:

Result
A

B

C
D

E
F

Usage:

1

Response

You reported a value of "1" as the [level] APS Indicator for [key], but you must use the
standard performance criteria for non-differential pressure flow monitors.

You reported a value of "1" as the [level] APS Indicator for [key], but you must use the
standard performance specification criteria for S02 and NOX components when the
instrument span is greater than or equal to 200.

You reported a value of "1" as the [level] APS Indicator for [key], but you must use the
standard performance specification criteria for C02 and 02 components.

You did not report a value of "1" in the [level] APS Indicator for [key], although EPA
applied the alternative performance specification to determine that the injection passed
the applicable performance specification.

The absolute difference reported as the [level] Calibration Error for [key] is inconsistent
with the recalculated absolute difference for the gas injection or reference signal.
The [level] Calibration Error reported for [key] is inconsistent with the recalculated
calibration error for the gas injection or reference signal.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 83 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-24

Check Name:	Reported Upscale Injection Results Consistent with Recalculated Values

Related Former Checks:

Applicability:	CEM Check

Description:

Validation Tables:

Test Tolerances (Cross Check Table)

Specifications:

For the daily calibration test with an upscale injection:

If the UpscaleAPSIndicator is equal to 1, the ComponentTypeCode of the associated component is equal to "FLOW", and the
SampleAcquisitionMethodCode of the associated component is not equal to "DP",
return result A.

If the UpscaleAPSIndicator is equal to 1, the ComponentTypeCode of the associated component is equal to "S02" or "NOX", and
the Daily Cal Span Value is greater than or equal to 200,
return result B.

If the UpscaleAPSIndicator is equal to 1, the ComponentTypeCode of the associated component is equal to "C02" or "02",
return result C.

Otherwise,

If Daily Cal Upscale Injection Calc Result is not null,

If the UpscaleAPSIndicator in the current record is not equal to 1 and the Daily Cal Upscale Injection Calc APS
Indicator is equal to 1,
return result D.

If the UpscaleCalibrationError is greater than or equal to 0,

If the ComponentTypeCode of the associated component is equal to "C02" or "02"

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to "7DAY" and
the FieldDescription is equal to "DifferencePCT".

If the absolute value of the difference between the Daily Cal Upscale Injection Calc Result and
the UpscaleCalibrationError is greater than the Tolerance in the cross-check record,
return result E.

If the Daily Cal Upscale Injection Calc APS Indicator is equal to 1,

If the ComponentTypeCode of the associated component is equal to "FLOW",

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to
"7DAY" and the FieldDescription is equal to "DifferencelNLQO".

If the absolute value of the difference between the Daily Cal Upscale Injection Calc
Result and the UpscaleCalibrationError is greater than the Tolerance in the cross-check
record,

return result E.

Otherwise,

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to
"7DAY" and the FieldDescription is equal to "DifferencePPM".

Environmental Protection Agency

Page 84 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If the absolute value of the difference between the Daily Cal Upscale Injection Calc
Result and the UpscaleCalibrationError is greater than the Tolerance in the cross-check
record,

return result E.

else if UpscaleAPSIndicator is equal to 0,

Locate the Test Tolerance cross-check record where the TestTypeCode is equal to "7DAY" and
the FieldDescription is equal to "CalibrationError".

If the absolute value of the difference between the Daily Cal Upscale Injection Calc Result and
the UpscaleCalibrationError is greater than the Tolerance in the cross-check record,
return result F.

Results:

Result
A

B

C
D

E
F

Usage:

1

Response

You reported a value of "1" as the [level] APS Indicator for [key], but you must use the
standard performance criteria for non-differential pressure flow monitors.

You reported a value of "1" as the [level] APS Indicator for [key], but you must use the
standard performance specification criteria for S02 and NOX components when the
instrument span is greater than or equal to 200.

You reported a value of "1" as the [level] APS Indicator for [key], but you must use the
standard performance specification criteria for C02 and 02 components.

You did not report a value of "1" in the [level] APS Indicator for [key], although EPA
applied the alternative performance specification to determine that the injection passed
the applicable performance specification.

The absolute difference reported as the [level] Calibration Error for [key] is inconsistent
with the recalculated absolute difference for the gas injection or reference signal.
The [level] Calibration Error reported for [key] is inconsistent with the recalculated
calibration error for the gas injection or reference signal.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 85 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-25

Check Name:	Determination of Overall Daily Calibration Test Result

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test:

If Daily Cal Calc Result is equal to "INVALID",
set Daily Cal Calc Result to null.

If TestResultCode is null,
return result A.

If TestResultCode is not equal to "PASSED", "PASSAPS", "FAILED", "INC", or "ABORTED",
return result B.

If Daily Cal Calc Result is equal to "FAILED",

If TestResultCode is equal to "PASSED" or "PASSAPS",
return result C.

If TestResultCode is equal to "INC",
return result D.

If Daily Cal Calc Result is equal to "PASSED" or "PASSAPS", and the TestResultCode is equal to "FAILED",
return result E.

Results:

Result

A

B

D

Usage:
1

Response

You did not provide [fieldname], which is required for [key].

You reported the value [value], which is not in the list of valid values for this test type,
in the field [fieldname] for [key].

The TestResultCode for [key] indicates a passing test, but the recalculated results
indicate a failing test.

The TestResultCode for [key] indicates an incomplete test, but the recalculated results
indicate a failing test. A test is considered to have failed if it fails to meet the
performance criteria for any injection.

You reported a TestResultCode of "FAILED" for [key], but the results recalculated or
determined from the other reported values indicate that the test passed.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 86 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-26

Check Name:	Upscale Gas Type Code Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Validation Tables:

Gas Type Code (Lookup Table)

Specifications:

For the daily calibration test with an upscale injection:

UpscaleGasTypeValid = true.

Locate System Parameter lookup table record where SysParamName = 'PGVP_AETB_RULE_DATE'.

Set Daily Cal PGVP Rule Date to System Parameter.Param Value 1.

If UpscaleGasTypeCode is null,

If the ComponentTypeCode of the associated component is equal to "S02", "NOX", "C02", or "02", and the Date of the
test is on or after 9/26/2011,

UpscaleGasTypeValid = false,
return result A.

Otherwise,

If the ComponentTypeCode of the associated component is equal to "FLOW",

UpscaleGasTypeValid = false
return result B.

else if the UpscaleGasTypeCode is not equal to "GMIS", "PRM", "RGM", or "SRM",

if the UpscaleGasTypeCode is not in the GasTypeCode lookup table.

UpscaleGasTypeValid = false
return result C.

else if the UpscaleGasTypeCode == "ZERO" or "ZAM"

UpscaleGasTypeValid = false
return result C

else if the UpscaleGasTypeCode == "APPVD"
return result D

else if the ComponentTypeCode == "S02", "NOX", "C02" or "02",

Locate Protocol Gas Parameter To Type Cross Reference records where ProtocolGasParameter is equal
to ComponentTypeCode in the current Daily Calibration record, and GasTypeList contains the
UpscaleGasTypeCode in the current Daily Calibration record.

If not found,

UpscaleGasTypeValid = false
return result E.

else if ComponentTypeCode == "02", UpscaleGasTypeCode == "AIR", and the UpscaleGasCode is not
equal to "HIGH",

UpscaleGasTypeValid = false

Environmental Protection Agency

Page 87 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result F.

Results:

Result
A

B

C

D

E
F

Usage:
1

Response

You did not report a UpscaleGasTypeCode for [key]. This information is required by
the Protocol Gas Verification Program reporting rule.

You reported a value in the UpscaleGasTypeCode field for [key]. This value should not
be reported for a FLOW component.

You reported the value [value], which is not in the list of valid values, in the field
[fieldname] for [key].

You reported "APPVD" as the [fieldname] for [key]. This code indicates that you
received approval from EPA for a new type of Protocol Gas. If you have not received
approval from EPA, please contact ECMPS support. If you have already received
approval, you should log in to the ECMPS host, so that the ECMPS program can obtain
the necessary information to override this error.

You reported an UpscaleGasTypeCode that is not appropriate for a [comptype]
component for [key].

You reported an [fieldname] of "AIR" for [key], which indicates the use of purified air
material, but this material can only be used for a high-level calibration.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 88 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-27

Check Name:	Cylinder ID Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

If CylinderlD is null,

If UpscaleGasTypeValid is true, and the UpscaleGasTypeCode is not null and not equal to "AIR",
return result A.

Otherwise,

If the UpscaleGasTypeCode is equal to "AIR",
return result B.

else if UpscaleGasTypeValid is true, and the UpscaleGasTypeCd is null,
return result C.

Results:

Result

A

B

Response

You did not provide [fieldname], which is required for [key].

You indicated that you used purified air material or zero air material instead of a

cylinder gas, but you reported a Cylinderldentifier.

You reported a [fieldname] for [key], but you did not report an UpscaleGasTypeCode.

Severity

Critical Error Level 1
Critical Error Level 1

Non-Critical Error

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 89 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-28

Check Name:	Vendor ID Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

If VendorlD is null,

If UpscaleGasTypeValid is true, and the UpscaleGasTypeCode is not null and not equal to "AIR", "SRM", "NTRM",
"GMIS", "RGM", or "PRM",
return result A.

else if the VendorlD is not in the Protocol Gas Vendor lookup table,
return result B.

Otherwise,

If the UpscaleGasTypeCode is equal to "AIR", "SRM", "NTRM", "GMIS", "RGM", or "PRM",
return result C.

else if the DeactivationDate in the Protocol Gas Vendor record is not null and the Date of the current test is on or after the
DeactivationDate + 3 years,
return result F.

else if the VendorlD is equal to "NONPGVP", and the Date of the test is on or after the Daily Cal PGVP Rule Date + 60
days + 3 years,

return result D.

else if UpscaleGasTypeValid is true, and the UpscaleGasTypeCd is null,
return result E.

Results:

Result

A

B

D

E
F

Response

You did not provide [fieldname], which is required for [key].

You reported a Vendorldentifier of [value], which is not in the list of Protocol Gas
Vendors, for [key]. Please visit the ECMPS Support Website for the list of Protocol
Gas Vendors.

You reported a [fieldname] for [key], but this value should only be reported for an EPA
Protocol Gas Type. The cylinder gas type of [gastype] indicates the use of a non-EPA
Protocol Gas Type.

You reported a Vendorldentifier of "NONPGVP" for [key], indicating the use of a EPA
Protocol Gas Type purchased from a vendor not participating in the Protocol Gas
Vendor Program (PGVP). You cannot use a gas purchased from a non-participating
vendor that was acquired more than 60 days after the PGVP Effective Date.
You reported a [fieldname] for [key], but you did not report an UpscaleGasTypeCode.
You have reported a Vendorldentifier for [key] of a vendor who is no longer
participating in the Protocol Gas Verification Program.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 2

Non-Critical Error
Critical Error Level 2

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 90 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAYCAL-29

Check Name:	Cylinder Expiration Date Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

If ExpirationDate is null,

If UpscaleGasTypeValid is true, and the UpscaleGasTypeCode is not null and not equal to "AIR",
return result A.

Otherwise,

If the UpscaleGasTypeCode is equal to "AIR",
return result B.

else if the ExpirationDate is prior to the Date of the test,
return result C.

else if the ExpirationDate is more than 8 years after the Date of the test,
return result D.

else if UpscaleGasTypeValid is true, and the UpscaleGasTypeCd is null,
return result E.

Results:

Result

A

B

C
D

E

Usage:

1

Response

You did not provide [fieldname], which is required for [key].

You reported a [fieldname] for [key], but this value should only be reported for an EPA
Protocol Gas Type. The cylinder gas type of [gastype] indicates the use of a non-EPA
Protocol Gas Type.

You reported an ExpirationDate for the cylinder that is prior to the date of the test for
[key].

You reported an ExpirationDate for the cylinder that is more than eight years after the

date of the test for [key]. Gas cylinders expire in less than eight years.

You reported a [fieldname] for [key], but you did not report an UpscaleGasTypeCode.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 2
Critical Error Level 2
Non-Critical Error

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 91 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAYCAL-30

Check Name:

Upscale Gas Type Code Components Valid

Related Former Checks: 2013 Q1 replacement for DAYCAL-26

Applicability:

CEM Check

Description:

Specifications:

For the daily calibration test with an upscale injection:

UpscaleGasTypeValid = true.

Locate System Parameter lookup table record where SysParamName = 'PGVP_AETB_RULE_DATE'.

Set Daily Cal PGVP Rule Date to System Parameter.Param Value 1.

If UpscaleGasTypeCode is null,

If the ComponentTypeCode of the associated component is equal to "S02", "NOX", "C02", or "02", and the Date of the
test is on or after 9/26/2011,

UpscaleGasTypeValid = false,
return result A.

Otherwise,

If the ComponentTypeCode of the associated component is equal to "FLOW",
UpscaleGasTypeValid = false
return result B.

Set Protocol Gas Invalid Component List to null.
Set Protocol Gas Exclusive Component List to null.
Set Protocol Gas Balance Component List to null.
Set Protocol Gas Duplicate Component List to null.

Set Protocol Gas Component List to null.

Set Protocol Gas Approval Requested = true.
Set Protocol Gas Component Count to 0.

Set Balance Component Count to 0.

For each GasComponentCode in UpscaleGasTypeCode ,

Locate a record in the GasComponentCodeLookupTable where GasComponentCode is equal to the
GasComponentCode in the UpscaleGasTypeCode .

If not found, or GasComponentCode is equal to "ZERO",

Add GasComponentCode to Protocol Gas Invalid Component List.

Else

If CanCombinelndicator is equal to 0,

Add GasComponentCode to Protocol Gas Exclusive Component List.

If BalanceComponentlndicator is equal to 1,

Add GasComponentCode to Protocol Gas Balance Component List.

Increament Balance Component Count by 1.

If the GasComponentCode is equal to "APPVD",

Else

Environmental Protection Agency

Page 92 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set Protocol Gas Approval Requested - true.

If GasComponentCode is not in Protocol Gas Component List,

add GasComponentCode to Protocol Gas Component List.

Else if GasComponentCode is not in Protocol Gas Duplicate Component List,
add GasComponentCode to Protocol Gas Duplicate Component List.

Increament Protocol Gas Component Count by 1.

If Protocol Gas Lnvalid Component List is not null,

UpscaleGasTypeValid = false
return result C.

Else if Protocol Gas Duplicate Component List is not null,
set Protocol Gas Component List Valid = false,
return result L.

Else if Protocol Gas Exclusive Component List is not null, and Protocol Gas Component Count is greater than 1,
UpscaleGasTypeValid = false
return result D.

Else if Protocol Gas Approval Requested is equal to true,
return result E.

Else if Protocol Gas Exclusive Component List is null, and Balance Component Count is equal to 0,

set UpscaleGasTypeValid = false,
return result J.

Else if Protocol Gas Exclusive Component List is null, and Balance Component Count is greater than 1,

set UpscaleGasTypeValid = false,
return result K.

Else if the UpscaleGasTypeCode is not equal to "GMIS", "NTRM", "PRM", "RGM", or "SRM",

If the ComponentTypeCode is equal to "S02" or "C02",

If no GasComponentCode in UpscaleGasTypeCode is equal to ComponentTypeCode,
UpscaleGasTypeValid = false
return result F.

Else if the ComponentTypeCode is equal to "02",

If UpscaleGasTypeCode is not equal to "AIR", and no GasComponentCode in
UpscaleGasTypeCode is equal to "02",

UpscaleGasTypeValid = false
return result G.

Else if UpscaleGasTypeCode is equal to "AIR", and the UpscaleGasCode is not equal to "HIGH",
UpscaleGasTypeValid = false
return result H.

Else if the ComponentTypeCode is equal to "NOX",

If no GasComponentCode in GasTypeCode is equal to "NO" or "N02",

UpscaleGasTypeValid = false
return result I.

Environmental Protection Agency

Page 93 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

E

F

G

H

I

J

K

Response

You did not report a UpscaleGasTypeCode for [key]. This information is required by
the Protocol Gas Verification Program reporting rule.

You reported a value in the UpscaleGasTypeCode field for [key]. This value should not
be reported for a FLOW component.

You reported the values ([invalidlist]), in the field [fieldname] for [key], which are not
in the list of valid values.

You reported multiple gas components in the field [fieldname] for [key] that include
values ([exclusivelist]) that you should report by themselves.

You reported "APPVD" as the [fieldname] for [key]. This code indicates that you
received approval from EPA for a new type of Protocol Gas. If you have not received
approval from EPA, please contact ECMPS support. If you have already received
approval, you should log in to the ECMPS host, so that the ECMPS program can obtain
the necessary information to override this error.

You reported an UpscaleGasTypeCode that is not appropriate for a [comptype]
component for [key].

You reported an UpscaleGasTypeCode that is not appropriate for a [comptype]
component for [key].

You reported an [fieldname] of "AIR" for [key], which indicates the use of purified air
material, but this material can only be used for a high-level calibration.

You reported an UpscaleGasTypeCode that is not appropriate for a [comptype]
component for [key].

You reported an UpscaleGasTypeCode that does not contain a PGVP balance
component. A single balance component is required when reporting other individual gas
components.

You reported an UpscaleGasTypeCode that contains multiple PGVP balance
components ([balancelist]). A single balance component is required when reporting
other individual gas components.

Your reported one or more duplicate gas component records.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Daily Calibration Test

Environmental Protection Agency

Page 94 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Daily Emissions Data

Environmental Protection Agency

Page 95 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-1

Check Name:

Determine Need for Daily C02 Emissions Record

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current C02 Mass Daily Record = null
Daily Op Time = null

if (Daily Op Time Accumulator Array for the location >= 0)

Daily Op Time = Daily Op Time Accumulator Array for the location

Daily Op Time Accumulator Array for the location = 0.

C02 Method Count = Active records in MonitoringMethodData for the location and date where
ParameterCode begins with "C02"

FSA Method Count = Active records in MonitoringMethodData for the location and date where
ParameterCode = "C02M" and MethodCode = "FSA"

if (FSA Method Count > 0 AND CO2 Method Count >1)
return result A

if (FSA Method Count > 0)

Expected Summary Value for C02 Array for the location = true

CO2 Mass Daily Emissions Count = count of DailyEmissionsData records with ParameterCode = "C02M" where
Current Date = DailyEmissionsData.Date

if (C02 Mass Daily Emissions Count >1)

Rpt Period C02 Mass Reported Accumulator Array for the location = -1
Rpt Period C02 Mass Calculated Accumulator Array for the location = -1
return result B

else if (FSA Method Count == 0 AND C02 Mass Daily Emissions Count > 0)
return result C

else if (FSA Method Count > 0 AND C02 Mass Daily Emissions Count == 0 AND Daily Op Time > 0
return result D

else if (FSA Method Count > 0 AND C02 Mass Daily Emissions Count ==1)

Current C02 Mass Daily Record = matching DailyEmissionsData record

else

If (Daily Op Time == 0)

return result E

Environmental Protection Agency

Page 96 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B
C

D

E

Response

You have reported more than one active method to determine C02 emissions in your
monitoring plan for this date.

You reported more than one Daily Emissions record for [param] for the day.
You reported a Daily Emissions record for C02M, but you did not report an active
C02M FSA method record in your monitoring plan for the day.

You did not report a Daily Emissions record for C02M for the day.

You reported a Daily Emissions record for C02M, but this is not appropriate for a
non-operating day.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	C02 Daily Emissions

Environmental Protection Agency

Page 97 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAILY-2

Check Name:	Check Total Daily Emissions Value

Related Former Checks:

Applicability:

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

Set Calc TDEto null.

If (Current C02 Mass Daily Record is not null)

If (Current C02 Mass Daily ifecorrf.TotalDailyEmissions >= 0 AND Rpt Period C02 Mass Reported Accumulator Array for the
location >= 0)

Rpt Period C02 Mass Reported Accumulator Array for the location = Rpt Period C02 Mass Reported Accumulator
Array for the location + Current C02 Mass Daily itecortf.TotalDailyEmissions

if (Current C02 Mass Daily ifecorrf.UnadjustedDailyEmissions is not null OR Calc C02 Unadj is not null)

if (Current C02 Mass Daily itecortf.AdjustedDailyEmissions is null)

Calc TDE = Calc C02 Unadj

else if (Current C02 Mass Daily ifecorrf.UnadjustedDailyEmissions is not null AND Current C02 Mass Daily
ifecortf.AdjustedDailyEmissions is greater than or equal to 0 AND is less than or equal to Current C02 Mass Daily
RecordUnadj ustedDailyEmi ssions)

Calc TDE = Current C02 Mass Daily ifecorrf.AdjustedDailyEmissions

else if (Current C02 Mass Daily ifecorrf.AdjustedDailyEmissions is greater than or equal to 0)

Calc TDE = Current C02 Mass Daily RecordAdjustedDailyEmissions

If (Calc TDE is not null)

If (Current C02 Mass Daily ifecorrf.SorbentRelatedMassEmissions is not null)

If (Current C02 Mass Daily ifecorrf.SorbentRelatedMassEmissions >= 0)

Calc TDE = Calc TDE + Current C02 Mass Daily ifecorrf.SorbentRelatedMassEmissions

else

Set Calc TDE to null.

else if (Current C02 Mass Daily ifecorrf.UnadjustedDailyEmissions is null AND Legacy Data Evaluation == true AND Current
C02 Mass Daily ifecorrf.TotalDailyEmissions >= 0)

Calc TDE = Current C02 Mass Daily ifecorrf.TotalDailyEmissions

If {Calc TDE is null)

Rpt Period C02 Mass Calculated Accumulator Array for the location = -1

else

If (Rpt Period C02 Mass Calculated Accumulator Array for the location >= 0)

Rpt Period C02 Mass Calculated Accumulator Array for the location = Rpt Period C02 Mass Calculated
Accumulator Array for the location + Calc TDE

If (Current C02 Mass Daily ifecorrf.TotalDailyEmissions >= 0)

Environmental Protection Agency

Page 98 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (Calc TDE is not null)

Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "C02M DAILY" AND
UOM = "TON"

if (ABS(Current C02 Mass Daily itecortf.TotalDailyEmissions - Calc TDE) > Tolerance)

return result A

else

return result C

else

Rpt Period C02 Mass Reported Accumulator Array for the location = -1
return result B

Results:

Result
A

Response

The [fieldname] reported in the Daily Emissions record for [param] is inconsistent with
the recalculated value.

The [fieldname] reported in the Daily Emissions record for [param] is invalid. The
value must be greater than or equal to 0.

The TotalDailyEmissions in the Daily Emissions record for [param] could not be
recalculated due to other errors listed in this report.

Severity

Critical Error Level 1

B

Critical Error Level 1

C

Informational Message

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions

Environmental Protection Agency

Page 99 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAILY-3

Check Name:	Check Adjusted Daily Emissions Value

Related Former Checks:

Applicability:

Description:

Specifications:

if (Current C02 Mass Daily Record is not null),

if (Current C02 Mass Daily itecortf.AdjustedDailyEmissions is not null),

If (Current C02 Mass Daily ifecortf.AdjustedDailyEmissions is less than 0),
return result A

else

If (Current C02 Mass Daily ifecorrf.UnadjustedDailyEmissions is greater than or equal to 0 AND is less than
Current C02 Mass Daily itecortf.AdjustedDailyEmissions),
return result B

Results:

Result
A

B

Response

The [fieldname] reported in the Daily Emissions record for [param] is invalid. The
value must be greater than or equal to 0.

The AdjustedDailyEmissions in the Daily Emissions record for [param] is greater than
the UnadjustedDailyEmissions. The adjusted value should be less than the unadjusted
value.

Severity

Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	C02 Daily Emissions

Environmental Protection Agency

Page 100 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-4

Check Name:

Check Sorbent Related Emissions

Related Former Checks:

Applicability:

Description:

Specifications:

if (Current C02 Mass Daily Record is not null),

if (Current C02 Mass Daily itecortf.SorbentRelatedMassEmissions is not null AND is less than 0),

return result A

Results:

Result
A

Response

The [fieldname] reported in the Daily Emissions record for [param] is invalid. The
value must be greater than or equal to 0.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions

Environmental Protection Agency

Page 101 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-5

Check Name:

Validate Presence of Adjusted Daily Emissions

Related Former Checks:

Applicability:

Description:

Specifications:

if (Current C02 Mass Daily Record) is not null

if (Current C02 Mass Daily itecortfAdjustedDailyEmissions is not null)

Locate a Monitor Formula record for the location and hour where the ParameterCode is equal to 'C02M" and the
FormulaCode is equal to "G-2" or "G-3".

If not found,

return result A.

Results:

Result
A

Response

You reported AdjustedDailyEmissions in the Daily Emissions record for C02M, but you
did not report a G-2 or G-3 formula in your monitoring plan.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions

Environmental Protection Agency

Page 102 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-6

Check Name:

Validate Presence of Sorbent Related Emissions

Related Former Checks:

Applicability:

Description:

Specifications:

if (Current C02 Mass Daily Record) is not null

if (Current C02 Mass Daily itecortf.SorbentRelatedMassEmissions is not null),

Missing C02M Formula = null

Locate a. Monitor Formula record for the location and hour where the ParameterCode is equal to 'C02M" and the
FormulaCode is equal to "G-5" or "G-6".

If not found,

Set Missing C02M Formula to "G-5 or G-6"

Locate a. Monitor Formula record for the location and hour where the ParameterCode is equal to 'C02M" and the
FormulaCode is equal to "G-8".

If not found,

Append "G-8" to Missing C02MFormula.

If (Missing C02M Formula is not null)
return result A.

Results:

Result
A

Response

You reported SorbentRelatedMassEmissions in the Daily Emissions record for C02M,
but you did not report [code] formula(s) in your monitoring plan.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions

Environmental Protection Agency

Page 103 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-7

Check Name:

Check Unadjusted Daily Emissions Value

Related Former Checks:

Applicability:

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

Set Calc C02 Unaclj to null.

if (Current C02 Mass Daily Record is not null)

if (Calc Total Carbon Burned is greater than 0)

Calculate Calc C02 Unadj = Calc Total Carbon Burned *44 / 24,000, and round the result to 1 decimal place.

if (Current C02 Mass Daily itecortf.UnadjustedDailyEmissions is null OR is less than 0)
return result A

else if (Current C02 Mass Daily ifecorrf.UnadjustedDailyEmissions >= 0)

Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "C02M DAILY" AND
UOM = "TON"

if (ABS(Current C02 Mass Daily itecortf.UnadjustedDailyEmissions - Calc C02 Unadj) > Tolerance)
return result B

else if (Current C02 Mass Daily ifecorrf.UnadjustedDailyEmissions is null)

If (Legacy Data Evaluation == false)

return result A.

else if (Current C02 Mass Daily ifecorrf.UnadjustedDailyEmissions is less than 0)
return result A

else

Set Calc C02 Unadj to Current C02 Mass Daily itecortf.UnadjustedDailyEmissions.

Results:

Result
A

Response

The [fieldname] reported in the Daily Emissions record for [param] is invalid. The
value must be greater than or equal to 0.

The [fieldname] reported in the Daily Emissions record for [param] is inconsistent with
the recalculated value.

Severity

Critical Error Level 1

B

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions

Environmental Protection Agency

Page 104 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-8

Check Name:

Check Fuel in Daily Fuel Record

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Locate UnitFuel record for the location and day

where FuelCd = Current Daily Fuel itecortf.UnitFuelCd

If not found,

return result A

Results:

Result
A

Response

You did not report an active Unit Fuel record for FuelCode [fueled] in your monitoring
plan.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions Fuel

Environmental Protection Agency

Page 105 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-9

Check Name:

Check Daily Fuel Feed

Related Former Checks:

Applicability:

Description:

Specifications:

if (Current Daily Fuel itecortf.DailyFuelFeed is null)
return result A.

else if (Current Daily Fuel ifecorrf.DailyFuelFeed is less than or equal to 0)
return result A.

Results:

Result
A

Response

The [fieldname] reported in the Daily Fuel record for [key] is missing or invalid. The
value must be greater than 0.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions Fuel

Environmental Protection Agency

Page 106 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-10

Check Name:

Check Carbon Content Used

Related Former Checks:

Applicability:

Description:

Specifications:

if (Current Daily Fuel itecortf.CarbonContentUsed is null)
return result A.

else if (Current Daily Fuel ifecortf.CarbonContentUsed is less than or equal to 0 or greater than 100)
return result A.

Results:

Result
A

Response

The CarbonContentUsed in the Daily Fuel record for [key] is invalid. The value must
be greater than 0 and less than or equal to 100.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions Fuel

Environmental Protection Agency

Page 107 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	DAILY-11

Check Name:	Check Fuel Carbon Burned

Related Former Checks:

Applicability:

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

Calc Fuel Carbon Burned = null

if (Current Daily Fuel itecortf.DailyFuelFeed is greater than 0 and Current Daily Fuel ifecortf.CarbonContentUsed is greater than 0 and
less than or equal to 100)

Calculate Calc Fuel Carbon Burned= Current Daily Fuel Record. I )ai I vlucl Iced * Current Daily Fuel
ifecortf.CarbonContentUsed /100, and round the result to 1 decimal place.

If Calc Total Carbon Burned is greater than or equal to 0,

Add Calc Fuel Carbon Burned to Calc Total Carbon Burned

else

Set Calc Total Carbon Burned to -1.

if (Current Daily Fuel itecortf.FuelCarbonBurned is null)
return result A.

else if (Current Daily Fuel ifecorrf.FuelCarbonBurned is less than or equal to 0)
return result A.

else if (Calc Fuel Carbon Burned is not null AND Current Daily Fwe/ifecorrfFuelCarbonBurned o Calc Fuel Carbon Burned)

Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "CARBON" AND
UOM = "LB"

if (ABS(Current Daily Fuel RecordsuelCarbonBurned - Calc Fuel Carbon Burned) > Tolerance)
return result B.

Results:

Result	Response	Severity

A	The [fieldname] reported in the Daily Fuel record for [key] is missing or invalid. The	Critical Error Level 1

value must be greater than 0.

B	The [fieldname] in the Daily Fuel record for [key] is inconsistent with the recalculated	Critical Error Level 1

value.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions Fuel

Environmental Protection Agency

Page 108 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-12

Check Name:

Intialize Daily Emissions

Related Former Checks:

Applicability:

Description:

Specifications:

Set Calc Total Carbon Burned to 0.

Daily Op Time Accumulator Array for the location = 0.

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report — C02 Daily Emissions Initialization

Environmental Protection Agency

Page 109 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

DAILY-13

Check Name:

Check Total Carbon Burned

Related Former Checks:

Applicability:

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

Set Calculate C02M TDE to true.

if (Current C02 Mass Daily ifecorrf.TotalCarbonBurned is null)
if (Calc Total Carbon Burned is not equal to 0)
return result A.

else if (Current C02 Mass Daily itecortf.TotalCarbonBurned is less than 0)
return result B.

if (Calc Total Carbon Burned is greater than 0 AND Current C02 Mass Daily ifecorrf.TotalCarbonBurned o Calc Total Carbon
Burned)

Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "CARBON" AND
UOM = "LB"

if (ABS(Current C02 Mass Daily ifecorrf.TotalCarbonBurned - Calc Total Carbon Burned) > Tolerance)
return result C.

else if (Calc Total Carbon Burned == 0 )

Set Calc Total Carbon Burned to Current C02 Mass Daily ifecorrf.TotalCarbonBurned.

else

Results:

Result
A

Response

You did not report TotalCarbonBurned in the Daily Emission record for C02M. You
must report this value if you report Daily Fuel records.

The [fieldname] reported in the Daily Emissions record for [param] is invalid. The
value must be greater than or equal to 0.

The [fieldname] reported in the Daily Emissions record for [param] is inconsistent with
the recalculated value.

Severity

Critical Error Level 1

B

Critical Error Level 1

C

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Daily Emissions

Environmental Protection Agency

Page 110 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Daily Interference Status

Environmental Protection Agency

Page 111 of667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

INTSTAT-1

Check Name:

Determine the Online Daily Interference Check

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set OnlineDailylntRecord = null
Set OfflineDailylntRecord = null.

Set DailylntStatusResult = null

Locate the latest record in DailylntCheckRecordsByLocationForQAStatus for the location:

a)	Date/Hour is on or prior to the Current MHVRecord. Date/Hour

b)	ComponentID is equal to the Current MHVitecortf.ComponentID AND

c)	TestResultCd is not equal to "IGNORED" //Ignored indicates an offline test

if (DailylntCheckRecordsByLocationForQAStatus is found)

Set OnlineDailylntRecord = the found record in DailyIntCheckRecordsByLocationForQAStatus.

If (OnlineDailylntRecord.TestResultCd = "PASSED")

If (the number of clock hours between the OnlineDaily fnt Record.].nd\y<\lc I lour and the CurrentMHVRecord.Date/Hour is
less than 26)

Set DailylntStatusResult = "IC"

else if (OnlineDailylntRecord.TesiRssultCd = "FAILED")

Set DailylntStatusResult = "OOC-Test Failed"

else if (OnlineDailylntRecord.TestResultCd = "ABORTED")

Set DailylntStatusResult = "OOC-Test Aborted"

Set DailylntStatusResult = "OOC-Test Has Critical Errors"

If (DailylntStatusResult is not equal to "IC")

Locate the latest record in DailylntCheckRecordsByLocationForQAStatus for the location where:

a)	Date/Hour is on or prior to the Current Mill' Record. I )atc I lour

b)	Date/Hour/Min is after the OnlineDailylntRecord.EndDate/YLour/Min

c)	The ComponentID is equal to the Current MHVRecord.ComponentID AND

d)	TestResultCd is equal to "IGNORED"

if (DailylntCheckRecordsByLocationForQAStatus is found

else

Set OfflineDailylntRecord = the found record in DailylntCheckRecordsByLocationForQAStatus.

If (DailylntStatusResult is not null)

Set DailylntStatusResult = DailylntStatusResult & "*

Results:

Result

Response

Severity

Environmental Protection Agency

Page 112 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Interference Check Status Evaluation

Environmental Protection Agency

Page 113 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

INTSTAT-2

Check Name:

Determine Daily Interference Status for No Prior Check

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (DailylntStalusResuti is null) and (OnlineDailylntRecord is null)

// Determine whether check in previous quarter is possibly effective for current hour.

If (the number of clock hours between the First Day of Operation/First Hour of Operation and the Current Mil]'Record.\)dlc I lour
is less than 25)

// If a non operating hour exists within the first 24 hours after the first operating hour in the quarter, a grace period exists
for seven hours after the operating hour subsequent to the non operating hour.

Locate the latest record in HourlyOpData where:

a)	Date/Hour is ON OR PRIOR to the 24th clock hour following the First Day of Operation/First Hour of Operation

b)	OpTime is equal to zero.

if (HourlyOpData is found)

Locate the first record in HourlyOpData where:

a)	Date/Hour is after the Date/Hour in the HourlyOpData record found above

b)	Date/Hour is ON OR PRIOR to the CurentMHVRecord.Date/Hour

c)	OpTime is greater than zero.

if (HourlyOpData is found) and (the number of clock hours starting at HourlyOpDataDatefHour and up to the
hour before CurrentMII]'Record.I lour is greater than 7)

Set DailylntStatusResult = "OOC-No Prior Test".

else

Set DailylntStatusResult = "IC-Undetermined".

If (DailylntStatusResult begins with "OOC")

Locate the record in DailylntCheckRecordsByLocationForQAStatus for the location where:

a)	Date/Hour is on or prior to the Current Mil]' Record. I )atc I lour

b)	the ComponentID is equal to the Current MHVRecord.ComponentID AND

c)	TestResultCd is equal to "IGNORED"

if (DailylntCheckRecordsByLocationForQAStatus is found)

Set DailylntStatusResult = "IC-Undetermined".

else

else

Set DailylntStatusResult = "OOC-No Prior Test".

Set OfflineDailylntRecord = the found record in DailylntCheckRecordsByLocationForQAStatus.
Set DailylntStatusResult = DailylntStatusResult &

Environmental Protection Agency

Page 114 of 667


-------
Draft ECMPS Emissions Check Specifications

Results:

Result	Response

Usage:

1	Process/Category:	Emissions Data Evaluation Report

9/17/2014 12:00:00AM

Severity

Daily Interference Check Status Evaluation

Environmental Protection Agency

Page 115 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

INTSTAT-3

Check Name:

Determine Expiration Status for Prior Daily Interference Check

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (DailylntStalusResuti is null)

// If a non operating hour exists within the first 27 hours after the hour of the online Daily Interference Check, a grace period exists
for seven hours after the operating hour subsequent to the non operating hour.

Locate the latest record in HourlyOpData where:

a)	DateHour is after the OnlmeI)ailyCalRecord.\)dlc I lour.

b)	Date/Hour is ON OR PRIOR to the 27th hour after the OnlineDailyCalRecord.DaXefHom.

c)	OpTime is equal to zero.

if (HourlyOpData is found)

Locate the earliest record in HourlyOpData where:

a)	Date/Hour is after the Date/Hour in the HourlyOpData record found above.

b)	Date/Hour is on or before the CurrentMHVRecord.Date/Hour

c)	OpTime is greater than zero.

if (HourlyOpData is found) and (the number of clock hours starting at HourlyOpData.DatefHour and up to the hour before
CurrentMHVRecord.Date/Hour is greater than 7)

else

Set DailyIntStatusResult = "OOC-Expired".

If {DailyIntStatusResult begins with "OOC" and OfflineDailylntRecord is not null)
Set DailylntStatusResult = DailylntStatusResult & "

Return DailylntStatusResult

Set DailylntStatusResult = "OOC-Expired".

else

Set DailylntStatusResult = "IC-Grace".

else

Return DailylntStatusResult

Environmental Protection Agency

Page 116 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

OOC-Expired
OOC-Expired*

OOC-No Prior
Test

OOC-No Prior
Test*

OOC-Test
Aborted
OOC-Test
Aborted*

OOC-Test Failed

OOC-Test

Failed*

OOC-Test Ftas
Critical Errors
OOC-Test Ftas
Critical Errors*

Response

The prior daily interference check for [compkey] completed on [date] expired.

The prior daily interference check for [compkey] completed on [date] expired. A daily
interference check completed on [invdate] was ignored because it was completed while
the unit was offline.

You did not report a prior daily interference check for [compkey] during the reporting
period. Any daily interference check that may have been completed in a prior reporting
period has expired.

You did not report a prior daily interference check for [compkey] during the reporting
period. Any daily interference check that may have been completed in a prior reporting
period has expired. A daily interference check completed on [invdate] was ignored
because it was completed while the unit was offline.

The prior daily interference check for [compkey] completed on [date] was aborted.

The prior daily interference check for [compkey] completed on [date] was aborted. An
daily interference check completed on [invdate] was ignored because it was performed
while the unit was offline.

The prior daily interference check for [compkey] completed on [date] failed.

The prior daily interference check for [compkey] completed on [date] failed. An daily
interference check completed on [invdate] was ignored because it was performed while
the unit was offline.

The prior daily interference check for [compkey] completed on [date] has critical errors.

The prior daily interference check for [compkey] completed on [date] has critical errors.
An daily interference check completed on [invdate] was ignored because it was
performed while the unit was offline.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Daily Interference Check Status Evaluation

Environmental Protection Agency

Page 117 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Daily Test

Environmental Protection Agency

Page 118 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks
Applicability:

Description:

Specifications:

For the daily emission test:

Set EM Test Date Valid to true.

If Date is null,

set EM Test Date Valid to false, and return result A.

IfDate is before 01/01/1993 or after the end of the Current Reporting Period,
set EM Test Date Valid to false, and return result B.

EMTEST-1

Daily Test Date Valid

CEM Check

Results:

Result

A

B

Usage:

1

Response

You did not provide [fieldname], which is required for [key].

You reported a [Fieldname] of [Date], which is outside the range of acceptable values
for this date for [key].

Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Process/Category:	Emissions Data Evaluation Report	Miscellaneous Emission File Test

Severity
Fatal

Critical Error Level 1

Environmental Protection Agency

Page 119 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks
Applicability:

Description:

Specifications:

For the daily emission test:

Set EM Test Hour Valid to true.

If Hour is null,

Set EM Test Hour Valid to false, and return result A.

If Hour is not between 0 and 23,

Set EM Test Hour Valid to false, and return result B.

Results:

Severity
Fatal

Critical Error Level 1
Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

2	Process/Category:	Emissions Data Evaluation Report	Miscellaneous Emission File Test

EMTEST-2

Daily Test Hour Valid

CEM Check

Result	Response

A	You did not provide [fieldname], which is required for [key],

B	You reported a [Fieldname] of [Hour], which is outside the range of acceptable values

for this hour for [key].

Environmental Protection Agency

Page 120 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks
Applicability:

Description:

Specifications:

For the daily emission test:

Set EM Test Minute Valid to true.

If Minute is null,

If (Legacy Data Evaluation == false)

set EM Test Minute Valid to false, and return result A.

Otherwise,

return result B.

If Minute is not between 0 and 59,

set EM Test Minute Valid to false, and return result C.

EMTEST-3

Daily Test Minute Valid
CEM Check

Results:

Result

A

B

Usage:
1

Response

You did not provide [fieldname], which is required for [key].

You did not provide [fieldname] for [key]. This information will be required for

ECMPS submissions.

You reported a [Fieldname] of [Minute] for [key], which is outside the range of
acceptable values.

Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

Process/Category:	Emissions Data Evaluation Report	Miscellaneous Emission File Test

Severity
Fatal

Informational Message
Critical Error Level 1

Environmental Protection Agency

Page 121 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks
Applicability:

Description:

Specifications:

For the daily test:

If both the MonitoringSystemID and ComponentID are not null,

return result A.

If TestTypeCode is equal to "INTCHK",

If ComponentID is null,
return result B.

If the ComponentTypeCode of the associated component is not equal to "FLOW",
return result C.

If TestTypeCode is equal to "PEMSCAL",

If MonitoringSystemID is null,
return result D.

If the SystemTypeCode of the associated system is not equal to "NOXP",
return result E.

EMTEST-4

Daily Test System or Component Valid
General Check

Results:

Result	Response

A	You have reported both a MonitoringSystemID and a ComponentID for [key]. This is

invalid.

B	You did not provide [fieldname], which is required for [key],

C	The ComponentTypeCode for [key] is not appropriate for this type of test.

D	You did not provide a MonitoringSystemID for [key], which is required for this test

type.

E	The SystemTypeCode of the system for [key] is not appropriate for this type of test.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Daily Calibration Test

2	Process/Category:	Emissions Data Evaluation Report	Miscellaneous Emission File Test

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 122 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	EMTEST-5

Check Name:	Daily Test Span Scale Valid

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

For the daily test:

If the SpanScaleCode is not null,
return result A.

Results:

Result	Response	Severity

A	You reported [fieldname] for [key], which is not appropriate for this test type.	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Miscellaneous Emission File Test

Environmental Protection Agency

Page 123 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks
Applicability:

Description:

Specifications:

For the daily test:

Set EM Test Calc Result to null.

If TestResultCode is null,
return result A.

else if TestResultCode is not equal to "ABORTED", "PASSED", or "FAILED",
return result B.

else

Set EM Test Calc Result to TestResultCode.

if TestTypeCode is equal to "INTCHK" and EM Test Date Valid and EM Test Hour Valid and OpTime is equal to 0,

Set Ignored Daily Interference Tests to true.

Set EM Test Calc Result to "IGNORED".

EMTEST-6

Daily Test Result Code Valid
General Check

Results:

Result	Response Severity

A	You did not provide [fieldname], which is required for [key].	Critical Error Level 1

B	You reported the value [value], which is not in the list of valid values for this test type,	Critical Error Level 1

in the field [fieldname] for [key].

Usage:

1	Process/Category: Emissions Data Evaluation Report	Miscellaneous Emission File Test

Environmental Protection Agency

Page 124 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Flow-to-Load Status

Environmental Protection Agency

Page 125 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	F2LSTAT-1

Check Name:	Determine Most Recent Flow-to-Load QA Operating Quarter

Related Former Checks:

Applicability:

Description:

Specifications:

Set F2LStatusPriorTestRequiredQuarter = null.

Set F2LStalusPriorTestRequiredQuarterMissingOpData = null.

If F2LStatusSystemResuItDictionary does not contain lookup value for CurrentMhvRecord.SystemlD

Locate the most recent record in RataTestRecordsByLocationForQaStatus where the SystemID is equal to
CurrentMhvRecord.SystemlD, EndDateHour is before the CurrentReportingPeriod, and TestResultCode is not equal to
"INVALID"

If found,

For each quarter before CurrentReportingPeriod beginning with the quarter immediately before CurrentReportingPeriod
and going back to later of the quarter of the located RataTestRecordsByLocationForQaStatus and the quarter of the
Earliest Location Report Date

If AnnualReportingRequirement equals true, or the quarter being checked is 2 or 3

If AnnualReportingRequirement equals true, or the quarter being checked is 3

Locate the record in OperatingSuppDataRecordsByLocation where OpTypeCode is equal to
"OPHOURS", FuelCode is null, and reporting period equals the quarter being checked

Else

Locate the record in OperatingSuppDataRecordsByLocation where OpTypeCode is equal to
"OSHOURS", FuelCode is null, and reporting period equals the quarter being checked

If OperatingSuppDataRecordsByLocation record is found

If F2LStatusPriorTestRequiredQuarter does not equal -1

If OperatingSuppDataRecordsByLocation.OpVa\ue >= 168

Locate a record in F2LCheckRecordsForQaStatus where SystemID is equal to
CurrentMhvRecord.SystemlD, the quarter is equal to the quarter being checked,
and TestResultCode is equal to "EXC168H" or "FEW168H"

If not found

Set F2LStatusPriorTestRequiredQuarter. Year = The year value of the
quarter being checked.

Set F2LStatusPriorTestRequiredQuarter.Quarter = The quarter value of
the quarter being checked.

Exit the check.

Else

Set F2LStatusPriorTestRequiredQuarter = -1.

Append "[YEAR]Q[QTR]" to F2LStatusPriorTestRequiredQuarterMissingOpData (where
[YEAR] and [QTR are the year and number of the quarter being checked.

Environmental Protection Agency

Page 126 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Else

Set F2LStatusPriorTestRequiredQuarter = -1.

Set F2LStatusPriorTestRequiredQuarterMissingOpDala = "No Prior RATA"

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Flow-to-Load Status Evaluation

Environmental Protection Agency

Page 127 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	F2LSTAT-2

Check Name:	Locate Most Recent Flow-to-Load Check Prior to the Current Hour

Related Former Checks:

Applicability:

Description:

Specifications:

If F2LStatusSystemResuItDictionary contains lookup value for CurrentMhvRecord.SystemID

Set F2LStatusResuIt = F2LStatusSystemResuItDictionary lookup value for CurrentMhvRecord.SystemID.

Set CurrentFlowToLoadStalusCheck = F2LStatusSystemCheckDictionary lookup value for CurrentMhvRecord.SystemID.

Set F2LStatusMissingOpDataInfo = F2lStatusSystemMissingOpDictionary lookup value for CurrentMhvRecord.SystemID.

Else

Set F2LStatusResult = null.

Set CurrentFlowToLoadStalusCheck = null.

Set F2LStatusMissingOpDataInfo = null.

Locate the most recent record in F2LCheckRecordsForQaStatus where SystemID is equal to CurrentMhvRecord.SystemID,
EndDate < CurrentReportingl'eriodlieginDateffour, and TestResultCode is equal to "PASSED" or "FAILED"

If not found

Locate a record in MpLocationNonLoadBasedRecords where the location is the location in CurrentMhvRecord.

If found, and NonLoadBaselnd equals 1

Set F2LStatusResult = "IC-Exempt".

Else

Locate a record in TestExtensionExemptionRecords where the SystemID is equal to the

CurrentMhvRecord.SystemID, the ExtensionExemptionCode is equal to "F2LEXP", and the reporting period is the
period before the current reporting period.

If found

Set F2LStatusResult = "IC-Exempt".

Else

Locate the most recent record in RataTestRecordsByLocationForQaStatus where the SystemID is equal to
CurrentMhvRecord.SystemID, EndDate < CurrentReportingPeriodBeginDateHour, and TestResultCode
is not equal to "INVALID"

If not found

Set F2LStatusResult = "IC-No Prior RATA".

Else if F2LStatusPriorTestRequiredQuarter is equal to -1

Set F2LStatusResult = "Missing Op Data".

Set F2LStatusMissingOpDataInfo = F2LStatusPriotTestRequiredQuarterMissingOpData.

Else if F2LStatusPriorTestRequiredQuarter is null or before the quarter of the located
RataTestRecordsByLocationForQaStatus record

Environmental Protection Agency

Page 128 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set F2LStatusResuIt = "IC".

Else if the quarter of the located RataTestRecordsByLocationForQaStatus record is the quarter before
CurrentReportingPeriod, the TestReasonCode equals "INITIAL" or "RECERT" and TestResultCode
equals "PASSED"

Set F2LStatusResuIt = "IC".

Else if CurrentMhvRecord.SystemDesignationCode is equal to "RB"

Set F2LStatusResuIt = "Undetermined-No Prior Check reported for Redundant Backup Monitor".

Else

Set F2LStatusResuIt = "OOC-Prior Check Missing".

Else

Set CurrentFlowToLoadStalusCheck = the located F2LCheckRecordsForQaStatus record.

If the quarter of CurrentFlowToLoadStatusCheck is not the quarter before CurrentReportingPeriod

If F2LStatusPriorTestRequiredQuarter is equal to -1
Set F2LStatusResult = "Missing Op Data".

Set F2LStatusMissingOpDataInfo = F2LStatusPriotTestRequiredQuarterMissingOpData.

Else if F2LStatusPriorTestRequiredQuarter is not null, and is after the quarter of
CurrentFlowToLoadStatusCheck

if CurrentMhvRecord.SystemDesignationCode is equal to "RB"

Set F2LStatusResuti = "Undetermined-No Prior Check reported for Redundant Backup Monitor".

Else

Set F2LStatusSystemResuItDictionary lookup value for CurrentMhvRecord.SystemID = F2LStatusResult.

Set F2LStatusSystemCheckDictionary lookup value for CurrentMhvRecord. SystemID = CurrentFlowToLoadStatusCheck.

Set F2lStatusSystemMissingOpDictionary lookup value for CurrentMhvRecord.SystemID = F2LStatusMissingOpDataInfo.

Set F2LStatusResult = "OOC-Prior Check Missing".

Else if CurrentFlowToLoadStatusCheck.IestResuitCode = "PASSED'

Set F2LStatusResult = "IC".

Else

If CurrentFlowToLoadStatusCheck. TestResultCode = "PASSED'

Set F2LStatusResult = "IC".

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report

Flow-to-Load Status Evaluation

Environmental Protection Agency

Page 129 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

F2LSTAT-3

Check Name:

Locate Intervening RATA

Related Former Checks:

Applicability:

Description:

Specifications:

Set F2LStalusInterveningRala = null.

If F2LStatusResult is null

Locate the most recent record in RataTestRecordsByLocationForQaStatus where the SystemID is equal to
CurrentMhvRecord.SystemID, EndDateHour is after CurrentFlowToLoadStalusCheck.EndDateHour and before
CurrentMhvRecord.BeginDatefBeginHour, and TestResultCode is not equal to "INVALID"

If found,

Set F2LStatusResuIt = "IC-Subsequent RATA Performed".

Set F2LStatusInterveningRata = The located record in RataTestRecordsByLocationForQaStatus.

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report

Flow-to-Load Status Evaluation

Environmental Protection Agency

Page 130 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	F2LSTAT-4

Check Name:	Locate Most Recent QA Cert Event

Related Former Checks:

Applicability:

Description:

Validation Tables:

[Test Type to Required Test Code] (Cross Check Table)

Specifications:

Set F2LStalusQaCertEvent = null.

Set F2L Status Event Requires RATA = false.

Set F2L Status Event Requires Abbreviated Check = false.

If F2LStatusResult is null

Locate the most recent record in QACertificationEventRecords where the SystemID is equal to CurrentMhvRecord.SystemID,
QaCertEventCode is equal to "312", QaCertEventDateHour is on or after CurrentFlowToLoadStatusCheckEndDaXeHom, and
QaCertEventDateHour is on or before CurrentMhvRecord.BeginDate/BegmHour.

If found,

Set F2LStatusQaCertEvent = The located record in QACertificationEventRecords.

Locate a record in Cross-Check Table "Test Type to Required Test Code" where TestTypeCode begins with "RATA" and
RequireTestCode equals F2LStatusQaCertEvent.RequiredTestCode.

If found,

F2L Status Event Requires RATA = true.

Locate a record in Cross-Check Table "Test Type to Required Test Code" where TestTypeCode is equal to "AF2LCHK"
and RequireTestCode equals F2LStatusQaCertEvent.KequiredIestCode.

If found,

F2L Status Event Requires Abbreviated Check = true.

If F2LStatusQaCertEvent.LastIestComp\etedDateHour is on or before Cur rentMhvRecard. I icgi n I )atc I icgi n I lour
If F2L Status Event Requires Abbreviated Check is equal to true,

Set F2LStatusResult = "IC-Subsequent Abbreviated Flow-to-Load Check Passed".

If F2LStatusResult is null,

If F2LStatusQaCertEvent = null, or F2LStatusQaCertEvent.Conditiona\DataBegmDateIIour is after
CurrentMhvRecordMegi nDatc I icgi nl lour.

Locate records in RataTestRecordsByLocationForQaStatus where the SystemID is null or is equal to
CurrentMhvRecord.SystemID, EndDateHour is after Current Flow ToLoadStatusCli eck. H n d Da tc Ho ur and before
CurrentMhvRecord.BegmDatefBegmHour, and TestResultCode is equal to "INVALID".

If found

Set F2LStatusResult = "OOC-Check Failed - Invalid RATA Ignored".

Environmental Protection Agency

Page 131 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Else

Set F2LStatusResu.lt = "OOC-Check Failed".

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Flow-to-Load Status Evaluation

Environmental Protection Agency

Page 132 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

F2LSTAT-5

Check Name:

Locate Earliest Valid Required Test

Related Former Checks:

Applicability:

Description:

Specifications:

Set F2lStatusEarliestValidRequiredTest = null.

If F2LStatusResult is null

If F2L Status Event Requires RATA is true,

Locate earliest record in RataTestRecordsByLocationForQaStatus where the SystemID is equal to
CurrentMhvRecord.SystemID, EndDateHour is after CurrentMlivRecordMeginDatc Iicginl lour, and TestResultCode is
not equal to "INVALID".

If found,

Set F2LStatusEarliestValidRequiredTest = The located record in RataTestRecordsByLocationForQaStatus .
If F2LStatusEarliestValidRequiredTest .TestResultCode is equal to "FAILED"

Locate records in RataTestRecordsByLocationForQaStatus where the SystemID is equal to
CurrentMhvRecord.SystemID, EndDateHour is after F2LStatusQaCertEvent.QaCertEventDateHour and
before F2LStatusEarIiestVaIidRequiredTest.EndDateHour, and TestResultCode is equal to "INVALID".

If found

Set F2LStatusResult = "OOC-Recertification RATA Failed - Invalid RATA Ignored".

Else

Set F2LStatusResult = "OOC-Recertification RATA Failed".

Else if F2L Status Event Requires Abbreviated Check is false,

Set F2LStatusResult = "OOC-Invalid Cert Event".

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report

Flow-to-Load Status Evaluation

Environmental Protection Agency

Page 133 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

F2LSTAT-6

Check Name:

Determine Event Conditional Status and Final Status

Related Former Checks:

Applicability:

Description:

Specifications:

If F2LStatusResult is null

Set F2L Status Missing Op Data Info = null.

If F2L Status Event Requires RATA is true,

If (the quarter of the F2LStatusQaCertEvent.ConditionalBeginDate is equal to the quarter of the CurrentMliv Record.\)dlc I lour)

Count the number of HourlyOpData records for the location where OpTime is greater than 0 and Date/Hour is ON OR
AFTER the F2LStalusQa.CertEvent.Con&i{ionaS*,e%mDaXel}lom and ON OR BEFORE Cur rentMhv Record.I lour,

If the number > OperatingHourLimit,

Set F2LStatusResult = "OOC-Conditional Period Expired".

else

Set F2LStatusResuIt = "IC-Conditional".

if {F2LStatusQaCertEvent.MinOpHoursPriorQuarter is null)

Set F2LStatusQaCertEvent. MinOpHoursPriorQuarter = 0
Set F2LStatusQaCertEvent.MaxOpYLoursPnorQuarter = 0

for each quarter beginning with the quarter of the F2LStatusQaCertEvent.ConditionalBeginDate and continuing
through the quarter BEFORE the Current.\/livRecord.\)dlc I lour:

if (EarliestLocationReportDate <= the last day of the quarter being checked)

if (Annual Reporting Requirement == false AND the quarter being checked == 2)

Set OperatingHourLimit - 720

else

Set OperatingHourLimit - 168

else

Locate the record in OperatingSuppDataRecordsbyLocation where the OpTypeCode is
equal to "OSHOURS" and the reporting period is equal to the quarter being checked.

else

Locate the record in OperatingSuppDataRecordsbyLocation where the OpTypeCode is
equal to "OPHOURS", FuelCode is null, and the reporting period is equal to the quarter
being checked.

if (OperatingSuppDataRecordsbyLocation is not found)

Environmental Protection Agency

Page 134 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set F2LStalusQaCertEvent. MinOpHoursPriorQuarter = -1

Append "[YEAR] Q[QTR]" to F2L Status Missing Op Data Info (where [YEAR] is the
year of the quarter being checked and [QTR] is the number of the quarter being checked.)
exit for.

else

If the quarter being checked is the quarter of the
F2LStatusOaCertEvent.Condili onal I icgi n I )atc

If {OperatingSuppDataRecordsbyLocation.OpValue MINUS the number of
calendar hours in the quarter being checked that are PRIOR to the
F2LStatusQaCertEvent.ConditionalBeginDate/Hour > 0)

Set F2LStatusQaCertEvent. MinOpHoursPriorQuarter =
OperatingSuppDataRecordsby Location. OpValue MINUS the number of
calendar hours in the quarter being checked that are PRIOR to the
F2LStatusQaCertEvent. ConditionalBeginDate/Hour

If {OperatingSuppDataRecordsbyLocation.OpValue is less than the number of
calendar hours in the quarter begin checked that are ON OR AFTER the
F2LStatusQaCertEvent. ConditionalBeginDate/Hour)

Set F2LStatusQaCertEvent.MaxOpRoursPriorQuarter =
OperatingSuppDataRecordsby Location OpValue.

else

Set F2LStatusQaCertEvent.MaxOpRoursPriorQuarter = the number of
calendar hours in the quarter being checked that are ON OR AFTER the
F2LStatusQaCertEvent. ConditionalBeginDate/Hour.

else

Set F2LStatusQaCertEvent. MinOpHoursPriorQuarter =

F2LStatusQaCertEvent. MinOpHoursPriorQuarter +
OperatingSuppDataRecordsbyLocation. Op Val ue.

Set F2LStatusQaCertEvent.MaxOpHours PriorQuarter =

F2LStatusQaCertEvent. MaxOpHoursPriorQuarter +
OperatingSuppDataRecordsbyLocation. Op Val ue.

If (F2LStatusQaCertEventMinOpRoursPr\orQuarter == -1)

set F2LStatusResult to "Missing Op Data"

Else if (F2LStatusQaCertEvent.MinOpRoursPriorQuarter > OperatingHourLimit)

If F2L Status Event Requires RATA is true,

Locate records in RataTestRecordsByLocationForQaStatus where the SystemID is equal to
CurrentMhvRecord.SystemID, EndDateHour is on or after

F2L5tato2aCert£Ven?.ConditionalDataBeginDate/ConditionalDataBeginHour and on or before
CurrentMhvRecord.BeginDatefBeginHour, and TestResultCode is equal to "INVALID".

If found,

Set F2LStatusResult = "OOC-Conditional Period Expired-Invalid RATA Ignored".

Environmental Protection Agency

Page 135 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Else

Set F2LStatusResuIt = "OOC-Conditional Period Expired".

Else

Set F2LStatusResuIt = "OOC-Conditional Period Expired".

Else if (Rpt Period Op Hours Accumulator Array for the location == -1)

Set F2LStatusResuIt = "Invalid Op Data".

Else if {F2LStatusQaCertEvent.MinOpHoursPriorQuarter + Rpt Period Op Hours Accumulator Array for the Location >
OperatingHourLimit)

If F2L Status Event Requires RATA is true,

Locate records in RataTestRecordsByLocationForQaStatus where the SystemID is equal to
CurrentMhvRecord.SystemID, EndDateHour is on or after

F2L5tato2aCert£Ven?.ConditionalDataBeginDate/ConditionalDataBeginHour and on or before
CurrentMhvRecord.BeginDatefBeginHour, and TestResultCode is equal to "INVALID".

If found,

Else

Set F2LStatusResult = "OOC-Conditional Period Expired".

Else if (F2LStatusQaCertEvent.MaxOpHoursPriorQuarter + Rpt Period Op Hours Accumulator Array for the Location >
OperatingHourLimit)

Set F2LStatusResult = "Undetermined-Conditional Data".

Set F2LStatusResult = "OOC-Conditional Period Expired-Invalid RATA Ignored".

Else

Set F2LStatusResult = "OOC-Conditional Period Expired".

Else

Set F2LStatusResult = "IC-Conditional".

If (FlowToLoadStatusResult does not begin with "IC")

Return result F2LStatusResult.

Environmental Protection Agency

Page 136 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Invalid Op Data
Missing Op Data

OOC-Check
Failed - Invalid
RATA Ignored
OOC-Conditional
Period Expired
OOC-Conditional
Period

Expired-Invalid
RATA Ignored
OOC-Invalid Cert
Event

OOC-Prior Check
Missing

OOC-Recertificat
ion RATA Failed
OOC-Recertificat
ion RATA Failed
- Invalid RATA
Ignored

Undetermined-Co
nditional Data

Undetermined-No
Prior Check
reported for
Redundant
Backup Monitor

Response

The Flow-to-Load status for [SYSID] could not be determined, because the
OperatingTime in at least one Hourly Operating Data records was missing or invalid.
The Flow-to-Load status for [SYSID] could not be determined, because the Op Supp
Data record for OPHOURS, OSHOURS, or OPDAYS is missing for one or more
previous reporting periods. If you have submitted emissions data for prior quarters, you
should be able to synchronize these records to your Client Tool by logging on to the
EPA host.

The prior Flow-to-Load Check for SystemID [SYSID] has failed, a subsequent invalid
RATA with was ignored.

The conditional data period for QACertEventCode [code] QACertEventDate [eventdate]
for [SYSID] has expired.

The conditional data period for QACertEventCode [code] QACertEventDate [eventdate]
for SystemID [EVENTKEY] has expired. An invalid RATA was ignored.

You reported an invalid QA Certification Event record for QACertEventCode [code]

QACertEventDate [eventdate] for [SYSID],

One or more Flow-to-Load Checks is missing for prior quarters.

The subsequent recertification RATA for SystemID [SYSID] with TestNumber
[subtestnum] failed.

The subsequent recertification RATA for SystemID [SYSID] with TestNumber
[subtestnum] failed. An invalid RATA was ignored.

The software could not determine if the current hour was within the conditional data
period for QACertEventCode [code] QACertEventDate [eventdate] for SystemID
[eventkey].

The software could not determine if a Flow-to-Load check is required for the Redundant
Backup Flow Monitor.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Informational Message
Informational Message

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Flow-to-Load Status Evaluation

Environmental Protection Agency

Page 137 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Hourly Aggregation

Environmental Protection Agency

Page 138 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-1

Check Name:	Determine Start Quarter

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

Set Start Quarter to null.

Set S02 Start Quarter to null.

Set XO.XR Start Quarter to null.

Set CO2 Start Quarter to null.

Set Heat Input Start Quarter to null.

Set XO.XStart Quarter to null.

Set Emissions Tolerance Deviators to null.

If (Quarter of the Current Reporting Period is greater than 1)

Locate the earliest Monitor Method for location where BeginDate is on or before the last day of the Current Reporting Period, and
EndDate is null or is on or after Jan 1 of the year of the Current Reporting Period.

If found,

If BeginDate is in a year prior to the current reporting period,

If (Annual Reporting Requirement == true)

Set Start Quarter to 1.

else

Set Start Quarter to 2.

else

Set Start Quarter to the quarter of the BeginDate.

Locate the earliest Monitor Method for location where ParameterCode = "S02" or "S02M", BeginDate is on or before the last day
of the Current Reporting Period, and EndDate is null or is on or after Jan 1 of the year of the Current Reporting Period.

If found,

If BeginDate is in a year prior to the current reporting period,

Set S02 Start Quarter to 1.

else

Set S02 Start Quarter to the quarter of the BeginDate.

If (LME Annual == true)

Locate the earliest Monitor Method for location where ParameterCode = "NOXM", BeginDate is on or before the last day
of the Current Reporting Period, and EndDate is null or is on or after Jan 1 of the year of the Current Reporting Period.

else

if {Current Monitor Plan Location itecortf.LocationName begins with "MS" OR Multiple Stack Configuration == false)

Locate the earliest Monitor Method for location where ParameterCode = "NOXR", BeginDate is on or before the
last day of the Current Reporting Period, and EndDate is null or is on or after Jan 1 of the year of the Current
Reporting Period.

else

Locate the earliest Monitor Method for ALL locations in the monitor plan where ParameterCode = "NOXR",
BeginDate is on or before the last day of the Current Reporting Period, and EndDate is null or is on or after Jan 1
of the year of the Current Reporting Period.

If the NOXR or NOXM method record was found,

Locate the earliest Location Program Record for location where ProgramCode is equal to "ARP", the Class is not equal to

Environmental Protection Agency

Page 139 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

"NA", and UnitMonitorCertBeginDate is on or before the last day of the Current Reporting Period, and the EndDate is null
or is on or after Jan 1 of the year of the Current Reporting Period.

If found,

If the EmissionsRecordingBeginDate is null,

If the later of the method BeginDate and the UnitMonitorCertBeginDate is in a year prior to the current
reporting period,

Set NOXR Start Quarter to 1.

else

Set NOXR Start Quarter to the quarter of the later of the method BeginDate and
UnitMonitorCertBeginDate .

Otherwise,

If the later of the method BeginDate and the EmissionsRecordingBeginDate is in a year prior to the current
reporting period,

Set NOXR Start Quarter to 1.

else

Set NOXR Start Quarter to the quarter of the later of the method BeginDate and
EmissionsRecordingBeginDate .

Locate the earliest Monitor Method for location where ParameterCode = "C02" or "C02M", BeginDate is on or before the last day
of the Current Reporting Period, and EndDate is null or is on or after Jan 1 of the year of the Current Reporting Period

If found,

If BeginDate is in a year prior to the current reporting period,
Set CO2 Start Quarter to 1.

else

Set C02 Start Quarter to the quarter of the BeginDate.

If (the Quarter of the Current Reporting Period is greater than 2 OR (Annual Reporting Requirement == true AND the Quarter of the
Current Reporting Period is equal to 2))

Locate the earliest Monitor Method for location where ParameterCode = "HI" or "HIT", MethodCode is not equal to "EXP",
BeginDate is on or before the last day of the Current Reporting Period, and EndDate is null or is on or after Jan 1 of the year of the
Current Reporting Period.

If found,

If BeginDate is in a year prior to the Current Reporting Period,

If Annual Reporting Requirement == true
Set Heat Input Start Quarter to 1

else

Set Heat Input Start Quarter to 2

else if BeginDate is in Quarter 1 of the year of the Current Reporting Period AND Annual Reporting Requirement ==

false,

Set Heat Input Start Quarter to to 2

else

Set Heat Input Start Quarter to the quarter of the BeginDate.

Locate the earliest Monitor Method for location where ParameterCode is equal to "NOX" or "NOXM", BeginDate is on or before
the last day of the Current Reporting Period, and EndDate is null or is on or after Jan 1 of the year of the Current Reporting
Period.

If found,

If BeginDate is in a year prior to the Current Reporting Period,

If Annual Reporting Requirement == true

Environmental Protection Agency

Page 140 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set XO.X Start Quarter to 1

else

Set XO.X Start Quarter to 2

else ifBeginDate is in Quarter 1 of the year of the Current Reporting Period AND Annual Reporting Requirement ==

false,

Set XO.X Start Quarter to to 2

else

Set NOX Start Quarter to the quarter of the BeginDate.

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 141 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-2

Check Name:	Compare S02 Mass Accumulator Values

Related Former Checks:	HOURCV-22

Applicability:	General Check
Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

S02 Mass Quarterly Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "S02M" AND
UOM = "TON"

Current S02 Summary Value Record = Summary Value record at this location where

Parameter = "S02M" AND
Reporting Period ID = Current Reporting Period

if (Rpt Period S02 Mass Calculated Accumulator Array for this location == -1 OR Expected Summary Value S02 Array for this location
== false)

Rpt Period S02 Mass Calculated Value = null

else

Rpt Period S02 Mass Calculated Value = (Rpt Period S02 Mass Calculated Accumulator Array for this location / 2000, and
rounded to one decimal place).

if (Rpt Period S02 Mass Reported Accumulator Array for this location >= 0)

Rpt Period S02 Mass Reported Accumulator Array for this location = (Rpt Period S02 Mass Reported Accumulator Array for
this location/ 2000, and rounded to one decimal place).

if (Current S02 Summary Value Record is null OR Current S02 Summary Value Record.Current Reporting Period Total is null)
if (Expected Summary Value S02 Array for this location == true)
return result C

else

if (Expected Summary Value S02 Array for this location == false)

if (Rpt Period Op Hours Accumulator Array for this Location is not equal to 0 OR Current S02 Summary Value
Record.Current Reporting Period Total is not equal to 0)
return result D

else

S02 Mass Quarterly Reported Value = Current S02 Summary Value Record.Current Reporting Period Total

if (S02 Mass Quarterly Reported Value < 0)
return result F

else if (S02 Mass Quarterly Reported Value is not rounded to one decimal place)
return result G

else if (Rpt Period S02 Mass Calculated Value is not null)

If (Rpt Period S02 Mass Calculated Value o S02 Mass Quarterly Reported Value)

if (ABS(Rpt Period S02 Mass Calculated Value - S02 Mass Quarterly Reported Value) > S02 Mass
Quarterly Tolerance)

return Result A

else

append "S02M" to Emissions Tolerance Deviators.

else

Environmental Protection Agency

Page 142 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result E
11 if no result

if {Rpt Period S02 Mass Reported Accumulator Array for this location >= 0 AND ABS (Rpt Period S02 Mass Reported
Accumulator Array for this location - S02 Mass Quarterly Reported Value) > S02 Mass Quarterly Tolerance)

Reported Emissions Value = Rpt Period S02 Mass Reported Accumulator Array for this location
return result B

Results:

Result
A

B

C
D

E
F
G

Usage:

1

Response

The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
S02M for the reporting period is inconsistent with the recalculated value of [calcval].
The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
S02M is inconsistent with [sum], the sum of the hourly values reported in the DHV
records for the reporting period.

The CurrentReportingPeriodTotal in the Summary Value record for S02M is missing or
the record is missing.

You reported a value as the CurrentReportingPeriodTotal in the Summary Value record
for S02M, but there were no Hourly Operating Data records or appropriate S02
Methods defined in your monitoring plan.

The CurrentReportingPeriodTotal in the Summary Value record for [param] could not
be recalculated because of errors listed above.

The CurrentReportingPeriodTotal reported in the Summary Value record for [param] is
invalid. The value must be greater than or equal to 0.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 143 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-3

Check Name:	Compare C02 Mass Accumulator Values

Related Former Checks:	HOURCV-23

Applicability:	General Check
Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

If Current Reporting Period Year is greater than or equal to 2012

C02 Mass Quarterly Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "C02M" AND
UOM = "TON"

else

C02 Mass Quarterly Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "C02M-OLD" AND
UOM = "TON"

Current C02 Summary Value Record = Summary Value record at this location where

Parameter = "C02M" AND
Reporting Period ID = Current Reporting Period

if (Rpt Period C02 Mass Calculated Accumulator Array for this location < 0 OR Expected Summary Value C02 Array for this location
== false)

Rpt Period C02 Mass Calculated Value = null

else

Rpt Period C02 Mass Calculated Value = Rpt Period C02 Mass Calculated Accumulator Array for this location, rounded to one
decimal place.

if (Rpt Period C02 Mass Reported Accumulator Array for this location >= 0)

Rpt Period C02 Mass Reported Accumulator Array for this location = (Rpt Period C02 Mass Reported Accumulator Array for
this location, rounded to one decimal place).

if (Current C02 Summary Value Record is null OR Current C02 Summary Value Record.Current Reporting Period Total is null)
if (Expected Summary Value C02 Array for this location == true)
return result C

else

if (Expected Summary Value C02 Array for this location == false)

if (Rpt Period Op Hours Accumulator Array for this Location is not equal to 0 OR Current C02 Summary Value
Record.Current Reporting Period Total is not equal to 0)
return result D

else

C02 Mass Quarterly Reported Value = Current C02 Summary Value Record.Current Reporting Period Total

if (C02 Mass Quarterly Reported Value < 0)
return result F

else if (C02 Mass Quarterly Reported Value is not rounded to one decimal place)
return result G

else if (Rpt Period C02 Mass Calculated Value is not null)

if (Rpt Period C02 Mass Calculated Value o C02 Mass Quarterly Reported Value)

if (ABS(Rpt Period C02 Mass Calculated Value - C02 Mass Quarterly Reported Value) > C02 Mass
Quarterly Tolerance)

return Result A

else

Environmental Protection Agency

Page 144 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

append "C02M" to Emissions Tolerance Deviators.

else

if (Rpt Period C02 Mass Calculated Accumulator Array for this location == -1)
return result E

11 if no result

if (Rpt Period C02 Mass Reported Accumulator Array for this location >= 0 AND ABS (Rpt Period C02 Mass Reported
Accumulator Array for this location - C02 Mass Quarterly Reported Value) > C02 Mass Quarterly Tolerance)

Reported Emissions Value = Rpt Period C02 Mass Reported Accumulator Array for this location
return Result B

Results:

Result
A

B

C
D

E
F
G

Usage:

1

Response

The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
C02M for the reporting period is inconsistent with the recalculated value of [calcval].
The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
C02M is inconsistent with [sum], the sum of the hourly values reported in the DHV
records for the reporting period.

The CurrentReportingPeriodTotal in the Summary Value record for C02M is missing or
the record is missing.

You reported a value for the CurrentReportingPeriodTotal in the Summary Value record
for [param], but there was no emissions data in your file or an appropriate C02 Method
defined in your monitoring plan.

The CurrentReportingPeriodTotal in the Summary Value record for [param] could not
be recalculated because of errors listed above.

The CurrentReportingPeriodTotal reported in the Summary Value record for [param] is
invalid. The value must be greater than or equal to 0.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 145 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-4

Check Name:	Compare HI Accumulator Values

Related Former Checks:	HOURCV-24

Applicability:	General Check

Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

HI Quarterly Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "HIT" AND
UOM = "MMBTU"

Current HI Summary Value Record = Summary Value record at this location where

Parameter = "HIT" AND
Reporting Period ID = Current Reporting Period

if {Rpt Period HI Calculated Accumulator Array for this location == -1 OR Expected Summary Value HI Array for this location == false)
Rpt Period HI Calculated Value = null

else

Rpt Period HI Calculated Value = Rpt Period HI Calculated Accumulator Array for this location, rounded to zero decimal places.

if {Rpt Period HI Reported Accumulator Array for this location >= 0)

Rpt Period HI Reported Accumulator Array for this location = {Rpt Period HI Reported Accumulator Array for this location,
rounded to zero decimal places).

if {Current HI Summary Value Record is null OR Current HI Summary Value Record.Current Reporting Period Total is null)
if {Expected Summary Value HI Array for this location == true)
return result C

else

if {Expected Summary Value HI Array for this location == false)

if {Rpt Period Op Hours Accumulator Array for this Location is not equal to 0 OR Current HI Summary Value
Record.Current Reporting Period Total is not equal to 0)
return result D

else

HI Quarterly Reported Value = Current HI Summary Value Record.Current Reporting Period Total

if (HI Quarterly Reported Value < 0)
return result F

else if (HI Quarterly Reported Value is not rounded to zero decimal places)
return result G

else if {Rpt Period HI Calculated Value is not null)

if {Rpt Period HI Calculated Value <> HI Quarterly Reported Value)

if (ABS{Rpt Period HI Calculated Value - HI Quarterly Reported Value) > HI Quarterly Tolerance)
return result A

else

append "HIT" to Emissions Tolerance Deviators.

else

return result E
11 if no result

if {Rpt Period HI Reported Accumulator Array for this location >= 0 AND ABS {Rpt Period HI Reported Accumulator
Array for this location (rounded to zero decimal places) - HI Quarterly Reported Value) > HI Quarterly Tolerance)
Reported Emissions Value = Rpt Period HI Reported Accumulator Array for this location

Environmental Protection Agency

Page 146 of 667


-------
Draft ECMPS Emissions Check Specifications

return Result B

9/17/2014 12:00:00AM

Results:

Result
A

B

C
D

E
F
G

Usage:

1

Response

The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
HIT for the reporting period is inconsistent with the recalculated value of [calcval].
The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
HIT is inconsistent with [sum], the sum of the hourly values reported in the DHV
records for the reporting period.

The CurrentReportingPeriodTotal in the Summary Value record for HIT is missing or
the record is missing.

You reported a value as the CurrentReportingPeriodTotal in the Summary Value record
for HIT, but there were no Hourly Operating Data records or appropriate HI Methods
defined in your monitoring plan.

The CurrentReportingPeriodTotal in the Summary Value record for [param] could not
be recalculated because of errors listed above.

The CurrentReportingPeriodTotal reported in the Summary Value record for [param] is
invalid. The value must be greater than or equal to 0.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 147 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-5

Check Name:	Compare Op Hours Values

Related Former Checks:	HOURCV-25

Applicability:	General Check
Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

Op Hours Quarterly Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "OPHOURS" AND
UOM = "HR"

Current Op Hours Summary Value Record = Summary Value record at this location where

Parameter = "OPHOURS" AND
Reporting Period ID = Current Reporting Period

if (Rpt Period Op Hours Accumulator Array for this location == -1 OR (LME HI Method is not null and location is a common pipe))
Rpt Period Op Hours Calculated Value = null
Rpt Period Op Days Calculated Value = null

else

Rpt Period Op Hours Calculated Value = Rpt Period Op Hours Accumulator Array for this location
Rpt Period Op Days Calculated Value = Rpt Period Op Days Accumulator Array for this location

if (Current Op Hours Summary Value Record is null OR Current Op Hours Summary Value Record.Current Reporting Period Total is
null)

If (LME HI Method is null or location is not a common pipe)
return result B

else

Op Hours Quarterly Reported Value = Current Op Hours Summary Value Record.Current Reporting Period Total

if (Op Hours Quarterly Reported Value < 0)
return result D

else if (Op Hours Quarterly Reported Value is not rounded to zero decimal places)
return result E

else if (Rpt Period Op Hours Calculated Value is not null)

if (Rpt Period Op Hours Calculated Value <> Op Hours Quarterly Reported Value)

if (ABS(Rpt Period Op Hours Calculated Value - Op Hours Quarterly Reported Value) > Op Hours Quarterly
Tolerance)

return Result A

else

append "OPHOURS" to Emissions Tolerance Deviators.

else

return result C

Environmental Protection Agency

Page 148 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B
C
D

E

Usage:
1

Response

The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
OPHOURS is inconsistent with [calcval], the number of operating hours reported in the
Hourly Operating Data records for the reporting period.

The CurrentReportingPeriodTotal in the Summary Value record for OPHOURS is
missing or the record is missing.

The CurrentReportingPeriodTotal in the Summary Value record for [param] could not
be recalculated because of errors listed above.

The CurrentReportingPeriodTotal reported in the Summary Value record for [param] is
invalid. The value must be greater than or equal to 0.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 149 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-6

Check Name:	Compare Op Time Values

Related Former Checks:	HOURCV-26

Applicability:	General Check
Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

Op Time Quarterly Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "OPTIME" AND
UOM = "HR"

Current Op Time Summary Value Record = Summary Value record at this location where

Parameter = "OPTIME" AND
Reporting Period ID = Current Reporting Period

if (Rpt Period Op Time Accumulator Array for this location == -1 OR (LME HI Method is not null and location is a common pipe))
Rpt Period Op Time Calculated Value = null

else

Rpt Period Op Time Calculated Value = Rpt Period Op Time Accumulator Array for this location

if (Current Op Time Summary Value Record is null OR Current Op Time Summary Value Record.Current Reporting Period Total is null)
If (LME HI Method is null or location is not a common pipe)
if (Legacy Data Evaluation == true)
return result B

else

return result E

else

Op Time Quarterly Reported Value = Current Op Time Summary Value Record.Current Reporting Period Total
if (Op Time Quarterly Reported Value >= 0)

if (Op Time Quarterly Reported Value is not rounded to two decimal places)
return result F

else

if (Rpt Period Op Time Calculated Value is not null)

if (Rpt Period Op Time Calculated Value <> Op Time Quarterly Reported Value)

if (ABS(Rpt Period Op Time Calculated Value - Op Time Quarterly Reported Value) > Op Time
Quarterly Tolerance)
return A

else

append "OPTIME" to Emissions Tolerance Deviators.

else

return result D

else

return result C

Environmental Protection Agency

Page 150 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B
C
D

E
F

Usage:
1

Response

The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
OPTIME is inconsistent with [calcval], the sum of the hourly values reported in the
Hourly Operating Data records for the reporting period.

You did not report a Summary Value record for OPTIME for the reporting period.

While this information was not required for legacy EDR data, it is required for ECMPS.
The CurrentReportingPeriodTotal reported in the Summary Value record for OPTIME
is invalid. The value must be greater than or equal to 0.

The CurrentReportingPeriodTotal in the Summary Value record for [param] could not
be recalculated because of errors listed above.

The CurrentReportingPeriodTotal in the Summary Value record for OPTIME is missing
or the record is missing.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1

Informational Message
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 151 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-7

Check Name:	Compare NOx Rate Accumulator Values

Related Former Checks:	HOURCV-27

Applicability:	General Check
Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

If (Expected Summary Value NOx Rate Array for this location == true)
if (LME Annual == true)

if (Rpt Period HI Calculated Value is not null and Rpt Period NOx Mass Calculated Value is not null)

If (Rpt Period NOx Mass Calculated Accumulator Array for this location = 0)

Rpt Period NOx Rate Calculated Value = 0

else

Rpt Period NOx Rate Calculated Value = Rpt Period NOx Mass Calculated Accumulator Array for this
location I Rpt Period HI Calculated Value, and round the result to three decimal places

else

Rpt Period NOx Rate Calculated Value = null

else

if (Rpt Period NOx Rate Hours Accumulator Array for this location > 0 AND Rpt Period NOx Rate Calculated
Accumulator Array for this location >= 0)

Rpt Period NOx Rate Calculated Value = Rpt Period NOx Rate Calculated Accumulator Array for this location /
Rpt Period NOx Rate Hours Accumulator Array for the location, and round the result to three decimal places
Rpt Period NOx Rate Sum = Rpt Period NOx Rate Calculated Accumulator Array for this location
Rpt Period NOx Rate Hours = Rpt Period NOx Rate Hours Accumulator Array for this location

else if (Rpt Period NOx Rate Hours Accumulator Array for this location == 0 AND Rpt Period NOx Rate Calculated
Accumulator Array for this location == 0)

Rpt Period NOx Rate Calculated Value = 0
Rpt Period NOx Rate Sum = 0
Rpt Period NOx Rate Hours = 0

else

Rpt Period NOx Rate Calculated Value = null
Rpt Period NOx Rate Sum = null
Rpt Period NOx Rate Hours = null

if (Rpt Period NOx Rate Hours Accumulator Array for this location > 0 AND Rpt Period NOx Rate Reported
Accumulator Array for this location >= 0)

Rpt Period NOx Rate Reported Accumulator Array for this location = Rpt Period NOx Rate Reported
Accumulator Array for this location I Rpt Period NOx Rate Hours Accumulator Array for this location, and
round the result to three decimal places

else

Rpt Period NOx Rate Reported Accumulator Array for this location = -1

else

Rpt Period NOx Rate Calculated Value = null

NOx Rate Quarterly Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "NOXR" AND
UOM = "LBMMBTU"

Current NOx Rate Summary Value Record = SummaryValue record at this location where

Parameter = "NOXR" AND
Reporting Period ID = Current Reporting Period

if (Current NOx Rate Summary Value Record is null OR Current NOx Rate Summary Value Record.Current Reporting Period Total is

Environmental Protection Agency

Page 152 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (Expected Summary Value NOx Rate Array for this location == true)
return result C

if (Expected Summary Value NOx Rate Array for this location == false)

if (Rpt Period NOx Rate Hours Accumulator Array for this Location is not equal to 0 OR Current NOx Rate Summary
Value Record.Current Reporting Period Total is not null)
return result D

else

NOx Rate Quarterly Reported Value = Current NOx Rate Summary Value Record.Current Reporting Period Total

If (NOx Rate Quarterly Reported Value < 0)
return result F

else if (Rpt Period NOx Rate Calculated Value is not null)

if (ABS(Rpt Period NOx Rate Calculated Value - NOx Rate Quarterly Reported Value) > NOx Rate Quarterly
Tolerance)

return result A

else

return result E
//if no result

if (LME Annual == false)

if (Current Monitor Plan Location itecortf.LocationName begins with "MS" OR Multiple Stack Configuration

== false)

if (Rpt Period NOx Rate Reported Accumulator Array for this location >= 0 AND ABS(Rpt Period NOx
Rate Reported Accumulator Array for this location - NOx Rate Quarterly Reported Value) > NOx Rate
Quarterly Tolerance)

Reported Emissions Value = Rpt Period NOx Rate Reported Accumulator Array for this location
return Result B

Results:

Result
A

B

C
D

E
F

Response

The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
NOXR for the reporting period is inconsistent with the recalculated value of [calcval].
The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
NOXR is inconsistent with [average], the average of the hourly values reported in the
DHV records for the reporting period.

The CurrentReportingPeriodTotal in the Summary Value record for NOXR is missing or
the record is missing.

You reported a value as the CurrentReportingPeriodTotal in the Summary Value record
for NOXR, but this is not appropriate, either because there were no Hourly Operating
Data records in your emissions file, or because this value is not consistent with the unit
program records and monitoring methodologies in your monitoring plan.
The CurrentReportingPeriodTotal in the Summary Value record for [param] could not
be recalculated because of errors listed above.

The CurrentReportingPeriodTotal reported in the Summary Value record for [param] is
invalid. The value must be greater than or equal to 0.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Environmental Protection Agency

Page 153 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 154 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-8

Check Name:	Compare NOx Mass Accumulator Values

Related Former Checks:

Applicability:	General Check

Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

NOx Mass Quarterly Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "NOXM" AND
UOM = "TON"

Current NOx Mass Summary Value Record = Summary Value record at this location where

Parameter = "NOXM" AND
Reporting Period ID = Current Reporting Period

if (Rpt Period NOx Mass Calculated Accumulator Array for this location == -1 OR Expected Summary Value NOx Mass Array for this
location == false)

Rpt Period NOx Mass Calculated Value = null

else

Rpt Period NOx Mass Calculated Value = Rpt Period NOx Mass Calculated Accumulator Array for this location / 2000, and
rounded to one decimal place).

if {Rpt Period NOx Mass Reported Accumulator Array for this location >= 0)

Rpt Period NOx Mass Reported Accumulator Array for this location = Rpt Period NOx Mass Reported Accumulator Array for
this location/ 2000, and rounded to one decimal place).

if (Current NOx Mass Summary Value Record is null OR Current NOx Mass Summary Value Record.Current Reporting Period Total is
null)

if (Expected Summary Value NOxMass Array for this location == true)
return result C

else

if (Expected Summary Value NOX Array for this location == false)

if (Rpt Period Op Hours Accumulator Array for this Location is not equal to 0 OR Current NOx Mass Summary Value
Record.Current Reporting Period Total is not equal to 0)
return result D

else

NOx Mass Quarterly Reported Value = Current NOx Mass Summary Value Record.Current Reporting Period Total

If (NOx Mass Quarterly Reported Value < 0)
return result F

else if (NOx Mass Quarterly Reported Value is not rounded to one decimal place)
return result G

else if (Rpt Period NOx Mass Calculated Value is not null)

if (Rpt Period NOx Mass Calculated Value <> NOx Mass Quarterly Reported Value)

if (ABS(Rpt Period NOx Mass Calculated Value - NOx Mass Quarterly Reported Value) > NOx Mass
Quarterly Tolerance)

return Result A

else

append "NOXM" to Emissions Tolerance Deviators.

else

return result E

Environmental Protection Agency

Page 155 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

11 if no result

If {Rpt Period NOx Mass Reported Accumulator Array for this location >= 0 AND ABS(Rpt Period NOx Mass Reported
Accumulator Array for this location - NOx Mass Quarterly Reported Value) > NOx Mass Quarterly Tolerance)

Reported Emissions Value = Rpt Period NOx Mass Reported Accumulator Array for this location
return Result B

Results:

Result
A

B

C
D

E
F
G

Usage:

1

Response

The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
NOXM for the reporting period is inconsistent with the recalculated value of [calcval].
The CurrentReportingPeriodTotal of [sumval] reported in the Summary Value record for
NOXM is inconsistent with [sum], the sum of the hourly values reported in the DHV
records for the reporting period.

The CurrentReportingPeriodTotal in the Summary Value record for NOXM is missing
or the record is missing.

You reported a value as the CurrentReportingPeriodTotal in the Summary Value record
for NOXM, but there were no Hourly Operating Data records or appropriate NOX
Methods defined in your monitoring plan.

The CurrentReportingPeriodTotal in the Summary Value record for [param] could not
be recalculated because of errors listed above.

The CurrentReportingPeriodTotal reported in the Summary Value record for [param] is
invalid. The value must be greater than or equal to 0.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 156 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAGG-10

Check Name:

Compare C02 Mass YTD Values

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Annual C02M Calculated Value = null

if (Rpt Period C02 Mass Calculated Value is not null OR Expected Summary Value C02 Array for this location == false)

if (Expected Summary Value C02 Array for this location == true)

If (Emissions Tolerance Deviators contains "C02M")

Annual C02M Calculated Value = Current C02 Summary Value Record.Current Reporting Period Total

else

Annual C02M Calculated Value = Rpt Period C02 Mass Calculated Value

else if (Quarter of the Current Reporting Period is greater than 1)

Annual C02M Calculated Value = 0

If (Quarter of the Current Reporting Period is greater than 1)

If (CO2 Start Quarter is not null)

For each quarter in the current year from the C02 Start Quarter to the quarter prior to the quarter of the Current
Reporting Period.

Locate an Op Supp Data record for the location and quarter where ParameterCode = "C02M".

If not found,

if (Expected Summary Value C02 Array for this location == true)
set Annual C02M Calculated Value to null
return result A

Otherwise,

add OpValue to Annual C02M Calculated Value.

else

set Annual C02M Calculated Value to null

if (Current C02 Summary Value Record is not null)

If (Annual C02M Calculated Value is null AND Expected Summary Value C02 Array for this location == false)
return result G

else if (Current C02 Summary I alue Record. YcarToDatcTotal is null or is less than 0)
return result B

else if (Current C02 Summary I alue Record. YcarToDatcTotal is not rounded to one decimal place)
return result D

else if (Annual C02M Calculated Value is not null)

if (Annual C02M Calculated Value <> Current C02 Summary Value Record. YearToDateTotal)
return result C

11 If no result

If (Current C02 Summary Value Record OzoneSeasonToDateTotal is not null)

Environmental Protection Agency	Page 157 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result E

else

If (Expected Summary Value C02 Array for this location =
return result F

false AND Annual C02M Calculated Value > 0)

Results:

Result

B
C

D

E

F
G

Response

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The [fieldname] in the Summary Value record for [param] is missing or invalid.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc].

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

You reported OzoneSeasonToDate in the Summary Value record for [param], but this is
not valid for this parameter.

You did not report a Summary Value record to report year-to-date total for [param].
You reported a Summary Value record for [param], but there was no [param] method
defined in your monitoring plan that was active during the year.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 158 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-11

Check Name:	Compare S02 Mass YTD Values

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

Annual S02M Calculated Value = null

if (Rpt Period S02 Mass Calculated Value is not null OR Expected Summary Value S02 Array for this location == false)

if (Expected Summary Value S02 Array for this location == true)

If (Emissions Tolerance Deviators contains "S02M")

Annual S02M Calculated Value = Current S02 Summary Value Record.Current Reporting Period Total

else

Annual S02M Calculated Value = Rpt Period S02 Mass Calculated Value

else if (Quarter of the Current Reporting Period is greater than 1)

Annual S02M Calculated Value = 0

If (Quarter of the Current Reporting Period is greater than 1)

If (S02 Start Quarter is not null)

For each quarter from the S02 Start Quarter to the quarter prior to the quarter of the Current Reporting Period.

Locate an Op Supp Data record for the location and quarter where ParameterCode = "S02M".

If not found,

if (Expected Summary Value S02 Array for this location == true)
set Annual S02M Calculated Value to null
return result A

Otherwise,

add OpValue to Annual S02M Calculated Value.

else

set Annual S02M Calculated Value to null

if (Current S02 Summary Value Record is not null)

if (Annual S02M Calculated Value is null AND Expected Summary Value S02 Array for this location == false)
return result H

else if (Current S02 Summary Value Record YearToDateTotal is null or is less than 0)
return result B

else if (Current S02 Summary Value Record YearToDateTotal is not rounded to one decimal place)
return result D

else if (Annual S02M Calculated Value is not null)

if (Annual S02M Calculated Value <> Current S02 Summary Value Record YearToDateTotal)
return result C

11 if no result

if (Current S02 Summary Value Record OzoneSeasonToDateTotal is not null)

Environmental Protection Agency

Page 159 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result F

else if {LME Annual is equal to true and Current S02 Summary Value Record. YearToDateTotal is greater than 25)
return result E

else

If (Expected Summary Value S02 Array for this location =
return result G

false AND Annual S02M Calculated Value > 0)

Results:

Result

B
C

D

E

G
H

Response

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The [fieldname] in the Summary Value record for [param] is missing or invalid.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc].

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

The [paramname] emissions from this unit exceed the applicable number of tons
necessary to qualify as an LME unit. According to Part 75.19(b), you must install the
appropriate monitoring systems to measure [paramname] by December 31 of the year
following this reporting period.

You reported OzoneSeasonToDate in the Summary Value record for [param], but this is
not valid for this parameter.

You did not report a Summary Value record to report year-to-date total for [param].
You reported a Summary Value record for [param], but there was no [param] method
defined in your monitoring plan that was active during the year.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Informational Message

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 160 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-12

Check Name:	Compare NOx Mass YTD and OS Values

Related Former Checks:

Applicability:	General Check

Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

Annual NOXM Calculated Value = null
OS NOXM Calculated Value = null
NOXM Summary Invalid Fields = null

Imprecise Fields = null

if (Rpt Period NOx Mass Calculated Value is not null OR Expected Summary Value NOx Mass Array for this location == false)

if (Expected Summary Value NOx Mass Array for this location == true)

If (Annual Reporting Requirement == true)

If (Emissions Tolerance Deviators contains "NOXM")

Annual NOXM Calculated Value = Current NOX Mass Summary Value Record. Current Reporting
Period Total

else

Annual NOXM Calculated Value = Rpt Period NOx Mass Calculated Value

If (OS Reporting Requirement == true)

if (Quarter of the Current Reporting Period is equal to 2 or 3)

If (Annual Reporting Requirement == true AND the Quarter of the Current Reporting Period is equal to

2)

OS NOXM Calculated Value = (Rpt Period NOx Mass Calculated Accumulator Array for this
location - April NOx Mass Calculated Accumulator Array for this location) / 2000, rounded to
one decimal place.

else

If (Emissions Tolerance Deviators contains "NOXM")

OS NOXM Calculated Value = Current NOX Mass Summary Value Record. Current
Reporting Period Total

else

OS NOXM Calculated Value = Rpt Period NOx Mass Calculated Value

else if (Quarter of the Current Reporting Period is equal to 4)

OS NOXM Calculated Value = 0

else

If (Annual Reporting Requirement == true AND the Quarter of the Current Reporting Period is greater than 1)

Annual NOXM Calculated Value = 0

If (OS Reporting Requirement == true AND the Quarter of the Current Reporting Period is greater than 2)

OS NOXM Calculated Value = 0

If (the Quarter of the Current Reporting Period is greater than 2 OR (Annual Reporting Requirement == true AND the Quarter of
the Current Reporting Period is equal to 2))

If (NOX Start Quarter is not null)

For each quarter in the current year from the NOX Start Quarter to the quarter prior to the quarter of the Current
Reporting Period.

Environmental Protection Agency

Page 161 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If this quarter is equal to 2 AND OS Reporting Requirement == true,

Locate an Op Supp Data record for the location and quarter where ParameterCode = "NOXMOS".

If not found,

if (Expected Summary Value NOx Mass Array for this location == true)
set Annual NOXM Calculated Value to null,
set OS NOXM Calculated Value to null
return result A

otherwise,

Locate an Op Supp Data record for the location and quarter where
ParameterCode = "NOXM".

If found,

set Annual NOXM Calculated Value to null,
set OS NOXM Calculated Value to null
return result A

Otherwise,

add OpValue to OS NOXM Calculated Value.

If this quarter is not equal to 2 OR Annual Reporting Requirement == true,

Locate an Op Supp Data record for the location and quarter where ParameterCode = "NOXM".

If not found,

if (Expected Summary Value NOx Mass Array for this location == true)
set Annual NOXM Calculated Value to null,
set OS NOXM Calculated Value to null
return result B

Otherwise,

if Annual Reporting Requirement == true

add OpValue to Annual NOXM Calculated Value.

if this quarter is equal to 3 AND OS Reporting Requirement == true
add OpValue to OS NOXM Calculated Value.

else

set Annual NOXM Calculated Value to null
set OS NOXM Calculated Value to null

if (Current NOX Mass Summary Value Record is not null)

If (OS NOXM Calculated Value Value is null AND Annual NOXM Calculated Value is null AND Expected Summary
Value NOx Mass Array for this location == false)
return result K

Otherwise,

If (Current NOX Mass Summary Value Record. YearToDateTotal is null and Annual Reporting Requirement ==
true) OR (Current NOX Mass Summary I alue Record. YearToDateTotal is less than 0,
append "YearToDateTotal" to NOXM Summary Invalid Fields

If (Current NOX Mass Summary Value Record. OzoneSeasonToDateTotal is null and OS Reporting Requirement
== true AND Quarter of the Current Reporting Period is equal to 2 or 3 or 4), OR Current NOX Mass Summary
Value Record OzoneSeasonToDateTotal is less than 0,

append "OzoneSeasonToDateTotal" to NOXM Summary Invalid Fields

Environmental Protection Agency

Page 162 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (Current NOX Mass Summary I alue Record YcarToDatcTotal is not rounded to one decimal place)
append "YearToDateTotal" to Imprecise Fields

If (Current NOX Mass Summary Value Record. OzoneSeasonToDateTotal is not rounded to one decimal place)
append "OzoneSeasonToDateTotal" to Imprecise Fields

If (NOXM Summary Invalid Fields is not null)
return result C

else if (Imprecise Fields is not null)

Set NOXM Summary Invalid Fields to Imprecise Fields
return result E

else if (Annual NOXM Calculated Value is not null OR OS NOXM Calculated Value is not null)

Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "NOXM" AND
UOM = "TON"

if (Annual NOXM Calculated Value is not null AND Annual NOXM Calculated Value o Current NOX
Mass Summary Value Record. YearToDateTotal)

append "YearToDateTotal" to NOXM Summary Invalid Fields

if (OS NOXM Calculated Value is not null AND OS NOXM Calculated Value o Current NOX Mass
Summary Value Record OzoneSeasonToDateTotal)

if (ABS(OS NOXM Calculated Value - Current NOXM Summary Value

Record OzoneSeasonToDateTotal) > Tolerance OR quarter of the Current Reporting Period is

greater than 2)

append "OzoneSeasonToDateTotal" to NOXM Summary Invalid Fields

If NOXM Summary Invalid Fields is not null,

If (NOXM Summary Invalid Fields contains "Year")

If (NOXM Summary Invalid Fields contains "Ozone")
return result D

else

return result H

else

return result I

11 if no result

if (OS Reporting Requirement == false and Current NOXM Summary Value Record. OzoneSeasonToDateTotal is
not null)

return result G

else if (Annual Reporting Requirement == false and Current NOXM Summary Value Record. YearToDateTotal
is not null)

return result L

else if ((LME Annual is equal to true and Current NOXM Summary Value Record YearToDateTotal is greater
than 100) OR (LME OS is equal to true and Current NOXM Summary Value Record OzoneSeasonToDateTotal is
greater than 50))

return result F

else

If (Expected Summary Value NOx Mass Array for this location == false AND (OS NOXM Calculated Value > 0 OR
Annual NOXM Calculated Value > 0))
return result J

Environmental Protection Agency

Page 163 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B

C
D

E
F

G

H

I

J
K

Response

The program could not determine ozone-season-to-date totals for [osparam], because the
Op Supp Data record for this parameter is missing for one or more previous reporting
periods. If you have submitted emissions data for prior quarters, you should be able to
retrieve these records by logging on to the EPA host.

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The [fieldname] in the Summary Value record for [param] is missing or invalid.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc], and the OzoneSeasonToDateTotal
of [osval] in the Summary Value record for [param] is inconsistent with the recalculated
value of [oscalc].

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

The [paramname] emissions from this unit exceed the applicable number of tons
necessary to qualify as an LME unit. According to Part 75.19(b), you must install the
appropriate monitoring systems to measure [paramname] by December 31 of the year
following this reporting period.

You reported OzoneSeasonToDate in the Summary Value record for [param], but this is
not valid for locations that are not associated with an ozone-season program.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc].

The OzoneSeasonToDateTotal of [osval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [oscalc].

You did not report a Summary Value record to report year-to-date total for [param].
You reported a Summary Value record for [param], but there was no [param] method
defined in your monitoring plan that was active during the year.

You reported YearToDate in the Summary Value record for [param], but this is not
valid for locations that only report during the ozone season.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Informational Message

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 164 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-13

Check Name:	Compare NOx Rate YTD Values

Related Former Checks:

Applicability:	General Check

Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

Annual NOXR Calculated Value = null
If (LME Annual == true)

Set Total NOx Mass to null.

if (Expected Summary Value NOx Rate Array for this location == true)

if (Rpt Period NOx Mass Calculated Accumulator Array for this location is greater than or equal to 0 AND Rpt Period HI
Calculated Value is not null)

Set Total NOx Mass to Rpt Period NOx Mass Calculated Accumulator Array for this location.

Set Total HI to Rpt Period HI Calculated Value.

else if (Quarter of the Current Reporting Period is greater than 1)

Set Total NOx Mass to 0.

Set Total HI to 0.

If (Quarter of the Current Reporting Period is greater than 1 AND Total NOx Mass is not null)

if (NOXR Start Quarter is not null)

For each quarter in the current year from the NOXR Start Quarter to the quarter prior to the quarter of the Current
Reporting Period.

Locate an Op Supp Data record for the location and quarter where ParameterCode = "NOXR".

If not found,

if (Expected Summary Value NOx Rate Array for this location == true)
set Total NOx Mass to null,
return result A

Otherwise,

set NOX Value to OpValue.

Locate an Op Supp Data record for the location and quarter where ParameterCode = "HIT".
If not found,

if (Expected Summary Value NOx Rate Array for this location == true)
set Total HI to null,
return result E

Otherwise,

Add OpValue to Total HI.

Calculate NOX Value = NOX Value * OpValue, and round the result to 1 decimal place.
Add NOX Value to Total NOx Mass.

Environmental Protection Agency

Page 165 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Set TotalNOxMass to null.

If (Total NOxMass is not null AND Total HI is not null)

If (Total NOxMass == 0)

Set Annual NOXR Calculated Value to 0.

else

Calculate Annual NOXR Calculated Value = Total NOx Mass I TotalHI, and round the result to 3 decimal places.

Set TotalOpHours to null.

if (Expected Summary Value NOx Rate Array for this location == true)

if (Rpt Period NOx Rate Calculated Value is not null)

Annual NOXR Calculated Value = Rpt Period NOx Rate Sum
Set TotalOpHours to Rpt Period NOx Rate Hours.

else if ((Quarter of the Current Reporting Period is greater than 1)

Set TotalOpHours to 0.

If (Quarter of the Current Reporting Period is greater than 1 AND TotalOpHours is not null)
if (NOXR Start Quarter is not null)

For each quarter from the NOXR Start Quarter to the quarter prior to the quarter of the Current Reporting Period.
Locate an Op Supp Data record for the location and quarter where ParameterCode = "NOXRSUM".
If found,

Add OpValue to Annual NOXR Calculated Value.

Locate an Op Supp Data record for the location and quarter where ParameterCode =
"NOXRHRS".

If found,

Add OpValue to TotalOpHours.

If not found,

set Annual NOXR Calculated Value to null
return result A

Otherwise,

Locate an Op Supp Data record for the location and quarter where ParameterCode = "NOXR".
If not found,

if (Expected Summary Value NOx Rate Array for this location == true)
set Annual NOXR Calculated Value to null
return result A

Otherwise,

set NOXVal to OpValue

Locate an Op Supp Data record for the location and quarter where ParameterCode = "OPHOURS"
and FuelCode is null.

Environmental Protection Agency

Page 166 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If not found,

if (Expected Summary Value NOx Rate Array for this location == true)
set Annual XO.XR Calculated Value to null
return result B

Otherwise,

Add OpValue to TotalOpHours.

Add OpValue * NOXVal to Annual NOXR Calculated Value

else

set Annual NOXR Calculated Value to null.

If (Annual NOXR Calculated Value is not null)

If (TotalOpHours == 0)

Set Annual NOXR Calculated Value to 0.

else if (Annual NOXR Calculated Value > 0)

Calculate Annual NOXR Calculated Value = Annual NOXR Calculated Value I TotalOpHours, and round the
result to 3 decimal places.

if (Current NOXR Summary Value Record is not null)

If (Annual NOXR Calculated Value is null AND Expected Summary Value NOx Rate Array for this location == false)
return result H

else if (Current NOXR Summary Value Record YearToDateTotal is null or is less than 0)
return result C

else if (Annual NOXR Calculated Value is not null)

if (Annual NOXR Calculated Value <> Current NOXR Summary Value Record YearToDateTotal)

Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "NOXR" AND
UOM = "LBMMBTU"

if (A\'S(Annual NOXR Calculated Value - Current NOXR Summary Value Record YearToDateTotal) >
Tolerance)

return result D

11 if no result

if (Current NOXR Summary Value Record OzoneSeasonToDateTotal is not null)
return result F

else

If (Expected Summary Value NOx Rate Array for this location == false AND Annual NOXR Calculated Value > 0)
return result G

Environmental Protection Agency

Page 167 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B

C
D

G
H

Response

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The program could not determine year-to-date for [param], because the Op Supp Data
record for OPHOURS is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The [fieldname] in the Summary Value record for [param] is missing or invalid.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc].

The program could not determine year-to-date for [param], because the Op Supp Data
record for HIT is missing for one or more previous reporting periods. If you have
submitted emissions data for prior quarters, you should be able to retrieve these records
by logging on to the EPA host.

You reported OzoneSeasonToDate in the Summary Value record for [param], but this is
not valid for this parameter.

You did not report a Summary Value record to report year-to-date total for [param].
You reported a Summary Value record for NOXR, but this is not appropriate, because
this record is not consistent with the unit program records and monitoring methodologies
in your monitoring plan. You only report a NOXR Summary Value if the unit belongs
to the Acid Rain program.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 168 of 667


-------
Draft ECMPS Emissions Check Specifications
Check Code:	HOURAGG-14

Check Name:	Compare Total Heat Input YTD and OS Values

Related Former Checks:

Applicability:	General Check

Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

Annual HIT Calculated Value = null
OS HIT Calculated Value = null
III Summary Invalid Fields = null

Imprecise Fields = null

9/17/2014 12:00:00AM

if (Rpt Period HI Calculated Value is not null OR Expected Summary Value HI Array for this location == false)

if (Expected Summary Value HI Array for this location == true)

If (Annual Reporting Requirement == true)

If (Emissions Tolerance Deviators contains "HIT")

Annual HI Calculated Value = Current HI Summary Value Record.Current Reporting Period Total

else

Annual HI Calculated Value = Rpt Period HI Calculated Value

If (OS Reporting Requirement == true)

if (the Quarter of the Current Reporting Period is equal to 2 or 3)

If (Annual Reporting Requirement == true AND the Quarter of the Current Reporting Period is equal to

2)

OS HIT Calculated Value = Rpt Period HI Calculated Accumulator Array for this location -
April HI Calculated Accumulator Array for this location, and round the result to zero decimal
places.

else

If (Emissions Tolerance Deviators contains "HIT")

OS HIT Calculated Value = Current HI Summary Value Record.Current Reporting
Period Total

else

OS HIT Calculated Value = Rpt Period HI Calculated Value

else if (Quarter of the Current Reporting Period is equal to 4)

OS HIT Calculated Value = 0

else

If (Annual Reporting Requirement == true AND the Quarter of the Current Reporting Period is greater than 1)

Annual HI Calculated Value = 0

If (OS Reporting Requirement == true AND the Quarter of the Current Reporting Period is greater than 2)

OS HIT Calculated Value = 0

If (the Quarter of the Current Reporting Period is greater than 2 OR (Annual Reporting Requirement == true AND the Quarter of
the Current Reporting Period is equal to 2))

If (Heat Input Start Quarter is not null)

For each quarter in the current year from the Heat Input Start Quarter to the quarter prior to the quarter of the
Current Reporting Period.

Environmental Protection Agency

Page 169 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If this quarter is equal to 2 AND OS Reporting Requirement == true,

Locate an Op Supp Data record for the location and quarter where ParameterCode = "HITOS".

If not found,

if (Expected Summary Value HI Array for this location == true)
set Annual HIT Calculated Value to null,
set OS HIT Calculated Value to null
return result A

otherwise,

Locate an Op Supp Data record for the location and quarter where
ParameterCode = "HIT".

If found,

set Annual HIT Calculated Value to null,
set OS HIT Calculated Value to null
return result A

Otherwise,

add OpValue to OS HIT Calculated Value.

If this quarter is not equal to 2 OR Annual Reporting Requirement == true,

Locate an Op Supp Data record for the location and quarter where ParameterCode = "HIT".

If not found,

if (Expected Summary Value HI Array for this location == true)
set Annual HIT Calculated Value to null,
set OS HIT Calculated Value to null
return result B

Otherwise,

if Annual Reporting Requirement == true

add OpValue to Annual HIT Calculated Value.

if this quarter is equal to 3 AND OS Reporting Requirement == true
add OpValue to OS HIT Calculated Value.

else

set Annual HIT Calculated Value to null
set Annual OS HIT Calculated Value to null

if (Current HI Summary Value Record is not null)

If (OS HIT Calculated Value is null AND Annual HIT Calculated Value is null AND Expected Summary Value HI
Array for this location == false and (LME HI Method <> "LTFF" or location does not start with "CP") )
return result K

Otherwise,

If (Current HI Summary Value Record YearToDateTotal is null and Annual Reporting Requirement == true) OR
(Current HI Summary Value Record. YearToDateTotal is less than 0,
append "YearToDateTotal" to HIT Summary Invalid Fields

If (Current HI Summary Value ifecorrf OzoneSeasonToDateTotal is null and OS Reporting Requirement == true
AND Quarter of the Current Reporting Period is equal to 2 or 3 or 4), OR Current HI Summary Value
ifecorrf OzoneSeasonToDateTotal is less than 0,

append "OzoneSeasonToDateTotal" to HIT Summary Invalid Fields

Environmental Protection Agency

Page 170 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (Current HI Summary Value ifecorrf YearToDateTotal is not rounded to zero decimal places)
append "YearToDateTotal" to Imprecise Fields

If (Current HI Summary Value ifecorrf OzoneSeasonToDateTotal is not rounded to zero decimal places)

If (Legacy Data Evaluation == false OR Current HI Summary Value ifecorrf OzoneSeasonToDateTotal
is not rounded to one decimal place)

append "OzoneSeasonToDateTotal" to Imprecise Fields

If (HIT Summary Invalid Fields is not null)
return result C

else if (Imprecise Fields is not null)

set HIT Summary Invalid Fields to Imprecise Fields
return result E

else if (Annual HIT Calculated Value is not null OR OS HIT Calculated Value is not null)

Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "HIT" AND
UOM = "MMBTU"

if (Annual HIT Calculated Value is not null AND Annual HIT Calculated Value <> Current HI
Summary Value Record YearToDateTotal)

append "YearToDateTotal" to HIT Summary Invalid Fields

if (OS HIT Calculated Value is not null AND OS HIT Calculated Value <> Current HI Summary Value
Record. OzoneSeasonToDateTotal)

If (Legacy Data Evaluation == false)

if (ABS(OS HIT Calculated Value - Current HI Summary Value

Record OzoneSeasonToDateTotal) > Tolerance OR the quarter of the Current Reporting
Period is greater than 2)

append "OzoneSeasonToDateTotal" to HIT Summary Invalid Fields

else

if (ABS(OS HIT Calculated Value - Current HI Summary Value

Record OzoneSeasonToDateTotal rounded to the nearest integer) > Tolerance OR the

quarter of the Current Reporting Period is greater than 2)

append "OzoneSeasonToDateTotal" to HIT Summary Invalid Fields

If (HIT Summary Invalid Fields is not null)

If (HIT Summary Invalid Fields contains "Year")

If (HIT Summary Invalid Fields contains "Ozone")
return result D

else

return result H

else

If (Legacy Data Evaluation == true)
return result F

else

return result I

11 if no result

if (OS Reporting Requirement == false and Current HI Summary Value Record OzoneSeasonToDateTotal is not
null)

return result G

Environmental Protection Agency

Page 171 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

else if (.Annual Reporting Requirement == false and Current HI Summary Value Record YearToDateTotal is not
null)

return result L

If (Expected Summary Value HI Array for this location == false AND (Annual HIT Calculated Value > 0 OR OS HIT
Calculated Value > 0))
return result J

Results:

Result

B

C
D

E

F

G

H

I

J
K

Response

The program could not determine ozone-season-to-date totals for [osparam], because the
Op Supp Data record for this parameter is missing for one or more previous reporting
periods. If you have submitted emissions data for prior quarters, you should be able to
retrieve these records by logging on to the EPA host.

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The [fieldname] in the Summary Value record for [param] is missing or invalid.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc], and the OzoneSeasonToDateTotal
of [osval] in the Summary Value record for [param] is inconsistent with the recalculated
value of [oscalc].

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

The OzoneSeasonToDateTotal of [osval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [oscalc].

You reported OzoneSeasonToDate in the Summary Value record for [param], but this is
not valid for locations that are not associated with an ozone-season program.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc].

The OzoneSeasonToDateTotal of [osval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [oscalc].

You did not report a Summary Value record to report year-to-date total for [param].
You reported a Summary Value record for [param], but there was no [param] method
defined in your monitoring plan that was active during the year.

You reported YearToDate in the Summary Value record for [param], but this is not
valid for locations that only report during the ozone season.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Informational Message

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 172 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAGG-15

Check Name:

Compare Operating Time YTD and OS Values

Related Former Checks:

Applicability:

General Check

Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

Annual OPTIME Calculated Value = null
OS OPTIME Calculated Value = null
OPTIME Summary Invalid Fields = null

Imprecise Fields = null

if (Rpt Period Op Time Calculated Value is not null)
If Annual Reporting Requirement == true

If (Emissions Tolerance Deviators contains "OPTIME")

Annual OPTIME Calculated Value = Current Op Time Summary Value Record.Current Reporting Period Total

Annual OPTIME Calculated Value = Rpt Period Op Time Calculated Value

If OS Reporting Requirement == true)

if (the Quarter of the Current Reporting Period is equal to 2 or 3)

If Annual Reporting Requirement == true AND the Quarter of the Current Reporting Period is equal to 2,

OS OPTIME Calculated Value = Rpt Period Op Time Accumulator Array for this location - April Op
Time Accumulator Array for this location.

If (Emissions Tolerance Deviators contains "OPTIME")

OS OPTIME Calculated Value = Current Op Time Summary Value Record.Current Reporting
Period Total

else

OS OPTIME Calculated Value = Rpt Period Op Time Calculated Value

else if (Quarter of the Current Reporting Period is equal to 4)
OS OPTIME Calculated Value = 0

If (the Quarter of the Current Reporting Period is greater than 2 OR (Annual Reporting Requirement == true AND the Quarter of
the Current Reporting Period is equal to 2))

If (Start Quarter is not null)

For each quarter in the current year from the Start Quarter to the quarter prior to the quarter of the Current
Reporting Period.

If this quarter is equal to 2 AND OS Reporting Requirement == true

Locate an Op Supp Data record for the location and quarter where ParameterCode = "OSTIME".

else

else

If not found,

set Annual OPTIME Calculated Value to null,
set OS OPTIME Calculated Value to null

Locate the Facility record for the location.

If the First ECMPS Reporting Period in the retrieved record is not null AND is on or
before the 2nd quarter of the current year,

Environmental Protection Agency

Page 173 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result A.

exit for.

Otherwise,

add OpValue to OS OPTIME Calculated Value.

If this quarter is not equal to 2 OR Annual Reporting Requirement == true,

Locate an Op Supp Data record for the location and quarter where ParameterCode = "OPTIME".

If not found,

if Annual Reporting Requirement == true

set Annual OPTIME Calculated Value to null.

if OS Reporting Requirement == true

set OS OPTIME Calculated Value to null.

Locate the Facility record for the location.

If the First ECMPS Reporting Period in the retrieved record is not null AND is on or
before the Start Quarter of the current year,
return result B.

exit for.

Otherwise,

if Annual Reporting Requirement == true

add OpValue to Annual OPTIME Calculated Value.

if this quarter is equal to 3 AND OS Reporting Requirement == true
add OpValue to OS OPTIME Calculated Value.

Otherwise,

set Annual OPTIME Calculated Value to null,
set OS OPTIME Calculated Value to null.

if (Current Op Time Summary Value Record is not null)

If (Current Op Time Summary Value Record YearToDateTotal is null and Annual Reporting Requirement == true) OR
(Current Op Time Summary Value Record. YearToDateTotal is less than 0,
append "YearToDateTotal" to OPTIME Summary Invalid Fields

If (Current Op Time Summary Value Record OzoneSeasonToDateTotal is null and OS Reporting Requirement == true
AND Quarter of the Current Reporting Period is equal to 2 or 3 or 4), OR Current Op Time Summary Value
Record. OzoneSeasonToDateTotal is less than 0,

append "OzoneSeasonToDateTotal" to OPTIME Summary Invalid Fields

If (Current Op Time Summary Value Record YearToDateTotal is not rounded to two decimal places)
append "YearToDateTotal" to Imprecise Fields

If (Current Op Time Summary Value Record OzoneSeasonToDateTotal is not rounded to two decimal places)
append "OzoneSeasonToDateTotal" to Imprecise Fields

If (OPTIME Summary Invalid Fields is not null)
return result C

else if (Imprecise Fields is not null)

Set OPTIME Summary Invalid Fields to Imprecise Fields
return result E

Environmental Protection Agency

Page 174 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else if (Annual OPTIME Calculated Value is not null OR OS OPTIME Calculated Value is not null)

Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "OPTIME" AND
UOM = "HR"

if (Annual OPTIME Calculated Value is not null AND Annual OPTIME Calculated Value o Current Op Time
Summary Value Record. YearToDateTotal)

append "YearToDateTotal" to OPTIME Summary Invalid Fields

if (OS OPTIME Calculated Value is not null AND OS OPTIME Calculated Value o Current Op Time
Summary Value itecoraJ OzoneSeasonToDateTotal)

if (ABS(0S OPTIME Calculated Value - Current Op Time Summary Value

Record. OzoneSeasonToDateTotal) > Tolerance OR quarter of the Current Reporting Period is greater
than 2)

append "OzoneSeasonToDateTotal" to OPTIME Summary Invalid Fields

If OPTIME Summary Invalid Fields is not null,

If (OPTIME Summary Invalid Fields contains "Year")

If (OPTIME Summary Invalid Fields contains "Ozone")
return result D

else

return result G

else

return result H

11 if no result

if (OS Reporting Requirement == false and Current Op Time Summary Value Record. OzoneSeasonToDateTotal is not
null)

return result F

else if (Annual Reporting Requirement == false and Current Op Time Summary Value Record YearToDateTotal is not
null)

return result I

Environmental Protection Agency

Page 175 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B

C
D

E
F
G
H
I

Response

The program could not determine ozone-season-to-date totals for [osparam], because the
Op Supp Data record for this parameter is missing for one or more previous reporting
periods. If you have submitted emissions data for prior quarters, you should be able to
retrieve these records by logging on to the EPA host.

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The [fieldname] in the Summary Value record for [param] is missing or invalid.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc], and the OzoneSeasonToDateTotal
of [osval] in the Summary Value record for [param] is inconsistent with the recalculated
value of [oscalc].

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

You reported OzoneSeasonToDate in the Summary Value record for [param], but this is
not valid for locations that are not associated with an ozone-season program.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc].

The OzoneSeasonToDateTotal of [osval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [oscalc].

You reported YearToDate in the Summary Value record for [param], but this is not
valid for locations that only report during the ozone season.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 176 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-16

Check Name:	Compare Operating Hours YTD and OS Values

Related Former Checks:

Applicability:	General Check

Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

Annual OPHOURS Calculated Value = null
OS OPHOURS Calculated Value = null
OPHOURS Summary Invalid Fields = null

Imprecise Fields = null

if (Rpt Period Op Hours Calculated Value is not null)

If Annual Reporting Requirement == true

If (Emissions Tolerance Deviators contains "OPHOURS")

Annual OPHOURS Calculated Value = Current Op Hours Summary Value Record.Current Reporting Period
Total

else

Annual OPHOURS Calculated Value = Rpt Period Op Hours Calculated Value

If OS Reporting Requirement == true)

if (the Quarter of the Current Reporting Period is equal to 2 or 3)

If Annual Reporting Requirement == true AND the Quarter of the Current Reporting Period is equal to 2,

OS OPHOURS Calculated Value = Rpt Period Op Hours Accumulator Array for this location - April Op
Hours Accumulator Array for this location.

else

If (Emissions Tolerance Deviators contains "OPHOURS")

OS OPHOURS Calculated Value = Current Op Hours Summary Value Record.Current
Reporting Period Total

else

OS OPHOURS Calculated Value = Rpt Period Op Hours Calculated Value

else if (Quarter of the Current Reporting Period is equal to 4)

OS OPHOURS Calculated Value = 0

If (the Quarter of the Current Reporting Period is greater than 2 OR (Annual Reporting Requirement == true AND the Quarter of
the Current Reporting Period is equal to 2))

If (Start Quarter is not null)

For each quarter in the current year from the Start Quarter to the quarter prior to the quarter of the Current
Reporting Period.

If this quarter is equal to 2 AND OS Reporting Requirement == true,

Locate an Op Supp Data record for the location and quarter where ParameterCode = "OSHOURS"
and FuelCd is null.

If not found,

set Annual OPHOURS Calculated Value to null,
set OS OPHOURS Calculated Value to null
return result A

Otherwise,

Environmental Protection Agency

Page 177 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

add OpValue to OS OPHOURS Calculated Value.

If this quarter is not equal to 2 OR Annual Reporting Requirement == true,

Locate an Op Supp Data record for the location and quarter where ParameterCode = "OPHOURS"
and FuelCd is null.

If not found,

set Annual OPHOURS Calculated Value to null,
set OS OPHOURS Calculated Value to null
return result B

Otherwise,

if Annual Reporting Requirement == true

add OpValue to Annual OPHOURS Calculated Value.

if this quarter is equal to 3 AND OS Reporting Requirement == true
add OpValue to OS OPHOURS Calculated Value.

Otherwise,

set Annual OPHOURS Calculated Value to null,
set OS OPHOURS Calculated Value to null.

if (Current Op Hours Summary Value Record is not null)

If (Current Op Hours Summary Value Record. YearToDateTotal is null and Annual Reporting Requirement == true) OR
(Current Op Hours Summary Value Record YearToDateTotal is less than 0,
append "YearToDateTotal" to OPHOURS Summary Invalid Fields

If (Current Op Hours Summary Value itecoraJ OzoneSeasonToDateTotal is null and OS Reporting Requirement == true
AND Quarter of the Current Reporting Period is equal to 2 or 3 or 4), OR Current Op Hours Summary Value
ifecoraJ OzoneSeasonToDateTotal is less than 0,

append "OzoneSeasonToDateTotal" to OPHOURS Summary Invalid Fields

If (Current Op Hours Summary Value Record. YearToDateTotal is not rounded to zero decimal places)
append "YearToDateTotal" to Imprecise Fields

If (Current Op Hours Summary Value Record. OzoneSeasonToDateTotal is not rounded to zero decimal places)
append "OzoneSeasonToDateTotal" to Imprecise Fields

If (OPHOURS Summary Invalid Fields is not null)
return result C

else if (Imprecise Fields is not null)

set OPHOURS Summary Invalid Fields to Imprecise Fields
return result E

else if {Annual OPHOURS Calculated Value is not null OR OS OPHOURS Calculated Value is not null)

Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "OPHOURS" AND
UOM = "HR"

if (Annual OPHOURS Calculated Value is not null AND Annual OPHOURS Calculated Value o Current Op
Hours Summary Value Record. YearToDateTotal)

append "YearToDateTotal" to OPTIME Summary Invalid Fields

if (OS OPHOURS Calculated Value is not null AND OS OPHOURS Calculated Value o Current Op Hours

Environmental Protection Agency

Page 178 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Summary Value itecoraJ OzoneSeasonToDateTotal)

if (ABS(OS OPHOURS Calculated Value - Current Op Hours Summary Value

Record. OzoneSeasonToDateTotal) > Tolerance OR quarter of the Current Reporting Period is greater

than 2)

append "OzoneSeasonToDateTotal" to OPHOURS Summary Invalid Fields

If OPHOURS Summary Invalid Fields is not null,

If (OPHOURS Summary Invalid Fields contains "Year")

If (OPHOURS Summary Invalid Fields contains "Ozone")
return result D

else

return result G

else

return result H

11 if no result

if (OS Reporting Requirement == false and Current Op Hours Summary Value Record. OzoneSeasonToDateTotal is not
null)

return result F

else if (Annual Reporting Requirement == false and Current Op Hours Summary Value Record. YearToDateTotal is not
null)

return result I

Environmental Protection Agency

Page 179 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B

C
D

E
F
G
H
I

Response

The program could not determine ozone-season-to-date totals for [osparam], because the
Op Supp Data record for this parameter is missing for one or more previous reporting
periods. If you have submitted emissions data for prior quarters, you should be able to
retrieve these records by logging on to the EPA host.

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The [fieldname] in the Summary Value record for [param] is missing or invalid.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc], and the OzoneSeasonToDateTotal
of [osval] in the Summary Value record for [param] is inconsistent with the recalculated
value of [oscalc].

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

You reported OzoneSeasonToDate in the Summary Value record for [param], but this is
not valid for locations that are not associated with an ozone-season program.
The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc].

The OzoneSeasonToDateTotal of [osval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [oscalc].

You reported YearToDate in the Summary Value record for [param], but this is not
valid for locations that only report during the ozone season.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 180 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAGG-17

Check Name:

Check BC02 Summary Value

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current BC02 Summary Value Record = Summary Value record at this location where
Parameter = "BC02" AND
Reporting Period ID = Current Reporting Period

Set RGGIBegin Date, RGGIStart Quarter, AND BC02 Quarterly Reported Value to null.

if (Current BC02 Summary Value Record is not null)

if {CurrentMonitorPlanLocationRecord.StackPipelD is not null)
return result A

Locate a Program record for the unit where the ProgramCode == "RGGI", the UnitMonitorCertBeginDate is on or prior to
the last day of the reporting period, and the EndDate is null or is on or after the first day of reporting period.

Set RGGI Begin Date to the later of the UnitMonitorCertBeginDate and the EmissionsRecordingBeginDate (if not
null) in the retrieved record.

If RGGI Begin Date is in a year prior to the current reporting period,

Set RGGI Start Quarter to 1

Set RGGI Start Quarter to the quarter of the RGGI Begin Date.

if (Current BC02 Summary Value Record.Current Reporting Period Total < 0)
return result C

else if (Current BC02 Summary Value Record.Current Reporting Period Total is not rounded to one decimal
place)

return result D

else

BC02 Quarterly Reported Value = Current BC02 Summary Value Record.Current Reporting Period
Total

else

If not found,

return result B

else

else

Environmental Protection Agency

Page 181 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

E

Usage:

1

Response

You reported a Summary Value record for [param], but this value should only be
reported at the unit, not at a stack or pipe.

You reported a Summary Value record for BC02, but this location does not belong to
the RGGI program during this reporting period.

The CurrentReportingPeriodTotal reported in the Summary Value record for [param] is
invalid. The value must be greater than or equal to 0.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

This check result is obsolete.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 182 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAGG-18

Check Name:	Compare BC02 Mass YTD Values

Related Former Checks:

Applicability:	General Check

Description:

Validation Tables:

[Quarterly Emissions Tolerances] (Cross Check Table)

Specifications:

Set Annual BC02 Calculated Value to null.

If (BC02 Quarterly Reported Value is not null)

Annual BC02M Calculated Value = BC02 Quarterly Reported Value

else

Annual BC02M Calculated Value = -1

If (RGGI Start Quarter i s not null AND Quarter of the Current Reporting Period i s greater than 1)

For each quarter in the current year from the RGGI Start Quarter to the quarter prior to the quarter of the Current Reporting
Period.

Locate an Op Supp Data record for the location and quarter where ParameterCode = "BC02".

If not found,

If (BC02 Quarterly Reported Value is not null)

set Annual BC02 Calculated Value to null
return result A

Otherwise,

If (Annual BC02M Calculated Value == -1)

Set Annual BC02M Calculated Value to OpValue

else

add OpValue to Annual BC02 Calculated Value.

If (Current BC02 Summary Value Record is not null)

If (.Annual BC02M Calculated Value = -1)

set Annual BC02 Calculated Value to null
return result G

else if (Current BC02 Summary Value Record YearToDateTotal is null or is less than 0)
return result B

else if (Current BC02 Summary Value Record YearToDate Total is not rounded to one decimal place)
return result C

else if (Annual BC02 Calculated Value is not null)

if (Annual BC02 Calculated Value <> Current BC02 Summary Value Record. YearToDateTotal)

Tolerance = Lookup Tolerance from Cross-Check Table "Quarterly Emissions Tolerances" where
Parameter = "C02M" AND
UOM = "TON"

if (A\'S(Annual BC02 Calculated Value - Current BC02 Summary Value Record. YearToDateTotal) >
Tolerance)

Environmental Protection Agency

Page 183 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result D

11 If no result

If (Current BC02 Summary Value Record. OzoneSeasonToDateTotal is not null)
return result E.

If (Annual BC02 Calculated Value == -1)

set Annual BC02 Calculated Value to null

If (Annual BC02 Calculated Value > 0)

return result F

Results:

Result

B
C

D

E

F
G

Usage:
1

Response

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The [fieldname] in the Summary Value record for [param] is missing or invalid.
You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

The YearToDateTotal of [ytdval] in the Summary Value record for [param] is
inconsistent with the recalculated value of [ytdcalc].

You reported OzoneSeasonToDate in the Summary Value record for [param], but this is
not valid for this parameter.

You did not report a Summary Value record to report year-to-date total for [param].
You reported a Summary Value record for [param], but there was no [param] method
defined in your monitoring plan that was active during the year.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 184 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Hourly Appendix D

Environmental Protection Agency

Page 185 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-1

Check Name:

Initialize Accumulators for Appendix D Calculations

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

HI App D Accumulator = 0
S02 App D Accumulator = 0
C02 App D Accumulator = 0
NOXR App E Accumulator = 0
Current Fuel Flow Record = null
Current Fuel Group = null
Fuels Used List = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Appendix D/E Unit-Level Initialization

Environmental Protection Agency

Page 186 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-3

Check Name:

Initialize Fuel Flow Record

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Current Fuel Group = Current Fuel Flow ifecorrf.Fuel Group Cd

if (Current Fuel Flow itecortf.UnitFuelCd in set {OGS, PRG,OOL})
Special Fuel Burned = true

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Ftourly Fuel Flow

Environmental Protection Agency

Page 187 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-4

Check Name:

Check Fuel Usage Time

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

HFF Usage Time Status = true

If (Current Fuel Flow itecortf.FuelUsageTime is null OR Current Fuel Flow ifecorrf.FuelUsageTime < 0 OR Current Fuel Flow
ifecorrf.FuelUsageTime > 1)

HFF Usage Time Status = false
return result A

else if {Current Hourly Op ifecorrf.OperatingTime > 0 AND Current Hourly Opifecorrf.OperatingTime <= 1)

if Current Fuel Flow Record.\: udCodc is not in Fuels Used List

add 1 to Fuel Op Hours Accumulator Array for the location and fuel
append FuelCode to the Fuels Used List

if (Current Fuel Flow ifecorrf.FuelUsageTime > Current Hourly Op itecortf.OperatingTime)

HFF Usage Time Status = false
return result B

else if (Hourly Fuel Flow Count For Gas + Hourly Fuel Flow Count For Oil == 1 AND (MP Pipe Config for Hourly Checks is
null OR Current Hourly Op ifecortf.LocationName begins with "CP") AND Current Fuel Flow ifecorrf.FuelUsageTime o
Current Hourly Op ifecorrf.OperatingTime)

HFF Usage Time Status = false

return result B

Results:

Result
A

Response

The FuelUsageTime reported in the FtFF record for FuelCode [fueled] is invalid. The
must be greater than 0 and less than or equal to 1.

The FuelUsageTime reported in the FtFF record for FuelCode [fueled] is inconsistent
with the OperatingTime for the hour.

Severity

Critical Error Level 1

B

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Ftourly Fuel Flow

Environmental Protection Agency

Page 188 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-5

Check Name:	Check Volumetric SODC Code

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

HFF SODC Status = true

If (Current Fuel Flow itecortf.SourceOfDataVolumetricCode is null)

If (Current Fuel Flow Record. VolumetricFlowRate is not null)

HFF SODC Status == false
return result A

else

If (Current Fuel Flow Record. VolumetricFlowRate is null)

HFF SODC Status == false
return result B

else if (Current Fuel Group == "GAS" and Current Fuel Flow ifecortf.SourceOfDataVolumetricCode in set {5, 6})
HFF SODC Status == false
return result C

else if (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode = "3" AND Current Unit Is Peaking == false)

HFF SODC Status == false
return result D
else if (HFF Fuel Indicator Code is not null)

if (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode == "4" AND HFF Fuel Indicator Code o "E")
HFF SODC Status == false
return result E

else if (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode in set {5, 6} AND HFF Fuel Indicator Code o "I")
HFF SODC Status == false
return result F

Results:

Result
A

B

C

D

E

Usage:
1

Response

You did not report a [fieldname] in the HFF record for FuelCode [fueled], but you
reported a [ratefieldname].

You reported a [fieldname] in the HFF record for FuelCode [fueled], but you did not
report a [ratefieldname].

The SourceOfDataVolumetricCode reported in the HFF record for FuelCode [fueled] is
invalid.

You reported a [fieldname] of 3 in the HFF record for FuelCode [fueled], but, according
to the qualification record in your monitoring plan, this is not a peaking unit.
You reported a [fieldname] of 4 in the HFF record for FuelCode [fueled], which
indicates that the fuel is an emergency fuel, but according to the Unit Fuel record in your
monitoring plan, this fuel is not an emergency fuel.

You reported a [fieldname] of [sodc] in the HFF record for FuelCode [fueled], which
indicates that the fuel is an igniter fuel, but according to the Unit Fuel record in your
monitoring plan, this fuel is not an igniter fuel.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 189 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-6

Check Name:	Check Oil Mass SODC Code

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

HFF Mass SODC Status == true

If (Current Fuel Flow itecortf.SourceOfDataMassCode is null)

If (Current Fuel Flow ifecortf.MassFlowRate is not null)

HFF Mass SODC Status == false
return result A

else

If (Current Fuel Flow ifecortf.MassFlowRate is null)

HFF Mass SODC Status == false
return result B

else if (Current Fuel Flow Record. VolumetricFlowRate is not null AND Current Fuel Flow itecortf.SourceOfDataMassCode o
"2")

HFF Mass SODC Status == false
return result C

else if (Current Fuel Flow Record. VolumetricFlowRate is null AND Current Fuel Flow ifecortf.SourceOfDataMassCode == "2")
HFF Mass SODC Status == false
return result D

else if (Current Fuel Flow ifecortf.SourceOfDataMassCode = "3" AND Current Unit Is Peaking == false)

HFF Mass SODC Status == false
return result E
else if (HFF Fuel Indicator Code is not null)

if (Current Fuel Flow ifecortf. SourceOfDataMassCode == "4" AND HFF Fuel Indicator Code o "E")

HFF Mass SODC Status == false
return result F

else if (Current Fuel Flow ifecortf.SourceOfDataMassCode in set {5, 6} AND HFF Fuel Indicator Code o "I")
HFF Mass SODC Status == false
return result G

Results:

Result	Response

A	You did not report a [fieldname] in the HFF record for FuelCode [fueled], but you

reported a [ratefieldname],

B	You reported a [fieldname] in the HFF record for FuelCode [fueled], but you did not

report a [ratefieldname],

C	You reported a SourceOfDataMassCode of [sodc] in the HFF record for FuelCode

[fueled], but you also reported a VolumetricFlowRate. The SourceOfDataMassCode
must be 2 when mass oil flow is calculated from volumetric oil flow.

D	You reported a SourceOfDataMassCode of 2 in the HFF record for FuelCode [fueled],

but you did not report a VolumetricFlowRate. The SourceOfDataMassCode should be 2
only when the mass oil rate is calculated from volumetric oil flow.

E	You reported a [fieldname] of 3 in the HFF record for FuelCode [fueled], but, according

to the qualification record in your monitoring plan, this is not a peaking unit.

F	You reported a [fieldname] of 4 in the HFF record for FuelCode [fueled], which

indicates that the fuel is an emergency fuel, but according to the Unit Fuel record in your
monitoring plan, this fuel is not an emergency fuel.

G	You reported a [fieldname] of [sodc] in the HFF record for FuelCode [fueled], which	Critical Error Level 1

indicates that the fuel is an igniter fuel, but according to the Unit Fuel record in your
monitoring plan, this fuel is not an igniter fuel.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Environmental Protection Agency

Page 190 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 191 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-7

Check Name:	Check Fuel Flow Monitoring System

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

HFF System Type = null
FuelFlowComponentRecords = null
CurrentAppendixDStalus = null

If {Current Fuel Flow ifecorrf.MonitoringSystemID is null)

If (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode in set {0, 9} OR (Current Fuel Group == "OIL" AND Current Fuel
Flow ifecortf.SourceOfDataMassCode in set {0, 9}))
return result A

else if (Legacy Data Evaluation == false AND (Current Fuel Flow Record.Soured )ll )ata Vol umctri cCodc in set {1,3} OR
(Current Fuel Group == "OIL" AND Current Fuel Flow itecortf.SourceOfDataMassCode in set {1, 3})))

return result B
else if (Current Fuel Group == "GAS")

HFF System Type = "GAS"
else if (Current Fuel Flow Record. VolumetricFlowRate is not null)

HFF System Type = "OILV"

else

HFF System Type = "OILM"

else

if (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode == "4")
return result C

else if (Current Fuel Group == "OIL" AND (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode in set {5,6} OR Current
Oil Fuel Flow ifecortf.SourceOfDataMassCode in set {5, 6}))
return result C

else

Current Mon Sys Record = find active MonitoringSystem record where

MonitoringSystemld = Current Fuel Flow itecortf.MonitoringSystemID

if Current Mon Sys Record is null
return result D

else if (Current Fuel Group == "GAS" AND Current Mon Sys Record. SystemTypeCode o "GAS")
return result E

else if (Current Fuel Group == "OIL" AND Current Mon Sy5 7?ecorrf.SystemTypeCode not in set {OILV, OILM})
return result F

else if (Current Fuel Group == "OIL" AND Current Oil Fuel Flow ifecortf.SourceOfDataMassCode == "2" AND Current
Mon Sys Record.SystemTypeCode o "OILV")
return result G

else

HFF System Type = Current Mon Sys Record. SystemTypeCode

if Current Mon Sys Record.FuelCode is not null and is not equal to Current Fuel Flow Record.FuelCode
HFF System Fuel = Current Mon Sys Record.FuelCode
return result H

else if (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode in set (0,9} OR (Current Fuel Group == "OIL"
AND Current Fuel Flow ifecortf.SourceOfDataMassCode in set {0,9}))

if (Current Fuel Group = "OIL")

Locate MonitorSystemComponentRecordsByHourLocation where the SystemID is equal to
CurrentFuelFlowRecord.SystemID and the ComponentTypeCd = "OFFM" or "BOFF"

For each retrieved record found:

Environmental Protection Agency

Page 192 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (Monitor SystemComponentRecordsByHourLocation.ComponentTypeCd ==

"OFFM")

Add the MonitorSystemComponentRecordsByHourLocation record to
FuelFlowComponentRecords.

If none were found,

return result I.

else if (Current Fuel Group = "GAS")

Locate MonitorSystemComponentRecordsByHourLocalion where the SystemID is equal to
CurrentFuelFlowRecord.SystemID and the ComponentTypeCd = "GFFM" or "BGFF"

For each retrieved record found:

If (Monitor SystemComponentRecordsByHourLocation.ComponentTypeCd ==

"GFFM")

Add the MonitorSystemComponentRecordsByHourLocation record to
FuelFlowComponentRecords.

If none were found,

return result I.

Environmental Protection Agency

Page 193 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B

D

E
F
G

H

Response

You reported a SourceOfDataVolumetricCode or SourceOfDataMassCode in the HFF
record for FuelCode [fueled], indicating the use of a fuel flowmeter system, but you did
not report its MonitoringSystemlD.

You reported a SourceOfDataVolumetricCode or SourceOfDataMassCode in the HFF
record for FuelCode [fueled] that indicates the use of substitute data, but you did not
report a MonitoringSystemlD. This was not required for legacy EDR data, but for
ECMPS, you should report the primary MonitoringSystemlD of the fuel flowmeter
system that normally records the flow for this fuel.

You reported a SourceOfDataVolumetricCode or SourceOfDataMassCode in the F1FF
record for FuelCode [fueled] that indicates the use of an emergency or igniter fuel, so
you should not have reported a MonitoringSystemlD in this record.

You reported MonitoringSystemlD [ID] in the FtFF record for FuelCode [fueled], but
there is no MonitorSystem record for this system in your monitoring plan that was active
during the hour.

You reported MonitoringSystemlD [ID] in the HFF record for FuelCode [fueled], but
this system is not a GAS monitoring system.

You reported MonitoringSystemlD [ID] in the HFF record for FuelCode [fueled], but
this system is not an OILM or OILV monitoring system.

You reported a SourceOfDataMassCode of 2 in the HFF record for FuelCode [fueled],
indicating that you are calculating mass oil rate from volumetric oil flow, but
MonitoringSystemlD [ID] is not an OILV monitoring system.

Your reported MonitoringSystemlD [ID] in the HFF record for FuelCode [fueled], but
the FuelCode for this system in the MonitorSystem record is [sysfuel]. The FuelCode in
the Monitor System record should be the same as the FuelCode in the HFF record.
You did not report any active fuel flowmeter components in your monitoring plan for
MonitoringSystemlD [ID]. The QA status for Appendix D testing for this system will
not be evaluated.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 194 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-8

Check Name:

Check Volumetric Units of Measure

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

HFF UOM Status = true

If (Current Fuel Flow Record. VolumetricUnitsOfMeasureCode is null)
If (Current Fuel Flow Record. VolumetricFlowRate is not null)

If (Current Fuel Flow Record. VolumetricFlowRate is null)

HFF UOM Status = false
return result B

else if (Current Fuel Group == "OIL" AND Current Fuel Flow Record VolumetricUnitsOfMeasureCode is not in set {"GALHR",

"BBLHR", "M3HR", "SCFH"})

HFF UOM Status = false
return result C

else if (Current Fuel Group == "GAS" AND Current Fuel Flow Record VolumetricUnitsOfMeasureCode o "HSCF")
HFF UOM Status = false
return result C

HFF UOM Status = false
return result A

else

Results:

Result
A

Response

You did not report a [fieldname] in the HFF record for FuelCode [fueled], but you
reported a [ratefieldname].

You reported a [fieldname] in the HFF record for FuelCode [fueled], but you did not
report a [ratefieldname].

The VolumetricUnitsOfMeasureCode reported in the HFF record for FuelCode [fueled]
is invalid.

Severity

Critical Error Level 1

B

Critical Error Level 1

C

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 195 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-9

Check Name:	Check Fuel in HFF Record

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

HFF Fuel Indicator Code = null

Locate active UnitFuel record for the location

where FuelCd = Current Fuel Flow ifecorrf.UnitFuelCd

If found,

HFF Fuel Indicator Code = Current Fuel Flow ifecorrf.IndicatorCd

else

return result A

Results:

Result	Response	Severity

A	You did not report an active Unit Fuel record for FuelCode [fueled] in your monitoring	Critical Error Level 1

plan.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 196 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-10

Check Name:	Check Volumetric Flow in HFF Record

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

HFF Calc Volumetric Rate = null
HFF Max Heat Input for Volume = null

If (HFF System Type is not null AND HFF SOD Status == true AND HFF Mass SODC Status == true AND HFF UOM Status == true)
If (Current Fuel Flow Record. VolumetricFlowRate is null)

If (HFF System Type o "OILM")
return result A

else

If (HFF System Type == "OILM")
return result B

else if (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode == "4")

If (Current Entity Type is equal to "Unit")

Locate a Unit Capacity record for the location and hour.

If exactly one record is found, and the MaximumHourlyHeatlnputCapacity in the retrieved record is greater
than 0,

HFF Max Heat Input for Volume =

UnitCapacityByHourLocation.MaximumHouriyYLeatlnputCapacity

If (HFF GCV is not null)

If (Current Fuel Flow itecortf.MassFlowRate is null)

HFF Calc Volumetric Rate = HFF Max Heat Input for Volume I HFF GCV *
1000000, rounded to one decimal place.

else if (HFFDensity is not null)

HFF Calc Volumetric Rate = HFF Max Heat Input for Volume I HFF GCV I
HFF Density * 1000000, rounded to one decimal place.

else

return result M

else

If (Current Fuel Flow Record. VolumetricFlowRate <= 0)
return result E

else

HFF Calc Volumetric Rate = Current Fuel Flow Record. VolumetricFlowRate

else if (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode == "9"

If (Current Fuel Group == "GAS")

HFF Volumetric Default Parameter = "MNGF"

else

HFF Volumetric Default Parameter = "MNOF"

Count active Default Record for the location where

ParameterCode == HFF Volumetric Default Parameter
FuelCode == Current Fuel Flow Record.FuelCode
if (Count o 1)

Environmental Protection Agency	Page 197 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result C
else if {Default Record.DefaultValue <= 0)
return result D

else if (Deyaw/;,Recoraf.DefaultUnitsOfMeasureCode == Current Fuel Flow
ifecorrf.VolumetricUnitsOfMeasureCode)

HFF Calc Volumetric Rate = Default .Recorof.DefaultValue
If (Current Fuel Flow Record. VolumetricFlowRate <= 0)
return result E

else if (Current Fuel Flow Record. VolumetricFlowRate o HFF Calc Volumetric Rate)
return result F

else

If (Current Fuel Flow Record. VolumetricFlowRate <= 0)
return result E

else

return result G

else if Current Fuel Flow ifecorrf.MonitoringSystemID is not null)

If (Current Fuel Flow Record. VolumetricFlowRate <= 0)
return result E

else

If (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode o 3)

HFF Calc Volumetric Rate = Current Fuel Flow Record. VolumetricFlowRate

Count active System Fuel Flow Record for the system.

If (Count o 1)

return result H

else if (System Fuel Flow .Recoraf.MaximumFuelFlowRate <= 0)
return result I

else if (System Fuel Flow .Recoraf.SystemFuelFlowUOMCode == Current Fuel Flow
itecortf.VolumetricUnitsOfMeasureCode)

If (Current Fuel Flow itecortf.SourceOfDataVolumetricCode == 3)

HFF Calc Volumetric Rate = System Fuel Flow .Recoraf.MaximumFuelFlowRate
If Current Fuel Flow Record VolumetricFlowRate o HFF Calc Volumetric Rate)
return result J

else

If (HFF Calc Volumetric Rate > System Fuel Flow .Recoraf.MaximumFuelFlowRate
return result K

else

return result L

else

If (Current Fuel Flow Record. VolumetricFlowRate <= 0)
return result E

else

HFF Calc Volumetric Rate = Current Fuel Flow Record. VolumetricFlowRate

Environmental Protection Agency

Page 198 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

E
F

G

H

I

J

K

M

Usage:
1

Response

You did not report a VolumetricFlowRate in the HFF record for FuelCode [fueled],
which is required when using [systype] MonitoringSystemID [ID].

You reported a VolumetricFlowRate in the HFF record for FuelCode [fueled], which is
invalid when using an OILM system.

You did not report one and only one default record for [parameter] for FuelCode
[fueled] in your monitoring plan that was active during current hour.

The DefaultValue reported in the active [parameter] default record for the hour is
invalid.

The VolumetricFlowRate reported in the HFF record for FuelCode [fueled] is invalid.
You reported a SourceOfDataVolumetricCode of [sodc] in the HFF record for FuelCode
[fueled], but the VolumetricFlowRate is not equal to the fuel flow rate defined in the
active [parameter] default record in your monitoring plan.

The VolumetricUnitsOfMeasureCode in the HFF record for FuelCode [fueled] is not the
same as the DefaultUnitsOfMeasureCode in the active [parameter] default record in
your monitoring plan.

You did not report one and only one active SystemFuelFlow record for
MonitoringSystemID [ID] in your monitoring plan for the hour.
The MaximumFuelFlowRate reported in the active System Fuel Flow record for
MonitoringSystemID [ID] in your monitoring plan is invalid.

You reported a SourceOfDataVolumetricCode of 3 in the HFF record for FuelCode
[fueled], but the VolumetricFlowRate is not equal to the MaximumFuelFlowRate
specified in the active System Fuel Flow record for MonitoringSystemID [ID] in your
monitoring plan.

Warning: The VolumetricFlowRate reported in the HFF record for FuelCode [fueled]
exceeds the MaximumFuelFlowRate specified in the active System Fuel Flow record for
MonitoringSystemID [ID] in your monitoring plan. Sources are required to periodically
(at least once annually) evaluate the appropriateness of these maximum values in the
monitoring plan and make proper adjustments when necessary. You should investigate
the cause of these exceedances and determine whether an adjustment to your monitoring
systems or monitoring plan is necessary.

The VolumetricUnitsOfMeasureCode in the HFF record for FuelCode [fueled] is not the
same as the SystemFuelFlowUOMCode in the active System Fuel Flow record for
MonitoringSystemID [ID] in your monitoring plan.

You did not report one and only one valid active Unit Capacity record in your
monitoring plan for the unit for the hour.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Informational Message

Critical Error Level 1

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 199 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-11

Check Name:	Check Mass Oil Flow in HFF Record

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

HFF Calc Mass Oil Rate = null
HFF Max Heat Input for Mass = null

If (HFF System Type is not null AND HFF SOD Status == true AND HFF Mass SODC Status == true AND HFF UOM Status == true)
If (Current Fuel Flow ifecortf.MassFlowRate is null)

If (HFF System Type == "OILM")

return result A
Else if (HFF System Type == "OILV"

If (Current Fuel Flow ifecortf.SourceOfDataMassCode == "2")

return result B
Else if (Current Unit is ARP == true)
return result C

else

If (HFFSystem Type == "GAS")

return result D
else if (HFF System Type == "OILV")

If (Current Fuel Flow ifecortf.SourceOfDataMassCode == "2" AND Current Fuel Flow itecortf.MassFlowRate

<=0)

return result E

else if (Current Fuel Flow ifecortf.SourceOfDataMassCode == "4")

If (Current Entity Type is equal to "Unit")

Locate a Unit Capacity record for the location and hour.

If exactly one record is found, and the MaximumHourlyHeatlnputCapacity in the retrieved record is greater
than 0,

HFF Max Heat Input for Mass =

UnitCapacityByHourLocation.MaximumHouriyYLeatlnputCapacity

If (HFF GCV is not null)

HFF Calc Mass Oil Rate = HFF Max Heat Input for Mass / HFF GCV * 1000000,
rounded to one decimal place.

else

return result M

If (Current Fuel Flow ifecortf.MassFlowRate <= 0)
return result E

else

HFF Calc Mass Oil Rate = Current Fuel Flow ifecortf.MassFlowRate

else if (Current Fuel Flow ifecortf.SourceOfDataMassCode == "9")

HFF Mass Oil Default Parameter = "MNOF"

Count active Default Record for the location where

ParameterCode == HFF Mass Oil Default Parameter
FuelCode == Current Fuel Flow Record.FuelCode
if (Count o 1)

return result F

else if (Default Record.DefaultValue <= 0 OR Default .Recorof.DefaultUnitsOfMeasureCode o "LBHR")
return result G

Environmental Protection Agency

Page 200 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

HFF Calc Mass Oil Rate = Default .Recorof.DefaultValue
If (Current Fuel Flow ifecortf.MassFlowRate <= 0)
return result E

else if (Current Fuel Flow ifecoraJ MassFlowRate o HFF Calc Mass Oil Rate)
return result H

else if (Current Fuel Flow ifecorrf.MonitoringSystemID is not null)

If (Current Fuel Flow ifecortf.MassFlowRate <= 0)
return result E

else

If (Current Fuel Flow ifecortf.SourceOfDataMassCode o 3)

HFF Calc Mass Oil Rate = Current Fuel Flow ifecortf.MassFlowRate

Count active System Fuel Flow Record for the system.

If (Count o 1)

return result I

else if (System Fuel Flow .Recoraf.MaximumFuelFlowRate <= 0 OR System Fuel Flow
Record. SystemFuelFlowUOMCode o "LBHR")
return result J

else

If (Current Fuel Flow itecortf.SourceOfDataMassCode == 3)

HFF Calc Mass Oil Rate = System Fuel Flow .Recorof.MaximumFuelFlowRate
If (Current Fuel Flow itecoraJ MassFlowRate o HFF Calc Mass Oil Rate)
return result K

else

If (HFF Calc Mass Oil Rate > System Fuel Flow .Recoraf.MaximumFuelFlowRate
return result L

else

If (Current Fuel Flow ifecortf.MassFlowRate <= 0)
return result E

else

HFF Calc Mass Oil Rate = Current Fuel Flow ifecortf.MassFlowRate

Environmental Protection Agency

Page 201 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

E
F

G

H

I
J

K

M

Usage:
1

Response

You did not report a [fieldname] in the HFF record for FuelCode [fueled], but the
MonitoringSystemID [ID] is an [systype] fuel flow system.

You reported a SourceOfDataMassCode of 2 in the HFF record for FuelCode [fueled],
which indicates that the mass oil rate was calculated from the volumetric oil rate, but
you did not report a MassFlowRate in the record.

You did not report a [fieldname] in the FtFF record for FuelCode [fueled], but this value
is required for an ARP unit.

You reported a MassFlowRate in the FtFF record for FuelCode [fueled]. This value
should be blank for a gas fuel.

The MassFlowRate reported in the FtFF record for FuelCode [fueled] is invalid.

You did not report one and only one default record for [parameter] for FuelCode
[fueled] in your monitoring plan that was active during current hour.

The DefaultValue or DefaultUnitsOfMeasureCode reported in the active [parameter]
default record for the hour is invalid.

You reported a SourceOfDataMassCode of [sodc] in the FtFF record for FuelCode

[fueled], but the MassFlowRate is not equal to the fuel flow rate defined in the active

[parameter] default record in your monitoring plan.

You did not report one and only one active SystemFuelFlow record for

MonitoringSystemID [ID] in your monitoring plan for the hour.

The MaximumFuelFlowRate or SystemFuelFlowUOMCode reported in the active

System Fuel Flow record for MonitoringSystemID [ID] in your monitoring plan is

invalid.

You reported a SourceOfDataMassCode of 3 in the HFF record for FuelCode [fueled],
but the MassFlowRate is not equal to the MaximumFuelFlowRate specified in the active
System Fuel Flow record for MonitoringSystemID [ID] in your monitoring plan.
Warning: The MassFlowRate reported in the HFF record for FuelCode [fueled] exceeds
the MaximumFuelFlowRate specified in the active System Fuel Flow record for
MonitoringSystemID [ID] in your monitoring plan. Sources are required to periodically
(at least once annually) evaluate the appropriateness of these maximum values in the
monitoring plan and make proper adjustments when necessary. You should investigate
the cause of these exceedances and determine whether an adjustment to your monitoring
systems or monitoring plan is necessary.

You did not report one and only one valid active Unit Capacity record in your
monitoring plan for the unit for the hour.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Informational Message

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 202 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-12

Check Name:	Determine Density

Related Former Checks:

Applicability:	Appendix D Check

Description:

Validation Tables:

Fuel Type Reality Checks for Density (Cross Check Table)
Fuel Type Warning Levels for Density (Cross Check Table)
Table D-6 Missing Data Values (Cross Check Table)

Specifications:

HFF Density = null
Current Density Record = null

Count the Hourly ParamFuelFlow record where

Hourly ParamFuelFlow.HourlyFuelFlowID = Current Fuel Flow ifecortf.HourlyFuelFlowID AND
HourlyParamFuelFlow.ParameterCode = "DENSOIL"

If (Count >1)

return result A

Else If (Count == 0)

If {HFF System Type == "OILV" and Current Fuel Flow ifecortf.SourceOfDataMassCode == "2")
return result B

Else if (HFF System Type = "OILV" AND Current Fuel Flow ifecortf.SourceOfDataMassCode == "2")

Current Density Record = matching record
Density UOM= Current Density ifecortf.ParameterUOMCode

if (Density UOM not in set {LBGAL, LBBBL, LBM3, LBSCF})
return result C

else if (Current Fuel Flow Record. VolumetricUnitsOfMeasureCode == "GALHR" AND Density UOM o "LBGAL")
return result D

else if (Current Fuel Flow Record. VolumetricUnitsOfMeasureCode == "BBLHR" AND Density UOM o "LBBBL")
return result D

else if (Current Fuel Flow Record. VolumetricUnitsOfMeasureCode == "M3HR" AND Density UOM o "LBM3")
return result D

else if (Current Fuel Flow Record. VolumetricUnitsOfMeasureCode == "SCFH" AND Density UOM o "LBSCF")

return result D
else if (Current Density ifecorrf.ParamValFuel > 0)

Density Default = null

If (Current Density ifecorrf.SampleTypeCode == 8)

Density Default = Lookup "MissingDataValue" in "Table D-6 Missing Data Values"

where "Parameter" column = "DENSOIL - " + Density UOM AND "FuelCode" column = Current Fuel
Flow ifecorrf.FuelCode

If (Density Default == null)

Max Expected Density = Lookup "Upper Value" in "Fuel Type Warning Levels for Density Cross Check Table"

where "Fuel Code - Units Of Measure" column = concatenation of (Current Fuel Flow itecortf.FuelCode,
" - ", Density UOM)

Min Expected Density = Lookup "Lower Value" in "Fuel Type Warning Levels for Density Cross Check Table"

where "Fuel Code - Units Of Measure" column = concatenation of (Current Fuel Flow itecortf.FuelCode,
" - ", Density UOM)

Max Allowed Density = Lookup "Upper Value" in "Fuel Type Reality Checks for Density Cross Check Table"

where "Fuel Code - Units Of Measure" column = concatenation of (Current Fuel Flow itecortf.FuelCode,
" - ", Density UOM)

Environmental Protection Agency

Page 203 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Min Allowed Density = Lookup "Lower Value" in "Fuel Type Reality Checks for Density Cross Check Table"

where "Fuel Code - Units Of Measure" column = concatenation of (Current Fuel Flow itecortf.FuelCode,
" - ", Density UOM)

if {Max Allowed Density is not null AND Current Density ifecortf.ParamValFuel > Max Allowed Density) OR
{Min Allowed Density is not null AND Current Density ifecortf.ParamValFuel < Min Allowed Density)
return result E

else

HFF Density = Current Density itecortf.ParamValFuel

if {Min Expected Density is not null AND HFF Density < Min Expected Density) OR {Max Expected
Density is not null AND HFF Density > Max Expected Density)
return result F

else

if {Density Default == Current Density itecortf.ParamValFuel)

HFF Density = Current Density itecortf.ParamValFuel

else

return result G

else

return result H

else

return result I

Results:

Result
A

B
C

D

E
F
G

H
I

Usage:

1

Response

You reported more than one HPFF record for [parameter] for FuelCode [fueled] for the
hour.

You did not report an HPFF record for [parameter] for FuelCode [fueled] for the hour.
The ParameterUOMCode reported in the HPFF record for DENSOIL for FuelCode
[fueled] is missing or invalid.

The ParameterUOMCode reported in the HPFF record for DENSOIL for FuelCode
[fueled] is inconsistent with the VolumetricUnitsOfMeasureCode reported in the
associated HFF record.

The ParameterValueForFuel reported in the HPFF record for [parameter] for FuelCode
[fueled] is outside the range of allowable values for the fuel type.
The ParameterValueForFuel reported in the HPFF record for [parameter] for FuelCode
[fueled] is outside the range of expected values for the fuel type.

You reported a SampleTypeCode of 8 in the HPFF record for [parameter] for FuelCode
[fueled], indicating the use of a Table D-6 default, but the ParameterValueForFuel does
not equal the default value for the fuel.

The ParameterValueForFuel reported in the HPFF record for [parameter] for FuelCode
[fueled] is invalid. The value should be greater than 0.

You reported an HPFF record for [parameter] for FuelCode [fueled], but this value is
only appropriate when using an OILV system and a SourceOfDataMassCode equal to 2.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 2
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 204 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-13

Check Name:	Check Density Sample Type

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current Density Record is not null)

If Current Density ifecorrf.SampleTypeCode not in {1, 2, 5, 6, 7, 8}
return result A

Results:

Result	Response	Severity

A	The SampleTypeCode reported in the HPFF record for DENSOIL for FuelCode [fueled]	Critical Error Level 1

is missing or invalid.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 205 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-14

Check Name:

Check Extraneous Density Record Fields

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Hourly Extraneous Fields = null

If (Current Density Record is not null)

If (Current Density ifecorrf.Formulaldentifier is not null)

append "Formulaldentifier" to Hourly Extraneous Fields
If (Current Density ifecorrf.MonitoringSystemID is not null)

append "MonitoringSystemID" to Hourly Extraneous Fields
If (Current Density ifecortf.SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields
If (Current Density ifecorrf.OperatingConditionCode is not null)

append "OperatingConditionCode" to Hourly Extraneous Fields

If (Hourly Extraneous Fields is not null)
return result A

Results:

Result
A

Response

You reported [fieldnames] in the HPFF record for DENSOIL for FuelCode [fueled].
This data should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 206 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-15

Check Name:

Calculate Mass Oil Flow

Related Former Checks:

Applicability:

Appendix D Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

IfHFF Calc Volumetric Flow is not null AND HFFDensity is not null)

HFF Calc Mass Oil Flow = HFF Density * HFF Calc Volumetric Flow, and round the result to one decimal place (0.1)

Flow Rate Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "OILM" AND
UOM = "LBHR"

If (Current Fuel Flow ifecortf.MassFlowRate > 0)

if (ABS{Current Fuel Flow Record.MassFlowRate - HFF Calc Mass Oil Flow) > Flow Rate Tolerance)

return result A

Results:

Result
A

Response

The MassFlowRate reported in the HFF record for Fuel Code [fueled] is inconsistent
with the value calculated from the VolumetricFlowRate and density.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 207 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-16

Check Name:	Determine GCV

Related Former Checks:

Applicability:	Appendix D Check

Description:

Validation Tables:

Fuel Type Reality Checks for GCV (Cross Check Table)

Fuel Type Warning Levels for GCV (Cross Check Table)

Table D-6 Missing Data Values (Cross Check Table)

Specifications:

HFF GCV = null
Current GCV Record = null

Count the Hourly ParamFuelFlow record where

Hourly ParamFuelFlow.HourlyFuelFlowID = Current Fuel Flow ifecortf.HourlyFuelFlowID AND
Hourly ParamFuelFlow.ParameterCode = "GCV"

If (Count >1)

return result A
Else If (Count == 0)

If (Current HI HPFFRecord is not null)
return result B
Else if (Current HI HPFF Record is not null)

Current GCV Record = matching record

GCV UOM = Current GCFifecortf.ParameterUOMCode

if (GCVUOMnot in set {BTUGAL, BTUBBL, BTUM3, BTUSCF, BTULB, BTUHSCF}
return result C

else if (Current Fuel Group == "GAS" AND GCV UOM o "BTUHSCF")
return result D

else if (Current Fuel Group == "OIL" AND Current Fuel Flow ifecortf.MassFlowRate is not null AND GCV UOM o "BTULB")
return result D

else if (Current Fuel Group == "OIL" AND Current Fuel Flow ifecortf.MassFlowRate is null AND Current Fuel Flow
Record:VolumetricUnitsOfMeasureCode == "GALHR" AND GCV UOM o "BTUGAL")
return result D

else if (Current Fuel Group == "OIL" AND Current Fuel Flow ifecortf.MassFlowRate is null AND Current Fuel Flow
Record.VolumetricUnitsOfMeasureCode == "BBLHR" AND GCVUOMo "BTUBBL")
return result D

else if (Current Fuel Group == "OIL" AND Current Fuel Flow ifecortf.MassFlowRate is null AND Current Fuel Flow
Record. VolumetricUnitsOfMeasureCode == "M3HR" AND GCV UOM o "BTUM3")
return result D

else if (Current Fuel Group == "OIL" AND Current Fuel Flow ifecortf.MassFlowRate is null AND Current Fuel Flow
ifecorrf.VolumetricUnitsOfMeasureCode == "SCFH" AND GCVUOMo "BTUSCF")

return result D
else if (Current GCFifecortf.ParamValFuel > 0)

GCV Default = null

If (Current GCFitecortf.SampleTypeCode == 8)

GCV Default = Lookup "MissingDataValue" in "Table D-6 Missing Data Values"

where "Parameter" column = "GCV - " + GCV UOM AND "FuelCode" column = Current Fuel Flow
Record F uelCode

If (GCVDefault == null)

GCV Default = Lookup "MissingDataValue" in "Table D-6 Missing Data Values"

where "Parameter" column = "GCV - " + GCV UOM and FuelCode column is null.

Environmental Protection Agency

Page 208 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (GCV Default == null)

Max Expected GCV= Lookup "Upper Value" in "Fuel Type Warning Levels for GCV Cross Check Table"

where "Fuel Code - Units Of Measure" column = concatenation of (Current Fuel Flow itecortf.FuelCode,

" - GCVUOM)

Min ExpectedGCV= Lookup "Lower Value" in "Fuel Type Warning Levels for GCV Cross Check Table"

where "Fuel Code - Units Of Measure" column = concatenation of (Current Fuel Flow itecortf.FuelCode,

" - GCVUOM)

Max Allowed GCV= Lookup "Upper Value" in "Fuel Type Reality Checks for GCV Cross Check Table"

where "Fuel Code - Units Of Measure" column = concatenation of (Current Fuel Flow itecortf.FuelCode,

" - GCVUOM)

Min Allowed GCV= Lookup "Lower Value" in "Fuel Type Reality Checks for GCV Cross Check Table"

where "Fuel Code - Units Of Measure" column = concatenation of (Current Fuel Flow itecortf.FuelCode,

" - GCVUOM)

if {Max Allowed GCV is not null AND Current GCFitecortf.ParamValFuel > Max Allowed GCV) OR (Min
Allowed GCV is not null AND Current GCVifecortf.ParamValFuel  Max Expected GCV)
return result F

else

If (Current GCFifecortf.ParamValFuel is not rounded to one decimal place)
return result J

else if (GCV Default == Current GCVifecorrf.ParamValFuel)

HFF GCV = Current GCFiJecortf.ParamValFuel

else

return result G

else

return result Ft

else

return result I

Environmental Protection Agency

Page 209 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B
C

D

E
F
G

H

I

J

Usage:

1

Response

You reported more than one HPFF record for [parameter] for FuelCode [fueled] for the
hour.

You did not report a FtPFF record for GCV for FuelCode [fueled] for the hour.
The ParameterUOMCode reported in the FtPFF record for GCV for FuelCode [fueled]
is missing or invalid.

The ParameterUOMCode reported in the FtPFF record for GCV for FuelCode [fueled]
is inconsistent with the fuel flow units of measure.

The ParameterValueForFuel reported in the FtPFF record for [parameter] for FuelCode
[fueled] is outside the range of allowable values for the fuel type.
The ParameterValueForFuel reported in the FtPFF record for [parameter] for FuelCode
[fueled] is outside the range of expected values for the fuel type.

You reported a SampleTypeCode of 8 in the FtPFF record for [parameter] for FuelCode
[fueled], indicating the use of a Table D-6 default, but the ParameterValueForFuel does
not equal the default value for the fuel.

The ParameterValueForFuel reported in the FtPFF record for GCV for FuelCode
[fueled] is invalid. The value must be greater than 0.

You reported an FtPFF record for GCV for FuelCode [fueled], but you have not reported
an FtPFF record for Ftt for the hour.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Non-Critical Error

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Ftourly Fuel Flow

Environmental Protection Agency

Page 210 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-17

Check Name:

Check GCV Sample Type

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

If (Current GCV Record is not null)

If (Current Fuel Group == "OIL" AND Current GCFitecortf.SampleTypeCode not in {1,2, 5, 6, 7, 8})
return result A

else if (Current Fuel Group == "GAS" AND Current GCFifecortf.SampleTypeCode not in {0,2, 3, 4, 6, 7, 8})
return result A

Results:

Result
A

Response

The SampleTypeCode reported in the HPFF record for GCV for FuelCode [fueled] is
missing or invalid.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 211 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-18

Check Name:

Check Extraneous GCV Record Fields

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Hourly Extraneous Fields = null

If (Current GCV Record is not null)

If (Current GCFitecortf.Formulaldentifier is not null)

append "Formulaldentifier" to Hourly Extraneous Fields
If (Current GCVitecortf.MonitoringSystemID is not null)

append "MonitoringSystemID" to Hourly Extraneous Fields
If (Current GCVitecortf.SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields
If (Current GCVitecortf.OperatingConditionCode is not null)

append "OperatingConditionCode" to Hourly Extraneous Fields

If (Hourly Extraneous Fields is not null)
return result A

Results:

Result
A

Response

You reported [fieldnames] in the HPFF record for GCV for FuelCode [fueled]. This
data should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 212 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-19

Check Name:

Validate Heat Input Record

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Current HI HPFF Record = null

Count the HourlyParamFuelFlow record where

HourlyParamFuelFlow.HourlyFuelFlowID = Current Fuel Flow ifecortf.HourlyFuelFlowID AND
HourlyParamFuelFlow.ParameterCode = "HI"

If (Count >1)

HI App D Accumulator = -1
return result A

Else If (Count == 0)

If (Heat Input App D Method Active For Hour == true)

HI App D Accumulator = -1
return result B

Else if (Heat Input App D Method Active For Hour == true)

Current HI HPFF Record = matching record

Cur HIMon Formula Record = Lookup active formula in MonitoringFormula Table where
MonitoringFormulalD = Current III 11 I'll' Record Moni tori nglorm ul all)

if (Cur HIMon Formula Record is null)
return result D

else if {Cur HIMon Formula Record.ParameterCode o "HI")
return result E

else if (Current Fuel Group == "GAS")

If (Cur HIMon Formula .Recorof.EquationCode not in set {D-6, F-20})
return result F

else if (Current Fuel Flow ifecortf.MassFlowRate is not null)

If (Cur HIMon Formula Record.EquationCode not in set {D-8, F-19})
return result F

if (Current HI HPFF Record.MonitonngFormuiald is null
return result C

else

else

If (Cur HIMon Formula Record.EquationCode <> "F-19V")
return result F

else

return result G

Environmental Protection Agency

Page 213 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B
C
D

E

F

G

Response

You reported more than one HPFF record for [parameter] for FuelCode [fueled] for the
hour.

You did not report an HPFF record for [parameter] for FuelCode [fueled] for the hour.
You did not report a FormulalD in the FtPFF record for HI for FuelCode [fueled].
You reported FormulalD [ID] in the FtPFF record for Ftt for FuelCode [fueled], but
there is no active Formula record for this formula in your monitoring plan.

You reported FormulalD [ID] in the FtPFF record for HI for FuelCode [fueled], but this
is not an HI formula.

The FormulaCode of FormulalD [ID] reported in the FtPFF record for HI for FuelCode
[fueled] is invalid.

You reported an HPFF record for GCV for FuelCode [fueled], but you have not reported
an HPFF record for HI for the hour.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 214 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-20

Check Name:

Check Extraneous Heat Input Record Fields

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Hourly Extraneous Fields = null

If (Current HIHPFFRecord is not null)

If {Current HI HPFF ifecorrf.MonitoringSystemID is not null)

append "MonitoringSystemID" to Hourly Extraneous Fields
If (Current HI HPFF ifecortf.SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields
If (Current HI HPFFRecord.OpemtingConditionCode is not null)

append "OperatingConditionCode" to Hourly Extraneous Fields
If (Current HI HPFF ifecorrf.SampleTypeCode is not null)

append "SampleTypeCode" to Hourly Extraneous Fields

If (Hourly Extraneous Fields is not null)
return result A

Results:

Result
A

Response

You reported [fieldnames] in the HPFF record for HI for FuelCode [fueled]. This data
should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 215 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-21

Check Name:	Calculate Heat Input Rate

Related Former Checks:

Applicability:	Appendix D Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

HFF Calc HI Rate = null

If (Current HIHPFFRecord is not null)

if (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode == "4")
if {HFF Max Heat Input for Volume is not null)

HFF Calc HI Rate = HFF Max Heat Input for Volume

else

HI App D Accumulator = -1
return result A

else if (Current Fuel Flow ifecortf.SourceOfDataMassCode == "4")
if {HFF Max Heat Input for Mass is not null)

HFF Calc HI Rate = HFF Max Heat Input for Mass

else

HI App D Accumulator = -1
return result A

else if {HFF GCV is not null)

HI HPFF Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "HI HPFF" AND
UOM = "MMBTUHR"

If {HFFSystem Type == "GAS" OR Current Fuel Flow itecortf.MassFlowRate is null)

If {HFF Calc Volumetric Rate is not null)

HFF Calc HI Rate = HFF Calc Volumetric Rate * HFF GCV I 1000000, and round the result to one
decimal place.

else

HI App D Accumulator = -1
return result A

if {HFF Calc Mass Oil Rate is not null)

HFF Calc HI Rate = HFF Calc Mass Oil Rate * HFF GCV I 1000000, and round the result to one
decimal place.

else

HI App D Accumulator = -1
return result A

If {HFF Calc HI Rate is not null)

If Current Fuel Flow itecortf.FuelUsageTime > 0 AND Current Fuel Flow ifecorrf.FuelUsageTime <= 1 AND HI App D
Accumulator >= 0)

11 Note - this accumulates totals for all Fuel flow records and does not work like a normal parameter
HI App D Accumulator = HI App D Accumulator + HFF Calc HI Rate * Current Fuel Flow
ifecorrf.FuelUsageTime

Environmental Protection Agency

Page 216 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

HI App D Accumulator = -1
If (Current HI HPFFifecortf.ParamValFuel > 0)

If (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode == "4" OR Current Fuel Flow
ifecortf.SourceOfDataMassCode == "4")

if (HFF Calc HI Rate is equal to Current III If I'll' Record. Param Vall ucl)

if (Current Fuel Flow itecortf.SourceOfDataVolumetricCode == "4")

If (Current Fuel Flow Record. VolumetricFlowRate is greater than 0, AND
HFF Calc Volumetric Rate is not equal to Current Fuel Flow
Record. Volumetri cF lo wRate)

Flow Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions
Tolerances" where Parameter = "FOIL"

if (ABS(HFF Calc Volumetric Rate - Current Fuel Flow
Record. VolumetricFlowRate) > Flow Tolerance)
return result C

else

If (Current Fuel Flow itecortf.MassFlowRate is greater than 0, AND

HFF Calc Mass Oil Rate is not equal to Current Fuel Flow ifecortf.MassFlowRate)

Flow Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions
Tolerances" where Parameter = "FOIL"

if (ABS(HFF Calc Mass Oil Rate - Current Fuel Flow ifecortf.MassFlowRate)

> Flow Tolerance)

return result D

else

If (ABS (HFF Calc HI Rate - Current HI HPFF Record ParamValFuel) > HI HPFF Tolerance)
return result B

else

HI App D Accumulator = -1
return result A

Results:

Result
A

B

C

D

Response

The ParameterValueForFuel in the HPFF record for [parameter] for FuelCode [fueled]
could not be recalculated due to errors listed above.

The ParameterValueForFuel reported in the HPFF record for HI for FuelCode [fueled]
is inconsistent with the recalculated value.

You reported a SourceOfDataVolumetricCode of 4, indicating that you burned an
emergency fuel, but the VolumetricFlowRate in the HFF record for FuelCode [fueled] is
inconsistent with the maximum fuel flow rate for the unit. When you burn an emergency
fuel, you should report the maximum fuel flow rate, which is based on the maximum
hourly heat input capacity of the unit.

You reported a SourceOfDataMassCode of 4, indicating that you burned an emergency
fuel, but the MassFlowRate in the HFF record for FuelCode [fueled] is inconsistent with
the maximum fuel flow rate for the unit. When you burn an emergency fuel, you should
report the maximum fuel flow rate, which is based on the maximum hourly heat input
capacity of the unit.

Severity

Informational Message
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 217 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 218 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-22

Check Name:

Check Reported Heat Input

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

If (Current HIHPFFRecord is not null)

If (Current HI HPFF ifecortf.ParamValFuel >= 0

If (Current HI HPFFifecortf.ParamValFuel is not rounded to one decimal place)
return result D

else if (Current Fuel Flow ifecortf.SourceOfDataVolumetricCode == "4" and HFF Max Heat Input for Volume is not
null)

if (Current II! 11 I'll' Record. ParamValluel is not equal to HFF Max Heat Input for Volume)
return result E

else if (Current Fuel Flow ifecortf.SourceOfDataMassCode == "4" and HFF Max Heat Input for Mass is not null)
if (Current II! 11 I'll' Recur d. ParamValluel is not equal to HFF Max Heat Input for Mass)
return result F

else

If Current Entity Type == "CP",

Count active UnitCapacity record for each unit linked to the pipe
if (Count o 1 for any unit)
return result A

else

Calculate Max Heat Input as the sum of Unit Capacity
.Recorof.MaximumHourlyHeatlnputCapacity for all units.

Count active UnitCapacity record for the associated unit,
if (Count o 1)

return result A

else

Max Heat Input = Unit Capacity .Recoraf.MaximumHourlyHeatlnputCapacity

if Current II! III'l'l' Record. Param Val Fuel Unit Capacity .Recoraf.MaximumHourlyHeatlnputCapacity
return result B

else

else

return result C

Environmental Protection Agency

Page 219 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C
D

E

Usage:
1

Response

You did not report one and only one active Unit Capacity record in your monitoring
plan for the unit (or for each unit linked to the pipe) for the hour.

Warning: The ParameterValueForFuel reported in the HPFF record for HI for FuelCode
[fueled] exceeds the MaximumHourlyHeatlnputCapacity reported in the Unit Capacity
record in your monitoring plan. Sources are required to periodically (at least once
annually) evaluate the appropriateness of maximum values in the monitoring plan and
make proper adjustments when necessary. You should investigate the cause of these
exceedances and determine whether an adjustment to the

MaximumHourlyHeatlnputCapacity reported in your monitoring plan is necessary.
The ParameterValueForFuel reported in the HPFF record for HI for FuelCode [fueled]
is invalid. The value must be greater than or equal to 0.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

You reported a SourceOfDataVolumetricCode of 4 in the HFF record, indicating that
you burned an emergency fuel. However, you did not report the maximum hourly heat
input capacity for the unit as the ParameterValueforFuel in the HPFF record for HI,
which is required when you burn an emergency fuel.

You reported a SourceOfDataMassCode of 4 in the HFF record, indicating that you
burned an emergency fuel. However, you did not report the maximum hourly heat input
capacity for the unit as the ParameterValueforFuel in the HPFF record for HI, which is
required when you burn an emergency fuel.

Severity

Critical Error Level 1
Informational Message

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 220 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-23

Check Name:	Check Heat Input Units Of Measure

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current HIHPFFRecord is not null)

If (Current HI HPFF ifecortf.ParameterUOMCode o "MMBTUHR")
return result A

Results:

Result	Response	Severity

A	The ParameterUOMCode reported in the HPFF record for HI for FuelCode [fueled] is	Critical Error Level 1

missing or invalid. The value should be "MMBTUHR".

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 221 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-24

Check Name:

Validate S02 Record

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Current S02 HPFF Record = null
HFF S02 Equation Code = null

Count the HourlyParamFuelFlow record where

HourlyParamFuelFlow.HourlyFuelFlowID = Current Fuel Flow ifecortf.HourlyFuelFlowID AND
HourlyParamFuelFlow.ParameterCode = "S02"

If (Count >1)

S02 App D Accumulator = -1
return result A
Else If (Count == 0)

If (S02 App D Method Active For Hour == true)

S02 App D Accumulator = -1
return result B
Else if (S02 App D Method Active For Hour == true)

Current S02 HPFF Record = matching record

Cur S02 Mon Formula Record = Lookup active formula in MonitoringFormula Table where
MonitoringFormulalD = Current S02 Z/PFFifecortf.MonitoringFormulalD

if (Cur S02 Mon Formula Record is null)
return result D

else if {Cur S02 Mon Formula Record. ParameterCode o "S02")

return result E
else if (Current Fuel Group == "GAS")

If (Cur SO2 Mon Formula .Recoraf.EquationCode in set {D-4, D-5})

HFF S02 Equation Code = Cur SO2 Mon Formula .Recorof.EquationCode

else

return result F

if (Current S02 flPFFitecortf.MonitoringFormulald is null
return result C

else

else

If (Cur S02 Mon Formula .Recoraf.EquationCode == "D-2")

HFF S02 Equation Code = Cur SO2 Mon Formula .Recorof.EquationCode

else

return result F

else

return result G

Environmental Protection Agency

Page 222 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B
C
D

E

F

G

Usage:

1

Response

You reported more than one HPFF record for [parameter] for FuelCode [fueled] for the
hour.

You did not report an FtPFF record for [parameter] for FuelCode [fueled] for the hour.
You did not report a FormulalD in the FtPFF record for S02 for FuelCode [fueled].
You reported FormulalD [ID] in the FtPFF record for S02 for FuelCode [fueled], but
there is no active Formula record for this formula in your monitoring plan.
You reported FormulalD [ID] in the FtPFF record for S02 for FuelCode [fueled], but
this is not an S02 formula.

The FormulaCode of FormulalD [ID] reported in the FtPFF record for S02 for
FuelCode [fueled] is invalid.

You reported an FtPFF record for S02 for FuelCode [fueled], but you do not have an
active Appendix D S02 method for the hour.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 223 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-25

Check Name:

Check Extraneous S02 Record Fields

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Hourly Extraneous Fields = null

If (Current S02 HPFFRecord is not null)

If (Current S02 HPFFitecortf.MonitoringSystemID is not null)

append "MonitoringSystemID" to Hourly Extraneous Fields
If (Current S02 HPFFitecortf.SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields
If (Current S02 HPFFitecortf.OperatingConditionCode is not null)

append "OperatingConditionCode" to Hourly Extraneous Fields
If (Current S02 HPFFitecortf.SampleTypeCode is not null)

append "SampleTypeCode" to Hourly Extraneous Fields

If (Hourly Extraneous Fields is not null)
return result A

Results:

Result
A

Response

You reported [fieldnames] in the HPFF record for S02 for FuelCode [fueled]. This data
should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 224 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-26

Check Name:	Check S02 Units Of Measure

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current S02 HPFFRecord is not null)

If (Current S02 HPFFitecortf.ParameterUOMCode o "LBHR")
return result A

Results:

Result	Response	Severity

A	The ParameterUOMCode reported in the HPFF record for S02 for FuelCode [fueled] is	Critical Error Level 1

missing or invalid. The value should be "LBHR".

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 225 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-27

Check Name:	Calculate S02 Mass Rate

Related Former Checks:

Applicability:	Appendix D Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

HFF Calc S02 = null

If (Current S02 HPFFRecord is not null)

if (Current Fuel Group == "GAS" AND HFF S02 Equation Code == "D-4" AND HFF Sulfur is not null AND HFF Calc
Volumetric Rate is not null

S02 HPFF Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "S02 Gas HPFF" AND
UOM = "LBHR"

HFF Calc S02 = HFF Sulfur * HFF Calc Volumetric Rate 4 2.0 / 7000, and round the result to 5 decimal places.

else if (Current Fuel Group == "GAS" AND HFFS02 Equation Code == "D-5" AND HFFS02 Emission Rate is not null AND
HFF Calc HI Rate is not null

S02 HPFF Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "S02 Gas HPFF" AND
UOM = "LBHR"

HFF Calc S02 = HFF S02 Emission Rate * HFF Calc HI Rate, and round the result to 5 decimal places.

else if (Current Fuel Group == "OIL" AND HFF Sulfur is not null AND HFF Calc Mass Oil Rate is not null

S02 HPFF Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "S02 Oil HPFF" AND
UOM = "LBHR"

HFF Calc S02 = HFF Sulfur * HFF Calc Mass Oil Rate * 2.0 / 100, and round the result to 1 decimal place.

If {HFF Calc S02 is not null)

If Current Fuel Flow itecortf.FuelUsageTime > 0 AND Current Fuel Flow ifecorrf.FuelUsageTime <= 1 AND S02 App
D Accumulator >= 0)

11 Note - this accumulates totals for all Fuel flow records and does not work like a normal parameter
S02 App D Accumulator = S02 App D Accumulator + HFF Calc S02 * Current Fuel Flow
ifecorrf.FuelUsageTime

else

S02 App D Accumulator = -1

If (Current S02 HPFF itecortf.ParamValFuel >= 0)

if (ABS {HFF Calc S02 - Current S02 HPFF Record ParamValFuel) > SO2 HPFF Tolerance)
return result A

else

S02 App D Accumulator = -1
return result B

Environmental Protection Agency

Page 226 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

Response

The ParameterValueForFuel reported in the HPFF record for S02 for FuelCode [fueled]
is inconsistent with the recalculated value.

The ParameterValueForFuel in the FtPFF record for [parameter] for FuelCode [fueled]
could not be recalculated due to errors listed above.

Severity

Critical Error Level 1
Informational Message

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Ftourly Fuel Flow

Environmental Protection Agency

Page 227 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-28

Check Name:	Determine Sulfur Content

Related Former Checks:

Applicability:	Appendix D Check

Description:

Validation Tables:

Fuel Type Reality Checks for Sulfur (Cross Check Table)

Fuel Type Warning Levels for Sulfur (Cross Check Table)

Table D-6 Missing Data Values (Cross Check Table)

Specifications:

HFF Sulfur = null
Current Sulfur Record = null

Count the Hourly ParamFuelFlow record where

Hourly ParamFuelFlow.HourlyFuelFlowID = Current Fuel Flow ifecortf.HourlyFuelFlowID AND
HourlyParamFuelFlow.ParameterCode = "SULFUR"

If (Count >1)

return result A
Else If (Count == 0)

If {HFFS02 Equation Code in set {D-2, D-4})
return result B
Else if (HFFS02 Equation Code in set {D-2, D-4})

Current Sulfur Record = matching record

Sulfur UOM = Current Sulfur ifecortf.ParameterUOMCode

If (Current Fuel Group == "GAS" AND Sulfur UOM o "GRHSCF")
return result C

else if (Current Fuel Group == "OIL" AND Sulfur UOM o "PCT")

return result C
else if (Current Sulfur itecortf.ParamValFuel > 0)

Sulfur Default = null
If (Sulfur UOM== "GRHSCF")

Sulfur Precision = 1

else

Sulfur Precision = 4

If (Current Sulfur Record.SampleTypeCode == 8)

Sulfur Default = Lookup "MissingDataValue" in "Table D-6 Missing Data Values"

where "Parameter" column = "SULFUR" AND "FuelCode" column = Current Fuel Flow
Records uelCode

If (Sulfur Default == null)

Max Expected Sulfur = Lookup "Upper Value" in "Fuel Flow Warning Levels for Sulfur Content Cross Check
Table"

where "Fuel Code" column = Current Fuel Flow Record^ueXCode
Min Expected Sulfur = Lookup "Lower Value" in "Fuel Flow Warning Levels for Sulfur Content Cross Check
Table"

where "Fuel Code" column = Current Fuel Flow Record^ueXCode
Max Allowed Sulfur = Lookup "Upper Value" in "Fuel Flow Reality Checks for Sulfur Content Cross Check
Table"

where "Fuel Code" column = Current Fuel Flow RecordJ
-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Table"

where "Fuel Code" column = Current Fuel Flow ifecortf.FuelCode

If {Max Allowed Sulfur is not null AND Current Sulfur itecortf.ParamValFuel > Max Allowed Sulfur) OR (,Min
Allowed Sulfur is not null AND Current Sulfur ifecortf.ParamValFuel < Min Allowed Sulfur)
return result D

else if (Current Sulfur ifecortf.ParamValFuel is not rounded to Sulfur Precision)
return result I

else

HFF Sulfur = Current Sulfur ifecortf.ParamValFuel

if (Min Expected Sulfur is not null AND HFF Sulfur < Min Expected Sulfur) OR (Max Expected Sulfur is
not null AND HFF Sulfur > Max Expected Sulfur)
return result E

If (Current Sulfur ifecorrf.ParamValFuel is not rounded to Sulfur Precision)
return result I

else if Sulfur Default == Current Sulfur itecortf.ParamValFuel
HFF Sulfur == Current Sulfur ifecorrf.ParamValFuel

else

return result F

else

return result G

else

return result H

Results:

Result
A

B

C
D

E
F

G
H
I

Usage:

1

Response

You reported more than one HPFF record for [parameter] for FuelCode [fueled] for the
hour.

You reported a formula with a FormulaCode of [code] in the HPFF record for S02 for
FuelCode [fueled], but you did not report an HPFF record for SULFUR. Use of this
formula to calculate S02 requires the reporting of the fuel's sulfur content.
The ParameterUOMCode reported in the HPFF record for SULFUR for FuelCode
[fueled] is missing or invalid.

The ParameterValueForFuel reported in the HPFF record for [parameter] for FuelCode
[fueled] is outside the range of allowable values for the fuel type.
The ParameterValueForFuel reported in the HPFF record for [parameter] for FuelCode
[fueled] is outside the range of expected values for the fuel type.

You reported a SampleTypeCode of 8 in the HPFF record for [parameter] for FuelCode
[fueled], indicating the use of a Table D-6 default, but the ParameterValueForFuel does
not equal the default value for the fuel.

The ParameterValueForFuel reported in the HPFF record for [parameter] for FuelCode
[fueled] is invalid. The value should be greater than 0.

You reported an HPFF record for [parameter] for FuelCode [fueled], but you do not
require this value to calculate S02.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 2
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 229 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-29

Check Name:

Check Extraneous Sulfur Record Fields

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Hourly Extraneous Fields = null

If (Current Sulfur Record is not null)

If (Current Sulfur ifecorrf.Formulaldentifier is not null)

append "Formulaldentifier" to Hourly Extraneous Fields
If (Current Sulfur ifecorrf.MonitoringSystemID is not null)

append "MonitoringSystemID" to Hourly Extraneous Fields
If (Current Sulfur Record.SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields
If (Current Sulfur Record.OpemtingConditionCode is not null)

append "OperatingConditionCode" to Hourly Extraneous Fields

If (Hourly Extraneous Fields is not null)
return result A

Results:

Result
A

Response

You reported [fieldnames] in the HPFF record for SULFUR for FuelCode [fueled].
This data should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 230 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-30

Check Name:

Check Sulfur Sample Type

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

If (Current Sulfur Record is not null)

If (Current Fuel Group == "OIL" AND Current Sulfur Record.SmnpieTypeCode not in {1, 2, 5, 6, 7, 8})
return result A

else if (Current Fuel Group == "GAS" AND Current Sulfur ifecorrf.SampleTypeCode not in {0,2, 4, 5, 6, 7, 8})
return result A

Results:

Result
A

Response

The SampleTypeCode reported in the HPFF record for SULFUR for FuelCode [fueled]
is missing or invalid.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 231 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-31

Check Name:	Determine S02 Emission Rate

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

HFF S02 Emission Rate = null
Current S02R Record = null

Count the HourlyParamFuelFlow record where

HourlyParamFuelFlow.HourlyFuelFlowID = Current Fuel Flow ifecortf.HourlyFuelFlowID AND
HourlyParamFuelFlow.ParameterCode = "S02R"

If (Count >1)

return result A
Else If (Count == 0)

If {HFF S02 Equation Code == "D-5")
return result B
Else if {HFF S02 Equation Code == "D-5")

Current S02R Record = matching record

If {Current S02R ifecortf.ParameterUOMCode o "LBMMBTU"}

return result C
else if {Current S02R ifecorrf.ParamValFuel > 0)

HFF S02 Emission Rate = Current S02R ifecorrf.ParamValFuel

else

return result D
return result E

Results:

Result
A

B

C
D

E

Usage:

1

Response

You reported more than one HPFF record for [parameter] for FuelCode [fueled] for the
hour.

You reported a formula with a FormulaCode of "D-5" in the HPFF record for S02 for
FuelCode [fueled], but you did not report an HPFF record for S02R. Use of formula
D-5 to calculate S02 requires the reporting of the S02 emission rate for the fuel.
The ParameterUOMCode reported in the HPFF record for S02R for FuelCode [fueled]
is missing or invalid. The value should be "LBMMBTU".

The ParameterValueForFuel reported in the HPFF record for [parameter] for FuelCode
[fueled] is invalid. The value should be greater than 0.

You reported an HPFF record for [parameter] for FuelCode [fueled], but you do not
require this value to calculate S02.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 232 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-32

Check Name:

Check Extraneous S02R Record Fields

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Hourly Extraneous Fields = null

If (Current S02R Record is not null)

If (Current S02R ifecorrf.MonitoringSystemID is not null)

append "MonitoringSystemID" to Hourly Extraneous Fields
If (Current S02R ifecortf.SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields
If (Current S02R ifecorrf.OperatingConditionCode is not null)

append "OperatingConditionCode" to Hourly Extraneous Fields
If (Current S02R ifecorrf.SampleTypeCode is not null)

append "SampleTypeCode" to Hourly Extraneous Fields

If (Hourly Extraneous Fields is not null)
return result A

Results:

Result
A

Response

You reported [fieldnames] in the HPFF record for S02R for FuelCode [fueled]. This
data should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 233 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-33

Check Name:	Check S02R Formula

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current S02R Record is not null)

If (Current S02R ifecorrf.Formulaldentifier is null)

If (Current Fuel Flow Record.FuelCode o "PNG" OR Current S02R ifecortf.ParamValFuel o 0.0006)
return result A

else

Cur S02RMon Formula Record = Lookup active formula in MonitoringFormula Table where
MonitoringFormulalD = Current S02R ifecorrf.MonitoringFormulalD

if (Cur S02RMon Formula Record is null)
return result B

else if {Cur S02RMon Formula Record. ParameterCode o "S02R"
return result C

else if {Cur S02RMon Formula .Recorof.EquationCode o "D-1H")
return result D

Results:

Result

B
C
D

Usage:
1

Response

You did not report a FormulalD in the HPFF record for S02R for FuelCode [fueled].
This formula is required except when using the standard default emission rate of 0.0006
for pipeline natural gas.

You reported FormulalD [ID] in the HPFF record for S02R for FuelCode [fueled], but
there is no active Formula record for this formula in your monitoring plan.

You reported FormulalD [ID] in the HPFF record for S02R for FuelCode [fueled], but
this is not an S02R formula.

The FormulaCode of FormulalD [ID] reported in the HPFF record for S02R for
FuelCode [fueled] is invalid. The FormulaCode should be "D-1H".

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 234 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-34

Check Name:	Check Reported S02 Mass Rate

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current S02 HPFFRecord is not null)

If (Current S02 HPFF Record. ParamValFuel is null or is less than 0
return result A

else if (Current Fuel Group == "OIL" AND Current S02 HPFF Record. ParamValFuel is not rounded to one decimal place)
return result B

Results:

Result	Response	Severity

A	The ParameterValueForFuel reported in the HPFF record for S02 for FuelCode [fueled]	Critical Error Level 1

is invalid. The value must be greater than or equal to 0.

B	You reported [fieldname] in the [type] record for [param] that is not rounded to the	Critical Error Level 1

appropriate precision for that parameter.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 235 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-35

Check Name:

Determine FC Factor

Related Former Checks:

Applicability:

Appendix D Check

Description:

Validation Tables:

Fuel Type Reality Checks for FC FACTOR (Cross Check Table)

Specifications:

HFF Fc Factor = null
Current Fc Factor Record = null

Count the Hourly ParamFuelFlow record where

Hourly ParamFuelFlow.HourlyFuelFlowID = Current Fuel Flow ifecortf.HourlyFuelFlowID AND
HourlyParamFuelFlow.ParameterCode = "FC"

If (Count >1)

return result A
Else If (Count == 0)

If (Current C02 HPFFRecord is not null)

Else if (Current C02 HPFF Record is not null)

Current Fc Factor Record = matching record

If (Current Fc Factor ifecortf.ParameterUOMCode o "SCFCBTU")

return result C
else if (Current FcFactor ifecorrf.ParamValFuel > 0)

if (Current FcFactor itecortf.ParamValFuel is not rounded to one decimal place)
return result G

else

HFF Fc Factor = Current Fc Factor itecortf.ParamValFuel

MaxAllowedFc Factor = Lookup "Upper Value" in "Fuel Type Reality Checks for FC Factor Cross Check Table"

where "FuelType" column = Current Fuel Group
MinAllowedFc Factor = Lookup "Lower Value" in "Fuel Type Reality Checks for FC Factor Cross Check Table"
where "FuelType" column = Current Fuel Group

If {Max Allowed FcFactor is not null AND Current Fc Factor ifecorrf.ParamValFuel > Max Allowed Fc Factor)

OR (,Min Allowed FcFactor is not null AND Current Fc Factor ifecorrf.ParamValFuel < Min Allowed Fc Factor)
return result D

return result B

else

return result E

else

return result F

Environmental Protection Agency

Page 236 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

E

F

G

Usage:

1

Response

You reported more than one HPFF record for [parameter] for FuelCode [fueled] for the
hour.

You reported an FtPFF record for C02 for FuelCode [fueled], but you did not report an
FtPFF record for FC for the hour.

The ParameterUOMCode reported in the FtPFF record for FC for FuelCode [fueled] is
missing or invalid.

The ParameterValueForFuel reported in the FtPFF record for [parameter] for FuelCode
[fueled] is outside the range of allowable values for the fuel type.
The ParameterValueForFuel reported in the FtPFF record for FC for FuelCode [fueled]
is invalid.

You reported an FtPFF record for FC for FuelCode [fueled], but you have not reported
an FtPFF record for C02 for the hour.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Ftourly Fuel Flow

Environmental Protection Agency

Page 237 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-36

Check Name:

Check Extraneous Fc Factor Record Fields

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Hourly Extraneous Fields = null

If (Current Fc Factor Record is not null)

If (Current Fc Factor ifecorrf.Formulaldentifier is not null)

append "Formulaldentifier" to Hourly Extraneous Fields
If (Current Fc Factor ifecorrf.MonitoringSystemID is not null)

append "MonitoringSystemID" to Hourly Extraneous Fields
If (Current Fc Factor ifecortf.SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields
If (Current Fc Factor ifecorrf.OperatingConditionCode is not null)

append "OperatingConditionCode" to Hourly Extraneous Fields
If (Current Fc Factor ifecorrf.SampleTypeCode is not null)

append "SampleTypeCode" to Hourly Extraneous Fields

If (Hourly Extraneous Fields is not null)
return result A

Results:

Result
A

Response

You reported [fieldnames] in the HPFF record for FC for FuelCode [fueled]. This data
should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 23 8 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-37

Check Name:

Validate C02 Record

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Current C02 HPFF Record = null

Count the HourlyParamFuelFlow record where

HourlyParamFuelFlow.HourlyFuelFlowID = Current Fuel Flow ifecortf.HourlyFuelFlowID AND
HourlyParamFuelFlow.ParameterCode = "C02"

If (Count >1)

CO2 App D Accumulator = -1
return result A

Else If (Count == 0)

If (CO 2 App D Method Active For Hour == true)

CO2 App D Accumulator = -1
If (Legacy Data Evaluation == false)
return result B

else

return result H

Else if (CO2 App D Method Active For Hour == true)

Current C02 HPFF Record = matching record

if (Current C02 flPFFitecortf.MonitoringFormulald is null
return result C

else

Cur C02 Mon Formula Record = Lookup active formula in MonitoringFormula Table where
MonitoringFormulalD = Current C02 ZWFFifecortf.MonitoringFormulalD

if (Cur C02 Mon Formula Record is null)
return result D

else if {Cur C02 Mon Formula Record. ParameterCode o "C02")
return result E

else if {Cur C02 Mon Formula .Recoraf.EquationCode o "G-4")
return result F

else

return result G

Environmental Protection Agency

Page 239 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C
D

E

F

G

H

Response

You reported more than one HPFF record for [parameter] for FuelCode [fueled] for the
hour.

Your monitoring plan indicates the use of the Appendix D C02 method, but you did not

report an FtPFF record for C02 for FuelCode [fueled] for the hour.

You did not report a FormulalD in the FtPFF record for C02 for FuelCode [fueled].

You reported FormulalD [ID] in the FtPFF record for C02 for FuelCode [fueled], but

there is no active Formula record for this formula in your monitoring plan.

You reported FormulalD [ID] in the FtPFF record for C02 for FuelCode [fueled], but

this is not a C02 formula.

The FormulaCode of FormulalD [ID] reported in the FtPFF record for C02 for
FuelCode [fueled] is invalid. The FormulaCode should be "G-4".

You reported an FtPFF record for C02 for FuelCode [fueled], but you do not have an
active Appendix D C02 method for the hour.

Your monitoring plan indicates the use of the Appendix D C02 method, but you did not
report an FtPFF record for C02 for FuelCode [fueled] for the hour. Fuel-specific C02
emissions data was not required in the EDR data, but is required for all data submitted
through ECMPS. The software will not recalculate C02 emissions values.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Informational Message

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 240 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-38

Check Name:

Check Extraneous C02 Record Fields

Related Former Checks:

Applicability:

Appendix D Check

Description:

Specifications:

Hourly Extraneous Fields = null

If (Current C02 HPFFRecord is not null)

If (Current C02 HPFFitecortf.MonitoringSystemID is not null)

append "MonitoringSystemID" to Hourly Extraneous Fields
If (Current C02 HPFFitecortf.SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields
If (Current C02 HPFFitecortf.OperatingConditionCode is not null)

append "OperatingConditionCode" to Hourly Extraneous Fields
If (Current C02 HPFFitecortf.SampleTypeCode is not null)

append "SampleTypeCode" to Hourly Extraneous Fields

If (Hourly Extraneous Fields is not null)
return result A

Results:

Result
A

Response

You reported [fieldnames] in the HPFF record for C02 for FuelCode [fueled]. This
data should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 241 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAD-39

Check Name:

Calculate C02 Mass Rate

Related Former Checks:

Applicability:

Appendix D Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

HFF Calc C02 = null

If (Current C02 HPFFRecord is not null)

if (HFF Calc HI Rate is not null AND HFF Fc Factor is not null)

C02 HPFF Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "C02" AND
UOM = "TNHR"

HFF Calc C02 = HFF Calc HI Rate * HFF Fc Factor * 44.0 / (385.0 * 2000.0), and round the result to one decimal
place.

If Current Fuel Flow itecortf.FuelUsageTime > 0 AND Current Fuel Flow ifecorrf.FuelUsageTime <= 1 AND CO2 App
D Accumulator >= 0)

11 Note - this accumulates totals for all Fuel flow records and does not work like a normal parameter
C02 App D Accumulator = C02 App D Accumulator + HFF Calc C02 * Current Fuel Flow
ifecorrf.FuelUsageTime

else

CO2 App D Accumulator = -1

If (Current C02 HPFFifecortf.ParamValFuel >= 0)

if (ABS(.HFF Calc C02 - Current C02 HPFF Record. ParamValFuel) > C02 HPFF Tolerance)

return result A

else

CO2 App D Accumulator = -1
return result B

Results:

Result
A

Response

The ParameterValueForFuel reported for HPFF record for C02 for FuelCode [fueled] is
inconsistent with the recalculated value.

The ParameterValueForFuel in the HPFF record for [parameter] for FuelCode [fueled]
could not be recalculated due to errors listed above.

Severity

Critical Error Level 1

B

Informational Message

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 242 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-40

Check Name:	Check Reported C02 Mass Rate

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current C02 HPFFRecord is not null)

If (Current C02 HPFF Record. ParamValFuel is null or is less than 0
return result A

else if (Current C02 HPFFifecortf.ParamValFuel is not rounded to one decimal place)
return result B

Results:

Severity

Critical Error Level 1
Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Result	Response

A	The ParameterValueForFuel reported in the HPFF record for C02 for FuelCode [fueled]

is invalid. The value should be greater than or equal to 0.

B	You reported [fieldname] in the [type] record for [param] that is not rounded to the

appropriate precision for that parameter.

Environmental Protection Agency

Page 243 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-44

Check Name:	Check C02 Units Of Measure

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current C02 HPFFRecord is not null)

If (Current C02 HPFFitecortf.ParameterUOMCode o "TNHR")
return result A

Results:

Result	Response	Severity

A	The ParameterUOMCode reported in the HPFF record for C02 for FuelCode [fueled] is	Critical Error Level 1

missing or invalid. The value should be "TNHR".

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 244 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAD-45

Check Name:	Determine Appendix D Measure Codes

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current Fuel Flow itecortf.SourceOfDataMassCode inset {4,5,6} OR Current Fuel Haw /f/Y/.SourceOn)ataVohimetricCode in
set {4, 5, 6} OR Monitor Measure Code Array for "FF" =="OTHER")

set Monitor Measure Code Array for "FF" to "OTHER"
else if (Current Fuel Flow ifecortf.SourceOfDataMassCode in set {1,3} OR Current Fuel Flow ifecortf.SourceOfDataVolumetricCode in

set {1,3})

if (Monitor Measure Code Array for "FF" begins with "MEAS")

set Monitor Measure Code Array for "FF" to "MEASSUB"

else

set Monitor Measure Code Array for "FF" to "SUB"
else if (Current Fuel Flow ifecortf.SourceOfDataMassCode in set {0, 9} OR Current Fuel Flow ifecortf.SourceOfDataVolumetricCode in

set {0, 9}))

if (Monitor Measure Code Array for "FF" contains "SUB")

set Monitor Measure Code Array for "FF" to "MEASSUB"

else

set Monitor Measure Code Array for "FF" to "MEASURE"

if (Current Sulfur Record is not null)

if (Current Sulfur ifecorrf.SampleTypeCode == 8)

if (Monitor Measure Code Array for "SULFUR" begins with "MEAS")

set Monitor Measure Code Array for "SULFUR" to "MEASSUB"

else

set Monitor Measure Code Array for "SULFUR" to "SUB"
else if (Current Sulfur itecortf.SampleTypeCode in set {0, 1,2,4, 5, 6,7})
if (Monitor Measure Code Array for "SULFUR" contains "SUB")

set Monitor Measure Code Array for "SULFUR" to "MEASSUB"

else

set Monitor Measure Code Array for "SULFUR" to "MEASURE"

if (Current GC VRecord is not null)

if (Current GC Fifecorrf.SampleTypeCode == 8)

if (Monitor Measure Code Array for "GCV" begins with "MEAS")

set Monitor Measure Code Array for "GCV" to "MEASSUB"

else

set Monitor Measure Code Array for "GCV" to "SUB"
else if (Current GCFifecortf.SampleTypeCode in set {0, 1, 2, 3,4, 5, 6, 7})
if (Monitor Measure Code Array for "GCV" contains "SUB")

set Monitor Measure Code Array for "GCV" to "MEASSUB"

else

set Monitor Measure Code Array for "GCV" to "MEASURE"

if (Current Density Record is not null)

if (Current Density itecortf.SampleTypeCode == 8)

if (Monitor Measure Code Array for "DENSITY" begins with "MEAS")

set Monitor Measure Code Array for "DENSITY" to "MEASSUB"

else

set Monitor Measure Code Array for "DENSITY" to "SUB"
else if (Current Density ifecorrf.SampleTypeCode in set {1,2, 5, 6, 7})

if (Monitor Measure Code Array for "DENSITY" contains "SUB")

set Monitor Measure Code Array for "DENSITY" to "MEASSUB"

Environmental Protection Agency

Page 245 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

else

set Monitor Measure Code Array for "DENSITY" to "MEASURE"

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 246 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Hourly Appendix E

Environmental Protection Agency

Page 247 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAE-1

Check Name:

Initialize AE Reporting Method

Related Former Checks:

Applicability:

Appendix E Check

Description:

Specifications:

App E Reporting Method = null
App E Op Code = null
App E Segment Number = null
App E Reported Value = null
App E Fuel Code = null
App E Calc HI = null

if (Current NOx Rate Method Code == "AE")

Total Fuel Sources = Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count for Oil

11 App E Constant Fuel Mix detected when processing DHV records
if (Total Fuel Sources >1)

App E Reporting Method = "MULTIPLE"
else if (Total Fuel Sources == 1)

App E Reporting Method = "SINGLE'

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 248 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAE-2

Check Name:

Validate NOXR Record

Related Former Checks:

Applicability:

Appendix E Check

Description:

Specifications:

Current App E NOXR Record = null

App E NOXR HPFF Count for Gas = find matching Hourly ParamFuelFlow records where

HourlyParamFuelFlow.HourlyFuelFlowID = Current Fuel Flow ifecortf.HourlyFuelFlowID AND
Hourly ParamFuelFlow.ParameterCode = "NOXR"

If (App E NOXR HPFF Count for Gas == 0)

if (App E Reporting Method in set {MULTIPLE, SINGLE})

NOXR App E Accumulator = -1
return result A

else if (If App E NOXR HPFF Count for Gas >1)

if (App E Reporting Method in set {MULTIPLE, SINGLE})

NOXR App E Accumulator = -1
return result B

else

return result D

Else if (App EReporting Method in set {MULTIPLE, SINGLE})

Current App E NOXR Record = matching record

App E Segment Number = Current App E NOXR Record. SegmentNumber
App E Reported Value = Current App E NOXR Record. ParamValFuel
App E Calc HI = HFF Calc HI Rate
App E Fuel Code = Current Fuel Flow itecortf.FuelCode

if Current Appe E NOXR Record OperatingConditionCode in set {E, X, Y, Z, U, W, N, M}

App E Op Code = Current App E NOXR Record OperatingConditionCode

else

App E Op Code = null
return result C

else if (App E Reporting Method == "CONSTANT")

return result D

else

return result E

Environmental Protection Agency

Page 249 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B
C

D

Response

You did not report an HPFF record for NOXR to report the NOx emission rate for
individual fuels.

You reported more than one HPFF record for NOXR for FuelCode [fueled] for the hour.
The OperatingConditionCode reported in the FtPFF record for NOXR for FuelCode
[FUELCD] is missing or invalid.

You reported an FtPFF record for NOXR, but, according to your monitoring plan, you
use an Appendix E mixed fuel curve to determine the NOx emission rate. If this is the
case, you should report the NOx emission rate in a NOXR DFtV record. The FtPFF
record will not be evaluated and the NOx emissions rate will not be recalculated.
You reported an FtPFF record for NOXR, but you have not defined a NOXR AE method
in your monitoring plan that is active during the current hour. The FtPFF record will not
be evaluated and the NOx emissions rate will not be recalculated.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Ftourly Fuel Flow

Environmental Protection Agency

Page 250 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAE-4

Check Name:

Check for Extraneous Fields in NOXR Record

Related Former Checks:

Applicability:

Appendix E Check

Description:

Specifications:

Hourly Extraneous Fields = null

if (Current App ENOXR Record is not null)

if (Current App E NOXR Record. SampleTypeCode is not NULL)
append "SampleTypeCode" to Hourly Extraneous Fields

if (Current App E NOXR ifecorrf.MonitoringFormulald is not NULL)
append "MonitoringFormulalD" to Hourly Extraneous Fields

If (Hourly Extraneous Fields is not null)
return result A

Results:

Result
A

Response

You reported [fieldnames] in the FtPFF record for NOXR for FuelCode [fueled]. This
data should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Ftourly Fuel Flow

Environmental Protection Agency

Page 251 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAE-5

Check Name:	Check Monitoring System Data for Appendix E NOXR

Related Former Checks:

Applicability:	Appendix E Check

Description:

Specifications:

if (Current App ENOXR Record is not null)

App E NOXE System ID = null
App E NOXE System Identifier = null

if (Current App E NOXR Record. MonitoringSy stemld is null)

if {Current App E NOXR Record. OperatingConditionCode == "E")
if (HFFFuel Indicator Code o "E")
return result A

else

return result B
11 report Monitoring System in all other cases
else

Current App E NOXR Mon Sys Record = find MonitoringSystem record where

MonitoringSystem.MonitoringSystemld = Current App E NOXR Record. MonitoringSystemld
if (Current App E NOXR Mon Sys Record is null)
return result C

else if (Current App E NOXR Mon Sys Record.SystemTypeCode o "NOXE"
return result D

else if (Current App E NOXR Mon Sys RecordsuelCode o Current Fuel Flow RecordsuelCode
return result E

else

App E NOXE System ID = Current App E NOXR Record. MonitoringSystemld

App E NOXE System Identifier = Current App E NOXR Mon Sys .Recoraf.Systemldentifier

Results:

Result

B

D

E

Usage:
1

Response

The OperatingConditionCode of E reported in the HPFF record for NOXR for FuelCode
[fueled] indicates that the fuel is an emergency fuel, but this is inconsistent with the
IndicatorCode in the UnitFuel record for the fuel.

You did not report a MonitoringSystemID in the HPFF record for NOXR for FuelCode
[fueled], but you did not report an OperatingConditionCode of E. You must report a
NOXE MonitoringSystemID for non-emergency fuels.

You reported MonitoringSystemID [ID] in the HPFF record for NOXR for FuelCode
[fueled], but there is no MonitorSystem record for this system in your monitoring plan
that was active during the hour.

You reported MonitoringSystemID [ID] in the HPFF record for NOXR for FuelCode
[fueled], but this system is not a NOXE monitoring system.

You reported NOXE MonitoringSystemID [ID] in the HPFF record for NOXR, but the
FuelCode of this system is not equal to FuelCode [fueled] in the associated HFF record.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 252 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAE-7

Check Name:

Retrieve Appendix E Correlation Test Results or Default Value

Related Former Checks:

Applicability:

Appendix E Check

Description:

Specifications:

Maximum App E Curve NOx Emission Rate = null
AppE NOx MER = null
App E Segment Total = null

If {App E Op Code in set {N, W, X, Y, Z} )

if (Current Appendix E Status begins with "IC" or "Undetermined")

QA Supp Attribute Count Record = matching record in QASuppAttribute where

QASuppAttribute.QASuppDatald = Prior Appendix E itecortf. QASuppDatald
QASuppAttribute.AttributeName = "SEGMENTCOUNT"

if (QA Supp Attribute Count Record is not null)

App E Segment Total = QA Supp AttributeCount Record.AttributeValue
Dimension App E Correlation NOx Rate Array with App E Segment Total elements
Dimension AppE Correlation Heat Input Array with AppE Segment Total elements

for (X = 1 to App E Segment Total)

QA Supp Attribute Segment NOx Record = matching record in QASuppAttribute where
QASuppAttribute.QASuppDatald = Prior Appendix E Record. QASuppDatald
QASuppAttributeAttributeName = "NOX RATE X" (where X matches the loop variable)

if (QA Supp Attribute Segment NOx Record is not null)

if (QA Supp Attribute Segment NOx Record. AttributeValue >Maximum App E Curve NOx
Emission Rate

Maximum App E Curve NOx Emission Rate = QA Supp Attribute Segment NOx
Record. A ttribute Value

App E Correlation NOx Rate Array[X\ = QA Supp Attribute Segment NOx .Recoraf AttributeValue

QA Supp Attribute Segment HI Record = matching record in QASuppAttribute where

QASuppAttribute.QASuppDatald = Prior Appendix E Record. QASuppDatald
QASuppAttribute.AttributeName = "HI_RATE_X" (where X matches the loop variable)

if (QA Supp Attribute Segment HI Record is not null)

App E Correlation Heat Input Array[X\ = QA Supp Attribute Segment HI Record.Attribute Value

else if (App E Op Code in set {E, M, U} )

Count active MonitoringDefault record for location where
ParameterCode = "NORX" AND
DefaultPurpose = "MD" AND
FuelCode = App E Fuel Code

if (Count o 1)

return result A

else

App E NOx MER Default Record = matching record
If (App E NOx MER Default .Recorof.DefaultValue > 0

Environmental Protection Agency

Page 253 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

App E NOx MER =AppE NOx MER Default .Recorof.DefaultValue

else

return result B

Results:

Result

B

Usage:

1

2

3

Response

The NOx emission rate could not be determined, because you did not report one and
only one missing data default record for NORX for FuelCode [fueled] in your
monitoring plan that was active during current hour.

The NOx emission rate could not be determined, because the DefaultValue in the
NORX default record for FuelCode [fueled] is invalid.

Severity

Critical Error Level 1

Critical Error Level 1

Process/Category:	Emissions Data Evaluation Report — Hourly Configuration Evaluation

Conditions:	App E Checks Needed Equals true

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Conditions:	App E Constant Fuel Mix Equals true

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Conditions:	App E Constant Fuel Mix Equals false

Environmental Protection Agency

Page 254 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAE-8

Check Name:

Determine Appendix E Curve Segment

Related Former Checks:

Applicability:

Appendix E Check

Description:

Specifications:

App E Calc Segment Num. = null

if (App E Op Code is not null)

switch {App E Op Code)

case "E" or "U" or "M" or "W":

if App E Segment Number is not null
return result A

case "N" or "X":

If {App E Segment Total is not null)

if App E Segment Number is not null

if [App E Segment Number > number of elements in the App E Correlation NOx Rate Array)
return result B

else if (App E Correlation NOx Rate Array [App E Segment Number] o Maximum App E

Curve NOx Emission Rate)
return result B

else

if {Legacy Data Evaluation == false)
return result G

If {App E Calc HI is not null) and {App E Segment Total is not null)

2=1

while (i <= App E Segment Total AND App E C ale HI > App E Correlation Heat Input Rate Array[i])
i = i + 1

if (i <= App E Segment Total AND App E Calc HI <= App E Correlation Heat Input Array[i])

App E Calc Segment Num = i

if {App E Op Code == "Z")

if {App E Calc Segment Num o 1)

return result C
else if App E Segment Number is null

if {Legacy Data Evaluation == false)
return result G
else if {App E Segment Number o 1)
return result D

else if App E Segment Number is null

if {Legacy Data Evaluation == false)
return result G

case "Y" OR "Z":

Environmental Protection Agency

Page 255 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else if {App E Calc HI == App E Correlation Heat Input Array[i\)

if (App E Segment Number o App E Calc Segment Num AND App E Segment
Number o App E Calc Segment Num +1)
return result E

else

if (App E Segment Number o App E Calc Segment Num)
return result E

return result F

Results:

Result
A

B

D

E
F

G

Usage:

1

2

3

Response

You reported a SegmentNumber in the FtPFF or DFtV record for NOXR for FuelCode
[fueled]. This field should be blank when OperatingConditionCode is [OpCode],
You reported an OperatingConditionCode of [OpCode] in the DFtV or FtPFF record for
NOXR for FuelCode [fueled], but the reported SegmentNumber does not represent the
segment on the Appendix E curve with the maximum NOx emission rate.

You reported an OperatingConditionCode of Z in the DFtV or FtPFF record for NOXR
for FuelCode [fueled], but the calculated heat input rate is not below the lowest point on
the Appendix E curve.

You reported an OperatingConditionCode of Z in the DFtV or FtPFF record for NOXR
for FuelCode [fueled], but you did not report a SegmentNumber of 1.
The SegmentNumber reported in the FtPFF or DFtV record for NOXR for FuelCode
[fueled] is inconsistent with the calculated heat input.

You reported an OperatingConditionCode of [OpCode] in the DFtV or FtPFF record for
NOXR for FuelCode [fueled], but the calculated heat input rate is higher than the
maximum heat input rate on the Appendix E curve. You should report an
OperatingConditionCode of W, and use the appropriate substitute data algorithm to
calculate the NOx emission rate.

You did not report a SegmentNumber in the FtPFF or DFtV record for NOXR for
FuelCode [fueled].

Severity

Critical Error Level 1
Non-Critical Error

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Process/Category:	Emissions Data Evaluation Report — Ftourly Configuration Evaluation

Conditions:	App E Checks Needed Equals true

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Conditions:	App E Constant Fuel Mix Equals true

Process/Category:	Emissions Data Evaluation Report	Ftourly Fuel Flow

Conditions:	App E Constant Fuel Mix Equals false

Environmental Protection Agency

Page 256 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAE-9

Check Name:	Calculate Appendix E NOx Rate

Related Former Checks:

Applicability:	Appendix E Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

App E Calculated NOx Rate for Source = null

if (App E Op Code in set {Y, Z})

If (App E Calc Segment Num. is not null)

if {App E Calc Segment Num ==1)

App E Calculated NOx Rate for Source = App E Correlation NOx Rate Array [ 1 ]

else

y2 = App E Correlation NOx Rate Array[App E Calc Segment Num]
x2 = App E Correlation Heat Input Array [App E Calc Segment Num]
y 1 = App E Correlation NOx Rate Array [App E Calc Segment Num - 1 ]
x 1 = App E Correlation Heat Input Array [App E Calc Segment Num - 1 ]

slope = (y2 - yl) / (x2 - xl)

App E Calculated NOx Rate for Source = slope * {App E Calc HI - xl) + yl, and round the result to 3 decimal
places.

else if {App E Op Code in set {N, X})

App E Calculated NOx Rate for Source = Maximum App E Curve NOx Emission Rate

else if {App E Op Code in set {E, M, U})

App E Calculated NOx Rate for Source = App E NOx MER

else if {App E Op Code == " W" AND Maximum App E Curve NOx Emission Rate is not null AND App E Reported Value >= 0 AND App
EReported Value is rounded to three decimal places)

If {App E Reported Value >= Maximum App E Curve NOx Emission Rate * 1.25 (rounded to 3 decimal places))

App E Calculated NOx Rate for Source = App E Reported Value

Count active MonitoringDefault record for location where
ParameterCode = "NORX" AND
DefaultPurpose = "MD" AND
FuelCode = App E Fuel Code

if {Count o 1)

return result A

else

NOx MER Default Record = matching record
If {NOx MER Default .Recorof.DefaultValue > 0)

If {App E Reported Value >= NOx MER Default .Recoraf.DefaultValue)

App E Calculated NOx Rate for Source = App E Reported Value

Environmental Protection Agency

Page 257 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

if {AppE Reporting Method == "CONSTANT" or "APPORTIONED")
return result B

else

NOXR App E Accumulator = -1
return result C

else

if {AppE Reporting Method == "CONSTANT" or "APPORTIONED")
return result D

else

NOXR App E Accumulator = -1
return result D

if {App E Calculated NOx Rate for Source is not null)

NOXR HPFF Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "NOXR" AND
UOM = "LBMMBTU"

if {App E Reporting Method == "CONSTANT")

if {App E Reported Value >= 0 AND AliSf.l/?/? E Calculated NOx Rate for Source - App E Reported Value) > NOXR
HPFF Tolerance )

return result E

if {App E Reporting Method == "APPORTIONED")

Apportionment Calc NOXR Array at this Location = App E Calculated NOx Rate for Source

if {Rpt Period NOx Rate Calculated Accumulator Array for this location is not null)

if {Rpt Period NOx Rate Calculated Accumulator Array for this location >= 0)

Rpt Period NOx Rate Calculated Accumulator Array for this location = Rpt Period NOx Rate
Calculated Accumulator Array for this location + App E Calculated NOx Rate for Source

else

Rpt Period NOx Rate Calculated Accumulator Array for this location = App E Calculated NOx Rate for Source

Rpt Period NOx Rate Hours Accumulator Array for this location = Rpt Period NOx Rate Hours Accumulator Array for
this location + 1

Set Current Measure Code to the Monitor Measure Code Array for "NOXR".

if {App E Reported Value >= 0 AND AliSf.l/?/? E Calculated NOx Rate for Source - App E Reported Value) > NOXR
HPFF Tolerance )

return result E

If Current Fuel Flow itecortf.FuelUsageTime > 0 AND Current Fuel Flow ifecorrf.FuelUsageTime <= 1 AND NOXR
App E Accumulator >= 0 AND App E Calc HI is not null)

NOXR App E Accumulator = NOXR App E Accumulator + {App E Calculated NOx Rate for Source * Current
Fuel Flow Record.luc\I JsagcTimc * App E Calc HI)

else

NOXR App E Accumulator = -1

if {App E Reported Value >= 0 AND AliSf.l/?/? E Calculated NOx Rate for Source - App E Reported Value) > NOXR
HPFF Tolerance )

return result F

if {App E Reporting Method == "CONSTANT")

Environmental Protection Agency

Page 258 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result G

else if (App E Reporting Method == "APPORTIONED")

Apportionment Calc NOXR Array at this Location = -1

Rpt Period NOX Rate Calculated Accumulator Array for this location = -1

return result G

else if (App E Op Code is not null)

NOXR App E Accumulator = -1
return result H

Results:

Result

B

D

E
F
G
H

Response

The NOx emission rate could not be determined, because you did not report one and
only one missing data default record for NORX for FuelCode [fueled] in your
monitoring plan that was active during current hour.

You reported an OperatingConditionCode of W in the DHV record for NOXR for

FuelCode [fueled], but the AdjustedFtourlyValue is less than the minimum allowable

substitute data value according to Appendix E sec. 2.5.2.1.

You reported an OperatingConditionCode of W in the FtPFF record for NOXR for

FuelCode [fueled], but the ParameterValueForFuel is less than the minimum allowable

substitute data value according to Appendix E sec. 2.5.2.1.

The NOx emission rate could not be determined, because the DefaultValue in the

NORX default record for FuelCode [fueled] is invalid.

The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with
the recalculated value.

The ParameterValueForFuel reported in the FtPFF record for NOXR for FuelCode
[fueled] is inconsistent with the value recalculated from the Appendix E curve.
The AdjustedFtourlyValue in the DFtV record for [param] could not be recalculated due
to errors listed above.

The ParameterValueForFuel in the FtPFF record for [parameter] for FuelCode [fueled]
could not be recalculated due to errors listed above.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Informational Message
Informational Message

Usage:

1

2

3

Process/Category:	Emissions Data Evaluation Report — Hourly Configuration Evaluation

Conditions:	App E Checks Needed Equals true

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Conditions:	App E Constant Fuel Mix Equals true

Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Conditions:	App E Constant Fuel Mix Equals false

Environmental Protection Agency

Page 259 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAE-13

Check Name:	Check Reported NOx Emission Rate

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current Appe E NOXR Record is not null)

If (Current App E NOXR itecortf.ParamValFuel is null or is less than 0
return result A

else if (Current App E NOXR itecortf.ParamValFuel is not rounded to three decimal places)
return result B

Results:

Result	Response	Severity

A	The ParameterValueforFuel reported in the HPFF record for NOXR for FuelCode	Critical Error Level 1

[fueled] is invalid. The value must be greater than or equal to 0.

B	You reported [fieldname] in the [type] record for [param] that is not rounded to the	Critical Error Level 1

appropriate precision for that parameter.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 260 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURAE-14

Check Name:	Check NOXR Units Of Measure

Related Former Checks:

Applicability:	Appendix D Check

Description:

Specifications:

If (Current App ENOXR Record is not null)

If (Current App E NOXR itecortf.ParameterUOMCode o "LBMMBTU")
return result A

Results:

Result	Response	Severity

A	The ParameterUOMCode reported in the HPFF record for NOXR for FuelCode [fueled]	Critical Error Level 1

is missing or invalid. The value should be "LBMMBTU".

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Hourly Fuel Flow

Environmental Protection Agency

Page 261 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAE-15

Check Name:

Determine Appendix E Measure Code

Related Former Checks:

Applicability:

Appendix E Check

Description:

Specifications:

if (App E Op Code is not null)

If (App E Op Code = "E" or Monitor Measure Code Array for "NOXR" =="OTHER")

set Monitor Measure Code Array for "NOXR" to "OTHER"
else if (App E Op Code in set {M, U, N})

if (Monitor Measure Code Array for "NOXR" begins with "MEAS")

set Monitor Measure Code Array for "NOXR" to "MEASSUB"

else

set Monitor Measure Code Array for "NOXR" to "SUB"
else if (App E Op Code in set {W, X, Y, Z})})

if (Monitor Measure Code Array for "NOXR" contains "SUB")

set Monitor Measure Code Array for "NOXR" to "MEASSUB"

else

set Monitor Measure Code Array for "NOXR" to "MEASURE"

Results:

Result

Response

Severity

Usage:
1

Process/Category:

Conditions:

Process/Category:

Conditions:

Process/Category:

Conditions:

Emissions Data Evaluation Report — Hourly Configuration Evaluation
App E Checks Needed Equals true

Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

App E Constant Fuel Mix Equals true

Emissions Data Evaluation Report	Hourly Fuel Flow

App E Constant Fuel Mix Equals false

2

3

Environmental Protection Agency

Page 262 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Hourly Apportionment

Environmental Protection Agency

Page 263 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAPP-1

Check Name:

Determine Monitoring Plan Configuration

Related Former Checks: HOUROP-28

Applicability:

CEM Check

Description:

Specifications:

MP Stack Config for Hourly Checks = null

MP Pipe Config for Hourly Checks = null

MP Load UOM = null

MP Unit Load = null

Stack OpTime Accumulator = 0

Stack LoadTimesOpTime Accumulator = 0

Pipe LoadTimesOpTime Accumulator = 0

Config HeatlnputTimesOpTime Accumulator = 0

Config NOxRateTimesHeatlnput Accumulator = 0

Config NOxRateTimesOpTime Accumulator = 0

Config OpTime Accumulator = 0

Config Heatlnput Accumulator = 0

Max Stack OpTime = 0

Unit OpTime Accumulator = 0

Unit LoadTimesOpTime Accumulator = 0

Unit HeatlnputTimesOpTime Accumulator = 0

Max Unit OpTime = 0

CP Fuel Count = 0

Current Month = month from Current Date

App E Reporting Method = null

App E Op Code = null

App E Segment Number = null

App E Reported Value = null

App E Fuel Code = null

App E Calc HI = null

App E NOXE System ID = null

App E NOXE System Identifier = null

CurrentAppendixEStatus = null

EarliestLocationReportDate = null

Current Measure Code = null

Set Monitor Measure Code Array to null for each parameter.

For each array below, initialize each array with Current Location Count entries and the values as described

Apportionment OpTime Array - set each element in array to 0.0
Apportionment Load Array - set each element in array to 0
Apportionment Calc HI Array - set each element in array to 0.0
Apportionment Calc NOXR Array - set each element in array to 0.0
Apportionment HI Method Array - set each element in array to null
Apportionment NOX Method Array - set each element in array to null
Apportionment HI Measure Code Array - set each element in array to null
Apportionment NOXR Measure Code Array - set each element in array to null
Apportionment Stack Unit List - set each element in array to null
Apportionment NOXR Method Array - set each element in array to null

If Current Location Count > 1

Find List of MonitorLocationlds in MonitorPlanLocation Table that match Current Monitoring Plan Id

Environmental Protection Agency

Page 264 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

For each MonitorLocationld in list, lookup record in MonitorLocalion table
if StackPipeld is not null, add StackPipeld to StackPipe list
if Unitld is not null, add Unitld to Unit list

MS Count = 0
MP Count = 0
CS Count = 0
CP Count = 0
Unit Count = 0
CS Unit Count = 0
CP Unit Count = 0
Unit MS Count = 0

For each MonitorLocationld in list, lookup record in MonitorLocalion table

if MonitorLocation.StackPipelD is not null,

set Stack Unit Count to 0

for each UnitStackConfiguration record where

BeginDate <= Current Date AND EndDate >= Current Date AND
StackPipeld = MonitorLocation.StackPipeld

add 1 to Stack Unit Count

append MonitorLocationID of the unit to Apportionment Stack Unit List for the stack location

if (StackPipeUnit Count > 0)

if {MonitorLocation.StackPipeName begins with "MS")
add 1 to MS Count

else if {MonitorLocation. StackPipeName begins with "MP")
add 1 to MP Count

else if {MonitorLocation. StackPipeName begins with "CS")
add 1 to CS Count

if (CS Count == 1)

CS Unit Count = Stack Unit Count

else if {MonitorLocation. StackPipeName begins with "CP")
add 1 to CP Count

if {CP Count ==1)

CP Unit Count = Stack Unit Count

else if Unitld is not null

add 1 to Unit Count

if {Unit Count == 1)

Unit MS Count = number of UnitStackConfiguration records where
UnitStackConfiguration.BeginDate <= Current Date AND
UnitStackConfiguration.EndDate >= Current Date AND
UnitStackConfiguration .UnitID = MonitorLocation. Unitld
UnitStackConfiguration.StackPipeName begins with "MS"

if {MS Count > 1 AND CS Count == 0 AND Unit Count == 1 AND MS Count == Unit MS Count)
MP Stack Configfor Hourly Checks = "MS"

Environmental Protection Agency

Page 265 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Multiple Stack Configuration = true
else if (CS Count == 1 AND MS Count == 0 AND Unit Count > 1 AND Unit Count = = CS Unit Count)

MP Stack Config for Hourly Checks = "CS"
else if (CS Count == 1 AND MS Count > 0)

MP Stack Config for Hourly Checks = "CSMS"
else if (CS Count + MS Count > 0)

MP Stack Config for Hourly Checks = "COMPLEX"

If (CP Count ==1 AND MP Count == 0 AND Unit Count > 1 AND Unit Count == CP Unit Count)

MP Pipe Config for Hourly Checks = "CP"
else if (CP Count + MP Count > 0)

MP Pipe Config for Hourly Checks = "MULTIPLE"

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report — Hourly Configuration Initialization

Environmental Protection Agency

Page 266 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAPP-2

Check Name:

Pre-Validate Heat Input Calculation

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Calculate Apportioned HI = false

Calculate NOXM From Apportioned HI = false

if Current Monitor Plan Location ifecortf. StackPipelD is not null

If the StackPipelD of the monitoring location begins with "CS",
set Current HI Entity Type = "CS"

If the StackPipelD of the monitoring location begins with "CP",
set Current HI Entity Type = "CP"

If the StackPipelD of the monitoring location begins with "MS",
set Current HI Entity Type = "MS"

If the StackPipelD of the monitoring location begins with "MP",
set Current HI Entity Type = "MP"

else if the UnitID of the monitoring location is not null

set Current HI Entity Type = "Unit"

If {Apportionment HI Method Array for the location contains "CALC") OR {Apportionment HI Method Array for the location ==

"COMPLEX")

If {MP Pipe Config for Hourly Checks == "CP" AND CP Fuel Count > 1)

Apportionment HI Method Array for the location == "NOCALC"

If {Apportionment OpTime Array for the location > 0 AND Apportionment OpTime Array for the location <= 1)

11F-25

If {MP Stack Config for Hourly Checks == "CS" AND Current HI Entity Type = "CS")

if {Apportionment NOX Method Array == "NOXR")

Calculate NOXM From Apportioned HI = true

If Apportionment OpTime Array for the location < Max Unit OpTime
return result A

else if Apportionment OpTime Array for the location > Unit OpTime Accumulator + (the number of units in the
monitoring plan * .005)
return result B

else

If {Config HeatlnputTimesOpTime Accumulator > 0)
Calculate Apportioned HI = true

if {MP Load UOM o "INVALID" AND Stack LoadTimesOpTime Accumulator > 0 AND Unit
LoadTimesOpTime Accumulator > 0 AND abs{Stack LoadTimesOpTime Accumulator - Unit
LoadTimesOpTime Accumulator) >= number of items in the Apportionment OpTime Array)

return result C

11F-21A/B

else if {{MP Stack Config for Hourly Checks == "CS" OR MP Pipe Config for Hourly Checks == "CP") AND
Apportionment HI Method Array for the location not in set {NOCALC, COMPLEX})

Environmental Protection Agency

Page 267 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (Apportionment NOX Method Array == "NOXR")

Calculate NOXM From Apportioned HI = true

If Max Stack OpTime < Max Unit OpTime AND MP Pipe Config for Hourly Checks is null
return result A

else if Max Stack OpTime > Unit OpTime Accumulator + (the number of units in the monitoring plan * .005)
AND MP Pipe Config for Hourly Checks is null

return result B
else if MP Load UOMo "INVALID"

if ((MP Pipe Config for Hourly Checks o "CP" AND MP Stack Config for Hourly Checks == "CS"
AND Stack LoadTimesOpTime Accumulator > 0 AND Unit LoadTimesOpTime Accumulator > 0 AND
(Stack LoadTimesOpTime Accumulator - Unit LoadTimesOpTime Accumulator) > number of items in
the Apportionment OpTime Array)
return result C

else if (Config HeatlnputTimesOpTime Accumulator >= 0 AND Apportionment Load Array for this
Location >= 0 AND Unit LoadTimesOpTime Accumulator >= 0 AND Apportionment Calc HI Array for
this Location >= 0)

Calculate Apportioned HI = true

If (Unit LoadTimesOpTime Accumulator == 0)

Apportionment HI Method Array for the location == "NOCALC"

11 Cannot apportionment but will validate total configuration

else if ((MP Stack Config for Hourly Checks begins with "CS" OR MP Pipe Config for Hourly Checks == "CP" OR MP
Pipe Config for Hourly Checks == "MULTIPLE") AND Apportionment HI Method Array for the location o
"COMPLEX")

if (Apportionment NOX Method Array == "NOXR")

Calculate NOXM From Apportioned HI = true

If Max Stack OpTime > Unit OpTime Accumulator + (the number of units in the monitoring plan * .005) AND
MP Pipe Config for Hourly Checks is null
return result B

else if (Config HeatlnputTimesOpTime Accumulator > 0 and Unit HeatlnputTimesOpTime Accumulator == 0)
OR (Config HeatlnputTimesOpTime Accumulator == 0 AND Unit HeatlnputTimesOpTime Accumulator > 0)
return result G

else if (Config HeatlnputTimesOpTime Accumulator >= 0 AND Unit HeatlnputTimesOpTime Accumulator >=

0)

Calculate Apportioned HI = true

11 COMPLEX

else if (MP Stack Config for Hourly Checks == "COMPLEX" OR Apportionment HI Method Array for the location ==
"COMPLEX")

if (Apportionment NOX Method Array == "NOXR")

Calculate NOXM From Apportioned HI = true

if (Config HeatlnputTimesOpTime Accumulator > 0 and Unit HeatlnputTimesOpTime Accumulator == 0) OR
(Config HeatlnputTimesOpTime Accumulator == 0 AND Unit HeatlnputTimesOpTime Accumulator > 0)
return result G

else if (Config HeatlnputTimesOpTime Accumulator >= 0 AND Unit HeatlnputTimesOpTime Accumulator >=

0)

Calculate Apportioned HI = true

11F-21C

else if (MP Stack Config for Hourly Checks == "MS")

if (Apportionment NOX Method Array == "NOXR")

Environmental Protection Agency

Page 268 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Calculate NOXM From Apportioned HI = true

if (Config HeatlnputTimesOpTime Accumulator >= 0)

Calculate Apportioned HI = true

If Apportionment OpTime Array for the location < Max Stack OpTime
return result D

else if Apportionment OpTime Array for the location > Stack OpTime Accumulator
return result E

else if (Current Entity Type o"Unit" AND Apportionment OpTime Array for the location > 0 AND the sum of Apportionment OpTime
Array for all units in the Apportionment Stack Unit List for the location == 0)
if {Current Entity Type starts with "C")
return result B

else

return result D

else if (Current Entity Type == "MS" AND MP Load UOM o "INVALID" and MP Unit Load > 0 AND Apportionment Load Array for
the location > 0)

if (MP Unit Load o Apportionment Load Array for the location)
return result F

Results:

Result
A

B

C

D

E

F

G

Usage:

1

Response

The OperatingTime reported at the common stack/pipe is less than the OperatingTime
reported for one or more units linked to the stack/pipe.

The OperatingTime reported for one (or more) stacks/pipes is greater than the sum of
the operating times reported for the units for the hour.

The HourLoad reported at the common stack/pipe is inconsistent with the load and
operating time values reported at the units linked to the stack/pipe.

The OperatingTime reported for the unit is less than the OperatingTime reported for one
or more multiple stacks linked to the unit.

The OperatingTime reported for the unit is greater than the sum of operating times at the
multiple stacks linked to the unit.

The HourLoad in the Hourly Operating record for all multiple stacks linked to this unit
are not equal.

The Heat Input Rate and Operating Time reported for the unit is inconsistent with the
Heat Input Rates and Operating Times for the configuration.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report — Hourly Configuration Evaluation

Environmental Protection Agency

Page 269 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAPP-3

Check Name:

Calculate Apportioned or Summed Heat Input Rate

Related Former Checks: HOUROP-29

Applicability:

CEM Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

Current HI Apportionment Record = null
III Calculated Apportioned Value = null
App E Checks Needed = false

If {Apportionment HI Method Array for the location contains "CALC" OR Apportionment HI Method Array for the location equals
"COMPLEX")

If (Calculate Apportioned HI = true)

Count active DerivedHourlyValueData records for location
WHERE ParameterCode = "HI"

If (Count ==1)

Current HI Apportionment Record = matching record

Heat Input Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where

else

Calculate Apportioned HI = false

11F-25

If (MP Stack Configfor Hourly Checks == "CS" AND Current HI Entity Type = "CS")

If (Calculate Apportioned HI == true)

III Calculated Apportioned Value = Config HeatlnputTimesOpTime Accumulator 1 Apportionment OpTime
Array for this Location, rounded to one decimal place.

if (Current Month is not April OR Annual Reporting Requirement == true)

If (Rpt Period HI Calculated Accumulator for this location >= 0)

Rpt Period HI Calculated Accumulator for this location = Rpt Period HI Calculated
Accumulator for this location + (III Calculated Apportioned Value * Apportionment OpTime
Array for this Location)

if (Current Month is April)

April HI Calculated Accumulator for this location = April HI Calculated Accumulator for this
location + (III Calculated Apportioned Value * Apportionment OpTime Array for this Location)

if (Current HI Apportionment Record AdjustedHourlyValue >= 0 AND ABS(Current HI Apportionment
ifecorrf.AdjustedHourlyValue - HI Calculated Apportioned Value) > Heat Input Tolerance)
return result A

else if (Apportionment OpTime Array for the location o 0)

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Calculated Accumulator for this location = -1
return result B

Parameter = "HI" AND
UOM = "MMBTUHR"

Environmental Protection Agency

Page 270 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

11 other complex situations

else if {Current HI Entity Type o "Unit")

If (Calculate Apportioned HI == true AND Current HI Apportionment Record. Ad)ustedHour\yVn\ue >= 0)

III Calculated Apportioned Value = Current HI Apportionment RecordAdjustedHourlyValue

if (Current Month is not April OR Annual Reporting Requirement == true)

If (Rpt Period HI Calculated Accumulator for this location >= 0)

Rpt Period HI Calculated Accumulator for this location = Rpt Period HI Calculated
Accumulator for this location + (HI Calculated Apportioned Value * Apportionment OpTime
Array for this Location)

if (Current Month is April)

April HI Calculated Accumulator for this location = April HI Calculated Accumulator for this
location + (HI Calculated Apportioned Value * Apportionment OpTime Array for this Location)

else if (Apportionment OpTime Array for the location o 0)

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Calculated Accumulator for this location = -1
return result B

// F-21A/B

else if ((MP Stack Configfor Hourly Checks == "CS" OR MP Pipe Configfor Hourly Checks == "CP") AND
(Apportionment HI Method Array for the location not in set {NOCALC, COMPLEX})

If (Apportionment NOXR Method Array for the location = "AE")

App E Checks Needed = true

If (Calculate Apportioned HI == true)

if (Unit LoadTimes OpTime Accumulator > 0 OR Current HI Apportionment Record. AdjustedHourly Value >=

0)

if (Unit LoadTimes OpTime Accumulator > 0)

HI Calculated Apportioned Value = (Config HeatlnputTimesOpTime Accumulator4
Apportionment OpTime Array for this Location * Apportionment Load Array for this Location /
Unit LoadTimesOpTime Accumulator) I Apportionment OpTime Array for this Location),
rounded to one decimal place.

else

HI Calculated Apportioned Value = Current HI Apportionment ifecortfAdjustedHourlyValue

III Calculated Apportioned Value = HI Calculated Apportioned Value + Apportionment Calc HI Array
for this Location

if (Current Month is not April OR Annual Reporting Requirement == true)

If (Rpt Period HI Calculated Accumulator for this location >= 0)

Rpt Period HI Calculated Accumulator for this location = Rpt Period HI Calculated
Accumulator for this location + (III Calculated Apportioned Value 4 Apportionment
OpTime Array for this Location)

if (Current Month is April)

April HI Calculated Accumulator for this location = April HI Calculated Accumulator
for this location + (III Calculated Apportioned Value * Apportionment OpTime Array

Environmental Protection Agency

Page 271 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

for this Location)

if (Current HI Apportionment ifecortfAdjustedHourly Value >= 0 AND ABS (Current HI
Apportionment itecortf.AdjustedHourlyValue - HI Calculated Apportioned Value) > Heat Input
Tolerance)

return result A

else if (Apportionment OpTime Array for the location o 0)

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Calculated Accumulator for this location = -1
return result B

else if (Apportionment OpTime Array for the location o 0)

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Calculated Accumulator for this location = -1
return result B

11 Cannot apporition or Complex configuration

else if (MP Stack Configfor Hourly Checks begins with "CS" OR MP Stack Configfor Hourly Checks == "COMPLEX" OR MP
Pipe Configfor Hourly Checks in set {CP, MULTIPLE})

If (Apportionment NOXR Method Array for the location = "AE")

App E Checks Needed = true

If (Calculate Apportioned HI == true)

If (ABS(Config HeatlnputTimesOpTime Accumulator - Unit HeatlnputTimesOpTime Accumulator) <= Heat
Input Tolerance OR Apportionment HI Method Array for the location == "COMPLEX" OR (MP Stack Config
for Hourly Checks == "COMPLEX" and MP Pipe Config for Hourly Checks is null))

HI Calculated Apportioned Value = Current HI Apportionment itecortf.AdjustedHourlyValue

if (Current Month is not April OR Annual Reporting Requirement == true)

If (Rpt Period HI Calculated Accumulator for this location >= 0)

Rpt Period HI Calculated Accumulator for this location = Rpt Period HI Calculated
Accumulator for this location + (HI Calculated Apportioned Value * Apportionment
OpTime Array for this Location)

if (Current Month is April)

April HI Calculated Accumulator for this location = April HI Calculated Accumulator
for this location + (HI Calculated Apportioned Value * Apportionment OpTime Array
for this Location)

else

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Calculated Accumulator for this location = -1
return result C

else if (Apportionment OpTime Array for the location o 0)

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Calculated Accumulator for this location = -1

Count active DerivedHourlyValueData records for location
WHERE ParameterCode = "HI"

If (Count ==1)

Current HI Apportionment Record = matching record

Environmental Protection Agency

Page 272 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (Current III Apportionment Record. Ad] Listed I Iourlv Value > 0 AND Config HeallnputTimesOpTime
Accumulator == 0)

return result D

else

return result B

III Calculated Apportioned Value = Config HeatlnputTimesOpTime Accumulator I Unit OpTime Accumulator,
rounded to one decimal place.

if (Current Month is not April OR Annual Reporting Requirement == true)

If {Rpt Period HI Calculated Accumulator for this location >= 0)

Rpt Period HI Calculated Accumulator for this location = Rpt Period HI Calculated
Accumulator for this location + (III Calculated Apportioned Value * Unit OpTime
Accumulator)

if {Current Month is April)

April HI Calculated Accumulator for this location = April HI Calculated Accumulator for this
location + (III Calculated Apportioned Value * Apportionment OpTime Array for this Location)

if (Current III Apportionment Record. Ad] Listed I Iourlv Value >= 0 AND ABS {Current HI Apportionment
ifecortf. AdjustedHourlyValue - HI Calculated Apportioned Value) > Heat Input Tolerance)

If {Calculate Apportioned HI == true)

return result A

else if {Apportionment OpTime Array for the location o 0)

if {Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Calculated Accumulator for this location = -1
return result B

Results:

Result
A

Response

The AdjustedHourlyValue reported in the DHV record for HI is inconsistent with the
recalculated apportioned or summed value.

The AdjustedHourlyValue in the DHV record for [param] could not be recalculated due
to other errors listed in this report.

The heat input calculated for the configuration is inconsistent with the sum of the
reported heat input at the units in this configuration.

You reported heat input at the unit, but there was no heat input at any of the locations
where heat input was measured.

Severity

Critical Error Level 1

B

Informational Message

C

Critical Error Level 1

D

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report — Hourly Configuration Evaluation

Environmental Protection Agency

Page 273 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAPP-4

Check Name:

Calculate NOx Mass Rate from Apportioned or Summed Heat Input Rate

Related Former Checks:

Applicability:

CEM Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

Current NOX Apportionment Based Record = null
NOX Calculated Apportionment Based Value = null

If (Calculate NOXM From Apportioned HI == true)

If (HI Calculated Apportioned Value is not null AND Apportionment Calc NOXR Array for this location >= 0)

Count active DerivedHourlyValueData records for location and hour
WHERE ParameterCode = "NOX"

If (Count ==1)

Current NOX Apportionment Based Record = matching record

NOX Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "NOX" AND
UOM = "LBHR"

NOX Calculated Apportionment Based Value = HI Calculated Apportioned Value * Apportionment Calc NOXR

Array, rounded to one decimal place.

if (Current Month is not April OR Annual Reporting Requirement == true

if (Apportionment OpTime Array for this location is between 0 and 1 (inclusive))

If (Rpt Period NOX Mass Calculated Accumulator for this location) >= 0)

Rpt Period NOX Mass Calculated Accumulator for this location = Rpt Period NOX
Mass Calculated Accumulator for this location + (NOX Calculated Apportionment
Based Value 4 Apportionment OpTime Array for this location)

if (Current Month is April)

April NOX Mass Calculated Accumulator for this location = April NOX Mass
Calculated Accumulator for this location + (NOX Calculated Apportionment Based
Value 4 Apportionment OpTime Array for this location)

else

Rpt Period NOX Mass Calculated Accumulator for this location = -1

if (Current NOX Apportionment ifecorrf AdjustedHourlyValue >= 0)

If (ABS(Current HI Apportionment ifecortfAdjustedHourlyValue - NOX Calculated Apportionment
Based Value) > NOX Tolerance)

If (Legacy Data Evaluation == false)
return result A

else if (Apportionment OpTime Array for this Location is greater than 0 and less than or equal to

1)

If (ABS(Current HI Apportionment Record. AdiustedHour\yVa\ue - NOX Calculated

Environmental Protection Agency

Page 274 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Apportionment Based Value) > NOX Tolerance / Apportionment OpTime Array for this
Location)

return result A

else

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Calculated Accumulator for this location = -1
return result B

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Calculated Accumulator for this location = -1
return result B

Results:

Result	Response	Severity

A	The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with	Critical Error Level 1

the recalculated value.

B	The AdjustedHourlyValue in the DHV record for [param] could not be recalculated due	Informational Message

to other errors listed in this report.

Usage:

1	Process/Category:	Emissions Data Evaluation Report — Hourly Configuration Evaluation

Environmental Protection Agency

Page 275 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAPP-5

Check Name:

Sum Weighted NOx Emission Rate from Multiple Stacks

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (MP Stack Configfor Hourly Checks == "MS" AND Current HI Entity Type == "Unit")

If (Config NOxRateTimesHeallnput Accumulator <> 0 OR Config NOxRateTimesOpTime Accumulator o 0)

Expected Summary Value NOx Rate Array for this location = true

If (Config NOxRateTimesHeallnput Accumulator > 0 AND Config Heatlnput Accumulator > 0 AND Rpt Period NOX
Rate Calculated Accumulator Array for this location >= 0)

Rpt Period NOX Rate Calculated Accumulator Array for this location = Rpt Period NOX Rate Calculated
Accumulator for this location + (Config NOxRateTimesHeallnput Accumulator I Config Heatlnput
Accumulator, rounded to 3 decimal places.)

Rpt Period NOX Rate Hours Accumulator Array for this location = Rpt Period NOX Rale Hours Accumulator
for this location + 1

else if (Config NOxRateTimesOpTime Accumulator > 0 AND Config OpTime Accumulator > 0 AND Rpt Period NOX
Rate Calculated Accumulator Array for this location >= 0)

Rpt Period NOX Rate Calculated Accumulator Array for this location = Rpt Period NOX Rale Calculated
Accumulator for this location + (Config NOxRateTimesOpTime Accumulator I Config OpTime Accumulator,
rounded to 3 decimal places.)

Rpt Period NOX Rate Hours Accumulator Array for this location = Rpt Period NOX Rale Hours Accumulator
for this location + 1

else

Rpt Period NOX Rate Calculated Accumulator Array for this location = -1

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report — Hourly Configuration Evaluation

Environmental Protection Agency

Page 276 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAPP-6

Check Name:

Initialize Variable for Calculating Appendix E NOx Rate via Apportionment

Related Former Checks:

Applicability:

Appendix E Check

Description:

Specifications:

If (App E Checks Needed == true)

App E Op Code = null

App E Reporting Method = "APPORTIONED'

Count active DerivedHourlyValueData records for location and hour
WHERE ParameterCode = "NOX"

If (Count == 1)

Current NOXR Apportionment Based Record = matching record

if (Current NOXR Apportionment BasedRecord MonitoringSystemlD is not null)

Mon Sys Record = find active MonitoringSystemData record for location where
MonitoringSystemData.MonitoringSy stemID = Current NOXR Apportionment Based
ifecorrf.MonitoringSystemID

if (found AND Mon Sys Recorof.SystemTypeCode == "NOXE" AND Mon iS>w,Recoraf.FuelTypeCode is not null)

if (Current XO.XR Apportionment Based Record. ()pcrati ngCondi tionCodc in set {X, Y, Z, U, W, N, M})

App E Op Code = Current NOXR Apportionment Based Record. OperatingConditionCode
App E Calc HI = HI Calculated Apportioned Value

App E Reported Value = Current NOXR Apportionment Based RecordAdjustedHourlyValue
App E Segment Number = Current NOXR Apportionment Based Record. SegmentNumber
App E NOXE System ID = Current NOXR Apportionment Based ifecorrf.MonitoringSy stemID
App E NOXE System Identifier = Current NOXR Apportionment Based
ifecortf.Systemldentifier

App E Fuel Code = Mon Sys Record.Fuel Type Code

EarliestLocationReportDate = CurrentMonitorPlanLocationRecord.E&rliestRsportD&te

else if (Current NOXR Apportionment Based Record.OpemtingConditionCode == "E")
return result A

else

return result B

else

return result C

Environmental Protection Agency

Page 277 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B
C

Usage:
1

Response

You reported an OperatingConditionCode of E in the DHV record for NOXR. You
should report the NOx emission rate for emergency fuels in an HPFF record, not a DHV
record.

The OperatingConditionCode reported in the DHV record for NOXR is missing or
invalid.

According to your monitoring plan, your reported that you are determining NOx
emission rate using the Appendix E methodology, but you did not report a
MonitoringSystemID in this record. You should report the MonitoringSystemID of the
NOXE system associated with the Appendix E fuel curve.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report — Hourly Configuration Evaluation

Environmental Protection Agency

Page 278 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURAPP-7

Check Name:

Handle NOx Rate Summary Expected for ARP

Related Former Checks:

Applicability:

Description:

Specifications:

If CurrentHIEntityType is equal to "Unit", MPStackConfigForHourly Checks is equal to "MS", and the
ExpectedSummaryValueNOxRaleArray value for this location is equal to false,

Locate a record in LocalionProgramRecordsByHourAndLocation where:

1)	ProgramCode is equal to ARP', and

2)	Class is equal to 'PI' or 'P2'.

if found,

Set ExpectedSummaryValueNOxRateArray for this location to true

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report — Hourly Configuration Evaluation

Environmental Protection Agency

Page 279 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Hourly Calculated Data

Environmental Protection Agency

Page 280 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-1

Check Name:	Calculate Percent H20

Related Former Checks:

Applicability:	CEM Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

if (H20 Method Code = "MWD" AND Current DHVRecord.ModcCode in set {01, 02, 03, 04, 53, 54})

if (H20 CEM Equation Code == "F-31")

if {Current DHV Record Valid == true AND 02 Wet Calculated Adjusted Value is not null AND 02 Dry Calculated
Adjusted Value is not null)

H20 DHV Calculated Adjusted Value = ((02 Dry Calculated Adjusted Value - 02 Wet Calculated Adjusted
Value) * 100.0 ) / 02 Dry Calculated Adjusted Value, ROUNDED to one decimal place.

H20 Cone Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "H20" AND
UOM = "PCT"

If (Derived Hourly Adjusted Value Status == true AND ABS(H20 DHV Calculated Adjusted Value - Current
.DZ/FitecortfAdjustedHourlyValue) > H20 Cone Tolerance)
return result A

else

return result B

else if (H20 CEM Equation Code == "M-1K")

if (Derived Hourly Adjusted Value Status == true)

H20 DHV Calculated Adjusted Value = Current DHV ifecorrf.AdjustedHourlyValue

else

return result B

else if (H20 Method Code = "MDF" AND Current DHV Record. ModcCode == "40")

H20 DHV Calculated Adjusted Value = H20 Default Value

else

H20 DHV Calculated Adjusted Value = Current DHV Calculated Adjusted Value

Results:

Result	Response	Severity

A	The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with	Critical Error Level 1

the recalculated value.

B	The AdjustedHourlyValue in the DHV record for [param] could not be recalculated due	Informational Message

to errors listed above.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	LOO Calculation Verification

Environmental Protection Agency

Page 281 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-3

Check Name:	Determine Diluent Cap and Moisture for C02 Concentration Calculation Verification

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

if (C02 Cone CEM Equation Code == "F-14B")

If (H20 Method Code == "MWD" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated Adjusted
Value is not null)

Calculated Moisture for C02C = H20 DHV Calculated Adjusted Value
else if (H20 Method Code in set {MMS, MTB} AND H20 Monitor Hourly Checks Needed == true AND H20 MHV Calculated
Adjusted Value is not null)

Calculated Moisture for C02C = H20 MHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated Adjusted
Value is not null)

Calculated Moisture for C02C = H20 DHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == false AND H20 Default Value is not null)
Calculated Moisture for C02C = H20 Default Value

if (Use 02 Diluent Cap for Co2 Cone Calc == true)

02X Count = # of active MonitoringDefault records for location where
ParameterCode = '02X' AND DefaultPurposeCode = 'DC' AND
FuelCode = 'NFS'
if (02X Count >1)

return result A
else if (02X Count == 0)
return result B
else if MonitoringDefault.DefaultValue <= 0
return result C

else

Calculated Diluent for C02C = MonitoringDefault.DefaultValue

else

case (CO2 Cone CEM Equation Code)

"F-14A":

Calculated Diluent for C02C = 02 Dry Calculated Adjusted Value

"F-14B":

Calculated Diluent for C02C= 02 Wet Calculated Adjusted Value

Results:

Result
A

B

Usage:
1

Response

You reported more than one diluent cap default record for 02X in your monitoring plan
that was active during current hour.

You did not report a default record for 02X in your monitoring plan that was active
during the current hour. Please note that the use of a diluent cap to calculate C02
concentration is only applicable to legacy data.

The DefaultValue reported in the active Default record for 02X in your monitoring plan
is invalid. The value must be greater than 0.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	C02 Concentration Calculation Verification

Environmental Protection Agency

Page 282 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-4

Check Name:

Calculate C02 Concentration

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (Current DHV Record.ModcCode in set {01, 02, 03, 04, 53, 54})

C02 Cone Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerance" where
Parameter = "C02C" AND
UOM = "PCT"

case (CO2 Cone CEM Equation Code)
"F-14A":

If (Current DHV Record Valid == true AND Calculated Diluent for C02C is not null AND Valid FC Factor
Exists == true AND Valid FD Factor == true)

C02C DHV Calculated Adjusted Value = 100 * (Current Hourly Op Recorded* actor I Current Hourly
Op ifecortf.FdFactor) * [(20.9 - Calculated Diluent for C02C) / 20.9 ], and round the result to 1 decimal
place.

If (C02C DHV Calculated Adjusted Value < 0)

C02C DHV Calculated Adjusted Value = 0

If (Derived Hourly Adjusted Value Status == true AND ABS(C02C DHV Calculated Adjusted Value -
Current DHV Record. AdjustedHourly Value) > C02 Cone Tolerance)
return result A

else

return result B

'F-14B":

If (Current DHV Record Valid == true AND Calculated Diluent for C02C is not null AND Valid FC Factor
Exists == true AND Valid FD Factor Exists == true AND Calculated Moisture for C02C is not null)

C02C DHV Calculated Adjusted Value = [100/20 .9] * (Current Hourly Op Record. I d ac tor ICurrent
Hourly Op Record.FdF actor) * [20.9 * ((100 - Calculated Moisture for C02C)l 100) - Calculated Diluent
for C02C ], and round the result to 1 decimal place.

If (C02C DHV Calculated Adjusted Value < 0)

C02C DHV Calculated Adjusted Value = 0

If (Derived Hourly Adjusted Value Status == true AND ABS(C02C DHV Calculated Adjusted Value -
Current DHV Record. AdjustedHourlyValue) > C02 Cone Tolerance)
return result A

else

return result B

Otherwise

return result B

else

C02C DHV Calculated Adjusted Value = Current DHV Calculated Adjusted Value

Environmental Protection Agency

Page 283 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result	Response	Severity

A	The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with	Critical Error Level 1

the recalculated value.

B	The AdjustedHourlyValue in the DHV record for [param] could not be recalculated due	Informational Message

to errors listed above.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Concentration Calculation Verification

Environmental Protection Agency

Page 284 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-6

Check Name:	Determine Diluent Cap and Moisture for Heat Input Calculation Verification

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

If {Heat Input Method Code == "CEM")

if {Heat Input Equation Code in set {F-16, F-17, F-18}

If {H20 Method Code == "MWD" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for HI = H20 DHV Calculated Adjusted Value
else if {H20 Method Code in set {MMS, MTB} AND H20 Monitor Hourly Checks Needed == true AND H20 MHV
Calculated Adjusted Value is not null)

Calculated Moisture for HI = H20 MHV Calculated Adjusted Value
else if {H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for HI = H20 DHV Calculated Adjusted Value
else if {H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == false AND H20 Default Value is
not null)

Calculated Moisture for HI = H20 Default Value

if {Heat Input Equation Code = "F-15" OR Heat Input Equation Code = "F-16"

If (Current 1)11]' Record.\)\ I ucntCapI ndicator == 1)

C02N Count = # of active MonitoringDefault records for the location where
ParameterCode = 'C02N' AND DefaultPurposeCode = 'DC' AND
FuelCode = 'NFS'
if {C02N Count >1)

return result A
else if {C02N Count == 0)

return result B
else if MonitoringDefault.DefaultValue <= 0
return result C

else

Calculated Diluent For HI = MonitoringDefault.DefaultValue

else if (CO 2 Cone Checks Needed for Heat Input == true)

if {Current C02 Cone Missing Data Monitor Hourly Record is not null)

Calculated Diluent for HI = C02C SD Calculated Adjusted Value

else

Calculated Diluent for HI = C02C MHV Calculated Adjusted Value

else if {Heat Input Equation Code == "F-17" OR Heat Input Equation Code == "F-18")
if (Current 1)11]' Record.\ )i I ucntCapI ndicator == 1)

02X Count = # of active MonitoringDefault records for the location where
ParameterCode = '02X' AND DefaultPurposeCode = 'DC' AND
FuelCode = 'NFS'
if {02X Count >1)

return result D
else if {02X Count == 0)

return result E
else if MonitoringDefault.DefaultValue <= 0
return result F

else

Calculated Diluent For HI = MonitoringDefault.DefaultValue

else if {Heat Input Equation Code == "F -17" AND 02 Wet Checks Needed for Heat Input == true)

Environmental Protection Agency

Page 285 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (Current 02 Wet Missing Data Monitor Hourly Record is not null)

Calculated Diluent for HI = 02C SD Calculated Adjusted Value

else

Calculated Diluent for HI = 02 Wet Calculated Adjusted Value

else if (Heat Input Equation Code == "F -18" AND 02 Dry Checks Needed for Heat Input == true)

if (Current 02 Dry Missing Data Monitor Hourly Record is not null)

Calculated Diluent for HI = 02C SD Calculated Adjusted Value

else

Calculated Diluent for HI = 02 Dry Calculated Adjusted Value

Results:

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Usage:

1	Process/Category:	Emissions Data Evaluation Report	Heat Input Calculation Verification

Result	Response

A	You reported more than one diluent cap default record for C02N in your monitoring

plan that was active during the current hour.

B	You did not report an active C02N diluent cap default record in your monitoring plan

for the hour. The use of the diluent cap to calculate HI is only applicable for legacy
data.

C	The DefaultValue reported in the active Default record for C02N in your monitoring

plan is invalid. The value must be greater than 0.

D	You reported more than one diluent cap default record for 02X in your monitoring plan

that was active during current hour.

E	You did not report a default record for 02X in your monitoring plan that was active

during the current hour. Please note that the use of a diluent cap to calculate HI is only
applicable to legacy data.

F	The DefaultValue reported in the active Default record for 02X in your monitoring plan

is invalid. The value must be greater than 0.

Environmental Protection Agency

Page 286 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-7

Check Name:

Calculate Heat Input

Related Former Checks:

Applicability:

General Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

if (Derived Hourly Adjusted Value Status == true AND Current Hourly Op ifecorrf.OperatingTime is between 0 and 1 (inclusive))

Heat Input Total Reported Value = Current Dill' Record. Ad] ustcdl Iourl v Val Lie * Current Hourly Op Record. () p c ra t i n g T im c.
if (Current Month is not April OR Annual Reporting Requirement == true)

if (Current Entity Type == "Unit" AND Unit HeatlnputTimesOpTime Accumulator >= 0)

Unit HeatlnputTimesOpTime Accumulator = Unit HeatlnputTimesOpTime Accumulator + Heat Input Total Reported
Value

else

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Reported Accumulator Array for this location = -1
if (Current Entity Type == "Unit")

Unit HeatlnputTimesOpTime Accumulator = -1

Total Heat Input from Fuel Flow = null

If (Heat Input Method Code == "CEM")

case (Heat Input Equation Code)

= "F-15":

If (Current DHV Record Valid == true AND Calculated Diluent for HI is not null AND Valid FC Factor Exists
== true AND FLOW Calculated Adjusted Value is not null)

HI Calculated Adjusted Value = (FLOW Calculated Adjusted Value * Calculated Diluent for Heat
Input) I (Current Hourly Op ifecortf.FcFactor * 100.0), and round the result to 1 decimal place.

else

return result A

= "F-16":

If (Current DHV Record Valid == true AND Calculated Diluent for HI is not null AND Valid FC Factor Exists
== true AND FLOW Calculated Adjusted Value is not null AND Calculated Moisture for HI is not null)

HI Calculated Adjusted Value = [FLOW Calculated Adjusted Value * (100 - Calculated Moisture for
HI) * Calculated Diluent for HI] I (10,000 * Current Hourly Op Record. Ic I ac tor), and round the result
to 1 decimal place.

else

return result A

= "F-17":

If (Current DHV Record Valid == true AND Calculated Diluent for HI is not null AND Valid FD Factor Exists

Environmental Protection Agency

Page 287 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

== true AND FLOW Calculated Adjusted Value is not null AND Calculated Moisture for HI is not null)

III Calculated Adjusted Value = [FLOW Calculated Adjusted Value * (1 / Current Hourly Op
itecortf.FdFactor)* [ 0.209 * (100 - Calculated Moisture for HI) - Calculated Diluent for HI\ 120.9) ],
and round the result to 1 decimal place.

else

return result A

= "F-18":

If (Current DHV Record Valid == true AND Calculated Diluent for HI is not null AND Valid FD Factor Exists
== true AND FLOW Calculated Adjusted Value is not null AND Calculated Moisture for HI is not null)

III Calculated Adjusted Value = (FLOW Calculated Adjusted Value *[100 - Calculated Moisture for
HI] * [20.9 - Calculated Diluent for HI\ ) / (2090 * Current Hourly Op itecortf.FdFactor), and round the
result to 1 decimal place.

else

return result A

= All Other Equation Codes:
return result A

if no result

if (III Calculated Adjusted Value is less than 1 AND Legacy Data Evaluation == false)

III Calculated Adjusted Value = 1

Apportionment Calc HI Array at this Location = HI Calculated Adjusted Value
if (MP Stack Config for Hourly Checks == "MS")

Config Heatlnput Accumulator = Config Heatlnput Accumulator + HI Calculated Adjusted Value

if result A

Apportionment Calc HI Array at this Location = -1
Config HeatlnputTimesOpTime Accumulator = -1

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Calculated Accumulator Array for this location = -1
if (MP Stack Config for Hourly Checks == "MS")

Config Heatlnput Accumulator = -1

else if (Heat Input App D Method Active for Hour == true)

if (HI App D Accumulator >= 0)

Total Heat Input from Fuel Flow = HI App D Accumulator

if (HI App D Accumulator >= 0 AND Current Hourly Op itecortf.OperatingTime is greater than 0 and less than or equal to 1)

Apportionment Calc HI Array at this Location = HI App D Accumulator I Current Hourly Op ifecorrf.OperatingTime,
rounded to one decimal place.

if (Heat Input Method Code == "AD")

III Calculated Adjusted Value = Apportionment Calc HI Array at this Location
App E Calc HI = HI Calculated Adjusted Value

else

for each location in the configuration where Apportionment HI Method Array in set {CALC, ADCALC}
set Apportionment HI Method Array for this location to "NOCALC"

else

Apportionment Calc HI Array at this Location = -1
Config HeatlnputTimesOpTime Accumulator = -1

if (Current Month is not April OR Annual Reporting Requirement == true)

Environmental Protection Agency

Page 288 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Rpt Period HI Calculated Accumulator Array for this location = -1
return result A

else if {Heat Input Method Code NOT in set {ADCALC, CALC})

III Calculated Adjusted Value = Current DHV Calculated Adjusted Value
Apportionment Calc HI Array at this Location = HI Calculated Adjusted Value

If {HI Calculated Adjusted Value is not null)

If {Current Hourly Op i?ecortf.OperatingTime is between 0 and 1 inclusive)

Heat Input Total Calculated Value = HI Calculated Adjusted Value * Current Hourly Op itecortf.OperatingTime.

if ( Config HeatlnputTimesOpTime Accumulator >= 0)

Config HeatlnputTimesOpTime Accumulator = Config HeatlnputTimesOpTime Accumulator + Heat Input
Total Calculated Value

if {Current Month is not April OR Annual Reporting Requirement == true)

if {Rpt Period HI Calculated Accumulator Array for this location is not null)

if {Rpt Period HI Calculated Accumulator Array for this location >= 0)

Rpt Period HI Calculated Accumulator Array for this location = Rpt Period HI Calculated
Accumulator Array for this location + Heat Input Total Calculated Value

else

Rpt Period HI Calculated Accumulator Array for this location = Heat Input Total Calculated Value

if {Current Month is April)

if {April HI Calculated Accumulator Array for this location is not null)

April HI Calculated Accumulator Array for this location = April HI Calculated Accumulator
Array for this location + Heat Input Total Calculated Value

else

April HI Calculated Accumulator Array for this location = Heat Input Total Calculated Value

else

Config HeatlnputTimesOpTime Accumulator = -1

if {Current Month is not April OR Annual Reporting Requirement == true)
Rpt Period HI Calculated Accumulator Array for this location = -1

If {Derived Hourly Adjusted Value Status == true)

If {Heat Input Method Code in set {CEM, AD})

if {HI Calculated Adjusted Value is equal to 1 AND Current Dill' Record. Ad] ustcdl Iourl v Val Lie is less than 1
AND Current DHV Record.)CCodc is not equal to "26" and Legacy Data Evaluation == false)
return result C

else

Heat Input Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "HI" AND
UOM = "MMBTUHR"

if (ABS{Current DHV Record A d j ustedHourly Value - III Calculated Adjusted Value) > Heat Input
Tolerance)

return result B

else if {Apportionment Calc HI Array at this Location is greater than or equal to 0) \\ ADCALC
If {Current Hourly Op i?ecortf.OperatingTime is between 0 and 1 inclusive)

Environmental Protection Agency

Page 289 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Heat Input Total Calculated Value = Apportionment Calc HI Array at this Location * Current Hourly Op
R ecord. Operati ng Time.

if ( Config HeatlnputTimesOpTime Accumulator >= 0)

Config HeatlnputTimesOpTime Accumulator = Config HeatlnputTimesOpTime Accumulator + Heat Input
Total Calculated Value

else

Config HeatlnputTimesOpTime Accumulator = -1

else if {Heat Input Method Code not in set {ADCALC, CALC})

Apportionment Calc HI Array at this Location = -1
Config HeatlnputTimesOpTime Accumulator = -1

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period HI Calculated Accumulator Array for this location = -1

Results:

Result
A

B

C

Usage:

1

Response

The AdjustedHourlyValue in the DHV record for [param] could not be recalculated due
to errors listed above.

The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with
the recalculated value.

You reported in AdjustedHourlyValue of less than 1 in the DHV record for [param].
You must report a minimum heat input of 1 and a MODCCode of "26".

Severity

Informational Message
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Heat Input Calculation Verification

Environmental Protection Agency

Page 290 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-9

Check Name:	Calculate S02 Mass Emissions

Related Former Checks:

Applicability:	CEM Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

if (Derived Hourly Adjusted Value Status == true AND Current Hourly Op ifecorrf.OperatingTime is between 0 and 1 (inclusive))

S02 Total Reported Value = Current 1)11]' /feewY/.Adjustedl Iourlv Value * Current Hourly Op Record. OperatingTime.
if (Rpt Period S02 Mass Reported Accumulator Array for this location is not null)

if (Rpt Period S02 Mass Reported Accumulator Array for this location >= 0)

Rpt Period S02 Mass Reported Accumulator Array for this location = Rpt Period S02 Mass Reported
Accumulator Array for this location + S02 Total Reported Value

else

Rpt Period S02 Mass Reported Accumulator Array for this location = SO2 Total Reported Value

else

Rpt Period S02 Mass Reported Accumulator Array for this location = -1

If (SO2 CEM Method Active for Hour == true)

if (S02 Equation Code == "F-l")

If (Current DHV Record Valid == true AND S02C Calculated Adjusted Value is not null AND FLOW Calculated
Adjusted Value is not null)

S02 Calculated Adjusted Value = 0.000000166 * S02C Calculated Adjusted Value 4 FLOW Calculated
Adjusted Value, ROUNDED to one decimal place.

else

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1
return result A

else if (S02 Equation Code == "F-2")

If (Current DHV Record Valid == true AND S02C Calculated Adjusted Value is not null AND FLOW Calculated
Adjusted Value is not null AND Calculated Moisture for S02 is not null)

S02 Calculated Adjusted Value = 0.000000166 * S02C Calculated Adjusted Value * FLOW Calculated
Adjusted Value * (100.0 - Calculated Moisture for S02) I 100.0, ROUNDED to one decimal place.

else

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1
return result A

else

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1
return result A

else if (S02 F23 Method Active for Hour == true)

If (Current DHV Record Valid == true AND 123 Default Value is not null AND HI Calculated Adjusted Value is not
null)

S02 Calculated Adjusted Value = F23 Default Value * HI Calculated Adjusted Value, rounded to one decimal
place.

Environmental Protection Agency

Page 291 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1
return result A

else if (S02 App D Method Active for Hour == true)

if (S02 App D Accumulator >= 0 AND Current Hourly Op itecortf.OperatingTime is between 0 and 1 (inclusive))
S02 Calculated Adjusted Value = S02 App D Accumulator I Current Hourly Op ifecorrf.OperatingTime.

If (Hourly Fuel Flow Count For Gas is greater than 0)

Round S02 Calculated Adjusted Value to four decimal places.

else

Round S02 Calculated Adjusted Value to one decimal place.

else

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1
return result A

else

S02 Calculated Adjusted Value = Current DHV Calculated Adjusted Value

If (SO 2 Calculated Adjusted Value is not null)

If {Current Hourly Op i?ecortf.OperatingTime is between 0 and 1 inclusive)

S02 Total Calculated Value = S02 Calculated Adjusted Value * Current Hourly Op ifecorrf.OperatingTime

if (Rpt Period S02 Mass Calculated Accumulator Array for this location is not null)

if (Rpt Period S02 Mass Calculated Accumulator Array for this location >= 0)

Rpt Period S02 Mass Calculated Accumulator Array for this location = Rpt Period S02 Mass
Calculated Accumulator Array for this location + S02 Total Calculated Value

else

Rpt Period S02 Mass Calculated Accumulator Array for this location = S02 Total Calculated Value

else

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1

If (Derived Hourly Adjusted Value Status == true)

S02 Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "S02" AND
UOM = "LBHR"

if (ABS(CMrren?Z)//Fifecorrf.AdjustedHourlyValue - S02 Calculated Adjusted Value) > S02 Tolerance)
return result B

else

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1

Results:

Result	Response	Severity

A	The AdjustedHourlyValue in the DHV record for [param] could not be recalculated due	Informational Message

to errors listed above.

B	The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with	Critical Error Level 1

the recalculated value.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	S02 Calculation Verification

Environmental Protection Agency

Page 292 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-12

Check Name:	Determine Diluent Cap, Moisture, and NOXC for NOx Rate Calculation Verification

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

If {Current NOx Rate Method Code == "CEM" AND Current DHVRecord.ModcCode in set {01, 02, 03, 04, 14, 22, 53, 54})

if (NOx Cone Monitor Hourly Count == 1 AND Current NOx Cone Monitor Hourly ifecorrf.UnadjustedHourlyValue is not null)
NOx Cone for NOx Rate Calculation = Current NOx Cone Monitor Hourly ifecorrf.UnadjustedHourly Value

else

NOx Cone for NOx Rate Calculation = null

if (NOx Rate Equation Code in set {19-3, 19-3D, 19-4, 19-5, 19-8, 19-9})

If (H20 Method Code == "MWD" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for NOXR = H20 DHV Calculated Adjusted Value
else if (H20 Method Code in set {MMS, MTB} AND H20 Monitor Hourly Checks Needed == true AND H20 MHV
Calculated Adjusted Value is not null)

Calculated Moisture for NOXR = H20 MHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for NOXR = H20 DHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == false AND H20 Default Value is
not null)

Calculated Moisture for NOXR = H20 Default Value
if (NOx Rate Equation Code in set {19-3D, 19-5D} OR Current Dill' Record. ModcCode == 14)

If (NOx Rate Equation Code in set {F-5, 19-1, 19-2, 19-3, 19-3D, 19-4, 19-5, 19-5D})

02 Monitor Default Matches = count of # active MonitoringDefaultData records for location where

MonitoringDefaultData.ParameterCode = "02X" AND MonitoringDefaultData.DefaultPurposeCode =
"DC" AND MonitoringDefaultData.FuelCode = "NFS"

if 02 Monitor Default Matches > 1

return result A
else if 02 Monitor Default Matches = 0
return result B

else

02 Monitor Default Record = the single matched record

if ( 02 Monitor Default Record.DefaultValue is NULL OR 02 Monitor Default Record.DefaultValue <=

0)

return result C

else

Calculated Diluent for NOXR = 02 Monitor Default .Recoraf.DefaultValue

else if (NOx Rate Equation Code in set {F-6, 19-6, 19-7, 19-8, 19-9})

CO2 Monitor Default Matches = count of # active MonitoringDefaultData records for location where

MonitoringDefaultData.ParameterCode = "C02N" AND MonitoringDefaultData.DefaultPurposeCode =
"DC" AND MonitoringDefaultData.FuelCode = "NFS"

if CO2 Monitor Default Matches > 1

return result D
else if C02 Monitor Default Matches = 0
return result E

Environmental Protection Agency

Page 293 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

C02 Monitor Default Record = the single matched record

if (C02 Monitor Default Record.DefmAW&\ue is NULL OR C02 Monitor Default Record.DefaultValue
<=0)

return result F

else

Calculated Diluent for NOx Rate = C02 Monitor Default .Recoraf.DefaultValue

If {NOx Rate Equation Code in set {F-5, 19-1, 19-4} AND 02 Dry Checks Needed for NOx Rate Calc == true)
Calculated Diluent for NOx Rate = 02 Dry Calculated Adjusted Value

else if (NOx Rate Equation Code in set {19-2, 19-3, 19-5} AND 02 Wet Checks Neededfor NOx Rate Calc == true)
Calculated Diluent for NOx Rate = 02 Wet Calculated Adjusted Value

else if (NOx Rate Equation Code in set {F-6, 19-6, 19-7, 19-8, 19-9} AND C02 Cone Monitor Hourly Checks Needed
== true)

Calculated Diluent for NOx Rate = C02C MHV Calculated Adjusted Value

else

Results:

Result
A

Response

You reported more than one diluent cap default record for 02X in your monitoring plan
that was active during current hour.

You did not report a default record for 02X in your monitoring plan that was active
during current hour.

The DefaultValue reported in the active Default record for 02X in your monitoring plan
is invalid. The value must be greater than 0.

You reported more than one diluent cap default record for C02N in your monitoring
plan that was active during the current hour.

You did not report an active C02N diluent cap default record in your monitoring plan
for the hour.

The DefaultValue reported in the active Default record for C02N in your monitoring
plan is invalid. The value must be greater than 0.

Severity

Critical Error Level 1

B

Critical Error Level 1

C

Critical Error Level 1

D

Critical Error Level 1

E

Critical Error Level 1

F

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Environmental Protection Agency

Page 294 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-13

Check Name:

Calculate Unadjusted NOx Emissions Rate

Related Former Checks:

Applicability:

CEM Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

XO.XR Calculated Unadjusted Value = null
Derived Hourly Unadjusted Calculation Status = false

If (Current NOx Rate Method Code == "CEM" AND Current DHV Record. ModcCodc in set {01, 02, 03, 14, 22, 53})

If {Current DHVifecortf.SystemTypeCode == "NOX")

RATA Status Required = true

case (NOx Rate Equation Code)

"19-1" or "F-5":

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FD Factor Exists == true)

if (Calculated Diluent for NOXR == 20.9)
return result A

else

NOXR Calculated Unadjusted Value = 0.0000001194 * NOX Cone for NOx Rate Calc * Current Hourly
Op ifecorrf.FdFactor * [20.9 / (20.9 - Calculated Diluent for NOXR)], rounded to 3 decimal places.

else

return result B

19-2":

Moisture Fraction = null

BWA Default Record Count = count active MonitoringDefaultData Records for the location where ParameterCd = 'BWA'

If (BWA Default Record Count == 0)

Moisture Fraction = 0.027
else If (BWA Default Record Count == 1 AND MonitorDefaultData.DefaultValue > 0 AND
MonitorDefaultData.DefaultValue < 1)

Moisture Fraction = MonitorDefaultData.DefaultValue

else

return result D

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FWFactor Exists == true AND Moisture Fraction is not null)

if (Calculated Diluent for NOXR == 20.9 * (1 - Moisture Fraction))
return result A

else

NOXR Calculated Unadjusted Value = 0.0000001194 * NOX Cone for NOx Rate Calc * Current Hourly
Op R ecord.FwF actor * [20.9 / (20.9 *(1 - Moisture Fraction) - Calculated Diluent for NOXR)], rounded
to 3 decimal places.

else

return result B

Environmental Protection Agency

Page 295 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

19-3":

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FD Factor Exists == true AND Calculated Moisture for NOXR is not null)

if (Calculated Diluent for NOXR == 20.9*(100 - Calculated Moisture for NOXR) /100 )
return result A

else

denom = (20.9*(100 - Calculated Moisture for NOXR )/l 00 - Calculated Diluent for NOXR)

NOXR Calculated Unadjusted Value = 0.0000001194 * NOX Cone for NOx Rate Calc * Current Hourly

Op ifecortf.FdFactor * [20.9 /denom ], rounded to 3 decimal places.

else

return result B

19-3D":

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FD Factor Exists == true AND Calculated Moisture for NOXR is not null)

h2oFactor = (100 - Calculated Moisture for NOXR) I 100.0
denomTerm = (20.9 * h2oFactor) - (Calculated Diluent for NOXR * h2oFactor)
if ( denomTerm == 0)
return result A

else

NOXR Calculated Unadjusted Value = 0.0000001194 * NOX Cone for NOx Rate Calc * Current Hourly
Op ifecortf.FdFactor * 20.9 I denomTerm, rounded to 3 decimal places.

else

return result B

"19-4":

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FD Factor Exists == true AND Calculated Moisture for NOXR is not null)

if ( Calculated Diluent for NOXR == 20.9 OR Calculated Moisture for NOXR == 100)
return result A

else

NOXR Calculated Unadjusted Value = 0.0000001194 * NOX Cone for NOx Rate Calc * Current Hourly
Op ifecorrf.FdFactor / [ (100 - Calculated Moisture for NOXR) I 100.0] * (20.9 / (20.9 - Calculated
Diluent for NOXR)), rounded to 3 decimal places.

else

return result B

19-5":

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FD Factor Exists == true AND Calculated Moisture for NOXR is not null)

if (Calculated Moisture for NOXR == 100)
return result A

H20Term = (100 - Calculated Moisture for NOXR) / 100.0
denom = 20.9 - Calculated Diluent for NOXR / FOOTerm

if (denom == 0)

return result A

Environmental Protection Agency

Page 296 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

NOXR Calculated Unadjusted Value = 0 .0000001194 * XO.X Cone for NOx Rate Calc '
Current Hourly Op Record. Id I ac to r I denom, rounded to 3 decimal places.

else

return result B

"19-5D":

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FD Factor Exists == true)

if (Calculated Diluent for NOXR == 20.9)
return result A

else

NOXR Calculated Unadjusted Value = 0.0000001194 * NOX Cone for NOx Rate Calc * Current Hourly
Op ifecortf.FdFactor * 20.9/ (20.9 - Calculated Diluent for NOXR), rounded to 3 decimal places.

else

return result B
"19-6" or "19-7" or "F-6":

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FC Factor Exists == true)

if (Calculated Diluent for NOXR == 0.0)
return result A

else

NOXR Calculated Unadjusted Value = 0.0000001194 * NOX Cone for NOx Rate Calc * Current Hourly
Op ifecortf.FcFactor * 100.0 I Calculated Diluent for NOXR , rounded to 3 decimal places.

else

return result B

"19-8":

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FC Factor Exists == true AND Calculated Moisture for NOXR is not null)

if (Calculated Diluent for NOXR == 0.0 OR Calculated Moisture for NOXR == 100)
return result A

else

NOXR Calculated Unadjusted Value = 0.0000001194 * NOX Cone for NOx Rate Calc * Current Hourly
Op Record.VcF actor / [ (100 - Calculated Moisture for NOXR) / 100.0] *(100.0/Calculated Diluent
for NOXR ), rounded to 3 decimal places.

else

return result B

"19-9":

If (Current DHV Record Valid == true AND Calculated Diluent for NOXR is not null AND NOX Cone for NOx Rate
Calc is not null AND Valid FC Factor Exists == true AND Calculated Moisture for NOXR is not null)

if (Calculated Diluent for NOXR == 0.0)
return result A

else

H20Term = (100 - Calculated Moisture for NOXR) I 100.0
C02Term = 100.0 I Calculated Diluent for NOXR

NOXR Calculated Unadjusted Value = 0.0000001194 * NOX Cone for NOx Rate Calc * Current Hourly
Op ifecorrf.FcFactor * H20Term * C02Term, rounded to 3 decimal places.

Environmental Protection Agency

Page 297 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

return result B

If (Derived Hourly Unadjusted Value Status == true AND NOXR Calculated Unadjusted Value is not null)

Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "NOXR" AND
UOM = "LBMMBTU"

if (ABS(CMrren?Z)//Fifecorrf.UnadjustedHourlyValue - NOXR Calculated Unadjusted Value) > Tolerance)
return result C

else

Derived Hourly Unadjusted Calculation Status = true

else if (Current NOx Rate Method Code == "PEM" AND Current DHVRecord ModcCode in set {01, 02, 03})

If (Current DHVifecortf.SystemTypeCode == "NOXP")

RATA Status Required = true

If Current DHVifecorrf.UnadjustedHourlyValue >= 0

NOXR Calculated Unadjusted Value = Current Z)//Fifecorrf.UnadjustedHourlyValue
Derived Hourly Unadjusted Calculation Status = true

else if (Current NOx Rate Method Code == "AE")

If (App E Constant Fuel Mix == true)

NOXR Calculated Adjusted Value = App E Calculated NOx Rate for Source

else

NOXR Calculated Adjusted Value = Current DHV Calculated Adjusted Value

if (Current NOx Rate Method Code in set {CEM, PEM} AND Current Dill' Record. ModcCode ==21)

If (Current DHVRecord.SystemTypeCode in set {NOX, NOXP})

RATA Status Required = true

Results:

Result

B
C
D

Response

The NOx emission rate could not be recalculated, because the diluent and/or moisture
value would result in division by zero. You should report an MODC of 14 indicating
the use of a diluent cap to prevent this.

The UnadjustedHourlyValue in the DHV record for [param] could not be recalculated
due to errors listed above.

The UnadjustedHourlyValue reported in the DHV record for [param] is inconsistent
with the recalculated value.

You did not report a single valid MonitorDefault record for ParameterCode BWA for
the hour.

Severity

Critical Error Level 1

Informational Message
Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Environmental Protection Agency

Page 298 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-15

Check Name:

Determine Moisture for NOx Mass Calculation Verification

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (NOx Mass Monitor Method Code begins with "CEM")
If (NOx Mass Equation Code == "F-26B")

If (H20 Method Code == "MWD" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for NOX = H20 DHV Calculated Adjusted Value
else if (H20 Method Code in set {MMS, MTB} AND H20 Monitor Hourly Checks Needed == true AND H20 MHV
Calculated Adjusted Value is not null)

Calculated Moisture for NOX = H20 MHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for NOX = H20 DHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == false AND H20 Default Value is
not null)

Calculated Moisture for NOX = H20 Default Value

Results:

Result

Response

Severity

Usage:

Process/Category:

Emissions Data Evaluation Report	NOx Mass Rate Calculation Verification

Environmental Protection Agency

Page 299 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-16

Check Name:	Calculate NOx Mass Emissions

Related Former Checks:

Applicability:	CEM Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

if (Derived Hourly Adjusted Value Status == true AND Current Hourly Op ifecorrf.OperatingTime is between 0 and 1 (inclusive))

NOX Mass Total Reported Value = Current Dill' Record. Ad] Listed [ Iourl v Val Lie * Current Hourly Op ifecorrf.OperatingTime.
if (Current Month is not April OR Annual Reporting Requirement == true)

if (Rpt Period NOX Mass Reported Accumulator Array for this location is not null)

if (Rpt Period NOX Mass Reported Accumulator Array for this location >= 0)

Rpt Period NOX Mass Reported Accumulator Array for this location = Rpt Period NOX Mass Reported
Accumulator Array for this location + NOX Mass Total Reported Value

else

Rpt Period NOX Mass Reported Accumulator Array for this location = NOX Mass Total Reported Value

else

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Reported Accumulator Array for this location = -1

If (NOx Mass Monitor Method Code in set {CEM, NOXR, CEMNOXR})

if (NOx Mass Equation Code == "F-26A")

If (Current DHV Record Valid == true AND NOXC Calculated Adjusted Value is not null AND FLOW Calculated
Adjusted Value is not null)

NOX Calculated Adjusted Value = 0 .0000001194 * NOXC Calculated Adjusted Value * Stack Flow Calculated
Adjusted Value, ROUNDED to one decimal place.

else

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Calculated Accumulator Array for this location = -1
return result A

else if (NOXMass Equation Code == "F-26B")

If (Current DHV Record Valid == true AND NOXC Calculated Adjusted Value is not null AND FLOW Calculated
Adjusted Value is not null AND Calculated Moisture for NOX is not null)

NOX Calculated Adjusted Value = 0.0000001194 * NOXC Calculated Adjusted Value * FLOW Calculated
Adjusted Value * (100.0 - Calculated Moisture for NOX) I 100.0, ROUNDED to one decimal place.

else

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Calculated Accumulator Array for this location = -1
return result A

else if (NOXMass Equation Code == "F-24A")

if (Heat Input Method Code NOT in set {CALC, ADCALC})

If (Current DHV Record Valid == true AND NOXR Calculated Adjusted Value is not null

Environmental Protection Agency

Page 300 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If {HI Calculated Adjusted Value is not null)

XO.X Calculated Adjusted Value = NOXR Calculated Adjusted Value * HI Calculated Adjusted
Value, ROUNDED to one decimal place.

else

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Calculated Accumulator Array for this location = -1
return result A

else

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Calculated Accumulator Array for this location = -1
return result A

else

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Calculated Accumulator Array for this location = -1
return result A

else

NOX Calculated Adjusted Value = Current DHV Calculated Adjusted Value

If (NOX Calculated Adjusted Value is not null)

If {Current Hourly Op i?ecortf.OperatingTime is between 0 and 1 inclusive)

NOx Mass Total Calculated Value = NOX Calculated Adjusted Value * Current Hourly Op ifecorrf.OperatingTime.

if {Current Month is not April OR Annual Reporting Requirement == true)

if {Rpt Period NOX Mass Calculated Accumulator Array for this location is not null)

if {Rpt Period NOX Mass Calculated Accumulator Array for this location >= 0)

Rpt Period NOX Mass Calculated Accumulator Array for this location = Rpt Period NOX Mass
Calculated Accumulator Array for this location + NOX Mass Total Calculated Value

else

Rpt Period NOX Mass Calculated Accumulator Array for this location = NOX Mass Total Calculated
Value

if {Current Month is April)

if {April NOX Mass Calculated Accumulator Array for this location is not null)

April NOX Mass Calculated Accumulator Array for this location = April NOX Mass Calculated
Accumulator Array for this location + NOX Mass Total Calculated Value

else

April NOX Mass Calculated Accumulator Array for this location = NOX Mass Total Calculated
Value

else

if {Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Calculated Accumulator Array for this location = -1

If {Derived Hourly Adjusted Value Status == true AND Current DHV Method in set {CEM, NOXR, CEMNOXR})

NOX Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "NOX" AND
UOM = "LBHR"

if {ABS{Current DHV Record. AdjustedHourly Value - NOX Calculated Adjusted Value) > NOX Tolerance)
If {Legacy Data Evaluation == false)
return result B

else if {Current Hourly Op Data.OpTime is greater than 0 and less than or equal to 1)

Environmental Protection Agency

Page 301 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (ABS(Current .M/Fifecortf. AdjustedHourlyValue - XO.X Calculated Adjusted Value) > NOX
Tolerance / Current Hourly Opifecorrf.OperatingTime)
return result B

else if (NOX Mass Equation Code o "F-24A" OR Current DHV Record Valid== false OR NOXR Calculated Adjusted Value is null OR
Heat Input Method Code NOT in set {CALC, ADCALC})

if (Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period NOX Mass Calculated Accumulator Array for this location = -1

Results:

Result	Response	Severity

A	The AdjustedHourlyValue in the DHV record for [param] could not be recalculated due	Informational Message

to errors listed above.

B	The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with	Critical Error Level 1

the recalculated value.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	NOx Mass Rate Calculation Verification

Environmental Protection Agency

Page 302 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-18

Check Name:	Determine Diluent Cap and Moisture for C02 Mass Calculation Verification

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

If (C02 Method Code == "CEM")

if (CO2 Mass Equation Code == "F-2")

If (H20 Method Code == "MWD" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for C02 = H20 DHV Calculated Adjusted Value
else if (H20 Method Code in set {MMS, MTB} AND H20 Monitor Hourly Checks Needed == true AND H20 MHV
Calculated Adjusted Value is not null)

Calculated Moisture for C02 = H20 MHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for C02 = H20 DHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == false AND H20 Default Value is
not null)

Calculated Moisture for C02 = H20 Default Value

if (Use CO2 Diluent Cap for C02 Mass Calc == true)

C02N Count = # of active MonitoringDefault records for location where
ParameterCode = 'C02N' AND DefaultPurposeCode = 'DC' AND
FuelCode = 'NFS'
if (C02N Count >1)

return result A
else if (C02N Count == 0)

return result B
else if MonitoringDefault.DefaultValue <= 0
return result C

else

Calculated Diluent for C02 = MonitoringDefault.DefaultValue

else if (CO2 Cone Derived Checks Needed == true)

Calculated Diluent for C02 = C02C DHV Calculated Adjusted Value

else if (CO2 Cone Checks Neededfor C02 Mass == true)

if (Current C02 Cone Missing Data Monitor Hourly Record is not null)

Calculated Diluent for C02 = C02C SD Calculated Adjusted Value

else

Calculated Diluent for C02 = C02C MHV Calculated Adjusted Value

Results:

Result
A

B

Response

You reported more than one diluent cap default record for C02N in your monitoring
plan that was active during the current hour.

A DHV record indicates use of a diluent cap to calculate C02, but you did not report an
active C02N default record in your monitoring plan for the hour. Please note that the
use of the diluent cap to calculate C02 is only applicable to legacy data.
The DefaultValue reported in the active Default record for C02N in your monitoring
plan is invalid. The value must be greater than 0.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 303 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Mass Rate Calculation Verification

Environmental Protection Agency

Page 304 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-19

Check Name:	Calculate C02 Mass Emissions

Related Former Checks:

Applicability:	CEM Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

if (Derived Hourly Adjusted Value Status == true AND Current Hourly Op ifecortf. OperatingTime is between 0 and 1 (inclusive))

C02 Total Reported Value = Current 1)11]' /feewY/.Adjustedl Iourlv Value * Current Hourly Op Record. OperatingTime.

if (Rpt Period C02 Mass Reported Accumulator Array for this location is not null)

if (Rpt Period C02 Mass Reported Accumulator Array for this location >= 0)

Rpt Period C02 Mass Reported Accumulator Array for this location = Rpt Period C02 Mass Reported
Accumulator Array for this location + C02 Total Reported Value

else

Rpt Period C02 Mass Reported Accumulator Array for this location = CO2 Total Reported Value

else

Rpt Period C02 Mass Reported Accumulator Array for this location = -1

If (C02 Method Code == "CEM")

if (CO2 Mass Equation Code == "F-l 1")

If (Current DHV Record Valid == true AND Calculated Diluent for C02 is not null AND FLOW Calculated Adjusted
Value is not null)

CO 2 Calculated Adjusted Value = 0.00000057 * Calculated Diluent for C02 * FLOW Calculated Adjusted
Value, ROUNDED to one decimal place.

else

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1
return result A

else if (CO2 Mass Equation Code == "F-2")

If (Current DHV Record Valid == true AND Calculated Diluent for C02 is not null AND FLOW Calculated Adjusted
Value is not null AND Calculated Moisture for C02 is not null)

CO 2 Calculated Adjusted Value = 0.00000057 * Calculated Diluent for C02 * FLOW Calculated Adjusted
Value* [(100.0 - Calculated Moisture for C02 ) I 100.0], ROUNDED to one decimal place.

else

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1
return result A

else

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1
return result A

else if (C02 App D Method Active for Hour == true)

if (CO2 App D Accumulator >= 0 AND Current Hourly Op Record.OperatingTime is between 0 and 1 (inclusive))

CO2 Calculated Adjusted Value = C02 App D Accumulator I Current Hourly Op Record.OperatingTime, rounded to one
decimal place.

else

if (Legacy Data Evaluation == false)

Environmental Protection Agency

Page 305 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1
return result A

else

Rpt Period C02 Mass Calculated Accumulator Array for this location = -2

else

CO2 Calculated Adjusted Value = Current DHV Calculated Adjusted Value

If (C02 Calculated Adjusted Value is not null)

If {Current Hourly Op i?ecortf.OperatingTime is between 0 and 1 inclusive)

CO 2 Total Calculated Value = C02 Calculated Adjusted Value * Current Hourly Op ifecorrf.OperatingTime.

if (Rpt Period C02 Mass Calculated Accumulator Array for this location is not null)

if (Rpt Period C02 Mass Calculated Accumulator Array for this location >= 0)

Rpt Period C02 Mass Calculated Accumulator Array for this location = Rpt Period C02 Mass
Calculated Accumulator Array for this location + C02 Total Calculated Value

else

Rpt Period C02 Mass Calculated Accumulator Array for this location = CO2 Total Calculated Value

else

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1

If (Derived Hourly Adjusted Value Status == true)

C02 Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "C02" AND
UOM = "TNHR"

if (ABS(Current DHV Record. AdjustedHourly Value - CO 2 Calculated Adjusted Value) > C02 Tolerance)
return result B

if (Rpt Period C02 Mass Calculated Accumulator Array for this location o -2)

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1

else

Results:

Result	Response	Severity

A	The AdjustedHourlyValue in the DHV record for [param] could not be recalculated due	Informational Message

to errors listed above.

B	The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with	Critical Error Level 1

the recalculated value.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Mass Rate Calculation Verification

Environmental Protection Agency

Page 306 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-25

Check Name:

Determine BAF Value for NOx Emission Rate System

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current NOX System BAF = null

If (Current NOx System Status == true AND NOXR Calculated Unadjusted Value is not null AND Current NOx Rate Method Code in
set {CEM, PEM}) AND Current Dill' Record ModcCodc in set {01, 02, 03, 14, 22, 53})

If (RATA Status BAF is not null)

Current NOX System BAF = RA TA Status BAF

else

return result A

Results:

Result
A

Response

The BAF for [ParamCode] MonitoringSystemID [ID] cannot be determined, because the
prior RATA had critical errors or because of a RATA Status error listed on this report.

Severity

Informational Message

Usage:
1

Process/Category:	Emissions Data Evaluation Report	NOX RATA Status Evaluation

Environmental Protection Agency

Page 307 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-30

Check Name:

Initialize S02 Calculated Hourly Data

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current DHV Parameter = "S02"

Current DHV Record Valid = S02 Derived Hourly Status
S02 Calculated Adjusted Value = null
Calculated Moisture for S02 = null

Current DHV Record = Current S02 Derived Hourly Record

Results:

Result	Response	Severity

Usage:
1

Process/Category:

Emissions Data Evaluation Report	S02 Calculation Verification

Environmental Protection Agency

Page 308 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-31

Check Name:

Initialize NOX Calculated Hourly Data

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current DHV Parameter = "NOX"

Current DHV Record Valid = NOX Derived Hourly Status

NOX Calculated Adjusted Value = null

Calculated Moisture for NOX = null

Current DHV Record = Current NOx Rate Derived Hourly Record

Results:

Result

Response

Severity

Usage:
1

Process/Category:

Emissions Data Evaluation Report	NOx Mass Rate Calculation Verification

Environmental Protection Agency

Page 309 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-32

Check Name:

Initialize NOXR Calculated Hourly Data

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current DHV Parameter = "NOXR"

Current DHV Record Valid = NOXR Derived Hourly Status

NOXR Calculated Adjusted Value = null

Calculated Diluent for NOXR = null

Calculated Moisture for NOXR = null

Current DHVHBHA Value = Current NOXR HBHA Value

Current DHV Record = Current NOx Rate Derived Hourly Record

Current Appendix E Status = null

RATA Status Required = false

RATA Status BAF= null

Current Hourly Record for RATA Status = Current NOx Rate Derived Hourly Record

Results:

Result

Response

Severity

Usage:
1

Process/Category:

Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Environmental Protection Agency

Page 310 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-33

Check Name:	Initialize C02 Calculated Hourly Data

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

Current DHV Parameter = "C02"

Current DHV Record Valid = CO2 Derived Hourly Status
C02 Calculated Adjusted Value = null
Calculated Diluent for C02 = null
Calculated Moisture for C02 = null

Current DHV Record = Current C02 Mass Derived Hourly Record

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Mass Rate Calculation Verification

Environmental Protection Agency

Page 311 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-34

Check Name:

Initialize C02C Calculated Hourly Data

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current DHV Parameter = "C02C"

Current DHV Record Valid = C02C Derived Hourly Status
C02C DHV Calculated Adjusted Value = null
Calculated Diluent for C02C = null
Calculated Moisture for C02C = null

Current DHVHBHA Value = Current C02C DHVHBHA Value
Current DHV Record = Current C02 Cone Derived Hourly Record

Results:

Result

Response

Severity

Usage:

Process/Category:

Emissions Data Evaluation Report	C02 Concentration Calculation Verification

Environmental Protection Agency

Page 312 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-35

Check Name:

Initialize H20 Calculated Hourly Data

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current DHV Parameter = "H20"

Current DHV Record Valid = H20 Derived Hourly Status
H20 DHV Calculated Adjusted Value = null
Current DHVHBHA Value = Current H20 DHVHBHA Value
Current DHV Record = Current H20 Derived Hourly Record

if {Current DHV Record. MODCCode in set {01, 02, 03, 21, 53} AND Current DHV Record.SystemTypeCode == "H20")
RATA Status Required = true

Results:

Result

Response

Severity

Usage:
1

Process/Category:

Emissions Data Evaluation Report	H20 Calculation Verification

Environmental Protection Agency

Page 313 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-36

Check Name:

Initialize HI Calculated Hourly Data

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current DHV Parameter = "HI"

Current DHV Record Valid = HI Derived Hourly Status
HI Calculated Adjusted Value = null
Calculated Diluent for HI = null
Calculated Moisture for HI = null

Current DHV Record = Current Heat Input Derived Hourly Record
RATA Status Required = false

Current Hourly Record for RA TA Status = Current Heat Input Derived Hourly Record

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Heat Input Calculation Verification

Environmental Protection Agency

Page 314 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-37

Check Name:

Check Unadjusted Value

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Derived Hourly Unadjusted Value Status = false

If (Current NOx Rate Method Code in set {CEM, PEM})

If (Current DHV RecordModcCode in set {01, 02, 03, 04, 14,21, 22, 53, 54})

If (Current DHV Record .UnadjustedHourly Value is not null)

If (Current DHVifecorrf.UnadjustedHourly Value <0.0 AND
Current DHV RecordModcCode <> "21" )
return result A

Else if (Current DHV Record. UnadjustedHourlyValue > 0 AND
Current DHV RecordModcCode == 21 )
return result B

Else if (Current DHV Record. UnadjustedHourlyValue is not rounded to three decimal places)
return result F

Else

Derived Hourly Unadjusted Value Status = true

if (Current DHV Max Min Value is not null AND (NOx ConcMODC is null OR is NOT in set {19,20}))
if (Current DHV ifecorrf.UnadjustedHourlyValue > Current DHV Max Min Value)
return result C

Else If (Current DHV RecordModcCode not in set {04, 53, 54})
return result A

Else

Derived Hourly Unadjusted Value Status = true

Else if (DerivedHourly Mode Status == true)

Environmental Protection Agency

Page 315 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

E
F

Usage:
1

Response

The UnadjustedHourlyValue reported in the DHV record for [param] is invalid. The
value must be greater than or equal to 0.

You reported an MODCCode of 21 in the DHV record for [param], but the
UnadjustedHourlyValue is greater than 0.

Warning: The UnadjustedHourlyValue reported in the DHV record for [param] is in
excess of the maximum value listed in the monitoring plan. Sources are required to
periodically (at least once annually) evaluate the appropriateness of these maximum
values in the monitoring plan and make proper adjustments when necessary.
Adjustments may include the need to update Span and/or Default values. You should
investigate the cause of these exceedances and determine whether adjustments to your
monitoring systems or monitoring plan are necessary.

You reported an MODCCode of [modcCode] in the DHV record for [param], so you

should not have reported a value for the UnadjustedHourlyValue.

You reported an UnadjustedHourlyValue in the DHV record for [param], A value in

this field should not be reported for the [param] [method] method.

You reported [fieldname] in the [type] record for [param] that is not rounded to the

appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1
Informational Message

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Environmental Protection Agency

Page 316 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-38

Check Name:	Determine Maximum or Minimum Value for Parameter in DHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current DHV Max Min Value = null

If (Current DHV Record Valid == true AND

((Current DHV Parameter == "H20" AND H20 Method Code == "MWD") OR

(Current DHV Parameter == "NOXR" AND Current NOx Rate Method Code in set {CEM,PEM}) OR

Current DHV Parameter == "C02C" OR

Current DHV Parameter =="HI")

If (Current DHV Parameter == "H20")

If (H20 Fuel Specific Missing Data == true)

Current DHV Fuel Specific Hour = true

If (H20 Missing Data Approach == "MAX")

Current DHV Default Parameter = "H20X"

Else If (H20 Missing Data Approach == "MIN")

Current DHV Default Parameter = "H20N"

Else If (Current DHVRecordModcCode == 12)
return result A

else if (Current DHV Parameter == "NOXR")

Current DHV Default Parameter = "NORX"

If (Current Dill' Record. ModcCodc in set {23,24})

If (NOx Rate Bypass Code == "BYMAXFS")

Current DHV Fuel Specific Hour = true

else

Current DHV Fuel Specific Hour = false
else if (NOx Rate Fuel Specific Missing Data == true)

Current DHV Fuel Specific Hour = true

else

Current DHV Fuel Specific Hour = false

else if (Current DHV Parameter == "C02C")

Current DHV Default Parameter = "C02X"

If (CO2 Fuel Specific Missing Data == true)

Current DHV Fuel Specific Hour = true

If (Current DHV Parameter == "HI")

Locate all active UnitCapacity records linked to the location where MaxHourlyHeatlnputCapacity > 0.

If any are found,

Set Current DHV Max Min Value to the sum of MaxHourlyHeatlnputCapacity in all records found,
else if (Current DHV Default Parameter is not null)

If (Current Dffl' Record. ModcCodc in set {12,23,25} AND Current DHV Fuel Specific Hour = true)
If (Current Hourly Op ifecorrf.FuelCode is not null)

Environmental Protection Agency

Page 317 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Current DHVMissing Data Fuel = Current Hourly Op ifecortf.FuelCode

Count active MonitoringDefaultData record for location where
ParameterCode = Current DHV Default Parameter
FuelCode = Current Hourly Op Record. I ucl Code
DefaultPurposeCode = "MD" // Missing Data
OperatingCode in set {A,U} // Not Controlled

if (count >1)

return result B
else if (count == 0)

return result C

else

Default Record = the single matched record

if {Default Record.DefaultValue > 0)

Current DHV Max Min Value = Default .Recorof.DefaultValue

else

return result D

else if (Current DHV RecordModcCode in set {13, 24}

If (Current DHV Fuel Specific Hour == true)

If Current Hourly Op ifecortf.FuelCode is not null

Current DHV Missing Data Fuel = Current Hourly Op Records uelCode

Count active MonitoringDefaultData record for location where
ParameterCode = Current DHV Default Parameter
FuelCode = Current Hourly Op Record. I ucl Code
DefaultPurposeCode = "MD" // Missing Data
OperatingCode in == "C" 11 Controlled

if (count >1)

return result B
else if (count == 0)

return result C

else

Default Record = the single matched record

if (Default Record.DefaultValue > 0)

Current DHV Max Min Value = Default Record. DefaultValue

else

return result D

else

Current DHV Missing Data Fuel = "NF S"

Count active MonitoringDefaultData record for location where
ParameterCode = Current DHV Default Parameter
FuelCode = "NFS"

DefaultPurposeCode = "MD" // Missing Data
OperatingCode in == "C" 11 Controlled

if (count >1)

return result B
else if (count == 0)

Environmental Protection Agency

Page 318 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

return result C

else

Default Record = the single matched record

if {Default Record.DefaultValue > 0)

Current DHVMax Min Value = Default .Recorof.DefaultValue

else

return result D

else if {Current DHV RecordModcCode o "15"

Current DHV Missing Data Fuel = "NFS"

Count active MonitoringDefaultData record for location where
ParameterCode = Current DHV Default Parameter
FuelCode = "NFS"

DefaultPurposeCode = "MD" // Missing Data
OperatingCode in set {A,U} // Not Controlled

if {count >1)

return result B

else if {count == 0 AND Current DHV Parameter == "C02C")

Monitor Span Record Count = Find active MonitoringSpanData records for location where
MonitoringSpanData .ComponentTypeCode = "C02" AND
MonitoringSpanData.SpanScaleCode = "Ft"

if {Monitor Span Record Count > 1)

return result E
else if {Monitor Span Record Count = 0)
return result F

else

Current Monitor Span Record = the single matched record

If {Current Monitor Span .Recorof.DefaultHighRange is null AND Current DHV
RecordModcCode not in set {13,24})

if {Current Monitor Span .Recorof.MPCValue > 0)

Current DHV Max Min Value = Current Monitor Span Record.MPCVa\ue

else

return result G

else if {count == 0 AND Current DHV Parameter == "NOXR")

Count active MonitoringDefaultData record for location where
ParameterCode = "MNNX"

FuelCode = "NFS"

DefaultPurposeCode = "MD" // Missing Data
OperatingCode in set {A,U} // Not Controlled

if {count >1)

Current DHV Default Parameter = "MNNX"
return result B

else if {count = 0)

return result C

Environmental Protection Agency

Page 319 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Current DHVDefault Parameter = "MNNX"

Default Record = the single matched record

if {Default Record.DefaultValue >= 0)

Current DHV Max Min Value = Default .Recorof.DefaultValue

else

return result D

else if (count == 0)

return result C

Default Record = the single matched record

if {Default Record.DefaultValue > 0)

Current DHV Max Min Value = Default .Recorof.DefaultValue

else

return result D

Results:

Result
A

B

C
D

E

F

G

Usage:

1

2

3

4

Response

The missing data default parameter for H20 could not be determined, because you used
both Standard and Inverse Part 75 missing data approaches during the hour.
You reported more than one applicable [param] Default record with a FuelCode of
[FuelCode] in your monitoring plan for the hour.

You did not report an applicable [param] Default record with a FuelCode of [FuelCode],
The values reported in the applicable [param] Default record with a FuelCode of
[FuelCode] are invalid.

You reported more than one active span record for [key] in your monitoring plan for the
hour.

You did not report a missing data maximum default for C02 in a span or default record
in your monitoring plan.

The values reported in the applicable span record for [key] are invalid.

Severity

Critical Error Level 2

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Calculation Verification

Process/Category:	Emissions Data Evaluation Report	LOO Calculation Verification

Process/Category:	Emissions Data Evaluation Report	Heat Input Calculation Verification

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Environmental Protection Agency

Page 320 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-39

Check Name:	Check Adjusted Hourly Value in DHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Validation Tables:

Parameter UOM (Complex Lookup Table)

Specifications:

Derived Hourly Adjusted Value Status = false
Current DHV Calculated Adjusted Value = null

if (Current DHV Record Valid == true)

Locate Parameter Units of Measure lookup table record where ParameterCode = Current DHV Parameter.

If (Hourly Fuel Flow Count For Gas is greater than 0 AND Current DHV Parameter == "S02")
Set Current DHV Precision to 4.

else

Set Current DHV Precision to the Parameter Units of MmsMre.DecimalsHrly.

if (Current DHV Record.ModcCode is not null)

case (Current DHV RecordModcCode )

= 21: Current DHV Calculated Adjusted Value = 0

if (Current DHV Record. AdjustedHourly Value == 0)

Derived Hourly Adjusted Value Status = true

else

return result A

= 12 OR 23 OR 25:

If (Current DHV Max Min Value is not null)

Current DHV Calculated Adjusted Value = Current DHV Max Min Value
if (Current DHV Record AdjustedHourlyValue == Current DHV Max Min Value )
Derived Hourly Adjusted Value Status = true

else

return result B

= 13 OR 24:

If (Current DHV Max Min Value is not null)

Current DHV Calculated Adjusted Value = Current DHV Max Min Value
if (Current DHV Record AdjustedHourlyValue == Current DHV Max Min Value )
Derived Hourly Adjusted Value Status = true

else

return result C

= 06:

If (Current DHV Parameter in set {C02C, H20} AND (Current DHV ifecortfAdjustedHourlyValue is null or
Current DHV Record .f\&\ Listed I Iourl y Val Lie < 0 or Current DHV Record lis ted I Iourl y Val Lie > 100))
return result L

else if (Current DHVHBHA Value is not null)

Environmental Protection Agency

Page 321 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Current DHV Calculated Adjusted Value = Current DHVHBHA Value

If {Current DHV Record. AdjustedHourly Value >= 0)

if ( Current DHV Record AdjustedHourlyValue == Current DHV Calculated Adjusted Value)
Derived Hourly Adjusted Value Status = true

else

return result D

else

return result E

else

If {Current DHV Record. AdjustedHourly Value >= 0)

If {Current .M/Fifecortf AdjustedHourly Value is not rounded to Current DHV Precision)
return result M

else

Current DHV Calculated Adjusted Value = Current DHV Record AdjustedHourlyValue
Derived Hourly Adjusted Value Status = true

if {Current DHV Parameter in set {C02C, H20, NOXR} AND Current DHV Max Min
Value is not null)

If {Current DHV Parameter == "H20" AND H20 Missing Data Approach ==

"MIN")

if {Current DHV Record AdjustedHourlyValue < Current DHV Max
Min Value)

return result H

else

if {Current DHV Record AdjustedHourlyValue > Current DHV Max
Min Value)

If {Current DHV Parameter == "NOXR" and Current DHV
Record AdjustedHourlyValue > Current DHV Max Min Value

*2)

return result O
Otherwise,

return result G

Else

return result E

= 08 OR 09:

If {Current DHV Parameter in set {C02C, H20} AND {Current DHV ifecorrfAdjustedHourlyValue is null or
Current DHV Kecord .f\&\ Listed I Iourl y Val Lie < 0 or Current DHV Kecord lis ted I Iourl y Val Lie > 100))
return result L

else if {Current DHVitecortfAdjustedHourly Value >= 0)

If {Current DHV HBHA Value is not null AND Current DHV Parameter == "H20" AND H20 Missing
Data Approach == "MIN" AND Current DHV HBHA Value < Current DHV
itecortfAdjustedHourlyValue)

Current DHV Calculated Adjusted Value = Current DHV HBHA Value
return result N

else if {Current DHV HBHA Value is not null AND {Current DHV Parameter o "H20" OR H20
Missing Data Approach == "MAX") AND Current DHV HBHA Value > Current DHV
itecora? AdjustedHourly Value AND {Unit is Load Based == true or Current DHV Parameter <>

"NOXR"))

Current DHV Calculated Adjusted Value = Current DHV HBHA Value
return result F

Environmental Protection Agency

Page 322 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

elseif (Current DHV Record. AdiustedHour\yVa\ue is not rounded to CurrentDHVPrecision)
return result M

else

Current DHV Calculated Adjusted Value = Current I) HI' /fecewY/. Adjusted I Iourlv Value
Derived Hourly Adjusted Value Status = true

if (Current DHV Parameter in set {C02C, H20, NOXR} AND Current DHV Max Min Value is
not null)

If (Current DHV Parameter == "H20" AND H20 Missing Data Approach == "MIN")
if (Current DHV RecordAdjustedHourlyValue < Current DHV Max Min
Value)

return result H

else

if (Current DHV RecordAdjustedHourlyValue > Current DHV Max Min
Value)

If (Current DHV Parameter == "NOXR" and Current DHV
ifecortfAdjustedHourly Value > Current DHV Max Min Value * 2)

return result O
Otherwise,

return result G

Else

return result E

= 04, 05, 07, 10, 11, 15, 53, 54, OR 55:

If (Current DHV Parameter in set {C02C, H20} AND (Current DHV ifecortfAdjustedHourlyValue is null or
Current DHV Kecord .f\&\ Listed I Iourl y Val lie < 0 or Current DHV Kecord us ted I Iourl y Val lie > 100))
return result L

else if (Current DHVitecortfAdjustedHourly Value >= 0)

If (Current DHV Record. AdjustedHourly Value is not rounded to Current DHV Precision)
return result M

else

Current DHV Calculated Adjusted Value = Current I) HI' /feeewY/. Adjusted I Iourl v Value
Derived Hourly Adjusted Value Status = true

if (Current DHV Parameter in set {C02C, H20, NOXR} AND Current DHV Max Min Value is
not null)

If (Current DHV Parameter == "H20" AND H20 Missing Data Approach == "MIN")
if (Current DHV RecordAdjustedHourlyValue < Current DHV Max Min
Value)

return result H

else

if (Current DHV RecordAdjustedHourlyValue > Current DHV Max Min
Value)

If (Current DHV Parameter == "NOXR" and Current DHV
RecordAdjustedHourlyValue > Current DHV Max Min Value * 2)

return result O
Otherwise,

return result G

Else

return result E

= 26: If (Current DHV Record.AdjustedHourlyValue == 1)

Derived Hourly Adjusted Value Status = true

else

Environmental Protection Agency

Page 323 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

return result I

= All Other Codes except 40:

If (Current DHVParameter in set {C02C, H20} AND (Current DHVifecortf.AdjustedHourlyValue is null or
Current DHV Record .f\&\ Listed I Iourl y Val Lie < 0 or Current DHV Record lis ted I Iourl y Val Lie > 100))
return result L

else if (Current DHVitecortf.AdjustedHourly Value >= 0)

If (Current DHV Record. AdjustedHourly Value is not rounded to Current DHV Precision)
return result M

else

Derived Hourly Adjusted Value Status = true

If (Current DHV Parameter in set {C02C, H20} AND Current DHV Max Min Value is not
null)

If (Current DHV Parameter == "H20" AND H20 Missing Data Approach == "MIN")
if (Current DHV Record.AdjustedHourlyValue < Current DHV Max Min
Value)

return result H

else

if (Current DHV Record.AdjustedHourlyValue > Current DHV Max Min
Value)

return result G

Else

return result E

else

If (Current DHV Record.AdjustedHourly Value >= 0)

If (Current DHV Record. AdjustedHourlyValue is not rounded to Current DHV Precision)
return result M

else

Derived Hourly Adjusted Value Status = true

If (Current DHV Parameter == "HI")

if (Heat Input Method Code not in set {AD, ADCALC, CALC})

Current DHV Calculated Adjusted Value = Current DHV Record .AdjustedHourlyValue

If (Current DZ/Fifecortf AdjustedHourly Value == 0.0)

If (Heat Input Method Code == "CEM")

If Legacy Data Evaluation = true

If (Current Hourly Op Record.OpTime > 0.25 )
return result J

else

If (Current Hourly Op Record.OpTime > 0)
return result K

else if (Current DHV Max Min Value is not null and Current DHV ifecorrf.AdjustedHourlyValue
> Current DHV Max Min Value)
return result G

else if (Current DHV Parameter == "NOXR")

if (Current NOx Rate Method Code o "AE")

Environmental Protection Agency

Page 324 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Current DHV Calculated Adjusted Value = Current 1)11]' /fecewY/. Adjusted I Iourlv Value

else if (Current DHV Parameter == "S02")

if (SO 2 App D Method Active for Hour == false)

Current DHV Calculated Adjusted Value = Current 1)11]' /fecewY/. Adjusted I Iourlv Value

else if (Current DHV Parameter == "C02")

if (CO 2 App D Method Active for Hour == false)

Current DHV Calculated Adjusted Value = Current 1)11]' /ferYWY/. Adjusted I Iourlv Value

else

Current DHV Calculated Adjusted Value = Current 1)11]' /feeewY/. Adjusted I Iourlv Value

else

return result E

Environmental Protection Agency

Page 325 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

D

E
F

G

H

I
J
K

L

M

N

O

Response

You reported an MODCCode of 21 in the DHV record for [param], but the
AdjustedHourlyValue does not equal 0.

You reported an MODCCode of [modcCode] in the DHV record for [param], but the
AdjustedHourlyValue does not equal the maximum potential value reported in the span
or default record in your monitoring plan.

You reported an MODCCode of 13 or 24 in the DHV record for NOXR, but the
AdjustedHourlyValue does not equal the maximum controlled emission rate reported in
the NORX default record in your monitoring plan.

You reported an MODCCode of 06 in the DHV record for [param], but the
AdjustedHourlyValue does not equal average of measured hour before and measured
hour after.

The AdjustedHourlyValue reported in the DHV record for [param] is invalid. The value
must be greater than or equal to 0.

You reported an MODCCode of [MODCCode] in the DHV record for [param], but you
reported an AdjustedHourlyValue that is less than the average of the measured hour
before and measured hour after.

Warning: The AdjustedHourlyValue reported in the DHV record for [param] is in
excess of the maximum value listed in the monitoring plan. Sources are required to
periodically (at least once annually) evaluate the appropriateness of these maximum
values in the monitoring plan and make proper adjustments when necessary.

Adjustments may include the need to update Span, Default, and/or Unit Capacity values.
You should investigate the cause of these exceedances and determine whether
adjustments to your monitoring systems or monitoring plan are necessary.

Warning: The AdjustedHourlyValue reported in the DHV record for [param] is lower
than the minimum value listed in the monitoring plan. Sources are required to
periodically (at least once annually) evaluate the appropriateness of these minimum
values in the monitoring plan and make proper adjustments when necessary.

Adjustments may include the need to update Span Default values. You should
investigate the cause of these low values and determine whether adjustments to your
monitoring systems or monitoring plan are necessary.

You reported an MODCCode of 26 in the DHV record for [param], but the
AdjustedHourlyValue does not equal 1.

You reported an AdjustedHourlyValue of 0 in the DHV record for HI, but you operated
more than 0.25 hour.

You reported an AdjustedHourlyValue of 0 in the DHV record for HI, but you had
operating time during the hour. If you operated, you must report a heat input rate of at
least 1 mmBtu/hr.

The AdjustedHourlyValue reported in the DHV record for [param] is invalid. The value
must be between 0 and 100.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

You reported an MODCCode of [MODCCode] in the DHV record for [param], but you
reported an AdjustedHourlyValue that is greater than the average of the measured hour
before and measured hour after.

The AdjustedHourlyValue reported in the DHV record for NOXR is in excess of 200%
of the maximum value listed in the monitoring plan. Sources are required to periodically
(at least once annually) evaluate the appropriateness of these maximum values in the
monitoring plan and make proper adjustments when necessary. Adjustments may include
the need to update Span and/or Default values. You should investigate the cause of these
exceedances and determine whether adjustments to your monitoring systems or
monitoring plan are necessary.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Informational Message

Informational Message

Critical Error Level 1
Non-Critical Error
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 2

Environmental Protection Agency

Page 326 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:

2	Process/Category:

3	Process/Category:

4	Process/Category:

5	Process/Category:

6	Process/Category:

7	Process/Category:

Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report

C02 Concentration Calculation Verification
C02 Mass Rate Calculation Verification
H20 Calculation Verification
Heat Input Calculation Verification
NOx Emissions Rate Calculation Verification
NOx Mass Rate Calculation Verification
S02 Calculation Verification

Environmental Protection Agency

Page 327 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-40

Check Name:

Determine Moisture for S02 Mass Calculation Verification

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (SO 2 Method Code begins with "CEM")

if (S()2 Mass Equation Code == "F-2")

If (H20 Method Code == "MWD" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for S02 = H20 DHV Calculated Adjusted Value
else if (H20 Method Code in set {MMS, MTB} AND H20 Monitor Hourly Checks Needed == true AND H20 MHV
Calculated Adjusted Value is not null)

Calculated Moisture for S02 = H20 MHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == true AND H20 DHV Calculated
Adjusted Value is not null)

Calculated Moisture for S02 = H20 DHV Calculated Adjusted Value
else if (H20 Method Code == "MDF" AND H20 Derived Hourly Checks Needed == false AND H20 Default Value is
not null)

Calculated Moisture for S02 = H20 Default Value

Results:

Result

Response

Severity

Usage:

Process/Category:

Emissions Data Evaluation Report	S02 Calculation Verification

Environmental Protection Agency

Page 328 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-41

Check Name:	Calculate Adjusted NOx Rate in DHV Record

Related Former Checks:

Applicability:	General Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

if (Derived Hourly Adjusted Value Status == true)

if (Rpt Period NOx Rate Reported Accumulator Array for this location is not null)

if (Rpt Period NOx Rate Reported Accumulator Array for this location >= 0)

Rpt Period NOx Rate Reported Accumulator Array for this location = Rpt Period NOx Rate Reported
Accumulator Array for this location + Current DHV Record. AdjustedHourlyValue

else

Rpt Period NOx Rate Reported Accumulator Array for this location = Current Dill' Record. Ad] ustcdl Iourl v Val Lie

else

Rpt Period NOx Rate Reported Accumulator Array for this location = -1

if (RATA Status Required == true AND Current NOX System BAF is not null)

NOXR Calculated Adjusted Value = NOXR Calculated Unadjusted Value * Current NOX System BAF, and round the result to
three decimal places

else if (Current NOx Rate Method Code == "AE" AND Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count for Oil > 0 AND
App E Constant Fuel Mix == false)

If (NOXR App E Accumulator >= 0 AND HI Calculated Adjusted Value is not null AND Current Hourly Op
ifecorrf.OperatingTime is between 0 and 1 (inclusive))

If (NOXR App E Accumulator == 0)

NOXR Calculated Adjusted Value = 0

else

NOXR Calculated Adjusted Value = NOXR App E Accumulator I Total Heat Input from Fuel Flow, and round
the result to three decimal places

else

Apportionment Calc NOXR Array at this Location = -1

Rpt Period NOx Rate Calculated Accumulator Array for this location = -1

return result A

If (NOXR Calculated Adjusted Value is not null)

Apportionment Calc NOXR Array at this Location = NOXR Calculated Adjusted Value

if (MP Stack Config for Hourly Checks == "MS" AND Expected Summary Value NOx Rate Array for the location == true)
if (Config NOxRateTimesHeatlnput Accumulator >= 0 AND HI Calculated Adjusted Value is not null)

Config NOxRateTimesHeatlnput Accumulator = Config NOxRateTimesHeatlnput Accumulator + (HI
Calculated Adjusted Value * NOXR Calculated Adjusted Value)

else

Config NOxRateTimesHeatlnput Accumulator = -1

if (Config NOxRateTimesOpTime Accumulator >= 0 AND Current Hourly Op ifecorrf.OperatingTime is between 0 and 1
(inclusive))

Config NOxRateTimesOpTime Accumulator = Config NOxRateTimesOpTime Accumulator + (Current Hourly
Op liecord.i )pcrati ng l i ni c * NOXR Calculated Adjusted Value)

Config OpTime Accumulator = Config OpTime Accumulator + Current Hourly Op ifecorrf.OperatingTime

else

Environmental Protection Agency

Page 329 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Config NOxRateTimesOpTime Accumulator = -1

if (Rpt Period NOx Rate Calculated Accumulator Array for this location is not null)

if {Rpt Period NOx Rate Calculated Accumulator Array for this location >= 0)

Rpt Period NOx Rate Calculated Accumulator Array for this location = Rpt Period NOx Rate Calculated
Accumulator Array for this location +NOXR Calculated Adjusted Value

else

Rpt Period NOx Rate Calculated Accumulator Array for this location = NOXR Calculated Adjusted Value

Rpt Period NOx Rate Hours Accumulator Array for this location = Rpt Period NOx Rate Hours Accumulator Array for this

location + 1

if (Derived Hourly Adjusted Value Status == true AND Derived Hourly Unadjusted Calculation Status == true)

Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "NOXR" AND
UOM = "LBMMBTU"

if ABS(NOXR Calculated Adjusted Value - Current DHV Record. AdjustedHourly Value) > Tolerance
return result B

else if Current NOx Rate Method Code o "AE" OR Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count for Oil > 0)

>0)

Apportionment Calc NOXR Array at this Location = -1

Rpt Period NOx Rate Calculated Accumulator Array for this location = -1

if (MP Stack Config for Hourly Checks == "MS")

Config NOxRateTimesHeatlnput Accumulator = -1

if (RATA Status Required == true AND Current NOX System BAF is null AND NOXR Calculated Unadjusted Value is not null)
return result A

Results:

Result
A

B

Response

The AdjustedHourlyValue in the DHV record for [param] could not be recalculated due
to errors listed above.

The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with
the recalculated value.

Severity

Informational Message
Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Calculation Verification

Conditions:	RATA Status Required Equals false

Process/Category:	Emissions Data Evaluation Report	NOX RATA Status Evaluation

Environmental Protection Agency

Page 330 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURCV-42

Check Name:

Check HI System in DHV Record

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If Current DHV Parameter == "HI" AND Heat Input Method Code in set {CEM, AMS} )

If (Current 1)11] Record.MonitoringSvstcmII ) is null

If (Heat Input Method Code == "CEM" AND

(CO 2 Cone Checks Needed for Heat Input == true AND Current C02 Cone Monitor Hourly Record is
not null AND Current C02 Cone Monitor Hourly Record. ModcCodc in set {01, 02, 03, 04, 17, 20, 21})
OR

(02 Wet Checks Needed for Heat Input == true AND Current 02 Wet Monitor Hourly Record is not null
AND Current 02 Wet Monitor Hourly RecordModcCode in set {01,02, 03,04, 17,20})OR
(02 Dry Checks Needed for Heat Input == true AND Current 02 Dry Monitor Hourly Record is not null
AND Current 02 Dry Monitor Hourly RecordModcCode in set {01, 02, 03, 04, 17, 20}))

If (Heat Input Method Code == "CEM" AND

((C02 Cone Checks Neededfor Heat Input == false OR (Current C02 Cone Monitor Hourly Record is
not null AND Current C02 Cone Monitor Hourly RecordModcCode NOT in set {01, 02, 03, 04, 05, 17,

20,21,53, 54})) AND

(02 Wet Checks Needed for Heat Input == false OR (Current 02 Wet Monitor Hourly Record is not null
AND Current 02 Wet Monitor Hourly RecordModcCode NOT in set {01, 02, 03, 04, 05, 17,20, 53,

54})) AND

(02 Dry Checks Needed for Heat Input == false OR (Current 02 Dry Monitor Hourly Record is not null
AND Current 02 Dry Monitor Hourly RecordModcCode NOT in set {01, 02, 03, 04, 05, 17,20, 53,

54})))

If (Current DHV Record Valid == true)
return result B

else

HI DHV Mon Sys Record = find active MonitoringSystemData record for location where
MonitoringSystemData.MonitoringSystemID = Current DHVitecortf.MonitoringSystemID

if {HI DHV Mon Sys Record is null)

return result A

else

return result C

else if (HIDHVMon Sys Recorof.SystemTypeCode not in set {C02, 02})
return result D

else

if (CO2 RATA Required == true)

RATA Status Required = true

Environmental Protection Agency

Page 331 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

Usage:

1

Response

You did not report MonitoringSystemID in the DHV record for HI. While this was
acceptable for legacy data, this field is required when you report measured data.
You reported a MonitoringSystemID in the DHV record for [param]. This field should
be blank when missing data substitution is used.

You reported MonitoringSystemID [ID] in the DHV record for [param], but according
to your monitoring plan this system was not active during the hour.

You reported MonitoringSystemID [ID] in the DHV record for HI, but this system is not
a C02 or 02 monitoring system.

Severity

Critical Error Level 1
Non-Critical Error
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Heat Input Calculation Verification

Environmental Protection Agency

Page 332 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURCV-43

Check Name:	Determine DHV Measure Code

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

Set Current Measure Code to null.

If (Current DHV Parameter in set {C02C, H20})

If {Current DHVRecordModcCode in set {01, 02, 03, 04,21, 53, 54})

Set Monitor Measure Code Array for the Current DHV Parameter to "MEASURE"

if {Current DHV Parameter == "C02C" AND C02 Cone CEM Equation Code == "F-14B" AND Monitor Measure
Code Array for "H20" == "SUB")

Set Monitor Measure Code Array for "C02C" to "MEASSUB".

else if {Current DHV RecordModcCode in set {06, 07, 08, 09, 10, 12, 55})

Set Monitor Measure Code Array for the Current DHV Parameter to "SUB"

if {Current DHV Parameter == "C02C" AND C02 Cone CEM Equation Code == "F-14B" AND Monitor Measure
Code Array for "H20" == "MEASURE")

Set Monitor Measure Code Array for "C02C" to "MEASSUB".

else if {Current DHV Parameter == "NOXR")

If {Current NOx Rate Method Code in set {CEM, PEM}

If {Current DHV RecordModcCode in set {01, 02, 03, 04, 05, 14,21, 22, 53, 54})

Set Current Measure Code" to "MEASURE".

if {NOx Rate Equation Code in set {19-3, 19-3D, 19-4, 19-5, 19-8, 19-9} AND Monitor Measure Code Array for
"H20" == "SUB")

set Current Measure Code to "MEASSUB".

else if {Current DHV RecordModcCode in set {06, 07, 08, 09, 10, 11, 12, 13, 15, 23,24,25, 55})

Set Current Measure Code to "SUB"

if {NOx Rate Equation Code in set {19-3, 19-3D, 19-4, 19-5, 19-8, 19-9} AND Monitor Measure Code Array for
"H20" == "MEASURE")

set Current Measure Code to "MEASSUB".

else if {Current NOx Rate Method Code == "AE")

Set Current Measure Code to the Monitor Measure Code Array for "NOXR".

Set NOXR Measure Code to the Current Measure Code.

else if {Current DHV Parameter == "HI")

If {Heat Input Method Code == "CEM")

if {Heat Input Equation Code in set {F-15, F-16})

If {Monitor Measure Code Array for "C02C" and "FLOW" are both equal to "MEASURE")
set Current Measure Code to "MEASURE".

Environmental Protection Agency

Page 333 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else if (Monitor Measure Code Array for "C02C" and "FLOW" are both equal to "SUB")
set Current Measure Code to "SUB".

else if (Monitor Measure Code Array for "C02C" and "FLOW" are both not null)
set Current Measure Code to "MEASSUB".

else if {Heat Input Equation Code in set {F-18})

If {Monitor Measure Code Array for "02D" and "FLOW" are both equal to "MEASURE")
set Current Measure Code to "MEASURE".

else if {Monitor Measure Code Array for "02D" and "FLOW" are both equal to "SUB")
set Current Measure Code to "SUB".

else if {Monitor Measure Code Array for "02D" and "FLOW" are both not null)
set Current Measure Code to "MEASSUB".

else if {Heat Input Equation Code in set {F-17})

If {Monitor Measure Code Array for "02W" and "FLOW" are both equal to "MEASURE")
set Current Measure Code to "MEASURE".

else if {Monitor Measure Code Array for "02W" and "FLOW" are both equal to "SUB")
set Current Measure Code to "SUB".

else if {Monitor Measure Code Array for "02W" and "FLOW" are both not null)
set Current Measure Code to "MEASSUB".

if {Heat Input Equation Code in set {F-16, F-17, F-18} AND Monitor Measure Code Array for "LEO" is not null)

If {{Current Measure Code == "MEASURE" AND Monitor Measure Code Array for "LOO" == "SUB") OR
{Current Measure Code == "SUB" AND Monitor Measure Code Array for "LOO" == "MEASURE"))
set Current Measure Code to "MEASSUB".

else if {Heat Input App D Method Active for Hour == true)

If {Monitor Measure Code Array for "FF" in set {OLHER, MEASSUB})

set Current Measure Code to Monitor Measure Code Array for "FF".

else if {Monitor Measure Code Array for "FF" and "GCV" are both equal to "MEASURE")
set Current Measure Code to "MEASURE".

else if {Monitor Measure Code Array for "FF" and "GCV" are both equal to "SUB")
set Current Measure Code to "SUB".

else if {Monitor Measure Code Array for "FF" and "GCV" are both not null)
set Current Measure Code to "MEASSUB".

if {Monitor Measure Code Array for "DENSILY" is not null)

If {{Current Measure Code == "MEASURE" AND Monitor Measure Code Array for "DENSILY" == "SUB")
OR {Current Measure Code == "SUB" AND Monitor Measure Code Array for "DENSILY" == "MEASURE"))
set Current Measure Code to "MEASSUB".

Set HI Measure Code to the Current Measure Code.

else if {Current DHVParameter == "S02")

Environmental Protection Agency

Page 334 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (S02 CEM Method Active for Hour == true)

If {Monitor Measure Code Array for "S02C" and "FLOW" are both equal to "MEASURE")
set Current Measure Code to "MEASURE".

else if (Monitor Measure Code Array for "S02C" and "FLOW" are both equal to "SUB")
set Current Measure Code to "SUB".

else if (Monitor Measure Code Array for "S02C" and "FLOW" are both not null)
set Current Measure Code to "MEASSUB".

if (S02 Equation Code == "F-2" AND Monitor Measure Code Array for "LOO" is not null)

If ((Current Measure Code == "MEASURE" AND Monitor Measure Code Array for "LOO" == "SUB") OR
(Current Measure Code == "SUB" AND Monitor Measure Code Array for "LOO" == "MEASURE"))
set Current Measure Code to "MEASSUB".

else if (SO 2 F23 Method Active for Hour == true)

set Current Measure Code to HI Measure Code.

else if (SO 2 App D Method Active for Hour == true)

If (Monitor Measure Code Array for "FF" in set {OLHER, MEASSUB} OR Monitor Measure Code Array for "SULFUR"
is null)

set Current Measure Code to Monitor Measure Code Array for "FF".

else if (Monitor Measure Code Array for "FF" and "SULFUR" are both equal to "MEASURE")
set Current Measure Code to "MEASURE".

else if (Monitor Measure Code Array for "FF" and "SULFUR" are both equal to "SUB")
set Current Measure Code to "SUB".

else if (Monitor Measure Code Array for "FF" is not null)
set Current Measure Code to "MEASSUB".

else if (Current DHVParameter == "C02")

If (CO2 Method Code == "CEM")

If (Monitor Measure Code Array for "C02C" and "FLOW" are both equal to "MEASURE")
set Current Measure Code to "MEASURE".

else if (Monitor Measure Code Array for "C02C" and "FLOW" are both equal to "SUB")
set Current Measure Code to "SUB".

else if (Monitor Measure Code Array for "C02C" and "FLOW" are both not null)
set Current Measure Code to "MEASSUB".

if (CO2 Mass Equation Code == "F-2" AND Monitor Measure Code Array for "LOO" is not null)

If ((Current Measure Code == "MEASURE" AND Monitor Measure Code Array for "LOO" == "SUB") OR
(Current Measure Code == "SUB" AND Monitor Measure Code Array for "LOO" == "MEASURE"))
set Current Measure Code to "MEASSUB".

else if (CO 2 App D Method Active for Hour == true)

Environmental Protection Agency

Page 335 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

set Current Measure Code to HI Measure Code.

else if (Current DHVParameter == "NOX")

if (XOx Mass Equation Code == "F-24A")

If (HI Measure Code and NOXR Measure Code are both equal to "MEASURE")
set Current Measure Code to "MEASURE".

else if (HI Measure Code and NOXR Measure Code are both equal to "SUB")
set Current Measure Code to "SUB".

else if (HI Measure Code and NOXR Measure Code are both not null)
set Current Measure Code to "MEASSUB".

else if (XOx Mass Equation Code in set {F-26A, F-26B})

If (Monitor Measure Code Array for "NOXC" and "FLOW" are both equal to "MEASURE")
set Current Measure Code to "MEASURE".

else if (Monitor Measure Code Array for "NOXC" and "FLOW" are both equal to "SUB")
set Current Measure Code to "SUB".

else if (Monitor Measure Code Array for "NOXC" and "FLOW" are both not null)
set Current Measure Code to "MEASSUB".

if (XOx Mass Equation Code == "F-26B" AND Monitor Measure Code Array for "LOO" is not null)

If ((Current Measure Code == "MEASURE" AND Monitor Measure Code Array for "LOO" == "SUB") OR
(Current Measure Code == "SUB" AND Monitor Measure Code Array for "LOO" == "MEASURE"))
set Current Measure Code to "MEASSUB".

else if (Current DHV Parameter in set {S02M, NOXM, C02M, HIL}
Set Current Measure Code to "LME".

Results:

Result

Response

Severity

Environmental Protection Agency

Page 336 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:

2	Process/Category:

3	Process/Category:

4	Process/Category:

5	Process/Category:

6	Process/Category:

7	Process/Category:

8	Process/Category:

9	Process/Category:

10	Process/Category:

11	Process/Category:

Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report

C02 Concentration Calculation Verification
C02 Mass Rate Calculation Verification
C02M Derived Hourly Evaluation (LME)
H20 Calculation Verification
Heat Input Calculation Verification
HIT Derived Hourly Evaluation (LME)
NOx Emissions Rate Calculation Verification
NOx Mass Rate Calculation Verification
NOXM Derived Hourly Evaluation (LME)
S02 Calculation Verification
S02M Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 337 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Hourly Derived Data

Environmental Protection Agency

Page 338 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-1

Check Name:

Initialize S02 Derived Hourly Data

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current DHV Parameter = "S02"

S02 Derived Hourly Status = true

Current DHV Record = Current S02 Derived Hourly Record
Current DHV Method = S02 Method Code
Current DHV System Type = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	S02 Derived Hourly Evaluation

Environmental Protection Agency

Page 339 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-2

Check Name:	Initialize NOX Derived Hourly Data

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

Current DHV Parameter = "NOX"

NOX Derived Hourly Status = true

Current DHV Record = Current NOx Mass Derived Hourly Record
Current DHV Method = NOx Mass Monitor Method Code
Current DHV System Type = null

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	NOx Mass Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 340 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-3

Check Name:

Initialize NOXR Derived Hourly Data

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current DHV Parameter = "NOXR"

NOXR Derived Hourly Status = true
Current DHV System Type = null

Current DHV Record = Current NOx Rate Derived Hourly Record
Current DHV Method = Current NOx Rate Method Code

NOx Emission Rate MODC = Current NOx Rate Derived Hourly Record ModcCode

if {Current DHV Method == "CEM";

Current DHV System Type = "NOX"
else if (Current DHV Method == "PEM")

Current DHV System Type = "NOXP"
if (Current DHV Method == "AE")

Current DHV System Type = "NOXE"

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 341 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-4

Check Name:	Initialize C02 Derived Hourly Data

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

Current DHV Parameter = "C02"

CO2 Derived Hourly Status = true

Current DHV Record = Current C02 Mass Derived Hourly Record
Current DHV Method = C02 Method Code
Current DHV System Type = null

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Mass Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 342 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-5

Check Name:

Initialize C02C Derived Hourly Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current DHV Parameter = "C02C"

C02C Derived Hourly Status = true

Current DHV Record = Current C02 Cone Derived Hourly Record
Current DHV System Type = 'C02'

Current DHV Method = "CEM"

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Derived Hourly Evaluation

Environmental Protection Agency

Page 343 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-6

Check Name:

Initialize H20 Derived Hourly Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current DHV Parameter = "H20"

H20 Derived Hourly Status = true

Current DHV Record = Current H20 Derived Hourly Record
Current DHV System Type = "H20"

Current DHV Method = H20 Method Code
RATA Status Required = false

Current Hourly Record for RATA Status = Current H20 Derived Hourly Record

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	H20 Derived Hourly Evaluation

Environmental Protection Agency

Page 344 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-7

Check Name:

Initialize HI Derived Hourly Data

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current DHV Parameter = "HI"

HI Derived Hourly Status = true
Current DHV System Type = null

Current DHV Record = Current Heat Input Derived Hourly Record
Current DHV Method = Heat Input Method Code

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Heat Input Derived Hourly Evaluation

Environmental Protection Agency

Page 345 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-8

Check Name:

Initialize S02R Derived Hourly Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current DHV Parameter = "S02R"

S02R Derived Hourly Status = true
Current DHV System Type = null

Current DHV Record = Current S02R Derived Hourly Record
Current DHV Method = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	S02R Derived Hourly Evaluation

Environmental Protection Agency

Page 346 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-9

Check Name:

Initialize S02M Derived Hourly Data

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

Current DHV Parameter = "S02M"

S02M Derived Hourly Status = true
Current DHV System Type = null
Current DHV Method = "LME"

Current DHV Record = Current S02 Derived Hourly Record

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	S02M Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 347 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-10

Check Name:

Initialize NOXM Derived Hourly Data

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

Current DHV Parameter = "NOXM"

NOXM Derived Hourly Status = true
Current DHV System Type = null
Current DHV Method = "LME"

Current DHV Record = Current NOx Mass Derived Hourly Record

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	NOXM Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 348 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-11

Check Name:

Initialize C02M Derived Hourly Data

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

Current DHV Parameter = "C02M"

C02M Derived Hourly Status = true
Current DHV System Type = null
Current DHV Method = "LME"

Current DHV Record = Current C02 Mass Derived Hourly Record

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02M Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 349 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-12

Check Name:	Initialize HIT Derived Hourly Data

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

Current DHV Parameter = "HIT"

HIT Derived Hourly Status = true

Current DHV System Type = null

Current DHV Method = Heat Input Method Code

Current DHV Record = Current Heat Input Derived Hourly Record

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	HIT Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 350 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-13

Check Name:	Check MODC in DHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Derived Hourly Mode Status = false

case (Current DHV Parameter)

S02: If {Current DHV Method == "AMS")

If (Current DHV RecordModcCode is not null and is not in set {01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 12, 13, 15,

16,21,23, 53, 54, 55})
return result A

Else

Derived Hourly Mode Status = true

else

If (CurrentDHVRecordModcCode is not null)
return result B

Else

Derived Hourly Mode Status = true

NOX: If (Current DHV Method == "AMS")

If (Current DHV RecordModcCode is not null and is not in set {01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 11, 12, 13,

15,21,23,24, 53, 54, 55})
return result A

Else

Derived Hourly Mode Status = true

else

If (Current DHV RecordModcCode is not null)
return result B

Else

Derived Hourly Mode Status = true

NOXR: If (Current DHV Method == "AMS" AND Current DHV RecordModcCode is null)

Derived Hourly Mode Status = true

else if (Current DHV Method == "AE")

If (Current DHV RecordModcCode is not null)
return result C

Else

Derived Hourly Mode Status = true

else

if (Current DHV RecordModcCode not in set {01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 11, 12, 13, 14, 15, 21,22,

23,24,25, 53, 54, 55})
return result A

Else

Derived Hourly Mode Status = true

C02C: If (Current DHV RecordModcCode not in set {01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 12,21, 53, 54, 55})
return result A

Else

Derived Mode Status = true

C02: If (Current DHV Method == "AMS")

If (Current DHV RecordModcCode is not null and is not in set {01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 12, 53, 54,

55})

Environmental Protection Agency	Page 351 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result A

Else

Derived Hourly Mode Status = true

else

If (CurrentDHVRecordModcCode is not null)
return result B

Else

Derived Hourly Mode Status = true

HI: If (Current DHV Method == "AMS")

If (Current DHV RecordModcCode is not null and is not in set {01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 12, 26, 53,
54,55})

return result A

Else

Derived Hourly Mode Status = true

else

If (Current DHV RecordModcCode is not null and Current DHV RecordModcCode o "26")
return result B

Else

Derived Hourly Mode Status = true

H20: if (Current DHV Method == "MWD")

If (Current DHV RecordModcCode not in set {01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 12, 21, 53, 54, 55})
return result A

else

Derived Hourly Mode Status = true

else if (Current DHV Method == "MDF")

If (Current DHV RecordModcCode o "40")
return result A

else

Derived Hourly Mode Status = true

S02R: If (S02 F23 Method Active For Hour == true)

If (Current DHV RecordModcCode o "40")
return result A

else

Derived Hourly Mode Status = true

HIT: If (Current DHV RecordModcCode == "45")

If (LME HI Substitute Data Code == "MHHI")
Derived Hourly Mode Status = true

else

return result D
else if (Current DHV RecordModcCode is not null)
return result A

Else

Derived Hourly Mode Status = true

S02M, NOXM, C02M:

If (Current DHV RecordModcCode is not null)
return result B

Else

Derived Hourly Mode Status = true

Environmental Protection Agency

Page 352 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result	Response

A	The MODCCode reported in the DHV record for [param] is invalid.

B	You reported an MODCCode in the DHV record for [param]. This field should be

blank.

C	You reported an MODCCode in the DHV record for NOXR. This field should be blank

when you use the Appendix E method to determine the NOx emission rate.

D	You reported an MODCCode of 45 in the DHV record for HIT, but you have not

reported a SubstituteDataCode of MHHI in the active heat input method record in your
monitoring plan.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Concentration Derived Hourly Evaluation

2	Process/Category:	Emissions Data Evaluation Report	C02 Mass Rate Derived Hourly Evaluation

3	Process/Category:	Emissions Data Evaluation Report	C02M Derived Hourly Evaluation (LME)

4	Process/Category:	Emissions Data Evaluation Report	H20 Derived Hourly Evaluation

5	Process/Category:	Emissions Data Evaluation Report	Heat Input Derived Hourly Evaluation

6	Process/Category:	Emissions Data Evaluation Report	HIT Derived Hourly Evaluation (LME)

7	Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

8	Process/Category:	Emissions Data Evaluation Report	NOx Mass Rate Derived Hourly Evaluation

9	Process/Category:	Emissions Data Evaluation Report	NOXM Derived Hourly Evaluation (LME)

10	Process/Category:	Emissions Data Evaluation Report	S02 Derived Hourly Evaluation

11	Process/Category:	Emissions Data Evaluation Report	S02M Derived Hourly Evaluation (LME)

12	Process/Category:	Emissions Data Evaluation Report	S02R Derived Hourly Evaluation

Severity

Critical Error Level 1
Non-Critical Error

Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 353 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-14

Check Name:	Check Percent Monitor Availability in DHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Derived Hourly Pma Status = false
Derived Hourly Missing Data Status = true

If (Derived Hourly Mode Status == true)

If ( Current DHVitecortf.PercentAvailable is NULL)

if (Current DHV Parameter not in set {LEO, C02C, NOXR})

Derived Hourly Pma Status = true

else if {Current DHV Parameter == "NOXR" and Current DHV Method not in set {PEM, CEM})
Derived Hourly Pma Status = true

else if (Current DHV Parameter == "LEO" and Current Dffl' Record. ModcCodc == "40")
Derived Hourly Pma Status = true

if (Current DHV RecordModcCode not in set {01, 02, 03, 04, 14, 21, 22, 53, 54} AND Legacy Data Evaluation
== true)

Derived Hourly Pma Status = true
return result A

else

return result B

else

if (Current DHV Parameter == "NOXR" and Current DHV Method == "AE")
return result C

else if (Current DHV Parameter == "LEO" and Current DHV RecordModcCode == "40")
return result C

else if (Current DHV Parameter not in set {H20, C02C, NOXR} AND Current DHV Method o "AMS")
return result C

else if (Current 1)11] Record. I 'crccn t A vail able 100.0 OR

Current Dffl Record. I 'crccn t A vail able < 0.0)
return result D

Else

case ( Current DHV RecordModcCode )

= 06: If Current DHVRecord.PercentAvm\&b\e >= 90.0
Derived Hourly Pma Status = true

Else

return result E

= 08: If Current DHV Record PercentAv&i\ab\e >= 95.0
Derived Hourly Pma Status = true

Else

return result E

= 09: If Current DHVifecortf.PercentAvailable >= 90.0 AND Current DHVifecortf.PercentAvailable < 95.0
Derived Hourly Pma Status = true

Else

return result E

= 10: If Current DHVifecortf.PercentAvailable >=80.0 AND Current DHVifecortf.PercentAvailable < 90.0

Environmental Protection Agency

Page 354 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Derived Hourly Pma Status = true
Else If Current DHVParameter == "NOXR" and Current DHVRecord.PercentAvai\ab\e >=90.0
Derived Hourly Pma Status = true
return result F

Else

return result E

= 11: If Current DZ/Fifecortf.PercentAvailable >=90.0
Derived Hourly Pma Status = true

Else

return result E

All other MODC Codes:

Derived Hourly Pma Status = true

Results:

Result

B
C

D

E
F

Usage:

1

2

3

4

5

6

7

8

9

10

11

12

Response

You reported an MODCCode of [ModcCode] in the DHV record for [param], but you

did not report a value for PercentAvailable. While this is not required for legacy EDR

data, it is required in all [param] DHV records for ECMPS.

You did not report PercentAvailable in the DHV record for [param].

You reported PercentAvailable in the DHV record for [param]. This field should be

blank.

The PercentAvailable reported in the DHV record for [param] is invalid. This value
must be between 0 and 100.

You reported an MODCCode of [modcCode] in the DHV for [param], but the
PercentAvailable is not appropriate for this MODC.

You reported an MODCCode of 10 in the [type] record for [param], but the
PercentAvailability is greater than or equal to 90. When the PMA is greater than or
equal to 90, you should only report an MODC of 10 to indicate that you used the
maximum hourly value in the lookback period for the next available higher load bin,
because there were no quality-assured data in the bin corresponding to the current load
range. (See Part 75.33(c)(5).)

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02 Mass Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02M Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	H20 Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	Heat Input Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	HIT Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Mass Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOXM Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	S02 Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	S02M Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	S02R Derived Hourly Evaluation

Severity

Informational Message

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Informational Message

Environmental Protection Agency

Page 355 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-15

Check Name:	Check Prior QA'd Hours for MODC 07

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

if (Derived Hourly Mode Status == true AND Derived Hourly PMA Status == true)
if (Current DHV Record. ModcCode == 07)

case (Current DHV Parameter)

NOXR: MODC Set = {01,02,04,14,21,22,53}
C02C: MODC Set = {01, 02, 04, 21, 53}
H20: MODC Set = {01, 02, 04, 21, 53}

Prior QA Hours = count DerivedHourly ValueData records where

DerivedHourlyValueData.ModcCode in set MODC Set AND

DerivedHourlyValueData.ParameterCode = Current DHVifecortf.ParameterCode AND
( DerivedHourly ValueData.BeginDate < Current Date OR

(DerivedHourlyValueData.BeginDate = Current Date AND DerivedHourlyValueData.BeginHour < Current
Hour))

if (Current DHV Parameter == "NOXR")
if (Prior QA Hours > 2160)

Derived Hourly Missing Data Status = false
return result A

else

if (Prior QA Hours > 720)

Derived Hourly Missing Data Status = false
return result A

Results:

Result	Response	Severity

A	You reported an MODCCode of 07 in the DHV record for [param], but too many prior	Critical Error Level 1

quality assured hours exist in evaluation period for use of this missing data approach.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Concentration Derived Hourly Evaluation

2	Process/Category:	Emissions Data Evaluation Report	H20 Derived Hourly Evaluation

3	Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 356 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-16

Check Name:

Check for Correct Use of Missing Data MODCs

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current DHVHBHA Value = null

if (Derived Hourly Mode Status == true AND Derived Hourly PMA Status == true)

case (Current DHV Parameter)

NOXR: MODCSet = {01, 02, 03, 04, 14, 21, 22, 53, 54}
C02C: MODC Set = {01, 02, 03, 04, 21, 53, 54}
H20: MODC Set = {01, 02, 03, 04, 21, 53, 54}

if {Current DHV Record. ModcCode in set {06, 08, 09})

If {Current MHVParameter in set {C02C, H20})

Prior Record = latest DerivedHourly ValueData record or MonitorHourlyValueData record where
ParameterCode = Current DHV Parameter AND
ModcCode in set MODC Set AND
(Date < Current Date OR

(Date = Current Date AND Hour < Current Hour ))

If Prior Record is not null and is in current reporting period

Next Record = earliest Deri vedHourly ValueData record or MonitorHourlyValueData record where
Data.ParameterCode = Current MHV Parameter AND
Data.ModcCode in set MODC Set AND
(Date > Current Date OR

(Date = Current Date AND Hour > Current Hour))

If Next Record is not null and is in current reporting period

If Prior Record. AdiustedHouriyValue >= 0 AND A'ex/^ecorrfAdjustedHourlyValue >= 0

Current DHV HBHA Value = {Prior .Recoraf A djustedHourlyValue + Next
.RecorafAdjustedHourlyValue) / 2, ROUNDED to a single decimal.

else

Derived Hourly Missing Data Status = false
return result A

Prior DHV Record = latest DerivedHourly ValueData record where

DerivedHourlyValueData.ParameterCode = Current DHV Parameter AND
DerivedHourValueData.ModcCode in set MODC Set AND
[DerivedHourly ValueData.Date < Current Date OR

(DerivedHourly ValueData.Date = Current Date AND DerivedHourly ValueData.Hour < Current Hour )]
If Prior DHV Record is not null and is in current reporting period

Next DHV Record = earliest DerivedHourly ValueData record where

else

Environmental Protection Agency

Page 357 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

DerivedHourlyValueData.ParameterCode = Current MHVParameter AND
DerivedHourValueData.ModcCode in set MODC Set AND
[DerivedHourly ValueData.Date > Current Date OR

(DerivedHourly ValueData.Date = Current Date AND DerivedHourlyValueData.Hour > Current
Hour)]

If Next DHV Record is not null and is in current reporting period

If Prior DHV Record. AdjustedHour\yValue >= 0 AND Next DHV Record.AdjustedHourlyValue

>=0

Current DHVHBHA Value = (Prior DHV.Recoraf.AdjustedHourlyValue + Next DHV
.Recoraf.AdjustedHourlyValue) / 2, ROUNDED to three decimal places.

else

Derived Hourly Missing Data Status = false
return result A

else if (Current DHVRecordMo&cCo&e =="11")

Prior Measured DHV Record = DerivedHourlyValueData record at latest time for the location where
DerivedHourlyValueData.ModcCode in set MODC Set AND
DerivedHourlyValueData.ParameterCode = Current DHV Parameter AND
(DerivedHourlyValueData.BeginDate < Current Date OR

(DerivedHourlyValueData.BeginDate = Current Date AND DerivedHourlyValueData.BeginHour < Current
Hour))

If Prior Measured DHVRecord is not null and is in the current reporting period
PriorDate = Prior Measured DHV Record. BeginDate
PriorHour = Prior Measured DHV Record. BeginHour

else

PriorDate = the day prior to the beginning of the current reporting period
PriorHour = 23

Next Measured DHV Record = DerivedHourlyValueData record at earliest time for the location where
DerivedHourlyValueData.ModcCode in set MODC Set AND
DerivedHourlyValueData.ParameterCode = Current DHV Parameter AND
(DerivedHourlyValueData.BeginDate > Current Date OR

(DerivedHourlyValueData.BeginDate = Current Date AND DerivedHourlyValueData.BeginHour > Current
Hour))

If Next Measured DHV Record is not null and is in the current reporting period
NextDate = Next Measured DHVRecordSegmDsAe
NextHour = Next Measured DHV Record. BeginHour

else

NextDate = the day after the end of the current reporting period
NextHour = 0

Missing Data Period Length = Count of DerivedHourlyValueData records for the location where
DerivedHourlyValueDataParameterCode = Current DHV Parameter AND
(DerivedHourlyValueData.BeginDate > PriorDate OR

(DerivedHourlyValueData.BeginDate = PriorDate AND DerivedHourlyValueData.BeginHour >
PriorHour) ) AND

(DerivedHourlyValueData.BeginDate < NextDate OR

(DerivedHourlyValueData.BeginDate = NextDate AND DerivedHourlyValueData.BeginHour <
NextHour) )

Environmental Protection Agency

Page 358 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (Current DHV Record PercentAvailable is null OR Current Dffl' Record PcrccntA vailablc >= 95.0)
if (Missing Data Period Length >24)

Derived Hourly Missing Data Status = false
return result B

else

if (Missing Data Period Length > 8)

Derived Hourly Missing Data Status = false
return result B

Results:

Result	Response	Severity

A	The AdjustedHourlyValue reported in the DHV record for [param] either before or after	Critical Error Level 1

the current hour is invalid.

B	You reported an MODCCode of 11 in the DHV record for [param], but the length of the	Critical Error Level 1

missing data period exceeds the allowable value for use of this missing data procedure.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Concentration Derived Hourly Evaluation

2	Process/Category:	Emissions Data Evaluation Report	LOO Derived Hourly Evaluation

3	Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 359 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-17

Check Name:

Check Extraneous Data in DHV Record

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Derived Hourly Null Status = false
Hourly Extraneous Fields = null

if (Current Z)//Fifecorrf.UnadjustedHourlyValue is not null)

append "UnadjustedHourlyValue" to Hourly Extraneous Fields

if (Current DHV Record.SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields

if (Current DHV Record.OpemtingConditionCode is not null)
if (Current DHV Parameter is not equal to "NOXM")

append "OperatingConditionCode" to Hourly Extraneous Fields

if (Current DHVifecorrf.FuelCode is not null)

if (Current DHV Parameter not in set {N0XM,S02M,C02M})
append "FuelCode" to Hourly Extraneous Fields

if (Hourly Extraneous Fields is not null)
return result A

else

Derived Hourly Null Status = true

Results:

Result
A

Response

You reported [fieldnames] in the DHV record for [param]. This data should be blank.

Severity

Non-Critical Error

Environmental Protection Agency

Page 360 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:

2	Process/Category:

3	Process/Category:

4	Process/Category:

5	Process/Category:

6	Process/Category:

7	Process/Category:

8	Process/Category:

9	Process/Category:

10	Process/Category:

11	Process/Category:

Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report

C02 Concentration Derived Hourly Evaluation
C02 Mass Rate Derived Hourly Evaluation
C02M Derived Hourly Evaluation (LME)
H20 Derived Hourly Evaluation
Heat Input Derived Hourly Evaluation
HIT Derived Hourly Evaluation (LME)
NOx Mass Rate Derived Hourly Evaluation
NOXM Derived Hourly Evaluation (LME)
S02 Derived Hourly Evaluation
S02M Derived Hourly Evaluation (LME)
S02R Derived Hourly Evaluation

Environmental Protection Agency

Page 361 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-18

Check Name:	Check System in DHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current DHVMon Sys Record = null
Derived Hourly System Status = false

if (Current DHV Parameter == "NOXR")

App E Constant Fuel Mix = false

If {{Current DHV Parameter in set {S02, S02R, NOX, C02} AND Current DHV Method o "AMS") OR

{Current DHV Parameter == "HI" AND Current DHV Method in set {CALC, AD, ADCALC}) OR
{Current DHV Parameter == "H20" AND Current DHV Method == "MDF") OR
LME HI Method is not null)

if Current DHVifecorrf.MonitoringSystemID is NOT null
return result A

else

Derived Hourly System Status = true

else if {Current DHV Parameter <> "HI")

case {Current DHV Parameter)

NOXR: MODCSet = {01, 02, 03, 04, 14, 21, 22}

C02C: MODC Set = {01, 02, 03, 04, 21}

H20: MODC Set = {01,02, 03, 04,21}

If (Current DHV Record.MonitoringSvstcmII ) is null)

If {Current DHV Method == "AMS")

Derived Hourly System Status = true

Else If {Current DHV Method == "AE")

If Current DHVifecorrf.OperatingConditionCode is null
Derived Hourly System Status = true

else

return result J

Else If {Current DHV Record. ModcCodc in set MODC Set)
return result C

else

Derived Hourly System Status = true

else

If {Derived Hourly MODC Status == true AND Current DHV Method in set {CEM, PEM, MWD} AND Current DHV
Record. ModcCodc not in set {05, 53, 54} AND Current Dffl' Record. ModcCodc not in set MODC Set)
return result B

else

Current DHV Mon Sys Record = find active MonitoringSystemData record for location where
MonitoringSystemData.MonitoringSystemID = Current DHVitecortf.MonitoringSystemID

if {Current DHV Mon Sys Record is null)

Environmental Protection Agency	Page 362 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result D

else if (Derived MHVMon Sys ifecorrf.SystemTypeCode o Current DHVSystem Type)
return result E

else if (Current DHV Method == "AE" AND Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count for
Oil > 0)

If (Derived DHV Mon Sys Record.VuelCode == "MIX" OR Current DHV
Record.OperatingConditionCode is not null)

if (Current DHV Record OperatingConditionCode == "E")
return result F

else

App E Constant Fuel Mix = true

App E Reporting Method = "CONSTANT"

App E Reported Value = Current DHV Record. AdjustedHourlyValue
App E Segment Number = Current DHV Record. SegmentNumber
App E Fuel Code = "MIX"

App E NOXE System ID = Current DHVifecorrf.MonitoringSystemID
App E NOXE System Identifier = Current DHVitecortf.Systemldentifier
Derived Hourly System Status = true

if (Current DHV Record OperatingConditionCode in set {X, Y, Z, U, W, N, M})
App E Op Code = Current DHV Record. OperatingConditionCode
if (Derived DHV Mon Sys Record.VuelCode o "MIX")
return result G

else

return result H

else

return result I

else

Derived Hourly System Status = true

else

Derived Hourly System Status = true

Environmental Protection Agency

Page 363 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

A

B

C

D

E
F

G

H
I

Usage:

1

2

3

4

5

6

7

8

9

10

11

12

Response

You reported [fieldnames] in the DHV record for [param]. This data should be blank.
You reported a MonitoringSystemID in the DHV record for [param]. This field should
be blank when missing data substitution is used.

You did not report a MonitoringSystemID in the DHV record for [param]. This
information is required when you report measured data.

You reported MonitoringSystemID [ID] in the DHV record for [param], but according
to your monitoring plan this system was not active during the hour.

You reported MonitoringSystemID [ID] in the DHV record for [param], but the
SystemTypeCode of this system is not appropriate.

You reported an OperatingConditionCode of E in the DHV record for NOXR. You
should report the NOx emission rate for emergency fuels in an HPFF record, not a DHV
record.

You reported an OperatingConditionCode in the DHV record for NOXR, which
indicates that you are determining NOx emission rate from a mixed fuel Appendix E
curve, but the FuelCode of NOXE MonitoringSystemID [ID] is not equal to "MIX". If a
NOXE system measures an individual fuel, the emissions from this system should be
reported in an HPFF record, not a DHV record.

The OperatingConditionCode reported in the DHV record for NOXR is missing or
invalid.

You reported NOXE MonitoringSystemID [ID] in the DHV record for NOXR, but the
FuelCode of this system is not equal to "MIX". If a NOXE system measures an
individual fuel, the emissions from this system should be reported in an HPFF record. If
this data represents unit-level emissions based on fuel-specific emissions data that have
been reported in one or more HPFF records, then the MonitoringSystemID should be
blank.

You reported an OperatingConditionCode in the DHV record for NOXR, which
indicates that you are determining NOx emission rate using Appendix E, but you did not
report a MonitoringSystemID in this record. If you determined the NOx emission rate
from a mixed fuel curve or via heat input apportionment, you should report the
MonitoringSystemID of the NOXE system for the curve. If you determined the NOx
emission rate from one or more individual fuel curves, you should not report an
OperatingConditionCode in the NOXR DHV record.

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02 Mass Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02M Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	H20 Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	Heat Input Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	HIT Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Mass Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOXM Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	S02 Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	S02M Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	S02R Derived Hourly Evaluation

Severity

Non-Critical Error
Non-Critical Error

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 364 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-19

Check Name:	Check System Designation Code for System in DHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

If (Derived Hourly Mode Status == true AND Derived Hourly System Status == true AND Current DHV Mon Sys Record is not null)

case (Current Dffl' Record. ModcCodc)

01: If (Current DHV Mon Sys Record. SystemDesignationCode NOT in set {P, PB})
return result A

02: If (Current DHV Mon Sys Record. SystemDesignationCode NOT in set {B, RB, DB}
return result B

04: If (Current DHV Mon Sys Record. SystemDesignationCode o "RM")
return result C

22: If (Current DHV Mon Sys Record. SystemDesignationCode o "CI")
return result D

Results:

Result
A

B

C

D

Usage:

1

2

3

Response

You reported an MODCCode of [modcCode] in the DHV record for [param], but
MonitoringSystemID [ID] is not a primary system.

You reported an MODCCode of [modcCode] in the DHV record for [param], but
MonitoringSystemID [ID] is not a backup system.

You reported an MODCCode of [modcCode] in the DHV record for [param], but
MonitoringSystemID [ID] is not a reference method system.

You reported an MODCCode of 22 in the DHV record for NOXR, but
MonitoringSystemID [ID] is not a certified inlet system.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	LOO Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 365 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-24

Check Name:	Check Formula in DHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Derived Hourly Formula Status = false
Derived Hourly Equation Status = false
Current DHV Multiple Fuel Equation Code == null
Current DHV Formula Record = null

If (Current DHV Records ormulalDKey is null)

If (Current DHV Method in set {AMS, LME}) OR

(Derived Hourly Mode Status == true AND Current DHV Record.ModcCode == "40") OR
LME HI Method is not null)

Derived Hourly Formula Status = true

else if (Current DHV Parameter = "AE" AND App E Constant Fuel Mix == true)

Derived Hourly Formula Status = true

else if (Current DHV Parameter in set {NOXR, S02, HI, C02}) AND Current DHV Method in set {AD, AE})
Derived Hourly Formula Status = true

If (Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count for Oil >1)

case (Current DHV Parameter)

NOXR: Current DHV Multiple Fuel Equation Code = "E-2"

S02: Current DHV Multiple Fuel Equation Code = "D-12"

C02: Current DHV Multiple Fuel Equation Code = "G-4A"

HI: Current DHV Multiple Fuel Equation Code = "D-15A"

Locate active Formula Record for location WHERE

ParameterCode == Current DHV Parameter AND
EquationCode == Current DHV Multiple Fuel Equation Code

If found,

If (Legacy Data Evaluation == true)
return result A

else

return result B

else if (Current DHV Method = "PEM")

Derived Hourly Formula Status = true

else if (Current DHV Parameter == "NOX" AND Current NOx Rate Method Code == " AE" AND Hourly Fuel Flow Count for
Gas + Hourly Fuel Flow Count for Oil > 1 AND Legacy Data Evaluation == true)

Derived Hourly Formula Status = true

else if (Current DHV Parameter in set {NOXR, H20, C02C})

If (Derived Hourly Mode Status == true)

If (Current DHV Record.ModcCode in set {01, 02, 03, 04, 05, 14, 21, 22, 53, 54})
return result C

else

Derived Hourly Formula Status = true

else

return result C

Environmental Protection Agency

Page 366 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

If {Current DHV Parameter in set {S02R, H20} AND Current DHV RecordMODCCode == "40")
return result D

else if (LME HI Method is not null)
return result J

else

Current DHV Formula Record= Find MonitoringFormulaData record where

MonitoringF ormulaData,MonitoringF ormulalDKey = Current DHV Records ormulalDKey

If (Current DHV Formula Record is null)
return result E

else if (Current DHV Formula ifecortf.ParameterCode is not equal to Current DHV Parameter)

If Current DHV Parameter == "HI" AND Current DHV Method = "AD" AND Hourly Fuel Flow Count for Gas
+ Hourly Fuel Flow Count for Oil > 1 AND Current DHV Formula itecortf.ParameterCode == "HIT" AND
Current DHV Formula ifecorrf.EquationCode == "D-15" AND Legacy Data Evaluation == true)
return result I

else

return result F

else

Derived Hourly Formula Status = true

if Current DHV Parameter == "HI" AND Current DHV Method = "ADCALC" and Current DHV Formula
ifecorrf.EquationCode not in {F-21A,F-21B,F-21D}

Count all active MonitoringFormulaData record for location where
EquationCode in {F-21A,F-21B,F-21D}

if (Count =1)

Current DHV Formula Record = Find active MonitoringFormulaData record for location where
EquationCode in {F-21A,F-21B,F-21D}

else if (Current DHV Method == "AE")

if (App E Constant Fuel Mix == true OR Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count
for Oil == 0)

return result H

else if (Derived Hourly Mode Status == true)

If (Current DHV Parameter in set {NOXR, H20, C02C} AND Current DHV RecordMODCCode NOT
in set {01, 02, 03, 04, 05, 14, 21, 22, 53, 54} AND Legacy Data Evaluation == false)
return result G

Environmental Protection Agency

Page 367 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C
D

E

F

G

H

I

Usage:

1

2

3

4

5

6

7

8

9

10

11

12

Response

You did not report a FormulalD in the DHV record for [param]. While this is

acceptable for legacy EDR data, the FormulalD will be required for ECMPS.

You did not report a FormulalD in the DHV record for [param]. This formula is

required when you burn multiple fuels during the hour.

You did not report a FormulalD in the DFtV record for [param].

You reported an MODC of 40, but you reported a FormulalD in the DFtV record for

[param]. This field should be blank when reporting a default value.

You reported FormulalD [ID] in the DFtV record for [param], but there is no active

Formula record for this formula in your monitoring plan.

You reported FormulalD [ID] in the DHV record for [param], but this is not a [param]
formula.

You reported a FormulalD in the DHV record for [param]. This field should be blank
when using missing data substitution.

You reported a FormulalD in the DHV record for NOXR. This field should be blank
unless you determine the NOX emission rate using multiple Appendix E curves.
You reported FormulalD [ID] in the DHV record for HI, but FormulaCode D-15 will no
longer be appropriate for calculating HI from multiple fuels. For ECMPS, the
ParameterCode should be for this formula should be HI and the FormulaCode should be
"D-15A".

You reported a FormulalD in the DHV record for [param]. This field should be blank
when reporting emissions for LME units.

Severity

Informational Message

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Non-Critical Error

Critical Error Level 1

Informational Message

Critical Error Level 1

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02 Mass Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02M Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	H20 Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	Heat Input Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	HIT Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Mass Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOXM Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	S02 Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	S02M Derived Hourly Evaluation (LME)

Process/Category:	Emissions Data Evaluation Report	S02R Derived Hourly Evaluation

Environmental Protection Agency

Page 368 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-25

Check Name:	Check Heat Input Equation Code

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

CO 2 Cone Checks Needed for Heat Input = false
02 Wet Checks Needed for Heat Input = false
02 Dry Checks Needed for Heat Input = false

if (Heat Input App D Method Active For Hour == true)

Hourly Fuel Flow Checks needed for Heat Input = true

else

Hourly Fuel Flow Checks needed for Heat Input = false

Heat Input Equation Code = null

if (Derived Hourly Formula Status == true)

if (Current DHVFormula Record is not null)

Heat Input Equation Code = Current DHV Formula ifecorrf.EquationCode
if (Heat Input CEM Method Active For Hour == true)

if {Heat Input Equation Code in set {F-15, F-16, F-17, F-18} )
Derived Hourly Equation Status = true
Flow Monitor Hourly Checks Needed = true

if {Heat Input Equation Code o "F-15")

Moisture Needed = true
append "MIN" to H20 Missing Data Approach

if {Heat Input Equation Code = "F-15" OR Heat Input Equation Code= "F-16" )

C02 Cone Checks Needed for Heat Input = true
FC Factor Needed = true
else if {Heat Input Equation Code = "F-17")

02 Wet Checks Needed for Heat Input = true
FD Factor Needed = true
else if {Heat Input Equation Code = "F-18")

02 Dry Checks Neededfor Heat Input = true
FD Factor Needed = true
else if {Heat Input Equation Code is null)
return result A

else

return result B

else if {Heat Input App D Method Active For Hour == true)
if {Heat Input Equation Code == "D-15A")

Derived Hourly Equation Status = true
else if {Heat Input Method Code == "ADCALC" and Heat Input Equation Code in set {F-21A, F-21B, F-21C,
F-21D, F-25})

Derived Hourly Equation Status = true
if {Heat Input Equation Code == "F-21D")

Apportionment HI Method Array for the location = "NOCALC"
else if {Heat Input Equation Code in set {F-19, F-19V, F-20, D-6, D-8} AND {Legacy Data Evaluation == true
OR Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count for Oil == 1))

Derived Hourly Equation Status = true
return result C
else if {Heat Input Equation Code is null)
return result A

else

Environmental Protection Agency

Page 369 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result B

else if (Current DHVMethod in set {CALC, ADCALC})

if (Heat Input Equation Code in set {F-21A, F-21B, F-21C, F-25})

Derived Hourly Equation Status = true
else if (Heat Input Equation Code == "SS-3B")

Derived Hourly Equation Status = true

Apportionment HI Method Array for the location = "COMPLEX"
else if (Heat Input Equation Code == "F-21D" OR Current DHV Method == "ADCALC")
Derived Hourly Equation Status = true

Apportionment HI Method Array for the location = "NOCALC"
else if (Heat Input Equation Code is null)
return result A

else

return result B

else

Derived Hourly Equation Status = true

else

Derived Hourly Equation Status = true

Results:

Result
A

You reported FormulalD [ID] in the DHV record for [param], but you did not report a
FormulaCode for this formula in your monitoring plan.

Response

Severity

Critical Error Level 1

B

You reported FormulalD [ID] in the DHV record for HI, but the FormulaCode of this
formula is not appropriate for calculating HI.

Critical Error Level 1

C

You reported FormulalD [ID] in the DHV record for HI, but a formula with a

Informational Message

FormulaCode [EQCODE] is no longer appropriate in this record. For ECMPS, if you
are calculating heat input from multiple fuels using Appendix D, you should report a
formula with a FormulaCode of D-15A in the DHV record; otherwise, do not report a
FormulalD.

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Heat Input Derived Hourly Evaluation

Environmental Protection Agency

Page 370 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks:

HOURDHV-26

Check NOX Equation Code

Applicability:	CEM Check

Description:

Specifications:

NOx Rate Checks Needed for NOx Mass Calc = false
Heat Input Checks Needed for NOx Mass Calc = false

NOx Mass Equation Code = null
if (Derived Hourly Formula Status == true)

if (Current DHVFormula Record is not null)

NOx Mass Equation Code = Current DHV Formula ifecorrf.EquationCode
if (Current DHV Method == "CEM")

if (NOx Mass Equation Code in set {F-26A, F-26B} )

Derived Hourly Equation Status = true

Flow Monitor Hourly Checks Needed = true

if (NOx Mass Equation Code = "F-26B") 11 note that the old name for this formula was "N-2"
Moisture Needed = true
append "MIN" to H20 Missing Data Approach

else if (NOx Mass Equation Code is null)
return result A

else

return result B

else if (Current DHV Method == "NOXR")

if (NOx Mass Equation Code == "F-24A" )

Derived Hourly Equation Status = true

Heat Input Checks Needed for NOx Mass Calc = true

Nox Rate Checks Needed for NOx Mass Calc = true

else if (NOx Mass Equation Code is null)
return result A

else

return result C

else

Derived Hourly Equation Status = true
Derived Hourly Equation Status = true

if (Current NOx Rate Method Code == "AE" AND Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count for Oil
> 1 AND Legacy Data Evaluation == true)

NOx Mass Equation Code = "F-24A"

Environmental Protection Agency

Page 371 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

Usage:

1

Response

You reported FormulalD [ID] in the DHV record for [param], but you did not report a
FormulaCode for this formula in your monitoring plan.

You reported FormulalD [ID] in the DHV record forNOX, but the FormulaCode of this
formula is not appropriate for calculating NOX from a NOXC system.

You reported FormulalD [ID] in the DHV record forNOX, but the FormulaCode of this
formula is not appropriate for calculating NOX from a NOx-diluent system.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	NOx Mass Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 372 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-27

Check Name:	Check NOXR Equation Code

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

02 Dry Checks Needed for NOx Rate Calc = false
02 Wet Checks Needed for NOx Rate Calc = false
CO 2 Diluent Checks Needed for NOx Rate Calc = false

if (Current DHV Method == "AE")

Hourly Fuel Flow Neededfor NOx Rate Calc = true

else

Hourly Fuel Flow Neededfor NOx Rate Calc = false

NOx Rate Equation Code = "" 11 null string
if (Derived Hourly Formula Status == true)

if (Current DHV Formula Record is not null)

NOx Rate Equation Code = Current DHV Formula ifecorrf.EquationCode

if {Current NOx Rate Method Code == "CEM")

if {NOx Rate Equation Code in set {19-1, 19-2, 19-3, 19-3D, 19-4, 19-5, 19-5D, 19-6, 19-7, 19-8, 19-9, F-5, F-6}
)

Derived Hourly Equation Status = true

If {Current DHVRecord.ModcCode in set {01, 02, 03, 04, 05, 14,21, 22, 53, 54})

if {NOx Rate Equation Code in set {19-1, 19-4, F-5} )

02 Dry Checks Needed for NOx Rate Calc = true
FD Factor Needed = true

else if {NOx Rate Equation Code in set {19-3, 19-5} )

02 Wet Checks Needed for NOx Rate Calc = true
FD Factor Needed = true

else if {NOx Rate Equation Code in set {19-3D, 19-5D} )

FD Factor Needed = true

else if {NOx Rate Equation Code in set {19-6, 19-7, 19-8, 19-9, F-6} )
C02 Diluent Checks Needed for NOx Rate Calc = true
FC Factor Needed = true

else if {NOx Rate Equation Code == "19-2")

02 Wet Checks Needed for NOx Rate Calc = true
FW Factor Needed = true

if {NOx Rate Equation Code in set {19-3, 19-3D, 19-4, 19-8}

Moisture Needed = true

append "MAX" to H20 Missing Data Approach

else if {NOx Rate Equation Code in set {19-5, 19-9}

Moisture Needed = true
append "MIN" to H20 Missing Data Approach

else (if {NOx Rate Equation Code is null)

Environmental Protection Agency

Page 373 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result A

else

return result B

else if (Current NOx Rate Method Code == "AE")
if (NOx Rate Equation Code == 'E-2')

Derived Hourly Equation Status = true
else if (NOx Rate Equation Code is null)
return result A

else

return result C

else

Derived Hourly Equation Status = true

else

Derived Hourly Equation Status = true

Results:

Result
A

B

C

Response

You reported FormulalD [ID] in the DHV record for [param], but you did not report a
FormulaCode for this formula in your monitoring plan.

You reported FormulalD [ID] in the DHV record forNOXR, but the FormulaCode of
this formula is not appropriate for calculating NOXR.

You reported FormulalD [ID] in the DHV record forNOXR, but the FormulaCode of
this formula is not appropriate for calculating NOXR from multiple fuels. The
FormulaCode should be E-2.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 374 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-28

Check Name:

Check C02C Equation Code

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

CO2 Cone CEM Equation Code = "" 11 null string
if (Derived Hourly Formula Status == true)

if (Current DHVFormula Record is not null)

CO2 Cone CEM Equation Code = Current DHV Formula ifecorrf.FormulaCode
if (C02 Cone CEM Equation Code in set {F-14A, F-14B})

Derived Hourly Equation Status = true

else

return result A

else

Derived Hourly Equation Status = true

Results:

Result
A

Response

You reported FormulalD [ID] in the DFtV record for C02C, but the FormulaCode of
this formula is not appropriate for calculating C02C.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Derived Ftourly Evaluation

Environmental Protection Agency

Page 375 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-29

Check Name:

Check C02 Equation Code

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

C02 Cone Checks Needed for C02 Mass Calc = false
Use C02 Diluent Cap for Co 2 Mass Calc = false
Use 02 Diluent Cap for Co2 Cone Calc = false
if (C02 App D Method Active For Hour == true)

Hourly Fuel Flow Checks Needed for C02= true

else

Hourly Fuel Flow Checks Needed for C02 = false

CO2 Mass Equation Code = "" 11 null string
if (Derived Hourly Formula Status == true)

if (Current DHVFormula Record is not null)

CO2 Mass Equation Code = Current DHV Formula ifecorrf.FormulaCode
if (CO2 CEM Method Active For Hour == true)

Flow Monitor Hourly Checks Needed = true
C02 Cone Checks Needed for C02 Mass Calc = true

if (C02 Mass Equation Code== "F-2" OR CO2 Mass Equation Code == "F-l 1")
Derived Hourly Equation Status= true

If (CO2 Mass Equation Code== 'F-2')

Moisture Needed = true
append "MIN" to H20 Missing Data Approach

if (Current I) HI' Record.\)i I ucntCapI ndicator == 1)

Use C02 Diluent Cap for Co2 Mass Calc = true
Use 02 Diluent Cap for Co2 Cone Calc = true

else if (CO2 App D Method Active For Hour == true)
if (C02 Mass Equation Code == "G-4A")

Derived Hourly Equation Status= true

else if (CO2 Mass Equation Code== "G-4" AND (Legacy Data Evaluation == true OR Hourly Fuel Flow Count
for Gas + Hourly Fuel Flow Count for Oil == 1))

Derived Hourly Equation Status= true
return result B

else

return result A

else

return result A

else

Derived Hourly Equation Status = true

else

Derived Hourly Equation Status= true

Environmental Protection Agency

Page 376 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

Usage:
1

Response

You reported FormulalD [ID] in the DHV record for C02, but the FormulaCode of this
formula is not appropriate for calculating C02.

You reported FormulalD [ID] in the DHV record for C02, but a formula with a
FormulaCode [EQCODE] is no longer appropriate in this record. For ECMPS, if you
are calculating C02 from multiple fuels using Appendix D, you should report a formula
with a FormulaCode of G-4A in the DHV record; otherwise, do not report a FormulalD.

Severity

Critical Error Level 1
Informational Message

Process/Category:

Emissions Data Evaluation Report	C02 Mass Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 377 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks:

HOURDHV-30

Check S02 Equation Code

Applicability:	CEM Check

Description:

Specifications:

S02 Monitor Hourly Checks Needed = false
if (SO 2 App D Method Active For Hour == true)

Hourly Fuel Flow Checks Needed for S02 = true

else

Hourly Fuel Flow Checks Needed for S02 = false

S02 Equation Code = "" 11 null string
if (Derived Hourly Formula Status == true)

If (Current DHVFormula Record is not null)

S02 Equation Code = Current DHV Formula ifecorrf.FormulaCode

if (S02 CEM Method Active For Hour == true)

if (SO2 Equation Code== "F-l" OR S02 Equation Code == "F-2")
Derived Hourly Equation Status = true

Flow Monitor Hourly Checks Needed = true

If (S02 Equation Code== "F-2")

Moisture Needed = true
append "MIN" to H20 Missing Data Approach

if (S02 Monitor Hourly Count == 0)
return result A

else

S02 Monitor Hourly Checks Needed = true

else if (S02 Equation Code== "F-23" AND S02 F23 Method Active For Hour == true)
Derived Hourly Equation Status = true

else

return result B

else if (SO2 F23 Method Active For Hour == true)
if (S02 Equation Code== "F-23")

Derived Hourly Equation Status = true

else

return result B

else if (SO2 App D Method Active For Hour == true)
if (S02 Equation Code = "D-12")

Derived Hourly Equation Status = true
else if (S02 Equation Code in {D-2, D-4, D-5} AND Hourly Fuel Flow Count for Gas + Hourly Fuel Flow
Count for Oil == 1))

Derived Hourly Equation Status = true
return result C

else

return result B

else

Derived Hourly Equation Status = true

else

Derived Hourly Equation Status = true

Environmental Protection Agency

Page 378 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

A

B

Response

You did not report an MHV record for [param] for the hour.

You reported FormulalD [ID] in the DHV record for S02, but the FormulaCode of this
formula is not appropriate for calculating S02.

You reported FormulalD [ID] in the DHV record for S02, but a formula with a
FormulaCode [EQCODE] is not appropriate in this record. If you are calculating S02
from multiple fuels using Appendix D, you should report a formula with a FormulaCode
of D-12 in the DHV record; otherwise, do not report a FormulalD.

Severity

Critical Error Level 1
Critical Error Level 1

Informational Message

Usage:
1

Process/Category:

Emissions Data Evaluation Report	S02 Derived Hourly Evaluation

Environmental Protection Agency

Page 379 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-31

Check Name:

Check H20 Equation Code

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

H20 CEM Equation Code = "" // null string
if (Derived Hourly Formula Status == true)

If (Current DHVFormula Record is not null)

H20 CEM Equation Code = Current DHV Formula ifecorrf.FormulaCode
if (H20 CEM Equation Code in set (F-31, M-1K)

Derived Hourly Equation Status = true

else

return result A

else

Derived Hourly Equation Status = true

Results:

Result
A

Response

You reported FormulalD [ID] in the DHV record for H20, but the FormulaCode of this
formula is not appropriate for calculating H20.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	H20 Derived Hourly Evaluation

Environmental Protection Agency

Page 380 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-32

Check Name:	Verify Correct Reporting of NOXC MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

If {Current DHVMethod in set {CEM, CEMNOXR})

If (Current DHV Parameter == "NOXR")

Nox Cone Needed for NOx Rate Calc = false

If Current DHVRecordModcCode in set {01, 02, 03, 04, 14, 21, 22, 53, 54} // only need cone for measured data
If (NOx Cone Monitor Hourly Count == 0)
return result A

else

Nox Cone Needed for NOx Rate Calc = true

else

If (NOx Cone Monitor Hourly Count == 1 AND Nox Cone Needed for NOx Mass Calc == false)
return result B

Else if (Current DHV Parameter == "NOX")

Nox Cone Needed for NOx Mass Calc = false

If (DerivedHourly Equation Status == true AND NOx Mass Equation Code begins with "F-26")
if (NOx Cone Monitor Hourly Count == 0)
return result A

else

Nox Cone Needed for NOx Mass Calc = true

Results:

Result

A

B

Usage:
1

Response

You did not report an MHV record for NOXC for the hour.

You reported an MHV record for NOXC, but you reported a MODCCode of [mode] in
the DHV record for NOXR. You should not report an MHV record for NOXC when
you use substitute data to determine the NOx emission rate.

Severity

Critical Error Level 1
Non-Critical Error

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Mass Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 381 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-33

Check Name:	Determine Default Value for MODC 40

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Derived Hourly Default Status == true

If (Derived Hourly Mode Status == true AND Current DHVRecordMo&cCo&e == 40)

If (Current DHV Parameter == "H20")

If Current DHV Record. AdiustedHour\yVa\ue is null OR

Current Dill' Record. Adj ustcdl Iourl v Val Lie <= 0 OR
Current Dill' Record. Ad} ustcdl Iourl v Val Lie >= 100
Derived Hourly Default Status == false
return result A

If H20 Default Max Value is null

\U112()Default Value > 0 AND H20Default Value < 100)

if (Current DHV Record. AdjustedHourly Value o H20 Default Value)
Derived Hourly Default Status == false
return result B

else if (H20 Default Max Value > 0 AND II2() Default Max Value < 100 AND II2() Default Min Value > 0 AND II2()
Default Min Value < 100)

If Current DHV Record. Adj ustedHourly Value < H20 Default Min Value OR

Current DHV Record AdjustedHourlyValue > H20 Default Max Value)

Derived Hourly Default Status == false
return result C

Else

H20 Default Value = Current DHV Record AdjustedHourlyValue

Else if (Current DHV Parameter == "S02R")

If Current DHV Record. AdiustedHour\yVa\ue is null OR

Current DHV Record. Adj ustedHourlyValue <= 0
Derived Hourly Default Status == false
return result D

If 123 Default Max Value is null

It'( 1-23 Default Value > 0)

if (Current DHV Record Adj ustedHourlyValue o F23 Default Value)
Derived Hourly Default Status == false
return result B

else if (F23 Default Max Value > 0 AND 123 Default Min Value > 0)

If Current DHV Record. Adj ustedHourlyValue < F23 Default Min Value OR

Current DHV Record AdjustedHourlyValue > 123 Default Max Value)
Derived Hourly Default Status == false
return result C

Else

F23 Default Value = Current Dill' Record. Ad] Listed I Iourl v Val lie

Environmental Protection Agency

Page 382 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

Usage:

1

Response

The AdjustedHourlyValue reported in the DHV record for [param] is invalid. The value
must be between 0 and 100.

You reported an MODCCode of 40 in the DHV record for [param], but the
AdjustedHourlyValue is not equal to the active default value in your monitoring plan.
You reported an MODCCode of 40 in the DHV record for [param], but the
AdjustedHourlyValue is outside the range of the active default values in your
monitoring plan.

The AdjustedHourlyValue reported in the DHV record for [param] is invalid. The value
must be greater than 0.

Process/Category:	Emissions Data Evaluation Report	H20 Derived Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	S02R Derived Hourly Evaluation

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 383 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV - 34

Check Name:

Determine Derived Hourly Record Status

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

If (Current DHV Parameter == "NOXR")

Current NOX System Status = Derived Hourly System Status
Current NOXR HBHA Value = Current DHVHBHA Value
else if (Current DHV Parameter == "C02C")

Current C02C DHV HBHA Value = Current DHV HBHA Value
else if (Current DHV Parameter == "H20")

Current H20 DHV HBHA Value = Current DHV HBHA Value

If (Derived Hourly Mode Status == false OR Derived Hourly Equation Status == false OR Derived Hourly Missing Data Status == false
OR (Current DHV Record. MOI )CCodc in set {06, 07, 08, 09, 10, 11) AND Derived Hourly Pma Status == false))

Case (Current DHV Parameter)

C02C:	C02C Derived Hourly Status = false

H20:	H20 Derived Hourly Status = false

S02R:	S02R Derived Hourly Status = false

S02M:	S02M Derived Hourly Status = false

NOXM:	NOXM Derived Hourly Status = false

C02M:	C02M Derived Hourly Status = false

HIT:	HIT Derived Hourly Status = false

S02:	S02 Derived Hourly Status = false

NOXR:	NOXR Derived Hourly Status = false

NOX:	NOX Derived Hourly Status = false

C02:	CO2 Derived Hourly Status false

HI:	HI Derived Hourly Status = fal se

Results:

Result

Response

Severity

Environmental Protection Agency

Page 384 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:

2	Process/Category:

3	Process/Category:

4	Process/Category:

5	Process/Category:

6	Process/Category:

7	Process/Category:

8	Process/Category:

Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report

C02 Concentration Derived Hourly Evaluation
C02 Mass Rate Derived Hourly Evaluation
H20 Derived Hourly Evaluation
Heat Input Derived Hourly Evaluation
NOx Emissions Rate Derived Hourly Evaluation
NOx Mass Rate Derived Hourly Evaluation
S02 Derived Hourly Evaluation
S02R Derived Hourly Evaluation

Environmental Protection Agency

Page 385 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-36

Check Name:

NOx Rate DHV Extraneous Fields Check

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Hourly Extraneous Fields = null

if (Current DHV Method o "AE" OR (Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count for Oil > 0 AND App E Constant
Fuel Mix == false)

if (Current DHV Record. SegmentNumber is not null)

append "SegmentNumber" to Hourly Extraneous Fields

if (Current DHV Record. OperatingConditionCode is not null)

if (Current DHV Method o "LME")

if (Current DHV Record.^ uelCode is not null)

append "FuelCode" to Hourly Extraneous Fields

if (Hourly Extraneous Fields is not null),
return result A

append "OperatingConditionCode" to Hourly Extraneous Fields

Results:

Result
A

Response

You reported [fieldnames] in the DHV record for [param]. This data should be blank.

Severity

Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Evaluation Report	NOx Emissions Rate Derived Hourly Evaluation

Environmental Protection Agency

Page 386 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-37

Check Name:	Calculate Heat Input for LME Unit

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

HIT Calculated Adjusted Value = null

If (Derived Hourly Mode Status == true)

if (LME HI Method is equal to "MHHI" OR Current DHV Record.MODCCode = "45")

Locate all Monitor Default records for the hour and location where the ParameterCode is equal to "MHHI".

If (one record is found, AND Monitor Default. DefaultValue is greater than 0, AND Monitor
De/awfeDefaultUnitsOfMeasureCode is equal to "MMBTUHR")

If (Current Hourly Op ifecortf. OpTime is greater than 0 and less than or equal to 1)

Calculate HIT Calculated Adjusted Value = DefaultValue * Current Hourly Op Record.OpTime.
rounded to one decimal place.

else

return result A

else if (LME HI Method is equal to "LTFF")

If (LME CP Total Heat Input is greater than or equal to 0, AND LME Total Heat Input Array for the location is greater
than or equal to 0, AND Current Hourly Op ifecorrf.HourLoad is greater than or equal to 0, AND Current Hourly Op
Record.OpTime is greater than 0 and less than or equal to 1)

If (LME OS is equal to true, AND the Quarter of the Current Reporting Period is equal to 2)

If the Current Month is April,

If (LME April Load is greater than 0)

If (HourLoad is equal to 0)

Set HIT Calculated Adjusted Value = 0

else

Calculate HIT Calculated Adjusted Value = (LME CP April Heat Input *
Current Hourly Op RecardA IourLoad * Current Hourly Op Record. OpTime /
LME April Load) + (LME April Heat Input Array for the location * Current
Hourly Op RecardA IourLoad * Current Hourly Op Record.OpTime I LME
April Load Array for the location), and round the result to 1 decimal place.

else if (LME April Optime is greater than 0)

Calculate HIT Calculated Adjusted Value = (LME CP April Heat Input * Current
Hourly Op Record. OpTime I LME April Optime) + (LME April Heat Input Array for
the location * Current Hourly Op Record.OpTime I LME April OpTime Array for the
location), and round the result to 1 decimal place.

Otherwise,

If (LME Total Load is greater than 0)

If (HourLoad is equal to 0)

Set HIT Calculated Adjusted Value = 0

Environmental Protection Agency

Page 387 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Calculate HIT Calculated Adjusted Value = ((LME CP Total Heat Input -
LME CP April Heat Input) * Current Hourly Op Record.\ lour Load * Current
Hourly Op itecortf. OpTime I (LME Total Load - LME April Load)) + ({LME
Total Heat Input Array for the location - LME April Heat Input Array for the
location) 4 Current Hourly Op itecortf.HourLoad * Current Hourly Op
Record.OpTime I (LME Total Load Array for the location - LME April Load
Array for the location)), and round the result to 1 decimal place.

else if (LME Total Optime is greater than 0)

Calculate HIT Calculated Adjusted Value = ((LME CP Total Heat Input - LME CP
April Heat Input) * Current Hourly Op Record. OpTime I (LME Total Optime - LME
April Optime)) + ((LME Total Heat Input Array for the location - LME April Heat
Input Array for the location) 4 Current Hourly Op Record.OpTime I (LME Total
OpTime Array for the location - LME April OpTime Array for the location)), and round
the result to 1 decimal place.

If (LME Total Load is greater than 0)

If (HourLoad is equal to 0)

Set HIT Calculated Adjusted Value = 0

else

Calculate HIT Calculated Adjusted Value = (LME CP Total Heat Input * Current
Hourly Op ifecorrf.HourLoad * Current Hourly Op Record.OpTime I LME Total Load)
+ (LME Total Heat Input Array for the location * Current Hourly Op ifecorrf.HourLoad
* Current Hourly Op Record. OpTime I LME Total Load Array for the location), and
round the result to 1 decimal place.

else if (LME Total Optime is greater than 0)

Calculate HIT Calculated Adjusted Value = (LME CP Total Heat Input * Current Hourly Op
Record.OpTime I LME Total Optime) + (LME Total Heat Input Array for the location * Current
Hourly Op Record.OpTime I LME Total OpTime Array for the location), and round the result to
1 decimal place.

Otherwise,

Results:

Result
A

Response

You did not report a single, active, valid default record for MHHI in your monitoring
plan.

This check result is obsolete.

Severity

Critical Error Level 1

B

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	HIT Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 388 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-38

Check Name:	Check Reported Heat Input for LME Unit

Related Former Checks:

Applicability:	LME Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

If (Current DHV Record. AdiustedHour\yVa\ue is null or is less than 0)

Rpt Period HI Reported Accumulator Array for this location = -1
return result A

else if (Current DHV Record. A&)wste&Y{om\yValue is not rounded to one decimal place)

Rpt Period HI Reported Accumulator Array for this location = -1
return result C

else

if (Current Month is not April OR LME Annual == true)

if (Rpt Period HI Reported Accumulator Array for this location is not null)
if (Rpt Period HI Reported Accumulator Array >= 0)

Rpt Period HI Reported Accumulator Array for this location = Rpt Period HI Reported Accumulator
Array for this location + Current DHVRecord.AdjustedHourlyValue

else

Rpt Period HI Reported Accumulator Array for this location = Current DHV Record .AdjustedHourlyValue

If (HIT Calculated Adjusted Value is not null and Current DHV Record .AdjustedHourlyValue is not equal to HIT Calculated
Adjusted Value)

If (HIT Calculated Adjusted Value is greater than 1 OR Current 1)11]' /feewY/.Adjustedl Iourlv Value is greater than 1)

Heat Input Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "HIT" AND
UOM = "MMBTU"

if (ABS(Current DHV Record. AdjustedHourly Value - HIT Calculated Adjusted Value) > Heat Input Tolerance)
return result B.

Results:

Result	Response	Severity

A	The AdjustedHourlyValue reported in the DHV record for [param] is invalid. The value	Critical Error Level 1

must be greater than or equal to 0.

B	The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with	Critical Error Level 1

the recalculated value.

C	You reported [fieldname] in the [type] record for [param] that is not rounded to the	Critical Error Level 1

appropriate precision for that parameter.

Environmental Protection Agency

Page 389 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	HIT Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 390 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-39

Check Name:	Calculate S02 Mass for LME Unit

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

S02M Calculated Adjusted Value = null

If Current DHVRecordsuelCode is null,

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1
return result A.

Otherwise,

Locate MonitorDefault record for the hour and location where ParameterCd = "S02R", DefaultPurposeCd = "LM", and FuelCode is
equal to Current DHVitecortf.FuelCode.

If not found, or if more than one record is found, or if DefaultValue is less than or equal to 0, or DefaultValueUnitsOfMeasure is not
equal to "LBMMBTU".

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1
return result B.

Otherwise,

S02R Default Value = MonitorDefault.DefaultValue

Locate MonitorDefault record for the hour and location where ParameterCd = "S02R", DefaultPurposeCd = "LM",
FuelCode is in LME Fuel Code List, FuelCode is not equal to Current DHVitecortf.FuelCode, Default Value is greater
than SO2R Default Value, and DefaultValueUnitsOfMeasure is equal to "LBMMBTU".

If found,

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1
return result C.

Otherwise,

If HIT Calculated Adjusted Value is null,

Rpt Period S02 Mass Calculated Accumulator Array for this location = -1
return result D.

else

Calculate S02M Calculated Adjusted Value =HIT Calculated Adjusted Value 4 SO2R Default Value,
and round the result to one decimal place.

if (Rpt Period S02 Mass Calculated Accumulator Array for this location is not null)

if (Rpt Period S02 Mass Calculated Accumulator Array for this location >= 0)

Rpt Period S02 Mass Calculated Accumulator Array for this location = Rpt Period S02
Mass Calculated Accumulator Array for this location + S02M Calculated Adjusted
Value

else

Rpt Period S02 Mass Calculated Accumulator Array for this location = S02 Mass Calculated
Adjusted Value

Environmental Protection Agency

Page 391 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

D

Usage:
1

Response

The AdjustedHourlyValue in the DHV record for [param] could not be recalculated,
because you did not report a FuelCode in this record.

You have not reported one and only one active Monitor Default record with a valid
ParameterCode and DefaultPurposeCode in your monitoring plan to report the default
emission rate for the fuel. The AdjustedHourlyValue in the DHV for [param] could not
be recalculated.

You reported [Fuel] as the FuelCode in the DHV record for [param], but, according to
the Monitor Default records in your monitoring plan, this fuel does not have the highest
default emissions rate of the fuels combusted during the hour. The
AdjustedHourlyValue could not be recalculated.

The AdjustedHourlyValue in the DHV record for [param] could not be recalculated
because the heat input rate could not be determined for the hour.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Informational Message

Process/Category:

Emissions Data Evaluation Report	S02M Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 392 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-40

Check Name:	Determine Fuels Burned for LME Unit

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

LME Fuel Code List = null

If (HIT Calculated Adjusted Value is not null)

Locate all DerivedHourly Value records for the location and hour where ParameterCode in set {S02M, C02M, NOXM}

For each record found,

Append DerivedHourly Value FuelCode to LME Fuel Code List.

if (Current Month is not April OR LME Annual == true)

if (Rpt Period HI Calculated Accumulator Array for this location is not null)

if (Rpt Period HI Calculated Accumulator Array for this location >= 0)

Rpt Period HI Calculated Accumulator Array for this location = Rpt Period HI Calculated Accumulator
Array for this location + HIT Calculated Adjusted Value

else

Rpt Period HI Calculated Accumulator Array for this location = HIT Calculated Adjusted Value

if (Current Month is April)

if (April HI Calculated Accumulator Array for this location is not null)

April HI Calculated Accumulator Array for this location = April HI Calculated Accumulator Array for
this location + HIT Calculated Adjusted Value

else

April HI Calculated Accumulator Array for this location = HIT Calculated Adjusted Value

else

if (Current Month is not April OR LME Annual == true)

Rpt Period HI Calculated Accumulator Array for this location = -1

return result A

Results:

Result	Response	Severity

A	The AdjustedHourlyValue in the DHV record for HIT could not be recalculated due to	Informational Message

another error listed in this report.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	HIT Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 393 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-41

Check Name:	Check Reported S02M for LME Unit

Related Former Checks:

Applicability:	LME Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

If (Current DHV Record. AdiustedHour\yVa\ue is null or is less than 0)

Rpt Period S02 Mass Reported Accumulator Array for this location = -1
return result A

else if (Current DHV Record. A&)wste&Y{om\yValue is not rounded to one decimal place)

Rpt Period S02 Reported Accumulator Array for this location = -1
return result C

else

if (Rpt Period S02 Mass Reported Accumulator Array for this location is not null)
if (Rpt Period S02 Mass Reported Accumulator Array >= 0)

Rpt Period S02 Mass Reported Accumulator Array for this location = Rpt Period S02 Mass Reported
Accumulator Array for this location + Current 1)11]' /feewY/.Adjustedl Iourlv Value

else

Rpt Period S02 Mass Reported Accumulator Array for this location = Current DHV Record. A d j ustedHourly Value

If (S02M Calculated Adjusted Value is not null AND Current DHVitecortf.AdjustedHourly Value is not equal to S02M
Calculated Adjusted Value)

SO2Mass Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "S02M" AND
UOM = "LB"

if (ABS(Current DHV Record. Adj ustedHourly Value - S02M Calculated Adjusted Value) > SO2 Mass Tolerance)
return result B

Results:

Result
A

B

C

Response

The AdjustedHourlyValue reported in the DHV record for [param] is invalid. The value
must be greater than or equal to 0.

The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with
the recalculated value.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	S02M Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 394 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-42

Check Name:	Calculate C02 Mass for LME Unit

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

C02M Calculated Adjusted Value = null

If Current DHVRecordsuelCode is null,

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1
return result A.

Otherwise,

Locate MonitorDefault record for the hour and location where ParameterCd = "C02R", DefaultPurposeCd = "LM", and FuelCode is
equal to Current DHVitecortf.FuelCode.

If not found, or if more than one record is found, or if DefaultValue is less than or equal to 0, or DefaultValueUnitsOfMeasure is not
equal to "TNMMBTU".

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1
return result B.

Otherwise,

C02R Default Value = MonitorDefault.DefaultValue

Locate MonitorDefault record for the hour and location where ParameterCd = "C02R", DefaultPurposeCd = "LM",
FuelCode is in LME Fuel Code List, FuelCode is not equal to Current DHVitecortf.FuelCode, Default Value is greater
than C02RDefault Value, and DefaultValueUnitsOfMeasure is equal to "TNMMBTU".

If found,

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1
return result C.

Otherwise,

If HIT Calculated Adjusted Value is null,

Rpt Period C02 Mass Calculated Accumulator Array for this location = -1
return result D.

else

Calculate C02M Calculated Adjusted Value =HIT Calculated Adjusted Value 4 CO2R Default Value,
and round the result to one decimal place.

if (Rpt Period C02 Mass Calculated Accumulator Array for this location is not null)

if (Rpt Period C02 Mass Calculated Accumulator Array for this location >= 0)

Rpt Period C02 Mass Calculated Accumulator Array for this location = Rpt Period C02
Mass Calculated Accumulator Array for this location + C02M Calculated Adjusted
Value

else

Rpt Period C02 Mass Calculated Accumulator Array for this location = C02 Mass Calculated
Adjusted Value

Environmental Protection Agency

Page 395 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

D

Usage:
1

Response

The AdjustedHourlyValue in the DHV record for [param] could not be recalculated,
because you did not report a FuelCode in this record.

You have not reported one and only one active Monitor Default record with a valid
ParameterCode and DefaultPurposeCode in your monitoring plan to report the default
emission rate for the fuel. The AdjustedHourlyValue in the DHV for [param] could not
be recalculated.

You reported [Fuel] as the FuelCode in the DHV record for [param], but, according to
the Monitor Default records in your monitoring plan, this fuel does not have the highest
default emissions rate of the fuels combusted during the hour. The
AdjustedHourlyValue could not be recalculated.

The AdjustedHourlyValue in the DHV record for [param] could not be recalculated
because the heat input rate could not be determined for the hour.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Informational Message

Process/Category:

Emissions Data Evaluation Report	C02M Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 396 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-43

Check Name:	Check Reported C02M for LME Unit

Related Former Checks:

Applicability:	LME Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

If (Current DHV Record. AdiustedHour\yVa\ue is null or is less than 0)

Rpt Period C02 Mass Reported Accumulator Array for this location = -1
return result A

else if (Current DHV Record. Ad)ustedY{om\yValue is not rounded to one decimal place)

Rpt Period C02 Reported Accumulator Array for this location = -1
return result C

else

if (Rpt Period C02 Mass Reported Accumulator Array for this location is not null)
if (Rpt Period C02 Mass Reported Accumulator Array >= 0)

Rpt Period C02 Mass Reported Accumulator Array for this location = Rpt Period C02 Mass Reported
Accumulator Array for this location + Current 1)11]' /feewY/.Adjustedl Iourlv Value

else

Rpt Period C02 Mass Reported Accumulator Array for this location = Current DHVRecord .Adj ustedHourly Value

If (C02M Calculated Adjusted Value is not null AND Current Dill' Record. Ad] Listed [ Iourl v Val Lie is not equal to C02M
Calculated Adjusted Value)

CO2Mass Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "C02M" AND
UOM = "TON"

if (ABS(Current DHV Record. Adj ustedHourly Value - C02M Calculated Adjusted Value) > CO2 Mass Tolerance)
return result B

Results:

Result
A

B

C

Usage:

1

Response

The AdjustedHourlyValue reported in the DHV record for [param] is invalid. The value
must be greater than or equal to 0.

The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with
the recalculated value.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	C02M Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 397 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURDHV-44

Check Name:

Calculate NOX Mass for LME Unit

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

NOXM Calculated Adjusted Value = null
UDEFStatus = null.

UDEFExpirationDate = null.

If Current DHVRecordsuelCode is null,

if (Current Month is not April OR LME Annual == true)

Rpt Period NOx Mass Calculated Accumulator Array for this location = -1

return result A

Default Condition - null

If Current DHV Record.OpemtingConditionCode is null,

Default Condition = "A"

else if Current DHV Record.OpemtingConditionCode in set {C, U, P, B}

Default Condition = Current DHV Record.OpemtingConditionCode

If Default Condition is null,

if {Current Month is not April OR LME Annual == true)

Rpt Period NOx Mass Calculated Accumulator Array for this location = -1

return result B

if (Current DHV Record.OpemtingConditionCode is equal to "U")

Locate MonitorDefault record for the hour and location where ParameterCd = "NORX", DefaultPurposeCd =
"MD", OperatingConditionCode is equal to Default Condition, and FuelCode is equal to Current DHV
RecordA ue\Code.

Locate MonitorDefault record for the hour and location where ParameterCd = "NOXR", DefaultPurposeCd =
"LM", OperatingConditionCode is equal to Default Condition, and FuelCode is equal to Current DHV
RecordA ue\Code.

If not found, or if more than one record is found, or if DefaultValue is less than or equal to 0, or
DefaultValueUnitsOfMeasure is not equal to "LBMMBTU".

if (Current Month is not April OR LME Annual == true)

Rpt Period NOx Mass Calculated Accumulator Array for this location = -1

Otherwise,

NOXR Default Value = MonitorDefault.DefaultValue

if (Default Condition is in set {A,C,B,P} AND MonitorDefault.DefaultSourceCode == "TEST")

Otherwise,

else

else

return result C

if (MonitorDefault.GroupID is null)

Environmental Protection Agency

Page 398 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (Default Condition — "A" or "C")

Locate the latest UnitDefaultTestRecordsByLocationForQAStatus for the location where
FuelCode = Current DHVifecortf.FuelCode and EndDate/EndHour is on or before the
Current OperatingDate/Hour.

else if (Default Condition == "B")

Locate the latest UnitDefaultTestRecordsByLocationForQAStatus for the location where
FuelCode = Current DHVifecortf.FuelCode, OperatingConditionCode == "A" or "B",
and EndDate/EndHour is on or before the CurrentOperatingDate/Hour.

else if (Default Condition == "P")

Locate the latest UnitDefaultTestRecordsByLocationForQAStatus for the location where
FuelCode = Current DHVRecord.VueiCode, OperatingConditionCode == "A" or "P",
and EndDate/EndHour is on or before the CurrentOperatingDate/Hour.

If not found,

UDEFStatus = "MISSING"

else

UDEFStatus = "FOUND"

Set UDEFExpiration Date to 5 years after the end of the quarter of the
UnitDefauItTestRecordsByLocationForQAStatus.EndDate.

Otherwise,

UDEFStatus = "GROUP"

Set UDEFExpiration Date to 5 years after the end of the quarter of the
Monitor Default. I icgi n I )atc.

if (Current DHV Record. OperatingConditionCode is equal to "U")

Locate MonitorDefault record for the hour and location where ParameterCd = "NORX",

DefaultPurposeCd = "MD", OperatingConditionCode is equal to Default Condition, FuelCode is in LME
Fuel Code List, FuelCode is not equal to Current DHVifecorrf.FuelCode, Default Value is greater than
NOXR Default Value, and DefaultValueUnitsOfMeasure is equal to "LBMMBTU".

else

Locate MonitorDefault record for the hour and location where ParameterCd = "NOXR",

DefaultPurposeCd = "LM", OperatingConditionCode is equal to Default Condition, FuelCode is in LME
Fuel Code List, FuelCode is not equal to Current DHVifecorrf.FuelCode, Default Value is greater than
NOXR Default Value, and DefaultValueUnitsOfMeasure is equal to "LBMMBTU".

If found,

if (Current Month is not April OR LME Annual == true)

Rpt Period NOx Mass Calculated Accumulator Array for this location = -1

return result D

Otherwise,

If HIT Calculated Adjusted Value is null,

if (Current Month is not April OR LME Annual == true)

Rpt Period NOx Mass Calculated Accumulator Array for this location = -1

return result E

Environmental Protection Agency

Page 399 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Calculate NOXM Calculated Adjusted Value =HIT Calculated Adjusted Value 4 NOXR Default
Value, and round the result to one decimal place.

if (Current Month is not April OR LME Annual == true)

if (Rpt Period NOx Mass Calculated Accumulator Array for this location is not null)

if {Rpt Period NOx Mass Calculated Accumulator Array for this location >= 0)

Rpt Period NOx Mass Calculated Accumulator Array for this location =
Rpt Period NOx Mass Calculated Accumulator Array for this location +
NOXM Calculated Adjusted Value

else

Rpt Period NOx Mass Calculated Accumulator Array for this location = NOx
Mass Calculated Adjusted Value

Results:

Result
A

B

C

D

Usage:
1

if (Current Month is April)

if (April NOx Mass Calculated Accumulator Array for this location is not null)

April NOx Mass Calculated Accumulator Array for this location = April
NOx Mass Calculated Accumulator Array for this location + NOXM
Calculated Adjusted Value

else

April NOx Mass Calculated Accumulator Array for this location =
NOXM Calculated Adjusted Value

Response

The AdjustedHourlyValue in the DHV record for [param] could not be recalculated,
because you did not report a FuelCode in this record.

You reported an invalid OperatingConditionCode in the DHV record for [param]. The
AdjustedHourlyValue could not be recalculated.

You have not reported one and only one active Monitor Default record with a valid
ParameterCode, DefaultPurposeCode, and OperatingConditionCode in your monitoring
plan to report the default emission rate for the fuel. The AdjustedHourlyValue in the
DHV for [param] could not be recalculated.

You reported [Fuel] as the FuelCode in the DHV record for [param], but, according to
the Monitor Default records in your monitoring plan, this fuel does not have the highest
default emissions rate of the fuels combusted during the hour. The
AdjustedHourlyValue could not be recalculated.

The AdjustedHourlyValue in the DHV record for [param] could not be recalculated
because the heat input rate could not be determined for the hour.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Informational Message

Process/Category:

Emissions Data Evaluation Report	NOXM Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 400 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-45

Check Name:	Check Reported NOXM for LME Unit

Related Former Checks:

Applicability:	LME Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

If (Current DHV Record. AdiustedHour\yVa\ue is null or is less than 0)

Rpt Period NOx Mass Reported Accumulator Array for this location = -1
return result A

else if (Current DHV Record. A&)wste&Y{om\yValue is not rounded to one decimal place)

Rpt Period NOx Mass Reported Accumulator Array for this location = -1
return result C

else

if (Current Month is not April OR LME Annual == true)

if (Rpt Period NOx Mass Reported Accumulator Array for this location is not null)
if (Rpt Period NOx Mass Reported Accumulator Array >= 0)

Rpt Period NOx Mass Reported Accumulator Array for this location = Rpt Period NOx Mass Reported
Accumulator Array for this location + Current DHVRecord.AdjustedHourly Value

else

Rpt Period NOx Mass Reported Accumulator Array for this location = Current DHV
Record. Adj ustedHourly Value

If (NOXM Calculated Adjusted Value is not null AND Current DHV Record. Adj ustedHourlyValue is not equal to NOXM
Calculated Adjusted Value)

NOX Mass Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "NOXM" AND
UOM = "LB"

if (ABS(CMrren?Z)//Fifecorrf.AdjustedHourlyValue - NOXM Calculated Adjusted Value) > NOX Mass Tolerance)
return result B

Results:

Result
A

B

C

Response

The AdjustedHourlyValue reported in the DHV record for [param] is invalid. The value
must be greater than or equal to 0.

The AdjustedHourlyValue reported in the DHV record for [param] is inconsistent with
the recalculated value.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	NOXM Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 401 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURDHV-46

Check Name:	Equation Code Consistent with Moisture Basis

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	S02M Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 402 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks
Applicability:

Description:

Specifications:

If UDEF Status is not null,

If {UDEF Status == "MISSING")
return result A.

else if {UDEFStatus == "FOUND")

if (Current Operating Date is after the UDEF Expiration Date)
return result B.

else

Append CurrentDII 1 .1 Lie IC ode to the LME Fuel Array for the location.

else if (UDEFStatus == "GROUP")

if (Current Operating Date is after the UDEF Expiration Date)
return result C.

HOURDHV-47

Unit Default Test Expiration Check
LME Check

Results:

Result

A

B

Response

You did not report an applicable prior LME Unit Default Test for Fuel Code [FUEL],
The applicable prior LME Unit Default Test for Fuel Code [FUEL] has expired. You
need to use a Part 75 default NOx emissions rate until you perform a new
unit-and-fuel-specific default test. You will need to put an end date on your existing
NOXR default records in your monitoring plan, and add a new NOXR default record
based on the Part 75 default value.

Warning: Based on the BeginDate in your NOXR Default record in your monitoring
plan, the LME Unit Default Test(s) that established the default NOx emission rate for
Fuel Code [FUEL] may have expired. Unit Default Tests must be performed every five
years. If your test has expired, you need to use a Part 75 default NOx emissions rate
until you perform a new unit-and-fuel-specific default test. You will need to put an end
date on your existing NOXR default records in your monitoring plan, and add a new
NOXR default record based on the Part 75 default value.

Severity

Critical Error Level 1
Critical Error Level 1

Informational Message

Usage:
1

Process/Category:

Emissions Data Evaluation Report	NOXM Derived Hourly Evaluation (LME)

Environmental Protection Agency

Page 403 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Hourly General

Environmental Protection Agency

Page 404 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-1

Check Name:

Initialize Accumulators for Summary Value Data

Related Former Checks: HOUROP-27

Applicability:

General Check

Description:

Specifications:

For each location in Monitoring Plan, initialize arrays with size Current Location Count
Rpt Period C02 Mass Reported Accumulator Array for the location = 0
Rpt Period C02 Mass Calculated Accumulator Array for the location = 0
Expected Summary Value C02 Array for the location = false

Rpt Period HI Reported Accumulator Array for the location =0
Rpt Period HI Calculated Accumulator Array for the location = 0
Expected Summary Value HI Array for the location = false

Rpt Period NOx Rate Reported Accumulator Array for the location = 0
Rpt Period NOx Rate Calculated Accumulator Array for the location = 0
Rpt Period NOx Rate Hours Accumulator Array for the location = 0
Expected Summary Value NOx Array for the location = false

Rpt Period S02 Mass Reported Accumulator Array for the location = 0
Rpt Period S02 Mass Calculated Accumulator Array for the location = 0
Expected Summary Value S02 Array for the location = false

Rpt Period NOx Mass Reported Accumulator Array for the location = 0
Rpt Period NOx Mass Calculated Accumulator Array for the location = 0
Expected Summary Value NOx Mass Array for the location = false

Rpt Period Op Time Accumulator Array for the location = 0
Rpt Period Op Hours Accumulator Array for the location = 0
Rpt Period Op Days Accumulator Array for the location = 0
Rpt Period Load Accumulator Array for the location = 0

Daily Op Time Accumulator Array for this location = 0

April HI Calculated Accumulator Array for the location = 0
April NOx Mass Calculated Accumulator Array for the location = 0
April Op Time Accumulator Array for the location = 0
April Op Hours Accumulator Array for the location = 0
April Op Days Accumulator Array for the location = 0

LME Total Load Array for the location = 0
LME April Load Array for the location = 0
LME Total Heat Input Array for the location = 0
LME April Heat Input Array for the location = 0
LME Total OpTime Array for the location = 0
LME April OpTime Array for the location = 0

Last Day of Operation Array for the location = null
First Day of Operation = null
First Hour of Operation = null

FLOW System ID Array for the location = null
NOXE System ID Array for the location = null
LME Fuel Array for the location = null

Environmental Protection Agency

Page 405 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Count the number of unique location + FuelCode in the Hourly Fuel Flow records for the monitoring configuration and reporting period.
Initialize an array with this number of elements:

Fuel Op Hours Accumulator Array for the location and FuelCode = 0

Initialize F2LStalusSystemResultDictionary as a dictionary with both a string key and lookup value
Initialize F2LStatusSystemCheckDictionary as a dictionary with a string key and a data row value
Initialize F2LStalusSystemMissingOpDictionary as a dictionary with both a string key and lookup value

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 406 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-2

Check Name:

Reporting Period Details

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Abort Hourly Checks = false
Legacy Data Evaluation = false
LME HI Method = null
LME HI Substitute Data Code = null
Annual Reporting Requirement = false
OS Reporting Requirement = false
LME Annual = false
LME OS = false

Reported Emissions Value = null
Multiple Stack Configuration = false
Ignored Daily Calibration Tests = false
Ignored Daily Interference Tests = false

if ((Current Reporting Period < Current Monitoring Plan itecortf.BeginReportPeriod) OR

{Current Monitoring Plan itecortf.EndReportPeriod is not null AND Current Monitoring Plan ifecortf.EndReportPeriod <
Current Reporting Period))

Abort Hourly Checks = true
return result A

else

Locate a UnitProgram record for any unit in the configuration where ProgramCode in set {NBP, CAIROS, NHNOX, SIPNOX},
UnitMonitorCertBeginDate is on or before the December 31 of the year of the Current Reporting Period, and the EndDate is null or
is on or after Jan 1 of the year of the Current Reporting Period

OS Reporting Requirement = true

Locate all LocationReportingFrequency record for any unit in the configuration where BeginQuarter is on or before the Current

Reporting Period, and the EndQuarter is null or is on or after the Current Reporting Period.

If found, and the ReportingFrequencyCode in all records == "Q",

Annual Reporting Requirement = true

else if found, and the ReportingFrequencyCode in all records == "OS",

If OS Reporting Requirement == false
Abort Hourly Checks = true
return result B

else if the Quarter of the Current Reporting Period is equal to 1 or 4,

Abort Hourly Checks = true
return result C

Otherwise,

Abort Hourly Checks = true
return result B

If (Abort Hourly Checks == false)

If (the associated First ECMPS Reporting Period for the monitoring plan is null)

If Current Reporting Period is on or prior to 2008)

If found,

Environmental Protection Agency

Page 407 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Legacy Data Evaluation = true

Else

If Current Reporting Period is prior to the First ECMPS Reporting Period)

Legacy Data Evaluation = true

Locate a Hourly Op Data record for the configuration and reporting period where OperatingTime is greater than 0,

If found,

Reporting Period Operating = true

else,

Reporting Period Operating = false

Locate MonitorMethod record for ANY location in the file where ParameterCode in set {S02M, NOXM, C02M}, MethodCode =
"LME"

BeginDate is on or before the first day of the Current Reporting Period, and the EndDate is null or is on or after the last day of the
Current Reporting Period.

If found,

Locate all MonitorQualification records for all units in the monitoring configuration where the QualificationTypeCode is
equal to "LMEA" or "LMES", BeginDate is on or before the last day of the reporting period, and the EndDate is null or is
on or after December 31 of the year prior to the Current Reporting Period.

If a record with QualificationTypeCode equal to "LMEA" is found,
set LME Annual to true.

If a record with QualificationTypeCode equal to "LMES" is found,
set LME OS to true.

If {LME Annual == true and Annual Reporting Requirement == false)

Abort Hourly Checks = true
return result D

else if (LME OS == true and OS Reporting Requirement == false)

Abort Hourly Checks = true
return result E

else if {LME Annual == false and LME OS == false)

Abort Hourly Checks = true
return result F

Otherwise,

Locate MonitorMethod records for all locations in the file where ParameterCode = "HIT", BeginDate is on or
before the first day of the Current Reporting Period, and the EndDate is null or is on or after the last day of the
Current Reporting Period.

If not found for any location,

Abort Hourly Checks = true
return result G

If MethodCode = "MffiH" for all locations,

LME HI Method = "MffiH"

If MethodCode in set {LTFF, CALC, LTFCALC} for all locations,

LME HI Method = "LTFF "

If SubstituteDataCode is equal to "MHHI" for any location,

LME HI Substitute Data Code = "MHHI".

Environmental Protection Agency

Page 408 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Otherwise,

Abort Hourly Checks = true
return result H

If (Abort Hourly Checks == false)

Locate all Unit Program records for all units in the configuration where the UnitMonitorCertBeginDate is on or prior to the Current
Reporting Period and the EndDate is null or is on or after the Current Reporting Period.

If the ProgramCode in all the retrieved Location Program records are only equal to "NBP", "OTC", "NHNOX", or "SIPNOX",

Locate all Unit Operating Status records for all units in the configuration where the Op Status Code is equal to "RET", the
year of the Begin Date is prior to Current Reporting Period, and the End Date is null or is on or after the last day of the
Current Reporting Period.

If found,

return result I

Otherwise,

For each Unit Program record retrieved above where the ProgramCode is not equal to "NBP", "OTC", "NHNOX", or
"SIPNOX",

If Program Code is equal to "CAIROS" and the Current Reporting Period is in the first or second quarter,

Locate a Unit Program Exemption record for the unit program where the Exempt Type is equal to "RUE",
the Exemption Begin Date is on or prior to May 1 of the year of the Current Reporting Period, and the
Exemption End Date is null or is on or after the last day of the Current Reporting Period.

Otherwise,

Locate a Unit Program Exemption record for the unit program where the Exempt Type is equal to "RUE",
the Exemption Begin Date is on or prior to the first day of the Current Reporting Period, and the
Exemption End Date is null or is on or after the last day of the Current Reporting Period.

If a Unit Program Exemption record was found for all unit programs,
return result I

Environmental Protection Agency

Page 409 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

D

G
H
I

Usage:
1

Response

The locations in the file do not represent a valid monitoring configuration during the
reporting period. The file will not be evaluated.

The active Reporting Frequency records for this configuration are missing or invalid.
The file will not be evaluated. Please contact ECMPS technical support for assistance
with this matter.

According to the Reporting Frequency records, this monitoring configuration is an
ozone-season-only reporter, however the reporting period is not within the ozone season.
The file will not be evaluated.

You have reported an LME Annual Qualification record in your monitoring plan, but,
according to the Reporting Frequency records, this configuration is not an annual
reporter. The file will not be evaluated.

You have reported an LME Ozone Season Qualification record in your monitoring plan,
but, according to the Unit Program records, this configuration does not report ozone
season totals. The file will not be evaluated.

You have reported an LME method in your monitoring plan for one or more units in this
configuration, but you have not reported an LME qualification record. The file will not
be evaluated.

You did not report an active heat input method for one or more locations in the file. The
file will not be evaluated.

The active heat input methods reported for the locations in the file are inconsistent. The
file will not be evaluated.

This file contains at least one unit that is retired. Please contact EPA if you believe that
all units in this configuration should report emissions data during this reporting period.

Severity
Fatal

Fatal

Fatal

Fatal

Fatal

Fatal

Fatal
Fatal

Critical Error Level 2

Process/Category:

Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 410 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Check Code:	HOURGEN-3

Check Name:	Calculate Total Load for LME Configuration for Reporting Period

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

LME Total Load = 0
LME April Load = 0
LME CP Total Heat Input = 0
LME CP April Heat Input = 0
LME Total Optime = 0
LME April Optime = 0

If {LME HI Method is not null)

If {LME HI Method == "MHHI")

Locate an LTFF record for any location in the monitoring configuration during the reporting period.

If found,

set Abort Hourly Checks to true, and return result A.

else

For each Hourly Op Data record for every unit in the monitoring configuration.

If Hourly Op Data OpTime is not equal to 0 or Hourly Op Data HourLoad is not null,

If Hourly Op Data HourLoad is greater than or equal to 0 and Hourly Op Data OpTime is between 0 and
1 (inclusive),

Locate the DerivedHourly Value record for the unit and the hour where ParameterCode is equal to
"HIT".

If found, AND DerivedHourlyValue. MODCCode is null,

Add HourLoad * OpTime to LME Total Load Array for the location
Add HourLoad * OpTime to LME Total Load.

Add OpTime to LME Total OpTime Array for the location
Add OpTime to LME Total Optime.

If the month of Hourly Op Data. Date is "April" AND LME OS is equal to true ,
Add HourLoad * OpTime to LME April Load Array for the location
Add HourLoad * OpTime to LME April Load.

Add OpTime to LME April OpTime Array for the location
Add OpTime to LME April Optime.

If not found, AND Hourly Op Data HourLoad is greater than 0,
set LME Total Load to -1.
exit for.

Otherwise,

set LME Total Load to -1.
exit for.

If LME OS is equal to true and the reporting period is the second quarter,

Locate an LTFF record for any location in the monitoring configuration during the reporting period where the
FuelFlowPeriodCode is equal to "A".

Environmental Protection Agency

Page 411 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If found, AND LME April Load is equal to 0 and LME April Optime is equal to 0,
set Abort Hourly Checks to true, and return result C.

else if not found AND {LME April Load is greater than 0 or LME April Optime is greater than 1),
return result F.

else

Locate an LTFF record for any location in the monitoring configuration during the reporting period where
the FuelFlowPeriodCode is equal to "MJ".

If found,

If {LME Total Load - LME April Load) is equal to 0 and {LME Total Optime - LME April
Optime) is equal to 0,

set Abort Hourly Checks to true, and return result E.

else

If {LME Total Load - LME April Load) is greater than 0 or {LME Total Optime - LME April
Optime) is greater than 1,
return result G.

Locate an LTFF record for any location in the monitoring configuration during the reporting period.
If found,

If LME Total Load is equal to 0 and LME Total Optime is equal to 0,
set Abort Hourly Checks to true, and return result B.

else

If LME Total Load is greater than 0 or LME Total Optime is greater than 1,
return result D.

else

Results:

Result
A

Response

You have reported MHHI as the heat input method for this configuration, but you have
reported a long-term fuel flow record.

You have reported a long-term fuel flow record for this reporting period, but the sum of
the load and operating time values in the hourly records (where MHHIIndicator is not
equal to 1) are equal to 0.

You have reported a long-term fuel flow record for April, but the sum of the load and
operating time values in the hourly records (where MHHIIndicator is not equal to 1) are
equal to 0.

You have reported LTFF as the heat input method for this configuration, but you have
not reported a long-term fuel flow record for this reporting period.

You have reported a long-term fuel flow record for May and June, but the sum of the
load and operating time values in the hourly records (where MHHIIndicator is not equal
to 1) are equal to 0.

You have reported LTFF as the heat input method for this ozone-season reporting
configuration, but you have not reported a long-term fuel flow record for April.
You have reported LTFF as the heat input method for this ozone-season reporting
configuration, but you have not reported a long-term fuel flow record for May/June.

Severity
Fatal

B

Fatal

C

Fatal

D

Critical Error Level 1

E

Fatal

F

Critical Error Level 1

G

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 412 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURGEN-7

Check Name:	Validate LME Eligibility

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

If (LME HI Method is not null)

Set LME Exceeding Parameter to null.

Set Final LME Year to false.

For each unit in the monitoring configuration:

If {LME Annual == true)

Locate the latest MonitorQualification record where location is the unit being evaluated, the
QualificationTypeCode is equal to "LMEA", BeginDate is on or before the first day of the Current Reporting
Period, and the EndDate is null or is on or after December 31 of the year prior to the Current Reporting Period.

If (not found)

return result A.

If (found and the BeginDate of the retrieved qualification record is prior to the Current Reporting Period Year)

For each year from three years prior to the Current Reporting Period Year until the year prior to the
Current Reporting Year.

Set Annual NOx to 0.

Set Annual SO 2 to 0.

For quarter 1 until quarter 4:

Locate an Op Supp Data record for the location and quarter/year being checked where the
OpTypeCode = "NOXM".

If (found)

add OpValue to Annual NOx.

Locate an Op Supp Data record for the location and quarter/year being checked where the
OpTypeCode = "S02M".

If (found)

add OpValue to Annual S02.

If (the year being evaluated is the year prior to the Current Reporting Period Year)

If (Annual NOx is greater than 100 or Annual S02 is greater than 25)
set Final LME Year to true.

Else

If (Annual NOx is greater than 100)

append "Annual NOx" to LME Exceeding Parameter.

If (Annual S02 is greater than 25)

append "Annual S02" to LME Exceeding Parameter.

Environmental Protection Agency

Page 413 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (LME OS == true)

Locate the latest MonitorQualification record where the location is the unit being evaluated,
QualificationTypeCode is equal to "LMES", BeginDate is on or before the later of the first day of the Current
Reporting Period and May 1 of the year of the Current Reporting Period, and the EndDate is null or is on or after
December 31 of the year prior to the Current Reporting Period.

If (not found)

return result B.

If (found and the BeginDate of the retrieved qualification record is prior to the Current Reporting Period Year)

For each year from three years prior to the Current Reporting Period Year until the year prior to the
Current Reporting Period Year.

Set OS NOx to 0.

Locate an Op Supp Data record for the location and quarter 2 of the year being checked where the
OpTypeCode = "NOXMOS".

If found,

add OpValue to OS NOx.

Locate an Op Supp Data record for the location and quarter 3 of the year being checked where the
OpTypeCode = "NOXM".

If found,

add OpValue to OS NOx.

If (the year being evaluated is the year prior to the Current Reporting Period Year)

If (OS NOx is greater than 50)

set Final LME Year to true.

Else

If (OS NOx is greater than 50)

append "Ozone Season NOx" to LME Exceeding Parameter.

if (LME Exceeding Parameter is not null)
return result C.

else if (Final LME Year == true)
return result D.

Results:

Result
A

Response

You have reported an active LMEA qualification record for this configuration in your
monitoring plan, but you have not reported an active LMEA qualification record for at
least one unit in the configuration.

You have reported an active LMES qualification record for this configuration in your
monitoring plan, but you have not reported an active LMES qualification record for at
least one unit in the configuration.

You have reported that this configuration has an active LME qualification, but this
configuration is no longer eligible to qualify for an LME methodology, because at least
one unit in the configuration has exceeded the eligibility limit for [param] in a prior
year.

The emissions from at least one unit in this configuration exceeded the applicable
number of tons necessary to qualify as an LME unit in the previous reporting year.
According to Part 75.19(b), you must install the appropriate monitoring systems by
December 31 of this reporting year.

Severity
Fatal

B

Fatal

C

Critical Error Level 2

D

Informational Message

Environmental Protection Agency

Page 414 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 415 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-8

Check Name:

Monitor Plan Evaluation Check

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Set MpSuccessfullyEvaluated = false.

If the SeverityLevelCd ofthe monitoring plan record for this configuration is equal to "CRIT1" or "FATAL",
return result A.

Otherwise,

If the NeedsEvalFlag and MustSubmitFlag of the monitoring plan record for this configuration are equal to " Y",

return result B.

Otherwise,

Set MpSuccessfully Evaluated = true.

Results:

Result
A

Response

The Monitoring Plan associated with this quarterly emissions file has critical errors.
You must correct the Monitoring Plan for this monitoring configuration in order to
submit this emissions file to be loaded on EPA's host system.

The Monitoring Plan associated with this quarterly emissions file has not been
evaluated. You must evaluate the Monitoring Plan for this monitoring configuration in
order to complete the evaluation of this emissions file.

Severity

Critical Error Level 1

B

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 416 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURGEN-9

Check Name:	QA/Cert Test Evaluation Check

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

Locate any QA/Cert Test record for the monitoring configuration where the EndDate is on or before the last day of the Current Reporting
Period, MustSubmitFlag is equal to 'Y' or CanSubmitFlag and UpdatedStatusFlag are equal to "Y", and the SeverityCd is equal to "CRIT1"
or "FATAL".

If found,

return result A.

Otherwise,

Locate any QA/Cert Test record for the monitoring configuration where the EndDate is on or before the last day of the Current
Reporting Period, MustSubmitFlag is equal to 'Y' or CanSubmitFlag and UpdatedStatusFlag are equal to "Y", and the
NeedsEvalFlag are equal to "Y".

If found,

return result B.

Otherwise,

Locate any QA Supp Data record for the monitoring configuration without any associated Test Summary record where the
EndDate is on or before the last day of the Current Reporting Period and MustSubmitFlag is equal to 'Y'.

If found,

return result C.

Results:

Result

B

Response

At least one QA/certification test associated with this monitoring configuration has
critical errors. You must correct all prior or concurrent QA/certification tests in order to
submit this quarterly emissions file to be loaded on EPA's host system.

At least one QA/certifi cation test associated with this monitoring configuration has not
been evaluated. You must evaluate all prior or concurrent QA/certification tests in order
to complete the evaluation of this quarterly emissions file.

The emissions quarterly reported cannot be submitted, because EPA has required the
resubmission of a QA/certification test that is not present in the Client Tool. Please
review the Submission Access report for more information about what needs to be
submitted.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 417 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-10

Check Name:

QA/Cert Event Evaluation Check

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Locate any QA/Certification Event record for the monitoring configuration where the QACertEventDate is on or before the last day of the
Current Reporting Period, the MustSubmitFlag is equal to "Y", and the SeverityCd is equal to "CRIT1" or "FATAL".

If found,

return result A.

Otherwise,

Locate any QA/Certification Event record for the monitoring configuration where the QACertEventDate is on or before the last day
of the Current Reporting Period and the MustSubmitFlag and NeedsEvalFlag are equal to "Y".

If found,

return result B.

Results:

Result
A

Response

At least one QA/certification event associated with this monitoring configuration has
critical errors. You must correct all prior or concurrent QA/certification events in order
to submit this quarterly emissions file to be loaded on EPA's host system.

At least one QA/certifi cation event associated with this monitoring configuration has not
been evaluated. You must evaluate all prior or concurrent QA/certification event in
order to complete the evaluation of this quarterly emissions file.

Severity

Critical Error Level 1

B

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 418 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-11

Check Name:

Test Extension/Exemption Evaluation Check

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Locate any Test Extension/Exemption record for the monitoring configuration where the ReportingPeriod is on or before the Current
Reporting Period, the MustSubmitFlag is equal to "Y", and the SeverityCd is equal to "CRIT1" or "FATAL".

If found,

return result A.

Otherwise,

Locate any Test Extension/Exemption record for the monitoring configuration where the ReportingPeriod is on or before the
Current Reporting Period and the MustSubmitFlag and NeedsEvalFlag are equal to "Y".

If found,

return result B.

Results:

Result
A

At least one test extension/exemption associated with this monitoring configuration has
critical errors. You must correct all prior or concurrent test extension/exemption records
in order to submit this quarterly emissions file to be loaded on EPA's host system.

Response

Severity

Critical Error Level 1

B

At least one test extension/exemption associated with this monitoring configuration has
not been evaluated. You must evaluate all prior or concurrent test extension/exemption
records in order to complete the evaluation of this quarterly emissions file.

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 419 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURGEN-12

Check Name:	Prior Emissions File Evaluation Check

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

Locate any Emissions File for any location in the current monitoring configuration where the ReportingPeriod is prior to the Current
Reporting Period, and either the Submission Availability Code = 'CRITERR' or (CANSUBMIT = 'Y' and SeverityCd is equal to "CRIT1"
or "FATAL").

If found,

return result A.

Otherwise,

Locate any Emissions File for any location in the current monitoring configuration where CAN SUBMIT = 'Y', the ReportingPeriod
is prior to the Current Reporting Period, and the NeedsEvalFlag is equal to "Y".

If found,

return result B.

If not found,

Locate any Emissions File for any location in the current monitoring configuration where the ReportingPeriod is prior to the
Current Reporting Period, and either the Submission Availability Code = 'NOTSUB' or (CAN SUBMIT = 'Y' and
UpdatedStatusFlag = 'NODATA').

If found,

return result C.

Results:

Result

B

Response

At least one prior quarterly emissions file for at least one location in this monitoring
configuration has critical errors. You must correct all prior quarterly emissions files in
order to submit this quarterly emissions file to be loaded on EPA's host system.

At least one prior quarterly emissions file for at least one location in this monitoring
configuration has not been evaluated. You must evaluate all prior quarterly emissions
files in order to complete the evaluation for this quarterly emissions file.

At least one prior quarterly emissions file for at least one location in this monitoring
configuration has not been submitted and has been authorized for resubmission. You
must submit all prior quarterly emissions files in order to submit this quarterly emissions
file to be loaded on EPA's host system.

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 420 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURGEN-13

Check Name:	Determine If File Can Be Submitted

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

Locate the Emission Submission Access record for the configuration and reporting period.

If not found, or the Submission Availability Code is null,
return result A.

else if the Submission Availability Code is not equal to "GRANTED" or "REQUIRE",
return result B.

Severity

Informational Message

Informational Message
Usage:

1	Process/Category:	Emissions Data Evaluation Report Summary Value Initialization

Results:

Result	Response

A	The emissions quarterly report cannot be submitted, either because the EPA has not yet

opened the submission window, you have not logged into the EPA host system, or you
are no longer a representative or agent for this facility. If you are a representative or
agent for this facility, when EPA opens the submission window you should log in to the
EPA host system to receive automatic permission to submit. You will then need to
reevaluate this file prior to submitting.

B	The emissions quarterly report cannot be resubmitted until you contact the EPA for

permission. After the EPA grants permission, you will need to log in to the EPA host
system to retrieve the permission record. You will then need to reevaluate this file prior
to submitting.

Environmental Protection Agency

Page 421 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-14

Check Name:

Ignored Offline Daily Calibration Check

Related Former Checks:

Applicability:

Description:

Specifications:

If (Ignored Daily Calibration Tests == true)

set Ignored Daily Calibration Tests to false
return result A.

Results:

Result	Response	Severity

A	You reported one or more daily calibration tests that will not fulfill your daily	Informational Message

calibration testing requirement, because these tests were performed while the unit was
not operating and you have not reported a prior online-offline calibration demonstration.
These tests have been assigned a CalculatedTestResult of "IGNORED", and they can be
viewed on the Daily Calibration tab of the View Detailed Emissions Screen. If you
intend to use offline tests to fulfill your daily calibration testing requirement, you must
conduct an online-offline calibration demonstration.

Usage:
1

Process/Category:	Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 422 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-15

Check Name:

Expiring Test Check

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Set Expired Systems and Expiring Systems to null.

Set Expiration Text to "have expired"

If FLOW System ID Array for the location is not null,

For each SystemID in the FLOW System ID Array for the location:

Locate the latest RATATestRecordsByLocationForQAStatus for the location where the SystemID is equal to the SystemID
being checked and the number of operating levels the OpLevelCodeList is equal to 3,

If found,

If RATATestRecordsByLocationForQAStatus.TestReasonCode equal to "INITIAL" then

Locate the latest QACertEventsForEMEvaluation where SystemID is equal to the SystemID being
checked and QACertEventCode equal to "305"

If QACertEventforEMEvaluation.TestCompletionDaXe is after the
RATATestRecordsByLocationForQAStatus.EndDate

Set ExpirationDate to five years after the end of the quarter of the
QACertEventforEMEvaluation. T estCompletionDate

Else

Set ExpirationDate to five years after the end of the quarter of the
RATATestRecordsByLocationForQAStatus. EndDate

Set ExpirationDate to five years after the end of the quarter of the
RATATestRecordsByLocationForQAStatus.EndDate.

If ExpirationDate is prior to the current calendar date,

Append the Systemldentifier being checked to Expired Systems.

else if ExpirationDate is on or before the last day of the Current Reporting Period,

Set Expiration Text to "will be expiring at the end of the reporting period".

Append the Systemldenitifier being checked to Expired Systems.

else if ExpirationDate is on or before the last day of the quarter following the Current Reporting Period,
Append the Systemldentifier being checked to Expiring Systems.

If both Expired Systems and Expiring Systems are not null,

return result A
else if Expired Systems is not null,

return result B
else if Expiring Systems is not null,
return result C

else if NOXE System ID Array for the location is not null,

For each SystemID in the NOXE System ID Array for the location:

Locate the XatestAppendixETestRecordsByLocationForQAStatus for the location where the SystemID is equal to the
SystemID being checked,

Else

Environmental Protection Agency

Page 423 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If found,

Set ExpirationDate to five years after the end of the quarter of the
AppendixETestRecordsByLocationForQAStatus. EndDate.

If ExpirationDate is prior to the current calendar date,

Append the Systemldentifier being checked to Expired Systems.

else if ExpirationDate is on or before the last day of the Current Reporting Period,

Set Expiration Text to "will be expiring at the end of the reporting period".

Append the Systemldentifier being checked to Expired Systems.

else if ExpirationDate is on or before the last day of the quarter following the Current Reporting Period,
Append the Systemldentifier being checked to Expiring Systems.

If both Expired Systems and Expiring Systems are not null,

return result D
else if Expired Systems is not null,

return result E
else if Expiring Systems is not null,
return result F

else if LME Fuel Array for the location is not null,

For each FuelCode in the LME Fuel Array for the location:

Locate the latest UnitDefauItTestRecordsByLocationForQAStatus for the location where the FuelCode is equal to the
FuelCode being checked,

If found,

Set ExpirationDate to five years after the end of the quarter of the
UnitDefaultTestRecordsByLocationForQAStatus. EndDate.

If ExpirationDate is prior to the current calendar date,

Append the FuelCode being checked to Expired Systems.

else if ExpirationDate is on or before the last day of the Current Reporting Period,

Set Expiration Text to "will be expiring at the end of the reporting period".

Append the FuelCode being checked to Expired Systems.

else if ExpirationDate is on or before the last day of the quarter following the Current Reporting Period,
Append the FuelCode being checked to Expiring Systems.

If both Expired Systems and Expiring Systems are not null,

return result G
else if Expired Systems is not null,

return result H
else if Expiring Systems is not null,
return result I

Environmental Protection Agency

Page 424 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B

D

G

H

Usage:
1

Response

Warning: The three-level RATA conducted for each of the following monitoring
systems [TEXT]: System ID(s) [EXPIRED], Except for a 720 operating-hour grace
period extension, you will need monitor stack flow with another FLOW system or report
substitute data until you perform another three-level RATA. In addition, the three-level
RATA conducted for each of the following monitoring systems will expire at the end of
the next reporting period: System ID(s) [EXPIRING], Three-level RATAs expire after
five years.

Warning: The three-level RATA conducted for each of the following monitoring
systems [TEXT]: System ID(s) [EXPIRED], Except for a 720 operating-hour grace
period extension, you will need monitor stack flow with another FLOW system or report
substitute data until you perform another three-level RATA. Three-level RATAs expire
after five years.

Prior Notice: The three-level RATA conducted for each of the following monitoring
systems will expire at the end of the next reporting period: System ID(s) [EXPIRING],
Three-level RATAs expire after five years.

Warning: The Appendix E test conducted to determine the NOx correlation curve for
each of the following monitoring systems [TEXT]: System ID(s) [EXPIRED], In
subsequent reporting periods, you will need report substitute data until you perform
another Appendix E test. In addition, the Appendix E test conducted for each of the
following monitoring systems will expire at the end of the next reporting period: System
ID(s) [EXPIRING], Appendix E tests expire after five years.

Warning: The Appendix E test conducted to determine the NOx correlation curve for
each of the following monitoring systems [TEXT]: System ID(s) [EXPIRED], In
subsequent reporting periods, you will need report substitute data until you perform
another Appendix E test. Appendix E tests expire after five years.

Prior Notice: The Appendix E test conducted to determine the NOx correlation curve
for each of the following monitoring systems will expire at the end of the next reporting
period: System ID(s) [EXPIRING], Appendix E tests expire after five years.

Warning: The LME Unit Default Test conducted to determine the default NOx emission
rate for each of the following fuels [TEXT]: Fuel Code(s) [EXPIRED], In subsequent
reporting periods, you will need report substitute data until you perform another Unit
Default Test. In addition, the Unit Default Test conducted for each of the following
fuels will expire at the end of the next reporting period: Fuel Code(s) [EXPIRING],
LME Unit Default Tests expire after five years.

Warning: The LME Unit Default Test conducted to determine the default NOx emission
rate for each of the following fuels [TEXT]: Fuel Code(s) [EXPIRED], In subsequent
reporting periods, you will need report substitute data until you perform another Unit
Default Test. LME Unit Default Tests expire after five years.

Prior Notice: The LME Unit Default Test conducted to determine the default NOx
emission rate for each of the following fuels will expire at the end of the next reporting
period: Fuel Code(s) [EXPIRING], LME Unit Default Tests expire after five years.

Severity

Informational Message

Informational Message

Informational Message
Informational Message

Informational Message

Informational Message
Informational Message

Informational Message

Informational Message

Process/Category:

Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 425 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-16

Check Name:

Ignored Offline Daily Interference Check

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (Ignored Daily Interference Tests == true)
return result A.

Results:

Result	Response	Severity

A	You reported one or more daily interference checks that will not fulfill your daily testing	Informational Message

requirement for your stack flow monitors, because these tests were performed while the
unit was not operating. These tests have been assigned a CalculatedTestResult of
"IGNORED". They can be viewed on the Other Daily Tests tab of the View Detailed
Emissions Screen.

Usage:
1

Process/Category:	Emissions Data Evaluation Report Summary Value Evaluation

Environmental Protection Agency

Page 426 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURGEN-17

Check Name:	Missing Peaking or Gas Fired Qualification Percent Check

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

If Mp Successfully Evaluated equals true,

Set Qualification Percent Missing List = null.

For each QualificationRecord record in MpQualificationRecords where QualificationTypeCode is equal to "PK", "SK" or "GF",
BeginDate is on or before Current Reporting Period End Hour, and EndDate is null or or is on or after Current Reporting Period
Begin Hour:

Locate the record in MpQualificationPercentRecords where MonitorQualificationld is equal to
QualificationRecord.MonitorQualificationld, and QualificationDataYear is equal to CurrentReportingPeriodYear.

If not found,

Add MpQualificationRecords.Location!d to Qualification Percent Missing List.

If Qualification Percent Missing List is not null,
return result A.

Results:

Result	Response	Severity

A	You did not report a current year peaking qualification percent record.	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 427 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-18

Check Name:

Validate Unit Fuel

Related Former Checks:

Applicability:

Description:

Specifications:

If Quarter of the Current Reporting Period is equal to 1,

For each unit in MonitoringPlanLocalionRecords

Locate all Facility Unit Fuel Records for the unit where Indicator Code is equal to "P"

If found,

Set Sum of Op Hours to 0

Locate all Facility Operating Supp Data Records for the unit where:

a)	The calendar year is the year prior to the calendar year of Current Reporting Period.

b)	Parameter Code is equal to "OPHOURS".

c)	Fuel Code is equal to NULL.

For each located record

Increament Sum of Op Hours by Facility Operating Supp Data Records. Op Value
If Sum of Op Hours >168

Set Sum of Op Hours by Fuel to null

Locate all Facility Operating Supp Data Records for the unit where:

a)	The calendar year is the year prior to the calendar year of Current Reporting Period.

b)	Parameter Code is equal to "OPHOURS".

c)	Fuel Code is NOT equal to NULL.

For each located record

Increament Sum of Op Hours by Fuel for Facility Operating Supp Data Records. FuelCode by
Facility Operating Supp Data Records.OpValue

For each FuelCode in Sum of Op Hours by Fuel

If (Sum of Op Hours by Fuel I Sum of Op Hours is greater than or equal to 0.60)

For each located Facility Unit Fuel Records record

If Facility Unit Fuel itecorafc.FuelCode is not equal to the FuelCode for Sum of

Op Hours by Fuel

return A

Environmental Protection Agency

Page 428 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result	Response	Severity

A	The current active primary fuel type defined in the monitoring plan is inconsistent with	Informational Message

the prior year operating hours by fuel type. Please update the primary fuel type in the
monitoring plan to match the prior year predominant fuel type by operating hours.

Usage:

1	Process/Category:	Emissions Data Evaluation Report Summary Value Initialization

Environmental Protection Agency

Page 429 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-4

Check Name:

Emission Comment Reporting Period Valid

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

For a Emission Comment record:

If ReportingPeriod is null,
return result A.

Results:

Result	Response	Severity

A	You did not provide [fieldname], which is required for [key].	Fatal

Usage:
1

Process/Category:	Emissions Data Entry Screen Evaluation Emission Comments Evaluation

Environmental Protection Agency

Page 430 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURGEN-5

Check Name:

Submission Comment Valid

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

For the Emission Comment record:

If SubmissionComment is null,
return result A.

Results:

Result	Response	Severity

A	You did not provide [fieldname], which is required for [key].	Fatal

Usage:
1

Process/Category:	Emissions Data Entry Screen Evaluation Emission Comments Evaluation

Environmental Protection Agency

Page 431 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURGEN-6

Check Name:	Duplicate Emission Comment Records

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

For a Emission Comment record:

Locate another EmissionComment record for the monitoring plan with a ReportingPeriod equal to the ReportingPeriod in the current
record.

If found,

return result A.

Results:

Result	Response	Severity

A	Another [recordtype] record already exists with the same [fieldnames].	Fatal

Usage:

1	Process/Category:	Emissions Data Entry Screen Evaluation Emission Comments Evaluation

Environmental Protection Agency

Page 432 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Hourly Monitor Data

Environmental Protection Agency

Page 433 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMHV-1

Check Name:

Initialize S02C Hourly Monitor Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHV Parameter = "S02C"

S02C Calculated Adjusted Value = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 434 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMHV-2

Check Name:

Initialize H20 Hourly Monitor Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHV Parameter = "H20"

H20MHV Calculated Adjusted Value = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	H20 Monitor Hourly Evaluation

Environmental Protection Agency

Page 435 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMHV-3

Check Name:

Initialize NOXC Hourly Monitor Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHV Parameter = "NOXC"

NOXC Calculated Adjusted Value = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Environmental Protection Agency

Page 436 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMHV-4

Check Name:

Initialize Flow Hourly Monitor Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHV Parameter = "FLOW"

FLOW Calculated Adjusted Value = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Environmental Protection Agency

Page 437 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMHV-5

Check Name:

Initialize C02C Hourly Monitor Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHV Parameter = "C02C"

C02C MHV Calculated Adjusted Value = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

Environmental Protection Agency

Page 43 8 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMHV-6

Check Name:

Initialize 02 Dry Hourly Monitor Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHV Parameter = "02D"

02 Dry Calculated Adjusted Value = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

Environmental Protection Agency

Page 439 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMHV-7

Check Name:

Initialize 02 Wet Hourly Monitor Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHV Parameter = "02W"

02 Wet Calculated Adjusted Value = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

Environmental Protection Agency

Page 440 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-8

Check Name:	Check MODC in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Monitor Hourly Mode Status = false

Current MHV Parameter Description = Current MHV Parameter
Complete MHV Record Needed = true

case (Current MHV Parameter)

S02C: Current MHV Record = Current S02 Monitor Hourly Record
Current MHV Component Type = 'S02'

Current MHV System Type = 'S02'

Current MHV Default Parameter = 'S02X'

If (Current MHV RecordModcCode == "23")

If (S02 Bypass Code == "BYMAXFS")

Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

else if (SO2 Fuel Specific Missing Data == true)
Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

If (Current MHV Record ModcCode not in set {01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 12, 13, 15, 16, 17, 18, 19, 20, 21,
22,23,53,54,55})

return result A

Else

Monitor Hourly Mode Status = true

NOXC: Current MHV Record = Current NOx Cone Monitor Hourly Record
Current MHV System Type = 'NOXC'

Current MHV Component Type = 'NOX'

Current MHV Default Parameter = 'NOCX'

NOx Cone MODC = null

If (Current MHV RecordModcCode in set {23, 24})

If (NOx Mass Bypass Code == "BYMAXFS")

Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false
else if (NOx Mass Fuel Specific Missing Data == true)
Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

If (NOx Cone Needed for Nox Mass Calc == true)

If (Current MHV Record ModcCode not in set {01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 11, 12, 13, 15, 17, 18, 19,
20,21,22, 23,24, 53, 54, 55})
return result A

Else

Environmental Protection Agency

Page 441 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Monitor Hourly Mode Status = true

Else

Complete MHVRecord Needed = false

If {Current MHV Record ModcCode not in set {01, 02, 03, 04, 17, 18, 19, 20, 21, 22, 53, 54})
return result B

Else

Monitor Hourly Mode Status = true

NOx Cone MODC = Current MHV Record. ModcCode

FLOW: Current MHV Record = Current Stack Flow Hourly Record
Current MHV Component Type = 'FLOW'

Current MHV System Type = 'FLOW'

Current MHV Default Parameter = 'FLOX'

If (S02 Fuel Specific Missing Data == true OR CO2 Fuel Specific Missing Data == true OR NOx Mass Fuel Specific
Missing Data == true OR Heat Input Fuel Specific Missing Data == true)

Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

If {Current MHV Record ModcCode not in set {01,02, 03,04, 05,06, 07, 08,09, 10, 11, 12,20, 53, 54, 55})
return result A

Else

Monitor Hourly Mode Status = true

C02C: Current MHV Record = Current C02 Cone Monitor Hourly Record
Current MHV Component Type = 'C02'

Current MHV System Type = 'C02'

Current MHV Default Parameter = 'C02X'

If ((C02 Fuel Specific Missing Data == true AND CO 2 Cone Checks Needed for C02 Mass Calc == true) OR {Heat
Input Fuel Specific Missing Data == true AND CO2 Cone Checks Neededfor Heat Input == true))

Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

If (C02 Cone Checks Neededfor Heat Input == true OR C02 Cone Checks Needed for C02 Mass Calc == true)

If {Current MHV Record ModcCode not in set {01, 02, 03, 04, 06, 07, 08, 09, 10, 12, 17, 18, 20, 21, 53, 54, 55})
return result A

Else

Monitor Hourly Mode Status = true

If (C02 Diluent Checks Neededfor NOx Rate Calc == true AND Current MHV Record ModcCode not
in set {01, 02, 03, 04, 17, 20,21, 53, 54}
return result E

Else

Complete MHV Record Needed = false

If Current MHV Record ModcCode not in set {01, 02, 03, 04, 17, 18, 20, 21, 53, 54}
return result C

Else

Monitor Hourly Mode Status = true

02D: Current MHV Record = Current 02 Dry Monitor Hourly Record
Current MHV Component Type = '02'

Current MHV System Type = null
Current MHV Default Parameter = '02N'

If {Current MHV Record. MoistureBasis is null)

Current MHV Parameter Description = "02C"

Environmental Protection Agency

Page 442 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Current MHVParameter Description = "02C with a MoistureBasis of" + Current MHVifecortf.MoistureBasis

If (Heat Input Fuel Specific Missing Data == true AND 02 Dry Checks Needed for Heat Input == true)

Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

If (02 Dry Checks Needed for Heat Input == true)

If {Current MHV Record ModcCode not in set {01, 02, 03, 04, 06, 07, 08, 09, 10, 12, 17, 20, 53, 54, 55})
return result A

Else

Monitor Hourly Mode Status = true

If <02 Dry Checks Needed for NOx Rate Calc == true AND Current MHV Record ModcCode not in set

{01,02, 03,04, 17,20,53,54}
return result E

Else

Complete MHV Record Needed = false

If Current MHV Record ModcCode not in set {01, 02, 03, 04, 17, 20, 53, 54}
return result D

Else

Monitor Hourly Mode Status = true

02W: Current MHV Record = Current 02 Wet Monitor Hourly Record
Current MHV Component Type = '02'

Current MHV System Type = null
Current MHV Default Parameter = '02N'

If (Current MHV Record. MoistureBasis is null)

Current MHV Parameter Description = "02C"

else

Current MHV Parameter Description = "02C with a MoistureBasis of" + Current MHV ifecortf.MoistureBasis

If (Heat Input Fuel Specific Missing Data == true AND 02 Wet Checks Needed for Heat Input == true)

Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

If (02 Wet Checks Needed for Heat Input == true)

If (Current MHV Record ModcCode not in set {01, 02, 03, 04, 06, 07, 08, 09, 10, 12, 17, 20, 53, 54, 55})
return result A

Else

Monitor Hourly Mode Status = true

If (02 Wet Checks Needed for NOx Rate Calc == true AND Current MHV Record ModcCode not in set

{01,02, 03,04, 17,20,53,54}
return result E

Else

Complete MHV Record Needed = false

If Current MHV Record ModcCode not in set {01, 02, 03, 04, 17, 20, 53, 54}
return result D

Else

Monitor Hourly Mode Status = true

H20: Current MHV Record = Current H20 Monitor Hourly Record
Current MHV Parameter = 'H20'

If (H20 Method Code == "MMS")

Environmental Protection Agency

Page 443 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Current MHV Component Type = "H20"

else

Current MHV Component Type = "DAHS"

Current MHV System Type = null
Current MHV Default Parameter = null'

If (H20 Fuel Specific Missing Data == true)

Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

If {Current MHVRecordModcCode not in set {01, 02, 03, 04, 06, 07, 08, 09, 10, 12,21, 53, 54, 55})
return result A

else

Monitor Hourly Mode Status = true

C02CSD:

Current MHV Record = Current C02 Cone Missing Data Monitor Hourly Record

Current MHV Component Type = 'C02'

Current MHV System Type = null

Current MHV Default Parameter = 'C02X'

Current MHV Parameter Description = "C02C (Substitute Data)"

If ((C02 Fuel Specific Missing Data == true AND CO 2 Cone Checks Needed for C02 Mass Calc == true) OR (Heat
Input Fuel Specific Missing Data == true AND CO2 Cone Checks Neededfor Heat Input == true))

Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

If (Current MHV RecordModcCode not in set {06, 07, 08, 09, 10, 12, 55})
return result A

Else

Monitor Hourly Mode Status = true

02CSD:

if (Current 02 Dry Missing Data Monitor Hourly Record is not null)

Current MHV Record = Current 02 Dry Missing Data Monitor Hourly Record

else

Current MHV Record = Current 02 Wet Missing Data Monitor Hourly Record

Current MHV Component Type = '02'

Current MHV System Type = null

Current MHV Default Parameter = '02N'

Current MHV Parameter Description = "02C (Substitute Data)"

If (Heat Input Fuel Specific Missing Data == true AND 02 Dry Checks Needed for Heat Input == true)

Current MHV Fuel Specific Hour = true

else

Current MHV Fuel Specific Hour = false

If (Current MHV RecordModcCode not in set {06, 07, 08, 09, 10, 12, 55})
return result A

Else

Monitor Hourly Mode Status = true

Environmental Protection Agency

Page 444 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

A

B

D

Usage:

1

2

3

4

5

6

7

Response

The MODCCode reported in the MHV record for [param] is invalid.

You reported a MODCCode of [MODC] in the MHV record for NOXC, but this MODC
is not appropriate when NOX concentration is used in a NOx-diluent system to calculate
the NOx emission rate.

You reported a MODCCode of [MODC] in the MHV record for C02C, but this MODC
is not appropriate when C02 concentration is only used to calculate the NOx emission
rate.

You reported a MODCCode of [MODC] in the MHV record for [param], but this
MODC is not appropriate when 02 concentration is not used to calculate the heat input
rate.

You reported a MODCCode of [MODC] in the MHV record for [param], but this
MODC is not appropriate when this value is used in a NOx-diluent system to calculate
the NOx emission rate.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	LOO Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 445 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-9

Check Name:	Check Percent Monitor Availability in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Monitor Hourly Pma Status = false
Monitor Hourly Missing Data Status = true

If (Monitor Hourly Mode Status == true)

If ( Current Mil I' Record. I 'crccn t A vai I alii c is NULL)
if (Complete MHV Record Needed == false)

Monitor Hourly Pma Status = true

else

if {Current MHVRecordModcCode not in set {01, 02, 03, 04, 16, 17, 18, 19, 20, 21, 22, 53, 54} AND Legacy
Data Evaluation == true)

Monitor Hourly Pma Status = true
return result A

else

return result B

else

if (Complete MHV Record Needed == false)
return result C

else if {Current MHVi?ecortf.PercentAvailable> 100.0 OR

Current MHV Record. PercentAvailable < 0.0)
return result D

Else

case { Current MHV RecordModcCode )

= 06:

If Current MffFTfecortf.PercentAvailable >= 90.0
Monitor Hourly Pma Status = true

Else

return result E

= 08:

If Current MHVRecord.PercentAvai\ab\e >= 95.0
Monitor Hourly Pma Status = true

Else

return result E

= 09:

If Current MHVitecortf.PercentAvailable >= 90.0 AND Current MHVifecortf.PercentAvailable < 95.0
Monitor Hourly Pma Status = true

Else

return result E

= 10:

If Current MHVitecortf.PercentAvailable >=80.0 AND Current MHVifecortf.PercentAvailable < 90.0

Monitor Hourly Pma Status = true
Else if Current MHV Parameter in {FLOW,NOXC} and Current MHV Record. PercentAvailable >=
90.0

Monitor Hourly Pma Status = true
return result F

Else

return result E

Environmental Protection Agency

Page 446 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

= 11:

If Current Mill' /fecYWY/.PcrccntA vailablc >=90.0
Monitor Hourly Pma Status = true

Else

return result E

All other MODC Codes:

Monitor Hourly Pma Status = true

Results:

Result

B
C

D

E
F

Usage:

1

2

3

4

5

6

7

Severity

Informational Message

Critical Error Level 1
Non-Critical Error

Critical Error Level 1
Critical Error Level 1
Informational Message

Response

You reported an MODCCode of [ModcCode] in the MHV record for [param], but you

did not report a value for PercentAvailable. While this is not required for legacy EDR

data, it is required in all MHV records for ECMPS.

You did not report PercentAvailable in the MHV record for [param].

You reported PercentAvailable in the MHV record for [param], but this value should not

be reported when the monitoring system is only being used to calculate the NOX

emission rate, moisture, and/or C02 concentration. In that case, the percent monitor

availability should be reported in the appropriate DHV record.

The PercentAvailable reported in the MHV record for [param] is invalid. This value

must be between 0 and 100.

You reported an MODCCode of [modcCode] in the MHV record for [param], but the
PercentAvailable is not appropriate for this MODC.

You reported an MODCCode of 10 in the [type] record for [param], but the
PercentAvailability is greater than or equal to 90. When the PMA is greater than or
equal to 90, you should only report an MODC of 10 to indicate that you used the
maximum hourly value in the lookback period for the next available higher load bin,
because there were no quality-assured data in the bin corresponding to the current load
range. (See Part 75.33(c)(5).)

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	LOO Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 447 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMH V -10

Check Name:

Check Prior QA'd Hours for MODC 07

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

if (Monitor Hourly Mode Status == true AND Monitor Hourly PMA Status == true)
if (Current MHV Record. ModcCode == 07)

if (Current MHV Parameter in set {02D, 02W, 02CSD})

Prior QA Hours = count MonitorHourlyValueData records where

MonitorHourlyValueData.ModcCode in set {01, 02, 04, 17, 20, 53} AND
MonitorHourlyValueData.ParameterCode = "02C" AND

(MonitorHourlyValueData.MoistureBasis = Current Mil]' /feeewY/. Moisture Basis OR
MonitorHourlyValueData.MoistureBasis is null) AND
(MonitorHourly ValueData.BeginDate < Current Date OR
(MonitorHourlyValueData.BeginDate = Current Date AND MonitorHourlyValueData.BeginHour <
Current Hour))

else if (Current MHV Parameter == "C02CSD")

Prior QA Hours = count MonitorHourlyValueData records where

MonitorHourlyValueData.ModcCode in set {01, 02, 04, 17, 20, 21, 53} AND
MonitorHourlyValueData.ParameterCode = "C02C" AND
(MonitorHourly ValueData.BeginDate < Current Date OR
(MonitorHourlyValueData.BeginDate = Current Date AND MonitorHourlyValueData.BeginHour <
Current Hour))

S02C:	MODC Set = {01,02,04,16,17,19,20,21,22,53}

NOXC:	MODC Set = {01,02,04, 17, 19,20,21,22,53}

C02C:	MODC Set = {01,02,04, 17,20,21,53}

FLOW:	MODC Set = {01, 02, 04, 20, 53}

H20:	MODC Set = {01, 02, 04, 21, 53}

Prior QA Hours = count MonitorHourlyValueData records where

MonitorHourly ValueData.ModcCode in set MODC Set AND

MonitorHourly ValueData.ParameterCode = Current MHVifecorrf.ParameterCode AND
(MonitorHourly ValueData.BeginDate < Current Date OR
(MonitorHourlyValueData.BeginDate = Current Date AND MonitorHourlyValueData.BeginHour <
Current Hour))

if (Current MHV Parameter in set {NOXC, FLOW})
if (Prior QA Hours > 2160)

else

case (Current MHV Parameter)

Monitor Hourly Missing Data Status = false
return result A

else

if (Prior QA Hours > 720)

Monitor Hourly Missing Data Status = false
return result A

Results:

Result
A

Response

You reported an MODCCode of 07 in the MHV record for [param], but too many prior
quality assured hours exist in evaluation period for use of this missing data approach.

Severity

Critical Error Level 1

Environmental Protection Agency

Page 448 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:

2	Process/Category:

3	Process/Category:

4	Process/Category:

5	Process/Category:

6	Process/Category:

7	Process/Category:

8	Process/Category:

9	Process/Category:

Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report

C02 Concentration Monitor Hourly Evaluation

C02C Monitor Hourly Evaluation for Substitute Data

FLOW Monitor Hourly Evaluation

H20 Monitor Hourly Evaluation

NOx Concentration Monitor Hourly Evaluation

02 Dry Monitor Hourly Evaluation

02 Wet Monitor Hourly Evaluation

02C Monitor Hourly Evaluation for Substitute Data

S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 449 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

HOURMHV-11

Check Extraneous Data in MHV Record
CEM Check

Check Code:

Check Name:

Related Former Checks:

Applicability:

Description:

Specifications:

Monitor Hourly Null Status = false
Hourly Extraneous Fields = null

if (Current MHV ifecorrfAdjustedHourlyValue is not null AND Current MHV Parameter not in set {S02C, NOXC, FLOW})
append "AdjustedHourlyValue" to Hourly Extraneous Fields

if (Current MHV Record.MoistureBasis is not null AND Current MHV Parameter not in set {02D, 02W, 02CSD})
append "MoistureBasis" to Hourly Extraneous Fields

if (Hourly Extraneous Fields is not null)
return result A

else

Monitor Hourly Null Status = true

Results:

Result
A

Usage:

1

2

3

4

5

6

7

Response

You reported [fieldnames] in the MHV record for [param]. This data should be blank.

Severity

Non-Critical Error

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	LOO Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 450 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMH V -12

Check Name:

Check For Correct Use of MODCs

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHVHBHA Value = null

if (Monitor Hourly Mode Status == true AND Monitor Hourly PMA Status == true)

if (Current MHV Record.ModcCode in set {06, 08, 09})

if (Current MHV Parameter in set {02D, 02W, 02CSD})

Prior MHV Record = latest MonitorHourlyValueData record where

MonitorHourlyValueData.ModcCode in set {01, 02, 03, 04, 17, 20, 53, 54} AND
MonitorHourlyValueData.ParameterCode = "02C" AND

(MonitorHourlyValueData.MoistureBasis = Current MHV Record.MoistureBasis OR
MonitorHourlyValueData.MoistureBasis is null) AND
[MonitorHourlyValueData.Date < Current Date OR

(MonitorHourlyValueData.Date = Current Date AND MonitorHourlyValueData.Hour < Current Hour )]
If Prior MHV Record is not null and is in current reporting period

Next MHV Record = earliest MonitorHourlyValueData record where

MonitorHourlyValueData.ModcCode in set {01, 02, 03, 04, 17,20, 53, 54} AND
MonitorHourlyValueData.ParameterCode = "02C" AND

(MonitorHourlyValueData.MoistureBasis = Current MHV Record.MoistureBasis OR
MonitorHourlyValueData.MoistureBasis is null) AND
[MonitorHourlyValueData.Date > Current Date OR

(MonitorHourlyValueData.Date = Current Date AND MonitorHourlyValueData.Hour > Current
Hour)]

If Next MHV Record is not null and is in current reporting period

If Prior MHV .Recorof.UnadjustedHourlyValue >= 0 AND Next MHV
.Recorof.UnadjustedHourlyValue >= 0

Current MHV HBHA Value = (Pr/orM//F,Recoraf.UnadjustedHourlyValue + Next MHV
.Recoraf.UnadjustedHourlyValue) / 2, ROUNDED to a single decimal.

else

Monitor Hourly Missing Data Status = false
return result A

else

case (Current MHV Parameter)

S02C:

NOXC:

FLOW:

C02C OR C02CSD:
H20:

MODC Set = {01, 02, 03, 04, 16, 17, 19, 20,21,22, 53,54}
MODC Set = {01, 02, 03, 04, 17, 19,20,21,22, 53, 54}
MODC Set = {01, 02, 03, 04, 20, 53, 54}

MODC Set = {01,02,03,04, 17,20,21, 53, 54}

MODC Set = {01,02, 03, 04,21,53, 54}

if (Current MHV Parameter in set {H20, C02C})

Environmental Protection Agency

Page 451 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Prior Record = latest MonitorHourlyValueData record or DerivedHourly ValueData record where
ParameterCode = Current MHVParameter AND
ModcCode in set MODC Set AND
(Date < Current Date OR

(Date = Current Date AND Hour < Current Hour ))

If Prior Record is not null and is in current reporting period

Next Record = earliest MonitorHourlyValueData record or DerivedHourly ValueData record where
ParameterCode = Current MHV Parameter AND
ModcCode in set MODC Set AND
(Date > Current Date OR

(Date = Current Date AND Hour > Current Hour ))

If Next Record is not null and is in current reporting period

IfPr/or,Recoraf.UnadjustedHourlyValue >= 0 AND iVex/.Record. UnadjustedHourly Value

>=0

Current MHVHBHA Value = (7-Wor,Recor(iUnadjustedHourlyValue + Next
.Recorof.UnadjustedHourlyValue) / 2, ROUNDED to a single decimal.

else

Monitor Hourly Missing Data Status = false
return result A

else if (Current MHV Parameter == "C02CSD")

Prior MHV Record = latest MonitorHourlyValueData record where
MonitorHourlyValueData.ParameterCode = "C02C" AND
MonitorHourValueData.ModcCode in set MODC Set AND
[MonitorHourlyValueData.Date < Current Date OR

(MonitorHourlyValueData.Date = Current Date AND MonitorHourly ValueData.Hour < Current
Hour)]

If Prior MHV Record is not null and is in current reporting period

Next MHV Record = earliest MonitorHourlyValueData record where
MonitorHourlyValueData.ParameterCode = "C02C" AND
MonitorHourValueData.ModcCode in set MODC Set AND
[MonitorHourlyValueData.Date > Current Date OR

(MonitorHourlyValueData.Date = Current Date AND MonitorHourly ValueData.Hour > Current
Hour)]

If Next MHVRecord is not null and is in current reporting period

IfPr/orM//F,Recoraf.UnadjustedHourlyValue >= 0 AND AND Next MHV
.Recoraf.UnadjustedHourlyValue >= 0

Current MHVHBHA Value = (7-WorM//F,Recor(iUnadjustedHourlyValue +
Next MHV .Recoraf.UnadjustedHourlyValue) / 2, ROUNDED to a single decimal.

else

Monitor Hourly Missing Data Status = false
return result A

else

Prior MHV Record = latest MonitorHourlyValueData record where

MonitorHourly ValueData.ParameterCode = Current MHV Parameter AND

Environmental Protection Agency

Page 452 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

MonitorHourValueData.ModcCode in set MODC Set AND
[MonitorHourlyValueData.Date < Current Date OR

(MonitorHourlyValueData.Date = Current Date AND MonitorHourly ValueData.Hour < Current
Hour)]

If Prior MHV Record is not null and is in current reporting period

Next MHVRecord = earliest MonitorHourly ValueData record where

MonitorHourly ValueData.ParameterCode = Current MHV Parameter AND
MonitorHourValueData.ModcCode in set MODC Set AND
[MonitorHourlyValueData.Date > Current Date OR

(MonitorHourlyValueData.Date = Current Date AND MonitorHourly ValueData.Hour >
Current Hour)]

If Next MHVRecord is not null and is in current reporting period

If Prior MHV Record. Ad]ustedHour\yValue >= 0 AND Next MHV
.Recoraf.AdjustedHourlyValue >= 0

if (Current MHV Parameter == "FLOW")

Current MHVHBHA Value = (Prior MHV
.Recoraf.AdjustedHourlyValue + Next MHV
.Recoraf.AdjustedHourlyValue) / 2, ROUNDED to the nearest 1000.

else

Current MHV HBHA Value = (Prior MHV
.Recoraf.AdjustedHourlyValue + Next MHV
.Recoraf.AdjustedHourlyValue) / 2, ROUNDED to a single decimal.

else

Monitor Hourly Missing Data Status = false
return result B

else if (Current MHVRecordMo&cCo&e =="11")

case (Current MHV Parameter)

NOXC: MODC Set = {01,02,03,04,17,19,20,21,22,53,54}

FLOW: MODC Set = {01, 02, 03, 04, 20, 53, 54}

Prior Measured MHV Record = MonitorHourly ValueData record at latest time for the location where
MonitorHourly ValueData.ModcCode in set MODC Set AND
MonitorHourly ValueData.ParameterCode = Current MHV Parameter AND
(MonitorHourlyValueData.BeginDate < Current Date OR

(MonitorHourlyValueData.BeginDate = Current Date AND MonitorHourlyValueData.BeginHour< Current Hour)

)

If Prior Measured MHV Record is not null and is in the current reporting period
PriorDate = Prior Measured MHV Record. BeginDate
PriorHour = Prior Measured MHV Record. BeginHour

else

PriorDate = the day prior to the beginning of the current reporting period
PriorHour = 23

Next Measured MHV Record = MonitorHourly ValueData record at earliest time for the location where
MonitorHourly ValueData.ModcCode in set MODC Set AND
MonitorHourly ValueData.ParameterCode = Current MHV Parameter AND
(MonitorHourlyValueData.BeginDate > Current Date OR

Environmental Protection Agency

Page 453 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

(MonitorHourlyValueData.BeginDate = Current Date AND MonitorHourlyValueData.BeginHour > Current
Hour))

If Next MeasuredMHVRecord is not null and is in the current reporting period
NextDate = Next Measured MHV Record.BegmD&te
NextHour = Next Measured MHV RecordSegmRom

else

NextDate = the day after the end of the current reporting period
NextHour = 0

Missing Data Period Length = Count of MonitorHourlyValueData records for the location where
MonitorHourlyValueData.ParameterCode = Current MHV Parameter AND
(MonitorHourly ValueData.BeginDate > PriorDate OR

(MonitorHourly ValueData.BeginDate = PriorDate AND MonitorHourlyValueData.BeginHour >
PriorHour) ) AND

(MonitorHourly ValueData.BeginDate < NextDate OR

(MonitorHourly ValueData.BeginDate = NextDate AND MonitorHourlyValueData.BeginHour <

NextHour) )

if {Current MHVifecorrf PercentAvailable is null OR Current Mill' Record. PcrccntA vailablc >= 95.0)
if (Missing Data Period Length >24)

Monitor Hourly Missing Data Status = false
return result C

else

if (Missing Data Period Length > 8)

Monitor Hourly Missing Data Status = false
return result C

else if (Current MHVRecord.ModcCode == "17" AND Monitor Hourly System Status == true)

Hours of Use of Like Kind Analyzer = Count of MonitorHourlyValueData records for the location and reporting period
where

MonitorHourly ValueData.ParameterCode = Current MHV Parameter AND
MonitorHourlyValueData.ModcCode == "17" AND
(MonitorHourlyValueData.BeginDate < Current Date OR

(MonitorHourlyValueData.BeginDate = Current Date AND MonitorHourlyValueData.BeginHour< Current Hour)

)

If Hours of Use of Like Kind Analyzer >= 720

First Use of Like Kind Analyzer Record = MonitorHourlyValueData record at earliest time for the location and
and reporting period where

MonitorHourly ValueData.ParameterCode = Current MHV Parameter AND
MonitorHourlyValueData.ModcCode == "17" AND
(MonitorHourly ValueData.BeginDate < Current Date OR

(MonitorHourly ValueData.BeginDate = Current Date AND MonitorHourly ValueData.BeginHour<

Current Hour))

If Current MHFifecorrf.MonitoringSystemID is not null,

Locate a RATATestRecordsByLocationForQAStatus for the location

where the MonitoringSystemID is equal to Current MHVitecortf.MonitoringSystemID, the
TestResultCode begins with "PASS", and the EndDate/EndHour is after the First Use of Like Kind
Analyzer .Recorof.Date/Hour and on or prior to the Current Date/Current Hour.

If not found,

return result D

Environmental Protection Agency

Page 454 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Locate all Monitor System Component Records for Hour and Location

where the ComponentID is equal to Current MHVRecord.ComponentlD.

Locate a RATATestRecordsByLocationForQAStatus for the location

where the MonitoringSystemID is equal to any MonitoringSystemID in the retrieved Monitor
System Component records, the TestResultCode begins with "PASS", and the EndDate/EndHour
is after the First Use of Like Kind Analyzer .Recorof.Date/Hour and on or prior to the Current
Date/Current Hour.

Results:

Result
A

B

C

D

Usage:

1

2

3

4

5

6

7

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

If not found,

return result D

Response

The UnadjustedHourlyValue reported in the MHV record for [param] either before or
after the current hour is invalid.

The AdjustedHourlyValue reported in the MHV record for [param] either before or after
the current hour is invalid.

You reported an MODCCode of 11 in the MHV record for [param], but the length of the
missing data period exceeds the allowable value for use of this missing data procedure.
You reported an MODCCode of 17 in the MHV record for [param], indicating the use
of a like-kind analyzer, but you have used a like-kind analyzer to monitor this parameter
for more than 720 hours during this reporting period. You are not allowed to use a
like-kind analyzer for more than 720 hours during a calendar year, unless the analyzer is
identified as a non-redundant backup and a RATA is performed.

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	LOO Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 455 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-13

Check Name:	Check System in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current MHVMon Sys Record = null
Monitor Hourly System Status = false

If (Current MHV Parameter == "NOXC" AND NOx Cone Checks Needed for Nox Mass == false)

if (Current MHVifecorrf.MonitoringSystemID is NOT null AND Legacy Data Evaluation == false)
return result A

else

Monitor Hourly System Status = true

else if (Current MHV Parameter == "C02C" AND CO 2 Cone Checks Needed for Heat Input == false AND CO 2 Cone Checks Needed
for C02 Mass Calc == false)

if (Current MHVifecorrf.MonitoringSystemID is NOT null AND Legacy Data Evaluation == false)
return result B

else

Monitor Hourly System Status = true

else if (Current MHV Parameter == "02W" AND 02 Wet Checks Needed for Heat Input == false AND 02 Wet Checks Needed to
Support C02 Calculation == false) OR (Current MHV Parameter == "02D" AND 02 Dry Checks Needed for Heat Input == false AND
02 Dry Checks Needed to Support C02 Calculation == false)

if (Current MHVifecorrf.MonitoringSystemID is NOT null AND Legacy Data Evaluation == false)
return result G

else

Monitor Hourly System Status = true

else if (Current MHV Parameter in set {C02CSD, 02CSD})

if Current MHVifecorrf.MonitoringSystemID is NOT null
return result F

else

Monitor Hourly System Status = true

else

case (Current MHV Parameter)

S02C:

NOXC:

C02C, 02D, or 02W:

FLOW:

H20:

MODC Set = {01, 02, 03, 04, 16, 17, 18, 19, 20,21,22}
MODC Set = {01, 02, 03,04, 17, 18, 19,20,21,22}
MODC Set = {01,02, 03,04, 17, 18,20,21}

MODC Set = {01,02,03,04,20}

MODC Set = {01,02, 03,04,21}

If (Current MHV Record ModcCode in set MODC Set)

if Current MHVifecorrf.MonitoringSystemID is null
return result C

else

Environmental Protection Agency

Page 456 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Current MHVMon Sys Record = find active MonitoringSystemData record for location where

MonitoringSy stemData.MonitoringSystemID = Current MHVifecorrf.MonitoringSy stemID

if Current MHV Mon Sys Record is null
return result D

else

if {Current MHV Parameter in set {02D, 02W})

if (Legacy Data Evaluation == true

if (Current MHV Mon Sys itecortf.SystemTypeCode not in set

{H20,02,C02,N0XC,N0X})
return result E

else

Monitor Hourly System Status = true
else if (Current MHV Mon Sys ifecorrf.SystemTypeCode not in {02, C02})
return result E

else

Monitor Hourly System Status = true

else if {Current MHV Parameter = "H20")

if {Current MHV Mon Sys itecortf.SystemTypeCode not in {H20T, H20M})
return result E

else

Monitor Hourly System Status = true

else

if {Current MHV Mon Sys itecortf.SystemTypeCode o Current MHV System Type)

If {Current MHV Parameter == "C02C" AND Legacy Data Evaluation == true AND
Current MHV Mon Sys ifecorrf.SystemTypeCode == "NOX")
Monitor Hourly System Status = true

else

return result E

else

Monitor Hourly System Status = true

else if {Current MHVifecorrf.MonitoringSy stemID is NOT null AND Monitor Hourly MODC Status == true AND Current MHV
ifecoraJModcCode not in set {05, 16, 53, 54} )
return result F

else

Monitor Hourly System Status = true

Environmental Protection Agency

Page 457 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Non-Critical Error
Critical Error Level 1

Results:

Result	Response

A	You reported a MonitoringSystemID in the MHV record for NOXC, but this field

should be blank when the NOX concentration is used to calculate the NOX emission rate
as part of a NOX-diluent system.

B	You reported a MonitoringSystemID in the MHV record for C02C, but this field should

be left blank when C02 concentration is not used to calculate C02 mass or heat input.

C	You did not report a MonitoringSystemID in the MHV record for [param]. This

information is required when you report measured data.

D	You reported MonitoringSystemID [ID] in the MHV record for [param], but there is no

Monitoring System record for this system in your monitoring plan that was active during
the hour.

E	You reported MonitoringSystemID [ID] in the MHV record for [param], but this

SystemTypeCode for this monitoring system is not appropriate.

F	You reported a MonitoringSystemID in the MHV record for [param], but this is not

appropriate when substitute data is used.

G	You reported a MonitoringSystemID in the MHV record for [param], but this field

should be left blank when 02 concentration is not used to calculate C02 concentration
or heat input.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

2	Process/Category:	Emissions Data Evaluation Report	C02C Monitor Hourly Evaluation for Substitute Data

3	Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

4	Process/Category:	Emissions Data Evaluation Report	LOO Monitor Hourly Evaluation

5	Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

6	Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

7	Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

8	Process/Category:	Emissions Data Evaluation Report	02C Monitor Hourly Evaluation for Substitute Data

9	Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 458 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-14

Check Name:	Check System Designation Code for System in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

If (Monitor Hourly Mode Status == true AND Monitor Hourly System Status == true AND Current MHV Mon Sys Record is not null)
case (Current Mil]' Record. ModcCodc)

01 OR 17: If (Current MHV Mon Sys Record. SystemDesignationCode NOT in set {P, PB})
return result A

02: If (Current MHV Mon Sys Record. SystemDesignationCode NOT in set {B, RB, DB}
return result B

04: If (Current MHV Mon Sys Record. SystemDesignationCode o "RM")
return result C

22: If (Current MHV Mon Sys Record. SystemDesignationCode o "CI")
return result D

Results:

Result
A

B

C

D

Usage:

1

2

3

4

5

6

7

Response

You reported an MODCCode of [modcCode] in the MHV record for [param], but

MonitoringSystemID [ID] is not a primary system.

You reported an MODCCode of 02 in the MHV record for [param], but

MonitoringSystemID [ID] is not a backup system.

You reported an MODCCode of 04 in the MHV record for [param], but

MonitoringSystemID [ID] is not a reference method system.

You reported an MODCCode of 22 in the MHV record for [param], but

MonitoringSystemID [ID] is not a certified inlet system.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	LOO Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 459 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-15

Check Name:	Check Component in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Monitor Hourly Component Status = false

if {Current MHV Parameter NOT in set {C02CSD, 02CSD})

case (Current MHV Parameter)

S02C:	MODC Set = {01, 02, 03, 04, 16, 17, 18, 19,20,21,22,53}

NOXC:	MODC Set = {01,02,03,04, 17, 18, 19,20,21,22,53}

C02C, 02D, 02W:	MODC Set = {01,02,03,04, 17, 18,20,21,53}

FLOW:	MODC Set = {01,02,03,04,20,53}

H20:	MODC Set = {01, 02, 03, 04, 21, 53}

If (Current MHVRecord.ModcCode in set MODC Set)
if Current MHV Record. ComponentID is null

If (Current MHV Parameter == "FLOW" and Current MHV ifecorrf.MonitoringSystemID is not null)

Count Mon Sys Comp Record = count active MonitoringSystemComponent record for location where
MonitoringSystemComponentData .ComponentTypeCode = "FLOW" AND
MonitoringSystemComponentData.MonitoringSystemID = Current MHV
Record MonitoringSy stemID

If (Count Mon Sys Comp Record < 2)
return result A

Otherwise,

return result A

else

Current MHV Component Record = find ComponentData record where ComponentData.ComponentID = Current
MHV Record ComponentID

If Current MHV Component Record.ComponentTypeCode o Current MHV Component Type
return result B

else if Monitor Hourly ModcStatus == true AND Current MHV Record. ModcCodc ==17 AND Current MHV
Component Record. Componentldentifier does not begin with "LK"
return result C

else if (Monitor Hourly System Status == true AND Current MHV Mon Sys Record is not null)

Count Mon Sys Comp Record = count active MonitoringSystemComponent record for location where

MonitoringSystemComponentData .ComponentID = Current MHV Record. ComponentID AND
MonitoringSystemComponentData.MonitoringSy stemID = Current MHV
Record MonitoringSy stemID

If Count Mon Sys Comp Record = 0
return result D

Else

Monitor Hourly Component Status= true

Else

Environmental Protection Agency

Page 460 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Monitor Hourly Component Status = true

else

if Current MHVRecord ComponentID is NOT null
return result E

else

Monitor Hourly Component Status = true

else

if Current MHV Record ComponentID is NOT null
return result E

else

Monitor Hourly Component Status = true

Results:

Result

A

B

C

D

Usage:

1

2

3

4

5

6

7

Response

You did not report a ComponentID in the MHV record for [param].

You reported ComponentID [ID] in the MHV record for [param], but this is not an

[comptype] component.

You reported an MODCCode of 17 in the MHV record for [param], which indicates that
the component is a like-kind analyzer, but the ComponentID does not begin with LK.
You reported MonitoringSystemID [sys] ComponentID [ID] in the MHV record for
[param], but there is no MonitorSystemComponent record for this system and
component in your monitoring plan that was active during the hour.

You reported a ComponentID in the MHV record for [param], but this field should be
blank whenever missing data substitution is performed.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Non-Critical Error

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	LOO Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 461 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOLTRMH V -16

Check Name:

Check Pre-Bias-Adj usted Value

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Monitor Hourly Preadjusted Value Status = false

S02C: MODC Set = {01, 02, 03, 04, 16, 17, 18, 19,20,21,22,53,54}

NOXC: MODC Set = {01,02,03,04, 17, 18, 19,20,21,22, 53, 54}

FLOW: MODC Set = {01, 02, 03, 04, 20, 53, 54}

If (Current Mill' Record. ModcCodc in set MODC Set)

If {Current MHV RecordMn?id}v&tedY{om\yN?i\\ie is null AND

Current MHVRecordModcCode not in set {04, 19,20, 53, 54})
return result A

else if {Current MHVifecorrf.UnadjustedHourlyValue < 0.0 AND

Current MHVRecordModcCode not in set {16,21} )
return result A

else if {Current MHVifecorrf.UnadjustedHourlyValue > 2 AND
Current MHV RecordModcCode == 16 )
return result B

else if {Current MHVifecorrf.UnadjustedHourlyValue > 0 AND
Current MHV RecordModcCode == 21 )
return result C

else if {Current MHV Parameter in set {S02C, NOXC} and CMrren^MffFifecortf.UnadjustedHourlyValue is not rounded to 1
decimal place)

return result F

else if {Current MHV Parameter == "FLOW" and Current MffFifecorrf.UnadjustedHourlyValue is not rounded to the nearest
1000)

return result F

else

Monitor Hourly Preadjusted Value Status = true

if {Current MHV Max Min Value is not null)

if {Current MHV itecortf.UnadjustedHourly Value > Current MHV Max Min Value)
return result D

else if {Monitor Hourly Mode Status == true)

If (CMrren^MffFifecortf.UnadjustedHourlyValue is not null)
return result E

Else

Monitor Hourly Preadjusted Value Status = true

Environmental Protection Agency

Page 462 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

E
F

Usage:

1

2

3

Response

The UnadjustedHourlyValue reported in the MHV record for [param] is missing or
invalid.

You reported an MODCCode of 16 in the MHV record for [param], but the
UnadjustedHourlyValue exceeds 2.

You reported an MODCCode of 21 in the MHV record for [param], but the
UnadjustedHourlyValue is greater than 0.

Warning: The UnadjustedHourlyValue reported in the MHV record for [param] is in
excess of the maximum value listed in the monitoring plan. Sources are required to
periodically (at least once annually) evaluate the appropriateness of these maximum
values in the monitoring plan and make proper adjustments when necessary.
Adjustments may include the need to update Span and/or Default values. You should
investigate the cause of these exceedances and determine whether adjustments to your
monitoring systems or monitoring plan are necessary.

You reported an MODCCode of [modcCode] in the MHV record for [param], so you
should not have reported a value for the UnadjustedHourlyValue.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Informational Message

Critical Error Level 1
Critical Error Level 1

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 463 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMH V -17

Check Name:

Verify Consistency Between NOx Emission Rate and NOx Concentration

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (NOx Cone Neededfor NOx Rate Calc == true AND Monitor Hourly Mode Status == true)

if (Current MHV RecordMODCCo&e not in set {01, 02, 03, 04, 17, 18, 19, 20, 21, 22, 53} )
return result A

else if (Current MHV Record.MODCCode ==21 AND NOx Emission Rate MODC not in set {14,21})
return result A

else if (Current MHV Record. MODCCode == 22 AND NOx Emission Rate MODC not in set{ 14,22})
return result A

Results:

Result
A

Response

You reported an MODCCode of [MODC] in the MHV record for NOXC that is
inconsistent with MODCCode of [NOX ER MODC] reported in the DHV record for
NOXR.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Environmental Protection Agency

Page 464 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-18

Check Name:	Determine Maximum or Minimum Value for Parameter in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current MHV Max Min Value = null

If (Current MHV Parameter == "H20")

If {H20 Missing Data Approach == "MAX")

Current MHV Default Parameter = "H20X"

Else If (H20 Missing Data Approach == "MIN")

Current MHV Default Parameter = "H20N"
else if {Current MHV RecordModcCode == 12)
return result A

If (Monitor Hourly Mode Status == true AND Current MHV Default Parameter is not null)

If (Current MHV Record. ModcCode in set {12,23} AND Current MHV Fuel Specific Hour = true)

If Current Hourly Op ifecortf.FuelCode is not null

Current MHV Missing Data Fuel = Current Hourly Op Records uelCode

Count active MonitoringDefaultData record for location where
ParameterCode = Current MHV Default Parameter
FuelCode = Current Hourly Op Record. I Lie IC ode
DefaultPurposeCode = "MD" // Missing Data
OperatingCode in set {A,U} // Not Controlled

if (count >1)

return result B
else if (count == 0)

return result C

else

Default Record = the single matched record

if {Default Record.DefaultValue > 0)

Current MHV Max Min Value = Default .Recorof.DefaultValue

else

return result D

else if {Current MHV Record ModcCode in set {13, 24} AND Current MHV Fuel Specific Hour == true)

If Current Hourly Op ifecortf.FuelCode is not null

Current MHV Missing Data Fuel = Current Hourly Op Records uelCode

Count active MonitoringDefaultData record for location where
ParameterCode = Current MHV Default Parameter
FuelCode = Current Hourly Op Record. I Lie IC ode
DefaultPurposeCode = "MD" // Missing Data
OperatingCode in == "C" 11 Controlled

if {count >1)

return result B
else if {count == 0)

Environmental Protection Agency	Page 465 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result C

else

Default Record = the single matched record

if {Default Record.DefaultValue > 0)

Current MHVMax Min Value = Default .Recorof.DefaultValue

else

return result D
else if {Current MHVRecordMo&cCo&e o 15)

If {Current MHV Parameter in set {H20, 02W, 02D, 02CSD})
if {Current MHV Default Parameter is not null)

Current MHV Missing Data Fuel = "NF S"

if {Current MHV Parameter in set {02W, 02D} AND Current Mill' Record. ModcCodc == 20)
Current MHV Default Parameter = "02X"

Count active MonitoringDefaultData record for location where
ParameterCode = Current MHV Default Parameter
FuelCode = "NFS"

DefaultPurposeCode = "DC" 11 diluent cap

else

Count active MonitoringDefaultData record for location where
ParameterCode = Current MHV Default Parameter
FuelCode = "NFS"

DefaultPurposeCode = "MD" 11 missing data

if {count >1)

return result B

else if {{Current MHV Parameter == "02D" AND ()2 Dry Checks Needed for Heat Input == false) OR
{Current MHV Parameter == "02W" AND 02 Wet Checks Needed for Heat Input == false))

Current MHV Max Min Value = 0

else if {count == 0)

return result C

else

Default Record = the single matched record

if {Default Record.DefaultValue > 0)

Current MHV Max Min Value = Default .Recorof.DefaultValue

else

return result D

If {Current MHV Component Type == "FLOW")

Current MHV Span Description = "FLOW"

Monitor Span Record Count = Find active MonitoringSpanData records for location where
MonitoringSpanData .ComponentTypeCode = "FLOW"

else

Current MHV Span Description = Current MHV Component Type + " with a SpanScale of H"

Environmental Protection Agency

Page 466 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Monitor Span Record Count = Find active MonitoringSpanData records for location where

MonitoringSpanData .ComponentTypeCode = Current MHV Component Type AND
MonitoringSpanData.SpanScaleCode = "H"

if (Monitor Span Record Count >1)

return result E
else if (Monitor Span Record Count = 0)
return result F

else

Current Monitor Span Record = the single matched record

If (Current MIH' Record. ModcCodc == 19)

if Current Monitor Span .Recoraf.DefaultHighRange > 0)

Current MHV Max Min Value = Current Monitor Span Record. DefaultHighRange

else

return result G

else if {{Current Monitor Span .Recoraf.DefaultHighRange is null AND Current MHV Record. ModcCodc
not in set {13,24}) or Current MHVRecordModcCode == 12)

if {Current MHV RecordModcCode == 20)

if {Current MHV Parameter == "FLOW")

if Current Monitor Span .Recorof.FlowFullScaleRange > 0)

Current MHV Max Min Value = Current Monitor Span
.RecordFlowFullScaleRange * 2

else

return result G

else

if Current Monitor Span .Recorof.FullScaleRange > 0)

Current MHV Max Min Value = Current Monitor Span
Record FullScaleRange * 2

else

return result G

else

if {Current MHV Parameter == "FLOW")

if Current Monitor Span ifecortf.MPFValue > 0)

Current MHV Max Min Value = Current Monitor Span
Record MPF Value

else

return result G

else

if Current Monitor Span Record.MPCNsAue > 0)

Current MHV Max Min Value = Current Monitor Span
Record MPC^Value

else

return result G

else if {Current MHV Parameter in set {S02C, NOXC})

Current MHV Span Description = Current MHV Component Type + " with a SpanScale of L"
Monitor Span Record Count = Find active MonitoringSpanData records for location where

MonitoringSpanData .ComponentTypeCode = Current MHV Component Type AND
MonitoringSpanData.SpanScaleCode = "L"

if {Monitor Span Record Count > 1)
return result E

Environmental Protection Agency

Page 467 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else if (Monitor Span Record Count - 0)
return result F

else

Current Monitor Span Record = the single matched record

if (Current MHV RecordModcCode == 20)

if Current Monitor Span .Recorof.FullScaleRange > 0)

Current MHV Max Min Value = Current Monitor Span
.Recoraf.FullScaleRange * 2

else

return result G
else if {Current MHVitecoraJ ModcCode in set {13,24})

if Current Monitor Span .Recorof.MECValue > 0)

Current MHV Max Min Value = Current Monitor Span
.Recoraf.MECValue

else

return result G

if Current Monitor Span .Recorof.SpanValue > 0)

Current MHV Max Min Value = Current Monitor Span
Record. SpanValue

else

return result G

else

Results:

Result
A

Response

The missing data default parameter for H20 could not be determined, because you used
both Standard and Inverse Part 75 missing data approaches during the hour.
You reported more than one applicable [param] Default record with a FuelCode of
[FuelCode] in your monitoring plan for the hour.

You did not report an applicable [param] Default record with a FuelCode of [FuelCode],
The values reported in the applicable [param] Default record with a FuelCode of
[FuelCode] are invalid.

You reported more than one active span record for [key] in your monitoring plan for the
hour.

You did not report an active span record for [key] in your monitoring plan for the hour.
The values reported in the applicable span record for [key] are invalid.

Severity

Critical Error Level 2

B

Critical Error Level 1

C
D

Critical Error Level 1
Critical Error Level 1

E

Critical Error Level 1

F
G

Critical Error Level 1
Critical Error Level 1

Environmental Protection Agency

Page 468 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:

2	Process/Category:

3	Process/Category:

4	Process/Category:

5	Process/Category:

6	Process/Category:

7	Process/Category:

8	Process/Category:

9	Process/Category:

Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report
Emissions Data Evaluation Report

C02 Concentration Monitor Hourly Evaluation

C02C Monitor Hourly Evaluation for Substitute Data

FLOW Monitor Hourly Evaluation

H20 Monitor Hourly Evaluation

NOx Concentration Monitor Hourly Evaluation

02 Dry Monitor Hourly Evaluation

02 Wet Monitor Hourly Evaluation

02C Monitor Hourly Evaluation for Substitute Data

S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 469 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-19

Check Name:	Check Adjusted Hourly Value in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Monitor Hourly Adjusted Value Status = false

if (Monitor Hourly Mode Status == true AND Monitor Hourly Missing Data Status == true AND

{Monitor Hourly Pma Status == true OR Current MHVRecord.ModcCode NOT in set {06,07,08,09, 10, 11}))

If (Current MHV Parameter o "NOXC" OR NOx Cone Neededfor Nox Mass Calc == true)

If (Current MHV Parameter == "FLOW")
set Current MHV Precision to -3.

else

set Current MHV Precision to 1.

case (Current MHV Record ModcCode )

21: Current MHV Calculated Adjusted Value = 0

if (Current MHV Record. AdjustedHourlyValue == 0)
Monitor Hourly Adjusted Value Status = true

else

return result A

16: Current MHV Calculated Adjusted Value = 2

if (Current MHV itecortfAdjustedHourlyValue == 2)
Monitor Hourly Adjusted Value Status = true

else

return result B

= 12 OR = 23:

If (Current MHV Max Min Value is not null)

Current MHV Calculated Adjusted Value = Current MHV Max Min Value
if (Current MHV RecordAdjustedHourlyValue == Current MHV Max Min Value)
Monitor Hourly Adjusted Value Status = true

else

return result C

= 13 OR 24:

If (Current MHV Max Min Value is not null)

Current MHV Calculated Adjusted Value = Current MHV Max Min Value
if (Current MHV Record. AdjustedHourlyValue == Current MHV Max Min Value)
Monitor Hourly Adjusted Value Status = true

else

return result D

= 06: If (Current MHVHBHA Value is not null)

Current MHV Calculated Adjusted Value = Current MHV HBHA Value

If (Current MHV Record. AdjustedHourlyValue >= 0)

if ( Current MHV Record AdjustedHourlyValue == Current MHV Calculated Adjusted Value)
Monitor Hourly Adjusted Value Status = true

else

return result G

Environmental Protection Agency

Page 470 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

return result H

else

If	AdjustedHourlyValue >= 0)

If (Current MffFifecortfAdjustedHourlyValue is not rounded to Current MHVPrecision)
return result L

else

Current MHV Calculated Adjusted Value = Current MHV

ifecortfAdjustedHourlyValue

Monitor Hourly Adjusted Value Status = true

If (Current MHV Max Min Value is not null)

if	AdjustedHourlyValue > Current MHV Max Min

Value)

If (Current MHV Parameter == "S02C" and Current MHV
ifecortfAdjustedHourlyValue > Current MHV Max Min Value * 2)

return result O
Otherwise,

return result K

Else

return result H

= 08 OR 09:

If (Current MHV itecortfAdjustedHourlyValue >= 0)

If (Current MHVHBHA Value is not null AND Current MHVHBHA Value > Current MHV
Record AdjustedHourlyValue AND (Unit is Load Based == true or Current MHV Parameter <>

"NOXC")

Current MHV Calculated Adjusted Value = Current MHV HBHA Value

return result I

else

If (Current MffFifecortfAdjustedHourlyValue is not rounded to Current MHV Precision)
return result L

else

Current MHV Calculated Adjusted Value = Current MHV

ifecortfAdjustedHourlyValue

Monitor Hourly Adjusted Value Status = true

If (Current MHV Max Min Value is not null)

if (Current MHV Record. AdjustedHourlyValue > Current MHV Max Min
Value)

If (Current MHV Parameter == "S02C" and Current MHV
ifecortfAdjustedHourlyValue > Current MHV Max Min Value * 2)

return result O
Otherwise,

return result K

Else

return result H

= 04, 05, 07, 10, 11, 15, 53, 54, OR 55:

If (Current MHV itecortfAdjustedHourlyValue >= 0)

If (Current MHV Record. AdjustedHourlyValue is not rounded to Current MHV Precision)
return result L

Environmental Protection Agency

Page 471 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Current MHV Calculated Adjusted Value = Current MffFifecorrf.AdjustedHourlyValue
Monitor Hourly Adjusted Value Status = true

If (Current MHV Max Min Value is not null)

if (Current MHV Record AdjustedHourlyValue > Current MHV Max Min Value )
If (Current MHV Parameter == "S02C" and Current MHV
itecortfAdjustedHourlyValue > Current MHV Max Min Value * 2)

If the Current MHV Record.ModcCode ==10

return result P
Otherwise,

return result O

Otherwise,

return result K

Else

return result H

= All Other Codes:

If (Current MHV itecortfAdjustedHourlyValue >= 0)

If (Current MHVitecoraJ ModcCode in set {19, 20} AND CMrren^MffFifecortf.UnadjustedHourlyValue
is null)

If (Current MHV Max Min Value is not null)

if (Current MHV Record AdjustedHourlyValue == Current MHV Max Min Value )
Current MHV Calculated Adjusted Value = Current MHV
itecortfAdjustedHourlyValue
Monitor Hourly Adjusted Value Status = true

else

if (Current MHV RecordModcCode == "19")
return result M

else

return result N

else if (Current MHV Record. AdjustedHourlyValue is not rounded to Current MHV Precision)
return result L

else

Monitor Hourly Adjusted Value Status = true

Else

return result H

If (Current MHV Record. AdjustedHourlyValue is not null)
return result J

Environmental Protection Agency

Page 472 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

G

H
I

K

L
M

N

O

Usage:

1

2

3

Response

You reported an MODCCode of 21 in the MHV record for [param], but the
AdjustedHourlyValue does not equal 0.

You reported an MODCCode of 16 in the MHV record for [param], but the
AdjustedHourlyValue does not equal 2.

You reported an MODCCode of [modcCode] in the MHV record for [param], but the
AdjustedHourlyValue does not equal the maximum potential value reported in the
[comptype] span or fuel-specific default record in your monitoring plan.

You reported an MODCCode of 13 or 24 in the MHV record for [param], but the
AdjustedHourlyValue does not equal the maximum expected value reported in the
[comptype] span or fuel-specific default record in your monitoring plan.

You reported an MODCCode of 06 in the MHV record for [param], but the
AdjustedHourlyValue does not equal average of measured hour before and measured
hour after.

The AdjustedHourlyValue reported in the MHV record for [param] is invalid.
You reported an MODCCode of [MODCCode] in the MHV record for [param], but you
reported an AdjustedHourlyValue that is less than the average of the measured hour
before and measured hour after.

You reported an AdjustedHourlyValue in the MHV record for NOXC. This field should
be blank when the NOX concentration is used to calculate the NOX emission rate as part
of a NOX system.

Warning: The AdjustedHourlyValue reported in the MHV record for [param] is in
excess of the maximum value listed in the monitoring plan. Sources are required to
periodically (at least once annually) evaluate the appropriateness of these maximum
values in the monitoring plan and make proper adjustments when necessary.

Adjustments may include the need to update Span and/or Default values. You should
investigate the cause of these exceedances and determine whether adjustments to your
monitoring systems or monitoring plan are necessary.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

You reported an MODCCode of 19 in the MHV record for [param], but the
AdjustedHourlyValue does not equal the DefaultHighRange reported in the [comptype]
span record in your monitoring plan.

You reported an MODCCode of 20 in the MHV record for [param], but the
AdjustedHourlyValue does not equal 200 percent of the FullScaleRange reported in the
[comptype] span record in your monitoring plan.

The AdjustedHourlyValue reported in the MHV record for [param] is in excess of the
maximum value listed in the monitoring plan. Sources are required to periodically (at
least once annually) evaluate the appropriateness of these maximum values in the
monitoring plan and make proper adjustments when necessary. Adjustments may
include the need to update Span and/or Default values. You should investigate the cause
of these exceedances and determine whether adjustments to your monitoring systems or
monitoring plan are necessary.

The AdjustedHourlyValue reported in the MHV record for [param] is in excess of the
maximum value listed in the monitoring plan. Sources are required to periodically (at
least once annually) evaluate the appropriateness of these maximum values in the
monitoring plan and make proper adjustments when necessary. Adjustments may
include the need to update Span and/or Default values. You should investigate the cause
of these exceedances and determine whether adjustments to your monitoring systems or
monitoring plan are necessary.

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Informational Message

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 2

Informational Message

Environmental Protection Agency

Page 473 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-20

Check Name:	Check Unadjusted Hourly Value in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Monitor Hourly Unadjusted Value Status = false

if (Monitor Hourly Mode Status == true AND Monitor Hourly Missing Data Status == true AND

{Monitor Hourly Pma Status == true OR Current MHVRecord.ModcCode NOT in set {06,07,08,09, 10, 11}))

Calculated Unadjusted Value = null

case (Current Mill' Record. ModcCodc )

= 21: Calculated Unadjusted Value = 0

if (Current MHVRecord.UnadjustedHourlyValue == 0)

If (Current MHV Parameter == "C02C" and Current Hourly Op Record. I .oadRangc is greater than 1,
return result L

else

Monitor Hourly Unadjusted Value Status = true

else

return result A

= 12 OR = 23:

If (Current MHV Max Min Value is not null)

Calculated Unadjusted Value = Current MHV Max Min Value
if (Current MHV itecortf.UnadjustedHourly Value == Current MHV Max Min Value)

Monitor Hourly Unadjusted Value Status = true

else

return result B

= 20: If (Current MHVifecorrf.UnadjustedHourlyValue >= 0)

If (Current MHV Max Min Value is not null)

If (Current MHV Parameter begins with "02" AND Current MffFifecorrf.UnadjustedHourlyValue >
20.9)

Calculated Unadjusted Value = Current MHV Max Min Value
return result K

else if Current MHV Parameter == "C02C" AND Current MffFitecortf.UnadjustedHourlyValue >
Current MHV Max Min Value)

Calculated Unadjusted Value = Current MHV Max Min Value
return result C

elseif (Current MffFifecorrf.UnadjustedHourlyValue is not rounded to one decimal place)
return result I

else

Calculated Unadjusted Value = Current MffFitecortf.UnadjustedHourlyValue
Monitor Hourly Unadjusted Value Status = true

else

return result E
= 06: If (Current MHVHBHA Value is not null)

Calculated Unadjusted Value = Current MHV HBHA Value
If (Current MHVitecortf.UnadjustedHourly Value >= 0)

Environmental Protection Agency

Page 474 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if ( Current MffFifecortf.UnadjustedHourlyValue == Calculated Unadjusted Value)

Monitor Hourly Unadjusted Value Status = true

else

return result D

else

return result E

else

If (Current MHVitecortf.UnadjustedHourly Value >= 0)

If (CMrren^MffFifecortf.UnadjustedHourlyValue is not rounded to one decimal place)
return result I

else

Calculated Unadjusted Value = Current MffFitecortf.UnadjustedHourlyValue
Monitor Hourly Unadjusted Value Status = true

if (Current MHV Max Min Value is not null)

If {{Current MHV Parameter == "H20" AND H20 Missing Data Approach == "MIN")
OR Current MHV Parameter begins with "02")

if {Current MHV Record. I Jnadj ustedHourly Value < Current MHV Max Min
Value)

return result H

else

if {Current MHV Record. I Jnadj ustedHourly Value > Current MHV Max Min
Value)

return result F

Else

return result E

= 08 OR = 09:

If (Cwrren^MffFifecorrf.UnadjustedHourlyValue >= 0)

If {Current MHV HBHA Value is not null AND {{Current MHV Parameter == "H20" AND H20 Missing Data
Approach == "MIN") OR Current MHV Parameter begins with "02") AND Current MHV HBHA Value <

Current MHVifecorrf.UnadjustedHourly Value)

Calculated Unadjusted Value = Current MHV HBHA Value
return result J

else if {Current MHV HBHA Value is not null AND {{Current MHV Parameter == "H20" AND H20 Missing
Data Approach == "MAX") OR Current MHV Parameter does not begin with "02" or "H20") AND Current
MHV HBHA Value > Current MffFifecorrf.UnadjustedHourlyValue)

Calculated Unadjusted Value = Current MHV HBHA Value
return result G

else

if (CMrren^MffFifecortf.UnadjustedHourlyValue is not rounded to one decimal place)
return result I

else

Calculated Unadjusted Value = Current MffFitecortf.UnadjustedHourlyValue
Monitor Hourly Unadjusted Value Status = true

if {Current MHV Max Min Value is not null)

If {{Current MHV Parameter == "H20" AND H20 Missing Data Approach == "MIN")
OR Current MHV Parameter begins with "02")

if {Current MHV Record. I Jnadj ustedHourly Value < Current MHV Max Min
Value)

return result H

else

if {Current MHV Record. I Jnadj ustedHourly Value > Current MHV Max Min

Environmental Protection Agency

Page 475 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Value)

return result F

Else

return result E

= All Other Codes:

If (CMrren^MffFifecorrf.UnadjustedHourlyValue >= 0)

If (Current MHV Parameter in set {"H20", "C02C", "02D", "02W", "C02CSD", "02CSD"} AND Current
MffFifecorrf.UnadjustedHourlyValue > 100)
return result E

else if (Current MffFifecorrf.UnadjustedHourlyValue is not rounded to one decimal place)
return result I

else if (Current MffFifecorrf.UnadjustedHourlyValue == 0 AND Current MHV Parameter == "C02C" and
Current Hourly Op ifecorrf.LoadRange is greater than 1,
return result L

else

Calculated Unadjusted Value = Current MHFifecorrf.UnadjustedHourlyValue
Monitor Hourly Unadjusted Value Status = true

if (Current MHV Max Min Value is not null)

If ((Current MHV Parameter == "H20" AND H20 Missing Data Approach == "MIN") OR
Current MHV Parameter begins with "02")

if (Current MHV ifecorrf.UnadjustedHourlyValue < Current MHV Max Min Value)
return result H

else

if (Current MHV ifecorrf.UnadjustedHourlyValue > Current MHV Max Min Value)
return result F

Else

return result E

Whether or not there is a result returned:
If (Calculated Unadjusted Value is not null)

case (Current MHV Parameter)

C02C:	C02C MHV Calculated Adjusted Value = Calculated Unadjusted Value

02W:	02 Wet Calculated Adjusted Value = Calculated Unadjusted Value

02D:	02 Dry Calculated Adjusted Value = Calculated Unadjusted Value

H20:	H20 MHVCalculated Adjusted Value = Calculated Unadjusted Value

C02CSD:	C02C SD Calculated Adjusted Value = Calculated Unadjusted Value

02CSD:	02C SD Calculated Adjusted Value = Calculated Unadjusted Value

Environmental Protection Agency

Page 476 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

D

E
F

G

H

I
J

K

Usage:

1

2

3

4

5

6

Response

You reported an MODCCode of 21 in the MHV record for [param], but the
UnadjustedHourly Value does not equal 0.

You reported an MODCCode of [mode] in the MHV record for [param], but the
UnadjustedHourly Value does not equal the maximum potential value reported in the
[comptype] span or default record in your monitoring plan.

You reported an MODCCode of 20 in the MHV record for [param], but the
UnadjustedHourly Value does not equal 200 percent of the FullScaleRange reported in
the C02 span record in your monitoring plan.

You reported an MODCCode of 06 in the MHV record for [param], but the
UnadjustedHourly Value does not equal average of measured hour before and measured
hour after.

The UnadjustedHourlyValue reported in the MHV record for [param] is missing or
invalid.

Warning: The UnadjustedHourlyValue reported in the MHV record for [param] is in
excess of the maximum value listed in the monitoring plan. Sources are required to
periodically (at least once annually) evaluate the appropriateness of these maximum
values in the monitoring plan and make proper adjustments when necessary.
Adjustments may include the need to update Span and/or Default values. You should
investigate the cause of these exceedances and determine whether adjustments to your
monitoring systems or monitoring plan are necessary.

You reported an MODCCode of [MODC] in the MHV record for [param], but you
reported an UnadjustedHourlyValue that is less than the average of the measured hour
before and measured hour after.

Warning: The UnadjustedHourlyValue reported in the MHV record for [param] is
lower than the minimum value listed in the monitoring plan. Sources are required to
periodically (at least once annually) evaluate the appropriateness of these minimum
values in the monitoring plan and make proper adjustments when necessary.
Adjustments may include the need to update Default values. You should investigate the
cause of these low values and determine whether adjustments to your monitoring
systems or monitoring plan are necessary.

You reported [fieldname] in the [type] record for [param] that is not rounded to the
appropriate precision for that parameter.

You reported an MODCCode of [MODC] in the MHV record for [param], but you
reported an UnadjustedHourlyValue that is greater than the average of the measured
hour before and measured hour after.

You reported an MODCCode of 20 in the MHV record for [param], but the
UnadjustedHourlyValue does not equal the default value reported in the 02X default
record in your monitoring plan.

You have reported an UnadjustedHourlyValue of 0 in the MHV record for [param], but
the LoadRange is greater than 1. Emissions for [param] should be greater than 0 when
the unit (or stack) is operating at this load level.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Informational Message

Critical Error Level 1

Informational Message

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	C02C Monitor Hourly Evaluation for Substitute Data

Process/Category:	Emissions Data Evaluation Report	LOO Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02C Monitor Hourly Evaluation for Substitute Data

Environmental Protection Agency

Page 477 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-21

Check Name:	Determine BAF Value for Monitoring System in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current S02 System BAF = null
Current NOXC System BAF = null
Current FLOW System BAF = null

Continue = true

If (Current MHV Parameter == "NOXC")

If (XOx Cone Needed for Nox Mass Calc == false)

Continue == false

If (Continue == true AND Monitor Hourly System Status == true AND Monitor Hourly Preadjusted Value Status == true AND (Current
MHV Record ModcCode in set {01, 02, 03, 17, 18, 22, 53} OR (Current MHV RecordModcCode in set {19, 20} AND Current MHV
ifecorrfUnadjustedHourlyValue is not null AND Current MHV Max Min Value is not null)))

If (RATA Status BAF is not null)

case (Current MHV Parameter)

S02C: Current S02 System BAF = RATA Status BAF
NOXC: Current NOXC System BAF = RATA Status BAF
FLOW: Current FLO W System BAF = RA TA Status BAF

else

return result A

Results:

Result	Response	Severity

A	The BAF for [ParamCode] MonitoringSystemID [ID] cannot be determined, because the	Critical Error Level 1

prior RATA had critical errors or because of a RATA Status error listed on this report.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	NOXC RATA Status Evaluation

2	Process/Category:	Emissions Data Evaluation Report	S02 RATA Status Evaluation

3	Process/Category:	Emissions Data Evaluation Report	Stack Flow RATA Status Evaluation

Environmental Protection Agency

Page 478 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-22

Check Name:	Calculate Bias Adjusted Value in MHV Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

case (Current MHV Parameter)

S02C: Current BAF = Current S02 System BAF
NOXC: Current BAF = Current NOXC System BAF
FLOW: Current BAF = Current FLOW System BAF

if (Current BAF is not null)

If (Current MHV Parameter == "FLOW")

Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = Current MHV Parameter AND
UOM = "SCFH"

Calculated Adjusted Value = Current MffFitecortf.UnadjustedHourlyValue * Current BAF, and the result to the nearest
1000.

Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = Current MHV Parameter AND
UOM = "PPM"

Calculated Adjusted Value = Current MffFitecortf.UnadjustedHourlyValue * Current BAF, and the result to one decimal
place (0.1).

If (Current MHV Record.ModcCode in set {19,20} AND Calculated Adjusted Value > Current MHV Max Min Value)

case (Current MHV Parameter)

S02C: S02C Calculated Adjusted Value = Current MHV Max Min Value
NOXC: NOXC Calculated Adjusted Value = Current MHV Max Min Value
FLOW: FLOW Calculated Adjusted Value = Current MHV Max Min Value

if (Monitor Hourly Adjusted Value Status == true)

if (Current MHV itecortf.AdjustedHourlyValue o Current MHV Max Min Value)
If (Current MHV Record.ModcCode == 20)
return result A

else

return result C

else

case (Current MHV Parameter)

S02C: S02C Calculated Adjusted Value = Calculated Adjusted Value
NOXC: NOXC Calculated Adjusted Value = Calculated Adjusted Value
FLOW: FLOW Calculated Adjusted Value = Calculated Adjusted Value

if (Monitor Hourly Adjusted Value Status == true)

if ABS(Calculated Adjusted Value - Current MHV Record. AdjustedHourlyValue) > Tolerance
return result B

else

case (Current MHV Parameter)

S02C: S02C Calculated Adjusted Value = Current MHV Calculated Adjusted Value
NOXC: NOXC Calculated Adjusted Value = Current MHV Calculated Adjusted Value
FLOW: FLOW Calculated Adjusted Value = Current MHV Calculated Adjusted Value

Environmental Protection Agency

Page 479 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

B
C

Usage:

1

2

3

Response

You reported an MODCCode of 20 in the MHV record for [param], but the
AdjustedHourlyValue does not equal 200 percent of the FullScaleRange reported in the
[comptype] span record in your monitoring plan.

The AdjustedHourlyValue reported in the MHV record for [param] is not equal to the
UnadjustedHourlyValue times the BAF for the [systype] MonitoringSystemID [ID].
You reported an MODCCode of 19 in the MHV record for [param], but the
AdjustedHourlyValue does not equal the DefaultHighRange reported in the [comptype]
span record in your monitoring plan.

Process/Category:	Emissions Data Evaluation Report	NOXC RATA Status Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 RATA Status Evaluation

Process/Category:	Emissions Data Evaluation Report	Stack Flow RATA Status Evaluation

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Environmental Protection Agency

Page 480 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMHV-23

Check Name:

Initialize C02C Hourly Monitor for Substitute Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHV Parameter = "C02CSD"

C02C SD Calculated Adjusted Value = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	C02C Monitor Hourly Evaluation for Substitute Data

Environmental Protection Agency

Page 481 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMH V-24

Check Name:

Initialize 02C Hourly Monitor for Substitute Data

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current MHV Parameter = "02CSD"

02C SD Calculated Adjusted Value = null

Results:

Result	Response	Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	02C Monitor Hourly Evaluation for Substitute Data

Environmental Protection Agency

Page 482 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOURMHV-26

Check Name:

Determine if MHV Record Needs QA Status Evaluation

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set LinearityStatusRequired = false.

Set Current Linearity Status = null.

Set RATAStatusRequired = false.

Set Current RATA Status = null.

Set RA TA Status BAF = null.

Set DailyCalStatusRequired = false
Set Current Daily Cal Status = null.

Set F2L Status Required = false.

Set Daily Int Status Required = false
Set Leak Status Required = false

if (Monitor Hourly Mode Status == true AND

{CurrentMHVRecord.ModcCode in set {01, 02, 03, 17, 18, 21, 22, 53} OR

(CurrentMHVRecord.ModcCode in set {19,20} AND CurrentMHVRecord.\JnadjustedHour\yVa\ue is not null AND
Current MHV Max Min Value is not null)))

if (MonitorHourlyComponentStatus = true AND CurrentMHVRecord.ComponentID is not null AND CurrentMHVParameter in

set {S02C, NOXC, C02C, 02D, 02W} )

Set LinearityStatusRequired = true.

Set DailyCalStatusRequired = true.

if (MonitorHourlyComponentStatus = true AND CurrentMHVRecord.ComponentID is not null AND CurrentMHVParameter in

set {FLOW} )

Set DailyCalStatusRequired = true.

Set Daily Int Status Required = true.

If CitfTCTtfMffFifecortf.SampleAcquistionMethodCd = "DP"

Set Leak Status Required = true.

if (MonitorHourlySystemStatus = true AND Current Mil] Record. Moni tori ngSvstcm 11) is not null AND
CurrentMHVRecord.SystemTypeCode is in {S02, NOXC, FLOW, H20M} )

Set RATAStatusRequired = true.

Set CurrentHourlyRecordforRATAStatus = Current MHV Record.
if CurrentMHVRecord.SystemTypeCode is equal to 'FLOW',

else if ((C02 Cone Checks Needed for Heat Input == true AND CurrentMHVParameter == "C02C") OR (02 Wet Checks
Needed for Heat Input == true AND CurrentMHVParameter == "02W") OR (02 Dry Checks Needed for Heat Input == true
AND CurrentMHVParameter == "02D"))

Set C02RATARequired = true.

if (RATA Status Required == false AND Current MHV Parameter in {S02C, NOXC, FLOW})

case (Current MHV Parameter)

Set F2L Status Required = true.

Environmental Protection Agency

Page 483 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

S02C: S02C Calculated Adjusted Value = Current MHV Calculated Adjusted Value
NOXC: NOXC Calculated Adjusted Value = Current MHV Calculated Adjusted Value
FLOW: FLOW Calculated Adjusted Value = Current MHV Calculated Adjusted Value

if (LinearityStatusRequired== true OR Daily CalStatusRequired == true)

Set DualRangeStatus = false.

Set CurrentAnalyzerRangeUsed = null.

Set ApplicableSystemlDs = null.

Set HighRangeComponentID = null.

Set LowRangeComponentID = null.

if (CurrentMHVParameter == "FLOW")

Set ApplicableComponentID = Current MHV Record. ComponentID

else

Set ApplicableComponentID = null.

Locate a record in AnalyzerRangeRecordsByHourLocation for the hour and location where the ComponentID is equal to
the CurrentMHVRecord.ComponentID.

if (AnalyzerRangeRecordsByHourLocation is not found OR if more than one AnalyzerRangeRecordsByHourLocation is
found)

set Linearity Status Required == false
set DailyCalStatusRequired = false
return result A

else

if (Analyzer Range Records By [four [^/cation.\)ud\Rdnuc\ndicdlor = 1)

Set DualRangeStatus = true.

if (Analyzer Range Record.AnalyzerRangeCode = "A")

Locate the record in MonitorSpanRecordsByHourLocation for the hour and location where the
ComponentTypeCode is equal to the CurrentMHVRecord.ComponentTypeCode and the
SpanScaleCode is equal to "L".

if (MonitorSpanRecordsByHourLocation is not found OR if more than one
MonitorSpanRecordsByHourLocation is found OR if the
MonitorSpanRecordsByHourLocation.ScaieTmnsitionPoint is null or <= 0)

set Linearity Status Required == false
set DailyCalStatusRequired = false
return result B

else if (MonitorSpanRecordsByHourLocation is found AND
CMrratfMZ/Fifecortf.UnadjustedHourlyValue >

Monitor SpanRecordsByHourLocation. S cale Transiti onPoi nt AND
CurrentMHVRecord.ModcCode o "18")

Set CurrentAnalyzerRangeUsed = "H".

Set HighRangeComponentID = CurrentMII] Record. Component ID.
Set LowRangeComponentID = CurrentMHVRecord Component ID.

else

Environmental Protection Agency

Page 484 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set CurrentAnalyzerRangeUsed = "L".

Set HighRangeComponentID = Current Mil] Record. Component ID.
Set LowRangeComponentID = CurrentMHVRecord Component ID.

else

Set CurrentAnalyzerRangeUsed =

AnalyzerRangeRecordsByHourLocation.AnalyzerRangeCode.

if (Analyzer Range Records By I lour Location. And\\/crRdnucCodc = "H")

Locate a record in AnalyzerRangeRecordsByHourLocation for the hour and location
where the ComponentTypeCode is equal to the

CurrentMHVRecord.ComponentTypeCode and the AnalyzerRangeCode is equal to "L"
AND the ComponentSerialNumber is equal to the

CurrentMII] '/f/Y/.ComponentSerial Number (removing the phrases "HIGH", "HI",
"LOW", and "LO").

if (AnalyzerRangeRecordsByHourLocation is not found OR if more than one
AnalyzerRangeRecordsByHourLocation is found)

set Linearity Status Required == false
set DailyCalStatusRequired = false
return result C

else If (AnalyzerRangeRecordsByHourLocation is found)

Set HighRangeComponentID = CurrentMII] Record. Component ID.
Set LowRangeComponentID =

AnalyzerRangeRecordsByHourLocation. Component ID.

else i [(CurrentMII] '/feewrf. AnalyzerRangeCode = "L")

Locate a record in AnalyzerRangeRecordsByHourLocation for the
CurrentMHVRecordHow where the ComponentTypeCode is equal to the
CurrentMHVRecord.ComponentTypeCode and the AnalyzerRangeCode is equal to "H"
AND the ComponentSerialNumber is equal to the

CurrentMII] '/f/Y/.ComponentSerial Number (removing the phrases "HIGH", "HI",
"LOW", and "LO").

if (AnalyzerRangeRecordsByHourLocation is not found OR if more than one
AnalyzerRangeRecordsByHourLocation is found)

set Linearity Status Required == false
set Daily CalStatusRequired = false
return result C

else If (AnalyzerRangeRecordsByHourLocation is found)

Set LowRangeComponentID = CurrentMII] Record. Component ID.
Set HighRangeComponentID =

AnalyzerRangeRecordsByHourLocation. Component ID.

Set CurrentAnalyzerRangeUsed = Analyzer Range Records By I lour Location. And\\/crRdnucCodc.

else

Environmental Protection Agency

Page 485 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (CurrentAnalyzerRangeUsed = "H")

Set HighRangeComponentID = CurrentMII] Record.Component ID.

else

Set LowRangeComponentID = CurrentMHVRecord Component ID.

if (CurrentAnalyzerRangeUsed = "H")

Set ApplicableComponentID = HighRangeComponentID.

else

Set ApplicableComponentID = LowRangeComponentID.

For each record in MonitorSystemComponentRecordsByHourLocation where the ComponentID is equal to the
ApplicableComponentID

Append MonitorSystemComponentRecordsByHourLocation.SystemID to ApplicableSystemlDs.

if (MonitorSystemComponentRecordsByHourLocation is not found)

set Linearity Status Required == false
set DailyCalStatusRequired = false
return result D

Results:

Result

B

D

Usage:

1

2

3

4

5

6

7

Response

You did not report one (and only one) valid Analyzer Range record in your monitoring
plan for ComponentID [COMPID] for this hour. The QA Status of the linearity and/or
daily calibration tests for this component will not be evaluated.

You reported that ComponentID [COMPID] is a dual-range analyzer, but you did not
report one (and only one) active low-scale [COMPTYPE] span record with a valid
ScaleTransitionPoint in your monitoring plan for this hour. The QA Status of the
linearity and/or daily calibration tests for this component will not be evaluated.
You reported that ComponentID [COMPID] is a dual-range analyzer, but the program
could not identify the alternate range component in your monitoring plan. The QA
Status of the linearity and/or daily calibration tests for this component will not be
evaluated.

You did not report any System Component records for ComponentID [compid] in your
monitoring plan for the hour. The QA Status of the linearity and/or daily calibration
tests for this component will not be evaluated.

Process/Category:	Emissions Data Evaluation Report	C02 Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	FLOW Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	H20 Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	NOx Concentration Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Monitor Hourly Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 Monitor Hourly Evaluation

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 486 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOURMHV-27

Check Name:	Determine MHV Measure Code

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

If {Current MHV Parameter == "C02CSD")

Set Monitor Measure Code Array for "C02C" to "SUB"

else If (Current MHV Parameter == "02CSD")

Set Monitor Measure Code Array for "02D" to "SUB"

Set Monitor Measure Code Array for "02W" to "SUB"

else if (Current MHV Parameter in set {S02C, NOXC, C02C, 02D, 02W, FLOW, H20} AND Monitor Measure Code Array for the
Current MHV Parameter is null)

If (Current MHV RecordModcCode in set {01, 02, 03, 04, 05, 16, 17, 19, 20, 21, 22, 53, 54})

Set Monitor Measure Code Array for the Current MHV Parameter to "MEASURE"
else if (Current MHV RecordModcCode in set {06, 07, 08, 09, 10, 11, 12, 13, 15, 23,24, 55})

Set Monitor Measure Code Array for the Current MHV Parameter to "SUB"
else if (Current MHV RecordModcCode == "18"

Set Monitor Measure Code Array for the Current MHV Parameter to "MEASSUB"

Results:

Result	Response

Usage:

1	Process/Category:	Emissions Data Evaluation

2	Process/Category:	Emissions Data Evaluation

3	Process/Category:	Emissions Data Evaluation

4	Process/Category:	Emissions Data Evaluation

5	Process/Category:	Emissions Data Evaluation

6	Process/Category:	Emissions Data Evaluation

7	Process/Category:	Emissions Data Evaluation

8	Process/Category:	Emissions Data Evaluation

9	Process/Category:	Emissions Data Evaluation

Severity

Report	C02 Concentration Monitor Hourly Evaluation

Report	C02C Monitor Hourly Evaluation for Substitute Data

Report	FLOW Monitor Hourly Evaluation

Report	LOO Monitor Hourly Evaluation

Report	NOx Concentration Monitor Hourly Evaluation

Report	02 Dry Monitor Hourly Evaluation

Report	02 Wet Monitor Hourly Evaluation

Report	02C Monitor Hourly Evaluation for Substitute Data

Report	S02 Monitor Hourly Evaluation

Environmental Protection Agency

Page 487 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Hourly Operating Data

Environmental Protection Agency

Page 488 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-1

Check Name:	Validate Single Operating Data record for hour

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current Hourly Op Record = null

Unit Hourly Operational Status = false

Hourly Extraneous Fields = null

Count all HourlyOperatingData records with current MonitoringLocationID where
BeginHour = Current Hour AND
BeginDate = Current Date

If count == 0

Derived Hourly Checks Needed = false

if (Current Month is not April OR Annual Reporting Requirement == true)

If {Current Entity Type == "Unit" OR LME HI Method is null)

If {Reporting Period Operating == false AND Legacy Data Evaluation == true)
return result E

else

Locate Monitor Method records where the BeginDate/BeginHour is on or before the Current Date and
Hour, and the EndDate/EndHour is null or is on or after the Current Date and Hour.

If found

return result A

else if count > 1

if {Current Month is not April OR Annual Reporting Requirement == true)

Rpt Period C02 Mass Reported Accumulator Array for the location = -1
Rpt Period C02 Mass Calculated Accumulator Array for the location =-1
Rpt Period HI Reported Accumulator Array for the location =-1
Rpt Period HI Calculated Accumulator Array for the location = -1
Rpt Period NOx Rate Reported Accumulator Array for the location = -1
Rpt Period NOx Rate Calculated Accumulator Array for the location = -1
Rpt Period S02 Mass Reported Accumulator Array for the location = -1
Rpt Period S02 Mass Calculated Accumulator Array for the location = -1
Rpt Period NOx Mass Reported Accumulator Array for the location = -1
Rpt Period NOx Mass Calculated Accumulator Array for the location = -1
Rpt Period Op Time Accumulator Array for the location = -1
Rpt Period Op Hours Accumulator Array for the location = -1
Daily Op Time Accumulator Array for the location = -1

Derived Hourly Checks Needed = false
return result B

else if {Current Entity Type o "Unit" AND LME HI Method is not null)

Derived Hourly Checks Needed = false
return result D

else

Current Hourly Op Record = Unique HourlyOperatingData record
Current Operating Time = Current Hourly Op ifecorrf.OperatingTime

If {First Day of Operation is null)

First Day of Operation = Current Hourly Op Record.Date

Environmental Protection Agency

Page 489 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

First Hour of Operation = Current Hourly Op Record.Hour

if Current Operating Time >1.0 OR Current Operating Time <0.0
Derived Hourly Checks Needed = false

if (Current Month is not April OR Annual Reporting Requirement == true)
Rpt Period Op Time Accumulator Array for the location = -1
Rpt Period Op Hours Accumulator Array for the location = -1
Daily Op Time Accumulator Array for the location = -1

if {Current Entity Type = "Unit")

Unit OpTime Accumulator = -1

else

Stack OpTime Accumulator = -1
return result C

else

Derived Hourly Checks Needed = true
if Current Operating Time >0.0

Unit Hourly Operational Status = true

if (Current Month is not April OR Annual Reporting Requirement == true)

if (Rpt Period Op Hours Accumulator Array for this location is not null)

if (Rpt Period Op Hours Accumulator Array for this location >= 0)

Rpt Period Op Hours Accumulator Array for this location = Rpt Period Op Hours
Accumulator + 1

else

Rpt Period Op Hours Accumulator Array for this location = 1

if (Rpt Period Op Time Accumulator Array for this location is not null)

if (Rpt Period Op Time Accumulator Array for this location >= 0)

Rpt Period Op Time Accumulator Array for this location = Rpt Period Op Time
Accumulator + Current Hourly Op ifecorrf.OperatingTime

else

Rpt Period Op Time Accumulator Array for this location = Current Hourly Op
ifecorrf.OperatingTime

If (Current Month is April)

if (April Op Hours Accumulator Array for this location is not null)

April Op Hours Accumulator Array for this location = April Op Hours Accumulator + 1

else

April Op Hours Accumulator Array for this location = 1

if (April Op Time Accumulator Array for this location is not null)

April Op Time Accumulator Array for this location = April Op Time Accumulator +
Current Hourly Op ifecorrf.OperatingTime

else

April Op Time Accumulator Array for this location = Current Hourly Op
ifecorrf.OperatingTime

if (Daily Op Time Accumulator Array for this location is not null)

if (Daily Op Time Accumulator Array for this location >= 0)

Daily Op Time Accumulator Array for this location = Daily Op Time Accumulator + Current
Hourly Op ifecorrf.OperatingTime

else

Daily Op Time Accumulator Array for this location = Current Hourly Op itecortf.OperatingTime
if (Last Day of Operation Array for the location is null OR is not equal to Current Date)

Environmental Protection Agency

Page 490 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Last Day of Operation Array for the location = Current Date

if (Rpt Period Op Days Accumulator Array for this location is not null)

if {Rpt Period Op Days Accumulator Array for this location >= 0)

Rpt Period Op Days Accumulator Array for this location = Rpt Period Op Days
Accumulator + 1

else

Rpt Period Op Days Accumulator Array for this location = 1

If {Current Month is April)

if {April Op Days Accumulator Array for this location is not null)

April Op Days Accumulator Array for this location = April Op Days Accumulator + 1

else

April Op Days Accumulator Array for this location = 1

if {Current Entity Type = "Unit")

if {Unit OpTime Accumulator >= 0)

Unit OpTime Accumulator = Unit OpTime Accumulator + Current Hourly Op
ifecorrf.OperatingTime

if Current Hourly Op itecortf.OperatingTime > Max Unit OpTime

Max Unit OpTime = Current Hourly Op ifecorrf.OperatingTime

else if {Current Entity Type == "CS" OR Current Entity Type == "MS")
if {Stack OpTime Accumulator >= 0)

Stack OpTime Accumulator = Stack OpTime Accumulator + Current Hourly Op
ifecorrf.OperatingTime

if Current Hourly Op itecortf.OperatingTime > Max Stack OpTime

Max Stack OpTime = Current Hourly Op ifecorrf.OperatingTime

Results:

Result

A

B

D

Response

You did not report an Hourly Operating record for the hour.

You reported more than one Hourly Operating records for the hour. There will be no
further evaluation of the reported emissions data for this hour.

The OperatingTime reported in the Hourly Operating record is invalid. This value must
be between 0 and 1. There will be no further evaluation of the reported emissions data
for this hour.

You reported an invalid Hourly Operating record. Only the units in an LME monitoring
configuration should report this record. There will be no further evaluation of the
reported emissions data for this hour.

You did not report an Hourly Operating record for the hour. Although this was
acceptable for legacy data during a non-operating quarter, it is not allowed in ECMPS.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Fatal

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 491 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-2

Check Name:

Count Flow, 02, and Heat Input records

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Flow Monitor Hourly Count = count of MonitorHourlyValueData records with parameter FLOW where
Current Date = MonitorFtourly ValueData.Date and
Current Hour = MonitorFtourly ValueData.Ftour

02 Wet Monitor Hourly Count = count of MonitorFtourly ValueData records with ParameterCode = "02C" AND MoistureBasis = "W"

02 Dry Monitor Hourly Count = count of MonitorFtourly ValueData records with ParameterCode = "02C" AND MoistureBasis = "D"

02 Null Monitor Hourly Count = count of MonitorFtourlyValueData records with ParameterCode = "02C" AND MoistureBasis is NULL
where

if 02 Null Monitor Hourly Count == 1

Current 02 Null Monitor Hourly Record = the single matching record

Heat Input Derived Hourly Count = count of DerivedFtourly ValueData records with ParameterCode equal to "Ftt" where
Current Date = DerivedFtourlyValueData.Date and
Current Hour = DerivedFtourly ValueData.Ftour

II 02 Needed To Support Heat Input = false

where

Current Date = MonitorFtourly ValueData.Date and
Current Hour = MonitorFtourly ValueData.Ftour

where

Current Date = MonitorFtourly ValueData.Date and
Current Hour = MonitorFtourly ValueData.Ftour

Current Date = MonitorFtourly ValueData.Date and
Current Hour = MonitorFtourly ValueData.Ftour

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Operating Flour Evaluation

Environmental Protection Agency

Page 492 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-3

Check Name:

Initialize Location Variables for the Hour

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Current Unit Is Peaking = false

Current Unit Is ARP = false

Special Fuel Burned = false

FC Factor Needed = false

FD Factor Needed = false

FWFactor Needed = false

Moisture Needed = false

H20 Missing Data Approach = null

Flow Monitor Hourly Checks Needed = false

Current MHV Parameter = null

Current DHV Parameter = null

Current DHV Record Valid = false

Current DHV Record = null

Current DHV Method = null

Current DHV System Type = null

Current DHVHBHA Value = null

C02 Cone Checks Needed for C02 Mass Calc = false

CO 2 Cone Checks Needed for Heat Input = false

CO 2 Diluent Checks Needed for NOx Rate Calc = false

02 Dry Checks Needed for Heat Input = false

02 Dry Checks Needed for NOx Rate Calc = false

02 Wet Checks Needed for Heat Input = false

02 Wet Checks Needed for NOx Rate Calc = false

Linearity Status Required = false

AppendixEStatus Required = false

RATAStatusRequired = false

Current RATA Status = null

CurrentHourlyRecordforRATAStatus = null

RATAStatusBAF = null

Daily Cal Status Required = false

C02RATA Required = false

HI Measure Code = null.

NOXR Measure Code = null.

F2L Status Required = false

Daily Int Status Required = false

Leak Status Required = false

If the StackPipelD of the monitoring location begins with "CS",
set Current Entity Type = "CS"

else if the StackPipelD of the monitoring location begins with "CP",
set Current Entity Type = "CP"

else if the StackPipelD of the monitoring location begins with "MS",
set Current Entity Type = "MS"

else if the StackPipelD of the monitoring location begins with "MP",
set Current Entity Type = "MP"

else

Environmental Protection Agency

Page 493 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

set Current Entity Type = "Unit"

if Current Entity Type = "Unit"

Mon Qual Record Count = Find Monitor Qualification Records by Hour where
MonitoringLocationld = Current Location

Mon Qual Record.QualTypecode == "PK" OR Mon Qual Record.QualTypecode == "SK"
if Mon Qual Record Count > 0

else if Current Entity Type = "CP"

find all entries in UnitStackConfiguration table where

UnitStackConfiguration.StackPipeld = the StackPipeld for this pipe
for each matching record

set^ssoc Unit = UnitStackConfiguration.Unitld

Mon Qual Record Count = Find MonitorQualification Records by Hour where
MonitoringLocationld = Assoc Unit

Mon Qual Record.QualTypecode == "PK" OR Mon Qual Record.QualTypecode == "SK"
ifMora Qual Record Count is not null

Current Unit Is Peaking = true

locate records in the UnitProgram Table where

either (a) for a unit there is a record with the location identifier for that unit, OR

(b) for a non-unit there is a record with the location identifier for a unit associated with that entity

if any records from UnitProgram table meeting these conditions exist and within those records:

PRG CD = "ARP", CLASS o "NA", EndDate is on or after the Current Operating Date

and either a) the EmissionsRecordingDate is not null and is on or prior to the Current Operating Date or b) the

EmissionsRecordingDate is null and the UnitMonitorCertBeginDate is not null and is on or prior to the Current Operating Date.

Current Unit Is ARP = true

Set EarliestLocationReportDate = CurrentMonitorPlanLocationRecord.EarhestReportDate

Current Unit Is Peaking = true

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 494 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-4

Check Name:

Verify S02 Monitor Method Active During Current Hour

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

If (Derived Hourly Checks Needed)

S02 Monitor Method Record = null

S02 CEM Method Active For Hour = false

S02 App D Method Active For Hour = false

S02 F23 Method Active For Hour = false

S02 Method Code = null

S02 Fuel Specific Missing Data = false

S02 Bypass Code = null

S02 Method Count = Active records in MonitoringMethodData for the location where
ParameterCode = "S02" or "S02M"

if (S()2 Method Count >1)

return result A
else if S02 Method Count == 1

if (S02 Monitor Method Record. SubDataCode begins with "FSP75")

S02 Fuel Specific Missing Data = true
S02 Bypass Code = S02 Monitor Method Record BypassApproachCode

Expected Summary Value S02 Array for this location = true

if (SO2 Monitor Method ifecoraJ MethodCode == "CEM")

S02 CEM Method Active For Hour = true
else if S02 Monitor Method itecoraJ MethodCode == "F23")

S02 F23 Method Active For Hour = true
else if (S02 Monitor Method Record MethodCode == "AD")

S02 App D Method Active For Hour = true

S02 Monitor Method Record = the single matched record
S02 Method Code = S02 Monitor Method Record MethodCode

if (LME HI Method is not null AND S02 Method Code o "LME")

return result B

else

Results:

Result
A

Response

You have reported more than one active S02 Method record in your monitoring plan for
this hour.

You reported an invalid [param] method for a location that is part of a configuration of
LME units.

Severity

Critical Error Level 1

B

Critical Error Level 1

Environmental Protection Agency

Page 495 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 496 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-5

Check Name:

Determine H20 Method

Related Former Checks:

Applicability:

Description:

Specifications:

if Derived Hourly Checks Needed
H20 Method Code = null
H20 Default Value = null
H20 Default Max Value = null
H20 Default Min Value = null
Current Hourly H20 Table Reference = null
H20 Fuel Specific Missing Data = false

H20 Reported Value = null

H20 Method Count = Active records in MonitoringMethodData for the location where
ParameterCode = "H20"

H20 Derived Hourly Count = count of DerivedHourlyValueData where ParameterCode = "H20" for current hour
H20 Monitor Hourly Count = count of MonitorHourlyValueData where ParameterCode = "H20" for current hour
if (H20 Method Count > 2

else if (H20 Method Count == 2)

If (H20 Derived Hourly Count + H20 Monitor Hourly Count > 0)

If (H20 Derived Hourly Count == 1 AND H20 Monitor Hourly Count == 0 AND the MethodCode in one of the
matched records is equal to "MWD")

Current Hourly H20 Table Reference = DerivedHourlyValueData where ParameterCode = "H20"
H20 Reported Value = Current Hourly H20 Table Reference AdjustedHourlyValue
H20 Method Code = "MWD"

else if (H20 Derived Hourly Count == 0 AND H20 Monitor Hourly Count == 1 AND the MethodCode in one
(but not both) of the matched records is equal to "MTB" or "MMS")

Current Hourly H20 Table Reference = MonitorHourlyValueData where ParameterCode = "H20"
H20 Reported Value = Current Hourly H20 JaWeife/erence UnadjustedHourlyValue
if the MethodCode in the matched record == "MMS"

H20 Method Code = "MMS"

else

else

return result A
else if H20 Method Count == 1

H20 Monitor Method Record = the single matched record
H20 Method Code = H20 Monitor Method ifecorrf.MethodCode
if (H20 Monitor Method Record. SubDataCode begins with "FSP75")

H20 Fuel Specific Missing Data = true

if CH20 Method Code == 'MDF)

H20 Default Record Count = count active MonitoringDefaultData Records for the location where ParameterCd =
'H20'

if (H20 Default Record Count == 0)

return result B
else if (H20 Default Record Count >1)

if (H20 Derived Hourly Count ==1)

Current Hourly H20 Table Reference = DerivedHourlyValueData where ParameterCode =

return result A

H20 Method Code = "MTB

Environmental Protection Agency

Page 497 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

"H20"

H20 Default Max Value = Highest DefaultValue field from active MonitoringDefaultData record for
location where ParameterCd = 'H20'

H20 Default Min Value = Lowest DefaultValue field from active MonitoringDefaultData record for
location where ParameterCd = 'H20'

If CH20 Default Max Value <= 0 OR H20 Default Min Value <= 0 OR H20 Default Max Value >=100
OR H20 Default Min Value >= 100)
return result C

H20 Default Value = DefaultValue field from active MonitoringDefaultData record for location where
ParameterCd = 'H20'

If CH20 Default Value <= 0 OR H20 Default Value >= 100)
return result C

else if (II2() Method Code == "MWD")

if (H20 Derived Hourly Count ==1)

Current Hourly H20 Table Reference = DerivedHourlyValueData where ParameterCode = "H20"
H20 Reported Value = Current Hourly H20 JaWeife/erence.AdjustedHourlyValue

else if {H20 Method Code == "MMS" OR H20 Method Code == "MTB")
if (H20 Monitor Hourly Count ==1)

Current Hourly H20 Table Reference = MonitorHourlyValueData where ParameterCode = "H20"
H20 Reported Value = Current Hourly H20 JaWeife/erence UnadjustedHourlyValue

else

Results:

Result
A

Response

You have reported more than one active H20 Method record in your monitoring plan
for this hour.

You reported an H20 MethodCode of MDF, but you did not report an active H20
default record in your monitoring plan for the hour.

The DefaultValue reported in the active H20 default record in your monitoring plan is
invalid.

Severity

Critical Error Level 1

B

Critical Error Level 1

C

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 498 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-6

Check Name:

Verify NOx Rate Monitor Method

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

If (Derived Hourly Checks Needed)

NOx Rate Bypass Code = null
NOx Rate Fuel Specific Missing Data = false
Current NOx Rate Monitor Method Record = null
Current NOx Rate Method Code = null

NOx Rate Method Count = Active records in MonitoringMethodData for the location where
ParameterCode = "NOXR"

if (NOx Rate Method Count >1)

return result A
else if NOx Rate Method Count == 1

if (LME HI Method is not null)

Current NOx Rate Monitor Method Record = the single matched record
Current NOx Rate Method Code = Current NOx Rate Monitor Method Record MethodCode
NOx Rate Bypass Code = Current NOx Rate Monitor Method ifecorrf.BypassApproachCode
if (Current NOx Rate Monitor Methodifecorrf.SubDataCode begins with "FSP75")
NOx Rate Fuel Specific Missing Data = true

If (Current Unit is ARP == true)

Expected Summary Value NOx Rate Array for this location = true

return result B

else

Results:

Result
A

Response

You reported more than one active NOXR Method record in your monitoring plan for
this hour.

You reported a [param] method, which is not valid for a location that is part of a
configuration of LME units.

Severity

Critical Error Level 1

B

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 499 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-7

Check Name:

Verify NOx Mass Monitor Method Record

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (Derived Hourly Checks Needed)

Current NOx Mass Monitor Method Record = null

NOx Mass Method Active For Hour = false

NOx Mass Monitor Method Code = null

NOx Mass Bypass Code = null

NOx Mass Fuel Specific Missing Data = false

NOx Mass Method Count = Active records in MonitoringMethodData for the location where
ParameterCode = "NOX" or "NOXM"

if (NOx Mass Method Count >1)

return result A
else if NOx Mass Method Count == 1

Current NOx Mass Monitor Method Record = the single matched record

NOx Mass Monitor Method Code = NOx Mass Monitor Method Record MethodCode

if (LME HI Method is not null AND NOx Mass Monitor Method Code o "LME")
return result B

else

Expected Summary Value NOx Mass Array for this location = true

NOx Mass Bypass Code = Current NOx Mass Monitor Method ifecorrf.BypassApproachCode
if (Current NOx Mass Monitor Method Record. SubDataCode begins with "FSP75")
NOx Mass Fuel Specific Missing Data = true

if (NOx Mass Monitor Method Record. MethodCode == "CEM" OR

NOx Mass Monitor Method RecordMethodCode == "NOXR" OR
NOx Mass Monitor Method RecordMethodCode == "CEMNOXR" OR
NOx Mass Monitor Method Record MethodCode == "AMS")

NOx Mass Method Active For Hour = true

If (NOx Mass Monitor Method Code == "LME" AND Current Unit is ARP == true)
Expected Summary Value NOx Rate Array for this location = true

Results:

Result
A

Response

You reported more than one active NOX Method record in your monitoring plan for this
hour.

You reported an invalid [param] method for a location that is part of a configuration of
LME units.

Severity

Critical Error Level 1

B

Critical Error Level 1

Environmental Protection Agency

Page 500 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 501 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-8

Check Name:

Verify C02 Method Active During Current Hour

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (Derived Hourly Checks Needed)

C02 Monitor Method Record = null
CO2 CEM Method Active For Hour = false
C02 App D Method Active For Hour = false
CO2 Fuel Specific Missing Data = false
CO2 Method Code = null

11 AD and CEMs are possible method codes

C02 Method Count = Active records in MonitoringMethodData for the location where
ParameterCode = "C02" or "C02M"

if (C02 Method Count >1)

else if CO2 Method Count == 1

CO2 Monitor Method Record = the single matched record
CO2 Method Code = C02 Monitor Method ifecorrf.MethodCode

if (LME HI Method is not null and C02 Method Code is not equal to "LME")

if (Current C02 Monitor Methoditecortf.SubDataCode begins with "FSP75")
CO2 Fuel Specific Missing Data = true

if (C02 Monitor Method ifecorrf MethodCode == "CEM")

CO2 CEM Method Active For Hour = true
else if (C02 Monitor Method Record MethodCode == "AD")

C02 App D Method Active For Hour = true

Expected Summary Value C02 Array for this location = true

return result A

return result B

else

Results:

Result
A

Response

You have reported more than one active C02 Method record in your monitoring plan for
this hour.

You reported an invalid [param] method for a location that is part of a configuration of
LME units.

Severity

Critical Error Level 1

B

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 502 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-9

Check Name:

Verify Heat Input Method Active During Current hour

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

If (Derived Hourly Checks Needed)

Heat Input Monitor Method Record = null
Heat Input Fuel Specific Missing Data = false
Heat Input Method Code = null
Heat Input CEM Meth od A ctive For Hour = fal se
Heat Input App D Method Active For Hour = false

Heat Input Method Count = Active records in MonitoringMethodData for the location where
ParameterCode begins with "HI"

if (Heat Input Method Count > 1)

return result A

else if (LME HI Method is not null AND (Heat Input Method Count == 0 OR ParameterCode in the matched record is not equal to
"HIT"))

return result B

else if {Heat Input Method Count == 1)

Heat Input Monitor Method Record = the single matched record

Heat Input Method Code = Heat Input Monitor Method ifecorrf.MethodCode

LME HI Substitute Data Code = Heat Input Monitor Method ifecortf.SubstituteDataCode

if (Heat Input Monitor Method Record.SubDataCode begins with "FSP75")

Heat Input Fuel Specific Missing Data = true

if (Heat Input Monitor Method Record MethodCode == "CEM")

Heat Input CEM Method Active For Hour = true
else i I (Heat Input .Monitor Met had Record. MethodCode == "AD" OR Heat Input Monitor MethodRecordMethodCode
== "ADCALC")

Heat Input App D Method Active For Hour = true

If (Heat Input Monitor Method Record MethodCode <> "EXP")

Expected Summary Value HI Array for this location = true

if (Heat Input Monitor Method ifecorrf.ParameterCode == "HI")

Apportionment HI Method Array for this location = Heat Input Method Code

Results:

Result
A

Response

You have reported more than one active HI Method record in your monitoring plan for
this hour.

You did not report an HIT Method record for this location in your monitoring plan,
which is required for all locations that are part of a configuration of LME units.

Severity

Critical Error Level 1

B

Critical Error Level 1

Environmental Protection Agency

Page 503 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 504 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-17

Check Name:

Verify Single S02 Derived Hourly Data Record

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (Derived Hourly Checks Needed == true)
S02 Derived Checks Needed = false
S02M Derived Checks Needed = false
Current S02 Derived Hourly Record = null
F23 Default Max Value = null
F23 Default Min Value = null
F23 Default Value = null

S02 Derived Hourly Count = count of DerivedHourlyValueData records with ParameterCode = "S02" or "S02M" where
Current Date = DerivedHourly ValueData.Date and
Current Hour = DerivedHourly ValueData.Hour

Else if (S02 Derived Hourly Count > 0 AND S02 Method Code is null)

Rpt Period S02 Mass Reported Accumulator Array for the location = -1
Rpt Period S02 Mass Calculated Accumulator Array for the location = -1
return result B
Else if (S02 DerivedHourly Count > 1)

Rpt Period S02 Mass Reported Accumulator Array for the location = -1
Rpt Period S02 Mass Calculated Accumulator Array for the location = -1
return result C

Else if (S02 Derived Hourly Count > 0 AND S02 Method Code == "AD" AND Hourly Fuel Flow Count for Gas +
Hourly Fuel Flow Count for Oil == 0)

Rpt Period S02 Mass Reported Accumulator Array for the location = -1
Rpt Period S02 Mass Calculated Accumulator Array for the location = -1
return result G
Else if (S02 Derived Hourly Count == 1)

Current S02 Derived Hourly Record = DerivedHourlyValueData rec matching with param S02 or S02M where

Current Date = DerivedHourly ValueData.Date and Current Hour = DerivedHourly ValueData.Hour

If (LME HI Method is not null)

If (S02 Method Code == "LME")

If (Current S02 Derived Hourly ifecortf.ParameterCode == "S02M")
S02M Derived Checks Needed = true

else

Rpt Period S02 Mass Reported Accumulator Array for the location = -1
Rpt Period S02 Mass Calculated Accumulator Array for the location = -1
return result H

else

Rpt Period S02 Mass Reported Accumulator Array for the location = -1
Rpt Period S02 Mass Calculated Accumulator Array for the location = -1

Environmental Protection Agency

Page 505 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

If (Current S02 Derived Hourly itecortf.ParameterCode == "S02M")

Rpt Period S02 Mass Reported Accumulator Array for the location = -1
Rpt Period S02 Mass Calculated Accumulator Array for the location = -1
return result H

else

S02 Derived Checks Needed = true

If (S02 Method Code in set {CEMF23AMS})

if {S02 Method Code == "CEMF23")

S02 CEM Method Active For Hour = true

if (Current S02 Derived Hourly ifecorrf.Formulaldentifier is not null)

S02 Formula Record = MonitorFormulaData record where

MonitorFormulaData.FormulalD = Current S02 Derived Hourly
Record Formulaldentifier

If (S02 Formula Record is not null)

If (S02 Formula Record.ParameterCode == "S02")

if (S02 Method Code == "CEMF23")

If (S02 Formula Record.EquationCode == "F-23")
S02 F23 Method Active For Hour = true
S02 CEM Method Active For Hour = false

if (S02 Method Code == "AMS")

If (S02 Formula Record.EquationCode in set
{F-l,F-2})

S02 Method Code == "CEM"

S02 CEM Method Active For Hour = true

If (S02 F23 Method Active For Hour == true)

F23 Default Record Count = count active MonitoringDefaultData Records for the location
where ParameterCd = 'S02R' and DefaultPurposeCd = 'F23'

if (F23 Default Record Count == 0)

return result D
else if (F23 Default Record Count >1)

F23 Default Max Value = Highest DefaultValue field from active
MonitoringDefaultData record for location where ParameterCd = 'S02R' and
DefaultPurposeCd = 'F23'

F23 Default Min Value = Lowest DefaultValue field from active
MonitoringDefaultData record for location where ParameterCd = 'S02R' and
DefaultPurposeCd = 'F23'

If (F23 Default Max Value <= 0 OR F23 Default Min Value <= 0)
return result E

else

F23 Default Value = DefaultValue field from active MonitoringDefaultData
record for location where ParameterCd = 'S02R' and DefaultPurposeCd = 'F23'

Environmental Protection Agency

Page 506 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (F23 Default Value <= 0)
return result E

else

If SO2 Derived Hourly Count > 0
Return result F

Results:

Result

A

B

C
D

E

F

G

H

Usage:

1

Response

You did not report a DHV record for S02 (or S02M) for the hour.

You reported a DHV record for S02 (or S02M), but you did not report an active S02

method record in your monitoring plan for the hour.

You reported more than one DHV records for S02 (or S02M) for the hour.

You did not report an active S02R default record in your monitoring plan for use in F23

calculation for the hour.

The DefaultValue reported in the active S02R F23 default record in your monitoring
plan is invalid.

You reported a DHV record for S02 (or S02M), but this is not appropriate for a
non-operating hour.

You reported a DHV record for [param], but you did not report any Hourly Fuel Flow
records at the location.

The ParameterCode reported in the DHV record does not match the ParameterCode in
the Method record in your monitoring plan used to determine [eparam].

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 507 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-18

Check Name:	Verify Single S02 Concentration record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current S02 Monitor Hourly Record = null

S02 Monitor Hourly Count = count of MonitorHourlyValueDate records with param "S02C" where
Current Date = MonitorHourlyValueData.Date and
Current Hour = MonitorHourlyValueData.Hour
If Unit Hourly Operational Status = true

If (S02 Monitor Hourly Count >0 AND S02 CEM Method Active For Hour == false)

Return result A
Else if (SO2 Monitor Hourly Count >1)

Return result B

Else if (SO 2 Monitor Hourly Count ==1 AND S02 CEM Method Active For Hour == true)

Current S02 Monitor Hourly Record = MonitorHourly ValueData rec with param S02C where
CurrentDate = MonitorHourlyValueData.Date and
CurrentHour = MonitorHourlyValueData.Hour

Else

if (S02 Monitor Hourly Count > 0)
return result C

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Results:

Result	Response

A	You reported an MHV record for S02C, but you did not report an active S02 method

record in your monitoring plan for the hour.

B	You reported more than one MHV record for S02C for the hour.

C	You reported an MHV record for S02C, but this is not appropriate for a non-operating

hour.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 508 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-19

Check Name:	Verify Single NOx Concentration Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current NOx Cone Monitor Hourly Record = null

NOx Cone Monitor Hourly Count = count of MonitorHourlyValueDate records with param "NOXC" where
Current Date = MonitorHourlyValueData.Date and
Current Hour = MonitorHourlyValueData.Hour

if Unit Hourly Operational Status = true

if (NOx Cone Monitor Hourly Count >1)

Return result A
Else if (NOx Cone Monitor Hourly Count ==1)

If (NOx Mass Monitor Method Code in {CEM, CEMNOXR, AMS} OR Current NOx Rate Method Code in
{CEMAMS})

Current NOx Cone Monitor Hourly Record = MonitorHourlyValueData rec with param "NOXC" where
CurrentDate = MonitorHourlyValueData.Date and
CurrentHour = MonitorHourlyValueData.Hour

else

return result B

Else

if (NOx Cone Monitor Hourly Count > 0)
return result C

Results:

Result	Response

A	You reported more than one MHV record for NOXC for the hour.

B	You reported an MHV record for NOXC, but you did not report an appropriate NOXR

or NOX method record in your monitoring plan for the hour.

C	You reported an MHV record for NOXC, but this is not appropriate for a non-operating

hour.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 509 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-20

Check Name:

Verify Single NOx Rate Derived Hourly Record

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (Derived Hourly Checks Needed == true)

NOx Rate Derived Checks Needed = false

NOx Rate Derived Hourly Count = count of DerivedHourlyValueData records with ParameterCode = "NOXR" where

Current Date = DerivedHourlyValueData.Date and
Current Hour = DerivedHourlyValueData.Hour

If Current Hourly Op itecortf.OperatingTime > 0

If (NOx Rate Derived Hourly Count == 0 AND Current NOx Rate Method Code is not null)

Return result A

Else if (NOx Rate Derived Hourly Count > 0 AND Current NOx Rate Method Code is NULL)

Rpt Period NOx Rate Reported Accumulator Array for the location = -1
Rpt Period NOx Rate Calculated Accumulator Array for the location = -1
Return result B
Else if (NOx Rate Derived Hourly Count >1)

Rpt Period NOx Rate Reported Accumulator Array for the location = -1
Rpt Period NOx Rate Calculated Accumulator Array for the location = -1
Return result C
Else if (NOx Rate Derived Hourly Count ==1)

Current NOx Rate Derived Hourly Record = DerivedHourlyValueData rec matching param NOXR
NOx Rate Derived Checks Needed = true

Apportionment NOXR Method Array at this location = Current NOx Rate Method Code
If (Current NOx Rate Method Code == "AMS")

if (Current NOx Rate Derived Hourly itecortf.Formulaldentifier is null)

if Current NOx Rate Derived Hourly Record.)CCodc is not null)

Current NOx Rate Method Code = "CEM"

else

NOXR Formula Record = MonitorFormulaData record where

MonitorFormulaData.FormulalD = Current NOx Rate Derived Hourly
Record Formulaldentifier

If (NOXR Formula Record is not null)

If (NOXR Formula Record.ParameterCode == "NOXR" AND NOXR Formula
Record.EquationCode in set

{F-5, F-6,19-1,19-2,19-3,19-3D, 19-4,19-5,19- 5D, 19-6,19-7,19-8,19-9})

Current NOx Rate Method Code = "CEM"

else

If NOx Rate Derived Hourly Count > 0
Return result D

Environmental Protection Agency

Page 510 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

A

B

C
D

Response

You did not report a DHV record for NOXR for the hour.

You reported a DHV record for NOXR, but you did not report an active NOXR method

record in your monitoring plan for the hour.

You reported more than one DHV record for NOXR for the hour.

You reported a DHV record for NOXR, but this is not appropriate for a non-operating

hour.

This check result is obsolete.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

No Errors

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 511 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-21

Check Name:

Verify Single NOx Mass Derived Hourly Record

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (Derived Hourly Checks Needed == true)

NOx Mass Derived Checks Needed = false
NOXM Derived Checks Needed = false
Current NOx Mass Derived Hourly Record = null

NOx Mass Derived Hourly Count = count of DerivedHourlyValueData records with ParameterCode = "NOX" or "NOXM" where

Current Date = DerivedHourly ValueData.Date and
Current Hour = DerivedHourly ValueData.Hour

If Current Hourly Op ifecorrf.OperatingTime > 0

If (NOx Mass Derived Hourly Count == 0 AND (NOx Mass Method Active For Hour == true OR NOx Mass Monitor
Method Code == "LME"))

Else if (NOx Mass Derived Hourly Count > 0 AND NOx Mass Method Active For Hour == false AND NOx Mass
Monitor Method Code o "LME")

Rpt Period NOx Mass Reported Accumulator Array for the location = -1
Rpt Period NOx Mass Calculated Accumulator Array for the location = -1
Return result B

Else if (NOx Mass Derived Hourly Count >1)

Rpt Period NOx Mass Reported Accumulator Array for the location = -1
Rpt Period NOx Mass Calculated Accumulator Array for the location = -1
Return result C

Else if (NOx Mass Derived Hourly Count > 0 AND Current NOx Rate Method Code == "AE" AND Hourly Fuel Flow
Count for Gas + Hourly Fuel Flow Count for Oil == 0)

Rpt Period NOx Mass Reported Accumulator Array for the location = -1
Rpt Period NOx Mass Calculated Accumulator Array for the location = -1
Return result E

Else if (NOx Mass Derived Hourly Count ==1)

Current NOX Mass Derived Hourly Record = DerivedHourlyValueData rec matching with param NOX or
NOXM where Current Date = DerivedHourly ValueData.Date and Current Hour =

DerivedHourly ValueData.Hour

If (LME HI Method is not null)

If (NOx Mass Monitor Method Code == "LME")

Return result A

if (Current NOX Mass Derived Hourly itecortf.ParameterCode == "NOXM")
NOXM Derived Checks Needed = true

else

Rpt Period NOx Mass Reported Accumulator Array for the location = -1
Rpt Period NOx Mass Calculated Accumulator Array for the location = -1
retunr result F

else

Rpt Period NOx Mass Reported Accumulator Array for the location = -1
Rpt Period NOx Mass Calculated Accumulator Array for the location = -1

else

Environmental Protection Agency

Page 512 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (Current NOX Mass Derived Hourly ifecortf.ParameterCode == "NOXM")

Rpt Period NOx Mass Reported Accumulator Array for the location = -1
Rpt Period NOx Mass Calculated Accumulator Array for the location = -1
retunr result F

else

NOx Mass Derived Checks Needed = true

I iTYO.v Mass Monitor Method Code in set {AMS, CEMNOXR})

If (NOx Rate Derived Hourly Count > 0)

NOx Mass Monitor Method Code = "NOXR"

Else if (NOx Mass Monitor Method Code == "CEMNOXR")

NOx Mass Monitor Method Code == "CEM"

Else if (Current NOx Mass Derived Hourly ifecorrf.Formulaldentifier is not null)

NOX Formula Record = MonitorFormulaData record where

MonitorFormulaData.FormulalD = Current NOx Mass Derived Hourly
Record Formulaldentifier

If (NOX Formula Record is not null)

Apportionment NOX Method Array at this location = NOx Mass Monitor Method Code

If (NOX Formula Record.ParameterCode == "NOX" AND NOX
Formula Record.EquationCode in set {F-26A,F-26B})
NOx Mass Monitor Method Code = "CEM"

else

If NOx Mass Derived Hourly Count > 0
Return result D

Results:

Result

A

B

Response

You did not report a DHV record for NOX (or NOXM) for the hour.

You reported a DHV record for NOX (or NOXM), but you did not report an active
NOX (or NOXM) method record in your monitoring plan for the hour.

You reported more than one DHV record for NOX (or NOXM) for the hour.
You reported a DHV record for NOX (or NOXM), but this is not appropriate for a
non-operating hour.

You reported a DHV record for [param], but you did not report any Hourly Fuel Flow
records at the location.

The ParameterCode reported in the DHV record does not match the ParameterCode in
the Method record in your monitoring plan used to determine [eparam].

Severity

Critical Error Level 1
Critical Error Level 1

C
D

Critical Error Level 1
Critical Error Level 1

E

Critical Error Level 1

F

Critical Error Level 1

Environmental Protection Agency

Page 513 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 514 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-22

Check Name:	Verify Single C02 Mass Derived Hourly Value Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

If (Derived Hourly Checks Needed == true)

CO2 Mass Derived Checks Needed = false
Current C02 Mass Derived Hourly Record = null
C02M Derived Checks Needed = false

C02 Mass Derived Hourly Count = count of DerivedHourlyValueData records with ParameterCode beginning with "C02" where

Current Date = DerivedHourly ValueData.Date and
Current Hour = DerivedHourly ValueData.Hour

If Current Hourly Op ifecorrf.OperatingTime > 0

If (C02 Mass Derived Hourly Count == 0 AND C02 Method Code is not null AND C02 Method Code o "FSA")
If (CO2 Method Code == "AD")

If (Hourly Fuel Flow Count for Gas + Hourly Fuel Flow Count for Oil > 0)
return result A

else

Return result A

Else if (CO2 Mass Derived Hourly Count > 0 AND (CO2 Method Code is null OR C02 Method Code == "FSA"))
Rpt Period C02 Mass Reported Accumulator Array for the location = -1
Rpt Period C02 Mass Calculated Accumulator Array for the location = -1
return result B
Else if (C02 Mass Derived Hourly Count >1)

Rpt Period C02 Mass Reported Accumulator Array for the location = -1
Rpt Period C02 Mass Calculated Accumulator Array for the location = -1
Return result C

Else if (CO 2 Mass Derived Hourly Count > 0 AND CO 2 Method Code == "AD" AND Hourly Fuel Flow Count for
Gas + Hourly Fuel Flow Count for Oil == 0)

Rpt Period C02 Mass Reported Accumulator Array for the location = -1
Rpt Period C02 Mass Calculated Accumulator Array for the location = -1
Return result E
Else if (C02 Mass Derived Hourly Count ==1)

Current C02 Mass Derived Hourly Record = DerivedHourlyValueData rec matching with param C02 or C02M
where Current Date = DerivedHourly ValueData.Date and Current Hour = DerivedHourly ValueData.Hour

If (LME HI Method is not null)

If (CO2 Method Code == "LME")

if (Current C02 Mass DerivedHourly ifecortf.ParameterCode == "C02M")
C02M Derived Checks Needed = true

else

Rpt Period C02 Mass Reported Accumulator Array for the location = -1
Rpt Period C02 Mass Calculated Accumulator Array for the location = -1
return result F

else

Rpt Period C02 Mass Reported Accumulator Array for the location = -1
Rpt Period C02 Mass Calculated Accumulator Array for the location =-1

else

if (Current C02 Mass Derived Hourly ifecorrf.ParameterCode == "C02M")

Rpt Period C02 Mass Reported Accumulator Array for the location = -1
Rpt Period C02 Mass Calculated Accumulator Array for the location =-1

Environmental Protection Agency

Page 515 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result F

else

CO2 Mass Derived Checks Needed = true

If (C02 Method Code == "AMS")

if (Current C02 Mass Derived Hourly itecortf.Formulaldentifier is not null)

C02 Formula Record = MonitorFormulaData record where

MonitorFormulaData.FormulalD = Current C02 Mass Derived Hourly
Record Formulaldentifier

If (C02 Formula Record is not null)

If (C02 Formula Record.ParameterCode == "C02" AND C02 Formula
Record.EquationCode in set {F-2,F-11})

C02 Method Code == "CEM"

C02 CEM Method Active For Hour = true

Else

If C02 Mass Derived Hourly Count > 0
Return result D

Results:

Result

A

B

C
D

E

F

Response

You did not report a DHV record for C02 (or C02M) for the hour.

You reported a DHV record for C02 (or C02M), but you did not report an active C02

(or C02M) method record in your monitoring plan for the hour.

You reported more than one DHV records for C02 (or C02M) for the hour.

You reported a DHV record for C02 (or C02M), but this is not appropriate for a

non-operating hour.

You reported a DHV record for [param], but you did not report any Hourly Fuel Flow
records at the location.

The ParameterCode reported in the DHV record does not match the ParameterCode in
the Method record in your monitoring plan used to determine [eparam].

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 516 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-23

Check Name:

Verify C02 Cone Derived and Monitor Hourly Data Record

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Current C02 Cone Derived Hourly Record = null

Current C02 Cone Monitor Hourly Record = null

Current C02 Cone Missing Data Monitor Hourly Record = null

CO2 Cone Derived Checks Needed = false

CO2 Cone Monitor Checks Needed = false

02 Dry Needed to Support C02 Calculation = false

02 Wet Needed to Support C02 Calculation = false

C02 Cone Derived Hourly Count = count of DerivedHourlyValueData records with ParameterCode = "C02C" where

Current Date = DerivedHourly ValueData.Date and
Current Hour = DerivedHourly ValueData.Hour

C02 Cone Monitor Hourly Count = count of MonitorHourlyValueData records with ParameterCode = "C02C" where

Current Date = MonitorHourly ValueData.Date and
Current Hour = MonitorHourly ValueData.Hour

Total C02 Cone Records = C02 Cone Derived Hourly Count + C02 Cone Monitor Hourly Count

If {Current Hourly Op ifecorrf.OperatingTime > 0)

If (CO 2 Cone Checks Needed for Heat Input == true OR CO 2 Diluent Checks Needed for NOx Rate Calc == true OR CO 2 Cone
Checks Neededfor CO2 Mass Calc = true)

else if (CO2 Cone Monitor Hourly Count == 2 AND C02 Cone Derived Hourly Count == 0 AND CO2 Diluent Checks
Needed for NOx Rate Calc == true AND (CO 2 Cone Checks Needed for Heat Input == true OR C02 Cone Checks
Needed for C02 Mass Calc = true)

Current C02 Cone Monitor Hourly Record = Find MonitorHourlyValueData records with ParameterCode =
"C02C" and MODCCode in set {01, 02, 03, 04, 53, 54} where
Current Date = MonitorHourly ValueData.Date and
Current Hour = MonitorHourly ValueData.Hour

Current C02 Cone Missing Data Monitor Hourly Record = Find MonitorHourlyValueData records with
ParameterCode = "C02C" and MODCCode not in set {01, 02, 03, 04, 54} where
Current Date = MonitorHourly ValueData.Date and
Current Hour = MonitorHourly ValueData.Hour

If (Current C02 Cone Monitor Hourly Record is null OR Current C02 Cone Missing Data Monitor Hourly
Record is null)

return result C

else

CO2 Cone Monitor Checks Needed = true

If (CO 2 Cone Monitor Hourly Count == 0 AND (CO 2 Cone Checks Needed for Heat Input == true OR CO 2 Diluent
Checks Needed for NOx Rate Calc == true))
return result B

else if (Total C02 Cone Records == 0)

return result A

Environmental Protection Agency

Page 517 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else if (Total C02 Cone Records > 1)
return result C

else if (CO 2 Cone Derived Hourly Count == 1)

CO2 Cone Derived Checks Needed = true

Current C02 Cone Derived Hourly Record = matching DerivedHourly ValueData rec

if (Current C02 Cone Derived Hourly Record.M()\ )CCodc in set {01, 02, 03, 04, 05, 21, 53, 54}

Fc Factor Needed = true
I'd Factor Needed = true

If (Current C02 Cone DerivedHourly ifecortf.Formula Id Key is not null)

else if (CO2 Cone Monitor Hourly Count ==1)

CO2 Cone Monitor Checks Needed = true

Current C02 Cone Monitor Hourly Record = matching MonitorHourlyValueData rec

C02C Formula record = Find MonitoringFormulaData record where

MonitoringFormulalDKey = Current C02 Cone Derived Hourly
itecortf.Formula Id Key

If (C02C Formula record is not null)

If (C02CFormula recoraf.ParameterCode == "C02C")

If (C02C Formula record.EquationCode == "F-14A")

02 Dry Needed to Support C02 Calculation = true

else if(C02C Formula record.EquationCode == "F-14B")
02 Wet Needed to Support C02 Calculation = true
Moisture Needed = true

else

If (Total C02 Cone Records > 0)

Return result D

else

If (Total C02 Cone Records > 0)

Return result E

Results:

Result

Response

You did not report a MHV or DHV record for C02C for the hour.

You did not report an MHV record for C02C for the hour.

You reported more than one MHV and/or DHV records for C02C for the hour.

You reported a MHV or DHV record for C02C, but this record is not required to

calculate emissions.

You reported a MHV or DHV record for C02C, but this is not appropriate for a
non-operating hour.

Severity

A
B
C
D

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Non-Critical Error

E

Critical Error Level 1

Environmental Protection Agency

Page 518 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Unit-Level Evaluation

Environmental Protection Agency

Page 519 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-24

Check Name:

Count Hourly Fuel Flow Records

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

If (Derived Hourly Checks Needed == true)

Hourly Fuel Flow Count For Oil = 0
Hourly Fuel Flow Count For Gas = 0

Appendix D Method Active = Heat Input App D Method Active For Hour OR

C02 App D Method Active For Hour OR
S02 App D Method Active For Hour

Hourly Fuel Flow List = set of all DerivedHourlyValueData records

Current Date = DerivedHourlyValueData.Date and
Current Hour = DerivedHourlyValueData.Hour

For each record (Current Hourly Fuel Flow Record) in Hourly Fuel Flow List

Cur Fuel Code = Current Hourly Fuel Flow RecordsuelCode
if (Cur Fuel Code is null)
return result D

Current Fuel Group = select FuelGroupCode from FuelCode Table where FuelCode = Cur Fuel Code

if (Current Fuel Group is null)

return result D
else If Current Fuel Group == "GAS"

Add 1 to Hourly Fuel Flow Count For Gas
else if Current Fuel Group == "OIL"

Add 1 to Hourly Fuel Flow Count For Oil

Hourly Fuel Flow Count = Hourly Fuel Flow Count For Gas + Hourly Fuel Flow Count For Oil

If (Current Hourly Op ifecortf.LocationName begins with "CP")

CP Fuel Count = CP Fuel Count + Hourly Fuel Flow Count

If (Current Hourly Op /feewrf. O p e r a t i n g T i m e 0)

if (Appendix D Method Active = true AND Hourly Fuel Flow Count == 0 AND MP Pipe Config for Hourly Checks is
null)

Return result B

else if (Appendix D Method Active = false AND Hourly Fuel Flow Count >0)

If (Hourly Fuel Flow Count > 0)
Return result A

else

return result C

Environmental Protection Agency

Page 520 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A
B
C

D

Response

You reported an HFF record, but this is not appropriate for a non-operating hour.
You did not report an HFF record for the hour.

You reported a FtFF record, but you did not report an active AD or AE method record in
your monitoring plan for the hour.

The Fuel Code reported in the FtFF record is missing or invalid.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Operating Ftour Evaluation

Environmental Protection Agency

Page 521 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-30

Check Name:

Determine Load Based Status of unit

Related Former Checks:

Applicability:

General Check

Description:

Specifications:

Unit is Load Based = false

Location Name = Current Monitor Plan Location ifecorrf.LOCATION NAME

if the Location Name begins with "CS" or "CP" or "MS" or "MP"

Locate all Unit Stack Configuration records where the stack/pipe location is the monitoring location, the BeginDate is on or before
the Current Date, and the EndDate is null or is on or after the Current Date.

If the NonLoadBasedlndicator in all of the retrieved records is equal to 1,

Unit is Load Based = false

else

Unit is Load Based = true

else 11 current location is a unit

if the NonLoadBasedlndicator field for the unit = 1
Unit is Load Based = false

else

Unit is Load Based = true

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 522 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-32

Check Name:	Perform Load Checks for Operating Hour

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

if (Current Hourly Op Record is not null)

Apportionment OpTime Array for this location = Current Hourly Op ifecorrf.OperatingTime
Apportionment Load Array for this Location = Current Hourly Op ifecorrf.HourlyLoad

if (Unit is Load Based == true and Current Hourly Op ifecorrf.OperatingTime > 0.0)

if (Current Hourly Op ifecorrf.HourLoad is null OR Current Hourly Op itecortf.HourLoad < 0)
if (Current Entity Type = "Unit")

Unit LoadTimesOpTime Accumulator = -1
else if (Current Entity Type in set {CP, MP})

Pipe LoadTimes OpTime Accumulator = -1

else

Stack LoadTimesOpTime Accumulator = -1
return result A

else

if (MP Stack Config for Hourly Checks == "MS" AND Current Entity Type == "Unit")
MP Unit Load = Current Hourly Op RecordHomLo&A

if (Current Entity Type = "Unit")

if (Unit LoadTimesOpTime Accumulator >= 0)

Unit LoadTimesOpTime Accumulator = Unit LoadTimesOpTime Accumulator +

(Current Hourly Op Record.\ lour Load * Current Hourly Op ifecortf.OperatingTime)

else if (Current Entity Type in set {CP, MP})

if (Pipe LoadTimesOpTime Accumulator >= 0)

Pipe LoadTimesOpTime Accumulator = Pipe LoadTimesOpTime Accumulator +

(Current Hourly Op Record.\ IourLoad * Current Hourly Op ifecortf.OperatingTime)

else

if (Stack LoadTimesOpTime Accumulator >= 0)

Stack LoadTimesOpTime Accumulator = Stack LoadTimesOpTime Accumulator +

(Current Hourly Op Record.\ IourLoad * Current Hourly Op ifecortf.OperatingTime)

if Current Hourly Op Record LoadUnitsOfMeasureCode not in {"MW","KLBHR", "MMBLUELR"}

MP Load UOM = "INVALID"
return result B

else if (MP Load UOM is not null AND MP Load UOM o "INVALID" AND MP Load UOM o Current
Hourly Op Record LoadUnitsOfMeasureCode )

MP Load UOM = "INVALID"
return result C

else

if (MP Load UOM is null)

MP Load UOM = Current Hourly Op Record LoadUnitsOfMeasureCode

Locate the MonitorLoadRecordsByHourandLocation record for the hour and location.

If (only one record is found AND MonitorLoadRecordliynourandLocation. Maximum Load Value is

greater than 0),

Environmental Protection Agency

Page 523 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (Current Hourly Op itecoraJ LoadUnitsOfMeasureCode ==

Monitor LoadltecordliyffourandLocation Maximuml.oadl JnitsOfMeasureCode)

If (Current Hourly Op Record.HourLoad is greater than
Monitor Loadfiy Hour andLocat ion.Ma\\ 111 uni [ ,oad Val Lie)

return result H
else if (Current Hourly Op RecordHomLo&A == 0)

If {Current Hourly Op Record. I ,oadRange is greater than or equal to 2 OR
Current Hourly Op itecortf.CommonStackLoadRange is greater than or equal to

2)

If (Current Entity Type o "Unit" OR {MP Stack Config for Hourly
Checks o "CS" AND MP Pipe Config for Hourly Checks o "CP"))
return result K

else

return result I

else

return result J

else if {Current Hourly Op ifecorrf.OperatingTime == 0.0)

if {Current Hourly Op ifecorrf.HourLoad is not null)
return result D

if Current Hourly Op itecoraJ LoadUnitsOfMeasureCode is not null
return result E

else if {Unit is Load Based == false)

if {Current Hourly Op ifecorrf.HourLoad is not null)
return result F

if Current Hourly Op itecoraJ LoadUnitsOfMeasureCode is not null
return result G

Environmental Protection Agency

Page 524 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B
C

D

E
F
G
H

I
J
K

Usage:
1

Response

The HourLoad reported in the Hourly Operating record is invalid. The value must be
greater than or equal to 0.

The LoadUnitsOfMeasureCode reported in the Hourly Operating record is invalid.
You did not report the same LoadUnitsOfMeasureCode for all locations in the
configuration.

You reported HourLoad in the Hourly Operating record. This field should be blank for
a non-operating hour.

You reported a LoadUnitsOfMeasureCode in the Hourly Operating record. This field
should be blank for a non-operating hour.

You reported HourLoad in the Hourly Operating record. This field should be blank for
a non-load-based unit.

You reported a LoadUnitsOfMeasureCode in the Hourly Operating record. This field
should be blank for a non-load-based unit.

Warning: The HourLoad reported in the Hourly Operating Data record is higher than the
MaximumLoadValue in the Monitoring Load record reported in your monitoring plan.
Sources are required to periodically (at least once annually) evaluate the appropriateness
of these maximum values in the monitoring plan and make proper adjustments when
necessary. You should investigate the cause of these exceedances and determine
whether an adjustment to the MaximumLoadValue in your monitoring plan is necessary.
The [fieldname] does not correspond to the MaximumLoadUnitsOfMeasure reported in
the monitoring plan.

You did not have one and only one valid Monitor Load record that was active during the
hour.

The LoadRange or CommonStackLoadRange reported in the Hourly Operating record is
inconsistent with the HourLoad. When no load is generated, the load range should be
less than 2.

Severity

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Non-Critical Error

Critical Error Level 1

Critical Error Level 1

Informational Message

Critical Error Level 2
Critical Error Level 1
Informational Message

Process/Category:

Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 525 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-33

Check Name:	Check reported Fuel Code for Operating Hour

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

if (Current Hourly Op Record is not null)

Fuel Code Validation Needed = false

If (XOx Rate Fuel Specific Missing Data == true OR NOx Mass Fuel Specific Missing Data == true OR S02 Fuel Specific
Missing Data == true OR CO2 Fuel Specific Missing Data == true OR Heat Input Fuel Specific Missing Data == true OR H20
Fuel Specific Missing Data == true)

Fuel Code Validation Needed = true

else

if (Current S02 Monitor Hourly Record is not null AND S02 Bypass Code == "BYMAXFS" )
if (Current S02 Monitor Hourly Record. MOI )CCodc == 23)

Fuel Code Validation Needed = true

if {Current NOx Cone Monitor Hourly Record is not null AND XOx Mass Bypass Code== "BYMAXFS")
if (Current NOx Cone Monitor Hourly Record. MOI )CCodc in set {23,24})

Fuel Code Validation Needed = true

if (Current NOx Rate Derived Hourly Record is not null AND NOx Rate Bypass Code == "BYMAXFS" )
if (Current NOx Rate Derived Hourly RecordMODCCo&e in set {23,24})

Fuel Code Validation Needed = true

if (Fuel Code Validation Needed == true)

if {Current Hourly Op ifecorrf.FuelCode is null)

If {Current Hourly Op ifecorrf.OperatingTime is greater than 0)
return result A

else

Current Hourly Fuel Group Code = FuelGroupCode from FuelCode table entry where

FuelCode = Current Hourly Op Record. I Lie IC ode
if {Current Hourly Op Record.FuelCode = "NFS" OR

{Current Hourly Fuel Group Code == "COAL" AND Current Hourly Op Record.I uclCode o "C"))
return result B

else if {Current Hourly Op Record.VueiCode is not null)

if (S02 Bypass Code o "BYMAXFS" AND NOx Rate Bypass Code o "BYMAXFS" AND NOx Mass Bypass Code o
"BYMAXFS")

return result C

Results:

Result
A
B
C

Response

You did not report a FuelCode in the Hourly Operating record.

The FuelCode reported Hourly Operating record is invalid.

You reported a FuelCode in the Hourly Operating record. This value should only be
reported if you use fuel-specific missing data or have an unmonitored bypass stack that
reports emissions based on fuel-specific maximum values.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Environmental Protection Agency

Page 526 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 527 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-34

Check Name:

Validate Reported FC Factor

Related Former Checks:

Applicability:

General Check

Description:

Validation Tables:

F-Factor Range Checks (Cross Check Table)

Specifications:

if FC Factor Needed = true

Valid FC Factor Exists = false

if (Current Hourly Op ifecorrf.FcFactor is null)

FC Factor Minimum = Lookup Lower from Cross-Check Table "F-Factor Range Checks" where Factor = "FC"
FC Factor Maximum = Lookup Upper from Cross-Check Table "F-Factor Range Checks" where Factor = "FC"
if (Current Hourly Op ifecorrf.FcFactor > FC Factor Maximum OR Current Hourly Op ifecorrf.FcFactor < FC
Factor Minimum)

return result B

return result A

else if {Current Hourly Op RecordscSactor <= 0)
return result A

else

Valid FC Factor Exists = true
if (Special Fuel Burned = false)

Results:

Result

A

B

Response

The [FNAME] reported in the Hourly Operating record is missing or invalid.

The [FNAME] reported in the Hourly Operating record is outside of the expected range

from [MIN] to [MAX],

Severity

Critical Error Level 1
Critical Error Level 2

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Unit-Level Evaluation

Environmental Protection Agency

Page 528 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-35

Check Name:

Validate Reported FD Factor

Related Former Checks:

Applicability:

Description:

Validation Tables:

F-Factor Range Checks (Cross Check Table)

Specifications:

if II) Factor Needed = true

Valid FD Factor Exists = false

if (Current Hourly Op ifecorrf.FdFactor is null)
return result A

else if {Current Hourly Op RecordsdFactor <= 0)
return result A

else

Valid FD Factor Exists = true
if (Special Fuel Burned = false)

FD Factor Minimum = Lookup Lower from Cross-Check Table "F-Factor Range Checks" where Factor = "FD"
FD Factor Maximum = Lookup Upper from Cross-Check Table "F-Factor Range Checks" where Factor = "FD"

if {Current Hourly Op ifecorrf.FdFactor > FD Factor Maximum OR Current Hourly Op ifecorrf.FdFactor < FD
Factor Minimum)

return result B

Results:

Result

A

B

Response

The [FNAME] reported in the Hourly Operating record is missing or invalid.

The [FNAME] reported in the Hourly Operating record is outside of the expected range

from [MIN] to [MAX],

Severity

Critical Error Level 1
Critical Error Level 2

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Unit-Level Evaluation

Environmental Protection Agency

Page 529 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-36

Check Name:

Validate Reported FW Factor

Related Former Checks:

Applicability:

General Check

Description:

Validation Tables:

F-Factor Range Checks (Cross Check Table)

Specifications:

if FW Factor Needed = true

Valid FW Factor Exists = false

if (Current Hourly Op ifecorrf.FwFactor is null)
return result A

else if {Current Hourly Op Record.FwFactor <= 0)
return result A

else

Valid FW Factor Exists = true

if (Special Fuel Burned = false)

FW Factor Minimum = Lookup Lower from Cross-Check Table "F-Factor Range Checks" where Factor = "FW"
FWFactor Maximum = Lookup Upper from Cross-Check Table "F-Factor Range Checks" where Factor = "FW"

if {Current Hourly Op ifecorrf.FwFactor > FW Factor Maximum OR Current Hourly Op Record. I wl actor < FW
Factor Minimum)

return result B

Results:

Result

A

B

Response

The [FNAME] reported in the Hourly Operating record is missing or invalid.

The [FNAME] reported in the Hourly Operating record is outside of the expected range

from [MIN] to [MAX],

Severity

Critical Error Level 1
Critical Error Level 2

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Unit-Level Evaluation

Environmental Protection Agency

Page 530 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-37

Check Name:	Verify Single Heat Input Derived Hourly Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current Heat Input Derived Hourly Record= null
Heat Input Derived Checks Needed = false
HIT Derived Checks Needed = false

Heat Input Derived Hourly Count = # of DerivedHourlyValueData record with parameter beginning with "HI" where
Current Date = DerivedHourlyValueData.Date and
Current Hour = DerivedHourlyValueData.Hour

If Current Hourly Op itecortf.OperatingTime > 0
If (Heat Input Derived Hourly Count == 0)

If (Heat Input Method Code is not null)

If {Heat Input Method Code not in set {EXP, LTFF})
return result A

else if {Heat Input Method Code == "LTFF" AND Current Entity Type == "Unit")
return result A
Else if (Heat Input Derived Hourly Count > 0 AND

{Heat Input Method Code is null OR
Heat Input Method Code == "EXP" OR

{Heat Input Method Code == "LTFF" AND Current Entity Type == "CP"))

Rpt Period HI Reported Accumulator Array for the location =-1
Rpt Period HI Calculated Accumulator Array for the location = -1
return result B
Else if (Heat Input Derived Hourly Count >1)

Rpt Period HI Reported Accumulator Array for the location =-1
Rpt Period HI Calculated Accumulator Array for the location = -1
return result C

Else

Current Heat Input Derived Hourly Record= DerivedHourlyValueData record with parameter "HI" or "HIT" where
Current Date = DerivedHourlyValueData.Date and
Current Hour = DerivedHourlyValueData.Hour

If {LME HI Method is not null)

if {Current Heat Input Derived Hourly ifecorrf.ParameterCode == "HIT")

HIT Derived Checks Needed = true

else

Rpt Period HI Reported Accumulator Array for the location =-1
Rpt Period HI Calculated Accumulator Array for the location = -1
return result E

else

if {Current Heat Input Derived Hourly ifecorrf.ParameterCode == "HIT")

Rpt Period HI Reported Accumulator Array for the location =-1
Rpt Period HI Calculated Accumulator Array for the location = -1
return result E

else

Heat Input Derived Checks Needed = true
If {Heat Input Method Code == "AMS")

if {Current Heat Input Derived Hourly itecortf.Formulaldentifier is not null)

Environmental Protection Agency

Page 531 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

HI Formula Record = MonitorFormulaData record where

MonitorFormulaData.FormulalD = Current Heat Input Derived Hourly
Record. F ormulaldentifier

If (HI Formula Record is not null)

If (HI Formula Record.ParameterCode == "HI" AND HI Formula
Record.EquationCode in set {F-15,F-16,F-17,F-18})

Heat Input Method Code == "CEM"

Heat Input CEM Method Active For Hour == true

else

If Heat Input Derived Hourly Count > 0
return result D

Results:

Result

B

C
D

Response

You did not report a DHV record for HI (or HIT) for the hour. If you have entered
LME data via the LME Emissions Data Utility, this error indicates that you have not yet
generated your quarterly emissions data. You must do this by clicking on the Generate
Emissions Data link on the LME Emissions Data Utility submenu.

You reported a DHV record for HI (or HIT), but, according to the monitoring methods
in your monitoring plan, you should not report hourly heat input at this location.
You reported more than one DHV record for HI (or HIT) for the hour.

You reported a DHV record for HI (or HIT), but this is not appropriate for a
non-operating hour.

The ParameterCode reported in the DHV record does not match the ParameterCode in
the Method record in your monitoring plan used to determine [eparam].

Severity

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 532 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-38

Check Name:	Determine Fuel Type

Related Former Checks:

Applicability:	General Check

Description:

Specifications:

If (Derived Hourly Checks Needed == true)

If Current Hourly Op itecortf.FcFactor is not null OR Current Hourly Op itecortf.FdFactor is not null OR Current Hourly Op
ifecorrf.FwFactor is not null

If (Hourly Fuel Flow Count For Oil + Hourly Fuel Flow Count For Gas == 0)

If (Current Hourly Op Record.VueiCd is null OR Current Hourly Op Record.VueiCd == "MIX")

Count all active UnitFuel records for the location where
FuelCd in set {OOL, PRO, PRS, OGS}

If count > 0

Special Fuel Burned = true

else if Current Hourly Op ifecorrf.UnitFuelCd in set {OOL, PRG, PRS, OGS}

Special Fuel Burned = true

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Unit-Level Evaluation

Environmental Protection Agency

Page 533 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-39

Check Name:

Verify Single H20 Cone Derived or Monitor Hourly Data Record

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

H20 Monitor Hourly Checks Needed = false
H20 Derived Hourly Checks Needed = false
Current H20 Monitor Hourly Record = null
Current H20 Derived Hourly Record = null
02 Wet Checks Needed for H20= false
02 Dry Checks Needed for H20= false

If Current Hourly Op ifecorrf.OperatingTime > 0.00

If (Moisture Needed == true)

If H20 Monitor Hourly Count + H20 Derived Hourly Count == 0

If {H20 Method Code == "MWD")
return result A

Else if {H20 Method Code o "MDF")
return result B

Else if H20 Default Max Value is not null
return result C

Else if (H20 Derived Hourly Count > 1)
return result D

Else if (H20 Monitor Hourly Count >1)
return result E

Else if (H20 Derived Hourly Count == 1 AND H20 Method Code in set {MTB, MMS})
return result F

Else if (H20 Monitor Hourly Count == 1 AND H20 Method Code in set {MWD, MDF})
return result G

Else if (H20 Monitor Hourly Count ==1)

Current H20 Monitor Hourly Record = MonitorHourlyValueData record matching with ParameterCode = "H20"
where

Current Date = MonitorHourlyValueData.Date and
Current Hour = MonitorHourlyValueData.Hour

H20 Monitor Hourly Checks Needed = true

Else if (H20 Derived Hourly Count ==1)

Current H20 Derived Hourly Record = DerivedHourlyValueData rec matching where
DerivedHourlyValueData.ParameterCode = "H20" AND
DerivedHourlyValueData.Date = Current Date AND
DerivedHourlyValueData.Hour = Current Hour

H20 Derived Hourly Checks Needed = true

Environmental Protection Agency

Page 534 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

else

if {Current H20 Derived Hourly RecordMo&cCo&e in set {01, 02, 03, 04, 05, 21, 53, 54} AND Current H20
Derived Hourly Record Formulaldentifier is not null)

H20 Formula Record = MonitorFormulaData record where

MonitorFormulaData.FormulalD = Current H20 Derived Hourly Record Formulaldentifier

If (H20 Formula Record is not null)

If (H20 Formula Record.ParameterCode == "H20" AND H20 Formula Record.EquationCode in
set {F-31, M-1K})

02 Wet Checks Needed for H20= true
()2 Dry Checks Needed for H20= true

If H20 Monitor Hourly Count + H20 Derived Hourly Count > 0

return result H

If H20 Monitor Hourly Count + H20 Derived Hourly Count > 0
return result I

Results:

Result
A
B
C

D

E
F

G

H

I

Usage:

1

Response

You did not report a DHV record for H20 for the hour.

You did not report an MHV record for H20 for the hour.

You did not report a DHV record for H20 for the hour. You must report this record if

you have multiple H20 default values for different fuels.

You reported more than one DHV record for H20 for the hour.

You reported more than one MHV record for H20 for the hour.

You reported a DHV record for H20, but the H20 MethodCode is not "MWD" or

"MDF".

You reported a MHV record for H20, but the H20 MethodCode is not "MTB" or
"MMS".

You reported a DHV and/or MHV record for H20, but this record is not required to
calculate emissions.

You reported a DHV and/or MHV record for H20, but this is not appropriate for a
non-operating hour.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Non-Critical Error

Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report	Unit-Level Evaluation

Environmental Protection Agency

Page 535 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-40

Check Name:	Verify Single 02 Dry Monitor Hourly Value Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current 02 Dry Monitor Hourly Record = null

Current 02 Dry Missing Data Monitor Hourly Record = null

02 Dry Monitor Hourly Checks Needed = false

If Current Hourly Op ifecorrf.OperatingTime > 0.00

If (02 Dry Checks Needed for Heat Input == true OR ()2 Dry Checks Needed for NOx Rate Calc == true OR 02 Dry Checks
Needed To Support C02 Calculation == true OR 02 Dry Checks Needed for H20 == true)

If (02 Dry Monitor Hourly Count == 0 AND (02 Wet Checks Needed for Heat Input == true OR 02 Wet Checks
Needed for NOx Rate Calc == true OR 02 Wet Checks Needed To Support C02 Calculation == true OR 02 Wet Checks
Needed for H20 == true))
return result A

Else if (02 Dry Monitor Hourly Count + 02 Null Monitor Hourly Count == 0)

Return result B

Else if ((02 Dry Monitor Hourly Count + 02 Null Monitor Hourly Count > 2) OR (02 Dry Monitor Hourly Count + 02
Null Monitor Hourly Count == 2 AND 02 Wet Monitor Hourly Count + 02 Null Monitor Hourly Count == 2))

Return result C

Else if (02 Dry Monitor Hourly Count + 02 Null Monitor Hourly Count == 2)

If (02 Dry Checks Needed for Heat Input == true AND (02 Dry Checks Needed for NOx Rate Calc == true OR
02 Dry Checks Needed for H20 == true))

Current 02 Dry Monitor Hourly Record = Find MonitorHourlyValueData records with ParameterCode =
"02C" AND (MoistureBasis = "D" OR MoistureBasis is null) and MODCCode in set {01, 02, 03, 04, 53,
54} where

Current Date = MonitorHourly ValueData.Date and
Current Hour = MonitorHourly ValueData.Hour

Current 02 Dry Missing Data Monitor Hourly Record = F ind MonitorHourlyValueData records with
ParameterCode = "02C" AND (MoistureBasis = "D" OR MoistureBasis is null) and MODCCode not in
set {01, 02, 03, 04, 54} where

Current Date = MonitorHourly ValueData.Date and
Current Hour = MonitorHourly ValueData.Hour

If (Current 02 Dry Monitor Hourly Record is null OR Current 02 Dry Missing Data Monitor Hourly
Record is null)

return result C

else

02 Dry Monitor Hourly Checks Needed = true

else

return result C
Else if (02 Dry Monitor Hourly Count ==1)

02 Dry Monitor Hourly Checks Needed = true

Environmental Protection Agency

Page 536 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Current 02 Dry Monitor Hourly Record = MonitorHourly ValueData record with ParameterCode = "02C" AND
MoistureBasis = "D" where

Current Date = MonitorHourly ValueData.Date and
Current Hour = MonitorHourly ValueData.Hour

Else if (02 Null Monitor Hourly Count == 1)

02 Dry Monitor Hourly Checks Needed = true

Current 02 Dry Monitor Hourly Record = Current 02 Null Monitor Hourly Record

else

If (02 Dry Monitor Hourly Count > 0)

Return result D

If (02 Null Monitor Hourly Count > 0 AND 02 Wet Checks Needed for Heat Input == false AND 02 Wet Checks
Needed for NOx Rate Calc == false AND 02 Wet Checks Needed To Support C02 Calculation == false AND 02 Wet
Checks Needed for H20 == false)

return result E

else

If (02 Dry Monitor Hourly Count 02 + Null Monitor Hourly Count + 02 Wet Monitor Hourly Count > 0)
Return result F

Results:

Result

A

B

Response

You did not report a MHV record for 02C with a MoistureBasis of D for the hour.
You did not report a MHV record for 02C with a MoistureBasis of D (or blank) for the
hour.

You reported too many MHV records for 02C with a MoistureBasis of D (or blank) for
the hour.

You reported an MHV record for 02C with a MoistureBasis of [basis], but this record is
not required to calculate emissions.

You reported an MHV record for 02C with a blank MoistureBasis, but this record is not
required to calculate emissions.

You reported a MHV record for 02C, but this is not appropriate for a non-operating
hour.

Severity

Critical Error Level 1
Critical Error Level 1

C

Critical Error Level 1

D

Non-Critical Error

E

Non-Critical Error

F

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Unit-Level Evaluation

Environmental Protection Agency

Page 537 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-41

Check Name:	Verify Single 02 Wet Monitor Hourly Value Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current 02 Wet Monitor Hourly Record = null
Current 02 Wet Missing Data Monitor Hourly Record = null
02 Wet Monitor Hourly Checks Needed = false
If Current Hourly Op ifecorrf.OperatingTime > 0.00

If <02 Wet Checks Needed for Heat Input == true OR 02 Wet Checks Needed for NOx Rate Calc == true OR 02 Wet Checks
Needed To Support C02 Calculation == true OR ()2 Wet Checks Needed for H20 == true)

If (02 Wet Monitor Hourly Count == 0 AND (02 Dry Checks Neededfor Heat Input == true OR 02 Dry Checks
Needed for NOx Rate Calc == true OR 02 Dry Checks Needed To Support C02 Calculation == true OR 02 Dry Checks
Needed for H20 == true))
return result A

Else if (02 Wet Monitor Hourly Count + 02 Null Monitor Hourly Count == 0)

Return result B

Else if (02 Wet Monitor Hourly Count + 02 Null Monitor Hourly Count > 2)

Return result C

Else if (02 Wet Monitor Hourly Count + 02 Null Monitor Hourly Count == 2

If (02 Wet Checks Needed for Heat Input == true AND 02 Dry Monitor Hourly Count + 02 Null Monitor
Hourly Count <> 2 AND (02 Wet Checks Needed for NOx Rate Calc == true OR 02 Wet Checks Needed for
H20 == true))

Current 02 Wet Monitor Hourly Record = Find MonitorHourlyValueData records with ParameterCode =
"02C" AND (MoistureBasis = "W" OR MoistureBasis is null) and MODCCode in set {01, 02, 03, 04, 53,
54} where

Current Date = MonitorHourly ValueData.Date and
Current Hour = MonitorHourly ValueData.Hour

Current 02 Wet Missing Data Monitor Hourly Record = F ind MonitorHourlyValueData records with
ParameterCode = "02C" AND (MoistureBasis = "W" OR MoistureBasis is null) and MODCCode not in
set {01, 02, 03, 04, 54} where

Current Date = MonitorHourly ValueData.Date and
Current Hour = MonitorHourly ValueData.Hour

If (Current 02 Wet Monitor Hourly Record is null OR Current 02 Wet Missing Data Monitor Hourly
Record is null)

return result C

else

02 Wet Monitor Hourly Checks Needed = true

else

return result C
Else if (02 Wet Monitor Hourly Count == 1)

02 Wet Monitor Hourly Checks Needed = true

Current 02 Wet Monitor Hourly Record = MonitorHourlyValueData record with ParameterCode = "02C" AND

Environmental Protection Agency

Page 538 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

MoistureBasis = "W" where

Current Date = MonitorHourlyValueData.Date and
Current Hour = MonitorHourlyValueData.Hour

Else if (02 Null Monitor Hourly Count == 1)

02 Wet Monitor Hourly Checks Needed = true

Current 02 Wet Monitor Hourly Record = Current 02 Null Monitor Hourly Record

else

If (02 Wet Monitor Hourly Count > 0)

Return result D

Results:

Result	Response	Severity

A	You did not report a MHV record for 02C with a MoistureBasis of W for the hour.	Critical Error Level 1

B	You did not report a MHV record for 02C with a MoistureBasis of W (or blank) for the	Critical Error Level 1

hour.

C	You reported too many MHV records for 02C with a MoistureBasis of W (or blank) for	Critical Error Level 1

the hour.

D	You reported an MHV record for 02C with a MoistureBasis of [basis], but this record is	Non-Critical Error

not required to calculate emissions.

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Unit-Level Evaluation

Environmental Protection Agency

Page 539 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

HOUROP-42

Check Name:

Verify Single S02R Derived Hourly Data Record

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

If (Derived Hourly Checks Needed == true)

S02R Derived Checks Needed = false

S02R Derived Hourly Count = count of DerivedHourlyValueData records with ParameterCode = "S02R" where
Current Date = DerivedHourlyValueData.Date and
Current Hour = DerivedHourlyValueData.Hour

If Current Hourly Op itecortf.OperatingTime > 0

If (S02R Derived Hourly Count == 0 AND F23 Default Max Value is not null)

Return result A

Else if (S02R Derived Hourly Count > 0 AND S02 F23 Method Active For Hour == false)

Return result B
Else if (S02R Derived Hourly Count >1)

Return result C
Else if (S02R Derived Hourly Count ==1)

Current S02R Derived Hourly Record = DerivedHourlyValueData rec matching with param S02R where
Current Date = DerivedHourlyValueData.Date and
Current Horn = DerivedHourlyValueData.Hour

S02R Derived Checks Needed = true

else

If S02R Derived Hourly Count > 0
Return result D

Results:

Result

A

B

Response

You did not report a DHV record for S02R for the hour.

You reported a DHV record for S02R, but this record is not required to calculate
emissions.

You reported more than one DHV record for S02R for the hour.

You reported a DHV record for S02R, but this is not appropriate for a non-operating

hour.

Severity

Critical Error Level 1
Non-Critical Error

C
D

Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report	Operating Hour Evaluation

Environmental Protection Agency

Page 540 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	HOUROP-43

Check Name:	Validate Single Stack Flow Record

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Current Stack Flow Hourly Record= null

If Flow Monitor Hourly Checks Needed == true)

If (Flow Monitor Hourly Count == 0)

Flow Monitor Hourly Checks Needed = false
return result A
Else if (Flow Monitor Hourly Count >1)
return result B

Else

Current Stack Flow Hourly Record = MonitorHourlyValueData record with parameter FLOW where
Current Date = MonitorHourly ValueData.Date and
Current Hour = MonitorHourly ValueData.Hour

else

If Flow Monitor Hourly Count > 0
return result C

Results:

Severity

Critical Error Level 1
Critical Error Level 1
Non-Critical Error

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Unit-Level Evaluation

Result	Response

A	You did not report an MHV record for FLOW for the hour.

B	You reported more than one MHV record for FLOW for the hour.

C	You reported a MHV record for FLOW, but this record is not appropriate for the hour.

Environmental Protection Agency

Page 541 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Leak Status

Environmental Protection Agency

Page 542 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LKSTAT-1

Check Name:

Locate Most Recent Prior Leak Check

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set PriorLeakRecord = null.

Locate the most recent record in LeakCheckRecordsByLocationForQAStatus for the location where:

a)	the ComponentID is equal to the CurrentMHV. ComponentID

b)	the TestResultCd is not equal to "INVALID" and

c)	the EndDate/Hour is on or prior to the CurrentMII] 'Record.\>dlc I lour

if (LeakCheckRecordsByLocationForQAStatus is found)

Set PriorLeakRecord = the found record in LeakCheckRecordsByLocalionForQAStatus.

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report

Leak Check Status Evaluation

Environmental Protection Agency

Page 543 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LKSTAT-2

Check Name:	Locate Most Recent Prior Event

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Set PriorLeakEventRecord = null.

Set LeakStatusResu.lt = null

If (PriorLeakRecord is null)

Locate the latest record in QACertificationEventRecords where the ComponentID is equal to the Current Mil] '.Component 11).

QaCertEventCode is equal to "300" or "305", and the QACertEventDate/Hour is prior to CurrentReportingPeriod.

if (QACertificationEventRecordis found)

Set PriorLeakEventRecord = the found record in QACertificationEventRecord.

Locate the latest record in RataTestRecordsByLocationForQaStatus where the SystemID is equal to
CurrentMhvRecord.SystemID, TestReasonCode is equal to "INITIAL" or "RECERT", TestResultCode is equal to
"PASSED", and EndDateHour is after QACertificationEventRecord.QACertEverrtDate/Hour and is prior to
CurrentReportingPeriod.

if found,

Set LeakStatusResult = "OOC-Event".

else

Set LeakStatusResult = "IC".

else

Locate the SystemComponent record with the earliest BeginDate where the ComponentID is equal to the
CurrentMIH '.Component11 ).

If found, and the BeginDate in the SystemComponent record is in the current reporting period,

Set LeakStatusResult = "IC"

else

Set LeakStatusResult = "OOC-No Prior Test".

Locate the latest record in QACertificationEventRecords where the ComponentID is equal to the Current Mil] '.ComponentID.

LeakRequired is equal to "Y" and QaCertEventCode is not equal to "300", and the QACertEventDate/Hour is prior to the
CurrentMII]'Record.\)dlc I lour and after the PriorLeakRecord.\.nd\)dlc I lour.

if a record is found

Set PriorLeakEventRecord = the found record in QACertificationEventRecords.

if PriorLeakEventRecord.LastCompietedTestDate is not null

Set ExpectedLeakCheckQuarter = the quarter of PriorLeakEventRecord. I .astComplctcdTcstDatc.

else

Set ExpectedLeakCheckQuarter = the quarter after PriorLeakEventRecord.QACertEverrtDate.

Set QuartersAfterCount = 0.

For each quarter beginning with ExpectedLeakCheckQuarter and ending with CurrentReportingPeriod,
if QuartersAfterCount is equal to 4,

Environmental Protection Agency	Page 544 of 667

else


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set RequiredLeakCheckQuarter to quarter.

Exit the loop.

else if AnnualReportingRequirement equals true, or the quarter being checked is 2 or 3

if AnnualReportingRequirement equals true, or the quarter being checked is 3

Locate the record in OperatingSuppDataRecordsByLocation where OpTypeCode is equal to
"OPHOURS", FuelCode is null, and reporting period equals the quarter being checked

else

Locate the record in OperatingSuppDataRecordsByLocation where OpTypeCode is equal to
"OSHOURS", FuelCode is null, and reporting period equals the quarter being checked

if OperatingSuppDataRecordsByLocation record is found

If OperatingSuppDataRecordsByLocation.OpValue >= 168
Set RequiredLeakCheckQuarter to quarter.

Exit the loop.

else

Set RequiredLeakCheckQuarter to quarter.

Exit the loop.

Increament QuartersAfterCount by 1.

if RequiredLeakCheckQuarter is prior to CurrentReportingPeriod
Set LeakStatusResu.lt ="OOC-Event".

else

Set LeakStatusResult = "IC".

else if Pr/orLeaAifecorrf.QANeedsEvaluationFlag = " Y"

Set LeakStatusResult = "Prior Test Not Yet Evaluated".

else if PriorLeakRecord.TestResuitCd is null

Set LeakStatusResult = "OOC-Test Has Critical Errors".

else if PriorLeakRecord.TestResultCd == "FAILED"

Set LeakStatusResult = "OOC-Test Failed".

else if PriorLeakRecord. TestResultCd == "ABORTED"

Set LeakStatusResult = "OOC-Test Aborted".

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Leak Check Status Evaluation

Environmental Protection Agency

Page 545 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LKSTAT-3

Check Name:

Determine Expiration Date For Prior Leak Check

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

if (LeakStalusResuti is null)

Set PriorLeakExpiralionDale = PriorLeakRecord.! estExpimtionDate.

if (PriorLeakExpirationDate is null)

if (Annual Reporting Requirement == false)

if (PriorLeakRecord .TestEndQuarter = "2")

Set PriorLeakExpirationDate = September 30th following PriorLeakRecord .EndDate.

else

Set PriorLeakExpirationDate = June 30th following PriorLeakRecord EndDate.

else

if (PriorLeakRecord .GracePeriodlnd = 1)

Set PriorLeakExpirationDate = the end of the quarter of the PriorLeakRecord.EndD&te.

else

Set PriorLeakExpirationDate = the end of the quarter following the quarter of the PriorLeakRecord

Set PriorLeakRecord TestExpirationDate = PriorLeakExpirationDate .
if (CurrentMIII Record. I )atc is ON OR BEFORE the PriorLeakExpirationDate)
Set LeakStatusResult = "IC".

else

Set PriorLeakExpirationDate = null.

.EndDate.

Results:

Result

Response

Severity

Usage:
1

Process/Category:	Emissions Data Evaluation Report

Leak Check Status Evaluation

Environmental Protection Agency

Page 546 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LKSTAT-4

Check Name:	Determine Extended Expiration Date for Prior Leak Check

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Set LeakMissingOpDatalnfo = null,
if (LeakStatusResult is null)

Set MissingOpData = false

if (Pr/orLeaAifecorrf.TestExpirationDateWithExtension is null)

For each quarter beginning with the quarter of the PriorLeakExpiralionDale and continuing through the quarter prior to the
quarter of the CurrentMII] Record. I )atc:

if (EarliestLocationReportDate > the last day of the quarter being checked)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

else

If {Annual Reporting Requirement == true OR the quarter being checked is == 2 or 3)

If (Annual Reporting Requirement == true OR the quarter being checked == 3)

Locate a record in OperalingSuppDataRecordsByLocation where the reporting period is
equal to the year/quarter being checked and the OpTypeCode = "OPHOURS" and
FuelCode is null.

else

Locate a record in OperalingSuppDataRecordsByLocation where the reporting period is
equal to the year/quarter being checked and the OpTypeCode = "OSHOURS" and
FuelCode is null.

if (OperatingSuppDataRecordsByLocation is found AND
OperatingSuppDataRecordsByLocation.OpValue < 168)

If (Annual Reporting Requirement = true OR the quarter being checked == 2)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

else

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 3.

else if (OperatingSuppDataRecordsByLocation is not found)

If (the quarter being checked == 1 or 4)

Locate a LocationReportingFrequency record for the test location where
ReportingFrequencyCode = "OS", the Begin Quarter is on or before the quarter
being checked and the EndQuarter is null or is on or after the quarter being
checked.

Environmental Protection Agency

Page 547 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (LocationReportingFrequency record is found)

if (Annual Reporting Requirement == true and the quarter being
checked == 4 and the year of the EndQuarter is equal to the year of the
quarter being checked.

else

else

Set NumberOfExtensionQuarters -
NumberOfExtensionQuarters + 1.

Stop looking for extensions.

Set Missing Op Data to true.

Set LeakMissingOpDatalnfo = "[YEAR] Q[QTR]" (where [YEAR] is
the year of the quarter being checked and [QTR] is the number of the
quarter being checked.)

Stop looking for extensions.

Set Missing Op Data to true.

Set LeakMissingOpDatalnfo = "[YEAR] Q[QTR]" (where [YEAR] is the year
of the quarter being checked and [QTR] is the number of the quarter being
checked.)

Stop looking for extensions.

Stop looking for extensions.

Add NumberOfExtensionQuarters to PriorLeakExpirationDate

Set i>/orLeaAifecorrf.TestExpirationDateWithExtension = PriorLeakExpirationDate

else

Set PriorLeakExpirationDate = i>/orLeaAifecorrf.TestExpirationDateWithExtension
If (CurrentMIIl Record. \ )dlc I lour is ON OR BEFORE the PriorLeakExpirationDate)

Set LeakStatusResult = "IC-Extension".

else if (Missing Op Data == true)

Set LeakStatusResult = "Missing Op Data".

Set i>/orLeaAifecorrf.TestExpirationDateWithExtension = null

Results:

Result	Response	Severity

Usage:

1	Process/Category:	Emissions Data Evaluation Report	Leak Check Status Evaluation

Environmental Protection Agency

Page 548 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks:

Applicability:

Description:

Specifications:

if (LeakStalusResuti is null)

if (Annual Reporting Requirement == false)

Set LeakStatusResult = "OOC-Expired".

else if (Rpt Period Op Hours Accumulator Array for the location == -1)

Set LeakStatusResult = "Invalid Op Data".

else

Set GraceOpHours = RptPeriodOpHoursAccumulatorArray for the location,
if (GraceOpHours > 168)

Set LeakStatusResult = "OOC-Expired".

else

If the quarter after the LATER of the PriorLeakExpirationDate and the EarliestLocationReportDate is the quarter
of the CurrentMHVRecord.Date/Hour ,

Set LeakStatusResult = "IC-Grace".

else

For each quarter beginning with the quarter after the LATER of the PriorLeakExpirationDate and the
EarliestLocationReportDate ,and continuing through the quarter prior to the
CurrentMHVRecord.Date/Hour ,

if (EarliestLocationReportDate <= the last day of the quarter being checked)

Locate a record in OperatingSuppDataRecordsByLocation where the reporting period is
equal to the year/quarter being checked and the OpTypeCode = "OPHOURS" and
FuelCode is null.

if (OperatingSuppDataRecordsByLocation is found)

Add OpValue to GraceOpHours.

LKSTAT-5

Determine Grace Period for Leak Check
CEM Check

if (GraceOpHours > 168)

Set LeakStatusResult = "OOC-Expired".
exit for.

else

Set LeakStatusResult = "Missing Op Data".

Set LeakMissingOpDatalnfo = "[YEAR] Q[QTR]" (where [YEAR] is the year
of the quarter being checked and [QTR] is the number of the quarter being

Environmental Protection Agency

Page 549 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

checked.)
exit for.

if (LeakStatusResuti is null)

Set LeakStatusResu.lt = "IC-Grace".

if LeakStatusResuti does not begin with "IC"
return LeakStatusResuti

Results:

Result

Invalid Op Data
Missing Op Data

OOC-Event

OOC-Expired
OOC-No Prior
Test

OOC-Test
Aborted

OOC-Test Failed
OOC-Test Has
Critical Errors
Prior Test Not
Yet Evaluated

Response

The [testtype] status for [key] could not be determined, because the OperatingTime in at

least one Hourly Operating Data records was missing or invalid.

The Leak Check status for [COMPID] could not be determined, because the Op Supp

Data record for OPHOURS or OSHOURS is missing for [MtSSINGOPDATAINFO]

(and possibly other previous reporting periods). If you have submitted emissions data

for prior quarters, you should be able to retrieve these records by logging on to the EPA

host.

You reported a QA Certification Event record for QACertEventCode [code]
QACertEventDate [eventdate] for [compid], but you did not perform a subsequent leak
check.

The prior leak check for [compid] completed on [date] has expired.

You did not report a prior [testtype] for [key].

The prior leak check for [compid] completed on [date] was aborted.

The prior leak check for [compid] completed on [date] failed.

The prior leak check for [compid] completed on [date] has critical errors.

The [testtype] status for [key] could not be determined, because the applicable prior
[testtype] with TestNumber [testnum] has not yet been evaluated.

Severity

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

Emissions Data Evaluation Report	Leak Check Status Evaluation

Environmental Protection Agency

Page 550 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
Linearity Status

Environmental Protection Agency

Page 551 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

LINSTAT-1

Check Analyzer Range Exemption For Linearity Status
CEM Check

Check Code:

Check Name:

Related Former Checks:

Applicability:

Description:

Specifications:

Set CurrentLinearityStalus = null

if (CurrentMHVParameter = "S02C" or CurrentMHVParameter = "NOXC")

Locate the record in MonitorSpanRecordsByHourLocation for the hour and location where the ComponentTypeCode is equal to
the CurrentMHVRecord.ComponentTypeCode and the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed.

if (MonitorSpanRecordsByHourLocation is not found OR more than one MonitorSpanRecordsByHourLocation is found OR if
the MonitorSpanRecordsByHourLocation.SpanValue is null or <= 0)

Set CurrentLinearityStatus = "Invalid Monitor Span".

else if (MonitorSpanRecordsByHourLocation is found and MonitorSpanRecordsByHourLocation.Sp&nV&lue <= 30)

Set CurrentLinearityStatus = "IC-Exempt".

Results:

Result

Usage:

1

2

3

4

5

Response

Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:

Severity

Emissions Data Evaluation Report	C02 Linearity Status Evaluation

Emissions Data Evaluation Report	NOX Linearity Status Evaluation

Emissions Data Evaluation Report	02 Dry Linearity Status Evaluation

Emissions Data Evaluation Report	02 Wet Linearity Status Evaluation

Emissions Data Evaluation Report	S02 Linearity Status Evaluation

Environmental Protection Agency

Page 552 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LINSTAT-2

Check Name:

Locate Most Recent Prior Linearity Test

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set PriorLinearity Record = null.

Set InvalidLinearityRecord = null.

if (CurrentLinearityStatus is null)

Locate the most recent record in LinearityTestRecordsByLocationForQAStatus for the location where the ComponentID is equal to
the ApplicableComponentID and the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed and the CalculatedTestResult is
not equal to "INVALID" and the EndDate/Hour is either:

a)	prior to the Current Mil]'Record.\)dlc I lour OR

b)	equal to the CurrentMHVRecordDatefHour and the EndMinute is less than 45 and the CalculatedTestResult is equal to
"PASSED" or "PASSAPS".

if (Linearity TestRecordsByLocationForQAStatus is found)

Set PriorLinearityRecord = the found record in Linearity TestRecordsByLocationForQAStatus.

Locate the most recent record in LinearityTestRecordsByLocationForQAStatus for the location where the ComponentID is
equal to the ApplicableComponentID and the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed and the
EndDate/Hour is prior to the CurrentMHVRecordDatefHour and the EndDate/Hour is greater than the
PriorTestRecord.EndDate/YLour and the CalculatedTestResult is equal to "INVALID".

if (Linearity TestRecordsByLocationForQAStatus is found)

Set InvalidLinearityRecord = the found record in LinearityTestRecordsByLocationForQAStatus.

Locate the most recent record in LinearityTestRecordsByLocationForQAStatus for the location where the ComponentID is
equal to the ApplicableComponentID and the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed and the
CalculatedTestResult is equal to "INVALID" and the EndDate/Hour is prior to the CurrentMHVRecordDate/YLour.

if (Linearity TestRecordsByLocationForQAStatus is found)

Set InvalidLinearityRecord = the found record in LinearityTestRecordsByLocationForQAStatus.

else

Results:

Result

Response

Severity

Environmental Protection Agency

Page 553 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1

2

3

4

5

Process/Category:	Emissions Data Evaluation Report	C02 Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	NOX Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 Linearity Status Evaluation

Environmental Protection Agency

Page 554 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LINSTAT-3

Check Name:

Locate Most Recent Prior Event

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set PriorLinearityEventRecord = null,
if (CurrentLinearityStatus is null)

Locate all records in QACertificalionEventRecords where:
the ComponentID is equal to the ApplicableComponentID
AND LinearityRequired is equal to "Y";

AND the QACertEventDate/Hour is either:

a)	prior to the Current Mil]'Record.\)dlc I lour OR

b)	equal to both the CurrentMHVRecordDatefHour and the ConditionalBeginDate/Hour;

a)	Prior Test Record is null OR

b)	QACertEventDate/Hour is after the PriorTestRecord.EndDatefHour OR

c)	QACertEventDate/Hour is equal to the PriorTestRecord.EndDate/Hour AND (TestCompletionDate is null or the
TestCompletionDate/Hour is after the PriorTestRecord.EndDate/Hour)

AND either

a)	DualRangeStalus = false OR

b)	HighRangeComponentID o LowRangeComponentID OR

c)	QACertEventCode o 30 or 172 and CurrentAnalyzerRangeUsed = "H" OR

d)	QACertEventCode o 35 or 171 and CurrentAnalyzerRangeUsed = "L"

AND either

a)	Annual Reporting Requirement is equal to true OR

b)	QACertEventDate/Hour is on or after April 1 of the year of the CurrentMHVRecordDate
if (QACertificationEventRecords is found)

Sort QACertificationEventRecords by QACertEventDate/Hour descending.

For each record in QACertificationEventRecords

Set PriorLinearityEventRecord = the found record in QACertificationEventRecords.

if (Prior fjnearity Event Record.QACcrl\'.\cnlCodc = 170 and DualRangeStalus = true)

Locate the record in MonitorSpanRecordsByLocalion where the ComponentTypeCode is equal to
CurrentMHVRecord.ComponentTypeCode and the SpanScaleCode is equal to the
CurrentAnalyzerRangeUsed and the BeginDate/Hour is equal to the
PriorLinearityEventRecord QACertEventDate/Hour.

if (MonitorSpanRecordsByLocalion is found)
exit for loop.

AND either

Environmental Protection Agency

Page 555 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

set PriorLinearityEventRecord = null.

else

exit for loop.

If (PriorLinearityEventRecord is null)

If (PriorLinearityRecord is null)

Set CurrentLinearityStalus = "OOC-No Prior Test or Event".

else if (InvalidLinearityRecord is not null Ahl\) Prior [jnearitylJvent Record.QACcrl\.xcnl\)-dlc I lour is after
fnvalidTestRecord.\ .nd\)dlc I lour)

Locate the earliest record in Linearity TestRecordsByLocationForQAStatus where the ComponentID is equal to the
ApplicableComponentID, the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed, the CalculatedTestResult is
equal to "INVALID", and the EndDate/Hour is after the PriorLinearityEventRecord.QACertEverrtDate/Hour and prior to
the CurrentDate/Hour.

if (Linearity TestRecordsByLocationForQAStatus is found)

Set InvalidLinearityRecord = the found record in LinearityTestRecordsByLocationForQAStatus.

else

Set InvalidLinearityRecord = null.

Results:

Result

Usage:

1

2

3

4

5

Response

Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:

Severity

Emissions Data Evaluation Report	C02 Linearity Status Evaluation

Emissions Data Evaluation Report	NOX Linearity Status Evaluation

Emissions Data Evaluation Report	02 Dry Linearity Status Evaluation

Emissions Data Evaluation Report	02 Wet Linearity Status Evaluation

Emissions Data Evaluation Report	S02 Linearity Status Evaluation

Environmental Protection Agency

Page 556 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LINSTAT-4

Check Name:

Determine Expiration Dates For Most Recent Prior Linearity Test

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set LinearityMissingOpDalalnfo = null.

if (CurrentLinearityStatus is blank and PriorLinearityRecord is not null and PriorLinearityEventRecordis null)

Set CheckForlgnoredLinearity = true.

Set PriorTestExpirationDate = null

Set PriorTestExpirationDateWithExtension = null

Set MissingOpData = false

if (PriorLinearityRecord.QANeedsEvaiuationFiag = " Y")

Set CurrentLinearityStatus = "Prior Test Not Yet Evaluated".

else if (PriorLinearityRecord.TestResuitCode = null or PriorLinearityRecord.TestResuitCode = "FAILED" or
PriorLinearityRecord.TestRssultCode = "ABORTED")

Locate the most recent record in QACertificationEventRecords where:
the ComponentID is equal to the ApplicableComponentID
AND LinearityRequired is equal to "Y";

AND the ConditionalBeginDate/Hour is:

a)	on or prior to the CurrentMHVRecord.DatefHour AND

b)	on or after the PriorTestRecord.EndDate/YLour;

AND either

a)	DualRangeStatus = false OR

b)	HighRangeComponentID o LowRangeComponentID OR

c)	QACertEventCode o 30 or 172 and CurrentAnalyzerRangeUsed = "H" OR

d)	QACertEventCode o 35 or 171 and CurrentAnalyzerRangeUsed = "L"

AND either

a)	Annual Reporting Requirement is equal to true OR

b)	QACertEventDate/Hour is on or after April 1 of the year of the Cur rent flour lyRecordforR. 1TA Stat us. I )atc
if (QACertificationEventRecords is found)

Set PriorLinearityEventRecord = found record in QACertificationEventRecords.
elseif (PriorLinearityRecord.TestResuitCode = null)

Set CurrentLinearityStatus = "OOC-Test Has Critical Errors",
else if {PriorLinearityRecord.TestResultCode = "FAILED")

Set CurrentLinearityStatus = "OOC-Test Failed".

Environmental Protection Agency

Page 557 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else if (PriorLinearityRecord.TestResultCode = "ABORTED")

Set CurrentLinearityStalus = "OOC-Test Aborted".

else

Set PriorTestExpirationDate = PriorLinearityRecord.TestExpimtionDate.

Set PriorTestExpirationDate WithExtension = PriorLinearityRecord. TestExpirationDateWithExtension.
if (PriorTestExpirationDate is null)

if (Annual Reporting Requirement == false)

if (Prior fJnearity Record. TcstI TidQuarter = "2")

Set PriorTestExpirationDate = July 30th following Prior Linearity Record.\.nd\)dlc.

else

Set PriorTestExpirationDate = April 30th following Prior fJnearity Record.\.nd\)dlc.

else

Locate the most recent QACertificalionEventRecords for the CurrentMHVRecord.ComponentID where
LinearityRequired is equal to "Y", and the BeginDate/Hour is prior to the
Prior Linearity Record. I icgi n I )atc I lour.

if (QACertificationEventRecords is found AND the LinearityCertEvent is equal to "Y" and the
ConditionalDataBeginDate is null and the CompletionTestDate/Hour is after the
Prior fJnearity Record.\.nd\)dlc I lour)

Set PriorTestExpirationDate = the end of the quarter following the quarter of the
QACertificalionEventRecords . Compl etionTestDate.

else if (PriorLinearityRecord.GmcePenodlnd = 1)

Set PriorTestExpirationDate = the end of the quarter of the Prior fjnearity Record.\.nd\)dlc.

else

Set PriorTestExpirationDate = the end of the quarter following the quarter of the
PriorLinearityRecord.EndDaXe.

Set PriorijiiearityRecord. I cstl Api rationl )atc = PriorTestExpirationDate.

if (CurrentMHVRecord.D&tefHour is ON OR BEFORE the PriorTestExpirationDate)

Set CurrentLinearityStalus = "IC".

else if (Annual Reporting Requirement == false)

Set CurrentLinearityStalus = "OOC-Expired".

else

if (PriorTestExpirationDate WithExtension is null)

Set NumberOfExtensionQuarters = 0;

Environmental Protection Agency

Page 558 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

For each quarter beginning with the quarter of the PriorTestExpirationDate and continuing through the
quarter prior to the quarter of the CurrentDate,

if (NumberOfExtensionQuarters - 3)
Stop looking for extensions.

else

if (EarliestLocalionReportDate > the last day of the quarter being checked)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

else

Locate a record in OperatingSuppDataRecordsByLocation where the reporting
period is equal to the year/quarter being checked and the OpTypeCode =
"OPHOURS".

if (OperatingSuppDataRecordsByLocation is found AND
OperatingSuppDataRecordsByLocation.OpValue < 168)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

else

Locate a record in TestExtensionExemptionRecords where the
ComponentID is equal to the ApplicableComponentID and the
ExtensionExemptionCode is equal to "RANGENU", and the
SpanScaleCode is equal to the CurrentAnalyzerRangeUsed and the
Year/Quarter is equal to the year/quarter to check.

if (TestExtensionExemptionRecords is found)

Set NumberOfExtensionQuarters -
NumberOfExtensionQuarters + 1.

else

Locate a record in TestExtensionExemptionRecords where the
ComponentID is equal to the ApplicableComponentID and the
ExtensionExemptionCode is equal to "NONQAPB", and the
Year/Quarter is equal to the year/quarter to check.

if (TestExtensionExemptionRecords is found)

Set NumberOfExtensionQuarters -
NumberOfExtensionQuarters + 1.

else if (OperatingSuppDataRecordsByLocation is not found)

If (the quarter being checked == 1 or 4)

Locate a LocationReportingFrequency record
for the test location where
ReportingFrequencyCode = "OS", the Begin
Quarter is on or before the quarter being
checked and the EndQuarter is null or is on or

Environmental Protection Agency

Page 559 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

before the quarter being checked.

If (LocalionReportingFrequency record is
found)

if (Annual Reporting Requirement ==

true and the quarter being checked == 4
and the year of the EndQuarter is equal
to the year of the quarter being
checked.

Set

NumberOfExtensionQuarters

NumberOfExtensionQuarters
+ 1.

else

Stop looking for extensions.

else

Set Missing Op Data to true.

Set LinearityMissingOpDatalnfo =

"[YEAR] Q[QTR]" (where [YEAR] is

the year of the quarter being checked

and [QTR] is the number of the quarter

being checked.)

Stop looking for extensions.

else

Set Missing Op Data to true.
Set LinearityMissingOpDatalnfo = "[YEAR]
Q[QTR]" (where [YEAR] is the year of the
quarter being checked and [QTR] is the number
of the quarter being checked.)

Stop looking for extensions.

else

Stop looking for extensions.

For each quarter beginning with the quarter after the End Quarter and continuing through the quarter prior
to the quarter of the CurrentffourlyReconlforRA TAStatus.\ )dlc I lour

Locate a record in TestExtensionExemptionRecords where the ComponentID is equal to the
ApplicableComponentID and the ExtensionExemptionCode is equal to "NONQAPB", and the
Year/Quarter is equal to the year/quarter to check.

if (TestExtensionExemptionRecords is found)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

Set PriorTestExpirationDateWithExtension = PriorTestExpirationDate.

Add NumberOfExtensionQuarters to PriorTestExpirationDateWithExtension.

Set PriorLinearityRecordAestExpimtionDateWithExtension = PriorTestExpirationDateWithExtension.

Environmental Protection Agency

Page 560 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

else

Set PriorLinearityRecord.TestExpimtionDateWithExtension = PriorTestExpirationDate

If (CurrentMII] 'RecordX)i\[c I lour is ON OR BEFORE the PriorTestExpirationDateWithExtension)

Set CurrentLinearityStatus = "IC-Extension".

else if (Missing Op Data == true)

Set CurrentLinearityStatus = "Missing Op Data".

Set PriorLinearityRecord.TestExpimtionDateWithExtension = null

else if (Rpt Period Op Days Accumulator Array for the location == -1)

Set CurrentLinearityStatus = "Invalid Op Data".

else

Set GraceOpHours = RptPeriodOpHoursAccumulatorArray for the location,
if (GraceOpHours > 168)

Set CurrentLinearityStatus = "OOC-Expired".

else

If there are NO quarters beginning with the LATER of the quarter after the
PriorTestExpirationDateWithExtension and the quarter of the EarliestLocationReportDate and
ending with the quarter prior to the CurrentMII]'Record.I lour,

Set CurrentLinearityStatus = "IC-Grace".

else

For each quarter beginning with the quarter after the

PriorTestExpirationDateWithExtension and continuing through the quarter prior to the
CurrentMII] '/f «/. Date I lour,

if (EarliestLocationReportDate <= the last day of the quarter being checked)

Locate a record in OperatingSuppDataRecordsByLocation where the
reporting period is equal to the year/quarter being checked and the
OpTypeCode = "OPHOURS" and FuelCode is null.

if (OperatingSuppDataRecordsByLocation is found)

Add Op Value to GraceOpHours.

if (GraceOpHours > 168)

Set CurrentLinearityStatus = "OOC-Expired".
exit for.

else

Set CurrentLinearityStatus = "Missing Op Data".

Set LinearityMissingOpDatalnfo = "[YEAR] Q[QTR]" (where

Environmental Protection Agency

Page 561 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Usage:

1

2

3

4

5

Response

Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:

[YEAR] is the year of the quarter being checked and [QTR] is
the number of the quarter being checked.)
exit for.

if (CurrentLinearityStatus is null)

Set CurrentLinearityStatus = "IC-Grace".

Emissions Data Evaluation Report	C02 Linearity Status Evaluation

Emissions Data Evaluation Report	NOX Linearity Status Evaluation

Emissions Data Evaluation Report	02 Dry Linearity Status Evaluation

Emissions Data Evaluation Report	02 Wet Linearity Status Evaluation

Emissions Data Evaluation Report	S02 Linearity Status Evaluation

Severity

Environmental Protection Agency

Page 562 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LINSTAT-5

Check Name:

Determine Event Conditional Status

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set SubsequentLinearityRecord = null.

if (CurrentLinearityStatus is null and PriorLinearityEventRecordis not null)

if (PriorLinearityEventRecord.ConditionaUDataBegmDate/YLour is null or CurrentMHVRecord.Date/Hour is prior to the
PriorLinearityEventRecord.Conditiona[DataBeginDate/Y{our)

Locate the earliest record in Linearity TestRecordsByLocalionForQAStatus where the ComponentID is equal to the
ApplicableComponentID, the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed, the CalculatedTestResult is not
equal to "INVALID" and the EndDate/Hour is on or after the PriorLinearityEventRecord.ConditionaUDataBegmDate/YLour.

if {Linearity TestRecordsByLocalionForQAStatus is found)

Set SubsequentLinearityRecord = the found record in LinearityTestRecordsByLocationForQAStatus.

if (LinearityTestRecordsByLocationForOAStatw;.QANccds]:.\a\ nation Mag = "Y")

Set CurrentLinearityStatus = "Recertification Test Not Yet Evaluated".

else if (LinearityTestRecordsByLocationForQAStatus.TestKesuitCode is null)

Set CurrentLinearityStatus = "OOC-Recertification Test Has Critical Errors".

else if (LinearityTestRecordsByLocationForQAStatus.TestKesuitCode = "FAILED")

Set CurrentLinearityStatus = "OOC-Recertification Test Failed".

else if (LinearityTestRecordsByLocationForQAStatus.TestKesuitCode = "ABORTED")

Set CurrentLinearityStatus = "OOC-Recertification Test Aborted".

If (InvalidLinearityRecord is null)

Locate the earliest record in Linearity TestRecordsByLocationForQAStatus where the ComponentID is
equal to the ApplicableComponentID, the SpanScaleCode is equal to the CurrentAnalyzerRangeUsed,
the CalculatedTestResult is equal to "INVALID" and the EndDate/Hour is on or after the
PriorLinearityEventRecord.ConditionnUDntaBeginDnte/Hour and is before the EndDate/EndHour of the
Linearity TestRecordsByLocationForQAStatus record retrieved above.

if (Linearity TestRecordsByLocationForQAStatus is found)

Set InvalidLinearityRecord = the found record in LinearityTestRecordsByLocationForQAStatus.

if (CurrentLinearityStatus is null AND Annual Reporting Requirement == false)

If (SubsequentLinearityRecord is not null and SubsequentfJnearityRecord.\ .nd\)dlc I lour is greater than October
30th of the year of the CurrentMHVRecord.Date/Hour) OR (SubsequentLinearityRecord is null and the
CurrentMII]'Record.I lour is in the 3rd quarter))

Set CurrentLinearityStatus = "OOC-Event".

else

Environmental Protection Agency

Page 563 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set CurrentLinearityStatus = "OOC-Conditional Period Expired",
if (CurrentLinearityStatus is null)

if (PriorLinearityEventRecord. I ,i ncari tvCert Event == "Y")
if (Prior Linearity Event Record.].\cnlCodc = 125)

If (PriorLinearityEventRecord.Mom tori ngSvstem 11) is null)

Set CurrentLinearityStatus = "Invalid Certification Event"

else if (the associated BeginDate of the system in the PriorLinearityEventRecord is null)
Set CurrentLinearityStatus = "Invalid Monitor System"

else

If (the associated SystemTypeCode of the system in the PriorLinearityEventRecord ==
"S02")

Locate the record in LocationProgramRecordsByHourLocation with the latest
UnitMonitorCertBeginDate where the ProgramCode is in set {ARP, CAIRS02}
and the UnitMonitorCertBeginDate is ON OR BEFORE the associated
BeginDate of the system in the PriorLinearityEventRecord.

If (the record in LocationProgramRecordsByHourLocation is not found)

Locate the record in LocationProgramRecordsByHourLocation with the
latest EmissionsRecordingBeginDate where the ProgramCode is in set
{ARP, CAIRS02} and the EmissionsRecordingBeginDate is ON OR
BEFORE the associated BeginDate of the system in the
PriorLinearityEventRecord.

else if (the associated SystemTypeCode of the system in the PriorLinearityEventRecord
== "NOX")

Locate the record in LocationProgramRecordsByHourLocation with the latest
UnitMonitorCertBeginDate where the ProgramCode is in set {ARP, NBP,
NHNOX, CAIRNOX, CAIROS, SIPNOX} and the UnitMonitorCertBeginDate is
ON OR BEFORE the associated BeginDate of the system in the
PriorLinearityEventRecord.

If (the record in LocationProgramRecordsByHourLocation is not found)

Locate the record in LocationProgramRecordsByHourLocation with the
latest EmissionsRecordingBeginDate where the ProgramCode is in set
{ARP, CAIRS02, NBP, NHNOX, CAIRNOX, CAIROS, SIPNOX} and
the EmissionsRecordingBeginDate is ON OR BEFORE the associated
BeginDate of the system in the PriorLinearityEventRecord.

else if (the associated SystemTypeCode of the system in the PriorLinearityEventRecord
== "NOXC")

Locate the record in LocationProgramRecordsByHourLocation with the latest
UnitMonitorCertBeginDate where the ProgramCode is in set {NBP, NHNOX,
CAIRNOX, CAIROS, SIPNOX} and the UnitMonitorCertBeginDate is ON OR
BEFORE the associated BeginDate of the system in the
PriorLinearityEventRecord.

If (the record in LocationProgramRecordsByHourLocation is not found)

Locate the record in LocationProgramRecordsByHourLocation with the

Environmental Protection Agency

Page 564 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

latest EmissionsRecordingBeginDate where the ProgramCode is in set
{NBP, NHNOX, CAIRNOX, CAIROS, SIPNOX} and the
EmissionsRecordingBeginDate is ON OR BEFORE the associated
BeginDate of the system in the PriorLinearityEventRecord.

Locate the record in LocationProgramRecordsByHourLocation with the latest
UnitMonitorCertBeginDate where the UnitMonitorCertBeginDate is ON OR
BEFORE the associated BeginDate of the system in the
PriorLinearityEventRecord.

If (the record in LocationProgramRecordsByHourLocation is not found)

Locate the record in LocationProgramRecordsByHourLocation with the
latest EmissionsRecordingBeginDate where the
EmissionsRecordingBeginDate is ON OR BEFORE the associated
BeginDate of the system in the PriorLinearityEventRecord.

If (the record in LocationProgramRecordsByHourLocation is not found)
Set CurrentLinearityStatus = "Missing Program".

else i I (LocationProgramRecordsBy/fourLocationl Jni tMoni torCcrtl )cadli nc is not null)

if (CurrentDate is prior to the

LocationProgramRecordsByHourLocationUnitMonitorCertDeadhne)
Set CurrentLinearityStatus = "IC-Conditional".

else

Set CurrentLinearityStatus = "OOC-Conditional Period Expired".

else

if (CurrentDate is prior to the

LocationProgramRecordsByHourLocationUnitMonitorCertBeginDate + 180

days)

Set CurrentLinearityStatus = "IC-Conditional".

else

Set CurrentLinearityStatus = "OOC-Conditional Period Expired".

else

If (the number of calendar days ON OR AFTER the

I'rior Linearity Invent Record.QACal].\cnl])dlc and ON OR BEFORE the

CurrentMHVRecord.D&tefHour > 180)

Set CurrentLinearityStatus = "OOC-Conditional Period Expired".

else if (the quarter of the PriorLinearityEventRecord.QACertEverrtDate is equal to the quarter of
the CurrentMHVRecord.Date/Hour)

If (the number of calendar days ON OR AFTER the
PriorLinearityEventRecord. Q A C cr 11 vc n 11 )a tc and ON OR BEFORE the
Current Mill /<«/. Date I lour > 90)

If (Rpt Period Op Hours Accumulator Array for the location == -1)
Set CurrentLinearityStatus = "Invalid Op Data".

else if (the number of calendar days ON OR AFTER the

I'rior Linearity Invent Record.QACcrl].\cnl\)dlc and ON OR BEFORE the

Environmental Protection Agency

Page 565 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Current Mil]'Record.\)dlc I lour is equal to Rpt Period Op Days Accumulator
Array for the location)

Set CurrentLinearityStatus = "OOC-Conditional Period Expired".

else

Set CurrentLinearity Status = "IC-Conditional".

else

Set CurrentLinearityStatus = "IC-Conditional".

else if (PriorLinearityEventRecord.MinOpDaysPriorQuarter is null)
Set PriorLinearityEventRecord.MinOpDaysPriorQuarter = 0
Set PriorLinearityEventRecord.MaxOpDaysPriorQuarter = 0

for each quarter beginning with the quarter of the

PriorLinearityEventRecord.QACertEverrtDate and continuing through the quarter
BEFORE the CurrentMIH'Record.\)d{c I lour:

if (EarliestLocationReportDate <= the last day of the quarter being checked)

Locate the record in OperatingSuppDataRecordsbyLocation where the
OpTypeCode is equal to "OPDAYS" and the reporting period is equal to
the quarter being checked.

if (OperatingSuppDataRecordsbyLocation is not found)

Set PriorLinearityEventRecord.MinOpDaysPnorQuarter = -1
Set LinearityMissingOpDatalnfo = "[YEAR] Q[QTR]" (where
[YEAR] is the year of the quarter being checked and [QTR] is
the number of the quarter being checked,
exit for.

else

If the quarter being checked is the quarter of the
Prior Linearity Event Record.QACcrl\.xcnl\>dlc

If (OperatingSuppDataRecordsby Location. Op Va I uc

MINUS the number of calendar days in the quarter

being checked that are PRIOR to the

Prior Linearity Event Record.QACcrl\.xcnl\)dlc > 0)

Set

PriorLinearityEventRecord.MinOpDaysPriorQ
uarter =

OperatingSuppDataRecordsby Location. ()p Va I

ue MINUS the number of calendar days in the
quarter being checked that are PRIOR to the
Priori jnearity IJvent Record.QACcrl\.xcnl\)dlc

If (OperatingSuppDataRecordsby Location. Op Va I uc is

less than the number of calendar days in the quarter
being checked that are ON OR AFTER the
PriorLinearityEventRecord. QACertEventDate)

Set

Prior Linearity Event Record.Md\<)p\)d\sl'nor
Quarter =

OperatingSuppDataRecordsby Location. ()p Va I

Environmental Protection Agency

Page 566 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

ue.

else

Set

PriorLinearityEventRecord.MaxOpDaysPrior
Quarter = the number of calendar days in the
quarter being checked that are ON OR AFTER
the

Prior IjnearitylJvent Record.QACcrl\.xcnl\)dlc.

else

Set

Prior IJnearity Invent Record.Min()p\)c\\%\'riorQuiulcr =
Prior [Jnearity Invent Record.Min()p\)c\\%l'riorQucUlcr +
Oper alingSuppDataRecordsbyLocation. Op Value.
Set PriorLinearityEventRecord. MaxOpDay s
PriorQuarter =

Prior [Jnearity Invent Record.Mc\x()p\)c\\%l'riorQucUlcr +
Oper alingSuppDataRecordsbyLocation. Op Value.

if (PriorLinearityEventRecord.MinOpDaysPriorQuarter == -1
set CurrentLinearityStatus to "Missing Op Data"

else if (Prior Invent Record. Mi nOp I )a vs I 'ri orQuarter + Rpt Period Op Days Accumulator
Array for the Location > 90)

Set CurrentLinearityStatus = "OOC-Conditional Period Expired".

else if (PriorEventRecord.MaxOpDaysPnorQuarter + Rpt Period Op Days Accumulator
Array for the Location > 90)

Set CurrentLinearityStatus = "Undetermined-Conditional Data".

else

Set CurrentLinearityStatus = "IC-Conditional".

else

Set CurrentLinearityStatus = "IC-Conditional".

If (the quarter of the PriorLinearityEventRecord.Conditiona\BeginDate is equal to the quarter of the
CurrentMII\'Record.Dnlc I lour)

Count the number of HourlyOpData records for the location where OpTime is greater than 0 and
Date/Hour is ON OR AFTER the PriorLinearityEventRecord.ConditionaiBeginDate/YLour and
ON OR BEFORE {hcCurrentMIH Record.\)i\{c I lour,

If the number > 168,

Set CurrentLinearityStatus = "OOC-Conditional Period Expired".

else

Set CurrentLinearityStatus = "IC-Conditional".

if (Prior fjnearitylJvent Record.Min()p\ lours PriorQuarter is null)

Set Prior [jnearitylJvent Record.Min()p\ lours PriorQuarter = 0
Set Prior[jnearitylJventRecord.Mdx()p\ IoursPriorQuartcr = 0

Environmental Protection Agency

Page 567 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

for each quarter beginning with the quarter of the

PriorLinearityEventRecord.ConditionalBeginDate and continuing through the quarter
BEFORE the CurrentMIH'Record.Y)i\{c I lour:

if (EarliestLocalionReportDale <= the last day of the quarter being checked)

if (Annual Reporting Requirement == false AND the quarter being
checked == 2)

Locate the record in OperalingSuppDataRecordsbyLocalion

where the OpTypeCode is equal to "OSHOURS" and the
reporting period is equal to the quarter being checked.

else

Locate the record in OperalingSuppDataRecordsbyLocalion

where the OpTypeCode is equal to "OPHOURS", FuelCode is
null, and the reporting period is equal to the quarter being
checked.

if (OperatingSuppDataRecordsbyLocation is not found)

Set Prior Linearity Event Record.IoursPriorQuartcr = -1
Set LinearityMissingOpDatalnfo = "[YEAR] Q[QTR]" (where
[YEAR] is the year of the quarter being checked and [QTR] is
the number of the quarter being checked.)
exit for.

else

If the quarter being checked is the quarter of the
PriorUnearity Event Record.Condi tional I icgi n I )atc

If (OperatingSuppDataRecordsby Location.Op VaI lie

MINUS the number of calendar hours in the quarter
being checked that are PRIOR to the
PriorLinearityEventRecord.ConditionaiBeginDatefYLou
r > 0)

Set

Prior [jnearity Event Record. Mi nOpI lour sPri or

Quarter =

OperatingSuppDataRecordsby Location. ()p Va I

ue MINUS the number of calendar hours in the
quarter being checked that are PRIOR to the
PriorLinearityEventRecord.ConditionalBegin
Date/Hour

If (OperatingSuppDataRecordsby Location. Op Va I lie is

less than the number of calendar hours in the quarter

begin checked that are ON OR AFTER the

PriorfJnearityLJventRecord.CondiUon-dWI Iou

r)

Set

Prior[jnearityLJventRecord.Mdx()p\ IoursPrior
Quarter =

Environmental Protection Agency

Page 568 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

OperatingSuppDataRecordsby Location. ()p Va I

ue.

else

Set

PriorLinearityEventRecord. MaxOpHoursPrior
Quarter = the number of calendar hours in the
quarter being checked that are ON OR AFTER
the

PriorLinearityEventRecord.Conditiona\Begm
Date/Hour.

else

Set

Prior Linearity Event Record.IoursPriorQuartcr

Prior Linearity Event Record.IoursPriorQuartcr
+ OperatingSuppDataRecordsbyLocation. Op Value.

Set Prior Linearity Event Record.MaxOpl lours
PriorQuarter =

Prior Linearity Event Record.MaxOpl IoursPriorQuartcr
+ OperatingSuppDataRecordsbyLocation. Op Value.

if (Prior[jiiearitylJventRecord.Min()p\ IoursPriorQuartcr == -1)
set CurrentLinearityStatus to "Missing Op Data"

else if (Rpt Period Op Days Accumulator Array for the location == -1)

if (_ft70r.EV«tfitec0ra?.MinOpHoursPriorQuarter > 168)

Set CurrentLinearityStatus = "OOC-Conditional Period Expired".

else

Set CurrentLinearityStatus = "Invalid Op Data".

else

if (/V70r£V«tfitec0ra?.MinOpHoursPriorQuarter + Rpt Period Op Hours Accumulator
Array for the Location > 168)

Set CurrentLinearityStatus = "OOC-Conditional Period Expired".

else if (PriorEventRecord.MaxOpHoursPriorQuarter + Rpt Period Op Hours
Accumulator Array for the Location > 168)

Set CurrentLinearityStatus = "Undetermined-Conditional Data".

else

Set CurrentLinearityStatus = "IC-Conditional".

Results:

Result	Response	Severity

Environmental Protection Agency

Page 569 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1

2

3

4

5

Process/Category:	Emissions Data Evaluation Report	C02 Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	NOX Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 Linearity Status Evaluation

Environmental Protection Agency

Page 570 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LINSTAT-6

Check Name:

Determine Final Linearity Status

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set AlternateLinearityRecord = null
Set AlternalelnvalidLinearity Record = null

if (CurrentLinearityStatus begins with "OOC")

if (InvalidLinearityRecord is not null)

Set CurrentLinearityStatus = CurrentLinearityStatus &

Return result CurrentLinearityStatus.

else if (CurrentLinearityStatus= "Invalid Monitor Span")

if {CurrentAnalyzerRangeUsed = "H")

Set CurrentLinearityStatus = CurrentLinearityStatus & " (High Scale)".

else

Set CurrentLinearityStatus = CurrentLinearityStatus & " (Low Scale)".

Return result CurrentLinearityStatus.

else if (DualRangeStatus = true and CurrentLinearityStatus begins with "IC" or "Undetermined")

if {CurrentAnalyzerRangeUsed = "H")

Set AlternateAnalyzerRange = "L".

Set AltemateComponentID = LowRangeComponentID.

else

Set AlternateAnalyzerRange = "H".

Set AltemateComponentID = HighRangeComponentlD.

for each record in MonitorSystemComponentRecordsByHourLocation where the ComponentID is equal to the
AltemateComponentID

Append MonitorSystemComponentRecordsByHourLocation.SystemID to AltemateSystemlDs.

if (MonitorSystemComponentRecordsByHourLocation is not found)

Set CurrentLinearityStatus = "Invalid Monitor System Component".

Return result CurrentLinearityStatus.

if (CurrentMHVParameter in set {S02C, NOXC})

Locate the record in MonitorSpanRecordsByHourAndLocation for the hour where the ComponentTypeCode is equal to
the CurrentMHVRecord.ComponentTypeCode and the SpanScaleCode is equal to the AlternateAnalyzerRange.

if (MonitorSpanRecordsByHourAndLocation is not found OR more than one MonitorSpanRecordsByHourAndLocation
is found or MonitorSpanRecordsByHourAndLocation.SpsmVaiue is null or is less than or equal to 0)

Environmental Protection Agency	Page 571 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set CurrentLinearityStatus = "Invalid Monitor Span",
if (AlternateAnalyzerRange = "H")

Set CurrentLinearityStatus = CurrentLinearityStalus & " (High Scale)".

else

Set CurrentLinearityStatus = CurrentLinearityStatus & " (Low Scale)".

Return result CurrentLinearityStatus.

else if (MonitorSpanRecordsByHourAndLocation.SpmiVsdue < =30)

If (CurrentLinearityStatus does not begin with "IC")

Return result CurrentLinearityStatus.

else

exit check.

Locate the most recent record in LinearityTestRecordsByLocationForQAStatus for the AlternateComponentID where the
SpanScaleCode is equal to the AlternateAnalyzerRange and the CalculatedTestResult is not equal to "INVALID" and the
EndDate/Hour is either:

a)	prior to the Current Mil]'Record.\)dlc I lour OR

b)	equal to the CurrentMHVRecordDatefHour and the EndMinute is less than "45" and the CalculatedTestResult is equal to
"PASSED" or "PASSAPS".

if (Linearity TestRecordsByLocationForQAStatus is found)

Set AlternateLinearityRecord = the found record in LinearityTestRecordsByLocationForQAStatus.

Locate all records in QACertificationEventRecords where:

the ComponentID is equal to the AlternateComponentID

AND LinearityRequired is equal to "Y",

AND the QACertEventDate/Hour is either:

a)	prior to the Current Mil]'Record.\)dlc I lour OR

b)	equal to both the CurrentMHVRecordDatefHour and the ConditionalDataBeginDate/Hour;

AND either

a)	AlternateLinearityRecord is null OR

b)	QACertEventDate/Hour is after the AlternateLinearityRecord.EndDatefHour OR

c)	QACertEventDate/Hour is equal to the AlternateLinearityRecord.EndDate/YLour AND (TestCompletionDate is null or the
TestCompletionDate/Hour is after the AlternateLinearityRecord.EndDsite/YLom)

AND either

a)	DualRangeStatus = false OR

b)	HighRangeComponentID o LowRangeComponentID OR

c)	QACertEventCode o 30 or 172 and AlternateAnalyzerRange = "H" OR

d)	QACertEventCode o 35 or 171 and AlternateAnalyzerRange — "L"

if (QACertificationEventRecords is found)

if (0.1 Certificationlivent Records.Cond]tional IicginI )atc I lour is null or CurrentMII] Record.\)dlc I lour is prior to the

Environmental Protection Agency

Page 572 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

0.1 Certif cationlJventRecords.Condi ti onal I icgi n I )atc I lour)

If (CurrentLinearityStalus does not begin with "IC")

Return result CurrentLinearityStalus.

else

Locate the most recent record in Linearity TestRecordsByLocationForQAStatus for the AlternateComponentID
where the SpanScaleCode is equal to the AlternateAnalyzerRange, the CalculatedTestResult is equal to
"INVALID", and the EndDate/Hour is after the QACertificationEventRecords.QACertEverrtDatefHour and prior
to the CurrentMHVRecord.Date/Hour.

if (LinearityTestRecordsByLocotionForQAStotus is found)

Set AlternatelnvalidLinearityRecord = the found record in
Linearity TestRecordsByLocalionForQAStatus.

else

Set AlternatelnvalidLinearityRecord = null.

Locate the first record in LinearityTestRecordsByLocationForQAStalus where the ComponentID is equal to the
AlternateComponentID, the SpanScaleCode is equal to the AlternateAnalyzerRange, the CalculatedTestResult is not
equal to "INVALID", and the EndDate/Hour is on or after the
0.1 CertificationFventRecords.Cond\l\ona\I )atalicginI )atc I lour.

if (LinearityTestRecordsByLocationForQAStatus is found)

Set AlternateLinearityRecord = the found record in Linearity TestRecordsByLocalionForQAStatus.

if (AlternateLinearityRecord .QANeedsEvaluationFlag = " Y")

Set CurrentLinearityStalus = "Alternate Range Recertification Test Not Yet Evaluated".

else if (AlternateLinearityRecord .TestResultCode is null or is in set {FAILED, ABORTED})

If (AlternatelnvalidLinearityRecord is null)

Locate the most recent record in Linearity TestRecordsByLocationForQAStatus for the
AlternateComponentID where the SpanScaleCode is equal to the
AlternateAnalyzerRange, the CalculatedTestResult is equal to "INVALID", and the
EndDate/Hour is after the QACertificationEventRecords.QACertEverrtDatefHour and
prior to the EndDate/Hour of the Linearity TestRecordsByLocationForQAStatus record
retrieved above.

if (Linearity TestRecordsByLocationForQAStatus is found)

Set AlternatelnvalidLinearity Record = the found record in
Linearity TestRecordsByLocationForQAStatus.

if (AlternateLinearityRecord .TestResultCode is null)

Set CurrentLinearityStalus = "OOC-Alternate Range Recertification Test Has Critical
Errors".

if (AlternateIn vaUdTestRecord is not null)

Set CurrentLinearityStatus = CurrentLinearityStalus &

else if (AlternateLinearityRecord TestResultCode = "FAILED")

Set CurrentLinearityStatus = "OOC-Alternate Range Recertification Test Failed",
if (AlternalelnvalidTestRecord is not null)

Set CurrentLinearityStatus = CurrentLinearityStatus &

else if (AlternateLinearityRecord TestResultCode = "ABORTED")

Set CurrentLinearityStatus = "OOC-Alternate Range Recertification Test Aborted",
if (AlternalelnvalidTestRecord is not null)

Set CurrentLinearityStatus = CurrentLinearityStatus &

Environmental Protection Agency

Page 573 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (CurrentLinearityStalus does not begin with "IC")
Return result CurrentLinearityStalus.

else

if (AlternateLinearityRecordis found)

if {AlternateLinearityRecord.QANeedsEvaluationFlag = "Y")

Set CurrentLinearityStatus = "Alternate Range Test Not Yet Evaluated".

else if (.AlternateLinearityRecord. TestResultCode is null or is in set {ABORTED, FAILED})

Locate the most recent record in LinearityTestRecordsByLocationForQAStatus for the
AlternateComponentID where the SpanScaleCode is equal to the AlternateAnalyzerRange and the
EndDate/Hour is prior to the CurrentMHVRecordDatefHour and the EndDate/Hour is greater than the
AlternateLinearityRecord.EndD&te/Ylour and the CalculatedTestResult is equal to "INVALID".

if (Linearity TestRecordsByLocationForQAStatus is found)

Set AlternatelnvalidLinearityRecord = the found record in
LinearityTestRecordsByLocationForQAStatus.

if (AlternateLinearityRecord TestResultCode = null)

Set CurrentLinearityStatus = "OOC-Alternate Range Test Has Critical Errors"
if (AlternatelnvalidLinearityRecord is not null)

Set CurrentLinearityStatus = CurrentLinearityStatus &

else if (AlternateLinearityRecord .TestResultCode = "FAILED")

Set CurrentLinearityStatus = "OOC-Alternate Range Test Failed",
if (AlternatelnvalidLinearityRecord is not null)

Set CurrentLinearityStatus = CurrentLinearityStatus &

else if (AlternateLinearityRecord .TestResultCode = "ABORTED")

Set CurrentLinearityStatus = "OOC-Alternate Range Test Aborted",
if (AlternatelnvalidLinearityRecord is not null)

Set CurrentLinearityStatus = CurrentLinearityStatus &

else

Set CurrentLinearityStatus = "OOC-No Prior Alternate Range Test or Event".

If (CurrentLinearityStatus does not begin with "IC")
Return result CurrentLinearityStatus.

else

If (CurrentLinearityStatus does not begin with "IC")

Return result CurrentLinearityStatus.

Environmental Protection Agency

Page 574 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Alternate Range

Recertification

Test Not Yet

Evaluated

Alternate Range

Test Not Yet

Evaluated

Invalid

Certification

Event

Invalid Monitor
Span (High
Scale)

Invalid Monitor
Span (Low Scale)
Invalid Monitor
System

Invalid Monitor
System
Component
Invalid Op Data

Missing Op Data

Missing Program

OOC-Alternate
Range

Recertification
Test Aborted
OOC-Alternate
Range

Recertification
Test Aborted*
OOC-Alternate
Range

Recertification
Test Failed
OOC-Alternate
Range

Recertification
Test Failed*
OOC-Alternate
Range

Recertification
Test Has Critical
Errors

OOC-Alternate
Range

Recertification
Test Has Critical
Errors*

Response	Severity

The [testtype] status for [key] could not be determined, because the prior [testtype] for	Critical Error Level 1

the alternate range component with TestNumber [alttestnum] has not yet been evaluated.

The [testtype] status for [key] could not be determined, because the prior [testtype] for
the alternate range component with TestNumber [alttestnum] has not yet been evaluated.

The [testtype] status for [key] could not be determined, because the QA Certification
Event record for QACertEventCode [code] QACertEventDate [eventdate] has a critical
error.

The [testtype] status for [key] could not be determined, because you did not report a
single, valid high-scale [comptype] span record that was active during the test.

The [testtype] status for [key] could not be determined, because you did not report a
single, valid low-scale [comptype] span record that was active during the test.

The [testtype] status for [key] could not be determined, because the Monitor System
record for MonitoringSystemID [system] has a critical error.

The [testtype] status for [key] could not be determined, because you did not report any
active Monitor System Component records for the alternate range of the component.

The [testtype] status for [key] could not be determined, because the OperatingTime in at
least one Hourly Operating Data records was missing or invalid.

The [testtype] status for [key] could not be determined, because the Op Supp Data
record for OPHOURS, OSHOURS, or OPDAYS is missing for

[MISSINGOPDATAINFO] (and possibly other previous reporting periods). If you have
submitted emissions data for prior quarters, you should be able to retrieve these records
by logging on to the EPA host.

The [testtype] status for [key] could not be determined, because a Unit Program record	Critical Error Level 1

associated with the initial certification event for QACertEventCode [code]

QACertEventDate [eventdate] either does not exist or has a

UnitMonitorCertificationBeginDate inconsistent with the BeginDate of the associated
Monitor System record.

The subsequent recertification [testtype] for the alternate range of the component for	Critical Error Level 1

[key] with TestNumber [alttestnum] was aborted.

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

The subsequent recertification [testtype] for the alternate range of [key] with	Critical Error Level 1

TestNumber [alttestnum] was aborted. An invalid [testtype] with TestNumber
[altinvtestnum] was ignored.

The subsequent recertification [testtype] for the alternate range of the component for	Critical Error Level 1

[key] with TestNumber [alttestnum] failed.

The subsequent recertification [testtype] for the alternate range of the component for	Critical Error Level 1

[key] with TestNumber [alttestnum] failed. An invalid [testtype] with TestNumber
[altinvtestnum] was ignored.

The subsequent recertification [testtype] for the alternate range of the component for	Critical Error Level 1

[key] with TestNumber [alttestnum] has critical errors.

The subsequent recertification [testtype] for the alternate range of the component for	Critical Error Level 1

[key] with TestNumber [alttestnum] has critical errors. An invalid [testtype] with
TestNumber [altinvtestnum] was ignored.

Environmental Protection Agency

Page 575 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

OOC-Alternate
Range Test
Aborted
OOC-Alternate
Range Test
Aborted*
OOC-Alternate
Range Test
Failed

OOC-Alternate
Range Test
Failed*

OOC-Alternate
Range Test Ftas
Critical Errors
OOC-Alternate
Range Test Ftas
Critical Errors*
OOC-Conditional
Period Expired
OOC-Conditional
Period Expired*
OOC-Event

OOC-Event*

OOC-Expired
OOC-Expired*

OOC-No Prior
Alternate Range
Test or Event
OOC-No Prior
Test or Event
OOC-No Prior
Test or Event*
OOC-Recertificat
ion Test Aborted
OOC-Recertificat
ion Test
Aborted*
OOC-Recertificat
ion Test Failed
OOC-Recertificat
ion Test Failed*
OOC-Recertificat
ion Test Ftas
Critical Errors
OOC-Recertificat
ion Test Ftas
Critical Errors*
OOC-Test
Aborted
OOC-Test
Aborted*
OOC-Test Failed
OOC-Test
Failed*

The prior [testtype] for the alternate range of the component for [key] with TestNumber	Critical Error Level

[alttestnum] was aborted.

The prior [testtype] for the alternate range of the component for [key] with TestNumber	Critical Error Level

[alttestnum] was aborted. An invalid [testtype] with TestNumber [altinvtestnum] was

ignored.

The prior [testtype] for the alternate range of the component for [key] with TestNumber	Critical Error Level

[alttestnum] failed.

The prior [testtype] for the alternate range of the component for [key] with TestNumber	Critical Error Level

[alttestnum] failed. An invalid [testtype] with TestNumber [altinvtestnum] was ignored.

The prior [testtype] for the alternate range of the component for [key] with TestNumber	Critical Error Level

[alttestnum] has critical errors.

The prior [testtype] for the alternate range of the component for [key] with TestNumber
[alttestnum] has critical errors. An invalid [testtype] with TestNumber [altinvtestnum]
was ignored.

The conditional data period for QACertEventCode [code] QACertEventDate [eventdate]
for [key] has expired.

The conditional data period for QACertEventCode [code] QACertEventDate [eventdate]

for [key] has expired. An invalid [testtype] was ignored.

You reported a QA Certification Event record for QACertEventCode [code]

QACertEventDate [eventdate], but you did not indicate the use of conditional data for

[key].

You reported a QA Certification Event record for QACertEventCode [code]
QACertEventDate [eventdate] for [key], but you did not indicate the use of conditional
data. An invalid [testtype] was ignored.

The prior [testtype] for [key] with TestNumber [testnum] has expired.

The prior [testtype] for [key] with TestNumber [testnum] has expired. An invalid prior

[testtype] with TestNumber [invtestnum] was ignored.

You did not report a prior [testtype] or certification event for the alternate range of the
component for [key].

You did not report a prior [testtype] or certification event for [key].

You did not report a valid prior [testtype] or certification event for [key]. An invalid
[testtype] with TestNumber [invtestnum] was ignored.

The subsequent recertification [testtype] for [key] with TestNumber [subtestnum] was
aborted.

The subsequent recertification [testtype] for [key] with TestNumber [subtestnum] was
aborted. An invalid [testtype] with TestNumber [invtestnum] was ignored.

Critical Error Level

Critical Error Level
Critical Error Level
Critical Error Level

Critical Error Level

Critical Error Level
Critical Error Level

Critical Error Level

Critical Error Level
Critical Error Level
Critical Error Level
Critical Error Level

The subsequent recertification [testtype] for [key] with TestNumber [subtestnum] failed.	Critical Error Level

The subsequent recertification [testtype] for [key] with TestNumber [subtestnum] failed.	Critical Error Level

An invalid [testtype] with TestNumber [invtestnum] was ignored.

The subsequent recertification [testtype] for [key] with TestNumber [subtestnum] has	Critical Error Level

critical errors.

The subsequent recertification [testtype] for [key] with TestNumber [subtestnum] has
critical errors. An invalid [testtype] with TestNumber [invtestnum] was ignored.

The applicable prior [testtype] for [key] with TestNumber [testnum] was aborted.

The prior [testtype] for [key] with TestNumber [testnum] was aborted. An invalid prior

[testtype] with TestNumber [invtestnum] was ignored.

The applicable prior [testtype] for [key] with TestNumber [testnum] failed.

The prior [testtype] for [key] with TestNumber [testnum] failed. An invalid prior

[testtype] with TestNumber [invtestnum] was ignored.

Critical Error Level

Critical Error Level

Critical Error Level

Critical Error Level
Critical Error Level

Environmental Protection Agency

Page 576 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

OOC-Test Has	The applicable prior [testtype] for [key] with TestNumber [testnum] has critical errors.
Critical Errors

OOC-Test Has	The prior [testtype] for [key] with TestNumber [testnum] has critical errors. An invalid

Critical Errors*	prior [testtype] with TestNumber [invtestnum] was ignored.

Prior Test Not	The [testtype] status for [key] could not be determined, because the applicable prior

Yet Evaluated	[testtype] with TestNumber [testnum] has not yet been evaluated.

Recertification	The [testtype] status for [key] could not be determined, because the subsequent

Test Not Yet	recertification [testtype] for the component with TestNumber [subtestnum] has not yet

Evaluated	been evaluated.

Undetermined-Co The software could not determine if the current hour was within the conditional data

nditional Data	period for QACertEventCode [code] QACertEventDate [eventdate] for [key]

Usage:

1

2

3

4

5

Process/Category:	Emissions Data Evaluation Report	C02 Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	NOX Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Dry Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	02 Wet Linearity Status Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 Linearity Status Evaluation

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Informational Message

Environmental Protection Agency

Page 577 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:

LME

Environmental Protection Agency

Page 578 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-11

Check Name:

Check LTFF System

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

For the LTFF record:

If MonitoringSystemID is null,
return result A.

else

Locate the Monitor System record for the MonitoringSystemID.

If the associated SystemTypeCode is not equal to "LTOL" or "LTGS",
return result B.

Results:

Result

A

B

Response

You did not report a MonitoringSystemID in an LTFF record.

The MonitoringSystemID reported in the LTFF record for [key] is not a long-term fuel
flow system.

Severity
Fatal

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report — Long Term Fuel Flow

1

Process/Category:	LME Emissions Data Generation LTFF Heat Input Data

1

Process/Category:	Emissions Data Entry Screen Evaluation LTFF Data Evaluation

Environmental Protection Agency

Page 579 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-13

Check Name:	Check Long Term Fuel Flow Value

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

For the LTFF record:

If the LongTermFuelFlowValue is null or is less than or equal to 0,
return result A.

Results:

Result	Response	Severity

A	The [fieldname] reported in the LTFF record for [key] is missing or invalid.	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report — Long Term Fuel Flow

1	Process/Category:	LME Emissions Data Generation LTFF Heat Input Data

1	Process/Category:	Emissions Data Entry Screen Evaluation LTFF Data Evaluation

Environmental Protection Agency

Page 580 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-14

Check Name:

Check Long Term Fuel Flow UOM

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

For the LTFF record:

If the LongTermFuelFlowUOMCode is null,
return result A.

Otherwise,

If the SystemTypeCode is "LTOL" and the LongTermFuelFlowUOMCode is not in set {"LB", "GAL"},
return result A.

If the SystemTypeCode is "LTGS" and the LongTermFuelFlowUOMCode is not equal to "SCF",
return result A.

Results:

Result
A

Response

The [fieldname] reported in the LTFF record for [key] is missing or invalid.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	Emissions Data Evaluation Report — Long Term Fuel Flow

1

Process/Category:	LME Emissions Data Generation LTFF Heat Input Data

1

Process/Category:	Emissions Data Entry Screen Evaluation LTFF Data Evaluation

Environmental Protection Agency

Page 581 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-15

Check Name:	Check LTFF GCV

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

For the LTFF record:

If the GrossCalorificValue is null or is less than or equal to 0,
return result A.

Results:

Result	Response	Severity

A	The [fieldname] reported in the LTFF record for [key] is missing or invalid.	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Evaluation Report — Long Term Fuel Flow

1	Process/Category:	LME Emissions Data Generation LTFF Heat Input Data

1	Process/Category:	Emissions Data Entry Screen Evaluation LTFF Data Evaluation

Environmental Protection Agency

Page 582 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-16

Check Name:

Check LTFF GCV UOM

Related Former Checks:

Applicability:

LME Check

Description:

Validation Tables:

Fuel Type Reality Checks for GCV (Cross Check Table)

Fuel Type Warning Levels for GCV (Cross Check Table)

Fuel Type Reality Checks for GCV (Cross Check Table)

Fuel Type Warning Levels for GCV (Cross Check Table)

Fuel Type Reality Checks for GCV (Cross Check Table)

Fuel Type Warning Levels for GCV (Cross Check Table)

Specifications:

For the LTFF record:

LME Gen LTFF Heat Input = null.

If the GCVUnitsOfMeasureCode is null,
return result A.

Otherwise,

If the LongTermFuelFlowUOMCode is "LB" and the GCVUnitsOfMeasureCode is not equal to "BTULB",
return result A.

If the LongTermFuelFlowUOMCode is "GAL" and the GCVUnitsOfMeasureCode is not equal to "BTUGAL",
return result A.

If the LongTermFuelFlowUOMCode is "SCF" and the GCVUnitsOfMeasureCode is not equal to "BTUSCF",
return result A.

Otherwise,

If GrossCalorificValue is greater than 0 and LongTermFuelFlowValue is greater than 0,

Calculate LME Gen LTFF Heat Input = GrossCalorificValue * LongTermFuelFlowValue / 1,000,000,
rounded to the nearest integer.

Max Expected GCV= Lookup "Upper Value" in "Fuel Type Warning Levels for GCV Cross Check Table"
where "Fuel Code - Units Of Measure" column = concatenation of (FuelCode, " - ",
LongTermFuelFlowUOMCode )

Min ExpectedGCV= Lookup "Lower Value" in "Fuel Type Warning Levels for GCV Cross Check Table"
where "Fuel Code - Units Of Measure" column = concatenation of (FuelCode, " - ",
LongTermFuelFlowUOMCode )

Max Allowed GCV= Lookup "Upper Value" in "Fuel Type Reality Checks for GCV Cross Check Table"
where "Fuel Code - Units Of Measure" column = concatenation of (FuelCode, " - ",
LongTermFuelFlowUOMCode )

Min Allowed GCV= Lookup "Lower Value" in "Fuel Type Reality Checks for GCV Cross Check Table"
where "Fuel Code - Units Of Measure" column = concatenation of (FuelCode, " - ",
LongTermFuelFlowUOMCode )

if {Max Allowed GCV is not null AND GrossCalorificValue > Max Allowed GCV) OR {Min Allowed GCV is not
null AND GrossCalorificValue < Min Allowed GCV)
return result B

else

if {Min Expected GCV is not null AND GrossCalorificValue < Min Expected GCV) OR {Max Expected
GCV is not null AND GrossCalorificValue > Max Expected GCV)
return result C

Environmental Protection Agency

Page 583 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

A

B

Usage:
1

1

1

Response

The [fieldname] reported in the LTFF record for [key] is missing or invalid.

The GrossCalorificValue reported in the long-term fuel flow record for [key] is outside

the range of allowable values for the fuel type [fueled].

The GrossCalorificValue reported in the long-term fuel flow record for [key] is outside
the range of expected values for the fuel type [fueled].

Process/Category:	Emissions Data Evaluation Report — Long Term Fuel Flow

Process/Category:	LME Emissions Data Generation LTFF Heat Input Data

Process/Category:	Emissions Data Entry Screen Evaluation LTFF Data Evaluation

Severity

Critical Error Level 1
Critical Error Level 1

Non-Critical Error

Environmental Protection Agency

Page 584 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-41

Check Name:	Check LTFF Fuel Flow Period Code

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

For the LTFF record:

If LME OS is equal to true,

If the Quarter of the Current Reporting Period is equal to 2,
If the FuelFlowPeriodCode is null,
return result A.

Otherwise,

If the FuelFlowPeriodCode is not null,
return result B.

Otherwise,

If the FuelFlowPeriodCode is not null,
return result C.

Results:

Result
A

B

C

Usage:

1

Response

You did not report a FuelFlowPeriodCode in the LTFF record for [key]. This value is
required for LME units with an ozone-season qualification during the second quarter.
You reported a FuelFlowPeriodCode in the LTFF record for [key], but this value is only
appropriate during the second quarter.

You reported a FuelFlowPeriodCode in the LTFF record for [key], but this value is only
appropriate for LME units with an ozone-season qualification.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Process/Category:

Emissions Data Evaluation Report — Long Term Fuel Flow

Environmental Protection Agency

Page 585 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-42

Check Name:

Check LTFF Total Heat Input

Related Former Checks:

Applicability:

LME Check

Description:

Validation Tables:

Hourly Emissions Tolerances (Cross Check Table)

Specifications:

For the Current LTFF record:

If LME Gen LTFF Heat Input is not null,

If LME Total Heat Input Array for the location is greater than or equal to 0,

add LME Gen LTFF Heat Input to LME Total Heat Input Array for the location.

If LME OS is true and the Current 777" Record. I Lie 11 I owPeri odCode is equal to "A",

add LME Gen LTFF Heat Input to LME April Total Heat Input Array for the location.

If (the LocationName begins with "CP")

If LME CP Total Heat Input is greater than or equal to 0,

add LME Gen LTFF Heat Input to LME CP Total Heat Input.

If LME OS is true and the Current LTFF /fecYWY/.Iuel MoxvPcriodCodc is equal to "A",
add LME Gen LTFF Heat Input to LME CP April Heat Input.

Set LME Total Heat Input Array for the location to -1.

If (the LocationName begins with "CP")

set LME CP Total Heat Input to -1.

If (the LocationName begins with "CP")

Rpt Period HI Calculated Accumulator Array for this location = LME Total Heat Input Array for the location.

April HI Calculated Accumulator Array for this location = LME Total April Input Array for the location
Expected Summary Value HI Array for this location = true

If Current LTfFitecortf. TotalHeatlnput is greater than or equal to 0,

If (the LocationName begins with "CP" AND Rpt Period HI Reported Accumulator Array for this location is greater than
or equal to 0)

Rpt Period HI Reported Accumulator Array for this location = Rpt Period HI Reported Accumulator Array for
this location + Current LTFF Record.'[oh\W Icatlnput

If LME Gen LTFF Heat Input is not null AND Current ITU' Record.\o[M Icatlnput is not equal to LME Gen LTFF
Heat Input,

Heat Input Tolerance = Lookup Tolerance from Cross-Check Table "Hourly Emissions Tolerances" where
Parameter = "HI" AND
UOM = "MMBTUHR"

else

if (ABS(Current LZFFifecorrf.TotalHeatlnput - LME Gen LTFF Heat Input) > Heat Input Tolerance)
return result A.

else

If (the LocationName begins with "CP")

Rpt Period HI Reported Accumulator Array for this location = -1.

return result B

Environmental Protection Agency

Page 586 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result	Response Severity

A	The TotalHeatlnput reported in the LTFF record for [key] is inconsistent with the	Critical Error Level 1

recalculated value.

B	The [fieldname] reported in the LTFF record for [key] is missing or invalid.	Critical Error Level 1

Usage:

1	Process/Category: Emissions Data Evaluation Report — Long Term Fuel Flow

Environmental Protection Agency

Page 587 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-10

Check Name:	Determine Total Load for Reporting Period

Related Former Checks: LME-EXP8A

Applicability:	LME Check

Description:

Specifications:

Set LME Gen LTFF Heat Input Array, LME Gen Total Heat Input Array, LME Gen Total Load Array, LME Gen Total S02M Array,
LME Gen Total NOXMArray, LME Gen Total C02M Array, LME Gen Total Op Time Array, LME Gen Total Op Hours Array, and
LME Gen LTFF Total Op Time Array to 0 for each location in the monitor configuration.

Set LME Gen LTFF April Heat Input Array, LME Gen April Heat Input Array, LME Gen April Load Array, LME Gen April NOXM
Array, LME Gen April Op Time Array, LME Gen April Op Hours Array, and LME Gen LTFF April Op Time Array to 0 for each
location in the monitoring configuration.

Set LME Gen CP Total Heat Input, LME Gen Total Load, and LME Gen Total Optime to 0.

Set LME Gen CP April Heat Input, LME Gen April Load, and LME Gen April Optime to 0.

Set LME Gen Annual and LME Gen OS to false.

Set LME Gen HI Method and LME Gen HI Substitute Data Code to null.

Locate MonitorMethod records for all locations in the monitoring configuration where ParameterCode = "HIT", BeginDate is on or before
the first day of the reporting period, and the EndDate is null or is on or after the last day of the reporting period.

If any location does not have a retrieved record,
return result A.

Otherwise,

Set LME Year Start Quarter to the quarter of the current reporting period.

Locate a MonitorQualification for all units in the monitoring configuration where the QualificationTypeCode is equal to "LMEA" or
"LMES", BeginDate is on or before the last day of the reporting period, and the EndDate is null or is on or after December 31 of the
year prior to the reporting period.

If a record with QualificationTypeCode equal to "LMEA" is found,
set LME Gen Annual to true.

If a record with QualificationTypeCode equal to "LMES" is found,
set LME Gen OS to true.

If LME Gen Annual AND LME Gen OS are both false,
return result B.

else if LME Gen Annual is false AND the Quarter of the reporting period is equal to 1 or 4,
return result C.

Otherwise,

If the Quarter of the reporting period is greater than 1,

If the earliest BeginDate in the retrieved records is in a year prior to the year of the current reporting period,
If LME Gen Annual is equal to true,

set LME Year Start Quarter to 1.

else

set LME Year Start Quarter to 2.

else if the earliest BeginDate in the retrieved records is in a quarter prior to the LME Year Start Quarter,
set LME Year Start Quarter to the quarter of the earliest BeginDate.

If MethodCode in all the retrieved Method records is equal to "MHHI",

Environmental Protection Agency

Page 588 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

LME Gen HI Method = "MHHI".

Locate an LTFF record for any location during the reporting period.

If found,

return result D.

If MethodCode in all the retrieved Method records is in set {LTFF, CALC, LTFCALC},

LME Gen HI Method = "LTFF".

If SubstituteDataCode in any retrieved record is equal to "MHHI",

LME Gen HI Substitute Data Code = "MHHI".

For each Hourly Op Data record for the configuration:

If Hourly Op Data HourLoad is not null and is less than 0,
return result E.

else if Hourly Op Data OpTime for any hour is null, less than 0, or greater than 1,
return result F.

else if Hourly Op Data OpTime is greater than 0 and Hourly Op Data HourLoad is null,
return result E.

else if Hourly Op Data OpTime is greater than 0 AND Hourly Op Data MHHI Indicator is not equal to 1,
Add HourLoad * OpTime to LME Gen Total Load Array for the location.

Add HourLoad * OpTime to LME Gen Total Load.

Add OpTime to LME Gen Total Optime.

Add OpTime to LME Gen LTFF Total Op Time Array for location.

If the month of Hourly Op Data Date is April AND LME Gen OS is equal to true,
Add HourLoad * OpTime to LME Gen April Load Array for the location.
Add HourLoad * OpTime to LME Gen April Load.

Add OpTime to LME Gen April Optime.

Add OpTime to LME Gen LTFF April Op Time Array for location

If LME Gen OS is equal to true and the Quarter of the reporting period is equal to 2,

Locate an LTFF record for any location in the monitoring configuration during the reporting period where
the FuelFlowPeriodCode is equal to "A".

If found and the LME Gen April Load is equal to 0 and LME Gen April Optime is equal to 0,
return result J.

Else if not found AND (LME Gen April Load is greater than 0 or LME Gen April Optime is greater than

1),

return result K.

Otherwise,

Locate an LTFF record for any location in the monitoring configuration during the reporting
period where the FuelFlowPeriodCode is equal to "MJ".

If found,

If (LME Gen Total Load - LME Gen April Load) is equal to 0 and (LME Gen Total
Optime - LME Gen April Optime) is equal to 0,

Environmental Protection Agency

Page 589 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

return result L.

If not found,

If (LME Gen Total Load - LME Gen April Load) is greater than 0 or (LME Gen Total
Optime - LME Gen April Optime) is greater than 1,
return result M.

Locate an LTFF record for any location in the monitoring configuration during the reporting period.

If LME Gen Total Load is equal to 0 and LME Gen Total Optime is equal to 0,
return result G.

If not found,

If LME Gen Total Load is greater than 0 or LME Gen Total Optime is greater than 1,
return result I.

Otherwise,

If found,

Otherwise,

return result H.

Do not process remaining categories if fatal error is returned.

Environmental Protection Agency

Page 590 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result
A

B

C

D

E
F
G

H

I

J

K
L

M

Usage:

1

Response

You have not reported an active HIT method in your monitoring plan for at least one
monitoring location in the configuration.

You have not reported an active LMEA or LMES qualification record for this
configuration in your monitoring plan.

You have not reported an active LMEA qualification record for this configuration in
your monitoring plan, but the reporting period is the first or fourth quarter. Only annual
LME units should report in the first or fourth quarter.

You have reported MHHI as the heat input method for this configuration, but you have
reported a long-term fuel flow record.

You have reported LTFF as the heat input method for this configuration, but the

LoadValue in at least one hourly record is missing or invalid.

You have reported LTFF as the heat input method for this configuration, but the

OperatingTime in at least one hourly record is missing or invalid.

You have reported a long-term fuel flow record for this reporting period, but the sum of

the load and operating time values in the hourly records (where MHHIIndicator is not

equal to 1) are equal to 0.

You have not reported the same heat input method in your monitoring plan for all
locations in the configuration during the reporting period.

You have reported LTFF as the heat input method for this configuration, but you have
not reported a long-term fuel flow record for this reporting period.

You have reported a long-term fuel flow record for April, but the sum of the load and
operating time values in the hourly records (where MHHIIndicator is not equal to 1) are
equal to 0.

You have reported LTFF as the heat input method for this ozone-season reporting
configuration, but you have not reported a long-term fuel flow record for April.
You have reported a long-term fuel flow record for May and June, but the sum of the
load and operating time values in the hourly records (where MHHIIndicator is not equal
to 1) are equal to 0.

You have reported LTFF as the heat input method for this ozone-season reporting
configuration, but you have not reported a long-term fuel flow record for May/June.

Severity
Fatal

Fatal

Fatal

Fatal
Fatal
Fatal
Fatal

Fatal

Critical Error Level 1
Fatal

Critical Error Level 1
Fatal

Critical Error Level 1

Process/Category:

LME Emissions Data Generation LME Initialization

Environmental Protection Agency

Page 591 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-12

Check Name:	Check LTFF Fuel Flow Period Code

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

For the LTFF record:

If LME Gen OS is equal to true,

If the Quarter of the reporting period is equal to 2,
If the FuelFlowPeriodCode is null,
return result A.

Otherwise,

If the FuelFlowPeriodCode is not null,
return result B.

Otherwise,

If the FuelFlowPeriodCode is not null,
return result C.

Results:

Result
A

B

C

Response

You did not report a FuelFlowPeriodCode in the LTFF record for [key]. This value is
required for LME units with an ozone-season qualification during the second quarter.
You reported a FuelFlowPeriodCode in the LTFF record for [key], but this value is only
appropriate during the second quarter.

You reported a FuelFlowPeriodCode in the LTFF record for [key], but this value is only
appropriate for LME units with an ozone-season qualification.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Usage:
1

Process/Category:

LME Emissions Data Generation LTFF Heat Input Data

Environmental Protection Agency

Page 592 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-17

Check Name:

Check LTFF Total Heat Input

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

For the LTFF record:

If LME Gen LTFF Heat Input is not null and is greater than or equal to 0 ,

if LME Gen Total Heat Input Array for the location is greater than or equal to 0,

add LME Gen LTFF Heat Input to LME Gen LTFF Heat Input Array for the location.

If LME Gen OS is true and the FuelFlowPeriodCode is equal to "A",

add LME Gen LTFF Heat Input to LME Gen LTFF April Heat Input Array for the location.

If Location is a common pipe,

If LME Gen CP Total Heat Input is greater than or equal to 0,

add LME Gen LTFF Heat Input to LME Gen CP Total Heat Input.

If LME Gen OS is true and the FuelFlowPeriodCode is equal to "A",

add LME Gen LTFF Heat Input to LME Gen CP April Heat Input.

Otherwise,

If Location is a common pipe,

set LME Gen CP Total Heat Input to -1.

Set LME Gen LTFF Heat Input Array for the location to -1.

Results:

Result
A

Response
obsolete

Severity
No Errors

Usage:
1

Process/Category:	LME Emissions Data Generation LTFF Heat Input Data

Environmental Protection Agency

Page 593 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-21

Check Name:	Locate Hourly Op Record for LME Unit

Related Former Checks:

Applicability:

Description:

Specifications:

Set Current LME Hourly Op Record to null.

Set Generate LME to false.

If LME Gen Annual = true

Locate all Monitor Method records for the unit and the hour where the ParameterCode is equal to "S02M", "NOXM", or "C02M",
and the MethodCode is equal to "LME".

else

Locate all Monitor Method records for the unit and the hour where the ParameterCode is equal to "NOXM and the MethodCode is
equal to "LME".

If found,

Set LME Gen Parameters to the list of ParameterCodes in the retrieved records.

Otherwise,

Set LME Gen Parameters to null.

Locate an Hourly Op Data record for the unit and the hour.
If found,

If LME Gen Parameters is null,
return result A.

Set Current LME Hourly Op Record to the retrieved record.

Set Generate LME to true.

if LME Gen Annual is equal to false, and the current date is in the month of April,
return result B.

Otherwise,

If LME Gen Parameters is not null, AND

{LME Gen Annual is equal to true OR the current date is in the months of May thru September),
return result C.

Results:

Result	Response	Severity

A	There is no active LME method in your monitoring plan.	Critical Error Level 1

B	You reported an LME Hourly record for April, but the unit does not have an annual	Informational Message

LME qualification. Emissions for this hour will not be included in the totals reported in
the Summary Value record.

C	You did not report an LME Hourly record for the hour.	Critical Error Level 1

Environmental Protection Agency

Page 594 of 667


-------
Draft ECMPS Emissions Check Specifications	9/17/2014 12:00:00AM

Usage:

1	Process/Category:	LME Emissions Data Generation Hourly Emissions Data

Environmental Protection Agency

Page 595 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-22

Check Name:

Check LME Op Time

Related Former Checks: LME-EXP2

Applicability:

LME Check

Description:

Specifications:

If Current LME Hourly Op Record is not null,

If OpTime is null, or is not between 0 and 1 inclusive,

Set LME Gen Total Op Time Array for location to -1, Generate LME to false, and return result A.

Otherwise,

If OpTime is greater than 0, AND LME Gen Total Op Time Array for location is greater than or equal to 0,
Add 1 to LME Gen Total Op Hours Array for location.

Add OpTime to LME Gen Total Op Time Array for location.

If current date in the month of April,

Add 1 to LME Gen April Op Hours Array for location.
Add OpTime to LME Gen April Op Time Array for location.

Results:

Result
A

Response

The [fieldname] reported in the LME Hourly record is missing or invalid.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Hourly Emissions Data

Environmental Protection Agency

Page 596 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-24

Check Name:

Check LME Load Value

Related Former Checks: LME-EXP5

Applicability:

LME Check

Description:

Specifications:

If Current LME Hourly Op Record is not null,

If LoadValue is less than 0,

set Generate LME to false, and return result A.

else if LoadValue is null,

If OperatingTime is greater than 0,

If LME Gen HI Method is equal to "LTFF"

set Generate LME to false, and return result B.

Otherwise

return result C.

else

If OperatingTime is equal to 0,
return result D.

Results:

Result

Response

The [fieldname] reported in the LME Hourly record is invalid.

You did not report a LoadValue in the LME Hourly record.

You did not report a LoadValue in the LME Hourly record.

You reported a LoadValue in the LME Hourly record. This field should be blank for a
non-operating hour.

Severity

A
B
C
D

Critical Error Level 1
Critical Error Level 1
Non-Critical Error

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Hourly Emissions Data

Environmental Protection Agency

Page 597 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-26

Check Name:

Check LME Load UOM

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

If Current LME Hourly Op Record is not null,

If LoadValue is null,

If LoadUOMCode is not null,
return result A.

Otherwise,

If LoadUOMCode is not equal to "MW", "KLBHR", or "MMBTUHR",
set Generate LME to false, and return result A.

Otherwise,

Locate Monitor Load record for the location and hour.

If not found, or more than one record is found, or the MaximumLoadUnitsOfMeasureCode is null,
set Generate LME to false, and return result B.

Otherwise,

If the LoadUOMCode is not equal to the MaximumLoadUnitsOfMeasureCode in the retrieved record,
set Generate LME to false, and return result C.

Results:

Result

A

B

Response

The [fieldname] reported in the LME Hourly record is missing or invalid.

You have not reported a single, active, valid Monitor Load record in your monitoring

plan.

The LoadUOMCode in the LME Hourly record is not consistent with the value in the
Monitor Load record in your monitoring plan.

Severity

Critical Error Level 1
Critical Error Level 1

C

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Hourly Emissions Data

1

Process/Category:	Emissions Data Entry Screen Evaluation Hourly Op Data Evaluation

Environmental Protection Agency

Page 598 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-27

Check Name:	Check LME Fuel Code List

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

If Current LME Hourly Op Record is not null,

If OpTime is greater than 0, and FuelCodeList is null,

set Generate LME to false, and return result A.

Results:

Result	Response Severity

A	You did not report a value in the FuelCodeList in the LME Hourly record, but the unit	Critical Error Level 1

operated during the hour.

Usage:

1	Process/Category: LME Emissions Data Generation Hourly Emissions Data

1	Process/Category: Emissions Data Entry Screen Evaluation Hourly Op Data Evaluation

Environmental Protection Agency

Page 599 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-28

Check Name:	Calculate Heat Input for LME Unit

Related Former Checks: LME-EXP3B, LME-EXP9A

Applicability:	LME Check

Description:

Specifications:

LME Gen Heat Input Record = null
LME Calc Heat Input = null
LME Gen Fuel Code = null

If Generate LME is equal to true,

If Current LME Hourly Op ifecorrf.OperatingTime is greater than 0,

If LME Gen HI Method is equal to "MHHI" or Current LME Hourly Op itecortf.MHHIIndicator is equal to 1,

Locate all Monitor Default records for the hour and location where the ParameterCode is equal to "MHHI".

If one record is found, the DefaultValue is greater than 0, and the DefaultUnitsOfMeasureCode is equal to
"MMBTUHR".

Calculate LME Calc Heat Input = DefaultValue * Current LME Hourly Op Record.OpTime, rounded to
one decimal place.

Otherwise,

If LME Gen Parameters contains "S02M",

set LME Gen Total S02M Array for location to -1.

If LME Gen Parameters contains "NOXM",

set LME Gen Total NOXM Array for location to -1.

If LME Gen Parameters contains "C02M",

set LME Gen Total C02M Array for location to -1.
set LME Gen Total Heat Input Array for location to -1, and return result A.

else if LME Gen HI Method is equal to "LTFF",

If LME Gen CP Total Heat Input is greater than or equal to 0, LME Gen Total Heat Input Array for the location
is greater than or equal to 0, AND Current LME Hourly Op itecortf.HourLoad is greater than or equal to 0,

If LME Gen OS is equal to true, and the Quarter of the reporting period is equal to 2,

If the current date is in the month of April,

if LME Gen April Load is greater than 0,

If Current LME Hourly Op itecortf.HourLoad is equal to 0
Set LME Calc Heat Input = 0

else

Calculate LME Calc Heat Input = {LME Gen CP April Heat Input *
Current LME Hourly Op itecortf.HourLoad * Current LME Hourly Op
Record. OpTime I LME Gen April Load) + (LME Gen LTFF April
Heat Input Array for the location * Current LME Hourly Op
RecordHomLo&A * Current LME Hourly Op Record.OpTime I LME
Gen April Load Array for the location), and round the result to 1 decimal
place.

else if LME Gen April Optime is greater than 0,

Environmental Protection Agency

Page 600 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Calculate LME Calc Heat Input = {LME Gen CP April Heat Input * Current
LME Hourly Op Record.0\)Time / LME Gen April Optime) + {LME Gen
LTFF April Heat Input Array for the location * Current LME Hourly Op
Record.0\)Time I LME Gen LTFF April Op Time Array for the location), and
round the result to 1 decimal place.

Otherwise,

if LME Gen Total Load is greater than 0,

If Current LME Hourly Op itecortf.HourLoad is equal to 0,

Set LME Calc Heat Input = 0

else

Calculate LME Calc Heat Input = {{LME Gen CP Total Heat Input -
LME Gen CP April Heat Input) * Current LME Hourly Op
RecordHomLo&A * Current LME Hourly Op Record.me {LME
Gen Total Load - LME Gen April Load)) + {{LME Gen LTFF Heat
Input Array for the location - LME Gen LTFF April Heat Input Array
for the location) 4 Current LME Hourly Op Record.HourLoad *
Current LME Hourly Op Record.OpTime I {LME Gen Total Load
Array for the location - LME Gen April Load Array for the location)),
and round the result to 1 decimal place.

else if LME Gen Total Optime is greater than 0,

Calculate LME Calc Heat Input = {{LME Gen CP Total Heat Input - LME
Gen CP April Heat Input) * Current LME Hourly Op Record.OpTime / {LME
Gen Total Optime - LME Gen April Optime)) + {{LME Gen LTFF Heat Input
Array for the location - LME Gen LTFF April Heat Input Array for the
location) 4 Current LME Hourly Op Record.OpTime I {LME Gen Total Optime
Array for the location - LME Gen LTFF April Op Time Array for the location)),
and round the result to 1 decimal place.

Otherwise,

if LME Gen Total Load is greater than 0,

If Current LME Hourly Op ifecorrf.HourLoad is equal to 0,

Set LME Calc Heat Input = 0

else

Calculate LME Calc Heat Input = {LME Gen CP Total Heat Input * Current
LME Hourly Op Recurd.\ IourLoad * Current LME Hourly Op Record.OpTime
/ LME Gen Total Load) + {LME Gen LTFF Heat Input Array for the location *
Current LME Hourly Op RecordHomLo&A * Current LME Hourly Op
Record.OpTime I LME Gen Total Load Array for the location), and round the
result to 1 decimal place.

else if LME Gen Total Optime is greater than 0,

Calculate LME Calc Heat Input = {LME Gen CP Total Heat Input * Current LME
Hourly Op Record. OpTime / LME Gen Total Optime) + {LME Gen LTFF Heat Input
Array for the location * Current LME Hourly Op Record.OpTime / LME Gen LTFF
Total Op Time Array for the location), and round the result to 1 decimal place.

If LME Calc Heat Input is not null,

Environmental Protection Agency

Page 601 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If LME Calc Heat Input is greater than 999,999.9

If LME Gen Parameters contains "S02M",

set LME Gen Total S02M Array for location to -1.

If LME Gen Parameters contains "NOXM",

set LME Gen Total NOXM Array for location to -1.

If LME Gen Parameters contains "C02M",

set LME Gen Total C02M Array for location to -1.
set LME Calc Heat Input to null, LME Gen Total Heat Input Array for location to -1, and return result
B.

else if LME Calc Heat Input is greater than or equal to 0,

LME Gen Heat Input RecordA Iourll) = Current LME Hourly Op Record A Iourll)

LME Gen Heat Input Record.PammeterCode = "HIT"

LME Gen Heat Input ifecorrf.AdjustedHourly Value = LME Calc Heat Input

If Current LME Hourly Op ifecorrf.MHHIIndicator is equal to 1,

LME Gen Heat Input Record.MODCCode = "45"

If LME Gen Total Heat Input Array for location is greater than or equal to 0,

Add LME Calc Heat Input to LME Gen Total Heat Input Array for location.

If current date in the month of April,

Add LME Calc Heat Input to LME Gen April Heat Input Array for location.

Otherwise,

If LME Gen Parameters is not null, AND

{LME Gen Annual is equal to true OR the current date is in the months of May thru September),

If LME Gen Parameters contains "S02M",

set LME Gen Total S02M Array for location to -1.

If LME Gen Parameters contains "NOXM",

set LME Gen Total NOXM Array for location to -1.

If LME Gen Parameters contains "C02M",

set LME Gen Total C02M Array for location to -1.
set LME Gen Total Heat Input Array for location to -1.

Environmental Protection Agency

Page 602 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result	Response	Severity

A	You did not report a single, active, valid default record for MHHI in your monitoring	Critical Error Level 1

plan.

B	The value calculated for [param] in the LME Hourly record exceeds the maximum	Critical Error Level 1

value.

Usage:

1	Process/Category:	LME Emissions Data Generation Hourly Emissions Data

Environmental Protection Agency

Page 603 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-29

Check Name:	Calculate S02 Mass for LME Unit

Related Former Checks: LME-EXP3C, LME-EXP9C

Applicability:	LME Check

Description:

Specifications:

LME Gen S02M Record = null

If LME Gen Parameters contains "S02M" and Current LME Hourly Op Record is not null,

If Current LME Hourly Op Record. I Lie IC ode list is not null,

SO 2 Rate = 0
S02 Fuel = null

For each FuelCode in the Current LME Hourly Op ifecorrf.FuelCodeList

Locate all Monitor Default Records for the location and hour where ParameterCode is equal to "S02R",
DefaultPurposeCd = "LM", and FuelCode is equal to the current Fuel Code.

If one and only one record is found, the DefaultValue is greater than 0, and DefaultUnitsOfMeasureCode is equal to
"LBMMBTU",

If S02 Rate is less than the DefaultValue in the retrieved record,
set S02 Rate to the DefaultValue.
set SO2 Fuel to the current FuelCode.

Otherwise,

set LME Gen Total S02M Array for location to -1, LME Gen Fuel Code to the current FuelCode,
and return result A.

If LME Calc Heat Input is not null and is greater than or equal to 0 AND SO2 Rate is greater than 0,

Calculate S02 Mass = LME Calc Heat Input 4 S02 Rate, and round the result to 1 decimal place.

If S02Mass is greater than 99,999.9

set LME Gen Total S02M Array for location to -1, and return result B.

Otherwise,

LME Gen S()2M Recur d.\ Iourll) = Current LME Hourly Op Record.l Iourll)

LME Gen S02M Record .ParameterCode = "S02M"

LME Gen S0.2M ifecortf.AdjustedHourlyValue = S02 Mass

LME Gen S()2M Record. I Lie IC ode = SO2 Fuel

If LME Gen Total S02M Array for location is greater than or equal to 0,
Add S02 Mass to LME Gen Total S02M Array for location.

Environmental Protection Agency

Page 604 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result	Response	Severity

A	You did not report a single, active, valid [defparm] default record for FuelCode [fuel] in	Critical Error Level 1

your monitoring plan.

B	The value calculated for [param] in the LME Hourly record exceeds the maximum	Critical Error Level 1

value.

Usage:

1	Process/Category:	LME Emissions Data Generation Hourly Emissions Data

Environmental Protection Agency

Page 605 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-30

Check Name:

Calculate NOX Mass for LME Unit

Related Former Checks: LME-EXP3A, LME-EXP9B

Applicability:

LME Check

Description:

Specifications:

LME Gen NOXM Record = null

If LME Gen Parameters contains "NOXM" and Current LME Hourly Op Record is not null and Current LME Hourly Op
ifecorrf.OpTime is greater than 0,

If Current LME Hourly Op Record. I Lie IC ode list is not null,

NOX Rate = 0
NOX Fuel = null

For each FuelCode in the Current LME Hourly Op ifecorrf.FuelCodeList

If Current LME Hourly Op ifecortf. OperatingConditionCode is null,

Locate all Monitor Default Records for the location and hour where ParameterCode is equal to "NOXR",
DefaultPurposeCd = "LM", OperatingConditionCode = "A", and FuelCode is equal to the current
FuelCode.

else if Current LME Hourly Op Record.OperatingConditionCode == "U",

Locate all Monitor Default Records for the location and hour where ParameterCode is equal to "NORX",
DefaultPurposeCd = "MD", the OperatingConditionCode is equal to "U", and FuelCode is equal to the
current FuelCode.

Locate all Monitor Default Records for the location and hour where ParameterCode is equal to "NOXR",
DefaultPurposeCd = "LM", the OperatingConditionCode is equal to Current LME Hourly Op
Record.OperatingConditionCode, and FuelCode is equal to the current FuelCode.

If one and only one record is found, the DefaultValue is greater than 0, and DefaultUnitsOfMeasureCode is equal to
"LBMMBTU",

If NOX Rate is less than the DefaultValue in the retrieved record,
set NOX Rate to the DefaultValue.
set NOX Fuel to the current FuelCode.

Otherwise,

LME Gen Total NOXM Array for location to -1.

Set LME Gen Fuel Code to the current FuelCode.

If Current LME Hourly Op Record.OperatingConditionCode is null,

If LME Calc Heat Input is not null and is greater than or equal to 0 AND NOX Rate is greater than 0,

Calculate NOX Mass = LME Calc Heat Input 4 NOX Rate, and round the result to 1 decimal place.

If NOX Mass is greater than 99,999.9

set LME Gen Total NOXM Array for location to -1, and return result C.

else

return result A.

else

return result B.

Environmental Protection Agency

Page 606 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Otherwise,

LME Gen NOXM Record.\ Iourll) = Current LMEHourly Op Record.\ Iourll)

LME Gen NOXM ifecortf.ParameterCode = "NOXM"

LME Gen NOXMifecorrf.AdjustedHourlyValue = NOXMass

LME Gen NOXM Record.FuelCode = NOXFuel

LME Gen NOXM ifecorrf.OperatingConditionCode = Current LME Hourly Op ifecorrf.OperatingConditionCode

If LME Gen Total NOXM Array for location is greater than or equal to 0,

Add NOXMass to LME Gen Total NOXM Array for location.

If current date in the month of April,

Add NOXMass to LME Gen April NOXM Array for location.

Results:

Result
A

Response

You did not report a single, active, valid [defparm] default record for FuelCode [fuel] in
your monitoring plan.

You did not report a single, active, valid [defparm] default record for FuelCode [fuel]
OperatingConditionCode [cond] in your monitoring plan.

The value calculated for [param] in the LME Hourly record exceeds the maximum
value.

Severity

Critical Error Level 1

B

Critical Error Level 1

C

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Hourly Emissions Data

Environmental Protection Agency

Page 607 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-31

Check Name:	Calculate C02 Mass for LME Unit

Related Former Checks: LME-EXP3D, LME-EXP9D

Applicability:	LME Check

Description:

Specifications:

LME Gen C02M Record = null

If LME Gen Parameters contains "C02M" and Current LME Hourly Op Record is not null,

If Current LME Hourly Op Record. I Lie IC ode list is not null,

C02 Rate = 0
C02 Fuel = null

For each FuelCode in the Current LME Hourly Op ifecorrf.FuelCodeList

Locate all Monitor Default Records for the location and hour where ParameterCode is equal to "C02R",
DefaultPurposeCd = "LM", and FuelCode is equal to the current Fuel Code.

If one and only one record is found, the DefaultValue is greater than 0, and DefaultUnitsOfMeasureCode is equal to
"TNMMBTU",

If C02 Rate is less than the DefaultValue in the retrieved record,
set C02 Rate to the DefaultValue.
set CO2 Fuel to the current FuelCode.

Otherwise,

set LME Gen Total C02M Array for location to -1, LME Gen Fuel Code to the current FuelCode,
and return result A.

If LME Calc Heat Input is not null and is greater than or equal to 0 AND CO2 Rate is greater than 0,

Calculate C02 Mass = LME Calc Heat Input 4 C02 Rate, and round the result to 1 decimal place.

If C02 Mass is greater than 99,999,999.9

set LME Gen Total C02M Array for location to -1, and return result B.

Otherwise,

LME Gen C02M Record.HourlD = Current LME Hourly Op Record.\ Iourll)

LME Gen C02M ifecorrf.ParameterCode = "C02M"

LME Gen CO^Mifecorrf.AdjustedHourlyValue = CO2 Mass

LME Gen C02M Record FuelCode = C02 Fuel

If LME Gen Total C02M Array for location is greater than or equal to 0,
Add CO2 Mass to LME Gen Total C02M Array for location.

Environmental Protection Agency

Page 608 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result	Response	Severity

A	You did not report a single, active, valid [defparm] default record for FuelCode [fuel] in	Critical Error Level 1

your monitoring plan.

B	The value calculated for [param] in the LME Hourly record exceeds the maximum	Critical Error Level 1

value.

Usage:

1	Process/Category:	LME Emissions Data Generation Hourly Emissions Data

Environmental Protection Agency

Page 609 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-32

Check Name:

Calculate HIT Summary Values

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

LME Summary Heat Input Record = null

If location is a common pipe,

tempHIT = LME Gen LTFF Heat Input Array for the location
tempAprilHIT = LME Gen LTFF April Heat Input Array for the location

else

tempHIT = If LME Gen Total Heat Input Array for the location
tempAprilHIT = LME Gen April Heat Input Array for the location

If tempHIT is greater than or equal to 0,

LME Summary Heat Input RecordMonLoclA = current location ID

LME Summary Heat Input ifecortf.ReportingPeriodld = current reporting period ID

LME Summary Heat Input ifecortf.ParameterCode = "HIT"

If LME Gen OS == true and LME Gen Annual == false and Quarter of Reporting Period is equal to 2,

LME Summary Heat Input ifecorrf.CurrentReportingPeriodTotal = tempHIT - tempAprilHIT, rounded to 0 decimal places.

LME Summary Heat Input ifecorrf.CurrentReportingPeriodTotal = tempHIT, rounded to 0 decimal places.

If LME Gen OS == true,

If Quarter of Reporting Period is equal to 2,

LME Summary Heat Input itecortf.OzoneSeasonToDateTotal = tempHIT - tempAprilHIT, rounded to 0 decimal
places.

else if Quarter of Reporting Period is equal to 3,

LME Summary Heat Input itecortf.OzoneSeasonToDateTotal = tempHIT, rounded to 0 decimal places.

else if Quarter of Reporting Period is equal to 4 AND LME Year Start Quarter is less than 4,

Locate the Op Supp Data records for the location WHERE the reporting period is the third quarter of the Year of
the Reporting Period and OpTypeCode = "HIT".

If not found,

set LME Summary Heat Input ifecorrf.OzoneSeasonToDateTotal to null, and return result A.

Otherwise,

LME Summary Heat Input ifecorrf.OzoneSeasonToDateTotal = OpValue in the retrived record.

if Quarter of Reporting Period is equal to 3 or 4 AND LME Year Start Quarter is less than 3,

Locate the Op Supp Data records for the location WHERE the reporting period is the second quarter of the Year of
the Reporting Period and OpTypeCode = "HITOS".

If not found,

set LME Summary Heat Input ifecorrf.OzoneSeasonToDateTotal to null, and return result A.

Otherwise,

add OpValue in the retrieved record to LME Summary Heat Input ifecorrf.OzoneSeasonToDateTotal.

else

Environmental Protection Agency

Page 610 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If LME Gen Annual == true,

LME Summary Heat Input Record. YearToDateTotal = LME Summary Heat Input ifecortf.CurrentReportingPeriodTotal,
rounded to 0 decimal places.

If the quarter of the current reporting period is greater than the LME Year Start Quarter,

For each reporting period in the year of the current reporting period and in a quarter that is on or after the LME
Year Start Quarter and is prior to the current reporting period.

Locate the Op Supp Data records for the location and reporting period WHERE the OpTypeCode =
"HIT".

If not found,

set LME Summary Heat Input Recorrf. YearToDateTotal to null, and return result B.
Otherwise,

add OpValue in the retrieved record to LME Summary Heat Input Record. YearToDateTotal.

Results:

Result
A

Response

The program could not determine ozone-season-to-date totals for [osparam], because the

Severity

Critical Error Level 1

Op Supp Data record for this parameter is missing for one or more previous reporting
periods. If you have submitted emissions data for prior quarters, you should be able to
retrieve these records by logging on to the EPA host.

B

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Summary Value Data

Environmental Protection Agency

Page 611 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-33

Check Name:

Calculate OPTIME Summary Values

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

LME Summary Op Time Record = null

If location is a unit AND LME Gen Total Op Time Array for the location is greater than or equal to 0,

LME Summary Op Time Record.MonLocId = current location ID

LME Summary Op Time ifecortf.ReportingPeriodld = current reporting period ID

LME Summary Op Time ifecortf.ParameterCode = "OPTIME"

If LME Gen OS == true and LME Gen Annual == false and Quarter of Reporting Period is equal to 2,

LME Summary Op Time ifecorrf.CurrentReportingPeriodTotal = LME Gen Total Op Time Array for the location - LME
Gen April Op Time Array for the location.

LME Summary Op Time ifecorrf.CurrentReportingPeriodTotal = LME Gen Total Op Time Array for the location.

If LME Gen OS == true,

If Quarter of Reporting Period is equal to 2,

LME Summary Op Time ifecorrf.OzoneSeasonToDateTotal = LME Gen Total Op Time Array for the location -
LME Gen April Op Time Array for the location.

else if Quarter of Reporting Period is equal to 3,

LME Summary Op Time ifecorrf.OzoneSeasonToDateTotal = LME Gen Total Op Time Array for the location.

else if Quarter of Reporting Period is equal to 4 AND LME Year Start Quarter is less than 4,

Locate the Op Supp Data records for the location WHERE the reporting period is the third quarter of the Year of
the Reporting Period and OpTypeCode = "OPTIME".

If not found,

set LME Summary Op Time itecortf.OzoneSeasonToDateTotal to null, and return result A.

Otherwise,

LME Summary Op Time ifecorrf.OzoneSeasonToDateTotal = OpValue in the retrived record.

if Quarter of Reporting Period is equal to 3 or 4 AND LME Year Start Quarter is less than 3,

Locate the Op Supp Data records for the location WHERE the reporting period is the second quarter of the current
year and OpTypeCode = "OSTIME".

If not found,

set LME Summary Op Time itecortf.OzoneSeasonToDateTotal to null.

Locate the Facility record for the location.

If the First ECMPS Reporting Period in the retrieved record is not null and is on or prior to the second
quarter of the current year,

return result A.

Otherwise,

add OpValue in the retrieved record to LME Summary Op Time ifecorrf.OzoneSeasonToDateTotal.

else

Environmental Protection Agency

Page 612 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If LME Gen Annual == true,

LME Summary Op Time ifecorrf.YearToDateTotal = LME Summary Op TwMeifecortf.CurrentReportingPeriodTotal.

If the quarter of the current reporting period is greater than the LME Year Start Quarter,

For each reporting period in the year of the current reporting period and in a quarter that is on or after the LME
Year Start Quarter and is prior to the current reporting period.

Locate the Op Supp Data records for the location and reporting period WHERE the OpTypeCode =
"OPTIME".

If not found,

set LME Summary Op Time ifecorrf.YearToDateTotal to null,

Locate the Facility record for the location.

If the First ECMPS Reporting Period in the retrieved record is not null and is on or prior to the
LME Year Start Quarter,
return result B.

Otherwise,

add OpValue in the retrieved record to LME Summary Op Time itecortf.YearToDateTotal.

Results:

Result

B

Response

The program could not determine ozone-season-to-date totals for [osparam], because the
Op Supp Data record for this parameter is missing for one or more previous reporting
periods. If you have submitted emissions data for prior quarters, you should be able to
retrieve these records by logging on to the EPA host.

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

Severity

Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

LME Emissions Data Generation Summary Value Data

Environmental Protection Agency

Page 613 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-34

Check Name:

Calculate OPHOURS Summary Values

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

LME Summary Op Hours Record = null

If location is a unit AND LME Gen Total Op Time Array for the location is greater than or equal to 0,

LME Summary Op Hours Record.MonLocld = current location ID

LME Summary Op Hours ifecortf.ReportingPeriodld = current reporting period ID

LME Summary Op Hours ifecortf.ParameterCode = "OPHOURS"

If LME Gen OS == true and LME Gen Annual == false and Quarter of Reporting Period is equal to 2,

LME Summary Op Hours ifecorrf.CurrentReportingPeriodTotal = LME Gen Total Op Hours Array for the location -
LME Gen April Op Hours Array for the location.

else

LME Summary Op Hours ifecorrf.CurrentReportingPeriodTotal = LME Gen Total Op Hours Array for the location.

If LME Gen OS == true,

If Quarter of Reporting Period is equal to 2,

LME Summary Op Hours ifecorrf.OzoneSeasonToDateTotal = LME Gen Total Op Hours Array for the location -
LME Gen April Op Hours Array for the location.

else if Quarter of Reporting Period is equal to 3,

LME Summary Op Hours ifecorrf.OzoneSeasonToDateTotal = LME Gen Total Op Hours Array for the location.

else if Quarter of Reporting Period is equal to 4 AND LME Year Start Quarter is less than 4,

Locate the Op Supp Data records for the location WHERE the reporting period is the third quarter of the Year of
the Reporting Period and OpTypeCode = "OPHOURS".

If not found,

set LME Summary Op Hours ifecorrf.OzoneSeasonToDateTotal to null, and return result A.

Otherwise,

LME Summary Op Hours ifecorrf.OzoneSeasonToDateTotal = OpValue in the retrived record.

if Quarter of Reporting Period is equal to 3 or 4 AND LME Year Start Quarter is less than 3,

Locate the Op Supp Data records for the location WHERE the reporting period is the second quarter of the current
year and OpTypeCode = "OSHOURS".

If not found,

set LME Summary Op Hours ifecorrf.OzoneSeasonToDateTotal to null, and return result A.

Otherwise,

add OpValue in the retrieved record to LME Summary Op Hours itecortf.OzoneSeasonToDateTotal.
If LME Gen Annual == true,

LME Summary Op Hours Record. YearToDateTotal = LME Summary Op Hours itecortf.CurrentReportingPeriodTotal.
If the quarter of the current reporting period is greater than the LME Year Start Quarter,

For each reporting period in the year of the current reporting period and in a quarter that is on or after the LME
Year Start Quarter and is prior to the current reporting period.

Environmental Protection Agency

Page 614 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Locate the Op Supp Data records for the location and reporting period WHERE the OpTypeCode =
"OPHOURS".

If not found,

set LME Summary Op Hours itecortf.YearToDateTotal to null, and return result B.
Otherwise,

add OpValue in the retrieved record to LME Summary Op Hours Record. YearToDateTotal.

Results:

Result
A

Response

The program could not determine ozone-season-to-date totals for [osparam], because the

Severity

Critical Error Level 1

Op Supp Data record for this parameter is missing for one or more previous reporting
periods. If you have submitted emissions data for prior quarters, you should be able to
retrieve these records by logging on to the EPA host.

B

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Summary Value Data

Environmental Protection Agency

Page 615 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-35

Check Name:

Calculate S02M Summary Values

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

LME Summary S02M Record = null

If location is a unit, LME Gen Annual == true, AND LME Gen Total S02M Array for the location is greater than or equal to 0,

Locate a Monitor Method record for the unit where the ParameterCode is equal to "S02M", and the MethodCode is equal to
"LME", BeginDate is on or before the first day of the reporting period, and the EndDate is null or is on or after the last day of the
reporting period.

LME Summary S()2M Record. Mon I ,oc Id = current location ID

LME Summary S0.2M ifecortf.ReportingPeriodld = current reporting period ID

LME Summary S()2M /feewrf. ParameterCode = "S02M"

LME Summary S0.2M ifecortf.CurrentReportingPeriodTotal = LME Gen Total S02M Array for the location / 2000,
rounded to one decimal place.

LME Summary 502Mifecorrf.YearToDateTotal = LME Summary S0.2M itecortf.CurrentReportingPeriodTotal.

If the quarter of the current reporting period is greater than the LME Year Start Quarter,

For each reporting period in the year of the current reporting period and in a quarter that is on or after the LME
Year Start Quarter and is prior to the current reporting period.

Locate the Op Supp Data records for the location and reporting period WHERE the OpTypeCode =
"S02M".

If not found,

set LME Summary 502Mifecorrf.YearToDateTotal to null, and return result A.
Otherwise,

add OpValue in the retrieved record to LME Summary 502Mifecorrf.YearToDateTotal.

If found,

Results:

Result
A

Response

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Summary Value Data

Environmental Protection Agency

Page 616 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-36

Check Name:

Calculate C02M Summary Values

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

LME Summary C02M Record = null

If location is a unit, LME Gen Annual == true, AND LME Gen Total C02M Array for the location is greater than or equal to 0,

Locate a Monitor Method record for the unit where the ParameterCode is equal to "C02M", and the MethodCode is equal to
"LME", BeginDate is on or before the first day of the reporting period, and the EndDate is null or is on or after the last day of the
reporting period.

LME Summary C02M Record. MonLocId = current location ID

LME Summary C0.2M ifecortf.ReportingPeriodld = current reporting period ID

LME Summary C02M Record.ParameterCode = "C02M"

LME Summary C02M ifecorrf.CurrentReportingPeriodTotal = LME Gen Total C02M Array for the location.
LME Summary C02MRecorrf. YearToDateTotal = LME Summary C02Mifecorrf.CurrentReportingPeriodTotal.

If the quarter of the current reporting period is greater than the LME Year Start Quarter,

For each reporting period in the year of the current reporting period and in a quarter that is on or after the LME
Year Start Quarter and is prior to the current reporting period.

Locate the Op Supp Data records for the location and reporting period WHERE the OpTypeCode =
"C02M".

If not found,

set LME Summary C02Mi?ec0«?. YearToDateTotal to null, and return result A.
Otherwise,

add OpValue in the retrieved record to LME Summary C02Mifecorrf.YearToDateTotal.

If found,

Results:

Result
A

Response

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Summary Value Data

Environmental Protection Agency

Page 617 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-37

Check Name:

Calculate NOXM Summary Values

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

LME Summary NOXM Record = null

If location is a unit AND LME Gen Total NOXM Array for the location is greater than or equal to 0,

Locate a Monitor Method record for the unit where the ParameterCode is equal to "NOXM", and the MethodCode is equal to
"LME", BeginDate is on or before the first day of the reporting period, and the EndDate is null or is on or after the last day of the
reporting period.

If found,

LME Summary NOXM RecordMonLoclA = current location ID

LME Summary NOXM ifecortf.ReportingPeriodld = current reporting period ID

LME Summary NOXM ifecortf.ParameterCode = "NOXM"

If LME Gen OS == true and LME Gen Annual == false and Quarter of Reporting Period is equal to 2,

LME Summary NOXM ifecorrf.CurrentReportingPeriodTotal = {LME Gen Total NOXM Array for the location -
LME Gen April NOXM Array for the location) / 2000, rounded to one decimal place.

LME Summary NOXM ifecorrf.CurrentReportingPeriodTotal = LME Gen Total NOXM Array for the location /
2000, rounded to one decimal place.

If LME Gen OS == true,

If Quarter of Reporting Period is equal to 2,

LME Summary NOXM ifecorrf.OzoneSeasonToDateTotal = {LME Gen Total NOXM Array for the
location - LME Gen April NOXM Array for the location) / 2000, rounded to one decimal place.

else if Quarter of Reporting Period is equal to 3,

LME Summary NOXM ifecorrf.OzoneSeasonToDateTotal = LME Gen Total NOXM Array for the
location / 2000, rounded to one decimal place.

else if Quarter of Reporting Period is equal to 4 AND LME Year Start Quarter is less than 4,

Locate the Op Supp Data records for the location WHERE the reporting period is the third quarter of the
Year of the Reporting Period and OpTypeCode = "NOXM".

If not found,

set LME Summary NOXM itecortf.OzoneSeasonToDateTotal to null, and return result A.
Otherwise,

LME Summary NOXM itecortf.OzoneSeasonToDateTotal = OpValue in the retrived record.

if Quarter of Reporting Period is equal to 3 or 4 AND LME Year Start Quarter is less than 3,

Locate the Op Supp Data records for the location WHERE the reporting period is the second quarter of the
current year and OpTypeCode = "NOXMOS".

If not found,

set LME Summary NOXM itecortf.OzoneSeasonToDateTotal to null, and return result A.
Otherwise,

add OpValue in the retrieved record to LME Summary NOXM
ifecorrf.OzoneSeasonT oDateT otal.

else

Environmental Protection Agency

Page 618 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If LME Gen Annual == true,

LME Summary NOXM Recortf. YearToDateTotal = LME Summary NOXM
ifecorrf.CurrentReportingPeriodTotal.

If the quarter of the current reporting period is greater than the LME Year Start Quarter,

For each reporting period in the year of the current reporting period and in a quarter that is on or after the
LME Year Start Quarter and is prior to the current reporting period.

Locate the Op Supp Data records for the location and reporting period WHERE the OpTypeCode
= "NOXM".

If not found,

set LME Summary NOXM itecortf.YearToDateTotal to null, and return result B.
Otherwise,

add OpValue in the retrieved record to LME Summary NOXMifecorrf.YearToDateTotal.

Results:

Result
A

Response

The program could not determine ozone-season-to-date totals for [osparam], because the

Severity

Critical Error Level 1

Op Supp Data record for this parameter is missing for one or more previous reporting
periods. If you have submitted emissions data for prior quarters, you should be able to
retrieve these records by logging on to the EPA host.

B

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Summary Value Data

Environmental Protection Agency

Page 619 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-38

Check Name:	Calculate NOXR Summary Values

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

LME Summary NOXR Record = null

If LME Summary Heat Input Record and LME Summary NOXM Record are both not null,

Locate a Program record for the unit where the ProgramCode is equal to "ARP", the Class is not equal to "NA",
UnitMonitorCertBeginDate is on or before the first day of the reporting period, and the EndDate is null or is on or after the last day
of the reporting period.

If found,

LME Summary NOXR RecordMonLoclA = current location ID

LME Summary NOXR ifecortf.ReportingPeriodld = current reporting period ID

LME Summary NOXR ifecorrf.ParameterCode = "NOXR"

If LME Summary NOXM itecortf.ReportingPeriodTotal == 0

LME Summary NOXR itecortf.CurrentReportingPeriodTotal = 0

else

LME Summary NOXR itecortf.CurrentReportingPeriodTotal = LME Gen Total NOXM Array for the location /
LME Summary Heat Input Record.ReportingPeriodTotai, rounded to 3 decimal places.

If the quarter of the current reporting period is greater than the LME Year Start Quarter,

If LME Summary Heat Input Record. YearToDateTotal is not null,

NOxTotal = LME Gen Total NOXM Array for the location.

For each reporting period in the year of the current reporting period and in a quarter that is on or after the
LME Year Start Quarter and is prior to the current reporting period.

Locate the Op Supp Data records for the location and reporting period WHERE the OpTypeCode
= "NOXR".

If not found,

set LME Summary NOXR Record. YearToDateTotal to null, and return result A.

Otherwise,

NOXRValue = Op Value.

Locate the Op Supp Data records for the location and reporting period WHERE the
OpTypeCode = "HIT".

If not found,

set LME Summary NOXR Record. YearToDateTotal to null, and return result B.
Otherwise,

Add OpValue * NOXRValue (rounded to 1 decimal) to NOxTotal.

If NOxTotal == 0,

LME Summary NOXR Record. YearToDateTotal = 0.

else

Environmental Protection Agency

Page 620 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

LME Summary XO.XR Record. YearToDateTotal = NOxTotal ILME Summary Heat Input
ifecortf.YearToDateTotal, rounded to 3 decimal places.

else

LME Summary NOXR Record. YearToDateTotal = LME Summary NOXR itecortf.CurrentReportingPeriodTotal.

Results:

Result

B

Response

The program could not determine year-to-date for [param], because the Op Supp Data
record for this parameter is missing for one or more previous reporting periods. If you
have submitted emissions data for prior quarters, you should be able to retrieve these
records by logging on to the EPA host.

The program could not determine year-to-date for [param], because the Op Supp Data
record for HIT is missing for one or more previous reporting periods. If you have
submitted emissions data for prior quarters, you should be able to retrieve these records
by logging on to the EPA host.

Severity

Critical Error Level 1

Critical Error Level 1

Usage:
1

Process/Category:

LME Emissions Data Generation Summary Value Data

Environmental Protection Agency

Page 621 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-40

Check Name:	Check LME MHHI Indicator

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

If Current LME Hourly Op Record is not null,

If MUHUndicator is equal to 1,

If LME Gen HI Substitute Data is not equal to "MHHI",
set Generate LME to false, and return result A.

Results:

Result	Response	Severity

A	You reported a MffiHIndicator, but you did not report an active LTFF heat input	Critical Error Level 1

method with a SubstituteDataCode of "MHHI".

Usage:

1	Process/Category:	LME Emissions Data Generation Hourly Emissions Data

Environmental Protection Agency

Page 622 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-44

Check Name:

Check Fuel Codes against LTFF Records

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

If Current LME Hourly Op Record is not null and LME Gen HI Method = "LTFF",

If MHHIIndicator is not equal to 1 and FuelCodeList is not null,

Locate all Unit Stack Configuration Records where the unit location is the location in the Current LME Hourly Op
Record, the StackID begins with "CP", the BeginDate and BeginHour is on or before the Date and Hour in the Current
LME Hourly Op Record, and the EndDate is null or the EndDate and EndHour is on or after the Date and Hour in the
Current LME Hourly Op Record.

For each Fuel Code in FuelCodeList,

Locate a LTFF Record for the configuration and reporting period where the location is the location in the Current
LME Hourly Op Record or is any of the common pipes in the retrieved Unit Stack Configuration Records, and
the FuelCode of the associated fuel flow system is equal to the FuelCode in the FuelCodeList that is being
evaluated.

If not found for any FuelCode,

set Generate LME to false, and return result A.

Results:

Result
A

Response

You did not report a Long Term Fuel Flow record for a fuel flow system for one or more
fuels in the FuelCodeList in the LME Hourly record. If you burn a fuel that is not
measured by a fuel flow meter, you must use maximum hourly heat input for the hour.

Severity

Critical Error Level 1

Usage:
1

Process/Category:	LME Emissions Data Generation Hourly Emissions Data

Environmental Protection Agency

Page 623 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-45

Check Name:	Duplicate LTFF Record

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

For the LTFF record:

Locate another LTFF record for the location with same ReportingPeriod, MonitoringSystemID, and FuelFlowPeriodCode as the
current record.

If found,

return result A.

Results:

Result	Response	Severity

A	Another [recordtype] record already exists with the same [fieldnames].	Fatal

Usage:

1	Process/Category:	LME Emissions Data Generation LTFF Heat Input Data

Environmental Protection Agency

Page 624 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-18

Check Name:	Check LME Begin Hour

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

For the LME Hourly Op record:

If BeginHour is null or is not between 0 and 23 (inclusive),
return result A.

Results:

Result	Response	Severity

A	The Hour is missing or invalid.	Fatal

Usage:

1	Process/Category:	Emissions Data Entry Screen Evaluation Hourly Op Data Evaluation

Environmental Protection Agency

Page 625 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-19

Check Name:	Check LME Begin Date

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

For the LME Hourly Op record:

If BeginDate is null or is not within the reporting period,
return result A.

Results:

Result	Response	Severity

A	The Date is missing or not within the reporting period.	Fatal

Usage:

1	Process/Category:	Emissions Data Entry Screen Evaluation Hourly Op Data Evaluation

Environmental Protection Agency

Page 626 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-20

Check Name:	Duplicate LME Hourly Op Record

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

For the LME Hourly Op record:

Locate another Hourly Op record for the location with same BeginDate and BeginHour.

If found,

return result A.

Results:

Result	Response	Severity

A	Another [recordtype] record already exists with the same [fieldnames].	Fatal

Usage:

1	Process/Category:	Emissions Data Entry Screen Evaluation Hourly Op Data Evaluation

Environmental Protection Agency

Page 627 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	LME-23

Check Name:	Check LME Data Entry Screen Op Time

Related Former Checks:

Applicability:	LME Check

Description:

Specifications:

For the LME Hourly Op record:

If OpTime is null, or is not between 0 and 1 inclusive,
return result A.

Results:

Result	Response	Severity

A	The [fieldname] reported in the LME Hourly record is missing or invalid.	Critical Error Level 1

Usage:

1	Process/Category:	Emissions Data Entry Screen Evaluation Hourly Op Data Evaluation

Environmental Protection Agency

Page 628 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

LME-25

Check Name:

Check LME Data Entry Screen Load Value

Related Former Checks:

Applicability:

LME Check

Description:

Specifications:

For the LME Hourly Op record:

If LoadValue is null,

If OperatingTime is greater than 0,
return result A.

else if LoadValue is less than 0,
return result A.

else

If OperatingTime is equal to 0,
return result B.

Results:

Result

A

B

Response

The [fieldname] reported in the LME Hourly record is missing or invalid.

You reported a LoadValue in the LME Hourly record. This field should be blank for a

non-operating hour.

Severity

Critical Error Level 1
Non-Critical Error

Usage:
1

Process/Category:	Emissions Data Entry Screen Evaluation Hourly Op Data Evaluation

Environmental Protection Agency

Page 629 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

Check Name:

Related Former Checks
Applicability:

Description:

Specifications:

For the LTFF record:

If the Quarter of the reporting period is not equal to 2,
If the FuelFlowPeriodCode is not null,
return result A.

LME-43

Check LTFF Fuel Flow Period Code
LME Check

Results:

Result	Response	Severity

A	You reported a FuelFlowPeriodCode in the LTFF record for [key], but this value is only	Critical Error Level 1

appropriate during the second quarter.

Usage:

1	Process/Category:	Emissions Data Entry Screen Evaluation LTFF Data Evaluation

Environmental Protection Agency

Page 630 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Category:
RATA Status

Environmental Protection Agency

Page 631 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	RATSTAT-1

Check Name:	Check Low Sulfur and FLOW Exemptions

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Set CurrentRATAStatus = null.

Set OverrideRATABAF = null.

Set MaxLevelCount = null.

Set FlowRATAExemption = false.

if (CurrentHourlyRecordforRATAStatus.SystemTypeCode begins with "S02")

Locate a record in TestExtensionExemptionRecords for the location where the SystemID is equal to the
CurrentHourlyRecordforRATAStatus.SystemID, the reporting period is the Current Reporting Period, AND the
ExtensionExemptionCode is equal to "LOWSYTD"

if (TestExtensionExemptionRecords is found)

Set CurrentRATAStatus = "IC-Exempt"

else

Locate a record in MonitorQualificalionRecordsByHour for the hour and where MonitoringLocationld = Current
Location

and the QualificationTypeCode is equal to "LOWSULF".
if (MonitorQualificationRecordsByHour is found)

Set CurrentRATAStatus = "IC-Exempt".
else i I' (Current Hourly Record/or RATAStatus.Sx^lcm'lxpcCodc = "FLOW")

Set PeakingBypass = false,
if (CurrentEntityType is equal to "CS" or "MS")

Locate the record in LocationAttributeRecordsByHourLocation for the hour and location,
if (LocationAttributeRecords. I ivpassl nd == 1)

Set PeakingBypass = true.

else

Set PeakingBypass = true.

For each record in UnitStackConfigurationRecordsByHourLocation for the hour and stack location

Locate a record in MonitorQualificationRecordsByHour for the hour where MonitoringLocationld = the
unit location in the UnitStackConfigurationRecordsByHourLocation record and QualificationTypeCode
is equal to "PK" or "SK".

if (MonitorQualificationRecordsByHour is NOT found)

Set PeakingBypass = false.

Exit for.

Environmental Protection Agency

Page 632 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else if (CurrentUnitisPeaking)

Set PeakingBypass = true,
if (PeakingBypassj

Set MaxLevelCount = 1.

else

Locate a record in MonitorQualificalionRecordsByHour for the hour where the MonitoringLocationld = Current Location
and QualificationTypeCode is equal to "PRATA1"

if (MonitorQualificationRecordsByHour is found)

Set MaxLevelCount = 1.

else

Locate a record in MonitorQualificationRecordsByHour for the hour where MonitoringLocationld = Current
Location and the QualificationTypeCode is equal to "PRATA2"

if (MonitorQualificationRecordsByHour is found)

Set MaxLevelCount = 2.

else

Set MaxLevelCount = 3.

Append CurrentHourlyRecordforRATAStatus.SystemlD to FLOWSystemlDArray for the location.

Locate a record in TestExtensionExemptionRecords for the location where the SystemID is equal to the
CurrentHourlyRecordforRATAStatus.SystemID, the ComponentID is equal to the the

CurrentHourlyRecordforRATAStatus.ComponentID the reporting period is the Current Reporting Period, AND the
ExtensionExemptionCode is equal to "FLOWEXP"

if (TestExtensionExemptionRecords is found)

Set FlowRATAExemption = true.

Results:

Result	Response	Severity

Environmental Protection Agency

Page 633 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02/02 RATA Status Evaluation

2	Process/Category:	Emissions Data Evaluation Report	H20 RATA Status Evaluation

3	Process/Category:	Emissions Data Evaluation Report	H20M RATA Status Evaluation

4	Process/Category:	Emissions Data Evaluation Report	NOX RATA Status Evaluation

5	Process/Category:	Emissions Data Evaluation Report	NOXC RATA Status Evaluation

6	Process/Category:	Emissions Data Evaluation Report	S02 RATA Status Evaluation

7	Process/Category:	Emissions Data Evaluation Report	Stack Flow RATA Status Evaluation

Environmental Protection Agency

Page 634 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

RATSTAT-2

Check Name:

Locate Most Recent Prior RATA Test

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set PriorRATARecord = null.

Set InvalidRATARecord = null.

Set ApplicableSystemlDList = null.

If Flow RATA Exemption is true,

Locate all MonitorSystemComponentRecordsforHourandLocation for the location and hour where the ComponentID is equal to
Current!lourly Recordfor RATA Status.ComponcnlW).

For each record found,

Append CurrentHourlyRecordforRATAStatus.SystemlD to the ApplicableSystemlDList.

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the SystemID is in the
ApplicableSystemlDList and the TestResultCode is not equal to "INVALID" and the EndDate/Hour is prior to the
CurrentHourlyRecordforRATAStatus. Date/Hour

if (RATATestRecordsByLocationForQAStatus is found)

Set PriorRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

if (CurrentRATAStatus is null)

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the SystemID is in the
ApplicableSystemlDList and the EndDate/Hour is prior to the Current flour ly Recordfor R1 TAStatus.\ )atc I lour and the
EndDate/Hour is greater than the PriorRATARecord.EndDate/Hour and the TestResultCode is equal to "INVALID".

if (RATATestRecordsByLocationForQAStatus is found)

Set InvalidRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the SystemID is in the
ApplicableSystemlDList and the TestResultCode is equal to "INVALID" and the EndDate/Hour is prior to the
Current Hourly Recordfor R1T. 1 Status .Date Hour

if (RATATestRecordsByLocationForQAStatus is found)

Set InvalidRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

Append MonitorSystemComponentRecordsforHourandLocation.SystemID to the ApplicableSystemlDList.

else

else

Results:

Result

Response

Severity

Environmental Protection Agency

Page 635 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02/02 RATA Status Evaluation

2	Process/Category:	Emissions Data Evaluation Report	H20 RATA Status Evaluation

3	Process/Category:	Emissions Data Evaluation Report	H20M RATA Status Evaluation

4	Process/Category:	Emissions Data Evaluation Report	NOX RATA Status Evaluation

5	Process/Category:	Emissions Data Evaluation Report	NOXC RATA Status Evaluation

6	Process/Category:	Emissions Data Evaluation Report	S02 RATA Status Evaluation

7	Process/Category:	Emissions Data Evaluation Report	Stack Flow RATA Status Evaluation

Environmental Protection Agency

Page 636 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

RATSTAT-3

Check Name:

Locate Most Recent Prior Event

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set PriorRATAEventRecord = null.

If (CurrentRATAStatus is null)

Locate the most recent record in QACertificalionEventRecords where the SystemID is in the ApplicableSystemlDList and
RATARequired is equal to "Y" and the QACertEventDate is either:

a)	prior to the Current Hour ly Record for li. 1 TAStatus.\ )atc I lour OR

b)	equal to both the CurrentHourlyRecordforRATAStatus.Date/Hour and the ConditionalBeginDate/Hour;

AND either:

a)	PriorRATARecordis null OR

b)	QACertEventDate/Hour is after the Priori?^ Mifecortf. EndDate/Hour OR

c)	QACertEventDate/Hour is equal to the i>/orit4714ifecorrf.EndDate/Hour AND (TestCompletionDate is null or the
TestCompletionDate/Hour is after the Priori?^ Z/4i?ecortf. EndDate/Hour)

AND either:

a)	Annual Reporting Requirement is equal to true OR

b)	QACertEventDate/Hour is on or after April 1 of the year of the Current!four lyRecordfor R 1TA Stat us. I )atc
if (QACertificationEventRecords is found)

Set PriorRATAEventRecord = the found record in QACertificationEventRecords.

if (PriorRATAEventRecord is null)

if (PriorRATARecord is null)

Set CurrentRATAStatus = "OOC-No Prior Test or Event"

if (Currentllourly RecordforR. 1T. 1 Status. I 'a ra ill ctcr == "FLOW")

Set OverrideRATABAF = 1.0

else if (InvalidRATARecord is not null AND Prior RATA IJvent Record.QACcrl\.xcnl\)dlc I lour is after
InvalidRA 7L4i?ecora?.EndDate/Hour)

Locate the earliest record in RATATestRecordsByLocationForQAStatus for the location where the SystemID is equal to
the CurrentHourlyRecordforRATAStatus.SystemID and the EndDate/Hour is after the

PriorRATAEventRecord.QACertEverrtDate/YLour and the EndDate/Hour is prior to the CurrentDate/Hour and the
TestResult is equal to "INVALID"

if (RATATestRecordsByLocationForQAStatus is found)

Set InvalidRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

else

Set InvalidRATARecord = null.

Environmental Protection Agency

Page 637 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Usage:

1

2

3

4

5

6

7

Response

Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:

Severity

Emissions Data Evaluation Report	C02/02 RATA Status Evaluation

Emissions Data Evaluation Report	H20 RATA Status Evaluation

Emissions Data Evaluation Report	H20M RATA Status Evaluation

Emissions Data Evaluation Report	NOX RATA Status Evaluation

Emissions Data Evaluation Report	NOXC RATA Status Evaluation

Emissions Data Evaluation Report	S02 RATA Status Evaluation

Emissions Data Evaluation Report	Stack Flow RATA Status Evaluation

Environmental Protection Agency

Page 63 8 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

RATSTAT-4

Check Name:

Check RATA Result

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

if (CurrentRATAStatus is null and PriorRATARecordis not null and PriorRATAEventRecordis null)

Set EvaluateMutiiLevelRATA = true.

if (Pr/0rii47L4i?ec0ra?.QANeedsEvaluationFlag = "Y")

Set CurrentRATAStatus = "Prior Test Not Yet Evaluated".

else if (PriorRATARecord.TestResultCode = null or PriorRATARecord.TestResultCode = "FAILED" or
PriorRATARecord. TestResultCode = "ABORTED")

Locate the most recent record in QACertificalionEventRecords where the SystemID is in the ApplicableSystemlDList and
RATARequired is equal to "Y" and the ConditionalBeginDate/Hour is:

a)	on or prior to the Current I lourly RecordforR. 1T. {Status.\)atc I lour AND

b)	on or after the PriorRATARecord.EndDate/Hour; AND

c)	Annual Reporting Requirement is equal to true OR QACertEventDate/Hour is on or after April 1 of the year of the
Current flourly Recordfor RATA Status.\)dlc.

if (QACertificationEventRecords is found)

Set PriorRATAEventRecord = found record in QACertificationEventRecords.

elseif (PriorRATARecord. TestResultCode = null)

Set CurrentRATAStatus = "OOC-Prior Test Has Critical Errors".

if (Current!lourly RecordforR. 1T. 1 Status. I 'a ra ill ctcr == "FLOW")

Set OverruleR. 1 TAB 1 /•" Prior R. 1T. 1 Record.()xcrd\ 11 iiasAdj ustmcntFactor.

else if (PriorRATARecord.TestResuitCode = "FAILED")

Set CurrentRATAStatus = "OOC-Prior Test Failed".

if (Currentllourly RecordforR. 1T. 1 Status. I 'a ra ill ctcr == "FLOW")

Set OverruleR. 1 TAB 1 /•" PriorR 1T. 1 Record.()xcrd\ 11 iiasAdj ustmentFactor.

else if (PriorRATARecord.TestResuitCode = "ABORTED")

Set CurrentRATAStatus = "OOC-Prior Test Aborted".

if (Currentl lourly RecordforR. 1T. 1 Status. I 'a ra ill ctcr == "FLOW")

Set OverruleR. 1 TAB 1 /•" PriorR 1T. 1 Record.()xcrd\ 11 iiasAdj ustmcntFactor.

Environmental Protection Agency

Page 639 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Usage:

1

2

3

4

5

6

7

Response

Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:

Severity

Emissions Data Evaluation Report	C02/02 RATA Status Evaluation

Emissions Data Evaluation Report	H20 RATA Status Evaluation

Emissions Data Evaluation Report	H20M RATA Status Evaluation

Emissions Data Evaluation Report	NOX RATA Status Evaluation

Emissions Data Evaluation Report	NOXC RATA Status Evaluation

Emissions Data Evaluation Report	S02 RATA Status Evaluation

Emissions Data Evaluation Report	Stack Flow RATA Status Evaluation

Environmental Protection Agency

Page 640 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	RATSTAT-5

Check Name:	Determine Event Conditional Status

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Set SubsequentRATARecord = null.

Set IlATWIlsslngOpDatalnfo = null.

Set RA TA Event Operating Level Count = null.

if (CurrentRATAStatus is null and PriorRATAEventRecord is not null)

if (Priori^ 7L4£Ven?i?ec0rtf.ConditionalDataBeginDate/Hour is null or Current Hourly Recordf or R. 1T. {Status.\)ate I lour is prior to
the Pr/orit4ry4£Ven?ifecorrf.ConditionalDataBeginDate/Hour)

Set CurrentRATAStatus = "OOC-Event".

Set OverrideRATABAF = 1.0.

else

Locate the earliest record in RATATestRecordsByLocationForQAStatus where the SystemID is equal to the
PriorRATAEventRecord.SystemID, the TestResult is not equal to "INVALID" and the EndDate/Hour is on or after the
PriorRATAEventRecord.ConditionaUDataBeginDate/Hour.

if (RATATestRecordsByLocationForQAStotus is found)

Set SubsequentRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

if (RATATest Records By [JocationI''orOAStatus.QAhlccLh\:.yd\uc\Uon\:\-du. = "Y")

Set CurrentRATAStatus = "Recertification Test Not Yet Evaluated".

else if (RATATestRecordsByLocationForQAStatusAestResuitCode is null)

Set CurrentRATAStatus = "OOC-Recertification Test Has Critical Errors".

if (Current Hourly Recordf or It 1T. l.SYata.v. Parameter == "FLOW")

Set OverrideRATABAF = SubsequentRATARecord.Ovem\XBi?isAA]\istmen\£?ictox.

else if (RATATestRecordsByLocationForQAStalus.TestResultCode = "FAILED")

Set CurrentRATAStatus = "OOC-Recertification Test Failed".

if (Current ffourly Recordf or R. 1T. l.SYata.v. Parameter == "FLOW")

Set OverrideRATABAF = SubsequentRATARecord.Ovem\XBi?isAA]\istmen\£?ictox.

else if (RATATestRecordsByLocationForQAStalus.TestResultCode = "ABORTED")

Set CurrentRATAStatus = "OOC-Recertification Test Aborted".

if (Current ffourly Recordf or R. 1T. l.SYata.v. Parameter == "FLOW")

Set OverrideRATABAF = SubsequentRATARecord.Ovem\XBi?isAA]\istmen\£?ictox.

else

if (PriorRATARecordis null)

RequiredLevelCount = MaxLevelCount

Environmental Protection Agency

Page 641 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else (if PriorRATAEventRecord.RATA3Required is equal to "Y")

RequiredLevelCount = 3

else (if PriorRATAEventRecord.RATA2Required is equal to "Y")

RequiredLevelCount = 2

else

RequiredLevelCount = 1

If (number of levels in RATATestRecordsByLocationForQAStatus.OpLeveiCodeList is less than
RequiredLevelCount)

Set CurrentRATAStatus = "OOC-Incomplete Recertification".

if (CurrentHourlyRecordforRATAStatus Parameter == "FLOW")

Set OverrideRATABAF = 5M6se^Men?it4714ifecorrf.OverallBiasAdjustmentFactor.

else

Set RATA Event Operating Level Count to the RequiredLevelCount.

If (InvalidRATARecordis null)

Locate the earliest record in RATATestRecordsByLocationForQAStatus where the SystemID is equal to
the PriorRATAEventRecord.SystemlD, the TestResult is equal to "INVALID" and the EndDate/Hour is
on or after the PriorRATAEventRecord.Con&iiwm&XDzAaBegmDaierilom and is before the
EndDate/EndHour of the RATATestRecordsByLocationForQAStatus record retrieved above.

if (RATATestRecordsByLocationForQAStatus is found)

Set InvalidRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

else

if (PriorRATAEventRecord.RATA3Rsqmred is equal to "Y")

Set RA TA Event Operating Level Count to 3.

else (if PriorRATAEventRecord.RATA2Required is equal to "Y")

Set RA TA Event Operating Level Count to 2.

else

Set RA TA Event Operating Level Count to 1.

if (CurrentRATAStatus is null AND Annual Reporting Requirement == false)

If (SubsequentRATARecord is not null and SubsequentR 1T. 1 Record.I Indl )atc I lour is greater than October 30th
of the year of the Current ffourlyRecordforRATAStatus.\)dlc I lour) OR (SubsequentRATARecord is null and the
Current 11ourly RecordforR 1T. {Status.\)atc I lour is in the 3rd quarter))

Set CurrentRATAStatus = "OOC-Conditional Period Expired".

if (Current ffourly Recordfor R1T. l.SYata.v. Parameter == "FLOW")

Set OverrideRATABAF = 1.0.

if (CurrentRATAStatus is null)

if (PnorRA'lAEvent Record. RATACcrtlAcnt == "Y")

if ({CurrentHourlyRecordforRATAStatus Parameter o "FLOW" and

Prior R 1 TAEventRecord. I AcntCodc = 125) or (Currentllourly RecordforR 1T. 1 Status. I 'a ra ill ctcr ==

Environmental Protection Agency

Page 642 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

"FLOW" and Prior R. 1 TAEventRecord. I AcntCodc = 305))

if (the associated BeginDate of the system in the PriorRATAEventRecord is null)
Set CurrentRATAStatus = "Invalid Monitor System"

else

If (the associated SystemTypeCode of the system in the PriorRATAEventRecord ==

"S02")

Locate the record in LocationProgramRecordsByHourLocation with the latest
UnitMonitorCertBeginDate where the ProgramCode is in set {ARP, CAIRS02}
and the UnitMonitorCertBeginDate is ON OR BEFORE the associated
BeginDate of the system in the PriorRATAEventRecord.

If (the record in LocationProgramRecordsByHourLocalion is not found)

Locate the record in LocationProgramRecordsByHourLocation with the
latest EmissionsRecordingBeginDate where the ProgramCode is in set
{ARP, CAIRS02} and the EmissionsRecordingBeginDate is ON OR
BEFORE the associated BeginDate of the system in the
PriorRA TAEventRecord.

else if (the associated SystemTypeCode of the system in the PriorRATAEventRecord ==
"NOX")

Locate the record in LocationProgramRecordsByHourLocation with the latest
UnitMonitorCertBeginDate where the ProgramCode is in set {ARP, NBP,
NHNOX, CAIRNOX, CAIROS, SIPNOX} and the UnitMonitorCertBeginDate is
ON OR BEFORE the associated BeginDate of the system in the
Prior RA TAEventRecord.

If (the record in LocationProgramRecordsByHourLocation is not found)

Locate the record in LocationProgramRecordsByHourLocation with the
latest EmissionsRecordingBeginDate where the ProgramCode is in set
{ARP, CAIRS02, NBP, NHNOX, CAIRNOX, CAIROS, SIPNOX} and
the EmissionsRecordingBeginDate is ON OR BEFORE the associated
BeginDate of the system in the PriorRATAEventRecord.

else if (the associated SystemTypeCode of the system in the PriorRATAEventRecord ==
"NOXC")

Locate the record in LocationProgramRecordsByHourLocation with the latest
UnitMonitorCertBeginDate where the ProgramCode is in set {NBP, NHNOX,
CAIRNOX, CAIROS, SIPNOX} and the UnitMonitorCertBeginDate is ON OR
BEFORE the associated BeginDate of the system in the PriorRATAEventRecord.

If (the record in LocationProgramRecordsByHourLocation is not found)

Locate the record in LocationProgramRecordsByHourLocation with the
latest EmissionsRecordingBeginDate where the ProgramCode is in set
{NBP, NHNOX, CAIRNOX, CAIROS, SIPNOX} and the
EmissionsRecordingBeginDate is ON OR BEFORE the associated
BeginDate of the system in the PriorRATAEventRecord.

else

Locate the record in LocationProgramRecordsByHourLocation with the latest
UnitMonitorCertBeginDate where the UnitMonitorCertBeginDate is ON OR
BEFORE the associated BeginDate of the system in the PriorRATAEventRecord.

Environmental Protection Agency

Page 643 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If (the record in LocationProgramRecordsByHourLocalion is not found)

Locate the record in LocalionProgramRecordsByHourLocalion with the
latest EmissionsRecordingBeginDate where the
EmissionsRecordingBeginDate is ON OR BEFORE the associated
BeginDate of the system in the PriorRATAEventRecord.

If (the record in LocalionProgramRecordsByHourLocation is not found)

Set CurrentRATAStatus = "Missing Program".

else i I (LocationProgramRecordsBy/fourLocationl Jni tMoni torCcrtl )cadli nc is not null)

if (CurrentDate is prior to the

LocationProgramRecordsByHourLocationUnitMonitorCertDeadhne)
Set CurrentRATAStatus = "IC-Conditional".

else

Set CurrentRATAStatus = "OOC-Conditional Period Expired".

if (Currentllourly ReeordforR. 1T. 1 Status. I 'a ra ill ctcr == "FLOW")
Set OverrideRATABAF = 1.0.

else

if (CurrentDate is prior to the

LocationProgramRecordsByHourLocationUnitMonitorCertBeginDate + 180

days)

Set CurrentRATAStatus = "IC-Conditional".

else

Set CurrentRATAStatus = "OOC-Conditional Period Expired".

if (Currentllourly ReeordforR. 1T. 1 Status. I 'a ra ill ctcr == "FLOW")
Set OverrideRATABAF = 1.0.

If (the number of calendar days ON OR AFTER the PriorRATAEventRecord.QACertEventDate
and ON OR BEFORE the CurrentllourlyReeordforR. 1 TAStatus.] )atc I lour > 180)

Set CurrentRATAStatus = "OOC-Conditional Period Expired".

if (Currentllourly ReeordforR. 1T. 1 Status. I 'a ra ill ctcr == "FLOW")
Set OverrideRATABAF = 1.0.

else if (the quarter of the PriorRATAEventRecord.QACertEverrtDate is equal to the quarter of the
CurrentHourlyRecordforRATAStatus.Date/Hour)

If (the number of calendar days ON OR AFTER the
PriorRATAEventRecord.QACertEventD&te and ON OR BEFORE the
CurrentHourlyRecordforRATAStotus.Date/Hour > 90)

If (Rpt Period Op Hours Accumulator Array for the location == -1)
Set CurrentRATAStatus = "Invalid Op Data".

else if (the number of calendar days ON OR AFTER the
PriorRATAEventRecord.QACertEventD&te and ON OR BEFORE the

Environmental Protection Agency

Page 644 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Current /four ly Record for R. 1 TAStatus.\ )atc I lour is equal to Rpt Period Op Days
Accumulator Array for the location)

Set CurrentRATAStatus = "OOC-Conditional Period Expired".

if (Current ffourly RecordforR. 1T. 1 Status. I 'a ra ni ctcr == "FLOW")
Set OverrideRATABAF = 1.0.

else

Set CurrentRATAStatus = "IC-Conditional".

else

Set CurrentRATAStatus = "IC-Conditional".

else if (Pr/orit4714£Ven?ifecorrf.MinOpDaysPriorQuarter is null)

Set Prior R 1 TALvent Record. Mi nOpDavsPriorQuartcr = 0
Set PriorRATAEventRecord.yi&xOpDaysPnorQu&rter = 0

For each quarter beginning with the quarter of the

PriorRATAEventRecord.QACertEventDate and continuing through the quarter BEFORE
the CurrentHourlyRecordforRATAStotus.Date/Hour :

if (EarliestLocationReportDate <= the last day of the quarter being checked)

Locate the record in OperatingSuppDataRecordsbyLocation where the
OpTypeCode is equal to "OPDAYS" and the reporting period is equal to
the quarter being checked.

if (OperatingSuppDataRecordsbyLocation is not found)

Locate the record in ReportingFrequency By Location where
CalendarYear/Quarter are equal to the quarter being checked.

if found, and (the quarter being checked is 2 or 3, or
ReportingFrequency By Location.ReportingFrequencyCode is
equal to "Q"),

Set Prior R 1 TAI'JventRecord.orQuartcr =
-1

Set RATAMissingOpDatalnfo = "[YEAR] Q[QTR]"
(where [YEAR] is the year of the quarter being checked
and [QTR] is the number of the quarter being checked.)
exit for.

else

If the quarter being checked is the quarter of the
Prior RA TAEventRecord. QACertEventDate

If (OperatingSuppDataRecordsby Location.Op VaI lie

MINUS the number of calendar days in the quarter

being checked that are PRIOR to the

Prior RATA/^vent Record.QACal].\cnl\)dlc > 0)

Set

Prior R 1 lAIivent Record. M i nOp I )a vs I 'ri orQuar

ter =

OperatingSuppDataRecordsby Location. ()p Va I

Environmental Protection Agency

Page 645 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

ue MINUS the number of calendar days in the
quarter being checked that are PRIOR to the
PriorRATAEventRecord. QACertEventDate

If (OperatingSuppDataRecordsby Location.Op VaI lie is

less than the number of calendar days in the quarter
being checked that are ON OR AFTER the
PriorRA TAEventRecord. QACertEventDate)

Set

PriorRATAEventRecordMaxOpDaysPriorQua
rter =

OperatingSuppDataRecordsby Locati on. ()p Va I

ue.

Set

PriorRATAEventRecord.MaxOpDaysPriorQua
rter = the number of calendar days in the
quarter being checked that are ON OR AFTER
the

Prior RA TAEventRecord. QACertEventDate.

Set Prior R 1 TALJvent Record.orQuartcr =
Prior RA TAEventRecord. MinOpDay sPri orQuarter +
OperatingSuppDataRecordsbyLocation. Op Value.
Set Prior R 1TA Event Record.Max( )pl)avs PriorQuarter
= PriorRATAEventRecord.MaxOpDaysPriorQuarter +
OperatingSuppDataRecordsbyLocation. Op Value.

if (PriorRATAEventRecordMinOpDaysPnoxQuaxtex == -1
set CurrentRATAStotus to "Missing Op Data"

else if (PriorR 1 TAEventRecord.MinOpDavsPriorQuarter + Rpt Period Op Days
Accumulator Array for the Location > 90)

Set CurrentRATAStotus = "OOC-Conditional Period Expired".

if (Current ttourly Recordf or R. 1'/'/ l.SYata.v. Parameter == "FLOW")
Set OverrideRATABAF = 1.0.

else if (PriorR4TAEventRecord.M.axOpDaysPnorQ\mrter + Rpt Period Op Days
Accumulator Array for the Location > 90)

Set CurrentRATAStotus = "Undetermined-Conditional Data".

else

Set CurrentRATAStotus = "IC-Conditional".

else

Set CurrentRATAStotus = "IC-Conditional".

else

If (the quarter of the PriorR4TAEventRecord.Conditiona\BeginDate is equal to the quarter of the
CurrentHourlyRecordf orRATAStatus. Date/Hour )

Environmental Protection Agency

Page 646 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Count the number of HourlyOpData records for the location where OpTime is greater than 0 and
Date/Hour is ON OR AFTER the i>/0rii47L4.EV«tfi?ec0ra?.ConditionalBeginDate/Hour and ON
OR BEFORE Current ffourlyRecordforR. 1 TAStatus.\)atc I lour,

If the number > 720,

Set CurrentRATAStatus = "OOC-Conditional Period Expired".

if (Current ffourly RecordforR. 1T. 1 Status. I 'a ra ill ctcr == "FLOW")
Set OverrideRATABAF = 1.0.

else

Set CurrentRATAStatus = "IC-Conditional".

if (Prior RATA IJvent Record.Min()p\ IoLirsPriorQLiartcr is null)

Set Prior R 1 TATvent Record. Mi nOpI kmrsPri orQuartcr = 0
Set PriorRA TAIJventRecord.Mdx()p\ IoLirsPriorQLiartcr = 0

for each quarter beginning with the quarter of the

PriorRATAEventRecord.Conditiona\BegmDate and continuing through the quarter
BEFORE the Cur rent Hourly RecordforR. 1 TAStatus.i )atc I lour:

if (EarliestLocalionReportDale <= the last day of the quarter being checked)

if (Annual Reporting Requirement == false AND the quarter being
checked == 2)

Locate the record in OperatingSuppDataRecordsbyLocation
where the OpTypeCode is equal to "OSHOURS" and the
reporting period is equal to the quarter being checked.

else

Locate the record in OperatingSuppDataRecordsbyLocation

where the OpTypeCode is equal to "OPHOURS", FuelCode is
null, and the reporting period is equal to the quarter being
checked.

if (OperatingSuppDataRecordsbyLocation is not found)

Locate the record in ReportingFrequency By Location where
CalendarYear/Quarter are equal to the quarter being checked.

if found, and (the quarter being checked is 2 or 3, or
ReportingFrequency By Location.ReportingFrequencyCode is
equal to "Q"),

Set Prior RATA IJvent Record.Min()p\ IoLirsPriorQLiartcr
= -1

Set RATAMissingOpDatalnfo = "[YEAR] Q[QTR]"
(where [YEAR] is the year of the quarter being checked
and [QTR] is the number of the quarter being checked.)
exit for.

else

Environmental Protection Agency

Page 647 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

If the quarter being checked is the quarter of the
Prior R 1 TALJvent Record.Condili onal I icgi n I )atc

If (OperatingSuppDataRecordsby Location. Op Va I ue

MINUS the number of calendar hours in the quarter
being checked that are PRIOR to the
PriorRATAEventRecord.Con&iivmaSiegmDaidYiom >

0)

Set

Prior R 1 TAIivent Record. M i nOpI IoursPri orQu

arter =

OperatingSuppDataRecordsby Location. ()p Va I

ue MINUS the number of calendar hours in the
quarter being checked that are PRIOR to the
PriorR 1 TALJvent Record.Condi tional I icgi n I )at
e/Hour

If (OperatingSuppDataRecordsby Location. Op Va I lie is

less than the number of calendar hours in the quarter
begin checked that are ON OR AFTER the
PriorRATAEventRecord.Con&iivmaSiegmDaidYiom)

Set

Prior RATALJvent Record.Mdx()p\ IoursPriorQu

arter =

OperatingSuppDataRecordsby Location. ()p Va I

ue.

Set

PriorRA TAIJventRecord.Mdx()p\ IoursPriorQu

arter = the number of calendar hours in the
quarter being checked that are ON OR AFTER
the

PriorR 1 TALJventRecord.Condi tional I icgi n I )at
e/Hour.

else

Set Prior RATA LJvent Record.Min()p\ IoursPriorQuartcr
= Prior R 1T. 1 Invent Record. Mi nOp I Io ursPri orQiiartcr +
OperatingSuppDataRecordsbyLocation. Op Value.

Set PriorR 1TALJventRecord.Md\< )pl lour s PriorQuarter
= Prior RATA LJvent Record.Mdx()p\ IoursPriorQuartcr +
OperatingSuppDataRecordsbyLocation. Op Value.

if (Prior RATA LJvent Record.Min()p\ IoursPriorQuartcr == -1)
set CurrentRATAStatus to "Missing Op Data"

else if (Rpt Period Op Days Accumulator Array for the location == -1)

if (Prior RATA LJvent Record.Min()p\ IoursPriorQuartcr > 720)

Set CurrentRATAStatus = "OOC-Conditional Period Expired".

if (Current ffourly Recordfor R. 1'/'/ l.SYata.v. Parameter == "FLOW")

Environmental Protection Agency

Page 648 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Usage:

1

2

3

4

5

6

7

Response

Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:
Process/Category:

else

else

Set OverrideRATABAF = 1.0.

Set CurrentRATAStatus = "Invalid Op Data".

if (Prior RATA IJvent Record.Min()p\ lours PriorQuarter + Rpt Period Op Hours
Accumulator Array for the Location > 720)

Set CurrentRATAStatus = "OOC-Conditional Period Expired".

if (Current Hourly Recordfor R 1'/'/ l.SYata.v. Parameter == "FLOW")
Set OverrideRATABAF = 1.0.

else if (Pr/or£Ven?ifecorrf.MaxOpHoursPriorQuarter + Rpt Period Op Hours
Accumulator Array for the Location > 720)

Set CurrentRATAStatus = "Undetermined-Conditional Data".

else

Set CurrentRATAStatus = "IC-Conditional".

Severity

Emissions Data Evaluation Report	C02/02 RATA Status Evaluation

Emissions Data Evaluation Report	LOO RATA Status Evaluation

Emissions Data Evaluation Report	LOOM RATA Status Evaluation

Emissions Data Evaluation Report	NOX RATA Status Evaluation

Emissions Data Evaluation Report	NOXC RATA Status Evaluation

Emissions Data Evaluation Report	S02 RATA Status Evaluation

Emissions Data Evaluation Report	Stack Flow RATA Status Evaluation

Environmental Protection Agency

Page 649 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:

RATSTAT-6

Check Name:

Evaluate Prior Multi-Level RATA

Related Former Checks:

Applicability:

CEM Check

Description:

Specifications:

Set PriorRatalsAtiernateSingleLevelRATA = false.

Set ThreeLoadRATAExpirationDate to null.

If (CurrentHourlyRecordforRATAStatus Parameter == "FLOW" AND PriorRATARecord is not null AND CurrentRATAStalus is null,
starts with "IC", or starts with "Undetermined")

Set PriorRatalsAlternateSingleLevelRATA = true.

Set PriorMultiLevelRATARecord = null.

Set InvalidMultiLevelRATARecord = null.

Set PriorMaxLevelRATARecord = null.

if (the number of levels in PriorRATARecord.OpLeveiCodeList is greater than or equal to the MaxLevelCount)

Set PriorRatalsAlternateSingleLevelRATA = false,
exit check.

else if (PriorRATARecord.OpLeveiCodeList contains 2 levels)

Set PriorRatalsAlternateSingleLevelRATA = false,
if (MaxLevelCount o 3)

else if (AnnualReportingRequiremnt == true)

if (PriorRATARecord.OpLevelCodeList contains 1 level and PriorRATARecord.TestClaimCode == "SLC" )

Set PriorRatalsAlternateSingleLevelRATA = false.

if (PriorRatalsAlternateSingleLevelRATA == true AND RATAEventOperatingLevelCount is null or less than 2)

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the SystemID is equal
to the PriorRATARecord.SystemlD and the TestResultCode is not equal to "INVALID" and the EndDate/Hour is prior to
the PriorRATARecord.EndDatefHour, and (the number of operating levels in the OpLevelCodeList is greater than or equal
to 2 or the TestClaimCode == "SLC").

if (RATATestRecordsByLocationForQAStalus is found)

Set PriorMultiLevelRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the SystemID
is equal to the PriorRATARecord.SystemlD and the EndDate/Hour is prior to the
PriorRATARecord.EndDate/ELour and the EndDate/Hour is greater than the

PriorMuItiLevelRATARecord.EndDatefHour and the TestResult is equal to "INVALID", and (the number of
operating levels the OpLevelCodeList is greater than or equal to 2 or the TestClaimCode == "SLC").

if (RATATestRecordsByLocationForQAStatus is found)

Set InvalidMultiLevelRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

exit check.

Environmental Protection Agency

Page 650 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Locate the most recent record in RATATestRecordsByLocalionForQAStatus for the location where the SystemID
is equal to the PriorRATARecord.SystemID and the EndDate/Hour is prior to the

PriorRATARecord.EndDate/ELour and the TestResultCode is equal to "INVALID", and the number of operating
levels the OpLevelCodeList is greater than or equal to 2 or the TestClaimCode == "SLC").

if (RATATestRecordsByLocationForQAStalus is found)

Set InvalidMultiLevelRATARecord = the found record in RATATestRecordsByLocationForQAStalus.

if (PriorMultiLevelRATARecordis not null)

Locate the most recent record in QACertificationEventRecords where the SystemID is equal to the
PriorMultiLevelRATARecord.SystemID and RATA2Required is equal to "Y" and the QACertEventDate is either:

a)	prior to the Current Hourly Recordfor R 1T. [Status.] )atc I lour OR

b)	equal to both the Cur rent 11 our ly Recordf or R 1 TAStatus.\ )atc I lour and the ConditionalBeginDate/Hour;
AND either:

a)	QACertEventDate/Hour is after the PriorMultiLevelRATARecord.EndDate/Hour OR

b)	QACertEventDate/Hour is equal to the PriorMultiLevelRATARecord.EndDate/Hour AND
(TestCompletionDate is null or the TestCompletionDate/Hour is after the
PriorMultiLevelRATARecordJLndDatefRom)

AND either

a)	Annual Reporting Requirement is equal to true OR

b)	QACertEventDate/Hour is on or after April 1 of the year of the Current ffourly Recordf or R 1 TAStatus.\)atc

if (QACertificationEventRecords is found)

Set SubsequentRATARecord = PriorMultiLevelRATARecord.

Set CurrentRataStatus = "OOC-Incomplete Recertification".

Set OverrideRataBaf= 1.0.

else

if (PriorMultiLevelRATARecord .QANeedsEvaluationFlag = "Y")

Set CurrentRATAStatus = "Prior Multi-Level RATA Not Yet Evaluated".

else if (PriorMultiLevelRATARecord TestResultCode = null or PriorMultiLevelRATARecord
.TestResultCode = "FAILED" or PriorMultiLevelRATARecord TestResultCode = "ABORTED")

Set CurrentRataStatus = "OOC-Incomplete QA RATA".

Set OverrideRataBaf= Pr/ori^JMifecortf.OverallBiasAdjustmentFactor.

else if (the number of levels in PriorMuItiLevelRATARecord.OpLeveiCodeList is greater than or equal to
MaxLevelCount)

exit check.

Set CurrentRataStatus = "OOC-Incomplete QA RATA".

Set OverrideRataBaf= PWorif^JMitecortf.OverallBiasAdjustmentFactor.

Environmental Protection Agency

Page 651 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (CurrentRATAStatus is null, starts with "IC", or starts with "Undetermined" AND RATAEventOperalingLevelCount is null or
less than MaxLevelCount))

Set InvalidMultiLevelRATARecord = null.

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the SystemID is equal
to the CurrentHourlyRecordforRATAStatus.SystemlD and the TestResultCode is not equal to "INVALID" and the
EndDate/Hour is prior to the PriorRATARecord.EndDate/Hour and the number of operating levels in the OpLevelCodeList
is equal to the MaxLevelCount.

if (RATATestRecordsByLocationForQAStalus is found)

Set PriorMaxLevelRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

Locate the most recent record in RATATestRecordsByLocalionForQAStatus for the location where the SystemID
is equal to the CurrentHourlyRecordforRATAStatus.SystemlD and the EndDate/Hour is prior to the
PriorRATARecord.EndDate/ELour and the EndDate/Hour is greater than the

PriorMaxLevelRATARecord.EndDate/Hour and the TestResultCode is equal to "INVALID" and the number of
operating levels the OpLevelCodeList is equal to the MaxLevelCount.

if (RATATestRecordsByLocationForQAStatus is found)

Set InvalidMultiLevelRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

else

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the SystemID
is equal to the CurrentHourlyRecordforRATAStatus.SystemlD and the EndDate/Hour is prior to the
PriorRATARecord.EndDate/ELour and the TestResultCode is equal to "INVALID" and the number of operating
levels the OpLevelCodeList is equal to the MaxLevelCount.

if (RATATestRecordsByLocationForQAStatus is found)

Set InvalidMultiLevelRATARecord = the found record in RATATestRecordsByLocationForQAStatus.

if (PriorMaxLevelRATARecord is null)

Set CurrentRATAStatus = "OOC-No Prior Maximum Level RATA".

Set OverrideRataBaf= 1.0.

Locate the most recent record in QACertificationEventRecords where the SystemID is equal to the
CurrentHourlyRecordforRATAStatus.SystemID and

AND either

a)	MaxLevelCount is equal to 2 and RATA2Required is equal to "Y" OR

b)	MaxLevelCount is equal to 2 and RATA3Required is equal to "Y" OR

c)	MaxLevelCount is equal to 3 and RATA3Required is equal to "Y"

AND the QACertEventDate is either:

a)	prior to the Current 11ourly Recordf or R 1T. {Status.\)atc I lour OR

b)	equal to both the Current Hour ly Recordf or R. 1 TAStatus.\ )atc I lour and the ConditionalBeginDate/Hour;
AND either:

Environmental Protection Agency

Page 652 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

a)	QACertEventDate/Hour is after the PriorMaxLevelRATARecord.EndDatefHour OR

b)	QACertEventDate/Hour is equal to the PriorMaxLevelRATARecord.EndDate/ELour AND (TestCompletionDate
is null or the TestCompletionDate/Hour is after the PriorMaxLevelRATARecord.EndDate/Hour)

if (QACertificalionEventRecords is found)

Set SubsequentRATARecord = PriorMaxLevelRATARecord.

Set CurrentRalaStatus = "OOC-Incomplete Recertification".

Set OverrideRataBaf= 1.0.

else if (PriorMaxLevelR4TARecord.QANeedsEva\uationF\ag = "Y")

Set CurrentRATAStatus = "Prior Maximum Level RATA Not Yet Evaluated".

else if (PriorMaxLevelRATARecord.TestKesuitCode = null)

Set CurrentRATAStatus = "OOC-Prior Maximum Level RATA Has Critical Errors".
Set OverrideRataBaf= Prior R. 1T. 1 Record.OxcrM I ii asAdj ustmcntFactor.

else if (PriorMaxLevelRATARecord.TestResultCode = "FAILED")

Set CurrentRATAStatus = "OOC-Prior Maximum Level RATA Failed".
Set OverrideRataBaf= Prior R. 1T. 1 Record.OxcrM I ii asAdj ustmentFactor.

else if (PriorMaxLevelRATARecord.TestResultCode = "ABORTED")

Set CurrentRATAStatus = "OOC-Prior Maximum Level RATA Aborted".
Set OverrideRataBaf= PriorR 1T. 1 Record.OxcrM I ii asAdj ustmcntF actor.

else

if PriorMaxLevelRATARecord.TestRe&sonCode = "INITIAL",

Locate the latest record in QACertificalionEventRecords where

1)	SystemID is equal to the CurrentHourlyRecordforRATAStatus.SystemID

2)	QaCertEventCode is equal to "305"

3)	QACertEventDate/Hour is prior to the Current flour ly Recordfor R1 TAStatus.\ )ate I lour:

if (QACertificalionEventRecords is found, and the TestCompletionDate in the located record is
after PriorMaxLevelRA TA Record. I jidF)ate)

Set PriorMaxLevelRATARecord.TestExpimtionDate = the end of the quarter twenty
quarters after the TestCompletionDate .

else

Set PriorMaxLevelRATARecord.TestExpimtionDate = the end of the quarter twenty
quarters after the PriorMaxLevelR 1T. 1 Record. Fnd I )ate.

Set PriorMaxLevelRATARecord.TestExpimtionDate = the end of the quarter twenty quarters
after the PriorMaxLevelR. 1T. 1 Record. Fnd I )ate.

if (Current 11ourly Recordfor R1T. [Status.] )ate is after the
PriorMaxLevelRA TARecord. TestExpirationDate)

if (Annual Reporting Requirement == false)

Set CurrentRATAStatus = "OOC-Prior Maximum Level RATA Expired".
Set OverrideRataBaf= /V/eWt 17/l/fecY«Y/.Ovcral 11 iiasAdj ustmcntF actor.

Environmental Protection Agency

Page 653 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else

Set GraceOpHours = RptPeriodOpHoursAccumulatorArray for the location.

If (GraceOpHours < 0)

Set CurrentRATAStatus = "Invalid Op Data".

else if (GraceOpHours > 720)

Set CurrentRATAStatus = "OOC-Prior Maximum Level RATA Expired".
Set OverrideRataBaf= Prior R. 1T. 1 Record.OxcrM I ii asAdj ustmcntl actor.

For each quarter beginning with the quarter after the

PriorMaxLevelRATARecord.TestExpimtionDate and continuing through the
quarter prior to the Current /four ly Record for R. 1 TAStatus.\ )atc I lour,

if (EarliestLocationReportDate <= the last day of the quarter being
checked)

Locate a record in OperatingSuppDataRecordsByLocation
where the reporting period is equal to the year/quarter being
checked and the OpTypeCode = "OPHOURS" and FuelCode is
null.

if (OperatingSuppDataRecordsByLocation is found)

Add Op Value to GraceOpHours.

if (GraceOpHours > 720)

Set CurrentRATAStatus = "OOC-Prior
Maximum Level RATA Expired".
Set OverrideRataBaf=

/V70rii47L4i?ec0ra?.OverallBiasAdjustmentFact
or.

exit for.

else

Locate the record in ReportingFrequency By Location
where CalendarYear/Quarter are equal to the quarter
being checked.

if found, and (the quarter being checked is 2 or 3, or
ReportingFrequency By Location.ReportingFrequencyC
ode is equal to "Q"),

Results:

Result

Response

Set CurrentRATAStatus = "Missing Op Data".
Set RATAMissingOpDatalnfo = "[YEAR]
Q[QTR]" (where [YEAR] is the year of the
quarter being checked and [QTR] is the number
of the quarter being checked.)
exit for.

Severity

Environmental Protection Agency

Page 654 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02/02 RATA Status Evaluation

2	Process/Category:	Emissions Data Evaluation Report	H20 RATA Status Evaluation

3	Process/Category:	Emissions Data Evaluation Report	H20M RATA Status Evaluation

4	Process/Category:	Emissions Data Evaluation Report	NOX RATA Status Evaluation

5	Process/Category:	Emissions Data Evaluation Report	NOXC RATA Status Evaluation

6	Process/Category:	Emissions Data Evaluation Report	S02 RATA Status Evaluation

7	Process/Category:	Emissions Data Evaluation Report	Stack Flow RATA Status Evaluation

Environmental Protection Agency

Page 655 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	RATSTAT-7

Check Name:	Determine Expiration Dates for Most Recent Prior RATA Test

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

if (CurrentRATAStatus is null and PriorRATARecordis not null and PriorRATAEventRecordis null)

Set PriorTestExpirationDate = null

Set PriorTestExpirationDateWithExtension = null

Set MissingOpData = false

Set NumberOfExtensionQuarters = 0

Set PriorTestExpirationDate = Priori?^ Mifecortf.TestExpirationDate.

Set PriorTestExpirationDateWithExtension = _fV70rii47L4i?ec0rtf.TestExpirationDateWithExtension.

if (PriorTestExpirationDate is null)

if (Annual Reporting Requirement == false)

if (PriorRATARecord.EndD&te is between 10/01/2007 and 12/31/2007)

Set PriorTestExpirationDate = 09/30/2008

else

Set PriorTestExpirationDate = September 30th of the year of the PriorRATARecord.EndDate.

else if (CurrentHourlyRecordforRATAStatus.SystemDesignationCode == "B")

Locate a record in TestExtensionExemptionRecords where the SystemID is equal to the
CurrentHourlyRecordforRATAStatus.SystemlD and the ExtensionExemptionCode is equal to "NRB720" and a
ReportingPeriod equal to the CurrentReportingPeriod.

if (TestExtensionExemptionRecords is found)

Locate the most recent QACertificalionEventRecords for the

CurrentHourlyRecordforRATAStatus.SystemID where RATARequired is equal to " Y" and the
QACertEventDate/Hour is prior to the PriorRATARecord.BeginDate/Hour.

if (QACertificationEventRecords is found AND RATACertEvent == "Y" and the
ConditionalDataBeginDate is null and the CompletionTestDate/Hour is after the
PriorRA Mitecortf.EndDate/Hour)

Set PriorTestExpirationDate = the end of the quarter eight quarters after the
QACertificalionEventRecords . Compl etionTestDate.

else

Set PriorTestExpirationDate = the end of the quarter eight quarters after the
Prior RA TARecord. EndDate.

if (PriorTestExpirationDate is null)

if (PriorRatalsAlternateSingleLevelRATA == true)

Set PriorTestExpirationDate = the end of the quarter one year after the
PriorMultiLevelRA TARecord. EndDate.

iff PriorMultiLevelR. 1T. 1 Record. (iracc I 'cri od I nd == 1)

Environmental Protection Agency

Page 656 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set PriorTestExpirationDate = the end of the quarter prior to the PriorTestExpirationDate.

if Cftwii47L4itec0ra?.RataFrequencyCd in set {4QTRS,8QTRS})

Locate the most recent QACertificalionEventRecords for the PriorRATARecord.SystemlD where
RATARequired is equal to "Y" and the BeginDate/Hour is prior to the
PriorRA 714ifecorrf.BeginDate/Hour.

if (QACertificalionEventRecords is found and RATACertEvent == "Y" and the
ConditionalDataBeginDate is null and the CompletionTestDate/Hour is after the
PriorRA Z4ifecorrf.EndDate/Hour)

else

Set PriorTestExpirationDate = the end of the quarter one year after the
QACertificationEventRecords . Compl etionTestDate.

Set PriorTestExpirationDate = the end of the quarter one year after the
PriorRA TARecord. EndDate.

if (Prior R 1T. 1 Record. (i race I 'c ri od I n d ==1)

Set PriorTestExpirationDate = the end of the quarter prior to the
PriorTestExpirationDate.

else

Locate the most recent QACertificationEventRecords for the PriorRATARecord.SystemlD where
RATARequired is equal to "Y" and the BeginDate/Hour is prior to the
PriorRA 714ifecorrf.BeginDate/Hour.

if (QACertificationEventRecords is found AND RATACertEvent == "Y" and the
ConditionalDataBeginDate is null and the CompletionTestDate/Hour is after the
PriorRA Z4ifecorrf.EndDate/Hour)

Set PriorTestExpirationDate = the end of the quarter two quarters after the
QA CertificationEventRecords CompletionTe stDate.

else

Set PriorTestExpirationDate = the end of the quarter two quarters after the
PriorRA TARecord. EndDate.

Set Prior R. 1T. 1 /feccwY/.TestI api rati on I )ate = PriorTestExpirationDate.

if (CurrentffourlyRecordforR. 1T. {Status.\)atc I lour is ON OR BEFORE the PriorTestExpirationDate)

Set CurrentRATAStatus = "IC".

else if {Annual Reporting Requirement == false)

Set CurrentRATAStatus = "OOC-Expired".

if (Current ffourly Recordf or R. 1T. l.SYata.v. Parameter == "FLOW")

Set OverrideRATABAF = Pr/orit4ry4ifecorrf.OverallBiasAdjustmentFactor.

else

Environmental Protection Agency

Page 657 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

if (PriorTestExpirationDateWithExtension is null)

if (CurrentHourlyRecordforRATAStatus.Parameter == "FLOW" and PriorRatalsAlternaleSingleLevelRATA ==

true)

iff PriorM ultiLevelR. 1T. 1 Record. (iracc I 'cri od I nd == 1)

StartQuarter = the quarter of the PriorM ultiLevelR. 1T. 1 Record. I Indl )atc

else

StartQuarter = the quarter after the PriorM ultiLevelR. 1T. 1 Record. I Indl )atc
set EndQuarter = the quarter two years after the quarter of the PriorM ultiLevelR. 1T. 1 Record. I jidDatc.

else

if (I'riorR I'/'.-1 /feewrf. G ra c e Pe r i o d I nd ==1)

StartQuarter = the quarter of the PriorR 1T. 1 Record. I jkI I )atc

else

StartQuarter = the quarter after the PriorR 1T. 1 Record. Hnd I )atc

set EndQuarter = the quarter two years after the quarter of the PriorRATARecord.EndDate.

For each quarter beginning with the StartQuarter and continuing through the earlier of the quarter prior to the
quarter of the CurrentHourlyRecordforRATAStatus.Date/Hour and EndQuarter

if (EarliestLocationReportDale > the last day of the quarter being checked)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

else

Locate a record in OperatingSuppDataRecordsByLocation where the reporting period is equal to
the year/quarter being checked and the OpTypeCode = "OPHOURS".

if (OperatingSuppDataRecordsByLocation is found AND
OperatingSuppDataRecordsByLocation.OpValue < 168)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

else i I (Current Ilourly Recordfor R. 17'l»SYata.v. S vstcmTvpcCodc begins with "S02")

Locate a record in TestExtensionExemptionRecords where the SystemID is equal to the
CurrentHourlyRecordforRATAStatus.SystemID and the ExtensionExemptionCode is
equal to "LOWSQTR" and the reporting period is equal to the year/quarter being checked.

if (TestExtensionExemptionRecords is found)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

else if (OperatingSuppDataRecordsByLocation is not found)

Locate the record in ReportingFrequencyByLocation where
CalendarYear/Quarter are equal to the year/quarter being checked .

if found, and (the quarter being checked is 2 or 3, or

ReportingFrequency By Location. ReportingFrequencyCode is equal to "Q"),
Set Missing Op Data to true.

Set RATAMissingOpDatalnfo = "[YEAR] Q[QTR]" (where [YEAR] is

Environmental Protection Agency

Page 658 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

the year of the quarter being checked and [QTR] is the number of the
quarter being checked.)

else i I (Current ffourlyRecordforR. 17'l.SYafM.v. S vstcm I )csignati onCodc == "PB")

Locate a record in TestExtensionExemptionRecords where the SystemID is equal to the
CurrentHourlyRecordforRATAStatus.SystemlD and the ExtensionExemptionCode is
equal to "NONQAPB" and the reporting period is equal to the year/quarter being checked.

if (TestExtensionExemptionRecords is found)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

else if (OperatingSuppDalaRecordsByLocalion is not found)

Locate the record in ReportingFrequency By Location where
CalendarYear/Quarter are equal to the year/quarter being checked .

if found, and (the quarter being checked is 2 or 3, or

ReportingFrequency By Location. ReportingFrequencyCode is equal to "Q"),
Set Missing Op Data to true.

Set RATAMissingOpDatalnfo = "[YEAR] Q[QTR]" (where [YEAR] is
the year of the quarter being checked and [QTR] is the number of the
quarter being checked.)

else if (OperatingSuppDataRecordsByLocation is not found)

Locate the record in ReportingFrequency By Location where CalendarYear/Quarter are
equal to the year/quarter being checked .

if found, and (the quarter being checked is 2 or 3, or

ReportingFrequencyByLocation.ReportingFrequencyCode is equal to "Q"),

Set Missing Op Data to true.

Set RATAMissingOpDatalnfo = "[YEAR] Q[QTR]" (where [YEAR] is the year
of the quarter being checked and [QTR] is the number of the quarter being
checked.)

For each quarter beginning with the quarter after the End Quarter and continuing through the quarter prior to the
quarter of the CurrentffourlyRecordforRATAStatus.\)dlc I lour

if (CurrentHourlyRecordforRATAStatus.SystemDesignationCode == "PB")

Locate a record in TestExtensionExemptionRecords where the SystemID is equal to the
CurrentHourlyRecordforRATAStatus.SystemlD and the ExtensionExemptionCode is equal to
"NONQAPB" and the reporting period is equal to the year/quarter being checked.

if (TestExtensionExemptionRecords is found)

Set NumberOfExtensionQuarters = NumberOfExtensionQuarters + 1.

Set PriorTestExpirationDateWithExtension = PriorTestExpirationDate.

Add NumberOfExtensionQuarters to PriorTestExpirationDate WithExtension.

Set Priori^7L4i?ec0ra?.TestExpirationDateWithExtension = PriorTestExpirationDateWithExtension.

Environmental Protection Agency

Page 659 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Set _ft70rii47L4i?ec0ra?.TestExpirationDateWithExtension = PriorTestExpirationDate

If (Cur rent 11iiurly Recordfor R 1T. [Status.] )ate I Iolii is ON OR BEFORE the PriorTestExpirationDateWithExtension)

Set CurrentRATAStalus = "IC-Extension".

else if (Missing Op Data is true)

Set CurrentRATAStalus = "Missing Op Data".

Set Priori^7L4i?ec0ra?.TestExpirationDateWithExtension = null

else if (RptPeriodOpTimeAccumulatorArray == -1)

Set CurrentRATAStalus = "Invalid Op Data".

else

Set GraceOpHours = RptPeriodOpHoursAccumulatorArray for the location.

if (GraceOpHours > 720)

Set CurrentRATAStatus = "OOC-Expired".

if (Current ff ourly Recordfor R 1T. l.SYata.v. Parameter == "FLOW")

Set OverrideRATABAF = Prior R 1T. 1 Record.OxcrM IiiasAdj ustmcntl actor.

else

If there are no quarters beginning with the LATER of the quarter after the

PriorTestExpirationDateWithExtension and the quarter of the EarliestLocationReportDate and ending
with the quarter prior to the Current ffourly Recor dfor R1T. 1 Status .Date Hour,

Set CurrentRATAStatus = "IC-Grace".

else

For each quarter beginning with the quarter after the PriorTestExpirationDateWithExtension and
continuing through the quarter prior to the Current 11 ourly Recordfor R1 TAStatus.\ )atc I Iolii ,

if (EarliestLocationReportDate <= the last day of the quarter being checked)

Locate a record in OperalingSuppDataRecordsByLocalion where the reporting
period is equal to the year/quarter being checked and the OpTypeCode =
"OPHOURS" and FuelCode is null.

if (OperatingSuppDataRecordsByLocation is found)

Add OpValue to GraceOpHours.

if (GraceOpHours > 720)

Set CurrentRATAStatus = "OOC-Expired".

if (Current ff ourly Recordfor R1T. l.SYata.v. Parameter ==

"FLOW")

Set OverrideRATABAF =

PW0rii47L4itec0ra?.OverallBiasAdjustmentFactor.

Environmental Protection Agency

Page 660 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

exit for.

else

Locate the record in ReportingFrequencyByLocation where
CalendarYear/Quarter are equal to the year/quarter being checked .

if found, and (the quarter being checked is 2 or 3, or
ReportingFrequencyByLocation.ReportingFrequencyCode is equal to
"Q"),

Set CurrentRATAStalus = "Missing Op Data".
Set RATAMissingOpDatalnfo = "[YEAR] Q[QTR]" (where
[YEAR] is the year of the quarter being checked and [QTR] is
the number of the quarter being checked.)
exit for.

if (CurrentRATAStatus is null)

Set CurrentRATAStatus = "IC-Grace".

If (PriorRatalsAlternateSingleLevelRATA == true AND CurrentRATAStatus = "OOC-Expired")
Set CurrentRATAStatus = "OOC-Incomplete QA RATA".

Results:

Result

Usage:

1

2

3

4

5

6

7

if (CurrentffourlyRecordforR. 1T. l.SYata.v. Parameter == "FLOW")

Set OverrideRATABAF = Pr/ori^JMifecortf.OverallBiasAdjustmentFactor.

Response

Process/Category:	Emissions Data Evaluation Report	C02/02 RATA Status Evaluation

Process/Category:	Emissions Data Evaluation Report	LOO RATA Status Evaluation

Process/Category:	Emissions Data Evaluation Report	LOOM RATA Status Evaluation

Process/Category:	Emissions Data Evaluation Report	NOX RATA Status Evaluation

Process/Category:	Emissions Data Evaluation Report	NOXC RATA Status Evaluation

Process/Category:	Emissions Data Evaluation Report	S02 RATA Status Evaluation

Process/Category:	Emissions Data Evaluation Report	Stack Flow RATA Status Evaluation

Severity

Environmental Protection Agency

Page 661 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Check Code:	RATSTAT-8

Check Name:	Determine Final RATA Status

Related Former Checks:

Applicability:	CEM Check

Description:

Specifications:

Set AlternateRATARecord = null.

if (CurrentRATAStatus begins with "OOC")

Set InvalidRATATestNumber = null.

if (InvalidMultiLevelRATARecordis not null)

Set Invalid RATA Test Number = InvalidMultiLevelR. 1T. 1 Record ! cslNLimber
Set CurrentRATAStatus = CurrentRATAStatus &

if (Current 11ourly Recordf or R 1T. l.SYata.v. Parameter == "FLOW")

Set RA TA Status BAF = InvalidMultiLevelRATARecord.Overa\\BiasAd)ustment¥actor.

else if (InvalidRATARecord is not null)

Set InvalidRATATestNumber = InvalidR1T. 1 Record.'l cslhlLimber
Set CurrentRATAStatus = CurrentRATAStatus &

if (Current 11 ourly Recordf or R 1T. l.SYata.v. Parameter == "FLOW")

Set RA TA Status B 11 InvalidR. 1T. 1 Record.( )\ci d\ 11 iiasAdj Listmcntl actor.

else if (OverrideRATABAFis not null)

if (Current flourly Recordf or R. 1T. l.SYata.v. Parameter == "FLOW")

Set RA TA Status BAF= OverrideRATABAF

else if (CurrentRATAStatus begins with "IC" or "Undetermined"

If (CurrentHourlyRecordforRATAStatus.SystemTypeCd == "NOX")

Set ComponentlDList = null.

Set AlternateSystemlDList = null.

For each record in MonitorSystemComponentRecordsforHourandLocation where the SystemID is equal to the
CurrentHourlyRecordforRATAStatus.SystemID and ComponentTypeCd in list {"C02", "NOX", "02"}

Add MonitorSystemGomponentRecordsforflourandLocation.ComponcnlW) to ComponentlDList.

if (ComponentlDList is not null)

For each record in MonitorSystemComponentRecordsforHourandLocation where the ComponentID is in
ComponentlDList and SysTypeCd in list {"C02", "02", "NOXC"}.

Add MonitorSystemComponentRecordsforllourandLocation. System 11) to AlternateSystemlDList.

if (AlternateSystemlDList is not null)

If (PriorRATAEventRecordis not null)

If (PriorR4TAEventRecord.Conditiona\BeginDate is not null)

Environmental Protection Agency

Page 662 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Locate the most recent record in RATATestRecordsByLocalionForQAStatus for the location
where the SystemID is in AlternateSystemlDList and the EndDate/Hour is prior to the
Current Hourly RecordforRATAStatu.s.\ydlc I lour and the EndDate/Hour is after the
Pr/orit4714£Ven?ifecorrf.ConditionalBeginDate/Hour and theTestResultCode is null or is equal to
"FAILED" or "ABORTED".

if {RATATestRecordsByLocalionForQAStatus is found)

Set AlternaleRATARecord = the found record in
RA TA TestRecordsByLocationForQAStatus.

if (Alternate R. 1T. 1 /feewrf.TestResul tCodc = null)

Set CurrentRATAStatus = "OOC-Prior Alternate System RATA Has Critical
Errors".

else if (AlternaleRATARecord.TestResultCode = "FAILED")

Set CurrentRATAStatus = "OOC-Prior Alternate System RATA Failed",
else if (AlternaleRATARecord.TestResultCode = "ABORTED")

Set CurrentRATAStatus = "OOC-Prior Alternate System RATA Aborted".

else

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the
location where the SystemID is in AlternateSystemlDList and the EndDate/Hour is prior to
the Current Ilaurly RecardfarRAIAStatusXydic I lour and the EndDate/Hour is after the
Pr/orit4714£Ven?ifecorrf.ConditionalBeginDate/Hour and the QANeedsEvaluationFlag is
equal to "Y".

if {RATATestRecordsByLocationForQAStatus is found)

Set AlternaleRATARecord = the found record in
RA TA TestRecordsByLocationForQAStatus.

Set CurrentRATAStatus = "Prior Alternate System RATA Not Yet Evaluated".

else if (PriorRATARecordis not null)

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the
SystemID is in AlternateSystemlDList and the EndDate/Hour is prior to the
CurrentffourlyRecordforR. 1 TAStatus.\ )atc I lour and the EndDate/Hour is after the
PriorRATARecord.EndDatefHour and the TestResultCode is null or is equal to "FAILED" or
"ABORTED".

if {RATATestRecordsByLocationForQAStatus is found)

Set AlternaleRATARecord = the found record in RATATestRecordsByLocationForQAStalus.
if (Alternate R. 1T. 1 /fecYWY/.TcstRcsul tCodc = null)

Set CurrentRATAStatus = "OOC-Prior Alternate System RATA Has Critical Errors",
else if (AlternaleRATARecord.TestResu\tCode = "FAILED")

Set CurrentRATAStatus = "OOC-Prior Alternate System RATA Failed".

Environmental Protection Agency

Page 663 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

else if (AlternateRATARecord.TestResuitCode = "ABORTED")

Set CurrentRATAStatus = "OOC-Prior Alternate System RATA Aborted".

else

Locate the most recent record in RATATestRecordsByLocalionForQAStatus for the location
where the SystemID is in AlternateSystemlDList and the EndDate/Hour is prior to the
Current Hourly RecordforRATAStatus.\ydlc I lour and the EndDate/Hour is after the
PriorRATARecord.EndDate/YLour and the QANeedsEvaluationFlag is equal to "Y".

if (RATATestRecordsByLocationForQAStatus is found)

Set AlternaleRATARecord = the found record in
RA TA TestRecordsByLocationForQAStatus.

Set CurrentRATAStatus = "Prior Alternate System RATA Not Yet Evaluated".
If {Current RATA Status begins with "IC" or "Undetermined")

If (PriorRATARecordis null)

Set RA TA Status BAF = 1

else if (Current RATA Status begins with "IC-Cond", "Undetermined-Cond" or "PendingOOC-Cond" AND

(PriorRATAEventRecord.QACertEventCode is in set {40, 50, 51, 100, 101, 120, 125, 151, 250,255,
300, 305}) OR PriorRATARecord.TestResultCode does NOT begin with "PASS"))

Set RA TA Status BAF = 1

else if (CurrentHourlyRecordforRATAStatus.SystemID is NOT equal to PriorRATARecord.SystemID)

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the SystemID
is equal to the CurrentHourlyRecordforRATAStatus.SystemID, the TestResultCode is NOT equal to "INVALID"
and the EndDate/Hour is prior to the Current Hourly RecordforR. 1T. 1 Status .Date Hour

If found,

Set RATA Status BAF to the OverallBiasAdjustmentFactor in the RATA record found above.

else

Set CurrentRATAStatus to "OOC-No Prior Test or Event".

Locate the most recent record in RATATestRecordsByLocationForQAStatus for the location where the
SystemID is equal to the CurrentHourlyRecordforRATAStatus.SystemID, the TestResultCode is equal to
"INVALID" and the EndDate/Hour is prior to the CurrentffourlyRecordforR. 1T. {Status.\)atc I lour.

If found,

Set InvalidRATATestNumber to the TestNumber in the RATA record found above.
Set CurrentRATAStatus = CurrentRATAStatus &

Set RATA Status B 11 Prior R. 1T. 1 Record.OxcrMIiiasAdj ustmcntFactor

If (CurrentRATAStatus does not begin with "IC")

Return result CurrentRATAStatus .

Environmental Protection Agency

Page 664 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

Results:

Result

Invalid Monitor
System

Invalid Op Data
Missing Op Data

Missing Program

OOC-Conditional
Period Expired
OOC-Conditional
Period Expired*
OOC-Event

OOC-Event*

OOC-Expired
OOC-Expired*

OOC-Incomplete
QA RATA

OOC-Incomplete
QA RATA*

OOC-Incomplete
Recertification
OOC-Incomplete
Recertification*

OOC-No Prior
Maximum Level
RATA

OOC-No Prior
Maximum Level
RATA*

OOC-No Prior
Test or Event
OOC-No Prior
Test or Event*
OOC-Prior
Alternate System
RATA Aborted
OOC-Prior
Alternate System
RATA Failed

Response

The [testtype] status for [key] could not be determined, because the Monitor System
record for MonitoringSystemID [system] has a critical error.

The [testtype] status for [key] could not be determined, because the OperatingTime in at
least one Hourly Operating Data records was missing or invalid.

The [testtype] status for [key] could not be determined, because the Op Supp Data
record for OPHOURS, OSHOURS, or OPDAYS is missing for

[MISSINGOPDATAINFO] (and possibly other previous reporting periods). If you have
submitted emissions data for prior quarters, you should be able to retrieve these records
by logging on to the EPA host.

The [testtype] status for [key] could not be determined, because a Unit Program record
associated with the initial certification event for QACertEventCode [code]
QACertEventDate [eventdate] either does not exist or has a

UnitMonitorCertificationBeginDate inconsistent with the BeginDate of the associated
Monitor System record.

The conditional data period for QACertEventCode [code] QACertEventDate [eventdate]
for SystemID [EVENTKEY] has expired.

The conditional data period for QACertEventCode [code] QACertEventDate [eventdate]
for SystemID [EVENTKEY] has expired. An invalid RATA was ignored.

You reported a QA Certification Event record for QACertEventCode [code]
QACertEventDate [eventdate] for SystemID [eventkey], but you did not indicate the use
of conditional data.

You reported a QA Certification Event record for QACertEventCode [code]
QACertEventDate [eventdate] for SystemID [eventkey], but you did not indicate the use
of conditional data. An invalid [testtype] was ignored.

The prior RATA for SystemID [RATASYS] with TestNumber [testnum] has expired.
The prior RATA for [RATASYS] with TestNumber [testnum] has expired. An invalid
prior [testtype] with TestNumber [invtestnum] was ignored.

The prior RATA for FLOW SystemID [RATASYS] with TestNumber [testnum] was a
single-level RATA instead of the required multi-level RATA. If applicable, please
review the prior single-level RATA to determine if it contained a single load flow claim
qualification record under Part 75, Appendix B, Section 2.3.1.3(c)(3)).

The prior RATA for FLOW SystemID [RATASYS] with TestNumber [testnum] was a
single-level RATA instead of the required multi-level RATA. An invalid prior test with
TestNumber [invtestnum] was ignored.

The subsequent recertification RATA for FLOW SystemID [SUBSYS] with
TestNumber [subtestnum] was performed at fewer than the required operating levels.
The subsequent recertification RATA for FLOW SystemID [SUBSYS] with
TestNumber [subtestnum] was performed at fewer than the required operating levels.
An invalid prior test with TestNumber [invtestnum] was ignored.

You did not report a valid prior [max]-level flow RATA for [key].

You did not report a valid prior [max]-level flow RATA for [key]. An invalid RATA
with TestNumber [invtestnum] was ignored.

You did not report a prior [testtype] or certification event for [key].

You did not report a valid prior [testtype] or certification event for [key]. An invalid
[testtype] with TestNumber [invtestnum] was ignored.

A prior RATA with TestNumber [alttestnum] for MonitoringSystemID [altsys] was
aborted, so [key], which contains a component that is also in the former system, is
out-of-control.

A prior RATA with TestNumber [alttestnum] for MonitoringSystemID [altsys] failed, so
[key], which contains a component that is also in the former system, is out-of-control.

Severity

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

Critical Error Level 1

Environmental Protection Agency

Page 665 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

OOC-Prior
Alternate System
RATA Has
Critical Errors
OOC-Prior
Maximum Level
RATA Aborted
OOC-Prior
Maximum Level
RATA Aborted*
OOC-Prior
Maximum Level
RATA Expired
OOC-Prior
Maximum Level
RATA Expired*
OOC-Prior
Maximum Level
RATA Failed
OOC-Prior
Maximum Level
RATA Failed*
OOC-Prior
Maximum Level
RATA Has
Critical Errors
OOC-Prior
Maximum Level
RATA Has
Critical Errors*
OOC-Prior Test
Aborted
OOC-Prior Test
Aborted*
OOC-Prior Test
Failed

OOC-Prior Test
Failed*

OOC-Prior Test
Has Critical
Errors

OOC-Prior Test
Has Critical
Errors*

OOC-Recertificat
ion Test Aborted
OOC-Recertificat
ion Test
Aborted*
OOC-Recertificat
ion Test Failed
OOC-Recertificat
ion Test Failed*
OOC-Recertificat
ion Test Has
Critical Errors
OOC-Recertificat
ion Test Has
Critical Errors*

A prior RATA with TestNumber [alttestnum] for MonitoringSystemID [altsys] has	Critical Error Level 1

critical errors, so [key], which contains a component that is also in the former system, is

out-of-control.

The prior [max]-level flow RATA for [key] with TestNumber [maxtestnum] was	Critical Error Level 1

aborted.

The prior [max]-level flow RATA for [key] with TestNumber [maxtestnum] was	Critical Error Level 1

aborted. An invalid RATA with TestNumber [invtestnum] was ignored.

The prior [max]-level flow RATA for [key] with TestNumber [maxtestnum] has expired.	Critical Error Level 1

The prior [max]-level flow RATA for [key] with TestNumber [maxtestnum] has expired.	Critical Error Level 1

An invalid RATA with TestNumber [invtestnum] was ignored.

The prior [max]-level flow RATA for [key] with TestNumber [maxtestnum] failed.	Critical Error Level 1

The prior [max]-level flow RATA for [key] with TestNumber [maxtestnum] failed. An	Critical Error Level 1

invalid RATA with TestNumber [invtestnum] was ignored.

The prior [max]-level flow RATA for [key] with TestNumber [maxtestnum] has critical	Critical Error Level 1

errors.

The prior [max]-level flow RATA for [key] with TestNumber [maxtestnum] has critical	Critical Error Level 1

errors. An invalid RATA with TestNumber [invtestnum] was ignored.

The prior RATA for SystemID [RATASYS] with TestNumber [testnum] was aborted.	Critical Error Level 1

The prior RATA for SystemID [RATASYS] with TestNumber [testnum] was aborted.	Critical Error Level 1

An invalid prior [testtype] with TestNumber [invtestnum] was ignored.

The prior RATA for SystemID [RATASYS] with TestNumber [testnum] failed.	Critical Error Level 1

The prior RATA for SystemID [RATASYS] with TestNumber [testnum] failed. An	Critical Error Level 1

invalid prior [testtype] with TestNumber [invtestnum] was ignored.

The prior RATA for SystemID [RATASYS] with TestNumber [testnum] has critical	Critical Error Level 1

errors.

The prior RATA for SystemID [RATASYS] with TestNumber [testnum] has critical	Critical Error Level 1

errors. An invalid prior [testtype] with TestNumber [invtestnum] was ignored.

The subsequent recertification RATA for SystemID [subsys] with TestNumber
[subtestnum] was aborted.

The subsequent recertification RATA for SystemID [subsys] with TestNumber
[subtestnum] was aborted. An invalid [testtype] with TestNumber [invtestnum] was
ignored.

The subsequent recertification RATA for SystemID [subsys] with TestNumber
[subtestnum] failed.

The subsequent recertification RATA for SystemID [subsys] with TestNumber
[subtestnum] failed. An invalid [testtype] with TestNumber [invtestnum] was ignored.
The subsequent recertification RATA for SystemID [subsys] with TestNumber
[subtestnum] has critical errors.

Critical Error Level 1
Critical Error Level 1

Critical Error Level 1
Critical Error Level 1
Critical Error Level 1

The subsequent recertification RATA for SystemID [subsys] with TestNumber	Critical Error Level 1

[subtestnum] has critical errors. An invalid [testtype] with TestNumber [invtestnum]
was ignored.

Environmental Protection Agency

Page 666 of 667


-------
Draft ECMPS Emissions Check Specifications

9/17/2014 12:00:00AM

The RATA status for [key] could not be determined, because a prior RATA with
TestNumber [alttestnum] for MonitoringSystemID [altsys], which contains a component
that is also in the former system, has not yet been evaluated.

Prior Alternate
System RATA
Not Yet
Evaluated

Prior Maximum The RATA status for [key] could not be determined, because the prior [max]-level flow
Level RATA Not RATA with TestNumber [maxtestnum] has not yet been evaluated.

Yet Evaluated

The RATA status could not be determined, because the prior multi-level flow RATA for
SystemID [RATASYS] with TestNumber [multitestnum] has not yet been evaluated.

Prior Multi-Level
RATA Not Yet
Evaluated
Prior Test Not
Yet Evaluated
Recertification
Test Not Yet
Evaluated

The RATA status could not be determined, because the applicable prior RATA for
SystemID [RATASYS] with TestNumber [testnum] has not yet been evaluated.

The RATA status could not be determined, because the subsequent recertification
RATA for SystemID [subsys] with TestNumber [subtestnum] has not yet been
evaluated.

Undetermined-Co The software could not determine if the current hour was within the conditional data
nditional Data period for QACertEventCode [code] QACertEventDate [eventdate] for SystemID
[eventkey].

Usage:

1	Process/Category:	Emissions Data Evaluation Report	C02/02 RATA Status Evaluation

2	Process/Category:	Emissions Data Evaluation Report	LOO RATA Status Evaluation

3	Process/Category:	Emissions Data Evaluation Report	LOOM RATA Status Evaluation

4	Process/Category:	Emissions Data Evaluation Report	NOX RATA Status Evaluation

5	Process/Category:	Emissions Data Evaluation Report	NOXC RATA Status Evaluation

6	Process/Category:	Emissions Data Evaluation Report	S02 RATA Status Evaluation

7	Process/Category:	Emissions Data Evaluation Report	Stack Plow RATA Status Evaluation

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1

Critical Error Level 1
Critical Error Level 1

Informational Message

Environmental Protection Agency

Page 667 of 667


-------