ENERGY STAR

ENERGY STAR Qualified Homes

National Attached Homes Builder Option Package

The requirements for the National Attached Homes Builder Option Package specified below apply to townhomes,
apartments, and condominiums that are subject to the residential code of the jurisdiction in which they are built1.

To qualify as ENERGY STAR using this BOP, a home must meet the requirements specified, be verified and field-tested
in accordance with the HERS Standards by a RESNET-accredited Provider, and meet all applicable codes.

Incorporate All Requirements in this Section

Minimum HVAC
Requirements

(where provided)

•	13 SEER A/C2 and 80 AFUE gas furnace; OR

•	13 SEER A/C2 and 80 AFUE boiler; OR

•	13 SEER A/C2 and 80 AFUE oil furnace; OR

•	13 SEER/7.7 HSPF heat pump2 3

Thermostat3

ENERGY STAR qualified thermostat (except for zones with radiant heat)

Ductwork

Leakage 4: < 4 cfm to outdoors /100 sq. ft.; AND
R-6 min. insulation on ducts in unconditioned spaces 5

Envelope

•	Infiltration 6 7 (ACH50): 7 in CZ's 1-2 | 6 in CZ's 3-4 | 5 in CZ's 5-7 | 4 in CZ 8; AND

•	Insulation levels that meet or exceed the 2004 IRC8; AND

•	Completed Thermal Bypass Inspection Checklist9

Windows

ENERGY STAR qualified windows or better (additional requirements for CZ2 and CZ4)10 11 12

Water Heater 13

Gas(EF): 40 Gal = 0.61 | 60 Gal = 0.57 | 80 Gal = 0.53
Electric (EF): 40 Gal = 0.93 | 50 Gal = 0.92 | 80 Gal = 0.89

14

Oil or Gas : Integrated with space heating boiler

Lighting and
Appliances 15 16

Five or more ENERGY STAR qualified appliances, light fixtures,
ceiling fans equipped with lighting fixtures, and/or ventilation fans

In Addition, Pick One of the Four Options Below



Hot Climates 17

(2004 IRC Climate Zones 1,2,3)

Mixed and Cold Climates 17

(2004 IRC Climate Zones 4,5,6,7,8)

Option 1:

HVAC
Equipment
(Where Provided)

Right-Sized:

•	ENERGY STAR qualified A/C
(14 SEER/11.5 EER)\ OR

•	ENERGY STAR qualified heat pump
(14 SEER/11.5 EER/8.2 HSPF)

•	ENERGY STAR qualified gas furnace
(90 AFUE): OR

•	ENERGY STAR qualified heat pump 18
(See Note 18 for specifications)] OR

•	ENERGY STAR qualified boiler
(85 AFUE)\ OR

•	ENERGY STAR qualified oil furnace
(85 AFUE)

Option 2:

1 Q

Lighting and/or
Windows

• 75% ENERGY STAR Lighting

•	75% ENERGY STAR Lighting; AND

•	Wndow U-value: 0.30 / SHGC: 0.35

Option 3:

Lighting19,
Windows20,
and/or Fan Motor

•	50% ENERGY STAR Lighting; AND

•	Homes with 1 detached wall: < 10% WFA

•	Homes with 2 detached walls: < 12% WFA

•	Homes with 3 detached walls: < 14% WFA

•	50% ENERGY STAR Lighting; AND

•	Furnace with two-stage burner and fan
motor with at least two speeds21; AND

•	Homes with 1 detached wall: < 10% WFA

•	Homes with 2 detached walls: < 12% WFA

•	Homes with 3 detached walls: < 14% WFA

Option 4:

Ductwork

• All ducts and air handling equipment
located in conditioned space

• All ducts and air handling equipment
located in conditioned space


-------


ENERGY STAR

ENERGY STAR Qualified Homes
National Attached Homes BOP Notes

Note: Due to the unique nature of some state codes and/or climates, EPA has agreed to allow regionally-developed definitions of ENERGY STAR in
California, Hawaii, Guam, and the Pacific Northwest to continue to define program requirements. The States of Montana and Idaho may use either the
requirements of the national program or the regionally-developed program in the Pacific Northwest.

1.	Most residential building codes apply to structures up to three stories tall. Units in four- and five-story multi-family buildings may
qualify for ENERGY STAR under this BOP if they are permitted as residential structures by the local building department. Multi-
family units that are located on top of commercial spaces (e.g., retail, restaurant, etc.) may be qualified as ENERGY STAR under
this BOP even if the structure is permitted as commercial, as long as: 1) the entire structure is five stories or less; and 2) the space
conditioning and water heating systems are not shared between the residential and commercial spaces.

2.	Cooling equipment shall be sized according to the latest editions of ACCA Manuals J and S, ASHRAE 2001 Handbook of
Fundamentals, or an equivalent procedure. Maximum oversizing limit for air conditioners and heat pumps is 15% (with the
exception of heat pumps in Climate Zones 5-8, where the maximum oversizing limit is 25%). The following operating conditions
shall be used in the sizing calculations and verified where reviewed by the rater:

Outdoor temperatures shall be the 99.0% and 1.0% design temperatures as published in the ASHRAE Handbook of Fundamentals
for the home's location or most representative city for which design temperature data are available; Indoor temperatures shall be
75 F for cooling and 70 F for heating; Infiltration rate shall be selected as "tight", or the equivalent term.

In specifying equipment, the next available size may be used. In addition, indoor and outdoor coils shall be matched in accordance
with ARI standards.

3.	Homes with heat pumps in Climate Zones 6, 7, and 8 cannot be qualified using this BOP, but can earn the label using the
ENERGY STAR Attached Housing Performance Path requirements. In homes with heat pumps that have programmable
thermostats, the thermostat must have "Adaptive Recovery" technology to prevent the excessive use of electric back-up heating.

4.	Ducts must be sealed and tested to be < 4 cfm to outdoors /100 sq. ft. of conditioned floor area, as determined and documented
by a RESNET-certified rater using a RESNET-approved or equivalent ASTM-approved testing protocol. Duct leakage testing can
be waived if all ducts and air handling equipment are located in conditioned space (i.e., within the home's air and thermal barriers)
AND the envelope leakage has been tested to be < 3 ACH50 OR < 0.25 CFM 50 per sq. ft. of the building envelope.

5.	EPA recommends, but does not require, locating ducts within the home's conditioned space (i.e., inside the air and thermal
barriers), and using a minimum of R-4 insulation for ducts inside the conditioned space to prevent condensation.

6.	Envelope leakage must be determined by a RESNET-certified rater using a RESNET-approved testing protocol.

7.	To ensure consistent exchange of indoor air, whole-house mechanical ventilation is recommended, but not required.

8.	Insulation levels of a home must meet or exceed Sections N1102.1 and N1102.2 of the 2004 IRC. These sections allow for
compliance to be determined by meeting prescriptive insulation requirements, by using U-factor alternatives, or by using a total UA
alternative. These sections also provide guidance and exceptions that may be used. However, note that the U-factor for steel-
frame envelope assemblies addressed in Section N1102.2.4 shall be calculated using the ASHRAE zone method or a method
providing equivalent results, and not a series-parallel path calculation method as is stated in the code. Additionally, Section

N1102.2.2, which allows for the reduction of ceiling insulation in space constrained roof/ceiling assemblies, shall be limited to 500
sq. ft. or 20% of ceiling area, whichever is less. In all cases, insulation shall be inspected to Grade I installation as defined in the
RESNET Standards by a RESNET-certified rater. Note that the fenestration requirements of the 2004 IRC do not apply to the
fenestration requirements of the National Attached Homes Builder Option Package. Therefore, if UA calculations are performed,
they must use the IRC requirements (with the exception of fenestration) plus the fenestration requirements contained in the
national BOP. For more information, refer to the "Codes and Standards Information" document.

9.	The Thermal Bypass Inspection Checklist must be completed for homes to earn the ENERGY STAR label. The Checklist requires
visual inspection of framing areas where air barriers are commonly missed and inspection of insulation to ensure proper alignment
with air barriers, thus serving as an extra check that the air and thermal barriers are continuous and complete.

10.	All windows and skylights must be ENERGY STAR qualified or meet all specifications for ENERGY STAR qualified windows.
Windows in Climate Zones 2 and 4 must exceed ENERGY STAR specifications (CZ 2: U-value < 0.55 and SHGC < 0.35; CZ 4:
U-value < 0.40 and SHGC < 0.45). Visit www.enerqvstar.qov/windows for more information on ENERGY STAR qualified windows.

11.	All decorative glass and skylight window area counts toward the total window area to above-grade conditioned floor area (WFA)
ratio. For homes with a WFA ratio >18%, the following additional requirements apply:

a.	In IRC Climate Zones 1, 2, and 3, an improved window SHGC is required, and is determined by:

Required SHGC = [0.18 / WFA] x [ENERGY STAR SHGC]

Where the ENERGY STAR SHGC is the minimum required SHGC of the climate-appropriate window specified in this BOP.

b.	In IRC Climate Zones 4, 5, 6, 7, and 8, an improved window U-Value is required, and is determined by:

Required U-Value = [0.18 / WFA] x [ENERGY STAR U-Value]

Where the ENERGY STAR U-Value is the minimum required U-Value of the climate-appropriate window specified in this BOP.

12.	Up to 0.75% WFA may be used for decorative glass that does not meet ENERGY STAR requirements. For example, a home with
total above-grade conditioned floor area of 2,000 sq. ft. may have up to 15 sq. ft. (0.75% of 2,000) of decorative glass.

13.	To determine domestic hot water (DHW) EF requirements for additional tank sizes, use the following equations:

Gas DHW EF > 0.69 - (0.002 x Tank Gallon Capacity); Electric DHW EF > 0.97 - (0.001 x Tank Gallon Capacity).


-------
ENERGY STAR

ENERGY STAR Qualified Homes
National Attached Homes BOP Notes

14.	In homes with gas or oil hydronic space heating, water heating systems must have an efficiency > 0.78 EF. This may be met
through the use of an instantaneous water heating system or an indirect storage system with a boiler that has a system efficiency >
85 AFUE. Homes with tankless coil hot water heating systems cannot be qualified using this BOP, but can earn the label using the
ENERGY STAR Attached Housing Performance Path requirements.

15.	Any combination of ENERGY STAR qualified products listed may be installed to meet this requirement. ENERGY STAR qualified
ventilation fans include range hood, bathroom, and inline fans. ENERGY STAR qualified lighting fixtures installed in the following
locations shall not be counted: storage rooms (e.g., closets, pantries, sheds), or garages. Eligible appliances include ENERGY
STAR qualified refrigerators, dish washers, and washing machines. Further efficiency and savings can be achieved by installing
ENERGY STAR qualified products, in addition to those required (e.g., additional lighting, appliances, etc.).

16.	Efficient lighting fixtures represent a significant opportunity for persistent energy savings and a meaningful way to differentiate
ENERGY STAR qualified homes from those meeting minimum code requirements. To learn more about the EPA's Advanced
Lighting Package (ALP), refer to www.eneravstar.gov/homes.

17.	The appropriate climate zone shall be determined by the 2004 International Residential Code (IRC), Figure N1101.2.

18.	In order to fulfill the efficient HVAC requirements of Option 1, homes in Climate Zones 1, 2, and 3 with heat pumps must have an
HSPF > 8.2. Homes in Climate Zones 4 and 5 with heat pumps must have an HSPF > 8.5, which exceeds the ENERGY STAR
minimum of 8.2 HSPF, in order to fulfill the requirements of this option. Homes with heat pumps in Climate Zones 6, 7, and 8
cannot be qualified using this BOP, but can earn the label using the ENERGY STAR Attached Housing Performance Path
requirements. In homes with heat pumps that have programmable thermostats, the thermostat must have "Adaptive Recovery"
technology to prevent the excessive use of electric back-up heating.

19.	Up to 20% of the lamps (i.e., light bulbs) installed may be ENERGY STAR qualified screw-in compact fluorescent light bulbs. The
remainder must be ENERGY STAR qualified hard-wired fixtures.

20.	Window to Floor Area (WFA) ratio is the calculated by dividing the gross window area by the total conditioned floor area of the
home.

21.	Gas furnaces and oil furnaces must be equipped with a two-stage burner and a fan motor with two or more speeds. Two-speed,
multi-speed, and variable-speed fan motors are all acceptable.


-------