EPA

Water Sense

Response to Public Comments Received on
February 2013 WaterSense®Draft Specification
for Commercial Pre-Rinse Spray Valves

September 19, 2013


-------
WaterSense

Response to Public Comments Received on February 2013
WaterSense® Draft Specification for Commercial Pre-Rinse Spray Valves

Background

This document provides WaterSense's responses to public comments received on the
WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves. For purposes
of this document, the comments are summarized. The verbatim comments can be
viewed in their entirety at www.epa.qov/watersense/partners/prsv backqround.html.

2

September 19, 2013


-------
WaterSense

Response to Public Comments Received on February 2013
WaterSense® Draft Specification for Commercial Pre-Rinse Spray Valves

Table of Contents

I.	Comments on Section 1.0: Scope and Objective	4

II.	Comments on Section 2.0: General Requirements	4

III.	Comments on Section 3.0: Water Efficiency Requirements	4

IV.	Comments on Section 4.0: Performance Requirements	5

V.	Comments on Section 5.0: Marking	8

VI.	Comments on Appendix A: Draft ASTM F2324 Standard Test Method for
Prerinse Spray Valves	9

VII.	General Comments on the Specification	9

VIII.	Comments on the Specification Supporting Documentation	11

3

September 19, 2013


-------
4

epa	Response to Public Comments Received on February 2013

WaterSense WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves

I.	Comments on Section 1.0: Scope and Objective

WaterSense received no comments on the specification's Scope and Objective section.

II.	Comments on Section 2.0: General Requirements

Flow Rate Test Method

a. One commenter noted that Section 2.1 of the specification omits the flow rate
test exception. The commenter recommended changing the language in Section
2.1 of the specification as follows:

"The pre-rinse spray valve shall conform to applicable requirements in ASME
A112.18.1/CSA B125.1 Plumbing Supply Fittings, with the exception of the life
cycle test requirements described in Section 4.2 below and the flow rate test in
3.0 below."

Response: WaterSense agrees with this comment and has updated the
specification to reflect this change (see Section 2.1).

During the specification development process, WaterSense collaborated with the
American Society of Mechanical Engineers (ASME)/Canadian Standards
Association (CSA) Joint Harmonization Task Force Project Team FT-07-11
(hereafter referred to as "project team"). The project team conducted round-robin
testing and found that the catch-and-weigh method for measuring a pre-rinse
spray valve's (PRSV's) flow rate was more accurate than measuring the flow rate
using a flow meter. ASME A112.18.1/CSA B125.1 Plumbing Supply Fittings
allows flow rate testing using water meters or the catch-and-weigh method,
whereas ASTM F2324 Standard Test Method forPrerinse Spray Valves only
allows for use of the catch-and-weigh method. For this reason, the WaterSense
specification specifies ASTM F2324 for flow rate testing. It is now clear in the
specification that WaterSense is making an exception to require flow rate testing
in accordance with ASTM F2324 rather than ASME A112.18.1/CSA B125.1.

III.	Comments on Section 3.0: Water Efficiency
Requirements

Maximum Flow Rate Requirement

a. One commenter expressed support of the proposed maximum flow rate
requirement of 1.28 gallons per minute (gpm), stating that it is 20 percent less
than the Energy Policy Act (EPAct) of 2005 standard of 1.6 gpm.

Response: WaterSense thanks the commenter for supporting the maximum flow
rate requirement in the specification. Consistent with the WaterSense program's

4

September 19, 2013


-------
4

epa	Response to Public Comments Received on February 2013

WaterSense WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves

goals, labeled commercial PRSVs will be at least 20 percent more efficient than
standard models on the market.

IV. Comments on Section 4.0: Performance
Requirements

Minimum Spray Force Requirement

a. Thirteen commenters urged WaterSense to establish a new product category
and efficiency and performance provisions for ultra low-flow PRSVs. The
commenters suggested defining this category of PRSVs as those with a
maximum flow rate of 0.8 gallons per minute (gpm) at 60 pounds per square inch
(psi) and a minimum spray force of 4 ounces.

Eleven of these commenters noted that by eliminating ultra low-flow PRSVs from
the WaterSense specification, WaterSense could be potentially increasing
current water and energy consumption by 25 to 50 percent and would be
eliminating the range of choices currently available on the PRSV market. The
commenters noted that they regularly sell ultra low-flow PRSVs to some
commercial kitchens because not every application requires a higher flow rate
and higher spray force. Further, the commenters stated that the extensive testing
done in their industry provides measurable data regarding performance,
sanitation, employee safety and satisfaction, and water and energy usage of
specific spray valves.

One commenter noted that the draft specification does not account for ultra low-
flow applications where lower rates are needed for specific niche markets. In
jurisdictions where the WaterSense label is promulgated into law, the
WaterSense draft specification for PRSVs might inadvertently ban these ultra
low-flow products. This commenter pointed out that setting a 0.8 gpm maximum
for ultra low-flow PRSVs would yield a minimum of 50 percent flow rate reduction
from the federal 1.6 gpm requirement.

One commenter stated that its customers are highly satisfied with its PRSVs
offered, and they have come to depend on both ultra low-flow and low-flow
PRSVs. This commenter noted that not including provisions for ultra low-flow
designs with lower spray forces in the WaterSense specification will severely
impede the end users' ability to choose products that best suit their specific
needs and will also have a negative impact on water and energy conservation
efforts.

Response: WaterSense agrees that some ultra low-flow PRSVs are satisfactory
to end users and did not intend to exclude lower-flowing models from the
specification. To address these comments, WaterSense has modified the
specification to require a minimum spray force of 4 ounces-force (ozf).

5

September 19, 2013


-------
4

epa	Response to Public Comments Received on February 2013

WaterSense WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves

After reconsidering the user satisfaction and spray force data, considering the
public comments, and discussing this change with the project team, WaterSense
has determined that a minimum spray force of 4.0 ozf represents an important
threshold for positive user satisfaction and will result in more significant water
savings for food service establishments and the WaterSense program. Further,
commenters supporting the change to 4.0 ozf represent a wide selection of the
PRSV industry (e.g., restaurant distributors, manufacturers, trade associations),
and the commenters have demonstrated that there is user satisfaction among
valves with a minimum force of 4.0 ozf.

However, WaterSense is not modifying the specification to include two distinct
categories of PRSVs, as the commenters suggested. Instead, WaterSense will
maintain a minimum threshold level of performance that is now able to
accommodate ultra low-flow PRSVs that are suitable for a variety of end uses
and applications. In this manner, the WaterSense label will continue to provide a
simple, single-tiered symbol to help purchasers recognize products that are
water-efficient and perform as well or better than standard models on the market.
To further help purchasers choose products that best meet their needs for a
specific application, WaterSense requires that PRSV packaging and/or product
literature be marked with the maximum rated flow rate and the tested spray force.
WaterSense's intent is to label PRSVs based on a minimum level of
performance, not put a minimum bound on product flow rate.

Including Spray Force as a Performance Criterion

b. One commenter suggested that WaterSense remove the minimum spray force
requirement from the specification. The commenter stated that WaterSense's
rationale that "several users indicated low pressure (i.e., spray force) as a reason
for dissatisfaction" during its field study is not an appropriate justification for
adopting spray force as a performance criterion because the sample size of the
study was too small. In addition, the commenter noted that the marketplace is
capable of distinguishing acceptable performance criteria among different
available PRSV models on its own. The commenter noted that spray force only
has a 27 percent correlation to user satisfaction, which is not high enough to
determine that spray force is an appropriate performance criterion. The
commenter urged WaterSense to only include a maximum flow rate requirement,
or find another performance test with a minimum of 60 percent positive
correlation to user satisfaction.

Response: WaterSense thanks the commenter for this suggestion but has not
removed the minimum spray force requirement from the specification. Consistent
with the WaterSense program's goals, the label will continue to provide a symbol
of both product efficiency and performance. Performance is critical for ensuring
the integrity of the WaterSense brand and the longevity of water savings.

WaterSense recognizes that the field study was limited, but in some cases,
several users interviewed expressed dissatisfaction with some of the PRSVs

6

September 19, 2013


-------
4

epa	Response to Public Comments Received on February 2013

WaterSense WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves

tested. This feedback indicates that there is a need for a mechanism in the
market to differentiate products based on performance.

In addition, manufacturers, restaurant distributors, utilities offering product
rebates, and other trade associations commented on the draft specification and
indicated support for including spray force as the performance criteria for PRSVs
to earn the label. In addition, the project team and ASTM support the inclusion of
spray force as a performance criterion; in fact, ASTM recently revised the ASTM
F2324 Standard Test Method forPrerinse Spray Valves to include the new spray
force test. While WaterSense acknowledges that the correlation between user
satisfaction and spray force might be low, it was an order of magnitude higher
than the correlation between user satisfaction and the former tomato paste
cleanability performance test (required under the previous version of ASTM
F2324). Further, WaterSense is adjusting the minimum spray force requirement
to allow a wider variety of products, which have demonstrated satisfactory
performance to end users, to earn the label.

Spray Force Units

c.	One commenter noted that the correct nomenclature for force is ounces-force
(ozf) and grams-force (gramf) or Newton (N). This change would also provide
better agreement with the two-digit resolution requirement in Section 5.1.5. The
commenter suggested changing Section 4.1.1 as follows:

"The minimum spray force shall not be less than 5.0 ounces-force (ozf) (142
grams-force (gramf))."

OR

"The minimum spray force shall not be less than 5.0 ounces-force (ozf) (142
grams 1.4 Newton (1.4 N)))."

Response: WaterSense agrees that the units used for spray force should be
clarified in the specification. As such, WaterSense changed "ounces" to "ounces-
force" and "grams" to "grams-force."

Life Cycle Testing Requirement

d.	One commenter suggested only requiring PRSVs to perform for 150,000 cycles.
This commenter noted that WaterSense's justification for requiring 500,000
cycles and the underlying assumptions are arbitrary. The commenter commented
that ASME/CSA A112.18.1/CSA B125.1 has required 150,000 cycles for years
and inquired whether there is field data to support the change to 500,000 cycles.
The commenter also noted that the requirements in this specification are
minimum performance requirements. The commenter indicated that EPA's field
study showed a high rate of breakage but noted that there was no confirmation
that the PRSVs tested were certified to the ASME/CSA standard. The

7

September 19, 2013


-------
WaterSense

Response to Public Comments Received on February 2013
WaterSense® Draft Specification for Commercial Pre-Rinse Spray Valves

commenter also noted that the project team agreed that the increased life cycle
requirement would only apply to high-efficiency PRSVs.

Another commenter suggested removing the life cycle testing requirements
altogether. This commenter noted that there was minimal discussion about the
life cycle testing requirement in the project team and that the requirement was
suggested by only one manufacturer. The commenter also noted that there was
no testing done to ascertain how PRSVs would stand up to a requirement of
500,000 cycles, and there was no correlation among life cycle testing and user
satisfaction.

Response: WaterSense maintains its position that the specification needs to
require a higher level of life cycle testing than is currently required in ASME/CSA
A112.18.1/CSA B125.1. Of the 14 PRSV models tested during EPA's field study,
at least one sample of five of those models leaked or otherwise malfunctioned
during its three-week testing period. Of those five models, two were certified to
meet the life cycle requirement of 150,000 cycles in ASME/CSA A112.18.1/CSA
B125.1. As a result, WaterSense determined that a more stringent requirement
for life cycle testing is necessary to ensure product duration and the longevity of
water and energy savings.

However, after reviewing the concerns raised during the public comment period
and discussing the feasibility and basis for this requirement further with the
project team, WaterSense and the project team determined that the life cycle
testing requirement should be 250,000 cycles in the final specification. The
250,000 cycles represents a 67 percent increase over the current life cycle
testing for standard PRSVs and puts the requirements in line with some manually
operated fittings. In addition, EPA is clarifying that the life cycle testing
requirements in the specification only apply to products under consideration for
the label.

V. Comments on Section 5.0: Marking

Flow Rate Override

a. One commenter suggested adding the following provision to control flow rate
override:

"High-efficiency commercial pre-rinse spray valves shall not be packaged,
marked, or provided with instructions directing the user to an alternative water-
use setting that would override the maximum flow rate specified in Section 5.1.4.
Instructions related to the maintenance of the devices, including changing or
cleaning pre-rinse spray valve components, shall direct the user on how to return
the device to its intended maximum flow rate."

Response: The specification already addresses flow rate override through
provisions in Section 2.3 of the specification.

8

September 19, 2013


-------
WaterSense

Response to Public Comments Received on February 2013
WaterSense® Draft Specification for Commercial Pre-Rinse Spray Valves

Spray Force Units

b. One commenter suggested providing the spray force units in Newtons for better
agreement with the two-digit resolution requirement for marking the minimum
spray force in Section 5.1.5. Throughout the specification, metric conversions are
used, and the correct nomenclature for force is ounces-force (ozf) and grams-
force (gramf) or Newton (N). The commenter suggested the following change to
Section 5.1.5:

"The spray force marking shall be in ounces force (ozf) and Newton in two-digit
resolution (e.g., 5.0 ounces ozf (1.4 N))."

Response: WaterSense discussed the appropriate units for spray force with the
project team and determined that spray force should be marked in ounces-force
and grams-force, to ensure an appropriate conversion for those using the metric
system (see Section 5.1.5).

VI.	Comments on Appendix A: Draft ASTM F2324
Standard Test Method for Prerinse Spray Valves

Not Accepting Comments on the Draft Revised ASTM F2324 Test Method

a. One commenter noted that it was surprising that WaterSense was not taking
comments on the draft ASTM F2324 test method revisions and questioned if
WaterSense would accept whatever ASTM finalized. The commenter noted that
WaterSense should want to comment on the ASTM draft to ensure the final
document is acceptable for the specification's intent.

Response: WaterSense worked closely with ASTM through the development of
the F2324 test method and finds the final test method acceptable for its
purposes. Since the draft specification was released, the ASTM F2324 revisions
have been finalized and the test method is now fully incorporated by reference
into the final specification. The test method was developed through a consensus-
based process that allowed for adequate public consideration and input. Further,
WaterSense urged its stakeholders to comment directly on the test method
through the ASTM process.

VII.	General Comments on the Specification

General Specification Support

a. One commenter expressed its support for the draft specification, noting that it
offers a solid foundation for energy efficiency programs. The commenter noted
that qualifying PRSVs would result in significant energy and water savings at low
or no extra cost and are expected to perform similar to non-qualifying, higher-
flowing units. Testing can be done in a consistent and repeatable manner, and

9

September 19, 2013


-------
4

epa	Response to Public Comments Received on February 2013

WaterSense WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves

test results for a subset of the criteria indicate that several models made by
multiple manufacturers should be able to meet the specification criteria. The
commenter stated it is aware of several of its member organizations that plan to
consider adopting the specification as the basis for program promotion once it is
finalized.

Response: WaterSense thanks the commenter for these comments and its
support of the WaterSense program, specification development process, and
specification requirements. The final specification for commercial PRSVs is a
reflection of the hard work and dedication of a variety of stakeholders who
provided invaluable input throughout the process. In addition, WaterSense looks
forward to working with the commercial food service sector, energy and water
utilities, and other key stakeholders to help transform the PRSV market and
inform purchasing decisions that will result in significant water and energy
savings.

b. One commenter expressed dissatisfaction with WaterSense's specification

development process. The commenter was concerned about the transparency of
the specification development process, the scientific methods used to support
field study data collection, EPA's collection of industry input, and the validity of
the assumptions and calculations.

Response: WaterSense followed its established specification development
process to develop the commercial PRSV specification. The specification was
developed over a four-year period, during which WaterSense worked through the
ASME/CSA project team process (open to any interested party); coordinated with
ASTM; and collaborated with a variety of other interested stakeholders, including
manufacturers, utilities, testing laboratories, efficiency programs, purchasers and
specifiers, standards organizations, and government agencies.

In July 2009, WaterSense issued a Notice of Intent (NOI) outlining its outstanding
questions about the PRSV product category and requested industry and
stakeholder input on these outstanding issues. From late 2009 through 2012,
WaterSense collected data and further researched PRSVs. During this time,
WaterSense also conducted a field study to inform the specification development
process. The study scope for that research was reviewed by the project team
prior to field data collection. EPA shared all of its data and discussed its
conclusions with the project team prior to publishing the research report.

Following the field study, WaterSense worked with the project team and ASTM to
develop the specification criteria. The project team independently collected data
on flow rate and spray force to ensure test methods were repeatable and
reproducible.

Once the draft specification was released in February 2013, EPA provided a 60-
day public comment period and held a public meeting to gather input and ensure
transparency.

10

September 19, 2013


-------
4

epa	Response to Public Comments Received on February 2013

WaterSense WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves

VIII. Comments on the Specification Supporting
Documentation

Estimated Number of Pre-Rinse Spray Valves Nationwide

a.	One commenter urged WaterSense to increase its estimate of PRSVs in the
United States to ensure that the national water savings estimate is more
accurate. The commenter noted that the California Urban Water Conservation
Council estimates there are 175,000 PRSVs in California, which can be
extrapolated to 1.5 million PRSVs nationally. The commenter noted that if
WaterSense uses the estimate from the National Restaurant Association of
970,000 food service establishments, WaterSense should assume 1.5 PRSVs
per establishment.

Response: WaterSense agrees that it might have underestimated the size of the
PRSV market. WaterSense has changed its assumption of the number of PRSVs
per establishment to 1.5 and has updated calculations in the supporting
statement accordingly. This change is supported by EPA's observations during
the field study that several establishments had more than one spray valve. The
size of the market and estimated national water and energy savings now more
accurately represent the savings potential.

Estimated Annual Sales

b.	One commenter noted that WaterSense's estimate of five years for a PRSVs
useful life is too long. The commenter noted that PRSVs only last one to one and
a half years. The commenter requested that WaterSense update the estimate for
annual sales of new PRSVs per year in its supporting statement based on a
useful life of one to one and a half years.

Response: WaterSense is confident in its estimate of five years for a PRSVs
useful life. The five-year useful life was determined based on conversations with
manufacturers, input from the project team, input from the Plumbing
Manufacturers International (PMI), and other research conducted on this product
category. The assumption is also supported by the field study conducted in early
2010, in which EPA found several existing PRSVs that were non-EPAct
compliant (approximately four years after EPAct requirements went into effect).
In addition, a five-year useful life provides a conservative estimate of annual
sales and potential national water and energy savings.

Average Use Time per Day Used in Life Cycle, Water, and Energy Savings

Calculations

c.	One commenter suggested that a use time of three hours per day is a more
appropriate estimate of daily use time than WaterSense's estimate of 64 minutes
per day. The commenter noted that "manufacturer input" upon which

11

September 19, 2013


-------
4

epa	Response to Public Comments Received on February 2013

WaterSense WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves

WaterSense's estimate is based is not an appropriate way to establish average
daily use time. The commenter suggested getting input from restaurant operators
and restaurant kitchen equipment service companies.

Response: WaterSense is confident in its estimate that PRSVs are used 64
minutes per day, based not on manufacturer input but rather on a weighted
average use time calculated from seven field studies, including EPA's own field
study. These studies include:

•	Tso, Bing, P.E. and John Koeller, P.E. December 1, 2005. Pre-Rinse
Spray Valve Programs: How Are They Really Doing? Page 8. The report
references PRSV use-time results from five studies, including:

o California Urban Water Conservation Council's Phase 1 and

Phase 2 programs
o Veritec Consulting's Region of Waterloo study
o Pilot test conducted by Seattle Public Utilities
o Pilot test done by Puget Sound Energy

•	Veritec Consulting, Inc. December 2005. City of Calgary Pre-Rinse Spray
Valve Pilot Study Final Report.

•	EPA's WaterSense program. March 31, 2011. Pre-Rinse Spray Valves
Field Study Report. Appendix D.

User Satisfaction Data

d.	One commenter expressed concern about WaterSense's draft supporting
statement that said "users were generally less satisfied with PRSVs that flow at
less than 1.0 gpm." The commenter indicated that this statement is false, since
some valves with flow rates less than 1.0 gpm are satisfactory to users. Further,
the commenter stated that manufacturers have the capability to design PRSVs
with flow rates less than 1.0 gpm that perform well.

Response: WaterSense has clarified in its supporting statement that the field
study indicated there was correlation between flow rate and user satisfaction, not
that users were generally less satisfied with PRSVs with flow rates less than 1.0
gpm. In addition, WaterSense is acknowledging the merit of this comment
through the change to the minimum spray force requirement to 4.0 ozf. With this
change, WaterSense recognizes that lower-flowing PRSVs have a valuable place
in the market and that manufacturers have the ability to market PRSVs with flow
rates less than 1.0 gpm that can achieve high user satisfaction. WaterSense
continues to provide flexibility and encourage manufacturers to make and
advertise products that are even more efficient or higher performing than the
thresholds established by the specification.

Potential Savings and Cost-Effectiveness

e.	One commenter noted that WaterSense grossly underestimates savings. The
commenter indicated that WaterSense should account for the total amount of
water and energy it takes to produce a gallon at the end-use spigot, rather than

12

September 19, 2013


-------
4

epa	Response to Public Comments Received on February 2013

WaterSense WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves

only accounting for the water and energy savings at the end-use spigot. This
includes losses incurred and energy used in collection, transportation, treatment,
and distribution of water, as well as the water used at the end-use spigot. The
commenter noted that these savings could be two to 10 times the savings
calculated from switching from a 1.6 gpm to a 1.28 gpm PRSV at the end use
only. The commenter also noted that WaterSense should account for the cost of
sewage in its cost-effectiveness calculations.

Response: WaterSense recognizes that there might be ancillary benefits to the
program, including the reduction of water and energy required to provide water
and treat wastewater. However, the water and energy savings presented in the
supporting statement are intended to provide food service establishments with
information to inform a purchasing decision and as a result, estimate the direct
benefits they can realize.

WaterSense's cost-savings estimates do include avoided wastewater costs for
these food service establishments. WaterSense uses the average price of water
supply and wastewater treatment (i.e., $9.30 per 1,000 gallons) in its cost-
effectiveness calculations, which are documented in Appendix A of the
WaterSense Specification for Pre-Rinse Spray Valves Supporting Statement.

f.	One commenter noted that calculating water savings by assuming all PRSVs are
1.6 gpm models underestimates the true savings. The commenter indicated that
EPA's field study demonstrates an average water use of more than 2 gpm from
existing PRSVs tested and suggested WaterSense use that number as the
standard flow rate of existing PRSVs.

Response: WaterSense uses 1.6 gpm as the standard PRSV flow rate to provide
conservative water, energy, and cost-savings estimates to those making
purchasing decisions. Since 1.6 gpm is the maximum flow rate required by EPAct
of 2005 (i.e., 1.6 gpm is the current fixture standard), it is the maximum flow rate
of products currently allowed for sale on the market.

ENERGY STAR® Support

g.	One commenter indicated that it seems that ENERGY STAR does not support
WaterSense's methodology in arriving at the performance criteria included in the
specification. The commenter asked that WaterSense fully disclose the opinions
of ENERGY STAR about the WaterSense process, conclusions, and
recommendations for PRSVs.

Response: WaterSense and ENERGY STAR have coordinated at each stage of
the specification development process, and ENERGY STAR has expressed
support for all of the specification's criteria. Upon the release of the draft
specification, WaterSense and ENERGY STAR made a collaborative decision
that PRSVs will only be eligible for the WaterSense label. However, ENERGY
STAR will continue to play an active role in promoting the WaterSense labeled

13

September 19, 2013


-------
4

epa	Response to Public Comments Received on February 2013

WaterSense WaterSense Draft Specification for Commercial Pre-Rinse Spray Valves

PRSVs, because they offer significant water and energy savings. This decision
provides a streamlined process and ensures that undue burden is not placed
upon manufacturers seeking to label their products, since the WaterSense and
ENERGY STAR have slightly different certification schemes and requirements.

14

September 19, 2013


-------